Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:05
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 09:05:12
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 32261.07 | 696.48 | 696.48 |
Net Site Energy | 32261.07 | 696.48 | 696.48 |
Total Source Energy | 84062.26 | 1814.80 | 1814.80 |
Net Source Energy | 84062.26 | 1814.80 | 1814.80 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 708.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1256.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7193.90 | 0.00 | 0.00 |
Interior Lighting | 2020.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 323.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3258.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1397.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 471.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 262.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5961.31 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 692.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 23665.43 | 1401.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7193.90 | 0.00 | 8241.48 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 708.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1256.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7193.90 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2020.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 323.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ComputerHVAC | 1349.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 1397.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 471.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 262.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5961.31 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 692.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 708.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1256.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7193.90 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2020.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 323.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 3258.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 1397.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 471.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 262.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5961.31 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 692.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 73.11 | 30.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.31 | 0.00 | 0.18 |
Other | 387.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 510.91 | 30.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.31 | 0.00 | 0.18 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 73.11 | 30.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.31 | 0.00 | 0.18 |
Other | 387.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 510.91 | 30.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.31 | 0.00 | 0.18 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 23665.427 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 23665.427 | 100.00 |
Total On-Site and Utility Electric Sources | 23665.427 | 100.00 |
Total Electricity End Uses | 23665.427 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 8241.48 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 8241.48 | 100.00 |
Total Water End Uses | 8241.48 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 8.50 |
Time Setpoint Not Met During Occupied Cooling | 358.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionDistrictHeatingCoolingMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:05 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.8895 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.8895 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 5.9168 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 5.9168 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.8895 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8895 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.8895 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8895 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.8895 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.9168 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.9168 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.8190 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
Time of Peak | 02-AUG-15:30 | 21-JAN-07:10 | - | - | - | - | - | - | - | - | 21-AUG-15:00 | 01-MAR-00:30 | 28-JUN-16:19 |
Heating | 0.00 | 681631.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 | 0.00 |
Cooling | 225839.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370603.48 | 0.00 | 0.00 |
Interior Lighting | 171235.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 151141.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 213932.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 48821.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 42924.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27561.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1632266.59 | 709192.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370603.48 | 12.11 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 | 0.00 |
Boiler | 0.00 | 681631.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 225839.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370603.48 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 171235.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3372.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ComputerHVAC | 68333.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 213932.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 48821.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 42924.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 27561.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 768.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Cooling | 3978.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7594.36 | 0.00 |
Interior Lighting | 6400.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1023.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10318.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4424.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1492.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 829.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 751.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 74948.41 | 1519.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7594.36 | 0.01 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 16.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 85.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.95 | 0.00 |
Interior Lighting | 138.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 22.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 222.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 95.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 32.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 17.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1618.04 | 32.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.95 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 16.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 85.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.95 | 0.00 |
Interior Lighting | 138.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 22.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 222.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 95.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 32.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 17.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1618.04 | 32.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.95 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.92 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.572047 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.46 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.558509 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.38 | 0.297994 | 0.310000 | 1.98 | 0.794649 | 0.500000 | 0.001279 | 0.000143 | 1.98 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 59.71 | 0.318540 | 0.324000 | 19.35 | 0.849441 | 0.500000 | 0.001196 | 0.003431 | 19.35 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.00 | 0.317065 | 0.331000 | 1.99 | 0.845507 | 0.500000 | 0.001202 | 0.000698 | 2.89 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.07 | 0.222863 | 0.232000 | 0.248612 | 0.594301 | 0.500000 | 0.001710 | 0.000079 | 0.327957 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.25 | 0.123293 | 0.200000 | 0.249657 | 0.328782 | 0.500000 | 0.003090 | 0.000058 | 0.249657 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.31 | 0.182056 | 0.200000 | 0.262365 | 0.485483 | 0.500000 | 0.002093 | 0.000099 | 0.411714 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.60 | 0.096318 | 0.200000 | 0.319577 | 0.300000 | 0.500000 | 0.003956 | 0.000049 | 0.319577 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 9.88 | 0.241740 | 0.246000 | 2.43 | 0.644640 | 0.500000 | 0.001576 | 0.001600 | 6.63 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 13.14 | 0.117097 | 0.200000 | 2.63 | 0.312259 | 0.500000 | 0.003254 | 0.001062 | 4.40 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 12.40 | 0.192649 | 0.200000 | 2.48 | 0.513732 | 0.500000 | 0.001978 | 0.001585 | 6.57 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 14.03 | 0.109665 | 0.200000 | 2.81 | 0.300000 | 0.500000 | 0.003474 | 0.000992 | 4.11 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.15 | 0.207368 | 0.216000 | 0.248762 | 0.552982 | 0.500000 | 0.001837 | 0.000213 | 0.884135 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.34 | 0.115282 | 0.200000 | 0.267005 | 0.307420 | 0.500000 | 0.003305 | 0.000141 | 0.583081 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.39 | 0.171796 | 0.200000 | 0.278034 | 0.458122 | 0.500000 | 0.002218 | 0.000211 | 0.876549 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.52 | 0.101461 | 0.200000 | 0.303379 | 0.300000 | 0.500000 | 0.003755 | 0.000135 | 0.561191 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 16386.31 | 0.000143 | 330.34 |
CORE_MID VAV BOX REHEAT COIL | 392212.65 | 0.003431 | 9242.71 |
CORE_TOP VAV BOX REHEAT COIL | 79734.00 | 0.000698 | 2104.64 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 9062.82 | 0.000079 | 239.25 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6630.45 | 0.000058 | 171.99 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 11368.61 | 0.000099 | 300.01 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5557.47 | 0.000049 | 125.79 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 182872.23 | 0.001600 | 4823.17 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 121417.22 | 0.001062 | 3202.23 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 181200.15 | 0.001585 | 4779.11 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 113412.91 | 0.000992 | 2991.31 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 24371.28 | 0.000213 | 642.63 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 16072.10 | 0.000141 | 423.79 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 24162.50 | 0.000211 | 637.13 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15469.52 | 0.000135 | 407.91 |
VAV_BOT WITH REHEAT HEATING COIL | 53572.94 | 0.000469 | 876.66 |
VAV_MID WITH REHEAT HEATING COIL | 492162.04 | 0.004306 | 8059.70 |
VAV_TOP WITH REHEAT HEATING COIL | 49205.19 | 0.000430 | 812.66 |
CAV_BAS HEATING COIL | 245298.44 | 0.002146 | 5426.05 |
Design Size Maximum Heating Air Flow Rate [m3/s] | Design Size Maximum Cooling Air Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT | 0.338402 | 25.88 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.81 | 3.06 | 11.61 | 3.06 | 10.49 | 10.49 | 0.300000 | 0.291663 | 10.49 |
VAV_MID WITH REHEAT | 54.58 | 29.69 | 109.16 | 33.61 | 97.16 | 97.16 | 0.300000 | 0.345919 | 97.16 |
VAV_TOP WITH REHEAT | 5.70 | 3.08 | 11.39 | 5.79 | 10.66 | 10.66 | 0.300000 | 0.543372 | 10.66 |
CAV_BAS | 5.92 | 5.92 | 5.92 | 5.92 | 5.92 | 5.92 | 1.00 | 1.00 | 5.92 |
AIRLOOP DATACENTER BOT | 0.572047 | 0.572047 | 0.572047 | 0.572047 | 0.572047 | 0.572047 | 1.00 | 1.00 | 0.572047 |
AIRLOOP DATACENTER MID | 5.46 | 5.46 | 5.46 | 5.46 | 5.46 | 5.46 | 1.00 | 1.00 | 5.46 |
AIRLOOP DATACENTER TOP | 0.558509 | 0.558509 | 0.558509 | 0.558509 | 0.558509 | 0.558509 | 1.00 | 1.00 | 0.558509 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.49 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 97.16 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.66 | |
CAV_BAS_OA_CONTROLLER | 5.92 | |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.572047 | 0.015633 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.46 | 0.156328 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.558509 | 0.015633 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.82 | 6.67 | 10.67 | 0.006950 | 0.006950 | 170803.67 | 0.007266 | 10.49 |
VAV_MID WITH REHEAT COOLING COIL | 27.17 | 6.67 | 10.55 | 0.006927 | 0.006927 | 1628129.92 | 0.069264 | 97.16 |
VAV_TOP WITH REHEAT COOLING COIL | 26.65 | 6.67 | 10.67 | 0.006955 | 0.006955 | 171726.02 | 0.007306 | 10.66 |
CAV_BAS COOLING COIL | 26.39 | 6.67 | 11.12 | 0.007142 | 0.007142 | 91227.73 | 0.003881 | 5.92 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.49 |
VAV_MID WITH REHEAT FAN | 97.16 |
VAV_TOP WITH REHEAT FAN | 10.66 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007266 | 0.000066 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000469 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.069264 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.004306 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.007306 | 0.000065 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000430 | |
CAV_BAS_COOLC_CONTROLLER | 0.003881 | 0.000123 |
CAV_BAS_HEATC_CONTROLLER | 0.002146 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.92 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.572047 | 10205.49 | 5462.03 | 0.000250 |
AIRLOOP DATACENTER MID COOLING COIL | 5.46 | 97515.33 | 52176.07 | 0.002388 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.558509 | 9966.77 | 5333.46 | 0.000244 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.572047 | 0.572047 | 0.572047 | 0.572047 | 10205.49 | 10205.49 | 745.23 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.46 | 5.46 | 5.46 | 5.46 | 97515.33 | 97515.33 | 7452.32 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.558509 | 0.558509 | 0.558509 | 0.558509 | 9966.77 | 9966.77 | 745.23 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.572047 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.46 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.558509 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT HEATING COIL | 0.572047 | 10205.49 | 0.000250 |
AIRLOOP DATACENTER MID HEATING COIL | 5.46 | 97515.33 | 0.002388 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.558509 | 9966.77 | 0.000244 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 745.23 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 7452.32 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 745.23 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.087717 | 17896.35 | |
HEATSYS1 PUMP | 0.017848 | 5321.90 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.087717 | 10.53 |
HEATSYS1 | 0.017848 | 2.14 |
COOLSYS1_SUPPLY | 0.087717 | 10.53 |
SINGLE WATER PLANT LOOP | 0.002882 | 0.345859 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.087717 | 0.087717 | 368194.17 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2040168.81 | 2040168.81 | 0.017848 |
CENTRAL BOILER | 118720.35 | 118720.35 | 0.002882 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.087717 | 12390.25 |
PLANT CIRC PUMP | 0.002882 | 727.82 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.087717 | 0.044247 | 1041235.76 | 1047573.35 | 0.053110 |
COOLSYS1 CHILLER2 | 0.087717 | 0.044247 | 1041235.76 | 1047573.35 | 0.053110 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.002882 | 35644.39 | 18351.61 | 17822.20 | 1996.20 | 5717.83 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.106219 | 12.75 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.106219 | 31674.25 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 48.72 | 1244454.21 | 9.74 | 155556.78 |
TOWERWATERSYS COOLTOWER 2 | 48.72 | 1244454.21 | 9.74 | 155556.78 |
Design Water Flow Rate [m3/s] Equipment # 45 | |
WSHPPLANT OPERATION SCHEME | 0.053845 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.889 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.731 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.889 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.313 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16369.361 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16369.361 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4615.459 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4615.459 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.339 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.260 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.694 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5795 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6262 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4230 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.13684007E-14 | 0.43769670E-16 | -0.13032795E-09 | -0.34517937E-17 |
51 | 8 | 0.19139952E-07 | 0.17580734E-12 | 0.34842432E-03 | -0.21762784E-09 |
52 | 7 | -0.11363040E-01 | 0.94207812E-08 | -0.21820187E-01 | 0.12920189E-03 |
53 | 6 | 0.38147639 | 0.33245073E-05 | 0.45170425 | -0.44663469E-02 |
54 | 5 | -4.9575440 | 0.12566514E-03 | -4.2844407 | 0.60294545E-01 |
55 | 4 | 31.971915 | 0.10393916E-02 | 20.826829 | -0.40843520 |
56 | 3 | -109.03212 | 0.22875987E-02 | -54.410870 | 1.4834967 |
57 | 2 | 194.95586 | 0.12980373E-02 | 76.763178 | -2.8661744 |
58 | 1 | -170.36074 | 0.13969006E-03 | -54.933270 | 2.7315001 |
59 | 0 | 57.057407 | 0.80219562E-06 | 15.613236 | |
60 | 9 | 0.17296484E-14 | 0.42300129E-16 | -0.13408130E-09 | -0.44058463E-17 |
61 | 8 | 0.19671007E-07 | 0.16641005E-12 | 0.35423406E-03 | -0.22366611E-09 |
62 | 7 | -0.11537194E-01 | 0.88593938E-08 | -0.22071206E-01 | 0.13118209E-03 |
63 | 6 | 0.38620962 | 0.31182457E-05 | 0.45575528 | -0.45221398E-02 |
64 | 5 | -5.0037487 | 0.11760487E-03 | -4.3156427 | 0.60867449E-01 |
65 | 4 | 32.176377 | 0.97077592E-03 | 20.948989 | -0.41114975 |
66 | 3 | -109.46738 | 0.21328008E-02 | -54.652468 | 1.4897847 |
67 | 2 | 195.38754 | 0.12083052E-02 | 76.984396 | -2.8730290 |
68 | 1 | -170.52030 | 0.12984550E-03 | -54.996922 | 2.7342967 |
69 | 0 | 57.057407 | 0.74448799E-06 | 15.602172 | |
70 | 9 | 0.10997584E-14 | 0.53843923E-16 | -0.11326114E-09 | -0.28570046E-17 |
71 | 8 | 0.16725364E-07 | 0.21557791E-12 | 0.32127585E-03 | -0.19017314E-09 |
72 | 7 | -0.10546704E-01 | 0.11930081E-07 | -0.20642631E-01 | 0.11991984E-03 |
73 | 6 | 0.35928609 | 0.42648229E-05 | 0.43264702 | -0.42047803E-02 |
74 | 5 | -4.7408821 | 0.16300219E-03 | -4.1373754 | 0.57608138E-01 |
75 | 4 | 31.012880 | 0.13615538E-02 | 20.250423 | -0.39570291 |
76 | 3 | -106.98970 | 0.30226891E-02 | -53.270634 | 1.4539929 |
77 | 2 | 192.92930 | 0.17282771E-02 | 75.720319 | -2.8339965 |
78 | 1 | -169.61128 | 0.18730106E-03 | -54.635416 | 2.7183650 |
79 | 0 | 57.057407 | 0.10839563E-05 | 15.666826 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3628_SHGC_EAST_0.36 | 35 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.361 | ||
2 | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 36 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.361 | ||
3 | WINDOW_U_0.3628_SHGC_WEST_0.36 | 37 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.361 | ||
4 | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 38 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62909E-002 | 0.27318 | 0.51969 | 0.51969 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62909E-002 | 0.27318 | 0.51969 | 0.51969 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62909E-002 | 0.27318 | 0.51969 | 0.51969 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62909E-002 | 0.27318 | 0.51969 | 0.51969 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2.856E-002 | 9.114E-005 | 1.371E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.384E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2.856E-002 | 9.114E-005 | 1.371E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.384E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 4.231E-002 | 1.187E-005 | 1.424E-004 | 3.506E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 4.231E-002 | 1.187E-005 | 1.424E-004 | 3.506E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 4.231E-002 | 1.187E-005 | 1.096E-005 | 3.506E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3860E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3877E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7646E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7661E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2096E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2108E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7698E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7704E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4263E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5465E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7986E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9037E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2388E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3257E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7873E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8319E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1196 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.8845E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1355 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5656E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.0371E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6353E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.7170E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3047E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4280E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5543E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8003E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9115E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2403E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3313E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7877E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8332E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3858E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3876E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7644E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7659E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2095E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2107E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7697E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7704E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8299E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0528E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6131E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8530E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4827E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5867E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0284E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0591E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3479E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2194E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0362E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9896E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5737E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9221E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8227E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4292E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7647E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8465E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5292E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5885E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4496E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4728E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0285E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0596E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8157E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8174E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5441E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5454E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3660E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3669E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7698E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7704E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8531E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9507E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5744E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6511E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3903E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4442E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7878E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8333E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8930E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6752E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2371E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2695E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2483E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.9379E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.7170E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3043E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8521E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9483E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5734E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6487E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3891E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4408E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7873E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8320E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8156E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8172E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5440E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5453E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3659E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3668E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7697E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7704E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6979E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7802E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4464E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5059E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3938E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4166E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0286E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0596E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2184E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1678E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8773E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9263E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4581E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8756E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8227E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4292E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7608E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9745E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5274E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7558E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4264E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5287E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0283E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0590E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1090 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.5388E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1192 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 8.3241E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.3368E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.9843E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.2949E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.0811E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.0110E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0676E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.6719E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7948E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1972E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6919E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.3948E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1031E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4588E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4431E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7447E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9285E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7506E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4992E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2949E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0807E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8707E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0000E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.4993E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7115E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.0730E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6331E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.3948E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1031E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1089 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.5496E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1191 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 8.3371E-002 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.3388E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.9944E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.2998E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.0851E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.0082E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0702E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.6703E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7974E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1989E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6965E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.3994E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1071E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4543E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4440E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7416E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9293E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7519E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5014E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2998E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0847E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8678E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0025E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.4975E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7140E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.0746E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6376E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.3994E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1071E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 67481.42265 | 67481.42265 | 5.92487 | 5.92487 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2779.42662 | 149.60210 | 1.20019 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20019 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | -7.90000 | 2.34317E-003 | 2779.42662 | 149.60210 | 1.20019 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 72698.80488 | 72698.80488 | 6.38284 | 6.38284 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 680271.83257 | 680271.83257 | 59.71124 | 59.71124 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 231996.30516 | 231996.30516 | 11.89377 | 11.89377 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 67722.60799 | 67722.60799 | 5.99890 | 5.99890 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 35.10000 | 5.69938E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 55833.43892 | 55833.43892 | 2.88604 | 2.88604 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12097.75478 | 12097.75478 | 1.07160 | 1.07160 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10000 | 5.69938E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 6348.18638 | 6348.18638 | 0.32796 | 0.32796 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14092.48820 | 14092.48820 | 1.24828 | 1.24828 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 27.67500 | 5.68796E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 4563.77433 | 4563.77433 | 0.23593 | 0.23593 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 14809.73902 | 14809.73902 | 1.31182 | 1.31182 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 34.65000 | 5.69869E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 7960.04906 | 7960.04906 | 0.41171 | 0.41171 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18039.35423 | 18039.35423 | 1.59788 | 1.59788 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.39000 | 5.69673E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 2913.25855 | 2913.25855 | 0.15011 | 0.15011 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 111530.95547 | 111530.95547 | 9.87924 | 9.87924 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.69938E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 127973.58069 | 127973.58069 | 6.63085 | 6.63085 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 148382.83518 | 148382.83518 | 13.14338 | 13.14338 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44000 | 5.68912E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 84965.18953 | 84965.18953 | 4.40279 | 4.40279 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 139954.44738 | 139954.44738 | 12.39691 | 12.39691 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76250 | 5.69886E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 126804.70501 | 126804.70501 | 6.57009 | 6.57009 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 158439.26832 | 158439.26832 | 14.03415 | 14.03415 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 79369.44463 | 79369.44463 | 4.11200 | 4.11200 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13001.80192 | 13001.80192 | 1.15167 | 1.15167 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10000 | 5.69938E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 17051.09552 | 17051.09552 | 0.88414 | 0.88414 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15071.86712 | 15071.86712 | 1.33503 | 1.33503 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.82250 | 5.68971E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 11244.50925 | 11244.50925 | 0.58308 | 0.58308 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 15694.35166 | 15694.35166 | 1.39017 | 1.39017 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.98750 | 5.69921E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 16905.13903 | 16905.13903 | 0.87655 | 0.87655 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 17125.12755 | 17125.12755 | 1.51690 | 1.51690 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 10823.19482 | 10823.19482 | 0.56119 | 0.56119 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8187.78955 | 8187.78955 | 0.57205 | 0.57205 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 30.51000 | 5.69229E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56328E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -7.90000 | 2.34317E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 78194.15466 | 78194.15466 | 5.46315 | 5.46315 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 30.17250 | 5.69177E-003 | 36.20274 | 1.94861 | 0.15633 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15633 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -7.90000 | 2.34317E-003 | 36.20274 | 1.94861 | 0.15633 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7993.98719 | 7993.98719 | 0.55851 | 0.55851 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 30.51000 | 5.69229E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56328E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -7.90000 | 2.34317E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370482.91565 | 370482.91565 | 25.88364 | 25.88364 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 22.81500 | 5.68069E-003 | 783.67941 | 42.18139 | 0.33840 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33840 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | -7.90000 | 2.34317E-003 | 783.67941 | 42.18139 | 0.33840 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 139179.39 | 10.48774 | 10.48774 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 45395.35 | 2.20354 | 2.20354 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1270288.12 | 97.16011 | 97.16011 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 522839.33 | 33.60951 | 33.60951 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 146366.90 | 10.65751 | 10.65751 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 51682.62 | 5.79100 | 5.79100 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 |
7 | CAV_BAS | Cooling | Sensible | 70813.47 | 5.92487 | 5.92487 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 57214.39 | 1.20019 | 1.20019 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8137.90 | 0.57205 | 0.57205 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BOT | Heating | Sensible | 745.23 | 1.56328E-002 | 1.56328E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER MID | Cooling | Sensible | 77736.59 | 5.46315 | 5.46315 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER MID | Heating | Sensible | 7452.32 | 0.15633 | 0.15633 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7946.57 | 0.55851 | 0.55851 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER TOP | Heating | Sensible | 745.23 | 1.56328E-002 | 1.56328E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.92487 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.38284 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29799 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.97868 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79465 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.27855E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.43355E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.97868 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16386.30636 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.43355E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 330.33507 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 59.71124 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31854 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32400 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.34644 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84944 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19608E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.43125E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.34644 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 392212.64843 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.43125E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9242.71072 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.99890 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31707 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33100 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.98564 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84551 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20165E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.97548E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.88604 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 79733.99513 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.97548E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2104.63894 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07160 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22286 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23200 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24861 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59430 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.70957E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.92855E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32796 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9062.82255 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.92855E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 239.24681 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.24828 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12329 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24966 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32878 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.09019E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.80061E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24966 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6630.45242 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.80061E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 171.98681 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.31182 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18206 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26236 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48548 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09276E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.94576E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41171 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11368.61244 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.94576E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 300.01033 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.59788 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.63181E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31958 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.95564E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.86192E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.31958 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5557.47149 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.86192E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 125.78513 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.87924 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24174 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24600 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.43029 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64464 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57607E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.59985E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.63085 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 182872.22730 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.59985E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4823.16928 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.14338 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11710 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.62868 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31226 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.25371E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.06221E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.40279 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 121417.21843 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06221E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3202.23254 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.39691 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19265 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.47938 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51373 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97769E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.58522E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.57009 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 181200.14802 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.58522E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4779.11117 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.03415 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10966 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.80683 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.47423E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.92186E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.11200 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 113412.90556 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.92186E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2991.30903 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.15167 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20737 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21600 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24876 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55298 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.83731E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.13211E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.88414 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24371.27764 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.13211E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 642.63291 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.33503 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11528 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26701 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30742 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.30493E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.40606E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.58308 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16072.10367 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40606E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 423.78949 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.39017 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17180 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27803 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45812 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.21775E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.11384E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.87655 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24162.50296 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.11384E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 637.13178 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.51690 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10146 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30338 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.75516E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.35334E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.56119 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15469.51513 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35334E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 407.90985 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.57205 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.46315 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.55851 |
215 | ZoneHVAC:IdealLoadsAirSystem | AIRLOOP DATACENTER BASEMENT | Design Size Maximum Heating Air Flow Rate [m3/s] | 0.33840 |
216 | ZoneHVAC:IdealLoadsAirSystem | AIRLOOP DATACENTER BASEMENT | Design Size Maximum Cooling Air Flow Rate [m3/s] | 25.88364 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.80621 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.05889 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.61243 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.05889 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.48774 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.48774 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.29166 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 54.58246 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 29.69162 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 109.16492 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 33.60951 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 97.16011 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 97.16011 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34592 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.69634 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.08282 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.39267 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.79100 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.65751 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.65751 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.54337 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.92487 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.92487 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.92487 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.92487 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.92487 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.92487 |
247 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.57205 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.57205 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.57205 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.57205 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.57205 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.57205 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
257 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.46315 |
258 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.46315 |
259 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.46315 |
260 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.46315 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.46315 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.46315 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
265 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.55851 |
266 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.55851 |
267 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.55851 |
268 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.55851 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.55851 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.55851 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
273 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.48774 |
274 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 97.16011 |
275 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.65751 |
276 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.92487 |
277 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.57205 |
278 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.46315 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.55851 |
280 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.48774 |
281 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.82439 |
282 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
283 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.66759 |
284 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.95019E-003 |
285 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.95019E-003 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 170803.66816 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.26638E-003 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.48774 |
289 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 53572.94005 |
290 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.68679E-004 |
291 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 876.66241 |
292 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.48774 |
293 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.26638E-003 |
294 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.55334E-005 |
295 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.68679E-004 |
296 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 97.16011 |
297 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.17125 |
298 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
299 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.54634 |
300 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.92715E-003 |
301 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.92715E-003 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1628129.91793 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.92644E-002 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 97.16011 |
305 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 492162.03702 |
306 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.30565E-003 |
307 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 8059.70099 |
308 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 97.16011 |
309 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.92644E-002 |
310 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.87497E-006 |
311 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.30565E-003 |
312 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.65751 |
313 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.65277 |
314 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
315 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.66761 |
316 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.95454E-003 |
317 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.95454E-003 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 171726.02431 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.30562E-003 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.65751 |
321 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 49205.19164 |
322 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.30468E-004 |
323 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 812.65837 |
324 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.65751 |
325 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.30562E-003 |
326 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.51814E-005 |
327 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.30468E-004 |
328 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.92487 |
329 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.38829 |
330 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
331 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.11839 |
332 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.14156E-003 |
333 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.14156E-003 |
334 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 91227.72715 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.88104E-003 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.92487 |
337 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 245298.43626 |
338 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.14598E-003 |
339 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5426.05473 |
340 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.92487 |
341 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.88104E-003 |
342 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.22697E-004 |
343 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.14598E-003 |
344 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.57205 |
345 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56328E-002 |
346 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.57205 |
347 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10205.48511 |
348 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5462.03377 |
349 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.49932E-004 |
350 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.57205 |
351 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.57205 |
352 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.57205 |
353 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.57205 |
354 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10205.48511 |
355 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10205.48511 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 745.23210 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
358 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.57205 |
359 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.57205 |
360 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10205.48511 |
361 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.49932E-004 |
362 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 745.23210 |
363 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.46315 |
364 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15633 |
365 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.46315 |
366 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 97515.33294 |
367 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 52176.07128 |
368 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.38814E-003 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.46315 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.46315 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.46315 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.46315 |
373 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 97515.33294 |
374 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 97515.33294 |
375 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 7452.32102 |
376 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
377 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.46315 |
378 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.46315 |
379 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 97515.33294 |
380 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.38814E-003 |
381 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 7452.32102 |
382 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.55851 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56328E-002 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.55851 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9966.77447 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5333.46173 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.44086E-004 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.55851 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.55851 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.55851 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.55851 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9966.77447 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9966.77447 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 745.23210 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
396 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.55851 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.55851 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9966.77447 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.44086E-004 |
400 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 745.23210 |
401 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 8.77175E-002 |
402 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 17896.35259 |
403 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 8.77175E-002 |
404 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 10.52609 |
405 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 8.77175E-002 |
406 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 8.77175E-002 |
407 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 368194.16742 |
408 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
409 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.78483E-002 |
410 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.14179 |
411 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.78483E-002 |
412 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 5321.90116 |
413 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
414 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2040168.81250 |
415 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2040168.81000 |
416 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.78483E-002 |
417 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 8.77175E-002 |
418 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 10.52609 |
419 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 8.77175E-002 |
420 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 12390.24858 |
421 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.77175E-002 |
422 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.42471E-002 |
423 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1041235.75617 |
424 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1047573.35500 |
425 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.31097E-002 |
426 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.77175E-002 |
427 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.42471E-002 |
428 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1041235.75617 |
429 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1047573.35500 |
430 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.31097E-002 |
431 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 2.88216E-003 |
432 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 0.34586 |
433 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 2.88216E-003 |
434 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 727.81716 |
435 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 2.88216E-003 |
436 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 35644.39112 |
437 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 18351.61028 |
438 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 17822.19556 |
439 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 1996.19659 |
440 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 5717.82824 |
441 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 118720.34761 |
442 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 118720.35000 |
443 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 2.88216E-003 |
444 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
445 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
446 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
447 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
448 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
449 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10622 |
450 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.74634 |
451 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10622 |
452 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 31674.25037 |
453 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 48.71626 |
454 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1244454.20625 |
455 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 9.74325 |
456 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 155556.77578 |
457 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 48.71626 |
458 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1244454.20625 |
459 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 9.74325 |
460 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 155556.77578 |
461 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 5.38450E-002 |
462 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 5.38450E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 15539.96 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 371734.75 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 75585.31 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8591.45 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6282.30 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10776.59 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5268.27 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 173330.88 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 115081.68 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 171746.33 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 107496.25 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 23098.70 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 15232.83 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22900.86 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14661.78 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 40762.93 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 375083.22 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 38160.65 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 193055.61 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 227411.43 | 143975.25 | 83436.19 | 0.63 | 23198.97 | 235.30 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2148671.52 | 1351687.09 | 796984.43 | 0.63 | 220983.66 | 2241.34 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 230011.28 | 145883.69 | 84127.59 | 0.63 | 23504.42 | 238.39 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 122119.22 | 78482.21 | 43637.01 | 0.64 | 12031.54 | 122.03 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 7.08 | 24.14 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 7.08 | 24.14 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.36 | N/A | 2.061 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.36 | N/A | 2.061 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.36 | N/A | 2.061 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.36 | N/A | 2.061 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.36 | N/A | 2.061 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.36 | N/A | 2.061 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.36 | N/A | 2.061 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.36 | N/A | 2.061 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.36 | N/A | 2.061 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.36 | N/A | 2.061 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2703190554 | 0.2393073030 | Pass | Pass | 1.3078150116 | 3.3645806942 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1053200471 | 0.1867453882 | Pass | Pass | 0.1611204753 | 0.3662005878 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 6.7022232701E-002 | 0.1296561022 | Pass | Pass | 0.1335922897 | 0.3390372838 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.8321574508E-002 | 5.4627354301E-002 | Pass | Pass | 0.1156550310 | 0.3179474301 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 8.0338556494E-002 | 0.1319801177 | Pass | Pass | 0.1604612090 | 0.3648564834 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1768742314 | 0.2511807182 | Pass | Pass | 0.1629586214 | 0.3686518247 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2550157716 | 0.4494589672 | Pass | Pass | 0.1803179142 | 0.3992724288 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1760505493 | 0.2957874705 | Pass | Pass | 0.1597025447 | 0.3610548940 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.0760122905E-002 | 6.8756358257E-002 | Pass | Pass | 0.1328603367 | 0.3363443662 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1453450397 | 0.1971656847 | Pass | Pass | 0.1357875420 | 0.3429127498 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2882093537 | 0.4934812694 | Pass | Pass | 0.1459982245 | 0.3630826909 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1284382440 | 0.1894682604 | Pass | Pass | 0.1312421155 | 0.3297157368 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.1055212427E-002 | 0.1028359251 | Pass | Pass | 0.1633563325 | 0.5363042836 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.6571671016E-002 | 0.1189610134 | Pass | Pass | 0.1997571828 | 0.9577940891 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2064583168 | 0.2348531380 | Pass | Pass | 0.1192741492 | 0.3174483292 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1133803104 | 0.1377518141 | Pass | Pass | 0.1181863573 | 0.3296024247 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.7404693688E-002 | 2.6691896383E-002 | Pass | Pass | 0.5531899410 | 1.9958527559 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.2655713272E-002 | 3.6489634492E-002 | Pass | Pass | 0.2150967455 | 0.5558879297 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.9024907421E-002 | 7.1687062478E-002 | Pass | Pass | 0.1331139002 | 0.3436630803 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.2169205160E-006 | 6.8077050365E-006 | Pass | Pass | 6.4884779185E-003 | 8.5039459715E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.0906075694E-006 | 6.6362929184E-006 | Pass | Pass | 3.3243326110E-002 | 2.1485918094E-002 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.1677525095E-002 | 2.6260858363E-002 | Pass | Pass | 0.1046767129 | 0.3719969774 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.0724163126E-015 | 2.5295332481E-015 | Pass | Pass | 5.8988249839E-005 | 1.0439200289E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8861.14 | 36.77 | 0.00 | 16405.59 | 10299.20 | 35602.69 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3628_SHGC_EAST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3628_SHGC_EAST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.3628_SHGC_EAST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3628_SHGC_WEST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3628_SHGC_WEST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.3628_SHGC_WEST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.061 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3628_SHGC_EAST_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.061 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.061 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3628_SHGC_WEST_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.061 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.061 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3628_SHGC_EAST_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.061 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.061 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3628_SHGC_WEST_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.061 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.061 | 0.361 | 0.361 | |||||||||||||||||
North Total or Average | 1043.06 | 2.061 | 0.361 | 0.361 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.061 | 0.361 | 0.361 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.8895 | 2779.43 | 16369.36 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 135.58 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8895 | 2496.12 | 14700.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 121.76 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8895 | 24961.20 | 147008.37 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 1217.57 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8895 | 2496.12 | 14700.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 121.76 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8895 | 313.41 | 1845.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.59 | 0.0000 | Y | 8.87 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.47 | 0.0000 | Y | 5.69 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8895 | 313.42 | 1845.88 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.15 | 0.0000 | Y | 8.71 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.25 | 0.0000 | Y | 5.64 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8895 | 3134.13 | 18458.37 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.60 | 0.0000 | Y | 88.69 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8895 | 2019.75 | 11895.27 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.46 | 0.0000 | Y | 56.86 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8895 | 3134.20 | 18458.77 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.15 | 0.0000 | Y | 87.15 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8895 | 2019.75 | 11895.27 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.25 | 0.0000 | Y | 56.38 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8895 | 313.41 | 1845.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.60 | 0.0000 | Y | 8.87 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.46 | 0.0000 | Y | 5.69 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8895 | 313.42 | 1845.88 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.15 | 0.0000 | Y | 8.71 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.25 | 0.0000 | Y | 5.64 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.8895 | 783.68 | 4615.46 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 38.23 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 8.8011 | 36.20 | 318.62 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.26 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 8.8011 | 362.03 | 3186.24 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 32.64 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 8.8011 | 36.20 | 318.62 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.26 |
Interior Lighting Total | 5.9168 | 46320.38 | 274067.57 | 635.59 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.05 | AstronomicalClock | - | 41.81 | 41.81 | 78.28 | |
EXTERIOR_LIGHTS_B | 991.40 | AstronomicalClock | - | 83.71 | 62.76 | 11.68 | |
EXTERIOR_LIGHTS_C | 26646.63 | AstronomicalClock | - | 83.71 | 46.63 | 233.23 | |
Exterior Lighting Total | 37611.08 | 323.19 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2057145.61 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2040168.81 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1047573.35 | 5.33 | 1035777.15 | 4.98 | 7.08 | 24.14 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1047573.35 | 5.33 | 1035777.15 | 4.98 | 7.08 | 24.14 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 148548.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 118720.35 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1244454.21 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1244454.21 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 170803.67 | 227411.43 | 143975.25 | 83436.19 | 0.63 | - | 23198.97 | 235.30 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1628129.92 | 2148671.52 | 1351687.09 | 796984.43 | 0.63 | - | 220983.66 | 2241.34 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 171726.02 | 230011.28 | 145883.69 | 84127.59 | 0.63 | - | 23504.42 | 238.39 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 91227.73 | 122119.22 | 78482.21 | 43637.01 | 0.64 | - | 12031.54 | 122.03 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10205.49 | 5462.03 | 4743.45 | 0.54 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 97515.33 | 52176.07 | 45339.26 | 0.54 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9966.77 | 5333.46 | 4633.31 | 0.54 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 16386.31 | 15539.96 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 392212.65 | 371734.75 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 79734.00 | 75585.31 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 9062.82 | 8591.45 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 6630.45 | 6282.30 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11368.61 | 10776.59 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 5557.47 | 5268.27 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 182872.23 | 173330.88 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 121417.22 | 115081.68 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 181200.15 | 171746.33 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 113412.91 | 107496.25 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 24371.28 | 23098.70 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 16072.10 | 15232.83 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 24162.50 | 22900.86 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 15469.52 | 14661.78 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 53572.94 | 40762.93 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 492162.04 | 375083.22 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 49205.19 | 38160.65 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 245298.44 | 193055.61 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10205.49 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 97515.33 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9966.77 | 0.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 745.23 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 7452.32 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 745.23 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.49 | 22543.03 | 2149.46 | 1.00 | 1.12 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 97.16 | 220708.26 | 2271.59 | 1.00 | 1.08 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.66 | 22907.94 | 2149.46 | 1.00 | 1.12 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.92 | 10046.53 | 1695.65 | 1.00 | 1.15 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.57 | 640.75 | 1120.11 | 1.00 | 1.55 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.46 | 6119.32 | 1120.11 | 1.00 | 1.15 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.56 | 625.59 | 1120.11 | 1.00 | 1.56 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.087717 | 17896.35 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.017848 | 5321.90 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.087717 | 12390.25 | 141251.81 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.002882 | 727.82 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.106219 | 31674.25 | 298196.27 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 67481.42 | 67481.42 | 24.28 | 5.925 | 5.925 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00752 | 25.11 | 0.00568 | 1.200 | 0.00 |
CORE_BOTTOM | 72698.80 | 72698.80 | 29.12 | 6.383 | 6.383 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00743 | 25.11 | 0.00568 | 1.078 | 0.00 |
CORE_MID | 680271.83 | 680271.83 | 272.53 | 59.711 | 59.711 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00746 | 25.11 | 0.00568 | 10.778 | 0.00 |
CORE_TOP | 67722.61 | 67722.61 | 27.13 | 5.999 | 5.999 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00745 | 35.10 | 0.00570 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12097.75 | 12097.75 | 38.60 | 1.072 | 1.072 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00731 | 35.10 | 0.00570 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14092.49 | 14092.49 | 69.77 | 1.248 | 1.248 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00717 | 27.68 | 0.00569 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 14809.74 | 14809.74 | 47.25 | 1.312 | 1.312 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00725 | 34.65 | 0.00570 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18039.35 | 18039.35 | 89.31 | 1.598 | 1.598 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00713 | 33.39 | 0.00570 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 111530.96 | 111530.96 | 355.86 | 9.879 | 9.879 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00732 | 35.10 | 0.00570 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 148382.84 | 148382.84 | 734.66 | 13.143 | 13.143 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00715 | 28.44 | 0.00569 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 139954.45 | 139954.45 | 446.54 | 12.397 | 12.397 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00725 | 34.76 | 0.00570 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 158439.27 | 158439.27 | 784.45 | 14.034 | 14.034 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00714 | 33.21 | 0.00570 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13001.80 | 13001.80 | 41.48 | 1.152 | 1.152 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00727 | 35.10 | 0.00570 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15071.87 | 15071.87 | 74.62 | 1.335 | 1.335 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00715 | 28.82 | 0.00569 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15694.35 | 15694.35 | 50.07 | 1.390 | 1.390 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00722 | 34.99 | 0.00570 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 17125.13 | 17125.13 | 84.79 | 1.517 | 1.517 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00713 | 33.21 | 0.00570 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8187.79 | 8187.79 | 226.16 | 0.572 | 0.572 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00709 | 30.51 | 0.00569 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 78194.15 | 78194.15 | 2159.90 | 5.463 | 5.463 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 30.17 | 0.00569 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7993.99 | 7993.99 | 220.81 | 0.559 | 0.559 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00709 | 30.51 | 0.00569 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370482.92 | 370482.92 | 472.75 | 25.884 | 25.884 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 22.82 | 0.00568 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | 21.00 | 24.44 | 0.00234 | -7.90 | 0.00234 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 19.60 | 21.89 | 0.00234 | -7.90 | 0.00234 | 1.078 | 0.00 |
CORE_MID | 231996.31 | 231996.31 | 92.94 | 11.894 | 11.894 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 10.778 | 0.00 |
CORE_TOP | 55833.44 | 55833.44 | 22.37 | 2.886 | 2.886 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 6348.19 | 6348.19 | 20.26 | 0.328 | 0.328 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 4563.77 | 4563.77 | 22.60 | 0.236 | 0.236 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 7960.05 | 7960.05 | 25.40 | 0.412 | 0.412 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00786 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 2913.26 | 2913.26 | 14.42 | 0.150 | 0.150 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00756 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 127973.58 | 127973.58 | 408.32 | 6.631 | 6.631 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -7.90 | 0.00234 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 84965.19 | 84965.19 | 420.67 | 4.403 | 4.403 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -7.90 | 0.00234 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 126804.71 | 126804.71 | 404.58 | 6.570 | 6.570 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -7.90 | 0.00234 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 79369.44 | 79369.44 | 392.97 | 4.112 | 4.112 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -7.90 | 0.00234 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 17051.10 | 17051.10 | 54.40 | 0.884 | 0.884 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 11244.51 | 11244.51 | 55.67 | 0.583 | 0.583 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 16905.14 | 16905.14 | 53.94 | 0.877 | 0.877 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 10823.19 | 10823.19 | 53.59 | 0.561 | 0.561 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -7.90 | 0.00234 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 18.00 | 26.38 | 0.00700 | -7.90 | 0.00234 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 23.23 | 0.00495 | -7.90 | 0.00234 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 21.35 | 0.00280 | -7.90 | 0.00234 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 04:00:00 | 18.00 | 27.00 | 0.00700 | -7.90 | 0.00234 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.49 | 10.49 | 2.20 | 2.20 | 10.4877 | 3.0589 | 10.4877 | 0.2917 | 0.3000 |
VAV_MID WITH REHEAT | 97.16 | 97.16 | 33.61 | 33.61 | 97.1601 | 33.6095 | 97.1601 | 0.3459 | 0.3000 |
VAV_TOP WITH REHEAT | 10.66 | 10.66 | 5.79 | 5.79 | 10.6575 | 5.7910 | 10.6575 | 0.5434 | 0.3000 |
CAV_BAS | 5.92 | 5.92 | 1.20 | 1.20 | 5.9249 | 5.9249 | 5.9249 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.57 | 0.57 | 0.02 | 0.02 | 0.5720 | 0.5720 | 0.5720 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.46 | 5.46 | 0.16 | 0.16 | 5.4631 | 5.4631 | 5.4631 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.56 | 0.56 | 0.02 | 0.02 | 0.5585 | 0.5585 | 0.5585 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 16386.306 | 16386.306 | 1.978679 | 0.00014335 | 330.335 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 16386.31 | 16386.31 | 1.978679 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 16446.73 | 16446.73 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 392212.648 | 392212.648 | 19.346440 | 0.00343125 | 9242.711 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 392212.65 | 392212.65 | 19.346440 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 231996.31 | 0.00 | 393496.22 | 393496.22 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 79733.995 | 79733.995 | 2.886039 | 0.00069755 | 2104.639 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 79734.00 | 79734.00 | 2.886039 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 55833.44 | 0.00 | 80008.85 | 80008.85 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 9062.823 | 9062.823 | 0.327957 | 0.00007929 | 239.247 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9062.82 | 9062.82 | 0.327957 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00777253 | 41.3436 | 6348.19 | 0.00 | 9094.26 | 9094.26 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6630.452 | 6630.452 | 0.249657 | 0.00005801 | 171.987 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6630.45 | 6630.45 | 0.249657 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00781279 | 41.5550 | 4563.77 | 0.00 | 6650.76 | 6650.76 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 11368.612 | 11368.612 | 0.411714 | 0.00009946 | 300.010 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11368.61 | 11368.61 | 0.411714 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00786304 | 41.8187 | 7960.05 | 0.00 | 11407.28 | 11407.28 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 5557.471 | 5557.471 | 0.319577 | 0.00004862 | 125.785 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5557.47 | 5557.47 | 0.319577 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00756483 | 40.2526 | 2913.26 | 0.00 | 5576.42 | 5576.42 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 182872.227 | 182872.227 | 6.630850 | 0.00159985 | 4823.169 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 182872.23 | 182872.23 | 6.630850 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00788729 | 41.9461 | 127973.58 | 0.00 | 183474.70 | 183474.70 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 121417.218 | 121417.218 | 4.402794 | 0.00106221 | 3202.233 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 121417.22 | 121417.22 | 4.402794 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00788851 | 41.9526 | 84965.19 | 0.00 | 121816.58 | 121816.58 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 181200.148 | 181200.148 | 6.570095 | 0.00158522 | 4779.111 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 181200.15 | 181200.15 | 6.570095 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00788564 | 41.9375 | 126804.71 | 0.00 | 181797.42 | 181797.42 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 113412.906 | 113412.906 | 4.112001 | 0.00099219 | 2991.309 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 113412.91 | 113412.91 | 4.112001 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00787502 | 41.8818 | 79369.44 | 0.00 | 113787.24 | 113787.24 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 24371.278 | 24371.278 | 0.884135 | 0.00021321 | 642.633 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24371.28 | 24371.28 | 0.884135 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00790224 | 42.0247 | 17051.10 | 0.00 | 24450.50 | 24450.50 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 16072.104 | 16072.104 | 0.583081 | 0.00014061 | 423.789 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16072.10 | 16072.10 | 0.583081 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00790129 | 42.0197 | 11244.51 | 0.00 | 16124.30 | 16124.30 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 24162.503 | 24162.503 | 0.876549 | 0.00021138 | 637.132 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24162.50 | 24162.50 | 0.876549 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00790136 | 42.0201 | 16905.14 | 0.00 | 24241.08 | 24241.08 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 15469.515 | 15469.515 | 0.561191 | 0.00013533 | 407.910 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15469.52 | 15469.52 | 0.561191 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00789723 | 41.9985 | 10823.19 | 0.00 | 15519.82 | 15519.82 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 170803.668 | -999.000 | 10.487743 | 0.00726638 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 170803.67 | 170803.67 | 10.487743 | 26.82 | 14.06 | 0.00695019 | 10.67 | 7.93 | 0.00695019 | 35.10 | 0.00569938 | 15.77 | 24.2015 | 24.00 | 0.00737728 | 32.7238 | 112573.93 | 0.00 | 153532.89 | 153532.89 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 53572.940 | 53572.940 | 3.146323 | 0.00046868 | 876.662 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 53572.94 | 53572.94 | 3.146323 | -4.31 | -4.82 | 0.00288065 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 80.6716 | 21.33 | 0.00586981 | 30.6888 | 21785.27 | 0.00 | 49301.00 | 49301.00 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1628129.918 | -999.000 | 97.160113 | 0.06926441 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1628129.92 | 1628129.91 | 97.160113 | 27.17 | 14.16 | 0.00692715 | 10.55 | 7.86 | 0.00692715 | 35.10 | 0.00569938 | 15.77 | 26.1238 | 24.00 | 0.00741843 | 32.9042 | 1002661.70 | 0.00 | 1466423.32 | 1466423.32 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 492162.037 | 492162.037 | 29.148034 | 0.00430565 | 8059.701 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 492162.04 | 492162.04 | 29.148034 | -4.17 | -4.44 | 0.00306260 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 87.0795 | 21.00 | 0.00789419 | 41.9820 | 408394.87 | 0.00 | 453669.95 | 453669.95 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 171726.024 | -999.000 | 10.657508 | 0.00730562 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 171726.02 | 171726.02 | 10.657508 | 26.65 | 14.01 | 0.00695454 | 10.67 | 7.94 | 0.00695454 | 35.10 | 0.00569938 | 15.77 | 23.8160 | 24.00 | 0.00734891 | 32.5994 | 119854.46 | 0.00 | 154285.92 | 154285.92 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 49205.192 | 49205.192 | 3.197252 | 0.00043047 | 812.658 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 49205.19 | 49205.19 | 3.197252 | -2.66 | -2.96 | 0.00347950 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 79.3866 | 17.60 | 0.00781322 | 51.3592 | 44233.07 | 0.00 | 46163.78 | 46163.78 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 91227.727 | -999.000 | 5.924872 | 0.00388104 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 91227.73 | 91227.73 | 5.924872 | 26.39 | 14.07 | 0.00714156 | 11.12 | 8.32 | 0.00714156 | 34.43 | 0.00569833 | 15.56 | 20.2568 | 24.00 | 0.00757071 | 33.5718 | 59114.17 | 0.00 | 82706.60 | 82706.60 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 245298.436 | 245298.436 | 5.924872 | 0.00214598 | 5426.055 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 245298.44 | 245298.44 | 5.924872 | -1.60 | -4.13 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 20.2568 | 24.49 | 0.00234317 | 10.1704 | 0.00 | 0.00 | 203831.60 | 203831.60 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10205.485 | 5462.034 | 0.572047 | 0.00024993 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8668.69 | 8620.44 | -999.0 | 28.25 | 14.62 | 0.00704991 | 12.80 | 8.87 | 0.00700000 | 30.51 | 0.00569229 | 14.27 | -999.0000 | 27.00 | 0.00708805 | 26.3224 | 8187.79 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 97515.333 | 52176.071 | 5.463149 | 0.00238814 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 82839.08 | 82357.64 | -999.0 | 28.25 | 14.63 | 0.00705213 | 12.80 | 8.87 | 0.00700000 | 30.51 | 0.00569229 | 14.27 | -999.0000 | 27.00 | 0.00709219 | 26.3377 | 78188.38 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9966.774 | 5333.462 | 0.558509 | 0.00024409 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8466.37 | 8418.10 | -999.0 | 28.25 | 14.62 | 0.00705114 | 12.80 | 8.87 | 0.00700000 | 30.51 | 0.00569229 | 14.27 | -999.0000 | 27.00 | 0.00709027 | 26.3306 | 7993.99 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10205.485 | 10205.485 | 0.572047 | 0.00024993 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10205.49 | 10205.49 | 0.572047 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7328 | 26.72 | 0.00699997 | 26.4287 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 97515.333 | 97515.333 | 5.463149 | 0.00238814 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 97515.33 | 97515.33 | 5.463149 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.8615 | 24.44 | 0.00494585 | 21.4490 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9966.774 | 9966.774 | 0.558509 | 0.00024409 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9966.77 | 9966.77 | 0.558509 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7990 | 23.21 | 0.00280089 | 13.1215 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 745.232 | 745.232 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 745.23 | 745.23 | 0.572047 | -0.22 | -0.22 | 0.00687271 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7328 | 26.72 | 0.00699997 | 26.4287 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 7452.321 | 7452.321 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 7452.32 | 7452.32 | 5.463149 | -0.23 | -0.23 | 0.00487137 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.8615 | 24.44 | 0.00494585 | 21.4490 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 745.232 | 745.232 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 745.23 | 745.23 | 0.558509 | -0.22 | -2.69 | 0.00278808 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7990 | 23.21 | 0.00280089 | 13.1215 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 16386.306 | 16386.306 | 1.978679 | 0.00014335 | 330.335 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 0.7873 | 0.803184 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | Sensible | 16386.31 | 16386.31 | 1.0000 | 1.95970120 | 1.978679 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.14333993 | 60.00 | 32.22 | 27.78 | 0.000 | 16386.31 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 16446.73 | 16446.73 | 1.95970120 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 392212.648 | 392212.648 | 19.346440 | 0.00343125 | 9242.711 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 18.8453 | 19.224519 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 392212.65 | 392212.65 | 1.0000 | 19.16088671 | 19.346440 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 3.43089732 | 60.00 | 32.22 | 27.78 | 0.000 | 392212.65 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.81 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 231996.31 | 0.00 | 393496.22 | 393496.22 | 19.16088671 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.94 | 19.00 | 0.00800000 | 53596.3 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 79733.995 | 79733.995 | 2.886039 | 0.00069755 | 2104.639 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 3.8311 | 3.908206 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 79734.00 | 79734.00 | 1.0000 | 2.85835914 | 2.886039 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.69747662 | 60.00 | 32.22 | 27.78 | 0.000 | 79734.00 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 55833.44 | 0.00 | 80008.85 | 80008.85 | 2.85835914 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.26 | 0.00800000 | 61051.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9062.823 | 9062.823 | 0.327957 | 0.00007929 | 239.247 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 0.4355 | 0.444219 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9062.82 | 9062.82 | 1.0000 | 0.32481106 | 0.327957 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.07927744 | 60.00 | 32.22 | 27.78 | 0.000 | 9062.82 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00777253 | 21.00 | 0.00777253 | 41.3436 | 6348.19 | 0.00 | 9094.26 | 9094.26 | 0.32481106 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.26 | 21.26 | 0.00800000 | 61058.4 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6630.452 | 6630.452 | 0.249657 | 0.00005801 | 171.987 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 0.3186 | 0.324995 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6630.45 | 6630.45 | 1.0000 | 0.24726209 | 0.249657 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.05800017 | 60.00 | 32.22 | 27.78 | 0.000 | 6630.45 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00781279 | 21.00 | 0.00781279 | 41.5550 | 4563.77 | 0.00 | 6650.76 | 6650.76 | 0.24726209 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.18 | 20.94 | 0.00800000 | 59957.5 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11368.612 | 11368.612 | 0.411714 | 0.00009946 | 300.010 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 0.5462 | 0.557239 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11368.61 | 11368.61 | 1.0000 | 0.40776551 | 0.411714 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.09944744 | 60.00 | 32.22 | 27.78 | 0.000 | 11368.61 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00786304 | 21.00 | 0.00786304 | 41.8187 | 7960.05 | 0.00 | 11407.28 | 11407.28 | 0.40776551 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61034.9 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5557.471 | 5557.471 | 0.319577 | 0.00004862 | 125.785 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 0.2670 | 0.272403 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5557.47 | 5557.47 | 1.0000 | 0.31651147 | 0.319577 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.04861423 | 60.00 | 32.22 | 27.78 | 0.000 | 5557.47 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.86 | 0.00756483 | 21.00 | 0.00756483 | 40.2526 | 2913.26 | 0.00 | 5576.42 | 5576.42 | 0.31651147 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.08 | 18.06 | 0.00800000 | 50678.2 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 182872.227 | 182872.227 | 6.630850 | 0.00159985 | 4823.169 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 8.7867 | 8.963583 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 182872.23 | 182872.23 | 1.0000 | 6.56725301 | 6.630850 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 1.59968282 | 60.00 | 32.22 | 27.78 | 0.000 | 182872.23 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00788729 | 21.00 | 0.00788729 | 41.9461 | 127973.58 | 0.00 | 183474.70 | 183474.70 | 6.56725301 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60997.6 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 121417.218 | 121417.218 | 4.402794 | 0.00106221 | 3202.233 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 5.8339 | 5.951332 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 121417.22 | 121417.22 | 1.0000 | 4.36056604 | 4.402794 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 1.06210244 | 60.00 | 32.22 | 27.78 | 0.000 | 121417.22 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00788851 | 21.00 | 0.00788851 | 41.9526 | 84965.19 | 0.00 | 121816.58 | 121816.58 | 4.36056604 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60995.8 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 181200.148 | 181200.148 | 6.570095 | 0.00158522 | 4779.111 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 8.7064 | 8.881625 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 181200.15 | 181200.15 | 1.0000 | 6.50708018 | 6.570095 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 1.58505623 | 60.00 | 32.22 | 27.78 | 0.000 | 181200.15 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00788564 | 21.00 | 0.00788564 | 41.9375 | 126804.71 | 0.00 | 181797.42 | 181797.42 | 6.50708018 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60998.2 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 113412.906 | 113412.906 | 4.112001 | 0.00099219 | 2991.309 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 5.4493 | 5.558996 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 113412.91 | 113412.91 | 1.0000 | 4.07256236 | 4.112001 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.99208436 | 60.00 | 32.22 | 27.78 | 0.000 | 113412.91 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00787502 | 21.00 | 0.00787502 | 41.8818 | 79369.44 | 0.00 | 113787.24 | 113787.24 | 4.07256236 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60999.8 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24371.278 | 24371.278 | 0.884135 | 0.00021321 | 642.633 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 1.1710 | 1.194572 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 24371.28 | 24371.28 | 1.0000 | 0.87565536 | 0.884135 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.21318882 | 60.00 | 32.22 | 27.78 | 0.000 | 24371.28 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00790224 | 21.00 | 0.00790224 | 42.0247 | 17051.10 | 0.00 | 24450.50 | 24450.50 | 0.87565536 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.3 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16072.104 | 16072.104 | 0.583081 | 0.00014061 | 423.789 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 0.7722 | 0.787783 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16072.10 | 16072.10 | 1.0000 | 0.57748860 | 0.583081 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.14059143 | 60.00 | 32.22 | 27.78 | 0.000 | 16072.10 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00790129 | 21.00 | 0.00790129 | 42.0197 | 11244.51 | 0.00 | 16124.30 | 16124.30 | 0.57748860 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60981.2 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24162.503 | 24162.503 | 0.876549 | 0.00021138 | 637.132 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 1.1610 | 1.184338 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 24162.50 | 24162.50 | 1.0000 | 0.86814238 | 0.876549 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.21136255 | 60.00 | 32.22 | 27.78 | 0.000 | 24162.50 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00790136 | 21.00 | 0.00790136 | 42.0201 | 16905.14 | 0.00 | 24241.08 | 24241.08 | 0.86814238 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.8 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15469.515 | 15469.515 | 0.561191 | 0.00013533 | 407.910 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 0.7433 | 0.758247 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15469.52 | 15469.52 | 1.0000 | 0.55580881 | 0.561191 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.13532026 | 60.00 | 32.22 | 27.78 | 0.000 | 15469.52 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00789723 | 21.00 | 0.00789723 | 41.9985 | 10823.19 | 0.00 | 15519.82 | 15519.82 | 0.55580881 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.8 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 170803.668 | -999.000 | 10.487743 | 0.00726638 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7601 | 1004.8586 | 0.9904 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.487743 | 10.38715347 | 4197.9300 | 999.8980 | 87.70850572 | 12.27 | 6.67 | 5.60 | 2061887.34 | 8.2839 | 8.283851 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 170803.67 | 170803.67 | 1.0000 | 10.38715347 | 10.487743 | 26.82 | 14.06 | 0.00695019 | 44682.8 | 10.67 | 7.93 | 0.00695019 | 28239.1 | 7.26564164 | 6.67 | 12.27 | 5.60 | 22543.031 | 148260.64 | 35.10 | 0.00569938 | 15.77 | 2.53819000 | 24.2015 | 24.00 | 0.00737728 | 24.00 | 0.00737728 | 32.7238 | 112573.93 | 0.00 | 153532.89 | 153532.89 | 10.38715347 | 26.82 | 16.05 | 0.00695019 | 44682.8 | 12.30 | 10.29 | 0.00695019 | 29901.8 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 53572.940 | 53572.940 | 3.146323 | 0.00046868 | 876.662 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.487743 | 10.38715347 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 2.5741 | 2.625907 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 53572.94 | 53572.94 | 1.0000 | 3.11614604 | 3.146323 | -4.31 | -4.82 | 0.00288065 | 2851.5 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 0.46863164 | 60.00 | 32.22 | 27.78 | 0.000 | 53572.94 | -7.90 | 0.00234317 | -7.90 | 2.53819000 | 80.6716 | 10.68 | 0.00512393 | 21.33 | 0.00586981 | 30.6888 | 21785.27 | 0.00 | 49301.00 | 49301.00 | 3.11614604 | 2.80 | 0.35 | 0.00288065 | 10032.9 | 18.46 | 8.56 | 0.00288065 | 25854.0 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1628129.918 | -999.000 | 97.160113 | 0.06926441 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7172 | 1004.8586 | 0.9904 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 97.160113 | 96.22824045 | 4197.9300 | 999.8980 | 87.70850572 | 12.27 | 6.67 | 5.60 | 2061887.34 | 78.9631 | 78.963088 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1628129.92 | 1628129.91 | 1.0000 | 96.22824045 | 97.160113 | 27.17 | 14.16 | 0.00692715 | 44977.0 | 10.55 | 7.86 | 0.00692715 | 28057.6 | 69.25734477 | 6.67 | 12.27 | 5.60 | 220708.256 | 1407421.66 | 35.10 | 0.00569938 | 15.77 | 25.38195000 | 26.1238 | 24.00 | 0.00741843 | 24.00 | 0.00741843 | 32.9042 | 1002661.70 | 0.00 | 1466423.32 | 1466423.32 | 96.22824045 | 27.17 | 16.16 | 0.00692715 | 44977.0 | 12.20 | 10.22 | 0.00692715 | 29738.0 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 492162.037 | 492162.037 | 29.148034 | 0.00430565 | 8059.701 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 97.160113 | 96.22824045 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 23.6477 | 24.123594 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 492162.04 | 492162.04 | 1.0000 | 28.86847214 | 29.148034 | -4.17 | -4.44 | 0.00306260 | 3449.5 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 4.30520898 | 60.00 | 32.22 | 27.78 | 0.000 | 492162.04 | -7.90 | 0.00234317 | -7.90 | 25.38195000 | 87.0795 | 21.00 | 0.00791127 | 21.00 | 0.00789419 | 41.9820 | 408394.87 | 0.00 | 453669.95 | 453669.95 | 28.86847214 | 2.80 | 0.61 | 0.00306260 | 10488.9 | 18.35 | 8.72 | 0.00306260 | 26203.9 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 171726.024 | -999.000 | 10.657508 | 0.00730562 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7681 | 1004.8586 | 0.9904 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.657508 | 10.55529089 | 4197.9300 | 999.8980 | 87.70850572 | 12.27 | 6.67 | 5.60 | 2061887.34 | 8.3286 | 8.328584 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 171726.02 | 171726.02 | 1.0000 | 10.55529089 | 10.657508 | 26.65 | 14.01 | 0.00695454 | 44519.2 | 10.67 | 7.94 | 0.00695454 | 28250.0 | 7.30487680 | 6.67 | 12.27 | 5.60 | 22907.936 | 148818.09 | 35.10 | 0.00569938 | 15.77 | 2.53819000 | 23.8160 | 24.00 | 0.00734891 | 24.00 | 0.00734891 | 32.5994 | 119854.46 | 0.00 | 154285.92 | 154285.92 | 10.55529089 | 26.65 | 15.99 | 0.00695454 | 44519.2 | 12.29 | 10.29 | 0.00695454 | 29902.3 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 49205.192 | 49205.192 | 3.197252 | 0.00043047 | 812.658 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.657508 | 10.55529089 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 2.3642 | 2.411820 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 49205.19 | 49205.19 | 1.0000 | 3.16658727 | 3.197252 | -2.66 | -2.96 | 0.00347950 | 6008.2 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 0.43042457 | 60.00 | 32.22 | 27.78 | 0.000 | 49205.19 | -7.90 | 0.00234317 | -7.90 | 2.53819000 | 79.3866 | 17.50 | 0.00785577 | 17.60 | 0.00781322 | 51.3592 | 44233.07 | 0.00 | 46163.78 | 46163.78 | 3.16658727 | 2.80 | 1.21 | 0.00347950 | 11533.7 | 17.22 | 8.67 | 0.00347950 | 26112.1 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 91227.727 | -999.000 | 5.924872 | 0.00388104 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1158 | 1004.8586 | 0.9904 | CAV_BAS FAN | Fan:ConstantVolume | 5.924872 | 5.86804562 | 4197.9300 | 999.8980 | 87.70850572 | 12.27 | 6.67 | 5.60 | 2061887.34 | 4.4245 | 4.424477 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 91227.73 | 91227.73 | 1.0000 | 5.86804562 | 5.924872 | 26.39 | 14.07 | 0.00714156 | 44726.9 | 11.12 | 8.32 | 0.00714156 | 29180.4 | 3.88064250 | 6.67 | 12.27 | 5.60 | 10046.534 | 81181.19 | 34.43 | 0.00569833 | 15.56 | 1.20019084 | 20.2568 | 24.00 | 0.00757071 | 24.00 | 0.00757071 | 33.5718 | 59114.17 | 0.00 | 82706.60 | 82706.60 | 5.86804562 | 26.39 | 16.06 | 0.00714156 | 44726.9 | 12.54 | 10.60 | 0.00714156 | 30632.5 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 245298.436 | 245298.436 | 5.924872 | 0.00214598 | 5426.055 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | CAV_BAS FAN | Fan:ConstantVolume | 5.924872 | 5.86804562 | 4197.9300 | 999.8980 | 17.84646606 | 54.44 | 82.22 | 27.78 | 2081228.02 | 11.7862 | 12.023438 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 245298.44 | 245298.44 | 1.0000 | 5.86804562 | 5.924872 | -1.60 | -4.13 | 0.00234317 | 4245.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 2.14575882 | 60.00 | 32.22 | 27.78 | 0.000 | 245298.44 | -7.90 | 0.00234317 | -7.90 | 1.20019084 | 20.2568 | 0.00 | 0.00234317 | 24.49 | 0.00234317 | 10.1704 | 0.00 | 0.00 | 203831.60 | 203831.60 | 5.86804562 | 12.80 | 5.14 | 0.00234317 | 18777.8 | 47.22 | 19.12 | 0.00234317 | 53513.7 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10205.485 | 5462.034 | 0.572047 | 0.00024993 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9454 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8668.69 | 8620.44 | 0.8494 | -999.0 | -999.0 | 28.25 | 14.62 | 0.00704991 | 46383.3 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8668.69 | 30.51 | 0.00569229 | 14.27 | 0.01563279 | -999.0000 | 27.00 | 0.00708805 | 27.00 | 0.00708805 | 26.3224 | 8187.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 97515.333 | 52176.071 | 5.463149 | 0.00238814 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9496 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 82839.08 | 82357.64 | 0.8495 | -999.0 | -999.0 | 28.25 | 14.63 | 0.00705213 | 46393.5 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 82839.08 | 30.51 | 0.00569229 | 14.27 | 0.15632792 | -999.0000 | 27.00 | 0.00709219 | 27.00 | 0.00709219 | 26.3377 | 78188.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9966.774 | 5333.462 | 0.558509 | 0.00024409 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9477 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8466.37 | 8418.10 | 0.8495 | -999.0 | -999.0 | 28.25 | 14.62 | 0.00705114 | 46388.8 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8466.37 | 30.51 | 0.00569229 | 14.27 | 0.01563279 | -999.0000 | 27.00 | 0.00709027 | 27.00 | 0.00709027 | 26.3306 | 7993.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10205.485 | 10205.485 | 0.572047 | 0.00024993 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10205.49 | 10205.49 | 1.0000 | 0.56656088 | 0.572047 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10205.49 | -7.90 | 0.00234317 | -7.90 | 0.01563279 | 2.7328 | 0.00 | 0.00699997 | 26.72 | 0.00699997 | 26.4287 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 97515.333 | 97515.333 | 5.463149 | 0.00238814 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 97515.33 | 97515.33 | 1.0000 | 5.41075114 | 5.463149 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 97515.33 | -7.90 | 0.00234317 | -7.90 | 0.15632792 | 2.8615 | 0.00 | 0.00494585 | 24.44 | 0.00494585 | 21.4490 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9966.774 | 9966.774 | 0.558509 | 0.00024409 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9966.77 | 9966.77 | 1.0000 | 0.55315231 | 0.558509 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9966.77 | -7.90 | 0.00234317 | -7.90 | 0.01563279 | 2.7990 | 0.00 | 0.00280089 | 23.21 | 0.00280089 | 13.1215 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 745.232 | 745.232 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.572047 | 0.56656088 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 745.23 | 745.23 | 1.0000 | 0.56656088 | 0.572047 | -0.22 | -0.22 | 0.00687271 | 16968.6 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 745.23 | -7.90 | 0.00234317 | -7.90 | 0.01563279 | 2.7328 | 0.00 | 0.00699997 | 26.72 | 0.00699997 | 26.4287 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7452.321 | 7452.321 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.463149 | 5.41075114 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 7452.32 | 7452.32 | 1.0000 | 5.41075114 | 5.463149 | -0.23 | -0.23 | 0.00487137 | 11953.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7452.32 | -7.90 | 0.00234317 | -7.90 | 0.15632792 | 2.8615 | 0.00 | 0.00494585 | 24.44 | 0.00494585 | 21.4490 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 745.232 | 745.232 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.558509 | 0.55315231 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 745.23 | 745.23 | 1.0000 | 0.55315231 | 0.558509 | -0.22 | -2.69 | 0.00278808 | 6749.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 745.23 | -7.90 | 0.00234317 | -7.90 | 0.01563279 | 2.7990 | 0.00 | 0.00280089 | 23.21 | 0.00280089 | 13.1215 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.49 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 97.16 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.66 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.92 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | BASEMENT_DCV | 0.002360 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2438.17 | 1601.33 | 212.67 |
CORE_BOTTOM | 2077.50 | 1735.33 | 259.00 |
CORE_MID | 1606.83 | 3455.00 | 288.17 |
CORE_TOP | 2139.83 | 3716.83 | 789.83 |
PERIMETER_BOT_ZN_3 | 1912.50 | 3385.00 | 207.67 |
PERIMETER_BOT_ZN_2 | 2346.17 | 2880.17 | 326.50 |
PERIMETER_BOT_ZN_1 | 2584.17 | 2139.83 | 323.50 |
PERIMETER_BOT_ZN_4 | 2943.67 | 1706.83 | 339.50 |
PERIMETER_MID_ZN_3 | 2771.17 | 3824.17 | 1347.00 |
PERIMETER_MID_ZN_2 | 2374.67 | 2863.33 | 854.50 |
PERIMETER_MID_ZN_1 | 2624.00 | 2461.67 | 507.33 |
PERIMETER_MID_ZN_4 | 2639.17 | 3248.50 | 772.33 |
PERIMETER_TOP_ZN_3 | 3517.33 | 3949.00 | 2110.50 |
PERIMETER_TOP_ZN_2 | 3368.67 | 3429.00 | 1553.83 |
PERIMETER_TOP_ZN_1 | 2836.50 | 2818.00 | 919.50 |
PERIMETER_TOP_ZN_4 | 3218.50 | 3483.67 | 1433.00 |
DATACENTER_BOT_ZN_6 | 5943.00 | 327.50 | 327.50 |
DATACENTER_MID_ZN_6 | 5830.17 | 38.17 | 38.17 |
DATACENTER_TOP_ZN_6 | 5198.00 | 208.67 | 100.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 81.67 | 0.00 | 4.17 |
CORE_BOTTOM | 0.00 | 3.17 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 4.00 | 0.00 | 1.67 |
PERIMETER_BOT_ZN_2 | 0.00 | 47.17 | 0.00 | 47.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 94.50 | 0.00 | 90.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 135.33 | 0.00 | 52.67 |
PERIMETER_MID_ZN_3 | 3.17 | 1.17 | 0.00 | 0.67 |
PERIMETER_MID_ZN_2 | 2.00 | 52.83 | 0.00 | 52.00 |
PERIMETER_MID_ZN_1 | 0.50 | 177.83 | 0.00 | 175.67 |
PERIMETER_MID_ZN_4 | 0.33 | 43.00 | 0.00 | 24.50 |
PERIMETER_TOP_ZN_3 | 44.17 | 10.67 | 8.50 | 7.17 |
PERIMETER_TOP_ZN_2 | 27.50 | 58.67 | 0.00 | 53.00 |
PERIMETER_TOP_ZN_1 | 18.17 | 82.67 | 0.17 | 76.67 |
PERIMETER_TOP_ZN_4 | 18.83 | 48.50 | 0.00 | 26.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 10.17 | 0.00 | 4.17 |
DATACENTER_MID_ZN_6 | 0.00 | 7.17 | 0.00 | 3.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 8.83 | 0.00 | 3.33 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 47.00 | 538.00 | 8.50 | 358.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 1.346 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 1.018 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.769 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.740 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.951 | 0.011 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.638 | 0.011 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 1.606 | 0.011 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 2.171 | 0.011 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.787 | 0.025 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.498 | 0.028 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 1.469 | 0.025 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.486 | 0.026 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.792 | 0.031 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.606 | 0.032 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 1.426 | 0.031 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.521 | 0.032 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.11 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 0.847 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.011 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.110 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.011 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 783.68 | 0.239 | ||
Total Facility | 1029.47 | 2493.19 | 126016.35 | 46320.38 | 1.3878 | 157.549 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 57805685.30 | 0.00 | 57805685.30 | 0.00 | 57805685.30 | 29876159.83 | 3690.50 | 1215.07 | 3854.43 | 491.85 |
CORE_BOTTOM | 45255870.18 | 0.00 | 45255870.18 | 0.00 | 45255870.18 | 33990283.35 | 4465.23 | 36.31 | 4258.46 | 675.23 |
CORE_MID | 0.32E+09 | 0.00 | 0.32E+09 | 0.00 | 0.32E+09 | 0.34E+09 | 5702.80 | 35.98 | 3021.22 | 228.18 |
CORE_TOP | 31125640.87 | 0.00 | 31125640.87 | 0.00 | 31125640.87 | 33990283.35 | 5967.71 | 29.51 | 2762.77 | 327.43 |
PERIMETER_BOT_ZN_3 | 5328826.88 | 0.00 | 5328826.88 | 108997.33 | 5437824.21 | 4267819.30 | 4301.80 | 68.54 | 4389.66 | 675.23 |
PERIMETER_BOT_ZN_2 | 5857027.31 | 0.00 | 5857027.31 | 72664.84 | 5929692.15 | 2750345.05 | 3119.79 | 7.92 | 5632.29 | 675.23 |
PERIMETER_BOT_ZN_1 | 8666878.82 | 0.00 | 8666878.82 | 108997.33 | 8775876.15 | 4267912.63 | 3612.74 | 69.66 | 5077.59 | 675.23 |
PERIMETER_BOT_ZN_4 | 7793602.38 | 0.00 | 7793602.38 | 72664.84 | 7866267.22 | 2750345.05 | 3062.71 | 1.19 | 5696.10 | 675.23 |
PERIMETER_MID_ZN_3 | 41349951.17 | 0.00 | 41349951.17 | 255627.27 | 41605578.44 | 42678193.03 | 5027.25 | 53.85 | 3678.90 | 228.18 |
PERIMETER_MID_ZN_2 | 53992437.08 | 0.00 | 53992437.08 | 170418.06 | 54162855.14 | 27503450.52 | 3735.56 | 5.05 | 5019.39 | 1137.18 |
PERIMETER_MID_ZN_1 | 75751805.84 | 0.00 | 75751805.84 | 255627.27 | 76007433.11 | 42679126.28 | 4125.73 | 495.94 | 4138.33 | 228.18 |
PERIMETER_MID_ZN_4 | 50351386.37 | 0.00 | 50351386.37 | 170418.06 | 50521804.43 | 27503450.52 | 3720.80 | 6.24 | 5032.97 | 228.18 |
PERIMETER_TOP_ZN_3 | 4176497.86 | 0.00 | 4176497.86 | 317386.02 | 4493883.87 | 4267819.30 | 5085.43 | 38.68 | 3635.89 | 327.43 |
PERIMETER_TOP_ZN_2 | 5406774.47 | 0.00 | 5406774.47 | 211590.53 | 5618365.00 | 2750345.05 | 3825.43 | 1.05 | 4933.52 | 327.43 |
PERIMETER_TOP_ZN_1 | 7387451.09 | 0.00 | 7387451.09 | 317386.02 | 7704837.10 | 4267912.63 | 3871.31 | 9.82 | 4878.87 | 327.43 |
PERIMETER_TOP_ZN_4 | 5175859.49 | 0.00 | 5175859.49 | 211590.53 | 5387450.02 | 2750345.05 | 3808.64 | 5.52 | 4945.84 | 327.43 |
DATACENTER_BOT_ZN_6 | 244303.03 | 0.00 | 244303.03 | 0.00 | 244303.03 | 389144.62 | 4419.00 | 504.00 | 3837.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2443030.26 | 0.00 | 2443030.26 | 0.00 | 2443030.26 | 3891446.16 | 4419.00 | 504.00 | 3837.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244303.03 | 0.00 | 244303.03 | 0.00 | 244303.03 | 389144.62 | 4419.00 | 504.00 | 3837.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8423799.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 0.56E+10 | 0.00 | 0.56E+10 | 9942184.14 | 0.57E+10 | 0.50E+10 | 8760.00 | 2160.15 | 5995.38 | 1906.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.4946 | 0.0000 | 2.4946 | 0.0000 | 2.4946 | 0.9949 | 1274.15 | 1211.79 | 3457.06 |
CORE_BOTTOM | 1.9060 | 0.0000 | 1.9060 | 0.0000 | 1.9060 | 1.0778 | 2257.77 | 33.45 | 3651.78 |
CORE_MID | 14.4078 | 0.0000 | 14.4078 | 0.0000 | 14.4078 | 10.7782 | 3069.41 | 35.69 | 2837.90 |
CORE_TOP | 1.3875 | 0.0000 | 1.3875 | 0.0000 | 1.3875 | 1.0778 | 3325.81 | 29.51 | 2587.67 |
PERIMETER_BOT_ZN_3 | 0.2236 | 0.0000 | 0.2236 | 0.0025 | 0.2261 | 0.1353 | 2088.35 | 65.36 | 3789.29 |
PERIMETER_BOT_ZN_2 | 0.2483 | 0.0000 | 0.2483 | 0.0017 | 0.2500 | 0.0872 | 968.79 | 6.77 | 4967.44 |
PERIMETER_BOT_ZN_1 | 0.3781 | 0.0000 | 0.3781 | 0.0025 | 0.3806 | 0.1353 | 1406.82 | 65.25 | 4470.93 |
PERIMETER_BOT_ZN_4 | 0.3291 | 0.0000 | 0.3291 | 0.0017 | 0.3308 | 0.0872 | 920.94 | 0.74 | 5021.32 |
PERIMETER_MID_ZN_3 | 1.8534 | 0.0000 | 1.8534 | 0.0059 | 1.8593 | 1.3533 | 2394.95 | 53.40 | 3494.66 |
PERIMETER_MID_ZN_2 | 2.2739 | 0.0000 | 2.2739 | 0.0043 | 2.2781 | 0.8721 | 1107.56 | 3.12 | 3923.32 |
PERIMETER_MID_ZN_1 | 3.4577 | 0.0000 | 3.4577 | 0.0059 | 3.4637 | 1.3533 | 1492.63 | 495.88 | 3954.50 |
PERIMETER_MID_ZN_4 | 2.2556 | 0.0000 | 2.2556 | 0.0040 | 2.2595 | 0.8721 | 1095.63 | 4.04 | 4843.32 |
PERIMETER_TOP_ZN_3 | 0.1867 | 0.0000 | 0.1867 | 0.0074 | 0.1941 | 0.1353 | 2444.44 | 38.52 | 3460.04 |
PERIMETER_TOP_ZN_2 | 0.2437 | 0.0000 | 0.2437 | 0.0049 | 0.2487 | 0.0872 | 1187.89 | 0.75 | 4754.36 |
PERIMETER_TOP_ZN_1 | 0.3358 | 0.0000 | 0.3358 | 0.0074 | 0.3431 | 0.1353 | 1229.66 | 9.82 | 4703.52 |
PERIMETER_TOP_ZN_4 | 0.2311 | 0.0000 | 0.2311 | 0.0049 | 0.2360 | 0.0872 | 1175.51 | 3.86 | 4763.63 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0130 | 1602.00 | 504.00 | 3837.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1296 | 1602.00 | 504.00 | 3837.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0130 | 1602.00 | 504.00 | 3837.00 |
DATACENTER_BASEMENT_ZN_6 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.2805 | 5943.00 | 0.00 | 0.00 |
Total Facility | 251.6127 | 0.0000 | 251.6127 | 0.2339 | 251.8465 | 157.9346 | 5943.00 | 2141.21 | 5127.78 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 71510493.20 | 0.00 | 71510493.20 | 48026705.38 | 3216.34 | 14.29 | 5529.36 | 675.23 |
VAV_MID WITH REHEAT | 0.53E+09 | 0.00 | 0.53E+09 | 0.48E+09 | 3820.58 | 9.32 | 4930.09 | 228.18 |
VAV_TOP WITH REHEAT | 52255246.61 | 0.00 | 52255246.61 | 48026705.38 | 3872.80 | 6.19 | 4881.01 | 327.43 |
CAV_BAS | 56702161.89 | 0.00 | 56702161.89 | 29876159.83 | 4905.51 | 5.55 | 3848.95 | 491.75 |
AIRLOOP DATACENTER BOT | 239639.23 | 0.00 | 239639.23 | 389144.62 | 4923.00 | 1512.00 | 2325.00 | 0.00 |
AIRLOOP DATACENTER MID | 2396392.27 | 0.00 | 2396392.27 | 3891446.16 | 4923.00 | 1512.00 | 2325.00 | 0.00 |
AIRLOOP DATACENTER TOP | 239639.23 | 0.00 | 239639.23 | 389144.62 | 4923.00 | 1512.00 | 2325.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.0263 | 0.0000 | 3.0263 | 1.5229 | 1017.65 | 11.30 | 4914.05 |
VAV_MID WITH REHEAT | 23.9466 | 0.0000 | 23.9466 | 15.2292 | 1188.03 | 9.16 | 4745.81 |
VAV_TOP WITH REHEAT | 2.3392 | 0.0000 | 2.3392 | 1.5229 | 1231.06 | 6.19 | 4705.75 |
CAV_BAS | 2.4470 | 0.0000 | 2.4470 | 0.9949 | 2485.94 | 1.81 | 3455.26 |
AIRLOOP DATACENTER BOT | 0.0112 | 0.0000 | 0.0112 | 0.0130 | 2106.00 | 1512.00 | 2325.00 |
AIRLOOP DATACENTER MID | 0.1120 | 0.0000 | 0.1120 | 0.1296 | 2106.00 | 1512.00 | 2325.00 |
AIRLOOP DATACENTER TOP | 0.0112 | 0.0000 | 0.0112 | 0.0130 | 2106.00 | 1512.00 | 2325.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.17 | 4268.53 | 0.00 | 0.00 | 0.00 | 1429.43 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.17 | 3577.67 | 0.00 | 0.00 | 0.00 | 1546.78 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.03 | 3236.96 | 0.00 | 0.00 | 0.00 | 1971.25 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 0.00 | 3961.66 | 0.00 | 0.00 | 0.00 | 1209.89 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 4.3540 | 0.0000 | 0.0000 | 0.0000 | 1.6375 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 34.8856 | 0.0000 | 0.0000 | 0.0000 | 16.4725 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 3.6840 | 0.0000 | 0.0000 | 0.0000 | 1.6160 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 0.0000 | 3.8378 | 0.0000 | 0.0000 | 0.0000 | 1.0169 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0153 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1534 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0153 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 7 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1352 |
Defaulted Fields | 1168 |
Fields with Defaults | 3820 |
Autosized Fields | 313 |
Autosizable Fields | 391 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 23665.43 | 287617.65 | 22-JAN-05:00 | 1632266.59 | 02-AUG-15:30 |
Electricity:Building | 16697.36 | 216770.18 | 04-SEP-17:10 | 977223.71 | 01-DEC-17:00 |
Electricity:Zone:BASEMENT | 559.97 | 14115.26 | 01-JAN-00:10 | 25295.37 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16697.36 | 216770.18 | 04-SEP-17:10 | 977223.71 | 01-DEC-17:00 |
InteriorLights:Electricity | 2020.96 | 9514.02 | 01-JAN-10:20 | 198852.03 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:BASEMENT | 135.58 | 657.72 | 01-JAN-00:10 | 11837.83 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2020.96 | 9514.02 | 01-JAN-10:20 | 198852.03 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity | 2020.96 | 9514.02 | 01-JAN-10:20 | 198852.03 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 135.58 | 657.72 | 01-JAN-00:10 | 11837.83 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2020.96 | 9514.02 | 01-JAN-10:20 | 198852.03 | 13-NOV-17:00 |
Electricity:Zone:CORE_BOTTOM | 411.37 | 5043.91 | 01-JAN-00:10 | 27837.83 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4113.71 | 50438.97 | 01-JAN-00:10 | 278377.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1217.58 | 5906.80 | 01-JAN-00:10 | 106312.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1217.58 | 5906.80 | 01-JAN-00:10 | 106312.04 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 411.37 | 5043.90 | 01-JAN-00:10 | 27837.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 45.23 | 594.46 | 09-APR-17:10 | 3495.41 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.87 | 35.29 | 01-JAN-10:20 | 1334.85 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.87 | 35.29 | 01-JAN-10:20 | 1334.85 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 29.12 | 383.09 | 30-APR-17:10 | 2252.57 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.69 | 22.74 | 01-JAN-07:50 | 860.23 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.69 | 22.74 | 01-JAN-07:50 | 860.23 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 45.08 | 594.47 | 26-MAR-17:10 | 3495.47 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.71 | 35.29 | 01-JAN-07:50 | 1334.88 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.71 | 35.29 | 01-JAN-07:50 | 1334.88 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 29.07 | 383.09 | 12-MAR-17:10 | 2252.56 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.64 | 22.74 | 01-JAN-10:10 | 860.23 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.64 | 22.74 | 01-JAN-10:10 | 860.23 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 452.35 | 5944.59 | 09-APR-17:10 | 34954.06 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 88.69 | 352.88 | 01-JAN-10:10 | 13348.54 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 88.69 | 352.88 | 01-JAN-10:10 | 13348.54 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 291.21 | 3830.92 | 30-APR-17:10 | 22525.72 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 56.86 | 227.41 | 01-JAN-07:50 | 8602.31 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 56.86 | 227.41 | 01-JAN-07:50 | 8602.31 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 450.81 | 5944.68 | 12-MAR-17:10 | 34954.68 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 87.15 | 352.89 | 01-JAN-07:50 | 13348.83 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 87.15 | 352.89 | 01-JAN-07:50 | 13348.83 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 290.73 | 3830.90 | 12-MAR-17:10 | 22525.63 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 56.38 | 227.41 | 01-JAN-10:00 | 8602.31 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 56.38 | 227.41 | 01-JAN-10:00 | 8602.31 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 45.23 | 594.46 | 09-APR-17:10 | 3495.41 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.87 | 35.29 | 01-JAN-10:10 | 1334.85 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.87 | 35.29 | 01-JAN-10:10 | 1334.85 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 29.12 | 383.09 | 30-APR-17:10 | 2252.57 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.69 | 22.74 | 01-JAN-07:50 | 860.23 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.69 | 22.74 | 01-JAN-07:50 | 860.23 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 45.08 | 594.47 | 12-MAR-17:10 | 3495.47 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.72 | 35.29 | 01-JAN-07:50 | 1334.88 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.72 | 35.29 | 01-JAN-07:50 | 1334.88 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 29.07 | 383.09 | 12-MAR-17:10 | 2252.56 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.64 | 22.74 | 01-JAN-10:00 | 860.23 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.64 | 22.74 | 01-JAN-10:00 | 860.23 | 13-NOV-17:00 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7533.08 | 95093.58 | 01-JAN-00:10 | 382970.28 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 38.23 | 185.45 | 01-JAN-00:10 | 3337.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 38.23 | 185.45 | 01-JAN-00:10 | 3337.76 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.14 | 1964.44 | 01-JAN-00:10 | 8079.39 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1571.44 | 19644.38 | 01-JAN-00:10 | 80793.90 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 32.64 | 158.32 | 01-JAN-00:10 | 2849.68 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 32.64 | 158.32 | 01-JAN-00:10 | 2849.68 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.14 | 1964.44 | 01-JAN-00:10 | 8079.39 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1558.24 | 885.61 | 22-JAN-07:00 | 337271.60 | 05-SEP-13:10 |
HeatRejection:Electricity | 262.02 | 55.71 | 17-JAN-07:20 | 42924.61 | 06-JUN-13:20 |
General:HeatRejection:Electricity | 262.02 | 55.71 | 17-JAN-07:20 | 42924.61 | 06-JUN-13:20 |
Electricity:HVAC | 1882.96 | 10153.42 | 22-JAN-07:40 | 253554.25 | 07-AUG-15:40 |
ExteriorEquipment:Electricity | 3258.17 | 45245.36 | 01-JAN-00:10 | 185192.48 | 08-DEC-08:20 |
Transformer:ExteriorEquipment:Electricity | 54.48 | 979.82 | 01-JAN-00:10 | 3387.38 | 05-DEC-17:00 |
ElectricityPurchased:Facility | 23665.43 | 287617.65 | 22-JAN-05:00 | 1632266.59 | 02-AUG-15:30 |
ElectricityPurchased:Plant | 23665.43 | 287617.65 | 22-JAN-05:00 | 1632266.59 | 02-AUG-15:30 |
Cogeneration:ElectricityPurchased | 23665.43 | 287617.65 | 22-JAN-05:00 | 1632266.59 | 02-AUG-15:30 |
General:Cogeneration:ElectricityPurchased | 23665.43 | 287617.65 | 22-JAN-05:00 | 1632266.59 | 02-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 23665.43 | 287617.65 | 22-JAN-05:00 | 1632266.59 | 02-AUG-15:30 |
ElectricityNet:Plant | 23665.43 | 287617.65 | 22-JAN-05:00 | 1632266.59 | 02-AUG-15:30 |
Cogeneration:ElectricityNet | 23665.43 | 287617.65 | 22-JAN-05:00 | 1632266.59 | 02-AUG-15:30 |
General:Cogeneration:ElectricityNet | 23665.43 | 287617.65 | 22-JAN-05:00 | 1632266.59 | 02-AUG-15:30 |
Fans:Electricity | 1397.04 | 7385.66 | 01-JAN-00:10 | 217050.77 | 07-AUG-15:40 |
General:Fans:Electricity | 1397.04 | 7385.66 | 01-JAN-00:10 | 217050.77 | 07-AUG-15:40 |
ExteriorLights:Electricity | 323.19 | 0.00 | 01-JAN-07:20 | 37611.08 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 323.19 | 0.00 | 01-JAN-07:20 | 37611.08 | 01-JAN-06:10 |
ComputerHVAC:ExteriorEquipment:Electricity | 1349.07 | 17083.47 | 01-JAN-00:10 | 68333.87 | 31-MAR-23:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 1256.34 | 561.27 | 17-JAN-07:10 | 250464.06 | 31-JUL-15:00 |
General:Cooling:Electricity | 1256.34 | 561.27 | 17-JAN-07:10 | 250464.06 | 31-JUL-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 471.31 | 727.82 | 17-JAN-04:50 | 61255.83 | 21-JUL-16:00 |
General:Pumps:Electricity | 471.31 | 727.82 | 17-JAN-04:50 | 61255.83 | 21-JUL-16:00 |
WIRED_LTG_ELECTRICITY | 56.79 | 0.00 | 01-JAN-00:10 | 5587.74 | 13-NOV-17:10 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1401.74 | 5695.87 | 06-FEB-05:30 | 709192.31 | 21-JAN-07:10 |
NaturalGas:Plant | 1401.74 | 5695.87 | 06-FEB-05:30 | 709192.31 | 21-JAN-07:10 |
Heating:NaturalGas | 708.77 | 0.00 | 01-JAN-00:10 | 681631.09 | 21-JAN-07:10 |
Boiler:Heating:NaturalGas | 708.77 | 0.00 | 01-JAN-00:10 | 681631.09 | 21-JAN-07:10 |
WaterSystems:NaturalGas | 692.97 | 5695.87 | 17-JAN-04:20 | 81624.73 | 03-FEB-12:40 |
Water Heater:WaterSystems:NaturalGas | 692.97 | 5695.87 | 17-JAN-04:20 | 81624.73 | 03-FEB-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 8208.84 | 1958.01 | 17-JAN-07:10 | 1707275.76 | 05-SEP-13:10 |
PlantLoopCoolingDemand:HVAC | 8208.84 | 1958.01 | 17-JAN-07:10 | 1707275.76 | 05-SEP-13:10 |
CoolingCoils:PlantLoopCoolingDemand | 8208.84 | 1958.01 | 17-JAN-07:10 | 1707275.76 | 05-SEP-13:10 |
DistrictCooling:Facility | 7193.90 | 87071.76 | 22-JAN-06:00 | 370603.48 | 21-AUG-16:00 |
DistrictCooling:HVAC | 7193.90 | 87071.76 | 22-JAN-06:00 | 370603.48 | 21-AUG-16:00 |
Cooling:DistrictCooling | 7193.90 | 87071.76 | 22-JAN-06:00 | 370603.48 | 21-AUG-16:00 |
General:Cooling:DistrictCooling | 7193.90 | 87071.76 | 22-JAN-06:00 | 370603.48 | 21-AUG-16:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 8241.48 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
Water:Plant | 8241.48 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 8241.48 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
MainsWater:Plant | 8241.48 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 5961.31 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
General:HeatRejection:Water | 5961.31 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
HeatRejection:MainsWater | 5961.31 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
General:HeatRejection:MainsWater | 5961.31 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 46894.97 | 96199.12 | 22-JAN-05:40 | 8112663.19 | 05-SEP-13:00 |
EnergyTransfer:Building | 18737.62 | 88748.02 | 22-JAN-03:10 | 1532302.24 | 07-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 628.05 | 0.00 | 01-JAN-00:10 | 67671.73 | 10-OCT-05:30 |
Heating:EnergyTransfer | 156.78 | 0.00 | 01-JAN-16:20 | 333361.57 | 17-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.06 | 0.00 | 01-JAN-00:10 | 17515.35 | 22-JUL-16:10 |
General:Heating:EnergyTransfer | 156.78 | 0.00 | 01-JAN-16:20 | 333361.57 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.06 | 0.00 | 01-JAN-00:10 | 17515.35 | 22-JUL-16:10 |
Cooling:EnergyTransfer | 18580.84 | 87938.92 | 22-JAN-05:40 | 1532302.24 | 07-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 623.99 | 0.00 | 01-JAN-00:10 | 67671.73 | 10-OCT-05:30 |
General:Cooling:EnergyTransfer | 18580.84 | 87938.92 | 22-JAN-05:40 | 1532302.24 | 07-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 623.99 | 0.00 | 01-JAN-00:10 | 67671.73 | 10-OCT-05:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 599.51 | 0.00 | 01-JAN-00:10 | 49887.88 | 21-AUG-09:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 599.51 | 0.00 | 01-JAN-00:10 | 49887.88 | 21-AUG-09:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 599.51 | 0.00 | 01-JAN-00:10 | 49887.88 | 21-AUG-09:10 |
EnergyTransfer:Zone:CORE_MID | 4217.95 | 0.00 | 01-JAN-00:10 | 386587.53 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4217.95 | 0.00 | 01-JAN-00:10 | 386587.53 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4217.95 | 0.00 | 01-JAN-00:10 | 386587.53 | 05-SEP-13:10 |
EnergyTransfer:Zone:CORE_TOP | 396.42 | 0.00 | 01-JAN-00:10 | 53785.81 | 26-DEC-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 4.35 | 0.00 | 01-JAN-00:10 | 53785.81 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 4.35 | 0.00 | 01-JAN-00:10 | 53785.81 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 392.07 | 0.00 | 01-JAN-00:10 | 46710.27 | 07-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 392.07 | 0.00 | 01-JAN-00:10 | 46710.27 | 07-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 72.07 | 0.00 | 01-JAN-00:10 | 10047.81 | 31-JUL-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 438.03 | 21-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 438.03 | 21-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 72.07 | 0.00 | 01-JAN-00:10 | 10047.81 | 31-JUL-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 72.07 | 0.00 | 01-JAN-00:10 | 10047.81 | 31-JUL-12:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 75.80 | 0.00 | 01-JAN-00:10 | 13139.62 | 05-JUL-07:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1130.32 | 21-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1130.32 | 21-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 75.79 | 0.00 | 01-JAN-00:10 | 13139.62 | 05-JUL-07:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 75.79 | 0.00 | 01-JAN-00:10 | 13139.62 | 05-JUL-07:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 118.72 | 0.00 | 01-JAN-00:10 | 16180.33 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 2723.79 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 2723.79 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 118.69 | 0.00 | 01-JAN-00:10 | 16180.33 | 28-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 118.69 | 0.00 | 01-JAN-00:10 | 16180.33 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 108.71 | 0.00 | 01-JAN-00:10 | 16482.97 | 21-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 108.71 | 0.00 | 01-JAN-00:10 | 16482.97 | 21-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 108.71 | 0.00 | 01-JAN-00:10 | 16482.97 | 21-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 541.30 | 0.00 | 01-JAN-00:10 | 92267.21 | 29-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.82 | 0.00 | 01-JAN-00:10 | 76584.45 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.82 | 0.00 | 01-JAN-00:10 | 76584.45 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 515.48 | 0.00 | 01-JAN-00:10 | 92267.21 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 515.48 | 0.00 | 01-JAN-00:10 | 92267.21 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 683.99 | 0.00 | 01-JAN-00:10 | 134214.90 | 05-JUL-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 10.50 | 0.00 | 01-JAN-00:10 | 51414.23 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 10.50 | 0.00 | 01-JAN-00:10 | 51414.23 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 673.49 | 0.00 | 01-JAN-00:10 | 134214.90 | 05-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 673.49 | 0.00 | 01-JAN-00:10 | 134214.90 | 05-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1052.55 | 0.00 | 01-JAN-00:10 | 162219.95 | 28-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 5.08 | 0.00 | 01-JAN-00:10 | 53681.09 | 18-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 5.08 | 0.00 | 01-JAN-00:10 | 53681.09 | 18-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1047.47 | 0.00 | 01-JAN-00:10 | 162219.95 | 28-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1047.47 | 0.00 | 01-JAN-00:10 | 162219.95 | 28-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 680.68 | 0.00 | 01-JAN-00:10 | 148430.02 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 5.79 | 0.00 | 01-JAN-00:10 | 44951.25 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 5.79 | 0.00 | 01-JAN-00:10 | 44951.25 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 674.89 | 0.00 | 01-JAN-00:10 | 148430.02 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 674.89 | 0.00 | 01-JAN-00:10 | 148430.02 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 61.93 | 0.00 | 01-JAN-00:10 | 12534.97 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.04 | 0.00 | 01-JAN-00:10 | 12534.97 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.04 | 0.00 | 01-JAN-00:10 | 12534.97 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 48.89 | 0.00 | 01-JAN-00:10 | 10613.41 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 48.89 | 0.00 | 01-JAN-00:10 | 10613.41 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 70.12 | 0.00 | 01-JAN-00:10 | 13769.50 | 05-JUL-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 5.25 | 0.00 | 01-JAN-00:10 | 11619.68 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 5.25 | 0.00 | 01-JAN-00:10 | 11619.68 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 64.87 | 0.00 | 01-JAN-00:10 | 13769.50 | 05-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 64.87 | 0.00 | 01-JAN-00:10 | 13769.50 | 05-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 102.54 | 0.00 | 01-JAN-00:10 | 17674.64 | 28-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 4.63 | 0.00 | 01-JAN-00:10 | 14487.26 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 4.63 | 0.00 | 01-JAN-00:10 | 14487.26 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 97.92 | 0.00 | 01-JAN-00:10 | 17674.64 | 28-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 97.92 | 0.00 | 01-JAN-00:10 | 17674.64 | 28-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 69.28 | 0.00 | 01-JAN-00:10 | 15827.98 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 3.95 | 0.00 | 01-JAN-00:10 | 9959.52 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 3.95 | 0.00 | 01-JAN-00:10 | 9959.52 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 65.33 | 0.00 | 01-JAN-00:10 | 15827.98 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 65.33 | 0.00 | 01-JAN-00:10 | 15827.98 | 28-JUN-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 61.59 | 0.00 | 01-JAN-00:10 | 10023.02 | 21-AUG-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.45 | 0.00 | 01-JAN-00:10 | 3811.56 | 10-DEC-11:10 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.45 | 0.00 | 01-JAN-00:10 | 3811.56 | 10-DEC-11:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 60.14 | 0.00 | 01-JAN-00:10 | 10023.02 | 21-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 60.14 | 0.00 | 01-JAN-00:10 | 10023.02 | 21-AUG-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 435.90 | 0.00 | 01-JAN-00:10 | 69832.43 | 05-JUL-15:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 48.94 | 0.00 | 01-JAN-00:10 | 39757.68 | 06-FEB-15:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 48.94 | 0.00 | 01-JAN-00:10 | 39757.68 | 06-FEB-15:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 386.96 | 0.00 | 01-JAN-00:10 | 69832.43 | 05-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 386.96 | 0.00 | 01-JAN-00:10 | 69832.43 | 05-JUL-15:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 96.08 | 0.00 | 01-JAN-00:10 | 22131.90 | 28-JUN-13:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.01 | 0.00 | 01-JAN-00:10 | 17651.00 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.01 | 0.00 | 01-JAN-00:10 | 17651.00 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 73.07 | 0.00 | 01-JAN-00:10 | 22131.90 | 28-JUN-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 73.07 | 0.00 | 01-JAN-00:10 | 22131.90 | 28-JUN-13:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.63 | 746.98 | 21-JAN-08:00 | 8246.09 | 16-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.63 | 746.98 | 21-JAN-08:00 | 8246.09 | 16-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.63 | 746.98 | 21-JAN-08:00 | 8246.09 | 16-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1239.42 | 6.38 | 22-JAN-13:10 | 77713.05 | 16-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.12 | 0.00 | 01-JAN-00:10 | 2027.16 | 17-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.12 | 0.00 | 01-JAN-00:10 | 2027.16 | 17-JAN-05:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1239.30 | 0.00 | 16-JAN-23:00 | 77713.05 | 16-APR-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1239.30 | 0.00 | 16-JAN-23:00 | 77713.05 | 16-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 116.05 | 1.17 | 28-JAN-16:50 | 7764.10 | 16-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.75 | 0.00 | 01-JAN-16:00 | 659.01 | 16-JAN-18:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.75 | 0.00 | 01-JAN-16:00 | 659.01 | 16-JAN-18:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 115.30 | 0.00 | 01-JAN-00:10 | 7764.10 | 16-APR-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 115.30 | 0.00 | 01-JAN-00:10 | 7764.10 | 16-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7169.33 | 87071.76 | 22-JAN-06:00 | 368004.50 | 21-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7169.33 | 87071.76 | 22-JAN-06:00 | 368004.50 | 21-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7169.33 | 87071.76 | 22-JAN-06:00 | 368004.50 | 21-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 917.63 | 0.00 | 01-JAN-00:10 | 592939.73 | 06-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 400.27 | 0.00 | 01-JAN-00:10 | 50679.46 | 03-FEB-12:50 |
WaterSystems:PlantLoopHeatingDemand | 400.27 | 0.00 | 01-JAN-00:10 | 50679.46 | 03-FEB-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 400.27 | 0.00 | 01-JAN-00:10 | 50679.46 | 03-FEB-12:50 |
EnergyTransfer:HVAC | 8294.76 | 5789.45 | 22-JAN-07:40 | 1698528.13 | 05-SEP-13:10 |
HeatingCoils:EnergyTransfer | 517.36 | 0.00 | 01-JAN-00:10 | 576155.32 | 06-FEB-07:10 |
PlantLoopHeatingDemand:HVAC | 517.36 | 0.00 | 01-JAN-00:10 | 576155.32 | 06-FEB-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 517.36 | 0.00 | 01-JAN-00:10 | 576155.32 | 06-FEB-07:10 |
CoolingCoils:EnergyTransfer | 7777.40 | 1396.74 | 17-JAN-07:10 | 1698528.13 | 05-SEP-13:10 |
DistrictHeating:Facility | 0.00 | 0.00 | 01-JAN-01:10 | 12.11 | 01-MAR-00:30 |
DistrictHeating:HVAC | 0.00 | 0.00 | 01-JAN-01:10 | 12.11 | 01-MAR-00:30 |
Heating:DistrictHeating | 0.00 | 0.00 | 01-JAN-01:10 | 12.11 | 01-MAR-00:30 |
General:Heating:DistrictHeating | 0.00 | 0.00 | 01-JAN-01:10 | 12.11 | 01-MAR-00:30 |
EnergyTransfer:Plant | 19862.59 | 0.00 | 01-JAN-00:10 | 5314925.64 | 05-SEP-13:00 |
LoopToLoop:EnergyTransfer | 6343.58 | 0.00 | 01-JAN-00:10 | 1674610.08 | 05-SEP-13:10 |
WaterSystems:EnergyTransfer | 400.27 | 0.00 | 01-JAN-00:10 | 50679.46 | 03-FEB-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 400.27 | 0.00 | 01-JAN-00:10 | 50679.46 | 03-FEB-12:50 |
Boilers:EnergyTransfer | 512.62 | 0.00 | 01-JAN-00:10 | 567347.86 | 21-JAN-07:10 |
Chillers:EnergyTransfer | 5890.60 | 0.00 | 01-JAN-00:10 | 1684443.15 | 05-SEP-13:10 |
HeatRejection:EnergyTransfer | 6715.50 | 0.00 | 01-JAN-00:10 | 1924758.03 | 05-SEP-13:10 |
General:HeatRejection:EnergyTransfer | 6715.50 | 0.00 | 01-JAN-00:10 | 1924758.03 | 05-SEP-13:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.065 | -623.985 | 0.000 | 0.000 | 92.617 | 135.577 | 424.397 | 0.000 | 0.000 | 0.000 | 0.006 | 0.000 | 0.000 | 0.000 | 0.000 | -32.672 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -599.503 | 0.000 | 0.000 | 83.428 | 121.758 | 289.614 | 0.000 | 0.000 | 0.000 | 104.703 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 0.000 | -4217.920 | 0.000 | 0.000 | 841.232 | 1217.578 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -737.017 |
CORE_TOP | 0.000 | 0.000 | 4.345 | -392.069 | 0.000 | 0.000 | 86.804 | 121.758 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -110.451 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.001 | -72.072 | 0.000 | 0.000 | 10.703 | 8.868 | 36.365 | 29.193 | 0.000 | 0.047 | 31.467 | 0.000 | -43.351 | 0.000 | -1.222 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.006 | -75.794 | 0.000 | 0.000 | 6.874 | 5.687 | 23.435 | 69.958 | 0.000 | 0.032 | 0.003 | 0.000 | -26.597 | 0.000 | -0.813 | -2.789 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.029 | -118.691 | 0.000 | 0.000 | 10.539 | 8.714 | 36.366 | 125.146 | 0.000 | 0.046 | 0.001 | 0.000 | -40.898 | 0.000 | -1.267 | -19.983 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -108.707 | 0.000 | 0.000 | 6.796 | 5.639 | 23.435 | 63.679 | 0.000 | 0.029 | 41.385 | 0.000 | -31.350 | 0.000 | -0.906 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 25.818 | -515.475 | 0.000 | 0.000 | 111.657 | 88.694 | 363.654 | 302.613 | 0.000 | 1.112 | 43.894 | 0.000 | -395.901 | 0.000 | -26.067 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 10.504 | -673.486 | 0.000 | 0.000 | 51.840 | 56.860 | 234.352 | 700.203 | 0.000 | 0.711 | 0.002 | 0.000 | -253.142 | 0.000 | -18.198 | -109.645 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 5.081 | -1047.447 | 0.000 | 0.000 | 105.860 | 87.151 | 363.660 | 1247.520 | 0.000 | 1.044 | 0.014 | 0.000 | -401.401 | 0.000 | -29.155 | -332.314 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 5.792 | -674.871 | 0.000 | 0.000 | 71.034 | 56.378 | 234.351 | 646.958 | 0.000 | 0.677 | 0.011 | 0.000 | -278.874 | 0.000 | -18.919 | -42.526 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 13.042 | -48.885 | 0.000 | 0.000 | 11.354 | 8.869 | 36.365 | 30.685 | 0.000 | 0.128 | 0.002 | 0.000 | -37.059 | 0.000 | -3.014 | -11.486 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 5.249 | -64.871 | 0.000 | 0.000 | 7.151 | 5.686 | 23.435 | 70.367 | 0.000 | 0.083 | 0.002 | 0.000 | -23.929 | 0.000 | -2.126 | -21.045 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 4.626 | -97.914 | 0.000 | 0.000 | 10.778 | 8.715 | 36.366 | 125.240 | 0.000 | 0.124 | 0.004 | 0.000 | -37.969 | 0.000 | -3.410 | -46.556 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 3.948 | -65.328 | 0.000 | 0.000 | 7.216 | 5.638 | 23.435 | 64.855 | 0.000 | 0.081 | 0.002 | 0.000 | -26.470 | 0.000 | -2.222 | -11.153 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -139.626 | 0.000 | 0.000 | 0.950 | 3.264 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -18.468 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.123 | -1239.301 | 0.000 | 0.000 | 9.501 | 32.637 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -341.765 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.751 | -115.298 | 0.000 | 0.000 | 0.951 | 3.264 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -43.549 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | -7169.327 | 0.000 | 0.000 | 0.000 | 0.000 | 20.569 | 38.227 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -384.326 |
GROUNDFLOOR_PLENUM | 1.451 | -60.135 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.087 | 61.207 | 0.000 | 0.000 | 0.000 | -2.611 | 0.000 |
MIDFLOOR_PLENUM | 48.943 | -386.959 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.615 | 381.241 | 0.000 | 0.000 | 0.000 | -44.839 | -0.005 |
TOPFLOOR_PLENUM | 23.007 | -73.072 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.133 | 54.672 | 0.000 | 0.000 | 0.000 | -4.739 | -0.001 |
Total Facility | 73.401 | -7689.494 | 83.379 | -10891.241 | 0.000 | 0.000 | 1547.855 | 2020.960 | 14676.396 | 3476.418 | 0.000 | 5.950 | 718.613 | 0.000 | -1596.941 | 0.000 | -159.506 | -2265.752 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 26-DEC-04:01 | 0.00 | 0.00 | 0.00 | -99505.94 | 0.00 | 0.00 | 0.00 | 657.72 | 13457.54 | 0.00 | 0.00 | 0.00 | 85390.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 10-OCT-03:02 | 0.00 | 0.00 | 0.00 | -81657.77 | 0.00 | 0.00 | 0.00 | 590.68 | 5937.65 | 0.00 | 0.00 | 0.00 | 75129.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 06-SEP-04:03 | 0.00 | 0.00 | 0.00 | -715951.47 | 0.00 | 0.00 | 0.00 | 11812.12 | 59376.23 | 0.00 | 0.00 | 0.00 | 644763.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 17-JUL-03:02 | 0.00 | 0.00 | 0.00 | -73166.21 | 0.00 | 0.00 | 0.00 | 590.68 | 5937.62 | 0.00 | 0.00 | 0.00 | 66637.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 02-JUL-17:31 | 0.00 | 0.00 | 0.00 | -15109.26 | 0.00 | 0.00 | 0.00 | 35.29 | 559.17 | 4911.33 | 0.00 | 38.39 | 9565.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 03-SEP-08:21 | 0.00 | 0.00 | 0.00 | -19701.71 | 0.00 | 0.00 | 21.12 | 22.74 | 464.11 | 15532.83 | 0.00 | 0.00 | 3666.81 | 0.00 | -0.00 | 0.00 | -5.89 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-12:41 | 0.00 | 0.00 | 0.00 | -21106.66 | 0.00 | 0.00 | 33.21 | 35.29 | 720.19 | 21413.32 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -16.27 | -1079.08 |
PERIMETER_BOT_ZN_4 | 11-JUN-17:11 | 0.00 | 0.00 | 0.00 | -26797.96 | 0.00 | 0.00 | 0.00 | 22.74 | 360.35 | 16823.34 | 0.00 | 0.00 | 9595.48 | 0.00 | -0.00 | 0.00 | -3.95 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUL-18:12 | 0.00 | 0.00 | 0.00 | -143943.32 | 0.00 | 0.00 | 0.00 | 352.88 | 5591.71 | 56501.20 | 0.00 | 1381.71 | 80115.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-08:51 | 0.00 | 0.00 | 0.00 | -221852.59 | 0.00 | 0.00 | 184.38 | 227.41 | 4641.14 | 150877.99 | 0.00 | 0.00 | 66091.81 | 0.00 | -0.00 | 0.00 | -170.14 | 0.00 |
PERIMETER_MID_ZN_1 | 01-OCT-12:21 | 0.00 | 0.00 | 0.00 | -210104.99 | 0.00 | 0.00 | 296.82 | 352.89 | 7201.95 | 214965.60 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -174.39 | -12537.88 |
PERIMETER_MID_ZN_4 | 04-JUL-16:51 | 0.00 | 0.00 | 0.00 | -243448.18 | 0.00 | 0.00 | 152.23 | 227.41 | 4641.11 | 173098.68 | 0.00 | 1087.82 | 64240.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 25-JUN-17:21 | 0.00 | 0.00 | 0.00 | -16825.53 | 0.00 | 0.00 | 0.00 | 35.29 | 559.17 | 5603.96 | 0.00 | 138.28 | 10488.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 25-JUN-08:61 | 0.00 | 0.00 | 0.00 | -21237.27 | 0.00 | 0.00 | 20.61 | 22.74 | 464.11 | 15511.69 | 0.00 | 0.00 | 5245.77 | 0.00 | -0.00 | 0.00 | -27.66 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-OCT-13:12 | 0.00 | 0.00 | 0.00 | -21703.61 | 0.00 | 0.00 | 28.60 | 35.29 | 720.19 | 19766.23 | 0.00 | 0.00 | 1159.26 | 0.00 | -0.00 | 0.00 | -5.96 | 0.00 |
PERIMETER_TOP_ZN_4 | 25-JUN-16:41 | 0.00 | 0.00 | 0.00 | -26439.99 | 0.00 | 0.00 | 14.67 | 22.74 | 464.11 | 16763.35 | 0.00 | 57.13 | 9117.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 16-APR-18:20 | 0.00 | 0.00 | 0.00 | -8249.41 | 0.00 | 0.00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 439.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 16-APR-17:42 | 0.00 | 0.00 | 0.00 | -77713.05 | 0.00 | 0.00 | 0.00 | 158.32 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -389.50 |
DATACENTER_TOP_ZN_6 | 16-APR-17:42 | 0.00 | 0.00 | 0.00 | -7764.10 | 0.00 | 0.00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -46.16 |
DATACENTER_BASEMENT_ZN_6 | 21-AUG-16:00 | 0.00 | -368004.49 | 0.00 | 0.00 | 0.00 | 0.00 | 2183.10 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17148.89 |
GROUNDFLOOR_PLENUM | 05-JUL-05:15 | 0.00 | -12946.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12962.49 | 0.00 | -0.00 | 0.00 | -15.66 | 0.00 |
MIDFLOOR_PLENUM | 17-JUL-05:03 | 0.00 | -74146.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74375.59 | 0.00 | -0.00 | 0.00 | -229.13 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-13:30 | 0.00 | -22126.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 | 22076.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-AUG-05:02 | 0.00 | -355094.00 | 0.00 | -1441993.47 | 0.00 | 0.00 | 15504.20 | 22094.05 | 616289.16 | 0.00 | 0.00 | 0.00 | 1199601.22 | 0.00 | -55065.24 | 0.00 | -1335.92 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 22-JUL-15:02 | 0.00 | 0.00 | 19666.85 | 0.00 | 0.00 | 0.00 | 1040.26 | 1973.00 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -36137.65 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 17-JAN-04:11 | 0.00 | 0.00 | 67593.13 | 0.00 | 0.00 | 0.00 | 0.00 | 590.68 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -74121.44 |
PERIMETER_BOT_ZN_3 | 21-JAN-06:01 | 0.00 | 0.00 | 2702.00 | 0.00 | 0.00 | 0.00 | 140.46 | 148.31 | 960.25 | 0.00 | 0.00 | 0.00 | 327.23 | 0.00 | -4278.25 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 21-JAN-06:01 | 0.00 | 0.00 | 5180.72 | 0.00 | 0.00 | 0.00 | 92.08 | 95.58 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2818.27 | 0.00 | 0.00 | -3168.92 |
PERIMETER_BOT_ZN_1 | 19-JAN-06:01 | 0.00 | 0.00 | 9373.41 | 0.00 | 0.00 | 0.00 | 144.33 | 148.32 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3544.91 | 0.00 | -9.87 | -7071.54 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 17-JAN-05:01 | 0.00 | 0.00 | 108725.61 | 0.00 | 0.00 | 0.00 | 0.00 | 1483.13 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -34482.16 | 0.00 | -6317.03 | -76865.16 |
PERIMETER_MID_ZN_2 | 17-JAN-05:01 | 0.00 | 0.00 | 123192.27 | 0.00 | 0.00 | 0.00 | 0.00 | 955.79 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -23139.49 | 0.00 | -4301.87 | -101511.37 |
PERIMETER_MID_ZN_1 | 18-JAN-05:01 | 0.00 | 0.00 | 129795.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1483.16 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -32828.91 | 0.00 | -3570.12 | -102335.70 |
PERIMETER_MID_ZN_4 | 06-FEB-05:01 | 0.00 | 0.00 | 118270.72 | 0.00 | 0.00 | 0.00 | 0.00 | 955.79 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25826.70 | 0.00 | -4103.90 | -94100.56 |
PERIMETER_TOP_ZN_3 | 06-FEB-04:11 | 0.00 | 0.00 | 14224.10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.17 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3227.99 | 0.00 | -610.20 | -11205.64 |
PERIMETER_TOP_ZN_2 | 17-JAN-04:11 | 0.00 | 0.00 | 16187.78 | 0.00 | 0.00 | 0.00 | 0.00 | 47.80 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1957.32 | 0.00 | -515.98 | -14242.75 |
PERIMETER_TOP_ZN_1 | 17-JAN-04:11 | 0.00 | 0.00 | 16929.46 | 0.00 | 0.00 | 0.00 | 0.00 | 74.17 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2911.35 | 0.00 | -772.09 | -14065.76 |
PERIMETER_TOP_ZN_4 | 06-FEB-04:11 | 0.00 | 0.00 | 16791.49 | 0.00 | 0.00 | 0.00 | 0.00 | 47.80 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2263.72 | 0.00 | -427.59 | -14628.44 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 17-JAN-05:17 | 0.00 | 0.00 | 2027.16 | 0.00 | 0.00 | 0.00 | 0.00 | 316.62 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21829.84 |
DATACENTER_TOP_ZN_6 | 16-JAN-18:30 | 0.00 | 0.00 | 659.01 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2623.45 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 11-DEC-04:01 | 10865.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -296.42 | -10568.79 |
MIDFLOOR_PLENUM | 12-MAR-16:21 | 87957.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -861.30 | -87096.61 |
TOPFLOOR_PLENUM | 06-FEB-05:13 | 20669.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -960.55 | -19709.10 |
Total Facility | 17-JAN-05:01 | -348730.74 | 228164.48 | 601911.48 | -228164.48 | 0.00 | 0.00 | 0.00 | 22094.05 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -139452.01 | 0.00 | -38306.48 | -329941.53 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.6124 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.4877 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 109.1649 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 97.1601 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.3927 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.6575 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.9249 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.9249 | 0.2026 | 1.0000 | Not calculated | 1.2002 | 0.2026 | ||
AIRLOOP DATACENTER BOT | 0.5720 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5720 | 0.0273 | 1.0000 | Not calculated | 0.0156 | 0.0273 | ||
AIRLOOP DATACENTER MID | 5.4631 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.4631 | 0.0286 | 1.0000 | Not calculated | 0.1563 | 0.0286 | ||
AIRLOOP DATACENTER TOP | 0.5585 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5585 | 0.0280 | 1.0000 | Not calculated | 0.0156 | 0.0280 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.8062 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.0589 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 54.5825 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 29.6916 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.6963 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.0828 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.9249 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.9249 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2026 | ||
AIRLOOP DATACENTER BOT | 0.5720 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5720 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0273 | ||
AIRLOOP DATACENTER MID | 5.4631 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.4631 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0286 | ||
AIRLOOP DATACENTER TOP | 0.5585 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5585 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0280 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.002360 | 149.6021 | 0.000305 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.002360 | 1.9486 | 0.000305 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.002360 | 19.4861 | 0.000305 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.002360 | 1.9486 | 0.000305 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.002360 | 149.60 | 0.000305 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BOT | 0.002360 | 1.95 | 0.000305 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.002360 | 19.49 | 0.000305 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.002360 | 1.95 | 0.000305 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.9249 | 5.9249 | 5.9249 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.3828 | 6.3828 | 1.9787 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 59.7112 | 59.7112 | 19.3464 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9989 | 5.9989 | 1.9856 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0716 | 1.0716 | 0.2486 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2483 | 1.2483 | 0.2497 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3118 | 1.3118 | 0.2624 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5979 | 1.5979 | 0.3196 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.8792 | 9.8792 | 2.4303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.1434 | 13.1434 | 2.6287 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.3969 | 12.3969 | 2.4794 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.0342 | 14.0342 | 2.8068 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1517 | 1.1517 | 0.2488 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3350 | 1.3350 | 0.2670 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3902 | 1.3902 | 0.2780 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5169 | 1.5169 | 0.3034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5720 | 0.5720 | 0.5720 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.4631 | 5.4631 | 5.4631 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5585 | 0.5585 | 0.5585 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.6124 | 10.4877 | 11.6124 | 3.0589 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 109.1649 | 97.1601 | 109.1649 | 29.6916 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.3927 | 10.6575 | 11.3927 | 3.0828 | 0.0000 | 1.0000 |
CAV_BAS | 5.9249 | 5.9249 | 5.9249 | 5.9249 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5720 | 0.5720 | 0.5720 | 0.5720 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.4631 | 5.4631 | 5.4631 | 5.4631 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5585 | 0.5585 | 0.5585 | 0.5585 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.9249 | 5.9249 | 5.9249 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1914 | 3.1914 | 1.9787 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 29.8556 | 29.8556 | 19.3464 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9995 | 2.9995 | 1.9856 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5358 | 0.5358 | 0.2486 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6241 | 0.6241 | 0.2497 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6559 | 0.6559 | 0.2624 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7989 | 0.7989 | 0.3196 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9396 | 4.9396 | 2.4303 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.5717 | 6.5717 | 2.6287 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1985 | 6.1985 | 2.4794 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.0171 | 7.0171 | 2.8068 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5758 | 0.5758 | 0.2488 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6675 | 0.6675 | 0.2670 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6951 | 0.6951 | 0.2780 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7584 | 0.7584 | 0.3034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5720 | 0.5720 | 0.5720 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.4631 | 5.4631 | 5.4631 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5585 | 0.5585 | 0.5585 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.8062 | 3.0589 | 3.0589 | 3.0589 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 54.5825 | 29.6916 | 29.6916 | 29.6916 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.6963 | 3.0828 | 3.0828 | 3.0828 | 0.0000 | 1.0000 |
CAV_BAS | 5.9249 | 5.9249 | 5.9249 | 5.9249 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5720 | 0.5720 | 0.5720 | 0.5720 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.4631 | 5.4631 | 5.4631 | 5.4631 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5585 | 0.5585 | 0.5585 | 0.5585 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 8.50 |
Number of hours cooling loads not met | 358.50 |
Number of hours not met | 367.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 |
Heating -- Boiler | 0.00 | 0.00 | 708.77 | 681631.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1256.34 | 250464.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7193.90 | 370603.48 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2020.96 | 198852.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 323.19 | 37611.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.48 | 3387.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ComputerHVAC | 1349.07 | 68333.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 1397.04 | 217050.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 471.31 | 61255.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 262.02 | 42924.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 692.97 | 81624.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 23665.43 |
Natural Gas | 0.00 | 1401.74 |
Additional | 0.00 | 7193.90 |
Total | 14676.40 | 32261.07 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 43.63 |
Space Heating | 0.00 |
Space Cooling | 27.12 |
Fans (All) | 30.16 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 510.91 |
Subtotal | 510.91 |
Natural Gas [MJ/m2] | |
Space Heating | 15.30 |
Service Water Heating | 14.96 |
Miscellaneous (All) | 30.26 |
Subtotal | 30.26 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.26 |
Space Heating | 2.20 |
Space Cooling | 26.19 |
Fans (All) | 4.33 |
Service Water Heating | 2.15 |
Receptacle Equipment | 45.49 |
Miscellaneous | 13.37 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2362. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8595.67 | 164.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8746.00 | 14.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8698.17 | 61.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8712.83 | 47.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8577.17 | 182.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8679.33 | 80.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8711.00 | 49.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8665.33 | 94.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8742.83 | 17.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8667.17 | 92.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8711.33 | 48.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8651.83 | 108.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8755.67 | 4.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8648.00 | 112.00 | 0.00 | 0.00 | 0.00 |
Min | 8577.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 182.83 | 0.00 | 0.00 | 0.00 |
Average | 8712.62 | 47.38 | 0.00 | 0.00 | 0.00 |
Sum | 200390.33 | 1089.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368024.50 | 591.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 103395.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368024.50 | 591.50 | 0.00 | 0.00 | 0.00 |
Average | 80309.20 | 25.72 | 0.00 | 0.00 | 0.00 |
Sum | 1847111.50 | 591.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8468.33 | 291.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8681.00 | 79.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8674.50 | 85.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8680.50 | 79.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8648.33 | 111.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8656.17 | 103.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8628.83 | 131.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8478.17 | 281.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8679.67 | 80.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8598.50 | 161.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8628.50 | 131.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8576.33 | 183.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8663.83 | 96.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8585.17 | 174.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8621.83 | 138.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8576.50 | 183.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8612.17 | 147.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8687.50 | 72.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8518.17 | 241.83 | 0.00 | 0.00 | 0.00 |
Min | 8468.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 291.67 | 0.00 | 0.00 | 0.00 |
Average | 8639.30 | 120.70 | 0.00 | 0.00 | 0.00 |
Sum | 198704.00 | 2776.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 367708.33 | 907.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330648.00 | 165.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330711.00 | 102.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330713.00 | 100.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 103395.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367708.33 | 907.67 | 0.00 | 0.00 | 0.00 |
Average | 80279.49 | 55.42 | 0.00 | 0.00 | 0.00 |
Sum | 1846428.33 | 1274.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:12
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.451263E+11 | 96079.45 | 02-JAN-04:01 | -1.8 | -3.6 | 0.566820E+10 | 7499.05 | 13-JAN-10:20 | 4.63 | 1.40 |
February | 0.412829E+11 | 95709.72 | 13-FEB-04:12 | 1.10 | -1.6 | 0.514248E+10 | 7499.06 | 01-FEB-10:00 | 1.10 | -1.6 |
March | 0.507331E+11 | 94938.96 | 27-MAR-03:02 | 5.50 | 0.89 | 0.613884E+10 | 7499.00 | 02-MAR-14:09 | 5.50 | 0.89 |
April | 0.490997E+11 | 96031.11 | 03-APR-03:02 | 9.22 | 2.19 | 0.545595E+10 | 7499.01 | 26-APR-13:20 | 24.80 | 9.90 |
May | 0.514072E+11 | 90367.51 | 08-MAY-03:02 | 11.78 | 4.09 | 0.590805E+10 | 7579.14 | 22-MAY-09:50 | 24.13 | 14.54 |
June | 0.534415E+11 | 90431.24 | 20-JUN-03:02 | 10.78 | 4.69 | 0.588901E+10 | 7524.83 | 12-JUN-09:00 | 10.78 | 4.69 |
July | 0.554158E+11 | 80936.43 | 24-JUL-03:02 | 22.80 | 14.96 | 0.548194E+10 | 7503.63 | 17-JUL-09:09 | 22.80 | 14.96 |
August | 0.612174E+11 | 81674.88 | 29-AUG-03:02 | 16.10 | 12.92 | 0.614799E+10 | 7559.33 | 28-AUG-09:00 | 16.10 | 12.92 |
September | 0.554090E+11 | 86787.53 | 25-SEP-04:33 | 11.50 | 9.68 | 0.546107E+10 | 7572.41 | 25-SEP-09:00 | 21.10 | 13.60 |
October | 0.572091E+11 | 96421.87 | 23-OCT-03:02 | 8.22 | 7.00 | 0.567979E+10 | 7592.33 | 10-OCT-09:00 | 8.22 | 7.00 |
November | 0.534212E+11 | 96358.15 | 06-NOV-04:03 | 2.62 | -1.0 | 0.562059E+10 | 7498.88 | 08-NOV-10:30 | 13.60 | 6.17 |
December | 0.502257E+11 | 99506.48 | 26-DEC-04:01 | 0.32 | -0.9 | 0.547607E+10 | 7498.98 | 15-DEC-10:09 | 0.32 | -0.9 |
Annual Sum or Average | 0.623989E+12 | 0.680700E+11 | ||||||||
Minimum of Months | 0.412829E+11 | 80936.43 | -1.8 | -3.6 | 0.514248E+10 | 7498.88 | 0.32 | -1.6 | ||
Maximum of Months | 0.612174E+11 | 99506.48 | 22.80 | 14.96 | 0.614799E+10 | 7592.33 | 24.80 | 14.96 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351877E+11 | 79998.77 | 02-JAN-04:01 | -1.8 | -3.6 | 0.505997E+10 | 6734.70 | 25-JAN-10:09 | 5.37 | 0.26 |
February | 0.351833E+11 | 77998.49 | 21-FEB-05:01 | 2.38 | 0.37 | 0.460072E+10 | 6734.73 | 15-FEB-10:09 | 2.38 | 0.37 |
March | 0.485980E+11 | 77652.34 | 06-MAR-05:01 | -0.5 | -2.7 | 0.549909E+10 | 6734.68 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.542047E+11 | 80188.60 | 24-APR-03:02 | 5.18 | 2.43 | 0.488243E+10 | 6734.75 | 17-APR-13:00 | 5.18 | 2.43 |
May | 0.496572E+11 | 80784.94 | 30-MAY-03:02 | 14.82 | 11.26 | 0.528584E+10 | 6734.97 | 11-MAY-09:09 | 14.82 | 11.26 |
June | 0.572387E+11 | 81363.13 | 05-JUN-03:02 | 15.00 | 13.28 | 0.526890E+10 | 6734.83 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.626860E+11 | 77325.47 | 10-JUL-05:04 | 20.10 | 15.68 | 0.489545E+10 | 6734.73 | 28-JUL-09:30 | 25.25 | 16.67 |
August | 0.683911E+11 | 73702.45 | 07-AUG-05:03 | 18.90 | 13.67 | 0.549697E+10 | 6735.72 | 28-AUG-13:39 | 23.30 | 16.88 |
September | 0.501024E+11 | 80281.51 | 18-SEP-03:02 | 14.90 | 11.31 | 0.488470E+10 | 6734.80 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.500654E+11 | 81648.50 | 10-OCT-03:02 | 14.82 | 11.26 | 0.507881E+10 | 6734.79 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.458073E+11 | 79880.82 | 13-NOV-04:02 | 0.00 | -1.8 | 0.502727E+10 | 6734.69 | 27-NOV-10:09 | 1.28 | -3.1 |
December | 0.423839E+11 | 79675.90 | 26-DEC-04:01 | 0.32 | -0.9 | 0.490004E+10 | 6734.74 | 26-DEC-10:09 | 2.38 | 0.81 |
Annual Sum or Average | 0.599506E+12 | 0.608802E+11 | ||||||||
Minimum of Months | 0.351833E+11 | 73702.45 | -1.8 | -3.6 | 0.460072E+10 | 6734.68 | 1.28 | -3.1 | ||
Maximum of Months | 0.683911E+11 | 81648.50 | 20.10 | 15.68 | 0.549909E+10 | 6735.72 | 26.70 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242329E+11 | 32835.33 | 06-JAN-06:02 | -1.2 | -3.4 | 0.485853E+10 | 6734.70 | 13-JAN-10:20 | 4.63 | 1.40 |
February | 0.233414E+11 | 65564.13 | 15-FEB-06:02 | 6.93 | 2.40 | 0.449228E+10 | 6734.69 | 24-FEB-10:09 | 3.07 | 0.76 |
March | 0.320848E+11 | 66413.10 | 17-MAR-05:03 | 7.02 | 1.62 | 0.545107E+10 | 6734.69 | 01-MAR-10:09 | 7.02 | 1.62 |
April | 0.349103E+11 | 70841.15 | 03-APR-05:02 | 7.85 | 1.31 | 0.486414E+10 | 6734.67 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.403018E+11 | 71170.20 | 27-MAY-05:02 | 11.70 | 9.43 | 0.527460E+10 | 6734.94 | 11-MAY-09:09 | 11.70 | 9.43 |
June | 0.444337E+11 | 71487.60 | 06-JUN-05:02 | 12.38 | 10.89 | 0.526338E+10 | 6734.84 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.455286E+11 | 69027.86 | 08-JUL-04:03 | 16.20 | 14.71 | 0.489099E+10 | 6734.76 | 18-JUL-09:39 | 25.37 | 17.15 |
August | 0.475830E+11 | 71252.39 | 11-AUG-04:03 | 17.02 | 14.97 | 0.549340E+10 | 6735.74 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.406932E+11 | 71607.36 | 06-SEP-04:03 | 15.00 | 14.26 | 0.487631E+10 | 6734.77 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.362992E+11 | 71350.80 | 03-OCT-04:03 | 14.27 | 11.53 | 0.505171E+10 | 6734.72 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.282900E+11 | 68235.06 | 02-NOV-05:03 | 7.12 | 4.64 | 0.496491E+10 | 6734.63 | 08-NOV-10:09 | 13.40 | 6.02 |
December | 0.240958E+11 | 52968.10 | 01-DEC-06:02 | 3.90 | -0.5 | 0.470402E+10 | 6734.68 | 20-DEC-10:20 | 1.10 | -3.7 |
Annual Sum or Average | 0.421795E+12 | 0.601853E+11 | ||||||||
Minimum of Months | 0.233414E+11 | 32835.33 | -1.2 | -3.4 | 0.449228E+10 | 6734.63 | 1.10 | -3.7 | ||
Maximum of Months | 0.475830E+11 | 71607.36 | 17.02 | 14.97 | 0.549340E+10 | 6735.74 | 26.70 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167203E+11 | 20067.73 | 26-JAN-14:30 | 10.30 | 1.59 | 0.422358E+10 | 6476.69 | 27-JAN-14:00 | 11.70 | 2.33 |
February | 0.173663E+11 | 28549.28 | 15-FEB-17:00 | 16.70 | 5.85 | 0.400944E+10 | 6734.15 | 15-FEB-14:00 | 16.70 | 5.85 |
March | 0.254087E+11 | 30862.57 | 08-MAR-17:00 | 22.20 | 8.27 | 0.517763E+10 | 6734.55 | 02-MAR-14:09 | 22.20 | 8.27 |
April | 0.318071E+11 | 67824.44 | 27-APR-05:02 | 9.40 | 3.12 | 0.479924E+10 | 6734.71 | 17-APR-13:00 | 9.40 | 3.12 |
May | 0.399091E+11 | 71538.32 | 22-MAY-04:03 | 17.62 | 11.88 | 0.525020E+10 | 6734.88 | 11-MAY-09:09 | 17.62 | 11.88 |
June | 0.481957E+11 | 70135.66 | 01-JUN-05:02 | 14.08 | 10.66 | 0.526001E+10 | 6759.25 | 28-JUN-13:50 | 37.70 | 14.07 |
July | 0.514775E+11 | 73178.46 | 17-JUL-03:02 | 19.82 | 16.22 | 0.489540E+10 | 6734.74 | 18-JUL-09:50 | 25.73 | 17.29 |
August | 0.523622E+11 | 71618.94 | 23-AUG-04:03 | 18.80 | 14.52 | 0.549586E+10 | 6735.80 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.407606E+11 | 71260.14 | 05-SEP-04:03 | 17.52 | 15.20 | 0.486642E+10 | 6734.73 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.308544E+11 | 69966.59 | 03-OCT-05:02 | 15.92 | 11.83 | 0.490441E+10 | 6734.65 | 24-OCT-13:50 | 8.87 | 4.55 |
November | 0.208740E+11 | 32200.75 | 01-NOV-15:30 | 11.70 | 6.90 | 0.454489E+10 | 6734.62 | 01-NOV-09:09 | 11.70 | 6.90 |
December | 0.163377E+11 | 19982.30 | 29-DEC-13:50 | 10.32 | 3.31 | 0.407714E+10 | 6597.41 | 01-DEC-14:00 | 10.32 | 3.31 |
Annual Sum or Average | 0.392074E+12 | 0.575042E+11 | ||||||||
Minimum of Months | 0.163377E+11 | 19982.30 | 9.40 | 1.59 | 0.400944E+10 | 6476.69 | 8.87 | 2.33 | ||
Maximum of Months | 0.523622E+11 | 73178.46 | 22.20 | 16.22 | 0.549586E+10 | 6759.25 | 37.70 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253108E+10 | 2719.64 | 02-JAN-15:00 | 14.40 | 5.68 | 0.562362E+09 | 838.01 | 24-JAN-14:00 | 16.10 | 4.97 |
February | 0.259073E+10 | 3750.60 | 15-FEB-15:00 | 17.20 | 6.67 | 0.534006E+09 | 845.61 | 15-FEB-10:09 | 17.20 | 6.67 |
March | 0.422152E+10 | 5760.11 | 27-MAR-14:30 | 18.05 | 6.97 | 0.675096E+09 | 845.62 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.615758E+10 | 7355.41 | 14-APR-14:00 | 23.30 | 10.26 | 0.609305E+09 | 845.63 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.668480E+10 | 11005.24 | 22-MAY-05:03 | 16.78 | 12.20 | 0.662366E+09 | 845.65 | 11-MAY-09:09 | 16.78 | 12.20 |
June | 0.982487E+10 | 13458.65 | 25-JUN-17:31 | 32.97 | 15.43 | 0.662532E+09 | 845.65 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.110037E+11 | 15111.79 | 02-JUL-17:31 | 31.50 | 16.65 | 0.616466E+09 | 846.27 | 05-JUL-13:39 | 32.43 | 17.28 |
August | 0.110605E+11 | 12691.04 | 06-AUG-17:11 | 30.20 | 16.04 | 0.691191E+09 | 845.77 | 28-AUG-13:39 | 23.30 | 16.88 |
September | 0.678979E+10 | 11564.76 | 05-SEP-05:03 | 15.92 | 14.88 | 0.612789E+09 | 845.63 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.503010E+10 | 11726.67 | 02-OCT-05:02 | 17.12 | 12.75 | 0.625855E+09 | 845.63 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.342341E+10 | 4238.76 | 09-NOV-14:10 | 19.22 | 9.76 | 0.608049E+09 | 845.61 | 21-NOV-14:09 | 15.18 | 5.79 |
December | 0.275487E+10 | 3069.03 | 01-DEC-14:10 | 11.78 | 4.41 | 0.556180E+09 | 845.60 | 11-DEC-14:50 | 8.30 | 1.61 |
Annual Sum or Average | 0.720730E+11 | 0.741620E+10 | ||||||||
Minimum of Months | 0.253108E+10 | 2719.64 | 11.78 | 4.41 | 0.534006E+09 | 838.01 | 8.30 | 1.61 | ||
Maximum of Months | 0.110605E+11 | 15111.79 | 32.97 | 16.65 | 0.691191E+09 | 846.27 | 32.43 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274580E+10 | 5898.44 | 02-JAN-09:25 | 2.75 | -0.6 | 0.371433E+09 | 544.95 | 13-JAN-10:20 | 4.63 | 1.40 |
February | 0.292795E+10 | 7858.14 | 14-FEB-09:05 | 7.25 | 1.90 | 0.351271E+09 | 544.96 | 15-FEB-10:09 | 11.38 | 5.33 |
March | 0.483383E+10 | 14575.87 | 26-MAR-10:02 | 14.50 | 5.54 | 0.436027E+09 | 544.95 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.721739E+10 | 18986.40 | 30-APR-07:42 | 14.63 | 5.07 | 0.393452E+09 | 546.04 | 28-APR-09:50 | 14.63 | 5.07 |
May | 0.767349E+10 | 18989.56 | 14-MAY-07:32 | 18.17 | 8.24 | 0.427534E+09 | 545.80 | 15-MAY-09:20 | 20.37 | 9.24 |
June | 0.990595E+10 | 18763.84 | 11-JUN-07:12 | 16.50 | 10.30 | 0.426977E+09 | 546.01 | 19-JUN-09:00 | 21.10 | 8.29 |
July | 0.104517E+11 | 19574.39 | 02-JUL-08:51 | 23.30 | 17.35 | 0.397402E+09 | 546.29 | 06-JUL-09:20 | 27.93 | 15.97 |
August | 0.105012E+11 | 18472.03 | 20-AUG-08:42 | 25.82 | 15.35 | 0.445229E+09 | 546.28 | 21-AUG-09:39 | 26.33 | 17.13 |
September | 0.738765E+10 | 19702.07 | 03-SEP-08:21 | 24.45 | 14.44 | 0.394901E+09 | 545.92 | 11-SEP-09:09 | 21.47 | 13.47 |
October | 0.561441E+10 | 18691.48 | 01-OCT-08:52 | 17.80 | 11.25 | 0.404587E+09 | 544.97 | 18-OCT-09:09 | 12.35 | 5.73 |
November | 0.371202E+10 | 8144.12 | 01-NOV-08:50 | 9.63 | 6.30 | 0.392614E+09 | 544.95 | 27-NOV-10:09 | 1.28 | -3.1 |
December | 0.282236E+10 | 5195.85 | 29-DEC-09:15 | 1.67 | -0.9 | 0.361860E+09 | 544.95 | 26-DEC-10:09 | 1.67 | -0.9 |
Annual Sum or Average | 0.757937E+11 | 0.480329E+10 | ||||||||
Minimum of Months | 0.274580E+10 | 5195.85 | 1.67 | -0.9 | 0.351271E+09 | 544.95 | 1.28 | -3.1 | ||
Maximum of Months | 0.105012E+11 | 19702.07 | 25.82 | 17.35 | 0.445229E+09 | 546.29 | 27.93 | 17.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.724252E+10 | 19019.32 | 01-JAN-13:42 | 15.22 | 5.54 | 0.608619E+09 | 872.06 | 02-JAN-14:09 | 13.98 | 5.50 |
February | 0.745306E+10 | 18959.56 | 12-FEB-13:52 | 17.20 | 5.72 | 0.564102E+09 | 897.77 | 14-FEB-14:09 | 20.78 | 7.02 |
March | 0.847981E+10 | 19031.34 | 12-MAR-12:32 | 16.50 | 5.25 | 0.680492E+09 | 847.08 | 20-MAR-13:00 | 18.30 | 8.36 |
April | 0.927265E+10 | 18649.04 | 30-APR-13:02 | 20.78 | 7.24 | 0.610108E+09 | 847.29 | 17-APR-13:00 | 20.78 | 7.24 |
May | 0.780952E+10 | 13227.95 | 14-MAY-14:12 | 27.23 | 10.89 | 0.661559E+09 | 845.67 | 09-MAY-13:20 | 27.23 | 10.89 |
June | 0.987727E+10 | 13958.08 | 26-JUN-05:02 | 15.73 | 10.17 | 0.662037E+09 | 845.67 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.119607E+11 | 18924.90 | 30-JUL-12:32 | 31.10 | 17.67 | 0.616649E+09 | 846.65 | 25-JUL-13:20 | 31.10 | 17.67 |
August | 0.141469E+11 | 19066.64 | 06-AUG-12:32 | 30.37 | 16.16 | 0.692019E+09 | 851.13 | 31-AUG-13:09 | 29.50 | 15.73 |
September | 0.120111E+11 | 20638.37 | 03-SEP-12:21 | 30.85 | 16.81 | 0.616411E+09 | 925.84 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.119626E+11 | 21108.33 | 09-OCT-12:41 | 20.13 | 9.80 | 0.640428E+09 | 927.84 | 31-OCT-13:30 | 21.40 | 8.63 |
November | 0.970347E+10 | 20309.76 | 23-NOV-12:02 | 12.48 | 4.07 | 0.628768E+09 | 931.80 | 01-NOV-13:20 | 12.48 | 4.07 |
December | 0.877304E+10 | 19326.24 | 31-DEC-13:32 | 9.43 | 1.41 | 0.599842E+09 | 881.56 | 29-DEC-14:09 | 9.43 | 1.41 |
Annual Sum or Average | 0.118693E+12 | 0.758103E+10 | ||||||||
Minimum of Months | 0.724252E+10 | 13227.95 | 9.43 | 1.41 | 0.564102E+09 | 845.67 | 9.43 | 1.41 | ||
Maximum of Months | 0.141469E+11 | 21108.33 | 31.10 | 17.67 | 0.692019E+09 | 931.80 | 31.10 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.410885E+10 | 8105.56 | 26-JAN-16:30 | 10.30 | 1.40 | 0.376521E+09 | 544.93 | 04-JAN-14:50 | 10.30 | 1.40 |
February | 0.491986E+10 | 15419.34 | 12-FEB-15:53 | 18.30 | 6.40 | 0.360400E+09 | 544.95 | 15-FEB-10:09 | 11.38 | 5.33 |
March | 0.780052E+10 | 22791.75 | 12-MAR-15:52 | 19.40 | 6.09 | 0.444061E+09 | 544.96 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.111739E+11 | 24315.45 | 16-APR-16:21 | 20.00 | 7.96 | 0.396682E+09 | 544.97 | 26-APR-13:30 | 25.00 | 9.94 |
May | 0.885787E+10 | 25307.63 | 14-MAY-16:11 | 28.30 | 10.92 | 0.427888E+09 | 544.98 | 11-MAY-09:09 | 28.30 | 10.92 |
June | 0.123365E+11 | 26797.93 | 11-JUN-17:11 | 28.13 | 12.99 | 0.427924E+09 | 544.97 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.142555E+11 | 26401.13 | 02-JUL-17:31 | 31.50 | 16.65 | 0.398278E+09 | 544.97 | 18-JUL-09:39 | 25.37 | 17.15 |
August | 0.158276E+11 | 24857.87 | 20-AUG-16:01 | 34.90 | 15.92 | 0.446723E+09 | 545.09 | 28-AUG-13:39 | 23.30 | 16.88 |
September | 0.905493E+10 | 23829.37 | 17-SEP-15:12 | 24.27 | 14.52 | 0.396254E+09 | 544.96 | 19-SEP-13:09 | 25.18 | 14.10 |
October | 0.823014E+10 | 24354.39 | 01-OCT-14:51 | 28.30 | 12.89 | 0.409082E+09 | 544.97 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.645171E+10 | 22358.65 | 12-NOV-15:02 | 9.40 | 2.60 | 0.405168E+09 | 544.95 | 21-NOV-14:09 | 15.18 | 5.79 |
December | 0.569155E+10 | 15342.68 | 24-DEC-16:03 | 11.93 | 3.13 | 0.392141E+09 | 544.95 | 26-DEC-10:09 | 2.38 | 0.81 |
Annual Sum or Average | 0.108709E+12 | 0.488112E+10 | ||||||||
Minimum of Months | 0.410885E+10 | 8105.56 | 9.40 | 1.40 | 0.360400E+09 | 544.93 | 2.38 | 0.81 | ||
Maximum of Months | 0.158276E+11 | 26797.93 | 34.90 | 16.65 | 0.446723E+09 | 545.09 | 28.30 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121441E+10 | 2286.36 | 05-JAN-15:40 | 16.10 | 6.84 | 0.482915E+09 | 722.27 | 04-JAN-14:00 | 16.10 | 6.84 |
February | 0.149282E+10 | 2594.80 | 15-FEB-16:00 | 17.20 | 6.50 | 0.457405E+09 | 799.81 | 15-FEB-14:00 | 17.20 | 6.50 |
March | 0.259427E+10 | 3289.05 | 27-MAR-14:50 | 18.22 | 7.02 | 0.613094E+09 | 845.61 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.369161E+10 | 6122.81 | 14-APR-14:30 | 23.60 | 10.45 | 0.591247E+09 | 845.62 | 26-APR-13:20 | 24.80 | 9.90 |
May | 0.534018E+10 | 6936.80 | 31-MAY-15:30 | 27.75 | 11.03 | 0.657133E+09 | 845.64 | 11-MAY-09:09 | 27.75 | 11.03 |
June | 0.814311E+10 | 13958.90 | 18-JUN-18:21 | 29.15 | 10.43 | 0.661759E+09 | 845.90 | 23-JUN-13:50 | 34.22 | 12.87 |
July | 0.877678E+10 | 14393.75 | 04-JUL-18:12 | 33.33 | 13.61 | 0.616190E+09 | 845.86 | 17-JUL-13:50 | 28.30 | 17.53 |
August | 0.820991E+10 | 10672.59 | 21-AUG-05:03 | 21.60 | 15.49 | 0.690592E+09 | 845.78 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.544343E+10 | 9345.46 | 15-SEP-05:02 | 18.90 | 12.28 | 0.609950E+09 | 845.62 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.351102E+10 | 6273.64 | 02-OCT-13:40 | 26.33 | 15.37 | 0.591129E+09 | 845.62 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.211611E+10 | 2639.61 | 01-NOV-15:10 | 12.43 | 7.32 | 0.523751E+09 | 845.59 | 09-NOV-14:00 | 18.30 | 9.49 |
December | 0.101452E+10 | 2136.06 | 29-DEC-15:40 | 11.50 | 3.90 | 0.458480E+09 | 765.11 | 01-DEC-14:00 | 11.50 | 3.90 |
Annual Sum or Average | 0.515482E+11 | 0.695365E+10 | ||||||||
Minimum of Months | 0.101452E+10 | 2136.06 | 11.50 | 3.90 | 0.457405E+09 | 722.27 | 10.53 | 3.90 | ||
Maximum of Months | 0.877678E+10 | 14393.75 | 33.33 | 15.49 | 0.690592E+09 | 845.90 | 34.22 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179589E+10 | 3060.89 | 27-JAN-09:50 | 2.43 | -2.7 | 0.243480E+09 | 521.19 | 27-JAN-09:39 | 2.43 | -2.7 |
February | 0.217423E+10 | 6192.25 | 14-FEB-09:40 | 8.90 | 2.72 | 0.233423E+09 | 521.20 | 09-FEB-11:09 | 8.90 | 2.72 |
March | 0.390738E+10 | 14733.90 | 26-MAR-09:53 | 14.40 | 5.52 | 0.306166E+09 | 521.22 | 17-MAR-15:30 | 14.40 | 5.52 |
April | 0.623859E+10 | 20495.33 | 30-APR-08:11 | 15.20 | 5.08 | 0.288104E+09 | 521.65 | 27-APR-08:00 | 15.20 | 5.08 |
May | 0.741088E+10 | 20892.27 | 29-MAY-08:51 | 18.30 | 12.78 | 0.313475E+09 | 521.41 | 19-MAY-08:50 | 18.30 | 12.78 |
June | 0.965776E+10 | 21504.21 | 18-JUN-09:01 | 25.78 | 11.91 | 0.313785E+09 | 529.03 | 29-JUN-07:19 | 27.93 | 17.35 |
July | 0.998803E+10 | 22171.54 | 04-JUL-08:51 | 26.70 | 18.67 | 0.293617E+09 | 528.01 | 05-JUL-07:19 | 24.80 | 15.16 |
August | 0.970457E+10 | 19868.04 | 20-AUG-08:42 | 25.82 | 15.35 | 0.327559E+09 | 522.95 | 02-AUG-10:30 | 25.82 | 15.35 |
September | 0.704741E+10 | 20843.26 | 03-SEP-09:01 | 25.97 | 15.10 | 0.289750E+09 | 521.46 | 01-SEP-08:39 | 25.97 | 15.10 |
October | 0.487100E+10 | 19213.91 | 01-OCT-08:22 | 16.70 | 10.70 | 0.290089E+09 | 521.22 | 02-OCT-12:20 | 25.20 | 14.93 |
November | 0.280285E+10 | 7186.20 | 01-NOV-09:00 | 10.00 | 6.46 | 0.266318E+09 | 521.20 | 01-NOV-07:49 | 10.00 | 6.46 |
December | 0.175024E+10 | 2792.13 | 31-DEC-10:53 | 3.30 | -1.9 | 0.231905E+09 | 521.19 | 29-DEC-09:39 | 3.30 | -1.9 |
Annual Sum or Average | 0.673488E+11 | 0.339767E+10 | ||||||||
Minimum of Months | 0.175024E+10 | 2792.13 | 2.43 | -2.7 | 0.231905E+09 | 521.19 | 2.43 | -2.7 | ||
Maximum of Months | 0.998803E+10 | 22171.54 | 26.70 | 18.67 | 0.327559E+09 | 529.03 | 27.93 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.695598E+10 | 18415.75 | 01-JAN-13:42 | 15.22 | 5.54 | 0.598821E+09 | 927.27 | 26-JAN-14:20 | 10.20 | 1.54 |
February | 0.701410E+10 | 18353.30 | 19-FEB-13:42 | 15.92 | 6.62 | 0.556167E+09 | 955.62 | 14-FEB-14:20 | 15.92 | 6.62 |
March | 0.740961E+10 | 18754.49 | 12-MAR-13:42 | 17.62 | 5.94 | 0.667497E+09 | 866.79 | 13-MAR-13:50 | 20.32 | 6.92 |
April | 0.728110E+10 | 17632.86 | 30-APR-12:53 | 20.60 | 7.16 | 0.603836E+09 | 846.64 | 17-APR-13:00 | 20.60 | 7.16 |
May | 0.679307E+10 | 11946.75 | 14-MAY-13:02 | 26.70 | 11.10 | 0.658357E+09 | 845.67 | 09-MAY-13:20 | 26.70 | 11.10 |
June | 0.829400E+10 | 16953.10 | 25-JUN-16:31 | 34.07 | 14.58 | 0.660956E+09 | 845.67 | 30-JUN-13:50 | 28.08 | 17.83 |
July | 0.978656E+10 | 17842.37 | 30-JUL-11:22 | 29.45 | 17.97 | 0.616618E+09 | 846.15 | 25-JUL-13:00 | 29.45 | 17.97 |
August | 0.116091E+11 | 18207.56 | 13-AUG-12:52 | 28.30 | 18.16 | 0.692182E+09 | 870.94 | 31-AUG-13:09 | 29.50 | 15.73 |
September | 0.114751E+11 | 19937.63 | 03-SEP-12:21 | 30.85 | 16.81 | 0.620160E+09 | 988.22 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.113833E+11 | 21009.57 | 01-OCT-12:21 | 26.40 | 14.34 | 0.644218E+09 | 987.71 | 31-OCT-13:00 | 22.80 | 8.86 |
November | 0.898756E+10 | 18872.81 | 05-NOV-14:42 | 12.70 | 3.30 | 0.626829E+09 | 989.80 | 01-NOV-13:30 | 12.70 | 3.30 |
December | 0.775747E+10 | 18688.48 | 31-DEC-13:32 | 9.43 | 1.41 | 0.588110E+09 | 920.22 | 29-DEC-14:09 | 9.43 | 1.41 |
Annual Sum or Average | 0.104747E+12 | 0.753375E+10 | ||||||||
Minimum of Months | 0.679307E+10 | 11946.75 | 9.43 | 1.41 | 0.556167E+09 | 845.67 | 9.43 | 1.41 | ||
Maximum of Months | 0.116091E+11 | 21009.57 | 34.07 | 18.16 | 0.692182E+09 | 989.80 | 29.63 | 17.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218459E+10 | 5985.73 | 26-JAN-16:30 | 10.30 | 1.40 | 0.332198E+09 | 544.05 | 05-JAN-14:00 | 10.30 | 1.40 |
February | 0.268999E+10 | 9756.71 | 15-FEB-16:30 | 16.95 | 6.18 | 0.313951E+09 | 544.93 | 14-FEB-14:30 | 16.95 | 6.18 |
March | 0.417059E+10 | 19540.50 | 12-MAR-16:21 | 20.00 | 6.24 | 0.400020E+09 | 544.94 | 17-MAR-13:00 | 16.10 | 5.42 |
April | 0.584456E+10 | 21997.81 | 16-APR-16:31 | 20.20 | 8.02 | 0.382675E+09 | 544.96 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.684979E+10 | 21237.34 | 14-MAY-16:21 | 28.30 | 10.87 | 0.421437E+09 | 544.97 | 16-MAY-13:00 | 25.00 | 9.24 |
June | 0.901648E+10 | 23754.38 | 25-JUN-16:31 | 34.07 | 14.58 | 0.425708E+09 | 544.97 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.944910E+10 | 24346.58 | 04-JUL-16:51 | 36.10 | 14.82 | 0.397430E+09 | 544.96 | 18-JUL-09:39 | 25.37 | 17.15 |
August | 0.950569E+10 | 22543.37 | 13-AUG-17:31 | 29.63 | 17.01 | 0.445702E+09 | 545.07 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.700198E+10 | 21849.66 | 24-SEP-16:11 | 25.40 | 15.61 | 0.393465E+09 | 544.97 | 18-SEP-13:00 | 25.40 | 15.61 |
October | 0.533805E+10 | 20314.07 | 01-OCT-14:21 | 28.30 | 13.27 | 0.384480E+09 | 544.96 | 04-OCT-13:50 | 25.32 | 13.57 |
November | 0.328876E+10 | 8561.60 | 02-NOV-16:00 | 16.70 | 9.78 | 0.355769E+09 | 544.93 | 03-NOV-13:50 | 12.12 | 2.35 |
December | 0.214945E+10 | 4958.10 | 29-DEC-16:00 | 11.70 | 3.88 | 0.320549E+09 | 542.11 | 29-DEC-14:00 | 11.70 | 3.88 |
Annual Sum or Average | 0.674890E+11 | 0.457338E+10 | ||||||||
Minimum of Months | 0.214945E+10 | 4958.10 | 10.30 | 1.40 | 0.313951E+09 | 542.11 | 10.30 | 1.40 | ||
Maximum of Months | 0.950569E+10 | 24346.58 | 36.10 | 17.01 | 0.445702E+09 | 545.07 | 26.70 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.438983E+09 | 1950.73 | 05-JAN-14:30 | 16.10 | 6.84 | 0.467256E+09 | 673.75 | 24-JAN-14:00 | 16.10 | 4.97 |
February | 0.762953E+09 | 2564.02 | 15-FEB-15:30 | 17.20 | 6.59 | 0.433826E+09 | 769.24 | 15-FEB-14:00 | 17.20 | 6.59 |
March | 0.195035E+10 | 2437.04 | 08-MAR-14:00 | 22.80 | 9.68 | 0.571670E+09 | 845.60 | 17-MAR-13:00 | 16.10 | 5.42 |
April | 0.335444E+10 | 6510.26 | 28-APR-15:30 | 25.00 | 10.42 | 0.569805E+09 | 845.62 | 17-APR-13:00 | 25.00 | 10.42 |
May | 0.527615E+10 | 7656.48 | 31-MAY-15:10 | 27.38 | 11.00 | 0.648023E+09 | 845.64 | 31-MAY-13:20 | 27.38 | 11.00 |
June | 0.869498E+10 | 16825.95 | 25-JUN-17:21 | 33.05 | 15.18 | 0.660389E+09 | 863.71 | 28-JUN-13:50 | 37.70 | 14.07 |
July | 0.965758E+10 | 16228.25 | 04-JUL-18:21 | 33.05 | 13.57 | 0.616489E+09 | 845.72 | 07-JUL-13:50 | 33.80 | 18.39 |
August | 0.885503E+10 | 16030.75 | 13-AUG-17:31 | 29.63 | 17.01 | 0.690456E+09 | 845.78 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.545486E+10 | 9809.10 | 05-SEP-05:03 | 15.92 | 14.88 | 0.605685E+09 | 845.64 | 13-SEP-13:30 | 26.40 | 14.44 |
October | 0.296495E+10 | 6697.20 | 02-OCT-13:40 | 26.33 | 15.37 | 0.564468E+09 | 845.63 | 02-OCT-13:30 | 26.33 | 15.37 |
November | 0.121881E+10 | 2622.24 | 01-NOV-15:20 | 12.07 | 7.11 | 0.487982E+09 | 795.79 | 09-NOV-14:00 | 18.30 | 9.49 |
December | 0.256919E+09 | 1771.74 | 29-DEC-15:00 | 11.10 | 3.93 | 0.448893E+09 | 693.92 | 01-DEC-14:00 | 11.10 | 3.93 |
Annual Sum or Average | 0.488860E+11 | 0.676494E+10 | ||||||||
Minimum of Months | 0.256919E+09 | 1771.74 | 11.10 | 3.93 | 0.433826E+09 | 673.75 | 11.10 | 3.93 | ||
Maximum of Months | 0.965758E+10 | 16825.95 | 33.05 | 17.01 | 0.690456E+09 | 863.71 | 37.70 | 18.39 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104916E+10 | 2306.27 | 03-JAN-13:40 | 14.63 | 5.67 | 0.312916E+09 | 501.62 | 27-JAN-10:30 | 4.45 | -1.6 |
February | 0.148182E+10 | 4103.45 | 14-FEB-10:10 | 10.83 | 3.59 | 0.301503E+09 | 544.94 | 13-FEB-10:20 | 10.83 | 3.59 |
March | 0.312278E+10 | 6216.37 | 24-MAR-09:40 | 8.87 | 2.60 | 0.405972E+09 | 544.95 | 10-MAR-10:20 | 8.87 | 2.60 |
April | 0.584130E+10 | 18563.88 | 30-APR-09:12 | 15.97 | 4.95 | 0.390253E+09 | 545.77 | 28-APR-09:00 | 15.97 | 4.95 |
May | 0.742923E+10 | 20967.31 | 29-MAY-08:51 | 18.30 | 12.78 | 0.425552E+09 | 545.74 | 19-MAY-09:00 | 18.30 | 12.78 |
June | 0.102358E+11 | 21241.33 | 25-JUN-08:61 | 24.37 | 15.49 | 0.426753E+09 | 548.24 | 28-JUN-13:50 | 37.70 | 14.07 |
July | 0.108249E+11 | 20396.73 | 09-JUL-07:32 | 21.67 | 17.20 | 0.398014E+09 | 546.00 | 06-JUL-09:39 | 21.67 | 17.20 |
August | 0.104359E+11 | 20239.70 | 20-AUG-09:22 | 27.20 | 16.00 | 0.445679E+09 | 545.77 | 21-AUG-09:39 | 26.33 | 17.13 |
September | 0.716749E+10 | 19327.39 | 03-SEP-09:12 | 26.33 | 15.30 | 0.392968E+09 | 545.69 | 01-SEP-09:20 | 26.33 | 15.30 |
October | 0.431562E+10 | 12533.01 | 01-OCT-10:32 | 22.97 | 13.29 | 0.388324E+09 | 544.97 | 02-OCT-13:30 | 26.15 | 15.30 |
November | 0.200711E+10 | 5957.18 | 01-NOV-09:30 | 11.40 | 7.09 | 0.341899E+09 | 544.95 | 01-NOV-09:09 | 11.40 | 7.09 |
December | 0.960740E+09 | 2326.75 | 29-DEC-13:30 | 9.75 | 3.05 | 0.296354E+09 | 494.48 | 29-DEC-10:09 | 9.75 | 3.05 |
Annual Sum or Average | 0.648718E+11 | 0.452619E+10 | ||||||||
Minimum of Months | 0.960740E+09 | 2306.27 | 8.87 | 2.60 | 0.296354E+09 | 494.48 | 4.45 | -1.6 | ||
Maximum of Months | 0.108249E+11 | 21241.33 | 27.20 | 17.20 | 0.445679E+09 | 548.24 | 37.70 | 17.20 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.513126E+10 | 15604.49 | 26-JAN-14:10 | 10.10 | 1.50 | 0.570943E+09 | 848.41 | 26-JAN-14:20 | 10.20 | 1.54 |
February | 0.553152E+10 | 19615.05 | 19-FEB-13:42 | 15.92 | 6.62 | 0.529391E+09 | 890.28 | 14-FEB-14:30 | 15.92 | 6.62 |
March | 0.613517E+10 | 20189.73 | 12-MAR-14:22 | 18.90 | 6.18 | 0.638696E+09 | 846.10 | 16-MAR-13:00 | 20.60 | 8.86 |
April | 0.683784E+10 | 13429.60 | 28-APR-13:20 | 24.40 | 9.99 | 0.589394E+09 | 846.74 | 27-APR-13:00 | 24.40 | 9.99 |
May | 0.684145E+10 | 19343.26 | 21-MAY-13:22 | 27.25 | 12.27 | 0.649239E+09 | 845.67 | 08-MAY-13:39 | 27.25 | 12.27 |
June | 0.895691E+10 | 20035.70 | 25-JUN-16:01 | 35.22 | 14.86 | 0.658413E+09 | 860.91 | 28-JUN-13:50 | 37.70 | 14.07 |
July | 0.108184E+11 | 19681.37 | 30-JUL-14:52 | 33.30 | 17.94 | 0.616556E+09 | 846.23 | 25-JUL-13:39 | 33.30 | 17.94 |
August | 0.125036E+11 | 20681.81 | 13-AUG-12:52 | 28.30 | 18.16 | 0.691601E+09 | 853.52 | 31-AUG-13:09 | 29.50 | 15.73 |
September | 0.116660E+11 | 21127.87 | 03-SEP-13:12 | 31.67 | 16.75 | 0.614744E+09 | 957.46 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.106020E+11 | 21703.13 | 01-OCT-13:12 | 27.57 | 13.97 | 0.622603E+09 | 951.99 | 05-OCT-13:50 | 26.52 | 12.57 |
November | 0.711001E+10 | 20705.00 | 19-NOV-12:52 | 11.10 | 2.63 | 0.599856E+09 | 933.78 | 01-NOV-13:39 | 11.10 | 2.63 |
December | 0.578218E+10 | 19573.49 | 31-DEC-13:53 | 10.00 | 1.60 | 0.560754E+09 | 845.63 | 20-DEC-14:00 | 10.00 | 1.60 |
Annual Sum or Average | 0.979163E+11 | 0.734219E+10 | ||||||||
Minimum of Months | 0.513126E+10 | 13429.60 | 10.00 | 1.50 | 0.529391E+09 | 845.63 | 10.00 | 1.54 | ||
Maximum of Months | 0.125036E+11 | 21703.13 | 35.22 | 18.16 | 0.691601E+09 | 957.46 | 37.70 | 17.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141734E+10 | 5111.87 | 26-JAN-16:30 | 10.30 | 1.40 | 0.321946E+09 | 525.05 | 05-JAN-14:00 | 10.30 | 1.40 |
February | 0.203853E+10 | 9462.24 | 15-FEB-16:30 | 16.95 | 6.18 | 0.301588E+09 | 544.91 | 15-FEB-14:00 | 16.95 | 6.18 |
March | 0.356438E+10 | 16945.30 | 12-MAR-16:21 | 20.00 | 6.24 | 0.377929E+09 | 544.93 | 09-MAR-14:09 | 20.00 | 6.24 |
April | 0.561767E+10 | 19624.90 | 16-APR-16:42 | 20.40 | 8.08 | 0.369699E+09 | 544.96 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.693513E+10 | 22372.87 | 29-MAY-16:11 | 26.83 | 13.10 | 0.413673E+09 | 544.97 | 08-MAY-13:39 | 26.83 | 13.10 |
June | 0.954943E+10 | 26440.78 | 25-JUN-16:41 | 33.68 | 14.48 | 0.423717E+09 | 562.83 | 27-JUN-15:00 | 37.80 | 15.32 |
July | 0.101852E+11 | 24114.46 | 04-JUL-17:01 | 35.73 | 14.63 | 0.397250E+09 | 544.96 | 18-JUL-09:50 | 25.73 | 17.29 |
August | 0.101260E+11 | 24590.33 | 13-AUG-17:31 | 29.63 | 17.01 | 0.445190E+09 | 545.07 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.711545E+10 | 21764.53 | 24-SEP-16:22 | 25.30 | 15.57 | 0.389735E+09 | 544.99 | 13-SEP-13:30 | 25.30 | 15.57 |
October | 0.490563E+10 | 20249.59 | 01-OCT-15:12 | 28.50 | 13.01 | 0.370528E+09 | 544.96 | 02-OCT-13:30 | 26.15 | 15.30 |
November | 0.254392E+10 | 8014.94 | 02-NOV-16:00 | 16.70 | 9.78 | 0.337074E+09 | 544.93 | 14-NOV-14:00 | 12.20 | 4.12 |
December | 0.133095E+10 | 4126.86 | 29-DEC-16:00 | 11.70 | 3.88 | 0.312010E+09 | 525.17 | 20-DEC-14:00 | 11.70 | 3.88 |
Annual Sum or Average | 0.653296E+11 | 0.446034E+10 | ||||||||
Minimum of Months | 0.133095E+10 | 4126.86 | 10.30 | 1.40 | 0.301588E+09 | 525.05 | 10.30 | 1.40 | ||
Maximum of Months | 0.101852E+11 | 26440.78 | 35.73 | 17.01 | 0.445190E+09 | 562.83 | 37.80 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105026E+10 | 4470.19 | 02-JAN-06:13 | -4.0 | -4.9 | 0.00 | 0.00 | 01-JAN-00:10 | -4.0 | -4.9 |
February | 0.139090E+10 | 3848.95 | 15-FEB-06:15 | 6.67 | 2.30 | 0.00 | 0.00 | 01-FEB-00:10 | 6.67 | 2.30 |
March | 0.326331E+10 | 4609.66 | 27-MAR-05:15 | 5.40 | 0.66 | 0.00 | 0.00 | 01-MAR-00:10 | 5.40 | 0.66 |
April | 0.520331E+10 | 5992.80 | 03-APR-05:15 | 7.40 | 1.11 | 0.00 | 0.00 | 01-APR-00:10 | 7.40 | 1.11 |
May | 0.568528E+10 | 9042.10 | 30-MAY-05:15 | 14.43 | 10.90 | 0.00 | 0.00 | 01-MAY-00:10 | 14.43 | 10.90 |
June | 0.803215E+10 | 9610.85 | 19-JUN-05:15 | 12.93 | 5.33 | 0.00 | 0.00 | 01-JUN-00:10 | 12.93 | 5.33 |
July | 0.940725E+10 | 12949.10 | 05-JUL-05:15 | 22.20 | 13.64 | 0.00 | 0.00 | 01-JUL-00:10 | 22.20 | 13.64 |
August | 0.989691E+10 | 11496.02 | 14-AUG-05:15 | 18.90 | 16.75 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 16.75 |
September | 0.671530E+10 | 11855.72 | 05-SEP-05:15 | 15.73 | 14.76 | 0.00 | 0.00 | 01-SEP-00:10 | 15.73 | 14.76 |
October | 0.503392E+10 | 9622.60 | 10-OCT-05:15 | 13.90 | 11.14 | 0.00 | 0.00 | 01-OCT-00:10 | 13.90 | 11.14 |
November | 0.293879E+10 | 4451.51 | 01-NOV-16:00 | 10.60 | 6.24 | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 6.24 |
December | 0.151846E+10 | 3296.45 | 01-DEC-06:08 | 3.90 | -0.5 | 0.00 | 0.00 | 01-DEC-00:10 | 3.90 | -0.5 |
Annual Sum or Average | 0.601358E+11 | 0.00 | ||||||||
Minimum of Months | 0.105026E+10 | 3296.45 | -4.0 | -4.9 | 0.00 | 0.00 | -4.0 | -4.9 | ||
Maximum of Months | 0.989691E+10 | 12949.10 | 22.20 | 16.75 | 0.00 | 0.00 | 22.20 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.413285E+09 | 5061.46 | 07-JAN-06:01 | -3.6 | -4.7 | 0.00 | 0.00 | 01-JAN-00:10 | -3.6 | -4.7 |
February | 0.514501E+09 | 5792.84 | 06-FEB-05:01 | -4.4 | -6.9 | 0.00 | 0.00 | 01-FEB-00:10 | -4.4 | -6.9 |
March | 0.109560E+10 | 3462.00 | 06-MAR-06:01 | -2.9 | -4.2 | 0.00 | 0.00 | 01-MAR-00:10 | -2.9 | -4.2 |
April | 0.268871E+10 | 4348.98 | 28-APR-15:00 | 25.00 | 10.42 | 0.00 | 0.00 | 01-APR-00:10 | 25.00 | 10.42 |
May | 0.402395E+10 | 4915.67 | 22-MAY-05:03 | 16.78 | 12.20 | 0.00 | 0.00 | 01-MAY-00:10 | 16.78 | 12.20 |
June | 0.615745E+10 | 6533.22 | 29-JUN-16:00 | 35.60 | 16.66 | 0.00 | 0.00 | 01-JUN-00:10 | 35.60 | 16.66 |
July | 0.719098E+10 | 7414.71 | 17-JUL-05:03 | 18.90 | 15.60 | 0.00 | 0.00 | 01-JUL-00:10 | 18.90 | 15.60 |
August | 0.723601E+10 | 7063.57 | 01-AUG-05:03 | 19.50 | 14.33 | 0.00 | 0.00 | 01-AUG-00:10 | 19.50 | 14.33 |
September | 0.504053E+10 | 6873.42 | 05-SEP-05:15 | 15.73 | 14.76 | 0.00 | 0.00 | 01-SEP-00:10 | 15.73 | 14.76 |
October | 0.296708E+10 | 5479.02 | 03-OCT-05:15 | 15.73 | 11.98 | 0.00 | 0.00 | 01-OCT-00:10 | 15.73 | 11.98 |
November | 0.973315E+09 | 4596.83 | 27-NOV-06:01 | -4.4 | -6.8 | 0.00 | 0.00 | 01-NOV-00:10 | -4.4 | -6.8 |
December | 0.394804E+09 | 4736.73 | 22-DEC-05:01 | -4.7 | -6.6 | 0.00 | 0.00 | 01-DEC-00:10 | -4.7 | -6.6 |
Annual Sum or Average | 0.386962E+11 | 0.00 | ||||||||
Minimum of Months | 0.394804E+09 | 3462.00 | -4.7 | -6.9 | 0.00 | 0.00 | -4.7 | -6.9 | ||
Maximum of Months | 0.723601E+10 | 7414.71 | 35.60 | 16.66 | 0.00 | 0.00 | 35.60 | 16.66 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151849E+09 | 2445.03 | 01-JAN-14:07 | 15.68 | 5.68 | 0.00 | 0.00 | 01-JAN-00:10 | 15.68 | 5.68 |
February | 0.632194E+09 | 5445.95 | 15-FEB-15:40 | 17.20 | 6.56 | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 6.56 |
March | 0.214067E+10 | 8089.37 | 08-MAR-15:00 | 22.20 | 9.10 | 0.00 | 0.00 | 01-MAR-00:10 | 22.20 | 9.10 |
April | 0.571951E+10 | 14519.40 | 28-APR-14:40 | 24.80 | 10.38 | 0.00 | 0.00 | 01-APR-00:10 | 24.80 | 10.38 |
May | 0.829070E+10 | 17188.04 | 30-MAY-14:30 | 27.20 | 12.25 | 0.00 | 0.00 | 01-MAY-00:10 | 27.20 | 12.25 |
June | 0.130640E+11 | 22131.90 | 28-JUN-13:30 | 37.50 | 13.98 | 0.00 | 0.00 | 01-JUN-00:10 | 37.50 | 13.98 |
July | 0.150163E+11 | 21191.77 | 21-JUL-14:20 | 37.80 | 15.31 | 0.00 | 0.00 | 01-JUL-00:10 | 37.80 | 15.31 |
August | 0.142201E+11 | 19721.30 | 07-AUG-14:20 | 33.13 | 15.81 | 0.00 | 0.00 | 01-AUG-00:10 | 33.13 | 15.81 |
September | 0.894466E+10 | 15310.84 | 01-SEP-15:00 | 28.90 | 16.64 | 0.00 | 0.00 | 01-SEP-00:10 | 28.90 | 16.64 |
October | 0.413873E+10 | 11768.63 | 05-OCT-14:30 | 26.70 | 12.37 | 0.00 | 0.00 | 01-OCT-00:10 | 26.70 | 12.37 |
November | 0.689807E+09 | 4850.12 | 01-NOV-14:30 | 12.50 | 7.40 | 0.00 | 0.00 | 01-NOV-00:10 | 12.50 | 7.40 |
December | 66184821.66 | 2760.66 | 31-DEC-14:35 | 10.73 | 2.01 | 0.00 | 0.00 | 01-DEC-00:10 | 10.73 | 2.01 |
Annual Sum or Average | 0.730746E+11 | 0.00 | ||||||||
Minimum of Months | 66184821.66 | 2445.03 | 10.73 | 2.01 | 0.00 | 0.00 | 10.73 | 2.01 | ||
Maximum of Months | 0.150163E+11 | 22131.90 | 37.80 | 16.64 | 0.00 | 0.00 | 37.80 | 16.64 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.329526E+10 | 2219.59 | 26-JAN-17:00 | 10.00 | 1.21 | 95230029.74 | 126.82 | 20-JAN-14:00 | 10.00 | 1.21 |
February | 0.796817E+10 | 4245.45 | 15-FEB-17:00 | 16.70 | 5.85 | 86396712.89 | 126.83 | 17-FEB-10:00 | 7.20 | 4.72 |
March | 0.143130E+11 | 7109.00 | 31-MAR-24:00 | 6.90 | 3.36 | 0.103236E+09 | 126.83 | 29-MAR-09:30 | 6.90 | 3.36 |
April | 0.189435E+11 | 8249.41 | 16-APR-18:20 | 19.03 | 7.42 | 91608945.43 | 126.82 | 20-APR-09:00 | 12.20 | 5.87 |
May | 0.444143E+10 | 3498.44 | 31-MAY-24:00 | 18.60 | 7.93 | 99235417.78 | 126.85 | 24-MAY-09:00 | 18.60 | 7.93 |
June | 0.936004E+10 | 5340.36 | 30-JUN-24:00 | 22.10 | 13.89 | 98962425.84 | 126.85 | 08-JUN-13:00 | 22.10 | 13.89 |
July | 0.147497E+11 | 7235.22 | 31-JUL-23:45 | 21.03 | 17.45 | 91887035.51 | 126.84 | 17-JUL-09:09 | 21.03 | 17.45 |
August | 0.197449E+11 | 7918.70 | 30-AUG-17:40 | 28.50 | 14.73 | 0.103347E+09 | 127.65 | 17-AUG-13:00 | 28.50 | 14.73 |
September | 0.444090E+10 | 3499.55 | 30-SEP-24:00 | 17.40 | 10.77 | 91612888.06 | 126.85 | 06-SEP-13:00 | 17.40 | 10.77 |
October | 0.946269E+10 | 5294.71 | 31-OCT-24:00 | 13.00 | 4.55 | 95233436.97 | 126.85 | 11-OCT-09:00 | 13.00 | 4.55 |
November | 0.138048E+11 | 6127.23 | 05-NOV-16:33 | 11.87 | 2.83 | 94300882.44 | 126.83 | 02-NOV-13:09 | 11.87 | 2.83 |
December | 0.191018E+11 | 7931.78 | 31-DEC-16:35 | 9.27 | 1.21 | 91880730.22 | 126.82 | 08-DEC-14:09 | 9.27 | 1.21 |
Annual Sum or Average | 0.139626E+12 | 0.114293E+10 | ||||||||
Minimum of Months | 0.329526E+10 | 2219.59 | 6.90 | 1.21 | 86396712.89 | 126.82 | 6.90 | 1.21 | ||
Maximum of Months | 0.197449E+11 | 8249.41 | 28.50 | 17.45 | 0.103347E+09 | 127.65 | 28.50 | 17.45 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143402E+10 | 1980.92 | 26-JAN-17:00 | 10.00 | 1.21 | 95230042.37 | 126.82 | 20-JAN-14:00 | 10.00 | 1.21 |
February | 0.625101E+10 | 3974.96 | 15-FEB-17:00 | 16.70 | 5.85 | 86396718.99 | 126.83 | 17-FEB-10:00 | 7.20 | 4.72 |
March | 0.126587E+11 | 6545.31 | 31-MAR-23:40 | 6.70 | 3.28 | 0.103236E+09 | 126.83 | 29-MAR-09:30 | 6.70 | 3.28 |
April | 0.176833E+11 | 7771.31 | 16-APR-17:42 | 19.60 | 7.69 | 91607558.64 | 126.82 | 20-APR-09:00 | 12.20 | 5.87 |
May | 0.387476E+10 | 3308.29 | 31-MAY-24:00 | 18.60 | 7.93 | 99235042.77 | 126.84 | 24-MAY-09:30 | 18.60 | 7.93 |
June | 0.877938E+10 | 5162.22 | 30-JUN-24:00 | 22.10 | 13.89 | 98962137.59 | 126.85 | 08-JUN-13:00 | 22.10 | 13.89 |
July | 0.140274E+11 | 6983.22 | 31-JUL-23:53 | 21.00 | 17.53 | 91886944.24 | 126.84 | 17-JUL-09:09 | 21.00 | 17.53 |
August | 0.188268E+11 | 7563.57 | 30-AUG-17:40 | 28.50 | 14.73 | 0.103339E+09 | 127.79 | 17-AUG-13:00 | 28.50 | 14.73 |
September | 0.394247E+10 | 3300.54 | 30-SEP-24:00 | 17.40 | 10.77 | 91612027.00 | 126.84 | 08-SEP-13:00 | 17.40 | 10.77 |
October | 0.833391E+10 | 4809.10 | 31-OCT-24:00 | 13.00 | 4.55 | 95233217.87 | 126.84 | 11-OCT-09:00 | 13.00 | 4.55 |
November | 0.118800E+11 | 5689.75 | 02-NOV-16:40 | 16.30 | 9.65 | 94300851.68 | 126.83 | 02-NOV-09:00 | 16.30 | 9.65 |
December | 0.162384E+11 | 7290.76 | 29-DEC-16:50 | 10.28 | 3.14 | 91880788.98 | 126.82 | 08-DEC-14:09 | 10.28 | 3.14 |
Annual Sum or Average | 0.123930E+12 | 0.114292E+10 | ||||||||
Minimum of Months | 0.143402E+10 | 1980.92 | 6.70 | 1.21 | 86396718.99 | 126.82 | 6.70 | 1.21 | ||
Maximum of Months | 0.188268E+11 | 7771.31 | 28.50 | 17.53 | 0.103339E+09 | 127.79 | 28.50 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.488023E+09 | 1825.53 | 26-JAN-17:00 | 10.00 | 1.21 | 93888477.51 | 129.20 | 24-JAN-10:09 | 10.00 | 1.21 |
February | 0.467750E+10 | 3971.19 | 15-FEB-17:00 | 16.70 | 5.85 | 86396718.66 | 126.83 | 17-FEB-10:00 | 7.20 | 4.72 |
March | 0.115334E+11 | 6175.24 | 31-MAR-23:20 | 6.50 | 3.19 | 0.103236E+09 | 126.83 | 29-MAR-09:30 | 6.50 | 3.19 |
April | 0.172076E+11 | 7764.10 | 16-APR-17:42 | 19.60 | 7.69 | 91606106.05 | 126.82 | 20-APR-09:00 | 12.20 | 5.87 |
May | 0.366192E+10 | 3262.81 | 31-MAY-24:00 | 18.60 | 7.93 | 99234943.30 | 126.84 | 23-MAY-13:00 | 18.60 | 7.93 |
June | 0.879585E+10 | 5175.89 | 30-JUN-24:00 | 22.10 | 13.89 | 98962310.71 | 126.85 | 08-JUN-13:00 | 22.10 | 13.89 |
July | 0.141508E+11 | 6973.42 | 31-JUL-23:53 | 21.00 | 17.53 | 91887325.22 | 126.84 | 17-JUL-09:09 | 21.00 | 17.53 |
August | 0.189069E+11 | 7723.61 | 13-AUG-19:23 | 26.95 | 17.61 | 0.103288E+09 | 126.91 | 17-AUG-13:00 | 33.90 | 18.07 |
September | 0.383152E+10 | 3278.72 | 30-SEP-24:00 | 17.40 | 10.77 | 91612131.59 | 126.85 | 01-SEP-13:00 | 17.40 | 10.77 |
October | 0.758988E+10 | 4553.32 | 31-OCT-23:40 | 13.33 | 4.91 | 95233251.71 | 126.84 | 11-OCT-09:00 | 13.33 | 4.91 |
November | 0.102756E+11 | 5660.62 | 02-NOV-16:40 | 16.30 | 9.65 | 94300873.40 | 126.83 | 02-NOV-09:00 | 16.30 | 9.65 |
December | 0.141788E+11 | 7147.55 | 29-DEC-16:50 | 10.28 | 3.14 | 91880808.96 | 126.82 | 08-DEC-14:09 | 10.28 | 3.14 |
Annual Sum or Average | 0.115298E+12 | 0.114153E+10 | ||||||||
Minimum of Months | 0.488023E+09 | 1825.53 | 6.50 | 1.21 | 86396718.66 | 126.82 | 6.50 | 1.21 | ||
Maximum of Months | 0.189069E+11 | 7764.10 | 26.95 | 17.61 | 0.103288E+09 | 129.20 | 33.90 | 18.07 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237387E+12 | 91564.98 | 02-JAN-17:00 | 11.10 | 4.18 | 0.206144E+10 | 2745.29 | 03-JAN-10:09 | 7.07 | 2.12 |
February | 0.435056E+12 | 182867.59 | 15-FEB-17:00 | 16.70 | 5.85 | 0.187022E+10 | 2745.29 | 24-FEB-14:30 | 8.60 | 2.09 |
March | 0.728249E+12 | 358508.74 | 31-MAR-24:00 | 6.90 | 3.36 | 0.223475E+10 | 2745.29 | 27-MAR-13:30 | 6.90 | 3.36 |
April | 0.942450E+12 | 366453.85 | 26-APR-16:00 | 25.00 | 9.93 | 0.198297E+10 | 2745.29 | 26-APR-09:39 | 25.00 | 9.93 |
May | 0.240189E+12 | 175775.06 | 31-MAY-24:00 | 18.60 | 7.93 | 0.214810E+10 | 2745.29 | 01-MAY-13:09 | 18.60 | 7.93 |
June | 0.469714E+12 | 267520.94 | 30-JUN-24:00 | 22.10 | 13.89 | 0.214213E+10 | 2745.29 | 23-JUN-13:09 | 22.10 | 13.89 |
July | 0.731863E+12 | 359978.96 | 31-JUL-23:55 | 21.00 | 17.53 | 0.198894E+10 | 2745.29 | 19-JUL-13:09 | 21.00 | 17.53 |
August | 0.977667E+12 | 368004.50 | 21-AUG-16:00 | 32.80 | 16.79 | 0.223475E+10 | 2745.29 | 02-AUG-09:30 | 32.80 | 16.79 |
September | 0.235734E+12 | 176457.17 | 30-SEP-24:00 | 17.40 | 10.77 | 0.198297E+10 | 2745.29 | 08-SEP-13:09 | 17.40 | 10.77 |
October | 0.487389E+12 | 268399.23 | 31-OCT-24:00 | 13.00 | 4.55 | 0.206144E+10 | 2745.29 | 10-OCT-13:30 | 13.00 | 4.55 |
November | 0.707892E+12 | 275800.37 | 24-NOV-17:00 | 13.90 | 4.33 | 0.204131E+10 | 2745.29 | 20-NOV-10:39 | 13.90 | 4.33 |
December | 0.975737E+12 | 367096.89 | 26-DEC-17:00 | 6.70 | 3.21 | 0.198894E+10 | 2745.29 | 13-DEC-10:30 | 6.70 | 3.21 |
Annual Sum or Average | 0.716933E+13 | 0.247380E+11 | ||||||||
Minimum of Months | 0.235734E+12 | 91564.98 | 6.70 | 3.21 | 0.187022E+10 | 2745.29 | 6.70 | 2.09 | ||
Maximum of Months | 0.977667E+12 | 368004.50 | 32.80 | 17.53 | 0.223475E+10 | 2745.29 | 32.80 | 17.53 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207132E+09 | 11643.37 | 17-JAN-04:07 | -3.3 |
February | 0.165915E+09 | 11644.74 | 27-FEB-04:04 | 1.20 |
March | 0.144147E+09 | 11728.76 | 13-MAR-03:05 | 1.20 |
April | 0.232122E+09 | 11599.91 | 08-APR-04:05 | 2.80 |
May | 0.356687E+09 | 11646.89 | 08-MAY-03:05 | 11.78 |
June | 0.423999E+09 | 16157.95 | 17-JUN-16:02 | 33.43 |
July | 0.538886E+09 | 19667.11 | 22-JUL-15:02 | 38.03 |
August | 0.485652E+09 | 15088.54 | 05-AUG-15:02 | 32.62 |
September | 0.493540E+09 | 14259.60 | 02-SEP-15:02 | 31.60 |
October | 0.413269E+09 | 12944.72 | 01-OCT-19:53 | 21.10 |
November | 0.349672E+09 | 13141.79 | 12-NOV-17:03 | 8.80 |
December | 0.253913E+09 | 12729.99 | 25-DEC-16:43 | 3.98 |
Annual Sum or Average | 0.406493E+10 | |||
Minimum of Months | 0.144147E+09 | 11599.91 | -3.3 | |
Maximum of Months | 0.538886E+09 | 19667.11 | 38.03 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172271E+10 | 67593.25 | 17-JAN-04:11 | -3.3 |
February | 0.708961E+09 | 66913.82 | 06-FEB-04:11 | -4.4 |
March | 33114367.17 | 58342.22 | 06-MAR-06:01 | -2.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 10653553.19 | 56326.00 | 26-OCT-05:03 | -2.5 |
November | 0.326368E+09 | 62485.95 | 27-NOV-05:01 | -4.0 |
December | 0.154344E+10 | 67217.86 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.434524E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.172271E+10 | 67593.25 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1262126.59 | 2702.02 | 21-JAN-06:01 | -6.5 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 1262126.59 | |||
Minimum of Months | 0.00 | 0.00 | -6.5 | |
Maximum of Months | 1262126.59 | 2702.02 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5723297.78 | 5180.84 | 21-JAN-06:01 | -6.5 |
February | 99840.59 | 499.34 | 07-FEB-06:02 | -3.9 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 536730.33 | 1831.08 | 22-DEC-06:01 | -6.1 |
Annual Sum or Average | 6359868.69 | |||
Minimum of Months | 0.00 | 0.00 | -6.5 | |
Maximum of Months | 5723297.78 | 5180.84 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21123725.00 | 9373.37 | 19-JAN-06:01 | -3.2 |
February | 5157955.27 | 8530.94 | 06-FEB-06:03 | -4.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 2723261.55 | 5323.48 | 22-DEC-06:01 | -6.1 |
Annual Sum or Average | 29004941.81 | |||
Minimum of Months | 0.00 | 0.00 | -6.1 | |
Maximum of Months | 21123725.00 | 9373.37 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.914472E+09 | 10872.61 | 17-JAN-05:01 | -3.3 |
February | 0.489412E+09 | 10731.45 | 06-FEB-05:01 | -4.4 |
March | 41400520.27 | 9678.70 | 04-MAR-06:02 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 20641726.55 | 9546.25 | 26-OCT-05:03 | -2.5 |
November | 0.145132E+09 | 10292.18 | 27-NOV-05:01 | -4.0 |
December | 0.970715E+09 | 10506.40 | 26-DEC-05:02 | -1.0 |
Annual Sum or Average | 0.258177E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.970715E+09 | 10872.61 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.419771E+09 | 12319.32 | 17-JAN-05:01 | -3.3 |
February | 0.178807E+09 | 12236.24 | 06-FEB-05:01 | -4.4 |
March | 7397846.89 | 10749.35 | 04-MAR-06:02 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 9774681.41 | 9337.28 | 26-OCT-05:03 | -2.5 |
November | 35608367.73 | 11149.20 | 27-NOV-05:01 | -4.0 |
December | 0.399030E+09 | 11778.31 | 26-DEC-05:02 | -1.0 |
Annual Sum or Average | 0.105039E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.419771E+09 | 12319.32 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211665E+09 | 12979.45 | 18-JAN-05:01 | -2.3 |
February | 86964927.44 | 12920.80 | 06-FEB-05:01 | -4.4 |
March | 4823729.13 | 11795.47 | 04-MAR-06:02 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 7129829.23 | 9398.44 | 26-OCT-05:03 | -2.5 |
November | 5273511.71 | 11867.20 | 27-NOV-06:01 | -4.4 |
December | 0.192240E+09 | 12677.13 | 26-DEC-05:02 | -1.0 |
Annual Sum or Average | 0.508097E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.211665E+09 | 12979.45 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233001E+09 | 11487.82 | 17-JAN-05:01 | -3.3 |
February | 0.109612E+09 | 11826.82 | 06-FEB-05:01 | -4.4 |
March | 4626944.11 | 7743.31 | 04-MAR-06:02 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 5244214.38 | 6158.16 | 26-OCT-05:03 | -2.5 |
November | 11290018.59 | 10560.94 | 27-NOV-06:01 | -4.4 |
December | 0.215412E+09 | 11145.97 | 22-DEC-05:01 | -4.7 |
Annual Sum or Average | 0.579185E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.7 | |
Maximum of Months | 0.233001E+09 | 11826.82 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.390456E+10 | 14215.36 | 17-JAN-04:11 | -3.3 |
February | 0.241836E+10 | 14224.06 | 06-FEB-04:11 | -4.4 |
March | 0.732735E+09 | 12709.01 | 04-MAR-05:01 | -1.2 |
April | 73848406.14 | 11101.53 | 24-APR-05:03 | 6.20 |
May | 4994791.90 | 6727.30 | 06-MAY-05:03 | 6.02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.344807E+09 | 12487.30 | 26-OCT-04:01 | -2.8 |
November | 0.139224E+10 | 13953.18 | 27-NOV-04:01 | -3.9 |
December | 0.417008E+10 | 14018.77 | 18-DEC-04:01 | -2.7 |
Annual Sum or Average | 0.130416E+11 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.417008E+10 | 14224.06 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172290E+10 | 16187.70 | 17-JAN-04:11 | -3.3 |
February | 0.950100E+09 | 16160.43 | 06-FEB-04:11 | -4.4 |
March | 0.235800E+09 | 14429.07 | 04-MAR-05:01 | -1.2 |
April | 12052141.90 | 7736.86 | 08-APR-05:03 | 2.62 |
May | 361322.99 | 1043.63 | 06-MAY-05:03 | 6.02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.143231E+09 | 14153.80 | 26-OCT-04:01 | -2.8 |
November | 0.475586E+09 | 15533.80 | 27-NOV-04:01 | -3.9 |
December | 0.170908E+10 | 15748.52 | 04-DEC-04:11 | -0.2 |
Annual Sum or Average | 0.524910E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.172290E+10 | 16187.70 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154631E+10 | 16929.38 | 17-JAN-04:11 | -3.3 |
February | 0.901050E+09 | 16850.38 | 06-FEB-04:11 | -4.4 |
March | 0.270780E+09 | 14922.87 | 04-MAR-05:01 | -1.2 |
April | 23334416.72 | 11556.48 | 08-APR-05:03 | 2.62 |
May | 2841363.83 | 3865.56 | 05-MAY-05:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.142619E+09 | 14978.83 | 26-OCT-04:01 | -2.8 |
November | 0.282296E+09 | 14976.13 | 27-NOV-05:01 | -4.0 |
December | 0.145666E+10 | 16637.88 | 04-DEC-04:11 | -0.2 |
Annual Sum or Average | 0.462589E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.154631E+10 | 16929.38 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134122E+10 | 16741.98 | 17-JAN-04:11 | -3.3 |
February | 0.752901E+09 | 16791.42 | 06-FEB-04:11 | -4.4 |
March | 0.169070E+09 | 14362.49 | 04-MAR-05:01 | -1.2 |
April | 3625643.70 | 6425.37 | 08-APR-05:03 | 2.62 |
May | 452908.07 | 1424.75 | 05-MAY-05:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 93696553.61 | 14495.86 | 26-OCT-04:01 | -2.8 |
November | 0.319565E+09 | 14680.18 | 28-NOV-05:01 | -1.3 |
December | 0.126705E+10 | 15966.30 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.394758E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.134122E+10 | 16791.42 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.281188E+09 | 8307.02 | 09-JAN-06:01 | -2.2 |
February | 0.157708E+09 | 9123.69 | 07-FEB-06:01 | -3.9 |
March | 0.109290E+09 | 8970.18 | 06-MAR-05:01 | -0.5 |
April | 0.133507E+09 | 8610.25 | 03-APR-03:02 | 9.22 |
May | 72638143.22 | 5938.79 | 22-MAY-03:02 | 18.22 |
June | 67483417.15 | 6933.89 | 05-JUN-03:02 | 15.00 |
July | 81376551.76 | 8639.84 | 02-JUL-16:11 | 31.83 |
August | 69993841.46 | 8587.44 | 20-AUG-15:21 | 35.00 |
September | 68086237.81 | 7429.01 | 03-SEP-13:41 | 32.52 |
October | 0.101758E+09 | 8313.91 | 15-OCT-14:42 | 20.92 |
November | 0.154414E+09 | 9302.15 | 27-NOV-04:01 | -3.9 |
December | 0.154020E+09 | 10864.52 | 11-DEC-04:01 | 2.12 |
Annual Sum or Average | 0.145146E+10 | |||
Minimum of Months | 67483417.15 | 5938.79 | -3.9 | |
Maximum of Months | 0.281188E+09 | 10864.52 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148968E+10 | 6937.17 | 22-JAN-15:02 | 13.80 |
February | 0.976131E+09 | 5545.44 | 19-FEB-13:42 | 15.92 |
March | 0.224540E+09 | 8795.91 | 12-MAR-16:21 | 20.00 |
April | 47726266.79 | 6005.36 | 30-APR-14:51 | 22.20 |
May | 51244613.34 | 5428.83 | 07-MAY-16:02 | 24.40 |
June | 46921433.29 | 7912.41 | 25-JUN-16:31 | 34.07 |
July | 59872943.63 | 8320.71 | 04-JUL-15:31 | 35.60 |
August | 45527851.16 | 7191.84 | 13-AUG-15:31 | 29.80 |
September | 54248717.74 | 7161.49 | 03-SEP-13:41 | 32.52 |
October | 0.121836E+09 | 7880.07 | 15-OCT-15:51 | 20.60 |
November | 0.416278E+09 | 5450.52 | 05-NOV-14:42 | 12.70 |
December | 0.136019E+10 | 6408.45 | 10-DEC-13:32 | 7.93 |
Annual Sum or Average | 0.489420E+10 | |||
Minimum of Months | 45527851.16 | 5428.83 | 7.93 | |
Maximum of Months | 0.148968E+10 | 8795.91 | 35.60 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.568428E+10 | 19656.11 | 17-JAN-05:13 | -3.3 |
February | 0.374617E+10 | 20669.67 | 06-FEB-05:13 | -4.4 |
March | 0.207704E+10 | 10015.64 | 06-MAR-06:01 | -2.9 |
April | 0.788551E+09 | 12429.25 | 14-APR-05:02 | 8.58 |
May | 0.398771E+09 | 13568.47 | 12-MAY-05:03 | 9.60 |
June | 0.157933E+09 | 13253.13 | 20-JUN-05:02 | 12.77 |
July | 71570976.69 | 9386.45 | 08-JUL-05:02 | 16.88 |
August | 75057538.70 | 10178.34 | 29-AUG-05:02 | 15.60 |
September | 0.201936E+09 | 11639.96 | 25-SEP-05:03 | 10.68 |
October | 0.127608E+10 | 13344.89 | 12-OCT-05:03 | 6.70 |
November | 0.264726E+10 | 16581.48 | 27-NOV-06:13 | -4.4 |
December | 0.588215E+10 | 18596.09 | 26-DEC-05:23 | -0.9 |
Annual Sum or Average | 0.230068E+11 | |||
Minimum of Months | 71570976.69 | 9386.45 | -4.4 | |
Maximum of Months | 0.588215E+10 | 20669.67 | 16.88 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12257781.81 | 202.72 | 17-JAN-05:17 | -3.3 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 12257781.81 | |||
Minimum of Months | 0.00 | 0.00 | -3.3 | |
Maximum of Months | 12257781.81 | 202.72 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.748106E+09 | 659.01 | 16-JAN-18:30 | -1.4 |
February | 3009020.85 | 432.21 | 06-FEB-00:25 | -4.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.751115E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.748106E+09 | 659.01 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113123E+11 | 11837.83 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.102611E+11 | 11837.83 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.121930E+11 | 11837.83 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.108909E+11 | 11837.83 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.117527E+11 | 11837.83 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.116958E+11 | 11837.83 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.109477E+11 | 11837.83 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.121930E+11 | 11837.83 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.108909E+11 | 11837.83 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.113123E+11 | 11837.83 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.111797E+11 | 11837.83 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.109477E+11 | 11837.83 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.135577E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.102611E+11 | 11837.83 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.121930E+11 | 11837.83 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.808776E+09 | 1212.73 | 09-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.701901E+09 | 1093.68 | 16-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.788097E+09 | 970.36 | 20-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.672585E+09 | 635.12 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.717825E+09 | 736.47 | 22-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.702811E+09 | 746.44 | 08-JUN-15:00 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.665905E+09 | 743.11 | 07-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.744266E+09 | 635.12 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.692412E+09 | 1075.38 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.759980E+09 | 1075.19 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.794888E+09 | 1334.85 | 13-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.818851E+09 | 1334.85 | 01-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.886830E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.665905E+09 | 635.12 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.818851E+09 | 1334.85 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.510232E+09 | 781.36 | 09-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.447236E+09 | 694.58 | 16-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.505175E+09 | 584.40 | 14-MAR-15:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.435657E+09 | 409.30 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.466866E+09 | 465.02 | 22-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.457479E+09 | 481.61 | 08-JUN-15:00 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.432369E+09 | 479.57 | 07-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.481801E+09 | 409.30 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.444654E+09 | 684.85 | 08-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.479908E+09 | 658.34 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.508373E+09 | 860.23 | 13-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.517313E+09 | 860.23 | 01-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.568706E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.432369E+09 | 409.30 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.517313E+09 | 860.23 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.765716E+09 | 1148.40 | 04-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.679488E+09 | 1084.12 | 16-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.778983E+09 | 951.46 | 20-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.675640E+09 | 635.14 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.724115E+09 | 738.78 | 22-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.712392E+09 | 746.65 | 08-JUN-15:00 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.672557E+09 | 743.16 | 07-JUL-15:00 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.748415E+09 | 669.18 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.689370E+09 | 1073.41 | 08-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.733087E+09 | 1053.17 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.762712E+09 | 1334.88 | 13-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.771220E+09 | 1334.88 | 01-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.871369E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.672557E+09 | 635.14 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.778983E+09 | 1334.88 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.503731E+09 | 724.09 | 04-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.442996E+09 | 706.67 | 16-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.503953E+09 | 665.69 | 22-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.433110E+09 | 437.97 | 05-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.461926E+09 | 479.93 | 22-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.454952E+09 | 585.53 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.430787E+09 | 476.33 | 07-JUL-15:00 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.480812E+09 | 453.16 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.444368E+09 | 696.51 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.481613E+09 | 704.16 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.494364E+09 | 860.23 | 13-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.506146E+09 | 860.23 | 01-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.563876E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.430787E+09 | 437.97 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.506146E+09 | 860.23 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.809119E+09 | 1216.43 | 09-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.702064E+09 | 1098.94 | 16-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.788178E+09 | 978.36 | 20-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.672625E+09 | 635.12 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.717699E+09 | 734.31 | 22-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.703004E+09 | 825.95 | 08-JUN-15:00 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.665953E+09 | 741.01 | 07-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.744174E+09 | 635.12 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.692399E+09 | 1081.07 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.759807E+09 | 1080.83 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.795215E+09 | 1334.85 | 13-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.819208E+09 | 1334.85 | 01-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.886944E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.665953E+09 | 635.12 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.819208E+09 | 1334.85 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.510106E+09 | 782.91 | 09-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.447148E+09 | 695.20 | 16-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.505112E+09 | 584.77 | 14-MAR-15:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.435623E+09 | 409.30 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.466725E+09 | 463.35 | 22-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.457439E+09 | 532.06 | 08-JUN-15:00 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.432367E+09 | 478.08 | 07-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.481771E+09 | 409.30 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.444610E+09 | 685.55 | 08-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.479689E+09 | 659.76 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.508259E+09 | 860.23 | 13-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.517117E+09 | 860.23 | 01-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.568597E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.432367E+09 | 409.30 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.517117E+09 | 860.23 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.766013E+09 | 1153.46 | 04-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.679337E+09 | 1089.72 | 16-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.779154E+09 | 960.10 | 20-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.675803E+09 | 635.14 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.724095E+09 | 736.65 | 22-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.712668E+09 | 827.41 | 08-JUN-15:00 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.672740E+09 | 741.07 | 07-JUL-15:00 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.748547E+09 | 664.35 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.689476E+09 | 1079.16 | 08-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.731966E+09 | 1059.57 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.763142E+09 | 1334.88 | 13-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.772134E+09 | 1334.88 | 01-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.871507E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.672740E+09 | 635.14 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.779154E+09 | 1334.88 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.503532E+09 | 725.70 | 04-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.443033E+09 | 707.02 | 16-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.503861E+09 | 665.94 | 22-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.433138E+09 | 435.39 | 05-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.461890E+09 | 478.45 | 22-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.454860E+09 | 585.82 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.430736E+09 | 474.80 | 07-JUL-15:00 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.480841E+09 | 450.73 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.444252E+09 | 696.87 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.481316E+09 | 704.51 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.494384E+09 | 860.23 | 13-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.505911E+09 | 860.23 | 01-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.563775E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.430736E+09 | 435.39 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.505911E+09 | 860.23 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.809121E+09 | 1216.53 | 09-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.702010E+09 | 1098.66 | 16-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.788187E+09 | 977.99 | 20-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.672623E+09 | 635.12 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.717681E+09 | 734.15 | 22-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.702998E+09 | 825.32 | 08-JUN-15:00 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.665946E+09 | 740.86 | 07-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.744164E+09 | 635.12 | 01-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.692395E+09 | 1080.76 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.759812E+09 | 1080.55 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.795209E+09 | 1334.85 | 13-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.819222E+09 | 1334.85 | 01-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.886937E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.665946E+09 | 635.12 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.819222E+09 | 1334.85 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.510113E+09 | 782.99 | 09-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.447151E+09 | 695.02 | 16-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.505096E+09 | 584.51 | 14-MAR-15:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.435623E+09 | 409.30 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.466719E+09 | 463.23 | 22-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.457436E+09 | 531.68 | 08-JUN-15:00 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.432360E+09 | 477.99 | 07-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.481780E+09 | 409.30 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.444601E+09 | 685.36 | 08-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.479696E+09 | 659.61 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.508271E+09 | 860.23 | 13-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.517155E+09 | 860.23 | 01-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.568600E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.432360E+09 | 409.30 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.517155E+09 | 860.23 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.766016E+09 | 1153.36 | 04-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.679330E+09 | 1089.44 | 16-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.779142E+09 | 959.73 | 20-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.675800E+09 | 635.14 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.724087E+09 | 736.49 | 22-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.712662E+09 | 826.78 | 08-JUN-15:00 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.672732E+09 | 740.91 | 07-JUL-15:00 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.748543E+09 | 664.27 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.689451E+09 | 1078.86 | 08-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.731960E+09 | 1059.29 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.763143E+09 | 1334.88 | 13-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.772141E+09 | 1334.88 | 01-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.871501E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.672732E+09 | 635.14 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.779142E+09 | 1334.88 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.503528E+09 | 725.65 | 04-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.443032E+09 | 706.84 | 16-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.503857E+09 | 665.81 | 22-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.433140E+09 | 435.28 | 05-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.461890E+09 | 478.35 | 22-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.454859E+09 | 585.57 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.430729E+09 | 474.70 | 07-JUL-15:00 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.480842E+09 | 450.61 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.444283E+09 | 696.68 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.481322E+09 | 704.35 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.494389E+09 | 860.23 | 13-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.505918E+09 | 860.23 | 01-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.563779E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.430729E+09 | 435.28 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.505918E+09 | 860.23 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.318958E+10 | 3337.76 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.289319E+10 | 3337.76 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.343791E+10 | 3337.76 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.307076E+10 | 3337.76 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.331375E+10 | 3337.76 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.329773E+10 | 3337.76 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.308678E+10 | 3337.76 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.343791E+10 | 3337.76 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.307076E+10 | 3337.76 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.318958E+10 | 3337.76 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.315220E+10 | 3337.76 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.308678E+10 | 3337.76 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.382269E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.289319E+10 | 3337.76 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.343791E+10 | 3337.76 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.113123E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.102611E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.108909E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.117527E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.116958E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.109477E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.108909E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.113123E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.111797E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.109477E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.135577E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.102611E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.808776E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176378E+09 |
February | 0.136985E+10 | 0.701901E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163721E+09 |
March | 0.163685E+10 | 0.788097E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161152E+09 |
April | 0.145243E+10 | 0.672585E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 255951.58 | 0.113971E+09 |
May | 0.157338E+10 | 0.717825E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2712530.76 | 77581739.22 |
June | 0.156900E+10 | 0.702811E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12832692.84 | 40152917.32 |
July | 0.145680E+10 | 0.665905E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18318219.64 | 20381498.56 |
August | 0.163685E+10 | 0.744266E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9249249.82 | 27573922.65 |
September | 0.145243E+10 | 0.692412E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3145734.47 | 46262260.39 |
October | 0.150991E+10 | 0.759980E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 758924.64 | 86986895.04 |
November | 0.149516E+10 | 0.794888E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143182E+09 |
December | 0.145680E+10 | 0.818851E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164976E+09 |
Annual Sum or Average | 0.181194E+11 | 0.886830E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47273303.75 | 0.122232E+10 |
Minimum of Months | 0.136985E+10 | 0.665905E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20381498.56 |
Maximum of Months | 0.163685E+10 | 0.818851E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18318219.64 | 0.176378E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.510232E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118931E+09 |
February | 0.882782E+09 | 0.447236E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109603E+09 |
March | 0.105485E+10 | 0.505175E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107093E+09 |
April | 0.936002E+09 | 0.435657E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 175577.21 | 75861733.21 |
May | 0.101394E+10 | 0.466866E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1717337.65 | 52735426.10 |
June | 0.101113E+10 | 0.457479E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8794787.35 | 25761309.62 |
July | 0.938820E+09 | 0.432369E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12574177.79 | 12344491.70 |
August | 0.105485E+10 | 0.481801E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6373538.74 | 16524987.41 |
September | 0.936002E+09 | 0.444654E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2062717.98 | 31018545.23 |
October | 0.973041E+09 | 0.479908E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 491699.21 | 58436108.52 |
November | 0.963541E+09 | 0.508373E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95348288.29 |
December | 0.938820E+09 | 0.517313E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108879E+09 |
Annual Sum or Average | 0.116768E+11 | 0.568706E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32189835.94 | 0.812537E+09 |
Minimum of Months | 0.882782E+09 | 0.432369E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12344491.70 |
Maximum of Months | 0.105485E+10 | 0.517313E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12574177.79 | 0.118931E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.765716E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183577E+09 |
February | 0.136988E+10 | 0.679488E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170363E+09 |
March | 0.163688E+10 | 0.778983E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164914E+09 |
April | 0.145246E+10 | 0.675640E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 248204.08 | 0.116825E+09 |
May | 0.157341E+10 | 0.724115E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2440712.46 | 78050247.35 |
June | 0.156904E+10 | 0.712392E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12955137.93 | 39390722.00 |
July | 0.145684E+10 | 0.672557E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17985687.85 | 20496632.01 |
August | 0.163688E+10 | 0.748415E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8873686.55 | 28951825.74 |
September | 0.145246E+10 | 0.689370E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2783071.23 | 49705883.93 |
October | 0.150994E+10 | 0.733087E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 625207.52 | 92725163.26 |
November | 0.149520E+10 | 0.762712E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150673E+09 |
December | 0.145684E+10 | 0.771220E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171272E+09 |
Annual Sum or Average | 0.181198E+11 | 0.871369E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45911707.62 | 0.126694E+10 |
Minimum of Months | 0.136988E+10 | 0.672557E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20496632.01 |
Maximum of Months | 0.163688E+10 | 0.778983E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17985687.85 | 0.183577E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.503731E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124666E+09 |
February | 0.882782E+09 | 0.442996E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118412E+09 |
March | 0.105485E+10 | 0.503953E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118855E+09 |
April | 0.936002E+09 | 0.433110E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 165382.21 | 87255750.01 |
May | 0.101394E+10 | 0.461926E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1489221.43 | 57261098.48 |
June | 0.101113E+10 | 0.454952E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7839449.36 | 30594546.78 |
July | 0.938820E+09 | 0.430787E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11120719.48 | 16804648.22 |
August | 0.105485E+10 | 0.480812E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5669169.39 | 23012513.79 |
September | 0.936002E+09 | 0.444368E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1936969.78 | 35026339.42 |
October | 0.973041E+09 | 0.481613E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 456067.70 | 64703486.66 |
November | 0.963541E+09 | 0.494364E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105866E+09 |
December | 0.938820E+09 | 0.506146E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123050E+09 |
Annual Sum or Average | 0.116768E+11 | 0.563876E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28676979.35 | 0.905508E+09 |
Minimum of Months | 0.882782E+09 | 0.430787E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16804648.22 |
Maximum of Months | 0.105485E+10 | 0.506146E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11120719.48 | 0.124666E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.809119E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366012E+09 |
February | 0.136985E+10 | 0.702064E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341967E+09 |
March | 0.163685E+10 | 0.788178E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340562E+09 |
April | 0.145243E+10 | 0.672625E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 670707.66 | 0.249102E+09 |
May | 0.157338E+10 | 0.717699E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6774508.59 | 0.173807E+09 |
June | 0.156900E+10 | 0.703004E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29649240.17 | 94147010.79 |
July | 0.145680E+10 | 0.665953E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42702315.29 | 53140848.32 |
August | 0.163685E+10 | 0.744174E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22130413.55 | 70202970.85 |
September | 0.145243E+10 | 0.692399E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7494018.96 | 0.103454E+09 |
October | 0.150991E+10 | 0.759807E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1803105.83 | 0.185359E+09 |
November | 0.149516E+10 | 0.795215E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295174E+09 |
December | 0.145680E+10 | 0.819208E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333741E+09 |
Annual Sum or Average | 0.181194E+11 | 0.886944E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111224E+09 | 0.260667E+10 |
Minimum of Months | 0.136985E+10 | 0.665953E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53140848.32 |
Maximum of Months | 0.163685E+10 | 0.819208E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42702315.29 | 0.366012E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.510106E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252817E+09 |
February | 0.649041E+09 | 0.447148E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236366E+09 |
March | 0.773965E+09 | 0.505112E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237374E+09 |
April | 0.688021E+09 | 0.435623E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 376592.14 | 0.179299E+09 |
May | 0.744847E+09 | 0.466725E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3716521.88 | 0.122803E+09 |
June | 0.742030E+09 | 0.457439E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19544658.84 | 63983639.53 |
July | 0.690839E+09 | 0.432367E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27627325.33 | 37903205.62 |
August | 0.773965E+09 | 0.481771E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14167994.73 | 49921281.23 |
September | 0.688021E+09 | 0.444610E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4632572.15 | 72731463.25 |
October | 0.715730E+09 | 0.479689E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1080515.77 | 0.131396E+09 |
November | 0.708685E+09 | 0.508259E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205929E+09 |
December | 0.690839E+09 | 0.517117E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229275E+09 |
Annual Sum or Average | 0.858171E+10 | 0.568597E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71146180.84 | 0.181980E+10 |
Minimum of Months | 0.649041E+09 | 0.432367E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37903205.62 |
Maximum of Months | 0.773965E+09 | 0.517117E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27627325.33 | 0.252817E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.766013E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418869E+09 |
February | 0.136988E+10 | 0.679337E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389102E+09 |
March | 0.163688E+10 | 0.779154E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374816E+09 |
April | 0.145246E+10 | 0.675803E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 508678.62 | 0.269106E+09 |
May | 0.157341E+10 | 0.724095E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5366859.93 | 0.179428E+09 |
June | 0.156904E+10 | 0.712668E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29766932.77 | 93265749.55 |
July | 0.145684E+10 | 0.672740E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41180318.64 | 54345554.58 |
August | 0.163688E+10 | 0.748547E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20322049.60 | 75917045.81 |
September | 0.145246E+10 | 0.689476E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6025237.41 | 0.116980E+09 |
October | 0.150994E+10 | 0.731966E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1216738.00 | 0.215215E+09 |
November | 0.149520E+10 | 0.763142E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343927E+09 |
December | 0.145684E+10 | 0.772134E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384484E+09 |
Annual Sum or Average | 0.181198E+11 | 0.871507E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104387E+09 | 0.291545E+10 |
Minimum of Months | 0.136988E+10 | 0.672740E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54345554.58 |
Maximum of Months | 0.163688E+10 | 0.779154E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41180318.64 | 0.418869E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.503532E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260416E+09 |
February | 0.882782E+09 | 0.443033E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245077E+09 |
March | 0.105485E+10 | 0.503861E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245024E+09 |
April | 0.936002E+09 | 0.433138E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 340610.33 | 0.185383E+09 |
May | 0.101394E+10 | 0.461890E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3395247.99 | 0.126789E+09 |
June | 0.101113E+10 | 0.454860E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18249069.55 | 69231252.84 |
July | 0.938820E+09 | 0.430736E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26704467.68 | 40484247.32 |
August | 0.105485E+10 | 0.480841E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13506029.80 | 54140086.73 |
September | 0.936002E+09 | 0.444252E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4436470.92 | 77573116.30 |
October | 0.973041E+09 | 0.481316E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1035091.63 | 0.136161E+09 |
November | 0.963541E+09 | 0.494384E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212718E+09 |
December | 0.938820E+09 | 0.505911E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238854E+09 |
Annual Sum or Average | 0.116768E+11 | 0.563775E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67666987.89 | 0.189185E+10 |
Minimum of Months | 0.882782E+09 | 0.430736E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40484247.32 |
Maximum of Months | 0.105485E+10 | 0.505911E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26704467.68 | 0.260416E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.809121E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411276E+09 |
February | 0.136985E+10 | 0.702010E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390331E+09 |
March | 0.163685E+10 | 0.788187E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389426E+09 |
April | 0.145243E+10 | 0.672623E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 748533.02 | 0.294647E+09 |
May | 0.157338E+10 | 0.717681E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7166759.53 | 0.210380E+09 |
June | 0.156900E+10 | 0.702998E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34624001.43 | 0.116836E+09 |
July | 0.145680E+10 | 0.665946E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49549143.36 | 68763118.24 |
August | 0.163685E+10 | 0.744164E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25205787.07 | 89403139.70 |
September | 0.145243E+10 | 0.692395E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8637035.46 | 0.126752E+09 |
October | 0.150991E+10 | 0.759812E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2072154.80 | 0.214263E+09 |
November | 0.149516E+10 | 0.795209E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328196E+09 |
December | 0.145680E+10 | 0.819222E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373746E+09 |
Annual Sum or Average | 0.181194E+11 | 0.886937E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128003E+09 | 0.301402E+10 |
Minimum of Months | 0.136985E+10 | 0.665946E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68763118.24 |
Maximum of Months | 0.163685E+10 | 0.819222E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49549143.36 | 0.411276E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.510113E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284735E+09 |
February | 0.882782E+09 | 0.447151E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270722E+09 |
March | 0.105485E+10 | 0.505096E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275997E+09 |
April | 0.936002E+09 | 0.435623E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 385308.16 | 0.216998E+09 |
May | 0.101394E+10 | 0.466719E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4114552.66 | 0.150840E+09 |
June | 0.101113E+10 | 0.457436E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22975106.70 | 79774960.16 |
July | 0.938820E+09 | 0.432360E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32570544.86 | 48829157.47 |
August | 0.105485E+10 | 0.481780E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16501228.14 | 63592253.11 |
September | 0.936002E+09 | 0.444601E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5415992.13 | 89905177.84 |
October | 0.973041E+09 | 0.479696E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1221010.25 | 0.155161E+09 |
November | 0.963541E+09 | 0.508271E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231589E+09 |
December | 0.938820E+09 | 0.517155E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257500E+09 |
Annual Sum or Average | 0.116768E+11 | 0.568600E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83183742.90 | 0.212564E+10 |
Minimum of Months | 0.882782E+09 | 0.432360E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48829157.47 |
Maximum of Months | 0.105485E+10 | 0.517155E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32570544.86 | 0.284735E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.766016E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475776E+09 |
February | 0.136988E+10 | 0.679330E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448652E+09 |
March | 0.163688E+10 | 0.779142E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436741E+09 |
April | 0.145246E+10 | 0.675800E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 545241.06 | 0.321381E+09 |
May | 0.157341E+10 | 0.724087E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6078375.93 | 0.217187E+09 |
June | 0.156904E+10 | 0.712662E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35233812.99 | 0.114832E+09 |
July | 0.145684E+10 | 0.672732E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48911857.48 | 69546871.47 |
August | 0.163688E+10 | 0.748543E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24090824.43 | 96110810.91 |
September | 0.145246E+10 | 0.689451E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7302837.14 | 0.143856E+09 |
October | 0.150994E+10 | 0.731960E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1580628.16 | 0.254975E+09 |
November | 0.149520E+10 | 0.763143E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393836E+09 |
December | 0.145684E+10 | 0.772141E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437178E+09 |
Annual Sum or Average | 0.181198E+11 | 0.871501E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123744E+09 | 0.341007E+10 |
Minimum of Months | 0.136988E+10 | 0.672732E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69546871.47 |
Maximum of Months | 0.163688E+10 | 0.779142E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48911857.48 | 0.475776E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.503528E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297148E+09 |
February | 0.882782E+09 | 0.443032E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284275E+09 |
March | 0.105485E+10 | 0.503857E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286472E+09 |
April | 0.936002E+09 | 0.433140E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 365824.87 | 0.222850E+09 |
May | 0.101394E+10 | 0.461890E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3974273.06 | 0.153933E+09 |
June | 0.101113E+10 | 0.454859E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22133465.49 | 85389107.75 |
July | 0.938820E+09 | 0.430729E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32064656.78 | 51071828.84 |
August | 0.105485E+10 | 0.480842E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16133034.21 | 67992900.67 |
September | 0.936002E+09 | 0.444283E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5325851.67 | 95242199.19 |
October | 0.973041E+09 | 0.481322E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1212079.58 | 0.161268E+09 |
November | 0.963541E+09 | 0.494389E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243122E+09 |
December | 0.938820E+09 | 0.505918E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273112E+09 |
Annual Sum or Average | 0.116768E+11 | 0.563779E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81209185.66 | 0.222188E+10 |
Minimum of Months | 0.882782E+09 | 0.430729E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51071828.84 |
Maximum of Months | 0.105485E+10 | 0.505918E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32064656.78 | 0.297148E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.318958E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.289319E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.343791E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.307076E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.331375E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.329773E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.308678E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.343791E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.307076E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.318958E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.315220E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.308678E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.382269E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.289319E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.343791E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379609E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350196E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341313E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202954.55 | 0.241790E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4611890.56 | 0.162293E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24333220.76 | 84473081.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35334247.72 | 44853646.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16798891.46 | 62065869.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5123229.77 | 97636459.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 957938.37 | 0.186540E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306681E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353419E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87362373.17 | 0.261087E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44853646.92 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35334247.72 | 0.379609E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642188E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597668E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586656E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425551.02 | 0.419509E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9010861.39 | 0.285840E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44371312.04 | 0.150114E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65141902.70 | 81285900.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31228834.93 | 0.112266E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9494226.31 | 0.171800E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1816304.79 | 0.323399E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523318E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589852E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161489E+09 | 0.448390E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81285900.63 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65141902.70 | 0.642188E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641777E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614942E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621792E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10727.09 | 0.471267E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4527557.01 | 0.325245E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38896780.71 | 0.172207E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56196890.99 | 99254002.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25944768.92 | 0.134459E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6356034.70 | 0.196375E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 901127.94 | 0.344427E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530602E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586923E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132834E+09 | 0.473927E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99254002.17 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56196890.99 | 0.641777E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 11837.83 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 11837.83 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 11837.83 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 11837.83 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 11837.83 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 11837.83 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 11837.83 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 11837.83 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 11837.83 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 11837.83 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 11837.83 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 11837.83 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 11837.83 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 11837.83 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1212.73 | 09-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 520.07 | 16-JAN-18:00 |
February | 2010.79 | 01-FEB-10:09 | 1093.68 | 16-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 387.79 | 05-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 970.36 | 20-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 350.10 | 14-MAR-03:00 |
April | 2010.79 | 03-APR-09:09 | 635.12 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.32 | 26-APR-15:00 | 379.21 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 736.47 | 22-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.65 | 14-MAY-17:00 | 234.43 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 746.44 | 08-JUN-15:00 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.39 | 18-JUN-16:00 | 180.48 | 10-JUN-01:10 |
July | 2010.79 | 03-JUL-09:09 | 743.11 | 07-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.83 | 04-JUL-14:51 | 81.19 | 15-JUL-19:10 |
August | 2010.79 | 01-AUG-09:09 | 635.12 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.52 | 20-AUG-17:00 | 96.33 | 22-AUG-21:53 |
September | 2010.79 | 01-SEP-09:09 | 1075.38 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.21 | 03-SEP-14:50 | 134.53 | 18-SEP-01:00 |
October | 2010.79 | 02-OCT-09:09 | 1075.19 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.15 | 01-OCT-16:00 | 215.80 | 11-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 1334.85 | 13-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 393.40 | 26-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 1334.85 | 01-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 550.93 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.19 | |||||
Maximum of Months | 2010.79 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 124.83 | 550.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 781.36 | 09-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 348.34 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 694.58 | 16-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 260.32 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 584.40 | 14-MAR-15:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 232.66 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 409.30 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 | 26-APR-15:00 | 250.01 | 07-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 465.02 | 22-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.21 | 14-MAY-17:00 | 154.19 | 03-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 481.61 | 08-JUN-15:00 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.07 | 18-JUN-16:00 | 118.41 | 10-JUN-01:10 |
July | 1295.83 | 03-JUL-09:09 | 479.57 | 07-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.23 | 04-JUL-15:07 | 53.45 | 15-JUL-19:10 |
August | 1295.83 | 01-AUG-09:09 | 409.30 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.98 | 05-AUG-17:10 | 70.60 | 27-AUG-08:10 |
September | 1295.83 | 01-SEP-09:09 | 684.85 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 | 03-SEP-14:25 | 92.39 | 18-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 658.34 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.14 | 01-OCT-16:20 | 142.51 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 13-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 258.26 | 26-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 361.56 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.45 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 83.23 | 361.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1148.40 | 04-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 517.68 | 16-JAN-18:00 |
February | 2010.83 | 01-FEB-10:09 | 1084.12 | 16-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 404.40 | 05-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 951.46 | 20-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 356.82 | 14-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 635.14 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.31 | 26-APR-15:00 | 383.86 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 738.78 | 22-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.92 | 14-MAY-17:00 | 230.80 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 746.65 | 08-JUN-15:00 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.71 | 18-JUN-16:00 | 176.80 | 10-JUN-01:10 |
July | 2010.83 | 03-JUL-09:09 | 743.16 | 07-JUL-15:00 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.79 | 04-JUL-15:05 | 83.50 | 15-JUL-19:10 |
August | 2010.83 | 01-AUG-09:09 | 669.18 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.96 | 20-AUG-17:00 | 100.71 | 22-AUG-21:53 |
September | 2010.83 | 01-SEP-09:09 | 1073.41 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.39 | 03-SEP-14:25 | 144.27 | 18-SEP-01:00 |
October | 2010.83 | 02-OCT-09:09 | 1053.17 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.15 | 11-OCT-14:10 | 223.12 | 11-OCT-23:00 |
November | 2010.83 | 01-NOV-09:09 | 1334.88 | 13-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 398.04 | 03-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 1334.88 | 01-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 562.12 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 | |||||
Maximum of Months | 2010.83 | 1334.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 122.79 | 562.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 724.09 | 04-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 365.34 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 706.67 | 16-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 284.96 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 665.69 | 22-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 262.27 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 437.97 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 | 26-APR-15:00 | 287.72 | 07-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 479.93 | 22-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.32 | 14-MAY-16:55 | 172.38 | 18-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 585.53 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.85 | 18-JUN-16:00 | 142.40 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 476.33 | 07-JUL-15:00 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.12 | 04-JUL-15:10 | 65.90 | 15-JUL-19:10 |
August | 1295.83 | 01-AUG-09:09 | 453.16 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.74 | 20-AUG-17:00 | 83.82 | 22-AUG-21:53 |
September | 1295.83 | 01-SEP-09:09 | 696.51 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.87 | 03-SEP-15:08 | 102.77 | 18-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 704.16 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.03 | 11-OCT-13:00 | 158.91 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 13-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 289.70 | 03-NOV-24:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 410.21 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 437.97 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.90 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 78.12 | 410.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1216.43 | 09-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1045.61 | 16-JAN-18:00 |
February | 2010.79 | 01-FEB-10:09 | 1098.94 | 16-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 800.74 | 05-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 978.36 | 20-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 723.21 | 14-MAR-03:00 |
April | 2010.79 | 03-APR-09:09 | 635.12 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.51 | 01-APR-17:10 | 821.55 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 734.31 | 22-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.42 | 14-MAY-16:30 | 522.78 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 825.95 | 08-JUN-15:00 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.94 | 18-JUN-15:50 | 394.61 | 10-JUN-01:20 |
July | 2010.79 | 03-JUL-09:09 | 741.01 | 07-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.89 | 04-JUL-14:54 | 215.52 | 15-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 635.12 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.46 | 20-AUG-17:00 | 215.72 | 22-AUG-22:00 |
September | 2010.79 | 01-SEP-09:09 | 1081.07 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.18 | 03-SEP-14:50 | 290.87 | 07-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 1080.83 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.83 | 01-OCT-16:10 | 480.92 | 11-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 1334.85 | 13-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 822.04 | 03-NOV-24:00 |
December | 2010.79 | 01-DEC-10:09 | 1334.85 | 01-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1119.40 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.52 | |||||
Maximum of Months | 2010.79 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 299.89 | 1119.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 782.91 | 09-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 715.53 | 16-JAN-18:00 |
February | 1239.33 | 01-FEB-08:09 | 695.20 | 16-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 551.54 | 05-FEB-01:00 |
March | 1239.33 | 01-MAR-08:09 | 584.77 | 14-MAR-15:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 503.35 | 14-MAR-03:00 |
April | 1239.33 | 03-APR-07:10 | 409.30 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.21 | 26-APR-15:00 | 568.95 | 23-APR-09:00 |
May | 1239.33 | 01-MAY-07:10 | 463.35 | 22-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.65 | 14-MAY-17:10 | 346.65 | 03-MAY-22:00 |
June | 1239.33 | 01-JUN-07:10 | 532.06 | 08-JUN-15:00 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.08 | 18-JUN-16:24 | 265.94 | 10-JUN-01:10 |
July | 1239.33 | 03-JUL-07:10 | 478.08 | 07-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.02 | 04-JUL-14:53 | 154.24 | 15-JUL-19:00 |
August | 1239.33 | 01-AUG-07:10 | 409.30 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.37 | 20-AUG-17:00 | 171.12 | 27-AUG-08:10 |
September | 1239.33 | 01-SEP-07:10 | 685.55 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.89 | 03-SEP-14:25 | 204.31 | 18-SEP-01:00 |
October | 1239.33 | 02-OCT-07:10 | 659.76 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.76 | 01-OCT-16:10 | 323.13 | 11-OCT-23:00 |
November | 1239.33 | 01-NOV-07:10 | 860.23 | 13-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 554.11 | 03-NOV-24:00 |
December | 1239.33 | 01-DEC-08:09 | 860.23 | 01-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 758.87 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.24 | |||||
Maximum of Months | 1239.33 | 860.23 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 207.02 | 758.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1153.46 | 04-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1169.81 | 16-JAN-18:00 |
February | 2010.83 | 01-FEB-10:09 | 1089.72 | 16-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 909.82 | 05-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 960.10 | 20-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 786.76 | 14-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 635.14 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 26-APR-15:00 | 856.74 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 736.65 | 22-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.10 | 14-MAY-17:10 | 519.84 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 827.41 | 08-JUN-15:00 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.90 | 18-JUN-16:30 | 391.93 | 10-JUN-01:20 |
July | 2010.83 | 03-JUL-09:09 | 741.07 | 07-JUL-15:00 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 294.52 | 04-JUL-14:53 | 222.63 | 15-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 664.35 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.40 | 20-AUG-17:00 | 231.11 | 22-AUG-22:00 |
September | 2010.83 | 01-SEP-09:09 | 1079.16 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.95 | 03-SEP-14:25 | 329.91 | 17-SEP-19:53 |
October | 2010.83 | 02-OCT-09:09 | 1059.57 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.61 | 11-OCT-15:00 | 506.98 | 11-OCT-23:00 |
November | 2010.83 | 01-NOV-09:09 | 1334.88 | 13-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 887.54 | 03-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 1334.88 | 01-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1230.77 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.63 | |||||
Maximum of Months | 2010.83 | 1334.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 294.52 | 1230.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 725.70 | 04-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 748.44 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 707.02 | 16-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 584.36 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 665.94 | 22-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 513.17 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 435.39 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.21 | 26-APR-15:00 | 595.57 | 07-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 478.45 | 22-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.88 | 21-MAY-16:45 | 372.79 | 18-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 585.82 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.28 | 18-JUN-16:00 | 293.48 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 474.80 | 07-JUL-15:00 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.82 | 04-JUL-14:53 | 161.54 | 15-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 450.73 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.51 | 20-AUG-17:00 | 166.80 | 08-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 696.87 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.44 | 03-SEP-14:25 | 222.96 | 17-SEP-19:53 |
October | 1295.83 | 02-OCT-09:09 | 704.51 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 11-OCT-13:00 | 337.88 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 13-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 585.14 | 03-NOV-24:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 789.67 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 435.39 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.54 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 193.82 | 789.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1216.53 | 09-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1071.96 | 16-JAN-18:00 |
February | 2010.79 | 01-FEB-10:09 | 1098.66 | 16-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 882.60 | 05-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 977.99 | 20-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 826.00 | 14-MAR-03:00 |
April | 2010.79 | 03-APR-09:09 | 635.12 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.96 | 01-APR-17:10 | 968.71 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 734.15 | 22-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.27 | 14-MAY-16:40 | 620.28 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 825.32 | 08-JUN-15:00 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.98 | 18-JUN-16:00 | 467.91 | 10-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 740.86 | 07-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.71 | 04-JUL-15:05 | 285.03 | 15-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 635.12 | 01-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.93 | 20-AUG-17:00 | 270.49 | 22-AUG-22:00 |
September | 2010.79 | 01-SEP-09:09 | 1080.76 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.00 | 03-SEP-14:50 | 351.11 | 07-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 1080.55 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.79 | 01-OCT-16:00 | 584.15 | 11-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 1334.85 | 13-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 949.06 | 03-NOV-21:13 |
December | 2010.79 | 01-DEC-10:09 | 1334.85 | 01-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1257.85 | 14-DEC-04:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.49 | |||||
Maximum of Months | 2010.79 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 350.71 | 1257.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 782.99 | 09-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 738.00 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 695.02 | 16-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 610.33 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 584.51 | 14-MAR-15:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 583.83 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 409.30 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 | 26-APR-15:00 | 685.01 | 23-APR-09:00 |
May | 1295.83 | 01-MAY-09:09 | 463.23 | 22-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.43 | 14-MAY-16:40 | 415.38 | 18-MAY-03:02 |
June | 1295.83 | 01-JUN-09:09 | 531.68 | 08-JUN-15:00 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.50 | 18-JUN-15:56 | 318.07 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 477.99 | 07-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.85 | 04-JUL-15:05 | 204.99 | 15-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 409.30 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.91 | 20-AUG-17:00 | 212.97 | 27-AUG-08:10 |
September | 1295.83 | 01-SEP-09:09 | 685.36 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.77 | 03-SEP-14:36 | 249.67 | 18-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 659.61 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.06 | 01-OCT-16:00 | 393.71 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 13-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 647.76 | 03-NOV-21:17 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 851.25 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.99 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 244.85 | 851.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1153.36 | 04-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1232.90 | 16-JAN-18:00 |
February | 2010.83 | 01-FEB-10:09 | 1089.44 | 16-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1027.34 | 05-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 959.73 | 20-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 916.07 | 14-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 635.14 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.69 | 26-APR-15:00 | 1021.83 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 736.49 | 22-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.30 | 14-MAY-16:40 | 615.81 | 18-MAY-03:02 |
June | 2010.83 | 01-JUN-09:09 | 826.78 | 08-JUN-15:00 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.45 | 18-JUN-16:00 | 463.94 | 10-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 740.91 | 07-JUL-15:00 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 353.31 | 04-JUL-15:05 | 294.26 | 15-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 664.27 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.20 | 20-AUG-17:00 | 290.48 | 22-AUG-22:00 |
September | 2010.83 | 01-SEP-09:09 | 1078.86 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.54 | 03-SEP-14:34 | 408.11 | 17-SEP-20:00 |
October | 2010.83 | 02-OCT-09:09 | 1059.29 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.82 | 11-OCT-14:10 | 618.16 | 11-OCT-23:00 |
November | 2010.83 | 01-NOV-09:09 | 1334.88 | 13-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1059.76 | 03-NOV-21:13 |
December | 2010.83 | 01-DEC-10:09 | 1334.88 | 01-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1392.58 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.48 | |||||
Maximum of Months | 2010.83 | 1334.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 353.31 | 1392.58 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 725.65 | 04-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 801.06 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 706.84 | 16-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 663.29 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 665.81 | 22-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 597.41 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 435.28 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 | 26-APR-15:00 | 726.41 | 15-APR-17:03 |
May | 1295.83 | 01-MAY-09:09 | 478.35 | 22-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.68 | 14-MAY-17:16 | 454.09 | 18-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 585.57 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.56 | 18-JUN-16:00 | 352.47 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 474.70 | 07-JUL-15:00 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.89 | 04-JUL-15:10 | 211.08 | 15-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 450.61 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.10 | 20-AUG-17:00 | 208.74 | 08-AUG-01:00 |
September | 1295.83 | 01-SEP-09:09 | 696.68 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.71 | 03-SEP-14:36 | 273.43 | 17-SEP-20:00 |
October | 1295.83 | 02-OCT-09:09 | 704.35 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.53 | 11-OCT-13:00 | 412.81 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 13-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 687.90 | 03-NOV-21:20 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 901.98 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 435.28 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.74 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 221.89 | 901.98 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 3337.76 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 3337.76 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 3337.76 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 3337.76 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 3337.76 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 3337.76 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 3337.76 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 3337.76 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 3337.76 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 3337.76 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 3337.76 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 3337.76 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 3337.76 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1099.42 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 848.40 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 739.70 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.78 | 26-APR-15:00 | 791.54 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.60 | 14-MAY-17:00 | 482.29 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.72 | 18-JUN-16:00 | 374.13 | 10-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.42 | 04-JUL-14:51 | 169.75 | 15-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.93 | 05-AUG-17:02 | 190.12 | 22-AUG-22:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.93 | 03-SEP-14:52 | 275.15 | 18-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.09 | 01-OCT-16:00 | 444.35 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 851.00 | 26-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1186.21 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.75 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.42 | 1186.21 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1840.49 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1452.13 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1259.84 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 17-APR-15:00 | 1388.23 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.40 | 14-MAY-16:52 | 854.96 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.60 | 18-JUN-16:00 | 656.79 | 10-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.62 | 04-JUL-15:00 | 316.85 | 15-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.52 | 05-AUG-17:02 | 326.90 | 22-AUG-22:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.42 | 03-SEP-14:52 | 473.53 | 18-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.64 | 01-OCT-16:00 | 782.45 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1443.95 | 26-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2007.24 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.85 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.62 | 2007.24 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1757.62 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1416.67 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1312.03 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 | 13-APR-17:00 | 1501.35 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.57 | 14-MAY-17:00 | 916.58 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.33 | 18-JUN-16:00 | 690.44 | 04-JUN-16:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.82 | 04-JUL-16:51 | 429.82 | 15-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.83 | 20-AUG-17:00 | 375.67 | 08-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.57 | 03-SEP-14:20 | 525.12 | 18-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.22 | 01-OCT-16:00 | 873.19 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1524.35 | 03-NOV-21:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2008.85 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.67 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.82 | 2008.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 96079.45 | 02-JAN-04:01 | 0.00 | 5261.77 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95709.72 | 13-FEB-04:12 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 94938.96 | 27-MAR-03:02 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96031.11 | 03-APR-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 90367.51 | 08-MAY-03:02 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 90431.24 | 20-JUN-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 80936.43 | 24-JUL-03:02 | 0.00 | 3946.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 81674.88 | 29-AUG-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86787.53 | 25-SEP-04:33 | 0.00 | 5261.11 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 96421.87 | 23-OCT-03:02 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 96358.15 | 06-NOV-04:03 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 99506.48 | 26-DEC-04:01 | 0.00 | 4604.05 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 80936.43 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 99506.48 | 0.00 | 5261.77 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 79998.77 | 02-JAN-04:01 | 0.00 | 4725.44 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 77998.49 | 21-FEB-05:01 | 0.00 | 9449.70 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 77652.34 | 06-MAR-05:01 | 0.00 | 8268.49 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80188.60 | 24-APR-03:02 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80784.94 | 30-MAY-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 81363.13 | 05-JUN-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 77325.47 | 10-JUL-05:04 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 73702.45 | 07-AUG-05:03 | 6448.95 | 4724.85 | 30589.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80281.51 | 18-SEP-03:02 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 81648.50 | 10-OCT-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 79880.82 | 13-NOV-04:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 79675.90 | 26-DEC-04:01 | 0.00 | 4134.76 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 73702.45 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81648.50 | 8061.19 | 9449.70 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 32835.33 | 06-JAN-06:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 65564.13 | 15-FEB-06:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 66413.10 | 17-MAR-05:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70841.15 | 03-APR-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71170.20 | 27-MAY-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 71487.60 | 06-JUN-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 69027.86 | 08-JUL-04:03 | 0.00 | 2362.72 | 17812.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 71252.39 | 11-AUG-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 71607.36 | 06-SEP-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 71350.80 | 03-OCT-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 68235.06 | 02-NOV-05:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 52968.10 | 01-DEC-06:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 32835.33 | 0.00 | 2362.72 | 17812.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 71607.36 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 20067.73 | 26-JAN-14:30 | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28549.28 | 15-FEB-17:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 30862.57 | 08-MAR-17:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 67824.44 | 27-APR-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71538.32 | 22-MAY-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 70135.66 | 01-JUN-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 73178.46 | 17-JUL-03:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 71618.94 | 23-AUG-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 71260.14 | 05-SEP-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 69966.59 | 03-OCT-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32200.75 | 01-NOV-15:30 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19982.30 | 29-DEC-13:50 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 19982.30 | 0.00 | 2953.40 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73178.46 | 16014.58 | 10631.20 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2719.64 | 02-JAN-15:00 | 2010.79 | 881.80 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.46 |
February | 3750.60 | 15-FEB-15:00 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.37 |
March | 5760.11 | 27-MAR-14:30 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.91 |
April | 7355.41 | 14-APR-14:00 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 |
May | 11005.24 | 22-MAY-05:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 |
June | 13458.65 | 25-JUN-17:31 | 0.00 | 247.02 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 54.02 | 0.00 |
July | 15111.79 | 02-JUL-17:31 | 0.00 | 317.59 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 38.39 | 0.00 |
August | 12691.04 | 06-AUG-17:11 | 0.00 | 282.30 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 31.12 | 0.00 |
September | 11564.76 | 05-SEP-05:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 |
October | 11726.67 | 02-OCT-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 |
November | 4238.76 | 09-NOV-14:10 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.21 |
December | 3069.03 | 01-DEC-14:10 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2719.64 | 0.00 | 247.02 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15111.79 | 2010.79 | 881.80 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 54.02 | 27.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5898.44 | 02-JAN-09:25 | 2478.65 | 818.60 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.30 |
February | 7858.14 | 14-FEB-09:05 | 2478.65 | 818.60 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.52 |
March | 14575.87 | 26-MAR-10:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.24 |
April | 18986.40 | 30-APR-07:42 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.62 |
May | 18989.56 | 14-MAY-07:32 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.43 |
June | 18763.84 | 11-JUN-07:12 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.55 |
July | 19574.39 | 02-JUL-08:51 | 456.59 | 159.19 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.18 |
August | 18472.03 | 20-AUG-08:42 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.51 |
September | 19702.07 | 03-SEP-08:21 | 456.59 | 159.19 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.89 |
October | 18691.48 | 01-OCT-08:52 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.20 |
November | 8144.12 | 01-NOV-08:50 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 |
December | 5195.85 | 29-DEC-09:15 | 2478.65 | 818.60 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5195.85 | 260.91 | 90.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.96 | |
Maximum of Months | 19702.07 | 2478.65 | 818.60 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19019.32 | 01-JAN-13:42 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.67 |
February | 18959.56 | 12-FEB-13:52 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.04 |
March | 19031.34 | 12-MAR-12:32 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.98 |
April | 18649.04 | 30-APR-13:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.20 |
May | 13227.95 | 14-MAY-14:12 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 | 0.00 |
June | 13958.08 | 26-JUN-05:02 | 1012.19 | 554.01 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 |
July | 18924.90 | 30-JUL-12:32 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 14.38 | 0.00 |
August | 19066.64 | 06-AUG-12:32 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 12.02 | 0.00 |
September | 20638.37 | 03-SEP-12:21 | 708.53 | 247.02 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 0.00 |
October | 21108.33 | 09-OCT-12:41 | 708.53 | 247.02 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.27 |
November | 20309.76 | 23-NOV-12:02 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.54 |
December | 19326.24 | 31-DEC-13:32 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13227.95 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21108.33 | 1012.19 | 554.01 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 14.38 | 66.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8105.56 | 26-JAN-16:30 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.85 |
February | 15419.34 | 12-FEB-15:53 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.08 |
March | 22791.75 | 12-MAR-15:52 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.29 |
April | 24315.45 | 16-APR-16:21 | 456.59 | 159.19 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.99 |
May | 25307.63 | 14-MAY-16:11 | 521.82 | 181.93 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.69 |
June | 26797.93 | 11-JUN-17:11 | 0.00 | 204.67 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 |
July | 26401.13 | 02-JUL-17:31 | 0.00 | 204.67 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 11.85 | 0.00 |
August | 24857.87 | 20-AUG-16:01 | 456.59 | 159.19 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 21.65 | 0.00 |
September | 23829.37 | 17-SEP-15:12 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.68 |
October | 24354.39 | 01-OCT-14:51 | 456.59 | 159.19 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 | 0.00 |
November | 22358.65 | 12-NOV-15:02 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.36 |
December | 15342.68 | 24-DEC-16:03 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8105.56 | 0.00 | 90.96 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26797.93 | 1239.33 | 409.30 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 21.65 | 111.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2286.36 | 05-JAN-15:40 | 1923.11 | 691.57 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.46 |
February | 2594.80 | 15-FEB-16:00 | 1923.11 | 688.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 |
March | 3289.05 | 27-MAR-14:50 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.08 |
April | 6122.81 | 14-APR-14:30 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 |
May | 6936.80 | 31-MAY-15:30 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 27.26 | 0.00 |
June | 13958.90 | 18-JUN-18:21 | 0.00 | 317.59 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 69.33 | 0.00 |
July | 14393.75 | 04-JUL-18:12 | 0.00 | 352.88 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 138.17 | 0.00 |
August | 10672.59 | 21-AUG-05:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.95 |
September | 9345.46 | 15-SEP-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.66 |
October | 6273.64 | 02-OCT-13:40 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 | 0.00 |
November | 2639.61 | 01-NOV-15:10 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.54 |
December | 2136.06 | 29-DEC-15:40 | 1923.11 | 887.17 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2136.06 | 0.00 | 317.59 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14393.75 | 2010.79 | 887.17 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 138.17 | 124.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3060.89 | 27-JAN-09:50 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6192.25 | 14-FEB-09:40 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.81 |
March | 14733.90 | 26-MAR-09:53 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.30 |
April | 20495.33 | 30-APR-08:11 | 456.59 | 159.19 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.39 |
May | 20892.27 | 29-MAY-08:51 | 456.59 | 159.19 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.62 |
June | 21504.21 | 18-JUN-09:01 | 521.82 | 181.93 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.88 |
July | 22171.54 | 04-JUL-08:51 | 587.05 | 204.67 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.01 |
August | 19868.04 | 20-AUG-08:42 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 |
September | 20843.26 | 03-SEP-09:01 | 456.59 | 159.19 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 |
October | 19213.91 | 01-OCT-08:22 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.04 |
November | 7186.20 | 01-NOV-09:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 |
December | 2792.13 | 31-DEC-10:53 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2792.13 | 260.91 | 90.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22171.54 | 1239.33 | 409.30 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18415.75 | 01-JAN-13:42 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.50 |
February | 18353.30 | 19-FEB-13:42 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.19 |
March | 18754.49 | 12-MAR-13:42 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.10 |
April | 17632.86 | 30-APR-12:53 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.14 |
May | 11946.75 | 14-MAY-13:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.28 |
June | 16953.10 | 25-JUN-16:31 | 1012.19 | 352.89 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 142.75 | 0.00 |
July | 17842.37 | 30-JUL-11:22 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 30.47 | 0.00 |
August | 18207.56 | 13-AUG-12:52 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 10.23 | 0.00 |
September | 19937.63 | 03-SEP-12:21 | 708.53 | 247.02 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 18.35 | 0.00 |
October | 21009.57 | 01-OCT-12:21 | 809.75 | 282.31 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 |
November | 18872.81 | 05-NOV-14:42 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.67 |
December | 18688.48 | 31-DEC-13:32 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11946.75 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21009.57 | 1012.19 | 352.89 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 142.75 | 444.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5985.73 | 26-JAN-16:30 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.64 |
February | 9756.71 | 15-FEB-16:30 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.15 |
March | 19540.50 | 12-MAR-16:21 | 521.82 | 181.93 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.89 |
April | 21997.81 | 16-APR-16:31 | 456.59 | 159.19 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.39 |
May | 21237.34 | 14-MAY-16:21 | 587.05 | 204.67 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 | 0.00 |
June | 23754.38 | 25-JUN-16:31 | 652.28 | 227.41 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 52.10 | 0.00 |
July | 24346.58 | 04-JUL-16:51 | 652.28 | 227.41 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 108.78 | 0.00 |
August | 22543.37 | 13-AUG-17:31 | 0.00 | 204.67 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 3.31 | 0.00 |
September | 21849.66 | 24-SEP-16:11 | 456.59 | 159.19 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.90 |
October | 20314.07 | 01-OCT-14:21 | 521.82 | 181.93 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 2.82 | 0.00 |
November | 8561.60 | 02-NOV-16:00 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.14 |
December | 4958.10 | 29-DEC-16:00 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4958.10 | 0.00 | 159.19 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24346.58 | 1239.33 | 409.30 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 108.78 | 63.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1950.73 | 05-JAN-14:30 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.80 |
February | 2564.02 | 15-FEB-15:30 | 1923.11 | 665.52 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 |
March | 2437.04 | 08-MAR-14:00 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 |
April | 6510.26 | 28-APR-15:30 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 | 0.00 |
May | 7656.48 | 31-MAY-15:10 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 27.10 | 0.00 |
June | 16825.95 | 25-JUN-17:21 | 0.00 | 352.88 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 138.28 | 0.00 |
July | 16228.25 | 04-JUL-18:21 | 0.00 | 247.02 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 149.50 | 0.00 |
August | 16030.75 | 13-AUG-17:31 | 0.00 | 317.59 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 24.68 | 0.00 |
September | 9809.10 | 05-SEP-05:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.18 |
October | 6697.20 | 02-OCT-13:40 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5.48 | 0.00 |
November | 2622.24 | 01-NOV-15:20 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.75 |
December | 1771.74 | 29-DEC-15:00 | 2010.79 | 780.77 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1771.74 | 0.00 | 247.02 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16825.95 | 2010.79 | 780.77 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 149.50 | 155.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2306.27 | 03-JAN-13:40 | 1239.33 | 437.56 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.13 |
February | 4103.45 | 14-FEB-10:10 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.99 |
March | 6216.37 | 24-MAR-09:40 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.62 |
April | 18563.88 | 30-APR-09:12 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.94 |
May | 20967.31 | 29-MAY-08:51 | 456.59 | 159.19 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.08 |
June | 21241.33 | 25-JUN-08:61 | 456.59 | 159.19 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.66 |
July | 20396.73 | 09-JUL-07:32 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.04 |
August | 20239.70 | 20-AUG-09:22 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 |
September | 19327.39 | 03-SEP-09:12 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.39 |
October | 12533.01 | 01-OCT-10:32 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.96 |
November | 5957.18 | 01-NOV-09:30 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.48 |
December | 2326.75 | 29-DEC-13:30 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2306.27 | 326.14 | 113.70 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.39 | |
Maximum of Months | 21241.33 | 1295.83 | 437.56 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15604.49 | 26-JAN-14:10 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.69 |
February | 19615.05 | 19-FEB-13:42 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.81 |
March | 20189.73 | 12-MAR-14:22 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.95 |
April | 13429.60 | 28-APR-13:20 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 | 0.00 |
May | 19343.26 | 21-MAY-13:22 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 | 0.00 |
June | 20035.70 | 25-JUN-16:01 | 1012.19 | 352.89 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 107.50 | 0.00 |
July | 19681.37 | 30-JUL-14:52 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 90.27 | 0.00 |
August | 20681.81 | 13-AUG-12:52 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 | 0.00 |
September | 21127.87 | 03-SEP-13:12 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 53.78 | 0.00 |
October | 21703.13 | 01-OCT-13:12 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.96 |
November | 20705.00 | 19-NOV-12:52 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.56 |
December | 19573.49 | 31-DEC-13:53 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13429.60 | 404.87 | 141.16 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21703.13 | 2010.83 | 635.14 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 107.50 | 288.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5111.87 | 26-JAN-16:30 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.08 |
February | 9462.24 | 15-FEB-16:30 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.09 |
March | 16945.30 | 12-MAR-16:21 | 521.82 | 181.93 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.35 |
April | 19624.90 | 16-APR-16:42 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.51 |
May | 22372.87 | 29-MAY-16:11 | 521.82 | 181.93 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 |
June | 26440.78 | 25-JUN-16:41 | 652.28 | 227.41 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 0.00 |
July | 24114.46 | 04-JUL-17:01 | 0.00 | 181.93 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 154.09 | 0.00 |
August | 24590.33 | 13-AUG-17:31 | 0.00 | 204.67 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 | 0.00 |
September | 21764.53 | 24-SEP-16:22 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 |
October | 20249.59 | 01-OCT-15:12 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 9.16 | 0.00 |
November | 8014.94 | 02-NOV-16:00 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.37 |
December | 4126.86 | 29-DEC-16:00 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4126.86 | 0.00 | 113.70 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26440.78 | 1239.33 | 409.30 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 154.09 | 79.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4470.19 | 02-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.66 |
February | 3848.95 | 15-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.00 |
March | 4609.66 | 27-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 |
April | 5992.80 | 03-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.51 |
May | 9042.10 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.29 |
June | 9610.85 | 19-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.12 |
July | 12949.10 | 05-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.66 |
August | 11496.02 | 14-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 |
September | 11855.72 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 |
October | 9622.60 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 |
November | 4451.51 | 01-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.53 |
December | 3296.45 | 01-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3296.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 | |
Maximum of Months | 12949.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5061.46 | 07-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 |
February | 5792.84 | 06-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1031.67 |
March | 3462.00 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.63 |
April | 4348.98 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 | 0.00 |
May | 4915.67 | 22-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.90 |
June | 6533.22 | 29-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.80 | 0.00 |
July | 7414.71 | 17-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.91 |
August | 7063.57 | 01-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 |
September | 6873.42 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.68 |
October | 5479.02 | 03-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.73 |
November | 4596.83 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.69 |
December | 4736.73 | 22-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3462.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7414.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.80 | 1031.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2445.03 | 01-JAN-14:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.49 |
February | 5445.95 | 15-FEB-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.51 |
March | 8089.37 | 08-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 |
April | 14519.40 | 28-APR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.82 |
May | 17188.04 | 30-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 | 0.00 |
June | 22131.90 | 28-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 | 0.00 |
July | 21191.77 | 21-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.13 | 0.00 |
August | 19721.30 | 07-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.66 | 0.00 |
September | 15310.84 | 01-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.58 | 0.00 |
October | 11768.63 | 05-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 | 0.00 |
November | 4850.12 | 01-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.02 |
December | 2760.66 | 31-DEC-14:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2445.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22131.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.13 | 256.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2219.59 | 26-JAN-17:00 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4245.45 | 15-FEB-17:00 | 222.14 | 284.97 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7109.00 | 31-MAR-24:00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8249.41 | 16-APR-18:20 | 0.00 | 94.99 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3498.44 | 31-MAY-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5340.36 | 30-JUN-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7235.22 | 31-JUL-23:45 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7918.70 | 30-AUG-17:40 | 23.38 | 94.99 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3499.55 | 30-SEP-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5294.71 | 31-OCT-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6127.23 | 05-NOV-16:33 | 35.07 | 47.50 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7931.78 | 31-DEC-16:35 | 23.38 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2219.59 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8249.41 | 222.14 | 284.97 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1980.92 | 26-JAN-17:00 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3974.96 | 15-FEB-17:00 | 222.14 | 284.97 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6545.31 | 31-MAR-23:40 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7771.31 | 16-APR-17:42 | 0.00 | 94.99 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3308.29 | 31-MAY-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5162.22 | 30-JUN-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6983.22 | 31-JUL-23:53 | 0.00 | 63.33 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7563.57 | 30-AUG-17:40 | 23.38 | 94.99 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3300.54 | 30-SEP-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4809.10 | 31-OCT-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5689.75 | 02-NOV-16:40 | 70.15 | 158.31 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7290.76 | 29-DEC-16:50 | 222.14 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1980.92 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7771.31 | 222.14 | 284.97 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1825.53 | 26-JAN-17:00 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3971.19 | 15-FEB-17:00 | 222.14 | 284.97 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6175.24 | 31-MAR-23:20 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7764.10 | 16-APR-17:42 | 0.00 | 94.99 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3262.81 | 31-MAY-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5175.89 | 30-JUN-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6973.42 | 31-JUL-23:53 | 0.00 | 63.33 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7723.61 | 13-AUG-19:23 | 0.00 | 63.33 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3278.72 | 30-SEP-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4553.32 | 31-OCT-23:40 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5660.62 | 02-NOV-16:40 | 70.15 | 158.31 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7147.55 | 29-DEC-16:50 | 222.14 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1825.53 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7764.10 | 222.14 | 284.97 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91564.98 | 02-JAN-17:00 | 4808.68 | 3337.76 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182867.59 | 15-FEB-17:00 | 4808.68 | 3337.76 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358508.74 | 31-MAR-24:00 | 0.00 | 185.45 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366453.85 | 26-APR-16:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175775.06 | 31-MAY-24:00 | 0.00 | 185.45 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267520.94 | 30-JUN-24:00 | 0.00 | 185.45 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359978.96 | 31-JUL-23:55 | 0.00 | 741.80 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 368004.50 | 21-AUG-16:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176457.17 | 30-SEP-24:00 | 0.00 | 185.45 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268399.23 | 31-OCT-24:00 | 0.00 | 185.45 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275800.37 | 24-NOV-17:00 | 4808.68 | 3337.76 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367096.89 | 26-DEC-17:00 | 9617.36 | 6675.52 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91564.98 | 0.00 | 185.45 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 368004.50 | 9617.36 | 6675.52 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.127994E+13 | 829262.65 | 05-JAN-16:10 | 0.292478E+12 | 709192.31 | 21-JAN-07:10 |
February | 0.150741E+13 | 1047087.78 | 14-FEB-16:40 | 0.193108E+12 | 683245.88 | 06-FEB-07:30 |
March | 0.210381E+13 | 1224917.38 | 08-MAR-16:19 | 0.100162E+12 | 363790.23 | 04-MAR-06:10 |
April | 0.244523E+13 | 1505520.84 | 28-APR-15:09 | 0.632825E+11 | 224632.36 | 08-APR-06:10 |
May | 0.146631E+13 | 1103822.97 | 19-MAY-15:09 | 0.593396E+11 | 87999.92 | 06-MAY-06:10 |
June | 0.194699E+13 | 1322808.02 | 26-JUN-15:30 | 0.549551E+11 | 74336.22 | 02-JUN-11:39 |
July | 0.242708E+13 | 1514677.49 | 31-JUL-15:09 | 0.516921E+11 | 71452.77 | 05-JUL-11:39 |
August | 0.283459E+13 | 1632266.59 | 02-AUG-15:30 | 0.546237E+11 | 70698.63 | 29-AUG-11:39 |
September | 0.147810E+13 | 1132057.43 | 05-SEP-15:09 | 0.517314E+11 | 72297.65 | 22-SEP-11:50 |
October | 0.177822E+13 | 1201376.65 | 02-OCT-15:00 | 0.767736E+11 | 425787.74 | 26-OCT-06:10 |
November | 0.199501E+13 | 1158434.14 | 02-NOV-15:00 | 0.113261E+12 | 523499.74 | 27-NOV-07:10 |
December | 0.240276E+13 | 1277946.71 | 19-DEC-16:00 | 0.290334E+12 | 669972.19 | 15-DEC-07:10 |
Annual Sum or Average | 0.236654E+14 | 0.140174E+13 | ||||
Minimum of Months | 0.127994E+13 | 829262.65 | 0.516921E+11 | 70698.63 | ||
Maximum of Months | 0.283459E+13 | 1632266.59 | 0.292478E+12 | 709192.31 |
Report: EnergyConsumptionDistrictHeatingCoolingMonthly
For: Meter
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportDISTRICTCOOLING:FACILITY [J] | DISTRICTCOOLING:FACILITY {Maximum} [W] | DISTRICTCOOLING:FACILITY {TIMESTAMP} | DISTRICTHEATING:FACILITY [J] | DISTRICTHEATING:FACILITY {Maximum} [W] | DISTRICTHEATING:FACILITY {TIMESTAMP} | |
January | 0.239431E+12 | 94164.18 | 02-JAN-16:00 | 161413.36 | 6.69 | 21-JAN-19:40 |
February | 0.436908E+12 | 185466.68 | 15-FEB-16:00 | 203569.01 | 11.73 | 01-FEB-00:40 |
March | 0.730473E+12 | 358509.33 | 31-MAR-23:00 | 203561.83 | 12.11 | 01-MAR-00:30 |
April | 0.944425E+12 | 369052.90 | 26-APR-15:00 | 79260.19 | 8.42 | 07-APR-23:30 |
May | 0.242328E+12 | 175778.23 | 31-MAY-23:00 | 138180.89 | 11.64 | 31-MAY-23:40 |
June | 0.471839E+12 | 267521.63 | 30-JUN-23:00 | 57374.55 | 8.40 | 19-JUN-23:30 |
July | 0.733833E+12 | 359979.00 | 31-JUL-23:00 | 20407.37 | 8.21 | 07-JUL-23:30 |
August | 0.979884E+12 | 370603.48 | 21-AUG-15:00 | 25103.61 | 5.68 | 27-AUG-17:19 |
September | 0.237707E+12 | 176457.17 | 30-SEP-23:00 | 125862.93 | 6.88 | 16-SEP-18:40 |
October | 0.489438E+12 | 268400.54 | 31-OCT-23:00 | 158043.46 | 12.08 | 31-OCT-23:30 |
November | 0.709921E+12 | 278399.26 | 24-NOV-16:00 | 193401.64 | 8.24 | 10-NOV-00:30 |
December | 0.977712E+12 | 369695.76 | 26-DEC-16:00 | 196712.15 | 11.12 | 01-DEC-00:30 |
Annual Sum or Average | 0.719390E+13 | 1562891.01 | ||||
Minimum of Months | 0.237707E+12 | 94164.18 | 20407.37 | 5.68 | ||
Maximum of Months | 0.979884E+12 | 370603.48 | 203569.01 | 12.11 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.170745E+12 | 0.355334E+11 | 0.766053E+12 | 0.207861E+12 | 0.777056E+11 | 0.987106E+10 | 0.00 | 0.107663E+11 | 0.140359E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153960E+12 | 0.290613E+11 | 0.978954E+12 | 0.229081E+12 | 0.731733E+11 | 0.126531E+11 | 0.00 | 0.263016E+11 | 0.423006E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181471E+12 | 0.279369E+11 | 0.141687E+13 | 0.299604E+12 | 0.941480E+11 | 0.185309E+11 | 0.00 | 0.534156E+11 | 0.118285E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161083E+12 | 0.231121E+11 | 0.165903E+13 | 0.333797E+12 | 0.114525E+12 | 0.335950E+11 | 0.00 | 0.979164E+11 | 0.221719E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173563E+12 | 0.206906E+11 | 0.774844E+12 | 0.208007E+12 | 0.129968E+12 | 0.442566E+11 | 0.00 | 0.936346E+11 | 0.213438E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172352E+12 | 0.187757E+11 | 0.106252E+13 | 0.245640E+12 | 0.160351E+12 | 0.689526E+11 | 0.00 | 0.183843E+12 | 0.345542E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161600E+12 | 0.199952E+11 | 0.139340E+13 | 0.299361E+12 | 0.173912E+12 | 0.826626E+11 | 0.00 | 0.241601E+12 | 0.545418E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180019E+12 | 0.225564E+11 | 0.173200E+13 | 0.345114E+12 | 0.175598E+12 | 0.838691E+11 | 0.00 | 0.245310E+12 | 0.501199E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161726E+12 | 0.251956E+11 | 0.740713E+12 | 0.201201E+12 | 0.128207E+12 | 0.579889E+11 | 0.00 | 0.133065E+12 | 0.300022E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169116E+12 | 0.303882E+11 | 0.108340E+13 | 0.253679E+12 | 0.105954E+12 | 0.357951E+11 | 0.00 | 0.816380E+11 | 0.182454E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168775E+12 | 0.333309E+11 | 0.135889E+13 | 0.289765E+12 | 0.842119E+11 | 0.116130E+11 | 0.00 | 0.405773E+11 | 0.784440E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166550E+12 | 0.366166E+11 | 0.170972E+13 | 0.345057E+12 | 0.792846E+11 | 0.115240E+11 | 0.00 | 0.482690E+11 | 0.573877E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202096E+13 | 0.323193E+12 | 0.146764E+14 | 0.325817E+13 | 0.139704E+13 | 0.471312E+12 | 0.00 | 0.125634E+13 | 0.262025E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153960E+12 | 0.187757E+11 | 0.740713E+12 | 0.201201E+12 | 0.731733E+11 | 0.987106E+10 | 0.00 | 0.107663E+11 | 0.140359E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181471E+12 | 0.366166E+11 | 0.173200E+13 | 0.345114E+12 | 0.175598E+12 | 0.838691E+11 | 0.00 | 0.245310E+12 | 0.545418E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.228703E+12 | 0.00 | 0.637748E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.134901E+12 | 0.00 | 0.582074E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.339971E+11 | 0.00 | 0.661649E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.466714E+10 | 0.00 | 0.586153E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.463068E+09 | 0.00 | 0.588765E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1941873.82 | 0.00 | 0.549531E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.516921E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.546237E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.517314E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.208692E+11 | 0.00 | 0.559044E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.556090E+11 | 0.00 | 0.576519E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.229554E+12 | 0.00 | 0.607793E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.708766E+12 | 0.00 | 0.692975E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.516921E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.229554E+12 | 0.00 | 0.661649E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 192435.19 | 04-JAN-16:00 | 37611.08 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 133938.60 | 03-JAN-08:20 | 73620.65 | 26-JAN-16:49 | 30873.67 | 17-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 189247.46 | 16-FEB-08:09 | 37611.08 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 151027.22 | 16-FEB-08:20 | 105323.07 | 15-FEB-16:00 | 45468.54 | 14-FEB-16:40 | 0.00 | 01-FEB-00:10 |
March | 184120.58 | 20-MAR-07:10 | 37611.08 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 168107.99 | 20-MAR-07:19 | 111998.84 | 15-MAR-15:00 | 45430.23 | 08-MAR-13:39 | 0.00 | 01-MAR-00:10 |
April | 171551.51 | 05-APR-07:10 | 37611.08 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 185184.84 | 05-APR-07:19 | 170896.73 | 13-APR-15:20 | 46328.61 | 28-APR-13:39 | 0.00 | 01-APR-00:10 |
May | 175129.67 | 22-MAY-07:10 | 37611.08 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 133936.32 | 22-MAY-07:19 | 178731.80 | 30-MAY-14:30 | 51027.25 | 23-MAY-12:30 | 0.00 | 01-MAY-00:10 |
June | 177912.80 | 08-JUN-15:00 | 24287.76 | 01-JUN-19:10 | 541788.89 | 01-JUN-07:10 | 151020.09 | 08-JUN-07:19 | 214828.06 | 28-JUN-14:39 | 58943.51 | 27-JUN-15:20 | 0.00 | 01-JUN-00:10 |
July | 175395.87 | 07-JUL-15:00 | 37611.08 | 19-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 168101.60 | 28-JUL-07:19 | 214182.38 | 06-JUL-15:09 | 61255.83 | 21-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 171918.60 | 17-AUG-07:10 | 37611.08 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 185185.04 | 17-AUG-07:19 | 217050.77 | 07-AUG-15:39 | 53447.85 | 02-AUG-07:00 | 0.00 | 01-AUG-00:10 |
September | 188667.91 | 08-SEP-07:10 | 37611.08 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 133943.45 | 08-SEP-07:19 | 171955.21 | 06-SEP-15:50 | 58762.59 | 21-SEP-14:00 | 0.00 | 01-SEP-00:10 |
October | 188210.97 | 25-OCT-07:10 | 37611.08 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 151026.67 | 25-OCT-07:19 | 149157.55 | 02-OCT-08:50 | 56132.74 | 02-OCT-10:00 | 0.00 | 01-OCT-00:10 |
November | 198852.03 | 13-NOV-16:00 | 37611.08 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 168112.40 | 02-NOV-07:19 | 108260.89 | 03-NOV-15:00 | 30100.22 | 27-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 198852.03 | 01-DEC-16:00 | 37611.08 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 185192.48 | 08-DEC-08:20 | 73761.64 | 29-DEC-16:30 | 30231.21 | 22-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 171551.51 | 24287.76 | 423497.50 | 133936.32 | 73620.65 | 30100.22 | 0.00 | |||||||
Maximum of Months | 198852.03 | 37611.08 | 778371.69 | 185192.48 | 217050.77 | 61255.83 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 41254.81 | 05-JAN-15:39 | 5952.96 | 05-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83021.07 | 14-FEB-16:49 | 12817.81 | 14-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 92446.88 | 08-MAR-16:19 | 13161.28 | 08-MAR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 189204.82 | 28-APR-13:00 | 13605.89 | 28-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 178568.80 | 23-MAY-12:30 | 16857.07 | 22-MAY-15:50 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 224182.17 | 28-JUN-14:50 | 42924.61 | 06-JUN-13:20 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 250464.06 | 31-JUL-14:00 | 42924.61 | 03-JUL-08:50 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 233985.11 | 21-AUG-13:00 | 42924.61 | 01-AUG-09:39 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 249062.52 | 05-SEP-13:09 | 42924.61 | 01-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 199575.65 | 02-OCT-10:00 | 42924.61 | 11-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 65373.21 | 02-NOV-14:00 | 12686.59 | 02-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23041.61 | 24-DEC-15:30 | 8108.54 | 01-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 23041.61 | 5952.96 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 250464.06 | 42924.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 829262.65 | 05-JAN-16:10 | 176113.97 | 423497.50 | 0.00 | 99892.85 | 68828.57 | 28877.14 | 0.00 | 27162.87 | 4889.76 |
February | 1047087.78 | 14-FEB-16:40 | 172091.91 | 541788.89 | 0.00 | 116974.36 | 75166.89 | 45468.54 | 0.00 | 82973.24 | 12623.94 |
March | 1224917.38 | 08-MAR-16:19 | 171235.93 | 660080.29 | 0.00 | 134057.82 | 109206.34 | 45088.84 | 0.00 | 92446.88 | 12801.29 |
April | 1505520.84 | 28-APR-15:09 | 171235.93 | 778371.69 | 0.00 | 151141.29 | 168115.79 | 45591.68 | 0.00 | 178023.42 | 13041.06 |
May | 1103822.97 | 19-MAY-15:09 | 171235.93 | 423497.50 | 0.00 | 99890.88 | 177064.94 | 45827.13 | 0.00 | 171832.23 | 14474.37 |
June | 1322808.02 | 26-JUN-15:30 | 171235.93 | 541788.89 | 0.00 | 116974.35 | 210061.18 | 52724.07 | 0.00 | 214775.05 | 15248.55 |
July | 1514677.49 | 31-JUL-15:09 | 171235.93 | 660080.29 | 0.00 | 134057.82 | 210925.51 | 47944.83 | 0.00 | 247508.52 | 42924.61 |
August | 1632266.59 | 02-AUG-15:30 | 171235.93 | 778371.69 | 0.00 | 151141.29 | 213932.73 | 48821.04 | 0.00 | 225839.31 | 42924.61 |
September | 1132057.43 | 05-SEP-15:09 | 171235.93 | 423497.50 | 0.00 | 99890.88 | 171567.09 | 46717.98 | 0.00 | 176223.45 | 42924.61 |
October | 1201376.65 | 02-OCT-15:00 | 171498.75 | 541788.89 | 0.00 | 116974.35 | 131652.62 | 51184.99 | 0.00 | 174101.79 | 14175.26 |
November | 1158434.14 | 02-NOV-15:00 | 175409.23 | 660080.29 | 0.00 | 134059.54 | 89668.59 | 29068.50 | 0.00 | 57496.90 | 12651.09 |
December | 1277946.71 | 19-DEC-16:00 | 198852.03 | 778371.69 | 37611.08 | 151155.16 | 57449.13 | 28843.24 | 0.00 | 22120.46 | 3543.94 |
Annual Sum or Average | |||||||||||
Minimum of Months | 829262.65 | 171235.93 | 423497.50 | 0.00 | 99890.88 | 57449.13 | 28843.24 | 0.00 | 22120.46 | 3543.94 | |
Maximum of Months | 1632266.59 | 198852.03 | 778371.69 | 37611.08 | 151155.16 | 213932.73 | 52724.07 | 0.00 | 247508.52 | 42924.61 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 681631.09 | 21-JAN-07:10 | 0.00 | 81596.13 | 31-JAN-12:39 | 0.00 |
February | 0.00 | 0.00 | 663664.77 | 06-FEB-07:10 | 0.00 | 81624.73 | 03-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 353259.75 | 04-MAR-07:10 | 0.00 | 81313.91 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 197024.15 | 08-APR-06:10 | 0.00 | 79728.05 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 60790.90 | 06-MAY-06:10 | 0.00 | 77475.05 | 01-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 471.66 | 09-JUN-05:00 | 0.00 | 74336.22 | 02-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 71452.77 | 05-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 70698.63 | 29-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 72297.65 | 22-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 403299.67 | 26-OCT-06:19 | 0.00 | 76004.99 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 494749.74 | 27-NOV-07:10 | 0.00 | 78752.11 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 640775.20 | 15-DEC-07:10 | 0.00 | 80622.86 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 70698.63 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 681631.09 | 0.00 | 81624.73 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.74 | 0.67 | 26.82 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 26.47 | 0.00 | 26.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.00 | 0.00 | 26.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 25.96 | 0.00 | 25.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 26.16 | 0.50 | 26.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.11 | 0.00 | 26.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.32 | 0.17 | 26.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.16 | 0.33 | 26.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 26.39 | 0.67 | 26.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 26.44 | 0.50 | 26.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.45 | 0.67 | 26.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.47 | 0.67 | 26.55 |
Annual Sum or Average | 0.00 | 0.00 | 81.67 | 26.35 | 4.17 | 26.39 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.96 | 0.00 | 25.96 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.74 | 0.67 | 26.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 25.61 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.03 | 0.00 | 26.03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.62 | 0.00 | 25.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.58 | 0.00 | 25.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.61 | 0.00 | 25.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.59 | 0.00 | 25.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.79 | 0.00 | 25.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 25.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 25.70 | 0.00 | 25.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.03 | 0.00 | 26.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
February | 0.17 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
Annual Sum or Average | 2.17 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.34 | 0.00 | 27.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.89 | 0.83 | 27.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 26.92 | 0.83 | 27.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.00 | 26.95 | 1.67 | 27.07 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.34 | 0.83 | 27.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.73 | 1.67 | 27.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.92 | 3.67 | 27.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.06 | 6.67 | 28.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.03 | 6.17 | 28.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 28.00 | 13.67 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.00 | 7.67 | 28.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.87 | 4.33 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.81 | 3.17 | 27.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 47.17 | 27.97 | 47.00 | 27.97 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 28.06 | 13.67 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.84 | 6.33 | 27.84 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.84 | 5.33 | 26.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.74 | 3.67 | 27.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.55 | 2.17 | 27.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.32 | 0.67 | 27.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.37 | 0.67 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.36 | 7.00 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.47 | 6.67 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 26.70 | 13.50 | 26.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 25.88 | 26.33 | 25.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.70 | 12.17 | 26.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.95 | 5.67 | 27.95 |
Annual Sum or Average | 0.00 | 0.00 | 94.50 | 26.83 | 90.17 | 26.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.88 | 0.67 | 25.87 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 27.95 | 26.33 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.76 | 1.17 | 27.76 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.33 | 3.00 | 28.35 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.33 | 6.00 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.91 | 4.00 | 28.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.41 | 5.50 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 33.33 | 27.45 | 9.67 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 27.43 | 8.67 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.88 | 4.83 | 28.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.92 | 3.83 | 28.15 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.83 | 3.50 | 27.83 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.81 | 2.17 | 27.81 |
Annual Sum or Average | 0.00 | 0.00 | 135.33 | 27.53 | 52.67 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 28.33 | 9.67 | 28.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
February | 0.50 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.37 | 0.67 | 27.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
December | 1.17 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Annual Sum or Average | 3.17 | 19.30 | 0.00 | 19.30 | 1.17 | 21.47 | 0.67 | 22.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 19.43 | 0.00 | 19.43 | 1.17 | 27.37 | 0.67 | 27.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
February | 0.33 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.60 | 1.00 | 27.60 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.90 | 3.33 | 27.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.06 | 7.67 | 28.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.09 | 7.83 | 28.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 28.19 | 16.00 | 28.20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 28.12 | 9.83 | 28.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.04 | 4.00 | 28.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.81 | 2.33 | 27.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Annual Sum or Average | 2.00 | 19.28 | 0.00 | 19.28 | 52.83 | 27.76 | 52.00 | 27.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.37 | 0.00 | 19.37 | 16.33 | 28.19 | 16.00 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.40 | 0.00 | 19.40 | 22.17 | 25.68 | 22.17 | 25.72 |
February | 0.17 | 19.39 | 0.00 | 19.39 | 16.50 | 25.54 | 16.50 | 25.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.83 | 3.50 | 27.83 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.58 | 1.33 | 27.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.32 | 0.33 | 27.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.54 | 5.67 | 27.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.68 | 6.17 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 26.53 | 17.50 | 26.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 55.50 | 25.62 | 54.83 | 25.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 37.33 | 25.57 | 37.33 | 25.57 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 26.40 | 10.17 | 26.40 |
Annual Sum or Average | 0.50 | 19.40 | 0.00 | 19.40 | 177.83 | 25.95 | 175.67 | 25.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.54 | 0.17 | 25.57 |
Maximum of Months | 0.33 | 19.40 | 0.00 | 19.40 | 55.50 | 27.83 | 54.83 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
February | 0.17 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.81 | 1.33 | 27.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.09 | 2.67 | 28.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.21 | 2.67 | 28.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.52 | 3.17 | 28.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 28.16 | 5.17 | 28.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.05 | 3.50 | 28.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.09 | 3.67 | 28.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.11 | 2.33 | 28.15 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.31 | 0.00 | 19.31 | 43.00 | 28.11 | 24.50 | 28.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.37 | 0.00 | 19.37 | 10.17 | 28.52 | 5.17 | 28.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.67 | 18.15 | 4.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
February | 9.67 | 18.03 | 1.67 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
March | 0.83 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.49 | 1.00 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.54 | 3.83 | 27.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.40 | 2.33 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
November | 4.17 | 18.83 | 0.50 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
December | 12.33 | 18.44 | 2.33 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
Annual Sum or Average | 44.17 | 18.29 | 8.50 | 18.55 | 10.67 | 20.05 | 7.17 | 20.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.67 | 19.17 | 4.00 | 19.17 | 5.17 | 27.54 | 3.83 | 27.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.33 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 |
February | 6.17 | 17.98 | 0.00 | 17.98 | 0.00 | 17.98 | 0.00 | 17.98 |
March | 0.50 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.10 | 1.67 | 28.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.93 | 10.00 | 27.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.06 | 9.33 | 28.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 28.27 | 16.33 | 28.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 28.23 | 10.33 | 28.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.00 | 4.17 | 28.01 |
October | 0.33 | 19.08 | 0.00 | 19.08 | 1.17 | 25.96 | 1.17 | 26.82 |
November | 2.50 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
December | 8.67 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 |
Annual Sum or Average | 27.50 | 18.02 | 0.00 | 18.02 | 58.67 | 24.91 | 53.00 | 26.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.76 | 0.00 | 17.76 |
Maximum of Months | 9.33 | 19.08 | 0.00 | 19.08 | 18.83 | 28.27 | 16.33 | 28.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.67 | 18.60 | 0.00 | 18.60 | 3.17 | 21.79 | 3.17 | 23.30 |
February | 3.83 | 18.69 | 0.00 | 18.69 | 2.17 | 21.80 | 2.17 | 23.26 |
March | 0.50 | 19.25 | 0.00 | 19.25 | 2.33 | 26.21 | 2.33 | 26.88 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.63 | 1.17 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.41 | 2.17 | 27.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.47 | 2.33 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.65 | 8.50 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.84 | 6.50 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 26.68 | 14.67 | 26.66 |
October | 0.17 | 18.92 | 0.00 | 18.92 | 25.17 | 25.85 | 24.67 | 25.86 |
November | 0.67 | 18.92 | 0.00 | 18.92 | 6.83 | 25.83 | 6.83 | 26.15 |
December | 7.33 | 18.64 | 0.17 | 18.68 | 2.17 | 20.71 | 2.17 | 22.00 |
Annual Sum or Average | 18.17 | 18.67 | 0.17 | 18.68 | 82.67 | 25.36 | 76.67 | 25.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 20.71 | 1.17 | 22.00 |
Maximum of Months | 7.33 | 19.25 | 0.17 | 19.25 | 25.17 | 27.84 | 24.67 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.83 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
February | 3.50 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
March | 0.17 | 19.17 | 0.00 | 19.17 | 0.50 | 25.68 | 0.33 | 26.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.08 | 2.50 | 28.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.19 | 3.17 | 28.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.36 | 4.50 | 28.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.30 | 5.83 | 28.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.22 | 4.17 | 28.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.10 | 4.00 | 28.16 |
October | 0.17 | 19.07 | 0.00 | 19.07 | 2.83 | 27.52 | 2.33 | 27.77 |
November | 1.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
December | 7.17 | 18.62 | 0.00 | 18.62 | 0.00 | 18.62 | 0.00 | 18.62 |
Annual Sum or Average | 18.83 | 18.66 | 0.00 | 18.66 | 48.50 | 25.55 | 26.83 | 26.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.61 | 0.00 | 18.61 |
Maximum of Months | 7.17 | 19.17 | 0.00 | 19.17 | 12.00 | 28.36 | 5.83 | 28.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.90 | 1.50 | 27.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.06 | 2.67 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.17 | 28.01 | 4.17 | 28.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.06 | 2.67 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.78 | 1.17 | 27.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.10 | 1.83 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.17 | 28.00 | 3.00 | 27.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.10 | 1.83 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.61 | 0.50 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.17 | 2.83 | 28.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.83 | 28.11 | 3.33 | 28.08 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.17 | 2.83 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 252.67 | 24.01 | 66.67 | 24.49 | 0.00 | 24.49 |
February | 222.33 | 24.01 | 65.00 | 24.53 | 0.00 | 24.53 |
March | 200.83 | 24.00 | 64.67 | 24.55 | 0.00 | 24.55 |
April | 183.17 | 24.00 | 76.83 | 24.72 | 0.00 | 24.72 |
May | 126.17 | 24.00 | 141.00 | 24.78 | 0.67 | 24.77 |
June | 6.33 | 24.00 | 290.17 | 24.83 | 0.00 | 24.83 |
July | 112.00 | 24.48 | 473.33 | 24.66 | 112.00 | 24.63 |
August | 86.17 | 24.31 | 500.50 | 24.52 | 86.17 | 24.50 |
September | 13.83 | 24.76 | 375.00 | 24.79 | 13.83 | 24.79 |
October | 73.67 | 24.00 | 191.67 | 25.12 | 0.00 | 25.12 |
November | 98.33 | 24.00 | 106.83 | 25.29 | 0.00 | 25.29 |
December | 225.83 | 24.01 | 86.50 | 24.71 | 0.00 | 24.71 |
Annual Sum or Average | 1601.33 | 24.06 | 2438.17 | 24.71 | 212.67 | 24.70 |
Minimum of Months | 6.33 | 24.00 | 64.67 | 24.49 | 0.00 | 24.49 |
Maximum of Months | 252.67 | 24.76 | 500.50 | 25.29 | 112.00 | 25.29 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 347.50 | 23.92 | 8.17 | 23.97 | 0.00 | 23.97 |
February | 226.33 | 23.98 | 16.83 | 24.11 | 0.00 | 24.11 |
March | 158.33 | 24.02 | 33.50 | 24.35 | 0.00 | 24.35 |
April | 143.33 | 24.02 | 24.17 | 24.31 | 0.00 | 24.31 |
May | 117.17 | 24.02 | 117.67 | 24.38 | 1.33 | 24.38 |
June | 3.67 | 24.01 | 280.00 | 24.31 | 0.00 | 24.31 |
July | 159.67 | 24.35 | 474.67 | 24.28 | 159.67 | 24.30 |
August | 78.00 | 24.20 | 508.83 | 24.22 | 78.00 | 24.21 |
September | 20.00 | 24.36 | 367.83 | 24.43 | 20.00 | 24.43 |
October | 88.67 | 24.00 | 156.83 | 24.54 | 0.00 | 24.54 |
November | 137.67 | 24.01 | 50.67 | 24.51 | 0.00 | 24.51 |
December | 255.00 | 24.01 | 38.33 | 24.28 | 0.00 | 24.28 |
Annual Sum or Average | 1735.33 | 24.03 | 2077.50 | 24.29 | 259.00 | 24.29 |
Minimum of Months | 3.67 | 23.92 | 8.17 | 23.97 | 0.00 | 23.97 |
Maximum of Months | 347.50 | 24.36 | 508.83 | 24.54 | 159.67 | 24.54 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 23.22 | 0.00 | 23.22 | 0.00 | 23.22 |
February | 440.17 | 23.50 | 0.00 | 23.50 | 0.00 | 23.50 |
March | 449.50 | 23.79 | 0.00 | 23.79 | 0.00 | 23.79 |
April | 347.50 | 23.92 | 1.33 | 23.93 | 0.00 | 23.93 |
May | 214.67 | 23.93 | 67.33 | 24.05 | 1.50 | 24.05 |
June | 43.00 | 23.90 | 212.50 | 24.22 | 0.00 | 24.22 |
July | 158.83 | 24.14 | 458.50 | 24.19 | 158.83 | 24.18 |
August | 105.50 | 24.14 | 468.83 | 24.19 | 105.50 | 24.18 |
September | 25.67 | 24.24 | 312.00 | 24.32 | 20.50 | 24.32 |
October | 235.33 | 23.80 | 86.33 | 23.97 | 1.83 | 23.97 |
November | 435.83 | 23.72 | 0.00 | 23.72 | 0.00 | 23.72 |
December | 497.00 | 23.26 | 0.00 | 23.26 | 0.00 | 23.26 |
Annual Sum or Average | 3455.00 | 23.64 | 1606.83 | 23.84 | 288.17 | 23.85 |
Minimum of Months | 25.67 | 23.22 | 0.00 | 23.22 | 0.00 | 23.22 |
Maximum of Months | 502.00 | 24.24 | 468.83 | 24.32 | 158.83 | 24.32 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.52 | 173.67 | 21.21 | 173.67 | 21.03 |
February | 454.00 | 22.07 | 84.33 | 21.84 | 84.33 | 21.68 |
March | 507.50 | 23.02 | 13.00 | 22.97 | 13.00 | 22.91 |
April | 390.83 | 23.66 | 0.83 | 23.66 | 0.00 | 23.66 |
May | 217.33 | 23.72 | 65.33 | 23.88 | 1.83 | 23.88 |
June | 39.83 | 23.74 | 246.17 | 24.21 | 0.00 | 24.21 |
July | 153.83 | 24.20 | 470.17 | 24.26 | 153.83 | 24.25 |
August | 101.83 | 24.21 | 489.17 | 24.24 | 101.83 | 24.23 |
September | 52.50 | 23.87 | 290.50 | 24.21 | 23.33 | 24.21 |
October | 328.33 | 23.21 | 73.33 | 23.39 | 4.67 | 23.38 |
November | 471.83 | 22.40 | 58.50 | 22.22 | 58.50 | 22.07 |
December | 497.00 | 21.53 | 174.83 | 21.25 | 174.83 | 21.09 |
Annual Sum or Average | 3716.83 | 22.65 | 2139.83 | 22.92 | 789.83 | 22.78 |
Minimum of Months | 39.83 | 21.52 | 0.83 | 21.21 | 0.00 | 21.03 |
Maximum of Months | 507.50 | 24.21 | 489.17 | 24.26 | 174.83 | 24.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.29 | 14.67 | 22.25 | 14.67 | 22.21 |
February | 451.83 | 22.80 | 8.33 | 22.77 | 8.33 | 22.74 |
March | 480.67 | 23.51 | 0.00 | 23.51 | 0.00 | 23.51 |
April | 317.67 | 23.89 | 6.50 | 23.92 | 0.00 | 23.92 |
May | 166.50 | 23.87 | 102.67 | 24.20 | 1.00 | 24.20 |
June | 3.83 | 24.31 | 352.00 | 24.45 | 0.50 | 24.45 |
July | 108.00 | 25.08 | 492.17 | 24.58 | 108.00 | 24.66 |
August | 55.67 | 24.59 | 507.83 | 24.36 | 55.67 | 24.38 |
September | 38.83 | 24.02 | 327.33 | 24.39 | 14.50 | 24.39 |
October | 298.33 | 23.54 | 96.00 | 23.74 | 0.00 | 23.74 |
November | 464.67 | 23.27 | 0.00 | 23.27 | 0.00 | 23.27 |
December | 497.00 | 22.63 | 5.00 | 22.61 | 5.00 | 22.59 |
Annual Sum or Average | 3385.00 | 23.20 | 1912.50 | 23.63 | 207.67 | 23.66 |
Minimum of Months | 3.83 | 22.29 | 0.00 | 22.25 | 0.00 | 22.21 |
Maximum of Months | 502.00 | 25.08 | 507.83 | 24.58 | 108.00 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 468.67 | 22.39 | 26.83 | 22.38 | 20.00 | 22.32 |
February | 395.83 | 22.76 | 15.17 | 22.80 | 6.83 | 22.77 |
March | 340.00 | 23.24 | 34.17 | 23.41 | 0.67 | 23.42 |
April | 186.83 | 23.76 | 92.00 | 24.16 | 5.33 | 24.23 |
May | 126.50 | 24.25 | 207.50 | 24.58 | 21.50 | 24.72 |
June | 31.33 | 25.99 | 388.67 | 24.56 | 22.50 | 24.68 |
July | 121.17 | 25.59 | 487.17 | 24.72 | 121.17 | 24.86 |
August | 75.83 | 25.38 | 501.67 | 24.46 | 74.50 | 24.57 |
September | 51.67 | 24.74 | 389.83 | 24.49 | 28.83 | 24.57 |
October | 211.50 | 23.34 | 163.17 | 23.95 | 5.67 | 24.00 |
November | 398.50 | 23.06 | 18.67 | 23.18 | 0.00 | 23.18 |
December | 472.33 | 22.46 | 21.33 | 22.42 | 19.50 | 22.36 |
Annual Sum or Average | 2880.17 | 23.18 | 2346.17 | 23.76 | 326.50 | 23.84 |
Minimum of Months | 31.33 | 22.39 | 15.17 | 22.38 | 0.00 | 22.32 |
Maximum of Months | 472.33 | 25.99 | 501.67 | 24.72 | 121.17 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 328.50 | 22.79 | 91.33 | 23.18 | 24.33 | 23.13 |
February | 256.50 | 23.10 | 80.50 | 23.50 | 12.17 | 23.49 |
March | 279.17 | 23.51 | 51.67 | 23.77 | 2.00 | 23.80 |
April | 182.33 | 23.79 | 48.00 | 24.16 | 0.67 | 24.17 |
May | 157.50 | 23.78 | 131.33 | 24.24 | 2.50 | 24.25 |
June | 26.33 | 24.22 | 319.50 | 24.43 | 3.83 | 24.45 |
July | 116.00 | 25.26 | 487.17 | 24.64 | 116.00 | 24.74 |
August | 71.67 | 25.30 | 510.17 | 24.52 | 71.67 | 24.61 |
September | 53.67 | 25.84 | 405.33 | 24.77 | 45.00 | 24.90 |
October | 134.17 | 24.05 | 254.83 | 24.62 | 23.33 | 24.77 |
November | 237.67 | 23.63 | 119.83 | 24.16 | 9.17 | 24.24 |
December | 296.33 | 23.07 | 84.50 | 23.47 | 12.83 | 23.48 |
Annual Sum or Average | 2139.83 | 23.60 | 2584.17 | 24.17 | 323.50 | 24.24 |
Minimum of Months | 26.33 | 22.79 | 48.00 | 23.18 | 0.67 | 23.13 |
Maximum of Months | 328.50 | 25.84 | 510.17 | 24.77 | 116.00 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 416.67 | 22.72 | 13.50 | 22.82 | 0.00 | 22.82 |
February | 275.00 | 23.33 | 54.00 | 23.63 | 0.67 | 23.64 |
March | 118.67 | 23.94 | 117.50 | 24.60 | 8.33 | 24.70 |
April | 35.50 | 25.78 | 219.50 | 25.35 | 20.17 | 25.48 |
May | 64.17 | 24.44 | 265.83 | 24.72 | 14.50 | 24.81 |
June | 26.17 | 26.84 | 448.50 | 24.70 | 25.00 | 24.81 |
July | 126.50 | 25.71 | 497.00 | 24.86 | 126.50 | 25.00 |
August | 90.83 | 25.83 | 514.00 | 24.74 | 90.83 | 24.88 |
September | 34.50 | 26.00 | 431.67 | 24.72 | 34.50 | 24.81 |
October | 106.67 | 24.05 | 242.83 | 24.61 | 14.67 | 24.71 |
November | 152.00 | 23.81 | 84.33 | 24.35 | 3.00 | 24.39 |
December | 260.17 | 23.71 | 55.00 | 24.05 | 1.33 | 24.07 |
Annual Sum or Average | 1706.83 | 23.88 | 2943.67 | 24.44 | 339.50 | 24.56 |
Minimum of Months | 26.17 | 22.72 | 13.50 | 22.82 | 0.00 | 22.82 |
Maximum of Months | 416.67 | 26.84 | 514.00 | 25.35 | 126.50 | 25.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.76 | 343.50 | 20.63 | 343.50 | 20.58 |
February | 454.00 | 21.21 | 198.33 | 21.02 | 198.33 | 20.92 |
March | 514.00 | 22.31 | 55.83 | 22.17 | 55.83 | 22.05 |
April | 439.17 | 23.35 | 0.83 | 23.35 | 0.83 | 23.34 |
May | 254.83 | 23.65 | 63.00 | 23.81 | 1.17 | 23.82 |
June | 20.83 | 23.63 | 289.33 | 24.40 | 0.00 | 24.40 |
July | 117.00 | 24.61 | 487.00 | 24.49 | 117.00 | 24.51 |
August | 74.33 | 24.26 | 487.67 | 24.31 | 72.83 | 24.30 |
September | 78.83 | 23.61 | 251.00 | 24.15 | 13.33 | 24.14 |
October | 383.17 | 22.64 | 73.33 | 22.73 | 22.83 | 22.65 |
November | 489.00 | 21.61 | 137.50 | 21.41 | 137.50 | 21.28 |
December | 497.00 | 20.68 | 383.83 | 20.59 | 383.83 | 20.56 |
Annual Sum or Average | 3824.17 | 22.06 | 2771.17 | 22.37 | 1347.00 | 22.16 |
Minimum of Months | 20.83 | 20.68 | 0.83 | 20.59 | 0.00 | 20.56 |
Maximum of Months | 514.00 | 24.61 | 487.67 | 24.49 | 383.83 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 21.29 | 201.17 | 21.07 | 201.17 | 20.96 |
February | 370.17 | 21.68 | 97.17 | 21.48 | 95.50 | 21.33 |
March | 364.83 | 22.61 | 26.17 | 22.69 | 10.83 | 22.65 |
April | 197.83 | 23.46 | 75.83 | 24.01 | 4.67 | 24.07 |
May | 147.83 | 24.04 | 157.83 | 24.53 | 24.00 | 24.71 |
June | 45.17 | 25.46 | 309.67 | 24.75 | 25.50 | 24.91 |
July | 112.50 | 25.85 | 410.33 | 24.97 | 112.50 | 25.12 |
August | 76.00 | 25.62 | 415.00 | 24.70 | 73.83 | 24.83 |
September | 70.50 | 24.29 | 290.00 | 24.50 | 27.17 | 24.60 |
October | 240.67 | 22.83 | 118.67 | 23.39 | 13.00 | 23.37 |
November | 388.83 | 22.07 | 44.17 | 22.00 | 37.67 | 21.90 |
December | 422.00 | 21.12 | 228.67 | 20.92 | 228.67 | 20.82 |
Annual Sum or Average | 2863.33 | 22.44 | 2374.67 | 23.01 | 854.50 | 22.92 |
Minimum of Months | 45.17 | 21.12 | 26.17 | 20.92 | 4.67 | 20.82 |
Maximum of Months | 427.00 | 25.85 | 415.00 | 24.97 | 228.67 | 25.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 343.83 | 22.44 | 152.33 | 22.73 | 78.83 | 22.57 |
February | 274.50 | 22.68 | 99.00 | 23.09 | 29.17 | 23.02 |
March | 325.83 | 23.10 | 52.50 | 23.35 | 7.33 | 23.36 |
April | 242.33 | 23.51 | 35.83 | 23.81 | 0.50 | 23.81 |
May | 196.00 | 23.62 | 100.83 | 24.02 | 1.67 | 24.02 |
June | 52.67 | 23.71 | 283.17 | 24.34 | 1.17 | 24.35 |
July | 121.67 | 25.01 | 479.67 | 24.61 | 121.67 | 24.68 |
August | 77.83 | 25.13 | 500.83 | 24.53 | 77.83 | 24.60 |
September | 69.17 | 25.48 | 387.50 | 24.78 | 50.17 | 24.92 |
October | 168.83 | 23.85 | 251.17 | 24.54 | 33.67 | 24.69 |
November | 269.00 | 23.22 | 129.83 | 23.83 | 23.67 | 23.90 |
December | 320.00 | 22.47 | 151.33 | 22.67 | 81.67 | 22.50 |
Annual Sum or Average | 2461.67 | 23.26 | 2624.00 | 23.88 | 507.33 | 23.89 |
Minimum of Months | 52.67 | 22.44 | 35.83 | 22.67 | 0.50 | 22.50 |
Maximum of Months | 343.83 | 25.48 | 500.83 | 24.78 | 121.67 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 482.83 | 21.42 | 179.33 | 21.21 | 179.33 | 21.10 |
February | 400.67 | 21.80 | 82.00 | 21.68 | 76.67 | 21.56 |
March | 423.83 | 22.54 | 37.17 | 22.68 | 9.50 | 22.66 |
April | 268.67 | 23.41 | 72.33 | 23.77 | 7.17 | 23.84 |
May | 162.00 | 23.56 | 175.67 | 24.16 | 10.50 | 24.24 |
June | 48.00 | 24.57 | 366.50 | 24.56 | 17.17 | 24.66 |
July | 125.67 | 24.87 | 495.00 | 24.59 | 125.67 | 24.64 |
August | 77.00 | 24.87 | 510.17 | 24.48 | 77.00 | 24.53 |
September | 68.33 | 24.37 | 354.67 | 24.49 | 30.67 | 24.58 |
October | 274.50 | 22.79 | 128.67 | 23.33 | 11.50 | 23.36 |
November | 431.50 | 22.12 | 40.00 | 22.10 | 29.50 | 22.02 |
December | 485.50 | 21.45 | 197.67 | 21.26 | 197.67 | 21.15 |
Annual Sum or Average | 3248.50 | 22.42 | 2639.17 | 23.06 | 772.33 | 22.98 |
Minimum of Months | 48.00 | 21.42 | 37.17 | 21.21 | 7.17 | 21.10 |
Maximum of Months | 485.50 | 24.87 | 510.17 | 24.59 | 197.67 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.10 | 455.50 | 20.05 | 455.50 | 20.02 |
February | 454.00 | 20.52 | 330.83 | 20.38 | 330.83 | 20.32 |
March | 514.00 | 21.58 | 176.17 | 21.31 | 176.17 | 21.15 |
April | 436.83 | 22.88 | 39.00 | 22.71 | 39.00 | 22.56 |
May | 267.17 | 23.31 | 72.00 | 23.52 | 9.00 | 23.46 |
June | 48.67 | 23.66 | 306.67 | 24.35 | 3.83 | 24.38 |
July | 120.83 | 24.93 | 489.17 | 24.58 | 120.83 | 24.64 |
August | 80.33 | 24.44 | 487.33 | 24.36 | 75.50 | 24.38 |
September | 129.17 | 23.40 | 235.67 | 23.99 | 16.50 | 23.99 |
October | 410.00 | 22.08 | 136.50 | 22.00 | 94.83 | 21.82 |
November | 489.00 | 20.74 | 309.00 | 20.51 | 309.00 | 20.41 |
December | 497.00 | 20.06 | 479.50 | 20.04 | 479.50 | 20.03 |
Annual Sum or Average | 3949.00 | 21.53 | 3517.33 | 21.81 | 2110.50 | 21.55 |
Minimum of Months | 48.67 | 20.06 | 39.00 | 20.04 | 3.83 | 20.02 |
Maximum of Months | 514.00 | 24.93 | 489.17 | 24.58 | 479.50 | 24.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.59 | 353.83 | 20.42 | 353.83 | 20.35 |
February | 452.50 | 21.14 | 203.17 | 20.84 | 203.17 | 20.69 |
March | 451.17 | 22.27 | 86.33 | 22.07 | 81.00 | 21.89 |
April | 216.67 | 23.17 | 87.33 | 23.62 | 13.83 | 23.57 |
May | 166.33 | 23.89 | 197.50 | 24.37 | 30.17 | 24.54 |
June | 56.17 | 25.22 | 395.50 | 24.61 | 29.67 | 24.76 |
July | 127.67 | 25.66 | 490.50 | 24.84 | 127.67 | 24.98 |
August | 88.50 | 25.43 | 498.33 | 24.60 | 84.00 | 24.72 |
September | 93.33 | 24.00 | 353.17 | 24.33 | 33.17 | 24.42 |
October | 296.83 | 22.54 | 148.17 | 22.87 | 44.33 | 22.74 |
November | 480.83 | 21.44 | 178.83 | 21.15 | 177.00 | 20.99 |
December | 497.00 | 20.41 | 376.00 | 20.28 | 376.00 | 20.22 |
Annual Sum or Average | 3429.00 | 21.95 | 3368.67 | 22.46 | 1553.83 | 22.26 |
Minimum of Months | 56.17 | 20.41 | 86.33 | 20.28 | 13.83 | 20.22 |
Maximum of Months | 502.00 | 25.66 | 498.33 | 24.84 | 376.00 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 376.33 | 21.57 | 211.83 | 21.50 | 170.00 | 21.24 |
February | 313.33 | 21.87 | 157.67 | 21.84 | 112.33 | 21.59 |
March | 370.50 | 22.45 | 104.33 | 22.41 | 70.50 | 22.21 |
April | 276.00 | 23.04 | 60.50 | 23.14 | 25.83 | 22.99 |
May | 228.50 | 23.27 | 106.50 | 23.68 | 11.00 | 23.64 |
June | 75.33 | 23.54 | 290.00 | 24.27 | 5.67 | 24.31 |
July | 119.17 | 25.09 | 480.17 | 24.63 | 119.17 | 24.71 |
August | 81.17 | 25.07 | 496.50 | 24.53 | 78.17 | 24.60 |
September | 96.33 | 24.71 | 361.00 | 24.62 | 49.67 | 24.77 |
October | 207.17 | 23.13 | 243.00 | 23.84 | 50.00 | 23.82 |
November | 316.50 | 22.31 | 140.17 | 22.48 | 69.33 | 22.23 |
December | 357.67 | 21.56 | 184.83 | 21.38 | 157.83 | 21.11 |
Annual Sum or Average | 2818.00 | 22.61 | 2836.50 | 23.16 | 919.50 | 22.99 |
Minimum of Months | 75.33 | 21.56 | 60.50 | 21.38 | 5.67 | 21.11 |
Maximum of Months | 376.33 | 25.09 | 496.50 | 24.63 | 170.00 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.50 | 20.85 | 321.17 | 20.60 | 321.17 | 20.49 |
February | 416.17 | 21.24 | 194.17 | 20.99 | 192.50 | 20.85 |
March | 438.00 | 21.91 | 114.00 | 21.87 | 91.17 | 21.72 |
April | 292.83 | 22.91 | 84.50 | 23.23 | 22.67 | 23.22 |
May | 201.00 | 23.17 | 167.50 | 23.83 | 15.50 | 23.89 |
June | 71.17 | 24.08 | 363.17 | 24.47 | 20.00 | 24.58 |
July | 118.50 | 24.94 | 493.67 | 24.60 | 118.50 | 24.65 |
August | 77.17 | 24.89 | 503.67 | 24.48 | 75.33 | 24.54 |
September | 110.00 | 23.79 | 325.00 | 24.31 | 33.50 | 24.40 |
October | 311.83 | 22.32 | 155.67 | 22.71 | 52.00 | 22.60 |
November | 455.83 | 21.45 | 159.17 | 21.21 | 153.83 | 21.05 |
December | 494.67 | 20.90 | 336.83 | 20.66 | 336.83 | 20.56 |
Annual Sum or Average | 3483.67 | 21.94 | 3218.50 | 22.47 | 1433.00 | 22.27 |
Minimum of Months | 71.17 | 20.85 | 84.50 | 20.60 | 15.50 | 20.49 |
Maximum of Months | 496.50 | 24.94 | 503.67 | 24.60 | 336.83 | 24.65 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 1.17 | 27.00 | 454.00 | 27.00 | 1.17 | 27.00 |
March | 9.83 | 27.00 | 514.00 | 27.00 | 9.83 | 27.00 |
April | 18.83 | 27.11 | 485.00 | 27.01 | 18.83 | 27.01 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 10.50 | 27.00 | 496.00 | 27.00 | 10.50 | 27.00 |
July | 86.50 | 27.00 | 497.00 | 27.00 | 86.50 | 27.00 |
August | 161.33 | 27.06 | 514.00 | 27.03 | 161.33 | 27.03 |
September | 6.33 | 27.00 | 485.00 | 27.00 | 6.33 | 27.00 |
October | 16.33 | 27.00 | 502.00 | 27.00 | 16.33 | 27.00 |
November | 10.17 | 27.00 | 489.00 | 27.00 | 10.17 | 27.00 |
December | 6.50 | 27.00 | 497.00 | 27.00 | 6.50 | 27.00 |
Annual Sum or Average | 327.50 | 27.04 | 5943.00 | 27.00 | 327.50 | 27.01 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 161.33 | 27.11 | 514.00 | 27.03 | 161.33 | 27.03 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 448.17 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 437.33 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 2.17 | 27.39 | 485.00 | 27.00 | 2.17 | 27.01 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 2.00 | 27.00 | 496.00 | 27.00 | 2.00 | 27.00 |
July | 6.50 | 27.00 | 497.00 | 27.00 | 6.50 | 27.00 |
August | 23.00 | 27.26 | 514.00 | 27.03 | 23.00 | 27.04 |
September | 1.00 | 27.00 | 485.00 | 27.00 | 1.00 | 27.00 |
October | 3.50 | 27.00 | 502.00 | 27.00 | 3.50 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 454.67 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 38.17 | 27.18 | 5830.17 | 27.00 | 38.17 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 437.33 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 23.00 | 27.39 | 514.00 | 27.03 | 23.00 | 27.04 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 88.67 | 25.54 | 242.00 | 26.61 | 0.00 | 26.61 |
February | 8.33 | 27.00 | 322.17 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 474.33 | 27.00 | 0.00 | 27.00 |
April | 3.00 | 27.09 | 485.00 | 27.00 | 3.00 | 27.00 |
May | 0.00 | 0.00 | 502.67 | 27.00 | 0.00 | 27.00 |
June | 7.50 | 27.00 | 496.00 | 27.00 | 7.50 | 27.00 |
July | 27.00 | 27.00 | 497.00 | 27.00 | 27.00 | 27.00 |
August | 52.50 | 27.12 | 514.00 | 27.02 | 52.50 | 27.03 |
September | 4.00 | 27.00 | 485.00 | 27.00 | 4.00 | 27.00 |
October | 6.17 | 27.00 | 482.67 | 27.00 | 6.17 | 27.00 |
November | 0.00 | 0.00 | 412.50 | 27.00 | 0.00 | 27.00 |
December | 11.50 | 27.00 | 284.67 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 208.67 | 26.41 | 5198.00 | 26.98 | 100.17 | 26.98 |
Minimum of Months | 0.00 | 0.00 | 242.00 | 26.61 | 0.00 | 26.61 |
Maximum of Months | 88.67 | 27.12 | 514.00 | 27.02 | 52.50 | 27.03 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5943.00 | 27.00 | 5943.00 | 27.00 | 5943.00 | 27.00 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 16.92504 | 0.71259 | 15.76836 |
February | 454.00000 | 27.00002 | 17.37891 | 0.77453 | 17.72414 |
March | 514.00000 | 27.00002 | 18.03988 | 0.83420 | 19.74026 |
April | 485.00000 | 27.00437 | 16.80465 | 0.87930 | 21.37773 |
May | 508.00000 | 27.00018 | 20.10901 | 0.14226 | 5.51504 |
June | 496.00000 | 27.00042 | 24.15475 | 0.24241 | 6.28982 |
July | 497.00000 | 27.00058 | 26.21642 | 0.31339 | 7.09790 |
August | 514.00000 | 27.01852 | 25.78620 | 0.35469 | 7.70139 |
September | 485.00000 | 27.00075 | 25.51858 | 0.20389 | 5.93691 |
October | 502.00000 | 27.00027 | 20.86676 | 0.84681 | 20.22473 |
November | 489.00000 | 27.00004 | 18.19698 | 0.83320 | 19.71092 |
December | 497.00000 | 26.99999 | 14.76282 | 0.81552 | 19.09825 |
Annual Sum or Average | 5943.00000 | 27.00215 | 20.42336 | 0.57747 | 13.80572 |
Minimum of Months | 454.00000 | 26.99999 | 14.76282 | 0.14226 | 5.51504 |
Maximum of Months | 514.00000 | 27.01852 | 26.21642 | 0.87930 | 21.37773 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 16.90850 | 0.60525 | 12.80251 |
February | 454.00000 | 27.00002 | 17.36272 | 0.65486 | 14.15596 |
March | 514.00000 | 27.00002 | 18.01511 | 0.71722 | 15.93749 |
April | 485.00000 | 27.00292 | 16.78152 | 0.77167 | 17.64657 |
May | 508.00000 | 27.00016 | 20.12372 | 0.07667 | 5.25622 |
June | 496.00000 | 27.00040 | 24.16324 | 0.16423 | 5.65493 |
July | 497.00000 | 27.00057 | 26.23903 | 0.21619 | 6.03843 |
August | 514.00000 | 27.01555 | 25.80417 | 0.23760 | 6.26836 |
September | 485.00000 | 27.00066 | 25.62470 | 0.14156 | 5.51166 |
October | 502.00000 | 27.00025 | 20.86678 | 0.76302 | 17.42075 |
November | 489.00000 | 27.00004 | 18.18106 | 0.69924 | 15.40197 |
December | 497.00000 | 26.99999 | 14.74201 | 0.63090 | 13.49268 |
Annual Sum or Average | 5943.00000 | 27.00176 | 20.42772 | 0.47135 | 11.26669 |
Minimum of Months | 454.00000 | 26.99999 | 14.74201 | 0.07667 | 5.25622 |
Maximum of Months | 514.00000 | 27.01555 | 26.23903 | 0.77167 | 17.64657 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.69800 | 17.15544 | 0.46289 | 10.26684 |
February | 454.00000 | 27.00002 | 17.37824 | 0.57836 | 12.28650 |
March | 514.00000 | 27.00002 | 18.03095 | 0.66262 | 14.45929 |
April | 485.00000 | 27.00142 | 16.79445 | 0.74834 | 16.99859 |
May | 508.00000 | 27.00015 | 20.14622 | 0.06836 | 5.36584 |
June | 496.00000 | 27.00042 | 24.17406 | 0.17808 | 5.84672 |
July | 497.00000 | 27.00060 | 26.24038 | 0.24071 | 6.33672 |
August | 514.00000 | 27.01265 | 25.81001 | 0.25557 | 6.52496 |
September | 485.00000 | 27.00066 | 25.64125 | 0.13988 | 5.59524 |
October | 502.00000 | 27.00026 | 20.88779 | 0.72664 | 16.41156 |
November | 489.00000 | 27.00004 | 18.19495 | 0.62133 | 13.33694 |
December | 497.00000 | 26.99999 | 14.75228 | 0.54056 | 11.36629 |
Annual Sum or Average | 5943.00000 | 26.97588 | 20.46076 | 0.43373 | 10.37532 |
Minimum of Months | 454.00000 | 26.69800 | 14.75228 | 0.06836 | 5.36584 |
Maximum of Months | 514.00000 | 27.01265 | 26.24038 | 0.74834 | 16.99859 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 33.85744 | 1.07174 | 29.24322 |
February | 454.00000 | 27.00000 | 33.64505 | 1.23153 | 36.80775 |
March | 514.00000 | 27.00000 | 33.52481 | 1.38186 | 44.54930 |
April | 485.00000 | 27.00000 | 33.51225 | 1.52406 | 52.20919 |
May | 508.00000 | 27.00000 | 33.77038 | 0.50676 | 10.40475 |
June | 496.00000 | 27.00000 | 33.72073 | 0.73679 | 16.43721 |
July | 497.00000 | 27.00000 | 33.67396 | 0.95066 | 24.09759 |
August | 514.00000 | 27.00000 | 33.67602 | 1.14820 | 32.76044 |
September | 485.00000 | 27.00000 | 33.88929 | 0.56185 | 11.63952 |
October | 502.00000 | 27.00000 | 33.64258 | 1.28029 | 39.26222 |
November | 489.00000 | 27.00000 | 33.74224 | 1.41142 | 46.12276 |
December | 497.00000 | 27.00000 | 33.64332 | 1.52923 | 52.49006 |
Annual Sum or Average | 5943.00000 | 27.00000 | 33.69146 | 1.11013 | 32.95656 |
Minimum of Months | 454.00000 | 27.00000 | 33.51225 | 0.50676 | 10.40475 |
Maximum of Months | 514.00000 | 27.00000 | 33.88929 | 1.52923 | 52.49006 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.52243 | 14.69933 | 0.29420 | 7.23309 |
February | 454.00000 | 24.52245 | 15.74186 | 0.30317 | 7.33991 |
March | 514.00000 | 24.45878 | 15.54202 | 0.29577 | 7.12991 |
April | 485.00000 | 24.56250 | 13.88142 | 0.31007 | 7.46523 |
May | 508.00000 | 24.54402 | 21.37319 | -0.4943 | 11.14936 |
June | 496.00000 | 24.51656 | 32.24980 | -0.4151 | 9.47646 |
July | 497.00000 | 24.67524 | 45.95193 | -0.2626 | 7.65614 |
August | 514.00000 | 24.54632 | 45.62962 | -0.2942 | 7.78130 |
September | 485.00000 | 24.62019 | 37.67845 | -0.3336 | 8.64193 |
October | 502.00000 | 24.66318 | 22.80700 | 0.40920 | 9.28191 |
November | 489.00000 | 24.63568 | 16.13749 | 0.35123 | 8.19075 |
December | 497.00000 | 24.60743 | 12.57612 | 0.31081 | 7.56107 |
Annual Sum or Average | 5943.00000 | 24.57269 | 24.60994 | 0.03682 | 8.25031 |
Minimum of Months | 454.00000 | 24.45878 | 12.57612 | -0.4943 | 7.12991 |
Maximum of Months | 514.00000 | 24.67524 | 45.95193 | 0.40920 | 11.14936 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.14237 | 16.66964 | 0.21795 | 6.15893 |
February | 454.00000 | 24.25423 | 17.34732 | 0.25874 | 6.56839 |
March | 514.00000 | 24.26956 | 16.59533 | 0.27802 | 6.77633 |
April | 485.00000 | 24.28958 | 14.47580 | 0.28359 | 6.83591 |
May | 508.00000 | 24.26322 | 22.80248 | -0.5442 | 11.66777 |
June | 496.00000 | 24.21836 | 33.64761 | -0.4610 | 9.70712 |
July | 497.00000 | 24.25209 | 47.96737 | -0.3365 | 7.62166 |
August | 514.00000 | 24.21535 | 46.41284 | -0.3514 | 7.74637 |
September | 485.00000 | 24.33903 | 38.91351 | -0.3967 | 8.84002 |
October | 502.00000 | 24.35497 | 23.85115 | 0.35667 | 8.03789 |
November | 489.00000 | 24.33603 | 17.14291 | 0.29694 | 7.05445 |
December | 497.00000 | 24.34880 | 14.10273 | 0.26666 | 6.73185 |
Annual Sum or Average | 5943.00000 | 24.27329 | 25.91313 | -0.0137 | 7.82460 |
Minimum of Months | 454.00000 | 24.14237 | 14.10273 | -0.5442 | 6.15893 |
Maximum of Months | 514.00000 | 24.35497 | 47.96737 | 0.35667 | 11.66777 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.21979 | 18.61313 | -0.0259 | 5.52082 |
February | 454.00000 | 23.52385 | 19.30329 | 0.05825 | 5.47545 |
March | 514.00000 | 23.86345 | 18.03972 | 0.15010 | 5.68895 |
April | 485.00000 | 24.07878 | 15.37087 | 0.19915 | 5.97631 |
May | 508.00000 | 24.11526 | 23.35093 | -0.6202 | 13.43775 |
June | 496.00000 | 24.14557 | 33.77658 | -0.5219 | 10.95454 |
July | 497.00000 | 24.19764 | 47.82869 | -0.4004 | 8.57825 |
August | 514.00000 | 24.17938 | 46.84510 | -0.4118 | 8.75245 |
September | 485.00000 | 24.21077 | 39.45089 | -0.4665 | 9.90128 |
October | 502.00000 | 24.05368 | 24.81127 | 0.25953 | 6.81187 |
November | 489.00000 | 23.78216 | 19.10775 | 0.13181 | 5.64321 |
December | 497.00000 | 23.26131 | 16.74541 | -0.0272 | 5.48972 |
Annual Sum or Average | 5943.00000 | 23.88842 | 27.01574 | -0.1418 | 7.70848 |
Minimum of Months | 454.00000 | 23.21979 | 15.37087 | -0.6202 | 5.47545 |
Maximum of Months | 514.00000 | 24.21077 | 47.82869 | 0.25953 | 13.43775 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.51933 | 20.44558 | -0.4535 | 11.00686 |
February | 454.00000 | 22.06912 | 21.15224 | -0.3055 | 8.48883 |
March | 514.00000 | 23.03433 | 19.48688 | -0.0623 | 6.16974 |
April | 485.00000 | 23.77313 | 15.67567 | 0.11955 | 5.80370 |
May | 508.00000 | 24.01082 | 23.15587 | -0.6545 | 14.73557 |
June | 496.00000 | 24.15299 | 33.79457 | -0.5003 | 10.57824 |
July | 497.00000 | 24.26917 | 47.79006 | -0.3499 | 7.89802 |
August | 514.00000 | 24.22895 | 46.68149 | -0.3757 | 8.23161 |
September | 485.00000 | 24.15138 | 39.17230 | -0.4834 | 10.26246 |
October | 502.00000 | 23.53140 | 25.64237 | 0.12244 | 6.57551 |
November | 489.00000 | 22.45770 | 21.34320 | -0.2011 | 7.36347 |
December | 497.00000 | 21.52881 | 18.47461 | -0.4633 | 10.97698 |
Annual Sum or Average | 5943.00000 | 23.23614 | 27.80527 | -0.3011 | 9.01712 |
Minimum of Months | 454.00000 | 21.51933 | 15.67567 | -0.6545 | 5.80370 |
Maximum of Months | 514.00000 | 24.26917 | 47.79006 | 0.12244 | 14.73557 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.28788 | 17.99868 | -0.2491 | 6.98790 |
February | 454.00000 | 22.80966 | 18.52441 | -0.1179 | 6.13441 |
March | 514.00000 | 23.55254 | 17.06576 | 0.06635 | 5.56494 |
April | 485.00000 | 24.03128 | 14.21429 | 0.19321 | 6.03841 |
May | 508.00000 | 24.18891 | 22.21573 | -0.5816 | 12.89746 |
June | 496.00000 | 24.34064 | 32.55295 | -0.3898 | 8.75740 |
July | 497.00000 | 24.47172 | 46.50598 | -0.2266 | 6.92688 |
August | 514.00000 | 24.33361 | 45.29783 | -0.2920 | 7.32538 |
September | 485.00000 | 24.30633 | 38.14746 | -0.4223 | 9.44906 |
October | 502.00000 | 23.83151 | 24.03623 | 0.19658 | 6.66682 |
November | 489.00000 | 23.30968 | 18.13508 | 0.00598 | 5.48284 |
December | 497.00000 | 22.62573 | 15.41444 | -0.1833 | 6.28734 |
Annual Sum or Average | 5943.00000 | 23.68022 | 25.91895 | -0.1677 | 7.39036 |
Minimum of Months | 454.00000 | 22.28788 | 14.21429 | -0.5816 | 5.48284 |
Maximum of Months | 514.00000 | 24.47172 | 46.50598 | 0.19658 | 12.89746 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.54340 | 16.87981 | -0.1655 | 7.01175 |
February | 454.00000 | 22.97272 | 17.51810 | -0.0471 | 6.44683 |
March | 514.00000 | 23.58878 | 16.39257 | 0.12619 | 6.39979 |
April | 485.00000 | 24.10097 | 13.66456 | 0.28710 | 7.66313 |
May | 508.00000 | 24.31031 | 21.61345 | -0.4350 | 11.27275 |
June | 496.00000 | 24.34878 | 32.32884 | -0.2823 | 8.14444 |
July | 497.00000 | 24.49103 | 46.24439 | -0.1247 | 7.44066 |
August | 514.00000 | 24.30793 | 45.12849 | -0.2066 | 7.38138 |
September | 485.00000 | 24.34617 | 37.70899 | -0.3110 | 8.54956 |
October | 502.00000 | 23.94871 | 23.31582 | 0.27954 | 8.31098 |
November | 489.00000 | 23.30953 | 17.34345 | 0.04356 | 6.13087 |
December | 497.00000 | 22.56373 | 14.58903 | -0.1720 | 6.83570 |
Annual Sum or Average | 5943.00000 | 23.74148 | 25.30697 | -0.0848 | 7.64346 |
Minimum of Months | 454.00000 | 22.54340 | 13.66456 | -0.4350 | 6.13087 |
Maximum of Months | 514.00000 | 24.49103 | 46.24439 | 0.28710 | 11.27275 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.40681 | 15.90143 | 0.07206 | 8.11083 |
February | 454.00000 | 23.67520 | 16.45404 | 0.15581 | 7.66254 |
March | 514.00000 | 23.88208 | 15.99228 | 0.20270 | 6.98431 |
April | 485.00000 | 24.17124 | 13.69905 | 0.27286 | 7.24471 |
May | 508.00000 | 24.20941 | 22.03840 | -0.5519 | 12.77345 |
June | 496.00000 | 24.30393 | 32.59092 | -0.4034 | 9.16941 |
July | 497.00000 | 24.48581 | 46.40098 | -0.2038 | 7.02955 |
August | 514.00000 | 24.40602 | 44.91296 | -0.2095 | 6.94011 |
September | 485.00000 | 24.52465 | 37.19258 | -0.2407 | 7.97597 |
October | 502.00000 | 24.38216 | 22.52386 | 0.42255 | 10.64493 |
November | 489.00000 | 24.07619 | 16.16408 | 0.27354 | 8.28322 |
December | 497.00000 | 23.61789 | 13.43862 | 0.12969 | 7.81097 |
Annual Sum or Average | 5943.00000 | 24.09728 | 24.86160 | -0.0088 | 8.39585 |
Minimum of Months | 454.00000 | 23.40681 | 13.43862 | -0.5519 | 6.94011 |
Maximum of Months | 514.00000 | 24.52465 | 46.40098 | 0.42255 | 12.77345 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.01051 | 16.02265 | -0.0295 | 6.21289 |
February | 454.00000 | 23.78537 | 16.28093 | 0.18298 | 6.78327 |
March | 514.00000 | 24.30297 | 15.34537 | 0.34395 | 8.18271 |
April | 485.00000 | 24.59503 | 13.12222 | 0.46940 | 10.53495 |
May | 508.00000 | 24.40959 | 21.53200 | -0.3753 | 9.65784 |
June | 496.00000 | 24.51408 | 31.96864 | -0.1750 | 7.27197 |
July | 497.00000 | 24.64560 | 45.74595 | 0.00979 | 6.82856 |
August | 514.00000 | 24.55204 | 44.35439 | -0.0075 | 6.51850 |
September | 485.00000 | 24.54629 | 37.16342 | -0.2019 | 7.58738 |
October | 502.00000 | 24.38506 | 22.54871 | 0.42838 | 10.06690 |
November | 489.00000 | 24.26086 | 15.88698 | 0.31549 | 7.70648 |
December | 497.00000 | 24.15274 | 12.86629 | 0.24622 | 6.98093 |
Annual Sum or Average | 5943.00000 | 24.26578 | 24.48634 | 0.09929 | 7.86517 |
Minimum of Months | 454.00000 | 23.01051 | 12.86629 | -0.3753 | 6.21289 |
Maximum of Months | 514.00000 | 24.64560 | 45.74595 | 0.46940 | 10.53495 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.76264 | 19.40334 | -0.6435 | 14.51990 |
February | 454.00000 | 21.21106 | 20.36370 | -0.5157 | 11.54936 |
March | 514.00000 | 22.31285 | 19.00471 | -0.2389 | 7.36043 |
April | 485.00000 | 23.43404 | 15.39713 | 0.02785 | 5.87740 |
May | 508.00000 | 23.94137 | 22.85827 | -0.6872 | 16.02737 |
June | 496.00000 | 24.28079 | 32.44489 | -0.4412 | 9.66609 |
July | 497.00000 | 24.45394 | 46.10640 | -0.2709 | 7.24644 |
August | 514.00000 | 24.29516 | 45.44864 | -0.3481 | 7.97621 |
September | 485.00000 | 24.11907 | 38.70862 | -0.5102 | 11.13552 |
October | 502.00000 | 22.98477 | 25.42754 | -0.0171 | 6.96524 |
November | 489.00000 | 21.61342 | 20.16721 | -0.4043 | 9.55169 |
December | 497.00000 | 20.67745 | 17.37597 | -0.6793 | 15.41172 |
Annual Sum or Average | 5943.00000 | 22.85303 | 26.96243 | -0.3936 | 10.26946 |
Minimum of Months | 454.00000 | 20.67745 | 15.39713 | -0.6872 | 5.87740 |
Maximum of Months | 514.00000 | 24.45394 | 46.10640 | 0.02785 | 16.02737 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.28751 | 17.49322 | -0.4985 | 11.48416 |
February | 385.00000 | 21.79180 | 18.29160 | -0.3509 | 9.40225 |
March | 433.00000 | 22.90694 | 16.89166 | -0.0569 | 6.90120 |
April | 410.00000 | 24.01781 | 13.63910 | 0.24057 | 7.76137 |
May | 430.00000 | 24.26833 | 21.69318 | -0.4701 | 12.95532 |
June | 418.00000 | 24.45323 | 31.36023 | -0.2748 | 8.69439 |
July | 422.00000 | 24.70659 | 44.65120 | -0.0843 | 8.00964 |
August | 433.00000 | 24.49523 | 44.04292 | -0.1780 | 7.74574 |
September | 410.00000 | 24.31712 | 37.29350 | -0.3506 | 9.63391 |
October | 427.00000 | 23.54774 | 23.27826 | 0.16168 | 8.19456 |
November | 417.00000 | 22.23138 | 18.20214 | -0.2288 | 7.69895 |
December | 422.00000 | 21.12323 | 15.64549 | -0.5477 | 12.45135 |
Annual Sum or Average | 5034.00000 | 23.27065 | 25.26636 | -0.2195 | 9.24650 |
Minimum of Months | 385.00000 | 21.12323 | 13.63910 | -0.5477 | 6.90120 |
Maximum of Months | 433.00000 | 24.70659 | 44.65120 | 0.24057 | 12.95532 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.13261 | 16.30228 | 0.00079 | 9.37870 |
February | 454.00000 | 23.39670 | 17.06381 | 0.08563 | 8.46708 |
March | 514.00000 | 23.55252 | 16.69724 | 0.11651 | 7.15986 |
April | 485.00000 | 23.95875 | 14.12049 | 0.20420 | 6.95403 |
May | 508.00000 | 24.07621 | 22.41089 | -0.6123 | 14.50931 |
June | 496.00000 | 24.25270 | 32.44407 | -0.4491 | 10.09001 |
July | 497.00000 | 24.49732 | 45.90412 | -0.2365 | 7.30971 |
August | 514.00000 | 24.42643 | 44.83898 | -0.2377 | 7.28802 |
September | 485.00000 | 24.51111 | 37.12327 | -0.2540 | 8.44447 |
October | 502.00000 | 24.31642 | 22.64912 | 0.40180 | 11.05169 |
November | 489.00000 | 23.82703 | 16.73704 | 0.21074 | 8.83396 |
December | 497.00000 | 23.17334 | 14.37331 | 0.01304 | 8.97371 |
Annual Sum or Average | 5943.00000 | 23.92973 | 25.13927 | -0.0652 | 9.04974 |
Minimum of Months | 454.00000 | 23.13261 | 14.12049 | -0.6123 | 6.95403 |
Maximum of Months | 514.00000 | 24.51111 | 45.90412 | 0.40180 | 14.50931 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.51787 | 17.68267 | -0.4251 | 10.52553 |
February | 454.00000 | 22.08748 | 18.43858 | -0.2614 | 8.61342 |
March | 514.00000 | 22.87262 | 17.37725 | -0.0522 | 6.93346 |
April | 485.00000 | 23.86594 | 14.19568 | 0.20807 | 7.38784 |
May | 508.00000 | 24.08355 | 22.25791 | -0.5349 | 13.39919 |
June | 496.00000 | 24.35732 | 32.13775 | -0.3114 | 8.97680 |
July | 497.00000 | 24.51923 | 45.78587 | -0.1440 | 7.00983 |
August | 514.00000 | 24.41908 | 44.83869 | -0.1884 | 7.03935 |
September | 485.00000 | 24.29946 | 37.76984 | -0.3385 | 9.25930 |
October | 502.00000 | 23.46483 | 23.88854 | 0.16341 | 8.06779 |
November | 489.00000 | 22.36955 | 18.32892 | -0.1798 | 7.42743 |
December | 497.00000 | 21.51531 | 15.67161 | -0.4371 | 10.68220 |
Annual Sum or Average | 5943.00000 | 23.28971 | 25.77430 | -0.2086 | 8.78083 |
Minimum of Months | 454.00000 | 21.51531 | 14.19568 | -0.5349 | 6.93346 |
Maximum of Months | 514.00000 | 24.51923 | 45.78587 | 0.20807 | 13.39919 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.10174 | 20.29503 | -0.8586 | 22.67761 |
February | 454.00000 | 20.52086 | 21.25307 | -0.7256 | 17.85307 |
March | 514.00000 | 21.57923 | 19.82541 | -0.4350 | 10.77941 |
April | 485.00000 | 23.00758 | 15.65380 | -0.0792 | 6.88048 |
May | 508.00000 | 23.75438 | 22.89255 | -0.7496 | 18.97811 |
June | 496.00000 | 24.25785 | 32.69095 | -0.4319 | 9.97207 |
July | 497.00000 | 24.48848 | 46.31481 | -0.2344 | 7.17826 |
August | 514.00000 | 24.31466 | 45.51303 | -0.3248 | 7.96236 |
September | 485.00000 | 23.99619 | 38.66563 | -0.5494 | 12.54816 |
October | 502.00000 | 22.44633 | 25.99053 | -0.1600 | 8.68109 |
November | 489.00000 | 20.73876 | 21.41330 | -0.6474 | 15.89389 |
December | 497.00000 | 20.06395 | 18.09829 | -0.8880 | 23.67018 |
Annual Sum or Average | 5943.00000 | 22.45412 | 27.45106 | -0.5057 | 13.56122 |
Minimum of Months | 454.00000 | 20.06395 | 15.65380 | -0.8880 | 6.88048 |
Maximum of Months | 514.00000 | 24.48848 | 46.31481 | -0.0792 | 23.67018 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.58766 | 18.95136 | -0.7057 | 17.24530 |
February | 454.00000 | 21.15089 | 19.77584 | -0.5322 | 13.38956 |
March | 514.00000 | 22.51241 | 17.93836 | -0.1669 | 8.02382 |
April | 485.00000 | 23.84645 | 13.83817 | 0.20455 | 7.67319 |
May | 508.00000 | 24.15523 | 21.56758 | -0.4885 | 13.48864 |
June | 496.00000 | 24.37617 | 32.15177 | -0.2538 | 8.45719 |
July | 497.00000 | 24.61923 | 45.72792 | -0.0553 | 7.67892 |
August | 514.00000 | 24.42668 | 44.83798 | -0.1494 | 7.45381 |
September | 485.00000 | 24.20257 | 37.56974 | -0.3583 | 9.82308 |
October | 502.00000 | 23.25254 | 24.08243 | 0.08585 | 8.44192 |
November | 489.00000 | 21.47798 | 19.77066 | -0.4325 | 10.98286 |
December | 497.00000 | 20.41267 | 16.98397 | -0.7585 | 18.98807 |
Annual Sum or Average | 5943.00000 | 22.93215 | 26.16866 | -0.2995 | 10.95173 |
Minimum of Months | 454.00000 | 20.41267 | 13.83817 | -0.7585 | 7.45381 |
Maximum of Months | 514.00000 | 24.61923 | 45.72792 | 0.20455 | 18.98807 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.32618 | 17.33461 | -0.2385 | 11.95968 |
February | 454.00000 | 22.64831 | 18.11108 | -0.1299 | 10.32625 |
March | 514.00000 | 22.97377 | 17.52250 | -0.0443 | 8.25585 |
April | 485.00000 | 23.61139 | 14.35043 | 0.11579 | 7.35031 |
May | 508.00000 | 23.86408 | 22.46264 | -0.6798 | 17.49965 |
June | 496.00000 | 24.18484 | 32.77569 | -0.4519 | 10.77158 |
July | 497.00000 | 24.49680 | 46.22696 | -0.2091 | 7.33041 |
August | 514.00000 | 24.41538 | 45.00848 | -0.2207 | 7.40037 |
September | 485.00000 | 24.38789 | 37.10051 | -0.2891 | 9.35822 |
October | 502.00000 | 23.90913 | 23.07579 | 0.29006 | 10.61674 |
November | 489.00000 | 23.08850 | 17.93957 | 0.00123 | 9.29710 |
December | 497.00000 | 22.35774 | 15.31126 | -0.2285 | 12.10751 |
Annual Sum or Average | 5943.00000 | 23.52781 | 25.68194 | -0.1750 | 10.19887 |
Minimum of Months | 454.00000 | 22.32618 | 14.35043 | -0.6798 | 7.33041 |
Maximum of Months | 514.00000 | 24.49680 | 46.22696 | 0.29006 | 17.49965 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.88005 | 18.51324 | -0.6230 | 15.99058 |
February | 454.00000 | 21.47859 | 19.22917 | -0.4420 | 12.23464 |
March | 514.00000 | 22.28312 | 18.05292 | -0.2109 | 8.69936 |
April | 485.00000 | 23.50089 | 14.34979 | 0.11761 | 7.75552 |
May | 508.00000 | 23.86727 | 22.28059 | -0.6019 | 16.23381 |
June | 496.00000 | 24.28183 | 32.48672 | -0.3150 | 9.71853 |
July | 497.00000 | 24.51027 | 46.14620 | -0.1200 | 7.21159 |
August | 514.00000 | 24.40387 | 45.01753 | -0.1734 | 7.22642 |
September | 485.00000 | 24.15633 | 37.79914 | -0.3786 | 10.48925 |
October | 502.00000 | 23.04976 | 24.28984 | 0.05179 | 8.69747 |
November | 489.00000 | 21.62658 | 19.40885 | -0.3838 | 10.72604 |
December | 497.00000 | 20.91152 | 16.37115 | -0.6293 | 15.97876 |
Annual Sum or Average | 5943.00000 | 22.92332 | 26.23618 | -0.3085 | 10.90700 |
Minimum of Months | 454.00000 | 20.88005 | 14.34979 | -0.6293 | 7.21159 |
Maximum of Months | 514.00000 | 24.51027 | 46.14620 | 0.11761 | 16.23381 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.235421E+10 | 35654.32 | 05-JAN-15:00 | 70.88 | 0.121118E+11 | 0.00 | 0.144661E+11 | 0.49 | 6.00 | 05-JAN-15:00 | 0.00 | 0.00 |
February | 0.479864E+10 | 69027.07 | 14-FEB-16:40 | 102.82 | 0.306843E+11 | 0.00 | 0.354830E+11 | 0.83 | 7.70 | 14-FEB-14:20 | 0.00 | 0.00 |
March | 0.145747E+11 | 73571.97 | 08-MAR-16:20 | 161.80 | 0.887446E+11 | 0.00 | 0.103319E+12 | 1.22 | 7.69 | 13-MAR-14:10 | 0.00 | 0.00 |
April | 0.389963E+11 | 81624.34 | 28-APR-14:00 | 295.14 | 0.268193E+12 | 0.00 | 0.307189E+12 | 2.55 | 7.74 | 28-APR-10:00 | 0.00 | 0.00 |
May | 0.634254E+11 | 85161.62 | 23-MAY-12:30 | 379.59 | 0.444367E+12 | 0.00 | 0.507792E+12 | 3.34 | 7.74 | 15-MAY-09:50 | 0.00 | 0.00 |
June | 0.102900E+12 | 101002.66 | 28-JUN-14:50 | 549.36 | 0.735484E+12 | 0.00 | 0.838384E+12 | 5.08 | 7.76 | 07-JUN-05:04 | 0.00 | 0.00 |
July | 0.124497E+12 | 112007.09 | 31-JUL-15:00 | 654.73 | 0.884422E+12 | 0.00 | 0.100892E+13 | 5.80 | 7.82 | 19-JUL-05:03 | 0.00 | 0.00 |
August | 0.118802E+12 | 101780.94 | 23-AUG-16:00 | 666.97 | 0.847500E+12 | 0.00 | 0.966302E+12 | 5.85 | 7.94 | 26-AUG-05:02 | 0.00 | 0.00 |
September | 0.832948E+11 | 120157.44 | 05-SEP-13:10 | 462.48 | 0.591281E+12 | 0.00 | 0.674576E+12 | 4.26 | 7.96 | 05-SEP-05:03 | 0.00 | 0.00 |
October | 0.435211E+11 | 92766.34 | 02-OCT-11:00 | 304.21 | 0.300300E+12 | 0.00 | 0.343821E+12 | 2.57 | 7.76 | 04-OCT-09:50 | 0.00 | 0.00 |
November | 0.443420E+10 | 49742.11 | 02-NOV-15:00 | 94.27 | 0.239354E+11 | 0.00 | 0.283696E+11 | 0.68 | 7.30 | 02-NOV-15:00 | 0.00 | 0.00 |
December | 0.689480E+09 | 7331.32 | 24-DEC-15:23 | 87.33 | 0.355899E+10 | 0.00 | 0.424847E+10 | 0.61 | 5.27 | 14-DEC-06:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.602289E+12 | 3829.58 | 0.423058E+13 | 0.00 | 0.483287E+13 | 2.78 | 0.00 | 0.00 | ||||
Minimum of Months | 0.689480E+09 | 7331.32 | 70.88 | 0.355899E+10 | 0.00 | 0.424847E+10 | 0.49 | 5.27 | 0.00 | 0.00 | ||
Maximum of Months | 0.124497E+12 | 120157.44 | 666.97 | 0.884422E+12 | 0.00 | 0.100892E+13 | 5.85 | 7.96 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.529992E+10 | 81624.34 | 28-APR-14:00 | 20.17 | 0.396765E+11 | 0.00 | 0.449764E+11 | 0.21 | 7.64 | 27-APR-13:30 | 0.00 | 0.00 |
May | 0.124477E+11 | 85161.62 | 23-MAY-12:30 | 46.67 | 0.933541E+11 | 0.00 | 0.105802E+12 | 0.47 | 7.66 | 23-MAY-12:40 | 0.00 | 0.00 |
June | 0.447062E+11 | 101002.66 | 28-JUN-14:50 | 155.18 | 0.335088E+12 | 0.00 | 0.379794E+12 | 1.62 | 7.68 | 22-JUN-07:20 | 0.00 | 0.00 |
July | 0.612040E+11 | 112007.09 | 31-JUL-15:00 | 205.01 | 0.452641E+12 | 0.00 | 0.513845E+12 | 2.04 | 7.77 | 27-JUL-05:04 | 0.00 | 0.00 |
August | 0.584537E+11 | 101780.94 | 23-AUG-16:00 | 200.26 | 0.434782E+12 | 0.00 | 0.493236E+12 | 2.00 | 7.94 | 26-AUG-05:02 | 0.00 | 0.00 |
September | 0.313489E+11 | 120157.44 | 05-SEP-13:10 | 112.60 | 0.235477E+12 | 0.00 | 0.266826E+12 | 1.18 | 7.96 | 05-SEP-05:03 | 0.00 | 0.00 |
October | 0.915033E+10 | 92766.34 | 02-OCT-11:00 | 34.17 | 0.690035E+11 | 0.00 | 0.781538E+11 | 0.35 | 7.72 | 02-OCT-10:30 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.222611E+12 | 774.05 | 0.166002E+13 | 0.00 | 0.188263E+13 | 0.66 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.612040E+11 | 120157.44 | 205.01 | 0.452641E+12 | 0.00 | 0.513845E+12 | 2.04 | 7.96 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.140359E+10 | 744.00 | 5952.96 | 05-JAN-16:00 | 35862.33 | 26-JAN-17:00 | 19.80 | 18.33 | 3.07 |
February | 0.422104E+10 | 672.00 | 12476.23 | 12-FEB-14:02 | 68694.43 | 13-FEB-17:05 | 22.73 | 18.39 | 3.07 |
March | 0.117942E+11 | 744.00 | 12476.23 | 06-MAR-15:00 | 106691.09 | 31-MAR-23:40 | 25.89 | 18.56 | 3.07 |
April | 0.220036E+11 | 720.00 | 12476.23 | 01-APR-10:10 | 128999.99 | 16-APR-17:42 | 30.28 | 19.95 | 3.07 |
May | 0.207966E+11 | 744.00 | 12476.23 | 02-MAY-12:00 | 60294.85 | 31-MAY-23:50 | 23.81 | 20.84 | 3.07 |
June | 0.292894E+11 | 720.00 | 12476.23 | 01-JUN-00:10 | 90358.86 | 30-JUN-23:23 | 31.02 | 25.11 | 3.07 |
July | 0.334097E+11 | 744.00 | 12476.23 | 01-JUL-00:10 | 116316.41 | 04-JUL-18:41 | 36.27 | 27.58 | 3.07 |
August | 0.333579E+11 | 744.00 | 12476.23 | 01-AUG-00:03 | 137128.91 | 20-AUG-18:31 | 37.72 | 26.59 | 3.07 |
September | 0.261477E+11 | 720.00 | 12476.23 | 01-SEP-00:05 | 59609.50 | 30-SEP-24:00 | 25.14 | 21.97 | 3.07 |
October | 0.175567E+11 | 744.00 | 12476.23 | 01-OCT-00:10 | 81476.79 | 31-OCT-24:00 | 24.85 | 19.63 | 3.07 |
November | 0.783985E+10 | 720.00 | 12476.23 | 02-NOV-14:40 | 92864.96 | 02-NOV-16:30 | 25.45 | 18.34 | 3.07 |
December | 0.573877E+10 | 744.00 | 8108.54 | 01-DEC-16:00 | 113748.64 | 29-DEC-16:40 | 27.43 | 18.33 | 3.07 |
Annual Sum or Average | 0.213559E+12 | 8760.00 | 27.57 | 21.15 | 3.07 | ||||
Minimum of Months | 0.140359E+10 | 672.00 | 5952.96 | 35862.33 | 19.80 | 18.33 | 3.07 | ||
Maximum of Months | 0.334097E+11 | 744.00 | 12476.23 | 137128.91 | 37.72 | 27.58 | 3.07 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 263486.77 | 05-JAN-15:00 | 21.00 | 20.97 | 1.93 |
February | 9016622.22 | 16.42 | 341.59 | 14-FEB-16:00 | 788198.92 | 14-FEB-16:10 | 21.07 | 20.99 | 3.29 |
March | 34299653.30 | 78.26 | 685.05 | 08-MAR-14:00 | 806466.80 | 08-MAR-14:00 | 21.14 | 20.95 | 8.35 |
April | 0.159223E+09 | 186.36 | 882.07 | 14-APR-16:10 | 968167.16 | 12-APR-15:00 | 21.62 | 21.01 | 17.19 |
May | 0.481215E+09 | 313.89 | 2190.42 | 22-MAY-15:50 | 1039071.89 | 19-MAY-15:20 | 22.23 | 21.21 | 25.23 |
June | 0.332580E+10 | 462.70 | 15224.19 | 06-JUN-13:20 | 1080829.47 | 22-JUN-12:10 | 22.96 | 21.16 | 37.72 |
July | 0.131702E+11 | 560.78 | 15224.19 | 01-JUL-05:04 | 1036923.18 | 21-JUL-16:50 | 23.22 | 21.27 | 45.18 |
August | 0.100976E+11 | 526.81 | 15224.19 | 01-AUG-09:40 | 1046173.21 | 31-AUG-16:00 | 23.14 | 21.19 | 44.46 |
September | 0.255704E+10 | 399.50 | 15224.19 | 01-SEP-10:50 | 1062601.83 | 21-SEP-13:50 | 22.78 | 21.32 | 32.29 |
October | 0.515128E+09 | 218.95 | 15224.19 | 11-OCT-10:30 | 1016444.77 | 02-OCT-10:20 | 21.81 | 21.10 | 18.62 |
November | 4553602.14 | 19.75 | 210.36 | 02-NOV-15:10 | 425420.35 | 02-NOV-15:10 | 21.01 | 20.96 | 3.44 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 207007.43 | 15-DEC-12:50 | 20.99 | 20.98 | 0.74 |
Annual Sum or Average | 0.303541E+11 | 2783.41 | 21.92 | 21.09 | 19.98 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 207007.43 | 20.99 | 20.95 | 0.74 | ||
Maximum of Months | 0.131702E+11 | 560.78 | 15224.19 | 1080829.47 | 23.22 | 21.32 | 45.18 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.00 | 21.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.07 | 21.07 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.14 | 21.14 | 0.00 |
April | 9064236.79 | 5.50 | 564.83 | 28-APR-14:20 | 952650.78 | 17-APR-13:50 | 21.62 | 21.59 | 0.40 |
May | 65981888.59 | 22.83 | 2190.42 | 22-MAY-15:50 | 1039071.89 | 19-MAY-15:20 | 22.23 | 22.09 | 1.62 |
June | 0.193906E+10 | 128.83 | 15224.19 | 06-JUN-13:20 | 1080829.47 | 22-JUN-12:10 | 22.96 | 22.22 | 9.46 |
July | 0.796189E+10 | 167.52 | 15224.19 | 01-JUL-05:04 | 1036923.18 | 21-JUL-16:50 | 23.22 | 22.39 | 11.91 |
August | 0.666447E+10 | 159.58 | 15224.19 | 01-AUG-09:40 | 1046173.21 | 31-AUG-16:00 | 23.14 | 22.32 | 11.34 |
September | 0.129738E+10 | 87.08 | 15224.19 | 01-SEP-10:50 | 1062601.83 | 21-SEP-13:50 | 22.78 | 22.26 | 6.40 |
October | 0.173594E+09 | 27.58 | 15224.19 | 11-OCT-10:50 | 1016444.77 | 02-OCT-10:20 | 21.81 | 21.65 | 1.96 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.01 | 21.01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.99 | 20.99 | 0.00 |
Annual Sum or Average | 0.181114E+11 | 598.93 | 21.92 | 21.65 | 3.62 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.99 | 20.99 | 0.00 | ||
Maximum of Months | 0.796189E+10 | 167.52 | 15224.19 | 1080829.47 | 23.22 | 22.39 | 11.91 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.169176E+12 | 0.00 | 400.40 | 998567.03 | 24-JAN-06:01 | 0.00 | 29.01 | 56.71 | 0.31 | 0.00 | 0.03 | 0.49 | 24-JAN-06:01 |
February | 0.967922E+11 | 0.00 | 300.00 | 1006272.54 | 08-FEB-06:01 | 0.00 | 26.91 | 50.24 | 0.19 | 0.00 | 0.02 | 0.49 | 08-FEB-06:01 |
March | 0.229811E+11 | 0.00 | 173.40 | 901086.37 | 04-MAR-06:02 | 0.00 | 25.86 | 38.42 | 0.04 | 0.00 | 0.00 | 0.44 | 04-MAR-06:02 |
April | 0.302068E+10 | 0.00 | 43.03 | 136334.97 | 08-APR-06:05 | 0.00 | 24.47 | 27.75 | 0.01 | 0.00 | 0.00 | 0.07 | 08-APR-06:05 |
May | 0.296689E+09 | 0.00 | 9.87 | 39056.86 | 06-MAY-06:10 | 0.00 | 22.93 | 23.68 | 0.00 | 0.00 | 0.00 | 0.02 | 06-MAY-06:10 |
June | 1244163.05 | 0.00 | 1.79 | 455.89 | 09-JUN-05:25 | 0.00 | 22.74 | 22.88 | 0.00 | 0.00 | 0.00 | 0.00 | 09-JUN-05:25 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 22.73 | 22.73 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 22.73 | 22.73 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 22.73 | 22.73 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.142121E+11 | 0.00 | 92.28 | 813974.74 | 26-OCT-05:03 | 0.00 | 24.05 | 30.77 | 0.02 | 0.00 | 0.00 | 0.40 | 26-OCT-05:03 |
November | 0.380810E+11 | 0.00 | 245.17 | 959104.05 | 28-NOV-06:01 | 0.00 | 25.50 | 43.72 | 0.07 | 0.00 | 0.01 | 0.47 | 28-NOV-06:01 |
December | 0.168062E+12 | 0.00 | 418.22 | 1071590.98 | 09-DEC-05:01 | 0.00 | 27.62 | 56.96 | 0.31 | 0.00 | 0.03 | 0.53 | 09-DEC-05:01 |
Annual Sum or Average | 0.512623E+12 | 0.00 | 1684.18 | 0.00 | 24.77 | 34.88 | 0.08 | 0.00 | 0.01 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.73 | 22.73 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.169176E+12 | 0.00 | 418.22 | 1071590.98 | 0.00 | 29.01 | 56.96 | 0.31 | 0.00 | 0.03 | 0.53 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 19.80 | 19.80 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 22.73 | 22.73 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 25.89 | 25.89 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 30.28 | 30.28 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 23.81 | 23.81 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 31.02 | 31.02 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 36.27 | 36.27 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 37.72 | 37.72 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 25.14 | 25.14 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 24.85 | 24.85 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 25.45 | 25.45 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 27.43 | 27.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 27.57 | 27.57 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.80 | 19.80 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.72 | 37.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.874801E+09 | 0.00 | 25.49 | 0.874801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21105.60 | 05-JAN-14:10 | 21105.60 | 05-JAN-14:10 | 0.00 | 0.00 | 0.00 |
February | 0.288684E+10 | 0.00 | 37.39 | 0.288684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64914.31 | 14-FEB-15:50 | 64914.31 | 14-FEB-15:50 | 0.00 | 0.00 | 0.00 |
March | 0.920135E+10 | 0.00 | 128.71 | 0.920135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71224.04 | 08-MAR-16:00 | 71224.04 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.335933E+11 | 0.00 | 277.02 | 0.335933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100858.86 | 17-APR-15:20 | 100858.86 | 17-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.515670E+11 | 0.00 | 354.30 | 0.515670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105239.26 | 30-MAY-14:30 | 105239.26 | 30-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.101735E+12 | 0.00 | 521.64 | 0.101732E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 140542.28 | 29-JUN-05:03 | 130936.98 | 29-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.131826E+12 | 0.00 | 618.44 | 0.128217E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 144602.24 | 01-JUL-05:02 | 129587.18 | 05-JUL-14:50 | 0.00 | 0.00 | 0.00 |
August | 0.129946E+12 | 0.00 | 644.84 | 0.126408E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 143294.69 | 14-AUG-05:02 | 132570.12 | 07-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.743874E+11 | 0.00 | 439.43 | 0.733643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149830.61 | 05-SEP-13:10 | 106228.57 | 11-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.358027E+11 | 0.00 | 270.63 | 0.357819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104163.96 | 10-OCT-16:00 | 104163.96 | 10-OCT-16:00 | 0.00 | 0.00 | 0.00 |
November | 0.223797E+10 | 0.00 | 58.50 | 0.223797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35243.54 | 02-NOV-15:00 | 35243.54 | 02-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 540032.06 | 0.00 | 0.85 | 540032.06 | 0.00 | 0.00 | 0.00 | 0.00 | 2843.22 | 24-DEC-15:23 | 2843.22 | 24-DEC-15:23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.574059E+12 | 0.00 | 3377.23 | 0.565865E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 540032.06 | 0.00 | 0.85 | 540032.06 | 0.00 | 0.00 | 0.00 | 0.00 | 2843.22 | 2843.22 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.131826E+12 | 0.00 | 644.84 | 0.128217E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 149830.61 | 132570.12 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.783570E+10 | 0.00 | 69.93 | 0.783570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 174912.06 | 05-JAN-15:40 | 174912.06 | 05-JAN-15:40 | 0.00 | 0.00 | 0.00 |
February | 0.228936E+11 | 0.00 | 100.30 | 0.228936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 511185.45 | 14-FEB-16:00 | 511185.45 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.680710E+11 | 0.00 | 152.71 | 0.680710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 527919.52 | 08-MAR-16:00 | 527919.52 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.246290E+12 | 0.00 | 247.14 | 0.246290E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 841050.45 | 26-APR-15:20 | 841050.45 | 26-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.445055E+12 | 0.00 | 347.92 | 0.445055E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 946872.31 | 19-MAY-15:20 | 946872.31 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.866327E+12 | 0.00 | 461.57 | 0.866290E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1410138.80 | 29-JUN-05:03 | 1265054.23 | 29-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.105124E+13 | 0.00 | 499.90 | 0.102797E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1332156.89 | 01-JUL-05:02 | 1172965.90 | 21-JUL-14:50 | 0.00 | 0.00 | 0.00 |
August | 0.996513E+12 | 0.00 | 503.24 | 0.974056E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1353616.86 | 14-AUG-05:02 | 1119225.27 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.651386E+12 | 0.00 | 414.90 | 0.641929E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1279607.79 | 05-SEP-13:00 | 964317.82 | 21-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.295152E+12 | 0.00 | 273.41 | 0.294984E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 903699.58 | 06-OCT-15:30 | 903699.58 | 06-OCT-15:30 | 0.00 | 0.00 | 0.00 |
November | 0.160066E+11 | 0.00 | 90.76 | 0.160066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 278742.50 | 02-NOV-15:00 | 278742.50 | 02-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 11358595.73 | 0.00 | 86.80 | 11358595.73 | 0.00 | 0.00 | 0.00 | 0.00 | 40176.06 | 24-DEC-14:43 | 40176.06 | 24-DEC-14:43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.466678E+13 | 0.00 | 3248.60 | 0.461139E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 11358595.73 | 0.00 | 69.93 | 11358595.73 | 0.00 | 0.00 | 0.00 | 0.00 | 40176.06 | 40176.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.105124E+13 | 0.00 | 503.24 | 0.102797E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1410138.80 | 1265054.23 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.394535E+09 | 0.00 | 20.17 | 0.394535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13174.34 | 05-JAN-14:20 | 13174.34 | 05-JAN-14:20 | 0.00 | 0.00 | 0.00 |
February | 0.189525E+10 | 0.00 | 30.77 | 0.189525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45922.81 | 14-FEB-15:50 | 45922.81 | 14-FEB-15:50 | 0.00 | 0.00 | 0.00 |
March | 0.549794E+10 | 0.00 | 115.88 | 0.549794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53550.47 | 08-MAR-16:00 | 53550.47 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.256558E+11 | 0.00 | 231.00 | 0.256558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102498.97 | 26-APR-15:00 | 102498.97 | 26-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.490399E+11 | 0.00 | 341.04 | 0.490399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117298.38 | 19-MAY-15:20 | 117298.38 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.995448E+11 | 0.00 | 461.96 | 0.995432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 148010.26 | 28-JUN-14:50 | 148010.26 | 28-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.122368E+12 | 0.00 | 508.13 | 0.119757E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 147247.25 | 21-JUL-14:50 | 147247.25 | 21-JUL-14:50 | 0.00 | 0.00 | 0.00 |
August | 0.113999E+12 | 0.00 | 506.89 | 0.111642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 157161.83 | 13-AUG-15:31 | 138326.38 | 07-AUG-15:50 | 0.00 | 0.00 | 0.00 |
September | 0.705042E+11 | 0.00 | 406.62 | 0.697699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140842.54 | 05-SEP-13:30 | 116043.96 | 21-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.291977E+11 | 0.00 | 245.00 | 0.291977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103545.96 | 06-OCT-15:20 | 103545.96 | 06-OCT-15:20 | 0.00 | 0.00 | 0.00 |
November | 0.103100E+10 | 0.00 | 47.51 | 0.103100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25157.14 | 02-NOV-15:00 | 25157.14 | 02-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 342.12 | 0.00 | 0.29 | 342.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 | 16-DEC-14:30 | 0.39 | 16-DEC-14:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.519128E+12 | 0.00 | 2915.27 | 0.513424E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 342.12 | 0.00 | 0.29 | 342.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 | 0.39 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.122368E+12 | 0.00 | 508.13 | 0.119757E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 157161.83 | 148010.26 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 16995512.17 | 0.00 | 2.33 | 16995512.17 | 0.00 | 0.00 | 0.00 | 0.00 | 3114.21 | 02-JAN-15:00 | 3114.21 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.123474E+10 | 0.00 | 16.67 | 0.123474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39417.81 | 13-FEB-16:00 | 39417.81 | 13-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.341121E+10 | 0.00 | 71.33 | 0.341121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41000.58 | 08-MAR-14:00 | 41000.58 | 08-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.172376E+11 | 0.00 | 173.65 | 0.172376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57569.73 | 17-APR-15:00 | 57569.73 | 17-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.303525E+11 | 0.00 | 257.92 | 0.303515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89026.03 | 29-MAY-16:11 | 89026.03 | 29-MAY-16:11 | 0.00 | 0.00 | 0.00 |
June | 0.560556E+11 | 0.00 | 365.51 | 0.560390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80445.61 | 29-JUN-05:03 | 74222.74 | 29-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.686866E+11 | 0.00 | 396.75 | 0.672441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121964.75 | 02-JUL-19:30 | 90910.82 | 04-JUL-19:00 | 0.00 | 0.00 | 0.00 |
August | 0.680956E+11 | 0.00 | 420.64 | 0.668576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99526.35 | 13-AUG-18:17 | 83839.79 | 13-AUG-18:17 | 0.00 | 0.00 | 0.00 |
September | 0.461517E+11 | 0.00 | 335.28 | 0.452770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99210.01 | 05-SEP-13:00 | 68033.60 | 04-SEP-10:40 | 0.00 | 0.00 | 0.00 |
October | 0.215095E+11 | 0.00 | 192.48 | 0.215059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90547.77 | 01-OCT-14:24 | 90547.77 | 01-OCT-14:24 | 0.00 | 0.00 | 0.00 |
November | 0.607606E+09 | 0.00 | 28.64 | 0.607606E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23115.54 | 09-NOV-14:00 | 23115.54 | 09-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.313360E+12 | 0.00 | 2261.21 | 0.309783E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.686866E+11 | 0.00 | 420.64 | 0.672441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121964.75 | 90910.82 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.456303E+10 | 0.116780E+10 | 744.00 | 0.456247E+10 | 565441.00 | 0.00 | 0.34 | 01-JAN-16:50 | 0.12 | 21-JAN-07:40 | 2759.23 | 01-JAN-16:50 | 2752.50 | 01-JAN-16:50 | 26.85 | 20-JAN-17:00 | 653.52 | 01-JAN-16:50 | 0.00 |
February | 0.914176E+10 | 0.218744E+10 | 672.00 | 0.913888E+10 | 2878588.73 | 0.00 | 0.58 | 14-FEB-17:00 | 0.38 | 02-FEB-08:00 | 4724.55 | 15-FEB-17:00 | 4724.55 | 15-FEB-17:00 | 80.16 | 17-FEB-11:10 | 1248.22 | 14-FEB-17:00 | 0.00 |
March | 0.156914E+11 | 0.359261E+10 | 744.00 | 0.156865E+11 | 4917504.69 | 0.00 | 0.87 | 31-MAR-24:00 | 0.61 | 04-MAR-07:05 | 7749.75 | 31-MAR-24:00 | 7749.75 | 31-MAR-24:00 | 92.12 | 20-MAR-14:40 | 1805.45 | 12-MAR-17:01 | 0.00 |
April | 0.203898E+11 | 0.474268E+10 | 720.00 | 0.203890E+11 | 725295.68 | 0.00 | 1.00 | 01-APR-16:40 | 0.33 | 30-APR-24:00 | 8909.61 | 16-APR-18:22 | 8909.61 | 16-APR-18:22 | 64.55 | 15-APR-08:00 | 2484.11 | 13-APR-17:00 | 0.00 |
May | 0.604297E+10 | 0.163193E+10 | 744.00 | 0.600275E+10 | 40225102.62 | 0.00 | 0.50 | 31-MAY-23:40 | 0.20 | 05-MAY-06:15 | 4139.19 | 31-MAY-24:00 | 4139.19 | 31-MAY-24:00 | 267.40 | 24-MAY-15:30 | 1035.87 | 31-MAY-23:20 | 0.00 |
June | 0.111029E+11 | 0.318145E+10 | 720.00 | 0.110071E+11 | 95812752.89 | 0.00 | 0.70 | 30-JUN-23:13 | 0.44 | 09-JUN-06:20 | 6014.27 | 30-JUN-24:00 | 5981.18 | 30-JUN-24:00 | 318.27 | 30-JUN-14:00 | 2006.29 | 28-JUN-16:00 | 0.00 |
July | 0.167198E+11 | 0.486554E+10 | 744.00 | 0.164950E+11 | 0.224829E+09 | 0.00 | 0.90 | 04-JUL-18:11 | 0.67 | 08-JUL-06:10 | 7884.50 | 31-JUL-23:53 | 7875.98 | 31-JUL-23:45 | 450.48 | 07-JUL-17:00 | 2608.48 | 21-JUL-17:00 | 0.00 |
August | 0.216872E+11 | 0.591511E+10 | 744.00 | 0.214456E+11 | 0.241569E+09 | 0.00 | 1.00 | 01-AUG-14:00 | 0.32 | 31-AUG-24:00 | 8615.95 | 07-AUG-18:30 | 8588.97 | 30-AUG-17:50 | 430.30 | 23-AUG-14:00 | 2974.03 | 01-AUG-16:00 | 0.00 |
September | 0.617214E+10 | 0.167048E+10 | 720.00 | 0.601907E+10 | 0.153071E+09 | 0.00 | 0.49 | 30-SEP-24:00 | 0.23 | 09-SEP-06:05 | 4169.71 | 30-SEP-24:00 | 4140.39 | 30-SEP-24:00 | 313.71 | 05-SEP-14:40 | 1056.27 | 02-SEP-17:31 | 0.00 |
October | 0.110074E+11 | 0.267724E+10 | 744.00 | 0.109490E+11 | 58404930.84 | 0.00 | 0.69 | 31-OCT-24:00 | 0.39 | 26-OCT-06:55 | 5935.47 | 31-OCT-24:00 | 5935.47 | 31-OCT-24:00 | 278.36 | 02-OCT-17:00 | 1514.98 | 01-OCT-16:02 | 0.00 |
November | 0.151238E+11 | 0.342272E+10 | 720.00 | 0.151126E+11 | 11135095.30 | 0.00 | 0.80 | 19-NOV-16:35 | 0.62 | 10-NOV-08:00 | 6767.95 | 05-NOV-16:40 | 6767.95 | 05-NOV-16:40 | 140.33 | 09-NOV-16:00 | 1545.76 | 19-NOV-16:35 | 0.00 |
December | 0.203470E+11 | 0.454654E+10 | 744.00 | 0.203468E+11 | 110100.56 | 0.00 | 0.99 | 17-DEC-16:23 | 0.80 | 09-DEC-07:40 | 8572.49 | 31-DEC-16:35 | 8572.49 | 31-DEC-16:35 | 24.51 | 27-DEC-17:03 | 1917.23 | 17-DEC-16:23 | 0.00 |
Annual Sum or Average | 0.157989E+12 | 0.396015E+11 | 8760.00 | 0.157155E+12 | 0.834243E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.456303E+10 | 0.116780E+10 | 672.00 | 0.456247E+10 | 110100.56 | 0.00 | 0.34 | 0.12 | 2759.23 | 2752.50 | 24.51 | 653.52 | 0.00 | ||||||
Maximum of Months | 0.216872E+11 | 0.591511E+10 | 744.00 | 0.214456E+11 | 0.241569E+09 | 0.00 | 1.00 | 0.80 | 8909.61 | 8909.61 | 450.48 | 2974.03 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.261244E+11 | 0.697287E+10 | 744.00 | 0.261184E+11 | 5934940.86 | 0.00 | 0.32 | 26-JAN-17:00 | 0.01 | 17-JAN-07:10 | 23273.69 | 26-JAN-17:00 | 23273.69 | 26-JAN-17:00 | 261.58 | 20-JAN-17:00 | 5848.04 | 26-JAN-17:00 | 0.00 |
February | 0.735495E+11 | 0.178761E+11 | 672.00 | 0.735204E+11 | 29093920.05 | 0.00 | 0.57 | 14-FEB-17:00 | 0.26 | 06-FEB-07:10 | 44252.51 | 15-FEB-17:00 | 44252.51 | 15-FEB-17:00 | 767.62 | 17-FEB-11:20 | 11659.56 | 14-FEB-17:00 | 0.00 |
March | 0.139600E+12 | 0.322423E+11 | 744.00 | 0.139549E+12 | 50430409.97 | 0.00 | 0.85 | 31-MAR-23:40 | 0.54 | 04-MAR-07:05 | 71572.41 | 31-MAR-23:40 | 71572.41 | 31-MAR-23:40 | 908.58 | 20-MAR-14:40 | 16541.70 | 12-MAR-17:01 | 0.00 |
April | 0.190549E+12 | 0.444989E+11 | 720.00 | 0.190541E+12 | 7784307.71 | 0.00 | 1.00 | 01-APR-17:00 | 0.30 | 30-APR-23:57 | 83832.37 | 16-APR-17:42 | 83832.37 | 16-APR-17:42 | 663.60 | 15-APR-08:00 | 23736.48 | 13-APR-17:00 | 0.00 |
May | 0.539837E+11 | 0.146949E+11 | 744.00 | 0.535888E+11 | 0.394905E+09 | 0.00 | 0.50 | 31-MAY-23:40 | 0.16 | 05-MAY-06:25 | 39202.24 | 31-MAY-24:00 | 39202.24 | 31-MAY-24:00 | 2617.17 | 24-MAY-15:30 | 9827.24 | 31-MAY-23:20 | 0.00 |
June | 0.104467E+12 | 0.300236E+11 | 720.00 | 0.103517E+12 | 0.949856E+09 | 0.00 | 0.71 | 30-JUN-23:23 | 0.40 | 09-JUN-06:10 | 58068.54 | 30-JUN-24:00 | 57742.12 | 30-JUN-24:00 | 3119.61 | 30-JUN-14:00 | 19199.40 | 28-JUN-16:00 | 0.00 |
July | 0.159193E+12 | 0.463411E+11 | 744.00 | 0.156954E+12 | 0.223847E+10 | 0.00 | 0.90 | 04-JUL-18:21 | 0.66 | 08-JUL-06:10 | 76039.90 | 31-JUL-23:53 | 75951.61 | 31-JUL-23:53 | 4407.39 | 07-JUL-17:00 | 25008.03 | 21-JUL-18:10 | 0.00 |
August | 0.206914E+12 | 0.564441E+11 | 744.00 | 0.204503E+12 | 0.241158E+10 | 0.00 | 1.00 | 01-AUG-13:50 | 0.30 | 31-AUG-24:00 | 82348.09 | 11-AUG-18:10 | 82047.20 | 30-AUG-17:50 | 4275.13 | 23-AUG-14:00 | 28419.67 | 01-AUG-16:00 | 0.00 |
September | 0.559572E+11 | 0.152364E+11 | 720.00 | 0.544590E+11 | 0.149821E+10 | 0.00 | 0.48 | 30-SEP-24:00 | 0.20 | 09-SEP-06:25 | 39411.62 | 30-SEP-24:00 | 39125.62 | 30-SEP-24:00 | 3116.83 | 05-SEP-14:40 | 10002.23 | 02-SEP-17:31 | 0.00 |
October | 0.980070E+11 | 0.240353E+11 | 744.00 | 0.974304E+11 | 0.576583E+09 | 0.00 | 0.67 | 31-OCT-24:00 | 0.32 | 26-OCT-06:55 | 54210.36 | 31-OCT-24:00 | 54210.36 | 31-OCT-24:00 | 2743.40 | 02-OCT-17:00 | 14204.51 | 01-OCT-16:02 | 0.00 |
November | 0.131243E+12 | 0.300357E+11 | 720.00 | 0.131132E+12 | 0.111208E+09 | 0.00 | 0.74 | 19-NOV-16:42 | 0.52 | 27-NOV-07:05 | 62203.90 | 02-NOV-16:40 | 61336.04 | 02-NOV-16:40 | 1364.19 | 09-NOV-16:00 | 13659.87 | 19-NOV-16:42 | 0.00 |
December | 0.174064E+12 | 0.394831E+11 | 744.00 | 0.174063E+12 | 1384061.39 | 0.00 | 0.91 | 17-DEC-16:45 | 0.70 | 27-DEC-07:10 | 76426.03 | 29-DEC-16:40 | 76426.03 | 29-DEC-16:40 | 246.86 | 27-DEC-17:03 | 16793.19 | 17-DEC-16:45 | 0.00 |
Annual Sum or Average | 0.141365E+13 | 0.357884E+12 | 8760.00 | 0.140538E+13 | 0.827545E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.261244E+11 | 0.697287E+10 | 672.00 | 0.261184E+11 | 1384061.39 | 0.00 | 0.32 | 0.01 | 23273.69 | 23273.69 | 246.86 | 5848.04 | 0.00 | ||||||
Maximum of Months | 0.206914E+12 | 0.564441E+11 | 744.00 | 0.204503E+12 | 0.241158E+10 | 0.00 | 1.00 | 0.70 | 83832.37 | 83832.37 | 4407.39 | 28419.67 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.972830E+09 | 0.271395E+09 | 442.86 | 0.972378E+09 | 451745.82 | 0.00 | 0.29 | 26-JAN-17:00 | 0.00 | 01-JAN-00:05 | 2185.67 | 26-JAN-17:00 | 2185.67 | 26-JAN-17:00 | 28.50 | 01-JAN-16:35 | 553.23 | 26-JAN-17:00 | 0.00 |
February | 0.581139E+10 | 0.143935E+10 | 671.92 | 0.580862E+10 | 2773848.81 | 0.00 | 0.55 | 14-FEB-17:00 | 0.00 | 06-FEB-00:25 | 4435.15 | 15-FEB-17:00 | 4435.15 | 15-FEB-17:00 | 73.17 | 17-FEB-11:30 | 1166.95 | 14-FEB-17:00 | 0.00 |
March | 0.128712E+11 | 0.300593E+10 | 744.00 | 0.128663E+11 | 4908821.69 | 0.00 | 0.80 | 31-MAR-23:20 | 0.43 | 04-MAR-07:05 | 6800.83 | 31-MAR-23:20 | 6800.83 | 31-MAR-23:20 | 88.15 | 20-MAR-14:40 | 1624.48 | 08-MAR-17:00 | 0.00 |
April | 0.186146E+11 | 0.437859E+10 | 720.00 | 0.186138E+11 | 746023.80 | 0.00 | 1.00 | 01-APR-17:01 | 0.28 | 30-APR-23:53 | 8389.69 | 16-APR-17:42 | 8389.69 | 16-APR-17:42 | 64.03 | 15-APR-08:00 | 2410.98 | 13-APR-17:00 | 0.00 |
May | 0.522189E+10 | 0.143466E+10 | 744.00 | 0.518263E+10 | 39257141.68 | 0.00 | 0.49 | 31-MAY-23:30 | 0.08 | 05-MAY-06:05 | 3888.40 | 31-MAY-24:00 | 3888.40 | 31-MAY-24:00 | 259.97 | 24-MAY-15:30 | 1012.36 | 20-MAY-18:00 | 0.00 |
June | 0.104985E+11 | 0.303123E+10 | 720.00 | 0.104036E+11 | 94877297.30 | 0.00 | 0.71 | 18-JUN-18:11 | 0.34 | 09-JUN-06:20 | 5834.46 | 30-JUN-24:00 | 5801.55 | 30-JUN-24:00 | 315.28 | 30-JUN-14:00 | 1975.49 | 28-JUN-16:00 | 0.00 |
July | 0.160792E+11 | 0.469293E+10 | 744.00 | 0.158554E+11 | 0.223809E+09 | 0.00 | 0.92 | 04-JUL-18:11 | 0.63 | 08-JUL-06:10 | 7607.93 | 31-JUL-23:53 | 7599.02 | 31-JUL-23:53 | 443.46 | 07-JUL-17:00 | 2587.65 | 04-JUL-18:01 | 0.00 |
August | 0.208082E+11 | 0.569450E+10 | 744.00 | 0.205672E+11 | 0.240998E+09 | 0.00 | 1.00 | 01-AUG-14:20 | 0.29 | 31-AUG-24:00 | 8387.94 | 13-AUG-19:23 | 8387.94 | 13-AUG-19:23 | 427.92 | 23-AUG-14:00 | 2904.25 | 01-AUG-16:00 | 0.00 |
September | 0.552014E+10 | 0.151389E+10 | 720.00 | 0.537036E+10 | 0.149774E+09 | 0.00 | 0.47 | 30-SEP-23:30 | 0.15 | 09-SEP-06:45 | 3934.03 | 30-SEP-23:40 | 3904.41 | 30-SEP-24:00 | 313.65 | 05-SEP-14:30 | 1054.60 | 02-SEP-17:31 | 0.00 |
October | 0.909302E+10 | 0.225405E+10 | 744.00 | 0.903562E+10 | 57400682.04 | 0.00 | 0.63 | 31-OCT-23:40 | 0.20 | 26-OCT-06:10 | 5178.91 | 31-OCT-23:40 | 5178.91 | 31-OCT-23:40 | 275.07 | 02-OCT-17:00 | 1469.25 | 01-OCT-16:02 | 0.00 |
November | 0.115553E+11 | 0.268466E+10 | 720.00 | 0.115443E+11 | 11003893.93 | 0.00 | 0.72 | 03-NOV-16:40 | 0.38 | 27-NOV-07:05 | 6205.29 | 02-NOV-16:40 | 6118.16 | 02-NOV-16:40 | 135.27 | 09-NOV-16:00 | 1354.38 | 03-NOV-16:40 | 0.00 |
December | 0.153835E+11 | 0.354988E+10 | 744.00 | 0.153834E+11 | 120520.97 | 0.00 | 0.87 | 13-DEC-16:40 | 0.54 | 26-DEC-04:03 | 7510.68 | 29-DEC-16:50 | 7510.68 | 29-DEC-16:50 | 24.28 | 27-DEC-17:03 | 1636.74 | 13-DEC-16:40 | 0.00 |
Annual Sum or Average | 0.132430E+12 | 0.339511E+11 | 8458.78 | 0.131604E+12 | 0.826120E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.972830E+09 | 0.271395E+09 | 442.86 | 0.972378E+09 | 120520.97 | 0.00 | 0.29 | 0.00 | 2185.67 | 2185.67 | 24.28 | 553.23 | 0.00 | ||||||
Maximum of Months | 0.208082E+11 | 0.569450E+10 | 744.00 | 0.205672E+11 | 0.240998E+09 | 0.00 | 1.00 | 0.63 | 8389.69 | 8389.69 | 443.46 | 2904.25 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.17 | 0.00 | 120.17 | 19.55 | 494.31 | 0.00 | 0.00 | 0.00 |
February | 150.20 | 0.00 | 150.20 | 47.00 | 447.78 | 0.00 | 0.00 | 0.00 |
March | 189.46 | 0.00 | 189.46 | 111.46 | 352.20 | 0.00 | 0.00 | 0.00 |
April | 240.36 | 2.06 | 238.30 | 189.78 | 231.96 | 0.00 | 0.00 | 0.00 |
May | 261.27 | 16.85 | 244.43 | 270.75 | 163.88 | 0.00 | 0.00 | 0.00 |
June | 296.88 | 48.58 | 248.29 | 421.42 | 106.93 | 0.00 | 0.00 | 0.00 |
July | 272.49 | 22.68 | 249.81 | 418.83 | 71.27 | 0.00 | 0.00 | 0.00 |
August | 252.78 | 5.66 | 247.12 | 353.94 | 81.52 | 0.00 | 0.00 | 0.00 |
September | 202.14 | 0.05 | 202.09 | 240.11 | 148.71 | 0.00 | 0.00 | 0.00 |
October | 150.84 | 0.00 | 150.84 | 105.20 | 273.31 | 0.00 | 0.00 | 0.00 |
November | 128.10 | 0.00 | 128.10 | 30.79 | 402.96 | 0.00 | 0.00 | 0.00 |
December | 102.29 | 0.00 | 102.29 | 4.08 | 534.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.42 | 8.00 | 189.42 | 185.14 | 274.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.29 | 0.00 | 102.29 | 4.08 | 71.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 296.88 | 48.58 | 249.81 | 421.42 | 534.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.17 | 0.00 | 120.17 | 19.55 | 494.31 | 0.00 | 0.00 | 0.00 |
February | 150.20 | 0.00 | 150.20 | 47.00 | 447.78 | 0.00 | 0.00 | 0.00 |
March | 189.45 | 0.00 | 189.45 | 111.46 | 352.20 | 0.00 | 0.00 | 0.00 |
April | 240.36 | 2.06 | 238.30 | 189.78 | 231.96 | 0.00 | 0.00 | 0.00 |
May | 261.27 | 16.84 | 244.43 | 270.74 | 163.88 | 0.00 | 0.00 | 0.00 |
June | 296.87 | 48.58 | 248.29 | 421.41 | 106.93 | 0.00 | 0.00 | 0.00 |
July | 272.48 | 22.68 | 249.81 | 418.83 | 71.27 | 0.00 | 0.00 | 0.00 |
August | 252.77 | 5.66 | 247.12 | 353.94 | 81.51 | 0.00 | 0.00 | 0.00 |
September | 202.14 | 0.05 | 202.09 | 240.11 | 148.71 | 0.00 | 0.00 | 0.00 |
October | 150.84 | 0.00 | 150.84 | 105.20 | 273.31 | 0.00 | 0.00 | 0.00 |
November | 128.10 | 0.00 | 128.10 | 30.79 | 402.96 | 0.00 | 0.00 | 0.00 |
December | 102.29 | 0.00 | 102.29 | 4.08 | 534.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.42 | 8.00 | 189.41 | 185.14 | 274.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.29 | 0.00 | 102.29 | 4.08 | 71.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 296.87 | 48.58 | 249.81 | 421.41 | 534.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.17 | 0.00 | 120.17 | 19.55 | 494.31 | 0.00 | 0.00 | 0.00 |
February | 150.20 | 0.00 | 150.20 | 47.00 | 447.78 | 0.00 | 0.00 | 0.00 |
March | 189.45 | 0.00 | 189.45 | 111.46 | 352.20 | 0.00 | 0.00 | 0.00 |
April | 240.36 | 2.06 | 238.30 | 189.78 | 231.96 | 0.00 | 0.00 | 0.00 |
May | 261.27 | 16.84 | 244.43 | 270.74 | 163.88 | 0.00 | 0.00 | 0.00 |
June | 296.87 | 48.58 | 248.29 | 421.42 | 106.93 | 0.00 | 0.00 | 0.00 |
July | 272.48 | 22.68 | 249.81 | 418.83 | 71.27 | 0.00 | 0.00 | 0.00 |
August | 252.78 | 5.66 | 247.12 | 353.94 | 81.51 | 0.00 | 0.00 | 0.00 |
September | 202.14 | 0.05 | 202.09 | 240.11 | 148.71 | 0.00 | 0.00 | 0.00 |
October | 150.84 | 0.00 | 150.84 | 105.20 | 273.31 | 0.00 | 0.00 | 0.00 |
November | 128.10 | 0.00 | 128.10 | 30.79 | 402.96 | 0.00 | 0.00 | 0.00 |
December | 102.29 | 0.00 | 102.29 | 4.08 | 534.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.42 | 8.00 | 189.41 | 185.14 | 274.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.29 | 0.00 | 102.29 | 4.08 | 71.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 296.87 | 48.58 | 249.81 | 421.42 | 534.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.17 | 0.00 | 120.17 | 19.55 | 494.31 | 0.00 | 0.00 | 0.00 |
February | 150.20 | 0.00 | 150.20 | 47.00 | 447.78 | 0.00 | 0.00 | 0.00 |
March | 189.45 | 0.00 | 189.45 | 111.46 | 352.20 | 0.00 | 0.00 | 0.00 |
April | 240.36 | 2.06 | 238.30 | 189.78 | 231.96 | 0.00 | 0.00 | 0.00 |
May | 261.27 | 16.84 | 244.43 | 270.74 | 163.88 | 0.00 | 0.00 | 0.00 |
June | 296.87 | 48.58 | 248.29 | 421.41 | 106.93 | 0.00 | 0.00 | 0.00 |
July | 272.48 | 22.68 | 249.81 | 418.83 | 71.27 | 0.00 | 0.00 | 0.00 |
August | 252.77 | 5.66 | 247.12 | 353.94 | 81.51 | 0.00 | 0.00 | 0.00 |
September | 202.14 | 0.05 | 202.09 | 240.11 | 148.71 | 0.00 | 0.00 | 0.00 |
October | 150.84 | 0.00 | 150.84 | 105.20 | 273.31 | 0.00 | 0.00 | 0.00 |
November | 128.10 | 0.00 | 128.10 | 30.79 | 402.96 | 0.00 | 0.00 | 0.00 |
December | 102.29 | 0.00 | 102.29 | 4.08 | 534.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.42 | 8.00 | 189.41 | 185.14 | 274.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.29 | 0.00 | 102.29 | 4.08 | 71.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 296.87 | 48.58 | 249.81 | 421.41 | 534.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.17 | 0.00 | 120.17 | 19.55 | 494.29 | 0.00 | 0.00 | 0.00 |
February | 150.19 | 0.00 | 150.19 | 47.00 | 447.76 | 0.00 | 0.00 | 0.00 |
March | 189.45 | 0.00 | 189.45 | 111.46 | 352.18 | 0.00 | 0.00 | 0.00 |
April | 240.35 | 2.06 | 238.29 | 189.77 | 231.95 | 0.00 | 0.00 | 0.00 |
May | 261.26 | 16.84 | 244.42 | 270.73 | 163.88 | 0.00 | 0.00 | 0.00 |
June | 296.86 | 48.58 | 248.28 | 421.40 | 106.93 | 0.00 | 0.00 | 0.00 |
July | 272.47 | 22.68 | 249.80 | 418.81 | 71.27 | 0.00 | 0.00 | 0.00 |
August | 252.76 | 5.66 | 247.11 | 353.93 | 81.51 | 0.00 | 0.00 | 0.00 |
September | 202.13 | 0.05 | 202.08 | 240.10 | 148.71 | 0.00 | 0.00 | 0.00 |
October | 150.83 | 0.00 | 150.83 | 105.20 | 273.30 | 0.00 | 0.00 | 0.00 |
November | 128.09 | 0.00 | 128.09 | 30.79 | 402.94 | 0.00 | 0.00 | 0.00 |
December | 102.28 | 0.00 | 102.28 | 4.08 | 534.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.41 | 8.00 | 189.41 | 185.14 | 274.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.28 | 0.00 | 102.28 | 4.08 | 71.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 296.86 | 48.58 | 249.80 | 421.40 | 534.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 369.79 | 206.75 | 163.04 | 310.51 | 498.03 | 0.00 | 0.00 | 0.00 |
February | 449.29 | 242.22 | 207.07 | 418.39 | 454.01 | 0.00 | 0.00 | 0.00 |
March | 592.68 | 336.93 | 255.75 | 633.93 | 357.29 | 0.00 | 0.00 | 0.00 |
April | 809.73 | 461.30 | 348.43 | 962.71 | 242.17 | 0.00 | 0.00 | 0.00 |
May | 772.65 | 440.33 | 332.32 | 974.71 | 184.66 | 0.00 | 0.00 | 0.00 |
June | 832.98 | 513.15 | 319.82 | 1160.90 | 115.23 | 0.00 | 0.00 | 0.00 |
July | 770.77 | 440.76 | 330.01 | 1121.92 | 74.74 | 0.00 | 0.00 | 0.00 |
August | 762.73 | 420.51 | 342.22 | 1076.71 | 84.47 | 0.00 | 0.00 | 0.00 |
September | 634.84 | 355.20 | 279.64 | 843.79 | 157.47 | 0.00 | 0.00 | 0.00 |
October | 552.12 | 350.30 | 201.82 | 640.25 | 277.96 | 0.00 | 0.00 | 0.00 |
November | 431.51 | 253.68 | 177.83 | 414.75 | 406.86 | 0.00 | 0.00 | 0.00 |
December | 349.64 | 212.79 | 136.85 | 297.54 | 530.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 611.32 | 353.26 | 258.06 | 739.46 | 281.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 349.64 | 206.75 | 136.85 | 297.54 | 74.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 832.98 | 513.15 | 348.43 | 1160.90 | 530.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 369.79 | 206.75 | 163.04 | 310.51 | 498.03 | 0.00 | 0.00 | 0.00 |
February | 449.29 | 242.22 | 207.07 | 418.39 | 454.01 | 0.00 | 0.00 | 0.00 |
March | 592.68 | 336.93 | 255.75 | 633.93 | 357.29 | 0.00 | 0.00 | 0.00 |
April | 809.73 | 461.30 | 348.43 | 962.71 | 242.17 | 0.00 | 0.00 | 0.00 |
May | 772.65 | 440.33 | 332.32 | 974.71 | 184.66 | 0.00 | 0.00 | 0.00 |
June | 832.98 | 513.15 | 319.82 | 1160.90 | 115.23 | 0.00 | 0.00 | 0.00 |
July | 770.77 | 440.76 | 330.01 | 1121.92 | 74.74 | 0.00 | 0.00 | 0.00 |
August | 762.73 | 420.51 | 342.22 | 1076.71 | 84.47 | 0.00 | 0.00 | 0.00 |
September | 634.84 | 355.20 | 279.64 | 843.79 | 157.47 | 0.00 | 0.00 | 0.00 |
October | 552.12 | 350.30 | 201.82 | 640.25 | 277.96 | 0.00 | 0.00 | 0.00 |
November | 431.51 | 253.68 | 177.83 | 414.75 | 406.86 | 0.00 | 0.00 | 0.00 |
December | 349.64 | 212.79 | 136.85 | 297.54 | 530.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 611.32 | 353.26 | 258.06 | 739.46 | 281.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 349.64 | 206.75 | 136.85 | 297.54 | 74.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 832.98 | 513.15 | 348.43 | 1160.90 | 530.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 369.79 | 206.75 | 163.04 | 310.50 | 498.02 | 0.00 | 0.00 | 0.00 |
February | 449.28 | 242.21 | 207.07 | 418.38 | 454.01 | 0.00 | 0.00 | 0.00 |
March | 592.67 | 336.92 | 255.75 | 633.92 | 357.28 | 0.00 | 0.00 | 0.00 |
April | 809.71 | 461.29 | 348.42 | 962.70 | 242.16 | 0.00 | 0.00 | 0.00 |
May | 772.64 | 440.32 | 332.32 | 974.69 | 184.66 | 0.00 | 0.00 | 0.00 |
June | 832.96 | 513.14 | 319.82 | 1160.88 | 115.23 | 0.00 | 0.00 | 0.00 |
July | 770.75 | 440.75 | 330.01 | 1121.90 | 74.74 | 0.00 | 0.00 | 0.00 |
August | 762.71 | 420.50 | 342.21 | 1076.69 | 84.47 | 0.00 | 0.00 | 0.00 |
September | 634.83 | 355.19 | 279.64 | 843.78 | 157.46 | 0.00 | 0.00 | 0.00 |
October | 552.11 | 350.29 | 201.82 | 640.24 | 277.95 | 0.00 | 0.00 | 0.00 |
November | 431.50 | 253.68 | 177.82 | 414.75 | 406.86 | 0.00 | 0.00 | 0.00 |
December | 349.64 | 212.79 | 136.85 | 297.53 | 530.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 611.31 | 353.26 | 258.06 | 739.45 | 281.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 349.64 | 206.75 | 136.85 | 297.53 | 74.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 832.96 | 513.14 | 348.42 | 1160.88 | 530.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 888.44 | 691.32 | 197.11 | 1023.23 | 441.23 | 0.00 | 0.00 | 0.00 |
February | 869.46 | 635.11 | 234.35 | 1023.85 | 410.84 | 0.00 | 0.00 | 0.00 |
March | 640.70 | 387.34 | 253.36 | 770.80 | 337.09 | 0.00 | 0.00 | 0.00 |
April | 499.67 | 205.10 | 294.56 | 625.10 | 241.37 | 0.00 | 0.00 | 0.00 |
May | 333.24 | 73.31 | 259.93 | 420.88 | 174.85 | 0.00 | 0.00 | 0.00 |
June | 281.89 | 34.74 | 247.15 | 420.75 | 114.07 | 0.00 | 0.00 | 0.00 |
July | 311.93 | 49.81 | 262.12 | 504.28 | 75.17 | 0.00 | 0.00 | 0.00 |
August | 428.92 | 139.42 | 289.50 | 663.46 | 88.26 | 0.00 | 0.00 | 0.00 |
September | 593.10 | 330.73 | 262.37 | 850.75 | 154.70 | 0.00 | 0.00 | 0.00 |
October | 811.43 | 597.62 | 213.82 | 1045.51 | 260.13 | 0.00 | 0.00 | 0.00 |
November | 903.78 | 693.65 | 210.13 | 1073.71 | 363.81 | 0.00 | 0.00 | 0.00 |
December | 963.93 | 795.14 | 168.79 | 1117.49 | 460.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 625.85 | 384.83 | 241.02 | 793.68 | 259.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 281.89 | 34.74 | 168.79 | 420.75 | 75.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 963.93 | 795.14 | 294.56 | 1117.49 | 460.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 888.43 | 691.32 | 197.11 | 1023.23 | 441.23 | 0.00 | 0.00 | 0.00 |
February | 869.45 | 635.10 | 234.35 | 1023.84 | 410.84 | 0.00 | 0.00 | 0.00 |
March | 640.70 | 387.34 | 253.36 | 770.80 | 337.09 | 0.00 | 0.00 | 0.00 |
April | 499.66 | 205.10 | 294.56 | 625.10 | 241.37 | 0.00 | 0.00 | 0.00 |
May | 333.24 | 73.30 | 259.93 | 420.87 | 174.85 | 0.00 | 0.00 | 0.00 |
June | 281.89 | 34.74 | 247.15 | 420.75 | 114.07 | 0.00 | 0.00 | 0.00 |
July | 311.93 | 49.81 | 262.11 | 504.27 | 75.17 | 0.00 | 0.00 | 0.00 |
August | 428.92 | 139.42 | 289.50 | 663.46 | 88.26 | 0.00 | 0.00 | 0.00 |
September | 593.10 | 330.73 | 262.37 | 850.74 | 154.70 | 0.00 | 0.00 | 0.00 |
October | 811.43 | 597.61 | 213.82 | 1045.50 | 260.13 | 0.00 | 0.00 | 0.00 |
November | 903.78 | 693.64 | 210.13 | 1073.71 | 363.81 | 0.00 | 0.00 | 0.00 |
December | 963.92 | 795.13 | 168.79 | 1117.48 | 460.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 625.84 | 384.83 | 241.02 | 793.67 | 259.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 281.89 | 34.74 | 168.79 | 420.75 | 75.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 963.92 | 795.13 | 294.56 | 1117.48 | 460.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 888.44 | 691.32 | 197.11 | 1023.23 | 441.23 | 0.00 | 0.00 | 0.00 |
February | 869.46 | 635.11 | 234.35 | 1023.85 | 410.84 | 0.00 | 0.00 | 0.00 |
March | 640.70 | 387.34 | 253.36 | 770.80 | 337.09 | 0.00 | 0.00 | 0.00 |
April | 499.67 | 205.10 | 294.56 | 625.10 | 241.37 | 0.00 | 0.00 | 0.00 |
May | 333.24 | 73.31 | 259.93 | 420.88 | 174.85 | 0.00 | 0.00 | 0.00 |
June | 281.89 | 34.74 | 247.15 | 420.75 | 114.07 | 0.00 | 0.00 | 0.00 |
July | 311.93 | 49.81 | 262.12 | 504.28 | 75.17 | 0.00 | 0.00 | 0.00 |
August | 428.92 | 139.42 | 289.50 | 663.46 | 88.26 | 0.00 | 0.00 | 0.00 |
September | 593.10 | 330.73 | 262.37 | 850.75 | 154.70 | 0.00 | 0.00 | 0.00 |
October | 811.43 | 597.62 | 213.82 | 1045.51 | 260.13 | 0.00 | 0.00 | 0.00 |
November | 903.78 | 693.65 | 210.13 | 1073.71 | 363.81 | 0.00 | 0.00 | 0.00 |
December | 963.93 | 795.14 | 168.79 | 1117.49 | 460.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 625.85 | 384.83 | 241.02 | 793.68 | 259.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 281.89 | 34.74 | 168.79 | 420.75 | 75.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 963.93 | 795.14 | 294.56 | 1117.49 | 460.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 888.43 | 691.32 | 197.11 | 1023.23 | 441.23 | 0.00 | 0.00 | 0.00 |
February | 869.45 | 635.10 | 234.35 | 1023.84 | 410.84 | 0.00 | 0.00 | 0.00 |
March | 640.70 | 387.34 | 253.36 | 770.80 | 337.09 | 0.00 | 0.00 | 0.00 |
April | 499.66 | 205.10 | 294.56 | 625.10 | 241.37 | 0.00 | 0.00 | 0.00 |
May | 333.24 | 73.30 | 259.93 | 420.87 | 174.85 | 0.00 | 0.00 | 0.00 |
June | 281.89 | 34.74 | 247.15 | 420.75 | 114.07 | 0.00 | 0.00 | 0.00 |
July | 311.93 | 49.81 | 262.11 | 504.27 | 75.17 | 0.00 | 0.00 | 0.00 |
August | 428.92 | 139.42 | 289.50 | 663.46 | 88.26 | 0.00 | 0.00 | 0.00 |
September | 593.10 | 330.73 | 262.37 | 850.74 | 154.70 | 0.00 | 0.00 | 0.00 |
October | 811.43 | 597.61 | 213.82 | 1045.50 | 260.13 | 0.00 | 0.00 | 0.00 |
November | 903.78 | 693.64 | 210.13 | 1073.71 | 363.81 | 0.00 | 0.00 | 0.00 |
December | 963.92 | 795.13 | 168.79 | 1117.48 | 460.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 625.84 | 384.83 | 241.02 | 793.67 | 259.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 281.89 | 34.74 | 168.79 | 420.75 | 75.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 963.92 | 795.13 | 294.56 | 1117.48 | 460.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 888.40 | 691.29 | 197.10 | 1023.19 | 441.21 | 0.00 | 0.00 | 0.00 |
February | 869.42 | 635.08 | 234.34 | 1023.80 | 410.83 | 0.00 | 0.00 | 0.00 |
March | 640.67 | 387.32 | 253.35 | 770.77 | 337.07 | 0.00 | 0.00 | 0.00 |
April | 499.64 | 205.09 | 294.55 | 625.08 | 241.36 | 0.00 | 0.00 | 0.00 |
May | 333.22 | 73.30 | 259.92 | 420.86 | 174.84 | 0.00 | 0.00 | 0.00 |
June | 281.88 | 34.74 | 247.14 | 420.73 | 114.06 | 0.00 | 0.00 | 0.00 |
July | 311.91 | 49.81 | 262.10 | 504.26 | 75.17 | 0.00 | 0.00 | 0.00 |
August | 428.90 | 139.41 | 289.49 | 663.43 | 88.26 | 0.00 | 0.00 | 0.00 |
September | 593.08 | 330.72 | 262.36 | 850.71 | 154.70 | 0.00 | 0.00 | 0.00 |
October | 811.40 | 597.59 | 213.81 | 1045.46 | 260.12 | 0.00 | 0.00 | 0.00 |
November | 903.74 | 693.62 | 210.12 | 1073.67 | 363.79 | 0.00 | 0.00 | 0.00 |
December | 963.88 | 795.10 | 168.78 | 1117.44 | 460.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 625.82 | 384.81 | 241.01 | 793.64 | 259.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 281.88 | 34.74 | 168.78 | 420.73 | 75.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 963.88 | 795.10 | 294.55 | 1117.44 | 460.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 381.43 | 217.52 | 163.91 | 353.69 | 555.74 | 0.00 | 0.00 | 0.00 |
February | 491.02 | 283.65 | 207.37 | 489.38 | 520.14 | 0.00 | 0.00 | 0.00 |
March | 548.42 | 291.93 | 256.48 | 580.61 | 423.49 | 0.00 | 0.00 | 0.00 |
April | 699.95 | 372.52 | 327.43 | 805.68 | 298.25 | 0.00 | 0.00 | 0.00 |
May | 663.65 | 341.96 | 321.69 | 823.02 | 210.17 | 0.00 | 0.00 | 0.00 |
June | 711.43 | 396.97 | 314.46 | 992.04 | 148.17 | 0.00 | 0.00 | 0.00 |
July | 641.69 | 314.03 | 327.66 | 932.71 | 102.67 | 0.00 | 0.00 | 0.00 |
August | 655.69 | 303.29 | 352.41 | 919.53 | 120.18 | 0.00 | 0.00 | 0.00 |
September | 592.25 | 311.91 | 280.33 | 789.76 | 185.28 | 0.00 | 0.00 | 0.00 |
October | 541.82 | 336.76 | 205.06 | 638.09 | 330.03 | 0.00 | 0.00 | 0.00 |
November | 425.33 | 250.23 | 175.10 | 415.05 | 473.27 | 0.00 | 0.00 | 0.00 |
December | 367.82 | 230.66 | 137.16 | 329.71 | 620.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 560.09 | 304.14 | 255.95 | 673.09 | 331.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 367.82 | 217.52 | 137.16 | 329.71 | 102.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 711.43 | 396.97 | 352.41 | 992.04 | 620.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 381.43 | 217.52 | 163.91 | 353.69 | 555.74 | 0.00 | 0.00 | 0.00 |
February | 491.02 | 283.65 | 207.37 | 489.38 | 520.14 | 0.00 | 0.00 | 0.00 |
March | 548.42 | 291.93 | 256.48 | 580.61 | 423.49 | 0.00 | 0.00 | 0.00 |
April | 699.95 | 372.52 | 327.43 | 805.68 | 298.25 | 0.00 | 0.00 | 0.00 |
May | 663.65 | 341.96 | 321.69 | 823.02 | 210.17 | 0.00 | 0.00 | 0.00 |
June | 711.43 | 396.97 | 314.46 | 992.04 | 148.17 | 0.00 | 0.00 | 0.00 |
July | 641.69 | 314.03 | 327.66 | 932.71 | 102.67 | 0.00 | 0.00 | 0.00 |
August | 655.69 | 303.29 | 352.41 | 919.53 | 120.18 | 0.00 | 0.00 | 0.00 |
September | 592.25 | 311.91 | 280.33 | 789.76 | 185.28 | 0.00 | 0.00 | 0.00 |
October | 541.82 | 336.76 | 205.06 | 638.09 | 330.03 | 0.00 | 0.00 | 0.00 |
November | 425.33 | 250.23 | 175.10 | 415.05 | 473.27 | 0.00 | 0.00 | 0.00 |
December | 367.82 | 230.66 | 137.16 | 329.71 | 620.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 560.09 | 304.14 | 255.95 | 673.09 | 331.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 367.82 | 217.52 | 137.16 | 329.71 | 102.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 711.43 | 396.97 | 352.41 | 992.04 | 620.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 381.42 | 217.51 | 163.91 | 353.69 | 555.73 | 0.00 | 0.00 | 0.00 |
February | 491.02 | 283.65 | 207.37 | 489.37 | 520.13 | 0.00 | 0.00 | 0.00 |
March | 548.41 | 291.93 | 256.48 | 580.60 | 423.48 | 0.00 | 0.00 | 0.00 |
April | 699.93 | 372.51 | 327.43 | 805.67 | 298.25 | 0.00 | 0.00 | 0.00 |
May | 663.64 | 341.95 | 321.69 | 823.00 | 210.16 | 0.00 | 0.00 | 0.00 |
June | 711.42 | 396.96 | 314.45 | 992.03 | 148.17 | 0.00 | 0.00 | 0.00 |
July | 641.68 | 314.03 | 327.65 | 932.69 | 102.67 | 0.00 | 0.00 | 0.00 |
August | 655.68 | 303.28 | 352.40 | 919.52 | 120.18 | 0.00 | 0.00 | 0.00 |
September | 592.23 | 311.91 | 280.33 | 789.75 | 185.28 | 0.00 | 0.00 | 0.00 |
October | 541.81 | 336.76 | 205.06 | 638.08 | 330.02 | 0.00 | 0.00 | 0.00 |
November | 425.32 | 250.23 | 175.10 | 415.04 | 473.26 | 0.00 | 0.00 | 0.00 |
December | 367.82 | 230.66 | 137.16 | 329.70 | 620.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 560.08 | 304.14 | 255.95 | 673.07 | 331.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 367.82 | 217.51 | 137.16 | 329.70 | 102.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 711.42 | 396.96 | 352.40 | 992.03 | 620.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 600.87 | 0.00 | 600.87 | 145.88 | 2238.36 | 0.00 | 0.00 | 0.00 |
February | 750.99 | 0.00 | 750.99 | 297.00 | 2029.04 | 0.00 | 0.00 | 0.00 |
March | 947.28 | 0.00 | 947.28 | 616.25 | 1610.15 | 0.00 | 0.00 | 0.00 |
April | 1201.80 | 10.29 | 1191.51 | 989.26 | 1080.27 | 0.00 | 0.00 | 0.00 |
May | 1306.37 | 84.23 | 1222.14 | 1372.46 | 786.39 | 0.00 | 0.00 | 0.00 |
June | 1484.38 | 242.92 | 1241.47 | 2120.53 | 523.33 | 0.00 | 0.00 | 0.00 |
July | 1362.43 | 113.40 | 1249.04 | 2109.84 | 352.83 | 0.00 | 0.00 | 0.00 |
August | 1263.88 | 28.30 | 1235.59 | 1788.01 | 399.30 | 0.00 | 0.00 | 0.00 |
September | 1010.72 | 0.26 | 1010.46 | 1215.96 | 711.46 | 0.00 | 0.00 | 0.00 |
October | 754.20 | 0.00 | 754.20 | 564.56 | 1254.67 | 0.00 | 0.00 | 0.00 |
November | 640.49 | 0.00 | 640.49 | 205.14 | 1785.33 | 0.00 | 0.00 | 0.00 |
December | 511.43 | 0.00 | 511.43 | 48.30 | 2338.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 987.10 | 40.02 | 947.07 | 959.58 | 1255.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 511.43 | 0.00 | 511.43 | 48.30 | 352.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1484.38 | 242.92 | 1249.04 | 2120.53 | 2338.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1109.37 | 620.24 | 489.13 | 963.52 | 1385.62 | 0.00 | 0.00 | 0.00 |
February | 1347.86 | 726.64 | 621.22 | 1281.99 | 1271.61 | 0.00 | 0.00 | 0.00 |
March | 1778.03 | 1010.78 | 767.25 | 1909.23 | 1021.62 | 0.00 | 0.00 | 0.00 |
April | 2429.15 | 1383.87 | 1045.28 | 2875.79 | 716.86 | 0.00 | 0.00 | 0.00 |
May | 2317.93 | 1320.97 | 996.96 | 2909.38 | 545.00 | 0.00 | 0.00 | 0.00 |
June | 2498.90 | 1539.44 | 959.46 | 3466.74 | 350.86 | 0.00 | 0.00 | 0.00 |
July | 2312.28 | 1322.25 | 990.02 | 3349.02 | 242.22 | 0.00 | 0.00 | 0.00 |
August | 2288.15 | 1261.50 | 1026.65 | 3212.23 | 273.27 | 0.00 | 0.00 | 0.00 |
September | 1904.50 | 1065.59 | 838.92 | 2521.83 | 465.60 | 0.00 | 0.00 | 0.00 |
October | 1656.33 | 1050.88 | 605.45 | 1922.73 | 799.08 | 0.00 | 0.00 | 0.00 |
November | 1294.51 | 761.03 | 533.48 | 1262.83 | 1133.38 | 0.00 | 0.00 | 0.00 |
December | 1048.92 | 638.36 | 410.56 | 918.03 | 1455.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1833.95 | 1059.78 | 774.18 | 2220.33 | 802.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1048.92 | 620.24 | 410.56 | 918.03 | 242.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2498.90 | 1539.44 | 1045.28 | 3466.74 | 1455.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4442.26 | 3456.69 | 985.57 | 5092.03 | 2177.04 | 0.00 | 0.00 | 0.00 |
February | 4347.36 | 3175.60 | 1171.76 | 5094.19 | 2021.55 | 0.00 | 0.00 | 0.00 |
March | 3203.56 | 1936.75 | 1266.81 | 3838.55 | 1646.69 | 0.00 | 0.00 | 0.00 |
April | 2498.36 | 1025.53 | 1472.83 | 3117.23 | 1175.28 | 0.00 | 0.00 | 0.00 |
May | 1666.20 | 366.53 | 1299.67 | 2100.93 | 855.41 | 0.00 | 0.00 | 0.00 |
June | 1409.47 | 173.70 | 1235.77 | 2114.94 | 559.49 | 0.00 | 0.00 | 0.00 |
July | 1559.65 | 249.06 | 1310.59 | 2528.89 | 375.46 | 0.00 | 0.00 | 0.00 |
August | 2144.63 | 697.11 | 1447.52 | 3314.91 | 441.79 | 0.00 | 0.00 | 0.00 |
September | 2965.56 | 1653.69 | 1311.88 | 4229.44 | 768.11 | 0.00 | 0.00 | 0.00 |
October | 4057.25 | 2988.14 | 1069.11 | 5197.82 | 1286.90 | 0.00 | 0.00 | 0.00 |
November | 4519.00 | 3468.32 | 1050.68 | 5344.62 | 1782.80 | 0.00 | 0.00 | 0.00 |
December | 4819.72 | 3975.77 | 843.96 | 5574.13 | 2229.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3129.29 | 1924.18 | 1205.11 | 3955.86 | 1272.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1409.47 | 173.70 | 843.96 | 2100.93 | 375.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4819.72 | 3975.77 | 1472.83 | 5574.13 | 2229.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1144.27 | 652.54 | 491.73 | 1097.33 | 1515.74 | 0.00 | 0.00 | 0.00 |
February | 1473.06 | 850.94 | 622.12 | 1513.84 | 1396.50 | 0.00 | 0.00 | 0.00 |
March | 1645.24 | 875.79 | 769.45 | 1789.35 | 1124.93 | 0.00 | 0.00 | 0.00 |
April | 2099.82 | 1117.53 | 982.28 | 2456.12 | 798.87 | 0.00 | 0.00 | 0.00 |
May | 1990.93 | 1025.87 | 965.06 | 2478.65 | 594.23 | 0.00 | 0.00 | 0.00 |
June | 2134.28 | 1190.90 | 943.37 | 2994.06 | 414.84 | 0.00 | 0.00 | 0.00 |
July | 1925.05 | 942.09 | 982.96 | 2825.10 | 277.91 | 0.00 | 0.00 | 0.00 |
August | 1967.06 | 909.85 | 1057.21 | 2789.30 | 319.99 | 0.00 | 0.00 | 0.00 |
September | 1776.72 | 935.73 | 840.99 | 2378.19 | 521.85 | 0.00 | 0.00 | 0.00 |
October | 1625.46 | 1010.28 | 615.18 | 1942.70 | 892.16 | 0.00 | 0.00 | 0.00 |
November | 1275.98 | 750.69 | 525.29 | 1293.89 | 1223.04 | 0.00 | 0.00 | 0.00 |
December | 1103.46 | 691.99 | 411.47 | 1036.89 | 1562.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1680.26 | 912.42 | 767.84 | 2051.49 | 884.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1103.46 | 652.54 | 411.47 | 1036.89 | 277.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2134.28 | 1190.90 | 1057.21 | 2994.06 | 1562.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 600.87 | 0.00 | 600.87 | 179.75 | 2058.62 | 0.00 | 0.00 | 0.00 |
February | 750.99 | 0.00 | 750.99 | 335.93 | 1874.33 | 0.00 | 0.00 | 0.00 |
March | 947.28 | 0.00 | 947.28 | 658.14 | 1495.74 | 0.00 | 0.00 | 0.00 |
April | 1201.80 | 10.29 | 1191.51 | 1010.56 | 1025.44 | 0.00 | 0.00 | 0.00 |
May | 1306.37 | 84.23 | 1222.14 | 1376.27 | 766.80 | 0.00 | 0.00 | 0.00 |
June | 1484.38 | 242.92 | 1241.47 | 2106.30 | 524.33 | 0.00 | 0.00 | 0.00 |
July | 1362.43 | 113.40 | 1249.04 | 2086.93 | 362.90 | 0.00 | 0.00 | 0.00 |
August | 1263.88 | 28.30 | 1235.59 | 1769.37 | 405.90 | 0.00 | 0.00 | 0.00 |
September | 1010.72 | 0.26 | 1010.46 | 1212.41 | 697.84 | 0.00 | 0.00 | 0.00 |
October | 754.20 | 0.00 | 754.20 | 587.47 | 1170.07 | 0.00 | 0.00 | 0.00 |
November | 640.49 | 0.00 | 640.49 | 245.91 | 1614.56 | 0.00 | 0.00 | 0.00 |
December | 511.43 | 0.00 | 511.43 | 67.37 | 2145.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 987.10 | 40.02 | 947.07 | 973.00 | 1175.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 511.43 | 0.00 | 511.43 | 67.37 | 362.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1484.38 | 242.92 | 1249.04 | 2106.30 | 2145.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1109.37 | 620.24 | 489.13 | 1005.51 | 1280.66 | 0.00 | 0.00 | 0.00 |
February | 1347.86 | 726.64 | 621.22 | 1319.73 | 1181.16 | 0.00 | 0.00 | 0.00 |
March | 1778.03 | 1010.78 | 767.25 | 1933.64 | 962.46 | 0.00 | 0.00 | 0.00 |
April | 2429.15 | 1383.87 | 1045.28 | 2880.15 | 693.52 | 0.00 | 0.00 | 0.00 |
May | 2317.93 | 1320.97 | 996.96 | 2903.36 | 536.26 | 0.00 | 0.00 | 0.00 |
June | 2498.90 | 1539.44 | 959.46 | 3453.05 | 352.61 | 0.00 | 0.00 | 0.00 |
July | 2312.28 | 1322.25 | 990.02 | 3332.27 | 249.16 | 0.00 | 0.00 | 0.00 |
August | 2288.15 | 1261.50 | 1026.65 | 3197.46 | 278.80 | 0.00 | 0.00 | 0.00 |
September | 1904.50 | 1065.59 | 838.92 | 2515.60 | 461.39 | 0.00 | 0.00 | 0.00 |
October | 1656.33 | 1050.88 | 605.45 | 1935.29 | 759.40 | 0.00 | 0.00 | 0.00 |
November | 1294.51 | 761.03 | 533.48 | 1301.37 | 1037.71 | 0.00 | 0.00 | 0.00 |
December | 1048.92 | 638.36 | 410.56 | 949.66 | 1337.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1833.95 | 1059.78 | 774.18 | 2231.32 | 758.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1048.92 | 620.24 | 410.56 | 949.66 | 249.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2498.90 | 1539.44 | 1045.28 | 3453.05 | 1337.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4442.26 | 3456.69 | 985.57 | 5147.80 | 2018.87 | 0.00 | 0.00 | 0.00 |
February | 4347.36 | 3175.60 | 1171.76 | 5139.23 | 1881.57 | 0.00 | 0.00 | 0.00 |
March | 3203.56 | 1936.75 | 1266.81 | 3870.19 | 1551.24 | 0.00 | 0.00 | 0.00 |
April | 2498.36 | 1025.53 | 1472.83 | 3126.49 | 1125.07 | 0.00 | 0.00 | 0.00 |
May | 1666.20 | 366.53 | 1299.67 | 2099.69 | 832.22 | 0.00 | 0.00 | 0.00 |
June | 1409.47 | 173.70 | 1235.77 | 2101.50 | 556.28 | 0.00 | 0.00 | 0.00 |
July | 1559.65 | 249.06 | 1310.59 | 2507.35 | 383.76 | 0.00 | 0.00 | 0.00 |
August | 2144.63 | 697.11 | 1447.52 | 3294.87 | 447.80 | 0.00 | 0.00 | 0.00 |
September | 2965.56 | 1653.69 | 1311.88 | 4220.04 | 758.07 | 0.00 | 0.00 | 0.00 |
October | 4057.25 | 2988.14 | 1069.11 | 5215.31 | 1226.03 | 0.00 | 0.00 | 0.00 |
November | 4519.00 | 3468.32 | 1050.68 | 5394.16 | 1650.71 | 0.00 | 0.00 | 0.00 |
December | 4819.72 | 3975.77 | 843.96 | 5618.87 | 2058.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3129.29 | 1924.18 | 1205.11 | 3971.34 | 1203.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1409.47 | 173.70 | 843.96 | 2099.69 | 383.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4819.72 | 3975.77 | 1472.83 | 5618.87 | 2058.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1144.27 | 652.54 | 491.73 | 1118.14 | 1413.13 | 0.00 | 0.00 | 0.00 |
February | 1473.06 | 850.94 | 622.12 | 1533.03 | 1309.40 | 0.00 | 0.00 | 0.00 |
March | 1645.24 | 875.79 | 769.45 | 1807.29 | 1062.86 | 0.00 | 0.00 | 0.00 |
April | 2099.82 | 1117.53 | 982.28 | 2461.70 | 768.44 | 0.00 | 0.00 | 0.00 |
May | 1990.93 | 1025.87 | 965.06 | 2476.31 | 580.43 | 0.00 | 0.00 | 0.00 |
June | 2134.28 | 1190.90 | 943.37 | 2983.45 | 413.06 | 0.00 | 0.00 | 0.00 |
July | 1925.05 | 942.09 | 982.96 | 2810.27 | 282.00 | 0.00 | 0.00 | 0.00 |
August | 1967.06 | 909.85 | 1057.21 | 2776.33 | 323.04 | 0.00 | 0.00 | 0.00 |
September | 1776.72 | 935.73 | 840.99 | 2373.29 | 514.91 | 0.00 | 0.00 | 0.00 |
October | 1625.46 | 1010.28 | 615.18 | 1950.54 | 848.28 | 0.00 | 0.00 | 0.00 |
November | 1275.98 | 750.69 | 525.29 | 1315.75 | 1130.77 | 0.00 | 0.00 | 0.00 |
December | 1103.46 | 691.99 | 411.47 | 1051.01 | 1454.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1680.26 | 912.42 | 767.84 | 2056.54 | 839.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1103.46 | 652.54 | 411.47 | 1051.01 | 282.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2134.28 | 1190.90 | 1057.21 | 2983.45 | 1454.43 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321876E+09 | 0.00 | 0.321876E+09 | 52370366.11 | 0.132396E+10 |
February | 0.363359E+09 | 0.00 | 0.363359E+09 | 0.113709E+09 | 0.108326E+10 |
March | 0.507438E+09 | 0.00 | 0.507438E+09 | 0.298539E+09 | 0.943326E+09 |
April | 0.623014E+09 | 5333940.93 | 0.617681E+09 | 0.491915E+09 | 0.601230E+09 |
May | 0.699796E+09 | 45117755.73 | 0.654678E+09 | 0.725168E+09 | 0.438945E+09 |
June | 0.769506E+09 | 0.125927E+09 | 0.643579E+09 | 0.109232E+10 | 0.277164E+09 |
July | 0.729829E+09 | 60743208.74 | 0.669086E+09 | 0.112181E+10 | 0.190896E+09 |
August | 0.677038E+09 | 15157315.94 | 0.661881E+09 | 0.948002E+09 | 0.218331E+09 |
September | 0.523956E+09 | 134472.84 | 0.523822E+09 | 0.622377E+09 | 0.385461E+09 |
October | 0.404009E+09 | 0.00 | 0.404009E+09 | 0.281775E+09 | 0.732029E+09 |
November | 0.332032E+09 | 0.00 | 0.332032E+09 | 79814778.55 | 0.104446E+10 |
December | 0.273965E+09 | 0.00 | 0.273965E+09 | 10933763.68 | 0.143113E+10 |
Annual Sum or Average | 0.622582E+10 | 0.252414E+09 | 0.597340E+10 | 0.583873E+10 | 0.867020E+10 |
Minimum of Months | 0.273965E+09 | 0.00 | 0.273965E+09 | 10933763.68 | 0.190896E+09 |
Maximum of Months | 0.769506E+09 | 0.125927E+09 | 0.669086E+09 | 0.112181E+10 | 0.143113E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321871E+09 | 0.00 | 0.321871E+09 | 52367919.50 | 0.132396E+10 |
February | 0.363355E+09 | 0.00 | 0.363355E+09 | 0.113706E+09 | 0.108326E+10 |
March | 0.507432E+09 | 0.00 | 0.507432E+09 | 0.298533E+09 | 0.943325E+09 |
April | 0.623007E+09 | 5333823.67 | 0.617673E+09 | 0.491907E+09 | 0.601228E+09 |
May | 0.699787E+09 | 45116763.87 | 0.654671E+09 | 0.725157E+09 | 0.438943E+09 |
June | 0.769496E+09 | 0.125925E+09 | 0.643572E+09 | 0.109230E+10 | 0.277163E+09 |
July | 0.729820E+09 | 60741873.38 | 0.669078E+09 | 0.112180E+10 | 0.190894E+09 |
August | 0.677030E+09 | 15156982.73 | 0.661873E+09 | 0.947992E+09 | 0.218329E+09 |
September | 0.523950E+09 | 134469.88 | 0.523815E+09 | 0.622371E+09 | 0.385459E+09 |
October | 0.404004E+09 | 0.00 | 0.404004E+09 | 0.281772E+09 | 0.732027E+09 |
November | 0.332027E+09 | 0.00 | 0.332027E+09 | 79811862.68 | 0.104446E+10 |
December | 0.273961E+09 | 0.00 | 0.273961E+09 | 10932869.11 | 0.143113E+10 |
Annual Sum or Average | 0.622574E+10 | 0.252408E+09 | 0.597333E+10 | 0.583865E+10 | 0.867018E+10 |
Minimum of Months | 0.273961E+09 | 0.00 | 0.273961E+09 | 10932869.11 | 0.190894E+09 |
Maximum of Months | 0.769496E+09 | 0.125925E+09 | 0.669078E+09 | 0.112180E+10 | 0.143113E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321873E+09 | 0.00 | 0.321873E+09 | 52368735.03 | 0.132396E+10 |
February | 0.363356E+09 | 0.00 | 0.363356E+09 | 0.113707E+09 | 0.108326E+10 |
March | 0.507434E+09 | 0.00 | 0.507434E+09 | 0.298535E+09 | 0.943325E+09 |
April | 0.623010E+09 | 5333862.76 | 0.617676E+09 | 0.491910E+09 | 0.601229E+09 |
May | 0.699790E+09 | 45117094.49 | 0.654673E+09 | 0.725161E+09 | 0.438944E+09 |
June | 0.769499E+09 | 0.125925E+09 | 0.643574E+09 | 0.109231E+10 | 0.277163E+09 |
July | 0.729823E+09 | 60742318.50 | 0.669081E+09 | 0.112180E+10 | 0.190895E+09 |
August | 0.677033E+09 | 15157093.80 | 0.661876E+09 | 0.947995E+09 | 0.218330E+09 |
September | 0.523952E+09 | 134470.87 | 0.523817E+09 | 0.622373E+09 | 0.385460E+09 |
October | 0.404006E+09 | 0.00 | 0.404006E+09 | 0.281773E+09 | 0.732028E+09 |
November | 0.332029E+09 | 0.00 | 0.332029E+09 | 79812834.64 | 0.104446E+10 |
December | 0.273963E+09 | 0.00 | 0.273963E+09 | 10933167.30 | 0.143113E+10 |
Annual Sum or Average | 0.622577E+10 | 0.252410E+09 | 0.597336E+10 | 0.583868E+10 | 0.867019E+10 |
Minimum of Months | 0.273963E+09 | 0.00 | 0.273963E+09 | 10933167.30 | 0.190895E+09 |
Maximum of Months | 0.769499E+09 | 0.125925E+09 | 0.669081E+09 | 0.112180E+10 | 0.143113E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321871E+09 | 0.00 | 0.321871E+09 | 52367919.50 | 0.132396E+10 |
February | 0.363355E+09 | 0.00 | 0.363355E+09 | 0.113706E+09 | 0.108326E+10 |
March | 0.507432E+09 | 0.00 | 0.507432E+09 | 0.298533E+09 | 0.943325E+09 |
April | 0.623007E+09 | 5333823.67 | 0.617673E+09 | 0.491907E+09 | 0.601228E+09 |
May | 0.699787E+09 | 45116763.87 | 0.654671E+09 | 0.725157E+09 | 0.438943E+09 |
June | 0.769496E+09 | 0.125925E+09 | 0.643572E+09 | 0.109230E+10 | 0.277163E+09 |
July | 0.729820E+09 | 60741873.38 | 0.669078E+09 | 0.112180E+10 | 0.190894E+09 |
August | 0.677030E+09 | 15156982.73 | 0.661873E+09 | 0.947992E+09 | 0.218329E+09 |
September | 0.523950E+09 | 134469.88 | 0.523815E+09 | 0.622371E+09 | 0.385459E+09 |
October | 0.404004E+09 | 0.00 | 0.404004E+09 | 0.281772E+09 | 0.732027E+09 |
November | 0.332027E+09 | 0.00 | 0.332027E+09 | 79811862.68 | 0.104446E+10 |
December | 0.273961E+09 | 0.00 | 0.273961E+09 | 10932869.11 | 0.143113E+10 |
Annual Sum or Average | 0.622574E+10 | 0.252408E+09 | 0.597333E+10 | 0.583865E+10 | 0.867018E+10 |
Minimum of Months | 0.273961E+09 | 0.00 | 0.273961E+09 | 10932869.11 | 0.190894E+09 |
Maximum of Months | 0.769496E+09 | 0.125925E+09 | 0.669078E+09 | 0.112180E+10 | 0.143113E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321859E+09 | 0.00 | 0.321859E+09 | 52366216.59 | 0.132391E+10 |
February | 0.363341E+09 | 0.00 | 0.363341E+09 | 0.113702E+09 | 0.108322E+10 |
March | 0.507413E+09 | 0.00 | 0.507413E+09 | 0.298522E+09 | 0.943287E+09 |
April | 0.622983E+09 | 5333628.24 | 0.617650E+09 | 0.491889E+09 | 0.601204E+09 |
May | 0.699761E+09 | 45115110.77 | 0.654645E+09 | 0.725130E+09 | 0.438926E+09 |
June | 0.769467E+09 | 0.125920E+09 | 0.643547E+09 | 0.109226E+10 | 0.277152E+09 |
July | 0.729792E+09 | 60739647.76 | 0.669053E+09 | 0.112175E+10 | 0.190887E+09 |
August | 0.677004E+09 | 15156427.37 | 0.661848E+09 | 0.947956E+09 | 0.218321E+09 |
September | 0.523930E+09 | 134464.96 | 0.523795E+09 | 0.622347E+09 | 0.385444E+09 |
October | 0.403989E+09 | 0.00 | 0.403989E+09 | 0.281761E+09 | 0.731998E+09 |
November | 0.332015E+09 | 0.00 | 0.332015E+09 | 79809131.87 | 0.104442E+10 |
December | 0.273951E+09 | 0.00 | 0.273951E+09 | 10932577.55 | 0.143107E+10 |
Annual Sum or Average | 0.622550E+10 | 0.252399E+09 | 0.597310E+10 | 0.583843E+10 | 0.866984E+10 |
Minimum of Months | 0.273951E+09 | 0.00 | 0.273951E+09 | 10932577.55 | 0.190887E+09 |
Maximum of Months | 0.769467E+09 | 0.125920E+09 | 0.669053E+09 | 0.112175E+10 | 0.143107E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.990453E+09 | 0.553757E+09 | 0.436696E+09 | 0.831661E+09 | 0.133391E+10 |
February | 0.108692E+10 | 0.585969E+09 | 0.500955E+09 | 0.101217E+10 | 0.109835E+10 |
March | 0.158744E+10 | 0.902431E+09 | 0.685010E+09 | 0.169792E+10 | 0.956956E+09 |
April | 0.209881E+10 | 0.119568E+10 | 0.903127E+09 | 0.249535E+10 | 0.627699E+09 |
May | 0.206946E+10 | 0.117937E+10 | 0.890094E+09 | 0.261066E+10 | 0.494604E+09 |
June | 0.215907E+10 | 0.133009E+10 | 0.828980E+09 | 0.300905E+10 | 0.298677E+09 |
July | 0.206442E+10 | 0.118052E+10 | 0.883902E+09 | 0.300495E+10 | 0.200186E+09 |
August | 0.204288E+10 | 0.112628E+10 | 0.916604E+09 | 0.288387E+10 | 0.226236E+09 |
September | 0.164551E+10 | 0.920676E+09 | 0.724832E+09 | 0.218712E+10 | 0.408156E+09 |
October | 0.147879E+10 | 0.938234E+09 | 0.540555E+09 | 0.171486E+10 | 0.744482E+09 |
November | 0.111847E+10 | 0.657538E+09 | 0.460928E+09 | 0.107504E+10 | 0.105459E+10 |
December | 0.936483E+09 | 0.569936E+09 | 0.366548E+09 | 0.796931E+09 | 0.142195E+10 |
Annual Sum or Average | 0.192787E+11 | 0.111405E+11 | 0.813823E+10 | 0.233196E+11 | 0.886580E+10 |
Minimum of Months | 0.936483E+09 | 0.553757E+09 | 0.366548E+09 | 0.796931E+09 | 0.200186E+09 |
Maximum of Months | 0.215907E+10 | 0.133009E+10 | 0.916604E+09 | 0.300905E+10 | 0.142195E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.990453E+09 | 0.553757E+09 | 0.436696E+09 | 0.831661E+09 | 0.133391E+10 |
February | 0.108692E+10 | 0.585969E+09 | 0.500955E+09 | 0.101217E+10 | 0.109835E+10 |
March | 0.158744E+10 | 0.902431E+09 | 0.685010E+09 | 0.169792E+10 | 0.956956E+09 |
April | 0.209881E+10 | 0.119568E+10 | 0.903127E+09 | 0.249535E+10 | 0.627699E+09 |
May | 0.206946E+10 | 0.117937E+10 | 0.890094E+09 | 0.261066E+10 | 0.494604E+09 |
June | 0.215907E+10 | 0.133009E+10 | 0.828980E+09 | 0.300905E+10 | 0.298677E+09 |
July | 0.206442E+10 | 0.118052E+10 | 0.883902E+09 | 0.300495E+10 | 0.200186E+09 |
August | 0.204288E+10 | 0.112628E+10 | 0.916604E+09 | 0.288387E+10 | 0.226236E+09 |
September | 0.164551E+10 | 0.920676E+09 | 0.724832E+09 | 0.218712E+10 | 0.408156E+09 |
October | 0.147879E+10 | 0.938234E+09 | 0.540555E+09 | 0.171486E+10 | 0.744482E+09 |
November | 0.111847E+10 | 0.657538E+09 | 0.460928E+09 | 0.107504E+10 | 0.105459E+10 |
December | 0.936483E+09 | 0.569936E+09 | 0.366548E+09 | 0.796931E+09 | 0.142195E+10 |
Annual Sum or Average | 0.192787E+11 | 0.111405E+11 | 0.813823E+10 | 0.233196E+11 | 0.886580E+10 |
Minimum of Months | 0.936483E+09 | 0.553757E+09 | 0.366548E+09 | 0.796931E+09 | 0.200186E+09 |
Maximum of Months | 0.215907E+10 | 0.133009E+10 | 0.916604E+09 | 0.300905E+10 | 0.142195E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.990434E+09 | 0.553747E+09 | 0.436688E+09 | 0.831646E+09 | 0.133389E+10 |
February | 0.108690E+10 | 0.585958E+09 | 0.500946E+09 | 0.101216E+10 | 0.109833E+10 |
March | 0.158741E+10 | 0.902415E+09 | 0.684997E+09 | 0.169789E+10 | 0.956938E+09 |
April | 0.209877E+10 | 0.119566E+10 | 0.903111E+09 | 0.249531E+10 | 0.627688E+09 |
May | 0.206943E+10 | 0.117935E+10 | 0.890078E+09 | 0.261061E+10 | 0.494594E+09 |
June | 0.215903E+10 | 0.133007E+10 | 0.828965E+09 | 0.300899E+10 | 0.298672E+09 |
July | 0.206438E+10 | 0.118050E+10 | 0.883886E+09 | 0.300490E+10 | 0.200182E+09 |
August | 0.204285E+10 | 0.112626E+10 | 0.916587E+09 | 0.288381E+10 | 0.226232E+09 |
September | 0.164548E+10 | 0.920659E+09 | 0.724819E+09 | 0.218708E+10 | 0.408148E+09 |
October | 0.147876E+10 | 0.938217E+09 | 0.540545E+09 | 0.171483E+10 | 0.744468E+09 |
November | 0.111845E+10 | 0.657526E+09 | 0.460919E+09 | 0.107502E+10 | 0.105457E+10 |
December | 0.936466E+09 | 0.569926E+09 | 0.366541E+09 | 0.796917E+09 | 0.142193E+10 |
Annual Sum or Average | 0.192784E+11 | 0.111403E+11 | 0.813808E+10 | 0.233192E+11 | 0.886564E+10 |
Minimum of Months | 0.936466E+09 | 0.553747E+09 | 0.366541E+09 | 0.796917E+09 | 0.200182E+09 |
Maximum of Months | 0.215903E+10 | 0.133007E+10 | 0.916587E+09 | 0.300899E+10 | 0.142193E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237958E+10 | 0.185164E+10 | 0.527943E+09 | 0.274063E+10 | 0.118180E+10 |
February | 0.210339E+10 | 0.153645E+10 | 0.566938E+09 | 0.247689E+10 | 0.993910E+09 |
March | 0.171605E+10 | 0.103745E+10 | 0.678598E+09 | 0.206452E+10 | 0.902850E+09 |
April | 0.129513E+10 | 0.531625E+09 | 0.763509E+09 | 0.162027E+10 | 0.625643E+09 |
May | 0.892543E+09 | 0.196341E+09 | 0.696202E+09 | 0.112727E+10 | 0.468324E+09 |
June | 0.730663E+09 | 90045041.91 | 0.640618E+09 | 0.109059E+10 | 0.295667E+09 |
July | 0.835464E+09 | 0.133414E+09 | 0.702050E+09 | 0.135065E+10 | 0.201336E+09 |
August | 0.114882E+10 | 0.373422E+09 | 0.775399E+09 | 0.177701E+10 | 0.236399E+09 |
September | 0.153732E+10 | 0.857252E+09 | 0.680071E+09 | 0.220514E+10 | 0.400991E+09 |
October | 0.217335E+10 | 0.160065E+10 | 0.572693E+09 | 0.280029E+10 | 0.696735E+09 |
November | 0.234261E+10 | 0.179794E+10 | 0.544666E+09 | 0.278307E+10 | 0.942986E+09 |
December | 0.258178E+10 | 0.212969E+10 | 0.452085E+09 | 0.299309E+10 | 0.123310E+10 |
Annual Sum or Average | 0.197367E+11 | 0.121359E+11 | 0.760077E+10 | 0.250294E+11 | 0.817974E+10 |
Minimum of Months | 0.730663E+09 | 90045041.91 | 0.452085E+09 | 0.109059E+10 | 0.201336E+09 |
Maximum of Months | 0.258178E+10 | 0.212969E+10 | 0.775399E+09 | 0.299309E+10 | 0.123310E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237957E+10 | 0.185163E+10 | 0.527940E+09 | 0.274061E+10 | 0.118180E+10 |
February | 0.210337E+10 | 0.153644E+10 | 0.566935E+09 | 0.247687E+10 | 0.993910E+09 |
March | 0.171604E+10 | 0.103745E+10 | 0.678594E+09 | 0.206451E+10 | 0.902850E+09 |
April | 0.129513E+10 | 0.531621E+09 | 0.763506E+09 | 0.162025E+10 | 0.625643E+09 |
May | 0.892539E+09 | 0.196339E+09 | 0.696200E+09 | 0.112727E+10 | 0.468323E+09 |
June | 0.730660E+09 | 90044382.05 | 0.640616E+09 | 0.109058E+10 | 0.295667E+09 |
July | 0.835461E+09 | 0.133413E+09 | 0.702047E+09 | 0.135065E+10 | 0.201335E+09 |
August | 0.114882E+10 | 0.373420E+09 | 0.775396E+09 | 0.177700E+10 | 0.236399E+09 |
September | 0.153731E+10 | 0.857246E+09 | 0.680068E+09 | 0.220513E+10 | 0.400990E+09 |
October | 0.217333E+10 | 0.160064E+10 | 0.572690E+09 | 0.280026E+10 | 0.696734E+09 |
November | 0.234259E+10 | 0.179793E+10 | 0.544664E+09 | 0.278305E+10 | 0.942985E+09 |
December | 0.258176E+10 | 0.212968E+10 | 0.452082E+09 | 0.299306E+10 | 0.123310E+10 |
Annual Sum or Average | 0.197366E+11 | 0.121358E+11 | 0.760074E+10 | 0.250292E+11 | 0.817973E+10 |
Minimum of Months | 0.730660E+09 | 90044382.05 | 0.452082E+09 | 0.109058E+10 | 0.201335E+09 |
Maximum of Months | 0.258176E+10 | 0.212968E+10 | 0.775396E+09 | 0.299306E+10 | 0.123310E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237958E+10 | 0.185164E+10 | 0.527943E+09 | 0.274063E+10 | 0.118180E+10 |
February | 0.210339E+10 | 0.153645E+10 | 0.566938E+09 | 0.247689E+10 | 0.993910E+09 |
March | 0.171605E+10 | 0.103745E+10 | 0.678598E+09 | 0.206452E+10 | 0.902850E+09 |
April | 0.129513E+10 | 0.531625E+09 | 0.763509E+09 | 0.162027E+10 | 0.625643E+09 |
May | 0.892543E+09 | 0.196341E+09 | 0.696202E+09 | 0.112727E+10 | 0.468324E+09 |
June | 0.730663E+09 | 90045041.91 | 0.640618E+09 | 0.109059E+10 | 0.295667E+09 |
July | 0.835464E+09 | 0.133414E+09 | 0.702050E+09 | 0.135065E+10 | 0.201336E+09 |
August | 0.114882E+10 | 0.373422E+09 | 0.775399E+09 | 0.177701E+10 | 0.236399E+09 |
September | 0.153732E+10 | 0.857252E+09 | 0.680071E+09 | 0.220514E+10 | 0.400991E+09 |
October | 0.217335E+10 | 0.160065E+10 | 0.572693E+09 | 0.280029E+10 | 0.696735E+09 |
November | 0.234261E+10 | 0.179794E+10 | 0.544666E+09 | 0.278307E+10 | 0.942986E+09 |
December | 0.258178E+10 | 0.212969E+10 | 0.452085E+09 | 0.299309E+10 | 0.123310E+10 |
Annual Sum or Average | 0.197367E+11 | 0.121359E+11 | 0.760077E+10 | 0.250294E+11 | 0.817974E+10 |
Minimum of Months | 0.730663E+09 | 90045041.91 | 0.452085E+09 | 0.109059E+10 | 0.201336E+09 |
Maximum of Months | 0.258178E+10 | 0.212969E+10 | 0.775399E+09 | 0.299309E+10 | 0.123310E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237957E+10 | 0.185163E+10 | 0.527940E+09 | 0.274061E+10 | 0.118180E+10 |
February | 0.210337E+10 | 0.153644E+10 | 0.566935E+09 | 0.247687E+10 | 0.993910E+09 |
March | 0.171604E+10 | 0.103745E+10 | 0.678594E+09 | 0.206451E+10 | 0.902850E+09 |
April | 0.129513E+10 | 0.531621E+09 | 0.763506E+09 | 0.162025E+10 | 0.625643E+09 |
May | 0.892539E+09 | 0.196339E+09 | 0.696200E+09 | 0.112727E+10 | 0.468323E+09 |
June | 0.730660E+09 | 90044382.05 | 0.640616E+09 | 0.109058E+10 | 0.295667E+09 |
July | 0.835461E+09 | 0.133413E+09 | 0.702047E+09 | 0.135065E+10 | 0.201335E+09 |
August | 0.114882E+10 | 0.373420E+09 | 0.775396E+09 | 0.177700E+10 | 0.236399E+09 |
September | 0.153731E+10 | 0.857246E+09 | 0.680068E+09 | 0.220513E+10 | 0.400990E+09 |
October | 0.217333E+10 | 0.160064E+10 | 0.572690E+09 | 0.280026E+10 | 0.696734E+09 |
November | 0.234259E+10 | 0.179793E+10 | 0.544664E+09 | 0.278305E+10 | 0.942985E+09 |
December | 0.258176E+10 | 0.212968E+10 | 0.452082E+09 | 0.299306E+10 | 0.123310E+10 |
Annual Sum or Average | 0.197366E+11 | 0.121358E+11 | 0.760074E+10 | 0.250292E+11 | 0.817973E+10 |
Minimum of Months | 0.730660E+09 | 90044382.05 | 0.452082E+09 | 0.109058E+10 | 0.201335E+09 |
Maximum of Months | 0.258176E+10 | 0.212968E+10 | 0.775396E+09 | 0.299306E+10 | 0.123310E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237948E+10 | 0.185156E+10 | 0.527920E+09 | 0.274051E+10 | 0.118175E+10 |
February | 0.210329E+10 | 0.153638E+10 | 0.566914E+09 | 0.247678E+10 | 0.993870E+09 |
March | 0.171598E+10 | 0.103741E+10 | 0.678569E+09 | 0.206443E+10 | 0.902814E+09 |
April | 0.129508E+10 | 0.531602E+09 | 0.763477E+09 | 0.162020E+10 | 0.625618E+09 |
May | 0.892505E+09 | 0.196332E+09 | 0.696173E+09 | 0.112722E+10 | 0.468305E+09 |
June | 0.730632E+09 | 90041082.78 | 0.640591E+09 | 0.109054E+10 | 0.295655E+09 |
July | 0.835429E+09 | 0.133408E+09 | 0.702020E+09 | 0.135060E+10 | 0.201327E+09 |
August | 0.114877E+10 | 0.373406E+09 | 0.775366E+09 | 0.177693E+10 | 0.236390E+09 |
September | 0.153726E+10 | 0.857215E+09 | 0.680042E+09 | 0.220504E+10 | 0.400974E+09 |
October | 0.217325E+10 | 0.160058E+10 | 0.572668E+09 | 0.280016E+10 | 0.696707E+09 |
November | 0.234250E+10 | 0.179786E+10 | 0.544643E+09 | 0.278294E+10 | 0.942948E+09 |
December | 0.258167E+10 | 0.212960E+10 | 0.452065E+09 | 0.299296E+10 | 0.123305E+10 |
Annual Sum or Average | 0.197358E+11 | 0.121354E+11 | 0.760045E+10 | 0.250283E+11 | 0.817940E+10 |
Minimum of Months | 0.730632E+09 | 90041082.78 | 0.452065E+09 | 0.109054E+10 | 0.201327E+09 |
Maximum of Months | 0.258167E+10 | 0.212960E+10 | 0.775366E+09 | 0.299296E+10 | 0.123305E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102161E+10 | 0.582595E+09 | 0.439020E+09 | 0.947336E+09 | 0.148850E+10 |
February | 0.118789E+10 | 0.686207E+09 | 0.501680E+09 | 0.118390E+10 | 0.125832E+10 |
March | 0.146888E+10 | 0.781916E+09 | 0.686968E+09 | 0.155511E+10 | 0.113428E+10 |
April | 0.181426E+10 | 0.965559E+09 | 0.848703E+09 | 0.208832E+10 | 0.773066E+09 |
May | 0.177752E+10 | 0.915905E+09 | 0.861619E+09 | 0.220437E+10 | 0.562916E+09 |
June | 0.184403E+10 | 0.102895E+10 | 0.815082E+09 | 0.257138E+10 | 0.384054E+09 |
July | 0.171870E+10 | 0.841111E+09 | 0.877592E+09 | 0.249817E+10 | 0.274991E+09 |
August | 0.175621E+10 | 0.812319E+09 | 0.943891E+09 | 0.246288E+10 | 0.321896E+09 |
September | 0.153510E+10 | 0.808475E+09 | 0.726624E+09 | 0.204706E+10 | 0.480243E+09 |
October | 0.145122E+10 | 0.901987E+09 | 0.549234E+09 | 0.170906E+10 | 0.883948E+09 |
November | 0.110245E+10 | 0.648599E+09 | 0.453856E+09 | 0.107580E+10 | 0.122671E+10 |
December | 0.985179E+09 | 0.617812E+09 | 0.367366E+09 | 0.883083E+09 | 0.166117E+10 |
Annual Sum or Average | 0.176631E+11 | 0.959144E+10 | 0.807163E+10 | 0.212265E+11 | 0.104501E+11 |
Minimum of Months | 0.985179E+09 | 0.582595E+09 | 0.367366E+09 | 0.883083E+09 | 0.274991E+09 |
Maximum of Months | 0.184403E+10 | 0.102895E+10 | 0.943891E+09 | 0.257138E+10 | 0.166117E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102161E+10 | 0.582595E+09 | 0.439020E+09 | 0.947336E+09 | 0.148850E+10 |
February | 0.118789E+10 | 0.686207E+09 | 0.501680E+09 | 0.118390E+10 | 0.125832E+10 |
March | 0.146888E+10 | 0.781916E+09 | 0.686968E+09 | 0.155511E+10 | 0.113428E+10 |
April | 0.181426E+10 | 0.965559E+09 | 0.848703E+09 | 0.208832E+10 | 0.773066E+09 |
May | 0.177752E+10 | 0.915905E+09 | 0.861619E+09 | 0.220437E+10 | 0.562916E+09 |
June | 0.184403E+10 | 0.102895E+10 | 0.815082E+09 | 0.257138E+10 | 0.384054E+09 |
July | 0.171870E+10 | 0.841111E+09 | 0.877592E+09 | 0.249817E+10 | 0.274991E+09 |
August | 0.175621E+10 | 0.812319E+09 | 0.943891E+09 | 0.246288E+10 | 0.321896E+09 |
September | 0.153510E+10 | 0.808475E+09 | 0.726624E+09 | 0.204706E+10 | 0.480243E+09 |
October | 0.145122E+10 | 0.901987E+09 | 0.549234E+09 | 0.170906E+10 | 0.883948E+09 |
November | 0.110245E+10 | 0.648599E+09 | 0.453856E+09 | 0.107580E+10 | 0.122671E+10 |
December | 0.985179E+09 | 0.617812E+09 | 0.367366E+09 | 0.883083E+09 | 0.166117E+10 |
Annual Sum or Average | 0.176631E+11 | 0.959144E+10 | 0.807163E+10 | 0.212265E+11 | 0.104501E+11 |
Minimum of Months | 0.985179E+09 | 0.582595E+09 | 0.367366E+09 | 0.883083E+09 | 0.274991E+09 |
Maximum of Months | 0.184403E+10 | 0.102895E+10 | 0.943891E+09 | 0.257138E+10 | 0.166117E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102160E+10 | 0.582584E+09 | 0.439012E+09 | 0.947318E+09 | 0.148847E+10 |
February | 0.118787E+10 | 0.686194E+09 | 0.501671E+09 | 0.118388E+10 | 0.125829E+10 |
March | 0.146886E+10 | 0.781902E+09 | 0.686956E+09 | 0.155508E+10 | 0.113426E+10 |
April | 0.181423E+10 | 0.965541E+09 | 0.848687E+09 | 0.208828E+10 | 0.773052E+09 |
May | 0.177749E+10 | 0.915888E+09 | 0.861603E+09 | 0.220433E+10 | 0.562905E+09 |
June | 0.184400E+10 | 0.102893E+10 | 0.815067E+09 | 0.257133E+10 | 0.384047E+09 |
July | 0.171867E+10 | 0.841095E+09 | 0.877576E+09 | 0.249812E+10 | 0.274986E+09 |
August | 0.175618E+10 | 0.812304E+09 | 0.943873E+09 | 0.246284E+10 | 0.321890E+09 |
September | 0.153507E+10 | 0.808460E+09 | 0.726611E+09 | 0.204703E+10 | 0.480234E+09 |
October | 0.145120E+10 | 0.901971E+09 | 0.549224E+09 | 0.170903E+10 | 0.883931E+09 |
November | 0.110243E+10 | 0.648587E+09 | 0.453848E+09 | 0.107578E+10 | 0.122669E+10 |
December | 0.985161E+09 | 0.617801E+09 | 0.367360E+09 | 0.883066E+09 | 0.166114E+10 |
Annual Sum or Average | 0.176627E+11 | 0.959126E+10 | 0.807149E+10 | 0.212261E+11 | 0.104499E+11 |
Minimum of Months | 0.985161E+09 | 0.582584E+09 | 0.367360E+09 | 0.883066E+09 | 0.274986E+09 |
Maximum of Months | 0.184400E+10 | 0.102893E+10 | 0.943873E+09 | 0.257133E+10 | 0.166114E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160938E+10 | 0.00 | 0.160938E+10 | 0.390720E+09 | 0.599523E+10 |
February | 0.181679E+10 | 0.00 | 0.181679E+10 | 0.718495E+09 | 0.490865E+10 |
March | 0.253719E+10 | 0.00 | 0.253719E+10 | 0.165056E+10 | 0.431261E+10 |
April | 0.311507E+10 | 26669874.63 | 0.308840E+10 | 0.256415E+10 | 0.280006E+10 |
May | 0.349897E+10 | 0.225590E+09 | 0.327338E+10 | 0.367599E+10 | 0.210626E+10 |
June | 0.384753E+10 | 0.629640E+09 | 0.321789E+10 | 0.549642E+10 | 0.135647E+10 |
July | 0.364914E+10 | 0.303718E+09 | 0.334542E+10 | 0.565099E+10 | 0.945012E+09 |
August | 0.338519E+10 | 75787062.69 | 0.330940E+10 | 0.478900E+10 | 0.106949E+10 |
September | 0.261977E+10 | 672368.48 | 0.261910E+10 | 0.315177E+10 | 0.184412E+10 |
October | 0.202004E+10 | 0.00 | 0.202004E+10 | 0.151212E+10 | 0.336050E+10 |
November | 0.166015E+10 | 0.00 | 0.166015E+10 | 0.531733E+09 | 0.462759E+10 |
December | 0.136982E+10 | 0.00 | 0.136982E+10 | 0.129359E+09 | 0.626410E+10 |
Annual Sum or Average | 0.311290E+11 | 0.126208E+10 | 0.298670E+11 | 0.302613E+11 | 0.395901E+11 |
Minimum of Months | 0.136982E+10 | 0.00 | 0.136982E+10 | 0.129359E+09 | 0.945012E+09 |
Maximum of Months | 0.384753E+10 | 0.629640E+09 | 0.334542E+10 | 0.565099E+10 | 0.626410E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.297133E+10 | 0.166125E+10 | 0.131007E+10 | 0.258069E+10 | 0.371124E+10 |
February | 0.326074E+10 | 0.175789E+10 | 0.150285E+10 | 0.310139E+10 | 0.307627E+10 |
March | 0.476227E+10 | 0.270727E+10 | 0.205501E+10 | 0.511368E+10 | 0.273630E+10 |
April | 0.629636E+10 | 0.358700E+10 | 0.270935E+10 | 0.745406E+10 | 0.185810E+10 |
May | 0.620833E+10 | 0.353808E+10 | 0.267025E+10 | 0.779248E+10 | 0.145973E+10 |
June | 0.647715E+10 | 0.399023E+10 | 0.248692E+10 | 0.898579E+10 | 0.909429E+09 |
July | 0.619320E+10 | 0.354153E+10 | 0.265168E+10 | 0.897002E+10 | 0.648774E+09 |
August | 0.612859E+10 | 0.337881E+10 | 0.274978E+10 | 0.860365E+10 | 0.731927E+09 |
September | 0.493647E+10 | 0.276200E+10 | 0.217447E+10 | 0.653658E+10 | 0.120683E+10 |
October | 0.443632E+10 | 0.281467E+10 | 0.162165E+10 | 0.514984E+10 | 0.214025E+10 |
November | 0.335536E+10 | 0.197259E+10 | 0.138277E+10 | 0.327325E+10 | 0.293772E+10 |
December | 0.280942E+10 | 0.170979E+10 | 0.109963E+10 | 0.245885E+10 | 0.389767E+10 |
Annual Sum or Average | 0.578356E+11 | 0.334211E+11 | 0.244144E+11 | 0.700203E+11 | 0.253142E+11 |
Minimum of Months | 0.280942E+10 | 0.166125E+10 | 0.109963E+10 | 0.245885E+10 | 0.648774E+09 |
Maximum of Months | 0.647715E+10 | 0.399023E+10 | 0.274978E+10 | 0.898579E+10 | 0.389767E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118982E+11 | 0.925840E+10 | 0.263975E+10 | 0.136385E+11 | 0.583098E+10 |
February | 0.105171E+11 | 0.768240E+10 | 0.283472E+10 | 0.123239E+11 | 0.489052E+10 |
March | 0.858041E+10 | 0.518738E+10 | 0.339302E+10 | 0.102812E+11 | 0.441050E+10 |
April | 0.647576E+10 | 0.265818E+10 | 0.381758E+10 | 0.807985E+10 | 0.304633E+10 |
May | 0.446276E+10 | 0.981725E+09 | 0.348103E+10 | 0.562712E+10 | 0.229114E+10 |
June | 0.365334E+10 | 0.450235E+09 | 0.320310E+10 | 0.548192E+10 | 0.145020E+10 |
July | 0.417736E+10 | 0.667085E+09 | 0.351027E+10 | 0.677337E+10 | 0.100562E+10 |
August | 0.574418E+10 | 0.186715E+10 | 0.387703E+10 | 0.887867E+10 | 0.118329E+10 |
September | 0.768674E+10 | 0.428635E+10 | 0.340039E+10 | 0.109627E+11 | 0.199094E+10 |
October | 0.108669E+11 | 0.800344E+10 | 0.286349E+10 | 0.139218E+11 | 0.344684E+10 |
November | 0.117133E+11 | 0.898989E+10 | 0.272337E+10 | 0.138533E+11 | 0.462102E+10 |
December | 0.129091E+11 | 0.106487E+11 | 0.226045E+10 | 0.149297E+11 | 0.597267E+10 |
Annual Sum or Average | 0.986851E+11 | 0.606809E+11 | 0.380042E+11 | 0.124752E+12 | 0.401401E+11 |
Minimum of Months | 0.365334E+10 | 0.450235E+09 | 0.226045E+10 | 0.548192E+10 | 0.100562E+10 |
Maximum of Months | 0.129091E+11 | 0.106487E+11 | 0.387703E+10 | 0.149297E+11 | 0.597267E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306481E+10 | 0.174777E+10 | 0.131705E+10 | 0.293909E+10 | 0.405975E+10 |
February | 0.356362E+10 | 0.205860E+10 | 0.150502E+10 | 0.366228E+10 | 0.337842E+10 |
March | 0.440661E+10 | 0.234573E+10 | 0.206088E+10 | 0.479259E+10 | 0.301302E+10 |
April | 0.544273E+10 | 0.289665E+10 | 0.254608E+10 | 0.636628E+10 | 0.207068E+10 |
May | 0.533252E+10 | 0.274769E+10 | 0.258483E+10 | 0.663881E+10 | 0.159159E+10 |
June | 0.553204E+10 | 0.308682E+10 | 0.244522E+10 | 0.776060E+10 | 0.107527E+10 |
July | 0.515606E+10 | 0.252331E+10 | 0.263275E+10 | 0.756675E+10 | 0.744348E+09 |
August | 0.526857E+10 | 0.243693E+10 | 0.283164E+10 | 0.747087E+10 | 0.857062E+09 |
September | 0.460525E+10 | 0.242540E+10 | 0.217985E+10 | 0.616427E+10 | 0.135264E+10 |
October | 0.435362E+10 | 0.270593E+10 | 0.164769E+10 | 0.520334E+10 | 0.238957E+10 |
November | 0.330733E+10 | 0.194578E+10 | 0.136155E+10 | 0.335376E+10 | 0.317012E+10 |
December | 0.295551E+10 | 0.185342E+10 | 0.110209E+10 | 0.277720E+10 | 0.418496E+10 |
Annual Sum or Average | 0.529887E+11 | 0.287740E+11 | 0.242147E+11 | 0.646958E+11 | 0.278874E+11 |
Minimum of Months | 0.295551E+10 | 0.174777E+10 | 0.110209E+10 | 0.277720E+10 | 0.744348E+09 |
Maximum of Months | 0.553204E+10 | 0.308682E+10 | 0.283164E+10 | 0.776060E+10 | 0.418496E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160938E+10 | 0.00 | 0.160938E+10 | 0.481433E+09 | 0.551380E+10 |
February | 0.181679E+10 | 0.00 | 0.181679E+10 | 0.812692E+09 | 0.453437E+10 |
March | 0.253719E+10 | 0.00 | 0.253719E+10 | 0.176277E+10 | 0.400620E+10 |
April | 0.311507E+10 | 26669874.63 | 0.308840E+10 | 0.261937E+10 | 0.265793E+10 |
May | 0.349897E+10 | 0.225590E+09 | 0.327338E+10 | 0.368621E+10 | 0.205379E+10 |
June | 0.384753E+10 | 0.629640E+09 | 0.321789E+10 | 0.545954E+10 | 0.135906E+10 |
July | 0.364914E+10 | 0.303718E+09 | 0.334542E+10 | 0.558964E+10 | 0.971991E+09 |
August | 0.338519E+10 | 75787062.69 | 0.330940E+10 | 0.473907E+10 | 0.108716E+10 |
September | 0.261977E+10 | 672368.48 | 0.261910E+10 | 0.314256E+10 | 0.180880E+10 |
October | 0.202004E+10 | 0.00 | 0.202004E+10 | 0.157348E+10 | 0.313390E+10 |
November | 0.166015E+10 | 0.00 | 0.166015E+10 | 0.637395E+09 | 0.418495E+10 |
December | 0.136982E+10 | 0.00 | 0.136982E+10 | 0.180455E+09 | 0.574667E+10 |
Annual Sum or Average | 0.311290E+11 | 0.126208E+10 | 0.298670E+11 | 0.306846E+11 | 0.370586E+11 |
Minimum of Months | 0.136982E+10 | 0.00 | 0.136982E+10 | 0.180455E+09 | 0.971991E+09 |
Maximum of Months | 0.384753E+10 | 0.629640E+09 | 0.334542E+10 | 0.558964E+10 | 0.574667E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.297133E+10 | 0.166125E+10 | 0.131007E+10 | 0.269316E+10 | 0.343012E+10 |
February | 0.326074E+10 | 0.175789E+10 | 0.150285E+10 | 0.319269E+10 | 0.285746E+10 |
March | 0.476227E+10 | 0.270727E+10 | 0.205501E+10 | 0.517907E+10 | 0.257785E+10 |
April | 0.629636E+10 | 0.358700E+10 | 0.270935E+10 | 0.746535E+10 | 0.179760E+10 |
May | 0.620833E+10 | 0.353808E+10 | 0.267025E+10 | 0.777635E+10 | 0.143633E+10 |
June | 0.647715E+10 | 0.399023E+10 | 0.248692E+10 | 0.895031E+10 | 0.913955E+09 |
July | 0.619320E+10 | 0.354153E+10 | 0.265168E+10 | 0.892514E+10 | 0.667340E+09 |
August | 0.612859E+10 | 0.337881E+10 | 0.274978E+10 | 0.856408E+10 | 0.746750E+09 |
September | 0.493647E+10 | 0.276200E+10 | 0.217447E+10 | 0.652044E+10 | 0.119592E+10 |
October | 0.443632E+10 | 0.281467E+10 | 0.162165E+10 | 0.518348E+10 | 0.203397E+10 |
November | 0.335536E+10 | 0.197259E+10 | 0.138277E+10 | 0.337314E+10 | 0.268974E+10 |
December | 0.280942E+10 | 0.170979E+10 | 0.109963E+10 | 0.254356E+10 | 0.358229E+10 |
Annual Sum or Average | 0.578356E+11 | 0.334211E+11 | 0.244144E+11 | 0.703668E+11 | 0.239293E+11 |
Minimum of Months | 0.280942E+10 | 0.166125E+10 | 0.109963E+10 | 0.254356E+10 | 0.667340E+09 |
Maximum of Months | 0.647715E+10 | 0.399023E+10 | 0.274978E+10 | 0.895031E+10 | 0.358229E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118982E+11 | 0.925840E+10 | 0.263975E+10 | 0.137879E+11 | 0.540733E+10 |
February | 0.105171E+11 | 0.768240E+10 | 0.283472E+10 | 0.124328E+11 | 0.455189E+10 |
March | 0.858041E+10 | 0.518738E+10 | 0.339302E+10 | 0.103659E+11 | 0.415484E+10 |
April | 0.647576E+10 | 0.265818E+10 | 0.381758E+10 | 0.810386E+10 | 0.291618E+10 |
May | 0.446276E+10 | 0.981725E+09 | 0.348103E+10 | 0.562381E+10 | 0.222902E+10 |
June | 0.365334E+10 | 0.450235E+09 | 0.320310E+10 | 0.544709E+10 | 0.144188E+10 |
July | 0.417736E+10 | 0.667085E+09 | 0.351027E+10 | 0.671568E+10 | 0.102787E+10 |
August | 0.574418E+10 | 0.186715E+10 | 0.387703E+10 | 0.882497E+10 | 0.119938E+10 |
September | 0.768674E+10 | 0.428635E+10 | 0.340039E+10 | 0.109383E+11 | 0.196491E+10 |
October | 0.108669E+11 | 0.800344E+10 | 0.286349E+10 | 0.139687E+11 | 0.328380E+10 |
November | 0.117133E+11 | 0.898989E+10 | 0.272337E+10 | 0.139817E+11 | 0.427865E+10 |
December | 0.129091E+11 | 0.106487E+11 | 0.226045E+10 | 0.150496E+11 | 0.551315E+10 |
Annual Sum or Average | 0.986851E+11 | 0.606809E+11 | 0.380042E+11 | 0.125240E+12 | 0.379689E+11 |
Minimum of Months | 0.365334E+10 | 0.450235E+09 | 0.226045E+10 | 0.544709E+10 | 0.102787E+10 |
Maximum of Months | 0.129091E+11 | 0.106487E+11 | 0.387703E+10 | 0.150496E+11 | 0.551315E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306481E+10 | 0.174777E+10 | 0.131705E+10 | 0.299484E+10 | 0.378493E+10 |
February | 0.356362E+10 | 0.205860E+10 | 0.150502E+10 | 0.370870E+10 | 0.316769E+10 |
March | 0.440661E+10 | 0.234573E+10 | 0.206088E+10 | 0.484064E+10 | 0.284676E+10 |
April | 0.544273E+10 | 0.289665E+10 | 0.254608E+10 | 0.638073E+10 | 0.199179E+10 |
May | 0.533252E+10 | 0.274769E+10 | 0.258483E+10 | 0.663255E+10 | 0.155461E+10 |
June | 0.553204E+10 | 0.308682E+10 | 0.244522E+10 | 0.773310E+10 | 0.107064E+10 |
July | 0.515606E+10 | 0.252331E+10 | 0.263275E+10 | 0.752703E+10 | 0.755302E+09 |
August | 0.526857E+10 | 0.243693E+10 | 0.283164E+10 | 0.743612E+10 | 0.865224E+09 |
September | 0.460525E+10 | 0.242540E+10 | 0.217985E+10 | 0.615157E+10 | 0.133464E+10 |
October | 0.435362E+10 | 0.270593E+10 | 0.164769E+10 | 0.522433E+10 | 0.227204E+10 |
November | 0.330733E+10 | 0.194578E+10 | 0.136155E+10 | 0.341042E+10 | 0.293097E+10 |
December | 0.295551E+10 | 0.185342E+10 | 0.110209E+10 | 0.281501E+10 | 0.389556E+10 |
Annual Sum or Average | 0.529887E+11 | 0.287740E+11 | 0.242147E+11 | 0.648550E+11 | 0.264702E+11 |
Minimum of Months | 0.295551E+10 | 0.174777E+10 | 0.110209E+10 | 0.281501E+10 | 0.755302E+09 |
Maximum of Months | 0.553204E+10 | 0.308682E+10 | 0.283164E+10 | 0.773310E+10 | 0.389556E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 97.76 | 2471.53 | 600.86 | 0.00 | 600.86 | 0.00 | 0.00 |
February | 235.01 | 2238.87 | 750.98 | 0.00 | 750.98 | 0.00 | 0.00 |
March | 557.30 | 1760.97 | 947.26 | 0.00 | 947.26 | 0.00 | 0.00 |
April | 948.89 | 1159.77 | 1201.78 | 10.29 | 1191.49 | 0.00 | 0.00 |
May | 1353.71 | 819.41 | 1306.35 | 84.22 | 1222.12 | 0.00 | 0.00 |
June | 2107.06 | 534.65 | 1484.36 | 242.91 | 1241.45 | 0.00 | 0.00 |
July | 2094.14 | 356.36 | 1362.41 | 113.39 | 1249.02 | 0.00 | 0.00 |
August | 1769.69 | 407.57 | 1263.86 | 28.29 | 1235.57 | 0.00 | 0.00 |
September | 1200.56 | 743.55 | 1010.70 | 0.26 | 1010.44 | 0.00 | 0.00 |
October | 526.01 | 1366.53 | 754.19 | 0.00 | 754.19 | 0.00 | 0.00 |
November | 153.96 | 2014.77 | 640.48 | 0.00 | 640.48 | 0.00 | 0.00 |
December | 20.41 | 2671.59 | 511.43 | 0.00 | 511.43 | 0.00 | 0.00 |
Annual Sum or Average | 925.71 | 1374.64 | 987.08 | 40.02 | 947.06 | 0.00 | 0.00 |
Minimum of Months | 20.41 | 356.36 | 511.43 | 0.00 | 511.43 | 0.00 | 0.00 |
Maximum of Months | 2107.06 | 2671.59 | 1484.36 | 242.91 | 1249.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 931.51 | 1494.07 | 1109.37 | 620.24 | 489.13 | 0.00 | 0.00 |
February | 1255.17 | 1362.03 | 1347.86 | 726.64 | 621.22 | 0.00 | 0.00 |
March | 1901.78 | 1071.85 | 1778.04 | 1010.78 | 767.26 | 0.00 | 0.00 |
April | 2888.12 | 726.50 | 2429.16 | 1383.88 | 1045.28 | 0.00 | 0.00 |
May | 2924.10 | 553.99 | 2317.93 | 1320.97 | 996.96 | 0.00 | 0.00 |
June | 3482.67 | 345.69 | 2498.91 | 1539.45 | 959.46 | 0.00 | 0.00 |
July | 3365.74 | 224.22 | 2312.29 | 1322.26 | 990.03 | 0.00 | 0.00 |
August | 3230.12 | 253.40 | 2288.16 | 1261.51 | 1026.66 | 0.00 | 0.00 |
September | 2531.37 | 472.40 | 1904.51 | 1065.59 | 838.92 | 0.00 | 0.00 |
October | 1920.75 | 833.87 | 1656.34 | 1050.88 | 605.46 | 0.00 | 0.00 |
November | 1244.25 | 1220.58 | 1294.51 | 761.03 | 533.48 | 0.00 | 0.00 |
December | 892.61 | 1592.68 | 1048.92 | 638.37 | 410.56 | 0.00 | 0.00 |
Annual Sum or Average | 2218.36 | 843.39 | 1833.96 | 1059.78 | 774.18 | 0.00 | 0.00 |
Minimum of Months | 892.61 | 224.22 | 1048.92 | 620.24 | 410.56 | 0.00 | 0.00 |
Maximum of Months | 3482.67 | 1592.68 | 2498.91 | 1539.45 | 1045.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5116.11 | 2206.15 | 4442.12 | 3456.58 | 985.55 | 0.00 | 0.00 |
February | 5119.18 | 2054.20 | 4347.23 | 3175.49 | 1171.73 | 0.00 | 0.00 |
March | 3853.97 | 1685.41 | 3203.47 | 1936.68 | 1266.78 | 0.00 | 0.00 |
April | 3125.48 | 1206.86 | 2498.30 | 1025.50 | 1472.80 | 0.00 | 0.00 |
May | 2104.35 | 874.25 | 1666.17 | 366.52 | 1299.65 | 0.00 | 0.00 |
June | 2103.74 | 570.34 | 1409.44 | 173.70 | 1235.75 | 0.00 | 0.00 |
July | 2521.36 | 375.85 | 1559.62 | 249.05 | 1310.56 | 0.00 | 0.00 |
August | 3317.26 | 441.30 | 2144.58 | 697.09 | 1447.49 | 0.00 | 0.00 |
September | 4253.70 | 773.51 | 2965.48 | 1653.63 | 1311.85 | 0.00 | 0.00 |
October | 5227.47 | 1300.64 | 4057.13 | 2988.04 | 1069.08 | 0.00 | 0.00 |
November | 5368.51 | 1819.02 | 4518.86 | 3468.21 | 1050.66 | 0.00 | 0.00 |
December | 5587.39 | 2301.91 | 4819.57 | 3975.64 | 843.94 | 0.00 | 0.00 |
Annual Sum or Average | 3968.34 | 1296.88 | 3129.20 | 1924.12 | 1205.08 | 0.00 | 0.00 |
Minimum of Months | 2103.74 | 375.85 | 1409.44 | 173.70 | 843.94 | 0.00 | 0.00 |
Maximum of Months | 5587.39 | 2301.91 | 4819.57 | 3975.64 | 1472.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1061.08 | 1667.21 | 1144.27 | 652.54 | 491.73 | 0.00 | 0.00 |
February | 1468.12 | 1560.40 | 1473.07 | 850.95 | 622.12 | 0.00 | 0.00 |
March | 1741.82 | 1270.46 | 1645.25 | 875.80 | 769.45 | 0.00 | 0.00 |
April | 2417.03 | 894.75 | 2099.83 | 1117.54 | 982.29 | 0.00 | 0.00 |
May | 2469.04 | 630.50 | 1990.94 | 1025.87 | 965.07 | 0.00 | 0.00 |
June | 2976.11 | 444.50 | 2134.28 | 1190.91 | 943.38 | 0.00 | 0.00 |
July | 2798.11 | 308.01 | 1925.06 | 942.10 | 982.96 | 0.00 | 0.00 |
August | 2758.59 | 360.54 | 1967.07 | 909.85 | 1057.22 | 0.00 | 0.00 |
September | 2369.27 | 555.83 | 1776.72 | 935.73 | 841.00 | 0.00 | 0.00 |
October | 1914.26 | 990.08 | 1625.46 | 1010.28 | 615.18 | 0.00 | 0.00 |
November | 1245.13 | 1419.79 | 1275.98 | 750.69 | 525.29 | 0.00 | 0.00 |
December | 989.11 | 1860.62 | 1103.46 | 691.99 | 411.47 | 0.00 | 0.00 |
Annual Sum or Average | 2019.25 | 994.10 | 1680.27 | 912.42 | 767.84 | 0.00 | 0.00 |
Minimum of Months | 989.11 | 308.01 | 1103.46 | 652.54 | 411.47 | 0.00 | 0.00 |
Maximum of Months | 2976.11 | 1860.62 | 2134.28 | 1190.91 | 1057.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 145.88 | 2238.36 | 600.87 | 0.00 | 600.87 | 0.00 | 0.00 |
February | 297.00 | 2029.04 | 750.99 | 0.00 | 750.99 | 0.00 | 0.00 |
March | 616.25 | 1610.15 | 947.28 | 0.00 | 947.28 | 0.00 | 0.00 |
April | 989.26 | 1080.27 | 1201.80 | 10.29 | 1191.51 | 0.00 | 0.00 |
May | 1372.46 | 786.39 | 1306.37 | 84.23 | 1222.14 | 0.00 | 0.00 |
June | 2120.53 | 523.33 | 1484.38 | 242.92 | 1241.47 | 0.00 | 0.00 |
July | 2109.84 | 352.83 | 1362.43 | 113.40 | 1249.04 | 0.00 | 0.00 |
August | 1788.01 | 399.30 | 1263.88 | 28.30 | 1235.59 | 0.00 | 0.00 |
September | 1215.96 | 711.46 | 1010.72 | 0.26 | 1010.46 | 0.00 | 0.00 |
October | 564.56 | 1254.67 | 754.20 | 0.00 | 754.20 | 0.00 | 0.00 |
November | 205.14 | 1785.33 | 640.49 | 0.00 | 640.49 | 0.00 | 0.00 |
December | 48.30 | 2338.75 | 511.43 | 0.00 | 511.43 | 0.00 | 0.00 |
Annual Sum or Average | 959.58 | 1255.39 | 987.10 | 40.02 | 947.07 | 0.00 | 0.00 |
Minimum of Months | 48.30 | 352.83 | 511.43 | 0.00 | 511.43 | 0.00 | 0.00 |
Maximum of Months | 2120.53 | 2338.75 | 1484.38 | 242.92 | 1249.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 963.52 | 1385.62 | 1109.37 | 620.24 | 489.13 | 0.00 | 0.00 |
February | 1281.99 | 1271.61 | 1347.86 | 726.64 | 621.22 | 0.00 | 0.00 |
March | 1909.23 | 1021.62 | 1778.03 | 1010.78 | 767.25 | 0.00 | 0.00 |
April | 2875.79 | 716.86 | 2429.15 | 1383.87 | 1045.28 | 0.00 | 0.00 |
May | 2909.38 | 545.00 | 2317.93 | 1320.97 | 996.96 | 0.00 | 0.00 |
June | 3466.74 | 350.86 | 2498.90 | 1539.44 | 959.46 | 0.00 | 0.00 |
July | 3349.02 | 242.22 | 2312.28 | 1322.25 | 990.02 | 0.00 | 0.00 |
August | 3212.23 | 273.27 | 2288.15 | 1261.50 | 1026.65 | 0.00 | 0.00 |
September | 2521.83 | 465.60 | 1904.50 | 1065.59 | 838.92 | 0.00 | 0.00 |
October | 1922.73 | 799.08 | 1656.33 | 1050.88 | 605.45 | 0.00 | 0.00 |
November | 1262.83 | 1133.38 | 1294.51 | 761.03 | 533.48 | 0.00 | 0.00 |
December | 918.03 | 1455.22 | 1048.92 | 638.36 | 410.56 | 0.00 | 0.00 |
Annual Sum or Average | 2220.33 | 802.71 | 1833.95 | 1059.78 | 774.18 | 0.00 | 0.00 |
Minimum of Months | 918.03 | 242.22 | 1048.92 | 620.24 | 410.56 | 0.00 | 0.00 |
Maximum of Months | 3466.74 | 1455.22 | 2498.90 | 1539.44 | 1045.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5092.03 | 2177.04 | 4442.26 | 3456.69 | 985.57 | 0.00 | 0.00 |
February | 5094.19 | 2021.55 | 4347.36 | 3175.60 | 1171.76 | 0.00 | 0.00 |
March | 3838.55 | 1646.69 | 3203.56 | 1936.75 | 1266.81 | 0.00 | 0.00 |
April | 3117.23 | 1175.28 | 2498.36 | 1025.53 | 1472.83 | 0.00 | 0.00 |
May | 2100.93 | 855.41 | 1666.20 | 366.53 | 1299.67 | 0.00 | 0.00 |
June | 2114.94 | 559.49 | 1409.47 | 173.70 | 1235.77 | 0.00 | 0.00 |
July | 2528.89 | 375.46 | 1559.65 | 249.06 | 1310.59 | 0.00 | 0.00 |
August | 3314.91 | 441.79 | 2144.63 | 697.11 | 1447.52 | 0.00 | 0.00 |
September | 4229.44 | 768.11 | 2965.56 | 1653.69 | 1311.88 | 0.00 | 0.00 |
October | 5197.82 | 1286.90 | 4057.25 | 2988.14 | 1069.11 | 0.00 | 0.00 |
November | 5344.62 | 1782.80 | 4519.00 | 3468.32 | 1050.68 | 0.00 | 0.00 |
December | 5574.13 | 2229.94 | 4819.72 | 3975.77 | 843.96 | 0.00 | 0.00 |
Annual Sum or Average | 3955.86 | 1272.83 | 3129.29 | 1924.18 | 1205.11 | 0.00 | 0.00 |
Minimum of Months | 2100.93 | 375.46 | 1409.47 | 173.70 | 843.96 | 0.00 | 0.00 |
Maximum of Months | 5574.13 | 2229.94 | 4819.72 | 3975.77 | 1472.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1097.33 | 1515.74 | 1144.27 | 652.54 | 491.73 | 0.00 | 0.00 |
February | 1513.84 | 1396.50 | 1473.06 | 850.94 | 622.12 | 0.00 | 0.00 |
March | 1789.35 | 1124.93 | 1645.24 | 875.79 | 769.45 | 0.00 | 0.00 |
April | 2456.12 | 798.87 | 2099.82 | 1117.53 | 982.28 | 0.00 | 0.00 |
May | 2478.65 | 594.23 | 1990.93 | 1025.87 | 965.06 | 0.00 | 0.00 |
June | 2994.06 | 414.84 | 2134.28 | 1190.90 | 943.37 | 0.00 | 0.00 |
July | 2825.10 | 277.91 | 1925.05 | 942.09 | 982.96 | 0.00 | 0.00 |
August | 2789.30 | 319.99 | 1967.06 | 909.85 | 1057.21 | 0.00 | 0.00 |
September | 2378.19 | 521.85 | 1776.72 | 935.73 | 840.99 | 0.00 | 0.00 |
October | 1942.70 | 892.16 | 1625.46 | 1010.28 | 615.18 | 0.00 | 0.00 |
November | 1293.89 | 1223.04 | 1275.98 | 750.69 | 525.29 | 0.00 | 0.00 |
December | 1036.89 | 1562.49 | 1103.46 | 691.99 | 411.47 | 0.00 | 0.00 |
Annual Sum or Average | 2051.49 | 884.30 | 1680.26 | 912.42 | 767.84 | 0.00 | 0.00 |
Minimum of Months | 1036.89 | 277.91 | 1103.46 | 652.54 | 411.47 | 0.00 | 0.00 |
Maximum of Months | 2994.06 | 1562.49 | 2134.28 | 1190.90 | 1057.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 179.75 | 2058.62 | 600.87 | 0.00 | 600.87 | 0.00 | 0.00 |
February | 335.93 | 1874.33 | 750.99 | 0.00 | 750.99 | 0.00 | 0.00 |
March | 658.14 | 1495.74 | 947.28 | 0.00 | 947.28 | 0.00 | 0.00 |
April | 1010.56 | 1025.44 | 1201.80 | 10.29 | 1191.51 | 0.00 | 0.00 |
May | 1376.27 | 766.80 | 1306.37 | 84.23 | 1222.14 | 0.00 | 0.00 |
June | 2106.30 | 524.33 | 1484.38 | 242.92 | 1241.47 | 0.00 | 0.00 |
July | 2086.93 | 362.90 | 1362.43 | 113.40 | 1249.04 | 0.00 | 0.00 |
August | 1769.37 | 405.90 | 1263.88 | 28.30 | 1235.59 | 0.00 | 0.00 |
September | 1212.41 | 697.84 | 1010.72 | 0.26 | 1010.46 | 0.00 | 0.00 |
October | 587.47 | 1170.07 | 754.20 | 0.00 | 754.20 | 0.00 | 0.00 |
November | 245.91 | 1614.56 | 640.49 | 0.00 | 640.49 | 0.00 | 0.00 |
December | 67.37 | 2145.56 | 511.43 | 0.00 | 511.43 | 0.00 | 0.00 |
Annual Sum or Average | 973.00 | 1175.12 | 987.10 | 40.02 | 947.07 | 0.00 | 0.00 |
Minimum of Months | 67.37 | 362.90 | 511.43 | 0.00 | 511.43 | 0.00 | 0.00 |
Maximum of Months | 2106.30 | 2145.56 | 1484.38 | 242.92 | 1249.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1005.51 | 1280.66 | 1109.37 | 620.24 | 489.13 | 0.00 | 0.00 |
February | 1319.73 | 1181.16 | 1347.86 | 726.64 | 621.22 | 0.00 | 0.00 |
March | 1933.64 | 962.46 | 1778.03 | 1010.78 | 767.25 | 0.00 | 0.00 |
April | 2880.15 | 693.52 | 2429.15 | 1383.87 | 1045.28 | 0.00 | 0.00 |
May | 2903.36 | 536.26 | 2317.93 | 1320.97 | 996.96 | 0.00 | 0.00 |
June | 3453.05 | 352.61 | 2498.90 | 1539.44 | 959.46 | 0.00 | 0.00 |
July | 3332.27 | 249.16 | 2312.28 | 1322.25 | 990.02 | 0.00 | 0.00 |
August | 3197.46 | 278.80 | 2288.15 | 1261.50 | 1026.65 | 0.00 | 0.00 |
September | 2515.60 | 461.39 | 1904.50 | 1065.59 | 838.92 | 0.00 | 0.00 |
October | 1935.29 | 759.40 | 1656.33 | 1050.88 | 605.45 | 0.00 | 0.00 |
November | 1301.37 | 1037.71 | 1294.51 | 761.03 | 533.48 | 0.00 | 0.00 |
December | 949.66 | 1337.47 | 1048.92 | 638.36 | 410.56 | 0.00 | 0.00 |
Annual Sum or Average | 2231.32 | 758.79 | 1833.95 | 1059.78 | 774.18 | 0.00 | 0.00 |
Minimum of Months | 949.66 | 249.16 | 1048.92 | 620.24 | 410.56 | 0.00 | 0.00 |
Maximum of Months | 3453.05 | 1337.47 | 2498.90 | 1539.44 | 1045.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5147.80 | 2018.87 | 4442.26 | 3456.69 | 985.57 | 0.00 | 0.00 |
February | 5139.23 | 1881.57 | 4347.36 | 3175.60 | 1171.76 | 0.00 | 0.00 |
March | 3870.19 | 1551.24 | 3203.56 | 1936.75 | 1266.81 | 0.00 | 0.00 |
April | 3126.49 | 1125.07 | 2498.36 | 1025.53 | 1472.83 | 0.00 | 0.00 |
May | 2099.69 | 832.22 | 1666.20 | 366.53 | 1299.67 | 0.00 | 0.00 |
June | 2101.50 | 556.28 | 1409.47 | 173.70 | 1235.77 | 0.00 | 0.00 |
July | 2507.35 | 383.76 | 1559.65 | 249.06 | 1310.59 | 0.00 | 0.00 |
August | 3294.87 | 447.80 | 2144.63 | 697.11 | 1447.52 | 0.00 | 0.00 |
September | 4220.04 | 758.07 | 2965.56 | 1653.69 | 1311.88 | 0.00 | 0.00 |
October | 5215.31 | 1226.03 | 4057.25 | 2988.14 | 1069.11 | 0.00 | 0.00 |
November | 5394.16 | 1650.71 | 4519.00 | 3468.32 | 1050.68 | 0.00 | 0.00 |
December | 5618.87 | 2058.37 | 4819.72 | 3975.77 | 843.96 | 0.00 | 0.00 |
Annual Sum or Average | 3971.34 | 1203.99 | 3129.29 | 1924.18 | 1205.11 | 0.00 | 0.00 |
Minimum of Months | 2099.69 | 383.76 | 1409.47 | 173.70 | 843.96 | 0.00 | 0.00 |
Maximum of Months | 5618.87 | 2058.37 | 4819.72 | 3975.77 | 1472.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1118.14 | 1413.13 | 1144.27 | 652.54 | 491.73 | 0.00 | 0.00 |
February | 1533.03 | 1309.40 | 1473.06 | 850.94 | 622.12 | 0.00 | 0.00 |
March | 1807.29 | 1062.86 | 1645.24 | 875.79 | 769.45 | 0.00 | 0.00 |
April | 2461.70 | 768.44 | 2099.82 | 1117.53 | 982.28 | 0.00 | 0.00 |
May | 2476.31 | 580.43 | 1990.93 | 1025.87 | 965.06 | 0.00 | 0.00 |
June | 2983.45 | 413.06 | 2134.28 | 1190.90 | 943.37 | 0.00 | 0.00 |
July | 2810.27 | 282.00 | 1925.05 | 942.09 | 982.96 | 0.00 | 0.00 |
August | 2776.33 | 323.04 | 1967.06 | 909.85 | 1057.21 | 0.00 | 0.00 |
September | 2373.29 | 514.91 | 1776.72 | 935.73 | 840.99 | 0.00 | 0.00 |
October | 1950.54 | 848.28 | 1625.46 | 1010.28 | 615.18 | 0.00 | 0.00 |
November | 1315.75 | 1130.77 | 1275.98 | 750.69 | 525.29 | 0.00 | 0.00 |
December | 1051.01 | 1454.43 | 1103.46 | 691.99 | 411.47 | 0.00 | 0.00 |
Annual Sum or Average | 2056.54 | 839.36 | 1680.26 | 912.42 | 767.84 | 0.00 | 0.00 |
Minimum of Months | 1051.01 | 282.00 | 1103.46 | 652.54 | 411.47 | 0.00 | 0.00 |
Maximum of Months | 2983.45 | 1454.43 | 2134.28 | 1190.90 | 1057.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.261841E+09 | 0.661975E+10 | 0.160935E+10 | 0.00 | 0.160935E+10 | 0.00 | 0.00 |
February | 0.568530E+09 | 0.541628E+10 | 0.181676E+10 | 0.00 | 0.181676E+10 | 0.00 | 0.00 |
March | 0.149266E+10 | 0.471659E+10 | 0.253715E+10 | 0.00 | 0.253715E+10 | 0.00 | 0.00 |
April | 0.245953E+10 | 0.300612E+10 | 0.311502E+10 | 26669079.28 | 0.308835E+10 | 0.00 | 0.00 |
May | 0.362577E+10 | 0.219470E+10 | 0.349892E+10 | 0.225583E+09 | 0.327334E+10 | 0.00 | 0.00 |
June | 0.546150E+10 | 0.138580E+10 | 0.384746E+10 | 0.629622E+09 | 0.321784E+10 | 0.00 | 0.00 |
July | 0.560895E+10 | 0.954465E+09 | 0.364909E+10 | 0.303709E+09 | 0.334538E+10 | 0.00 | 0.00 |
August | 0.473994E+10 | 0.109164E+10 | 0.338514E+10 | 75784802.57 | 0.330935E+10 | 0.00 | 0.00 |
September | 0.311184E+10 | 0.192728E+10 | 0.261974E+10 | 672348.43 | 0.261907E+10 | 0.00 | 0.00 |
October | 0.140885E+10 | 0.366011E+10 | 0.202001E+10 | 0.00 | 0.202001E+10 | 0.00 | 0.00 |
November | 0.399060E+09 | 0.522227E+10 | 0.166013E+10 | 0.00 | 0.166013E+10 | 0.00 | 0.00 |
December | 54665246.74 | 0.715558E+10 | 0.136980E+10 | 0.00 | 0.136980E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.291931E+11 | 0.433506E+11 | 0.311286E+11 | 0.126204E+10 | 0.298665E+11 | 0.00 | 0.00 |
Minimum of Months | 54665246.74 | 0.954465E+09 | 0.136980E+10 | 0.00 | 0.136980E+10 | 0.00 | 0.00 |
Maximum of Months | 0.560895E+10 | 0.715558E+10 | 0.384746E+10 | 0.629622E+09 | 0.334538E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.249497E+10 | 0.400171E+10 | 0.297134E+10 | 0.166126E+10 | 0.131008E+10 | 0.00 | 0.00 |
February | 0.303650E+10 | 0.329503E+10 | 0.326075E+10 | 0.175790E+10 | 0.150286E+10 | 0.00 | 0.00 |
March | 0.509372E+10 | 0.287085E+10 | 0.476229E+10 | 0.270728E+10 | 0.205502E+10 | 0.00 | 0.00 |
April | 0.748601E+10 | 0.188309E+10 | 0.629638E+10 | 0.358702E+10 | 0.270937E+10 | 0.00 | 0.00 |
May | 0.783192E+10 | 0.148380E+10 | 0.620836E+10 | 0.353809E+10 | 0.267027E+10 | 0.00 | 0.00 |
June | 0.902709E+10 | 0.896027E+09 | 0.647718E+10 | 0.399025E+10 | 0.248693E+10 | 0.00 | 0.00 |
July | 0.901480E+10 | 0.600554E+09 | 0.619323E+10 | 0.354154E+10 | 0.265169E+10 | 0.00 | 0.00 |
August | 0.865155E+10 | 0.678703E+09 | 0.612862E+10 | 0.337882E+10 | 0.274979E+10 | 0.00 | 0.00 |
September | 0.656131E+10 | 0.122446E+10 | 0.493649E+10 | 0.276201E+10 | 0.217448E+10 | 0.00 | 0.00 |
October | 0.514454E+10 | 0.223343E+10 | 0.443634E+10 | 0.281469E+10 | 0.162166E+10 | 0.00 | 0.00 |
November | 0.322510E+10 | 0.316375E+10 | 0.335538E+10 | 0.197260E+10 | 0.138278E+10 | 0.00 | 0.00 |
December | 0.239078E+10 | 0.426584E+10 | 0.280943E+10 | 0.170980E+10 | 0.109964E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.699583E+11 | 0.265972E+11 | 0.578358E+11 | 0.334213E+11 | 0.244145E+11 | 0.00 | 0.00 |
Minimum of Months | 0.239078E+10 | 0.600554E+09 | 0.280943E+10 | 0.166126E+10 | 0.109964E+10 | 0.00 | 0.00 |
Maximum of Months | 0.902709E+10 | 0.426584E+10 | 0.647718E+10 | 0.399025E+10 | 0.274979E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.137030E+11 | 0.590894E+10 | 0.118978E+11 | 0.925810E+10 | 0.263969E+10 | 0.00 | 0.00 |
February | 0.123843E+11 | 0.496951E+10 | 0.105168E+11 | 0.768215E+10 | 0.283466E+10 | 0.00 | 0.00 |
March | 0.103225E+11 | 0.451421E+10 | 0.858016E+10 | 0.518721E+10 | 0.339295E+10 | 0.00 | 0.00 |
April | 0.810124E+10 | 0.312819E+10 | 0.647560E+10 | 0.265810E+10 | 0.381751E+10 | 0.00 | 0.00 |
May | 0.563630E+10 | 0.234160E+10 | 0.446267E+10 | 0.981693E+09 | 0.348098E+10 | 0.00 | 0.00 |
June | 0.545289E+10 | 0.147832E+10 | 0.365328E+10 | 0.450220E+09 | 0.320306E+10 | 0.00 | 0.00 |
July | 0.675321E+10 | 0.100667E+10 | 0.417728E+10 | 0.667063E+09 | 0.351022E+10 | 0.00 | 0.00 |
August | 0.888495E+10 | 0.118199E+10 | 0.574405E+10 | 0.186709E+10 | 0.387696E+10 | 0.00 | 0.00 |
September | 0.110256E+11 | 0.200494E+10 | 0.768653E+10 | 0.428621E+10 | 0.340032E+10 | 0.00 | 0.00 |
October | 0.140013E+11 | 0.348364E+10 | 0.108666E+11 | 0.800317E+10 | 0.286343E+10 | 0.00 | 0.00 |
November | 0.139152E+11 | 0.471489E+10 | 0.117129E+11 | 0.898959E+10 | 0.272330E+10 | 0.00 | 0.00 |
December | 0.149653E+11 | 0.616543E+10 | 0.129087E+11 | 0.106483E+11 | 0.226040E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.125146E+12 | 0.408983E+11 | 0.986824E+11 | 0.606790E+11 | 0.380035E+11 | 0.00 | 0.00 |
Minimum of Months | 0.545289E+10 | 0.100667E+10 | 0.365328E+10 | 0.450220E+09 | 0.226040E+10 | 0.00 | 0.00 |
Maximum of Months | 0.149653E+11 | 0.616543E+10 | 0.129087E+11 | 0.106483E+11 | 0.387696E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.284199E+10 | 0.446547E+10 | 0.306482E+10 | 0.174777E+10 | 0.131705E+10 | 0.00 | 0.00 |
February | 0.355167E+10 | 0.377493E+10 | 0.356364E+10 | 0.205861E+10 | 0.150503E+10 | 0.00 | 0.00 |
March | 0.466529E+10 | 0.340281E+10 | 0.440663E+10 | 0.234573E+10 | 0.206089E+10 | 0.00 | 0.00 |
April | 0.626493E+10 | 0.231918E+10 | 0.544275E+10 | 0.289666E+10 | 0.254609E+10 | 0.00 | 0.00 |
May | 0.661308E+10 | 0.168874E+10 | 0.533254E+10 | 0.274770E+10 | 0.258484E+10 | 0.00 | 0.00 |
June | 0.771408E+10 | 0.115215E+10 | 0.553207E+10 | 0.308684E+10 | 0.244523E+10 | 0.00 | 0.00 |
July | 0.749445E+10 | 0.824969E+09 | 0.515608E+10 | 0.252332E+10 | 0.263276E+10 | 0.00 | 0.00 |
August | 0.738860E+10 | 0.965681E+09 | 0.526860E+10 | 0.243694E+10 | 0.283165E+10 | 0.00 | 0.00 |
September | 0.614115E+10 | 0.144072E+10 | 0.460527E+10 | 0.242541E+10 | 0.217986E+10 | 0.00 | 0.00 |
October | 0.512716E+10 | 0.265183E+10 | 0.435364E+10 | 0.270594E+10 | 0.164769E+10 | 0.00 | 0.00 |
November | 0.322739E+10 | 0.368010E+10 | 0.330734E+10 | 0.194579E+10 | 0.136156E+10 | 0.00 | 0.00 |
December | 0.264923E+10 | 0.498349E+10 | 0.295552E+10 | 0.185343E+10 | 0.110209E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.636790E+11 | 0.313501E+11 | 0.529889E+11 | 0.287741E+11 | 0.242148E+11 | 0.00 | 0.00 |
Minimum of Months | 0.264923E+10 | 0.824969E+09 | 0.295552E+10 | 0.174777E+10 | 0.110209E+10 | 0.00 | 0.00 |
Maximum of Months | 0.771408E+10 | 0.498349E+10 | 0.553207E+10 | 0.308684E+10 | 0.283165E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.390720E+09 | 0.599523E+10 | 0.160938E+10 | 0.00 | 0.160938E+10 | 0.00 | 0.00 |
February | 0.718495E+09 | 0.490865E+10 | 0.181679E+10 | 0.00 | 0.181679E+10 | 0.00 | 0.00 |
March | 0.165056E+10 | 0.431261E+10 | 0.253719E+10 | 0.00 | 0.253719E+10 | 0.00 | 0.00 |
April | 0.256415E+10 | 0.280006E+10 | 0.311507E+10 | 26669874.63 | 0.308840E+10 | 0.00 | 0.00 |
May | 0.367599E+10 | 0.210626E+10 | 0.349897E+10 | 0.225590E+09 | 0.327338E+10 | 0.00 | 0.00 |
June | 0.549642E+10 | 0.135647E+10 | 0.384753E+10 | 0.629640E+09 | 0.321789E+10 | 0.00 | 0.00 |
July | 0.565099E+10 | 0.945012E+09 | 0.364914E+10 | 0.303718E+09 | 0.334542E+10 | 0.00 | 0.00 |
August | 0.478900E+10 | 0.106949E+10 | 0.338519E+10 | 75787062.69 | 0.330940E+10 | 0.00 | 0.00 |
September | 0.315177E+10 | 0.184412E+10 | 0.261977E+10 | 672368.48 | 0.261910E+10 | 0.00 | 0.00 |
October | 0.151212E+10 | 0.336050E+10 | 0.202004E+10 | 0.00 | 0.202004E+10 | 0.00 | 0.00 |
November | 0.531733E+09 | 0.462759E+10 | 0.166015E+10 | 0.00 | 0.166015E+10 | 0.00 | 0.00 |
December | 0.129359E+09 | 0.626410E+10 | 0.136982E+10 | 0.00 | 0.136982E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.302613E+11 | 0.395901E+11 | 0.311290E+11 | 0.126208E+10 | 0.298670E+11 | 0.00 | 0.00 |
Minimum of Months | 0.129359E+09 | 0.945012E+09 | 0.136982E+10 | 0.00 | 0.136982E+10 | 0.00 | 0.00 |
Maximum of Months | 0.565099E+10 | 0.626410E+10 | 0.384753E+10 | 0.629640E+09 | 0.334542E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.258069E+10 | 0.371124E+10 | 0.297133E+10 | 0.166125E+10 | 0.131007E+10 | 0.00 | 0.00 |
February | 0.310139E+10 | 0.307627E+10 | 0.326074E+10 | 0.175789E+10 | 0.150285E+10 | 0.00 | 0.00 |
March | 0.511368E+10 | 0.273630E+10 | 0.476227E+10 | 0.270727E+10 | 0.205501E+10 | 0.00 | 0.00 |
April | 0.745406E+10 | 0.185810E+10 | 0.629636E+10 | 0.358700E+10 | 0.270935E+10 | 0.00 | 0.00 |
May | 0.779248E+10 | 0.145973E+10 | 0.620833E+10 | 0.353808E+10 | 0.267025E+10 | 0.00 | 0.00 |
June | 0.898579E+10 | 0.909429E+09 | 0.647715E+10 | 0.399023E+10 | 0.248692E+10 | 0.00 | 0.00 |
July | 0.897002E+10 | 0.648774E+09 | 0.619320E+10 | 0.354153E+10 | 0.265168E+10 | 0.00 | 0.00 |
August | 0.860365E+10 | 0.731927E+09 | 0.612859E+10 | 0.337881E+10 | 0.274978E+10 | 0.00 | 0.00 |
September | 0.653658E+10 | 0.120683E+10 | 0.493647E+10 | 0.276200E+10 | 0.217447E+10 | 0.00 | 0.00 |
October | 0.514984E+10 | 0.214025E+10 | 0.443632E+10 | 0.281467E+10 | 0.162165E+10 | 0.00 | 0.00 |
November | 0.327325E+10 | 0.293772E+10 | 0.335536E+10 | 0.197259E+10 | 0.138277E+10 | 0.00 | 0.00 |
December | 0.245885E+10 | 0.389767E+10 | 0.280942E+10 | 0.170979E+10 | 0.109963E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.700203E+11 | 0.253142E+11 | 0.578356E+11 | 0.334211E+11 | 0.244144E+11 | 0.00 | 0.00 |
Minimum of Months | 0.245885E+10 | 0.648774E+09 | 0.280942E+10 | 0.166125E+10 | 0.109963E+10 | 0.00 | 0.00 |
Maximum of Months | 0.898579E+10 | 0.389767E+10 | 0.647715E+10 | 0.399023E+10 | 0.274978E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136385E+11 | 0.583098E+10 | 0.118982E+11 | 0.925840E+10 | 0.263975E+10 | 0.00 | 0.00 |
February | 0.123239E+11 | 0.489052E+10 | 0.105171E+11 | 0.768240E+10 | 0.283472E+10 | 0.00 | 0.00 |
March | 0.102812E+11 | 0.441050E+10 | 0.858041E+10 | 0.518738E+10 | 0.339302E+10 | 0.00 | 0.00 |
April | 0.807985E+10 | 0.304633E+10 | 0.647576E+10 | 0.265818E+10 | 0.381758E+10 | 0.00 | 0.00 |
May | 0.562712E+10 | 0.229114E+10 | 0.446276E+10 | 0.981725E+09 | 0.348103E+10 | 0.00 | 0.00 |
June | 0.548192E+10 | 0.145020E+10 | 0.365334E+10 | 0.450235E+09 | 0.320310E+10 | 0.00 | 0.00 |
July | 0.677337E+10 | 0.100562E+10 | 0.417736E+10 | 0.667085E+09 | 0.351027E+10 | 0.00 | 0.00 |
August | 0.887867E+10 | 0.118329E+10 | 0.574418E+10 | 0.186715E+10 | 0.387703E+10 | 0.00 | 0.00 |
September | 0.109627E+11 | 0.199094E+10 | 0.768674E+10 | 0.428635E+10 | 0.340039E+10 | 0.00 | 0.00 |
October | 0.139218E+11 | 0.344684E+10 | 0.108669E+11 | 0.800344E+10 | 0.286349E+10 | 0.00 | 0.00 |
November | 0.138533E+11 | 0.462102E+10 | 0.117133E+11 | 0.898989E+10 | 0.272337E+10 | 0.00 | 0.00 |
December | 0.149297E+11 | 0.597267E+10 | 0.129091E+11 | 0.106487E+11 | 0.226045E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.124752E+12 | 0.401401E+11 | 0.986851E+11 | 0.606809E+11 | 0.380042E+11 | 0.00 | 0.00 |
Minimum of Months | 0.548192E+10 | 0.100562E+10 | 0.365334E+10 | 0.450235E+09 | 0.226045E+10 | 0.00 | 0.00 |
Maximum of Months | 0.149297E+11 | 0.597267E+10 | 0.129091E+11 | 0.106487E+11 | 0.387703E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.293909E+10 | 0.405975E+10 | 0.306481E+10 | 0.174777E+10 | 0.131705E+10 | 0.00 | 0.00 |
February | 0.366228E+10 | 0.337842E+10 | 0.356362E+10 | 0.205860E+10 | 0.150502E+10 | 0.00 | 0.00 |
March | 0.479259E+10 | 0.301302E+10 | 0.440661E+10 | 0.234573E+10 | 0.206088E+10 | 0.00 | 0.00 |
April | 0.636628E+10 | 0.207068E+10 | 0.544273E+10 | 0.289665E+10 | 0.254608E+10 | 0.00 | 0.00 |
May | 0.663881E+10 | 0.159159E+10 | 0.533252E+10 | 0.274769E+10 | 0.258483E+10 | 0.00 | 0.00 |
June | 0.776060E+10 | 0.107527E+10 | 0.553204E+10 | 0.308682E+10 | 0.244522E+10 | 0.00 | 0.00 |
July | 0.756675E+10 | 0.744348E+09 | 0.515606E+10 | 0.252331E+10 | 0.263275E+10 | 0.00 | 0.00 |
August | 0.747087E+10 | 0.857062E+09 | 0.526857E+10 | 0.243693E+10 | 0.283164E+10 | 0.00 | 0.00 |
September | 0.616427E+10 | 0.135264E+10 | 0.460525E+10 | 0.242540E+10 | 0.217985E+10 | 0.00 | 0.00 |
October | 0.520334E+10 | 0.238957E+10 | 0.435362E+10 | 0.270593E+10 | 0.164769E+10 | 0.00 | 0.00 |
November | 0.335376E+10 | 0.317012E+10 | 0.330733E+10 | 0.194578E+10 | 0.136155E+10 | 0.00 | 0.00 |
December | 0.277720E+10 | 0.418496E+10 | 0.295551E+10 | 0.185342E+10 | 0.110209E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.646958E+11 | 0.278874E+11 | 0.529887E+11 | 0.287740E+11 | 0.242147E+11 | 0.00 | 0.00 |
Minimum of Months | 0.277720E+10 | 0.744348E+09 | 0.295551E+10 | 0.174777E+10 | 0.110209E+10 | 0.00 | 0.00 |
Maximum of Months | 0.776060E+10 | 0.418496E+10 | 0.553204E+10 | 0.308682E+10 | 0.283164E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.481433E+09 | 0.551380E+10 | 0.160938E+10 | 0.00 | 0.160938E+10 | 0.00 | 0.00 |
February | 0.812692E+09 | 0.453437E+10 | 0.181679E+10 | 0.00 | 0.181679E+10 | 0.00 | 0.00 |
March | 0.176277E+10 | 0.400620E+10 | 0.253719E+10 | 0.00 | 0.253719E+10 | 0.00 | 0.00 |
April | 0.261937E+10 | 0.265793E+10 | 0.311507E+10 | 26669874.63 | 0.308840E+10 | 0.00 | 0.00 |
May | 0.368621E+10 | 0.205379E+10 | 0.349897E+10 | 0.225590E+09 | 0.327338E+10 | 0.00 | 0.00 |
June | 0.545954E+10 | 0.135906E+10 | 0.384753E+10 | 0.629640E+09 | 0.321789E+10 | 0.00 | 0.00 |
July | 0.558964E+10 | 0.971991E+09 | 0.364914E+10 | 0.303718E+09 | 0.334542E+10 | 0.00 | 0.00 |
August | 0.473907E+10 | 0.108716E+10 | 0.338519E+10 | 75787062.69 | 0.330940E+10 | 0.00 | 0.00 |
September | 0.314256E+10 | 0.180880E+10 | 0.261977E+10 | 672368.48 | 0.261910E+10 | 0.00 | 0.00 |
October | 0.157348E+10 | 0.313390E+10 | 0.202004E+10 | 0.00 | 0.202004E+10 | 0.00 | 0.00 |
November | 0.637395E+09 | 0.418495E+10 | 0.166015E+10 | 0.00 | 0.166015E+10 | 0.00 | 0.00 |
December | 0.180455E+09 | 0.574667E+10 | 0.136982E+10 | 0.00 | 0.136982E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.306846E+11 | 0.370586E+11 | 0.311290E+11 | 0.126208E+10 | 0.298670E+11 | 0.00 | 0.00 |
Minimum of Months | 0.180455E+09 | 0.971991E+09 | 0.136982E+10 | 0.00 | 0.136982E+10 | 0.00 | 0.00 |
Maximum of Months | 0.558964E+10 | 0.574667E+10 | 0.384753E+10 | 0.629640E+09 | 0.334542E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.269316E+10 | 0.343012E+10 | 0.297133E+10 | 0.166125E+10 | 0.131007E+10 | 0.00 | 0.00 |
February | 0.319269E+10 | 0.285746E+10 | 0.326074E+10 | 0.175789E+10 | 0.150285E+10 | 0.00 | 0.00 |
March | 0.517907E+10 | 0.257785E+10 | 0.476227E+10 | 0.270727E+10 | 0.205501E+10 | 0.00 | 0.00 |
April | 0.746535E+10 | 0.179760E+10 | 0.629636E+10 | 0.358700E+10 | 0.270935E+10 | 0.00 | 0.00 |
May | 0.777635E+10 | 0.143633E+10 | 0.620833E+10 | 0.353808E+10 | 0.267025E+10 | 0.00 | 0.00 |
June | 0.895031E+10 | 0.913955E+09 | 0.647715E+10 | 0.399023E+10 | 0.248692E+10 | 0.00 | 0.00 |
July | 0.892514E+10 | 0.667340E+09 | 0.619320E+10 | 0.354153E+10 | 0.265168E+10 | 0.00 | 0.00 |
August | 0.856408E+10 | 0.746750E+09 | 0.612859E+10 | 0.337881E+10 | 0.274978E+10 | 0.00 | 0.00 |
September | 0.652044E+10 | 0.119592E+10 | 0.493647E+10 | 0.276200E+10 | 0.217447E+10 | 0.00 | 0.00 |
October | 0.518348E+10 | 0.203397E+10 | 0.443632E+10 | 0.281467E+10 | 0.162165E+10 | 0.00 | 0.00 |
November | 0.337314E+10 | 0.268974E+10 | 0.335536E+10 | 0.197259E+10 | 0.138277E+10 | 0.00 | 0.00 |
December | 0.254356E+10 | 0.358229E+10 | 0.280942E+10 | 0.170979E+10 | 0.109963E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.703668E+11 | 0.239293E+11 | 0.578356E+11 | 0.334211E+11 | 0.244144E+11 | 0.00 | 0.00 |
Minimum of Months | 0.254356E+10 | 0.667340E+09 | 0.280942E+10 | 0.166125E+10 | 0.109963E+10 | 0.00 | 0.00 |
Maximum of Months | 0.895031E+10 | 0.358229E+10 | 0.647715E+10 | 0.399023E+10 | 0.274978E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.137879E+11 | 0.540733E+10 | 0.118982E+11 | 0.925840E+10 | 0.263975E+10 | 0.00 | 0.00 |
February | 0.124328E+11 | 0.455189E+10 | 0.105171E+11 | 0.768240E+10 | 0.283472E+10 | 0.00 | 0.00 |
March | 0.103659E+11 | 0.415484E+10 | 0.858041E+10 | 0.518738E+10 | 0.339302E+10 | 0.00 | 0.00 |
April | 0.810386E+10 | 0.291618E+10 | 0.647576E+10 | 0.265818E+10 | 0.381758E+10 | 0.00 | 0.00 |
May | 0.562381E+10 | 0.222902E+10 | 0.446276E+10 | 0.981725E+09 | 0.348103E+10 | 0.00 | 0.00 |
June | 0.544709E+10 | 0.144188E+10 | 0.365334E+10 | 0.450235E+09 | 0.320310E+10 | 0.00 | 0.00 |
July | 0.671568E+10 | 0.102787E+10 | 0.417736E+10 | 0.667085E+09 | 0.351027E+10 | 0.00 | 0.00 |
August | 0.882497E+10 | 0.119938E+10 | 0.574418E+10 | 0.186715E+10 | 0.387703E+10 | 0.00 | 0.00 |
September | 0.109383E+11 | 0.196491E+10 | 0.768674E+10 | 0.428635E+10 | 0.340039E+10 | 0.00 | 0.00 |
October | 0.139687E+11 | 0.328380E+10 | 0.108669E+11 | 0.800344E+10 | 0.286349E+10 | 0.00 | 0.00 |
November | 0.139817E+11 | 0.427865E+10 | 0.117133E+11 | 0.898989E+10 | 0.272337E+10 | 0.00 | 0.00 |
December | 0.150496E+11 | 0.551315E+10 | 0.129091E+11 | 0.106487E+11 | 0.226045E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.125240E+12 | 0.379689E+11 | 0.986851E+11 | 0.606809E+11 | 0.380042E+11 | 0.00 | 0.00 |
Minimum of Months | 0.544709E+10 | 0.102787E+10 | 0.365334E+10 | 0.450235E+09 | 0.226045E+10 | 0.00 | 0.00 |
Maximum of Months | 0.150496E+11 | 0.551315E+10 | 0.129091E+11 | 0.106487E+11 | 0.387703E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.299484E+10 | 0.378493E+10 | 0.306481E+10 | 0.174777E+10 | 0.131705E+10 | 0.00 | 0.00 |
February | 0.370870E+10 | 0.316769E+10 | 0.356362E+10 | 0.205860E+10 | 0.150502E+10 | 0.00 | 0.00 |
March | 0.484064E+10 | 0.284676E+10 | 0.440661E+10 | 0.234573E+10 | 0.206088E+10 | 0.00 | 0.00 |
April | 0.638073E+10 | 0.199179E+10 | 0.544273E+10 | 0.289665E+10 | 0.254608E+10 | 0.00 | 0.00 |
May | 0.663255E+10 | 0.155461E+10 | 0.533252E+10 | 0.274769E+10 | 0.258483E+10 | 0.00 | 0.00 |
June | 0.773310E+10 | 0.107064E+10 | 0.553204E+10 | 0.308682E+10 | 0.244522E+10 | 0.00 | 0.00 |
July | 0.752703E+10 | 0.755302E+09 | 0.515606E+10 | 0.252331E+10 | 0.263275E+10 | 0.00 | 0.00 |
August | 0.743612E+10 | 0.865224E+09 | 0.526857E+10 | 0.243693E+10 | 0.283164E+10 | 0.00 | 0.00 |
September | 0.615157E+10 | 0.133464E+10 | 0.460525E+10 | 0.242540E+10 | 0.217985E+10 | 0.00 | 0.00 |
October | 0.522433E+10 | 0.227204E+10 | 0.435362E+10 | 0.270593E+10 | 0.164769E+10 | 0.00 | 0.00 |
November | 0.341042E+10 | 0.293097E+10 | 0.330733E+10 | 0.194578E+10 | 0.136155E+10 | 0.00 | 0.00 |
December | 0.281501E+10 | 0.389556E+10 | 0.295551E+10 | 0.185342E+10 | 0.110209E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.648550E+11 | 0.264702E+11 | 0.529887E+11 | 0.287740E+11 | 0.242147E+11 | 0.00 | 0.00 |
Minimum of Months | 0.281501E+10 | 0.755302E+09 | 0.295551E+10 | 0.174777E+10 | 0.110209E+10 | 0.00 | 0.00 |
Maximum of Months | 0.773310E+10 | 0.389556E+10 | 0.553204E+10 | 0.308682E+10 | 0.283164E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.390131E+11 | -0.379883E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102482E+10 | 58.98 | 0.00 | 0.00 |
February | 0.357125E+11 | -0.347868E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -925712008.3 | 58.99 | 0.00 | 0.00 |
March | 0.409301E+11 | -0.399036E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102649E+10 | 58.99 | 0.00 | 0.00 |
April | 0.352565E+11 | -0.342675E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988928766.7 | 58.97 | 0.00 | 0.00 |
May | 0.350661E+11 | -0.340431E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102306E+10 | 58.98 | 0.00 | 0.00 |
June | 0.323104E+11 | -0.313199E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990477644.0 | 58.98 | 0.00 | 0.00 |
July | 0.292904E+11 | -0.282727E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101774E+10 | 58.97 | 0.00 | 0.00 |
August | 0.316439E+11 | -0.306219E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102196E+10 | 58.97 | 0.00 | 0.00 |
September | 0.297251E+11 | -0.287384E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986666448.3 | 58.97 | 0.00 | 0.00 |
October | 0.326754E+11 | -0.316568E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101862E+10 | 58.98 | 0.00 | 0.00 |
November | 0.344796E+11 | -0.334933E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986357054.4 | 58.97 | 0.00 | 0.00 |
December | 0.365992E+11 | -0.355788E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102034E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.412702E+12 | -0.400671E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120312E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.292904E+11 | -0.399036E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102649E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.409301E+11 | -0.282727E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -925712008.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.50 | 0.48 | 01-JAN-07:49 | 8985.82 | 35.41 | 269.50 | 278.33 | 2171.50 | 27.32 | 198.17 | 270.67 |
February | 282.00 | 0.50 | 0.48 | 01-FEB-07:49 | 11231.19 | 37.05 | 271.33 | 270.17 | 1467.45 | 22.34 | 139.67 | 251.33 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:19 | 1834.68 | 17.25 | 10.67 | 321.17 | 1051.67 | 19.94 | 119.50 | 285.00 |
April | 381.83 | 0.51 | 0.48 | 01-APR-06:00 | 1466.51 | 17.26 | 0.00 | 342.83 | 882.96 | 20.23 | 120.50 | 309.83 |
May | 378.00 | 0.51 | 0.48 | 01-MAY-06:40 | 1125.58 | 16.51 | 0.00 | 358.83 | 695.22 | 19.54 | 56.67 | 314.17 |
June | 412.83 | 0.51 | 0.48 | 01-JUN-06:19 | 897.35 | 15.49 | 0.00 | 348.33 | 560.80 | 18.61 | 44.83 | 290.17 |
July | 395.33 | 0.51 | 0.48 | 01-JUL-06:00 | 1089.52 | 16.32 | 0.00 | 359.33 | 665.36 | 19.40 | 72.33 | 310.83 |
August | 408.83 | 0.51 | 0.48 | 01-AUG-06:40 | 1364.71 | 17.00 | 0.00 | 360.67 | 812.53 | 20.00 | 138.50 | 323.17 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-06:49 | 1811.84 | 17.67 | 16.50 | 317.83 | 981.21 | 19.92 | 110.17 | 286.33 |
October | 329.00 | 0.51 | 0.48 | 01-OCT-06:00 | 5298.94 | 27.15 | 181.17 | 310.67 | 1319.51 | 20.17 | 87.00 | 294.33 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-06:00 | 10214.51 | 36.78 | 266.00 | 276.17 | 2122.10 | 26.92 | 165.50 | 267.50 |
December | 265.67 | 0.50 | 0.48 | 01-DEC-07:49 | 10069.08 | 35.63 | 227.83 | 257.33 | 3247.09 | 30.79 | 173.83 | 255.33 |
Annual Sum or Average | 4149.83 | 0.51 | 4057.42 | 22.89 | 1243.00 | 3801.67 | 1233.08 | 21.64 | 1426.67 | 3458.67 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 897.35 | 15.49 | 0.00 | 257.33 | 560.80 | 18.61 | 44.83 | 251.33 | |
Maximum of Months | 412.83 | 0.51 | 0.48 | 11231.19 | 37.05 | 271.33 | 360.67 | 3247.09 | 30.79 | 198.17 | 323.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.52 | 0.48 | 01-JAN-07:49 | 2112.05 | 20.32 | 85.83 | 241.33 | 1230.70 | 23.37 | 108.50 | 203.33 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2663.75 | 20.32 | 74.17 | 247.83 | 1568.35 | 23.45 | 107.50 | 211.00 |
March | 351.33 | 0.51 | 0.48 | 01-MAR-06:00 | 2753.19 | 20.05 | 85.17 | 308.00 | 1390.53 | 21.67 | 103.00 | 269.33 |
April | 381.83 | 0.51 | 0.48 | 01-APR-05:00 | 4065.75 | 21.96 | 114.83 | 345.33 | 1493.73 | 22.03 | 95.67 | 321.00 |
May | 378.00 | 0.51 | 0.48 | 01-MAY-05:00 | 3113.12 | 19.54 | 80.83 | 363.00 | 1766.49 | 22.49 | 79.83 | 326.50 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-05:30 | 2945.49 | 18.71 | 83.67 | 368.67 | 1737.33 | 22.14 | 98.83 | 329.83 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-06:49 | 2999.00 | 19.61 | 84.67 | 369.17 | 1600.20 | 22.42 | 96.00 | 334.33 |
August | 408.83 | 0.51 | 0.48 | 01-AUG-05:49 | 3738.42 | 21.44 | 115.83 | 370.00 | 1417.40 | 21.89 | 92.83 | 340.17 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-06:19 | 3015.48 | 19.65 | 81.83 | 316.50 | 1771.16 | 23.20 | 112.50 | 287.67 |
October | 329.00 | 0.52 | 0.48 | 01-OCT-06:40 | 2795.36 | 19.82 | 82.67 | 280.83 | 1585.46 | 23.04 | 93.67 | 251.83 |
November | 284.17 | 0.52 | 0.48 | 01-NOV-06:49 | 2292.93 | 20.83 | 77.00 | 245.67 | 1205.26 | 22.43 | 82.83 | 214.17 |
December | 265.67 | 0.54 | 0.48 | 01-DEC-07:49 | 2452.65 | 20.54 | 80.33 | 223.17 | 1511.15 | 23.30 | 84.17 | 179.33 |
Annual Sum or Average | 4149.83 | 0.51 | 2968.99 | 20.21 | 1046.83 | 3679.50 | 1535.31 | 22.56 | 1155.33 | 3268.50 | ||
Minimum of Months | 265.67 | 0.50 | 0.48 | 2112.05 | 18.71 | 74.17 | 223.17 | 1205.26 | 21.67 | 79.83 | 179.33 | |
Maximum of Months | 412.83 | 0.54 | 0.48 | 4065.75 | 21.96 | 115.83 | 370.00 | 1771.16 | 23.45 | 112.50 | 340.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.55 | 0.48 | 01-JAN-10:20 | 499.04 | 13.18 | 0.00 | 205.83 | 323.19 | 16.73 | 0.00 | 119.00 |
February | 282.00 | 0.53 | 0.48 | 01-FEB-08:39 | 584.26 | 14.13 | 0.00 | 227.83 | 390.35 | 17.59 | 0.00 | 159.67 |
March | 351.33 | 0.52 | 0.48 | 01-MAR-07:40 | 703.73 | 15.05 | 0.00 | 296.50 | 442.59 | 18.22 | 0.00 | 228.50 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:30 | 881.33 | 16.68 | 0.00 | 355.33 | 564.97 | 19.70 | 7.00 | 324.00 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:30 | 1039.53 | 16.96 | 0.00 | 383.33 | 598.72 | 19.93 | 54.17 | 337.67 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-05:49 | 1079.03 | 18.33 | 49.33 | 393.33 | 566.53 | 19.51 | 47.67 | 359.50 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:00 | 1056.35 | 18.40 | 34.83 | 386.83 | 606.33 | 19.90 | 59.83 | 358.50 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:00 | 934.46 | 16.82 | 0.00 | 375.67 | 598.15 | 19.83 | 48.83 | 352.00 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-06:49 | 740.59 | 15.61 | 0.00 | 311.17 | 477.91 | 18.77 | 3.83 | 255.50 |
October | 329.00 | 0.54 | 0.48 | 01-OCT-07:00 | 531.36 | 13.58 | 0.00 | 254.17 | 368.75 | 17.02 | 0.00 | 183.33 |
November | 284.17 | 0.54 | 0.48 | 01-NOV-07:49 | 523.40 | 13.84 | 0.00 | 224.17 | 354.08 | 17.42 | 0.00 | 149.17 |
December | 265.67 | 0.56 | 0.48 | 01-DEC-08:39 | 431.78 | 12.27 | 0.00 | 189.83 | 304.63 | 16.02 | 0.00 | 86.17 |
Annual Sum or Average | 4149.83 | 0.52 | 781.09 | 15.67 | 84.17 | 3604.00 | 481.41 | 18.56 | 221.33 | 2913.00 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 431.78 | 12.27 | 0.00 | 189.83 | 304.63 | 16.02 | 0.00 | 86.17 | |
Maximum of Months | 412.83 | 0.56 | 0.48 | 1079.03 | 18.40 | 49.33 | 393.33 | 606.33 | 19.93 | 59.83 | 359.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.52 | 0.48 | 01-JAN-10:09 | 1614.22 | 18.44 | 57.17 | 245.83 | 927.85 | 21.80 | 93.17 | 204.83 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-08:50 | 2678.64 | 20.75 | 75.00 | 246.50 | 1522.08 | 23.77 | 105.50 | 209.00 |
March | 351.33 | 0.51 | 0.48 | 01-MAR-07:00 | 2759.27 | 19.45 | 80.67 | 308.33 | 1073.40 | 21.25 | 106.33 | 268.50 |
April | 381.83 | 0.50 | 0.48 | 01-APR-07:30 | 3636.38 | 21.32 | 110.17 | 345.83 | 1368.67 | 21.82 | 89.00 | 319.17 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:00 | 2557.22 | 17.15 | 46.50 | 374.17 | 1467.61 | 19.00 | 34.50 | 342.00 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-06:40 | 2661.07 | 13.74 | 0.00 | 363.50 | 1612.50 | 18.05 | 30.83 | 327.83 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-07:19 | 2602.57 | 14.81 | 3.67 | 369.67 | 1462.10 | 18.79 | 47.50 | 335.83 |
August | 408.83 | 0.51 | 0.48 | 01-AUG-07:10 | 2597.03 | 17.91 | 59.83 | 360.00 | 1373.24 | 19.51 | 89.50 | 332.17 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-07:19 | 2898.36 | 19.55 | 82.00 | 317.50 | 1125.94 | 21.50 | 104.83 | 288.00 |
October | 329.00 | 0.52 | 0.48 | 01-OCT-07:00 | 2667.92 | 19.74 | 82.00 | 282.50 | 1406.09 | 21.53 | 87.67 | 246.83 |
November | 284.17 | 0.51 | 0.48 | 01-NOV-07:49 | 2518.10 | 20.83 | 78.67 | 254.17 | 1603.20 | 24.47 | 101.83 | 217.00 |
December | 265.67 | 0.53 | 0.48 | 01-DEC-08:39 | 2323.66 | 20.56 | 80.17 | 229.50 | 1492.96 | 24.47 | 88.50 | 188.17 |
Annual Sum or Average | 4149.83 | 0.51 | 2652.62 | 18.46 | 755.83 | 3697.50 | 1370.65 | 21.05 | 979.17 | 3279.33 | ||
Minimum of Months | 265.67 | 0.50 | 0.48 | 1614.22 | 13.74 | 0.00 | 229.50 | 927.85 | 18.05 | 30.83 | 188.17 | |
Maximum of Months | 412.83 | 0.53 | 0.48 | 3636.38 | 21.32 | 110.17 | 374.17 | 1612.50 | 24.47 | 106.33 | 342.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.50 | 0.48 | 01-JAN-07:49 | 8977.98 | 34.50 | 269.17 | 277.67 | 2236.05 | 23.58 | 126.83 | 271.33 |
February | 282.00 | 0.49 | 0.48 | 01-FEB-07:40 | 11228.38 | 36.67 | 270.50 | 269.67 | 1668.69 | 20.43 | 78.83 | 257.50 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:10 | 1822.05 | 11.00 | 10.67 | 320.33 | 1099.42 | 15.62 | 3.50 | 286.83 |
April | 381.83 | 0.51 | 0.48 | 01-APR-06:00 | 1452.18 | 11.76 | 0.00 | 341.50 | 916.65 | 16.64 | 0.00 | 311.83 |
May | 378.00 | 0.51 | 0.48 | 01-MAY-06:40 | 1114.10 | 11.15 | 0.00 | 356.50 | 720.27 | 16.03 | 0.00 | 317.17 |
June | 412.83 | 0.52 | 0.48 | 01-JUN-06:19 | 888.96 | 9.92 | 0.00 | 345.83 | 581.38 | 14.96 | 0.00 | 295.00 |
July | 395.33 | 0.51 | 0.48 | 01-JUL-06:00 | 1076.70 | 10.81 | 0.00 | 357.50 | 688.67 | 15.76 | 0.00 | 314.33 |
August | 408.83 | 0.51 | 0.48 | 01-AUG-06:40 | 1348.65 | 11.49 | 0.00 | 358.83 | 841.52 | 16.34 | 0.00 | 325.67 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-06:49 | 1804.93 | 11.85 | 16.50 | 317.00 | 1022.86 | 15.81 | 0.00 | 288.33 |
October | 329.00 | 0.50 | 0.48 | 01-OCT-06:00 | 5339.90 | 23.75 | 181.00 | 314.83 | 1380.17 | 15.56 | 14.67 | 295.67 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-06:00 | 10208.80 | 36.16 | 265.83 | 275.50 | 2189.36 | 22.93 | 105.67 | 268.00 |
December | 265.67 | 0.50 | 0.48 | 01-DEC-07:49 | 10029.43 | 33.90 | 222.67 | 255.17 | 3324.66 | 27.49 | 146.67 | 255.33 |
Annual Sum or Average | 4149.83 | 0.51 | 4049.30 | 18.73 | 1236.33 | 3790.33 | 1285.98 | 17.95 | 476.17 | 3487.00 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 888.96 | 9.92 | 0.00 | 255.17 | 581.38 | 14.96 | 0.00 | 255.33 | |
Maximum of Months | 412.83 | 0.52 | 0.48 | 11228.38 | 36.67 | 270.50 | 358.83 | 3324.66 | 27.49 | 146.67 | 325.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.52 | 0.48 | 01-JAN-07:49 | 2116.69 | 17.59 | 85.67 | 241.50 | 1125.71 | 19.66 | 55.50 | 205.50 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2669.23 | 17.50 | 74.17 | 247.83 | 1598.83 | 21.56 | 70.50 | 215.33 |
March | 351.33 | 0.51 | 0.48 | 01-MAR-06:00 | 2768.32 | 16.86 | 85.17 | 308.00 | 1428.74 | 19.11 | 55.67 | 273.17 |
April | 381.83 | 0.51 | 0.48 | 01-APR-05:00 | 3708.33 | 16.58 | 84.83 | 344.17 | 1538.89 | 19.36 | 54.83 | 323.17 |
May | 378.00 | 0.51 | 0.48 | 01-MAY-05:00 | 3104.93 | 16.19 | 80.83 | 362.67 | 1814.63 | 19.93 | 66.33 | 329.67 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-05:30 | 2955.35 | 15.12 | 83.67 | 368.33 | 1782.37 | 19.53 | 82.50 | 333.33 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-06:40 | 3000.95 | 16.18 | 84.67 | 367.83 | 1646.66 | 19.81 | 70.33 | 337.17 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:49 | 3734.74 | 18.49 | 115.83 | 369.50 | 1459.95 | 19.25 | 59.83 | 342.00 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-06:19 | 3028.44 | 16.39 | 81.67 | 316.17 | 1809.01 | 20.92 | 80.67 | 290.33 |
October | 329.00 | 0.52 | 0.48 | 01-OCT-06:40 | 2730.54 | 16.42 | 78.67 | 281.00 | 1623.22 | 20.91 | 74.33 | 256.83 |
November | 284.17 | 0.52 | 0.48 | 01-NOV-06:49 | 1970.91 | 15.68 | 54.50 | 246.00 | 1236.97 | 20.40 | 53.33 | 217.00 |
December | 265.67 | 0.54 | 0.48 | 01-DEC-07:49 | 2462.58 | 18.15 | 80.33 | 223.17 | 1498.87 | 21.20 | 63.67 | 185.00 |
Annual Sum or Average | 4149.83 | 0.51 | 2912.72 | 16.72 | 990.00 | 3676.17 | 1562.29 | 20.06 | 787.50 | 3308.50 | ||
Minimum of Months | 265.67 | 0.50 | 0.48 | 1970.91 | 15.12 | 54.50 | 223.17 | 1125.71 | 19.11 | 53.33 | 185.00 | |
Maximum of Months | 412.83 | 0.54 | 0.48 | 3734.74 | 18.49 | 115.83 | 369.50 | 1814.63 | 21.56 | 82.50 | 342.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.55 | 0.48 | 01-JAN-10:09 | 490.79 | 7.65 | 0.00 | 203.33 | 332.83 | 12.90 | 0.00 | 132.00 |
February | 282.00 | 0.53 | 0.48 | 01-FEB-08:39 | 576.03 | 8.89 | 0.00 | 226.17 | 402.45 | 14.07 | 0.00 | 167.67 |
March | 351.33 | 0.52 | 0.48 | 01-MAR-07:40 | 694.50 | 9.84 | 0.00 | 293.67 | 457.14 | 14.84 | 0.00 | 236.50 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:30 | 870.46 | 11.94 | 0.00 | 355.33 | 582.78 | 16.88 | 0.00 | 326.17 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:30 | 1029.57 | 11.75 | 0.00 | 382.83 | 619.23 | 16.75 | 0.00 | 340.50 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-05:49 | 1072.90 | 13.32 | 48.50 | 392.17 | 587.95 | 15.95 | 0.00 | 361.67 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:00 | 1049.19 | 13.48 | 34.50 | 386.00 | 627.46 | 16.50 | 0.00 | 360.00 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:00 | 941.60 | 11.83 | 0.00 | 377.50 | 616.60 | 16.76 | 0.00 | 354.67 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-06:49 | 731.57 | 10.65 | 0.00 | 308.83 | 493.59 | 15.64 | 0.00 | 261.00 |
October | 329.00 | 0.54 | 0.48 | 01-OCT-07:49 | 526.13 | 8.55 | 0.00 | 252.33 | 381.13 | 13.72 | 0.00 | 192.33 |
November | 284.17 | 0.54 | 0.48 | 01-NOV-07:49 | 514.64 | 8.59 | 0.00 | 221.83 | 364.32 | 13.86 | 0.00 | 157.33 |
December | 265.67 | 0.56 | 0.48 | 01-DEC-08:39 | 424.89 | 7.00 | 0.00 | 186.33 | 313.53 | 12.25 | 0.00 | 102.00 |
Annual Sum or Average | 4149.83 | 0.52 | 774.42 | 10.57 | 83.00 | 3586.33 | 497.25 | 15.21 | 0.00 | 2991.83 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 424.89 | 7.00 | 0.00 | 186.33 | 313.53 | 12.25 | 0.00 | 102.00 | |
Maximum of Months | 412.83 | 0.56 | 0.48 | 1072.90 | 13.48 | 48.50 | 392.17 | 627.46 | 16.88 | 0.00 | 361.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.52 | 0.48 | 01-JAN-09:00 | 1618.15 | 15.31 | 57.00 | 245.17 | 951.69 | 19.70 | 54.17 | 210.67 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-08:39 | 2686.50 | 17.84 | 74.83 | 246.17 | 1404.13 | 19.87 | 48.33 | 212.17 |
March | 351.33 | 0.51 | 0.48 | 01-MAR-07:00 | 2770.45 | 16.26 | 79.83 | 307.50 | 1105.07 | 18.61 | 46.83 | 272.17 |
April | 381.83 | 0.50 | 0.48 | 01-APR-07:19 | 3642.18 | 18.44 | 110.00 | 344.33 | 1408.44 | 19.15 | 51.00 | 321.33 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:00 | 2552.87 | 13.37 | 46.50 | 373.83 | 1508.07 | 15.68 | 0.00 | 344.83 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-06:30 | 2668.58 | 9.06 | 0.00 | 363.50 | 1653.94 | 14.63 | 0.00 | 333.00 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-07:19 | 2598.14 | 10.35 | 3.67 | 368.83 | 1501.86 | 15.50 | 0.00 | 338.50 |
August | 408.83 | 0.51 | 0.48 | 01-AUG-07:10 | 2584.46 | 14.25 | 59.83 | 359.00 | 1409.42 | 16.33 | 5.17 | 334.67 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-07:19 | 2910.84 | 16.28 | 82.00 | 317.33 | 1163.53 | 18.89 | 51.50 | 292.00 |
October | 329.00 | 0.52 | 0.48 | 01-OCT-07:49 | 2683.67 | 16.81 | 82.00 | 282.33 | 1443.10 | 19.16 | 56.33 | 252.33 |
November | 284.17 | 0.51 | 0.48 | 01-NOV-07:49 | 2522.94 | 18.08 | 78.67 | 253.83 | 1632.78 | 22.76 | 77.33 | 220.83 |
December | 265.67 | 0.53 | 0.48 | 01-DEC-08:39 | 2333.81 | 18.13 | 80.00 | 229.33 | 1520.77 | 22.98 | 79.33 | 194.33 |
Annual Sum or Average | 4149.83 | 0.51 | 2656.92 | 15.05 | 754.33 | 3691.17 | 1395.87 | 18.27 | 470.00 | 3326.83 | ||
Minimum of Months | 265.67 | 0.50 | 0.48 | 1618.15 | 9.06 | 0.00 | 229.33 | 951.69 | 14.63 | 0.00 | 194.33 | |
Maximum of Months | 412.83 | 0.53 | 0.48 | 3642.18 | 18.44 | 110.00 | 373.83 | 1653.94 | 22.98 | 79.33 | 344.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.50 | 0.48 | 01-JAN-07:49 | 8977.10 | 34.48 | 269.17 | 277.67 | 2237.17 | 23.57 | 126.83 | 271.33 |
February | 282.00 | 0.49 | 0.48 | 01-FEB-07:40 | 11228.14 | 36.66 | 270.50 | 269.67 | 1669.91 | 20.42 | 78.83 | 257.50 |
March | 351.33 | 0.50 | 0.48 | 01-MAR-07:10 | 1822.70 | 10.96 | 10.67 | 320.17 | 1100.49 | 15.60 | 3.50 | 287.00 |
April | 381.83 | 0.51 | 0.48 | 01-APR-06:49 | 1452.62 | 11.72 | 0.00 | 341.50 | 917.48 | 16.62 | 0.00 | 312.00 |
May | 378.00 | 0.51 | 0.48 | 01-MAY-06:40 | 1114.29 | 11.11 | 0.00 | 356.50 | 720.87 | 16.01 | 0.00 | 317.17 |
June | 412.83 | 0.52 | 0.48 | 01-JUN-06:19 | 889.13 | 9.88 | 0.00 | 345.67 | 581.84 | 14.94 | 0.00 | 295.33 |
July | 395.33 | 0.51 | 0.48 | 01-JUL-06:00 | 1076.95 | 10.77 | 0.00 | 357.33 | 689.26 | 15.74 | 0.00 | 314.33 |
August | 408.83 | 0.51 | 0.48 | 01-AUG-06:40 | 1349.05 | 11.45 | 0.00 | 358.83 | 842.30 | 16.32 | 0.00 | 325.83 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-06:49 | 1805.44 | 11.81 | 16.50 | 317.00 | 1023.78 | 15.79 | 0.00 | 288.33 |
October | 329.00 | 0.50 | 0.48 | 01-OCT-06:00 | 5340.02 | 23.72 | 181.00 | 314.83 | 1381.06 | 15.54 | 14.67 | 295.67 |
November | 284.17 | 0.49 | 0.48 | 01-NOV-06:00 | 10207.93 | 36.14 | 265.83 | 275.50 | 2190.51 | 22.92 | 105.67 | 268.00 |
December | 265.67 | 0.50 | 0.48 | 01-DEC-07:49 | 10028.15 | 33.88 | 222.67 | 255.17 | 3325.62 | 27.48 | 146.67 | 255.33 |
Annual Sum or Average | 4149.83 | 0.51 | 4049.33 | 18.70 | 1236.33 | 3789.83 | 1286.83 | 17.93 | 476.17 | 3487.83 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 889.13 | 9.88 | 0.00 | 255.17 | 581.84 | 14.94 | 0.00 | 255.33 | |
Maximum of Months | 412.83 | 0.52 | 0.48 | 11228.14 | 36.66 | 270.50 | 358.83 | 3325.62 | 27.48 | 146.67 | 325.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.52 | 0.48 | 01-JAN-07:49 | 2116.38 | 17.55 | 85.67 | 241.33 | 1126.18 | 19.64 | 55.50 | 205.50 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2668.79 | 17.46 | 74.17 | 247.83 | 1599.40 | 21.55 | 70.50 | 215.33 |
March | 351.33 | 0.51 | 0.48 | 01-MAR-06:00 | 2768.04 | 16.82 | 85.17 | 308.00 | 1429.44 | 19.09 | 55.67 | 273.17 |
April | 381.83 | 0.51 | 0.48 | 01-APR-05:00 | 3707.81 | 16.53 | 84.83 | 344.17 | 1539.70 | 19.34 | 54.83 | 323.17 |
May | 378.00 | 0.51 | 0.48 | 01-MAY-05:00 | 3104.45 | 16.15 | 80.83 | 362.67 | 1815.36 | 19.91 | 66.33 | 329.67 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-05:30 | 2955.02 | 15.07 | 83.67 | 368.33 | 1782.96 | 19.51 | 82.50 | 333.17 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-06:40 | 2973.17 | 15.97 | 82.67 | 367.83 | 1647.34 | 19.80 | 70.33 | 337.33 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:49 | 3425.20 | 16.30 | 87.83 | 369.33 | 1460.71 | 19.23 | 59.83 | 342.17 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-06:19 | 3028.06 | 16.35 | 81.67 | 316.17 | 1809.70 | 20.91 | 80.67 | 290.33 |
October | 329.00 | 0.52 | 0.48 | 01-OCT-06:40 | 2730.05 | 16.38 | 78.67 | 281.00 | 1623.66 | 20.89 | 74.33 | 257.00 |
November | 284.17 | 0.52 | 0.48 | 01-NOV-06:49 | 1970.34 | 15.64 | 54.50 | 246.00 | 1237.43 | 20.38 | 53.33 | 217.00 |
December | 265.67 | 0.54 | 0.48 | 01-DEC-07:49 | 2462.11 | 18.11 | 80.33 | 223.17 | 1499.22 | 21.18 | 63.67 | 185.00 |
Annual Sum or Average | 4149.83 | 0.51 | 2879.24 | 16.45 | 960.00 | 3675.83 | 1562.91 | 20.04 | 787.50 | 3308.83 | ||
Minimum of Months | 265.67 | 0.50 | 0.48 | 1970.34 | 15.07 | 54.50 | 223.17 | 1126.18 | 19.09 | 53.33 | 185.00 | |
Maximum of Months | 412.83 | 0.54 | 0.48 | 3707.81 | 18.11 | 87.83 | 369.33 | 1815.36 | 21.55 | 82.50 | 342.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.55 | 0.48 | 01-JAN-10:09 | 490.65 | 7.61 | 0.00 | 203.00 | 333.06 | 12.88 | 0.00 | 132.00 |
February | 282.00 | 0.53 | 0.48 | 01-FEB-08:39 | 575.81 | 8.85 | 0.00 | 226.17 | 402.69 | 14.05 | 0.00 | 167.83 |
March | 351.33 | 0.52 | 0.48 | 01-MAR-07:40 | 694.46 | 9.80 | 0.00 | 293.67 | 457.50 | 14.82 | 0.00 | 236.67 |
April | 381.83 | 0.50 | 0.48 | 01-APR-06:30 | 870.26 | 11.90 | 0.00 | 355.33 | 583.18 | 16.86 | 0.00 | 326.33 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:30 | 1029.43 | 11.71 | 0.00 | 382.83 | 619.68 | 16.74 | 0.00 | 340.67 |
June | 412.83 | 0.49 | 0.48 | 01-JUN-05:49 | 1072.84 | 13.28 | 48.50 | 392.17 | 588.38 | 15.93 | 0.00 | 361.83 |
July | 395.33 | 0.49 | 0.48 | 01-JUL-06:00 | 1049.11 | 13.44 | 34.50 | 386.00 | 627.92 | 16.48 | 0.00 | 360.17 |
August | 408.83 | 0.50 | 0.48 | 01-AUG-05:00 | 941.45 | 11.78 | 0.00 | 377.50 | 617.06 | 16.74 | 0.00 | 354.67 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-06:49 | 731.43 | 10.60 | 0.00 | 308.67 | 493.94 | 15.62 | 0.00 | 261.00 |
October | 329.00 | 0.54 | 0.48 | 01-OCT-07:49 | 525.89 | 8.50 | 0.00 | 252.17 | 381.32 | 13.70 | 0.00 | 192.50 |
November | 284.17 | 0.54 | 0.48 | 01-NOV-07:49 | 514.37 | 8.54 | 0.00 | 221.83 | 364.52 | 13.84 | 0.00 | 157.83 |
December | 265.67 | 0.56 | 0.48 | 01-DEC-08:39 | 424.60 | 6.96 | 0.00 | 186.33 | 313.66 | 12.23 | 0.00 | 102.17 |
Annual Sum or Average | 4149.83 | 0.52 | 774.27 | 10.53 | 83.00 | 3585.67 | 497.59 | 15.19 | 0.00 | 2993.67 | ||
Minimum of Months | 265.67 | 0.49 | 0.48 | 424.60 | 6.96 | 0.00 | 186.33 | 313.66 | 12.23 | 0.00 | 102.17 | |
Maximum of Months | 412.83 | 0.56 | 0.48 | 1072.84 | 13.44 | 48.50 | 392.17 | 627.92 | 16.86 | 0.00 | 361.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.52 | 0.48 | 01-JAN-09:00 | 1617.80 | 15.26 | 57.00 | 245.17 | 952.17 | 19.68 | 54.17 | 210.67 |
February | 282.00 | 0.51 | 0.48 | 01-FEB-08:39 | 2686.01 | 17.80 | 74.83 | 246.17 | 1404.69 | 19.85 | 48.33 | 212.33 |
March | 351.33 | 0.51 | 0.48 | 01-MAR-07:00 | 2770.28 | 16.22 | 79.83 | 307.50 | 1105.77 | 18.59 | 46.83 | 272.33 |
April | 381.83 | 0.50 | 0.48 | 01-APR-07:19 | 3641.92 | 18.40 | 110.00 | 344.33 | 1409.17 | 19.13 | 51.00 | 321.33 |
May | 378.00 | 0.50 | 0.48 | 01-MAY-06:00 | 2552.60 | 13.32 | 46.50 | 373.83 | 1508.77 | 15.66 | 0.00 | 344.83 |
June | 412.83 | 0.50 | 0.48 | 01-JUN-06:30 | 2668.37 | 9.01 | 0.00 | 363.50 | 1654.56 | 14.60 | 0.00 | 333.17 |
July | 395.33 | 0.50 | 0.48 | 01-JUL-07:19 | 2597.97 | 10.30 | 3.67 | 368.83 | 1502.62 | 15.48 | 0.00 | 338.67 |
August | 408.83 | 0.51 | 0.48 | 01-AUG-07:10 | 2584.27 | 14.21 | 59.83 | 359.00 | 1410.30 | 16.31 | 5.17 | 335.00 |
September | 359.33 | 0.51 | 0.48 | 01-SEP-07:19 | 2910.54 | 16.23 | 82.00 | 317.33 | 1164.26 | 18.87 | 51.50 | 292.00 |
October | 329.00 | 0.52 | 0.48 | 01-OCT-07:49 | 2683.15 | 16.77 | 82.00 | 282.33 | 1443.56 | 19.14 | 56.33 | 252.33 |
November | 284.17 | 0.51 | 0.48 | 01-NOV-07:49 | 2522.44 | 18.04 | 78.67 | 253.17 | 1633.24 | 22.75 | 77.33 | 220.83 |
December | 265.67 | 0.53 | 0.48 | 01-DEC-08:39 | 2333.37 | 18.09 | 80.00 | 229.33 | 1521.10 | 22.97 | 79.33 | 194.50 |
Annual Sum or Average | 4149.83 | 0.51 | 2656.61 | 15.00 | 754.33 | 3690.50 | 1396.50 | 18.25 | 470.00 | 3328.00 | ||
Minimum of Months | 265.67 | 0.50 | 0.48 | 1617.80 | 9.01 | 0.00 | 229.33 | 952.17 | 14.60 | 0.00 | 194.50 | |
Maximum of Months | 412.83 | 0.53 | 0.48 | 3641.92 | 18.40 | 110.00 | 373.83 | 1654.56 | 22.97 | 79.33 | 344.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.590608E+10 | 25414.87 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.305017E+10 | 22771.98 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.557226E+09 | 13565.74 | 04-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30264058.54 | 5718.87 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1173737.94 | 1232.59 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.376384E+09 | 16192.22 | 26-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.672844E+09 | 15382.02 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.412407E+10 | 24684.80 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.590608E+10 | 25414.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 37117583.10 | 4568.48 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11367954.98 | 1304.72 | 06-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3071538.37 | 475.10 | 15-DEC-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51557076.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37117583.10 | 4568.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 92945427.64 | 9805.45 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26654118.68 | 2546.79 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 180432.87 | 418.52 | 04-MAR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2027301.80 | 1228.61 | 26-OCT-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 299036.21 | 221.51 | 28-NOV-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 62196017.37 | 3778.02 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 92945427.64 | 9805.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 80048788.84 | 14172.63 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26063125.49 | 12267.33 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2418848.66 | 1118.32 | 26-OCT-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28318319.07 | 7503.98 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80048788.84 | 14172.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 280308.51 | 108.86 | 19-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 280308.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 280308.51 | 108.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.919317E+11 | 275900.38 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.547029E+11 | 247978.13 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134131E+11 | 155979.01 | 04-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.199727E+10 | 97812.57 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152909E+09 | 28480.30 | 06-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.866309E+10 | 179782.32 | 26-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.211637E+11 | 210179.31 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.911367E+11 | 273254.39 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.283161E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.919317E+11 | 275900.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.184247E+11 | 121300.20 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101600E+11 | 121006.58 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174968E+10 | 120254.86 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33846879.77 | 14319.65 | 08-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.735862E+09 | 122050.03 | 27-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.385453E+10 | 120847.13 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205106E+11 | 121486.87 | 09-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.554692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.205106E+11 | 122050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111921E+11 | 143033.84 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.499159E+10 | 143172.62 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.784166E+09 | 140412.22 | 04-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15376279.53 | 9799.85 | 08-APR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.604457E+09 | 116797.55 | 26-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181329E+10 | 142097.74 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107988E+11 | 143168.28 | 15-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111921E+11 | 143172.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.471462E+10 | 151655.03 | 17-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.223815E+10 | 150995.17 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.205465E+09 | 150192.22 | 04-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223355E+09 | 117771.53 | 26-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154775E+09 | 150188.02 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.424415E+10 | 151369.60 | 09-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.471462E+10 | 151655.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.870827E+10 | 141681.88 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.448455E+10 | 141825.70 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.730299E+09 | 98608.19 | 04-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.418536E+09 | 77216.30 | 26-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125795E+10 | 140757.96 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.849963E+10 | 141829.44 | 15-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.870827E+10 | 141829.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118741E+11 | 32927.30 | 21-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.761615E+10 | 30406.48 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.255811E+10 | 20653.69 | 04-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.556232E+09 | 13981.46 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71631368.07 | 6359.74 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167955E+10 | 23119.62 | 26-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.383872E+10 | 26776.58 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.124881E+11 | 33743.39 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.406827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.124881E+11 | 33743.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.428735E+10 | 73790.94 | 30-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.204483E+10 | 73729.08 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168592E+09 | 72440.13 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72312407.87 | 71727.36 | 26-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.884859E+09 | 73295.91 | 27-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.401115E+10 | 73602.85 | 26-DEC-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.428735E+10 | 73790.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.566701E+10 | 14220.66 | 12-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.366118E+10 | 14198.02 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126576E+10 | 14160.96 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189311E+09 | 14092.93 | 24-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22771543.88 | 8633.33 | 06-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.633144E+09 | 14102.85 | 26-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.232857E+10 | 14194.65 | 13-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.608792E+10 | 14222.51 | 09-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.608792E+10 | 14222.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.295954E+10 | 16452.16 | 20-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170730E+10 | 16405.05 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.560987E+09 | 16279.43 | 04-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 55526113.62 | 9897.20 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8526694.82 | 2481.97 | 06-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.316526E+09 | 16230.91 | 26-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.979919E+09 | 16340.14 | 27-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.294886E+10 | 16351.95 | 26-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.953719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.295954E+10 | 16452.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.225695E+10 | 17146.67 | 18-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134475E+10 | 17144.86 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.574230E+09 | 17100.16 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104753E+09 | 14781.59 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29115564.49 | 5368.67 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.274210E+09 | 17058.32 | 26-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.574045E+09 | 17125.82 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203065E+10 | 17174.38 | 09-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.718870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.225695E+10 | 17174.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.266658E+10 | 17426.88 | 30-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162855E+10 | 17392.35 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.619371E+09 | 17017.80 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 67261519.69 | 8225.56 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19873861.66 | 3064.26 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1394288.02 | 504.26 | 09-JUN-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.323120E+09 | 16983.49 | 26-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.901812E+09 | 17268.55 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.259823E+10 | 17424.57 | 22-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.882619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.266658E+10 | 17426.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.874801E+09 | 0.874801E+09 | 21105.60 | 05-JAN-14:10 | 21105.60 | 0.00 |
February | 0.00 | 0.00 | 0.288684E+10 | 0.288684E+10 | 64914.31 | 14-FEB-15:50 | 64914.31 | 0.00 |
March | 0.00 | 0.00 | 0.920135E+10 | 0.920135E+10 | 71224.04 | 08-MAR-16:00 | 71224.04 | 0.00 |
April | 0.00 | 0.00 | 0.335933E+11 | 0.335933E+11 | 100858.86 | 17-APR-15:20 | 100858.86 | 0.00 |
May | 0.00 | 0.00 | 0.515670E+11 | 0.515670E+11 | 105239.26 | 30-MAY-14:30 | 105239.26 | 0.05 |
June | 0.00 | 0.00 | 0.101735E+12 | 0.101732E+12 | 140542.28 | 29-JUN-05:03 | 130936.98 | 0.27 |
July | 0.00 | 0.00 | 0.131826E+12 | 0.128217E+12 | 144602.24 | 01-JUL-05:02 | 63366.92 | 0.77 |
August | 0.00 | 0.00 | 0.129946E+12 | 0.126408E+12 | 143294.69 | 14-AUG-05:02 | 70045.10 | 0.81 |
September | 0.00 | 0.00 | 0.743874E+11 | 0.733643E+11 | 149830.61 | 05-SEP-13:10 | 90275.88 | 0.39 |
October | 0.00 | 0.00 | 0.358027E+11 | 0.357819E+11 | 104163.96 | 10-OCT-16:00 | 104163.96 | 0.09 |
November | 0.00 | 0.00 | 0.223797E+10 | 0.223797E+10 | 35243.54 | 02-NOV-15:00 | 35243.54 | 0.00 |
December | 0.00 | 0.00 | 540032.06 | 540032.06 | 2843.22 | 24-DEC-15:23 | 2843.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.574059E+12 | 0.565865E+12 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 540032.06 | 540032.06 | 2843.22 | 2843.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.131826E+12 | 0.128217E+12 | 149830.61 | 130936.98 | 0.81 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.783570E+10 | 0.783570E+10 | 174912.06 | 05-JAN-15:40 | 174912.06 | 0.00 |
February | 0.00 | 0.00 | 0.228936E+11 | 0.228936E+11 | 511185.45 | 14-FEB-16:00 | 511185.45 | 0.00 |
March | 0.00 | 0.00 | 0.680710E+11 | 0.680710E+11 | 527919.52 | 08-MAR-16:00 | 527919.52 | 0.00 |
April | 0.00 | 0.00 | 0.246290E+12 | 0.246290E+12 | 841050.45 | 26-APR-15:20 | 841050.45 | 0.00 |
May | 0.00 | 0.00 | 0.445055E+12 | 0.445055E+12 | 946872.31 | 19-MAY-15:20 | 946872.31 | 0.06 |
June | 0.00 | 0.00 | 0.866327E+12 | 0.866290E+12 | 1410138.80 | 29-JUN-05:03 | 1265054.23 | 0.24 |
July | 0.00 | 0.00 | 0.105124E+13 | 0.102797E+13 | 1332156.89 | 01-JUL-05:02 | 580074.20 | 0.62 |
August | 0.00 | 0.00 | 0.996513E+12 | 0.974056E+12 | 1353616.86 | 14-AUG-05:02 | 659295.66 | 0.63 |
September | 0.00 | 0.00 | 0.651386E+12 | 0.641929E+12 | 1279607.79 | 05-SEP-13:00 | 765628.35 | 0.37 |
October | 0.00 | 0.00 | 0.295152E+12 | 0.294984E+12 | 903699.58 | 06-OCT-15:30 | 903699.58 | 0.08 |
November | 0.00 | 0.00 | 0.160066E+11 | 0.160066E+11 | 278742.50 | 02-NOV-15:00 | 278742.50 | 0.00 |
December | 0.00 | 0.00 | 11358595.73 | 11358595.73 | 40176.06 | 24-DEC-14:43 | 40176.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.466678E+13 | 0.461139E+13 | 0.17 | |||
Minimum of Months | 0.00 | 0.00 | 11358595.73 | 11358595.73 | 40176.06 | 40176.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.105124E+13 | 0.102797E+13 | 1410138.80 | 1265054.23 | 0.63 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.394535E+09 | 0.394535E+09 | 13174.34 | 05-JAN-14:20 | 13174.34 | 0.00 |
February | 0.00 | 0.00 | 0.189525E+10 | 0.189525E+10 | 45922.81 | 14-FEB-15:50 | 45922.81 | 0.00 |
March | 0.00 | 0.00 | 0.549794E+10 | 0.549794E+10 | 53550.47 | 08-MAR-16:00 | 53550.47 | 0.00 |
April | 0.00 | 0.00 | 0.256558E+11 | 0.256558E+11 | 102498.97 | 26-APR-15:00 | 102498.97 | 0.00 |
May | 0.00 | 0.00 | 0.490399E+11 | 0.490399E+11 | 117298.38 | 19-MAY-15:20 | 117298.38 | 0.05 |
June | 0.00 | 0.00 | 0.995448E+11 | 0.995432E+11 | 148010.26 | 28-JUN-14:50 | 148010.26 | 0.24 |
July | 0.00 | 0.00 | 0.122368E+12 | 0.119757E+12 | 147247.25 | 21-JUL-14:50 | 147247.25 | 0.63 |
August | 0.00 | 0.00 | 0.113999E+12 | 0.111642E+12 | 157161.83 | 13-AUG-15:31 | 123408.60 | 0.64 |
September | 0.00 | 0.00 | 0.705042E+11 | 0.697699E+11 | 140842.54 | 05-SEP-13:30 | 88516.10 | 0.35 |
October | 0.00 | 0.00 | 0.291977E+11 | 0.291977E+11 | 103545.96 | 06-OCT-15:20 | 103545.96 | 0.08 |
November | 0.00 | 0.00 | 0.103100E+10 | 0.103100E+10 | 25157.14 | 02-NOV-15:00 | 25157.14 | 0.00 |
December | 0.00 | 0.00 | 342.12 | 342.12 | 0.39 | 16-DEC-14:30 | 0.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.519128E+12 | 0.513424E+12 | 0.17 | |||
Minimum of Months | 0.00 | 0.00 | 342.12 | 342.12 | 0.39 | 0.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.122368E+12 | 0.119757E+12 | 157161.83 | 148010.26 | 0.64 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 16995512.17 | 16995512.17 | 3114.21 | 02-JAN-15:00 | 3114.21 | 0.00 |
February | 0.00 | 0.00 | 0.123474E+10 | 0.123474E+10 | 39417.81 | 13-FEB-16:00 | 39417.81 | 0.00 |
March | 0.00 | 0.00 | 0.341121E+10 | 0.341121E+10 | 41000.58 | 08-MAR-14:00 | 41000.58 | 0.00 |
April | 0.00 | 0.00 | 0.172376E+11 | 0.172376E+11 | 57569.73 | 17-APR-15:00 | 57569.73 | 0.00 |
May | 0.00 | 0.00 | 0.303525E+11 | 0.303515E+11 | 89026.03 | 29-MAY-16:11 | 89026.03 | 0.03 |
June | 0.00 | 0.00 | 0.560556E+11 | 0.560390E+11 | 80445.61 | 29-JUN-05:03 | 74222.74 | 0.20 |
July | 0.00 | 0.00 | 0.686866E+11 | 0.672441E+11 | 121964.75 | 02-JUL-19:30 | 76498.41 | 0.50 |
August | 0.00 | 0.00 | 0.680956E+11 | 0.668576E+11 | 99526.35 | 13-AUG-18:17 | 83839.79 | 0.54 |
September | 0.00 | 0.00 | 0.461517E+11 | 0.452770E+11 | 99210.01 | 05-SEP-13:00 | 63847.11 | 0.30 |
October | 0.00 | 0.00 | 0.215095E+11 | 0.215059E+11 | 90547.77 | 01-OCT-14:24 | 90547.77 | 0.08 |
November | 0.00 | 0.00 | 0.607606E+09 | 0.607606E+09 | 23115.54 | 09-NOV-14:00 | 23115.54 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.313360E+12 | 0.309783E+12 | 0.14 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.686866E+11 | 0.672441E+11 | 121964.75 | 90547.77 | 0.54 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.456303E+10 | 0.456247E+10 | 2759.23 | 01-JAN-16:50 | 2752.50 | 0.00 |
February | 0.00 | 0.00 | 0.914176E+10 | 0.913888E+10 | 4724.55 | 15-FEB-17:00 | 4724.55 | 0.00 |
March | 0.00 | 0.00 | 0.156914E+11 | 0.156865E+11 | 7749.75 | 31-MAR-24:00 | 7749.75 | 0.00 |
April | 0.00 | 0.00 | 0.203898E+11 | 0.203890E+11 | 8909.61 | 16-APR-18:22 | 8909.61 | 0.00 |
May | 0.00 | 0.00 | 0.604297E+10 | 0.600275E+10 | 4139.19 | 31-MAY-24:00 | 4139.19 | 0.00 |
June | 0.00 | 0.00 | 0.111029E+11 | 0.110071E+11 | 6014.27 | 30-JUN-24:00 | 5981.18 | 0.00 |
July | 0.00 | 0.00 | 0.167198E+11 | 0.164950E+11 | 7884.50 | 31-JUL-23:53 | 7875.57 | 0.00 |
August | 0.00 | 0.00 | 0.216872E+11 | 0.214456E+11 | 8615.95 | 07-AUG-18:30 | 8486.59 | 0.00 |
September | 0.00 | 0.00 | 0.617214E+10 | 0.601907E+10 | 4169.71 | 30-SEP-24:00 | 4140.39 | 0.00 |
October | 0.00 | 0.00 | 0.110074E+11 | 0.109490E+11 | 5935.47 | 31-OCT-24:00 | 5935.47 | 0.00 |
November | 0.00 | 0.00 | 0.151238E+11 | 0.151126E+11 | 6767.95 | 05-NOV-16:40 | 6767.95 | 0.00 |
December | 0.00 | 0.00 | 0.203470E+11 | 0.203468E+11 | 8572.49 | 31-DEC-16:35 | 8572.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157989E+12 | 0.157155E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.456303E+10 | 0.456247E+10 | 2759.23 | 2752.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216872E+11 | 0.214456E+11 | 8909.61 | 8909.61 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.261244E+11 | 0.261184E+11 | 23273.69 | 26-JAN-17:00 | 23273.69 | 0.00 |
February | 0.00 | 0.00 | 0.735495E+11 | 0.735204E+11 | 44252.51 | 15-FEB-17:00 | 44252.51 | 0.00 |
March | 0.00 | 0.00 | 0.139600E+12 | 0.139549E+12 | 71572.41 | 31-MAR-23:40 | 71572.41 | 0.00 |
April | 0.00 | 0.00 | 0.190549E+12 | 0.190541E+12 | 83832.37 | 16-APR-17:42 | 83832.37 | 0.00 |
May | 0.00 | 0.00 | 0.539837E+11 | 0.535888E+11 | 39202.24 | 31-MAY-24:00 | 39202.24 | 0.00 |
June | 0.00 | 0.00 | 0.104467E+12 | 0.103517E+12 | 58068.54 | 30-JUN-24:00 | 57742.12 | 0.00 |
July | 0.00 | 0.00 | 0.159193E+12 | 0.156954E+12 | 76039.90 | 31-JUL-23:53 | 75951.61 | 0.00 |
August | 0.00 | 0.00 | 0.206914E+12 | 0.204503E+12 | 82348.09 | 11-AUG-18:10 | 80648.26 | 0.00 |
September | 0.00 | 0.00 | 0.559572E+11 | 0.544590E+11 | 39411.62 | 30-SEP-24:00 | 39125.62 | 0.00 |
October | 0.00 | 0.00 | 0.980070E+11 | 0.974304E+11 | 54210.36 | 31-OCT-24:00 | 54210.36 | 0.00 |
November | 0.00 | 0.00 | 0.131243E+12 | 0.131132E+12 | 62203.90 | 02-NOV-16:40 | 61336.04 | 0.00 |
December | 0.00 | 0.00 | 0.174064E+12 | 0.174063E+12 | 76426.03 | 29-DEC-16:40 | 76426.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.141365E+13 | 0.140538E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.261244E+11 | 0.261184E+11 | 23273.69 | 23273.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.206914E+12 | 0.204503E+12 | 83832.37 | 83832.37 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.972830E+09 | 0.972378E+09 | 2185.67 | 26-JAN-17:00 | 2185.67 | 0.00 |
February | 0.00 | 0.00 | 0.581139E+10 | 0.580862E+10 | 4435.15 | 15-FEB-17:00 | 4435.15 | 0.00 |
March | 0.00 | 0.00 | 0.128712E+11 | 0.128663E+11 | 6800.83 | 31-MAR-23:20 | 6800.83 | 0.00 |
April | 0.00 | 0.00 | 0.186146E+11 | 0.186138E+11 | 8389.69 | 16-APR-17:42 | 8389.69 | 0.00 |
May | 0.00 | 0.00 | 0.522189E+10 | 0.518263E+10 | 3888.40 | 31-MAY-24:00 | 3888.40 | 0.00 |
June | 0.00 | 0.00 | 0.104985E+11 | 0.104036E+11 | 5834.46 | 30-JUN-24:00 | 5801.55 | 0.00 |
July | 0.00 | 0.00 | 0.160792E+11 | 0.158554E+11 | 7607.93 | 31-JUL-23:53 | 7599.02 | 0.00 |
August | 0.00 | 0.00 | 0.208082E+11 | 0.205672E+11 | 8387.94 | 13-AUG-19:23 | 8387.94 | 0.00 |
September | 0.00 | 0.00 | 0.552014E+10 | 0.537036E+10 | 3934.03 | 30-SEP-23:40 | 3902.93 | 0.00 |
October | 0.00 | 0.00 | 0.909302E+10 | 0.903562E+10 | 5178.91 | 31-OCT-23:40 | 5178.91 | 0.00 |
November | 0.00 | 0.00 | 0.115553E+11 | 0.115443E+11 | 6205.29 | 02-NOV-16:40 | 6118.16 | 0.00 |
December | 0.00 | 0.00 | 0.153835E+11 | 0.153834E+11 | 7510.68 | 29-DEC-16:50 | 7510.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.132430E+12 | 0.131604E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.972830E+09 | 0.972378E+09 | 2185.67 | 2185.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208082E+11 | 0.205672E+11 | 8389.69 | 8389.69 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 63163.15 | 998567.03 | 24-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 40010.02 | 1006272.54 | 08-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 8580.16 | 901086.37 | 04-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1165.39 | 136334.97 | 08-APR-06:05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 110.77 | 39056.86 | 06-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.48 | 455.89 | 09-JUN-05:25 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 5306.19 | 813974.74 | 26-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14691.73 | 959104.05 | 28-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 62747.26 | 1071590.98 | 09-DEC-05:01 |
Annual Sum or Average | 0.00 | 16255.18 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 63163.15 | 1071590.98 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 8964.71 | 423828.40 | 05-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 25151.56 | 1061184.11 | 14-FEB-16:40 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 65693.85 | 1131772.04 | 08-MAR-16:20 | 0.25 | 2194.57 | 12-MAR-18:35 |
April | 205482.27 | 1177823.25 | 28-APR-14:00 | 46.01 | 101323.69 | 29-APR-00:53 |
May | 329663.20 | 1287745.47 | 23-MAY-12:30 | 302.17 | 339632.51 | 28-MAY-07:12 |
June | 564915.38 | 1527723.49 | 28-JUN-14:50 | 72.28 | 89638.65 | 14-JUN-02:42 |
July | 657685.78 | 1540165.94 | 31-JUL-15:00 | 0.44 | 4592.26 | 13-JUL-01:53 |
August | 630233.76 | 1477440.37 | 23-AUG-16:00 | 0.48 | 6456.36 | 20-AUG-03:53 |
September | 453953.84 | 1684443.15 | 05-SEP-13:10 | 80.45 | 230331.96 | 11-SEP-03:02 |
October | 222766.57 | 1360370.92 | 02-OCT-11:00 | 181.44 | 375987.88 | 01-OCT-06:53 |
November | 18306.58 | 720062.61 | 02-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2634.22 | 74653.51 | 24-DEC-15:23 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 266933.95 | 57.51 | ||||
Minimum of Months | 2634.22 | 74653.51 | 0.00 | 0.00 | ||
Maximum of Months | 657685.78 | 1684443.15 | 302.17 | 375987.88 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4843.08 | 291170.57 | 05-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 16260.38 | 854776.38 | 14-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 41296.80 | 860649.10 | 08-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 148248.89 | 1215941.84 | 28-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 249681.44 | 1351899.10 | 23-MAY-12:30 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 474792.37 | 2350507.04 | 29-JUN-05:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 558463.56 | 2784983.38 | 01-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 546282.19 | 2814204.09 | 14-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 380518.85 | 2299150.48 | 05-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 177088.53 | 1482950.91 | 02-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 10783.48 | 548060.99 | 02-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 6.77 | 59314.14 | 24-DEC-14:43 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 218611.32 | 0.00 | ||||
Minimum of Months | 6.77 | 59314.14 | 0.00 | 0.00 | ||
Maximum of Months | 558463.56 | 2814204.09 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15646.96 | 35862.33 | 26-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 46927.39 | 118007.55 | 14-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 80945.67 | 158478.81 | 08-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 128576.86 | 238672.93 | 13-APR-17:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 58705.61 | 176625.20 | 19-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 136969.42 | 321255.27 | 28-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 194361.30 | 345163.62 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 210250.26 | 344865.34 | 01-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 73064.02 | 204536.26 | 03-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 69891.78 | 200425.82 | 01-OCT-16:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 76161.21 | 113534.65 | 09-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 97614.43 | 113748.64 | 29-DEC-16:40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 99471.26 | 0.00 | ||||
Minimum of Months | 15646.96 | 35862.33 | 0.00 | 0.00 | ||
Maximum of Months | 210250.26 | 345163.62 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15593.79 | 52445.88 | 31-JAN-12:25 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 15792.92 | 52488.40 | 03-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16305.49 | 51970.47 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 14628.31 | 49723.47 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14122.48 | 46850.42 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13495.46 | 43471.19 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11972.26 | 40728.70 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 12847.81 | 40024.56 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12506.54 | 41934.99 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13235.23 | 45171.19 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14336.50 | 48453.87 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14698.30 | 51015.09 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 14118.47 | ||||
Minimum of Months | 0.00 | 0.00 | 11972.26 | 40024.56 | ||
Maximum of Months | 0.00 | 0.00 | 16305.49 | 52488.40 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3239.85 | 263486.77 | 05-JAN-15:00 | 1559.97 | 117985.43 | 25-JAN-10:50 |
February | 13286.13 | 788198.92 | 14-FEB-16:10 | 2600.35 | 129080.78 | 03-FEB-14:30 |
March | 37466.42 | 806466.80 | 08-MAR-14:00 | 2013.17 | 109137.33 | 22-MAR-11:20 |
April | 151830.92 | 1905301.56 | 17-APR-13:50 | 2302.23 | 103202.14 | 03-APR-05:40 |
May | 275475.17 | 2078143.78 | 19-MAY-15:20 | 736.62 | 89176.17 | 20-MAY-07:00 |
June | 592939.25 | 2165423.34 | 29-JUN-10:30 | 849.49 | 85714.26 | 19-JUN-05:50 |
July | 706421.31 | 2864688.88 | 31-JUL-15:00 | 156.58 | 33870.59 | 19-JUL-01:40 |
August | 680971.93 | 2398205.74 | 23-AUG-16:00 | 477.85 | 38345.49 | 16-AUG-01:55 |
September | 469307.63 | 2860103.55 | 05-SEP-13:10 | 531.21 | 89571.45 | 21-SEP-05:40 |
October | 194115.60 | 2032889.55 | 02-OCT-10:20 | 1356.61 | 112367.99 | 26-OCT-05:30 |
November | 8285.88 | 425420.35 | 02-NOV-15:10 | 1987.57 | 129741.28 | 27-NOV-06:50 |
December | 124.34 | 26442.44 | 24-DEC-15:23 | 3265.93 | 131156.39 | 14-DEC-15:20 |
Annual Sum or Average | 262671.71 | 1478.06 | ||||
Minimum of Months | 124.34 | 26442.44 | 156.58 | 33870.59 | ||
Maximum of Months | 706421.31 | 2864688.88 | 3265.93 | 131156.39 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154502E+11 | 0.97 | 10046.53 | 01-JAN-00:20 | 1.69 |
February | 0.137999E+11 | 0.96 | 10046.53 | 01-FEB-05:01 | 1.70 |
March | 0.160684E+11 | 1.01 | 10046.53 | 01-MAR-05:02 | 1.69 |
April | 0.149844E+11 | 0.98 | 10046.53 | 01-APR-04:03 | 1.70 |
May | 0.160233E+11 | 1.01 | 10046.53 | 01-MAY-03:05 | 1.68 |
June | 0.159539E+11 | 1.03 | 10046.53 | 01-JUN-03:02 | 1.68 |
July | 0.160654E+11 | 1.00 | 10046.53 | 01-JUL-03:02 | 1.67 |
August | 0.173825E+11 | 1.08 | 10046.53 | 01-AUG-03:02 | 1.68 |
September | 0.164455E+11 | 1.06 | 10046.53 | 01-SEP-03:02 | 1.67 |
October | 0.167371E+11 | 1.05 | 10046.53 | 01-OCT-14:23 | 1.68 |
November | 0.154090E+11 | 1.00 | 10046.53 | 01-NOV-03:02 | 1.69 |
December | 0.153812E+11 | 0.97 | 10046.53 | 01-DEC-04:10 | 1.69 |
Annual Sum or Average | 0.189701E+12 | 1.01 | |||
Minimum of Months | 0.137999E+11 | 0.96 | 10046.53 | 1.67 | |
Maximum of Months | 0.173825E+11 | 1.08 | 10046.53 | 1.70 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.458725E+10 | 0.39 | 10863.98 | 20-JAN-06:01 | 1.36 |
February | 0.498953E+10 | 0.42 | 11179.52 | 15-FEB-16:40 | 1.38 |
March | 0.788127E+10 | 0.53 | 12578.73 | 13-MAR-15:10 | 1.49 |
April | 0.108003E+11 | 0.67 | 16258.36 | 17-APR-15:20 | 1.74 |
May | 0.948329E+10 | 0.59 | 18404.11 | 22-MAY-05:03 | 1.87 |
June | 0.125899E+11 | 0.75 | 22534.01 | 19-JUN-05:02 | 2.14 |
July | 0.146175E+11 | 0.81 | 22534.01 | 01-JUL-05:02 | 2.12 |
August | 0.157237E+11 | 0.86 | 22534.01 | 04-AUG-05:02 | 2.12 |
September | 0.941927E+10 | 0.59 | 21623.76 | 05-SEP-05:03 | 2.06 |
October | 0.816781E+10 | 0.54 | 22534.01 | 02-OCT-05:02 | 2.12 |
November | 0.678771E+10 | 0.49 | 11922.84 | 24-NOV-16:00 | 1.44 |
December | 0.604498E+10 | 0.44 | 10630.42 | 11-DEC-06:01 | 1.34 |
Annual Sum or Average | 0.111093E+12 | 0.59 | |||
Minimum of Months | 0.458725E+10 | 0.39 | 10630.42 | 1.34 | |
Maximum of Months | 0.157237E+11 | 0.86 | 22534.01 | 2.14 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.345227E+11 | 0.38 | 52630.89 | 06-JAN-06:02 | 0.96 |
February | 0.334650E+11 | 0.39 | 101934.55 | 17-FEB-06:02 | 1.39 |
March | 0.467155E+11 | 0.43 | 98628.34 | 11-MAR-06:02 | 1.37 |
April | 0.641628E+11 | 0.50 | 126658.13 | 13-APR-15:20 | 1.60 |
May | 0.774971E+11 | 0.55 | 177076.39 | 15-MAY-05:03 | 1.97 |
June | 0.101941E+12 | 0.67 | 220619.97 | 07-JUN-05:02 | 2.25 |
July | 0.111277E+12 | 0.68 | 220619.97 | 05-JUL-05:02 | 2.25 |
August | 0.110952E+12 | 0.69 | 220619.97 | 03-AUG-05:03 | 2.24 |
September | 0.759651E+11 | 0.55 | 220619.97 | 15-SEP-05:02 | 2.25 |
October | 0.566034E+11 | 0.46 | 157441.29 | 07-OCT-05:03 | 1.82 |
November | 0.396160E+11 | 0.40 | 101308.60 | 25-NOV-06:03 | 1.39 |
December | 0.347382E+11 | 0.38 | 92722.84 | 01-DEC-06:02 | 1.32 |
Annual Sum or Average | 0.787455E+12 | 0.51 | |||
Minimum of Months | 0.334650E+11 | 0.38 | 52630.89 | 0.96 | |
Maximum of Months | 0.111277E+12 | 0.69 | 220619.97 | 2.25 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.336373E+10 | 0.38 | 4836.00 | 02-JAN-05:01 | 0.85 |
February | 0.305154E+10 | 0.37 | 6174.28 | 15-FEB-16:40 | 0.97 |
March | 0.370104E+10 | 0.38 | 6859.50 | 24-MAR-15:50 | 1.03 |
April | 0.543433E+10 | 0.43 | 14115.96 | 28-APR-14:50 | 1.58 |
May | 0.718289E+10 | 0.49 | 16062.93 | 30-MAY-14:30 | 1.71 |
June | 0.107229E+11 | 0.64 | 22898.77 | 27-JUN-15:40 | 2.13 |
July | 0.121707E+11 | 0.67 | 22898.77 | 01-JUL-05:02 | 2.12 |
August | 0.117582E+11 | 0.66 | 22850.56 | 14-AUG-05:02 | 2.11 |
September | 0.723327E+10 | 0.50 | 16911.30 | 01-SEP-05:03 | 1.75 |
October | 0.466422E+10 | 0.40 | 11496.69 | 07-OCT-05:03 | 1.38 |
November | 0.325552E+10 | 0.36 | 6046.42 | 02-NOV-16:00 | 0.95 |
December | 0.333844E+10 | 0.37 | 4836.00 | 04-DEC-05:01 | 0.85 |
Annual Sum or Average | 0.758767E+11 | 0.47 | |||
Minimum of Months | 0.305154E+10 | 0.36 | 4836.00 | 0.85 | |
Maximum of Months | 0.121707E+11 | 0.67 | 22898.77 | 2.13 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.171620E+10 | 1.12 | 640.75 | 01-JAN-00:05 | 1.11 |
February | 0.155011E+10 | 1.12 | 640.75 | 01-FEB-00:10 | 1.12 |
March | 0.171620E+10 | 1.12 | 640.75 | 01-MAR-00:10 | 1.12 |
April | 0.166084E+10 | 1.12 | 640.75 | 01-APR-00:10 | 1.12 |
May | 0.171620E+10 | 1.11 | 640.75 | 01-MAY-00:03 | 1.12 |
June | 0.166084E+10 | 1.11 | 640.75 | 01-JUN-00:10 | 1.12 |
July | 0.171620E+10 | 1.11 | 640.75 | 01-JUL-00:10 | 1.11 |
August | 0.171620E+10 | 1.11 | 640.75 | 01-AUG-00:03 | 1.11 |
September | 0.166084E+10 | 1.11 | 640.75 | 01-SEP-00:05 | 1.11 |
October | 0.171620E+10 | 1.11 | 640.75 | 01-OCT-00:10 | 1.11 |
November | 0.166084E+10 | 1.12 | 640.75 | 01-NOV-00:10 | 1.12 |
December | 0.171620E+10 | 1.12 | 640.75 | 01-DEC-00:10 | 1.12 |
Annual Sum or Average | 0.202068E+11 | 1.11 | |||
Minimum of Months | 0.155011E+10 | 1.11 | 640.75 | 1.11 | |
Maximum of Months | 0.171620E+10 | 1.12 | 640.75 | 1.12 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.163900E+11 | 1.12 | 6119.32 | 01-JAN-00:10 | 1.11 |
February | 0.148039E+11 | 1.12 | 6119.32 | 01-FEB-00:10 | 1.12 |
March | 0.163900E+11 | 1.12 | 6119.32 | 01-MAR-00:10 | 1.12 |
April | 0.158613E+11 | 1.12 | 6119.32 | 01-APR-00:10 | 1.12 |
May | 0.163900E+11 | 1.11 | 6119.32 | 01-MAY-00:07 | 1.12 |
June | 0.158613E+11 | 1.11 | 6119.32 | 01-JUN-00:10 | 1.12 |
July | 0.163900E+11 | 1.11 | 6119.32 | 01-JUL-00:10 | 1.11 |
August | 0.163900E+11 | 1.11 | 6119.32 | 01-AUG-00:03 | 1.11 |
September | 0.158613E+11 | 1.11 | 6119.32 | 01-SEP-00:05 | 1.11 |
October | 0.163900E+11 | 1.11 | 6119.32 | 01-OCT-00:10 | 1.11 |
November | 0.158613E+11 | 1.12 | 6119.32 | 01-NOV-00:10 | 1.12 |
December | 0.163900E+11 | 1.12 | 6119.32 | 01-DEC-00:10 | 1.12 |
Annual Sum or Average | 0.192979E+12 | 1.11 | |||
Minimum of Months | 0.148039E+11 | 1.11 | 6119.32 | 1.11 | |
Maximum of Months | 0.163900E+11 | 1.12 | 6119.32 | 1.12 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.167558E+10 | 1.12 | 625.59 | 01-JAN-00:05 | 1.11 |
February | 0.151343E+10 | 1.12 | 625.59 | 01-FEB-00:10 | 1.12 |
March | 0.167558E+10 | 1.12 | 625.59 | 01-MAR-00:10 | 1.12 |
April | 0.162153E+10 | 1.12 | 625.59 | 01-APR-00:10 | 1.12 |
May | 0.167558E+10 | 1.11 | 625.59 | 01-MAY-00:03 | 1.12 |
June | 0.162153E+10 | 1.11 | 625.59 | 01-JUN-00:10 | 1.12 |
July | 0.167558E+10 | 1.11 | 625.59 | 01-JUL-00:10 | 1.11 |
August | 0.167558E+10 | 1.11 | 625.59 | 01-AUG-00:03 | 1.11 |
September | 0.162153E+10 | 1.11 | 625.59 | 01-SEP-00:05 | 1.11 |
October | 0.167558E+10 | 1.11 | 625.59 | 01-OCT-00:10 | 1.11 |
November | 0.162153E+10 | 1.12 | 625.59 | 01-NOV-00:10 | 1.12 |
December | 0.167558E+10 | 1.12 | 625.59 | 01-DEC-00:10 | 1.12 |
Annual Sum or Average | 0.197286E+11 | 1.11 | |||
Minimum of Months | 0.151343E+10 | 1.11 | 625.59 | 1.11 | |
Maximum of Months | 0.167558E+10 | 1.12 | 625.59 | 1.12 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.732010E+09 | 0.665397E+09 | 3292.58 | 20-JAN-06:01 | 2992.95 | 2992.95 | 39.96 | 5.36 |
February | 0.417252E+09 | 0.379282E+09 | 3272.09 | 08-FEB-06:01 | 2974.33 | 2974.33 | 35.63 | 5.30 |
March | 96814124.70 | 88004039.35 | 3124.83 | 04-MAR-06:02 | 2840.47 | 2840.47 | 37.15 | 4.88 |
April | 12581463.08 | 11436549.94 | 554.82 | 08-APR-06:10 | 504.33 | 504.33 | 26.72 | 0.60 |
May | 1207086.10 | 1097241.27 | 157.04 | 06-MAY-06:10 | 142.75 | 142.75 | 23.10 | 0.16 |
June | 5085.73 | 4622.93 | 1.86 | 09-JUN-05:25 | 1.69 | 1.69 | 22.76 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 22.73 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 22.73 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 22.73 | 0.00 |
October | 59887448.89 | 54437691.04 | 2936.60 | 26-OCT-05:03 | 2669.37 | 2669.37 | 37.13 | 4.39 |
November | 0.162714E+09 | 0.147907E+09 | 3238.01 | 27-NOV-06:01 | 2943.35 | 2943.35 | 37.99 | 5.20 |
December | 0.725156E+09 | 0.659166E+09 | 3277.97 | 11-DEC-06:01 | 2979.67 | 2979.67 | 37.49 | 5.32 |
Annual Sum or Average | 0.220763E+10 | 0.200673E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.73 | 0.00 | |
Maximum of Months | 0.732010E+09 | 0.665397E+09 | 3292.58 | 2992.95 | 2992.95 | 39.96 | 5.36 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 4806123.71 | 4368766.45 | 148.16 | 05-JAN-14:30 | 134.68 | 134.68 | 8.88 | 9.84 |
February | 29541168.62 | 26852922.27 | 1057.11 | 14-FEB-15:50 | 960.92 | 960.92 | 8.76 | 26.41 |
March | 52332252.71 | 47570017.71 | 1003.62 | 08-MAR-14:00 | 912.29 | 912.29 | 7.85 | 25.78 |
April | 0.225165E+09 | 0.204675E+09 | 1691.71 | 28-APR-13:40 | 1537.77 | 1537.77 | 7.38 | 32.71 |
May | 0.486061E+09 | 0.441829E+09 | 6382.53 | 23-MAY-12:30 | 5801.72 | 5801.72 | 7.21 | 57.82 |
June | 0.202167E+10 | 0.183770E+10 | 16960.44 | 29-JUN-05:03 | 15417.04 | 15417.04 | 7.43 | 85.67 |
July | 0.228161E+10 | 0.207399E+10 | 18001.94 | 01-JUL-05:02 | 16363.76 | 16363.76 | 8.30 | 87.71 |
August | 0.254748E+10 | 0.231566E+10 | 18001.94 | 14-AUG-05:02 | 16363.76 | 16363.76 | 8.31 | 87.71 |
September | 0.227164E+10 | 0.206492E+10 | 17344.79 | 05-SEP-05:03 | 15766.42 | 15766.42 | 8.93 | 86.43 |
October | 0.794719E+09 | 0.722400E+09 | 11487.28 | 02-OCT-11:00 | 10441.94 | 10441.94 | 7.31 | 73.41 |
November | 11737969.16 | 10669813.97 | 547.97 | 02-NOV-15:00 | 498.10 | 498.10 | 9.12 | 19.33 |
December | 4035.45 | 3668.22 | 14.19 | 24-DEC-14:43 | 12.90 | 12.90 | 8.55 | 2.22 |
Annual Sum or Average | 0.107268E+11 | 0.975063E+10 | ||||||
Minimum of Months | 4035.45 | 3668.22 | 14.19 | 12.90 | 12.90 | 7.21 | 2.22 | |
Maximum of Months | 0.254748E+10 | 0.231566E+10 | 18001.94 | 16363.76 | 16363.76 | 9.12 | 87.71 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.316148E+10 | 0.287379E+10 | 12390.25 | 01-JAN-12:22 | 11262.74 | 11262.74 | 8.44 | 87.71 |
February | 0.458624E+10 | 0.416889E+10 | 12390.25 | 01-FEB-13:00 | 11262.74 | 11262.74 | 8.43 | 87.71 |
March | 0.722091E+10 | 0.656381E+10 | 12390.25 | 01-MAR-16:30 | 11262.74 | 11262.74 | 8.46 | 87.71 |
April | 0.132085E+11 | 0.120066E+11 | 12390.25 | 01-APR-04:03 | 11262.74 | 11262.74 | 8.69 | 87.71 |
May | 0.169960E+11 | 0.154494E+11 | 12390.25 | 01-MAY-03:05 | 11262.74 | 11262.74 | 8.45 | 87.71 |
June | 0.245753E+11 | 0.223390E+11 | 12390.25 | 01-JUN-03:02 | 11262.74 | 11262.74 | 8.58 | 87.71 |
July | 0.292091E+11 | 0.265510E+11 | 12390.25 | 01-JUL-00:12 | 11262.74 | 11262.74 | 7.49 | 87.71 |
August | 0.297528E+11 | 0.270453E+11 | 12390.25 | 01-AUG-00:13 | 11262.74 | 11262.74 | 7.75 | 87.71 |
September | 0.206638E+11 | 0.187834E+11 | 12390.25 | 01-SEP-00:05 | 11262.74 | 11262.74 | 7.61 | 87.71 |
October | 0.136050E+11 | 0.123669E+11 | 12390.25 | 01-OCT-06:53 | 11262.74 | 11262.74 | 7.35 | 87.71 |
November | 0.420479E+10 | 0.382215E+10 | 12390.25 | 01-NOV-09:40 | 11262.74 | 11262.74 | 8.46 | 87.71 |
December | 0.389546E+10 | 0.354097E+10 | 12390.25 | 01-DEC-06:02 | 11262.74 | 11262.74 | 8.53 | 87.71 |
Annual Sum or Average | 0.171079E+12 | 0.155511E+12 | ||||||
Minimum of Months | 0.316148E+10 | 0.287379E+10 | 12390.25 | 11262.74 | 11262.74 | 7.35 | 87.71 | |
Maximum of Months | 0.297528E+11 | 0.270453E+11 | 12390.25 | 11262.74 | 11262.74 | 8.69 | 87.71 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.194939E+10 | 0.177199E+10 | 727.82 | 01-JAN-00:05 | 661.59 | 661.59 | 19.82 | 3.07 |
February | 0.176074E+10 | 0.160051E+10 | 727.82 | 01-FEB-00:10 | 661.59 | 661.59 | 22.04 | 3.07 |
March | 0.194939E+10 | 0.177199E+10 | 727.82 | 01-MAR-00:10 | 661.59 | 661.59 | 25.07 | 3.07 |
April | 0.188650E+10 | 0.171483E+10 | 727.82 | 01-APR-00:10 | 661.59 | 661.59 | 28.27 | 3.07 |
May | 0.194939E+10 | 0.177199E+10 | 727.82 | 01-MAY-00:03 | 661.59 | 661.59 | 21.51 | 3.07 |
June | 0.188650E+10 | 0.171483E+10 | 727.82 | 01-JUN-00:10 | 661.59 | 661.59 | 25.29 | 3.07 |
July | 0.194939E+10 | 0.177199E+10 | 727.82 | 01-JUL-00:10 | 661.59 | 661.59 | 32.16 | 3.07 |
August | 0.194939E+10 | 0.177199E+10 | 727.82 | 01-AUG-00:03 | 661.59 | 661.59 | 34.14 | 3.07 |
September | 0.188650E+10 | 0.171483E+10 | 727.82 | 01-SEP-00:05 | 661.59 | 661.59 | 25.97 | 3.07 |
October | 0.194939E+10 | 0.177199E+10 | 727.82 | 01-OCT-00:10 | 661.59 | 661.59 | 24.14 | 3.07 |
November | 0.188650E+10 | 0.171483E+10 | 727.82 | 01-NOV-00:10 | 661.59 | 661.59 | 25.94 | 3.07 |
December | 0.194939E+10 | 0.177199E+10 | 727.82 | 01-DEC-00:10 | 661.59 | 661.59 | 27.54 | 3.07 |
Annual Sum or Average | 0.229524E+11 | 0.208638E+11 | ||||||
Minimum of Months | 0.176074E+10 | 0.160051E+10 | 727.82 | 661.59 | 661.59 | 19.82 | 3.07 | |
Maximum of Months | 0.194939E+10 | 0.177199E+10 | 727.82 | 661.59 | 661.59 | 34.14 | 3.07 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:05 | 1.79 | 1.79 | 55.66 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:01 | 1.79 | 1.79 | 55.85 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:02 | 1.79 | 1.79 | 56.55 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:03 | 1.79 | 1.79 | 56.32 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:03 | 1.79 | 1.79 | 55.93 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:02 | 1.79 | 1.79 | 56.49 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:02 | 1.79 | 1.79 | 56.37 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:03 | 1.79 | 1.79 | 56.74 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 56.21 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 56.10 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:03 | 1.79 | 1.79 | 56.86 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:02 | 1.79 | 1.79 | 56.34 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.66 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 56.86 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.401141E+10 | 0.364637E+10 | 15733.77 | 05-JAN-15:00 | 14302.00 | 14302.00 | 22.29 | 52.89 |
February | 0.584847E+10 | 0.531626E+10 | 31476.81 | 14-FEB-16:40 | 28612.42 | 28612.42 | 22.69 | 105.79 |
March | 0.919950E+10 | 0.836235E+10 | 31478.79 | 08-MAR-16:20 | 28614.22 | 28614.22 | 22.78 | 105.79 |
April | 0.182506E+11 | 0.165898E+11 | 31539.85 | 17-APR-13:50 | 28669.72 | 28669.72 | 25.41 | 105.79 |
May | 0.248120E+11 | 0.225541E+11 | 31550.18 | 19-MAY-15:20 | 28679.11 | 28679.11 | 25.80 | 105.79 |
June | 0.404576E+11 | 0.367759E+11 | 31555.40 | 29-JUN-10:30 | 28683.86 | 28683.86 | 26.00 | 105.79 |
July | 0.492106E+11 | 0.447325E+11 | 31597.29 | 31-JUL-15:00 | 28721.94 | 28721.94 | 27.58 | 105.79 |
August | 0.496074E+11 | 0.450931E+11 | 31569.33 | 23-AUG-16:00 | 28696.52 | 28696.52 | 26.52 | 105.79 |
September | 0.331554E+11 | 0.301382E+11 | 31597.01 | 05-SEP-13:10 | 28721.69 | 28721.69 | 27.57 | 105.79 |
October | 0.193742E+11 | 0.176111E+11 | 31547.47 | 02-OCT-10:20 | 28676.65 | 28676.65 | 25.70 | 105.79 |
November | 0.533572E+10 | 0.485017E+10 | 15742.07 | 02-NOV-15:10 | 14309.54 | 14309.54 | 23.02 | 52.89 |
December | 0.494199E+10 | 0.449227E+10 | 15721.65 | 24-DEC-15:23 | 14290.98 | 14290.98 | 21.22 | 52.89 |
Annual Sum or Average | 0.264205E+12 | 0.240162E+12 | ||||||
Minimum of Months | 0.401141E+10 | 0.364637E+10 | 15721.65 | 14290.98 | 14290.98 | 21.22 | 52.89 | |
Maximum of Months | 0.496074E+11 | 0.450931E+11 | 31597.29 | 28721.94 | 28721.94 | 27.58 | 105.79 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.40 | 57.40 | 63163.15 | 998567.03 | 24-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 32.58 | 32.58 | 40010.02 | 1006272.54 | 08-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.28 | 25.28 | 8580.16 | 901086.37 | 04-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 24.58 | 24.58 | 1165.39 | 136334.97 | 08-APR-06:05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 24.18 | 24.18 | 110.77 | 39056.86 | 06-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.76 | 22.76 | 0.48 | 455.89 | 09-JUN-05:25 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.73 | 22.73 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 22.73 | 22.73 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.73 | 22.73 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.73 | 22.73 | 5306.19 | 813974.74 | 26-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.33 | 25.33 | 14691.73 | 959104.05 | 28-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.97 | 23.97 | 62747.26 | 1071590.98 | 09-DEC-05:01 |
Annual Sum or Average | 0.00 | 16255.18 | ||||||
Minimum of Months | 0.00 | 0.00 | 22.73 | 22.73 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 57.40 | 57.40 | 63163.15 | 1071590.98 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 8964.71 | 423828.40 | 05-JAN-15:00 | 9.45 | 8.87 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 25151.56 | 1061184.11 | 14-FEB-16:40 | 10.37 | 8.91 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 65693.85 | 1131772.04 | 08-MAR-16:20 | 10.40 | 8.73 | 0.25 | 2194.57 | 12-MAR-18:35 |
April | 205482.27 | 1177823.25 | 28-APR-14:00 | 10.25 | 7.05 | 46.01 | 101323.69 | 29-APR-00:53 |
May | 329663.20 | 1287745.47 | 23-MAY-12:30 | 10.50 | 7.00 | 302.17 | 339632.51 | 28-MAY-07:12 |
June | 564915.38 | 1527723.49 | 28-JUN-14:50 | 10.86 | 6.70 | 72.28 | 89638.65 | 14-JUN-02:42 |
July | 657685.78 | 1540165.94 | 31-JUL-15:00 | 10.89 | 6.70 | 0.44 | 4592.26 | 13-JUL-01:53 |
August | 630233.76 | 1477440.37 | 23-AUG-16:00 | 11.23 | 7.21 | 0.48 | 6456.36 | 20-AUG-03:53 |
September | 453953.84 | 1684443.15 | 05-SEP-13:10 | 11.69 | 7.11 | 80.45 | 230331.96 | 11-SEP-03:02 |
October | 222766.57 | 1360370.92 | 02-OCT-11:00 | 10.82 | 7.12 | 181.44 | 375987.88 | 01-OCT-06:53 |
November | 18306.58 | 720062.61 | 02-NOV-15:00 | 10.09 | 9.10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2634.22 | 74653.51 | 24-DEC-15:23 | 8.57 | 8.47 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 266933.95 | 57.51 | ||||||
Minimum of Months | 2634.22 | 74653.51 | 8.57 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 657685.78 | 1684443.15 | 11.69 | 9.10 | 302.17 | 375987.88 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4843.08 | 291170.57 | 05-JAN-15:00 | 13.79 | 8.87 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 16260.38 | 854776.38 | 14-FEB-16:00 | 14.49 | 8.75 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 41296.80 | 860649.10 | 08-MAR-14:00 | 14.68 | 8.34 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 148248.89 | 1215941.84 | 28-APR-14:00 | 15.65 | 7.05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 249681.44 | 1351899.10 | 23-MAY-12:30 | 12.28 | 8.27 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 474792.37 | 2350507.04 | 29-JUN-05:03 | 13.25 | 7.12 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 558463.56 | 2784983.38 | 01-JUL-05:02 | 14.29 | 8.17 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 546282.19 | 2814204.09 | 14-AUG-05:02 | 14.37 | 8.12 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 380518.85 | 2299150.48 | 05-SEP-05:03 | 13.05 | 9.21 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 177088.53 | 1482950.91 | 02-OCT-11:00 | 11.52 | 7.13 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 10783.48 | 548060.99 | 02-NOV-15:00 | 13.47 | 9.12 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 6.77 | 59314.14 | 24-DEC-14:43 | 13.07 | 8.43 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 218611.32 | 0.00 | ||||||
Minimum of Months | 6.77 | 59314.14 | 11.52 | 7.05 | 0.00 | 0.00 | ||
Maximum of Months | 558463.56 | 2814204.09 | 15.65 | 9.21 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15646.96 | 35862.33 | 26-JAN-17:00 | 21.69 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 46927.39 | 118007.55 | 14-FEB-16:00 | 29.31 | 23.49 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 80945.67 | 158478.81 | 08-MAR-16:00 | 33.03 | 24.67 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 128576.86 | 238672.93 | 13-APR-17:00 | 40.32 | 28.72 | 0.00 | 0.00 | 01-APR-00:10 |
May | 58705.61 | 176625.20 | 19-MAY-16:00 | 34.69 | 30.86 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 136969.42 | 321255.27 | 28-JUN-16:00 | 47.71 | 40.55 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 194361.30 | 345163.62 | 22-JUL-15:00 | 49.84 | 40.46 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 210250.26 | 344865.34 | 01-AUG-16:00 | 49.81 | 37.77 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 73064.02 | 204536.26 | 03-SEP-14:00 | 37.23 | 33.61 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 69891.78 | 200425.82 | 01-OCT-16:00 | 36.85 | 30.36 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 76161.21 | 113534.65 | 09-NOV-14:00 | 28.90 | 21.12 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 97614.43 | 113748.64 | 29-DEC-16:40 | 28.92 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 99471.26 | 0.00 | ||||||
Minimum of Months | 15646.96 | 35862.33 | 21.69 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 210250.26 | 345163.62 | 49.84 | 40.55 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.62 | 57.62 | 15593.79 | 52445.88 | 31-JAN-12:25 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.34 | 56.34 | 15792.92 | 52488.40 | 03-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.07 | 57.07 | 16305.49 | 51970.47 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.93 | 56.93 | 14628.31 | 49723.47 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 56.69 | 56.69 | 14122.48 | 46850.42 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.97 | 56.97 | 13495.46 | 43471.19 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.77 | 56.77 | 11972.26 | 40728.70 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.18 | 57.18 | 12847.81 | 40024.56 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 56.83 | 56.83 | 12506.54 | 41934.99 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.02 | 57.02 | 13235.23 | 45171.19 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.36 | 57.36 | 14336.50 | 48453.87 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.90 | 56.90 | 14698.30 | 51015.09 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 14118.47 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.34 | 56.34 | 11972.26 | 40024.56 | ||
Maximum of Months | 0.00 | 0.00 | 57.62 | 57.62 | 16305.49 | 52488.40 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3239.85 | 263486.77 | 05-JAN-15:00 | 22.29 | 21.10 | 1559.97 | 117985.43 | 25-JAN-10:50 |
February | 13286.13 | 788198.92 | 14-FEB-16:10 | 24.67 | 21.10 | 2600.35 | 129080.78 | 03-FEB-14:30 |
March | 37466.42 | 806466.80 | 08-MAR-14:00 | 24.75 | 21.10 | 2013.17 | 109137.33 | 22-MAR-11:20 |
April | 151830.92 | 1905301.56 | 17-APR-13:50 | 25.41 | 21.10 | 2302.23 | 103202.14 | 03-APR-05:40 |
May | 275475.17 | 2078143.78 | 19-MAY-15:20 | 25.80 | 21.10 | 736.62 | 89176.17 | 20-MAY-07:00 |
June | 592939.25 | 2165423.34 | 29-JUN-10:30 | 26.00 | 21.86 | 849.49 | 85714.26 | 19-JUN-05:50 |
July | 706421.31 | 2864688.88 | 31-JUL-15:00 | 27.58 | 23.54 | 156.58 | 33870.59 | 19-JUL-01:40 |
August | 680971.93 | 2398205.74 | 23-AUG-16:00 | 26.52 | 22.66 | 477.85 | 38345.49 | 16-AUG-01:55 |
September | 469307.63 | 2860103.55 | 05-SEP-13:10 | 27.57 | 23.12 | 531.21 | 89571.45 | 21-SEP-05:40 |
October | 194115.60 | 2032889.55 | 02-OCT-10:20 | 25.70 | 21.10 | 1356.61 | 112367.99 | 26-OCT-05:30 |
November | 8285.88 | 425420.35 | 02-NOV-15:10 | 23.02 | 21.10 | 1987.57 | 129741.28 | 27-NOV-06:50 |
December | 124.34 | 26442.44 | 24-DEC-15:23 | 21.22 | 20.44 | 3265.93 | 131156.39 | 14-DEC-15:20 |
Annual Sum or Average | 262671.71 | 1478.06 | ||||||
Minimum of Months | 124.34 | 26442.44 | 21.22 | 20.44 | 156.58 | 33870.59 | ||
Maximum of Months | 706421.31 | 2864688.88 | 27.58 | 23.54 | 3265.93 | 131156.39 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.611647E+10 | 0.00 | 0.874801E+09 | 0.458725E+10 | 0.00 | 0.00 |
February | 0.311425E+10 | 0.00 | 0.288684E+10 | 0.498953E+10 | 0.00 | 0.00 |
March | 0.557406E+09 | 0.00 | 0.920135E+10 | 0.788127E+10 | 0.00 | 0.00 |
April | 30264058.54 | 0.00 | 0.335933E+11 | 0.108003E+11 | 0.00 | 0.00 |
May | 1173737.94 | 0.00 | 0.515670E+11 | 0.948329E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.101735E+12 | 0.125899E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.131826E+12 | 0.146175E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.129946E+12 | 0.157237E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.743874E+11 | 0.941927E+10 | 0.00 | 0.00 |
October | 0.380830E+09 | 0.00 | 0.358027E+11 | 0.816781E+10 | 0.00 | 0.00 |
November | 0.673143E+09 | 0.00 | 0.223797E+10 | 0.678771E+10 | 0.00 | 0.00 |
December | 0.421766E+10 | 0.00 | 540032.06 | 0.604498E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150912E+11 | 0.00 | 0.574059E+12 | 0.111093E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 540032.06 | 0.458725E+10 | 0.00 | 0.00 |
Maximum of Months | 0.611647E+10 | 0.00 | 0.131826E+12 | 0.157237E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.134971E+12 | 0.00 | 0.783570E+10 | 0.345227E+11 | 0.00 | 0.00 |
February | 0.765772E+11 | 0.00 | 0.228936E+11 | 0.334650E+11 | 0.00 | 0.00 |
March | 0.168827E+11 | 0.00 | 0.680710E+11 | 0.467155E+11 | 0.00 | 0.00 |
April | 0.204649E+10 | 0.00 | 0.246290E+12 | 0.641628E+11 | 0.00 | 0.00 |
May | 0.152909E+09 | 0.00 | 0.445055E+12 | 0.774971E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.866327E+12 | 0.101941E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.105124E+13 | 0.111277E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.996513E+12 | 0.110952E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.651386E+12 | 0.759651E+11 | 0.00 | 0.00 |
October | 0.106453E+11 | 0.00 | 0.295152E+12 | 0.566034E+11 | 0.00 | 0.00 |
November | 0.282442E+11 | 0.00 | 0.160066E+11 | 0.396160E+11 | 0.00 | 0.00 |
December | 0.135190E+12 | 0.00 | 11358595.73 | 0.347382E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.404710E+12 | 0.00 | 0.466678E+13 | 0.787455E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 11358595.73 | 0.334650E+11 | 0.00 | 0.00 |
Maximum of Months | 0.135190E+12 | 0.00 | 0.105124E+13 | 0.111277E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.297115E+11 | 0.00 | 0.394535E+09 | 0.336373E+10 | 0.00 | 0.00 |
February | 0.180028E+11 | 0.00 | 0.189525E+10 | 0.305154E+10 | 0.00 | 0.00 |
March | 0.574705E+10 | 0.00 | 0.549794E+10 | 0.370104E+10 | 0.00 | 0.00 |
April | 0.973084E+09 | 0.00 | 0.256558E+11 | 0.543433E+10 | 0.00 | 0.00 |
May | 0.151919E+09 | 0.00 | 0.490399E+11 | 0.718289E+10 | 0.00 | 0.00 |
June | 1394288.02 | 0.00 | 0.995448E+11 | 0.107229E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.122368E+12 | 0.121707E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.113999E+12 | 0.117582E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.705042E+11 | 0.723327E+10 | 0.00 | 0.00 |
October | 0.329886E+10 | 0.00 | 0.291977E+11 | 0.466422E+10 | 0.00 | 0.00 |
November | 0.950793E+10 | 0.00 | 0.103100E+10 | 0.325552E+10 | 0.00 | 0.00 |
December | 0.301650E+11 | 0.00 | 342.12 | 0.333844E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.975595E+11 | 0.00 | 0.519128E+12 | 0.758767E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 342.12 | 0.305154E+10 | 0.00 | 0.00 |
Maximum of Months | 0.301650E+11 | 0.00 | 0.122368E+12 | 0.121707E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 16995512.17 | 0.154502E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.123474E+10 | 0.137999E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.341121E+10 | 0.160684E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.172376E+11 | 0.149844E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.303525E+11 | 0.160233E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.560556E+11 | 0.159539E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.686866E+11 | 0.160654E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.680956E+11 | 0.173825E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.461517E+11 | 0.164455E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.215095E+11 | 0.167371E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.607606E+09 | 0.154090E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.153812E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.313360E+12 | 0.189701E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.137999E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.686866E+11 | 0.173825E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.573083E+10 | 0.288400E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.113292E+11 | 0.373755E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.192840E+11 | 0.530881E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.251324E+11 | 0.640351E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.767490E+10 | 0.334813E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.142843E+11 | 0.484229E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.215853E+11 | 0.658174E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.276023E+11 | 0.763131E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.784262E+10 | 0.333132E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.136847E+11 | 0.439344E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.185465E+11 | 0.508356E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.248935E+11 | 0.626273E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.197591E+12 | 0.598084E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.573083E+10 | 0.288400E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.276023E+11 | 0.763131E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.330972E+11 | 0.233628E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.914256E+11 | 0.326800E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.171842E+12 | 0.486323E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.235048E+12 | 0.603601E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.686786E+11 | 0.310849E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.134491E+12 | 0.458849E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.205534E+12 | 0.627311E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.263359E+12 | 0.728340E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.711936E+11 | 0.310977E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.122042E+12 | 0.404253E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.161279E+12 | 0.458969E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.213548E+12 | 0.558731E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.177154E+13 | 0.550863E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.330972E+11 | 0.233628E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.263359E+12 | 0.728340E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.124422E+10 | 0.194698E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.725074E+10 | 0.295278E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.158771E+11 | 0.468151E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.229932E+11 | 0.600012E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.665655E+10 | 0.311024E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.135297E+11 | 0.465276E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.207721E+11 | 0.636852E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.265027E+11 | 0.737008E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.703403E+10 | 0.313542E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.113471E+11 | 0.392963E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.142399E+11 | 0.430619E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.189334E+11 | 0.522546E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.166381E+12 | 0.536797E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.124422E+10 | 0.194698E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.265027E+11 | 0.737008E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.458725E+10 | 0.874801E+09 | 0.611647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.498953E+10 | 0.288684E+10 | 0.311425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.788127E+10 | 0.920135E+10 | 0.557406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108003E+11 | 0.335933E+11 | 30264058.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.948329E+10 | 0.515670E+11 | 1173737.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125899E+11 | 0.101735E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146175E+11 | 0.131826E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157237E+11 | 0.129946E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.941927E+10 | 0.743874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.816781E+10 | 0.358027E+11 | 0.380830E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.678771E+10 | 0.223797E+10 | 0.673143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.604498E+10 | 540032.06 | 0.421766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111093E+12 | 0.574059E+12 | 0.150912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.458725E+10 | 540032.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157237E+11 | 0.131826E+12 | 0.611647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.345227E+11 | 0.783570E+10 | 0.134971E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.334650E+11 | 0.228936E+11 | 0.765772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.467155E+11 | 0.680710E+11 | 0.168827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.641628E+11 | 0.246290E+12 | 0.204649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.774971E+11 | 0.445055E+12 | 0.152909E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101941E+12 | 0.866327E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111277E+12 | 0.105124E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110952E+12 | 0.996513E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.759651E+11 | 0.651386E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.566034E+11 | 0.295152E+12 | 0.106453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.396160E+11 | 0.160066E+11 | 0.282442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347382E+11 | 11358595.73 | 0.135190E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.787455E+12 | 0.466678E+13 | 0.404710E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.334650E+11 | 11358595.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111277E+12 | 0.105124E+13 | 0.135190E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.336373E+10 | 0.394535E+09 | 0.297115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.305154E+10 | 0.189525E+10 | 0.180028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.370104E+10 | 0.549794E+10 | 0.574705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.543433E+10 | 0.256558E+11 | 0.973084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.718289E+10 | 0.490399E+11 | 0.151919E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107229E+11 | 0.995448E+11 | 1394288.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121707E+11 | 0.122368E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117582E+11 | 0.113999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.723327E+10 | 0.705042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.466422E+10 | 0.291977E+11 | 0.329886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.325552E+10 | 0.103100E+10 | 0.950793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.333844E+10 | 342.12 | 0.301650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.758767E+11 | 0.519128E+12 | 0.975595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.305154E+10 | 342.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.121707E+11 | 0.122368E+12 | 0.301650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154502E+11 | 16995512.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137999E+11 | 0.123474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160684E+11 | 0.341121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149844E+11 | 0.172376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160233E+11 | 0.303525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159539E+11 | 0.560556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160654E+11 | 0.686866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173825E+11 | 0.680956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164455E+11 | 0.461517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167371E+11 | 0.215095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154090E+11 | 0.607606E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189701E+12 | 0.313360E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173825E+11 | 0.686866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.171620E+10 | 0.456303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155011E+10 | 0.914176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171620E+10 | 0.156914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166084E+10 | 0.203898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171620E+10 | 0.604297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166084E+10 | 0.111029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.171620E+10 | 0.167198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171620E+10 | 0.216872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.166084E+10 | 0.617214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171620E+10 | 0.110074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166084E+10 | 0.151238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171620E+10 | 0.203470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202068E+11 | 0.157989E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155011E+10 | 0.456303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171620E+10 | 0.216872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.163900E+11 | 0.261244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148039E+11 | 0.735495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163900E+11 | 0.139600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158613E+11 | 0.190549E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163900E+11 | 0.539837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158613E+11 | 0.104467E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163900E+11 | 0.159193E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.163900E+11 | 0.206914E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158613E+11 | 0.559572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163900E+11 | 0.980070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158613E+11 | 0.131243E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163900E+11 | 0.174064E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192979E+12 | 0.141365E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148039E+11 | 0.261244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163900E+11 | 0.206914E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.167558E+10 | 0.972830E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151343E+10 | 0.581139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167558E+10 | 0.128712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162153E+10 | 0.186146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167558E+10 | 0.522189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162153E+10 | 0.104985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167558E+10 | 0.160792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167558E+10 | 0.208082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162153E+10 | 0.552014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167558E+10 | 0.909302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162153E+10 | 0.115553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167558E+10 | 0.153835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197286E+11 | 0.132430E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151343E+10 | 0.972830E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167558E+10 | 0.208082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.458725E+10 | 0.611647E+10 | 0.874801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.498953E+10 | 0.311425E+10 | 0.288684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.788127E+10 | 0.557406E+09 | 0.920135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108003E+11 | 30264058.54 | 0.335933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.948329E+10 | 1173737.94 | 0.515670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125899E+11 | 0.00 | 0.101735E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146175E+11 | 0.00 | 0.131826E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157237E+11 | 0.00 | 0.129946E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.941927E+10 | 0.00 | 0.743874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.816781E+10 | 0.380830E+09 | 0.358027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.678771E+10 | 0.673143E+09 | 0.223797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.604498E+10 | 0.421766E+10 | 540032.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111093E+12 | 0.150912E+11 | 0.574059E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.458725E+10 | 0.00 | 540032.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157237E+11 | 0.611647E+10 | 0.131826E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.345227E+11 | 0.134971E+12 | 0.783570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.334650E+11 | 0.765772E+11 | 0.228936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.467155E+11 | 0.168827E+11 | 0.680710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.641628E+11 | 0.204649E+10 | 0.246290E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.774971E+11 | 0.152909E+09 | 0.445055E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101941E+12 | 0.00 | 0.866327E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.111277E+12 | 0.00 | 0.105124E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110952E+12 | 0.00 | 0.996513E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.759651E+11 | 0.00 | 0.651386E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.566034E+11 | 0.106453E+11 | 0.295152E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.396160E+11 | 0.282442E+11 | 0.160066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347382E+11 | 0.135190E+12 | 11358595.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.787455E+12 | 0.404710E+12 | 0.466678E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.334650E+11 | 0.00 | 11358595.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111277E+12 | 0.135190E+12 | 0.105124E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.336373E+10 | 0.297115E+11 | 0.394535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.305154E+10 | 0.180028E+11 | 0.189525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.370104E+10 | 0.574705E+10 | 0.549794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.543433E+10 | 0.973084E+09 | 0.256558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.718289E+10 | 0.151919E+09 | 0.490399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107229E+11 | 1394288.02 | 0.995448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121707E+11 | 0.00 | 0.122368E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117582E+11 | 0.00 | 0.113999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.723327E+10 | 0.00 | 0.705042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.466422E+10 | 0.329886E+10 | 0.291977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.325552E+10 | 0.950793E+10 | 0.103100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.333844E+10 | 0.301650E+11 | 342.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.758767E+11 | 0.975595E+11 | 0.519128E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.305154E+10 | 0.00 | 342.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.121707E+11 | 0.301650E+11 | 0.122368E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.154502E+11 | 0.00 | 16995512.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137999E+11 | 0.00 | 0.123474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160684E+11 | 0.00 | 0.341121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149844E+11 | 0.00 | 0.172376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160233E+11 | 0.00 | 0.303525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159539E+11 | 0.00 | 0.560556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160654E+11 | 0.00 | 0.686866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173825E+11 | 0.00 | 0.680956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164455E+11 | 0.00 | 0.461517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167371E+11 | 0.00 | 0.215095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154090E+11 | 0.00 | 0.607606E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189701E+12 | 0.00 | 0.313360E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173825E+11 | 0.00 | 0.686866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.171620E+10 | 0.00 | 0.573083E+10 | 0.00 | 0.116780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155011E+10 | 0.00 | 0.113292E+11 | 0.00 | 0.218744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171620E+10 | 0.00 | 0.192840E+11 | 0.00 | 0.359261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.166084E+10 | 0.00 | 0.251324E+11 | 0.00 | 0.474268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171620E+10 | 0.00 | 0.767490E+10 | 0.00 | 0.163193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166084E+10 | 0.00 | 0.142843E+11 | 0.00 | 0.318145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.171620E+10 | 0.00 | 0.215853E+11 | 0.00 | 0.486554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171620E+10 | 0.00 | 0.276023E+11 | 0.00 | 0.591511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.166084E+10 | 0.00 | 0.784262E+10 | 0.00 | 0.167048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171620E+10 | 0.00 | 0.136847E+11 | 0.00 | 0.267724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166084E+10 | 0.00 | 0.185465E+11 | 0.00 | 0.342272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171620E+10 | 0.00 | 0.248935E+11 | 0.00 | 0.454654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202068E+11 | 0.00 | 0.197591E+12 | 0.00 | 0.396015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155011E+10 | 0.00 | 0.573083E+10 | 0.00 | 0.116780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171620E+10 | 0.00 | 0.276023E+11 | 0.00 | 0.591511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.163900E+11 | 0.00 | 0.330972E+11 | 0.00 | 0.697287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148039E+11 | 0.00 | 0.914256E+11 | 0.00 | 0.178761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163900E+11 | 0.00 | 0.171842E+12 | 0.00 | 0.322423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158613E+11 | 0.00 | 0.235048E+12 | 0.00 | 0.444989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163900E+11 | 0.00 | 0.686786E+11 | 0.00 | 0.146949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158613E+11 | 0.00 | 0.134491E+12 | 0.00 | 0.300236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163900E+11 | 0.00 | 0.205534E+12 | 0.00 | 0.463411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.163900E+11 | 0.00 | 0.263359E+12 | 0.00 | 0.564441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158613E+11 | 0.00 | 0.711936E+11 | 0.00 | 0.152364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163900E+11 | 0.00 | 0.122042E+12 | 0.00 | 0.240353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158613E+11 | 0.00 | 0.161279E+12 | 0.00 | 0.300357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163900E+11 | 0.00 | 0.213548E+12 | 0.00 | 0.394831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192979E+12 | 0.00 | 0.177154E+13 | 0.00 | 0.357884E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148039E+11 | 0.00 | 0.330972E+11 | 0.00 | 0.697287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163900E+11 | 0.00 | 0.263359E+12 | 0.00 | 0.564441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.167558E+10 | 0.00 | 0.124422E+10 | 0.00 | 0.271395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151343E+10 | 0.00 | 0.725074E+10 | 0.00 | 0.143935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167558E+10 | 0.00 | 0.158771E+11 | 0.00 | 0.300593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162153E+10 | 0.00 | 0.229932E+11 | 0.00 | 0.437859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167558E+10 | 0.00 | 0.665655E+10 | 0.00 | 0.143466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162153E+10 | 0.00 | 0.135297E+11 | 0.00 | 0.303123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167558E+10 | 0.00 | 0.207721E+11 | 0.00 | 0.469293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167558E+10 | 0.00 | 0.265027E+11 | 0.00 | 0.569450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162153E+10 | 0.00 | 0.703403E+10 | 0.00 | 0.151389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167558E+10 | 0.00 | 0.113471E+11 | 0.00 | 0.225405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162153E+10 | 0.00 | 0.142399E+11 | 0.00 | 0.268466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167558E+10 | 0.00 | 0.189334E+11 | 0.00 | 0.354988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.197286E+11 | 0.00 | 0.166381E+12 | 0.00 | 0.339511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151343E+10 | 0.00 | 0.124422E+10 | 0.00 | 0.271395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167558E+10 | 0.00 | 0.265027E+11 | 0.00 | 0.569450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.123946E+10 | 0.00 | 0.00 | 0.106519E+09 | 0.00 | 0.00 | 0.647932E+11 | 0.00 | 0.68 |
February | 0.755767E+09 | 0.00 | 0.00 | 93855061.29 | 0.00 | 0.00 | 0.580256E+11 | 0.00 | 0.74 |
March | 0.405346E+09 | 0.00 | 0.00 | 0.106041E+09 | 0.00 | 0.00 | 0.689186E+11 | 0.00 | 1.10 |
April | 0.242750E+09 | 4792404.31 | 0.00 | 0.100552E+09 | 530951.96 | 0.00 | 0.517709E+11 | 0.00 | 1.23 |
May | 0.169954E+09 | 73671306.38 | 0.00 | 0.101678E+09 | 8487299.51 | 0.00 | 0.425418E+11 | 0.00 | 1.21 |
June | 92885291.63 | 0.181586E+10 | 0.00 | 70479303.77 | 42119845.63 | 0.00 | 0.203008E+11 | 0.00 | 0.94 |
July | 0.116325E+09 | 0.230780E+10 | 0.00 | 65079678.25 | 52925374.56 | 0.00 | 0.970911E+10 | 0.00 | 0.82 |
August | 0.140635E+09 | 0.127563E+10 | 0.00 | 94082709.16 | 36262062.87 | 0.00 | 0.174198E+11 | 0.00 | 1.03 |
September | 0.186026E+09 | 0.286185E+09 | 0.00 | 0.109845E+09 | 5221371.70 | 0.00 | 0.308046E+11 | 0.00 | 1.22 |
October | 0.339669E+09 | 11696356.11 | 0.00 | 0.125955E+09 | 0.00 | 0.00 | 0.574501E+11 | 0.00 | 1.26 |
November | 0.588708E+09 | 0.00 | 0.00 | 0.120996E+09 | 0.00 | 0.00 | 0.728511E+11 | 0.00 | 0.98 |
December | 0.944183E+09 | 0.00 | 0.00 | 0.122389E+09 | 0.00 | 0.00 | 0.699255E+11 | 0.00 | 0.64 |
Annual Sum or Average | 0.522171E+10 | 0.577563E+10 | 0.00 | 0.121747E+10 | 0.145547E+09 | 0.00 | 0.564511E+12 | 0.00 | 0.99 |
Minimum of Months | 92885291.63 | 0.00 | 0.00 | 65079678.25 | 0.00 | 0.00 | 0.970911E+10 | 0.00 | 0.64 |
Maximum of Months | 0.123946E+10 | 0.230780E+10 | 0.00 | 0.125955E+09 | 52925374.56 | 0.00 | 0.728511E+11 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.549672E+10 | 0.00 | 0.00 | 61815334.25 | 0.00 | 0.00 | 0.412518E+11 | 0.00 | 0.47 |
February | 0.377800E+10 | 0.00 | 0.00 | 66969180.72 | 0.00 | 0.00 | 0.403212E+11 | 0.00 | 0.54 |
March | 0.497639E+10 | 0.00 | 0.00 | 87743425.36 | 0.00 | 0.00 | 0.516452E+11 | 0.00 | 0.85 |
April | 0.971036E+10 | 1698903.75 | 0.00 | 82686649.46 | 531093.07 | 0.00 | 0.403382E+11 | 0.00 | 1.08 |
May | 0.396107E+10 | 33085366.71 | 0.00 | 78745286.32 | 48987988.64 | 0.00 | 0.304950E+11 | 0.00 | 0.91 |
June | 0.489780E+10 | 0.850973E+09 | 0.00 | 56167043.97 | 0.301291E+09 | 0.00 | 0.136736E+11 | 0.00 | 0.78 |
July | 0.443102E+10 | 0.131003E+10 | 0.00 | 43089303.24 | 0.469959E+09 | 0.00 | 0.462539E+10 | 0.00 | 0.71 |
August | 0.622339E+10 | 0.824438E+09 | 0.00 | 67658835.49 | 0.171188E+09 | 0.00 | 0.109681E+11 | 0.00 | 0.93 |
September | 0.379112E+10 | 0.254653E+09 | 0.00 | 74487285.90 | 25246379.33 | 0.00 | 0.194101E+11 | 0.00 | 0.84 |
October | 0.582316E+10 | 1053626.75 | 0.00 | 84493764.62 | 2236896.96 | 0.00 | 0.377114E+11 | 0.00 | 0.86 |
November | 0.596560E+10 | 0.00 | 0.00 | 84960084.97 | 0.00 | 0.00 | 0.505021E+11 | 0.00 | 0.72 |
December | 0.498688E+10 | 0.00 | 0.00 | 87438299.15 | 0.00 | 0.00 | 0.500302E+11 | 0.00 | 0.49 |
Annual Sum or Average | 0.640415E+11 | 0.327593E+10 | 0.00 | 0.876254E+09 | 0.101944E+10 | 0.00 | 0.390972E+12 | 0.00 | 0.77 |
Minimum of Months | 0.377800E+10 | 0.00 | 0.00 | 43089303.24 | 0.00 | 0.00 | 0.462539E+10 | 0.00 | 0.47 |
Maximum of Months | 0.971036E+10 | 0.131003E+10 | 0.00 | 87743425.36 | 0.469959E+09 | 0.00 | 0.516452E+11 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.208367E+12 | 0.00 | 0.00 | 0.150245E+09 | 0.00 | 0.00 | 0.142059E+12 | 0.00 | 0.35 |
February | 0.138413E+12 | 0.00 | 0.00 | 0.222418E+09 | 0.00 | 0.00 | 0.171280E+12 | 0.00 | 0.38 |
March | 0.806763E+11 | 0.00 | 0.00 | 0.416559E+09 | 0.00 | 0.00 | 0.295330E+12 | 0.00 | 0.57 |
April | 0.431504E+11 | 13531408.19 | 0.00 | 0.536702E+09 | 35441341.84 | 0.00 | 0.273833E+12 | 0.00 | 0.71 |
May | 0.321257E+11 | 0.329278E+09 | 0.00 | 0.621892E+09 | 0.336675E+09 | 0.00 | 0.242345E+12 | 0.00 | 0.74 |
June | 0.221942E+11 | 0.956973E+10 | 0.00 | 0.446992E+09 | 0.291588E+10 | 0.00 | 0.106557E+12 | 0.00 | 0.60 |
July | 0.157673E+11 | 0.127499E+11 | 0.00 | 0.341791E+09 | 0.403820E+10 | 0.00 | 0.339938E+11 | 0.00 | 0.49 |
August | 0.183775E+11 | 0.720024E+10 | 0.00 | 0.539214E+09 | 0.175603E+10 | 0.00 | 0.839874E+11 | 0.00 | 0.61 |
September | 0.234298E+11 | 0.230160E+10 | 0.00 | 0.606722E+09 | 0.299663E+09 | 0.00 | 0.152446E+12 | 0.00 | 0.67 |
October | 0.581770E+11 | 4420234.55 | 0.00 | 0.544345E+09 | 61951110.94 | 0.00 | 0.249348E+12 | 0.00 | 0.63 |
November | 0.102317E+12 | 0.00 | 0.00 | 0.344541E+09 | 0.00 | 0.00 | 0.253949E+12 | 0.00 | 0.47 |
December | 0.197634E+12 | 0.00 | 0.00 | 0.154787E+09 | 0.00 | 0.00 | 0.152807E+12 | 0.00 | 0.32 |
Annual Sum or Average | 0.940629E+12 | 0.321687E+11 | 0.00 | 0.492621E+10 | 0.944384E+10 | 0.00 | 0.215794E+13 | 0.00 | 0.55 |
Minimum of Months | 0.157673E+11 | 0.00 | 0.00 | 0.150245E+09 | 0.00 | 0.00 | 0.339938E+11 | 0.00 | 0.32 |
Maximum of Months | 0.208367E+12 | 0.127499E+11 | 0.00 | 0.621892E+09 | 0.403820E+10 | 0.00 | 0.295330E+12 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.266496E+11 | 0.00 | 0.00 | 674124.42 | 0.00 | 0.141965E+10 | 0.134776E+10 | 0.00 | 0.32 |
February | 0.217123E+11 | 0.00 | 0.00 | 2853983.87 | 0.00 | 0.763951E+09 | 0.364160E+10 | 0.00 | 0.34 |
March | 0.155388E+11 | 0.00 | 0.00 | 17020819.57 | 0.00 | 56487102.88 | 0.153535E+11 | 0.00 | 0.49 |
April | 0.705513E+10 | 0.00 | 0.00 | 38942235.69 | 0.00 | 0.00 | 0.214462E+11 | 0.00 | 0.70 |
May | 0.467976E+10 | 10358097.02 | 0.00 | 54142550.24 | 35496229.58 | 0.00 | 0.213382E+11 | 0.00 | 0.77 |
June | 0.276360E+10 | 0.564612E+09 | 0.00 | 51113584.77 | 0.249319E+09 | 0.00 | 0.975561E+10 | 0.00 | 0.61 |
July | 0.168404E+10 | 0.791745E+09 | 0.00 | 46085768.49 | 0.343839E+09 | 0.00 | 0.339928E+10 | 0.00 | 0.52 |
August | 0.188116E+10 | 0.435359E+09 | 0.00 | 64170866.68 | 0.148723E+09 | 0.00 | 0.857955E+10 | 0.00 | 0.65 |
September | 0.258955E+10 | 0.126888E+09 | 0.00 | 56797811.11 | 11131600.84 | 0.00 | 0.134326E+11 | 0.00 | 0.69 |
October | 0.100380E+11 | 1210968.19 | 0.00 | 33568955.47 | 126567.34 | 8663490.60 | 0.150238E+11 | 0.00 | 0.57 |
November | 0.195393E+11 | 0.00 | 0.00 | 8019418.90 | 0.00 | 0.412387E+09 | 0.809411E+10 | 0.00 | 0.38 |
December | 0.265300E+11 | 0.00 | 0.00 | 399897.97 | 0.00 | 0.186575E+10 | 0.841784E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.140661E+12 | 0.193017E+10 | 0.00 | 0.373790E+09 | 0.788636E+09 | 0.452689E+10 | 0.122254E+12 | 0.00 | 0.53 |
Minimum of Months | 0.168404E+10 | 0.00 | 0.00 | 399897.97 | 0.00 | 0.00 | 0.841784E+09 | 0.00 | 0.28 |
Maximum of Months | 0.266496E+11 | 0.791745E+09 | 0.00 | 64170866.68 | 0.343839E+09 | 0.186575E+10 | 0.214462E+11 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.400094E+10 | 0.00 | 0.00 | 119630.29 | 0.00 | 21623705.70 | 0.232065E+09 | 0.00 | 0.33 |
February | 0.291741E+10 | 0.00 | 0.00 | 948468.92 | 0.00 | 0.00 | 0.862106E+09 | 0.00 | 0.37 |
March | 0.198714E+10 | 0.00 | 0.00 | 4255059.57 | 0.00 | 0.00 | 0.314265E+10 | 0.00 | 0.63 |
April | 0.168499E+10 | 334586.40 | 0.00 | 7476364.64 | 49344.26 | 0.00 | 0.371583E+10 | 0.00 | 1.02 |
May | 0.755016E+09 | 8722193.51 | 0.00 | 9172008.60 | 4722959.13 | 0.00 | 0.336224E+10 | 0.00 | 0.95 |
June | 0.647327E+09 | 0.208526E+09 | 0.00 | 8899700.00 | 22367088.29 | 0.00 | 0.191539E+10 | 0.00 | 0.98 |
July | 0.543294E+09 | 0.298169E+09 | 0.00 | 7385689.71 | 51619737.22 | 0.00 | 0.742942E+09 | 0.00 | 0.91 |
August | 0.812690E+09 | 0.167508E+09 | 0.00 | 10730454.56 | 17072528.32 | 0.00 | 0.151255E+10 | 0.00 | 1.09 |
September | 0.608404E+09 | 43041957.11 | 0.00 | 8823704.16 | 2354788.62 | 0.00 | 0.210816E+10 | 0.00 | 0.85 |
October | 0.165043E+10 | 193983.86 | 0.00 | 5732797.79 | 281056.02 | 0.00 | 0.244546E+10 | 0.00 | 0.70 |
November | 0.246031E+10 | 0.00 | 0.00 | 2421059.82 | 0.00 | 0.00 | 0.212379E+10 | 0.00 | 0.47 |
December | 0.383254E+10 | 0.00 | 0.00 | 320649.77 | 0.00 | 0.00 | 0.469966E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.219005E+11 | 0.726495E+09 | 0.00 | 66285587.83 | 98467501.85 | 21623705.70 | 0.226331E+11 | 0.00 | 0.72 |
Minimum of Months | 0.543294E+09 | 0.00 | 0.00 | 119630.29 | 0.00 | 0.00 | 0.232065E+09 | 0.00 | 0.30 |
Maximum of Months | 0.400094E+10 | 0.298169E+09 | 0.00 | 10730454.56 | 51619737.22 | 21623705.70 | 0.371583E+10 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.322292E+10 | 0.00 | 0.00 | 1603022.46 | 0.00 | 40671788.33 | 0.125551E+10 | 0.00 | 0.55 |
February | 0.232649E+10 | 0.00 | 0.00 | 2626487.39 | 0.00 | 746680.18 | 0.185150E+10 | 0.00 | 0.62 |
March | 0.175415E+10 | 0.00 | 0.00 | 6521017.34 | 0.00 | 0.00 | 0.422380E+10 | 0.00 | 1.07 |
April | 0.153570E+10 | 307254.29 | 0.00 | 10922291.64 | 26488.13 | 0.00 | 0.548861E+10 | 0.00 | 1.83 |
May | 0.678616E+09 | 11027682.15 | 0.00 | 12983481.03 | 2983897.69 | 0.00 | 0.478291E+10 | 0.00 | 1.78 |
June | 0.681204E+09 | 0.162003E+09 | 0.00 | 10812752.37 | 23992369.78 | 0.00 | 0.213506E+10 | 0.00 | 1.62 |
July | 0.559516E+09 | 0.251917E+09 | 0.00 | 8386395.80 | 50660363.28 | 0.00 | 0.703025E+09 | 0.00 | 1.40 |
August | 0.850102E+09 | 0.141704E+09 | 0.00 | 10826000.92 | 17032856.42 | 0.00 | 0.157610E+10 | 0.00 | 1.74 |
September | 0.659387E+09 | 32576699.25 | 0.00 | 10602135.20 | 2212196.22 | 0.00 | 0.265806E+10 | 0.00 | 1.57 |
October | 0.143783E+10 | 138259.85 | 0.00 | 8056068.55 | 273646.62 | 0.00 | 0.355507E+10 | 0.00 | 1.24 |
November | 0.223265E+10 | 0.00 | 0.00 | 3902501.23 | 0.00 | 0.00 | 0.276315E+10 | 0.00 | 0.76 |
December | 0.331678E+10 | 0.00 | 0.00 | 1632783.69 | 0.00 | 6680025.37 | 0.118763E+10 | 0.00 | 0.49 |
Annual Sum or Average | 0.192553E+11 | 0.599674E+09 | 0.00 | 88874937.63 | 97181818.14 | 48098493.88 | 0.321804E+11 | 0.00 | 1.22 |
Minimum of Months | 0.559516E+09 | 0.00 | 0.00 | 1603022.46 | 0.00 | 0.00 | 0.703025E+09 | 0.00 | 0.49 |
Maximum of Months | 0.331678E+10 | 0.251917E+09 | 0.00 | 12983481.03 | 50660363.28 | 40671788.33 | 0.548861E+10 | 0.00 | 1.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.203474E+10 | 0.00 | 0.00 | 13078636.78 | 0.00 | 87515294.58 | 0.750421E+10 | 0.00 | 0.87 |
February | 0.151360E+10 | 0.00 | 0.00 | 13279148.44 | 0.00 | 17079321.51 | 0.777281E+10 | 0.00 | 1.00 |
March | 0.145042E+10 | 0.00 | 0.00 | 13294158.92 | 0.00 | 0.00 | 0.826261E+10 | 0.00 | 1.29 |
April | 0.168069E+10 | 556707.72 | 0.00 | 13175353.62 | 14689.97 | 0.00 | 0.613005E+10 | 0.00 | 1.54 |
May | 0.895999E+09 | 13786585.56 | 0.00 | 10632315.03 | 4560789.10 | 0.00 | 0.372692E+10 | 0.00 | 1.10 |
June | 0.756571E+09 | 0.212495E+09 | 0.00 | 8328438.07 | 23689964.81 | 0.00 | 0.165354E+10 | 0.00 | 0.94 |
July | 0.566112E+09 | 0.341437E+09 | 0.00 | 7613327.34 | 54001027.45 | 0.00 | 0.713250E+09 | 0.00 | 0.93 |
August | 0.813492E+09 | 0.232198E+09 | 0.00 | 13967615.70 | 17309866.86 | 0.00 | 0.176157E+10 | 0.00 | 1.28 |
September | 0.466405E+09 | 86026696.57 | 0.00 | 18365950.99 | 1189718.44 | 0.00 | 0.338158E+10 | 0.00 | 1.35 |
October | 0.106195E+10 | 1456376.73 | 0.00 | 23741406.66 | 0.00 | 0.00 | 0.790379E+10 | 0.00 | 1.60 |
November | 0.121977E+10 | 0.00 | 0.00 | 19115353.93 | 0.00 | 0.00 | 0.107917E+11 | 0.00 | 1.25 |
December | 0.171520E+10 | 0.00 | 0.00 | 15946066.86 | 0.00 | 13295731.47 | 0.974091E+10 | 0.00 | 0.85 |
Annual Sum or Average | 0.141749E+11 | 0.887956E+09 | 0.00 | 0.170538E+09 | 0.100766E+09 | 0.117890E+09 | 0.693429E+11 | 0.00 | 1.17 |
Minimum of Months | 0.466405E+09 | 0.00 | 0.00 | 7613327.34 | 0.00 | 0.00 | 0.713250E+09 | 0.00 | 0.85 |
Maximum of Months | 0.203474E+10 | 0.341437E+09 | 0.00 | 23741406.66 | 54001027.45 | 87515294.58 | 0.107917E+11 | 0.00 | 1.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.388933E+10 | 0.00 | 0.00 | 2604998.97 | 0.00 | 0.00 | 0.227761E+10 | 0.00 | 0.78 |
February | 0.190481E+10 | 0.00 | 0.00 | 6108591.76 | 0.00 | 0.00 | 0.443164E+10 | 0.00 | 1.04 |
March | 0.833329E+09 | 0.00 | 0.00 | 13308472.32 | 0.00 | 0.00 | 0.793782E+10 | 0.00 | 1.78 |
April | 0.897570E+09 | 622673.65 | 0.00 | 21669782.94 | 0.00 | 0.00 | 0.820461E+10 | 0.00 | 2.74 |
May | 0.630989E+09 | 21655218.95 | 0.00 | 13351968.58 | 3325626.61 | 0.00 | 0.441064E+10 | 0.00 | 1.87 |
June | 0.549313E+09 | 0.302767E+09 | 0.00 | 12315323.49 | 17383971.98 | 0.00 | 0.232626E+10 | 0.00 | 1.78 |
July | 0.423741E+09 | 0.417628E+09 | 0.00 | 11565478.16 | 42866109.71 | 0.00 | 0.118325E+10 | 0.00 | 1.73 |
August | 0.539219E+09 | 0.259451E+09 | 0.00 | 18877788.15 | 4587498.72 | 0.00 | 0.263112E+10 | 0.00 | 2.30 |
September | 0.480733E+09 | 56200360.27 | 0.00 | 13862725.47 | 1006714.63 | 0.00 | 0.279451E+10 | 0.00 | 1.61 |
October | 0.101307E+10 | 265243.72 | 0.00 | 13897602.62 | 361281.37 | 0.00 | 0.526833E+10 | 0.00 | 1.72 |
November | 0.105898E+10 | 0.00 | 0.00 | 10154483.48 | 0.00 | 0.00 | 0.691752E+10 | 0.00 | 1.32 |
December | 0.151347E+10 | 0.00 | 0.00 | 8349210.00 | 0.00 | 0.00 | 0.600193E+10 | 0.00 | 0.87 |
Annual Sum or Average | 0.137345E+11 | 0.105859E+10 | 0.00 | 0.146066E+09 | 69531203.02 | 0.00 | 0.543852E+11 | 0.00 | 1.63 |
Minimum of Months | 0.423741E+09 | 0.00 | 0.00 | 2604998.97 | 0.00 | 0.00 | 0.118325E+10 | 0.00 | 0.78 |
Maximum of Months | 0.388933E+10 | 0.417628E+09 | 0.00 | 21669782.94 | 42866109.71 | 0.00 | 0.820461E+10 | 0.00 | 2.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.285966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142216E+11 | 0.00 | 0.00 | 0.34 |
February | 0.277150E+11 | 0.00 | 0.00 | 28564.91 | 0.00 | 0.809308E+10 | 0.198838E+09 | 0.00 | 0.35 |
March | 0.314900E+11 | 0.00 | 0.00 | 5811336.58 | 0.00 | 0.106485E+10 | 0.537461E+10 | 0.00 | 0.46 |
April | 0.154514E+11 | 2667688.95 | 0.00 | 36375429.80 | 4395176.20 | 0.00 | 0.167062E+11 | 0.00 | 0.62 |
May | 0.858688E+10 | 84120008.38 | 0.00 | 67867452.89 | 27659068.74 | 0.00 | 0.229912E+11 | 0.00 | 0.76 |
June | 0.361087E+10 | 0.260244E+10 | 0.00 | 70057053.68 | 0.197971E+09 | 0.00 | 0.142225E+11 | 0.00 | 0.79 |
July | 0.194075E+10 | 0.331392E+10 | 0.00 | 60330678.75 | 0.402694E+09 | 0.00 | 0.558745E+10 | 0.00 | 0.69 |
August | 0.251214E+10 | 0.166542E+10 | 0.00 | 84117733.75 | 0.170018E+09 | 0.00 | 0.114235E+11 | 0.00 | 0.77 |
September | 0.627484E+10 | 0.400502E+09 | 0.00 | 65292024.53 | 27708027.87 | 0.00 | 0.139710E+11 | 0.00 | 0.67 |
October | 0.209779E+11 | 851841.24 | 0.00 | 26858727.76 | 7782277.04 | 0.639563E+09 | 0.933029E+10 | 0.00 | 0.53 |
November | 0.333053E+11 | 0.00 | 0.00 | 996563.45 | 0.00 | 0.327173E+10 | 0.178460E+10 | 0.00 | 0.39 |
December | 0.252310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174991E+11 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.205693E+12 | 0.806992E+10 | 0.00 | 0.417736E+09 | 0.838228E+09 | 0.447899E+11 | 0.101590E+12 | 0.00 | 0.56 |
Minimum of Months | 0.194075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.333053E+11 | 0.331392E+10 | 0.00 | 84117733.75 | 0.402694E+09 | 0.174991E+11 | 0.229912E+11 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.341628E+11 | 0.00 | 0.00 | 2075890.72 | 0.00 | 0.101467E+11 | 0.193424E+10 | 0.00 | 0.57 |
February | 0.302540E+11 | 0.00 | 0.00 | 8471101.39 | 0.00 | 0.369864E+10 | 0.621700E+10 | 0.00 | 0.61 |
March | 0.219315E+11 | 0.00 | 0.00 | 40615663.08 | 0.00 | 0.185004E+09 | 0.284553E+11 | 0.00 | 0.92 |
April | 0.856016E+10 | 4830393.78 | 0.00 | 0.100037E+09 | 3298242.55 | 0.00 | 0.502862E+11 | 0.00 | 1.58 |
May | 0.622312E+10 | 0.102912E+09 | 0.00 | 0.131177E+09 | 24179854.51 | 0.00 | 0.453552E+11 | 0.00 | 1.72 |
June | 0.363149E+10 | 0.230525E+10 | 0.00 | 0.105241E+09 | 0.201484E+09 | 0.00 | 0.204419E+11 | 0.00 | 1.55 |
July | 0.197986E+10 | 0.370301E+10 | 0.00 | 83848281.13 | 0.254620E+09 | 0.00 | 0.686348E+10 | 0.00 | 1.27 |
August | 0.249170E+10 | 0.170891E+10 | 0.00 | 0.113862E+09 | 0.151989E+09 | 0.00 | 0.164373E+11 | 0.00 | 1.52 |
September | 0.535759E+10 | 0.334036E+09 | 0.00 | 0.100851E+09 | 26405078.16 | 0.00 | 0.243074E+11 | 0.00 | 1.48 |
October | 0.156438E+11 | 1560865.16 | 0.00 | 62859277.45 | 8206433.19 | 0.488907E+09 | 0.269753E+11 | 0.00 | 1.11 |
November | 0.319084E+11 | 0.00 | 0.00 | 13061507.37 | 0.00 | 0.105591E+10 | 0.106158E+11 | 0.00 | 0.68 |
December | 0.360239E+11 | 0.00 | 0.00 | 713306.96 | 0.00 | 0.922379E+10 | 0.912846E+09 | 0.00 | 0.51 |
Annual Sum or Average | 0.198168E+12 | 0.816052E+10 | 0.00 | 0.762813E+09 | 0.670183E+09 | 0.247989E+11 | 0.238802E+12 | 0.00 | 1.13 |
Minimum of Months | 0.197986E+10 | 0.00 | 0.00 | 713306.96 | 0.00 | 0.00 | 0.912846E+09 | 0.00 | 0.51 |
Maximum of Months | 0.360239E+11 | 0.370301E+10 | 0.00 | 0.131177E+09 | 0.254620E+09 | 0.101467E+11 | 0.502862E+11 | 0.00 | 1.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.195684E+11 | 0.00 | 0.00 | 0.136286E+09 | 0.00 | 0.380692E+10 | 0.683135E+11 | 0.00 | 0.86 |
February | 0.144120E+11 | 0.00 | 0.00 | 0.131573E+09 | 0.00 | 0.189693E+10 | 0.704141E+11 | 0.00 | 0.95 |
March | 0.145546E+11 | 0.00 | 0.00 | 0.119943E+09 | 0.00 | 99705143.38 | 0.682916E+11 | 0.00 | 1.13 |
April | 0.104141E+11 | 8755437.84 | 0.00 | 0.107479E+09 | 2355514.23 | 0.00 | 0.483040E+11 | 0.00 | 1.20 |
May | 0.848610E+10 | 0.149861E+09 | 0.00 | 90986443.90 | 22861425.47 | 0.00 | 0.302148E+11 | 0.00 | 0.96 |
June | 0.438022E+10 | 0.263335E+10 | 0.00 | 67086612.19 | 0.208517E+09 | 0.00 | 0.128269E+11 | 0.00 | 0.77 |
July | 0.186234E+10 | 0.386493E+10 | 0.00 | 64704851.39 | 0.403440E+09 | 0.00 | 0.557866E+10 | 0.00 | 0.73 |
August | 0.214149E+10 | 0.256228E+10 | 0.00 | 0.123254E+09 | 0.127878E+09 | 0.00 | 0.148014E+11 | 0.00 | 1.00 |
September | 0.332227E+10 | 0.916847E+09 | 0.00 | 0.179364E+09 | 9285172.35 | 0.00 | 0.296024E+11 | 0.00 | 1.25 |
October | 0.839022E+10 | 25514740.12 | 0.00 | 0.243766E+09 | 68200.44 | 0.210250E+09 | 0.718913E+11 | 0.00 | 1.48 |
November | 0.119471E+11 | 0.00 | 0.00 | 0.189069E+09 | 0.00 | 0.127393E+09 | 0.960197E+11 | 0.00 | 1.14 |
December | 0.171117E+11 | 0.00 | 0.00 | 0.143299E+09 | 0.00 | 0.356727E+10 | 0.824300E+11 | 0.00 | 0.79 |
Annual Sum or Average | 0.116590E+12 | 0.101615E+11 | 0.00 | 0.159681E+10 | 0.774406E+09 | 0.970847E+10 | 0.598688E+12 | 0.00 | 1.02 |
Minimum of Months | 0.186234E+10 | 0.00 | 0.00 | 64704851.39 | 0.00 | 0.00 | 0.557866E+10 | 0.00 | 0.73 |
Maximum of Months | 0.195684E+11 | 0.386493E+10 | 0.00 | 0.243766E+09 | 0.403440E+09 | 0.380692E+10 | 0.960197E+11 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.358285E+11 | 0.00 | 0.00 | 7999920.73 | 0.00 | 0.805778E+10 | 0.672606E+10 | 0.00 | 0.63 |
February | 0.297815E+11 | 0.00 | 0.00 | 18672425.29 | 0.00 | 0.377234E+10 | 0.126009E+11 | 0.00 | 0.73 |
March | 0.292331E+11 | 0.00 | 0.00 | 37739422.54 | 0.00 | 0.231949E+09 | 0.233030E+11 | 0.00 | 1.06 |
April | 0.139824E+11 | 7491800.71 | 0.00 | 90110816.40 | 2866349.67 | 0.00 | 0.318530E+11 | 0.00 | 1.47 |
May | 0.906920E+10 | 0.211317E+09 | 0.00 | 88529395.37 | 4851331.17 | 0.00 | 0.274971E+11 | 0.00 | 1.43 |
June | 0.456009E+10 | 0.345019E+10 | 0.00 | 71209186.93 | 0.142342E+09 | 0.00 | 0.121150E+11 | 0.00 | 1.24 |
July | 0.182618E+10 | 0.397326E+10 | 0.00 | 58956988.56 | 0.367965E+09 | 0.00 | 0.518895E+10 | 0.00 | 1.06 |
August | 0.220317E+10 | 0.211654E+10 | 0.00 | 96532699.88 | 95843245.38 | 0.00 | 0.120950E+11 | 0.00 | 1.28 |
September | 0.532234E+10 | 0.519533E+09 | 0.00 | 95145242.42 | 13009945.81 | 0.00 | 0.173710E+11 | 0.00 | 1.19 |
October | 0.193292E+11 | 12496058.28 | 0.00 | 64154555.43 | 2649588.22 | 0.246134E+09 | 0.220332E+11 | 0.00 | 1.15 |
November | 0.333753E+11 | 0.00 | 0.00 | 19081377.99 | 0.00 | 0.495311E+09 | 0.154779E+11 | 0.00 | 0.80 |
December | 0.358693E+11 | 0.00 | 0.00 | 7751414.55 | 0.00 | 0.777863E+10 | 0.676794E+10 | 0.00 | 0.56 |
Annual Sum or Average | 0.220380E+12 | 0.102908E+11 | 0.00 | 0.655883E+09 | 0.629528E+09 | 0.205821E+11 | 0.193029E+12 | 0.00 | 1.05 |
Minimum of Months | 0.182618E+10 | 0.00 | 0.00 | 7751414.55 | 0.00 | 0.00 | 0.518895E+10 | 0.00 | 0.56 |
Maximum of Months | 0.358693E+11 | 0.397326E+10 | 0.00 | 96532699.88 | 0.367965E+09 | 0.805778E+10 | 0.318530E+11 | 0.00 | 1.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.115544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279211E+10 | 0.00 | 0.00 | 0.33 |
February | 0.158230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181306E+10 | 0.00 | 0.00 | 0.35 |
March | 0.280112E+10 | 0.00 | 0.00 | 190371.06 | 0.00 | 0.606086E+09 | 0.205664E+09 | 0.00 | 0.44 |
April | 0.168092E+10 | 0.00 | 0.00 | 3048270.57 | 0.00 | 0.116402E+09 | 0.131307E+10 | 0.00 | 0.64 |
May | 0.101914E+10 | 2949546.16 | 0.00 | 6404755.12 | 3754379.42 | 9189632.88 | 0.205972E+10 | 0.00 | 0.79 |
June | 0.431519E+09 | 0.150195E+09 | 0.00 | 8716535.89 | 16235275.54 | 0.00 | 0.132336E+10 | 0.00 | 0.78 |
July | 0.193349E+09 | 0.191251E+09 | 0.00 | 8486328.65 | 36623560.57 | 0.00 | 0.584797E+09 | 0.00 | 0.71 |
August | 0.307672E+09 | 96741211.71 | 0.00 | 10237408.80 | 12734596.15 | 0.00 | 0.116083E+10 | 0.00 | 0.80 |
September | 0.657907E+09 | 20204226.87 | 0.00 | 6633883.10 | 1556956.80 | 0.00 | 0.128981E+10 | 0.00 | 0.69 |
October | 0.191124E+10 | 164719.22 | 0.00 | 2125867.69 | 15856.43 | 0.321586E+09 | 0.618332E+09 | 0.00 | 0.52 |
November | 0.236269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111922E+10 | 0.00 | 0.00 | 0.37 |
December | 0.799224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314622E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.149025E+11 | 0.461506E+09 | 0.00 | 45843420.89 | 70920624.91 | 0.992388E+10 | 0.855559E+10 | 0.00 | 0.56 |
Minimum of Months | 0.193349E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.280112E+10 | 0.191251E+09 | 0.00 | 10237408.80 | 36623560.57 | 0.314622E+10 | 0.205972E+10 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.220494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177972E+10 | 0.00 | 0.00 | 0.53 |
February | 0.239035E+10 | 0.00 | 0.00 | 273269.17 | 0.00 | 0.869219E+09 | 0.271660E+09 | 0.00 | 0.56 |
March | 0.214062E+10 | 0.00 | 0.00 | 2618262.52 | 0.00 | 0.293759E+09 | 0.196734E+10 | 0.00 | 0.84 |
April | 0.825660E+09 | 0.00 | 0.00 | 8937852.71 | 0.00 | 25874119.62 | 0.461504E+10 | 0.00 | 1.58 |
May | 0.572889E+09 | 5009477.20 | 0.00 | 13072197.24 | 2795707.36 | 2347719.32 | 0.447578E+10 | 0.00 | 1.79 |
June | 0.354376E+09 | 0.137075E+09 | 0.00 | 12636636.92 | 15771095.56 | 0.00 | 0.203847E+10 | 0.00 | 1.58 |
July | 0.191534E+09 | 0.233804E+09 | 0.00 | 11140182.57 | 22714544.60 | 0.00 | 0.731550E+09 | 0.00 | 1.32 |
August | 0.250481E+09 | 0.101828E+09 | 0.00 | 14007770.63 | 12935691.60 | 0.00 | 0.175095E+10 | 0.00 | 1.62 |
September | 0.530409E+09 | 16866799.67 | 0.00 | 10391264.52 | 1365096.49 | 0.00 | 0.234674E+10 | 0.00 | 1.56 |
October | 0.144941E+10 | 153162.61 | 0.00 | 5149506.54 | 17019.29 | 0.196273E+09 | 0.212464E+10 | 0.00 | 1.06 |
November | 0.289115E+10 | 0.00 | 0.00 | 379408.60 | 0.00 | 0.454952E+09 | 0.375134E+09 | 0.00 | 0.62 |
December | 0.225360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170845E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.160554E+11 | 0.494736E+09 | 0.00 | 78606351.42 | 55599154.89 | 0.533060E+10 | 0.206973E+11 | 0.00 | 1.13 |
Minimum of Months | 0.191534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.289115E+10 | 0.233804E+09 | 0.00 | 14007770.63 | 22714544.60 | 0.177972E+10 | 0.461504E+10 | 0.00 | 1.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163684E+10 | 0.00 | 0.00 | 7750390.73 | 0.00 | 0.102416E+10 | 0.475210E+10 | 0.00 | 0.73 |
February | 0.142091E+10 | 0.00 | 0.00 | 8769864.75 | 0.00 | 0.533983E+09 | 0.530456E+10 | 0.00 | 0.83 |
March | 0.155776E+10 | 0.00 | 0.00 | 8845149.82 | 0.00 | 0.307576E+09 | 0.582039E+10 | 0.00 | 1.04 |
April | 0.115315E+10 | 0.00 | 0.00 | 9790537.05 | 0.00 | 59869251.17 | 0.466006E+10 | 0.00 | 1.24 |
May | 0.102131E+10 | 5431855.53 | 0.00 | 9099745.04 | 3665127.72 | 13524109.63 | 0.295649E+10 | 0.00 | 1.03 |
June | 0.556056E+09 | 0.148164E+09 | 0.00 | 8593604.99 | 19302139.32 | 0.00 | 0.125866E+10 | 0.00 | 0.79 |
July | 0.217232E+09 | 0.216324E+09 | 0.00 | 9282296.10 | 40893402.44 | 0.00 | 0.592306E+09 | 0.00 | 0.75 |
August | 0.291971E+09 | 0.140255E+09 | 0.00 | 15281203.67 | 12603601.11 | 0.00 | 0.159515E+10 | 0.00 | 1.05 |
September | 0.423402E+09 | 43807461.05 | 0.00 | 18991443.20 | 792639.51 | 0.00 | 0.303491E+10 | 0.00 | 1.36 |
October | 0.872286E+09 | 397895.08 | 0.00 | 21392343.76 | 3744.49 | 0.170153E+09 | 0.666792E+10 | 0.00 | 1.50 |
November | 0.125285E+10 | 0.00 | 0.00 | 12032769.81 | 0.00 | 0.299382E+09 | 0.741849E+10 | 0.00 | 0.99 |
December | 0.169815E+10 | 0.00 | 0.00 | 8796088.09 | 0.00 | 0.758322E+09 | 0.560020E+10 | 0.00 | 0.64 |
Annual Sum or Average | 0.121019E+11 | 0.554381E+09 | 0.00 | 0.138625E+09 | 77260654.59 | 0.316696E+10 | 0.496612E+11 | 0.00 | 0.99 |
Minimum of Months | 0.217232E+09 | 0.00 | 0.00 | 7750390.73 | 0.00 | 0.00 | 0.592306E+09 | 0.00 | 0.64 |
Maximum of Months | 0.169815E+10 | 0.216324E+09 | 0.00 | 21392343.76 | 40893402.44 | 0.102416E+10 | 0.741849E+10 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.242276E+10 | 0.00 | 0.00 | 456522.43 | 0.00 | 0.168797E+10 | 0.455160E+09 | 0.00 | 0.61 |
February | 0.240119E+10 | 0.00 | 0.00 | 1353357.04 | 0.00 | 0.942924E+09 | 0.981183E+09 | 0.00 | 0.72 |
March | 0.289053E+10 | 0.00 | 0.00 | 2918515.67 | 0.00 | 0.354298E+09 | 0.198485E+10 | 0.00 | 1.05 |
April | 0.167016E+10 | 0.00 | 0.00 | 8361949.91 | 0.00 | 17218406.32 | 0.300285E+10 | 0.00 | 1.57 |
May | 0.112527E+10 | 7629592.37 | 0.00 | 9383614.80 | 3419016.79 | 5040240.46 | 0.269198E+10 | 0.00 | 1.55 |
June | 0.532687E+09 | 0.187214E+09 | 0.00 | 9454953.63 | 14082974.11 | 0.00 | 0.123109E+10 | 0.00 | 1.26 |
July | 0.209975E+09 | 0.215463E+09 | 0.00 | 8529101.47 | 37106754.35 | 0.00 | 0.550523E+09 | 0.00 | 1.08 |
August | 0.285243E+09 | 0.113435E+09 | 0.00 | 11811968.19 | 11192821.65 | 0.00 | 0.127468E+10 | 0.00 | 1.34 |
September | 0.703879E+09 | 25534714.60 | 0.00 | 10143001.73 | 852409.92 | 0.00 | 0.158284E+10 | 0.00 | 1.29 |
October | 0.195485E+10 | 284635.50 | 0.00 | 5778160.46 | 613.40 | 0.209551E+09 | 0.187293E+10 | 0.00 | 1.18 |
November | 0.286896E+10 | 0.00 | 0.00 | 1300473.96 | 0.00 | 0.543075E+09 | 0.111178E+10 | 0.00 | 0.77 |
December | 0.238895E+10 | 0.00 | 0.00 | 393768.78 | 0.00 | 0.166488E+10 | 0.446431E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.194545E+11 | 0.549561E+09 | 0.00 | 69885388.05 | 66654590.22 | 0.542496E+10 | 0.171863E+11 | 0.00 | 1.08 |
Minimum of Months | 0.209975E+09 | 0.00 | 0.00 | 393768.78 | 0.00 | 0.00 | 0.446431E+09 | 0.00 | 0.54 |
Maximum of Months | 0.289053E+10 | 0.215463E+09 | 0.00 | 11811968.19 | 37106754.35 | 0.168797E+10 | 0.300285E+10 | 0.00 | 1.57 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3375828.00 | 0.00 | 0.00 | 0.543772E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 8067422.50 | 0.00 | 0.00 | 0.454144E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 14324602.97 | 0.00 | 0.00 | 0.427640E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 17331306.61 | 0.00 | 0.00 | 0.289639E+09 | 0.00 | 0.29 |
May | 0.00 | 479648.05 | 0.00 | 3962266.18 | 0.00 | 0.00 | 0.214510E+09 | 0.00 | 0.29 |
June | 0.00 | 26705883.17 | 0.00 | 5052281.98 | 0.00 | 0.00 | 48621112.36 | 0.00 | 0.30 |
July | 0.00 | 0.149320E+09 | 0.00 | 204996.57 | 0.00 | 0.00 | 196401.98 | 0.00 | 0.28 |
August | 0.00 | 0.120727E+09 | 0.00 | 1079992.66 | 0.00 | 0.00 | 654174.07 | 0.00 | 0.30 |
September | 0.00 | 18510473.24 | 0.00 | 2632473.73 | 0.00 | 0.00 | 55695917.43 | 0.00 | 0.29 |
October | 0.00 | 4414026.04 | 0.00 | 7728326.09 | 0.00 | 0.00 | 0.274121E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 13014527.12 | 0.00 | 0.00 | 0.423863E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 18992947.31 | 0.00 | 0.00 | 0.546592E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.320157E+09 | 0.00 | 95766971.72 | 0.00 | 0.00 | 0.327945E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 204996.57 | 0.00 | 0.00 | 196401.98 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.149320E+09 | 0.00 | 18992947.31 | 0.00 | 0.00 | 0.546592E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 66002704.06 | 0.00 | 0.00 | 19072425.49 | 0.00 | 0.00 | 0.538565E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 66303317.22 | 0.00 | 0.00 | 0.455593E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.128573E+09 | 0.00 | 0.00 | 0.428994E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.162763E+09 | 0.00 | 0.00 | 0.290612E+10 | 0.00 | 0.29 |
May | 0.00 | 4329856.39 | 0.00 | 35341719.42 | 0.00 | 0.00 | 0.215389E+10 | 0.00 | 0.29 |
June | 0.00 | 0.265006E+09 | 0.00 | 47585894.81 | 0.00 | 0.00 | 0.490115E+09 | 0.00 | 0.30 |
July | 0.00 | 0.148839E+10 | 0.00 | 1946275.73 | 0.00 | 0.00 | 1885121.91 | 0.00 | 0.28 |
August | 0.00 | 0.120420E+10 | 0.00 | 10473010.69 | 0.00 | 0.00 | 6807104.29 | 0.00 | 0.30 |
September | 0.00 | 0.175516E+09 | 0.00 | 24103997.70 | 0.00 | 0.00 | 0.567782E+09 | 0.00 | 0.29 |
October | 0.00 | 42790199.47 | 0.00 | 68904573.10 | 0.00 | 0.00 | 0.275021E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.114825E+09 | 0.00 | 0.00 | 0.425343E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.165882E+09 | 0.00 | 0.00 | 0.548937E+10 | 0.00 | 0.28 |
Annual Sum or Average | 66002704.06 | 0.318023E+10 | 0.00 | 0.845774E+09 | 0.00 | 0.00 | 0.328511E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1946275.73 | 0.00 | 0.00 | 1885121.91 | 0.00 | 0.28 |
Maximum of Months | 66002704.06 | 0.148839E+10 | 0.00 | 0.165882E+09 | 0.00 | 0.00 | 0.548937E+10 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.213739E+09 | 0.00 | 0.00 | 883962.68 | 0.00 | 0.00 | 0.328261E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 5538465.04 | 0.00 | 0.00 | 0.456803E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 12015351.73 | 0.00 | 0.00 | 0.429961E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 15971310.84 | 0.00 | 0.00 | 0.290949E+09 | 0.00 | 0.29 |
May | 0.00 | 436878.58 | 0.00 | 3420529.14 | 0.00 | 0.00 | 0.215755E+09 | 0.00 | 0.29 |
June | 0.00 | 26535709.77 | 0.00 | 4764402.76 | 0.00 | 0.00 | 49143220.56 | 0.00 | 0.30 |
July | 0.00 | 0.148861E+09 | 0.00 | 197608.02 | 0.00 | 0.00 | 194411.36 | 0.00 | 0.28 |
August | 0.00 | 0.120610E+09 | 0.00 | 1045603.85 | 0.00 | 0.00 | 674953.78 | 0.00 | 0.30 |
September | 0.00 | 17548326.18 | 0.00 | 2355460.48 | 0.00 | 0.00 | 57024557.88 | 0.00 | 0.29 |
October | 0.00 | 4256309.24 | 0.00 | 6365311.92 | 0.00 | 0.00 | 0.275782E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 10417928.92 | 0.00 | 0.00 | 0.426531E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 15198203.69 | 0.00 | 0.00 | 0.550361E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.213739E+09 | 0.318249E+09 | 0.00 | 78174139.08 | 0.00 | 0.00 | 0.308144E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 197608.02 | 0.00 | 0.00 | 194411.36 | 0.00 | 0.28 |
Maximum of Months | 0.213739E+09 | 0.148861E+09 | 0.00 | 15971310.84 | 0.00 | 0.00 | 0.550361E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:05:12
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.482296E+12 | 0.539179E+10 | 0.00 | 0.170988E+13 | 0.121045E+12 |
February | 0.586122E+12 | 0.499280E+10 | 0.00 | 0.159677E+13 | 0.197331E+12 |
March | 0.755113E+12 | 0.483964E+10 | 0.00 | 0.181982E+13 | 0.347596E+12 |
April | 0.924086E+12 | 0.351128E+10 | 0.00 | 0.172452E+13 | 0.680397E+12 |
May | 0.981086E+12 | 0.220722E+10 | 0.00 | 0.139938E+13 | 0.785210E+12 |
June | 0.916950E+12 | 0.107798E+10 | 0.00 | 0.750123E+12 | 0.166239E+13 |
July | 0.941478E+12 | 0.439537E+09 | 0.00 | 0.274198E+12 | 0.195386E+13 |
August | 0.925106E+12 | 0.859417E+09 | 0.00 | 0.613562E+12 | 0.201783E+13 |
September | 0.757545E+12 | 0.146187E+10 | 0.00 | 0.119125E+13 | 0.125491E+13 |
October | 0.628012E+12 | 0.269358E+10 | 0.00 | 0.170541E+13 | 0.687530E+12 |
November | 0.511015E+12 | 0.443021E+10 | 0.00 | 0.186514E+13 | 0.255013E+12 |
December | 0.452333E+12 | 0.486679E+10 | 0.00 | 0.175529E+13 | 0.336086E+12 |
Annual Sum or Average | 0.886114E+13 | 0.367721E+11 | 0.00 | 0.164054E+14 | 0.102992E+14 |
Minimum of Months | 0.452333E+12 | 0.439537E+09 | 0.00 | 0.274198E+12 | 0.121045E+12 |
Maximum of Months | 0.981086E+12 | 0.539179E+10 | 0.00 | 0.186514E+13 | 0.201783E+13 |