Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:05

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650

Simulation Timestamp: 2023-10-16 09:05:12


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 32261.07 696.48 696.48
Net Site Energy 32261.07 696.48 696.48
Total Source Energy 84062.26 1814.80 1814.80
Net Source Energy 84062.26 1814.80 1814.80


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 708.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1256.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7193.90 0.00 0.00
Interior Lighting 2020.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 323.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 3258.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1397.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 471.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 262.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5961.31
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 692.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 23665.43 1401.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7193.90 0.00 8241.48
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 708.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 1256.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7193.90 0.00 0.00
Interior Lighting LightsWired 2020.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 323.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5334.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 54.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ComputerHVAC 1349.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 1397.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 471.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 262.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5961.31
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 692.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 708.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 1256.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7193.90 0.00 0.00
Interior Lighting GENERAL 2020.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 323.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 3258.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 1397.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 471.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 262.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5961.31
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 692.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 73.11 30.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 155.31 0.00 0.18
Other 387.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 510.91 30.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 155.31 0.00 0.18


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 73.11 30.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 155.31 0.00 0.18
Other 387.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 510.91 30.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 155.31 0.00 0.18


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 23665.427 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 23665.427 100.00
     
Total On-Site and Utility Electric Sources 23665.427 100.00
Total Electricity End Uses 23665.427 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 8241.48 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 8241.48 100.00
Total Water End Uses 8241.48 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 8.50
Time Setpoint Not Met During Occupied Cooling 358.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 5943.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EnergyConsumptionDistrictHeatingCoolingMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:05
RunPeriod RUNPERIOD 1
Weather File Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Latitude [deg] 35.04
Longitude [deg] -106.6
Elevation [m] 1619.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 5.8895 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 5.8895 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 5.8895 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 5.8895 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 8.8011 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 8.8011 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 8.8011 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 5.8895 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 5.9168 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 5.9168 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 5.8895 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 5.8895 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 5.8895 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 5.8895 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 5.8895 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 5.8895 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 5.8895 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 5.8895 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 5.8895 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 5.8895 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 5.8895 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 5.8895 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 5.8895 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 5.8895 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 5.8895 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 5.8895 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 8.8011 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 8.8011 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 8.8011 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 5.8895 18.58 484.4232  
Total 46320.38             5.9168 9.29 17.8789  
Conditioned Total 46320.38             5.9168 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 1.8190 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] District Heating [W] Water [m3/s]
Time of Peak 02-AUG-15:30 21-JAN-07:10 - - - - - - - - 21-AUG-15:00 01-MAR-00:30 28-JUN-16:19
Heating 0.00 681631.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.11 0.00
Cooling 225839.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370603.48 0.00 0.00
Interior Lighting 171235.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 778371.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 151141.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 213932.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 48821.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 42924.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 27561.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1632266.59 709192.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370603.48 12.11 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] District Heating [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.11 0.00
  Boiler 0.00 681631.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 225839.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370603.48 0.00 0.00
Interior Lighting LightsWired 171235.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 3372.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ComputerHVAC 68333.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 263.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 213932.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 48821.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 42924.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 27561.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 768.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01
Cooling 3978.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7594.36 0.00
Interior Lighting 6400.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1023.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 46480.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 10318.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 4424.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1492.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 829.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 751.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 74948.41 1519.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7594.36 0.01


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 16.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 85.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 163.95 0.00
Interior Lighting 138.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 22.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 222.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 95.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 32.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 17.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 16.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1618.04 32.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 163.95 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 16.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 85.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 163.95 0.00
Interior Lighting 138.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 22.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 222.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 95.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 32.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 17.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 16.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1618.04 32.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 163.95 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 5.92
DATACENTER_BOT_ZN_6 DIRECT AIR 0.572047
DATACENTER_MID_ZN_6 DIRECT AIR 5.46
DATACENTER_TOP_ZN_6 DIRECT AIR 0.558509
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 6.38 0.297994 0.310000 1.98 0.794649 0.500000 0.001279 0.000143 1.98 12.80 0.008000
CORE_MID VAV BOX COMPONENT 59.71 0.318540 0.324000 19.35 0.849441 0.500000 0.001196 0.003431 19.35 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 6.00 0.317065 0.331000 1.99 0.845507 0.500000 0.001202 0.000698 2.89 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 1.07 0.222863 0.232000 0.248612 0.594301 0.500000 0.001710 0.000079 0.327957 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.25 0.123293 0.200000 0.249657 0.328782 0.500000 0.003090 0.000058 0.249657 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.31 0.182056 0.200000 0.262365 0.485483 0.500000 0.002093 0.000099 0.411714 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.60 0.096318 0.200000 0.319577 0.300000 0.500000 0.003956 0.000049 0.319577 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 9.88 0.241740 0.246000 2.43 0.644640 0.500000 0.001576 0.001600 6.63 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 13.14 0.117097 0.200000 2.63 0.312259 0.500000 0.003254 0.001062 4.40 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 12.40 0.192649 0.200000 2.48 0.513732 0.500000 0.001978 0.001585 6.57 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 14.03 0.109665 0.200000 2.81 0.300000 0.500000 0.003474 0.000992 4.11 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.15 0.207368 0.216000 0.248762 0.552982 0.500000 0.001837 0.000213 0.884135 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.34 0.115282 0.200000 0.267005 0.307420 0.500000 0.003305 0.000141 0.583081 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.39 0.171796 0.200000 0.278034 0.458122 0.500000 0.002218 0.000211 0.876549 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.52 0.101461 0.200000 0.303379 0.300000 0.500000 0.003755 0.000135 0.561191 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 16386.31 0.000143 330.34
CORE_MID VAV BOX REHEAT COIL 392212.65 0.003431 9242.71
CORE_TOP VAV BOX REHEAT COIL 79734.00 0.000698 2104.64
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 9062.82 0.000079 239.25
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 6630.45 0.000058 171.99
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 11368.61 0.000099 300.01
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 5557.47 0.000049 125.79
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 182872.23 0.001600 4823.17
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 121417.22 0.001062 3202.23
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 181200.15 0.001585 4779.11
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 113412.91 0.000992 2991.31
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 24371.28 0.000213 642.63
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 16072.10 0.000141 423.79
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 24162.50 0.000211 637.13
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 15469.52 0.000135 407.91
VAV_BOT WITH REHEAT HEATING COIL 53572.94 0.000469 876.66
VAV_MID WITH REHEAT HEATING COIL 492162.04 0.004306 8059.70
VAV_TOP WITH REHEAT HEATING COIL 49205.19 0.000430 812.66
CAV_BAS HEATING COIL 245298.44 0.002146 5426.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:IdealLoadsAirSystem

Design Size Maximum Heating Air Flow Rate [m3/s] Design Size Maximum Cooling Air Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT 0.338402 25.88
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 5.81 3.06 11.61 3.06 10.49 10.49 0.300000 0.291663 10.49
VAV_MID WITH REHEAT 54.58 29.69 109.16 33.61 97.16 97.16 0.300000 0.345919 97.16
VAV_TOP WITH REHEAT 5.70 3.08 11.39 5.79 10.66 10.66 0.300000 0.543372 10.66
CAV_BAS 5.92 5.92 5.92 5.92 5.92 5.92 1.00 1.00 5.92
AIRLOOP DATACENTER BOT 0.572047 0.572047 0.572047 0.572047 0.572047 0.572047 1.00 1.00 0.572047
AIRLOOP DATACENTER MID 5.46 5.46 5.46 5.46 5.46 5.46 1.00 1.00 5.46
AIRLOOP DATACENTER TOP 0.558509 0.558509 0.558509 0.558509 0.558509 0.558509 1.00 1.00 0.558509
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 10.49  
VAV_MID WITH REHEAT_OA_CONTROLLER 97.16  
VAV_TOP WITH REHEAT_OA_CONTROLLER 10.66  
CAV_BAS_OA_CONTROLLER 5.92  
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.572047 0.015633
AIRLOOP DATACENTER MID_OA_CONTROLLER 5.46 0.156328
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.558509 0.015633
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 26.82 6.67 10.67 0.006950 0.006950 170803.67 0.007266 10.49
VAV_MID WITH REHEAT COOLING COIL 27.17 6.67 10.55 0.006927 0.006927 1628129.92 0.069264 97.16
VAV_TOP WITH REHEAT COOLING COIL 26.65 6.67 10.67 0.006955 0.006955 171726.02 0.007306 10.66
CAV_BAS COOLING COIL 26.39 6.67 11.12 0.007142 0.007142 91227.73 0.003881 5.92
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 10.49
VAV_MID WITH REHEAT FAN 97.16
VAV_TOP WITH REHEAT FAN 10.66
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.007266 0.000066
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000469  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.069264 0.000007
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.004306  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.007306 0.000065
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000430  
CAV_BAS_COOLC_CONTROLLER 0.003881 0.000123
CAV_BAS_HEATC_CONTROLLER 0.002146  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 5.92
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BOT COOLING COIL 0.572047 10205.49 5462.03 0.000250
AIRLOOP DATACENTER MID COOLING COIL 5.46 97515.33 52176.07 0.002388
AIRLOOP DATACENTER TOP COOLING COIL 0.558509 9966.77 5333.46 0.000244
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.572047 0.572047 0.572047 0.572047 10205.49 10205.49 745.23 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 5.46 5.46 5.46 5.46 97515.33 97515.33 7452.32 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.558509 0.558509 0.558509 0.558509 9966.77 9966.77 745.23 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BOT SUPPLY FAN 0.572047
AIRLOOP DATACENTER MID SUPPLY FAN 5.46
AIRLOOP DATACENTER TOP SUPPLY FAN 0.558509
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BOT HEATING COIL 0.572047 10205.49 0.000250
AIRLOOP DATACENTER MID HEATING COIL 5.46 97515.33 0.002388
AIRLOOP DATACENTER TOP HEATING COIL 0.558509 9966.77 0.000244
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 745.23
AIRLOOP DATACENTER MID_SUPPHEATCOIL 7452.32
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 745.23
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.087717 17896.35  
HEATSYS1 PUMP 0.017848 5321.90 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.087717 10.53
HEATSYS1 0.017848 2.14
COOLSYS1_SUPPLY 0.087717 10.53
SINGLE WATER PLANT LOOP 0.002882 0.345859
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.087717 0.087717 368194.17 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 2040168.81 2040168.81 0.017848
CENTRAL BOILER 118720.35 118720.35 0.002882
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.087717 12390.25
PLANT CIRC PUMP 0.002882 727.82
SWHSYS1 PUMP 0.000440 5.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.087717 0.044247 1041235.76 1047573.35 0.053110
COOLSYS1 CHILLER2 0.087717 0.044247 1041235.76 1047573.35 0.053110
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.002882 35644.39 18351.61 17822.20 1996.20 5717.83
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.106219 12.75
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.106219 31674.25
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 48.72 1244454.21 9.74 155556.78
TOWERWATERSYS COOLTOWER 2 48.72 1244454.21 9.74 155556.78
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 45
WSHPPLANT OPERATION SCHEME 0.053845
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.70 7.00 2.10 2.60 4.30 8.80 13.90 17.80 23.20 25.60 24.10 20.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 35.04 -106.62 -7.00 1619.00 83328 0.9904


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 13.63 23.50 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 105.88 86.92 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 105.88 86.92 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 5.889 4.842 0.000 0.000 0.000 0.000 10.731 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 8.801 215.299 0.000 0.000 0.000 0.000 224.100 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 8.801 215.299 0.000 0.000 0.000 0.000 224.100 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 8.801 215.299 0.000 0.000 0.000 0.000 224.100 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 5.889 484.423 0.000 0.000 0.000 0.000 490.313 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 16369.361 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16369.361
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 14700.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14700.837
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 14700.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14700.837
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 14700.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14700.837
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 1845.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.837
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 1845.877 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.877
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 1845.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.837
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 1845.877 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.877
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 1845.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.837
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 1845.877 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.877
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 4615.459 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4615.459
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 318.624 8.801 163.514 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 318.624
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 318.624 8.801 163.514 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 318.624
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 318.624 8.801 163.514 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 318.624


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.1864 0.900 0.900 0.700 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.339 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.260 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.694 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.5795
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.6262
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.4230
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 2.312
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 2.312
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
47 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
48 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
49 0 21.357363 0.71091016E-01 5.4032014  
50 9 0.13684007E-14 0.43769670E-16 -0.13032795E-09 -0.34517937E-17
51 8 0.19139952E-07 0.17580734E-12 0.34842432E-03 -0.21762784E-09
52 7 -0.11363040E-01 0.94207812E-08 -0.21820187E-01 0.12920189E-03
53 6 0.38147639 0.33245073E-05 0.45170425 -0.44663469E-02
54 5 -4.9575440 0.12566514E-03 -4.2844407 0.60294545E-01
55 4 31.971915 0.10393916E-02 20.826829 -0.40843520
56 3 -109.03212 0.22875987E-02 -54.410870 1.4834967
57 2 194.95586 0.12980373E-02 76.763178 -2.8661744
58 1 -170.36074 0.13969006E-03 -54.933270 2.7315001
59 0 57.057407 0.80219562E-06 15.613236  
60 9 0.17296484E-14 0.42300129E-16 -0.13408130E-09 -0.44058463E-17
61 8 0.19671007E-07 0.16641005E-12 0.35423406E-03 -0.22366611E-09
62 7 -0.11537194E-01 0.88593938E-08 -0.22071206E-01 0.13118209E-03
63 6 0.38620962 0.31182457E-05 0.45575528 -0.45221398E-02
64 5 -5.0037487 0.11760487E-03 -4.3156427 0.60867449E-01
65 4 32.176377 0.97077592E-03 20.948989 -0.41114975
66 3 -109.46738 0.21328008E-02 -54.652468 1.4897847
67 2 195.38754 0.12083052E-02 76.984396 -2.8730290
68 1 -170.52030 0.12984550E-03 -54.996922 2.7342967
69 0 57.057407 0.74448799E-06 15.602172  
70 9 0.10997584E-14 0.53843923E-16 -0.11326114E-09 -0.28570046E-17
71 8 0.16725364E-07 0.21557791E-12 0.32127585E-03 -0.19017314E-09
72 7 -0.10546704E-01 0.11930081E-07 -0.20642631E-01 0.11991984E-03
73 6 0.35928609 0.42648229E-05 0.43264702 -0.42047803E-02
74 5 -4.7408821 0.16300219E-03 -4.1373754 0.57608138E-01
75 4 31.012880 0.13615538E-02 20.250423 -0.39570291
76 3 -106.98970 0.30226891E-02 -53.270634 1.4539929
77 2 192.92930 0.17282771E-02 75.720319 -2.8339965
78 1 -169.61128 0.18730106E-03 -54.635416 2.7183650
79 0 57.057407 0.10839563E-05 15.666826  
80 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
81 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
82 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
83 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
84 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
85 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
86 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
87 0 0.43108349 0.21254961E-04 60.838472  
88 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
89 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
90 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
91 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
92 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
93 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
94 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
95 0 0.43108349 0.21254961E-04 60.838472  
96 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
97 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
98 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
99 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
100 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
101 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
102 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
103 0 0.43108349 0.21254961E-04 60.838472  
104 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
105 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
106 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
107 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
108 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
109 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
110 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
111 0 0.43108349 0.21254961E-04 60.838472  
112 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
113 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
114 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
115 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
116 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
117 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
118 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
119 0 0.43108349 0.21254961E-04 60.838472  
120 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
121 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
122 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
123 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
124 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
125 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
126 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
127 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.3628_SHGC_EAST_0.36 35 1 VerySmooth 2.061 2.061 1.000 0.361    
2 WINDOW_U_0.3628_SHGC_SOUTH_0.36 36 1 VerySmooth 2.061 2.061 1.000 0.361    
3 WINDOW_U_0.3628_SHGC_WEST_0.36 37 1 VerySmooth 2.061 2.061 1.000 0.361    
4 WINDOW_U_0.3628_SHGC_NORTH_0.36 38 1 VerySmooth 2.061 2.061 1.000 0.361    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   3.62909E-002 0.27318 0.51969 0.51969 0.36000 0.14234 0.19141 0.00000 0.84000 0.84000 0.11614 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   3.62909E-002 0.27318 0.51969 0.51969 0.36000 0.14234 0.19141 0.00000 0.84000 0.84000 0.11614 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   3.62909E-002 0.27318 0.51969 0.51969 0.36000 0.14234 0.19141 0.00000 0.84000 0.84000 0.11614 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   3.62909E-002 0.27318 0.51969 0.51969 0.36000 0.14234 0.19141 0.00000 0.84000 0.84000 0.11614 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.496 7.5104E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 2.856E-002 9.114E-005 1.371E-004 0.120 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 1.904E-002 9.429E-005 1.384E-004 0.124 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 2.856E-002 9.114E-005 1.371E-004 0.120 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 1.904E-002 9.429E-005 1.384E-004 0.124 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 2.856E-002 9.114E-005 1.424E-004 0.120 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 1.904E-002 9.429E-005 1.424E-004 0.124 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 2.856E-002 9.114E-005 1.424E-004 0.120 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 1.904E-002 9.429E-005 1.424E-004 0.124 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 2.856E-002 9.114E-005 1.424E-004 0.120 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 1.904E-002 9.429E-005 1.424E-004 0.124 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 2.856E-002 9.114E-005 1.424E-004 0.120 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 1.904E-002 9.429E-005 1.424E-004 0.124 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 4.231E-002 1.187E-005 1.424E-004 3.506E-002 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 4.231E-002 1.187E-005 1.424E-004 3.506E-002 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 4.231E-002 1.187E-005 1.096E-005 3.506E-002 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.3860E-003
2 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.3877E-003
3 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.7646E-003
4 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.7661E-003
5 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.2096E-003
6 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.2108E-003
7 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7698E-003
8 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7704E-003
9 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.4263E-003
10 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.5465E-003
11 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.7986E-003
12 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.9037E-003
13 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.2388E-003
14 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.3257E-003
15 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7873E-003
16 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.8319E-003
17 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1196
18 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.8845E-002
19 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1355
20 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 6.5656E-002
21 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 9.0371E-002
22 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.6353E-002
23 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.7170E-002
24 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.3047E-002
25 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.4280E-003
26 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.5543E-003
27 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.8003E-003
28 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.9115E-003
29 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.2403E-003
30 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.3313E-003
31 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7877E-003
32 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.8332E-003
33 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.3858E-003
34 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.3876E-003
35 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.7644E-003
36 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.7659E-003
37 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.2095E-003
38 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.2107E-003
39 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7697E-003
40 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7704E-003
41 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.8299E-003
42 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.0528E-003
43 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.6131E-003
44 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.8530E-003
45 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.4827E-003
46 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.5867E-003
47 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.0284E-003
48 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0591E-003
49 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.3479E-002
50 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.2194E-002
51 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.0362E-002
52 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.9896E-002
53 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.5737E-002
54 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.9221E-002
55 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.8227E-002
56 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.4292E-002
57 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.7647E-003
58 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.8465E-003
59 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.5292E-003
60 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.5885E-003
61 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.4496E-003
62 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.4728E-003
63 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.0285E-003
64 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0596E-003
65 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8157E-003
66 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8174E-003
67 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5441E-003
68 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5454E-003
69 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3660E-003
70 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3669E-003
71 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7698E-003
72 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7704E-003
73 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8531E-003
74 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.9507E-003
75 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5744E-003
76 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6511E-003
77 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3903E-003
78 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4442E-003
79 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7878E-003
80 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8333E-003
81 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.8930E-002
82 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6752E-002
83 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.2371E-002
84 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2695E-002
85 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.2483E-002
86 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 8.9379E-003
87 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.7170E-002
88 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3043E-002
89 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8521E-003
90 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.9483E-003
91 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5734E-003
92 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6487E-003
93 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3891E-003
94 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4408E-003
95 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7873E-003
96 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8320E-003
97 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8156E-003
98 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8172E-003
99 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5440E-003
100 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5453E-003
101 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3659E-003
102 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3668E-003
103 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7697E-003
104 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7704E-003
105 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.6979E-003
106 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.7802E-003
107 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.4464E-003
108 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.5059E-003
109 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3938E-003
110 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.4166E-003
111 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0286E-003
112 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0596E-003
113 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.2184E-002
114 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1678E-002
115 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.8773E-002
116 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.9263E-002
117 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.4581E-002
118 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.8756E-002
119 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.8227E-002
120 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.4292E-002
121 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.7608E-003
122 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.9745E-003
123 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.5274E-003
124 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.7558E-003
125 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.4264E-003
126 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.5287E-003
127 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0283E-003
128 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0590E-003
129 Clear Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1090
130 Clear Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 7.5388E-002
131 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1192
132 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 8.3241E-002
133 Intermediate Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 9.3368E-002
134 Intermediate Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 4.9843E-002
135 Overcast Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 4.2949E-002
136 Overcast Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 2.0811E-002
137 Clear Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.0110E-002
138 Clear Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.0676E-002
139 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.6719E-002
140 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.7948E-002
141 Intermediate Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.1972E-002
142 Intermediate Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.6919E-002
143 Overcast Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.3948E-002
144 Overcast Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.1031E-002
145 Clear Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.4588E-002
146 Clear Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.4431E-002
147 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.7447E-002
148 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.9285E-002
149 Intermediate Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.7506E-002
150 Intermediate Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.4992E-002
151 Overcast Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.2949E-002
152 Overcast Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.0807E-002
153 Clear Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 4.8707E-002
154 Clear Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.0000E-002
155 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 4.4993E-002
156 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.7115E-002
157 Intermediate Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.0730E-002
158 Intermediate Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.6331E-002
159 Overcast Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 4.3948E-002
160 Overcast Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.1031E-002
161 Clear Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1089
162 Clear Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 7.5496E-002
163 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1191
164 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 8.3371E-002
165 Intermediate Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 9.3388E-002
166 Intermediate Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 4.9944E-002
167 Overcast Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 4.2998E-002
168 Overcast Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 2.0851E-002
169 Clear Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.0082E-002
170 Clear Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.0702E-002
171 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.6703E-002
172 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.7974E-002
173 Intermediate Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.1989E-002
174 Intermediate Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.6965E-002
175 Overcast Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.3994E-002
176 Overcast Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.1071E-002
177 Clear Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.4543E-002
178 Clear Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.4440E-002
179 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.7416E-002
180 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.9293E-002
181 Intermediate Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.7519E-002
182 Intermediate Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.5014E-002
183 Overcast Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.2998E-002
184 Overcast Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.0847E-002
185 Clear Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 4.8678E-002
186 Clear Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.0025E-002
187 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 4.4975E-002
188 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.7140E-002
189 Intermediate Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.0746E-002
190 Intermediate Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.6376E-002
191 Overcast Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 4.3994E-002
192 Overcast Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.1071E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 67481.42265 67481.42265 5.92487 5.92487 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 25.11000 5.68410E-003 2779.42662 149.60210 1.20019 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20019 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 -7.90000 2.34317E-003 2779.42662 149.60210 1.20019 0.00000
3 CORE_BOTTOM Cooling 72698.80488 72698.80488 6.38284 6.38284 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 25.11000 5.68410E-003 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 06:30:00 -7.90000 2.34317E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 680271.83257 680271.83257 59.71124 59.71124 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 25.11000 5.68410E-003 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 231996.30516 231996.30516 11.89377 11.89377 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -7.90000 2.34317E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 67722.60799 67722.60799 5.99890 5.99890 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 35.10000 5.69938E-003 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 55833.43892 55833.43892 2.88604 2.88604 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -7.90000 2.34317E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 12097.75478 12097.75478 1.07160 1.07160 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 35.10000 5.69938E-003 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 6348.18638 6348.18638 0.32796 0.32796 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -7.90000 2.34317E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 14092.48820 14092.48820 1.24828 1.24828 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 27.67500 5.68796E-003 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 4563.77433 4563.77433 0.23593 0.23593 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -7.90000 2.34317E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 14809.73902 14809.73902 1.31182 1.31182 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 34.65000 5.69869E-003 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 7960.04906 7960.04906 0.41171 0.41171 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -7.90000 2.34317E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 18039.35423 18039.35423 1.59788 1.59788 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 33.39000 5.69673E-003 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 2913.25855 2913.25855 0.15011 0.15011 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -7.90000 2.34317E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 111530.95547 111530.95547 9.87924 9.87924 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 35.10000 5.69938E-003 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 127973.58069 127973.58069 6.63085 6.63085 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -7.90000 2.34317E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 148382.83518 148382.83518 13.14338 13.14338 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 28.44000 5.68912E-003 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 84965.18953 84965.18953 4.40279 4.40279 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -7.90000 2.34317E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 139954.44738 139954.44738 12.39691 12.39691 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 34.76250 5.69886E-003 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 126804.70501 126804.70501 6.57009 6.57009 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -7.90000 2.34317E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 158439.26832 158439.26832 14.03415 14.03415 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 33.21000 5.69645E-003 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 79369.44463 79369.44463 4.11200 4.11200 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -7.90000 2.34317E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 13001.80192 13001.80192 1.15167 1.15167 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 35.10000 5.69938E-003 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 17051.09552 17051.09552 0.88414 0.88414 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -7.90000 2.34317E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 15071.86712 15071.86712 1.33503 1.33503 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 28.82250 5.68971E-003 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 11244.50925 11244.50925 0.58308 0.58308 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -7.90000 2.34317E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 15694.35166 15694.35166 1.39017 1.39017 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 34.98750 5.69921E-003 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 16905.13903 16905.13903 0.87655 0.87655 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -7.90000 2.34317E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 17125.12755 17125.12755 1.51690 1.51690 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 33.21000 5.69645E-003 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 10823.19482 10823.19482 0.56119 0.56119 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -7.90000 2.34317E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8187.78955 8187.78955 0.57205 0.57205 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 30.51000 5.69229E-003 36.20274 1.94861 1.56328E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56328E-002 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 06:30:00 -7.90000 2.34317E-003 36.20274 1.94861 1.56328E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 78194.15466 78194.15466 5.46315 5.46315 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 30.17250 5.69177E-003 36.20274 1.94861 0.15633 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15633 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 05:40:00 -7.90000 2.34317E-003 36.20274 1.94861 0.15633 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 7993.98719 7993.98719 0.55851 0.55851 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 30.51000 5.69229E-003 36.20274 1.94861 1.56328E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56328E-002 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 05:40:00 -7.90000 2.34317E-003 36.20274 1.94861 1.56328E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 370482.91565 370482.91565 25.88364 25.88364 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 22.81500 5.68069E-003 783.67941 42.18139 0.33840 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33840 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 -7.90000 2.34317E-003 783.67941 42.18139 0.33840 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 139179.39 10.48774 10.48774 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 45395.35 2.20354 2.20354 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1270288.12 97.16011 97.16011 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 522839.33 33.60951 33.60951 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 20:00:00
5 VAV_TOP WITH REHEAT Cooling Sensible 146366.90 10.65751 10.65751 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 51682.62 5.79100 5.79100 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 06:00:00
7 CAV_BAS Cooling Sensible 70813.47 5.92487 5.92487 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 57214.39 1.20019 1.20019 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
9 AIRLOOP DATACENTER BOT Cooling Sensible 8137.90 0.57205 0.57205 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BOT Heating Sensible 745.23 1.56328E-002 1.56328E-002 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
11 AIRLOOP DATACENTER MID Cooling Sensible 77736.59 5.46315 5.46315 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER MID Heating Sensible 7452.32 0.15633 0.15633 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
13 AIRLOOP DATACENTER TOP Cooling Sensible 7946.57 0.55851 0.55851 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER TOP Heating Sensible 745.23 1.56328E-002 1.56328E-002 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.92487
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.38284
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.29799
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.31000
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.97868
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.79465
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.27855E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.43355E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.97868
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16386.30636
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.43355E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 330.33507
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 59.71124
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.31854
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.32400
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 19.34644
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.84944
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.19608E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.43125E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 19.34644
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 392212.64843
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.43125E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 9242.71072
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.99890
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.31707
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33100
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.98564
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.84551
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.20165E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.97548E-004
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.88604
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 79733.99513
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.97548E-004
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2104.63894
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.07160
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22286
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.23200
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24861
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.59430
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.70957E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.92855E-005
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.32796
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9062.82255
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.92855E-005
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 239.24681
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.24828
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12329
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24966
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.32878
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.09019E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.80061E-005
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.24966
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6630.45242
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.80061E-005
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 171.98681
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.31182
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18206
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.26236
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.48548
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.09276E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.94576E-005
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.41171
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11368.61244
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.94576E-005
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 300.01033
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.59788
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.63181E-002
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.31958
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.95564E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.86192E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.31958
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5557.47149
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.86192E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 125.78513
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.87924
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24174
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.24600
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.43029
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.64464
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.57607E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.59985E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.63085
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 182872.22730
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.59985E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4823.16928
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 13.14338
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11710
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.62868
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.31226
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.25371E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.06221E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.40279
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 121417.21843
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.06221E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3202.23254
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 12.39691
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19265
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.47938
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51373
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.97769E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.58522E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.57009
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 181200.14802
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.58522E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4779.11117
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 14.03415
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10966
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.80683
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.47423E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.92186E-004
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.11200
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 113412.90556
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.92186E-004
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2991.30903
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.15167
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20737
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.21600
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24876
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.55298
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.83731E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.13211E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.88414
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 24371.27764
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.13211E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 642.63291
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.33503
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11528
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.26701
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30742
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.30493E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.40606E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.58308
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16072.10367
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.40606E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 423.78949
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.39017
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17180
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.27803
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.45812
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.21775E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.11384E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.87655
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 24162.50296
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.11384E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 637.13178
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.51690
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10146
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.30338
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.75516E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.35334E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.56119
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15469.51513
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.35334E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 407.90985
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.57205
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.46315
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.55851
215 ZoneHVAC:IdealLoadsAirSystem AIRLOOP DATACENTER BASEMENT Design Size Maximum Heating Air Flow Rate [m3/s] 0.33840
216 ZoneHVAC:IdealLoadsAirSystem AIRLOOP DATACENTER BASEMENT Design Size Maximum Cooling Air Flow Rate [m3/s] 25.88364
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.80621
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.05889
219 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 11.61243
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.05889
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 10.48774
222 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 10.48774
223 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
224 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.29166
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 54.58246
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 29.69162
227 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 109.16492
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 33.60951
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 97.16011
230 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 97.16011
231 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
232 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.34592
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.69634
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.08282
235 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 11.39267
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 5.79100
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 10.65751
238 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 10.65751
239 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
240 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.54337
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.92487
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.92487
243 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 5.92487
244 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 5.92487
245 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 5.92487
246 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 5.92487
247 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
249 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.57205
250 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.57205
251 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.57205
252 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.57205
253 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.57205
254 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.57205
255 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
256 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
257 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.46315
258 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.46315
259 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 5.46315
260 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 5.46315
261 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 5.46315
262 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 5.46315
263 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
265 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.55851
266 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.55851
267 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.55851
268 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.55851
269 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.55851
270 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.55851
271 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
273 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 10.48774
274 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 97.16011
275 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 10.65751
276 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 5.92487
277 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.57205
278 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 5.46315
279 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.55851
280 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 10.48774
281 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.82439
282 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
283 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.66759
284 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 6.95019E-003
285 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 6.95019E-003
286 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 170803.66816
287 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.26638E-003
288 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 10.48774
289 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 53572.94005
290 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.68679E-004
291 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 876.66241
292 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 10.48774
293 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 7.26638E-003
294 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 6.55334E-005
295 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 4.68679E-004
296 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 97.16011
297 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.17125
298 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
299 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.54634
300 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 6.92715E-003
301 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 6.92715E-003
302 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 1628129.91793
303 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.92644E-002
304 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 97.16011
305 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 492162.03702
306 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.30565E-003
307 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 8059.70099
308 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 97.16011
309 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 6.92644E-002
310 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 6.87497E-006
311 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 4.30565E-003
312 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 10.65751
313 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.65277
314 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
315 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.66761
316 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 6.95454E-003
317 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 6.95454E-003
318 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 171726.02431
319 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.30562E-003
320 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 10.65751
321 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 49205.19164
322 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.30468E-004
323 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 812.65837
324 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 10.65751
325 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 7.30562E-003
326 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 6.51814E-005
327 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 4.30468E-004
328 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.92487
329 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 26.38829
330 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
331 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.11839
332 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.14156E-003
333 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.14156E-003
334 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 91227.72715
335 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.88104E-003
336 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.92487
337 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 245298.43626
338 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.14598E-003
339 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 5426.05473
340 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 5.92487
341 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 3.88104E-003
342 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.22697E-004
343 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.14598E-003
344 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.57205
345 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56328E-002
346 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.57205
347 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 10205.48511
348 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 5462.03377
349 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.49932E-004
350 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.57205
351 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.57205
352 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.57205
353 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.57205
354 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 10205.48511
355 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 10205.48511
356 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 745.23210
357 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
358 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.57205
359 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.57205
360 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 10205.48511
361 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.49932E-004
362 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 745.23210
363 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.46315
364 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15633
365 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 5.46315
366 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 97515.33294
367 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 52176.07128
368 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.38814E-003
369 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 5.46315
370 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 5.46315
371 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 5.46315
372 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 5.46315
373 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 97515.33294
374 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 97515.33294
375 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 7452.32102
376 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
377 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 5.46315
378 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 5.46315
379 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 97515.33294
380 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.38814E-003
381 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 7452.32102
382 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.55851
383 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56328E-002
384 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.55851
385 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9966.77447
386 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 5333.46173
387 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.44086E-004
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.55851
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.55851
390 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.55851
391 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.55851
392 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9966.77447
393 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9966.77447
394 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 745.23210
395 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
396 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.55851
397 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.55851
398 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9966.77447
399 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.44086E-004
400 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 745.23210
401 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 8.77175E-002
402 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 17896.35259
403 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 8.77175E-002
404 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 10.52609
405 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 8.77175E-002
406 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 8.77175E-002
407 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 368194.16742
408 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
409 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 1.78483E-002
410 PlantLoop HEATSYS1 Plant Loop Volume [m3] 2.14179
411 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 1.78483E-002
412 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 5321.90116
413 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
414 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 2040168.81250
415 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 2040168.81000
416 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 1.78483E-002
417 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 8.77175E-002
418 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 10.52609
419 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 8.77175E-002
420 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 12390.24858
421 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 8.77175E-002
422 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 4.42471E-002
423 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1041235.75617
424 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1047573.35500
425 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 5.31097E-002
426 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 8.77175E-002
427 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 4.42471E-002
428 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1041235.75617
429 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1047573.35500
430 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 5.31097E-002
431 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 2.88216E-003
432 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 0.34586
433 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 2.88216E-003
434 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 727.81716
435 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 2.88216E-003
436 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 35644.39112
437 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 18351.61028
438 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 17822.19556
439 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 1996.19659
440 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 5717.82824
441 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 118720.34761
442 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 118720.35000
443 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 2.88216E-003
444 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
445 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
446 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
447 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 5.95776
448 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
449 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.10622
450 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 12.74634
451 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.10622
452 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 31674.25037
453 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 48.71626
454 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1244454.20625
455 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 9.74325
456 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 155556.77578
457 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 48.71626
458 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1244454.20625
459 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 9.74325
460 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 155556.77578
461 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 45 5.38450E-002
462 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 45 5.38450E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 15539.96
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 371734.75
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 75585.31
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 8591.45
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 6282.30
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 10776.59
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 5268.27
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 173330.88
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 115081.68
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 171746.33
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 107496.25
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 23098.70
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 15232.83
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 22900.86
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 14661.78
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 40762.93
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 375083.22
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 38160.65
19 Coil:Heating:Water CAV_BAS HEATING COIL 193055.61


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 227411.43 143975.25 83436.19 0.63 23198.97 235.30
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2148671.52 1351687.09 796984.43 0.63 220983.66 2241.34
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 230011.28 145883.69 84127.59 0.63 23504.42 238.39
4 Coil:Cooling:Water CAV_BAS COOLING COIL 122119.22 78482.21 43637.01 0.64 12031.54 122.03


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 7.08 24.14
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 7.08 24.14


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.339 1.115   105.88 200.61 105.88 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_NORTH_0.36 N/A 2.061 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_NORTH_0.36 N/A 2.061 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_NORTH_0.36 N/A 2.061 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_NORTH_0.36 N/A 2.061 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_NORTH_0.36 N/A 2.061 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.339 1.115   71.89 133.74 71.89 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_EAST_0.36 N/A 2.061 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_EAST_0.36 N/A 2.061 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_EAST_0.36 N/A 2.061 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.339 1.115   105.88 200.61 105.88 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_SOUTH_0.36 N/A 2.061 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_SOUTH_0.36 N/A 2.061 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_SOUTH_0.36 N/A 2.061 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_SOUTH_0.36 N/A 2.061 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_SOUTH_0.36 N/A 2.061 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.339 1.115   71.89 133.74 71.89 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_WEST_0.36 N/A 2.061 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_WEST_0.36 N/A 2.061 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_WEST_0.36 N/A 2.061 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.260 1.060   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_NORTH_0.36 N/A 2.061 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.260 1.060   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_EAST_0.36 N/A 2.061 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.260 1.060   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_SOUTH_0.36 N/A 2.061 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.260 1.060   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_WEST_0.36 N/A 2.061 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.694 1.351   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_NORTH_0.36 N/A 2.061 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.694 1.351   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_EAST_0.36 N/A 2.061 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.694 1.351   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_SOUTH_0.36 N/A 2.061 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.694 1.351   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3628_SHGC_WEST_0.36 N/A 2.061 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.339 1.115   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.339 1.115   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.339 1.115   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.339 1.115   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.260 1.060   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.260 1.060   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.260 1.060   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.260 1.060   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.694 1.351   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.694 1.351   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.694 1.351   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.694 1.351   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.419 0.394   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.2703190554 0.2393073030 Pass Pass 1.3078150116 3.3645806942 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 0.1053200471 0.1867453882 Pass Pass 0.1611204753 0.3662005878 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 6.7022232701E-002 0.1296561022 Pass Pass 0.1335922897 0.3390372838 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 5.8321574508E-002 5.4627354301E-002 Pass Pass 0.1156550310 0.3179474301 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 8.0338556494E-002 0.1319801177 Pass Pass 0.1604612090 0.3648564834 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.1768742314 0.2511807182 Pass Pass 0.1629586214 0.3686518247 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.2550157716 0.4494589672 Pass Pass 0.1803179142 0.3992724288 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 0.1760505493 0.2957874705 Pass Pass 0.1597025447 0.3610548940 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 5.0760122905E-002 6.8756358257E-002 Pass Pass 0.1328603367 0.3363443662 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.1453450397 0.1971656847 Pass Pass 0.1357875420 0.3429127498 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.2882093537 0.4934812694 Pass Pass 0.1459982245 0.3630826909 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.1284382440 0.1894682604 Pass Pass 0.1312421155 0.3297157368 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 7.1055212427E-002 0.1028359251 Pass Pass 0.1633563325 0.5363042836 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 9.6571671016E-002 0.1189610134 Pass Pass 0.1997571828 0.9577940891 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.2064583168 0.2348531380 Pass Pass 0.1192741492 0.3174483292 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.1133803104 0.1377518141 Pass Pass 0.1181863573 0.3296024247 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 1.7404693688E-002 2.6691896383E-002 Pass Pass 0.5531899410 1.9958527559 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 2.2655713272E-002 3.6489634492E-002 Pass Pass 0.2150967455 0.5558879297 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 8.9024907421E-002 7.1687062478E-002 Pass Pass 0.1331139002 0.3436630803 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 5.2169205160E-006 6.8077050365E-006 Pass Pass 6.4884779185E-003 8.5039459715E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 5.0906075694E-006 6.6362929184E-006 Pass Pass 3.3243326110E-002 2.1485918094E-002 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 3.1677525095E-002 2.6260858363E-002 Pass Pass 0.1046767129 0.3719969774 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 2.0724163126E-015 2.5295332481E-015 Pass Pass 5.8988249839E-005 1.0439200289E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 8861.14 36.77 0.00 16405.59 10299.20 35602.69



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB -7.90 0.00 -7.90 Wetbulb [C] 3.20 0.00
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 35.10 13.50 15.70 Wetbulb [C] 4.40 220.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 9.00 6      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 0.00 0      
Oct 5.00 4      
Nov 9.00 7      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.115 1.339 200.61 105.88 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.115 1.339 133.74 71.89 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.115 1.339 200.61 105.88 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.115 1.339 133.74 71.89 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.060 1.260 2006.06 1136.85 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.060 1.260 1337.37 757.90 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.060 1.260 2006.06 1136.85 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.060 1.260 1337.37 757.90 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.351 1.694 200.61 113.68 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.351 1.694 133.74 75.79 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.351 1.694 200.61 113.68 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.351 1.694 133.74 75.79 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.115 1.339 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 1.115 1.339 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.115 1.339 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.115 1.339 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.060 1.260 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.060 1.260 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.060 1.260 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.060 1.260 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.351 1.694 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.351 1.694 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.351 1.694 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.351 1.694 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.30 0.182 0.186 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.399 0.419 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.3628_SHGC_NORTH_0.36   17.38 0.00 0.00 17.38 17.38 2.061 0.361 0.361             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.3628_SHGC_NORTH_0.36   17.38 0.00 0.00 17.38 17.38 2.061 0.361 0.361             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.3628_SHGC_NORTH_0.36   17.38 0.00 0.00 17.38 17.38 2.061 0.361 0.361             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.3628_SHGC_NORTH_0.36   17.38 0.00 0.00 17.38 17.38 2.061 0.361 0.361             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.3628_SHGC_NORTH_0.36   17.38 0.00 0.00 17.38 17.38 2.061 0.361 0.361             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.3628_SHGC_EAST_0.36   19.32 0.00 0.00 19.32 19.32 2.061 0.361 0.361             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.3628_SHGC_EAST_0.36   19.32 0.00 0.00 19.32 19.32 2.061 0.361 0.361             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.3628_SHGC_EAST_0.36   19.32 0.00 0.00 19.32 19.32 2.061 0.361 0.361             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.3628_SHGC_SOUTH_0.36   17.38 0.00 0.00 17.38 17.38 2.061 0.361 0.361             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.3628_SHGC_SOUTH_0.36   17.38 0.00 0.00 17.38 17.38 2.061 0.361 0.361             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.3628_SHGC_SOUTH_0.36   17.38 0.00 0.00 17.38 17.38 2.061 0.361 0.361             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.3628_SHGC_SOUTH_0.36   17.38 0.00 0.00 17.38 17.38 2.061 0.361 0.361             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.3628_SHGC_SOUTH_0.36   17.38 0.00 0.00 17.38 17.38 2.061 0.361 0.361             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.3628_SHGC_WEST_0.36   19.32 0.00 0.00 19.32 19.32 2.061 0.361 0.361             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.3628_SHGC_WEST_0.36   19.32 0.00 0.00 19.32 19.32 2.061 0.361 0.361             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.3628_SHGC_WEST_0.36   19.32 0.00 0.00 19.32 19.32 2.061 0.361 0.361             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.3628_SHGC_NORTH_0.36   86.92 0.00 0.00 86.92 869.21 2.061 0.361 0.361             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.3628_SHGC_EAST_0.36   57.95 0.00 0.00 57.95 579.48 2.061 0.361 0.361             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.3628_SHGC_SOUTH_0.36   86.92 0.00 0.00 86.92 869.21 2.061 0.361 0.361             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.3628_SHGC_WEST_0.36   57.95 0.00 0.00 57.95 579.48 2.061 0.361 0.361             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.3628_SHGC_NORTH_0.36   86.92 0.00 0.00 86.92 86.92 2.061 0.361 0.361             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.3628_SHGC_EAST_0.36   57.95 0.00 0.00 57.95 57.95 2.061 0.361 0.361             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.3628_SHGC_SOUTH_0.36   86.92 0.00 0.00 86.92 86.92 2.061 0.361 0.361             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.3628_SHGC_WEST_0.36   57.95 0.00 0.00 57.95 57.95 2.061 0.361 0.361             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             3476.85 2.061 0.361 0.361                      
North Total or Average             1043.06 2.061 0.361 0.361                      
Non-North Total or Average             2433.80 2.061 0.361 0.361                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 5.8895 2779.43 16369.36 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 135.58
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 5.8895 2496.12 14700.84 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 121.76
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 5.8895 24961.20 147008.37 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 1217.57
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 5.8895 2496.12 14700.84 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 121.76
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 5.8895 313.41 1845.84 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.59 0.0000 Y 8.87
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 5.8895 201.98 1189.53 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.47 0.0000 Y 5.69
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 5.8895 313.42 1845.88 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.15 0.0000 Y 8.71
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 5.8895 201.98 1189.53 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.25 0.0000 Y 5.64
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 5.8895 3134.13 18458.37 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.60 0.0000 Y 88.69
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 5.8895 2019.75 11895.27 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.46 0.0000 Y 56.86
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 5.8895 3134.20 18458.77 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.15 0.0000 Y 87.15
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 5.8895 2019.75 11895.27 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.25 0.0000 Y 56.38
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 5.8895 313.41 1845.84 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.60 0.0000 Y 8.87
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 5.8895 201.98 1189.53 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.46 0.0000 Y 5.69
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 5.8895 313.42 1845.88 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.15 0.0000 Y 8.71
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 5.8895 201.98 1189.53 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.25 0.0000 Y 5.64
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 5.8895 783.68 4615.46 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 38.23
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 8.8011 36.20 318.62 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 3.26
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 8.8011 362.03 3186.24 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 32.64
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 8.8011 36.20 318.62 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 3.26
Interior Lighting Total       5.9168 46320.38 274067.57               635.59


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.88 711.95
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.88 255.65
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.84 711.94
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.84 255.65
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.88 711.95
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.88 255.65
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.84 711.94
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.84 255.65
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.88 711.95
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.88 255.65
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.84 711.94
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.84 255.65
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 9973.05 AstronomicalClock -   41.81 41.81 78.28
EXTERIOR_LIGHTS_B 991.40 AstronomicalClock -   83.71 62.76 11.68
EXTERIOR_LIGHTS_C 26646.63 AstronomicalClock -   83.71 46.63 233.23
Exterior Lighting Total 37611.08           323.19



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2057145.61          
HEATSYS1 BOILER Boiler:HotWater 2040168.81 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1047573.35 5.33 1035777.15 4.98 7.08 24.14
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1047573.35 5.33 1035777.15 4.98 7.08 24.14
CENTRAL TOWER FluidCooler:TwoSpeed 148548.00          
CENTRAL BOILER Boiler:HotWater 118720.35 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1244454.21          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1244454.21          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 170803.67 227411.43 143975.25 83436.19 0.63 - 23198.97 235.30
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 1628129.92 2148671.52 1351687.09 796984.43 0.63 - 220983.66 2241.34
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 171726.02 230011.28 145883.69 84127.59 0.63 - 23504.42 238.39
CAV_BAS COOLING COIL Coil:Cooling:Water 91227.73 122119.22 78482.21 43637.01 0.64 - 12031.54 122.03
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   10205.49 5462.03 4743.45 0.54 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   97515.33 52176.07 45339.26 0.54 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9966.77 5333.46 4633.31 0.54 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 16386.31 15539.96 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 392212.65 371734.75 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 79734.00 75585.31 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 9062.82 8591.45 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 6630.45 6282.30 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 11368.61 10776.59 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 5557.47 5268.27 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 182872.23 173330.88 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 121417.22 115081.68 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 181200.15 171746.33 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 113412.91 107496.25 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 24371.28 23098.70 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 16072.10 15232.83 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 24162.50 22900.86 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 15469.52 14661.78 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 53572.94 40762.93 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 492162.04 375083.22 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 49205.19 38160.65 -
CAV_BAS HEATING COIL Coil:Heating:Water 245298.44 193055.61 -
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   10205.49 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   97515.33 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9966.77 0.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   745.23 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   7452.32 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   745.23 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 10.49 22543.03 2149.46 1.00 1.12 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 97.16 220708.26 2271.59 1.00 1.08 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 10.66 22907.94 2149.46 1.00 1.12 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 5.92 10046.53 1695.65 1.00 1.15 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.57 640.75 1120.11 1.00 1.55 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 5.46 6119.32 1120.11 1.00 1.15 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.56 625.59 1120.11 1.00 1.56 General ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.087717 17896.35 204022.71 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.017848 5321.90 298174.34 0.91 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.087717 12390.25 141251.81 0.91 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.002882 727.82 252524.76 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 3168.45 0.000440 5.96 13540.37 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 180718.98 0.106219 31674.25 298196.27 0.91 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.50 0.08



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 67481.42 67481.42 24.28 5.925 5.925 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00752 25.11 0.00568 1.200 0.00
CORE_BOTTOM 72698.80 72698.80 29.12 6.383 6.383 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00743 25.11 0.00568 1.078 0.00
CORE_MID 680271.83 680271.83 272.53 59.711 59.711 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00746 25.11 0.00568 10.778 0.00
CORE_TOP 67722.61 67722.61 27.13 5.999 5.999 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 24.00 0.00745 35.10 0.00570 1.078 0.00
PERIMETER_BOT_ZN_3 12097.75 12097.75 38.60 1.072 1.072 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00731 35.10 0.00570 0.135 0.00
PERIMETER_BOT_ZN_2 14092.49 14092.49 69.77 1.248 1.248 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 24.00 24.00 0.00717 27.68 0.00569 0.087 0.00
PERIMETER_BOT_ZN_1 14809.74 14809.74 47.25 1.312 1.312 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 24.00 24.00 0.00725 34.65 0.00570 0.135 0.00
PERIMETER_BOT_ZN_4 18039.35 18039.35 89.31 1.598 1.598 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 24.00 24.00 0.00713 33.39 0.00570 0.087 0.00
PERIMETER_MID_ZN_3 111530.96 111530.96 355.86 9.879 9.879 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 24.00 0.00732 35.10 0.00570 1.353 0.00
PERIMETER_MID_ZN_2 148382.84 148382.84 734.66 13.143 13.143 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 24.00 24.00 0.00715 28.44 0.00569 0.872 0.00
PERIMETER_MID_ZN_1 139954.45 139954.45 446.54 12.397 12.397 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 24.00 24.00 0.00725 34.76 0.00570 1.353 0.00
PERIMETER_MID_ZN_4 158439.27 158439.27 784.45 14.034 14.034 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 24.00 24.00 0.00714 33.21 0.00570 0.872 0.00
PERIMETER_TOP_ZN_3 13001.80 13001.80 41.48 1.152 1.152 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 24.00 0.00727 35.10 0.00570 0.135 0.00
PERIMETER_TOP_ZN_2 15071.87 15071.87 74.62 1.335 1.335 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 24.00 24.00 0.00715 28.82 0.00569 0.087 0.00
PERIMETER_TOP_ZN_1 15694.35 15694.35 50.07 1.390 1.390 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 24.00 24.00 0.00722 34.99 0.00570 0.135 0.00
PERIMETER_TOP_ZN_4 17125.13 17125.13 84.79 1.517 1.517 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 24.00 24.00 0.00713 33.21 0.00570 0.087 0.00
DATACENTER_BOT_ZN_6 8187.79 8187.79 226.16 0.572 0.572 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 27.00 27.00 0.00709 30.51 0.00569 0.016 0.00
DATACENTER_MID_ZN_6 78194.15 78194.15 2159.90 5.463 5.463 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 27.00 27.00 0.00709 30.17 0.00569 0.156 0.00
DATACENTER_TOP_ZN_6 7993.99 7993.99 220.81 0.559 0.559 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 27.00 27.00 0.00709 30.51 0.00569 0.016 0.00
DATACENTER_BASEMENT_ZN_6 370482.92 370482.92 472.75 25.884 25.884 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.00 27.00 0.00704 22.82 0.00568 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 24.44 0.00234 -7.90 0.00234 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 06:30:00 19.60 21.89 0.00234 -7.90 0.00234 1.078 0.00
CORE_MID 231996.31 231996.31 92.94 11.894 11.894 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -7.90 0.00234 10.778 0.00
CORE_TOP 55833.44 55833.44 22.37 2.886 2.886 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -7.90 0.00234 1.078 0.00
PERIMETER_BOT_ZN_3 6348.19 6348.19 20.26 0.328 0.328 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00777 -7.90 0.00234 0.135 0.00
PERIMETER_BOT_ZN_2 4563.77 4563.77 22.60 0.236 0.236 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00781 -7.90 0.00234 0.087 0.00
PERIMETER_BOT_ZN_1 7960.05 7960.05 25.40 0.412 0.412 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00786 -7.90 0.00234 0.135 0.00
PERIMETER_BOT_ZN_4 2913.26 2913.26 14.42 0.150 0.150 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00756 -7.90 0.00234 0.087 0.00
PERIMETER_MID_ZN_3 127973.58 127973.58 408.32 6.631 6.631 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00789 -7.90 0.00234 1.353 0.00
PERIMETER_MID_ZN_2 84965.19 84965.19 420.67 4.403 4.403 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00789 -7.90 0.00234 0.872 0.00
PERIMETER_MID_ZN_1 126804.71 126804.71 404.58 6.570 6.570 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00789 -7.90 0.00234 1.353 0.00
PERIMETER_MID_ZN_4 79369.44 79369.44 392.97 4.112 4.112 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00788 -7.90 0.00234 0.872 0.00
PERIMETER_TOP_ZN_3 17051.10 17051.10 54.40 0.884 0.884 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00790 -7.90 0.00234 0.135 0.00
PERIMETER_TOP_ZN_2 11244.51 11244.51 55.67 0.583 0.583 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00790 -7.90 0.00234 0.087 0.00
PERIMETER_TOP_ZN_1 16905.14 16905.14 53.94 0.877 0.877 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00790 -7.90 0.00234 0.135 0.00
PERIMETER_TOP_ZN_4 10823.19 10823.19 53.59 0.561 0.561 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00790 -7.90 0.00234 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 06:30:00 18.00 26.38 0.00700 -7.90 0.00234 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 05:40:00 18.00 23.23 0.00495 -7.90 0.00234 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 05:40:00 18.00 21.35 0.00280 -7.90 0.00234 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 04:00:00 18.00 27.00 0.00700 -7.90 0.00234 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 10.49 10.49 2.20 2.20 10.4877 3.0589 10.4877 0.2917 0.3000
VAV_MID WITH REHEAT 97.16 97.16 33.61 33.61 97.1601 33.6095 97.1601 0.3459 0.3000
VAV_TOP WITH REHEAT 10.66 10.66 5.79 5.79 10.6575 5.7910 10.6575 0.5434 0.3000
CAV_BAS 5.92 5.92 1.20 1.20 5.9249 5.9249 5.9249 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.57 0.57 0.02 0.02 0.5720 0.5720 0.5720 1.0000 1.0000
AIRLOOP DATACENTER MID 5.46 5.46 0.16 0.16 5.4631 5.4631 5.4631 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.56 0.56 0.02 0.02 0.5585 0.5585 0.5585 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 16386.306 16386.306 1.978679 0.00014335 330.335 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 06:30:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 06:30:00 16386.31 16386.31 1.978679 12.80 9.86 0.00800000 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 0.0000 21.00 0.00800000 42.5367 0.00 0.00 16446.73 16446.73
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 392212.648 392212.648 19.346440 0.00343125 9242.711 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 392212.65 392212.65 19.346440 12.80 9.86 0.00800000 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 0.0000 21.00 0.00800000 42.5367 231996.31 0.00 393496.22 393496.22
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 79733.995 79733.995 2.886039 0.00069755 2104.639 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 79734.00 79734.00 2.886039 12.80 9.86 0.00800000 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 0.0000 21.00 0.00800000 42.5367 55833.44 0.00 80008.85 80008.85
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 9062.823 9062.823 0.327957 0.00007929 239.247 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 9062.82 9062.82 0.327957 12.80 9.86 0.00800000 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 0.0000 21.00 0.00777253 41.3436 6348.19 0.00 9094.26 9094.26
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 6630.452 6630.452 0.249657 0.00005801 171.987 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 6630.45 6630.45 0.249657 12.80 9.86 0.00800000 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 0.0000 21.00 0.00781279 41.5550 4563.77 0.00 6650.76 6650.76
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 11368.612 11368.612 0.411714 0.00009946 300.010 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 11368.61 11368.61 0.411714 12.80 9.86 0.00800000 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 0.0000 21.00 0.00786304 41.8187 7960.05 0.00 11407.28 11407.28
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 5557.471 5557.471 0.319577 0.00004862 125.785 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 5557.47 5557.47 0.319577 12.80 9.86 0.00800000 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 0.0000 21.00 0.00756483 40.2526 2913.26 0.00 5576.42 5576.42
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 182872.227 182872.227 6.630850 0.00159985 4823.169 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 182872.23 182872.23 6.630850 12.80 9.86 0.00800000 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 0.0000 21.00 0.00788729 41.9461 127973.58 0.00 183474.70 183474.70
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 121417.218 121417.218 4.402794 0.00106221 3202.233 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 121417.22 121417.22 4.402794 12.80 9.86 0.00800000 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 0.0000 21.00 0.00788851 41.9526 84965.19 0.00 121816.58 121816.58
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 181200.148 181200.148 6.570095 0.00158522 4779.111 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 181200.15 181200.15 6.570095 12.80 9.86 0.00800000 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 0.0000 21.00 0.00788564 41.9375 126804.71 0.00 181797.42 181797.42
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 113412.906 113412.906 4.112001 0.00099219 2991.309 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 113412.91 113412.91 4.112001 12.80 9.86 0.00800000 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 0.0000 21.00 0.00787502 41.8818 79369.44 0.00 113787.24 113787.24
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 24371.278 24371.278 0.884135 0.00021321 642.633 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 24371.28 24371.28 0.884135 12.80 9.86 0.00800000 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 0.0000 21.00 0.00790224 42.0247 17051.10 0.00 24450.50 24450.50
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 16072.104 16072.104 0.583081 0.00014061 423.789 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 16072.10 16072.10 0.583081 12.80 9.86 0.00800000 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 0.0000 21.00 0.00790129 42.0197 11244.51 0.00 16124.30 16124.30
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 24162.503 24162.503 0.876549 0.00021138 637.132 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 24162.50 24162.50 0.876549 12.80 9.86 0.00800000 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 0.0000 21.00 0.00790136 42.0201 16905.14 0.00 24241.08 24241.08
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 15469.515 15469.515 0.561191 0.00013533 407.910 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 15469.52 15469.52 0.561191 12.80 9.86 0.00800000 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 0.0000 21.00 0.00789723 41.9985 10823.19 0.00 15519.82 15519.82
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 170803.668 -999.000 10.487743 0.00726638 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 170803.67 170803.67 10.487743 26.82 14.06 0.00695019 10.67 7.93 0.00695019 35.10 0.00569938 15.77 24.2015 24.00 0.00737728 32.7238 112573.93 0.00 153532.89 153532.89
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 53572.940 53572.940 3.146323 0.00046868 876.662 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 53572.94 53572.94 3.146323 -4.31 -4.82 0.00288065 12.80 9.86 0.00800000 -7.90 0.00234317 -7.90 80.6716 21.33 0.00586981 30.6888 21785.27 0.00 49301.00 49301.00
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 1628129.918 -999.000 97.160113 0.06926441 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 1628129.92 1628129.91 97.160113 27.17 14.16 0.00692715 10.55 7.86 0.00692715 35.10 0.00569938 15.77 26.1238 24.00 0.00741843 32.9042 1002661.70 0.00 1466423.32 1466423.32
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 492162.037 492162.037 29.148034 0.00430565 8059.701 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 20:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 492162.04 492162.04 29.148034 -4.17 -4.44 0.00306260 12.80 9.86 0.00800000 -7.90 0.00234317 -7.90 87.0795 21.00 0.00789419 41.9820 408394.87 0.00 453669.95 453669.95
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 171726.024 -999.000 10.657508 0.00730562 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 171726.02 171726.02 10.657508 26.65 14.01 0.00695454 10.67 7.94 0.00695454 35.10 0.00569938 15.77 23.8160 24.00 0.00734891 32.5994 119854.46 0.00 154285.92 154285.92
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 49205.192 49205.192 3.197252 0.00043047 812.658 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 06:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 49205.19 49205.19 3.197252 -2.66 -2.96 0.00347950 12.80 9.86 0.00800000 -7.90 0.00234317 -7.90 79.3866 17.60 0.00781322 51.3592 44233.07 0.00 46163.78 46163.78
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 91227.727 -999.000 5.924872 0.00388104 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 91227.73 91227.73 5.924872 26.39 14.07 0.00714156 11.12 8.32 0.00714156 34.43 0.00569833 15.56 20.2568 24.00 0.00757071 33.5718 59114.17 0.00 82706.60 82706.60
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 245298.436 245298.436 5.924872 0.00214598 5426.055 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 245298.44 245298.44 5.924872 -1.60 -4.13 0.00234317 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 20.2568 24.49 0.00234317 10.1704 0.00 0.00 203831.60 203831.60
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 10205.485 5462.034 0.572047 0.00024993 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 8668.69 8620.44 -999.0 28.25 14.62 0.00704991 12.80 8.87 0.00700000 30.51 0.00569229 14.27 -999.0000 27.00 0.00708805 26.3224 8187.79 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 97515.333 52176.071 5.463149 0.00238814 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 82839.08 82357.64 -999.0 28.25 14.63 0.00705213 12.80 8.87 0.00700000 30.51 0.00569229 14.27 -999.0000 27.00 0.00709219 26.3377 78188.38 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9966.774 5333.462 0.558509 0.00024409 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 8466.37 8418.10 -999.0 28.25 14.62 0.00705114 12.80 8.87 0.00700000 30.51 0.00569229 14.27 -999.0000 27.00 0.00709027 26.3306 7993.99 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 10205.485 10205.485 0.572047 0.00024993 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 10205.49 10205.49 0.572047 -7.90 -7.90 0.00234317 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 2.7328 26.72 0.00699997 26.4287 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 97515.333 97515.333 5.463149 0.00238814 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 97515.33 97515.33 5.463149 -7.90 -7.90 0.00234317 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 2.8615 24.44 0.00494585 21.4490 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9966.774 9966.774 0.558509 0.00024409 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 9966.77 9966.77 0.558509 -7.90 -7.90 0.00234317 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 2.7990 23.21 0.00280089 13.1215 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 745.232 745.232 -999.0 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 745.23 745.23 0.572047 -0.22 -0.22 0.00687271 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 2.7328 26.72 0.00699997 26.4287 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 7452.321 7452.321 -999.0 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 7452.32 7452.32 5.463149 -0.23 -0.23 0.00487137 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 2.8615 24.44 0.00494585 21.4490 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 745.232 745.232 -999.0 -999.0 -999.000 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 745.23 745.23 0.558509 -0.22 -2.69 0.00278808 40.00 18.92 0.00800000 -7.90 0.00234317 -7.90 2.7990 23.21 0.00280089 13.1215 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 16386.306 16386.306 1.978679 0.00014335 330.335 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 0.7873 0.803184 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 06:30:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 06:30:00 Sensible 16386.31 16386.31 1.0000 1.95970120 1.978679 12.80 9.86 0.00800000 33059.8 40.00 18.92 0.00800000 60796.0 0.14333993 60.00 32.22 27.78 0.000 16386.31 -7.90 0.00234317 -7.90 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 42.5367 0.00 0.00 16446.73 16446.73 1.95970120 12.80 11.60 0.00800000 33059.8 21.03 14.86 0.00800000 41452.3
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 392212.648 392212.648 19.346440 0.00343125 9242.711 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 18.8453 19.224519 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 392212.65 392212.65 1.0000 19.16088671 19.346440 12.80 9.86 0.00800000 33059.8 40.00 18.92 0.00800000 60796.0 3.43089732 60.00 32.22 27.78 0.000 392212.65 -7.90 0.00234317 -7.90 0.00000000 0.0000 20.81 0.00800000 21.00 0.00800000 42.5367 231996.31 0.00 393496.22 393496.22 19.16088671 12.80 11.60 0.00800000 33059.8 32.94 19.00 0.00800000 53596.3
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 79733.995 79733.995 2.886039 0.00069755 2104.639 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 3.8311 3.908206 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 79734.00 79734.00 1.0000 2.85835914 2.886039 12.80 9.86 0.00800000 33059.8 40.00 18.92 0.00800000 60796.0 0.69747662 60.00 32.22 27.78 0.000 79734.00 -7.90 0.00234317 -7.90 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 42.5367 55833.44 0.00 80008.85 80008.85 2.85835914 12.80 11.60 0.00800000 33059.8 40.25 21.26 0.00800000 61051.0
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 9062.823 9062.823 0.327957 0.00007929 239.247 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 0.4355 0.444219 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 9062.82 9062.82 1.0000 0.32481106 0.327957 12.80 9.86 0.00800000 33059.8 40.00 18.92 0.00800000 60796.0 0.07927744 60.00 32.22 27.78 0.000 9062.82 -7.90 0.00234317 -7.90 0.00000000 0.0000 20.91 0.00777253 21.00 0.00777253 41.3436 6348.19 0.00 9094.26 9094.26 0.32481106 12.80 11.60 0.00800000 33059.8 40.26 21.26 0.00800000 61058.4
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 6630.452 6630.452 0.249657 0.00005801 171.987 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 0.3186 0.324995 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 6630.45 6630.45 1.0000 0.24726209 0.249657 12.80 9.86 0.00800000 33059.8 40.00 18.92 0.00800000 60796.0 0.05800017 60.00 32.22 27.78 0.000 6630.45 -7.90 0.00234317 -7.90 0.00000000 0.0000 20.91 0.00781279 21.00 0.00781279 41.5550 4563.77 0.00 6650.76 6650.76 0.24726209 12.80 11.60 0.00800000 33059.8 39.18 20.94 0.00800000 59957.5
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 11368.612 11368.612 0.411714 0.00009946 300.010 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 0.5462 0.557239 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 11368.61 11368.61 1.0000 0.40776551 0.411714 12.80 9.86 0.00800000 33059.8 40.00 18.92 0.00800000 60796.0 0.09944744 60.00 32.22 27.78 0.000 11368.61 -7.90 0.00234317 -7.90 0.00000000 0.0000 20.91 0.00786304 21.00 0.00786304 41.8187 7960.05 0.00 11407.28 11407.28 0.40776551 12.80 11.60 0.00800000 33059.8 40.23 21.25 0.00800000 61034.9
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 5557.471 5557.471 0.319577 0.00004862 125.785 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 0.2670 0.272403 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 5557.47 5557.47 1.0000 0.31651147 0.319577 12.80 9.86 0.00800000 33059.8 40.00 18.92 0.00800000 60796.0 0.04861423 60.00 32.22 27.78 0.000 5557.47 -7.90 0.00234317 -7.90 0.00000000 0.0000 20.86 0.00756483 21.00 0.00756483 40.2526 2913.26 0.00 5576.42 5576.42 0.31651147 12.80 11.60 0.00800000 33059.8 30.08 18.06 0.00800000 50678.2
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 182872.227 182872.227 6.630850 0.00159985 4823.169 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 8.7867 8.963583 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 182872.23 182872.23 1.0000 6.56725301 6.630850 12.80 9.86 0.00800000 33059.8 40.00 18.92 0.00800000 60796.0 1.59968282 60.00 32.22 27.78 0.000 182872.23 -7.90 0.00234317 -7.90 0.00000000 0.0000 20.95 0.00788729 21.00 0.00788729 41.9461 127973.58 0.00 183474.70 183474.70 6.56725301 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60997.6
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 121417.218 121417.218 4.402794 0.00106221 3202.233 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 5.8339 5.951332 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 121417.22 121417.22 1.0000 4.36056604 4.402794 12.80 9.86 0.00800000 33059.8 40.00 18.92 0.00800000 60796.0 1.06210244 60.00 32.22 27.78 0.000 121417.22 -7.90 0.00234317 -7.90 0.00000000 0.0000 20.95 0.00788851 21.00 0.00788851 41.9526 84965.19 0.00 121816.58 121816.58 4.36056604 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60995.8
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 181200.148 181200.148 6.570095 0.00158522 4779.111 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 8.7064 8.881625 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 181200.15 181200.15 1.0000 6.50708018 6.570095 12.80 9.86 0.00800000 33059.8 40.00 18.92 0.00800000 60796.0 1.58505623 60.00 32.22 27.78 0.000 181200.15 -7.90 0.00234317 -7.90 0.00000000 0.0000 20.95 0.00788564 21.00 0.00788564 41.9375 126804.71 0.00 181797.42 181797.42 6.50708018 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60998.2
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 113412.906 113412.906 4.112001 0.00099219 2991.309 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 5.4493 5.558996 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 113412.91 113412.91 1.0000 4.07256236 4.112001 12.80 9.86 0.00800000 33059.8 40.00 18.92 0.00800000 60796.0 0.99208436 60.00 32.22 27.78 0.000 113412.91 -7.90 0.00234317 -7.90 0.00000000 0.0000 20.95 0.00787502 21.00 0.00787502 41.8818 79369.44 0.00 113787.24 113787.24 4.07256236 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60999.8
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 24371.278 24371.278 0.884135 0.00021321 642.633 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 1.1710 1.194572 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 24371.28 24371.28 1.0000 0.87565536 0.884135 12.80 9.86 0.00800000 33059.8 40.00 18.92 0.00800000 60796.0 0.21318882 60.00 32.22 27.78 0.000 24371.28 -7.90 0.00234317 -7.90 0.00000000 0.0000 20.95 0.00790224 21.00 0.00790224 42.0247 17051.10 0.00 24450.50 24450.50 0.87565536 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60982.3
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 16072.104 16072.104 0.583081 0.00014061 423.789 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 0.7722 0.787783 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 16072.10 16072.10 1.0000 0.57748860 0.583081 12.80 9.86 0.00800000 33059.8 40.00 18.92 0.00800000 60796.0 0.14059143 60.00 32.22 27.78 0.000 16072.10 -7.90 0.00234317 -7.90 0.00000000 0.0000 20.95 0.00790129 21.00 0.00790129 42.0197 11244.51 0.00 16124.30 16124.30 0.57748860 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60981.2
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 24162.503 24162.503 0.876549 0.00021138 637.132 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 1.1610 1.184338 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 24162.50 24162.50 1.0000 0.86814238 0.876549 12.80 9.86 0.00800000 33059.8 40.00 18.92 0.00800000 60796.0 0.21136255 60.00 32.22 27.78 0.000 24162.50 -7.90 0.00234317 -7.90 0.00000000 0.0000 20.95 0.00790136 21.00 0.00790136 42.0201 16905.14 0.00 24241.08 24241.08 0.86814238 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60982.8
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 15469.515 15469.515 0.561191 0.00013533 407.910 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 0.7433 0.758247 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 15469.52 15469.52 1.0000 0.55580881 0.561191 12.80 9.86 0.00800000 33059.8 40.00 18.92 0.00800000 60796.0 0.13532026 60.00 32.22 27.78 0.000 15469.52 -7.90 0.00234317 -7.90 0.00000000 0.0000 20.95 0.00789723 21.00 0.00789723 41.9985 10823.19 0.00 15519.82 15519.82 0.55580881 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60982.8
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 170803.668 -999.000 10.487743 0.00726638 -999.000 -999.0000 1.00000 1.00000 1017.7601 1004.8586 0.9904 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 10.487743 10.38715347   4197.9300 999.8980 87.70850572 12.27 6.67 5.60 2061887.34 8.2839 8.283851 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 170803.67 170803.67 1.0000 10.38715347 10.487743 26.82 14.06 0.00695019 44682.8 10.67 7.93 0.00695019 28239.1 7.26564164 6.67 12.27 5.60 22543.031 148260.64 35.10 0.00569938 15.77 2.53819000 24.2015 24.00 0.00737728 24.00 0.00737728 32.7238 112573.93 0.00 153532.89 153532.89 10.38715347 26.82 16.05 0.00695019 44682.8 12.30 10.29 0.00695019 29901.8
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 53572.940 53572.940 3.146323 0.00046868 876.662 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 10.487743 10.38715347   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 2.5741 2.625907 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 53572.94 53572.94 1.0000 3.11614604 3.146323 -4.31 -4.82 0.00288065 2851.5 12.80 9.86 0.00800000 33059.8 0.46863164 60.00 32.22 27.78 0.000 53572.94 -7.90 0.00234317 -7.90 2.53819000 80.6716 10.68 0.00512393 21.33 0.00586981 30.6888 21785.27 0.00 49301.00 49301.00 3.11614604 2.80 0.35 0.00288065 10032.9 18.46 8.56 0.00288065 25854.0
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 1628129.918 -999.000 97.160113 0.06926441 -999.000 -999.0000 1.00000 1.00000 1017.7172 1004.8586 0.9904 VAV_MID WITH REHEAT FAN Fan:VariableVolume 97.160113 96.22824045   4197.9300 999.8980 87.70850572 12.27 6.67 5.60 2061887.34 78.9631 78.963088 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 1628129.92 1628129.91 1.0000 96.22824045 97.160113 27.17 14.16 0.00692715 44977.0 10.55 7.86 0.00692715 28057.6 69.25734477 6.67 12.27 5.60 220708.256 1407421.66 35.10 0.00569938 15.77 25.38195000 26.1238 24.00 0.00741843 24.00 0.00741843 32.9042 1002661.70 0.00 1466423.32 1466423.32 96.22824045 27.17 16.16 0.00692715 44977.0 12.20 10.22 0.00692715 29738.0
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 492162.037 492162.037 29.148034 0.00430565 8059.701 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 VAV_MID WITH REHEAT FAN Fan:VariableVolume 97.160113 96.22824045   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 23.6477 24.123594 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 20:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 492162.04 492162.04 1.0000 28.86847214 29.148034 -4.17 -4.44 0.00306260 3449.5 12.80 9.86 0.00800000 33059.8 4.30520898 60.00 32.22 27.78 0.000 492162.04 -7.90 0.00234317 -7.90 25.38195000 87.0795 21.00 0.00791127 21.00 0.00789419 41.9820 408394.87 0.00 453669.95 453669.95 28.86847214 2.80 0.61 0.00306260 10488.9 18.35 8.72 0.00306260 26203.9
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 171726.024 -999.000 10.657508 0.00730562 -999.000 -999.0000 1.00000 1.00000 1017.7681 1004.8586 0.9904 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 10.657508 10.55529089   4197.9300 999.8980 87.70850572 12.27 6.67 5.60 2061887.34 8.3286 8.328584 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 Sensible 171726.02 171726.02 1.0000 10.55529089 10.657508 26.65 14.01 0.00695454 44519.2 10.67 7.94 0.00695454 28250.0 7.30487680 6.67 12.27 5.60 22907.936 148818.09 35.10 0.00569938 15.77 2.53819000 23.8160 24.00 0.00734891 24.00 0.00734891 32.5994 119854.46 0.00 154285.92 154285.92 10.55529089 26.65 15.99 0.00695454 44519.2 12.29 10.29 0.00695454 29902.3
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 49205.192 49205.192 3.197252 0.00043047 812.658 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 10.657508 10.55529089   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 2.3642 2.411820 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 06:00:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 49205.19 49205.19 1.0000 3.16658727 3.197252 -2.66 -2.96 0.00347950 6008.2 12.80 9.86 0.00800000 33059.8 0.43042457 60.00 32.22 27.78 0.000 49205.19 -7.90 0.00234317 -7.90 2.53819000 79.3866 17.50 0.00785577 17.60 0.00781322 51.3592 44233.07 0.00 46163.78 46163.78 3.16658727 2.80 1.21 0.00347950 11533.7 17.22 8.67 0.00347950 26112.1
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 91227.727 -999.000 5.924872 0.00388104 -999.000 -999.0000 1.00000 1.00000 1018.1158 1004.8586 0.9904 CAV_BAS FAN Fan:ConstantVolume 5.924872 5.86804562   4197.9300 999.8980 87.70850572 12.27 6.67 5.60 2061887.34 4.4245 4.424477 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 91227.73 91227.73 1.0000 5.86804562 5.924872 26.39 14.07 0.00714156 44726.9 11.12 8.32 0.00714156 29180.4 3.88064250 6.67 12.27 5.60 10046.534 81181.19 34.43 0.00569833 15.56 1.20019084 20.2568 24.00 0.00757071 24.00 0.00757071 33.5718 59114.17 0.00 82706.60 82706.60 5.86804562 26.39 16.06 0.00714156 44726.9 12.54 10.60 0.00714156 30632.5
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 245298.436 245298.436 5.924872 0.00214598 5426.055 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 CAV_BAS FAN Fan:ConstantVolume 5.924872 5.86804562   4197.9300 999.8980 17.84646606 54.44 82.22 27.78 2081228.02 11.7862 12.023438 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 245298.44 245298.44 1.0000 5.86804562 5.924872 -1.60 -4.13 0.00234317 4245.1 40.00 18.92 0.00800000 60796.0 2.14575882 60.00 32.22 27.78 0.000 245298.44 -7.90 0.00234317 -7.90 1.20019084 20.2568 0.00 0.00234317 24.49 0.00234317 10.1704 0.00 0.00 203831.60 203831.60 5.86804562 12.80 5.14 0.00234317 18777.8 47.22 19.12 0.00234317 53513.7
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 10205.485 5462.034 0.572047 0.00024993 -999.000 -999.0000 -999.00000 -999.00000 1017.9454 1004.8586 0.9904 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 Sensible 8668.69 8620.44 0.8494 -999.0 -999.0 28.25 14.62 0.00704991 46383.3 12.80 8.87 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 8668.69 30.51 0.00569229 14.27 0.01563279 -999.0000 27.00 0.00708805 27.00 0.00708805 26.3224 8187.79 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 97515.333 52176.071 5.463149 0.00238814 -999.000 -999.0000 -999.00000 -999.00000 1017.9496 1004.8586 0.9904 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 Sensible 82839.08 82357.64 0.8495 -999.0 -999.0 28.25 14.63 0.00705213 46393.5 12.80 8.87 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 82839.08 30.51 0.00569229 14.27 0.15632792 -999.0000 27.00 0.00709219 27.00 0.00709219 26.3377 78188.38 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9966.774 5333.462 0.558509 0.00024409 -999.000 -999.0000 -999.00000 -999.00000 1017.9477 1004.8586 0.9904 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 Sensible 8466.37 8418.10 0.8495 -999.0 -999.0 28.25 14.62 0.00705114 46388.8 12.80 8.87 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 8466.37 30.51 0.00569229 14.27 0.01563279 -999.0000 27.00 0.00709027 27.00 0.00709027 26.3306 7993.99 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 10205.485 10205.485 0.572047 0.00024993 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 0.9904 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 10205.49 10205.49 1.0000 0.56656088 0.572047 -7.90 -7.90 0.00234317 -2112.5 40.00 18.92 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 10205.49 -7.90 0.00234317 -7.90 0.01563279 2.7328 0.00 0.00699997 26.72 0.00699997 26.4287 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 97515.333 97515.333 5.463149 0.00238814 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 0.9904 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 97515.33 97515.33 1.0000 5.41075114 5.463149 -7.90 -7.90 0.00234317 -2112.5 40.00 18.92 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 97515.33 -7.90 0.00234317 -7.90 0.15632792 2.8615 0.00 0.00494585 24.44 0.00494585 21.4490 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9966.774 9966.774 0.558509 0.00024409 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 0.9904 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 9966.77 9966.77 1.0000 0.55315231 0.558509 -7.90 -7.90 0.00234317 -2112.5 40.00 18.92 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9966.77 -7.90 0.00234317 -7.90 0.01563279 2.7990 0.00 0.00280089 23.21 0.00280089 13.1215 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 745.232 745.232 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.572047 0.56656088   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 745.23 745.23 1.0000 0.56656088 0.572047 -0.22 -0.22 0.00687271 16968.6 40.00 18.92 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 745.23 -7.90 0.00234317 -7.90 0.01563279 2.7328 0.00 0.00699997 26.72 0.00699997 26.4287 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 7452.321 7452.321 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 5.463149 5.41075114   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 7452.32 7452.32 1.0000 5.41075114 5.463149 -0.23 -0.23 0.00487137 11953.8 40.00 18.92 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 7452.32 -7.90 0.00234317 -7.90 0.15632792 2.8615 0.00 0.00494585 24.44 0.00494585 21.4490 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 745.232 745.232 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9904 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.558509 0.55315231   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 745.23 745.23 1.0000 0.55315231 0.558509 -0.22 -2.69 0.00278808 6749.5 40.00 18.92 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 745.23 -7.90 0.00234317 -7.90 0.01563279 2.7990 0.00 0.00280089 23.21 0.00280089 13.1215 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 10.49 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 97.16 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 10.66 -      
CAV_BAS_OA_CONTROLLER DifferentialDryBulb 0.00 5.92 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT BASEMENT_DCV 0.002360 0.000305 0.000000 0.000000 Sum   1.00 1.00  
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 2438.17 1601.33 212.67
CORE_BOTTOM 2077.50 1735.33 259.00
CORE_MID 1606.83 3455.00 288.17
CORE_TOP 2139.83 3716.83 789.83
PERIMETER_BOT_ZN_3 1912.50 3385.00 207.67
PERIMETER_BOT_ZN_2 2346.17 2880.17 326.50
PERIMETER_BOT_ZN_1 2584.17 2139.83 323.50
PERIMETER_BOT_ZN_4 2943.67 1706.83 339.50
PERIMETER_MID_ZN_3 2771.17 3824.17 1347.00
PERIMETER_MID_ZN_2 2374.67 2863.33 854.50
PERIMETER_MID_ZN_1 2624.00 2461.67 507.33
PERIMETER_MID_ZN_4 2639.17 3248.50 772.33
PERIMETER_TOP_ZN_3 3517.33 3949.00 2110.50
PERIMETER_TOP_ZN_2 3368.67 3429.00 1553.83
PERIMETER_TOP_ZN_1 2836.50 2818.00 919.50
PERIMETER_TOP_ZN_4 3218.50 3483.67 1433.00
DATACENTER_BOT_ZN_6 5943.00 327.50 327.50
DATACENTER_MID_ZN_6 5830.17 38.17 38.17
DATACENTER_TOP_ZN_6 5198.00 208.67 100.17
DATACENTER_BASEMENT_ZN_6 5943.00 5943.00 5943.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5943.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 81.67 0.00 4.17
CORE_BOTTOM 0.00 3.17 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 2.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 4.00 0.00 1.67
PERIMETER_BOT_ZN_2 0.00 47.17 0.00 47.00
PERIMETER_BOT_ZN_1 0.00 94.50 0.00 90.17
PERIMETER_BOT_ZN_4 0.00 135.33 0.00 52.67
PERIMETER_MID_ZN_3 3.17 1.17 0.00 0.67
PERIMETER_MID_ZN_2 2.00 52.83 0.00 52.00
PERIMETER_MID_ZN_1 0.50 177.83 0.00 175.67
PERIMETER_MID_ZN_4 0.33 43.00 0.00 24.50
PERIMETER_TOP_ZN_3 44.17 10.67 8.50 7.17
PERIMETER_TOP_ZN_2 27.50 58.67 0.00 53.00
PERIMETER_TOP_ZN_1 18.17 82.67 0.17 76.67
PERIMETER_TOP_ZN_4 18.83 48.50 0.00 26.83
DATACENTER_BOT_ZN_6 0.00 10.17 0.00 4.17
DATACENTER_MID_ZN_6 0.00 7.17 0.00 3.00
DATACENTER_TOP_ZN_6 0.00 8.83 0.00 3.33
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 47.00 538.00 8.50 358.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.11 149.60 6779.02 1.346 0.000 0.000 0.000
CORE_BOTTOM 55.78 134.35 6849.35 1.018 0.000 0.000 0.000
CORE_MID 55.78 134.35 6849.35 0.769 0.000 0.000 0.000
CORE_TOP 55.78 134.35 6849.35 0.740 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.00 16.87 860.00 0.951 0.011 0.000 0.000
PERIMETER_BOT_ZN_2 4.51 10.87 554.22 1.638 0.011 0.000 0.000
PERIMETER_BOT_ZN_1 7.00 16.87 860.02 1.606 0.011 0.000 0.000
PERIMETER_BOT_ZN_4 4.51 10.87 554.22 2.171 0.011 0.000 0.000
PERIMETER_MID_ZN_3 7.00 16.87 860.00 0.787 0.025 0.000 0.000
PERIMETER_MID_ZN_2 3.94 10.87 554.22 1.498 0.028 0.000 0.000
PERIMETER_MID_ZN_1 7.00 16.87 860.02 1.469 0.025 0.000 0.000
PERIMETER_MID_ZN_4 4.51 10.87 554.22 1.486 0.026 0.000 0.000
PERIMETER_TOP_ZN_3 7.00 16.87 860.00 0.792 0.031 0.000 0.000
PERIMETER_TOP_ZN_2 4.51 10.87 554.22 1.606 0.032 0.000 0.000
PERIMETER_TOP_ZN_1 7.00 16.87 860.02 1.426 0.031 0.000 0.000
PERIMETER_TOP_ZN_4 4.51 10.87 554.22 1.521 0.032 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.424 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.424 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.424 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.51 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.11 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 55.78 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 55.78 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 55.78 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.00 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 7.00 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 7.00 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.94 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 7.00 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 7.00 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 7.00 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.51 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.11 149.60 6779.02 2779.43 1.2002 0.847
CORE_BOTTOM VAV_BOT WITH REHEAT 55.78 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 55.78 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 55.78 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 7.00 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 7.00 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 7.00 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.94 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 7.00 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 7.00 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 7.00 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.81 1.95 99.34 36.20 0.0156 0.011
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.81 1.95 99.34 36.20 0.1563 0.110
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.81 1.95 99.34 36.20 0.0156 0.011
DATACENTER_BASEMENT_ZN_6   17.51 42.18 1911.37 783.68   0.239
Total Facility   1029.47 2493.19 126016.35 46320.38 1.3878 157.549


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 57805685.30 0.00 57805685.30 0.00 57805685.30 29876159.83 3690.50 1215.07 3854.43 491.85
CORE_BOTTOM 45255870.18 0.00 45255870.18 0.00 45255870.18 33990283.35 4465.23 36.31 4258.46 675.23
CORE_MID 0.32E+09 0.00 0.32E+09 0.00 0.32E+09 0.34E+09 5702.80 35.98 3021.22 228.18
CORE_TOP 31125640.87 0.00 31125640.87 0.00 31125640.87 33990283.35 5967.71 29.51 2762.77 327.43
PERIMETER_BOT_ZN_3 5328826.88 0.00 5328826.88 108997.33 5437824.21 4267819.30 4301.80 68.54 4389.66 675.23
PERIMETER_BOT_ZN_2 5857027.31 0.00 5857027.31 72664.84 5929692.15 2750345.05 3119.79 7.92 5632.29 675.23
PERIMETER_BOT_ZN_1 8666878.82 0.00 8666878.82 108997.33 8775876.15 4267912.63 3612.74 69.66 5077.59 675.23
PERIMETER_BOT_ZN_4 7793602.38 0.00 7793602.38 72664.84 7866267.22 2750345.05 3062.71 1.19 5696.10 675.23
PERIMETER_MID_ZN_3 41349951.17 0.00 41349951.17 255627.27 41605578.44 42678193.03 5027.25 53.85 3678.90 228.18
PERIMETER_MID_ZN_2 53992437.08 0.00 53992437.08 170418.06 54162855.14 27503450.52 3735.56 5.05 5019.39 1137.18
PERIMETER_MID_ZN_1 75751805.84 0.00 75751805.84 255627.27 76007433.11 42679126.28 4125.73 495.94 4138.33 228.18
PERIMETER_MID_ZN_4 50351386.37 0.00 50351386.37 170418.06 50521804.43 27503450.52 3720.80 6.24 5032.97 228.18
PERIMETER_TOP_ZN_3 4176497.86 0.00 4176497.86 317386.02 4493883.87 4267819.30 5085.43 38.68 3635.89 327.43
PERIMETER_TOP_ZN_2 5406774.47 0.00 5406774.47 211590.53 5618365.00 2750345.05 3825.43 1.05 4933.52 327.43
PERIMETER_TOP_ZN_1 7387451.09 0.00 7387451.09 317386.02 7704837.10 4267912.63 3871.31 9.82 4878.87 327.43
PERIMETER_TOP_ZN_4 5175859.49 0.00 5175859.49 211590.53 5387450.02 2750345.05 3808.64 5.52 4945.84 327.43
DATACENTER_BOT_ZN_6 244303.03 0.00 244303.03 0.00 244303.03 389144.62 4419.00 504.00 3837.00 0.00
DATACENTER_MID_ZN_6 2443030.26 0.00 2443030.26 0.00 2443030.26 3891446.16 4419.00 504.00 3837.00 0.00
DATACENTER_TOP_ZN_6 244303.03 0.00 244303.03 0.00 244303.03 389144.62 4419.00 504.00 3837.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00 0.00 8423799.00 8760.00 0.00 0.00 0.00
Total Facility 0.56E+10 0.00 0.56E+10 9942184.14 0.57E+10 0.50E+10 8760.00 2160.15 5995.38 1906.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.4946 0.0000 2.4946 0.0000 2.4946 0.9949 1274.15 1211.79 3457.06
CORE_BOTTOM 1.9060 0.0000 1.9060 0.0000 1.9060 1.0778 2257.77 33.45 3651.78
CORE_MID 14.4078 0.0000 14.4078 0.0000 14.4078 10.7782 3069.41 35.69 2837.90
CORE_TOP 1.3875 0.0000 1.3875 0.0000 1.3875 1.0778 3325.81 29.51 2587.67
PERIMETER_BOT_ZN_3 0.2236 0.0000 0.2236 0.0025 0.2261 0.1353 2088.35 65.36 3789.29
PERIMETER_BOT_ZN_2 0.2483 0.0000 0.2483 0.0017 0.2500 0.0872 968.79 6.77 4967.44
PERIMETER_BOT_ZN_1 0.3781 0.0000 0.3781 0.0025 0.3806 0.1353 1406.82 65.25 4470.93
PERIMETER_BOT_ZN_4 0.3291 0.0000 0.3291 0.0017 0.3308 0.0872 920.94 0.74 5021.32
PERIMETER_MID_ZN_3 1.8534 0.0000 1.8534 0.0059 1.8593 1.3533 2394.95 53.40 3494.66
PERIMETER_MID_ZN_2 2.2739 0.0000 2.2739 0.0043 2.2781 0.8721 1107.56 3.12 3923.32
PERIMETER_MID_ZN_1 3.4577 0.0000 3.4577 0.0059 3.4637 1.3533 1492.63 495.88 3954.50
PERIMETER_MID_ZN_4 2.2556 0.0000 2.2556 0.0040 2.2595 0.8721 1095.63 4.04 4843.32
PERIMETER_TOP_ZN_3 0.1867 0.0000 0.1867 0.0074 0.1941 0.1353 2444.44 38.52 3460.04
PERIMETER_TOP_ZN_2 0.2437 0.0000 0.2437 0.0049 0.2487 0.0872 1187.89 0.75 4754.36
PERIMETER_TOP_ZN_1 0.3358 0.0000 0.3358 0.0074 0.3431 0.1353 1229.66 9.82 4703.52
PERIMETER_TOP_ZN_4 0.2311 0.0000 0.2311 0.0049 0.2360 0.0872 1175.51 3.86 4763.63
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0130 1602.00 504.00 3837.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1296 1602.00 504.00 3837.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0130 1602.00 504.00 3837.00
DATACENTER_BASEMENT_ZN_6 0.0000 0.0000 0.0000 0.0000 0.0000 0.2805 5943.00 0.00 0.00
Total Facility 251.6127 0.0000 251.6127 0.2339 251.8465 157.9346 5943.00 2141.21 5127.78


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 71510493.20 0.00 71510493.20 48026705.38 3216.34 14.29 5529.36 675.23
VAV_MID WITH REHEAT 0.53E+09 0.00 0.53E+09 0.48E+09 3820.58 9.32 4930.09 228.18
VAV_TOP WITH REHEAT 52255246.61 0.00 52255246.61 48026705.38 3872.80 6.19 4881.01 327.43
CAV_BAS 56702161.89 0.00 56702161.89 29876159.83 4905.51 5.55 3848.95 491.75
AIRLOOP DATACENTER BOT 239639.23 0.00 239639.23 389144.62 4923.00 1512.00 2325.00 0.00
AIRLOOP DATACENTER MID 2396392.27 0.00 2396392.27 3891446.16 4923.00 1512.00 2325.00 0.00
AIRLOOP DATACENTER TOP 239639.23 0.00 239639.23 389144.62 4923.00 1512.00 2325.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 3.0263 0.0000 3.0263 1.5229 1017.65 11.30 4914.05
VAV_MID WITH REHEAT 23.9466 0.0000 23.9466 15.2292 1188.03 9.16 4745.81
VAV_TOP WITH REHEAT 2.3392 0.0000 2.3392 1.5229 1231.06 6.19 4705.75
CAV_BAS 2.4470 0.0000 2.4470 0.9949 2485.94 1.81 3455.26
AIRLOOP DATACENTER BOT 0.0112 0.0000 0.0112 0.0130 2106.00 1512.00 2325.00
AIRLOOP DATACENTER MID 0.1120 0.0000 0.1120 0.1296 2106.00 1512.00 2325.00
AIRLOOP DATACENTER TOP 0.0112 0.0000 0.0112 0.0130 2106.00 1512.00 2325.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 0.17 4268.53 0.00 0.00 0.00 1429.43 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 0.17 3577.67 0.00 0.00 0.00 1546.78 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 0.03 3236.96 0.00 0.00 0.00 1971.25 0.00 0.00 0.00
CAV_BAS 0.00 0.00 3961.66 0.00 0.00 0.00 1209.89 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 0.0000 4.3540 0.0000 0.0000 0.0000 1.6375 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 0.0000 34.8856 0.0000 0.0000 0.0000 16.4725 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 0.0000 3.6840 0.0000 0.0000 0.0000 1.6160 0.0000 0.0000 0.0000
CAV_BAS 0.0000 0.0000 3.8378 0.0000 0.0000 0.0000 1.0169 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0153 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.1534 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0153 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 7
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1352
Defaulted Fields 1168
Fields with Defaults 3820
Autosized Fields 313
Autosizable Fields 391
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 23665.43 287617.65 22-JAN-05:00 1632266.59 02-AUG-15:30
Electricity:Building 16697.36 216770.18 04-SEP-17:10 977223.71 01-DEC-17:00
Electricity:Zone:BASEMENT 559.97 14115.26 01-JAN-00:10 25295.37 02-JAN-08:10
Electricity:SpaceType:GENERAL 16697.36 216770.18 04-SEP-17:10 977223.71 01-DEC-17:00
InteriorLights:Electricity 2020.96 9514.02 01-JAN-10:20 198852.03 13-NOV-17:00
InteriorLights:Electricity:Zone:BASEMENT 135.58 657.72 01-JAN-00:10 11837.83 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 2020.96 9514.02 01-JAN-10:20 198852.03 13-NOV-17:00
LightsWired:InteriorLights:Electricity 2020.96 9514.02 01-JAN-10:20 198852.03 13-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 135.58 657.72 01-JAN-00:10 11837.83 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 2020.96 9514.02 01-JAN-10:20 198852.03 13-NOV-17:00
Electricity:Zone:CORE_BOTTOM 411.37 5043.91 01-JAN-00:10 27837.83 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 121.76 590.68 01-JAN-00:10 10631.20 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 121.76 590.68 01-JAN-00:10 10631.20 02-JAN-08:10
Electricity:Zone:CORE_MID 4113.71 50438.97 01-JAN-00:10 278377.67 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 1217.58 5906.80 01-JAN-00:10 106312.04 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 1217.58 5906.80 01-JAN-00:10 106312.04 02-JAN-08:10
Electricity:Zone:CORE_TOP 411.37 5043.90 01-JAN-00:10 27837.77 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 121.76 590.68 01-JAN-00:10 10631.20 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 121.76 590.68 01-JAN-00:10 10631.20 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 45.23 594.46 09-APR-17:10 3495.41 13-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 8.87 35.29 01-JAN-10:20 1334.85 13-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 8.87 35.29 01-JAN-10:20 1334.85 13-NOV-17:00
Electricity:Zone:PERIMETER_BOT_ZN_2 29.12 383.09 30-APR-17:10 2252.57 13-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 5.69 22.74 01-JAN-07:50 860.23 13-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 5.69 22.74 01-JAN-07:50 860.23 13-NOV-17:00
Electricity:Zone:PERIMETER_BOT_ZN_1 45.08 594.47 26-MAR-17:10 3495.47 13-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 8.71 35.29 01-JAN-07:50 1334.88 13-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 8.71 35.29 01-JAN-07:50 1334.88 13-NOV-17:00
Electricity:Zone:PERIMETER_BOT_ZN_4 29.07 383.09 12-MAR-17:10 2252.56 13-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 5.64 22.74 01-JAN-10:10 860.23 13-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 5.64 22.74 01-JAN-10:10 860.23 13-NOV-17:00
Electricity:Zone:PERIMETER_MID_ZN_3 452.35 5944.59 09-APR-17:10 34954.06 13-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 88.69 352.88 01-JAN-10:10 13348.54 13-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 88.69 352.88 01-JAN-10:10 13348.54 13-NOV-17:00
Electricity:Zone:PERIMETER_MID_ZN_2 291.21 3830.92 30-APR-17:10 22525.72 13-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 56.86 227.41 01-JAN-07:50 8602.31 13-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 56.86 227.41 01-JAN-07:50 8602.31 13-NOV-17:00
Electricity:Zone:PERIMETER_MID_ZN_1 450.81 5944.68 12-MAR-17:10 34954.68 13-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 87.15 352.89 01-JAN-07:50 13348.83 13-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 87.15 352.89 01-JAN-07:50 13348.83 13-NOV-17:00
Electricity:Zone:PERIMETER_MID_ZN_4 290.73 3830.90 12-MAR-17:10 22525.63 13-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 56.38 227.41 01-JAN-10:00 8602.31 13-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 56.38 227.41 01-JAN-10:00 8602.31 13-NOV-17:00
Electricity:Zone:PERIMETER_TOP_ZN_3 45.23 594.46 09-APR-17:10 3495.41 13-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 8.87 35.29 01-JAN-10:10 1334.85 13-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 8.87 35.29 01-JAN-10:10 1334.85 13-NOV-17:00
Electricity:Zone:PERIMETER_TOP_ZN_2 29.12 383.09 30-APR-17:10 2252.57 13-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 5.69 22.74 01-JAN-07:50 860.23 13-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 5.69 22.74 01-JAN-07:50 860.23 13-NOV-17:00
Electricity:Zone:PERIMETER_TOP_ZN_1 45.08 594.47 12-MAR-17:10 3495.47 13-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 8.72 35.29 01-JAN-07:50 1334.88 13-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 8.72 35.29 01-JAN-07:50 1334.88 13-NOV-17:00
Electricity:Zone:PERIMETER_TOP_ZN_4 29.07 383.09 12-MAR-17:10 2252.56 13-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 5.64 22.74 01-JAN-10:00 860.23 13-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 5.64 22.74 01-JAN-10:00 860.23 13-NOV-17:00
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7533.08 95093.58 01-JAN-00:10 382970.28 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 38.23 185.45 01-JAN-00:10 3337.76 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 38.23 185.45 01-JAN-00:10 3337.76 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 157.14 1964.44 01-JAN-00:10 8079.39 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 3.26 15.83 01-JAN-00:10 284.97 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 3.26 15.83 01-JAN-00:10 284.97 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1571.44 19644.38 01-JAN-00:10 80793.90 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 32.64 158.32 01-JAN-00:10 2849.68 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 32.64 158.32 01-JAN-00:10 2849.68 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 157.14 1964.44 01-JAN-00:10 8079.39 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 3.26 15.83 01-JAN-00:10 284.97 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 3.26 15.83 01-JAN-00:10 284.97 02-JAN-08:10
InteriorEquipment:Electricity 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 1558.24 885.61 22-JAN-07:00 337271.60 05-SEP-13:10
HeatRejection:Electricity 262.02 55.71 17-JAN-07:20 42924.61 06-JUN-13:20
General:HeatRejection:Electricity 262.02 55.71 17-JAN-07:20 42924.61 06-JUN-13:20
Electricity:HVAC 1882.96 10153.42 22-JAN-07:40 253554.25 07-AUG-15:40
ExteriorEquipment:Electricity 3258.17 45245.36 01-JAN-00:10 185192.48 08-DEC-08:20
Transformer:ExteriorEquipment:Electricity 54.48 979.82 01-JAN-00:10 3387.38 05-DEC-17:00
ElectricityPurchased:Facility 23665.43 287617.65 22-JAN-05:00 1632266.59 02-AUG-15:30
ElectricityPurchased:Plant 23665.43 287617.65 22-JAN-05:00 1632266.59 02-AUG-15:30
Cogeneration:ElectricityPurchased 23665.43 287617.65 22-JAN-05:00 1632266.59 02-AUG-15:30
General:Cogeneration:ElectricityPurchased 23665.43 287617.65 22-JAN-05:00 1632266.59 02-AUG-15:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 23665.43 287617.65 22-JAN-05:00 1632266.59 02-AUG-15:30
ElectricityNet:Plant 23665.43 287617.65 22-JAN-05:00 1632266.59 02-AUG-15:30
Cogeneration:ElectricityNet 23665.43 287617.65 22-JAN-05:00 1632266.59 02-AUG-15:30
General:Cogeneration:ElectricityNet 23665.43 287617.65 22-JAN-05:00 1632266.59 02-AUG-15:30
Fans:Electricity 1397.04 7385.66 01-JAN-00:10 217050.77 07-AUG-15:40
General:Fans:Electricity 1397.04 7385.66 01-JAN-00:10 217050.77 07-AUG-15:40
ExteriorLights:Electricity 323.19 0.00 01-JAN-07:20 37611.08 01-JAN-06:10
General:ExteriorLights:Electricity 323.19 0.00 01-JAN-07:20 37611.08 01-JAN-06:10
ComputerHVAC:ExteriorEquipment:Electricity 1349.07 17083.47 01-JAN-00:10 68333.87 31-MAR-23:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
Cooling:Electricity 1256.34 561.27 17-JAN-07:10 250464.06 31-JUL-15:00
General:Cooling:Electricity 1256.34 561.27 17-JAN-07:10 250464.06 31-JUL-15:00
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 471.31 727.82 17-JAN-04:50 61255.83 21-JUL-16:00
General:Pumps:Electricity 471.31 727.82 17-JAN-04:50 61255.83 21-JUL-16:00
WIRED_LTG_ELECTRICITY 56.79 0.00 01-JAN-00:10 5587.74 13-NOV-17:10
WIRED_INT_EQUIP 5334.97 88964.76 31-MAR-23:10 305206.10 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 1401.74 5695.87 06-FEB-05:30 709192.31 21-JAN-07:10
NaturalGas:Plant 1401.74 5695.87 06-FEB-05:30 709192.31 21-JAN-07:10
Heating:NaturalGas 708.77 0.00 01-JAN-00:10 681631.09 21-JAN-07:10
Boiler:Heating:NaturalGas 708.77 0.00 01-JAN-00:10 681631.09 21-JAN-07:10
WaterSystems:NaturalGas 692.97 5695.87 17-JAN-04:20 81624.73 03-FEB-12:40
Water Heater:WaterSystems:NaturalGas 692.97 5695.87 17-JAN-04:20 81624.73 03-FEB-12:40


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 8208.84 1958.01 17-JAN-07:10 1707275.76 05-SEP-13:10
PlantLoopCoolingDemand:HVAC 8208.84 1958.01 17-JAN-07:10 1707275.76 05-SEP-13:10
CoolingCoils:PlantLoopCoolingDemand 8208.84 1958.01 17-JAN-07:10 1707275.76 05-SEP-13:10
DistrictCooling:Facility 7193.90 87071.76 22-JAN-06:00 370603.48 21-AUG-16:00
DistrictCooling:HVAC 7193.90 87071.76 22-JAN-06:00 370603.48 21-AUG-16:00
Cooling:DistrictCooling 7193.90 87071.76 22-JAN-06:00 370603.48 21-AUG-16:00
General:Cooling:DistrictCooling 7193.90 87071.76 22-JAN-06:00 370603.48 21-AUG-16:00


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 8241.48 0.00 01-JAN-00:10 0.00 28-JUN-16:20
Water:Plant 8241.48 0.00 01-JAN-00:10 0.00 28-JUN-16:20
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Facility 8241.48 0.00 01-JAN-00:10 0.00 28-JUN-16:20
MainsWater:Plant 8241.48 0.00 01-JAN-00:10 0.00 28-JUN-16:20
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 5961.31 0.00 01-JAN-00:10 0.00 28-JUN-16:20
General:HeatRejection:Water 5961.31 0.00 01-JAN-00:10 0.00 28-JUN-16:20
HeatRejection:MainsWater 5961.31 0.00 01-JAN-00:10 0.00 28-JUN-16:20
General:HeatRejection:MainsWater 5961.31 0.00 01-JAN-00:10 0.00 28-JUN-16:20


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 46894.97 96199.12 22-JAN-05:40 8112663.19 05-SEP-13:00
EnergyTransfer:Building 18737.62 88748.02 22-JAN-03:10 1532302.24 07-AUG-15:30
EnergyTransfer:Zone:BASEMENT 628.05 0.00 01-JAN-00:10 67671.73 10-OCT-05:30
Heating:EnergyTransfer 156.78 0.00 01-JAN-16:20 333361.57 17-JAN-05:10
Heating:EnergyTransfer:Zone:BASEMENT 4.06 0.00 01-JAN-00:10 17515.35 22-JUL-16:10
General:Heating:EnergyTransfer 156.78 0.00 01-JAN-16:20 333361.57 17-JAN-05:10
General:Heating:EnergyTransfer:Zone:BASEMENT 4.06 0.00 01-JAN-00:10 17515.35 22-JUL-16:10
Cooling:EnergyTransfer 18580.84 87938.92 22-JAN-05:40 1532302.24 07-AUG-15:30
Cooling:EnergyTransfer:Zone:BASEMENT 623.99 0.00 01-JAN-00:10 67671.73 10-OCT-05:30
General:Cooling:EnergyTransfer 18580.84 87938.92 22-JAN-05:40 1532302.24 07-AUG-15:30
General:Cooling:EnergyTransfer:Zone:BASEMENT 623.99 0.00 01-JAN-00:10 67671.73 10-OCT-05:30
EnergyTransfer:Zone:CORE_BOTTOM 599.51 0.00 01-JAN-00:10 49887.88 21-AUG-09:10
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 599.51 0.00 01-JAN-00:10 49887.88 21-AUG-09:10
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 599.51 0.00 01-JAN-00:10 49887.88 21-AUG-09:10
EnergyTransfer:Zone:CORE_MID 4217.95 0.00 01-JAN-00:10 386587.53 05-SEP-13:10
Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_MID 4217.95 0.00 01-JAN-00:10 386587.53 05-SEP-13:10
General:Cooling:EnergyTransfer:Zone:CORE_MID 4217.95 0.00 01-JAN-00:10 386587.53 05-SEP-13:10
EnergyTransfer:Zone:CORE_TOP 396.42 0.00 01-JAN-00:10 53785.81 26-DEC-06:10
Heating:EnergyTransfer:Zone:CORE_TOP 4.35 0.00 01-JAN-00:10 53785.81 26-DEC-06:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 4.35 0.00 01-JAN-00:10 53785.81 26-DEC-06:10
Cooling:EnergyTransfer:Zone:CORE_TOP 392.07 0.00 01-JAN-00:10 46710.27 07-AUG-14:00
General:Cooling:EnergyTransfer:Zone:CORE_TOP 392.07 0.00 01-JAN-00:10 46710.27 07-AUG-14:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 72.07 0.00 01-JAN-00:10 10047.81 31-JUL-12:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 438.03 21-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 438.03 21-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 72.07 0.00 01-JAN-00:10 10047.81 31-JUL-12:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 72.07 0.00 01-JAN-00:10 10047.81 31-JUL-12:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 75.80 0.00 01-JAN-00:10 13139.62 05-JUL-07:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.01 0.00 01-JAN-00:10 1130.32 21-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.01 0.00 01-JAN-00:10 1130.32 21-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 75.79 0.00 01-JAN-00:10 13139.62 05-JUL-07:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 75.79 0.00 01-JAN-00:10 13139.62 05-JUL-07:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 118.72 0.00 01-JAN-00:10 16180.33 28-SEP-13:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.03 0.00 01-JAN-00:10 2723.79 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.03 0.00 01-JAN-00:10 2723.79 06-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 118.69 0.00 01-JAN-00:10 16180.33 28-SEP-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 118.69 0.00 01-JAN-00:10 16180.33 28-SEP-13:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 108.71 0.00 01-JAN-00:10 16482.97 21-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 108.71 0.00 01-JAN-00:10 16482.97 21-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 108.71 0.00 01-JAN-00:10 16482.97 21-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 541.30 0.00 01-JAN-00:10 92267.21 29-JUN-15:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 25.82 0.00 01-JAN-00:10 76584.45 17-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 25.82 0.00 01-JAN-00:10 76584.45 17-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 515.48 0.00 01-JAN-00:10 92267.21 29-JUN-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 515.48 0.00 01-JAN-00:10 92267.21 29-JUN-15:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 683.99 0.00 01-JAN-00:10 134214.90 05-JUL-08:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 10.50 0.00 01-JAN-00:10 51414.23 17-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 10.50 0.00 01-JAN-00:10 51414.23 17-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 673.49 0.00 01-JAN-00:10 134214.90 05-JUL-08:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 673.49 0.00 01-JAN-00:10 134214.90 05-JUL-08:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1052.55 0.00 01-JAN-00:10 162219.95 28-SEP-13:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 5.08 0.00 01-JAN-00:10 53681.09 18-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 5.08 0.00 01-JAN-00:10 53681.09 18-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1047.47 0.00 01-JAN-00:10 162219.95 28-SEP-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1047.47 0.00 01-JAN-00:10 162219.95 28-SEP-13:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 680.68 0.00 01-JAN-00:10 148430.02 28-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 5.79 0.00 01-JAN-00:10 44951.25 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 5.79 0.00 01-JAN-00:10 44951.25 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 674.89 0.00 01-JAN-00:10 148430.02 28-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 674.89 0.00 01-JAN-00:10 148430.02 28-JUN-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 61.93 0.00 01-JAN-00:10 12534.97 06-FEB-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 13.04 0.00 01-JAN-00:10 12534.97 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 13.04 0.00 01-JAN-00:10 12534.97 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 48.89 0.00 01-JAN-00:10 10613.41 29-JUN-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 48.89 0.00 01-JAN-00:10 10613.41 29-JUN-15:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 70.12 0.00 01-JAN-00:10 13769.50 05-JUL-08:50
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 5.25 0.00 01-JAN-00:10 11619.68 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 5.25 0.00 01-JAN-00:10 11619.68 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 64.87 0.00 01-JAN-00:10 13769.50 05-JUL-08:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 64.87 0.00 01-JAN-00:10 13769.50 05-JUL-08:50
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 102.54 0.00 01-JAN-00:10 17674.64 28-SEP-13:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 4.63 0.00 01-JAN-00:10 14487.26 17-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 4.63 0.00 01-JAN-00:10 14487.26 17-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 97.92 0.00 01-JAN-00:10 17674.64 28-SEP-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 97.92 0.00 01-JAN-00:10 17674.64 28-SEP-13:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 69.28 0.00 01-JAN-00:10 15827.98 28-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 3.95 0.00 01-JAN-00:10 9959.52 17-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 3.95 0.00 01-JAN-00:10 9959.52 17-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 65.33 0.00 01-JAN-00:10 15827.98 28-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 65.33 0.00 01-JAN-00:10 15827.98 28-JUN-16:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 61.59 0.00 01-JAN-00:10 10023.02 21-AUG-07:10
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 1.45 0.00 01-JAN-00:10 3811.56 10-DEC-11:10
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 1.45 0.00 01-JAN-00:10 3811.56 10-DEC-11:10
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 60.14 0.00 01-JAN-00:10 10023.02 21-AUG-07:10
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 60.14 0.00 01-JAN-00:10 10023.02 21-AUG-07:10
EnergyTransfer:Zone:MIDFLOOR_PLENUM 435.90 0.00 01-JAN-00:10 69832.43 05-JUL-15:00
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 48.94 0.00 01-JAN-00:10 39757.68 06-FEB-15:30
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 48.94 0.00 01-JAN-00:10 39757.68 06-FEB-15:30
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 386.96 0.00 01-JAN-00:10 69832.43 05-JUL-15:00
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 386.96 0.00 01-JAN-00:10 69832.43 05-JUL-15:00
EnergyTransfer:Zone:TOPFLOOR_PLENUM 96.08 0.00 01-JAN-00:10 22131.90 28-JUN-13:30
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 23.01 0.00 01-JAN-00:10 17651.00 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 23.01 0.00 01-JAN-00:10 17651.00 06-FEB-06:10
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 73.07 0.00 01-JAN-00:10 22131.90 28-JUN-13:30
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 73.07 0.00 01-JAN-00:10 22131.90 28-JUN-13:30
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 139.63 746.98 21-JAN-08:00 8246.09 16-APR-18:00
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 139.63 746.98 21-JAN-08:00 8246.09 16-APR-18:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 139.63 746.98 21-JAN-08:00 8246.09 16-APR-18:00
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1239.42 6.38 22-JAN-13:10 77713.05 16-APR-17:50
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.12 0.00 01-JAN-00:10 2027.16 17-JAN-05:20
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.12 0.00 01-JAN-00:10 2027.16 17-JAN-05:20
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1239.30 0.00 16-JAN-23:00 77713.05 16-APR-17:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1239.30 0.00 16-JAN-23:00 77713.05 16-APR-17:50
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 116.05 1.17 28-JAN-16:50 7764.10 16-APR-17:50
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.75 0.00 01-JAN-16:00 659.01 16-JAN-18:30
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.75 0.00 01-JAN-16:00 659.01 16-JAN-18:30
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 115.30 0.00 01-JAN-00:10 7764.10 16-APR-17:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 115.30 0.00 01-JAN-00:10 7764.10 16-APR-17:50
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7169.33 87071.76 22-JAN-06:00 368004.50 21-AUG-16:00
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7169.33 87071.76 22-JAN-06:00 368004.50 21-AUG-16:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7169.33 87071.76 22-JAN-06:00 368004.50 21-AUG-16:00
PlantLoopHeatingDemand:Facility 917.63 0.00 01-JAN-00:10 592939.73 06-FEB-07:10
PlantLoopHeatingDemand:Plant 400.27 0.00 01-JAN-00:10 50679.46 03-FEB-12:50
WaterSystems:PlantLoopHeatingDemand 400.27 0.00 01-JAN-00:10 50679.46 03-FEB-12:50
General:WaterSystems:PlantLoopHeatingDemand 400.27 0.00 01-JAN-00:10 50679.46 03-FEB-12:50
EnergyTransfer:HVAC 8294.76 5789.45 22-JAN-07:40 1698528.13 05-SEP-13:10
HeatingCoils:EnergyTransfer 517.36 0.00 01-JAN-00:10 576155.32 06-FEB-07:10
PlantLoopHeatingDemand:HVAC 517.36 0.00 01-JAN-00:10 576155.32 06-FEB-07:10
HeatingCoils:PlantLoopHeatingDemand 517.36 0.00 01-JAN-00:10 576155.32 06-FEB-07:10
CoolingCoils:EnergyTransfer 7777.40 1396.74 17-JAN-07:10 1698528.13 05-SEP-13:10
DistrictHeating:Facility 0.00 0.00 01-JAN-01:10 12.11 01-MAR-00:30
DistrictHeating:HVAC 0.00 0.00 01-JAN-01:10 12.11 01-MAR-00:30
Heating:DistrictHeating 0.00 0.00 01-JAN-01:10 12.11 01-MAR-00:30
General:Heating:DistrictHeating 0.00 0.00 01-JAN-01:10 12.11 01-MAR-00:30
EnergyTransfer:Plant 19862.59 0.00 01-JAN-00:10 5314925.64 05-SEP-13:00
LoopToLoop:EnergyTransfer 6343.58 0.00 01-JAN-00:10 1674610.08 05-SEP-13:10
WaterSystems:EnergyTransfer 400.27 0.00 01-JAN-00:10 50679.46 03-FEB-12:50
WaterUse:WaterSystems:EnergyTransfer 400.27 0.00 01-JAN-00:10 50679.46 03-FEB-12:50
Boilers:EnergyTransfer 512.62 0.00 01-JAN-00:10 567347.86 21-JAN-07:10
Chillers:EnergyTransfer 5890.60 0.00 01-JAN-00:10 1684443.15 05-SEP-13:10
HeatRejection:EnergyTransfer 6715.50 0.00 01-JAN-00:10 1924758.03 05-SEP-13:10
General:HeatRejection:EnergyTransfer 6715.50 0.00 01-JAN-00:10 1924758.03 05-SEP-13:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 4.065 -623.985 0.000 0.000 92.617 135.577 424.397 0.000 0.000 0.000 0.006 0.000 0.000 0.000 0.000 -32.672
CORE_BOTTOM 0.000 0.000 0.000 -599.503 0.000 0.000 83.428 121.758 289.614 0.000 0.000 0.000 104.703 0.000 0.000 0.000 0.000 -0.002
CORE_MID 0.000 0.000 0.000 -4217.920 0.000 0.000 841.232 1217.578 2896.128 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -737.017
CORE_TOP 0.000 0.000 4.345 -392.069 0.000 0.000 86.804 121.758 289.613 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -110.451
PERIMETER_BOT_ZN_3 0.000 0.000 0.001 -72.072 0.000 0.000 10.703 8.868 36.365 29.193 0.000 0.047 31.467 0.000 -43.351 0.000 -1.222 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.006 -75.794 0.000 0.000 6.874 5.687 23.435 69.958 0.000 0.032 0.003 0.000 -26.597 0.000 -0.813 -2.789
PERIMETER_BOT_ZN_1 0.000 0.000 0.029 -118.691 0.000 0.000 10.539 8.714 36.366 125.146 0.000 0.046 0.001 0.000 -40.898 0.000 -1.267 -19.983
PERIMETER_BOT_ZN_4 0.000 0.000 0.000 -108.707 0.000 0.000 6.796 5.639 23.435 63.679 0.000 0.029 41.385 0.000 -31.350 0.000 -0.906 0.000
PERIMETER_MID_ZN_3 0.000 0.000 25.818 -515.475 0.000 0.000 111.657 88.694 363.654 302.613 0.000 1.112 43.894 0.000 -395.901 0.000 -26.067 0.000
PERIMETER_MID_ZN_2 0.000 0.000 10.504 -673.486 0.000 0.000 51.840 56.860 234.352 700.203 0.000 0.711 0.002 0.000 -253.142 0.000 -18.198 -109.645
PERIMETER_MID_ZN_1 0.000 0.000 5.081 -1047.447 0.000 0.000 105.860 87.151 363.660 1247.520 0.000 1.044 0.014 0.000 -401.401 0.000 -29.155 -332.314
PERIMETER_MID_ZN_4 0.000 0.000 5.792 -674.871 0.000 0.000 71.034 56.378 234.351 646.958 0.000 0.677 0.011 0.000 -278.874 0.000 -18.919 -42.526
PERIMETER_TOP_ZN_3 0.000 0.000 13.042 -48.885 0.000 0.000 11.354 8.869 36.365 30.685 0.000 0.128 0.002 0.000 -37.059 0.000 -3.014 -11.486
PERIMETER_TOP_ZN_2 0.000 0.000 5.249 -64.871 0.000 0.000 7.151 5.686 23.435 70.367 0.000 0.083 0.002 0.000 -23.929 0.000 -2.126 -21.045
PERIMETER_TOP_ZN_1 0.000 0.000 4.626 -97.914 0.000 0.000 10.778 8.715 36.366 125.240 0.000 0.124 0.004 0.000 -37.969 0.000 -3.410 -46.556
PERIMETER_TOP_ZN_4 0.000 0.000 3.948 -65.328 0.000 0.000 7.216 5.638 23.435 64.855 0.000 0.081 0.002 0.000 -26.470 0.000 -2.222 -11.153
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -139.626 0.000 0.000 0.950 3.264 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -18.468
DATACENTER_MID_ZN_6 0.000 0.000 0.123 -1239.301 0.000 0.000 9.501 32.637 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -341.765
DATACENTER_TOP_ZN_6 0.000 0.000 0.751 -115.298 0.000 0.000 0.951 3.264 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -43.549
DATACENTER_BASEMENT_ZN_6 0.000 -7169.327 0.000 0.000 0.000 0.000 20.569 38.227 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -384.326
GROUNDFLOOR_PLENUM 1.451 -60.135 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.087 61.207 0.000 0.000 0.000 -2.611 0.000
MIDFLOOR_PLENUM 48.943 -386.959 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.615 381.241 0.000 0.000 0.000 -44.839 -0.005
TOPFLOOR_PLENUM 23.007 -73.072 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.133 54.672 0.000 0.000 0.000 -4.739 -0.001
Total Facility 73.401 -7689.494 83.379 -10891.241 0.000 0.000 1547.855 2020.960 14676.396 3476.418 0.000 5.950 718.613 0.000 -1596.941 0.000 -159.506 -2265.752


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 26-DEC-04:01 0.00 0.00 0.00 -99505.94 0.00 0.00 0.00 657.72 13457.54 0.00 0.00 0.00 85390.68 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 10-OCT-03:02 0.00 0.00 0.00 -81657.77 0.00 0.00 0.00 590.68 5937.65 0.00 0.00 0.00 75129.45 0.00 -0.00 0.00 0.00 0.00
CORE_MID 06-SEP-04:03 0.00 0.00 0.00 -715951.47 0.00 0.00 0.00 11812.12 59376.23 0.00 0.00 0.00 644763.12 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 17-JUL-03:02 0.00 0.00 0.00 -73166.21 0.00 0.00 0.00 590.68 5937.62 0.00 0.00 0.00 66637.91 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 02-JUL-17:31 0.00 0.00 0.00 -15109.26 0.00 0.00 0.00 35.29 559.17 4911.33 0.00 38.39 9565.08 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 03-SEP-08:21 0.00 0.00 0.00 -19701.71 0.00 0.00 21.12 22.74 464.11 15532.83 0.00 0.00 3666.81 0.00 -0.00 0.00 -5.89 0.00
PERIMETER_BOT_ZN_1 09-OCT-12:41 0.00 0.00 0.00 -21106.66 0.00 0.00 33.21 35.29 720.19 21413.32 0.00 0.00 0.00 0.00 -0.00 0.00 -16.27 -1079.08
PERIMETER_BOT_ZN_4 11-JUN-17:11 0.00 0.00 0.00 -26797.96 0.00 0.00 0.00 22.74 360.35 16823.34 0.00 0.00 9595.48 0.00 -0.00 0.00 -3.95 0.00
PERIMETER_MID_ZN_3 04-JUL-18:12 0.00 0.00 0.00 -143943.32 0.00 0.00 0.00 352.88 5591.71 56501.20 0.00 1381.71 80115.83 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 04-JUL-08:51 0.00 0.00 0.00 -221852.59 0.00 0.00 184.38 227.41 4641.14 150877.99 0.00 0.00 66091.81 0.00 -0.00 0.00 -170.14 0.00
PERIMETER_MID_ZN_1 01-OCT-12:21 0.00 0.00 0.00 -210104.99 0.00 0.00 296.82 352.89 7201.95 214965.60 0.00 0.00 0.00 0.00 -0.00 0.00 -174.39 -12537.88
PERIMETER_MID_ZN_4 04-JUL-16:51 0.00 0.00 0.00 -243448.18 0.00 0.00 152.23 227.41 4641.11 173098.68 0.00 1087.82 64240.93 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 25-JUN-17:21 0.00 0.00 0.00 -16825.53 0.00 0.00 0.00 35.29 559.17 5603.96 0.00 138.28 10488.83 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 25-JUN-08:61 0.00 0.00 0.00 -21237.27 0.00 0.00 20.61 22.74 464.11 15511.69 0.00 0.00 5245.77 0.00 -0.00 0.00 -27.66 0.00
PERIMETER_TOP_ZN_1 01-OCT-13:12 0.00 0.00 0.00 -21703.61 0.00 0.00 28.60 35.29 720.19 19766.23 0.00 0.00 1159.26 0.00 -0.00 0.00 -5.96 0.00
PERIMETER_TOP_ZN_4 25-JUN-16:41 0.00 0.00 0.00 -26439.99 0.00 0.00 14.67 22.74 464.11 16763.35 0.00 57.13 9117.99 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 16-APR-18:20 0.00 0.00 0.00 -8249.41 0.00 0.00 0.00 15.83 7794.42 0.00 0.00 0.00 439.16 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 16-APR-17:42 0.00 0.00 0.00 -77713.05 0.00 0.00 0.00 158.32 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -389.50
DATACENTER_TOP_ZN_6 16-APR-17:42 0.00 0.00 0.00 -7764.10 0.00 0.00 0.00 15.83 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -46.16
DATACENTER_BASEMENT_ZN_6 21-AUG-16:00 0.00 -368004.49 0.00 0.00 0.00 0.00 2183.10 3337.76 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -17148.89
GROUNDFLOOR_PLENUM 05-JUL-05:15 0.00 -12946.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12962.49 0.00 -0.00 0.00 -15.66 0.00
MIDFLOOR_PLENUM 17-JUL-05:03 0.00 -74146.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 74375.59 0.00 -0.00 0.00 -229.13 0.00
TOPFLOOR_PLENUM 28-JUN-13:30 0.00 -22126.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 49.67 22076.80 0.00 -0.00 0.00 0.00 0.00
Total Facility 04-AUG-05:02 0.00 -355094.00 0.00 -1441993.47 0.00 0.00 15504.20 22094.05 616289.16 0.00 0.00 0.00 1199601.22 0.00 -55065.24 0.00 -1335.92 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 22-JUL-15:02 0.00 0.00 19666.85 0.00 0.00 0.00 1040.26 1973.00 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -36137.65
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_TOP 17-JAN-04:11 0.00 0.00 67593.13 0.00 0.00 0.00 0.00 590.68 5937.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -74121.44
PERIMETER_BOT_ZN_3 21-JAN-06:01 0.00 0.00 2702.00 0.00 0.00 0.00 140.46 148.31 960.25 0.00 0.00 0.00 327.23 0.00 -4278.25 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 21-JAN-06:01 0.00 0.00 5180.72 0.00 0.00 0.00 92.08 95.58 618.82 0.00 0.00 0.00 0.00 0.00 -2818.27 0.00 0.00 -3168.92
PERIMETER_BOT_ZN_1 19-JAN-06:01 0.00 0.00 9373.41 0.00 0.00 0.00 144.33 148.32 960.26 0.00 0.00 0.00 0.00 0.00 -3544.91 0.00 -9.87 -7071.54
PERIMETER_BOT_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 17-JAN-05:01 0.00 0.00 108725.61 0.00 0.00 0.00 0.00 1483.13 7455.61 0.00 0.00 0.00 0.00 0.00 -34482.16 0.00 -6317.03 -76865.16
PERIMETER_MID_ZN_2 17-JAN-05:01 0.00 0.00 123192.27 0.00 0.00 0.00 0.00 955.79 4804.68 0.00 0.00 0.00 0.00 0.00 -23139.49 0.00 -4301.87 -101511.37
PERIMETER_MID_ZN_1 18-JAN-05:01 0.00 0.00 129795.84 0.00 0.00 0.00 0.00 1483.16 7455.72 0.00 0.00 0.00 0.00 0.00 -32828.91 0.00 -3570.12 -102335.70
PERIMETER_MID_ZN_4 06-FEB-05:01 0.00 0.00 118270.72 0.00 0.00 0.00 0.00 955.79 4804.65 0.00 0.00 0.00 0.00 0.00 -25826.70 0.00 -4103.90 -94100.56
PERIMETER_TOP_ZN_3 06-FEB-04:11 0.00 0.00 14224.10 0.00 0.00 0.00 0.00 74.17 745.56 0.00 0.00 0.00 0.00 0.00 -3227.99 0.00 -610.20 -11205.64
PERIMETER_TOP_ZN_2 17-JAN-04:11 0.00 0.00 16187.78 0.00 0.00 0.00 0.00 47.80 480.47 0.00 0.00 0.00 0.00 0.00 -1957.32 0.00 -515.98 -14242.75
PERIMETER_TOP_ZN_1 17-JAN-04:11 0.00 0.00 16929.46 0.00 0.00 0.00 0.00 74.17 745.57 0.00 0.00 0.00 0.00 0.00 -2911.35 0.00 -772.09 -14065.76
PERIMETER_TOP_ZN_4 06-FEB-04:11 0.00 0.00 16791.49 0.00 0.00 0.00 0.00 47.80 480.46 0.00 0.00 0.00 0.00 0.00 -2263.72 0.00 -427.59 -14628.44
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 17-JAN-05:17 0.00 0.00 2027.16 0.00 0.00 0.00 0.00 316.62 19486.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -21829.84
DATACENTER_TOP_ZN_6 16-JAN-18:30 0.00 0.00 659.01 0.00 0.00 0.00 0.00 15.83 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2623.45
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 11-DEC-04:01 10865.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -296.42 -10568.79
MIDFLOOR_PLENUM 12-MAR-16:21 87957.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -861.30 -87096.61
TOPFLOOR_PLENUM 06-FEB-05:13 20669.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -960.55 -19709.10
Total Facility 17-JAN-05:01 -348730.74 228164.48 601911.48 -228164.48 0.00 0.00 0.00 22094.05 232425.23 0.00 0.00 0.00 0.00 0.00 -139452.01 0.00 -38306.48 -329941.53



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 11.6124 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.4877 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 109.1649 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 97.1601 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 11.3927 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.6575 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.9249 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.9249 0.2026 1.0000 Not calculated 1.2002 0.2026    
AIRLOOP DATACENTER BOT 0.5720 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5720 0.0273 1.0000 Not calculated 0.0156 0.0273    
AIRLOOP DATACENTER MID 5.4631 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 5.4631 0.0286 1.0000 Not calculated 0.1563 0.0286    
AIRLOOP DATACENTER TOP 0.5585 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5585 0.0280 1.0000 Not calculated 0.0156 0.0280    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 5.8062 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.0589 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 54.5825 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 29.6916 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.6963 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.0828 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.9249 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.9249 1.0000 1.0000 Not calculated 1.2002 0.2026    
AIRLOOP DATACENTER BOT 0.5720 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5720 1.0000 1.0000 Not calculated 0.0156 0.0273    
AIRLOOP DATACENTER MID 5.4631 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 5.4631 1.0000 1.0000 Not calculated 0.1563 0.0286    
AIRLOOP DATACENTER TOP 0.5585 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5585 1.0000 1.0000 Not calculated 0.0156 0.0280    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.002360 149.6021 0.000305 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.002360 1.9486 0.000305 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.002360 19.4861 0.000305 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.002360 1.9486 0.000305 36.20 0.0156 1.0000 0.0156 1.000 0.0156


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.002360 149.60 0.000305 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BOT 0.002360 1.95 0.000305 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.002360 19.49 0.000305 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.002360 1.95 0.000305 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.9249 5.9249 5.9249 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.3828 6.3828 1.9787 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 59.7112 59.7112 19.3464 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.9989 5.9989 1.9856 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0716 1.0716 0.2486 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2483 1.2483 0.2497 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3118 1.3118 0.2624 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5979 1.5979 0.3196 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.8792 9.8792 2.4303 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 13.1434 13.1434 2.6287 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 12.3969 12.3969 2.4794 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 14.0342 14.0342 2.8068 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1517 1.1517 0.2488 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3350 1.3350 0.2670 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3902 1.3902 0.2780 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5169 1.5169 0.3034 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5720 0.5720 0.5720 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.4631 5.4631 5.4631 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5585 0.5585 0.5585 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 11.6124 10.4877 11.6124 3.0589 0.0000 1.0000
VAV_MID WITH REHEAT 109.1649 97.1601 109.1649 29.6916 0.0000 1.0000
VAV_TOP WITH REHEAT 11.3927 10.6575 11.3927 3.0828 0.0000 1.0000
CAV_BAS 5.9249 5.9249 5.9249 5.9249 1.2002 1.0000
AIRLOOP DATACENTER BOT 0.5720 0.5720 0.5720 0.5720 0.0156 1.0000
AIRLOOP DATACENTER MID 5.4631 5.4631 5.4631 5.4631 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.5585 0.5585 0.5585 0.5585 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.9249 5.9249 5.9249 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.1914 3.1914 1.9787 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 29.8556 29.8556 19.3464 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.9995 2.9995 1.9856 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5358 0.5358 0.2486 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6241 0.6241 0.2497 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6559 0.6559 0.2624 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7989 0.7989 0.3196 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.9396 4.9396 2.4303 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.5717 6.5717 2.6287 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.1985 6.1985 2.4794 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.0171 7.0171 2.8068 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5758 0.5758 0.2488 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6675 0.6675 0.2670 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6951 0.6951 0.2780 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7584 0.7584 0.3034 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5720 0.5720 0.5720 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.4631 5.4631 5.4631 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5585 0.5585 0.5585 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 5.8062 3.0589 3.0589 3.0589 0.0000 1.0000
VAV_MID WITH REHEAT 54.5825 29.6916 29.6916 29.6916 0.0000 1.0000
VAV_TOP WITH REHEAT 5.6963 3.0828 3.0828 3.0828 0.0000 1.0000
CAV_BAS 5.9249 5.9249 5.9249 5.9249 1.2002 1.0000
AIRLOOP DATACENTER BOT 0.5720 0.5720 0.5720 0.5720 0.0156 1.0000
AIRLOOP DATACENTER MID 5.4631 5.4631 5.4631 5.4631 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.5585 0.5585 0.5585 0.5585 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 8.50
Number of hours cooling loads not met 358.50
Number of hours not met 367.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.11
Heating -- Boiler 0.00 0.00 708.77 681631.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 1256.34 250464.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7193.90 370603.48 0.00 0.00
Interior Lighting -- LightsWired 2020.96 198852.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 323.19 37611.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5334.97 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 54.48 3387.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ComputerHVAC 1349.07 68333.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 1397.04 217050.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 471.31 61255.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 262.02 42924.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 692.97 81624.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 14676.40 23665.43
Natural Gas 0.00 1401.74
Additional 0.00 7193.90
Total 14676.40 32261.07


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 43.63
Space Heating 0.00
Space Cooling 27.12
Fans (All) 30.16
Service Water Heating 0.00
Receptacle Equipment 316.85
Miscellaneous (All) 510.91
Subtotal 510.91


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 15.30
Service Water Heating 14.96
Miscellaneous (All) 30.26
Subtotal 30.26


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.26
Space Heating 2.20
Space Cooling 26.19
Fans (All) 4.33
Service Water Heating 2.15
Receptacle Equipment 45.49
Miscellaneous 13.37


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2362. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4049. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 1565. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8595.67 164.33 0.00 0.00 0.00
CORE_BOTTOM 8759.33 0.67 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8746.00 14.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8698.17 61.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8712.83 47.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8577.17 182.83 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8757.50 2.50 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8679.33 80.67 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8711.00 49.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8665.33 94.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8742.83 17.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8667.17 92.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8711.33 48.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8651.83 108.17 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8755.67 4.33 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8756.50 3.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8754.67 5.33 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 8760.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8648.00 112.00 0.00 0.00 0.00
Min 8577.17 0.00 0.00 0.00 0.00
Max 8760.00 182.83 0.00 0.00 0.00
Average 8712.62 47.38 0.00 0.00 0.00
Sum 200390.33 1089.67 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 368024.50 591.50 0.00 0.00 0.00
CORE_BOTTOM 330813.00 0.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 103395.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 368024.50 591.50 0.00 0.00 0.00
Average 80309.20 25.72 0.00 0.00 0.00
Sum 1847111.50 591.50 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8468.33 291.67 0.00 0.00 0.00
CORE_BOTTOM 8681.00 79.00 0.00 0.00 0.00
CORE_MID 8674.50 85.50 0.00 0.00 0.00
CORE_TOP 8680.50 79.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8648.33 111.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8656.17 103.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8628.83 131.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8478.17 281.83 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8679.67 80.33 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8598.50 161.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8628.50 131.50 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8576.33 183.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8663.83 96.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8585.17 174.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8621.83 138.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8576.50 183.50 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 8760.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8612.17 147.83 0.00 0.00 0.00
MIDFLOOR_PLENUM 8687.50 72.50 0.00 0.00 0.00
TOPFLOOR_PLENUM 8518.17 241.83 0.00 0.00 0.00
Min 8468.33 0.00 0.00 0.00 0.00
Max 8760.00 291.67 0.00 0.00 0.00
Average 8639.30 120.70 0.00 0.00 0.00
Sum 198704.00 2776.00 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 367708.33 907.67 0.00 0.00 0.00
CORE_BOTTOM 330648.00 165.00 0.00 0.00 0.00
CORE_MID 330711.00 102.00 0.00 0.00 0.00
CORE_TOP 330713.00 100.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 103395.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 367708.33 907.67 0.00 0.00 0.00
Average 80279.49 55.42 0.00 0.00 0.00
Sum 1846428.33 1274.67 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:05:12

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

For: Environment

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B

For: Environment

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE

For: Environment

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 2.601
February 4.285
March 8.765
April 13.905
May 17.822
June 23.208
July 25.626
August 24.075
September 20.490
October 13.707
November 6.961
December 2.072
   
Annual Sum or Average 13.676
Minimum of Months 2.072
Maximum of Months 25.626



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.451263E+11 96079.45 02-JAN-04:01 -1.8 -3.6 0.566820E+10 7499.05 13-JAN-10:20 4.63 1.40
February 0.412829E+11 95709.72 13-FEB-04:12 1.10 -1.6 0.514248E+10 7499.06 01-FEB-10:00 1.10 -1.6
March 0.507331E+11 94938.96 27-MAR-03:02 5.50 0.89 0.613884E+10 7499.00 02-MAR-14:09 5.50 0.89
April 0.490997E+11 96031.11 03-APR-03:02 9.22 2.19 0.545595E+10 7499.01 26-APR-13:20 24.80 9.90
May 0.514072E+11 90367.51 08-MAY-03:02 11.78 4.09 0.590805E+10 7579.14 22-MAY-09:50 24.13 14.54
June 0.534415E+11 90431.24 20-JUN-03:02 10.78 4.69 0.588901E+10 7524.83 12-JUN-09:00 10.78 4.69
July 0.554158E+11 80936.43 24-JUL-03:02 22.80 14.96 0.548194E+10 7503.63 17-JUL-09:09 22.80 14.96
August 0.612174E+11 81674.88 29-AUG-03:02 16.10 12.92 0.614799E+10 7559.33 28-AUG-09:00 16.10 12.92
September 0.554090E+11 86787.53 25-SEP-04:33 11.50 9.68 0.546107E+10 7572.41 25-SEP-09:00 21.10 13.60
October 0.572091E+11 96421.87 23-OCT-03:02 8.22 7.00 0.567979E+10 7592.33 10-OCT-09:00 8.22 7.00
November 0.534212E+11 96358.15 06-NOV-04:03 2.62 -1.0 0.562059E+10 7498.88 08-NOV-10:30 13.60 6.17
December 0.502257E+11 99506.48 26-DEC-04:01 0.32 -0.9 0.547607E+10 7498.98 15-DEC-10:09 0.32 -0.9
                     
Annual Sum or Average 0.623989E+12         0.680700E+11        
Minimum of Months 0.412829E+11 80936.43   -1.8 -3.6 0.514248E+10 7498.88   0.32 -1.6
Maximum of Months 0.612174E+11 99506.48   22.80 14.96 0.614799E+10 7592.33   24.80 14.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.351877E+11 79998.77 02-JAN-04:01 -1.8 -3.6 0.505997E+10 6734.70 25-JAN-10:09 5.37 0.26
February 0.351833E+11 77998.49 21-FEB-05:01 2.38 0.37 0.460072E+10 6734.73 15-FEB-10:09 2.38 0.37
March 0.485980E+11 77652.34 06-MAR-05:01 -0.5 -2.7 0.549909E+10 6734.68 28-MAR-13:09 16.42 7.54
April 0.542047E+11 80188.60 24-APR-03:02 5.18 2.43 0.488243E+10 6734.75 17-APR-13:00 5.18 2.43
May 0.496572E+11 80784.94 30-MAY-03:02 14.82 11.26 0.528584E+10 6734.97 11-MAY-09:09 14.82 11.26
June 0.572387E+11 81363.13 05-JUN-03:02 15.00 13.28 0.526890E+10 6734.83 30-JUN-13:00 26.70 17.72
July 0.626860E+11 77325.47 10-JUL-05:04 20.10 15.68 0.489545E+10 6734.73 28-JUL-09:30 25.25 16.67
August 0.683911E+11 73702.45 07-AUG-05:03 18.90 13.67 0.549697E+10 6735.72 28-AUG-13:39 23.30 16.88
September 0.501024E+11 80281.51 18-SEP-03:02 14.90 11.31 0.488470E+10 6734.80 27-SEP-09:09 18.77 10.94
October 0.500654E+11 81648.50 10-OCT-03:02 14.82 11.26 0.507881E+10 6734.79 24-OCT-13:39 10.53 5.31
November 0.458073E+11 79880.82 13-NOV-04:02 0.00 -1.8 0.502727E+10 6734.69 27-NOV-10:09 1.28 -3.1
December 0.423839E+11 79675.90 26-DEC-04:01 0.32 -0.9 0.490004E+10 6734.74 26-DEC-10:09 2.38 0.81
                     
Annual Sum or Average 0.599506E+12         0.608802E+11        
Minimum of Months 0.351833E+11 73702.45   -1.8 -3.6 0.460072E+10 6734.68   1.28 -3.1
Maximum of Months 0.683911E+11 81648.50   20.10 15.68 0.549909E+10 6735.72   26.70 17.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.242329E+11 32835.33 06-JAN-06:02 -1.2 -3.4 0.485853E+10 6734.70 13-JAN-10:20 4.63 1.40
February 0.233414E+11 65564.13 15-FEB-06:02 6.93 2.40 0.449228E+10 6734.69 24-FEB-10:09 3.07 0.76
March 0.320848E+11 66413.10 17-MAR-05:03 7.02 1.62 0.545107E+10 6734.69 01-MAR-10:09 7.02 1.62
April 0.349103E+11 70841.15 03-APR-05:02 7.85 1.31 0.486414E+10 6734.67 17-APR-13:00 24.40 9.80
May 0.403018E+11 71170.20 27-MAY-05:02 11.70 9.43 0.527460E+10 6734.94 11-MAY-09:09 11.70 9.43
June 0.444337E+11 71487.60 06-JUN-05:02 12.38 10.89 0.526338E+10 6734.84 30-JUN-13:00 26.70 17.72
July 0.455286E+11 69027.86 08-JUL-04:03 16.20 14.71 0.489099E+10 6734.76 18-JUL-09:39 25.37 17.15
August 0.475830E+11 71252.39 11-AUG-04:03 17.02 14.97 0.549340E+10 6735.74 28-AUG-13:50 23.30 17.44
September 0.406932E+11 71607.36 06-SEP-04:03 15.00 14.26 0.487631E+10 6734.77 27-SEP-09:09 18.77 10.94
October 0.362992E+11 71350.80 03-OCT-04:03 14.27 11.53 0.505171E+10 6734.72 24-OCT-13:39 10.53 5.31
November 0.282900E+11 68235.06 02-NOV-05:03 7.12 4.64 0.496491E+10 6734.63 08-NOV-10:09 13.40 6.02
December 0.240958E+11 52968.10 01-DEC-06:02 3.90 -0.5 0.470402E+10 6734.68 20-DEC-10:20 1.10 -3.7
                     
Annual Sum or Average 0.421795E+12         0.601853E+11        
Minimum of Months 0.233414E+11 32835.33   -1.2 -3.4 0.449228E+10 6734.63   1.10 -3.7
Maximum of Months 0.475830E+11 71607.36   17.02 14.97 0.549340E+10 6735.74   26.70 17.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.167203E+11 20067.73 26-JAN-14:30 10.30 1.59 0.422358E+10 6476.69 27-JAN-14:00 11.70 2.33
February 0.173663E+11 28549.28 15-FEB-17:00 16.70 5.85 0.400944E+10 6734.15 15-FEB-14:00 16.70 5.85
March 0.254087E+11 30862.57 08-MAR-17:00 22.20 8.27 0.517763E+10 6734.55 02-MAR-14:09 22.20 8.27
April 0.318071E+11 67824.44 27-APR-05:02 9.40 3.12 0.479924E+10 6734.71 17-APR-13:00 9.40 3.12
May 0.399091E+11 71538.32 22-MAY-04:03 17.62 11.88 0.525020E+10 6734.88 11-MAY-09:09 17.62 11.88
June 0.481957E+11 70135.66 01-JUN-05:02 14.08 10.66 0.526001E+10 6759.25 28-JUN-13:50 37.70 14.07
July 0.514775E+11 73178.46 17-JUL-03:02 19.82 16.22 0.489540E+10 6734.74 18-JUL-09:50 25.73 17.29
August 0.523622E+11 71618.94 23-AUG-04:03 18.80 14.52 0.549586E+10 6735.80 28-AUG-13:50 23.30 17.44
September 0.407606E+11 71260.14 05-SEP-04:03 17.52 15.20 0.486642E+10 6734.73 27-SEP-09:09 18.77 10.94
October 0.308544E+11 69966.59 03-OCT-05:02 15.92 11.83 0.490441E+10 6734.65 24-OCT-13:50 8.87 4.55
November 0.208740E+11 32200.75 01-NOV-15:30 11.70 6.90 0.454489E+10 6734.62 01-NOV-09:09 11.70 6.90
December 0.163377E+11 19982.30 29-DEC-13:50 10.32 3.31 0.407714E+10 6597.41 01-DEC-14:00 10.32 3.31
                     
Annual Sum or Average 0.392074E+12         0.575042E+11        
Minimum of Months 0.163377E+11 19982.30   9.40 1.59 0.400944E+10 6476.69   8.87 2.33
Maximum of Months 0.523622E+11 73178.46   22.20 16.22 0.549586E+10 6759.25   37.70 17.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.253108E+10 2719.64 02-JAN-15:00 14.40 5.68 0.562362E+09 838.01 24-JAN-14:00 16.10 4.97
February 0.259073E+10 3750.60 15-FEB-15:00 17.20 6.67 0.534006E+09 845.61 15-FEB-10:09 17.20 6.67
March 0.422152E+10 5760.11 27-MAR-14:30 18.05 6.97 0.675096E+09 845.62 28-MAR-13:09 16.42 7.54
April 0.615758E+10 7355.41 14-APR-14:00 23.30 10.26 0.609305E+09 845.63 17-APR-13:00 24.40 9.80
May 0.668480E+10 11005.24 22-MAY-05:03 16.78 12.20 0.662366E+09 845.65 11-MAY-09:09 16.78 12.20
June 0.982487E+10 13458.65 25-JUN-17:31 32.97 15.43 0.662532E+09 845.65 30-JUN-13:00 26.70 17.72
July 0.110037E+11 15111.79 02-JUL-17:31 31.50 16.65 0.616466E+09 846.27 05-JUL-13:39 32.43 17.28
August 0.110605E+11 12691.04 06-AUG-17:11 30.20 16.04 0.691191E+09 845.77 28-AUG-13:39 23.30 16.88
September 0.678979E+10 11564.76 05-SEP-05:03 15.92 14.88 0.612789E+09 845.63 27-SEP-09:09 18.77 10.94
October 0.503010E+10 11726.67 02-OCT-05:02 17.12 12.75 0.625855E+09 845.63 24-OCT-13:39 10.53 5.31
November 0.342341E+10 4238.76 09-NOV-14:10 19.22 9.76 0.608049E+09 845.61 21-NOV-14:09 15.18 5.79
December 0.275487E+10 3069.03 01-DEC-14:10 11.78 4.41 0.556180E+09 845.60 11-DEC-14:50 8.30 1.61
                     
Annual Sum or Average 0.720730E+11         0.741620E+10        
Minimum of Months 0.253108E+10 2719.64   11.78 4.41 0.534006E+09 838.01   8.30 1.61
Maximum of Months 0.110605E+11 15111.79   32.97 16.65 0.691191E+09 846.27   32.43 17.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.274580E+10 5898.44 02-JAN-09:25 2.75 -0.6 0.371433E+09 544.95 13-JAN-10:20 4.63 1.40
February 0.292795E+10 7858.14 14-FEB-09:05 7.25 1.90 0.351271E+09 544.96 15-FEB-10:09 11.38 5.33
March 0.483383E+10 14575.87 26-MAR-10:02 14.50 5.54 0.436027E+09 544.95 28-MAR-13:09 16.42 7.54
April 0.721739E+10 18986.40 30-APR-07:42 14.63 5.07 0.393452E+09 546.04 28-APR-09:50 14.63 5.07
May 0.767349E+10 18989.56 14-MAY-07:32 18.17 8.24 0.427534E+09 545.80 15-MAY-09:20 20.37 9.24
June 0.990595E+10 18763.84 11-JUN-07:12 16.50 10.30 0.426977E+09 546.01 19-JUN-09:00 21.10 8.29
July 0.104517E+11 19574.39 02-JUL-08:51 23.30 17.35 0.397402E+09 546.29 06-JUL-09:20 27.93 15.97
August 0.105012E+11 18472.03 20-AUG-08:42 25.82 15.35 0.445229E+09 546.28 21-AUG-09:39 26.33 17.13
September 0.738765E+10 19702.07 03-SEP-08:21 24.45 14.44 0.394901E+09 545.92 11-SEP-09:09 21.47 13.47
October 0.561441E+10 18691.48 01-OCT-08:52 17.80 11.25 0.404587E+09 544.97 18-OCT-09:09 12.35 5.73
November 0.371202E+10 8144.12 01-NOV-08:50 9.63 6.30 0.392614E+09 544.95 27-NOV-10:09 1.28 -3.1
December 0.282236E+10 5195.85 29-DEC-09:15 1.67 -0.9 0.361860E+09 544.95 26-DEC-10:09 1.67 -0.9
                     
Annual Sum or Average 0.757937E+11         0.480329E+10        
Minimum of Months 0.274580E+10 5195.85   1.67 -0.9 0.351271E+09 544.95   1.28 -3.1
Maximum of Months 0.105012E+11 19702.07   25.82 17.35 0.445229E+09 546.29   27.93 17.13



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.724252E+10 19019.32 01-JAN-13:42 15.22 5.54 0.608619E+09 872.06 02-JAN-14:09 13.98 5.50
February 0.745306E+10 18959.56 12-FEB-13:52 17.20 5.72 0.564102E+09 897.77 14-FEB-14:09 20.78 7.02
March 0.847981E+10 19031.34 12-MAR-12:32 16.50 5.25 0.680492E+09 847.08 20-MAR-13:00 18.30 8.36
April 0.927265E+10 18649.04 30-APR-13:02 20.78 7.24 0.610108E+09 847.29 17-APR-13:00 20.78 7.24
May 0.780952E+10 13227.95 14-MAY-14:12 27.23 10.89 0.661559E+09 845.67 09-MAY-13:20 27.23 10.89
June 0.987727E+10 13958.08 26-JUN-05:02 15.73 10.17 0.662037E+09 845.67 30-JUN-13:00 26.70 17.72
July 0.119607E+11 18924.90 30-JUL-12:32 31.10 17.67 0.616649E+09 846.65 25-JUL-13:20 31.10 17.67
August 0.141469E+11 19066.64 06-AUG-12:32 30.37 16.16 0.692019E+09 851.13 31-AUG-13:09 29.50 15.73
September 0.120111E+11 20638.37 03-SEP-12:21 30.85 16.81 0.616411E+09 925.84 28-SEP-13:39 29.63 15.09
October 0.119626E+11 21108.33 09-OCT-12:41 20.13 9.80 0.640428E+09 927.84 31-OCT-13:30 21.40 8.63
November 0.970347E+10 20309.76 23-NOV-12:02 12.48 4.07 0.628768E+09 931.80 01-NOV-13:20 12.48 4.07
December 0.877304E+10 19326.24 31-DEC-13:32 9.43 1.41 0.599842E+09 881.56 29-DEC-14:09 9.43 1.41
                     
Annual Sum or Average 0.118693E+12         0.758103E+10        
Minimum of Months 0.724252E+10 13227.95   9.43 1.41 0.564102E+09 845.67   9.43 1.41
Maximum of Months 0.141469E+11 21108.33   31.10 17.67 0.692019E+09 931.80   31.10 17.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.410885E+10 8105.56 26-JAN-16:30 10.30 1.40 0.376521E+09 544.93 04-JAN-14:50 10.30 1.40
February 0.491986E+10 15419.34 12-FEB-15:53 18.30 6.40 0.360400E+09 544.95 15-FEB-10:09 11.38 5.33
March 0.780052E+10 22791.75 12-MAR-15:52 19.40 6.09 0.444061E+09 544.96 28-MAR-13:09 16.42 7.54
April 0.111739E+11 24315.45 16-APR-16:21 20.00 7.96 0.396682E+09 544.97 26-APR-13:30 25.00 9.94
May 0.885787E+10 25307.63 14-MAY-16:11 28.30 10.92 0.427888E+09 544.98 11-MAY-09:09 28.30 10.92
June 0.123365E+11 26797.93 11-JUN-17:11 28.13 12.99 0.427924E+09 544.97 30-JUN-13:00 26.70 17.72
July 0.142555E+11 26401.13 02-JUL-17:31 31.50 16.65 0.398278E+09 544.97 18-JUL-09:39 25.37 17.15
August 0.158276E+11 24857.87 20-AUG-16:01 34.90 15.92 0.446723E+09 545.09 28-AUG-13:39 23.30 16.88
September 0.905493E+10 23829.37 17-SEP-15:12 24.27 14.52 0.396254E+09 544.96 19-SEP-13:09 25.18 14.10
October 0.823014E+10 24354.39 01-OCT-14:51 28.30 12.89 0.409082E+09 544.97 24-OCT-13:39 10.53 5.31
November 0.645171E+10 22358.65 12-NOV-15:02 9.40 2.60 0.405168E+09 544.95 21-NOV-14:09 15.18 5.79
December 0.569155E+10 15342.68 24-DEC-16:03 11.93 3.13 0.392141E+09 544.95 26-DEC-10:09 2.38 0.81
                     
Annual Sum or Average 0.108709E+12         0.488112E+10        
Minimum of Months 0.410885E+10 8105.56   9.40 1.40 0.360400E+09 544.93   2.38 0.81
Maximum of Months 0.158276E+11 26797.93   34.90 16.65 0.446723E+09 545.09   28.30 17.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.121441E+10 2286.36 05-JAN-15:40 16.10 6.84 0.482915E+09 722.27 04-JAN-14:00 16.10 6.84
February 0.149282E+10 2594.80 15-FEB-16:00 17.20 6.50 0.457405E+09 799.81 15-FEB-14:00 17.20 6.50
March 0.259427E+10 3289.05 27-MAR-14:50 18.22 7.02 0.613094E+09 845.61 28-MAR-13:09 16.42 7.54
April 0.369161E+10 6122.81 14-APR-14:30 23.60 10.45 0.591247E+09 845.62 26-APR-13:20 24.80 9.90
May 0.534018E+10 6936.80 31-MAY-15:30 27.75 11.03 0.657133E+09 845.64 11-MAY-09:09 27.75 11.03
June 0.814311E+10 13958.90 18-JUN-18:21 29.15 10.43 0.661759E+09 845.90 23-JUN-13:50 34.22 12.87
July 0.877678E+10 14393.75 04-JUL-18:12 33.33 13.61 0.616190E+09 845.86 17-JUL-13:50 28.30 17.53
August 0.820991E+10 10672.59 21-AUG-05:03 21.60 15.49 0.690592E+09 845.78 28-AUG-13:50 23.30 17.44
September 0.544343E+10 9345.46 15-SEP-05:02 18.90 12.28 0.609950E+09 845.62 27-SEP-09:09 18.77 10.94
October 0.351102E+10 6273.64 02-OCT-13:40 26.33 15.37 0.591129E+09 845.62 24-OCT-13:39 10.53 5.31
November 0.211611E+10 2639.61 01-NOV-15:10 12.43 7.32 0.523751E+09 845.59 09-NOV-14:00 18.30 9.49
December 0.101452E+10 2136.06 29-DEC-15:40 11.50 3.90 0.458480E+09 765.11 01-DEC-14:00 11.50 3.90
                     
Annual Sum or Average 0.515482E+11         0.695365E+10        
Minimum of Months 0.101452E+10 2136.06   11.50 3.90 0.457405E+09 722.27   10.53 3.90
Maximum of Months 0.877678E+10 14393.75   33.33 15.49 0.690592E+09 845.90   34.22 17.53



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.179589E+10 3060.89 27-JAN-09:50 2.43 -2.7 0.243480E+09 521.19 27-JAN-09:39 2.43 -2.7
February 0.217423E+10 6192.25 14-FEB-09:40 8.90 2.72 0.233423E+09 521.20 09-FEB-11:09 8.90 2.72
March 0.390738E+10 14733.90 26-MAR-09:53 14.40 5.52 0.306166E+09 521.22 17-MAR-15:30 14.40 5.52
April 0.623859E+10 20495.33 30-APR-08:11 15.20 5.08 0.288104E+09 521.65 27-APR-08:00 15.20 5.08
May 0.741088E+10 20892.27 29-MAY-08:51 18.30 12.78 0.313475E+09 521.41 19-MAY-08:50 18.30 12.78
June 0.965776E+10 21504.21 18-JUN-09:01 25.78 11.91 0.313785E+09 529.03 29-JUN-07:19 27.93 17.35
July 0.998803E+10 22171.54 04-JUL-08:51 26.70 18.67 0.293617E+09 528.01 05-JUL-07:19 24.80 15.16
August 0.970457E+10 19868.04 20-AUG-08:42 25.82 15.35 0.327559E+09 522.95 02-AUG-10:30 25.82 15.35
September 0.704741E+10 20843.26 03-SEP-09:01 25.97 15.10 0.289750E+09 521.46 01-SEP-08:39 25.97 15.10
October 0.487100E+10 19213.91 01-OCT-08:22 16.70 10.70 0.290089E+09 521.22 02-OCT-12:20 25.20 14.93
November 0.280285E+10 7186.20 01-NOV-09:00 10.00 6.46 0.266318E+09 521.20 01-NOV-07:49 10.00 6.46
December 0.175024E+10 2792.13 31-DEC-10:53 3.30 -1.9 0.231905E+09 521.19 29-DEC-09:39 3.30 -1.9
                     
Annual Sum or Average 0.673488E+11         0.339767E+10        
Minimum of Months 0.175024E+10 2792.13   2.43 -2.7 0.231905E+09 521.19   2.43 -2.7
Maximum of Months 0.998803E+10 22171.54   26.70 18.67 0.327559E+09 529.03   27.93 17.35



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.695598E+10 18415.75 01-JAN-13:42 15.22 5.54 0.598821E+09 927.27 26-JAN-14:20 10.20 1.54
February 0.701410E+10 18353.30 19-FEB-13:42 15.92 6.62 0.556167E+09 955.62 14-FEB-14:20 15.92 6.62
March 0.740961E+10 18754.49 12-MAR-13:42 17.62 5.94 0.667497E+09 866.79 13-MAR-13:50 20.32 6.92
April 0.728110E+10 17632.86 30-APR-12:53 20.60 7.16 0.603836E+09 846.64 17-APR-13:00 20.60 7.16
May 0.679307E+10 11946.75 14-MAY-13:02 26.70 11.10 0.658357E+09 845.67 09-MAY-13:20 26.70 11.10
June 0.829400E+10 16953.10 25-JUN-16:31 34.07 14.58 0.660956E+09 845.67 30-JUN-13:50 28.08 17.83
July 0.978656E+10 17842.37 30-JUL-11:22 29.45 17.97 0.616618E+09 846.15 25-JUL-13:00 29.45 17.97
August 0.116091E+11 18207.56 13-AUG-12:52 28.30 18.16 0.692182E+09 870.94 31-AUG-13:09 29.50 15.73
September 0.114751E+11 19937.63 03-SEP-12:21 30.85 16.81 0.620160E+09 988.22 28-SEP-13:39 29.63 15.09
October 0.113833E+11 21009.57 01-OCT-12:21 26.40 14.34 0.644218E+09 987.71 31-OCT-13:00 22.80 8.86
November 0.898756E+10 18872.81 05-NOV-14:42 12.70 3.30 0.626829E+09 989.80 01-NOV-13:30 12.70 3.30
December 0.775747E+10 18688.48 31-DEC-13:32 9.43 1.41 0.588110E+09 920.22 29-DEC-14:09 9.43 1.41
                     
Annual Sum or Average 0.104747E+12         0.753375E+10        
Minimum of Months 0.679307E+10 11946.75   9.43 1.41 0.556167E+09 845.67   9.43 1.41
Maximum of Months 0.116091E+11 21009.57   34.07 18.16 0.692182E+09 989.80   29.63 17.97



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.218459E+10 5985.73 26-JAN-16:30 10.30 1.40 0.332198E+09 544.05 05-JAN-14:00 10.30 1.40
February 0.268999E+10 9756.71 15-FEB-16:30 16.95 6.18 0.313951E+09 544.93 14-FEB-14:30 16.95 6.18
March 0.417059E+10 19540.50 12-MAR-16:21 20.00 6.24 0.400020E+09 544.94 17-MAR-13:00 16.10 5.42
April 0.584456E+10 21997.81 16-APR-16:31 20.20 8.02 0.382675E+09 544.96 17-APR-13:00 24.40 9.80
May 0.684979E+10 21237.34 14-MAY-16:21 28.30 10.87 0.421437E+09 544.97 16-MAY-13:00 25.00 9.24
June 0.901648E+10 23754.38 25-JUN-16:31 34.07 14.58 0.425708E+09 544.97 30-JUN-13:00 26.70 17.72
July 0.944910E+10 24346.58 04-JUL-16:51 36.10 14.82 0.397430E+09 544.96 18-JUL-09:39 25.37 17.15
August 0.950569E+10 22543.37 13-AUG-17:31 29.63 17.01 0.445702E+09 545.07 28-AUG-13:50 23.30 17.44
September 0.700198E+10 21849.66 24-SEP-16:11 25.40 15.61 0.393465E+09 544.97 18-SEP-13:00 25.40 15.61
October 0.533805E+10 20314.07 01-OCT-14:21 28.30 13.27 0.384480E+09 544.96 04-OCT-13:50 25.32 13.57
November 0.328876E+10 8561.60 02-NOV-16:00 16.70 9.78 0.355769E+09 544.93 03-NOV-13:50 12.12 2.35
December 0.214945E+10 4958.10 29-DEC-16:00 11.70 3.88 0.320549E+09 542.11 29-DEC-14:00 11.70 3.88
                     
Annual Sum or Average 0.674890E+11         0.457338E+10        
Minimum of Months 0.214945E+10 4958.10   10.30 1.40 0.313951E+09 542.11   10.30 1.40
Maximum of Months 0.950569E+10 24346.58   36.10 17.01 0.445702E+09 545.07   26.70 17.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.438983E+09 1950.73 05-JAN-14:30 16.10 6.84 0.467256E+09 673.75 24-JAN-14:00 16.10 4.97
February 0.762953E+09 2564.02 15-FEB-15:30 17.20 6.59 0.433826E+09 769.24 15-FEB-14:00 17.20 6.59
March 0.195035E+10 2437.04 08-MAR-14:00 22.80 9.68 0.571670E+09 845.60 17-MAR-13:00 16.10 5.42
April 0.335444E+10 6510.26 28-APR-15:30 25.00 10.42 0.569805E+09 845.62 17-APR-13:00 25.00 10.42
May 0.527615E+10 7656.48 31-MAY-15:10 27.38 11.00 0.648023E+09 845.64 31-MAY-13:20 27.38 11.00
June 0.869498E+10 16825.95 25-JUN-17:21 33.05 15.18 0.660389E+09 863.71 28-JUN-13:50 37.70 14.07
July 0.965758E+10 16228.25 04-JUL-18:21 33.05 13.57 0.616489E+09 845.72 07-JUL-13:50 33.80 18.39
August 0.885503E+10 16030.75 13-AUG-17:31 29.63 17.01 0.690456E+09 845.78 28-AUG-13:50 23.30 17.44
September 0.545486E+10 9809.10 05-SEP-05:03 15.92 14.88 0.605685E+09 845.64 13-SEP-13:30 26.40 14.44
October 0.296495E+10 6697.20 02-OCT-13:40 26.33 15.37 0.564468E+09 845.63 02-OCT-13:30 26.33 15.37
November 0.121881E+10 2622.24 01-NOV-15:20 12.07 7.11 0.487982E+09 795.79 09-NOV-14:00 18.30 9.49
December 0.256919E+09 1771.74 29-DEC-15:00 11.10 3.93 0.448893E+09 693.92 01-DEC-14:00 11.10 3.93
                     
Annual Sum or Average 0.488860E+11         0.676494E+10        
Minimum of Months 0.256919E+09 1771.74   11.10 3.93 0.433826E+09 673.75   11.10 3.93
Maximum of Months 0.965758E+10 16825.95   33.05 17.01 0.690456E+09 863.71   37.70 18.39



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.104916E+10 2306.27 03-JAN-13:40 14.63 5.67 0.312916E+09 501.62 27-JAN-10:30 4.45 -1.6
February 0.148182E+10 4103.45 14-FEB-10:10 10.83 3.59 0.301503E+09 544.94 13-FEB-10:20 10.83 3.59
March 0.312278E+10 6216.37 24-MAR-09:40 8.87 2.60 0.405972E+09 544.95 10-MAR-10:20 8.87 2.60
April 0.584130E+10 18563.88 30-APR-09:12 15.97 4.95 0.390253E+09 545.77 28-APR-09:00 15.97 4.95
May 0.742923E+10 20967.31 29-MAY-08:51 18.30 12.78 0.425552E+09 545.74 19-MAY-09:00 18.30 12.78
June 0.102358E+11 21241.33 25-JUN-08:61 24.37 15.49 0.426753E+09 548.24 28-JUN-13:50 37.70 14.07
July 0.108249E+11 20396.73 09-JUL-07:32 21.67 17.20 0.398014E+09 546.00 06-JUL-09:39 21.67 17.20
August 0.104359E+11 20239.70 20-AUG-09:22 27.20 16.00 0.445679E+09 545.77 21-AUG-09:39 26.33 17.13
September 0.716749E+10 19327.39 03-SEP-09:12 26.33 15.30 0.392968E+09 545.69 01-SEP-09:20 26.33 15.30
October 0.431562E+10 12533.01 01-OCT-10:32 22.97 13.29 0.388324E+09 544.97 02-OCT-13:30 26.15 15.30
November 0.200711E+10 5957.18 01-NOV-09:30 11.40 7.09 0.341899E+09 544.95 01-NOV-09:09 11.40 7.09
December 0.960740E+09 2326.75 29-DEC-13:30 9.75 3.05 0.296354E+09 494.48 29-DEC-10:09 9.75 3.05
                     
Annual Sum or Average 0.648718E+11         0.452619E+10        
Minimum of Months 0.960740E+09 2306.27   8.87 2.60 0.296354E+09 494.48   4.45 -1.6
Maximum of Months 0.108249E+11 21241.33   27.20 17.20 0.445679E+09 548.24   37.70 17.20



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.513126E+10 15604.49 26-JAN-14:10 10.10 1.50 0.570943E+09 848.41 26-JAN-14:20 10.20 1.54
February 0.553152E+10 19615.05 19-FEB-13:42 15.92 6.62 0.529391E+09 890.28 14-FEB-14:30 15.92 6.62
March 0.613517E+10 20189.73 12-MAR-14:22 18.90 6.18 0.638696E+09 846.10 16-MAR-13:00 20.60 8.86
April 0.683784E+10 13429.60 28-APR-13:20 24.40 9.99 0.589394E+09 846.74 27-APR-13:00 24.40 9.99
May 0.684145E+10 19343.26 21-MAY-13:22 27.25 12.27 0.649239E+09 845.67 08-MAY-13:39 27.25 12.27
June 0.895691E+10 20035.70 25-JUN-16:01 35.22 14.86 0.658413E+09 860.91 28-JUN-13:50 37.70 14.07
July 0.108184E+11 19681.37 30-JUL-14:52 33.30 17.94 0.616556E+09 846.23 25-JUL-13:39 33.30 17.94
August 0.125036E+11 20681.81 13-AUG-12:52 28.30 18.16 0.691601E+09 853.52 31-AUG-13:09 29.50 15.73
September 0.116660E+11 21127.87 03-SEP-13:12 31.67 16.75 0.614744E+09 957.46 28-SEP-13:39 29.63 15.09
October 0.106020E+11 21703.13 01-OCT-13:12 27.57 13.97 0.622603E+09 951.99 05-OCT-13:50 26.52 12.57
November 0.711001E+10 20705.00 19-NOV-12:52 11.10 2.63 0.599856E+09 933.78 01-NOV-13:39 11.10 2.63
December 0.578218E+10 19573.49 31-DEC-13:53 10.00 1.60 0.560754E+09 845.63 20-DEC-14:00 10.00 1.60
                     
Annual Sum or Average 0.979163E+11         0.734219E+10        
Minimum of Months 0.513126E+10 13429.60   10.00 1.50 0.529391E+09 845.63   10.00 1.54
Maximum of Months 0.125036E+11 21703.13   35.22 18.16 0.691601E+09 957.46   37.70 17.94



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.141734E+10 5111.87 26-JAN-16:30 10.30 1.40 0.321946E+09 525.05 05-JAN-14:00 10.30 1.40
February 0.203853E+10 9462.24 15-FEB-16:30 16.95 6.18 0.301588E+09 544.91 15-FEB-14:00 16.95 6.18
March 0.356438E+10 16945.30 12-MAR-16:21 20.00 6.24 0.377929E+09 544.93 09-MAR-14:09 20.00 6.24
April 0.561767E+10 19624.90 16-APR-16:42 20.40 8.08 0.369699E+09 544.96 17-APR-13:00 24.40 9.80
May 0.693513E+10 22372.87 29-MAY-16:11 26.83 13.10 0.413673E+09 544.97 08-MAY-13:39 26.83 13.10
June 0.954943E+10 26440.78 25-JUN-16:41 33.68 14.48 0.423717E+09 562.83 27-JUN-15:00 37.80 15.32
July 0.101852E+11 24114.46 04-JUL-17:01 35.73 14.63 0.397250E+09 544.96 18-JUL-09:50 25.73 17.29
August 0.101260E+11 24590.33 13-AUG-17:31 29.63 17.01 0.445190E+09 545.07 28-AUG-13:50 23.30 17.44
September 0.711545E+10 21764.53 24-SEP-16:22 25.30 15.57 0.389735E+09 544.99 13-SEP-13:30 25.30 15.57
October 0.490563E+10 20249.59 01-OCT-15:12 28.50 13.01 0.370528E+09 544.96 02-OCT-13:30 26.15 15.30
November 0.254392E+10 8014.94 02-NOV-16:00 16.70 9.78 0.337074E+09 544.93 14-NOV-14:00 12.20 4.12
December 0.133095E+10 4126.86 29-DEC-16:00 11.70 3.88 0.312010E+09 525.17 20-DEC-14:00 11.70 3.88
                     
Annual Sum or Average 0.653296E+11         0.446034E+10        
Minimum of Months 0.133095E+10 4126.86   10.30 1.40 0.301588E+09 525.05   10.30 1.40
Maximum of Months 0.101852E+11 26440.78   35.73 17.01 0.445190E+09 562.83   37.80 17.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.105026E+10 4470.19 02-JAN-06:13 -4.0 -4.9 0.00 0.00 01-JAN-00:10 -4.0 -4.9
February 0.139090E+10 3848.95 15-FEB-06:15 6.67 2.30 0.00 0.00 01-FEB-00:10 6.67 2.30
March 0.326331E+10 4609.66 27-MAR-05:15 5.40 0.66 0.00 0.00 01-MAR-00:10 5.40 0.66
April 0.520331E+10 5992.80 03-APR-05:15 7.40 1.11 0.00 0.00 01-APR-00:10 7.40 1.11
May 0.568528E+10 9042.10 30-MAY-05:15 14.43 10.90 0.00 0.00 01-MAY-00:10 14.43 10.90
June 0.803215E+10 9610.85 19-JUN-05:15 12.93 5.33 0.00 0.00 01-JUN-00:10 12.93 5.33
July 0.940725E+10 12949.10 05-JUL-05:15 22.20 13.64 0.00 0.00 01-JUL-00:10 22.20 13.64
August 0.989691E+10 11496.02 14-AUG-05:15 18.90 16.75 0.00 0.00 01-AUG-00:10 18.90 16.75
September 0.671530E+10 11855.72 05-SEP-05:15 15.73 14.76 0.00 0.00 01-SEP-00:10 15.73 14.76
October 0.503392E+10 9622.60 10-OCT-05:15 13.90 11.14 0.00 0.00 01-OCT-00:10 13.90 11.14
November 0.293879E+10 4451.51 01-NOV-16:00 10.60 6.24 0.00 0.00 01-NOV-00:10 10.60 6.24
December 0.151846E+10 3296.45 01-DEC-06:08 3.90 -0.5 0.00 0.00 01-DEC-00:10 3.90 -0.5
                     
Annual Sum or Average 0.601358E+11         0.00        
Minimum of Months 0.105026E+10 3296.45   -4.0 -4.9 0.00 0.00   -4.0 -4.9
Maximum of Months 0.989691E+10 12949.10   22.20 16.75 0.00 0.00   22.20 16.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.413285E+09 5061.46 07-JAN-06:01 -3.6 -4.7 0.00 0.00 01-JAN-00:10 -3.6 -4.7
February 0.514501E+09 5792.84 06-FEB-05:01 -4.4 -6.9 0.00 0.00 01-FEB-00:10 -4.4 -6.9
March 0.109560E+10 3462.00 06-MAR-06:01 -2.9 -4.2 0.00 0.00 01-MAR-00:10 -2.9 -4.2
April 0.268871E+10 4348.98 28-APR-15:00 25.00 10.42 0.00 0.00 01-APR-00:10 25.00 10.42
May 0.402395E+10 4915.67 22-MAY-05:03 16.78 12.20 0.00 0.00 01-MAY-00:10 16.78 12.20
June 0.615745E+10 6533.22 29-JUN-16:00 35.60 16.66 0.00 0.00 01-JUN-00:10 35.60 16.66
July 0.719098E+10 7414.71 17-JUL-05:03 18.90 15.60 0.00 0.00 01-JUL-00:10 18.90 15.60
August 0.723601E+10 7063.57 01-AUG-05:03 19.50 14.33 0.00 0.00 01-AUG-00:10 19.50 14.33
September 0.504053E+10 6873.42 05-SEP-05:15 15.73 14.76 0.00 0.00 01-SEP-00:10 15.73 14.76
October 0.296708E+10 5479.02 03-OCT-05:15 15.73 11.98 0.00 0.00 01-OCT-00:10 15.73 11.98
November 0.973315E+09 4596.83 27-NOV-06:01 -4.4 -6.8 0.00 0.00 01-NOV-00:10 -4.4 -6.8
December 0.394804E+09 4736.73 22-DEC-05:01 -4.7 -6.6 0.00 0.00 01-DEC-00:10 -4.7 -6.6
                     
Annual Sum or Average 0.386962E+11         0.00        
Minimum of Months 0.394804E+09 3462.00   -4.7 -6.9 0.00 0.00   -4.7 -6.9
Maximum of Months 0.723601E+10 7414.71   35.60 16.66 0.00 0.00   35.60 16.66



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.151849E+09 2445.03 01-JAN-14:07 15.68 5.68 0.00 0.00 01-JAN-00:10 15.68 5.68
February 0.632194E+09 5445.95 15-FEB-15:40 17.20 6.56 0.00 0.00 01-FEB-00:10 17.20 6.56
March 0.214067E+10 8089.37 08-MAR-15:00 22.20 9.10 0.00 0.00 01-MAR-00:10 22.20 9.10
April 0.571951E+10 14519.40 28-APR-14:40 24.80 10.38 0.00 0.00 01-APR-00:10 24.80 10.38
May 0.829070E+10 17188.04 30-MAY-14:30 27.20 12.25 0.00 0.00 01-MAY-00:10 27.20 12.25
June 0.130640E+11 22131.90 28-JUN-13:30 37.50 13.98 0.00 0.00 01-JUN-00:10 37.50 13.98
July 0.150163E+11 21191.77 21-JUL-14:20 37.80 15.31 0.00 0.00 01-JUL-00:10 37.80 15.31
August 0.142201E+11 19721.30 07-AUG-14:20 33.13 15.81 0.00 0.00 01-AUG-00:10 33.13 15.81
September 0.894466E+10 15310.84 01-SEP-15:00 28.90 16.64 0.00 0.00 01-SEP-00:10 28.90 16.64
October 0.413873E+10 11768.63 05-OCT-14:30 26.70 12.37 0.00 0.00 01-OCT-00:10 26.70 12.37
November 0.689807E+09 4850.12 01-NOV-14:30 12.50 7.40 0.00 0.00 01-NOV-00:10 12.50 7.40
December 66184821.66 2760.66 31-DEC-14:35 10.73 2.01 0.00 0.00 01-DEC-00:10 10.73 2.01
                     
Annual Sum or Average 0.730746E+11         0.00        
Minimum of Months 66184821.66 2445.03   10.73 2.01 0.00 0.00   10.73 2.01
Maximum of Months 0.150163E+11 22131.90   37.80 16.64 0.00 0.00   37.80 16.64



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.329526E+10 2219.59 26-JAN-17:00 10.00 1.21 95230029.74 126.82 20-JAN-14:00 10.00 1.21
February 0.796817E+10 4245.45 15-FEB-17:00 16.70 5.85 86396712.89 126.83 17-FEB-10:00 7.20 4.72
March 0.143130E+11 7109.00 31-MAR-24:00 6.90 3.36 0.103236E+09 126.83 29-MAR-09:30 6.90 3.36
April 0.189435E+11 8249.41 16-APR-18:20 19.03 7.42 91608945.43 126.82 20-APR-09:00 12.20 5.87
May 0.444143E+10 3498.44 31-MAY-24:00 18.60 7.93 99235417.78 126.85 24-MAY-09:00 18.60 7.93
June 0.936004E+10 5340.36 30-JUN-24:00 22.10 13.89 98962425.84 126.85 08-JUN-13:00 22.10 13.89
July 0.147497E+11 7235.22 31-JUL-23:45 21.03 17.45 91887035.51 126.84 17-JUL-09:09 21.03 17.45
August 0.197449E+11 7918.70 30-AUG-17:40 28.50 14.73 0.103347E+09 127.65 17-AUG-13:00 28.50 14.73
September 0.444090E+10 3499.55 30-SEP-24:00 17.40 10.77 91612888.06 126.85 06-SEP-13:00 17.40 10.77
October 0.946269E+10 5294.71 31-OCT-24:00 13.00 4.55 95233436.97 126.85 11-OCT-09:00 13.00 4.55
November 0.138048E+11 6127.23 05-NOV-16:33 11.87 2.83 94300882.44 126.83 02-NOV-13:09 11.87 2.83
December 0.191018E+11 7931.78 31-DEC-16:35 9.27 1.21 91880730.22 126.82 08-DEC-14:09 9.27 1.21
                     
Annual Sum or Average 0.139626E+12         0.114293E+10        
Minimum of Months 0.329526E+10 2219.59   6.90 1.21 86396712.89 126.82   6.90 1.21
Maximum of Months 0.197449E+11 8249.41   28.50 17.45 0.103347E+09 127.65   28.50 17.45



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.143402E+10 1980.92 26-JAN-17:00 10.00 1.21 95230042.37 126.82 20-JAN-14:00 10.00 1.21
February 0.625101E+10 3974.96 15-FEB-17:00 16.70 5.85 86396718.99 126.83 17-FEB-10:00 7.20 4.72
March 0.126587E+11 6545.31 31-MAR-23:40 6.70 3.28 0.103236E+09 126.83 29-MAR-09:30 6.70 3.28
April 0.176833E+11 7771.31 16-APR-17:42 19.60 7.69 91607558.64 126.82 20-APR-09:00 12.20 5.87
May 0.387476E+10 3308.29 31-MAY-24:00 18.60 7.93 99235042.77 126.84 24-MAY-09:30 18.60 7.93
June 0.877938E+10 5162.22 30-JUN-24:00 22.10 13.89 98962137.59 126.85 08-JUN-13:00 22.10 13.89
July 0.140274E+11 6983.22 31-JUL-23:53 21.00 17.53 91886944.24 126.84 17-JUL-09:09 21.00 17.53
August 0.188268E+11 7563.57 30-AUG-17:40 28.50 14.73 0.103339E+09 127.79 17-AUG-13:00 28.50 14.73
September 0.394247E+10 3300.54 30-SEP-24:00 17.40 10.77 91612027.00 126.84 08-SEP-13:00 17.40 10.77
October 0.833391E+10 4809.10 31-OCT-24:00 13.00 4.55 95233217.87 126.84 11-OCT-09:00 13.00 4.55
November 0.118800E+11 5689.75 02-NOV-16:40 16.30 9.65 94300851.68 126.83 02-NOV-09:00 16.30 9.65
December 0.162384E+11 7290.76 29-DEC-16:50 10.28 3.14 91880788.98 126.82 08-DEC-14:09 10.28 3.14
                     
Annual Sum or Average 0.123930E+12         0.114292E+10        
Minimum of Months 0.143402E+10 1980.92   6.70 1.21 86396718.99 126.82   6.70 1.21
Maximum of Months 0.188268E+11 7771.31   28.50 17.53 0.103339E+09 127.79   28.50 17.53



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.488023E+09 1825.53 26-JAN-17:00 10.00 1.21 93888477.51 129.20 24-JAN-10:09 10.00 1.21
February 0.467750E+10 3971.19 15-FEB-17:00 16.70 5.85 86396718.66 126.83 17-FEB-10:00 7.20 4.72
March 0.115334E+11 6175.24 31-MAR-23:20 6.50 3.19 0.103236E+09 126.83 29-MAR-09:30 6.50 3.19
April 0.172076E+11 7764.10 16-APR-17:42 19.60 7.69 91606106.05 126.82 20-APR-09:00 12.20 5.87
May 0.366192E+10 3262.81 31-MAY-24:00 18.60 7.93 99234943.30 126.84 23-MAY-13:00 18.60 7.93
June 0.879585E+10 5175.89 30-JUN-24:00 22.10 13.89 98962310.71 126.85 08-JUN-13:00 22.10 13.89
July 0.141508E+11 6973.42 31-JUL-23:53 21.00 17.53 91887325.22 126.84 17-JUL-09:09 21.00 17.53
August 0.189069E+11 7723.61 13-AUG-19:23 26.95 17.61 0.103288E+09 126.91 17-AUG-13:00 33.90 18.07
September 0.383152E+10 3278.72 30-SEP-24:00 17.40 10.77 91612131.59 126.85 01-SEP-13:00 17.40 10.77
October 0.758988E+10 4553.32 31-OCT-23:40 13.33 4.91 95233251.71 126.84 11-OCT-09:00 13.33 4.91
November 0.102756E+11 5660.62 02-NOV-16:40 16.30 9.65 94300873.40 126.83 02-NOV-09:00 16.30 9.65
December 0.141788E+11 7147.55 29-DEC-16:50 10.28 3.14 91880808.96 126.82 08-DEC-14:09 10.28 3.14
                     
Annual Sum or Average 0.115298E+12         0.114153E+10        
Minimum of Months 0.488023E+09 1825.53   6.50 1.21 86396718.66 126.82   6.50 1.21
Maximum of Months 0.189069E+11 7764.10   26.95 17.61 0.103288E+09 129.20   33.90 18.07



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.237387E+12 91564.98 02-JAN-17:00 11.10 4.18 0.206144E+10 2745.29 03-JAN-10:09 7.07 2.12
February 0.435056E+12 182867.59 15-FEB-17:00 16.70 5.85 0.187022E+10 2745.29 24-FEB-14:30 8.60 2.09
March 0.728249E+12 358508.74 31-MAR-24:00 6.90 3.36 0.223475E+10 2745.29 27-MAR-13:30 6.90 3.36
April 0.942450E+12 366453.85 26-APR-16:00 25.00 9.93 0.198297E+10 2745.29 26-APR-09:39 25.00 9.93
May 0.240189E+12 175775.06 31-MAY-24:00 18.60 7.93 0.214810E+10 2745.29 01-MAY-13:09 18.60 7.93
June 0.469714E+12 267520.94 30-JUN-24:00 22.10 13.89 0.214213E+10 2745.29 23-JUN-13:09 22.10 13.89
July 0.731863E+12 359978.96 31-JUL-23:55 21.00 17.53 0.198894E+10 2745.29 19-JUL-13:09 21.00 17.53
August 0.977667E+12 368004.50 21-AUG-16:00 32.80 16.79 0.223475E+10 2745.29 02-AUG-09:30 32.80 16.79
September 0.235734E+12 176457.17 30-SEP-24:00 17.40 10.77 0.198297E+10 2745.29 08-SEP-13:09 17.40 10.77
October 0.487389E+12 268399.23 31-OCT-24:00 13.00 4.55 0.206144E+10 2745.29 10-OCT-13:30 13.00 4.55
November 0.707892E+12 275800.37 24-NOV-17:00 13.90 4.33 0.204131E+10 2745.29 20-NOV-10:39 13.90 4.33
December 0.975737E+12 367096.89 26-DEC-17:00 6.70 3.21 0.198894E+10 2745.29 13-DEC-10:30 6.70 3.21
                     
Annual Sum or Average 0.716933E+13         0.247380E+11        
Minimum of Months 0.235734E+12 91564.98   6.70 3.21 0.187022E+10 2745.29   6.70 2.09
Maximum of Months 0.977667E+12 368004.50   32.80 17.53 0.223475E+10 2745.29   32.80 17.53



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.207132E+09 11643.37 17-JAN-04:07 -3.3
February 0.165915E+09 11644.74 27-FEB-04:04 1.20
March 0.144147E+09 11728.76 13-MAR-03:05 1.20
April 0.232122E+09 11599.91 08-APR-04:05 2.80
May 0.356687E+09 11646.89 08-MAY-03:05 11.78
June 0.423999E+09 16157.95 17-JUN-16:02 33.43
July 0.538886E+09 19667.11 22-JUL-15:02 38.03
August 0.485652E+09 15088.54 05-AUG-15:02 32.62
September 0.493540E+09 14259.60 02-SEP-15:02 31.60
October 0.413269E+09 12944.72 01-OCT-19:53 21.10
November 0.349672E+09 13141.79 12-NOV-17:03 8.80
December 0.253913E+09 12729.99 25-DEC-16:43 3.98
         
Annual Sum or Average 0.406493E+10      
Minimum of Months 0.144147E+09 11599.91   -3.3
Maximum of Months 0.538886E+09 19667.11   38.03



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 2.30
February 0.00 0.00 01-FEB-00:10 -3.2
March 0.00 0.00 01-MAR-00:10 2.47
April 0.00 0.00 01-APR-00:10 7.00
May 0.00 0.00 01-MAY-00:03 14.45
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 0.00 0.00 01-OCT-00:10 17.33
November 0.00 0.00 01-NOV-00:10 12.83
December 0.00 0.00 01-DEC-00:10 5.13
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -3.2
Maximum of Months 0.00 0.00   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 2.30
February 0.00 0.00 01-FEB-00:10 -3.2
March 0.00 0.00 01-MAR-00:10 2.47
April 0.00 0.00 01-APR-00:10 7.00
May 0.00 0.00 01-MAY-00:03 14.45
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 0.00 0.00 01-OCT-00:10 17.33
November 0.00 0.00 01-NOV-00:10 12.83
December 0.00 0.00 01-DEC-00:10 5.13
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -3.2
Maximum of Months 0.00 0.00   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.172271E+10 67593.25 17-JAN-04:11 -3.3
February 0.708961E+09 66913.82 06-FEB-04:11 -4.4
March 33114367.17 58342.22 06-MAR-06:01 -2.9
April 0.00 0.00 01-APR-00:10 7.00
May 0.00 0.00 01-MAY-00:03 14.45
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 10653553.19 56326.00 26-OCT-05:03 -2.5
November 0.326368E+09 62485.95 27-NOV-05:01 -4.0
December 0.154344E+10 67217.86 26-DEC-04:01 0.32
         
Annual Sum or Average 0.434524E+10      
Minimum of Months 0.00 0.00   -4.4
Maximum of Months 0.172271E+10 67593.25   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1262126.59 2702.02 21-JAN-06:01 -6.5
February 0.00 0.00 01-FEB-00:10 -3.2
March 0.00 0.00 01-MAR-00:10 2.47
April 0.00 0.00 01-APR-00:10 7.00
May 0.00 0.00 01-MAY-00:03 14.45
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 0.00 0.00 01-OCT-00:10 17.33
November 0.00 0.00 01-NOV-00:10 12.83
December 0.00 0.00 01-DEC-00:10 5.13
         
Annual Sum or Average 1262126.59      
Minimum of Months 0.00 0.00   -6.5
Maximum of Months 1262126.59 2702.02   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 5723297.78 5180.84 21-JAN-06:01 -6.5
February 99840.59 499.34 07-FEB-06:02 -3.9
March 0.00 0.00 01-MAR-00:10 2.47
April 0.00 0.00 01-APR-00:10 7.00
May 0.00 0.00 01-MAY-00:03 14.45
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 0.00 0.00 01-OCT-00:10 17.33
November 0.00 0.00 01-NOV-00:10 12.83
December 536730.33 1831.08 22-DEC-06:01 -6.1
         
Annual Sum or Average 6359868.69      
Minimum of Months 0.00 0.00   -6.5
Maximum of Months 5723297.78 5180.84   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 21123725.00 9373.37 19-JAN-06:01 -3.2
February 5157955.27 8530.94 06-FEB-06:03 -4.6
March 0.00 0.00 01-MAR-00:10 2.47
April 0.00 0.00 01-APR-00:10 7.00
May 0.00 0.00 01-MAY-00:03 14.45
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 0.00 0.00 01-OCT-00:10 17.33
November 0.00 0.00 01-NOV-00:10 12.83
December 2723261.55 5323.48 22-DEC-06:01 -6.1
         
Annual Sum or Average 29004941.81      
Minimum of Months 0.00 0.00   -6.1
Maximum of Months 21123725.00 9373.37   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 2.30
February 0.00 0.00 01-FEB-00:10 -3.2
March 0.00 0.00 01-MAR-00:10 2.47
April 0.00 0.00 01-APR-00:10 7.00
May 0.00 0.00 01-MAY-00:03 14.45
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 0.00 0.00 01-OCT-00:10 17.33
November 0.00 0.00 01-NOV-00:10 12.83
December 0.00 0.00 01-DEC-00:10 5.13
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -3.2
Maximum of Months 0.00 0.00   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.914472E+09 10872.61 17-JAN-05:01 -3.3
February 0.489412E+09 10731.45 06-FEB-05:01 -4.4
March 41400520.27 9678.70 04-MAR-06:02 -1.7
April 0.00 0.00 01-APR-00:10 7.00
May 0.00 0.00 01-MAY-00:03 14.45
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 20641726.55 9546.25 26-OCT-05:03 -2.5
November 0.145132E+09 10292.18 27-NOV-05:01 -4.0
December 0.970715E+09 10506.40 26-DEC-05:02 -1.0
         
Annual Sum or Average 0.258177E+10      
Minimum of Months 0.00 0.00   -4.4
Maximum of Months 0.970715E+09 10872.61   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.419771E+09 12319.32 17-JAN-05:01 -3.3
February 0.178807E+09 12236.24 06-FEB-05:01 -4.4
March 7397846.89 10749.35 04-MAR-06:02 -1.7
April 0.00 0.00 01-APR-00:10 7.00
May 0.00 0.00 01-MAY-00:03 14.45
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 9774681.41 9337.28 26-OCT-05:03 -2.5
November 35608367.73 11149.20 27-NOV-05:01 -4.0
December 0.399030E+09 11778.31 26-DEC-05:02 -1.0
         
Annual Sum or Average 0.105039E+10      
Minimum of Months 0.00 0.00   -4.4
Maximum of Months 0.419771E+09 12319.32   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.211665E+09 12979.45 18-JAN-05:01 -2.3
February 86964927.44 12920.80 06-FEB-05:01 -4.4
March 4823729.13 11795.47 04-MAR-06:02 -1.7
April 0.00 0.00 01-APR-00:10 7.00
May 0.00 0.00 01-MAY-00:03 14.45
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 7129829.23 9398.44 26-OCT-05:03 -2.5
November 5273511.71 11867.20 27-NOV-06:01 -4.4
December 0.192240E+09 12677.13 26-DEC-05:02 -1.0
         
Annual Sum or Average 0.508097E+09      
Minimum of Months 0.00 0.00   -4.4
Maximum of Months 0.211665E+09 12979.45   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.233001E+09 11487.82 17-JAN-05:01 -3.3
February 0.109612E+09 11826.82 06-FEB-05:01 -4.4
March 4626944.11 7743.31 04-MAR-06:02 -1.7
April 0.00 0.00 01-APR-00:10 7.00
May 0.00 0.00 01-MAY-00:03 14.45
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 5244214.38 6158.16 26-OCT-05:03 -2.5
November 11290018.59 10560.94 27-NOV-06:01 -4.4
December 0.215412E+09 11145.97 22-DEC-05:01 -4.7
         
Annual Sum or Average 0.579185E+09      
Minimum of Months 0.00 0.00   -4.7
Maximum of Months 0.233001E+09 11826.82   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.390456E+10 14215.36 17-JAN-04:11 -3.3
February 0.241836E+10 14224.06 06-FEB-04:11 -4.4
March 0.732735E+09 12709.01 04-MAR-05:01 -1.2
April 73848406.14 11101.53 24-APR-05:03 6.20
May 4994791.90 6727.30 06-MAY-05:03 6.02
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 0.344807E+09 12487.30 26-OCT-04:01 -2.8
November 0.139224E+10 13953.18 27-NOV-04:01 -3.9
December 0.417008E+10 14018.77 18-DEC-04:01 -2.7
         
Annual Sum or Average 0.130416E+11      
Minimum of Months 0.00 0.00   -4.4
Maximum of Months 0.417008E+10 14224.06   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.172290E+10 16187.70 17-JAN-04:11 -3.3
February 0.950100E+09 16160.43 06-FEB-04:11 -4.4
March 0.235800E+09 14429.07 04-MAR-05:01 -1.2
April 12052141.90 7736.86 08-APR-05:03 2.62
May 361322.99 1043.63 06-MAY-05:03 6.02
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 0.143231E+09 14153.80 26-OCT-04:01 -2.8
November 0.475586E+09 15533.80 27-NOV-04:01 -3.9
December 0.170908E+10 15748.52 04-DEC-04:11 -0.2
         
Annual Sum or Average 0.524910E+10      
Minimum of Months 0.00 0.00   -4.4
Maximum of Months 0.172290E+10 16187.70   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.154631E+10 16929.38 17-JAN-04:11 -3.3
February 0.901050E+09 16850.38 06-FEB-04:11 -4.4
March 0.270780E+09 14922.87 04-MAR-05:01 -1.2
April 23334416.72 11556.48 08-APR-05:03 2.62
May 2841363.83 3865.56 05-MAY-05:03 5.68
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 0.142619E+09 14978.83 26-OCT-04:01 -2.8
November 0.282296E+09 14976.13 27-NOV-05:01 -4.0
December 0.145666E+10 16637.88 04-DEC-04:11 -0.2
         
Annual Sum or Average 0.462589E+10      
Minimum of Months 0.00 0.00   -4.4
Maximum of Months 0.154631E+10 16929.38   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.134122E+10 16741.98 17-JAN-04:11 -3.3
February 0.752901E+09 16791.42 06-FEB-04:11 -4.4
March 0.169070E+09 14362.49 04-MAR-05:01 -1.2
April 3625643.70 6425.37 08-APR-05:03 2.62
May 452908.07 1424.75 05-MAY-05:03 5.68
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 93696553.61 14495.86 26-OCT-04:01 -2.8
November 0.319565E+09 14680.18 28-NOV-05:01 -1.3
December 0.126705E+10 15966.30 26-DEC-04:01 0.32
         
Annual Sum or Average 0.394758E+10      
Minimum of Months 0.00 0.00   -4.4
Maximum of Months 0.134122E+10 16791.42   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.281188E+09 8307.02 09-JAN-06:01 -2.2
February 0.157708E+09 9123.69 07-FEB-06:01 -3.9
March 0.109290E+09 8970.18 06-MAR-05:01 -0.5
April 0.133507E+09 8610.25 03-APR-03:02 9.22
May 72638143.22 5938.79 22-MAY-03:02 18.22
June 67483417.15 6933.89 05-JUN-03:02 15.00
July 81376551.76 8639.84 02-JUL-16:11 31.83
August 69993841.46 8587.44 20-AUG-15:21 35.00
September 68086237.81 7429.01 03-SEP-13:41 32.52
October 0.101758E+09 8313.91 15-OCT-14:42 20.92
November 0.154414E+09 9302.15 27-NOV-04:01 -3.9
December 0.154020E+09 10864.52 11-DEC-04:01 2.12
         
Annual Sum or Average 0.145146E+10      
Minimum of Months 67483417.15 5938.79   -3.9
Maximum of Months 0.281188E+09 10864.52   35.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.148968E+10 6937.17 22-JAN-15:02 13.80
February 0.976131E+09 5545.44 19-FEB-13:42 15.92
March 0.224540E+09 8795.91 12-MAR-16:21 20.00
April 47726266.79 6005.36 30-APR-14:51 22.20
May 51244613.34 5428.83 07-MAY-16:02 24.40
June 46921433.29 7912.41 25-JUN-16:31 34.07
July 59872943.63 8320.71 04-JUL-15:31 35.60
August 45527851.16 7191.84 13-AUG-15:31 29.80
September 54248717.74 7161.49 03-SEP-13:41 32.52
October 0.121836E+09 7880.07 15-OCT-15:51 20.60
November 0.416278E+09 5450.52 05-NOV-14:42 12.70
December 0.136019E+10 6408.45 10-DEC-13:32 7.93
         
Annual Sum or Average 0.489420E+10      
Minimum of Months 45527851.16 5428.83   7.93
Maximum of Months 0.148968E+10 8795.91   35.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.568428E+10 19656.11 17-JAN-05:13 -3.3
February 0.374617E+10 20669.67 06-FEB-05:13 -4.4
March 0.207704E+10 10015.64 06-MAR-06:01 -2.9
April 0.788551E+09 12429.25 14-APR-05:02 8.58
May 0.398771E+09 13568.47 12-MAY-05:03 9.60
June 0.157933E+09 13253.13 20-JUN-05:02 12.77
July 71570976.69 9386.45 08-JUL-05:02 16.88
August 75057538.70 10178.34 29-AUG-05:02 15.60
September 0.201936E+09 11639.96 25-SEP-05:03 10.68
October 0.127608E+10 13344.89 12-OCT-05:03 6.70
November 0.264726E+10 16581.48 27-NOV-06:13 -4.4
December 0.588215E+10 18596.09 26-DEC-05:23 -0.9
         
Annual Sum or Average 0.230068E+11      
Minimum of Months 71570976.69 9386.45   -4.4
Maximum of Months 0.588215E+10 20669.67   16.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 2.30
February 0.00 0.00 01-FEB-00:10 -3.2
March 0.00 0.00 01-MAR-00:10 2.47
April 0.00 0.00 01-APR-00:10 7.00
May 0.00 0.00 01-MAY-00:03 14.45
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 0.00 0.00 01-OCT-00:10 17.33
November 0.00 0.00 01-NOV-00:10 12.83
December 0.00 0.00 01-DEC-00:10 5.13
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -3.2
Maximum of Months 0.00 0.00   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 12257781.81 202.72 17-JAN-05:17 -3.3
February 0.00 0.00 01-FEB-00:10 -3.2
March 0.00 0.00 01-MAR-00:10 2.47
April 0.00 0.00 01-APR-00:10 7.00
May 0.00 0.00 01-MAY-00:03 14.45
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 0.00 0.00 01-OCT-00:10 17.33
November 0.00 0.00 01-NOV-00:10 12.83
December 0.00 0.00 01-DEC-00:10 5.13
         
Annual Sum or Average 12257781.81      
Minimum of Months 0.00 0.00   -3.3
Maximum of Months 12257781.81 202.72   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.748106E+09 659.01 16-JAN-18:30 -1.4
February 3009020.85 432.21 06-FEB-00:25 -4.4
March 0.00 0.00 01-MAR-00:10 2.47
April 0.00 0.00 01-APR-00:10 7.00
May 0.00 0.00 01-MAY-00:03 14.45
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 0.00 0.00 01-OCT-00:10 17.33
November 0.00 0.00 01-NOV-00:10 12.83
December 0.00 0.00 01-DEC-00:10 5.13
         
Annual Sum or Average 0.751115E+09      
Minimum of Months 0.00 0.00   -4.4
Maximum of Months 0.748106E+09 659.01   21.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 2.30
February 0.00 0.00 01-FEB-00:10 -3.2
March 0.00 0.00 01-MAR-00:10 2.47
April 0.00 0.00 01-APR-00:10 7.00
May 0.00 0.00 01-MAY-00:03 14.45
June 0.00 0.00 01-JUN-00:10 18.42
July 0.00 0.00 01-JUL-00:10 21.95
August 0.00 0.00 01-AUG-00:03 20.95
September 0.00 0.00 01-SEP-00:05 21.88
October 0.00 0.00 01-OCT-00:10 17.33
November 0.00 0.00 01-NOV-00:10 12.83
December 0.00 0.00 01-DEC-00:10 5.13
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -3.2
Maximum of Months 0.00 0.00   21.95



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.113123E+11 11837.83 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.102611E+11 11837.83 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.121930E+11 11837.83 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.108909E+11 11837.83 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.117527E+11 11837.83 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.116958E+11 11837.83 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.109477E+11 11837.83 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.121930E+11 11837.83 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.108909E+11 11837.83 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.113123E+11 11837.83 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.111797E+11 11837.83 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.109477E+11 11837.83 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.135577E+12     0.424397E+12    
Minimum of Months 0.102611E+11 11837.83   0.325565E+11 13457.54  
Maximum of Months 0.121930E+11 11837.83   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101592E+11 10631.20 02-JAN-08:09 0.243681E+11 17206.63 02-JAN-08:09
February 0.921518E+10 10631.20 01-FEB-08:09 0.220609E+11 17206.63 01-FEB-08:09
March 0.109502E+11 10631.20 01-MAR-08:09 0.253549E+11 17206.63 01-MAR-08:09
April 0.978077E+10 10631.20 03-APR-07:10 0.235306E+11 17206.63 03-APR-07:10
May 0.105547E+11 10631.20 01-MAY-07:10 0.248615E+11 17206.63 01-MAY-07:10
June 0.105037E+11 10631.20 01-JUN-07:10 0.244160E+11 17206.63 01-JUN-07:10
July 0.983180E+10 10631.20 03-JUL-07:10 0.239708E+11 17206.63 03-JUL-07:10
August 0.109502E+11 10631.20 01-AUG-07:10 0.253549E+11 17206.63 01-AUG-07:10
September 0.978077E+10 10631.20 01-SEP-07:10 0.235199E+11 17206.63 01-SEP-07:10
October 0.101592E+11 10631.20 02-OCT-07:10 0.243735E+11 17206.63 02-OCT-07:10
November 0.100402E+11 10631.20 01-NOV-07:10 0.238373E+11 17206.63 01-NOV-07:10
December 0.983180E+10 10631.20 01-DEC-08:09 0.239654E+11 17206.63 01-DEC-08:09
             
Annual Sum or Average 0.121758E+12     0.289614E+12    
Minimum of Months 0.921518E+10 10631.20   0.220609E+11 17206.63  
Maximum of Months 0.109502E+11 10631.20   0.253549E+11 17206.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101592E+11 10631.20 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.921518E+10 10631.20 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.109502E+11 10631.20 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.978077E+10 10631.20 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.105547E+11 10631.20 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.105037E+11 10631.20 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.983180E+10 10631.20 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.109502E+11 10631.20 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.978077E+10 10631.20 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.101592E+11 10631.20 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.100402E+11 10631.20 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.983180E+10 10631.20 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.121758E+12     0.289613E+12    
Minimum of Months 0.921518E+10 10631.20   0.220609E+11 17206.56  
Maximum of Months 0.109502E+11 10631.20   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101592E+11 10631.20 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.921518E+10 10631.20 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.109502E+11 10631.20 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.978077E+10 10631.20 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.105547E+11 10631.20 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.105037E+11 10631.20 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.983180E+10 10631.20 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.109502E+11 10631.20 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.978077E+10 10631.20 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.101592E+11 10631.20 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.100402E+11 10631.20 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.983180E+10 10631.20 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.121758E+12     0.289613E+12    
Minimum of Months 0.921518E+10 10631.20   0.220609E+11 17206.56  
Maximum of Months 0.109502E+11 10631.20   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.808776E+09 1212.73 09-JAN-16:00 0.305979E+10 2160.55 02-JAN-08:09
February 0.701901E+09 1093.68 16-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.788097E+09 970.36 20-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.672585E+09 635.12 03-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.717825E+09 736.47 22-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.702811E+09 746.44 08-JUN-15:00 0.306580E+10 2160.55 01-JUN-07:10
July 0.665905E+09 743.11 07-JUL-15:00 0.300989E+10 2160.55 03-JUL-07:10
August 0.744266E+09 635.12 01-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.692412E+09 1075.38 08-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.759980E+09 1075.19 25-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.794888E+09 1334.85 13-NOV-16:00 0.299314E+10 2160.55 01-NOV-07:10
December 0.818851E+09 1334.85 01-DEC-16:00 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.886830E+10     0.363654E+11    
Minimum of Months 0.665905E+09 635.12   0.277008E+10 2160.55  
Maximum of Months 0.818851E+09 1334.85   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.510232E+09 781.36 09-JAN-16:00 0.197184E+10 1392.34 02-JAN-08:09
February 0.447236E+09 694.58 16-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.505175E+09 584.40 14-MAR-15:00 0.205169E+10 1392.34 01-MAR-08:09
April 0.435657E+09 409.30 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.466866E+09 465.02 22-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.457479E+09 481.61 08-JUN-15:00 0.197572E+10 1392.34 01-JUN-07:10
July 0.432369E+09 479.57 07-JUL-15:00 0.193969E+10 1392.34 03-JUL-07:10
August 0.481801E+09 409.30 01-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.444654E+09 684.85 08-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.479908E+09 658.34 25-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.508373E+09 860.23 13-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.517313E+09 860.23 01-DEC-16:00 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.568706E+10     0.234352E+11    
Minimum of Months 0.432369E+09 409.30   0.178515E+10 1392.34  
Maximum of Months 0.517313E+09 860.23   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.765716E+09 1148.40 04-JAN-16:00 0.305983E+10 2160.58 02-JAN-08:09
February 0.679488E+09 1084.12 16-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.778983E+09 951.46 20-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.675640E+09 635.14 03-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.724115E+09 738.78 22-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.712392E+09 746.65 08-JUN-15:00 0.306585E+10 2160.58 01-JUN-07:10
July 0.672557E+09 743.16 07-JUL-15:00 0.300994E+10 2160.58 03-JUL-07:10
August 0.748415E+09 669.18 17-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.689370E+09 1073.41 08-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.733087E+09 1053.17 25-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.762712E+09 1334.88 13-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.771220E+09 1334.88 01-DEC-16:00 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.871369E+10     0.363660E+11    
Minimum of Months 0.672557E+09 635.14   0.277013E+10 2160.58  
Maximum of Months 0.778983E+09 1334.88   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.503731E+09 724.09 04-JAN-16:00 0.197183E+10 1392.33 02-JAN-08:09
February 0.442996E+09 706.67 16-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.503953E+09 665.69 22-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.433110E+09 437.97 05-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.461926E+09 479.93 22-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.454952E+09 585.53 08-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.430787E+09 476.33 07-JUL-15:00 0.193968E+10 1392.33 03-JUL-07:10
August 0.480812E+09 453.16 28-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.444368E+09 696.51 08-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.481613E+09 704.16 25-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.494364E+09 860.23 13-NOV-16:00 0.192888E+10 1392.33 01-NOV-07:10
December 0.506146E+09 860.23 01-DEC-16:00 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.563876E+10     0.234351E+11    
Minimum of Months 0.430787E+09 437.97   0.178514E+10 1392.33  
Maximum of Months 0.506146E+09 860.23   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.809119E+09 1216.43 09-JAN-16:00 0.305979E+10 2160.55 02-JAN-08:09
February 0.702064E+09 1098.94 16-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.788178E+09 978.36 20-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.672625E+09 635.12 03-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.717699E+09 734.31 22-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.703004E+09 825.95 08-JUN-15:00 0.306580E+10 2160.55 01-JUN-07:10
July 0.665953E+09 741.01 07-JUL-15:00 0.300989E+10 2160.55 03-JUL-07:10
August 0.744174E+09 635.12 01-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.692399E+09 1081.07 08-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.759807E+09 1080.83 25-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.795215E+09 1334.85 13-NOV-16:00 0.299314E+10 2160.55 01-NOV-07:10
December 0.819208E+09 1334.85 01-DEC-16:00 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.886944E+10     0.363654E+11    
Minimum of Months 0.665953E+09 635.12   0.277008E+10 2160.55  
Maximum of Months 0.819208E+09 1334.85   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.510106E+09 782.91 09-JAN-16:00 0.197184E+10 1392.34 02-JAN-08:09
February 0.447148E+09 695.20 16-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.505112E+09 584.77 14-MAR-15:00 0.205169E+10 1392.34 01-MAR-08:09
April 0.435623E+09 409.30 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.466725E+09 463.35 22-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.457439E+09 532.06 08-JUN-15:00 0.197572E+10 1392.34 01-JUN-07:10
July 0.432367E+09 478.08 07-JUL-15:00 0.193969E+10 1392.34 03-JUL-07:10
August 0.481771E+09 409.30 01-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.444610E+09 685.55 08-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.479689E+09 659.76 25-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.508259E+09 860.23 13-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.517117E+09 860.23 01-DEC-16:00 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.568597E+10     0.234352E+11    
Minimum of Months 0.432367E+09 409.30   0.178515E+10 1392.34  
Maximum of Months 0.517117E+09 860.23   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.766013E+09 1153.46 04-JAN-16:00 0.305983E+10 2160.58 02-JAN-08:09
February 0.679337E+09 1089.72 16-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.779154E+09 960.10 20-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.675803E+09 635.14 03-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.724095E+09 736.65 22-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.712668E+09 827.41 08-JUN-15:00 0.306585E+10 2160.58 01-JUN-07:10
July 0.672740E+09 741.07 07-JUL-15:00 0.300994E+10 2160.58 03-JUL-07:10
August 0.748547E+09 664.35 17-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.689476E+09 1079.16 08-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.731966E+09 1059.57 25-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.763142E+09 1334.88 13-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.772134E+09 1334.88 01-DEC-16:00 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.871507E+10     0.363660E+11    
Minimum of Months 0.672740E+09 635.14   0.277013E+10 2160.58  
Maximum of Months 0.779154E+09 1334.88   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.503532E+09 725.70 04-JAN-16:00 0.197183E+10 1392.33 02-JAN-08:09
February 0.443033E+09 707.02 16-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.503861E+09 665.94 22-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.433138E+09 435.39 05-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.461890E+09 478.45 22-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.454860E+09 585.82 08-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.430736E+09 474.80 07-JUL-15:00 0.193968E+10 1392.33 03-JUL-07:10
August 0.480841E+09 450.73 28-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.444252E+09 696.87 08-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.481316E+09 704.51 25-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.494384E+09 860.23 13-NOV-16:00 0.192888E+10 1392.33 01-NOV-07:10
December 0.505911E+09 860.23 01-DEC-16:00 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.563775E+10     0.234351E+11    
Minimum of Months 0.430736E+09 435.39   0.178514E+10 1392.33  
Maximum of Months 0.505911E+09 860.23   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.809121E+09 1216.53 09-JAN-16:00 0.305979E+10 2160.55 02-JAN-08:09
February 0.702010E+09 1098.66 16-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.788187E+09 977.99 20-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.672623E+09 635.12 03-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.717681E+09 734.15 22-MAY-07:10 0.312174E+10 2160.55 01-MAY-07:10
June 0.702998E+09 825.32 08-JUN-15:00 0.306580E+10 2160.55 01-JUN-07:10
July 0.665946E+09 740.86 07-JUL-15:00 0.300989E+10 2160.55 03-JUL-07:10
August 0.744164E+09 635.12 01-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.692395E+09 1080.76 08-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.759812E+09 1080.55 25-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.795209E+09 1334.85 13-NOV-16:00 0.299314E+10 2160.55 01-NOV-07:10
December 0.819222E+09 1334.85 01-DEC-16:00 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.886937E+10     0.363654E+11    
Minimum of Months 0.665946E+09 635.12   0.277008E+10 2160.55  
Maximum of Months 0.819222E+09 1334.85   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.510113E+09 782.99 09-JAN-16:00 0.197184E+10 1392.34 02-JAN-08:09
February 0.447151E+09 695.02 16-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.505096E+09 584.51 14-MAR-15:00 0.205169E+10 1392.34 01-MAR-08:09
April 0.435623E+09 409.30 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.466719E+09 463.23 22-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.457436E+09 531.68 08-JUN-15:00 0.197572E+10 1392.34 01-JUN-07:10
July 0.432360E+09 477.99 07-JUL-15:00 0.193969E+10 1392.34 03-JUL-07:10
August 0.481780E+09 409.30 01-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.444601E+09 685.36 08-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.479696E+09 659.61 25-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.508271E+09 860.23 13-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.517155E+09 860.23 01-DEC-16:00 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.568600E+10     0.234352E+11    
Minimum of Months 0.432360E+09 409.30   0.178515E+10 1392.34  
Maximum of Months 0.517155E+09 860.23   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.766016E+09 1153.36 04-JAN-16:00 0.305983E+10 2160.58 02-JAN-08:09
February 0.679330E+09 1089.44 16-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.779142E+09 959.73 20-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.675800E+09 635.14 03-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.724087E+09 736.49 22-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.712662E+09 826.78 08-JUN-15:00 0.306585E+10 2160.58 01-JUN-07:10
July 0.672732E+09 740.91 07-JUL-15:00 0.300994E+10 2160.58 03-JUL-07:10
August 0.748543E+09 664.27 17-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.689451E+09 1078.86 08-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.731960E+09 1059.29 25-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.763143E+09 1334.88 13-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.772141E+09 1334.88 01-DEC-16:00 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.871501E+10     0.363660E+11    
Minimum of Months 0.672732E+09 635.14   0.277013E+10 2160.58  
Maximum of Months 0.779142E+09 1334.88   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.503528E+09 725.65 04-JAN-16:00 0.197183E+10 1392.33 02-JAN-08:09
February 0.443032E+09 706.84 16-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.503857E+09 665.81 22-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.433140E+09 435.28 05-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.461890E+09 478.35 22-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.454859E+09 585.57 08-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.430729E+09 474.70 07-JUL-15:00 0.193968E+10 1392.33 03-JUL-07:10
August 0.480842E+09 450.61 28-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.444283E+09 696.68 08-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.481322E+09 704.35 25-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.494389E+09 860.23 13-NOV-16:00 0.192888E+10 1392.33 01-NOV-07:10
December 0.505918E+09 860.23 01-DEC-16:00 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.563779E+10     0.234351E+11    
Minimum of Months 0.430729E+09 435.28   0.178514E+10 1392.33  
Maximum of Months 0.505918E+09 860.23   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272315E+09 284.97 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.247010E+09 284.97 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.293517E+09 284.97 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.262171E+09 284.97 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.282916E+09 284.97 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.281548E+09 284.97 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.263538E+09 284.97 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.293517E+09 284.97 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.262171E+09 284.97 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.272315E+09 284.97 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.269124E+09 284.97 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.263538E+09 284.97 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.326368E+10     0.153881E+12    
Minimum of Months 0.247010E+09 284.97   0.505780E+10 1948.61  
Maximum of Months 0.293517E+09 284.97   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272315E+09 284.97 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.247010E+09 284.97 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.293517E+09 284.97 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.262171E+09 284.97 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.282916E+09 284.97 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.281548E+09 284.97 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.263538E+09 284.97 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.293517E+09 284.97 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.262171E+09 284.97 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.272315E+09 284.97 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.269124E+09 284.97 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.263538E+09 284.97 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.326368E+10     0.153881E+12    
Minimum of Months 0.247010E+09 284.97   0.505780E+10 1948.61  
Maximum of Months 0.293517E+09 284.97   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272315E+09 284.97 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.247010E+09 284.97 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.293517E+09 284.97 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.262171E+09 284.97 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.282916E+09 284.97 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.281548E+09 284.97 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.263538E+09 284.97 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.293517E+09 284.97 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.262171E+09 284.97 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.272315E+09 284.97 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.269124E+09 284.97 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.263538E+09 284.97 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.326368E+10     0.153881E+12    
Minimum of Months 0.247010E+09 284.97   0.505780E+10 1948.61  
Maximum of Months 0.293517E+09 284.97   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.318958E+10 3337.76 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.289319E+10 3337.76 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.343791E+10 3337.76 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.307076E+10 3337.76 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.331375E+10 3337.76 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.329773E+10 3337.76 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.308678E+10 3337.76 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.343791E+10 3337.76 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.307076E+10 3337.76 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.318958E+10 3337.76 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.315220E+10 3337.76 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.308678E+10 3337.76 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.382269E+11     0.749486E+13    
Minimum of Months 0.289319E+10 3337.76   0.246344E+12 94908.13  
Maximum of Months 0.343791E+10 3337.76   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.113123E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.102611E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.121930E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.108909E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.117527E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.116958E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.109477E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.121930E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.108909E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.113123E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.111797E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.109477E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.135577E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.102611E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.121930E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.101592E+11 0.243681E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.109502E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.978077E+10 0.235306E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.105547E+11 0.248615E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.105037E+11 0.244160E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.983180E+10 0.239708E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.109502E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.978077E+10 0.235199E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.101592E+11 0.243735E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.100402E+11 0.238373E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.983180E+10 0.239654E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.121758E+12 0.289614E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.109502E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.101592E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.978077E+10 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.105547E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.105037E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.983180E+10 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.978077E+10 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.101592E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.100402E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.983180E+10 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.121758E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.101592E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.978077E+10 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.105547E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.105037E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.983180E+10 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.978077E+10 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.101592E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.100402E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.983180E+10 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.121758E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.808776E+09 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.176378E+09
February 0.136985E+10 0.701901E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.163721E+09
March 0.163685E+10 0.788097E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.161152E+09
April 0.145243E+10 0.672585E+09 0.295462E+10 0.00 0.00 0.00 0.00 255951.58 0.113971E+09
May 0.157338E+10 0.717825E+09 0.312174E+10 0.00 0.00 0.00 0.00 2712530.76 77581739.22
June 0.156900E+10 0.702811E+09 0.306580E+10 0.00 0.00 0.00 0.00 12832692.84 40152917.32
July 0.145680E+10 0.665905E+09 0.300989E+10 0.00 0.00 0.00 0.00 18318219.64 20381498.56
August 0.163685E+10 0.744266E+09 0.318369E+10 0.00 0.00 0.00 0.00 9249249.82 27573922.65
September 0.145243E+10 0.692412E+09 0.295328E+10 0.00 0.00 0.00 0.00 3145734.47 46262260.39
October 0.150991E+10 0.759980E+09 0.306046E+10 0.00 0.00 0.00 0.00 758924.64 86986895.04
November 0.149516E+10 0.794888E+09 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.143182E+09
December 0.145680E+10 0.818851E+09 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.164976E+09
                   
Annual Sum or Average 0.181194E+11 0.886830E+10 0.363654E+11 0.00 0.00 0.00 0.00 47273303.75 0.122232E+10
Minimum of Months 0.136985E+10 0.665905E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 20381498.56
Maximum of Months 0.163685E+10 0.818851E+09 0.318369E+10 0.00 0.00 0.00 0.00 18318219.64 0.176378E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.510232E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.118931E+09
February 0.882782E+09 0.447236E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.109603E+09
March 0.105485E+10 0.505175E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.107093E+09
April 0.936002E+09 0.435657E+09 0.190407E+10 0.00 0.00 0.00 0.00 175577.21 75861733.21
May 0.101394E+10 0.466866E+09 0.201177E+10 0.00 0.00 0.00 0.00 1717337.65 52735426.10
June 0.101113E+10 0.457479E+09 0.197572E+10 0.00 0.00 0.00 0.00 8794787.35 25761309.62
July 0.938820E+09 0.432369E+09 0.193969E+10 0.00 0.00 0.00 0.00 12574177.79 12344491.70
August 0.105485E+10 0.481801E+09 0.205169E+10 0.00 0.00 0.00 0.00 6373538.74 16524987.41
September 0.936002E+09 0.444654E+09 0.190321E+10 0.00 0.00 0.00 0.00 2062717.98 31018545.23
October 0.973041E+09 0.479908E+09 0.197228E+10 0.00 0.00 0.00 0.00 491699.21 58436108.52
November 0.963541E+09 0.508373E+09 0.192889E+10 0.00 0.00 0.00 0.00 0.00 95348288.29
December 0.938820E+09 0.517313E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.108879E+09
                   
Annual Sum or Average 0.116768E+11 0.568706E+10 0.234352E+11 0.00 0.00 0.00 0.00 32189835.94 0.812537E+09
Minimum of Months 0.882782E+09 0.432369E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 12344491.70
Maximum of Months 0.105485E+10 0.517313E+09 0.205169E+10 0.00 0.00 0.00 0.00 12574177.79 0.118931E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.765716E+09 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.183577E+09
February 0.136988E+10 0.679488E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.170363E+09
March 0.163688E+10 0.778983E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.164914E+09
April 0.145246E+10 0.675640E+09 0.295467E+10 0.00 0.00 0.00 0.00 248204.08 0.116825E+09
May 0.157341E+10 0.724115E+09 0.312179E+10 0.00 0.00 0.00 0.00 2440712.46 78050247.35
June 0.156904E+10 0.712392E+09 0.306585E+10 0.00 0.00 0.00 0.00 12955137.93 39390722.00
July 0.145684E+10 0.672557E+09 0.300994E+10 0.00 0.00 0.00 0.00 17985687.85 20496632.01
August 0.163688E+10 0.748415E+09 0.318374E+10 0.00 0.00 0.00 0.00 8873686.55 28951825.74
September 0.145246E+10 0.689370E+09 0.295333E+10 0.00 0.00 0.00 0.00 2783071.23 49705883.93
October 0.150994E+10 0.733087E+09 0.306051E+10 0.00 0.00 0.00 0.00 625207.52 92725163.26
November 0.149520E+10 0.762712E+09 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.150673E+09
December 0.145684E+10 0.771220E+09 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.171272E+09
                   
Annual Sum or Average 0.181198E+11 0.871369E+10 0.363660E+11 0.00 0.00 0.00 0.00 45911707.62 0.126694E+10
Minimum of Months 0.136988E+10 0.672557E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 20496632.01
Maximum of Months 0.163688E+10 0.778983E+09 0.318374E+10 0.00 0.00 0.00 0.00 17985687.85 0.183577E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.503731E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.124666E+09
February 0.882782E+09 0.442996E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.118412E+09
March 0.105485E+10 0.503953E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.118855E+09
April 0.936002E+09 0.433110E+09 0.190406E+10 0.00 0.00 0.00 0.00 165382.21 87255750.01
May 0.101394E+10 0.461926E+09 0.201175E+10 0.00 0.00 0.00 0.00 1489221.43 57261098.48
June 0.101113E+10 0.454952E+09 0.197570E+10 0.00 0.00 0.00 0.00 7839449.36 30594546.78
July 0.938820E+09 0.430787E+09 0.193968E+10 0.00 0.00 0.00 0.00 11120719.48 16804648.22
August 0.105485E+10 0.480812E+09 0.205168E+10 0.00 0.00 0.00 0.00 5669169.39 23012513.79
September 0.936002E+09 0.444368E+09 0.190319E+10 0.00 0.00 0.00 0.00 1936969.78 35026339.42
October 0.973041E+09 0.481613E+09 0.197226E+10 0.00 0.00 0.00 0.00 456067.70 64703486.66
November 0.963541E+09 0.494364E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.105866E+09
December 0.938820E+09 0.506146E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.123050E+09
                   
Annual Sum or Average 0.116768E+11 0.563876E+10 0.234351E+11 0.00 0.00 0.00 0.00 28676979.35 0.905508E+09
Minimum of Months 0.882782E+09 0.430787E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 16804648.22
Maximum of Months 0.105485E+10 0.506146E+09 0.205168E+10 0.00 0.00 0.00 0.00 11120719.48 0.124666E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.809119E+09 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.366012E+09
February 0.136985E+10 0.702064E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.341967E+09
March 0.163685E+10 0.788178E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.340562E+09
April 0.145243E+10 0.672625E+09 0.295462E+10 0.00 0.00 0.00 0.00 670707.66 0.249102E+09
May 0.157338E+10 0.717699E+09 0.312174E+10 0.00 0.00 0.00 0.00 6774508.59 0.173807E+09
June 0.156900E+10 0.703004E+09 0.306580E+10 0.00 0.00 0.00 0.00 29649240.17 94147010.79
July 0.145680E+10 0.665953E+09 0.300989E+10 0.00 0.00 0.00 0.00 42702315.29 53140848.32
August 0.163685E+10 0.744174E+09 0.318369E+10 0.00 0.00 0.00 0.00 22130413.55 70202970.85
September 0.145243E+10 0.692399E+09 0.295328E+10 0.00 0.00 0.00 0.00 7494018.96 0.103454E+09
October 0.150991E+10 0.759807E+09 0.306046E+10 0.00 0.00 0.00 0.00 1803105.83 0.185359E+09
November 0.149516E+10 0.795215E+09 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.295174E+09
December 0.145680E+10 0.819208E+09 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.333741E+09
                   
Annual Sum or Average 0.181194E+11 0.886944E+10 0.363654E+11 0.00 0.00 0.00 0.00 0.111224E+09 0.260667E+10
Minimum of Months 0.136985E+10 0.665953E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 53140848.32
Maximum of Months 0.163685E+10 0.819208E+09 0.318369E+10 0.00 0.00 0.00 0.00 42702315.29 0.366012E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.510106E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.252817E+09
February 0.649041E+09 0.447148E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.236366E+09
March 0.773965E+09 0.505112E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.237374E+09
April 0.688021E+09 0.435623E+09 0.190407E+10 0.00 0.00 0.00 0.00 376592.14 0.179299E+09
May 0.744847E+09 0.466725E+09 0.201177E+10 0.00 0.00 0.00 0.00 3716521.88 0.122803E+09
June 0.742030E+09 0.457439E+09 0.197572E+10 0.00 0.00 0.00 0.00 19544658.84 63983639.53
July 0.690839E+09 0.432367E+09 0.193969E+10 0.00 0.00 0.00 0.00 27627325.33 37903205.62
August 0.773965E+09 0.481771E+09 0.205169E+10 0.00 0.00 0.00 0.00 14167994.73 49921281.23
September 0.688021E+09 0.444610E+09 0.190321E+10 0.00 0.00 0.00 0.00 4632572.15 72731463.25
October 0.715730E+09 0.479689E+09 0.197228E+10 0.00 0.00 0.00 0.00 1080515.77 0.131396E+09
November 0.708685E+09 0.508259E+09 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.205929E+09
December 0.690839E+09 0.517117E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.229275E+09
                   
Annual Sum or Average 0.858171E+10 0.568597E+10 0.234352E+11 0.00 0.00 0.00 0.00 71146180.84 0.181980E+10
Minimum of Months 0.649041E+09 0.432367E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 37903205.62
Maximum of Months 0.773965E+09 0.517117E+09 0.205169E+10 0.00 0.00 0.00 0.00 27627325.33 0.252817E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.766013E+09 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.418869E+09
February 0.136988E+10 0.679337E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.389102E+09
March 0.163688E+10 0.779154E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.374816E+09
April 0.145246E+10 0.675803E+09 0.295467E+10 0.00 0.00 0.00 0.00 508678.62 0.269106E+09
May 0.157341E+10 0.724095E+09 0.312179E+10 0.00 0.00 0.00 0.00 5366859.93 0.179428E+09
June 0.156904E+10 0.712668E+09 0.306585E+10 0.00 0.00 0.00 0.00 29766932.77 93265749.55
July 0.145684E+10 0.672740E+09 0.300994E+10 0.00 0.00 0.00 0.00 41180318.64 54345554.58
August 0.163688E+10 0.748547E+09 0.318374E+10 0.00 0.00 0.00 0.00 20322049.60 75917045.81
September 0.145246E+10 0.689476E+09 0.295333E+10 0.00 0.00 0.00 0.00 6025237.41 0.116980E+09
October 0.150994E+10 0.731966E+09 0.306051E+10 0.00 0.00 0.00 0.00 1216738.00 0.215215E+09
November 0.149520E+10 0.763142E+09 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.343927E+09
December 0.145684E+10 0.772134E+09 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.384484E+09
                   
Annual Sum or Average 0.181198E+11 0.871507E+10 0.363660E+11 0.00 0.00 0.00 0.00 0.104387E+09 0.291545E+10
Minimum of Months 0.136988E+10 0.672740E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 54345554.58
Maximum of Months 0.163688E+10 0.779154E+09 0.318374E+10 0.00 0.00 0.00 0.00 41180318.64 0.418869E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.503532E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.260416E+09
February 0.882782E+09 0.443033E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.245077E+09
March 0.105485E+10 0.503861E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.245024E+09
April 0.936002E+09 0.433138E+09 0.190406E+10 0.00 0.00 0.00 0.00 340610.33 0.185383E+09
May 0.101394E+10 0.461890E+09 0.201175E+10 0.00 0.00 0.00 0.00 3395247.99 0.126789E+09
June 0.101113E+10 0.454860E+09 0.197570E+10 0.00 0.00 0.00 0.00 18249069.55 69231252.84
July 0.938820E+09 0.430736E+09 0.193968E+10 0.00 0.00 0.00 0.00 26704467.68 40484247.32
August 0.105485E+10 0.480841E+09 0.205168E+10 0.00 0.00 0.00 0.00 13506029.80 54140086.73
September 0.936002E+09 0.444252E+09 0.190319E+10 0.00 0.00 0.00 0.00 4436470.92 77573116.30
October 0.973041E+09 0.481316E+09 0.197226E+10 0.00 0.00 0.00 0.00 1035091.63 0.136161E+09
November 0.963541E+09 0.494384E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.212718E+09
December 0.938820E+09 0.505911E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.238854E+09
                   
Annual Sum or Average 0.116768E+11 0.563775E+10 0.234351E+11 0.00 0.00 0.00 0.00 67666987.89 0.189185E+10
Minimum of Months 0.882782E+09 0.430736E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 40484247.32
Maximum of Months 0.105485E+10 0.505911E+09 0.205168E+10 0.00 0.00 0.00 0.00 26704467.68 0.260416E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.809121E+09 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.411276E+09
February 0.136985E+10 0.702010E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.390331E+09
March 0.163685E+10 0.788187E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.389426E+09
April 0.145243E+10 0.672623E+09 0.295462E+10 0.00 0.00 0.00 0.00 748533.02 0.294647E+09
May 0.157338E+10 0.717681E+09 0.312174E+10 0.00 0.00 0.00 0.00 7166759.53 0.210380E+09
June 0.156900E+10 0.702998E+09 0.306580E+10 0.00 0.00 0.00 0.00 34624001.43 0.116836E+09
July 0.145680E+10 0.665946E+09 0.300989E+10 0.00 0.00 0.00 0.00 49549143.36 68763118.24
August 0.163685E+10 0.744164E+09 0.318369E+10 0.00 0.00 0.00 0.00 25205787.07 89403139.70
September 0.145243E+10 0.692395E+09 0.295328E+10 0.00 0.00 0.00 0.00 8637035.46 0.126752E+09
October 0.150991E+10 0.759812E+09 0.306046E+10 0.00 0.00 0.00 0.00 2072154.80 0.214263E+09
November 0.149516E+10 0.795209E+09 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.328196E+09
December 0.145680E+10 0.819222E+09 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.373746E+09
                   
Annual Sum or Average 0.181194E+11 0.886937E+10 0.363654E+11 0.00 0.00 0.00 0.00 0.128003E+09 0.301402E+10
Minimum of Months 0.136985E+10 0.665946E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 68763118.24
Maximum of Months 0.163685E+10 0.819222E+09 0.318369E+10 0.00 0.00 0.00 0.00 49549143.36 0.411276E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.510113E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.284735E+09
February 0.882782E+09 0.447151E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.270722E+09
March 0.105485E+10 0.505096E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.275997E+09
April 0.936002E+09 0.435623E+09 0.190407E+10 0.00 0.00 0.00 0.00 385308.16 0.216998E+09
May 0.101394E+10 0.466719E+09 0.201177E+10 0.00 0.00 0.00 0.00 4114552.66 0.150840E+09
June 0.101113E+10 0.457436E+09 0.197572E+10 0.00 0.00 0.00 0.00 22975106.70 79774960.16
July 0.938820E+09 0.432360E+09 0.193969E+10 0.00 0.00 0.00 0.00 32570544.86 48829157.47
August 0.105485E+10 0.481780E+09 0.205169E+10 0.00 0.00 0.00 0.00 16501228.14 63592253.11
September 0.936002E+09 0.444601E+09 0.190321E+10 0.00 0.00 0.00 0.00 5415992.13 89905177.84
October 0.973041E+09 0.479696E+09 0.197228E+10 0.00 0.00 0.00 0.00 1221010.25 0.155161E+09
November 0.963541E+09 0.508271E+09 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.231589E+09
December 0.938820E+09 0.517155E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.257500E+09
                   
Annual Sum or Average 0.116768E+11 0.568600E+10 0.234352E+11 0.00 0.00 0.00 0.00 83183742.90 0.212564E+10
Minimum of Months 0.882782E+09 0.432360E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 48829157.47
Maximum of Months 0.105485E+10 0.517155E+09 0.205169E+10 0.00 0.00 0.00 0.00 32570544.86 0.284735E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.766016E+09 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.475776E+09
February 0.136988E+10 0.679330E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.448652E+09
March 0.163688E+10 0.779142E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.436741E+09
April 0.145246E+10 0.675800E+09 0.295467E+10 0.00 0.00 0.00 0.00 545241.06 0.321381E+09
May 0.157341E+10 0.724087E+09 0.312179E+10 0.00 0.00 0.00 0.00 6078375.93 0.217187E+09
June 0.156904E+10 0.712662E+09 0.306585E+10 0.00 0.00 0.00 0.00 35233812.99 0.114832E+09
July 0.145684E+10 0.672732E+09 0.300994E+10 0.00 0.00 0.00 0.00 48911857.48 69546871.47
August 0.163688E+10 0.748543E+09 0.318374E+10 0.00 0.00 0.00 0.00 24090824.43 96110810.91
September 0.145246E+10 0.689451E+09 0.295333E+10 0.00 0.00 0.00 0.00 7302837.14 0.143856E+09
October 0.150994E+10 0.731960E+09 0.306051E+10 0.00 0.00 0.00 0.00 1580628.16 0.254975E+09
November 0.149520E+10 0.763143E+09 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.393836E+09
December 0.145684E+10 0.772141E+09 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.437178E+09
                   
Annual Sum or Average 0.181198E+11 0.871501E+10 0.363660E+11 0.00 0.00 0.00 0.00 0.123744E+09 0.341007E+10
Minimum of Months 0.136988E+10 0.672732E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 69546871.47
Maximum of Months 0.163688E+10 0.779142E+09 0.318374E+10 0.00 0.00 0.00 0.00 48911857.48 0.475776E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.503528E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.297148E+09
February 0.882782E+09 0.443032E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.284275E+09
March 0.105485E+10 0.503857E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.286472E+09
April 0.936002E+09 0.433140E+09 0.190406E+10 0.00 0.00 0.00 0.00 365824.87 0.222850E+09
May 0.101394E+10 0.461890E+09 0.201175E+10 0.00 0.00 0.00 0.00 3974273.06 0.153933E+09
June 0.101113E+10 0.454859E+09 0.197570E+10 0.00 0.00 0.00 0.00 22133465.49 85389107.75
July 0.938820E+09 0.430729E+09 0.193968E+10 0.00 0.00 0.00 0.00 32064656.78 51071828.84
August 0.105485E+10 0.480842E+09 0.205168E+10 0.00 0.00 0.00 0.00 16133034.21 67992900.67
September 0.936002E+09 0.444283E+09 0.190319E+10 0.00 0.00 0.00 0.00 5325851.67 95242199.19
October 0.973041E+09 0.481322E+09 0.197226E+10 0.00 0.00 0.00 0.00 1212079.58 0.161268E+09
November 0.963541E+09 0.494389E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.243122E+09
December 0.938820E+09 0.505918E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.273112E+09
                   
Annual Sum or Average 0.116768E+11 0.563779E+10 0.234351E+11 0.00 0.00 0.00 0.00 81209185.66 0.222188E+10
Minimum of Months 0.882782E+09 0.430729E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 51071828.84
Maximum of Months 0.105485E+10 0.505918E+09 0.205168E+10 0.00 0.00 0.00 0.00 32064656.78 0.297148E+09



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.272315E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.247010E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.293517E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.262171E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.282916E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.281548E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.263538E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.293517E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.262171E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.272315E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.269124E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.263538E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.326368E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.247010E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.293517E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.272315E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.247010E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.293517E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.262171E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.282916E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.281548E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.263538E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.293517E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.262171E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.272315E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.269124E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.263538E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.326368E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.247010E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.293517E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.272315E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.247010E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.293517E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.262171E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.282916E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.281548E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.263538E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.293517E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.262171E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.272315E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.269124E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.263538E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.326368E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.247010E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.293517E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.318958E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.289319E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.343791E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.307076E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.331375E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.329773E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.308678E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.343791E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.307076E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.318958E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.315220E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.308678E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.382269E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.289319E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.343791E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.379609E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.350196E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.341313E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 202954.55 0.241790E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4611890.56 0.162293E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24333220.76 84473081.56
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35334247.72 44853646.92
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16798891.46 62065869.16
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5123229.77 97636459.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 957938.37 0.186540E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.306681E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.353419E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 87362373.17 0.261087E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 44853646.92
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35334247.72 0.379609E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.642188E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.597668E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.586656E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 425551.02 0.419509E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9010861.39 0.285840E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 44371312.04 0.150114E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 65141902.70 81285900.63
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31228834.93 0.112266E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9494226.31 0.171800E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1816304.79 0.323399E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.523318E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.589852E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.161489E+09 0.448390E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 81285900.63
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 65141902.70 0.642188E+09



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.641777E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.614942E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.621792E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10727.09 0.471267E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4527557.01 0.325245E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38896780.71 0.172207E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 56196890.99 99254002.17
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25944768.92 0.134459E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6356034.70 0.196375E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 901127.94 0.344427E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.530602E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.586923E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.132834E+09 0.473927E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 99254002.17
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 56196890.99 0.641777E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 11837.83 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 11837.83 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 11837.83 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 11837.83 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 11837.83 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 11837.83 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 11837.83 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 11837.83 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 11837.83 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 11837.83 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 11837.83 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 11837.83 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   11837.83   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   11837.83   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 10631.20 02-JAN-08:09 17206.63 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 10631.20 01-FEB-08:09 17206.63 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 10631.20 01-MAR-08:09 17206.63 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 10631.20 03-APR-07:10 17206.63 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 10631.20 01-MAY-07:10 17206.63 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 10631.20 01-JUN-07:10 17206.63 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 10631.20 03-JUL-07:10 17206.63 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 10631.20 01-AUG-07:10 17206.63 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 10631.20 01-SEP-07:10 17206.63 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 10631.20 02-OCT-07:10 17206.63 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 10631.20 01-NOV-07:10 17206.63 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 10631.20 01-DEC-08:09 17206.63 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   10631.20   17206.63   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   10631.20   17206.63   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 10631.20 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 10631.20 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 10631.20 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 10631.20 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 10631.20 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 10631.20 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 10631.20 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 10631.20 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 10631.20 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 10631.20 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 10631.20 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 10631.20 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   10631.20   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   10631.20   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 10631.20 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 10631.20 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 10631.20 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 10631.20 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 10631.20 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 10631.20 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 10631.20 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 10631.20 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 10631.20 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 10631.20 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 10631.20 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 10631.20 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   10631.20   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   10631.20   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1212.73 09-JAN-16:00 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 520.07 16-JAN-18:00
February 2010.79 01-FEB-10:09 1093.68 16-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 387.79 05-FEB-01:00
March 2010.79 01-MAR-10:09 970.36 20-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 350.10 14-MAR-03:00
April 2010.79 03-APR-09:09 635.12 03-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 6.32 26-APR-15:00 379.21 07-APR-22:00
May 2010.79 01-MAY-09:09 736.47 22-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 39.65 14-MAY-17:00 234.43 03-MAY-22:00
June 2010.79 01-JUN-09:09 746.44 08-JUN-15:00 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 99.39 18-JUN-16:00 180.48 10-JUN-01:10
July 2010.79 03-JUL-09:09 743.11 07-JUL-15:00 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 124.83 04-JUL-14:51 81.19 15-JUL-19:10
August 2010.79 01-AUG-09:09 635.12 01-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 66.52 20-AUG-17:00 96.33 22-AUG-21:53
September 2010.79 01-SEP-09:09 1075.38 08-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 42.21 03-SEP-14:50 134.53 18-SEP-01:00
October 2010.79 02-OCT-09:09 1075.19 25-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 20.15 01-OCT-16:00 215.80 11-OCT-23:00
November 2010.79 01-NOV-09:09 1334.85 13-NOV-16:00 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 393.40 26-NOV-06:00
December 2010.79 01-DEC-10:09 1334.85 01-DEC-16:00 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 550.93 14-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   635.12   2160.55   0.00 0.00 0.00 0.00 0.00   81.19  
Maximum of Months 2010.79   1334.85   2160.55   0.00 0.00 0.00 0.00 124.83   550.93  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 781.36 09-JAN-16:00 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 348.34 16-JAN-18:00
February 1295.83 01-FEB-10:09 694.58 16-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 260.32 05-FEB-01:00
March 1295.83 01-MAR-10:09 584.40 14-MAR-15:00 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 232.66 14-MAR-03:00
April 1295.83 03-APR-09:09 409.30 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 4.21 26-APR-15:00 250.01 07-APR-22:00
May 1295.83 01-MAY-09:09 465.02 22-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 26.21 14-MAY-17:00 154.19 03-MAY-22:00
June 1295.83 01-JUN-09:09 481.61 08-JUN-15:00 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 67.07 18-JUN-16:00 118.41 10-JUN-01:10
July 1295.83 03-JUL-09:09 479.57 07-JUL-15:00 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 83.23 04-JUL-15:07 53.45 15-JUL-19:10
August 1295.83 01-AUG-09:09 409.30 01-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 45.98 05-AUG-17:10 70.60 27-AUG-08:10
September 1295.83 01-SEP-09:09 684.85 08-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 29.58 03-SEP-14:25 92.39 18-SEP-01:00
October 1295.83 02-OCT-09:09 658.34 25-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 13.14 01-OCT-16:20 142.51 11-OCT-23:00
November 1295.83 01-NOV-09:09 860.23 13-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 258.26 26-NOV-06:00
December 1295.83 01-DEC-10:09 860.23 01-DEC-16:00 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 361.56 14-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   409.30   1392.34   0.00 0.00 0.00 0.00 0.00   53.45  
Maximum of Months 1295.83   860.23   1392.34   0.00 0.00 0.00 0.00 83.23   361.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1148.40 04-JAN-16:00 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 517.68 16-JAN-18:00
February 2010.83 01-FEB-10:09 1084.12 16-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 404.40 05-FEB-01:00
March 2010.83 01-MAR-10:09 951.46 20-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 356.82 14-MAR-03:00
April 2010.83 03-APR-09:09 635.14 03-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 6.31 26-APR-15:00 383.86 07-APR-22:00
May 2010.83 01-MAY-09:09 738.78 22-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 33.92 14-MAY-17:00 230.80 03-MAY-22:00
June 2010.83 01-JUN-09:09 746.65 08-JUN-15:00 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 97.71 18-JUN-16:00 176.80 10-JUN-01:10
July 2010.83 03-JUL-09:09 743.16 07-JUL-15:00 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 122.79 04-JUL-15:05 83.50 15-JUL-19:10
August 2010.83 01-AUG-09:09 669.18 17-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 64.96 20-AUG-17:00 100.71 22-AUG-21:53
September 2010.83 01-SEP-09:09 1073.41 08-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 39.39 03-SEP-14:25 144.27 18-SEP-01:00
October 2010.83 02-OCT-09:09 1053.17 25-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 16.15 11-OCT-14:10 223.12 11-OCT-23:00
November 2010.83 01-NOV-09:09 1334.88 13-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 398.04 03-NOV-24:00
December 2010.83 01-DEC-10:09 1334.88 01-DEC-16:00 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 562.12 14-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   635.14   2160.58   0.00 0.00 0.00 0.00 0.00   83.50  
Maximum of Months 2010.83   1334.88   2160.58   0.00 0.00 0.00 0.00 122.79   562.12  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 724.09 04-JAN-16:00 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 365.34 16-JAN-18:00
February 1295.83 01-FEB-10:09 706.67 16-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 284.96 05-FEB-01:00
March 1295.83 01-MAR-10:09 665.69 22-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 262.27 14-MAR-03:00
April 1295.83 03-APR-09:09 437.97 05-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 4.21 26-APR-15:00 287.72 07-APR-22:00
May 1295.83 01-MAY-09:09 479.93 22-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 21.32 14-MAY-16:55 172.38 18-MAY-03:00
June 1295.83 01-JUN-09:09 585.53 08-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 58.85 18-JUN-16:00 142.40 10-JUN-01:00
July 1295.83 03-JUL-09:09 476.33 07-JUL-15:00 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 78.12 04-JUL-15:10 65.90 15-JUL-19:10
August 1295.83 01-AUG-09:09 453.16 28-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 41.74 20-AUG-17:00 83.82 22-AUG-21:53
September 1295.83 01-SEP-09:09 696.51 08-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 31.87 03-SEP-15:08 102.77 18-SEP-01:00
October 1295.83 02-OCT-09:09 704.16 25-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 11.03 11-OCT-13:00 158.91 11-OCT-23:00
November 1295.83 01-NOV-09:09 860.23 13-NOV-16:00 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 289.70 03-NOV-24:00
December 1295.83 01-DEC-10:09 860.23 01-DEC-16:00 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 410.21 14-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   437.97   1392.33   0.00 0.00 0.00 0.00 0.00   65.90  
Maximum of Months 1295.83   860.23   1392.33   0.00 0.00 0.00 0.00 78.12   410.21  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1216.43 09-JAN-16:00 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1045.61 16-JAN-18:00
February 2010.79 01-FEB-10:09 1098.94 16-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 800.74 05-FEB-01:00
March 2010.79 01-MAR-10:09 978.36 20-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 723.21 14-MAR-03:00
April 2010.79 03-APR-09:09 635.12 03-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 29.51 01-APR-17:10 821.55 07-APR-22:00
May 2010.79 01-MAY-09:09 734.31 22-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 96.42 14-MAY-16:30 522.78 03-MAY-22:00
June 2010.79 01-JUN-09:09 825.95 08-JUN-15:00 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 228.94 18-JUN-15:50 394.61 10-JUN-01:20
July 2010.79 03-JUL-09:09 741.01 07-JUL-15:00 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 299.89 04-JUL-14:54 215.52 15-JUL-19:00
August 2010.79 01-AUG-09:09 635.12 01-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 155.46 20-AUG-17:00 215.72 22-AUG-22:00
September 2010.79 01-SEP-09:09 1081.07 08-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 104.18 03-SEP-14:50 290.87 07-SEP-22:00
October 2010.79 02-OCT-09:09 1080.83 25-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 54.83 01-OCT-16:10 480.92 11-OCT-23:00
November 2010.79 01-NOV-09:09 1334.85 13-NOV-16:00 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 822.04 03-NOV-24:00
December 2010.79 01-DEC-10:09 1334.85 01-DEC-16:00 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1119.40 14-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   635.12   2160.55   0.00 0.00 0.00 0.00 0.00   215.52  
Maximum of Months 2010.79   1334.85   2160.55   0.00 0.00 0.00 0.00 299.89   1119.40  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 782.91 09-JAN-16:00 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 715.53 16-JAN-18:00
February 1239.33 01-FEB-08:09 695.20 16-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 551.54 05-FEB-01:00
March 1239.33 01-MAR-08:09 584.77 14-MAR-15:00 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 503.35 14-MAR-03:00
April 1239.33 03-APR-07:10 409.30 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 9.21 26-APR-15:00 568.95 23-APR-09:00
May 1239.33 01-MAY-07:10 463.35 22-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 54.65 14-MAY-17:10 346.65 03-MAY-22:00
June 1239.33 01-JUN-07:10 532.06 08-JUN-15:00 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 152.08 18-JUN-16:24 265.94 10-JUN-01:10
July 1239.33 03-JUL-07:10 478.08 07-JUL-15:00 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 207.02 04-JUL-14:53 154.24 15-JUL-19:00
August 1239.33 01-AUG-07:10 409.30 01-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 105.37 20-AUG-17:00 171.12 27-AUG-08:10
September 1239.33 01-SEP-07:10 685.55 08-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 69.89 03-SEP-14:25 204.31 18-SEP-01:00
October 1239.33 02-OCT-07:10 659.76 25-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 28.76 01-OCT-16:10 323.13 11-OCT-23:00
November 1239.33 01-NOV-07:10 860.23 13-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 554.11 03-NOV-24:00
December 1239.33 01-DEC-08:09 860.23 01-DEC-16:00 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 758.87 14-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   409.30   1392.34   0.00 0.00 0.00 0.00 0.00   154.24  
Maximum of Months 1239.33   860.23   1392.34   0.00 0.00 0.00 0.00 207.02   758.87  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1153.46 04-JAN-16:00 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1169.81 16-JAN-18:00
February 2010.83 01-FEB-10:09 1089.72 16-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 909.82 05-FEB-01:00
March 2010.83 01-MAR-10:09 960.10 20-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 786.76 14-MAR-03:00
April 2010.83 03-APR-09:09 635.14 03-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 13.67 26-APR-15:00 856.74 07-APR-22:00
May 2010.83 01-MAY-09:09 736.65 22-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 71.10 14-MAY-17:10 519.84 03-MAY-22:00
June 2010.83 01-JUN-09:09 827.41 08-JUN-15:00 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 222.90 18-JUN-16:30 391.93 10-JUN-01:20
July 2010.83 03-JUL-09:09 741.07 07-JUL-15:00 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 294.52 04-JUL-14:53 222.63 15-JUL-19:00
August 2010.83 01-AUG-09:09 664.35 17-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 150.40 20-AUG-17:00 231.11 22-AUG-22:00
September 2010.83 01-SEP-09:09 1079.16 08-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 90.95 03-SEP-14:25 329.91 17-SEP-19:53
October 2010.83 02-OCT-09:09 1059.57 25-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 31.61 11-OCT-15:00 506.98 11-OCT-23:00
November 2010.83 01-NOV-09:09 1334.88 13-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 887.54 03-NOV-24:00
December 2010.83 01-DEC-10:09 1334.88 01-DEC-16:00 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1230.77 14-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   635.14   2160.58   0.00 0.00 0.00 0.00 0.00   222.63  
Maximum of Months 2010.83   1334.88   2160.58   0.00 0.00 0.00 0.00 294.52   1230.77  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 725.70 04-JAN-16:00 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 748.44 16-JAN-18:00
February 1295.83 01-FEB-10:09 707.02 16-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 584.36 05-FEB-01:00
March 1295.83 01-MAR-10:09 665.94 22-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 513.17 14-MAR-03:00
April 1295.83 03-APR-09:09 435.39 05-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 9.21 26-APR-15:00 595.57 07-APR-22:00
May 1295.83 01-MAY-09:09 478.45 22-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 34.88 21-MAY-16:45 372.79 18-MAY-02:00
June 1295.83 01-JUN-09:09 585.82 08-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 135.28 18-JUN-16:00 293.48 10-JUN-01:00
July 1295.83 03-JUL-09:09 474.80 07-JUL-15:00 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 193.82 04-JUL-14:53 161.54 15-JUL-19:00
August 1295.83 01-AUG-09:09 450.73 28-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 96.51 20-AUG-17:00 166.80 08-AUG-01:00
September 1295.83 01-SEP-09:09 696.87 08-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 68.44 03-SEP-14:25 222.96 17-SEP-19:53
October 1295.83 02-OCT-09:09 704.51 25-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 24.83 11-OCT-13:00 337.88 11-OCT-23:00
November 1295.83 01-NOV-09:09 860.23 13-NOV-16:00 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 585.14 03-NOV-24:00
December 1295.83 01-DEC-10:09 860.23 01-DEC-16:00 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 789.67 14-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   435.39   1392.33   0.00 0.00 0.00 0.00 0.00   161.54  
Maximum of Months 1295.83   860.23   1392.33   0.00 0.00 0.00 0.00 193.82   789.67  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1216.53 09-JAN-16:00 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1071.96 16-JAN-18:00
February 2010.79 01-FEB-10:09 1098.66 16-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 882.60 05-FEB-01:00
March 2010.79 01-MAR-10:09 977.99 20-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 826.00 14-MAR-03:00
April 2010.79 03-APR-09:09 635.12 03-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 38.96 01-APR-17:10 968.71 07-APR-22:00
May 2010.79 01-MAY-09:09 734.15 22-MAY-07:10 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 90.27 14-MAY-16:40 620.28 03-MAY-22:00
June 2010.79 01-JUN-09:09 825.32 08-JUN-15:00 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 268.98 18-JUN-16:00 467.91 10-JUN-01:00
July 2010.79 03-JUL-09:09 740.86 07-JUL-15:00 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 350.71 04-JUL-15:05 285.03 15-JUL-19:00
August 2010.79 01-AUG-09:09 635.12 01-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 185.93 20-AUG-17:00 270.49 22-AUG-22:00
September 2010.79 01-SEP-09:09 1080.76 08-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 118.00 03-SEP-14:50 351.11 07-SEP-22:00
October 2010.79 02-OCT-09:09 1080.55 25-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 61.79 01-OCT-16:00 584.15 11-OCT-23:00
November 2010.79 01-NOV-09:09 1334.85 13-NOV-16:00 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 949.06 03-NOV-21:13
December 2010.79 01-DEC-10:09 1334.85 01-DEC-16:00 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1257.85 14-DEC-04:05
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   635.12   2160.55   0.00 0.00 0.00 0.00 0.00   270.49  
Maximum of Months 2010.79   1334.85   2160.55   0.00 0.00 0.00 0.00 350.71   1257.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 782.99 09-JAN-16:00 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 738.00 16-JAN-18:00
February 1295.83 01-FEB-10:09 695.02 16-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 610.33 05-FEB-01:00
March 1295.83 01-MAR-10:09 584.51 14-MAR-15:00 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 583.83 14-MAR-03:00
April 1295.83 03-APR-09:09 409.30 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 10.60 26-APR-15:00 685.01 23-APR-09:00
May 1295.83 01-MAY-09:09 463.23 22-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 59.43 14-MAY-16:40 415.38 18-MAY-03:02
June 1295.83 01-JUN-09:09 531.68 08-JUN-15:00 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 189.50 18-JUN-15:56 318.07 10-JUN-01:00
July 1295.83 03-JUL-09:09 477.99 07-JUL-15:00 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 244.85 04-JUL-15:05 204.99 15-JUL-19:00
August 1295.83 01-AUG-09:09 409.30 01-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 125.91 20-AUG-17:00 212.97 27-AUG-08:10
September 1295.83 01-SEP-09:09 685.36 08-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 81.77 03-SEP-14:36 249.67 18-SEP-01:00
October 1295.83 02-OCT-09:09 659.61 25-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 35.06 01-OCT-16:00 393.71 11-OCT-23:00
November 1295.83 01-NOV-09:09 860.23 13-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 647.76 03-NOV-21:17
December 1295.83 01-DEC-10:09 860.23 01-DEC-16:00 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 851.25 14-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   409.30   1392.34   0.00 0.00 0.00 0.00 0.00   204.99  
Maximum of Months 1295.83   860.23   1392.34   0.00 0.00 0.00 0.00 244.85   851.25  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1153.36 04-JAN-16:00 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1232.90 16-JAN-18:00
February 2010.83 01-FEB-10:09 1089.44 16-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1027.34 05-FEB-01:00
March 2010.83 01-MAR-10:09 959.73 20-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 916.07 14-MAR-03:00
April 2010.83 03-APR-09:09 635.14 03-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 15.69 26-APR-15:00 1021.83 07-APR-22:00
May 2010.83 01-MAY-09:09 736.49 22-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 80.30 14-MAY-16:40 615.81 18-MAY-03:02
June 2010.83 01-JUN-09:09 826.78 08-JUN-15:00 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 270.45 18-JUN-16:00 463.94 10-JUN-01:00
July 2010.83 03-JUL-09:09 740.91 07-JUL-15:00 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 353.31 04-JUL-15:05 294.26 15-JUL-19:00
August 2010.83 01-AUG-09:09 664.27 17-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 177.20 20-AUG-17:00 290.48 22-AUG-22:00
September 2010.83 01-SEP-09:09 1078.86 08-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 105.54 03-SEP-14:34 408.11 17-SEP-20:00
October 2010.83 02-OCT-09:09 1059.29 25-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 42.82 11-OCT-14:10 618.16 11-OCT-23:00
November 2010.83 01-NOV-09:09 1334.88 13-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1059.76 03-NOV-21:13
December 2010.83 01-DEC-10:09 1334.88 01-DEC-16:00 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1392.58 14-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   635.14   2160.58   0.00 0.00 0.00 0.00 0.00   290.48  
Maximum of Months 2010.83   1334.88   2160.58   0.00 0.00 0.00 0.00 353.31   1392.58  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 725.65 04-JAN-16:00 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 801.06 16-JAN-18:00
February 1295.83 01-FEB-10:09 706.84 16-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 663.29 05-FEB-01:00
March 1295.83 01-MAR-10:09 665.81 22-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 597.41 14-MAR-03:00
April 1295.83 03-APR-09:09 435.28 05-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 10.60 26-APR-15:00 726.41 15-APR-17:03
May 1295.83 01-MAY-09:09 478.35 22-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 43.68 14-MAY-17:16 454.09 18-MAY-02:00
June 1295.83 01-JUN-09:09 585.57 08-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 164.56 18-JUN-16:00 352.47 10-JUN-01:00
July 1295.83 03-JUL-09:09 474.70 07-JUL-15:00 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 221.89 04-JUL-15:10 211.08 15-JUL-19:00
August 1295.83 01-AUG-09:09 450.61 28-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 118.10 20-AUG-17:00 208.74 08-AUG-01:00
September 1295.83 01-SEP-09:09 696.68 08-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 81.71 03-SEP-14:36 273.43 17-SEP-20:00
October 1295.83 02-OCT-09:09 704.35 25-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 29.53 11-OCT-13:00 412.81 11-OCT-23:00
November 1295.83 01-NOV-09:09 860.23 13-NOV-16:00 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 687.90 03-NOV-21:20
December 1295.83 01-DEC-10:09 860.23 01-DEC-16:00 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 901.98 14-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   435.28   1392.33   0.00 0.00 0.00 0.00 0.00   208.74  
Maximum of Months 1295.83   860.23   1392.33   0.00 0.00 0.00 0.00 221.89   901.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 284.97 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 284.97 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 284.97 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 284.97 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 284.97 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 284.97 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 284.97 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 284.97 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 284.97 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 284.97 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 284.97 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 284.97 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   284.97   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   284.97   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 284.97 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 284.97 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 284.97 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 284.97 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 284.97 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 284.97 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 284.97 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 284.97 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 284.97 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 284.97 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 284.97 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 284.97 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   284.97   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   284.97   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 284.97 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 284.97 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 284.97 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 284.97 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 284.97 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 284.97 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 284.97 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 284.97 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 284.97 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 284.97 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 284.97 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 284.97 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   284.97   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   284.97   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 3337.76 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 3337.76 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 3337.76 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 3337.76 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 3337.76 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 3337.76 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 3337.76 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 3337.76 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 3337.76 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 3337.76 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 3337.76 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 3337.76 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   3337.76   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   3337.76   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1099.42 16-JAN-18:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 848.40 05-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 739.70 14-MAR-03:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.78 26-APR-15:00 791.54 07-APR-22:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 74.60 14-MAY-17:00 482.29 03-MAY-22:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 200.72 18-JUN-16:00 374.13 10-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 262.42 04-JUL-14:51 169.75 15-JUL-19:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 133.93 05-AUG-17:02 190.12 22-AUG-22:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 88.93 03-SEP-14:52 275.15 18-SEP-01:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35.09 01-OCT-16:00 444.35 11-OCT-23:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 851.00 26-NOV-06:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1186.21 14-DEC-04:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   169.75  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 262.42   1186.21  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1840.49 16-JAN-18:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1452.13 05-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1259.84 14-MAR-03:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.62 17-APR-15:00 1388.23 07-APR-22:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 149.40 14-MAY-16:52 854.96 03-MAY-22:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 373.60 18-JUN-16:00 656.79 10-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 480.62 04-JUL-15:00 316.85 15-JUL-19:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 251.52 05-AUG-17:02 326.90 22-AUG-22:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 167.42 03-SEP-14:52 473.53 18-SEP-01:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 68.64 01-OCT-16:00 782.45 11-OCT-23:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1443.95 26-NOV-06:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2007.24 14-DEC-04:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   316.85  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 480.62   2007.24  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1757.62 16-JAN-18:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1416.67 05-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1312.03 14-MAR-03:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.08 13-APR-17:00 1501.35 07-APR-22:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 61.57 14-MAY-17:00 916.58 03-MAY-22:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 289.33 18-JUN-16:00 690.44 04-JUN-16:53
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 419.82 04-JUL-16:51 429.82 15-JUL-19:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 213.83 20-AUG-17:00 375.67 08-AUG-01:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 111.57 03-SEP-14:20 525.12 18-SEP-01:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.22 01-OCT-16:00 873.19 11-OCT-23:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1524.35 03-NOV-21:03
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2008.85 14-DEC-04:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   375.67  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 419.82   2008.85  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 96079.45 02-JAN-04:01 0.00 5261.77 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
February 95709.72 13-FEB-04:12 0.00 3288.60 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
March 94938.96 27-MAR-03:02 0.00 2630.88 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
April 96031.11 03-APR-03:02 0.00 3288.60 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
May 90367.51 08-MAY-03:02 0.00 2630.88 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
June 90431.24 20-JUN-03:02 0.00 3288.60 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
July 80936.43 24-JUL-03:02 0.00 3946.33 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
August 81674.88 29-AUG-03:02 0.00 3288.60 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
September 86787.53 25-SEP-04:33 0.00 5261.11 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
October 96421.87 23-OCT-03:02 0.00 2630.88 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
November 96358.15 06-NOV-04:03 0.00 2630.88 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
December 99506.48 26-DEC-04:01 0.00 4604.05 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 80936.43   0.00 2630.88 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 99506.48   0.00 5261.77 107660.35 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 79998.77 02-JAN-04:01 0.00 4725.44 47501.16 0.00 0.00 0.00 0.00 0.00 0.00
February 77998.49 21-FEB-05:01 0.00 9449.70 47501.16 0.00 0.00 0.00 0.00 0.00 0.00
March 77652.34 06-MAR-05:01 0.00 8268.49 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
April 80188.60 24-APR-03:02 0.00 2362.72 23750.58 0.00 0.00 0.00 0.00 0.00 0.00
May 80784.94 30-MAY-03:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
June 81363.13 05-JUN-03:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
July 77325.47 10-JUL-05:04 8061.19 5906.06 38236.95 0.00 0.00 0.00 0.00 0.00 0.00
August 73702.45 07-AUG-05:03 6448.95 4724.85 30589.56 0.00 0.00 0.00 0.00 0.00 0.00
September 80281.51 18-SEP-03:02 0.00 2362.72 23750.58 0.00 0.00 0.00 0.00 0.00 0.00
October 81648.50 10-OCT-03:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
November 79880.82 13-NOV-04:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
December 79675.90 26-DEC-04:01 0.00 4134.76 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 73702.45   0.00 2362.72 23750.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 81648.50   8061.19 9449.70 47501.16 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 32835.33 06-JAN-06:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
February 65564.13 15-FEB-06:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
March 66413.10 17-MAR-05:03 6448.95 4724.85 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
April 70841.15 03-APR-05:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
May 71170.20 27-MAY-05:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
June 71487.60 06-JUN-05:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
July 69027.86 08-JUL-04:03 0.00 2362.72 17812.87 0.00 0.00 0.00 0.00 0.00 0.00
August 71252.39 11-AUG-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
September 71607.36 06-SEP-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
October 71350.80 03-OCT-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
November 68235.06 02-NOV-05:03 6448.95 4724.85 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
December 52968.10 01-DEC-06:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 32835.33   0.00 2362.72 17812.87 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 71607.36   8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 20067.73 26-JAN-14:30 16014.58 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
February 28549.28 15-FEB-17:00 15316.26 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
March 30862.57 08-MAR-17:00 15316.26 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
April 67824.44 27-APR-05:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
May 71538.32 22-MAY-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
June 70135.66 01-JUN-05:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
July 73178.46 17-JUL-03:02 0.00 2953.40 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
August 71618.94 23-AUG-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
September 71260.14 05-SEP-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
October 69966.59 03-OCT-05:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
November 32200.75 01-NOV-15:30 15316.26 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
December 19982.30 29-DEC-13:50 15316.26 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 19982.30   0.00 2953.40 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 73178.46   16014.58 10631.20 38236.81 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2719.64 02-JAN-15:00 2010.79 881.80 2160.55 0.00 0.00 0.00 0.00 0.00 7.46
February 3750.60 15-FEB-15:00 2010.79 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 5.37
March 5760.11 27-MAR-14:30 1923.11 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 10.91
April 7355.41 14-APR-14:00 2010.79 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 1.19
May 11005.24 22-MAY-05:03 809.73 593.25 3840.98 0.00 0.00 0.00 0.00 0.00 8.56
June 13458.65 25-JUN-17:31 0.00 247.02 3914.20 0.00 0.00 0.00 0.00 54.02 0.00
July 15111.79 02-JUL-17:31 0.00 317.59 5032.54 0.00 0.00 0.00 0.00 38.39 0.00
August 12691.04 06-AUG-17:11 0.00 282.30 4473.37 0.00 0.00 0.00 0.00 31.12 0.00
September 11564.76 05-SEP-05:03 809.73 593.25 3840.98 0.00 0.00 0.00 0.00 0.00 6.97
October 11726.67 02-OCT-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 6.07
November 4238.76 09-NOV-14:10 2010.79 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 19.21
December 3069.03 01-DEC-14:10 2010.79 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 27.03
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2719.64   0.00 247.02 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15111.79   2010.79 881.80 5032.54 0.00 0.00 0.00 0.00 54.02 27.03



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5898.44 02-JAN-09:25 2478.65 818.60 2784.68 0.00 0.00 0.00 0.00 0.00 13.30
February 7858.14 14-FEB-09:05 2478.65 818.60 2784.68 0.00 0.00 0.00 0.00 0.00 6.52
March 14575.87 26-MAR-10:02 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 50.24
April 18986.40 30-APR-07:42 391.37 136.45 2784.68 0.00 0.00 0.00 0.00 0.00 83.62
May 18989.56 14-MAY-07:32 391.37 136.45 2784.68 0.00 0.00 0.00 0.00 0.00 30.43
June 18763.84 11-JUN-07:12 391.37 136.45 2784.68 0.00 0.00 0.00 0.00 0.00 37.55
July 19574.39 02-JUL-08:51 456.59 159.19 3248.80 0.00 0.00 0.00 0.00 0.00 15.18
August 18472.03 20-AUG-08:42 391.37 136.45 2784.68 0.00 0.00 0.00 0.00 0.00 3.51
September 19702.07 03-SEP-08:21 456.59 159.19 3248.80 0.00 0.00 0.00 0.00 0.00 5.89
October 18691.48 01-OCT-08:52 391.37 136.45 2784.68 0.00 0.00 0.00 0.00 0.00 31.20
November 8144.12 01-NOV-08:50 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 11.83
December 5195.85 29-DEC-09:15 2478.65 818.60 2784.68 0.00 0.00 0.00 0.00 0.00 2.96
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5195.85   260.91 90.96 1392.34 0.00 0.00 0.00 0.00 0.00 2.96
Maximum of Months 19702.07   2478.65 818.60 3248.80 0.00 0.00 0.00 0.00 0.00 83.62



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19019.32 01-JAN-13:42 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 55.67
February 18959.56 12-FEB-13:52 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 0.00 32.04
March 19031.34 12-MAR-12:32 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 58.98
April 18649.04 30-APR-13:02 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 66.20
May 13227.95 14-MAY-14:12 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 4.79 0.00
June 13958.08 26-JUN-05:02 1012.19 554.01 4801.30 0.00 0.00 0.00 0.00 0.00 7.67
July 18924.90 30-JUL-12:32 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 14.38 0.00
August 19066.64 06-AUG-12:32 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 12.02 0.00
September 20638.37 03-SEP-12:21 708.53 247.02 5041.36 0.00 0.00 0.00 0.00 9.58 0.00
October 21108.33 09-OCT-12:41 708.53 247.02 5041.36 0.00 0.00 0.00 0.00 0.00 16.27
November 20309.76 23-NOV-12:02 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 0.00 12.54
December 19326.24 31-DEC-13:32 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 14.03
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 13227.95   404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21108.33   1012.19 554.01 5041.36 0.00 0.00 0.00 0.00 14.38 66.20



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8105.56 26-JAN-16:30 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 10.85
February 15419.34 12-FEB-15:53 260.91 90.96 1856.44 0.00 0.00 0.00 0.00 0.00 18.08
March 22791.75 12-MAR-15:52 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 0.00 16.29
April 24315.45 16-APR-16:21 456.59 159.19 3248.78 0.00 0.00 0.00 0.00 0.00 11.99
May 25307.63 14-MAY-16:11 521.82 181.93 3712.89 0.00 0.00 0.00 0.00 0.00 3.69
June 26797.93 11-JUN-17:11 0.00 204.67 3243.14 0.00 0.00 0.00 0.00 0.00 3.95
July 26401.13 02-JUL-17:31 0.00 204.67 3243.14 0.00 0.00 0.00 0.00 11.85 0.00
August 24857.87 20-AUG-16:01 456.59 159.19 3248.78 0.00 0.00 0.00 0.00 21.65 0.00
September 23829.37 17-SEP-15:12 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 0.00 15.68
October 24354.39 01-OCT-14:51 456.59 159.19 3248.78 0.00 0.00 0.00 0.00 0.35 0.00
November 22358.65 12-NOV-15:02 326.14 113.70 2320.55 0.00 0.00 0.00 0.00 0.00 29.36
December 15342.68 24-DEC-16:03 260.91 90.96 1856.44 0.00 0.00 0.00 0.00 0.00 111.38
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8105.56   0.00 90.96 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 26797.93   1239.33 409.30 3712.89 0.00 0.00 0.00 0.00 21.65 111.38



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2286.36 05-JAN-15:40 1923.11 691.57 2160.55 0.00 0.00 0.00 0.00 0.00 23.46
February 2594.80 15-FEB-16:00 1923.11 688.52 2160.55 0.00 0.00 0.00 0.00 0.00 17.35
March 3289.05 27-MAR-14:50 1923.11 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 28.08
April 6122.81 14-APR-14:30 1923.11 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 2.38
May 6936.80 31-MAY-15:30 1923.11 635.12 2160.55 0.00 0.00 0.00 0.00 27.26 0.00
June 13958.90 18-JUN-18:21 0.00 317.59 5032.54 0.00 0.00 0.00 0.00 69.33 0.00
July 14393.75 04-JUL-18:12 0.00 352.88 5591.71 0.00 0.00 0.00 0.00 138.17 0.00
August 10672.59 21-AUG-05:03 809.73 593.25 3840.98 0.00 0.00 0.00 0.00 0.00 20.95
September 9345.46 15-SEP-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 23.66
October 6273.64 02-OCT-13:40 2010.79 635.12 2160.55 0.00 0.00 0.00 0.00 4.64 0.00
November 2639.61 01-NOV-15:10 1923.11 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 124.54
December 2136.06 29-DEC-15:40 1923.11 887.17 2160.55 0.00 0.00 0.00 0.00 0.00 7.95
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2136.06   0.00 317.59 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14393.75   2010.79 887.17 5591.71 0.00 0.00 0.00 0.00 138.17 124.54



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3060.89 27-JAN-09:50 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
February 6192.25 14-FEB-09:40 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 13.81
March 14733.90 26-MAR-09:53 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 122.30
April 20495.33 30-APR-08:11 456.59 159.19 3248.80 0.00 0.00 0.00 0.00 0.00 216.39
May 20892.27 29-MAY-08:51 456.59 159.19 3248.80 0.00 0.00 0.00 0.00 0.00 36.62
June 21504.21 18-JUN-09:01 521.82 181.93 3712.91 0.00 0.00 0.00 0.00 0.00 61.88
July 22171.54 04-JUL-08:51 587.05 204.67 4177.03 0.00 0.00 0.00 0.00 0.00 17.01
August 19868.04 20-AUG-08:42 391.37 136.45 2784.68 0.00 0.00 0.00 0.00 0.00 10.33
September 20843.26 03-SEP-09:01 456.59 159.19 3248.80 0.00 0.00 0.00 0.00 0.00 9.54
October 19213.91 01-OCT-08:22 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 0.00 73.04
November 7186.20 01-NOV-09:00 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 26.52
December 2792.13 31-DEC-10:53 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 75.48
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2792.13   260.91 90.96 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22171.54   1239.33 409.30 4177.03 0.00 0.00 0.00 0.00 0.00 216.39



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 18415.75 01-JAN-13:42 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 135.50
February 18353.30 19-FEB-13:42 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 244.19
March 18754.49 12-MAR-13:42 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 68.10
April 17632.86 30-APR-12:53 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 154.14
May 11946.75 14-MAY-13:02 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 4.28
June 16953.10 25-JUN-16:31 1012.19 352.89 7201.95 0.00 0.00 0.00 0.00 142.75 0.00
July 17842.37 30-JUL-11:22 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 30.47 0.00
August 18207.56 13-AUG-12:52 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 10.23 0.00
September 19937.63 03-SEP-12:21 708.53 247.02 5041.36 0.00 0.00 0.00 0.00 18.35 0.00
October 21009.57 01-OCT-12:21 809.75 282.31 5761.56 0.00 0.00 0.00 0.00 0.00 17.44
November 18872.81 05-NOV-14:42 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 444.67
December 18688.48 31-DEC-13:32 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 33.73
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11946.75   404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21009.57   1012.19 352.89 7201.95 0.00 0.00 0.00 0.00 142.75 444.67



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5985.73 26-JAN-16:30 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 25.64
February 9756.71 15-FEB-16:30 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 15.15
March 19540.50 12-MAR-16:21 521.82 181.93 3712.89 0.00 0.00 0.00 0.00 0.00 63.89
April 21997.81 16-APR-16:31 456.59 159.19 3248.78 0.00 0.00 0.00 0.00 0.00 29.39
May 21237.34 14-MAY-16:21 587.05 204.67 4177.00 0.00 0.00 0.00 0.00 5.44 0.00
June 23754.38 25-JUN-16:31 652.28 227.41 4641.11 0.00 0.00 0.00 0.00 52.10 0.00
July 24346.58 04-JUL-16:51 652.28 227.41 4641.11 0.00 0.00 0.00 0.00 108.78 0.00
August 22543.37 13-AUG-17:31 0.00 204.67 3243.14 0.00 0.00 0.00 0.00 3.31 0.00
September 21849.66 24-SEP-16:11 456.59 159.19 3248.78 0.00 0.00 0.00 0.00 0.00 24.90
October 20314.07 01-OCT-14:21 521.82 181.93 3712.89 0.00 0.00 0.00 0.00 2.82 0.00
November 8561.60 02-NOV-16:00 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 20.14
December 4958.10 29-DEC-16:00 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4958.10   0.00 159.19 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24346.58   1239.33 409.30 4641.11 0.00 0.00 0.00 0.00 108.78 63.89



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1950.73 05-JAN-14:30 2010.79 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 26.80
February 2564.02 15-FEB-15:30 1923.11 665.52 2160.55 0.00 0.00 0.00 0.00 0.00 17.36
March 2437.04 08-MAR-14:00 1923.11 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 2.56
April 6510.26 28-APR-15:30 1923.11 635.12 2160.55 0.00 0.00 0.00 0.00 6.45 0.00
May 7656.48 31-MAY-15:10 1923.11 635.12 2160.55 0.00 0.00 0.00 0.00 27.10 0.00
June 16825.95 25-JUN-17:21 0.00 352.88 5591.71 0.00 0.00 0.00 0.00 138.28 0.00
July 16228.25 04-JUL-18:21 0.00 247.02 3914.20 0.00 0.00 0.00 0.00 149.50 0.00
August 16030.75 13-AUG-17:31 0.00 317.59 5032.54 0.00 0.00 0.00 0.00 24.68 0.00
September 9809.10 05-SEP-05:03 809.73 593.25 3840.98 0.00 0.00 0.00 0.00 0.00 20.18
October 6697.20 02-OCT-13:40 2010.79 635.12 2160.55 0.00 0.00 0.00 0.00 5.48 0.00
November 2622.24 01-NOV-15:20 1923.11 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 155.75
December 1771.74 29-DEC-15:00 2010.79 780.77 2160.55 0.00 0.00 0.00 0.00 0.00 29.53
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1771.74   0.00 247.02 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16825.95   2010.79 780.77 5591.71 0.00 0.00 0.00 0.00 149.50 155.75



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2306.27 03-JAN-13:40 1239.33 437.56 1392.34 0.00 0.00 0.00 0.00 0.00 12.13
February 4103.45 14-FEB-10:10 1295.83 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 15.99
March 6216.37 24-MAR-09:40 1295.83 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 43.62
April 18563.88 30-APR-09:12 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 0.00 213.94
May 20967.31 29-MAY-08:51 456.59 159.19 3248.80 0.00 0.00 0.00 0.00 0.00 45.08
June 21241.33 25-JUN-08:61 456.59 159.19 3248.80 0.00 0.00 0.00 0.00 0.00 27.66
July 20396.73 09-JUL-07:32 391.37 136.45 2784.68 0.00 0.00 0.00 0.00 0.00 93.04
August 20239.70 20-AUG-09:22 391.37 136.45 2784.68 0.00 0.00 0.00 0.00 0.00 6.14
September 19327.39 03-SEP-09:12 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 0.00 4.39
October 12533.01 01-OCT-10:32 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 0.00 19.96
November 5957.18 01-NOV-09:30 1295.83 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 49.48
December 2326.75 29-DEC-13:30 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 20.69
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2306.27   326.14 113.70 1392.34 0.00 0.00 0.00 0.00 0.00 4.39
Maximum of Months 21241.33   1295.83 437.56 3248.80 0.00 0.00 0.00 0.00 0.00 213.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 15604.49 26-JAN-14:10 2010.83 635.14 2160.58 0.00 0.00 0.00 0.00 0.00 47.69
February 19615.05 19-FEB-13:42 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 288.81
March 20189.73 12-MAR-14:22 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 86.95
April 13429.60 28-APR-13:20 2010.83 635.14 2160.58 0.00 0.00 0.00 0.00 1.11 0.00
May 19343.26 21-MAY-13:22 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 3.93 0.00
June 20035.70 25-JUN-16:01 1012.19 352.89 7201.95 0.00 0.00 0.00 0.00 107.50 0.00
July 19681.37 30-JUL-14:52 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 90.27 0.00
August 20681.81 13-AUG-12:52 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 7.59 0.00
September 21127.87 03-SEP-13:12 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 53.78 0.00
October 21703.13 01-OCT-13:12 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 0.00 5.96
November 20705.00 19-NOV-12:52 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 0.00 236.56
December 19573.49 31-DEC-13:53 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 13429.60   404.87 141.16 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21703.13   2010.83 635.14 7201.95 0.00 0.00 0.00 0.00 107.50 288.81



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5111.87 26-JAN-16:30 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 32.08
February 9462.24 15-FEB-16:30 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 19.09
March 16945.30 12-MAR-16:21 521.82 181.93 3712.89 0.00 0.00 0.00 0.00 0.00 79.35
April 19624.90 16-APR-16:42 326.14 113.70 2320.55 0.00 0.00 0.00 0.00 0.00 29.51
May 22372.87 29-MAY-16:11 521.82 181.93 3712.89 0.00 0.00 0.00 0.00 0.00 13.15
June 26440.78 25-JUN-16:41 652.28 227.41 4641.11 0.00 0.00 0.00 0.00 57.13 0.00
July 24114.46 04-JUL-17:01 0.00 181.93 2882.79 0.00 0.00 0.00 0.00 154.09 0.00
August 24590.33 13-AUG-17:31 0.00 204.67 3243.14 0.00 0.00 0.00 0.00 1.13 0.00
September 21764.53 24-SEP-16:22 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 0.00 17.36
October 20249.59 01-OCT-15:12 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 9.16 0.00
November 8014.94 02-NOV-16:00 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 25.37
December 4126.86 29-DEC-16:00 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4126.86   0.00 113.70 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 26440.78   1239.33 409.30 4641.11 0.00 0.00 0.00 0.00 154.09 79.35



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4470.19 02-JAN-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 48.66
February 3848.95 15-FEB-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50.00
March 4609.66 27-MAR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31.64
April 5992.80 03-APR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.51
May 9042.10 30-MAY-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.29
June 9610.85 19-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32.12
July 12949.10 05-JUL-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.66
August 11496.02 14-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.90
September 11855.72 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16.61
October 9622.60 10-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.83
November 4451.51 01-NOV-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 126.53
December 3296.45 01-DEC-06:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32.15
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3296.45   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.90
Maximum of Months 12949.10   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 126.53



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5061.46 07-JAN-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.13
February 5792.84 06-FEB-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1031.67
March 3462.00 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 84.63
April 4348.98 28-APR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.05 0.00
May 4915.67 22-MAY-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35.90
June 6533.22 29-JUN-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 77.80 0.00
July 7414.71 17-JUL-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22.91
August 7063.57 01-AUG-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.67
September 6873.42 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.68
October 5479.02 03-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 104.73
November 4596.83 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 98.69
December 4736.73 22-DEC-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 569.56
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3462.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7414.71   0.00 0.00 0.00 0.00 0.00 0.00 0.00 77.80 1031.67



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2445.03 01-JAN-14:07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 120.49
February 5445.95 15-FEB-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.51
March 8089.37 08-MAR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.83
April 14519.40 28-APR-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.82
May 17188.04 30-MAY-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.94 0.00
June 22131.90 28-JUN-13:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 49.67 0.00
July 21191.77 21-JUL-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 80.13 0.00
August 19721.30 07-AUG-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.66 0.00
September 15310.84 01-SEP-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.58 0.00
October 11768.63 05-OCT-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.09 0.00
November 4850.12 01-NOV-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 256.02
December 2760.66 31-DEC-14:35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2445.03   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22131.90   0.00 0.00 0.00 0.00 0.00 0.00 0.00 80.13 256.02



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2219.59 26-JAN-17:00 222.14 284.97 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 4245.45 15-FEB-17:00 222.14 284.97 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 7109.00 31-MAR-24:00 0.00 15.83 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 8249.41 16-APR-18:20 0.00 94.99 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
May 3498.44 31-MAY-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5340.36 30-JUN-24:00 0.00 15.83 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7235.22 31-JUL-23:45 0.00 31.66 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
August 7918.70 30-AUG-17:40 23.38 94.99 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3499.55 30-SEP-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5294.71 31-OCT-24:00 0.00 15.83 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 6127.23 05-NOV-16:33 35.07 47.50 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
December 7931.78 31-DEC-16:35 23.38 31.66 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2219.59   0.00 15.83 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8249.41   222.14 284.97 46766.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1980.92 26-JAN-17:00 222.14 284.97 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3974.96 15-FEB-17:00 222.14 284.97 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6545.31 31-MAR-23:40 0.00 15.83 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7771.31 16-APR-17:42 0.00 94.99 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
May 3308.29 31-MAY-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5162.22 30-JUN-24:00 0.00 15.83 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6983.22 31-JUL-23:53 0.00 63.33 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
August 7563.57 30-AUG-17:40 23.38 94.99 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3300.54 30-SEP-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4809.10 31-OCT-24:00 0.00 15.83 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5689.75 02-NOV-16:40 70.15 158.31 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7290.76 29-DEC-16:50 222.14 284.97 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1980.92   0.00 15.83 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7771.31   222.14 284.97 46766.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1825.53 26-JAN-17:00 222.14 284.97 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3971.19 15-FEB-17:00 222.14 284.97 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6175.24 31-MAR-23:20 0.00 15.83 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7764.10 16-APR-17:42 0.00 94.99 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
May 3262.81 31-MAY-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5175.89 30-JUN-24:00 0.00 15.83 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6973.42 31-JUL-23:53 0.00 63.33 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
August 7723.61 13-AUG-19:23 0.00 63.33 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
September 3278.72 30-SEP-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4553.32 31-OCT-23:40 0.00 15.83 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5660.62 02-NOV-16:40 70.15 158.31 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7147.55 29-DEC-16:50 222.14 284.97 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1825.53   0.00 15.83 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7764.10   222.14 284.97 46766.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 91564.98 02-JAN-17:00 4808.68 3337.76 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 182867.59 15-FEB-17:00 4808.68 3337.76 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 358508.74 31-MAR-24:00 0.00 185.45 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 366453.85 26-APR-16:00 4808.68 3337.76 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
May 175775.06 31-MAY-24:00 0.00 185.45 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 267520.94 30-JUN-24:00 0.00 185.45 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
July 359978.96 31-JUL-23:55 0.00 741.80 1518530.09 0.00 0.00 0.00 0.00 0.00 0.00
August 368004.50 21-AUG-16:00 4808.68 3337.76 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
September 176457.17 30-SEP-24:00 0.00 185.45 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 268399.23 31-OCT-24:00 0.00 185.45 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 275800.37 24-NOV-17:00 4808.68 3337.76 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 367096.89 26-DEC-17:00 9617.36 6675.52 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 91564.98   0.00 185.45 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 368004.50   9617.36 6675.52 1518530.09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.127994E+13 829262.65 05-JAN-16:10 0.292478E+12 709192.31 21-JAN-07:10
February 0.150741E+13 1047087.78 14-FEB-16:40 0.193108E+12 683245.88 06-FEB-07:30
March 0.210381E+13 1224917.38 08-MAR-16:19 0.100162E+12 363790.23 04-MAR-06:10
April 0.244523E+13 1505520.84 28-APR-15:09 0.632825E+11 224632.36 08-APR-06:10
May 0.146631E+13 1103822.97 19-MAY-15:09 0.593396E+11 87999.92 06-MAY-06:10
June 0.194699E+13 1322808.02 26-JUN-15:30 0.549551E+11 74336.22 02-JUN-11:39
July 0.242708E+13 1514677.49 31-JUL-15:09 0.516921E+11 71452.77 05-JUL-11:39
August 0.283459E+13 1632266.59 02-AUG-15:30 0.546237E+11 70698.63 29-AUG-11:39
September 0.147810E+13 1132057.43 05-SEP-15:09 0.517314E+11 72297.65 22-SEP-11:50
October 0.177822E+13 1201376.65 02-OCT-15:00 0.767736E+11 425787.74 26-OCT-06:10
November 0.199501E+13 1158434.14 02-NOV-15:00 0.113261E+12 523499.74 27-NOV-07:10
December 0.240276E+13 1277946.71 19-DEC-16:00 0.290334E+12 669972.19 15-DEC-07:10
             
Annual Sum or Average 0.236654E+14     0.140174E+13    
Minimum of Months 0.127994E+13 829262.65   0.516921E+11 70698.63  
Maximum of Months 0.283459E+13 1632266.59   0.292478E+12 709192.31  



Table of Contents

Report: EnergyConsumptionDistrictHeatingCoolingMonthly

For: Meter

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

DISTRICTCOOLING:FACILITY [J] DISTRICTCOOLING:FACILITY {Maximum} [W] DISTRICTCOOLING:FACILITY {TIMESTAMP} DISTRICTHEATING:FACILITY [J] DISTRICTHEATING:FACILITY {Maximum} [W] DISTRICTHEATING:FACILITY {TIMESTAMP}
January 0.239431E+12 94164.18 02-JAN-16:00 161413.36 6.69 21-JAN-19:40
February 0.436908E+12 185466.68 15-FEB-16:00 203569.01 11.73 01-FEB-00:40
March 0.730473E+12 358509.33 31-MAR-23:00 203561.83 12.11 01-MAR-00:30
April 0.944425E+12 369052.90 26-APR-15:00 79260.19 8.42 07-APR-23:30
May 0.242328E+12 175778.23 31-MAY-23:00 138180.89 11.64 31-MAY-23:40
June 0.471839E+12 267521.63 30-JUN-23:00 57374.55 8.40 19-JUN-23:30
July 0.733833E+12 359979.00 31-JUL-23:00 20407.37 8.21 07-JUL-23:30
August 0.979884E+12 370603.48 21-AUG-15:00 25103.61 5.68 27-AUG-17:19
September 0.237707E+12 176457.17 30-SEP-23:00 125862.93 6.88 16-SEP-18:40
October 0.489438E+12 268400.54 31-OCT-23:00 158043.46 12.08 31-OCT-23:30
November 0.709921E+12 278399.26 24-NOV-16:00 193401.64 8.24 10-NOV-00:30
December 0.977712E+12 369695.76 26-DEC-16:00 196712.15 11.12 01-DEC-00:30
             
Annual Sum or Average 0.719390E+13     1562891.01    
Minimum of Months 0.237707E+12 94164.18   20407.37 5.68  
Maximum of Months 0.979884E+12 370603.48   203569.01 12.11  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.170745E+12 0.355334E+11 0.766053E+12 0.207861E+12 0.777056E+11 0.987106E+10 0.00 0.107663E+11 0.140359E+10 0.00 0.00 0.00 0.00
February 0.153960E+12 0.290613E+11 0.978954E+12 0.229081E+12 0.731733E+11 0.126531E+11 0.00 0.263016E+11 0.423006E+10 0.00 0.00 0.00 0.00
March 0.181471E+12 0.279369E+11 0.141687E+13 0.299604E+12 0.941480E+11 0.185309E+11 0.00 0.534156E+11 0.118285E+11 0.00 0.00 0.00 0.00
April 0.161083E+12 0.231121E+11 0.165903E+13 0.333797E+12 0.114525E+12 0.335950E+11 0.00 0.979164E+11 0.221719E+11 0.00 0.00 0.00 0.00
May 0.173563E+12 0.206906E+11 0.774844E+12 0.208007E+12 0.129968E+12 0.442566E+11 0.00 0.936346E+11 0.213438E+11 0.00 0.00 0.00 0.00
June 0.172352E+12 0.187757E+11 0.106252E+13 0.245640E+12 0.160351E+12 0.689526E+11 0.00 0.183843E+12 0.345542E+11 0.00 0.00 0.00 0.00
July 0.161600E+12 0.199952E+11 0.139340E+13 0.299361E+12 0.173912E+12 0.826626E+11 0.00 0.241601E+12 0.545418E+11 0.00 0.00 0.00 0.00
August 0.180019E+12 0.225564E+11 0.173200E+13 0.345114E+12 0.175598E+12 0.838691E+11 0.00 0.245310E+12 0.501199E+11 0.00 0.00 0.00 0.00
September 0.161726E+12 0.251956E+11 0.740713E+12 0.201201E+12 0.128207E+12 0.579889E+11 0.00 0.133065E+12 0.300022E+11 0.00 0.00 0.00 0.00
October 0.169116E+12 0.303882E+11 0.108340E+13 0.253679E+12 0.105954E+12 0.357951E+11 0.00 0.816380E+11 0.182454E+11 0.00 0.00 0.00 0.00
November 0.168775E+12 0.333309E+11 0.135889E+13 0.289765E+12 0.842119E+11 0.116130E+11 0.00 0.405773E+11 0.784440E+10 0.00 0.00 0.00 0.00
December 0.166550E+12 0.366166E+11 0.170972E+13 0.345057E+12 0.792846E+11 0.115240E+11 0.00 0.482690E+11 0.573877E+10 0.00 0.00 0.00 0.00
                           
Annual Sum or Average 0.202096E+13 0.323193E+12 0.146764E+14 0.325817E+13 0.139704E+13 0.471312E+12 0.00 0.125634E+13 0.262025E+12 0.00 0.00 0.00 0.00
Minimum of Months 0.153960E+12 0.187757E+11 0.740713E+12 0.201201E+12 0.731733E+11 0.987106E+10 0.00 0.107663E+11 0.140359E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.181471E+12 0.366166E+11 0.173200E+13 0.345114E+12 0.175598E+12 0.838691E+11 0.00 0.245310E+12 0.545418E+11 0.00 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.228703E+12 0.00 0.637748E+11 0.00 0.00
February 0.00 0.00 0.134901E+12 0.00 0.582074E+11 0.00 0.00
March 0.00 0.00 0.339971E+11 0.00 0.661649E+11 0.00 0.00
April 0.00 0.00 0.466714E+10 0.00 0.586153E+11 0.00 0.00
May 0.00 0.00 0.463068E+09 0.00 0.588765E+11 0.00 0.00
June 0.00 0.00 1941873.82 0.00 0.549531E+11 0.00 0.00
July 0.00 0.00 0.00 0.00 0.516921E+11 0.00 0.00
August 0.00 0.00 0.00 0.00 0.546237E+11 0.00 0.00
September 0.00 0.00 0.00 0.00 0.517314E+11 0.00 0.00
October 0.00 0.00 0.208692E+11 0.00 0.559044E+11 0.00 0.00
November 0.00 0.00 0.556090E+11 0.00 0.576519E+11 0.00 0.00
December 0.00 0.00 0.229554E+12 0.00 0.607793E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.708766E+12 0.00 0.692975E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.516921E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.229554E+12 0.00 0.661649E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 192435.19 04-JAN-16:00 37611.08 01-JAN-06:10 423497.50 02-JAN-08:09 133938.60 03-JAN-08:20 73620.65 26-JAN-16:49 30873.67 17-JAN-06:10 0.00 01-JAN-00:10
February 189247.46 16-FEB-08:09 37611.08 01-FEB-06:10 541788.89 01-FEB-08:09 151027.22 16-FEB-08:20 105323.07 15-FEB-16:00 45468.54 14-FEB-16:40 0.00 01-FEB-00:10
March 184120.58 20-MAR-07:10 37611.08 01-MAR-06:10 660080.29 01-MAR-08:09 168107.99 20-MAR-07:19 111998.84 15-MAR-15:00 45430.23 08-MAR-13:39 0.00 01-MAR-00:10
April 171551.51 05-APR-07:10 37611.08 01-APR-05:10 778371.69 03-APR-07:10 185184.84 05-APR-07:19 170896.73 13-APR-15:20 46328.61 28-APR-13:39 0.00 01-APR-00:10
May 175129.67 22-MAY-07:10 37611.08 01-MAY-05:10 423497.50 01-MAY-07:10 133936.32 22-MAY-07:19 178731.80 30-MAY-14:30 51027.25 23-MAY-12:30 0.00 01-MAY-00:10
June 177912.80 08-JUN-15:00 24287.76 01-JUN-19:10 541788.89 01-JUN-07:10 151020.09 08-JUN-07:19 214828.06 28-JUN-14:39 58943.51 27-JUN-15:20 0.00 01-JUN-00:10
July 175395.87 07-JUL-15:00 37611.08 19-JUL-05:10 660080.29 03-JUL-07:10 168101.60 28-JUL-07:19 214182.38 06-JUL-15:09 61255.83 21-JUL-15:00 0.00 01-JUL-00:10
August 171918.60 17-AUG-07:10 37611.08 01-AUG-05:10 778371.69 01-AUG-07:10 185185.04 17-AUG-07:19 217050.77 07-AUG-15:39 53447.85 02-AUG-07:00 0.00 01-AUG-00:10
September 188667.91 08-SEP-07:10 37611.08 01-SEP-05:10 423497.50 01-SEP-07:10 133943.45 08-SEP-07:19 171955.21 06-SEP-15:50 58762.59 21-SEP-14:00 0.00 01-SEP-00:10
October 188210.97 25-OCT-07:10 37611.08 01-OCT-05:10 541788.89 02-OCT-07:10 151026.67 25-OCT-07:19 149157.55 02-OCT-08:50 56132.74 02-OCT-10:00 0.00 01-OCT-00:10
November 198852.03 13-NOV-16:00 37611.08 01-NOV-05:10 660080.29 01-NOV-07:10 168112.40 02-NOV-07:19 108260.89 03-NOV-15:00 30100.22 27-NOV-06:10 0.00 01-NOV-00:10
December 198852.03 01-DEC-16:00 37611.08 01-DEC-06:10 778371.69 01-DEC-08:09 185192.48 08-DEC-08:20 73761.64 29-DEC-16:30 30231.21 22-DEC-06:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 171551.51   24287.76   423497.50   133936.32   73620.65   30100.22   0.00  
Maximum of Months 198852.03   37611.08   778371.69   185192.48   217050.77   61255.83   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 41254.81 05-JAN-15:39 5952.96 05-JAN-15:00 0.00 0.00 0.00 0.00
February 83021.07 14-FEB-16:49 12817.81 14-FEB-15:00 0.00 0.00 0.00 0.00
March 92446.88 08-MAR-16:19 13161.28 08-MAR-13:00 0.00 0.00 0.00 0.00
April 189204.82 28-APR-13:00 13605.89 28-APR-14:20 0.00 0.00 0.00 0.00
May 178568.80 23-MAY-12:30 16857.07 22-MAY-15:50 0.00 0.00 0.00 0.00
June 224182.17 28-JUN-14:50 42924.61 06-JUN-13:20 0.00 0.00 0.00 0.00
July 250464.06 31-JUL-14:00 42924.61 03-JUL-08:50 0.00 0.00 0.00 0.00
August 233985.11 21-AUG-13:00 42924.61 01-AUG-09:39 0.00 0.00 0.00 0.00
September 249062.52 05-SEP-13:09 42924.61 01-SEP-10:50 0.00 0.00 0.00 0.00
October 199575.65 02-OCT-10:00 42924.61 11-OCT-10:50 0.00 0.00 0.00 0.00
November 65373.21 02-NOV-14:00 12686.59 02-NOV-15:09 0.00 0.00 0.00 0.00
December 23041.61 24-DEC-15:30 8108.54 01-DEC-15:00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average         0.00 0.00 0.00 0.00
Minimum of Months 23041.61   5952.96   0.00 0.00 0.00 0.00
Maximum of Months 250464.06   42924.61   0.00 0.00 0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 829262.65 05-JAN-16:10 176113.97 423497.50 0.00 99892.85 68828.57 28877.14 0.00 27162.87 4889.76
February 1047087.78 14-FEB-16:40 172091.91 541788.89 0.00 116974.36 75166.89 45468.54 0.00 82973.24 12623.94
March 1224917.38 08-MAR-16:19 171235.93 660080.29 0.00 134057.82 109206.34 45088.84 0.00 92446.88 12801.29
April 1505520.84 28-APR-15:09 171235.93 778371.69 0.00 151141.29 168115.79 45591.68 0.00 178023.42 13041.06
May 1103822.97 19-MAY-15:09 171235.93 423497.50 0.00 99890.88 177064.94 45827.13 0.00 171832.23 14474.37
June 1322808.02 26-JUN-15:30 171235.93 541788.89 0.00 116974.35 210061.18 52724.07 0.00 214775.05 15248.55
July 1514677.49 31-JUL-15:09 171235.93 660080.29 0.00 134057.82 210925.51 47944.83 0.00 247508.52 42924.61
August 1632266.59 02-AUG-15:30 171235.93 778371.69 0.00 151141.29 213932.73 48821.04 0.00 225839.31 42924.61
September 1132057.43 05-SEP-15:09 171235.93 423497.50 0.00 99890.88 171567.09 46717.98 0.00 176223.45 42924.61
October 1201376.65 02-OCT-15:00 171498.75 541788.89 0.00 116974.35 131652.62 51184.99 0.00 174101.79 14175.26
November 1158434.14 02-NOV-15:00 175409.23 660080.29 0.00 134059.54 89668.59 29068.50 0.00 57496.90 12651.09
December 1277946.71 19-DEC-16:00 198852.03 778371.69 37611.08 151155.16 57449.13 28843.24 0.00 22120.46 3543.94
                       
Annual Sum or Average                      
Minimum of Months 829262.65   171235.93 423497.50 0.00 99890.88 57449.13 28843.24 0.00 22120.46 3543.94
Maximum of Months 1632266.59   198852.03 778371.69 37611.08 151155.16 213932.73 52724.07 0.00 247508.52 42924.61



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 681631.09 21-JAN-07:10 0.00 81596.13 31-JAN-12:39 0.00
February 0.00 0.00 663664.77 06-FEB-07:10 0.00 81624.73 03-FEB-12:39 0.00
March 0.00 0.00 353259.75 04-MAR-07:10 0.00 81313.91 01-MAR-12:30 0.00
April 0.00 0.00 197024.15 08-APR-06:10 0.00 79728.05 03-APR-11:20 0.00
May 0.00 0.00 60790.90 06-MAY-06:10 0.00 77475.05 01-MAY-11:39 0.00
June 0.00 0.00 471.66 09-JUN-05:00 0.00 74336.22 02-JUN-11:39 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 71452.77 05-JUL-11:39 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 70698.63 29-AUG-11:39 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 72297.65 22-SEP-11:50 0.00
October 0.00 0.00 403299.67 26-OCT-06:19 0.00 76004.99 31-OCT-11:39 0.00
November 0.00 0.00 494749.74 27-NOV-07:10 0.00 78752.11 30-NOV-12:39 0.00
December 0.00 0.00 640775.20 15-DEC-07:10 0.00 80622.86 29-DEC-12:20 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 0.00   0.00 70698.63   0.00
Maximum of Months 0.00 0.00 681631.09   0.00 81624.73   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 5.83 26.74 0.67 26.82
February 0.00 0.00 0.00 0.00 4.67 26.47 0.00 26.47
March 0.00 0.00 0.00 0.00 2.67 26.00 0.00 26.00
April 0.00 0.00 0.00 0.00 3.17 25.96 0.00 25.96
May 0.00 0.00 0.00 0.00 4.17 26.16 0.50 26.29
June 0.00 0.00 0.00 0.00 5.83 26.11 0.00 26.11
July 0.00 0.00 0.00 0.00 7.33 26.32 0.17 26.29
August 0.00 0.00 0.00 0.00 7.83 26.16 0.33 26.15
September 0.00 0.00 0.00 0.00 8.67 26.39 0.67 26.46
October 0.00 0.00 0.00 0.00 11.50 26.44 0.50 26.48
November 0.00 0.00 0.00 0.00 12.17 26.45 0.67 26.50
December 0.00 0.00 0.00 0.00 7.83 26.47 0.67 26.55
                 
Annual Sum or Average 0.00   0.00   81.67 26.35 4.17 26.39
Minimum of Months 0.00 0.00 0.00 0.00 2.67 25.96 0.00 25.96
Maximum of Months 0.00 0.00 0.00 0.00 12.17 26.74 0.67 26.82



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 25.61 0.00 25.61
March 0.00 0.00 0.00 0.00 0.50 26.03 0.00 26.03
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.33 25.62 0.00 25.62
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.50 25.58 0.00 25.58
August 0.00 0.00 0.00 0.00 0.67 25.61 0.00 25.61
September 0.00 0.00 0.00 0.00 0.33 25.59 0.00 25.59
October 0.00 0.00 0.00 0.00 0.50 25.79 0.00 25.79
November 0.00 0.00 0.00 0.00 0.17 25.61 0.00 25.61
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.17 25.70 0.00 25.70
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.67 26.03 0.00 26.03



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.00 18.93 0.00 18.93 0.00 18.93 0.00 18.93
February 0.17 19.01 0.00 19.01 0.00 19.01 0.00 19.01
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.00 19.07 0.00 19.07 0.00 19.07 0.00 19.07
                 
Annual Sum or Average 2.17 19.00 0.00 19.00 0.00 19.00 0.00 19.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.00 19.07 0.00 19.07 0.00 19.07 0.00 19.07



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.50 27.34 0.00 27.34
July 0.00 0.00 0.00 0.00 2.17 26.89 0.83 27.03
August 0.00 0.00 0.00 0.00 1.33 26.92 0.83 27.08
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.00 26.95 1.67 27.07
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.17 27.34 0.83 27.34



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 1.67 27.73 1.67 27.73
April 0.00 0.00 0.00 0.00 3.67 27.92 3.67 27.92
May 0.00 0.00 0.00 0.00 6.67 28.06 6.67 28.06
June 0.00 0.00 0.00 0.00 6.17 28.03 6.17 28.03
July 0.00 0.00 0.00 0.00 13.67 28.00 13.67 28.00
August 0.00 0.00 0.00 0.00 7.83 28.00 7.67 28.01
September 0.00 0.00 0.00 0.00 4.33 27.87 4.33 27.87
October 0.00 0.00 0.00 0.00 3.17 27.81 3.17 27.81
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   47.17 27.97 47.00 27.97
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 13.67 28.06 13.67 28.06



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 6.33 27.84 6.33 27.84
February 0.00 0.00 0.00 0.00 5.33 26.84 5.33 26.84
March 0.00 0.00 0.00 0.00 3.67 27.74 3.67 27.74
April 0.00 0.00 0.00 0.00 2.17 27.55 2.17 27.55
May 0.00 0.00 0.00 0.00 0.67 27.32 0.67 27.32
June 0.00 0.00 0.00 0.00 0.67 27.37 0.67 27.37
July 0.00 0.00 0.00 0.00 8.33 27.36 7.00 27.45
August 0.00 0.00 0.00 0.00 9.17 27.47 6.67 27.60
September 0.00 0.00 0.00 0.00 13.50 26.70 13.50 26.70
October 0.00 0.00 0.00 0.00 26.83 25.88 26.33 25.87
November 0.00 0.00 0.00 0.00 12.17 26.70 12.17 26.70
December 0.00 0.00 0.00 0.00 5.67 27.95 5.67 27.95
                 
Annual Sum or Average 0.00   0.00   94.50 26.83 90.17 26.83
Minimum of Months 0.00 0.00 0.00 0.00 0.67 25.88 0.67 25.87
Maximum of Months 0.00 0.00 0.00 0.00 26.83 27.95 26.33 27.95



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.33 27.30 0.33 27.30
February 0.00 0.00 0.00 0.00 1.17 27.76 1.17 27.76
March 0.00 0.00 0.00 0.00 3.67 28.33 3.00 28.35
April 0.00 0.00 0.00 0.00 18.50 27.33 6.00 27.59
May 0.00 0.00 0.00 0.00 6.17 27.91 4.00 28.06
June 0.00 0.00 0.00 0.00 20.00 27.41 5.50 27.63
July 0.00 0.00 0.00 0.00 33.33 27.45 9.67 27.67
August 0.00 0.00 0.00 0.00 33.50 27.43 8.67 27.61
September 0.00 0.00 0.00 0.00 7.50 27.88 4.83 28.02
October 0.00 0.00 0.00 0.00 5.50 27.92 3.83 28.15
November 0.00 0.00 0.00 0.00 3.50 27.83 3.50 27.83
December 0.00 0.00 0.00 0.00 2.17 27.81 2.17 27.81
                 
Annual Sum or Average 0.00   0.00   135.33 27.53 52.67 27.74
Minimum of Months 0.00 0.00 0.00 0.00 0.33 27.30 0.33 27.30
Maximum of Months 0.00 0.00 0.00 0.00 33.50 28.33 9.67 28.35



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.33 19.27 0.00 19.27 0.00 19.27 0.00 19.27
February 0.50 19.15 0.00 19.15 0.00 19.15 0.00 19.15
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.17 27.37 0.67 27.35
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 19.43 0.00 19.43 0.00 19.43 0.00 19.43
December 1.17 19.37 0.00 19.37 0.00 19.37 0.00 19.37
                 
Annual Sum or Average 3.17 19.30 0.00 19.30 1.17 21.47 0.67 22.25
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.33 19.43 0.00 19.43 1.17 27.37 0.67 27.35



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.00 19.25 0.00 19.25 0.00 19.25 0.00 19.25
February 0.33 19.17 0.00 19.17 0.00 19.17 0.00 19.17
March 0.00 0.00 0.00 0.00 1.00 27.60 1.00 27.60
April 0.00 0.00 0.00 0.00 3.33 27.90 3.33 27.90
May 0.00 0.00 0.00 0.00 7.67 28.06 7.67 28.06
June 0.00 0.00 0.00 0.00 8.00 28.09 7.83 28.10
July 0.00 0.00 0.00 0.00 16.33 28.19 16.00 28.20
August 0.00 0.00 0.00 0.00 10.17 28.12 9.83 28.14
September 0.00 0.00 0.00 0.00 4.00 28.04 4.00 28.04
October 0.00 0.00 0.00 0.00 2.33 27.81 2.33 27.81
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.67 19.37 0.00 19.37 0.00 19.37 0.00 19.37
                 
Annual Sum or Average 2.00 19.28 0.00 19.28 52.83 27.76 52.00 27.93
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.00 19.37 0.00 19.37 16.33 28.19 16.00 28.20



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 19.40 0.00 19.40 22.17 25.68 22.17 25.72
February 0.17 19.39 0.00 19.39 16.50 25.54 16.50 25.57
March 0.00 0.00 0.00 0.00 3.50 27.83 3.50 27.83
April 0.00 0.00 0.00 0.00 1.33 27.58 1.33 27.58
May 0.00 0.00 0.00 0.00 0.33 27.32 0.33 27.32
June 0.00 0.00 0.00 0.00 0.17 27.28 0.17 27.28
July 0.00 0.00 0.00 0.00 6.00 27.54 5.67 27.54
August 0.00 0.00 0.00 0.00 7.17 27.68 6.17 27.71
September 0.00 0.00 0.00 0.00 17.67 26.53 17.50 26.53
October 0.00 0.00 0.00 0.00 55.50 25.62 54.83 25.61
November 0.00 0.00 0.00 0.00 37.33 25.57 37.33 25.57
December 0.00 0.00 0.00 0.00 10.17 26.40 10.17 26.40
                 
Annual Sum or Average 0.50 19.40 0.00 19.40 177.83 25.95 175.67 25.96
Minimum of Months 0.00 0.00 0.00 0.00 0.17 25.54 0.17 25.57
Maximum of Months 0.33 19.40 0.00 19.40 55.50 27.83 54.83 27.83



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.37 0.00 19.37 0.00 19.37 0.00 19.37
February 0.17 19.24 0.00 19.24 0.00 19.24 0.00 19.24
March 0.00 0.00 0.00 0.00 1.50 27.81 1.33 27.81
April 0.00 0.00 0.00 0.00 4.33 28.09 2.67 28.14
May 0.00 0.00 0.00 0.00 4.00 28.21 2.67 28.28
June 0.00 0.00 0.00 0.00 7.50 28.52 3.17 28.60
July 0.00 0.00 0.00 0.00 10.17 28.16 5.17 28.29
August 0.00 0.00 0.00 0.00 7.33 28.05 3.50 28.17
September 0.00 0.00 0.00 0.00 5.17 28.09 3.67 28.13
October 0.00 0.00 0.00 0.00 3.00 28.11 2.33 28.15
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 19.31 0.00 19.31 43.00 28.11 24.50 28.21
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.37 0.00 19.37 10.17 28.52 5.17 28.60



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 16.67 18.15 4.00 18.42 0.00 18.42 0.00 18.42
February 9.67 18.03 1.67 18.32 0.00 18.32 0.00 18.32
March 0.83 18.89 0.00 18.89 0.00 18.89 0.00 18.89
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 2.33 27.49 1.00 27.48
July 0.00 0.00 0.00 0.00 5.17 27.54 3.83 27.54
August 0.00 0.00 0.00 0.00 3.17 27.40 2.33 27.40
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.50 19.17 0.00 19.17 0.00 19.17 0.00 19.17
November 4.17 18.83 0.50 18.98 0.00 18.98 0.00 18.98
December 12.33 18.44 2.33 18.72 0.00 18.72 0.00 18.72
                 
Annual Sum or Average 44.17 18.29 8.50 18.55 10.67 20.05 7.17 20.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16.67 19.17 4.00 19.17 5.17 27.54 3.83 27.54



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 9.33 17.76 0.00 17.76 0.00 17.76 0.00 17.76
February 6.17 17.98 0.00 17.98 0.00 17.98 0.00 17.98
March 0.50 18.87 0.00 18.87 0.00 18.87 0.00 18.87
April 0.00 0.00 0.00 0.00 1.67 28.10 1.67 28.10
May 0.00 0.00 0.00 0.00 10.00 27.93 10.00 27.93
June 0.00 0.00 0.00 0.00 10.50 28.06 9.33 28.09
July 0.00 0.00 0.00 0.00 18.83 28.27 16.33 28.33
August 0.00 0.00 0.00 0.00 12.17 28.23 10.33 28.28
September 0.00 0.00 0.00 0.00 4.33 28.00 4.17 28.01
October 0.33 19.08 0.00 19.08 1.17 25.96 1.17 26.82
November 2.50 18.72 0.00 18.72 0.00 18.72 0.00 18.72
December 8.67 18.04 0.00 18.04 0.00 18.04 0.00 18.04
                 
Annual Sum or Average 27.50 18.02 0.00 18.02 58.67 24.91 53.00 26.16
Minimum of Months 0.00 0.00 0.00 0.00 0.00 17.76 0.00 17.76
Maximum of Months 9.33 19.08 0.00 19.08 18.83 28.27 16.33 28.33



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.67 18.60 0.00 18.60 3.17 21.79 3.17 23.30
February 3.83 18.69 0.00 18.69 2.17 21.80 2.17 23.26
March 0.50 19.25 0.00 19.25 2.33 26.21 2.33 26.88
April 0.00 0.00 0.00 0.00 1.17 27.63 1.17 27.63
May 0.00 0.00 0.00 0.00 2.17 27.41 2.17 27.41
June 0.00 0.00 0.00 0.00 3.00 27.47 2.33 27.47
July 0.00 0.00 0.00 0.00 10.33 27.65 8.50 27.68
August 0.00 0.00 0.00 0.00 8.83 27.84 6.50 27.90
September 0.00 0.00 0.00 0.00 15.33 26.68 14.67 26.66
October 0.17 18.92 0.00 18.92 25.17 25.85 24.67 25.86
November 0.67 18.92 0.00 18.92 6.83 25.83 6.83 26.15
December 7.33 18.64 0.17 18.68 2.17 20.71 2.17 22.00
                 
Annual Sum or Average 18.17 18.67 0.17 18.68 82.67 25.36 76.67 25.98
Minimum of Months 0.00 0.00 0.00 0.00 1.17 20.71 1.17 22.00
Maximum of Months 7.33 19.25 0.17 19.25 25.17 27.84 24.67 27.90



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.83 18.66 0.00 18.66 0.00 18.66 0.00 18.66
February 3.50 18.61 0.00 18.61 0.00 18.61 0.00 18.61
March 0.17 19.17 0.00 19.17 0.50 25.68 0.33 26.44
April 0.00 0.00 0.00 0.00 4.17 28.08 2.50 28.12
May 0.00 0.00 0.00 0.00 4.83 28.19 3.17 28.24
June 0.00 0.00 0.00 0.00 9.67 28.36 4.50 28.33
July 0.00 0.00 0.00 0.00 12.00 28.30 5.83 28.45
August 0.00 0.00 0.00 0.00 8.83 28.22 4.17 28.33
September 0.00 0.00 0.00 0.00 5.67 28.10 4.00 28.16
October 0.17 19.07 0.00 19.07 2.83 27.52 2.33 27.77
November 1.00 18.93 0.00 18.93 0.00 18.93 0.00 18.93
December 7.17 18.62 0.00 18.62 0.00 18.62 0.00 18.62
                 
Annual Sum or Average 18.83 18.66 0.00 18.66 48.50 25.55 26.83 26.36
Minimum of Months 0.00 0.00 0.00 0.00 0.00 18.61 0.00 18.61
Maximum of Months 7.17 19.17 0.00 19.17 12.00 28.36 5.83 28.45



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 3.00 27.90 1.50 27.90
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 7.17 28.06 2.67 28.05
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   10.17 28.01 4.17 28.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.17 28.06 2.67 28.05



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.33 27.78 1.17 27.77
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 4.83 28.10 1.83 28.05
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   7.17 28.00 3.00 27.95
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 4.83 28.10 1.83 28.05



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.00 27.61 0.50 27.61
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 7.83 28.17 2.83 28.14
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   8.83 28.11 3.33 28.08
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.83 28.17 2.83 28.14



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 252.67 24.01 66.67 24.49 0.00 24.49
February 222.33 24.01 65.00 24.53 0.00 24.53
March 200.83 24.00 64.67 24.55 0.00 24.55
April 183.17 24.00 76.83 24.72 0.00 24.72
May 126.17 24.00 141.00 24.78 0.67 24.77
June 6.33 24.00 290.17 24.83 0.00 24.83
July 112.00 24.48 473.33 24.66 112.00 24.63
August 86.17 24.31 500.50 24.52 86.17 24.50
September 13.83 24.76 375.00 24.79 13.83 24.79
October 73.67 24.00 191.67 25.12 0.00 25.12
November 98.33 24.00 106.83 25.29 0.00 25.29
December 225.83 24.01 86.50 24.71 0.00 24.71
             
Annual Sum or Average 1601.33 24.06 2438.17 24.71 212.67 24.70
Minimum of Months 6.33 24.00 64.67 24.49 0.00 24.49
Maximum of Months 252.67 24.76 500.50 25.29 112.00 25.29



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 347.50 23.92 8.17 23.97 0.00 23.97
February 226.33 23.98 16.83 24.11 0.00 24.11
March 158.33 24.02 33.50 24.35 0.00 24.35
April 143.33 24.02 24.17 24.31 0.00 24.31
May 117.17 24.02 117.67 24.38 1.33 24.38
June 3.67 24.01 280.00 24.31 0.00 24.31
July 159.67 24.35 474.67 24.28 159.67 24.30
August 78.00 24.20 508.83 24.22 78.00 24.21
September 20.00 24.36 367.83 24.43 20.00 24.43
October 88.67 24.00 156.83 24.54 0.00 24.54
November 137.67 24.01 50.67 24.51 0.00 24.51
December 255.00 24.01 38.33 24.28 0.00 24.28
             
Annual Sum or Average 1735.33 24.03 2077.50 24.29 259.00 24.29
Minimum of Months 3.67 23.92 8.17 23.97 0.00 23.97
Maximum of Months 347.50 24.36 508.83 24.54 159.67 24.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 23.22 0.00 23.22 0.00 23.22
February 440.17 23.50 0.00 23.50 0.00 23.50
March 449.50 23.79 0.00 23.79 0.00 23.79
April 347.50 23.92 1.33 23.93 0.00 23.93
May 214.67 23.93 67.33 24.05 1.50 24.05
June 43.00 23.90 212.50 24.22 0.00 24.22
July 158.83 24.14 458.50 24.19 158.83 24.18
August 105.50 24.14 468.83 24.19 105.50 24.18
September 25.67 24.24 312.00 24.32 20.50 24.32
October 235.33 23.80 86.33 23.97 1.83 23.97
November 435.83 23.72 0.00 23.72 0.00 23.72
December 497.00 23.26 0.00 23.26 0.00 23.26
             
Annual Sum or Average 3455.00 23.64 1606.83 23.84 288.17 23.85
Minimum of Months 25.67 23.22 0.00 23.22 0.00 23.22
Maximum of Months 502.00 24.24 468.83 24.32 158.83 24.32



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.52 173.67 21.21 173.67 21.03
February 454.00 22.07 84.33 21.84 84.33 21.68
March 507.50 23.02 13.00 22.97 13.00 22.91
April 390.83 23.66 0.83 23.66 0.00 23.66
May 217.33 23.72 65.33 23.88 1.83 23.88
June 39.83 23.74 246.17 24.21 0.00 24.21
July 153.83 24.20 470.17 24.26 153.83 24.25
August 101.83 24.21 489.17 24.24 101.83 24.23
September 52.50 23.87 290.50 24.21 23.33 24.21
October 328.33 23.21 73.33 23.39 4.67 23.38
November 471.83 22.40 58.50 22.22 58.50 22.07
December 497.00 21.53 174.83 21.25 174.83 21.09
             
Annual Sum or Average 3716.83 22.65 2139.83 22.92 789.83 22.78
Minimum of Months 39.83 21.52 0.83 21.21 0.00 21.03
Maximum of Months 507.50 24.21 489.17 24.26 174.83 24.25



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 22.29 14.67 22.25 14.67 22.21
February 451.83 22.80 8.33 22.77 8.33 22.74
March 480.67 23.51 0.00 23.51 0.00 23.51
April 317.67 23.89 6.50 23.92 0.00 23.92
May 166.50 23.87 102.67 24.20 1.00 24.20
June 3.83 24.31 352.00 24.45 0.50 24.45
July 108.00 25.08 492.17 24.58 108.00 24.66
August 55.67 24.59 507.83 24.36 55.67 24.38
September 38.83 24.02 327.33 24.39 14.50 24.39
October 298.33 23.54 96.00 23.74 0.00 23.74
November 464.67 23.27 0.00 23.27 0.00 23.27
December 497.00 22.63 5.00 22.61 5.00 22.59
             
Annual Sum or Average 3385.00 23.20 1912.50 23.63 207.67 23.66
Minimum of Months 3.83 22.29 0.00 22.25 0.00 22.21
Maximum of Months 502.00 25.08 507.83 24.58 108.00 24.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 468.67 22.39 26.83 22.38 20.00 22.32
February 395.83 22.76 15.17 22.80 6.83 22.77
March 340.00 23.24 34.17 23.41 0.67 23.42
April 186.83 23.76 92.00 24.16 5.33 24.23
May 126.50 24.25 207.50 24.58 21.50 24.72
June 31.33 25.99 388.67 24.56 22.50 24.68
July 121.17 25.59 487.17 24.72 121.17 24.86
August 75.83 25.38 501.67 24.46 74.50 24.57
September 51.67 24.74 389.83 24.49 28.83 24.57
October 211.50 23.34 163.17 23.95 5.67 24.00
November 398.50 23.06 18.67 23.18 0.00 23.18
December 472.33 22.46 21.33 22.42 19.50 22.36
             
Annual Sum or Average 2880.17 23.18 2346.17 23.76 326.50 23.84
Minimum of Months 31.33 22.39 15.17 22.38 0.00 22.32
Maximum of Months 472.33 25.99 501.67 24.72 121.17 24.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 328.50 22.79 91.33 23.18 24.33 23.13
February 256.50 23.10 80.50 23.50 12.17 23.49
March 279.17 23.51 51.67 23.77 2.00 23.80
April 182.33 23.79 48.00 24.16 0.67 24.17
May 157.50 23.78 131.33 24.24 2.50 24.25
June 26.33 24.22 319.50 24.43 3.83 24.45
July 116.00 25.26 487.17 24.64 116.00 24.74
August 71.67 25.30 510.17 24.52 71.67 24.61
September 53.67 25.84 405.33 24.77 45.00 24.90
October 134.17 24.05 254.83 24.62 23.33 24.77
November 237.67 23.63 119.83 24.16 9.17 24.24
December 296.33 23.07 84.50 23.47 12.83 23.48
             
Annual Sum or Average 2139.83 23.60 2584.17 24.17 323.50 24.24
Minimum of Months 26.33 22.79 48.00 23.18 0.67 23.13
Maximum of Months 328.50 25.84 510.17 24.77 116.00 24.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 416.67 22.72 13.50 22.82 0.00 22.82
February 275.00 23.33 54.00 23.63 0.67 23.64
March 118.67 23.94 117.50 24.60 8.33 24.70
April 35.50 25.78 219.50 25.35 20.17 25.48
May 64.17 24.44 265.83 24.72 14.50 24.81
June 26.17 26.84 448.50 24.70 25.00 24.81
July 126.50 25.71 497.00 24.86 126.50 25.00
August 90.83 25.83 514.00 24.74 90.83 24.88
September 34.50 26.00 431.67 24.72 34.50 24.81
October 106.67 24.05 242.83 24.61 14.67 24.71
November 152.00 23.81 84.33 24.35 3.00 24.39
December 260.17 23.71 55.00 24.05 1.33 24.07
             
Annual Sum or Average 1706.83 23.88 2943.67 24.44 339.50 24.56
Minimum of Months 26.17 22.72 13.50 22.82 0.00 22.82
Maximum of Months 416.67 26.84 514.00 25.35 126.50 25.48



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.76 343.50 20.63 343.50 20.58
February 454.00 21.21 198.33 21.02 198.33 20.92
March 514.00 22.31 55.83 22.17 55.83 22.05
April 439.17 23.35 0.83 23.35 0.83 23.34
May 254.83 23.65 63.00 23.81 1.17 23.82
June 20.83 23.63 289.33 24.40 0.00 24.40
July 117.00 24.61 487.00 24.49 117.00 24.51
August 74.33 24.26 487.67 24.31 72.83 24.30
September 78.83 23.61 251.00 24.15 13.33 24.14
October 383.17 22.64 73.33 22.73 22.83 22.65
November 489.00 21.61 137.50 21.41 137.50 21.28
December 497.00 20.68 383.83 20.59 383.83 20.56
             
Annual Sum or Average 3824.17 22.06 2771.17 22.37 1347.00 22.16
Minimum of Months 20.83 20.68 0.83 20.59 0.00 20.56
Maximum of Months 514.00 24.61 487.67 24.49 383.83 24.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 21.29 201.17 21.07 201.17 20.96
February 370.17 21.68 97.17 21.48 95.50 21.33
March 364.83 22.61 26.17 22.69 10.83 22.65
April 197.83 23.46 75.83 24.01 4.67 24.07
May 147.83 24.04 157.83 24.53 24.00 24.71
June 45.17 25.46 309.67 24.75 25.50 24.91
July 112.50 25.85 410.33 24.97 112.50 25.12
August 76.00 25.62 415.00 24.70 73.83 24.83
September 70.50 24.29 290.00 24.50 27.17 24.60
October 240.67 22.83 118.67 23.39 13.00 23.37
November 388.83 22.07 44.17 22.00 37.67 21.90
December 422.00 21.12 228.67 20.92 228.67 20.82
             
Annual Sum or Average 2863.33 22.44 2374.67 23.01 854.50 22.92
Minimum of Months 45.17 21.12 26.17 20.92 4.67 20.82
Maximum of Months 427.00 25.85 415.00 24.97 228.67 25.12



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 343.83 22.44 152.33 22.73 78.83 22.57
February 274.50 22.68 99.00 23.09 29.17 23.02
March 325.83 23.10 52.50 23.35 7.33 23.36
April 242.33 23.51 35.83 23.81 0.50 23.81
May 196.00 23.62 100.83 24.02 1.67 24.02
June 52.67 23.71 283.17 24.34 1.17 24.35
July 121.67 25.01 479.67 24.61 121.67 24.68
August 77.83 25.13 500.83 24.53 77.83 24.60
September 69.17 25.48 387.50 24.78 50.17 24.92
October 168.83 23.85 251.17 24.54 33.67 24.69
November 269.00 23.22 129.83 23.83 23.67 23.90
December 320.00 22.47 151.33 22.67 81.67 22.50
             
Annual Sum or Average 2461.67 23.26 2624.00 23.88 507.33 23.89
Minimum of Months 52.67 22.44 35.83 22.67 0.50 22.50
Maximum of Months 343.83 25.48 500.83 24.78 121.67 24.92



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 482.83 21.42 179.33 21.21 179.33 21.10
February 400.67 21.80 82.00 21.68 76.67 21.56
March 423.83 22.54 37.17 22.68 9.50 22.66
April 268.67 23.41 72.33 23.77 7.17 23.84
May 162.00 23.56 175.67 24.16 10.50 24.24
June 48.00 24.57 366.50 24.56 17.17 24.66
July 125.67 24.87 495.00 24.59 125.67 24.64
August 77.00 24.87 510.17 24.48 77.00 24.53
September 68.33 24.37 354.67 24.49 30.67 24.58
October 274.50 22.79 128.67 23.33 11.50 23.36
November 431.50 22.12 40.00 22.10 29.50 22.02
December 485.50 21.45 197.67 21.26 197.67 21.15
             
Annual Sum or Average 3248.50 22.42 2639.17 23.06 772.33 22.98
Minimum of Months 48.00 21.42 37.17 21.21 7.17 21.10
Maximum of Months 485.50 24.87 510.17 24.59 197.67 24.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.10 455.50 20.05 455.50 20.02
February 454.00 20.52 330.83 20.38 330.83 20.32
March 514.00 21.58 176.17 21.31 176.17 21.15
April 436.83 22.88 39.00 22.71 39.00 22.56
May 267.17 23.31 72.00 23.52 9.00 23.46
June 48.67 23.66 306.67 24.35 3.83 24.38
July 120.83 24.93 489.17 24.58 120.83 24.64
August 80.33 24.44 487.33 24.36 75.50 24.38
September 129.17 23.40 235.67 23.99 16.50 23.99
October 410.00 22.08 136.50 22.00 94.83 21.82
November 489.00 20.74 309.00 20.51 309.00 20.41
December 497.00 20.06 479.50 20.04 479.50 20.03
             
Annual Sum or Average 3949.00 21.53 3517.33 21.81 2110.50 21.55
Minimum of Months 48.67 20.06 39.00 20.04 3.83 20.02
Maximum of Months 514.00 24.93 489.17 24.58 479.50 24.64



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.59 353.83 20.42 353.83 20.35
February 452.50 21.14 203.17 20.84 203.17 20.69
March 451.17 22.27 86.33 22.07 81.00 21.89
April 216.67 23.17 87.33 23.62 13.83 23.57
May 166.33 23.89 197.50 24.37 30.17 24.54
June 56.17 25.22 395.50 24.61 29.67 24.76
July 127.67 25.66 490.50 24.84 127.67 24.98
August 88.50 25.43 498.33 24.60 84.00 24.72
September 93.33 24.00 353.17 24.33 33.17 24.42
October 296.83 22.54 148.17 22.87 44.33 22.74
November 480.83 21.44 178.83 21.15 177.00 20.99
December 497.00 20.41 376.00 20.28 376.00 20.22
             
Annual Sum or Average 3429.00 21.95 3368.67 22.46 1553.83 22.26
Minimum of Months 56.17 20.41 86.33 20.28 13.83 20.22
Maximum of Months 502.00 25.66 498.33 24.84 376.00 24.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 376.33 21.57 211.83 21.50 170.00 21.24
February 313.33 21.87 157.67 21.84 112.33 21.59
March 370.50 22.45 104.33 22.41 70.50 22.21
April 276.00 23.04 60.50 23.14 25.83 22.99
May 228.50 23.27 106.50 23.68 11.00 23.64
June 75.33 23.54 290.00 24.27 5.67 24.31
July 119.17 25.09 480.17 24.63 119.17 24.71
August 81.17 25.07 496.50 24.53 78.17 24.60
September 96.33 24.71 361.00 24.62 49.67 24.77
October 207.17 23.13 243.00 23.84 50.00 23.82
November 316.50 22.31 140.17 22.48 69.33 22.23
December 357.67 21.56 184.83 21.38 157.83 21.11
             
Annual Sum or Average 2818.00 22.61 2836.50 23.16 919.50 22.99
Minimum of Months 75.33 21.56 60.50 21.38 5.67 21.11
Maximum of Months 376.33 25.09 496.50 24.63 170.00 24.77



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 496.50 20.85 321.17 20.60 321.17 20.49
February 416.17 21.24 194.17 20.99 192.50 20.85
March 438.00 21.91 114.00 21.87 91.17 21.72
April 292.83 22.91 84.50 23.23 22.67 23.22
May 201.00 23.17 167.50 23.83 15.50 23.89
June 71.17 24.08 363.17 24.47 20.00 24.58
July 118.50 24.94 493.67 24.60 118.50 24.65
August 77.17 24.89 503.67 24.48 75.33 24.54
September 110.00 23.79 325.00 24.31 33.50 24.40
October 311.83 22.32 155.67 22.71 52.00 22.60
November 455.83 21.45 159.17 21.21 153.83 21.05
December 494.67 20.90 336.83 20.66 336.83 20.56
             
Annual Sum or Average 3483.67 21.94 3218.50 22.47 1433.00 22.27
Minimum of Months 71.17 20.85 84.50 20.60 15.50 20.49
Maximum of Months 496.50 24.94 503.67 24.60 336.83 24.65



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 27.00 0.00 27.00
February 1.17 27.00 454.00 27.00 1.17 27.00
March 9.83 27.00 514.00 27.00 9.83 27.00
April 18.83 27.11 485.00 27.01 18.83 27.01
May 0.00 0.00 508.00 27.00 0.00 27.00
June 10.50 27.00 496.00 27.00 10.50 27.00
July 86.50 27.00 497.00 27.00 86.50 27.00
August 161.33 27.06 514.00 27.03 161.33 27.03
September 6.33 27.00 485.00 27.00 6.33 27.00
October 16.33 27.00 502.00 27.00 16.33 27.00
November 10.17 27.00 489.00 27.00 10.17 27.00
December 6.50 27.00 497.00 27.00 6.50 27.00
             
Annual Sum or Average 327.50 27.04 5943.00 27.00 327.50 27.01
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 161.33 27.11 514.00 27.03 161.33 27.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 448.17 27.00 0.00 27.00
February 0.00 0.00 437.33 27.00 0.00 27.00
March 0.00 0.00 514.00 27.00 0.00 27.00
April 2.17 27.39 485.00 27.00 2.17 27.01
May 0.00 0.00 508.00 27.00 0.00 27.00
June 2.00 27.00 496.00 27.00 2.00 27.00
July 6.50 27.00 497.00 27.00 6.50 27.00
August 23.00 27.26 514.00 27.03 23.00 27.04
September 1.00 27.00 485.00 27.00 1.00 27.00
October 3.50 27.00 502.00 27.00 3.50 27.00
November 0.00 0.00 489.00 27.00 0.00 27.00
December 0.00 0.00 454.67 27.00 0.00 27.00
             
Annual Sum or Average 38.17 27.18 5830.17 27.00 38.17 27.00
Minimum of Months 0.00 0.00 437.33 27.00 0.00 27.00
Maximum of Months 23.00 27.39 514.00 27.03 23.00 27.04



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 88.67 25.54 242.00 26.61 0.00 26.61
February 8.33 27.00 322.17 27.00 0.00 27.00
March 0.00 0.00 474.33 27.00 0.00 27.00
April 3.00 27.09 485.00 27.00 3.00 27.00
May 0.00 0.00 502.67 27.00 0.00 27.00
June 7.50 27.00 496.00 27.00 7.50 27.00
July 27.00 27.00 497.00 27.00 27.00 27.00
August 52.50 27.12 514.00 27.02 52.50 27.03
September 4.00 27.00 485.00 27.00 4.00 27.00
October 6.17 27.00 482.67 27.00 6.17 27.00
November 0.00 0.00 412.50 27.00 0.00 27.00
December 11.50 27.00 284.67 27.00 0.00 27.00
             
Annual Sum or Average 208.67 26.41 5198.00 26.98 100.17 26.98
Minimum of Months 0.00 0.00 242.00 26.61 0.00 26.61
Maximum of Months 88.67 27.12 514.00 27.02 52.50 27.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 27.00 502.00 27.00 502.00 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.00 485.00 27.00 485.00 27.00
May 508.00 27.00 508.00 27.00 508.00 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 27.00 514.00 27.00 514.00 27.00
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.00 497.00 27.00 497.00 27.00
             
Annual Sum or Average 5943.00 27.00 5943.00 27.00 5943.00 27.00
Minimum of Months 454.00 27.00 454.00 27.00 454.00 27.00
Maximum of Months 514.00 27.00 514.00 27.00 514.00 27.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00000 16.92504 0.71259 15.76836
February 454.00000 27.00002 17.37891 0.77453 17.72414
March 514.00000 27.00002 18.03988 0.83420 19.74026
April 485.00000 27.00437 16.80465 0.87930 21.37773
May 508.00000 27.00018 20.10901 0.14226 5.51504
June 496.00000 27.00042 24.15475 0.24241 6.28982
July 497.00000 27.00058 26.21642 0.31339 7.09790
August 514.00000 27.01852 25.78620 0.35469 7.70139
September 485.00000 27.00075 25.51858 0.20389 5.93691
October 502.00000 27.00027 20.86676 0.84681 20.22473
November 489.00000 27.00004 18.19698 0.83320 19.71092
December 497.00000 26.99999 14.76282 0.81552 19.09825
           
Annual Sum or Average 5943.00000 27.00215 20.42336 0.57747 13.80572
Minimum of Months 454.00000 26.99999 14.76282 0.14226 5.51504
Maximum of Months 514.00000 27.01852 26.21642 0.87930 21.37773



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00000 16.90850 0.60525 12.80251
February 454.00000 27.00002 17.36272 0.65486 14.15596
March 514.00000 27.00002 18.01511 0.71722 15.93749
April 485.00000 27.00292 16.78152 0.77167 17.64657
May 508.00000 27.00016 20.12372 0.07667 5.25622
June 496.00000 27.00040 24.16324 0.16423 5.65493
July 497.00000 27.00057 26.23903 0.21619 6.03843
August 514.00000 27.01555 25.80417 0.23760 6.26836
September 485.00000 27.00066 25.62470 0.14156 5.51166
October 502.00000 27.00025 20.86678 0.76302 17.42075
November 489.00000 27.00004 18.18106 0.69924 15.40197
December 497.00000 26.99999 14.74201 0.63090 13.49268
           
Annual Sum or Average 5943.00000 27.00176 20.42772 0.47135 11.26669
Minimum of Months 454.00000 26.99999 14.74201 0.07667 5.25622
Maximum of Months 514.00000 27.01555 26.23903 0.77167 17.64657



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.69800 17.15544 0.46289 10.26684
February 454.00000 27.00002 17.37824 0.57836 12.28650
March 514.00000 27.00002 18.03095 0.66262 14.45929
April 485.00000 27.00142 16.79445 0.74834 16.99859
May 508.00000 27.00015 20.14622 0.06836 5.36584
June 496.00000 27.00042 24.17406 0.17808 5.84672
July 497.00000 27.00060 26.24038 0.24071 6.33672
August 514.00000 27.01265 25.81001 0.25557 6.52496
September 485.00000 27.00066 25.64125 0.13988 5.59524
October 502.00000 27.00026 20.88779 0.72664 16.41156
November 489.00000 27.00004 18.19495 0.62133 13.33694
December 497.00000 26.99999 14.75228 0.54056 11.36629
           
Annual Sum or Average 5943.00000 26.97588 20.46076 0.43373 10.37532
Minimum of Months 454.00000 26.69800 14.75228 0.06836 5.36584
Maximum of Months 514.00000 27.01265 26.24038 0.74834 16.99859



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00000 33.85744 1.07174 29.24322
February 454.00000 27.00000 33.64505 1.23153 36.80775
March 514.00000 27.00000 33.52481 1.38186 44.54930
April 485.00000 27.00000 33.51225 1.52406 52.20919
May 508.00000 27.00000 33.77038 0.50676 10.40475
June 496.00000 27.00000 33.72073 0.73679 16.43721
July 497.00000 27.00000 33.67396 0.95066 24.09759
August 514.00000 27.00000 33.67602 1.14820 32.76044
September 485.00000 27.00000 33.88929 0.56185 11.63952
October 502.00000 27.00000 33.64258 1.28029 39.26222
November 489.00000 27.00000 33.74224 1.41142 46.12276
December 497.00000 27.00000 33.64332 1.52923 52.49006
           
Annual Sum or Average 5943.00000 27.00000 33.69146 1.11013 32.95656
Minimum of Months 454.00000 27.00000 33.51225 0.50676 10.40475
Maximum of Months 514.00000 27.00000 33.88929 1.52923 52.49006



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.52243 14.69933 0.29420 7.23309
February 454.00000 24.52245 15.74186 0.30317 7.33991
March 514.00000 24.45878 15.54202 0.29577 7.12991
April 485.00000 24.56250 13.88142 0.31007 7.46523
May 508.00000 24.54402 21.37319 -0.4943 11.14936
June 496.00000 24.51656 32.24980 -0.4151 9.47646
July 497.00000 24.67524 45.95193 -0.2626 7.65614
August 514.00000 24.54632 45.62962 -0.2942 7.78130
September 485.00000 24.62019 37.67845 -0.3336 8.64193
October 502.00000 24.66318 22.80700 0.40920 9.28191
November 489.00000 24.63568 16.13749 0.35123 8.19075
December 497.00000 24.60743 12.57612 0.31081 7.56107
           
Annual Sum or Average 5943.00000 24.57269 24.60994 0.03682 8.25031
Minimum of Months 454.00000 24.45878 12.57612 -0.4943 7.12991
Maximum of Months 514.00000 24.67524 45.95193 0.40920 11.14936



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.14237 16.66964 0.21795 6.15893
February 454.00000 24.25423 17.34732 0.25874 6.56839
March 514.00000 24.26956 16.59533 0.27802 6.77633
April 485.00000 24.28958 14.47580 0.28359 6.83591
May 508.00000 24.26322 22.80248 -0.5442 11.66777
June 496.00000 24.21836 33.64761 -0.4610 9.70712
July 497.00000 24.25209 47.96737 -0.3365 7.62166
August 514.00000 24.21535 46.41284 -0.3514 7.74637
September 485.00000 24.33903 38.91351 -0.3967 8.84002
October 502.00000 24.35497 23.85115 0.35667 8.03789
November 489.00000 24.33603 17.14291 0.29694 7.05445
December 497.00000 24.34880 14.10273 0.26666 6.73185
           
Annual Sum or Average 5943.00000 24.27329 25.91313 -0.0137 7.82460
Minimum of Months 454.00000 24.14237 14.10273 -0.5442 6.15893
Maximum of Months 514.00000 24.35497 47.96737 0.35667 11.66777



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.21979 18.61313 -0.0259 5.52082
February 454.00000 23.52385 19.30329 0.05825 5.47545
March 514.00000 23.86345 18.03972 0.15010 5.68895
April 485.00000 24.07878 15.37087 0.19915 5.97631
May 508.00000 24.11526 23.35093 -0.6202 13.43775
June 496.00000 24.14557 33.77658 -0.5219 10.95454
July 497.00000 24.19764 47.82869 -0.4004 8.57825
August 514.00000 24.17938 46.84510 -0.4118 8.75245
September 485.00000 24.21077 39.45089 -0.4665 9.90128
October 502.00000 24.05368 24.81127 0.25953 6.81187
November 489.00000 23.78216 19.10775 0.13181 5.64321
December 497.00000 23.26131 16.74541 -0.0272 5.48972
           
Annual Sum or Average 5943.00000 23.88842 27.01574 -0.1418 7.70848
Minimum of Months 454.00000 23.21979 15.37087 -0.6202 5.47545
Maximum of Months 514.00000 24.21077 47.82869 0.25953 13.43775



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.51933 20.44558 -0.4535 11.00686
February 454.00000 22.06912 21.15224 -0.3055 8.48883
March 514.00000 23.03433 19.48688 -0.0623 6.16974
April 485.00000 23.77313 15.67567 0.11955 5.80370
May 508.00000 24.01082 23.15587 -0.6545 14.73557
June 496.00000 24.15299 33.79457 -0.5003 10.57824
July 497.00000 24.26917 47.79006 -0.3499 7.89802
August 514.00000 24.22895 46.68149 -0.3757 8.23161
September 485.00000 24.15138 39.17230 -0.4834 10.26246
October 502.00000 23.53140 25.64237 0.12244 6.57551
November 489.00000 22.45770 21.34320 -0.2011 7.36347
December 497.00000 21.52881 18.47461 -0.4633 10.97698
           
Annual Sum or Average 5943.00000 23.23614 27.80527 -0.3011 9.01712
Minimum of Months 454.00000 21.51933 15.67567 -0.6545 5.80370
Maximum of Months 514.00000 24.26917 47.79006 0.12244 14.73557



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.28788 17.99868 -0.2491 6.98790
February 454.00000 22.80966 18.52441 -0.1179 6.13441
March 514.00000 23.55254 17.06576 0.06635 5.56494
April 485.00000 24.03128 14.21429 0.19321 6.03841
May 508.00000 24.18891 22.21573 -0.5816 12.89746
June 496.00000 24.34064 32.55295 -0.3898 8.75740
July 497.00000 24.47172 46.50598 -0.2266 6.92688
August 514.00000 24.33361 45.29783 -0.2920 7.32538
September 485.00000 24.30633 38.14746 -0.4223 9.44906
October 502.00000 23.83151 24.03623 0.19658 6.66682
November 489.00000 23.30968 18.13508 0.00598 5.48284
December 497.00000 22.62573 15.41444 -0.1833 6.28734
           
Annual Sum or Average 5943.00000 23.68022 25.91895 -0.1677 7.39036
Minimum of Months 454.00000 22.28788 14.21429 -0.5816 5.48284
Maximum of Months 514.00000 24.47172 46.50598 0.19658 12.89746



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.54340 16.87981 -0.1655 7.01175
February 454.00000 22.97272 17.51810 -0.0471 6.44683
March 514.00000 23.58878 16.39257 0.12619 6.39979
April 485.00000 24.10097 13.66456 0.28710 7.66313
May 508.00000 24.31031 21.61345 -0.4350 11.27275
June 496.00000 24.34878 32.32884 -0.2823 8.14444
July 497.00000 24.49103 46.24439 -0.1247 7.44066
August 514.00000 24.30793 45.12849 -0.2066 7.38138
September 485.00000 24.34617 37.70899 -0.3110 8.54956
October 502.00000 23.94871 23.31582 0.27954 8.31098
November 489.00000 23.30953 17.34345 0.04356 6.13087
December 497.00000 22.56373 14.58903 -0.1720 6.83570
           
Annual Sum or Average 5943.00000 23.74148 25.30697 -0.0848 7.64346
Minimum of Months 454.00000 22.54340 13.66456 -0.4350 6.13087
Maximum of Months 514.00000 24.49103 46.24439 0.28710 11.27275



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.40681 15.90143 0.07206 8.11083
February 454.00000 23.67520 16.45404 0.15581 7.66254
March 514.00000 23.88208 15.99228 0.20270 6.98431
April 485.00000 24.17124 13.69905 0.27286 7.24471
May 508.00000 24.20941 22.03840 -0.5519 12.77345
June 496.00000 24.30393 32.59092 -0.4034 9.16941
July 497.00000 24.48581 46.40098 -0.2038 7.02955
August 514.00000 24.40602 44.91296 -0.2095 6.94011
September 485.00000 24.52465 37.19258 -0.2407 7.97597
October 502.00000 24.38216 22.52386 0.42255 10.64493
November 489.00000 24.07619 16.16408 0.27354 8.28322
December 497.00000 23.61789 13.43862 0.12969 7.81097
           
Annual Sum or Average 5943.00000 24.09728 24.86160 -0.0088 8.39585
Minimum of Months 454.00000 23.40681 13.43862 -0.5519 6.94011
Maximum of Months 514.00000 24.52465 46.40098 0.42255 12.77345



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.01051 16.02265 -0.0295 6.21289
February 454.00000 23.78537 16.28093 0.18298 6.78327
March 514.00000 24.30297 15.34537 0.34395 8.18271
April 485.00000 24.59503 13.12222 0.46940 10.53495
May 508.00000 24.40959 21.53200 -0.3753 9.65784
June 496.00000 24.51408 31.96864 -0.1750 7.27197
July 497.00000 24.64560 45.74595 0.00979 6.82856
August 514.00000 24.55204 44.35439 -0.0075 6.51850
September 485.00000 24.54629 37.16342 -0.2019 7.58738
October 502.00000 24.38506 22.54871 0.42838 10.06690
November 489.00000 24.26086 15.88698 0.31549 7.70648
December 497.00000 24.15274 12.86629 0.24622 6.98093
           
Annual Sum or Average 5943.00000 24.26578 24.48634 0.09929 7.86517
Minimum of Months 454.00000 23.01051 12.86629 -0.3753 6.21289
Maximum of Months 514.00000 24.64560 45.74595 0.46940 10.53495



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.76264 19.40334 -0.6435 14.51990
February 454.00000 21.21106 20.36370 -0.5157 11.54936
March 514.00000 22.31285 19.00471 -0.2389 7.36043
April 485.00000 23.43404 15.39713 0.02785 5.87740
May 508.00000 23.94137 22.85827 -0.6872 16.02737
June 496.00000 24.28079 32.44489 -0.4412 9.66609
July 497.00000 24.45394 46.10640 -0.2709 7.24644
August 514.00000 24.29516 45.44864 -0.3481 7.97621
September 485.00000 24.11907 38.70862 -0.5102 11.13552
October 502.00000 22.98477 25.42754 -0.0171 6.96524
November 489.00000 21.61342 20.16721 -0.4043 9.55169
December 497.00000 20.67745 17.37597 -0.6793 15.41172
           
Annual Sum or Average 5943.00000 22.85303 26.96243 -0.3936 10.26946
Minimum of Months 454.00000 20.67745 15.39713 -0.6872 5.87740
Maximum of Months 514.00000 24.45394 46.10640 0.02785 16.02737



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 21.28751 17.49322 -0.4985 11.48416
February 385.00000 21.79180 18.29160 -0.3509 9.40225
March 433.00000 22.90694 16.89166 -0.0569 6.90120
April 410.00000 24.01781 13.63910 0.24057 7.76137
May 430.00000 24.26833 21.69318 -0.4701 12.95532
June 418.00000 24.45323 31.36023 -0.2748 8.69439
July 422.00000 24.70659 44.65120 -0.0843 8.00964
August 433.00000 24.49523 44.04292 -0.1780 7.74574
September 410.00000 24.31712 37.29350 -0.3506 9.63391
October 427.00000 23.54774 23.27826 0.16168 8.19456
November 417.00000 22.23138 18.20214 -0.2288 7.69895
December 422.00000 21.12323 15.64549 -0.5477 12.45135
           
Annual Sum or Average 5034.00000 23.27065 25.26636 -0.2195 9.24650
Minimum of Months 385.00000 21.12323 13.63910 -0.5477 6.90120
Maximum of Months 433.00000 24.70659 44.65120 0.24057 12.95532



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.13261 16.30228 0.00079 9.37870
February 454.00000 23.39670 17.06381 0.08563 8.46708
March 514.00000 23.55252 16.69724 0.11651 7.15986
April 485.00000 23.95875 14.12049 0.20420 6.95403
May 508.00000 24.07621 22.41089 -0.6123 14.50931
June 496.00000 24.25270 32.44407 -0.4491 10.09001
July 497.00000 24.49732 45.90412 -0.2365 7.30971
August 514.00000 24.42643 44.83898 -0.2377 7.28802
September 485.00000 24.51111 37.12327 -0.2540 8.44447
October 502.00000 24.31642 22.64912 0.40180 11.05169
November 489.00000 23.82703 16.73704 0.21074 8.83396
December 497.00000 23.17334 14.37331 0.01304 8.97371
           
Annual Sum or Average 5943.00000 23.92973 25.13927 -0.0652 9.04974
Minimum of Months 454.00000 23.13261 14.12049 -0.6123 6.95403
Maximum of Months 514.00000 24.51111 45.90412 0.40180 14.50931



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.51787 17.68267 -0.4251 10.52553
February 454.00000 22.08748 18.43858 -0.2614 8.61342
March 514.00000 22.87262 17.37725 -0.0522 6.93346
April 485.00000 23.86594 14.19568 0.20807 7.38784
May 508.00000 24.08355 22.25791 -0.5349 13.39919
June 496.00000 24.35732 32.13775 -0.3114 8.97680
July 497.00000 24.51923 45.78587 -0.1440 7.00983
August 514.00000 24.41908 44.83869 -0.1884 7.03935
September 485.00000 24.29946 37.76984 -0.3385 9.25930
October 502.00000 23.46483 23.88854 0.16341 8.06779
November 489.00000 22.36955 18.32892 -0.1798 7.42743
December 497.00000 21.51531 15.67161 -0.4371 10.68220
           
Annual Sum or Average 5943.00000 23.28971 25.77430 -0.2086 8.78083
Minimum of Months 454.00000 21.51531 14.19568 -0.5349 6.93346
Maximum of Months 514.00000 24.51923 45.78587 0.20807 13.39919



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.10174 20.29503 -0.8586 22.67761
February 454.00000 20.52086 21.25307 -0.7256 17.85307
March 514.00000 21.57923 19.82541 -0.4350 10.77941
April 485.00000 23.00758 15.65380 -0.0792 6.88048
May 508.00000 23.75438 22.89255 -0.7496 18.97811
June 496.00000 24.25785 32.69095 -0.4319 9.97207
July 497.00000 24.48848 46.31481 -0.2344 7.17826
August 514.00000 24.31466 45.51303 -0.3248 7.96236
September 485.00000 23.99619 38.66563 -0.5494 12.54816
October 502.00000 22.44633 25.99053 -0.1600 8.68109
November 489.00000 20.73876 21.41330 -0.6474 15.89389
December 497.00000 20.06395 18.09829 -0.8880 23.67018
           
Annual Sum or Average 5943.00000 22.45412 27.45106 -0.5057 13.56122
Minimum of Months 454.00000 20.06395 15.65380 -0.8880 6.88048
Maximum of Months 514.00000 24.48848 46.31481 -0.0792 23.67018



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.58766 18.95136 -0.7057 17.24530
February 454.00000 21.15089 19.77584 -0.5322 13.38956
March 514.00000 22.51241 17.93836 -0.1669 8.02382
April 485.00000 23.84645 13.83817 0.20455 7.67319
May 508.00000 24.15523 21.56758 -0.4885 13.48864
June 496.00000 24.37617 32.15177 -0.2538 8.45719
July 497.00000 24.61923 45.72792 -0.0553 7.67892
August 514.00000 24.42668 44.83798 -0.1494 7.45381
September 485.00000 24.20257 37.56974 -0.3583 9.82308
October 502.00000 23.25254 24.08243 0.08585 8.44192
November 489.00000 21.47798 19.77066 -0.4325 10.98286
December 497.00000 20.41267 16.98397 -0.7585 18.98807
           
Annual Sum or Average 5943.00000 22.93215 26.16866 -0.2995 10.95173
Minimum of Months 454.00000 20.41267 13.83817 -0.7585 7.45381
Maximum of Months 514.00000 24.61923 45.72792 0.20455 18.98807



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.32618 17.33461 -0.2385 11.95968
February 454.00000 22.64831 18.11108 -0.1299 10.32625
March 514.00000 22.97377 17.52250 -0.0443 8.25585
April 485.00000 23.61139 14.35043 0.11579 7.35031
May 508.00000 23.86408 22.46264 -0.6798 17.49965
June 496.00000 24.18484 32.77569 -0.4519 10.77158
July 497.00000 24.49680 46.22696 -0.2091 7.33041
August 514.00000 24.41538 45.00848 -0.2207 7.40037
September 485.00000 24.38789 37.10051 -0.2891 9.35822
October 502.00000 23.90913 23.07579 0.29006 10.61674
November 489.00000 23.08850 17.93957 0.00123 9.29710
December 497.00000 22.35774 15.31126 -0.2285 12.10751
           
Annual Sum or Average 5943.00000 23.52781 25.68194 -0.1750 10.19887
Minimum of Months 454.00000 22.32618 14.35043 -0.6798 7.33041
Maximum of Months 514.00000 24.49680 46.22696 0.29006 17.49965



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.88005 18.51324 -0.6230 15.99058
February 454.00000 21.47859 19.22917 -0.4420 12.23464
March 514.00000 22.28312 18.05292 -0.2109 8.69936
April 485.00000 23.50089 14.34979 0.11761 7.75552
May 508.00000 23.86727 22.28059 -0.6019 16.23381
June 496.00000 24.28183 32.48672 -0.3150 9.71853
July 497.00000 24.51027 46.14620 -0.1200 7.21159
August 514.00000 24.40387 45.01753 -0.1734 7.22642
September 485.00000 24.15633 37.79914 -0.3786 10.48925
October 502.00000 23.04976 24.28984 0.05179 8.69747
November 489.00000 21.62658 19.40885 -0.3838 10.72604
December 497.00000 20.91152 16.37115 -0.6293 15.97876
           
Annual Sum or Average 5943.00000 22.92332 26.23618 -0.3085 10.90700
Minimum of Months 454.00000 20.88005 14.34979 -0.6293 7.21159
Maximum of Months 514.00000 24.51027 46.14620 0.11761 16.23381



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.235421E+10 35654.32 05-JAN-15:00 70.88 0.121118E+11 0.00 0.144661E+11 0.49 6.00 05-JAN-15:00 0.00 0.00
February 0.479864E+10 69027.07 14-FEB-16:40 102.82 0.306843E+11 0.00 0.354830E+11 0.83 7.70 14-FEB-14:20 0.00 0.00
March 0.145747E+11 73571.97 08-MAR-16:20 161.80 0.887446E+11 0.00 0.103319E+12 1.22 7.69 13-MAR-14:10 0.00 0.00
April 0.389963E+11 81624.34 28-APR-14:00 295.14 0.268193E+12 0.00 0.307189E+12 2.55 7.74 28-APR-10:00 0.00 0.00
May 0.634254E+11 85161.62 23-MAY-12:30 379.59 0.444367E+12 0.00 0.507792E+12 3.34 7.74 15-MAY-09:50 0.00 0.00
June 0.102900E+12 101002.66 28-JUN-14:50 549.36 0.735484E+12 0.00 0.838384E+12 5.08 7.76 07-JUN-05:04 0.00 0.00
July 0.124497E+12 112007.09 31-JUL-15:00 654.73 0.884422E+12 0.00 0.100892E+13 5.80 7.82 19-JUL-05:03 0.00 0.00
August 0.118802E+12 101780.94 23-AUG-16:00 666.97 0.847500E+12 0.00 0.966302E+12 5.85 7.94 26-AUG-05:02 0.00 0.00
September 0.832948E+11 120157.44 05-SEP-13:10 462.48 0.591281E+12 0.00 0.674576E+12 4.26 7.96 05-SEP-05:03 0.00 0.00
October 0.435211E+11 92766.34 02-OCT-11:00 304.21 0.300300E+12 0.00 0.343821E+12 2.57 7.76 04-OCT-09:50 0.00 0.00
November 0.443420E+10 49742.11 02-NOV-15:00 94.27 0.239354E+11 0.00 0.283696E+11 0.68 7.30 02-NOV-15:00 0.00 0.00
December 0.689480E+09 7331.32 24-DEC-15:23 87.33 0.355899E+10 0.00 0.424847E+10 0.61 5.27 14-DEC-06:50 0.00 0.00
                         
Annual Sum or Average 0.602289E+12     3829.58 0.423058E+13 0.00 0.483287E+13 2.78     0.00 0.00
Minimum of Months 0.689480E+09 7331.32   70.88 0.355899E+10 0.00 0.424847E+10 0.49 5.27   0.00 0.00
Maximum of Months 0.124497E+12 120157.44   666.97 0.884422E+12 0.00 0.100892E+13 5.85 7.96   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.529992E+10 81624.34 28-APR-14:00 20.17 0.396765E+11 0.00 0.449764E+11 0.21 7.64 27-APR-13:30 0.00 0.00
May 0.124477E+11 85161.62 23-MAY-12:30 46.67 0.933541E+11 0.00 0.105802E+12 0.47 7.66 23-MAY-12:40 0.00 0.00
June 0.447062E+11 101002.66 28-JUN-14:50 155.18 0.335088E+12 0.00 0.379794E+12 1.62 7.68 22-JUN-07:20 0.00 0.00
July 0.612040E+11 112007.09 31-JUL-15:00 205.01 0.452641E+12 0.00 0.513845E+12 2.04 7.77 27-JUL-05:04 0.00 0.00
August 0.584537E+11 101780.94 23-AUG-16:00 200.26 0.434782E+12 0.00 0.493236E+12 2.00 7.94 26-AUG-05:02 0.00 0.00
September 0.313489E+11 120157.44 05-SEP-13:10 112.60 0.235477E+12 0.00 0.266826E+12 1.18 7.96 05-SEP-05:03 0.00 0.00
October 0.915033E+10 92766.34 02-OCT-11:00 34.17 0.690035E+11 0.00 0.781538E+11 0.35 7.72 02-OCT-10:30 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.222611E+12     774.05 0.166002E+13 0.00 0.188263E+13 0.66     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.612040E+11 120157.44   205.01 0.452641E+12 0.00 0.513845E+12 2.04 7.96   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.140359E+10 744.00 5952.96 05-JAN-16:00 35862.33 26-JAN-17:00 19.80 18.33 3.07
February 0.422104E+10 672.00 12476.23 12-FEB-14:02 68694.43 13-FEB-17:05 22.73 18.39 3.07
March 0.117942E+11 744.00 12476.23 06-MAR-15:00 106691.09 31-MAR-23:40 25.89 18.56 3.07
April 0.220036E+11 720.00 12476.23 01-APR-10:10 128999.99 16-APR-17:42 30.28 19.95 3.07
May 0.207966E+11 744.00 12476.23 02-MAY-12:00 60294.85 31-MAY-23:50 23.81 20.84 3.07
June 0.292894E+11 720.00 12476.23 01-JUN-00:10 90358.86 30-JUN-23:23 31.02 25.11 3.07
July 0.334097E+11 744.00 12476.23 01-JUL-00:10 116316.41 04-JUL-18:41 36.27 27.58 3.07
August 0.333579E+11 744.00 12476.23 01-AUG-00:03 137128.91 20-AUG-18:31 37.72 26.59 3.07
September 0.261477E+11 720.00 12476.23 01-SEP-00:05 59609.50 30-SEP-24:00 25.14 21.97 3.07
October 0.175567E+11 744.00 12476.23 01-OCT-00:10 81476.79 31-OCT-24:00 24.85 19.63 3.07
November 0.783985E+10 720.00 12476.23 02-NOV-14:40 92864.96 02-NOV-16:30 25.45 18.34 3.07
December 0.573877E+10 744.00 8108.54 01-DEC-16:00 113748.64 29-DEC-16:40 27.43 18.33 3.07
                   
Annual Sum or Average 0.213559E+12 8760.00         27.57 21.15 3.07
Minimum of Months 0.140359E+10 672.00 5952.96   35862.33   19.80 18.33 3.07
Maximum of Months 0.334097E+11 744.00 12476.23   137128.91   37.72 27.58 3.07



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 263486.77 05-JAN-15:00 21.00 20.97 1.93
February 9016622.22 16.42 341.59 14-FEB-16:00 788198.92 14-FEB-16:10 21.07 20.99 3.29
March 34299653.30 78.26 685.05 08-MAR-14:00 806466.80 08-MAR-14:00 21.14 20.95 8.35
April 0.159223E+09 186.36 882.07 14-APR-16:10 968167.16 12-APR-15:00 21.62 21.01 17.19
May 0.481215E+09 313.89 2190.42 22-MAY-15:50 1039071.89 19-MAY-15:20 22.23 21.21 25.23
June 0.332580E+10 462.70 15224.19 06-JUN-13:20 1080829.47 22-JUN-12:10 22.96 21.16 37.72
July 0.131702E+11 560.78 15224.19 01-JUL-05:04 1036923.18 21-JUL-16:50 23.22 21.27 45.18
August 0.100976E+11 526.81 15224.19 01-AUG-09:40 1046173.21 31-AUG-16:00 23.14 21.19 44.46
September 0.255704E+10 399.50 15224.19 01-SEP-10:50 1062601.83 21-SEP-13:50 22.78 21.32 32.29
October 0.515128E+09 218.95 15224.19 11-OCT-10:30 1016444.77 02-OCT-10:20 21.81 21.10 18.62
November 4553602.14 19.75 210.36 02-NOV-15:10 425420.35 02-NOV-15:10 21.01 20.96 3.44
December 0.00 0.00 0.00 01-DEC-00:10 207007.43 15-DEC-12:50 20.99 20.98 0.74
                   
Annual Sum or Average 0.303541E+11 2783.41         21.92 21.09 19.98
Minimum of Months 0.00 0.00 0.00   207007.43   20.99 20.95 0.74
Maximum of Months 0.131702E+11 560.78 15224.19   1080829.47   23.22 21.32 45.18



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 21.00 21.00 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 21.07 21.07 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 21.14 21.14 0.00
April 9064236.79 5.50 564.83 28-APR-14:20 952650.78 17-APR-13:50 21.62 21.59 0.40
May 65981888.59 22.83 2190.42 22-MAY-15:50 1039071.89 19-MAY-15:20 22.23 22.09 1.62
June 0.193906E+10 128.83 15224.19 06-JUN-13:20 1080829.47 22-JUN-12:10 22.96 22.22 9.46
July 0.796189E+10 167.52 15224.19 01-JUL-05:04 1036923.18 21-JUL-16:50 23.22 22.39 11.91
August 0.666447E+10 159.58 15224.19 01-AUG-09:40 1046173.21 31-AUG-16:00 23.14 22.32 11.34
September 0.129738E+10 87.08 15224.19 01-SEP-10:50 1062601.83 21-SEP-13:50 22.78 22.26 6.40
October 0.173594E+09 27.58 15224.19 11-OCT-10:50 1016444.77 02-OCT-10:20 21.81 21.65 1.96
November 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 21.01 21.01 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 20.99 20.99 0.00
                   
Annual Sum or Average 0.181114E+11 598.93         21.92 21.65 3.62
Minimum of Months 0.00 0.00 0.00   0.00   20.99 20.99 0.00
Maximum of Months 0.796189E+10 167.52 15224.19   1080829.47   23.22 22.39 11.91



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.169176E+12 0.00 400.40 998567.03 24-JAN-06:01 0.00 29.01 56.71 0.31 0.00 0.03 0.49 24-JAN-06:01
February 0.967922E+11 0.00 300.00 1006272.54 08-FEB-06:01 0.00 26.91 50.24 0.19 0.00 0.02 0.49 08-FEB-06:01
March 0.229811E+11 0.00 173.40 901086.37 04-MAR-06:02 0.00 25.86 38.42 0.04 0.00 0.00 0.44 04-MAR-06:02
April 0.302068E+10 0.00 43.03 136334.97 08-APR-06:05 0.00 24.47 27.75 0.01 0.00 0.00 0.07 08-APR-06:05
May 0.296689E+09 0.00 9.87 39056.86 06-MAY-06:10 0.00 22.93 23.68 0.00 0.00 0.00 0.02 06-MAY-06:10
June 1244163.05 0.00 1.79 455.89 09-JUN-05:25 0.00 22.74 22.88 0.00 0.00 0.00 0.00 09-JUN-05:25
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 22.73 22.73 0.00 0.00 0.00 0.00 01-JUL-00:10
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 22.73 22.73 0.00 0.00 0.00 0.00 01-AUG-00:03
September 0.00 0.00 0.00 0.00 01-SEP-00:05 0.00 22.73 22.73 0.00 0.00 0.00 0.00 01-SEP-00:05
October 0.142121E+11 0.00 92.28 813974.74 26-OCT-05:03 0.00 24.05 30.77 0.02 0.00 0.00 0.40 26-OCT-05:03
November 0.380810E+11 0.00 245.17 959104.05 28-NOV-06:01 0.00 25.50 43.72 0.07 0.00 0.01 0.47 28-NOV-06:01
December 0.168062E+12 0.00 418.22 1071590.98 09-DEC-05:01 0.00 27.62 56.96 0.31 0.00 0.03 0.53 09-DEC-05:01
                           
Annual Sum or Average 0.512623E+12 0.00 1684.18     0.00 24.77 34.88 0.08 0.00 0.01    
Minimum of Months 0.00 0.00 0.00 0.00   0.00 22.73 22.73 0.00 0.00 0.00 0.00  
Maximum of Months 0.169176E+12 0.00 418.22 1071590.98   0.00 29.01 56.96 0.31 0.00 0.03 0.53  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 19.80 19.80 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 22.73 22.73 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 25.89 25.89 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 30.28 30.28 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:03 0.00 23.81 23.81 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 31.02 31.02 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 36.27 36.27 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 37.72 37.72 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:05 0.00 25.14 25.14 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 24.85 24.85 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 25.45 25.45 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 27.43 27.43 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 27.57 27.57 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 19.80 19.80 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 37.72 37.72 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.874801E+09 0.00 25.49 0.874801E+09 0.00 0.00 0.00 0.00 21105.60 05-JAN-14:10 21105.60 05-JAN-14:10 0.00 0.00 0.00
February 0.288684E+10 0.00 37.39 0.288684E+10 0.00 0.00 0.00 0.00 64914.31 14-FEB-15:50 64914.31 14-FEB-15:50 0.00 0.00 0.00
March 0.920135E+10 0.00 128.71 0.920135E+10 0.00 0.00 0.00 0.00 71224.04 08-MAR-16:00 71224.04 08-MAR-16:00 0.00 0.00 0.00
April 0.335933E+11 0.00 277.02 0.335933E+11 0.00 0.00 0.00 0.00 100858.86 17-APR-15:20 100858.86 17-APR-15:20 0.00 0.00 0.00
May 0.515670E+11 0.00 354.30 0.515670E+11 0.00 0.00 0.00 0.00 105239.26 30-MAY-14:30 105239.26 30-MAY-14:30 0.00 0.00 0.00
June 0.101735E+12 0.00 521.64 0.101732E+12 0.00 0.00 0.00 0.00 140542.28 29-JUN-05:03 130936.98 29-JUN-05:03 0.00 0.00 0.00
July 0.131826E+12 0.00 618.44 0.128217E+12 0.00 0.00 0.00 0.00 144602.24 01-JUL-05:02 129587.18 05-JUL-14:50 0.00 0.00 0.00
August 0.129946E+12 0.00 644.84 0.126408E+12 0.00 0.00 0.00 0.00 143294.69 14-AUG-05:02 132570.12 07-AUG-15:20 0.00 0.00 0.00
September 0.743874E+11 0.00 439.43 0.733643E+11 0.00 0.00 0.00 0.00 149830.61 05-SEP-13:10 106228.57 11-SEP-15:50 0.00 0.00 0.00
October 0.358027E+11 0.00 270.63 0.357819E+11 0.00 0.00 0.00 0.00 104163.96 10-OCT-16:00 104163.96 10-OCT-16:00 0.00 0.00 0.00
November 0.223797E+10 0.00 58.50 0.223797E+10 0.00 0.00 0.00 0.00 35243.54 02-NOV-15:00 35243.54 02-NOV-15:00 0.00 0.00 0.00
December 540032.06 0.00 0.85 540032.06 0.00 0.00 0.00 0.00 2843.22 24-DEC-15:23 2843.22 24-DEC-15:23 0.00 0.00 0.00
                               
Annual Sum or Average 0.574059E+12 0.00 3377.23 0.565865E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 540032.06 0.00 0.85 540032.06 0.00 0.00 0.00 0.00 2843.22   2843.22   0.00 0.00 0.00
Maximum of Months 0.131826E+12 0.00 644.84 0.128217E+12 0.00 0.00 0.00 0.00 149830.61   132570.12   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.783570E+10 0.00 69.93 0.783570E+10 0.00 0.00 0.00 0.00 174912.06 05-JAN-15:40 174912.06 05-JAN-15:40 0.00 0.00 0.00
February 0.228936E+11 0.00 100.30 0.228936E+11 0.00 0.00 0.00 0.00 511185.45 14-FEB-16:00 511185.45 14-FEB-16:00 0.00 0.00 0.00
March 0.680710E+11 0.00 152.71 0.680710E+11 0.00 0.00 0.00 0.00 527919.52 08-MAR-16:00 527919.52 08-MAR-16:00 0.00 0.00 0.00
April 0.246290E+12 0.00 247.14 0.246290E+12 0.00 0.00 0.00 0.00 841050.45 26-APR-15:20 841050.45 26-APR-15:20 0.00 0.00 0.00
May 0.445055E+12 0.00 347.92 0.445055E+12 0.00 0.00 0.00 0.00 946872.31 19-MAY-15:20 946872.31 19-MAY-15:20 0.00 0.00 0.00
June 0.866327E+12 0.00 461.57 0.866290E+12 0.00 0.00 0.00 0.00 1410138.80 29-JUN-05:03 1265054.23 29-JUN-05:03 0.00 0.00 0.00
July 0.105124E+13 0.00 499.90 0.102797E+13 0.00 0.00 0.00 0.00 1332156.89 01-JUL-05:02 1172965.90 21-JUL-14:50 0.00 0.00 0.00
August 0.996513E+12 0.00 503.24 0.974056E+12 0.00 0.00 0.00 0.00 1353616.86 14-AUG-05:02 1119225.27 07-AUG-15:40 0.00 0.00 0.00
September 0.651386E+12 0.00 414.90 0.641929E+12 0.00 0.00 0.00 0.00 1279607.79 05-SEP-13:00 964317.82 21-SEP-16:00 0.00 0.00 0.00
October 0.295152E+12 0.00 273.41 0.294984E+12 0.00 0.00 0.00 0.00 903699.58 06-OCT-15:30 903699.58 06-OCT-15:30 0.00 0.00 0.00
November 0.160066E+11 0.00 90.76 0.160066E+11 0.00 0.00 0.00 0.00 278742.50 02-NOV-15:00 278742.50 02-NOV-15:00 0.00 0.00 0.00
December 11358595.73 0.00 86.80 11358595.73 0.00 0.00 0.00 0.00 40176.06 24-DEC-14:43 40176.06 24-DEC-14:43 0.00 0.00 0.00
                               
Annual Sum or Average 0.466678E+13 0.00 3248.60 0.461139E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 11358595.73 0.00 69.93 11358595.73 0.00 0.00 0.00 0.00 40176.06   40176.06   0.00 0.00 0.00
Maximum of Months 0.105124E+13 0.00 503.24 0.102797E+13 0.00 0.00 0.00 0.00 1410138.80   1265054.23   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.394535E+09 0.00 20.17 0.394535E+09 0.00 0.00 0.00 0.00 13174.34 05-JAN-14:20 13174.34 05-JAN-14:20 0.00 0.00 0.00
February 0.189525E+10 0.00 30.77 0.189525E+10 0.00 0.00 0.00 0.00 45922.81 14-FEB-15:50 45922.81 14-FEB-15:50 0.00 0.00 0.00
March 0.549794E+10 0.00 115.88 0.549794E+10 0.00 0.00 0.00 0.00 53550.47 08-MAR-16:00 53550.47 08-MAR-16:00 0.00 0.00 0.00
April 0.256558E+11 0.00 231.00 0.256558E+11 0.00 0.00 0.00 0.00 102498.97 26-APR-15:00 102498.97 26-APR-15:00 0.00 0.00 0.00
May 0.490399E+11 0.00 341.04 0.490399E+11 0.00 0.00 0.00 0.00 117298.38 19-MAY-15:20 117298.38 19-MAY-15:20 0.00 0.00 0.00
June 0.995448E+11 0.00 461.96 0.995432E+11 0.00 0.00 0.00 0.00 148010.26 28-JUN-14:50 148010.26 28-JUN-14:50 0.00 0.00 0.00
July 0.122368E+12 0.00 508.13 0.119757E+12 0.00 0.00 0.00 0.00 147247.25 21-JUL-14:50 147247.25 21-JUL-14:50 0.00 0.00 0.00
August 0.113999E+12 0.00 506.89 0.111642E+12 0.00 0.00 0.00 0.00 157161.83 13-AUG-15:31 138326.38 07-AUG-15:50 0.00 0.00 0.00
September 0.705042E+11 0.00 406.62 0.697699E+11 0.00 0.00 0.00 0.00 140842.54 05-SEP-13:30 116043.96 21-SEP-16:00 0.00 0.00 0.00
October 0.291977E+11 0.00 245.00 0.291977E+11 0.00 0.00 0.00 0.00 103545.96 06-OCT-15:20 103545.96 06-OCT-15:20 0.00 0.00 0.00
November 0.103100E+10 0.00 47.51 0.103100E+10 0.00 0.00 0.00 0.00 25157.14 02-NOV-15:00 25157.14 02-NOV-15:00 0.00 0.00 0.00
December 342.12 0.00 0.29 342.12 0.00 0.00 0.00 0.00 0.39 16-DEC-14:30 0.39 16-DEC-14:30 0.00 0.00 0.00
                               
Annual Sum or Average 0.519128E+12 0.00 2915.27 0.513424E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 342.12 0.00 0.29 342.12 0.00 0.00 0.00 0.00 0.39   0.39   0.00 0.00 0.00
Maximum of Months 0.122368E+12 0.00 508.13 0.119757E+12 0.00 0.00 0.00 0.00 157161.83   148010.26   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 16995512.17 0.00 2.33 16995512.17 0.00 0.00 0.00 0.00 3114.21 02-JAN-15:00 3114.21 02-JAN-15:00 0.00 0.00 0.00
February 0.123474E+10 0.00 16.67 0.123474E+10 0.00 0.00 0.00 0.00 39417.81 13-FEB-16:00 39417.81 13-FEB-16:00 0.00 0.00 0.00
March 0.341121E+10 0.00 71.33 0.341121E+10 0.00 0.00 0.00 0.00 41000.58 08-MAR-14:00 41000.58 08-MAR-14:00 0.00 0.00 0.00
April 0.172376E+11 0.00 173.65 0.172376E+11 0.00 0.00 0.00 0.00 57569.73 17-APR-15:00 57569.73 17-APR-15:00 0.00 0.00 0.00
May 0.303525E+11 0.00 257.92 0.303515E+11 0.00 0.00 0.00 0.00 89026.03 29-MAY-16:11 89026.03 29-MAY-16:11 0.00 0.00 0.00
June 0.560556E+11 0.00 365.51 0.560390E+11 0.00 0.00 0.00 0.00 80445.61 29-JUN-05:03 74222.74 29-JUN-05:03 0.00 0.00 0.00
July 0.686866E+11 0.00 396.75 0.672441E+11 0.00 0.00 0.00 0.00 121964.75 02-JUL-19:30 90910.82 04-JUL-19:00 0.00 0.00 0.00
August 0.680956E+11 0.00 420.64 0.668576E+11 0.00 0.00 0.00 0.00 99526.35 13-AUG-18:17 83839.79 13-AUG-18:17 0.00 0.00 0.00
September 0.461517E+11 0.00 335.28 0.452770E+11 0.00 0.00 0.00 0.00 99210.01 05-SEP-13:00 68033.60 04-SEP-10:40 0.00 0.00 0.00
October 0.215095E+11 0.00 192.48 0.215059E+11 0.00 0.00 0.00 0.00 90547.77 01-OCT-14:24 90547.77 01-OCT-14:24 0.00 0.00 0.00
November 0.607606E+09 0.00 28.64 0.607606E+09 0.00 0.00 0.00 0.00 23115.54 09-NOV-14:00 23115.54 09-NOV-14:00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.313360E+12 0.00 2261.21 0.309783E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.686866E+11 0.00 420.64 0.672441E+11 0.00 0.00 0.00 0.00 121964.75   90910.82   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.456303E+10 0.116780E+10 744.00 0.456247E+10 565441.00 0.00 0.34 01-JAN-16:50 0.12 21-JAN-07:40 2759.23 01-JAN-16:50 2752.50 01-JAN-16:50 26.85 20-JAN-17:00 653.52 01-JAN-16:50 0.00
February 0.914176E+10 0.218744E+10 672.00 0.913888E+10 2878588.73 0.00 0.58 14-FEB-17:00 0.38 02-FEB-08:00 4724.55 15-FEB-17:00 4724.55 15-FEB-17:00 80.16 17-FEB-11:10 1248.22 14-FEB-17:00 0.00
March 0.156914E+11 0.359261E+10 744.00 0.156865E+11 4917504.69 0.00 0.87 31-MAR-24:00 0.61 04-MAR-07:05 7749.75 31-MAR-24:00 7749.75 31-MAR-24:00 92.12 20-MAR-14:40 1805.45 12-MAR-17:01 0.00
April 0.203898E+11 0.474268E+10 720.00 0.203890E+11 725295.68 0.00 1.00 01-APR-16:40 0.33 30-APR-24:00 8909.61 16-APR-18:22 8909.61 16-APR-18:22 64.55 15-APR-08:00 2484.11 13-APR-17:00 0.00
May 0.604297E+10 0.163193E+10 744.00 0.600275E+10 40225102.62 0.00 0.50 31-MAY-23:40 0.20 05-MAY-06:15 4139.19 31-MAY-24:00 4139.19 31-MAY-24:00 267.40 24-MAY-15:30 1035.87 31-MAY-23:20 0.00
June 0.111029E+11 0.318145E+10 720.00 0.110071E+11 95812752.89 0.00 0.70 30-JUN-23:13 0.44 09-JUN-06:20 6014.27 30-JUN-24:00 5981.18 30-JUN-24:00 318.27 30-JUN-14:00 2006.29 28-JUN-16:00 0.00
July 0.167198E+11 0.486554E+10 744.00 0.164950E+11 0.224829E+09 0.00 0.90 04-JUL-18:11 0.67 08-JUL-06:10 7884.50 31-JUL-23:53 7875.98 31-JUL-23:45 450.48 07-JUL-17:00 2608.48 21-JUL-17:00 0.00
August 0.216872E+11 0.591511E+10 744.00 0.214456E+11 0.241569E+09 0.00 1.00 01-AUG-14:00 0.32 31-AUG-24:00 8615.95 07-AUG-18:30 8588.97 30-AUG-17:50 430.30 23-AUG-14:00 2974.03 01-AUG-16:00 0.00
September 0.617214E+10 0.167048E+10 720.00 0.601907E+10 0.153071E+09 0.00 0.49 30-SEP-24:00 0.23 09-SEP-06:05 4169.71 30-SEP-24:00 4140.39 30-SEP-24:00 313.71 05-SEP-14:40 1056.27 02-SEP-17:31 0.00
October 0.110074E+11 0.267724E+10 744.00 0.109490E+11 58404930.84 0.00 0.69 31-OCT-24:00 0.39 26-OCT-06:55 5935.47 31-OCT-24:00 5935.47 31-OCT-24:00 278.36 02-OCT-17:00 1514.98 01-OCT-16:02 0.00
November 0.151238E+11 0.342272E+10 720.00 0.151126E+11 11135095.30 0.00 0.80 19-NOV-16:35 0.62 10-NOV-08:00 6767.95 05-NOV-16:40 6767.95 05-NOV-16:40 140.33 09-NOV-16:00 1545.76 19-NOV-16:35 0.00
December 0.203470E+11 0.454654E+10 744.00 0.203468E+11 110100.56 0.00 0.99 17-DEC-16:23 0.80 09-DEC-07:40 8572.49 31-DEC-16:35 8572.49 31-DEC-16:35 24.51 27-DEC-17:03 1917.23 17-DEC-16:23 0.00
                                       
Annual Sum or Average 0.157989E+12 0.396015E+11 8760.00 0.157155E+12 0.834243E+09 0.00                         0.00
Minimum of Months 0.456303E+10 0.116780E+10 672.00 0.456247E+10 110100.56 0.00 0.34   0.12   2759.23   2752.50   24.51   653.52   0.00
Maximum of Months 0.216872E+11 0.591511E+10 744.00 0.214456E+11 0.241569E+09 0.00 1.00   0.80   8909.61   8909.61   450.48   2974.03   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.261244E+11 0.697287E+10 744.00 0.261184E+11 5934940.86 0.00 0.32 26-JAN-17:00 0.01 17-JAN-07:10 23273.69 26-JAN-17:00 23273.69 26-JAN-17:00 261.58 20-JAN-17:00 5848.04 26-JAN-17:00 0.00
February 0.735495E+11 0.178761E+11 672.00 0.735204E+11 29093920.05 0.00 0.57 14-FEB-17:00 0.26 06-FEB-07:10 44252.51 15-FEB-17:00 44252.51 15-FEB-17:00 767.62 17-FEB-11:20 11659.56 14-FEB-17:00 0.00
March 0.139600E+12 0.322423E+11 744.00 0.139549E+12 50430409.97 0.00 0.85 31-MAR-23:40 0.54 04-MAR-07:05 71572.41 31-MAR-23:40 71572.41 31-MAR-23:40 908.58 20-MAR-14:40 16541.70 12-MAR-17:01 0.00
April 0.190549E+12 0.444989E+11 720.00 0.190541E+12 7784307.71 0.00 1.00 01-APR-17:00 0.30 30-APR-23:57 83832.37 16-APR-17:42 83832.37 16-APR-17:42 663.60 15-APR-08:00 23736.48 13-APR-17:00 0.00
May 0.539837E+11 0.146949E+11 744.00 0.535888E+11 0.394905E+09 0.00 0.50 31-MAY-23:40 0.16 05-MAY-06:25 39202.24 31-MAY-24:00 39202.24 31-MAY-24:00 2617.17 24-MAY-15:30 9827.24 31-MAY-23:20 0.00
June 0.104467E+12 0.300236E+11 720.00 0.103517E+12 0.949856E+09 0.00 0.71 30-JUN-23:23 0.40 09-JUN-06:10 58068.54 30-JUN-24:00 57742.12 30-JUN-24:00 3119.61 30-JUN-14:00 19199.40 28-JUN-16:00 0.00
July 0.159193E+12 0.463411E+11 744.00 0.156954E+12 0.223847E+10 0.00 0.90 04-JUL-18:21 0.66 08-JUL-06:10 76039.90 31-JUL-23:53 75951.61 31-JUL-23:53 4407.39 07-JUL-17:00 25008.03 21-JUL-18:10 0.00
August 0.206914E+12 0.564441E+11 744.00 0.204503E+12 0.241158E+10 0.00 1.00 01-AUG-13:50 0.30 31-AUG-24:00 82348.09 11-AUG-18:10 82047.20 30-AUG-17:50 4275.13 23-AUG-14:00 28419.67 01-AUG-16:00 0.00
September 0.559572E+11 0.152364E+11 720.00 0.544590E+11 0.149821E+10 0.00 0.48 30-SEP-24:00 0.20 09-SEP-06:25 39411.62 30-SEP-24:00 39125.62 30-SEP-24:00 3116.83 05-SEP-14:40 10002.23 02-SEP-17:31 0.00
October 0.980070E+11 0.240353E+11 744.00 0.974304E+11 0.576583E+09 0.00 0.67 31-OCT-24:00 0.32 26-OCT-06:55 54210.36 31-OCT-24:00 54210.36 31-OCT-24:00 2743.40 02-OCT-17:00 14204.51 01-OCT-16:02 0.00
November 0.131243E+12 0.300357E+11 720.00 0.131132E+12 0.111208E+09 0.00 0.74 19-NOV-16:42 0.52 27-NOV-07:05 62203.90 02-NOV-16:40 61336.04 02-NOV-16:40 1364.19 09-NOV-16:00 13659.87 19-NOV-16:42 0.00
December 0.174064E+12 0.394831E+11 744.00 0.174063E+12 1384061.39 0.00 0.91 17-DEC-16:45 0.70 27-DEC-07:10 76426.03 29-DEC-16:40 76426.03 29-DEC-16:40 246.86 27-DEC-17:03 16793.19 17-DEC-16:45 0.00
                                       
Annual Sum or Average 0.141365E+13 0.357884E+12 8760.00 0.140538E+13 0.827545E+10 0.00                         0.00
Minimum of Months 0.261244E+11 0.697287E+10 672.00 0.261184E+11 1384061.39 0.00 0.32   0.01   23273.69   23273.69   246.86   5848.04   0.00
Maximum of Months 0.206914E+12 0.564441E+11 744.00 0.204503E+12 0.241158E+10 0.00 1.00   0.70   83832.37   83832.37   4407.39   28419.67   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.972830E+09 0.271395E+09 442.86 0.972378E+09 451745.82 0.00 0.29 26-JAN-17:00 0.00 01-JAN-00:05 2185.67 26-JAN-17:00 2185.67 26-JAN-17:00 28.50 01-JAN-16:35 553.23 26-JAN-17:00 0.00
February 0.581139E+10 0.143935E+10 671.92 0.580862E+10 2773848.81 0.00 0.55 14-FEB-17:00 0.00 06-FEB-00:25 4435.15 15-FEB-17:00 4435.15 15-FEB-17:00 73.17 17-FEB-11:30 1166.95 14-FEB-17:00 0.00
March 0.128712E+11 0.300593E+10 744.00 0.128663E+11 4908821.69 0.00 0.80 31-MAR-23:20 0.43 04-MAR-07:05 6800.83 31-MAR-23:20 6800.83 31-MAR-23:20 88.15 20-MAR-14:40 1624.48 08-MAR-17:00 0.00
April 0.186146E+11 0.437859E+10 720.00 0.186138E+11 746023.80 0.00 1.00 01-APR-17:01 0.28 30-APR-23:53 8389.69 16-APR-17:42 8389.69 16-APR-17:42 64.03 15-APR-08:00 2410.98 13-APR-17:00 0.00
May 0.522189E+10 0.143466E+10 744.00 0.518263E+10 39257141.68 0.00 0.49 31-MAY-23:30 0.08 05-MAY-06:05 3888.40 31-MAY-24:00 3888.40 31-MAY-24:00 259.97 24-MAY-15:30 1012.36 20-MAY-18:00 0.00
June 0.104985E+11 0.303123E+10 720.00 0.104036E+11 94877297.30 0.00 0.71 18-JUN-18:11 0.34 09-JUN-06:20 5834.46 30-JUN-24:00 5801.55 30-JUN-24:00 315.28 30-JUN-14:00 1975.49 28-JUN-16:00 0.00
July 0.160792E+11 0.469293E+10 744.00 0.158554E+11 0.223809E+09 0.00 0.92 04-JUL-18:11 0.63 08-JUL-06:10 7607.93 31-JUL-23:53 7599.02 31-JUL-23:53 443.46 07-JUL-17:00 2587.65 04-JUL-18:01 0.00
August 0.208082E+11 0.569450E+10 744.00 0.205672E+11 0.240998E+09 0.00 1.00 01-AUG-14:20 0.29 31-AUG-24:00 8387.94 13-AUG-19:23 8387.94 13-AUG-19:23 427.92 23-AUG-14:00 2904.25 01-AUG-16:00 0.00
September 0.552014E+10 0.151389E+10 720.00 0.537036E+10 0.149774E+09 0.00 0.47 30-SEP-23:30 0.15 09-SEP-06:45 3934.03 30-SEP-23:40 3904.41 30-SEP-24:00 313.65 05-SEP-14:30 1054.60 02-SEP-17:31 0.00
October 0.909302E+10 0.225405E+10 744.00 0.903562E+10 57400682.04 0.00 0.63 31-OCT-23:40 0.20 26-OCT-06:10 5178.91 31-OCT-23:40 5178.91 31-OCT-23:40 275.07 02-OCT-17:00 1469.25 01-OCT-16:02 0.00
November 0.115553E+11 0.268466E+10 720.00 0.115443E+11 11003893.93 0.00 0.72 03-NOV-16:40 0.38 27-NOV-07:05 6205.29 02-NOV-16:40 6118.16 02-NOV-16:40 135.27 09-NOV-16:00 1354.38 03-NOV-16:40 0.00
December 0.153835E+11 0.354988E+10 744.00 0.153834E+11 120520.97 0.00 0.87 13-DEC-16:40 0.54 26-DEC-04:03 7510.68 29-DEC-16:50 7510.68 29-DEC-16:50 24.28 27-DEC-17:03 1636.74 13-DEC-16:40 0.00
                                       
Annual Sum or Average 0.132430E+12 0.339511E+11 8458.78 0.131604E+12 0.826120E+09 0.00                         0.00
Minimum of Months 0.972830E+09 0.271395E+09 442.86 0.972378E+09 120520.97 0.00 0.29   0.00   2185.67   2185.67   24.28   553.23   0.00
Maximum of Months 0.208082E+11 0.569450E+10 744.00 0.205672E+11 0.240998E+09 0.00 1.00   0.63   8389.69   8389.69   443.46   2904.25   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.17 0.00 120.17 19.55 494.31 0.00 0.00 0.00
February 150.20 0.00 150.20 47.00 447.78 0.00 0.00 0.00
March 189.46 0.00 189.46 111.46 352.20 0.00 0.00 0.00
April 240.36 2.06 238.30 189.78 231.96 0.00 0.00 0.00
May 261.27 16.85 244.43 270.75 163.88 0.00 0.00 0.00
June 296.88 48.58 248.29 421.42 106.93 0.00 0.00 0.00
July 272.49 22.68 249.81 418.83 71.27 0.00 0.00 0.00
August 252.78 5.66 247.12 353.94 81.52 0.00 0.00 0.00
September 202.14 0.05 202.09 240.11 148.71 0.00 0.00 0.00
October 150.84 0.00 150.84 105.20 273.31 0.00 0.00 0.00
November 128.10 0.00 128.10 30.79 402.96 0.00 0.00 0.00
December 102.29 0.00 102.29 4.08 534.32 0.00 0.00 0.00
                 
Annual Sum or Average 197.42 8.00 189.42 185.14 274.93 0.00 0.00 0.00
Minimum of Months 102.29 0.00 102.29 4.08 71.27 0.00 0.00 0.00
Maximum of Months 296.88 48.58 249.81 421.42 534.32 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.17 0.00 120.17 19.55 494.31 0.00 0.00 0.00
February 150.20 0.00 150.20 47.00 447.78 0.00 0.00 0.00
March 189.45 0.00 189.45 111.46 352.20 0.00 0.00 0.00
April 240.36 2.06 238.30 189.78 231.96 0.00 0.00 0.00
May 261.27 16.84 244.43 270.74 163.88 0.00 0.00 0.00
June 296.87 48.58 248.29 421.41 106.93 0.00 0.00 0.00
July 272.48 22.68 249.81 418.83 71.27 0.00 0.00 0.00
August 252.77 5.66 247.12 353.94 81.51 0.00 0.00 0.00
September 202.14 0.05 202.09 240.11 148.71 0.00 0.00 0.00
October 150.84 0.00 150.84 105.20 273.31 0.00 0.00 0.00
November 128.10 0.00 128.10 30.79 402.96 0.00 0.00 0.00
December 102.29 0.00 102.29 4.08 534.32 0.00 0.00 0.00
                 
Annual Sum or Average 197.42 8.00 189.41 185.14 274.93 0.00 0.00 0.00
Minimum of Months 102.29 0.00 102.29 4.08 71.27 0.00 0.00 0.00
Maximum of Months 296.87 48.58 249.81 421.41 534.32 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.17 0.00 120.17 19.55 494.31 0.00 0.00 0.00
February 150.20 0.00 150.20 47.00 447.78 0.00 0.00 0.00
March 189.45 0.00 189.45 111.46 352.20 0.00 0.00 0.00
April 240.36 2.06 238.30 189.78 231.96 0.00 0.00 0.00
May 261.27 16.84 244.43 270.74 163.88 0.00 0.00 0.00
June 296.87 48.58 248.29 421.42 106.93 0.00 0.00 0.00
July 272.48 22.68 249.81 418.83 71.27 0.00 0.00 0.00
August 252.78 5.66 247.12 353.94 81.51 0.00 0.00 0.00
September 202.14 0.05 202.09 240.11 148.71 0.00 0.00 0.00
October 150.84 0.00 150.84 105.20 273.31 0.00 0.00 0.00
November 128.10 0.00 128.10 30.79 402.96 0.00 0.00 0.00
December 102.29 0.00 102.29 4.08 534.32 0.00 0.00 0.00
                 
Annual Sum or Average 197.42 8.00 189.41 185.14 274.93 0.00 0.00 0.00
Minimum of Months 102.29 0.00 102.29 4.08 71.27 0.00 0.00 0.00
Maximum of Months 296.87 48.58 249.81 421.42 534.32 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.17 0.00 120.17 19.55 494.31 0.00 0.00 0.00
February 150.20 0.00 150.20 47.00 447.78 0.00 0.00 0.00
March 189.45 0.00 189.45 111.46 352.20 0.00 0.00 0.00
April 240.36 2.06 238.30 189.78 231.96 0.00 0.00 0.00
May 261.27 16.84 244.43 270.74 163.88 0.00 0.00 0.00
June 296.87 48.58 248.29 421.41 106.93 0.00 0.00 0.00
July 272.48 22.68 249.81 418.83 71.27 0.00 0.00 0.00
August 252.77 5.66 247.12 353.94 81.51 0.00 0.00 0.00
September 202.14 0.05 202.09 240.11 148.71 0.00 0.00 0.00
October 150.84 0.00 150.84 105.20 273.31 0.00 0.00 0.00
November 128.10 0.00 128.10 30.79 402.96 0.00 0.00 0.00
December 102.29 0.00 102.29 4.08 534.32 0.00 0.00 0.00
                 
Annual Sum or Average 197.42 8.00 189.41 185.14 274.93 0.00 0.00 0.00
Minimum of Months 102.29 0.00 102.29 4.08 71.27 0.00 0.00 0.00
Maximum of Months 296.87 48.58 249.81 421.41 534.32 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.17 0.00 120.17 19.55 494.29 0.00 0.00 0.00
February 150.19 0.00 150.19 47.00 447.76 0.00 0.00 0.00
March 189.45 0.00 189.45 111.46 352.18 0.00 0.00 0.00
April 240.35 2.06 238.29 189.77 231.95 0.00 0.00 0.00
May 261.26 16.84 244.42 270.73 163.88 0.00 0.00 0.00
June 296.86 48.58 248.28 421.40 106.93 0.00 0.00 0.00
July 272.47 22.68 249.80 418.81 71.27 0.00 0.00 0.00
August 252.76 5.66 247.11 353.93 81.51 0.00 0.00 0.00
September 202.13 0.05 202.08 240.10 148.71 0.00 0.00 0.00
October 150.83 0.00 150.83 105.20 273.30 0.00 0.00 0.00
November 128.09 0.00 128.09 30.79 402.94 0.00 0.00 0.00
December 102.28 0.00 102.28 4.08 534.30 0.00 0.00 0.00
                 
Annual Sum or Average 197.41 8.00 189.41 185.14 274.92 0.00 0.00 0.00
Minimum of Months 102.28 0.00 102.28 4.08 71.27 0.00 0.00 0.00
Maximum of Months 296.86 48.58 249.80 421.40 534.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 369.79 206.75 163.04 310.51 498.03 0.00 0.00 0.00
February 449.29 242.22 207.07 418.39 454.01 0.00 0.00 0.00
March 592.68 336.93 255.75 633.93 357.29 0.00 0.00 0.00
April 809.73 461.30 348.43 962.71 242.17 0.00 0.00 0.00
May 772.65 440.33 332.32 974.71 184.66 0.00 0.00 0.00
June 832.98 513.15 319.82 1160.90 115.23 0.00 0.00 0.00
July 770.77 440.76 330.01 1121.92 74.74 0.00 0.00 0.00
August 762.73 420.51 342.22 1076.71 84.47 0.00 0.00 0.00
September 634.84 355.20 279.64 843.79 157.47 0.00 0.00 0.00
October 552.12 350.30 201.82 640.25 277.96 0.00 0.00 0.00
November 431.51 253.68 177.83 414.75 406.86 0.00 0.00 0.00
December 349.64 212.79 136.85 297.54 530.90 0.00 0.00 0.00
                 
Annual Sum or Average 611.32 353.26 258.06 739.46 281.13 0.00 0.00 0.00
Minimum of Months 349.64 206.75 136.85 297.54 74.74 0.00 0.00 0.00
Maximum of Months 832.98 513.15 348.43 1160.90 530.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 369.79 206.75 163.04 310.51 498.03 0.00 0.00 0.00
February 449.29 242.22 207.07 418.39 454.01 0.00 0.00 0.00
March 592.68 336.93 255.75 633.93 357.29 0.00 0.00 0.00
April 809.73 461.30 348.43 962.71 242.17 0.00 0.00 0.00
May 772.65 440.33 332.32 974.71 184.66 0.00 0.00 0.00
June 832.98 513.15 319.82 1160.90 115.23 0.00 0.00 0.00
July 770.77 440.76 330.01 1121.92 74.74 0.00 0.00 0.00
August 762.73 420.51 342.22 1076.71 84.47 0.00 0.00 0.00
September 634.84 355.20 279.64 843.79 157.47 0.00 0.00 0.00
October 552.12 350.30 201.82 640.25 277.96 0.00 0.00 0.00
November 431.51 253.68 177.83 414.75 406.86 0.00 0.00 0.00
December 349.64 212.79 136.85 297.54 530.90 0.00 0.00 0.00
                 
Annual Sum or Average 611.32 353.26 258.06 739.46 281.13 0.00 0.00 0.00
Minimum of Months 349.64 206.75 136.85 297.54 74.74 0.00 0.00 0.00
Maximum of Months 832.98 513.15 348.43 1160.90 530.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 369.79 206.75 163.04 310.50 498.02 0.00 0.00 0.00
February 449.28 242.21 207.07 418.38 454.01 0.00 0.00 0.00
March 592.67 336.92 255.75 633.92 357.28 0.00 0.00 0.00
April 809.71 461.29 348.42 962.70 242.16 0.00 0.00 0.00
May 772.64 440.32 332.32 974.69 184.66 0.00 0.00 0.00
June 832.96 513.14 319.82 1160.88 115.23 0.00 0.00 0.00
July 770.75 440.75 330.01 1121.90 74.74 0.00 0.00 0.00
August 762.71 420.50 342.21 1076.69 84.47 0.00 0.00 0.00
September 634.83 355.19 279.64 843.78 157.46 0.00 0.00 0.00
October 552.11 350.29 201.82 640.24 277.95 0.00 0.00 0.00
November 431.50 253.68 177.82 414.75 406.86 0.00 0.00 0.00
December 349.64 212.79 136.85 297.53 530.89 0.00 0.00 0.00
                 
Annual Sum or Average 611.31 353.26 258.06 739.45 281.13 0.00 0.00 0.00
Minimum of Months 349.64 206.75 136.85 297.53 74.74 0.00 0.00 0.00
Maximum of Months 832.96 513.14 348.42 1160.88 530.89 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 888.44 691.32 197.11 1023.23 441.23 0.00 0.00 0.00
February 869.46 635.11 234.35 1023.85 410.84 0.00 0.00 0.00
March 640.70 387.34 253.36 770.80 337.09 0.00 0.00 0.00
April 499.67 205.10 294.56 625.10 241.37 0.00 0.00 0.00
May 333.24 73.31 259.93 420.88 174.85 0.00 0.00 0.00
June 281.89 34.74 247.15 420.75 114.07 0.00 0.00 0.00
July 311.93 49.81 262.12 504.28 75.17 0.00 0.00 0.00
August 428.92 139.42 289.50 663.46 88.26 0.00 0.00 0.00
September 593.10 330.73 262.37 850.75 154.70 0.00 0.00 0.00
October 811.43 597.62 213.82 1045.51 260.13 0.00 0.00 0.00
November 903.78 693.65 210.13 1073.71 363.81 0.00 0.00 0.00
December 963.93 795.14 168.79 1117.49 460.39 0.00 0.00 0.00
                 
Annual Sum or Average 625.85 384.83 241.02 793.68 259.38 0.00 0.00 0.00
Minimum of Months 281.89 34.74 168.79 420.75 75.17 0.00 0.00 0.00
Maximum of Months 963.93 795.14 294.56 1117.49 460.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 888.43 691.32 197.11 1023.23 441.23 0.00 0.00 0.00
February 869.45 635.10 234.35 1023.84 410.84 0.00 0.00 0.00
March 640.70 387.34 253.36 770.80 337.09 0.00 0.00 0.00
April 499.66 205.10 294.56 625.10 241.37 0.00 0.00 0.00
May 333.24 73.30 259.93 420.87 174.85 0.00 0.00 0.00
June 281.89 34.74 247.15 420.75 114.07 0.00 0.00 0.00
July 311.93 49.81 262.11 504.27 75.17 0.00 0.00 0.00
August 428.92 139.42 289.50 663.46 88.26 0.00 0.00 0.00
September 593.10 330.73 262.37 850.74 154.70 0.00 0.00 0.00
October 811.43 597.61 213.82 1045.50 260.13 0.00 0.00 0.00
November 903.78 693.64 210.13 1073.71 363.81 0.00 0.00 0.00
December 963.92 795.13 168.79 1117.48 460.39 0.00 0.00 0.00
                 
Annual Sum or Average 625.84 384.83 241.02 793.67 259.38 0.00 0.00 0.00
Minimum of Months 281.89 34.74 168.79 420.75 75.17 0.00 0.00 0.00
Maximum of Months 963.92 795.13 294.56 1117.48 460.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 888.44 691.32 197.11 1023.23 441.23 0.00 0.00 0.00
February 869.46 635.11 234.35 1023.85 410.84 0.00 0.00 0.00
March 640.70 387.34 253.36 770.80 337.09 0.00 0.00 0.00
April 499.67 205.10 294.56 625.10 241.37 0.00 0.00 0.00
May 333.24 73.31 259.93 420.88 174.85 0.00 0.00 0.00
June 281.89 34.74 247.15 420.75 114.07 0.00 0.00 0.00
July 311.93 49.81 262.12 504.28 75.17 0.00 0.00 0.00
August 428.92 139.42 289.50 663.46 88.26 0.00 0.00 0.00
September 593.10 330.73 262.37 850.75 154.70 0.00 0.00 0.00
October 811.43 597.62 213.82 1045.51 260.13 0.00 0.00 0.00
November 903.78 693.65 210.13 1073.71 363.81 0.00 0.00 0.00
December 963.93 795.14 168.79 1117.49 460.39 0.00 0.00 0.00
                 
Annual Sum or Average 625.85 384.83 241.02 793.68 259.38 0.00 0.00 0.00
Minimum of Months 281.89 34.74 168.79 420.75 75.17 0.00 0.00 0.00
Maximum of Months 963.93 795.14 294.56 1117.49 460.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 888.43 691.32 197.11 1023.23 441.23 0.00 0.00 0.00
February 869.45 635.10 234.35 1023.84 410.84 0.00 0.00 0.00
March 640.70 387.34 253.36 770.80 337.09 0.00 0.00 0.00
April 499.66 205.10 294.56 625.10 241.37 0.00 0.00 0.00
May 333.24 73.30 259.93 420.87 174.85 0.00 0.00 0.00
June 281.89 34.74 247.15 420.75 114.07 0.00 0.00 0.00
July 311.93 49.81 262.11 504.27 75.17 0.00 0.00 0.00
August 428.92 139.42 289.50 663.46 88.26 0.00 0.00 0.00
September 593.10 330.73 262.37 850.74 154.70 0.00 0.00 0.00
October 811.43 597.61 213.82 1045.50 260.13 0.00 0.00 0.00
November 903.78 693.64 210.13 1073.71 363.81 0.00 0.00 0.00
December 963.92 795.13 168.79 1117.48 460.39 0.00 0.00 0.00
                 
Annual Sum or Average 625.84 384.83 241.02 793.67 259.38 0.00 0.00 0.00
Minimum of Months 281.89 34.74 168.79 420.75 75.17 0.00 0.00 0.00
Maximum of Months 963.92 795.13 294.56 1117.48 460.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 888.40 691.29 197.10 1023.19 441.21 0.00 0.00 0.00
February 869.42 635.08 234.34 1023.80 410.83 0.00 0.00 0.00
March 640.67 387.32 253.35 770.77 337.07 0.00 0.00 0.00
April 499.64 205.09 294.55 625.08 241.36 0.00 0.00 0.00
May 333.22 73.30 259.92 420.86 174.84 0.00 0.00 0.00
June 281.88 34.74 247.14 420.73 114.06 0.00 0.00 0.00
July 311.91 49.81 262.10 504.26 75.17 0.00 0.00 0.00
August 428.90 139.41 289.49 663.43 88.26 0.00 0.00 0.00
September 593.08 330.72 262.36 850.71 154.70 0.00 0.00 0.00
October 811.40 597.59 213.81 1045.46 260.12 0.00 0.00 0.00
November 903.74 693.62 210.12 1073.67 363.79 0.00 0.00 0.00
December 963.88 795.10 168.78 1117.44 460.37 0.00 0.00 0.00
                 
Annual Sum or Average 625.82 384.81 241.01 793.64 259.37 0.00 0.00 0.00
Minimum of Months 281.88 34.74 168.78 420.73 75.17 0.00 0.00 0.00
Maximum of Months 963.88 795.10 294.55 1117.44 460.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 381.43 217.52 163.91 353.69 555.74 0.00 0.00 0.00
February 491.02 283.65 207.37 489.38 520.14 0.00 0.00 0.00
March 548.42 291.93 256.48 580.61 423.49 0.00 0.00 0.00
April 699.95 372.52 327.43 805.68 298.25 0.00 0.00 0.00
May 663.65 341.96 321.69 823.02 210.17 0.00 0.00 0.00
June 711.43 396.97 314.46 992.04 148.17 0.00 0.00 0.00
July 641.69 314.03 327.66 932.71 102.67 0.00 0.00 0.00
August 655.69 303.29 352.41 919.53 120.18 0.00 0.00 0.00
September 592.25 311.91 280.33 789.76 185.28 0.00 0.00 0.00
October 541.82 336.76 205.06 638.09 330.03 0.00 0.00 0.00
November 425.33 250.23 175.10 415.05 473.27 0.00 0.00 0.00
December 367.82 230.66 137.16 329.71 620.21 0.00 0.00 0.00
                 
Annual Sum or Average 560.09 304.14 255.95 673.09 331.37 0.00 0.00 0.00
Minimum of Months 367.82 217.52 137.16 329.71 102.67 0.00 0.00 0.00
Maximum of Months 711.43 396.97 352.41 992.04 620.21 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 381.43 217.52 163.91 353.69 555.74 0.00 0.00 0.00
February 491.02 283.65 207.37 489.38 520.14 0.00 0.00 0.00
March 548.42 291.93 256.48 580.61 423.49 0.00 0.00 0.00
April 699.95 372.52 327.43 805.68 298.25 0.00 0.00 0.00
May 663.65 341.96 321.69 823.02 210.17 0.00 0.00 0.00
June 711.43 396.97 314.46 992.04 148.17 0.00 0.00 0.00
July 641.69 314.03 327.66 932.71 102.67 0.00 0.00 0.00
August 655.69 303.29 352.41 919.53 120.18 0.00 0.00 0.00
September 592.25 311.91 280.33 789.76 185.28 0.00 0.00 0.00
October 541.82 336.76 205.06 638.09 330.03 0.00 0.00 0.00
November 425.33 250.23 175.10 415.05 473.27 0.00 0.00 0.00
December 367.82 230.66 137.16 329.71 620.21 0.00 0.00 0.00
                 
Annual Sum or Average 560.09 304.14 255.95 673.09 331.37 0.00 0.00 0.00
Minimum of Months 367.82 217.52 137.16 329.71 102.67 0.00 0.00 0.00
Maximum of Months 711.43 396.97 352.41 992.04 620.21 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 381.42 217.51 163.91 353.69 555.73 0.00 0.00 0.00
February 491.02 283.65 207.37 489.37 520.13 0.00 0.00 0.00
March 548.41 291.93 256.48 580.60 423.48 0.00 0.00 0.00
April 699.93 372.51 327.43 805.67 298.25 0.00 0.00 0.00
May 663.64 341.95 321.69 823.00 210.16 0.00 0.00 0.00
June 711.42 396.96 314.45 992.03 148.17 0.00 0.00 0.00
July 641.68 314.03 327.65 932.69 102.67 0.00 0.00 0.00
August 655.68 303.28 352.40 919.52 120.18 0.00 0.00 0.00
September 592.23 311.91 280.33 789.75 185.28 0.00 0.00 0.00
October 541.81 336.76 205.06 638.08 330.02 0.00 0.00 0.00
November 425.32 250.23 175.10 415.04 473.26 0.00 0.00 0.00
December 367.82 230.66 137.16 329.70 620.20 0.00 0.00 0.00
                 
Annual Sum or Average 560.08 304.14 255.95 673.07 331.36 0.00 0.00 0.00
Minimum of Months 367.82 217.51 137.16 329.70 102.67 0.00 0.00 0.00
Maximum of Months 711.42 396.96 352.40 992.03 620.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 600.87 0.00 600.87 145.88 2238.36 0.00 0.00 0.00
February 750.99 0.00 750.99 297.00 2029.04 0.00 0.00 0.00
March 947.28 0.00 947.28 616.25 1610.15 0.00 0.00 0.00
April 1201.80 10.29 1191.51 989.26 1080.27 0.00 0.00 0.00
May 1306.37 84.23 1222.14 1372.46 786.39 0.00 0.00 0.00
June 1484.38 242.92 1241.47 2120.53 523.33 0.00 0.00 0.00
July 1362.43 113.40 1249.04 2109.84 352.83 0.00 0.00 0.00
August 1263.88 28.30 1235.59 1788.01 399.30 0.00 0.00 0.00
September 1010.72 0.26 1010.46 1215.96 711.46 0.00 0.00 0.00
October 754.20 0.00 754.20 564.56 1254.67 0.00 0.00 0.00
November 640.49 0.00 640.49 205.14 1785.33 0.00 0.00 0.00
December 511.43 0.00 511.43 48.30 2338.75 0.00 0.00 0.00
                 
Annual Sum or Average 987.10 40.02 947.07 959.58 1255.39 0.00 0.00 0.00
Minimum of Months 511.43 0.00 511.43 48.30 352.83 0.00 0.00 0.00
Maximum of Months 1484.38 242.92 1249.04 2120.53 2338.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1109.37 620.24 489.13 963.52 1385.62 0.00 0.00 0.00
February 1347.86 726.64 621.22 1281.99 1271.61 0.00 0.00 0.00
March 1778.03 1010.78 767.25 1909.23 1021.62 0.00 0.00 0.00
April 2429.15 1383.87 1045.28 2875.79 716.86 0.00 0.00 0.00
May 2317.93 1320.97 996.96 2909.38 545.00 0.00 0.00 0.00
June 2498.90 1539.44 959.46 3466.74 350.86 0.00 0.00 0.00
July 2312.28 1322.25 990.02 3349.02 242.22 0.00 0.00 0.00
August 2288.15 1261.50 1026.65 3212.23 273.27 0.00 0.00 0.00
September 1904.50 1065.59 838.92 2521.83 465.60 0.00 0.00 0.00
October 1656.33 1050.88 605.45 1922.73 799.08 0.00 0.00 0.00
November 1294.51 761.03 533.48 1262.83 1133.38 0.00 0.00 0.00
December 1048.92 638.36 410.56 918.03 1455.22 0.00 0.00 0.00
                 
Annual Sum or Average 1833.95 1059.78 774.18 2220.33 802.71 0.00 0.00 0.00
Minimum of Months 1048.92 620.24 410.56 918.03 242.22 0.00 0.00 0.00
Maximum of Months 2498.90 1539.44 1045.28 3466.74 1455.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 4442.26 3456.69 985.57 5092.03 2177.04 0.00 0.00 0.00
February 4347.36 3175.60 1171.76 5094.19 2021.55 0.00 0.00 0.00
March 3203.56 1936.75 1266.81 3838.55 1646.69 0.00 0.00 0.00
April 2498.36 1025.53 1472.83 3117.23 1175.28 0.00 0.00 0.00
May 1666.20 366.53 1299.67 2100.93 855.41 0.00 0.00 0.00
June 1409.47 173.70 1235.77 2114.94 559.49 0.00 0.00 0.00
July 1559.65 249.06 1310.59 2528.89 375.46 0.00 0.00 0.00
August 2144.63 697.11 1447.52 3314.91 441.79 0.00 0.00 0.00
September 2965.56 1653.69 1311.88 4229.44 768.11 0.00 0.00 0.00
October 4057.25 2988.14 1069.11 5197.82 1286.90 0.00 0.00 0.00
November 4519.00 3468.32 1050.68 5344.62 1782.80 0.00 0.00 0.00
December 4819.72 3975.77 843.96 5574.13 2229.94 0.00 0.00 0.00
                 
Annual Sum or Average 3129.29 1924.18 1205.11 3955.86 1272.83 0.00 0.00 0.00
Minimum of Months 1409.47 173.70 843.96 2100.93 375.46 0.00 0.00 0.00
Maximum of Months 4819.72 3975.77 1472.83 5574.13 2229.94 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1144.27 652.54 491.73 1097.33 1515.74 0.00 0.00 0.00
February 1473.06 850.94 622.12 1513.84 1396.50 0.00 0.00 0.00
March 1645.24 875.79 769.45 1789.35 1124.93 0.00 0.00 0.00
April 2099.82 1117.53 982.28 2456.12 798.87 0.00 0.00 0.00
May 1990.93 1025.87 965.06 2478.65 594.23 0.00 0.00 0.00
June 2134.28 1190.90 943.37 2994.06 414.84 0.00 0.00 0.00
July 1925.05 942.09 982.96 2825.10 277.91 0.00 0.00 0.00
August 1967.06 909.85 1057.21 2789.30 319.99 0.00 0.00 0.00
September 1776.72 935.73 840.99 2378.19 521.85 0.00 0.00 0.00
October 1625.46 1010.28 615.18 1942.70 892.16 0.00 0.00 0.00
November 1275.98 750.69 525.29 1293.89 1223.04 0.00 0.00 0.00
December 1103.46 691.99 411.47 1036.89 1562.49 0.00 0.00 0.00
                 
Annual Sum or Average 1680.26 912.42 767.84 2051.49 884.30 0.00 0.00 0.00
Minimum of Months 1103.46 652.54 411.47 1036.89 277.91 0.00 0.00 0.00
Maximum of Months 2134.28 1190.90 1057.21 2994.06 1562.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 600.87 0.00 600.87 179.75 2058.62 0.00 0.00 0.00
February 750.99 0.00 750.99 335.93 1874.33 0.00 0.00 0.00
March 947.28 0.00 947.28 658.14 1495.74 0.00 0.00 0.00
April 1201.80 10.29 1191.51 1010.56 1025.44 0.00 0.00 0.00
May 1306.37 84.23 1222.14 1376.27 766.80 0.00 0.00 0.00
June 1484.38 242.92 1241.47 2106.30 524.33 0.00 0.00 0.00
July 1362.43 113.40 1249.04 2086.93 362.90 0.00 0.00 0.00
August 1263.88 28.30 1235.59 1769.37 405.90 0.00 0.00 0.00
September 1010.72 0.26 1010.46 1212.41 697.84 0.00 0.00 0.00
October 754.20 0.00 754.20 587.47 1170.07 0.00 0.00 0.00
November 640.49 0.00 640.49 245.91 1614.56 0.00 0.00 0.00
December 511.43 0.00 511.43 67.37 2145.56 0.00 0.00 0.00
                 
Annual Sum or Average 987.10 40.02 947.07 973.00 1175.12 0.00 0.00 0.00
Minimum of Months 511.43 0.00 511.43 67.37 362.90 0.00 0.00 0.00
Maximum of Months 1484.38 242.92 1249.04 2106.30 2145.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1109.37 620.24 489.13 1005.51 1280.66 0.00 0.00 0.00
February 1347.86 726.64 621.22 1319.73 1181.16 0.00 0.00 0.00
March 1778.03 1010.78 767.25 1933.64 962.46 0.00 0.00 0.00
April 2429.15 1383.87 1045.28 2880.15 693.52 0.00 0.00 0.00
May 2317.93 1320.97 996.96 2903.36 536.26 0.00 0.00 0.00
June 2498.90 1539.44 959.46 3453.05 352.61 0.00 0.00 0.00
July 2312.28 1322.25 990.02 3332.27 249.16 0.00 0.00 0.00
August 2288.15 1261.50 1026.65 3197.46 278.80 0.00 0.00 0.00
September 1904.50 1065.59 838.92 2515.60 461.39 0.00 0.00 0.00
October 1656.33 1050.88 605.45 1935.29 759.40 0.00 0.00 0.00
November 1294.51 761.03 533.48 1301.37 1037.71 0.00 0.00 0.00
December 1048.92 638.36 410.56 949.66 1337.47 0.00 0.00 0.00
                 
Annual Sum or Average 1833.95 1059.78 774.18 2231.32 758.79 0.00 0.00 0.00
Minimum of Months 1048.92 620.24 410.56 949.66 249.16 0.00 0.00 0.00
Maximum of Months 2498.90 1539.44 1045.28 3453.05 1337.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 4442.26 3456.69 985.57 5147.80 2018.87 0.00 0.00 0.00
February 4347.36 3175.60 1171.76 5139.23 1881.57 0.00 0.00 0.00
March 3203.56 1936.75 1266.81 3870.19 1551.24 0.00 0.00 0.00
April 2498.36 1025.53 1472.83 3126.49 1125.07 0.00 0.00 0.00
May 1666.20 366.53 1299.67 2099.69 832.22 0.00 0.00 0.00
June 1409.47 173.70 1235.77 2101.50 556.28 0.00 0.00 0.00
July 1559.65 249.06 1310.59 2507.35 383.76 0.00 0.00 0.00
August 2144.63 697.11 1447.52 3294.87 447.80 0.00 0.00 0.00
September 2965.56 1653.69 1311.88 4220.04 758.07 0.00 0.00 0.00
October 4057.25 2988.14 1069.11 5215.31 1226.03 0.00 0.00 0.00
November 4519.00 3468.32 1050.68 5394.16 1650.71 0.00 0.00 0.00
December 4819.72 3975.77 843.96 5618.87 2058.37 0.00 0.00 0.00
                 
Annual Sum or Average 3129.29 1924.18 1205.11 3971.34 1203.99 0.00 0.00 0.00
Minimum of Months 1409.47 173.70 843.96 2099.69 383.76 0.00 0.00 0.00
Maximum of Months 4819.72 3975.77 1472.83 5618.87 2058.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1144.27 652.54 491.73 1118.14 1413.13 0.00 0.00 0.00
February 1473.06 850.94 622.12 1533.03 1309.40 0.00 0.00 0.00
March 1645.24 875.79 769.45 1807.29 1062.86 0.00 0.00 0.00
April 2099.82 1117.53 982.28 2461.70 768.44 0.00 0.00 0.00
May 1990.93 1025.87 965.06 2476.31 580.43 0.00 0.00 0.00
June 2134.28 1190.90 943.37 2983.45 413.06 0.00 0.00 0.00
July 1925.05 942.09 982.96 2810.27 282.00 0.00 0.00 0.00
August 1967.06 909.85 1057.21 2776.33 323.04 0.00 0.00 0.00
September 1776.72 935.73 840.99 2373.29 514.91 0.00 0.00 0.00
October 1625.46 1010.28 615.18 1950.54 848.28 0.00 0.00 0.00
November 1275.98 750.69 525.29 1315.75 1130.77 0.00 0.00 0.00
December 1103.46 691.99 411.47 1051.01 1454.43 0.00 0.00 0.00
                 
Annual Sum or Average 1680.26 912.42 767.84 2056.54 839.36 0.00 0.00 0.00
Minimum of Months 1103.46 652.54 411.47 1051.01 282.00 0.00 0.00 0.00
Maximum of Months 2134.28 1190.90 1057.21 2983.45 1454.43 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.321876E+09 0.00 0.321876E+09 52370366.11 0.132396E+10
February 0.363359E+09 0.00 0.363359E+09 0.113709E+09 0.108326E+10
March 0.507438E+09 0.00 0.507438E+09 0.298539E+09 0.943326E+09
April 0.623014E+09 5333940.93 0.617681E+09 0.491915E+09 0.601230E+09
May 0.699796E+09 45117755.73 0.654678E+09 0.725168E+09 0.438945E+09
June 0.769506E+09 0.125927E+09 0.643579E+09 0.109232E+10 0.277164E+09
July 0.729829E+09 60743208.74 0.669086E+09 0.112181E+10 0.190896E+09
August 0.677038E+09 15157315.94 0.661881E+09 0.948002E+09 0.218331E+09
September 0.523956E+09 134472.84 0.523822E+09 0.622377E+09 0.385461E+09
October 0.404009E+09 0.00 0.404009E+09 0.281775E+09 0.732029E+09
November 0.332032E+09 0.00 0.332032E+09 79814778.55 0.104446E+10
December 0.273965E+09 0.00 0.273965E+09 10933763.68 0.143113E+10
           
Annual Sum or Average 0.622582E+10 0.252414E+09 0.597340E+10 0.583873E+10 0.867020E+10
Minimum of Months 0.273965E+09 0.00 0.273965E+09 10933763.68 0.190896E+09
Maximum of Months 0.769506E+09 0.125927E+09 0.669086E+09 0.112181E+10 0.143113E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.321871E+09 0.00 0.321871E+09 52367919.50 0.132396E+10
February 0.363355E+09 0.00 0.363355E+09 0.113706E+09 0.108326E+10
March 0.507432E+09 0.00 0.507432E+09 0.298533E+09 0.943325E+09
April 0.623007E+09 5333823.67 0.617673E+09 0.491907E+09 0.601228E+09
May 0.699787E+09 45116763.87 0.654671E+09 0.725157E+09 0.438943E+09
June 0.769496E+09 0.125925E+09 0.643572E+09 0.109230E+10 0.277163E+09
July 0.729820E+09 60741873.38 0.669078E+09 0.112180E+10 0.190894E+09
August 0.677030E+09 15156982.73 0.661873E+09 0.947992E+09 0.218329E+09
September 0.523950E+09 134469.88 0.523815E+09 0.622371E+09 0.385459E+09
October 0.404004E+09 0.00 0.404004E+09 0.281772E+09 0.732027E+09
November 0.332027E+09 0.00 0.332027E+09 79811862.68 0.104446E+10
December 0.273961E+09 0.00 0.273961E+09 10932869.11 0.143113E+10
           
Annual Sum or Average 0.622574E+10 0.252408E+09 0.597333E+10 0.583865E+10 0.867018E+10
Minimum of Months 0.273961E+09 0.00 0.273961E+09 10932869.11 0.190894E+09
Maximum of Months 0.769496E+09 0.125925E+09 0.669078E+09 0.112180E+10 0.143113E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.321873E+09 0.00 0.321873E+09 52368735.03 0.132396E+10
February 0.363356E+09 0.00 0.363356E+09 0.113707E+09 0.108326E+10
March 0.507434E+09 0.00 0.507434E+09 0.298535E+09 0.943325E+09
April 0.623010E+09 5333862.76 0.617676E+09 0.491910E+09 0.601229E+09
May 0.699790E+09 45117094.49 0.654673E+09 0.725161E+09 0.438944E+09
June 0.769499E+09 0.125925E+09 0.643574E+09 0.109231E+10 0.277163E+09
July 0.729823E+09 60742318.50 0.669081E+09 0.112180E+10 0.190895E+09
August 0.677033E+09 15157093.80 0.661876E+09 0.947995E+09 0.218330E+09
September 0.523952E+09 134470.87 0.523817E+09 0.622373E+09 0.385460E+09
October 0.404006E+09 0.00 0.404006E+09 0.281773E+09 0.732028E+09
November 0.332029E+09 0.00 0.332029E+09 79812834.64 0.104446E+10
December 0.273963E+09 0.00 0.273963E+09 10933167.30 0.143113E+10
           
Annual Sum or Average 0.622577E+10 0.252410E+09 0.597336E+10 0.583868E+10 0.867019E+10
Minimum of Months 0.273963E+09 0.00 0.273963E+09 10933167.30 0.190895E+09
Maximum of Months 0.769499E+09 0.125925E+09 0.669081E+09 0.112180E+10 0.143113E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.321871E+09 0.00 0.321871E+09 52367919.50 0.132396E+10
February 0.363355E+09 0.00 0.363355E+09 0.113706E+09 0.108326E+10
March 0.507432E+09 0.00 0.507432E+09 0.298533E+09 0.943325E+09
April 0.623007E+09 5333823.67 0.617673E+09 0.491907E+09 0.601228E+09
May 0.699787E+09 45116763.87 0.654671E+09 0.725157E+09 0.438943E+09
June 0.769496E+09 0.125925E+09 0.643572E+09 0.109230E+10 0.277163E+09
July 0.729820E+09 60741873.38 0.669078E+09 0.112180E+10 0.190894E+09
August 0.677030E+09 15156982.73 0.661873E+09 0.947992E+09 0.218329E+09
September 0.523950E+09 134469.88 0.523815E+09 0.622371E+09 0.385459E+09
October 0.404004E+09 0.00 0.404004E+09 0.281772E+09 0.732027E+09
November 0.332027E+09 0.00 0.332027E+09 79811862.68 0.104446E+10
December 0.273961E+09 0.00 0.273961E+09 10932869.11 0.143113E+10
           
Annual Sum or Average 0.622574E+10 0.252408E+09 0.597333E+10 0.583865E+10 0.867018E+10
Minimum of Months 0.273961E+09 0.00 0.273961E+09 10932869.11 0.190894E+09
Maximum of Months 0.769496E+09 0.125925E+09 0.669078E+09 0.112180E+10 0.143113E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.321859E+09 0.00 0.321859E+09 52366216.59 0.132391E+10
February 0.363341E+09 0.00 0.363341E+09 0.113702E+09 0.108322E+10
March 0.507413E+09 0.00 0.507413E+09 0.298522E+09 0.943287E+09
April 0.622983E+09 5333628.24 0.617650E+09 0.491889E+09 0.601204E+09
May 0.699761E+09 45115110.77 0.654645E+09 0.725130E+09 0.438926E+09
June 0.769467E+09 0.125920E+09 0.643547E+09 0.109226E+10 0.277152E+09
July 0.729792E+09 60739647.76 0.669053E+09 0.112175E+10 0.190887E+09
August 0.677004E+09 15156427.37 0.661848E+09 0.947956E+09 0.218321E+09
September 0.523930E+09 134464.96 0.523795E+09 0.622347E+09 0.385444E+09
October 0.403989E+09 0.00 0.403989E+09 0.281761E+09 0.731998E+09
November 0.332015E+09 0.00 0.332015E+09 79809131.87 0.104442E+10
December 0.273951E+09 0.00 0.273951E+09 10932577.55 0.143107E+10
           
Annual Sum or Average 0.622550E+10 0.252399E+09 0.597310E+10 0.583843E+10 0.866984E+10
Minimum of Months 0.273951E+09 0.00 0.273951E+09 10932577.55 0.190887E+09
Maximum of Months 0.769467E+09 0.125920E+09 0.669053E+09 0.112175E+10 0.143107E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.990453E+09 0.553757E+09 0.436696E+09 0.831661E+09 0.133391E+10
February 0.108692E+10 0.585969E+09 0.500955E+09 0.101217E+10 0.109835E+10
March 0.158744E+10 0.902431E+09 0.685010E+09 0.169792E+10 0.956956E+09
April 0.209881E+10 0.119568E+10 0.903127E+09 0.249535E+10 0.627699E+09
May 0.206946E+10 0.117937E+10 0.890094E+09 0.261066E+10 0.494604E+09
June 0.215907E+10 0.133009E+10 0.828980E+09 0.300905E+10 0.298677E+09
July 0.206442E+10 0.118052E+10 0.883902E+09 0.300495E+10 0.200186E+09
August 0.204288E+10 0.112628E+10 0.916604E+09 0.288387E+10 0.226236E+09
September 0.164551E+10 0.920676E+09 0.724832E+09 0.218712E+10 0.408156E+09
October 0.147879E+10 0.938234E+09 0.540555E+09 0.171486E+10 0.744482E+09
November 0.111847E+10 0.657538E+09 0.460928E+09 0.107504E+10 0.105459E+10
December 0.936483E+09 0.569936E+09 0.366548E+09 0.796931E+09 0.142195E+10
           
Annual Sum or Average 0.192787E+11 0.111405E+11 0.813823E+10 0.233196E+11 0.886580E+10
Minimum of Months 0.936483E+09 0.553757E+09 0.366548E+09 0.796931E+09 0.200186E+09
Maximum of Months 0.215907E+10 0.133009E+10 0.916604E+09 0.300905E+10 0.142195E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.990453E+09 0.553757E+09 0.436696E+09 0.831661E+09 0.133391E+10
February 0.108692E+10 0.585969E+09 0.500955E+09 0.101217E+10 0.109835E+10
March 0.158744E+10 0.902431E+09 0.685010E+09 0.169792E+10 0.956956E+09
April 0.209881E+10 0.119568E+10 0.903127E+09 0.249535E+10 0.627699E+09
May 0.206946E+10 0.117937E+10 0.890094E+09 0.261066E+10 0.494604E+09
June 0.215907E+10 0.133009E+10 0.828980E+09 0.300905E+10 0.298677E+09
July 0.206442E+10 0.118052E+10 0.883902E+09 0.300495E+10 0.200186E+09
August 0.204288E+10 0.112628E+10 0.916604E+09 0.288387E+10 0.226236E+09
September 0.164551E+10 0.920676E+09 0.724832E+09 0.218712E+10 0.408156E+09
October 0.147879E+10 0.938234E+09 0.540555E+09 0.171486E+10 0.744482E+09
November 0.111847E+10 0.657538E+09 0.460928E+09 0.107504E+10 0.105459E+10
December 0.936483E+09 0.569936E+09 0.366548E+09 0.796931E+09 0.142195E+10
           
Annual Sum or Average 0.192787E+11 0.111405E+11 0.813823E+10 0.233196E+11 0.886580E+10
Minimum of Months 0.936483E+09 0.553757E+09 0.366548E+09 0.796931E+09 0.200186E+09
Maximum of Months 0.215907E+10 0.133009E+10 0.916604E+09 0.300905E+10 0.142195E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.990434E+09 0.553747E+09 0.436688E+09 0.831646E+09 0.133389E+10
February 0.108690E+10 0.585958E+09 0.500946E+09 0.101216E+10 0.109833E+10
March 0.158741E+10 0.902415E+09 0.684997E+09 0.169789E+10 0.956938E+09
April 0.209877E+10 0.119566E+10 0.903111E+09 0.249531E+10 0.627688E+09
May 0.206943E+10 0.117935E+10 0.890078E+09 0.261061E+10 0.494594E+09
June 0.215903E+10 0.133007E+10 0.828965E+09 0.300899E+10 0.298672E+09
July 0.206438E+10 0.118050E+10 0.883886E+09 0.300490E+10 0.200182E+09
August 0.204285E+10 0.112626E+10 0.916587E+09 0.288381E+10 0.226232E+09
September 0.164548E+10 0.920659E+09 0.724819E+09 0.218708E+10 0.408148E+09
October 0.147876E+10 0.938217E+09 0.540545E+09 0.171483E+10 0.744468E+09
November 0.111845E+10 0.657526E+09 0.460919E+09 0.107502E+10 0.105457E+10
December 0.936466E+09 0.569926E+09 0.366541E+09 0.796917E+09 0.142193E+10
           
Annual Sum or Average 0.192784E+11 0.111403E+11 0.813808E+10 0.233192E+11 0.886564E+10
Minimum of Months 0.936466E+09 0.553747E+09 0.366541E+09 0.796917E+09 0.200182E+09
Maximum of Months 0.215903E+10 0.133007E+10 0.916587E+09 0.300899E+10 0.142193E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.237958E+10 0.185164E+10 0.527943E+09 0.274063E+10 0.118180E+10
February 0.210339E+10 0.153645E+10 0.566938E+09 0.247689E+10 0.993910E+09
March 0.171605E+10 0.103745E+10 0.678598E+09 0.206452E+10 0.902850E+09
April 0.129513E+10 0.531625E+09 0.763509E+09 0.162027E+10 0.625643E+09
May 0.892543E+09 0.196341E+09 0.696202E+09 0.112727E+10 0.468324E+09
June 0.730663E+09 90045041.91 0.640618E+09 0.109059E+10 0.295667E+09
July 0.835464E+09 0.133414E+09 0.702050E+09 0.135065E+10 0.201336E+09
August 0.114882E+10 0.373422E+09 0.775399E+09 0.177701E+10 0.236399E+09
September 0.153732E+10 0.857252E+09 0.680071E+09 0.220514E+10 0.400991E+09
October 0.217335E+10 0.160065E+10 0.572693E+09 0.280029E+10 0.696735E+09
November 0.234261E+10 0.179794E+10 0.544666E+09 0.278307E+10 0.942986E+09
December 0.258178E+10 0.212969E+10 0.452085E+09 0.299309E+10 0.123310E+10
           
Annual Sum or Average 0.197367E+11 0.121359E+11 0.760077E+10 0.250294E+11 0.817974E+10
Minimum of Months 0.730663E+09 90045041.91 0.452085E+09 0.109059E+10 0.201336E+09
Maximum of Months 0.258178E+10 0.212969E+10 0.775399E+09 0.299309E+10 0.123310E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.237957E+10 0.185163E+10 0.527940E+09 0.274061E+10 0.118180E+10
February 0.210337E+10 0.153644E+10 0.566935E+09 0.247687E+10 0.993910E+09
March 0.171604E+10 0.103745E+10 0.678594E+09 0.206451E+10 0.902850E+09
April 0.129513E+10 0.531621E+09 0.763506E+09 0.162025E+10 0.625643E+09
May 0.892539E+09 0.196339E+09 0.696200E+09 0.112727E+10 0.468323E+09
June 0.730660E+09 90044382.05 0.640616E+09 0.109058E+10 0.295667E+09
July 0.835461E+09 0.133413E+09 0.702047E+09 0.135065E+10 0.201335E+09
August 0.114882E+10 0.373420E+09 0.775396E+09 0.177700E+10 0.236399E+09
September 0.153731E+10 0.857246E+09 0.680068E+09 0.220513E+10 0.400990E+09
October 0.217333E+10 0.160064E+10 0.572690E+09 0.280026E+10 0.696734E+09
November 0.234259E+10 0.179793E+10 0.544664E+09 0.278305E+10 0.942985E+09
December 0.258176E+10 0.212968E+10 0.452082E+09 0.299306E+10 0.123310E+10
           
Annual Sum or Average 0.197366E+11 0.121358E+11 0.760074E+10 0.250292E+11 0.817973E+10
Minimum of Months 0.730660E+09 90044382.05 0.452082E+09 0.109058E+10 0.201335E+09
Maximum of Months 0.258176E+10 0.212968E+10 0.775396E+09 0.299306E+10 0.123310E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.237958E+10 0.185164E+10 0.527943E+09 0.274063E+10 0.118180E+10
February 0.210339E+10 0.153645E+10 0.566938E+09 0.247689E+10 0.993910E+09
March 0.171605E+10 0.103745E+10 0.678598E+09 0.206452E+10 0.902850E+09
April 0.129513E+10 0.531625E+09 0.763509E+09 0.162027E+10 0.625643E+09
May 0.892543E+09 0.196341E+09 0.696202E+09 0.112727E+10 0.468324E+09
June 0.730663E+09 90045041.91 0.640618E+09 0.109059E+10 0.295667E+09
July 0.835464E+09 0.133414E+09 0.702050E+09 0.135065E+10 0.201336E+09
August 0.114882E+10 0.373422E+09 0.775399E+09 0.177701E+10 0.236399E+09
September 0.153732E+10 0.857252E+09 0.680071E+09 0.220514E+10 0.400991E+09
October 0.217335E+10 0.160065E+10 0.572693E+09 0.280029E+10 0.696735E+09
November 0.234261E+10 0.179794E+10 0.544666E+09 0.278307E+10 0.942986E+09
December 0.258178E+10 0.212969E+10 0.452085E+09 0.299309E+10 0.123310E+10
           
Annual Sum or Average 0.197367E+11 0.121359E+11 0.760077E+10 0.250294E+11 0.817974E+10
Minimum of Months 0.730663E+09 90045041.91 0.452085E+09 0.109059E+10 0.201336E+09
Maximum of Months 0.258178E+10 0.212969E+10 0.775399E+09 0.299309E+10 0.123310E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.237957E+10 0.185163E+10 0.527940E+09 0.274061E+10 0.118180E+10
February 0.210337E+10 0.153644E+10 0.566935E+09 0.247687E+10 0.993910E+09
March 0.171604E+10 0.103745E+10 0.678594E+09 0.206451E+10 0.902850E+09
April 0.129513E+10 0.531621E+09 0.763506E+09 0.162025E+10 0.625643E+09
May 0.892539E+09 0.196339E+09 0.696200E+09 0.112727E+10 0.468323E+09
June 0.730660E+09 90044382.05 0.640616E+09 0.109058E+10 0.295667E+09
July 0.835461E+09 0.133413E+09 0.702047E+09 0.135065E+10 0.201335E+09
August 0.114882E+10 0.373420E+09 0.775396E+09 0.177700E+10 0.236399E+09
September 0.153731E+10 0.857246E+09 0.680068E+09 0.220513E+10 0.400990E+09
October 0.217333E+10 0.160064E+10 0.572690E+09 0.280026E+10 0.696734E+09
November 0.234259E+10 0.179793E+10 0.544664E+09 0.278305E+10 0.942985E+09
December 0.258176E+10 0.212968E+10 0.452082E+09 0.299306E+10 0.123310E+10
           
Annual Sum or Average 0.197366E+11 0.121358E+11 0.760074E+10 0.250292E+11 0.817973E+10
Minimum of Months 0.730660E+09 90044382.05 0.452082E+09 0.109058E+10 0.201335E+09
Maximum of Months 0.258176E+10 0.212968E+10 0.775396E+09 0.299306E+10 0.123310E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.237948E+10 0.185156E+10 0.527920E+09 0.274051E+10 0.118175E+10
February 0.210329E+10 0.153638E+10 0.566914E+09 0.247678E+10 0.993870E+09
March 0.171598E+10 0.103741E+10 0.678569E+09 0.206443E+10 0.902814E+09
April 0.129508E+10 0.531602E+09 0.763477E+09 0.162020E+10 0.625618E+09
May 0.892505E+09 0.196332E+09 0.696173E+09 0.112722E+10 0.468305E+09
June 0.730632E+09 90041082.78 0.640591E+09 0.109054E+10 0.295655E+09
July 0.835429E+09 0.133408E+09 0.702020E+09 0.135060E+10 0.201327E+09
August 0.114877E+10 0.373406E+09 0.775366E+09 0.177693E+10 0.236390E+09
September 0.153726E+10 0.857215E+09 0.680042E+09 0.220504E+10 0.400974E+09
October 0.217325E+10 0.160058E+10 0.572668E+09 0.280016E+10 0.696707E+09
November 0.234250E+10 0.179786E+10 0.544643E+09 0.278294E+10 0.942948E+09
December 0.258167E+10 0.212960E+10 0.452065E+09 0.299296E+10 0.123305E+10
           
Annual Sum or Average 0.197358E+11 0.121354E+11 0.760045E+10 0.250283E+11 0.817940E+10
Minimum of Months 0.730632E+09 90041082.78 0.452065E+09 0.109054E+10 0.201327E+09
Maximum of Months 0.258167E+10 0.212960E+10 0.775366E+09 0.299296E+10 0.123305E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.102161E+10 0.582595E+09 0.439020E+09 0.947336E+09 0.148850E+10
February 0.118789E+10 0.686207E+09 0.501680E+09 0.118390E+10 0.125832E+10
March 0.146888E+10 0.781916E+09 0.686968E+09 0.155511E+10 0.113428E+10
April 0.181426E+10 0.965559E+09 0.848703E+09 0.208832E+10 0.773066E+09
May 0.177752E+10 0.915905E+09 0.861619E+09 0.220437E+10 0.562916E+09
June 0.184403E+10 0.102895E+10 0.815082E+09 0.257138E+10 0.384054E+09
July 0.171870E+10 0.841111E+09 0.877592E+09 0.249817E+10 0.274991E+09
August 0.175621E+10 0.812319E+09 0.943891E+09 0.246288E+10 0.321896E+09
September 0.153510E+10 0.808475E+09 0.726624E+09 0.204706E+10 0.480243E+09
October 0.145122E+10 0.901987E+09 0.549234E+09 0.170906E+10 0.883948E+09
November 0.110245E+10 0.648599E+09 0.453856E+09 0.107580E+10 0.122671E+10
December 0.985179E+09 0.617812E+09 0.367366E+09 0.883083E+09 0.166117E+10
           
Annual Sum or Average 0.176631E+11 0.959144E+10 0.807163E+10 0.212265E+11 0.104501E+11
Minimum of Months 0.985179E+09 0.582595E+09 0.367366E+09 0.883083E+09 0.274991E+09
Maximum of Months 0.184403E+10 0.102895E+10 0.943891E+09 0.257138E+10 0.166117E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.102161E+10 0.582595E+09 0.439020E+09 0.947336E+09 0.148850E+10
February 0.118789E+10 0.686207E+09 0.501680E+09 0.118390E+10 0.125832E+10
March 0.146888E+10 0.781916E+09 0.686968E+09 0.155511E+10 0.113428E+10
April 0.181426E+10 0.965559E+09 0.848703E+09 0.208832E+10 0.773066E+09
May 0.177752E+10 0.915905E+09 0.861619E+09 0.220437E+10 0.562916E+09
June 0.184403E+10 0.102895E+10 0.815082E+09 0.257138E+10 0.384054E+09
July 0.171870E+10 0.841111E+09 0.877592E+09 0.249817E+10 0.274991E+09
August 0.175621E+10 0.812319E+09 0.943891E+09 0.246288E+10 0.321896E+09
September 0.153510E+10 0.808475E+09 0.726624E+09 0.204706E+10 0.480243E+09
October 0.145122E+10 0.901987E+09 0.549234E+09 0.170906E+10 0.883948E+09
November 0.110245E+10 0.648599E+09 0.453856E+09 0.107580E+10 0.122671E+10
December 0.985179E+09 0.617812E+09 0.367366E+09 0.883083E+09 0.166117E+10
           
Annual Sum or Average 0.176631E+11 0.959144E+10 0.807163E+10 0.212265E+11 0.104501E+11
Minimum of Months 0.985179E+09 0.582595E+09 0.367366E+09 0.883083E+09 0.274991E+09
Maximum of Months 0.184403E+10 0.102895E+10 0.943891E+09 0.257138E+10 0.166117E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.102160E+10 0.582584E+09 0.439012E+09 0.947318E+09 0.148847E+10
February 0.118787E+10 0.686194E+09 0.501671E+09 0.118388E+10 0.125829E+10
March 0.146886E+10 0.781902E+09 0.686956E+09 0.155508E+10 0.113426E+10
April 0.181423E+10 0.965541E+09 0.848687E+09 0.208828E+10 0.773052E+09
May 0.177749E+10 0.915888E+09 0.861603E+09 0.220433E+10 0.562905E+09
June 0.184400E+10 0.102893E+10 0.815067E+09 0.257133E+10 0.384047E+09
July 0.171867E+10 0.841095E+09 0.877576E+09 0.249812E+10 0.274986E+09
August 0.175618E+10 0.812304E+09 0.943873E+09 0.246284E+10 0.321890E+09
September 0.153507E+10 0.808460E+09 0.726611E+09 0.204703E+10 0.480234E+09
October 0.145120E+10 0.901971E+09 0.549224E+09 0.170903E+10 0.883931E+09
November 0.110243E+10 0.648587E+09 0.453848E+09 0.107578E+10 0.122669E+10
December 0.985161E+09 0.617801E+09 0.367360E+09 0.883066E+09 0.166114E+10
           
Annual Sum or Average 0.176627E+11 0.959126E+10 0.807149E+10 0.212261E+11 0.104499E+11
Minimum of Months 0.985161E+09 0.582584E+09 0.367360E+09 0.883066E+09 0.274986E+09
Maximum of Months 0.184400E+10 0.102893E+10 0.943873E+09 0.257133E+10 0.166114E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.160938E+10 0.00 0.160938E+10 0.390720E+09 0.599523E+10
February 0.181679E+10 0.00 0.181679E+10 0.718495E+09 0.490865E+10
March 0.253719E+10 0.00 0.253719E+10 0.165056E+10 0.431261E+10
April 0.311507E+10 26669874.63 0.308840E+10 0.256415E+10 0.280006E+10
May 0.349897E+10 0.225590E+09 0.327338E+10 0.367599E+10 0.210626E+10
June 0.384753E+10 0.629640E+09 0.321789E+10 0.549642E+10 0.135647E+10
July 0.364914E+10 0.303718E+09 0.334542E+10 0.565099E+10 0.945012E+09
August 0.338519E+10 75787062.69 0.330940E+10 0.478900E+10 0.106949E+10
September 0.261977E+10 672368.48 0.261910E+10 0.315177E+10 0.184412E+10
October 0.202004E+10 0.00 0.202004E+10 0.151212E+10 0.336050E+10
November 0.166015E+10 0.00 0.166015E+10 0.531733E+09 0.462759E+10
December 0.136982E+10 0.00 0.136982E+10 0.129359E+09 0.626410E+10
           
Annual Sum or Average 0.311290E+11 0.126208E+10 0.298670E+11 0.302613E+11 0.395901E+11
Minimum of Months 0.136982E+10 0.00 0.136982E+10 0.129359E+09 0.945012E+09
Maximum of Months 0.384753E+10 0.629640E+09 0.334542E+10 0.565099E+10 0.626410E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.297133E+10 0.166125E+10 0.131007E+10 0.258069E+10 0.371124E+10
February 0.326074E+10 0.175789E+10 0.150285E+10 0.310139E+10 0.307627E+10
March 0.476227E+10 0.270727E+10 0.205501E+10 0.511368E+10 0.273630E+10
April 0.629636E+10 0.358700E+10 0.270935E+10 0.745406E+10 0.185810E+10
May 0.620833E+10 0.353808E+10 0.267025E+10 0.779248E+10 0.145973E+10
June 0.647715E+10 0.399023E+10 0.248692E+10 0.898579E+10 0.909429E+09
July 0.619320E+10 0.354153E+10 0.265168E+10 0.897002E+10 0.648774E+09
August 0.612859E+10 0.337881E+10 0.274978E+10 0.860365E+10 0.731927E+09
September 0.493647E+10 0.276200E+10 0.217447E+10 0.653658E+10 0.120683E+10
October 0.443632E+10 0.281467E+10 0.162165E+10 0.514984E+10 0.214025E+10
November 0.335536E+10 0.197259E+10 0.138277E+10 0.327325E+10 0.293772E+10
December 0.280942E+10 0.170979E+10 0.109963E+10 0.245885E+10 0.389767E+10
           
Annual Sum or Average 0.578356E+11 0.334211E+11 0.244144E+11 0.700203E+11 0.253142E+11
Minimum of Months 0.280942E+10 0.166125E+10 0.109963E+10 0.245885E+10 0.648774E+09
Maximum of Months 0.647715E+10 0.399023E+10 0.274978E+10 0.898579E+10 0.389767E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.118982E+11 0.925840E+10 0.263975E+10 0.136385E+11 0.583098E+10
February 0.105171E+11 0.768240E+10 0.283472E+10 0.123239E+11 0.489052E+10
March 0.858041E+10 0.518738E+10 0.339302E+10 0.102812E+11 0.441050E+10
April 0.647576E+10 0.265818E+10 0.381758E+10 0.807985E+10 0.304633E+10
May 0.446276E+10 0.981725E+09 0.348103E+10 0.562712E+10 0.229114E+10
June 0.365334E+10 0.450235E+09 0.320310E+10 0.548192E+10 0.145020E+10
July 0.417736E+10 0.667085E+09 0.351027E+10 0.677337E+10 0.100562E+10
August 0.574418E+10 0.186715E+10 0.387703E+10 0.887867E+10 0.118329E+10
September 0.768674E+10 0.428635E+10 0.340039E+10 0.109627E+11 0.199094E+10
October 0.108669E+11 0.800344E+10 0.286349E+10 0.139218E+11 0.344684E+10
November 0.117133E+11 0.898989E+10 0.272337E+10 0.138533E+11 0.462102E+10
December 0.129091E+11 0.106487E+11 0.226045E+10 0.149297E+11 0.597267E+10
           
Annual Sum or Average 0.986851E+11 0.606809E+11 0.380042E+11 0.124752E+12 0.401401E+11
Minimum of Months 0.365334E+10 0.450235E+09 0.226045E+10 0.548192E+10 0.100562E+10
Maximum of Months 0.129091E+11 0.106487E+11 0.387703E+10 0.149297E+11 0.597267E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.306481E+10 0.174777E+10 0.131705E+10 0.293909E+10 0.405975E+10
February 0.356362E+10 0.205860E+10 0.150502E+10 0.366228E+10 0.337842E+10
March 0.440661E+10 0.234573E+10 0.206088E+10 0.479259E+10 0.301302E+10
April 0.544273E+10 0.289665E+10 0.254608E+10 0.636628E+10 0.207068E+10
May 0.533252E+10 0.274769E+10 0.258483E+10 0.663881E+10 0.159159E+10
June 0.553204E+10 0.308682E+10 0.244522E+10 0.776060E+10 0.107527E+10
July 0.515606E+10 0.252331E+10 0.263275E+10 0.756675E+10 0.744348E+09
August 0.526857E+10 0.243693E+10 0.283164E+10 0.747087E+10 0.857062E+09
September 0.460525E+10 0.242540E+10 0.217985E+10 0.616427E+10 0.135264E+10
October 0.435362E+10 0.270593E+10 0.164769E+10 0.520334E+10 0.238957E+10
November 0.330733E+10 0.194578E+10 0.136155E+10 0.335376E+10 0.317012E+10
December 0.295551E+10 0.185342E+10 0.110209E+10 0.277720E+10 0.418496E+10
           
Annual Sum or Average 0.529887E+11 0.287740E+11 0.242147E+11 0.646958E+11 0.278874E+11
Minimum of Months 0.295551E+10 0.174777E+10 0.110209E+10 0.277720E+10 0.744348E+09
Maximum of Months 0.553204E+10 0.308682E+10 0.283164E+10 0.776060E+10 0.418496E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.160938E+10 0.00 0.160938E+10 0.481433E+09 0.551380E+10
February 0.181679E+10 0.00 0.181679E+10 0.812692E+09 0.453437E+10
March 0.253719E+10 0.00 0.253719E+10 0.176277E+10 0.400620E+10
April 0.311507E+10 26669874.63 0.308840E+10 0.261937E+10 0.265793E+10
May 0.349897E+10 0.225590E+09 0.327338E+10 0.368621E+10 0.205379E+10
June 0.384753E+10 0.629640E+09 0.321789E+10 0.545954E+10 0.135906E+10
July 0.364914E+10 0.303718E+09 0.334542E+10 0.558964E+10 0.971991E+09
August 0.338519E+10 75787062.69 0.330940E+10 0.473907E+10 0.108716E+10
September 0.261977E+10 672368.48 0.261910E+10 0.314256E+10 0.180880E+10
October 0.202004E+10 0.00 0.202004E+10 0.157348E+10 0.313390E+10
November 0.166015E+10 0.00 0.166015E+10 0.637395E+09 0.418495E+10
December 0.136982E+10 0.00 0.136982E+10 0.180455E+09 0.574667E+10
           
Annual Sum or Average 0.311290E+11 0.126208E+10 0.298670E+11 0.306846E+11 0.370586E+11
Minimum of Months 0.136982E+10 0.00 0.136982E+10 0.180455E+09 0.971991E+09
Maximum of Months 0.384753E+10 0.629640E+09 0.334542E+10 0.558964E+10 0.574667E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.297133E+10 0.166125E+10 0.131007E+10 0.269316E+10 0.343012E+10
February 0.326074E+10 0.175789E+10 0.150285E+10 0.319269E+10 0.285746E+10
March 0.476227E+10 0.270727E+10 0.205501E+10 0.517907E+10 0.257785E+10
April 0.629636E+10 0.358700E+10 0.270935E+10 0.746535E+10 0.179760E+10
May 0.620833E+10 0.353808E+10 0.267025E+10 0.777635E+10 0.143633E+10
June 0.647715E+10 0.399023E+10 0.248692E+10 0.895031E+10 0.913955E+09
July 0.619320E+10 0.354153E+10 0.265168E+10 0.892514E+10 0.667340E+09
August 0.612859E+10 0.337881E+10 0.274978E+10 0.856408E+10 0.746750E+09
September 0.493647E+10 0.276200E+10 0.217447E+10 0.652044E+10 0.119592E+10
October 0.443632E+10 0.281467E+10 0.162165E+10 0.518348E+10 0.203397E+10
November 0.335536E+10 0.197259E+10 0.138277E+10 0.337314E+10 0.268974E+10
December 0.280942E+10 0.170979E+10 0.109963E+10 0.254356E+10 0.358229E+10
           
Annual Sum or Average 0.578356E+11 0.334211E+11 0.244144E+11 0.703668E+11 0.239293E+11
Minimum of Months 0.280942E+10 0.166125E+10 0.109963E+10 0.254356E+10 0.667340E+09
Maximum of Months 0.647715E+10 0.399023E+10 0.274978E+10 0.895031E+10 0.358229E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.118982E+11 0.925840E+10 0.263975E+10 0.137879E+11 0.540733E+10
February 0.105171E+11 0.768240E+10 0.283472E+10 0.124328E+11 0.455189E+10
March 0.858041E+10 0.518738E+10 0.339302E+10 0.103659E+11 0.415484E+10
April 0.647576E+10 0.265818E+10 0.381758E+10 0.810386E+10 0.291618E+10
May 0.446276E+10 0.981725E+09 0.348103E+10 0.562381E+10 0.222902E+10
June 0.365334E+10 0.450235E+09 0.320310E+10 0.544709E+10 0.144188E+10
July 0.417736E+10 0.667085E+09 0.351027E+10 0.671568E+10 0.102787E+10
August 0.574418E+10 0.186715E+10 0.387703E+10 0.882497E+10 0.119938E+10
September 0.768674E+10 0.428635E+10 0.340039E+10 0.109383E+11 0.196491E+10
October 0.108669E+11 0.800344E+10 0.286349E+10 0.139687E+11 0.328380E+10
November 0.117133E+11 0.898989E+10 0.272337E+10 0.139817E+11 0.427865E+10
December 0.129091E+11 0.106487E+11 0.226045E+10 0.150496E+11 0.551315E+10
           
Annual Sum or Average 0.986851E+11 0.606809E+11 0.380042E+11 0.125240E+12 0.379689E+11
Minimum of Months 0.365334E+10 0.450235E+09 0.226045E+10 0.544709E+10 0.102787E+10
Maximum of Months 0.129091E+11 0.106487E+11 0.387703E+10 0.150496E+11 0.551315E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.306481E+10 0.174777E+10 0.131705E+10 0.299484E+10 0.378493E+10
February 0.356362E+10 0.205860E+10 0.150502E+10 0.370870E+10 0.316769E+10
March 0.440661E+10 0.234573E+10 0.206088E+10 0.484064E+10 0.284676E+10
April 0.544273E+10 0.289665E+10 0.254608E+10 0.638073E+10 0.199179E+10
May 0.533252E+10 0.274769E+10 0.258483E+10 0.663255E+10 0.155461E+10
June 0.553204E+10 0.308682E+10 0.244522E+10 0.773310E+10 0.107064E+10
July 0.515606E+10 0.252331E+10 0.263275E+10 0.752703E+10 0.755302E+09
August 0.526857E+10 0.243693E+10 0.283164E+10 0.743612E+10 0.865224E+09
September 0.460525E+10 0.242540E+10 0.217985E+10 0.615157E+10 0.133464E+10
October 0.435362E+10 0.270593E+10 0.164769E+10 0.522433E+10 0.227204E+10
November 0.330733E+10 0.194578E+10 0.136155E+10 0.341042E+10 0.293097E+10
December 0.295551E+10 0.185342E+10 0.110209E+10 0.281501E+10 0.389556E+10
           
Annual Sum or Average 0.529887E+11 0.287740E+11 0.242147E+11 0.648550E+11 0.264702E+11
Minimum of Months 0.295551E+10 0.174777E+10 0.110209E+10 0.281501E+10 0.755302E+09
Maximum of Months 0.553204E+10 0.308682E+10 0.283164E+10 0.773310E+10 0.389556E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 97.76 2471.53 600.86 0.00 600.86 0.00 0.00
February 235.01 2238.87 750.98 0.00 750.98 0.00 0.00
March 557.30 1760.97 947.26 0.00 947.26 0.00 0.00
April 948.89 1159.77 1201.78 10.29 1191.49 0.00 0.00
May 1353.71 819.41 1306.35 84.22 1222.12 0.00 0.00
June 2107.06 534.65 1484.36 242.91 1241.45 0.00 0.00
July 2094.14 356.36 1362.41 113.39 1249.02 0.00 0.00
August 1769.69 407.57 1263.86 28.29 1235.57 0.00 0.00
September 1200.56 743.55 1010.70 0.26 1010.44 0.00 0.00
October 526.01 1366.53 754.19 0.00 754.19 0.00 0.00
November 153.96 2014.77 640.48 0.00 640.48 0.00 0.00
December 20.41 2671.59 511.43 0.00 511.43 0.00 0.00
               
Annual Sum or Average 925.71 1374.64 987.08 40.02 947.06 0.00 0.00
Minimum of Months 20.41 356.36 511.43 0.00 511.43 0.00 0.00
Maximum of Months 2107.06 2671.59 1484.36 242.91 1249.02 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 931.51 1494.07 1109.37 620.24 489.13 0.00 0.00
February 1255.17 1362.03 1347.86 726.64 621.22 0.00 0.00
March 1901.78 1071.85 1778.04 1010.78 767.26 0.00 0.00
April 2888.12 726.50 2429.16 1383.88 1045.28 0.00 0.00
May 2924.10 553.99 2317.93 1320.97 996.96 0.00 0.00
June 3482.67 345.69 2498.91 1539.45 959.46 0.00 0.00
July 3365.74 224.22 2312.29 1322.26 990.03 0.00 0.00
August 3230.12 253.40 2288.16 1261.51 1026.66 0.00 0.00
September 2531.37 472.40 1904.51 1065.59 838.92 0.00 0.00
October 1920.75 833.87 1656.34 1050.88 605.46 0.00 0.00
November 1244.25 1220.58 1294.51 761.03 533.48 0.00 0.00
December 892.61 1592.68 1048.92 638.37 410.56 0.00 0.00
               
Annual Sum or Average 2218.36 843.39 1833.96 1059.78 774.18 0.00 0.00
Minimum of Months 892.61 224.22 1048.92 620.24 410.56 0.00 0.00
Maximum of Months 3482.67 1592.68 2498.91 1539.45 1045.28 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 5116.11 2206.15 4442.12 3456.58 985.55 0.00 0.00
February 5119.18 2054.20 4347.23 3175.49 1171.73 0.00 0.00
March 3853.97 1685.41 3203.47 1936.68 1266.78 0.00 0.00
April 3125.48 1206.86 2498.30 1025.50 1472.80 0.00 0.00
May 2104.35 874.25 1666.17 366.52 1299.65 0.00 0.00
June 2103.74 570.34 1409.44 173.70 1235.75 0.00 0.00
July 2521.36 375.85 1559.62 249.05 1310.56 0.00 0.00
August 3317.26 441.30 2144.58 697.09 1447.49 0.00 0.00
September 4253.70 773.51 2965.48 1653.63 1311.85 0.00 0.00
October 5227.47 1300.64 4057.13 2988.04 1069.08 0.00 0.00
November 5368.51 1819.02 4518.86 3468.21 1050.66 0.00 0.00
December 5587.39 2301.91 4819.57 3975.64 843.94 0.00 0.00
               
Annual Sum or Average 3968.34 1296.88 3129.20 1924.12 1205.08 0.00 0.00
Minimum of Months 2103.74 375.85 1409.44 173.70 843.94 0.00 0.00
Maximum of Months 5587.39 2301.91 4819.57 3975.64 1472.80 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1061.08 1667.21 1144.27 652.54 491.73 0.00 0.00
February 1468.12 1560.40 1473.07 850.95 622.12 0.00 0.00
March 1741.82 1270.46 1645.25 875.80 769.45 0.00 0.00
April 2417.03 894.75 2099.83 1117.54 982.29 0.00 0.00
May 2469.04 630.50 1990.94 1025.87 965.07 0.00 0.00
June 2976.11 444.50 2134.28 1190.91 943.38 0.00 0.00
July 2798.11 308.01 1925.06 942.10 982.96 0.00 0.00
August 2758.59 360.54 1967.07 909.85 1057.22 0.00 0.00
September 2369.27 555.83 1776.72 935.73 841.00 0.00 0.00
October 1914.26 990.08 1625.46 1010.28 615.18 0.00 0.00
November 1245.13 1419.79 1275.98 750.69 525.29 0.00 0.00
December 989.11 1860.62 1103.46 691.99 411.47 0.00 0.00
               
Annual Sum or Average 2019.25 994.10 1680.27 912.42 767.84 0.00 0.00
Minimum of Months 989.11 308.01 1103.46 652.54 411.47 0.00 0.00
Maximum of Months 2976.11 1860.62 2134.28 1190.91 1057.22 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 145.88 2238.36 600.87 0.00 600.87 0.00 0.00
February 297.00 2029.04 750.99 0.00 750.99 0.00 0.00
March 616.25 1610.15 947.28 0.00 947.28 0.00 0.00
April 989.26 1080.27 1201.80 10.29 1191.51 0.00 0.00
May 1372.46 786.39 1306.37 84.23 1222.14 0.00 0.00
June 2120.53 523.33 1484.38 242.92 1241.47 0.00 0.00
July 2109.84 352.83 1362.43 113.40 1249.04 0.00 0.00
August 1788.01 399.30 1263.88 28.30 1235.59 0.00 0.00
September 1215.96 711.46 1010.72 0.26 1010.46 0.00 0.00
October 564.56 1254.67 754.20 0.00 754.20 0.00 0.00
November 205.14 1785.33 640.49 0.00 640.49 0.00 0.00
December 48.30 2338.75 511.43 0.00 511.43 0.00 0.00
               
Annual Sum or Average 959.58 1255.39 987.10 40.02 947.07 0.00 0.00
Minimum of Months 48.30 352.83 511.43 0.00 511.43 0.00 0.00
Maximum of Months 2120.53 2338.75 1484.38 242.92 1249.04 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 963.52 1385.62 1109.37 620.24 489.13 0.00 0.00
February 1281.99 1271.61 1347.86 726.64 621.22 0.00 0.00
March 1909.23 1021.62 1778.03 1010.78 767.25 0.00 0.00
April 2875.79 716.86 2429.15 1383.87 1045.28 0.00 0.00
May 2909.38 545.00 2317.93 1320.97 996.96 0.00 0.00
June 3466.74 350.86 2498.90 1539.44 959.46 0.00 0.00
July 3349.02 242.22 2312.28 1322.25 990.02 0.00 0.00
August 3212.23 273.27 2288.15 1261.50 1026.65 0.00 0.00
September 2521.83 465.60 1904.50 1065.59 838.92 0.00 0.00
October 1922.73 799.08 1656.33 1050.88 605.45 0.00 0.00
November 1262.83 1133.38 1294.51 761.03 533.48 0.00 0.00
December 918.03 1455.22 1048.92 638.36 410.56 0.00 0.00
               
Annual Sum or Average 2220.33 802.71 1833.95 1059.78 774.18 0.00 0.00
Minimum of Months 918.03 242.22 1048.92 620.24 410.56 0.00 0.00
Maximum of Months 3466.74 1455.22 2498.90 1539.44 1045.28 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 5092.03 2177.04 4442.26 3456.69 985.57 0.00 0.00
February 5094.19 2021.55 4347.36 3175.60 1171.76 0.00 0.00
March 3838.55 1646.69 3203.56 1936.75 1266.81 0.00 0.00
April 3117.23 1175.28 2498.36 1025.53 1472.83 0.00 0.00
May 2100.93 855.41 1666.20 366.53 1299.67 0.00 0.00
June 2114.94 559.49 1409.47 173.70 1235.77 0.00 0.00
July 2528.89 375.46 1559.65 249.06 1310.59 0.00 0.00
August 3314.91 441.79 2144.63 697.11 1447.52 0.00 0.00
September 4229.44 768.11 2965.56 1653.69 1311.88 0.00 0.00
October 5197.82 1286.90 4057.25 2988.14 1069.11 0.00 0.00
November 5344.62 1782.80 4519.00 3468.32 1050.68 0.00 0.00
December 5574.13 2229.94 4819.72 3975.77 843.96 0.00 0.00
               
Annual Sum or Average 3955.86 1272.83 3129.29 1924.18 1205.11 0.00 0.00
Minimum of Months 2100.93 375.46 1409.47 173.70 843.96 0.00 0.00
Maximum of Months 5574.13 2229.94 4819.72 3975.77 1472.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1097.33 1515.74 1144.27 652.54 491.73 0.00 0.00
February 1513.84 1396.50 1473.06 850.94 622.12 0.00 0.00
March 1789.35 1124.93 1645.24 875.79 769.45 0.00 0.00
April 2456.12 798.87 2099.82 1117.53 982.28 0.00 0.00
May 2478.65 594.23 1990.93 1025.87 965.06 0.00 0.00
June 2994.06 414.84 2134.28 1190.90 943.37 0.00 0.00
July 2825.10 277.91 1925.05 942.09 982.96 0.00 0.00
August 2789.30 319.99 1967.06 909.85 1057.21 0.00 0.00
September 2378.19 521.85 1776.72 935.73 840.99 0.00 0.00
October 1942.70 892.16 1625.46 1010.28 615.18 0.00 0.00
November 1293.89 1223.04 1275.98 750.69 525.29 0.00 0.00
December 1036.89 1562.49 1103.46 691.99 411.47 0.00 0.00
               
Annual Sum or Average 2051.49 884.30 1680.26 912.42 767.84 0.00 0.00
Minimum of Months 1036.89 277.91 1103.46 652.54 411.47 0.00 0.00
Maximum of Months 2994.06 1562.49 2134.28 1190.90 1057.21 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 179.75 2058.62 600.87 0.00 600.87 0.00 0.00
February 335.93 1874.33 750.99 0.00 750.99 0.00 0.00
March 658.14 1495.74 947.28 0.00 947.28 0.00 0.00
April 1010.56 1025.44 1201.80 10.29 1191.51 0.00 0.00
May 1376.27 766.80 1306.37 84.23 1222.14 0.00 0.00
June 2106.30 524.33 1484.38 242.92 1241.47 0.00 0.00
July 2086.93 362.90 1362.43 113.40 1249.04 0.00 0.00
August 1769.37 405.90 1263.88 28.30 1235.59 0.00 0.00
September 1212.41 697.84 1010.72 0.26 1010.46 0.00 0.00
October 587.47 1170.07 754.20 0.00 754.20 0.00 0.00
November 245.91 1614.56 640.49 0.00 640.49 0.00 0.00
December 67.37 2145.56 511.43 0.00 511.43 0.00 0.00
               
Annual Sum or Average 973.00 1175.12 987.10 40.02 947.07 0.00 0.00
Minimum of Months 67.37 362.90 511.43 0.00 511.43 0.00 0.00
Maximum of Months 2106.30 2145.56 1484.38 242.92 1249.04 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1005.51 1280.66 1109.37 620.24 489.13 0.00 0.00
February 1319.73 1181.16 1347.86 726.64 621.22 0.00 0.00
March 1933.64 962.46 1778.03 1010.78 767.25 0.00 0.00
April 2880.15 693.52 2429.15 1383.87 1045.28 0.00 0.00
May 2903.36 536.26 2317.93 1320.97 996.96 0.00 0.00
June 3453.05 352.61 2498.90 1539.44 959.46 0.00 0.00
July 3332.27 249.16 2312.28 1322.25 990.02 0.00 0.00
August 3197.46 278.80 2288.15 1261.50 1026.65 0.00 0.00
September 2515.60 461.39 1904.50 1065.59 838.92 0.00 0.00
October 1935.29 759.40 1656.33 1050.88 605.45 0.00 0.00
November 1301.37 1037.71 1294.51 761.03 533.48 0.00 0.00
December 949.66 1337.47 1048.92 638.36 410.56 0.00 0.00
               
Annual Sum or Average 2231.32 758.79 1833.95 1059.78 774.18 0.00 0.00
Minimum of Months 949.66 249.16 1048.92 620.24 410.56 0.00 0.00
Maximum of Months 3453.05 1337.47 2498.90 1539.44 1045.28 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 5147.80 2018.87 4442.26 3456.69 985.57 0.00 0.00
February 5139.23 1881.57 4347.36 3175.60 1171.76 0.00 0.00
March 3870.19 1551.24 3203.56 1936.75 1266.81 0.00 0.00
April 3126.49 1125.07 2498.36 1025.53 1472.83 0.00 0.00
May 2099.69 832.22 1666.20 366.53 1299.67 0.00 0.00
June 2101.50 556.28 1409.47 173.70 1235.77 0.00 0.00
July 2507.35 383.76 1559.65 249.06 1310.59 0.00 0.00
August 3294.87 447.80 2144.63 697.11 1447.52 0.00 0.00
September 4220.04 758.07 2965.56 1653.69 1311.88 0.00 0.00
October 5215.31 1226.03 4057.25 2988.14 1069.11 0.00 0.00
November 5394.16 1650.71 4519.00 3468.32 1050.68 0.00 0.00
December 5618.87 2058.37 4819.72 3975.77 843.96 0.00 0.00
               
Annual Sum or Average 3971.34 1203.99 3129.29 1924.18 1205.11 0.00 0.00
Minimum of Months 2099.69 383.76 1409.47 173.70 843.96 0.00 0.00
Maximum of Months 5618.87 2058.37 4819.72 3975.77 1472.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1118.14 1413.13 1144.27 652.54 491.73 0.00 0.00
February 1533.03 1309.40 1473.06 850.94 622.12 0.00 0.00
March 1807.29 1062.86 1645.24 875.79 769.45 0.00 0.00
April 2461.70 768.44 2099.82 1117.53 982.28 0.00 0.00
May 2476.31 580.43 1990.93 1025.87 965.06 0.00 0.00
June 2983.45 413.06 2134.28 1190.90 943.37 0.00 0.00
July 2810.27 282.00 1925.05 942.09 982.96 0.00 0.00
August 2776.33 323.04 1967.06 909.85 1057.21 0.00 0.00
September 2373.29 514.91 1776.72 935.73 840.99 0.00 0.00
October 1950.54 848.28 1625.46 1010.28 615.18 0.00 0.00
November 1315.75 1130.77 1275.98 750.69 525.29 0.00 0.00
December 1051.01 1454.43 1103.46 691.99 411.47 0.00 0.00
               
Annual Sum or Average 2056.54 839.36 1680.26 912.42 767.84 0.00 0.00
Minimum of Months 1051.01 282.00 1103.46 652.54 411.47 0.00 0.00
Maximum of Months 2983.45 1454.43 2134.28 1190.90 1057.21 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.261841E+09 0.661975E+10 0.160935E+10 0.00 0.160935E+10 0.00 0.00
February 0.568530E+09 0.541628E+10 0.181676E+10 0.00 0.181676E+10 0.00 0.00
March 0.149266E+10 0.471659E+10 0.253715E+10 0.00 0.253715E+10 0.00 0.00
April 0.245953E+10 0.300612E+10 0.311502E+10 26669079.28 0.308835E+10 0.00 0.00
May 0.362577E+10 0.219470E+10 0.349892E+10 0.225583E+09 0.327334E+10 0.00 0.00
June 0.546150E+10 0.138580E+10 0.384746E+10 0.629622E+09 0.321784E+10 0.00 0.00
July 0.560895E+10 0.954465E+09 0.364909E+10 0.303709E+09 0.334538E+10 0.00 0.00
August 0.473994E+10 0.109164E+10 0.338514E+10 75784802.57 0.330935E+10 0.00 0.00
September 0.311184E+10 0.192728E+10 0.261974E+10 672348.43 0.261907E+10 0.00 0.00
October 0.140885E+10 0.366011E+10 0.202001E+10 0.00 0.202001E+10 0.00 0.00
November 0.399060E+09 0.522227E+10 0.166013E+10 0.00 0.166013E+10 0.00 0.00
December 54665246.74 0.715558E+10 0.136980E+10 0.00 0.136980E+10 0.00 0.00
               
Annual Sum or Average 0.291931E+11 0.433506E+11 0.311286E+11 0.126204E+10 0.298665E+11 0.00 0.00
Minimum of Months 54665246.74 0.954465E+09 0.136980E+10 0.00 0.136980E+10 0.00 0.00
Maximum of Months 0.560895E+10 0.715558E+10 0.384746E+10 0.629622E+09 0.334538E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.249497E+10 0.400171E+10 0.297134E+10 0.166126E+10 0.131008E+10 0.00 0.00
February 0.303650E+10 0.329503E+10 0.326075E+10 0.175790E+10 0.150286E+10 0.00 0.00
March 0.509372E+10 0.287085E+10 0.476229E+10 0.270728E+10 0.205502E+10 0.00 0.00
April 0.748601E+10 0.188309E+10 0.629638E+10 0.358702E+10 0.270937E+10 0.00 0.00
May 0.783192E+10 0.148380E+10 0.620836E+10 0.353809E+10 0.267027E+10 0.00 0.00
June 0.902709E+10 0.896027E+09 0.647718E+10 0.399025E+10 0.248693E+10 0.00 0.00
July 0.901480E+10 0.600554E+09 0.619323E+10 0.354154E+10 0.265169E+10 0.00 0.00
August 0.865155E+10 0.678703E+09 0.612862E+10 0.337882E+10 0.274979E+10 0.00 0.00
September 0.656131E+10 0.122446E+10 0.493649E+10 0.276201E+10 0.217448E+10 0.00 0.00
October 0.514454E+10 0.223343E+10 0.443634E+10 0.281469E+10 0.162166E+10 0.00 0.00
November 0.322510E+10 0.316375E+10 0.335538E+10 0.197260E+10 0.138278E+10 0.00 0.00
December 0.239078E+10 0.426584E+10 0.280943E+10 0.170980E+10 0.109964E+10 0.00 0.00
               
Annual Sum or Average 0.699583E+11 0.265972E+11 0.578358E+11 0.334213E+11 0.244145E+11 0.00 0.00
Minimum of Months 0.239078E+10 0.600554E+09 0.280943E+10 0.166126E+10 0.109964E+10 0.00 0.00
Maximum of Months 0.902709E+10 0.426584E+10 0.647718E+10 0.399025E+10 0.274979E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.137030E+11 0.590894E+10 0.118978E+11 0.925810E+10 0.263969E+10 0.00 0.00
February 0.123843E+11 0.496951E+10 0.105168E+11 0.768215E+10 0.283466E+10 0.00 0.00
March 0.103225E+11 0.451421E+10 0.858016E+10 0.518721E+10 0.339295E+10 0.00 0.00
April 0.810124E+10 0.312819E+10 0.647560E+10 0.265810E+10 0.381751E+10 0.00 0.00
May 0.563630E+10 0.234160E+10 0.446267E+10 0.981693E+09 0.348098E+10 0.00 0.00
June 0.545289E+10 0.147832E+10 0.365328E+10 0.450220E+09 0.320306E+10 0.00 0.00
July 0.675321E+10 0.100667E+10 0.417728E+10 0.667063E+09 0.351022E+10 0.00 0.00
August 0.888495E+10 0.118199E+10 0.574405E+10 0.186709E+10 0.387696E+10 0.00 0.00
September 0.110256E+11 0.200494E+10 0.768653E+10 0.428621E+10 0.340032E+10 0.00 0.00
October 0.140013E+11 0.348364E+10 0.108666E+11 0.800317E+10 0.286343E+10 0.00 0.00
November 0.139152E+11 0.471489E+10 0.117129E+11 0.898959E+10 0.272330E+10 0.00 0.00
December 0.149653E+11 0.616543E+10 0.129087E+11 0.106483E+11 0.226040E+10 0.00 0.00
               
Annual Sum or Average 0.125146E+12 0.408983E+11 0.986824E+11 0.606790E+11 0.380035E+11 0.00 0.00
Minimum of Months 0.545289E+10 0.100667E+10 0.365328E+10 0.450220E+09 0.226040E+10 0.00 0.00
Maximum of Months 0.149653E+11 0.616543E+10 0.129087E+11 0.106483E+11 0.387696E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.284199E+10 0.446547E+10 0.306482E+10 0.174777E+10 0.131705E+10 0.00 0.00
February 0.355167E+10 0.377493E+10 0.356364E+10 0.205861E+10 0.150503E+10 0.00 0.00
March 0.466529E+10 0.340281E+10 0.440663E+10 0.234573E+10 0.206089E+10 0.00 0.00
April 0.626493E+10 0.231918E+10 0.544275E+10 0.289666E+10 0.254609E+10 0.00 0.00
May 0.661308E+10 0.168874E+10 0.533254E+10 0.274770E+10 0.258484E+10 0.00 0.00
June 0.771408E+10 0.115215E+10 0.553207E+10 0.308684E+10 0.244523E+10 0.00 0.00
July 0.749445E+10 0.824969E+09 0.515608E+10 0.252332E+10 0.263276E+10 0.00 0.00
August 0.738860E+10 0.965681E+09 0.526860E+10 0.243694E+10 0.283165E+10 0.00 0.00
September 0.614115E+10 0.144072E+10 0.460527E+10 0.242541E+10 0.217986E+10 0.00 0.00
October 0.512716E+10 0.265183E+10 0.435364E+10 0.270594E+10 0.164769E+10 0.00 0.00
November 0.322739E+10 0.368010E+10 0.330734E+10 0.194579E+10 0.136156E+10 0.00 0.00
December 0.264923E+10 0.498349E+10 0.295552E+10 0.185343E+10 0.110209E+10 0.00 0.00
               
Annual Sum or Average 0.636790E+11 0.313501E+11 0.529889E+11 0.287741E+11 0.242148E+11 0.00 0.00
Minimum of Months 0.264923E+10 0.824969E+09 0.295552E+10 0.174777E+10 0.110209E+10 0.00 0.00
Maximum of Months 0.771408E+10 0.498349E+10 0.553207E+10 0.308684E+10 0.283165E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.390720E+09 0.599523E+10 0.160938E+10 0.00 0.160938E+10 0.00 0.00
February 0.718495E+09 0.490865E+10 0.181679E+10 0.00 0.181679E+10 0.00 0.00
March 0.165056E+10 0.431261E+10 0.253719E+10 0.00 0.253719E+10 0.00 0.00
April 0.256415E+10 0.280006E+10 0.311507E+10 26669874.63 0.308840E+10 0.00 0.00
May 0.367599E+10 0.210626E+10 0.349897E+10 0.225590E+09 0.327338E+10 0.00 0.00
June 0.549642E+10 0.135647E+10 0.384753E+10 0.629640E+09 0.321789E+10 0.00 0.00
July 0.565099E+10 0.945012E+09 0.364914E+10 0.303718E+09 0.334542E+10 0.00 0.00
August 0.478900E+10 0.106949E+10 0.338519E+10 75787062.69 0.330940E+10 0.00 0.00
September 0.315177E+10 0.184412E+10 0.261977E+10 672368.48 0.261910E+10 0.00 0.00
October 0.151212E+10 0.336050E+10 0.202004E+10 0.00 0.202004E+10 0.00 0.00
November 0.531733E+09 0.462759E+10 0.166015E+10 0.00 0.166015E+10 0.00 0.00
December 0.129359E+09 0.626410E+10 0.136982E+10 0.00 0.136982E+10 0.00 0.00
               
Annual Sum or Average 0.302613E+11 0.395901E+11 0.311290E+11 0.126208E+10 0.298670E+11 0.00 0.00
Minimum of Months 0.129359E+09 0.945012E+09 0.136982E+10 0.00 0.136982E+10 0.00 0.00
Maximum of Months 0.565099E+10 0.626410E+10 0.384753E+10 0.629640E+09 0.334542E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.258069E+10 0.371124E+10 0.297133E+10 0.166125E+10 0.131007E+10 0.00 0.00
February 0.310139E+10 0.307627E+10 0.326074E+10 0.175789E+10 0.150285E+10 0.00 0.00
March 0.511368E+10 0.273630E+10 0.476227E+10 0.270727E+10 0.205501E+10 0.00 0.00
April 0.745406E+10 0.185810E+10 0.629636E+10 0.358700E+10 0.270935E+10 0.00 0.00
May 0.779248E+10 0.145973E+10 0.620833E+10 0.353808E+10 0.267025E+10 0.00 0.00
June 0.898579E+10 0.909429E+09 0.647715E+10 0.399023E+10 0.248692E+10 0.00 0.00
July 0.897002E+10 0.648774E+09 0.619320E+10 0.354153E+10 0.265168E+10 0.00 0.00
August 0.860365E+10 0.731927E+09 0.612859E+10 0.337881E+10 0.274978E+10 0.00 0.00
September 0.653658E+10 0.120683E+10 0.493647E+10 0.276200E+10 0.217447E+10 0.00 0.00
October 0.514984E+10 0.214025E+10 0.443632E+10 0.281467E+10 0.162165E+10 0.00 0.00
November 0.327325E+10 0.293772E+10 0.335536E+10 0.197259E+10 0.138277E+10 0.00 0.00
December 0.245885E+10 0.389767E+10 0.280942E+10 0.170979E+10 0.109963E+10 0.00 0.00
               
Annual Sum or Average 0.700203E+11 0.253142E+11 0.578356E+11 0.334211E+11 0.244144E+11 0.00 0.00
Minimum of Months 0.245885E+10 0.648774E+09 0.280942E+10 0.166125E+10 0.109963E+10 0.00 0.00
Maximum of Months 0.898579E+10 0.389767E+10 0.647715E+10 0.399023E+10 0.274978E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.136385E+11 0.583098E+10 0.118982E+11 0.925840E+10 0.263975E+10 0.00 0.00
February 0.123239E+11 0.489052E+10 0.105171E+11 0.768240E+10 0.283472E+10 0.00 0.00
March 0.102812E+11 0.441050E+10 0.858041E+10 0.518738E+10 0.339302E+10 0.00 0.00
April 0.807985E+10 0.304633E+10 0.647576E+10 0.265818E+10 0.381758E+10 0.00 0.00
May 0.562712E+10 0.229114E+10 0.446276E+10 0.981725E+09 0.348103E+10 0.00 0.00
June 0.548192E+10 0.145020E+10 0.365334E+10 0.450235E+09 0.320310E+10 0.00 0.00
July 0.677337E+10 0.100562E+10 0.417736E+10 0.667085E+09 0.351027E+10 0.00 0.00
August 0.887867E+10 0.118329E+10 0.574418E+10 0.186715E+10 0.387703E+10 0.00 0.00
September 0.109627E+11 0.199094E+10 0.768674E+10 0.428635E+10 0.340039E+10 0.00 0.00
October 0.139218E+11 0.344684E+10 0.108669E+11 0.800344E+10 0.286349E+10 0.00 0.00
November 0.138533E+11 0.462102E+10 0.117133E+11 0.898989E+10 0.272337E+10 0.00 0.00
December 0.149297E+11 0.597267E+10 0.129091E+11 0.106487E+11 0.226045E+10 0.00 0.00
               
Annual Sum or Average 0.124752E+12 0.401401E+11 0.986851E+11 0.606809E+11 0.380042E+11 0.00 0.00
Minimum of Months 0.548192E+10 0.100562E+10 0.365334E+10 0.450235E+09 0.226045E+10 0.00 0.00
Maximum of Months 0.149297E+11 0.597267E+10 0.129091E+11 0.106487E+11 0.387703E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.293909E+10 0.405975E+10 0.306481E+10 0.174777E+10 0.131705E+10 0.00 0.00
February 0.366228E+10 0.337842E+10 0.356362E+10 0.205860E+10 0.150502E+10 0.00 0.00
March 0.479259E+10 0.301302E+10 0.440661E+10 0.234573E+10 0.206088E+10 0.00 0.00
April 0.636628E+10 0.207068E+10 0.544273E+10 0.289665E+10 0.254608E+10 0.00 0.00
May 0.663881E+10 0.159159E+10 0.533252E+10 0.274769E+10 0.258483E+10 0.00 0.00
June 0.776060E+10 0.107527E+10 0.553204E+10 0.308682E+10 0.244522E+10 0.00 0.00
July 0.756675E+10 0.744348E+09 0.515606E+10 0.252331E+10 0.263275E+10 0.00 0.00
August 0.747087E+10 0.857062E+09 0.526857E+10 0.243693E+10 0.283164E+10 0.00 0.00
September 0.616427E+10 0.135264E+10 0.460525E+10 0.242540E+10 0.217985E+10 0.00 0.00
October 0.520334E+10 0.238957E+10 0.435362E+10 0.270593E+10 0.164769E+10 0.00 0.00
November 0.335376E+10 0.317012E+10 0.330733E+10 0.194578E+10 0.136155E+10 0.00 0.00
December 0.277720E+10 0.418496E+10 0.295551E+10 0.185342E+10 0.110209E+10 0.00 0.00
               
Annual Sum or Average 0.646958E+11 0.278874E+11 0.529887E+11 0.287740E+11 0.242147E+11 0.00 0.00
Minimum of Months 0.277720E+10 0.744348E+09 0.295551E+10 0.174777E+10 0.110209E+10 0.00 0.00
Maximum of Months 0.776060E+10 0.418496E+10 0.553204E+10 0.308682E+10 0.283164E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.481433E+09 0.551380E+10 0.160938E+10 0.00 0.160938E+10 0.00 0.00
February 0.812692E+09 0.453437E+10 0.181679E+10 0.00 0.181679E+10 0.00 0.00
March 0.176277E+10 0.400620E+10 0.253719E+10 0.00 0.253719E+10 0.00 0.00
April 0.261937E+10 0.265793E+10 0.311507E+10 26669874.63 0.308840E+10 0.00 0.00
May 0.368621E+10 0.205379E+10 0.349897E+10 0.225590E+09 0.327338E+10 0.00 0.00
June 0.545954E+10 0.135906E+10 0.384753E+10 0.629640E+09 0.321789E+10 0.00 0.00
July 0.558964E+10 0.971991E+09 0.364914E+10 0.303718E+09 0.334542E+10 0.00 0.00
August 0.473907E+10 0.108716E+10 0.338519E+10 75787062.69 0.330940E+10 0.00 0.00
September 0.314256E+10 0.180880E+10 0.261977E+10 672368.48 0.261910E+10 0.00 0.00
October 0.157348E+10 0.313390E+10 0.202004E+10 0.00 0.202004E+10 0.00 0.00
November 0.637395E+09 0.418495E+10 0.166015E+10 0.00 0.166015E+10 0.00 0.00
December 0.180455E+09 0.574667E+10 0.136982E+10 0.00 0.136982E+10 0.00 0.00
               
Annual Sum or Average 0.306846E+11 0.370586E+11 0.311290E+11 0.126208E+10 0.298670E+11 0.00 0.00
Minimum of Months 0.180455E+09 0.971991E+09 0.136982E+10 0.00 0.136982E+10 0.00 0.00
Maximum of Months 0.558964E+10 0.574667E+10 0.384753E+10 0.629640E+09 0.334542E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.269316E+10 0.343012E+10 0.297133E+10 0.166125E+10 0.131007E+10 0.00 0.00
February 0.319269E+10 0.285746E+10 0.326074E+10 0.175789E+10 0.150285E+10 0.00 0.00
March 0.517907E+10 0.257785E+10 0.476227E+10 0.270727E+10 0.205501E+10 0.00 0.00
April 0.746535E+10 0.179760E+10 0.629636E+10 0.358700E+10 0.270935E+10 0.00 0.00
May 0.777635E+10 0.143633E+10 0.620833E+10 0.353808E+10 0.267025E+10 0.00 0.00
June 0.895031E+10 0.913955E+09 0.647715E+10 0.399023E+10 0.248692E+10 0.00 0.00
July 0.892514E+10 0.667340E+09 0.619320E+10 0.354153E+10 0.265168E+10 0.00 0.00
August 0.856408E+10 0.746750E+09 0.612859E+10 0.337881E+10 0.274978E+10 0.00 0.00
September 0.652044E+10 0.119592E+10 0.493647E+10 0.276200E+10 0.217447E+10 0.00 0.00
October 0.518348E+10 0.203397E+10 0.443632E+10 0.281467E+10 0.162165E+10 0.00 0.00
November 0.337314E+10 0.268974E+10 0.335536E+10 0.197259E+10 0.138277E+10 0.00 0.00
December 0.254356E+10 0.358229E+10 0.280942E+10 0.170979E+10 0.109963E+10 0.00 0.00
               
Annual Sum or Average 0.703668E+11 0.239293E+11 0.578356E+11 0.334211E+11 0.244144E+11 0.00 0.00
Minimum of Months 0.254356E+10 0.667340E+09 0.280942E+10 0.166125E+10 0.109963E+10 0.00 0.00
Maximum of Months 0.895031E+10 0.358229E+10 0.647715E+10 0.399023E+10 0.274978E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.137879E+11 0.540733E+10 0.118982E+11 0.925840E+10 0.263975E+10 0.00 0.00
February 0.124328E+11 0.455189E+10 0.105171E+11 0.768240E+10 0.283472E+10 0.00 0.00
March 0.103659E+11 0.415484E+10 0.858041E+10 0.518738E+10 0.339302E+10 0.00 0.00
April 0.810386E+10 0.291618E+10 0.647576E+10 0.265818E+10 0.381758E+10 0.00 0.00
May 0.562381E+10 0.222902E+10 0.446276E+10 0.981725E+09 0.348103E+10 0.00 0.00
June 0.544709E+10 0.144188E+10 0.365334E+10 0.450235E+09 0.320310E+10 0.00 0.00
July 0.671568E+10 0.102787E+10 0.417736E+10 0.667085E+09 0.351027E+10 0.00 0.00
August 0.882497E+10 0.119938E+10 0.574418E+10 0.186715E+10 0.387703E+10 0.00 0.00
September 0.109383E+11 0.196491E+10 0.768674E+10 0.428635E+10 0.340039E+10 0.00 0.00
October 0.139687E+11 0.328380E+10 0.108669E+11 0.800344E+10 0.286349E+10 0.00 0.00
November 0.139817E+11 0.427865E+10 0.117133E+11 0.898989E+10 0.272337E+10 0.00 0.00
December 0.150496E+11 0.551315E+10 0.129091E+11 0.106487E+11 0.226045E+10 0.00 0.00
               
Annual Sum or Average 0.125240E+12 0.379689E+11 0.986851E+11 0.606809E+11 0.380042E+11 0.00 0.00
Minimum of Months 0.544709E+10 0.102787E+10 0.365334E+10 0.450235E+09 0.226045E+10 0.00 0.00
Maximum of Months 0.150496E+11 0.551315E+10 0.129091E+11 0.106487E+11 0.387703E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.299484E+10 0.378493E+10 0.306481E+10 0.174777E+10 0.131705E+10 0.00 0.00
February 0.370870E+10 0.316769E+10 0.356362E+10 0.205860E+10 0.150502E+10 0.00 0.00
March 0.484064E+10 0.284676E+10 0.440661E+10 0.234573E+10 0.206088E+10 0.00 0.00
April 0.638073E+10 0.199179E+10 0.544273E+10 0.289665E+10 0.254608E+10 0.00 0.00
May 0.663255E+10 0.155461E+10 0.533252E+10 0.274769E+10 0.258483E+10 0.00 0.00
June 0.773310E+10 0.107064E+10 0.553204E+10 0.308682E+10 0.244522E+10 0.00 0.00
July 0.752703E+10 0.755302E+09 0.515606E+10 0.252331E+10 0.263275E+10 0.00 0.00
August 0.743612E+10 0.865224E+09 0.526857E+10 0.243693E+10 0.283164E+10 0.00 0.00
September 0.615157E+10 0.133464E+10 0.460525E+10 0.242540E+10 0.217985E+10 0.00 0.00
October 0.522433E+10 0.227204E+10 0.435362E+10 0.270593E+10 0.164769E+10 0.00 0.00
November 0.341042E+10 0.293097E+10 0.330733E+10 0.194578E+10 0.136155E+10 0.00 0.00
December 0.281501E+10 0.389556E+10 0.295551E+10 0.185342E+10 0.110209E+10 0.00 0.00
               
Annual Sum or Average 0.648550E+11 0.264702E+11 0.529887E+11 0.287740E+11 0.242147E+11 0.00 0.00
Minimum of Months 0.281501E+10 0.755302E+09 0.295551E+10 0.174777E+10 0.110209E+10 0.00 0.00
Maximum of Months 0.773310E+10 0.389556E+10 0.553204E+10 0.308682E+10 0.283164E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 2.60 -1.3 -7.5 3.29 -12.5 38.91 220.14 0.00
February 4.28 0.13 -5.8 3.80 -10.7 48.21 247.44 0.00
March 8.76 2.64 -5.5 4.72 -6.0 66.36 249.43 0.00
April 13.90 4.70 -6.4 4.61 -1.8 81.54 308.98 0.00
May 17.82 8.42 -1.1 4.68 3.61 77.67 310.50 0.00
June 23.21 12.42 4.15 4.28 9.16 70.88 348.57 0.00
July 25.63 16.13 10.74 4.00 14.07 80.74 308.61 0.00
August 24.08 15.39 10.38 3.96 13.00 86.20 290.42 0.00
September 20.49 12.87 7.70 3.48 8.22 67.00 274.65 0.00
October 13.71 6.72 -0.1 3.54 -0.8 42.11 283.53 0.00
November 6.96 1.72 -4.9 3.43 -7.6 39.44 239.51 0.01
December 2.07 -2.2 -8.9 2.95 -13.5 27.44 240.96 0.00
                 
Annual Sum or Average 13.68 6.50 -0.6 3.90 -0.3 60.60 276.96 0.00
Minimum of Months 2.07 -2.2 -8.9 2.95 -13.5 27.44 220.14 0.00
Maximum of Months 25.63 16.13 10.74 4.72 14.07 86.20 348.57 0.01



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.10 01-JAN-14:00 5.83 -6.7 5.20 -2.3 27.00 880.00
February 22.20 14-FEB-15:00 7.86 -10.0 4.60 4.72 61.50 778.50
March 22.80 08-MAR-13:00 9.68 -2.8 3.60 4.92 122.50 851.50
April 26.10 13-APR-16:00 10.32 -4.4 5.20 7.55 95.00 507.00
May 30.00 19-MAY-15:20 12.71 -1.5 8.93 13.35 108.33 887.00
June 38.90 28-JUN-15:00 14.16 -8.9 3.10 20.75 70.00 888.00
July 38.30 22-JUL-14:00 16.71 3.30 5.20 24.16 99.00 907.50
August 35.00 01-AUG-14:00 16.30 4.40 2.60 19.52 113.00 840.50
September 32.80 03-SEP-13:00 16.76 7.80 3.60 21.78 263.50 532.50
October 28.90 01-OCT-15:00 13.26 1.70 4.10 15.94 85.00 435.00
November 19.40 09-NOV-13:00 9.81 1.70 10.80 8.35 157.50 0.00
December 13.30 24-DEC-14:00 4.02 -8.3 8.20 -2.5 40.50 792.50
                 
Annual Sum or Average                
Minimum of Months 13.30   4.02 -10.0 2.60 -2.5 27.00 0.00
Maximum of Months 38.90   16.76 7.80 10.80 24.16 263.50 907.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -8.3 20-JAN-01:00 -8.3 -8.3 2.10 -25.6 0.00 0.00
February -6.7 04-FEB-06:10 -8.2 -11.7 5.10 -25.0 0.00 0.00
March -3.9 05-MAR-06:00 -5.7 -9.4 1.50 -21.6 17.00 434.50
April 1.70 06-APR-05:00 -2.4 -8.3 2.60 -12.9 28.00 215.00
May 4.40 07-MAY-04:00 -1.0 -8.3 1.50 -13.7 0.00 0.00
June 7.80 09-JUN-04:40 5.54 3.30 4.83 -7.8 0.00 0.00
July 16.10 08-JUL-02:00 14.67 13.90 0.00 4.72 0.00 0.00
August 12.80 31-AUG-05:00 10.77 9.40 3.10 -1.7 24.50 228.50
September 10.60 09-SEP-05:00 9.95 9.40 2.10 -2.5 15.50 177.00
October -2.8 26-OCT-04:10 -4.1 -6.1 2.42 -17.7 0.00 0.00
November -4.4 27-NOV-05:00 -6.9 -11.7 2.60 -22.7 0.00 0.00
December -9.4 15-DEC-04:00 -12.1 -21.7 0.00 -29.7 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -9.4   -12.1 -21.7 0.00 -29.7 0.00 0.00
Maximum of Months 16.10   14.67 13.90 5.10 4.72 28.00 434.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 6.84 05-JAN-13:00 16.10 -2.8 3.10 -0.1 62.00 873.00
February 7.86 14-FEB-15:00 22.20 -10.0 4.60 4.72 61.50 778.50
March 9.68 08-MAR-13:00 22.80 -2.8 3.60 4.92 122.50 851.50
April 10.95 14-APR-15:00 24.40 -0.6 8.20 17.21 237.00 154.00
May 15.08 22-MAY-12:30 28.60 6.40 5.15 16.76 167.00 0.00
June 18.19 24-JUN-13:00 31.70 11.70 2.60 19.17 130.00 891.50
July 19.21 31-JUL-14:00 32.80 12.80 6.20 22.98 264.50 624.50
August 19.18 26-AUG-12:00 27.80 15.60 3.60 17.03 289.00 426.50
September 18.19 05-SEP-12:00 23.90 15.60 3.10 13.35 196.50 796.00
October 16.16 11-OCT-10:00 23.90 12.20 13.40 13.73 219.50 450.00
November 9.81 09-NOV-13:00 19.40 1.70 10.80 8.35 157.50 0.00
December 4.92 01-DEC-15:00 12.80 -3.9 2.10 1.58 50.00 276.00
                 
Annual Sum or Average                
Minimum of Months 4.92   12.80 -10.0 2.10 -0.1 50.00 0.00
Maximum of Months 19.21   32.80 15.60 13.40 22.98 289.00 891.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -0.6 28-JAN-17:00 6.10 3.01 4.60 -5.0 0.00 0.00
February 2.20 17-FEB-10:00 7.20 4.72 3.10 -4.1 212.50 561.00
March 5.60 28-MAR-17:10 8.80 7.05 4.60 3.37 35.00 0.67
April 7.20 15-APR-06:00 13.30 9.79 7.20 6.35 116.00 422.00
May 13.90 24-MAY-14:00 16.70 14.90 4.60 11.07 128.00 0.00
June 13.30 30-JUN-13:00 26.70 17.72 6.70 20.75 170.00 126.50
July 17.80 01-JUL-13:00 22.20 19.05 3.60 13.91 361.00 125.00
August 17.20 26-AUG-09:00 21.70 18.59 2.60 11.65 243.50 681.50
September 15.60 05-SEP-11:00 22.20 17.61 3.10 12.79 231.00 705.00
October 13.90 02-OCT-16:00 20.60 16.04 6.20 13.54 38.50 65.00
November 6.10 09-NOV-21:00 8.90 7.38 11.80 3.69 0.00 0.00
December 1.10 25-DEC-08:00 2.20 1.65 2.10 -4.1 54.00 0.00
                 
Annual Sum or Average                
Minimum of Months -0.6   2.20 1.65 2.10 -5.0 0.00 0.00
Maximum of Months 17.80   26.70 19.05 11.80 20.75 361.00 705.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 11.28 25.87 0.00
February 18.00 13.00 16.00 10.91 34.17 0.00
March 18.00 13.00 16.00 12.10 41.92 0.00
April 18.00 13.00 16.00 14.59 56.24 0.00
May 18.00 13.00 16.00 17.73 59.47 0.00
June 18.00 13.00 16.00 20.66 62.98 0.00
July 18.00 13.00 16.00 22.59 61.22 0.00
August 18.00 13.00 16.00 23.01 57.83 0.00
September 18.00 13.00 16.00 21.78 48.11 0.00
October 18.00 13.00 16.00 19.25 37.89 0.00
November 18.00 13.00 16.00 16.11 28.37 0.00
December 18.00 13.00 16.00 13.20 24.17 0.00
             
Annual Sum or Average 18.00 13.00 16.00 16.97 44.90 0.00
Minimum of Months 18.00 13.00 16.00 10.91 24.17 0.00
Maximum of Months 18.00 13.00 16.00 23.01 62.98 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.390131E+11 -0.379883E+11 0.00 0.00 744.00 0.00 -0.102482E+10 58.98 0.00 0.00
February 0.357125E+11 -0.347868E+11 0.00 0.00 672.00 0.00 -925712008.3 58.99 0.00 0.00
March 0.409301E+11 -0.399036E+11 0.00 0.00 744.00 0.00 -0.102649E+10 58.99 0.00 0.00
April 0.352565E+11 -0.342675E+11 0.00 0.00 720.00 0.00 -988928766.7 58.97 0.00 0.00
May 0.350661E+11 -0.340431E+11 0.00 0.00 744.00 0.00 -0.102306E+10 58.98 0.00 0.00
June 0.323104E+11 -0.313199E+11 0.00 0.00 720.00 0.00 -990477644.0 58.98 0.00 0.00
July 0.292904E+11 -0.282727E+11 0.00 0.00 744.00 0.00 -0.101774E+10 58.97 0.00 0.00
August 0.316439E+11 -0.306219E+11 0.00 0.00 744.00 0.00 -0.102196E+10 58.97 0.00 0.00
September 0.297251E+11 -0.287384E+11 0.00 0.00 720.00 0.00 -986666448.3 58.97 0.00 0.00
October 0.326754E+11 -0.316568E+11 0.00 0.00 744.00 0.00 -0.101862E+10 58.98 0.00 0.00
November 0.344796E+11 -0.334933E+11 0.00 0.00 720.00 0.00 -986357054.4 58.97 0.00 0.00
December 0.365992E+11 -0.355788E+11 0.00 0.00 744.00 0.00 -0.102034E+10 58.97 0.00 0.00
                     
Annual Sum or Average 0.412702E+12 -0.400671E+12 0.00 0.00 8760.00 0.00 -0.120312E+11 58.98 0.00 0.00
Minimum of Months 0.292904E+11 -0.399036E+11 0.00 0.00 672.00 0.00 -0.102649E+10 58.97 0.00 0.00
Maximum of Months 0.409301E+11 -0.282727E+11 0.00 0.00 744.00 0.00 -925712008.3 58.99 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 301.50 0.50 0.48 01-JAN-07:49 8985.82 35.41 269.50 278.33 2171.50 27.32 198.17 270.67
February 282.00 0.50 0.48 01-FEB-07:49 11231.19 37.05 271.33 270.17 1467.45 22.34 139.67 251.33
March 351.33 0.50 0.48 01-MAR-07:19 1834.68 17.25 10.67 321.17 1051.67 19.94 119.50 285.00
April 381.83 0.51 0.48 01-APR-06:00 1466.51 17.26 0.00 342.83 882.96 20.23 120.50 309.83
May 378.00 0.51 0.48 01-MAY-06:40 1125.58 16.51 0.00 358.83 695.22 19.54 56.67 314.17
June 412.83 0.51 0.48 01-JUN-06:19 897.35 15.49 0.00 348.33 560.80 18.61 44.83 290.17
July 395.33 0.51 0.48 01-JUL-06:00 1089.52 16.32 0.00 359.33 665.36 19.40 72.33 310.83
August 408.83 0.51 0.48 01-AUG-06:40 1364.71 17.00 0.00 360.67 812.53 20.00 138.50 323.17
September 359.33 0.51 0.48 01-SEP-06:49 1811.84 17.67 16.50 317.83 981.21 19.92 110.17 286.33
October 329.00 0.51 0.48 01-OCT-06:00 5298.94 27.15 181.17 310.67 1319.51 20.17 87.00 294.33
November 284.17 0.49 0.48 01-NOV-06:00 10214.51 36.78 266.00 276.17 2122.10 26.92 165.50 267.50
December 265.67 0.50 0.48 01-DEC-07:49 10069.08 35.63 227.83 257.33 3247.09 30.79 173.83 255.33
                         
Annual Sum or Average 4149.83 0.51     4057.42 22.89 1243.00 3801.67 1233.08 21.64 1426.67 3458.67
Minimum of Months 265.67 0.49 0.48   897.35 15.49 0.00 257.33 560.80 18.61 44.83 251.33
Maximum of Months 412.83 0.51 0.48   11231.19 37.05 271.33 360.67 3247.09 30.79 198.17 323.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 301.50 0.52 0.48 01-JAN-07:49 2112.05 20.32 85.83 241.33 1230.70 23.37 108.50 203.33
February 282.00 0.51 0.48 01-FEB-07:40 2663.75 20.32 74.17 247.83 1568.35 23.45 107.50 211.00
March 351.33 0.51 0.48 01-MAR-06:00 2753.19 20.05 85.17 308.00 1390.53 21.67 103.00 269.33
April 381.83 0.51 0.48 01-APR-05:00 4065.75 21.96 114.83 345.33 1493.73 22.03 95.67 321.00
May 378.00 0.51 0.48 01-MAY-05:00 3113.12 19.54 80.83 363.00 1766.49 22.49 79.83 326.50
June 412.83 0.50 0.48 01-JUN-05:30 2945.49 18.71 83.67 368.67 1737.33 22.14 98.83 329.83
July 395.33 0.50 0.48 01-JUL-06:49 2999.00 19.61 84.67 369.17 1600.20 22.42 96.00 334.33
August 408.83 0.51 0.48 01-AUG-05:49 3738.42 21.44 115.83 370.00 1417.40 21.89 92.83 340.17
September 359.33 0.51 0.48 01-SEP-06:19 3015.48 19.65 81.83 316.50 1771.16 23.20 112.50 287.67
October 329.00 0.52 0.48 01-OCT-06:40 2795.36 19.82 82.67 280.83 1585.46 23.04 93.67 251.83
November 284.17 0.52 0.48 01-NOV-06:49 2292.93 20.83 77.00 245.67 1205.26 22.43 82.83 214.17
December 265.67 0.54 0.48 01-DEC-07:49 2452.65 20.54 80.33 223.17 1511.15 23.30 84.17 179.33
                         
Annual Sum or Average 4149.83 0.51     2968.99 20.21 1046.83 3679.50 1535.31 22.56 1155.33 3268.50
Minimum of Months 265.67 0.50 0.48   2112.05 18.71 74.17 223.17 1205.26 21.67 79.83 179.33
Maximum of Months 412.83 0.54 0.48   4065.75 21.96 115.83 370.00 1771.16 23.45 112.50 340.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 301.50 0.55 0.48 01-JAN-10:20 499.04 13.18 0.00 205.83 323.19 16.73 0.00 119.00
February 282.00 0.53 0.48 01-FEB-08:39 584.26 14.13 0.00 227.83 390.35 17.59 0.00 159.67
March 351.33 0.52 0.48 01-MAR-07:40 703.73 15.05 0.00 296.50 442.59 18.22 0.00 228.50
April 381.83 0.50 0.48 01-APR-06:30 881.33 16.68 0.00 355.33 564.97 19.70 7.00 324.00
May 378.00 0.50 0.48 01-MAY-06:30 1039.53 16.96 0.00 383.33 598.72 19.93 54.17 337.67
June 412.83 0.49 0.48 01-JUN-05:49 1079.03 18.33 49.33 393.33 566.53 19.51 47.67 359.50
July 395.33 0.49 0.48 01-JUL-06:00 1056.35 18.40 34.83 386.83 606.33 19.90 59.83 358.50
August 408.83 0.50 0.48 01-AUG-05:00 934.46 16.82 0.00 375.67 598.15 19.83 48.83 352.00
September 359.33 0.51 0.48 01-SEP-06:49 740.59 15.61 0.00 311.17 477.91 18.77 3.83 255.50
October 329.00 0.54 0.48 01-OCT-07:00 531.36 13.58 0.00 254.17 368.75 17.02 0.00 183.33
November 284.17 0.54 0.48 01-NOV-07:49 523.40 13.84 0.00 224.17 354.08 17.42 0.00 149.17
December 265.67 0.56 0.48 01-DEC-08:39 431.78 12.27 0.00 189.83 304.63 16.02 0.00 86.17
                         
Annual Sum or Average 4149.83 0.52     781.09 15.67 84.17 3604.00 481.41 18.56 221.33 2913.00
Minimum of Months 265.67 0.49 0.48   431.78 12.27 0.00 189.83 304.63 16.02 0.00 86.17
Maximum of Months 412.83 0.56 0.48   1079.03 18.40 49.33 393.33 606.33 19.93 59.83 359.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 301.50 0.52 0.48 01-JAN-10:09 1614.22 18.44 57.17 245.83 927.85 21.80 93.17 204.83
February 282.00 0.51 0.48 01-FEB-08:50 2678.64 20.75 75.00 246.50 1522.08 23.77 105.50 209.00
March 351.33 0.51 0.48 01-MAR-07:00 2759.27 19.45 80.67 308.33 1073.40 21.25 106.33 268.50
April 381.83 0.50 0.48 01-APR-07:30 3636.38 21.32 110.17 345.83 1368.67 21.82 89.00 319.17
May 378.00 0.50 0.48 01-MAY-06:00 2557.22 17.15 46.50 374.17 1467.61 19.00 34.50 342.00
June 412.83 0.50 0.48 01-JUN-06:40 2661.07 13.74 0.00 363.50 1612.50 18.05 30.83 327.83
July 395.33 0.50 0.48 01-JUL-07:19 2602.57 14.81 3.67 369.67 1462.10 18.79 47.50 335.83
August 408.83 0.51 0.48 01-AUG-07:10 2597.03 17.91 59.83 360.00 1373.24 19.51 89.50 332.17
September 359.33 0.51 0.48 01-SEP-07:19 2898.36 19.55 82.00 317.50 1125.94 21.50 104.83 288.00
October 329.00 0.52 0.48 01-OCT-07:00 2667.92 19.74 82.00 282.50 1406.09 21.53 87.67 246.83
November 284.17 0.51 0.48 01-NOV-07:49 2518.10 20.83 78.67 254.17 1603.20 24.47 101.83 217.00
December 265.67 0.53 0.48 01-DEC-08:39 2323.66 20.56 80.17 229.50 1492.96 24.47 88.50 188.17
                         
Annual Sum or Average 4149.83 0.51     2652.62 18.46 755.83 3697.50 1370.65 21.05 979.17 3279.33
Minimum of Months 265.67 0.50 0.48   1614.22 13.74 0.00 229.50 927.85 18.05 30.83 188.17
Maximum of Months 412.83 0.53 0.48   3636.38 21.32 110.17 374.17 1612.50 24.47 106.33 342.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 301.50 0.50 0.48 01-JAN-07:49 8977.98 34.50 269.17 277.67 2236.05 23.58 126.83 271.33
February 282.00 0.49 0.48 01-FEB-07:40 11228.38 36.67 270.50 269.67 1668.69 20.43 78.83 257.50
March 351.33 0.50 0.48 01-MAR-07:10 1822.05 11.00 10.67 320.33 1099.42 15.62 3.50 286.83
April 381.83 0.51 0.48 01-APR-06:00 1452.18 11.76 0.00 341.50 916.65 16.64 0.00 311.83
May 378.00 0.51 0.48 01-MAY-06:40 1114.10 11.15 0.00 356.50 720.27 16.03 0.00 317.17
June 412.83 0.52 0.48 01-JUN-06:19 888.96 9.92 0.00 345.83 581.38 14.96 0.00 295.00
July 395.33 0.51 0.48 01-JUL-06:00 1076.70 10.81 0.00 357.50 688.67 15.76 0.00 314.33
August 408.83 0.51 0.48 01-AUG-06:40 1348.65 11.49 0.00 358.83 841.52 16.34 0.00 325.67
September 359.33 0.51 0.48 01-SEP-06:49 1804.93 11.85 16.50 317.00 1022.86 15.81 0.00 288.33
October 329.00 0.50 0.48 01-OCT-06:00 5339.90 23.75 181.00 314.83 1380.17 15.56 14.67 295.67
November 284.17 0.49 0.48 01-NOV-06:00 10208.80 36.16 265.83 275.50 2189.36 22.93 105.67 268.00
December 265.67 0.50 0.48 01-DEC-07:49 10029.43 33.90 222.67 255.17 3324.66 27.49 146.67 255.33
                         
Annual Sum or Average 4149.83 0.51     4049.30 18.73 1236.33 3790.33 1285.98 17.95 476.17 3487.00
Minimum of Months 265.67 0.49 0.48   888.96 9.92 0.00 255.17 581.38 14.96 0.00 255.33
Maximum of Months 412.83 0.52 0.48   11228.38 36.67 270.50 358.83 3324.66 27.49 146.67 325.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 301.50 0.52 0.48 01-JAN-07:49 2116.69 17.59 85.67 241.50 1125.71 19.66 55.50 205.50
February 282.00 0.51 0.48 01-FEB-07:40 2669.23 17.50 74.17 247.83 1598.83 21.56 70.50 215.33
March 351.33 0.51 0.48 01-MAR-06:00 2768.32 16.86 85.17 308.00 1428.74 19.11 55.67 273.17
April 381.83 0.51 0.48 01-APR-05:00 3708.33 16.58 84.83 344.17 1538.89 19.36 54.83 323.17
May 378.00 0.51 0.48 01-MAY-05:00 3104.93 16.19 80.83 362.67 1814.63 19.93 66.33 329.67
June 412.83 0.50 0.48 01-JUN-05:30 2955.35 15.12 83.67 368.33 1782.37 19.53 82.50 333.33
July 395.33 0.50 0.48 01-JUL-06:40 3000.95 16.18 84.67 367.83 1646.66 19.81 70.33 337.17
August 408.83 0.50 0.48 01-AUG-05:49 3734.74 18.49 115.83 369.50 1459.95 19.25 59.83 342.00
September 359.33 0.51 0.48 01-SEP-06:19 3028.44 16.39 81.67 316.17 1809.01 20.92 80.67 290.33
October 329.00 0.52 0.48 01-OCT-06:40 2730.54 16.42 78.67 281.00 1623.22 20.91 74.33 256.83
November 284.17 0.52 0.48 01-NOV-06:49 1970.91 15.68 54.50 246.00 1236.97 20.40 53.33 217.00
December 265.67 0.54 0.48 01-DEC-07:49 2462.58 18.15 80.33 223.17 1498.87 21.20 63.67 185.00
                         
Annual Sum or Average 4149.83 0.51     2912.72 16.72 990.00 3676.17 1562.29 20.06 787.50 3308.50
Minimum of Months 265.67 0.50 0.48   1970.91 15.12 54.50 223.17 1125.71 19.11 53.33 185.00
Maximum of Months 412.83 0.54 0.48   3734.74 18.49 115.83 369.50 1814.63 21.56 82.50 342.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 301.50 0.55 0.48 01-JAN-10:09 490.79 7.65 0.00 203.33 332.83 12.90 0.00 132.00
February 282.00 0.53 0.48 01-FEB-08:39 576.03 8.89 0.00 226.17 402.45 14.07 0.00 167.67
March 351.33 0.52 0.48 01-MAR-07:40 694.50 9.84 0.00 293.67 457.14 14.84 0.00 236.50
April 381.83 0.50 0.48 01-APR-06:30 870.46 11.94 0.00 355.33 582.78 16.88 0.00 326.17
May 378.00 0.50 0.48 01-MAY-06:30 1029.57 11.75 0.00 382.83 619.23 16.75 0.00 340.50
June 412.83 0.49 0.48 01-JUN-05:49 1072.90 13.32 48.50 392.17 587.95 15.95 0.00 361.67
July 395.33 0.49 0.48 01-JUL-06:00 1049.19 13.48 34.50 386.00 627.46 16.50 0.00 360.00
August 408.83 0.50 0.48 01-AUG-05:00 941.60 11.83 0.00 377.50 616.60 16.76 0.00 354.67
September 359.33 0.51 0.48 01-SEP-06:49 731.57 10.65 0.00 308.83 493.59 15.64 0.00 261.00
October 329.00 0.54 0.48 01-OCT-07:49 526.13 8.55 0.00 252.33 381.13 13.72 0.00 192.33
November 284.17 0.54 0.48 01-NOV-07:49 514.64 8.59 0.00 221.83 364.32 13.86 0.00 157.33
December 265.67 0.56 0.48 01-DEC-08:39 424.89 7.00 0.00 186.33 313.53 12.25 0.00 102.00
                         
Annual Sum or Average 4149.83 0.52     774.42 10.57 83.00 3586.33 497.25 15.21 0.00 2991.83
Minimum of Months 265.67 0.49 0.48   424.89 7.00 0.00 186.33 313.53 12.25 0.00 102.00
Maximum of Months 412.83 0.56 0.48   1072.90 13.48 48.50 392.17 627.46 16.88 0.00 361.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 301.50 0.52 0.48 01-JAN-09:00 1618.15 15.31 57.00 245.17 951.69 19.70 54.17 210.67
February 282.00 0.51 0.48 01-FEB-08:39 2686.50 17.84 74.83 246.17 1404.13 19.87 48.33 212.17
March 351.33 0.51 0.48 01-MAR-07:00 2770.45 16.26 79.83 307.50 1105.07 18.61 46.83 272.17
April 381.83 0.50 0.48 01-APR-07:19 3642.18 18.44 110.00 344.33 1408.44 19.15 51.00 321.33
May 378.00 0.50 0.48 01-MAY-06:00 2552.87 13.37 46.50 373.83 1508.07 15.68 0.00 344.83
June 412.83 0.50 0.48 01-JUN-06:30 2668.58 9.06 0.00 363.50 1653.94 14.63 0.00 333.00
July 395.33 0.50 0.48 01-JUL-07:19 2598.14 10.35 3.67 368.83 1501.86 15.50 0.00 338.50
August 408.83 0.51 0.48 01-AUG-07:10 2584.46 14.25 59.83 359.00 1409.42 16.33 5.17 334.67
September 359.33 0.51 0.48 01-SEP-07:19 2910.84 16.28 82.00 317.33 1163.53 18.89 51.50 292.00
October 329.00 0.52 0.48 01-OCT-07:49 2683.67 16.81 82.00 282.33 1443.10 19.16 56.33 252.33
November 284.17 0.51 0.48 01-NOV-07:49 2522.94 18.08 78.67 253.83 1632.78 22.76 77.33 220.83
December 265.67 0.53 0.48 01-DEC-08:39 2333.81 18.13 80.00 229.33 1520.77 22.98 79.33 194.33
                         
Annual Sum or Average 4149.83 0.51     2656.92 15.05 754.33 3691.17 1395.87 18.27 470.00 3326.83
Minimum of Months 265.67 0.50 0.48   1618.15 9.06 0.00 229.33 951.69 14.63 0.00 194.33
Maximum of Months 412.83 0.53 0.48   3642.18 18.44 110.00 373.83 1653.94 22.98 79.33 344.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 301.50 0.50 0.48 01-JAN-07:49 8977.10 34.48 269.17 277.67 2237.17 23.57 126.83 271.33
February 282.00 0.49 0.48 01-FEB-07:40 11228.14 36.66 270.50 269.67 1669.91 20.42 78.83 257.50
March 351.33 0.50 0.48 01-MAR-07:10 1822.70 10.96 10.67 320.17 1100.49 15.60 3.50 287.00
April 381.83 0.51 0.48 01-APR-06:49 1452.62 11.72 0.00 341.50 917.48 16.62 0.00 312.00
May 378.00 0.51 0.48 01-MAY-06:40 1114.29 11.11 0.00 356.50 720.87 16.01 0.00 317.17
June 412.83 0.52 0.48 01-JUN-06:19 889.13 9.88 0.00 345.67 581.84 14.94 0.00 295.33
July 395.33 0.51 0.48 01-JUL-06:00 1076.95 10.77 0.00 357.33 689.26 15.74 0.00 314.33
August 408.83 0.51 0.48 01-AUG-06:40 1349.05 11.45 0.00 358.83 842.30 16.32 0.00 325.83
September 359.33 0.51 0.48 01-SEP-06:49 1805.44 11.81 16.50 317.00 1023.78 15.79 0.00 288.33
October 329.00 0.50 0.48 01-OCT-06:00 5340.02 23.72 181.00 314.83 1381.06 15.54 14.67 295.67
November 284.17 0.49 0.48 01-NOV-06:00 10207.93 36.14 265.83 275.50 2190.51 22.92 105.67 268.00
December 265.67 0.50 0.48 01-DEC-07:49 10028.15 33.88 222.67 255.17 3325.62 27.48 146.67 255.33
                         
Annual Sum or Average 4149.83 0.51     4049.33 18.70 1236.33 3789.83 1286.83 17.93 476.17 3487.83
Minimum of Months 265.67 0.49 0.48   889.13 9.88 0.00 255.17 581.84 14.94 0.00 255.33
Maximum of Months 412.83 0.52 0.48   11228.14 36.66 270.50 358.83 3325.62 27.48 146.67 325.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 301.50 0.52 0.48 01-JAN-07:49 2116.38 17.55 85.67 241.33 1126.18 19.64 55.50 205.50
February 282.00 0.51 0.48 01-FEB-07:40 2668.79 17.46 74.17 247.83 1599.40 21.55 70.50 215.33
March 351.33 0.51 0.48 01-MAR-06:00 2768.04 16.82 85.17 308.00 1429.44 19.09 55.67 273.17
April 381.83 0.51 0.48 01-APR-05:00 3707.81 16.53 84.83 344.17 1539.70 19.34 54.83 323.17
May 378.00 0.51 0.48 01-MAY-05:00 3104.45 16.15 80.83 362.67 1815.36 19.91 66.33 329.67
June 412.83 0.50 0.48 01-JUN-05:30 2955.02 15.07 83.67 368.33 1782.96 19.51 82.50 333.17
July 395.33 0.50 0.48 01-JUL-06:40 2973.17 15.97 82.67 367.83 1647.34 19.80 70.33 337.33
August 408.83 0.50 0.48 01-AUG-05:49 3425.20 16.30 87.83 369.33 1460.71 19.23 59.83 342.17
September 359.33 0.51 0.48 01-SEP-06:19 3028.06 16.35 81.67 316.17 1809.70 20.91 80.67 290.33
October 329.00 0.52 0.48 01-OCT-06:40 2730.05 16.38 78.67 281.00 1623.66 20.89 74.33 257.00
November 284.17 0.52 0.48 01-NOV-06:49 1970.34 15.64 54.50 246.00 1237.43 20.38 53.33 217.00
December 265.67 0.54 0.48 01-DEC-07:49 2462.11 18.11 80.33 223.17 1499.22 21.18 63.67 185.00
                         
Annual Sum or Average 4149.83 0.51     2879.24 16.45 960.00 3675.83 1562.91 20.04 787.50 3308.83
Minimum of Months 265.67 0.50 0.48   1970.34 15.07 54.50 223.17 1126.18 19.09 53.33 185.00
Maximum of Months 412.83 0.54 0.48   3707.81 18.11 87.83 369.33 1815.36 21.55 82.50 342.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 301.50 0.55 0.48 01-JAN-10:09 490.65 7.61 0.00 203.00 333.06 12.88 0.00 132.00
February 282.00 0.53 0.48 01-FEB-08:39 575.81 8.85 0.00 226.17 402.69 14.05 0.00 167.83
March 351.33 0.52 0.48 01-MAR-07:40 694.46 9.80 0.00 293.67 457.50 14.82 0.00 236.67
April 381.83 0.50 0.48 01-APR-06:30 870.26 11.90 0.00 355.33 583.18 16.86 0.00 326.33
May 378.00 0.50 0.48 01-MAY-06:30 1029.43 11.71 0.00 382.83 619.68 16.74 0.00 340.67
June 412.83 0.49 0.48 01-JUN-05:49 1072.84 13.28 48.50 392.17 588.38 15.93 0.00 361.83
July 395.33 0.49 0.48 01-JUL-06:00 1049.11 13.44 34.50 386.00 627.92 16.48 0.00 360.17
August 408.83 0.50 0.48 01-AUG-05:00 941.45 11.78 0.00 377.50 617.06 16.74 0.00 354.67
September 359.33 0.51 0.48 01-SEP-06:49 731.43 10.60 0.00 308.67 493.94 15.62 0.00 261.00
October 329.00 0.54 0.48 01-OCT-07:49 525.89 8.50 0.00 252.17 381.32 13.70 0.00 192.50
November 284.17 0.54 0.48 01-NOV-07:49 514.37 8.54 0.00 221.83 364.52 13.84 0.00 157.83
December 265.67 0.56 0.48 01-DEC-08:39 424.60 6.96 0.00 186.33 313.66 12.23 0.00 102.17
                         
Annual Sum or Average 4149.83 0.52     774.27 10.53 83.00 3585.67 497.59 15.19 0.00 2993.67
Minimum of Months 265.67 0.49 0.48   424.60 6.96 0.00 186.33 313.66 12.23 0.00 102.17
Maximum of Months 412.83 0.56 0.48   1072.84 13.44 48.50 392.17 627.92 16.86 0.00 361.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 301.50 0.52 0.48 01-JAN-09:00 1617.80 15.26 57.00 245.17 952.17 19.68 54.17 210.67
February 282.00 0.51 0.48 01-FEB-08:39 2686.01 17.80 74.83 246.17 1404.69 19.85 48.33 212.33
March 351.33 0.51 0.48 01-MAR-07:00 2770.28 16.22 79.83 307.50 1105.77 18.59 46.83 272.33
April 381.83 0.50 0.48 01-APR-07:19 3641.92 18.40 110.00 344.33 1409.17 19.13 51.00 321.33
May 378.00 0.50 0.48 01-MAY-06:00 2552.60 13.32 46.50 373.83 1508.77 15.66 0.00 344.83
June 412.83 0.50 0.48 01-JUN-06:30 2668.37 9.01 0.00 363.50 1654.56 14.60 0.00 333.17
July 395.33 0.50 0.48 01-JUL-07:19 2597.97 10.30 3.67 368.83 1502.62 15.48 0.00 338.67
August 408.83 0.51 0.48 01-AUG-07:10 2584.27 14.21 59.83 359.00 1410.30 16.31 5.17 335.00
September 359.33 0.51 0.48 01-SEP-07:19 2910.54 16.23 82.00 317.33 1164.26 18.87 51.50 292.00
October 329.00 0.52 0.48 01-OCT-07:49 2683.15 16.77 82.00 282.33 1443.56 19.14 56.33 252.33
November 284.17 0.51 0.48 01-NOV-07:49 2522.44 18.04 78.67 253.17 1633.24 22.75 77.33 220.83
December 265.67 0.53 0.48 01-DEC-08:39 2333.37 18.09 80.00 229.33 1521.10 22.97 79.33 194.50
                         
Annual Sum or Average 4149.83 0.51     2656.61 15.00 754.33 3690.50 1396.50 18.25 470.00 3328.00
Minimum of Months 265.67 0.50 0.48   1617.80 9.01 0.00 229.33 952.17 14.60 0.00 194.50
Maximum of Months 412.83 0.53 0.48   3641.92 18.40 110.00 373.83 1654.56 22.97 79.33 344.83



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.590608E+10 25414.87 21-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.305017E+10 22771.98 04-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.557226E+09 13565.74 04-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 30264058.54 5718.87 08-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 1173737.94 1232.59 06-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.376384E+09 16192.22 26-OCT-06:55 0.00 0.00 0.00 0.00 0.00
November 0.672844E+09 15382.02 27-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.412407E+10 24684.80 15-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.147182E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.590608E+10 25414.87   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 37117583.10 4568.48 21-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 11367954.98 1304.72 06-FEB-06:05 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 3071538.37 475.10 15-DEC-06:07 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 51557076.45     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 37117583.10 4568.48   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 92945427.64 9805.45 21-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 26654118.68 2546.79 07-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 180432.87 418.52 04-MAR-06:08 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 2027301.80 1228.61 26-OCT-05:08 0.00 0.00 0.00 0.00 0.00
November 299036.21 221.51 28-NOV-06:50 0.00 0.00 0.00 0.00 0.00
December 62196017.37 3778.02 22-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.184302E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 92945427.64 9805.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 80048788.84 14172.63 17-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 26063125.49 12267.33 06-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 2418848.66 1118.32 26-OCT-05:08 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 28318319.07 7503.98 22-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.136849E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 80048788.84 14172.63   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 280308.51 108.86 19-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 280308.51     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 280308.51 108.86   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.919317E+11 275900.38 21-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.547029E+11 247978.13 04-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.134131E+11 155979.01 04-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.199727E+10 97812.57 08-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.152909E+09 28480.30 06-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.866309E+10 179782.32 26-OCT-07:00 0.00 0.00 0.00 0.00 0.00
November 0.211637E+11 210179.31 27-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.911367E+11 273254.39 15-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.283161E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.919317E+11 275900.38   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.184247E+11 121300.20 18-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.101600E+11 121006.58 04-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.174968E+10 120254.86 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 33846879.77 14319.65 08-APR-05:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.735862E+09 122050.03 27-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.385453E+10 120847.13 27-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.205106E+11 121486.87 09-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.554692E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.205106E+11 122050.03   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.111921E+11 143033.84 21-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.499159E+10 143172.62 04-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.784166E+09 140412.22 04-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 15376279.53 9799.85 08-APR-05:08 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.604457E+09 116797.55 26-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.181329E+10 142097.74 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.107988E+11 143168.28 15-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.301998E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.111921E+11 143172.62   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.471462E+10 151655.03 17-JAN-05:02 0.00 0.00 0.00 0.00 0.00
February 0.223815E+10 150995.17 02-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.205465E+09 150192.22 04-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.223355E+09 117771.53 26-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.154775E+09 150188.02 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.424415E+10 151369.60 09-DEC-05:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.117805E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.471462E+10 151655.03   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.870827E+10 141681.88 21-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.448455E+10 141825.70 04-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.730299E+09 98608.19 04-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.418536E+09 77216.30 26-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.125795E+10 140757.96 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.849963E+10 141829.44 15-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.240992E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.870827E+10 141829.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.118741E+11 32927.30 21-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.761615E+10 30406.48 04-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.255811E+10 20653.69 04-MAR-07:05 0.00 0.00 0.00 0.00 0.00
April 0.556232E+09 13981.46 08-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 71631368.07 6359.74 06-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.167955E+10 23119.62 26-OCT-06:55 0.00 0.00 0.00 0.00 0.00
November 0.383872E+10 26776.58 27-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.124881E+11 33743.39 15-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.406827E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.124881E+11 33743.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.428735E+10 73790.94 30-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.204483E+10 73729.08 27-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.168592E+09 72440.13 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 72312407.87 71727.36 26-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.884859E+09 73295.91 27-NOV-05:03 0.00 0.00 0.00 0.00 0.00
December 0.401115E+10 73602.85 26-DEC-05:14 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.114691E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.428735E+10 73790.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.566701E+10 14220.66 12-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.366118E+10 14198.02 02-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.126576E+10 14160.96 06-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.189311E+09 14092.93 24-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 22771543.88 8633.33 06-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.633144E+09 14102.85 26-OCT-04:03 0.00 0.00 0.00 0.00 0.00
November 0.232857E+10 14194.65 13-NOV-05:03 0.00 0.00 0.00 0.00 0.00
December 0.608792E+10 14222.51 09-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.198557E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.608792E+10 14222.51   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.295954E+10 16452.16 20-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.170730E+10 16405.05 04-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.560987E+09 16279.43 04-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 55526113.62 9897.20 08-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 8526694.82 2481.97 06-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.316526E+09 16230.91 26-OCT-04:01 0.00 0.00 0.00 0.00 0.00
November 0.979919E+09 16340.14 27-NOV-05:03 0.00 0.00 0.00 0.00 0.00
December 0.294886E+10 16351.95 26-DEC-05:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.953719E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.295954E+10 16452.16   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.225695E+10 17146.67 18-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.134475E+10 17144.86 02-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.574230E+09 17100.16 06-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.104753E+09 14781.59 08-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 29115564.49 5368.67 05-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.274210E+09 17058.32 26-OCT-04:03 0.00 0.00 0.00 0.00 0.00
November 0.574045E+09 17125.82 28-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.203065E+10 17174.38 09-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.718870E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.225695E+10 17174.38   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.266658E+10 17426.88 30-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.162855E+10 17392.35 04-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.619371E+09 17017.80 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 67261519.69 8225.56 08-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 19873861.66 3064.26 05-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 1394288.02 504.26 09-JUN-05:25 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.323120E+09 16983.49 26-OCT-04:01 0.00 0.00 0.00 0.00 0.00
November 0.901812E+09 17268.55 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.259823E+10 17424.57 22-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.882619E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.266658E+10 17426.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.874801E+09 0.874801E+09 21105.60 05-JAN-14:10 21105.60 0.00
February 0.00 0.00 0.288684E+10 0.288684E+10 64914.31 14-FEB-15:50 64914.31 0.00
March 0.00 0.00 0.920135E+10 0.920135E+10 71224.04 08-MAR-16:00 71224.04 0.00
April 0.00 0.00 0.335933E+11 0.335933E+11 100858.86 17-APR-15:20 100858.86 0.00
May 0.00 0.00 0.515670E+11 0.515670E+11 105239.26 30-MAY-14:30 105239.26 0.05
June 0.00 0.00 0.101735E+12 0.101732E+12 140542.28 29-JUN-05:03 130936.98 0.27
July 0.00 0.00 0.131826E+12 0.128217E+12 144602.24 01-JUL-05:02 63366.92 0.77
August 0.00 0.00 0.129946E+12 0.126408E+12 143294.69 14-AUG-05:02 70045.10 0.81
September 0.00 0.00 0.743874E+11 0.733643E+11 149830.61 05-SEP-13:10 90275.88 0.39
October 0.00 0.00 0.358027E+11 0.357819E+11 104163.96 10-OCT-16:00 104163.96 0.09
November 0.00 0.00 0.223797E+10 0.223797E+10 35243.54 02-NOV-15:00 35243.54 0.00
December 0.00 0.00 540032.06 540032.06 2843.22 24-DEC-15:23 2843.22 0.00
                 
Annual Sum or Average 0.00 0.00 0.574059E+12 0.565865E+12       0.20
Minimum of Months 0.00 0.00 540032.06 540032.06 2843.22   2843.22 0.00
Maximum of Months 0.00 0.00 0.131826E+12 0.128217E+12 149830.61   130936.98 0.81



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.783570E+10 0.783570E+10 174912.06 05-JAN-15:40 174912.06 0.00
February 0.00 0.00 0.228936E+11 0.228936E+11 511185.45 14-FEB-16:00 511185.45 0.00
March 0.00 0.00 0.680710E+11 0.680710E+11 527919.52 08-MAR-16:00 527919.52 0.00
April 0.00 0.00 0.246290E+12 0.246290E+12 841050.45 26-APR-15:20 841050.45 0.00
May 0.00 0.00 0.445055E+12 0.445055E+12 946872.31 19-MAY-15:20 946872.31 0.06
June 0.00 0.00 0.866327E+12 0.866290E+12 1410138.80 29-JUN-05:03 1265054.23 0.24
July 0.00 0.00 0.105124E+13 0.102797E+13 1332156.89 01-JUL-05:02 580074.20 0.62
August 0.00 0.00 0.996513E+12 0.974056E+12 1353616.86 14-AUG-05:02 659295.66 0.63
September 0.00 0.00 0.651386E+12 0.641929E+12 1279607.79 05-SEP-13:00 765628.35 0.37
October 0.00 0.00 0.295152E+12 0.294984E+12 903699.58 06-OCT-15:30 903699.58 0.08
November 0.00 0.00 0.160066E+11 0.160066E+11 278742.50 02-NOV-15:00 278742.50 0.00
December 0.00 0.00 11358595.73 11358595.73 40176.06 24-DEC-14:43 40176.06 0.00
                 
Annual Sum or Average 0.00 0.00 0.466678E+13 0.461139E+13       0.17
Minimum of Months 0.00 0.00 11358595.73 11358595.73 40176.06   40176.06 0.00
Maximum of Months 0.00 0.00 0.105124E+13 0.102797E+13 1410138.80   1265054.23 0.63



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.394535E+09 0.394535E+09 13174.34 05-JAN-14:20 13174.34 0.00
February 0.00 0.00 0.189525E+10 0.189525E+10 45922.81 14-FEB-15:50 45922.81 0.00
March 0.00 0.00 0.549794E+10 0.549794E+10 53550.47 08-MAR-16:00 53550.47 0.00
April 0.00 0.00 0.256558E+11 0.256558E+11 102498.97 26-APR-15:00 102498.97 0.00
May 0.00 0.00 0.490399E+11 0.490399E+11 117298.38 19-MAY-15:20 117298.38 0.05
June 0.00 0.00 0.995448E+11 0.995432E+11 148010.26 28-JUN-14:50 148010.26 0.24
July 0.00 0.00 0.122368E+12 0.119757E+12 147247.25 21-JUL-14:50 147247.25 0.63
August 0.00 0.00 0.113999E+12 0.111642E+12 157161.83 13-AUG-15:31 123408.60 0.64
September 0.00 0.00 0.705042E+11 0.697699E+11 140842.54 05-SEP-13:30 88516.10 0.35
October 0.00 0.00 0.291977E+11 0.291977E+11 103545.96 06-OCT-15:20 103545.96 0.08
November 0.00 0.00 0.103100E+10 0.103100E+10 25157.14 02-NOV-15:00 25157.14 0.00
December 0.00 0.00 342.12 342.12 0.39 16-DEC-14:30 0.39 0.00
                 
Annual Sum or Average 0.00 0.00 0.519128E+12 0.513424E+12       0.17
Minimum of Months 0.00 0.00 342.12 342.12 0.39   0.39 0.00
Maximum of Months 0.00 0.00 0.122368E+12 0.119757E+12 157161.83   148010.26 0.64



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 16995512.17 16995512.17 3114.21 02-JAN-15:00 3114.21 0.00
February 0.00 0.00 0.123474E+10 0.123474E+10 39417.81 13-FEB-16:00 39417.81 0.00
March 0.00 0.00 0.341121E+10 0.341121E+10 41000.58 08-MAR-14:00 41000.58 0.00
April 0.00 0.00 0.172376E+11 0.172376E+11 57569.73 17-APR-15:00 57569.73 0.00
May 0.00 0.00 0.303525E+11 0.303515E+11 89026.03 29-MAY-16:11 89026.03 0.03
June 0.00 0.00 0.560556E+11 0.560390E+11 80445.61 29-JUN-05:03 74222.74 0.20
July 0.00 0.00 0.686866E+11 0.672441E+11 121964.75 02-JUL-19:30 76498.41 0.50
August 0.00 0.00 0.680956E+11 0.668576E+11 99526.35 13-AUG-18:17 83839.79 0.54
September 0.00 0.00 0.461517E+11 0.452770E+11 99210.01 05-SEP-13:00 63847.11 0.30
October 0.00 0.00 0.215095E+11 0.215059E+11 90547.77 01-OCT-14:24 90547.77 0.08
November 0.00 0.00 0.607606E+09 0.607606E+09 23115.54 09-NOV-14:00 23115.54 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.313360E+12 0.309783E+12       0.14
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.686866E+11 0.672441E+11 121964.75   90547.77 0.54



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.456303E+10 0.456247E+10 2759.23 01-JAN-16:50 2752.50 0.00
February 0.00 0.00 0.914176E+10 0.913888E+10 4724.55 15-FEB-17:00 4724.55 0.00
March 0.00 0.00 0.156914E+11 0.156865E+11 7749.75 31-MAR-24:00 7749.75 0.00
April 0.00 0.00 0.203898E+11 0.203890E+11 8909.61 16-APR-18:22 8909.61 0.00
May 0.00 0.00 0.604297E+10 0.600275E+10 4139.19 31-MAY-24:00 4139.19 0.00
June 0.00 0.00 0.111029E+11 0.110071E+11 6014.27 30-JUN-24:00 5981.18 0.00
July 0.00 0.00 0.167198E+11 0.164950E+11 7884.50 31-JUL-23:53 7875.57 0.00
August 0.00 0.00 0.216872E+11 0.214456E+11 8615.95 07-AUG-18:30 8486.59 0.00
September 0.00 0.00 0.617214E+10 0.601907E+10 4169.71 30-SEP-24:00 4140.39 0.00
October 0.00 0.00 0.110074E+11 0.109490E+11 5935.47 31-OCT-24:00 5935.47 0.00
November 0.00 0.00 0.151238E+11 0.151126E+11 6767.95 05-NOV-16:40 6767.95 0.00
December 0.00 0.00 0.203470E+11 0.203468E+11 8572.49 31-DEC-16:35 8572.49 0.00
                 
Annual Sum or Average 0.00 0.00 0.157989E+12 0.157155E+12       0.00
Minimum of Months 0.00 0.00 0.456303E+10 0.456247E+10 2759.23   2752.50 0.00
Maximum of Months 0.00 0.00 0.216872E+11 0.214456E+11 8909.61   8909.61 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.261244E+11 0.261184E+11 23273.69 26-JAN-17:00 23273.69 0.00
February 0.00 0.00 0.735495E+11 0.735204E+11 44252.51 15-FEB-17:00 44252.51 0.00
March 0.00 0.00 0.139600E+12 0.139549E+12 71572.41 31-MAR-23:40 71572.41 0.00
April 0.00 0.00 0.190549E+12 0.190541E+12 83832.37 16-APR-17:42 83832.37 0.00
May 0.00 0.00 0.539837E+11 0.535888E+11 39202.24 31-MAY-24:00 39202.24 0.00
June 0.00 0.00 0.104467E+12 0.103517E+12 58068.54 30-JUN-24:00 57742.12 0.00
July 0.00 0.00 0.159193E+12 0.156954E+12 76039.90 31-JUL-23:53 75951.61 0.00
August 0.00 0.00 0.206914E+12 0.204503E+12 82348.09 11-AUG-18:10 80648.26 0.00
September 0.00 0.00 0.559572E+11 0.544590E+11 39411.62 30-SEP-24:00 39125.62 0.00
October 0.00 0.00 0.980070E+11 0.974304E+11 54210.36 31-OCT-24:00 54210.36 0.00
November 0.00 0.00 0.131243E+12 0.131132E+12 62203.90 02-NOV-16:40 61336.04 0.00
December 0.00 0.00 0.174064E+12 0.174063E+12 76426.03 29-DEC-16:40 76426.03 0.00
                 
Annual Sum or Average 0.00 0.00 0.141365E+13 0.140538E+13       0.00
Minimum of Months 0.00 0.00 0.261244E+11 0.261184E+11 23273.69   23273.69 0.00
Maximum of Months 0.00 0.00 0.206914E+12 0.204503E+12 83832.37   83832.37 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.972830E+09 0.972378E+09 2185.67 26-JAN-17:00 2185.67 0.00
February 0.00 0.00 0.581139E+10 0.580862E+10 4435.15 15-FEB-17:00 4435.15 0.00
March 0.00 0.00 0.128712E+11 0.128663E+11 6800.83 31-MAR-23:20 6800.83 0.00
April 0.00 0.00 0.186146E+11 0.186138E+11 8389.69 16-APR-17:42 8389.69 0.00
May 0.00 0.00 0.522189E+10 0.518263E+10 3888.40 31-MAY-24:00 3888.40 0.00
June 0.00 0.00 0.104985E+11 0.104036E+11 5834.46 30-JUN-24:00 5801.55 0.00
July 0.00 0.00 0.160792E+11 0.158554E+11 7607.93 31-JUL-23:53 7599.02 0.00
August 0.00 0.00 0.208082E+11 0.205672E+11 8387.94 13-AUG-19:23 8387.94 0.00
September 0.00 0.00 0.552014E+10 0.537036E+10 3934.03 30-SEP-23:40 3902.93 0.00
October 0.00 0.00 0.909302E+10 0.903562E+10 5178.91 31-OCT-23:40 5178.91 0.00
November 0.00 0.00 0.115553E+11 0.115443E+11 6205.29 02-NOV-16:40 6118.16 0.00
December 0.00 0.00 0.153835E+11 0.153834E+11 7510.68 29-DEC-16:50 7510.68 0.00
                 
Annual Sum or Average 0.00 0.00 0.132430E+12 0.131604E+12       0.00
Minimum of Months 0.00 0.00 0.972830E+09 0.972378E+09 2185.67   2185.67 0.00
Maximum of Months 0.00 0.00 0.208082E+11 0.205672E+11 8389.69   8389.69 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 63163.15 998567.03 24-JAN-06:01
February 0.00 0.00 01-FEB-00:10 40010.02 1006272.54 08-FEB-06:01
March 0.00 0.00 01-MAR-00:10 8580.16 901086.37 04-MAR-06:02
April 0.00 0.00 01-APR-00:10 1165.39 136334.97 08-APR-06:05
May 0.00 0.00 01-MAY-00:03 110.77 39056.86 06-MAY-06:10
June 0.00 0.00 01-JUN-00:10 0.48 455.89 09-JUN-05:25
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:03 0.00 0.00 01-AUG-00:03
September 0.00 0.00 01-SEP-00:05 0.00 0.00 01-SEP-00:05
October 0.00 0.00 01-OCT-00:10 5306.19 813974.74 26-OCT-05:03
November 0.00 0.00 01-NOV-00:10 14691.73 959104.05 28-NOV-06:01
December 0.00 0.00 01-DEC-00:10 62747.26 1071590.98 09-DEC-05:01
             
Annual Sum or Average 0.00     16255.18    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   63163.15 1071590.98  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 8964.71 423828.40 05-JAN-15:00 0.00 0.00 01-JAN-00:05
February 25151.56 1061184.11 14-FEB-16:40 0.00 0.00 01-FEB-00:10
March 65693.85 1131772.04 08-MAR-16:20 0.25 2194.57 12-MAR-18:35
April 205482.27 1177823.25 28-APR-14:00 46.01 101323.69 29-APR-00:53
May 329663.20 1287745.47 23-MAY-12:30 302.17 339632.51 28-MAY-07:12
June 564915.38 1527723.49 28-JUN-14:50 72.28 89638.65 14-JUN-02:42
July 657685.78 1540165.94 31-JUL-15:00 0.44 4592.26 13-JUL-01:53
August 630233.76 1477440.37 23-AUG-16:00 0.48 6456.36 20-AUG-03:53
September 453953.84 1684443.15 05-SEP-13:10 80.45 230331.96 11-SEP-03:02
October 222766.57 1360370.92 02-OCT-11:00 181.44 375987.88 01-OCT-06:53
November 18306.58 720062.61 02-NOV-15:00 0.00 0.00 01-NOV-00:10
December 2634.22 74653.51 24-DEC-15:23 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 266933.95     57.51    
Minimum of Months 2634.22 74653.51   0.00 0.00  
Maximum of Months 657685.78 1684443.15   302.17 375987.88  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 4843.08 291170.57 05-JAN-15:00 0.00 0.00 01-JAN-00:05
February 16260.38 854776.38 14-FEB-16:00 0.00 0.00 01-FEB-00:10
March 41296.80 860649.10 08-MAR-14:00 0.00 0.00 01-MAR-00:10
April 148248.89 1215941.84 28-APR-14:00 0.00 0.00 01-APR-00:10
May 249681.44 1351899.10 23-MAY-12:30 0.00 0.00 01-MAY-00:03
June 474792.37 2350507.04 29-JUN-05:03 0.00 0.00 01-JUN-00:10
July 558463.56 2784983.38 01-JUL-05:02 0.00 0.00 01-JUL-00:10
August 546282.19 2814204.09 14-AUG-05:02 0.00 0.00 01-AUG-00:03
September 380518.85 2299150.48 05-SEP-05:03 0.00 0.00 01-SEP-00:05
October 177088.53 1482950.91 02-OCT-11:00 0.00 0.00 01-OCT-00:10
November 10783.48 548060.99 02-NOV-15:00 0.00 0.00 01-NOV-00:10
December 6.77 59314.14 24-DEC-14:43 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 218611.32     0.00    
Minimum of Months 6.77 59314.14   0.00 0.00  
Maximum of Months 558463.56 2814204.09   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 15646.96 35862.33 26-JAN-17:00 0.00 0.00 01-JAN-00:05
February 46927.39 118007.55 14-FEB-16:00 0.00 0.00 01-FEB-00:10
March 80945.67 158478.81 08-MAR-16:00 0.00 0.00 01-MAR-00:10
April 128576.86 238672.93 13-APR-17:00 0.00 0.00 01-APR-00:10
May 58705.61 176625.20 19-MAY-16:00 0.00 0.00 01-MAY-00:03
June 136969.42 321255.27 28-JUN-16:00 0.00 0.00 01-JUN-00:10
July 194361.30 345163.62 22-JUL-15:00 0.00 0.00 01-JUL-00:10
August 210250.26 344865.34 01-AUG-16:00 0.00 0.00 01-AUG-00:03
September 73064.02 204536.26 03-SEP-14:00 0.00 0.00 01-SEP-00:05
October 69891.78 200425.82 01-OCT-16:00 0.00 0.00 01-OCT-00:10
November 76161.21 113534.65 09-NOV-14:00 0.00 0.00 01-NOV-00:10
December 97614.43 113748.64 29-DEC-16:40 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 99471.26     0.00    
Minimum of Months 15646.96 35862.33   0.00 0.00  
Maximum of Months 210250.26 345163.62   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 15593.79 52445.88 31-JAN-12:25
February 0.00 0.00 01-FEB-00:10 15792.92 52488.40 03-FEB-12:10
March 0.00 0.00 01-MAR-00:10 16305.49 51970.47 01-MAR-12:50
April 0.00 0.00 01-APR-00:10 14628.31 49723.47 03-APR-11:40
May 0.00 0.00 01-MAY-00:03 14122.48 46850.42 01-MAY-12:00
June 0.00 0.00 01-JUN-00:10 13495.46 43471.19 01-JUN-11:50
July 0.00 0.00 01-JUL-00:10 11972.26 40728.70 03-JUL-12:00
August 0.00 0.00 01-AUG-00:03 12847.81 40024.56 31-AUG-11:40
September 0.00 0.00 01-SEP-00:05 12506.54 41934.99 29-SEP-11:40
October 0.00 0.00 01-OCT-00:10 13235.23 45171.19 31-OCT-12:00
November 0.00 0.00 01-NOV-00:10 14336.50 48453.87 30-NOV-13:00
December 0.00 0.00 01-DEC-00:10 14698.30 51015.09 29-DEC-12:40
             
Annual Sum or Average 0.00     14118.47    
Minimum of Months 0.00 0.00   11972.26 40024.56  
Maximum of Months 0.00 0.00   16305.49 52488.40  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 3239.85 263486.77 05-JAN-15:00 1559.97 117985.43 25-JAN-10:50
February 13286.13 788198.92 14-FEB-16:10 2600.35 129080.78 03-FEB-14:30
March 37466.42 806466.80 08-MAR-14:00 2013.17 109137.33 22-MAR-11:20
April 151830.92 1905301.56 17-APR-13:50 2302.23 103202.14 03-APR-05:40
May 275475.17 2078143.78 19-MAY-15:20 736.62 89176.17 20-MAY-07:00
June 592939.25 2165423.34 29-JUN-10:30 849.49 85714.26 19-JUN-05:50
July 706421.31 2864688.88 31-JUL-15:00 156.58 33870.59 19-JUL-01:40
August 680971.93 2398205.74 23-AUG-16:00 477.85 38345.49 16-AUG-01:55
September 469307.63 2860103.55 05-SEP-13:10 531.21 89571.45 21-SEP-05:40
October 194115.60 2032889.55 02-OCT-10:20 1356.61 112367.99 26-OCT-05:30
November 8285.88 425420.35 02-NOV-15:10 1987.57 129741.28 27-NOV-06:50
December 124.34 26442.44 24-DEC-15:23 3265.93 131156.39 14-DEC-15:20
             
Annual Sum or Average 262671.71     1478.06    
Minimum of Months 124.34 26442.44   156.58 33870.59  
Maximum of Months 706421.31 2864688.88   3265.93 131156.39  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.154502E+11 0.97 10046.53 01-JAN-00:20 1.69
February 0.137999E+11 0.96 10046.53 01-FEB-05:01 1.70
March 0.160684E+11 1.01 10046.53 01-MAR-05:02 1.69
April 0.149844E+11 0.98 10046.53 01-APR-04:03 1.70
May 0.160233E+11 1.01 10046.53 01-MAY-03:05 1.68
June 0.159539E+11 1.03 10046.53 01-JUN-03:02 1.68
July 0.160654E+11 1.00 10046.53 01-JUL-03:02 1.67
August 0.173825E+11 1.08 10046.53 01-AUG-03:02 1.68
September 0.164455E+11 1.06 10046.53 01-SEP-03:02 1.67
October 0.167371E+11 1.05 10046.53 01-OCT-14:23 1.68
November 0.154090E+11 1.00 10046.53 01-NOV-03:02 1.69
December 0.153812E+11 0.97 10046.53 01-DEC-04:10 1.69
           
Annual Sum or Average 0.189701E+12 1.01      
Minimum of Months 0.137999E+11 0.96 10046.53   1.67
Maximum of Months 0.173825E+11 1.08 10046.53   1.70



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.458725E+10 0.39 10863.98 20-JAN-06:01 1.36
February 0.498953E+10 0.42 11179.52 15-FEB-16:40 1.38
March 0.788127E+10 0.53 12578.73 13-MAR-15:10 1.49
April 0.108003E+11 0.67 16258.36 17-APR-15:20 1.74
May 0.948329E+10 0.59 18404.11 22-MAY-05:03 1.87
June 0.125899E+11 0.75 22534.01 19-JUN-05:02 2.14
July 0.146175E+11 0.81 22534.01 01-JUL-05:02 2.12
August 0.157237E+11 0.86 22534.01 04-AUG-05:02 2.12
September 0.941927E+10 0.59 21623.76 05-SEP-05:03 2.06
October 0.816781E+10 0.54 22534.01 02-OCT-05:02 2.12
November 0.678771E+10 0.49 11922.84 24-NOV-16:00 1.44
December 0.604498E+10 0.44 10630.42 11-DEC-06:01 1.34
           
Annual Sum or Average 0.111093E+12 0.59      
Minimum of Months 0.458725E+10 0.39 10630.42   1.34
Maximum of Months 0.157237E+11 0.86 22534.01   2.14



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.345227E+11 0.38 52630.89 06-JAN-06:02 0.96
February 0.334650E+11 0.39 101934.55 17-FEB-06:02 1.39
March 0.467155E+11 0.43 98628.34 11-MAR-06:02 1.37
April 0.641628E+11 0.50 126658.13 13-APR-15:20 1.60
May 0.774971E+11 0.55 177076.39 15-MAY-05:03 1.97
June 0.101941E+12 0.67 220619.97 07-JUN-05:02 2.25
July 0.111277E+12 0.68 220619.97 05-JUL-05:02 2.25
August 0.110952E+12 0.69 220619.97 03-AUG-05:03 2.24
September 0.759651E+11 0.55 220619.97 15-SEP-05:02 2.25
October 0.566034E+11 0.46 157441.29 07-OCT-05:03 1.82
November 0.396160E+11 0.40 101308.60 25-NOV-06:03 1.39
December 0.347382E+11 0.38 92722.84 01-DEC-06:02 1.32
           
Annual Sum or Average 0.787455E+12 0.51      
Minimum of Months 0.334650E+11 0.38 52630.89   0.96
Maximum of Months 0.111277E+12 0.69 220619.97   2.25



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.336373E+10 0.38 4836.00 02-JAN-05:01 0.85
February 0.305154E+10 0.37 6174.28 15-FEB-16:40 0.97
March 0.370104E+10 0.38 6859.50 24-MAR-15:50 1.03
April 0.543433E+10 0.43 14115.96 28-APR-14:50 1.58
May 0.718289E+10 0.49 16062.93 30-MAY-14:30 1.71
June 0.107229E+11 0.64 22898.77 27-JUN-15:40 2.13
July 0.121707E+11 0.67 22898.77 01-JUL-05:02 2.12
August 0.117582E+11 0.66 22850.56 14-AUG-05:02 2.11
September 0.723327E+10 0.50 16911.30 01-SEP-05:03 1.75
October 0.466422E+10 0.40 11496.69 07-OCT-05:03 1.38
November 0.325552E+10 0.36 6046.42 02-NOV-16:00 0.95
December 0.333844E+10 0.37 4836.00 04-DEC-05:01 0.85
           
Annual Sum or Average 0.758767E+11 0.47      
Minimum of Months 0.305154E+10 0.36 4836.00   0.85
Maximum of Months 0.121707E+11 0.67 22898.77   2.13



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.171620E+10 1.12 640.75 01-JAN-00:05 1.11
February 0.155011E+10 1.12 640.75 01-FEB-00:10 1.12
March 0.171620E+10 1.12 640.75 01-MAR-00:10 1.12
April 0.166084E+10 1.12 640.75 01-APR-00:10 1.12
May 0.171620E+10 1.11 640.75 01-MAY-00:03 1.12
June 0.166084E+10 1.11 640.75 01-JUN-00:10 1.12
July 0.171620E+10 1.11 640.75 01-JUL-00:10 1.11
August 0.171620E+10 1.11 640.75 01-AUG-00:03 1.11
September 0.166084E+10 1.11 640.75 01-SEP-00:05 1.11
October 0.171620E+10 1.11 640.75 01-OCT-00:10 1.11
November 0.166084E+10 1.12 640.75 01-NOV-00:10 1.12
December 0.171620E+10 1.12 640.75 01-DEC-00:10 1.12
           
Annual Sum or Average 0.202068E+11 1.11      
Minimum of Months 0.155011E+10 1.11 640.75   1.11
Maximum of Months 0.171620E+10 1.12 640.75   1.12



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.163900E+11 1.12 6119.32 01-JAN-00:10 1.11
February 0.148039E+11 1.12 6119.32 01-FEB-00:10 1.12
March 0.163900E+11 1.12 6119.32 01-MAR-00:10 1.12
April 0.158613E+11 1.12 6119.32 01-APR-00:10 1.12
May 0.163900E+11 1.11 6119.32 01-MAY-00:07 1.12
June 0.158613E+11 1.11 6119.32 01-JUN-00:10 1.12
July 0.163900E+11 1.11 6119.32 01-JUL-00:10 1.11
August 0.163900E+11 1.11 6119.32 01-AUG-00:03 1.11
September 0.158613E+11 1.11 6119.32 01-SEP-00:05 1.11
October 0.163900E+11 1.11 6119.32 01-OCT-00:10 1.11
November 0.158613E+11 1.12 6119.32 01-NOV-00:10 1.12
December 0.163900E+11 1.12 6119.32 01-DEC-00:10 1.12
           
Annual Sum or Average 0.192979E+12 1.11      
Minimum of Months 0.148039E+11 1.11 6119.32   1.11
Maximum of Months 0.163900E+11 1.12 6119.32   1.12



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.167558E+10 1.12 625.59 01-JAN-00:05 1.11
February 0.151343E+10 1.12 625.59 01-FEB-00:10 1.12
March 0.167558E+10 1.12 625.59 01-MAR-00:10 1.12
April 0.162153E+10 1.12 625.59 01-APR-00:10 1.12
May 0.167558E+10 1.11 625.59 01-MAY-00:03 1.12
June 0.162153E+10 1.11 625.59 01-JUN-00:10 1.12
July 0.167558E+10 1.11 625.59 01-JUL-00:10 1.11
August 0.167558E+10 1.11 625.59 01-AUG-00:03 1.11
September 0.162153E+10 1.11 625.59 01-SEP-00:05 1.11
October 0.167558E+10 1.11 625.59 01-OCT-00:10 1.11
November 0.162153E+10 1.12 625.59 01-NOV-00:10 1.12
December 0.167558E+10 1.12 625.59 01-DEC-00:10 1.12
           
Annual Sum or Average 0.197286E+11 1.11      
Minimum of Months 0.151343E+10 1.11 625.59   1.11
Maximum of Months 0.167558E+10 1.12 625.59   1.12



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.732010E+09 0.665397E+09 3292.58 20-JAN-06:01 2992.95 2992.95 39.96 5.36
February 0.417252E+09 0.379282E+09 3272.09 08-FEB-06:01 2974.33 2974.33 35.63 5.30
March 96814124.70 88004039.35 3124.83 04-MAR-06:02 2840.47 2840.47 37.15 4.88
April 12581463.08 11436549.94 554.82 08-APR-06:10 504.33 504.33 26.72 0.60
May 1207086.10 1097241.27 157.04 06-MAY-06:10 142.75 142.75 23.10 0.16
June 5085.73 4622.93 1.86 09-JUN-05:25 1.69 1.69 22.76 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 22.73 0.00
August 0.00 0.00 0.00 01-AUG-00:03 0.00 0.00 22.73 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00 0.00 22.73 0.00
October 59887448.89 54437691.04 2936.60 26-OCT-05:03 2669.37 2669.37 37.13 4.39
November 0.162714E+09 0.147907E+09 3238.01 27-NOV-06:01 2943.35 2943.35 37.99 5.20
December 0.725156E+09 0.659166E+09 3277.97 11-DEC-06:01 2979.67 2979.67 37.49 5.32
                 
Annual Sum or Average 0.220763E+10 0.200673E+10            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 22.73 0.00
Maximum of Months 0.732010E+09 0.665397E+09 3292.58   2992.95 2992.95 39.96 5.36



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 4806123.71 4368766.45 148.16 05-JAN-14:30 134.68 134.68 8.88 9.84
February 29541168.62 26852922.27 1057.11 14-FEB-15:50 960.92 960.92 8.76 26.41
March 52332252.71 47570017.71 1003.62 08-MAR-14:00 912.29 912.29 7.85 25.78
April 0.225165E+09 0.204675E+09 1691.71 28-APR-13:40 1537.77 1537.77 7.38 32.71
May 0.486061E+09 0.441829E+09 6382.53 23-MAY-12:30 5801.72 5801.72 7.21 57.82
June 0.202167E+10 0.183770E+10 16960.44 29-JUN-05:03 15417.04 15417.04 7.43 85.67
July 0.228161E+10 0.207399E+10 18001.94 01-JUL-05:02 16363.76 16363.76 8.30 87.71
August 0.254748E+10 0.231566E+10 18001.94 14-AUG-05:02 16363.76 16363.76 8.31 87.71
September 0.227164E+10 0.206492E+10 17344.79 05-SEP-05:03 15766.42 15766.42 8.93 86.43
October 0.794719E+09 0.722400E+09 11487.28 02-OCT-11:00 10441.94 10441.94 7.31 73.41
November 11737969.16 10669813.97 547.97 02-NOV-15:00 498.10 498.10 9.12 19.33
December 4035.45 3668.22 14.19 24-DEC-14:43 12.90 12.90 8.55 2.22
                 
Annual Sum or Average 0.107268E+11 0.975063E+10            
Minimum of Months 4035.45 3668.22 14.19   12.90 12.90 7.21 2.22
Maximum of Months 0.254748E+10 0.231566E+10 18001.94   16363.76 16363.76 9.12 87.71



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.316148E+10 0.287379E+10 12390.25 01-JAN-12:22 11262.74 11262.74 8.44 87.71
February 0.458624E+10 0.416889E+10 12390.25 01-FEB-13:00 11262.74 11262.74 8.43 87.71
March 0.722091E+10 0.656381E+10 12390.25 01-MAR-16:30 11262.74 11262.74 8.46 87.71
April 0.132085E+11 0.120066E+11 12390.25 01-APR-04:03 11262.74 11262.74 8.69 87.71
May 0.169960E+11 0.154494E+11 12390.25 01-MAY-03:05 11262.74 11262.74 8.45 87.71
June 0.245753E+11 0.223390E+11 12390.25 01-JUN-03:02 11262.74 11262.74 8.58 87.71
July 0.292091E+11 0.265510E+11 12390.25 01-JUL-00:12 11262.74 11262.74 7.49 87.71
August 0.297528E+11 0.270453E+11 12390.25 01-AUG-00:13 11262.74 11262.74 7.75 87.71
September 0.206638E+11 0.187834E+11 12390.25 01-SEP-00:05 11262.74 11262.74 7.61 87.71
October 0.136050E+11 0.123669E+11 12390.25 01-OCT-06:53 11262.74 11262.74 7.35 87.71
November 0.420479E+10 0.382215E+10 12390.25 01-NOV-09:40 11262.74 11262.74 8.46 87.71
December 0.389546E+10 0.354097E+10 12390.25 01-DEC-06:02 11262.74 11262.74 8.53 87.71
                 
Annual Sum or Average 0.171079E+12 0.155511E+12            
Minimum of Months 0.316148E+10 0.287379E+10 12390.25   11262.74 11262.74 7.35 87.71
Maximum of Months 0.297528E+11 0.270453E+11 12390.25   11262.74 11262.74 8.69 87.71



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.194939E+10 0.177199E+10 727.82 01-JAN-00:05 661.59 661.59 19.82 3.07
February 0.176074E+10 0.160051E+10 727.82 01-FEB-00:10 661.59 661.59 22.04 3.07
March 0.194939E+10 0.177199E+10 727.82 01-MAR-00:10 661.59 661.59 25.07 3.07
April 0.188650E+10 0.171483E+10 727.82 01-APR-00:10 661.59 661.59 28.27 3.07
May 0.194939E+10 0.177199E+10 727.82 01-MAY-00:03 661.59 661.59 21.51 3.07
June 0.188650E+10 0.171483E+10 727.82 01-JUN-00:10 661.59 661.59 25.29 3.07
July 0.194939E+10 0.177199E+10 727.82 01-JUL-00:10 661.59 661.59 32.16 3.07
August 0.194939E+10 0.177199E+10 727.82 01-AUG-00:03 661.59 661.59 34.14 3.07
September 0.188650E+10 0.171483E+10 727.82 01-SEP-00:05 661.59 661.59 25.97 3.07
October 0.194939E+10 0.177199E+10 727.82 01-OCT-00:10 661.59 661.59 24.14 3.07
November 0.188650E+10 0.171483E+10 727.82 01-NOV-00:10 661.59 661.59 25.94 3.07
December 0.194939E+10 0.177199E+10 727.82 01-DEC-00:10 661.59 661.59 27.54 3.07
                 
Annual Sum or Average 0.229524E+11 0.208638E+11            
Minimum of Months 0.176074E+10 0.160051E+10 727.82   661.59 661.59 19.82 3.07
Maximum of Months 0.194939E+10 0.177199E+10 727.82   661.59 661.59 34.14 3.07



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 11967951.72 3590385.52 5.96 01-JAN-06:05 1.79 1.79 55.66 0.44
February 10809762.85 3242928.85 5.96 01-FEB-06:01 1.79 1.79 55.85 0.44
March 11967951.72 3590385.52 5.96 01-MAR-06:02 1.79 1.79 56.55 0.44
April 11581888.76 3474566.63 5.96 01-APR-05:03 1.79 1.79 56.32 0.44
May 11967951.72 3590385.52 5.96 01-MAY-05:03 1.79 1.79 55.93 0.44
June 11581888.76 3474566.63 5.96 01-JUN-05:02 1.79 1.79 56.49 0.44
July 11967951.72 3590385.52 5.96 01-JUL-05:02 1.79 1.79 56.37 0.44
August 11967951.72 3590385.52 5.96 01-AUG-05:03 1.79 1.79 56.74 0.44
September 11581888.76 3474566.63 5.96 01-SEP-05:03 1.79 1.79 56.21 0.44
October 11967951.72 3590385.52 5.96 01-OCT-05:10 1.79 1.79 56.10 0.44
November 11581888.76 3474566.63 5.96 01-NOV-05:03 1.79 1.79 56.86 0.44
December 11967951.72 3590385.52 5.96 01-DEC-06:02 1.79 1.79 56.34 0.44
                 
Annual Sum or Average 0.140913E+09 42273893.99            
Minimum of Months 10809762.85 3242928.85 5.96   1.79 1.79 55.66 0.44
Maximum of Months 11967951.72 3590385.52 5.96   1.79 1.79 56.86 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.401141E+10 0.364637E+10 15733.77 05-JAN-15:00 14302.00 14302.00 22.29 52.89
February 0.584847E+10 0.531626E+10 31476.81 14-FEB-16:40 28612.42 28612.42 22.69 105.79
March 0.919950E+10 0.836235E+10 31478.79 08-MAR-16:20 28614.22 28614.22 22.78 105.79
April 0.182506E+11 0.165898E+11 31539.85 17-APR-13:50 28669.72 28669.72 25.41 105.79
May 0.248120E+11 0.225541E+11 31550.18 19-MAY-15:20 28679.11 28679.11 25.80 105.79
June 0.404576E+11 0.367759E+11 31555.40 29-JUN-10:30 28683.86 28683.86 26.00 105.79
July 0.492106E+11 0.447325E+11 31597.29 31-JUL-15:00 28721.94 28721.94 27.58 105.79
August 0.496074E+11 0.450931E+11 31569.33 23-AUG-16:00 28696.52 28696.52 26.52 105.79
September 0.331554E+11 0.301382E+11 31597.01 05-SEP-13:10 28721.69 28721.69 27.57 105.79
October 0.193742E+11 0.176111E+11 31547.47 02-OCT-10:20 28676.65 28676.65 25.70 105.79
November 0.533572E+10 0.485017E+10 15742.07 02-NOV-15:10 14309.54 14309.54 23.02 52.89
December 0.494199E+10 0.449227E+10 15721.65 24-DEC-15:23 14290.98 14290.98 21.22 52.89
                 
Annual Sum or Average 0.264205E+12 0.240162E+12            
Minimum of Months 0.401141E+10 0.364637E+10 15721.65   14290.98 14290.98 21.22 52.89
Maximum of Months 0.496074E+11 0.450931E+11 31597.29   28721.94 28721.94 27.58 105.79



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 57.40 57.40 63163.15 998567.03 24-JAN-06:01
February 0.00 0.00 01-FEB-00:10 32.58 32.58 40010.02 1006272.54 08-FEB-06:01
March 0.00 0.00 01-MAR-00:10 25.28 25.28 8580.16 901086.37 04-MAR-06:02
April 0.00 0.00 01-APR-00:10 24.58 24.58 1165.39 136334.97 08-APR-06:05
May 0.00 0.00 01-MAY-00:03 24.18 24.18 110.77 39056.86 06-MAY-06:10
June 0.00 0.00 01-JUN-00:10 22.76 22.76 0.48 455.89 09-JUN-05:25
July 0.00 0.00 01-JUL-00:10 22.73 22.73 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:03 22.73 22.73 0.00 0.00 01-AUG-00:03
September 0.00 0.00 01-SEP-00:05 22.73 22.73 0.00 0.00 01-SEP-00:05
October 0.00 0.00 01-OCT-00:10 22.73 22.73 5306.19 813974.74 26-OCT-05:03
November 0.00 0.00 01-NOV-00:10 25.33 25.33 14691.73 959104.05 28-NOV-06:01
December 0.00 0.00 01-DEC-00:10 23.97 23.97 62747.26 1071590.98 09-DEC-05:01
                 
Annual Sum or Average 0.00         16255.18    
Minimum of Months 0.00 0.00   22.73 22.73 0.00 0.00  
Maximum of Months 0.00 0.00   57.40 57.40 63163.15 1071590.98  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 8964.71 423828.40 05-JAN-15:00 9.45 8.87 0.00 0.00 01-JAN-00:05
February 25151.56 1061184.11 14-FEB-16:40 10.37 8.91 0.00 0.00 01-FEB-00:10
March 65693.85 1131772.04 08-MAR-16:20 10.40 8.73 0.25 2194.57 12-MAR-18:35
April 205482.27 1177823.25 28-APR-14:00 10.25 7.05 46.01 101323.69 29-APR-00:53
May 329663.20 1287745.47 23-MAY-12:30 10.50 7.00 302.17 339632.51 28-MAY-07:12
June 564915.38 1527723.49 28-JUN-14:50 10.86 6.70 72.28 89638.65 14-JUN-02:42
July 657685.78 1540165.94 31-JUL-15:00 10.89 6.70 0.44 4592.26 13-JUL-01:53
August 630233.76 1477440.37 23-AUG-16:00 11.23 7.21 0.48 6456.36 20-AUG-03:53
September 453953.84 1684443.15 05-SEP-13:10 11.69 7.11 80.45 230331.96 11-SEP-03:02
October 222766.57 1360370.92 02-OCT-11:00 10.82 7.12 181.44 375987.88 01-OCT-06:53
November 18306.58 720062.61 02-NOV-15:00 10.09 9.10 0.00 0.00 01-NOV-00:10
December 2634.22 74653.51 24-DEC-15:23 8.57 8.47 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 266933.95         57.51    
Minimum of Months 2634.22 74653.51   8.57 6.70 0.00 0.00  
Maximum of Months 657685.78 1684443.15   11.69 9.10 302.17 375987.88  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 4843.08 291170.57 05-JAN-15:00 13.79 8.87 0.00 0.00 01-JAN-00:05
February 16260.38 854776.38 14-FEB-16:00 14.49 8.75 0.00 0.00 01-FEB-00:10
March 41296.80 860649.10 08-MAR-14:00 14.68 8.34 0.00 0.00 01-MAR-00:10
April 148248.89 1215941.84 28-APR-14:00 15.65 7.05 0.00 0.00 01-APR-00:10
May 249681.44 1351899.10 23-MAY-12:30 12.28 8.27 0.00 0.00 01-MAY-00:03
June 474792.37 2350507.04 29-JUN-05:03 13.25 7.12 0.00 0.00 01-JUN-00:10
July 558463.56 2784983.38 01-JUL-05:02 14.29 8.17 0.00 0.00 01-JUL-00:10
August 546282.19 2814204.09 14-AUG-05:02 14.37 8.12 0.00 0.00 01-AUG-00:03
September 380518.85 2299150.48 05-SEP-05:03 13.05 9.21 0.00 0.00 01-SEP-00:05
October 177088.53 1482950.91 02-OCT-11:00 11.52 7.13 0.00 0.00 01-OCT-00:10
November 10783.48 548060.99 02-NOV-15:00 13.47 9.12 0.00 0.00 01-NOV-00:10
December 6.77 59314.14 24-DEC-14:43 13.07 8.43 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 218611.32         0.00    
Minimum of Months 6.77 59314.14   11.52 7.05 0.00 0.00  
Maximum of Months 558463.56 2814204.09   15.65 9.21 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 15646.96 35862.33 26-JAN-17:00 21.69 18.33 0.00 0.00 01-JAN-00:05
February 46927.39 118007.55 14-FEB-16:00 29.31 23.49 0.00 0.00 01-FEB-00:10
March 80945.67 158478.81 08-MAR-16:00 33.03 24.67 0.00 0.00 01-MAR-00:10
April 128576.86 238672.93 13-APR-17:00 40.32 28.72 0.00 0.00 01-APR-00:10
May 58705.61 176625.20 19-MAY-16:00 34.69 30.86 0.00 0.00 01-MAY-00:03
June 136969.42 321255.27 28-JUN-16:00 47.71 40.55 0.00 0.00 01-JUN-00:10
July 194361.30 345163.62 22-JUL-15:00 49.84 40.46 0.00 0.00 01-JUL-00:10
August 210250.26 344865.34 01-AUG-16:00 49.81 37.77 0.00 0.00 01-AUG-00:03
September 73064.02 204536.26 03-SEP-14:00 37.23 33.61 0.00 0.00 01-SEP-00:05
October 69891.78 200425.82 01-OCT-16:00 36.85 30.36 0.00 0.00 01-OCT-00:10
November 76161.21 113534.65 09-NOV-14:00 28.90 21.12 0.00 0.00 01-NOV-00:10
December 97614.43 113748.64 29-DEC-16:40 28.92 18.33 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 99471.26         0.00    
Minimum of Months 15646.96 35862.33   21.69 18.33 0.00 0.00  
Maximum of Months 210250.26 345163.62   49.84 40.55 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 57.62 57.62 15593.79 52445.88 31-JAN-12:25
February 0.00 0.00 01-FEB-00:10 56.34 56.34 15792.92 52488.40 03-FEB-12:10
March 0.00 0.00 01-MAR-00:10 57.07 57.07 16305.49 51970.47 01-MAR-12:50
April 0.00 0.00 01-APR-00:10 56.93 56.93 14628.31 49723.47 03-APR-11:40
May 0.00 0.00 01-MAY-00:03 56.69 56.69 14122.48 46850.42 01-MAY-12:00
June 0.00 0.00 01-JUN-00:10 56.97 56.97 13495.46 43471.19 01-JUN-11:50
July 0.00 0.00 01-JUL-00:10 56.77 56.77 11972.26 40728.70 03-JUL-12:00
August 0.00 0.00 01-AUG-00:03 57.18 57.18 12847.81 40024.56 31-AUG-11:40
September 0.00 0.00 01-SEP-00:05 56.83 56.83 12506.54 41934.99 29-SEP-11:40
October 0.00 0.00 01-OCT-00:10 57.02 57.02 13235.23 45171.19 31-OCT-12:00
November 0.00 0.00 01-NOV-00:10 57.36 57.36 14336.50 48453.87 30-NOV-13:00
December 0.00 0.00 01-DEC-00:10 56.90 56.90 14698.30 51015.09 29-DEC-12:40
                 
Annual Sum or Average 0.00         14118.47    
Minimum of Months 0.00 0.00   56.34 56.34 11972.26 40024.56  
Maximum of Months 0.00 0.00   57.62 57.62 16305.49 52488.40  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 3239.85 263486.77 05-JAN-15:00 22.29 21.10 1559.97 117985.43 25-JAN-10:50
February 13286.13 788198.92 14-FEB-16:10 24.67 21.10 2600.35 129080.78 03-FEB-14:30
March 37466.42 806466.80 08-MAR-14:00 24.75 21.10 2013.17 109137.33 22-MAR-11:20
April 151830.92 1905301.56 17-APR-13:50 25.41 21.10 2302.23 103202.14 03-APR-05:40
May 275475.17 2078143.78 19-MAY-15:20 25.80 21.10 736.62 89176.17 20-MAY-07:00
June 592939.25 2165423.34 29-JUN-10:30 26.00 21.86 849.49 85714.26 19-JUN-05:50
July 706421.31 2864688.88 31-JUL-15:00 27.58 23.54 156.58 33870.59 19-JUL-01:40
August 680971.93 2398205.74 23-AUG-16:00 26.52 22.66 477.85 38345.49 16-AUG-01:55
September 469307.63 2860103.55 05-SEP-13:10 27.57 23.12 531.21 89571.45 21-SEP-05:40
October 194115.60 2032889.55 02-OCT-10:20 25.70 21.10 1356.61 112367.99 26-OCT-05:30
November 8285.88 425420.35 02-NOV-15:10 23.02 21.10 1987.57 129741.28 27-NOV-06:50
December 124.34 26442.44 24-DEC-15:23 21.22 20.44 3265.93 131156.39 14-DEC-15:20
                 
Annual Sum or Average 262671.71         1478.06    
Minimum of Months 124.34 26442.44   21.22 20.44 156.58 33870.59  
Maximum of Months 706421.31 2864688.88   27.58 23.54 3265.93 131156.39  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.611647E+10 0.00 0.874801E+09 0.458725E+10 0.00 0.00
February 0.311425E+10 0.00 0.288684E+10 0.498953E+10 0.00 0.00
March 0.557406E+09 0.00 0.920135E+10 0.788127E+10 0.00 0.00
April 30264058.54 0.00 0.335933E+11 0.108003E+11 0.00 0.00
May 1173737.94 0.00 0.515670E+11 0.948329E+10 0.00 0.00
June 0.00 0.00 0.101735E+12 0.125899E+11 0.00 0.00
July 0.00 0.00 0.131826E+12 0.146175E+11 0.00 0.00
August 0.00 0.00 0.129946E+12 0.157237E+11 0.00 0.00
September 0.00 0.00 0.743874E+11 0.941927E+10 0.00 0.00
October 0.380830E+09 0.00 0.358027E+11 0.816781E+10 0.00 0.00
November 0.673143E+09 0.00 0.223797E+10 0.678771E+10 0.00 0.00
December 0.421766E+10 0.00 540032.06 0.604498E+10 0.00 0.00
             
Annual Sum or Average 0.150912E+11 0.00 0.574059E+12 0.111093E+12 0.00 0.00
Minimum of Months 0.00 0.00 540032.06 0.458725E+10 0.00 0.00
Maximum of Months 0.611647E+10 0.00 0.131826E+12 0.157237E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.134971E+12 0.00 0.783570E+10 0.345227E+11 0.00 0.00
February 0.765772E+11 0.00 0.228936E+11 0.334650E+11 0.00 0.00
March 0.168827E+11 0.00 0.680710E+11 0.467155E+11 0.00 0.00
April 0.204649E+10 0.00 0.246290E+12 0.641628E+11 0.00 0.00
May 0.152909E+09 0.00 0.445055E+12 0.774971E+11 0.00 0.00
June 0.00 0.00 0.866327E+12 0.101941E+12 0.00 0.00
July 0.00 0.00 0.105124E+13 0.111277E+12 0.00 0.00
August 0.00 0.00 0.996513E+12 0.110952E+12 0.00 0.00
September 0.00 0.00 0.651386E+12 0.759651E+11 0.00 0.00
October 0.106453E+11 0.00 0.295152E+12 0.566034E+11 0.00 0.00
November 0.282442E+11 0.00 0.160066E+11 0.396160E+11 0.00 0.00
December 0.135190E+12 0.00 11358595.73 0.347382E+11 0.00 0.00
             
Annual Sum or Average 0.404710E+12 0.00 0.466678E+13 0.787455E+12 0.00 0.00
Minimum of Months 0.00 0.00 11358595.73 0.334650E+11 0.00 0.00
Maximum of Months 0.135190E+12 0.00 0.105124E+13 0.111277E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.297115E+11 0.00 0.394535E+09 0.336373E+10 0.00 0.00
February 0.180028E+11 0.00 0.189525E+10 0.305154E+10 0.00 0.00
March 0.574705E+10 0.00 0.549794E+10 0.370104E+10 0.00 0.00
April 0.973084E+09 0.00 0.256558E+11 0.543433E+10 0.00 0.00
May 0.151919E+09 0.00 0.490399E+11 0.718289E+10 0.00 0.00
June 1394288.02 0.00 0.995448E+11 0.107229E+11 0.00 0.00
July 0.00 0.00 0.122368E+12 0.121707E+11 0.00 0.00
August 0.00 0.00 0.113999E+12 0.117582E+11 0.00 0.00
September 0.00 0.00 0.705042E+11 0.723327E+10 0.00 0.00
October 0.329886E+10 0.00 0.291977E+11 0.466422E+10 0.00 0.00
November 0.950793E+10 0.00 0.103100E+10 0.325552E+10 0.00 0.00
December 0.301650E+11 0.00 342.12 0.333844E+10 0.00 0.00
             
Annual Sum or Average 0.975595E+11 0.00 0.519128E+12 0.758767E+11 0.00 0.00
Minimum of Months 0.00 0.00 342.12 0.305154E+10 0.00 0.00
Maximum of Months 0.301650E+11 0.00 0.122368E+12 0.121707E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 16995512.17 0.154502E+11 0.00 0.00
February 0.00 0.00 0.123474E+10 0.137999E+11 0.00 0.00
March 0.00 0.00 0.341121E+10 0.160684E+11 0.00 0.00
April 0.00 0.00 0.172376E+11 0.149844E+11 0.00 0.00
May 0.00 0.00 0.303525E+11 0.160233E+11 0.00 0.00
June 0.00 0.00 0.560556E+11 0.159539E+11 0.00 0.00
July 0.00 0.00 0.686866E+11 0.160654E+11 0.00 0.00
August 0.00 0.00 0.680956E+11 0.173825E+11 0.00 0.00
September 0.00 0.00 0.461517E+11 0.164455E+11 0.00 0.00
October 0.00 0.00 0.215095E+11 0.167371E+11 0.00 0.00
November 0.00 0.00 0.607606E+09 0.154090E+11 0.00 0.00
December 0.00 0.00 0.00 0.153812E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.313360E+12 0.189701E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.137999E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.686866E+11 0.173825E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.573083E+10 0.288400E+10 0.00 0.00
February 0.00 0.00 0.113292E+11 0.373755E+10 0.00 0.00
March 0.00 0.00 0.192840E+11 0.530881E+10 0.00 0.00
April 0.00 0.00 0.251324E+11 0.640351E+10 0.00 0.00
May 0.00 0.00 0.767490E+10 0.334813E+10 0.00 0.00
June 0.00 0.00 0.142843E+11 0.484229E+10 0.00 0.00
July 0.00 0.00 0.215853E+11 0.658174E+10 0.00 0.00
August 0.00 0.00 0.276023E+11 0.763131E+10 0.00 0.00
September 0.00 0.00 0.784262E+10 0.333132E+10 0.00 0.00
October 0.00 0.00 0.136847E+11 0.439344E+10 0.00 0.00
November 0.00 0.00 0.185465E+11 0.508356E+10 0.00 0.00
December 0.00 0.00 0.248935E+11 0.626273E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.197591E+12 0.598084E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.573083E+10 0.288400E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.276023E+11 0.763131E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.330972E+11 0.233628E+11 0.00 0.00
February 0.00 0.00 0.914256E+11 0.326800E+11 0.00 0.00
March 0.00 0.00 0.171842E+12 0.486323E+11 0.00 0.00
April 0.00 0.00 0.235048E+12 0.603601E+11 0.00 0.00
May 0.00 0.00 0.686786E+11 0.310849E+11 0.00 0.00
June 0.00 0.00 0.134491E+12 0.458849E+11 0.00 0.00
July 0.00 0.00 0.205534E+12 0.627311E+11 0.00 0.00
August 0.00 0.00 0.263359E+12 0.728340E+11 0.00 0.00
September 0.00 0.00 0.711936E+11 0.310977E+11 0.00 0.00
October 0.00 0.00 0.122042E+12 0.404253E+11 0.00 0.00
November 0.00 0.00 0.161279E+12 0.458969E+11 0.00 0.00
December 0.00 0.00 0.213548E+12 0.558731E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.177154E+13 0.550863E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.330972E+11 0.233628E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.263359E+12 0.728340E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.124422E+10 0.194698E+10 0.00 0.00
February 0.00 0.00 0.725074E+10 0.295278E+10 0.00 0.00
March 0.00 0.00 0.158771E+11 0.468151E+10 0.00 0.00
April 0.00 0.00 0.229932E+11 0.600012E+10 0.00 0.00
May 0.00 0.00 0.665655E+10 0.311024E+10 0.00 0.00
June 0.00 0.00 0.135297E+11 0.465276E+10 0.00 0.00
July 0.00 0.00 0.207721E+11 0.636852E+10 0.00 0.00
August 0.00 0.00 0.265027E+11 0.737008E+10 0.00 0.00
September 0.00 0.00 0.703403E+10 0.313542E+10 0.00 0.00
October 0.00 0.00 0.113471E+11 0.392963E+10 0.00 0.00
November 0.00 0.00 0.142399E+11 0.430619E+10 0.00 0.00
December 0.00 0.00 0.189334E+11 0.522546E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.166381E+12 0.536797E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.124422E+10 0.194698E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.265027E+11 0.737008E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.458725E+10 0.874801E+09 0.611647E+10 0.00 0.00 0.00 0.00 0.00
February 0.498953E+10 0.288684E+10 0.311425E+10 0.00 0.00 0.00 0.00 0.00
March 0.788127E+10 0.920135E+10 0.557406E+09 0.00 0.00 0.00 0.00 0.00
April 0.108003E+11 0.335933E+11 30264058.54 0.00 0.00 0.00 0.00 0.00
May 0.948329E+10 0.515670E+11 1173737.94 0.00 0.00 0.00 0.00 0.00
June 0.125899E+11 0.101735E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.146175E+11 0.131826E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.157237E+11 0.129946E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.941927E+10 0.743874E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.816781E+10 0.358027E+11 0.380830E+09 0.00 0.00 0.00 0.00 0.00
November 0.678771E+10 0.223797E+10 0.673143E+09 0.00 0.00 0.00 0.00 0.00
December 0.604498E+10 540032.06 0.421766E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.111093E+12 0.574059E+12 0.150912E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.458725E+10 540032.06 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.157237E+11 0.131826E+12 0.611647E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.345227E+11 0.783570E+10 0.134971E+12 0.00 0.00 0.00 0.00 0.00
February 0.334650E+11 0.228936E+11 0.765772E+11 0.00 0.00 0.00 0.00 0.00
March 0.467155E+11 0.680710E+11 0.168827E+11 0.00 0.00 0.00 0.00 0.00
April 0.641628E+11 0.246290E+12 0.204649E+10 0.00 0.00 0.00 0.00 0.00
May 0.774971E+11 0.445055E+12 0.152909E+09 0.00 0.00 0.00 0.00 0.00
June 0.101941E+12 0.866327E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.111277E+12 0.105124E+13 0.00 0.00 0.00 0.00 0.00 0.00
August 0.110952E+12 0.996513E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.759651E+11 0.651386E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.566034E+11 0.295152E+12 0.106453E+11 0.00 0.00 0.00 0.00 0.00
November 0.396160E+11 0.160066E+11 0.282442E+11 0.00 0.00 0.00 0.00 0.00
December 0.347382E+11 11358595.73 0.135190E+12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.787455E+12 0.466678E+13 0.404710E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.334650E+11 11358595.73 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.111277E+12 0.105124E+13 0.135190E+12 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.336373E+10 0.394535E+09 0.297115E+11 0.00 0.00 0.00 0.00 0.00
February 0.305154E+10 0.189525E+10 0.180028E+11 0.00 0.00 0.00 0.00 0.00
March 0.370104E+10 0.549794E+10 0.574705E+10 0.00 0.00 0.00 0.00 0.00
April 0.543433E+10 0.256558E+11 0.973084E+09 0.00 0.00 0.00 0.00 0.00
May 0.718289E+10 0.490399E+11 0.151919E+09 0.00 0.00 0.00 0.00 0.00
June 0.107229E+11 0.995448E+11 1394288.02 0.00 0.00 0.00 0.00 0.00
July 0.121707E+11 0.122368E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.117582E+11 0.113999E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.723327E+10 0.705042E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.466422E+10 0.291977E+11 0.329886E+10 0.00 0.00 0.00 0.00 0.00
November 0.325552E+10 0.103100E+10 0.950793E+10 0.00 0.00 0.00 0.00 0.00
December 0.333844E+10 342.12 0.301650E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.758767E+11 0.519128E+12 0.975595E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.305154E+10 342.12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.121707E+11 0.122368E+12 0.301650E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.154502E+11 16995512.17 0.00 0.00 0.00 0.00 0.00 0.00
February 0.137999E+11 0.123474E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.160684E+11 0.341121E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.149844E+11 0.172376E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.160233E+11 0.303525E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.159539E+11 0.560556E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.160654E+11 0.686866E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.173825E+11 0.680956E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.164455E+11 0.461517E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.167371E+11 0.215095E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.154090E+11 0.607606E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.153812E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.189701E+12 0.313360E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.137999E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.173825E+11 0.686866E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.171620E+10 0.456303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.155011E+10 0.914176E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.171620E+10 0.156914E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.166084E+10 0.203898E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.171620E+10 0.604297E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.166084E+10 0.111029E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.171620E+10 0.167198E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.171620E+10 0.216872E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.166084E+10 0.617214E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.171620E+10 0.110074E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.166084E+10 0.151238E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.171620E+10 0.203470E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.202068E+11 0.157989E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.155011E+10 0.456303E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.171620E+10 0.216872E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.163900E+11 0.261244E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.148039E+11 0.735495E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.163900E+11 0.139600E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.158613E+11 0.190549E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.163900E+11 0.539837E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.158613E+11 0.104467E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.163900E+11 0.159193E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.163900E+11 0.206914E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.158613E+11 0.559572E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.163900E+11 0.980070E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.158613E+11 0.131243E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.163900E+11 0.174064E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.192979E+12 0.141365E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.148039E+11 0.261244E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.163900E+11 0.206914E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.167558E+10 0.972830E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.151343E+10 0.581139E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.167558E+10 0.128712E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.162153E+10 0.186146E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.167558E+10 0.522189E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.162153E+10 0.104985E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.167558E+10 0.160792E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.167558E+10 0.208082E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.162153E+10 0.552014E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.167558E+10 0.909302E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.162153E+10 0.115553E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.167558E+10 0.153835E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.197286E+11 0.132430E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.151343E+10 0.972830E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.167558E+10 0.208082E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.458725E+10 0.611647E+10 0.874801E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.498953E+10 0.311425E+10 0.288684E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.788127E+10 0.557406E+09 0.920135E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.108003E+11 30264058.54 0.335933E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.948329E+10 1173737.94 0.515670E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.125899E+11 0.00 0.101735E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.146175E+11 0.00 0.131826E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.157237E+11 0.00 0.129946E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.941927E+10 0.00 0.743874E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.816781E+10 0.380830E+09 0.358027E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.678771E+10 0.673143E+09 0.223797E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.604498E+10 0.421766E+10 540032.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.111093E+12 0.150912E+11 0.574059E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.458725E+10 0.00 540032.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.157237E+11 0.611647E+10 0.131826E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.345227E+11 0.134971E+12 0.783570E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.334650E+11 0.765772E+11 0.228936E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.467155E+11 0.168827E+11 0.680710E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.641628E+11 0.204649E+10 0.246290E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.774971E+11 0.152909E+09 0.445055E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.101941E+12 0.00 0.866327E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.111277E+12 0.00 0.105124E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.110952E+12 0.00 0.996513E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.759651E+11 0.00 0.651386E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.566034E+11 0.106453E+11 0.295152E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.396160E+11 0.282442E+11 0.160066E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.347382E+11 0.135190E+12 11358595.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.787455E+12 0.404710E+12 0.466678E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.334650E+11 0.00 11358595.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.111277E+12 0.135190E+12 0.105124E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.336373E+10 0.297115E+11 0.394535E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.305154E+10 0.180028E+11 0.189525E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.370104E+10 0.574705E+10 0.549794E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.543433E+10 0.973084E+09 0.256558E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.718289E+10 0.151919E+09 0.490399E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.107229E+11 1394288.02 0.995448E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.121707E+11 0.00 0.122368E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.117582E+11 0.00 0.113999E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.723327E+10 0.00 0.705042E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.466422E+10 0.329886E+10 0.291977E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.325552E+10 0.950793E+10 0.103100E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.333844E+10 0.301650E+11 342.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.758767E+11 0.975595E+11 0.519128E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.305154E+10 0.00 342.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.121707E+11 0.301650E+11 0.122368E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.154502E+11 0.00 16995512.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.137999E+11 0.00 0.123474E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.160684E+11 0.00 0.341121E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.149844E+11 0.00 0.172376E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.160233E+11 0.00 0.303525E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.159539E+11 0.00 0.560556E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.160654E+11 0.00 0.686866E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.173825E+11 0.00 0.680956E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.164455E+11 0.00 0.461517E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.167371E+11 0.00 0.215095E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.154090E+11 0.00 0.607606E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.153812E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.189701E+12 0.00 0.313360E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.137999E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.173825E+11 0.00 0.686866E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.171620E+10 0.00 0.573083E+10 0.00 0.116780E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.155011E+10 0.00 0.113292E+11 0.00 0.218744E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.171620E+10 0.00 0.192840E+11 0.00 0.359261E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.166084E+10 0.00 0.251324E+11 0.00 0.474268E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.171620E+10 0.00 0.767490E+10 0.00 0.163193E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.166084E+10 0.00 0.142843E+11 0.00 0.318145E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.171620E+10 0.00 0.215853E+11 0.00 0.486554E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.171620E+10 0.00 0.276023E+11 0.00 0.591511E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.166084E+10 0.00 0.784262E+10 0.00 0.167048E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.171620E+10 0.00 0.136847E+11 0.00 0.267724E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.166084E+10 0.00 0.185465E+11 0.00 0.342272E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.171620E+10 0.00 0.248935E+11 0.00 0.454654E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.202068E+11 0.00 0.197591E+12 0.00 0.396015E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.155011E+10 0.00 0.573083E+10 0.00 0.116780E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.171620E+10 0.00 0.276023E+11 0.00 0.591511E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.163900E+11 0.00 0.330972E+11 0.00 0.697287E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.148039E+11 0.00 0.914256E+11 0.00 0.178761E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.163900E+11 0.00 0.171842E+12 0.00 0.322423E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.158613E+11 0.00 0.235048E+12 0.00 0.444989E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.163900E+11 0.00 0.686786E+11 0.00 0.146949E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.158613E+11 0.00 0.134491E+12 0.00 0.300236E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.163900E+11 0.00 0.205534E+12 0.00 0.463411E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.163900E+11 0.00 0.263359E+12 0.00 0.564441E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.158613E+11 0.00 0.711936E+11 0.00 0.152364E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.163900E+11 0.00 0.122042E+12 0.00 0.240353E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.158613E+11 0.00 0.161279E+12 0.00 0.300357E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.163900E+11 0.00 0.213548E+12 0.00 0.394831E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.192979E+12 0.00 0.177154E+13 0.00 0.357884E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.148039E+11 0.00 0.330972E+11 0.00 0.697287E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.163900E+11 0.00 0.263359E+12 0.00 0.564441E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.167558E+10 0.00 0.124422E+10 0.00 0.271395E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.151343E+10 0.00 0.725074E+10 0.00 0.143935E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.167558E+10 0.00 0.158771E+11 0.00 0.300593E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.162153E+10 0.00 0.229932E+11 0.00 0.437859E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.167558E+10 0.00 0.665655E+10 0.00 0.143466E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.162153E+10 0.00 0.135297E+11 0.00 0.303123E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.167558E+10 0.00 0.207721E+11 0.00 0.469293E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.167558E+10 0.00 0.265027E+11 0.00 0.569450E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.162153E+10 0.00 0.703403E+10 0.00 0.151389E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.167558E+10 0.00 0.113471E+11 0.00 0.225405E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.162153E+10 0.00 0.142399E+11 0.00 0.268466E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.167558E+10 0.00 0.189334E+11 0.00 0.354988E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.197286E+11 0.00 0.166381E+12 0.00 0.339511E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.151343E+10 0.00 0.124422E+10 0.00 0.271395E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.167558E+10 0.00 0.265027E+11 0.00 0.569450E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.123946E+10 0.00 0.00 0.106519E+09 0.00 0.00 0.647932E+11 0.00 0.68
February 0.755767E+09 0.00 0.00 93855061.29 0.00 0.00 0.580256E+11 0.00 0.74
March 0.405346E+09 0.00 0.00 0.106041E+09 0.00 0.00 0.689186E+11 0.00 1.10
April 0.242750E+09 4792404.31 0.00 0.100552E+09 530951.96 0.00 0.517709E+11 0.00 1.23
May 0.169954E+09 73671306.38 0.00 0.101678E+09 8487299.51 0.00 0.425418E+11 0.00 1.21
June 92885291.63 0.181586E+10 0.00 70479303.77 42119845.63 0.00 0.203008E+11 0.00 0.94
July 0.116325E+09 0.230780E+10 0.00 65079678.25 52925374.56 0.00 0.970911E+10 0.00 0.82
August 0.140635E+09 0.127563E+10 0.00 94082709.16 36262062.87 0.00 0.174198E+11 0.00 1.03
September 0.186026E+09 0.286185E+09 0.00 0.109845E+09 5221371.70 0.00 0.308046E+11 0.00 1.22
October 0.339669E+09 11696356.11 0.00 0.125955E+09 0.00 0.00 0.574501E+11 0.00 1.26
November 0.588708E+09 0.00 0.00 0.120996E+09 0.00 0.00 0.728511E+11 0.00 0.98
December 0.944183E+09 0.00 0.00 0.122389E+09 0.00 0.00 0.699255E+11 0.00 0.64
                   
Annual Sum or Average 0.522171E+10 0.577563E+10 0.00 0.121747E+10 0.145547E+09 0.00 0.564511E+12 0.00 0.99
Minimum of Months 92885291.63 0.00 0.00 65079678.25 0.00 0.00 0.970911E+10 0.00 0.64
Maximum of Months 0.123946E+10 0.230780E+10 0.00 0.125955E+09 52925374.56 0.00 0.728511E+11 0.00 1.26



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.549672E+10 0.00 0.00 61815334.25 0.00 0.00 0.412518E+11 0.00 0.47
February 0.377800E+10 0.00 0.00 66969180.72 0.00 0.00 0.403212E+11 0.00 0.54
March 0.497639E+10 0.00 0.00 87743425.36 0.00 0.00 0.516452E+11 0.00 0.85
April 0.971036E+10 1698903.75 0.00 82686649.46 531093.07 0.00 0.403382E+11 0.00 1.08
May 0.396107E+10 33085366.71 0.00 78745286.32 48987988.64 0.00 0.304950E+11 0.00 0.91
June 0.489780E+10 0.850973E+09 0.00 56167043.97 0.301291E+09 0.00 0.136736E+11 0.00 0.78
July 0.443102E+10 0.131003E+10 0.00 43089303.24 0.469959E+09 0.00 0.462539E+10 0.00 0.71
August 0.622339E+10 0.824438E+09 0.00 67658835.49 0.171188E+09 0.00 0.109681E+11 0.00 0.93
September 0.379112E+10 0.254653E+09 0.00 74487285.90 25246379.33 0.00 0.194101E+11 0.00 0.84
October 0.582316E+10 1053626.75 0.00 84493764.62 2236896.96 0.00 0.377114E+11 0.00 0.86
November 0.596560E+10 0.00 0.00 84960084.97 0.00 0.00 0.505021E+11 0.00 0.72
December 0.498688E+10 0.00 0.00 87438299.15 0.00 0.00 0.500302E+11 0.00 0.49
                   
Annual Sum or Average 0.640415E+11 0.327593E+10 0.00 0.876254E+09 0.101944E+10 0.00 0.390972E+12 0.00 0.77
Minimum of Months 0.377800E+10 0.00 0.00 43089303.24 0.00 0.00 0.462539E+10 0.00 0.47
Maximum of Months 0.971036E+10 0.131003E+10 0.00 87743425.36 0.469959E+09 0.00 0.516452E+11 0.00 1.08



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.208367E+12 0.00 0.00 0.150245E+09 0.00 0.00 0.142059E+12 0.00 0.35
February 0.138413E+12 0.00 0.00 0.222418E+09 0.00 0.00 0.171280E+12 0.00 0.38
March 0.806763E+11 0.00 0.00 0.416559E+09 0.00 0.00 0.295330E+12 0.00 0.57
April 0.431504E+11 13531408.19 0.00 0.536702E+09 35441341.84 0.00 0.273833E+12 0.00 0.71
May 0.321257E+11 0.329278E+09 0.00 0.621892E+09 0.336675E+09 0.00 0.242345E+12 0.00 0.74
June 0.221942E+11 0.956973E+10 0.00 0.446992E+09 0.291588E+10 0.00 0.106557E+12 0.00 0.60
July 0.157673E+11 0.127499E+11 0.00 0.341791E+09 0.403820E+10 0.00 0.339938E+11 0.00 0.49
August 0.183775E+11 0.720024E+10 0.00 0.539214E+09 0.175603E+10 0.00 0.839874E+11 0.00 0.61
September 0.234298E+11 0.230160E+10 0.00 0.606722E+09 0.299663E+09 0.00 0.152446E+12 0.00 0.67
October 0.581770E+11 4420234.55 0.00 0.544345E+09 61951110.94 0.00 0.249348E+12 0.00 0.63
November 0.102317E+12 0.00 0.00 0.344541E+09 0.00 0.00 0.253949E+12 0.00 0.47
December 0.197634E+12 0.00 0.00 0.154787E+09 0.00 0.00 0.152807E+12 0.00 0.32
                   
Annual Sum or Average 0.940629E+12 0.321687E+11 0.00 0.492621E+10 0.944384E+10 0.00 0.215794E+13 0.00 0.55
Minimum of Months 0.157673E+11 0.00 0.00 0.150245E+09 0.00 0.00 0.339938E+11 0.00 0.32
Maximum of Months 0.208367E+12 0.127499E+11 0.00 0.621892E+09 0.403820E+10 0.00 0.295330E+12 0.00 0.74



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.266496E+11 0.00 0.00 674124.42 0.00 0.141965E+10 0.134776E+10 0.00 0.32
February 0.217123E+11 0.00 0.00 2853983.87 0.00 0.763951E+09 0.364160E+10 0.00 0.34
March 0.155388E+11 0.00 0.00 17020819.57 0.00 56487102.88 0.153535E+11 0.00 0.49
April 0.705513E+10 0.00 0.00 38942235.69 0.00 0.00 0.214462E+11 0.00 0.70
May 0.467976E+10 10358097.02 0.00 54142550.24 35496229.58 0.00 0.213382E+11 0.00 0.77
June 0.276360E+10 0.564612E+09 0.00 51113584.77 0.249319E+09 0.00 0.975561E+10 0.00 0.61
July 0.168404E+10 0.791745E+09 0.00 46085768.49 0.343839E+09 0.00 0.339928E+10 0.00 0.52
August 0.188116E+10 0.435359E+09 0.00 64170866.68 0.148723E+09 0.00 0.857955E+10 0.00 0.65
September 0.258955E+10 0.126888E+09 0.00 56797811.11 11131600.84 0.00 0.134326E+11 0.00 0.69
October 0.100380E+11 1210968.19 0.00 33568955.47 126567.34 8663490.60 0.150238E+11 0.00 0.57
November 0.195393E+11 0.00 0.00 8019418.90 0.00 0.412387E+09 0.809411E+10 0.00 0.38
December 0.265300E+11 0.00 0.00 399897.97 0.00 0.186575E+10 0.841784E+09 0.00 0.28
                   
Annual Sum or Average 0.140661E+12 0.193017E+10 0.00 0.373790E+09 0.788636E+09 0.452689E+10 0.122254E+12 0.00 0.53
Minimum of Months 0.168404E+10 0.00 0.00 399897.97 0.00 0.00 0.841784E+09 0.00 0.28
Maximum of Months 0.266496E+11 0.791745E+09 0.00 64170866.68 0.343839E+09 0.186575E+10 0.214462E+11 0.00 0.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.400094E+10 0.00 0.00 119630.29 0.00 21623705.70 0.232065E+09 0.00 0.33
February 0.291741E+10 0.00 0.00 948468.92 0.00 0.00 0.862106E+09 0.00 0.37
March 0.198714E+10 0.00 0.00 4255059.57 0.00 0.00 0.314265E+10 0.00 0.63
April 0.168499E+10 334586.40 0.00 7476364.64 49344.26 0.00 0.371583E+10 0.00 1.02
May 0.755016E+09 8722193.51 0.00 9172008.60 4722959.13 0.00 0.336224E+10 0.00 0.95
June 0.647327E+09 0.208526E+09 0.00 8899700.00 22367088.29 0.00 0.191539E+10 0.00 0.98
July 0.543294E+09 0.298169E+09 0.00 7385689.71 51619737.22 0.00 0.742942E+09 0.00 0.91
August 0.812690E+09 0.167508E+09 0.00 10730454.56 17072528.32 0.00 0.151255E+10 0.00 1.09
September 0.608404E+09 43041957.11 0.00 8823704.16 2354788.62 0.00 0.210816E+10 0.00 0.85
October 0.165043E+10 193983.86 0.00 5732797.79 281056.02 0.00 0.244546E+10 0.00 0.70
November 0.246031E+10 0.00 0.00 2421059.82 0.00 0.00 0.212379E+10 0.00 0.47
December 0.383254E+10 0.00 0.00 320649.77 0.00 0.00 0.469966E+09 0.00 0.30
                   
Annual Sum or Average 0.219005E+11 0.726495E+09 0.00 66285587.83 98467501.85 21623705.70 0.226331E+11 0.00 0.72
Minimum of Months 0.543294E+09 0.00 0.00 119630.29 0.00 0.00 0.232065E+09 0.00 0.30
Maximum of Months 0.400094E+10 0.298169E+09 0.00 10730454.56 51619737.22 21623705.70 0.371583E+10 0.00 1.09



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.322292E+10 0.00 0.00 1603022.46 0.00 40671788.33 0.125551E+10 0.00 0.55
February 0.232649E+10 0.00 0.00 2626487.39 0.00 746680.18 0.185150E+10 0.00 0.62
March 0.175415E+10 0.00 0.00 6521017.34 0.00 0.00 0.422380E+10 0.00 1.07
April 0.153570E+10 307254.29 0.00 10922291.64 26488.13 0.00 0.548861E+10 0.00 1.83
May 0.678616E+09 11027682.15 0.00 12983481.03 2983897.69 0.00 0.478291E+10 0.00 1.78
June 0.681204E+09 0.162003E+09 0.00 10812752.37 23992369.78 0.00 0.213506E+10 0.00 1.62
July 0.559516E+09 0.251917E+09 0.00 8386395.80 50660363.28 0.00 0.703025E+09 0.00 1.40
August 0.850102E+09 0.141704E+09 0.00 10826000.92 17032856.42 0.00 0.157610E+10 0.00 1.74
September 0.659387E+09 32576699.25 0.00 10602135.20 2212196.22 0.00 0.265806E+10 0.00 1.57
October 0.143783E+10 138259.85 0.00 8056068.55 273646.62 0.00 0.355507E+10 0.00 1.24
November 0.223265E+10 0.00 0.00 3902501.23 0.00 0.00 0.276315E+10 0.00 0.76
December 0.331678E+10 0.00 0.00 1632783.69 0.00 6680025.37 0.118763E+10 0.00 0.49
                   
Annual Sum or Average 0.192553E+11 0.599674E+09 0.00 88874937.63 97181818.14 48098493.88 0.321804E+11 0.00 1.22
Minimum of Months 0.559516E+09 0.00 0.00 1603022.46 0.00 0.00 0.703025E+09 0.00 0.49
Maximum of Months 0.331678E+10 0.251917E+09 0.00 12983481.03 50660363.28 40671788.33 0.548861E+10 0.00 1.83



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.203474E+10 0.00 0.00 13078636.78 0.00 87515294.58 0.750421E+10 0.00 0.87
February 0.151360E+10 0.00 0.00 13279148.44 0.00 17079321.51 0.777281E+10 0.00 1.00
March 0.145042E+10 0.00 0.00 13294158.92 0.00 0.00 0.826261E+10 0.00 1.29
April 0.168069E+10 556707.72 0.00 13175353.62 14689.97 0.00 0.613005E+10 0.00 1.54
May 0.895999E+09 13786585.56 0.00 10632315.03 4560789.10 0.00 0.372692E+10 0.00 1.10
June 0.756571E+09 0.212495E+09 0.00 8328438.07 23689964.81 0.00 0.165354E+10 0.00 0.94
July 0.566112E+09 0.341437E+09 0.00 7613327.34 54001027.45 0.00 0.713250E+09 0.00 0.93
August 0.813492E+09 0.232198E+09 0.00 13967615.70 17309866.86 0.00 0.176157E+10 0.00 1.28
September 0.466405E+09 86026696.57 0.00 18365950.99 1189718.44 0.00 0.338158E+10 0.00 1.35
October 0.106195E+10 1456376.73 0.00 23741406.66 0.00 0.00 0.790379E+10 0.00 1.60
November 0.121977E+10 0.00 0.00 19115353.93 0.00 0.00 0.107917E+11 0.00 1.25
December 0.171520E+10 0.00 0.00 15946066.86 0.00 13295731.47 0.974091E+10 0.00 0.85
                   
Annual Sum or Average 0.141749E+11 0.887956E+09 0.00 0.170538E+09 0.100766E+09 0.117890E+09 0.693429E+11 0.00 1.17
Minimum of Months 0.466405E+09 0.00 0.00 7613327.34 0.00 0.00 0.713250E+09 0.00 0.85
Maximum of Months 0.203474E+10 0.341437E+09 0.00 23741406.66 54001027.45 87515294.58 0.107917E+11 0.00 1.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.388933E+10 0.00 0.00 2604998.97 0.00 0.00 0.227761E+10 0.00 0.78
February 0.190481E+10 0.00 0.00 6108591.76 0.00 0.00 0.443164E+10 0.00 1.04
March 0.833329E+09 0.00 0.00 13308472.32 0.00 0.00 0.793782E+10 0.00 1.78
April 0.897570E+09 622673.65 0.00 21669782.94 0.00 0.00 0.820461E+10 0.00 2.74
May 0.630989E+09 21655218.95 0.00 13351968.58 3325626.61 0.00 0.441064E+10 0.00 1.87
June 0.549313E+09 0.302767E+09 0.00 12315323.49 17383971.98 0.00 0.232626E+10 0.00 1.78
July 0.423741E+09 0.417628E+09 0.00 11565478.16 42866109.71 0.00 0.118325E+10 0.00 1.73
August 0.539219E+09 0.259451E+09 0.00 18877788.15 4587498.72 0.00 0.263112E+10 0.00 2.30
September 0.480733E+09 56200360.27 0.00 13862725.47 1006714.63 0.00 0.279451E+10 0.00 1.61
October 0.101307E+10 265243.72 0.00 13897602.62 361281.37 0.00 0.526833E+10 0.00 1.72
November 0.105898E+10 0.00 0.00 10154483.48 0.00 0.00 0.691752E+10 0.00 1.32
December 0.151347E+10 0.00 0.00 8349210.00 0.00 0.00 0.600193E+10 0.00 0.87
                   
Annual Sum or Average 0.137345E+11 0.105859E+10 0.00 0.146066E+09 69531203.02 0.00 0.543852E+11 0.00 1.63
Minimum of Months 0.423741E+09 0.00 0.00 2604998.97 0.00 0.00 0.118325E+10 0.00 0.78
Maximum of Months 0.388933E+10 0.417628E+09 0.00 21669782.94 42866109.71 0.00 0.820461E+10 0.00 2.74



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.285966E+11 0.00 0.00 0.00 0.00 0.142216E+11 0.00 0.00 0.34
February 0.277150E+11 0.00 0.00 28564.91 0.00 0.809308E+10 0.198838E+09 0.00 0.35
March 0.314900E+11 0.00 0.00 5811336.58 0.00 0.106485E+10 0.537461E+10 0.00 0.46
April 0.154514E+11 2667688.95 0.00 36375429.80 4395176.20 0.00 0.167062E+11 0.00 0.62
May 0.858688E+10 84120008.38 0.00 67867452.89 27659068.74 0.00 0.229912E+11 0.00 0.76
June 0.361087E+10 0.260244E+10 0.00 70057053.68 0.197971E+09 0.00 0.142225E+11 0.00 0.79
July 0.194075E+10 0.331392E+10 0.00 60330678.75 0.402694E+09 0.00 0.558745E+10 0.00 0.69
August 0.251214E+10 0.166542E+10 0.00 84117733.75 0.170018E+09 0.00 0.114235E+11 0.00 0.77
September 0.627484E+10 0.400502E+09 0.00 65292024.53 27708027.87 0.00 0.139710E+11 0.00 0.67
October 0.209779E+11 851841.24 0.00 26858727.76 7782277.04 0.639563E+09 0.933029E+10 0.00 0.53
November 0.333053E+11 0.00 0.00 996563.45 0.00 0.327173E+10 0.178460E+10 0.00 0.39
December 0.252310E+11 0.00 0.00 0.00 0.00 0.174991E+11 0.00 0.00 0.30
                   
Annual Sum or Average 0.205693E+12 0.806992E+10 0.00 0.417736E+09 0.838228E+09 0.447899E+11 0.101590E+12 0.00 0.56
Minimum of Months 0.194075E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.30
Maximum of Months 0.333053E+11 0.331392E+10 0.00 84117733.75 0.402694E+09 0.174991E+11 0.229912E+11 0.00 0.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.341628E+11 0.00 0.00 2075890.72 0.00 0.101467E+11 0.193424E+10 0.00 0.57
February 0.302540E+11 0.00 0.00 8471101.39 0.00 0.369864E+10 0.621700E+10 0.00 0.61
March 0.219315E+11 0.00 0.00 40615663.08 0.00 0.185004E+09 0.284553E+11 0.00 0.92
April 0.856016E+10 4830393.78 0.00 0.100037E+09 3298242.55 0.00 0.502862E+11 0.00 1.58
May 0.622312E+10 0.102912E+09 0.00 0.131177E+09 24179854.51 0.00 0.453552E+11 0.00 1.72
June 0.363149E+10 0.230525E+10 0.00 0.105241E+09 0.201484E+09 0.00 0.204419E+11 0.00 1.55
July 0.197986E+10 0.370301E+10 0.00 83848281.13 0.254620E+09 0.00 0.686348E+10 0.00 1.27
August 0.249170E+10 0.170891E+10 0.00 0.113862E+09 0.151989E+09 0.00 0.164373E+11 0.00 1.52
September 0.535759E+10 0.334036E+09 0.00 0.100851E+09 26405078.16 0.00 0.243074E+11 0.00 1.48
October 0.156438E+11 1560865.16 0.00 62859277.45 8206433.19 0.488907E+09 0.269753E+11 0.00 1.11
November 0.319084E+11 0.00 0.00 13061507.37 0.00 0.105591E+10 0.106158E+11 0.00 0.68
December 0.360239E+11 0.00 0.00 713306.96 0.00 0.922379E+10 0.912846E+09 0.00 0.51
                   
Annual Sum or Average 0.198168E+12 0.816052E+10 0.00 0.762813E+09 0.670183E+09 0.247989E+11 0.238802E+12 0.00 1.13
Minimum of Months 0.197986E+10 0.00 0.00 713306.96 0.00 0.00 0.912846E+09 0.00 0.51
Maximum of Months 0.360239E+11 0.370301E+10 0.00 0.131177E+09 0.254620E+09 0.101467E+11 0.502862E+11 0.00 1.72



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.195684E+11 0.00 0.00 0.136286E+09 0.00 0.380692E+10 0.683135E+11 0.00 0.86
February 0.144120E+11 0.00 0.00 0.131573E+09 0.00 0.189693E+10 0.704141E+11 0.00 0.95
March 0.145546E+11 0.00 0.00 0.119943E+09 0.00 99705143.38 0.682916E+11 0.00 1.13
April 0.104141E+11 8755437.84 0.00 0.107479E+09 2355514.23 0.00 0.483040E+11 0.00 1.20
May 0.848610E+10 0.149861E+09 0.00 90986443.90 22861425.47 0.00 0.302148E+11 0.00 0.96
June 0.438022E+10 0.263335E+10 0.00 67086612.19 0.208517E+09 0.00 0.128269E+11 0.00 0.77
July 0.186234E+10 0.386493E+10 0.00 64704851.39 0.403440E+09 0.00 0.557866E+10 0.00 0.73
August 0.214149E+10 0.256228E+10 0.00 0.123254E+09 0.127878E+09 0.00 0.148014E+11 0.00 1.00
September 0.332227E+10 0.916847E+09 0.00 0.179364E+09 9285172.35 0.00 0.296024E+11 0.00 1.25
October 0.839022E+10 25514740.12 0.00 0.243766E+09 68200.44 0.210250E+09 0.718913E+11 0.00 1.48
November 0.119471E+11 0.00 0.00 0.189069E+09 0.00 0.127393E+09 0.960197E+11 0.00 1.14
December 0.171117E+11 0.00 0.00 0.143299E+09 0.00 0.356727E+10 0.824300E+11 0.00 0.79
                   
Annual Sum or Average 0.116590E+12 0.101615E+11 0.00 0.159681E+10 0.774406E+09 0.970847E+10 0.598688E+12 0.00 1.02
Minimum of Months 0.186234E+10 0.00 0.00 64704851.39 0.00 0.00 0.557866E+10 0.00 0.73
Maximum of Months 0.195684E+11 0.386493E+10 0.00 0.243766E+09 0.403440E+09 0.380692E+10 0.960197E+11 0.00 1.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.358285E+11 0.00 0.00 7999920.73 0.00 0.805778E+10 0.672606E+10 0.00 0.63
February 0.297815E+11 0.00 0.00 18672425.29 0.00 0.377234E+10 0.126009E+11 0.00 0.73
March 0.292331E+11 0.00 0.00 37739422.54 0.00 0.231949E+09 0.233030E+11 0.00 1.06
April 0.139824E+11 7491800.71 0.00 90110816.40 2866349.67 0.00 0.318530E+11 0.00 1.47
May 0.906920E+10 0.211317E+09 0.00 88529395.37 4851331.17 0.00 0.274971E+11 0.00 1.43
June 0.456009E+10 0.345019E+10 0.00 71209186.93 0.142342E+09 0.00 0.121150E+11 0.00 1.24
July 0.182618E+10 0.397326E+10 0.00 58956988.56 0.367965E+09 0.00 0.518895E+10 0.00 1.06
August 0.220317E+10 0.211654E+10 0.00 96532699.88 95843245.38 0.00 0.120950E+11 0.00 1.28
September 0.532234E+10 0.519533E+09 0.00 95145242.42 13009945.81 0.00 0.173710E+11 0.00 1.19
October 0.193292E+11 12496058.28 0.00 64154555.43 2649588.22 0.246134E+09 0.220332E+11 0.00 1.15
November 0.333753E+11 0.00 0.00 19081377.99 0.00 0.495311E+09 0.154779E+11 0.00 0.80
December 0.358693E+11 0.00 0.00 7751414.55 0.00 0.777863E+10 0.676794E+10 0.00 0.56
                   
Annual Sum or Average 0.220380E+12 0.102908E+11 0.00 0.655883E+09 0.629528E+09 0.205821E+11 0.193029E+12 0.00 1.05
Minimum of Months 0.182618E+10 0.00 0.00 7751414.55 0.00 0.00 0.518895E+10 0.00 0.56
Maximum of Months 0.358693E+11 0.397326E+10 0.00 96532699.88 0.367965E+09 0.805778E+10 0.318530E+11 0.00 1.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.115544E+10 0.00 0.00 0.00 0.00 0.279211E+10 0.00 0.00 0.33
February 0.158230E+10 0.00 0.00 0.00 0.00 0.181306E+10 0.00 0.00 0.35
March 0.280112E+10 0.00 0.00 190371.06 0.00 0.606086E+09 0.205664E+09 0.00 0.44
April 0.168092E+10 0.00 0.00 3048270.57 0.00 0.116402E+09 0.131307E+10 0.00 0.64
May 0.101914E+10 2949546.16 0.00 6404755.12 3754379.42 9189632.88 0.205972E+10 0.00 0.79
June 0.431519E+09 0.150195E+09 0.00 8716535.89 16235275.54 0.00 0.132336E+10 0.00 0.78
July 0.193349E+09 0.191251E+09 0.00 8486328.65 36623560.57 0.00 0.584797E+09 0.00 0.71
August 0.307672E+09 96741211.71 0.00 10237408.80 12734596.15 0.00 0.116083E+10 0.00 0.80
September 0.657907E+09 20204226.87 0.00 6633883.10 1556956.80 0.00 0.128981E+10 0.00 0.69
October 0.191124E+10 164719.22 0.00 2125867.69 15856.43 0.321586E+09 0.618332E+09 0.00 0.52
November 0.236269E+10 0.00 0.00 0.00 0.00 0.111922E+10 0.00 0.00 0.37
December 0.799224E+09 0.00 0.00 0.00 0.00 0.314622E+10 0.00 0.00 0.30
                   
Annual Sum or Average 0.149025E+11 0.461506E+09 0.00 45843420.89 70920624.91 0.992388E+10 0.855559E+10 0.00 0.56
Minimum of Months 0.193349E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.30
Maximum of Months 0.280112E+10 0.191251E+09 0.00 10237408.80 36623560.57 0.314622E+10 0.205972E+10 0.00 0.80



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.220494E+10 0.00 0.00 0.00 0.00 0.177972E+10 0.00 0.00 0.53
February 0.239035E+10 0.00 0.00 273269.17 0.00 0.869219E+09 0.271660E+09 0.00 0.56
March 0.214062E+10 0.00 0.00 2618262.52 0.00 0.293759E+09 0.196734E+10 0.00 0.84
April 0.825660E+09 0.00 0.00 8937852.71 0.00 25874119.62 0.461504E+10 0.00 1.58
May 0.572889E+09 5009477.20 0.00 13072197.24 2795707.36 2347719.32 0.447578E+10 0.00 1.79
June 0.354376E+09 0.137075E+09 0.00 12636636.92 15771095.56 0.00 0.203847E+10 0.00 1.58
July 0.191534E+09 0.233804E+09 0.00 11140182.57 22714544.60 0.00 0.731550E+09 0.00 1.32
August 0.250481E+09 0.101828E+09 0.00 14007770.63 12935691.60 0.00 0.175095E+10 0.00 1.62
September 0.530409E+09 16866799.67 0.00 10391264.52 1365096.49 0.00 0.234674E+10 0.00 1.56
October 0.144941E+10 153162.61 0.00 5149506.54 17019.29 0.196273E+09 0.212464E+10 0.00 1.06
November 0.289115E+10 0.00 0.00 379408.60 0.00 0.454952E+09 0.375134E+09 0.00 0.62
December 0.225360E+10 0.00 0.00 0.00 0.00 0.170845E+10 0.00 0.00 0.47
                   
Annual Sum or Average 0.160554E+11 0.494736E+09 0.00 78606351.42 55599154.89 0.533060E+10 0.206973E+11 0.00 1.13
Minimum of Months 0.191534E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.47
Maximum of Months 0.289115E+10 0.233804E+09 0.00 14007770.63 22714544.60 0.177972E+10 0.461504E+10 0.00 1.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.163684E+10 0.00 0.00 7750390.73 0.00 0.102416E+10 0.475210E+10 0.00 0.73
February 0.142091E+10 0.00 0.00 8769864.75 0.00 0.533983E+09 0.530456E+10 0.00 0.83
March 0.155776E+10 0.00 0.00 8845149.82 0.00 0.307576E+09 0.582039E+10 0.00 1.04
April 0.115315E+10 0.00 0.00 9790537.05 0.00 59869251.17 0.466006E+10 0.00 1.24
May 0.102131E+10 5431855.53 0.00 9099745.04 3665127.72 13524109.63 0.295649E+10 0.00 1.03
June 0.556056E+09 0.148164E+09 0.00 8593604.99 19302139.32 0.00 0.125866E+10 0.00 0.79
July 0.217232E+09 0.216324E+09 0.00 9282296.10 40893402.44 0.00 0.592306E+09 0.00 0.75
August 0.291971E+09 0.140255E+09 0.00 15281203.67 12603601.11 0.00 0.159515E+10 0.00 1.05
September 0.423402E+09 43807461.05 0.00 18991443.20 792639.51 0.00 0.303491E+10 0.00 1.36
October 0.872286E+09 397895.08 0.00 21392343.76 3744.49 0.170153E+09 0.666792E+10 0.00 1.50
November 0.125285E+10 0.00 0.00 12032769.81 0.00 0.299382E+09 0.741849E+10 0.00 0.99
December 0.169815E+10 0.00 0.00 8796088.09 0.00 0.758322E+09 0.560020E+10 0.00 0.64
                   
Annual Sum or Average 0.121019E+11 0.554381E+09 0.00 0.138625E+09 77260654.59 0.316696E+10 0.496612E+11 0.00 0.99
Minimum of Months 0.217232E+09 0.00 0.00 7750390.73 0.00 0.00 0.592306E+09 0.00 0.64
Maximum of Months 0.169815E+10 0.216324E+09 0.00 21392343.76 40893402.44 0.102416E+10 0.741849E+10 0.00 1.50



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.242276E+10 0.00 0.00 456522.43 0.00 0.168797E+10 0.455160E+09 0.00 0.61
February 0.240119E+10 0.00 0.00 1353357.04 0.00 0.942924E+09 0.981183E+09 0.00 0.72
March 0.289053E+10 0.00 0.00 2918515.67 0.00 0.354298E+09 0.198485E+10 0.00 1.05
April 0.167016E+10 0.00 0.00 8361949.91 0.00 17218406.32 0.300285E+10 0.00 1.57
May 0.112527E+10 7629592.37 0.00 9383614.80 3419016.79 5040240.46 0.269198E+10 0.00 1.55
June 0.532687E+09 0.187214E+09 0.00 9454953.63 14082974.11 0.00 0.123109E+10 0.00 1.26
July 0.209975E+09 0.215463E+09 0.00 8529101.47 37106754.35 0.00 0.550523E+09 0.00 1.08
August 0.285243E+09 0.113435E+09 0.00 11811968.19 11192821.65 0.00 0.127468E+10 0.00 1.34
September 0.703879E+09 25534714.60 0.00 10143001.73 852409.92 0.00 0.158284E+10 0.00 1.29
October 0.195485E+10 284635.50 0.00 5778160.46 613.40 0.209551E+09 0.187293E+10 0.00 1.18
November 0.286896E+10 0.00 0.00 1300473.96 0.00 0.543075E+09 0.111178E+10 0.00 0.77
December 0.238895E+10 0.00 0.00 393768.78 0.00 0.166488E+10 0.446431E+09 0.00 0.54
                   
Annual Sum or Average 0.194545E+11 0.549561E+09 0.00 69885388.05 66654590.22 0.542496E+10 0.171863E+11 0.00 1.08
Minimum of Months 0.209975E+09 0.00 0.00 393768.78 0.00 0.00 0.446431E+09 0.00 0.54
Maximum of Months 0.289053E+10 0.215463E+09 0.00 11811968.19 37106754.35 0.168797E+10 0.300285E+10 0.00 1.57



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 3375828.00 0.00 0.00 0.543772E+09 0.00 0.28
February 0.00 0.00 0.00 8067422.50 0.00 0.00 0.454144E+09 0.00 0.28
March 0.00 0.00 0.00 14324602.97 0.00 0.00 0.427640E+09 0.00 0.30
April 0.00 0.00 0.00 17331306.61 0.00 0.00 0.289639E+09 0.00 0.29
May 0.00 479648.05 0.00 3962266.18 0.00 0.00 0.214510E+09 0.00 0.29
June 0.00 26705883.17 0.00 5052281.98 0.00 0.00 48621112.36 0.00 0.30
July 0.00 0.149320E+09 0.00 204996.57 0.00 0.00 196401.98 0.00 0.28
August 0.00 0.120727E+09 0.00 1079992.66 0.00 0.00 654174.07 0.00 0.30
September 0.00 18510473.24 0.00 2632473.73 0.00 0.00 55695917.43 0.00 0.29
October 0.00 4414026.04 0.00 7728326.09 0.00 0.00 0.274121E+09 0.00 0.28
November 0.00 0.00 0.00 13014527.12 0.00 0.00 0.423863E+09 0.00 0.28
December 0.00 0.00 0.00 18992947.31 0.00 0.00 0.546592E+09 0.00 0.28
                   
Annual Sum or Average 0.00 0.320157E+09 0.00 95766971.72 0.00 0.00 0.327945E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 204996.57 0.00 0.00 196401.98 0.00 0.28
Maximum of Months 0.00 0.149320E+09 0.00 18992947.31 0.00 0.00 0.546592E+09 0.00 0.30



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 66002704.06 0.00 0.00 19072425.49 0.00 0.00 0.538565E+10 0.00 0.28
February 0.00 0.00 0.00 66303317.22 0.00 0.00 0.455593E+10 0.00 0.28
March 0.00 0.00 0.00 0.128573E+09 0.00 0.00 0.428994E+10 0.00 0.30
April 0.00 0.00 0.00 0.162763E+09 0.00 0.00 0.290612E+10 0.00 0.29
May 0.00 4329856.39 0.00 35341719.42 0.00 0.00 0.215389E+10 0.00 0.29
June 0.00 0.265006E+09 0.00 47585894.81 0.00 0.00 0.490115E+09 0.00 0.30
July 0.00 0.148839E+10 0.00 1946275.73 0.00 0.00 1885121.91 0.00 0.28
August 0.00 0.120420E+10 0.00 10473010.69 0.00 0.00 6807104.29 0.00 0.30
September 0.00 0.175516E+09 0.00 24103997.70 0.00 0.00 0.567782E+09 0.00 0.29
October 0.00 42790199.47 0.00 68904573.10 0.00 0.00 0.275021E+10 0.00 0.28
November 0.00 0.00 0.00 0.114825E+09 0.00 0.00 0.425343E+10 0.00 0.28
December 0.00 0.00 0.00 0.165882E+09 0.00 0.00 0.548937E+10 0.00 0.28
                   
Annual Sum or Average 66002704.06 0.318023E+10 0.00 0.845774E+09 0.00 0.00 0.328511E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 1946275.73 0.00 0.00 1885121.91 0.00 0.28
Maximum of Months 66002704.06 0.148839E+10 0.00 0.165882E+09 0.00 0.00 0.548937E+10 0.00 0.30



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.213739E+09 0.00 0.00 883962.68 0.00 0.00 0.328261E+09 0.00 0.28
February 0.00 0.00 0.00 5538465.04 0.00 0.00 0.456803E+09 0.00 0.28
March 0.00 0.00 0.00 12015351.73 0.00 0.00 0.429961E+09 0.00 0.30
April 0.00 0.00 0.00 15971310.84 0.00 0.00 0.290949E+09 0.00 0.29
May 0.00 436878.58 0.00 3420529.14 0.00 0.00 0.215755E+09 0.00 0.29
June 0.00 26535709.77 0.00 4764402.76 0.00 0.00 49143220.56 0.00 0.30
July 0.00 0.148861E+09 0.00 197608.02 0.00 0.00 194411.36 0.00 0.28
August 0.00 0.120610E+09 0.00 1045603.85 0.00 0.00 674953.78 0.00 0.30
September 0.00 17548326.18 0.00 2355460.48 0.00 0.00 57024557.88 0.00 0.29
October 0.00 4256309.24 0.00 6365311.92 0.00 0.00 0.275782E+09 0.00 0.28
November 0.00 0.00 0.00 10417928.92 0.00 0.00 0.426531E+09 0.00 0.28
December 0.00 0.00 0.00 15198203.69 0.00 0.00 0.550361E+09 0.00 0.28
                   
Annual Sum or Average 0.213739E+09 0.318249E+09 0.00 78174139.08 0.00 0.00 0.308144E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 197608.02 0.00 0.00 194411.36 0.00 0.28
Maximum of Months 0.213739E+09 0.148861E+09 0.00 15971310.84 0.00 0.00 0.550361E+09 0.00 0.30



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:05:12

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.482296E+12 0.539179E+10 0.00 0.170988E+13 0.121045E+12
February 0.586122E+12 0.499280E+10 0.00 0.159677E+13 0.197331E+12
March 0.755113E+12 0.483964E+10 0.00 0.181982E+13 0.347596E+12
April 0.924086E+12 0.351128E+10 0.00 0.172452E+13 0.680397E+12
May 0.981086E+12 0.220722E+10 0.00 0.139938E+13 0.785210E+12
June 0.916950E+12 0.107798E+10 0.00 0.750123E+12 0.166239E+13
July 0.941478E+12 0.439537E+09 0.00 0.274198E+12 0.195386E+13
August 0.925106E+12 0.859417E+09 0.00 0.613562E+12 0.201783E+13
September 0.757545E+12 0.146187E+10 0.00 0.119125E+13 0.125491E+13
October 0.628012E+12 0.269358E+10 0.00 0.170541E+13 0.687530E+12
November 0.511015E+12 0.443021E+10 0.00 0.186514E+13 0.255013E+12
December 0.452333E+12 0.486679E+10 0.00 0.175529E+13 0.336086E+12
           
Annual Sum or Average 0.886114E+13 0.367721E+11 0.00 0.164054E+14 0.102992E+14
Minimum of Months 0.452333E+12 0.439537E+09 0.00 0.274198E+12 0.121045E+12
Maximum of Months 0.981086E+12 0.539179E+10 0.00 0.186514E+13 0.201783E+13