Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:06
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2023-10-16 09:06:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 33790.54 | 729.50 | 729.50 |
Net Site Energy | 33790.54 | 729.50 | 729.50 |
Total Source Energy | 83347.78 | 1799.38 | 1799.38 |
Net Source Energy | 83347.78 | 1799.38 | 1799.38 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3325.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 701.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7167.51 | 0.00 | 0.00 |
Interior Lighting | 2028.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3183.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1177.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 277.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 150.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2642.93 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 771.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 22526.12 | 4096.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7167.51 | 0.00 | 4923.10 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3325.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 701.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7167.51 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2028.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ComputerHVAC | 1274.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 1177.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 277.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 150.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2642.93 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 771.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3325.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 701.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7167.51 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2028.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 330.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 3183.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 1177.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 277.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 150.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2642.93 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 771.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 49.81 | 88.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.74 | 0.00 | 0.11 |
Other | 385.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 486.31 | 88.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.74 | 0.00 | 0.11 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 49.81 | 88.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.74 | 0.00 | 0.11 |
Other | 385.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 486.31 | 88.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.74 | 0.00 | 0.11 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 22526.123 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 22526.123 | 100.00 |
Total On-Site and Utility Electric Sources | 22526.123 | 100.00 |
Total Electricity End Uses | 22526.123 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 4923.10 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 4923.10 | 100.00 |
Total Water End Uses | 4923.10 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 117.83 |
Time Setpoint Not Met During Occupied Cooling | 127.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionDistrictHeatingCoolingMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:06 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.8895 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.8895 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 5.9168 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 5.9168 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.8895 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8895 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.8895 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8895 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.8895 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.9168 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.9168 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.8190 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
Time of Peak | 08-AUG-15:39 | 09-JAN-07:19 | - | - | - | - | - | - | - | - | 07-AUG-15:00 | 01-FEB-00:30 | 25-JUL-11:50 |
Heating | 0.00 | 2299529.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 | 0.00 |
Cooling | 199313.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370300.48 | 0.00 | 0.00 |
Interior Lighting | 171235.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 147344.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 217601.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 45013.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 39494.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 28720.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1598375.19 | 2328249.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370300.48 | 14.26 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 | 0.00 |
Boiler | 0.00 | 2299529.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 199313.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370300.48 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 171235.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3372.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ComputerHVAC | 64537.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 217601.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 45013.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 39494.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 28720.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3604.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Cooling | 2222.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7566.50 | 0.00 |
Interior Lighting | 6424.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1048.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10081.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3728.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 877.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 477.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 836.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 71340.23 | 4441.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7566.50 | 0.01 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 77.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 47.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.35 | 0.00 |
Interior Lighting | 138.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 22.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 217.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 80.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 18.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 10.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1540.15 | 95.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.35 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 77.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 47.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.35 | 0.00 |
Interior Lighting | 138.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 22.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 217.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 80.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 18.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 10.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1540.15 | 95.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.35 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.51 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.550797 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.27 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.537081 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.98 | 0.318190 | 0.324000 | 1.94 | 0.848507 | 0.500000 | 0.001197 | 0.000213 | 1.94 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 55.89 | 0.340335 | 0.339000 | 18.95 | 0.907561 | 0.500000 | 0.001119 | 0.004310 | 18.95 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.49 | 0.346306 | 0.356000 | 1.96 | 0.923482 | 0.500000 | 0.001100 | 0.000977 | 3.80 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.957073 | 0.249532 | 0.254000 | 0.243097 | 0.665419 | 0.500000 | 0.001527 | 0.000161 | 0.627377 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.23 | 0.124930 | 0.200000 | 0.246386 | 0.333147 | 0.500000 | 0.003050 | 0.000111 | 0.432081 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.54 | 0.155015 | 0.200000 | 0.308132 | 0.413374 | 0.500000 | 0.002458 | 0.000179 | 0.696502 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.55 | 0.099151 | 0.200000 | 0.310446 | 0.300000 | 0.500000 | 0.003843 | 0.000090 | 0.349233 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.81 | 0.271158 | 0.270000 | 2.38 | 0.723089 | 0.500000 | 0.001405 | 0.002258 | 8.81 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 12.99 | 0.118471 | 0.200000 | 2.60 | 0.315922 | 0.500000 | 0.003216 | 0.001498 | 5.84 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 15.32 | 0.155908 | 0.200000 | 3.06 | 0.415755 | 0.500000 | 0.002444 | 0.002287 | 8.92 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 13.86 | 0.111046 | 0.200000 | 2.77 | 0.300000 | 0.500000 | 0.003431 | 0.001462 | 5.70 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.18 | 0.202870 | 0.242000 | 0.284884 | 0.540988 | 0.500000 | 0.001878 | 0.000302 | 1.18 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.30 | 0.118097 | 0.200000 | 0.260641 | 0.314926 | 0.500000 | 0.003226 | 0.000199 | 0.776225 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.66 | 0.143778 | 0.200000 | 0.332215 | 0.383408 | 0.500000 | 0.002650 | 0.000305 | 1.19 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.48 | 0.103904 | 0.200000 | 0.296244 | 0.300000 | 0.500000 | 0.003667 | 0.000198 | 0.773010 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 24329.76 | 0.000213 | 512.01 |
CORE_MID VAV BOX REHEAT COIL | 492660.63 | 0.004310 | 12358.55 |
CORE_TOP VAV BOX REHEAT COIL | 111644.35 | 0.000977 | 2945.83 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18400.30 | 0.000161 | 485.32 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12670.65 | 0.000111 | 334.18 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 20423.58 | 0.000179 | 538.64 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10246.20 | 0.000090 | 270.30 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 258142.90 | 0.002258 | 6806.69 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 171248.80 | 0.001498 | 4515.38 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 261402.25 | 0.002287 | 6892.57 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 167108.37 | 0.001462 | 4406.27 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 34490.74 | 0.000302 | 909.29 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 22741.82 | 0.000199 | 599.54 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 34897.49 | 0.000305 | 920.01 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 22647.61 | 0.000198 | 597.06 |
VAV_BOT WITH REHEAT HEATING COIL | 105624.68 | 0.000924 | 1552.37 |
VAV_MID WITH REHEAT HEATING COIL | 1074744.71 | 0.009402 | 15383.52 |
VAV_TOP WITH REHEAT HEATING COIL | 104881.90 | 0.000918 | 1557.33 |
CAV_BAS HEATING COIL | 268429.26 | 0.002348 | 5691.92 |
Design Size Maximum Heating Air Flow Rate [m3/s] | Design Size Maximum Cooling Air Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT | 0.338402 | 24.33 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.63 | 3.04 | 11.26 | 3.18 | 9.73 | 9.73 | 0.300000 | 0.326967 | 9.73 |
VAV_MID WITH REHEAT | 53.43 | 29.76 | 106.86 | 45.04 | 89.92 | 89.92 | 0.300000 | 0.500867 | 89.92 |
VAV_TOP WITH REHEAT | 5.56 | 3.13 | 11.12 | 7.72 | 10.04 | 10.04 | 0.300000 | 0.768857 | 10.04 |
CAV_BAS | 5.51 | 5.51 | 5.51 | 5.51 | 5.51 | 5.51 | 1.00 | 1.00 | 5.51 |
AIRLOOP DATACENTER BOT | 0.550797 | 0.550797 | 0.550797 | 0.550797 | 0.550797 | 0.550797 | 1.00 | 1.00 | 0.550797 |
AIRLOOP DATACENTER MID | 5.27 | 5.27 | 5.27 | 5.27 | 5.27 | 5.27 | 1.00 | 1.00 | 5.27 |
AIRLOOP DATACENTER TOP | 0.537081 | 0.537081 | 0.537081 | 0.537081 | 0.537081 | 0.537081 | 1.00 | 1.00 | 0.537081 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.73 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 89.92 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.04 | |
CAV_BAS_OA_CONTROLLER | 5.51 | |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.550797 | 0.015633 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.27 | 0.156328 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.537081 | 0.015633 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.51 | 6.67 | 10.68 | 0.007087 | 0.007000 | 167452.84 | 0.007124 | 9.73 |
VAV_MID WITH REHEAT COOLING COIL | 26.79 | 6.67 | 10.67 | 0.007081 | 0.007000 | 1573216.64 | 0.066928 | 89.92 |
VAV_TOP WITH REHEAT COOLING COIL | 26.39 | 6.67 | 10.68 | 0.007083 | 0.007000 | 171295.37 | 0.007287 | 10.04 |
CAV_BAS COOLING COIL | 26.11 | 6.67 | 11.22 | 0.007263 | 0.007000 | 91921.22 | 0.003911 | 5.51 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.73 |
VAV_MID WITH REHEAT FAN | 89.92 |
VAV_TOP WITH REHEAT FAN | 10.04 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007124 | 0.000067 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000924 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.066928 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.009402 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.007287 | 0.000065 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000918 | |
CAV_BAS_COOLC_CONTROLLER | 0.003911 | 0.000122 |
CAV_BAS_HEATC_CONTROLLER | 0.002348 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.51 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.550797 | 10177.41 | 5787.06 | 0.000249 |
AIRLOOP DATACENTER MID COOLING COIL | 5.27 | 97434.05 | 55390.68 | 0.002386 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.537081 | 9925.99 | 5643.37 | 0.000243 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.550797 | 0.550797 | 0.550797 | 0.550797 | 10177.41 | 10177.41 | 1118.34 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.27 | 5.27 | 5.27 | 5.27 | 97434.05 | 97434.05 | 11183.41 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.537081 | 0.537081 | 0.537081 | 0.537081 | 9925.99 | 9925.99 | 1118.34 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.550797 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.27 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.537081 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT HEATING COIL | 0.550797 | 10177.41 | 0.000249 |
AIRLOOP DATACENTER MID HEATING COIL | 5.27 | 97434.05 | 0.002386 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.537081 | 9925.99 | 0.000243 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1118.34 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 11183.41 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1118.34 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.085250 | 17392.92 | |
HEATSYS1 PUMP | 0.028141 | 8391.05 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.085250 | 10.23 |
HEATSYS1 | 0.028141 | 3.38 |
COOLSYS1_SUPPLY | 0.085250 | 10.23 |
SINGLE WATER PLANT LOOP | 0.002878 | 0.345418 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.085250 | 0.085250 | 357836.80 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3216735.99 | 3216735.99 | 0.028141 |
CENTRAL BOILER | 118568.89 | 118568.89 | 0.002878 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.085250 | 12041.71 |
PLANT CIRC PUMP | 0.002878 | 726.89 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.085250 | 0.042911 | 1009797.79 | 1015943.93 | 0.050766 |
COOLSYS1 CHILLER2 | 0.085250 | 0.042911 | 1009797.79 | 1015943.93 | 0.050766 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.002878 | 35644.39 | 18388.84 | 17822.20 | 1996.20 | 5720.05 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.101533 | 12.18 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.101533 | 30276.75 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 40.65 | 1206897.55 | 8.13 | 150862.19 |
TOWERWATERSYS COOLTOWER 2 | 40.65 | 1206897.55 | 8.13 | 150862.19 |
Design Water Flow Rate [m3/s] Equipment # 45 | |
WSHPPLANT OPERATION SCHEME | 0.052220 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.889 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.731 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.889 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.313 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16369.361 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16369.361 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4615.459 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4615.459 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.147 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.072 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.485 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7043 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7653 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5060 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.18777991E-14 | 0.39318316E-16 | -0.13945218E-09 | -0.53504997E-17 |
51 | 8 | 0.20428582E-07 | 0.15263370E-12 | 0.36243033E-03 | -0.23227999E-09 |
52 | 7 | -0.11782580E-01 | 0.80534805E-08 | -0.22424787E-01 | 0.13397222E-03 |
53 | 6 | 0.39287835 | 0.28244099E-05 | 0.46145507 | -0.46007477E-02 |
54 | 5 | -5.0688419 | 0.10619431E-03 | -4.3595097 | 0.61674563E-01 |
55 | 4 | 32.464389 | 0.87416084E-03 | 21.120657 | -0.41497362 |
56 | 3 | -110.08041 | 0.19158287E-02 | -54.991947 | 1.4986409 |
57 | 2 | 195.99541 | 0.10830235E-02 | 77.295382 | -2.8826816 |
58 | 1 | -170.74495 | 0.11614893E-03 | -55.086664 | 2.7382339 |
59 | 0 | 57.057407 | 0.66454694E-06 | 15.586789 | |
60 | 9 | -0.35772101E-15 | 0.35300796E-16 | -0.14299885E-09 | 0.43432634E-17 |
61 | 8 | 0.20929462E-07 | 0.14329262E-12 | 0.36779278E-03 | -0.23797519E-09 |
62 | 7 | -0.11942934E-01 | 0.75175974E-08 | -0.22655780E-01 | 0.13579551E-03 |
63 | 6 | 0.39723595 | 0.26304111E-05 | 0.46517473 | -0.46521131E-02 |
64 | 5 | -5.1113728 | 0.98704798E-04 | -4.3881162 | 0.62201922E-01 |
65 | 4 | 32.652551 | 0.81106559E-03 | 21.232557 | -0.41747184 |
66 | 3 | -110.48086 | 0.17747443E-02 | -55.213214 | 1.5044261 |
67 | 2 | 196.39242 | 0.10018625E-02 | 77.498162 | -2.8889858 |
68 | 1 | -170.89164 | 0.10730575E-03 | -55.145342 | 2.7408049 |
69 | 0 | 57.057407 | 0.61309336E-06 | 15.576862 | |
70 | 9 | 0.62620750E-15 | 0.53459335E-16 | -0.12331227E-09 | -0.46720721E-17 |
71 | 8 | 0.18149323E-07 | 0.19273772E-12 | 0.33743729E-03 | -0.20636407E-09 |
72 | 7 | -0.11033179E-01 | 0.10459398E-07 | -0.21344557E-01 | 0.12545125E-03 |
73 | 6 | 0.37251059 | 0.37098382E-05 | 0.44401761 | -0.43606628E-02 |
74 | 5 | -4.8700128 | 0.14084247E-03 | -4.2251796 | 0.59209231E-01 |
75 | 4 | 31.584523 | 0.11694623E-02 | 20.594689 | -0.40329204 |
76 | 3 | -108.20727 | 0.25827026E-02 | -53.951706 | 1.4715810 |
77 | 2 | 194.13760 | 0.14699268E-02 | 76.342983 | -2.8531817 |
78 | 1 | -170.05820 | 0.15862972E-03 | -54.812808 | 2.7261979 |
79 | 0 | 57.057407 | 0.91374417E-06 | 15.634538 | |
80 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
81 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
82 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
83 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
84 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
85 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
86 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
87 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
88 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
89 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
90 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
91 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
92 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
93 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
94 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
95 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
96 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
97 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
98 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
99 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
100 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
101 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
102 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
103 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
104 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
105 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
106 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
107 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
108 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
109 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
110 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
111 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
112 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
113 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
114 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
115 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
116 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
117 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
118 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
119 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
120 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
121 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
122 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
123 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
124 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
125 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
126 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
127 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3425_SHGC_EAST_0.38 | 35 | 1 | VerySmooth | 1.946 | 1.946 | 1.000 | 0.381 | ||
2 | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | 36 | 1 | VerySmooth | 1.946 | 1.946 | 1.000 | 0.381 | ||
3 | WINDOW_U_0.3425_SHGC_WEST_0.38 | 37 | 1 | VerySmooth | 1.946 | 1.946 | 1.000 | 0.381 | ||
4 | WINDOW_U_0.3425_SHGC_NORTH_0.38 | 38 | 1 | VerySmooth | 1.946 | 1.946 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.81926E-002 | 0.29373 | 0.50259 | 0.50259 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11205 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.81926E-002 | 0.29373 | 0.50259 | 0.50259 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11205 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.81926E-002 | 0.29373 | 0.50259 | 0.50259 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11205 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.81926E-002 | 0.29373 | 0.50259 | 0.50259 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11205 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 4.570E-002 | 1.458E-004 | 2.193E-004 | 0.191 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.047E-002 | 1.509E-004 | 2.214E-004 | 0.198 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 4.570E-002 | 1.458E-004 | 2.193E-004 | 0.191 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.047E-002 | 1.509E-004 | 2.214E-004 | 0.198 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 4.570E-002 | 1.458E-004 | 2.278E-004 | 0.191 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.047E-002 | 1.509E-004 | 2.278E-004 | 0.198 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 4.570E-002 | 1.458E-004 | 2.278E-004 | 0.191 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.047E-002 | 1.509E-004 | 2.278E-004 | 0.198 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 4.570E-002 | 1.458E-004 | 2.278E-004 | 0.191 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.047E-002 | 1.509E-004 | 2.278E-004 | 0.198 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 4.570E-002 | 1.458E-004 | 2.278E-004 | 0.191 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.047E-002 | 1.509E-004 | 2.278E-004 | 0.198 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 6.769E-002 | 1.900E-005 | 2.278E-004 | 5.609E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 6.769E-002 | 1.900E-005 | 2.278E-004 | 5.609E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 6.769E-002 | 1.900E-005 | 1.754E-005 | 5.609E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2080E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2099E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.8307E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.8323E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.3533E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3545E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.8674E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8681E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2510E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3756E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.8669E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.9753E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.3837E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4734E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.8859E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9330E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1271 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7555E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1460 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.0393E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.0688E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.9183E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.9234E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3771E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2609E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4286E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.8779E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.0346E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.3919E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5049E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.8864E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9344E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2079E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2101E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.8306E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.8325E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.3533E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3548E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.8673E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8680E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6904E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0911E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6178E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0891E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0237E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1501E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1954E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2279E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6178E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8669E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5421E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7379E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5210E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3538E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0350E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5085E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5627E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.6575E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4491E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5190E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9850E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0137E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1955E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2284E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0537E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0556E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7391E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7408E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5207E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5219E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8674E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8681E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0974E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2083E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7759E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8662E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5515E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6204E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8864E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9344E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4133E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9860E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6470E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5120E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6466E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0476E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9234E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3767E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0951E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2088E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7724E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8610E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5451E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6002E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8860E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9331E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0535E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0554E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7390E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7405E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5205E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5215E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8674E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8680E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8651E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9656E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5509E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6238E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5003E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5257E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1956E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2284E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2882E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2972E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8440E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0081E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.5252E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9336E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0350E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5085E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9492E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1892E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6630E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9244E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5351E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6419E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1954E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2278E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1242 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.8790E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1391 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1141 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.6599E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.3481E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.5331E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.1963E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.4085E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.9176E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.3265E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.7824E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.2260E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.2414E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.6386E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2195E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0353E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8516E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.2039E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2520E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1996E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7220E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.5332E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1959E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.9667E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.1698E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.4833E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.8221E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.1580E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7146E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.6386E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2195E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1240 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.8883E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1389 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1142 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.6594E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.3581E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.5383E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.2005E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.4040E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.9211E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.3230E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.7861E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.2271E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.2469E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.6435E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2237E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0298E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8527E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.2001E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2530E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.2012E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7246E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.5383E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2001E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.9624E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.1721E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.4801E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.8244E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.1593E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7191E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.6435E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2237E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 66788.18604 | 66788.18604 | 5.51318 | 5.51318 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2779.42662 | 149.60210 | 1.20019 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20019 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2779.42662 | 149.60210 | 1.20019 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 72414.01207 | 72414.01207 | 5.97770 | 5.97770 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 7274.62001 | 7274.62001 | 0.35271 | 1.07782 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 677210.49441 | 677210.49441 | 55.88737 | 55.88737 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 325824.30253 | 325824.30253 | 15.76542 | 15.76542 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 65931.93035 | 65931.93035 | 5.49238 | 5.49238 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.08000 | 6.30633E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 78151.19350 | 78151.19350 | 3.80346 | 3.80346 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 11489.16626 | 11489.16626 | 0.95707 | 0.95707 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.40000 | 6.30683E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 12877.04593 | 12877.04593 | 0.62738 | 0.62738 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14788.80239 | 14788.80239 | 1.23193 | 1.23193 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.09333 | 6.29258E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 8866.64703 | 8866.64703 | 0.43208 | 0.43208 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 18494.93623 | 18494.93623 | 1.54066 | 1.54066 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.13333 | 6.30642E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 14291.50950 | 14291.50950 | 0.69650 | 0.69650 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18633.96703 | 18633.96703 | 1.55223 | 1.55223 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 7172.02460 | 7172.02460 | 0.34923 | 0.34923 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 105573.38939 | 105573.38939 | 8.79446 | 8.79446 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.40000 | 6.30683E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 180614.82195 | 180614.82195 | 8.80742 | 8.80742 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 155952.55325 | 155952.55325 | 12.99100 | 12.99100 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.50667 | 6.29470E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 119815.46062 | 119815.46062 | 5.84300 | 5.84300 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 183891.13224 | 183891.13224 | 15.31838 | 15.31838 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.30663E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 182893.47650 | 182893.47650 | 8.91879 | 8.91879 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 166380.28173 | 166380.28173 | 13.85964 | 13.85964 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 30.09333 | 6.30170E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 116920.53849 | 116920.53849 | 5.70155 | 5.70155 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 12175.07349 | 12175.07349 | 1.01420 | 1.01420 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.08000 | 6.30633E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 24128.19188 | 24128.19188 | 1.17721 | 1.17721 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15644.56958 | 15644.56958 | 1.30320 | 1.30320 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.41333 | 6.29608E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 15909.01959 | 15909.01959 | 0.77622 | 0.77622 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 19940.58600 | 19940.58600 | 1.66107 | 1.66107 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40000 | 6.30683E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 24412.56711 | 24412.56711 | 1.19111 | 1.19111 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 17781.59824 | 17781.59824 | 1.48122 | 1.48122 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 15843.11888 | 15843.11888 | 0.77301 | 0.77301 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8383.01682 | 8383.01682 | 0.55080 | 0.55080 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56328E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 80227.39620 | 80227.39620 | 5.27129 | 5.27129 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 0.15633 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15633 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 0.15633 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8174.24021 | 8174.24021 | 0.53708 | 0.53708 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 26.57333 | 6.29632E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56328E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370303.90436 | 370303.90436 | 24.33003 | 24.33003 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 18.84000 | 6.28481E-003 | 783.67941 | 42.18139 | 0.33840 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33840 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60000 | 3.41898E-004 | 783.67941 | 42.18139 | 0.33840 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 137904.59 | 9.73497 | 9.73497 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 107789.61 | 3.18302 | 3.18302 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1265822.91 | 89.91651 | 89.91651 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 1083966.37 | 45.03618 | 45.03618 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 143741.18 | 10.04219 | 10.04219 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 108418.37 | 7.72101 | 7.72101 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 |
7 | CAV_BAS | Cooling | Sensible | 68771.58 | 5.51318 | 5.51318 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 85859.43 | 1.20019 | 1.20019 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8264.42 | 0.55080 | 0.55080 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1118.34 | 1.56328E-002 | 1.56328E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER MID | Cooling | Sensible | 79084.74 | 5.27129 | 5.27129 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER MID | Heating | Sensible | 11183.41 | 0.15633 | 0.15633 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8062.86 | 0.53708 | 0.53708 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1118.34 | 1.56328E-002 | 1.56328E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.51318 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.97770 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31819 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32400 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.93677 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84851 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19740E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.12847E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.93677 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24329.75580 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.12847E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 512.01010 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 55.88737 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34034 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33900 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.94582 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90756 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11948E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.31001E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.94582 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 492660.62856 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.31001E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 12358.55284 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.49238 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34631 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35600 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.95529 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92348 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10018E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.76713E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.80346 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 111644.35007 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.76713E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2945.83342 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95707 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24953 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25400 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24310 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66542 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.52686E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.60974E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.62738 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18400.29837 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.60974E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 485.32285 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23193 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12493 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24639 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33315 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.04970E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.10848E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.43208 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12670.64667 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.10848E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 334.17664 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.54066 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15502 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30813 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41337 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.45782E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.78674E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.69650 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20423.57933 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.78674E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 538.63938 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.55223 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.91509E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31045 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.84263E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.96383E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34923 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10246.20424 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.96383E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 270.29517 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.80742 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27116 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.37800 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72309 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.40508E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.25835E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.80742 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 258142.90267 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.25835E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6806.68875 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.99100 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11847 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.59820 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31592 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.21599E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49816E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.84300 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 171248.80212 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49816E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4515.38020 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 15.31838 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15591 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.06368 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41575 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.44375E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.28686E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.91879 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 261402.24717 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.28686E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6892.57108 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.85964 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11105 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.77193 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.43103E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.46194E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.70155 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 167108.37033 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.46194E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4406.26866 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.17721 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20287 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24200 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28488 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54099 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.87805E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.01740E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.17721 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 34490.74395 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.01740E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 909.29369 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.30320 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11810 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26064 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31493 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.22615E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.98955E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.77622 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22741.81694 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.98955E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 599.54451 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.66107 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14378 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33221 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38341 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.64992E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.05299E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.19111 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 34897.49442 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.05299E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 920.01156 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.48122 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10390 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29624 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.66684E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.98131E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.77301 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22647.61034 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.98131E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 597.06058 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.55080 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.27129 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.53708 |
215 | ZoneHVAC:IdealLoadsAirSystem | AIRLOOP DATACENTER BASEMENT | Design Size Maximum Heating Air Flow Rate [m3/s] | 0.33840 |
216 | ZoneHVAC:IdealLoadsAirSystem | AIRLOOP DATACENTER BASEMENT | Design Size Maximum Cooling Air Flow Rate [m3/s] | 24.33003 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.62979 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.04483 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.25959 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.18302 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.73497 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.73497 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32697 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 53.43190 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 29.75762 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 106.86380 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 45.03618 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 89.91651 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 89.91651 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.50087 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.55754 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.12927 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.11509 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 7.72101 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.04219 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.04219 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.76886 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.51318 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.51318 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.51318 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.51318 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.51318 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.51318 |
247 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.55080 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.55080 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.55080 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.55080 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.55080 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.55080 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
257 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.27129 |
258 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.27129 |
259 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.27129 |
260 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.27129 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.27129 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.27129 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
265 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.53708 |
266 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.53708 |
267 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.53708 |
268 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.53708 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.53708 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.53708 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
273 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.73497 |
274 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 89.91651 |
275 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.04219 |
276 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.51318 |
277 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.55080 |
278 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.27129 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.53708 |
280 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.73497 |
281 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.50906 |
282 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
283 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68120 |
284 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.08736E-003 |
285 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 167452.83653 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.12383E-003 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.73497 |
289 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 105624.67687 |
290 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.24051E-004 |
291 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1552.36793 |
292 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.73497 |
293 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.12383E-003 |
294 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.68447E-005 |
295 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.24051E-004 |
296 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 89.91651 |
297 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.78957 |
298 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
299 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.66985 |
300 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.08079E-003 |
301 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1573216.63694 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.69283E-002 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 89.91651 |
305 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 1074744.70763 |
306 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.40234E-003 |
307 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 15383.51714 |
308 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 89.91651 |
309 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.69283E-002 |
310 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.11494E-006 |
311 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.40234E-003 |
312 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.04219 |
313 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.38543 |
314 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
315 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68118 |
316 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.08324E-003 |
317 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 171295.36808 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.28730E-003 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.04219 |
321 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 104881.89672 |
322 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.17553E-004 |
323 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1557.33028 |
324 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.04219 |
325 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.28730E-003 |
326 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.53452E-005 |
327 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.17553E-004 |
328 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.51318 |
329 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.11349 |
330 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
331 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.21891 |
332 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.26328E-003 |
333 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
334 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 91921.22236 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.91054E-003 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.51318 |
337 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 268429.25809 |
338 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.34834E-003 |
339 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5691.92056 |
340 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.51318 |
341 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.91054E-003 |
342 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.21771E-004 |
343 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.34834E-003 |
344 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.55080 |
345 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56328E-002 |
346 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.55080 |
347 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10177.41420 |
348 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5787.05732 |
349 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.49244E-004 |
350 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.55080 |
351 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.55080 |
352 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.55080 |
353 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.55080 |
354 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10177.41420 |
355 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10177.41420 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1118.34104 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
358 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.55080 |
359 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.55080 |
360 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10177.41420 |
361 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.49244E-004 |
362 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1118.34104 |
363 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.27129 |
364 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15633 |
365 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.27129 |
366 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 97434.04555 |
367 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 55390.67823 |
368 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.38615E-003 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.27129 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.27129 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.27129 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.27129 |
373 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 97434.04555 |
374 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 97434.04555 |
375 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 11183.41045 |
376 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
377 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.27129 |
378 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.27129 |
379 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 97434.04555 |
380 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.38615E-003 |
381 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 11183.41045 |
382 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.53708 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56328E-002 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.53708 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9925.99058 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5643.36940 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.43087E-004 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.53708 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.53708 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.53708 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.53708 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9925.99058 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9925.99058 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1118.34104 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
396 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.53708 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.53708 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9925.99058 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.43087E-004 |
400 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1118.34104 |
401 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 8.52499E-002 |
402 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 17392.92487 |
403 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 8.52499E-002 |
404 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 10.22999 |
405 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 8.52499E-002 |
406 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 8.52499E-002 |
407 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 357836.79712 |
408 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
409 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.81414E-002 |
410 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.37697 |
411 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.81414E-002 |
412 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 8391.04631 |
413 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
414 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3216735.99029 |
415 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3216735.99000 |
416 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.81414E-002 |
417 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 8.52499E-002 |
418 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 10.22999 |
419 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 8.52499E-002 |
420 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 12041.70859 |
421 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.52499E-002 |
422 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.29112E-002 |
423 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1009797.78830 |
424 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1015943.92500 |
425 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.07665E-002 |
426 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.52499E-002 |
427 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.29112E-002 |
428 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1009797.78830 |
429 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1015943.92500 |
430 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.07665E-002 |
431 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 2.87848E-003 |
432 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 0.34542 |
433 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 2.87848E-003 |
434 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 726.88863 |
435 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 2.87848E-003 |
436 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 35644.39112 |
437 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 18388.83511 |
438 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 17822.19556 |
439 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 1996.19659 |
440 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 5720.04929 |
441 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 118568.88787 |
442 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 118568.89000 |
443 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 2.87848E-003 |
444 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
445 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
446 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
447 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
448 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
449 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10153 |
450 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.18396 |
451 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10153 |
452 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 30276.74918 |
453 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 40.65314 |
454 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1206897.55131 |
455 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 8.13063 |
456 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 150862.19391 |
457 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 40.65314 |
458 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1206897.55131 |
459 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 8.13063 |
460 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 150862.19391 |
461 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 5.22200E-002 |
462 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 5.22200E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 23068.41 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 466748.12 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 105813.44 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17438.05 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12007.88 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 19355.19 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9710.67 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 244629.47 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 162283.53 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 247717.79 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 158360.27 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 32684.15 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 21550.57 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 33069.56 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 21461.30 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 67183.27 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 661538.60 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 67545.37 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 200868.92 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 276280.40 | 169290.01 | 106990.39 | 0.61 | 53841.52 | 546.09 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2564772.93 | 1568776.69 | 995996.24 | 0.61 | 493914.01 | 5009.55 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 284339.89 | 174371.38 | 109968.51 | 0.61 | 55796.36 | 565.92 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 151163.49 | 93719.48 | 57444.01 | 0.62 | 27092.40 | 274.79 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 7.80 | 26.60 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 7.80 | 26.60 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.354 | 0.336 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_NORTH_0.38 | N/A | 1.946 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_NORTH_0.38 | N/A | 1.946 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_NORTH_0.38 | N/A | 1.946 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_NORTH_0.38 | N/A | 1.946 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_NORTH_0.38 | N/A | 1.946 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_EAST_0.38 | N/A | 1.946 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_EAST_0.38 | N/A | 1.946 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_EAST_0.38 | N/A | 1.946 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | N/A | 1.946 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | N/A | 1.946 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | N/A | 1.946 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | N/A | 1.946 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | N/A | 1.946 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_WEST_0.38 | N/A | 1.946 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_WEST_0.38 | N/A | 1.946 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_WEST_0.38 | N/A | 1.946 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_NORTH_0.38 | N/A | 1.946 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_EAST_0.38 | N/A | 1.946 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | N/A | 1.946 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_WEST_0.38 | N/A | 1.946 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_NORTH_0.38 | N/A | 1.946 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_EAST_0.38 | N/A | 1.946 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | N/A | 1.946 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_WEST_0.38 | N/A | 1.946 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.354 | 0.336 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2715174102 | 0.2014965493 | Pass | Pass | 5.3061433129 | 15.8261485772 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.6799962322E-002 | 0.1233096291 | Pass | Pass | 4.9601487233E-002 | 0.2168665108 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.6781578838E-002 | 5.4562308149E-002 | Pass | Pass | 6.9467294717E-003 | 8.1780731415E-002 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.3674295228E-002 | 2.5719189112E-002 | Pass | Pass | 0.4946572531 | 0.5335151751 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.7655368481E-002 | 7.6960116346E-002 | Pass | Pass | 4.9114923748E-002 | 0.2149722245 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.0999298388E-002 | 0.1428288520 | Pass | Pass | 4.9785889334E-002 | 0.2178905031 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1317371316 | 0.1677707827 | Pass | Pass | 5.3910776817E-002 | 0.2294051470 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.6030975931E-002 | 0.1641117912 | Pass | Pass | 4.8565333935E-002 | 0.2131040273 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.0836537303E-002 | 2.2068923621E-002 | Pass | Pass | 6.9483206407E-003 | 6.7950134588E-002 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.2180530626E-002 | 7.9895541919E-002 | Pass | Pass | 6.9469942703E-003 | 7.8570691326E-002 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1325691731 | 0.1364262199 | Pass | Pass | 1.0394098436E-002 | 0.1055297989 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.9522516757E-002 | 7.4139152963E-002 | Pass | Pass | 6.9247969207E-003 | 7.7096679434E-002 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3110037143 | 0.3087063827 | Pass | Pass | 31.6653777475 | 90.9003936198 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2022849561 | 0.2678660405 | Pass | Pass | 11.4248653698 | 48.1863380343 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1961073566 | 0.1811097642 | Pass | Pass | 2.8771502264 | 20.6784345541 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1546059683 | 0.1863080163 | Pass | Pass | 37.0845675463 | 287.1675103539 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.8722060887E-003 | 1.8783633201E-002 | Pass | Pass | 0.1088117779 | 0.4791899704 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.0687430303E-002 | 2.2807268561E-002 | Pass | Pass | 3.2839587736E-002 | 0.2778237007 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1011244608 | 7.4389561682E-002 | Pass | Pass | 0.4972041967 | 0.4875701438 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.9199346560E-006 | 4.9279688481E-006 | Pass | Pass | 3.9618853572E-003 | 3.9379942685E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.5433789456E-005 | 2.6486113783E-004 | Pass | Pass | 0.1104713779 | 0.4387455796 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.6276859814E-002 | 2.0690069443E-002 | Pass | Pass | 4.4274963817E-003 | 5.0332716771E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.2944609176E-015 | 2.6303930358E-015 | Pass | Pass | 4.8665940859E-005 | 1.0555455783E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6998.27 | 126.16 | 0.00 | 18979.95 | 6552.20 | 32656.56 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.340 | 0.354 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.340 | 0.354 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3425_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3425_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3425_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.3425_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.3425_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3425_SHGC_EAST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3425_SHGC_EAST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.3425_SHGC_EAST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3425_SHGC_WEST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3425_SHGC_WEST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.3425_SHGC_WEST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3425_SHGC_NORTH_0.38 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 1.946 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3425_SHGC_EAST_0.38 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 1.946 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 1.946 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3425_SHGC_WEST_0.38 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 1.946 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3425_SHGC_NORTH_0.38 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 1.946 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3425_SHGC_EAST_0.38 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 1.946 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 1.946 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3425_SHGC_WEST_0.38 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 1.946 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 1.946 | 0.381 | 0.381 | |||||||||||||||||
North Total or Average | 1043.06 | 1.946 | 0.381 | 0.381 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 1.946 | 0.381 | 0.381 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.8895 | 2779.43 | 16369.36 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 135.58 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8895 | 2496.12 | 14700.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 121.76 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8895 | 24961.20 | 147008.37 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 1217.57 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8895 | 2496.12 | 14700.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 121.76 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8895 | 313.41 | 1845.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.26 | 0.0000 | Y | 9.10 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.85 | 0.0000 | Y | 5.77 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8895 | 313.42 | 1845.88 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.59 | 0.0000 | Y | 8.87 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.96 | 0.0000 | Y | 5.80 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8895 | 3134.13 | 18458.37 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.27 | 0.0000 | Y | 91.01 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8895 | 2019.75 | 11895.27 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.85 | 0.0000 | Y | 57.72 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8895 | 3134.20 | 18458.77 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.59 | 0.0000 | Y | 88.69 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8895 | 2019.75 | 11895.27 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.96 | 0.0000 | Y | 57.96 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8895 | 313.41 | 1845.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.27 | 0.0000 | Y | 9.10 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.85 | 0.0000 | Y | 5.77 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8895 | 313.42 | 1845.88 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.59 | 0.0000 | Y | 8.87 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.96 | 0.0000 | Y | 5.80 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.8895 | 783.68 | 4615.46 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 38.23 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 8.8011 | 36.20 | 318.62 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.26 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 8.8011 | 362.03 | 3186.24 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 32.64 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 8.8011 | 36.20 | 318.62 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.26 |
Interior Lighting Total | 5.9168 | 46320.38 | 274067.57 | 637.48 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.05 | AstronomicalClock | - | 42.11 | 42.11 | 78.82 | |
EXTERIOR_LIGHTS_B | 991.40 | AstronomicalClock | - | 83.57 | 62.84 | 11.69 | |
EXTERIOR_LIGHTS_C | 26646.63 | AstronomicalClock | - | 83.57 | 48.07 | 240.44 | |
Exterior Lighting Total | 37611.08 | 330.95 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 1999277.72 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3216735.99 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1015943.93 | 5.86 | 1005119.02 | 5.50 | 7.80 | 26.60 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1015943.93 | 5.86 | 1005119.02 | 5.50 | 7.80 | 26.60 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 148548.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 118568.89 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1206897.55 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1206897.55 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 167452.84 | 276280.40 | 169290.01 | 106990.39 | 0.61 | - | 53841.52 | 546.09 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1573216.64 | 2564772.93 | 1568776.69 | 995996.24 | 0.61 | - | 493914.01 | 5009.55 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 171295.37 | 284339.89 | 174371.38 | 109968.51 | 0.61 | - | 55796.36 | 565.92 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 91921.22 | 151163.49 | 93719.48 | 57444.01 | 0.62 | - | 27092.40 | 274.79 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10177.41 | 5787.06 | 4390.36 | 0.57 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 97434.05 | 55390.68 | 42043.37 | 0.57 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9925.99 | 5643.37 | 4282.62 | 0.57 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 24329.76 | 23068.41 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 492660.63 | 466748.12 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 111644.35 | 105813.44 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 18400.30 | 17438.05 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12670.65 | 12007.88 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 20423.58 | 19355.19 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 10246.20 | 9710.67 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 258142.90 | 244629.47 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 171248.80 | 162283.53 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 261402.25 | 247717.79 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 167108.37 | 158360.27 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 34490.74 | 32684.15 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 22741.82 | 21550.57 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 34897.49 | 33069.56 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 22647.61 | 21461.30 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 105624.68 | 67183.27 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 1074744.71 | 661538.60 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 104881.90 | 67545.37 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 268429.26 | 200868.92 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10177.41 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 97434.05 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9925.99 | 0.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1118.34 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 11183.41 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1118.34 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.73 | 22113.90 | 2271.59 | 1.00 | 1.12 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 89.92 | 205344.84 | 2283.73 | 1.00 | 1.07 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.04 | 22811.77 | 2271.59 | 1.00 | 1.12 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.51 | 9348.44 | 1695.65 | 1.00 | 1.16 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.55 | 616.95 | 1120.11 | 1.00 | 1.56 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.27 | 5904.41 | 1120.11 | 1.00 | 1.15 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.54 | 601.59 | 1120.11 | 1.00 | 1.57 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.085250 | 17392.92 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.028141 | 8391.05 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.085250 | 12041.71 | 141251.81 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.002878 | 726.89 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.101533 | 30276.75 | 298196.27 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 66788.19 | 66788.19 | 24.03 | 5.513 | 5.513 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00752 | 21.56 | 0.00629 | 1.200 | 0.00 |
CORE_BOTTOM | 72414.01 | 72414.01 | 29.01 | 5.978 | 5.978 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00743 | 21.56 | 0.00629 | 1.078 | 0.00 |
CORE_MID | 677210.49 | 677210.49 | 271.31 | 55.887 | 55.887 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00746 | 21.56 | 0.00629 | 10.778 | 0.00 |
CORE_TOP | 65931.93 | 65931.93 | 26.41 | 5.492 | 5.492 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00746 | 33.08 | 0.00631 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11489.17 | 11489.17 | 36.66 | 0.957 | 0.957 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00732 | 33.40 | 0.00631 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14788.80 | 14788.80 | 73.22 | 1.232 | 1.232 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00716 | 24.09 | 0.00629 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 18494.94 | 18494.94 | 59.01 | 1.541 | 1.541 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00720 | 33.13 | 0.00631 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18633.97 | 18633.97 | 92.26 | 1.552 | 1.552 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00713 | 30.36 | 0.00630 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 105573.39 | 105573.39 | 336.85 | 8.794 | 8.794 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00733 | 33.40 | 0.00631 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 155952.55 | 155952.55 | 772.14 | 12.991 | 12.991 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00715 | 25.51 | 0.00629 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 183891.13 | 183891.13 | 586.72 | 15.318 | 15.318 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00719 | 33.27 | 0.00631 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 166380.28 | 166380.28 | 823.77 | 13.860 | 13.860 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00714 | 30.09 | 0.00630 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12175.07 | 12175.07 | 38.85 | 1.014 | 1.014 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00728 | 33.08 | 0.00631 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15644.57 | 15644.57 | 77.46 | 1.303 | 1.303 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00714 | 26.41 | 0.00630 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 19940.59 | 19940.59 | 63.62 | 1.661 | 1.661 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00717 | 33.40 | 0.00631 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 17781.60 | 17781.60 | 88.04 | 1.481 | 1.481 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00713 | 30.36 | 0.00630 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8383.02 | 8383.02 | 231.56 | 0.551 | 0.551 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00709 | 26.28 | 0.00630 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 80227.40 | 80227.40 | 2216.06 | 5.271 | 5.271 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00709 | 26.28 | 0.00630 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8174.24 | 8174.24 | 225.79 | 0.537 | 0.537 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 27.00 | 27.00 | 0.00709 | 26.57 | 0.00630 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370303.90 | 370303.90 | 472.52 | 24.330 | 24.330 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 18.84 | 0.00628 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 22.86 | 0.00034 | -27.60 | 0.00034 | 1.200 | 0.00 |
CORE_BOTTOM | 7274.62 | 7274.62 | 2.91 | 0.353 | 1.078 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 1.078 | 0.00 |
CORE_MID | 325824.30 | 325824.30 | 130.53 | 15.765 | 15.765 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 10.778 | 0.00 |
CORE_TOP | 78151.19 | 78151.19 | 31.31 | 3.803 | 3.803 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12877.05 | 12877.05 | 41.09 | 0.627 | 0.627 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 8866.65 | 8866.65 | 43.90 | 0.432 | 0.432 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 14291.51 | 14291.51 | 45.60 | 0.697 | 0.697 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 7172.02 | 7172.02 | 35.51 | 0.349 | 0.349 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 180614.82 | 180614.82 | 576.28 | 8.807 | 8.807 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -27.60 | 0.00034 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 119815.46 | 119815.46 | 593.22 | 5.843 | 5.843 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -27.60 | 0.00034 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 182893.48 | 182893.48 | 583.54 | 8.919 | 8.919 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -27.60 | 0.00034 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 116920.54 | 116920.54 | 578.89 | 5.702 | 5.702 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -27.60 | 0.00034 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 24128.19 | 24128.19 | 76.99 | 1.177 | 1.177 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00786 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15909.02 | 15909.02 | 78.77 | 0.776 | 0.776 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 24412.57 | 24412.57 | 77.89 | 1.191 | 1.191 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00786 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 15843.12 | 15843.12 | 78.44 | 0.773 | 0.773 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -27.60 | 0.00034 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.44 | 0.00098 | -27.60 | 0.00034 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.39 | 0.00097 | -27.60 | 0.00034 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 19.80 | 0.00097 | -27.60 | 0.00034 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 18.00 | 27.00 | 0.00700 | -27.60 | 0.00034 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.73 | 9.73 | 3.18 | 3.18 | 9.7350 | 3.1830 | 9.7350 | 0.3270 | 0.3000 |
VAV_MID WITH REHEAT | 89.92 | 89.92 | 45.04 | 45.04 | 89.9165 | 45.0362 | 89.9165 | 0.5009 | 0.3000 |
VAV_TOP WITH REHEAT | 10.04 | 10.04 | 7.72 | 7.72 | 10.0422 | 7.7210 | 10.0422 | 0.7689 | 0.3000 |
CAV_BAS | 5.51 | 5.51 | 1.20 | 1.20 | 5.5132 | 5.5132 | 5.5132 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.55 | 0.55 | 0.02 | 0.02 | 0.5508 | 0.5508 | 0.5508 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.27 | 5.27 | 0.16 | 0.16 | 5.2713 | 5.2713 | 5.2713 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.54 | 0.54 | 0.02 | 0.02 | 0.5371 | 0.5371 | 0.5371 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 24329.756 | 24329.756 | 1.936774 | 0.00021285 | 512.010 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24329.76 | 24329.76 | 1.936774 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00799881 | 45.2243 | 7274.62 | 0.00 | 24417.66 | 24417.66 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 492660.629 | 492660.629 | 18.945817 | 0.00431001 | 12358.553 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 492660.63 | 492660.63 | 18.945817 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 325824.30 | 0.00 | 494193.57 | 494193.57 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 111644.350 | 111644.350 | 3.803460 | 0.00097671 | 2945.833 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 111644.35 | 111644.35 | 3.803460 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 78151.19 | 0.00 | 112021.28 | 112021.28 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 18400.298 | 18400.298 | 0.627377 | 0.00016097 | 485.323 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18400.30 | 18400.30 | 0.627377 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00789075 | 44.6223 | 12877.05 | 0.00 | 18461.09 | 18461.09 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 12670.647 | 12670.647 | 0.432081 | 0.00011085 | 334.177 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12670.65 | 12670.65 | 0.432081 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00790028 | 44.6754 | 8866.65 | 0.00 | 12712.35 | 12712.35 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 20423.579 | 20423.579 | 0.696502 | 0.00017867 | 538.639 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20423.58 | 20423.58 | 0.696502 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00790973 | 44.7281 | 14291.51 | 0.00 | 20490.70 | 20490.70 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 10246.204 | 10246.204 | 0.349233 | 0.00008964 | 270.295 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10246.20 | 10246.20 | 0.349233 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783794 | 44.3279 | 7172.02 | 0.00 | 10280.37 | 10280.37 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 258142.903 | 258142.903 | 8.807419 | 0.00225835 | 6806.689 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 258142.90 | 257265.16 | 8.807419 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00784296 | 44.3563 | 180614.82 | 0.00 | 258981.04 | 258981.04 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 171248.802 | 171248.802 | 5.842995 | 0.00149816 | 4515.380 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 171248.80 | 171248.80 | 5.842995 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00784254 | 44.3540 | 119815.46 | 0.00 | 171804.14 | 171804.14 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 261402.247 | 261402.247 | 8.918792 | 0.00228686 | 6892.571 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 261402.25 | 261402.25 | 8.918792 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00784504 | 44.3679 | 182893.48 | 0.00 | 262250.53 | 262250.53 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 167108.370 | 167108.370 | 5.701552 | 0.00146194 | 4406.269 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 167108.37 | 167108.37 | 5.701552 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783838 | 44.3308 | 116920.54 | 0.00 | 167650.72 | 167650.72 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 34490.744 | 34490.744 | 1.177208 | 0.00030174 | 909.294 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 34490.74 | 34386.31 | 1.177208 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00785513 | 44.4246 | 24128.19 | 0.00 | 34601.61 | 34601.61 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 22741.817 | 22741.817 | 0.776225 | 0.00019896 | 599.545 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22741.82 | 22741.82 | 0.776225 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00785354 | 44.4158 | 15909.02 | 0.00 | 22814.86 | 22814.86 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 34897.494 | 34897.494 | 1.191106 | 0.00030530 | 920.012 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 34897.49 | 34897.49 | 1.191106 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00785679 | 44.4339 | 24412.57 | 0.00 | 35009.63 | 35009.63 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 22647.610 | 22647.610 | 0.773010 | 0.00019813 | 597.061 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22647.61 | 22647.61 | 0.773010 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00785302 | 44.4129 | 15843.12 | 0.00 | 22720.35 | 22720.35 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 167452.837 | -999.000 | 9.734974 | 0.00712383 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 167452.84 | 165616.57 | 9.734974 | 26.51 | 14.70 | 0.00708736 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 26.0729 | 24.00 | 0.00737170 | 34.7704 | 114108.97 | 0.00 | 188432.38 | 185629.60 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 105624.677 | 105624.677 | 2.920492 | 0.00092405 | 1552.368 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 105624.68 | 105624.68 | 2.920492 | -21.38 | -21.38 | 0.00132390 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 86.9097 | 19.82 | 0.00781081 | 47.5086 | 32255.77 | 0.00 | 81218.39 | 81218.39 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1573216.637 | -999.000 | 89.916511 | 0.06692827 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1573216.64 | 1557466.93 | 89.916511 | 26.79 | 14.79 | 0.00708079 | 10.67 | 8.50 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 28.2284 | 24.00 | 0.00740755 | 34.9375 | 1026402.33 | 0.00 | 1767640.89 | 1742304.83 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1074744.708 | 1074744.708 | 26.974953 | 0.00940234 | 15383.517 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1074744.71 | 1074744.71 | 26.974953 | -24.85 | -24.85 | 0.00078201 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 94.0945 | 17.87 | 0.00777912 | 53.4488 | 358921.30 | 0.00 | 799478.82 | 799478.82 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 171295.368 | -999.000 | 10.042189 | 0.00728730 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 171295.37 | 169493.60 | 10.042189 | 26.39 | 14.65 | 0.00708324 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 25.2753 | 24.00 | 0.00734741 | 34.6571 | 120021.13 | 0.00 | 192905.44 | 190145.41 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 104881.897 | 104881.897 | 3.012657 | 0.00091755 | 1557.330 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 104881.90 | 104881.90 | 3.012657 | -20.10 | -20.10 | 0.00151754 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 84.2509 | 17.22 | 0.00779965 | 55.8394 | 50607.84 | 0.00 | 81665.29 | 81665.29 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 91921.222 | -999.000 | 5.513176 | 0.00391054 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 91921.22 | 88891.11 | 5.513176 | 26.11 | 14.71 | 0.00726328 | 11.22 | 8.74 | 0.00700000 | 32.60 | 0.00630558 | 16.10 | 21.7695 | 24.00 | 0.00757554 | 35.7206 | 58594.84 | 0.00 | 103503.08 | 101163.93 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 268429.258 | 268429.258 | 5.513176 | 0.00234834 | 5691.921 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 268429.26 | 268429.26 | 5.513176 | -6.01 | -10.13 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 21.7695 | 22.97 | 0.00034190 | 1.7353 | 0.00 | 0.00 | 211861.70 | 211861.70 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10177.414 | 5787.057 | 0.550797 | 0.00024924 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 8796.99 | 8731.62 | -999.0 | 28.07 | 15.21 | 0.00706357 | 12.80 | 9.41 | 0.00700000 | 26.57 | 0.00629632 | 14.04 | -999.0000 | 27.00 | 0.00708599 | 27.9814 | 8383.02 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 97434.046 | 55390.678 | 5.271288 | 0.00238615 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 84223.50 | 83570.94 | -999.0 | 28.07 | 15.21 | 0.00706631 | 12.80 | 9.41 | 0.00700000 | 26.57 | 0.00629632 | 14.04 | -999.0000 | 27.00 | 0.00708985 | 27.9966 | 80227.40 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9925.991 | 5643.369 | 0.537081 | 0.00024309 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 8579.97 | 8514.62 | -999.0 | 28.07 | 15.21 | 0.00706518 | 12.80 | 9.41 | 0.00700000 | 26.57 | 0.00629632 | 14.04 | -999.0000 | 27.00 | 0.00708823 | 27.9902 | 8174.24 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10177.414 | 10177.414 | 0.550797 | 0.00024924 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10177.41 | 10177.41 | 0.550797 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8382 | 25.23 | 0.00098087 | 4.3430 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 97434.046 | 97434.046 | 5.271288 | 0.00238615 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 97434.05 | 97434.05 | 5.271288 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.9656 | 23.63 | 0.00097461 | 4.7491 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9925.991 | 9925.991 | 0.537081 | 0.00024309 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9925.99 | 9925.99 | 0.537081 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.9107 | 22.04 | 0.00097402 | 5.2258 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1118.341 | 1118.341 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1118.34 | 1118.34 | 0.550797 | -0.78 | -5.62 | 0.00096273 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8382 | 25.23 | 0.00098087 | 4.3430 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 11183.410 | 11183.410 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 11183.41 | 11183.41 | 5.271288 | -0.82 | -5.66 | 0.00095584 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.9656 | 23.63 | 0.00097461 | 4.7491 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1118.341 | 1118.341 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1118.34 | 1118.34 | 0.537081 | -0.80 | -5.65 | 0.00095562 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.9107 | 22.04 | 0.00097402 | 5.2258 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 24329.756 | 24329.756 | 1.936774 | 0.00021285 | 512.010 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 0.7414 | 0.756349 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24329.76 | 24329.76 | 1.0000 | 2.03969353 | 1.936774 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.21282560 | 60.00 | 32.22 | 27.78 | 0.000 | 24329.76 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.81 | 0.00799881 | 21.00 | 0.00799881 | 45.2243 | 7274.62 | 0.00 | 24417.66 | 24417.66 | 2.03969353 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 24.54 | 16.15 | 0.00800000 | 45031.1 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 492660.629 | 492660.629 | 18.945817 | 0.00431001 | 12358.553 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 15.0134 | 15.315544 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 492660.63 | 492660.63 | 1.0000 | 19.95259583 | 18.945817 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 4.30957043 | 60.00 | 32.22 | 27.78 | 0.000 | 492660.63 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 325824.30 | 0.00 | 494193.57 | 494193.57 | 19.95259583 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.09 | 20.31 | 0.00800000 | 57828.2 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 111644.350 | 111644.350 | 3.803460 | 0.00097671 | 2945.833 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 3.4023 | 3.470734 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 111644.35 | 111644.35 | 1.0000 | 4.00557500 | 3.803460 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.97661384 | 60.00 | 32.22 | 27.78 | 0.000 | 111644.35 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 78151.19 | 0.00 | 112021.28 | 112021.28 | 4.00557500 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61026.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18400.298 | 18400.298 | 0.627377 | 0.00016097 | 485.323 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 0.5607 | 0.572018 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18400.30 | 18400.30 | 1.0000 | 0.66071577 | 0.627377 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.16095742 | 60.00 | 32.22 | 27.78 | 0.000 | 18400.30 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00789075 | 21.00 | 0.00789075 | 44.6223 | 12877.05 | 0.00 | 18461.09 | 18461.09 | 0.66071577 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61000.9 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12670.647 | 12670.647 | 0.432081 | 0.00011085 | 334.177 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 0.3861 | 0.393898 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12670.65 | 12670.65 | 1.0000 | 0.45504153 | 0.432081 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.11083704 | 60.00 | 32.22 | 27.78 | 0.000 | 12670.65 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00790028 | 21.00 | 0.00790028 | 44.6754 | 8866.65 | 0.00 | 12712.35 | 12712.35 | 0.45504153 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60996.5 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20423.579 | 20423.579 | 0.696502 | 0.00017867 | 538.639 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 0.6224 | 0.634916 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20423.58 | 20423.58 | 1.0000 | 0.73351384 | 0.696502 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.17865615 | 60.00 | 32.22 | 27.78 | 0.000 | 20423.58 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00790973 | 21.00 | 0.00790973 | 44.7281 | 14291.51 | 0.00 | 20490.70 | 20490.70 | 0.73351384 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60994.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10246.204 | 10246.204 | 0.349233 | 0.00008964 | 270.295 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 0.3122 | 0.318528 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10246.20 | 10246.20 | 1.0000 | 0.36779104 | 0.349233 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.08962912 | 60.00 | 32.22 | 27.78 | 0.000 | 10246.20 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00783794 | 21.00 | 0.00783794 | 44.3279 | 7172.02 | 0.00 | 10280.37 | 10280.37 | 0.36779104 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61011.5 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 258142.903 | 258142.903 | 8.807419 | 0.00225835 | 6806.689 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 7.8667 | 8.024995 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 258142.90 | 257265.16 | 1.0000 | 9.27544414 | 8.807419 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.25811635 | 60.00 | 32.22 | 27.78 | 0.000 | 258142.90 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00784296 | 21.00 | 0.00784296 | 44.3563 | 180614.82 | 0.00 | 258981.04 | 258981.04 | 9.27544414 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60981.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 171248.802 | 171248.802 | 5.842995 | 0.00149816 | 4515.380 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 5.2187 | 5.323682 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 171248.80 | 171248.80 | 1.0000 | 6.15349129 | 5.842995 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 1.49800640 | 60.00 | 32.22 | 27.78 | 0.000 | 171248.80 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00784254 | 21.00 | 0.00784254 | 44.3540 | 119815.46 | 0.00 | 171804.14 | 171804.14 | 6.15349129 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60979.6 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 261402.247 | 261402.247 | 8.918792 | 0.00228686 | 6892.571 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 7.9660 | 8.126320 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 261402.25 | 261402.25 | 1.0000 | 9.39273528 | 8.918792 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.28662761 | 60.00 | 32.22 | 27.78 | 0.000 | 261402.25 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00784504 | 21.00 | 0.00784504 | 44.3679 | 182893.48 | 0.00 | 262250.53 | 262250.53 | 9.39273528 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60980.4 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 167108.370 | 167108.370 | 5.701552 | 0.00146194 | 4406.269 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 5.0925 | 5.194967 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 167108.37 | 167108.37 | 1.0000 | 6.00453177 | 5.701552 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 1.46178779 | 60.00 | 32.22 | 27.78 | 0.000 | 167108.37 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00783838 | 21.00 | 0.00783838 | 44.3308 | 116920.54 | 0.00 | 167650.72 | 167650.72 | 6.00453177 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60980.5 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34490.744 | 34490.744 | 1.177208 | 0.00030174 | 909.294 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 1.0511 | 1.072228 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 34490.74 | 34386.31 | 1.0000 | 1.23976471 | 1.177208 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.30170929 | 60.00 | 32.22 | 27.78 | 0.000 | 34490.74 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00785513 | 21.00 | 0.00785513 | 44.4246 | 24128.19 | 0.00 | 34601.61 | 34601.61 | 1.23976471 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60969.6 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22741.817 | 22741.817 | 0.776225 | 0.00019896 | 599.545 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 0.6930 | 0.706984 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22741.82 | 22741.82 | 1.0000 | 0.81747327 | 0.776225 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.19893504 | 60.00 | 32.22 | 27.78 | 0.000 | 22741.82 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00785354 | 21.00 | 0.00785354 | 44.4158 | 15909.02 | 0.00 | 22814.86 | 22814.86 | 0.81747327 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60968.8 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34897.494 | 34897.494 | 1.191106 | 0.00030530 | 920.012 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 1.0635 | 1.084873 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 34897.49 | 34897.49 | 1.0000 | 1.25440159 | 1.191106 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.30526736 | 60.00 | 32.22 | 27.78 | 0.000 | 34897.49 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00785679 | 21.00 | 0.00785679 | 44.4339 | 24412.57 | 0.00 | 35009.63 | 35009.63 | 1.25440159 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60969.3 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22647.610 | 22647.610 | 0.773010 | 0.00019813 | 597.061 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 0.6902 | 0.704056 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22647.61 | 22647.61 | 1.0000 | 0.81408799 | 0.773010 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.19811096 | 60.00 | 32.22 | 27.78 | 0.000 | 22647.61 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00785302 | 21.00 | 0.00785302 | 44.4129 | 15843.12 | 0.00 | 22720.35 | 22720.35 | 0.81408799 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60968.8 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 167452.837 | -999.000 | 9.734974 | 0.00712383 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0150 | 1004.8586 | 1.0531 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.734974 | 10.25228913 | 4197.9300 | 999.8980 | 85.24124917 | 12.27 | 6.67 | 5.60 | 2003886.06 | 8.3564 | 8.356405 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 167452.84 | 165616.57 | 1.0000 | 10.25228913 | 9.734974 | 26.51 | 14.70 | 0.00708736 | 44711.7 | 10.68 | 8.51 | 0.00700000 | 28378.5 | 7.12310406 | 6.67 | 12.27 | 5.60 | 22113.901 | 145338.94 | 33.40 | 0.00630683 | 16.37 | 2.53819000 | 26.0729 | 24.00 | 0.00737170 | 24.00 | 0.00737170 | 34.7704 | 114108.97 | 0.00 | 188432.38 | 185629.60 | 10.25228913 | 26.51 | 16.06 | 0.00708736 | 44711.7 | 8.72 | 8.71 | 0.00697875 | 26332.1 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 105624.677 | 105624.677 | 2.920492 | 0.00092405 | 1552.368 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.734974 | 10.25228913 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 3.2188 | 3.283598 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 105624.68 | 105624.68 | 1.0000 | 3.07568674 | 2.920492 | -21.38 | -21.38 | 0.00132390 | -18220.8 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.92395649 | 60.00 | 32.22 | 27.78 | 0.000 | 105624.68 | -27.60 | 0.00034190 | -27.60 | 2.53819000 | 86.9097 | 19.95 | 0.00784367 | 19.82 | 0.00781081 | 47.5086 | 32255.77 | 0.00 | 81218.39 | 81218.39 | 3.07568674 | 2.80 | -2.26 | 0.00132390 | 6131.4 | 29.02 | 11.52 | 0.00132390 | 32538.0 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1573216.637 | -999.000 | 89.916511 | 0.06692827 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0028 | 1004.8586 | 1.0531 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 89.916511 | 94.69466336 | 4197.9300 | 999.8980 | 85.24124917 | 12.27 | 6.67 | 5.60 | 2003886.06 | 78.5083 | 78.508288 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1573216.64 | 1557466.93 | 1.0000 | 94.69466336 | 89.916511 | 26.79 | 14.79 | 0.00708079 | 44980.5 | 10.67 | 8.50 | 0.00700000 | 28366.9 | 66.92144517 | 6.67 | 12.27 | 5.60 | 205344.836 | 1367871.80 | 33.40 | 0.00630683 | 16.37 | 25.38195000 | 28.2284 | 24.00 | 0.00740755 | 24.00 | 0.00740755 | 34.9375 | 1026402.33 | 0.00 | 1767640.89 | 1742304.83 | 94.69466336 | 26.79 | 16.15 | 0.00708079 | 44980.5 | 8.72 | 8.70 | 0.00697450 | 26313.7 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1074744.708 | 1074744.708 | 26.974953 | 0.00940234 | 15383.517 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 89.916511 | 94.69466336 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 32.7519 | 33.411033 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1074744.71 | 1074744.71 | 1.0000 | 28.40839901 | 26.974953 | -24.85 | -24.85 | 0.00078201 | -23049.7 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 9.40137641 | 60.00 | 32.22 | 27.78 | 0.000 | 1074744.71 | -27.60 | 0.00034190 | -27.60 | 25.38195000 | 94.0945 | 18.98 | 0.00779442 | 17.87 | 0.00777912 | 53.4488 | 358921.30 | 0.00 | 799478.82 | 799478.82 | 28.40839901 | 2.80 | -3.15 | 0.00078201 | 4773.4 | 30.77 | 11.69 | 0.00078201 | 32915.7 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 171295.368 | -999.000 | 10.042189 | 0.00728730 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0074 | 1004.8586 | 1.0531 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.042189 | 10.57583006 | 4197.9300 | 999.8980 | 85.24124917 | 12.27 | 6.67 | 5.60 | 2003886.06 | 8.5482 | 8.548159 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 171295.37 | 169493.60 | 1.0000 | 10.57583006 | 10.042189 | 26.39 | 14.65 | 0.00708324 | 44575.3 | 10.68 | 8.51 | 0.00700000 | 28378.4 | 7.28655756 | 6.67 | 12.27 | 5.60 | 22811.769 | 148483.60 | 33.40 | 0.00630683 | 16.37 | 2.53819000 | 25.2753 | 24.00 | 0.00734741 | 24.00 | 0.00734741 | 34.6571 | 120021.13 | 0.00 | 192905.44 | 190145.41 | 10.57583006 | 26.39 | 16.01 | 0.00708324 | 44575.3 | 8.72 | 8.71 | 0.00697956 | 26335.1 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 104881.897 | 104881.897 | 3.012657 | 0.00091755 | 1557.330 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.042189 | 10.57583006 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 3.1962 | 3.260507 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 104881.90 | 104881.90 | 1.0000 | 3.17274902 | 3.012657 | -20.10 | -20.10 | 0.00151754 | -16456.0 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.91745899 | 60.00 | 32.22 | 27.78 | 0.000 | 104881.90 | -27.60 | 0.00034190 | -27.60 | 2.53819000 | 84.2509 | 20.04 | 0.00780668 | 17.22 | 0.00779965 | 55.8394 | 50607.84 | 0.00 | 81665.29 | 81665.29 | 3.17274902 | 2.80 | -1.95 | 0.00151754 | 6616.7 | 28.34 | 11.44 | 0.00151754 | 32356.3 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 91921.222 | -999.000 | 5.513176 | 0.00391054 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3421 | 1004.8586 | 1.0531 | CAV_BAS FAN | Fan:ConstantVolume | 5.513176 | 5.80614591 | 4197.9300 | 999.8980 | 85.24124917 | 12.27 | 6.67 | 5.60 | 2003886.06 | 4.5871 | 4.587148 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 91921.22 | 88891.11 | 1.0000 | 5.80614591 | 5.513176 | 26.11 | 14.71 | 0.00726328 | 44757.5 | 11.22 | 8.74 | 0.00700000 | 28925.8 | 3.91014238 | 6.67 | 12.27 | 5.60 | 9348.441 | 82572.78 | 32.60 | 0.00630558 | 16.10 | 1.20019084 | 21.7695 | 24.00 | 0.00757554 | 24.00 | 0.00757554 | 35.7206 | 58594.84 | 0.00 | 103503.08 | 101163.93 | 5.80614591 | 26.11 | 16.07 | 0.00726328 | 44757.5 | 9.00 | 8.97 | 0.00710326 | 26931.0 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 268429.258 | 268429.258 | 5.513176 | 0.00234834 | 5691.921 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | CAV_BAS FAN | Fan:ConstantVolume | 5.513176 | 5.80614591 | 4197.9300 | 999.8980 | 28.13853899 | 54.44 | 82.22 | 27.78 | 3281474.08 | 8.1801 | 8.344771 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 268429.26 | 268429.26 | 1.0000 | 5.80614591 | 5.513176 | -6.01 | -10.13 | 0.00034190 | -5186.2 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.34809669 | 60.00 | 32.22 | 27.78 | 0.000 | 268429.26 | -27.60 | 0.00034190 | -27.60 | 1.20019084 | 21.7695 | 0.00 | 0.00034190 | 22.97 | 0.00034190 | 1.7353 | 0.00 | 0.00 | 211861.70 | 211861.70 | 5.80614591 | 12.80 | 2.46 | 0.00034190 | 13725.2 | 49.09 | 18.11 | 0.00034190 | 50214.4 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10177.414 | 5787.057 | 0.550797 | 0.00024924 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9708 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 8796.99 | 8731.62 | 0.8644 | -999.0 | -999.0 | 28.07 | 15.21 | 0.00706357 | 46238.1 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8796.99 | 26.57 | 0.00629632 | 14.04 | 0.01563279 | -999.0000 | 27.00 | 0.00708599 | 27.00 | 0.00708599 | 27.9814 | 8383.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 97434.046 | 55390.678 | 5.271288 | 0.00238615 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9759 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 84223.50 | 83570.94 | 0.8644 | -999.0 | -999.0 | 28.07 | 15.21 | 0.00706631 | 46244.4 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84223.50 | 26.57 | 0.00629632 | 14.04 | 0.15632792 | -999.0000 | 27.00 | 0.00708985 | 27.00 | 0.00708985 | 27.9966 | 80227.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9925.991 | 5643.369 | 0.537081 | 0.00024309 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9738 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 8579.97 | 8514.62 | 0.8644 | -999.0 | -999.0 | 28.07 | 15.21 | 0.00706518 | 46241.8 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8579.97 | 26.57 | 0.00629632 | 14.04 | 0.01563279 | -999.0000 | 27.00 | 0.00708823 | 27.00 | 0.00708823 | 27.9902 | 8174.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10177.414 | 10177.414 | 0.550797 | 0.00024924 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10177.41 | 10177.41 | 1.0000 | 0.58006614 | 0.550797 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10177.41 | -27.60 | 0.00034190 | -27.60 | 0.01563279 | 2.8382 | 0.00 | 0.00098087 | 25.23 | 0.00098087 | 4.3430 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 97434.046 | 97434.046 | 5.271288 | 0.00238615 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 97434.05 | 97434.05 | 1.0000 | 5.55140315 | 5.271288 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 97434.05 | -27.60 | 0.00034190 | -27.60 | 0.15632792 | 2.9656 | 0.00 | 0.00097461 | 23.63 | 0.00097461 | 4.7491 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9925.991 | 9925.991 | 0.537081 | 0.00024309 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9925.99 | 9925.99 | 1.0000 | 0.56562188 | 0.537081 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9925.99 | -27.60 | 0.00034190 | -27.60 | 0.01563279 | 2.9107 | 0.00 | 0.00097402 | 22.04 | 0.00097402 | 5.2258 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1118.341 | 1118.341 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.550797 | 0.58006614 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1118.34 | 1118.34 | 1.0000 | 0.58006614 | 0.550797 | -0.78 | -5.62 | 0.00096273 | 1619.2 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1118.34 | -27.60 | 0.00034190 | -27.60 | 0.01563279 | 2.8382 | 0.00 | 0.00098087 | 25.23 | 0.00098087 | 4.3430 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11183.410 | 11183.410 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.271288 | 5.55140315 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 11183.41 | 11183.41 | 1.0000 | 5.55140315 | 5.271288 | -0.82 | -5.66 | 0.00095584 | 1566.6 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11183.41 | -27.60 | 0.00034190 | -27.60 | 0.15632792 | 2.9656 | 0.00 | 0.00097461 | 23.63 | 0.00097461 | 4.7491 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1118.341 | 1118.341 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.537081 | 0.56562188 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1118.34 | 1118.34 | 1.0000 | 0.56562188 | 0.537081 | -0.80 | -5.65 | 0.00095562 | 1581.3 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1118.34 | -27.60 | 0.00034190 | -27.60 | 0.01563279 | 2.9107 | 0.00 | 0.00097402 | 22.04 | 0.00097402 | 5.2258 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.73 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 89.92 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.04 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.51 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | BASEMENT_DCV | 0.002360 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1491.83 | 1937.67 | 35.83 |
CORE_BOTTOM | 1208.17 | 2090.83 | 29.00 |
CORE_MID | 850.17 | 3942.50 | 289.00 |
CORE_TOP | 2065.67 | 4410.83 | 1482.67 |
PERIMETER_BOT_ZN_3 | 1574.67 | 3986.00 | 672.17 |
PERIMETER_BOT_ZN_2 | 2029.33 | 3720.50 | 827.83 |
PERIMETER_BOT_ZN_1 | 2153.33 | 3233.83 | 700.17 |
PERIMETER_BOT_ZN_4 | 2423.67 | 2563.33 | 460.00 |
PERIMETER_MID_ZN_3 | 2702.83 | 4506.83 | 2109.67 |
PERIMETER_MID_ZN_2 | 2534.33 | 3587.83 | 1684.17 |
PERIMETER_MID_ZN_1 | 2530.83 | 3619.33 | 1253.67 |
PERIMETER_MID_ZN_4 | 2783.33 | 4102.17 | 1675.00 |
PERIMETER_TOP_ZN_3 | 3479.00 | 4754.50 | 2919.83 |
PERIMETER_TOP_ZN_2 | 3579.33 | 4290.00 | 2558.83 |
PERIMETER_TOP_ZN_1 | 3068.67 | 4023.50 | 1971.33 |
PERIMETER_TOP_ZN_4 | 3379.83 | 4361.17 | 2373.00 |
DATACENTER_BOT_ZN_6 | 5771.33 | 181.83 | 180.33 |
DATACENTER_MID_ZN_6 | 5126.17 | 184.00 | 23.83 |
DATACENTER_TOP_ZN_6 | 4297.00 | 559.00 | 86.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5755.00 | 5755.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 59.50 | 0.00 | 4.00 |
CORE_BOTTOM | 0.00 | 2.00 | 0.00 | 0.00 |
CORE_MID | 0.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 25.50 | 0.00 | 6.67 | 0.00 |
PERIMETER_BOT_ZN_3 | 6.17 | 0.83 | 1.33 | 0.67 |
PERIMETER_BOT_ZN_2 | 5.50 | 21.33 | 0.50 | 21.17 |
PERIMETER_BOT_ZN_1 | 6.17 | 32.33 | 0.50 | 30.00 |
PERIMETER_BOT_ZN_4 | 2.00 | 84.00 | 0.00 | 30.17 |
PERIMETER_MID_ZN_3 | 118.33 | 0.00 | 52.17 | 0.00 |
PERIMETER_MID_ZN_2 | 51.33 | 21.67 | 6.67 | 21.50 |
PERIMETER_MID_ZN_1 | 35.33 | 29.00 | 4.67 | 27.17 |
PERIMETER_MID_ZN_4 | 35.67 | 26.83 | 5.50 | 12.50 |
PERIMETER_TOP_ZN_3 | 287.83 | 0.50 | 115.83 | 0.00 |
PERIMETER_TOP_ZN_2 | 159.33 | 24.17 | 30.17 | 22.50 |
PERIMETER_TOP_ZN_1 | 134.33 | 24.50 | 23.00 | 20.83 |
PERIMETER_TOP_ZN_4 | 112.50 | 27.17 | 18.50 | 11.67 |
DATACENTER_BOT_ZN_6 | 0.00 | 4.50 | 0.00 | 2.00 |
DATACENTER_MID_ZN_6 | 0.00 | 1.50 | 0.00 | 0.67 |
DATACENTER_TOP_ZN_6 | 0.00 | 3.50 | 0.00 | 1.33 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 309.83 | 252.17 | 117.83 | 127.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.70 | 149.60 | 6779.02 | 1.130 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.41 | 134.35 | 6849.35 | 0.888 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.41 | 134.35 | 6849.35 | 0.669 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.41 | 134.35 | 6849.35 | 0.632 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.96 | 16.87 | 860.00 | 0.802 | 0.024 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.48 | 10.87 | 554.22 | 1.337 | 0.024 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.96 | 16.87 | 860.02 | 1.329 | 0.024 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.48 | 10.87 | 554.22 | 1.803 | 0.024 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.96 | 16.87 | 860.00 | 0.668 | 0.055 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.91 | 10.87 | 554.22 | 1.198 | 0.060 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.96 | 16.87 | 860.02 | 1.235 | 0.055 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.48 | 10.87 | 554.22 | 1.270 | 0.057 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.96 | 16.87 | 860.00 | 0.740 | 0.068 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.48 | 10.87 | 554.22 | 1.275 | 0.071 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.96 | 16.87 | 860.02 | 1.191 | 0.068 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.48 | 10.87 | 554.22 | 1.289 | 0.071 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.40 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.70 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.41 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.41 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.41 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.96 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.96 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.96 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.91 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.96 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.96 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.96 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.40 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.70 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 0.847 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.41 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.41 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.41 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.96 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.96 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.96 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.91 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.96 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.96 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.96 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.011 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.110 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.011 |
DATACENTER_BASEMENT_ZN_6 | 17.40 | 42.18 | 1911.37 | 783.68 | 0.239 | ||
Total Facility | 1022.56 | 2493.19 | 126016.35 | 46320.38 | 1.3878 | 157.549 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 46814212.37 | 0.00 | 46814212.37 | 0.00 | 46814212.37 | 29876159.83 | 3898.28 | 1065.16 | 3796.56 | 343.95 |
CORE_BOTTOM | 38168487.35 | 0.00 | 38168487.35 | 0.00 | 38168487.35 | 33990283.35 | 4799.52 | 50.98 | 3909.50 | 482.60 |
CORE_MID | 0.28E+09 | 0.00 | 0.28E+09 | 0.00 | 0.28E+09 | 0.34E+09 | 6255.00 | 46.30 | 2458.70 | 313.18 |
CORE_TOP | 26162447.41 | 0.00 | 26162447.41 | 0.00 | 26162447.41 | 33990283.35 | 6611.79 | 34.74 | 2113.47 | 360.49 |
PERIMETER_BOT_ZN_3 | 4355820.70 | 0.00 | 4355820.70 | 236634.01 | 4592454.70 | 4267819.30 | 5564.30 | 58.37 | 3137.33 | 482.60 |
PERIMETER_BOT_ZN_2 | 4665082.47 | 0.00 | 4665082.47 | 157755.90 | 4822838.37 | 2750345.05 | 3500.74 | 11.63 | 5247.63 | 482.60 |
PERIMETER_BOT_ZN_1 | 7092797.88 | 0.00 | 7092797.88 | 236634.01 | 7329431.88 | 4267912.63 | 3812.57 | 51.53 | 4895.90 | 482.60 |
PERIMETER_BOT_ZN_4 | 6295205.89 | 0.00 | 6295205.89 | 157755.90 | 6452961.78 | 2750345.05 | 3452.39 | 2.53 | 5305.08 | 482.60 |
PERIMETER_MID_ZN_3 | 34873823.15 | 0.00 | 34873823.15 | 554973.83 | 35428796.98 | 42678193.03 | 5970.45 | 64.23 | 2725.32 | 313.18 |
PERIMETER_MID_ZN_2 | 43632225.24 | 0.00 | 43632225.24 | 369982.30 | 44002207.54 | 27503450.52 | 3957.11 | 6.95 | 4795.93 | 1222.18 |
PERIMETER_MID_ZN_1 | 63588898.92 | 0.00 | 63588898.92 | 554973.83 | 64143872.75 | 42679126.28 | 4031.60 | 3.59 | 4724.80 | 313.18 |
PERIMETER_MID_ZN_4 | 42752518.27 | 0.00 | 42752518.27 | 369982.30 | 43122500.57 | 27503450.52 | 3940.71 | 7.44 | 4811.84 | 313.18 |
PERIMETER_TOP_ZN_3 | 3859691.93 | 0.00 | 3859691.93 | 689060.14 | 4548752.06 | 4267819.30 | 4165.43 | 23.89 | 4570.68 | 360.49 |
PERIMETER_TOP_ZN_2 | 4248833.75 | 0.00 | 4248833.75 | 459373.11 | 4708206.86 | 2750345.05 | 4068.18 | 3.53 | 4688.29 | 360.49 |
PERIMETER_TOP_ZN_1 | 6135421.33 | 0.00 | 6135421.33 | 689060.14 | 6824481.47 | 4267912.63 | 4091.15 | 2.68 | 4666.17 | 360.49 |
PERIMETER_TOP_ZN_4 | 4330940.24 | 0.00 | 4330940.24 | 459373.11 | 4790313.35 | 2750345.05 | 4050.04 | 2.99 | 4706.97 | 360.49 |
DATACENTER_BOT_ZN_6 | 244303.03 | 0.00 | 244303.03 | 0.00 | 244303.03 | 389144.62 | 4419.00 | 504.00 | 3837.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2443030.26 | 0.00 | 2443030.26 | 0.00 | 2443030.26 | 3891446.16 | 4419.00 | 504.00 | 3837.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244303.03 | 0.00 | 244303.03 | 0.00 | 244303.03 | 389144.62 | 4419.00 | 504.00 | 3837.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8423799.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 0.48E+10 | 0.00 | 0.48E+10 | 21584768.85 | 0.48E+10 | 0.50E+10 | 8760.00 | 1704.24 | 5505.93 | 1855.20 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.0873 | 0.0000 | 2.0873 | 0.0000 | 2.0873 | 0.9949 | 1325.67 | 1062.08 | 3555.24 |
CORE_BOTTOM | 1.6567 | 0.0000 | 1.6567 | 0.0000 | 1.6567 | 1.0778 | 2363.70 | 48.13 | 3531.17 |
CORE_MID | 12.5044 | 0.0000 | 12.5044 | 0.0000 | 12.5044 | 10.7782 | 3549.42 | 46.24 | 2347.34 |
CORE_TOP | 1.1836 | 0.0000 | 1.1836 | 0.0000 | 1.1836 | 1.0778 | 3884.59 | 34.14 | 2024.27 |
PERIMETER_BOT_ZN_3 | 0.1881 | 0.0000 | 0.1881 | 0.0055 | 0.1937 | 0.1353 | 3123.32 | 55.23 | 2764.45 |
PERIMETER_BOT_ZN_2 | 0.2024 | 0.0000 | 0.2024 | 0.0037 | 0.2061 | 0.0872 | 1125.99 | 9.34 | 4807.67 |
PERIMETER_BOT_ZN_1 | 0.3119 | 0.0000 | 0.3119 | 0.0055 | 0.3174 | 0.1353 | 1405.41 | 49.73 | 4487.86 |
PERIMETER_BOT_ZN_4 | 0.2726 | 0.0000 | 0.2726 | 0.0037 | 0.2763 | 0.0872 | 1086.24 | 1.87 | 4854.89 |
PERIMETER_MID_ZN_3 | 1.5728 | 0.0000 | 1.5728 | 0.0130 | 1.5858 | 1.3533 | 3266.31 | 63.81 | 2612.88 |
PERIMETER_MID_ZN_2 | 1.8160 | 0.0000 | 1.8160 | 0.0092 | 1.8252 | 0.8721 | 1269.03 | 5.55 | 3759.42 |
PERIMETER_MID_ZN_1 | 2.8996 | 0.0000 | 2.8996 | 0.0130 | 2.9127 | 1.3533 | 1332.22 | 3.53 | 4607.25 |
PERIMETER_MID_ZN_4 | 1.9261 | 0.0000 | 1.9261 | 0.0087 | 1.9348 | 0.8721 | 1255.52 | 4.65 | 4682.83 |
PERIMETER_TOP_ZN_3 | 0.1745 | 0.0000 | 0.1745 | 0.0162 | 0.1906 | 0.1353 | 1441.16 | 23.48 | 4478.37 |
PERIMETER_TOP_ZN_2 | 0.1933 | 0.0000 | 0.1933 | 0.0108 | 0.2041 | 0.0872 | 1351.87 | 2.93 | 4588.20 |
PERIMETER_TOP_ZN_1 | 0.2800 | 0.0000 | 0.2800 | 0.0162 | 0.2961 | 0.1353 | 1368.45 | 2.52 | 4572.03 |
PERIMETER_TOP_ZN_4 | 0.1956 | 0.0000 | 0.1956 | 0.0108 | 0.2064 | 0.0872 | 1338.35 | 2.25 | 4602.40 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0130 | 1602.00 | 504.00 | 3837.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1296 | 1602.00 | 504.00 | 3837.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0130 | 1602.00 | 504.00 | 3837.00 |
DATACENTER_BASEMENT_ZN_6 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.2805 | 5943.00 | 0.00 | 0.00 |
Total Facility | 215.1005 | 0.0000 | 215.1005 | 0.5111 | 215.6116 | 157.9346 | 5943.00 | 1686.78 | 4922.45 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 67186607.02 | 0.00 | 67186607.02 | 48026705.38 | 3582.48 | 7.03 | 5170.49 | 482.60 |
VAV_MID WITH REHEAT | 0.51E+09 | 0.00 | 0.51E+09 | 0.48E+09 | 4045.29 | 4.79 | 4709.92 | 313.18 |
VAV_TOP WITH REHEAT | 49618339.37 | 0.00 | 49618339.37 | 48026705.38 | 4102.84 | 0.81 | 4656.35 | 360.07 |
CAV_BAS | 51921811.80 | 0.00 | 51921811.80 | 29876159.83 | 3881.13 | 3.54 | 4875.33 | 343.95 |
AIRLOOP DATACENTER BOT | 270957.37 | 0.00 | 270957.37 | 389144.62 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 2709573.68 | 0.00 | 2709573.68 | 3891446.16 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 270957.37 | 0.00 | 270957.37 | 389144.62 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.9189 | 0.0000 | 2.9189 | 1.5229 | 1174.77 | 4.78 | 4763.44 |
VAV_MID WITH REHEAT | 23.1594 | 0.0000 | 23.1594 | 15.2292 | 1342.06 | 4.27 | 4596.67 |
VAV_TOP WITH REHEAT | 2.2480 | 0.0000 | 2.2480 | 1.5229 | 1378.09 | 0.77 | 4564.14 |
CAV_BAS | 2.3150 | 0.0000 | 2.3150 | 0.9949 | 1322.08 | 0.70 | 4620.22 |
AIRLOOP DATACENTER BOT | 0.0127 | 0.0000 | 0.0127 | 0.0130 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1266 | 0.0000 | 0.1266 | 0.1296 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0127 | 0.0000 | 0.0127 | 0.0130 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.07 | 3682.33 | 0.00 | 0.00 | 0.00 | 1697.44 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.11 | 3521.94 | 0.00 | 0.00 | 0.00 | 1608.46 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 2788.46 | 0.00 | 0.00 | 0.00 | 2378.75 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 0.00 | 3940.18 | 0.00 | 0.00 | 0.00 | 1055.82 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 4.4117 | 0.0000 | 0.0000 | 0.0000 | 1.9053 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 33.6001 | 0.0000 | 0.0000 | 0.0000 | 18.5550 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 3.7000 | 0.0000 | 0.0000 | 0.0000 | 1.8404 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 0.0000 | 3.4940 | 0.0000 | 0.0000 | 0.0000 | 1.1315 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1734 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 7 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1352 |
Defaulted Fields | 1168 |
Fields with Defaults | 3820 |
Autosized Fields | 313 |
Autosizable Fields | 391 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 22526.12 | 284390.32 | 29-JAN-04:00 | 1598375.19 | 08-AUG-15:40 |
Electricity:Building | 16704.92 | 216770.18 | 06-MAY-18:10 | 977223.71 | 01-DEC-16:40 |
Electricity:Zone:BASEMENT | 559.97 | 14115.26 | 01-JAN-00:10 | 25295.37 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16704.92 | 216770.18 | 06-MAY-18:10 | 977223.71 | 01-DEC-16:40 |
InteriorLights:Electricity | 2028.52 | 9514.02 | 01-JAN-11:30 | 198852.03 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 135.58 | 657.72 | 01-JAN-00:10 | 11837.83 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2028.52 | 9514.02 | 01-JAN-11:30 | 198852.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 2028.52 | 9514.02 | 01-JAN-11:30 | 198852.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 135.58 | 657.72 | 01-JAN-00:10 | 11837.83 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2028.52 | 9514.02 | 01-JAN-11:30 | 198852.03 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 411.37 | 5043.91 | 01-JAN-00:10 | 27837.83 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4113.71 | 50438.97 | 01-JAN-00:10 | 278377.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1217.58 | 5906.80 | 01-JAN-00:10 | 106312.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1217.58 | 5906.80 | 01-JAN-00:10 | 106312.04 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 411.37 | 5043.90 | 01-JAN-00:10 | 27837.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 45.46 | 594.46 | 26-MAR-17:10 | 3495.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.10 | 35.29 | 01-JAN-11:30 | 1334.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.10 | 35.29 | 01-JAN-11:30 | 1334.85 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 29.21 | 383.09 | 26-MAR-17:10 | 2252.57 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.77 | 22.74 | 01-JAN-08:50 | 860.23 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.77 | 22.74 | 01-JAN-08:50 | 860.23 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 45.23 | 594.47 | 12-MAR-17:10 | 3495.47 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.87 | 35.29 | 01-JAN-08:50 | 1334.88 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.87 | 35.29 | 01-JAN-08:50 | 1334.88 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 29.23 | 383.09 | 12-MAR-17:10 | 2252.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.80 | 22.74 | 01-JAN-11:10 | 860.23 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.80 | 22.74 | 01-JAN-11:10 | 860.23 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 454.67 | 5944.59 | 26-MAR-17:10 | 34954.06 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 91.01 | 352.88 | 01-JAN-11:20 | 13348.54 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 91.01 | 352.88 | 01-JAN-11:20 | 13348.54 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 292.08 | 3830.92 | 26-MAR-17:10 | 22525.72 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 57.72 | 227.41 | 01-JAN-09:00 | 8602.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 57.72 | 227.41 | 01-JAN-09:00 | 8602.31 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 452.35 | 5944.68 | 12-MAR-17:10 | 34954.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 88.69 | 352.89 | 01-JAN-09:00 | 13348.83 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 88.69 | 352.89 | 01-JAN-09:00 | 13348.83 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 292.32 | 3830.90 | 12-MAR-17:10 | 22525.63 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 57.96 | 227.41 | 01-JAN-11:00 | 8602.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 57.96 | 227.41 | 01-JAN-11:00 | 8602.31 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 45.47 | 594.46 | 26-MAR-17:10 | 3495.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.10 | 35.29 | 01-JAN-11:20 | 1334.85 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.10 | 35.29 | 01-JAN-11:20 | 1334.85 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 29.21 | 383.09 | 26-MAR-17:10 | 2252.57 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.77 | 22.74 | 01-JAN-09:00 | 860.23 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.77 | 22.74 | 01-JAN-09:00 | 860.23 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 45.23 | 594.47 | 12-MAR-17:10 | 3495.47 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.87 | 35.29 | 01-JAN-09:00 | 1334.88 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.87 | 35.29 | 01-JAN-09:00 | 1334.88 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 29.23 | 383.09 | 12-MAR-17:10 | 2252.56 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.80 | 22.74 | 01-JAN-11:00 | 860.23 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.80 | 22.74 | 01-JAN-11:00 | 860.23 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7533.08 | 95093.58 | 01-JAN-00:10 | 382970.28 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 38.23 | 185.45 | 01-JAN-00:10 | 3337.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 38.23 | 185.45 | 01-JAN-00:10 | 3337.76 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.14 | 1964.44 | 01-JAN-00:10 | 8079.39 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1571.44 | 19644.38 | 01-JAN-00:10 | 80793.90 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 32.64 | 158.32 | 01-JAN-00:10 | 2849.68 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 32.64 | 158.32 | 01-JAN-00:10 | 2849.68 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.14 | 1964.44 | 01-JAN-00:10 | 8079.39 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 798.22 | 119.24 | 07-JAN-17:30 | 371888.36 | 07-SEP-15:00 |
HeatRejection:Electricity | 150.74 | 0.00 | 07-JAN-17:30 | 39494.40 | 06-JUN-14:50 |
General:HeatRejection:Electricity | 150.74 | 0.00 | 07-JAN-17:30 | 39494.40 | 06-JUN-14:50 |
Electricity:HVAC | 1563.29 | 8174.87 | 08-JAN-22:40 | 259463.37 | 11-AUG-15:40 |
ExteriorEquipment:Electricity | 3183.22 | 44296.28 | 01-JAN-00:10 | 181402.89 | 13-DEC-08:20 |
Transformer:ExteriorEquipment:Electricity | 54.48 | 979.82 | 01-JAN-00:10 | 3387.38 | 01-DEC-16:50 |
ElectricityPurchased:Facility | 22526.12 | 284390.32 | 29-JAN-04:00 | 1598375.19 | 08-AUG-15:40 |
ElectricityPurchased:Plant | 22526.12 | 284390.32 | 29-JAN-04:00 | 1598375.19 | 08-AUG-15:40 |
Cogeneration:ElectricityPurchased | 22526.12 | 284390.32 | 29-JAN-04:00 | 1598375.19 | 08-AUG-15:40 |
General:Cogeneration:ElectricityPurchased | 22526.12 | 284390.32 | 29-JAN-04:00 | 1598375.19 | 08-AUG-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 22526.12 | 284390.32 | 29-JAN-04:00 | 1598375.19 | 08-AUG-15:40 |
ElectricityNet:Plant | 22526.12 | 284390.32 | 29-JAN-04:00 | 1598375.19 | 08-AUG-15:40 |
Cogeneration:ElectricityNet | 22526.12 | 284390.32 | 29-JAN-04:00 | 1598375.19 | 08-AUG-15:40 |
General:Cogeneration:ElectricityNet | 22526.12 | 284390.32 | 29-JAN-04:00 | 1598375.19 | 08-AUG-15:40 |
Fans:Electricity | 1177.24 | 7122.95 | 01-JAN-00:10 | 231088.31 | 26-JUL-15:20 |
General:Fans:Electricity | 1177.24 | 7122.95 | 01-JAN-00:10 | 231088.31 | 26-JUL-15:20 |
ExteriorLights:Electricity | 330.95 | 0.00 | 01-JAN-08:20 | 37611.08 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 330.95 | 0.00 | 01-JAN-08:20 | 37611.08 | 01-JAN-06:10 |
ComputerHVAC:ExteriorEquipment:Electricity | 1274.13 | 16134.39 | 01-JAN-00:10 | 64537.54 | 31-MAR-23:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 701.92 | 0.00 | 07-JAN-17:30 | 294589.30 | 07-SEP-15:00 |
General:Cooling:Electricity | 701.92 | 0.00 | 07-JAN-17:30 | 294589.30 | 07-SEP-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 277.14 | 119.24 | 07-JAN-17:30 | 47997.75 | 05-SEP-12:40 |
General:Pumps:Electricity | 277.14 | 119.24 | 07-JAN-17:30 | 47997.75 | 05-SEP-12:40 |
WIRED_LTG_ELECTRICITY | 57.00 | 0.00 | 01-JAN-00:10 | 5587.74 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4096.91 | 5695.87 | 04-FEB-05:40 | 2328249.77 | 09-JAN-07:20 |
NaturalGas:Plant | 4096.91 | 5695.87 | 04-FEB-05:40 | 2328249.77 | 09-JAN-07:20 |
Heating:NaturalGas | 3325.34 | 0.00 | 01-JAN-00:10 | 2299529.62 | 09-JAN-07:20 |
Boiler:Heating:NaturalGas | 3325.34 | 0.00 | 01-JAN-00:10 | 2299529.62 | 09-JAN-07:20 |
WaterSystems:NaturalGas | 771.56 | 5695.87 | 02-JAN-04:20 | 85520.58 | 14-FEB-12:20 |
Water Heater:WaterSystems:NaturalGas | 771.56 | 5695.87 | 02-JAN-04:20 | 85520.58 | 14-FEB-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 4910.29 | 0.00 | 07-JAN-17:30 | 1984079.16 | 07-SEP-15:00 |
PlantLoopCoolingDemand:HVAC | 4910.29 | 0.00 | 07-JAN-17:30 | 1984079.16 | 07-SEP-15:00 |
CoolingCoils:PlantLoopCoolingDemand | 4910.29 | 0.00 | 07-JAN-17:30 | 1984079.16 | 07-SEP-15:00 |
DistrictCooling:Facility | 7167.51 | 83226.79 | 09-JAN-05:00 | 370300.48 | 07-AUG-16:00 |
DistrictCooling:HVAC | 7167.51 | 83226.79 | 09-JAN-05:00 | 370300.48 | 07-AUG-16:00 |
Cooling:DistrictCooling | 7167.51 | 83226.79 | 09-JAN-05:00 | 370300.48 | 07-AUG-16:00 |
General:Cooling:DistrictCooling | 7167.51 | 83226.79 | 09-JAN-05:00 | 370300.48 | 07-AUG-16:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 4923.10 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-11:50 |
Water:Plant | 4923.10 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-11:50 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 4923.10 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-11:50 |
MainsWater:Plant | 4923.10 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-11:50 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 2642.93 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
General:HeatRejection:Water | 2642.93 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
HeatRejection:MainsWater | 2642.93 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
General:HeatRejection:MainsWater | 2642.93 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 36519.95 | 90655.69 | 30-JAN-06:00 | 9248909.36 | 07-SEP-15:00 |
EnergyTransfer:Building | 17079.65 | 87713.69 | 14-JAN-18:30 | 1562859.57 | 07-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 577.49 | 0.00 | 01-JAN-00:10 | 67541.80 | 05-SEP-05:10 |
Heating:EnergyTransfer | 843.75 | 0.00 | 01-FEB-00:10 | 1208194.71 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.17 | 0.00 | 01-JAN-00:10 | 16787.91 | 05-AUG-16:10 |
General:Heating:EnergyTransfer | 843.75 | 0.00 | 01-FEB-00:10 | 1208194.71 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 3.17 | 0.00 | 01-JAN-00:10 | 16787.91 | 05-AUG-16:10 |
Cooling:EnergyTransfer | 16235.90 | 83231.18 | 09-JAN-05:50 | 1562859.57 | 07-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 574.32 | 0.00 | 01-JAN-00:10 | 67541.80 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer | 16235.90 | 83231.18 | 09-JAN-05:50 | 1562859.57 | 07-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 574.32 | 0.00 | 01-JAN-00:10 | 67541.80 | 05-SEP-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 522.74 | 0.00 | 01-JAN-00:10 | 49090.07 | 07-AUG-09:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 522.74 | 0.00 | 01-JAN-00:10 | 49090.07 | 07-AUG-09:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 522.74 | 0.00 | 01-JAN-00:10 | 49090.07 | 07-AUG-09:10 |
EnergyTransfer:Zone:CORE_MID | 3568.38 | 0.00 | 01-JAN-00:10 | 379692.79 | 14-AUG-10:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 9.32 | 0.00 | 01-JAN-00:10 | 366530.61 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 9.32 | 0.00 | 01-JAN-00:10 | 366530.61 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 3559.06 | 0.00 | 01-JAN-00:10 | 379692.79 | 14-AUG-10:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 3559.06 | 0.00 | 01-JAN-00:10 | 379692.79 | 14-AUG-10:00 |
EnergyTransfer:Zone:CORE_TOP | 323.32 | 0.00 | 01-JAN-00:10 | 63844.30 | 09-JAN-04:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 27.25 | 0.00 | 01-JAN-00:10 | 63844.30 | 09-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 27.25 | 0.00 | 01-JAN-00:10 | 63844.30 | 09-JAN-04:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 296.07 | 0.00 | 01-JAN-00:10 | 46545.83 | 17-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 296.07 | 0.00 | 01-JAN-00:10 | 46545.83 | 17-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 56.44 | 0.00 | 01-JAN-00:10 | 10730.36 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.97 | 0.00 | 01-JAN-00:10 | 10730.36 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.97 | 0.00 | 01-JAN-00:10 | 10730.36 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 53.47 | 0.00 | 01-JAN-00:10 | 9280.94 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 53.47 | 0.00 | 01-JAN-00:10 | 9280.94 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 57.07 | 0.00 | 01-JAN-00:10 | 13527.42 | 07-AUG-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.16 | 0.00 | 01-JAN-00:10 | 8955.58 | 11-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.16 | 0.00 | 01-JAN-00:10 | 8955.58 | 11-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 54.91 | 0.00 | 01-JAN-00:10 | 13527.42 | 07-AUG-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 54.91 | 0.00 | 01-JAN-00:10 | 13527.42 | 07-AUG-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 93.48 | 0.00 | 01-JAN-00:10 | 18654.99 | 18-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 3.02 | 0.00 | 01-JAN-00:10 | 14759.49 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 3.02 | 0.00 | 01-JAN-00:10 | 14759.49 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 90.46 | 0.00 | 01-JAN-00:10 | 18654.99 | 18-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 90.46 | 0.00 | 01-JAN-00:10 | 18654.99 | 18-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 83.89 | 0.00 | 01-JAN-00:10 | 16224.86 | 07-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.60 | 0.00 | 01-JAN-00:10 | 6424.97 | 11-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.60 | 0.00 | 01-JAN-00:10 | 6424.97 | 11-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 83.29 | 0.00 | 01-JAN-00:10 | 16224.86 | 07-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 83.29 | 0.00 | 01-JAN-00:10 | 16224.86 | 07-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 510.29 | 0.00 | 01-JAN-00:10 | 112719.84 | 09-JAN-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 172.62 | 0.00 | 01-JAN-00:10 | 112719.84 | 09-JAN-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 172.62 | 0.00 | 01-JAN-00:10 | 112719.84 | 09-JAN-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 337.67 | 0.00 | 01-JAN-00:10 | 82792.90 | 18-JUL-12:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 337.67 | 0.00 | 01-JAN-00:10 | 82792.90 | 18-JUL-12:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 542.34 | 0.00 | 01-JAN-00:10 | 136858.33 | 07-AUG-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 101.15 | 0.00 | 01-JAN-00:10 | 135084.61 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 101.15 | 0.00 | 01-JAN-00:10 | 135084.61 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 441.20 | 0.00 | 01-JAN-00:10 | 136858.33 | 07-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 441.20 | 0.00 | 01-JAN-00:10 | 136858.33 | 07-AUG-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 861.96 | 0.00 | 01-JAN-00:10 | 191632.88 | 18-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 96.83 | 0.00 | 01-JAN-00:10 | 170950.06 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 96.83 | 0.00 | 01-JAN-00:10 | 170950.06 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 765.13 | 0.00 | 01-JAN-00:10 | 191632.88 | 18-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 765.13 | 0.00 | 01-JAN-00:10 | 191632.88 | 18-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 536.34 | 0.00 | 01-JAN-00:10 | 143935.52 | 17-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 77.52 | 0.00 | 01-JAN-00:10 | 132047.14 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 77.52 | 0.00 | 01-JAN-00:10 | 132047.14 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 458.82 | 0.00 | 01-JAN-00:10 | 143935.52 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 458.82 | 0.00 | 01-JAN-00:10 | 143935.52 | 17-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 74.48 | 0.00 | 01-JAN-00:10 | 15461.11 | 09-JAN-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 44.03 | 0.00 | 01-JAN-00:10 | 15461.11 | 09-JAN-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 44.03 | 0.00 | 01-JAN-00:10 | 15461.11 | 09-JAN-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.45 | 0.00 | 01-JAN-00:10 | 9562.23 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.45 | 0.00 | 01-JAN-00:10 | 9562.23 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 64.65 | 0.00 | 01-JAN-00:10 | 15375.01 | 09-JAN-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 24.92 | 0.00 | 01-JAN-00:10 | 15375.01 | 09-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 24.92 | 0.00 | 01-JAN-00:10 | 15375.01 | 09-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 39.73 | 0.00 | 01-JAN-00:10 | 13976.34 | 07-AUG-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 39.73 | 0.00 | 01-JAN-00:10 | 13976.34 | 07-AUG-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 95.43 | 0.00 | 01-JAN-00:10 | 20274.64 | 01-SEP-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 28.01 | 0.00 | 01-JAN-00:10 | 20239.42 | 09-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 28.01 | 0.00 | 01-JAN-00:10 | 20239.42 | 09-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 67.42 | 0.00 | 01-JAN-00:10 | 20274.64 | 01-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 67.42 | 0.00 | 01-JAN-00:10 | 20274.64 | 01-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 61.99 | 0.00 | 01-JAN-00:10 | 16422.89 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 20.20 | 0.00 | 01-JAN-00:10 | 16422.89 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 20.20 | 0.00 | 01-JAN-00:10 | 16422.89 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 41.78 | 0.00 | 01-JAN-00:10 | 15333.97 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 41.78 | 0.00 | 01-JAN-00:10 | 15333.97 | 17-JUL-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 44.96 | 0.00 | 01-JAN-00:10 | 9201.88 | 07-AUG-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 5.69 | 0.00 | 01-JAN-00:10 | 6136.81 | 30-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 5.69 | 0.00 | 01-JAN-00:10 | 6136.81 | 30-JAN-13:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 39.28 | 0.00 | 01-JAN-00:10 | 9201.88 | 07-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 39.28 | 0.00 | 01-JAN-00:10 | 9201.88 | 07-AUG-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 384.77 | 0.00 | 01-JAN-00:10 | 110420.99 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 150.28 | 0.00 | 01-JAN-00:10 | 110420.99 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 150.28 | 0.00 | 01-JAN-00:10 | 110420.99 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 234.49 | 0.00 | 01-JAN-00:10 | 66422.20 | 17-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 234.49 | 0.00 | 01-JAN-00:10 | 66422.20 | 17-JUL-15:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 105.59 | 0.00 | 01-JAN-00:10 | 30985.39 | 11-JAN-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 66.78 | 0.00 | 01-JAN-00:10 | 30985.39 | 11-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 66.78 | 0.00 | 01-JAN-00:10 | 30985.39 | 11-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 38.82 | 0.00 | 01-JAN-00:10 | 20956.76 | 17-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 38.82 | 0.00 | 01-JAN-00:10 | 20956.76 | 17-JUL-15:10 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.09 | 5.15 | 28-JAN-06:50 | 8166.50 | 22-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.07 | 0.00 | 01-JAN-00:10 | 594.62 | 09-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.07 | 0.00 | 01-JAN-00:10 | 594.62 | 09-JAN-04:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.01 | 0.00 | 07-JAN-23:00 | 8166.50 | 22-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.01 | 0.00 | 07-JAN-23:00 | 8166.50 | 22-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1135.68 | 2.04 | 11-JAN-09:40 | 77428.57 | 03-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 6.04 | 0.00 | 01-JAN-15:20 | 6519.35 | 29-JAN-17:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 6.04 | 0.00 | 01-JAN-15:20 | 6519.35 | 29-JAN-17:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1129.65 | 0.00 | 01-JAN-00:10 | 77428.57 | 03-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1129.65 | 0.00 | 01-JAN-00:10 | 77428.57 | 03-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 101.37 | 0.23 | 18-JAN-11:50 | 7895.69 | 05-AUG-19:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.14 | 0.00 | 02-JAN-14:30 | 727.44 | 30-APR-23:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.14 | 0.00 | 02-JAN-14:30 | 727.44 | 30-APR-23:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 100.23 | 0.00 | 01-JAN-00:10 | 7895.69 | 05-AUG-19:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 100.23 | 0.00 | 01-JAN-00:10 | 7895.69 | 05-AUG-19:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7142.91 | 83226.79 | 09-JAN-05:00 | 367701.48 | 07-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7142.91 | 83226.79 | 09-JAN-05:00 | 367701.48 | 07-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7142.91 | 83226.79 | 09-JAN-05:00 | 367701.48 | 07-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 3037.76 | 0.00 | 01-JAN-00:10 | 1971311.69 | 09-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 463.31 | 0.00 | 01-JAN-00:10 | 57401.81 | 17-FEB-12:50 |
WaterSystems:PlantLoopHeatingDemand | 463.31 | 0.00 | 01-JAN-00:10 | 57401.81 | 17-FEB-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 463.31 | 0.00 | 01-JAN-00:10 | 57401.81 | 17-FEB-12:50 |
EnergyTransfer:HVAC | 7153.17 | 217.96 | 08-JAN-22:40 | 1976075.20 | 07-SEP-15:00 |
HeatingCoils:EnergyTransfer | 2574.45 | 0.00 | 01-JAN-00:10 | 1952748.92 | 09-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 2574.45 | 0.00 | 01-JAN-00:10 | 1952748.92 | 09-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 2574.45 | 0.00 | 01-JAN-00:10 | 1952748.92 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 4578.72 | 0.00 | 07-JAN-17:30 | 1976075.20 | 07-SEP-15:00 |
DistrictHeating:Facility | 0.00 | 0.00 | 01-JAN-00:40 | 14.26 | 01-FEB-00:30 |
DistrictHeating:HVAC | 0.00 | 0.00 | 01-JAN-00:40 | 14.26 | 01-FEB-00:30 |
Heating:DistrictHeating | 0.00 | 0.00 | 01-JAN-00:40 | 14.26 | 01-FEB-00:30 |
General:Heating:DistrictHeating | 0.00 | 0.00 | 01-JAN-00:40 | 14.26 | 01-FEB-00:30 |
EnergyTransfer:Plant | 12287.12 | 0.00 | 01-JAN-00:10 | 6246270.23 | 07-SEP-15:00 |
LoopToLoop:EnergyTransfer | 3128.62 | -2316.24 | 25-FEB-13:50 | 1976919.28 | 07-SEP-15:00 |
WaterSystems:EnergyTransfer | 463.31 | 0.00 | 01-JAN-00:10 | 57401.81 | 17-FEB-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 463.31 | 0.00 | 01-JAN-00:10 | 57401.81 | 17-FEB-12:50 |
Boilers:EnergyTransfer | 2561.20 | 0.00 | 01-JAN-00:10 | 1919616.61 | 09-JAN-07:20 |
Chillers:EnergyTransfer | 2881.83 | 0.00 | 01-JAN-00:10 | 1978323.13 | 07-SEP-15:00 |
HeatRejection:EnergyTransfer | 3252.18 | 0.00 | 01-JAN-00:10 | 2264908.47 | 07-SEP-15:00 |
General:HeatRejection:EnergyTransfer | 3252.18 | 0.00 | 01-JAN-00:10 | 2264908.47 | 07-SEP-15:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.170 | -574.321 | 0.000 | 0.000 | 93.325 | 135.577 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -82.148 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -522.739 | 0.000 | 0.000 | 83.701 | 121.758 | 289.614 | 0.000 | 0.000 | 0.000 | 27.666 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 9.320 | -3559.047 | 0.000 | 0.000 | 860.318 | 1217.578 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1424.296 |
CORE_TOP | 0.000 | 0.000 | 27.248 | -296.068 | 0.000 | 0.000 | 90.174 | 121.758 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -232.725 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 2.971 | -53.467 | 0.000 | 0.000 | 10.995 | 9.099 | 36.365 | 21.421 | 0.000 | 0.035 | 36.444 | 0.000 | -59.683 | 0.000 | -4.180 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 2.156 | -54.913 | 0.000 | 0.000 | 7.127 | 5.773 | 23.435 | 49.792 | 0.000 | 0.023 | 5.990 | 0.000 | -36.626 | 0.000 | -2.758 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 3.020 | -90.458 | 0.000 | 0.000 | 10.900 | 8.866 | 36.366 | 108.092 | 0.000 | 0.033 | 0.000 | 0.000 | -54.268 | 0.000 | -4.210 | -18.342 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.603 | -83.287 | 0.000 | 0.000 | 6.948 | 5.797 | 23.435 | 46.596 | 0.000 | 0.022 | 44.809 | 0.000 | -41.906 | 0.000 | -3.017 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 172.616 | -337.670 | 0.000 | 0.000 | 115.481 | 91.012 | 363.654 | 224.766 | 0.000 | 0.847 | 3.993 | 0.000 | -546.879 | 0.000 | -87.820 | -0.002 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 101.146 | -441.196 | 0.000 | 0.000 | 54.212 | 57.723 | 234.352 | 501.026 | 0.000 | 0.527 | 0.002 | 0.000 | -345.228 | 0.000 | -59.882 | -102.680 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 96.830 | -765.119 | 0.000 | 0.000 | 111.192 | 88.686 | 363.660 | 1079.149 | 0.000 | 0.750 | 0.052 | 0.000 | -527.146 | 0.000 | -94.427 | -353.574 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 77.521 | -458.810 | 0.000 | 0.000 | 74.064 | 57.964 | 234.351 | 477.393 | 0.000 | 0.519 | 0.008 | 0.000 | -372.363 | 0.000 | -61.625 | -29.014 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 44.026 | -30.450 | 0.000 | 0.000 | 11.811 | 9.101 | 36.365 | 23.206 | 0.000 | 0.104 | 0.001 | 0.000 | -51.493 | 0.000 | -10.205 | -32.466 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 24.921 | -39.731 | 0.000 | 0.000 | 7.466 | 5.772 | 23.435 | 50.586 | 0.000 | 0.062 | 0.000 | 0.000 | -32.713 | 0.000 | -7.003 | -32.797 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 28.009 | -67.418 | 0.000 | 0.000 | 11.375 | 8.868 | 36.366 | 108.772 | 0.000 | 0.090 | 0.000 | 0.000 | -49.690 | 0.000 | -10.962 | -65.409 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 20.203 | -41.781 | 0.000 | 0.000 | 7.540 | 5.796 | 23.435 | 48.095 | 0.000 | 0.063 | 0.000 | 0.000 | -35.398 | 0.000 | -7.228 | -20.725 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.074 | -134.013 | 0.000 | 0.000 | 0.950 | 3.264 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -24.156 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 6.035 | -1129.647 | 0.000 | 0.000 | 9.531 | 32.637 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -457.362 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 1.144 | -100.229 | 0.000 | 0.000 | 0.960 | 3.264 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -59.019 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | -7142.910 | 0.000 | 0.000 | 0.000 | 0.000 | 20.569 | 38.227 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -410.743 |
GROUNDFLOOR_PLENUM | 5.686 | -39.276 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.064 | 42.360 | 0.000 | 0.000 | 0.000 | -8.834 | -0.000 |
MIDFLOOR_PLENUM | 150.279 | -234.492 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.201 | 231.854 | 0.000 | 0.000 | 0.000 | -148.843 | -0.004 |
TOPFLOOR_PLENUM | 66.777 | -38.815 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.104 | 0.001 | 0.000 | 0.000 | 0.000 | -15.515 | -12.551 |
Total Facility | 222.742 | -7455.493 | 621.013 | -8780.364 | 0.000 | 0.000 | 1588.641 | 2028.520 | 14676.396 | 2738.894 | 0.000 | 4.444 | 393.181 | 0.000 | -2153.391 | 0.000 | -526.511 | -3358.017 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 21-AUG-03:02 | 0.00 | 0.00 | 0.00 | -99114.67 | 0.00 | 0.00 | 0.00 | 657.72 | 13457.54 | 0.00 | 0.00 | 0.00 | 84999.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 05-JUL-03:02 | 0.00 | 0.00 | 0.00 | -81358.17 | 0.00 | 0.00 | 0.00 | 590.68 | 5937.65 | 0.00 | 0.00 | 0.00 | 74829.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 21-JUN-05:04 | 0.00 | 0.00 | 0.00 | -728046.75 | 0.00 | 0.00 | 8374.11 | 11812.12 | 76473.61 | 0.00 | 0.00 | 0.00 | 631386.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 21-JUN-05:04 | 0.00 | 0.00 | 0.00 | -72309.47 | 0.00 | 0.00 | 867.51 | 1181.21 | 7647.36 | 0.00 | 0.00 | 0.00 | 62613.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 06-AUG-16:01 | 0.00 | 0.00 | 0.00 | -13902.06 | 0.00 | 0.00 | 42.67 | 35.29 | 720.18 | 3860.74 | 0.00 | 110.64 | 9132.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 06-AUG-07:22 | 0.00 | 0.00 | 0.00 | -19858.83 | 0.00 | 0.00 | 22.44 | 22.74 | 464.11 | 18040.98 | 0.00 | 0.00 | 1333.73 | 0.00 | -0.00 | 0.00 | -25.17 | 0.00 |
PERIMETER_BOT_ZN_1 | 15-OCT-12:31 | 0.00 | 0.00 | 0.00 | -26014.99 | 0.00 | 0.00 | 33.35 | 35.29 | 720.19 | 27794.75 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -168.88 | -2399.71 |
PERIMETER_BOT_ZN_4 | 16-JUL-16:51 | 0.00 | 0.00 | 0.00 | -25675.11 | 0.00 | 0.00 | 15.31 | 22.74 | 464.11 | 17921.57 | 0.00 | 21.07 | 7230.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 19-JUL-05:03 | 0.00 | 0.00 | 0.00 | -99741.50 | 0.00 | 0.00 | 1092.58 | 1423.11 | 9602.45 | 0.00 | 0.00 | 0.00 | 96510.12 | 0.00 | -8459.35 | 0.00 | -427.42 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-07:51 | 0.00 | 0.00 | 0.00 | -219898.45 | 0.00 | 0.00 | 205.92 | 227.41 | 4641.14 | 171635.53 | 0.00 | 0.00 | 45017.19 | 0.00 | -0.00 | 0.00 | -1828.73 | 0.00 |
PERIMETER_MID_ZN_1 | 03-SEP-13:21 | 0.00 | 0.00 | 0.00 | -272518.86 | 0.00 | 0.00 | 288.23 | 352.89 | 7201.95 | 211416.33 | 0.00 | 1496.07 | 51763.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JUL-17:51 | 0.00 | 0.00 | 0.00 | -246186.89 | 0.00 | 0.00 | 0.00 | 227.41 | 3603.49 | 173339.10 | 0.00 | 0.00 | 69526.96 | 0.00 | -0.00 | 0.00 | -510.07 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-18:31 | 0.00 | 0.00 | 0.00 | -16549.49 | 0.00 | 0.00 | 0.00 | 35.29 | 559.17 | 5567.48 | 0.00 | 107.23 | 10280.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-07:51 | 0.00 | 0.00 | 0.00 | -21839.24 | 0.00 | 0.00 | 21.14 | 22.74 | 464.11 | 17150.83 | 0.00 | 0.00 | 4405.87 | 0.00 | -0.00 | 0.00 | -225.46 | 0.00 |
PERIMETER_TOP_ZN_1 | 15-OCT-14:22 | 0.00 | 0.00 | 0.00 | -27420.39 | 0.00 | 0.00 | 33.84 | 35.29 | 720.19 | 21644.70 | 0.00 | 0.00 | 5359.88 | 0.00 | -0.00 | 0.00 | -373.52 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-17:51 | 0.00 | 0.00 | 0.00 | -26296.15 | 0.00 | 0.00 | 0.00 | 22.74 | 360.35 | 17267.39 | 0.00 | 0.00 | 8713.75 | 0.00 | -0.00 | 0.00 | -68.08 | 0.00 |
DATACENTER_BOT_ZN_6 | 22-APR-18:10 | 0.00 | 0.00 | 0.00 | -8166.50 | 0.00 | 0.00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 356.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 05-AUG-19:42 | 0.00 | 0.00 | 0.00 | -77625.65 | 0.00 | 0.00 | 0.00 | 158.32 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -476.89 |
DATACENTER_TOP_ZN_6 | 05-AUG-19:42 | 0.00 | 0.00 | 0.00 | -7932.67 | 0.00 | 0.00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 122.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 07-AUG-16:00 | 0.00 | -367701.48 | 0.00 | 0.00 | 0.00 | 0.00 | 2183.10 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17451.91 |
GROUNDFLOOR_PLENUM | 17-JUL-05:15 | 0.00 | -10390.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10409.29 | 0.00 | -0.00 | 0.00 | -18.55 | 0.00 |
MIDFLOOR_PLENUM | 06-JAN-04:01 | 0.00 | -84233.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109945.79 | 0.00 | -0.00 | 0.00 | -25712.11 | 0.00 |
TOPFLOOR_PLENUM | 17-JUL-15:10 | 0.00 | -20956.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.55 | 20935.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-AUG-05:03 | 0.00 | -377302.13 | 0.00 | -1392561.95 | 0.00 | 0.00 | 15841.38 | 22094.05 | 616289.16 | 0.00 | 0.00 | 0.00 | 1169135.29 | 0.00 | -51469.02 | 0.00 | -2026.78 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 05-AUG-16:02 | 0.00 | 0.00 | 17614.94 | 0.00 | 0.00 | 0.00 | 484.19 | 657.72 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -32214.39 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 09-JAN-05:01 | 0.00 | 0.00 | 493193.51 | 0.00 | 0.00 | 0.00 | 0.00 | 11812.12 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -564381.86 |
CORE_TOP | 09-JAN-04:01 | 0.00 | 0.00 | 71493.64 | 0.00 | 0.00 | 0.00 | 0.00 | 590.68 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -78021.94 |
PERIMETER_BOT_ZN_3 | 09-JAN-04:01 | 0.00 | 0.00 | 12119.56 | 0.00 | 0.00 | 0.00 | 0.00 | 74.17 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6282.08 | 0.00 | -337.61 | -6319.60 |
PERIMETER_BOT_ZN_2 | 09-JAN-04:01 | 0.00 | 0.00 | 14257.18 | 0.00 | 0.00 | 0.00 | 0.00 | 47.80 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4170.44 | 0.00 | -226.10 | -10388.90 |
PERIMETER_BOT_ZN_1 | 11-JAN-04:01 | 0.00 | 0.00 | 19455.50 | 0.00 | 0.00 | 0.00 | 0.00 | 74.17 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6603.01 | 0.00 | -386.27 | -13285.96 |
PERIMETER_BOT_ZN_4 | 09-JAN-04:01 | 0.00 | 0.00 | 12727.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.80 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4223.33 | 0.00 | -232.44 | -8799.48 |
PERIMETER_MID_ZN_3 | 31-DEC-03:12 | 0.00 | 0.00 | 119059.81 | 0.00 | 0.00 | 0.00 | 0.00 | 741.66 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -60208.42 | 0.00 | -14106.74 | -51078.02 |
PERIMETER_MID_ZN_2 | 09-JAN-04:01 | 0.00 | 0.00 | 172597.25 | 0.00 | 0.00 | 0.00 | 0.00 | 477.95 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -40071.65 | 0.00 | -5151.55 | -132656.69 |
PERIMETER_MID_ZN_1 | 09-JAN-04:01 | 0.00 | 0.00 | 203311.42 | 0.00 | 0.00 | 0.00 | 0.00 | 741.67 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -58785.01 | 0.00 | -7722.50 | -145001.31 |
PERIMETER_MID_ZN_4 | 09-JAN-04:01 | 0.00 | 0.00 | 181776.75 | 0.00 | 0.00 | 0.00 | 0.00 | 477.95 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -39306.02 | 0.00 | -5184.75 | -142568.58 |
PERIMETER_TOP_ZN_3 | 09-JAN-06:01 | 0.00 | 0.00 | 16941.47 | 0.00 | 0.00 | 0.00 | 184.61 | 148.31 | 960.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5897.15 | 0.00 | -235.31 | -12102.18 |
PERIMETER_TOP_ZN_2 | 31-DEC-05:52 | 0.00 | 0.00 | 18002.67 | 0.00 | 0.00 | 0.00 | 0.00 | 47.80 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3832.39 | 0.00 | -725.87 | -13852.55 |
PERIMETER_TOP_ZN_1 | 31-DEC-05:52 | 0.00 | 0.00 | 23006.83 | 0.00 | 0.00 | 0.00 | 0.00 | 74.17 | 559.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5941.87 | 0.00 | -1086.68 | -16611.63 |
PERIMETER_TOP_ZN_4 | 09-JAN-04:01 | 0.00 | 0.00 | 20214.35 | 0.00 | 0.00 | 0.00 | 0.00 | 47.80 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3790.24 | 0.00 | -630.53 | -16321.84 |
DATACENTER_BOT_ZN_6 | 09-JAN-04:12 | 0.00 | 0.00 | 594.62 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2559.05 |
DATACENTER_MID_ZN_6 | 29-JAN-17:50 | 0.00 | 0.00 | 6519.39 | 0.00 | 0.00 | 0.00 | 54.63 | 158.32 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26218.39 |
DATACENTER_TOP_ZN_6 | 30-APR-23:10 | 0.00 | 0.00 | 727.44 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2691.88 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 19-DEC-06:01 | 11891.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -170.04 | -11721.49 |
MIDFLOOR_PLENUM | 09-JAN-06:15 | 124383.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3365.75 | -121017.89 |
TOPFLOOR_PLENUM | 11-JAN-05:18 | 32829.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -586.37 | -32243.48 |
Total Facility | 09-JAN-06:01 | -21787.47 | 15602.68 | 1307669.70 | -15602.68 | 0.00 | 0.00 | 22610.59 | 22094.05 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -247979.05 | 0.00 | -11639.58 | -1332383.21 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.2596 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.7350 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 106.8638 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 89.9165 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.1151 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.0422 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.5132 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.5132 | 0.2177 | 1.0000 | Not calculated | 1.2002 | 0.2177 | ||
AIRLOOP DATACENTER BOT | 0.5508 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5508 | 0.0284 | 1.0000 | Not calculated | 0.0156 | 0.0284 | ||
AIRLOOP DATACENTER MID | 5.2713 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.2713 | 0.0297 | 1.0000 | Not calculated | 0.1563 | 0.0297 | ||
AIRLOOP DATACENTER TOP | 0.5371 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5371 | 0.0291 | 1.0000 | Not calculated | 0.0156 | 0.0291 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.6298 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.0448 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 53.4319 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 29.7576 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.5575 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1293 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.5132 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.5132 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2177 | ||
AIRLOOP DATACENTER BOT | 0.5508 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5508 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0284 | ||
AIRLOOP DATACENTER MID | 5.2713 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.2713 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0297 | ||
AIRLOOP DATACENTER TOP | 0.5371 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5371 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0291 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.002360 | 149.6021 | 0.000305 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.002360 | 1.9486 | 0.000305 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.002360 | 19.4861 | 0.000305 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.002360 | 1.9486 | 0.000305 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.002360 | 149.60 | 0.000305 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BOT | 0.002360 | 1.95 | 0.000305 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.002360 | 19.49 | 0.000305 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.002360 | 1.95 | 0.000305 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.5132 | 5.5132 | 5.5132 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9777 | 5.9777 | 1.9368 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 55.8874 | 55.8874 | 18.9458 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4924 | 5.4924 | 1.9553 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9571 | 0.9571 | 0.2431 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2319 | 1.2319 | 0.2464 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5407 | 1.5407 | 0.3081 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5522 | 1.5522 | 0.3104 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.8074 | 8.8074 | 2.3780 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.9910 | 12.9910 | 2.5982 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 15.3184 | 15.3184 | 3.0637 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.8596 | 13.8596 | 2.7719 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1772 | 1.1772 | 0.2849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3032 | 1.3032 | 0.2606 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6611 | 1.6611 | 0.3322 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4812 | 1.4812 | 0.2962 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5508 | 0.5508 | 0.5508 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.2713 | 5.2713 | 5.2713 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5371 | 0.5371 | 0.5371 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.2596 | 9.7350 | 11.2596 | 3.0448 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 106.8638 | 89.9165 | 106.8638 | 29.7576 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.1151 | 10.0422 | 11.1151 | 3.1293 | 0.0000 | 1.0000 |
CAV_BAS | 5.5132 | 5.5132 | 5.5132 | 5.5132 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5508 | 0.5508 | 0.5508 | 0.5508 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.2713 | 5.2713 | 5.2713 | 5.2713 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5371 | 0.5371 | 0.5371 | 0.5371 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.5132 | 5.5132 | 5.5132 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9888 | 2.9888 | 1.9368 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 27.9437 | 27.9437 | 18.9458 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7462 | 2.7462 | 1.9553 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4785 | 0.4785 | 0.2431 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6160 | 0.6160 | 0.2464 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7703 | 0.7703 | 0.3081 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7761 | 0.7761 | 0.3104 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.4037 | 4.4037 | 2.3780 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.4955 | 6.4955 | 2.5982 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.6592 | 7.6592 | 3.0637 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.9298 | 6.9298 | 2.7719 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5886 | 0.5886 | 0.2849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6516 | 0.6516 | 0.2606 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8305 | 0.8305 | 0.3322 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7406 | 0.7406 | 0.2962 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5508 | 0.5508 | 0.5508 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.2713 | 5.2713 | 5.2713 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5371 | 0.5371 | 0.5371 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.6298 | 3.0448 | 3.0448 | 3.0448 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 53.4319 | 29.7576 | 29.7576 | 29.7576 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.5575 | 3.1293 | 3.1293 | 3.1293 | 0.0000 | 1.0000 |
CAV_BAS | 5.5132 | 5.5132 | 5.5132 | 5.5132 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5508 | 0.5508 | 0.5508 | 0.5508 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.2713 | 5.2713 | 5.2713 | 5.2713 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5371 | 0.5371 | 0.5371 | 0.5371 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 117.83 |
Number of hours cooling loads not met | 127.50 |
Number of hours not met | 245.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 |
Heating -- Boiler | 0.00 | 0.00 | 3325.34 | 2299529.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 701.92 | 294589.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7167.51 | 370300.48 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2028.52 | 198852.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 330.95 | 37611.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.48 | 3387.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ComputerHVAC | 1274.13 | 64537.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 1177.24 | 231088.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 277.14 | 47997.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 150.74 | 39494.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 771.56 | 85520.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 22526.12 |
Natural Gas | 0.00 | 4096.91 |
Additional | 0.00 | 7167.51 |
Total | 14676.40 | 33790.54 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 43.79 |
Space Heating | 0.00 |
Space Cooling | 15.15 |
Fans (All) | 25.42 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 486.31 |
Subtotal | 486.31 |
Natural Gas [MJ/m2] | |
Space Heating | 71.79 |
Service Water Heating | 16.66 |
Miscellaneous (All) | 88.45 |
Subtotal | 88.45 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.00 |
Space Heating | 9.84 |
Space Cooling | 23.29 |
Fans (All) | 3.48 |
Service Water Heating | 2.28 |
Receptacle Equipment | 43.43 |
Miscellaneous | 11.67 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2362. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8714.50 | 45.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8743.50 | 16.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8743.00 | 17.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8690.67 | 69.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8739.33 | 20.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8741.83 | 18.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8735.00 | 25.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8738.17 | 21.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8732.00 | 28.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8733.17 | 26.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8738.00 | 22.00 | 0.00 | 0.00 | 0.00 |
Min | 8690.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 69.33 | 0.00 | 0.00 | 0.00 |
Average | 8745.30 | 14.70 | 0.00 | 0.00 | 0.00 |
Sum | 201142.00 | 338.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368456.17 | 159.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330808.00 | 5.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 102324.50 | 1070.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368456.17 | 1070.50 | 0.00 | 0.00 | 0.00 |
Average | 80281.20 | 53.71 | 0.00 | 0.00 | 0.00 |
Sum | 1846467.67 | 1235.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8673.67 | 86.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8730.33 | 29.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8726.00 | 34.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8736.83 | 23.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8746.50 | 13.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8740.50 | 19.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8703.17 | 56.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8750.17 | 9.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8736.00 | 24.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8736.00 | 24.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8727.83 | 32.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8748.17 | 11.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8736.67 | 23.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8737.50 | 22.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8727.83 | 32.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8744.33 | 15.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8716.33 | 43.67 | 0.00 | 0.00 | 0.00 |
Min | 8673.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 86.33 | 0.00 | 0.00 | 0.00 |
Average | 8737.58 | 22.42 | 0.00 | 0.00 | 0.00 |
Sum | 200964.33 | 515.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 368296.50 | 319.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330742.00 | 71.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330721.00 | 92.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330765.00 | 48.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24908.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 103395.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368296.50 | 319.50 | 0.00 | 0.00 | 0.00 |
Average | 80311.83 | 23.08 | 0.00 | 0.00 | 0.00 |
Sum | 1847172.17 | 530.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:06:43
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408843E+11 | 96920.44 | 02-JAN-04:11 | -0.4 | -2.9 | 0.525269E+10 | 7499.19 | 13-JAN-14:20 | 8.53 | 4.10 |
February | 0.362948E+11 | 96327.88 | 21-FEB-04:01 | 6.88 | 1.33 | 0.497961E+10 | 7499.15 | 07-FEB-10:30 | 6.88 | 1.33 |
March | 0.456892E+11 | 95428.53 | 20-MAR-03:11 | -1.5 | -3.4 | 0.611757E+10 | 7499.13 | 01-MAR-10:09 | -1.5 | -3.4 |
April | 0.446544E+11 | 93912.38 | 10-APR-03:02 | 4.40 | 0.24 | 0.545075E+10 | 7499.17 | 04-APR-09:09 | 4.40 | 0.24 |
May | 0.469532E+11 | 93518.67 | 15-MAY-03:02 | 4.22 | 0.54 | 0.590514E+10 | 7499.77 | 02-MAY-13:20 | 4.22 | 0.54 |
June | 0.511445E+11 | 95674.68 | 05-JUN-03:02 | 8.62 | 5.44 | 0.588701E+10 | 7499.14 | 20-JUN-13:20 | 27.77 | 18.21 |
July | 0.534783E+11 | 94048.98 | 24-JUL-03:02 | 12.38 | 8.99 | 0.547924E+10 | 7499.18 | 03-JUL-13:09 | 12.38 | 8.99 |
August | 0.588847E+11 | 99112.07 | 21-AUG-03:02 | 11.70 | 9.43 | 0.614422E+10 | 7499.04 | 01-AUG-13:20 | 11.70 | 9.43 |
September | 0.509430E+11 | 96426.34 | 04-SEP-16:51 | 32.80 | 16.77 | 0.545777E+10 | 7499.35 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.520073E+11 | 98322.70 | 10-OCT-03:01 | -4.1 | -4.8 | 0.567513E+10 | 7499.09 | 27-OCT-09:09 | 7.67 | 3.31 |
November | 0.478570E+11 | 98798.36 | 06-NOV-04:02 | -2.8 | -3.9 | 0.561586E+10 | 7499.05 | 03-NOV-09:09 | -2.8 | -3.9 |
December | 0.455315E+11 | 94789.38 | 26-DEC-04:01 | -6.3 | -8.0 | 0.539690E+10 | 7499.16 | 07-DEC-10:09 | -6.3 | -8.0 |
Annual Sum or Average | 0.574322E+12 | 0.673619E+11 | ||||||||
Minimum of Months | 0.362948E+11 | 93518.67 | -6.3 | -8.0 | 0.497961E+10 | 7499.04 | -6.3 | -8.0 | ||
Maximum of Months | 0.588847E+11 | 99112.07 | 32.80 | 16.77 | 0.614422E+10 | 7499.77 | 27.77 | 18.21 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.266953E+11 | 77558.40 | 02-JAN-05:01 | -0.2 | -2.7 | 0.487451E+10 | 6734.76 | 02-JAN-10:09 | 2.48 | -0.4 |
February | 0.285744E+11 | 75913.50 | 21-FEB-06:01 | 6.70 | 0.70 | 0.454394E+10 | 6734.74 | 28-FEB-10:09 | 1.57 | -0.3 |
March | 0.407424E+11 | 77071.22 | 30-MAR-05:02 | 0.00 | -2.1 | 0.548755E+10 | 6734.77 | 01-MAR-10:09 | 0.00 | -2.1 |
April | 0.455557E+11 | 79098.16 | 10-APR-03:02 | 4.40 | 0.24 | 0.488275E+10 | 6734.78 | 04-APR-09:09 | 4.40 | 0.24 |
May | 0.421926E+11 | 80103.45 | 30-MAY-03:02 | 15.60 | 10.52 | 0.528700E+10 | 6735.16 | 02-MAY-13:09 | 15.60 | 10.52 |
June | 0.525771E+11 | 78652.49 | 05-JUN-03:02 | 8.62 | 5.44 | 0.526944E+10 | 6734.78 | 20-JUN-13:09 | 27.48 | 18.05 |
July | 0.595528E+11 | 81364.82 | 05-JUL-03:02 | 9.90 | 9.28 | 0.489713E+10 | 6734.95 | 03-JUL-13:09 | 9.90 | 9.28 |
August | 0.645117E+11 | 78345.52 | 02-AUG-03:02 | 8.90 | 6.89 | 0.549823E+10 | 6734.78 | 22-AUG-09:09 | 16.88 | 12.48 |
September | 0.451758E+11 | 81074.78 | 11-SEP-03:02 | 11.10 | 10.41 | 0.488084E+10 | 6735.08 | 07-SEP-09:00 | 11.10 | 10.41 |
October | 0.429576E+11 | 78532.48 | 10-OCT-03:01 | -4.1 | -4.8 | 0.507825E+10 | 6734.75 | 27-OCT-09:09 | 7.67 | 3.31 |
November | 0.387771E+11 | 80098.00 | 06-NOV-04:02 | -2.8 | -3.9 | 0.502536E+10 | 6734.75 | 03-NOV-09:09 | -2.8 | -3.9 |
December | 0.354266E+11 | 77398.34 | 11-DEC-05:01 | -1.6 | -4.2 | 0.488205E+10 | 6734.78 | 07-DEC-10:09 | -1.6 | -4.2 |
Annual Sum or Average | 0.522739E+12 | 0.606070E+11 | ||||||||
Minimum of Months | 0.266953E+11 | 75913.50 | -4.1 | -4.8 | 0.454394E+10 | 6734.74 | -2.8 | -4.2 | ||
Maximum of Months | 0.645117E+11 | 81364.82 | 15.60 | 10.52 | 0.549823E+10 | 6735.16 | 27.48 | 18.05 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190911E+11 | 16071.04 | 04-JAN-17:00 | 1.10 | -3.1 | 0.427973E+10 | 6387.13 | 04-JAN-14:00 | 1.10 | -3.1 |
February | 0.190747E+11 | 25243.52 | 28-FEB-17:00 | 10.00 | 4.31 | 0.410104E+10 | 6734.74 | 28-FEB-10:09 | 10.00 | 4.31 |
March | 0.254812E+11 | 47936.49 | 30-MAR-05:02 | 0.00 | -2.1 | 0.522044E+10 | 6734.76 | 01-MAR-10:09 | 0.00 | -2.1 |
April | 0.275417E+11 | 67845.68 | 26-APR-05:03 | 5.37 | 2.97 | 0.480937E+10 | 6734.76 | 04-APR-09:09 | 5.37 | 2.97 |
May | 0.315096E+11 | 69934.46 | 30-MAY-04:03 | 15.60 | 10.83 | 0.522656E+10 | 6735.18 | 02-MAY-13:09 | 15.60 | 10.83 |
June | 0.400566E+11 | 72833.30 | 21-JUN-05:04 | 15.87 | 11.84 | 0.525527E+10 | 6734.81 | 20-JUN-13:09 | 15.87 | 11.84 |
July | 0.424662E+11 | 70913.13 | 21-JUL-04:03 | 12.02 | 7.75 | 0.488971E+10 | 6734.93 | 03-JUL-13:09 | 12.02 | 7.75 |
August | 0.436628E+11 | 70310.39 | 21-AUG-05:02 | 10.10 | 8.00 | 0.549106E+10 | 6734.77 | 01-AUG-13:09 | 10.10 | 8.00 |
September | 0.350282E+11 | 71039.68 | 06-SEP-04:03 | 15.00 | 12.93 | 0.485598E+10 | 6735.09 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.286432E+11 | 69032.58 | 20-OCT-05:02 | 2.70 | 0.86 | 0.500898E+10 | 6734.75 | 27-OCT-09:09 | 7.67 | 3.31 |
November | 0.232108E+11 | 46618.20 | 08-NOV-06:02 | 10.13 | 4.88 | 0.477374E+10 | 6734.75 | 03-NOV-09:09 | 10.13 | 4.88 |
December | 0.201399E+11 | 19541.82 | 07-DEC-17:00 | 4.40 | 1.14 | 0.436478E+10 | 6734.36 | 07-DEC-14:30 | 4.40 | 1.14 |
Annual Sum or Average | 0.355906E+12 | 0.582767E+11 | ||||||||
Minimum of Months | 0.190747E+11 | 16071.04 | 0.00 | -3.1 | 0.410104E+10 | 6387.13 | 0.00 | -3.1 | ||
Maximum of Months | 0.436628E+11 | 72833.30 | 15.87 | 12.93 | 0.549106E+10 | 6735.18 | 16.70 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100106E+11 | 14996.38 | 13-JAN-17:00 | 7.80 | 3.93 | 0.381129E+10 | 5781.14 | 13-JAN-14:00 | 7.80 | 3.93 |
February | 0.125402E+11 | 17164.33 | 28-FEB-17:00 | 10.00 | 4.31 | 0.362610E+10 | 6377.32 | 28-FEB-14:00 | 10.00 | 4.31 |
March | 0.182751E+11 | 18424.25 | 23-MAR-16:00 | 7.20 | 0.71 | 0.460319E+10 | 6624.71 | 23-MAR-13:00 | 7.20 | 0.71 |
April | 0.213272E+11 | 33804.71 | 25-APR-16:00 | 17.80 | 7.70 | 0.442447E+10 | 6734.56 | 13-APR-13:00 | 17.80 | 7.70 |
May | 0.273140E+11 | 67417.24 | 30-MAY-05:03 | 15.60 | 11.34 | 0.495572E+10 | 6734.70 | 30-MAY-09:09 | 17.07 | 12.52 |
June | 0.395696E+11 | 72335.74 | 21-JUN-05:04 | 15.87 | 11.84 | 0.521978E+10 | 6734.76 | 20-JUN-13:09 | 15.87 | 11.84 |
July | 0.442701E+11 | 70113.88 | 19-JUL-04:03 | 20.40 | 16.48 | 0.487984E+10 | 6734.94 | 03-JUL-13:09 | 20.40 | 16.48 |
August | 0.430626E+11 | 68201.97 | 29-AUG-05:02 | 9.40 | 6.64 | 0.546781E+10 | 6734.75 | 01-AUG-13:09 | 9.40 | 6.64 |
September | 0.305312E+11 | 68724.87 | 08-SEP-05:03 | 14.40 | 11.72 | 0.468910E+10 | 6735.03 | 07-SEP-09:00 | 14.40 | 11.72 |
October | 0.212249E+11 | 30104.62 | 18-OCT-16:00 | 24.40 | 11.02 | 0.455809E+10 | 6734.50 | 19-OCT-13:00 | 21.10 | 10.22 |
November | 0.157711E+11 | 17327.12 | 03-NOV-16:00 | 14.30 | 7.69 | 0.411214E+10 | 6447.30 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.121735E+11 | 16033.25 | 06-DEC-16:50 | 7.15 | 2.74 | 0.378645E+10 | 6167.69 | 06-DEC-14:00 | 7.15 | 2.74 |
Annual Sum or Average | 0.296070E+12 | 0.541340E+11 | ||||||||
Minimum of Months | 0.100106E+11 | 14996.38 | 7.15 | 0.71 | 0.362610E+10 | 5781.14 | 7.15 | 0.71 | ||
Maximum of Months | 0.442701E+11 | 72335.74 | 24.40 | 16.48 | 0.546781E+10 | 6735.03 | 21.10 | 16.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109827E+10 | 2418.17 | 02-JAN-06:03 | -1.3 | -3.4 | 0.492480E+09 | 799.03 | 02-JAN-14:00 | 6.10 | 1.11 |
February | 0.171758E+10 | 3407.97 | 27-FEB-16:00 | 18.90 | 7.06 | 0.481056E+09 | 845.60 | 21-FEB-14:00 | 18.90 | 7.06 |
March | 0.293289E+10 | 3812.21 | 27-MAR-14:40 | 9.63 | 2.75 | 0.632622E+09 | 845.61 | 02-MAR-14:09 | 9.63 | 2.75 |
April | 0.406503E+10 | 6014.96 | 07-APR-14:30 | 22.50 | 9.29 | 0.594891E+09 | 845.62 | 13-APR-13:00 | 13.30 | 7.60 |
May | 0.459227E+10 | 11018.80 | 30-MAY-05:03 | 15.60 | 11.34 | 0.648330E+09 | 845.68 | 02-MAY-13:09 | 15.60 | 11.34 |
June | 0.762313E+10 | 11262.50 | 23-JUN-05:03 | 17.88 | 11.72 | 0.660312E+09 | 845.64 | 20-JUN-13:09 | 17.88 | 11.72 |
July | 0.932719E+10 | 13062.29 | 16-JUL-18:51 | 32.20 | 17.25 | 0.615503E+09 | 846.32 | 18-JUL-13:20 | 33.17 | 17.33 |
August | 0.893818E+10 | 13902.00 | 06-AUG-16:01 | 35.50 | 16.24 | 0.689980E+09 | 845.64 | 01-AUG-13:09 | 35.50 | 16.24 |
September | 0.495816E+10 | 11066.61 | 05-SEP-05:02 | 18.40 | 11.40 | 0.603795E+09 | 845.67 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.359634E+10 | 5006.29 | 19-OCT-14:30 | 21.40 | 10.24 | 0.614435E+09 | 845.62 | 18-OCT-13:30 | 21.40 | 10.24 |
November | 0.265524E+10 | 3537.99 | 24-NOV-14:30 | 14.90 | 6.43 | 0.572066E+09 | 845.61 | 08-NOV-10:09 | 14.90 | 6.43 |
December | 0.196290E+10 | 2555.11 | 06-DEC-06:02 | 7.02 | 3.93 | 0.519132E+09 | 845.59 | 06-DEC-14:00 | 11.10 | 5.34 |
Annual Sum or Average | 0.534672E+11 | 0.712460E+10 | ||||||||
Minimum of Months | 0.109827E+10 | 2418.17 | -1.3 | -3.4 | 0.481056E+09 | 799.03 | 6.10 | 1.11 | ||
Maximum of Months | 0.932719E+10 | 13902.00 | 35.50 | 17.25 | 0.689980E+09 | 846.32 | 35.50 | 17.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106358E+10 | 2429.76 | 02-JAN-05:01 | -0.2 | -2.7 | 0.317276E+09 | 541.59 | 17-JAN-10:39 | 5.53 | 1.42 |
February | 0.178715E+10 | 6019.08 | 27-FEB-09:55 | 11.70 | 4.23 | 0.313031E+09 | 544.95 | 28-FEB-10:09 | 1.57 | -0.3 |
March | 0.315125E+10 | 8400.38 | 28-MAR-09:15 | 5.73 | 0.86 | 0.403130E+09 | 544.95 | 06-MAR-10:20 | 5.73 | 0.86 |
April | 0.439923E+10 | 16944.29 | 16-APR-08:32 | 11.47 | 4.88 | 0.374392E+09 | 544.95 | 25-APR-09:09 | 9.87 | 4.86 |
May | 0.515899E+10 | 10727.02 | 19-MAY-08:30 | 16.95 | 11.09 | 0.415810E+09 | 544.99 | 02-MAY-13:09 | 16.95 | 11.09 |
June | 0.782049E+10 | 19718.92 | 25-JUN-07:52 | 15.60 | 11.35 | 0.424239E+09 | 546.20 | 23-JUN-09:50 | 15.60 | 11.35 |
July | 0.953871E+10 | 19116.15 | 23-JUL-09:02 | 20.18 | 12.10 | 0.396487E+09 | 546.26 | 03-JUL-09:00 | 20.18 | 12.10 |
August | 0.895537E+10 | 19863.02 | 06-AUG-07:22 | 22.20 | 12.89 | 0.443153E+09 | 546.13 | 01-AUG-09:09 | 22.20 | 12.89 |
September | 0.527972E+10 | 18696.73 | 03-SEP-09:12 | 25.93 | 14.07 | 0.387855E+09 | 544.98 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.367685E+10 | 8077.33 | 18-OCT-09:20 | 18.13 | 8.00 | 0.393395E+09 | 544.95 | 18-OCT-13:30 | 24.70 | 11.11 |
November | 0.244081E+10 | 5488.77 | 06-NOV-09:35 | 1.20 | -1.1 | 0.358828E+09 | 544.95 | 03-NOV-09:09 | 1.20 | -1.1 |
December | 0.164037E+10 | 2366.05 | 06-DEC-06:02 | 7.02 | 3.93 | 0.321960E+09 | 544.88 | 20-DEC-10:30 | 3.85 | -0.4 |
Annual Sum or Average | 0.549125E+11 | 0.454955E+10 | ||||||||
Minimum of Months | 0.106358E+10 | 2366.05 | -0.2 | -2.7 | 0.313031E+09 | 541.59 | 1.20 | -1.1 | ||
Maximum of Months | 0.953871E+10 | 19863.02 | 25.93 | 14.07 | 0.443153E+09 | 546.26 | 24.70 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240354E+10 | 12467.95 | 15-JAN-13:53 | 5.60 | -0.5 | 0.527231E+09 | 845.64 | 13-JAN-14:20 | 5.60 | -0.5 |
February | 0.440503E+10 | 23524.27 | 26-FEB-13:52 | 15.60 | 5.76 | 0.521292E+09 | 847.15 | 27-FEB-14:39 | 18.70 | 7.17 |
March | 0.628597E+10 | 17088.53 | 01-MAR-13:40 | 6.33 | 2.52 | 0.638823E+09 | 847.78 | 23-MAR-13:00 | 10.00 | 2.51 |
April | 0.677405E+10 | 23215.29 | 16-APR-13:13 | 18.67 | 7.93 | 0.583378E+09 | 846.30 | 24-APR-13:00 | 17.80 | 9.82 |
May | 0.678435E+10 | 14041.20 | 14-MAY-12:13 | 15.93 | 6.83 | 0.636572E+09 | 845.71 | 02-MAY-13:09 | 15.93 | 6.83 |
June | 0.963875E+10 | 18264.93 | 25-JUN-13:13 | 23.33 | 13.15 | 0.657157E+09 | 845.68 | 19-JUN-13:30 | 23.33 | 13.15 |
July | 0.125312E+11 | 23178.12 | 16-JUL-11:32 | 27.07 | 17.35 | 0.615448E+09 | 846.59 | 14-JUL-13:20 | 27.07 | 17.35 |
August | 0.141383E+11 | 24937.74 | 06-AUG-14:01 | 34.40 | 15.37 | 0.689699E+09 | 849.73 | 30-AUG-13:39 | 26.33 | 14.35 |
September | 0.999953E+10 | 25161.06 | 03-SEP-13:11 | 33.50 | 16.05 | 0.602761E+09 | 849.89 | 01-SEP-13:30 | 33.50 | 16.05 |
October | 0.821775E+10 | 26011.58 | 15-OCT-12:31 | 21.83 | 10.70 | 0.618015E+09 | 858.67 | 18-OCT-13:30 | 24.70 | 11.11 |
November | 0.557002E+10 | 17028.35 | 03-NOV-13:20 | 14.13 | 7.69 | 0.586014E+09 | 846.97 | 06-NOV-14:39 | 7.97 | 3.07 |
December | 0.371001E+10 | 11924.61 | 12-DEC-12:30 | -2.8 | -5.7 | 0.542883E+09 | 845.64 | 19-DEC-14:09 | 10.97 | 6.81 |
Annual Sum or Average | 0.904585E+11 | 0.721927E+10 | ||||||||
Minimum of Months | 0.240354E+10 | 11924.61 | -2.8 | -5.7 | 0.521292E+09 | 845.64 | 5.60 | -0.5 | ||
Maximum of Months | 0.141383E+11 | 26011.58 | 34.40 | 17.35 | 0.689699E+09 | 858.67 | 33.50 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187766E+10 | 3774.67 | 13-JAN-15:40 | 9.27 | 4.85 | 0.325131E+09 | 544.93 | 02-JAN-14:00 | 9.27 | 4.85 |
February | 0.326628E+10 | 11581.39 | 26-FEB-16:33 | 15.77 | 6.02 | 0.331197E+09 | 544.95 | 27-FEB-10:09 | 12.15 | 4.44 |
March | 0.538774E+10 | 11764.88 | 28-MAR-16:00 | 10.60 | 3.09 | 0.430923E+09 | 544.95 | 13-MAR-09:39 | 10.60 | 3.09 |
April | 0.773443E+10 | 24391.80 | 16-APR-16:32 | 20.00 | 8.92 | 0.394992E+09 | 544.96 | 13-APR-13:00 | 20.00 | 8.92 |
May | 0.689339E+10 | 23776.13 | 28-MAY-17:12 | 20.73 | 10.39 | 0.419114E+09 | 544.99 | 02-MAY-13:09 | 20.73 | 10.39 |
June | 0.102272E+11 | 24022.82 | 18-JUN-17:32 | 25.20 | 14.48 | 0.427236E+09 | 544.97 | 19-JUN-13:30 | 24.70 | 12.18 |
July | 0.131707E+11 | 25676.78 | 16-JUL-16:51 | 33.30 | 17.43 | 0.398236E+09 | 544.98 | 13-JUL-09:00 | 33.30 | 17.43 |
August | 0.138038E+11 | 25394.43 | 06-AUG-16:41 | 35.10 | 15.80 | 0.446580E+09 | 544.97 | 15-AUG-13:30 | 25.00 | 13.67 |
September | 0.691726E+10 | 24068.85 | 04-SEP-16:22 | 32.80 | 16.63 | 0.389966E+09 | 544.99 | 07-SEP-09:50 | 16.52 | 15.26 |
October | 0.563630E+10 | 22250.42 | 15-OCT-15:11 | 22.60 | 10.96 | 0.403913E+09 | 544.96 | 18-OCT-13:30 | 24.70 | 11.11 |
November | 0.456706E+10 | 12023.08 | 08-NOV-06:02 | 10.13 | 4.88 | 0.391384E+09 | 544.96 | 16-NOV-14:09 | 10.63 | 6.46 |
December | 0.380596E+10 | 10973.82 | 06-DEC-06:02 | 7.02 | 3.93 | 0.370561E+09 | 544.95 | 07-DEC-10:09 | 3.35 | 1.22 |
Annual Sum or Average | 0.832878E+11 | 0.472923E+10 | ||||||||
Minimum of Months | 0.187766E+10 | 3774.67 | 7.02 | 3.09 | 0.325131E+09 | 544.93 | 3.35 | 1.22 | ||
Maximum of Months | 0.138038E+11 | 25676.78 | 35.10 | 17.43 | 0.446580E+09 | 544.99 | 33.30 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 86986042.55 | 1319.53 | 14-JAN-16:03 | 9.82 | 4.49 | 0.461079E+09 | 626.03 | 10-JAN-14:00 | 9.82 | 4.49 |
February | 0.516711E+09 | 2324.69 | 27-FEB-13:30 | 17.75 | 6.76 | 0.428127E+09 | 729.79 | 27-FEB-14:00 | 18.90 | 7.23 |
March | 0.141914E+10 | 2306.79 | 23-MAR-13:30 | 9.70 | 2.18 | 0.535951E+09 | 780.59 | 29-MAR-13:00 | 12.80 | 4.50 |
April | 0.220376E+10 | 4195.46 | 07-APR-14:30 | 22.50 | 9.29 | 0.529184E+09 | 845.60 | 26-APR-13:00 | 11.10 | 4.95 |
May | 0.326600E+10 | 6037.99 | 19-MAY-16:00 | 27.80 | 14.54 | 0.605072E+09 | 845.62 | 30-MAY-09:09 | 17.07 | 12.52 |
June | 0.584374E+10 | 9944.63 | 23-JUN-05:03 | 17.88 | 11.72 | 0.654130E+09 | 845.64 | 20-JUN-13:09 | 17.88 | 11.72 |
July | 0.698859E+10 | 9977.07 | 19-JUL-05:03 | 19.50 | 16.15 | 0.613793E+09 | 846.04 | 18-JUL-13:20 | 19.50 | 16.15 |
August | 0.604989E+10 | 9052.30 | 11-AUG-05:03 | 18.80 | 8.36 | 0.684092E+09 | 845.64 | 01-AUG-13:09 | 18.80 | 8.36 |
September | 0.369948E+10 | 9569.92 | 05-SEP-05:02 | 18.40 | 11.40 | 0.575920E+09 | 845.66 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.225460E+10 | 3554.96 | 19-OCT-14:40 | 21.50 | 10.24 | 0.547981E+09 | 845.60 | 19-OCT-13:09 | 21.50 | 10.24 |
November | 0.114305E+10 | 2259.61 | 03-NOV-13:30 | 14.35 | 7.74 | 0.486566E+09 | 776.29 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.295263E+09 | 1550.31 | 06-DEC-16:00 | 9.40 | 4.51 | 0.449352E+09 | 671.01 | 06-DEC-14:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.337672E+11 | 0.657125E+10 | ||||||||
Minimum of Months | 86986042.55 | 1319.53 | 9.40 | 2.18 | 0.428127E+09 | 626.03 | 9.40 | 4.49 | ||
Maximum of Months | 0.698859E+10 | 9977.07 | 27.80 | 16.15 | 0.684092E+09 | 846.04 | 21.50 | 16.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206081E+09 | 1628.03 | 17-JAN-10:00 | 4.40 | 0.80 | 0.219644E+09 | 403.61 | 17-JAN-09:00 | 4.40 | 0.80 |
February | 0.866573E+09 | 3491.19 | 28-FEB-09:55 | 1.10 | -0.5 | 0.208968E+09 | 521.20 | 28-FEB-11:20 | 4.83 | 1.71 |
March | 0.195070E+10 | 6405.96 | 23-MAR-10:10 | 8.40 | 1.62 | 0.265915E+09 | 521.20 | 13-MAR-10:09 | 8.40 | 1.62 |
April | 0.326616E+10 | 9622.96 | 25-APR-09:00 | 9.40 | 4.65 | 0.258367E+09 | 521.21 | 13-APR-14:09 | 9.40 | 4.65 |
May | 0.439652E+10 | 11145.17 | 19-MAY-08:50 | 17.52 | 11.29 | 0.293627E+09 | 521.26 | 02-MAY-12:20 | 17.52 | 11.29 |
June | 0.734959E+10 | 21086.39 | 25-JUN-09:22 | 18.05 | 12.22 | 0.309534E+09 | 522.14 | 30-JUN-10:30 | 21.95 | 13.70 |
July | 0.895056E+10 | 21990.36 | 02-JUL-07:51 | 20.60 | 14.56 | 0.291865E+09 | 522.75 | 17-JUL-10:50 | 33.03 | 16.32 |
August | 0.798179E+10 | 20736.74 | 06-AUG-09:32 | 29.07 | 14.77 | 0.324005E+09 | 523.00 | 07-AUG-10:50 | 30.60 | 14.99 |
September | 0.467398E+10 | 19860.81 | 03-SEP-11:21 | 31.10 | 15.57 | 0.275293E+09 | 521.22 | 07-SEP-10:09 | 16.88 | 15.79 |
October | 0.274363E+10 | 6606.01 | 18-OCT-10:10 | 20.28 | 8.90 | 0.267184E+09 | 521.20 | 19-OCT-10:09 | 19.18 | 9.33 |
November | 0.134768E+10 | 3135.70 | 03-NOV-10:10 | 9.10 | 5.57 | 0.233339E+09 | 521.20 | 03-NOV-10:20 | 9.50 | 5.81 |
December | 0.386304E+09 | 1748.72 | 20-DEC-10:00 | 3.30 | -0.6 | 0.212752E+09 | 420.68 | 20-DEC-09:00 | 3.30 | -0.6 |
Annual Sum or Average | 0.441196E+11 | 0.316049E+10 | ||||||||
Minimum of Months | 0.206081E+09 | 1628.03 | 1.10 | -0.6 | 0.208968E+09 | 403.61 | 3.30 | -0.6 | ||
Maximum of Months | 0.895056E+10 | 21990.36 | 31.10 | 15.57 | 0.324005E+09 | 523.00 | 33.03 | 16.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163400E+10 | 11227.89 | 15-JAN-13:43 | 5.50 | -0.5 | 0.507227E+09 | 845.64 | 13-JAN-14:39 | 5.50 | -0.5 |
February | 0.365142E+10 | 25487.35 | 26-FEB-13:02 | 15.10 | 5.55 | 0.500528E+09 | 845.91 | 27-FEB-14:00 | 18.90 | 7.23 |
March | 0.516893E+10 | 22898.59 | 26-MAR-13:32 | 9.63 | 1.94 | 0.603619E+09 | 846.70 | 01-MAR-14:09 | 9.63 | 1.94 |
April | 0.529257E+10 | 23144.97 | 16-APR-13:43 | 19.22 | 8.29 | 0.555359E+09 | 845.94 | 24-APR-13:00 | 17.80 | 9.82 |
May | 0.593727E+10 | 18631.00 | 14-MAY-14:02 | 16.70 | 6.66 | 0.618342E+09 | 846.06 | 19-MAY-13:00 | 27.20 | 15.02 |
June | 0.834193E+10 | 18127.65 | 25-JUN-14:02 | 24.50 | 13.57 | 0.650720E+09 | 845.68 | 19-JUN-13:09 | 24.50 | 13.57 |
July | 0.106275E+11 | 23519.75 | 02-JUL-13:52 | 24.40 | 14.05 | 0.613771E+09 | 846.35 | 19-JUL-13:50 | 29.68 | 17.39 |
August | 0.119411E+11 | 23725.48 | 06-AUG-13:32 | 34.23 | 15.17 | 0.685506E+09 | 866.99 | 30-AUG-13:39 | 26.33 | 14.35 |
September | 0.963931E+10 | 27252.23 | 03-SEP-13:21 | 33.60 | 16.11 | 0.593443E+09 | 878.17 | 01-SEP-13:50 | 33.60 | 16.11 |
October | 0.757954E+10 | 24673.68 | 15-OCT-14:02 | 23.22 | 11.15 | 0.603148E+09 | 888.43 | 18-OCT-13:50 | 24.90 | 11.31 |
November | 0.445389E+10 | 23173.26 | 12-NOV-13:32 | -0.6 | -3.6 | 0.560983E+09 | 846.03 | 06-NOV-14:50 | -0.6 | -3.6 |
December | 0.224513E+10 | 9953.59 | 12-DEC-14:30 | -2.2 | -5.4 | 0.507949E+09 | 845.63 | 07-DEC-10:00 | -2.2 | -5.4 |
Annual Sum or Average | 0.765126E+11 | 0.700060E+10 | ||||||||
Minimum of Months | 0.163400E+10 | 9953.59 | -2.2 | -5.4 | 0.500528E+09 | 845.63 | -2.2 | -5.4 | ||
Maximum of Months | 0.119411E+11 | 27252.23 | 34.23 | 16.11 | 0.685506E+09 | 888.43 | 33.60 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.353242E+09 | 2221.29 | 13-JAN-15:50 | 9.08 | 4.76 | 0.302157E+09 | 478.18 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.111223E+10 | 6212.77 | 28-FEB-16:40 | 10.37 | 4.49 | 0.286112E+09 | 544.05 | 27-FEB-14:00 | 10.37 | 4.49 |
March | 0.224441E+10 | 7893.35 | 28-MAR-17:00 | 10.60 | 2.97 | 0.354667E+09 | 544.94 | 02-MAR-14:39 | 10.60 | 2.97 |
April | 0.348944E+10 | 21233.28 | 16-APR-17:01 | 19.90 | 8.94 | 0.343249E+09 | 544.94 | 07-APR-13:09 | 19.90 | 8.94 |
May | 0.488605E+10 | 23584.66 | 28-MAY-17:41 | 20.18 | 10.35 | 0.388649E+09 | 544.95 | 25-MAY-13:09 | 20.18 | 10.35 |
June | 0.705834E+10 | 22722.07 | 18-JUN-18:01 | 25.00 | 14.75 | 0.418147E+09 | 544.97 | 27-JUN-13:00 | 25.00 | 13.11 |
July | 0.848025E+10 | 24620.10 | 02-JUL-17:51 | 25.60 | 14.12 | 0.395516E+09 | 544.97 | 03-JUL-13:09 | 19.07 | 14.10 |
August | 0.773764E+10 | 21734.96 | 06-AUG-16:12 | 35.40 | 16.13 | 0.439237E+09 | 544.96 | 01-AUG-13:09 | 35.40 | 16.13 |
September | 0.496719E+10 | 21844.56 | 04-SEP-16:22 | 32.80 | 16.63 | 0.367080E+09 | 544.98 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.314047E+10 | 9471.86 | 15-OCT-16:42 | 21.28 | 10.50 | 0.354934E+09 | 544.94 | 19-OCT-13:09 | 21.10 | 10.07 |
November | 0.171907E+10 | 4786.33 | 03-NOV-15:50 | 14.35 | 7.69 | 0.324620E+09 | 544.88 | 09-NOV-14:00 | 9.00 | 3.82 |
December | 0.693352E+09 | 2466.17 | 06-DEC-15:50 | 9.68 | 4.65 | 0.296035E+09 | 517.33 | 06-DEC-15:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.458817E+11 | 0.427040E+10 | ||||||||
Minimum of Months | 0.353242E+09 | 2221.29 | 9.08 | 2.97 | 0.286112E+09 | 478.18 | 8.90 | 2.97 | ||
Maximum of Months | 0.848025E+10 | 24620.10 | 35.40 | 16.63 | 0.439237E+09 | 544.98 | 35.40 | 16.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24210040.50 | 1647.73 | 13-JAN-06:06 | 0.50 | -2.4 | 0.456674E+09 | 626.06 | 26-JAN-10:00 | -21.7 | -22.3 |
February | 0.166298E+09 | 1935.58 | 27-FEB-16:20 | 16.67 | 6.71 | 0.421269E+09 | 670.49 | 27-FEB-14:00 | 16.67 | 6.71 |
March | 0.673273E+09 | 2103.38 | 29-MAR-16:00 | 12.20 | 4.07 | 0.510577E+09 | 703.52 | 29-MAR-13:00 | 12.20 | 4.07 |
April | 0.164038E+10 | 3710.14 | 07-APR-14:40 | 22.23 | 9.16 | 0.485832E+09 | 845.60 | 07-APR-13:20 | 22.23 | 9.16 |
May | 0.298695E+10 | 6684.12 | 19-MAY-16:00 | 27.80 | 14.54 | 0.566823E+09 | 845.63 | 19-MAY-13:09 | 27.80 | 14.54 |
June | 0.589942E+10 | 12886.04 | 21-JUN-05:02 | 15.87 | 11.84 | 0.639474E+09 | 845.64 | 20-JUN-13:09 | 15.87 | 11.84 |
July | 0.736853E+10 | 16549.72 | 16-JUL-18:31 | 32.40 | 17.11 | 0.609475E+09 | 845.65 | 03-JUL-13:09 | 32.40 | 17.11 |
August | 0.617257E+10 | 9577.59 | 06-AUG-16:12 | 35.40 | 16.13 | 0.670153E+09 | 845.64 | 01-AUG-13:09 | 35.40 | 16.13 |
September | 0.344148E+10 | 8858.68 | 05-SEP-05:02 | 18.40 | 11.40 | 0.541616E+09 | 845.65 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.154184E+10 | 3123.34 | 18-OCT-14:00 | 25.00 | 11.40 | 0.498313E+09 | 835.56 | 19-OCT-13:00 | 21.10 | 10.22 |
November | 0.456689E+09 | 1934.56 | 17-NOV-17:00 | 17.20 | 8.89 | 0.462467E+09 | 684.71 | 08-NOV-14:00 | 17.20 | 8.89 |
December | 78870800.93 | 1565.46 | 06-DEC-16:00 | 9.40 | 4.51 | 0.445602E+09 | 626.05 | 28-DEC-10:09 | -22.1 | -22.5 |
Annual Sum or Average | 0.304505E+11 | 0.630828E+10 | ||||||||
Minimum of Months | 24210040.50 | 1565.46 | 0.50 | -2.4 | 0.421269E+09 | 626.05 | -22.1 | -22.5 | ||
Maximum of Months | 0.736853E+10 | 16549.72 | 35.40 | 17.11 | 0.670153E+09 | 845.65 | 35.40 | 17.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 47788649.49 | 1583.57 | 13-JAN-06:04 | 0.50 | -2.4 | 0.298445E+09 | 403.46 | 09-JAN-14:00 | 0.50 | -2.4 |
February | 0.489596E+09 | 2173.93 | 26-FEB-14:51 | 16.70 | 6.48 | 0.277271E+09 | 513.22 | 27-FEB-10:00 | 14.40 | 5.37 |
March | 0.125960E+10 | 4670.27 | 23-MAR-10:30 | 8.60 | 1.66 | 0.349594E+09 | 544.95 | 22-MAR-09:00 | 8.60 | 1.66 |
April | 0.244921E+10 | 8556.23 | 25-APR-09:40 | 11.27 | 5.45 | 0.340510E+09 | 544.95 | 25-APR-09:09 | 11.27 | 5.45 |
May | 0.387547E+10 | 10616.61 | 19-MAY-09:20 | 18.53 | 11.74 | 0.391309E+09 | 544.99 | 02-MAY-13:09 | 18.53 | 11.74 |
June | 0.729176E+10 | 19840.57 | 11-JUN-09:42 | 21.23 | 11.78 | 0.419027E+09 | 545.96 | 23-JUN-09:00 | 27.80 | 15.44 |
July | 0.925580E+10 | 21839.77 | 02-JUL-07:51 | 20.60 | 14.56 | 0.395090E+09 | 545.72 | 13-JUL-09:39 | 22.57 | 13.31 |
August | 0.805829E+10 | 20850.67 | 06-AUG-09:32 | 29.07 | 14.77 | 0.439298E+09 | 546.01 | 11-AUG-09:00 | 27.80 | 12.62 |
September | 0.417997E+10 | 15897.80 | 04-SEP-09:02 | 26.88 | 14.90 | 0.365840E+09 | 544.96 | 14-SEP-13:00 | 21.70 | 13.42 |
October | 0.198029E+10 | 5314.39 | 18-OCT-10:00 | 20.00 | 8.80 | 0.344009E+09 | 544.94 | 12-OCT-09:30 | 20.00 | 8.80 |
November | 0.697100E+09 | 2091.36 | 03-NOV-10:10 | 9.10 | 5.57 | 0.302107E+09 | 498.96 | 03-NOV-09:00 | 9.10 | 5.57 |
December | 0.146116E+09 | 1622.53 | 19-DEC-06:04 | 3.80 | 0.86 | 0.288052E+09 | 412.43 | 06-DEC-10:50 | 3.80 | 0.86 |
Annual Sum or Average | 0.397310E+11 | 0.421055E+10 | ||||||||
Minimum of Months | 47788649.49 | 1583.57 | 0.50 | -2.4 | 0.277271E+09 | 403.46 | 0.50 | -2.4 | ||
Maximum of Months | 0.925580E+10 | 21839.77 | 29.07 | 14.90 | 0.439298E+09 | 546.01 | 27.80 | 15.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102543E+10 | 7865.02 | 31-JAN-13:40 | -0.8 | -4.5 | 0.489865E+09 | 845.63 | 31-JAN-14:00 | -1.1 | -4.4 |
February | 0.263181E+10 | 25205.76 | 26-FEB-14:11 | 15.97 | 6.00 | 0.478319E+09 | 845.63 | 01-FEB-14:00 | 15.97 | 6.00 |
March | 0.377529E+10 | 15941.66 | 01-MAR-14:10 | 6.97 | 2.89 | 0.575361E+09 | 845.64 | 14-MAR-13:00 | 15.00 | 6.94 |
April | 0.409938E+10 | 17155.95 | 16-APR-14:13 | 19.40 | 8.41 | 0.526728E+09 | 846.02 | 24-APR-13:00 | 17.80 | 9.82 |
May | 0.527045E+10 | 16901.06 | 14-MAY-13:53 | 16.70 | 6.76 | 0.594123E+09 | 845.71 | 02-MAY-13:09 | 16.70 | 6.76 |
June | 0.829211E+10 | 14571.78 | 30-JUN-13:40 | 28.33 | 14.03 | 0.638169E+09 | 845.66 | 21-JUN-13:09 | 28.33 | 14.03 |
July | 0.110335E+11 | 25629.45 | 02-JUL-13:52 | 24.40 | 14.05 | 0.609414E+09 | 846.30 | 14-JUL-13:00 | 32.80 | 16.83 |
August | 0.120414E+11 | 25858.90 | 06-AUG-13:32 | 34.23 | 15.17 | 0.676334E+09 | 849.17 | 30-AUG-13:39 | 26.33 | 14.35 |
September | 0.888953E+10 | 27260.18 | 03-SEP-13:32 | 33.70 | 16.17 | 0.572374E+09 | 860.06 | 01-SEP-13:50 | 33.70 | 16.17 |
October | 0.587830E+10 | 27420.36 | 15-OCT-14:22 | 23.05 | 11.10 | 0.571526E+09 | 848.79 | 18-OCT-13:50 | 24.90 | 11.31 |
November | 0.304462E+10 | 15345.92 | 03-NOV-13:30 | 14.35 | 7.74 | 0.528077E+09 | 845.63 | 10-NOV-14:30 | 5.80 | 0.98 |
December | 0.143721E+10 | 7612.83 | 06-DEC-14:40 | 11.30 | 5.42 | 0.484441E+09 | 845.62 | 12-DEC-14:00 | -2.8 | -5.6 |
Annual Sum or Average | 0.674191E+11 | 0.674473E+10 | ||||||||
Minimum of Months | 0.102543E+10 | 7612.83 | -0.8 | -4.5 | 0.478319E+09 | 845.62 | -2.8 | -5.6 | ||
Maximum of Months | 0.120414E+11 | 27420.36 | 34.23 | 16.17 | 0.676334E+09 | 860.06 | 33.70 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183031E+09 | 2230.16 | 13-JAN-15:50 | 9.08 | 4.76 | 0.299484E+09 | 457.44 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.721024E+09 | 5358.24 | 28-FEB-16:40 | 10.37 | 4.49 | 0.280230E+09 | 521.20 | 27-FEB-16:49 | 10.37 | 4.49 |
March | 0.151381E+10 | 7309.48 | 28-MAR-17:00 | 10.60 | 2.97 | 0.342445E+09 | 544.81 | 02-MAR-14:00 | 10.60 | 2.97 |
April | 0.282911E+10 | 17134.28 | 16-APR-17:32 | 19.60 | 8.82 | 0.323692E+09 | 544.94 | 07-APR-13:20 | 19.60 | 8.82 |
May | 0.448930E+10 | 25155.20 | 28-MAY-17:41 | 20.18 | 10.35 | 0.371815E+09 | 544.96 | 19-MAY-13:09 | 20.18 | 10.35 |
June | 0.706856E+10 | 24271.47 | 18-JUN-18:01 | 25.00 | 14.75 | 0.409224E+09 | 544.96 | 29-JUN-09:30 | 25.55 | 12.82 |
July | 0.876244E+10 | 26295.81 | 02-JUL-17:51 | 25.60 | 14.12 | 0.392394E+09 | 544.97 | 03-JUL-13:09 | 19.07 | 14.10 |
August | 0.779991E+10 | 23363.13 | 06-AUG-16:12 | 35.40 | 16.13 | 0.431837E+09 | 544.96 | 01-AUG-13:09 | 35.40 | 16.13 |
September | 0.461398E+10 | 23400.97 | 04-SEP-16:22 | 32.80 | 16.63 | 0.351476E+09 | 544.95 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.238364E+10 | 8817.31 | 18-OCT-16:00 | 24.40 | 11.02 | 0.333242E+09 | 544.78 | 13-OCT-13:00 | 24.40 | 11.02 |
November | 0.105316E+10 | 3779.42 | 03-NOV-15:50 | 14.35 | 7.69 | 0.310017E+09 | 521.18 | 03-NOV-15:00 | 14.30 | 7.69 |
December | 0.364085E+09 | 2457.31 | 06-DEC-15:50 | 9.68 | 4.65 | 0.290815E+09 | 490.66 | 06-DEC-15:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.417821E+11 | 0.413667E+10 | ||||||||
Minimum of Months | 0.183031E+09 | 2230.16 | 9.08 | 2.97 | 0.280230E+09 | 457.44 | 8.90 | 2.97 | ||
Maximum of Months | 0.876244E+10 | 26295.81 | 35.40 | 16.63 | 0.431837E+09 | 544.97 | 35.40 | 16.13 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294962E+09 | 6763.44 | 06-JAN-05:01 | -24.5 | -24.9 | 0.00 | 0.00 | 01-JAN-00:10 | -24.5 | -24.9 |
February | 0.500668E+09 | 3306.61 | 09-FEB-06:01 | -17.9 | -18.2 | 0.00 | 0.00 | 01-FEB-00:10 | -17.9 | -18.2 |
March | 0.133814E+10 | 4110.25 | 04-MAR-06:01 | -20.1 | -20.7 | 0.00 | 0.00 | 01-MAR-00:10 | -20.1 | -20.7 |
April | 0.287506E+10 | 4710.53 | 25-APR-15:40 | 17.53 | 7.62 | 0.00 | 0.00 | 01-APR-00:10 | 17.53 | 7.62 |
May | 0.292806E+10 | 8407.49 | 30-MAY-05:15 | 15.60 | 11.34 | 0.00 | 0.00 | 01-MAY-00:10 | 15.60 | 11.34 |
June | 0.608974E+10 | 6882.95 | 26-JUN-05:15 | 10.33 | 9.12 | 0.00 | 0.00 | 01-JUN-00:10 | 10.33 | 9.12 |
July | 0.796397E+10 | 10390.56 | 17-JUL-05:15 | 16.83 | 12.38 | 0.00 | 0.00 | 01-JUL-00:10 | 16.83 | 12.38 |
August | 0.803895E+10 | 9813.80 | 07-AUG-05:10 | 17.48 | 9.94 | 0.00 | 0.00 | 01-AUG-00:10 | 17.48 | 9.94 |
September | 0.443642E+10 | 9994.60 | 05-SEP-05:25 | 18.60 | 12.09 | 0.00 | 0.00 | 01-SEP-00:10 | 18.60 | 12.09 |
October | 0.289593E+10 | 4788.83 | 20-OCT-05:15 | 2.60 | 0.80 | 0.00 | 0.00 | 01-OCT-00:10 | 2.60 | 0.80 |
November | 0.142437E+10 | 4643.21 | 06-NOV-06:07 | -3.5 | -4.3 | 0.00 | 0.00 | 01-NOV-00:10 | -3.5 | -4.3 |
December | 0.489943E+09 | 3443.02 | 07-DEC-06:08 | -1.2 | -2.6 | 0.00 | 0.00 | 01-DEC-00:10 | -1.2 | -2.6 |
Annual Sum or Average | 0.392762E+11 | 0.00 | ||||||||
Minimum of Months | 0.294962E+09 | 3306.61 | -24.5 | -24.9 | 0.00 | 0.00 | -24.5 | -24.9 | ||
Maximum of Months | 0.803895E+10 | 10390.56 | 18.60 | 12.38 | 0.00 | 0.00 | 18.60 | 12.38 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199294E+09 | 8423.43 | 06-JAN-04:01 | -24.4 | -24.9 | 0.00 | 0.00 | 01-JAN-00:10 | -24.4 | -24.9 |
February | 0.167347E+09 | 7724.18 | 04-FEB-04:01 | -21.9 | -22.2 | 0.00 | 0.00 | 01-FEB-00:10 | -21.9 | -22.2 |
March | 0.543671E+09 | 7907.73 | 04-MAR-05:01 | -19.1 | -19.6 | 0.00 | 0.00 | 01-MAR-00:10 | -19.1 | -19.6 |
April | 0.918442E+09 | 5092.20 | 15-APR-05:02 | -0.6 | -3.4 | 0.00 | 0.00 | 01-APR-00:10 | -0.6 | -3.4 |
May | 0.152707E+10 | 5274.66 | 08-MAY-04:02 | -2.3 | -2.7 | 0.00 | 0.00 | 01-MAY-00:10 | -2.3 | -2.7 |
June | 0.412227E+10 | 5676.48 | 23-JUN-05:15 | 17.97 | 11.79 | 0.00 | 0.00 | 01-JUN-00:10 | 17.97 | 11.79 |
July | 0.568136E+10 | 6642.22 | 17-JUL-15:30 | 36.65 | 17.14 | 0.00 | 0.00 | 01-JUL-00:10 | 36.65 | 17.14 |
August | 0.541988E+10 | 6546.47 | 10-AUG-15:40 | 32.43 | 13.91 | 0.00 | 0.00 | 01-AUG-00:10 | 32.43 | 13.91 |
September | 0.296788E+10 | 6350.59 | 05-SEP-14:50 | 24.40 | 14.84 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 14.84 |
October | 0.119254E+10 | 3913.99 | 11-OCT-05:01 | -0.5 | -2.4 | 0.00 | 0.00 | 01-OCT-00:10 | -0.5 | -2.4 |
November | 0.554011E+09 | 7941.31 | 27-NOV-04:01 | -15.8 | -16.7 | 0.00 | 0.00 | 01-NOV-00:10 | -15.8 | -16.7 |
December | 0.155501E+09 | 7416.82 | 28-DEC-04:11 | -22.6 | -23.0 | 0.00 | 0.00 | 01-DEC-00:10 | -22.6 | -23.0 |
Annual Sum or Average | 0.234493E+11 | 0.00 | ||||||||
Minimum of Months | 0.155501E+09 | 3913.99 | -24.4 | -24.9 | 0.00 | 0.00 | -24.4 | -24.9 | ||
Maximum of Months | 0.568136E+10 | 8423.43 | 36.65 | 17.14 | 0.00 | 0.00 | 36.65 | 17.14 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 | -1.3 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.3 |
February | 47435308.52 | 2556.79 | 26-FEB-15:37 | 16.30 | 6.32 | 0.00 | 0.00 | 01-FEB-00:10 | 16.30 | 6.32 |
March | 0.275962E+09 | 2865.79 | 18-MAR-15:02 | 12.12 | 4.19 | 0.00 | 0.00 | 01-MAR-00:10 | 12.12 | 4.19 |
April | 0.149686E+10 | 9045.82 | 25-APR-15:00 | 17.00 | 7.46 | 0.00 | 0.00 | 01-APR-00:10 | 17.00 | 7.46 |
May | 0.355993E+10 | 14500.42 | 19-MAY-15:00 | 28.30 | 14.88 | 0.00 | 0.00 | 01-MAY-00:10 | 28.30 | 14.88 |
June | 0.816015E+10 | 17417.27 | 23-JUN-13:30 | 31.40 | 15.21 | 0.00 | 0.00 | 01-JUN-00:10 | 31.40 | 15.21 |
July | 0.111437E+11 | 20956.76 | 17-JUL-15:10 | 36.28 | 17.05 | 0.00 | 0.00 | 01-JUL-00:10 | 36.28 | 17.05 |
August | 0.929109E+10 | 18390.35 | 07-AUG-15:40 | 32.40 | 16.10 | 0.00 | 0.00 | 01-AUG-00:10 | 32.40 | 16.10 |
September | 0.403733E+10 | 13204.98 | 01-SEP-15:40 | 28.30 | 14.15 | 0.00 | 0.00 | 01-SEP-00:10 | 28.30 | 14.15 |
October | 0.781449E+09 | 6745.85 | 18-OCT-15:20 | 24.80 | 11.42 | 0.00 | 0.00 | 01-OCT-00:10 | 24.80 | 11.42 |
November | 21626511.32 | 1774.96 | 04-NOV-15:02 | 16.60 | 7.90 | 0.00 | 0.00 | 01-NOV-00:10 | 16.60 | 7.90 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.388156E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.1 | -4.2 | 0.00 | 0.00 | -2.1 | -4.2 | ||
Maximum of Months | 0.111437E+11 | 20956.76 | 36.28 | 17.05 | 0.00 | 0.00 | 36.28 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182163E+10 | 1834.61 | 19-JAN-16:50 | -6.4 | -8.0 | 95126378.79 | 126.82 | 20-JAN-14:09 | 0.50 | -3.2 |
February | 0.709744E+10 | 4208.55 | 26-FEB-17:27 | 13.35 | 5.05 | 86396455.26 | 126.82 | 23-FEB-14:09 | 13.35 | 5.05 |
March | 0.137135E+11 | 6820.24 | 31-MAR-24:00 | 2.50 | 0.99 | 0.103236E+09 | 126.82 | 15-MAR-13:09 | 2.50 | 0.99 |
April | 0.186708E+11 | 8166.50 | 22-APR-18:10 | 15.63 | 8.19 | 91605276.45 | 126.82 | 24-APR-09:00 | 14.40 | 8.99 |
May | 0.411981E+10 | 3473.41 | 31-MAY-24:00 | 15.50 | 10.27 | 99234972.78 | 126.84 | 30-MAY-09:30 | 15.50 | 10.27 |
June | 0.923618E+10 | 5362.06 | 30-JUN-24:00 | 19.60 | 12.23 | 98962958.01 | 126.85 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.147233E+11 | 7237.68 | 31-JUL-23:40 | 19.77 | 11.91 | 91884637.63 | 126.84 | 03-JUL-13:09 | 19.77 | 11.91 |
August | 0.196665E+11 | 8146.15 | 05-AUG-19:42 | 27.22 | 14.68 | 0.103244E+09 | 126.83 | 22-AUG-09:09 | 16.88 | 12.48 |
September | 0.412068E+10 | 3315.40 | 30-SEP-24:00 | 11.80 | 6.26 | 91610391.10 | 126.85 | 06-SEP-13:30 | 11.80 | 6.26 |
October | 0.909416E+10 | 4977.59 | 31-OCT-24:00 | 4.70 | 1.47 | 95230920.76 | 126.83 | 25-OCT-09:00 | 4.70 | 1.47 |
November | 0.133714E+11 | 5916.85 | 13-NOV-16:20 | 3.27 | -2.5 | 94300362.51 | 126.83 | 08-NOV-14:00 | 3.27 | -2.5 |
December | 0.183771E+11 | 7694.20 | 06-DEC-16:10 | 8.95 | 4.16 | 91880814.44 | 126.82 | 01-DEC-14:09 | 8.95 | 4.16 |
Annual Sum or Average | 0.134013E+12 | 0.114271E+10 | ||||||||
Minimum of Months | 0.182163E+10 | 1834.61 | -6.4 | -8.0 | 86396455.26 | 126.82 | 0.50 | -3.2 | ||
Maximum of Months | 0.196665E+11 | 8166.50 | 27.22 | 14.68 | 0.103244E+09 | 126.85 | 19.77 | 12.48 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.307180E+09 | 1367.93 | 19-JAN-16:50 | -6.4 | -8.0 | 92302050.86 | 126.82 | 20-JAN-14:09 | 0.50 | -3.2 |
February | 0.469503E+10 | 3778.95 | 28-FEB-17:00 | 10.00 | 4.31 | 86396468.70 | 126.82 | 23-FEB-14:09 | 10.00 | 4.31 |
March | 0.111306E+11 | 5825.80 | 31-MAR-23:40 | 2.17 | 0.68 | 0.103236E+09 | 126.82 | 15-MAR-13:09 | 2.17 | 0.68 |
April | 0.166580E+11 | 7650.19 | 25-APR-18:10 | 16.73 | 7.64 | 91605308.83 | 126.82 | 24-APR-09:00 | 16.73 | 7.64 |
May | 0.311762E+10 | 3275.65 | 31-MAY-24:00 | 15.50 | 10.27 | 99234856.52 | 126.84 | 30-MAY-09:39 | 15.50 | 10.27 |
June | 0.845695E+10 | 5225.70 | 30-JUN-24:00 | 19.60 | 12.23 | 98962652.33 | 126.85 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.138988E+11 | 7010.97 | 31-JUL-23:53 | 19.20 | 11.32 | 91884435.00 | 126.84 | 03-JUL-13:09 | 19.20 | 11.32 |
August | 0.186081E+11 | 7762.66 | 05-AUG-19:42 | 27.22 | 14.68 | 0.103242E+09 | 126.83 | 01-AUG-13:00 | 27.22 | 14.68 |
September | 0.330806E+10 | 2910.97 | 30-SEP-23:50 | 12.03 | 6.45 | 91609659.35 | 126.84 | 11-SEP-13:00 | 12.03 | 6.45 |
October | 0.738893E+10 | 4147.12 | 31-OCT-24:00 | 4.70 | 1.47 | 95230874.25 | 126.83 | 25-OCT-09:00 | 4.70 | 1.47 |
November | 0.107738E+11 | 5411.18 | 03-NOV-16:00 | 14.30 | 7.69 | 94300375.59 | 126.83 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.146218E+11 | 6976.31 | 06-DEC-16:20 | 8.50 | 3.80 | 91880840.76 | 126.82 | 01-DEC-14:09 | 8.50 | 3.80 |
Annual Sum or Average | 0.112965E+12 | 0.113989E+10 | ||||||||
Minimum of Months | 0.307180E+09 | 1367.93 | -6.4 | -8.0 | 86396468.70 | 126.82 | 0.50 | -3.2 | ||
Maximum of Months | 0.186081E+11 | 7762.66 | 27.22 | 14.68 | 0.103242E+09 | 126.85 | 27.22 | 14.68 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123629E+09 | 1106.10 | 13-JAN-16:30 | 8.35 | 4.30 | 86035906.68 | 128.67 | 02-JAN-14:30 | 8.35 | 4.30 |
February | 0.311666E+10 | 3637.71 | 28-FEB-17:00 | 10.00 | 4.31 | 86389044.28 | 126.82 | 23-FEB-14:09 | 10.00 | 4.31 |
March | 0.929635E+10 | 5621.28 | 28-MAR-17:50 | 9.18 | 2.32 | 0.103236E+09 | 126.82 | 15-MAR-13:09 | 9.18 | 2.32 |
April | 0.153051E+11 | 7704.76 | 25-APR-18:10 | 16.73 | 7.64 | 91605348.85 | 126.83 | 24-APR-09:00 | 16.73 | 7.64 |
May | 0.244674E+10 | 3196.31 | 31-MAY-23:50 | 15.60 | 10.31 | 98859375.05 | 126.84 | 30-MAY-09:39 | 15.60 | 10.31 |
June | 0.819537E+10 | 5190.09 | 30-JUN-24:00 | 19.60 | 12.23 | 98962786.84 | 126.85 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.138342E+11 | 7008.07 | 31-JUL-23:53 | 19.20 | 11.32 | 91884589.43 | 126.84 | 03-JUL-13:09 | 19.20 | 11.32 |
August | 0.184351E+11 | 7932.72 | 05-AUG-19:42 | 27.22 | 14.68 | 0.103242E+09 | 126.83 | 01-AUG-13:00 | 27.22 | 14.68 |
September | 0.267720E+10 | 2669.82 | 04-SEP-17:32 | 32.07 | 16.48 | 91602156.42 | 126.86 | 19-SEP-09:09 | 5.10 | 3.14 |
October | 0.574574E+10 | 3878.60 | 18-OCT-17:00 | 21.70 | 10.27 | 95230848.66 | 126.83 | 25-OCT-09:00 | 13.30 | 8.54 |
November | 0.861742E+10 | 5248.32 | 03-NOV-16:00 | 14.30 | 7.69 | 94300382.58 | 126.83 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.124358E+11 | 6824.60 | 06-DEC-16:20 | 8.50 | 3.80 | 91880847.86 | 126.82 | 01-DEC-14:09 | 8.50 | 3.80 |
Annual Sum or Average | 0.100229E+12 | 0.113323E+10 | ||||||||
Minimum of Months | 0.123629E+09 | 1106.10 | 8.35 | 2.32 | 86035906.68 | 126.82 | 5.10 | 2.32 | ||
Maximum of Months | 0.184351E+11 | 7932.72 | 32.07 | 16.48 | 0.103242E+09 | 128.67 | 27.22 | 14.68 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232601E+12 | 90731.48 | 02-JAN-17:00 | 2.20 | -1.7 | 0.206144E+10 | 2745.29 | 02-JAN-14:00 | 2.20 | -1.7 |
February | 0.431922E+12 | 182427.28 | 27-FEB-17:00 | 12.20 | 5.32 | 0.187022E+10 | 2745.29 | 02-FEB-10:20 | 12.20 | 5.32 |
March | 0.725794E+12 | 357279.86 | 31-MAR-24:00 | 2.50 | 0.99 | 0.223475E+10 | 2745.29 | 03-MAR-14:09 | 2.50 | 0.99 |
April | 0.940310E+12 | 366089.42 | 25-APR-16:00 | 17.80 | 7.70 | 0.198297E+10 | 2745.29 | 07-APR-13:50 | 17.80 | 7.70 |
May | 0.238800E+12 | 175643.84 | 31-MAY-24:00 | 15.50 | 10.27 | 0.214810E+10 | 2745.29 | 09-MAY-09:50 | 15.50 | 10.27 |
June | 0.468655E+12 | 267540.23 | 30-JUN-23:53 | 19.60 | 12.23 | 0.214213E+10 | 2745.29 | 12-JUN-09:50 | 19.60 | 12.23 |
July | 0.731149E+12 | 359858.06 | 31-JUL-23:53 | 19.20 | 11.32 | 0.198894E+10 | 2745.29 | 31-JUL-13:09 | 19.20 | 11.32 |
August | 0.976590E+12 | 367701.48 | 07-AUG-16:00 | 32.20 | 16.16 | 0.223475E+10 | 2745.29 | 17-AUG-09:20 | 8.90 | 6.69 |
September | 0.233961E+12 | 175594.96 | 30-SEP-24:00 | 11.80 | 6.26 | 0.198297E+10 | 2745.29 | 01-SEP-09:09 | 11.80 | 6.26 |
October | 0.485319E+12 | 267264.64 | 31-OCT-24:00 | 4.70 | 1.47 | 0.206144E+10 | 2745.29 | 05-OCT-13:20 | 4.70 | 1.47 |
November | 0.705585E+12 | 275333.80 | 06-NOV-16:55 | 6.70 | 2.26 | 0.204131E+10 | 2745.29 | 01-NOV-13:09 | 6.70 | 2.26 |
December | 0.972227E+12 | 366415.84 | 06-DEC-17:00 | 6.70 | 2.38 | 0.198894E+10 | 2745.29 | 14-DEC-10:39 | -7.8 | -8.1 |
Annual Sum or Average | 0.714291E+13 | 0.247380E+11 | ||||||||
Minimum of Months | 0.232601E+12 | 90731.48 | 2.20 | -1.7 | 0.187022E+10 | 2745.29 | -7.8 | -8.1 | ||
Maximum of Months | 0.976590E+12 | 367701.48 | 32.20 | 16.16 | 0.223475E+10 | 2745.29 | 19.60 | 12.23 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310787E+09 | 10575.06 | 05-JAN-05:03 | -4.1 |
February | 80849053.29 | 10629.47 | 28-FEB-05:04 | -3.4 |
March | 87501689.68 | 10811.20 | 15-MAR-04:04 | -1.1 |
April | 0.115807E+09 | 11026.00 | 24-APR-03:05 | 4.82 |
May | 0.281398E+09 | 12277.47 | 20-MAY-16:15 | 29.63 |
June | 0.260200E+09 | 11743.27 | 24-JUN-15:02 | 28.80 |
July | 0.439905E+09 | 15506.76 | 15-JUL-16:02 | 32.80 |
August | 0.454627E+09 | 17614.99 | 05-AUG-16:02 | 35.22 |
September | 0.481710E+09 | 16434.61 | 02-SEP-16:13 | 34.07 |
October | 0.327882E+09 | 11063.97 | 03-OCT-03:15 | 3.17 |
November | 0.262912E+09 | 11919.30 | 12-NOV-16:03 | -0.8 |
December | 66355329.53 | 10630.16 | 18-DEC-04:03 | -3.7 |
Annual Sum or Average | 0.316993E+10 | |||
Minimum of Months | 66355329.53 | 10575.06 | -4.1 | |
Maximum of Months | 0.481710E+09 | 17614.99 | 35.22 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.622617E+09 | 49319.40 | 09-JAN-05:01 | -27.2 |
February | 0.187685E+09 | 47727.01 | 06-FEB-05:01 | -0.4 |
March | 45598071.01 | 45845.76 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 7813137.97 | 43063.39 | 27-NOV-06:02 | -14.5 |
December | 68255377.70 | 43931.24 | 26-DEC-06:02 | -7.9 |
Annual Sum or Average | 0.931968E+09 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.622617E+09 | 49319.40 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109353E+11 | 71493.69 | 09-JAN-04:01 | -27.2 |
February | 0.410616E+10 | 70575.83 | 06-FEB-04:11 | -0.6 |
March | 0.230994E+10 | 70713.87 | 06-MAR-04:11 | -18.5 |
April | 0.143234E+09 | 57432.24 | 29-APR-05:01 | -7.7 |
May | 0.570419E+09 | 63697.51 | 08-MAY-04:11 | -2.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 4883606.03 | 22944.71 | 19-SEP-05:03 | 2.20 |
October | 0.366432E+09 | 64071.48 | 10-OCT-04:11 | -5.4 |
November | 0.267902E+10 | 70002.39 | 27-NOV-04:01 | -15.8 |
December | 0.613236E+10 | 70616.20 | 26-DEC-04:11 | -6.5 |
Annual Sum or Average | 0.272478E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.109353E+11 | 71493.69 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207312E+10 | 12119.53 | 09-JAN-04:01 | -27.2 |
February | 0.518213E+09 | 10927.61 | 04-FEB-05:01 | -20.4 |
March | 67217290.45 | 10641.39 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 16460001.99 | 9839.92 | 27-NOV-06:02 | -14.5 |
December | 0.295887E+09 | 10714.76 | 30-DEC-05:01 | -20.6 |
Annual Sum or Average | 0.297090E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.207312E+10 | 12119.53 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134880E+10 | 14257.14 | 09-JAN-04:01 | -27.2 |
February | 0.389212E+09 | 12888.81 | 04-FEB-05:01 | -20.4 |
March | 58579393.36 | 12545.67 | 06-MAR-05:01 | -18.4 |
April | 19515.25 | 131.33 | 28-APR-05:04 | -6.5 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 29418773.67 | 11135.55 | 27-NOV-05:01 | -15.4 |
December | 0.330196E+09 | 12689.69 | 30-DEC-05:01 | -20.6 |
Annual Sum or Average | 0.215623E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.134880E+10 | 14257.14 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189986E+10 | 19455.32 | 11-JAN-04:01 | -28.9 |
February | 0.462339E+09 | 18020.02 | 04-FEB-05:01 | -20.4 |
March | 0.123049E+09 | 17939.22 | 06-MAR-05:01 | -18.4 |
April | 1307114.99 | 8503.67 | 29-APR-05:01 | -7.7 |
May | 8683681.28 | 14149.73 | 09-MAY-05:01 | -2.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 1895396.78 | 7523.73 | 10-OCT-05:03 | -6.1 |
November | 81610974.89 | 17208.12 | 27-NOV-05:01 | -15.4 |
December | 0.441515E+09 | 17800.17 | 29-DEC-05:01 | -25.0 |
Annual Sum or Average | 0.302026E+10 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.189986E+10 | 19455.32 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.565192E+09 | 12726.97 | 09-JAN-04:01 | -27.2 |
February | 31999047.01 | 10211.25 | 01-FEB-06:01 | -25.0 |
March | 1919592.02 | 10134.86 | 06-MAR-06:01 | -16.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 237056.65 | 1975.47 | 27-NOV-06:02 | -14.5 |
December | 3370788.25 | 10135.16 | 29-DEC-06:01 | -25.1 |
Annual Sum or Average | 0.602718E+09 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.565192E+09 | 12726.97 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.708346E+10 | 11896.42 | 09-JAN-04:01 | -27.2 |
February | 0.333474E+10 | 11518.06 | 06-FEB-04:01 | -0.6 |
March | 0.132276E+10 | 11566.23 | 06-MAR-04:01 | -18.4 |
April | 0.103008E+09 | 9666.30 | 29-APR-04:01 | -7.8 |
May | 98650006.10 | 9898.74 | 08-MAY-04:02 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 7968567.36 | 8733.47 | 20-SEP-05:02 | 3.30 |
October | 0.103534E+09 | 9767.68 | 10-OCT-04:02 | -5.2 |
November | 0.122492E+10 | 11225.98 | 27-NOV-04:01 | -15.8 |
December | 0.398255E+10 | 11906.08 | 31-DEC-03:12 | -24.6 |
Annual Sum or Average | 0.172616E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.708346E+10 | 11906.08 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.426860E+10 | 17259.71 | 09-JAN-04:01 | -27.2 |
February | 0.184046E+10 | 16617.31 | 06-FEB-04:01 | -0.6 |
March | 0.687055E+09 | 16701.13 | 06-MAR-04:01 | -18.4 |
April | 57372032.92 | 13921.72 | 29-APR-04:01 | -7.8 |
May | 58975748.69 | 14165.99 | 08-MAY-04:02 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 4007086.76 | 4925.83 | 19-SEP-05:03 | 2.20 |
October | 57170694.45 | 13541.66 | 10-OCT-04:02 | -5.2 |
November | 0.745954E+09 | 16116.98 | 27-NOV-04:01 | -15.8 |
December | 0.239504E+10 | 17076.51 | 31-DEC-03:12 | -24.6 |
Annual Sum or Average | 0.101146E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.426860E+10 | 17259.71 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.434019E+10 | 20331.13 | 09-JAN-04:01 | -27.2 |
February | 0.156531E+10 | 19496.32 | 06-FEB-04:01 | -0.6 |
March | 0.660264E+09 | 19723.80 | 06-MAR-04:01 | -18.4 |
April | 79898674.66 | 16431.11 | 29-APR-04:01 | -7.8 |
May | 92943490.74 | 16776.49 | 08-MAY-04:02 | -2.3 |
June | 32259.01 | 215.06 | 17-JUN-05:05 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 700391.28 | 2813.68 | 19-SEP-05:03 | 2.20 |
October | 42380882.32 | 15692.04 | 11-OCT-05:01 | -0.5 |
November | 0.647734E+09 | 19191.39 | 27-NOV-04:01 | -15.8 |
December | 0.225356E+10 | 20231.11 | 31-DEC-03:12 | -24.6 |
Annual Sum or Average | 0.968302E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.434019E+10 | 20331.13 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367499E+10 | 18177.66 | 09-JAN-04:01 | -27.2 |
February | 0.131969E+10 | 17198.84 | 06-FEB-04:01 | -0.6 |
March | 0.479741E+09 | 17588.24 | 06-MAR-04:01 | -18.4 |
April | 24564242.43 | 14055.15 | 29-APR-05:01 | -7.7 |
May | 32436276.25 | 13820.72 | 09-MAY-05:01 | -2.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 989709.11 | 2786.58 | 19-SEP-05:03 | 2.20 |
October | 28072720.51 | 13033.25 | 11-OCT-05:01 | -0.5 |
November | 0.463388E+09 | 17131.50 | 27-NOV-04:01 | -15.8 |
December | 0.172820E+10 | 17367.86 | 30-DEC-04:11 | -20.2 |
Annual Sum or Average | 0.775208E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.367499E+10 | 18177.66 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138405E+11 | 16941.69 | 09-JAN-06:01 | -27.2 |
February | 0.717678E+10 | 16220.30 | 05-FEB-17:32 | -17.9 |
March | 0.455503E+10 | 16563.28 | 06-MAR-02:52 | -18.9 |
April | 0.121628E+10 | 14308.72 | 29-APR-03:02 | -6.9 |
May | 0.817917E+09 | 15174.77 | 01-MAY-03:01 | -0.7 |
June | 20101118.99 | 12844.71 | 17-JUN-04:02 | 2.12 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 7585965.78 | 12292.54 | 18-AUG-05:02 | 7.30 |
September | 0.260172E+09 | 13577.19 | 19-SEP-04:01 | 2.20 |
October | 0.123143E+10 | 14968.16 | 10-OCT-03:01 | -4.1 |
November | 0.479898E+10 | 16298.69 | 26-NOV-22:32 | -14.3 |
December | 0.101013E+11 | 16554.67 | 31-DEC-05:52 | -26.1 |
Annual Sum or Average | 0.440260E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.138405E+11 | 16941.69 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.832917E+10 | 18000.20 | 09-JAN-04:01 | -27.2 |
February | 0.390336E+10 | 17521.36 | 05-FEB-02:52 | -20.0 |
March | 0.236979E+10 | 17975.07 | 06-MAR-02:52 | -18.9 |
April | 0.561895E+09 | 15188.20 | 29-APR-03:02 | -6.9 |
May | 0.422558E+09 | 16499.76 | 01-MAY-03:01 | -0.7 |
June | 9936610.59 | 13473.44 | 17-JUN-04:02 | 2.12 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 3773805.57 | 13326.63 | 18-AUG-05:02 | 7.30 |
September | 0.118148E+09 | 14632.49 | 19-SEP-04:01 | 2.20 |
October | 0.581001E+09 | 16224.09 | 10-OCT-03:01 | -4.1 |
November | 0.262030E+10 | 17518.25 | 26-NOV-22:32 | -14.3 |
December | 0.600160E+10 | 18002.74 | 31-DEC-05:52 | -26.1 |
Annual Sum or Average | 0.249215E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.832917E+10 | 18002.74 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.944109E+10 | 23005.01 | 11-JAN-03:52 | -28.9 |
February | 0.408836E+10 | 22364.95 | 05-FEB-02:52 | -20.0 |
March | 0.288153E+10 | 22908.43 | 06-MAR-02:52 | -18.9 |
April | 0.885923E+09 | 19692.00 | 29-APR-03:02 | -6.9 |
May | 0.748632E+09 | 20988.89 | 01-MAY-03:01 | -0.7 |
June | 32503804.89 | 17873.67 | 17-JUN-04:02 | 2.12 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 11465558.95 | 17075.82 | 18-AUG-05:02 | 7.30 |
September | 0.153365E+09 | 18595.20 | 19-SEP-04:01 | 2.20 |
October | 0.600250E+09 | 20803.20 | 10-OCT-03:01 | -4.1 |
November | 0.269974E+10 | 22121.37 | 26-NOV-22:32 | -14.3 |
December | 0.646572E+10 | 23006.95 | 31-DEC-05:52 | -26.1 |
Annual Sum or Average | 0.280086E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.944109E+10 | 23006.95 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.763720E+10 | 20214.31 | 09-JAN-04:01 | -27.2 |
February | 0.311223E+10 | 19276.66 | 05-FEB-02:52 | -20.0 |
March | 0.186142E+10 | 19761.81 | 06-MAR-02:52 | -18.9 |
April | 0.386893E+09 | 16615.11 | 29-APR-04:01 | -7.8 |
May | 0.313524E+09 | 18244.13 | 08-MAY-03:01 | -2.7 |
June | 12934778.29 | 8227.77 | 17-JUN-05:03 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 4247487.45 | 9205.75 | 18-AUG-05:02 | 7.30 |
September | 80319159.34 | 16131.56 | 19-SEP-04:01 | 2.20 |
October | 0.384700E+09 | 18030.66 | 10-OCT-03:01 | -4.1 |
November | 0.185841E+10 | 19249.11 | 26-NOV-22:32 | -14.3 |
December | 0.455162E+10 | 19847.64 | 31-DEC-05:52 | -26.1 |
Annual Sum or Average | 0.202035E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.763720E+10 | 20214.31 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235090E+10 | 9646.47 | 24-JAN-06:03 | 8.22 |
February | 0.125528E+10 | 10937.91 | 08-FEB-06:01 | -4.1 |
March | 0.440682E+09 | 10635.20 | 09-MAR-06:01 | 2.30 |
April | 0.143493E+09 | 10093.83 | 03-APR-04:01 | 2.52 |
May | 89403452.46 | 9240.47 | 01-MAY-04:01 | -0.6 |
June | 87680852.68 | 6753.99 | 12-JUN-03:02 | 12.12 |
July | 0.106770E+09 | 8050.48 | 05-JUL-03:02 | 9.90 |
August | 0.102455E+09 | 10691.33 | 06-AUG-16:01 | 35.50 |
September | 76479339.49 | 7241.00 | 18-SEP-04:02 | 3.90 |
October | 85073574.06 | 9987.07 | 15-OCT-15:11 | 22.60 |
November | 0.284723E+09 | 10835.17 | 30-NOV-06:01 | 1.10 |
December | 0.662635E+09 | 11891.18 | 19-DEC-06:01 | 3.80 |
Annual Sum or Average | 0.568558E+10 | |||
Minimum of Months | 76479339.49 | 6753.99 | -4.1 | |
Maximum of Months | 0.235090E+10 | 11891.18 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.474234E+10 | 12438.37 | 09-JAN-06:15 | -27.2 |
February | 0.289764E+10 | 11576.86 | 06-FEB-06:13 | 0.60 |
March | 0.172098E+10 | 8512.19 | 26-MAR-13:32 | 9.63 |
April | 0.315176E+09 | 9739.08 | 16-APR-16:21 | 20.00 |
May | 0.478838E+09 | 6117.63 | 22-MAY-04:02 | -0.1 |
June | 51177127.96 | 6954.17 | 18-JUN-15:21 | 24.70 |
July | 63473365.20 | 7451.17 | 09-JUL-15:31 | 28.30 |
August | 43781088.73 | 8245.79 | 06-AUG-15:32 | 35.20 |
September | 0.110221E+09 | 7689.30 | 03-SEP-15:21 | 33.30 |
October | 0.364603E+09 | 7264.41 | 15-OCT-16:03 | 22.02 |
November | 0.141068E+10 | 7712.96 | 12-NOV-14:13 | -0.1 |
December | 0.282874E+10 | 5954.32 | 26-DEC-06:08 | -7.9 |
Annual Sum or Average | 0.150277E+11 | |||
Minimum of Months | 43781088.73 | 5954.32 | -27.2 | |
Maximum of Months | 0.474234E+10 | 12438.37 | 35.20 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185625E+11 | 32829.85 | 11-JAN-05:18 | -30.2 |
February | 0.981830E+10 | 27390.41 | 01-FEB-06:13 | -25.0 |
March | 0.709676E+10 | 28292.03 | 06-MAR-05:12 | -17.8 |
April | 0.281234E+10 | 15534.10 | 29-APR-05:02 | -7.7 |
May | 0.196574E+10 | 18973.91 | 08-MAY-04:23 | -2.5 |
June | 0.454313E+09 | 13659.21 | 05-JUN-05:02 | 10.97 |
July | 0.187797E+09 | 13642.22 | 12-JUL-05:03 | 6.85 |
August | 0.347287E+09 | 13022.36 | 28-AUG-05:02 | 7.12 |
September | 0.111065E+10 | 14248.79 | 28-SEP-05:02 | 8.90 |
October | 0.287700E+10 | 19387.52 | 10-OCT-05:03 | -6.1 |
November | 0.746305E+10 | 27905.77 | 27-NOV-05:22 | -15.1 |
December | 0.140811E+11 | 30141.36 | 29-DEC-05:33 | -25.0 |
Annual Sum or Average | 0.667769E+11 | |||
Minimum of Months | 0.187797E+09 | 13022.36 | -30.2 | |
Maximum of Months | 0.185625E+11 | 32829.85 | 10.97 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 74095115.27 | 594.62 | 09-JAN-04:12 | -27.2 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 74095115.27 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 74095115.27 | 594.62 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.603522E+09 | 651.94 | 29-JAN-17:50 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 1910.42 | 3.18 | 08-MAY-04:57 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.603524E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.9 | |
Maximum of Months | 0.603522E+09 | 651.94 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.909793E+09 | 673.81 | 29-JAN-17:50 | -21.9 |
February | 71136365.45 | 620.51 | 05-FEB-18:30 | -18.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 2459457.78 | 727.44 | 30-APR-23:10 | -1.3 |
May | 0.126443E+09 | 649.12 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 34135997.71 | 567.77 | 19-SEP-04:15 | 2.20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.114397E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.9 | |
Maximum of Months | 0.909793E+09 | 727.44 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113123E+11 | 11837.83 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.102611E+11 | 11837.83 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.121930E+11 | 11837.83 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.108909E+11 | 11837.83 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.117527E+11 | 11837.83 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.116958E+11 | 11837.83 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.109477E+11 | 11837.83 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.121930E+11 | 11837.83 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.108909E+11 | 11837.83 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.113123E+11 | 11837.83 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.111797E+11 | 11837.83 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.109477E+11 | 11837.83 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.135577E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.102611E+11 | 11837.83 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.121930E+11 | 11837.83 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.902224E+09 | 1334.85 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.726608E+09 | 1178.67 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.798627E+09 | 1278.46 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.679595E+09 | 1024.05 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.704020E+09 | 897.05 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.683180E+09 | 706.25 | 26-JUN-11:30 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.654440E+09 | 733.63 | 07-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.733667E+09 | 827.98 | 17-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.697843E+09 | 1042.62 | 11-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.779582E+09 | 1334.85 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.852080E+09 | 1334.85 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.887103E+09 | 1334.85 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.909897E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.654440E+09 | 706.25 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.902224E+09 | 1334.85 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.558792E+09 | 860.23 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.457306E+09 | 727.42 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.507934E+09 | 823.85 | 17-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.435497E+09 | 636.18 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.455295E+09 | 536.51 | 03-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.444785E+09 | 409.30 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.423356E+09 | 462.44 | 07-JUL-07:30 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.475736E+09 | 466.96 | 17-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.446353E+09 | 600.84 | 13-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.488886E+09 | 860.23 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.530913E+09 | 860.23 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.547786E+09 | 860.23 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.577264E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.423356E+09 | 409.30 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.558792E+09 | 860.23 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.848286E+09 | 1334.88 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.692334E+09 | 1057.77 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.785516E+09 | 1278.48 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.679589E+09 | 1022.28 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.708910E+09 | 904.17 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.691544E+09 | 694.08 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.659843E+09 | 735.29 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.739748E+09 | 835.54 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.692444E+09 | 1019.29 | 11-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.748758E+09 | 1334.88 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.797581E+09 | 1334.88 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.821133E+09 | 1334.88 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.886569E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.659843E+09 | 694.08 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.848286E+09 | 1334.88 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.565756E+09 | 860.23 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.457156E+09 | 766.62 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.513098E+09 | 823.85 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.440148E+09 | 672.89 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.455824E+09 | 603.55 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.442228E+09 | 459.30 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.424085E+09 | 478.09 | 07-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.475865E+09 | 577.47 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.449893E+09 | 716.85 | 11-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.496063E+09 | 860.23 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.529420E+09 | 860.23 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.547791E+09 | 860.23 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.579733E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.424085E+09 | 459.30 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.565756E+09 | 860.23 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.902342E+09 | 1334.85 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.726744E+09 | 1182.95 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.798833E+09 | 1279.70 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.679748E+09 | 1030.88 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.704090E+09 | 906.55 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.683274E+09 | 702.55 | 26-JUN-11:30 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.654467E+09 | 731.39 | 07-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.733691E+09 | 839.02 | 17-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.697663E+09 | 1048.91 | 11-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.779995E+09 | 1334.85 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.852390E+09 | 1334.85 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.887986E+09 | 1334.85 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.910122E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.654467E+09 | 702.55 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.902342E+09 | 1334.85 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.559286E+09 | 860.23 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.457148E+09 | 729.57 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.507858E+09 | 823.93 | 17-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.435452E+09 | 637.72 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.455207E+09 | 539.27 | 03-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.444751E+09 | 409.30 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.423294E+09 | 460.74 | 07-JUL-07:30 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.475670E+09 | 465.55 | 17-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.446279E+09 | 603.05 | 13-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.488796E+09 | 860.23 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.530757E+09 | 860.23 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.547833E+09 | 860.23 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.577233E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.423294E+09 | 409.30 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.559286E+09 | 860.23 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.848927E+09 | 1334.88 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.692638E+09 | 1064.95 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.785720E+09 | 1279.73 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.679837E+09 | 1029.15 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.708983E+09 | 913.45 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.691710E+09 | 690.92 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.659872E+09 | 733.07 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.739938E+09 | 846.32 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.692537E+09 | 1026.30 | 11-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.748070E+09 | 1334.88 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.798701E+09 | 1334.88 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.821653E+09 | 1334.88 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.886858E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.659872E+09 | 690.92 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.848927E+09 | 1334.88 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.565602E+09 | 860.23 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.457097E+09 | 767.18 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.512960E+09 | 823.93 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.439990E+09 | 673.30 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.455657E+09 | 604.08 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.442196E+09 | 457.18 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.424000E+09 | 476.55 | 07-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.475720E+09 | 578.05 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.449804E+09 | 717.09 | 11-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.496031E+09 | 860.23 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.529800E+09 | 860.23 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.547573E+09 | 860.23 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.579643E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.424000E+09 | 457.18 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.565602E+09 | 860.23 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.902277E+09 | 1334.85 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.726752E+09 | 1183.07 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.798811E+09 | 1279.63 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.679710E+09 | 1030.53 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.704078E+09 | 906.08 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.683274E+09 | 702.43 | 26-JUN-11:30 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.654460E+09 | 731.23 | 07-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.733684E+09 | 838.52 | 17-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.697639E+09 | 1048.71 | 11-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.779984E+09 | 1334.85 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.852384E+09 | 1334.85 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.887895E+09 | 1334.85 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.910095E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.654460E+09 | 702.43 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.902277E+09 | 1334.85 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.559270E+09 | 860.23 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.457142E+09 | 729.70 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.507841E+09 | 823.88 | 17-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.435444E+09 | 637.52 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.455201E+09 | 538.99 | 03-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.444748E+09 | 409.30 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.423291E+09 | 460.61 | 07-JUL-07:30 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.475667E+09 | 465.44 | 17-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.446274E+09 | 602.87 | 13-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.488785E+09 | 860.23 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.530788E+09 | 860.23 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.547799E+09 | 860.23 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.577225E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.423291E+09 | 409.30 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.559270E+09 | 860.23 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.848916E+09 | 1334.88 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.692634E+09 | 1064.96 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.785687E+09 | 1279.66 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.679820E+09 | 1028.81 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.708986E+09 | 912.98 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.691703E+09 | 690.69 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.659871E+09 | 732.91 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.739932E+09 | 845.82 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.692508E+09 | 1026.09 | 11-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.748056E+09 | 1334.88 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.798706E+09 | 1334.88 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.821656E+09 | 1334.88 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.886847E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.659871E+09 | 690.69 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.848916E+09 | 1334.88 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.565590E+09 | 860.23 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.457083E+09 | 767.15 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.512951E+09 | 823.88 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.439978E+09 | 673.09 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.455651E+09 | 603.79 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.442193E+09 | 457.05 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.423997E+09 | 476.46 | 07-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.475717E+09 | 577.74 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.449785E+09 | 716.96 | 11-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.496032E+09 | 860.23 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.529803E+09 | 860.23 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.547599E+09 | 860.23 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.579638E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.423997E+09 | 457.05 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.565590E+09 | 860.23 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.318958E+10 | 3337.76 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.289319E+10 | 3337.76 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.343791E+10 | 3337.76 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.307076E+10 | 3337.76 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.331375E+10 | 3337.76 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.329773E+10 | 3337.76 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.308678E+10 | 3337.76 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.343791E+10 | 3337.76 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.307076E+10 | 3337.76 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.318958E+10 | 3337.76 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.315220E+10 | 3337.76 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.308678E+10 | 3337.76 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.382269E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.289319E+10 | 3337.76 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.343791E+10 | 3337.76 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.113123E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.102611E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.108909E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.117527E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.116958E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.109477E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.108909E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.113123E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.111797E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.109477E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.135577E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.102611E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.902224E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619340E+09 |
February | 0.136985E+10 | 0.726608E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497793E+09 |
March | 0.163685E+10 | 0.798627E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454729E+09 |
April | 0.145243E+10 | 0.679595E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330787E+09 |
May | 0.157338E+10 | 0.704020E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 718669.82 | 0.324799E+09 |
June | 0.156900E+10 | 0.683180E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3692950.09 | 0.159995E+09 |
July | 0.145680E+10 | 0.654440E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12726990.95 | 0.104190E+09 |
August | 0.163685E+10 | 0.733667E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10827504.93 | 0.115057E+09 |
September | 0.145243E+10 | 0.697843E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6996434.15 | 0.213291E+09 |
October | 0.150991E+10 | 0.779582E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43341.09 | 0.322705E+09 |
November | 0.149516E+10 | 0.852080E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456541E+09 |
December | 0.145680E+10 | 0.887103E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581031E+09 |
Annual Sum or Average | 0.181194E+11 | 0.909897E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35005891.02 | 0.418026E+10 |
Minimum of Months | 0.136985E+10 | 0.654440E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104190E+09 |
Maximum of Months | 0.163685E+10 | 0.902224E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12726990.95 | 0.619340E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.558792E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412447E+09 |
February | 0.882782E+09 | 0.457306E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332382E+09 |
March | 0.105485E+10 | 0.507934E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300598E+09 |
April | 0.936002E+09 | 0.435497E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217463E+09 |
May | 0.101394E+10 | 0.455295E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 504318.16 | 0.214164E+09 |
June | 0.101113E+10 | 0.444785E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2509878.38 | 0.105433E+09 |
July | 0.938820E+09 | 0.423356E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8479155.84 | 67108465.59 |
August | 0.105485E+10 | 0.475736E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7250489.00 | 73115182.26 |
September | 0.936002E+09 | 0.446353E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4486141.80 | 0.142542E+09 |
October | 0.973041E+09 | 0.488886E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28892.12 | 0.214692E+09 |
November | 0.963541E+09 | 0.530913E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298629E+09 |
December | 0.938820E+09 | 0.547786E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379786E+09 |
Annual Sum or Average | 0.116768E+11 | 0.577264E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23258875.29 | 0.275836E+10 |
Minimum of Months | 0.882782E+09 | 0.423356E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67108465.59 |
Maximum of Months | 0.105485E+10 | 0.558792E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8479155.84 | 0.412447E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.848286E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623707E+09 |
February | 0.136988E+10 | 0.692334E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511101E+09 |
March | 0.163688E+10 | 0.785516E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457231E+09 |
April | 0.145246E+10 | 0.679589E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330181E+09 |
May | 0.157341E+10 | 0.708910E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 708710.10 | 0.321129E+09 |
June | 0.156904E+10 | 0.691544E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3663016.26 | 0.159151E+09 |
July | 0.145684E+10 | 0.659843E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11995334.49 | 0.104389E+09 |
August | 0.163688E+10 | 0.739748E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10487844.42 | 0.116389E+09 |
September | 0.145246E+10 | 0.692444E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6009049.01 | 0.218047E+09 |
October | 0.150994E+10 | 0.748758E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39579.71 | 0.330398E+09 |
November | 0.149520E+10 | 0.797581E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457091E+09 |
December | 0.145684E+10 | 0.821133E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581009E+09 |
Annual Sum or Average | 0.181198E+11 | 0.886569E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32903533.99 | 0.420982E+10 |
Minimum of Months | 0.136988E+10 | 0.659843E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104389E+09 |
Maximum of Months | 0.163688E+10 | 0.848286E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11995334.49 | 0.623707E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.565756E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427023E+09 |
February | 0.882782E+09 | 0.457156E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357813E+09 |
March | 0.105485E+10 | 0.513098E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327410E+09 |
April | 0.936002E+09 | 0.440148E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246412E+09 |
May | 0.101394E+10 | 0.455824E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 454376.29 | 0.231294E+09 |
June | 0.101113E+10 | 0.442228E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2375435.64 | 0.117004E+09 |
July | 0.938820E+09 | 0.424085E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7616061.04 | 79916002.12 |
August | 0.105485E+10 | 0.475865E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6824625.06 | 87130718.64 |
September | 0.936002E+09 | 0.449893E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4318679.05 | 0.152262E+09 |
October | 0.973041E+09 | 0.496063E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28891.77 | 0.234598E+09 |
November | 0.963541E+09 | 0.529420E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331538E+09 |
December | 0.938820E+09 | 0.547791E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424712E+09 |
Annual Sum or Average | 0.116768E+11 | 0.579733E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21618068.85 | 0.301711E+10 |
Minimum of Months | 0.882782E+09 | 0.424085E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79916002.12 |
Maximum of Months | 0.105485E+10 | 0.565756E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7616061.04 | 0.427023E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.902342E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132934E+10 |
February | 0.136985E+10 | 0.726744E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102806E+10 |
March | 0.163685E+10 | 0.798833E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.950573E+09 |
April | 0.145243E+10 | 0.679748E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687521E+09 |
May | 0.157338E+10 | 0.704090E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1626274.22 | 0.703583E+09 |
June | 0.156900E+10 | 0.683274E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8653464.15 | 0.359918E+09 |
July | 0.145680E+10 | 0.654467E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30990574.18 | 0.241546E+09 |
August | 0.163685E+10 | 0.733691E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25737675.37 | 0.263475E+09 |
September | 0.145243E+10 | 0.697663E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17037780.38 | 0.462732E+09 |
October | 0.150991E+10 | 0.779995E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 658047.69 | 0.658389E+09 |
November | 0.149516E+10 | 0.852390E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.927294E+09 |
December | 0.145680E+10 | 0.887986E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116959E+10 |
Annual Sum or Average | 0.181194E+11 | 0.910122E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84703816.00 | 0.878202E+10 |
Minimum of Months | 0.136985E+10 | 0.654467E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241546E+09 |
Maximum of Months | 0.163685E+10 | 0.902342E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30990574.18 | 0.132934E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.559286E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895857E+09 |
February | 0.649041E+09 | 0.457148E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704890E+09 |
March | 0.773965E+09 | 0.507858E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650368E+09 |
April | 0.688021E+09 | 0.435452E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477085E+09 |
May | 0.744847E+09 | 0.455207E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1135383.95 | 0.474087E+09 |
June | 0.742030E+09 | 0.444751E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5672312.55 | 0.246217E+09 |
July | 0.690839E+09 | 0.423294E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19119740.77 | 0.167860E+09 |
August | 0.773965E+09 | 0.475670E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16517160.37 | 0.180483E+09 |
September | 0.688021E+09 | 0.446279E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10184041.95 | 0.319209E+09 |
October | 0.715730E+09 | 0.488796E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64047.40 | 0.457287E+09 |
November | 0.708685E+09 | 0.530757E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626092E+09 |
December | 0.690839E+09 | 0.547833E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788746E+09 |
Annual Sum or Average | 0.858171E+10 | 0.577233E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52692687.01 | 0.598818E+10 |
Minimum of Months | 0.649041E+09 | 0.423294E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167860E+09 |
Maximum of Months | 0.773965E+09 | 0.559286E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19119740.77 | 0.895857E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.848927E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140206E+10 |
February | 0.136988E+10 | 0.692638E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113993E+10 |
March | 0.163688E+10 | 0.785720E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102299E+10 |
April | 0.145246E+10 | 0.679837E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739519E+09 |
May | 0.157341E+10 | 0.708983E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1543204.52 | 0.725426E+09 |
June | 0.156904E+10 | 0.691710E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8304626.04 | 0.366789E+09 |
July | 0.145684E+10 | 0.659872E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27587227.38 | 0.251222E+09 |
August | 0.163688E+10 | 0.739938E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24071588.55 | 0.278215E+09 |
September | 0.145246E+10 | 0.692537E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13435251.97 | 0.500261E+09 |
October | 0.150994E+10 | 0.748070E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50086.50 | 0.745654E+09 |
November | 0.149520E+10 | 0.798701E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101033E+10 |
December | 0.145684E+10 | 0.821653E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126034E+10 |
Annual Sum or Average | 0.181198E+11 | 0.886858E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74991984.96 | 0.944272E+10 |
Minimum of Months | 0.136988E+10 | 0.659872E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251222E+09 |
Maximum of Months | 0.163688E+10 | 0.848927E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27587227.38 | 0.140206E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.565602E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.908595E+09 |
February | 0.882782E+09 | 0.457097E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722477E+09 |
March | 0.105485E+10 | 0.512960E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663645E+09 |
April | 0.936002E+09 | 0.439990E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494960E+09 |
May | 0.101394E+10 | 0.455657E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1014548.17 | 0.500248E+09 |
June | 0.101113E+10 | 0.442196E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5457634.31 | 0.255830E+09 |
July | 0.938820E+09 | 0.424000E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18666238.01 | 0.179447E+09 |
August | 0.105485E+10 | 0.475720E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16330525.51 | 0.189180E+09 |
September | 0.936002E+09 | 0.449804E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10345345.93 | 0.326558E+09 |
October | 0.973041E+09 | 0.496031E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85917.79 | 0.467564E+09 |
November | 0.963541E+09 | 0.529800E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644486E+09 |
December | 0.938820E+09 | 0.547573E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.809529E+09 |
Annual Sum or Average | 0.116768E+11 | 0.579643E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51900209.72 | 0.616252E+10 |
Minimum of Months | 0.882782E+09 | 0.424000E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179447E+09 |
Maximum of Months | 0.105485E+10 | 0.565602E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18666238.01 | 0.908595E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.902277E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159214E+10 |
February | 0.136985E+10 | 0.726752E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118627E+10 |
March | 0.163685E+10 | 0.798811E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110719E+10 |
April | 0.145243E+10 | 0.679710E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776789E+09 |
May | 0.157338E+10 | 0.704078E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1950078.02 | 0.817565E+09 |
June | 0.156900E+10 | 0.683274E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10423214.73 | 0.432130E+09 |
July | 0.145680E+10 | 0.654460E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37388874.12 | 0.293862E+09 |
August | 0.163685E+10 | 0.733684E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30880503.57 | 0.315069E+09 |
September | 0.145243E+10 | 0.697639E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20823057.21 | 0.530451E+09 |
October | 0.150991E+10 | 0.779984E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2547277.25 | 0.715277E+09 |
November | 0.149516E+10 | 0.852384E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105192E+10 |
December | 0.145680E+10 | 0.887895E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138593E+10 |
Annual Sum or Average | 0.181194E+11 | 0.910095E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104013E+09 | 0.102046E+11 |
Minimum of Months | 0.136985E+10 | 0.654460E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293862E+09 |
Maximum of Months | 0.163685E+10 | 0.902277E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37388874.12 | 0.159214E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.559270E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107062E+10 |
February | 0.882782E+09 | 0.457142E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812948E+09 |
March | 0.105485E+10 | 0.507841E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.759802E+09 |
April | 0.936002E+09 | 0.435444E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548975E+09 |
May | 0.101394E+10 | 0.455201E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1276456.35 | 0.559046E+09 |
June | 0.101113E+10 | 0.444748E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6682925.01 | 0.301319E+09 |
July | 0.938820E+09 | 0.423291E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22360285.67 | 0.208689E+09 |
August | 0.105485E+10 | 0.475667E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19720326.60 | 0.220721E+09 |
September | 0.936002E+09 | 0.446274E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11809058.27 | 0.375596E+09 |
October | 0.973041E+09 | 0.488785E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 259532.74 | 0.505211E+09 |
November | 0.963541E+09 | 0.530788E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710636E+09 |
December | 0.938820E+09 | 0.547799E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929398E+09 |
Annual Sum or Average | 0.116768E+11 | 0.577225E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62108584.65 | 0.700296E+10 |
Minimum of Months | 0.882782E+09 | 0.423291E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208689E+09 |
Maximum of Months | 0.105485E+10 | 0.559270E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22360285.67 | 0.107062E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.848916E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165053E+10 |
February | 0.136988E+10 | 0.692634E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131324E+10 |
March | 0.163688E+10 | 0.785687E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119313E+10 |
April | 0.145246E+10 | 0.679820E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.849577E+09 |
May | 0.157341E+10 | 0.708986E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1815509.94 | 0.851331E+09 |
June | 0.156904E+10 | 0.691703E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9910011.11 | 0.443769E+09 |
July | 0.145684E+10 | 0.659871E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32906057.15 | 0.308425E+09 |
August | 0.163688E+10 | 0.739932E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29051371.51 | 0.337849E+09 |
September | 0.145246E+10 | 0.692508E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16065492.26 | 0.587486E+09 |
October | 0.150994E+10 | 0.748056E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87428.54 | 0.836532E+09 |
November | 0.149520E+10 | 0.798706E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113721E+10 |
December | 0.145684E+10 | 0.821656E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145249E+10 |
Annual Sum or Average | 0.181198E+11 | 0.886847E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89835870.51 | 0.109616E+11 |
Minimum of Months | 0.136988E+10 | 0.659871E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308425E+09 |
Maximum of Months | 0.163688E+10 | 0.848916E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32906057.15 | 0.165053E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.565590E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108030E+10 |
February | 0.882782E+09 | 0.457083E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841844E+09 |
March | 0.105485E+10 | 0.512951E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781126E+09 |
April | 0.936002E+09 | 0.439978E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573799E+09 |
May | 0.101394E+10 | 0.455651E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1197120.13 | 0.591021E+09 |
June | 0.101113E+10 | 0.442193E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6576160.60 | 0.310593E+09 |
July | 0.938820E+09 | 0.423997E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22523325.18 | 0.220903E+09 |
August | 0.105485E+10 | 0.475717E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19783558.56 | 0.229881E+09 |
September | 0.936002E+09 | 0.449785E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12480863.08 | 0.383491E+09 |
October | 0.973041E+09 | 0.496032E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 328355.73 | 0.526837E+09 |
November | 0.963541E+09 | 0.529803E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739096E+09 |
December | 0.938820E+09 | 0.547599E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.949508E+09 |
Annual Sum or Average | 0.116768E+11 | 0.579638E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62889383.29 | 0.722840E+10 |
Minimum of Months | 0.882782E+09 | 0.423997E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220903E+09 |
Maximum of Months | 0.105485E+10 | 0.565590E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22523325.18 | 0.108030E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.318958E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.289319E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.343791E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.307076E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.331375E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.329773E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.308678E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.343791E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.307076E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.318958E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.315220E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.308678E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.382269E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.289319E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.343791E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131271E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105812E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957768E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693566E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1171309.25 | 0.675046E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6105631.54 | 0.332266E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23534186.85 | 0.220617E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20063773.47 | 0.245618E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13391170.98 | 0.451813E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28815.32 | 0.682551E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969560E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123476E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64294887.42 | 0.883439E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220617E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23534186.85 | 0.131271E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220297E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175005E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161449E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117482E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2245371.11 | 0.116809E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11322117.06 | 0.583573E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44261244.44 | 0.390744E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36958026.32 | 0.434555E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25246012.90 | 0.789178E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75413.73 | 0.115203E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161155E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201227E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120108E+09 | 0.148843E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390744E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44261244.44 | 0.220297E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231159E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179911E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169038E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122657E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1295062.72 | 0.126959E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9045054.31 | 0.665530E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37414413.74 | 0.451635E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34390407.14 | 0.489019E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21764871.95 | 0.839120E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114195E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159276E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203806E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103910E+09 | 0.155153E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451635E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37414413.74 | 0.231159E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 11837.83 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 11837.83 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 11837.83 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 11837.83 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 11837.83 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 11837.83 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 11837.83 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 11837.83 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 11837.83 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 11837.83 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 11837.83 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 11837.83 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 11837.83 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 11837.83 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1334.85 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 984.24 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 1178.67 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 647.48 | 17-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1278.46 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 786.25 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 1024.05 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 561.95 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 897.05 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.84 | 20-MAY-17:03 | 1094.74 | 22-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 706.25 | 26-JUN-11:30 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.08 | 29-JUN-15:00 | 452.16 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 733.63 | 07-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.49 | 30-JUL-11:53 | 268.04 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 827.98 | 17-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.71 | 06-AUG-17:30 | 346.45 | 23-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 1042.62 | 11-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.10 | 03-SEP-13:00 | 604.99 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 1334.85 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 | 18-OCT-14:00 | 515.59 | 30-OCT-22:20 |
November | 2010.79 | 01-NOV-09:09 | 1334.85 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 614.39 | 26-NOV-19:52 |
December | 2010.79 | 01-DEC-10:09 | 1334.85 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 967.87 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 706.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.04 | |||||
Maximum of Months | 2010.79 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 160.10 | 1094.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 860.23 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 655.89 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 727.42 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 424.24 | 17-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 823.85 | 17-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 515.33 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 636.18 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 368.17 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 536.51 | 03-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.90 | 20-MAY-17:03 | 721.71 | 22-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 409.30 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.05 | 29-JUN-15:00 | 294.21 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 462.44 | 07-JUL-07:30 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.74 | 30-JUL-14:10 | 173.07 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 466.96 | 17-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.97 | 06-AUG-17:30 | 223.73 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 600.84 | 13-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.17 | 03-SEP-13:00 | 397.73 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 860.23 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.20 | 18-OCT-14:00 | 338.64 | 30-OCT-22:30 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 406.89 | 26-NOV-19:52 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 624.36 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.07 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 102.17 | 721.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1334.88 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 983.46 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 1057.77 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 636.63 | 17-FEB-04:00 |
March | 2010.83 | 01-MAR-10:09 | 1278.48 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 798.08 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 1022.28 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 556.60 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 904.17 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.82 | 20-MAY-17:03 | 1067.92 | 22-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 694.08 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.08 | 29-JUN-15:00 | 445.06 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 735.29 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.80 | 30-JUL-12:10 | 263.56 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 835.54 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.63 | 06-AUG-17:24 | 346.67 | 23-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 1019.29 | 11-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.50 | 03-SEP-12:55 | 589.87 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 1334.88 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 | 18-OCT-14:30 | 523.18 | 30-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 1334.88 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 605.62 | 26-NOV-19:52 |
December | 2010.83 | 01-DEC-10:09 | 1334.88 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 933.49 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 694.08 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.56 | |||||
Maximum of Months | 2010.83 | 1334.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 140.50 | 1067.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 860.23 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 657.31 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 766.62 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 463.33 | 17-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 823.85 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 562.97 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 672.89 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 411.63 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 603.55 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.36 | 20-MAY-17:03 | 745.97 | 22-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 459.30 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.05 | 29-JUN-15:00 | 329.14 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 478.09 | 07-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.33 | 30-JUL-12:10 | 201.46 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 577.47 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.51 | 06-AUG-17:24 | 269.66 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 716.85 | 11-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.55 | 03-SEP-12:52 | 418.82 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 860.23 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.20 | 18-OCT-14:00 | 369.66 | 30-OCT-22:50 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 435.70 | 26-NOV-19:52 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 711.37 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 459.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.46 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 105.55 | 745.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1334.85 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2303.52 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 1182.95 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1307.90 | 17-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1279.70 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1700.74 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 1030.88 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1210.57 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 906.55 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.41 | 20-MAY-17:03 | 2339.34 | 22-MAY-03:55 |
June | 2010.79 | 01-JUN-09:09 | 702.55 | 26-JUN-11:30 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.20 | 29-JUN-15:00 | 985.30 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 731.39 | 07-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 274.92 | 30-JUL-11:55 | 578.36 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 839.02 | 17-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.84 | 06-AUG-18:00 | 727.43 | 23-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 1048.91 | 11-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 382.56 | 03-SEP-13:00 | 1295.00 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 1334.85 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.54 | 15-OCT-14:10 | 1074.81 | 30-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 1334.85 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1411.60 | 28-NOV-05:44 |
December | 2010.79 | 01-DEC-10:09 | 1334.85 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2017.30 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 702.55 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 578.36 | |||||
Maximum of Months | 2010.79 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 382.56 | 2339.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 860.23 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1535.65 | 05-JAN-22:01 |
February | 1239.33 | 01-FEB-08:09 | 729.57 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 873.61 | 17-FEB-04:00 |
March | 1239.33 | 01-MAR-08:09 | 823.93 | 17-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1132.57 | 02-MAR-23:00 |
April | 1239.33 | 03-APR-07:10 | 637.72 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 813.74 | 27-APR-02:00 |
May | 1239.33 | 01-MAY-07:10 | 539.27 | 03-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.50 | 20-MAY-17:03 | 1555.97 | 22-MAY-03:55 |
June | 1239.33 | 01-JUN-07:10 | 409.30 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.80 | 29-JUN-15:00 | 649.15 | 14-JUN-02:00 |
July | 1239.33 | 03-JUL-07:10 | 460.74 | 07-JUL-07:30 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.98 | 30-JUL-11:53 | 386.72 | 05-JUL-01:00 |
August | 1239.33 | 01-AUG-07:10 | 465.55 | 17-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.10 | 06-AUG-17:40 | 488.53 | 23-AUG-03:00 |
September | 1239.33 | 01-SEP-07:10 | 603.05 | 13-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.81 | 03-SEP-12:52 | 853.48 | 12-SEP-03:00 |
October | 1239.33 | 02-OCT-07:10 | 860.23 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 | 18-OCT-14:00 | 719.83 | 30-OCT-22:00 |
November | 1239.33 | 01-NOV-07:10 | 860.23 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 941.08 | 28-NOV-05:50 |
December | 1239.33 | 01-DEC-08:09 | 860.23 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1352.16 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 386.72 | |||||
Maximum of Months | 1239.33 | 860.23 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 232.81 | 1555.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1334.88 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2304.63 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 1064.95 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1416.74 | 19-FEB-12:50 |
March | 2010.83 | 01-MAR-10:09 | 1279.73 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1795.61 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 1029.15 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1231.06 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 913.45 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.24 | 20-MAY-17:03 | 2352.13 | 22-MAY-03:55 |
June | 2010.83 | 01-JUN-09:09 | 690.92 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.20 | 29-JUN-15:00 | 982.31 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 733.07 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.20 | 30-JUL-11:53 | 586.43 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 846.32 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.27 | 06-AUG-17:36 | 751.34 | 23-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 1026.30 | 11-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.06 | 03-SEP-12:58 | 1296.89 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 1334.88 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.51 | 18-OCT-15:10 | 1166.65 | 08-OCT-15:00 |
November | 2010.83 | 01-NOV-09:09 | 1334.88 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1411.62 | 28-NOV-05:47 |
December | 2010.83 | 01-DEC-10:09 | 1334.88 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2017.31 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 690.92 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586.43 | |||||
Maximum of Months | 2010.83 | 1334.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 324.06 | 2352.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 860.23 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1536.19 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 767.18 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 903.48 | 17-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 823.93 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1182.84 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 673.30 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 829.77 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 604.08 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.46 | 20-MAY-17:03 | 1565.84 | 22-MAY-03:55 |
June | 1295.83 | 01-JUN-09:09 | 457.18 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.80 | 29-JUN-15:00 | 674.38 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 476.55 | 07-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.97 | 30-JUL-11:53 | 416.11 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 578.05 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.83 | 06-AUG-11:52 | 508.48 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 717.09 | 11-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.81 | 03-SEP-12:53 | 858.88 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 860.23 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.02 | 18-OCT-12:50 | 745.50 | 30-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 941.08 | 28-NOV-05:43 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1349.65 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 457.18 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.11 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 258.81 | 1565.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1334.85 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2854.95 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 1183.07 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1607.46 | 17-FEB-05:47 |
March | 2010.79 | 01-MAR-10:09 | 1279.63 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2001.03 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 1030.53 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1393.78 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 906.08 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.80 | 20-MAY-17:03 | 2845.06 | 22-MAY-04:05 |
June | 2010.79 | 01-JUN-09:09 | 702.43 | 26-JUN-11:30 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.77 | 29-JUN-15:00 | 1155.18 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 731.23 | 07-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 334.57 | 30-JUL-12:00 | 670.02 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 838.52 | 17-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 377.79 | 06-AUG-17:40 | 839.30 | 23-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 1048.71 | 11-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 471.47 | 03-SEP-13:00 | 1435.23 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 1334.85 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.84 | 15-OCT-13:53 | 1209.96 | 30-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 1334.85 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1760.25 | 28-NOV-05:50 |
December | 2010.79 | 01-DEC-10:09 | 1334.85 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2519.09 | 01-DEC-05:09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 702.43 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 670.02 | |||||
Maximum of Months | 2010.79 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 471.47 | 2854.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 860.23 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1903.27 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 729.70 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1071.69 | 17-FEB-05:47 |
March | 1295.83 | 01-MAR-10:09 | 823.88 | 17-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1339.55 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 637.52 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 946.84 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 538.99 | 03-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.34 | 20-MAY-17:03 | 1894.37 | 22-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 409.30 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.51 | 29-JUN-15:00 | 763.59 | 04-JUN-14:00 |
July | 1295.83 | 03-JUL-09:09 | 460.61 | 07-JUL-07:30 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.21 | 30-JUL-12:00 | 450.55 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 465.44 | 17-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.44 | 06-AUG-17:38 | 567.71 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 602.87 | 13-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.60 | 03-SEP-12:57 | 950.66 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 860.23 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.36 | 15-OCT-13:50 | 819.60 | 30-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1179.49 | 28-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1679.45 | 01-DEC-05:06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.55 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 300.60 | 1903.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1334.88 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2856.71 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 1064.96 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1607.51 | 17-FEB-05:50 |
March | 2010.83 | 01-MAR-10:09 | 1279.66 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2117.23 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 1028.81 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1430.76 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 912.98 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.24 | 20-MAY-17:03 | 2841.50 | 22-MAY-04:53 |
June | 2010.83 | 01-JUN-09:09 | 690.69 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.77 | 29-JUN-15:00 | 1151.57 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 732.91 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.39 | 30-JUL-11:58 | 682.45 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 845.82 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 372.08 | 06-AUG-17:36 | 876.32 | 22-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 1026.09 | 11-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 395.58 | 03-SEP-13:00 | 1439.93 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 1334.88 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.85 | 18-OCT-14:30 | 1332.98 | 30-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 1334.88 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1769.20 | 28-NOV-05:58 |
December | 2010.83 | 01-DEC-10:09 | 1334.88 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2519.10 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 690.69 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 682.45 | |||||
Maximum of Months | 2010.83 | 1334.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 395.58 | 2856.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 860.23 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1904.03 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 767.15 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1071.69 | 17-FEB-05:47 |
March | 1295.83 | 01-MAR-10:09 | 823.88 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1401.94 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 673.09 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 965.94 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 603.79 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.66 | 20-MAY-17:03 | 1918.20 | 22-MAY-04:03 |
June | 1295.83 | 01-JUN-09:09 | 457.05 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.51 | 29-JUN-15:00 | 795.44 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 476.46 | 07-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.05 | 30-JUL-12:00 | 490.66 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 577.74 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.00 | 06-AUG-11:52 | 593.51 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 716.96 | 11-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.46 | 03-SEP-13:00 | 963.01 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 860.23 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.75 | 15-OCT-12:31 | 853.80 | 30-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1179.49 | 28-NOV-05:58 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1679.47 | 01-DEC-05:09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 457.05 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.66 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 321.46 | 1918.20 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 3337.76 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 3337.76 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 3337.76 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 3337.76 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 3337.76 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 3337.76 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 3337.76 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 3337.76 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 3337.76 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 3337.76 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 3337.76 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 3337.76 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 3337.76 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2069.89 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1395.52 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1656.25 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1178.92 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.08 | 20-MAY-17:03 | 2365.36 | 22-MAY-04:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.24 | 29-JUN-15:00 | 938.77 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.25 | 30-JUL-11:53 | 547.09 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.04 | 06-AUG-17:51 | 717.84 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.21 | 03-SEP-13:00 | 1288.46 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 | 18-OCT-15:00 | 1088.92 | 30-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1324.66 | 26-NOV-19:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2079.36 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.09 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.21 | 2365.36 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3634.65 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2344.08 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2890.78 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2061.69 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.31 | 20-MAY-17:03 | 4162.82 | 22-MAY-04:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.02 | 29-JUN-15:00 | 1646.59 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.54 | 30-JUL-12:00 | 956.00 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.43 | 06-AUG-18:00 | 1244.13 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.92 | 03-SEP-13:00 | 2264.01 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 | 18-OCT-14:00 | 1858.20 | 30-OCT-22:30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2224.67 | 26-NOV-19:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3367.55 | 01-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 956.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.92 | 4162.82 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4041.40 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2264.91 | 17-FEB-04:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3119.82 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2173.74 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.40 | 20-MAY-17:03 | 4262.49 | 22-MAY-04:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.44 | 29-JUN-15:00 | 1734.75 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 396.09 | 30-JUL-14:00 | 1018.31 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.72 | 06-AUG-18:00 | 1289.03 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.98 | 03-SEP-13:00 | 2261.40 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1895.17 | 30-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2310.70 | 28-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3356.98 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1018.31 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.98 | 4262.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 96920.44 | 02-JAN-04:11 | 0.00 | 5919.49 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 96327.88 | 21-FEB-04:01 | 0.00 | 5919.49 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 95428.53 | 20-MAR-03:11 | 0.00 | 5261.77 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 93912.38 | 10-APR-03:02 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 93518.67 | 15-MAY-03:02 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 95674.68 | 05-JUN-03:02 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 94048.98 | 24-JUL-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 99112.07 | 21-AUG-03:02 | 0.00 | 3946.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 96426.34 | 04-SEP-16:51 | 8078.51 | 5919.49 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 98322.70 | 10-OCT-03:01 | 0.00 | 4604.05 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98798.36 | 06-NOV-04:02 | 0.00 | 3946.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 94789.38 | 26-DEC-04:01 | 0.00 | 4604.05 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 93518.67 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 99112.07 | 8078.51 | 5919.49 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 77558.40 | 02-JAN-05:01 | 0.00 | 9449.70 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 75913.50 | 21-FEB-06:01 | 12897.91 | 9449.70 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 77071.22 | 30-MAR-05:02 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79098.16 | 10-APR-03:02 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80103.45 | 30-MAY-03:02 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 78652.49 | 05-JUN-03:02 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81364.82 | 05-JUL-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 78345.52 | 02-AUG-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81074.78 | 11-SEP-03:02 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 78532.48 | 10-OCT-03:01 | 0.00 | 4134.76 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 80098.00 | 06-NOV-04:02 | 0.00 | 3544.08 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 77398.34 | 11-DEC-05:01 | 0.00 | 8268.49 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 75913.50 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81364.82 | 12897.91 | 9449.70 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16071.04 | 04-JAN-17:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25243.52 | 28-FEB-17:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 47936.49 | 30-MAR-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 67845.68 | 26-APR-05:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69934.46 | 30-MAY-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 72833.30 | 21-JUN-05:04 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 70913.13 | 21-JUL-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 70310.39 | 21-AUG-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 71039.68 | 06-SEP-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 69032.58 | 20-OCT-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 46618.20 | 08-NOV-06:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19541.82 | 07-DEC-17:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 16071.04 | 0.00 | 4724.85 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72833.30 | 15316.26 | 10631.20 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14996.38 | 13-JAN-17:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17164.33 | 28-FEB-17:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18424.25 | 23-MAR-16:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33804.71 | 25-APR-16:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67417.24 | 30-MAY-05:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 72335.74 | 21-JUN-05:04 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 70113.88 | 19-JUL-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 68201.97 | 29-AUG-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 68724.87 | 08-SEP-05:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30104.62 | 18-OCT-16:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17327.12 | 03-NOV-16:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16033.25 | 06-DEC-16:50 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14996.38 | 0.00 | 4724.85 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72335.74 | 15316.26 | 10631.20 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2418.17 | 02-JAN-06:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.95 |
February | 3407.97 | 27-FEB-16:00 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.49 |
March | 3812.21 | 27-MAR-14:40 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.56 |
April | 6014.96 | 07-APR-14:30 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 |
May | 11018.80 | 30-MAY-05:03 | 809.73 | 563.20 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.02 |
June | 11262.50 | 23-JUN-05:03 | 809.73 | 282.27 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.80 |
July | 13062.29 | 16-JUL-18:51 | 0.00 | 247.02 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 41.57 | 0.00 |
August | 13902.00 | 06-AUG-16:01 | 910.95 | 317.59 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 110.64 | 0.00 |
September | 11066.61 | 05-SEP-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.44 |
October | 5006.29 | 19-OCT-14:30 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 |
November | 3537.99 | 24-NOV-14:30 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.74 |
December | 2555.11 | 06-DEC-06:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2418.17 | 0.00 | 247.02 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13902.00 | 2010.79 | 741.56 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 110.64 | 81.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2429.76 | 02-JAN-05:01 | 0.00 | 764.63 | 3843.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.56 |
February | 6019.08 | 27-FEB-09:55 | 2478.65 | 818.60 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.23 |
March | 8400.38 | 28-MAR-09:15 | 2591.66 | 818.60 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.24 |
April | 16944.29 | 16-APR-08:32 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.46 |
May | 10727.02 | 19-MAY-08:30 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.09 |
June | 19718.92 | 25-JUN-07:52 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.58 |
July | 19116.15 | 23-JUL-09:02 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.89 |
August | 19863.02 | 06-AUG-07:22 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 |
September | 18696.73 | 03-SEP-09:12 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.87 |
October | 8077.33 | 18-OCT-09:20 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 |
November | 5488.77 | 06-NOV-09:35 | 2478.65 | 818.60 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.88 |
December | 2366.05 | 06-DEC-06:02 | 652.28 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2366.05 | 0.00 | 90.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.87 | |
Maximum of Months | 19863.02 | 2591.66 | 818.60 | 3843.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12467.95 | 15-JAN-13:53 | 303.66 | 105.87 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.82 |
February | 23524.27 | 26-FEB-13:52 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.40 |
March | 17088.53 | 01-MAR-13:40 | 1923.15 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.18 |
April | 23215.29 | 16-APR-13:13 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.29 |
May | 14041.20 | 14-MAY-12:13 | 303.66 | 105.87 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.88 |
June | 18264.93 | 25-JUN-13:13 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.51 |
July | 23178.12 | 16-JUL-11:32 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 | 0.00 |
August | 24937.74 | 06-AUG-14:01 | 708.53 | 247.02 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 72.22 | 0.00 |
September | 25161.06 | 03-SEP-13:11 | 910.97 | 317.60 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 99.12 | 0.00 |
October | 26011.58 | 15-OCT-12:31 | 708.53 | 247.02 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.88 |
November | 17028.35 | 03-NOV-13:20 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.01 |
December | 11924.61 | 12-DEC-12:30 | 1058.33 | 635.14 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11924.61 | 303.66 | 105.87 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26011.58 | 2010.83 | 635.14 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 99.12 | 299.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3774.67 | 13-JAN-15:40 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.03 |
February | 11581.39 | 26-FEB-16:33 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.50 |
March | 11764.88 | 28-MAR-16:00 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.45 |
April | 24391.80 | 16-APR-16:32 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.50 |
May | 23776.13 | 28-MAY-17:12 | 0.00 | 136.45 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.86 |
June | 24022.82 | 18-JUN-17:32 | 0.00 | 136.45 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.41 |
July | 25676.78 | 16-JUL-16:51 | 456.59 | 159.19 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 21.07 | 0.00 |
August | 25394.43 | 06-AUG-16:41 | 587.05 | 204.67 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.37 | 0.00 |
September | 24068.85 | 04-SEP-16:22 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 24.44 | 0.00 |
October | 22250.42 | 15-OCT-15:11 | 456.59 | 159.19 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 |
November | 12023.08 | 08-NOV-06:02 | 652.28 | 477.89 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 |
December | 10973.82 | 06-DEC-06:02 | 652.28 | 477.89 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3774.67 | 0.00 | 90.96 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25676.78 | 1239.33 | 477.89 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.37 | 104.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1319.53 | 14-JAN-16:03 | 607.30 | 495.04 | 2520.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.05 |
February | 2324.69 | 27-FEB-13:30 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.05 |
March | 2306.79 | 23-MAR-13:30 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.09 |
April | 4195.46 | 07-APR-14:30 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.12 |
May | 6037.99 | 19-MAY-16:00 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 71.54 | 0.00 |
June | 9944.63 | 23-JUN-05:03 | 809.73 | 282.27 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.47 |
July | 9977.07 | 19-JUL-05:03 | 809.73 | 569.24 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.74 |
August | 9052.30 | 11-AUG-05:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.20 |
September | 9569.92 | 05-SEP-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.70 |
October | 3554.96 | 19-OCT-14:40 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.59 |
November | 2259.61 | 03-NOV-13:30 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.46 |
December | 1550.31 | 06-DEC-16:00 | 1923.11 | 1051.14 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1319.53 | 607.30 | 282.27 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9977.07 | 2010.79 | 1051.14 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 71.54 | 234.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1628.03 | 17-JAN-10:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.19 |
February | 3491.19 | 28-FEB-09:55 | 2478.65 | 818.60 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.88 |
March | 6405.96 | 23-MAR-10:10 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.63 |
April | 9622.96 | 25-APR-09:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.46 |
May | 11145.17 | 19-MAY-08:50 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.75 |
June | 21086.39 | 25-JUN-09:22 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.53 |
July | 21990.36 | 02-JUL-07:51 | 456.59 | 159.19 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.87 |
August | 20736.74 | 06-AUG-09:32 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 21.05 | 0.00 |
September | 19860.81 | 03-SEP-11:21 | 456.59 | 159.19 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 47.68 | 0.00 |
October | 6606.01 | 18-OCT-10:10 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.33 |
November | 3135.70 | 03-NOV-10:10 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.58 |
December | 1748.72 | 20-DEC-10:00 | 2478.65 | 818.60 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1628.03 | 391.37 | 136.45 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21990.36 | 2478.65 | 818.60 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 47.68 | 221.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11227.89 | 15-JAN-13:43 | 303.66 | 105.87 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 704.21 |
February | 25487.35 | 26-FEB-13:02 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.93 |
March | 22898.59 | 26-MAR-13:32 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729.80 |
April | 23144.97 | 16-APR-13:43 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.93 |
May | 18631.00 | 14-MAY-14:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677.14 |
June | 18127.65 | 25-JUN-14:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.86 |
July | 23519.75 | 02-JUL-13:52 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.46 |
August | 23725.48 | 06-AUG-13:32 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 200.92 | 0.00 |
September | 27252.23 | 03-SEP-13:21 | 910.97 | 317.60 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 149.61 | 0.00 |
October | 24673.68 | 15-OCT-14:02 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.88 |
November | 23173.26 | 12-NOV-13:32 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.65 |
December | 9953.59 | 12-DEC-14:30 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9953.59 | 303.66 | 105.87 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27252.23 | 2010.83 | 635.14 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 200.92 | 729.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2221.29 | 13-JAN-15:50 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.75 |
February | 6212.77 | 28-FEB-16:40 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.71 |
March | 7893.35 | 28-MAR-17:00 | 391.37 | 227.39 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.58 |
April | 21233.28 | 16-APR-17:01 | 0.00 | 204.67 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.16 |
May | 23584.66 | 28-MAY-17:41 | 0.00 | 181.93 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.45 |
June | 22722.07 | 18-JUN-18:01 | 0.00 | 159.19 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.70 |
July | 24620.10 | 02-JUL-17:51 | 0.00 | 227.41 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.01 |
August | 21734.96 | 06-AUG-16:12 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 153.93 | 0.00 |
September | 21844.56 | 04-SEP-16:22 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 54.05 | 0.00 |
October | 9471.86 | 15-OCT-16:42 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.06 |
November | 4786.33 | 03-NOV-15:50 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.90 |
December | 2466.17 | 06-DEC-15:50 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2221.29 | 0.00 | 90.96 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24620.10 | 1239.33 | 409.30 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 153.93 | 323.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1647.73 | 13-JAN-06:06 | 1417.03 | 1038.19 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.67 |
February | 1935.58 | 27-FEB-16:20 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.96 |
March | 2103.38 | 29-MAR-16:00 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.92 |
April | 3710.14 | 07-APR-14:40 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.16 |
May | 6684.12 | 19-MAY-16:00 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 86.19 | 0.00 |
June | 12886.04 | 21-JUN-05:02 | 1012.16 | 352.84 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.79 |
July | 16549.72 | 16-JUL-18:31 | 0.00 | 247.02 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 107.23 | 0.00 |
August | 9577.59 | 06-AUG-16:12 | 607.30 | 211.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.04 | 0.00 |
September | 8858.68 | 05-SEP-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.58 |
October | 3123.34 | 18-OCT-14:00 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 0.00 |
November | 1934.56 | 17-NOV-17:00 | 1923.11 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.78 |
December | 1565.46 | 06-DEC-16:00 | 1923.11 | 1051.38 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1565.46 | 0.00 | 211.73 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16549.72 | 2010.79 | 1334.85 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 319.04 | 277.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1583.57 | 13-JAN-06:04 | 913.19 | 669.05 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.32 |
February | 2173.93 | 26-FEB-14:51 | 456.59 | 159.19 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.52 |
March | 4670.27 | 23-MAR-10:30 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.08 |
April | 8556.23 | 25-APR-09:40 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.88 |
May | 10616.61 | 19-MAY-09:20 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.60 |
June | 19840.57 | 11-JUN-09:42 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.81 |
July | 21839.77 | 02-JUL-07:51 | 456.59 | 159.19 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.46 |
August | 20850.67 | 06-AUG-09:32 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 23.24 | 0.00 |
September | 15897.80 | 04-SEP-09:02 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 |
October | 5314.39 | 18-OCT-10:00 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.38 |
November | 2091.36 | 03-NOV-10:10 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.59 |
December | 1622.53 | 19-DEC-06:04 | 913.19 | 669.05 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1583.57 | 326.14 | 113.70 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21839.77 | 1295.83 | 669.05 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 23.24 | 270.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7865.02 | 31-JAN-13:40 | 1923.15 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.56 |
February | 25205.76 | 26-FEB-14:11 | 708.53 | 247.02 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.82 |
March | 15941.66 | 01-MAR-14:10 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.54 |
April | 17155.95 | 16-APR-14:13 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.33 |
May | 16901.06 | 14-MAY-13:53 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 826.79 |
June | 14571.78 | 30-JUN-13:40 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 19.16 | 0.00 |
July | 25629.45 | 02-JUL-13:52 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.16 |
August | 25858.90 | 06-AUG-13:32 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 241.95 | 0.00 |
September | 27260.18 | 03-SEP-13:32 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 238.82 | 0.00 |
October | 27420.36 | 15-OCT-14:22 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.52 |
November | 15345.92 | 03-NOV-13:30 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.39 |
December | 7612.83 | 06-DEC-14:40 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7612.83 | 404.87 | 141.16 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27420.36 | 2010.83 | 635.14 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 241.95 | 826.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2230.16 | 13-JAN-15:50 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.22 |
February | 5358.24 | 28-FEB-16:40 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.48 |
March | 7309.48 | 28-MAR-17:00 | 391.37 | 227.39 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.46 |
April | 17134.28 | 16-APR-17:32 | 0.00 | 136.45 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.48 |
May | 25155.20 | 28-MAY-17:41 | 0.00 | 181.93 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.87 |
June | 24271.47 | 18-JUN-18:01 | 0.00 | 159.19 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.38 |
July | 26295.81 | 02-JUL-17:51 | 0.00 | 227.41 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.08 |
August | 23363.13 | 06-AUG-16:12 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 184.41 | 0.00 |
September | 23400.97 | 04-SEP-16:22 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 64.47 | 0.00 |
October | 8817.31 | 18-OCT-16:00 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1.71 | 0.00 |
November | 3779.42 | 03-NOV-15:50 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.94 |
December | 2457.31 | 06-DEC-15:50 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2230.16 | 0.00 | 136.45 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26295.81 | 1239.33 | 409.30 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 184.41 | 404.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6763.44 | 06-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1044.46 |
February | 3306.61 | 09-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.08 |
March | 4110.25 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.66 |
April | 4710.53 | 25-APR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.66 |
May | 8407.49 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.69 |
June | 6882.95 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.06 |
July | 10390.56 | 17-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 |
August | 9813.80 | 07-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.59 |
September | 9994.60 | 05-SEP-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.73 |
October | 4788.83 | 20-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.88 |
November | 4643.21 | 06-NOV-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.14 |
December | 3443.02 | 07-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3306.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 | |
Maximum of Months | 10390.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1044.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8423.43 | 06-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2571.21 |
February | 7724.18 | 04-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1169.83 |
March | 7907.73 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.11 |
April | 5092.20 | 15-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.18 |
May | 5274.66 | 08-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1719.54 |
June | 5676.48 | 23-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.79 |
July | 6642.22 | 17-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 0.00 |
August | 6546.47 | 10-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.29 | 0.00 |
September | 6350.59 | 05-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.63 |
October | 3913.99 | 11-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.56 |
November | 7941.31 | 27-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2039.99 |
December | 7416.82 | 28-DEC-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1452.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3913.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8423.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.29 | 2571.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.94 |
February | 2556.79 | 26-FEB-15:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.34 |
March | 2865.79 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.95 |
April | 9045.82 | 25-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.02 |
May | 14500.42 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.87 | 0.00 |
June | 17417.27 | 23-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.33 | 0.00 |
July | 20956.76 | 17-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.55 | 0.00 |
August | 18390.35 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.66 | 0.00 |
September | 13204.98 | 01-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.00 | 0.00 |
October | 6745.85 | 18-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.07 |
November | 1774.96 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.37 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2059.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20956.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.87 | 2059.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1834.61 | 19-JAN-16:50 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4208.55 | 26-FEB-17:27 | 35.07 | 47.50 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6820.24 | 31-MAR-24:00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8166.50 | 22-APR-18:10 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3473.41 | 31-MAY-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5362.06 | 30-JUN-24:00 | 0.00 | 47.50 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7237.68 | 31-JUL-23:40 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8146.15 | 05-AUG-19:42 | 0.00 | 79.16 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3315.40 | 30-SEP-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4977.59 | 31-OCT-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5916.85 | 13-NOV-16:20 | 222.14 | 284.97 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7694.20 | 06-DEC-16:10 | 222.14 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1834.61 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8166.50 | 222.14 | 284.97 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1367.93 | 19-JAN-16:50 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3778.95 | 28-FEB-17:00 | 222.14 | 284.97 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5825.80 | 31-MAR-23:40 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7650.19 | 25-APR-18:10 | 23.38 | 94.99 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3275.65 | 31-MAY-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5225.70 | 30-JUN-24:00 | 0.00 | 47.50 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7010.97 | 31-JUL-23:53 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7762.66 | 05-AUG-19:42 | 0.00 | 79.16 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2910.97 | 30-SEP-23:50 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4147.12 | 31-OCT-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5411.18 | 03-NOV-16:00 | 222.14 | 284.97 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6976.31 | 06-DEC-16:20 | 222.14 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1367.93 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7762.66 | 222.14 | 284.97 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1106.10 | 13-JAN-16:30 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3637.71 | 28-FEB-17:00 | 222.14 | 284.97 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5621.28 | 28-MAR-17:50 | 23.38 | 94.99 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7704.76 | 25-APR-18:10 | 23.38 | 94.99 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3196.31 | 31-MAY-23:50 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5190.09 | 30-JUN-24:00 | 0.00 | 47.50 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7008.07 | 31-JUL-23:53 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7932.72 | 05-AUG-19:42 | 0.00 | 79.16 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2669.82 | 04-SEP-17:32 | 0.00 | 126.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3878.60 | 18-OCT-17:00 | 70.15 | 158.31 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5248.32 | 03-NOV-16:00 | 222.14 | 284.97 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6824.60 | 06-DEC-16:20 | 222.14 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1106.10 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7932.72 | 222.14 | 284.97 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 90731.48 | 02-JAN-17:00 | 4808.68 | 3337.76 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182427.28 | 27-FEB-17:00 | 4808.68 | 3337.76 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357279.86 | 31-MAR-24:00 | 0.00 | 185.45 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366089.42 | 25-APR-16:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175643.84 | 31-MAY-24:00 | 0.00 | 185.45 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267540.23 | 30-JUN-23:53 | 0.00 | 556.35 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359858.06 | 31-JUL-23:53 | 0.00 | 556.35 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 367701.48 | 07-AUG-16:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175594.96 | 30-SEP-24:00 | 0.00 | 185.45 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267264.64 | 31-OCT-24:00 | 0.00 | 185.45 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275333.80 | 06-NOV-16:55 | 9617.36 | 6675.52 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366415.84 | 06-DEC-17:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 90731.48 | 0.00 | 185.45 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 367701.48 | 9617.36 | 6675.52 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.126951E+13 | 844272.72 | 09-JAN-08:09 | 0.115264E+13 | 2328249.77 | 09-JAN-07:19 |
February | 0.148201E+13 | 978088.58 | 27-FEB-16:10 | 0.656938E+12 | 1564993.70 | 01-FEB-07:10 |
March | 0.204268E+13 | 1092918.02 | 16-MAR-15:39 | 0.442273E+12 | 1606577.55 | 06-MAR-07:10 |
April | 0.232313E+13 | 1351693.03 | 06-APR-15:20 | 0.173996E+12 | 618020.56 | 29-APR-06:10 |
May | 0.133041E+13 | 1073392.70 | 19-MAY-15:30 | 0.133256E+12 | 602177.84 | 08-MAY-06:40 |
June | 0.178392E+13 | 1268438.35 | 30-JUN-15:39 | 0.650410E+11 | 217997.77 | 16-JUN-06:00 |
July | 0.227206E+13 | 1501534.03 | 17-JUL-15:20 | 0.588052E+11 | 78924.83 | 03-JUL-11:30 |
August | 0.265843E+13 | 1598375.19 | 08-AUG-15:39 | 0.619149E+11 | 77619.77 | 18-AUG-05:10 |
September | 0.133932E+13 | 1189494.76 | 07-SEP-14:00 | 0.740750E+11 | 343002.70 | 19-SEP-06:10 |
October | 0.167767E+13 | 1136530.18 | 18-OCT-15:50 | 0.140529E+12 | 703943.71 | 10-OCT-06:19 |
November | 0.196911E+13 | 1155209.37 | 17-NOV-16:00 | 0.357165E+12 | 1324339.06 | 27-NOV-07:19 |
December | 0.237788E+13 | 1254894.98 | 29-DEC-08:09 | 0.780270E+12 | 1728196.65 | 29-DEC-07:00 |
Annual Sum or Average | 0.225261E+14 | 0.409691E+13 | ||||
Minimum of Months | 0.126951E+13 | 844272.72 | 0.588052E+11 | 77619.77 | ||
Maximum of Months | 0.265843E+13 | 1598375.19 | 0.115264E+13 | 2328249.77 |
Report: EnergyConsumptionDistrictHeatingCoolingMonthly
For: Meter
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportDISTRICTCOOLING:FACILITY [J] | DISTRICTCOOLING:FACILITY {Maximum} [W] | DISTRICTCOOLING:FACILITY {TIMESTAMP} | DISTRICTHEATING:FACILITY [J] | DISTRICTHEATING:FACILITY {Maximum} [W] | DISTRICTHEATING:FACILITY {TIMESTAMP} | |
January | 0.234646E+12 | 93349.39 | 02-JAN-14:00 | 114482.70 | 9.13 | 22-JAN-18:40 |
February | 0.433777E+12 | 185026.32 | 27-FEB-16:00 | 166553.01 | 14.26 | 01-FEB-00:30 |
March | 0.728016E+12 | 357280.57 | 31-MAR-23:00 | 206055.04 | 11.76 | 01-MAR-00:30 |
April | 0.942285E+12 | 368688.47 | 25-APR-15:00 | 138061.87 | 8.46 | 21-APR-23:30 |
May | 0.240941E+12 | 175647.15 | 31-MAY-23:00 | 142683.36 | 12.28 | 31-MAY-23:40 |
June | 0.470788E+12 | 267540.54 | 30-JUN-23:00 | 105446.76 | 6.16 | 01-JUN-23:40 |
July | 0.733127E+12 | 359858.06 | 31-JUL-23:00 | 26063.35 | 8.04 | 03-JUL-23:30 |
August | 0.978813E+12 | 370300.48 | 07-AUG-15:00 | 36548.63 | 8.46 | 01-AUG-23:30 |
September | 0.235935E+12 | 175594.96 | 30-SEP-23:00 | 126967.39 | 6.28 | 23-SEP-18:40 |
October | 0.487371E+12 | 267266.11 | 31-OCT-23:00 | 206079.99 | 11.79 | 31-OCT-23:30 |
November | 0.707612E+12 | 277938.32 | 06-NOV-14:00 | 192373.34 | 8.07 | 25-NOV-00:30 |
December | 0.974201E+12 | 369014.74 | 06-DEC-16:00 | 171474.45 | 11.14 | 01-DEC-00:30 |
Annual Sum or Average | 0.716751E+13 | 1632789.87 | ||||
Minimum of Months | 0.234646E+12 | 93349.39 | 26063.35 | 6.16 | ||
Maximum of Months | 0.978813E+12 | 370300.48 | 206079.99 | 14.26 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.174193E+12 | 0.406334E+11 | 0.766053E+12 | 0.205321E+12 | 0.767215E+11 | 0.399832E+10 | 0.00 | 0.229525E+10 | 0.298524E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154704E+12 | 0.317693E+11 | 0.978954E+12 | 0.224489E+12 | 0.681240E+11 | 0.544335E+10 | 0.00 | 0.161835E+11 | 0.233917E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181820E+12 | 0.287146E+11 | 0.141687E+13 | 0.291975E+12 | 0.803459E+11 | 0.761792E+10 | 0.00 | 0.313318E+11 | 0.400753E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161297E+12 | 0.218965E+11 | 0.165903E+13 | 0.323967E+12 | 0.826740E+11 | 0.131542E+11 | 0.00 | 0.501027E+11 | 0.110112E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173005E+12 | 0.179155E+11 | 0.774844E+12 | 0.205461E+12 | 0.935113E+11 | 0.221415E+11 | 0.00 | 0.341043E+11 | 0.942482E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.171559E+12 | 0.155823E+11 | 0.106252E+13 | 0.240716E+12 | 0.132431E+12 | 0.430961E+11 | 0.00 | 0.948038E+11 | 0.232134E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161118E+12 | 0.167639E+11 | 0.139340E+13 | 0.291731E+12 | 0.155315E+12 | 0.612802E+11 | 0.00 | 0.158147E+12 | 0.343025E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179656E+12 | 0.204283E+11 | 0.173200E+13 | 0.334956E+12 | 0.152330E+12 | 0.570137E+11 | 0.00 | 0.150917E+12 | 0.311252E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161912E+12 | 0.249997E+11 | 0.740713E+12 | 0.198738E+12 | 0.103761E+12 | 0.330306E+11 | 0.00 | 0.598001E+11 | 0.163667E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169836E+12 | 0.322838E+11 | 0.108340E+13 | 0.248592E+12 | 0.846793E+11 | 0.164656E+11 | 0.00 | 0.339724E+11 | 0.844083E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170582E+12 | 0.375508E+11 | 0.135889E+13 | 0.282386E+12 | 0.741253E+11 | 0.869595E+10 | 0.00 | 0.309525E+11 | 0.592134E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168838E+12 | 0.424162E+11 | 0.170972E+13 | 0.334890E+12 | 0.732214E+11 | 0.520253E+10 | 0.00 | 0.393057E+11 | 0.428405E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202852E+13 | 0.330954E+12 | 0.146764E+14 | 0.318322E+13 | 0.117724E+13 | 0.277140E+12 | 0.00 | 0.701916E+12 | 0.150735E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154704E+12 | 0.155823E+11 | 0.740713E+12 | 0.198738E+12 | 0.681240E+11 | 0.399832E+10 | 0.00 | 0.229525E+10 | 0.298524E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181820E+12 | 0.424162E+11 | 0.173200E+13 | 0.334956E+12 | 0.155315E+12 | 0.612802E+11 | 0.00 | 0.158147E+12 | 0.343025E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.108301E+13 | 0.00 | 0.696302E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.592912E+12 | 0.00 | 0.640260E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.368605E+12 | 0.00 | 0.736683E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.108094E+12 | 0.00 | 0.659020E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.663484E+11 | 0.00 | 0.669073E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.220148E+10 | 0.00 | 0.628395E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.588052E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.145730E+09 | 0.00 | 0.617692E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.164732E+11 | 0.00 | 0.576018E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.790689E+11 | 0.00 | 0.614596E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.294293E+12 | 0.00 | 0.628717E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.714187E+12 | 0.00 | 0.660831E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.332534E+13 | 0.00 | 0.771564E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.576018E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.108301E+13 | 0.00 | 0.736683E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 198852.03 | 02-JAN-08:09 | 37611.08 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 132999.73 | 02-JAN-08:20 | 69321.78 | 09-JAN-06:19 | 27963.13 | 07-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 189730.43 | 02-FEB-08:09 | 37611.08 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 149129.31 | 02-FEB-08:20 | 83486.79 | 28-FEB-15:00 | 28080.03 | 04-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 196654.12 | 17-MAR-07:10 | 37611.08 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 165267.35 | 17-MAR-07:19 | 89599.42 | 28-MAR-15:50 | 27927.09 | 04-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 186605.48 | 14-APR-07:10 | 37611.08 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 181396.44 | 14-APR-07:19 | 137251.85 | 25-APR-15:39 | 43130.52 | 06-APR-15:20 | 0.00 | 01-APR-00:10 |
May | 181706.25 | 03-MAY-07:10 | 37611.08 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 132990.70 | 03-MAY-07:19 | 170421.18 | 19-MAY-15:30 | 44871.61 | 19-MAY-12:30 | 0.00 | 01-MAY-00:10 |
June | 173044.97 | 16-JUN-07:10 | 24287.76 | 01-JUN-20:10 | 541788.89 | 01-JUN-07:10 | 149120.53 | 16-JUN-07:19 | 200158.97 | 29-JUN-14:30 | 46027.35 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 174997.81 | 07-JUL-07:30 | 24287.76 | 01-JUL-20:30 | 660080.29 | 03-JUL-07:10 | 165255.94 | 07-JUL-07:40 | 231088.31 | 26-JUL-15:20 | 47132.45 | 31-JUL-15:39 | 0.00 | 01-JUL-00:10 |
August | 178894.40 | 17-AUG-07:10 | 37611.08 | 03-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 181392.38 | 17-AUG-07:19 | 227908.41 | 11-AUG-15:39 | 47481.77 | 07-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 186049.93 | 11-SEP-07:10 | 37611.08 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 132992.99 | 11-SEP-07:19 | 183695.36 | 05-SEP-14:50 | 47997.75 | 05-SEP-12:39 | 0.00 | 01-SEP-00:10 |
October | 198852.03 | 30-OCT-07:10 | 37611.08 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 149134.12 | 30-OCT-07:19 | 117265.93 | 18-OCT-15:00 | 43480.16 | 18-OCT-14:30 | 0.00 | 01-OCT-00:10 |
November | 198852.03 | 01-NOV-07:10 | 37611.08 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 165268.51 | 01-NOV-07:19 | 88269.60 | 03-NOV-15:20 | 28103.28 | 27-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 198852.03 | 01-DEC-16:40 | 37611.08 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 181402.89 | 13-DEC-08:20 | 56932.52 | 29-DEC-06:10 | 28132.05 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 173044.97 | 24287.76 | 423497.50 | 132990.70 | 56932.52 | 27927.09 | 0.00 | |||||||
Maximum of Months | 198852.03 | 37611.08 | 778371.69 | 181402.89 | 231088.31 | 47997.75 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 5219.65 | 19-JAN-15:50 | 875.80 | 13-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51660.85 | 27-FEB-13:39 | 12476.23 | 27-FEB-13:09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17990.74 | 14-MAR-13:30 | 8921.65 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 86468.20 | 07-APR-14:20 | 13257.25 | 06-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 149294.76 | 19-MAY-15:30 | 16409.44 | 19-MAY-12:20 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 183725.36 | 30-JUN-15:00 | 39494.40 | 06-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 226836.45 | 17-JUL-15:30 | 39494.40 | 13-JUL-13:09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 208346.11 | 07-AUG-15:39 | 39494.40 | 05-AUG-13:39 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 294589.30 | 07-SEP-14:00 | 39494.40 | 02-SEP-10:00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 138989.80 | 18-OCT-15:50 | 13641.10 | 18-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36871.09 | 17-NOV-16:00 | 12500.52 | 17-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18800.37 | 06-DEC-16:10 | 8300.00 | 10-DEC-01:00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5219.65 | 875.80 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 294589.30 | 39494.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 844272.72 | 09-JAN-08:09 | 198852.03 | 423497.50 | 37611.08 | 132930.40 | 50571.57 | 810.15 | 0.00 | 0.00 | 0.00 |
February | 978088.58 | 27-FEB-16:10 | 171235.93 | 541788.89 | 0.00 | 115076.19 | 66590.49 | 27868.36 | 0.00 | 43052.49 | 12476.23 |
March | 1092918.02 | 16-MAR-15:39 | 171235.93 | 660080.29 | 0.00 | 131210.58 | 85714.55 | 27800.74 | 0.00 | 15166.78 | 1709.16 |
April | 1351693.03 | 06-APR-15:20 | 171235.93 | 778371.69 | 0.00 | 147344.96 | 115781.50 | 43130.52 | 0.00 | 82685.26 | 13143.18 |
May | 1073392.70 | 19-MAY-15:30 | 171235.93 | 423497.50 | 0.00 | 98941.80 | 170421.18 | 44655.84 | 0.00 | 149294.76 | 15345.70 |
June | 1268438.35 | 30-JUN-15:39 | 171235.93 | 541788.89 | 0.00 | 115076.19 | 195842.14 | 45974.04 | 0.00 | 183344.11 | 15177.07 |
July | 1501534.03 | 17-JUL-15:20 | 171235.93 | 660080.29 | 0.00 | 131210.58 | 227742.50 | 46511.59 | 0.00 | 225258.75 | 39494.40 |
August | 1598375.19 | 08-AUG-15:39 | 171235.93 | 778371.69 | 0.00 | 147344.96 | 217601.34 | 45013.10 | 0.00 | 199313.79 | 39494.40 |
September | 1189494.76 | 07-SEP-14:00 | 171235.93 | 423497.50 | 0.00 | 53550.62 | 161318.41 | 45808.62 | 0.00 | 294589.30 | 39494.40 |
October | 1136530.18 | 18-OCT-15:50 | 174869.97 | 541788.89 | 0.00 | 115077.70 | 109443.20 | 43360.56 | 0.00 | 138989.80 | 13000.06 |
November | 1155209.37 | 17-NOV-16:00 | 198852.03 | 660080.29 | 37611.08 | 131225.12 | 50235.00 | 27834.25 | 0.00 | 36871.09 | 12500.52 |
December | 1254894.98 | 29-DEC-08:09 | 198852.03 | 778371.69 | 37611.08 | 181333.56 | 44005.79 | 1212.87 | 0.00 | 12899.63 | 608.33 |
Annual Sum or Average | |||||||||||
Minimum of Months | 844272.72 | 171235.93 | 423497.50 | 0.00 | 53550.62 | 44005.79 | 810.15 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1598375.19 | 198852.03 | 778371.69 | 37611.08 | 181333.56 | 227742.50 | 46511.59 | 0.00 | 294589.30 | 39494.40 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 2299529.62 | 09-JAN-07:19 | 0.00 | 85365.32 | 30-JAN-12:39 | 0.00 |
February | 0.00 | 0.00 | 1534304.95 | 01-FEB-07:10 | 0.00 | 85520.58 | 14-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 1576505.97 | 06-MAR-07:10 | 0.00 | 85467.39 | 02-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 590149.55 | 29-APR-06:10 | 0.00 | 84640.52 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 580013.17 | 08-MAY-06:19 | 0.00 | 83179.28 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 188388.31 | 16-JUN-06:00 | 0.00 | 81118.55 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 78924.83 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 50914.48 | 18-AUG-05:10 | 0.00 | 77483.63 | 04-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 314047.13 | 19-SEP-06:10 | 0.00 | 78384.27 | 28-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 677479.37 | 10-OCT-06:30 | 0.00 | 80552.75 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 1300942.40 | 27-NOV-07:19 | 0.00 | 82619.10 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 1697862.07 | 29-DEC-07:00 | 0.00 | 84270.86 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 77483.63 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 2299529.62 | 0.00 | 85520.58 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.19 | 1.50 | 27.22 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.85 | 0.00 | 25.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.84 | 0.00 | 25.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 25.88 | 0.00 | 25.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 26.01 | 0.17 | 26.05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.02 | 0.00 | 26.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 26.29 | 0.00 | 26.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.22 | 0.00 | 26.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 26.59 | 1.17 | 26.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 26.50 | 1.17 | 26.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.40 | 0.00 | 26.40 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.73 | 0.00 | 25.73 |
Annual Sum or Average | 0.00 | 0.00 | 59.50 | 26.35 | 4.00 | 26.42 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.73 | 0.00 | 25.73 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.19 | 1.50 | 27.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.60 | 0.00 | 25.60 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.88 | 0.00 | 25.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.20 | 0.00 | 26.20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 25.58 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 25.60 |
Annual Sum or Average | 0.00 | 0.00 | 2.00 | 25.69 | 0.00 | 25.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.20 | 0.00 | 26.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
February | 0.17 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.83 | 18.79 | 3.83 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
February | 3.50 | 18.84 | 0.50 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
March | 2.50 | 18.71 | 0.83 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.50 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
November | 2.33 | 18.87 | 0.67 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
December | 4.50 | 18.77 | 0.83 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
Annual Sum or Average | 25.50 | 18.79 | 6.67 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.83 | 18.87 | 3.83 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 18.86 | 1.33 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
February | 0.50 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
March | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.00 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.30 | 0.67 | 27.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Annual Sum or Average | 6.17 | 18.94 | 1.33 | 19.15 | 0.83 | 19.96 | 0.67 | 20.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.17 | 19.43 | 1.33 | 19.43 | 0.67 | 27.34 | 0.67 | 27.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 18.37 | 0.50 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
February | 0.83 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
March | 0.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.77 | 0.83 | 27.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.91 | 4.83 | 27.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.99 | 7.33 | 27.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.93 | 3.17 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.76 | 4.50 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Annual Sum or Average | 5.50 | 18.59 | 0.50 | 18.74 | 21.33 | 25.88 | 21.17 | 26.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 19.24 | 0.50 | 19.24 | 7.33 | 27.99 | 7.33 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 18.41 | 0.50 | 18.60 | 0.50 | 19.39 | 0.50 | 20.06 |
February | 0.83 | 19.21 | 0.00 | 19.21 | 1.83 | 25.24 | 1.83 | 26.36 |
March | 0.17 | 18.90 | 0.00 | 18.90 | 0.67 | 25.81 | 0.67 | 26.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.61 | 1.83 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.47 | 1.17 | 27.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.45 | 2.50 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.71 | 6.33 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.77 | 4.00 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.94 | 6.33 | 27.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.05 | 3.00 | 28.05 |
November | 0.17 | 19.32 | 0.00 | 19.32 | 1.67 | 26.83 | 1.67 | 27.19 |
December | 0.50 | 19.05 | 0.00 | 19.05 | 0.17 | 21.11 | 0.17 | 22.34 |
Annual Sum or Average | 6.17 | 18.61 | 0.50 | 18.73 | 32.33 | 26.22 | 30.00 | 26.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 19.39 | 0.17 | 20.06 |
Maximum of Months | 4.50 | 19.32 | 0.50 | 19.32 | 7.17 | 28.05 | 6.33 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.65 | 1.00 | 27.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.59 | 0.67 | 27.63 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.76 | 3.33 | 27.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.11 | 2.00 | 28.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.72 | 4.17 | 27.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 27.55 | 8.33 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 27.16 | 5.83 | 27.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.82 | 3.50 | 27.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.74 | 1.33 | 27.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.00 | 18.85 | 0.00 | 18.85 | 84.00 | 27.32 | 30.17 | 27.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 18.85 | 0.00 | 18.85 | 27.17 | 28.11 | 8.33 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.17 | 17.53 | 31.00 | 17.87 | 0.00 | 17.87 | 0.00 | 17.87 |
February | 19.33 | 17.87 | 7.00 | 18.13 | 0.00 | 18.13 | 0.00 | 18.13 |
March | 7.17 | 17.91 | 2.33 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
November | 5.67 | 18.55 | 1.67 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
December | 23.67 | 18.00 | 10.17 | 18.16 | 0.00 | 18.16 | 0.00 | 18.16 |
Annual Sum or Average | 118.33 | 17.76 | 52.17 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.17 | 19.42 | 31.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.67 | 15.81 | 4.00 | 15.72 | 0.00 | 15.72 | 0.00 | 15.72 |
February | 9.33 | 16.61 | 0.33 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 |
March | 3.50 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
April | 0.17 | 19.42 | 0.00 | 19.42 | 0.33 | 24.77 | 0.33 | 25.83 |
May | 0.17 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.97 | 5.00 | 27.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.07 | 9.00 | 28.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.22 | 3.00 | 28.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.80 | 4.17 | 27.80 |
October | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
November | 2.17 | 17.99 | 0.00 | 17.99 | 0.00 | 17.99 | 0.00 | 17.99 |
December | 11.17 | 16.50 | 2.33 | 16.18 | 0.00 | 16.18 | 0.00 | 16.18 |
Annual Sum or Average | 51.33 | 16.32 | 6.67 | 16.16 | 21.67 | 19.38 | 21.50 | 21.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.72 | 0.00 | 15.72 |
Maximum of Months | 24.67 | 19.43 | 4.00 | 19.43 | 9.17 | 28.22 | 9.00 | 28.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.50 | 16.51 | 2.83 | 16.48 | 0.17 | 16.56 | 0.17 | 16.64 |
February | 4.83 | 17.52 | 0.33 | 17.36 | 1.67 | 20.00 | 1.67 | 21.61 |
March | 1.83 | 18.29 | 0.17 | 18.46 | 0.67 | 20.76 | 0.67 | 22.13 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.73 | 1.00 | 27.73 |
May | 0.17 | 19.38 | 0.00 | 19.38 | 0.67 | 25.91 | 0.67 | 26.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.43 | 1.67 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.72 | 5.83 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.88 | 3.67 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.05 | 7.00 | 28.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.26 | 3.00 | 28.26 |
November | 1.50 | 18.15 | 0.00 | 18.15 | 1.83 | 23.39 | 1.83 | 24.92 |
December | 8.50 | 16.62 | 1.33 | 16.36 | 0.00 | 16.36 | 0.00 | 16.36 |
Annual Sum or Average | 35.33 | 16.85 | 4.67 | 16.74 | 29.00 | 21.42 | 27.17 | 23.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.36 | 0.00 | 16.36 |
Maximum of Months | 18.50 | 19.38 | 2.83 | 19.38 | 7.83 | 28.26 | 7.00 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.17 | 15.98 | 3.67 | 15.87 | 0.00 | 15.87 | 0.00 | 15.87 |
February | 3.83 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 |
March | 1.50 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.09 | 0.50 | 28.16 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.08 | 1.33 | 28.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.09 | 1.50 | 28.12 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.36 | 4.50 | 28.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.13 | 2.17 | 28.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.14 | 2.17 | 28.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.54 | 0.33 | 27.58 |
November | 1.50 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 |
December | 8.67 | 16.54 | 1.83 | 16.25 | 0.00 | 16.25 | 0.00 | 16.25 |
Annual Sum or Average | 35.67 | 16.56 | 5.50 | 16.37 | 26.83 | 21.03 | 12.50 | 22.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 | 0.00 | 15.87 |
Maximum of Months | 20.17 | 18.39 | 3.67 | 18.39 | 9.33 | 28.36 | 4.50 | 28.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 109.17 | 16.81 | 51.83 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 |
February | 43.67 | 17.41 | 16.50 | 17.78 | 0.00 | 17.78 | 0.00 | 17.78 |
March | 25.67 | 16.94 | 8.17 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
April | 3.00 | 18.85 | 0.17 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
May | 3.50 | 18.13 | 0.50 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.40 | 0.00 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.50 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
October | 3.17 | 18.65 | 0.33 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
November | 29.50 | 16.73 | 10.50 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 |
December | 69.67 | 16.55 | 27.83 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 |
Annual Sum or Average | 287.83 | 16.91 | 115.83 | 17.20 | 0.50 | 17.22 | 0.00 | 17.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 109.17 | 19.27 | 51.83 | 19.27 | 0.50 | 27.40 | 0.00 | 27.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 53.00 | 15.49 | 12.17 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 |
February | 22.17 | 15.92 | 2.67 | 15.77 | 0.00 | 15.77 | 0.00 | 15.77 |
March | 17.33 | 16.32 | 2.83 | 16.14 | 0.00 | 16.14 | 0.00 | 16.14 |
April | 2.67 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
May | 2.00 | 17.82 | 0.00 | 17.82 | 0.00 | 17.82 | 0.00 | 17.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.80 | 5.00 | 27.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 28.01 | 10.00 | 28.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.30 | 2.83 | 28.35 |
September | 0.50 | 19.30 | 0.00 | 19.30 | 4.83 | 27.06 | 4.67 | 27.44 |
October | 2.17 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
November | 18.00 | 16.07 | 3.33 | 15.95 | 0.00 | 15.95 | 0.00 | 15.95 |
December | 41.50 | 15.34 | 9.17 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
Annual Sum or Average | 159.33 | 15.80 | 30.17 | 15.71 | 24.17 | 17.09 | 22.50 | 18.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 0.00 | 15.22 |
Maximum of Months | 53.00 | 19.30 | 12.17 | 19.30 | 11.00 | 28.30 | 10.00 | 28.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 49.33 | 16.25 | 12.33 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
February | 17.50 | 16.40 | 0.83 | 16.29 | 1.00 | 16.90 | 1.00 | 17.44 |
March | 15.17 | 16.64 | 2.00 | 16.65 | 0.00 | 16.65 | 0.00 | 16.65 |
April | 2.17 | 18.68 | 0.00 | 18.68 | 0.33 | 19.84 | 0.33 | 20.73 |
May | 2.17 | 18.02 | 0.00 | 18.02 | 0.50 | 19.78 | 0.50 | 20.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.49 | 1.33 | 27.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.81 | 6.00 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.93 | 3.83 | 27.96 |
September | 0.33 | 19.36 | 0.00 | 19.36 | 7.33 | 27.73 | 6.00 | 27.94 |
October | 1.50 | 18.28 | 0.00 | 18.28 | 1.83 | 23.65 | 1.83 | 25.22 |
November | 11.83 | 16.77 | 1.50 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
December | 34.33 | 15.79 | 6.33 | 15.67 | 0.00 | 15.67 | 0.00 | 15.67 |
Annual Sum or Average | 134.33 | 16.34 | 23.00 | 16.36 | 24.50 | 17.92 | 20.83 | 18.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 0.00 | 15.67 |
Maximum of Months | 49.33 | 19.36 | 12.33 | 19.36 | 7.50 | 27.93 | 6.00 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 39.17 | 15.26 | 7.33 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
February | 17.00 | 16.26 | 2.17 | 16.06 | 0.00 | 16.06 | 0.00 | 16.06 |
March | 12.67 | 16.42 | 1.50 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
April | 1.67 | 18.99 | 0.00 | 18.99 | 1.00 | 22.31 | 0.50 | 23.19 |
May | 1.50 | 18.28 | 0.00 | 18.28 | 3.67 | 25.20 | 1.33 | 25.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.16 | 1.50 | 28.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.44 | 4.33 | 28.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.26 | 2.00 | 28.28 |
September | 0.17 | 19.39 | 0.00 | 19.39 | 3.67 | 27.97 | 2.00 | 28.21 |
October | 1.50 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
November | 10.00 | 16.47 | 1.83 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
December | 28.83 | 15.72 | 5.67 | 15.55 | 0.00 | 15.55 | 0.00 | 15.55 |
Annual Sum or Average | 112.50 | 15.91 | 18.50 | 15.75 | 27.17 | 17.90 | 11.67 | 18.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 0.00 | 15.22 |
Maximum of Months | 39.17 | 19.39 | 7.33 | 19.39 | 10.00 | 28.44 | 4.33 | 28.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.74 | 2.00 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.50 | 27.74 | 2.00 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.74 | 2.00 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.64 | 0.67 | 27.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.50 | 27.64 | 0.67 | 27.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.64 | 0.67 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.71 | 1.33 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.50 | 27.71 | 1.33 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.71 | 1.33 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 408.00 | 23.25 | 30.00 | 23.45 | 1.00 | 23.44 |
February | 345.50 | 23.69 | 30.83 | 23.90 | 0.00 | 23.90 |
March | 335.33 | 24.00 | 32.00 | 24.18 | 0.00 | 24.18 |
April | 143.83 | 24.01 | 77.33 | 24.74 | 0.00 | 24.74 |
May | 118.83 | 24.00 | 102.33 | 24.90 | 0.00 | 24.90 |
June | 24.50 | 24.19 | 222.83 | 24.95 | 8.67 | 24.93 |
July | 10.00 | 24.75 | 329.50 | 24.96 | 9.33 | 24.95 |
August | 0.00 | 0.00 | 213.17 | 25.22 | 0.00 | 25.22 |
September | 27.17 | 24.00 | 205.00 | 25.15 | 16.83 | 25.07 |
October | 29.33 | 24.00 | 112.17 | 25.91 | 0.00 | 25.91 |
November | 168.83 | 24.01 | 89.67 | 24.84 | 0.00 | 24.84 |
December | 326.33 | 23.87 | 47.00 | 24.17 | 0.00 | 24.17 |
Annual Sum or Average | 1937.67 | 23.77 | 1491.83 | 24.52 | 35.83 | 24.52 |
Minimum of Months | 0.00 | 0.00 | 30.00 | 23.45 | 0.00 | 23.44 |
Maximum of Months | 408.00 | 24.75 | 329.50 | 25.91 | 16.83 | 25.91 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.83 | 23.35 | 11.50 | 23.40 | 1.33 | 23.39 |
February | 385.83 | 23.70 | 2.83 | 23.71 | 0.00 | 23.71 |
March | 307.00 | 23.94 | 11.17 | 24.01 | 0.00 | 24.01 |
April | 88.83 | 23.98 | 47.83 | 24.66 | 0.00 | 24.66 |
May | 144.17 | 23.96 | 73.50 | 24.46 | 0.00 | 24.46 |
June | 13.33 | 24.14 | 209.17 | 24.48 | 7.17 | 24.47 |
July | 4.17 | 24.08 | 329.83 | 24.39 | 4.17 | 24.38 |
August | 0.00 | 0.00 | 213.33 | 24.50 | 0.00 | 24.50 |
September | 47.67 | 24.04 | 175.83 | 24.54 | 16.33 | 24.52 |
October | 77.33 | 23.97 | 74.50 | 24.91 | 0.00 | 24.91 |
November | 221.00 | 23.97 | 43.83 | 24.29 | 0.00 | 24.29 |
December | 334.67 | 23.90 | 14.83 | 23.98 | 0.00 | 23.98 |
Annual Sum or Average | 2090.83 | 23.77 | 1208.17 | 24.14 | 29.00 | 24.14 |
Minimum of Months | 0.00 | 0.00 | 2.83 | 23.40 | 0.00 | 23.39 |
Maximum of Months | 466.83 | 24.14 | 329.83 | 24.91 | 16.33 | 24.91 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.80 | 126.17 | 21.57 | 126.17 | 21.42 |
February | 454.00 | 22.38 | 48.33 | 22.20 | 48.33 | 22.06 |
March | 514.00 | 23.13 | 18.33 | 23.05 | 18.33 | 22.99 |
April | 427.17 | 23.61 | 0.00 | 23.61 | 0.00 | 23.61 |
May | 311.17 | 23.67 | 41.50 | 23.86 | 0.00 | 23.86 |
June | 105.33 | 23.75 | 129.17 | 24.06 | 8.17 | 24.07 |
July | 42.83 | 24.02 | 199.67 | 24.36 | 10.33 | 24.37 |
August | 37.33 | 23.77 | 113.33 | 24.47 | 0.00 | 24.47 |
September | 188.67 | 23.73 | 110.33 | 24.02 | 17.83 | 24.02 |
October | 384.50 | 23.66 | 3.50 | 23.67 | 0.00 | 23.67 |
November | 478.50 | 23.24 | 4.17 | 23.22 | 4.17 | 23.20 |
December | 497.00 | 22.30 | 55.67 | 22.12 | 55.67 | 21.98 |
Annual Sum or Average | 3942.50 | 22.99 | 850.17 | 23.06 | 289.00 | 22.95 |
Minimum of Months | 37.33 | 21.80 | 0.00 | 21.57 | 0.00 | 21.42 |
Maximum of Months | 514.00 | 24.02 | 199.67 | 24.47 | 126.17 | 24.47 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.43 | 397.17 | 20.30 | 397.17 | 20.25 |
February | 454.00 | 21.01 | 260.00 | 20.78 | 260.00 | 20.67 |
March | 514.00 | 21.64 | 154.33 | 21.34 | 154.33 | 21.15 |
April | 472.33 | 22.49 | 56.00 | 22.30 | 56.00 | 22.14 |
May | 375.17 | 22.93 | 60.00 | 22.93 | 28.67 | 22.80 |
June | 169.83 | 23.44 | 120.83 | 23.78 | 7.83 | 23.80 |
July | 60.17 | 23.64 | 240.67 | 24.19 | 9.33 | 24.20 |
August | 97.17 | 23.54 | 125.67 | 24.06 | 0.00 | 24.06 |
September | 288.17 | 23.07 | 100.67 | 23.42 | 19.00 | 23.45 |
October | 492.00 | 22.42 | 32.33 | 22.29 | 32.33 | 22.18 |
November | 489.00 | 21.40 | 184.00 | 21.10 | 184.00 | 20.93 |
December | 497.00 | 20.65 | 334.00 | 20.42 | 334.00 | 20.33 |
Annual Sum or Average | 4410.83 | 21.82 | 2065.67 | 21.71 | 1482.67 | 21.46 |
Minimum of Months | 60.17 | 20.43 | 32.33 | 20.30 | 0.00 | 20.25 |
Maximum of Months | 514.00 | 23.64 | 397.17 | 24.19 | 397.17 | 24.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.98 | 292.67 | 20.75 | 292.67 | 20.65 |
February | 454.00 | 21.75 | 141.33 | 21.46 | 141.33 | 21.28 |
March | 514.00 | 22.68 | 45.33 | 22.51 | 45.33 | 22.36 |
April | 435.83 | 23.46 | 0.33 | 23.46 | 0.00 | 23.46 |
May | 317.83 | 23.45 | 55.33 | 23.70 | 0.00 | 23.70 |
June | 65.33 | 23.80 | 202.83 | 24.27 | 4.33 | 24.27 |
July | 7.33 | 24.27 | 336.83 | 24.49 | 1.33 | 24.50 |
August | 34.67 | 23.81 | 196.33 | 24.40 | 0.33 | 24.41 |
September | 230.67 | 23.45 | 124.67 | 23.87 | 12.17 | 23.88 |
October | 443.33 | 23.35 | 4.33 | 23.37 | 0.00 | 23.37 |
November | 484.00 | 22.65 | 28.83 | 22.55 | 28.83 | 22.46 |
December | 497.00 | 21.78 | 145.83 | 21.51 | 145.83 | 21.33 |
Annual Sum or Average | 3986.00 | 22.54 | 1574.67 | 22.63 | 672.17 | 22.41 |
Minimum of Months | 7.33 | 20.98 | 0.33 | 20.75 | 0.00 | 20.65 |
Maximum of Months | 514.00 | 24.27 | 336.83 | 24.49 | 292.67 | 24.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.17 | 20.98 | 302.00 | 20.77 | 302.00 | 20.67 |
February | 433.00 | 21.69 | 153.17 | 21.44 | 149.50 | 21.26 |
March | 470.83 | 22.31 | 53.67 | 22.18 | 49.50 | 22.04 |
April | 337.33 | 22.87 | 44.67 | 23.09 | 1.33 | 23.09 |
May | 236.83 | 23.03 | 97.83 | 23.51 | 0.00 | 23.51 |
June | 95.00 | 24.05 | 271.00 | 24.36 | 21.00 | 24.47 |
July | 47.00 | 25.57 | 386.83 | 24.60 | 29.17 | 24.74 |
August | 72.50 | 23.74 | 280.83 | 24.22 | 7.83 | 24.28 |
September | 204.83 | 23.38 | 182.33 | 23.99 | 24.33 | 24.08 |
October | 354.33 | 22.93 | 13.83 | 23.03 | 0.00 | 23.03 |
November | 472.67 | 22.29 | 52.50 | 22.14 | 52.50 | 22.02 |
December | 497.00 | 21.42 | 190.67 | 21.18 | 190.67 | 21.04 |
Annual Sum or Average | 3720.50 | 22.27 | 2029.33 | 22.54 | 827.83 | 22.36 |
Minimum of Months | 47.00 | 20.98 | 13.83 | 20.77 | 0.00 | 20.67 |
Maximum of Months | 499.17 | 25.57 | 386.83 | 24.60 | 302.00 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 468.17 | 21.35 | 265.17 | 21.10 | 255.17 | 20.92 |
February | 363.17 | 22.02 | 147.00 | 21.93 | 118.17 | 21.72 |
March | 399.33 | 22.42 | 85.00 | 22.42 | 46.33 | 22.25 |
April | 311.50 | 22.94 | 51.67 | 23.19 | 4.50 | 23.19 |
May | 261.67 | 22.92 | 98.33 | 23.41 | 6.33 | 23.38 |
June | 105.00 | 23.61 | 228.33 | 24.20 | 8.83 | 24.24 |
July | 45.17 | 25.10 | 371.17 | 24.59 | 20.67 | 24.70 |
August | 50.00 | 24.29 | 319.00 | 24.45 | 11.33 | 24.53 |
September | 171.67 | 23.60 | 233.00 | 24.26 | 29.00 | 24.38 |
October | 272.17 | 23.13 | 103.17 | 23.57 | 6.83 | 23.63 |
November | 358.33 | 22.49 | 90.33 | 22.58 | 45.50 | 22.42 |
December | 427.67 | 21.76 | 161.17 | 21.53 | 147.50 | 21.32 |
Annual Sum or Average | 3233.83 | 22.46 | 2153.33 | 22.86 | 700.17 | 22.67 |
Minimum of Months | 45.17 | 21.35 | 51.67 | 21.10 | 4.50 | 20.92 |
Maximum of Months | 468.17 | 25.10 | 371.17 | 24.59 | 255.17 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.00 | 21.40 | 215.33 | 21.14 | 215.33 | 21.00 |
February | 389.33 | 22.38 | 89.17 | 22.25 | 74.67 | 22.06 |
March | 312.33 | 23.22 | 46.50 | 23.32 | 11.33 | 23.26 |
April | 79.17 | 23.99 | 154.50 | 24.89 | 7.33 | 24.96 |
May | 159.00 | 23.38 | 173.00 | 24.21 | 6.33 | 24.27 |
June | 35.33 | 25.15 | 372.83 | 24.66 | 19.17 | 24.74 |
July | 40.67 | 26.97 | 475.33 | 24.86 | 40.67 | 25.01 |
August | 20.50 | 27.10 | 470.00 | 24.69 | 20.50 | 24.78 |
September | 137.83 | 23.66 | 231.33 | 24.35 | 21.33 | 24.43 |
October | 190.50 | 23.45 | 97.17 | 24.06 | 2.83 | 24.09 |
November | 298.67 | 23.23 | 46.00 | 23.55 | 0.33 | 23.55 |
December | 403.00 | 22.90 | 52.50 | 22.81 | 40.17 | 22.65 |
Annual Sum or Average | 2563.33 | 22.88 | 2423.67 | 23.53 | 460.00 | 23.42 |
Minimum of Months | 20.50 | 21.40 | 46.00 | 21.14 | 0.33 | 21.00 |
Maximum of Months | 497.00 | 27.10 | 475.33 | 24.89 | 215.33 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.97 | 496.00 | 19.97 | 496.00 | 19.97 |
February | 454.00 | 20.44 | 394.17 | 20.37 | 394.17 | 20.35 |
March | 514.00 | 20.95 | 288.50 | 20.75 | 288.50 | 20.65 |
April | 485.00 | 22.04 | 71.17 | 21.85 | 71.17 | 21.71 |
May | 397.17 | 22.63 | 62.33 | 22.61 | 34.33 | 22.46 |
June | 171.83 | 23.48 | 136.33 | 23.85 | 5.17 | 23.86 |
July | 41.17 | 23.67 | 250.00 | 24.34 | 0.67 | 24.34 |
August | 130.00 | 23.47 | 118.50 | 23.96 | 0.00 | 23.96 |
September | 323.67 | 22.74 | 83.33 | 23.10 | 17.17 | 23.11 |
October | 502.00 | 22.01 | 59.17 | 21.87 | 59.17 | 21.75 |
November | 489.00 | 20.85 | 281.50 | 20.64 | 281.50 | 20.54 |
December | 497.00 | 20.10 | 461.83 | 20.06 | 461.83 | 20.04 |
Annual Sum or Average | 4506.83 | 21.39 | 2702.83 | 21.30 | 2109.67 | 21.06 |
Minimum of Months | 41.17 | 19.97 | 59.17 | 19.97 | 0.00 | 19.97 |
Maximum of Months | 514.00 | 23.67 | 496.00 | 24.34 | 496.00 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.04 | 408.83 | 20.01 | 408.83 | 20.01 |
February | 383.17 | 20.69 | 275.83 | 20.51 | 275.83 | 20.43 |
March | 424.33 | 21.20 | 200.17 | 20.93 | 200.17 | 20.79 |
April | 340.83 | 22.05 | 62.17 | 21.98 | 48.50 | 21.83 |
May | 267.17 | 22.40 | 89.83 | 22.65 | 28.67 | 22.49 |
June | 124.50 | 23.70 | 206.17 | 24.30 | 22.67 | 24.44 |
July | 59.83 | 25.28 | 309.17 | 24.80 | 32.17 | 24.97 |
August | 92.17 | 23.55 | 217.50 | 24.30 | 9.83 | 24.39 |
September | 233.50 | 22.83 | 125.33 | 23.56 | 22.50 | 23.69 |
October | 397.33 | 22.11 | 42.00 | 22.03 | 37.67 | 21.92 |
November | 416.00 | 20.98 | 213.17 | 20.77 | 213.17 | 20.66 |
December | 422.00 | 20.08 | 384.17 | 20.03 | 384.17 | 20.01 |
Annual Sum or Average | 3587.83 | 21.44 | 2534.33 | 21.61 | 1684.17 | 21.37 |
Minimum of Months | 59.83 | 20.04 | 42.00 | 20.01 | 9.83 | 20.01 |
Maximum of Months | 427.00 | 25.28 | 408.83 | 24.80 | 408.83 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 479.67 | 20.89 | 344.33 | 20.66 | 337.33 | 20.54 |
February | 383.33 | 21.51 | 226.83 | 21.37 | 198.67 | 21.16 |
March | 415.33 | 21.66 | 181.00 | 21.56 | 143.33 | 21.35 |
April | 355.67 | 22.27 | 82.17 | 22.41 | 41.00 | 22.28 |
May | 302.33 | 22.52 | 107.00 | 22.79 | 34.00 | 22.63 |
June | 154.67 | 23.26 | 198.83 | 23.95 | 7.67 | 23.98 |
July | 65.67 | 24.38 | 330.50 | 24.53 | 19.33 | 24.64 |
August | 96.17 | 23.66 | 280.67 | 24.32 | 10.00 | 24.40 |
September | 197.83 | 23.23 | 218.33 | 24.05 | 30.17 | 24.19 |
October | 319.33 | 22.71 | 112.67 | 23.10 | 23.67 | 23.10 |
November | 392.33 | 21.88 | 163.67 | 21.79 | 126.17 | 21.57 |
December | 457.00 | 20.95 | 284.83 | 20.66 | 282.33 | 20.51 |
Annual Sum or Average | 3619.33 | 21.96 | 2530.83 | 22.25 | 1253.67 | 21.99 |
Minimum of Months | 65.67 | 20.89 | 82.17 | 20.66 | 7.67 | 20.51 |
Maximum of Months | 479.67 | 24.38 | 344.33 | 24.53 | 337.33 | 24.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.30 | 460.83 | 20.25 | 460.83 | 20.23 |
February | 443.00 | 20.86 | 292.67 | 20.68 | 291.17 | 20.60 |
March | 487.17 | 21.28 | 190.00 | 21.05 | 189.67 | 20.92 |
April | 404.33 | 22.20 | 55.83 | 22.30 | 28.67 | 22.24 |
May | 295.83 | 22.50 | 122.67 | 22.99 | 24.83 | 22.93 |
June | 134.83 | 23.28 | 238.33 | 24.05 | 12.67 | 24.12 |
July | 59.50 | 24.66 | 369.00 | 24.59 | 22.33 | 24.70 |
August | 96.67 | 23.41 | 263.50 | 24.27 | 7.50 | 24.33 |
September | 268.00 | 22.70 | 158.67 | 23.47 | 19.83 | 23.56 |
October | 435.00 | 22.13 | 41.83 | 22.12 | 27.50 | 22.05 |
November | 478.83 | 21.27 | 197.33 | 21.02 | 197.33 | 20.88 |
December | 497.00 | 20.42 | 392.67 | 20.29 | 392.67 | 20.25 |
Annual Sum or Average | 4102.17 | 21.53 | 2783.33 | 21.77 | 1675.00 | 21.53 |
Minimum of Months | 59.50 | 20.30 | 41.83 | 20.25 | 7.50 | 20.23 |
Maximum of Months | 502.00 | 24.66 | 460.83 | 24.59 | 460.83 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.60 | 501.17 | 19.60 | 501.17 | 19.60 |
February | 454.00 | 19.98 | 442.50 | 19.97 | 442.50 | 19.96 |
March | 514.00 | 20.35 | 422.67 | 20.26 | 422.67 | 20.22 |
April | 485.00 | 21.14 | 229.83 | 20.84 | 229.83 | 20.69 |
May | 433.50 | 21.99 | 132.17 | 21.80 | 108.33 | 21.56 |
June | 220.83 | 22.93 | 133.50 | 23.42 | 6.67 | 23.42 |
July | 98.33 | 23.36 | 236.00 | 24.11 | 4.17 | 24.13 |
August | 190.83 | 23.03 | 119.67 | 23.55 | 1.17 | 23.55 |
September | 368.00 | 22.07 | 119.67 | 22.29 | 61.50 | 22.17 |
October | 502.00 | 20.97 | 236.67 | 20.72 | 236.67 | 20.59 |
November | 489.00 | 20.11 | 417.83 | 20.02 | 417.83 | 19.99 |
December | 497.00 | 19.78 | 487.33 | 19.77 | 487.33 | 19.76 |
Annual Sum or Average | 4754.50 | 20.87 | 3479.00 | 20.80 | 2919.83 | 20.58 |
Minimum of Months | 98.33 | 19.60 | 119.67 | 19.60 | 1.17 | 19.60 |
Maximum of Months | 514.00 | 23.36 | 501.17 | 24.11 | 501.17 | 24.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.82 | 495.67 | 19.81 | 495.67 | 19.81 |
February | 454.00 | 20.29 | 393.33 | 20.19 | 393.33 | 20.16 |
March | 510.00 | 20.78 | 333.83 | 20.54 | 333.83 | 20.44 |
April | 412.67 | 21.53 | 162.83 | 21.22 | 154.17 | 21.01 |
May | 329.83 | 22.06 | 130.17 | 22.09 | 71.17 | 21.81 |
June | 143.00 | 23.29 | 251.67 | 24.06 | 24.50 | 24.15 |
July | 73.83 | 24.90 | 371.17 | 24.63 | 34.33 | 24.79 |
August | 112.17 | 23.23 | 290.00 | 24.11 | 11.00 | 24.18 |
September | 282.33 | 22.46 | 160.33 | 23.07 | 50.50 | 23.09 |
October | 484.17 | 21.45 | 144.17 | 21.15 | 144.17 | 20.97 |
November | 489.00 | 20.30 | 370.50 | 20.16 | 370.50 | 20.11 |
December | 497.00 | 19.86 | 475.67 | 19.84 | 475.67 | 19.83 |
Annual Sum or Average | 4290.00 | 21.03 | 3579.33 | 21.20 | 2558.83 | 20.96 |
Minimum of Months | 73.83 | 19.82 | 130.17 | 19.81 | 11.00 | 19.81 |
Maximum of Months | 510.00 | 24.90 | 495.67 | 24.63 | 495.67 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.50 | 20.37 | 402.67 | 20.15 | 402.33 | 20.07 |
February | 414.50 | 21.01 | 273.33 | 20.74 | 261.67 | 20.57 |
March | 443.83 | 21.05 | 270.50 | 20.80 | 256.50 | 20.64 |
April | 389.50 | 21.58 | 181.50 | 21.42 | 150.50 | 21.18 |
May | 342.00 | 22.03 | 145.00 | 22.11 | 81.00 | 21.85 |
June | 188.17 | 22.79 | 194.50 | 23.62 | 11.67 | 23.64 |
July | 96.67 | 23.86 | 314.50 | 24.39 | 22.00 | 24.51 |
August | 133.33 | 23.21 | 280.17 | 24.09 | 12.17 | 24.15 |
September | 235.67 | 22.57 | 219.83 | 23.40 | 55.00 | 23.41 |
October | 363.83 | 21.79 | 159.83 | 21.83 | 103.17 | 21.61 |
November | 435.50 | 21.07 | 253.67 | 20.80 | 242.17 | 20.64 |
December | 483.00 | 20.39 | 373.17 | 20.15 | 373.17 | 20.06 |
Annual Sum or Average | 4023.50 | 21.40 | 3068.67 | 21.57 | 1971.33 | 21.29 |
Minimum of Months | 96.67 | 20.37 | 145.00 | 20.15 | 11.67 | 20.06 |
Maximum of Months | 497.50 | 23.86 | 402.67 | 24.39 | 402.33 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.89 | 477.33 | 19.86 | 477.33 | 19.85 |
February | 450.33 | 20.47 | 363.33 | 20.32 | 363.33 | 20.26 |
March | 495.67 | 20.80 | 312.00 | 20.59 | 312.00 | 20.50 |
April | 420.83 | 21.51 | 162.00 | 21.37 | 141.00 | 21.20 |
May | 338.00 | 22.08 | 148.00 | 22.31 | 70.17 | 22.12 |
June | 177.50 | 22.86 | 227.83 | 23.76 | 14.33 | 23.82 |
July | 90.00 | 23.98 | 341.83 | 24.44 | 24.17 | 24.56 |
August | 136.17 | 23.01 | 258.67 | 24.01 | 8.67 | 24.07 |
September | 305.67 | 22.22 | 166.00 | 22.87 | 47.83 | 22.86 |
October | 460.50 | 21.41 | 145.67 | 21.21 | 137.00 | 21.04 |
November | 487.50 | 20.60 | 329.33 | 20.40 | 329.33 | 20.31 |
December | 497.00 | 20.01 | 447.83 | 19.94 | 447.83 | 19.91 |
Annual Sum or Average | 4361.17 | 21.10 | 3379.83 | 21.28 | 2373.00 | 21.04 |
Minimum of Months | 90.00 | 19.89 | 145.67 | 19.86 | 8.67 | 19.85 |
Maximum of Months | 502.00 | 23.98 | 477.33 | 24.44 | 477.33 | 24.56 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 26.26 | 358.67 | 27.00 | 0.00 | 27.00 |
February | 0.17 | 27.00 | 425.83 | 27.00 | 0.17 | 27.00 |
March | 3.00 | 27.00 | 513.83 | 27.00 | 3.00 | 27.00 |
April | 10.33 | 27.00 | 485.00 | 27.00 | 10.33 | 27.00 |
May | 0.50 | 27.00 | 508.00 | 27.00 | 0.50 | 27.00 |
June | 8.83 | 27.00 | 496.00 | 27.00 | 8.83 | 27.00 |
July | 48.83 | 27.00 | 497.00 | 27.00 | 48.83 | 27.00 |
August | 98.17 | 27.03 | 514.00 | 27.01 | 98.17 | 27.01 |
September | 4.50 | 27.00 | 485.00 | 27.00 | 4.50 | 27.00 |
October | 4.50 | 27.00 | 502.00 | 27.00 | 4.50 | 27.00 |
November | 0.50 | 27.00 | 489.00 | 27.00 | 0.50 | 27.00 |
December | 1.00 | 27.00 | 497.00 | 27.00 | 1.00 | 27.00 |
Annual Sum or Average | 181.83 | 27.01 | 5771.33 | 27.00 | 180.33 | 27.00 |
Minimum of Months | 0.17 | 26.26 | 358.67 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 98.17 | 27.03 | 514.00 | 27.01 | 98.17 | 27.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 128.67 | 25.45 | 169.00 | 26.33 | 0.00 | 26.33 |
February | 13.50 | 27.00 | 270.67 | 27.00 | 0.00 | 27.00 |
March | 6.00 | 27.00 | 455.83 | 27.00 | 0.00 | 27.00 |
April | 1.17 | 27.00 | 481.83 | 27.00 | 1.17 | 27.00 |
May | 0.00 | 0.00 | 503.17 | 27.00 | 0.00 | 27.00 |
June | 2.17 | 27.00 | 496.00 | 27.00 | 2.17 | 27.00 |
July | 6.33 | 27.00 | 497.00 | 27.00 | 6.33 | 27.00 |
August | 13.33 | 27.11 | 514.00 | 27.01 | 13.33 | 27.01 |
September | 0.83 | 27.00 | 485.00 | 27.00 | 0.83 | 27.00 |
October | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
November | 0.00 | 0.00 | 441.33 | 27.00 | 0.00 | 27.00 |
December | 12.00 | 27.00 | 310.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 184.00 | 25.93 | 5126.17 | 26.96 | 23.83 | 26.96 |
Minimum of Months | 0.00 | 0.00 | 169.00 | 26.33 | 0.00 | 26.33 |
Maximum of Months | 128.67 | 27.11 | 514.00 | 27.01 | 13.33 | 27.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 324.83 | 24.62 | 88.00 | 24.69 | 34.50 | 24.47 |
February | 45.33 | 26.91 | 146.00 | 26.98 | 0.00 | 26.98 |
March | 23.17 | 27.00 | 317.33 | 27.00 | 0.00 | 27.00 |
April | 2.00 | 27.00 | 420.67 | 27.00 | 2.00 | 27.00 |
May | 22.00 | 25.95 | 466.67 | 26.95 | 0.67 | 26.95 |
June | 6.00 | 27.00 | 496.00 | 27.00 | 6.00 | 27.00 |
July | 18.33 | 27.00 | 497.00 | 27.00 | 18.33 | 27.00 |
August | 21.83 | 27.08 | 514.00 | 27.01 | 21.83 | 27.01 |
September | 3.00 | 27.00 | 472.50 | 27.00 | 3.00 | 27.00 |
October | 0.00 | 0.00 | 444.83 | 27.00 | 0.00 | 27.00 |
November | 23.33 | 27.00 | 278.67 | 27.00 | 0.00 | 27.00 |
December | 69.17 | 27.00 | 155.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 559.00 | 25.57 | 4297.00 | 26.80 | 86.33 | 26.77 |
Minimum of Months | 0.00 | 0.00 | 88.00 | 24.69 | 0.00 | 24.47 |
Maximum of Months | 324.83 | 27.08 | 514.00 | 27.01 | 34.50 | 27.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 314.00 | 27.00 | 502.00 | 27.00 | 314.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5755.00 | 27.00 | 5943.00 | 27.00 | 5755.00 | 27.00 |
Minimum of Months | 314.00 | 27.00 | 454.00 | 27.00 | 314.00 | 27.00 |
Maximum of Months | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.98620 | 13.59004 | 0.59407 | 12.63309 |
February | 454.00000 | 27.00000 | 14.86668 | 0.69378 | 15.29684 |
March | 514.00000 | 26.99999 | 16.82948 | 0.78202 | 17.99724 |
April | 485.00000 | 27.00002 | 19.92400 | 0.87569 | 21.25020 |
May | 508.00000 | 27.00015 | 22.16311 | 0.12703 | 5.47271 |
June | 496.00000 | 27.00046 | 25.43775 | 0.23620 | 6.22760 |
July | 497.00000 | 27.00032 | 26.25568 | 0.30679 | 7.02181 |
August | 514.00000 | 27.00537 | 25.71606 | 0.33821 | 7.45975 |
September | 485.00000 | 27.00046 | 25.31396 | 0.16398 | 5.68194 |
October | 502.00000 | 27.00006 | 22.30490 | 0.82902 | 19.54803 |
November | 489.00000 | 27.00000 | 18.41997 | 0.80083 | 18.60893 |
December | 497.00000 | 26.99999 | 14.76413 | 0.76303 | 17.40987 |
Annual Sum or Average | 5943.00000 | 26.99942 | 20.50273 | 0.54087 | 12.84840 |
Minimum of Months | 454.00000 | 26.98620 | 13.59004 | 0.12703 | 5.47271 |
Maximum of Months | 514.00000 | 27.00537 | 26.25568 | 0.87569 | 21.25020 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.56349 | 13.59286 | 0.39288 | 9.22533 |
February | 454.00000 | 27.00000 | 14.85977 | 0.54677 | 11.46674 |
March | 514.00000 | 27.00000 | 16.81472 | 0.62447 | 13.37717 |
April | 485.00000 | 27.00002 | 19.89586 | 0.72634 | 16.24674 |
May | 508.00000 | 27.00014 | 22.18278 | 0.02777 | 5.27992 |
June | 496.00000 | 27.00044 | 25.45344 | 0.14135 | 5.54431 |
July | 497.00000 | 27.00031 | 26.25994 | 0.19937 | 5.92415 |
August | 514.00000 | 27.00327 | 25.71402 | 0.20674 | 6.01446 |
September | 485.00000 | 27.00040 | 25.42117 | 0.07529 | 5.32576 |
October | 502.00000 | 27.00006 | 22.28838 | 0.71679 | 15.90914 |
November | 489.00000 | 27.00001 | 18.39661 | 0.63648 | 13.67090 |
December | 497.00000 | 27.00000 | 14.74086 | 0.54983 | 11.53272 |
Annual Sum or Average | 5943.00000 | 26.96352 | 20.50553 | 0.40201 | 9.93550 |
Minimum of Months | 454.00000 | 26.56349 | 13.59286 | 0.02777 | 5.27992 |
Maximum of Months | 514.00000 | 27.00327 | 26.25994 | 0.72634 | 16.24674 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.40673 | 14.19859 | 0.10399 | 8.24732 |
February | 454.00000 | 26.99131 | 14.86038 | 0.47289 | 9.97362 |
March | 514.00000 | 27.00000 | 16.82101 | 0.54681 | 11.56185 |
April | 485.00000 | 27.00002 | 19.91233 | 0.65738 | 14.37773 |
May | 508.00000 | 26.94850 | 22.23879 | -0.0423 | 5.94119 |
June | 496.00000 | 27.00045 | 25.46753 | 0.12689 | 5.62890 |
July | 497.00000 | 27.00032 | 26.26854 | 0.20218 | 6.06086 |
August | 514.00000 | 27.00374 | 25.72330 | 0.19769 | 6.07517 |
September | 485.00000 | 26.99938 | 25.54232 | 0.02688 | 5.47747 |
October | 502.00000 | 27.00006 | 22.31779 | 0.63862 | 13.77559 |
November | 489.00000 | 27.00001 | 18.40887 | 0.54052 | 11.37117 |
December | 497.00000 | 27.00000 | 14.75119 | 0.46541 | 9.82930 |
Annual Sum or Average | 5943.00000 | 26.86069 | 20.58036 | 0.32637 | 9.01004 |
Minimum of Months | 454.00000 | 25.40673 | 14.19859 | -0.0423 | 5.47747 |
Maximum of Months | 514.00000 | 27.00374 | 26.26854 | 0.65738 | 14.37773 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 35.77523 | 1.02078 | 27.04152 |
February | 454.00000 | 27.00000 | 35.72772 | 1.21281 | 35.89587 |
March | 514.00000 | 27.00000 | 35.46400 | 1.37622 | 44.25334 |
April | 485.00000 | 27.00000 | 35.62532 | 1.52421 | 52.21746 |
May | 508.00000 | 27.00000 | 35.82282 | 0.49773 | 10.21631 |
June | 496.00000 | 27.00000 | 35.63552 | 0.73866 | 16.49704 |
July | 497.00000 | 27.00000 | 35.77197 | 0.95978 | 24.46559 |
August | 514.00000 | 27.00000 | 35.63316 | 1.15312 | 32.99350 |
September | 485.00000 | 27.00000 | 35.77930 | 0.54681 | 11.29901 |
October | 502.00000 | 27.00000 | 35.70149 | 1.27832 | 39.16196 |
November | 489.00000 | 27.00000 | 35.78167 | 1.40719 | 45.89736 |
December | 497.00000 | 27.00000 | 35.43835 | 1.51635 | 51.79035 |
Annual Sum or Average | 5943.00000 | 27.00000 | 35.67876 | 1.10168 | 32.60250 |
Minimum of Months | 454.00000 | 27.00000 | 35.43835 | 0.49773 | 10.21631 |
Maximum of Months | 514.00000 | 27.00000 | 35.82282 | 1.52421 | 52.21746 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.63537 | 13.24447 | 0.06563 | 6.68177 |
February | 454.00000 | 24.07474 | 14.78402 | 0.17876 | 6.44354 |
March | 514.00000 | 24.32024 | 15.62141 | 0.25357 | 6.60362 |
April | 485.00000 | 24.49032 | 18.96183 | 0.31961 | 7.47847 |
May | 508.00000 | 24.51245 | 22.62465 | -0.5096 | 11.43111 |
June | 496.00000 | 24.49195 | 31.38273 | -0.4362 | 9.80202 |
July | 497.00000 | 24.65087 | 35.76566 | -0.3474 | 8.79983 |
August | 514.00000 | 24.52872 | 30.91290 | -0.4116 | 9.47731 |
September | 485.00000 | 24.58733 | 30.44175 | -0.4100 | 9.66754 |
October | 502.00000 | 24.61548 | 21.15363 | 0.37691 | 8.54686 |
November | 489.00000 | 24.57614 | 16.76628 | 0.32942 | 7.76808 |
December | 497.00000 | 24.32001 | 14.04351 | 0.24493 | 6.82364 |
Annual Sum or Average | 5943.00000 | 24.40173 | 22.18950 | -0.0314 | 8.30958 |
Minimum of Months | 454.00000 | 23.63537 | 13.24447 | -0.5096 | 6.44354 |
Maximum of Months | 514.00000 | 24.65087 | 35.76566 | 0.37691 | 11.43111 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.46208 | 14.86528 | 0.01168 | 6.02752 |
February | 454.00000 | 23.86163 | 16.27513 | 0.13320 | 5.88512 |
March | 514.00000 | 24.16217 | 16.98172 | 0.23270 | 6.34030 |
April | 485.00000 | 24.31057 | 20.12794 | 0.30831 | 7.21723 |
May | 508.00000 | 24.30068 | 24.12983 | -0.5528 | 12.02793 |
June | 496.00000 | 24.23510 | 32.69632 | -0.4745 | 10.03820 |
July | 497.00000 | 24.28345 | 36.63666 | -0.4151 | 8.98636 |
August | 514.00000 | 24.23946 | 32.04751 | -0.4546 | 9.57430 |
September | 485.00000 | 24.28023 | 31.92018 | -0.4837 | 10.42495 |
October | 502.00000 | 24.35618 | 22.95967 | 0.33193 | 7.58964 |
November | 489.00000 | 24.32972 | 18.35012 | 0.28193 | 6.91443 |
December | 497.00000 | 24.16561 | 15.45788 | 0.21096 | 6.26241 |
Annual Sum or Average | 5943.00000 | 24.16703 | 23.58420 | -0.0750 | 8.12606 |
Minimum of Months | 454.00000 | 23.46208 | 14.86528 | -0.5528 | 5.88512 |
Maximum of Months | 514.00000 | 24.35618 | 36.63666 | 0.33193 | 12.02793 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.80180 | 16.67774 | -0.4024 | 9.62030 |
February | 454.00000 | 22.37837 | 18.23804 | -0.2444 | 7.57023 |
March | 514.00000 | 23.12547 | 19.26449 | -0.0454 | 6.04889 |
April | 485.00000 | 23.69069 | 22.17496 | 0.12841 | 5.74712 |
May | 508.00000 | 23.95288 | 25.31897 | -0.7035 | 16.30749 |
June | 496.00000 | 24.07202 | 33.39984 | -0.5638 | 12.01649 |
July | 497.00000 | 24.18255 | 37.26221 | -0.4913 | 10.43965 |
August | 514.00000 | 24.16554 | 32.55026 | -0.5307 | 11.19138 |
September | 485.00000 | 24.04596 | 32.82022 | -0.5940 | 13.02361 |
October | 502.00000 | 23.80133 | 24.87488 | 0.17349 | 5.88991 |
November | 489.00000 | 23.25746 | 20.85749 | -0.0058 | 5.80770 |
December | 497.00000 | 22.29752 | 18.12616 | -0.2661 | 7.77916 |
Annual Sum or Average | 5943.00000 | 23.40463 | 25.17258 | -0.2968 | 9.30968 |
Minimum of Months | 454.00000 | 21.80180 | 16.67774 | -0.7035 | 5.74712 |
Maximum of Months | 514.00000 | 24.18255 | 37.26221 | 0.17349 | 16.30749 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.43228 | 16.78134 | -0.7760 | 19.94696 |
February | 454.00000 | 21.01274 | 19.24532 | -0.5995 | 14.36974 |
March | 514.00000 | 21.64191 | 20.80239 | -0.4210 | 10.81717 |
April | 485.00000 | 22.52869 | 24.00580 | -0.1636 | 7.27596 |
May | 508.00000 | 23.30801 | 26.37215 | -0.9363 | 26.21295 |
June | 496.00000 | 23.89885 | 33.63684 | -0.6200 | 14.05121 |
July | 497.00000 | 24.13012 | 37.19996 | -0.4980 | 10.68809 |
August | 514.00000 | 24.07090 | 32.71519 | -0.5614 | 12.14792 |
September | 485.00000 | 23.54833 | 34.05669 | -0.7759 | 19.94093 |
October | 502.00000 | 22.44910 | 27.42168 | -0.1657 | 7.04378 |
November | 489.00000 | 21.39743 | 22.83821 | -0.4731 | 11.81209 |
December | 497.00000 | 20.64643 | 18.77213 | -0.6964 | 17.87716 |
Annual Sum or Average | 5943.00000 | 22.43338 | 26.19259 | -0.5576 | 14.35909 |
Minimum of Months | 454.00000 | 20.43228 | 16.78134 | -0.9363 | 7.04378 |
Maximum of Months | 514.00000 | 24.13012 | 37.19996 | -0.1636 | 26.21295 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.97608 | 14.78828 | -0.6265 | 15.43926 |
February | 454.00000 | 21.75052 | 16.90925 | -0.3987 | 10.29845 |
March | 514.00000 | 22.67581 | 17.81460 | -0.1531 | 6.87438 |
April | 485.00000 | 23.52697 | 20.61274 | 0.08639 | 5.71761 |
May | 508.00000 | 23.81687 | 24.20791 | -0.7414 | 18.31520 |
June | 496.00000 | 24.18813 | 31.98186 | -0.4905 | 10.64255 |
July | 497.00000 | 24.36542 | 35.62327 | -0.3748 | 8.61576 |
August | 514.00000 | 24.22785 | 31.37834 | -0.4703 | 10.16158 |
September | 485.00000 | 23.92290 | 32.05981 | -0.6394 | 15.31192 |
October | 502.00000 | 23.44744 | 23.58246 | 0.07869 | 5.67688 |
November | 489.00000 | 22.66987 | 19.41508 | -0.1463 | 6.66523 |
December | 497.00000 | 21.77824 | 16.30116 | -0.3881 | 9.85556 |
Annual Sum or Average | 5943.00000 | 23.12170 | 23.76431 | -0.3559 | 10.30691 |
Minimum of Months | 454.00000 | 20.97608 | 14.78828 | -0.7414 | 5.67688 |
Maximum of Months | 514.00000 | 24.36542 | 35.62327 | 0.08639 | 18.31520 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.00789 | 13.94772 | -0.6133 | 15.29002 |
February | 454.00000 | 21.82706 | 16.01987 | -0.3657 | 10.45808 |
March | 514.00000 | 22.48354 | 17.06623 | -0.1681 | 7.62552 |
April | 485.00000 | 23.29343 | 20.25814 | 0.07743 | 6.66756 |
May | 508.00000 | 23.70375 | 23.65559 | -0.7045 | 18.04496 |
June | 496.00000 | 24.18367 | 31.67027 | -0.4003 | 10.39057 |
July | 497.00000 | 24.37262 | 35.36308 | -0.2689 | 8.33019 |
August | 514.00000 | 24.12116 | 31.22161 | -0.4114 | 10.00267 |
September | 485.00000 | 23.92394 | 31.55625 | -0.5660 | 14.67956 |
October | 502.00000 | 23.31670 | 23.05001 | 0.08204 | 6.29119 |
November | 489.00000 | 22.35913 | 18.90802 | -0.2009 | 7.34607 |
December | 497.00000 | 21.41587 | 15.79672 | -0.4668 | 11.21041 |
Annual Sum or Average | 5943.00000 | 23.00905 | 23.25320 | -0.3345 | 10.53684 |
Minimum of Months | 454.00000 | 21.00789 | 13.94772 | -0.7045 | 6.29119 |
Maximum of Months | 514.00000 | 24.37262 | 35.36308 | 0.08204 | 18.04496 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.58705 | 13.79173 | -0.4662 | 13.89187 |
February | 454.00000 | 22.52716 | 15.43329 | -0.1796 | 10.04699 |
March | 514.00000 | 22.83173 | 16.69981 | -0.0744 | 7.98638 |
April | 485.00000 | 23.43300 | 20.16964 | 0.10352 | 7.01303 |
May | 508.00000 | 23.63670 | 23.87612 | -0.7551 | 20.47957 |
June | 496.00000 | 24.13091 | 31.85580 | -0.4703 | 11.29907 |
July | 497.00000 | 24.38844 | 35.37774 | -0.3073 | 8.42276 |
August | 514.00000 | 24.27498 | 30.92153 | -0.3585 | 9.13291 |
September | 485.00000 | 24.10114 | 31.14887 | -0.4738 | 13.44267 |
October | 502.00000 | 23.67808 | 22.37313 | 0.19741 | 7.66860 |
November | 489.00000 | 23.02497 | 18.14043 | -0.0253 | 7.91601 |
December | 497.00000 | 22.14557 | 15.23341 | -0.2842 | 10.53893 |
Annual Sum or Average | 5943.00000 | 23.31824 | 22.96522 | -0.2594 | 10.66934 |
Minimum of Months | 454.00000 | 21.58705 | 13.79173 | -0.7551 | 7.01303 |
Maximum of Months | 514.00000 | 24.38844 | 35.37774 | 0.19741 | 20.47957 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.42728 | 13.33873 | -0.4806 | 11.93243 |
February | 454.00000 | 22.69482 | 14.88325 | -0.1231 | 7.94886 |
March | 514.00000 | 23.66909 | 15.59212 | 0.14580 | 6.74975 |
April | 485.00000 | 24.43365 | 18.59580 | 0.40115 | 9.19200 |
May | 508.00000 | 24.13279 | 22.95678 | -0.5188 | 13.36664 |
June | 496.00000 | 24.44540 | 31.09160 | -0.2561 | 7.92354 |
July | 497.00000 | 24.64633 | 34.71120 | -0.0990 | 7.14425 |
August | 514.00000 | 24.53234 | 30.25768 | -0.1644 | 7.12055 |
September | 485.00000 | 24.19740 | 30.84619 | -0.4324 | 11.58960 |
October | 502.00000 | 24.08676 | 21.67364 | 0.29611 | 7.65423 |
November | 489.00000 | 23.74051 | 17.06896 | 0.15895 | 6.76527 |
December | 497.00000 | 23.20310 | 13.95144 | -0.0078 | 6.80281 |
Annual Sum or Average | 5943.00000 | 23.77381 | 22.12601 | -0.0907 | 8.68415 |
Minimum of Months | 454.00000 | 21.42728 | 13.33873 | -0.5188 | 6.74975 |
Maximum of Months | 514.00000 | 24.64633 | 34.71120 | 0.40115 | 13.36664 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.97444 | 14.89809 | -0.9524 | 26.07350 |
February | 454.00000 | 20.44168 | 17.78633 | -0.7764 | 19.18676 |
March | 514.00000 | 20.94823 | 19.49441 | -0.5936 | 14.01066 |
April | 485.00000 | 22.03835 | 23.07221 | -0.2790 | 8.12303 |
May | 508.00000 | 22.99813 | 25.70212 | -1.0345 | 30.58252 |
June | 496.00000 | 23.92674 | 32.70132 | -0.6076 | 13.83915 |
July | 497.00000 | 24.23024 | 35.90385 | -0.4577 | 10.04433 |
August | 514.00000 | 24.03067 | 31.89618 | -0.5813 | 12.96234 |
September | 485.00000 | 23.28580 | 33.42465 | -0.8717 | 24.28165 |
October | 502.00000 | 22.01443 | 25.97686 | -0.2688 | 7.78183 |
November | 489.00000 | 20.85446 | 21.19121 | -0.6106 | 14.69734 |
December | 497.00000 | 20.09831 | 17.49326 | -0.8686 | 23.02736 |
Annual Sum or Average | 5943.00000 | 22.08315 | 25.00208 | -0.6583 | 17.04700 |
Minimum of Months | 454.00000 | 19.97444 | 14.89809 | -1.0345 | 7.78183 |
Maximum of Months | 514.00000 | 24.23024 | 35.90385 | -0.2688 | 30.58252 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.03768 | 13.64639 | -0.9247 | 24.92528 |
February | 385.00000 | 20.71206 | 16.26582 | -0.6923 | 17.41713 |
March | 433.00000 | 21.25820 | 17.71456 | -0.4996 | 12.74345 |
April | 410.00000 | 22.43679 | 21.19748 | -0.1494 | 8.16516 |
May | 430.00000 | 23.13473 | 24.27484 | -0.9235 | 27.22057 |
June | 418.00000 | 24.11437 | 31.52273 | -0.4493 | 12.44600 |
July | 422.00000 | 24.48097 | 34.76381 | -0.2637 | 9.02852 |
August | 433.00000 | 24.17385 | 30.60028 | -0.4328 | 11.30802 |
September | 410.00000 | 23.52863 | 32.01901 | -0.7240 | 21.17758 |
October | 427.00000 | 22.26744 | 24.21586 | -0.1843 | 7.41340 |
November | 417.00000 | 20.98789 | 19.54499 | -0.5677 | 13.48322 |
December | 422.00000 | 20.08086 | 16.10451 | -0.8637 | 22.75884 |
Annual Sum or Average | 5034.00000 | 22.27674 | 23.52006 | -0.5561 | 15.67403 |
Minimum of Months | 385.00000 | 20.03768 | 13.64639 | -0.9247 | 7.41340 |
Maximum of Months | 433.00000 | 24.48097 | 34.76381 | -0.1494 | 27.22057 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.06712 | 13.69747 | -0.6313 | 17.90960 |
February | 454.00000 | 21.99189 | 15.71930 | -0.3328 | 12.88035 |
March | 514.00000 | 22.16239 | 17.45023 | -0.2474 | 10.47553 |
April | 485.00000 | 22.83128 | 21.24409 | -0.0482 | 8.00731 |
May | 508.00000 | 23.27035 | 24.54920 | -0.8869 | 26.02816 |
June | 496.00000 | 23.95508 | 32.25482 | -0.5460 | 13.59306 |
July | 497.00000 | 24.32962 | 35.42248 | -0.3520 | 9.39383 |
August | 514.00000 | 24.20390 | 30.94739 | -0.4085 | 10.58909 |
September | 485.00000 | 23.91267 | 31.52377 | -0.5386 | 16.24519 |
October | 502.00000 | 23.28384 | 23.16342 | 0.10376 | 8.10511 |
November | 489.00000 | 22.39505 | 18.81607 | -0.1922 | 10.06767 |
December | 497.00000 | 21.22148 | 15.94102 | -0.5452 | 15.91284 |
Annual Sum or Average | 5943.00000 | 22.89159 | 23.44062 | -0.3868 | 13.28651 |
Minimum of Months | 454.00000 | 21.06712 | 13.69747 | -0.8869 | 8.00731 |
Maximum of Months | 514.00000 | 24.32962 | 35.42248 | 0.10376 | 26.02816 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.29511 | 13.88880 | -0.8495 | 22.06353 |
February | 454.00000 | 20.94934 | 16.37061 | -0.6148 | 15.50168 |
March | 514.00000 | 21.42718 | 18.00223 | -0.4420 | 11.58881 |
April | 485.00000 | 22.55576 | 21.45008 | -0.1088 | 7.56799 |
May | 508.00000 | 23.30070 | 24.39257 | -0.8452 | 24.99808 |
June | 496.00000 | 23.99972 | 32.15470 | -0.4822 | 12.54881 |
July | 497.00000 | 24.36865 | 35.38625 | -0.2993 | 8.85308 |
August | 514.00000 | 24.15793 | 31.11347 | -0.4249 | 10.88258 |
September | 485.00000 | 23.47069 | 32.30377 | -0.7235 | 21.08076 |
October | 502.00000 | 22.40495 | 24.36109 | -0.1369 | 7.22616 |
November | 489.00000 | 21.32513 | 19.71063 | -0.4682 | 11.75399 |
December | 497.00000 | 20.41670 | 16.32122 | -0.7604 | 19.30290 |
Annual Sum or Average | 5943.00000 | 22.40063 | 23.83090 | -0.5128 | 14.44567 |
Minimum of Months | 454.00000 | 20.29511 | 13.88880 | -0.8495 | 7.22616 |
Maximum of Months | 514.00000 | 24.36865 | 35.38625 | -0.1088 | 24.99808 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.60047 | 14.98074 | -1.1112 | 33.13470 |
February | 454.00000 | 19.98493 | 17.91367 | -0.9452 | 25.93102 |
March | 514.00000 | 20.35341 | 19.81441 | -0.7921 | 20.25857 |
April | 485.00000 | 21.13527 | 23.86628 | -0.5221 | 13.17423 |
May | 508.00000 | 22.33370 | 26.40642 | -1.2737 | 40.96980 |
June | 496.00000 | 23.60584 | 33.19843 | -0.7099 | 18.14472 |
July | 497.00000 | 24.07632 | 36.15534 | -0.4973 | 11.54343 |
August | 514.00000 | 23.76976 | 32.34422 | -0.6624 | 16.20706 |
September | 485.00000 | 22.64169 | 34.46608 | -1.0962 | 34.61384 |
October | 502.00000 | 20.97393 | 27.24769 | -0.5470 | 13.25473 |
November | 489.00000 | 20.10733 | 21.97110 | -0.8518 | 22.74555 |
December | 497.00000 | 19.77900 | 17.55187 | -1.0235 | 29.41063 |
Annual Sum or Average | 5943.00000 | 21.54387 | 25.53415 | -0.8355 | 23.26601 |
Minimum of Months | 454.00000 | 19.60047 | 14.98074 | -1.2737 | 11.54343 |
Maximum of Months | 514.00000 | 24.07632 | 36.15534 | -0.4973 | 40.96980 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.81593 | 14.56390 | -1.0418 | 30.02695 |
February | 454.00000 | 20.29380 | 17.16841 | -0.8392 | 22.20894 |
March | 514.00000 | 20.80673 | 18.85442 | -0.6495 | 16.87957 |
April | 485.00000 | 21.92060 | 22.24772 | -0.2982 | 11.00714 |
May | 508.00000 | 22.83104 | 25.07399 | -1.0389 | 31.79701 |
June | 496.00000 | 23.97237 | 31.92352 | -0.4781 | 13.65837 |
July | 497.00000 | 24.36235 | 35.16421 | -0.2656 | 9.11084 |
August | 514.00000 | 24.04598 | 31.17577 | -0.4450 | 12.04135 |
September | 485.00000 | 23.22684 | 32.95537 | -0.8321 | 25.72101 |
October | 502.00000 | 21.53675 | 25.92691 | -0.3834 | 10.65267 |
November | 489.00000 | 20.30172 | 21.24414 | -0.7817 | 20.19865 |
December | 497.00000 | 19.86295 | 17.09143 | -0.9858 | 27.85714 |
Annual Sum or Average | 5943.00000 | 21.92819 | 24.48948 | -0.6691 | 19.24284 |
Minimum of Months | 454.00000 | 19.81593 | 14.56390 | -1.0418 | 9.11084 |
Maximum of Months | 514.00000 | 24.36235 | 35.16421 | -0.2656 | 31.79701 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.40977 | 14.26083 | -0.8459 | 24.27235 |
February | 454.00000 | 21.31176 | 16.33984 | -0.5421 | 17.05261 |
March | 514.00000 | 21.47272 | 18.18276 | -0.4600 | 14.78545 |
April | 485.00000 | 22.13153 | 22.13780 | -0.2478 | 11.09308 |
May | 508.00000 | 22.79704 | 25.25578 | -1.0709 | 33.75489 |
June | 496.00000 | 23.70582 | 32.64523 | -0.6277 | 17.17706 |
July | 497.00000 | 24.20088 | 35.63801 | -0.3827 | 10.73858 |
August | 514.00000 | 24.03417 | 31.28096 | -0.4606 | 12.79035 |
September | 485.00000 | 23.51016 | 32.35558 | -0.6926 | 22.73601 |
October | 502.00000 | 22.47340 | 24.49303 | -0.1232 | 10.05763 |
November | 489.00000 | 21.40101 | 20.08349 | -0.4760 | 14.60593 |
December | 497.00000 | 20.49412 | 16.64077 | -0.7774 | 22.38129 |
Annual Sum or Average | 5943.00000 | 22.33672 | 24.15476 | -0.5597 | 17.63870 |
Minimum of Months | 454.00000 | 20.40977 | 14.26083 | -1.0709 | 10.05763 |
Maximum of Months | 514.00000 | 24.20088 | 35.63801 | -0.1232 | 33.75489 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.89077 | 14.37403 | -1.0099 | 28.80459 |
February | 454.00000 | 20.49882 | 16.80817 | -0.7704 | 20.40039 |
March | 514.00000 | 20.91033 | 18.55131 | -0.6118 | 15.97160 |
April | 485.00000 | 21.88328 | 22.24403 | -0.2954 | 10.37644 |
May | 508.00000 | 22.84610 | 25.01490 | -1.0177 | 32.36313 |
June | 496.00000 | 23.75085 | 32.50397 | -0.5620 | 15.92559 |
July | 497.00000 | 24.24141 | 35.58895 | -0.3295 | 10.07742 |
August | 514.00000 | 23.97375 | 31.46050 | -0.4815 | 13.15760 |
September | 485.00000 | 23.02943 | 33.14848 | -0.8842 | 28.27307 |
October | 502.00000 | 21.63464 | 25.55900 | -0.3486 | 10.25987 |
November | 489.00000 | 20.60731 | 20.73288 | -0.6869 | 17.69606 |
December | 497.00000 | 20.00696 | 16.81361 | -0.9194 | 25.41398 |
Annual Sum or Average | 5943.00000 | 21.95187 | 24.44232 | -0.6593 | 19.05127 |
Minimum of Months | 454.00000 | 19.89077 | 14.37403 | -1.0177 | 10.07742 |
Maximum of Months | 514.00000 | 24.24141 | 35.58895 | -0.2954 | 32.36313 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.138204E+09 | 1950.88 | 26-JAN-05:36 | 19.85 | 0.781973E+09 | 0.00 | 0.920178E+09 | 0.15 | 5.80 | 31-JAN-02:20 | 0.00 | 0.00 |
February | 0.917138E+09 | 42857.25 | 27-FEB-13:40 | 37.12 | 0.612117E+10 | 0.00 | 0.703831E+10 | 0.32 | 7.93 | 27-FEB-13:40 | 0.00 | 0.00 |
March | 0.416580E+09 | 5342.06 | 14-MAR-13:30 | 57.85 | 0.236237E+10 | 0.00 | 0.277895E+10 | 0.44 | 5.80 | 04-MAR-07:00 | 0.00 | 0.00 |
April | 0.741554E+10 | 64620.44 | 07-APR-14:20 | 114.58 | 0.508683E+11 | 0.00 | 0.582838E+11 | 0.98 | 8.47 | 06-APR-14:10 | 0.00 | 0.00 |
May | 0.207106E+11 | 70338.10 | 19-MAY-15:30 | 200.83 | 0.151985E+12 | 0.00 | 0.172696E+12 | 1.79 | 8.50 | 30-MAY-15:00 | 0.00 | 0.00 |
June | 0.528632E+11 | 83927.11 | 30-JUN-16:00 | 377.67 | 0.403773E+12 | 0.00 | 0.456636E+12 | 3.68 | 8.52 | 26-JUN-14:10 | 0.00 | 0.00 |
July | 0.819805E+11 | 100538.38 | 17-JUL-15:30 | 521.48 | 0.641767E+12 | 0.00 | 0.723748E+12 | 5.07 | 8.54 | 27-JUL-12:20 | 0.00 | 0.00 |
August | 0.710438E+11 | 89559.49 | 07-AUG-15:40 | 491.38 | 0.554683E+12 | 0.00 | 0.625727E+12 | 4.69 | 8.54 | 29-AUG-10:50 | 0.00 | 0.00 |
September | 0.387834E+11 | 143292.67 | 07-SEP-15:00 | 294.73 | 0.295140E+12 | 0.00 | 0.333923E+12 | 2.85 | 8.56 | 08-SEP-14:00 | 0.00 | 0.00 |
October | 0.114552E+11 | 63324.72 | 16-OCT-12:30 | 146.04 | 0.827236E+11 | 0.00 | 0.941788E+11 | 1.24 | 8.50 | 16-OCT-14:40 | 0.00 | 0.00 |
November | 0.120787E+10 | 23418.17 | 17-NOV-17:00 | 69.61 | 0.674005E+10 | 0.00 | 0.794792E+10 | 0.55 | 5.79 | 10-NOV-06:40 | 0.00 | 0.00 |
December | 0.226592E+09 | 1995.26 | 26-DEC-05:17 | 32.57 | 0.128376E+10 | 0.00 | 0.151036E+10 | 0.25 | 5.80 | 11-DEC-06:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.287159E+12 | 2363.71 | 0.219823E+13 | 0.00 | 0.248539E+13 | 1.84 | 0.00 | 0.00 | ||||
Minimum of Months | 0.138204E+09 | 1950.88 | 19.85 | 0.781973E+09 | 0.00 | 0.920178E+09 | 0.15 | 5.79 | 0.00 | 0.00 | ||
Maximum of Months | 0.819805E+11 | 143292.67 | 521.48 | 0.641767E+12 | 0.00 | 0.723748E+12 | 5.07 | 8.56 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.123862E+10 | 70338.10 | 19-MAY-15:30 | 5.17 | 0.102047E+11 | 0.00 | 0.114433E+11 | 0.06 | 8.41 | 19-MAY-12:20 | 0.00 | 0.00 |
June | 0.151442E+11 | 83927.11 | 30-JUN-16:00 | 60.50 | 0.123690E+12 | 0.00 | 0.138834E+12 | 0.69 | 8.46 | 30-JUN-10:50 | 0.00 | 0.00 |
July | 0.324926E+11 | 100538.38 | 17-JUL-15:30 | 125.43 | 0.267189E+12 | 0.00 | 0.299682E+12 | 1.39 | 8.45 | 06-JUL-15:20 | 0.00 | 0.00 |
August | 0.262256E+11 | 89559.49 | 07-AUG-15:40 | 102.33 | 0.216705E+12 | 0.00 | 0.242931E+12 | 1.14 | 8.47 | 08-AUG-09:20 | 0.00 | 0.00 |
September | 0.771557E+10 | 143292.67 | 07-SEP-15:00 | 30.38 | 0.627175E+11 | 0.00 | 0.704330E+11 | 0.34 | 8.53 | 07-SEP-12:50 | 0.00 | 0.00 |
October | 0.374304E+09 | 63171.42 | 18-OCT-14:30 | 1.67 | 0.309155E+10 | 0.00 | 0.346586E+10 | 0.02 | 8.34 | 18-OCT-15:50 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.831909E+11 | 325.48 | 0.683598E+12 | 0.00 | 0.766789E+12 | 0.31 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.324926E+11 | 143292.67 | 125.43 | 0.267189E+12 | 0.00 | 0.299682E+12 | 1.39 | 8.53 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.298524E+09 | 721.22 | 875.80 | 13-JAN-16:10 | 23234.04 | 13-JAN-16:30 | 18.76 | 18.33 | 2.97 |
February | 0.233917E+10 | 672.00 | 12476.23 | 27-FEB-13:10 | 60677.34 | 26-FEB-17:30 | 21.62 | 18.34 | 3.07 |
March | 0.400753E+10 | 744.00 | 8921.65 | 14-MAR-14:00 | 94056.51 | 31-MAR-23:40 | 24.63 | 18.33 | 3.07 |
April | 0.109908E+11 | 720.00 | 12476.23 | 01-APR-13:30 | 123243.66 | 16-APR-18:03 | 27.93 | 18.53 | 3.07 |
May | 0.924587E+10 | 744.00 | 12476.23 | 02-MAY-11:40 | 57255.83 | 31-MAY-24:00 | 21.29 | 18.94 | 3.07 |
June | 0.205857E+11 | 720.00 | 12476.23 | 01-JUN-14:30 | 87770.70 | 30-JUN-23:42 | 26.14 | 20.77 | 3.07 |
July | 0.289450E+11 | 744.00 | 12476.23 | 01-JUL-00:10 | 114891.92 | 16-JUL-19:01 | 31.65 | 23.51 | 3.07 |
August | 0.291203E+11 | 744.00 | 12476.23 | 01-AUG-00:03 | 139075.69 | 05-AUG-19:32 | 33.23 | 22.79 | 3.07 |
September | 0.146731E+11 | 720.00 | 12476.23 | 01-SEP-00:03 | 51735.43 | 30-SEP-23:50 | 22.67 | 20.07 | 3.07 |
October | 0.839374E+10 | 744.00 | 12476.23 | 12-OCT-10:30 | 71543.16 | 15-OCT-17:02 | 23.06 | 18.57 | 3.07 |
November | 0.592124E+10 | 720.00 | 12476.23 | 04-NOV-13:30 | 85539.49 | 03-NOV-16:00 | 24.66 | 18.33 | 3.07 |
December | 0.428405E+10 | 744.00 | 8300.00 | 10-DEC-02:00 | 106613.13 | 06-DEC-16:10 | 26.39 | 18.33 | 3.07 |
Annual Sum or Average | 0.138805E+12 | 8737.22 | 25.20 | 19.58 | 3.06 | ||||
Minimum of Months | 0.298524E+09 | 672.00 | 875.80 | 23234.04 | 18.76 | 18.33 | 2.97 | ||
Maximum of Months | 0.291203E+11 | 744.00 | 12476.23 | 139075.69 | 33.23 | 23.51 | 3.07 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 199620.07 | 26-JAN-06:50 | 20.98 | 20.98 | 0.09 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 393963.00 | 27-FEB-13:40 | 21.05 | 21.03 | 0.69 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 199646.74 | 22-MAR-06:00 | 20.95 | 20.94 | 0.71 |
April | 20374050.54 | 39.22 | 781.02 | 06-APR-16:00 | 747203.33 | 07-APR-13:00 | 21.12 | 21.01 | 4.91 |
May | 0.160215E+09 | 127.34 | 1966.60 | 19-MAY-12:20 | 974178.55 | 19-MAY-15:30 | 21.43 | 21.08 | 11.00 |
June | 0.175099E+10 | 292.89 | 13509.08 | 06-JUN-14:50 | 1049166.44 | 30-JUN-14:40 | 22.07 | 21.07 | 24.02 |
July | 0.345680E+10 | 422.86 | 13509.08 | 01-JUL-13:10 | 1043789.72 | 26-JUL-10:50 | 22.65 | 21.12 | 32.69 |
August | 0.137798E+10 | 365.79 | 13509.08 | 05-AUG-11:30 | 1045210.21 | 04-AUG-14:10 | 22.41 | 21.06 | 29.29 |
September | 0.120487E+10 | 219.83 | 13509.08 | 02-SEP-11:00 | 1124357.28 | 07-SEP-15:00 | 21.87 | 21.18 | 18.16 |
October | 46433009.34 | 66.14 | 734.60 | 18-OCT-16:10 | 908482.05 | 18-OCT-14:00 | 21.27 | 21.08 | 6.55 |
November | 104739.14 | 2.50 | 24.29 | 17-NOV-17:00 | 199816.55 | 02-NOV-05:02 | 21.06 | 21.04 | 1.26 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 199579.21 | 26-DEC-03:45 | 21.05 | 21.05 | 0.23 |
Annual Sum or Average | 0.801777E+10 | 1536.57 | 21.50 | 21.05 | 10.87 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 199579.21 | 20.95 | 20.94 | 0.09 | ||
Maximum of Months | 0.345680E+10 | 422.86 | 13509.08 | 1124357.28 | 22.65 | 21.18 | 32.69 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 20.98 | 20.98 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 21.05 | 21.05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 20.95 | 20.95 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.12 | 21.12 | 0.00 |
May | 18733994.39 | 3.67 | 1966.60 | 19-MAY-12:20 | 974178.55 | 19-MAY-15:30 | 21.43 | 21.41 | 0.25 |
June | 0.876708E+09 | 42.83 | 13509.08 | 06-JUN-14:50 | 1049166.44 | 30-JUN-14:40 | 22.07 | 21.83 | 3.01 |
July | 0.190064E+10 | 98.17 | 13509.08 | 13-JUL-13:10 | 1043789.72 | 26-JUL-10:50 | 22.65 | 22.11 | 6.67 |
August | 0.626937E+09 | 82.67 | 13509.08 | 05-AUG-13:40 | 1045210.21 | 04-AUG-14:10 | 22.41 | 21.95 | 5.62 |
September | 0.488766E+09 | 21.50 | 13509.08 | 02-SEP-11:00 | 1124357.28 | 07-SEP-15:00 | 21.87 | 21.75 | 1.51 |
October | 654871.94 | 0.33 | 582.44 | 18-OCT-14:30 | 899147.23 | 18-OCT-14:30 | 21.27 | 21.26 | 0.02 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.06 | 21.06 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.05 | 21.05 | 0.00 |
Annual Sum or Average | 0.391244E+10 | 249.17 | 21.50 | 21.38 | 1.44 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.95 | 20.95 | 0.00 | ||
Maximum of Months | 0.190064E+10 | 98.17 | 13509.08 | 1124357.28 | 22.65 | 22.11 | 6.67 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.867789E+12 | 0.00 | 577.98 | 1937802.61 | 09-JAN-07:10 | 0.00 | 33.65 | 69.91 | 1.81 | 0.00 | 0.10 | 0.60 | 09-JAN-07:10 |
February | 0.462036E+12 | 0.00 | 440.41 | 1754014.61 | 07-FEB-06:01 | 0.00 | 29.78 | 62.49 | 0.99 | 0.00 | 0.06 | 0.55 | 07-FEB-06:01 |
March | 0.270720E+12 | 0.00 | 435.58 | 1827513.10 | 07-MAR-06:01 | 0.00 | 27.38 | 58.04 | 0.49 | 0.00 | 0.03 | 0.57 | 07-MAR-06:01 |
April | 0.729954E+11 | 0.00 | 239.60 | 1259582.69 | 01-APR-05:01 | 0.00 | 24.39 | 42.70 | 0.13 | 0.00 | 0.01 | 0.39 | 01-APR-05:01 |
May | 0.453567E+11 | 0.00 | 156.63 | 1213159.16 | 09-MAY-05:01 | 0.00 | 24.24 | 35.78 | 0.08 | 0.00 | 0.01 | 0.38 | 09-MAY-05:01 |
June | 0.142918E+10 | 0.00 | 27.56 | 122299.68 | 16-JUN-07:00 | 0.00 | 23.59 | 25.74 | 0.00 | 0.00 | 0.00 | 0.04 | 16-JUN-07:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 23.56 | 23.56 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 94606098.91 | 0.00 | 7.00 | 118193.97 | 18-AUG-05:02 | 0.00 | 23.82 | 24.34 | 0.00 | 0.00 | 0.00 | 0.04 | 18-AUG-05:02 |
September | 0.107760E+11 | 0.00 | 91.31 | 455337.18 | 19-SEP-05:03 | 0.00 | 23.51 | 30.65 | 0.02 | 0.00 | 0.00 | 0.14 | 19-SEP-05:03 |
October | 0.539203E+11 | 0.00 | 236.06 | 1230036.50 | 11-OCT-05:01 | 0.00 | 24.14 | 41.63 | 0.09 | 0.00 | 0.01 | 0.38 | 11-OCT-05:01 |
November | 0.218549E+12 | 0.00 | 415.25 | 1527465.53 | 27-NOV-06:02 | 0.00 | 26.98 | 57.38 | 0.40 | 0.00 | 0.03 | 0.47 | 27-NOV-06:02 |
December | 0.557529E+12 | 0.00 | 548.53 | 1727477.61 | 27-DEC-06:01 | 0.00 | 31.64 | 67.78 | 1.08 | 0.00 | 0.06 | 0.54 | 27-DEC-06:01 |
Annual Sum or Average | 0.256120E+13 | 0.00 | 3175.91 | 0.00 | 26.38 | 44.92 | 0.42 | 0.00 | 0.03 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.51 | 23.56 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.867789E+12 | 0.00 | 577.98 | 1937802.61 | 0.00 | 33.65 | 69.91 | 1.81 | 0.00 | 0.10 | 0.60 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 18.76 | 18.76 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 21.62 | 21.62 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 24.63 | 24.63 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 27.93 | 27.93 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 21.29 | 21.29 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 26.14 | 26.14 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 31.65 | 31.65 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 33.23 | 33.23 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 22.67 | 22.67 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 23.06 | 23.06 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 24.66 | 24.66 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 26.39 | 26.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 25.20 | 25.20 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.76 | 18.76 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.23 | 33.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.547329E+09 | 0.00 | 11.04 | 0.547329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36647.46 | 27-FEB-15:30 | 36647.46 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 |
March | 27485668.80 | 0.00 | 3.00 | 27485668.80 | 0.00 | 0.00 | 0.00 | 0.00 | 5892.17 | 14-MAR-13:30 | 5892.17 | 14-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.572886E+10 | 0.00 | 77.50 | 0.572886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72757.10 | 07-APR-14:00 | 72757.10 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.157044E+11 | 0.00 | 167.92 | 0.157044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97046.87 | 19-MAY-15:20 | 97046.87 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.526794E+11 | 0.00 | 354.38 | 0.526289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113381.43 | 29-JUN-14:40 | 113381.43 | 29-JUN-14:40 | 0.00 | 0.00 | 0.00 |
July | 0.911420E+11 | 0.00 | 493.84 | 0.909781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139001.18 | 17-JUL-15:20 | 139001.18 | 17-JUL-15:20 | 0.00 | 0.00 | 0.00 |
August | 0.820902E+11 | 0.00 | 470.01 | 0.820902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135935.70 | 07-AUG-15:30 | 135935.70 | 07-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.339074E+11 | 0.00 | 260.66 | 0.327995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170322.07 | 07-SEP-15:00 | 109662.48 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.909578E+10 | 0.00 | 107.45 | 0.909578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90044.00 | 18-OCT-15:50 | 90044.00 | 18-OCT-15:50 | 0.00 | 0.00 | 0.00 |
November | 0.449206E+09 | 0.00 | 24.03 | 0.449206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15081.60 | 17-NOV-17:00 | 15081.60 | 17-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 441.66 | 0.00 | 0.35 | 441.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 | 20-DEC-06:15 | 0.70 | 20-DEC-06:15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.291372E+12 | 0.00 | 1970.17 | 0.290050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.911420E+11 | 0.00 | 493.84 | 0.909781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170322.07 | 139001.18 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 44594.84 | 0.00 | 18.88 | 44594.84 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 | 02-JAN-06:03 | 3.73 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.381850E+10 | 0.00 | 35.24 | 0.381850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 261458.64 | 27-FEB-13:40 | 261458.64 | 27-FEB-13:40 | 0.00 | 0.00 | 0.00 |
March | 34632748.16 | 0.00 | 57.01 | 34632748.16 | 0.00 | 0.00 | 0.00 | 0.00 | 9028.05 | 14-MAR-13:30 | 9028.05 | 14-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.382635E+11 | 0.00 | 104.40 | 0.382635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 527069.65 | 06-APR-16:00 | 527069.65 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.131126E+12 | 0.00 | 186.87 | 0.131126E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 902728.77 | 19-MAY-15:30 | 902728.77 | 19-MAY-15:30 | 0.00 | 0.00 | 0.00 |
June | 0.438724E+12 | 0.00 | 334.22 | 0.438325E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1054031.85 | 29-JUN-14:50 | 1054031.85 | 29-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.741519E+12 | 0.00 | 424.73 | 0.740629E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1234778.66 | 19-JUL-05:03 | 1222648.89 | 17-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.638843E+12 | 0.00 | 390.81 | 0.638843E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1152497.44 | 10-AUG-15:40 | 1152497.44 | 10-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.291560E+12 | 0.00 | 264.91 | 0.281647E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1554962.33 | 07-SEP-15:00 | 994510.22 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.678401E+11 | 0.00 | 133.17 | 0.678401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 719539.77 | 18-OCT-15:10 | 719539.77 | 18-OCT-15:10 | 0.00 | 0.00 | 0.00 |
November | 0.316546E+10 | 0.00 | 64.38 | 0.316546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108144.83 | 03-NOV-14:00 | 108144.83 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 52811.18 | 0.00 | 30.78 | 52811.18 | 0.00 | 0.00 | 0.00 | 0.00 | 2.27 | 22-DEC-06:10 | 2.27 | 22-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235489E+13 | 0.00 | 2045.41 | 0.234369E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 44594.84 | 0.00 | 18.88 | 44594.84 | 0.00 | 0.00 | 0.00 | 0.00 | 2.27 | 2.27 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.741519E+12 | 0.00 | 424.73 | 0.740629E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1554962.33 | 1222648.89 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 142480.92 | 0.00 | 0.87 | 142480.92 | 0.00 | 0.00 | 0.00 | 0.00 | 880.52 | 17-JAN-04:52 | 880.52 | 17-JAN-04:52 | 0.00 | 0.00 | 0.00 |
February | 0.279553E+09 | 0.00 | 11.30 | 0.279553E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21580.44 | 26-FEB-14:51 | 21580.44 | 26-FEB-14:51 | 0.00 | 0.00 | 0.00 |
March | 1418806.73 | 0.00 | 1.50 | 1418806.73 | 0.00 | 0.00 | 0.00 | 0.00 | 341.26 | 14-MAR-13:40 | 341.26 | 14-MAR-13:40 | 0.00 | 0.00 | 0.00 |
April | 0.342778E+10 | 0.00 | 65.46 | 0.342778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51639.34 | 06-APR-16:00 | 51639.34 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.135838E+11 | 0.00 | 155.01 | 0.135838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109549.13 | 19-MAY-15:30 | 109549.13 | 19-MAY-15:30 | 0.00 | 0.00 | 0.00 |
June | 0.485946E+11 | 0.00 | 323.02 | 0.485398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127291.63 | 29-JUN-15:00 | 127291.63 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.829818E+11 | 0.00 | 422.62 | 0.828859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 154040.54 | 17-JUL-15:30 | 154040.54 | 17-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.691476E+11 | 0.00 | 383.56 | 0.691476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140782.15 | 07-AUG-15:50 | 140782.15 | 07-AUG-15:50 | 0.00 | 0.00 | 0.00 |
September | 0.296298E+11 | 0.00 | 241.42 | 0.286470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159383.50 | 07-SEP-15:20 | 115274.24 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.570456E+10 | 0.00 | 93.99 | 0.570456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71885.44 | 18-OCT-15:00 | 71885.44 | 18-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.238240E+09 | 0.00 | 15.90 | 0.238240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8954.08 | 04-NOV-14:00 | 8954.08 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 194737.66 | 0.00 | 1.23 | 194737.66 | 0.00 | 0.00 | 0.00 | 0.00 | 865.93 | 26-DEC-05:17 | 865.93 | 26-DEC-05:17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.253589E+12 | 0.00 | 1715.86 | 0.252456E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 142480.92 | 0.00 | 0.87 | 142480.92 | 0.00 | 0.00 | 0.00 | 0.00 | 341.26 | 341.26 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.829818E+11 | 0.00 | 422.62 | 0.828859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159383.50 | 154040.54 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 330121.22 | 0.00 | 0.19 | 330121.22 | 0.00 | 0.00 | 0.00 | 0.00 | 4738.22 | 24-JAN-05:01 | 4738.22 | 24-JAN-05:01 | 0.00 | 0.00 | 0.00 |
February | 0.253499E+09 | 0.00 | 5.50 | 0.253499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21750.05 | 27-FEB-15:00 | 21750.05 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 27403.46 | 0.00 | 0.17 | 27403.46 | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 03-MAR-07:50 | 45.67 | 03-MAR-07:50 | 0.00 | 0.00 | 0.00 |
April | 0.210276E+10 | 0.00 | 39.41 | 0.210276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42581.56 | 07-APR-14:00 | 42581.56 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.773591E+10 | 0.00 | 105.03 | 0.773591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51429.40 | 19-MAY-15:00 | 51429.40 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.270330E+11 | 0.00 | 229.36 | 0.270222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61219.33 | 26-JUN-11:00 | 61219.33 | 26-JUN-11:00 | 0.00 | 0.00 | 0.00 |
July | 0.462436E+11 | 0.00 | 318.95 | 0.462110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91893.32 | 19-JUL-05:03 | 75528.16 | 17-JUL-13:10 | 0.00 | 0.00 | 0.00 |
August | 0.423222E+11 | 0.00 | 314.42 | 0.423222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93262.07 | 06-AUG-19:20 | 93262.07 | 06-AUG-19:20 | 0.00 | 0.00 | 0.00 |
September | 0.177612E+11 | 0.00 | 180.80 | 0.174169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108678.16 | 04-SEP-16:51 | 108678.16 | 04-SEP-16:51 | 0.00 | 0.00 | 0.00 |
October | 0.521742E+10 | 0.00 | 64.32 | 0.521742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51799.87 | 18-OCT-14:00 | 51799.87 | 18-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 72775089.87 | 0.00 | 5.33 | 72775089.87 | 0.00 | 0.00 | 0.00 | 0.00 | 21633.98 | 17-NOV-06:03 | 21633.98 | 17-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 96326.67 | 0.00 | 0.67 | 96326.67 | 0.00 | 0.00 | 0.00 | 0.00 | 94.48 | 27-DEC-12:40 | 94.48 | 27-DEC-12:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148743E+12 | 0.00 | 1264.13 | 0.148355E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 27403.46 | 0.00 | 0.17 | 27403.46 | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 45.67 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.462436E+11 | 0.00 | 318.95 | 0.462110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108678.16 | 108678.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.264833E+10 | 0.641557E+09 | 721.22 | 0.264802E+10 | 313916.02 | 0.00 | 0.27 | 01-JAN-16:05 | 0.00 | 07-JAN-17:23 | 2162.16 | 01-JAN-16:05 | 2155.50 | 01-JAN-16:05 | 13.35 | 02-JAN-07:10 | 467.57 | 01-JAN-16:05 | 0.00 |
February | 0.802248E+10 | 0.177100E+10 | 672.00 | 0.802248E+10 | 0.00 | 0.00 | 0.59 | 26-FEB-17:23 | 0.26 | 01-FEB-07:03 | 4825.50 | 26-FEB-17:27 | 4825.50 | 26-FEB-17:27 | 0.00 | 21-FEB-17:20 | 1033.07 | 26-FEB-17:23 | 0.00 |
March | 0.147958E+11 | 0.307238E+10 | 744.00 | 0.147958E+11 | 0.00 | 0.00 | 0.83 | 31-MAR-24:00 | 0.54 | 06-MAR-07:05 | 7437.19 | 31-MAR-24:00 | 7437.19 | 31-MAR-24:00 | 0.00 | 26-MAR-12:50 | 1467.31 | 31-MAR-24:00 | 0.00 |
April | 0.198848E+11 | 0.392266E+10 | 720.00 | 0.198763E+11 | 8470201.21 | 0.00 | 1.00 | 16-APR-17:22 | 0.31 | 30-APR-24:00 | 8783.45 | 22-APR-18:10 | 8783.45 | 22-APR-18:10 | 129.19 | 17-APR-16:10 | 1937.15 | 16-APR-17:22 | 0.00 |
May | 0.546152E+10 | 0.123700E+10 | 744.00 | 0.543650E+10 | 25021272.50 | 0.00 | 0.49 | 31-MAY-24:00 | 0.14 | 08-MAY-07:00 | 4090.36 | 31-MAY-24:00 | 4090.36 | 31-MAY-24:00 | 148.74 | 30-MAY-09:30 | 855.49 | 31-MAY-24:00 | 0.00 |
June | 0.107509E+11 | 0.239941E+10 | 720.00 | 0.106576E+11 | 93271658.03 | 0.00 | 0.68 | 30-JUN-23:42 | 0.40 | 17-JUN-06:30 | 6002.97 | 30-JUN-23:57 | 5979.06 | 30-JUN-24:00 | 310.32 | 06-JUN-16:40 | 1419.40 | 29-JUN-15:00 | 0.00 |
July | 0.164176E+11 | 0.382328E+10 | 744.00 | 0.163082E+11 | 0.109399E+09 | 0.00 | 0.87 | 16-JUL-18:41 | 0.63 | 08-JUL-06:10 | 7854.63 | 31-JUL-23:40 | 7854.63 | 31-JUL-23:40 | 324.46 | 03-JUL-16:50 | 2284.21 | 17-JUL-16:00 | 0.00 |
August | 0.212765E+11 | 0.469055E+10 | 744.00 | 0.211965E+11 | 79973018.00 | 0.00 | 1.00 | 04-AUG-18:00 | 0.31 | 31-AUG-24:00 | 8836.73 | 05-AUG-19:44 | 8807.02 | 05-AUG-19:42 | 375.38 | 22-AUG-15:50 | 2716.91 | 06-AUG-16:00 | 0.00 |
September | 0.557017E+10 | 0.129373E+10 | 720.00 | 0.548182E+10 | 88354101.63 | 0.00 | 0.46 | 30-SEP-24:00 | 0.17 | 19-SEP-07:00 | 3932.36 | 30-SEP-24:00 | 3932.36 | 30-SEP-24:00 | 347.88 | 07-SEP-15:30 | 1064.67 | 04-SEP-17:23 | 0.00 |
October | 0.103982E+11 | 0.219157E+10 | 744.00 | 0.103869E+11 | 11315050.91 | 0.00 | 0.66 | 31-OCT-24:00 | 0.38 | 10-OCT-06:55 | 5594.54 | 31-OCT-24:00 | 5594.54 | 31-OCT-24:00 | 110.50 | 25-OCT-11:00 | 1196.94 | 15-OCT-16:42 | 0.00 |
November | 0.145101E+11 | 0.297493E+10 | 720.00 | 0.145078E+11 | 2285212.23 | 0.00 | 0.73 | 12-NOV-16:15 | 0.55 | 27-NOV-07:10 | 6417.52 | 12-NOV-16:20 | 6417.52 | 12-NOV-16:20 | 74.32 | 08-NOV-15:10 | 1288.54 | 12-NOV-16:15 | 0.00 |
December | 0.193914E+11 | 0.393646E+10 | 744.00 | 0.193911E+11 | 260992.03 | 0.00 | 0.92 | 10-DEC-16:00 | 0.75 | 29-DEC-07:05 | 8219.65 | 10-DEC-16:00 | 8219.65 | 10-DEC-16:00 | 52.59 | 19-DEC-17:05 | 1621.99 | 10-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.149128E+12 | 0.319545E+11 | 8737.22 | 0.148709E+12 | 0.418664E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.264833E+10 | 0.641557E+09 | 672.00 | 0.264802E+10 | 0.00 | 0.00 | 0.27 | 0.00 | 2162.16 | 2155.50 | 0.00 | 467.57 | 0.00 | ||||||
Maximum of Months | 0.212765E+11 | 0.469055E+10 | 744.00 | 0.211965E+11 | 0.109399E+09 | 0.00 | 1.00 | 0.75 | 8836.73 | 8807.02 | 375.38 | 2716.91 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.541830E+10 | 0.148760E+10 | 427.57 | 0.541516E+10 | 3143572.85 | 0.00 | 0.20 | 13-JAN-16:30 | 0.00 | 01-JAN-08:25 | 15004.75 | 13-JAN-16:30 | 15004.75 | 13-JAN-16:30 | 109.63 | 01-JAN-15:33 | 3383.77 | 13-JAN-16:30 | 0.00 |
February | 0.555600E+11 | 0.125845E+11 | 672.00 | 0.555600E+11 | -0.0 | 0.00 | 0.53 | 26-FEB-17:23 | 0.12 | 06-FEB-04:01 | 40858.59 | 28-FEB-17:00 | 40858.59 | 28-FEB-17:00 | 0.00 | 15-FEB-23:20 | 8817.61 | 26-FEB-17:23 | 0.00 |
March | 0.121420E+12 | 0.256267E+11 | 744.00 | 0.121420E+12 | -0.0 | 0.00 | 0.76 | 31-MAR-23:40 | 0.38 | 06-MAR-07:05 | 64162.46 | 31-MAR-23:40 | 64162.46 | 31-MAR-23:40 | 0.00 | 11-MAR-07:20 | 12836.64 | 31-MAR-23:40 | 0.00 |
April | 0.178035E+12 | 0.354455E+11 | 720.00 | 0.177949E+12 | 86252025.70 | 0.00 | 0.98 | 16-APR-17:52 | 0.15 | 30-APR-24:00 | 81097.12 | 22-APR-18:10 | 81097.12 | 22-APR-18:10 | 1287.67 | 17-APR-16:10 | 18387.93 | 07-APR-14:00 | 0.00 |
May | 0.438765E+11 | 0.100770E+11 | 744.00 | 0.436332E+11 | 0.243323E+09 | 0.00 | 0.48 | 31-MAY-24:00 | 0.03 | 08-MAY-06:10 | 38660.89 | 31-MAY-24:00 | 38660.89 | 31-MAY-24:00 | 1436.23 | 30-MAY-09:30 | 8100.21 | 31-MAY-24:00 | 0.00 |
June | 0.990206E+11 | 0.222137E+11 | 720.00 | 0.980967E+11 | 0.923913E+09 | 0.00 | 0.69 | 30-JUN-23:13 | 0.35 | 17-JUN-06:30 | 58396.29 | 30-JUN-23:57 | 58161.96 | 30-JUN-24:00 | 3038.71 | 06-JUN-16:40 | 13511.11 | 29-JUN-15:00 | 0.00 |
July | 0.155215E+12 | 0.362209E+11 | 744.00 | 0.154127E+12 | 0.108801E+10 | 0.00 | 0.88 | 31-JUL-23:10 | 0.61 | 08-JUL-06:40 | 76014.11 | 31-JUL-23:53 | 76014.11 | 31-JUL-23:53 | 3173.98 | 03-JUL-16:50 | 21751.48 | 17-JUL-16:00 | 0.00 |
August | 0.201468E+12 | 0.445146E+11 | 744.00 | 0.200670E+12 | 0.797997E+09 | 0.00 | 1.00 | 04-AUG-18:00 | 0.27 | 31-AUG-24:00 | 84234.23 | 05-AUG-19:42 | 83894.03 | 05-AUG-19:42 | 3691.84 | 22-AUG-15:50 | 26001.76 | 06-AUG-16:00 | 0.00 |
September | 0.468638E+11 | 0.110348E+11 | 720.00 | 0.460047E+11 | 0.859005E+09 | 0.00 | 0.43 | 30-SEP-23:50 | 0.10 | 19-SEP-06:10 | 35014.09 | 30-SEP-23:50 | 35014.09 | 30-SEP-23:50 | 3487.88 | 07-SEP-15:30 | 9922.96 | 04-SEP-17:23 | 0.00 |
October | 0.862199E+11 | 0.184252E+11 | 744.00 | 0.861069E+11 | 0.112992E+09 | 0.00 | 0.60 | 31-OCT-24:00 | 0.25 | 10-OCT-06:10 | 47375.58 | 31-OCT-24:00 | 47375.58 | 31-OCT-24:00 | 1083.58 | 25-OCT-11:00 | 10852.41 | 18-OCT-16:00 | 0.00 |
November | 0.118439E+12 | 0.247029E+11 | 720.00 | 0.118415E+12 | 23497870.57 | 0.00 | 0.68 | 03-NOV-16:00 | 0.39 | 27-NOV-07:10 | 58442.08 | 03-NOV-16:00 | 57894.99 | 03-NOV-16:00 | 744.81 | 08-NOV-15:10 | 11473.74 | 03-NOV-16:00 | 0.00 |
December | 0.155652E+12 | 0.323093E+11 | 744.00 | 0.155649E+12 | 3443711.73 | 0.00 | 0.84 | 10-DEC-16:03 | 0.57 | 31-DEC-23:53 | 72893.99 | 06-DEC-16:10 | 72596.36 | 06-DEC-16:10 | 541.90 | 19-DEC-17:05 | 14100.55 | 10-DEC-16:03 | 0.00 |
Annual Sum or Average | 0.126719E+13 | 0.274643E+12 | 8443.57 | 0.126305E+13 | 0.414158E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.541830E+10 | 0.148760E+10 | 427.57 | 0.541516E+10 | -0.0 | 0.00 | 0.20 | 0.00 | 15004.75 | 15004.75 | 0.00 | 3383.77 | 0.00 | ||||||
Maximum of Months | 0.201468E+12 | 0.445146E+11 | 744.00 | 0.200670E+12 | 0.108801E+10 | 0.00 | 1.00 | 0.61 | 84234.23 | 83894.03 | 3691.84 | 26001.76 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 98383223.48 | 27893965.25 | 92.83 | 98383223.48 | -0.0 | 0.00 | 0.18 | 13-JAN-16:30 | 0.00 | 01-JAN-00:05 | 1396.58 | 13-JAN-16:30 | 1396.58 | 13-JAN-16:30 | 0.00 | 14-JAN-16:15 | 317.54 | 13-JAN-16:30 | 0.00 |
February | 0.393360E+10 | 0.910865E+09 | 647.73 | 0.393360E+10 | -0.0 | 0.00 | 0.48 | 28-FEB-17:00 | 0.00 | 03-FEB-03:23 | 3955.80 | 28-FEB-17:00 | 3955.80 | 28-FEB-17:00 | 0.00 | 12-FEB-24:00 | 820.17 | 28-FEB-17:00 | 0.00 |
March | 0.103376E+11 | 0.221619E+10 | 744.00 | 0.103376E+11 | -0.0 | 0.00 | 0.71 | 28-MAR-17:50 | 0.19 | 06-MAR-04:23 | 5926.23 | 28-MAR-17:50 | 5926.23 | 28-MAR-17:50 | 0.00 | 30-MAR-23:50 | 1209.00 | 28-MAR-17:50 | 0.00 |
April | 0.164772E+11 | 0.331901E+10 | 719.00 | 0.164687E+11 | 8476085.58 | 0.00 | 0.95 | 16-APR-17:52 | 0.00 | 30-APR-23:10 | 8136.91 | 25-APR-18:00 | 8136.91 | 25-APR-18:00 | 127.41 | 17-APR-16:10 | 1846.48 | 07-APR-14:00 | 0.00 |
May | 0.362052E+10 | 0.841047E+09 | 687.00 | 0.359666E+10 | 23865418.85 | 0.00 | 0.47 | 31-MAY-23:50 | 0.00 | 01-MAY-00:10 | 3797.89 | 31-MAY-23:50 | 3797.89 | 31-MAY-23:50 | 138.67 | 30-MAY-09:30 | 798.34 | 31-MAY-23:50 | 0.00 |
June | 0.966923E+10 | 0.218329E+10 | 720.00 | 0.957700E+10 | 92235797.46 | 0.00 | 0.68 | 30-JUN-23:13 | 0.24 | 17-JUN-06:10 | 5815.23 | 30-JUN-23:57 | 5791.73 | 30-JUN-24:00 | 306.57 | 06-JUN-16:40 | 1383.46 | 29-JUN-15:00 | 0.00 |
July | 0.154866E+11 | 0.363007E+10 | 744.00 | 0.153779E+11 | 0.108672E+09 | 0.00 | 0.89 | 16-JUL-18:41 | 0.55 | 08-JUL-06:40 | 7609.65 | 31-JUL-23:53 | 7609.65 | 31-JUL-23:53 | 318.13 | 03-JUL-16:50 | 2223.08 | 17-JUL-16:00 | 0.00 |
August | 0.200036E+11 | 0.444236E+10 | 744.00 | 0.199240E+11 | 79629698.13 | 0.00 | 1.00 | 04-AUG-18:00 | 0.26 | 31-AUG-24:00 | 8608.50 | 05-AUG-19:44 | 8574.68 | 05-AUG-19:42 | 370.51 | 22-AUG-15:50 | 2649.47 | 06-AUG-16:00 | 0.00 |
September | 0.404857E+10 | 0.972604E+09 | 716.07 | 0.396454E+10 | 84035171.31 | 0.00 | 0.44 | 04-SEP-17:23 | 0.00 | 13-SEP-06:10 | 3271.41 | 04-SEP-17:32 | 3271.41 | 04-SEP-17:32 | 351.58 | 07-SEP-15:20 | 1071.33 | 04-SEP-17:23 | 0.00 |
October | 0.700836E+10 | 0.152621E+10 | 744.00 | 0.699742E+10 | 10948129.27 | 0.00 | 0.54 | 18-OCT-16:50 | 0.09 | 10-OCT-03:20 | 4396.67 | 18-OCT-16:50 | 4396.67 | 18-OCT-16:50 | 106.46 | 25-OCT-11:00 | 1092.11 | 18-OCT-16:00 | 0.00 |
November | 0.971643E+10 | 0.206675E+10 | 720.00 | 0.971416E+10 | 2272845.46 | 0.00 | 0.65 | 03-NOV-16:00 | 0.19 | 27-NOV-04:01 | 5692.71 | 03-NOV-16:00 | 5637.82 | 03-NOV-16:00 | 73.51 | 08-NOV-15:20 | 1123.37 | 03-NOV-16:00 | 0.00 |
December | 0.134091E+11 | 0.283333E+10 | 744.00 | 0.134088E+11 | 300839.57 | 0.00 | 0.80 | 06-DEC-16:10 | 0.41 | 31-DEC-23:25 | 7147.41 | 06-DEC-16:10 | 7119.26 | 06-DEC-16:10 | 51.42 | 19-DEC-17:05 | 1375.78 | 06-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.113809E+12 | 0.249696E+11 | 8022.63 | 0.113399E+12 | 0.410436E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 98383223.48 | 27893965.25 | 92.83 | 98383223.48 | -0.0 | 0.00 | 0.18 | 0.00 | 1396.58 | 1396.58 | 0.00 | 317.54 | 0.00 | ||||||
Maximum of Months | 0.200036E+11 | 0.444236E+10 | 744.00 | 0.199240E+11 | 0.108672E+09 | 0.00 | 1.00 | 0.55 | 8608.50 | 8574.68 | 370.51 | 2649.47 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.47 | 0.00 | 84.47 | 1.40 | 757.75 | 0.00 | 0.00 | 0.00 |
February | 119.27 | 0.00 | 119.27 | 14.34 | 571.66 | 0.00 | 0.00 | 0.00 |
March | 193.75 | 0.00 | 193.75 | 58.42 | 468.07 | 0.00 | 0.00 | 0.00 |
April | 220.92 | 1.29 | 219.63 | 108.76 | 336.53 | 0.00 | 0.00 | 0.00 |
May | 290.12 | 17.19 | 272.93 | 213.38 | 242.92 | 0.00 | 0.00 | 0.00 |
June | 337.83 | 38.83 | 299.00 | 347.93 | 151.64 | 0.00 | 0.00 | 0.00 |
July | 308.63 | 28.91 | 279.72 | 378.43 | 124.72 | 0.00 | 0.00 | 0.00 |
August | 247.30 | 6.63 | 240.68 | 274.03 | 144.46 | 0.00 | 0.00 | 0.00 |
September | 185.21 | 0.07 | 185.15 | 158.55 | 225.34 | 0.00 | 0.00 | 0.00 |
October | 135.10 | 0.00 | 135.10 | 54.83 | 346.24 | 0.00 | 0.00 | 0.00 |
November | 91.84 | 0.00 | 91.84 | 10.65 | 501.86 | 0.00 | 0.00 | 0.00 |
December | 70.84 | 0.00 | 70.84 | 0.42 | 679.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.82 | 7.78 | 183.04 | 135.85 | 378.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 70.84 | 0.00 | 70.84 | 0.42 | 124.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 337.83 | 38.83 | 299.00 | 378.43 | 757.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.47 | 0.00 | 84.47 | 1.40 | 757.75 | 0.00 | 0.00 | 0.00 |
February | 119.27 | 0.00 | 119.27 | 14.34 | 571.66 | 0.00 | 0.00 | 0.00 |
March | 193.75 | 0.00 | 193.75 | 58.42 | 468.07 | 0.00 | 0.00 | 0.00 |
April | 220.92 | 1.29 | 219.63 | 108.75 | 336.53 | 0.00 | 0.00 | 0.00 |
May | 290.12 | 17.19 | 272.93 | 213.37 | 242.92 | 0.00 | 0.00 | 0.00 |
June | 337.83 | 38.83 | 299.00 | 347.92 | 151.64 | 0.00 | 0.00 | 0.00 |
July | 308.62 | 28.91 | 279.72 | 378.43 | 124.72 | 0.00 | 0.00 | 0.00 |
August | 247.30 | 6.63 | 240.67 | 274.03 | 144.46 | 0.00 | 0.00 | 0.00 |
September | 185.21 | 0.07 | 185.14 | 158.55 | 225.34 | 0.00 | 0.00 | 0.00 |
October | 135.10 | 0.00 | 135.10 | 54.83 | 346.24 | 0.00 | 0.00 | 0.00 |
November | 91.84 | 0.00 | 91.84 | 10.65 | 501.86 | 0.00 | 0.00 | 0.00 |
December | 70.84 | 0.00 | 70.84 | 0.42 | 679.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.82 | 7.78 | 183.04 | 135.85 | 378.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 70.84 | 0.00 | 70.84 | 0.42 | 124.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 337.83 | 38.83 | 299.00 | 378.43 | 757.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.47 | 0.00 | 84.47 | 1.40 | 757.75 | 0.00 | 0.00 | 0.00 |
February | 119.27 | 0.00 | 119.27 | 14.34 | 571.66 | 0.00 | 0.00 | 0.00 |
March | 193.75 | 0.00 | 193.75 | 58.42 | 468.07 | 0.00 | 0.00 | 0.00 |
April | 220.92 | 1.29 | 219.63 | 108.75 | 336.53 | 0.00 | 0.00 | 0.00 |
May | 290.12 | 17.19 | 272.93 | 213.37 | 242.92 | 0.00 | 0.00 | 0.00 |
June | 337.83 | 38.83 | 299.00 | 347.93 | 151.64 | 0.00 | 0.00 | 0.00 |
July | 308.62 | 28.91 | 279.72 | 378.43 | 124.72 | 0.00 | 0.00 | 0.00 |
August | 247.30 | 6.63 | 240.67 | 274.03 | 144.46 | 0.00 | 0.00 | 0.00 |
September | 185.21 | 0.07 | 185.15 | 158.55 | 225.34 | 0.00 | 0.00 | 0.00 |
October | 135.10 | 0.00 | 135.10 | 54.83 | 346.24 | 0.00 | 0.00 | 0.00 |
November | 91.84 | 0.00 | 91.84 | 10.65 | 501.86 | 0.00 | 0.00 | 0.00 |
December | 70.84 | 0.00 | 70.84 | 0.42 | 679.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.82 | 7.78 | 183.04 | 135.85 | 378.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 70.84 | 0.00 | 70.84 | 0.42 | 124.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 337.83 | 38.83 | 299.00 | 378.43 | 757.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.47 | 0.00 | 84.47 | 1.40 | 757.75 | 0.00 | 0.00 | 0.00 |
February | 119.27 | 0.00 | 119.27 | 14.34 | 571.66 | 0.00 | 0.00 | 0.00 |
March | 193.75 | 0.00 | 193.75 | 58.42 | 468.07 | 0.00 | 0.00 | 0.00 |
April | 220.92 | 1.29 | 219.63 | 108.75 | 336.53 | 0.00 | 0.00 | 0.00 |
May | 290.12 | 17.19 | 272.93 | 213.37 | 242.92 | 0.00 | 0.00 | 0.00 |
June | 337.83 | 38.83 | 299.00 | 347.92 | 151.64 | 0.00 | 0.00 | 0.00 |
July | 308.62 | 28.91 | 279.72 | 378.43 | 124.72 | 0.00 | 0.00 | 0.00 |
August | 247.30 | 6.63 | 240.67 | 274.03 | 144.46 | 0.00 | 0.00 | 0.00 |
September | 185.21 | 0.07 | 185.14 | 158.55 | 225.34 | 0.00 | 0.00 | 0.00 |
October | 135.10 | 0.00 | 135.10 | 54.83 | 346.24 | 0.00 | 0.00 | 0.00 |
November | 91.84 | 0.00 | 91.84 | 10.65 | 501.86 | 0.00 | 0.00 | 0.00 |
December | 70.84 | 0.00 | 70.84 | 0.42 | 679.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.82 | 7.78 | 183.04 | 135.85 | 378.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 70.84 | 0.00 | 70.84 | 0.42 | 124.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 337.83 | 38.83 | 299.00 | 378.43 | 757.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.47 | 0.00 | 84.47 | 1.40 | 757.72 | 0.00 | 0.00 | 0.00 |
February | 119.27 | 0.00 | 119.27 | 14.34 | 571.64 | 0.00 | 0.00 | 0.00 |
March | 193.74 | 0.00 | 193.74 | 58.42 | 468.05 | 0.00 | 0.00 | 0.00 |
April | 220.91 | 1.29 | 219.62 | 108.75 | 336.51 | 0.00 | 0.00 | 0.00 |
May | 290.11 | 17.19 | 272.92 | 213.36 | 242.91 | 0.00 | 0.00 | 0.00 |
June | 337.81 | 38.83 | 298.98 | 347.91 | 151.63 | 0.00 | 0.00 | 0.00 |
July | 308.61 | 28.90 | 279.71 | 378.41 | 124.72 | 0.00 | 0.00 | 0.00 |
August | 247.29 | 6.63 | 240.66 | 274.02 | 144.46 | 0.00 | 0.00 | 0.00 |
September | 185.20 | 0.07 | 185.14 | 158.55 | 225.33 | 0.00 | 0.00 | 0.00 |
October | 135.10 | 0.00 | 135.10 | 54.83 | 346.23 | 0.00 | 0.00 | 0.00 |
November | 91.84 | 0.00 | 91.84 | 10.65 | 501.84 | 0.00 | 0.00 | 0.00 |
December | 70.83 | 0.00 | 70.83 | 0.42 | 679.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.81 | 7.78 | 183.03 | 135.85 | 378.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 70.83 | 0.00 | 70.83 | 0.42 | 124.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 337.81 | 38.83 | 298.98 | 378.41 | 757.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 215.53 | 98.81 | 116.72 | 112.25 | 768.88 | 0.00 | 0.00 | 0.00 |
February | 337.11 | 167.37 | 169.74 | 249.41 | 575.51 | 0.00 | 0.00 | 0.00 |
March | 453.27 | 187.55 | 265.72 | 367.62 | 478.84 | 0.00 | 0.00 | 0.00 |
April | 578.33 | 286.62 | 291.71 | 562.86 | 345.76 | 0.00 | 0.00 | 0.00 |
May | 638.84 | 284.24 | 354.60 | 670.60 | 269.04 | 0.00 | 0.00 | 0.00 |
June | 826.90 | 425.52 | 401.38 | 1003.79 | 170.07 | 0.00 | 0.00 | 0.00 |
July | 867.85 | 490.62 | 377.23 | 1137.50 | 134.72 | 0.00 | 0.00 | 0.00 |
August | 754.20 | 420.22 | 333.98 | 965.29 | 152.21 | 0.00 | 0.00 | 0.00 |
September | 533.52 | 275.40 | 258.12 | 616.70 | 233.49 | 0.00 | 0.00 | 0.00 |
October | 382.78 | 194.37 | 188.41 | 361.96 | 353.23 | 0.00 | 0.00 | 0.00 |
November | 242.60 | 113.26 | 129.34 | 163.29 | 495.43 | 0.00 | 0.00 | 0.00 |
December | 178.93 | 76.85 | 102.08 | 85.37 | 676.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 501.68 | 252.17 | 249.51 | 526.30 | 387.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 178.93 | 76.85 | 102.08 | 85.37 | 134.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 867.85 | 490.62 | 401.38 | 1137.50 | 768.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 215.53 | 98.81 | 116.72 | 112.25 | 768.88 | 0.00 | 0.00 | 0.00 |
February | 337.11 | 167.37 | 169.74 | 249.41 | 575.51 | 0.00 | 0.00 | 0.00 |
March | 453.27 | 187.55 | 265.72 | 367.62 | 478.84 | 0.00 | 0.00 | 0.00 |
April | 578.33 | 286.62 | 291.71 | 562.86 | 345.76 | 0.00 | 0.00 | 0.00 |
May | 638.84 | 284.24 | 354.60 | 670.60 | 269.04 | 0.00 | 0.00 | 0.00 |
June | 826.90 | 425.52 | 401.38 | 1003.79 | 170.07 | 0.00 | 0.00 | 0.00 |
July | 867.85 | 490.62 | 377.23 | 1137.50 | 134.72 | 0.00 | 0.00 | 0.00 |
August | 754.20 | 420.22 | 333.98 | 965.29 | 152.21 | 0.00 | 0.00 | 0.00 |
September | 533.52 | 275.40 | 258.12 | 616.70 | 233.49 | 0.00 | 0.00 | 0.00 |
October | 382.78 | 194.37 | 188.41 | 361.96 | 353.23 | 0.00 | 0.00 | 0.00 |
November | 242.60 | 113.26 | 129.34 | 163.29 | 495.43 | 0.00 | 0.00 | 0.00 |
December | 178.93 | 76.85 | 102.08 | 85.37 | 676.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 501.68 | 252.17 | 249.51 | 526.30 | 387.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 178.93 | 76.85 | 102.08 | 85.37 | 134.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 867.85 | 490.62 | 401.38 | 1137.50 | 768.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 215.53 | 98.81 | 116.72 | 112.25 | 768.87 | 0.00 | 0.00 | 0.00 |
February | 337.10 | 167.36 | 169.74 | 249.41 | 575.50 | 0.00 | 0.00 | 0.00 |
March | 453.26 | 187.55 | 265.72 | 367.61 | 478.83 | 0.00 | 0.00 | 0.00 |
April | 578.32 | 286.61 | 291.71 | 562.85 | 345.75 | 0.00 | 0.00 | 0.00 |
May | 638.83 | 284.24 | 354.59 | 670.59 | 269.03 | 0.00 | 0.00 | 0.00 |
June | 826.88 | 425.51 | 401.37 | 1003.77 | 170.06 | 0.00 | 0.00 | 0.00 |
July | 867.84 | 490.61 | 377.23 | 1137.48 | 134.72 | 0.00 | 0.00 | 0.00 |
August | 754.19 | 420.21 | 333.98 | 965.27 | 152.20 | 0.00 | 0.00 | 0.00 |
September | 533.51 | 275.40 | 258.12 | 616.69 | 233.48 | 0.00 | 0.00 | 0.00 |
October | 382.77 | 194.36 | 188.40 | 361.96 | 353.22 | 0.00 | 0.00 | 0.00 |
November | 242.59 | 113.26 | 129.33 | 163.29 | 495.42 | 0.00 | 0.00 | 0.00 |
December | 178.93 | 76.85 | 102.08 | 85.36 | 676.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 501.67 | 252.17 | 249.50 | 526.29 | 387.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 178.93 | 76.85 | 102.08 | 85.36 | 134.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 867.84 | 490.61 | 401.37 | 1137.48 | 768.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 595.44 | 425.28 | 170.17 | 561.73 | 635.85 | 0.00 | 0.00 | 0.00 |
February | 758.29 | 545.39 | 212.90 | 787.25 | 486.34 | 0.00 | 0.00 | 0.00 |
March | 677.81 | 380.63 | 297.18 | 700.92 | 438.64 | 0.00 | 0.00 | 0.00 |
April | 544.85 | 260.60 | 284.24 | 584.48 | 331.35 | 0.00 | 0.00 | 0.00 |
May | 484.08 | 160.78 | 323.31 | 530.49 | 257.15 | 0.00 | 0.00 | 0.00 |
June | 480.99 | 140.28 | 340.71 | 602.81 | 173.86 | 0.00 | 0.00 | 0.00 |
July | 518.55 | 191.55 | 327.00 | 725.23 | 137.08 | 0.00 | 0.00 | 0.00 |
August | 616.26 | 310.71 | 305.56 | 836.25 | 155.62 | 0.00 | 0.00 | 0.00 |
September | 683.51 | 418.81 | 264.70 | 860.54 | 224.52 | 0.00 | 0.00 | 0.00 |
October | 714.57 | 494.11 | 220.46 | 822.81 | 321.12 | 0.00 | 0.00 | 0.00 |
November | 651.48 | 471.90 | 179.57 | 680.67 | 416.90 | 0.00 | 0.00 | 0.00 |
December | 566.23 | 408.88 | 157.36 | 542.51 | 557.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 606.62 | 349.45 | 257.18 | 685.52 | 344.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 480.99 | 140.28 | 157.36 | 530.49 | 137.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 758.29 | 545.39 | 340.71 | 860.54 | 635.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 595.44 | 425.27 | 170.16 | 561.73 | 635.85 | 0.00 | 0.00 | 0.00 |
February | 758.28 | 545.38 | 212.90 | 787.25 | 486.34 | 0.00 | 0.00 | 0.00 |
March | 677.81 | 380.62 | 297.18 | 700.92 | 438.64 | 0.00 | 0.00 | 0.00 |
April | 544.84 | 260.60 | 284.24 | 584.48 | 331.35 | 0.00 | 0.00 | 0.00 |
May | 484.08 | 160.78 | 323.31 | 530.49 | 257.15 | 0.00 | 0.00 | 0.00 |
June | 480.98 | 140.28 | 340.71 | 602.80 | 173.86 | 0.00 | 0.00 | 0.00 |
July | 518.55 | 191.55 | 327.00 | 725.23 | 137.08 | 0.00 | 0.00 | 0.00 |
August | 616.26 | 310.70 | 305.55 | 836.25 | 155.62 | 0.00 | 0.00 | 0.00 |
September | 683.50 | 418.80 | 264.70 | 860.53 | 224.52 | 0.00 | 0.00 | 0.00 |
October | 714.57 | 494.11 | 220.45 | 822.80 | 321.12 | 0.00 | 0.00 | 0.00 |
November | 651.47 | 471.90 | 179.57 | 680.66 | 416.90 | 0.00 | 0.00 | 0.00 |
December | 566.23 | 408.87 | 157.35 | 542.51 | 557.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 606.62 | 349.44 | 257.18 | 685.52 | 344.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 480.98 | 140.28 | 157.35 | 530.49 | 137.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 758.28 | 545.38 | 340.71 | 860.53 | 635.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 595.44 | 425.28 | 170.17 | 561.73 | 635.85 | 0.00 | 0.00 | 0.00 |
February | 758.29 | 545.39 | 212.90 | 787.25 | 486.34 | 0.00 | 0.00 | 0.00 |
March | 677.81 | 380.63 | 297.18 | 700.92 | 438.64 | 0.00 | 0.00 | 0.00 |
April | 544.85 | 260.60 | 284.24 | 584.48 | 331.35 | 0.00 | 0.00 | 0.00 |
May | 484.08 | 160.78 | 323.31 | 530.49 | 257.15 | 0.00 | 0.00 | 0.00 |
June | 480.99 | 140.28 | 340.71 | 602.81 | 173.86 | 0.00 | 0.00 | 0.00 |
July | 518.55 | 191.55 | 327.00 | 725.23 | 137.08 | 0.00 | 0.00 | 0.00 |
August | 616.26 | 310.71 | 305.56 | 836.25 | 155.62 | 0.00 | 0.00 | 0.00 |
September | 683.51 | 418.81 | 264.70 | 860.54 | 224.52 | 0.00 | 0.00 | 0.00 |
October | 714.57 | 494.11 | 220.46 | 822.81 | 321.12 | 0.00 | 0.00 | 0.00 |
November | 651.48 | 471.90 | 179.57 | 680.67 | 416.90 | 0.00 | 0.00 | 0.00 |
December | 566.23 | 408.88 | 157.36 | 542.51 | 557.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 606.62 | 349.45 | 257.18 | 685.52 | 344.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 480.99 | 140.28 | 157.36 | 530.49 | 137.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 758.29 | 545.39 | 340.71 | 860.54 | 635.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 595.44 | 425.27 | 170.16 | 561.73 | 635.85 | 0.00 | 0.00 | 0.00 |
February | 758.28 | 545.38 | 212.90 | 787.25 | 486.34 | 0.00 | 0.00 | 0.00 |
March | 677.81 | 380.62 | 297.18 | 700.92 | 438.64 | 0.00 | 0.00 | 0.00 |
April | 544.84 | 260.60 | 284.24 | 584.48 | 331.35 | 0.00 | 0.00 | 0.00 |
May | 484.08 | 160.78 | 323.31 | 530.49 | 257.15 | 0.00 | 0.00 | 0.00 |
June | 480.98 | 140.28 | 340.71 | 602.80 | 173.86 | 0.00 | 0.00 | 0.00 |
July | 518.55 | 191.55 | 327.00 | 725.23 | 137.08 | 0.00 | 0.00 | 0.00 |
August | 616.26 | 310.70 | 305.55 | 836.25 | 155.62 | 0.00 | 0.00 | 0.00 |
September | 683.50 | 418.80 | 264.70 | 860.53 | 224.52 | 0.00 | 0.00 | 0.00 |
October | 714.57 | 494.11 | 220.45 | 822.80 | 321.12 | 0.00 | 0.00 | 0.00 |
November | 651.47 | 471.90 | 179.57 | 680.66 | 416.90 | 0.00 | 0.00 | 0.00 |
December | 566.23 | 408.87 | 157.35 | 542.51 | 557.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 606.62 | 349.44 | 257.18 | 685.52 | 344.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 480.98 | 140.28 | 157.35 | 530.49 | 137.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 758.28 | 545.38 | 340.71 | 860.53 | 635.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 595.42 | 425.26 | 170.16 | 561.71 | 635.83 | 0.00 | 0.00 | 0.00 |
February | 758.25 | 545.36 | 212.89 | 787.22 | 486.32 | 0.00 | 0.00 | 0.00 |
March | 677.78 | 380.61 | 297.17 | 700.89 | 438.62 | 0.00 | 0.00 | 0.00 |
April | 544.82 | 260.59 | 284.23 | 584.45 | 331.34 | 0.00 | 0.00 | 0.00 |
May | 484.06 | 160.77 | 323.29 | 530.47 | 257.14 | 0.00 | 0.00 | 0.00 |
June | 480.97 | 140.27 | 340.69 | 602.78 | 173.85 | 0.00 | 0.00 | 0.00 |
July | 518.53 | 191.54 | 326.99 | 725.20 | 137.08 | 0.00 | 0.00 | 0.00 |
August | 616.24 | 310.69 | 305.54 | 836.22 | 155.61 | 0.00 | 0.00 | 0.00 |
September | 683.48 | 418.79 | 264.69 | 860.50 | 224.51 | 0.00 | 0.00 | 0.00 |
October | 714.54 | 494.09 | 220.45 | 822.77 | 321.10 | 0.00 | 0.00 | 0.00 |
November | 651.45 | 471.88 | 179.57 | 680.64 | 416.89 | 0.00 | 0.00 | 0.00 |
December | 566.21 | 408.86 | 157.35 | 542.49 | 557.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 606.60 | 349.43 | 257.17 | 685.49 | 344.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 480.97 | 140.27 | 157.35 | 530.47 | 137.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 758.25 | 545.36 | 340.69 | 860.50 | 635.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 195.22 | 78.68 | 116.55 | 96.68 | 828.57 | 0.00 | 0.00 | 0.00 |
February | 333.22 | 163.79 | 169.42 | 244.75 | 632.37 | 0.00 | 0.00 | 0.00 |
March | 426.44 | 156.25 | 270.19 | 325.36 | 548.14 | 0.00 | 0.00 | 0.00 |
April | 556.72 | 246.65 | 310.07 | 528.29 | 415.37 | 0.00 | 0.00 | 0.00 |
May | 688.62 | 314.05 | 374.57 | 736.68 | 303.58 | 0.00 | 0.00 | 0.00 |
June | 749.19 | 344.13 | 405.06 | 898.40 | 208.51 | 0.00 | 0.00 | 0.00 |
July | 767.46 | 387.81 | 379.65 | 999.52 | 175.05 | 0.00 | 0.00 | 0.00 |
August | 651.68 | 319.83 | 331.85 | 820.94 | 195.98 | 0.00 | 0.00 | 0.00 |
September | 524.24 | 265.03 | 259.20 | 608.56 | 267.96 | 0.00 | 0.00 | 0.00 |
October | 374.69 | 186.16 | 188.52 | 353.91 | 406.17 | 0.00 | 0.00 | 0.00 |
November | 265.24 | 131.58 | 133.66 | 195.83 | 569.37 | 0.00 | 0.00 | 0.00 |
December | 178.29 | 75.25 | 103.04 | 85.76 | 772.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 476.57 | 222.65 | 253.92 | 492.52 | 442.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 178.29 | 75.25 | 103.04 | 85.76 | 175.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 767.46 | 387.81 | 405.06 | 999.52 | 828.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 195.22 | 78.68 | 116.55 | 96.68 | 828.57 | 0.00 | 0.00 | 0.00 |
February | 333.22 | 163.79 | 169.42 | 244.75 | 632.37 | 0.00 | 0.00 | 0.00 |
March | 426.44 | 156.25 | 270.19 | 325.36 | 548.14 | 0.00 | 0.00 | 0.00 |
April | 556.72 | 246.65 | 310.07 | 528.29 | 415.37 | 0.00 | 0.00 | 0.00 |
May | 688.62 | 314.05 | 374.57 | 736.68 | 303.58 | 0.00 | 0.00 | 0.00 |
June | 749.19 | 344.13 | 405.06 | 898.40 | 208.51 | 0.00 | 0.00 | 0.00 |
July | 767.46 | 387.81 | 379.65 | 999.52 | 175.05 | 0.00 | 0.00 | 0.00 |
August | 651.68 | 319.83 | 331.85 | 820.94 | 195.98 | 0.00 | 0.00 | 0.00 |
September | 524.24 | 265.03 | 259.20 | 608.56 | 267.96 | 0.00 | 0.00 | 0.00 |
October | 374.69 | 186.16 | 188.52 | 353.91 | 406.17 | 0.00 | 0.00 | 0.00 |
November | 265.24 | 131.58 | 133.66 | 195.83 | 569.37 | 0.00 | 0.00 | 0.00 |
December | 178.29 | 75.25 | 103.04 | 85.76 | 772.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 476.57 | 222.65 | 253.92 | 492.52 | 442.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 178.29 | 75.25 | 103.04 | 85.76 | 175.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 767.46 | 387.81 | 405.06 | 999.52 | 828.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 195.22 | 78.68 | 116.55 | 96.68 | 828.56 | 0.00 | 0.00 | 0.00 |
February | 333.21 | 163.79 | 169.42 | 244.75 | 632.36 | 0.00 | 0.00 | 0.00 |
March | 426.43 | 156.25 | 270.18 | 325.36 | 548.13 | 0.00 | 0.00 | 0.00 |
April | 556.71 | 246.65 | 310.06 | 528.28 | 415.36 | 0.00 | 0.00 | 0.00 |
May | 688.61 | 314.04 | 374.57 | 736.67 | 303.57 | 0.00 | 0.00 | 0.00 |
June | 749.18 | 344.13 | 405.05 | 898.39 | 208.51 | 0.00 | 0.00 | 0.00 |
July | 767.45 | 387.80 | 379.65 | 999.50 | 175.05 | 0.00 | 0.00 | 0.00 |
August | 651.67 | 319.83 | 331.84 | 820.92 | 195.97 | 0.00 | 0.00 | 0.00 |
September | 524.23 | 265.03 | 259.20 | 608.55 | 267.96 | 0.00 | 0.00 | 0.00 |
October | 374.68 | 186.16 | 188.52 | 353.90 | 406.16 | 0.00 | 0.00 | 0.00 |
November | 265.24 | 131.58 | 133.66 | 195.83 | 569.35 | 0.00 | 0.00 | 0.00 |
December | 178.29 | 75.25 | 103.04 | 85.76 | 772.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 476.56 | 222.65 | 253.91 | 492.51 | 442.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 178.29 | 75.25 | 103.04 | 85.76 | 175.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 767.45 | 387.80 | 405.05 | 999.50 | 828.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 422.37 | 0.00 | 422.37 | 13.85 | 3559.91 | 0.00 | 0.00 | 0.00 |
February | 596.37 | 0.00 | 596.37 | 111.07 | 2627.19 | 0.00 | 0.00 | 0.00 |
March | 968.77 | 0.00 | 968.77 | 360.06 | 2119.60 | 0.00 | 0.00 | 0.00 |
April | 1104.60 | 6.45 | 1098.16 | 610.45 | 1512.19 | 0.00 | 0.00 | 0.00 |
May | 1450.61 | 85.96 | 1364.65 | 1109.11 | 1134.53 | 0.00 | 0.00 | 0.00 |
June | 1689.15 | 194.15 | 1495.00 | 1761.77 | 730.06 | 0.00 | 0.00 | 0.00 |
July | 1543.13 | 144.53 | 1398.60 | 1913.29 | 606.61 | 0.00 | 0.00 | 0.00 |
August | 1236.52 | 33.14 | 1203.38 | 1393.75 | 694.41 | 0.00 | 0.00 | 0.00 |
September | 926.07 | 0.33 | 925.74 | 821.56 | 1054.18 | 0.00 | 0.00 | 0.00 |
October | 675.51 | 0.00 | 675.51 | 324.87 | 1554.66 | 0.00 | 0.00 | 0.00 |
November | 459.22 | 0.00 | 459.22 | 80.33 | 2216.46 | 0.00 | 0.00 | 0.00 |
December | 354.18 | 0.00 | 354.18 | 8.05 | 3040.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 954.12 | 38.91 | 915.21 | 712.73 | 1734.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 354.18 | 0.00 | 354.18 | 8.05 | 606.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1689.15 | 194.15 | 1495.00 | 1913.29 | 3559.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 646.58 | 296.43 | 350.15 | 352.40 | 2191.00 | 0.00 | 0.00 | 0.00 |
February | 1011.31 | 502.09 | 509.22 | 775.40 | 1619.43 | 0.00 | 0.00 | 0.00 |
March | 1359.80 | 562.65 | 797.16 | 1132.37 | 1341.86 | 0.00 | 0.00 | 0.00 |
April | 1734.98 | 859.84 | 875.13 | 1703.53 | 975.22 | 0.00 | 0.00 | 0.00 |
May | 1916.51 | 852.73 | 1063.78 | 2016.37 | 767.34 | 0.00 | 0.00 | 0.00 |
June | 2480.67 | 1276.55 | 1204.12 | 2999.24 | 504.18 | 0.00 | 0.00 | 0.00 |
July | 2603.53 | 1471.85 | 1131.69 | 3396.86 | 411.76 | 0.00 | 0.00 | 0.00 |
August | 2262.59 | 1260.64 | 1001.94 | 2882.29 | 465.07 | 0.00 | 0.00 | 0.00 |
September | 1600.56 | 826.20 | 774.36 | 1850.38 | 672.29 | 0.00 | 0.00 | 0.00 |
October | 1148.32 | 583.10 | 565.22 | 1106.57 | 984.43 | 0.00 | 0.00 | 0.00 |
November | 727.78 | 339.78 | 388.00 | 516.72 | 1358.88 | 0.00 | 0.00 | 0.00 |
December | 536.78 | 230.55 | 306.23 | 277.16 | 1867.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1505.02 | 756.51 | 748.51 | 1588.74 | 1094.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 536.78 | 230.55 | 306.23 | 277.16 | 411.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2603.53 | 1471.85 | 1204.12 | 3396.86 | 2191.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2977.27 | 2126.42 | 850.84 | 2806.24 | 3113.64 | 0.00 | 0.00 | 0.00 |
February | 3791.51 | 2726.99 | 1064.51 | 3927.66 | 2363.13 | 0.00 | 0.00 | 0.00 |
March | 3389.11 | 1903.17 | 1485.94 | 3500.29 | 2120.17 | 0.00 | 0.00 | 0.00 |
April | 2724.28 | 1303.04 | 1421.24 | 2922.98 | 1590.85 | 0.00 | 0.00 | 0.00 |
May | 2420.45 | 803.90 | 1616.55 | 2646.15 | 1251.36 | 0.00 | 0.00 | 0.00 |
June | 2404.96 | 701.40 | 1703.56 | 3007.49 | 854.18 | 0.00 | 0.00 | 0.00 |
July | 2592.79 | 957.77 | 1635.02 | 3620.30 | 680.96 | 0.00 | 0.00 | 0.00 |
August | 3081.36 | 1553.57 | 1527.79 | 4168.50 | 773.19 | 0.00 | 0.00 | 0.00 |
September | 3417.60 | 2094.07 | 1323.53 | 4275.13 | 1107.76 | 0.00 | 0.00 | 0.00 |
October | 3572.92 | 2470.63 | 1102.29 | 4095.26 | 1566.89 | 0.00 | 0.00 | 0.00 |
November | 3257.44 | 2359.56 | 897.88 | 3405.31 | 2009.94 | 0.00 | 0.00 | 0.00 |
December | 2831.21 | 2044.42 | 786.79 | 2734.66 | 2657.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3033.18 | 1747.27 | 1285.90 | 3421.96 | 1671.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2404.96 | 701.40 | 786.79 | 2646.15 | 680.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3791.51 | 2726.99 | 1703.56 | 4275.13 | 3113.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 585.67 | 236.03 | 349.64 | 305.02 | 2317.12 | 0.00 | 0.00 | 0.00 |
February | 999.65 | 491.38 | 508.27 | 778.43 | 1701.55 | 0.00 | 0.00 | 0.00 |
March | 1279.30 | 468.76 | 810.55 | 1038.25 | 1435.25 | 0.00 | 0.00 | 0.00 |
April | 1670.14 | 739.95 | 930.19 | 1647.33 | 1068.40 | 0.00 | 0.00 | 0.00 |
May | 2065.84 | 942.13 | 1123.71 | 2232.66 | 843.84 | 0.00 | 0.00 | 0.00 |
June | 2247.56 | 1032.39 | 1215.17 | 2718.21 | 580.44 | 0.00 | 0.00 | 0.00 |
July | 2302.37 | 1163.42 | 1138.95 | 3025.18 | 486.45 | 0.00 | 0.00 | 0.00 |
August | 1955.02 | 959.48 | 995.54 | 2497.55 | 527.47 | 0.00 | 0.00 | 0.00 |
September | 1572.69 | 795.09 | 777.60 | 1845.00 | 741.77 | 0.00 | 0.00 | 0.00 |
October | 1124.04 | 558.48 | 565.57 | 1107.60 | 1066.99 | 0.00 | 0.00 | 0.00 |
November | 795.72 | 394.74 | 400.97 | 632.85 | 1452.28 | 0.00 | 0.00 | 0.00 |
December | 534.87 | 225.75 | 309.11 | 291.85 | 1969.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1429.68 | 667.94 | 761.74 | 1513.80 | 1180.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 534.87 | 225.75 | 309.11 | 291.85 | 486.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2302.37 | 1163.42 | 1215.17 | 3025.18 | 2317.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 422.37 | 0.00 | 422.37 | 20.61 | 3428.65 | 0.00 | 0.00 | 0.00 |
February | 596.37 | 0.00 | 596.37 | 133.04 | 2497.63 | 0.00 | 0.00 | 0.00 |
March | 968.77 | 0.00 | 968.77 | 396.69 | 1984.66 | 0.00 | 0.00 | 0.00 |
April | 1104.60 | 6.45 | 1098.16 | 662.35 | 1384.16 | 0.00 | 0.00 | 0.00 |
May | 1450.61 | 85.96 | 1364.65 | 1147.67 | 1057.86 | 0.00 | 0.00 | 0.00 |
June | 1689.15 | 194.15 | 1495.00 | 1776.29 | 706.97 | 0.00 | 0.00 | 0.00 |
July | 1543.13 | 144.53 | 1398.60 | 1912.10 | 599.09 | 0.00 | 0.00 | 0.00 |
August | 1236.52 | 33.14 | 1203.38 | 1400.19 | 673.58 | 0.00 | 0.00 | 0.00 |
September | 926.07 | 0.33 | 925.74 | 849.01 | 982.52 | 0.00 | 0.00 | 0.00 |
October | 675.51 | 0.00 | 675.51 | 376.40 | 1396.77 | 0.00 | 0.00 | 0.00 |
November | 459.22 | 0.00 | 459.22 | 101.69 | 2026.65 | 0.00 | 0.00 | 0.00 |
December | 354.18 | 0.00 | 354.18 | 10.21 | 2892.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 954.12 | 38.91 | 915.21 | 735.85 | 1632.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 354.18 | 0.00 | 354.18 | 10.21 | 599.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1689.15 | 194.15 | 1495.00 | 1912.10 | 3428.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 646.58 | 296.43 | 350.15 | 364.40 | 2110.43 | 0.00 | 0.00 | 0.00 |
February | 1011.31 | 502.09 | 509.22 | 800.51 | 1540.85 | 0.00 | 0.00 | 0.00 |
March | 1359.80 | 562.65 | 797.16 | 1162.91 | 1260.70 | 0.00 | 0.00 | 0.00 |
April | 1734.98 | 859.84 | 875.13 | 1732.57 | 906.34 | 0.00 | 0.00 | 0.00 |
May | 1916.51 | 852.73 | 1063.78 | 2030.15 | 725.38 | 0.00 | 0.00 | 0.00 |
June | 2480.67 | 1276.55 | 1204.12 | 2997.59 | 495.18 | 0.00 | 0.00 | 0.00 |
July | 2603.53 | 1471.85 | 1131.69 | 3388.14 | 411.41 | 0.00 | 0.00 | 0.00 |
August | 2262.59 | 1260.64 | 1001.94 | 2878.17 | 458.52 | 0.00 | 0.00 | 0.00 |
September | 1600.56 | 826.20 | 774.36 | 1861.03 | 640.47 | 0.00 | 0.00 | 0.00 |
October | 1148.32 | 583.10 | 565.22 | 1144.04 | 896.80 | 0.00 | 0.00 | 0.00 |
November | 727.78 | 339.78 | 388.00 | 546.18 | 1246.06 | 0.00 | 0.00 | 0.00 |
December | 536.78 | 230.55 | 306.23 | 288.67 | 1776.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1505.02 | 756.51 | 748.51 | 1604.07 | 1037.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 536.78 | 230.55 | 306.23 | 288.67 | 411.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2603.53 | 1471.85 | 1204.12 | 3388.14 | 2110.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2977.27 | 2126.42 | 850.84 | 2842.80 | 2972.71 | 0.00 | 0.00 | 0.00 |
February | 3791.51 | 2726.99 | 1064.51 | 3969.48 | 2235.28 | 0.00 | 0.00 | 0.00 |
March | 3389.11 | 1903.17 | 1485.94 | 3541.37 | 1986.90 | 0.00 | 0.00 | 0.00 |
April | 2724.28 | 1303.04 | 1421.24 | 2960.90 | 1474.13 | 0.00 | 0.00 | 0.00 |
May | 2420.45 | 803.90 | 1616.55 | 2666.59 | 1177.98 | 0.00 | 0.00 | 0.00 |
June | 2404.96 | 701.40 | 1703.56 | 3009.31 | 830.02 | 0.00 | 0.00 | 0.00 |
July | 2592.79 | 957.77 | 1635.02 | 3611.38 | 674.53 | 0.00 | 0.00 | 0.00 |
August | 3081.36 | 1553.57 | 1527.79 | 4162.56 | 757.24 | 0.00 | 0.00 | 0.00 |
September | 3417.60 | 2094.07 | 1323.53 | 4285.50 | 1051.81 | 0.00 | 0.00 | 0.00 |
October | 3572.92 | 2470.63 | 1102.29 | 4139.50 | 1433.29 | 0.00 | 0.00 | 0.00 |
November | 3257.44 | 2359.56 | 897.88 | 3468.82 | 1837.36 | 0.00 | 0.00 | 0.00 |
December | 2831.21 | 2044.42 | 786.79 | 2779.35 | 2504.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3033.18 | 1747.27 | 1285.90 | 3449.13 | 1575.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2404.96 | 701.40 | 786.79 | 2666.59 | 674.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3791.51 | 2726.99 | 1703.56 | 4285.50 | 2972.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 585.67 | 236.03 | 349.64 | 313.92 | 2229.74 | 0.00 | 0.00 | 0.00 |
February | 999.65 | 491.38 | 508.27 | 793.54 | 1625.19 | 0.00 | 0.00 | 0.00 |
March | 1279.30 | 468.76 | 810.55 | 1057.45 | 1357.66 | 0.00 | 0.00 | 0.00 |
April | 1670.14 | 739.95 | 930.19 | 1670.97 | 999.28 | 0.00 | 0.00 | 0.00 |
May | 2065.84 | 942.13 | 1123.71 | 2244.57 | 800.09 | 0.00 | 0.00 | 0.00 |
June | 2247.56 | 1032.39 | 1215.17 | 2718.55 | 566.13 | 0.00 | 0.00 | 0.00 |
July | 2302.37 | 1163.42 | 1138.95 | 3019.11 | 482.45 | 0.00 | 0.00 | 0.00 |
August | 1955.02 | 959.48 | 995.54 | 2495.58 | 517.16 | 0.00 | 0.00 | 0.00 |
September | 1572.69 | 795.09 | 777.60 | 1854.60 | 705.46 | 0.00 | 0.00 | 0.00 |
October | 1124.04 | 558.48 | 565.57 | 1133.63 | 983.34 | 0.00 | 0.00 | 0.00 |
November | 795.72 | 394.74 | 400.97 | 653.40 | 1345.90 | 0.00 | 0.00 | 0.00 |
December | 534.87 | 225.75 | 309.11 | 300.49 | 1877.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1429.68 | 667.94 | 761.74 | 1525.07 | 1122.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 534.87 | 225.75 | 309.11 | 300.49 | 482.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2302.37 | 1163.42 | 1215.17 | 3019.11 | 2229.74 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226257E+09 | 0.00 | 0.226257E+09 | 3753676.10 | 0.202956E+10 |
February | 0.288546E+09 | 0.00 | 0.288546E+09 | 34693874.04 | 0.138297E+10 |
March | 0.518951E+09 | 0.00 | 0.518951E+09 | 0.156472E+09 | 0.125367E+10 |
April | 0.572626E+09 | 3341698.05 | 0.569285E+09 | 0.281896E+09 | 0.872277E+09 |
May | 0.777062E+09 | 46045429.18 | 0.731016E+09 | 0.571505E+09 | 0.650639E+09 |
June | 0.875657E+09 | 0.100649E+09 | 0.775008E+09 | 0.901837E+09 | 0.393041E+09 |
July | 0.826626E+09 | 77422927.49 | 0.749203E+09 | 0.101359E+10 | 0.334052E+09 |
August | 0.662380E+09 | 17754750.82 | 0.644626E+09 | 0.733963E+09 | 0.386930E+09 |
September | 0.480074E+09 | 172275.45 | 0.479902E+09 | 0.410971E+09 | 0.584091E+09 |
October | 0.361859E+09 | 0.00 | 0.361859E+09 | 0.146862E+09 | 0.927367E+09 |
November | 0.238060E+09 | 0.00 | 0.238060E+09 | 27599873.72 | 0.130083E+10 |
December | 0.189730E+09 | 0.00 | 0.189730E+09 | 1123495.63 | 0.182123E+10 |
Annual Sum or Average | 0.601783E+10 | 0.245386E+09 | 0.577244E+10 | 0.428427E+10 | 0.119366E+11 |
Minimum of Months | 0.189730E+09 | 0.00 | 0.189730E+09 | 1123495.63 | 0.334052E+09 |
Maximum of Months | 0.875657E+09 | 0.100649E+09 | 0.775008E+09 | 0.101359E+10 | 0.202956E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226254E+09 | 0.00 | 0.226254E+09 | 3753318.81 | 0.202956E+10 |
February | 0.288542E+09 | 0.00 | 0.288542E+09 | 34692175.31 | 0.138297E+10 |
March | 0.518943E+09 | 0.00 | 0.518943E+09 | 0.156466E+09 | 0.125367E+10 |
April | 0.572618E+09 | 3341624.59 | 0.569277E+09 | 0.281889E+09 | 0.872278E+09 |
May | 0.777050E+09 | 46044416.92 | 0.731006E+09 | 0.571492E+09 | 0.650640E+09 |
June | 0.875644E+09 | 0.100646E+09 | 0.774998E+09 | 0.901822E+09 | 0.393040E+09 |
July | 0.826615E+09 | 77421225.44 | 0.749194E+09 | 0.101358E+10 | 0.334050E+09 |
August | 0.662372E+09 | 17754360.50 | 0.644617E+09 | 0.733953E+09 | 0.386928E+09 |
September | 0.480068E+09 | 172271.67 | 0.479896E+09 | 0.410964E+09 | 0.584090E+09 |
October | 0.361854E+09 | 0.00 | 0.361854E+09 | 0.146857E+09 | 0.927366E+09 |
November | 0.238056E+09 | 0.00 | 0.238056E+09 | 27598448.91 | 0.130083E+10 |
December | 0.189727E+09 | 0.00 | 0.189727E+09 | 1123363.47 | 0.182123E+10 |
Annual Sum or Average | 0.601774E+10 | 0.245380E+09 | 0.577236E+10 | 0.428419E+10 | 0.119366E+11 |
Minimum of Months | 0.189727E+09 | 0.00 | 0.189727E+09 | 1123363.47 | 0.334050E+09 |
Maximum of Months | 0.875644E+09 | 0.100646E+09 | 0.774998E+09 | 0.101358E+10 | 0.202956E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226255E+09 | 0.00 | 0.226255E+09 | 3753437.90 | 0.202956E+10 |
February | 0.288543E+09 | 0.00 | 0.288543E+09 | 34692741.56 | 0.138297E+10 |
March | 0.518946E+09 | 0.00 | 0.518946E+09 | 0.156468E+09 | 0.125367E+10 |
April | 0.572621E+09 | 3341649.07 | 0.569279E+09 | 0.281891E+09 | 0.872277E+09 |
May | 0.777054E+09 | 46044754.34 | 0.731009E+09 | 0.571496E+09 | 0.650640E+09 |
June | 0.875648E+09 | 0.100647E+09 | 0.775001E+09 | 0.901827E+09 | 0.393041E+09 |
July | 0.826619E+09 | 77421792.79 | 0.749197E+09 | 0.101359E+10 | 0.334051E+09 |
August | 0.662375E+09 | 17754490.60 | 0.644620E+09 | 0.733957E+09 | 0.386929E+09 |
September | 0.480070E+09 | 172272.93 | 0.479898E+09 | 0.410966E+09 | 0.584090E+09 |
October | 0.361855E+09 | 0.00 | 0.361855E+09 | 0.146859E+09 | 0.927367E+09 |
November | 0.238057E+09 | 0.00 | 0.238057E+09 | 27598923.85 | 0.130083E+10 |
December | 0.189728E+09 | 0.00 | 0.189728E+09 | 1123407.52 | 0.182123E+10 |
Annual Sum or Average | 0.601777E+10 | 0.245382E+09 | 0.577239E+10 | 0.428422E+10 | 0.119366E+11 |
Minimum of Months | 0.189728E+09 | 0.00 | 0.189728E+09 | 1123407.52 | 0.334051E+09 |
Maximum of Months | 0.875648E+09 | 0.100647E+09 | 0.775001E+09 | 0.101359E+10 | 0.202956E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226254E+09 | 0.00 | 0.226254E+09 | 3753318.81 | 0.202956E+10 |
February | 0.288542E+09 | 0.00 | 0.288542E+09 | 34692175.31 | 0.138297E+10 |
March | 0.518943E+09 | 0.00 | 0.518943E+09 | 0.156466E+09 | 0.125367E+10 |
April | 0.572618E+09 | 3341624.59 | 0.569277E+09 | 0.281889E+09 | 0.872278E+09 |
May | 0.777050E+09 | 46044416.92 | 0.731006E+09 | 0.571492E+09 | 0.650640E+09 |
June | 0.875644E+09 | 0.100646E+09 | 0.774998E+09 | 0.901822E+09 | 0.393040E+09 |
July | 0.826615E+09 | 77421225.44 | 0.749194E+09 | 0.101358E+10 | 0.334050E+09 |
August | 0.662372E+09 | 17754360.50 | 0.644617E+09 | 0.733953E+09 | 0.386928E+09 |
September | 0.480068E+09 | 172271.67 | 0.479896E+09 | 0.410964E+09 | 0.584090E+09 |
October | 0.361854E+09 | 0.00 | 0.361854E+09 | 0.146857E+09 | 0.927366E+09 |
November | 0.238056E+09 | 0.00 | 0.238056E+09 | 27598448.91 | 0.130083E+10 |
December | 0.189727E+09 | 0.00 | 0.189727E+09 | 1123363.47 | 0.182123E+10 |
Annual Sum or Average | 0.601774E+10 | 0.245380E+09 | 0.577236E+10 | 0.428419E+10 | 0.119366E+11 |
Minimum of Months | 0.189727E+09 | 0.00 | 0.189727E+09 | 1123363.47 | 0.334050E+09 |
Maximum of Months | 0.875644E+09 | 0.100646E+09 | 0.774998E+09 | 0.101358E+10 | 0.202956E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.226245E+09 | 0.00 | 0.226245E+09 | 3753227.08 | 0.202948E+10 |
February | 0.288531E+09 | 0.00 | 0.288531E+09 | 34691060.18 | 0.138291E+10 |
March | 0.518924E+09 | 0.00 | 0.518924E+09 | 0.156461E+09 | 0.125362E+10 |
April | 0.572597E+09 | 3341502.15 | 0.569255E+09 | 0.281879E+09 | 0.872242E+09 |
May | 0.777021E+09 | 46042729.83 | 0.730978E+09 | 0.571471E+09 | 0.650614E+09 |
June | 0.875611E+09 | 0.100643E+09 | 0.774968E+09 | 0.901788E+09 | 0.393025E+09 |
July | 0.826584E+09 | 77418388.69 | 0.749165E+09 | 0.101354E+10 | 0.334037E+09 |
August | 0.662346E+09 | 17753709.97 | 0.644593E+09 | 0.733926E+09 | 0.386913E+09 |
September | 0.480050E+09 | 172265.35 | 0.479877E+09 | 0.410949E+09 | 0.584066E+09 |
October | 0.361840E+09 | 0.00 | 0.361840E+09 | 0.146852E+09 | 0.927329E+09 |
November | 0.238047E+09 | 0.00 | 0.238047E+09 | 27597574.03 | 0.130078E+10 |
December | 0.189719E+09 | 0.00 | 0.189719E+09 | 1123340.22 | 0.182115E+10 |
Annual Sum or Average | 0.601751E+10 | 0.245371E+09 | 0.577214E+10 | 0.428403E+10 | 0.119362E+11 |
Minimum of Months | 0.189719E+09 | 0.00 | 0.189719E+09 | 1123340.22 | 0.334037E+09 |
Maximum of Months | 0.875611E+09 | 0.100643E+09 | 0.774968E+09 | 0.101354E+10 | 0.202948E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.577276E+09 | 0.264658E+09 | 0.312618E+09 | 0.300644E+09 | 0.205938E+10 |
February | 0.815532E+09 | 0.404892E+09 | 0.410640E+09 | 0.603376E+09 | 0.139228E+10 |
March | 0.121405E+10 | 0.502338E+09 | 0.711707E+09 | 0.984622E+09 | 0.128252E+10 |
April | 0.149903E+10 | 0.742911E+09 | 0.756124E+09 | 0.145894E+10 | 0.896202E+09 |
May | 0.171108E+10 | 0.761321E+09 | 0.949754E+09 | 0.179614E+10 | 0.720585E+09 |
June | 0.214332E+10 | 0.110295E+10 | 0.104037E+10 | 0.260181E+10 | 0.440815E+09 |
July | 0.232446E+10 | 0.131408E+10 | 0.101038E+10 | 0.304668E+10 | 0.360842E+09 |
August | 0.202006E+10 | 0.112551E+10 | 0.894544E+09 | 0.258544E+10 | 0.407669E+09 |
September | 0.138290E+10 | 0.713846E+09 | 0.669050E+09 | 0.159848E+10 | 0.605198E+09 |
October | 0.102523E+10 | 0.520594E+09 | 0.504633E+09 | 0.969483E+09 | 0.946081E+09 |
November | 0.628809E+09 | 0.293571E+09 | 0.335238E+09 | 0.423254E+09 | 0.128416E+10 |
December | 0.479242E+09 | 0.205836E+09 | 0.273407E+09 | 0.228644E+09 | 0.181286E+10 |
Annual Sum or Average | 0.158210E+11 | 0.795251E+10 | 0.786846E+10 | 0.165975E+11 | 0.122086E+11 |
Minimum of Months | 0.479242E+09 | 0.205836E+09 | 0.273407E+09 | 0.228644E+09 | 0.360842E+09 |
Maximum of Months | 0.232446E+10 | 0.131408E+10 | 0.104037E+10 | 0.304668E+10 | 0.205938E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.577276E+09 | 0.264658E+09 | 0.312618E+09 | 0.300644E+09 | 0.205938E+10 |
February | 0.815532E+09 | 0.404892E+09 | 0.410640E+09 | 0.603376E+09 | 0.139228E+10 |
March | 0.121405E+10 | 0.502338E+09 | 0.711707E+09 | 0.984622E+09 | 0.128252E+10 |
April | 0.149903E+10 | 0.742911E+09 | 0.756124E+09 | 0.145894E+10 | 0.896202E+09 |
May | 0.171108E+10 | 0.761321E+09 | 0.949754E+09 | 0.179614E+10 | 0.720585E+09 |
June | 0.214332E+10 | 0.110295E+10 | 0.104037E+10 | 0.260181E+10 | 0.440815E+09 |
July | 0.232446E+10 | 0.131408E+10 | 0.101038E+10 | 0.304668E+10 | 0.360842E+09 |
August | 0.202006E+10 | 0.112551E+10 | 0.894544E+09 | 0.258544E+10 | 0.407669E+09 |
September | 0.138290E+10 | 0.713846E+09 | 0.669050E+09 | 0.159848E+10 | 0.605198E+09 |
October | 0.102523E+10 | 0.520594E+09 | 0.504633E+09 | 0.969483E+09 | 0.946081E+09 |
November | 0.628809E+09 | 0.293571E+09 | 0.335238E+09 | 0.423254E+09 | 0.128416E+10 |
December | 0.479242E+09 | 0.205836E+09 | 0.273407E+09 | 0.228644E+09 | 0.181286E+10 |
Annual Sum or Average | 0.158210E+11 | 0.795251E+10 | 0.786846E+10 | 0.165975E+11 | 0.122086E+11 |
Minimum of Months | 0.479242E+09 | 0.205836E+09 | 0.273407E+09 | 0.228644E+09 | 0.360842E+09 |
Maximum of Months | 0.232446E+10 | 0.131408E+10 | 0.104037E+10 | 0.304668E+10 | 0.205938E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.577265E+09 | 0.264653E+09 | 0.312612E+09 | 0.300638E+09 | 0.205934E+10 |
February | 0.815517E+09 | 0.404885E+09 | 0.410632E+09 | 0.603365E+09 | 0.139226E+10 |
March | 0.121402E+10 | 0.502329E+09 | 0.711694E+09 | 0.984604E+09 | 0.128249E+10 |
April | 0.149901E+10 | 0.742897E+09 | 0.756110E+09 | 0.145892E+10 | 0.896186E+09 |
May | 0.171104E+10 | 0.761307E+09 | 0.949737E+09 | 0.179611E+10 | 0.720572E+09 |
June | 0.214328E+10 | 0.110293E+10 | 0.104035E+10 | 0.260177E+10 | 0.440807E+09 |
July | 0.232442E+10 | 0.131405E+10 | 0.101036E+10 | 0.304662E+10 | 0.360835E+09 |
August | 0.202002E+10 | 0.112549E+10 | 0.894528E+09 | 0.258539E+10 | 0.407661E+09 |
September | 0.138287E+10 | 0.713832E+09 | 0.669038E+09 | 0.159845E+10 | 0.605187E+09 |
October | 0.102521E+10 | 0.520585E+09 | 0.504624E+09 | 0.969465E+09 | 0.946064E+09 |
November | 0.628797E+09 | 0.293566E+09 | 0.335232E+09 | 0.423246E+09 | 0.128414E+10 |
December | 0.479234E+09 | 0.205832E+09 | 0.273402E+09 | 0.228640E+09 | 0.181283E+10 |
Annual Sum or Average | 0.158207E+11 | 0.795236E+10 | 0.786832E+10 | 0.165972E+11 | 0.122084E+11 |
Minimum of Months | 0.479234E+09 | 0.205832E+09 | 0.273402E+09 | 0.228640E+09 | 0.360835E+09 |
Maximum of Months | 0.232442E+10 | 0.131405E+10 | 0.104035E+10 | 0.304662E+10 | 0.205934E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.159483E+10 | 0.113906E+10 | 0.455773E+09 | 0.150454E+10 | 0.170307E+10 |
February | 0.183445E+10 | 0.131940E+10 | 0.515047E+09 | 0.190452E+10 | 0.117655E+10 |
March | 0.181545E+10 | 0.101947E+10 | 0.795978E+09 | 0.187736E+10 | 0.117486E+10 |
April | 0.141224E+10 | 0.675481E+09 | 0.736761E+09 | 0.151497E+10 | 0.858871E+09 |
May | 0.129657E+10 | 0.430623E+09 | 0.865946E+09 | 0.142088E+10 | 0.688756E+09 |
June | 0.124672E+10 | 0.363599E+09 | 0.883117E+09 | 0.156248E+10 | 0.450644E+09 |
July | 0.138889E+10 | 0.513047E+09 | 0.875841E+09 | 0.194246E+10 | 0.367160E+09 |
August | 0.165060E+10 | 0.832197E+09 | 0.818401E+09 | 0.223982E+10 | 0.416815E+09 |
September | 0.177165E+10 | 0.108554E+10 | 0.686108E+09 | 0.223051E+10 | 0.581958E+09 |
October | 0.191390E+10 | 0.132344E+10 | 0.590467E+09 | 0.220381E+10 | 0.860076E+09 |
November | 0.168863E+10 | 0.122317E+10 | 0.465455E+09 | 0.176429E+10 | 0.108062E+10 |
December | 0.151659E+10 | 0.109513E+10 | 0.421461E+09 | 0.145306E+10 | 0.149423E+10 |
Annual Sum or Average | 0.191305E+11 | 0.110202E+11 | 0.811035E+10 | 0.216187E+11 | 0.108536E+11 |
Minimum of Months | 0.124672E+10 | 0.363599E+09 | 0.421461E+09 | 0.142088E+10 | 0.367160E+09 |
Maximum of Months | 0.191390E+10 | 0.132344E+10 | 0.883117E+09 | 0.223982E+10 | 0.170307E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.159482E+10 | 0.113905E+10 | 0.455770E+09 | 0.150453E+10 | 0.170307E+10 |
February | 0.183443E+10 | 0.131939E+10 | 0.515044E+09 | 0.190450E+10 | 0.117655E+10 |
March | 0.181543E+10 | 0.101946E+10 | 0.795974E+09 | 0.187734E+10 | 0.117486E+10 |
April | 0.141223E+10 | 0.675477E+09 | 0.736757E+09 | 0.151496E+10 | 0.858871E+09 |
May | 0.129656E+10 | 0.430620E+09 | 0.865941E+09 | 0.142087E+10 | 0.688756E+09 |
June | 0.124671E+10 | 0.363596E+09 | 0.883113E+09 | 0.156247E+10 | 0.450644E+09 |
July | 0.138888E+10 | 0.513043E+09 | 0.875837E+09 | 0.194245E+10 | 0.367160E+09 |
August | 0.165059E+10 | 0.832191E+09 | 0.818397E+09 | 0.223981E+10 | 0.416814E+09 |
September | 0.177164E+10 | 0.108554E+10 | 0.686104E+09 | 0.223049E+10 | 0.581958E+09 |
October | 0.191389E+10 | 0.132343E+10 | 0.590463E+09 | 0.220379E+10 | 0.860076E+09 |
November | 0.168861E+10 | 0.122316E+10 | 0.465452E+09 | 0.176427E+10 | 0.108062E+10 |
December | 0.151658E+10 | 0.109513E+10 | 0.421459E+09 | 0.145305E+10 | 0.149423E+10 |
Annual Sum or Average | 0.191304E+11 | 0.110201E+11 | 0.811031E+10 | 0.216185E+11 | 0.108536E+11 |
Minimum of Months | 0.124671E+10 | 0.363596E+09 | 0.421459E+09 | 0.142087E+10 | 0.367160E+09 |
Maximum of Months | 0.191389E+10 | 0.132343E+10 | 0.883113E+09 | 0.223981E+10 | 0.170307E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.159483E+10 | 0.113906E+10 | 0.455773E+09 | 0.150454E+10 | 0.170307E+10 |
February | 0.183445E+10 | 0.131940E+10 | 0.515047E+09 | 0.190452E+10 | 0.117655E+10 |
March | 0.181545E+10 | 0.101947E+10 | 0.795978E+09 | 0.187736E+10 | 0.117486E+10 |
April | 0.141224E+10 | 0.675481E+09 | 0.736761E+09 | 0.151497E+10 | 0.858871E+09 |
May | 0.129657E+10 | 0.430623E+09 | 0.865946E+09 | 0.142088E+10 | 0.688756E+09 |
June | 0.124672E+10 | 0.363599E+09 | 0.883117E+09 | 0.156248E+10 | 0.450644E+09 |
July | 0.138889E+10 | 0.513047E+09 | 0.875841E+09 | 0.194246E+10 | 0.367160E+09 |
August | 0.165060E+10 | 0.832197E+09 | 0.818401E+09 | 0.223982E+10 | 0.416815E+09 |
September | 0.177165E+10 | 0.108554E+10 | 0.686108E+09 | 0.223051E+10 | 0.581958E+09 |
October | 0.191390E+10 | 0.132344E+10 | 0.590467E+09 | 0.220381E+10 | 0.860076E+09 |
November | 0.168863E+10 | 0.122317E+10 | 0.465455E+09 | 0.176429E+10 | 0.108062E+10 |
December | 0.151659E+10 | 0.109513E+10 | 0.421461E+09 | 0.145306E+10 | 0.149423E+10 |
Annual Sum or Average | 0.191305E+11 | 0.110202E+11 | 0.811035E+10 | 0.216187E+11 | 0.108536E+11 |
Minimum of Months | 0.124672E+10 | 0.363599E+09 | 0.421461E+09 | 0.142088E+10 | 0.367160E+09 |
Maximum of Months | 0.191390E+10 | 0.132344E+10 | 0.883117E+09 | 0.223982E+10 | 0.170307E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.159482E+10 | 0.113905E+10 | 0.455770E+09 | 0.150453E+10 | 0.170307E+10 |
February | 0.183443E+10 | 0.131939E+10 | 0.515044E+09 | 0.190450E+10 | 0.117655E+10 |
March | 0.181543E+10 | 0.101946E+10 | 0.795974E+09 | 0.187734E+10 | 0.117486E+10 |
April | 0.141223E+10 | 0.675477E+09 | 0.736757E+09 | 0.151496E+10 | 0.858871E+09 |
May | 0.129656E+10 | 0.430620E+09 | 0.865941E+09 | 0.142087E+10 | 0.688756E+09 |
June | 0.124671E+10 | 0.363596E+09 | 0.883113E+09 | 0.156247E+10 | 0.450644E+09 |
July | 0.138888E+10 | 0.513043E+09 | 0.875837E+09 | 0.194245E+10 | 0.367160E+09 |
August | 0.165059E+10 | 0.832191E+09 | 0.818397E+09 | 0.223981E+10 | 0.416814E+09 |
September | 0.177164E+10 | 0.108554E+10 | 0.686104E+09 | 0.223049E+10 | 0.581958E+09 |
October | 0.191389E+10 | 0.132343E+10 | 0.590463E+09 | 0.220379E+10 | 0.860076E+09 |
November | 0.168861E+10 | 0.122316E+10 | 0.465452E+09 | 0.176427E+10 | 0.108062E+10 |
December | 0.151658E+10 | 0.109513E+10 | 0.421459E+09 | 0.145305E+10 | 0.149423E+10 |
Annual Sum or Average | 0.191304E+11 | 0.110201E+11 | 0.811031E+10 | 0.216185E+11 | 0.108536E+11 |
Minimum of Months | 0.124671E+10 | 0.363596E+09 | 0.421459E+09 | 0.142087E+10 | 0.367160E+09 |
Maximum of Months | 0.191389E+10 | 0.132343E+10 | 0.883113E+09 | 0.223981E+10 | 0.170307E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.159476E+10 | 0.113901E+10 | 0.455753E+09 | 0.150448E+10 | 0.170300E+10 |
February | 0.183437E+10 | 0.131934E+10 | 0.515024E+09 | 0.190444E+10 | 0.117650E+10 |
March | 0.181537E+10 | 0.101942E+10 | 0.795944E+09 | 0.187727E+10 | 0.117481E+10 |
April | 0.141218E+10 | 0.675452E+09 | 0.736729E+09 | 0.151491E+10 | 0.858837E+09 |
May | 0.129651E+10 | 0.430604E+09 | 0.865908E+09 | 0.142082E+10 | 0.688729E+09 |
June | 0.124666E+10 | 0.363583E+09 | 0.883079E+09 | 0.156241E+10 | 0.450625E+09 |
July | 0.138883E+10 | 0.513024E+09 | 0.875803E+09 | 0.194238E+10 | 0.367145E+09 |
August | 0.165053E+10 | 0.832161E+09 | 0.818366E+09 | 0.223972E+10 | 0.416798E+09 |
September | 0.177158E+10 | 0.108550E+10 | 0.686078E+09 | 0.223041E+10 | 0.581935E+09 |
October | 0.191382E+10 | 0.132338E+10 | 0.590441E+09 | 0.220371E+10 | 0.860041E+09 |
November | 0.168855E+10 | 0.122312E+10 | 0.465435E+09 | 0.176421E+10 | 0.108057E+10 |
December | 0.151653E+10 | 0.109509E+10 | 0.421443E+09 | 0.145300E+10 | 0.149417E+10 |
Annual Sum or Average | 0.191297E+11 | 0.110197E+11 | 0.811000E+10 | 0.216177E+11 | 0.108532E+11 |
Minimum of Months | 0.124666E+10 | 0.363583E+09 | 0.421443E+09 | 0.142082E+10 | 0.367145E+09 |
Maximum of Months | 0.191382E+10 | 0.132338E+10 | 0.883079E+09 | 0.223972E+10 | 0.170300E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.522889E+09 | 0.210728E+09 | 0.312161E+09 | 0.258946E+09 | 0.221925E+10 |
February | 0.806123E+09 | 0.396250E+09 | 0.409873E+09 | 0.592108E+09 | 0.152983E+10 |
March | 0.114217E+10 | 0.418510E+09 | 0.723664E+09 | 0.871453E+09 | 0.146814E+10 |
April | 0.144301E+10 | 0.639322E+09 | 0.803692E+09 | 0.136934E+10 | 0.107664E+10 |
May | 0.184440E+10 | 0.841146E+09 | 0.100326E+10 | 0.197313E+10 | 0.813103E+09 |
June | 0.194191E+10 | 0.891991E+09 | 0.104992E+10 | 0.232866E+10 | 0.540462E+09 |
July | 0.205558E+10 | 0.103871E+10 | 0.101686E+10 | 0.267712E+10 | 0.468865E+09 |
August | 0.174546E+10 | 0.856636E+09 | 0.888826E+09 | 0.219880E+10 | 0.524907E+09 |
September | 0.135882E+10 | 0.686965E+09 | 0.671857E+09 | 0.157739E+10 | 0.694554E+09 |
October | 0.100356E+10 | 0.498613E+09 | 0.504944E+09 | 0.947906E+09 | 0.108788E+10 |
November | 0.687506E+09 | 0.341062E+09 | 0.346444E+09 | 0.507602E+09 | 0.147579E+10 |
December | 0.477534E+09 | 0.201554E+09 | 0.275980E+09 | 0.229691E+09 | 0.206919E+10 |
Annual Sum or Average | 0.150290E+11 | 0.702149E+10 | 0.800748E+10 | 0.155322E+11 | 0.139686E+11 |
Minimum of Months | 0.477534E+09 | 0.201554E+09 | 0.275980E+09 | 0.229691E+09 | 0.468865E+09 |
Maximum of Months | 0.205558E+10 | 0.103871E+10 | 0.104992E+10 | 0.267712E+10 | 0.221925E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.522889E+09 | 0.210728E+09 | 0.312161E+09 | 0.258946E+09 | 0.221925E+10 |
February | 0.806123E+09 | 0.396250E+09 | 0.409873E+09 | 0.592108E+09 | 0.152983E+10 |
March | 0.114217E+10 | 0.418510E+09 | 0.723664E+09 | 0.871453E+09 | 0.146814E+10 |
April | 0.144301E+10 | 0.639322E+09 | 0.803692E+09 | 0.136934E+10 | 0.107664E+10 |
May | 0.184440E+10 | 0.841146E+09 | 0.100326E+10 | 0.197313E+10 | 0.813103E+09 |
June | 0.194191E+10 | 0.891991E+09 | 0.104992E+10 | 0.232866E+10 | 0.540462E+09 |
July | 0.205558E+10 | 0.103871E+10 | 0.101686E+10 | 0.267712E+10 | 0.468865E+09 |
August | 0.174546E+10 | 0.856636E+09 | 0.888826E+09 | 0.219880E+10 | 0.524907E+09 |
September | 0.135882E+10 | 0.686965E+09 | 0.671857E+09 | 0.157739E+10 | 0.694554E+09 |
October | 0.100356E+10 | 0.498613E+09 | 0.504944E+09 | 0.947906E+09 | 0.108788E+10 |
November | 0.687506E+09 | 0.341062E+09 | 0.346444E+09 | 0.507602E+09 | 0.147579E+10 |
December | 0.477534E+09 | 0.201554E+09 | 0.275980E+09 | 0.229691E+09 | 0.206919E+10 |
Annual Sum or Average | 0.150290E+11 | 0.702149E+10 | 0.800748E+10 | 0.155322E+11 | 0.139686E+11 |
Minimum of Months | 0.477534E+09 | 0.201554E+09 | 0.275980E+09 | 0.229691E+09 | 0.468865E+09 |
Maximum of Months | 0.205558E+10 | 0.103871E+10 | 0.104992E+10 | 0.267712E+10 | 0.221925E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.522880E+09 | 0.210724E+09 | 0.312155E+09 | 0.258941E+09 | 0.221921E+10 |
February | 0.806108E+09 | 0.396243E+09 | 0.409865E+09 | 0.592097E+09 | 0.152980E+10 |
March | 0.114215E+10 | 0.418502E+09 | 0.723651E+09 | 0.871437E+09 | 0.146811E+10 |
April | 0.144299E+10 | 0.639310E+09 | 0.803677E+09 | 0.136931E+10 | 0.107663E+10 |
May | 0.184437E+10 | 0.841131E+09 | 0.100324E+10 | 0.197310E+10 | 0.813088E+09 |
June | 0.194187E+10 | 0.891975E+09 | 0.104990E+10 | 0.232862E+10 | 0.540452E+09 |
July | 0.205554E+10 | 0.103869E+10 | 0.101685E+10 | 0.267707E+10 | 0.468857E+09 |
August | 0.174543E+10 | 0.856621E+09 | 0.888810E+09 | 0.219876E+10 | 0.524898E+09 |
September | 0.135880E+10 | 0.686952E+09 | 0.671844E+09 | 0.157736E+10 | 0.694541E+09 |
October | 0.100354E+10 | 0.498604E+09 | 0.504934E+09 | 0.947889E+09 | 0.108786E+10 |
November | 0.687493E+09 | 0.341055E+09 | 0.346438E+09 | 0.507593E+09 | 0.147577E+10 |
December | 0.477525E+09 | 0.201550E+09 | 0.275975E+09 | 0.229687E+09 | 0.206915E+10 |
Annual Sum or Average | 0.150287E+11 | 0.702136E+10 | 0.800733E+10 | 0.155319E+11 | 0.139684E+11 |
Minimum of Months | 0.477525E+09 | 0.201550E+09 | 0.275975E+09 | 0.229687E+09 | 0.468857E+09 |
Maximum of Months | 0.205554E+10 | 0.103869E+10 | 0.104990E+10 | 0.267707E+10 | 0.221921E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113129E+10 | 0.00 | 0.113129E+10 | 37104057.49 | 0.953486E+10 |
February | 0.144273E+10 | 0.00 | 0.144273E+10 | 0.268695E+09 | 0.635571E+10 |
March | 0.259476E+10 | 0.00 | 0.259476E+10 | 0.964373E+09 | 0.567712E+10 |
April | 0.286313E+10 | 16708596.73 | 0.284642E+10 | 0.158228E+10 | 0.391960E+10 |
May | 0.388531E+10 | 0.230229E+09 | 0.365508E+10 | 0.297064E+10 | 0.303873E+10 |
June | 0.437828E+10 | 0.503247E+09 | 0.387504E+10 | 0.456652E+10 | 0.189232E+10 |
July | 0.413313E+10 | 0.387117E+09 | 0.374601E+10 | 0.512456E+10 | 0.162475E+10 |
August | 0.331190E+10 | 88774319.81 | 0.322312E+10 | 0.373302E+10 | 0.185991E+10 |
September | 0.240037E+10 | 861382.76 | 0.239951E+10 | 0.212949E+10 | 0.273244E+10 |
October | 0.180929E+10 | 0.00 | 0.180929E+10 | 0.870141E+09 | 0.416401E+10 |
November | 0.119030E+10 | 0.00 | 0.119030E+10 | 0.208219E+09 | 0.574507E+10 |
December | 0.948649E+09 | 0.00 | 0.948649E+09 | 21550712.82 | 0.814334E+10 |
Annual Sum or Average | 0.300891E+11 | 0.122694E+10 | 0.288622E+11 | 0.224766E+11 | 0.546879E+11 |
Minimum of Months | 0.948649E+09 | 0.00 | 0.948649E+09 | 21550712.82 | 0.162475E+10 |
Maximum of Months | 0.437828E+10 | 0.503247E+09 | 0.387504E+10 | 0.512456E+10 | 0.953486E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173181E+10 | 0.793965E+09 | 0.937845E+09 | 0.943860E+09 | 0.586837E+10 |
February | 0.244657E+10 | 0.121466E+10 | 0.123191E+10 | 0.187585E+10 | 0.391774E+10 |
March | 0.364210E+10 | 0.150700E+10 | 0.213510E+10 | 0.303294E+10 | 0.359404E+10 |
April | 0.449706E+10 | 0.222871E+10 | 0.226835E+10 | 0.441555E+10 | 0.252778E+10 |
May | 0.513317E+10 | 0.228394E+10 | 0.284923E+10 | 0.540064E+10 | 0.205525E+10 |
June | 0.642990E+10 | 0.330882E+10 | 0.312108E+10 | 0.777403E+10 | 0.130684E+10 |
July | 0.697330E+10 | 0.394219E+10 | 0.303111E+10 | 0.909815E+10 | 0.110286E+10 |
August | 0.606011E+10 | 0.337651E+10 | 0.268361E+10 | 0.771993E+10 | 0.124564E+10 |
September | 0.414864E+10 | 0.214151E+10 | 0.200713E+10 | 0.479617E+10 | 0.174258E+10 |
October | 0.307565E+10 | 0.156177E+10 | 0.151388E+10 | 0.296383E+10 | 0.263670E+10 |
November | 0.188641E+10 | 0.880704E+09 | 0.100570E+10 | 0.133934E+10 | 0.352222E+10 |
December | 0.143771E+10 | 0.617501E+09 | 0.820212E+09 | 0.742335E+09 | 0.500281E+10 |
Annual Sum or Average | 0.474624E+11 | 0.238573E+11 | 0.236052E+11 | 0.501026E+11 | 0.345228E+11 |
Minimum of Months | 0.143771E+10 | 0.617501E+09 | 0.820212E+09 | 0.742335E+09 | 0.110286E+10 |
Maximum of Months | 0.697330E+10 | 0.394219E+10 | 0.312108E+10 | 0.909815E+10 | 0.586837E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.797431E+10 | 0.569541E+10 | 0.227890E+10 | 0.751622E+10 | 0.833956E+10 |
February | 0.917241E+10 | 0.659714E+10 | 0.257527E+10 | 0.950180E+10 | 0.571689E+10 |
March | 0.907740E+10 | 0.509745E+10 | 0.397995E+10 | 0.937518E+10 | 0.567867E+10 |
April | 0.706133E+10 | 0.337748E+10 | 0.368385E+10 | 0.757635E+10 | 0.412348E+10 |
May | 0.648294E+10 | 0.215316E+10 | 0.432978E+10 | 0.708745E+10 | 0.335163E+10 |
June | 0.623366E+10 | 0.181803E+10 | 0.441563E+10 | 0.779540E+10 | 0.221404E+10 |
July | 0.694453E+10 | 0.256529E+10 | 0.437924E+10 | 0.969661E+10 | 0.182387E+10 |
August | 0.825312E+10 | 0.416107E+10 | 0.409204E+10 | 0.111649E+11 | 0.207092E+10 |
September | 0.885842E+10 | 0.542784E+10 | 0.343058E+10 | 0.110811E+11 | 0.287132E+10 |
October | 0.956970E+10 | 0.661733E+10 | 0.295237E+10 | 0.109687E+11 | 0.419675E+10 |
November | 0.844329E+10 | 0.611598E+10 | 0.232731E+10 | 0.882657E+10 | 0.520975E+10 |
December | 0.758312E+10 | 0.547578E+10 | 0.210734E+10 | 0.732452E+10 | 0.711770E+10 |
Annual Sum or Average | 0.956542E+11 | 0.551020E+11 | 0.405523E+11 | 0.107915E+12 | 0.527146E+11 |
Minimum of Months | 0.623366E+10 | 0.181803E+10 | 0.210734E+10 | 0.708745E+10 | 0.182387E+10 |
Maximum of Months | 0.956970E+10 | 0.661733E+10 | 0.441563E+10 | 0.111649E+11 | 0.833956E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156865E+10 | 0.632178E+09 | 0.936473E+09 | 0.816960E+09 | 0.620619E+10 |
February | 0.241834E+10 | 0.118874E+10 | 0.122960E+10 | 0.188318E+10 | 0.411639E+10 |
March | 0.342649E+10 | 0.125552E+10 | 0.217097E+10 | 0.278084E+10 | 0.384416E+10 |
April | 0.432900E+10 | 0.191795E+10 | 0.241105E+10 | 0.426987E+10 | 0.276929E+10 |
May | 0.553315E+10 | 0.252341E+10 | 0.300974E+10 | 0.597995E+10 | 0.226015E+10 |
June | 0.582567E+10 | 0.267595E+10 | 0.314972E+10 | 0.704561E+10 | 0.150450E+10 |
July | 0.616667E+10 | 0.311611E+10 | 0.305056E+10 | 0.810263E+10 | 0.130289E+10 |
August | 0.523634E+10 | 0.256988E+10 | 0.266645E+10 | 0.668943E+10 | 0.141277E+10 |
September | 0.407642E+10 | 0.206087E+10 | 0.201555E+10 | 0.478224E+10 | 0.192266E+10 |
October | 0.301064E+10 | 0.149582E+10 | 0.151482E+10 | 0.296658E+10 | 0.285783E+10 |
November | 0.206250E+10 | 0.102317E+10 | 0.103932E+10 | 0.164034E+10 | 0.376431E+10 |
December | 0.143259E+10 | 0.604655E+09 | 0.827933E+09 | 0.781697E+09 | 0.527516E+10 |
Annual Sum or Average | 0.450864E+11 | 0.210643E+11 | 0.240222E+11 | 0.477393E+11 | 0.372363E+11 |
Minimum of Months | 0.143259E+10 | 0.604655E+09 | 0.827933E+09 | 0.781697E+09 | 0.130289E+10 |
Maximum of Months | 0.616667E+10 | 0.311611E+10 | 0.314972E+10 | 0.810263E+10 | 0.620619E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113129E+10 | 0.00 | 0.113129E+10 | 55204646.23 | 0.918330E+10 |
February | 0.144273E+10 | 0.00 | 0.144273E+10 | 0.321851E+09 | 0.604227E+10 |
March | 0.259476E+10 | 0.00 | 0.259476E+10 | 0.106251E+10 | 0.531571E+10 |
April | 0.286313E+10 | 16708596.73 | 0.284642E+10 | 0.171682E+10 | 0.358774E+10 |
May | 0.388531E+10 | 0.230229E+09 | 0.365508E+10 | 0.307392E+10 | 0.283337E+10 |
June | 0.437828E+10 | 0.503247E+09 | 0.387504E+10 | 0.460414E+10 | 0.183246E+10 |
July | 0.413313E+10 | 0.387117E+09 | 0.374601E+10 | 0.512138E+10 | 0.160461E+10 |
August | 0.331190E+10 | 88774319.81 | 0.322312E+10 | 0.375026E+10 | 0.180412E+10 |
September | 0.240037E+10 | 861382.76 | 0.239951E+10 | 0.220065E+10 | 0.254669E+10 |
October | 0.180929E+10 | 0.00 | 0.180929E+10 | 0.100814E+10 | 0.374111E+10 |
November | 0.119030E+10 | 0.00 | 0.119030E+10 | 0.263591E+09 | 0.525309E+10 |
December | 0.948649E+09 | 0.00 | 0.948649E+09 | 27357747.57 | 0.774848E+10 |
Annual Sum or Average | 0.300891E+11 | 0.122694E+10 | 0.288622E+11 | 0.232058E+11 | 0.514929E+11 |
Minimum of Months | 0.948649E+09 | 0.00 | 0.948649E+09 | 27357747.57 | 0.160461E+10 |
Maximum of Months | 0.437828E+10 | 0.503247E+09 | 0.387504E+10 | 0.512138E+10 | 0.918330E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.173181E+10 | 0.793965E+09 | 0.937845E+09 | 0.976015E+09 | 0.565257E+10 |
February | 0.244657E+10 | 0.121466E+10 | 0.123191E+10 | 0.193659E+10 | 0.372763E+10 |
March | 0.364210E+10 | 0.150700E+10 | 0.213510E+10 | 0.311474E+10 | 0.337665E+10 |
April | 0.449706E+10 | 0.222871E+10 | 0.226835E+10 | 0.449083E+10 | 0.234924E+10 |
May | 0.513317E+10 | 0.228394E+10 | 0.284923E+10 | 0.543755E+10 | 0.194285E+10 |
June | 0.642990E+10 | 0.330882E+10 | 0.312108E+10 | 0.776974E+10 | 0.128351E+10 |
July | 0.697330E+10 | 0.394219E+10 | 0.303111E+10 | 0.907479E+10 | 0.110193E+10 |
August | 0.606011E+10 | 0.337651E+10 | 0.268361E+10 | 0.770888E+10 | 0.122810E+10 |
September | 0.414864E+10 | 0.214151E+10 | 0.200713E+10 | 0.482380E+10 | 0.166009E+10 |
October | 0.307565E+10 | 0.156177E+10 | 0.151388E+10 | 0.306421E+10 | 0.240199E+10 |
November | 0.188641E+10 | 0.880704E+09 | 0.100570E+10 | 0.141571E+10 | 0.322980E+10 |
December | 0.143771E+10 | 0.617501E+09 | 0.820212E+09 | 0.773176E+09 | 0.475839E+10 |
Annual Sum or Average | 0.474624E+11 | 0.238573E+11 | 0.236052E+11 | 0.505860E+11 | 0.327127E+11 |
Minimum of Months | 0.143771E+10 | 0.617501E+09 | 0.820212E+09 | 0.773176E+09 | 0.110193E+10 |
Maximum of Months | 0.697330E+10 | 0.394219E+10 | 0.312108E+10 | 0.907479E+10 | 0.565257E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.797431E+10 | 0.569541E+10 | 0.227890E+10 | 0.761416E+10 | 0.796211E+10 |
February | 0.917241E+10 | 0.659714E+10 | 0.257527E+10 | 0.960297E+10 | 0.540758E+10 |
March | 0.907740E+10 | 0.509745E+10 | 0.397995E+10 | 0.948521E+10 | 0.532172E+10 |
April | 0.706133E+10 | 0.337748E+10 | 0.368385E+10 | 0.767465E+10 | 0.382094E+10 |
May | 0.648294E+10 | 0.215316E+10 | 0.432978E+10 | 0.714221E+10 | 0.315511E+10 |
June | 0.623366E+10 | 0.181803E+10 | 0.441563E+10 | 0.780014E+10 | 0.215141E+10 |
July | 0.694453E+10 | 0.256529E+10 | 0.437924E+10 | 0.967273E+10 | 0.180667E+10 |
August | 0.825312E+10 | 0.416107E+10 | 0.409204E+10 | 0.111490E+11 | 0.202819E+10 |
September | 0.885842E+10 | 0.542784E+10 | 0.343058E+10 | 0.111080E+11 | 0.272630E+10 |
October | 0.956970E+10 | 0.661733E+10 | 0.295237E+10 | 0.110872E+11 | 0.383891E+10 |
November | 0.844329E+10 | 0.611598E+10 | 0.232731E+10 | 0.899118E+10 | 0.476243E+10 |
December | 0.758312E+10 | 0.547578E+10 | 0.210734E+10 | 0.744420E+10 | 0.670880E+10 |
Annual Sum or Average | 0.956542E+11 | 0.551020E+11 | 0.405523E+11 | 0.108772E+12 | 0.496902E+11 |
Minimum of Months | 0.623366E+10 | 0.181803E+10 | 0.210734E+10 | 0.714221E+10 | 0.180667E+10 |
Maximum of Months | 0.956970E+10 | 0.661733E+10 | 0.441563E+10 | 0.111490E+11 | 0.796211E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156865E+10 | 0.632178E+09 | 0.936473E+09 | 0.840807E+09 | 0.597215E+10 |
February | 0.241834E+10 | 0.118874E+10 | 0.122960E+10 | 0.191972E+10 | 0.393165E+10 |
March | 0.342649E+10 | 0.125552E+10 | 0.217097E+10 | 0.283228E+10 | 0.363636E+10 |
April | 0.432900E+10 | 0.191795E+10 | 0.241105E+10 | 0.433116E+10 | 0.259014E+10 |
May | 0.553315E+10 | 0.252341E+10 | 0.300974E+10 | 0.601186E+10 | 0.214297E+10 |
June | 0.582567E+10 | 0.267595E+10 | 0.314972E+10 | 0.704648E+10 | 0.146741E+10 |
July | 0.616667E+10 | 0.311611E+10 | 0.305056E+10 | 0.808638E+10 | 0.129218E+10 |
August | 0.523634E+10 | 0.256988E+10 | 0.266645E+10 | 0.668417E+10 | 0.138517E+10 |
September | 0.407642E+10 | 0.206087E+10 | 0.201555E+10 | 0.480713E+10 | 0.182856E+10 |
October | 0.301064E+10 | 0.149582E+10 | 0.151482E+10 | 0.303631E+10 | 0.263378E+10 |
November | 0.206250E+10 | 0.102317E+10 | 0.103932E+10 | 0.169360E+10 | 0.348858E+10 |
December | 0.143259E+10 | 0.604655E+09 | 0.827933E+09 | 0.804832E+09 | 0.502903E+10 |
Annual Sum or Average | 0.450864E+11 | 0.210643E+11 | 0.240222E+11 | 0.480947E+11 | 0.353980E+11 |
Minimum of Months | 0.143259E+10 | 0.604655E+09 | 0.827933E+09 | 0.804832E+09 | 0.129218E+10 |
Maximum of Months | 0.616667E+10 | 0.311611E+10 | 0.314972E+10 | 0.808638E+10 | 0.597215E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.01 | 3788.73 | 422.37 | 0.00 | 422.37 | 0.00 | 0.00 |
February | 71.70 | 2858.29 | 596.36 | 0.00 | 596.36 | 0.00 | 0.00 |
March | 292.09 | 2340.31 | 968.75 | 0.00 | 968.75 | 0.00 | 0.00 |
April | 543.77 | 1682.62 | 1104.58 | 6.45 | 1098.14 | 0.00 | 0.00 |
May | 1066.85 | 1214.60 | 1450.58 | 85.95 | 1364.63 | 0.00 | 0.00 |
June | 1739.62 | 758.17 | 1689.12 | 194.15 | 1494.97 | 0.00 | 0.00 |
July | 1892.13 | 623.60 | 1543.11 | 144.53 | 1398.58 | 0.00 | 0.00 |
August | 1370.13 | 722.31 | 1236.50 | 33.14 | 1203.36 | 0.00 | 0.00 |
September | 792.75 | 1126.71 | 926.05 | 0.33 | 925.72 | 0.00 | 0.00 |
October | 274.15 | 1731.18 | 675.50 | 0.00 | 675.50 | 0.00 | 0.00 |
November | 53.24 | 2509.29 | 459.21 | 0.00 | 459.21 | 0.00 | 0.00 |
December | 2.10 | 3399.81 | 354.18 | 0.00 | 354.18 | 0.00 | 0.00 |
Annual Sum or Average | 679.25 | 1892.53 | 954.10 | 38.90 | 915.20 | 0.00 | 0.00 |
Minimum of Months | 2.10 | 623.60 | 354.18 | 0.00 | 354.18 | 0.00 | 0.00 |
Maximum of Months | 1892.13 | 3788.73 | 1689.12 | 194.15 | 1494.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 336.74 | 2306.64 | 646.59 | 296.43 | 350.15 | 0.00 | 0.00 |
February | 748.23 | 1726.53 | 1011.32 | 502.10 | 509.22 | 0.00 | 0.00 |
March | 1102.84 | 1436.50 | 1359.81 | 562.65 | 797.16 | 0.00 | 0.00 |
April | 1688.58 | 1037.26 | 1734.98 | 859.85 | 875.14 | 0.00 | 0.00 |
May | 2011.79 | 807.10 | 1916.52 | 852.73 | 1063.79 | 0.00 | 0.00 |
June | 3011.34 | 510.20 | 2480.68 | 1276.56 | 1204.12 | 0.00 | 0.00 |
July | 3412.48 | 404.17 | 2603.54 | 1471.85 | 1131.69 | 0.00 | 0.00 |
August | 2895.86 | 456.62 | 2262.60 | 1260.65 | 1001.95 | 0.00 | 0.00 |
September | 1850.08 | 700.46 | 1600.56 | 826.21 | 774.36 | 0.00 | 0.00 |
October | 1085.88 | 1059.67 | 1148.32 | 583.10 | 565.22 | 0.00 | 0.00 |
November | 489.87 | 1486.29 | 727.78 | 339.78 | 388.00 | 0.00 | 0.00 |
December | 256.10 | 2030.53 | 536.78 | 230.55 | 306.23 | 0.00 | 0.00 |
Annual Sum or Average | 1578.90 | 1161.39 | 1505.03 | 756.51 | 748.52 | 0.00 | 0.00 |
Minimum of Months | 256.10 | 404.17 | 536.78 | 230.55 | 306.23 | 0.00 | 0.00 |
Maximum of Months | 3412.48 | 2306.64 | 2603.54 | 1471.85 | 1204.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2808.63 | 3179.24 | 2977.17 | 2126.35 | 850.82 | 0.00 | 0.00 |
February | 3936.21 | 2431.67 | 3791.39 | 2726.90 | 1064.49 | 0.00 | 0.00 |
March | 3504.58 | 2193.19 | 3389.01 | 1903.11 | 1485.91 | 0.00 | 0.00 |
April | 2922.37 | 1656.76 | 2724.20 | 1303.00 | 1421.21 | 0.00 | 0.00 |
May | 2652.44 | 1285.75 | 2420.39 | 803.87 | 1616.52 | 0.00 | 0.00 |
June | 3014.01 | 869.29 | 2404.90 | 701.38 | 1703.53 | 0.00 | 0.00 |
July | 3626.12 | 685.40 | 2592.73 | 957.74 | 1634.99 | 0.00 | 0.00 |
August | 4181.22 | 778.10 | 3081.28 | 1553.52 | 1527.76 | 0.00 | 0.00 |
September | 4302.63 | 1122.60 | 3417.50 | 2094.01 | 1323.50 | 0.00 | 0.00 |
October | 4113.99 | 1605.56 | 3572.81 | 2470.55 | 1102.26 | 0.00 | 0.00 |
November | 3403.29 | 2084.51 | 3257.34 | 2359.48 | 897.86 | 0.00 | 0.00 |
December | 2712.52 | 2789.38 | 2831.13 | 2044.36 | 786.77 | 0.00 | 0.00 |
Annual Sum or Average | 3427.58 | 1720.81 | 3033.09 | 1747.21 | 1285.87 | 0.00 | 0.00 |
Minimum of Months | 2652.44 | 685.40 | 2404.90 | 701.38 | 786.77 | 0.00 | 0.00 |
Maximum of Months | 4302.63 | 3179.24 | 3791.39 | 2726.90 | 1703.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 290.04 | 2485.70 | 585.67 | 236.03 | 349.64 | 0.00 | 0.00 |
February | 734.26 | 1897.10 | 999.65 | 491.38 | 508.27 | 0.00 | 0.00 |
March | 976.08 | 1644.41 | 1279.31 | 468.76 | 810.55 | 0.00 | 0.00 |
April | 1584.87 | 1246.11 | 1670.15 | 739.95 | 930.19 | 0.00 | 0.00 |
May | 2210.04 | 910.73 | 2065.85 | 942.14 | 1123.71 | 0.00 | 0.00 |
June | 2695.20 | 625.53 | 2247.57 | 1032.39 | 1215.17 | 0.00 | 0.00 |
July | 2998.55 | 525.16 | 2302.38 | 1163.43 | 1138.95 | 0.00 | 0.00 |
August | 2462.80 | 587.93 | 1955.03 | 959.49 | 995.54 | 0.00 | 0.00 |
September | 1825.67 | 803.88 | 1572.70 | 795.09 | 777.61 | 0.00 | 0.00 |
October | 1061.72 | 1218.49 | 1124.05 | 558.48 | 565.57 | 0.00 | 0.00 |
November | 587.50 | 1708.09 | 795.72 | 394.74 | 400.97 | 0.00 | 0.00 |
December | 257.27 | 2317.63 | 534.87 | 225.75 | 309.12 | 0.00 | 0.00 |
Annual Sum or Average | 1477.56 | 1328.82 | 1429.69 | 667.95 | 761.74 | 0.00 | 0.00 |
Minimum of Months | 257.27 | 525.16 | 534.87 | 225.75 | 309.12 | 0.00 | 0.00 |
Maximum of Months | 2998.55 | 2485.70 | 2302.38 | 1163.43 | 1215.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13.85 | 3559.91 | 422.37 | 0.00 | 422.37 | 0.00 | 0.00 |
February | 111.07 | 2627.19 | 596.37 | 0.00 | 596.37 | 0.00 | 0.00 |
March | 360.06 | 2119.60 | 968.77 | 0.00 | 968.77 | 0.00 | 0.00 |
April | 610.45 | 1512.19 | 1104.60 | 6.45 | 1098.16 | 0.00 | 0.00 |
May | 1109.11 | 1134.53 | 1450.61 | 85.96 | 1364.65 | 0.00 | 0.00 |
June | 1761.77 | 730.06 | 1689.15 | 194.15 | 1495.00 | 0.00 | 0.00 |
July | 1913.29 | 606.61 | 1543.13 | 144.53 | 1398.60 | 0.00 | 0.00 |
August | 1393.75 | 694.41 | 1236.52 | 33.14 | 1203.38 | 0.00 | 0.00 |
September | 821.56 | 1054.18 | 926.07 | 0.33 | 925.74 | 0.00 | 0.00 |
October | 324.87 | 1554.66 | 675.51 | 0.00 | 675.51 | 0.00 | 0.00 |
November | 80.33 | 2216.46 | 459.22 | 0.00 | 459.22 | 0.00 | 0.00 |
December | 8.05 | 3040.38 | 354.18 | 0.00 | 354.18 | 0.00 | 0.00 |
Annual Sum or Average | 712.73 | 1734.14 | 954.12 | 38.91 | 915.21 | 0.00 | 0.00 |
Minimum of Months | 8.05 | 606.61 | 354.18 | 0.00 | 354.18 | 0.00 | 0.00 |
Maximum of Months | 1913.29 | 3559.91 | 1689.15 | 194.15 | 1495.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 352.40 | 2191.00 | 646.58 | 296.43 | 350.15 | 0.00 | 0.00 |
February | 775.40 | 1619.43 | 1011.31 | 502.09 | 509.22 | 0.00 | 0.00 |
March | 1132.37 | 1341.86 | 1359.80 | 562.65 | 797.16 | 0.00 | 0.00 |
April | 1703.53 | 975.22 | 1734.98 | 859.84 | 875.13 | 0.00 | 0.00 |
May | 2016.37 | 767.34 | 1916.51 | 852.73 | 1063.78 | 0.00 | 0.00 |
June | 2999.24 | 504.18 | 2480.67 | 1276.55 | 1204.12 | 0.00 | 0.00 |
July | 3396.86 | 411.76 | 2603.53 | 1471.85 | 1131.69 | 0.00 | 0.00 |
August | 2882.29 | 465.07 | 2262.59 | 1260.64 | 1001.94 | 0.00 | 0.00 |
September | 1850.38 | 672.29 | 1600.56 | 826.20 | 774.36 | 0.00 | 0.00 |
October | 1106.57 | 984.43 | 1148.32 | 583.10 | 565.22 | 0.00 | 0.00 |
November | 516.72 | 1358.88 | 727.78 | 339.78 | 388.00 | 0.00 | 0.00 |
December | 277.16 | 1867.83 | 536.78 | 230.55 | 306.23 | 0.00 | 0.00 |
Annual Sum or Average | 1588.74 | 1094.71 | 1505.02 | 756.51 | 748.51 | 0.00 | 0.00 |
Minimum of Months | 277.16 | 411.76 | 536.78 | 230.55 | 306.23 | 0.00 | 0.00 |
Maximum of Months | 3396.86 | 2191.00 | 2603.53 | 1471.85 | 1204.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2806.24 | 3113.64 | 2977.27 | 2126.42 | 850.84 | 0.00 | 0.00 |
February | 3927.66 | 2363.13 | 3791.51 | 2726.99 | 1064.51 | 0.00 | 0.00 |
March | 3500.29 | 2120.17 | 3389.11 | 1903.17 | 1485.94 | 0.00 | 0.00 |
April | 2922.98 | 1590.85 | 2724.28 | 1303.04 | 1421.24 | 0.00 | 0.00 |
May | 2646.15 | 1251.36 | 2420.45 | 803.90 | 1616.55 | 0.00 | 0.00 |
June | 3007.49 | 854.18 | 2404.96 | 701.40 | 1703.56 | 0.00 | 0.00 |
July | 3620.30 | 680.96 | 2592.79 | 957.77 | 1635.02 | 0.00 | 0.00 |
August | 4168.50 | 773.19 | 3081.36 | 1553.57 | 1527.79 | 0.00 | 0.00 |
September | 4275.13 | 1107.76 | 3417.60 | 2094.07 | 1323.53 | 0.00 | 0.00 |
October | 4095.26 | 1566.89 | 3572.92 | 2470.63 | 1102.29 | 0.00 | 0.00 |
November | 3405.31 | 2009.94 | 3257.44 | 2359.56 | 897.88 | 0.00 | 0.00 |
December | 2734.66 | 2657.45 | 2831.21 | 2044.42 | 786.79 | 0.00 | 0.00 |
Annual Sum or Average | 3421.96 | 1671.57 | 3033.18 | 1747.27 | 1285.90 | 0.00 | 0.00 |
Minimum of Months | 2646.15 | 680.96 | 2404.96 | 701.40 | 786.79 | 0.00 | 0.00 |
Maximum of Months | 4275.13 | 3113.64 | 3791.51 | 2726.99 | 1703.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 305.02 | 2317.12 | 585.67 | 236.03 | 349.64 | 0.00 | 0.00 |
February | 778.43 | 1701.55 | 999.65 | 491.38 | 508.27 | 0.00 | 0.00 |
March | 1038.25 | 1435.25 | 1279.30 | 468.76 | 810.55 | 0.00 | 0.00 |
April | 1647.33 | 1068.40 | 1670.14 | 739.95 | 930.19 | 0.00 | 0.00 |
May | 2232.66 | 843.84 | 2065.84 | 942.13 | 1123.71 | 0.00 | 0.00 |
June | 2718.21 | 580.44 | 2247.56 | 1032.39 | 1215.17 | 0.00 | 0.00 |
July | 3025.18 | 486.45 | 2302.37 | 1163.42 | 1138.95 | 0.00 | 0.00 |
August | 2497.55 | 527.47 | 1955.02 | 959.48 | 995.54 | 0.00 | 0.00 |
September | 1845.00 | 741.77 | 1572.69 | 795.09 | 777.60 | 0.00 | 0.00 |
October | 1107.60 | 1066.99 | 1124.04 | 558.48 | 565.57 | 0.00 | 0.00 |
November | 632.85 | 1452.28 | 795.72 | 394.74 | 400.97 | 0.00 | 0.00 |
December | 291.85 | 1969.52 | 534.87 | 225.75 | 309.11 | 0.00 | 0.00 |
Annual Sum or Average | 1513.80 | 1180.76 | 1429.68 | 667.94 | 761.74 | 0.00 | 0.00 |
Minimum of Months | 291.85 | 486.45 | 534.87 | 225.75 | 309.11 | 0.00 | 0.00 |
Maximum of Months | 3025.18 | 2317.12 | 2302.37 | 1163.42 | 1215.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 20.61 | 3428.65 | 422.37 | 0.00 | 422.37 | 0.00 | 0.00 |
February | 133.04 | 2497.63 | 596.37 | 0.00 | 596.37 | 0.00 | 0.00 |
March | 396.69 | 1984.66 | 968.77 | 0.00 | 968.77 | 0.00 | 0.00 |
April | 662.35 | 1384.16 | 1104.60 | 6.45 | 1098.16 | 0.00 | 0.00 |
May | 1147.67 | 1057.86 | 1450.61 | 85.96 | 1364.65 | 0.00 | 0.00 |
June | 1776.29 | 706.97 | 1689.15 | 194.15 | 1495.00 | 0.00 | 0.00 |
July | 1912.10 | 599.09 | 1543.13 | 144.53 | 1398.60 | 0.00 | 0.00 |
August | 1400.19 | 673.58 | 1236.52 | 33.14 | 1203.38 | 0.00 | 0.00 |
September | 849.01 | 982.52 | 926.07 | 0.33 | 925.74 | 0.00 | 0.00 |
October | 376.40 | 1396.77 | 675.51 | 0.00 | 675.51 | 0.00 | 0.00 |
November | 101.69 | 2026.65 | 459.22 | 0.00 | 459.22 | 0.00 | 0.00 |
December | 10.21 | 2892.95 | 354.18 | 0.00 | 354.18 | 0.00 | 0.00 |
Annual Sum or Average | 735.85 | 1632.83 | 954.12 | 38.91 | 915.21 | 0.00 | 0.00 |
Minimum of Months | 10.21 | 599.09 | 354.18 | 0.00 | 354.18 | 0.00 | 0.00 |
Maximum of Months | 1912.10 | 3428.65 | 1689.15 | 194.15 | 1495.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 364.40 | 2110.43 | 646.58 | 296.43 | 350.15 | 0.00 | 0.00 |
February | 800.51 | 1540.85 | 1011.31 | 502.09 | 509.22 | 0.00 | 0.00 |
March | 1162.91 | 1260.70 | 1359.80 | 562.65 | 797.16 | 0.00 | 0.00 |
April | 1732.57 | 906.34 | 1734.98 | 859.84 | 875.13 | 0.00 | 0.00 |
May | 2030.15 | 725.38 | 1916.51 | 852.73 | 1063.78 | 0.00 | 0.00 |
June | 2997.59 | 495.18 | 2480.67 | 1276.55 | 1204.12 | 0.00 | 0.00 |
July | 3388.14 | 411.41 | 2603.53 | 1471.85 | 1131.69 | 0.00 | 0.00 |
August | 2878.17 | 458.52 | 2262.59 | 1260.64 | 1001.94 | 0.00 | 0.00 |
September | 1861.03 | 640.47 | 1600.56 | 826.20 | 774.36 | 0.00 | 0.00 |
October | 1144.04 | 896.80 | 1148.32 | 583.10 | 565.22 | 0.00 | 0.00 |
November | 546.18 | 1246.06 | 727.78 | 339.78 | 388.00 | 0.00 | 0.00 |
December | 288.67 | 1776.58 | 536.78 | 230.55 | 306.23 | 0.00 | 0.00 |
Annual Sum or Average | 1604.07 | 1037.31 | 1505.02 | 756.51 | 748.51 | 0.00 | 0.00 |
Minimum of Months | 288.67 | 411.41 | 536.78 | 230.55 | 306.23 | 0.00 | 0.00 |
Maximum of Months | 3388.14 | 2110.43 | 2603.53 | 1471.85 | 1204.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2842.80 | 2972.71 | 2977.27 | 2126.42 | 850.84 | 0.00 | 0.00 |
February | 3969.48 | 2235.28 | 3791.51 | 2726.99 | 1064.51 | 0.00 | 0.00 |
March | 3541.37 | 1986.90 | 3389.11 | 1903.17 | 1485.94 | 0.00 | 0.00 |
April | 2960.90 | 1474.13 | 2724.28 | 1303.04 | 1421.24 | 0.00 | 0.00 |
May | 2666.59 | 1177.98 | 2420.45 | 803.90 | 1616.55 | 0.00 | 0.00 |
June | 3009.31 | 830.02 | 2404.96 | 701.40 | 1703.56 | 0.00 | 0.00 |
July | 3611.38 | 674.53 | 2592.79 | 957.77 | 1635.02 | 0.00 | 0.00 |
August | 4162.56 | 757.24 | 3081.36 | 1553.57 | 1527.79 | 0.00 | 0.00 |
September | 4285.50 | 1051.81 | 3417.60 | 2094.07 | 1323.53 | 0.00 | 0.00 |
October | 4139.50 | 1433.29 | 3572.92 | 2470.63 | 1102.29 | 0.00 | 0.00 |
November | 3468.82 | 1837.36 | 3257.44 | 2359.56 | 897.88 | 0.00 | 0.00 |
December | 2779.35 | 2504.78 | 2831.21 | 2044.42 | 786.79 | 0.00 | 0.00 |
Annual Sum or Average | 3449.13 | 1575.67 | 3033.18 | 1747.27 | 1285.90 | 0.00 | 0.00 |
Minimum of Months | 2666.59 | 674.53 | 2404.96 | 701.40 | 786.79 | 0.00 | 0.00 |
Maximum of Months | 4285.50 | 2972.71 | 3791.51 | 2726.99 | 1703.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 313.92 | 2229.74 | 585.67 | 236.03 | 349.64 | 0.00 | 0.00 |
February | 793.54 | 1625.19 | 999.65 | 491.38 | 508.27 | 0.00 | 0.00 |
March | 1057.45 | 1357.66 | 1279.30 | 468.76 | 810.55 | 0.00 | 0.00 |
April | 1670.97 | 999.28 | 1670.14 | 739.95 | 930.19 | 0.00 | 0.00 |
May | 2244.57 | 800.09 | 2065.84 | 942.13 | 1123.71 | 0.00 | 0.00 |
June | 2718.55 | 566.13 | 2247.56 | 1032.39 | 1215.17 | 0.00 | 0.00 |
July | 3019.11 | 482.45 | 2302.37 | 1163.42 | 1138.95 | 0.00 | 0.00 |
August | 2495.58 | 517.16 | 1955.02 | 959.48 | 995.54 | 0.00 | 0.00 |
September | 1854.60 | 705.46 | 1572.69 | 795.09 | 777.60 | 0.00 | 0.00 |
October | 1133.63 | 983.34 | 1124.04 | 558.48 | 565.57 | 0.00 | 0.00 |
November | 653.40 | 1345.90 | 795.72 | 394.74 | 400.97 | 0.00 | 0.00 |
December | 300.49 | 1877.63 | 534.87 | 225.75 | 309.11 | 0.00 | 0.00 |
Annual Sum or Average | 1525.07 | 1122.46 | 1429.68 | 667.94 | 761.74 | 0.00 | 0.00 |
Minimum of Months | 300.49 | 482.45 | 534.87 | 225.75 | 309.11 | 0.00 | 0.00 |
Maximum of Months | 3019.11 | 2229.74 | 2302.37 | 1163.42 | 1215.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 18766978.70 | 0.101477E+11 | 0.113127E+10 | 0.00 | 0.113127E+10 | 0.00 | 0.00 |
February | 0.173462E+09 | 0.691478E+10 | 0.144270E+10 | 0.00 | 0.144270E+10 | 0.00 | 0.00 |
March | 0.782332E+09 | 0.626829E+10 | 0.259471E+10 | 0.00 | 0.259471E+10 | 0.00 | 0.00 |
April | 0.140944E+10 | 0.436135E+10 | 0.286308E+10 | 16708098.44 | 0.284637E+10 | 0.00 | 0.00 |
May | 0.285746E+10 | 0.325317E+10 | 0.388524E+10 | 0.230222E+09 | 0.365502E+10 | 0.00 | 0.00 |
June | 0.450910E+10 | 0.196519E+10 | 0.437821E+10 | 0.503232E+09 | 0.387497E+10 | 0.00 | 0.00 |
July | 0.506788E+10 | 0.167024E+10 | 0.413306E+10 | 0.387106E+09 | 0.374595E+10 | 0.00 | 0.00 |
August | 0.366975E+10 | 0.193463E+10 | 0.331184E+10 | 88771672.39 | 0.322307E+10 | 0.00 | 0.00 |
September | 0.205481E+10 | 0.292043E+10 | 0.240033E+10 | 861357.07 | 0.239947E+10 | 0.00 | 0.00 |
October | 0.734287E+09 | 0.463680E+10 | 0.180926E+10 | 0.00 | 0.180926E+10 | 0.00 | 0.00 |
November | 0.137993E+09 | 0.650409E+10 | 0.119028E+10 | 0.00 | 0.119028E+10 | 0.00 | 0.00 |
December | 5616970.32 | 0.910606E+10 | 0.948630E+09 | 0.00 | 0.948630E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.214209E+11 | 0.596827E+11 | 0.300886E+11 | 0.122690E+10 | 0.288617E+11 | 0.00 | 0.00 |
Minimum of Months | 5616970.32 | 0.167024E+10 | 0.948630E+09 | 0.00 | 0.948630E+09 | 0.00 | 0.00 |
Maximum of Months | 0.506788E+10 | 0.101477E+11 | 0.437821E+10 | 0.503232E+09 | 0.387497E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.901926E+09 | 0.617810E+10 | 0.173182E+10 | 0.793968E+09 | 0.937849E+09 | 0.00 | 0.00 |
February | 0.181012E+10 | 0.417683E+10 | 0.244658E+10 | 0.121467E+10 | 0.123191E+10 | 0.00 | 0.00 |
March | 0.295385E+10 | 0.384753E+10 | 0.364211E+10 | 0.150701E+10 | 0.213511E+10 | 0.00 | 0.00 |
April | 0.437681E+10 | 0.268859E+10 | 0.449708E+10 | 0.222872E+10 | 0.226836E+10 | 0.00 | 0.00 |
May | 0.538839E+10 | 0.216174E+10 | 0.513319E+10 | 0.228395E+10 | 0.284924E+10 | 0.00 | 0.00 |
June | 0.780540E+10 | 0.132244E+10 | 0.642992E+10 | 0.330883E+10 | 0.312109E+10 | 0.00 | 0.00 |
July | 0.913997E+10 | 0.108252E+10 | 0.697333E+10 | 0.394221E+10 | 0.303112E+10 | 0.00 | 0.00 |
August | 0.775627E+10 | 0.122300E+10 | 0.606014E+10 | 0.337652E+10 | 0.268362E+10 | 0.00 | 0.00 |
September | 0.479541E+10 | 0.181558E+10 | 0.414866E+10 | 0.214152E+10 | 0.200714E+10 | 0.00 | 0.00 |
October | 0.290843E+10 | 0.283823E+10 | 0.307566E+10 | 0.156177E+10 | 0.151389E+10 | 0.00 | 0.00 |
November | 0.126975E+10 | 0.385246E+10 | 0.188642E+10 | 0.880708E+09 | 0.100571E+10 | 0.00 | 0.00 |
December | 0.685928E+09 | 0.543856E+10 | 0.143772E+10 | 0.617503E+09 | 0.820215E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.497922E+11 | 0.366256E+11 | 0.474626E+11 | 0.238574E+11 | 0.236052E+11 | 0.00 | 0.00 |
Minimum of Months | 0.685928E+09 | 0.108252E+10 | 0.143772E+10 | 0.617503E+09 | 0.820215E+09 | 0.00 | 0.00 |
Maximum of Months | 0.913997E+10 | 0.617810E+10 | 0.697333E+10 | 0.394221E+10 | 0.312109E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.752263E+10 | 0.851528E+10 | 0.797406E+10 | 0.569523E+10 | 0.227884E+10 | 0.00 | 0.00 |
February | 0.952248E+10 | 0.588271E+10 | 0.917213E+10 | 0.659692E+10 | 0.257521E+10 | 0.00 | 0.00 |
March | 0.938667E+10 | 0.587424E+10 | 0.907713E+10 | 0.509728E+10 | 0.397985E+10 | 0.00 | 0.00 |
April | 0.757477E+10 | 0.429432E+10 | 0.706113E+10 | 0.337737E+10 | 0.368377E+10 | 0.00 | 0.00 |
May | 0.710430E+10 | 0.344375E+10 | 0.648277E+10 | 0.215309E+10 | 0.432968E+10 | 0.00 | 0.00 |
June | 0.781230E+10 | 0.225320E+10 | 0.623351E+10 | 0.181797E+10 | 0.441554E+10 | 0.00 | 0.00 |
July | 0.971220E+10 | 0.183579E+10 | 0.694436E+10 | 0.256520E+10 | 0.437916E+10 | 0.00 | 0.00 |
August | 0.111990E+11 | 0.208405E+10 | 0.825290E+10 | 0.416094E+10 | 0.409196E+10 | 0.00 | 0.00 |
September | 0.111524E+11 | 0.290977E+10 | 0.885816E+10 | 0.542766E+10 | 0.343050E+10 | 0.00 | 0.00 |
October | 0.110189E+11 | 0.430034E+10 | 0.956941E+10 | 0.661711E+10 | 0.295230E+10 | 0.00 | 0.00 |
November | 0.882132E+10 | 0.540304E+10 | 0.844303E+10 | 0.611578E+10 | 0.232725E+10 | 0.00 | 0.00 |
December | 0.726522E+10 | 0.747108E+10 | 0.758289E+10 | 0.547560E+10 | 0.210728E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.108092E+12 | 0.542676E+11 | 0.956515E+11 | 0.551002E+11 | 0.405513E+11 | 0.00 | 0.00 |
Minimum of Months | 0.710430E+10 | 0.183579E+10 | 0.623351E+10 | 0.181797E+10 | 0.210728E+10 | 0.00 | 0.00 |
Maximum of Months | 0.111990E+11 | 0.851528E+10 | 0.956941E+10 | 0.661711E+10 | 0.441554E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.776834E+09 | 0.665770E+10 | 0.156866E+10 | 0.632181E+09 | 0.936477E+09 | 0.00 | 0.00 |
February | 0.177631E+10 | 0.458947E+10 | 0.241835E+10 | 0.118874E+10 | 0.122961E+10 | 0.00 | 0.00 |
March | 0.261434E+10 | 0.440438E+10 | 0.342650E+10 | 0.125552E+10 | 0.217098E+10 | 0.00 | 0.00 |
April | 0.410799E+10 | 0.322991E+10 | 0.432902E+10 | 0.191795E+10 | 0.241106E+10 | 0.00 | 0.00 |
May | 0.591936E+10 | 0.243929E+10 | 0.553317E+10 | 0.252342E+10 | 0.300975E+10 | 0.00 | 0.00 |
June | 0.698595E+10 | 0.162138E+10 | 0.582569E+10 | 0.267596E+10 | 0.314973E+10 | 0.00 | 0.00 |
July | 0.803132E+10 | 0.140659E+10 | 0.616670E+10 | 0.311612E+10 | 0.305057E+10 | 0.00 | 0.00 |
August | 0.659637E+10 | 0.157471E+10 | 0.523636E+10 | 0.256989E+10 | 0.266646E+10 | 0.00 | 0.00 |
September | 0.473215E+10 | 0.208365E+10 | 0.407644E+10 | 0.206088E+10 | 0.201556E+10 | 0.00 | 0.00 |
October | 0.284370E+10 | 0.326361E+10 | 0.301065E+10 | 0.149583E+10 | 0.151482E+10 | 0.00 | 0.00 |
November | 0.152280E+10 | 0.442736E+10 | 0.206251E+10 | 0.102318E+10 | 0.103933E+10 | 0.00 | 0.00 |
December | 0.689069E+09 | 0.620753E+10 | 0.143259E+10 | 0.604657E+09 | 0.827936E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.465962E+11 | 0.419056E+11 | 0.450866E+11 | 0.210643E+11 | 0.240223E+11 | 0.00 | 0.00 |
Minimum of Months | 0.689069E+09 | 0.140659E+10 | 0.143259E+10 | 0.604657E+09 | 0.827936E+09 | 0.00 | 0.00 |
Maximum of Months | 0.803132E+10 | 0.665770E+10 | 0.616670E+10 | 0.311612E+10 | 0.314973E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 37104057.49 | 0.953486E+10 | 0.113129E+10 | 0.00 | 0.113129E+10 | 0.00 | 0.00 |
February | 0.268695E+09 | 0.635571E+10 | 0.144273E+10 | 0.00 | 0.144273E+10 | 0.00 | 0.00 |
March | 0.964373E+09 | 0.567712E+10 | 0.259476E+10 | 0.00 | 0.259476E+10 | 0.00 | 0.00 |
April | 0.158228E+10 | 0.391960E+10 | 0.286313E+10 | 16708596.73 | 0.284642E+10 | 0.00 | 0.00 |
May | 0.297064E+10 | 0.303873E+10 | 0.388531E+10 | 0.230229E+09 | 0.365508E+10 | 0.00 | 0.00 |
June | 0.456652E+10 | 0.189232E+10 | 0.437828E+10 | 0.503247E+09 | 0.387504E+10 | 0.00 | 0.00 |
July | 0.512456E+10 | 0.162475E+10 | 0.413313E+10 | 0.387117E+09 | 0.374601E+10 | 0.00 | 0.00 |
August | 0.373302E+10 | 0.185991E+10 | 0.331190E+10 | 88774319.81 | 0.322312E+10 | 0.00 | 0.00 |
September | 0.212949E+10 | 0.273244E+10 | 0.240037E+10 | 861382.76 | 0.239951E+10 | 0.00 | 0.00 |
October | 0.870141E+09 | 0.416401E+10 | 0.180929E+10 | 0.00 | 0.180929E+10 | 0.00 | 0.00 |
November | 0.208219E+09 | 0.574507E+10 | 0.119030E+10 | 0.00 | 0.119030E+10 | 0.00 | 0.00 |
December | 21550712.82 | 0.814334E+10 | 0.948649E+09 | 0.00 | 0.948649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.224766E+11 | 0.546879E+11 | 0.300891E+11 | 0.122694E+10 | 0.288622E+11 | 0.00 | 0.00 |
Minimum of Months | 21550712.82 | 0.162475E+10 | 0.948649E+09 | 0.00 | 0.948649E+09 | 0.00 | 0.00 |
Maximum of Months | 0.512456E+10 | 0.953486E+10 | 0.437828E+10 | 0.503247E+09 | 0.387504E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.943860E+09 | 0.586837E+10 | 0.173181E+10 | 0.793965E+09 | 0.937845E+09 | 0.00 | 0.00 |
February | 0.187585E+10 | 0.391774E+10 | 0.244657E+10 | 0.121466E+10 | 0.123191E+10 | 0.00 | 0.00 |
March | 0.303294E+10 | 0.359404E+10 | 0.364210E+10 | 0.150700E+10 | 0.213510E+10 | 0.00 | 0.00 |
April | 0.441555E+10 | 0.252778E+10 | 0.449706E+10 | 0.222871E+10 | 0.226835E+10 | 0.00 | 0.00 |
May | 0.540064E+10 | 0.205525E+10 | 0.513317E+10 | 0.228394E+10 | 0.284923E+10 | 0.00 | 0.00 |
June | 0.777403E+10 | 0.130684E+10 | 0.642990E+10 | 0.330882E+10 | 0.312108E+10 | 0.00 | 0.00 |
July | 0.909815E+10 | 0.110286E+10 | 0.697330E+10 | 0.394219E+10 | 0.303111E+10 | 0.00 | 0.00 |
August | 0.771993E+10 | 0.124564E+10 | 0.606011E+10 | 0.337651E+10 | 0.268361E+10 | 0.00 | 0.00 |
September | 0.479617E+10 | 0.174258E+10 | 0.414864E+10 | 0.214151E+10 | 0.200713E+10 | 0.00 | 0.00 |
October | 0.296383E+10 | 0.263670E+10 | 0.307565E+10 | 0.156177E+10 | 0.151388E+10 | 0.00 | 0.00 |
November | 0.133934E+10 | 0.352222E+10 | 0.188641E+10 | 0.880704E+09 | 0.100570E+10 | 0.00 | 0.00 |
December | 0.742335E+09 | 0.500281E+10 | 0.143771E+10 | 0.617501E+09 | 0.820212E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.501026E+11 | 0.345228E+11 | 0.474624E+11 | 0.238573E+11 | 0.236052E+11 | 0.00 | 0.00 |
Minimum of Months | 0.742335E+09 | 0.110286E+10 | 0.143771E+10 | 0.617501E+09 | 0.820212E+09 | 0.00 | 0.00 |
Maximum of Months | 0.909815E+10 | 0.586837E+10 | 0.697330E+10 | 0.394219E+10 | 0.312108E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.751622E+10 | 0.833956E+10 | 0.797431E+10 | 0.569541E+10 | 0.227890E+10 | 0.00 | 0.00 |
February | 0.950180E+10 | 0.571689E+10 | 0.917241E+10 | 0.659714E+10 | 0.257527E+10 | 0.00 | 0.00 |
March | 0.937518E+10 | 0.567867E+10 | 0.907740E+10 | 0.509745E+10 | 0.397995E+10 | 0.00 | 0.00 |
April | 0.757635E+10 | 0.412348E+10 | 0.706133E+10 | 0.337748E+10 | 0.368385E+10 | 0.00 | 0.00 |
May | 0.708745E+10 | 0.335163E+10 | 0.648294E+10 | 0.215316E+10 | 0.432978E+10 | 0.00 | 0.00 |
June | 0.779540E+10 | 0.221404E+10 | 0.623366E+10 | 0.181803E+10 | 0.441563E+10 | 0.00 | 0.00 |
July | 0.969661E+10 | 0.182387E+10 | 0.694453E+10 | 0.256529E+10 | 0.437924E+10 | 0.00 | 0.00 |
August | 0.111649E+11 | 0.207092E+10 | 0.825312E+10 | 0.416107E+10 | 0.409204E+10 | 0.00 | 0.00 |
September | 0.110811E+11 | 0.287132E+10 | 0.885842E+10 | 0.542784E+10 | 0.343058E+10 | 0.00 | 0.00 |
October | 0.109687E+11 | 0.419675E+10 | 0.956970E+10 | 0.661733E+10 | 0.295237E+10 | 0.00 | 0.00 |
November | 0.882657E+10 | 0.520975E+10 | 0.844329E+10 | 0.611598E+10 | 0.232731E+10 | 0.00 | 0.00 |
December | 0.732452E+10 | 0.711770E+10 | 0.758312E+10 | 0.547578E+10 | 0.210734E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.107915E+12 | 0.527146E+11 | 0.956542E+11 | 0.551020E+11 | 0.405523E+11 | 0.00 | 0.00 |
Minimum of Months | 0.708745E+10 | 0.182387E+10 | 0.623366E+10 | 0.181803E+10 | 0.210734E+10 | 0.00 | 0.00 |
Maximum of Months | 0.111649E+11 | 0.833956E+10 | 0.956970E+10 | 0.661733E+10 | 0.441563E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.816960E+09 | 0.620619E+10 | 0.156865E+10 | 0.632178E+09 | 0.936473E+09 | 0.00 | 0.00 |
February | 0.188318E+10 | 0.411639E+10 | 0.241834E+10 | 0.118874E+10 | 0.122960E+10 | 0.00 | 0.00 |
March | 0.278084E+10 | 0.384416E+10 | 0.342649E+10 | 0.125552E+10 | 0.217097E+10 | 0.00 | 0.00 |
April | 0.426987E+10 | 0.276929E+10 | 0.432900E+10 | 0.191795E+10 | 0.241105E+10 | 0.00 | 0.00 |
May | 0.597995E+10 | 0.226015E+10 | 0.553315E+10 | 0.252341E+10 | 0.300974E+10 | 0.00 | 0.00 |
June | 0.704561E+10 | 0.150450E+10 | 0.582567E+10 | 0.267595E+10 | 0.314972E+10 | 0.00 | 0.00 |
July | 0.810263E+10 | 0.130289E+10 | 0.616667E+10 | 0.311611E+10 | 0.305056E+10 | 0.00 | 0.00 |
August | 0.668943E+10 | 0.141277E+10 | 0.523634E+10 | 0.256988E+10 | 0.266645E+10 | 0.00 | 0.00 |
September | 0.478224E+10 | 0.192266E+10 | 0.407642E+10 | 0.206087E+10 | 0.201555E+10 | 0.00 | 0.00 |
October | 0.296658E+10 | 0.285783E+10 | 0.301064E+10 | 0.149582E+10 | 0.151482E+10 | 0.00 | 0.00 |
November | 0.164034E+10 | 0.376431E+10 | 0.206250E+10 | 0.102317E+10 | 0.103932E+10 | 0.00 | 0.00 |
December | 0.781697E+09 | 0.527516E+10 | 0.143259E+10 | 0.604655E+09 | 0.827933E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.477393E+11 | 0.372363E+11 | 0.450864E+11 | 0.210643E+11 | 0.240222E+11 | 0.00 | 0.00 |
Minimum of Months | 0.781697E+09 | 0.130289E+10 | 0.143259E+10 | 0.604655E+09 | 0.827933E+09 | 0.00 | 0.00 |
Maximum of Months | 0.810263E+10 | 0.620619E+10 | 0.616667E+10 | 0.311611E+10 | 0.314972E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 55204646.23 | 0.918330E+10 | 0.113129E+10 | 0.00 | 0.113129E+10 | 0.00 | 0.00 |
February | 0.321851E+09 | 0.604227E+10 | 0.144273E+10 | 0.00 | 0.144273E+10 | 0.00 | 0.00 |
March | 0.106251E+10 | 0.531571E+10 | 0.259476E+10 | 0.00 | 0.259476E+10 | 0.00 | 0.00 |
April | 0.171682E+10 | 0.358774E+10 | 0.286313E+10 | 16708596.73 | 0.284642E+10 | 0.00 | 0.00 |
May | 0.307392E+10 | 0.283337E+10 | 0.388531E+10 | 0.230229E+09 | 0.365508E+10 | 0.00 | 0.00 |
June | 0.460414E+10 | 0.183246E+10 | 0.437828E+10 | 0.503247E+09 | 0.387504E+10 | 0.00 | 0.00 |
July | 0.512138E+10 | 0.160461E+10 | 0.413313E+10 | 0.387117E+09 | 0.374601E+10 | 0.00 | 0.00 |
August | 0.375026E+10 | 0.180412E+10 | 0.331190E+10 | 88774319.81 | 0.322312E+10 | 0.00 | 0.00 |
September | 0.220065E+10 | 0.254669E+10 | 0.240037E+10 | 861382.76 | 0.239951E+10 | 0.00 | 0.00 |
October | 0.100814E+10 | 0.374111E+10 | 0.180929E+10 | 0.00 | 0.180929E+10 | 0.00 | 0.00 |
November | 0.263591E+09 | 0.525309E+10 | 0.119030E+10 | 0.00 | 0.119030E+10 | 0.00 | 0.00 |
December | 27357747.57 | 0.774848E+10 | 0.948649E+09 | 0.00 | 0.948649E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.232058E+11 | 0.514929E+11 | 0.300891E+11 | 0.122694E+10 | 0.288622E+11 | 0.00 | 0.00 |
Minimum of Months | 27357747.57 | 0.160461E+10 | 0.948649E+09 | 0.00 | 0.948649E+09 | 0.00 | 0.00 |
Maximum of Months | 0.512138E+10 | 0.918330E+10 | 0.437828E+10 | 0.503247E+09 | 0.387504E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.976015E+09 | 0.565257E+10 | 0.173181E+10 | 0.793965E+09 | 0.937845E+09 | 0.00 | 0.00 |
February | 0.193659E+10 | 0.372763E+10 | 0.244657E+10 | 0.121466E+10 | 0.123191E+10 | 0.00 | 0.00 |
March | 0.311474E+10 | 0.337665E+10 | 0.364210E+10 | 0.150700E+10 | 0.213510E+10 | 0.00 | 0.00 |
April | 0.449083E+10 | 0.234924E+10 | 0.449706E+10 | 0.222871E+10 | 0.226835E+10 | 0.00 | 0.00 |
May | 0.543755E+10 | 0.194285E+10 | 0.513317E+10 | 0.228394E+10 | 0.284923E+10 | 0.00 | 0.00 |
June | 0.776974E+10 | 0.128351E+10 | 0.642990E+10 | 0.330882E+10 | 0.312108E+10 | 0.00 | 0.00 |
July | 0.907479E+10 | 0.110193E+10 | 0.697330E+10 | 0.394219E+10 | 0.303111E+10 | 0.00 | 0.00 |
August | 0.770888E+10 | 0.122810E+10 | 0.606011E+10 | 0.337651E+10 | 0.268361E+10 | 0.00 | 0.00 |
September | 0.482380E+10 | 0.166009E+10 | 0.414864E+10 | 0.214151E+10 | 0.200713E+10 | 0.00 | 0.00 |
October | 0.306421E+10 | 0.240199E+10 | 0.307565E+10 | 0.156177E+10 | 0.151388E+10 | 0.00 | 0.00 |
November | 0.141571E+10 | 0.322980E+10 | 0.188641E+10 | 0.880704E+09 | 0.100570E+10 | 0.00 | 0.00 |
December | 0.773176E+09 | 0.475839E+10 | 0.143771E+10 | 0.617501E+09 | 0.820212E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.505860E+11 | 0.327127E+11 | 0.474624E+11 | 0.238573E+11 | 0.236052E+11 | 0.00 | 0.00 |
Minimum of Months | 0.773176E+09 | 0.110193E+10 | 0.143771E+10 | 0.617501E+09 | 0.820212E+09 | 0.00 | 0.00 |
Maximum of Months | 0.907479E+10 | 0.565257E+10 | 0.697330E+10 | 0.394219E+10 | 0.312108E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.761416E+10 | 0.796211E+10 | 0.797431E+10 | 0.569541E+10 | 0.227890E+10 | 0.00 | 0.00 |
February | 0.960297E+10 | 0.540758E+10 | 0.917241E+10 | 0.659714E+10 | 0.257527E+10 | 0.00 | 0.00 |
March | 0.948521E+10 | 0.532172E+10 | 0.907740E+10 | 0.509745E+10 | 0.397995E+10 | 0.00 | 0.00 |
April | 0.767465E+10 | 0.382094E+10 | 0.706133E+10 | 0.337748E+10 | 0.368385E+10 | 0.00 | 0.00 |
May | 0.714221E+10 | 0.315511E+10 | 0.648294E+10 | 0.215316E+10 | 0.432978E+10 | 0.00 | 0.00 |
June | 0.780014E+10 | 0.215141E+10 | 0.623366E+10 | 0.181803E+10 | 0.441563E+10 | 0.00 | 0.00 |
July | 0.967273E+10 | 0.180667E+10 | 0.694453E+10 | 0.256529E+10 | 0.437924E+10 | 0.00 | 0.00 |
August | 0.111490E+11 | 0.202819E+10 | 0.825312E+10 | 0.416107E+10 | 0.409204E+10 | 0.00 | 0.00 |
September | 0.111080E+11 | 0.272630E+10 | 0.885842E+10 | 0.542784E+10 | 0.343058E+10 | 0.00 | 0.00 |
October | 0.110872E+11 | 0.383891E+10 | 0.956970E+10 | 0.661733E+10 | 0.295237E+10 | 0.00 | 0.00 |
November | 0.899118E+10 | 0.476243E+10 | 0.844329E+10 | 0.611598E+10 | 0.232731E+10 | 0.00 | 0.00 |
December | 0.744420E+10 | 0.670880E+10 | 0.758312E+10 | 0.547578E+10 | 0.210734E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.108772E+12 | 0.496902E+11 | 0.956542E+11 | 0.551020E+11 | 0.405523E+11 | 0.00 | 0.00 |
Minimum of Months | 0.714221E+10 | 0.180667E+10 | 0.623366E+10 | 0.181803E+10 | 0.210734E+10 | 0.00 | 0.00 |
Maximum of Months | 0.111490E+11 | 0.796211E+10 | 0.956970E+10 | 0.661733E+10 | 0.441563E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.840807E+09 | 0.597215E+10 | 0.156865E+10 | 0.632178E+09 | 0.936473E+09 | 0.00 | 0.00 |
February | 0.191972E+10 | 0.393165E+10 | 0.241834E+10 | 0.118874E+10 | 0.122960E+10 | 0.00 | 0.00 |
March | 0.283228E+10 | 0.363636E+10 | 0.342649E+10 | 0.125552E+10 | 0.217097E+10 | 0.00 | 0.00 |
April | 0.433116E+10 | 0.259014E+10 | 0.432900E+10 | 0.191795E+10 | 0.241105E+10 | 0.00 | 0.00 |
May | 0.601186E+10 | 0.214297E+10 | 0.553315E+10 | 0.252341E+10 | 0.300974E+10 | 0.00 | 0.00 |
June | 0.704648E+10 | 0.146741E+10 | 0.582567E+10 | 0.267595E+10 | 0.314972E+10 | 0.00 | 0.00 |
July | 0.808638E+10 | 0.129218E+10 | 0.616667E+10 | 0.311611E+10 | 0.305056E+10 | 0.00 | 0.00 |
August | 0.668417E+10 | 0.138517E+10 | 0.523634E+10 | 0.256988E+10 | 0.266645E+10 | 0.00 | 0.00 |
September | 0.480713E+10 | 0.182856E+10 | 0.407642E+10 | 0.206087E+10 | 0.201555E+10 | 0.00 | 0.00 |
October | 0.303631E+10 | 0.263378E+10 | 0.301064E+10 | 0.149582E+10 | 0.151482E+10 | 0.00 | 0.00 |
November | 0.169360E+10 | 0.348858E+10 | 0.206250E+10 | 0.102317E+10 | 0.103932E+10 | 0.00 | 0.00 |
December | 0.804832E+09 | 0.502903E+10 | 0.143259E+10 | 0.604655E+09 | 0.827933E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.480947E+11 | 0.353980E+11 | 0.450864E+11 | 0.210643E+11 | 0.240222E+11 | 0.00 | 0.00 |
Minimum of Months | 0.804832E+09 | 0.129218E+10 | 0.143259E+10 | 0.604655E+09 | 0.827933E+09 | 0.00 | 0.00 |
Maximum of Months | 0.808638E+10 | 0.597215E+10 | 0.616667E+10 | 0.311611E+10 | 0.314972E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.437202E+11 | -0.426677E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.105254E+10 | 58.98 | 0.00 | 0.00 |
February | 0.403918E+11 | -0.394525E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -939310217.8 | 58.98 | 0.00 | 0.00 |
March | 0.469605E+11 | -0.459286E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103190E+10 | 58.97 | 0.00 | 0.00 |
April | 0.411154E+11 | -0.401231E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992280712.6 | 58.97 | 0.00 | 0.00 |
May | 0.415201E+11 | -0.404953E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102483E+10 | 58.98 | 0.00 | 0.00 |
June | 0.386504E+11 | -0.376586E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991775114.3 | 58.98 | 0.00 | 0.00 |
July | 0.350095E+11 | -0.339907E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101878E+10 | 58.98 | 0.00 | 0.00 |
August | 0.373958E+11 | -0.363731E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102277E+10 | 58.97 | 0.00 | 0.00 |
September | 0.344378E+11 | -0.334499E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987894953.3 | 58.97 | 0.00 | 0.00 |
October | 0.371410E+11 | -0.361208E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102019E+10 | 58.98 | 0.00 | 0.00 |
November | 0.386804E+11 | -0.376912E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989183910.4 | 58.98 | 0.00 | 0.00 |
December | 0.408555E+11 | -0.398249E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103059E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.475878E+12 | -0.463776E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.121021E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.344378E+11 | -0.459286E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.105254E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.469605E+11 | -0.334499E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -939310217.8 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.51 | 0.48 | 01-JAN-08:50 | 4842.55 | 32.52 | 185.83 | 220.17 | 4283.22 | 37.49 | 217.67 | 205.83 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-08:20 | 6828.38 | 34.12 | 240.50 | 248.33 | 2862.26 | 30.95 | 228.33 | 238.33 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:00 | 8110.27 | 31.93 | 253.17 | 313.50 | 1507.43 | 21.93 | 185.50 | 281.83 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:50 | 1842.55 | 17.83 | 0.00 | 336.83 | 1039.70 | 20.85 | 149.00 | 291.67 |
May | 385.83 | 0.51 | 0.48 | 01-MAY-06:49 | 1632.57 | 17.52 | 0.00 | 383.33 | 905.50 | 20.51 | 157.00 | 331.00 |
June | 434.17 | 0.52 | 0.48 | 01-JUN-13:39 | 1388.16 | 16.86 | 0.00 | 389.00 | 800.24 | 19.90 | 165.50 | 336.33 |
July | 417.33 | 0.51 | 0.48 | 01-JUL-06:49 | 1487.69 | 17.30 | 0.00 | 390.00 | 881.88 | 20.37 | 131.17 | 345.67 |
August | 421.33 | 0.52 | 0.48 | 01-AUG-06:49 | 1593.19 | 16.88 | 0.00 | 367.50 | 941.97 | 19.89 | 138.17 | 322.67 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 2317.25 | 18.54 | 29.50 | 316.33 | 1105.67 | 20.17 | 134.17 | 281.67 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:50 | 7007.91 | 33.36 | 276.50 | 293.33 | 1791.34 | 22.93 | 163.50 | 269.83 |
November | 269.50 | 0.51 | 0.48 | 01-NOV-07:00 | 5026.89 | 33.01 | 223.00 | 239.83 | 4636.26 | 38.02 | 261.17 | 234.50 |
December | 236.83 | 0.51 | 0.48 | 01-DEC-08:50 | 3636.08 | 30.39 | 166.33 | 220.17 | 3496.72 | 37.18 | 224.50 | 209.00 |
Annual Sum or Average | 3965.83 | 0.51 | 3485.72 | 23.68 | 1374.83 | 3718.33 | 1778.39 | 24.55 | 2155.67 | 3348.33 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1388.16 | 16.86 | 0.00 | 220.17 | 800.24 | 19.89 | 131.17 | 205.83 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 8110.27 | 34.12 | 276.50 | 390.00 | 4636.26 | 38.02 | 261.17 | 345.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-08:50 | 1440.00 | 20.67 | 73.67 | 198.67 | 864.09 | 23.59 | 83.00 | 151.00 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-08:20 | 1436.89 | 18.27 | 48.83 | 227.33 | 852.73 | 21.76 | 91.50 | 186.83 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:49 | 2511.32 | 20.64 | 73.17 | 306.83 | 1466.79 | 23.73 | 138.83 | 266.50 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:50 | 2528.42 | 19.94 | 65.17 | 343.67 | 1474.52 | 23.30 | 107.83 | 288.67 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-05:40 | 2907.70 | 20.72 | 96.33 | 392.67 | 1249.88 | 22.51 | 124.00 | 337.67 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 3529.18 | 20.68 | 107.17 | 403.50 | 1510.22 | 22.79 | 129.67 | 364.17 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 3844.80 | 21.53 | 108.83 | 406.50 | 1621.67 | 23.32 | 112.33 | 368.83 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-05:40 | 2871.28 | 19.50 | 86.83 | 375.50 | 1746.61 | 23.00 | 133.17 | 332.50 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:30 | 2232.80 | 19.70 | 81.83 | 309.83 | 1276.72 | 23.03 | 130.67 | 268.33 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:39 | 1973.25 | 19.92 | 81.67 | 269.83 | 1185.85 | 23.07 | 124.00 | 222.67 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-07:00 | 1304.64 | 20.07 | 80.50 | 211.83 | 691.30 | 21.45 | 78.17 | 163.17 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-08:50 | 1115.77 | 20.27 | 79.83 | 184.83 | 701.34 | 23.49 | 81.17 | 136.33 |
Annual Sum or Average | 3965.83 | 0.51 | 2472.33 | 20.20 | 983.83 | 3631.00 | 1282.26 | 22.92 | 1334.33 | 3086.67 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1115.77 | 18.27 | 48.83 | 184.83 | 691.30 | 21.45 | 78.17 | 136.33 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 3844.80 | 21.53 | 108.83 | 406.50 | 1746.61 | 23.73 | 138.83 | 368.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.57 | 0.48 | 01-JAN-11:30 | 469.85 | 12.86 | 0.00 | 164.17 | 279.27 | 16.11 | 0.00 | 57.17 |
February | 275.00 | 0.54 | 0.48 | 02-FEB-10:00 | 511.76 | 13.75 | 0.00 | 204.50 | 317.99 | 17.08 | 0.00 | 111.50 |
March | 304.00 | 0.51 | 0.48 | 01-MAR-08:20 | 815.93 | 16.04 | 0.00 | 296.17 | 480.00 | 19.14 | 0.00 | 238.83 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 848.40 | 16.70 | 0.00 | 339.50 | 507.26 | 19.70 | 0.83 | 273.17 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-06:10 | 1058.75 | 18.98 | 38.17 | 402.67 | 619.09 | 21.67 | 74.50 | 357.00 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 1097.45 | 20.67 | 96.17 | 430.33 | 605.91 | 20.51 | 87.17 | 391.33 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 1073.55 | 20.15 | 72.17 | 418.33 | 614.16 | 20.57 | 61.67 | 381.67 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 826.42 | 16.31 | 0.00 | 389.33 | 530.66 | 19.34 | 2.17 | 350.67 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-07:10 | 672.39 | 15.21 | 0.00 | 305.33 | 420.55 | 18.31 | 0.00 | 230.83 |
October | 317.67 | 0.54 | 0.48 | 01-OCT-12:39 | 555.55 | 14.14 | 0.00 | 244.00 | 341.03 | 17.39 | 0.00 | 151.50 |
November | 269.50 | 0.57 | 0.48 | 01-NOV-09:20 | 439.67 | 12.85 | 0.00 | 173.33 | 266.44 | 16.18 | 0.00 | 44.33 |
December | 236.83 | 0.59 | 0.48 | 01-DEC-10:20 | 381.03 | 12.18 | 0.00 | 140.17 | 230.47 | 15.59 | 0.00 | 8.50 |
Annual Sum or Average | 3965.83 | 0.52 | 775.23 | 16.33 | 206.50 | 3507.83 | 460.51 | 18.81 | 226.33 | 2596.50 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 381.03 | 12.18 | 0.00 | 140.17 | 230.47 | 15.59 | 0.00 | 8.50 | |
Maximum of Months | 434.17 | 0.59 | 0.48 | 1097.45 | 20.67 | 96.17 | 430.33 | 619.09 | 21.67 | 87.17 | 391.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.54 | 0.48 | 01-JAN-11:09 | 1326.66 | 19.71 | 68.33 | 191.83 | 823.39 | 22.57 | 80.00 | 143.83 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-11:50 | 1762.17 | 20.53 | 77.33 | 226.67 | 907.64 | 21.84 | 93.67 | 185.00 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:30 | 2367.76 | 20.39 | 71.00 | 302.83 | 1341.73 | 23.50 | 138.67 | 263.83 |
April | 325.17 | 0.50 | 0.48 | 01-APR-09:09 | 2474.14 | 20.38 | 75.83 | 332.00 | 1436.71 | 22.29 | 110.67 | 290.83 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-07:10 | 2922.44 | 19.46 | 74.50 | 384.83 | 1686.18 | 21.73 | 115.50 | 342.00 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 2988.68 | 17.61 | 52.00 | 405.50 | 1333.53 | 19.51 | 99.17 | 364.33 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:00 | 3479.44 | 19.44 | 79.67 | 393.50 | 1553.14 | 19.85 | 86.00 | 356.17 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-07:10 | 2570.52 | 19.18 | 88.33 | 370.17 | 1463.35 | 21.18 | 107.17 | 331.00 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-07:30 | 2733.06 | 20.96 | 98.33 | 311.50 | 1057.79 | 21.33 | 104.00 | 268.33 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-12:39 | 1760.85 | 20.07 | 80.67 | 266.67 | 942.04 | 21.96 | 113.00 | 222.50 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-09:20 | 1503.37 | 20.28 | 81.83 | 208.67 | 894.32 | 23.38 | 97.33 | 164.50 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-10:20 | 1066.39 | 20.28 | 76.67 | 189.50 | 578.21 | 21.29 | 69.33 | 133.00 |
Annual Sum or Average | 3965.83 | 0.52 | 2382.78 | 19.75 | 924.50 | 3583.67 | 1224.32 | 21.54 | 1214.50 | 3065.33 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1066.39 | 17.61 | 52.00 | 189.50 | 578.21 | 19.51 | 69.33 | 133.00 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 3479.44 | 20.96 | 98.33 | 405.50 | 1686.18 | 23.50 | 138.67 | 364.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.51 | 0.48 | 01-JAN-08:00 | 4239.96 | 25.47 | 138.83 | 219.00 | 4326.83 | 37.04 | 214.00 | 206.50 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-08:20 | 6795.39 | 33.15 | 239.17 | 247.50 | 2913.95 | 28.46 | 169.50 | 239.00 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:00 | 8065.76 | 30.93 | 249.67 | 313.33 | 1555.89 | 17.22 | 6.67 | 283.33 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:50 | 1813.18 | 11.82 | 0.00 | 333.67 | 1077.52 | 16.68 | 0.00 | 294.83 |
May | 385.83 | 0.51 | 0.48 | 01-MAY-06:40 | 1602.94 | 11.74 | 0.00 | 380.67 | 935.89 | 16.53 | 0.00 | 332.67 |
June | 434.17 | 0.52 | 0.48 | 01-JUN-13:39 | 1366.18 | 11.29 | 0.00 | 386.67 | 827.18 | 16.14 | 0.00 | 338.83 |
July | 417.33 | 0.51 | 0.48 | 01-JUL-06:49 | 1468.39 | 11.69 | 0.00 | 388.50 | 914.04 | 16.62 | 0.00 | 347.00 |
August | 421.33 | 0.52 | 0.48 | 01-AUG-06:49 | 1576.65 | 11.00 | 0.00 | 365.67 | 978.86 | 15.86 | 0.00 | 325.50 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 2297.88 | 12.78 | 29.50 | 315.50 | 1164.13 | 16.03 | 5.50 | 284.17 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:50 | 6926.65 | 32.14 | 269.50 | 292.33 | 1919.51 | 20.48 | 75.67 | 275.33 |
November | 269.50 | 0.51 | 0.48 | 01-NOV-08:09 | 4780.12 | 28.57 | 191.00 | 238.33 | 4642.14 | 36.41 | 248.67 | 231.67 |
December | 236.83 | 0.51 | 0.48 | 01-DEC-08:50 | 2931.60 | 21.09 | 108.67 | 219.50 | 3532.00 | 36.53 | 217.83 | 209.17 |
Annual Sum or Average | 3965.83 | 0.51 | 3366.99 | 18.78 | 1226.33 | 3700.67 | 1822.46 | 21.31 | 937.83 | 3368.00 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1366.18 | 11.00 | 0.00 | 219.00 | 827.18 | 15.86 | 0.00 | 206.50 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 8065.76 | 33.15 | 269.50 | 388.50 | 4642.14 | 37.04 | 248.67 | 347.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-08:00 | 1436.47 | 18.32 | 73.33 | 198.17 | 801.55 | 19.88 | 47.00 | 152.83 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-08:09 | 1437.35 | 15.12 | 48.83 | 227.17 | 876.22 | 19.72 | 48.17 | 190.50 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:49 | 2508.95 | 17.67 | 72.50 | 306.00 | 1499.28 | 21.69 | 68.50 | 269.33 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:39 | 2533.29 | 16.61 | 64.67 | 343.17 | 1509.11 | 20.95 | 60.17 | 292.83 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-05:40 | 2906.10 | 17.65 | 95.83 | 392.17 | 1284.89 | 20.00 | 57.83 | 342.17 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 3520.42 | 17.52 | 107.17 | 402.33 | 1550.90 | 20.28 | 78.33 | 367.17 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 3844.83 | 18.43 | 108.67 | 406.33 | 1666.98 | 20.80 | 74.17 | 372.67 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-05:40 | 2879.06 | 16.16 | 86.67 | 375.00 | 1786.02 | 20.63 | 85.00 | 335.67 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:30 | 2235.73 | 16.67 | 81.33 | 309.00 | 1307.01 | 20.88 | 74.67 | 271.00 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:30 | 1921.77 | 16.70 | 76.67 | 268.67 | 1208.71 | 21.19 | 78.50 | 227.33 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-07:00 | 1109.43 | 14.99 | 55.17 | 210.50 | 708.77 | 19.58 | 54.00 | 168.33 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-08:50 | 1111.08 | 17.90 | 79.83 | 184.33 | 714.59 | 22.08 | 72.83 | 139.17 |
Annual Sum or Average | 3965.83 | 0.51 | 2454.69 | 17.01 | 950.67 | 3622.83 | 1308.95 | 20.63 | 799.17 | 3129.00 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1109.43 | 14.99 | 48.83 | 184.33 | 708.77 | 19.58 | 47.00 | 139.17 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 3844.83 | 18.43 | 108.67 | 406.33 | 1786.02 | 22.08 | 85.00 | 372.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.57 | 0.48 | 01-JAN-11:20 | 458.72 | 7.28 | 0.00 | 161.00 | 286.20 | 12.17 | 0.00 | 62.33 |
February | 275.00 | 0.54 | 0.48 | 01-FEB-12:09 | 501.04 | 8.25 | 0.00 | 200.83 | 326.43 | 13.30 | 0.00 | 120.00 |
March | 304.00 | 0.51 | 0.48 | 01-MAR-08:20 | 799.75 | 10.76 | 0.00 | 294.50 | 493.43 | 15.61 | 0.00 | 242.33 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 833.25 | 11.62 | 0.00 | 336.83 | 522.28 | 16.50 | 0.00 | 277.33 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-06:10 | 1042.02 | 14.16 | 37.83 | 401.67 | 637.20 | 18.63 | 36.83 | 360.33 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 1083.04 | 16.57 | 95.33 | 429.00 | 624.92 | 17.10 | 0.00 | 393.50 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 1061.09 | 15.86 | 71.83 | 416.67 | 634.09 | 17.37 | 0.00 | 383.67 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 814.71 | 11.24 | 0.00 | 389.00 | 546.39 | 16.19 | 0.00 | 354.83 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-07:10 | 660.76 | 10.18 | 0.00 | 303.33 | 432.89 | 15.04 | 0.00 | 236.33 |
October | 317.67 | 0.54 | 0.48 | 01-OCT-12:39 | 544.17 | 8.76 | 0.00 | 241.33 | 350.31 | 13.77 | 0.00 | 159.33 |
November | 269.50 | 0.57 | 0.48 | 01-NOV-09:20 | 429.63 | 7.24 | 0.00 | 169.33 | 273.17 | 12.25 | 0.00 | 53.00 |
December | 236.83 | 0.59 | 0.48 | 01-DEC-10:20 | 370.94 | 6.45 | 0.00 | 135.00 | 235.63 | 11.47 | 0.00 | 11.00 |
Annual Sum or Average | 3965.83 | 0.52 | 762.38 | 11.30 | 205.00 | 3478.50 | 473.97 | 15.36 | 36.83 | 2654.00 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 370.94 | 6.45 | 0.00 | 135.00 | 235.63 | 11.47 | 0.00 | 11.00 | |
Maximum of Months | 434.17 | 0.59 | 0.48 | 1083.04 | 16.57 | 95.33 | 429.00 | 637.20 | 18.63 | 36.83 | 393.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.54 | 0.48 | 01-JAN-10:00 | 1321.96 | 17.37 | 67.33 | 191.00 | 839.72 | 21.04 | 60.33 | 146.33 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-11:30 | 1760.57 | 17.84 | 76.67 | 225.83 | 930.46 | 19.76 | 49.67 | 190.00 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:30 | 2362.53 | 17.36 | 69.83 | 301.67 | 1370.86 | 21.41 | 65.00 | 266.33 |
April | 325.17 | 0.50 | 0.48 | 01-APR-09:09 | 2474.89 | 17.19 | 75.17 | 331.33 | 1470.67 | 19.75 | 48.00 | 293.00 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-07:10 | 2682.12 | 16.02 | 74.33 | 384.67 | 1722.95 | 18.96 | 45.83 | 344.67 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 2977.26 | 13.81 | 52.00 | 404.67 | 1369.13 | 16.30 | 0.00 | 367.00 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:00 | 3472.56 | 16.03 | 79.67 | 392.67 | 1595.12 | 16.68 | 3.67 | 359.33 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-07:10 | 2539.19 | 15.71 | 85.17 | 369.50 | 1498.41 | 18.54 | 55.33 | 334.17 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-07:30 | 2495.69 | 16.01 | 72.83 | 310.33 | 1088.59 | 18.87 | 47.67 | 271.33 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-12:39 | 1530.73 | 14.97 | 54.17 | 265.83 | 950.18 | 19.45 | 53.50 | 225.33 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-09:09 | 1491.87 | 17.36 | 77.83 | 208.50 | 823.71 | 19.57 | 53.33 | 164.67 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-10:09 | 905.79 | 15.17 | 51.33 | 188.33 | 591.91 | 19.59 | 50.00 | 137.83 |
Annual Sum or Average | 3965.83 | 0.52 | 2303.49 | 16.10 | 836.33 | 3574.33 | 1246.88 | 18.92 | 532.33 | 3100.00 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 905.79 | 13.81 | 51.33 | 188.33 | 591.91 | 16.30 | 0.00 | 137.83 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 3472.56 | 17.84 | 85.17 | 404.67 | 1722.95 | 21.41 | 65.00 | 367.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.51 | 0.48 | 01-JAN-08:00 | 4238.44 | 25.45 | 138.83 | 219.00 | 4327.77 | 37.04 | 214.00 | 206.50 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-08:20 | 6794.23 | 33.14 | 239.17 | 247.50 | 2915.21 | 28.45 | 169.50 | 239.17 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:00 | 8065.91 | 30.91 | 249.67 | 313.33 | 1557.67 | 17.21 | 6.67 | 283.33 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:50 | 1814.01 | 11.78 | 0.00 | 333.67 | 1078.77 | 16.67 | 0.00 | 294.83 |
May | 385.83 | 0.51 | 0.48 | 01-MAY-06:40 | 1603.79 | 11.70 | 0.00 | 380.67 | 936.98 | 16.51 | 0.00 | 332.83 |
June | 434.17 | 0.52 | 0.48 | 01-JUN-13:39 | 1366.72 | 11.25 | 0.00 | 386.50 | 828.02 | 16.12 | 0.00 | 338.83 |
July | 417.33 | 0.51 | 0.48 | 01-JUL-06:49 | 1468.91 | 11.64 | 0.00 | 388.50 | 914.90 | 16.60 | 0.00 | 347.17 |
August | 421.33 | 0.52 | 0.48 | 01-AUG-06:49 | 1577.26 | 10.96 | 0.00 | 365.67 | 979.83 | 15.84 | 0.00 | 325.67 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 2298.32 | 12.75 | 29.50 | 315.50 | 1165.31 | 16.01 | 5.50 | 284.17 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:50 | 6925.86 | 32.12 | 269.50 | 292.33 | 1920.78 | 20.47 | 75.67 | 275.33 |
November | 269.50 | 0.51 | 0.48 | 01-NOV-08:09 | 4778.66 | 28.55 | 191.00 | 238.33 | 4643.13 | 36.40 | 248.67 | 231.67 |
December | 236.83 | 0.51 | 0.48 | 01-DEC-08:50 | 2929.95 | 21.06 | 108.67 | 219.50 | 3532.63 | 36.52 | 217.83 | 209.17 |
Annual Sum or Average | 3965.83 | 0.51 | 3366.95 | 18.75 | 1226.33 | 3700.50 | 1823.54 | 21.29 | 937.83 | 3368.67 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1366.72 | 10.96 | 0.00 | 219.00 | 828.02 | 15.84 | 0.00 | 206.50 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 8065.91 | 33.14 | 269.50 | 388.50 | 4643.13 | 37.04 | 248.67 | 347.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-08:00 | 1436.20 | 18.28 | 73.33 | 198.00 | 802.05 | 19.86 | 47.00 | 153.00 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-08:09 | 1436.95 | 15.08 | 48.83 | 227.17 | 876.75 | 19.71 | 48.17 | 190.50 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:49 | 2508.74 | 17.63 | 72.50 | 306.00 | 1500.24 | 21.68 | 68.50 | 269.33 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:39 | 2533.08 | 16.57 | 64.67 | 343.17 | 1509.94 | 20.94 | 60.17 | 293.33 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-05:40 | 2906.16 | 17.61 | 95.83 | 392.33 | 1285.84 | 19.99 | 57.83 | 342.33 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 3520.10 | 17.47 | 107.17 | 402.33 | 1551.72 | 20.27 | 78.33 | 367.33 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 3844.44 | 18.39 | 108.67 | 406.33 | 1667.77 | 20.78 | 74.17 | 372.83 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-05:40 | 2878.75 | 16.12 | 86.67 | 375.00 | 1786.79 | 20.62 | 85.00 | 335.83 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:30 | 2235.31 | 16.63 | 81.33 | 309.00 | 1307.72 | 20.86 | 74.67 | 271.00 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:30 | 1921.39 | 16.66 | 76.67 | 268.33 | 1209.29 | 21.17 | 78.33 | 227.50 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-07:00 | 1109.14 | 14.95 | 55.17 | 210.33 | 709.23 | 19.56 | 54.00 | 168.33 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-08:50 | 1110.79 | 17.86 | 79.83 | 184.33 | 714.97 | 22.07 | 72.83 | 139.33 |
Annual Sum or Average | 3965.83 | 0.51 | 2454.40 | 16.97 | 950.67 | 3622.33 | 1309.67 | 20.62 | 799.00 | 3130.67 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1109.14 | 14.95 | 48.83 | 184.33 | 709.23 | 19.56 | 47.00 | 139.33 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 3844.44 | 18.39 | 108.67 | 406.33 | 1786.79 | 22.07 | 85.00 | 372.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.57 | 0.48 | 01-JAN-11:20 | 458.67 | 7.24 | 0.00 | 160.83 | 286.48 | 12.15 | 0.00 | 63.17 |
February | 275.00 | 0.54 | 0.48 | 01-FEB-12:09 | 500.92 | 8.21 | 0.00 | 200.83 | 326.70 | 13.28 | 0.00 | 120.67 |
March | 304.00 | 0.51 | 0.48 | 01-MAR-08:20 | 799.77 | 10.72 | 0.00 | 294.50 | 493.93 | 15.59 | 0.00 | 242.33 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 833.25 | 11.58 | 0.00 | 336.67 | 522.78 | 16.48 | 0.00 | 277.67 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-06:10 | 1042.06 | 14.12 | 37.83 | 401.67 | 637.79 | 18.61 | 36.83 | 361.17 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 1082.88 | 16.54 | 95.33 | 429.00 | 625.43 | 17.08 | 0.00 | 393.50 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 1060.88 | 15.83 | 71.83 | 416.67 | 634.55 | 17.35 | 0.00 | 383.83 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 814.57 | 11.19 | 0.00 | 389.00 | 546.79 | 16.17 | 0.00 | 354.83 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-07:10 | 660.64 | 10.14 | 0.00 | 303.50 | 433.24 | 15.02 | 0.00 | 236.83 |
October | 317.67 | 0.54 | 0.48 | 01-OCT-12:39 | 544.08 | 8.72 | 0.00 | 241.33 | 350.61 | 13.75 | 0.00 | 159.50 |
November | 269.50 | 0.57 | 0.48 | 01-NOV-09:09 | 429.55 | 7.20 | 0.00 | 169.33 | 273.41 | 12.23 | 0.00 | 53.00 |
December | 236.83 | 0.59 | 0.48 | 01-DEC-10:20 | 370.84 | 6.41 | 0.00 | 134.83 | 235.84 | 11.45 | 0.00 | 11.33 |
Annual Sum or Average | 3965.83 | 0.52 | 762.29 | 11.26 | 205.00 | 3478.17 | 474.37 | 15.34 | 36.83 | 2657.83 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 370.84 | 6.41 | 0.00 | 134.83 | 235.84 | 11.45 | 0.00 | 11.33 | |
Maximum of Months | 434.17 | 0.59 | 0.48 | 1082.88 | 16.54 | 95.33 | 429.00 | 637.79 | 18.61 | 36.83 | 393.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.54 | 0.48 | 01-JAN-10:00 | 1321.73 | 17.34 | 67.33 | 191.00 | 840.22 | 21.03 | 60.17 | 146.33 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-11:30 | 1760.19 | 17.80 | 76.67 | 225.83 | 931.00 | 19.74 | 49.67 | 190.17 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:30 | 2362.32 | 17.32 | 69.83 | 301.67 | 1371.84 | 21.40 | 65.00 | 266.50 |
April | 325.17 | 0.50 | 0.48 | 01-APR-09:09 | 2474.56 | 17.15 | 75.17 | 331.33 | 1471.61 | 19.73 | 48.00 | 293.17 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-07:10 | 2681.97 | 15.98 | 74.33 | 384.50 | 1723.98 | 18.95 | 45.83 | 344.83 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 2977.06 | 13.76 | 52.00 | 404.67 | 1370.03 | 16.28 | 0.00 | 367.00 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:00 | 3472.19 | 15.99 | 79.67 | 392.67 | 1595.99 | 16.66 | 3.67 | 359.33 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-07:10 | 2538.93 | 15.67 | 85.17 | 369.50 | 1499.21 | 18.52 | 55.33 | 334.33 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-07:30 | 2495.26 | 15.97 | 72.83 | 310.33 | 1089.29 | 18.85 | 47.67 | 271.33 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-12:39 | 1530.35 | 14.93 | 54.17 | 265.83 | 950.77 | 19.43 | 53.33 | 225.50 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-09:09 | 1491.52 | 17.32 | 77.67 | 208.50 | 824.18 | 19.56 | 53.33 | 164.83 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-10:09 | 905.49 | 15.13 | 51.33 | 188.33 | 592.29 | 19.57 | 50.00 | 137.83 |
Annual Sum or Average | 3965.83 | 0.52 | 2303.20 | 16.06 | 836.17 | 3574.17 | 1247.64 | 18.90 | 532.00 | 3101.17 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 905.49 | 13.76 | 51.33 | 188.33 | 592.29 | 16.28 | 0.00 | 137.83 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 3472.19 | 17.80 | 85.17 | 404.67 | 1723.98 | 21.40 | 65.00 | 367.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.366908E+11 | 76055.40 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198882E+11 | 59274.41 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102629E+11 | 49732.58 | 04-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.199181E+10 | 24969.66 | 29-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.123438E+10 | 18229.54 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22729212.35 | 6343.24 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.240087E+09 | 9081.08 | 19-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148122E+10 | 22487.29 | 10-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.705863E+10 | 37893.01 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.214751E+11 | 64282.46 | 29-DEC-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100346E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.366908E+11 | 76055.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.314008E+10 | 12880.38 | 20-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100149E+10 | 12472.73 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166500E+09 | 12430.86 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 64481098.62 | 13332.34 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.642189E+09 | 13450.42 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.501475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.314008E+10 | 13450.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.242448E+10 | 14677.89 | 07-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.929038E+09 | 14667.45 | 04-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210229E+09 | 14654.28 | 06-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5185293.73 | 2198.02 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3402345.91 | 1039.01 | 08-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2588431.97 | 683.36 | 05-OCT-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168273E+09 | 14978.78 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.880731E+09 | 15109.96 | 14-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.462392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.242448E+10 | 15109.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.300076E+10 | 21360.89 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.933886E+09 | 21436.51 | 23-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.289341E+09 | 21299.84 | 07-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20416309.50 | 12063.33 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44283772.63 | 19763.49 | 09-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15753694.00 | 10538.81 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.241534E+09 | 21247.79 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.927866E+09 | 21446.51 | 27-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.547384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.300076E+10 | 21446.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.149250E+10 | 14238.12 | 09-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236796E+09 | 14216.42 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21078260.05 | 14215.03 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4101031.71 | 3735.50 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 66089248.49 | 14214.56 | 29-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.149250E+10 | 14238.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.414935E+12 | 801233.92 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.243419E+12 | 639844.21 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155293E+12 | 551467.29 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.466925E+11 | 272911.93 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.276666E+11 | 208620.22 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.814119E+09 | 95719.10 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.607227E+10 | 110818.12 | 19-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.322940E+11 | 269910.23 | 10-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111220E+12 | 437529.73 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.281741E+12 | 705034.16 | 29-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132015E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.414935E+12 | 801233.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.203103E+11 | 576558.77 | 30-JAN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.716381E+10 | 573912.33 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175444E+10 | 575795.38 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.879346E+09 | 573670.85 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.555886E+10 | 575996.33 | 29-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.356667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.203103E+11 | 576558.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.923874E+11 | 115888.64 | 12-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.476798E+11 | 115424.07 | 06-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218650E+11 | 115458.76 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.329252E+10 | 122141.05 | 28-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196067E+10 | 125591.88 | 22-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.430892E+09 | 108672.67 | 20-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.290535E+10 | 121076.68 | 04-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210499E+11 | 115143.26 | 27-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.574611E+11 | 115547.72 | 18-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.249033E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.923874E+11 | 125591.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.631368E+11 | 169652.70 | 09-JAN-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311993E+11 | 169583.41 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150332E+11 | 169595.46 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.279617E+10 | 177499.48 | 28-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176662E+10 | 168105.93 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4075793.58 | 11010.96 | 17-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1578491.26 | 4548.22 | 18-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.418296E+09 | 62750.66 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.254678E+10 | 167714.46 | 11-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162640E+11 | 169191.89 | 29-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.415717E+11 | 169244.86 | 15-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174739E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.631368E+11 | 177499.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.609799E+11 | 200392.14 | 23-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249798E+11 | 200555.91 | 06-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129068E+11 | 200847.20 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.273876E+10 | 212536.42 | 28-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.242781E+10 | 198139.23 | 09-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 44660061.91 | 22062.78 | 17-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.300653E+09 | 44082.86 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133455E+10 | 197907.78 | 11-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125928E+11 | 200370.56 | 27-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347713E+11 | 200396.96 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153077E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.609799E+11 | 212536.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.570793E+11 | 179276.84 | 10-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.255715E+11 | 179342.76 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125098E+11 | 179291.92 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197164E+10 | 178402.08 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139903E+10 | 176237.00 | 09-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34299796.20 | 13818.78 | 17-JUN-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.333284E+09 | 42273.42 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.181477E+10 | 166005.54 | 11-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123239E+11 | 178931.95 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.335196E+11 | 178959.44 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146557E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.570793E+11 | 179342.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.475521E+11 | 88729.85 | 10-JAN-21:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.271260E+11 | 71649.09 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186021E+11 | 63049.41 | 04-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.660273E+10 | 33197.14 | 29-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.386926E+10 | 25760.91 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.272593E+09 | 12324.92 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12691450.96 | 3289.30 | 18-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136018E+10 | 15538.71 | 19-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.497800E+10 | 32546.53 | 10-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139176E+11 | 46715.74 | 27-NOV-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.328863E+11 | 78614.11 | 29-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157180E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.475521E+11 | 88729.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.194078E+11 | 71870.57 | 02-JAN-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.883699E+10 | 71976.95 | 13-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.520362E+10 | 71848.47 | 07-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106342E+10 | 71379.65 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109049E+10 | 71806.69 | 08-MAY-04:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 69905743.97 | 34050.91 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100410E+10 | 71969.79 | 10-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.571368E+10 | 71808.31 | 20-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126877E+11 | 71761.20 | 11-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.550777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.194078E+11 | 71976.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.167839E+11 | 15477.16 | 02-JAN-04:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.949653E+10 | 15444.77 | 13-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.660285E+10 | 15433.81 | 20-MAR-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.219943E+10 | 15428.02 | 10-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135681E+10 | 15458.26 | 08-MAY-04:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 57931606.57 | 15333.67 | 17-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20511166.23 | 15285.06 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.582638E+09 | 15420.27 | 19-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.228200E+10 | 15476.56 | 10-OCT-04:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.676371E+10 | 15437.60 | 13-NOV-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127567E+11 | 15433.64 | 08-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.589031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.167839E+11 | 15477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107474E+11 | 17044.71 | 05-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.556925E+10 | 17013.82 | 24-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.370567E+10 | 17030.41 | 03-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123159E+10 | 16976.73 | 15-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.762630E+09 | 16973.65 | 09-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38278944.15 | 16315.18 | 17-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10639000.56 | 16935.90 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.329985E+09 | 16966.96 | 13-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121074E+10 | 16993.11 | 05-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.410552E+10 | 16991.18 | 28-NOV-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.815798E+10 | 17034.65 | 22-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.358697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107474E+11 | 17044.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.119909E+11 | 21743.33 | 13-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.559021E+10 | 21753.08 | 14-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.428657E+10 | 21755.10 | 31-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171485E+10 | 21733.61 | 28-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128683E+10 | 21732.57 | 09-MAY-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 98482364.13 | 21599.52 | 17-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 27294682.25 | 21564.42 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.378267E+09 | 21603.84 | 13-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115812E+10 | 21710.58 | 10-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.393838E+10 | 21757.04 | 29-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.852568E+10 | 21761.28 | 09-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119909E+11 | 21761.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101516E+11 | 19306.47 | 25-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.483951E+10 | 19310.04 | 09-FEB-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.338342E+10 | 19230.74 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108119E+10 | 19211.79 | 19-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.720409E+09 | 19237.42 | 08-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 51263227.48 | 10516.27 | 17-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19127436.52 | 11750.08 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.328186E+09 | 19204.59 | 19-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111350E+10 | 19325.26 | 10-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.334335E+10 | 19230.71 | 13-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.671391E+10 | 19234.67 | 04-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.101516E+11 | 19325.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.182365E+09 | 11023.86 | 10-JAN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.182365E+09 | 11023.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.547329E+09 | 0.547329E+09 | 36647.46 | 27-FEB-15:30 | 36647.46 | 0.00 |
March | 0.00 | 0.00 | 27485668.80 | 27485668.80 | 5892.17 | 14-MAR-13:30 | 5892.17 | 0.00 |
April | 0.00 | 0.00 | 0.572886E+10 | 0.572886E+10 | 72757.10 | 07-APR-14:00 | 72757.10 | 0.00 |
May | 0.00 | 0.00 | 0.157044E+11 | 0.157044E+11 | 97046.87 | 19-MAY-15:20 | 97046.87 | 0.02 |
June | 0.00 | 0.00 | 0.526794E+11 | 0.526289E+11 | 113381.43 | 29-JUN-14:40 | 113381.43 | 0.17 |
July | 0.00 | 0.00 | 0.911420E+11 | 0.909781E+11 | 139001.18 | 17-JUL-15:20 | 139001.18 | 0.31 |
August | 0.00 | 0.00 | 0.820902E+11 | 0.820902E+11 | 135935.70 | 07-AUG-15:30 | 135935.70 | 0.13 |
September | 0.00 | 0.00 | 0.339074E+11 | 0.327995E+11 | 170322.07 | 07-SEP-15:00 | 90599.22 | 0.10 |
October | 0.00 | 0.00 | 0.909578E+10 | 0.909578E+10 | 90044.00 | 18-OCT-15:50 | 90044.00 | 0.00 |
November | 0.00 | 0.00 | 0.449206E+09 | 0.449206E+09 | 15081.60 | 17-NOV-17:00 | 15081.60 | 0.00 |
December | 0.00 | 0.00 | 441.66 | 441.66 | 0.70 | 20-DEC-06:15 | 0.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.291372E+12 | 0.290050E+12 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.911420E+11 | 0.909781E+11 | 170322.07 | 139001.18 | 0.31 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 44594.84 | 44594.84 | 3.73 | 02-JAN-06:03 | 3.73 | 0.00 |
February | 0.00 | 0.00 | 0.381850E+10 | 0.381850E+10 | 261458.64 | 27-FEB-13:40 | 261458.64 | 0.00 |
March | 0.00 | 0.00 | 34632748.16 | 34632748.16 | 9028.05 | 14-MAR-13:30 | 9028.05 | 0.00 |
April | 0.00 | 0.00 | 0.382635E+11 | 0.382635E+11 | 527069.65 | 06-APR-16:00 | 527069.65 | 0.00 |
May | 0.00 | 0.00 | 0.131126E+12 | 0.131126E+12 | 902728.77 | 19-MAY-15:30 | 902728.77 | 0.02 |
June | 0.00 | 0.00 | 0.438724E+12 | 0.438325E+12 | 1054031.85 | 29-JUN-14:50 | 1054031.85 | 0.15 |
July | 0.00 | 0.00 | 0.741519E+12 | 0.740629E+12 | 1234778.66 | 19-JUL-05:03 | 758689.37 | 0.27 |
August | 0.00 | 0.00 | 0.638843E+12 | 0.638843E+12 | 1152497.44 | 10-AUG-15:40 | 1152497.44 | 0.12 |
September | 0.00 | 0.00 | 0.291560E+12 | 0.281647E+12 | 1554962.33 | 07-SEP-15:00 | 827986.92 | 0.09 |
October | 0.00 | 0.00 | 0.678401E+11 | 0.678401E+11 | 719539.77 | 18-OCT-15:10 | 719539.77 | 0.00 |
November | 0.00 | 0.00 | 0.316546E+10 | 0.316546E+10 | 108144.83 | 03-NOV-14:00 | 108144.83 | 0.00 |
December | 0.00 | 0.00 | 52811.18 | 52811.18 | 2.27 | 22-DEC-06:10 | 2.27 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.235489E+13 | 0.234369E+13 | 0.05 | |||
Minimum of Months | 0.00 | 0.00 | 44594.84 | 44594.84 | 2.27 | 2.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.741519E+12 | 0.740629E+12 | 1554962.33 | 1152497.44 | 0.27 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 142480.92 | 142480.92 | 880.52 | 17-JAN-04:52 | 880.52 | 0.00 |
February | 0.00 | 0.00 | 0.279553E+09 | 0.279553E+09 | 21580.44 | 26-FEB-14:51 | 21580.44 | 0.00 |
March | 0.00 | 0.00 | 1418806.73 | 1418806.73 | 341.26 | 14-MAR-13:40 | 341.26 | 0.00 |
April | 0.00 | 0.00 | 0.342778E+10 | 0.342778E+10 | 51639.34 | 06-APR-16:00 | 51639.34 | 0.00 |
May | 0.00 | 0.00 | 0.135838E+11 | 0.135838E+11 | 109549.13 | 19-MAY-15:30 | 109549.13 | 0.01 |
June | 0.00 | 0.00 | 0.485946E+11 | 0.485398E+11 | 127291.63 | 29-JUN-15:00 | 127291.63 | 0.15 |
July | 0.00 | 0.00 | 0.829818E+11 | 0.828859E+11 | 154040.54 | 17-JUL-15:30 | 154040.54 | 0.27 |
August | 0.00 | 0.00 | 0.691476E+11 | 0.691476E+11 | 140782.15 | 07-AUG-15:50 | 140782.15 | 0.11 |
September | 0.00 | 0.00 | 0.296298E+11 | 0.286470E+11 | 159383.50 | 07-SEP-15:20 | 91808.45 | 0.09 |
October | 0.00 | 0.00 | 0.570456E+10 | 0.570456E+10 | 71885.44 | 18-OCT-15:00 | 71885.44 | 0.00 |
November | 0.00 | 0.00 | 0.238240E+09 | 0.238240E+09 | 8954.08 | 04-NOV-14:00 | 8954.08 | 0.00 |
December | 0.00 | 0.00 | 194737.66 | 194737.66 | 865.93 | 26-DEC-05:17 | 865.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.253589E+12 | 0.252456E+12 | 0.05 | |||
Minimum of Months | 0.00 | 0.00 | 142480.92 | 142480.92 | 341.26 | 341.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.829818E+11 | 0.828859E+11 | 159383.50 | 154040.54 | 0.27 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 330121.22 | 330121.22 | 4738.22 | 24-JAN-05:01 | 4738.22 | 0.00 |
February | 0.00 | 0.00 | 0.253499E+09 | 0.253499E+09 | 21750.05 | 27-FEB-15:00 | 21750.05 | 0.00 |
March | 0.00 | 0.00 | 27403.46 | 27403.46 | 45.67 | 03-MAR-07:50 | 45.67 | 0.00 |
April | 0.00 | 0.00 | 0.210276E+10 | 0.210276E+10 | 42581.56 | 07-APR-14:00 | 42581.56 | 0.00 |
May | 0.00 | 0.00 | 0.773591E+10 | 0.773591E+10 | 51429.40 | 19-MAY-15:00 | 51429.40 | 0.02 |
June | 0.00 | 0.00 | 0.270330E+11 | 0.270222E+11 | 61219.33 | 26-JUN-11:00 | 61219.33 | 0.12 |
July | 0.00 | 0.00 | 0.462436E+11 | 0.462110E+11 | 91893.32 | 19-JUL-05:03 | 53059.36 | 0.22 |
August | 0.00 | 0.00 | 0.423222E+11 | 0.423222E+11 | 93262.07 | 06-AUG-19:20 | 93262.07 | 0.12 |
September | 0.00 | 0.00 | 0.177612E+11 | 0.174169E+11 | 108678.16 | 04-SEP-16:51 | 108678.16 | 0.08 |
October | 0.00 | 0.00 | 0.521742E+10 | 0.521742E+10 | 51799.87 | 18-OCT-14:00 | 51799.87 | 0.00 |
November | 0.00 | 0.00 | 72775089.87 | 72775089.87 | 21633.98 | 17-NOV-06:03 | 21633.98 | 0.00 |
December | 0.00 | 0.00 | 96326.67 | 96326.67 | 94.48 | 27-DEC-12:40 | 94.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.148743E+12 | 0.148355E+12 | 0.05 | |||
Minimum of Months | 0.00 | 0.00 | 27403.46 | 27403.46 | 45.67 | 45.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.462436E+11 | 0.462110E+11 | 108678.16 | 108678.16 | 0.22 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.264833E+10 | 0.264802E+10 | 2162.16 | 01-JAN-16:05 | 2155.50 | 0.00 |
February | 0.00 | 0.00 | 0.802248E+10 | 0.802248E+10 | 4825.50 | 26-FEB-17:27 | 4825.50 | 0.00 |
March | 0.00 | 0.00 | 0.147958E+11 | 0.147958E+11 | 7437.19 | 31-MAR-24:00 | 7437.19 | 0.00 |
April | 0.00 | 0.00 | 0.198848E+11 | 0.198763E+11 | 8783.45 | 22-APR-18:10 | 8783.45 | 0.00 |
May | 0.00 | 0.00 | 0.546152E+10 | 0.543650E+10 | 4090.36 | 31-MAY-24:00 | 4090.36 | 0.00 |
June | 0.00 | 0.00 | 0.107509E+11 | 0.106576E+11 | 6002.97 | 30-JUN-23:57 | 5979.06 | 0.00 |
July | 0.00 | 0.00 | 0.164176E+11 | 0.163082E+11 | 7854.63 | 31-JUL-23:40 | 7854.63 | 0.00 |
August | 0.00 | 0.00 | 0.212765E+11 | 0.211965E+11 | 8836.73 | 05-AUG-19:44 | 8800.29 | 0.00 |
September | 0.00 | 0.00 | 0.557017E+10 | 0.548182E+10 | 3932.36 | 30-SEP-24:00 | 3932.36 | 0.00 |
October | 0.00 | 0.00 | 0.103982E+11 | 0.103869E+11 | 5594.54 | 31-OCT-24:00 | 5594.54 | 0.00 |
November | 0.00 | 0.00 | 0.145101E+11 | 0.145078E+11 | 6417.52 | 12-NOV-16:20 | 6417.52 | 0.00 |
December | 0.00 | 0.00 | 0.193914E+11 | 0.193911E+11 | 8219.65 | 10-DEC-16:00 | 8219.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.149128E+12 | 0.148709E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.264833E+10 | 0.264802E+10 | 2162.16 | 2155.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.212765E+11 | 0.211965E+11 | 8836.73 | 8800.29 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.541830E+10 | 0.541516E+10 | 15004.75 | 13-JAN-16:30 | 15004.75 | 0.00 |
February | 0.00 | 0.00 | 0.555600E+11 | 0.555600E+11 | 40858.59 | 28-FEB-17:00 | 40858.59 | 0.00 |
March | 0.00 | 0.00 | 0.121420E+12 | 0.121420E+12 | 64162.46 | 31-MAR-23:40 | 64162.46 | 0.00 |
April | 0.00 | 0.00 | 0.178035E+12 | 0.177949E+12 | 81097.12 | 22-APR-18:10 | 81097.12 | 0.00 |
May | 0.00 | 0.00 | 0.438765E+11 | 0.436332E+11 | 38660.89 | 31-MAY-24:00 | 38660.89 | 0.00 |
June | 0.00 | 0.00 | 0.990206E+11 | 0.980967E+11 | 58396.29 | 30-JUN-23:57 | 58161.94 | 0.00 |
July | 0.00 | 0.00 | 0.155215E+12 | 0.154127E+12 | 76014.11 | 31-JUL-23:53 | 76014.11 | 0.00 |
August | 0.00 | 0.00 | 0.201468E+12 | 0.200670E+12 | 84234.23 | 05-AUG-19:42 | 83894.03 | 0.00 |
September | 0.00 | 0.00 | 0.468638E+11 | 0.460047E+11 | 35014.09 | 30-SEP-23:50 | 35014.09 | 0.00 |
October | 0.00 | 0.00 | 0.862199E+11 | 0.861069E+11 | 47375.58 | 31-OCT-24:00 | 47375.58 | 0.00 |
November | 0.00 | 0.00 | 0.118439E+12 | 0.118415E+12 | 58442.08 | 03-NOV-16:00 | 57894.99 | 0.00 |
December | 0.00 | 0.00 | 0.155652E+12 | 0.155649E+12 | 72893.99 | 06-DEC-16:10 | 72596.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.126719E+13 | 0.126305E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.541830E+10 | 0.541516E+10 | 15004.75 | 15004.75 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.201468E+12 | 0.200670E+12 | 84234.23 | 83894.03 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 98383223.48 | 98383223.48 | 1396.58 | 13-JAN-16:30 | 1396.58 | 0.00 |
February | 0.00 | 0.00 | 0.393360E+10 | 0.393360E+10 | 3955.80 | 28-FEB-17:00 | 3955.80 | 0.00 |
March | 0.00 | 0.00 | 0.103376E+11 | 0.103376E+11 | 5926.23 | 28-MAR-17:50 | 5926.23 | 0.00 |
April | 0.00 | 0.00 | 0.164772E+11 | 0.164687E+11 | 8136.91 | 25-APR-18:00 | 8136.91 | 0.00 |
May | 0.00 | 0.00 | 0.362052E+10 | 0.359666E+10 | 3797.89 | 31-MAY-23:50 | 3797.89 | 0.00 |
June | 0.00 | 0.00 | 0.966923E+10 | 0.957700E+10 | 5815.23 | 30-JUN-23:57 | 5791.73 | 0.00 |
July | 0.00 | 0.00 | 0.154866E+11 | 0.153779E+11 | 7609.65 | 31-JUL-23:53 | 7609.65 | 0.00 |
August | 0.00 | 0.00 | 0.200036E+11 | 0.199240E+11 | 8608.50 | 05-AUG-19:44 | 8563.26 | 0.00 |
September | 0.00 | 0.00 | 0.404857E+10 | 0.396454E+10 | 3271.41 | 04-SEP-17:32 | 3271.41 | 0.00 |
October | 0.00 | 0.00 | 0.700836E+10 | 0.699742E+10 | 4396.67 | 18-OCT-16:50 | 4396.67 | 0.00 |
November | 0.00 | 0.00 | 0.971643E+10 | 0.971416E+10 | 5692.71 | 03-NOV-16:00 | 5637.82 | 0.00 |
December | 0.00 | 0.00 | 0.134091E+11 | 0.134088E+11 | 7147.41 | 06-DEC-16:10 | 7119.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.113809E+12 | 0.113399E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 98383223.48 | 98383223.48 | 1396.58 | 1396.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.200036E+11 | 0.199240E+11 | 8608.50 | 8563.26 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 323995.45 | 1937802.61 | 09-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 190987.31 | 1754014.61 | 07-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 101075.15 | 1827513.10 | 07-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 28161.82 | 1259582.69 | 01-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16934.25 | 1213159.16 | 09-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 551.38 | 122299.68 | 16-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 35.32 | 118193.97 | 18-AUG-05:02 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 4157.39 | 455337.18 | 19-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 20131.52 | 1230036.50 | 11-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 84316.57 | 1527465.53 | 27-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 208157.52 | 1727477.61 | 27-DEC-06:01 |
Annual Sum or Average | 0.00 | 81214.97 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 323995.45 | 1937802.61 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 580.02 | 21745.72 | 26-JAN-04:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 5026.74 | 674825.38 | 27-FEB-13:40 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 1752.25 | 59999.74 | 14-MAR-13:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 39001.39 | 1091503.14 | 07-APR-14:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 112819.58 | 1173972.67 | 19-MAY-12:20 | 160.67 | 270926.22 | 22-MAY-04:03 |
June | 310226.17 | 1356975.59 | 29-JUN-14:50 | 60.57 | 131651.34 | 11-JUN-19:42 |
July | 477479.48 | 1596911.87 | 17-JUL-15:30 | 36.67 | 89074.53 | 15-JUL-02:32 |
August | 412641.48 | 1488823.35 | 07-AUG-15:40 | 33.47 | 93554.69 | 12-AUG-02:42 |
September | 226618.09 | 1978323.13 | 07-SEP-15:00 | 33.54 | 137110.42 | 24-SEP-08:53 |
October | 61399.25 | 1070290.63 | 16-OCT-12:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5165.97 | 251607.76 | 17-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 952.21 | 22427.74 | 26-DEC-05:17 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 138814.93 | 27.34 | ||||
Minimum of Months | 580.02 | 21745.72 | 0.00 | 0.00 | ||
Maximum of Months | 477479.48 | 1978323.13 | 160.67 | 270926.22 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 30.14 | 24-JAN-05:01 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 2413.10 | 429530.62 | 27-FEB-13:40 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 37.43 | 23837.46 | 14-MAR-13:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 22844.25 | 783344.84 | 06-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 72242.83 | 1210559.25 | 19-MAY-12:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 244755.94 | 1347821.38 | 29-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 391479.68 | 2057556.34 | 19-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 338752.20 | 1480660.59 | 07-AUG-15:40 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 163109.64 | 2036438.66 | 07-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 38988.06 | 1048797.13 | 18-OCT-15:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 1913.01 | 168927.77 | 01-NOV-04:01 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.15 | 1047.06 | 26-DEC-05:17 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 107213.05 | 0.00 | ||||
Minimum of Months | 0.00 | 30.14 | 0.00 | 0.00 | ||
Maximum of Months | 391479.68 | 2057556.34 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4497.21 | 23234.04 | 13-JAN-16:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 35054.04 | 74981.01 | 27-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 67333.26 | 94056.51 | 31-MAR-23:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 102913.18 | 193500.42 | 07-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 31607.60 | 166227.53 | 20-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 83699.39 | 234207.58 | 29-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 143583.88 | 332760.47 | 17-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 160833.65 | 344546.49 | 06-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 46396.23 | 224983.15 | 02-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 50442.00 | 147181.78 | 18-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 67606.64 | 87392.75 | 17-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 86288.07 | 106613.13 | 06-DEC-16:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 73649.68 | 0.00 | ||||
Minimum of Months | 4497.21 | 23234.04 | 0.00 | 0.00 | ||
Maximum of Months | 160833.65 | 344546.49 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17332.17 | 58855.85 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 17710.16 | 59175.16 | 23-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 18546.02 | 59075.44 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 16883.46 | 57456.21 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16524.89 | 54983.50 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15933.17 | 51689.52 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14100.23 | 48654.35 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 14986.26 | 46970.17 | 01-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 14316.18 | 48065.18 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14900.48 | 50877.00 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15950.55 | 54068.61 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 16275.18 | 56870.36 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 16112.35 | ||||
Minimum of Months | 0.00 | 0.00 | 14100.23 | 46970.17 | ||
Maximum of Months | 0.00 | 0.00 | 18546.02 | 59175.16 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 8.17 | 21494.04 | 26-JAN-06:50 | 610.64 | 106136.90 | 18-JAN-06:30 |
February | 2065.93 | 393963.00 | 27-FEB-13:40 | 999.66 | 125121.23 | 08-FEB-06:50 |
March | 124.86 | 23282.03 | 14-MAR-13:30 | 1888.77 | 129553.47 | 04-MAR-05:01 |
April | 21771.62 | 747203.33 | 07-APR-13:00 | 1773.85 | 106812.09 | 19-APR-14:50 |
May | 76371.49 | 1948357.10 | 19-MAY-15:30 | 1477.11 | 125563.72 | 08-MAY-05:50 |
June | 283567.14 | 2171062.01 | 20-JUN-15:40 | 1205.35 | 83799.92 | 16-JUN-14:50 |
July | 472812.02 | 2256031.81 | 19-JUL-12:20 | 848.13 | 68544.86 | 05-JUL-05:30 |
August | 402430.65 | 2097326.83 | 09-AUG-10:50 | 1457.73 | 74957.82 | 19-AUG-05:50 |
September | 188132.61 | 4007560.36 | 07-SEP-15:00 | 1310.41 | 106087.41 | 18-SEP-13:20 |
October | 37961.18 | 1798294.45 | 18-OCT-14:30 | 1721.73 | 108532.29 | 02-OCT-05:30 |
November | 1288.14 | 162868.87 | 17-NOV-17:00 | 1893.96 | 122536.86 | 13-NOV-05:01 |
December | 28.98 | 20703.59 | 26-DEC-03:45 | 1178.21 | 126688.07 | 07-DEC-06:02 |
Annual Sum or Average | 124883.53 | 1364.79 | ||||
Minimum of Months | 8.17 | 20703.59 | 610.64 | 68544.86 | ||
Maximum of Months | 472812.02 | 4007560.36 | 1893.96 | 129553.47 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137602E+11 | 0.88 | 9348.44 | 01-JAN-00:20 | 1.59 |
February | 0.122669E+11 | 0.86 | 9348.44 | 01-FEB-06:01 | 1.60 |
March | 0.146943E+11 | 0.93 | 9348.44 | 01-MAR-05:03 | 1.59 |
April | 0.136637E+11 | 0.90 | 9348.44 | 01-APR-04:01 | 1.60 |
May | 0.145775E+11 | 0.92 | 9348.44 | 01-MAY-03:01 | 1.59 |
June | 0.145817E+11 | 0.95 | 9348.44 | 01-JUN-03:02 | 1.58 |
July | 0.144606E+11 | 0.91 | 9348.44 | 01-JUL-03:02 | 1.57 |
August | 0.157906E+11 | 1.00 | 9348.44 | 01-AUG-03:02 | 1.58 |
September | 0.147659E+11 | 0.96 | 9348.44 | 01-SEP-03:05 | 1.58 |
October | 0.144536E+11 | 0.92 | 9348.44 | 02-OCT-02:30 | 1.58 |
November | 0.138296E+11 | 0.91 | 9348.44 | 01-NOV-03:10 | 1.60 |
December | 0.135459E+11 | 0.86 | 9348.44 | 01-DEC-05:01 | 1.60 |
Annual Sum or Average | 0.170391E+12 | 0.92 | |||
Minimum of Months | 0.122669E+11 | 0.86 | 9348.44 | 1.57 | |
Maximum of Months | 0.157906E+11 | 1.00 | 9348.44 | 1.60 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.342259E+10 | 0.35 | 13659.97 | 20-JAN-06:01 | 1.58 |
February | 0.384268E+10 | 0.38 | 11354.89 | 23-FEB-06:01 | 1.41 |
March | 0.585553E+10 | 0.45 | 12574.61 | 07-MAR-06:01 | 1.50 |
April | 0.762426E+10 | 0.52 | 16407.33 | 24-APR-14:50 | 1.76 |
May | 0.681951E+10 | 0.48 | 15172.80 | 30-MAY-05:03 | 1.67 |
June | 0.110614E+11 | 0.67 | 21678.56 | 21-JUN-05:02 | 2.09 |
July | 0.139214E+11 | 0.77 | 22105.06 | 18-JUL-05:02 | 2.12 |
August | 0.146411E+11 | 0.81 | 22105.06 | 07-AUG-04:02 | 2.12 |
September | 0.776907E+10 | 0.53 | 22105.06 | 05-SEP-05:02 | 2.12 |
October | 0.674243E+10 | 0.46 | 14852.99 | 16-OCT-15:50 | 1.66 |
November | 0.546976E+10 | 0.42 | 13659.97 | 28-NOV-06:01 | 1.58 |
December | 0.459013E+10 | 0.38 | 13659.97 | 16-DEC-06:02 | 1.58 |
Annual Sum or Average | 0.917598E+11 | 0.52 | |||
Minimum of Months | 0.342259E+10 | 0.35 | 11354.89 | 1.41 | |
Maximum of Months | 0.146411E+11 | 0.81 | 22105.06 | 2.12 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.357792E+11 | 0.41 | 54493.27 | 12-JAN-06:01 | 0.96 |
February | 0.312686E+11 | 0.38 | 54562.42 | 28-FEB-16:00 | 0.96 |
March | 0.369145E+11 | 0.39 | 99969.51 | 30-MAR-05:02 | 1.37 |
April | 0.394796E+11 | 0.38 | 145189.44 | 28-APR-05:01 | 1.72 |
May | 0.486637E+11 | 0.42 | 126253.87 | 19-MAY-15:30 | 1.56 |
June | 0.806270E+11 | 0.56 | 205262.70 | 21-JUN-05:02 | 2.12 |
July | 0.979840E+11 | 0.61 | 205262.70 | 17-JUL-05:03 | 2.12 |
August | 0.939657E+11 | 0.60 | 205262.70 | 07-AUG-05:03 | 2.14 |
September | 0.577957E+11 | 0.47 | 205262.70 | 05-SEP-05:02 | 2.13 |
October | 0.409948E+11 | 0.38 | 103373.40 | 04-OCT-05:02 | 1.39 |
November | 0.328467E+11 | 0.36 | 114288.38 | 10-NOV-06:02 | 1.48 |
December | 0.317400E+11 | 0.36 | 54493.27 | 26-DEC-06:02 | 0.96 |
Annual Sum or Average | 0.628060E+12 | 0.44 | |||
Minimum of Months | 0.312686E+11 | 0.36 | 54493.27 | 0.96 | |
Maximum of Months | 0.979840E+11 | 0.61 | 205262.70 | 2.14 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.468141E+10 | 0.48 | 5181.20 | 02-JAN-04:11 | 0.88 |
February | 0.351397E+10 | 0.41 | 5181.20 | 01-FEB-05:01 | 0.88 |
March | 0.380344E+10 | 0.40 | 5181.20 | 03-MAR-06:01 | 0.88 |
April | 0.344378E+10 | 0.36 | 9198.49 | 25-APR-16:00 | 1.21 |
May | 0.437245E+10 | 0.39 | 14359.45 | 19-MAY-15:30 | 1.58 |
June | 0.769842E+10 | 0.52 | 22802.64 | 21-JUN-05:02 | 2.11 |
July | 0.987064E+10 | 0.57 | 22802.64 | 17-JUL-05:03 | 2.11 |
August | 0.885417E+10 | 0.54 | 22802.64 | 07-AUG-03:02 | 2.12 |
September | 0.496734E+10 | 0.42 | 17192.38 | 05-SEP-05:02 | 1.77 |
October | 0.341028E+10 | 0.35 | 7770.20 | 18-OCT-16:00 | 1.10 |
November | 0.351651E+10 | 0.39 | 5181.20 | 06-NOV-06:01 | 0.87 |
December | 0.426731E+10 | 0.46 | 5181.20 | 01-DEC-05:01 | 0.88 |
Annual Sum or Average | 0.623997E+11 | 0.44 | |||
Minimum of Months | 0.341028E+10 | 0.35 | 5181.20 | 0.87 | |
Maximum of Months | 0.987064E+10 | 0.57 | 22802.64 | 2.12 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.165244E+10 | 1.05 | 616.95 | 01-JAN-00:05 | 1.05 |
February | 0.149253E+10 | 1.05 | 616.95 | 01-FEB-00:05 | 1.05 |
March | 0.165244E+10 | 1.05 | 616.95 | 01-MAR-00:10 | 1.05 |
April | 0.159914E+10 | 1.05 | 616.95 | 01-APR-00:10 | 1.05 |
May | 0.165244E+10 | 1.05 | 616.95 | 01-MAY-00:10 | 1.05 |
June | 0.159914E+10 | 1.05 | 616.95 | 01-JUN-00:10 | 1.05 |
July | 0.165244E+10 | 1.05 | 616.95 | 01-JUL-00:10 | 1.05 |
August | 0.165244E+10 | 1.05 | 616.95 | 01-AUG-00:03 | 1.05 |
September | 0.159914E+10 | 1.05 | 616.95 | 01-SEP-00:03 | 1.05 |
October | 0.165244E+10 | 1.05 | 616.95 | 01-OCT-00:10 | 1.05 |
November | 0.159914E+10 | 1.05 | 616.95 | 01-NOV-00:10 | 1.05 |
December | 0.165244E+10 | 1.05 | 616.95 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.194562E+11 | 1.05 | |||
Minimum of Months | 0.149253E+10 | 1.05 | 616.95 | 1.05 | |
Maximum of Months | 0.165244E+10 | 1.05 | 616.95 | 1.05 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158144E+11 | 1.05 | 5904.41 | 01-JAN-00:10 | 1.05 |
February | 0.142840E+11 | 1.05 | 5904.41 | 01-FEB-00:30 | 1.05 |
March | 0.158144E+11 | 1.05 | 5904.41 | 01-MAR-00:10 | 1.05 |
April | 0.153042E+11 | 1.05 | 5904.41 | 01-APR-00:10 | 1.05 |
May | 0.158144E+11 | 1.05 | 5904.41 | 01-MAY-00:10 | 1.05 |
June | 0.153042E+11 | 1.05 | 5904.41 | 01-JUN-00:10 | 1.05 |
July | 0.158144E+11 | 1.05 | 5904.41 | 01-JUL-00:10 | 1.05 |
August | 0.158144E+11 | 1.05 | 5904.41 | 01-AUG-00:03 | 1.05 |
September | 0.153042E+11 | 1.05 | 5904.41 | 01-SEP-00:03 | 1.05 |
October | 0.158144E+11 | 1.05 | 5904.41 | 01-OCT-00:10 | 1.05 |
November | 0.153042E+11 | 1.05 | 5904.41 | 01-NOV-00:10 | 1.05 |
December | 0.158144E+11 | 1.05 | 5904.41 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.186202E+12 | 1.05 | |||
Minimum of Months | 0.142840E+11 | 1.05 | 5904.41 | 1.05 | |
Maximum of Months | 0.158144E+11 | 1.05 | 5904.41 | 1.05 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.161130E+10 | 1.05 | 601.59 | 01-JAN-00:05 | 1.04 |
February | 0.145536E+10 | 1.05 | 601.59 | 01-FEB-00:05 | 1.05 |
March | 0.161130E+10 | 1.05 | 601.59 | 01-MAR-00:10 | 1.05 |
April | 0.155932E+10 | 1.05 | 601.59 | 01-APR-00:10 | 1.05 |
May | 0.161130E+10 | 1.05 | 601.59 | 01-MAY-00:10 | 1.05 |
June | 0.155932E+10 | 1.05 | 601.59 | 01-JUN-00:10 | 1.05 |
July | 0.161130E+10 | 1.05 | 601.59 | 01-JUL-00:10 | 1.05 |
August | 0.161130E+10 | 1.05 | 601.59 | 01-AUG-00:03 | 1.05 |
September | 0.155932E+10 | 1.05 | 601.59 | 01-SEP-00:03 | 1.05 |
October | 0.161130E+10 | 1.05 | 601.59 | 01-OCT-00:10 | 1.05 |
November | 0.155932E+10 | 1.05 | 601.59 | 01-NOV-00:10 | 1.05 |
December | 0.161130E+10 | 1.05 | 601.59 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.189717E+11 | 1.05 | |||
Minimum of Months | 0.145536E+10 | 1.05 | 601.59 | 1.04 | |
Maximum of Months | 0.161130E+10 | 1.05 | 601.59 | 1.05 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.164647E+09 | 0.149664E+09 | 1262.37 | 09-JAN-07:03 | 1147.49 | 1147.49 | 47.19 | 12.74 |
February | 55397449.38 | 50356281.48 | 919.46 | 06-FEB-06:01 | 835.79 | 835.79 | 46.65 | 11.09 |
March | 22480849.84 | 20435092.50 | 865.24 | 06-MAR-06:01 | 786.51 | 786.51 | 47.63 | 10.79 |
April | 3202375.25 | 2910959.11 | 276.99 | 01-APR-05:01 | 251.78 | 251.78 | 33.06 | 6.40 |
May | 2172919.08 | 1975183.44 | 279.26 | 09-MAY-05:01 | 253.85 | 253.85 | 36.20 | 6.42 |
June | 44364.22 | 40327.07 | 4.43 | 16-JUN-07:00 | 4.02 | 4.02 | 24.69 | 0.52 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 23.56 | 0.00 |
August | 2699.51 | 2453.86 | 4.24 | 18-AUG-05:02 | 3.86 | 3.86 | 23.91 | 0.51 |
September | 368142.46 | 334641.50 | 34.81 | 19-SEP-05:03 | 31.64 | 31.64 | 29.33 | 2.12 |
October | 2458354.60 | 2234644.33 | 261.71 | 11-OCT-05:01 | 237.90 | 237.90 | 33.89 | 6.23 |
November | 16534995.42 | 15030310.84 | 851.72 | 27-NOV-06:02 | 774.22 | 774.22 | 48.10 | 10.71 |
December | 69705848.32 | 63362616.12 | 864.48 | 29-DEC-06:01 | 785.81 | 785.81 | 46.95 | 10.79 |
Annual Sum or Average | 0.337015E+09 | 0.306347E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.56 | 0.00 | |
Maximum of Months | 0.164647E+09 | 0.149664E+09 | 1262.37 | 1147.49 | 1147.49 | 48.10 | 12.74 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 168.12 | 152.82 | 2.17 | 24-JAN-05:01 | 1.97 | 1.97 | 6.71 | 0.47 |
February | 1642593.85 | 1493117.81 | 176.92 | 27-FEB-13:40 | 160.82 | 160.82 | 8.96 | 10.70 |
March | 11059.94 | 10053.49 | 2.71 | 14-MAR-13:30 | 2.46 | 2.46 | 8.62 | 0.57 |
April | 14971718.35 | 13609291.98 | 288.08 | 06-APR-16:00 | 261.86 | 261.86 | 8.00 | 13.82 |
May | 76793672.05 | 69805447.90 | 1974.92 | 19-MAY-12:30 | 1795.20 | 1795.20 | 7.02 | 34.49 |
June | 0.411106E+09 | 0.373696E+09 | 4039.46 | 21-JUN-05:02 | 3671.87 | 3671.87 | 8.51 | 46.98 |
July | 0.887246E+09 | 0.806507E+09 | 5911.61 | 19-JUL-05:03 | 5373.65 | 5373.65 | 8.06 | 55.09 |
August | 0.779731E+09 | 0.708776E+09 | 4574.07 | 07-AUG-13:00 | 4157.83 | 4157.83 | 6.72 | 49.51 |
September | 0.290396E+09 | 0.263970E+09 | 5096.17 | 05-SEP-12:40 | 4632.42 | 4632.42 | 7.49 | 51.79 |
October | 33530280.67 | 30479025.13 | 573.63 | 18-OCT-15:10 | 521.43 | 521.43 | 7.45 | 19.48 |
November | 884906.32 | 804379.84 | 43.36 | 03-NOV-13:50 | 39.41 | 39.41 | 8.67 | 4.72 |
December | 49.77 | 45.24 | 0.13 | 26-DEC-05:17 | 0.12 | 0.12 | 8.46 | 0.03 |
Annual Sum or Average | 0.249631E+10 | 0.226915E+10 | ||||||
Minimum of Months | 49.77 | 45.24 | 0.13 | 0.12 | 0.12 | 6.71 | 0.03 | |
Maximum of Months | 0.887246E+09 | 0.806507E+09 | 5911.61 | 5373.65 | 5373.65 | 8.96 | 55.09 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.860581E+09 | 0.782268E+09 | 12041.71 | 01-JAN-11:15 | 10945.91 | 10945.91 | 8.43 | 85.24 |
February | 0.160901E+10 | 0.146259E+10 | 12041.71 | 01-FEB-04:01 | 10945.91 | 10945.91 | 8.43 | 85.24 |
March | 0.250760E+10 | 0.227941E+10 | 12041.71 | 01-MAR-06:30 | 10945.91 | 10945.91 | 8.43 | 85.24 |
April | 0.496714E+10 | 0.451513E+10 | 12041.71 | 01-APR-04:01 | 10945.91 | 10945.91 | 8.43 | 85.24 |
May | 0.874225E+10 | 0.794670E+10 | 12041.71 | 01-MAY-13:00 | 10945.91 | 10945.91 | 8.43 | 85.24 |
June | 0.164262E+11 | 0.149314E+11 | 12041.71 | 01-JUN-04:03 | 10945.91 | 10945.91 | 8.61 | 85.24 |
July | 0.226527E+11 | 0.205913E+11 | 12041.71 | 01-JUL-00:10 | 10945.91 | 10945.91 | 8.01 | 85.24 |
August | 0.213414E+11 | 0.193993E+11 | 12041.71 | 01-AUG-00:03 | 10945.91 | 10945.91 | 7.94 | 85.24 |
September | 0.127936E+11 | 0.116293E+11 | 12041.71 | 01-SEP-00:03 | 10945.91 | 10945.91 | 8.06 | 85.24 |
October | 0.633100E+10 | 0.575488E+10 | 12041.71 | 02-OCT-05:05 | 10945.91 | 10945.91 | 8.62 | 85.24 |
November | 0.301747E+10 | 0.274288E+10 | 12041.71 | 01-NOV-04:01 | 10945.91 | 10945.91 | 8.64 | 85.24 |
December | 0.141205E+10 | 0.128355E+10 | 12041.71 | 06-DEC-16:00 | 10945.91 | 10945.91 | 8.43 | 85.24 |
Annual Sum or Average | 0.102661E+12 | 0.933188E+11 | ||||||
Minimum of Months | 0.860581E+09 | 0.782268E+09 | 12041.71 | 10945.91 | 10945.91 | 7.94 | 85.24 | |
Maximum of Months | 0.226527E+11 | 0.205913E+11 | 12041.71 | 10945.91 | 10945.91 | 8.64 | 85.24 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.188730E+10 | 0.171556E+10 | 726.89 | 01-JAN-00:05 | 660.74 | 660.74 | 18.86 | 3.07 |
February | 0.175849E+10 | 0.159847E+10 | 726.89 | 01-FEB-00:05 | 660.74 | 660.74 | 20.56 | 3.07 |
March | 0.194690E+10 | 0.176973E+10 | 726.89 | 01-MAR-00:10 | 660.74 | 660.74 | 24.82 | 3.07 |
April | 0.188410E+10 | 0.171264E+10 | 726.89 | 01-APR-00:10 | 660.74 | 660.74 | 27.11 | 3.07 |
May | 0.194690E+10 | 0.176973E+10 | 726.89 | 01-MAY-00:10 | 660.74 | 660.74 | 19.83 | 3.07 |
June | 0.188410E+10 | 0.171264E+10 | 726.89 | 01-JUN-00:10 | 660.74 | 660.74 | 23.70 | 3.07 |
July | 0.194690E+10 | 0.176973E+10 | 726.89 | 01-JUL-00:10 | 660.74 | 660.74 | 29.35 | 3.07 |
August | 0.194690E+10 | 0.176973E+10 | 726.89 | 01-AUG-00:03 | 660.74 | 660.74 | 31.83 | 3.07 |
September | 0.188410E+10 | 0.171264E+10 | 726.89 | 01-SEP-00:03 | 660.74 | 660.74 | 22.14 | 3.07 |
October | 0.194690E+10 | 0.176973E+10 | 726.89 | 01-OCT-00:10 | 660.74 | 660.74 | 23.18 | 3.07 |
November | 0.188410E+10 | 0.171264E+10 | 726.89 | 01-NOV-00:10 | 660.74 | 660.74 | 24.88 | 3.07 |
December | 0.194690E+10 | 0.176973E+10 | 726.89 | 01-DEC-00:10 | 660.74 | 660.74 | 26.34 | 3.07 |
Annual Sum or Average | 0.228636E+11 | 0.207830E+11 | ||||||
Minimum of Months | 0.175849E+10 | 0.159847E+10 | 726.89 | 660.74 | 660.74 | 18.86 | 3.07 | |
Maximum of Months | 0.194690E+10 | 0.176973E+10 | 726.89 | 660.74 | 660.74 | 31.83 | 3.07 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:03 | 1.79 | 1.79 | 55.05 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:01 | 1.79 | 1.79 | 55.73 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:03 | 1.79 | 1.79 | 55.99 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:01 | 1.79 | 1.79 | 56.34 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:01 | 1.79 | 1.79 | 56.15 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:03 | 1.79 | 1.79 | 56.48 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:02 | 1.79 | 1.79 | 56.75 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:03 | 1.79 | 1.79 | 56.69 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 56.56 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 56.24 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:02 | 1.79 | 1.79 | 55.46 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:01 | 1.79 | 1.79 | 56.06 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.05 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 56.75 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.107383E+10 | 0.976108E+09 | 15027.80 | 26-JAN-06:50 | 13660.27 | 13660.27 | 21.20 | 50.56 |
February | 0.200800E+10 | 0.182527E+10 | 15046.86 | 27-FEB-13:40 | 13677.59 | 13677.59 | 22.96 | 50.56 |
March | 0.312896E+10 | 0.284423E+10 | 15027.89 | 14-MAR-13:30 | 13660.35 | 13660.35 | 21.21 | 50.56 |
April | 0.627322E+10 | 0.570236E+10 | 30090.42 | 07-APR-13:40 | 27352.19 | 27352.19 | 22.80 | 101.12 |
May | 0.113614E+11 | 0.103275E+11 | 30155.88 | 19-MAY-15:30 | 27411.69 | 27411.69 | 25.71 | 101.12 |
June | 0.243631E+11 | 0.221460E+11 | 30169.20 | 20-JUN-15:40 | 27423.80 | 27423.80 | 26.24 | 101.12 |
July | 0.357814E+11 | 0.325253E+11 | 30174.28 | 19-JUL-12:20 | 27428.42 | 27428.42 | 26.44 | 101.12 |
August | 0.329337E+11 | 0.299368E+11 | 30164.79 | 09-AUG-10:50 | 27419.79 | 27419.79 | 26.06 | 101.12 |
September | 0.180506E+11 | 0.164080E+11 | 30234.36 | 07-SEP-14:40 | 27483.03 | 27483.03 | 28.94 | 101.12 |
October | 0.813977E+10 | 0.739905E+10 | 30146.90 | 18-OCT-14:30 | 27403.54 | 27403.54 | 25.36 | 101.12 |
November | 0.376539E+10 | 0.342274E+10 | 15035.03 | 17-NOV-17:00 | 13666.84 | 13666.84 | 21.87 | 50.56 |
December | 0.176192E+10 | 0.160158E+10 | 15027.76 | 26-DEC-03:45 | 13660.24 | 13660.24 | 21.20 | 50.56 |
Annual Sum or Average | 0.148641E+12 | 0.135115E+12 | ||||||
Minimum of Months | 0.107383E+10 | 0.976108E+09 | 15027.76 | 13660.24 | 13660.24 | 21.20 | 50.56 | |
Maximum of Months | 0.357814E+11 | 0.325253E+11 | 30234.36 | 27483.03 | 27483.03 | 28.94 | 101.12 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 39.59 | 39.59 | 323995.45 | 1937802.61 | 09-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 31.01 | 31.01 | 190987.31 | 1754014.61 | 07-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 26.87 | 26.87 | 101075.15 | 1827513.10 | 07-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 28.20 | 28.20 | 28161.82 | 1259582.69 | 01-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 24.12 | 24.12 | 16934.25 | 1213159.16 | 09-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 23.81 | 23.81 | 551.38 | 122299.68 | 16-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 23.56 | 23.56 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.56 | 23.56 | 35.32 | 118193.97 | 18-AUG-05:02 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.13 | 24.13 | 4157.39 | 455337.18 | 19-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.23 | 22.23 | 20131.52 | 1230036.50 | 11-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 28.24 | 28.24 | 84316.57 | 1527465.53 | 27-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 29.93 | 29.93 | 208157.52 | 1727477.61 | 27-DEC-06:01 |
Annual Sum or Average | 0.00 | 81214.97 | ||||||
Minimum of Months | 0.00 | 0.00 | 22.23 | 22.23 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 39.59 | 39.59 | 323995.45 | 1937802.61 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 580.02 | 21745.72 | 26-JAN-04:30 | 8.43 | 8.40 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 5026.74 | 674825.38 | 27-FEB-13:40 | 9.91 | 8.96 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 1752.25 | 59999.74 | 14-MAR-13:30 | 8.54 | 8.45 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 39001.39 | 1091503.14 | 07-APR-14:20 | 10.35 | 8.69 | 0.00 | 0.00 | 01-APR-00:10 |
May | 112819.58 | 1173972.67 | 19-MAY-12:20 | 10.30 | 7.01 | 160.67 | 270926.22 | 22-MAY-04:03 |
June | 310226.17 | 1356975.59 | 29-JUN-14:50 | 10.50 | 6.70 | 60.57 | 131651.34 | 11-JUN-19:42 |
July | 477479.48 | 1596911.87 | 17-JUL-15:30 | 11.17 | 6.70 | 36.67 | 89074.53 | 15-JUL-02:32 |
August | 412641.48 | 1488823.35 | 07-AUG-15:40 | 10.87 | 6.70 | 33.47 | 93554.69 | 12-AUG-02:42 |
September | 226618.09 | 1978323.13 | 07-SEP-15:00 | 12.59 | 7.05 | 33.54 | 137110.42 | 24-SEP-08:53 |
October | 61399.25 | 1070290.63 | 16-OCT-12:30 | 10.54 | 8.91 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5165.97 | 251607.76 | 17-NOV-17:00 | 8.83 | 8.48 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 952.21 | 22427.74 | 26-DEC-05:17 | 8.43 | 8.40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 138814.93 | 27.34 | ||||||
Minimum of Months | 580.02 | 21745.72 | 8.43 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 477479.48 | 1978323.13 | 12.59 | 8.96 | 160.67 | 270926.22 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 30.14 | 24-JAN-05:01 | 6.72 | 8.40 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 2413.10 | 429530.62 | 27-FEB-13:40 | 16.30 | 8.97 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 37.43 | 23837.46 | 14-MAR-13:30 | 16.70 | 8.45 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 22844.25 | 783344.84 | 06-APR-16:00 | 20.26 | 8.44 | 0.00 | 0.00 | 01-APR-00:10 |
May | 72242.83 | 1210559.25 | 19-MAY-12:20 | 15.97 | 7.14 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 244755.94 | 1347821.38 | 29-JUN-14:50 | 22.43 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 391479.68 | 2057556.34 | 19-JUL-05:03 | 15.63 | 7.82 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 338752.20 | 1480660.59 | 07-AUG-15:40 | 14.38 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 163109.64 | 2036438.66 | 07-SEP-15:00 | 18.82 | 7.11 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 38988.06 | 1048797.13 | 18-OCT-15:10 | 19.58 | 8.18 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 1913.01 | 168927.77 | 01-NOV-04:01 | 17.03 | 8.45 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.15 | 1047.06 | 26-DEC-05:17 | 14.55 | 8.40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 107213.05 | 0.00 | ||||||
Minimum of Months | 0.00 | 30.14 | 6.72 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 391479.68 | 2057556.34 | 22.43 | 8.97 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4497.21 | 23234.04 | 13-JAN-16:30 | 20.51 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 35054.04 | 74981.01 | 27-FEB-16:00 | 25.34 | 20.05 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 67333.26 | 94056.51 | 31-MAR-23:40 | 27.11 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 102913.18 | 193500.42 | 07-APR-14:00 | 36.25 | 25.66 | 0.00 | 0.00 | 01-APR-00:10 |
May | 31607.60 | 166227.53 | 20-MAY-16:00 | 33.76 | 30.68 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 83699.39 | 234207.58 | 29-JUN-15:00 | 39.94 | 33.62 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 143583.88 | 332760.47 | 17-JUL-16:00 | 48.77 | 39.35 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 160833.65 | 344546.49 | 06-AUG-16:00 | 49.82 | 38.25 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 46396.23 | 224983.15 | 02-SEP-17:00 | 39.11 | 35.26 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 50442.00 | 147181.78 | 18-OCT-15:00 | 32.01 | 26.27 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 67606.64 | 87392.75 | 17-NOV-17:00 | 26.50 | 18.87 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 86288.07 | 106613.13 | 06-DEC-16:10 | 28.28 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 73649.68 | 0.00 | ||||||
Minimum of Months | 4497.21 | 23234.04 | 20.51 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 160833.65 | 344546.49 | 49.82 | 39.35 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.21 | 56.21 | 17332.17 | 58855.85 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 56.21 | 56.21 | 17710.16 | 59175.16 | 23-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.69 | 56.69 | 18546.02 | 59075.44 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.79 | 56.79 | 16883.46 | 57456.21 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.82 | 56.82 | 16524.89 | 54983.50 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.93 | 56.93 | 15933.17 | 51689.52 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.27 | 57.27 | 14100.23 | 48654.35 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 56.97 | 56.97 | 14986.26 | 46970.17 | 01-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 57.11 | 57.11 | 14316.18 | 48065.18 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.24 | 57.24 | 14900.48 | 50877.00 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.03 | 56.03 | 15950.55 | 54068.61 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.53 | 56.53 | 16275.18 | 56870.36 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 16112.35 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.03 | 56.03 | 14100.23 | 46970.17 | ||
Maximum of Months | 0.00 | 0.00 | 57.27 | 57.27 | 18546.02 | 59175.16 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 8.17 | 21494.04 | 26-JAN-06:50 | 21.20 | 20.26 | 610.64 | 106136.90 | 18-JAN-06:30 |
February | 2065.93 | 393963.00 | 27-FEB-13:40 | 22.96 | 21.10 | 999.66 | 125121.23 | 08-FEB-06:50 |
March | 124.86 | 23282.03 | 14-MAR-13:30 | 21.21 | 20.54 | 1888.77 | 129553.47 | 04-MAR-05:01 |
April | 21771.62 | 747203.33 | 07-APR-13:00 | 24.64 | 21.10 | 1773.85 | 106812.09 | 19-APR-14:50 |
May | 76371.49 | 1948357.10 | 19-MAY-15:30 | 25.71 | 21.10 | 1477.11 | 125563.72 | 08-MAY-05:50 |
June | 283567.14 | 2171062.01 | 20-JUN-15:40 | 26.24 | 22.79 | 1205.35 | 83799.92 | 16-JUN-14:50 |
July | 472812.02 | 2256031.81 | 19-JUL-12:20 | 26.44 | 22.81 | 848.13 | 68544.86 | 05-JUL-05:30 |
August | 402430.65 | 2097326.83 | 09-AUG-10:50 | 26.06 | 21.60 | 1457.73 | 74957.82 | 19-AUG-05:50 |
September | 188132.61 | 4007560.36 | 07-SEP-15:00 | 30.58 | 25.26 | 1310.41 | 106087.41 | 18-SEP-13:20 |
October | 37961.18 | 1798294.45 | 18-OCT-14:30 | 25.36 | 21.10 | 1721.73 | 108532.29 | 02-OCT-05:30 |
November | 1288.14 | 162868.87 | 17-NOV-17:00 | 21.87 | 21.10 | 1893.96 | 122536.86 | 13-NOV-05:01 |
December | 28.98 | 20703.59 | 26-DEC-03:45 | 21.20 | 20.25 | 1178.21 | 126688.07 | 07-DEC-06:02 |
Annual Sum or Average | 124883.53 | 1364.79 | ||||||
Minimum of Months | 8.17 | 20703.59 | 21.20 | 20.25 | 610.64 | 68544.86 | ||
Maximum of Months | 472812.02 | 4007560.36 | 30.58 | 25.26 | 1893.96 | 129553.47 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.467487E+11 | 0.00 | 0.00 | 0.342259E+10 | 0.00 | 0.00 |
February | 0.229894E+11 | 0.00 | 0.547329E+09 | 0.384268E+10 | 0.00 | 0.00 |
March | 0.109500E+11 | 0.00 | 27485668.80 | 0.585553E+10 | 0.00 | 0.00 |
April | 0.201742E+10 | 0.00 | 0.572886E+10 | 0.762426E+10 | 0.00 | 0.00 |
May | 0.128206E+10 | 0.00 | 0.157044E+11 | 0.681951E+10 | 0.00 | 0.00 |
June | 22729212.35 | 0.00 | 0.526794E+11 | 0.110614E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.911420E+11 | 0.139214E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.820902E+11 | 0.146411E+11 | 0.00 | 0.00 |
September | 0.240087E+09 | 0.00 | 0.339074E+11 | 0.776907E+10 | 0.00 | 0.00 |
October | 0.149956E+10 | 0.00 | 0.909578E+10 | 0.674243E+10 | 0.00 | 0.00 |
November | 0.753701E+10 | 0.00 | 0.449206E+09 | 0.546976E+10 | 0.00 | 0.00 |
December | 0.239920E+11 | 0.00 | 441.66 | 0.459013E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.117279E+12 | 0.00 | 0.291372E+12 | 0.917598E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.342259E+10 | 0.00 | 0.00 |
Maximum of Months | 0.467487E+11 | 0.00 | 0.911420E+11 | 0.146411E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.708828E+12 | 0.00 | 44594.84 | 0.357792E+11 | 0.00 | 0.00 |
February | 0.380014E+12 | 0.00 | 0.381850E+10 | 0.312686E+11 | 0.00 | 0.00 |
March | 0.219362E+12 | 0.00 | 34632748.16 | 0.369145E+11 | 0.00 | 0.00 |
April | 0.574916E+11 | 0.00 | 0.382635E+11 | 0.394796E+11 | 0.00 | 0.00 |
May | 0.352207E+11 | 0.00 | 0.131126E+12 | 0.486637E+11 | 0.00 | 0.00 |
June | 0.897155E+09 | 0.00 | 0.438724E+12 | 0.806270E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.741519E+12 | 0.979840E+11 | 0.00 | 0.00 |
August | 1578491.26 | 0.00 | 0.638843E+12 | 0.939657E+11 | 0.00 | 0.00 |
September | 0.755540E+10 | 0.00 | 0.291560E+12 | 0.577957E+11 | 0.00 | 0.00 |
October | 0.408954E+11 | 0.00 | 0.678401E+11 | 0.409948E+11 | 0.00 | 0.00 |
November | 0.174329E+12 | 0.00 | 0.316546E+10 | 0.328467E+11 | 0.00 | 0.00 |
December | 0.454624E+12 | 0.00 | 52811.18 | 0.317400E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.207922E+13 | 0.00 | 0.235489E+13 | 0.628060E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 44594.84 | 0.312686E+11 | 0.00 | 0.00 |
Maximum of Months | 0.708828E+12 | 0.00 | 0.741519E+12 | 0.979840E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.116634E+12 | 0.00 | 142480.92 | 0.468141E+10 | 0.00 | 0.00 |
February | 0.614585E+11 | 0.00 | 0.279553E+09 | 0.351397E+10 | 0.00 | 0.00 |
March | 0.417843E+11 | 0.00 | 1418806.73 | 0.380344E+10 | 0.00 | 0.00 |
April | 0.138932E+11 | 0.00 | 0.342778E+10 | 0.344378E+10 | 0.00 | 0.00 |
May | 0.908643E+10 | 0.00 | 0.135838E+11 | 0.437245E+10 | 0.00 | 0.00 |
June | 0.518550E+09 | 0.00 | 0.485946E+11 | 0.769842E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.829818E+11 | 0.987064E+10 | 0.00 | 0.00 |
August | 90263736.52 | 0.00 | 0.691476E+11 | 0.885417E+10 | 0.00 | 0.00 |
September | 0.304916E+10 | 0.00 | 0.296298E+11 | 0.496734E+10 | 0.00 | 0.00 |
October | 0.117465E+11 | 0.00 | 0.570456E+10 | 0.341028E+10 | 0.00 | 0.00 |
November | 0.377822E+11 | 0.00 | 0.238240E+09 | 0.351651E+10 | 0.00 | 0.00 |
December | 0.817282E+11 | 0.00 | 194737.66 | 0.426731E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.377771E+12 | 0.00 | 0.253589E+12 | 0.623997E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 142480.92 | 0.341028E+10 | 0.00 | 0.00 |
Maximum of Months | 0.116634E+12 | 0.00 | 0.829818E+11 | 0.987064E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.182365E+09 | 0.00 | 330121.22 | 0.137602E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.253499E+09 | 0.122669E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 27403.46 | 0.146943E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.210276E+10 | 0.136637E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.773591E+10 | 0.145775E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.270330E+11 | 0.145817E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.462436E+11 | 0.144606E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.423222E+11 | 0.157906E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.177612E+11 | 0.147659E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.521742E+10 | 0.144536E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 72775089.87 | 0.138296E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 96326.67 | 0.135459E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.182365E+09 | 0.00 | 0.148743E+12 | 0.170391E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 27403.46 | 0.122669E+11 | 0.00 | 0.00 |
Maximum of Months | 0.182365E+09 | 0.00 | 0.462436E+11 | 0.157906E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.328989E+10 | 0.229400E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.979348E+10 | 0.326353E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.178682E+11 | 0.472482E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.238075E+11 | 0.552180E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.669852E+10 | 0.288945E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.131503E+11 | 0.399855E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.202409E+11 | 0.547573E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.259670E+11 | 0.634299E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.686390E+10 | 0.289287E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.125898E+11 | 0.384401E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.174850E+11 | 0.457407E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.233278E+11 | 0.558890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.181082E+12 | 0.514107E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.328989E+10 | 0.229400E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.259670E+11 | 0.634299E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.690589E+10 | 0.173020E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.681445E+11 | 0.268685E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.147046E+12 | 0.414410E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.213480E+12 | 0.507498E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.539535E+11 | 0.258914E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.121234E+12 | 0.375179E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.191436E+12 | 0.520352E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.245983E+12 | 0.603290E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.578985E+11 | 0.263390E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.104645E+12 | 0.342395E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.143142E+12 | 0.400071E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.187961E+12 | 0.481237E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.154183E+13 | 0.460844E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.690589E+10 | 0.173020E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.245983E+12 | 0.603290E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.126277E+09 | 0.163919E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.484447E+10 | 0.236623E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.125538E+11 | 0.382749E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.197962E+11 | 0.487833E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.446157E+10 | 0.245234E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.118525E+11 | 0.374260E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.191167E+11 | 0.524137E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.244460E+11 | 0.605366E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.502118E+10 | 0.253192E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.853457E+10 | 0.313750E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.117832E+11 | 0.362607E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.162424E+11 | 0.444463E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.138779E+12 | 0.439413E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.126277E+09 | 0.163919E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.244460E+11 | 0.605366E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.342259E+10 | 0.00 | 0.467487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.384268E+10 | 0.547329E+09 | 0.229894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.585553E+10 | 27485668.80 | 0.109500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.762426E+10 | 0.572886E+10 | 0.201742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.681951E+10 | 0.157044E+11 | 0.128206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110614E+11 | 0.526794E+11 | 22729212.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139214E+11 | 0.911420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146411E+11 | 0.820902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.776907E+10 | 0.339074E+11 | 0.240087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.674243E+10 | 0.909578E+10 | 0.149956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.546976E+10 | 0.449206E+09 | 0.753701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.459013E+10 | 441.66 | 0.239920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.917598E+11 | 0.291372E+12 | 0.117279E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146411E+11 | 0.911420E+11 | 0.467487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.357792E+11 | 44594.84 | 0.708828E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.312686E+11 | 0.381850E+10 | 0.380014E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.369145E+11 | 34632748.16 | 0.219362E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.394796E+11 | 0.382635E+11 | 0.574916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.486637E+11 | 0.131126E+12 | 0.352207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.806270E+11 | 0.438724E+12 | 0.897155E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.979840E+11 | 0.741519E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.939657E+11 | 0.638843E+12 | 1578491.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.577957E+11 | 0.291560E+12 | 0.755540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.409948E+11 | 0.678401E+11 | 0.408954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328467E+11 | 0.316546E+10 | 0.174329E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.317400E+11 | 52811.18 | 0.454624E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.628060E+12 | 0.235489E+13 | 0.207922E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.312686E+11 | 44594.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.979840E+11 | 0.741519E+12 | 0.708828E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.468141E+10 | 142480.92 | 0.116634E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.351397E+10 | 0.279553E+09 | 0.614585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.380344E+10 | 1418806.73 | 0.417843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.344378E+10 | 0.342778E+10 | 0.138932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.437245E+10 | 0.135838E+11 | 0.908643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.769842E+10 | 0.485946E+11 | 0.518550E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.987064E+10 | 0.829818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.885417E+10 | 0.691476E+11 | 90263736.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.496734E+10 | 0.296298E+11 | 0.304916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.341028E+10 | 0.570456E+10 | 0.117465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.351651E+10 | 0.238240E+09 | 0.377822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.426731E+10 | 194737.66 | 0.817282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.623997E+11 | 0.253589E+12 | 0.377771E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.341028E+10 | 142480.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.987064E+10 | 0.829818E+11 | 0.116634E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137602E+11 | 330121.22 | 0.182365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122669E+11 | 0.253499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146943E+11 | 27403.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136637E+11 | 0.210276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145775E+11 | 0.773591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145817E+11 | 0.270330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144606E+11 | 0.462436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157906E+11 | 0.423222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147659E+11 | 0.177612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144536E+11 | 0.521742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138296E+11 | 72775089.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135459E+11 | 96326.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170391E+12 | 0.148743E+12 | 0.182365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122669E+11 | 27403.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157906E+11 | 0.462436E+11 | 0.182365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.165244E+10 | 0.264833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149253E+10 | 0.802248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165244E+10 | 0.147958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159914E+10 | 0.198848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165244E+10 | 0.546152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159914E+10 | 0.107509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165244E+10 | 0.164176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165244E+10 | 0.212765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159914E+10 | 0.557017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165244E+10 | 0.103982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159914E+10 | 0.145101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165244E+10 | 0.193914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194562E+11 | 0.149128E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149253E+10 | 0.264833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.165244E+10 | 0.212765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158144E+11 | 0.541830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142840E+11 | 0.555600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158144E+11 | 0.121420E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153042E+11 | 0.178035E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158144E+11 | 0.438765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153042E+11 | 0.990206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158144E+11 | 0.155215E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158144E+11 | 0.201468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153042E+11 | 0.468638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158144E+11 | 0.862199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153042E+11 | 0.118439E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158144E+11 | 0.155652E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186202E+12 | 0.126719E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142840E+11 | 0.541830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158144E+11 | 0.201468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.161130E+10 | 98383223.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145536E+10 | 0.393360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161130E+10 | 0.103376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155932E+10 | 0.164772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161130E+10 | 0.362052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155932E+10 | 0.966923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161130E+10 | 0.154866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161130E+10 | 0.200036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155932E+10 | 0.404857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161130E+10 | 0.700836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155932E+10 | 0.971643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161130E+10 | 0.134091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189717E+11 | 0.113809E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145536E+10 | 98383223.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161130E+10 | 0.200036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.342259E+10 | 0.467487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.384268E+10 | 0.229894E+11 | 0.547329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.585553E+10 | 0.109500E+11 | 27485668.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.762426E+10 | 0.201742E+10 | 0.572886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.681951E+10 | 0.128206E+10 | 0.157044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110614E+11 | 22729212.35 | 0.526794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139214E+11 | 0.00 | 0.911420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146411E+11 | 0.00 | 0.820902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.776907E+10 | 0.240087E+09 | 0.339074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.674243E+10 | 0.149956E+10 | 0.909578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.546976E+10 | 0.753701E+10 | 0.449206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.459013E+10 | 0.239920E+11 | 441.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.917598E+11 | 0.117279E+12 | 0.291372E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146411E+11 | 0.467487E+11 | 0.911420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.357792E+11 | 0.708828E+12 | 44594.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.312686E+11 | 0.380014E+12 | 0.381850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.369145E+11 | 0.219362E+12 | 34632748.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.394796E+11 | 0.574916E+11 | 0.382635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.486637E+11 | 0.352207E+11 | 0.131126E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.806270E+11 | 0.897155E+09 | 0.438724E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.979840E+11 | 0.00 | 0.741519E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.939657E+11 | 1578491.26 | 0.638843E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.577957E+11 | 0.755540E+10 | 0.291560E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.409948E+11 | 0.408954E+11 | 0.678401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328467E+11 | 0.174329E+12 | 0.316546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.317400E+11 | 0.454624E+12 | 52811.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.628060E+12 | 0.207922E+13 | 0.235489E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.312686E+11 | 0.00 | 44594.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.979840E+11 | 0.708828E+12 | 0.741519E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.468141E+10 | 0.116634E+12 | 142480.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.351397E+10 | 0.614585E+11 | 0.279553E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.380344E+10 | 0.417843E+11 | 1418806.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.344378E+10 | 0.138932E+11 | 0.342778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.437245E+10 | 0.908643E+10 | 0.135838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.769842E+10 | 0.518550E+09 | 0.485946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.987064E+10 | 0.00 | 0.829818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.885417E+10 | 90263736.52 | 0.691476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.496734E+10 | 0.304916E+10 | 0.296298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.341028E+10 | 0.117465E+11 | 0.570456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.351651E+10 | 0.377822E+11 | 0.238240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.426731E+10 | 0.817282E+11 | 194737.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.623997E+11 | 0.377771E+12 | 0.253589E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.341028E+10 | 0.00 | 142480.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.987064E+10 | 0.116634E+12 | 0.829818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137602E+11 | 0.182365E+09 | 330121.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122669E+11 | 0.00 | 0.253499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146943E+11 | 0.00 | 27403.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136637E+11 | 0.00 | 0.210276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145775E+11 | 0.00 | 0.773591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145817E+11 | 0.00 | 0.270330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144606E+11 | 0.00 | 0.462436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157906E+11 | 0.00 | 0.423222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147659E+11 | 0.00 | 0.177612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144536E+11 | 0.00 | 0.521742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138296E+11 | 0.00 | 72775089.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135459E+11 | 0.00 | 96326.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170391E+12 | 0.182365E+09 | 0.148743E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122669E+11 | 0.00 | 27403.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157906E+11 | 0.182365E+09 | 0.462436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.165244E+10 | 0.00 | 0.328989E+10 | 0.00 | 0.641557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149253E+10 | 0.00 | 0.979348E+10 | 0.00 | 0.177100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165244E+10 | 0.00 | 0.178682E+11 | 0.00 | 0.307238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159914E+10 | 0.00 | 0.238075E+11 | 0.00 | 0.392266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165244E+10 | 0.00 | 0.669852E+10 | 0.00 | 0.123700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159914E+10 | 0.00 | 0.131503E+11 | 0.00 | 0.239941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165244E+10 | 0.00 | 0.202409E+11 | 0.00 | 0.382328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.165244E+10 | 0.00 | 0.259670E+11 | 0.00 | 0.469055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159914E+10 | 0.00 | 0.686390E+10 | 0.00 | 0.129373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165244E+10 | 0.00 | 0.125898E+11 | 0.00 | 0.219157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159914E+10 | 0.00 | 0.174850E+11 | 0.00 | 0.297493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165244E+10 | 0.00 | 0.233278E+11 | 0.00 | 0.393646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194562E+11 | 0.00 | 0.181082E+12 | 0.00 | 0.319545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149253E+10 | 0.00 | 0.328989E+10 | 0.00 | 0.641557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.165244E+10 | 0.00 | 0.259670E+11 | 0.00 | 0.469055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.158144E+11 | 0.00 | 0.690589E+10 | 0.00 | 0.148760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142840E+11 | 0.00 | 0.681445E+11 | 0.00 | 0.125845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158144E+11 | 0.00 | 0.147046E+12 | 0.00 | 0.256267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153042E+11 | 0.00 | 0.213480E+12 | 0.00 | 0.354455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158144E+11 | 0.00 | 0.539535E+11 | 0.00 | 0.100770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.153042E+11 | 0.00 | 0.121234E+12 | 0.00 | 0.222137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158144E+11 | 0.00 | 0.191436E+12 | 0.00 | 0.362209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.158144E+11 | 0.00 | 0.245983E+12 | 0.00 | 0.445146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153042E+11 | 0.00 | 0.578985E+11 | 0.00 | 0.110348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158144E+11 | 0.00 | 0.104645E+12 | 0.00 | 0.184252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153042E+11 | 0.00 | 0.143142E+12 | 0.00 | 0.247029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158144E+11 | 0.00 | 0.187961E+12 | 0.00 | 0.323093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186202E+12 | 0.00 | 0.154183E+13 | 0.00 | 0.274643E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142840E+11 | 0.00 | 0.690589E+10 | 0.00 | 0.148760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.158144E+11 | 0.00 | 0.245983E+12 | 0.00 | 0.445146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.161130E+10 | 0.00 | 0.126277E+09 | 0.00 | 27893965.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145536E+10 | 0.00 | 0.484447E+10 | 0.00 | 0.910865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161130E+10 | 0.00 | 0.125538E+11 | 0.00 | 0.221619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155932E+10 | 0.00 | 0.197962E+11 | 0.00 | 0.331901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161130E+10 | 0.00 | 0.446157E+10 | 0.00 | 0.841047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155932E+10 | 0.00 | 0.118525E+11 | 0.00 | 0.218329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161130E+10 | 0.00 | 0.191167E+11 | 0.00 | 0.363007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161130E+10 | 0.00 | 0.244460E+11 | 0.00 | 0.444236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155932E+10 | 0.00 | 0.502118E+10 | 0.00 | 0.972604E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161130E+10 | 0.00 | 0.853457E+10 | 0.00 | 0.152621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155932E+10 | 0.00 | 0.117832E+11 | 0.00 | 0.206675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161130E+10 | 0.00 | 0.162424E+11 | 0.00 | 0.283333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189717E+11 | 0.00 | 0.138779E+12 | 0.00 | 0.249696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145536E+10 | 0.00 | 0.126277E+09 | 0.00 | 27893965.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161130E+10 | 0.00 | 0.244460E+11 | 0.00 | 0.444236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.272489E+11 | 0.00 | 0.00 | 45765037.12 | 0.00 | 0.00 | 0.326602E+11 | 0.00 | 0.36 |
February | 0.139373E+11 | 0.00 | 0.00 | 59417049.00 | 0.00 | 0.00 | 0.392609E+11 | 0.00 | 0.46 |
March | 0.299867E+10 | 0.00 | 0.00 | 97268567.96 | 0.00 | 0.00 | 0.634362E+11 | 0.00 | 0.58 |
April | 0.842838E+09 | 0.00 | 0.00 | 93415762.00 | 0.00 | 0.00 | 0.607468E+11 | 0.00 | 0.80 |
May | 0.419755E+09 | 21185263.80 | 0.00 | 96793753.51 | 4393167.14 | 0.00 | 0.590219E+11 | 0.00 | 0.97 |
June | 0.225220E+09 | 0.271119E+09 | 0.00 | 92563593.09 | 1040948.24 | 0.00 | 0.442935E+11 | 0.00 | 1.13 |
July | 0.177492E+09 | 0.963234E+09 | 0.00 | 90447708.85 | 30910672.84 | 0.00 | 0.275086E+11 | 0.00 | 0.96 |
August | 0.192129E+09 | 0.663086E+09 | 0.00 | 0.104003E+09 | 39961937.04 | 0.00 | 0.385345E+11 | 0.00 | 1.15 |
September | 0.376336E+09 | 0.265415E+09 | 0.00 | 0.101935E+09 | 28332978.33 | 0.00 | 0.528985E+11 | 0.00 | 1.12 |
October | 0.638344E+09 | 0.00 | 0.00 | 0.112350E+09 | 0.00 | 0.00 | 0.660533E+11 | 0.00 | 0.94 |
November | 0.117527E+10 | 0.00 | 0.00 | 0.107189E+09 | 0.00 | 0.00 | 0.657910E+11 | 0.00 | 0.70 |
December | 0.742860E+10 | 0.00 | 0.00 | 89866814.12 | 0.00 | 0.00 | 0.570358E+11 | 0.00 | 0.46 |
Annual Sum or Average | 0.556609E+11 | 0.218404E+10 | 0.00 | 0.109101E+10 | 0.104640E+09 | 0.00 | 0.607241E+12 | 0.00 | 0.80 |
Minimum of Months | 0.177492E+09 | 0.00 | 0.00 | 45765037.12 | 0.00 | 0.00 | 0.275086E+11 | 0.00 | 0.36 |
Maximum of Months | 0.272489E+11 | 0.963234E+09 | 0.00 | 0.112350E+09 | 39961937.04 | 0.00 | 0.660533E+11 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.280394E+11 | 0.00 | 0.00 | 25230442.29 | 0.00 | 0.00 | 0.265841E+11 | 0.00 | 0.31 |
February | 0.128350E+11 | 0.00 | 0.00 | 41540188.03 | 0.00 | 0.00 | 0.339350E+11 | 0.00 | 0.39 |
March | 0.622020E+10 | 0.00 | 0.00 | 75455584.14 | 0.00 | 0.00 | 0.509226E+11 | 0.00 | 0.48 |
April | 0.637430E+10 | 0.00 | 0.00 | 78732477.62 | 0.00 | 0.00 | 0.491289E+11 | 0.00 | 0.69 |
May | 0.414827E+10 | 8780307.81 | 0.00 | 71007844.28 | 16283585.13 | 0.00 | 0.416547E+11 | 0.00 | 0.69 |
June | 0.635260E+10 | 0.198408E+09 | 0.00 | 73972365.43 | 15678805.43 | 0.00 | 0.327880E+11 | 0.00 | 0.93 |
July | 0.923714E+10 | 0.527698E+09 | 0.00 | 65181650.53 | 0.122513E+09 | 0.00 | 0.184808E+11 | 0.00 | 0.88 |
August | 0.105869E+11 | 0.364587E+09 | 0.00 | 78426651.60 | 99524605.83 | 0.00 | 0.282195E+11 | 0.00 | 1.04 |
September | 0.433175E+10 | 0.321106E+09 | 0.00 | 70337926.27 | 67000897.02 | 0.00 | 0.352316E+11 | 0.00 | 0.78 |
October | 0.448705E+10 | 0.00 | 0.00 | 78585477.13 | 0.00 | 0.00 | 0.458758E+11 | 0.00 | 0.68 |
November | 0.415530E+10 | 0.00 | 0.00 | 71681338.93 | 0.00 | 0.00 | 0.483972E+11 | 0.00 | 0.52 |
December | 0.701512E+10 | 0.00 | 0.00 | 62578780.16 | 0.00 | 0.00 | 0.500367E+11 | 0.00 | 0.39 |
Annual Sum or Average | 0.103783E+12 | 0.142058E+10 | 0.00 | 0.792731E+09 | 0.321001E+09 | 0.00 | 0.461255E+12 | 0.00 | 0.65 |
Minimum of Months | 0.414827E+10 | 0.00 | 0.00 | 25230442.29 | 0.00 | 0.00 | 0.184808E+11 | 0.00 | 0.31 |
Maximum of Months | 0.280394E+11 | 0.527698E+09 | 0.00 | 78732477.62 | 0.122513E+09 | 0.00 | 0.509226E+11 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.468476E+12 | 0.00 | 0.00 | 349306.32 | 0.00 | 0.112886E+11 | 0.493765E+10 | 0.00 | 0.28 |
February | 0.327725E+12 | 0.00 | 0.00 | 40722773.56 | 0.00 | 0.120624E+10 | 0.500081E+11 | 0.00 | 0.31 |
March | 0.235680E+12 | 0.00 | 0.00 | 0.181101E+09 | 0.00 | 0.180241E+10 | 0.168834E+12 | 0.00 | 0.34 |
April | 0.110625E+12 | 0.00 | 0.00 | 0.315927E+09 | 0.00 | 0.00 | 0.242410E+12 | 0.00 | 0.44 |
May | 0.811567E+11 | 0.132071E+09 | 0.00 | 0.390085E+09 | 0.185940E+09 | 0.00 | 0.264725E+12 | 0.00 | 0.53 |
June | 0.401085E+11 | 0.209847E+10 | 0.00 | 0.554855E+09 | 0.242326E+09 | 0.00 | 0.249068E+12 | 0.00 | 0.71 |
July | 0.344475E+11 | 0.587522E+10 | 0.00 | 0.509661E+09 | 0.100105E+10 | 0.00 | 0.139271E+12 | 0.00 | 0.61 |
August | 0.344851E+11 | 0.397112E+10 | 0.00 | 0.579240E+09 | 0.988043E+09 | 0.00 | 0.206804E+12 | 0.00 | 0.70 |
September | 0.517923E+11 | 0.311629E+10 | 0.00 | 0.459086E+09 | 0.706200E+09 | 0.00 | 0.247260E+12 | 0.00 | 0.60 |
October | 0.103334E+12 | 0.00 | 0.00 | 0.346916E+09 | 0.00 | 0.00 | 0.240135E+12 | 0.00 | 0.47 |
November | 0.207489E+12 | 0.00 | 0.00 | 0.171074E+09 | 0.00 | 0.115282E+09 | 0.142516E+12 | 0.00 | 0.35 |
December | 0.356979E+12 | 0.00 | 0.00 | 30788237.85 | 0.00 | 0.178391E+10 | 0.577036E+11 | 0.00 | 0.28 |
Annual Sum or Average | 0.205230E+13 | 0.151932E+11 | 0.00 | 0.357980E+10 | 0.312356E+10 | 0.161965E+11 | 0.201367E+13 | 0.00 | 0.47 |
Minimum of Months | 0.344475E+11 | 0.00 | 0.00 | 349306.32 | 0.00 | 0.00 | 0.493765E+10 | 0.00 | 0.28 |
Maximum of Months | 0.468476E+12 | 0.587522E+10 | 0.00 | 0.579240E+09 | 0.100105E+10 | 0.112886E+11 | 0.264725E+12 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.269067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143657E+11 | 0.00 | 0.00 | 0.26 |
February | 0.274262E+11 | 0.00 | 0.00 | 105022.85 | 0.00 | 0.549562E+10 | 0.245069E+09 | 0.00 | 0.29 |
March | 0.299030E+11 | 0.00 | 0.00 | 1090589.74 | 0.00 | 0.284083E+10 | 0.195631E+10 | 0.00 | 0.31 |
April | 0.203113E+11 | 0.00 | 0.00 | 9498518.82 | 0.00 | 0.297079E+09 | 0.886558E+10 | 0.00 | 0.39 |
May | 0.151331E+11 | 4039040.93 | 0.00 | 21402457.64 | 10638982.88 | 0.350266E+09 | 0.152619E+11 | 0.00 | 0.50 |
June | 0.599092E+10 | 0.115646E+09 | 0.00 | 49291467.91 | 14820899.15 | 0.00 | 0.211222E+11 | 0.00 | 0.72 |
July | 0.412303E+10 | 0.359114E+09 | 0.00 | 49932550.12 | 70344951.76 | 0.00 | 0.123646E+11 | 0.00 | 0.63 |
August | 0.444904E+10 | 0.227987E+09 | 0.00 | 54045608.31 | 76277937.97 | 0.00 | 0.170325E+11 | 0.00 | 0.68 |
September | 0.104176E+11 | 0.262151E+09 | 0.00 | 27155243.97 | 61018113.11 | 2420490.61 | 0.142026E+11 | 0.00 | 0.55 |
October | 0.197283E+11 | 0.00 | 0.00 | 7481798.51 | 4760373.44 | 0.359156E+09 | 0.667152E+10 | 0.00 | 0.40 |
November | 0.248001E+11 | 0.00 | 0.00 | 418877.01 | 0.00 | 0.258114E+10 | 0.110733E+10 | 0.00 | 0.31 |
December | 0.269409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.893800E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.216130E+12 | 0.968937E+09 | 0.00 | 0.220422E+09 | 0.237861E+09 | 0.352302E+11 | 0.988297E+11 | 0.00 | 0.44 |
Minimum of Months | 0.412303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.299030E+11 | 0.359114E+09 | 0.00 | 54045608.31 | 76277937.97 | 0.143657E+11 | 0.211222E+11 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.274972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353050E+10 | 0.00 | 0.00 | 0.28 |
February | 0.337451E+10 | 0.00 | 0.00 | 251256.92 | 0.00 | 0.123883E+10 | 0.206764E+09 | 0.00 | 0.30 |
March | 0.364421E+10 | 0.00 | 0.00 | 1208008.48 | 0.00 | 0.172560E+09 | 0.123283E+10 | 0.00 | 0.33 |
April | 0.229797E+10 | 0.00 | 0.00 | 3803246.22 | 0.00 | 0.00 | 0.286732E+10 | 0.00 | 0.54 |
May | 0.156498E+10 | 3479010.22 | 0.00 | 5228369.50 | 1097198.10 | 0.00 | 0.321576E+10 | 0.00 | 0.64 |
June | 0.957383E+09 | 37253656.38 | 0.00 | 9740663.11 | 1741499.48 | 0.00 | 0.408533E+10 | 0.00 | 1.05 |
July | 0.119887E+10 | 0.119084E+09 | 0.00 | 9671085.99 | 11343229.14 | 0.00 | 0.251128E+10 | 0.00 | 1.02 |
August | 0.148011E+10 | 82479779.91 | 0.00 | 9550079.19 | 7316481.51 | 0.00 | 0.317149E+10 | 0.00 | 1.09 |
September | 0.139185E+10 | 58068550.78 | 0.00 | 5149333.91 | 5641264.39 | 0.00 | 0.258183E+10 | 0.00 | 0.69 |
October | 0.233311E+10 | 0.00 | 0.00 | 2951525.42 | 0.00 | 0.00 | 0.211138E+10 | 0.00 | 0.50 |
November | 0.342100E+10 | 0.00 | 0.00 | 914603.61 | 0.00 | 60396318.33 | 0.883348E+09 | 0.00 | 0.34 |
December | 0.401100E+10 | 0.00 | 0.00 | 119622.42 | 0.00 | 0.876112E+09 | 0.185951E+09 | 0.00 | 0.26 |
Annual Sum or Average | 0.284247E+11 | 0.300365E+09 | 0.00 | 48587794.79 | 27139672.63 | 0.587840E+10 | 0.230533E+11 | 0.00 | 0.59 |
Minimum of Months | 0.957383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.401100E+10 | 0.119084E+09 | 0.00 | 9740663.11 | 11343229.14 | 0.353050E+10 | 0.408533E+10 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.311428E+10 | 0.00 | 0.00 | 22260.31 | 0.00 | 0.309390E+10 | 31587573.47 | 0.00 | 0.43 |
February | 0.324521E+10 | 0.00 | 0.00 | 919486.24 | 0.00 | 0.115567E+10 | 0.610528E+09 | 0.00 | 0.50 |
March | 0.346831E+10 | 0.00 | 0.00 | 2561602.47 | 0.00 | 0.256851E+09 | 0.182345E+10 | 0.00 | 0.56 |
April | 0.253413E+10 | 0.00 | 0.00 | 4831483.40 | 0.00 | 485948.92 | 0.329001E+10 | 0.00 | 0.92 |
May | 0.153320E+10 | 2644674.57 | 0.00 | 6735940.54 | 1163006.57 | 0.00 | 0.413693E+10 | 0.00 | 1.11 |
June | 0.104043E+10 | 31401236.16 | 0.00 | 11419304.95 | 1831559.63 | 0.00 | 0.442790E+10 | 0.00 | 1.73 |
July | 0.123482E+10 | 90514638.33 | 0.00 | 12326438.98 | 11511574.58 | 0.00 | 0.303874E+10 | 0.00 | 1.77 |
August | 0.169740E+10 | 71363180.38 | 0.00 | 9554948.14 | 7505334.59 | 0.00 | 0.342048E+10 | 0.00 | 1.80 |
September | 0.144968E+10 | 48422935.53 | 0.00 | 6056226.30 | 5155964.69 | 0.00 | 0.301978E+10 | 0.00 | 1.16 |
October | 0.228249E+10 | 0.00 | 0.00 | 3756351.95 | 0.00 | 0.00 | 0.239211E+10 | 0.00 | 0.79 |
November | 0.331940E+10 | 0.00 | 0.00 | 904978.09 | 0.00 | 0.156478E+09 | 0.936999E+09 | 0.00 | 0.52 |
December | 0.376784E+10 | 0.00 | 0.00 | 65926.65 | 0.00 | 0.128739E+10 | 87183407.78 | 0.00 | 0.41 |
Annual Sum or Average | 0.286872E+11 | 0.244347E+09 | 0.00 | 59154948.04 | 27167440.06 | 0.595078E+10 | 0.272157E+11 | 0.00 | 0.98 |
Minimum of Months | 0.104043E+10 | 0.00 | 0.00 | 22260.31 | 0.00 | 0.00 | 31587573.47 | 0.00 | 0.41 |
Maximum of Months | 0.376784E+10 | 90514638.33 | 0.00 | 12326438.98 | 11511574.58 | 0.309390E+10 | 0.442790E+10 | 0.00 | 1.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.353832E+10 | 0.00 | 0.00 | 2072257.09 | 0.00 | 0.323747E+10 | 0.199460E+10 | 0.00 | 0.40 |
February | 0.321117E+10 | 0.00 | 0.00 | 6445358.71 | 0.00 | 0.110689E+10 | 0.408506E+10 | 0.00 | 0.62 |
March | 0.367081E+10 | 0.00 | 0.00 | 8035387.24 | 0.00 | 0.266262E+09 | 0.583875E+10 | 0.00 | 0.70 |
April | 0.293949E+10 | 0.00 | 0.00 | 8337861.49 | 0.00 | 6472949.25 | 0.553576E+10 | 0.00 | 0.96 |
May | 0.219652E+10 | 5498028.79 | 0.00 | 8386341.29 | 1213767.63 | 38303168.61 | 0.480328E+10 | 0.00 | 0.97 |
June | 0.148707E+10 | 55154056.73 | 0.00 | 11772750.70 | 2001218.30 | 0.00 | 0.450023E+10 | 0.00 | 1.29 |
July | 0.158428E+10 | 0.175176E+09 | 0.00 | 12873297.88 | 13811109.18 | 0.00 | 0.286873E+10 | 0.00 | 1.30 |
August | 0.190004E+10 | 0.163496E+09 | 0.00 | 15648771.58 | 6776067.35 | 0.00 | 0.445185E+10 | 0.00 | 1.64 |
September | 0.158659E+10 | 0.160738E+09 | 0.00 | 12667487.86 | 1552255.99 | 0.00 | 0.549371E+10 | 0.00 | 1.36 |
October | 0.214527E+10 | 0.00 | 0.00 | 13323152.97 | 0.00 | 11506409.62 | 0.707673E+10 | 0.00 | 1.13 |
November | 0.301815E+10 | 0.00 | 0.00 | 7187892.91 | 0.00 | 0.251791E+09 | 0.511372E+10 | 0.00 | 0.68 |
December | 0.376400E+10 | 0.00 | 0.00 | 3599119.61 | 0.00 | 0.130464E+10 | 0.285701E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.310417E+11 | 0.560062E+09 | 0.00 | 0.110350E+09 | 25354418.45 | 0.622334E+10 | 0.546194E+11 | 0.00 | 0.96 |
Minimum of Months | 0.148707E+10 | 0.00 | 0.00 | 2072257.09 | 0.00 | 0.00 | 0.199460E+10 | 0.00 | 0.40 |
Maximum of Months | 0.376400E+10 | 0.175176E+09 | 0.00 | 15648771.58 | 13811109.18 | 0.323747E+10 | 0.707673E+10 | 0.00 | 1.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.499367E+10 | 0.00 | 0.00 | 180132.88 | 0.00 | 0.266099E+10 | 0.189695E+09 | 0.00 | 0.54 |
February | 0.443446E+10 | 0.00 | 0.00 | 2300465.13 | 0.00 | 0.224486E+09 | 0.193209E+10 | 0.00 | 0.68 |
March | 0.259039E+10 | 0.00 | 0.00 | 6712910.09 | 0.00 | 8120590.44 | 0.533102E+10 | 0.00 | 0.85 |
April | 0.814211E+09 | 0.00 | 0.00 | 13840837.49 | 0.00 | 0.00 | 0.822504E+10 | 0.00 | 1.54 |
May | 0.137603E+10 | 4613382.47 | 0.00 | 10527464.36 | 1222883.56 | 0.00 | 0.557701E+10 | 0.00 | 1.44 |
June | 0.704843E+09 | 53944438.56 | 0.00 | 15760836.04 | 555924.37 | 0.00 | 0.566131E+10 | 0.00 | 2.10 |
July | 0.889285E+09 | 0.199793E+09 | 0.00 | 18348091.35 | 7864372.15 | 0.00 | 0.399071E+10 | 0.00 | 2.13 |
August | 0.948192E+09 | 0.142347E+09 | 0.00 | 20010041.73 | 1552493.94 | 0.00 | 0.583581E+10 | 0.00 | 2.51 |
September | 0.116664E+10 | 0.105773E+09 | 0.00 | 8209532.51 | 405533.14 | 0.00 | 0.405216E+10 | 0.00 | 1.44 |
October | 0.150908E+10 | 0.00 | 0.00 | 7643158.45 | 0.00 | 0.00 | 0.501715E+10 | 0.00 | 1.17 |
November | 0.243913E+10 | 0.00 | 0.00 | 4994628.54 | 0.00 | 348939.66 | 0.411637E+10 | 0.00 | 0.82 |
December | 0.416001E+10 | 0.00 | 0.00 | 3042602.38 | 0.00 | 11403756.48 | 0.285107E+10 | 0.00 | 0.59 |
Annual Sum or Average | 0.260259E+11 | 0.506471E+09 | 0.00 | 0.111571E+09 | 11601207.16 | 0.290535E+10 | 0.527794E+11 | 0.00 | 1.32 |
Minimum of Months | 0.704843E+09 | 0.00 | 0.00 | 180132.88 | 0.00 | 0.00 | 0.189695E+09 | 0.00 | 0.54 |
Maximum of Months | 0.499367E+10 | 0.199793E+09 | 0.00 | 20010041.73 | 7864372.15 | 0.266099E+10 | 0.822504E+10 | 0.00 | 2.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.480935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689308E+11 | 0.00 | 0.00 | 0.33 |
February | 0.137502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365417E+11 | 0.00 | 0.00 | 0.32 |
March | 0.322743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170679E+11 | 0.00 | 0.00 | 0.32 |
April | 0.310411E+11 | 0.00 | 0.00 | 4641416.44 | 0.00 | 0.269577E+10 | 0.388528E+10 | 0.00 | 0.38 |
May | 0.234827E+11 | 34924343.39 | 0.00 | 23656052.46 | 17346942.35 | 0.132382E+10 | 0.131775E+11 | 0.00 | 0.50 |
June | 0.915493E+10 | 0.419993E+09 | 0.00 | 69450358.78 | 30415765.29 | 0.00 | 0.270980E+11 | 0.00 | 0.79 |
July | 0.554038E+10 | 0.146528E+10 | 0.00 | 72235280.72 | 87763818.48 | 0.00 | 0.173318E+11 | 0.00 | 0.74 |
August | 0.927018E+10 | 0.947263E+09 | 0.00 | 59051910.29 | 73971336.31 | 0.00 | 0.181368E+11 | 0.00 | 0.72 |
September | 0.197068E+11 | 0.519010E+09 | 0.00 | 26055775.83 | 66826130.50 | 0.353173E+09 | 0.111610E+11 | 0.00 | 0.53 |
October | 0.307152E+11 | 0.00 | 0.00 | 3750540.70 | 0.00 | 0.232622E+10 | 0.316061E+10 | 0.00 | 0.39 |
November | 0.241784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177904E+11 | 0.00 | 0.00 | 0.32 |
December | 0.102816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460227E+11 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.214205E+12 | 0.338647E+10 | 0.00 | 0.258841E+09 | 0.276324E+09 | 0.193053E+12 | 0.939510E+11 | 0.00 | 0.47 |
Minimum of Months | 0.480935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.322743E+11 | 0.146528E+10 | 0.00 | 72235280.72 | 87763818.48 | 0.689308E+11 | 0.270980E+11 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.984793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589759E+11 | 0.00 | 0.00 | 0.49 |
February | 0.196163E+11 | 0.00 | 0.00 | 1460148.09 | 0.00 | 0.316847E+11 | 0.102423E+10 | 0.00 | 0.53 |
March | 0.328397E+11 | 0.00 | 0.00 | 9407553.70 | 0.00 | 0.145396E+11 | 0.760580E+10 | 0.00 | 0.56 |
April | 0.255172E+11 | 0.00 | 0.00 | 31074879.92 | 0.00 | 0.179374E+10 | 0.222733E+11 | 0.00 | 0.78 |
May | 0.189339E+11 | 36494856.36 | 0.00 | 50303792.12 | 15456322.67 | 0.137002E+10 | 0.306419E+11 | 0.00 | 1.01 |
June | 0.810870E+10 | 0.410422E+09 | 0.00 | 0.110770E+09 | 29792924.50 | 0.00 | 0.407001E+11 | 0.00 | 1.61 |
July | 0.522247E+10 | 0.129428E+10 | 0.00 | 0.128957E+09 | 89036033.41 | 0.00 | 0.298370E+11 | 0.00 | 1.62 |
August | 0.887928E+10 | 0.102278E+10 | 0.00 | 91630457.00 | 79503676.87 | 0.00 | 0.318481E+11 | 0.00 | 1.56 |
September | 0.179594E+11 | 0.534749E+09 | 0.00 | 45998503.11 | 58453758.36 | 0.244950E+09 | 0.215187E+11 | 0.00 | 1.04 |
October | 0.289946E+11 | 0.00 | 0.00 | 15119467.06 | 0.00 | 0.167387E+10 | 0.105550E+11 | 0.00 | 0.70 |
November | 0.280542E+11 | 0.00 | 0.00 | 957703.54 | 0.00 | 0.164699E+11 | 0.822463E+09 | 0.00 | 0.54 |
December | 0.154858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422044E+11 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.219459E+12 | 0.329873E+10 | 0.00 | 0.485680E+09 | 0.272243E+09 | 0.168957E+12 | 0.196826E+12 | 0.00 | 0.91 |
Minimum of Months | 0.522247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.328397E+11 | 0.129428E+10 | 0.00 | 0.128957E+09 | 89036033.41 | 0.589759E+11 | 0.407001E+11 | 0.00 | 1.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.240519E+11 | 0.00 | 0.00 | 13153576.77 | 0.00 | 0.507787E+11 | 0.141067E+11 | 0.00 | 0.41 |
February | 0.262474E+11 | 0.00 | 0.00 | 56473036.22 | 0.00 | 0.221423E+11 | 0.330328E+11 | 0.00 | 0.62 |
March | 0.349372E+11 | 0.00 | 0.00 | 65597035.40 | 0.00 | 0.117948E+11 | 0.459176E+11 | 0.00 | 0.66 |
April | 0.278611E+11 | 0.00 | 0.00 | 64472096.59 | 0.00 | 0.239839E+10 | 0.407822E+11 | 0.00 | 0.81 |
May | 0.235105E+11 | 78987167.07 | 0.00 | 70323441.24 | 14630555.59 | 0.168024E+10 | 0.383440E+11 | 0.00 | 0.88 |
June | 0.133528E+11 | 0.692172E+09 | 0.00 | 98732438.39 | 23383327.95 | 5551561.92 | 0.355704E+11 | 0.00 | 1.10 |
July | 0.811340E+10 | 0.235050E+10 | 0.00 | 0.111166E+09 | 97094716.68 | 0.00 | 0.232390E+11 | 0.00 | 1.06 |
August | 0.106302E+11 | 0.222652E+10 | 0.00 | 0.135229E+09 | 56058977.57 | 0.00 | 0.354555E+11 | 0.00 | 1.34 |
September | 0.161898E+11 | 0.182891E+10 | 0.00 | 0.118472E+09 | 11503100.72 | 71379529.84 | 0.485738E+11 | 0.00 | 1.28 |
October | 0.215793E+11 | 0.00 | 0.00 | 0.123821E+09 | 0.00 | 0.122630E+10 | 0.613902E+11 | 0.00 | 1.07 |
November | 0.273343E+11 | 0.00 | 0.00 | 57986534.85 | 0.00 | 0.102716E+11 | 0.397665E+11 | 0.00 | 0.63 |
December | 0.293975E+11 | 0.00 | 0.00 | 18934592.04 | 0.00 | 0.304130E+11 | 0.165677E+11 | 0.00 | 0.42 |
Annual Sum or Average | 0.263205E+12 | 0.717709E+10 | 0.00 | 0.934360E+09 | 0.202671E+09 | 0.130782E+12 | 0.432746E+12 | 0.00 | 0.86 |
Minimum of Months | 0.811340E+10 | 0.00 | 0.00 | 13153576.77 | 0.00 | 0.00 | 0.141067E+11 | 0.00 | 0.41 |
Maximum of Months | 0.349372E+11 | 0.235050E+10 | 0.00 | 0.135229E+09 | 97094716.68 | 0.507787E+11 | 0.613902E+11 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565960E+11 | 0.00 | 0.00 | 0.52 |
February | 0.252866E+11 | 0.00 | 0.00 | 3354515.32 | 0.00 | 0.283090E+11 | 0.251222E+10 | 0.00 | 0.57 |
March | 0.390309E+11 | 0.00 | 0.00 | 9999704.88 | 0.00 | 0.124552E+11 | 0.815915E+10 | 0.00 | 0.61 |
April | 0.313121E+11 | 0.00 | 0.00 | 30511962.36 | 0.00 | 0.127536E+10 | 0.182376E+11 | 0.00 | 0.85 |
May | 0.224254E+11 | 40993206.11 | 0.00 | 63594476.24 | 17784548.95 | 0.112660E+10 | 0.290439E+11 | 0.00 | 1.10 |
June | 0.104561E+11 | 0.577685E+09 | 0.00 | 88779328.09 | 21393096.43 | 0.00 | 0.303662E+11 | 0.00 | 1.43 |
July | 0.574519E+10 | 0.227893E+10 | 0.00 | 99672556.74 | 34712406.83 | 0.00 | 0.195170E+11 | 0.00 | 1.31 |
August | 0.974488E+10 | 0.137903E+10 | 0.00 | 82441307.63 | 33047291.70 | 0.00 | 0.220607E+11 | 0.00 | 1.36 |
September | 0.208523E+11 | 0.952643E+09 | 0.00 | 40416631.06 | 4101285.21 | 0.102526E+09 | 0.177326E+11 | 0.00 | 1.06 |
October | 0.328290E+11 | 0.00 | 0.00 | 17352682.99 | 0.00 | 0.128589E+10 | 0.110318E+11 | 0.00 | 0.79 |
November | 0.334906E+11 | 0.00 | 0.00 | 3809068.58 | 0.00 | 0.116053E+11 | 0.364774E+10 | 0.00 | 0.59 |
December | 0.234017E+11 | 0.00 | 0.00 | 153204.37 | 0.00 | 0.374731E+11 | 0.252202E+09 | 0.00 | 0.51 |
Annual Sum or Average | 0.270170E+12 | 0.522928E+10 | 0.00 | 0.440085E+09 | 0.111039E+09 | 0.150229E+12 | 0.162561E+12 | 0.00 | 0.89 |
Minimum of Months | 0.574519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.390309E+11 | 0.227893E+10 | 0.00 | 99672556.74 | 34712406.83 | 0.565960E+11 | 0.303662E+11 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822228E+10 | 0.00 | 0.00 | 0.39 |
February | 0.585329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498170E+10 | 0.00 | 0.00 | 0.38 |
March | 0.190773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340881E+10 | 0.00 | 0.00 | 0.37 |
April | 0.276635E+10 | 0.00 | 0.00 | 160379.14 | 0.00 | 0.126190E+10 | 0.124901E+09 | 0.00 | 0.43 |
May | 0.267148E+10 | 1871543.96 | 0.00 | 1586106.00 | 838242.60 | 0.691614E+09 | 0.863441E+09 | 0.00 | 0.55 |
June | 0.130860E+10 | 21348154.41 | 0.00 | 6498761.75 | 2159396.13 | 23128344.60 | 0.235057E+10 | 0.00 | 0.84 |
July | 0.799203E+09 | 84367320.45 | 0.00 | 7243058.16 | 7274578.97 | 0.00 | 0.152591E+10 | 0.00 | 0.78 |
August | 0.122993E+10 | 55702281.83 | 0.00 | 5996271.86 | 6340591.93 | 14483258.55 | 0.153245E+10 | 0.00 | 0.74 |
September | 0.220544E+10 | 44486828.21 | 0.00 | 1830995.90 | 5877383.96 | 0.323151E+09 | 0.714111E+09 | 0.00 | 0.57 |
October | 0.250330E+10 | 0.00 | 0.00 | 53428.33 | 693583.56 | 0.132486E+10 | 28516067.44 | 0.00 | 0.45 |
November | 0.116926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320346E+10 | 0.00 | 0.00 | 0.38 |
December | 0.327856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593190E+10 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.175865E+11 | 0.207776E+09 | 0.00 | 23369001.15 | 23183777.15 | 0.293873E+11 | 0.713990E+10 | 0.00 | 0.52 |
Minimum of Months | 0.112000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.276635E+10 | 84367320.45 | 0.00 | 7243058.16 | 7274578.97 | 0.822228E+10 | 0.235057E+10 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.279127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581314E+10 | 0.00 | 0.00 | 0.47 |
February | 0.121399E+10 | 0.00 | 0.00 | 1813.76 | 0.00 | 0.332977E+10 | 16139660.35 | 0.00 | 0.49 |
March | 0.234203E+10 | 0.00 | 0.00 | 335687.85 | 0.00 | 0.208904E+10 | 0.273582E+09 | 0.00 | 0.52 |
April | 0.199625E+10 | 0.00 | 0.00 | 2174446.71 | 0.00 | 0.750947E+09 | 0.159334E+10 | 0.00 | 0.71 |
May | 0.167249E+10 | 1598140.89 | 0.00 | 4186657.34 | 736394.97 | 0.412954E+09 | 0.260226E+10 | 0.00 | 0.97 |
June | 0.808958E+09 | 21114123.94 | 0.00 | 10926692.35 | 1975633.78 | 8441368.92 | 0.388105E+10 | 0.00 | 1.63 |
July | 0.480340E+09 | 74269041.16 | 0.00 | 13787020.71 | 6555367.11 | 0.00 | 0.296247E+10 | 0.00 | 1.67 |
August | 0.792843E+09 | 62990726.50 | 0.00 | 9852257.96 | 5374527.62 | 4007500.60 | 0.305329E+10 | 0.00 | 1.56 |
September | 0.153932E+10 | 47954152.68 | 0.00 | 3837452.21 | 4096001.37 | 0.169805E+09 | 0.177796E+10 | 0.00 | 0.99 |
October | 0.238561E+10 | 0.00 | 0.00 | 642401.64 | 634560.33 | 0.737463E+09 | 0.430827E+09 | 0.00 | 0.65 |
November | 0.156782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227563E+10 | 0.00 | 0.00 | 0.52 |
December | 0.562028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446381E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.156408E+11 | 0.207926E+09 | 0.00 | 45744430.53 | 19372485.18 | 0.200550E+11 | 0.165909E+11 | 0.00 | 0.89 |
Minimum of Months | 0.279127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.238561E+10 | 74269041.16 | 0.00 | 13787020.71 | 6555367.11 | 0.581314E+10 | 0.388105E+10 | 0.00 | 1.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.157061E+10 | 0.00 | 0.00 | 506664.66 | 0.00 | 0.600907E+10 | 0.529703E+09 | 0.00 | 0.40 |
February | 0.200666E+10 | 0.00 | 0.00 | 3470406.08 | 0.00 | 0.293077E+10 | 0.201711E+10 | 0.00 | 0.54 |
March | 0.245990E+10 | 0.00 | 0.00 | 4487938.58 | 0.00 | 0.224034E+10 | 0.331477E+10 | 0.00 | 0.59 |
April | 0.227535E+10 | 0.00 | 0.00 | 4578955.26 | 0.00 | 0.978154E+09 | 0.329495E+10 | 0.00 | 0.74 |
May | 0.221929E+10 | 3260152.26 | 0.00 | 5892278.28 | 824990.47 | 0.673879E+09 | 0.336251E+10 | 0.00 | 0.87 |
June | 0.149336E+10 | 33565016.33 | 0.00 | 10047524.22 | 2387691.38 | 31094913.08 | 0.344840E+10 | 0.00 | 1.15 |
July | 0.886326E+09 | 0.130593E+09 | 0.00 | 12532543.22 | 6371134.82 | 0.00 | 0.240074E+10 | 0.00 | 1.12 |
August | 0.113759E+10 | 0.131700E+09 | 0.00 | 14793683.94 | 4051412.46 | 16743099.12 | 0.355492E+10 | 0.00 | 1.37 |
September | 0.169904E+10 | 0.152187E+09 | 0.00 | 10300175.13 | 458159.15 | 0.208935E+09 | 0.418750E+10 | 0.00 | 1.24 |
October | 0.215293E+10 | 1254283.09 | 0.00 | 8469690.13 | 56347.44 | 0.610151E+09 | 0.418232E+10 | 0.00 | 0.94 |
November | 0.210981E+10 | 0.00 | 0.00 | 2899087.52 | 0.00 | 0.191592E+10 | 0.207698E+10 | 0.00 | 0.54 |
December | 0.190974E+10 | 0.00 | 0.00 | 934389.41 | 0.00 | 0.410534E+10 | 0.767587E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.219206E+11 | 0.452559E+09 | 0.00 | 78913336.44 | 14149735.72 | 0.197204E+11 | 0.331375E+11 | 0.00 | 0.83 |
Minimum of Months | 0.886326E+09 | 0.00 | 0.00 | 506664.66 | 0.00 | 0.00 | 0.529703E+09 | 0.00 | 0.40 |
Maximum of Months | 0.245990E+10 | 0.152187E+09 | 0.00 | 14793683.94 | 6371134.82 | 0.600907E+10 | 0.418750E+10 | 0.00 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.563822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606251E+10 | 0.00 | 0.00 | 0.51 |
February | 0.150256E+10 | 0.00 | 0.00 | 194795.96 | 0.00 | 0.343882E+10 | 0.158871E+09 | 0.00 | 0.56 |
March | 0.264318E+10 | 0.00 | 0.00 | 695407.26 | 0.00 | 0.225617E+10 | 0.568909E+09 | 0.00 | 0.60 |
April | 0.284650E+10 | 0.00 | 0.00 | 2310359.26 | 0.00 | 0.648007E+09 | 0.143645E+10 | 0.00 | 0.84 |
May | 0.225641E+10 | 2153910.71 | 0.00 | 5704412.45 | 735664.86 | 0.418266E+09 | 0.261503E+10 | 0.00 | 1.12 |
June | 0.127656E+10 | 28817555.59 | 0.00 | 9853524.72 | 448528.11 | 22182573.03 | 0.288549E+10 | 0.00 | 1.51 |
July | 0.651061E+09 | 0.123650E+09 | 0.00 | 11094609.47 | 3397001.84 | 0.00 | 0.193023E+10 | 0.00 | 1.37 |
August | 0.103791E+10 | 77199638.90 | 0.00 | 8978042.04 | 2704653.35 | 14718115.69 | 0.211787E+10 | 0.00 | 1.38 |
September | 0.208641E+10 | 80265119.54 | 0.00 | 3464288.78 | 593470.21 | 0.166126E+09 | 0.148627E+10 | 0.00 | 1.07 |
October | 0.276316E+10 | 0.00 | 0.00 | 1124425.35 | 721240.35 | 0.686676E+09 | 0.720685E+09 | 0.00 | 0.78 |
November | 0.206362E+10 | 0.00 | 0.00 | 107605.48 | 0.00 | 0.213958E+10 | 0.130938E+09 | 0.00 | 0.59 |
December | 0.110851E+10 | 0.00 | 0.00 | 1545.47 | 0.00 | 0.438418E+10 | 9390630.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.207997E+11 | 0.312086E+09 | 0.00 | 43529016.25 | 8600558.73 | 0.202372E+11 | 0.140601E+11 | 0.00 | 0.91 |
Minimum of Months | 0.563822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.284650E+10 | 0.123650E+09 | 0.00 | 11094609.47 | 3397001.84 | 0.606251E+10 | 0.288549E+10 | 0.00 | 1.51 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 37197510.88 | 0.00 | 0.00 | 1982745.85 | 0.00 | 0.00 | 0.812180E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7101131.33 | 0.00 | 0.00 | 0.645311E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 14121821.72 | 0.00 | 0.00 | 0.660801E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 17549509.52 | 0.00 | 0.00 | 0.461562E+09 | 0.00 | 0.29 |
May | 0.00 | 150965.34 | 0.00 | 3814495.83 | 0.00 | 0.00 | 0.407524E+09 | 0.00 | 0.29 |
June | 0.00 | 14340476.44 | 0.00 | 7343305.90 | 0.00 | 0.00 | 0.198062E+09 | 0.00 | 0.30 |
July | 0.00 | 24436644.71 | 0.00 | 8755621.93 | 0.00 | 0.00 | 75677823.27 | 0.00 | 0.28 |
August | 0.00 | 7368545.07 | 0.00 | 15855089.77 | 0.00 | 0.00 | 0.141231E+09 | 0.00 | 0.31 |
September | 0.00 | 11363819.41 | 0.00 | 3397104.51 | 0.00 | 0.00 | 0.257298E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8377133.78 | 0.00 | 0.00 | 0.439018E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12327186.87 | 0.00 | 0.00 | 0.543032E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16985234.31 | 0.00 | 0.00 | 0.715816E+09 | 0.00 | 0.28 |
Annual Sum or Average | 37197510.88 | 57660450.96 | 0.00 | 0.117610E+09 | 0.00 | 0.00 | 0.535751E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1982745.85 | 0.00 | 0.00 | 75677823.27 | 0.00 | 0.28 |
Maximum of Months | 37197510.88 | 24436644.71 | 0.00 | 17549509.52 | 0.00 | 0.00 | 0.812180E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.424993E+10 | 0.00 | 0.00 | 4400742.04 | 0.00 | 0.00 | 0.414734E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 52005313.64 | 0.00 | 0.00 | 0.647250E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.118993E+09 | 0.00 | 0.00 | 0.663010E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.159011E+09 | 0.00 | 0.00 | 0.462987E+10 | 0.00 | 0.29 |
May | 0.00 | 1431987.91 | 0.00 | 29782991.01 | 0.00 | 0.00 | 0.408891E+10 | 0.00 | 0.29 |
June | 0.00 | 0.141894E+09 | 0.00 | 67855528.61 | 0.00 | 0.00 | 0.198853E+10 | 0.00 | 0.30 |
July | 0.00 | 0.243253E+09 | 0.00 | 82989477.28 | 0.00 | 0.00 | 0.761887E+09 | 0.00 | 0.28 |
August | 0.00 | 73315946.71 | 0.00 | 0.150533E+09 | 0.00 | 0.00 | 0.141982E+10 | 0.00 | 0.31 |
September | 0.00 | 0.110780E+09 | 0.00 | 27428574.75 | 0.00 | 0.00 | 0.259577E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 70547471.89 | 0.00 | 0.00 | 0.440302E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.103427E+09 | 0.00 | 0.00 | 0.544947E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.142109E+09 | 0.00 | 0.00 | 0.718410E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.424993E+10 | 0.570675E+09 | 0.00 | 0.100908E+10 | 0.00 | 0.00 | 0.497713E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 4400742.04 | 0.00 | 0.00 | 0.761887E+09 | 0.00 | 0.28 |
Maximum of Months | 0.424993E+10 | 0.243253E+09 | 0.00 | 0.159011E+09 | 0.00 | 0.00 | 0.718410E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.729606E+09 | 0.00 | 0.00 | 91041.59 | 0.00 | 0.00 | 87852192.69 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 4154619.87 | 0.00 | 0.00 | 0.648212E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 10625402.99 | 0.00 | 0.00 | 0.664290E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 14956258.43 | 0.00 | 0.00 | 0.464105E+09 | 0.00 | 0.29 |
May | 41002132.50 | 145524.81 | 0.00 | 2413496.18 | 0.00 | 0.00 | 0.367635E+09 | 0.00 | 0.29 |
June | 0.00 | 14240787.56 | 0.00 | 6615446.16 | 0.00 | 0.00 | 0.199260E+09 | 0.00 | 0.30 |
July | 0.00 | 24336062.00 | 0.00 | 8273020.15 | 0.00 | 0.00 | 76334374.32 | 0.00 | 0.28 |
August | 0.00 | 7341688.27 | 0.00 | 14921636.72 | 0.00 | 0.00 | 0.142264E+09 | 0.00 | 0.31 |
September | 10433187.67 | 11070735.88 | 0.00 | 2213826.62 | 0.00 | 0.00 | 0.251554E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 5938695.58 | 0.00 | 0.00 | 0.441782E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9022737.28 | 0.00 | 0.00 | 0.546333E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 12969495.93 | 0.00 | 0.00 | 0.719735E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.781041E+09 | 57134798.52 | 0.00 | 92195677.50 | 0.00 | 0.00 | 0.460936E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 91041.59 | 0.00 | 0.00 | 76334374.32 | 0.00 | 0.28 |
Maximum of Months | 0.729606E+09 | 24336062.00 | 0.00 | 14956258.43 | 0.00 | 0.00 | 0.719735E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:06:43
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.275746E+12 | 0.189459E+11 | 0.00 | 0.156619E+13 | 0.228487E+12 |
February | 0.368883E+12 | 0.147824E+11 | 0.00 | 0.143410E+13 | 0.225607E+12 |
March | 0.631686E+12 | 0.139018E+11 | 0.00 | 0.171069E+13 | 0.289017E+12 |
April | 0.677468E+12 | 0.994975E+10 | 0.00 | 0.179296E+13 | 0.371950E+12 |
May | 0.892118E+12 | 0.984483E+10 | 0.00 | 0.174697E+13 | 0.306365E+12 |
June | 0.975582E+12 | 0.509894E+10 | 0.00 | 0.149686E+13 | 0.851482E+12 |
July | 0.966397E+12 | 0.336409E+10 | 0.00 | 0.120167E+13 | 0.144430E+13 |
August | 0.804369E+12 | 0.365026E+10 | 0.00 | 0.135679E+13 | 0.136455E+13 |
September | 0.606507E+12 | 0.659527E+10 | 0.00 | 0.154742E+13 | 0.540390E+12 |
October | 0.399159E+12 | 0.958850E+10 | 0.00 | 0.187164E+13 | 0.269181E+12 |
November | 0.219420E+12 | 0.134159E+11 | 0.00 | 0.168363E+13 | 0.266557E+12 |
December | 0.180931E+12 | 0.170183E+11 | 0.00 | 0.157085E+13 | 0.394306E+12 |
Annual Sum or Average | 0.699827E+13 | 0.126156E+12 | 0.00 | 0.189798E+14 | 0.655220E+13 |
Minimum of Months | 0.180931E+12 | 0.336409E+10 | 0.00 | 0.120167E+13 | 0.225607E+12 |
Maximum of Months | 0.975582E+12 | 0.189459E+11 | 0.00 | 0.187164E+13 | 0.144430E+13 |