Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:06
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2023-10-16 09:07:05
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 36417.38 | 786.21 | 786.21 |
Net Site Energy | 36417.38 | 786.21 | 786.21 |
Total Source Energy | 98978.91 | 2136.83 | 2136.83 |
Net Source Energy | 98978.91 | 2136.83 | 2136.83 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3964.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7226.18 | 0.00 | 0.00 |
Interior Lighting | 2019.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 317.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3333.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1482.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1389.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1351.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17602.68 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 128.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 527.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28664.05 | 527.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7226.18 | 0.00 | 19882.85 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3964.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7226.18 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2019.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 317.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ComputerHVAC | 1424.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 1482.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 1389.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1351.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17602.68 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 128.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 527.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3964.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7226.18 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2019.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 317.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 3333.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 1482.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1389.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1351.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17602.68 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 128.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 527.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 176.80 | 11.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.00 | 0.00 | 0.43 |
Other | 391.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 618.82 | 11.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.00 | 0.00 | 0.43 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 176.80 | 11.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.00 | 0.00 | 0.43 |
Other | 391.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 618.82 | 11.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.00 | 0.00 | 0.43 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 28664.047 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 28664.047 | 100.00 |
Total On-Site and Utility Electric Sources | 28664.047 | 100.00 |
Total Electricity End Uses | 28664.047 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 6996.93 | 100.00 |
Air to Air Heat Recovery for Heating | 0.00 | 0.00 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 6996.93 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 19882.85 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 19882.85 | 100.00 |
Total Water End Uses | 19882.85 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 353.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionDistrictHeatingCoolingMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:06 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.8895 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.8895 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 5.9168 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 5.9168 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.8895 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8895 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.8895 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8895 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.8895 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.9168 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.9168 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.8190 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
Time of Peak | 09-AUG-07:49 | 29-DEC-12:00 | - | - | - | - | - | - | - | - | 14-AUG-13:00 | 31-OCT-23:30 | 21-MAR-12:00 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 0.00 |
Cooling | 296585.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370785.23 | 0.00 | 0.00 |
Interior Lighting | 171235.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 188981.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 112132.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 68102.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 58053.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 60220.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1679076.92 | 60220.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370785.23 | 14.83 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 296585.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370785.23 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 171235.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3372.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ComputerHVAC | 72130.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLift | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 112132.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 68102.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 58053.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 60220.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12557.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7628.44 | 0.00 |
Interior Lighting | 6394.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1006.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10555.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4694.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4401.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 4281.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 406.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 571.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 90779.04 | 571.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7628.44 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 271.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.69 | 0.00 |
Interior Lighting | 138.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 101.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 95.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 92.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 12.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1959.81 | 12.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.69 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 271.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.69 | 0.00 |
Interior Lighting | 138.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 21.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 101.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 95.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 92.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 12.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1959.81 | 12.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.69 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.02 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.458172 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.35 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.443642 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.27 | 0.360839 | 0.353000 | 1.86 | 0.962236 | 0.500000 | 0.001056 | 0.000164 | 1.86 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 49.21 | 0.386491 | 0.369000 | 18.16 | 1.00 | 0.500000 | 0.000986 | 0.001711 | 18.16 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.07 | 0.375495 | 0.369000 | 1.87 | 1.00 | 0.500000 | 0.001015 | 0.000269 | 1.87 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.890217 | 0.268272 | 0.263000 | 0.234127 | 0.715393 | 0.500000 | 0.001420 | 0.000021 | 0.234127 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.843920 | 0.182369 | 0.200000 | 0.168784 | 0.486318 | 0.500000 | 0.002089 | 0.000015 | 0.168784 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.870691 | 0.274294 | 0.269000 | 0.234216 | 0.731452 | 0.500000 | 0.001389 | 0.000021 | 0.234216 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.13 | 0.136346 | 0.200000 | 0.225756 | 0.363590 | 0.500000 | 0.002794 | 0.000020 | 0.225756 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.18 | 0.292030 | 0.279000 | 2.28 | 0.778748 | 0.500000 | 0.001305 | 0.000317 | 2.28 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 8.59 | 0.179089 | 0.200000 | 1.72 | 0.477570 | 0.500000 | 0.002127 | 0.000231 | 1.72 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 7.94 | 0.300884 | 0.287000 | 2.28 | 0.802357 | 0.500000 | 0.001266 | 0.000325 | 2.28 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 9.34 | 0.164778 | 0.200000 | 1.87 | 0.439408 | 0.500000 | 0.002312 | 0.000170 | 1.87 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.972895 | 0.245474 | 0.241000 | 0.234468 | 0.654598 | 0.500000 | 0.001552 | 0.000043 | 0.234468 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.883735 | 0.174153 | 0.200000 | 0.176747 | 0.464408 | 0.500000 | 0.002188 | 0.000031 | 0.176747 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.944632 | 0.252824 | 0.249000 | 0.235213 | 0.674197 | 0.500000 | 0.001507 | 0.000044 | 0.235213 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.04 | 0.148265 | 0.200000 | 0.207608 | 0.395374 | 0.500000 | 0.002570 | 0.000026 | 0.207608 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18726.38 | 0.000164 | 377.51 |
CORE_MID VAV BOX REHEAT COIL | 195577.92 | 0.001711 | 3970.04 |
CORE_TOP VAV BOX REHEAT COIL | 30801.10 | 0.000269 | 662.62 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 2356.26 | 0.000021 | 47.50 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 1698.65 | 0.000015 | 34.24 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 2357.15 | 0.000021 | 47.52 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2272.01 | 0.000020 | 45.80 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 36239.07 | 0.000317 | 774.74 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 26436.50 | 0.000231 | 562.22 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 37182.49 | 0.000325 | 798.59 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 19456.84 | 0.000170 | 393.58 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 4928.44 | 0.000043 | 111.41 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 3489.66 | 0.000031 | 77.77 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 5041.43 | 0.000044 | 114.49 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 3008.22 | 0.000026 | 63.39 |
VAV_BOT WITH REHEAT HEATING COIL | 39579.96 | 0.000346 | 664.78 |
VAV_MID WITH REHEAT HEATING COIL | 365450.50 | 0.003197 | 6138.06 |
VAV_TOP WITH REHEAT HEATING COIL | 40128.59 | 0.000351 | 673.99 |
CAV_BAS HEATING COIL | 213658.42 | 0.001869 | 5046.89 |
Design Size Maximum Heating Air Flow Rate [m3/s] | Design Size Maximum Cooling Air Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT | 0.338402 | 21.25 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 4.50 | 2.72 | 9.00 | 2.72 | 8.52 | 8.52 | 0.300000 | 0.319585 | 8.52 |
VAV_MID WITH REHEAT | 41.63 | 26.31 | 83.26 | 26.31 | 78.69 | 78.69 | 0.300000 | 0.334307 | 78.69 |
VAV_TOP WITH REHEAT | 4.45 | 2.72 | 8.90 | 2.72 | 8.64 | 8.64 | 0.300000 | 0.315166 | 8.64 |
CAV_BAS | 5.02 | 5.02 | 5.02 | 5.02 | 5.02 | 5.02 | 1.00 | 1.00 | 5.02 |
AIRLOOP DATACENTER BOT | 0.458172 | 0.458172 | 0.458172 | 0.458172 | 0.458172 | 0.458172 | 1.00 | 1.00 | 0.458172 |
AIRLOOP DATACENTER MID | 4.35 | 4.35 | 4.35 | 4.35 | 4.35 | 4.35 | 1.00 | 1.00 | 4.35 |
AIRLOOP DATACENTER TOP | 0.443642 | 0.443642 | 0.443642 | 0.443642 | 0.443642 | 0.443642 | 1.00 | 1.00 | 0.443642 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.52 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 78.69 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.64 | |
CAV_BAS_OA_CONTROLLER | 5.02 | 1.20 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.458172 | 0.015633 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.35 | 0.156328 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.443642 | 0.015633 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 27.56 | 6.67 | 11.05 | 0.011532 | 0.008500 | 252185.36 | 0.010729 | 8.52 |
VAV_MID WITH REHEAT COOLING COIL | 28.04 | 6.67 | 11.05 | 0.011940 | 0.008500 | 2473928.04 | 0.105247 | 78.69 |
VAV_TOP WITH REHEAT COOLING COIL | 27.29 | 6.67 | 11.05 | 0.011338 | 0.008500 | 247707.56 | 0.010538 | 8.64 |
CAV_BAS COOLING COIL | 26.41 | 6.67 | 11.43 | 0.011148 | 0.008500 | 133170.82 | 0.005665 | 5.02 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.52 |
VAV_MID WITH REHEAT FAN | 78.69 |
VAV_TOP WITH REHEAT FAN | 8.64 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.010729 | 0.000044 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000346 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.105247 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.003197 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.010538 | 0.000045 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000351 | |
CAV_BAS_COOLC_CONTROLLER | 0.005665 | 0.000084 |
CAV_BAS_HEATC_CONTROLLER | 0.001869 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.02 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.458172 | 9423.91 | 6739.71 | 0.000231 |
AIRLOOP DATACENTER MID COOLING COIL | 4.35 | 89795.39 | 64114.50 | 0.002199 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.443642 | 9140.98 | 6531.36 | 0.000224 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.458172 | 0.458172 | 0.458172 | 0.458172 | 9423.91 | 9423.91 | 376.25 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.35 | 4.35 | 4.35 | 4.35 | 89795.39 | 89795.39 | 3762.49 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.443642 | 0.443642 | 0.443642 | 0.443642 | 9140.98 | 9140.98 | 376.25 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.458172 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.35 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.443642 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT HEATING COIL | 0.458172 | 9423.91 | 0.000231 |
AIRLOOP DATACENTER MID HEATING COIL | 4.35 | 89795.39 | 0.002199 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.443642 | 9140.98 | 0.000224 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 376.25 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 3762.49 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 376.25 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.132179 | 26967.44 | |
HEATSYS1 PUMP | 0.009172 | 2734.79 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.132179 | 15.86 |
HEATSYS1 | 0.009172 | 1.10 |
COOLSYS1_SUPPLY | 0.132179 | 15.86 |
SINGLE WATER PLANT LOOP | 0.002654 | 0.318448 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.132179 | 0.132179 | 554819.96 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1048389.59 | 1048389.59 | 0.009172 |
CENTRAL BOILER | 109311.18 | 109311.18 | 0.002654 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.132179 | 18670.47 |
PLANT CIRC PUMP | 0.002654 | 670.13 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.132179 | 0.066585 | 1568992.41 | 1576441.04 | 0.078012 |
COOLSYS1 CHILLER2 | 0.132179 | 0.066585 | 1568992.41 | 1576441.04 | 0.078012 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.002654 | 35644.39 | 21601.32 | 17822.20 | 1996.20 | 5877.22 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.156024 | 18.72 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.156024 | 46525.91 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 60.01 | 1870406.49 | 12.00 | 233800.81 |
TOWERWATERSYS COOLTOWER 2 | 60.01 | 1870406.49 | 12.00 | 233800.81 |
Design Water Flow Rate [m3/s] Equipment # 45 | |
WSHPPLANT OPERATION SCHEME | 0.081030 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.889 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.731 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.889 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.313 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16369.361 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16369.361 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4615.459 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4615.459 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.743 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.656 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 2.135 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4064 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4365 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3009 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
47 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
48 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
49 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
50 | 9 | 0.76055735E-15 | 0.55973061E-16 | -0.11090261E-09 | -0.43371185E-17 |
51 | 8 | 0.16390423E-07 | 0.22068143E-12 | 0.31740643E-03 | -0.18636477E-09 |
52 | 7 | -0.10429999E-01 | 0.12271718E-07 | -0.20474149E-01 | 0.11859286E-03 |
53 | 6 | 0.35611320 | 0.43955117E-05 | 0.42991281 | -0.41673803E-02 |
54 | 5 | -4.7098961 | 0.16827687E-03 | -4.1162358 | 0.57223947E-01 |
55 | 4 | 30.875684 | 0.14076848E-02 | 20.167480 | -0.39388153 |
56 | 3 | -106.69740 | 0.31291265E-02 | -53.106522 | 1.4497707 |
57 | 2 | 192.63914 | 0.17911574E-02 | 75.570394 | -2.8293896 |
58 | 1 | -169.50392 | 0.19431750E-03 | -54.592911 | 2.7164834 |
59 | 0 | 57.057407 | 0.11257899E-05 | 15.674734 | |
60 | 9 | 0.11474244E-14 | 0.54197419E-16 | -0.11508650E-09 | -0.49945851E-17 |
61 | 8 | 0.16984416E-07 | 0.21156325E-12 | 0.32425024E-03 | -0.19311866E-09 |
62 | 7 | -0.10636353E-01 | 0.11664670E-07 | -0.20772028E-01 | 0.12093918E-03 |
63 | 6 | 0.36172330 | 0.41637772E-05 | 0.43474562 | -0.42335086E-02 |
64 | 5 | -4.7646824 | 0.15893927E-03 | -4.1535939 | 0.57903236E-01 |
65 | 4 | 31.118254 | 0.13261305E-02 | 20.314042 | -0.39710182 |
66 | 3 | -107.21418 | 0.29411649E-02 | -53.396504 | 1.4572354 |
67 | 2 | 193.15212 | 0.16802168E-02 | 75.835339 | -2.8375342 |
68 | 1 | -169.69371 | 0.18194848E-03 | -54.668081 | 2.7198097 |
69 | 0 | 57.057407 | 0.10520719E-05 | 15.660794 | |
70 | 9 | 0.66246833E-15 | 0.57738042E-16 | -0.92036509E-10 | -0.27018983E-17 |
71 | 8 | 0.13701644E-07 | 0.25726543E-12 | 0.28527343E-03 | -0.15579243E-09 |
72 | 7 | -0.94571194E-02 | 0.14940887E-07 | -0.19068097E-01 | 0.10753086E-03 |
73 | 6 | 0.32965778 | 0.54453531E-05 | 0.40701455 | -0.38555430E-02 |
74 | 5 | -4.4514676 | 0.21157254E-03 | -3.9387765 | 0.54019785E-01 |
75 | 4 | 29.731016 | 0.17930056E-02 | 19.470280 | -0.37868589 |
76 | 3 | -104.25747 | 0.40308508E-02 | -51.726693 | 1.4145289 |
77 | 2 | 190.21562 | 0.23301583E-02 | 74.311741 | -2.7909129 |
78 | 1 | -168.60668 | 0.25508611E-03 | -54.239505 | 2.7007581 |
79 | 0 | 57.057407 | 0.14924561E-05 | 15.743350 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.5037_SHGC_EAST_0.23 | 35 | 1 | VerySmooth | 2.864 | 2.864 | 1.000 | 0.231 | ||
2 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 36 | 1 | VerySmooth | 2.864 | 2.864 | 1.000 | 0.231 | ||
3 | WINDOW_U_0.5037_SHGC_WEST_0.23 | 37 | 1 | VerySmooth | 2.864 | 2.864 | 1.000 | 0.231 | ||
4 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 38 | 1 | VerySmooth | 2.864 | 2.864 | 1.000 | 0.231 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.92411E-002 | 0.14129 | 0.63052 | 0.63052 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10752 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.92411E-002 | 0.14129 | 0.63052 | 0.63052 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10752 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.92411E-002 | 0.14129 | 0.63052 | 0.63052 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10752 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.92411E-002 | 0.14129 | 0.63052 | 0.63052 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10752 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2.856E-002 | 9.114E-005 | 1.371E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.384E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2.856E-002 | 9.114E-005 | 1.371E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.384E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 4.231E-002 | 1.187E-005 | 1.424E-004 | 3.506E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 4.231E-002 | 1.187E-005 | 1.424E-004 | 3.506E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 4.231E-002 | 1.187E-005 | 1.096E-005 | 3.506E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9448E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9458E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9661E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9670E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6855E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6861E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1459E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1463E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9695E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.0390E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9866E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.0456E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7001E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7421E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1575E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1867E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7317E-002 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9152E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9307E-002 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8772E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.2669E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4923E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.3959E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.3815E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9689E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.0360E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9859E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.0420E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6993E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7390E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1578E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1876E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9447E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9457E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9660E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9669E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6854E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6860E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1458E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1463E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1823E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2512E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.0100E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.0735E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 1.8889E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9300E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 1.9611E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9812E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.3612E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.1766E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1020E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.0097E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1823E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 8.7659E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.4646E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.1889E-003 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1708E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2133E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 1.9961E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.0276E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 1.8772E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8896E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 1.9612E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9816E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0783E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0793E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.4301E-004 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.4380E-004 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 8.1756E-004 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.1801E-004 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1459E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1463E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1008E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1583E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.6089E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0056E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 8.2878E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.5384E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1578E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1876E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6622E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.9947E-003 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3279E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.0280E-003 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1913E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.6699E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3959E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.3789E-003 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1008E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1575E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.6107E-004 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0057E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 8.2944E-004 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.5594E-004 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1576E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1867E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0783E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0793E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.4298E-004 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.4378E-004 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 8.1753E-004 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.1802E-004 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1459E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1463E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.2574E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2995E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.0974E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1288E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 1.9689E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9816E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 1.9612E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9816E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.5270E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2357E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.2928E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.0769E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3645E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 9.4189E-003 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.4646E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 9.1889E-003 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.2694E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3414E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1119E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1789E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 1.9807E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0232E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 1.9611E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9812E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.9723E-002 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.7424E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.0952E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.7144E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.5897E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.2217E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 2.7727E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.3412E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 2.7521E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.6552E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 2.4705E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4523E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 2.5396E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.2956E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 2.8359E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.3555E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0181E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3619E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.6521E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.1096E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.4970E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 8.2803E-003 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7727E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3410E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.9330E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7336E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.6794E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5420E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.7373E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.3810E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.8359E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.3555E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.9747E-002 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.7463E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.0992E-002 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.7186E-002 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.5949E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.2261E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 2.7759E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.3438E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 2.7514E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.6567E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 2.4705E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4536E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 2.5416E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.2977E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 2.8390E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.3581E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0164E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3626E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.6510E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.1102E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.4981E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 8.2917E-003 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7759E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3436E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.9325E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7352E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.6797E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5436E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.7396E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.3832E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.8390E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.3581E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 69714.95748 | 69714.95748 | 5.01956 | 5.01956 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 2779.42662 | 149.60210 | 1.20019 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20019 | 00:10:00 | 20.10000 | 1.47983E-002 | 2779.42662 | 149.60210 | 1.20019 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 73213.60159 | 73213.60159 | 5.27118 | 5.27118 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 20.10000 | 1.47983E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 683763.78149 | 683763.78149 | 49.21313 | 49.21313 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 12242.74517 | 12242.74517 | 0.52293 | 10.77825 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 69684.78257 | 69684.78257 | 5.06543 | 5.06543 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:20:00 | 35.20000 | 1.71581E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 11990.00138 | 11990.00138 | 0.50373 | 1.07782 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12246.61936 | 12246.61936 | 0.89022 | 0.89022 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 35.11500 | 1.71580E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.13533 | 00:10:00 | 20.10000 | 1.47983E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 | |
11 | PERIMETER_BOT_ZN_2 | Cooling | 11609.76571 | 11609.76571 | 0.84392 | 0.84392 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:00:00 | 30.52500 | 1.71492E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 0.00000 | 0.00000 | 0.00000 | 8.72129E-002 | 00:10:00 | 20.10000 | 1.47983E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 | |
13 | PERIMETER_BOT_ZN_1 | Cooling | 11977.99591 | 11977.99591 | 0.87069 | 0.87069 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:20:00 | 35.20000 | 1.71581E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.13533 | 00:10:00 | 20.10000 | 1.47983E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 | |
15 | PERIMETER_BOT_ZN_4 | Cooling | 15528.64342 | 15528.64342 | 1.12878 | 1.12878 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 0.00000 | 0.00000 | 0.00000 | 8.72129E-002 | 00:10:00 | 20.10000 | 1.47983E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 | |
17 | PERIMETER_MID_ZN_3 | Cooling | 112500.25418 | 112500.25418 | 8.17794 | 8.17794 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 35.03000 | 1.71578E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 13192.22370 | 13192.22370 | 0.55703 | 1.35332 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 118221.57648 | 118221.57648 | 8.59379 | 8.59379 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:10:00 | 30.76583 | 1.71497E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 9075.55406 | 9075.55406 | 0.38302 | 0.87213 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 109192.18679 | 109192.18679 | 7.93747 | 7.93747 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 35.20000 | 1.71581E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 14174.71666 | 14174.71666 | 0.59805 | 1.35335 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 128489.18916 | 128489.18916 | 9.34015 | 9.34015 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 446.55488 | 446.55488 | 1.91295E-002 | 0.87213 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13383.60204 | 13383.60204 | 0.97289 | 0.97289 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 35.11500 | 1.71580E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 2561.19442 | 2561.19442 | 0.10762 | 0.13533 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 12157.11194 | 12157.11194 | 0.88373 | 0.88373 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:30:00 | 31.24750 | 1.71506E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 1705.76678 | 1705.76678 | 7.32241E-002 | 8.72129E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 20.10000 | 1.47983E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 12994.79771 | 12994.79771 | 0.94463 | 0.94463 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 35.20000 | 1.71581E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 2667.70077 | 2667.70077 | 0.11451 | 0.13533 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 20.10000 | 1.47983E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 14279.82976 | 14279.82976 | 1.03804 | 1.03804 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 909.45163 | 909.45163 | 3.84957E-002 | 8.72129E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 7992.26798 | 7992.26798 | 0.45817 | 0.45817 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:20:00 | 26.75667 | 1.71421E-002 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56328E-002 | 00:10:00 | 20.10000 | 1.47983E-002 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 75917.70883 | 75917.70883 | 4.35212 | 4.35212 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:20:00 | 26.75667 | 1.71421E-002 | 36.20274 | 1.94861 | 0.15633 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15633 | 00:10:00 | 20.10000 | 1.47983E-002 | 36.20274 | 1.94861 | 0.15633 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7737.87970 | 7737.87970 | 0.44364 | 0.44364 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | 33.44333 | 1.71548E-002 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56328E-002 | 00:10:00 | 20.10000 | 1.47983E-002 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370667.72942 | 370667.72942 | 21.25123 | 21.25123 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 07:00:00 | 27.46500 | 1.71434E-002 | 783.67941 | 42.18139 | 0.33840 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33840 | 00:10:00 | 20.10000 | 1.47983E-002 | 783.67941 | 42.18139 | 0.33840 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 142560.09 | 8.52234 | 8.52234 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1296718.51 | 78.68864 | 78.68864 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 151310.22 | 8.64047 | 8.64047 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
7 | CAV_BAS | Cooling | Sensible | 75835.67 | 5.01956 | 5.01956 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 28886.09 | 1.20019 | 1.20019 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 7927.45 | 0.45817 | 0.45817 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
10 | AIRLOOP DATACENTER BOT | Heating | Sensible | 376.25 | 1.56328E-002 | 1.56328E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER MID | Cooling | Sensible | 75443.20 | 4.35212 | 4.35212 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
12 | AIRLOOP DATACENTER MID | Heating | Sensible | 3762.49 | 0.15633 | 0.15633 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7740.56 | 0.44364 | 0.44364 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
14 | AIRLOOP DATACENTER TOP | Heating | Sensible | 376.25 | 1.56328E-002 | 1.56328E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.01956 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.27118 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36084 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35300 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.86073 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96224 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05587E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.63827E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.86073 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18726.38007 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.63827E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 377.50912 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 49.21313 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38649 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36900 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.15965 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.85792E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.71100E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.15965 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 195577.91525 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.71100E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3970.03722 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.06543 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37550 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36900 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.86914 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.01466E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.69461E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.86914 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30801.10264 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.69461E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 662.62499 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89022 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26827 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26300 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23413 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71539 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42020E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.06136E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23413 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2356.26074 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.06136E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 47.50037 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84392 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18237 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16878 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48632 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.08917E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.48605E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.16878 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1698.64679 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.48605E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 34.24339 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87069 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27429 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26900 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23422 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73145 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.38902E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.06214E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23422 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2357.15469 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.06214E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 47.51839 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.12878 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13635 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22576 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36359 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.79435E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.98766E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.22576 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2272.01282 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.98766E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 45.80199 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.17794 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29203 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27900 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.28164 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77875 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.30466E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.17035E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.28164 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 36239.07334 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.17035E-004 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 774.73892 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.59379 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17909 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.71876 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47757 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.12744E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.31278E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.71876 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26436.49715 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.31278E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 562.21933 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.93747 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30088 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28700 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.27805 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80236 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.26627E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.25289E-004 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.27805 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 37182.48839 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.25289E-004 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 798.58617 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.34015 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16478 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.86803 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43941 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.31220E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.70217E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.86803 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19456.83974 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.70217E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 393.58435 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.97289 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24547 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24100 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23447 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65460 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.55210E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.31162E-005 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23447 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4928.44369 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.31162E-005 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 111.40541 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88373 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17415 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17675 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46441 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18773E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.05290E-005 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17675 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3489.65559 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.05290E-005 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 77.76816 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94463 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25282 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24900 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23521 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67420 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.50698E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.41047E-005 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23521 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5041.43422 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.41047E-005 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 114.49273 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03804 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14827 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20761 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39537 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56972E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.63172E-005 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20761 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3008.22183 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.63172E-005 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 63.39380 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45817 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.35212 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.44364 |
215 | ZoneHVAC:IdealLoadsAirSystem | AIRLOOP DATACENTER BASEMENT | Design Size Maximum Heating Air Flow Rate [m3/s] | 0.33840 |
216 | ZoneHVAC:IdealLoadsAirSystem | AIRLOOP DATACENTER BASEMENT | Design Size Maximum Cooling Air Flow Rate [m3/s] | 21.25123 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.50239 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.72361 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.00479 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.72361 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.52234 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.52234 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31958 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 41.63124 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 26.30613 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 83.26248 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 26.30613 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 78.68864 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 78.68864 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.33431 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.45236 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.72318 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.90473 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.72318 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.64047 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.64047 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31517 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.01956 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.01956 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.01956 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.01956 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.01956 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.01956 |
247 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45817 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45817 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45817 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45817 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45817 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.45817 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
257 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.35212 |
258 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.35212 |
259 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.35212 |
260 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.35212 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.35212 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.35212 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
265 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.44364 |
266 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.44364 |
267 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.44364 |
268 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.44364 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.44364 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.44364 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
273 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.52234 |
274 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 78.68864 |
275 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.64047 |
276 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.01956 |
277 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.45817 |
278 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.35212 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.44364 |
280 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.52234 |
281 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
282 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.55847 |
283 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
284 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.05056 |
285 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.15315E-002 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 252185.36016 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.07285E-002 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.52234 |
290 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 39579.95883 |
291 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.46263E-004 |
292 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 664.77977 |
293 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.52234 |
294 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.07285E-002 |
295 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.43854E-005 |
296 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.46263E-004 |
297 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 78.68864 |
298 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
299 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.03985 |
300 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
301 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.05185 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.19400E-002 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2473928.03888 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 0.10525 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 78.68864 |
307 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 365450.50484 |
308 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.19712E-003 |
309 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6138.05848 |
310 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 78.68864 |
311 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.10525 |
312 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.52452E-006 |
313 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.19712E-003 |
314 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.64047 |
315 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
316 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.29194 |
317 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04995 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.13380E-002 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 247707.56033 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.05381E-002 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.64047 |
324 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 40128.58520 |
325 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.51062E-004 |
326 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 673.99442 |
327 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.64047 |
328 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.05381E-002 |
329 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.51877E-005 |
330 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.51062E-004 |
331 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.01956 |
332 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20019 |
333 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.40686 |
334 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.42629 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.11481E-002 |
337 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 133170.82281 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.66539E-003 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.01956 |
341 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 213658.41512 |
342 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.86918E-003 |
343 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5046.89399 |
344 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.01956 |
345 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.66539E-003 |
346 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.40525E-005 |
347 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.86918E-003 |
348 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45817 |
349 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56328E-002 |
350 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45817 |
351 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9423.91348 |
352 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6739.71112 |
353 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.30791E-004 |
354 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45817 |
355 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45817 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45817 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45817 |
358 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9423.91348 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9423.91348 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 376.24865 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
362 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45817 |
363 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45817 |
364 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9423.91348 |
365 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.30791E-004 |
366 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 376.24865 |
367 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.35212 |
368 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15633 |
369 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.35212 |
370 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 89795.38867 |
371 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 64114.50313 |
372 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.19908E-003 |
373 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.35212 |
374 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.35212 |
375 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.35212 |
376 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.35212 |
377 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 89795.38867 |
378 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 89795.38867 |
379 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 3762.48653 |
380 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
381 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.35212 |
382 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.35212 |
383 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 89795.38867 |
384 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.19908E-003 |
385 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 3762.48653 |
386 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.44364 |
387 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56328E-002 |
388 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44364 |
389 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9140.97581 |
390 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6531.35965 |
391 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.23862E-004 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.44364 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.44364 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.44364 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.44364 |
396 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9140.97581 |
397 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9140.97581 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 376.24865 |
399 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
400 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.44364 |
401 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44364 |
402 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9140.97581 |
403 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.23862E-004 |
404 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 376.24865 |
405 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.13218 |
406 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 26967.43872 |
407 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.13218 |
408 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 15.86143 |
409 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.13218 |
410 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.13218 |
411 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 554819.96110 |
412 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
413 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 9.17177E-003 |
414 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.10061 |
415 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 9.17177E-003 |
416 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 2734.78633 |
417 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
418 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1048389.59094 |
419 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1048389.59000 |
420 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 9.17177E-003 |
421 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.13218 |
422 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 15.86143 |
423 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 0.13218 |
424 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 18670.46750 |
425 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.13218 |
426 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.65850E-002 |
427 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1568992.40561 |
428 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1576441.04500 |
429 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.80122E-002 |
430 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.13218 |
431 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.65850E-002 |
432 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1568992.40561 |
433 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1576441.04500 |
434 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.80122E-002 |
435 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 2.65374E-003 |
436 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 0.31845 |
437 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 2.65374E-003 |
438 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 670.13411 |
439 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 2.65374E-003 |
440 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 35644.39112 |
441 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 21601.32120 |
442 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 17822.19556 |
443 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 1996.19659 |
444 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 5877.22134 |
445 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 109311.18218 |
446 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 109311.18000 |
447 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 2.65374E-003 |
448 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
449 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
450 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
451 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
452 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
453 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.15602 |
454 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 18.72293 |
455 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.15602 |
456 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 46525.90934 |
457 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 60.00601 |
458 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1870406.48667 |
459 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 12.00120 |
460 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 233800.81083 |
461 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 60.00601 |
462 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1870406.48667 |
463 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 12.00120 |
464 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 233800.81083 |
465 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 8.10300E-002 |
466 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 8.10300E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17756.25 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 185439.61 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 29194.44 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 2234.19 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 1610.65 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 2235.04 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2154.31 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 34349.82 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 25058.94 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 35243.25 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 18448.56 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 4670.31 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 3307.08 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 4777.29 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 2851.80 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 31704.59 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 292735.51 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 32144.06 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 181435.04 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 240252.02 | 160896.86 | 79355.16 | 0.67 | 25132.23 | 254.91 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2266133.98 | 1508343.69 | 757790.29 | 0.67 | 238530.02 | 2419.30 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 240819.38 | 161816.06 | 79003.32 | 0.67 | 25124.12 | 254.82 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 134702.16 | 91464.71 | 43237.45 | 0.68 | 13770.17 | 139.66 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.1998690041 | 0.1897116366 | Pass | Pass | 0.8836952611 | 1.1598893899 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.3833078193 | 0.2559636783 | Pass | Pass | 0.3044073679 | 0.4575306008 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.2504006342 | 0.2470661919 | Pass | Pass | 0.1995334194 | 0.3980998546 | Pass | Fail |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.2236715741 | 0.2486373438 | Pass | Pass | 0.2136257612 | 0.4074947032 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3685106810 | 0.2502236547 | Pass | Pass | 0.3080472726 | 0.4615984785 | Pass | Fail |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3981327712 | 0.2733271082 | Pass | Pass | 0.3119965850 | 0.4683687486 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3796406633 | 0.2705146206 | Pass | Pass | 0.3331804306 | 0.5120079780 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5150117960 | 0.3614385280 | Pass | Pass | 0.3195848019 | 0.4777156131 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2351660575 | 0.2519629689 | Pass | Pass | 0.2045684096 | 0.4049505748 | Pass | Fail |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2675324396 | 0.2934013379 | Pass | Pass | 0.2087538268 | 0.4176279593 | Pass | Fail |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2396721939 | 0.2794087153 | Pass | Pass | 0.2275600801 | 0.4806467870 | Pass | Fail |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2834551081 | 0.3143190317 | Pass | Pass | 0.2046354026 | 0.4058294015 | Pass | Fail |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2113654485 | 0.2551091022 | Pass | Pass | 0.2154544350 | 0.4102105168 | Pass | Fail |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2392602056 | 0.2960690368 | Pass | Pass | 0.2228210431 | 0.4220016303 | Pass | Fail |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2214703333 | 0.2873938067 | Pass | Pass | 0.2438901191 | 0.4629304267 | Pass | Fail |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2713187584 | 0.3327550403 | Pass | Pass | 0.2140974384 | 0.4078478322 | Pass | Fail |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.5945017495E-002 | 5.2872484951E-002 | Pass | Pass | 0.4468948916 | 0.9774879850 | Fail | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.1956167609E-002 | 5.9558304786E-002 | Pass | Pass | 0.8926380633 | 7.8552695284 | Fail | Fail |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.0654030803E-002 | 6.8097615839E-002 | Pass | Pass | 0.2521581422 | 0.5417769758 | Fail | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.3719300321E-006 | 3.6764631362E-006 | Pass | Pass | 1.6558580388E-003 | 1.0862715619E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.3456510194E-006 | 3.6504898808E-006 | Pass | Pass | 1.3097667682E-003 | 1.1687437743E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.4606696434E-006 | 3.7875218880E-006 | Pass | Pass | 1.3031965979E-003 | 1.1363995182E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.1464311809E-015 | 2.9670639653E-015 | Pass | Pass | 2.8068359837E-005 | 1.0596990498E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6140.39 | -51.7 | 0.00 | -17359.7 | 30948.51 | 19677.52 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.5037_SHGC_EAST_0.23 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.5037_SHGC_EAST_0.23 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.5037_SHGC_EAST_0.23 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.5037_SHGC_WEST_0.23 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.5037_SHGC_WEST_0.23 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.5037_SHGC_WEST_0.23 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.864 | 0.231 | 0.231 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5037_SHGC_EAST_0.23 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.864 | 0.231 | 0.231 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.864 | 0.231 | 0.231 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5037_SHGC_WEST_0.23 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.864 | 0.231 | 0.231 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.864 | 0.231 | 0.231 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5037_SHGC_EAST_0.23 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.864 | 0.231 | 0.231 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.864 | 0.231 | 0.231 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5037_SHGC_WEST_0.23 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.864 | 0.231 | 0.231 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.864 | 0.231 | 0.231 | |||||||||||||||||
North Total or Average | 1043.06 | 2.864 | 0.231 | 0.231 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.864 | 0.231 | 0.231 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.8895 | 2779.43 | 16369.36 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 135.58 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8895 | 2496.12 | 14700.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 121.76 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8895 | 24961.20 | 147008.37 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 1217.57 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8895 | 2496.12 | 14700.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 121.76 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8895 | 313.41 | 1845.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.25 | 0.0000 | Y | 8.75 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.40 | 0.0000 | Y | 5.67 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8895 | 313.42 | 1845.88 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.16 | 0.0000 | Y | 8.72 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.16 | 0.0000 | Y | 5.62 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8895 | 3134.13 | 18458.37 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.26 | 0.0000 | Y | 87.51 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8895 | 2019.75 | 11895.27 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.39 | 0.0000 | Y | 56.70 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8895 | 3134.20 | 18458.77 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.15 | 0.0000 | Y | 87.16 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8895 | 2019.75 | 11895.27 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.15 | 0.0000 | Y | 56.16 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8895 | 313.41 | 1845.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.26 | 0.0000 | Y | 8.75 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.39 | 0.0000 | Y | 5.67 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8895 | 313.42 | 1845.88 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.15 | 0.0000 | Y | 8.72 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.15 | 0.0000 | Y | 5.62 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.8895 | 783.68 | 4615.46 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 38.23 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 8.8011 | 36.20 | 318.62 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.26 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 8.8011 | 362.03 | 3186.24 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 32.64 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 8.8011 | 36.20 | 318.62 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.26 |
Interior Lighting Total | 5.9168 | 46320.38 | 274067.57 | 635.13 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.05 | AstronomicalClock | - | 41.93 | 41.93 | 78.49 | |
EXTERIOR_LIGHTS_B | 991.40 | AstronomicalClock | - | 83.83 | 62.88 | 11.70 | |
EXTERIOR_LIGHTS_C | 26646.63 | AstronomicalClock | - | 83.83 | 45.49 | 227.52 | |
Exterior Lighting Total | 37611.08 | 317.72 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3099846.62 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1048389.59 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1576441.04 | 6.28 | 1508859.51 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1576441.04 | 6.28 | 1508859.51 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 148548.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 109311.18 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1870406.49 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1870406.49 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 252185.36 | 240252.02 | 160896.86 | 79355.16 | 0.67 | - | 25132.23 | 254.91 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2473928.04 | 2266133.98 | 1508343.69 | 757790.29 | 0.67 | - | 238530.02 | 2419.30 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 247707.56 | 240819.38 | 161816.06 | 79003.32 | 0.67 | - | 25124.12 | 254.82 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 133170.82 | 134702.16 | 91464.71 | 43237.45 | 0.68 | - | 13770.17 | 139.66 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9423.91 | 6739.71 | 2684.20 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 89795.39 | 64114.50 | 25680.89 | 0.71 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9140.98 | 6531.36 | 2609.62 | 0.71 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18726.38 | 17756.25 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 195577.92 | 185439.61 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 30801.10 | 29194.44 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 2356.26 | 2234.19 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 1698.65 | 1610.65 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2357.15 | 2235.04 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 2272.01 | 2154.31 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 36239.07 | 34349.82 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 26436.50 | 25058.94 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 37182.49 | 35243.25 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 19456.84 | 18448.56 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 4928.44 | 4670.31 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 3489.66 | 3307.08 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 5041.43 | 4777.29 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3008.22 | 2851.80 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 39579.96 | 31704.59 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 365450.50 | 292735.51 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 40128.59 | 32144.06 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 213658.42 | 181435.04 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9423.91 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 89795.39 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9140.98 | 0.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 376.25 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 3762.49 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 376.25 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.52 | 18416.32 | 2160.95 | 1.00 | 1.12 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 78.69 | 170041.95 | 2160.95 | 1.00 | 1.08 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.64 | 18671.59 | 2160.95 | 1.00 | 1.12 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.02 | 8511.44 | 1695.65 | 1.00 | 1.16 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 513.20 | 1120.11 | 1.00 | 1.65 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.35 | 4874.85 | 1120.11 | 1.00 | 1.16 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.44 | 496.93 | 1120.11 | 1.00 | 1.66 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.132179 | 26967.44 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.009172 | 2734.79 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.132179 | 18670.47 | 141251.81 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.002654 | 670.13 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.156024 | 46525.91 | 298196.27 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 69714.96 | 69714.96 | 25.08 | 5.020 | 5.020 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00900 | 28.91 | 0.01715 | 1.200 | 0.00 |
CORE_BOTTOM | 73213.60 | 73213.60 | 29.33 | 5.271 | 5.271 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 28.91 | 0.01715 | 1.078 | 0.00 |
CORE_MID | 683763.78 | 683763.78 | 273.93 | 49.213 | 49.213 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 28.91 | 0.01715 | 10.778 | 0.00 |
CORE_TOP | 69684.78 | 69684.78 | 27.92 | 5.065 | 5.065 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:20:00 | 24.00 | 24.00 | 0.00894 | 35.20 | 0.01716 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12246.62 | 12246.62 | 39.08 | 0.890 | 0.890 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 24.00 | 24.00 | 0.00886 | 35.12 | 0.01716 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 11609.77 | 11609.77 | 57.48 | 0.844 | 0.844 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:00:00 | 24.00 | 24.00 | 0.00875 | 30.53 | 0.01715 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 11978.00 | 11978.00 | 38.22 | 0.871 | 0.871 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:20:00 | 24.00 | 24.00 | 0.00887 | 35.20 | 0.01716 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 15528.64 | 15528.64 | 76.88 | 1.129 | 1.129 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00869 | 34.58 | 0.01716 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 112500.25 | 112500.25 | 358.95 | 8.178 | 8.178 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 24.00 | 24.00 | 0.00897 | 35.03 | 0.01716 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 118221.58 | 118221.58 | 585.33 | 8.594 | 8.594 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:10:00 | 24.00 | 24.00 | 0.00879 | 30.77 | 0.01715 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 109192.19 | 109192.19 | 348.39 | 7.937 | 7.937 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:30:00 | 24.00 | 24.00 | 0.00899 | 35.20 | 0.01716 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 128489.19 | 128489.19 | 636.16 | 9.340 | 9.340 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00877 | 34.58 | 0.01716 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13383.60 | 13383.60 | 42.70 | 0.973 | 0.973 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 24.00 | 24.00 | 0.00892 | 35.12 | 0.01716 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 12157.11 | 12157.11 | 60.19 | 0.884 | 0.884 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:30:00 | 24.00 | 24.00 | 0.00881 | 31.25 | 0.01715 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 12994.80 | 12994.80 | 41.46 | 0.945 | 0.945 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 24.00 | 24.00 | 0.00894 | 35.20 | 0.01716 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 14279.83 | 14279.83 | 70.70 | 1.038 | 1.038 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00876 | 34.58 | 0.01716 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 7992.27 | 7992.27 | 220.76 | 0.458 | 0.458 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 26.76 | 0.01714 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 75917.71 | 75917.71 | 2097.02 | 4.352 | 4.352 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 26.76 | 0.01714 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7737.88 | 7737.88 | 213.74 | 0.444 | 0.444 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | 27.00 | 27.00 | 0.00859 | 33.44 | 0.01715 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370667.73 | 370667.73 | 472.98 | 21.251 | 21.251 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 27.47 | 0.01714 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 26.70 | 0.00850 | 20.10 | 0.01480 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 25.75 | 0.01480 | 20.10 | 0.01480 | 1.078 | 0.00 | |
CORE_MID | 12242.75 | 12242.75 | 4.90 | 0.523 | 10.778 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00972 | 20.10 | 0.01480 | 10.778 | 0.00 |
CORE_TOP | 11990.00 | 11990.00 | 4.80 | 0.504 | 1.078 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 20.10 | 0.01480 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.000 | 0.135 | 00:10:00 | 15.60 | 24.46 | 0.01480 | 20.10 | 0.01480 | 0.135 | 0.00 | |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 0.00 | 0.000 | 0.087 | 00:10:00 | 15.60 | 24.22 | 0.01480 | 20.10 | 0.01480 | 0.087 | 0.00 | |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 0.00 | 0.000 | 0.135 | 00:10:00 | 15.60 | 23.12 | 0.01480 | 20.10 | 0.01480 | 0.135 | 0.00 | |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 0.00 | 0.000 | 0.087 | 00:10:00 | 15.60 | 25.04 | 0.01480 | 20.10 | 0.01480 | 0.087 | 0.00 | |
PERIMETER_MID_ZN_3 | 13192.22 | 13192.22 | 42.09 | 0.557 | 1.353 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00997 | 20.10 | 0.01480 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 9075.55 | 9075.55 | 44.93 | 0.383 | 0.872 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00996 | 20.10 | 0.01480 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 14174.72 | 14174.72 | 45.23 | 0.598 | 1.353 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00990 | 20.10 | 0.01480 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 446.55 | 446.55 | 2.21 | 0.019 | 0.872 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01413 | 20.10 | 0.01480 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 2561.19 | 2561.19 | 8.17 | 0.108 | 0.135 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00967 | 20.10 | 0.01480 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 1705.77 | 1705.77 | 8.45 | 0.073 | 0.087 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 21.00 | 0.00949 | 20.10 | 0.01480 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 2667.70 | 2667.70 | 8.51 | 0.115 | 0.135 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 21.00 | 0.00943 | 20.10 | 0.01480 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 909.45 | 909.45 | 4.50 | 0.038 | 0.087 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01040 | 20.10 | 0.01480 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 20.10 | 0.01480 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 26.51 | 0.00850 | 20.10 | 0.01480 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 26.00 | 0.00850 | 20.10 | 0.01480 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 20.10 | 0.01480 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 8.52 | 8.52 | 0.00 | 0.00 | 8.5223 | 2.7236 | 8.5223 | 0.3196 | 0.3000 |
VAV_MID WITH REHEAT | 78.69 | 78.69 | 0.00 | 0.00 | 78.6886 | 26.3061 | 78.6886 | 0.3343 | 0.3000 |
VAV_TOP WITH REHEAT | 8.64 | 8.64 | 0.00 | 0.00 | 8.6405 | 2.7232 | 8.6405 | 0.3152 | 0.3000 |
CAV_BAS | 5.02 | 5.02 | 1.20 | 1.20 | 5.0196 | 5.0196 | 5.0196 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.46 | 0.46 | 0.02 | 0.02 | 0.4582 | 0.4582 | 0.4582 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.35 | 4.35 | 0.16 | 0.16 | 4.3521 | 4.3521 | 4.3521 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.44 | 0.44 | 0.02 | 0.02 | 0.4436 | 0.4436 | 0.4436 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18726.380 | 18726.380 | 1.860725 | 0.00016383 | 377.509 | 12/21 00:10:00 | 12/21 00:10:00 | 18726.38 | 18726.38 | 1.860725 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 18795.43 | 18795.43 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 195577.915 | 195577.915 | 18.159645 | 0.00171100 | 3970.037 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 195577.92 | 195577.92 | 18.159645 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00972174 | 62.6463 | 12242.75 | 0.00 | 196296.38 | 196296.38 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 30801.103 | 30801.103 | 1.869143 | 0.00026946 | 662.625 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 30801.10 | 30801.10 | 1.869143 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 11990.00 | 0.00 | 30908.86 | 30908.86 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 2356.261 | 2356.261 | 0.234127 | 0.00002061 | 47.500 | 12/21 00:10:00 | 12/21 00:10:00 | 2356.26 | 2356.26 | 0.234127 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 2364.95 | 2364.95 | ||
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 1698.647 | 1698.647 | 0.168784 | 0.00001486 | 34.243 | 12/21 00:10:00 | 12/21 00:10:00 | 1698.65 | 1698.65 | 0.168784 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 1704.91 | 1704.91 | ||
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 2357.155 | 2357.155 | 0.234216 | 0.00002062 | 47.518 | 12/21 00:10:00 | 12/21 00:10:00 | 2357.15 | 2357.15 | 0.234216 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 2365.85 | 2365.85 | ||
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 2272.013 | 2272.013 | 0.225756 | 0.00001988 | 45.802 | 12/21 00:10:00 | 12/21 00:10:00 | 2272.01 | 2272.01 | 0.225756 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 2280.39 | 2280.39 | ||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 36239.073 | 36239.073 | 2.281645 | 0.00031704 | 774.739 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 36239.07 | 36239.07 | 2.281645 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00996728 | 64.2013 | 13192.22 | 0.00 | 36366.34 | 36366.34 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 26436.497 | 26436.497 | 1.718757 | 0.00023128 | 562.219 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26436.50 | 26436.50 | 1.718757 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00995756 | 64.1395 | 9075.55 | 0.00 | 26529.63 | 26529.63 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 37182.488 | 37182.488 | 2.278054 | 0.00032529 | 798.586 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 37182.49 | 37182.49 | 2.278054 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00989766 | 63.7597 | 14174.72 | 0.00 | 37312.70 | 37312.70 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 19456.840 | 19456.840 | 1.868031 | 0.00017022 | 393.584 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19456.84 | 19456.84 | 1.868031 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01412991 | 90.4213 | 446.55 | 0.00 | 19528.45 | 19528.45 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 4928.444 | 4928.444 | 0.234468 | 0.00004312 | 111.405 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4928.44 | 4928.44 | 0.234468 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00966683 | 62.2932 | 2561.19 | 0.00 | 4945.26 | 4945.26 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 3489.656 | 3489.656 | 0.176747 | 0.00003053 | 77.768 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3489.66 | 3489.66 | 0.176747 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00948650 | 61.1488 | 1705.77 | 0.00 | 3501.64 | 3501.64 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 5041.434 | 5041.434 | 0.235213 | 0.00004410 | 114.493 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 5041.43 | 5041.43 | 0.235213 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00943033 | 60.7922 | 2667.70 | 0.00 | 5058.60 | 5058.60 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 3008.222 | 3008.222 | 0.207608 | 0.00002632 | 63.394 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3008.22 | 3008.22 | 0.207608 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01039908 | 66.9355 | 909.45 | 0.00 | 3019.09 | 3019.09 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 252185.360 | -999.000 | 8.522339 | 0.01072855 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 252185.36 | 171001.74 | 8.522339 | 27.56 | 19.99 | 0.01153152 | 11.05 | 11.05 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 29.7828 | 24.00 | 0.00891038 | 47.9151 | 109873.41 | 0.00 | 252440.58 | 167613.55 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 39579.959 | 39579.959 | 2.556702 | 0.00034626 | 664.780 | unknown | unknown | unknown | 39579.96 | 39579.96 | 2.556702 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 99.2760 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 38343.09 | 38343.09 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2473928.039 | -999.000 | 78.688637 | 0.10524662 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 2473928.04 | 1624220.66 | 78.688637 | 28.04 | 20.44 | 0.01194004 | 11.05 | 11.05 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 32.2562 | 24.00 | 0.00899488 | 48.3634 | 967822.51 | 0.00 | 2476668.73 | 1598407.51 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 365450.505 | 365450.505 | 23.606591 | 0.00319712 | 6138.058 | unknown | unknown | unknown | 365450.50 | 365450.50 | 23.606591 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 107.5206 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 354030.18 | 354030.18 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 247707.560 | -999.000 | 8.640469 | 0.01053805 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | 247707.56 | 170608.78 | 8.640469 | 27.29 | 19.76 | 0.01133800 | 11.05 | 11.05 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 29.3756 | 24.00 | 0.00891415 | 47.9355 | 118760.53 | 0.00 | 247947.95 | 166880.06 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 40128.585 | 40128.585 | 2.592141 | 0.00035106 | 673.994 | unknown | unknown | unknown | 40128.59 | 40128.59 | 2.592141 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 97.9187 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 38874.57 | 38874.57 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 133170.823 | -999.000 | 5.019560 | 0.00566539 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 11:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 133170.82 | 92059.41 | 5.019560 | 26.41 | 19.34 | 0.01114814 | 11.43 | 11.43 | 0.00850000 | 33.25 | 0.01715442 | 25.34 | 23.9103 | 24.00 | 0.00903291 | 48.5647 | 68853.89 | 0.00 | 133318.18 | 90220.63 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 213658.415 | 213658.415 | 5.019560 | 0.00186918 | 5046.894 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 213658.42 | 213658.42 | 5.019560 | 4.81 | 4.81 | 0.01000594 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 23.9103 | 26.70 | 0.00850000 | 38.9515 | 0.00 | 0.00 | 192321.47 | 192321.47 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9423.913 | 6739.711 | 0.458172 | 0.00023079 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:20:00 | 8845.11 | 8358.42 | -999.0 | 28.17 | 18.14 | 0.00888581 | 12.80 | 12.09 | 0.00850000 | 33.44 | 0.01715480 | 25.39 | -999.0000 | 27.00 | 0.00859129 | 38.6798 | 7928.19 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 89795.389 | 64114.503 | 4.352125 | 0.00219908 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:20:00 | 84325.10 | 79464.78 | -999.0 | 28.18 | 18.16 | 0.00890553 | 12.80 | 12.09 | 0.00850000 | 33.44 | 0.01715480 | 25.39 | -999.0000 | 27.00 | 0.00859599 | 38.7010 | 75390.40 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9140.976 | 6531.360 | 0.443642 | 0.00022386 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | 8582.13 | 8099.24 | -999.0 | 28.18 | 18.15 | 0.00889530 | 12.80 | 12.09 | 0.00850000 | 33.59 | 0.01715507 | 25.42 | -999.0000 | 27.00 | 0.00859352 | 38.6898 | 7735.64 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9423.913 | 9423.913 | 0.458172 | 0.00023079 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9423.91 | 9423.91 | 0.458172 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 3.4120 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 89795.389 | 89795.389 | 4.352125 | 0.00219908 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 89795.39 | 89795.39 | 4.352125 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 3.5920 | 26.51 | 0.00850000 | 39.3911 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9140.976 | 9140.976 | 0.443642 | 0.00022386 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9140.98 | 9140.98 | 0.443642 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 3.5237 | 26.00 | 0.00850209 | 40.6022 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 376.249 | 376.249 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 376.25 | 376.25 | 0.458172 | 0.69 | 0.69 | 0.00871490 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 3.4120 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 3762.487 | 3762.487 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 3762.49 | 3762.49 | 4.352125 | 0.72 | 0.72 | 0.00872623 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 3.5920 | 26.51 | 0.00850000 | 39.3911 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 376.249 | 376.249 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 376.25 | 376.25 | 0.443642 | 0.71 | 0.71 | 0.00872396 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 3.5237 | 26.00 | 0.00850209 | 40.6022 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18726.380 | 18726.380 | 1.860725 | 0.00016383 | 377.509 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 1.7510 | 1.786204 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 18726.38 | 18726.38 | 1.0000 | 2.23955958 | 1.860725 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.16380983 | 60.00 | 32.22 | 27.78 | 0.000 | 18726.38 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 18795.43 | 18795.43 | 2.23955958 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 195577.915 | 195577.915 | 18.159645 | 0.00171100 | 3970.037 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 18.2870 | 18.655080 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 195577.92 | 195577.92 | 1.0000 | 21.85685814 | 18.159645 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 1.71082638 | 60.00 | 32.22 | 27.78 | 0.000 | 195577.92 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.93 | 0.00972174 | 21.00 | 0.00972174 | 62.6463 | 12242.75 | 0.00 | 196296.38 | 196296.38 | 21.85685814 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.61 | 15.08 | 0.00800000 | 42040.8 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 30801.103 | 30801.103 | 1.869143 | 0.00026946 | 662.625 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 2.8800 | 2.937944 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 30801.10 | 30801.10 | 1.0000 | 2.24969163 | 1.869143 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.26943399 | 60.00 | 32.22 | 27.78 | 0.000 | 30801.10 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.69 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 11990.00 | 0.00 | 30908.86 | 30908.86 | 2.24969163 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 26.27 | 16.76 | 0.00800000 | 46799.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2356.261 | 2356.261 | 0.234127 | 0.00002061 | 47.500 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 0.2203 | 0.224750 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 2356.26 | 2356.26 | 1.0000 | 0.28179425 | 0.234127 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.02061149 | 60.00 | 32.22 | 27.78 | 0.000 | 2356.26 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 2364.95 | 2364.95 | 0.28179425 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1698.647 | 1698.647 | 0.168784 | 0.00001486 | 34.243 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 0.1588 | 0.162024 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 1698.65 | 1698.65 | 1.0000 | 0.20314768 | 0.168784 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01485899 | 60.00 | 32.22 | 27.78 | 0.000 | 1698.65 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 1704.91 | 1704.91 | 0.20314768 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2357.155 | 2357.155 | 0.234216 | 0.00002062 | 47.518 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 0.2204 | 0.224836 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 2357.15 | 2357.15 | 1.0000 | 0.28190117 | 0.234216 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.02061931 | 60.00 | 32.22 | 27.78 | 0.000 | 2357.15 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 2365.85 | 2365.85 | 0.28190117 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2272.013 | 2272.013 | 0.225756 | 0.00001988 | 45.802 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 0.2124 | 0.216715 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 2272.01 | 2272.01 | 1.0000 | 0.27171872 | 0.225756 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01987453 | 60.00 | 32.22 | 27.78 | 0.000 | 2272.01 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 2280.39 | 2280.39 | 0.27171872 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 36239.073 | 36239.073 | 2.281645 | 0.00031704 | 774.739 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 3.3884 | 3.456642 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 36239.07 | 36239.07 | 1.0000 | 2.74617600 | 2.281645 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.31700288 | 60.00 | 32.22 | 27.78 | 0.000 | 36239.07 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.75 | 0.00996728 | 21.00 | 0.00996728 | 64.2013 | 13192.22 | 0.00 | 36366.34 | 36366.34 | 2.74617600 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 25.79 | 16.59 | 0.00800000 | 46302.4 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26436.497 | 26436.497 | 1.718757 | 0.00023128 | 562.219 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 2.4719 | 2.521629 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26436.50 | 26436.50 | 1.0000 | 2.06868751 | 1.718757 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.23125442 | 60.00 | 32.22 | 27.78 | 0.000 | 26436.50 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.73 | 0.00995756 | 21.00 | 0.00995756 | 64.1395 | 9075.55 | 0.00 | 26529.63 | 26529.63 | 2.06868751 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 25.38 | 16.45 | 0.00800000 | 45884.2 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37182.488 | 37182.488 | 2.278054 | 0.00032529 | 798.586 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 3.4767 | 3.546629 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 37182.49 | 37182.49 | 1.0000 | 2.74185486 | 2.278054 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.32525545 | 60.00 | 32.22 | 27.78 | 0.000 | 37182.49 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.73 | 0.00989766 | 21.00 | 0.00989766 | 63.7597 | 14174.72 | 0.00 | 37312.70 | 37312.70 | 2.74185486 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 26.15 | 16.72 | 0.00800000 | 46668.4 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19456.840 | 19456.840 | 1.868031 | 0.00017022 | 393.584 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 1.8193 | 1.855879 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19456.84 | 19456.84 | 1.0000 | 2.24835223 | 1.868031 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.17019956 | 60.00 | 32.22 | 27.78 | 0.000 | 19456.84 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.98 | 0.01412991 | 21.00 | 0.01412991 | 90.4213 | 446.55 | 0.00 | 19528.45 | 19528.45 | 2.24835223 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.32 | 14.97 | 0.00800000 | 41745.5 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4928.444 | 4928.444 | 0.234468 | 0.00004312 | 111.405 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 0.4608 | 0.470097 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4928.44 | 4928.44 | 1.0000 | 0.28220413 | 0.234468 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.04311178 | 60.00 | 32.22 | 27.78 | 0.000 | 4928.44 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.56 | 0.00966683 | 21.00 | 0.00966683 | 62.2932 | 2561.19 | 0.00 | 4945.26 | 4945.26 | 0.28220413 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.98 | 18.03 | 0.00800000 | 50583.5 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3489.656 | 3489.656 | 0.176747 | 0.00003053 | 77.768 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 0.3263 | 0.332859 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | Sensible | 3489.66 | 3489.66 | 1.0000 | 0.21273175 | 0.176747 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.03052592 | 60.00 | 32.22 | 27.78 | 0.000 | 3489.66 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.02 | 0.00948650 | 21.00 | 0.00948650 | 61.1488 | 1705.77 | 0.00 | 3501.64 | 3501.64 | 0.21273175 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.94 | 17.68 | 0.00800000 | 49520.2 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5041.434 | 5041.434 | 0.235213 | 0.00004410 | 114.493 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 0.4714 | 0.480874 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | Sensible | 5041.43 | 5041.43 | 1.0000 | 0.28310175 | 0.235213 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.04410017 | 60.00 | 32.22 | 27.78 | 0.000 | 5041.43 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.02 | 0.00943033 | 21.00 | 0.00943033 | 60.7922 | 2667.70 | 0.00 | 5058.60 | 5058.60 | 0.28310175 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.32 | 18.15 | 0.00800000 | 50928.3 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3008.222 | 3008.222 | 0.207608 | 0.00002632 | 63.394 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 0.2813 | 0.286937 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 3008.22 | 3008.22 | 1.0000 | 0.24987545 | 0.207608 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.02631455 | 60.00 | 32.22 | 27.78 | 0.000 | 3008.22 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.75 | 0.01039908 | 21.00 | 0.01039908 | 66.9355 | 909.45 | 0.00 | 3019.09 | 3019.09 | 0.24987545 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 24.65 | 16.19 | 0.00800000 | 45142.2 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 252185.360 | -999.000 | 8.522339 | 0.01072855 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2765 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.522339 | 10.25744423 | 4197.9300 | 999.8980 | 132.16512927 | 12.27 | 6.67 | 5.60 | 3106991.78 | 8.1167 | 8.116705 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | Sensible | 252185.36 | 171001.74 | 1.0000 | 10.25744423 | 8.522339 | 27.56 | 19.99 | 0.01153152 | 57122.2 | 11.05 | 11.05 | 0.00850000 | 32536.6 | 10.72745378 | 6.67 | 12.27 | 5.60 | 18416.320 | 233769.04 | 35.20 | 0.01715815 | 25.83 | 2.53819000 | 29.7828 | 24.00 | 0.00891038 | 24.00 | 0.00891038 | 47.9151 | 109873.41 | 0.00 | 252440.58 | 167613.55 | 10.25744423 | 27.56 | 20.00 | 0.01153152 | 57122.2 | 11.64 | 11.36 | 0.00825319 | 32511.8 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 39579.959 | 39579.959 | 2.556702 | 0.00034626 | 664.780 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.522339 | 10.25744423 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 3.7008 | 3.775310 | unknown | unknown | unknown | unknown | unknown | Sensible | 39579.96 | 39579.96 | 1.0000 | 3.07723327 | 2.556702 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.34622742 | 60.00 | 32.22 | 27.78 | 0.000 | 39579.96 | 0.00 | 0.00000000 | -6.26 | 2.53819000 | 99.2760 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 38343.09 | 38343.09 | 3.07723327 | 2.80 | -4.48 | 0.00000000 | 2838.6 | 15.20 | 3.32 | 0.00000000 | 15298.9 | ||
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2473928.039 | -999.000 | 78.688637 | 0.10524662 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.0359 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 78.688637 | 94.70924894 | 4197.9300 | 999.8980 | 132.16512927 | 12.27 | 6.67 | 5.60 | 3106991.78 | 79.6245 | 79.624544 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | Sensible | 2473928.04 | 1624220.66 | 1.0000 | 94.70924894 | 78.688637 | 28.04 | 20.44 | 0.01194004 | 58659.3 | 11.05 | 11.05 | 0.00850000 | 32538.0 | 105.23588151 | 6.67 | 12.27 | 5.60 | 170041.955 | 2303886.08 | 35.20 | 0.01715815 | 25.83 | 25.38195000 | 32.2562 | 24.00 | 0.00899488 | 24.00 | 0.00899488 | 48.3634 | 967822.51 | 0.00 | 2476668.73 | 1598407.51 | 94.70924894 | 28.04 | 20.45 | 0.01194004 | 58659.3 | 11.61 | 11.36 | 0.00826386 | 32509.0 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 365450.505 | 365450.505 | 23.606591 | 0.00319712 | 6138.058 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 78.688637 | 94.70924894 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 34.1706 | 34.858273 | unknown | unknown | unknown | unknown | unknown | Sensible | 365450.50 | 365450.50 | 1.0000 | 28.41277468 | 23.606591 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 3.19679430 | 60.00 | 32.22 | 27.78 | 0.000 | 365450.50 | 0.00 | 0.00000000 | -6.26 | 25.38195000 | 107.5206 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 354030.18 | 354030.18 | 28.41277468 | 2.80 | -4.48 | 0.00000000 | 2838.6 | 15.20 | 3.32 | 0.00000000 | 15298.9 | ||
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 247707.560 | -999.000 | 8.640469 | 0.01053805 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.9168 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.640469 | 10.39962489 | 4197.9300 | 999.8980 | 132.16512927 | 12.27 | 6.67 | 5.60 | 3106991.78 | 7.9726 | 7.972585 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | Sensible | 247707.56 | 170608.78 | 1.0000 | 10.39962489 | 8.640469 | 27.29 | 19.76 | 0.01133800 | 56354.9 | 11.05 | 11.05 | 0.00850000 | 32536.0 | 10.53697725 | 6.67 | 12.27 | 5.60 | 18671.593 | 229035.97 | 35.20 | 0.01715815 | 25.83 | 2.53819000 | 29.3756 | 24.00 | 0.00891415 | 24.00 | 0.00891415 | 47.9355 | 118760.53 | 0.00 | 247947.95 | 166880.06 | 10.39962489 | 27.29 | 19.77 | 0.01133800 | 56354.9 | 11.65 | 11.36 | 0.00824782 | 32512.9 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 40128.585 | 40128.585 | 2.592141 | 0.00035106 | 673.994 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.640469 | 10.39962489 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 3.7521 | 3.827641 | unknown | unknown | unknown | unknown | unknown | Sensible | 40128.59 | 40128.59 | 1.0000 | 3.11988747 | 2.592141 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.35102656 | 60.00 | 32.22 | 27.78 | 0.000 | 40128.59 | 0.00 | 0.00000000 | -6.26 | 2.53819000 | 97.9187 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | 38874.57 | 38874.57 | 3.11988747 | 2.80 | -4.48 | 0.00000000 | 2838.6 | 15.20 | 3.32 | 0.00000000 | 15298.9 | ||
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 133170.823 | -999.000 | 5.019560 | 0.00566539 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.5638 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 5.019560 | 6.04151709 | 4197.9300 | 999.8980 | 132.16512927 | 12.27 | 6.67 | 5.60 | 3106991.78 | 4.2862 | 4.286166 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 11:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | Sensible | 133170.82 | 92059.41 | 1.0000 | 6.04151709 | 5.019560 | 26.41 | 19.34 | 0.01114814 | 54962.7 | 11.43 | 11.43 | 0.00850000 | 32920.1 | 5.66481672 | 6.67 | 12.27 | 5.60 | 8511.439 | 124659.38 | 33.25 | 0.01715442 | 25.34 | 1.20019084 | 23.9103 | 24.00 | 0.00903291 | 24.00 | 0.00903291 | 48.5647 | 68853.89 | 0.00 | 133318.18 | 90220.63 | 6.04151709 | 26.41 | 19.35 | 0.01114814 | 54962.7 | 11.85 | 11.52 | 0.00832068 | 32895.7 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 213658.415 | 213658.415 | 5.019560 | 0.00186918 | 5046.894 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 5.019560 | 6.04151709 | 4197.9300 | 999.8980 | 9.17083387 | 54.44 | 82.22 | 27.78 | 1069488.85 | 19.9776 | 20.379677 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 213658.42 | 213658.42 | 1.0000 | 6.04151709 | 5.019560 | 4.81 | 4.81 | 0.01000594 | 29942.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 1.86898635 | 60.00 | 32.22 | 27.78 | 0.000 | 213658.42 | 20.10 | 0.01479830 | 20.10 | 1.20019084 | 23.9103 | 0.00 | 0.00850000 | 26.70 | 0.00850000 | 38.9515 | 0.00 | 0.00 | 192321.47 | 192321.47 | 6.04151709 | 12.80 | 12.80 | 0.01000594 | 38124.3 | 43.90 | 23.66 | 0.01000594 | 69957.6 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9423.913 | 6739.711 | 0.458172 | 0.00023079 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3583 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:20:00 | Sensible | 8845.11 | 8358.42 | 0.9386 | -999.0 | -999.0 | 28.17 | 18.14 | 0.00888581 | 50991.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8845.11 | 33.44 | 0.01715480 | 25.39 | 0.01563279 | -999.0000 | 27.00 | 0.00859129 | 27.00 | 0.00859129 | 38.6798 | 7928.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 89795.389 | 64114.503 | 4.352125 | 0.00219908 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3949 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:20:00 | Sensible | 84325.10 | 79464.78 | 0.9391 | -999.0 | -999.0 | 28.18 | 18.16 | 0.00890553 | 51053.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84325.10 | 33.44 | 0.01715480 | 25.39 | 0.15632792 | -999.0000 | 27.00 | 0.00859599 | 27.00 | 0.00859599 | 38.7010 | 75390.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9140.976 | 6531.360 | 0.443642 | 0.00022386 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3759 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | Sensible | 8582.13 | 8099.24 | 0.9389 | -999.0 | -999.0 | 28.18 | 18.15 | 0.00889530 | 51026.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8582.13 | 33.59 | 0.01715507 | 25.42 | 0.01563279 | -999.0000 | 27.00 | 0.00859352 | 27.00 | 0.00859352 | 38.6898 | 7735.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9423.913 | 9423.913 | 0.458172 | 0.00023079 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9423.91 | 9423.91 | 1.0000 | 0.55145319 | 0.458172 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9423.91 | 20.10 | 0.01479830 | 20.10 | 0.01563279 | 3.4120 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 89795.389 | 89795.389 | 4.352125 | 0.00219908 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 89795.39 | 89795.39 | 1.0000 | 5.23819554 | 4.352125 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89795.39 | 20.10 | 0.01479830 | 20.10 | 0.15632792 | 3.5920 | 0.00 | 0.00850000 | 26.51 | 0.00850000 | 39.3911 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9140.976 | 9140.976 | 0.443642 | 0.00022386 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9140.98 | 9140.98 | 1.0000 | 0.53396498 | 0.443642 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9140.98 | 20.10 | 0.01479830 | 20.10 | 0.01563279 | 3.5237 | 0.00 | 0.00850209 | 26.00 | 0.00850209 | 40.6022 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 376.249 | 376.249 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.458172 | 0.55145319 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 376.25 | 376.25 | 1.0000 | 0.55145319 | 0.458172 | 0.69 | 0.69 | 0.00871490 | 22495.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 376.25 | 20.10 | 0.01479830 | 20.10 | 0.01563279 | 3.4120 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 3762.487 | 3762.487 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.352125 | 5.23819554 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 3762.49 | 3762.49 | 1.0000 | 5.23819554 | 4.352125 | 0.72 | 0.72 | 0.00872623 | 22561.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3762.49 | 20.10 | 0.01479830 | 20.10 | 0.15632792 | 3.5920 | 0.00 | 0.00850000 | 26.51 | 0.00850000 | 39.3911 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 376.249 | 376.249 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.443642 | 0.53396498 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 376.25 | 376.25 | 1.0000 | 0.53396498 | 0.443642 | 0.71 | 0.71 | 0.00872396 | 22541.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 376.25 | 20.10 | 0.01479830 | 20.10 | 0.01563279 | 3.5237 | 0.00 | 0.00850209 | 26.00 | 0.00850209 | 40.6022 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5943.00 | 2517.50 | 2517.50 |
CORE_BOTTOM | 5943.00 | 0.00 | 0.00 |
CORE_MID | 5873.50 | 2.50 | 1.00 |
CORE_TOP | 5940.67 | 0.67 | 0.67 |
PERIMETER_BOT_ZN_3 | 5943.00 | 175.17 | 175.17 |
PERIMETER_BOT_ZN_2 | 5943.00 | 335.67 | 335.67 |
PERIMETER_BOT_ZN_1 | 5943.00 | 342.83 | 342.83 |
PERIMETER_BOT_ZN_4 | 5943.00 | 857.83 | 857.83 |
PERIMETER_MID_ZN_3 | 5942.17 | 225.50 | 225.50 |
PERIMETER_MID_ZN_2 | 5034.00 | 527.33 | 527.33 |
PERIMETER_MID_ZN_1 | 5943.00 | 398.17 | 398.17 |
PERIMETER_MID_ZN_4 | 5943.00 | 479.67 | 479.67 |
PERIMETER_TOP_ZN_3 | 5932.33 | 423.00 | 422.83 |
PERIMETER_TOP_ZN_2 | 5942.17 | 644.00 | 644.00 |
PERIMETER_TOP_ZN_1 | 5943.00 | 536.50 | 536.50 |
PERIMETER_TOP_ZN_4 | 5939.83 | 569.00 | 569.00 |
DATACENTER_BOT_ZN_6 | 5943.00 | 2501.00 | 2501.00 |
DATACENTER_MID_ZN_6 | 5943.00 | 192.33 | 192.33 |
DATACENTER_TOP_ZN_6 | 5943.00 | 851.83 | 851.83 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 110.83 | 0.00 | 4.83 |
CORE_BOTTOM | 0.00 | 0.50 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 32.67 | 0.00 | 18.67 |
PERIMETER_BOT_ZN_2 | 0.00 | 51.33 | 0.00 | 46.17 |
PERIMETER_BOT_ZN_1 | 0.00 | 80.33 | 0.00 | 67.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 361.00 | 0.00 | 124.33 |
PERIMETER_MID_ZN_3 | 0.00 | 16.67 | 0.00 | 12.67 |
PERIMETER_MID_ZN_2 | 0.00 | 68.00 | 0.00 | 66.33 |
PERIMETER_MID_ZN_1 | 0.00 | 99.83 | 0.00 | 96.67 |
PERIMETER_MID_ZN_4 | 0.00 | 98.33 | 0.00 | 54.67 |
PERIMETER_TOP_ZN_3 | 0.00 | 63.00 | 0.00 | 46.17 |
PERIMETER_TOP_ZN_2 | 0.00 | 123.83 | 0.00 | 109.17 |
PERIMETER_TOP_ZN_1 | 0.00 | 106.00 | 0.00 | 89.50 |
PERIMETER_TOP_ZN_4 | 0.00 | 131.83 | 0.00 | 74.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 9.17 | 0.00 | 8.50 |
DATACENTER_MID_ZN_6 | 0.00 | 19.00 | 0.00 | 18.83 |
DATACENTER_TOP_ZN_6 | 0.00 | 25.33 | 0.00 | 20.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 736.17 | 0.00 | 353.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.531 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.478 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.452 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.452 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.683 | 0.007 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.750 | 0.007 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.740 | 0.007 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 1.138 | 0.007 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.697 | 0.017 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.817 | 0.018 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.774 | 0.017 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.922 | 0.017 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.683 | 0.021 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.849 | 0.021 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.761 | 0.021 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.895 | 0.021 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.580 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.580 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.580 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 60.99 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 0.847 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.86 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.011 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.79 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.110 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.011 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 783.68 | 0.239 | ||
Total Facility | 1010.73 | 2493.19 | 126016.35 | 46320.38 | 1.3878 | 157.549 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 24193995.66 | 0.00 | 24193995.66 | 0.00 | 24193995.66 | 29876159.83 | 3160.43 | 504.00 | 5095.57 | 819.52 |
CORE_BOTTOM | 25335461.39 | 0.00 | 25335461.39 | 0.00 | 25335461.39 | 33990283.35 | 8729.18 | 5.35 | 25.47 | 1721.64 |
CORE_MID | 0.21E+09 | 0.00 | 0.21E+09 | 0.00 | 0.21E+09 | 0.34E+09 | 8695.79 | 37.91 | 26.30 | 728.03 |
CORE_TOP | 21035083.93 | 0.00 | 21035083.93 | 0.00 | 21035083.93 | 33990283.35 | 8739.48 | 3.54 | 16.98 | 853.82 |
PERIMETER_BOT_ZN_3 | 4204000.35 | 0.00 | 4204000.35 | 64330.56 | 4268330.92 | 4267819.30 | 4406.78 | 20.27 | 4332.94 | 1721.64 |
PERIMETER_BOT_ZN_2 | 2981832.96 | 0.00 | 2981832.96 | 42887.01 | 3024719.97 | 2750345.05 | 1710.11 | 37.03 | 7012.86 | 1721.64 |
PERIMETER_BOT_ZN_1 | 4493787.60 | 0.00 | 4493787.60 | 64330.56 | 4558118.17 | 4267912.63 | 4266.38 | 11.43 | 4482.19 | 1721.64 |
PERIMETER_BOT_ZN_4 | 4533385.28 | 0.00 | 4533385.28 | 42887.01 | 4576272.30 | 2750345.05 | 1589.44 | 0.09 | 7170.47 | 1721.64 |
PERIMETER_MID_ZN_3 | 38026993.56 | 0.00 | 38026993.56 | 150869.21 | 38177862.77 | 42678193.03 | 4419.08 | 79.67 | 4261.25 | 728.03 |
PERIMETER_MID_ZN_2 | 29794257.10 | 0.00 | 29794257.10 | 100579.41 | 29894836.51 | 27503450.52 | 2902.24 | 2.45 | 5855.30 | 1637.03 |
PERIMETER_MID_ZN_1 | 41864318.20 | 0.00 | 41864318.20 | 150869.21 | 42015187.42 | 42679126.28 | 4316.33 | 13.60 | 4430.08 | 728.03 |
PERIMETER_MID_ZN_4 | 32500388.66 | 0.00 | 32500388.66 | 100579.41 | 32600968.07 | 27503450.52 | 2892.28 | 0.33 | 5867.40 | 728.03 |
PERIMETER_TOP_ZN_3 | 3800414.26 | 0.00 | 3800414.26 | 187315.26 | 3987729.52 | 4267819.30 | 4426.03 | 16.78 | 4317.19 | 853.82 |
PERIMETER_TOP_ZN_2 | 3020845.89 | 0.00 | 3020845.89 | 124876.75 | 3145722.64 | 2750345.05 | 2745.62 | 2.06 | 6012.32 | 853.82 |
PERIMETER_TOP_ZN_1 | 4193059.41 | 0.00 | 4193059.41 | 187315.26 | 4380374.67 | 4267912.63 | 4240.35 | 19.93 | 4499.72 | 853.82 |
PERIMETER_TOP_ZN_4 | 3241033.68 | 0.00 | 3241033.68 | 124876.75 | 3365910.43 | 2750345.05 | 2737.32 | 0.25 | 6022.43 | 853.82 |
DATACENTER_BOT_ZN_6 | 492995.74 | 0.00 | 492995.74 | 0.00 | 492995.74 | 389144.62 | 0.00 | 504.00 | 8256.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929957.41 | 0.00 | 4929957.41 | 0.00 | 4929957.41 | 3891446.16 | 0.00 | 504.00 | 8256.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492995.74 | 0.00 | 492995.74 | 0.00 | 492995.74 | 389144.62 | 0.00 | 504.00 | 8256.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8423799.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 0.36E+10 | 0.00 | 0.36E+10 | 5867791.55 | 0.36E+10 | 0.50E+10 | 8760.00 | 693.34 | 8760.00 | 3726.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9653 | 0.0000 | 0.9653 | 0.0000 | 0.9653 | 0.9949 | 1162.95 | 504.00 | 4276.05 |
CORE_BOTTOM | 0.8795 | 0.0000 | 0.8795 | 0.0000 | 0.8795 | 1.0778 | 5915.58 | 5.05 | 22.37 |
CORE_MID | 8.3116 | 0.0000 | 8.3116 | 0.0000 | 8.3116 | 10.7782 | 5895.05 | 26.88 | 21.07 |
CORE_TOP | 0.8319 | 0.0000 | 0.8319 | 0.0000 | 0.8319 | 1.0778 | 5926.69 | 3.16 | 13.15 |
PERIMETER_BOT_ZN_3 | 0.1576 | 0.0000 | 0.1576 | 0.0016 | 0.1593 | 0.1353 | 1634.79 | 18.14 | 4290.07 |
PERIMETER_BOT_ZN_2 | 0.1117 | 0.0000 | 0.1117 | 0.0011 | 0.1128 | 0.0872 | 596.14 | 28.47 | 5318.38 |
PERIMETER_BOT_ZN_1 | 0.1710 | 0.0000 | 0.1710 | 0.0016 | 0.1727 | 0.1353 | 1502.98 | 9.71 | 4430.31 |
PERIMETER_BOT_ZN_4 | 0.1693 | 0.0000 | 0.1693 | 0.0011 | 0.1704 | 0.0872 | 494.07 | 0.09 | 5448.83 |
PERIMETER_MID_ZN_3 | 1.6099 | 0.0000 | 1.6099 | 0.0038 | 1.6137 | 1.3533 | 1657.49 | 61.45 | 4224.05 |
PERIMETER_MID_ZN_2 | 1.2165 | 0.0000 | 1.2165 | 0.0027 | 1.2192 | 0.8721 | 809.66 | 1.94 | 4222.40 |
PERIMETER_MID_ZN_1 | 1.7870 | 0.0000 | 1.7870 | 0.0038 | 1.7908 | 1.3533 | 1551.23 | 9.49 | 4382.28 |
PERIMETER_MID_ZN_4 | 1.3716 | 0.0000 | 1.3716 | 0.0025 | 1.3741 | 0.8721 | 803.27 | 0.24 | 5139.49 |
PERIMETER_TOP_ZN_3 | 0.1578 | 0.0000 | 0.1578 | 0.0047 | 0.1625 | 0.1353 | 1673.08 | 14.81 | 4255.11 |
PERIMETER_TOP_ZN_2 | 0.1264 | 0.0000 | 0.1264 | 0.0032 | 0.1296 | 0.0872 | 779.77 | 1.86 | 5161.36 |
PERIMETER_TOP_ZN_1 | 0.1758 | 0.0000 | 0.1758 | 0.0047 | 0.1806 | 0.1353 | 1500.53 | 13.45 | 4429.02 |
PERIMETER_TOP_ZN_4 | 0.1331 | 0.0000 | 0.1331 | 0.0032 | 0.1363 | 0.0872 | 774.02 | 0.19 | 5168.78 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0130 | 0.00 | 504.00 | 5439.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1296 | 0.00 | 504.00 | 5439.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0130 | 0.00 | 504.00 | 5439.00 |
DATACENTER_BASEMENT_ZN_6 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.2805 | 5943.00 | 0.00 | 0.00 |
Total Facility | 148.4400 | 0.0000 | 148.4400 | 0.1502 | 148.5902 | 157.9346 | 5943.00 | 655.43 | 5943.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 60188813.76 | 0.00 | 60188813.76 | 48026705.38 | 1588.13 | 0.00 | 7171.87 | 1721.64 |
VAV_MID WITH REHEAT | 0.50E+09 | 0.00 | 0.50E+09 | 0.48E+09 | 2887.86 | 0.00 | 5872.14 | 728.03 |
VAV_TOP WITH REHEAT | 51123172.08 | 0.00 | 51123172.08 | 48026705.38 | 2734.78 | 0.00 | 6025.22 | 853.82 |
CAV_BAS | 35048411.15 | 0.00 | 35048411.15 | 29876159.83 | 3160.43 | 0.00 | 5599.57 | 819.52 |
AIRLOOP DATACENTER BOT | 714173.78 | 0.00 | 714173.78 | 389144.62 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 7141737.84 | 0.00 | 7141737.84 | 3891446.16 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 714173.78 | 0.00 | 714173.78 | 389144.62 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.1573 | 0.0000 | 2.1573 | 1.5229 | 492.77 | 0.00 | 5450.23 |
VAV_MID WITH REHEAT | 20.7846 | 0.0000 | 20.7846 | 15.2292 | 798.89 | 0.00 | 5144.11 |
VAV_TOP WITH REHEAT | 2.0643 | 0.0000 | 2.0643 | 1.5229 | 771.60 | 0.00 | 5171.40 |
CAV_BAS | 1.3984 | 0.0000 | 1.3984 | 0.9949 | 1162.95 | 0.00 | 4780.05 |
AIRLOOP DATACENTER BOT | 0.0226 | 0.0000 | 0.0226 | 0.0130 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2265 | 0.0000 | 0.2265 | 0.1296 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0226 | 0.0000 | 0.0226 | 0.0130 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7171.87 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5872.14 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6025.22 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 5599.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.3524 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 24.0130 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.3725 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7387 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2265 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 7 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1358 |
Defaulted Fields | 1168 |
Fields with Defaults | 3880 |
Autosized Fields | 317 |
Autosizable Fields | 394 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 28664.05 | 303411.52 | 28-JAN-04:40 | 1679076.92 | 09-AUG-07:50 |
Electricity:Building | 16695.51 | 216891.80 | 29-MAY-17:10 | 969176.01 | 18-DEC-17:00 |
Electricity:Zone:BASEMENT | 559.97 | 14115.26 | 01-JAN-00:10 | 25295.37 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16695.51 | 216891.80 | 29-MAY-17:10 | 969176.01 | 18-DEC-17:00 |
InteriorLights:Electricity | 2019.12 | 9514.02 | 01-JAN-09:30 | 190804.33 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:BASEMENT | 135.58 | 657.72 | 01-JAN-00:10 | 11837.83 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2019.12 | 9514.02 | 01-JAN-09:30 | 190804.33 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity | 2019.12 | 9514.02 | 01-JAN-09:30 | 190804.33 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 135.58 | 657.72 | 01-JAN-00:10 | 11837.83 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2019.12 | 9514.02 | 01-JAN-09:30 | 190804.33 | 18-DEC-17:00 |
Electricity:Zone:CORE_BOTTOM | 411.37 | 5043.91 | 01-JAN-00:10 | 27837.83 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4113.71 | 50438.97 | 01-JAN-00:10 | 278377.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1217.58 | 5906.80 | 01-JAN-00:10 | 106312.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1217.58 | 5906.80 | 01-JAN-00:10 | 106312.04 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 411.37 | 5043.90 | 01-JAN-00:10 | 27837.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 45.12 | 594.46 | 28-MAY-17:10 | 3311.28 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.75 | 35.29 | 01-JAN-09:10 | 1150.73 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.75 | 35.29 | 01-JAN-09:10 | 1150.73 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 29.11 | 386.47 | 25-JUN-17:10 | 2143.85 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.67 | 22.74 | 01-JAN-07:20 | 751.51 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.67 | 22.74 | 01-JAN-07:20 | 751.51 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 45.08 | 598.24 | 26-MAR-17:10 | 3274.60 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.72 | 35.29 | 01-JAN-08:00 | 1114.01 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.72 | 35.29 | 01-JAN-08:00 | 1114.01 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 29.05 | 383.09 | 12-MAR-17:10 | 2089.99 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.62 | 22.74 | 01-JAN-09:30 | 697.66 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.62 | 22.74 | 01-JAN-09:30 | 697.66 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 451.17 | 5944.59 | 28-MAY-17:10 | 33151.82 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 87.51 | 352.88 | 01-JAN-09:00 | 11546.30 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 87.51 | 352.88 | 01-JAN-09:00 | 11546.30 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 291.05 | 3892.62 | 25-JUN-17:10 | 21440.96 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 56.70 | 227.41 | 01-JAN-07:20 | 7517.54 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 56.70 | 227.41 | 01-JAN-07:20 | 7517.54 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 450.82 | 5980.99 | 26-MAR-17:10 | 32757.79 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 87.16 | 352.89 | 01-JAN-07:50 | 11151.94 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 87.16 | 352.89 | 01-JAN-07:50 | 11151.94 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 290.52 | 3830.90 | 12-MAR-17:10 | 20908.73 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 56.16 | 227.41 | 01-JAN-09:30 | 6985.41 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 56.16 | 227.41 | 01-JAN-09:30 | 6985.41 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 45.12 | 594.46 | 28-MAY-17:10 | 3315.01 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.75 | 35.29 | 01-JAN-09:00 | 1154.45 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.75 | 35.29 | 01-JAN-09:00 | 1154.45 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 29.11 | 389.26 | 25-JUN-17:10 | 2143.99 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.67 | 22.74 | 01-JAN-07:20 | 751.65 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.67 | 22.74 | 01-JAN-07:20 | 751.65 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 45.08 | 598.09 | 26-MAR-17:10 | 3275.61 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.72 | 35.29 | 01-JAN-07:50 | 1115.02 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.72 | 35.29 | 01-JAN-07:50 | 1115.02 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 29.05 | 383.09 | 12-MAR-17:10 | 2090.79 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.62 | 22.74 | 01-JAN-09:30 | 698.45 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.62 | 22.74 | 01-JAN-09:30 | 698.45 | 18-DEC-17:00 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7533.08 | 95093.58 | 01-JAN-00:10 | 382970.28 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 38.23 | 185.45 | 01-JAN-00:10 | 3337.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 38.23 | 185.45 | 01-JAN-00:10 | 3337.76 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.14 | 1964.44 | 01-JAN-00:10 | 8079.39 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1571.44 | 19644.38 | 01-JAN-00:10 | 80793.90 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 32.64 | 158.32 | 01-JAN-00:10 | 2849.68 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 32.64 | 158.32 | 01-JAN-00:10 | 2849.68 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.14 | 1964.44 | 01-JAN-00:10 | 8079.39 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 6159.55 | 13146.36 | 01-JAN-00:50 | 410766.89 | 15-FEB-13:10 |
HeatRejection:Electricity | 1351.90 | 12476.23 | 01-JAN-00:50 | 58053.77 | 09-JAN-21:10 |
General:HeatRejection:Electricity | 1351.90 | 12476.23 | 01-JAN-00:50 | 58053.77 | 09-JAN-21:10 |
Electricity:HVAC | 2212.63 | 12503.63 | 28-JAN-06:00 | 190129.70 | 27-APR-14:50 |
ExteriorEquipment:Electricity | 3333.11 | 46194.44 | 01-JAN-00:10 | 188982.90 | 21-AUG-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.48 | 979.82 | 01-JAN-00:10 | 3382.54 | 18-DEC-17:00 |
ElectricityPurchased:Facility | 28664.05 | 303411.52 | 28-JAN-04:40 | 1679076.92 | 09-AUG-07:50 |
ElectricityPurchased:Plant | 28664.05 | 303411.52 | 28-JAN-04:40 | 1679076.92 | 09-AUG-07:50 |
Cogeneration:ElectricityPurchased | 28664.05 | 303411.52 | 28-JAN-04:40 | 1679076.92 | 09-AUG-07:50 |
General:Cogeneration:ElectricityPurchased | 28664.05 | 303411.52 | 28-JAN-04:40 | 1679076.92 | 09-AUG-07:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 28664.05 | 303411.52 | 28-JAN-04:40 | 1679076.92 | 09-AUG-07:50 |
ElectricityNet:Plant | 28664.05 | 303411.52 | 28-JAN-04:40 | 1679076.92 | 09-AUG-07:50 |
Cogeneration:ElectricityNet | 28664.05 | 303411.52 | 28-JAN-04:40 | 1679076.92 | 09-AUG-07:50 |
General:Cogeneration:ElectricityNet | 28664.05 | 303411.52 | 28-JAN-04:40 | 1679076.92 | 09-AUG-07:50 |
Fans:Electricity | 1482.47 | 5884.98 | 01-JAN-00:50 | 150562.08 | 27-APR-14:50 |
General:Fans:Electricity | 1482.47 | 5884.98 | 01-JAN-00:50 | 150562.08 | 27-APR-14:50 |
ExteriorLights:Electricity | 317.72 | 0.00 | 01-JAN-06:20 | 37611.08 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 317.72 | 0.00 | 01-JAN-06:20 | 37611.08 | 01-JAN-06:10 |
ComputerHVAC:ExteriorEquipment:Electricity | 1424.02 | 18032.55 | 01-JAN-00:10 | 72130.20 | 31-MAR-23:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 128.45 | 0.00 | 01-JAN-00:40 | 5613.48 | 01-JAN-07:40 |
General:HeatRecovery:Electricity | 128.45 | 0.00 | 01-JAN-00:40 | 5613.48 | 01-JAN-07:40 |
Cooling:Electricity | 3964.96 | 5543.75 | 24-JAN-04:50 | 307770.32 | 12-DEC-13:50 |
General:Cooling:Electricity | 3964.96 | 5543.75 | 24-JAN-04:50 | 307770.32 | 12-DEC-13:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 1389.92 | 670.13 | 01-JAN-00:50 | 71801.86 | 21-FEB-16:00 |
General:Pumps:Electricity | 1389.92 | 670.13 | 01-JAN-00:50 | 71801.86 | 21-FEB-16:00 |
WIRED_LTG_ELECTRICITY | 56.74 | 0.00 | 01-JAN-00:10 | 5361.60 | 18-DEC-17:10 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 527.15 | 5695.87 | 01-JAN-00:10 | 60220.58 | 29-DEC-13:00 |
NaturalGas:Plant | 527.15 | 5695.87 | 01-JAN-00:10 | 60220.58 | 29-DEC-13:00 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:NaturalGas | 527.15 | 5695.87 | 01-JAN-00:10 | 60220.58 | 29-DEC-13:00 |
Water Heater:WaterSystems:NaturalGas | 527.15 | 5695.87 | 01-JAN-00:10 | 60220.58 | 29-DEC-13:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 25319.76 | 29519.86 | 28-JAN-06:00 | 1896891.82 | 18-SEP-05:10 |
PlantLoopCoolingDemand:HVAC | 25319.76 | 29519.86 | 28-JAN-06:00 | 1896891.82 | 18-SEP-05:10 |
CoolingCoils:PlantLoopCoolingDemand | 25319.76 | 29519.86 | 28-JAN-06:00 | 1896891.82 | 18-SEP-05:10 |
DistrictCooling:Facility | 7226.18 | 89455.44 | 07-JAN-19:40 | 370785.23 | 14-AUG-14:00 |
DistrictCooling:HVAC | 7226.18 | 89455.44 | 07-JAN-19:40 | 370785.23 | 14-AUG-14:00 |
Cooling:DistrictCooling | 7226.18 | 89455.44 | 07-JAN-19:40 | 370785.23 | 14-AUG-14:00 |
General:Cooling:DistrictCooling | 7226.18 | 89455.44 | 07-JAN-19:40 | 370785.23 | 14-AUG-14:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 19882.85 | 0.00 | 01-JAN-00:50 | 0.00 | 21-MAR-13:00 |
Water:Plant | 19882.85 | 0.00 | 01-JAN-00:50 | 0.00 | 21-MAR-13:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 19882.85 | 0.00 | 01-JAN-00:50 | 0.00 | 21-MAR-13:00 |
MainsWater:Plant | 19882.85 | 0.00 | 01-JAN-00:50 | 0.00 | 21-MAR-13:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 17602.68 | 0.00 | 01-JAN-00:50 | 0.00 | 21-MAR-13:00 |
General:HeatRejection:Water | 17602.68 | 0.00 | 01-JAN-00:50 | 0.00 | 21-MAR-13:00 |
HeatRejection:MainsWater | 17602.68 | 0.00 | 01-JAN-00:50 | 0.00 | 21-MAR-13:00 |
General:HeatRejection:MainsWater | 17602.68 | 0.00 | 01-JAN-00:50 | 0.00 | 21-MAR-13:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 126652.05 | 131235.65 | 28-JAN-06:00 | 9460635.81 | 15-JUN-10:00 |
EnergyTransfer:Building | 22839.45 | 105755.66 | 16-SEP-17:20 | 1475061.74 | 26-DEC-15:10 |
EnergyTransfer:Zone:BASEMENT | 726.14 | 0.00 | 01-JAN-00:10 | 67334.67 | 02-JAN-08:20 |
Heating:EnergyTransfer | 10.96 | 0.00 | 01-JAN-00:30 | 20097.35 | 06-MAY-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 6.62 | 0.00 | 01-JAN-00:10 | 20097.35 | 06-MAY-16:10 |
General:Heating:EnergyTransfer | 10.96 | 0.00 | 01-JAN-00:30 | 20097.35 | 06-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 6.62 | 0.00 | 01-JAN-00:10 | 20097.35 | 06-MAY-16:10 |
Cooling:EnergyTransfer | 22828.50 | 105755.66 | 16-SEP-17:20 | 1475061.74 | 26-DEC-15:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 719.52 | 0.00 | 01-JAN-00:10 | 67334.67 | 02-JAN-08:20 |
General:Cooling:EnergyTransfer | 22828.50 | 105755.66 | 16-SEP-17:20 | 1475061.74 | 26-DEC-15:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 719.52 | 0.00 | 01-JAN-00:10 | 67334.67 | 02-JAN-08:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 763.23 | 0.00 | 01-JAN-00:40 | 51251.64 | 26-DEC-10:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 763.23 | 0.00 | 01-JAN-00:40 | 51251.64 | 26-DEC-10:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 763.23 | 0.00 | 01-JAN-00:40 | 51251.64 | 26-DEC-10:10 |
EnergyTransfer:Zone:CORE_MID | 5607.75 | 0.00 | 01-JAN-00:10 | 437410.73 | 02-JAN-08:40 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5607.75 | 0.00 | 01-JAN-00:10 | 437410.73 | 02-JAN-08:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5607.75 | 0.00 | 01-JAN-00:10 | 437410.73 | 02-JAN-08:40 |
EnergyTransfer:Zone:CORE_TOP | 632.12 | 0.00 | 01-JAN-00:10 | 47901.52 | 20-MAR-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 632.12 | 0.00 | 01-JAN-00:10 | 47901.52 | 20-MAR-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 632.12 | 0.00 | 01-JAN-00:10 | 47901.52 | 20-MAR-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 135.91 | 0.00 | 01-JAN-00:40 | 12176.26 | 12-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 135.91 | 0.00 | 01-JAN-00:40 | 12176.26 | 12-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 135.91 | 0.00 | 01-JAN-00:40 | 12176.26 | 12-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 96.19 | 0.00 | 01-JAN-00:40 | 9536.17 | 20-MAR-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 96.19 | 0.00 | 01-JAN-00:40 | 9536.17 | 20-MAR-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 96.19 | 0.00 | 01-JAN-00:40 | 9536.17 | 20-MAR-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 147.17 | 0.00 | 01-JAN-00:40 | 12924.97 | 26-DEC-12:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 147.17 | 0.00 | 01-JAN-00:40 | 12924.97 | 26-DEC-12:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 147.17 | 0.00 | 01-JAN-00:40 | 12924.97 | 26-DEC-12:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 145.99 | 0.00 | 01-JAN-00:40 | 13460.17 | 18-APR-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 145.99 | 0.00 | 01-JAN-00:40 | 13460.17 | 18-APR-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 145.99 | 0.00 | 01-JAN-00:40 | 13460.17 | 18-APR-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1096.21 | 0.00 | 01-JAN-00:10 | 112747.29 | 12-JUN-15:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1096.21 | 0.00 | 01-JAN-00:10 | 112747.29 | 12-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1096.21 | 0.00 | 01-JAN-00:10 | 112747.29 | 12-JUN-15:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 860.30 | 0.00 | 01-JAN-00:10 | 95884.33 | 05-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 860.30 | 0.00 | 01-JAN-00:10 | 95884.33 | 05-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 860.30 | 0.00 | 01-JAN-00:10 | 95884.33 | 05-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1220.88 | 0.00 | 01-JAN-00:10 | 119760.22 | 07-DEC-14:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1220.88 | 0.00 | 01-JAN-00:10 | 119760.22 | 07-DEC-14:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1220.88 | 0.00 | 01-JAN-00:10 | 119760.22 | 07-DEC-14:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 932.21 | 0.00 | 01-JAN-00:10 | 106344.15 | 18-APR-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 932.21 | 0.00 | 01-JAN-00:10 | 106344.15 | 18-APR-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 932.21 | 0.00 | 01-JAN-00:10 | 106344.15 | 18-APR-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 121.33 | 0.00 | 01-JAN-00:10 | 12980.72 | 12-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 121.33 | 0.00 | 01-JAN-00:10 | 12980.72 | 12-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 121.33 | 0.00 | 01-JAN-00:10 | 12980.72 | 12-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 96.14 | 0.00 | 01-JAN-00:10 | 10039.20 | 05-MAY-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 96.14 | 0.00 | 01-JAN-00:10 | 10039.20 | 05-MAY-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 96.14 | 0.00 | 01-JAN-00:10 | 10039.20 | 05-MAY-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 134.86 | 0.00 | 01-JAN-00:10 | 13868.98 | 07-DEC-14:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 134.86 | 0.00 | 01-JAN-00:10 | 13868.98 | 07-DEC-14:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 134.86 | 0.00 | 01-JAN-00:10 | 13868.98 | 07-DEC-14:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 102.35 | 0.00 | 01-JAN-00:10 | 11624.35 | 18-APR-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 102.35 | 0.00 | 01-JAN-00:10 | 11624.35 | 18-APR-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 102.35 | 0.00 | 01-JAN-00:10 | 11624.35 | 18-APR-15:30 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 115.59 | 0.00 | 01-JAN-00:40 | 10815.84 | 02-JAN-06:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.56 | 0.00 | 01-JAN-00:20 | 1736.97 | 17-SEP-07:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.56 | 0.00 | 01-JAN-00:20 | 1736.97 | 17-SEP-07:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 115.03 | 0.00 | 01-JAN-00:40 | 10815.84 | 02-JAN-06:30 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 115.03 | 0.00 | 01-JAN-00:40 | 10815.84 | 02-JAN-06:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 894.53 | 0.00 | 01-JAN-00:10 | 96344.54 | 02-JAN-06:30 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 3.37 | 0.00 | 01-JAN-00:10 | 16986.96 | 20-AUG-14:00 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 3.37 | 0.00 | 01-JAN-00:10 | 16986.96 | 20-AUG-14:00 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 891.16 | 0.00 | 01-JAN-00:10 | 96344.54 | 02-JAN-06:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 891.16 | 0.00 | 01-JAN-00:10 | 96344.54 | 02-JAN-06:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 171.02 | 0.00 | 01-JAN-00:10 | 21671.90 | 11-APR-13:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 0.40 | 0.00 | 01-JAN-00:10 | 3064.93 | 27-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 0.40 | 0.00 | 01-JAN-00:10 | 3064.93 | 27-DEC-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 170.62 | 0.00 | 01-JAN-00:10 | 21671.90 | 11-APR-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 170.62 | 0.00 | 01-JAN-00:10 | 21671.90 | 11-APR-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.31 | 1473.02 | 16-SEP-07:00 | 7856.02 | 25-DEC-17:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.31 | 1473.02 | 16-SEP-07:00 | 7856.02 | 25-DEC-17:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.31 | 1473.02 | 16-SEP-07:00 | 7856.02 | 25-DEC-17:20 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1357.35 | 12867.73 | 16-SEP-07:00 | 73661.21 | 25-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1357.35 | 12867.73 | 16-SEP-07:00 | 73661.21 | 25-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1357.35 | 12867.73 | 16-SEP-07:00 | 73661.21 | 25-DEC-17:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 137.16 | 1212.72 | 16-SEP-07:00 | 7613.78 | 24-DEC-17:10 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 137.16 | 1212.72 | 16-SEP-07:00 | 7613.78 | 24-DEC-17:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 137.16 | 1212.72 | 16-SEP-07:00 | 7613.78 | 24-DEC-17:10 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7201.69 | 89450.35 | 07-JAN-19:10 | 368142.12 | 28-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7201.69 | 89450.35 | 07-JAN-19:10 | 368142.12 | 28-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7201.69 | 89450.35 | 07-JAN-19:10 | 368142.12 | 28-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 267.17 | 0.00 | 01-JAN-00:10 | 30859.47 | 10-JAN-12:20 |
PlantLoopHeatingDemand:Plant | 267.17 | 0.00 | 01-JAN-00:10 | 30859.47 | 10-JAN-12:20 |
WaterSystems:PlantLoopHeatingDemand | 267.17 | 0.00 | 01-JAN-00:10 | 30859.47 | 10-JAN-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 267.17 | 0.00 | 01-JAN-00:10 | 30859.47 | 10-JAN-12:20 |
EnergyTransfer:HVAC | 31769.46 | 23882.36 | 28-JAN-06:00 | 2572116.02 | 15-JUN-10:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatingCoils:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 24772.53 | 23882.36 | 28-JAN-06:00 | 1889097.23 | 18-SEP-05:10 |
DistrictHeating:Facility | 0.00 | 0.00 | 01-JAN-00:30 | 14.83 | 31-OCT-23:30 |
DistrictHeating:HVAC | 0.00 | 0.00 | 01-JAN-00:30 | 14.83 | 31-OCT-23:30 |
Heating:DistrictHeating | 0.00 | 0.00 | 01-JAN-00:30 | 14.83 | 31-OCT-23:30 |
General:Heating:DistrictHeating | 0.00 | 0.00 | 01-JAN-00:30 | 14.83 | 31-OCT-23:30 |
HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 27-FEB-06:50 |
HeatRecoveryForCooling:EnergyTransfer | 6996.93 | 0.00 | 01-JAN-00:10 | 764554.79 | 30-SEP-11:00 |
EnergyTransfer:Plant | 72043.13 | 0.00 | 01-JAN-00:50 | 5916211.60 | 06-FEB-13:20 |
LoopToLoop:EnergyTransfer | 24603.15 | 0.00 | 01-JAN-00:50 | 1994338.39 | 18-SEP-05:10 |
WaterSystems:EnergyTransfer | 267.17 | 0.00 | 01-JAN-00:10 | 30859.47 | 10-JAN-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 267.17 | 0.00 | 01-JAN-00:10 | 30859.47 | 10-JAN-12:20 |
Boilers:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Chillers:EnergyTransfer | 21877.55 | 0.00 | 01-JAN-00:50 | 1873699.89 | 06-FEB-13:20 |
HeatRejection:EnergyTransfer | 25295.27 | 0.00 | 01-JAN-00:50 | 2151544.60 | 06-FEB-13:20 |
General:HeatRejection:EnergyTransfer | 25295.27 | 0.00 | 01-JAN-00:50 | 2151544.60 | 06-FEB-13:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 6.624 | -719.498 | 0.000 | 0.000 | 92.565 | 135.577 | 424.397 | 0.000 | 0.000 | 0.000 | 60.335 | 0.000 | 0.000 | 0.000 | 0.000 | -0.010 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -763.233 | 0.000 | 0.000 | 83.451 | 121.758 | 289.614 | 0.000 | 0.000 | 0.000 | 268.410 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5607.732 | 0.000 | 0.000 | 835.039 | 1217.578 | 2896.128 | 0.000 | 0.000 | 0.000 | 658.988 | 0.000 | 0.000 | 0.000 | 0.000 | -0.008 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -632.117 | 0.000 | 0.000 | 83.448 | 121.758 | 289.613 | 0.000 | 0.000 | 0.000 | 137.299 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -135.913 | 0.000 | 0.000 | 10.456 | 8.750 | 36.365 | 52.338 | 0.000 | 0.215 | 32.877 | 0.000 | -5.064 | 0.000 | -0.025 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -96.186 | 0.000 | 0.000 | 6.740 | 5.672 | 23.435 | 52.647 | 0.000 | 0.148 | 10.489 | 0.000 | -2.930 | 0.000 | -0.014 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -147.173 | 0.000 | 0.000 | 10.441 | 8.717 | 36.366 | 67.295 | 0.000 | 0.212 | 29.352 | 0.000 | -5.182 | 0.000 | -0.029 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -145.985 | 0.000 | 0.000 | 6.726 | 5.618 | 23.435 | 50.958 | 0.000 | 0.126 | 64.505 | 0.000 | -5.352 | 0.000 | -0.030 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -1096.196 | 0.000 | 0.000 | 104.569 | 87.515 | 363.654 | 526.950 | 0.000 | 4.725 | 60.014 | 0.000 | -50.426 | 0.000 | -0.805 | -0.004 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -860.289 | 0.000 | 0.000 | 49.412 | 56.703 | 234.352 | 522.443 | 0.000 | 3.060 | 28.823 | 0.000 | -33.914 | 0.000 | -0.590 | -0.010 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -1220.870 | 0.000 | 0.000 | 104.267 | 87.161 | 363.660 | 674.854 | 0.000 | 4.656 | 39.871 | 0.000 | -52.650 | 0.000 | -0.948 | -0.000 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -932.211 | 0.000 | 0.000 | 67.317 | 56.165 | 234.351 | 519.129 | 0.000 | 2.901 | 95.272 | 0.000 | -42.178 | 0.000 | -0.747 | -0.002 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -121.332 | 0.000 | 0.000 | 10.453 | 8.751 | 36.365 | 51.702 | 0.000 | 0.551 | 19.035 | 0.000 | -5.416 | 0.000 | -0.110 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -96.144 | 0.000 | 0.000 | 6.733 | 5.670 | 23.435 | 51.552 | 0.000 | 0.361 | 12.107 | 0.000 | -3.634 | 0.000 | -0.080 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -134.854 | 0.000 | 0.000 | 10.440 | 8.716 | 36.366 | 66.486 | 0.000 | 0.547 | 18.046 | 0.000 | -5.619 | 0.000 | -0.128 | -0.001 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -102.354 | 0.000 | 0.000 | 6.732 | 5.616 | 23.435 | 51.314 | 0.000 | 0.351 | 19.397 | 0.000 | -4.394 | 0.000 | -0.097 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -143.314 | 0.000 | 0.000 | 0.949 | 3.264 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -14.779 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1357.352 | 0.000 | 0.000 | 9.483 | 32.637 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -223.574 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.000 | -137.161 | 0.000 | 0.000 | 0.949 | 3.264 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -20.933 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | -7201.693 | 0.000 | 0.000 | 0.000 | 0.000 | 20.569 | 38.227 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -351.960 |
GROUNDFLOOR_PLENUM | 0.560 | -115.033 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.392 | 114.141 | 0.000 | 0.000 | 0.000 | -0.060 | -0.000 |
MIDFLOOR_PLENUM | 3.372 | -891.159 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.137 | 881.757 | 0.000 | 0.000 | 0.000 | -1.106 | -0.001 |
TOPFLOOR_PLENUM | 0.402 | -170.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.655 | 169.691 | 0.000 | 0.000 | 0.000 | -0.135 | 0.000 |
Total Facility | 4.334 | -8378.499 | 6.624 | -14449.913 | 0.000 | 0.000 | 1520.739 | 2019.115 | 14676.396 | 2687.668 | 0.000 | 26.036 | 2720.410 | 0.000 | -216.760 | 0.000 | -4.905 | -611.285 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 16-JAN-14:38 | 0.00 | 0.00 | 0.00 | -76479.33 | 0.00 | 0.00 | 399.88 | 657.72 | 13457.54 | 0.00 | 0.00 | 0.00 | 61964.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 23-JAN-04:02 | 0.00 | 0.00 | 0.00 | -80529.97 | 0.00 | 0.00 | 0.00 | 590.68 | 5937.65 | 0.00 | 0.00 | 0.00 | 74001.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:04 | 0.00 | 0.00 | 0.00 | -801448.36 | 0.00 | 0.00 | 0.00 | 5906.80 | 59376.23 | 0.00 | 0.00 | 0.00 | 736165.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 23-OCT-03:02 | 0.00 | 0.00 | 0.00 | -78704.90 | 0.00 | 0.00 | 0.00 | 590.68 | 5937.62 | 0.00 | 0.00 | 0.00 | 72176.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 18-JUN-13:02 | 0.00 | 0.00 | 0.00 | -15609.66 | 0.00 | 0.00 | 40.50 | 35.29 | 720.18 | 6657.84 | 0.00 | 63.25 | 8092.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 26-MAR-09:42 | 0.00 | 0.00 | 0.00 | -14976.45 | 0.00 | 0.00 | 25.07 | 22.74 | 464.11 | 7774.41 | 0.00 | 24.68 | 6665.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 03-DEC-14:12 | 0.00 | 0.00 | 0.00 | -16283.65 | 0.00 | 0.00 | 37.62 | 35.29 | 720.19 | 8980.14 | 0.00 | 11.52 | 6498.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-APR-15:41 | 0.00 | 0.00 | 0.00 | -22509.02 | 0.00 | 0.00 | 19.15 | 22.74 | 464.11 | 9163.42 | 0.00 | 24.70 | 12814.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 11-JUN-15:32 | 0.00 | 0.00 | 0.00 | -147929.27 | 0.00 | 0.00 | 396.86 | 352.88 | 7201.84 | 59867.11 | 0.00 | 1183.42 | 78927.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 26-MAR-09:42 | 0.00 | 0.00 | 0.00 | -156044.66 | 0.00 | 0.00 | 242.80 | 227.41 | 4641.14 | 76586.40 | 0.00 | 540.47 | 73806.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 31-DEC-12:32 | 0.00 | 0.00 | 0.00 | -148929.44 | 0.00 | 0.00 | 377.34 | 352.89 | 7201.95 | 107360.52 | 0.00 | 421.03 | 33215.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 19-MAR-14:51 | 0.00 | 0.00 | 0.00 | -177466.93 | 0.00 | 0.00 | 220.87 | 227.41 | 4641.11 | 100253.57 | 0.00 | 1193.97 | 70930.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 11-JUN-14:02 | 0.00 | 0.00 | 0.00 | -17900.02 | 0.00 | 0.00 | 37.32 | 35.29 | 720.18 | 6442.80 | 0.00 | 169.17 | 10495.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 19-MAR-14:51 | 0.00 | 0.00 | 0.00 | -16037.59 | 0.00 | 0.00 | 24.42 | 22.74 | 464.11 | 2385.65 | 0.00 | 162.74 | 12977.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 19-NOV-13:22 | 0.00 | 0.00 | 0.00 | -17623.74 | 0.00 | 0.00 | 36.38 | 35.29 | 720.19 | 9380.22 | 0.00 | 51.80 | 7399.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 19-MAR-14:51 | 0.00 | 0.00 | 0.00 | -20270.06 | 0.00 | 0.00 | 20.33 | 22.74 | 464.11 | 9903.30 | 0.00 | 136.74 | 9722.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 25-DEC-17:20 | 0.00 | 0.00 | 0.00 | -7857.13 | 0.00 | 0.00 | 5.27 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 41.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 25-DEC-16:52 | 0.00 | 0.00 | 0.00 | -73661.18 | 0.00 | 0.00 | 53.08 | 158.32 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4494.45 |
DATACENTER_TOP_ZN_6 | 24-DEC-17:12 | 0.00 | 0.00 | 0.00 | -7616.45 | 0.00 | 0.00 | 5.30 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -199.11 |
DATACENTER_BASEMENT_ZN_6 | 28-AUG-16:00 | 0.00 | -368142.11 | 0.00 | 0.00 | 0.00 | 0.00 | 2183.10 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17011.27 |
GROUNDFLOOR_PLENUM | 26-DEC-06:13 | 0.00 | -13876.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13882.17 | 0.00 | -0.00 | 0.00 | -5.66 | 0.00 |
MIDFLOOR_PLENUM | 02-JAN-06:15 | 0.00 | -129258.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129258.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 11-APR-13:50 | 0.00 | -21670.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 21629.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 26-APR-05:02 | 0.00 | -411299.31 | 0.00 | -1433374.77 | 0.00 | 0.00 | 16012.07 | 22094.05 | 616289.16 | 203.37 | 0.00 | 166.70 | 1191249.26 | 0.00 | -1340.54 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-MAY-15:02 | 0.00 | 0.00 | 24607.19 | 0.00 | 0.00 | 0.00 | 1040.25 | 1973.00 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -41077.98 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 19-SEP-03:02 | 6579.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7.36 | -6572.16 |
MIDFLOOR_PLENUM | 18-SEP-03:02 | 62297.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -13.97 | -62283.61 |
TOPFLOOR_PLENUM | 21-DEC-06:02 | 10871.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -27.31 | -10843.94 |
Total Facility | 18-SEP-03:02 | -1453428.36 | 1435124.54 | 0.00 | -1435124.54 | 0.00 | 0.00 | 0.00 | 11048.40 | 232425.23 | 0.00 | 0.00 | 0.00 | 1230609.19 | 0.00 | -20596.76 | 0.00 | -57.69 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 9.0048 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.5223 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 83.2625 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 78.6886 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 8.9047 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.6405 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.0196 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.0196 | 0.2391 | 1.0000 | Not calculated | 1.2002 | 0.2391 | ||
AIRLOOP DATACENTER BOT | 0.4582 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4582 | 0.0341 | 1.0000 | Not calculated | 0.0156 | 0.0341 | ||
AIRLOOP DATACENTER MID | 4.3521 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.3521 | 0.0359 | 1.0000 | Not calculated | 0.1563 | 0.0359 | ||
AIRLOOP DATACENTER TOP | 0.4436 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4436 | 0.0352 | 1.0000 | Not calculated | 0.0156 | 0.0352 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 4.5024 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.7236 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 41.6312 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 26.3061 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.4524 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.7232 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.0196 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.0196 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2391 | ||
AIRLOOP DATACENTER BOT | 0.4582 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4582 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0341 | ||
AIRLOOP DATACENTER MID | 4.3521 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.3521 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0359 | ||
AIRLOOP DATACENTER TOP | 0.4436 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4436 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0352 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.002360 | 149.6021 | 0.000305 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.002360 | 1.9486 | 0.000305 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.002360 | 19.4861 | 0.000305 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.002360 | 1.9486 | 0.000305 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.002360 | 149.60 | 0.000305 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BOT | 0.002360 | 1.95 | 0.000305 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.002360 | 19.49 | 0.000305 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.002360 | 1.95 | 0.000305 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0196 | 5.0196 | 5.0196 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2712 | 5.2712 | 1.8607 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 49.2131 | 49.2131 | 18.1596 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0654 | 5.0654 | 1.8691 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8902 | 0.8902 | 0.2341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8439 | 0.8439 | 0.1688 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8707 | 0.8707 | 0.2342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1288 | 1.1288 | 0.2258 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.1779 | 8.1779 | 2.2816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.5938 | 8.5938 | 1.7188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.9375 | 7.9375 | 2.2781 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.3402 | 9.3402 | 1.8680 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9729 | 0.9729 | 0.2345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8837 | 0.8837 | 0.1767 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9446 | 0.9446 | 0.2352 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0380 | 1.0380 | 0.2076 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4582 | 0.4582 | 0.4582 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.3521 | 4.3521 | 4.3521 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4436 | 0.4436 | 0.4436 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 9.0048 | 8.5223 | 9.0048 | 2.7236 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 83.2625 | 78.6886 | 83.2625 | 26.3061 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 8.9047 | 8.6405 | 8.9047 | 2.7232 | 0.0000 | 1.0000 |
CAV_BAS | 5.0196 | 5.0196 | 5.0196 | 5.0196 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4582 | 0.4582 | 0.4582 | 0.4582 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.3521 | 4.3521 | 4.3521 | 4.3521 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4436 | 0.4436 | 0.4436 | 0.4436 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0196 | 5.0196 | 5.0196 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6356 | 2.6356 | 1.8607 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 24.6066 | 24.6066 | 18.1596 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5327 | 2.5327 | 1.8691 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4451 | 0.4451 | 0.2341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4220 | 0.4220 | 0.1688 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4353 | 0.4353 | 0.2342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5644 | 0.5644 | 0.2258 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.0890 | 4.0890 | 2.2816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.2969 | 4.2969 | 1.7188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.9687 | 3.9687 | 2.2781 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.6701 | 4.6701 | 1.8680 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4864 | 0.4864 | 0.2345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4419 | 0.4419 | 0.1767 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4723 | 0.4723 | 0.2352 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5190 | 0.5190 | 0.2076 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4582 | 0.4582 | 0.4582 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.3521 | 4.3521 | 4.3521 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4436 | 0.4436 | 0.4436 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 4.5024 | 2.7236 | 2.7236 | 2.7236 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 41.6312 | 26.3061 | 26.3061 | 26.3061 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.4524 | 2.7232 | 2.7232 | 2.7232 | 0.0000 | 1.0000 |
CAV_BAS | 5.0196 | 5.0196 | 5.0196 | 5.0196 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4582 | 0.4582 | 0.4582 | 0.4582 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.3521 | 4.3521 | 4.3521 | 4.3521 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4436 | 0.4436 | 0.4436 | 0.4436 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | District Heat |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 353.33 |
Number of hours not met | 353.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 |
Heating -- Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3964.96 | 307770.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7226.18 | 370785.23 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2019.12 | 190804.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 317.72 | 37611.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.48 | 3382.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ComputerHVAC | 1424.02 | 72130.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 1482.47 | 150562.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1389.92 | 71801.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1351.90 | 58053.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 128.45 | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 527.15 | 60220.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 28664.05 |
Natural Gas | 0.00 | 527.15 |
Additional | 0.00 | 7226.18 |
Total | 14676.40 | 36417.38 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 43.59 |
Space Heating | 0.00 |
Space Cooling | 85.60 |
Fans (All) | 32.00 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 618.82 |
Subtotal | 618.82 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 11.38 |
Miscellaneous (All) | 11.38 |
Subtotal | 11.38 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.54 |
Space Heating | 0.00 |
Space Cooling | 30.73 |
Fans (All) | 4.07 |
Service Water Heating | 1.45 |
Receptacle Equipment | 40.30 |
Miscellaneous | 17.91 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2362. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 5785.33 | 2974.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8756.17 | 3.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8749.17 | 10.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8742.67 | 17.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8639.17 | 120.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8575.00 | 185.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8491.83 | 268.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7218.83 | 1541.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8456.67 | 303.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8222.00 | 538.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8176.67 | 583.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7123.33 | 1636.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8223.17 | 536.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7968.67 | 791.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7914.33 | 845.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7162.33 | 1597.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 55.50 | 8704.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 64.00 | 8696.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 51.67 | 8708.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8170.17 | 589.83 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
Average | 6698.33 | 2061.67 | 0.00 | 0.00 | 0.00 |
Sum | 154061.50 | 47418.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 361945.00 | 6671.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330807.00 | 6.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330805.00 | 8.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330803.00 | 10.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.17 | 2267.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.33 | 2267.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.17 | 2267.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 103395.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 361945.00 | 103395.00 | 0.00 | 0.00 | 0.00 |
Average | 75252.59 | 5082.32 | 0.00 | 0.00 | 0.00 |
Sum | 1730809.67 | 116893.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 3164.83 | 5595.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 7144.00 | 1616.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 6330.17 | 2429.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 6110.83 | 2649.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 5259.33 | 3500.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 5969.50 | 2790.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5054.67 | 3705.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 4833.00 | 3927.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 4769.83 | 3990.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 4798.00 | 3962.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 4713.50 | 4046.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 4724.67 | 4035.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 4738.67 | 4021.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 4754.67 | 4005.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 4679.50 | 4080.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 4735.83 | 4024.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 569.00 | 8191.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 572.67 | 8187.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 526.33 | 8233.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 4343.00 | 4417.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 4336.17 | 4423.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 2196.83 | 6563.17 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 1616.00 | 0.00 | 0.00 | 0.00 |
Max | 7144.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
Average | 4101.09 | 4658.91 | 0.00 | 0.00 | 0.00 |
Sum | 94325.00 | 107155.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 334385.67 | 34230.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 327443.00 | 3370.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 327040.00 | 3773.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 325904.00 | 4909.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38922.17 | 2.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18353.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38924.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24904.67 | 4.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38922.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24908.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38923.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24907.50 | 1.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 14.17 | 2253.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 14.50 | 2253.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 12.83 | 2255.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 103395.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 334385.67 | 103395.00 | 0.00 | 0.00 | 0.00 |
Average | 73532.55 | 6802.36 | 0.00 | 0.00 | 0.00 |
Sum | 1691248.67 | 156454.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:05
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.606599E+11 | 76497.44 | 16-JAN-14:38 | 31.83 | 21.82 | 0.568010E+10 | 7498.77 | 11-JAN-10:20 | 31.83 | 21.82 |
February | 0.540228E+11 | 72860.18 | 20-FEB-21:53 | 27.20 | 19.52 | 0.515107E+10 | 7498.76 | 23-FEB-10:20 | 24.73 | 20.87 |
March | 0.620519E+11 | 71411.76 | 14-MAR-03:02 | 25.18 | 22.85 | 0.614548E+10 | 7498.76 | 10-MAR-10:20 | 25.18 | 22.85 |
April | 0.582703E+11 | 68210.59 | 05-APR-03:02 | 26.02 | 23.82 | 0.546184E+10 | 7498.75 | 21-APR-09:20 | 27.90 | 25.74 |
May | 0.610398E+11 | 68249.07 | 31-MAY-03:02 | 25.90 | 25.23 | 0.591303E+10 | 7498.77 | 03-MAY-13:20 | 25.90 | 25.23 |
June | 0.608961E+11 | 68418.43 | 27-JUN-03:02 | 23.87 | 23.87 | 0.589209E+10 | 7498.77 | 02-JUN-09:20 | 23.87 | 23.87 |
July | 0.608096E+11 | 70158.89 | 06-JUL-03:02 | 25.45 | 24.03 | 0.548312E+10 | 7498.74 | 20-JUL-09:20 | 25.13 | 23.76 |
August | 0.652511E+11 | 67549.31 | 24-AUG-03:02 | 24.00 | 23.92 | 0.614713E+10 | 7498.74 | 31-AUG-09:20 | 29.27 | 27.15 |
September | 0.578051E+11 | 68657.83 | 06-SEP-03:02 | 26.35 | 24.60 | 0.546118E+10 | 7498.77 | 28-SEP-09:20 | 28.53 | 26.05 |
October | 0.594487E+11 | 70749.96 | 10-OCT-05:03 | 24.00 | 23.57 | 0.568000E+10 | 7498.76 | 05-OCT-09:20 | 24.00 | 23.57 |
November | 0.591039E+11 | 73916.22 | 24-NOV-04:02 | 26.03 | 22.05 | 0.562431E+10 | 7498.77 | 09-NOV-10:20 | 26.03 | 22.05 |
December | 0.601561E+11 | 72905.89 | 27-DEC-04:03 | 20.08 | 18.73 | 0.548263E+10 | 7498.76 | 22-DEC-10:20 | 20.08 | 18.73 |
Annual Sum or Average | 0.719515E+12 | 0.681220E+11 | ||||||||
Minimum of Months | 0.540228E+11 | 67549.31 | 20.08 | 18.73 | 0.515107E+10 | 7498.74 | 20.08 | 18.73 | ||
Maximum of Months | 0.652511E+11 | 76497.44 | 31.83 | 25.23 | 0.614713E+10 | 7498.77 | 31.83 | 27.15 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.572698E+11 | 80545.05 | 23-JAN-04:02 | 19.75 | 17.10 | 0.507683E+10 | 6734.59 | 11-JAN-14:00 | 19.75 | 17.10 |
February | 0.570539E+11 | 70657.33 | 21-FEB-05:33 | 25.00 | 21.92 | 0.460107E+10 | 6734.56 | 15-FEB-14:00 | 25.00 | 21.92 |
March | 0.691490E+11 | 73454.38 | 06-MAR-06:04 | 24.03 | 21.85 | 0.549352E+10 | 6734.54 | 03-MAR-10:09 | 24.03 | 21.85 |
April | 0.673632E+11 | 72096.76 | 10-APR-05:04 | 25.08 | 23.67 | 0.487730E+10 | 6734.55 | 12-APR-09:50 | 31.42 | 25.22 |
May | 0.606433E+11 | 76557.14 | 09-MAY-03:02 | 24.03 | 24.03 | 0.528369E+10 | 6734.61 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.639238E+11 | 73670.64 | 12-JUN-05:04 | 26.17 | 26.04 | 0.526707E+10 | 6734.60 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.664657E+11 | 72293.00 | 03-JUL-05:04 | 25.05 | 22.93 | 0.489360E+10 | 6734.56 | 03-JUL-13:09 | 23.40 | 22.58 |
August | 0.713130E+11 | 72790.61 | 21-AUG-05:04 | 24.00 | 24.00 | 0.549471E+10 | 6734.58 | 15-AUG-13:00 | 24.00 | 24.00 |
September | 0.557379E+11 | 76447.53 | 22-SEP-03:02 | 24.02 | 23.98 | 0.487943E+10 | 6734.61 | 11-SEP-13:00 | 24.02 | 23.98 |
October | 0.613743E+11 | 79127.90 | 31-OCT-03:02 | 23.45 | 23.13 | 0.507276E+10 | 6734.59 | 13-OCT-13:00 | 23.45 | 23.13 |
November | 0.644576E+11 | 71222.95 | 24-NOV-05:03 | 24.42 | 21.44 | 0.502266E+10 | 6734.70 | 09-NOV-14:00 | 24.42 | 21.44 |
December | 0.684817E+11 | 73460.08 | 26-DEC-04:12 | 23.20 | 22.88 | 0.489448E+10 | 6734.64 | 29-DEC-10:39 | 29.67 | 24.10 |
Annual Sum or Average | 0.763233E+12 | 0.608571E+11 | ||||||||
Minimum of Months | 0.557379E+11 | 70657.33 | 19.75 | 17.10 | 0.460107E+10 | 6734.54 | 19.75 | 17.10 | ||
Maximum of Months | 0.713130E+11 | 80545.05 | 26.17 | 26.04 | 0.549471E+10 | 6734.70 | 34.17 | 26.79 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.470677E+11 | 80171.42 | 02-JAN-04:04 | 23.88 | 23.02 | 0.506944E+10 | 6734.55 | 11-JAN-10:09 | 25.75 | 23.59 |
February | 0.431603E+11 | 69720.52 | 07-FEB-04:02 | 24.08 | 22.03 | 0.459771E+10 | 6734.52 | 08-FEB-10:09 | 28.25 | 23.30 |
March | 0.499636E+11 | 68706.34 | 01-MAR-04:02 | 25.83 | 23.95 | 0.549091E+10 | 6734.56 | 03-MAR-14:09 | 32.17 | 22.91 |
April | 0.470232E+11 | 64726.30 | 15-APR-05:02 | 25.50 | 24.34 | 0.486995E+10 | 6734.57 | 20-APR-13:09 | 33.50 | 26.37 |
May | 0.488833E+11 | 70764.52 | 26-MAY-04:03 | 24.00 | 23.90 | 0.527761E+10 | 6734.62 | 01-MAY-13:09 | 24.00 | 23.90 |
June | 0.490802E+11 | 66728.38 | 01-JUN-03:02 | 23.87 | 23.74 | 0.526313E+10 | 6734.62 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.461240E+11 | 69027.35 | 01-JUL-04:03 | 26.00 | 24.56 | 0.489059E+10 | 6734.58 | 03-JUL-13:09 | 23.40 | 22.58 |
August | 0.483945E+11 | 74538.37 | 21-AUG-03:02 | 24.03 | 23.95 | 0.549252E+10 | 6734.59 | 15-AUG-13:50 | 24.03 | 23.95 |
September | 0.447837E+11 | 70142.72 | 15-SEP-04:03 | 24.83 | 24.50 | 0.487335E+10 | 6734.61 | 11-SEP-13:00 | 24.83 | 24.50 |
October | 0.457284E+11 | 74288.31 | 23-OCT-03:02 | 23.35 | 23.03 | 0.506866E+10 | 6734.62 | 31-OCT-13:39 | 27.80 | 25.26 |
November | 0.452101E+11 | 74839.55 | 27-NOV-04:03 | 21.67 | 20.80 | 0.502020E+10 | 6734.71 | 09-NOV-14:00 | 21.67 | 20.80 |
December | 0.453556E+11 | 72850.21 | 18-DEC-04:03 | 23.67 | 23.16 | 0.489050E+10 | 6734.61 | 19-DEC-14:00 | 29.00 | 22.59 |
Annual Sum or Average | 0.560775E+12 | 0.608046E+11 | ||||||||
Minimum of Months | 0.431603E+11 | 64726.30 | 21.67 | 20.80 | 0.459771E+10 | 6734.52 | 21.67 | 20.80 | ||
Maximum of Months | 0.499636E+11 | 80171.42 | 26.00 | 24.56 | 0.549252E+10 | 6734.71 | 34.17 | 26.79 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.508977E+11 | 76928.50 | 02-JAN-04:02 | 23.88 | 23.02 | 0.507341E+10 | 6734.55 | 11-JAN-14:00 | 33.00 | 24.27 |
February | 0.480730E+11 | 73408.33 | 06-FEB-04:02 | 23.58 | 22.32 | 0.460170E+10 | 6734.53 | 15-FEB-14:00 | 29.00 | 24.59 |
March | 0.572056E+11 | 71193.79 | 10-MAR-04:02 | 25.08 | 23.12 | 0.549495E+10 | 6734.55 | 03-MAR-10:09 | 25.08 | 23.12 |
April | 0.551017E+11 | 70845.47 | 14-APR-03:02 | 26.40 | 24.56 | 0.487612E+10 | 6734.58 | 20-APR-13:00 | 34.50 | 26.74 |
May | 0.567222E+11 | 75111.65 | 09-MAY-03:02 | 24.03 | 24.03 | 0.528419E+10 | 6734.62 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.570015E+11 | 73404.54 | 01-JUN-03:02 | 23.87 | 23.74 | 0.526851E+10 | 6734.64 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.525595E+11 | 72509.98 | 17-JUL-03:02 | 24.92 | 23.44 | 0.489657E+10 | 6734.54 | 03-JUL-13:09 | 24.92 | 23.44 |
August | 0.543157E+11 | 77883.40 | 21-AUG-03:02 | 24.03 | 23.95 | 0.549603E+10 | 6734.57 | 17-AUG-13:00 | 24.03 | 23.95 |
September | 0.510951E+11 | 73152.36 | 18-SEP-03:02 | 25.50 | 25.14 | 0.487846E+10 | 6734.56 | 14-SEP-13:00 | 25.50 | 25.14 |
October | 0.505492E+11 | 78724.19 | 23-OCT-03:02 | 23.35 | 23.03 | 0.507278E+10 | 6734.65 | 13-OCT-13:09 | 23.35 | 23.03 |
November | 0.497288E+11 | 77861.28 | 27-NOV-04:03 | 21.67 | 20.80 | 0.502449E+10 | 6734.66 | 09-NOV-14:50 | 21.67 | 20.80 |
December | 0.488698E+11 | 76497.79 | 18-DEC-04:03 | 23.67 | 23.16 | 0.489372E+10 | 6734.59 | 11-DEC-14:00 | 23.67 | 23.16 |
Annual Sum or Average | 0.632120E+12 | 0.608609E+11 | ||||||||
Minimum of Months | 0.480730E+11 | 70845.47 | 21.67 | 20.80 | 0.460170E+10 | 6734.53 | 21.67 | 20.80 | ||
Maximum of Months | 0.572056E+11 | 78724.19 | 26.40 | 25.14 | 0.549603E+10 | 6734.66 | 34.50 | 26.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.942036E+10 | 13036.22 | 02-JAN-04:02 | 23.88 | 23.02 | 0.638604E+09 | 845.62 | 11-JAN-14:00 | 33.00 | 24.27 |
February | 0.964084E+10 | 11914.31 | 21-FEB-05:33 | 25.00 | 21.92 | 0.579233E+09 | 845.62 | 15-FEB-14:00 | 25.00 | 21.92 |
March | 0.120163E+11 | 15331.63 | 26-MAR-15:01 | 33.90 | 25.32 | 0.691376E+09 | 845.61 | 01-MAR-14:00 | 33.90 | 25.32 |
April | 0.121636E+11 | 15527.81 | 02-APR-15:41 | 33.75 | 27.23 | 0.614477E+09 | 845.90 | 17-APR-09:00 | 34.50 | 26.75 |
May | 0.122627E+11 | 15208.72 | 14-MAY-13:02 | 34.50 | 26.67 | 0.666018E+09 | 845.90 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.137866E+11 | 15615.54 | 18-JUN-13:02 | 34.67 | 27.38 | 0.663832E+09 | 845.88 | 28-JUN-13:20 | 34.13 | 26.89 |
July | 0.125596E+11 | 15268.64 | 04-JUL-13:13 | 32.17 | 24.95 | 0.616955E+09 | 845.79 | 18-JUL-13:20 | 30.47 | 25.47 |
August | 0.127114E+11 | 15520.74 | 27-AUG-15:41 | 32.83 | 25.58 | 0.691575E+09 | 845.83 | 08-AUG-13:20 | 32.83 | 25.58 |
September | 0.991418E+10 | 13646.02 | 05-SEP-03:02 | 26.53 | 25.79 | 0.614384E+09 | 845.62 | 11-SEP-13:00 | 27.00 | 24.83 |
October | 0.101737E+11 | 12039.62 | 16-OCT-04:53 | 26.00 | 25.22 | 0.638584E+09 | 845.61 | 31-OCT-13:09 | 27.95 | 25.33 |
November | 0.105136E+11 | 12004.04 | 24-NOV-05:03 | 24.42 | 21.44 | 0.632070E+09 | 845.63 | 09-NOV-14:00 | 24.42 | 21.44 |
December | 0.107507E+11 | 11896.29 | 26-DEC-04:12 | 23.20 | 22.88 | 0.615832E+09 | 845.62 | 29-DEC-10:39 | 29.67 | 24.10 |
Annual Sum or Average | 0.135914E+12 | 0.766294E+10 | ||||||||
Minimum of Months | 0.942036E+10 | 11896.29 | 23.20 | 21.44 | 0.579233E+09 | 845.61 | 24.42 | 21.44 | ||
Maximum of Months | 0.137866E+11 | 15615.54 | 34.67 | 27.38 | 0.691575E+09 | 845.90 | 34.50 | 26.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.730585E+10 | 11062.85 | 16-JAN-09:23 | 26.35 | 21.11 | 0.411825E+09 | 544.95 | 11-JAN-14:00 | 26.35 | 21.11 |
February | 0.747397E+10 | 10743.58 | 20-FEB-12:53 | 32.60 | 24.54 | 0.373446E+09 | 544.95 | 15-FEB-14:00 | 32.60 | 24.54 |
March | 0.915821E+10 | 14982.96 | 26-MAR-09:42 | 32.50 | 25.17 | 0.445626E+09 | 545.18 | 29-MAR-09:20 | 31.47 | 23.98 |
April | 0.891901E+10 | 14747.75 | 09-APR-09:02 | 30.75 | 25.93 | 0.395930E+09 | 545.37 | 12-APR-09:50 | 31.42 | 25.22 |
May | 0.841197E+10 | 14345.69 | 14-MAY-08:23 | 29.00 | 25.69 | 0.429045E+09 | 545.19 | 05-MAY-09:39 | 29.00 | 25.69 |
June | 0.882684E+10 | 11643.04 | 18-JUN-13:02 | 34.67 | 27.38 | 0.427399E+09 | 544.95 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.793524E+10 | 11494.25 | 30-JUL-09:43 | 29.33 | 24.40 | 0.397048E+09 | 544.94 | 03-JUL-13:09 | 29.33 | 24.40 |
August | 0.853224E+10 | 14518.81 | 27-AUG-09:02 | 31.05 | 28.34 | 0.445286E+09 | 545.17 | 28-AUG-09:20 | 30.97 | 27.04 |
September | 0.739741E+10 | 14694.34 | 04-SEP-09:32 | 30.13 | 27.16 | 0.396136E+09 | 545.42 | 05-SEP-09:00 | 31.20 | 26.93 |
October | 0.728716E+10 | 11632.24 | 08-OCT-14:02 | 32.33 | 26.14 | 0.411490E+09 | 544.95 | 31-OCT-13:09 | 27.95 | 25.33 |
November | 0.739244E+10 | 10123.89 | 13-NOV-06:02 | 25.13 | 24.29 | 0.407219E+09 | 544.96 | 09-NOV-14:00 | 25.13 | 24.29 |
December | 0.754623E+10 | 9897.57 | 03-DEC-10:13 | 29.53 | 22.41 | 0.396747E+09 | 544.96 | 29-DEC-10:39 | 29.67 | 24.10 |
Annual Sum or Average | 0.961866E+11 | 0.493720E+10 | ||||||||
Minimum of Months | 0.728716E+10 | 9897.57 | 25.13 | 21.11 | 0.373446E+09 | 544.94 | 25.13 | 21.11 | ||
Maximum of Months | 0.915821E+10 | 14982.96 | 34.67 | 28.34 | 0.445626E+09 | 545.42 | 34.17 | 27.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132943E+11 | 15803.51 | 22-JAN-15:22 | 30.20 | 22.25 | 0.643158E+09 | 889.75 | 04-JAN-14:09 | 30.20 | 22.25 |
February | 0.126124E+11 | 15845.80 | 20-FEB-12:53 | 32.60 | 24.54 | 0.581832E+09 | 887.76 | 21-FEB-14:20 | 34.67 | 21.94 |
March | 0.134823E+11 | 15453.06 | 26-MAR-15:01 | 33.90 | 25.32 | 0.691951E+09 | 845.83 | 13-MAR-09:20 | 33.90 | 25.32 |
April | 0.119301E+11 | 15229.81 | 02-APR-15:41 | 33.75 | 27.23 | 0.614408E+09 | 846.09 | 03-APR-13:00 | 32.10 | 25.45 |
May | 0.111605E+11 | 13296.30 | 01-MAY-03:42 | 28.40 | 26.77 | 0.665458E+09 | 845.64 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.116246E+11 | 14657.09 | 04-JUN-13:52 | 33.00 | 27.70 | 0.663156E+09 | 845.64 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.112876E+11 | 12743.13 | 09-JUL-15:02 | 31.80 | 25.12 | 0.616425E+09 | 845.63 | 03-JUL-13:09 | 31.80 | 25.12 |
August | 0.120561E+11 | 14969.15 | 27-AUG-15:41 | 32.83 | 25.58 | 0.691279E+09 | 845.63 | 15-AUG-13:00 | 32.83 | 25.58 |
September | 0.103030E+11 | 13386.25 | 05-SEP-03:02 | 26.53 | 25.79 | 0.614569E+09 | 846.02 | 11-SEP-13:39 | 28.90 | 25.49 |
October | 0.116107E+11 | 15460.25 | 29-OCT-11:53 | 31.50 | 26.00 | 0.639326E+09 | 845.97 | 31-OCT-13:20 | 27.90 | 25.30 |
November | 0.131991E+11 | 15652.83 | 23-NOV-13:02 | 30.75 | 25.19 | 0.633770E+09 | 859.04 | 20-NOV-14:20 | 30.75 | 25.19 |
December | 0.146126E+11 | 16289.70 | 03-DEC-14:12 | 31.00 | 21.64 | 0.623551E+09 | 907.81 | 26-DEC-14:09 | 31.17 | 22.67 |
Annual Sum or Average | 0.147173E+12 | 0.767888E+10 | ||||||||
Minimum of Months | 0.103030E+11 | 12743.13 | 26.53 | 21.64 | 0.581832E+09 | 845.63 | 27.90 | 21.94 | ||
Maximum of Months | 0.146126E+11 | 16289.70 | 33.90 | 27.70 | 0.691951E+09 | 907.81 | 34.67 | 26.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.957366E+10 | 19903.29 | 22-JAN-15:22 | 30.20 | 22.25 | 0.412589E+09 | 544.95 | 11-JAN-14:00 | 30.20 | 22.25 |
February | 0.107559E+11 | 19532.82 | 26-FEB-15:42 | 34.25 | 25.06 | 0.374338E+09 | 544.96 | 15-FEB-14:00 | 34.25 | 25.06 |
March | 0.143729E+11 | 21875.83 | 26-MAR-15:41 | 33.50 | 25.39 | 0.446734E+09 | 544.95 | 01-MAR-14:00 | 33.50 | 25.39 |
April | 0.149098E+11 | 22521.25 | 02-APR-15:41 | 33.75 | 27.23 | 0.397128E+09 | 544.94 | 20-APR-13:09 | 33.50 | 26.37 |
May | 0.108578E+11 | 17961.99 | 01-MAY-03:02 | 28.80 | 26.67 | 0.429593E+09 | 544.95 | 01-MAY-13:09 | 27.83 | 25.07 |
June | 0.124841E+11 | 20071.42 | 25-JUN-15:42 | 30.83 | 27.58 | 0.428222E+09 | 544.95 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.127029E+11 | 19824.76 | 04-JUL-15:52 | 31.50 | 25.29 | 0.398420E+09 | 544.94 | 03-JUL-13:09 | 31.50 | 25.29 |
August | 0.145452E+11 | 21931.52 | 27-AUG-15:41 | 32.83 | 25.58 | 0.446775E+09 | 544.95 | 15-AUG-13:00 | 32.83 | 25.58 |
September | 0.967763E+10 | 18604.87 | 24-SEP-15:23 | 31.15 | 27.29 | 0.396702E+09 | 544.95 | 11-SEP-13:00 | 31.15 | 27.29 |
October | 0.108046E+11 | 20076.44 | 08-OCT-14:02 | 32.33 | 26.14 | 0.412656E+09 | 544.95 | 31-OCT-13:09 | 27.95 | 25.33 |
November | 0.119235E+11 | 18939.64 | 19-NOV-14:52 | 31.50 | 24.93 | 0.408692E+09 | 544.96 | 09-NOV-14:00 | 31.50 | 24.93 |
December | 0.133770E+11 | 20870.01 | 03-DEC-14:12 | 31.00 | 21.64 | 0.398474E+09 | 544.96 | 29-DEC-10:39 | 29.67 | 24.10 |
Annual Sum or Average | 0.145985E+12 | 0.495032E+10 | ||||||||
Minimum of Months | 0.957366E+10 | 17961.99 | 28.80 | 21.64 | 0.374338E+09 | 544.94 | 27.83 | 22.25 | ||
Maximum of Months | 0.149098E+11 | 22521.25 | 34.25 | 27.58 | 0.446775E+09 | 544.96 | 34.25 | 27.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.804816E+10 | 12075.15 | 02-JAN-04:02 | 23.88 | 23.02 | 0.638094E+09 | 845.61 | 11-JAN-14:00 | 33.00 | 24.27 |
February | 0.782129E+10 | 11926.38 | 27-FEB-04:02 | 23.67 | 22.19 | 0.579166E+09 | 845.60 | 07-FEB-14:00 | 23.67 | 22.19 |
March | 0.952067E+10 | 13902.23 | 19-MAR-14:51 | 35.00 | 24.37 | 0.691482E+09 | 845.61 | 01-MAR-14:00 | 35.00 | 24.37 |
April | 0.950183E+10 | 12634.31 | 19-APR-03:02 | 27.02 | 25.52 | 0.614337E+09 | 845.61 | 28-APR-13:00 | 34.00 | 26.11 |
May | 0.109449E+11 | 14278.77 | 07-MAY-13:32 | 34.50 | 26.47 | 0.666031E+09 | 845.83 | 01-MAY-13:09 | 34.50 | 26.47 |
June | 0.120735E+11 | 14796.23 | 11-JUN-15:32 | 34.67 | 28.13 | 0.664042E+09 | 845.73 | 19-JUN-13:39 | 29.50 | 26.97 |
July | 0.990632E+10 | 13760.89 | 04-JUL-15:32 | 31.67 | 25.13 | 0.617283E+09 | 845.68 | 10-JUL-13:00 | 28.00 | 26.07 |
August | 0.967881E+10 | 13941.14 | 13-AUG-16:52 | 28.00 | 26.50 | 0.691775E+09 | 845.65 | 02-AUG-13:00 | 28.00 | 26.50 |
September | 0.854071E+10 | 12643.73 | 25-SEP-03:02 | 25.42 | 25.08 | 0.614157E+09 | 845.61 | 11-SEP-13:00 | 25.42 | 25.08 |
October | 0.809136E+10 | 12468.09 | 30-OCT-03:02 | 24.98 | 24.18 | 0.638551E+09 | 845.61 | 31-OCT-13:39 | 27.80 | 25.26 |
November | 0.792877E+10 | 11551.91 | 13-NOV-04:02 | 25.00 | 24.13 | 0.632020E+09 | 845.63 | 09-NOV-14:00 | 25.00 | 24.13 |
December | 0.756433E+10 | 10550.56 | 15-DEC-06:03 | 19.43 | 18.58 | 0.615553E+09 | 845.61 | 19-DEC-14:00 | 29.00 | 22.59 |
Annual Sum or Average | 0.109621E+12 | 0.766249E+10 | ||||||||
Minimum of Months | 0.756433E+10 | 10550.56 | 19.43 | 18.58 | 0.579166E+09 | 845.60 | 23.67 | 22.19 | ||
Maximum of Months | 0.120735E+11 | 14796.23 | 35.00 | 28.13 | 0.691775E+09 | 845.83 | 35.00 | 26.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.674183E+10 | 12292.55 | 02-JAN-04:02 | 23.88 | 23.02 | 0.303638E+09 | 521.22 | 11-JAN-15:20 | 32.23 | 24.62 |
February | 0.677942E+10 | 15040.78 | 20-FEB-09:53 | 29.40 | 22.77 | 0.275497E+09 | 521.21 | 07-FEB-15:20 | 29.40 | 22.77 |
March | 0.830725E+10 | 15610.65 | 26-MAR-09:42 | 32.50 | 25.17 | 0.328033E+09 | 521.21 | 01-MAR-15:20 | 32.50 | 25.17 |
April | 0.807460E+10 | 15223.38 | 30-APR-09:13 | 30.87 | 26.89 | 0.292130E+09 | 521.20 | 03-APR-14:20 | 30.87 | 26.89 |
May | 0.787934E+10 | 15194.60 | 14-MAY-09:53 | 32.40 | 26.26 | 0.316059E+09 | 521.34 | 05-MAY-07:00 | 32.40 | 26.26 |
June | 0.819129E+10 | 15095.31 | 18-JUN-09:32 | 32.00 | 27.60 | 0.314595E+09 | 521.20 | 19-JUN-12:09 | 29.25 | 26.86 |
July | 0.681492E+10 | 11061.50 | 03-JUL-03:02 | 25.00 | 22.79 | 0.293404E+09 | 521.20 | 17-JUL-14:20 | 31.33 | 26.20 |
August | 0.743108E+10 | 14924.31 | 13-AUG-09:32 | 31.00 | 27.34 | 0.327844E+09 | 521.20 | 15-AUG-12:09 | 33.32 | 27.86 |
September | 0.685654E+10 | 15038.65 | 04-SEP-09:23 | 30.10 | 27.11 | 0.291969E+09 | 521.20 | 11-SEP-14:09 | 26.67 | 24.75 |
October | 0.638834E+10 | 14962.53 | 08-OCT-09:32 | 30.17 | 26.36 | 0.303669E+09 | 521.21 | 13-OCT-14:20 | 29.67 | 26.26 |
November | 0.631469E+10 | 13712.76 | 05-NOV-09:32 | 28.43 | 24.08 | 0.300612E+09 | 521.22 | 16-NOV-13:09 | 30.58 | 25.75 |
December | 0.625072E+10 | 12787.42 | 31-DEC-10:32 | 30.93 | 24.98 | 0.293082E+09 | 521.21 | 04-DEC-15:20 | 30.93 | 24.98 |
Annual Sum or Average | 0.860300E+11 | 0.364053E+10 | ||||||||
Minimum of Months | 0.625072E+10 | 11061.50 | 23.88 | 22.77 | 0.275497E+09 | 521.20 | 26.67 | 22.77 | ||
Maximum of Months | 0.830725E+10 | 15610.65 | 32.50 | 27.60 | 0.328033E+09 | 521.34 | 33.32 | 27.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122652E+11 | 14800.18 | 29-JAN-14:12 | 32.00 | 23.25 | 0.648960E+09 | 926.77 | 04-JAN-14:20 | 32.00 | 23.25 |
February | 0.109875E+11 | 14114.96 | 19-FEB-14:13 | 32.33 | 24.90 | 0.584820E+09 | 900.11 | 21-FEB-14:30 | 34.50 | 21.90 |
March | 0.110679E+11 | 14168.50 | 19-MAR-14:51 | 35.00 | 24.37 | 0.692223E+09 | 845.90 | 20-MAR-09:20 | 31.60 | 23.77 |
April | 0.932807E+10 | 12137.40 | 01-APR-03:02 | 26.97 | 25.29 | 0.614237E+09 | 845.96 | 03-APR-13:00 | 32.10 | 25.45 |
May | 0.975791E+10 | 13384.40 | 07-MAY-13:32 | 34.50 | 26.47 | 0.665360E+09 | 845.64 | 01-MAY-13:09 | 34.50 | 26.47 |
June | 0.976088E+10 | 13518.62 | 11-JUN-15:32 | 34.67 | 28.13 | 0.663151E+09 | 845.63 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.861846E+10 | 12349.32 | 10-JUL-03:02 | 25.67 | 23.72 | 0.616563E+09 | 845.62 | 10-JUL-13:00 | 28.00 | 26.07 |
August | 0.906812E+10 | 12043.52 | 15-AUG-03:02 | 26.87 | 26.08 | 0.691434E+09 | 845.63 | 15-AUG-13:50 | 27.73 | 27.13 |
September | 0.895560E+10 | 13349.01 | 04-SEP-16:42 | 32.17 | 26.80 | 0.614393E+09 | 845.90 | 11-SEP-13:00 | 27.00 | 24.83 |
October | 0.962799E+10 | 14275.18 | 29-OCT-12:02 | 31.57 | 26.03 | 0.639469E+09 | 845.83 | 13-OCT-13:00 | 31.57 | 26.03 |
November | 0.108747E+11 | 14287.37 | 05-NOV-11:32 | 30.83 | 22.94 | 0.635260E+09 | 877.06 | 29-NOV-14:09 | 30.08 | 24.77 |
December | 0.117759E+11 | 14897.42 | 31-DEC-12:32 | 31.67 | 24.84 | 0.627188E+09 | 932.48 | 07-DEC-14:09 | 31.67 | 24.84 |
Annual Sum or Average | 0.122088E+12 | 0.769306E+10 | ||||||||
Minimum of Months | 0.861846E+10 | 12043.52 | 25.67 | 22.94 | 0.584820E+09 | 845.62 | 27.00 | 21.90 | ||
Maximum of Months | 0.122652E+11 | 14897.42 | 35.00 | 28.13 | 0.692223E+09 | 932.48 | 34.50 | 27.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.727284E+10 | 16790.43 | 29-JAN-15:32 | 32.20 | 23.14 | 0.412041E+09 | 544.95 | 11-JAN-14:00 | 32.20 | 23.14 |
February | 0.729988E+10 | 16211.75 | 26-FEB-15:42 | 34.25 | 25.06 | 0.373975E+09 | 544.94 | 07-FEB-14:00 | 34.25 | 25.06 |
March | 0.915718E+10 | 17753.64 | 19-MAR-14:51 | 35.00 | 24.37 | 0.446548E+09 | 544.94 | 06-MAR-14:00 | 35.00 | 24.37 |
April | 0.887091E+10 | 16535.92 | 02-APR-16:02 | 33.25 | 27.16 | 0.396736E+09 | 544.94 | 20-APR-13:09 | 33.50 | 26.37 |
May | 0.834459E+10 | 16257.75 | 07-MAY-13:32 | 34.50 | 26.47 | 0.429350E+09 | 544.95 | 01-MAY-13:09 | 34.50 | 26.47 |
June | 0.869005E+10 | 17384.29 | 11-JUN-16:12 | 34.00 | 27.98 | 0.427969E+09 | 544.95 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.740658E+10 | 16289.20 | 04-JUL-16:12 | 30.83 | 25.29 | 0.398004E+09 | 544.94 | 10-JUL-13:00 | 28.00 | 26.07 |
August | 0.806711E+10 | 16804.62 | 13-AUG-16:52 | 28.00 | 26.50 | 0.446304E+09 | 544.94 | 15-AUG-13:50 | 27.73 | 27.13 |
September | 0.724884E+10 | 17246.71 | 04-SEP-16:42 | 32.17 | 26.80 | 0.396323E+09 | 544.95 | 11-SEP-13:00 | 27.00 | 24.83 |
October | 0.694778E+10 | 14448.97 | 30-OCT-03:02 | 24.98 | 24.18 | 0.412165E+09 | 544.94 | 31-OCT-13:39 | 27.80 | 25.26 |
November | 0.693375E+10 | 14655.30 | 20-NOV-04:02 | 24.25 | 22.75 | 0.408040E+09 | 544.96 | 09-NOV-14:00 | 24.25 | 22.75 |
December | 0.698191E+10 | 16090.30 | 31-DEC-15:52 | 31.40 | 24.10 | 0.397655E+09 | 544.95 | 29-DEC-10:39 | 31.40 | 24.10 |
Annual Sum or Average | 0.932214E+11 | 0.494511E+10 | ||||||||
Minimum of Months | 0.693375E+10 | 14448.97 | 24.25 | 22.75 | 0.373975E+09 | 544.94 | 24.25 | 22.75 | ||
Maximum of Months | 0.915718E+10 | 17753.64 | 35.00 | 27.98 | 0.446548E+09 | 544.96 | 35.00 | 27.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.865177E+10 | 14362.82 | 02-JAN-04:02 | 23.88 | 23.02 | 0.638294E+09 | 845.61 | 11-JAN-14:00 | 33.00 | 24.27 |
February | 0.859466E+10 | 16142.94 | 19-FEB-14:13 | 32.33 | 24.90 | 0.579491E+09 | 845.62 | 15-FEB-14:00 | 32.33 | 24.90 |
March | 0.106498E+11 | 17347.17 | 19-MAR-14:51 | 35.00 | 24.37 | 0.691794E+09 | 845.61 | 01-MAR-14:00 | 35.00 | 24.37 |
April | 0.108066E+11 | 17370.13 | 30-APR-15:31 | 32.87 | 27.15 | 0.614784E+09 | 845.61 | 20-APR-13:20 | 32.87 | 27.15 |
May | 0.123500E+11 | 17564.17 | 07-MAY-13:32 | 34.50 | 26.47 | 0.666342E+09 | 845.99 | 03-MAY-13:20 | 34.50 | 26.47 |
June | 0.135234E+11 | 17905.36 | 11-JUN-14:02 | 35.00 | 28.16 | 0.664261E+09 | 845.88 | 13-JUN-09:20 | 32.47 | 28.31 |
July | 0.110389E+11 | 16661.88 | 04-JUL-15:32 | 31.67 | 25.13 | 0.617593E+09 | 845.84 | 06-JUL-13:20 | 31.00 | 24.61 |
August | 0.106592E+11 | 17026.71 | 13-AUG-16:52 | 28.00 | 26.50 | 0.691989E+09 | 845.73 | 14-AUG-13:20 | 33.53 | 27.57 |
September | 0.952361E+10 | 16433.73 | 24-SEP-15:52 | 31.30 | 27.35 | 0.614504E+09 | 845.61 | 11-SEP-13:39 | 31.30 | 27.35 |
October | 0.881525E+10 | 15221.60 | 09-OCT-15:23 | 29.45 | 26.42 | 0.638807E+09 | 845.62 | 13-OCT-13:09 | 31.75 | 26.46 |
November | 0.861659E+10 | 16543.51 | 19-NOV-15:22 | 30.80 | 25.37 | 0.632376E+09 | 845.62 | 09-NOV-14:50 | 30.80 | 25.37 |
December | 0.810390E+10 | 13413.92 | 11-DEC-04:02 | 23.17 | 22.97 | 0.615689E+09 | 845.61 | 04-DEC-14:00 | 23.17 | 22.97 |
Annual Sum or Average | 0.121334E+12 | 0.766592E+10 | ||||||||
Minimum of Months | 0.810390E+10 | 13413.92 | 23.17 | 22.97 | 0.579491E+09 | 845.61 | 23.17 | 22.97 | ||
Maximum of Months | 0.135234E+11 | 17905.36 | 35.00 | 28.16 | 0.691989E+09 | 845.99 | 35.00 | 28.31 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.733968E+10 | 12492.77 | 02-JAN-04:02 | 23.88 | 23.02 | 0.412009E+09 | 544.95 | 11-JAN-14:00 | 33.00 | 24.27 |
February | 0.750857E+10 | 15578.53 | 20-FEB-09:53 | 29.40 | 22.77 | 0.373905E+09 | 544.95 | 15-FEB-14:00 | 29.40 | 22.77 |
March | 0.929080E+10 | 16043.15 | 19-MAR-14:51 | 35.00 | 24.37 | 0.446263E+09 | 545.29 | 29-MAR-09:20 | 31.47 | 23.98 |
April | 0.918513E+10 | 15830.74 | 30-APR-15:31 | 32.87 | 27.15 | 0.396573E+09 | 545.33 | 12-APR-09:00 | 32.87 | 27.15 |
May | 0.897833E+10 | 15660.56 | 07-MAY-13:32 | 34.50 | 26.47 | 0.429383E+09 | 545.23 | 01-MAY-09:00 | 34.50 | 26.47 |
June | 0.927003E+10 | 15633.63 | 18-JUN-08:43 | 30.83 | 27.19 | 0.427919E+09 | 544.95 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.770697E+10 | 15233.64 | 30-JUL-09:43 | 29.33 | 24.40 | 0.397896E+09 | 544.94 | 11-JUL-13:00 | 29.33 | 24.40 |
August | 0.828547E+10 | 15647.23 | 27-AUG-09:13 | 31.10 | 28.02 | 0.446072E+09 | 545.34 | 28-AUG-09:00 | 30.90 | 26.65 |
September | 0.772777E+10 | 15673.07 | 03-SEP-09:32 | 30.47 | 27.16 | 0.396391E+09 | 545.27 | 05-SEP-09:50 | 31.00 | 26.94 |
October | 0.707256E+10 | 15509.17 | 08-OCT-09:32 | 30.17 | 26.36 | 0.411986E+09 | 544.95 | 13-OCT-13:09 | 31.75 | 26.46 |
November | 0.698041E+10 | 14974.05 | 23-NOV-13:32 | 30.00 | 25.61 | 0.407931E+09 | 544.95 | 09-NOV-14:50 | 30.00 | 25.61 |
December | 0.679926E+10 | 12431.89 | 03-DEC-11:02 | 31.00 | 22.63 | 0.397499E+09 | 544.95 | 29-DEC-10:39 | 29.67 | 24.10 |
Annual Sum or Average | 0.961450E+11 | 0.494383E+10 | ||||||||
Minimum of Months | 0.679926E+10 | 12431.89 | 23.88 | 22.63 | 0.373905E+09 | 544.94 | 29.33 | 22.77 | ||
Maximum of Months | 0.929080E+10 | 16043.15 | 35.00 | 28.02 | 0.446263E+09 | 545.34 | 34.50 | 27.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132564E+11 | 17361.77 | 15-JAN-14:32 | 30.83 | 22.30 | 0.643103E+09 | 900.30 | 04-JAN-14:20 | 30.83 | 22.30 |
February | 0.120506E+11 | 16932.54 | 19-FEB-14:13 | 32.33 | 24.90 | 0.581928E+09 | 880.85 | 21-FEB-14:30 | 34.50 | 21.90 |
March | 0.123106E+11 | 17489.58 | 19-MAR-14:51 | 35.00 | 24.37 | 0.692422E+09 | 845.85 | 06-MAR-14:00 | 35.00 | 24.37 |
April | 0.106038E+11 | 16730.20 | 30-APR-15:31 | 32.87 | 27.15 | 0.614676E+09 | 846.19 | 03-APR-13:00 | 32.87 | 27.15 |
May | 0.110234E+11 | 16607.13 | 07-MAY-13:32 | 34.50 | 26.47 | 0.665761E+09 | 845.64 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.109980E+11 | 16563.82 | 11-JUN-14:02 | 35.00 | 28.16 | 0.663503E+09 | 845.64 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.961967E+10 | 15842.52 | 30-JUL-13:02 | 31.50 | 24.65 | 0.616981E+09 | 845.62 | 11-JUL-13:00 | 31.50 | 24.65 |
August | 0.998448E+10 | 16207.55 | 13-AUG-16:52 | 28.00 | 26.50 | 0.691677E+09 | 845.62 | 17-AUG-13:20 | 27.40 | 25.59 |
September | 0.997395E+10 | 16194.35 | 24-SEP-15:52 | 31.30 | 27.35 | 0.614688E+09 | 846.15 | 11-SEP-13:39 | 31.30 | 27.35 |
October | 0.104839E+11 | 17074.64 | 29-OCT-12:02 | 31.57 | 26.03 | 0.639610E+09 | 845.87 | 17-OCT-13:20 | 31.57 | 26.03 |
November | 0.118415E+11 | 17630.03 | 19-NOV-13:22 | 32.20 | 24.78 | 0.633802E+09 | 853.43 | 29-NOV-14:20 | 30.07 | 24.78 |
December | 0.127094E+11 | 17613.79 | 24-DEC-13:22 | 31.60 | 24.46 | 0.621617E+09 | 905.85 | 07-DEC-14:20 | 31.60 | 24.46 |
Annual Sum or Average | 0.134856E+12 | 0.767977E+10 | ||||||||
Minimum of Months | 0.961967E+10 | 15842.52 | 28.00 | 22.30 | 0.581928E+09 | 845.62 | 27.40 | 21.90 | ||
Maximum of Months | 0.132564E+11 | 17630.03 | 35.00 | 28.16 | 0.692422E+09 | 905.85 | 35.00 | 27.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.780443E+10 | 18296.77 | 15-JAN-15:52 | 31.20 | 21.80 | 0.411976E+09 | 544.95 | 11-JAN-14:00 | 31.20 | 21.80 |
February | 0.795414E+10 | 18025.62 | 26-FEB-15:42 | 34.25 | 25.06 | 0.373987E+09 | 544.95 | 15-FEB-14:00 | 34.25 | 25.06 |
March | 0.100858E+11 | 20278.62 | 19-MAR-14:51 | 35.00 | 24.37 | 0.446566E+09 | 544.94 | 01-MAR-14:00 | 35.00 | 24.37 |
April | 0.994178E+10 | 19951.62 | 30-APR-15:31 | 32.87 | 27.15 | 0.396769E+09 | 544.94 | 20-APR-13:20 | 32.87 | 27.15 |
May | 0.933502E+10 | 18566.98 | 07-MAY-13:32 | 34.50 | 26.47 | 0.429370E+09 | 544.95 | 30-MAY-13:00 | 28.00 | 26.50 |
June | 0.965096E+10 | 18724.91 | 11-JUN-14:02 | 35.00 | 28.16 | 0.427985E+09 | 544.95 | 28-JUN-13:09 | 34.17 | 26.79 |
July | 0.821727E+10 | 18108.69 | 04-JUL-16:12 | 30.83 | 25.29 | 0.398048E+09 | 544.94 | 11-JUL-13:00 | 25.00 | 23.59 |
August | 0.878977E+10 | 18960.27 | 13-AUG-16:52 | 28.00 | 26.50 | 0.446293E+09 | 544.94 | 17-AUG-13:20 | 27.40 | 25.59 |
September | 0.802043E+10 | 18357.21 | 24-SEP-15:52 | 31.30 | 27.35 | 0.396319E+09 | 544.94 | 11-SEP-13:39 | 31.30 | 27.35 |
October | 0.756059E+10 | 17413.38 | 08-OCT-16:53 | 29.30 | 24.86 | 0.412037E+09 | 544.95 | 13-OCT-13:09 | 31.75 | 26.46 |
November | 0.752573E+10 | 18990.47 | 19-NOV-15:22 | 30.80 | 25.37 | 0.408021E+09 | 544.95 | 09-NOV-14:50 | 30.80 | 25.37 |
December | 0.746892E+10 | 17834.52 | 24-DEC-16:42 | 29.33 | 23.37 | 0.397544E+09 | 544.95 | 04-DEC-14:00 | 29.33 | 23.37 |
Annual Sum or Average | 0.102355E+12 | 0.494491E+10 | ||||||||
Minimum of Months | 0.746892E+10 | 17413.38 | 28.00 | 21.80 | 0.373987E+09 | 544.94 | 25.00 | 21.80 | ||
Maximum of Months | 0.100858E+11 | 20278.62 | 35.00 | 28.16 | 0.446566E+09 | 544.95 | 35.00 | 27.35 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.903650E+10 | 13732.37 | 02-JAN-06:15 | 23.37 | 23.04 | 0.00 | 0.00 | 01-JAN-00:10 | 23.37 | 23.04 |
February | 0.871362E+10 | 13236.67 | 21-FEB-06:15 | 24.67 | 21.61 | 0.00 | 0.00 | 01-FEB-00:10 | 24.67 | 21.61 |
March | 0.106053E+11 | 13186.63 | 27-MAR-05:15 | 26.00 | 24.56 | 0.00 | 0.00 | 01-MAR-00:10 | 26.00 | 24.56 |
April | 0.104658E+11 | 13419.70 | 03-APR-05:15 | 27.00 | 24.93 | 0.00 | 0.00 | 01-APR-00:10 | 27.00 | 24.93 |
May | 0.985815E+10 | 13605.30 | 01-MAY-05:15 | 28.00 | 26.50 | 0.00 | 0.00 | 01-MAY-00:10 | 28.00 | 26.50 |
June | 0.103513E+11 | 13177.23 | 12-JUN-05:15 | 26.33 | 26.08 | 0.00 | 0.00 | 01-JUN-00:10 | 26.33 | 26.08 |
July | 0.968094E+10 | 12769.54 | 31-JUL-05:15 | 24.20 | 23.24 | 0.00 | 0.00 | 01-JUL-00:10 | 24.20 | 23.24 |
August | 0.103706E+11 | 13235.92 | 28-AUG-05:15 | 25.00 | 25.00 | 0.00 | 0.00 | 01-AUG-00:10 | 25.00 | 25.00 |
September | 0.863844E+10 | 13617.24 | 05-SEP-05:15 | 26.67 | 26.15 | 0.00 | 0.00 | 01-SEP-00:10 | 26.67 | 26.15 |
October | 0.876595E+10 | 13741.11 | 10-OCT-05:13 | 24.00 | 23.51 | 0.00 | 0.00 | 01-OCT-00:10 | 24.00 | 23.51 |
November | 0.913416E+10 | 12007.27 | 13-NOV-06:15 | 25.27 | 24.33 | 0.00 | 0.00 | 01-NOV-00:10 | 25.27 | 24.33 |
December | 0.941258E+10 | 13877.65 | 26-DEC-06:13 | 22.33 | 21.42 | 0.00 | 0.00 | 01-DEC-00:10 | 22.33 | 21.42 |
Annual Sum or Average | 0.115033E+12 | 0.00 | ||||||||
Minimum of Months | 0.863844E+10 | 12007.27 | 22.33 | 21.42 | 0.00 | 0.00 | 22.33 | 21.42 | ||
Maximum of Months | 0.106053E+11 | 13877.65 | 28.00 | 26.50 | 0.00 | 0.00 | 28.00 | 26.50 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.733287E+10 | 12927.38 | 02-JAN-06:15 | 23.37 | 23.04 | 0.00 | 0.00 | 01-JAN-00:10 | 23.37 | 23.04 |
February | 0.695363E+10 | 8849.44 | 06-FEB-06:15 | 23.90 | 22.57 | 0.00 | 0.00 | 01-FEB-00:10 | 23.90 | 22.57 |
March | 0.817110E+10 | 7114.08 | 03-MAR-06:03 | 22.23 | 20.03 | 0.00 | 0.00 | 01-MAR-00:10 | 22.23 | 20.03 |
April | 0.771654E+10 | 7245.52 | 29-APR-05:03 | 27.00 | 25.53 | 0.00 | 0.00 | 01-APR-00:10 | 27.00 | 25.53 |
May | 0.805474E+10 | 9267.83 | 15-MAY-05:02 | 26.00 | 26.00 | 0.00 | 0.00 | 01-MAY-00:10 | 26.00 | 26.00 |
June | 0.832665E+10 | 8315.01 | 03-JUN-05:02 | 26.00 | 26.00 | 0.00 | 0.00 | 01-JUN-00:10 | 26.00 | 26.00 |
July | 0.731854E+10 | 7848.83 | 18-JUL-05:15 | 24.30 | 23.55 | 0.00 | 0.00 | 01-JUL-00:10 | 24.30 | 23.55 |
August | 0.761314E+10 | 7050.82 | 22-AUG-05:15 | 24.00 | 24.00 | 0.00 | 0.00 | 01-AUG-00:10 | 24.00 | 24.00 |
September | 0.702478E+10 | 7361.28 | 06-SEP-05:15 | 25.07 | 24.22 | 0.00 | 0.00 | 01-SEP-00:10 | 25.07 | 24.22 |
October | 0.688448E+10 | 9968.46 | 10-OCT-05:13 | 24.00 | 23.51 | 0.00 | 0.00 | 01-OCT-00:10 | 24.00 | 23.51 |
November | 0.692656E+10 | 9636.01 | 13-NOV-06:15 | 25.27 | 24.33 | 0.00 | 0.00 | 01-NOV-00:10 | 25.27 | 24.33 |
December | 0.679330E+10 | 9040.88 | 18-DEC-06:15 | 23.13 | 23.13 | 0.00 | 0.00 | 01-DEC-00:10 | 23.13 | 23.13 |
Annual Sum or Average | 0.891163E+11 | 0.00 | ||||||||
Minimum of Months | 0.679330E+10 | 7050.82 | 22.23 | 20.03 | 0.00 | 0.00 | 22.23 | 20.03 | ||
Maximum of Months | 0.832665E+10 | 12927.38 | 27.00 | 26.00 | 0.00 | 0.00 | 27.00 | 26.00 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127887E+11 | 17255.39 | 04-JAN-13:10 | 34.08 | 23.62 | 0.00 | 0.00 | 01-JAN-00:10 | 34.08 | 23.62 |
February | 0.131638E+11 | 19035.75 | 21-FEB-14:10 | 34.83 | 21.98 | 0.00 | 0.00 | 01-FEB-00:10 | 34.83 | 21.98 |
March | 0.167834E+11 | 20867.41 | 29-MAR-14:00 | 36.00 | 23.48 | 0.00 | 0.00 | 01-MAR-00:10 | 36.00 | 23.48 |
April | 0.166151E+11 | 21671.90 | 11-APR-13:50 | 34.83 | 26.30 | 0.00 | 0.00 | 01-APR-00:10 | 34.83 | 26.30 |
May | 0.162117E+11 | 21398.06 | 05-MAY-13:10 | 36.33 | 27.23 | 0.00 | 0.00 | 01-MAY-00:10 | 36.33 | 27.23 |
June | 0.168320E+11 | 19890.79 | 16-JUN-14:00 | 36.00 | 27.59 | 0.00 | 0.00 | 01-JUN-00:10 | 36.00 | 27.59 |
July | 0.139480E+11 | 18996.58 | 14-JUL-14:00 | 32.00 | 24.80 | 0.00 | 0.00 | 01-JUL-00:10 | 32.00 | 24.80 |
August | 0.143053E+11 | 20065.38 | 14-AUG-13:30 | 33.40 | 27.60 | 0.00 | 0.00 | 01-AUG-00:10 | 33.40 | 27.60 |
September | 0.136904E+11 | 20365.95 | 06-SEP-14:10 | 33.83 | 26.60 | 0.00 | 0.00 | 01-SEP-00:10 | 33.83 | 26.60 |
October | 0.120825E+11 | 17831.53 | 04-OCT-13:30 | 32.65 | 26.30 | 0.00 | 0.00 | 01-OCT-00:10 | 32.65 | 26.30 |
November | 0.122370E+11 | 16510.54 | 22-NOV-13:10 | 31.50 | 24.57 | 0.00 | 0.00 | 01-NOV-00:10 | 31.50 | 24.57 |
December | 0.119575E+11 | 16752.79 | 08-DEC-14:10 | 33.00 | 23.30 | 0.00 | 0.00 | 01-DEC-00:10 | 33.00 | 23.30 |
Annual Sum or Average | 0.170615E+12 | 0.00 | ||||||||
Minimum of Months | 0.119575E+11 | 16510.54 | 31.50 | 21.98 | 0.00 | 0.00 | 31.50 | 21.98 | ||
Maximum of Months | 0.168320E+11 | 21671.90 | 36.33 | 27.60 | 0.00 | 0.00 | 36.33 | 27.60 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.462542E+10 | 2166.41 | 16-JAN-17:40 | 28.07 | 21.84 | 95231503.87 | 126.85 | 24-JAN-14:00 | 30.70 | 20.80 |
February | 0.870625E+10 | 3971.14 | 20-FEB-17:15 | 30.00 | 23.63 | 86418479.70 | 126.87 | 15-FEB-10:50 | 30.00 | 23.63 |
March | 0.146910E+11 | 7234.29 | 31-MAR-23:35 | 27.53 | 24.91 | 0.103252E+09 | 126.85 | 15-MAR-09:09 | 27.53 | 24.91 |
April | 0.190803E+11 | 7709.11 | 23-APR-17:55 | 30.50 | 24.94 | 92202706.42 | 131.57 | 18-APR-13:00 | 30.50 | 24.94 |
May | 0.461756E+10 | 3504.47 | 31-MAY-23:50 | 24.07 | 23.94 | 99233193.98 | 126.82 | 03-MAY-13:00 | 24.07 | 23.94 |
June | 0.935335E+10 | 5332.36 | 30-JUN-24:00 | 25.40 | 24.37 | 98995677.45 | 126.88 | 30-JUN-13:09 | 25.40 | 24.37 |
July | 0.146664E+11 | 7245.23 | 31-JUL-23:53 | 25.60 | 24.83 | 91898444.12 | 126.85 | 11-JUL-09:20 | 25.60 | 24.83 |
August | 0.196565E+11 | 7752.73 | 13-AUG-17:30 | 28.00 | 26.50 | 0.103788E+09 | 132.05 | 14-AUG-13:00 | 33.00 | 27.70 |
September | 0.444057E+10 | 3479.99 | 30-SEP-23:57 | 26.30 | 25.39 | 91605165.42 | 126.82 | 25-SEP-09:30 | 26.30 | 25.39 |
October | 0.960404E+10 | 5357.62 | 31-OCT-23:57 | 25.30 | 24.41 | 95265394.62 | 126.88 | 06-OCT-09:00 | 25.30 | 24.41 |
November | 0.141779E+11 | 5796.25 | 19-NOV-17:10 | 29.42 | 25.42 | 94318034.98 | 126.85 | 01-NOV-09:00 | 29.42 | 25.42 |
December | 0.196944E+11 | 7857.16 | 25-DEC-17:20 | 28.33 | 24.30 | 91884034.82 | 126.83 | 08-DEC-14:00 | 28.33 | 24.30 |
Annual Sum or Average | 0.143314E+12 | 0.114409E+10 | ||||||||
Minimum of Months | 0.444057E+10 | 2166.41 | 24.07 | 21.84 | 86418479.70 | 126.82 | 24.07 | 20.80 | ||
Maximum of Months | 0.196944E+11 | 7857.16 | 30.50 | 26.50 | 0.103788E+09 | 132.05 | 33.00 | 27.70 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.422890E+10 | 1981.20 | 16-JAN-17:40 | 28.07 | 21.84 | 95230423.09 | 126.82 | 23-JAN-10:09 | 26.40 | 20.55 |
February | 0.824360E+10 | 3692.60 | 20-FEB-17:22 | 30.00 | 23.63 | 86417503.96 | 126.87 | 15-FEB-14:00 | 30.00 | 23.63 |
March | 0.139898E+11 | 7010.24 | 31-MAR-24:00 | 27.60 | 24.97 | 0.103252E+09 | 126.85 | 15-MAR-09:09 | 27.60 | 24.97 |
April | 0.181612E+11 | 7305.39 | 23-APR-17:55 | 30.50 | 24.94 | 92503231.64 | 132.79 | 18-APR-13:00 | 30.50 | 24.94 |
May | 0.423543E+10 | 3383.72 | 31-MAY-23:57 | 24.10 | 23.98 | 99233194.77 | 126.82 | 23-MAY-09:39 | 24.10 | 23.98 |
June | 0.883890E+10 | 5085.56 | 30-JUN-24:00 | 25.40 | 24.37 | 98993271.53 | 126.88 | 30-JUN-13:09 | 25.40 | 24.37 |
July | 0.139448E+11 | 6968.67 | 31-JUL-23:53 | 25.60 | 24.83 | 91897838.78 | 126.85 | 03-JUL-13:09 | 25.60 | 24.83 |
August | 0.187295E+11 | 7297.42 | 13-AUG-17:15 | 28.00 | 26.50 | 0.104101E+09 | 132.88 | 10-AUG-13:00 | 28.00 | 26.50 |
September | 0.405297E+10 | 3404.06 | 30-SEP-23:57 | 26.30 | 25.39 | 91605166.61 | 126.82 | 25-SEP-09:20 | 26.30 | 25.39 |
October | 0.905842E+10 | 5096.05 | 31-OCT-23:57 | 25.30 | 24.41 | 95263194.27 | 126.87 | 30-OCT-13:20 | 25.30 | 24.41 |
November | 0.134861E+11 | 5488.79 | 20-NOV-17:00 | 30.00 | 25.17 | 94317602.28 | 126.85 | 13-NOV-10:09 | 30.00 | 25.17 |
December | 0.187655E+11 | 7366.12 | 25-DEC-16:52 | 29.00 | 23.94 | 91887637.34 | 127.23 | 08-DEC-14:00 | 29.00 | 23.94 |
Annual Sum or Average | 0.135735E+12 | 0.114470E+10 | ||||||||
Minimum of Months | 0.405297E+10 | 1981.20 | 24.10 | 21.84 | 86417503.96 | 126.82 | 24.10 | 20.55 | ||
Maximum of Months | 0.187655E+11 | 7366.12 | 30.50 | 26.50 | 0.104101E+09 | 132.88 | 30.50 | 26.50 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.430707E+10 | 2221.89 | 16-JAN-17:40 | 28.07 | 21.84 | 95231045.13 | 126.85 | 24-JAN-14:00 | 30.70 | 20.80 |
February | 0.833752E+10 | 3986.70 | 20-FEB-16:55 | 30.00 | 23.63 | 86418393.23 | 126.87 | 14-FEB-14:20 | 30.00 | 23.63 |
March | 0.141205E+11 | 6991.86 | 31-MAR-24:00 | 27.60 | 24.97 | 0.103252E+09 | 126.85 | 15-MAR-09:09 | 27.60 | 24.97 |
April | 0.183183E+11 | 7509.95 | 23-APR-17:55 | 30.50 | 24.94 | 92278726.53 | 132.27 | 18-APR-13:00 | 30.50 | 24.94 |
May | 0.441521E+10 | 3408.86 | 31-MAY-23:57 | 24.10 | 23.98 | 99233198.10 | 126.82 | 03-MAY-13:00 | 24.10 | 23.98 |
June | 0.900203E+10 | 5033.80 | 30-JUN-24:00 | 25.40 | 24.37 | 98995389.08 | 126.88 | 01-JUN-13:00 | 25.40 | 24.37 |
July | 0.140745E+11 | 6974.37 | 31-JUL-23:53 | 25.60 | 24.83 | 91899061.20 | 126.86 | 03-JUL-13:09 | 25.60 | 24.83 |
August | 0.188343E+11 | 7542.31 | 13-AUG-17:10 | 28.00 | 26.50 | 0.103796E+09 | 132.31 | 14-AUG-13:00 | 33.00 | 27.70 |
September | 0.419545E+10 | 3400.37 | 30-SEP-23:57 | 26.30 | 25.39 | 91605169.28 | 126.82 | 25-SEP-09:30 | 26.30 | 25.39 |
October | 0.916072E+10 | 5078.78 | 31-OCT-23:57 | 25.30 | 24.41 | 95264817.75 | 126.88 | 06-OCT-13:00 | 25.30 | 24.41 |
November | 0.135653E+11 | 5758.75 | 19-NOV-16:55 | 29.50 | 25.36 | 94318747.91 | 126.85 | 13-NOV-10:09 | 29.50 | 25.36 |
December | 0.188295E+11 | 7616.52 | 24-DEC-17:12 | 28.33 | 23.35 | 91885065.12 | 126.85 | 08-DEC-14:00 | 28.33 | 23.35 |
Annual Sum or Average | 0.137160E+12 | 0.114418E+10 | ||||||||
Minimum of Months | 0.419545E+10 | 2221.89 | 24.10 | 21.84 | 86418393.23 | 126.82 | 24.10 | 20.80 | ||
Maximum of Months | 0.188343E+11 | 7616.52 | 30.50 | 26.50 | 0.103796E+09 | 132.31 | 33.00 | 27.70 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243093E+12 | 92975.48 | 17-JAN-17:00 | 28.50 | 21.82 | 0.206144E+10 | 2745.29 | 10-JAN-10:00 | 28.50 | 21.82 |
February | 0.439993E+12 | 184430.69 | 21-FEB-17:00 | 31.30 | 23.84 | 0.187022E+10 | 2745.29 | 21-FEB-14:30 | 31.30 | 23.84 |
March | 0.732742E+12 | 360014.20 | 31-MAR-24:00 | 27.60 | 24.97 | 0.223475E+10 | 2745.29 | 27-MAR-09:30 | 27.60 | 24.97 |
April | 0.945835E+12 | 367806.93 | 03-APR-16:00 | 31.50 | 24.56 | 0.198297E+10 | 2745.29 | 03-APR-09:09 | 31.50 | 24.56 |
May | 0.243983E+12 | 177076.70 | 31-MAY-23:53 | 24.10 | 23.98 | 0.214810E+10 | 2745.29 | 03-MAY-13:09 | 24.10 | 23.98 |
June | 0.472476E+12 | 268456.53 | 30-JUN-24:00 | 25.40 | 24.37 | 0.214213E+10 | 2745.29 | 14-JUN-09:50 | 25.40 | 24.37 |
July | 0.733571E+12 | 360582.58 | 31-JUL-23:57 | 25.60 | 24.83 | 0.198894E+10 | 2745.29 | 03-JUL-09:09 | 25.60 | 24.83 |
August | 0.978390E+12 | 368142.12 | 28-AUG-16:00 | 31.20 | 26.59 | 0.223475E+10 | 2745.29 | 02-AUG-13:09 | 31.20 | 26.59 |
September | 0.236348E+12 | 176651.44 | 30-SEP-23:53 | 26.30 | 25.39 | 0.198297E+10 | 2745.29 | 01-SEP-13:50 | 26.30 | 25.39 |
October | 0.487481E+12 | 268348.59 | 31-OCT-23:53 | 25.30 | 24.41 | 0.206144E+10 | 2745.29 | 12-OCT-09:00 | 25.30 | 24.41 |
November | 0.709211E+12 | 276043.41 | 20-NOV-17:00 | 30.00 | 25.17 | 0.204131E+10 | 2745.29 | 02-NOV-09:20 | 30.00 | 25.17 |
December | 0.978570E+12 | 368112.28 | 26-DEC-17:00 | 29.00 | 22.59 | 0.198894E+10 | 2745.29 | 15-DEC-10:20 | 29.00 | 22.59 |
Annual Sum or Average | 0.720169E+13 | 0.247380E+11 | ||||||||
Minimum of Months | 0.236348E+12 | 92975.48 | 24.10 | 21.82 | 0.187022E+10 | 2745.29 | 24.10 | 21.82 | ||
Maximum of Months | 0.978570E+12 | 368142.12 | 31.50 | 26.59 | 0.223475E+10 | 2745.29 | 31.50 | 26.59 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.565544E+09 | 17090.51 | 28-JAN-16:03 | 31.42 |
February | 0.560950E+09 | 18657.87 | 04-FEB-16:03 | 32.50 |
March | 0.551839E+09 | 20213.73 | 25-MAR-15:02 | 33.62 |
April | 0.628017E+09 | 22017.79 | 01-APR-15:02 | 34.87 |
May | 0.614272E+09 | 24602.86 | 06-MAY-15:02 | 36.65 |
June | 0.505110E+09 | 20801.82 | 10-JUN-15:02 | 34.00 |
July | 0.659527E+09 | 19365.66 | 15-JUL-15:02 | 33.03 |
August | 0.487712E+09 | 19682.41 | 13-AUG-14:24 | 34.00 |
September | 0.589675E+09 | 19163.74 | 02-SEP-15:02 | 32.83 |
October | 0.536202E+09 | 16358.04 | 14-OCT-15:02 | 30.85 |
November | 0.463499E+09 | 15754.98 | 04-NOV-15:02 | 30.47 |
December | 0.460754E+09 | 17013.21 | 31-DEC-13:44 | 32.00 |
Annual Sum or Average | 0.662310E+10 | |||
Minimum of Months | 0.460754E+09 | 15754.98 | 30.47 | |
Maximum of Months | 0.659527E+09 | 24602.86 | 36.65 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 48269861.51 | 5950.67 | 12-JAN-04:02 | 24.17 |
February | 42371430.28 | 3933.13 | 08-FEB-04:02 | 23.83 |
March | 36796209.82 | 5459.41 | 26-MAR-14:22 | 34.50 |
April | 40459799.71 | 5407.12 | 02-APR-15:01 | 34.75 |
May | 45733399.51 | 6519.57 | 18-MAY-03:02 | 25.67 |
June | 39445950.43 | 4430.16 | 04-JUN-13:52 | 33.00 |
July | 48098719.09 | 3993.79 | 12-JUL-03:02 | 24.00 |
August | 50108889.06 | 5250.89 | 27-AUG-15:41 | 32.83 |
September | 42479915.65 | 6579.25 | 19-SEP-03:02 | 24.65 |
October | 57601735.42 | 6497.47 | 20-OCT-03:02 | 25.00 |
November | 54711943.26 | 3636.15 | 19-NOV-14:52 | 31.50 |
December | 53867190.99 | 4615.43 | 03-DEC-14:12 | 31.00 |
Annual Sum or Average | 0.559945E+09 | |||
Minimum of Months | 36796209.82 | 3636.15 | 23.83 | |
Maximum of Months | 57601735.42 | 6579.25 | 34.75 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28342097.63 | 4018.34 | 05-JAN-04:02 | 24.63 |
February | 25515149.43 | 4252.52 | 06-FEB-04:02 | 23.58 |
March | 30136148.92 | 5215.39 | 17-MAR-03:02 | 25.98 |
April | 28050999.98 | 5524.29 | 11-APR-03:02 | 27.00 |
May | 30695634.43 | 5719.97 | 22-MAY-03:02 | 27.00 |
June | 31097428.20 | 5118.99 | 28-JUN-03:02 | 26.07 |
July | 23812122.54 | 5117.99 | 14-JUL-03:02 | 25.70 |
August | 25962056.73 | 5597.29 | 21-AUG-03:02 | 24.03 |
September | 25066514.71 | 6229.71 | 18-SEP-03:02 | 25.50 |
October | 29457487.81 | 4888.34 | 05-OCT-03:02 | 26.00 |
November | 29167780.60 | 4813.95 | 03-NOV-03:02 | 26.00 |
December | 29865280.75 | 5351.55 | 18-DEC-04:03 | 23.67 |
Annual Sum or Average | 0.337169E+09 | |||
Minimum of Months | 23812122.54 | 4018.34 | 23.58 | |
Maximum of Months | 31097428.20 | 6229.71 | 27.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55228726.88 | 9710.29 | 23-JAN-04:02 | 19.75 |
February | 43037304.26 | 9154.94 | 13-FEB-04:02 | 23.73 |
March | 34166518.24 | 6142.19 | 10-MAR-04:02 | 25.08 |
April | 23652239.21 | 7592.10 | 10-APR-03:02 | 25.03 |
May | 20292880.19 | 6296.54 | 22-MAY-03:02 | 27.00 |
June | 16892923.57 | 7183.76 | 05-JUN-03:02 | 25.85 |
July | 27718239.00 | 7806.80 | 17-JUL-03:02 | 24.92 |
August | 29396375.04 | 6561.83 | 07-AUG-03:02 | 24.98 |
September | 26965735.86 | 7244.06 | 18-SEP-03:02 | 25.50 |
October | 32237004.86 | 7832.69 | 02-OCT-03:02 | 24.00 |
November | 35927908.80 | 8309.48 | 13-NOV-04:02 | 25.00 |
December | 56913369.47 | 10870.95 | 21-DEC-06:02 | 18.07 |
Annual Sum or Average | 0.402429E+09 | |||
Minimum of Months | 16892923.57 | 6142.19 | 18.07 | |
Maximum of Months | 56913369.47 | 10870.95 | 27.00 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:05 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113123E+11 | 11837.83 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.102611E+11 | 11837.83 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.121930E+11 | 11837.83 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.108909E+11 | 11837.83 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.117527E+11 | 11837.83 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.116958E+11 | 11837.83 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.109477E+11 | 11837.83 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.121930E+11 | 11837.83 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.108909E+11 | 11837.83 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.113123E+11 | 11837.83 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.111797E+11 | 11837.83 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.109477E+11 | 11837.83 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.135577E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.102611E+11 | 11837.83 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.121930E+11 | 11837.83 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.757902E+09 | 1077.00 | 02-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.677174E+09 | 830.54 | 07-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.781292E+09 | 903.92 | 01-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.685138E+09 | 708.67 | 21-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.737833E+09 | 718.02 | 17-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.726177E+09 | 700.74 | 20-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.686907E+09 | 706.61 | 11-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.765058E+09 | 712.68 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.698586E+09 | 712.91 | 21-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.734201E+09 | 742.63 | 30-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.754540E+09 | 1132.26 | 27-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.745243E+09 | 1150.73 | 18-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.875005E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.677174E+09 | 700.74 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.781292E+09 | 1150.73 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.489102E+09 | 718.03 | 02-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.438207E+09 | 627.92 | 07-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.505203E+09 | 626.55 | 01-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.444731E+09 | 454.09 | 13-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.480375E+09 | 462.93 | 22-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.473859E+09 | 450.50 | 01-JUN-15:00 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.448092E+09 | 459.58 | 17-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.496603E+09 | 453.56 | 24-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.452303E+09 | 463.13 | 22-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.474141E+09 | 568.55 | 30-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.488669E+09 | 749.14 | 27-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.480897E+09 | 751.51 | 18-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.567218E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.438207E+09 | 450.50 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.505203E+09 | 751.51 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.740178E+09 | 954.17 | 02-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.668077E+09 | 741.60 | 01-FEB-17:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.778318E+09 | 743.71 | 01-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.689678E+09 | 717.08 | 21-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.747015E+09 | 735.14 | 17-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.737643E+09 | 728.38 | 20-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.698155E+09 | 731.05 | 11-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.771725E+09 | 727.42 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.698720E+09 | 713.51 | 21-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.726490E+09 | 725.36 | 23-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.736178E+09 | 1061.38 | 09-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.724745E+09 | 1114.01 | 18-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.871692E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.668077E+09 | 713.51 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.778318E+09 | 1114.01 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.479035E+09 | 574.07 | 02-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.431202E+09 | 477.90 | 01-FEB-17:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.501318E+09 | 536.53 | 15-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.443853E+09 | 477.69 | 21-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.479617E+09 | 554.03 | 17-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.472357E+09 | 478.51 | 20-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.448344E+09 | 539.78 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.496819E+09 | 543.58 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.451454E+09 | 478.27 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.470926E+09 | 572.80 | 23-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.474939E+09 | 653.13 | 09-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.468000E+09 | 697.66 | 18-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.561786E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.431202E+09 | 477.69 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.501318E+09 | 697.66 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.758045E+09 | 1082.30 | 02-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.677107E+09 | 840.63 | 07-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.781334E+09 | 912.85 | 01-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.685226E+09 | 706.10 | 21-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.738016E+09 | 715.70 | 17-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.726276E+09 | 698.03 | 20-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.687082E+09 | 704.04 | 11-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.765249E+09 | 710.24 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.698696E+09 | 710.41 | 21-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.734262E+09 | 821.79 | 30-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.754748E+09 | 1136.54 | 27-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.745422E+09 | 1154.63 | 18-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.875146E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.677107E+09 | 698.03 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.781334E+09 | 1154.63 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.488943E+09 | 718.34 | 02-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.437995E+09 | 628.28 | 07-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.505105E+09 | 626.95 | 01-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.444630E+09 | 451.68 | 13-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.480211E+09 | 460.85 | 22-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.473741E+09 | 447.92 | 01-JUN-15:00 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.447826E+09 | 457.40 | 17-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.496440E+09 | 451.14 | 24-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.452109E+09 | 461.03 | 22-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.473881E+09 | 569.08 | 30-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.488604E+09 | 749.42 | 27-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.480769E+09 | 751.75 | 18-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.567025E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.437995E+09 | 447.92 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.505105E+09 | 751.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.738522E+09 | 948.64 | 02-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.668099E+09 | 741.60 | 01-FEB-17:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.778414E+09 | 741.96 | 01-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.689794E+09 | 714.62 | 21-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.747167E+09 | 733.02 | 17-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.737805E+09 | 726.06 | 20-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.698143E+09 | 728.83 | 11-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.771718E+09 | 725.16 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.698867E+09 | 711.01 | 21-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.726602E+09 | 723.20 | 23-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.737033E+09 | 1081.41 | 09-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.723942E+09 | 1115.19 | 18-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.871611E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.668099E+09 | 711.01 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.778414E+09 | 1115.19 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.478914E+09 | 575.94 | 02-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.431121E+09 | 477.90 | 01-FEB-17:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.501188E+09 | 537.29 | 15-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.443785E+09 | 476.09 | 21-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.479341E+09 | 554.48 | 17-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.472308E+09 | 527.04 | 20-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.448124E+09 | 540.23 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.496720E+09 | 543.97 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.451196E+09 | 476.69 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.471011E+09 | 573.21 | 23-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.474828E+09 | 654.43 | 09-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.467959E+09 | 698.54 | 18-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.561650E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.431121E+09 | 476.09 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.501188E+09 | 698.54 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.758027E+09 | 1082.10 | 02-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.677046E+09 | 840.38 | 07-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.781307E+09 | 912.48 | 01-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.685221E+09 | 705.90 | 21-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.738219E+09 | 715.51 | 17-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.726261E+09 | 697.82 | 20-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.687073E+09 | 703.83 | 11-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.765224E+09 | 710.04 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.698654E+09 | 710.22 | 21-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.734274E+09 | 821.33 | 30-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.754718E+09 | 1136.39 | 27-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.745368E+09 | 1154.45 | 18-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.875139E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.677046E+09 | 697.82 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.781307E+09 | 1154.45 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.488926E+09 | 718.21 | 02-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.437991E+09 | 628.14 | 07-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.505102E+09 | 626.73 | 01-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.444621E+09 | 451.55 | 13-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.480185E+09 | 460.74 | 22-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.473736E+09 | 447.80 | 01-JUN-15:00 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.447806E+09 | 457.28 | 17-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.496432E+09 | 451.02 | 24-AUG-15:00 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.452107E+09 | 460.92 | 22-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.473889E+09 | 568.80 | 30-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.488581E+09 | 749.33 | 27-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.480732E+09 | 751.65 | 18-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.567011E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.437991E+09 | 447.80 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.505102E+09 | 751.65 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.738503E+09 | 948.44 | 02-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.668079E+09 | 741.60 | 01-FEB-17:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.778397E+09 | 741.82 | 01-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.689787E+09 | 714.43 | 21-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.747138E+09 | 732.87 | 17-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.737792E+09 | 725.90 | 20-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.698122E+09 | 728.67 | 11-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.771697E+09 | 725.00 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.698852E+09 | 710.82 | 21-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.726587E+09 | 723.03 | 23-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.737026E+09 | 1081.25 | 09-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.723941E+09 | 1115.02 | 18-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.871592E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.668079E+09 | 710.82 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.778397E+09 | 1115.02 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.478914E+09 | 575.87 | 02-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.431138E+09 | 477.90 | 01-FEB-17:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.501181E+09 | 537.17 | 15-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.443783E+09 | 476.00 | 21-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.479331E+09 | 554.19 | 17-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.472302E+09 | 526.73 | 20-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.448113E+09 | 539.94 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.496689E+09 | 543.68 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.451186E+09 | 476.60 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.470960E+09 | 572.94 | 23-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.474824E+09 | 654.37 | 09-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.467956E+09 | 698.45 | 18-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.561638E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.431138E+09 | 476.00 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.501181E+09 | 698.45 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.318958E+10 | 3337.76 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.289319E+10 | 3337.76 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.343791E+10 | 3337.76 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.307076E+10 | 3337.76 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.331375E+10 | 3337.76 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.329773E+10 | 3337.76 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.308678E+10 | 3337.76 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.343791E+10 | 3337.76 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.307076E+10 | 3337.76 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.318958E+10 | 3337.76 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.315220E+10 | 3337.76 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.308678E+10 | 3337.76 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.382269E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.289319E+10 | 3337.76 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.343791E+10 | 3337.76 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.113123E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.102611E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.108909E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.117527E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.116958E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.109477E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.108909E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.113123E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.111797E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.109477E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.135577E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.102611E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.757902E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10182787.07 | 6339466.03 |
February | 0.136985E+10 | 0.677174E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15097949.70 | 943866.40 |
March | 0.163685E+10 | 0.781292E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27707488.42 | 1205935.71 |
April | 0.145243E+10 | 0.685138E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27620724.92 | 134133.15 |
May | 0.157338E+10 | 0.737833E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28903519.80 | 1269527.98 |
June | 0.156900E+10 | 0.726177E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26141196.57 | 1189649.31 |
July | 0.145680E+10 | 0.686907E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15831072.53 | 750756.65 |
August | 0.163685E+10 | 0.765058E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19652858.82 | 1379268.98 |
September | 0.145243E+10 | 0.698586E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14420531.63 | 1400208.73 |
October | 0.150991E+10 | 0.734201E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11694562.18 | 1808645.16 |
November | 0.149516E+10 | 0.754540E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9085271.19 | 2350705.95 |
December | 0.145680E+10 | 0.745243E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8317102.88 | 5984685.10 |
Annual Sum or Average | 0.181194E+11 | 0.875005E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214655E+09 | 24756849.18 |
Minimum of Months | 0.136985E+10 | 0.677174E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8317102.88 | 134133.15 |
Maximum of Months | 0.163685E+10 | 0.781292E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28903519.80 | 6339466.03 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.489102E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6618385.26 | 4264527.02 |
February | 0.882782E+09 | 0.438207E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10000894.92 | 596868.82 |
March | 0.105485E+10 | 0.505203E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18696010.54 | 622617.32 |
April | 0.936002E+09 | 0.444731E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19193809.16 | 42277.37 |
May | 0.101394E+10 | 0.480375E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19854674.72 | 709328.48 |
June | 0.101113E+10 | 0.473859E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18622160.49 | 600926.24 |
July | 0.938820E+09 | 0.448092E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11449413.16 | 304373.88 |
August | 0.105485E+10 | 0.496603E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14129705.93 | 514080.61 |
September | 0.936002E+09 | 0.452303E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9444028.01 | 896103.32 |
October | 0.973041E+09 | 0.474141E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7833600.77 | 1001908.49 |
November | 0.963541E+09 | 0.488669E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6153883.00 | 1244869.12 |
December | 0.938820E+09 | 0.480897E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5639996.42 | 3454379.53 |
Annual Sum or Average | 0.116768E+11 | 0.567218E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147637E+09 | 14252260.18 |
Minimum of Months | 0.882782E+09 | 0.438207E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5639996.42 | 42277.37 |
Maximum of Months | 0.105485E+10 | 0.505203E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19854674.72 | 4264527.02 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.740178E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9017064.31 | 7783475.51 |
February | 0.136988E+10 | 0.668077E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13723353.37 | 1443559.67 |
March | 0.163688E+10 | 0.778318E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26222306.15 | 1453738.70 |
April | 0.145246E+10 | 0.689678E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27835882.44 | 131802.66 |
May | 0.157341E+10 | 0.747015E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29912370.23 | 1142495.44 |
June | 0.156904E+10 | 0.737643E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27753790.95 | 1035751.87 |
July | 0.145684E+10 | 0.698155E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16600033.94 | 620653.97 |
August | 0.163688E+10 | 0.771725E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20271270.40 | 1260460.54 |
September | 0.145246E+10 | 0.698720E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14139312.61 | 1428896.26 |
October | 0.150994E+10 | 0.726490E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10821047.47 | 2200531.62 |
November | 0.149520E+10 | 0.736178E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8133909.76 | 2998837.19 |
December | 0.145684E+10 | 0.724745E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7236288.75 | 7137206.69 |
Annual Sum or Average | 0.181198E+11 | 0.871692E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211667E+09 | 28637410.12 |
Minimum of Months | 0.136988E+10 | 0.668077E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7236288.75 | 131802.66 |
Maximum of Months | 0.163688E+10 | 0.778318E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29912370.23 | 7783475.51 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.479035E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6154073.40 | 5785959.01 |
February | 0.882782E+09 | 0.431202E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8836627.11 | 1654115.94 |
March | 0.105485E+10 | 0.501318E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15130542.18 | 2491853.32 |
April | 0.936002E+09 | 0.443853E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14959961.58 | 523130.39 |
May | 0.101394E+10 | 0.479617E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18227152.95 | 1317168.95 |
June | 0.101113E+10 | 0.472357E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16247395.23 | 1189238.70 |
July | 0.938820E+09 | 0.448344E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9507720.47 | 1150837.12 |
August | 0.105485E+10 | 0.496819E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11167929.50 | 2798289.75 |
September | 0.936002E+09 | 0.451454E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8696234.20 | 1652926.26 |
October | 0.973041E+09 | 0.470926E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6811767.87 | 2391200.16 |
November | 0.963541E+09 | 0.474939E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5176478.35 | 3111519.99 |
December | 0.938820E+09 | 0.468000E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4729499.96 | 6372630.90 |
Annual Sum or Average | 0.116768E+11 | 0.561786E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125645E+09 | 30438870.48 |
Minimum of Months | 0.882782E+09 | 0.431202E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4729499.96 | 523130.39 |
Maximum of Months | 0.105485E+10 | 0.501318E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18227152.95 | 6372630.90 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.758045E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23800475.38 | 15747215.84 |
February | 0.136985E+10 | 0.677107E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33666941.14 | 4177064.87 |
March | 0.163685E+10 | 0.781334E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59861589.40 | 5553928.52 |
April | 0.145243E+10 | 0.685226E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61142616.31 | 915712.49 |
May | 0.157338E+10 | 0.738016E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63381124.24 | 3577829.09 |
June | 0.156900E+10 | 0.726276E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56437766.63 | 4104376.45 |
July | 0.145680E+10 | 0.687082E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34242998.62 | 3700523.85 |
August | 0.163685E+10 | 0.765249E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42200874.51 | 6803640.24 |
September | 0.145243E+10 | 0.698696E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32126899.43 | 3729878.89 |
October | 0.150991E+10 | 0.734262E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25919535.40 | 6174269.13 |
November | 0.149516E+10 | 0.754748E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20363940.46 | 8523843.50 |
December | 0.145680E+10 | 0.745422E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19323057.28 | 17481615.35 |
Annual Sum or Average | 0.181194E+11 | 0.875146E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472468E+09 | 80489898.21 |
Minimum of Months | 0.136985E+10 | 0.677107E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19323057.28 | 915712.49 |
Maximum of Months | 0.163685E+10 | 0.781334E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63381124.24 | 17481615.35 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.488943E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14872607.06 | 11648169.57 |
February | 0.649041E+09 | 0.437995E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21134107.17 | 3557549.36 |
March | 0.773965E+09 | 0.505105E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37396657.74 | 4642160.55 |
April | 0.688021E+09 | 0.444630E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38831847.31 | 755785.83 |
May | 0.744847E+09 | 0.480211E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42649128.23 | 2328047.60 |
June | 0.742030E+09 | 0.473741E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39127562.84 | 2539526.97 |
July | 0.690839E+09 | 0.447826E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23281834.97 | 2310114.63 |
August | 0.773965E+09 | 0.496440E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27646326.32 | 4735655.40 |
September | 0.688021E+09 | 0.452109E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20264404.63 | 2927787.70 |
October | 0.715730E+09 | 0.473881E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16280732.76 | 4678637.50 |
November | 0.708685E+09 | 0.488604E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12662497.31 | 6332672.75 |
December | 0.690839E+09 | 0.480769E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11848476.86 | 12571577.68 |
Annual Sum or Average | 0.858171E+10 | 0.567025E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305996E+09 | 59027685.55 |
Minimum of Months | 0.649041E+09 | 0.437995E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11848476.86 | 755785.83 |
Maximum of Months | 0.773965E+09 | 0.505105E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42649128.23 | 12571577.68 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.738522E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20179591.89 | 20631285.63 |
February | 0.136988E+10 | 0.668099E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30124529.58 | 6318027.13 |
March | 0.163688E+10 | 0.778414E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56109804.88 | 7008312.85 |
April | 0.145246E+10 | 0.689794E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61764867.63 | 883484.99 |
May | 0.157341E+10 | 0.747167E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66563383.56 | 3138484.34 |
June | 0.156904E+10 | 0.737805E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61484081.13 | 3365310.47 |
July | 0.145684E+10 | 0.698143E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36646371.50 | 2869897.41 |
August | 0.163688E+10 | 0.771718E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43859472.12 | 6178246.27 |
September | 0.145246E+10 | 0.698867E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31508148.67 | 3949350.28 |
October | 0.150994E+10 | 0.726602E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23630950.58 | 7721124.51 |
November | 0.149520E+10 | 0.737033E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17754966.98 | 10977028.38 |
December | 0.145684E+10 | 0.723942E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15991590.75 | 21736279.80 |
Annual Sum or Average | 0.181198E+11 | 0.871611E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465618E+09 | 94776832.07 |
Minimum of Months | 0.136988E+10 | 0.668099E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15991590.75 | 883484.99 |
Maximum of Months | 0.163688E+10 | 0.778414E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66563383.56 | 21736279.80 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.478914E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14312796.35 | 13329025.97 |
February | 0.882782E+09 | 0.431121E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20474627.56 | 4750833.86 |
March | 0.105485E+10 | 0.501188E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34886177.28 | 7365067.63 |
April | 0.936002E+09 | 0.443785E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35218108.31 | 1334125.09 |
May | 0.101394E+10 | 0.479341E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40746296.12 | 2959604.93 |
June | 0.101113E+10 | 0.472308E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36932049.31 | 3193055.32 |
July | 0.938820E+09 | 0.448124E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22150003.86 | 3247838.52 |
August | 0.105485E+10 | 0.496720E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26333652.05 | 6724723.16 |
September | 0.936002E+09 | 0.451196E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19684275.95 | 3702090.42 |
October | 0.973041E+09 | 0.471011E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15727481.23 | 6011635.64 |
November | 0.963541E+09 | 0.474828E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12316323.71 | 7647862.10 |
December | 0.938820E+09 | 0.467959E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11367792.18 | 14448532.91 |
Annual Sum or Average | 0.116768E+11 | 0.561650E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290150E+09 | 74714395.55 |
Minimum of Months | 0.882782E+09 | 0.431121E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11367792.18 | 1334125.09 |
Maximum of Months | 0.105485E+10 | 0.501188E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40746296.12 | 14448532.91 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.758027E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27324445.81 | 20706338.16 |
February | 0.136985E+10 | 0.677046E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39139671.62 | 5919750.26 |
March | 0.163685E+10 | 0.781307E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69663330.89 | 7797765.43 |
April | 0.145243E+10 | 0.685221E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70964898.54 | 1430521.53 |
May | 0.157338E+10 | 0.738219E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75055819.49 | 5257748.31 |
June | 0.156900E+10 | 0.726261E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67192020.30 | 6003519.98 |
July | 0.145680E+10 | 0.687073E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40106797.18 | 5482426.08 |
August | 0.163685E+10 | 0.765224E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49419493.36 | 9348091.98 |
September | 0.145243E+10 | 0.698654E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37311672.38 | 5337382.16 |
October | 0.150991E+10 | 0.734274E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29638085.73 | 8864650.63 |
November | 0.149516E+10 | 0.754718E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23246845.62 | 11370808.52 |
December | 0.145680E+10 | 0.745368E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21912403.07 | 22343363.48 |
Annual Sum or Average | 0.181194E+11 | 0.875139E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550975E+09 | 0.109862E+09 |
Minimum of Months | 0.136985E+10 | 0.677046E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21912403.07 | 1430521.53 |
Maximum of Months | 0.163685E+10 | 0.781307E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75055819.49 | 22343363.48 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.488926E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17341817.72 | 15330058.19 |
February | 0.882782E+09 | 0.437991E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25038578.71 | 4930086.97 |
March | 0.105485E+10 | 0.505102E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44266457.87 | 6430464.19 |
April | 0.936002E+09 | 0.444621E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45693541.19 | 1160264.96 |
May | 0.101394E+10 | 0.480185E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50660612.42 | 3423693.48 |
June | 0.101113E+10 | 0.473736E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46431788.21 | 3713309.07 |
July | 0.938820E+09 | 0.447806E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27212909.42 | 3426801.85 |
August | 0.105485E+10 | 0.496432E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32642326.71 | 6477655.56 |
September | 0.936002E+09 | 0.452107E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23894841.75 | 4064475.38 |
October | 0.973041E+09 | 0.473889E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18955468.93 | 6524197.01 |
November | 0.963541E+09 | 0.488581E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14781453.28 | 8423238.55 |
December | 0.938820E+09 | 0.480732E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13759840.38 | 16164414.18 |
Annual Sum or Average | 0.116768E+11 | 0.567011E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360680E+09 | 80068659.41 |
Minimum of Months | 0.882782E+09 | 0.437991E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13759840.38 | 1160264.96 |
Maximum of Months | 0.105485E+10 | 0.505102E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50660612.42 | 16164414.18 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.738503E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24342704.17 | 26985340.14 |
February | 0.136988E+10 | 0.668079E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36119240.47 | 8679761.97 |
March | 0.163688E+10 | 0.778397E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66268951.65 | 9766640.33 |
April | 0.145246E+10 | 0.689787E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71735946.40 | 1374588.55 |
May | 0.157341E+10 | 0.747138E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78144899.44 | 4618591.34 |
June | 0.156904E+10 | 0.737792E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72408281.81 | 4979453.60 |
July | 0.145684E+10 | 0.698122E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42116092.94 | 4360905.29 |
August | 0.163688E+10 | 0.771697E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51192036.64 | 8453059.47 |
September | 0.145246E+10 | 0.698852E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36782233.50 | 5604415.19 |
October | 0.150994E+10 | 0.726587E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27677250.53 | 10718583.95 |
November | 0.149520E+10 | 0.737026E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21125351.77 | 14547060.56 |
December | 0.145684E+10 | 0.723941E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19244286.53 | 27998250.90 |
Annual Sum or Average | 0.181198E+11 | 0.871592E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547157E+09 | 0.128087E+09 |
Minimum of Months | 0.136988E+10 | 0.668079E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19244286.53 | 1374588.55 |
Maximum of Months | 0.163688E+10 | 0.778397E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78144899.44 | 27998250.90 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.478914E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17165994.05 | 17108270.84 |
February | 0.882782E+09 | 0.431138E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24719931.20 | 6241647.71 |
March | 0.105485E+10 | 0.501181E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42318551.71 | 9629944.94 |
April | 0.936002E+09 | 0.443783E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42726260.85 | 1856563.77 |
May | 0.101394E+10 | 0.479331E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49568640.94 | 4166277.36 |
June | 0.101113E+10 | 0.472302E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45051855.31 | 4380229.94 |
July | 0.938820E+09 | 0.448113E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26722629.81 | 4355338.36 |
August | 0.105485E+10 | 0.496689E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31852842.80 | 8709848.76 |
September | 0.936002E+09 | 0.451186E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23697173.31 | 4785823.31 |
October | 0.973041E+09 | 0.470960E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18785804.72 | 7827803.96 |
November | 0.963541E+09 | 0.474824E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14748977.70 | 9809498.14 |
December | 0.938820E+09 | 0.467956E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13664393.13 | 18267024.36 |
Annual Sum or Average | 0.116768E+11 | 0.561638E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351023E+09 | 97138271.45 |
Minimum of Months | 0.882782E+09 | 0.431138E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13664393.13 | 1856563.77 |
Maximum of Months | 0.105485E+10 | 0.501181E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49568640.94 | 18267024.36 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.318958E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.289319E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.343791E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.307076E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.331375E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.329773E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.308678E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.343791E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.307076E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.318958E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.315220E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.308678E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.382269E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.289319E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.343791E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17180407.22 | 14198459.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26771318.38 | 2692884.21 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48395357.31 | 3838939.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50584108.60 | 487022.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55773960.40 | 2275970.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50219472.73 | 2482312.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30839350.90 | 1744818.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35360550.24 | 3840559.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26511268.36 | 2357139.30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21194547.34 | 4365811.14 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15578300.19 | 6439141.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14084290.09 | 15207324.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392493E+09 | 59930383.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14084290.09 | 487022.69 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55773960.40 | 15207324.27 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31590899.64 | 25110138.52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48278292.56 | 5465125.86 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87245638.23 | 7563774.21 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93661996.87 | 955033.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101258E+09 | 3978743.23 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90851409.26 | 4617359.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56034392.53 | 3338833.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64209144.50 | 7215763.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48297788.54 | 3995578.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38293445.67 | 7992326.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28144346.33 | 12355662.10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25811935.10 | 27997872.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713677E+09 | 0.110586E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25811935.10 | 955033.41 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101258E+09 | 27997872.95 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28146446.80 | 28480260.83 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43908074.17 | 5921767.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81573795.74 | 8357307.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89654977.02 | 1258090.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99563582.04 | 5447674.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87488633.45 | 7110662.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46469375.70 | 5710521.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59381862.44 | 8974592.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42044800.39 | 6462392.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31393316.08 | 11761046.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23883034.14 | 15100977.82 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21378663.84 | 30850259.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654887E+09 | 0.135436E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21378663.84 | 1258090.98 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99563582.04 | 30850259.86 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 11837.83 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 11837.83 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 11837.83 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 11837.83 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 11837.83 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 11837.83 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 11837.83 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 11837.83 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 11837.83 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 11837.83 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 11837.83 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 11837.83 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 11837.83 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 11837.83 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1077.00 | 02-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.44 | 15-JAN-13:00 | 89.86 | 07-JAN-04:45 |
February | 2010.79 | 01-FEB-10:09 | 830.54 | 07-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.52 | 19-FEB-15:00 | 12.62 | 20-FEB-06:57 |
March | 2010.79 | 01-MAR-10:09 | 903.92 | 01-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 131.30 | 19-MAR-16:00 | 17.73 | 14-MAR-22:10 |
April | 2010.79 | 03-APR-09:09 | 708.67 | 21-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.60 | 30-APR-15:45 | 6.37 | 22-APR-03:20 |
May | 2010.79 | 01-MAY-09:09 | 718.02 | 17-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.04 | 07-MAY-14:42 | 43.09 | 08-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 700.74 | 20-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.01 | 18-JUN-14:25 | 33.57 | 20-JUN-22:53 |
July | 2010.79 | 03-JUL-09:09 | 706.61 | 11-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.28 | 04-JUL-13:58 | 16.39 | 02-JUL-13:40 |
August | 2010.79 | 01-AUG-09:09 | 712.68 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.99 | 06-AUG-12:33 | 35.03 | 20-AUG-11:00 |
September | 2010.79 | 01-SEP-09:09 | 712.91 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.87 | 10-SEP-15:00 | 26.76 | 15-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 742.63 | 30-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.56 | 29-OCT-13:00 | 15.70 | 23-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 1132.26 | 27-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.68 | 11-NOV-16:00 | 18.05 | 26-NOV-06:30 |
December | 2010.79 | 01-DEC-10:09 | 1150.73 | 18-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.32 | 24-DEC-15:00 | 36.41 | 21-DEC-04:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 700.74 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 31.32 | 6.37 | |||||
Maximum of Months | 2010.79 | 1150.73 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 131.30 | 89.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 718.03 | 02-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.10 | 15-JAN-13:00 | 58.94 | 07-JAN-04:45 |
February | 1295.83 | 01-FEB-10:09 | 627.92 | 07-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.88 | 19-FEB-15:00 | 12.16 | 20-FEB-06:57 |
March | 1295.83 | 01-MAR-10:09 | 626.55 | 01-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.08 | 19-MAR-16:00 | 11.13 | 14-MAR-21:30 |
April | 1295.83 | 03-APR-09:09 | 454.09 | 13-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.36 | 30-APR-15:47 | 3.39 | 23-APR-07:40 |
May | 1295.83 | 01-MAY-09:09 | 462.93 | 22-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.51 | 07-MAY-14:42 | 27.78 | 08-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 450.50 | 01-JUN-15:00 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.68 | 18-JUN-14:28 | 17.51 | 25-JUN-21:00 |
July | 1295.83 | 03-JUL-09:09 | 459.58 | 17-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.11 | 04-JUL-14:00 | 8.19 | 19-JUL-21:17 |
August | 1295.83 | 01-AUG-09:09 | 453.56 | 24-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.71 | 06-AUG-12:33 | 21.43 | 20-AUG-11:00 |
September | 1295.83 | 01-SEP-09:09 | 463.13 | 22-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.19 | 10-SEP-14:52 | 16.80 | 15-SEP-22:00 |
October | 1295.83 | 02-OCT-09:09 | 568.55 | 30-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.24 | 29-OCT-13:20 | 9.11 | 23-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 749.14 | 27-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.20 | 11-NOV-16:00 | 11.02 | 25-NOV-05:30 |
December | 1295.83 | 01-DEC-10:09 | 751.51 | 18-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.68 | 24-DEC-15:00 | 22.80 | 21-DEC-04:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 450.50 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 21.68 | 3.39 | |||||
Maximum of Months | 1295.83 | 751.51 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 88.08 | 58.94 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 954.17 | 02-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.13 | 15-JAN-13:00 | 97.83 | 07-JAN-04:45 |
February | 2010.83 | 01-FEB-10:09 | 741.60 | 01-FEB-17:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.42 | 19-FEB-14:53 | 15.34 | 20-FEB-06:57 |
March | 2010.83 | 01-MAR-10:09 | 743.71 | 01-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 128.84 | 19-MAR-16:00 | 18.52 | 03-MAR-05:30 |
April | 2010.83 | 03-APR-09:09 | 717.08 | 21-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.53 | 30-APR-15:47 | 6.35 | 22-APR-03:20 |
May | 2010.83 | 01-MAY-09:09 | 735.14 | 17-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.90 | 07-MAY-14:42 | 41.32 | 08-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 728.38 | 20-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.00 | 18-JUN-14:28 | 30.32 | 20-JUN-22:53 |
July | 2010.83 | 03-JUL-09:09 | 731.05 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.11 | 04-JUL-14:00 | 13.16 | 19-JUL-21:17 |
August | 2010.83 | 01-AUG-09:09 | 727.42 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.56 | 06-AUG-12:33 | 34.50 | 20-AUG-11:00 |
September | 2010.83 | 01-SEP-09:09 | 713.51 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.44 | 10-SEP-14:52 | 26.63 | 15-SEP-22:00 |
October | 2010.83 | 02-OCT-09:09 | 725.36 | 23-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.57 | 29-OCT-13:16 | 16.45 | 23-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1061.38 | 09-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.48 | 11-NOV-15:38 | 19.28 | 26-NOV-06:30 |
December | 2010.83 | 01-DEC-10:09 | 1114.01 | 18-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.61 | 31-DEC-13:00 | 38.08 | 21-DEC-04:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 713.51 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 27.61 | 6.35 | |||||
Maximum of Months | 2010.83 | 1114.01 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 128.84 | 97.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 574.07 | 02-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.48 | 15-JAN-13:00 | 75.71 | 07-JAN-04:45 |
February | 1295.83 | 01-FEB-10:09 | 477.90 | 01-FEB-17:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.94 | 19-FEB-14:53 | 12.29 | 20-FEB-06:57 |
March | 1295.83 | 01-MAR-10:09 | 536.53 | 15-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.13 | 19-MAR-16:00 | 18.59 | 14-MAR-22:10 |
April | 1295.83 | 03-APR-09:09 | 477.69 | 21-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.96 | 02-APR-15:50 | 14.38 | 09-APR-16:20 |
May | 1295.83 | 01-MAY-09:09 | 554.03 | 17-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.08 | 07-MAY-14:42 | 34.97 | 08-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 478.51 | 20-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.39 | 18-JUN-14:25 | 26.93 | 20-JUN-23:20 |
July | 1295.83 | 03-JUL-09:09 | 539.78 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.22 | 04-JUL-13:55 | 16.72 | 02-JUL-13:40 |
August | 1295.83 | 01-AUG-09:09 | 543.58 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.18 | 06-AUG-13:05 | 32.65 | 20-AUG-11:00 |
September | 1295.83 | 01-SEP-09:09 | 478.27 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.08 | 10-SEP-14:52 | 23.57 | 15-SEP-22:00 |
October | 1295.83 | 02-OCT-09:09 | 572.80 | 23-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.26 | 29-OCT-13:16 | 16.38 | 23-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 653.13 | 09-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.73 | 11-NOV-15:38 | 17.41 | 26-NOV-06:30 |
December | 1295.83 | 01-DEC-10:09 | 697.66 | 18-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 | 24-DEC-14:54 | 30.68 | 21-DEC-04:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 477.69 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 | 12.29 | |||||
Maximum of Months | 1295.83 | 697.66 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 82.13 | 75.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1082.30 | 02-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.37 | 15-JAN-13:00 | 245.70 | 07-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 840.63 | 07-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 169.38 | 19-FEB-15:00 | 29.42 | 19-FEB-06:57 |
March | 2010.79 | 01-MAR-10:09 | 912.85 | 01-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.00 | 19-MAR-16:00 | 47.31 | 14-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 706.10 | 21-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.00 | 30-APR-16:00 | 21.88 | 22-APR-03:00 |
May | 2010.79 | 01-MAY-09:09 | 715.70 | 17-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.23 | 07-MAY-14:56 | 92.92 | 08-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 698.03 | 20-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.92 | 18-JUN-14:15 | 110.25 | 20-JUN-22:53 |
July | 2010.79 | 03-JUL-09:09 | 704.04 | 11-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.60 | 04-JUL-14:18 | 37.48 | 02-JUL-13:30 |
August | 2010.79 | 01-AUG-09:09 | 710.24 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.40 | 06-AUG-13:00 | 96.13 | 20-AUG-10:53 |
September | 2010.79 | 01-SEP-09:09 | 710.41 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.73 | 10-SEP-15:00 | 56.03 | 15-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 821.79 | 30-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.75 | 29-OCT-13:00 | 41.97 | 22-OCT-17:53 |
November | 2010.79 | 01-NOV-09:09 | 1136.54 | 27-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.53 | 11-NOV-15:50 | 45.65 | 26-NOV-10:00 |
December | 2010.79 | 01-DEC-10:09 | 1154.63 | 18-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.58 | 24-DEC-15:00 | 90.78 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 698.03 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 74.58 | 21.88 | |||||
Maximum of Months | 2010.79 | 1154.63 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 293.00 | 245.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 718.34 | 02-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.88 | 15-JAN-13:00 | 171.76 | 07-JAN-05:00 |
February | 1239.33 | 01-FEB-08:09 | 628.28 | 07-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 112.10 | 19-FEB-15:00 | 27.83 | 19-FEB-06:57 |
March | 1239.33 | 01-MAR-08:09 | 626.95 | 01-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 190.35 | 19-MAR-15:34 | 34.60 | 14-MAR-22:00 |
April | 1239.33 | 03-APR-07:10 | 451.68 | 13-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.26 | 30-APR-16:00 | 17.79 | 23-APR-07:00 |
May | 1239.33 | 01-MAY-07:10 | 460.85 | 22-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.12 | 07-MAY-14:56 | 62.44 | 08-MAY-22:00 |
June | 1239.33 | 01-JUN-07:10 | 447.92 | 01-JUN-15:00 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.42 | 18-JUN-14:15 | 71.45 | 20-JUN-22:53 |
July | 1239.33 | 03-JUL-07:10 | 457.40 | 17-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.35 | 04-JUL-14:20 | 23.74 | 02-JUL-13:30 |
August | 1239.33 | 01-AUG-07:10 | 451.14 | 24-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.26 | 06-AUG-13:00 | 68.60 | 20-AUG-10:53 |
September | 1239.33 | 01-SEP-07:10 | 461.03 | 22-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.91 | 10-SEP-14:52 | 38.23 | 15-SEP-22:00 |
October | 1239.33 | 02-OCT-07:10 | 569.08 | 30-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.20 | 29-OCT-13:00 | 28.28 | 22-OCT-17:53 |
November | 1239.33 | 01-NOV-07:10 | 749.42 | 27-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.41 | 19-NOV-13:52 | 34.41 | 26-NOV-10:00 |
December | 1239.33 | 01-DEC-08:09 | 751.75 | 18-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.56 | 31-DEC-12:38 | 61.74 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 447.92 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 47.56 | 17.79 | |||||
Maximum of Months | 1239.33 | 751.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 190.35 | 171.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 948.64 | 02-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.32 | 15-JAN-13:00 | 279.81 | 07-JAN-05:00 |
February | 2010.83 | 01-FEB-10:09 | 741.60 | 01-FEB-17:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 162.71 | 19-FEB-14:55 | 35.42 | 19-FEB-06:57 |
March | 2010.83 | 01-MAR-10:09 | 741.96 | 01-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 285.01 | 19-MAR-16:00 | 50.56 | 14-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 714.62 | 21-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.43 | 30-APR-16:00 | 21.25 | 22-APR-02:55 |
May | 2010.83 | 01-MAY-09:09 | 733.02 | 17-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.99 | 07-MAY-14:58 | 89.24 | 08-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 726.06 | 20-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.00 | 18-JUN-14:20 | 101.08 | 20-JUN-22:53 |
July | 2010.83 | 03-JUL-09:09 | 728.83 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.76 | 04-JUL-14:00 | 27.52 | 19-JUL-21:20 |
August | 2010.83 | 01-AUG-09:09 | 725.16 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.20 | 06-AUG-13:00 | 94.91 | 20-AUG-10:53 |
September | 2010.83 | 01-SEP-09:09 | 711.01 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.35 | 10-SEP-15:00 | 57.15 | 15-SEP-22:00 |
October | 2010.83 | 02-OCT-09:09 | 723.20 | 23-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.07 | 29-OCT-13:00 | 44.05 | 22-OCT-17:53 |
November | 2010.83 | 01-NOV-09:09 | 1081.41 | 09-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.64 | 19-NOV-14:00 | 53.45 | 26-NOV-10:00 |
December | 2010.83 | 01-DEC-10:09 | 1115.19 | 18-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.44 | 31-DEC-13:00 | 97.64 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 711.01 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 63.44 | 21.25 | |||||
Maximum of Months | 2010.83 | 1115.19 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 285.01 | 279.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 575.94 | 02-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 57.65 | 15-JAN-13:00 | 183.59 | 07-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 477.90 | 01-FEB-17:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 108.86 | 19-FEB-14:55 | 25.52 | 19-FEB-06:57 |
March | 1295.83 | 01-MAR-10:09 | 537.29 | 15-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 190.00 | 19-MAR-16:00 | 36.96 | 14-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 476.09 | 21-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.48 | 30-APR-15:55 | 19.84 | 22-APR-02:55 |
May | 1295.83 | 01-MAY-09:09 | 554.48 | 17-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.74 | 07-MAY-14:54 | 67.43 | 08-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 527.04 | 20-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.66 | 18-JUN-14:13 | 79.35 | 20-JUN-22:53 |
July | 1295.83 | 03-JUL-09:09 | 540.23 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.68 | 04-JUL-14:15 | 26.81 | 02-JUL-14:10 |
August | 1295.83 | 01-AUG-09:09 | 543.97 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.91 | 06-AUG-12:23 | 68.31 | 20-AUG-10:53 |
September | 1295.83 | 01-SEP-09:09 | 476.69 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.47 | 10-SEP-15:00 | 42.25 | 15-SEP-22:00 |
October | 1295.83 | 02-OCT-09:09 | 573.21 | 23-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.21 | 29-OCT-13:00 | 31.99 | 01-OCT-22:53 |
November | 1295.83 | 01-NOV-09:09 | 654.43 | 09-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.55 | 11-NOV-15:26 | 35.24 | 26-NOV-10:00 |
December | 1295.83 | 01-DEC-10:09 | 698.54 | 18-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.09 | 31-DEC-12:40 | 65.54 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 476.09 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 48.09 | 19.84 | |||||
Maximum of Months | 1295.83 | 698.54 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 190.00 | 183.59 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1082.10 | 02-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.32 | 15-JAN-13:00 | 314.43 | 07-JAN-04:55 |
February | 2010.79 | 01-FEB-10:09 | 840.38 | 07-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 203.94 | 19-FEB-15:00 | 38.35 | 19-FEB-06:57 |
March | 2010.79 | 01-MAR-10:09 | 912.48 | 01-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 348.97 | 19-MAR-16:00 | 63.07 | 14-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 705.90 | 21-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.27 | 02-APR-15:55 | 29.40 | 22-APR-02:55 |
May | 2010.79 | 01-MAY-09:09 | 715.51 | 17-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.48 | 07-MAY-14:56 | 125.93 | 08-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 697.82 | 20-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.46 | 18-JUN-14:06 | 154.69 | 20-JUN-22:53 |
July | 2010.79 | 03-JUL-09:09 | 703.83 | 11-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.19 | 04-JUL-14:18 | 67.09 | 02-JUL-13:50 |
August | 2010.79 | 01-AUG-09:09 | 710.04 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.42 | 06-AUG-12:50 | 118.73 | 20-AUG-10:53 |
September | 2010.79 | 01-SEP-09:09 | 710.22 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.62 | 10-SEP-14:52 | 70.60 | 15-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 821.33 | 30-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.47 | 29-OCT-13:00 | 56.98 | 22-OCT-17:53 |
November | 2010.79 | 01-NOV-09:09 | 1136.39 | 27-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.58 | 11-NOV-16:00 | 59.65 | 26-NOV-10:00 |
December | 2010.79 | 01-DEC-10:09 | 1154.45 | 18-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 84.44 | 31-DEC-12:50 | 108.15 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 697.82 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 84.44 | 29.40 | |||||
Maximum of Months | 2010.79 | 1154.45 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 348.97 | 314.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 718.21 | 02-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.81 | 15-JAN-13:20 | 221.94 | 07-JAN-04:55 |
February | 1295.83 | 01-FEB-10:09 | 628.14 | 07-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 139.09 | 19-FEB-15:00 | 35.64 | 19-FEB-06:57 |
March | 1295.83 | 01-MAR-10:09 | 626.73 | 01-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 232.65 | 19-MAR-16:00 | 46.28 | 14-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 451.55 | 13-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.70 | 02-APR-15:55 | 23.30 | 23-APR-07:00 |
May | 1295.83 | 01-MAY-09:09 | 460.74 | 22-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.93 | 07-MAY-14:56 | 84.75 | 08-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 447.80 | 01-JUN-15:00 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.81 | 18-JUN-14:06 | 100.52 | 20-JUN-22:53 |
July | 1295.83 | 03-JUL-09:09 | 457.28 | 17-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.05 | 04-JUL-14:20 | 44.17 | 02-JUL-13:50 |
August | 1295.83 | 01-AUG-09:09 | 451.02 | 24-AUG-15:00 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.74 | 06-AUG-12:50 | 84.69 | 20-AUG-10:53 |
September | 1295.83 | 01-SEP-09:09 | 460.92 | 22-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.22 | 10-SEP-14:52 | 48.31 | 15-SEP-22:00 |
October | 1295.83 | 02-OCT-09:09 | 568.80 | 30-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.14 | 29-OCT-13:00 | 38.27 | 22-OCT-17:53 |
November | 1295.83 | 01-NOV-09:09 | 749.33 | 27-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.09 | 11-NOV-15:40 | 44.97 | 26-NOV-10:00 |
December | 1295.83 | 01-DEC-10:09 | 751.65 | 18-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 55.77 | 24-DEC-14:50 | 73.78 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 447.80 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 55.77 | 23.30 | |||||
Maximum of Months | 1295.83 | 751.65 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 232.65 | 221.94 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 948.44 | 02-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.79 | 15-JAN-13:00 | 360.31 | 07-JAN-04:55 |
February | 2010.83 | 01-FEB-10:09 | 741.60 | 01-FEB-17:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 198.91 | 19-FEB-14:55 | 45.92 | 19-FEB-06:57 |
March | 2010.83 | 01-MAR-10:09 | 741.82 | 01-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 348.97 | 19-MAR-16:00 | 67.39 | 14-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 714.43 | 21-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.80 | 02-APR-15:55 | 28.50 | 22-APR-02:55 |
May | 2010.83 | 01-MAY-09:09 | 732.87 | 17-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.74 | 07-MAY-14:56 | 121.18 | 08-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 725.90 | 20-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.64 | 18-JUN-14:06 | 142.08 | 20-JUN-22:53 |
July | 2010.83 | 03-JUL-09:09 | 728.67 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.15 | 04-JUL-14:20 | 53.91 | 02-JUL-13:50 |
August | 2010.83 | 01-AUG-09:09 | 725.00 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.93 | 06-AUG-12:50 | 117.16 | 20-AUG-10:53 |
September | 2010.83 | 01-SEP-09:09 | 710.82 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.49 | 10-SEP-14:52 | 72.07 | 15-SEP-22:00 |
October | 2010.83 | 02-OCT-09:09 | 723.03 | 23-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.88 | 29-OCT-12:45 | 60.73 | 29-OCT-17:20 |
November | 2010.83 | 01-NOV-09:09 | 1081.25 | 09-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.35 | 11-NOV-15:38 | 70.02 | 26-NOV-10:00 |
December | 2010.83 | 01-DEC-10:09 | 1115.02 | 18-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.10 | 31-DEC-13:00 | 117.02 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 710.82 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 77.10 | 28.50 | |||||
Maximum of Months | 2010.83 | 1115.02 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 348.97 | 360.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 575.87 | 02-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.85 | 15-JAN-13:20 | 237.57 | 07-JAN-04:55 |
February | 1295.83 | 01-FEB-10:09 | 477.90 | 01-FEB-17:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 134.79 | 19-FEB-14:58 | 32.78 | 19-FEB-06:57 |
March | 1295.83 | 01-MAR-10:09 | 537.17 | 15-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 232.64 | 19-MAR-16:00 | 48.55 | 14-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 476.00 | 21-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.45 | 30-APR-15:34 | 33.93 | 09-APR-16:00 |
May | 1295.83 | 01-MAY-09:09 | 554.19 | 17-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.15 | 07-MAY-14:54 | 89.97 | 08-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 526.73 | 20-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.74 | 18-JUN-14:06 | 109.33 | 20-JUN-22:53 |
July | 1295.83 | 03-JUL-09:09 | 539.94 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.29 | 04-JUL-14:18 | 46.69 | 02-JUL-13:50 |
August | 1295.83 | 01-AUG-09:09 | 543.68 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.69 | 06-AUG-12:50 | 84.25 | 20-AUG-10:53 |
September | 1295.83 | 01-SEP-09:09 | 476.60 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.41 | 10-SEP-14:50 | 52.58 | 15-SEP-22:00 |
October | 1295.83 | 02-OCT-09:09 | 572.94 | 23-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.37 | 29-OCT-12:50 | 43.24 | 29-OCT-17:20 |
November | 1295.83 | 01-NOV-09:09 | 654.37 | 09-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.54 | 11-NOV-15:38 | 45.73 | 26-NOV-10:00 |
December | 1295.83 | 01-DEC-10:09 | 698.45 | 18-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.23 | 31-DEC-12:50 | 78.46 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 476.00 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 56.23 | 32.78 | |||||
Maximum of Months | 1295.83 | 698.45 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 232.64 | 237.57 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 3337.76 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 3337.76 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 3337.76 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 3337.76 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 3337.76 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 3337.76 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 3337.76 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 3337.76 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 3337.76 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 3337.76 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 3337.76 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 3337.76 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 3337.76 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.22 | 15-JAN-13:00 | 229.11 | 07-JAN-04:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.01 | 19-FEB-15:00 | 23.22 | 20-FEB-07:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.65 | 19-MAR-16:00 | 36.79 | 03-MAR-05:30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.19 | 30-APR-15:31 | 13.41 | 22-APR-02:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.68 | 07-MAY-14:52 | 70.25 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.26 | 18-JUN-14:12 | 66.70 | 20-JUN-22:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.73 | 04-JUL-14:00 | 24.15 | 19-JUL-21:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.18 | 06-AUG-12:52 | 61.15 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.75 | 10-SEP-15:00 | 45.55 | 15-SEP-22:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.04 | 29-OCT-13:00 | 30.21 | 23-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.91 | 11-NOV-16:00 | 39.97 | 25-NOV-04:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.03 | 31-DEC-13:00 | 80.07 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.03 | 13.41 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.65 | 229.11 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.87 | 15-JAN-13:00 | 409.75 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.93 | 19-FEB-15:00 | 40.52 | 20-FEB-06:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.79 | 19-MAR-16:00 | 68.77 | 03-MAR-05:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.20 | 30-APR-15:40 | 27.73 | 22-APR-03:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.51 | 07-MAY-15:00 | 116.12 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.20 | 18-JUN-14:40 | 117.11 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.25 | 04-JUL-14:00 | 41.05 | 19-JUL-21:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.80 | 06-AUG-13:00 | 114.18 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.94 | 10-SEP-15:00 | 79.98 | 15-SEP-22:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.29 | 29-OCT-13:10 | 57.58 | 23-OCT-04:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.06 | 11-NOV-15:53 | 72.52 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.82 | 24-DEC-15:00 | 148.34 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.82 | 27.73 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.79 | 409.75 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.37 | 15-JAN-13:00 | 420.35 | 07-JAN-04:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.26 | 19-FEB-15:00 | 46.10 | 20-FEB-06:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.57 | 19-MAR-16:00 | 76.68 | 03-MAR-05:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.09 | 09-APR-15:00 | 32.48 | 22-APR-03:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.18 | 21-MAY-12:00 | 153.20 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.37 | 18-JUN-13:52 | 186.96 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.25 | 04-JUL-14:00 | 103.66 | 02-JUL-13:50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.06 | 06-AUG-12:33 | 151.26 | 20-AUG-10:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.36 | 10-SEP-14:50 | 89.40 | 03-SEP-16:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.57 | 29-OCT-13:00 | 75.84 | 23-OCT-03:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.79 | 11-NOV-16:00 | 87.02 | 26-NOV-10:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.46 | 31-DEC-09:53 | 153.19 | 21-DEC-04:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.46 | 32.48 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.57 | 420.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 76497.44 | 16-JAN-14:38 | 5385.68 | 3946.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 72860.18 | 20-FEB-21:53 | 0.00 | 1973.16 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 71411.76 | 14-MAR-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 68210.59 | 05-APR-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 68249.07 | 31-MAY-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 68418.43 | 27-JUN-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 70158.89 | 06-JUL-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 67549.31 | 24-AUG-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 68657.83 | 06-SEP-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 70749.96 | 10-OCT-05:03 | 7180.90 | 5261.11 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 73916.22 | 24-NOV-04:02 | 0.00 | 3946.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 72905.89 | 27-DEC-04:03 | 0.00 | 1973.16 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 67549.31 | 0.00 | 1973.16 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76497.44 | 7180.90 | 5261.11 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 80545.05 | 23-JAN-04:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 70657.33 | 21-FEB-05:33 | 0.00 | 4724.85 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 73454.38 | 06-MAR-06:04 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72096.76 | 10-APR-05:04 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76557.14 | 09-MAY-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73670.64 | 12-JUN-05:04 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 72293.00 | 03-JUL-05:04 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 72790.61 | 21-AUG-05:04 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76447.53 | 22-SEP-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 79127.90 | 31-OCT-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 71222.95 | 24-NOV-05:03 | 0.00 | 4724.85 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 73460.08 | 26-DEC-04:12 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 70657.33 | 0.00 | 2953.40 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80545.05 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 80171.42 | 02-JAN-04:04 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 69720.52 | 07-FEB-04:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 68706.34 | 01-MAR-04:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 64726.30 | 15-APR-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 70764.52 | 26-MAY-04:03 | 0.00 | 3543.64 | 17812.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 66728.38 | 01-JUN-03:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 69027.35 | 01-JUL-04:03 | 0.00 | 2362.72 | 17812.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 74538.37 | 21-AUG-03:02 | 0.00 | 2362.72 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 70142.72 | 15-SEP-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 74288.31 | 23-OCT-03:02 | 0.00 | 2362.72 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 74839.55 | 27-NOV-04:03 | 0.00 | 2362.72 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 72850.21 | 18-DEC-04:03 | 0.00 | 2362.72 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 64726.30 | 0.00 | 2362.72 | 17812.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80171.42 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 76928.50 | 02-JAN-04:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 73408.33 | 06-FEB-04:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 71193.79 | 10-MAR-04:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70845.47 | 14-APR-03:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75111.65 | 09-MAY-03:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73404.54 | 01-JUN-03:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 72509.98 | 17-JUL-03:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 77883.40 | 21-AUG-03:02 | 0.00 | 2362.72 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 73152.36 | 18-SEP-03:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 78724.19 | 23-OCT-03:02 | 0.00 | 2362.72 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 77861.28 | 27-NOV-04:03 | 0.00 | 2362.72 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 76497.79 | 18-DEC-04:03 | 0.00 | 2362.72 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 70845.47 | 0.00 | 2362.72 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 78724.19 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13036.22 | 02-JAN-04:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.48 |
February | 11914.31 | 21-FEB-05:33 | 0.00 | 593.25 | 2982.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15331.63 | 26-MAR-15:01 | 708.51 | 247.02 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 70.35 | 0.00 |
April | 15527.81 | 02-APR-15:41 | 809.73 | 282.30 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 53.89 | 0.00 |
May | 15208.72 | 14-MAY-13:02 | 404.87 | 141.15 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 41.38 | 0.00 |
June | 15615.54 | 18-JUN-13:02 | 404.87 | 141.15 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 63.25 | 0.00 |
July | 15268.64 | 04-JUL-13:13 | 404.87 | 141.15 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 57.97 | 0.00 |
August | 15520.74 | 27-AUG-15:41 | 708.51 | 247.02 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 48.14 | 0.00 |
September | 13646.02 | 05-SEP-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 2.62 | 0.00 |
October | 12039.62 | 16-OCT-04:53 | 0.00 | 593.25 | 2982.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 | 0.00 |
November | 12004.04 | 24-NOV-05:03 | 0.00 | 593.25 | 2982.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 |
December | 11896.29 | 26-DEC-04:12 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11896.29 | 0.00 | 141.15 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15615.54 | 809.73 | 593.25 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 70.35 | 6.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11062.85 | 16-JAN-09:23 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 |
February | 10743.58 | 20-FEB-12:53 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 0.00 |
March | 14982.96 | 26-MAR-09:42 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 24.68 | 0.00 |
April | 14747.75 | 09-APR-09:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 | 0.00 |
May | 14345.69 | 14-MAY-08:23 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 5.13 | 0.00 |
June | 11643.04 | 18-JUN-13:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 45.15 | 0.00 |
July | 11494.25 | 30-JUL-09:43 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 0.00 |
August | 14518.81 | 27-AUG-09:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 10.56 | 0.00 |
September | 14694.34 | 04-SEP-09:32 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 | 0.00 |
October | 11632.24 | 08-OCT-14:02 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 16.13 | 0.00 |
November | 10123.89 | 13-NOV-06:02 | 652.28 | 227.38 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 0.00 |
December | 9897.57 | 03-DEC-10:13 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 4.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9897.57 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14982.96 | 652.28 | 227.38 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.15 | 0.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15803.51 | 22-JAN-15:22 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 5.98 | 0.00 |
February | 15845.80 | 20-FEB-12:53 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 16.82 | 0.00 |
March | 15453.06 | 26-MAR-15:01 | 708.53 | 247.02 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 65.95 | 0.00 |
April | 15229.81 | 02-APR-15:41 | 809.75 | 282.31 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 53.56 | 0.00 |
May | 13296.30 | 01-MAY-03:42 | 0.00 | 296.67 | 2982.29 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 0.00 |
June | 14657.09 | 04-JUN-13:52 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 21.65 | 0.00 |
July | 12743.13 | 09-JUL-15:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 40.89 | 0.00 |
August | 14969.15 | 27-AUG-15:41 | 708.53 | 247.02 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 49.84 | 0.00 |
September | 13386.25 | 05-SEP-03:02 | 0.00 | 370.84 | 3727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 0.00 |
October | 15460.25 | 29-OCT-11:53 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 50.51 | 0.00 |
November | 15652.83 | 23-NOV-13:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 13.09 | 0.00 |
December | 16289.70 | 03-DEC-14:12 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 11.52 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12743.13 | 0.00 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 0.00 | |
Maximum of Months | 16289.70 | 809.75 | 370.84 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 65.95 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19903.29 | 22-JAN-15:22 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 | 0.00 |
February | 19532.82 | 26-FEB-15:42 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 40.70 | 0.00 |
March | 21875.83 | 26-MAR-15:41 | 456.59 | 159.19 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 32.15 | 0.00 |
April | 22521.25 | 02-APR-15:41 | 521.82 | 181.93 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 24.70 | 0.00 |
May | 17961.99 | 01-MAY-03:02 | 0.00 | 238.98 | 2402.32 | 0.00 | 0.00 | 0.00 | 0.00 | 9.47 | 0.00 |
June | 20071.42 | 25-JUN-15:42 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 11.16 | 0.00 |
July | 19824.76 | 04-JUL-15:52 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 31.20 | 0.00 |
August | 21931.52 | 27-AUG-15:41 | 456.59 | 159.19 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 22.79 | 0.00 |
September | 18604.87 | 24-SEP-15:23 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 24.64 | 0.00 |
October | 20076.44 | 08-OCT-14:02 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 14.01 | 0.00 |
November | 18939.64 | 19-NOV-14:52 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 13.30 | 0.00 |
December | 20870.01 | 03-DEC-14:12 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17961.99 | 0.00 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 | 0.00 | |
Maximum of Months | 22521.25 | 521.82 | 238.98 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 40.70 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12075.15 | 02-JAN-04:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.73 |
February | 11926.38 | 27-FEB-04:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.45 |
March | 13902.23 | 19-MAR-14:51 | 708.51 | 247.02 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 224.93 | 0.00 |
April | 12634.31 | 19-APR-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 | 0.00 |
May | 14278.77 | 07-MAY-13:32 | 506.08 | 176.44 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 142.90 | 0.00 |
June | 14796.23 | 11-JUN-15:32 | 607.30 | 211.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.34 | 0.00 |
July | 13760.89 | 04-JUL-15:32 | 506.08 | 176.44 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 124.57 | 0.00 |
August | 13941.14 | 13-AUG-16:52 | 607.30 | 211.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 | 0.00 |
September | 12643.73 | 25-SEP-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 |
October | 12468.09 | 30-OCT-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 |
November | 11551.91 | 13-NOV-04:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 |
December | 10550.56 | 15-DEC-06:03 | 809.73 | 583.77 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10550.56 | 0.00 | 176.44 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14796.23 | 809.73 | 583.77 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 224.93 | 18.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12292.55 | 02-JAN-04:02 | 0.00 | 238.98 | 2402.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.52 |
February | 15040.78 | 20-FEB-09:53 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 18.21 | 0.00 |
March | 15610.65 | 26-MAR-09:42 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 54.05 | 0.00 |
April | 15223.38 | 30-APR-09:13 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 26.44 | 0.00 |
May | 15194.60 | 14-MAY-09:53 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 41.21 | 0.00 |
June | 15095.31 | 18-JUN-09:32 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 64.22 | 0.00 |
July | 11061.50 | 03-JUL-03:02 | 0.00 | 238.98 | 2402.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
August | 14924.31 | 13-AUG-09:32 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 43.14 | 0.00 |
September | 15038.65 | 04-SEP-09:23 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 20.28 | 0.00 |
October | 14962.53 | 08-OCT-09:32 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 15.38 | 0.00 |
November | 13712.76 | 05-NOV-09:32 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 | 0.00 |
December | 12787.42 | 31-DEC-10:32 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11061.50 | 0.00 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15610.65 | 326.14 | 238.98 | 2402.34 | 0.00 | 0.00 | 0.00 | 0.00 | 64.22 | 10.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14800.18 | 29-JAN-14:12 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 20.76 | 0.00 |
February | 14114.96 | 19-FEB-14:13 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 80.95 | 0.00 |
March | 14168.50 | 19-MAR-14:51 | 708.53 | 247.02 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 205.47 | 0.00 |
April | 12137.40 | 01-APR-03:02 | 0.00 | 370.84 | 2795.90 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 | 0.00 |
May | 13384.40 | 07-MAY-13:32 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 152.70 | 0.00 |
June | 13518.62 | 11-JUN-15:32 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 133.48 | 0.00 |
July | 12349.32 | 10-JUL-03:02 | 0.00 | 370.84 | 3727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 |
August | 12043.52 | 15-AUG-03:02 | 0.00 | 370.84 | 3727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 9.22 | 0.00 |
September | 13349.01 | 04-SEP-16:42 | 607.31 | 222.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 86.00 | 0.00 |
October | 14275.18 | 29-OCT-12:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 116.32 | 0.00 |
November | 14287.37 | 05-NOV-11:32 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 48.66 | 0.00 |
December | 14897.42 | 31-DEC-12:32 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 42.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12043.52 | 0.00 | 141.16 | 2795.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14897.42 | 708.53 | 370.84 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 205.47 | 1.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16790.43 | 29-JAN-15:32 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 24.81 | 0.00 |
February | 16211.75 | 26-FEB-15:42 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 93.65 | 0.00 |
March | 17753.64 | 19-MAR-14:51 | 456.59 | 159.19 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 119.40 | 0.00 |
April | 16535.92 | 02-APR-16:02 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 80.92 | 0.00 |
May | 16257.75 | 07-MAY-13:32 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 95.83 | 0.00 |
June | 17384.29 | 11-JUN-16:12 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 61.15 | 0.00 |
July | 16289.20 | 04-JUL-16:12 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 62.34 | 0.00 |
August | 16804.62 | 13-AUG-16:52 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 0.00 |
September | 17246.71 | 04-SEP-16:42 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 42.79 | 0.00 |
October | 14448.97 | 30-OCT-03:02 | 0.00 | 238.98 | 2402.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.28 |
November | 14655.30 | 20-NOV-04:02 | 0.00 | 238.98 | 2402.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.71 |
December | 16090.30 | 31-DEC-15:52 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 36.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14448.97 | 0.00 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17753.64 | 456.59 | 238.98 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 119.40 | 12.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14362.82 | 02-JAN-04:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.69 |
February | 16142.94 | 19-FEB-14:13 | 404.87 | 141.15 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 111.73 | 0.00 |
March | 17347.17 | 19-MAR-14:51 | 708.51 | 247.02 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 253.35 | 0.00 |
April | 17370.13 | 30-APR-15:31 | 708.51 | 247.02 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 139.85 | 0.00 |
May | 17564.17 | 07-MAY-13:32 | 506.08 | 176.44 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 163.64 | 0.00 |
June | 17905.36 | 11-JUN-14:02 | 506.08 | 176.44 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 169.17 | 0.00 |
July | 16661.88 | 04-JUL-15:32 | 506.08 | 176.44 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 147.13 | 0.00 |
August | 17026.71 | 13-AUG-16:52 | 607.30 | 211.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 | 0.00 |
September | 16433.73 | 24-SEP-15:52 | 506.08 | 176.44 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 107.34 | 0.00 |
October | 15221.60 | 09-OCT-15:23 | 404.87 | 141.15 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 44.22 | 0.00 |
November | 16543.51 | 19-NOV-15:22 | 607.30 | 211.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.32 | 0.00 |
December | 13413.92 | 11-DEC-04:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13413.92 | 0.00 | 141.15 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17905.36 | 708.51 | 370.83 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 253.35 | 21.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12492.77 | 02-JAN-04:02 | 0.00 | 238.98 | 2402.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.72 |
February | 15578.53 | 20-FEB-09:53 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 20.48 | 0.00 |
March | 16043.15 | 19-MAR-14:51 | 456.59 | 159.19 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 162.74 | 0.00 |
April | 15830.74 | 30-APR-15:31 | 456.59 | 159.19 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 92.29 | 0.00 |
May | 15660.56 | 07-MAY-13:32 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 113.55 | 0.00 |
June | 15633.63 | 18-JUN-08:43 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 55.29 | 0.00 |
July | 15233.64 | 30-JUL-09:43 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 37.46 | 0.00 |
August | 15647.23 | 27-AUG-09:13 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 29.07 | 0.00 |
September | 15673.07 | 03-SEP-09:32 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 20.58 | 0.00 |
October | 15509.17 | 08-OCT-09:32 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 17.72 | 0.00 |
November | 14974.05 | 23-NOV-13:32 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 33.32 | 0.00 |
December | 12431.89 | 03-DEC-11:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 27.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12431.89 | 0.00 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16043.15 | 456.59 | 238.98 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 162.74 | 12.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17361.77 | 15-JAN-14:32 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 29.38 | 0.00 |
February | 16932.54 | 19-FEB-14:13 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 93.20 | 0.00 |
March | 17489.58 | 19-MAR-14:51 | 708.53 | 247.02 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 233.97 | 0.00 |
April | 16730.20 | 30-APR-15:31 | 708.53 | 247.02 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 143.07 | 0.00 |
May | 16607.13 | 07-MAY-13:32 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 173.25 | 0.00 |
June | 16563.82 | 11-JUN-14:02 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 186.90 | 0.00 |
July | 15842.52 | 30-JUL-13:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 130.85 | 0.00 |
August | 16207.55 | 13-AUG-16:52 | 607.31 | 228.04 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 0.00 |
September | 16194.35 | 24-SEP-15:52 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 102.13 | 0.00 |
October | 17074.64 | 29-OCT-12:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 133.79 | 0.00 |
November | 17630.03 | 19-NOV-13:22 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 51.80 | 0.00 |
December | 17613.79 | 24-DEC-13:22 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 32.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15842.52 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 0.00 | |
Maximum of Months | 17630.03 | 708.53 | 247.02 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 233.97 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18296.77 | 15-JAN-15:52 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 12.31 | 0.00 |
February | 18025.62 | 26-FEB-15:42 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 112.83 | 0.00 |
March | 20278.62 | 19-MAR-14:51 | 456.59 | 159.19 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 136.74 | 0.00 |
April | 19951.62 | 30-APR-15:31 | 456.59 | 159.19 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 72.84 | 0.00 |
May | 18566.98 | 07-MAY-13:32 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 111.33 | 0.00 |
June | 18724.91 | 11-JUN-14:02 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 117.69 | 0.00 |
July | 18108.69 | 04-JUL-16:12 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 72.95 | 0.00 |
August | 18960.27 | 13-AUG-16:52 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
September | 18357.21 | 24-SEP-15:52 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 60.59 | 0.00 |
October | 17413.38 | 08-OCT-16:53 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 26.47 | 0.00 |
November | 18990.47 | 19-NOV-15:22 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 28.73 | 0.00 |
December | 17834.52 | 24-DEC-16:42 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17413.38 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20278.62 | 456.59 | 159.19 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 136.74 | 0.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13732.37 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13236.67 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13186.63 | 27-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.73 | 0.00 |
April | 13419.70 | 03-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.84 | 0.00 |
May | 13605.30 | 01-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 | 0.00 |
June | 13177.23 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 | 0.00 |
July | 12769.54 | 31-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 |
August | 13235.92 | 28-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 13617.24 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 | 0.00 |
October | 13741.11 | 10-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.27 |
November | 12007.27 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
December | 13877.65 | 26-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 12007.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13877.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 | 5.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12927.38 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8849.44 | 06-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7114.08 | 03-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 |
April | 7245.52 | 29-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 | 0.00 |
May | 9267.83 | 15-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 0.00 |
June | 8315.01 | 03-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 | 0.00 |
July | 7848.83 | 18-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7050.82 | 22-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 |
September | 7361.28 | 06-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 9968.46 | 10-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 |
November | 9636.01 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
December | 9040.88 | 18-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7050.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12927.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 | 13.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17255.39 | 04-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.52 | 0.00 |
February | 19035.75 | 21-FEB-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.68 | 0.00 |
March | 20867.41 | 29-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.97 | 0.00 |
April | 21671.90 | 11-APR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 | 0.00 |
May | 21398.06 | 05-MAY-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.37 | 0.00 |
June | 19890.79 | 16-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.12 | 0.00 |
July | 18996.58 | 14-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.02 | 0.00 |
August | 20065.38 | 14-AUG-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.27 | 0.00 |
September | 20365.95 | 06-SEP-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.85 | 0.00 |
October | 17831.53 | 04-OCT-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.27 | 0.00 |
November | 16510.54 | 22-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.29 | 0.00 |
December | 16752.79 | 08-DEC-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 16510.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.29 | 0.00 | |
Maximum of Months | 21671.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.12 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2166.41 | 16-JAN-17:40 | 23.38 | 31.66 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3971.14 | 20-FEB-17:15 | 46.77 | 63.33 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7234.29 | 31-MAR-23:35 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7709.11 | 23-APR-17:55 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3504.47 | 31-MAY-23:50 | 0.00 | 31.66 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5332.36 | 30-JUN-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7245.23 | 31-JUL-23:53 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7752.73 | 13-AUG-17:30 | 0.00 | 79.16 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3479.99 | 30-SEP-23:57 | 0.00 | 47.50 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5357.62 | 31-OCT-23:57 | 0.00 | 47.50 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5796.25 | 19-NOV-17:10 | 23.38 | 31.66 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7857.16 | 25-DEC-17:20 | 46.77 | 63.33 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2166.41 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7857.16 | 46.77 | 79.16 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1981.20 | 16-JAN-17:40 | 23.38 | 31.66 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3692.60 | 20-FEB-17:22 | 58.46 | 79.16 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7010.24 | 31-MAR-24:00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7305.39 | 23-APR-17:55 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3383.72 | 31-MAY-23:57 | 0.00 | 47.50 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5085.56 | 30-JUN-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6968.67 | 31-JUL-23:53 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7297.42 | 13-AUG-17:15 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3404.06 | 30-SEP-23:57 | 0.00 | 47.50 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5096.05 | 31-OCT-23:57 | 0.00 | 47.50 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5488.79 | 20-NOV-17:00 | 222.14 | 284.97 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7366.12 | 25-DEC-16:52 | 58.46 | 79.16 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1981.20 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7366.12 | 222.14 | 284.97 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2221.89 | 16-JAN-17:40 | 23.38 | 31.66 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3986.70 | 20-FEB-16:55 | 46.77 | 63.33 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6991.86 | 31-MAR-24:00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7509.95 | 23-APR-17:55 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3408.86 | 31-MAY-23:57 | 0.00 | 47.50 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5033.80 | 30-JUN-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6974.37 | 31-JUL-23:53 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7542.31 | 13-AUG-17:10 | 0.00 | 79.16 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3400.37 | 30-SEP-23:57 | 0.00 | 47.50 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5078.78 | 31-OCT-23:57 | 0.00 | 47.50 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5758.75 | 19-NOV-16:55 | 46.77 | 63.33 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7616.52 | 24-DEC-17:12 | 46.77 | 63.33 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2221.89 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7616.52 | 46.77 | 79.16 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92975.48 | 17-JAN-17:00 | 4808.68 | 3337.76 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 184430.69 | 21-FEB-17:00 | 4808.68 | 3337.76 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 360014.20 | 31-MAR-24:00 | 0.00 | 185.45 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367806.93 | 03-APR-16:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 177076.70 | 31-MAY-23:53 | 0.00 | 556.35 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268456.53 | 30-JUN-24:00 | 0.00 | 185.45 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360582.58 | 31-JUL-23:57 | 0.00 | 556.35 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 368142.12 | 28-AUG-16:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176651.44 | 30-SEP-23:53 | 0.00 | 556.35 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268348.59 | 31-OCT-23:53 | 0.00 | 556.35 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276043.41 | 20-NOV-17:00 | 4808.68 | 3337.76 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 368112.28 | 26-DEC-17:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92975.48 | 0.00 | 185.45 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 368142.12 | 4808.68 | 3337.76 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.176921E+13 | 1262493.46 | 02-JAN-08:09 | 0.454944E+11 | 60188.04 | 31-JAN-12:50 |
February | 0.198433E+13 | 1369693.82 | 06-FEB-08:50 | 0.410968E+11 | 60169.01 | 01-FEB-12:50 |
March | 0.265791E+13 | 1515517.73 | 29-MAR-15:00 | 0.468279E+11 | 59586.49 | 01-MAR-12:30 |
April | 0.295034E+13 | 1677840.46 | 24-APR-15:20 | 0.428597E+11 | 58325.61 | 04-APR-11:00 |
May | 0.191690E+13 | 1255843.81 | 05-MAY-07:49 | 0.446000E+11 | 57153.87 | 02-MAY-11:39 |
June | 0.226243E+13 | 1399550.70 | 06-JUN-07:49 | 0.434019E+11 | 55954.72 | 02-JUN-11:39 |
July | 0.258829E+13 | 1517551.23 | 28-JUL-15:30 | 0.424496E+11 | 55369.80 | 20-JUL-11:50 |
August | 0.308422E+13 | 1679076.92 | 09-AUG-07:49 | 0.451092E+11 | 56125.37 | 30-AUG-11:39 |
September | 0.179020E+13 | 1247045.06 | 06-SEP-07:00 | 0.423722E+11 | 57261.69 | 28-SEP-11:30 |
October | 0.221593E+13 | 1379841.84 | 16-OCT-07:00 | 0.443511E+11 | 58600.24 | 30-OCT-11:30 |
November | 0.252472E+13 | 1526327.33 | 14-NOV-08:00 | 0.438862E+11 | 59667.29 | 28-NOV-12:30 |
December | 0.291956E+13 | 1647518.76 | 18-DEC-08:00 | 0.447032E+11 | 60220.58 | 29-DEC-12:00 |
Annual Sum or Average | 0.286640E+14 | 0.527152E+12 | ||||
Minimum of Months | 0.176921E+13 | 1247045.06 | 0.410968E+11 | 55369.80 | ||
Maximum of Months | 0.308422E+13 | 1679076.92 | 0.468279E+11 | 60220.58 |
Report: EnergyConsumptionDistrictHeatingCoolingMonthly
For: Meter
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportDISTRICTCOOLING:FACILITY [J] | DISTRICTCOOLING:FACILITY {Maximum} [W] | DISTRICTCOOLING:FACILITY {TIMESTAMP} | DISTRICTHEATING:FACILITY [J] | DISTRICTHEATING:FACILITY {Maximum} [W] | DISTRICTHEATING:FACILITY {TIMESTAMP} | |
January | 0.245133E+12 | 95684.41 | 02-JAN-14:00 | 59449.28 | 5.01 | 18-JAN-00:40 |
February | 0.441844E+12 | 187064.10 | 21-FEB-14:00 | 22826.85 | 3.78 | 08-FEB-00:30 |
March | 0.734954E+12 | 360014.20 | 31-MAR-23:00 | 46035.30 | 5.65 | 23-MAR-23:30 |
April | 0.947798E+12 | 370440.56 | 03-APR-13:00 | 24788.00 | 7.07 | 10-APR-23:19 |
May | 0.246110E+12 | 177076.70 | 31-MAY-23:00 | 41521.17 | 5.00 | 24-MAY-23:40 |
June | 0.474596E+12 | 268457.25 | 30-JUN-23:00 | 15624.85 | 2.80 | 29-JUN-23:30 |
July | 0.735540E+12 | 360582.60 | 31-JUL-23:00 | 43812.24 | 5.65 | 13-JUL-23:30 |
August | 0.980602E+12 | 370785.23 | 14-AUG-13:00 | 80530.97 | 7.07 | 02-AUG-23:19 |
September | 0.238311E+12 | 176651.44 | 30-SEP-23:00 | 61341.20 | 4.52 | 20-SEP-23:40 |
October | 0.489521E+12 | 268348.68 | 31-OCT-23:00 | 62094.92 | 14.83 | 31-OCT-23:30 |
November | 0.711232E+12 | 278721.04 | 13-NOV-14:00 | 52165.66 | 5.65 | 03-NOV-23:30 |
December | 0.980540E+12 | 370776.59 | 26-DEC-14:00 | 92181.67 | 9.23 | 01-DEC-00:20 |
Annual Sum or Average | 0.722618E+13 | 602372.11 | ||||
Minimum of Months | 0.238311E+12 | 95684.41 | 15624.85 | 2.80 | ||
Maximum of Months | 0.980602E+12 | 370785.23 | 92181.67 | 14.83 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.169255E+12 | 0.293501E+11 | 0.766053E+12 | 0.210403E+12 | 0.110168E+12 | 0.103086E+12 | 0.00 | 0.279492E+12 | 0.914358E+11 | 0.00 | 0.996654E+10 | 0.00 | 0.00 |
February | 0.153273E+12 | 0.257665E+11 | 0.978954E+12 | 0.233672E+12 | 0.103887E+12 | 0.103756E+12 | 0.00 | 0.284295E+12 | 0.910434E+11 | 0.00 | 0.968652E+10 | 0.00 | 0.00 |
March | 0.181348E+12 | 0.269355E+11 | 0.141687E+13 | 0.307234E+12 | 0.136408E+12 | 0.122972E+12 | 0.00 | 0.345305E+12 | 0.109290E+12 | 0.00 | 0.115477E+11 | 0.00 | 0.00 |
April | 0.161638E+12 | 0.249135E+11 | 0.165903E+13 | 0.343627E+12 | 0.136425E+12 | 0.122221E+12 | 0.00 | 0.367564E+12 | 0.123548E+12 | 0.00 | 0.113760E+11 | 0.00 | 0.00 |
May | 0.174455E+12 | 0.249045E+11 | 0.774844E+12 | 0.210552E+12 | 0.135244E+12 | 0.116689E+12 | 0.00 | 0.341967E+12 | 0.127242E+12 | 0.00 | 0.110065E+11 | 0.00 | 0.00 |
June | 0.173338E+12 | 0.237514E+11 | 0.106252E+13 | 0.250564E+12 | 0.130992E+12 | 0.120124E+12 | 0.00 | 0.362982E+12 | 0.127032E+12 | 0.00 | 0.111265E+11 | 0.00 | 0.00 |
July | 0.162553E+12 | 0.249718E+11 | 0.139340E+13 | 0.306990E+12 | 0.126893E+12 | 0.120652E+12 | 0.00 | 0.329442E+12 | 0.112373E+12 | 0.00 | 0.110169E+11 | 0.00 | 0.00 |
August | 0.180917E+12 | 0.254292E+11 | 0.173200E+13 | 0.355272E+12 | 0.139465E+12 | 0.126432E+12 | 0.00 | 0.385561E+12 | 0.127907E+12 | 0.00 | 0.112386E+11 | 0.00 | 0.00 |
September | 0.162087E+12 | 0.257259E+11 | 0.740713E+12 | 0.203664E+12 | 0.123465E+12 | 0.106264E+12 | 0.00 | 0.302869E+12 | 0.115277E+12 | 0.00 | 0.101330E+11 | 0.00 | 0.00 |
October | 0.168550E+12 | 0.278833E+11 | 0.108340E+13 | 0.258766E+12 | 0.120181E+12 | 0.112596E+12 | 0.00 | 0.317644E+12 | 0.116470E+12 | 0.00 | 0.104424E+11 | 0.00 | 0.00 |
November | 0.167505E+12 | 0.283823E+11 | 0.135889E+13 | 0.297145E+12 | 0.111637E+12 | 0.115964E+12 | 0.00 | 0.325715E+12 | 0.109197E+12 | 0.00 | 0.102815E+11 | 0.00 | 0.00 |
December | 0.164196E+12 | 0.297029E+11 | 0.170972E+13 | 0.355224E+12 | 0.107705E+12 | 0.119166E+12 | 0.00 | 0.322121E+12 | 0.101090E+12 | 0.00 | 0.106314E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.201912E+13 | 0.317717E+12 | 0.146764E+14 | 0.333311E+13 | 0.148247E+13 | 0.138992E+13 | 0.00 | 0.396496E+13 | 0.135190E+13 | 0.00 | 0.128454E+12 | 0.00 | 0.00 |
Minimum of Months | 0.153273E+12 | 0.237514E+11 | 0.740713E+12 | 0.203664E+12 | 0.103887E+12 | 0.103086E+12 | 0.00 | 0.279492E+12 | 0.910434E+11 | 0.00 | 0.968652E+10 | 0.00 | 0.00 |
Maximum of Months | 0.181348E+12 | 0.297029E+11 | 0.173200E+13 | 0.355272E+12 | 0.139465E+12 | 0.126432E+12 | 0.00 | 0.385561E+12 | 0.127907E+12 | 0.00 | 0.115477E+11 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.454944E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.410968E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.468279E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.428597E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.446000E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.434019E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.424496E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.451092E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.423722E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.443511E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.438862E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.447032E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.527152E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.410968E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.468279E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 186069.76 | 02-JAN-16:00 | 37611.08 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 134884.04 | 02-JAN-08:20 | 144572.48 | 02-JAN-09:50 | 71632.20 | 30-JAN-15:50 | 0.00 | 01-JAN-00:10 |
February | 177229.19 | 07-FEB-16:00 | 37611.08 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 152916.38 | 08-FEB-08:20 | 119350.98 | 06-FEB-08:50 | 71801.86 | 21-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 178773.89 | 01-MAR-16:00 | 37611.08 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 170949.91 | 15-MAR-07:19 | 138618.64 | 10-MAR-16:49 | 70327.60 | 20-MAR-14:30 | 0.00 | 01-MAR-00:10 |
April | 173849.11 | 21-APR-07:10 | 37611.08 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 188982.38 | 21-APR-07:19 | 150562.08 | 27-APR-14:50 | 68864.75 | 12-APR-15:39 | 0.00 | 01-APR-00:10 |
May | 175122.97 | 17-MAY-07:10 | 37611.08 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 134885.40 | 17-MAY-07:19 | 135657.59 | 22-MAY-09:09 | 69811.21 | 31-MAY-15:39 | 0.00 | 01-MAY-00:10 |
June | 174450.62 | 20-JUN-07:10 | 37611.08 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 152917.60 | 20-JUN-07:19 | 127713.48 | 21-JUN-15:50 | 70628.57 | 13-JUN-15:30 | 0.00 | 01-JUN-00:10 |
July | 174762.01 | 11-JUL-07:10 | 37611.08 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 170950.31 | 11-JUL-07:19 | 134600.66 | 31-JUL-15:20 | 69375.31 | 14-JUL-14:30 | 0.00 | 01-JUL-00:10 |
August | 174837.36 | 21-AUG-07:10 | 37611.08 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 188982.90 | 21-AUG-07:19 | 146613.12 | 28-AUG-15:39 | 68571.05 | 25-AUG-10:00 | 0.00 | 01-AUG-00:10 |
September | 173864.70 | 21-SEP-07:10 | 37611.08 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 134884.74 | 21-SEP-07:19 | 145895.15 | 12-SEP-15:20 | 69340.13 | 29-SEP-12:50 | 0.00 | 01-SEP-00:10 |
October | 176555.57 | 30-OCT-15:00 | 37611.08 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 152918.14 | 23-OCT-07:19 | 129533.81 | 10-OCT-15:00 | 70080.13 | 04-OCT-13:50 | 0.00 | 01-OCT-00:10 |
November | 189528.10 | 09-NOV-16:00 | 37611.08 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 170949.53 | 03-NOV-07:19 | 127291.15 | 27-NOV-13:09 | 71530.21 | 20-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 190804.33 | 18-DEC-16:00 | 37611.08 | 01-DEC-17:30 | 778371.69 | 01-DEC-08:09 | 188981.63 | 18-DEC-08:20 | 126777.23 | 18-DEC-13:09 | 71359.66 | 12-DEC-14:09 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 173849.11 | 37611.08 | 423497.50 | 134884.04 | 119350.98 | 68571.05 | 0.00 | |||||||
Maximum of Months | 190804.33 | 37611.08 | 778371.69 | 188982.90 | 150562.08 | 71801.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 286331.87 | 30-JAN-15:50 | 58053.77 | 09-JAN-21:10 | 0.00 | 5613.48 | 01-JAN-07:40 | 0.00 | 0.00 |
February | 299603.58 | 15-FEB-13:09 | 58053.77 | 05-FEB-14:20 | 0.00 | 5613.48 | 01-FEB-04:19 | 0.00 | 0.00 |
March | 295947.73 | 27-MAR-14:09 | 58053.77 | 24-MAR-20:10 | 0.00 | 5613.48 | 01-MAR-04:30 | 0.00 | 0.00 |
April | 299360.43 | 17-APR-09:00 | 58053.77 | 01-APR-03:00 | 0.00 | 5613.48 | 01-APR-03:20 | 0.00 | 0.00 |
May | 294194.04 | 22-MAY-05:10 | 58053.77 | 01-MAY-00:10 | 0.00 | 5613.48 | 01-MAY-01:49 | 0.00 | 0.00 |
June | 297751.34 | 15-JUN-09:00 | 58053.77 | 01-JUN-20:10 | 0.00 | 5613.48 | 01-JUN-03:20 | 0.00 | 0.00 |
July | 293578.89 | 26-JUL-13:00 | 58053.77 | 01-JUL-16:10 | 0.00 | 5613.48 | 01-JUL-04:10 | 0.00 | 0.00 |
August | 299839.63 | 17-AUG-10:39 | 58053.77 | 01-AUG-03:20 | 0.00 | 5613.48 | 01-AUG-03:09 | 0.00 | 0.00 |
September | 284928.30 | 20-SEP-05:10 | 58053.77 | 01-SEP-04:40 | 0.00 | 5613.48 | 01-SEP-03:20 | 0.00 | 0.00 |
October | 292455.48 | 04-OCT-13:50 | 58053.77 | 01-OCT-00:30 | 0.00 | 5613.48 | 01-OCT-06:19 | 0.00 | 0.00 |
November | 302794.79 | 03-NOV-13:50 | 58053.77 | 02-NOV-20:10 | 0.00 | 5613.48 | 01-NOV-03:20 | 0.00 | 0.00 |
December | 307770.32 | 12-DEC-13:50 | 58053.77 | 09-DEC-17:19 | 0.00 | 5613.48 | 01-DEC-05:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 284928.30 | 58053.77 | 0.00 | 5613.48 | 0.00 | 0.00 | |||
Maximum of Months | 307770.32 | 58053.77 | 0.00 | 5613.48 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1262493.46 | 02-JAN-08:09 | 172544.75 | 423497.50 | 0.00 | 134824.06 | 142214.96 | 68065.96 | 0.00 | 257679.00 | 58053.77 |
February | 1369693.82 | 06-FEB-08:50 | 171235.93 | 541788.89 | 0.00 | 152915.91 | 119350.98 | 67784.05 | 0.00 | 252950.83 | 58053.77 |
March | 1515517.73 | 29-MAR-15:00 | 171235.93 | 660080.29 | 0.00 | 136905.07 | 123818.28 | 69050.03 | 0.00 | 290760.90 | 58053.77 |
April | 1677840.46 | 24-APR-15:20 | 171235.93 | 778371.69 | 0.00 | 154937.61 | 148210.70 | 68340.78 | 0.00 | 293076.51 | 58053.77 |
May | 1255843.81 | 05-MAY-07:49 | 171235.93 | 423497.50 | 0.00 | 134883.36 | 125149.22 | 67943.46 | 0.00 | 269467.10 | 58053.77 |
June | 1399550.70 | 06-JUN-07:49 | 171235.93 | 541788.89 | 0.00 | 152915.91 | 118991.90 | 68107.48 | 0.00 | 282843.36 | 58053.77 |
July | 1517551.23 | 28-JUL-15:30 | 171235.93 | 660080.29 | 0.00 | 136905.07 | 126331.93 | 68496.25 | 0.00 | 290834.54 | 58053.77 |
August | 1679076.92 | 09-AUG-07:49 | 171235.93 | 778371.69 | 0.00 | 188981.00 | 112132.90 | 68102.29 | 0.00 | 296585.87 | 58053.77 |
September | 1247045.06 | 06-SEP-07:00 | 171235.93 | 423497.50 | 0.00 | 134883.36 | 112057.36 | 67993.57 | 0.00 | 273710.11 | 58053.77 |
October | 1379841.84 | 16-OCT-07:00 | 171235.93 | 541788.89 | 0.00 | 152915.91 | 106390.02 | 68023.78 | 0.00 | 275820.08 | 58053.77 |
November | 1526327.33 | 14-NOV-08:00 | 171235.93 | 660080.29 | 0.00 | 170948.45 | 112218.86 | 67922.19 | 0.00 | 280254.37 | 58053.77 |
December | 1647518.76 | 18-DEC-08:00 | 171235.93 | 778371.69 | 0.00 | 188981.12 | 111371.32 | 67864.79 | 0.00 | 266026.68 | 58053.77 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1247045.06 | 171235.93 | 423497.50 | 0.00 | 134824.06 | 106390.02 | 67784.05 | 0.00 | 252950.83 | 58053.77 | |
Maximum of Months | 1679076.92 | 172544.75 | 778371.69 | 0.00 | 188981.12 | 148210.70 | 69050.03 | 0.00 | 296585.87 | 58053.77 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 60188.04 | 31-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 60169.01 | 01-FEB-12:50 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 59586.49 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 58325.61 | 04-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 57153.87 | 02-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 55954.72 | 02-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 55369.80 | 20-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 56125.37 | 30-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 57261.69 | 28-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 58600.24 | 30-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 59667.29 | 28-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 60220.58 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 55369.80 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 60220.58 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 26.56 | 0.33 | 26.59 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 26.59 | 0.00 | 26.59 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 26.42 | 0.00 | 26.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 26.26 | 0.00 | 26.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.39 | 0.50 | 26.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.22 | 0.00 | 26.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 26.38 | 0.33 | 26.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 26.28 | 0.33 | 26.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 26.46 | 0.50 | 26.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.54 | 1.67 | 26.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 26.63 | 0.50 | 26.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 26.63 | 0.67 | 26.60 |
Annual Sum or Average | 0.00 | 0.00 | 110.83 | 26.46 | 4.83 | 26.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.22 | 0.00 | 26.22 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 26.63 | 1.67 | 26.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.59 | 0.00 | 25.59 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 25.59 | 0.00 | 25.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.59 | 0.00 | 25.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.62 | 0.00 | 25.62 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.63 | 0.00 | 25.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.94 | 0.17 | 26.13 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 26.64 | 1.83 | 26.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.04 | 5.00 | 27.21 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.01 | 6.67 | 27.21 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.81 | 3.17 | 27.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.59 | 1.83 | 26.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.69 | 0.00 | 25.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.65 | 0.00 | 25.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 25.58 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.60 | 0.00 | 25.60 |
Annual Sum or Average | 0.00 | 0.00 | 32.67 | 26.78 | 18.67 | 27.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.04 | 6.67 | 27.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.19 | 0.83 | 27.34 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.36 | 2.83 | 27.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.37 | 5.67 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.36 | 7.33 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.33 | 8.33 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.31 | 5.00 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.97 | 1.17 | 27.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.14 | 3.50 | 27.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.32 | 5.50 | 27.38 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.32 | 4.00 | 27.35 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.37 | 1.00 | 27.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.31 | 1.00 | 27.31 |
Annual Sum or Average | 0.00 | 0.00 | 51.33 | 27.31 | 46.17 | 27.39 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.97 | 0.83 | 27.14 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.37 | 8.33 | 27.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.36 | 10.50 | 27.44 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.46 | 9.00 | 27.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.19 | 5.67 | 27.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.73 | 1.67 | 26.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.43 | 1.00 | 26.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.40 | 0.67 | 26.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.64 | 0.00 | 25.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.94 | 0.17 | 26.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.70 | 0.00 | 25.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.25 | 6.00 | 27.35 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.43 | 8.50 | 27.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 26.10 | 24.67 | 26.09 |
Annual Sum or Average | 0.00 | 0.00 | 80.33 | 26.81 | 67.83 | 26.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.64 | 0.00 | 25.64 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 27.46 | 24.67 | 27.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 26.90 | 7.33 | 27.21 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 27.01 | 9.67 | 27.21 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 32.00 | 27.22 | 9.33 | 27.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 56.00 | 27.47 | 16.67 | 27.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 27.03 | 7.50 | 27.22 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 27.05 | 9.33 | 27.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 27.20 | 13.67 | 27.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 27.29 | 9.33 | 27.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 26.89 | 5.83 | 27.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 26.98 | 9.83 | 27.16 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 27.11 | 12.17 | 27.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 27.33 | 13.67 | 27.50 |
Annual Sum or Average | 0.00 | 0.00 | 361.00 | 27.18 | 124.33 | 27.35 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 26.89 | 5.83 | 27.09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 56.00 | 27.47 | 16.67 | 27.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 25.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.14 | 4.67 | 27.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.18 | 5.83 | 27.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.22 | 1.33 | 27.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.32 | 0.83 | 27.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.67 | 27.16 | 12.67 | 27.30 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.32 | 5.83 | 27.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.17 | 0.83 | 27.31 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.42 | 7.17 | 27.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.59 | 8.67 | 27.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.59 | 9.00 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.43 | 9.33 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.46 | 6.33 | 27.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.41 | 2.00 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.48 | 5.00 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.52 | 7.17 | 27.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.46 | 4.33 | 27.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.40 | 3.50 | 27.40 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.41 | 3.00 | 27.41 |
Annual Sum or Average | 0.00 | 0.00 | 68.00 | 27.48 | 66.33 | 27.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.17 | 0.83 | 27.31 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.59 | 9.33 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 25.85 | 27.17 | 25.85 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 26.70 | 12.33 | 26.72 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.41 | 5.00 | 27.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.35 | 4.33 | 27.41 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.43 | 7.67 | 27.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 | 25.59 | 40.17 | 25.59 |
Annual Sum or Average | 0.00 | 0.00 | 99.83 | 26.13 | 96.67 | 26.14 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 | 27.43 | 40.17 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.54 | 5.00 | 27.66 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.36 | 5.33 | 27.54 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.02 | 5.17 | 27.33 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 26.93 | 5.67 | 27.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.09 | 4.83 | 27.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 26.95 | 4.33 | 27.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.17 | 4.17 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 26.94 | 3.33 | 27.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.12 | 3.33 | 27.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.11 | 4.17 | 27.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.21 | 4.00 | 27.39 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.60 | 5.33 | 27.68 |
Annual Sum or Average | 0.00 | 0.00 | 98.33 | 27.12 | 54.67 | 27.37 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 26.93 | 3.33 | 27.20 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.60 | 5.67 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.38 | 3.50 | 27.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.37 | 4.17 | 27.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.38 | 4.67 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.24 | 7.83 | 27.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.21 | 7.17 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.29 | 8.67 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.39 | 3.00 | 27.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.25 | 4.33 | 27.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.34 | 1.83 | 27.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.30 | 1.00 | 27.30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 63.00 | 27.29 | 46.17 | 27.39 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.39 | 8.67 | 27.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.41 | 6.00 | 27.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.58 | 11.17 | 27.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.69 | 9.33 | 27.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.67 | 11.33 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.55 | 10.00 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.55 | 9.17 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.42 | 9.83 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.61 | 6.33 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.53 | 9.17 | 27.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.51 | 10.00 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.46 | 7.67 | 27.48 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.46 | 9.17 | 27.46 |
Annual Sum or Average | 0.00 | 0.00 | 123.83 | 27.55 | 109.17 | 27.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.41 | 6.00 | 27.41 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.69 | 11.33 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.04 | 14.00 | 27.05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.65 | 9.67 | 27.72 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.52 | 6.50 | 27.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.34 | 4.33 | 27.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.22 | 5.00 | 27.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.35 | 3.67 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.32 | 3.17 | 27.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.47 | 2.50 | 27.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.33 | 5.17 | 27.39 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.51 | 8.33 | 27.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.51 | 9.83 | 27.62 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 26.85 | 17.33 | 26.84 |
Annual Sum or Average | 0.00 | 0.00 | 106.00 | 27.28 | 89.50 | 27.33 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.85 | 2.50 | 26.84 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.65 | 17.33 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.86 | 5.83 | 27.91 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.68 | 6.33 | 27.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.35 | 5.83 | 27.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.18 | 7.50 | 27.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.32 | 7.00 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.29 | 5.50 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.38 | 7.33 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.32 | 4.50 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.36 | 5.33 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.33 | 6.17 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.47 | 6.00 | 27.59 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.73 | 6.67 | 27.82 |
Annual Sum or Average | 0.00 | 0.00 | 131.83 | 27.39 | 74.00 | 27.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.18 | 4.50 | 27.41 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.86 | 7.50 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.64 | 6.17 | 27.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.67 | 2.33 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.17 | 27.65 | 8.50 | 27.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.67 | 6.17 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.63 | 7.50 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.60 | 11.33 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 19.00 | 27.62 | 18.83 | 27.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.63 | 11.33 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.74 | 11.33 | 27.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.70 | 8.67 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 25.33 | 27.72 | 20.00 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.74 | 11.33 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 213.00 | 25.59 | 502.00 | 24.95 | 213.00 | 25.10 |
February | 191.50 | 25.52 | 454.00 | 24.91 | 191.50 | 25.05 |
March | 208.67 | 25.35 | 514.00 | 24.78 | 208.67 | 24.91 |
April | 205.67 | 25.51 | 485.00 | 24.90 | 205.67 | 25.04 |
May | 232.83 | 25.34 | 508.00 | 24.84 | 232.83 | 24.96 |
June | 208.33 | 25.34 | 496.00 | 24.79 | 208.33 | 24.92 |
July | 205.17 | 25.69 | 497.00 | 24.99 | 205.17 | 25.15 |
August | 196.33 | 25.46 | 514.00 | 24.81 | 196.33 | 24.95 |
September | 221.17 | 25.39 | 485.00 | 24.87 | 221.17 | 24.99 |
October | 229.00 | 25.49 | 502.00 | 24.94 | 229.00 | 25.07 |
November | 204.67 | 25.64 | 489.00 | 24.97 | 204.67 | 25.12 |
December | 201.17 | 25.70 | 497.00 | 24.98 | 201.17 | 25.14 |
Annual Sum or Average | 2517.50 | 25.50 | 5943.00 | 24.89 | 2517.50 | 25.03 |
Minimum of Months | 191.50 | 25.34 | 454.00 | 24.78 | 191.50 | 24.91 |
Maximum of Months | 232.83 | 25.70 | 514.00 | 24.99 | 232.83 | 25.15 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 24.32 | 0.00 | 24.32 |
February | 0.00 | 0.00 | 454.00 | 24.23 | 0.00 | 24.23 |
March | 0.00 | 0.00 | 514.00 | 24.17 | 0.00 | 24.17 |
April | 0.00 | 0.00 | 485.00 | 24.20 | 0.00 | 24.20 |
May | 0.00 | 0.00 | 508.00 | 24.23 | 0.00 | 24.23 |
June | 0.00 | 0.00 | 496.00 | 24.19 | 0.00 | 24.19 |
July | 0.00 | 0.00 | 497.00 | 24.23 | 0.00 | 24.23 |
August | 0.00 | 0.00 | 514.00 | 24.19 | 0.00 | 24.19 |
September | 0.00 | 0.00 | 485.00 | 24.25 | 0.00 | 24.25 |
October | 0.00 | 0.00 | 502.00 | 24.26 | 0.00 | 24.26 |
November | 0.00 | 0.00 | 489.00 | 24.25 | 0.00 | 24.25 |
December | 0.00 | 0.00 | 497.00 | 24.25 | 0.00 | 24.25 |
Annual Sum or Average | 0.00 | 5943.00 | 24.23 | 0.00 | 24.23 | |
Minimum of Months | 0.00 | 0.00 | 454.00 | 24.17 | 0.00 | 24.17 |
Maximum of Months | 0.00 | 0.00 | 514.00 | 24.32 | 0.00 | 24.32 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 24.83 | 484.33 | 24.25 | 1.00 | 24.26 |
February | 0.00 | 0.00 | 448.33 | 24.20 | 0.00 | 24.20 |
March | 0.00 | 0.00 | 512.83 | 24.16 | 0.00 | 24.16 |
April | 0.00 | 0.00 | 482.67 | 24.12 | 0.00 | 24.12 |
May | 0.00 | 0.00 | 506.83 | 24.15 | 0.00 | 24.15 |
June | 0.00 | 0.00 | 495.50 | 24.15 | 0.00 | 24.15 |
July | 0.00 | 0.00 | 494.00 | 24.21 | 0.00 | 24.21 |
August | 0.00 | 0.00 | 511.17 | 24.19 | 0.00 | 24.19 |
September | 0.00 | 0.00 | 480.67 | 24.18 | 0.00 | 24.18 |
October | 0.00 | 0.00 | 494.67 | 24.22 | 0.00 | 24.22 |
November | 0.00 | 0.00 | 478.67 | 24.24 | 0.00 | 24.24 |
December | 0.00 | 0.00 | 483.83 | 24.22 | 0.00 | 24.22 |
Annual Sum or Average | 2.50 | 24.83 | 5873.50 | 24.19 | 1.00 | 24.19 |
Minimum of Months | 0.00 | 0.00 | 448.33 | 24.12 | 0.00 | 24.12 |
Maximum of Months | 2.50 | 24.83 | 512.83 | 24.25 | 1.00 | 24.26 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 27.12 | 502.00 | 24.30 | 0.67 | 24.30 |
February | 0.00 | 0.00 | 454.00 | 24.27 | 0.00 | 24.27 |
March | 0.00 | 0.00 | 514.00 | 24.22 | 0.00 | 24.22 |
April | 0.00 | 0.00 | 485.00 | 24.22 | 0.00 | 24.22 |
May | 0.00 | 0.00 | 508.00 | 24.25 | 0.00 | 24.25 |
June | 0.00 | 0.00 | 496.00 | 24.23 | 0.00 | 24.23 |
July | 0.00 | 0.00 | 497.00 | 24.30 | 0.00 | 24.30 |
August | 0.00 | 0.00 | 513.17 | 24.24 | 0.00 | 24.24 |
September | 0.00 | 0.00 | 483.50 | 24.25 | 0.00 | 24.25 |
October | 0.00 | 0.00 | 502.00 | 24.28 | 0.00 | 24.28 |
November | 0.00 | 0.00 | 489.00 | 24.30 | 0.00 | 24.30 |
December | 0.00 | 0.00 | 497.00 | 24.27 | 0.00 | 24.27 |
Annual Sum or Average | 0.67 | 27.12 | 5940.67 | 24.26 | 0.67 | 24.26 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 24.22 | 0.00 | 24.22 |
Maximum of Months | 0.67 | 27.12 | 514.00 | 24.30 | 0.67 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 26.76 | 502.00 | 24.47 | 1.67 | 24.48 |
February | 7.83 | 26.72 | 454.00 | 24.48 | 7.83 | 24.51 |
March | 8.83 | 26.75 | 514.00 | 24.40 | 8.83 | 24.44 |
April | 18.83 | 26.75 | 485.00 | 24.54 | 18.83 | 24.62 |
May | 32.00 | 26.75 | 508.00 | 24.66 | 32.00 | 24.77 |
June | 33.83 | 26.81 | 496.00 | 24.63 | 33.83 | 24.76 |
July | 35.83 | 26.70 | 497.00 | 24.68 | 35.83 | 24.81 |
August | 16.33 | 26.70 | 514.00 | 24.45 | 16.33 | 24.51 |
September | 7.50 | 26.68 | 485.00 | 24.50 | 7.50 | 24.53 |
October | 7.67 | 26.70 | 502.00 | 24.49 | 7.67 | 24.52 |
November | 1.83 | 26.72 | 489.00 | 24.43 | 1.83 | 24.44 |
December | 3.00 | 26.80 | 497.00 | 24.42 | 3.00 | 24.43 |
Annual Sum or Average | 175.17 | 26.74 | 5943.00 | 24.51 | 175.17 | 24.58 |
Minimum of Months | 1.67 | 26.68 | 454.00 | 24.40 | 1.67 | 24.43 |
Maximum of Months | 35.83 | 26.81 | 514.00 | 24.68 | 35.83 | 24.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.17 | 26.74 | 502.00 | 24.61 | 22.17 | 24.70 |
February | 30.67 | 26.75 | 454.00 | 24.62 | 30.67 | 24.75 |
March | 33.17 | 26.75 | 514.00 | 24.52 | 33.17 | 24.65 |
April | 41.83 | 26.74 | 485.00 | 24.63 | 41.83 | 24.79 |
May | 41.00 | 26.80 | 508.00 | 24.67 | 41.00 | 24.82 |
June | 29.83 | 26.78 | 496.00 | 24.55 | 29.83 | 24.67 |
July | 17.83 | 26.72 | 497.00 | 24.52 | 17.83 | 24.59 |
August | 21.83 | 26.70 | 514.00 | 24.41 | 21.83 | 24.50 |
September | 39.17 | 26.73 | 485.00 | 24.67 | 39.17 | 24.81 |
October | 26.83 | 26.72 | 502.00 | 24.57 | 26.83 | 24.67 |
November | 14.50 | 26.71 | 489.00 | 24.48 | 14.50 | 24.54 |
December | 16.83 | 26.70 | 497.00 | 24.47 | 16.83 | 24.54 |
Annual Sum or Average | 335.67 | 26.74 | 5943.00 | 24.56 | 335.67 | 24.67 |
Minimum of Months | 14.50 | 26.70 | 454.00 | 24.41 | 14.50 | 24.50 |
Maximum of Months | 41.83 | 26.80 | 514.00 | 24.67 | 41.83 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 50.50 | 26.88 | 502.00 | 24.87 | 50.50 | 25.03 |
February | 41.50 | 26.84 | 454.00 | 24.77 | 41.50 | 24.93 |
March | 27.33 | 26.79 | 514.00 | 24.54 | 27.33 | 24.64 |
April | 18.50 | 26.74 | 485.00 | 24.53 | 18.50 | 24.61 |
May | 16.00 | 26.69 | 508.00 | 24.53 | 16.00 | 24.59 |
June | 15.17 | 26.71 | 496.00 | 24.48 | 15.17 | 24.54 |
July | 15.17 | 26.71 | 497.00 | 24.54 | 15.17 | 24.60 |
August | 10.17 | 26.68 | 514.00 | 24.39 | 10.17 | 24.43 |
September | 17.17 | 26.66 | 485.00 | 24.55 | 17.17 | 24.62 |
October | 37.00 | 26.77 | 502.00 | 24.69 | 37.00 | 24.82 |
November | 43.17 | 26.83 | 489.00 | 24.75 | 43.17 | 24.90 |
December | 51.17 | 26.92 | 497.00 | 24.84 | 51.17 | 25.02 |
Annual Sum or Average | 342.83 | 26.81 | 5943.00 | 24.62 | 342.83 | 24.74 |
Minimum of Months | 10.17 | 26.66 | 454.00 | 24.39 | 10.17 | 24.43 |
Maximum of Months | 51.17 | 26.92 | 514.00 | 24.87 | 51.17 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 53.33 | 26.92 | 502.00 | 24.86 | 53.33 | 25.04 |
February | 62.67 | 26.84 | 454.00 | 24.91 | 62.67 | 25.11 |
March | 71.33 | 26.81 | 514.00 | 24.84 | 71.33 | 25.06 |
April | 101.83 | 26.78 | 485.00 | 25.04 | 101.83 | 25.29 |
May | 57.17 | 26.85 | 508.00 | 24.82 | 57.17 | 25.01 |
June | 59.50 | 26.87 | 496.00 | 24.81 | 59.50 | 25.01 |
July | 86.67 | 26.80 | 497.00 | 25.00 | 86.67 | 25.23 |
August | 78.67 | 26.78 | 514.00 | 24.87 | 78.67 | 25.09 |
September | 49.67 | 26.85 | 485.00 | 24.81 | 49.67 | 24.98 |
October | 67.67 | 26.80 | 502.00 | 24.91 | 67.67 | 25.11 |
November | 79.00 | 26.81 | 489.00 | 24.97 | 79.00 | 25.20 |
December | 90.33 | 26.83 | 497.00 | 25.02 | 90.33 | 25.26 |
Annual Sum or Average | 857.83 | 26.82 | 5943.00 | 24.91 | 857.83 | 25.12 |
Minimum of Months | 49.67 | 26.78 | 454.00 | 24.81 | 49.67 | 24.98 |
Maximum of Months | 101.83 | 26.92 | 514.00 | 25.04 | 101.83 | 25.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.50 | 26.13 | 502.00 | 24.44 | 8.50 | 24.46 |
February | 3.83 | 26.34 | 454.00 | 24.46 | 3.83 | 24.47 |
March | 9.67 | 26.10 | 514.00 | 24.42 | 9.67 | 24.45 |
April | 9.17 | 26.46 | 485.00 | 24.49 | 9.17 | 24.53 |
May | 43.33 | 26.65 | 508.00 | 24.70 | 43.33 | 24.84 |
June | 41.50 | 26.70 | 496.00 | 24.69 | 41.50 | 24.83 |
July | 38.00 | 26.63 | 497.00 | 24.73 | 38.00 | 24.86 |
August | 35.50 | 26.27 | 514.00 | 24.54 | 35.50 | 24.64 |
September | 13.67 | 26.08 | 485.00 | 24.49 | 13.67 | 24.53 |
October | 12.50 | 26.35 | 502.00 | 24.51 | 12.50 | 24.55 |
November | 6.50 | 26.24 | 489.00 | 24.46 | 6.50 | 24.48 |
December | 3.33 | 26.07 | 496.17 | 24.40 | 3.33 | 24.41 |
Annual Sum or Average | 225.50 | 26.47 | 5942.17 | 24.53 | 225.50 | 24.60 |
Minimum of Months | 3.33 | 26.07 | 454.00 | 24.40 | 3.33 | 24.41 |
Maximum of Months | 43.33 | 26.70 | 514.00 | 24.73 | 43.33 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.50 | 26.72 | 427.00 | 24.76 | 30.50 | 24.88 |
February | 47.83 | 26.72 | 385.00 | 24.88 | 47.83 | 25.06 |
March | 44.50 | 26.77 | 433.00 | 24.77 | 44.50 | 24.94 |
April | 48.83 | 26.79 | 410.00 | 24.88 | 48.83 | 25.06 |
May | 51.33 | 26.79 | 430.00 | 24.87 | 51.33 | 25.05 |
June | 42.67 | 26.71 | 418.00 | 24.78 | 42.67 | 24.94 |
July | 45.83 | 26.66 | 422.00 | 24.87 | 45.83 | 25.03 |
August | 44.50 | 26.62 | 433.00 | 24.73 | 44.50 | 24.89 |
September | 49.33 | 26.70 | 410.00 | 24.85 | 49.33 | 25.03 |
October | 48.83 | 26.66 | 427.00 | 24.84 | 48.83 | 25.01 |
November | 36.00 | 26.70 | 417.00 | 24.78 | 36.00 | 24.93 |
December | 37.17 | 26.71 | 422.00 | 24.78 | 37.17 | 24.92 |
Annual Sum or Average | 527.33 | 26.71 | 5034.00 | 24.82 | 527.33 | 24.98 |
Minimum of Months | 30.50 | 26.62 | 385.00 | 24.73 | 30.50 | 24.88 |
Maximum of Months | 51.33 | 26.79 | 433.00 | 24.88 | 51.33 | 25.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 58.67 | 26.86 | 502.00 | 24.94 | 58.67 | 25.12 |
February | 43.67 | 26.83 | 454.00 | 24.84 | 43.67 | 25.00 |
March | 32.17 | 26.63 | 514.00 | 24.59 | 32.17 | 24.70 |
April | 7.50 | 26.40 | 485.00 | 24.47 | 7.50 | 24.50 |
May | 21.17 | 26.34 | 508.00 | 24.53 | 21.17 | 24.60 |
June | 18.33 | 26.29 | 496.00 | 24.48 | 18.33 | 24.55 |
July | 8.00 | 26.44 | 497.00 | 24.53 | 8.00 | 24.56 |
August | 28.17 | 25.98 | 514.00 | 24.46 | 28.17 | 24.54 |
September | 20.83 | 26.29 | 485.00 | 24.54 | 20.83 | 24.61 |
October | 49.33 | 26.68 | 502.00 | 24.75 | 49.33 | 24.91 |
November | 52.33 | 26.82 | 489.00 | 24.84 | 52.33 | 25.01 |
December | 58.00 | 26.91 | 497.00 | 24.94 | 58.00 | 25.13 |
Annual Sum or Average | 398.17 | 26.65 | 5943.00 | 24.66 | 398.17 | 24.78 |
Minimum of Months | 7.50 | 25.98 | 454.00 | 24.46 | 7.50 | 24.50 |
Maximum of Months | 58.67 | 26.91 | 514.00 | 24.94 | 58.67 | 25.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 33.17 | 26.76 | 502.00 | 24.69 | 33.17 | 24.81 |
February | 30.33 | 26.83 | 454.00 | 24.72 | 30.33 | 24.85 |
March | 39.17 | 26.90 | 514.00 | 24.71 | 39.17 | 24.85 |
April | 48.17 | 26.87 | 485.00 | 24.81 | 48.17 | 24.98 |
May | 44.00 | 26.80 | 508.00 | 24.74 | 44.00 | 24.89 |
June | 41.00 | 26.83 | 496.00 | 24.70 | 41.00 | 24.85 |
July | 46.67 | 26.75 | 497.00 | 24.81 | 46.67 | 24.96 |
August | 45.17 | 26.67 | 514.00 | 24.68 | 45.17 | 24.83 |
September | 36.00 | 26.69 | 485.00 | 24.69 | 36.00 | 24.82 |
October | 46.67 | 26.77 | 502.00 | 24.77 | 46.67 | 24.93 |
November | 36.83 | 26.77 | 489.00 | 24.73 | 36.83 | 24.86 |
December | 32.50 | 26.81 | 497.00 | 24.70 | 32.50 | 24.82 |
Annual Sum or Average | 479.67 | 26.79 | 5943.00 | 24.73 | 479.67 | 24.87 |
Minimum of Months | 30.33 | 26.67 | 454.00 | 24.68 | 30.33 | 24.81 |
Maximum of Months | 48.17 | 26.90 | 514.00 | 24.81 | 48.17 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.67 | 26.29 | 498.33 | 24.52 | 19.67 | 24.59 |
February | 30.50 | 26.58 | 454.00 | 24.61 | 30.50 | 24.73 |
March | 30.33 | 26.47 | 514.00 | 24.53 | 30.33 | 24.63 |
April | 31.00 | 26.66 | 485.00 | 24.64 | 31.00 | 24.75 |
May | 52.67 | 26.76 | 508.00 | 24.77 | 52.67 | 24.94 |
June | 46.33 | 26.77 | 496.00 | 24.73 | 46.33 | 24.89 |
July | 48.17 | 26.75 | 497.00 | 24.81 | 48.17 | 24.97 |
August | 41.67 | 26.41 | 514.00 | 24.59 | 41.67 | 24.72 |
September | 32.67 | 26.45 | 485.00 | 24.61 | 32.67 | 24.71 |
October | 41.00 | 26.57 | 502.00 | 24.66 | 41.00 | 24.79 |
November | 28.67 | 26.50 | 489.00 | 24.59 | 28.67 | 24.69 |
December | 20.33 | 26.34 | 490.00 | 24.51 | 20.17 | 24.58 |
Annual Sum or Average | 423.00 | 26.58 | 5932.33 | 24.63 | 422.83 | 24.75 |
Minimum of Months | 19.67 | 26.29 | 454.00 | 24.51 | 19.67 | 24.58 |
Maximum of Months | 52.67 | 26.77 | 514.00 | 24.81 | 52.67 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 58.50 | 26.64 | 501.67 | 24.78 | 58.50 | 24.95 |
February | 55.67 | 26.75 | 454.00 | 24.81 | 55.67 | 25.00 |
March | 46.50 | 26.81 | 514.00 | 24.69 | 46.50 | 24.85 |
April | 52.67 | 26.85 | 485.00 | 24.80 | 52.67 | 24.98 |
May | 54.67 | 26.85 | 508.00 | 24.79 | 54.67 | 24.97 |
June | 46.00 | 26.79 | 496.00 | 24.71 | 46.00 | 24.87 |
July | 56.50 | 26.74 | 497.00 | 24.82 | 56.50 | 25.00 |
August | 46.50 | 26.65 | 514.00 | 24.65 | 46.50 | 24.80 |
September | 54.17 | 26.75 | 485.00 | 24.77 | 54.17 | 24.95 |
October | 60.50 | 26.74 | 501.50 | 24.79 | 60.50 | 24.98 |
November | 55.17 | 26.68 | 489.00 | 24.77 | 55.17 | 24.94 |
December | 57.17 | 26.69 | 497.00 | 24.76 | 57.17 | 24.94 |
Annual Sum or Average | 644.00 | 26.74 | 5942.17 | 24.76 | 644.00 | 24.94 |
Minimum of Months | 46.00 | 26.64 | 454.00 | 24.65 | 46.00 | 24.80 |
Maximum of Months | 60.50 | 26.85 | 514.00 | 24.82 | 60.50 | 25.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.50 | 26.87 | 502.00 | 24.92 | 62.50 | 25.12 |
February | 47.67 | 26.85 | 454.00 | 24.84 | 47.67 | 25.02 |
March | 37.00 | 26.67 | 514.00 | 24.63 | 37.00 | 24.75 |
April | 29.83 | 26.64 | 485.00 | 24.62 | 29.83 | 24.73 |
May | 39.17 | 26.60 | 508.00 | 24.65 | 39.17 | 24.78 |
June | 34.00 | 26.57 | 496.00 | 24.59 | 34.00 | 24.71 |
July | 36.50 | 26.65 | 497.00 | 24.70 | 36.50 | 24.82 |
August | 39.83 | 26.24 | 514.00 | 24.54 | 39.83 | 24.65 |
September | 34.17 | 26.51 | 485.00 | 24.63 | 34.17 | 24.75 |
October | 55.17 | 26.78 | 502.00 | 24.80 | 55.17 | 24.98 |
November | 58.33 | 26.84 | 489.00 | 24.86 | 58.33 | 25.05 |
December | 62.33 | 26.91 | 497.00 | 24.93 | 62.33 | 25.12 |
Annual Sum or Average | 536.50 | 26.71 | 5943.00 | 24.73 | 536.50 | 24.88 |
Minimum of Months | 29.83 | 26.24 | 454.00 | 24.54 | 29.83 | 24.65 |
Maximum of Months | 62.50 | 26.91 | 514.00 | 24.93 | 62.50 | 25.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 38.67 | 26.71 | 500.50 | 24.71 | 38.67 | 24.84 |
February | 36.17 | 26.81 | 454.00 | 24.75 | 36.17 | 24.89 |
March | 49.67 | 26.89 | 514.00 | 24.75 | 49.67 | 24.92 |
April | 57.83 | 26.85 | 485.00 | 24.85 | 57.83 | 25.04 |
May | 51.67 | 26.85 | 508.00 | 24.78 | 51.67 | 24.95 |
June | 45.67 | 26.82 | 496.00 | 24.72 | 45.67 | 24.88 |
July | 57.33 | 26.78 | 497.00 | 24.86 | 57.33 | 25.04 |
August | 49.50 | 26.69 | 514.00 | 24.70 | 49.50 | 24.86 |
September | 45.00 | 26.68 | 485.00 | 24.72 | 45.00 | 24.88 |
October | 53.00 | 26.76 | 501.67 | 24.78 | 53.00 | 24.96 |
November | 46.83 | 26.73 | 489.00 | 24.76 | 46.83 | 24.92 |
December | 37.67 | 26.78 | 495.67 | 24.71 | 37.67 | 24.85 |
Annual Sum or Average | 569.00 | 26.78 | 5939.83 | 24.76 | 569.00 | 24.92 |
Minimum of Months | 36.17 | 26.68 | 454.00 | 24.70 | 36.17 | 24.84 |
Maximum of Months | 57.83 | 26.89 | 514.00 | 24.86 | 57.83 | 25.04 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 36.67 | 27.00 | 502.00 | 27.00 | 36.67 | 27.00 |
February | 101.33 | 27.00 | 454.00 | 27.00 | 101.33 | 27.00 |
March | 259.83 | 27.00 | 514.00 | 27.00 | 259.83 | 27.00 |
April | 430.67 | 27.06 | 485.00 | 27.06 | 430.67 | 27.06 |
May | 106.50 | 27.00 | 508.00 | 27.00 | 106.50 | 27.00 |
June | 176.50 | 27.00 | 496.00 | 27.00 | 176.50 | 27.00 |
July | 248.17 | 27.00 | 497.00 | 27.00 | 248.17 | 27.00 |
August | 416.67 | 27.05 | 514.00 | 27.05 | 416.67 | 27.05 |
September | 57.33 | 27.00 | 485.00 | 27.00 | 57.33 | 27.00 |
October | 95.00 | 27.00 | 502.00 | 27.00 | 95.00 | 27.00 |
November | 235.67 | 27.00 | 489.00 | 27.00 | 235.67 | 27.00 |
December | 336.67 | 27.00 | 497.00 | 27.00 | 336.67 | 27.00 |
Annual Sum or Average | 2501.00 | 27.02 | 5943.00 | 27.01 | 2501.00 | 27.01 |
Minimum of Months | 36.67 | 27.00 | 454.00 | 27.00 | 36.67 | 27.00 |
Maximum of Months | 430.67 | 27.06 | 514.00 | 27.06 | 430.67 | 27.06 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 27.00 | 502.00 | 27.00 | 2.50 | 27.00 |
February | 3.50 | 27.00 | 454.00 | 27.00 | 3.50 | 27.00 |
March | 7.33 | 27.00 | 514.00 | 27.00 | 7.33 | 27.00 |
April | 79.17 | 27.34 | 485.00 | 27.11 | 79.17 | 27.14 |
May | 5.67 | 27.00 | 508.00 | 27.00 | 5.67 | 27.00 |
June | 5.50 | 27.00 | 496.00 | 27.00 | 5.50 | 27.00 |
July | 1.83 | 27.00 | 497.00 | 27.00 | 1.83 | 27.00 |
August | 61.00 | 27.40 | 514.00 | 27.10 | 61.00 | 27.13 |
September | 5.00 | 27.00 | 485.00 | 27.00 | 5.00 | 27.00 |
October | 0.67 | 27.00 | 502.00 | 27.00 | 0.67 | 27.00 |
November | 2.83 | 27.00 | 489.00 | 27.00 | 2.83 | 27.00 |
December | 17.33 | 27.00 | 497.00 | 27.00 | 17.33 | 27.00 |
Annual Sum or Average | 192.33 | 27.27 | 5943.00 | 27.02 | 192.33 | 27.03 |
Minimum of Months | 0.67 | 27.00 | 454.00 | 27.00 | 0.67 | 27.00 |
Maximum of Months | 79.17 | 27.40 | 514.00 | 27.11 | 79.17 | 27.14 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.00 | 27.00 | 502.00 | 27.00 | 29.00 | 27.00 |
February | 53.17 | 27.00 | 454.00 | 27.00 | 53.17 | 27.00 |
March | 96.17 | 27.00 | 514.00 | 27.00 | 96.17 | 27.00 |
April | 144.83 | 27.21 | 485.00 | 27.10 | 144.83 | 27.12 |
May | 84.50 | 27.00 | 508.00 | 27.00 | 84.50 | 27.00 |
June | 79.67 | 27.00 | 496.00 | 27.00 | 79.67 | 27.00 |
July | 51.33 | 27.00 | 497.00 | 27.00 | 51.33 | 27.00 |
August | 98.83 | 27.24 | 514.00 | 27.08 | 98.83 | 27.10 |
September | 50.00 | 27.00 | 485.00 | 27.00 | 50.00 | 27.00 |
October | 42.33 | 27.00 | 502.00 | 27.00 | 42.33 | 27.00 |
November | 47.00 | 27.00 | 489.00 | 27.00 | 47.00 | 27.00 |
December | 75.00 | 27.01 | 497.00 | 27.00 | 75.00 | 27.00 |
Annual Sum or Average | 851.83 | 27.07 | 5943.00 | 27.02 | 851.83 | 27.02 |
Minimum of Months | 29.00 | 27.00 | 454.00 | 27.00 | 29.00 | 27.00 |
Maximum of Months | 144.83 | 27.24 | 514.00 | 27.10 | 144.83 | 27.12 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5943.00 | 27.00 | 5943.00 | 27.00 | 5943.00 | 27.00 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00021 | 43.15153 | 1.01794 | 26.89841 |
February | 454.00000 | 27.00268 | 40.63176 | 1.02963 | 27.40238 |
March | 514.00000 | 27.00169 | 39.76890 | 1.05356 | 28.44415 |
April | 485.00000 | 27.05415 | 39.50566 | 1.09405 | 30.27593 |
May | 508.00000 | 27.00001 | 47.29733 | 0.38620 | 8.13316 |
June | 496.00000 | 27.00410 | 42.98001 | 0.39994 | 8.36319 |
July | 497.00000 | 27.00203 | 39.82992 | 0.41350 | 8.59305 |
August | 514.00000 | 27.04319 | 39.43340 | 0.46179 | 9.51949 |
September | 485.00000 | 27.00001 | 46.58982 | 0.37594 | 7.97041 |
October | 502.00000 | 27.00384 | 41.99234 | 1.03515 | 27.63663 |
November | 489.00000 | 27.00204 | 39.75592 | 1.05063 | 28.31463 |
December | 497.00000 | 27.00072 | 38.42364 | 1.06956 | 29.15655 |
Annual Sum or Average | 5943.00000 | 27.00959 | 41.61755 | 0.77997 | 19.98440 |
Minimum of Months | 454.00000 | 27.00001 | 38.42364 | 0.37594 | 7.97041 |
Maximum of Months | 514.00000 | 27.05415 | 47.29733 | 1.09405 | 30.27593 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00008 | 43.49835 | 0.98302 | 25.42845 |
February | 454.00000 | 27.00258 | 40.73552 | 0.97899 | 25.26337 |
March | 514.00000 | 27.00164 | 39.79845 | 0.98761 | 25.61803 |
April | 485.00000 | 27.06812 | 39.50283 | 1.01298 | 26.70991 |
May | 508.00000 | 27.00001 | 47.84158 | 0.33671 | 7.38311 |
June | 496.00000 | 27.00385 | 43.18046 | 0.32655 | 7.24690 |
July | 497.00000 | 27.00195 | 39.87839 | 0.31603 | 7.10649 |
August | 514.00000 | 27.06027 | 39.43538 | 0.34781 | 7.60052 |
September | 485.00000 | 27.00001 | 47.15151 | 0.32502 | 7.22442 |
October | 502.00000 | 27.00365 | 42.18070 | 0.98391 | 25.46288 |
November | 489.00000 | 27.00197 | 39.80455 | 0.98288 | 25.42177 |
December | 497.00000 | 27.00065 | 38.40883 | 0.98590 | 25.55030 |
Annual Sum or Average | 5943.00000 | 27.01213 | 41.78909 | 0.71141 | 17.92971 |
Minimum of Months | 454.00000 | 27.00001 | 38.40883 | 0.31603 | 7.10649 |
Maximum of Months | 514.00000 | 27.06812 | 47.84158 | 1.01298 | 26.70991 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00014 | 43.43639 | 0.99483 | 25.93900 |
February | 454.00000 | 27.00267 | 40.73112 | 0.99543 | 25.97301 |
March | 514.00000 | 27.00171 | 39.81801 | 1.00646 | 26.43423 |
April | 485.00000 | 27.06499 | 39.53349 | 1.03495 | 27.69014 |
May | 508.00000 | 27.00001 | 47.60305 | 0.36276 | 7.80507 |
June | 496.00000 | 27.00406 | 43.12808 | 0.35544 | 7.70427 |
July | 497.00000 | 27.00206 | 39.90000 | 0.34083 | 7.48953 |
August | 514.00000 | 27.04678 | 39.48525 | 0.36592 | 7.93257 |
September | 485.00000 | 27.00001 | 46.94116 | 0.34724 | 7.57709 |
October | 502.00000 | 27.00379 | 42.16967 | 0.99745 | 26.04829 |
November | 489.00000 | 27.00207 | 39.83314 | 0.99689 | 26.02830 |
December | 497.00000 | 27.00149 | 38.45190 | 0.99877 | 26.11454 |
Annual Sum or Average | 5943.00000 | 27.01084 | 41.75693 | 0.73055 | 18.48795 |
Minimum of Months | 454.00000 | 27.00001 | 38.45190 | 0.34083 | 7.48953 |
Maximum of Months | 514.00000 | 27.06499 | 47.60305 | 1.03495 | 27.69014 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 40.72506 | 1.19657 | 35.08179 |
February | 454.00000 | 27.00000 | 40.58913 | 1.33953 | 42.32021 |
March | 514.00000 | 27.00000 | 40.46274 | 1.47568 | 49.58144 |
April | 485.00000 | 27.00000 | 40.40019 | 1.60650 | 56.69875 |
May | 508.00000 | 27.00000 | 40.58683 | 0.62209 | 13.14970 |
June | 496.00000 | 27.00000 | 40.44013 | 0.82757 | 19.45411 |
July | 497.00000 | 27.00000 | 40.40766 | 1.02391 | 27.14388 |
August | 514.00000 | 27.00000 | 40.35761 | 1.21021 | 35.75104 |
September | 485.00000 | 27.00000 | 40.69401 | 0.62691 | 13.27350 |
October | 502.00000 | 27.00000 | 40.48091 | 1.33862 | 42.27290 |
November | 489.00000 | 27.00000 | 40.46538 | 1.47932 | 49.77873 |
December | 497.00000 | 27.00000 | 40.51995 | 1.60930 | 56.85120 |
Annual Sum or Average | 5943.00000 | 27.00000 | 40.50988 | 1.19521 | 36.72547 |
Minimum of Months | 454.00000 | 27.00000 | 40.35761 | 0.62209 | 13.14970 |
Maximum of Months | 514.00000 | 27.00000 | 40.72506 | 1.60930 | 56.85120 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.67958 | 61.54400 | 0.70134 | 16.40874 |
February | 454.00000 | 24.65190 | 62.04880 | 0.69625 | 16.22481 |
March | 514.00000 | 24.54859 | 62.02028 | 0.67333 | 15.35797 |
April | 485.00000 | 24.64167 | 63.38646 | 0.70612 | 16.67208 |
May | 508.00000 | 24.61353 | 64.26882 | -0.1331 | 7.39707 |
June | 496.00000 | 24.56344 | 64.09158 | -0.1469 | 7.35033 |
July | 497.00000 | 24.70210 | 62.09705 | -0.1182 | 7.35975 |
August | 514.00000 | 24.55902 | 63.16196 | -0.1491 | 7.28938 |
September | 485.00000 | 24.63329 | 64.63118 | -0.1251 | 7.45626 |
October | 502.00000 | 24.68257 | 64.44915 | 0.72186 | 17.31158 |
November | 489.00000 | 24.68882 | 62.63855 | 0.71227 | 16.86895 |
December | 497.00000 | 24.69502 | 62.27468 | 0.71144 | 16.85023 |
Annual Sum or Average | 5943.00000 | 24.63769 | 63.05434 | 0.35074 | 12.67397 |
Minimum of Months | 454.00000 | 24.54859 | 61.54400 | -0.1491 | 7.28938 |
Maximum of Months | 514.00000 | 24.70210 | 64.63118 | 0.72186 | 17.31158 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.32215 | 54.32193 | 0.57963 | 12.30383 |
February | 454.00000 | 24.23349 | 54.50778 | 0.56429 | 11.79496 |
March | 514.00000 | 24.17315 | 55.36085 | 0.56135 | 11.66667 |
April | 485.00000 | 24.20494 | 55.41824 | 0.57310 | 11.96160 |
May | 508.00000 | 24.22531 | 55.92694 | -0.2994 | 7.09787 |
June | 496.00000 | 24.19468 | 55.20593 | -0.3047 | 7.10610 |
July | 497.00000 | 24.23129 | 55.62606 | -0.2870 | 6.89734 |
August | 514.00000 | 24.18641 | 55.72802 | -0.2924 | 6.91515 |
September | 485.00000 | 24.25097 | 56.37795 | -0.2920 | 7.06700 |
October | 502.00000 | 24.25714 | 55.86309 | 0.57561 | 12.07574 |
November | 489.00000 | 24.24692 | 54.71477 | 0.57323 | 12.00700 |
December | 497.00000 | 24.24516 | 54.16712 | 0.57303 | 12.00693 |
Annual Sum or Average | 5943.00000 | 24.23074 | 55.27444 | 0.20695 | 9.88904 |
Minimum of Months | 454.00000 | 24.17315 | 54.16712 | -0.3047 | 6.89734 |
Maximum of Months | 514.00000 | 24.32215 | 56.37795 | 0.57963 | 12.30383 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.22596 | 54.74041 | 0.53871 | 11.29418 |
February | 454.00000 | 24.19344 | 54.96858 | 0.53262 | 11.07768 |
March | 514.00000 | 24.15611 | 56.26823 | 0.53075 | 11.00323 |
April | 485.00000 | 24.11276 | 57.03401 | 0.52378 | 10.82914 |
May | 508.00000 | 24.14982 | 56.61845 | -0.3524 | 7.79198 |
June | 496.00000 | 24.15216 | 55.86521 | -0.3531 | 7.81046 |
July | 497.00000 | 24.20268 | 56.69886 | -0.3365 | 7.64976 |
August | 514.00000 | 24.18241 | 57.01092 | -0.3412 | 7.70675 |
September | 485.00000 | 24.17078 | 57.11035 | -0.3451 | 7.72159 |
October | 502.00000 | 24.20986 | 56.62642 | 0.54329 | 11.33733 |
November | 489.00000 | 24.22790 | 55.46518 | 0.54223 | 11.33148 |
December | 497.00000 | 24.20558 | 55.20213 | 0.53473 | 11.15133 |
Annual Sum or Average | 5943.00000 | 24.18241 | 56.14268 | 0.16467 | 9.71258 |
Minimum of Months | 454.00000 | 24.11276 | 54.74041 | -0.3531 | 7.64976 |
Maximum of Months | 514.00000 | 24.22790 | 57.11035 | 0.54329 | 11.33733 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.29348 | 54.91738 | 0.56828 | 12.00188 |
February | 454.00000 | 24.26868 | 54.90147 | 0.56662 | 11.91730 |
March | 514.00000 | 24.22090 | 55.82046 | 0.56359 | 11.80247 |
April | 485.00000 | 24.21504 | 56.11911 | 0.56530 | 11.82634 |
May | 508.00000 | 24.24841 | 55.94311 | -0.2941 | 7.12730 |
June | 496.00000 | 24.23064 | 55.46720 | -0.2974 | 7.15332 |
July | 497.00000 | 24.30104 | 56.13940 | -0.2837 | 7.07707 |
August | 514.00000 | 24.23755 | 56.51918 | -0.3036 | 7.23754 |
September | 485.00000 | 24.25114 | 56.51189 | -0.2964 | 7.16933 |
October | 502.00000 | 24.28318 | 56.40799 | 0.57334 | 12.10323 |
November | 489.00000 | 24.30399 | 55.52319 | 0.57406 | 12.13536 |
December | 497.00000 | 24.27066 | 55.33077 | 0.56327 | 11.84482 |
Annual Sum or Average | 5943.00000 | 24.26024 | 55.80709 | 0.20480 | 9.93064 |
Minimum of Months | 454.00000 | 24.21504 | 54.90147 | -0.3036 | 7.07707 |
Maximum of Months | 514.00000 | 24.30399 | 56.51918 | 0.57406 | 12.13536 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.46008 | 53.01442 | 0.62269 | 13.58232 |
February | 454.00000 | 24.43727 | 52.94052 | 0.62766 | 13.71278 |
March | 514.00000 | 24.35863 | 53.93220 | 0.62756 | 13.59401 |
April | 485.00000 | 24.45849 | 53.86399 | 0.66298 | 14.68237 |
May | 508.00000 | 24.52498 | 54.13205 | -0.1353 | 6.54489 |
June | 496.00000 | 24.48386 | 53.29997 | -0.1227 | 6.39238 |
July | 497.00000 | 24.53286 | 53.82854 | -0.1322 | 6.45248 |
August | 514.00000 | 24.37390 | 54.41491 | -0.1864 | 6.40887 |
September | 485.00000 | 24.46229 | 54.94006 | -0.1867 | 6.57786 |
October | 502.00000 | 24.45762 | 54.51211 | 0.63656 | 13.94976 |
November | 489.00000 | 24.42578 | 53.34027 | 0.62727 | 13.64619 |
December | 497.00000 | 24.40524 | 52.86450 | 0.61725 | 13.38364 |
Annual Sum or Average | 5943.00000 | 24.44816 | 53.76399 | 0.30172 | 10.71283 |
Minimum of Months | 454.00000 | 24.35863 | 52.86450 | -0.1867 | 6.39238 |
Maximum of Months | 514.00000 | 24.53286 | 54.94006 | 0.66298 | 14.68237 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.51980 | 52.58293 | 0.66108 | 14.77991 |
February | 454.00000 | 24.47673 | 52.57237 | 0.66438 | 14.86680 |
March | 514.00000 | 24.37578 | 53.68689 | 0.65893 | 14.60015 |
April | 485.00000 | 24.44947 | 53.73051 | 0.68276 | 15.35749 |
May | 508.00000 | 24.50150 | 54.14147 | -0.1311 | 6.64915 |
June | 496.00000 | 24.41926 | 53.48707 | -0.1484 | 6.41646 |
July | 497.00000 | 24.44139 | 54.13922 | -0.1694 | 6.49236 |
August | 514.00000 | 24.31114 | 54.56549 | -0.1986 | 6.54544 |
September | 485.00000 | 24.50514 | 54.64425 | -0.1437 | 6.68212 |
October | 502.00000 | 24.45573 | 54.39821 | 0.65014 | 14.42015 |
November | 489.00000 | 24.41013 | 53.28126 | 0.63576 | 13.94159 |
December | 497.00000 | 24.39209 | 52.77754 | 0.62658 | 13.71960 |
Annual Sum or Average | 5943.00000 | 24.43744 | 53.67684 | 0.31228 | 11.17098 |
Minimum of Months | 454.00000 | 24.31114 | 52.57237 | -0.1986 | 6.41646 |
Maximum of Months | 514.00000 | 24.51980 | 54.64425 | 0.68276 | 15.35749 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.66302 | 52.00522 | 0.72277 | 16.79275 |
February | 454.00000 | 24.57950 | 52.17857 | 0.70500 | 16.13214 |
March | 514.00000 | 24.41582 | 53.61520 | 0.66031 | 14.61014 |
April | 485.00000 | 24.44565 | 53.92908 | 0.65658 | 14.48921 |
May | 508.00000 | 24.46254 | 54.42120 | -0.1770 | 6.54645 |
June | 496.00000 | 24.40782 | 53.72685 | -0.1893 | 6.52303 |
July | 497.00000 | 24.47176 | 54.13055 | -0.1774 | 6.55645 |
August | 514.00000 | 24.34071 | 54.58307 | -0.2100 | 6.49261 |
September | 485.00000 | 24.48041 | 54.84711 | -0.1728 | 6.55789 |
October | 502.00000 | 24.53834 | 54.11206 | 0.67498 | 15.21554 |
November | 489.00000 | 24.56485 | 52.63167 | 0.69702 | 15.89237 |
December | 497.00000 | 24.62825 | 51.82841 | 0.72196 | 16.73805 |
Annual Sum or Average | 5943.00000 | 24.49880 | 53.51225 | 0.32231 | 11.83856 |
Minimum of Months | 454.00000 | 24.34071 | 51.82841 | -0.2100 | 6.49261 |
Maximum of Months | 514.00000 | 24.66302 | 54.84711 | 0.72277 | 16.79275 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.64100 | 52.04846 | 0.73316 | 17.11456 |
February | 454.00000 | 24.64007 | 51.86791 | 0.76695 | 18.18655 |
March | 514.00000 | 24.56861 | 52.82664 | 0.79105 | 18.92284 |
April | 485.00000 | 24.67216 | 52.78532 | 0.83762 | 20.66153 |
May | 508.00000 | 24.59260 | 53.67138 | -0.0391 | 6.52094 |
June | 496.00000 | 24.56360 | 52.82713 | -0.0103 | 6.46717 |
July | 497.00000 | 24.68709 | 53.08358 | 0.02918 | 6.74111 |
August | 514.00000 | 24.57419 | 53.37245 | 0.03086 | 6.51333 |
September | 485.00000 | 24.60183 | 54.16477 | -0.0496 | 6.50395 |
October | 502.00000 | 24.65628 | 53.48226 | 0.76053 | 17.97430 |
November | 489.00000 | 24.67804 | 52.10089 | 0.78049 | 18.66670 |
December | 497.00000 | 24.69624 | 51.42878 | 0.79933 | 19.37925 |
Annual Sum or Average | 5943.00000 | 24.63045 | 52.81321 | 0.44946 | 13.58757 |
Minimum of Months | 454.00000 | 24.56360 | 51.42878 | -0.0496 | 6.46717 |
Maximum of Months | 514.00000 | 24.69624 | 54.16477 | 0.83762 | 20.66153 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.40751 | 53.55763 | 0.59617 | 12.84025 |
February | 454.00000 | 24.44153 | 53.48366 | 0.61207 | 13.32232 |
March | 514.00000 | 24.38398 | 55.01016 | 0.61482 | 13.30528 |
April | 485.00000 | 24.45586 | 55.48246 | 0.64299 | 14.11176 |
May | 508.00000 | 24.53541 | 54.98077 | -0.1465 | 6.74588 |
June | 496.00000 | 24.51797 | 54.04137 | -0.1310 | 6.61803 |
July | 497.00000 | 24.58490 | 54.88401 | -0.1438 | 6.76310 |
August | 514.00000 | 24.41697 | 56.16935 | -0.2059 | 6.75882 |
September | 485.00000 | 24.44275 | 55.91006 | -0.2103 | 6.77195 |
October | 502.00000 | 24.46315 | 55.59534 | 0.62392 | 13.68572 |
November | 489.00000 | 24.43402 | 54.29612 | 0.60907 | 13.20830 |
December | 497.00000 | 24.38788 | 54.06142 | 0.58929 | 12.64179 |
Annual Sum or Average | 5943.00000 | 24.45594 | 54.80051 | 0.28440 | 10.53651 |
Minimum of Months | 454.00000 | 24.38398 | 53.48366 | -0.2103 | 6.61803 |
Maximum of Months | 514.00000 | 24.58490 | 56.16935 | 0.64299 | 14.11176 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 24.62256 | 53.13893 | 0.67204 | 15.23029 |
February | 385.00000 | 24.65361 | 52.98571 | 0.69383 | 15.97050 |
March | 433.00000 | 24.56562 | 54.27175 | 0.68914 | 15.73853 |
April | 410.00000 | 24.65255 | 54.62955 | 0.71682 | 16.63730 |
May | 430.00000 | 24.63715 | 54.69089 | -0.1059 | 7.00116 |
June | 418.00000 | 24.58341 | 54.07046 | -0.1146 | 6.71085 |
July | 422.00000 | 24.67154 | 54.66062 | -0.1191 | 6.86450 |
August | 433.00000 | 24.53222 | 55.72214 | -0.1505 | 6.82860 |
September | 410.00000 | 24.62958 | 55.14982 | -0.1230 | 7.00109 |
October | 427.00000 | 24.62855 | 55.01518 | 0.67748 | 15.50298 |
November | 417.00000 | 24.61939 | 53.93763 | 0.67119 | 15.23439 |
December | 422.00000 | 24.60817 | 53.55249 | 0.66344 | 15.03684 |
Annual Sum or Average | 5034.00000 | 24.61642 | 54.32949 | 0.34491 | 11.94791 |
Minimum of Months | 385.00000 | 24.53222 | 52.98571 | -0.1505 | 6.71085 |
Maximum of Months | 433.00000 | 24.67154 | 55.72214 | 0.71682 | 16.63730 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.71301 | 52.09607 | 0.72466 | 16.90193 |
February | 454.00000 | 24.64286 | 52.40397 | 0.70610 | 16.25805 |
March | 514.00000 | 24.45933 | 54.55910 | 0.65285 | 14.48563 |
April | 485.00000 | 24.44088 | 55.55575 | 0.63705 | 13.92493 |
May | 508.00000 | 24.45846 | 55.39419 | -0.1949 | 6.70993 |
June | 496.00000 | 24.41804 | 54.68547 | -0.2089 | 6.73893 |
July | 497.00000 | 24.50089 | 55.31445 | -0.1978 | 6.81446 |
August | 514.00000 | 24.37857 | 56.39369 | -0.2305 | 6.82329 |
September | 485.00000 | 24.46644 | 55.77695 | -0.1939 | 6.72398 |
October | 502.00000 | 24.56369 | 55.01664 | 0.66873 | 15.15242 |
November | 489.00000 | 24.62583 | 53.25384 | 0.69467 | 15.95622 |
December | 497.00000 | 24.71105 | 52.48789 | 0.72259 | 16.88137 |
Annual Sum or Average | 5943.00000 | 24.53039 | 54.42894 | 0.31128 | 11.90822 |
Minimum of Months | 454.00000 | 24.37857 | 52.09607 | -0.2305 | 6.70993 |
Maximum of Months | 514.00000 | 24.71301 | 56.39369 | 0.72466 | 16.90193 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.55518 | 52.72892 | 0.67337 | 15.24285 |
February | 454.00000 | 24.58427 | 52.62920 | 0.69557 | 15.93465 |
March | 514.00000 | 24.54150 | 54.07145 | 0.70909 | 16.32409 |
April | 485.00000 | 24.60637 | 54.61302 | 0.73257 | 17.08820 |
May | 508.00000 | 24.56127 | 54.68945 | -0.1051 | 6.75913 |
June | 496.00000 | 24.52606 | 53.93069 | -0.1066 | 6.64547 |
July | 497.00000 | 24.62445 | 54.61070 | -0.1032 | 6.80596 |
August | 514.00000 | 24.50484 | 55.55198 | -0.1268 | 6.66721 |
September | 485.00000 | 24.54343 | 55.25513 | -0.1262 | 6.72898 |
October | 502.00000 | 24.58270 | 54.84229 | 0.68710 | 15.72645 |
November | 489.00000 | 24.57311 | 53.48277 | 0.67980 | 15.44726 |
December | 497.00000 | 24.55954 | 53.08437 | 0.67370 | 15.27553 |
Annual Sum or Average | 5943.00000 | 24.56313 | 54.13702 | 0.35367 | 12.01544 |
Minimum of Months | 454.00000 | 24.50484 | 52.62920 | -0.1268 | 6.64547 |
Maximum of Months | 514.00000 | 24.62445 | 55.55198 | 0.73257 | 17.08820 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.44693 | 54.00499 | 0.61981 | 13.57903 |
February | 454.00000 | 24.48231 | 53.68816 | 0.63877 | 14.17473 |
March | 514.00000 | 24.41782 | 54.84908 | 0.64069 | 14.12097 |
April | 485.00000 | 24.50824 | 54.92023 | 0.67384 | 15.14771 |
May | 508.00000 | 24.56621 | 54.70363 | -0.1085 | 6.83904 |
June | 496.00000 | 24.54059 | 54.05809 | -0.0913 | 6.66352 |
July | 497.00000 | 24.62168 | 54.61329 | -0.1090 | 6.86851 |
August | 514.00000 | 24.44080 | 56.00895 | -0.1773 | 6.75165 |
September | 485.00000 | 24.48134 | 55.57482 | -0.1752 | 6.79770 |
October | 502.00000 | 24.49867 | 55.59943 | 0.64529 | 14.42988 |
November | 489.00000 | 24.47936 | 54.62454 | 0.63443 | 14.03290 |
December | 497.00000 | 24.42421 | 54.43859 | 0.61140 | 13.36607 |
Annual Sum or Average | 5943.00000 | 24.49216 | 54.76685 | 0.31375 | 11.03245 |
Minimum of Months | 454.00000 | 24.41782 | 53.68816 | -0.1773 | 6.66352 |
Maximum of Months | 514.00000 | 24.62168 | 56.00895 | 0.67384 | 15.14771 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.56050 | 53.20074 | 0.68235 | 15.52591 |
February | 454.00000 | 24.57633 | 52.95104 | 0.70485 | 16.26854 |
March | 514.00000 | 24.49383 | 54.16027 | 0.70530 | 16.18081 |
April | 485.00000 | 24.57713 | 54.30576 | 0.73415 | 17.15641 |
May | 508.00000 | 24.56316 | 54.50251 | -0.0836 | 6.91758 |
June | 496.00000 | 24.51796 | 53.99325 | -0.0858 | 6.59610 |
July | 497.00000 | 24.60734 | 54.52980 | -0.0989 | 6.83115 |
August | 514.00000 | 24.46492 | 55.61720 | -0.1314 | 6.68176 |
September | 485.00000 | 24.55449 | 54.99736 | -0.1048 | 6.90573 |
October | 502.00000 | 24.55617 | 55.07572 | 0.68680 | 15.79176 |
November | 489.00000 | 24.55373 | 54.01105 | 0.68135 | 15.52923 |
December | 497.00000 | 24.54021 | 53.61172 | 0.67134 | 15.25749 |
Annual Sum or Average | 5943.00000 | 24.54652 | 54.25843 | 0.36012 | 12.09600 |
Minimum of Months | 454.00000 | 24.46492 | 52.95104 | -0.1314 | 6.59610 |
Maximum of Months | 514.00000 | 24.60734 | 55.61720 | 0.73415 | 17.15641 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.67886 | 52.75265 | 0.73652 | 17.34823 |
February | 454.00000 | 24.63223 | 52.81416 | 0.72501 | 16.91984 |
March | 514.00000 | 24.47842 | 54.46796 | 0.67675 | 15.25317 |
April | 485.00000 | 24.49339 | 54.99534 | 0.66751 | 14.94345 |
May | 508.00000 | 24.50325 | 55.06049 | -0.1542 | 6.75076 |
June | 496.00000 | 24.45669 | 54.61610 | -0.1669 | 6.68671 |
July | 497.00000 | 24.55157 | 55.00274 | -0.1604 | 6.88100 |
August | 514.00000 | 24.40546 | 56.22673 | -0.2019 | 6.79101 |
September | 485.00000 | 24.50000 | 55.45866 | -0.1601 | 6.76871 |
October | 502.00000 | 24.58212 | 55.08647 | 0.68790 | 15.84001 |
November | 489.00000 | 24.62618 | 53.72732 | 0.71349 | 16.60383 |
December | 497.00000 | 24.67639 | 53.06919 | 0.73382 | 17.31019 |
Annual Sum or Average | 5943.00000 | 24.54767 | 54.45480 | 0.33774 | 12.29876 |
Minimum of Months | 454.00000 | 24.40546 | 52.75265 | -0.2019 | 6.68671 |
Maximum of Months | 514.00000 | 24.67886 | 56.22673 | 0.73652 | 17.34823 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.55414 | 53.28529 | 0.68993 | 15.77459 |
February | 454.00000 | 24.58807 | 52.98811 | 0.71583 | 16.60363 |
March | 514.00000 | 24.54360 | 54.04098 | 0.72927 | 17.00809 |
April | 485.00000 | 24.61047 | 54.22142 | 0.75366 | 17.83574 |
May | 508.00000 | 24.56578 | 54.49641 | -0.0767 | 6.86096 |
June | 496.00000 | 24.52832 | 54.01037 | -0.0753 | 6.68767 |
July | 497.00000 | 24.63436 | 54.43215 | -0.0780 | 6.90601 |
August | 514.00000 | 24.50379 | 55.47570 | -0.1066 | 6.72346 |
September | 485.00000 | 24.54321 | 55.05465 | -0.1027 | 6.81190 |
October | 502.00000 | 24.57386 | 54.98056 | 0.69979 | 16.19408 |
November | 489.00000 | 24.57165 | 53.94198 | 0.69645 | 15.99280 |
December | 497.00000 | 24.54959 | 53.59233 | 0.68772 | 15.73623 |
Annual Sum or Average | 5943.00000 | 24.56344 | 54.22104 | 0.37450 | 12.38677 |
Minimum of Months | 454.00000 | 24.50379 | 52.98811 | -0.1066 | 6.68767 |
Maximum of Months | 514.00000 | 24.63436 | 55.47570 | 0.75366 | 17.83574 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.194286E+12 | 221640.07 | 10-JAN-06:04 | 563.04 | 0.127646E+13 | 0.00 | 0.147074E+13 | 4.76 | 7.77 | 25-JAN-06:04 | 0.00 | 0.00 |
February | 0.186482E+12 | 219888.87 | 16-FEB-06:02 | 572.60 | 0.121213E+13 | 0.00 | 0.139861E+13 | 5.20 | 7.66 | 23-FEB-06:02 | 0.00 | 0.00 |
March | 0.222943E+12 | 196432.37 | 02-MAR-06:03 | 689.73 | 0.142987E+13 | 0.00 | 0.165281E+13 | 5.56 | 7.47 | 04-MAR-06:03 | 0.00 | 0.00 |
April | 0.226931E+12 | 217736.71 | 10-APR-05:02 | 680.12 | 0.141410E+13 | 0.00 | 0.164103E+13 | 5.53 | 7.24 | 13-APR-05:02 | 0.00 | 0.00 |
May | 0.231682E+12 | 246532.09 | 22-MAY-05:03 | 627.07 | 0.144266E+13 | 0.00 | 0.167434E+13 | 5.04 | 7.22 | 18-MAY-05:02 | 0.00 | 0.00 |
June | 0.232772E+12 | 232096.87 | 28-JUN-05:02 | 645.07 | 0.144706E+13 | 0.00 | 0.167983E+13 | 5.30 | 7.25 | 01-JUN-03:02 | 0.00 | 0.00 |
July | 0.214891E+12 | 223373.81 | 18-JUL-05:04 | 677.69 | 0.136121E+13 | 0.00 | 0.157611E+13 | 5.36 | 7.39 | 13-JUL-05:03 | 0.00 | 0.00 |
August | 0.227557E+12 | 224460.65 | 15-AUG-05:03 | 687.98 | 0.141869E+13 | 0.00 | 0.164624E+13 | 5.36 | 7.22 | 31-AUG-05:03 | 0.00 | 0.00 |
September | 0.209316E+12 | 232395.35 | 20-SEP-05:03 | 576.31 | 0.131550E+13 | 0.00 | 0.152481E+13 | 4.82 | 7.31 | 16-SEP-05:03 | 0.00 | 0.00 |
October | 0.211030E+12 | 233238.89 | 26-OCT-05:03 | 622.67 | 0.132801E+13 | 0.00 | 0.153904E+13 | 4.96 | 7.37 | 23-OCT-04:03 | 0.00 | 0.00 |
November | 0.204346E+12 | 226699.14 | 13-NOV-06:04 | 636.96 | 0.130134E+13 | 0.00 | 0.150569E+13 | 5.22 | 7.63 | 25-NOV-06:03 | 0.00 | 0.00 |
December | 0.200527E+12 | 220531.41 | 12-DEC-06:04 | 678.56 | 0.129192E+13 | 0.00 | 0.149245E+13 | 5.39 | 7.80 | 21-DEC-06:04 | 0.00 | 0.00 |
Annual Sum or Average | 0.256276E+13 | 7657.80 | 0.162389E+14 | 0.00 | 0.188017E+14 | 5.21 | 0.00 | 0.00 | ||||
Minimum of Months | 0.186482E+12 | 196432.37 | 563.04 | 0.121213E+13 | 0.00 | 0.139861E+13 | 4.76 | 7.22 | 0.00 | 0.00 | ||
Maximum of Months | 0.232772E+12 | 246532.09 | 689.73 | 0.144706E+13 | 0.00 | 0.167983E+13 | 5.56 | 7.80 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.635806E+11 | 221640.07 | 10-JAN-06:04 | 141.09 | 0.433112E+12 | 0.00 | 0.496692E+12 | 1.29 | 7.77 | 25-JAN-06:04 | 0.00 | 0.00 |
February | 0.629502E+11 | 219888.87 | 16-FEB-06:02 | 138.52 | 0.427080E+12 | 0.00 | 0.490030E+12 | 1.40 | 7.66 | 23-FEB-06:02 | 0.00 | 0.00 |
March | 0.671483E+11 | 196432.37 | 02-MAR-06:03 | 148.08 | 0.449940E+12 | 0.00 | 0.517088E+12 | 1.33 | 7.47 | 04-MAR-06:03 | 0.00 | 0.00 |
April | 0.710502E+11 | 217736.71 | 10-APR-05:02 | 154.85 | 0.464489E+12 | 0.00 | 0.535539E+12 | 1.41 | 7.24 | 13-APR-05:02 | 0.00 | 0.00 |
May | 0.850088E+11 | 246532.09 | 22-MAY-05:03 | 183.54 | 0.548557E+12 | 0.00 | 0.633566E+12 | 1.59 | 7.22 | 18-MAY-05:02 | 0.00 | 0.00 |
June | 0.897122E+11 | 232096.87 | 28-JUN-05:02 | 192.22 | 0.578843E+12 | 0.00 | 0.668556E+12 | 1.72 | 7.25 | 01-JUN-03:02 | 0.00 | 0.00 |
July | 0.608810E+11 | 223373.81 | 18-JUL-05:04 | 133.89 | 0.404268E+12 | 0.00 | 0.465149E+12 | 1.19 | 7.39 | 13-JUL-05:03 | 0.00 | 0.00 |
August | 0.889927E+11 | 224460.65 | 15-AUG-05:03 | 192.31 | 0.576311E+12 | 0.00 | 0.665304E+12 | 1.67 | 7.22 | 31-AUG-05:03 | 0.00 | 0.00 |
September | 0.707204E+11 | 232395.35 | 20-SEP-05:03 | 152.98 | 0.458760E+12 | 0.00 | 0.529480E+12 | 1.38 | 7.31 | 16-SEP-05:03 | 0.00 | 0.00 |
October | 0.680086E+11 | 233238.89 | 26-OCT-05:03 | 147.94 | 0.444503E+12 | 0.00 | 0.512512E+12 | 1.30 | 7.37 | 23-OCT-04:03 | 0.00 | 0.00 |
November | 0.703073E+11 | 226699.14 | 13-NOV-06:04 | 152.66 | 0.467677E+12 | 0.00 | 0.537985E+12 | 1.41 | 7.63 | 25-NOV-06:03 | 0.00 | 0.00 |
December | 0.566008E+11 | 220531.41 | 12-DEC-06:04 | 126.33 | 0.385064E+12 | 0.00 | 0.441665E+12 | 1.15 | 7.80 | 21-DEC-06:04 | 0.00 | 0.00 |
Annual Sum or Average | 0.854961E+12 | 1864.41 | 0.563860E+13 | 0.00 | 0.649357E+13 | 1.40 | 0.00 | 0.00 | ||||
Minimum of Months | 0.566008E+11 | 196432.37 | 126.33 | 0.385064E+12 | 0.00 | 0.441665E+12 | 1.15 | 7.22 | 0.00 | 0.00 | ||
Maximum of Months | 0.897122E+11 | 246532.09 | 192.31 | 0.578843E+12 | 0.00 | 0.668556E+12 | 1.72 | 7.80 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.334163E+11 | 744.00 | 12476.23 | 01-JAN-00:03 | 45522.80 | 04-JAN-17:00 | 30.69 | 26.90 | 2.83 |
February | 0.301825E+11 | 672.00 | 12476.23 | 01-FEB-00:10 | 79626.65 | 26-FEB-16:12 | 35.10 | 28.37 | 2.83 |
March | 0.334163E+11 | 744.00 | 12476.23 | 01-MAR-00:05 | 124225.32 | 31-MAR-23:13 | 39.23 | 29.58 | 2.83 |
April | 0.323384E+11 | 720.00 | 12476.23 | 01-APR-00:05 | 135453.31 | 30-APR-19:33 | 43.39 | 30.80 | 2.83 |
May | 0.334163E+11 | 744.00 | 12476.23 | 01-MAY-00:03 | 68830.60 | 31-MAY-23:20 | 33.81 | 29.55 | 2.83 |
June | 0.323384E+11 | 720.00 | 12476.23 | 01-JUN-00:03 | 94141.26 | 30-JUN-23:10 | 36.95 | 29.78 | 2.83 |
July | 0.334163E+11 | 744.00 | 12476.23 | 01-JUL-00:10 | 122363.93 | 31-JUL-23:17 | 38.13 | 28.50 | 2.83 |
August | 0.334163E+11 | 744.00 | 12476.23 | 01-AUG-00:03 | 137126.03 | 13-AUG-15:22 | 41.72 | 29.18 | 2.83 |
September | 0.323384E+11 | 720.00 | 12476.23 | 01-SEP-00:05 | 71084.29 | 30-SEP-23:15 | 32.20 | 28.10 | 2.83 |
October | 0.334163E+11 | 744.00 | 12476.23 | 01-OCT-00:03 | 93902.00 | 31-OCT-23:20 | 34.67 | 27.78 | 2.83 |
November | 0.323384E+11 | 720.00 | 12476.23 | 01-NOV-00:05 | 106581.34 | 11-NOV-16:03 | 37.51 | 27.92 | 2.83 |
December | 0.334163E+11 | 744.00 | 12476.23 | 01-DEC-00:03 | 132759.02 | 10-DEC-16:42 | 39.70 | 27.55 | 2.83 |
Annual Sum or Average | 0.393450E+12 | 8760.00 | 36.93 | 28.67 | 2.83 | ||||
Minimum of Months | 0.301825E+11 | 672.00 | 12476.23 | 45522.80 | 30.69 | 26.90 | 2.83 | ||
Maximum of Months | 0.334163E+11 | 744.00 | 12476.23 | 137126.03 | 43.39 | 30.80 | 2.83 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.434452E+11 | 561.84 | 22788.77 | 01-JAN-00:03 | 1336937.16 | 10-JAN-06:04 | 25.65 | 23.89 | 57.80 |
February | 0.457881E+11 | 572.60 | 22788.77 | 01-FEB-00:23 | 1349633.66 | 16-FEB-06:04 | 25.87 | 24.02 | 64.56 |
March | 0.559711E+11 | 689.73 | 22788.77 | 01-MAR-00:05 | 1211909.05 | 02-MAR-06:03 | 26.62 | 24.65 | 68.67 |
April | 0.557965E+11 | 680.12 | 22788.77 | 01-APR-00:05 | 1356453.54 | 10-APR-05:04 | 28.25 | 26.24 | 60.38 |
May | 0.514450E+11 | 627.07 | 22788.77 | 01-MAY-00:03 | 1512812.93 | 31-MAY-05:05 | 29.23 | 27.23 | 49.71 |
June | 0.529214E+11 | 645.07 | 22788.77 | 01-JUN-00:43 | 1455128.04 | 28-JUN-05:04 | 29.11 | 27.04 | 54.00 |
July | 0.555978E+11 | 677.69 | 22788.77 | 01-JUL-00:43 | 1424307.82 | 18-JUL-05:04 | 27.06 | 25.19 | 65.06 |
August | 0.564419E+11 | 687.98 | 22788.77 | 01-AUG-00:07 | 1405314.00 | 21-AUG-05:04 | 28.41 | 26.45 | 59.26 |
September | 0.472801E+11 | 576.31 | 22788.77 | 01-SEP-00:05 | 1399250.03 | 06-SEP-05:04 | 28.58 | 26.72 | 48.82 |
October | 0.510833E+11 | 622.67 | 22788.77 | 01-OCT-00:03 | 1373233.50 | 24-OCT-05:05 | 27.88 | 26.03 | 53.91 |
November | 0.516218E+11 | 636.96 | 22788.77 | 01-NOV-00:05 | 1398944.21 | 10-NOV-06:05 | 26.90 | 25.06 | 62.13 |
December | 0.514220E+11 | 676.44 | 22788.77 | 01-DEC-00:03 | 1374469.25 | 12-DEC-06:04 | 25.70 | 23.91 | 68.21 |
Annual Sum or Average | 0.618814E+12 | 7654.49 | 27.44 | 25.54 | 59.37 | ||||
Minimum of Months | 0.434452E+11 | 561.84 | 22788.77 | 1211909.05 | 25.65 | 23.89 | 48.82 | ||
Maximum of Months | 0.564419E+11 | 689.73 | 22788.77 | 1512812.93 | 29.23 | 27.23 | 68.67 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.145742E+11 | 177.69 | 22788.77 | 01-JAN-11:40 | 1336937.16 | 10-JAN-06:04 | 25.65 | 24.93 | 17.56 |
February | 0.150727E+11 | 183.72 | 22788.77 | 01-FEB-04:02 | 1349633.66 | 16-FEB-06:04 | 25.87 | 25.06 | 19.59 |
March | 0.199025E+11 | 242.60 | 22788.77 | 01-MAR-04:02 | 1211909.05 | 02-MAR-06:03 | 26.62 | 25.68 | 21.97 |
April | 0.354128E+11 | 431.66 | 22788.77 | 01-APR-03:02 | 1356453.54 | 10-APR-05:04 | 28.25 | 26.65 | 33.57 |
May | 0.423803E+11 | 516.58 | 22788.77 | 01-MAY-00:03 | 1512812.93 | 31-MAY-05:05 | 29.23 | 27.39 | 38.17 |
June | 0.417718E+11 | 509.17 | 22788.77 | 01-JUN-03:02 | 1455128.04 | 28-JUN-05:04 | 29.11 | 27.22 | 39.33 |
July | 0.233587E+11 | 284.73 | 22788.77 | 01-JUL-04:03 | 1424307.82 | 18-JUL-05:04 | 27.06 | 25.99 | 24.02 |
August | 0.380485E+11 | 463.78 | 22788.77 | 01-AUG-03:08 | 1405314.00 | 21-AUG-05:04 | 28.41 | 26.72 | 35.85 |
September | 0.356587E+11 | 434.65 | 22788.77 | 01-SEP-03:13 | 1399250.03 | 06-SEP-05:04 | 28.58 | 26.97 | 33.53 |
October | 0.319704E+11 | 389.69 | 22788.77 | 01-OCT-00:18 | 1373233.50 | 24-OCT-05:05 | 27.88 | 26.45 | 29.58 |
November | 0.252370E+11 | 307.62 | 22788.77 | 01-NOV-05:02 | 1398944.21 | 10-NOV-06:05 | 26.90 | 25.70 | 26.58 |
December | 0.162520E+11 | 198.13 | 22788.77 | 01-DEC-05:05 | 1374469.25 | 12-DEC-06:04 | 25.70 | 24.94 | 18.03 |
Annual Sum or Average | 0.339640E+12 | 4140.02 | 27.44 | 26.15 | 28.16 | ||||
Minimum of Months | 0.145742E+11 | 177.69 | 22788.77 | 1211909.05 | 25.65 | 24.93 | 17.56 | ||
Maximum of Months | 0.423803E+11 | 516.58 | 22788.77 | 1512812.93 | 29.23 | 27.39 | 39.33 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 79.40 | 79.40 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 79.40 | 79.40 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 79.40 | 79.40 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 79.40 | 79.40 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 79.40 | 79.40 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 79.40 | 79.40 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 79.40 | 79.40 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 79.40 | 79.40 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 79.40 | 79.40 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 79.40 | 79.40 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 79.40 | 79.40 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 79.40 | 79.40 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 79.40 | 79.40 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.40 | 79.40 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.40 | 79.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 30.69 | 30.69 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 35.10 | 35.10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 39.23 | 39.23 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 43.39 | 43.39 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 33.81 | 33.81 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 36.95 | 36.95 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 38.13 | 38.13 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 41.72 | 41.72 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 32.20 | 32.20 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 34.67 | 34.67 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 37.51 | 37.51 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 39.70 | 39.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 36.93 | 36.93 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.69 | 30.69 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.39 | 43.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.151427E+12 | 0.00 | 523.03 | 0.114990E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 236835.24 | 02-JAN-04:02 | 147563.85 | 02-JAN-04:02 | 0.00 | 0.00 | 0.00 |
February | 0.153950E+12 | 0.00 | 541.10 | 0.116973E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 224098.84 | 16-FEB-06:02 | 144755.98 | 21-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.189252E+12 | 0.00 | 649.76 | 0.145227E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 229173.69 | 13-MAR-05:02 | 148165.08 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.194712E+12 | 0.00 | 632.51 | 0.144194E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 234574.02 | 24-APR-05:03 | 149402.59 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 |
May | 0.188452E+12 | 0.00 | 577.07 | 0.129258E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 241559.61 | 16-MAY-03:02 | 150142.92 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 |
June | 0.199860E+12 | 0.00 | 602.56 | 0.137055E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 227255.55 | 14-JUN-05:02 | 147711.42 | 12-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.191014E+12 | 0.00 | 634.18 | 0.134864E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 233761.10 | 24-JUL-04:23 | 143293.62 | 24-JUL-04:23 | 0.00 | 0.00 | 0.00 |
August | 0.214379E+12 | 0.00 | 653.08 | 0.146499E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 242725.38 | 07-AUG-05:03 | 147153.61 | 14-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.167500E+12 | 0.00 | 534.46 | 0.114701E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 239502.35 | 23-SEP-05:02 | 146780.64 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.181851E+12 | 0.00 | 582.50 | 0.122402E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 236127.66 | 20-OCT-05:02 | 144120.76 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.183393E+12 | 0.00 | 600.60 | 0.127909E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 234668.66 | 13-NOV-06:02 | 141852.81 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.184583E+12 | 0.00 | 641.03 | 0.132749E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 229184.15 | 09-DEC-06:03 | 137798.72 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220037E+13 | 0.00 | 7171.87 | 0.156682E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.151427E+12 | 0.00 | 523.03 | 0.114701E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 224098.84 | 137798.72 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.214379E+12 | 0.00 | 653.08 | 0.146499E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 242725.38 | 150142.92 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.129243E+13 | 0.00 | 475.89 | 0.966067E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2327591.76 | 02-JAN-04:02 | 1382635.26 | 02-JAN-04:02 | 0.00 | 0.00 | 0.00 |
February | 0.122018E+13 | 0.00 | 444.53 | 0.917183E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2146886.69 | 16-FEB-06:02 | 1325154.50 | 21-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.145098E+13 | 0.00 | 525.53 | 0.109090E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2259834.68 | 25-MAR-05:03 | 1347157.85 | 18-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.146821E+13 | 0.00 | 518.23 | 0.104329E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2261148.54 | 14-APR-05:03 | 1352062.32 | 11-APR-05:03 | 0.00 | 0.00 | 0.00 |
May | 0.162371E+13 | 0.00 | 520.33 | 0.107694E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2339099.99 | 16-MAY-05:03 | 1337370.54 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.165051E+13 | 0.00 | 516.11 | 0.109451E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2282675.57 | 05-JUN-03:02 | 1342051.31 | 09-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.139514E+13 | 0.00 | 490.83 | 0.967836E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2248720.85 | 27-JUL-05:03 | 1318692.88 | 01-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.154845E+13 | 0.00 | 501.89 | 0.102570E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2294483.33 | 05-AUG-05:03 | 1331214.81 | 29-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.141743E+13 | 0.00 | 476.67 | 0.945083E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2329593.37 | 18-SEP-03:02 | 1349153.29 | 08-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.141216E+13 | 0.00 | 476.61 | 0.935377E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2285727.77 | 03-OCT-03:02 | 1343524.81 | 03-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.133898E+13 | 0.00 | 458.72 | 0.929749E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2291303.09 | 13-NOV-04:02 | 1333243.52 | 24-NOV-04:02 | 0.00 | 0.00 | 0.00 |
December | 0.127122E+13 | 0.00 | 466.79 | 0.921233E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2206249.23 | 09-DEC-06:03 | 1279816.83 | 09-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170894E+14 | 0.00 | 5872.14 | 0.119139E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.122018E+13 | 0.00 | 444.53 | 0.917183E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2146886.69 | 1279816.83 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.165051E+13 | 0.00 | 525.53 | 0.109451E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2339099.99 | 1382635.26 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.142059E+12 | 0.00 | 480.64 | 0.109392E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 243770.73 | 02-JAN-04:02 | 145782.28 | 02-JAN-04:02 | 0.00 | 0.00 | 0.00 |
February | 0.137586E+12 | 0.00 | 452.36 | 0.106975E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 228477.45 | 06-FEB-04:02 | 139602.49 | 06-FEB-04:02 | 0.00 | 0.00 | 0.00 |
March | 0.167629E+12 | 0.00 | 538.99 | 0.130572E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 236361.48 | 25-MAR-05:03 | 143001.77 | 17-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.171820E+12 | 0.00 | 538.06 | 0.127345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 237150.86 | 14-APR-05:03 | 146418.69 | 14-APR-03:02 | 0.00 | 0.00 | 0.00 |
May | 0.186456E+12 | 0.00 | 536.55 | 0.129820E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 258428.97 | 22-MAY-03:02 | 149271.34 | 31-MAY-03:02 | 0.00 | 0.00 | 0.00 |
June | 0.189425E+12 | 0.00 | 533.09 | 0.132099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 264150.84 | 28-JUN-03:02 | 147287.29 | 30-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.159936E+12 | 0.00 | 510.47 | 0.114549E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 247219.40 | 27-JUL-03:02 | 145914.82 | 14-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.173731E+12 | 0.00 | 513.42 | 0.119463E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 262554.50 | 03-AUG-03:02 | 147435.25 | 03-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.161667E+12 | 0.00 | 493.14 | 0.111956E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 257752.47 | 07-SEP-03:02 | 148344.07 | 28-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.156263E+12 | 0.00 | 491.08 | 0.107072E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 243990.75 | 17-OCT-03:02 | 144307.18 | 10-OCT-03:02 | 0.00 | 0.00 | 0.00 |
November | 0.148466E+12 | 0.00 | 466.99 | 0.106593E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 247731.79 | 13-NOV-04:02 | 145328.34 | 13-NOV-04:02 | 0.00 | 0.00 | 0.00 |
December | 0.139608E+12 | 0.00 | 470.43 | 0.104035E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 231962.29 | 11-DEC-04:02 | 138513.11 | 11-DEC-04:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193465E+13 | 0.00 | 6025.22 | 0.139987E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.137586E+12 | 0.00 | 452.36 | 0.104035E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 228477.45 | 138513.11 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.189425E+12 | 0.00 | 538.99 | 0.132099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 264150.84 | 149271.34 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.110132E+12 | 0.00 | 464.33 | 0.824332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 172221.01 | 09-JAN-04:02 | 94006.53 | 16-JAN-14:38 | 0.00 | 0.00 | 0.00 |
February | 0.101122E+12 | 0.00 | 415.71 | 0.755599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 177494.78 | 12-FEB-16:42 | 89531.37 | 20-FEB-12:30 | 0.00 | 0.00 | 0.00 |
March | 0.123299E+12 | 0.00 | 467.89 | 0.889803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 173744.57 | 12-MAR-16:30 | 90128.71 | 26-MAR-15:04 | 0.00 | 0.00 | 0.00 |
April | 0.130162E+12 | 0.00 | 441.16 | 0.851313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 188052.62 | 30-APR-15:29 | 87530.07 | 09-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.149536E+12 | 0.00 | 469.04 | 0.892060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 201409.18 | 22-MAY-01:13 | 85051.70 | 29-MAY-12:23 | 0.00 | 0.00 | 0.00 |
June | 0.149316E+12 | 0.00 | 459.65 | 0.887476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 204410.09 | 04-JUN-14:32 | 86596.35 | 18-JUN-13:52 | 0.00 | 0.00 | 0.00 |
July | 0.124788E+12 | 0.00 | 451.09 | 0.829933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 178474.77 | 02-JUL-13:43 | 87440.67 | 04-JUL-13:28 | 0.00 | 0.00 | 0.00 |
August | 0.151754E+12 | 0.00 | 476.16 | 0.903528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 202132.97 | 13-AUG-14:22 | 83833.99 | 27-AUG-14:10 | 0.00 | 0.00 | 0.00 |
September | 0.133022E+12 | 0.00 | 447.79 | 0.811057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 193623.49 | 10-SEP-14:52 | 80402.57 | 04-SEP-16:01 | 0.00 | 0.00 | 0.00 |
October | 0.131006E+12 | 0.00 | 456.54 | 0.811440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 190043.92 | 15-OCT-16:02 | 80478.36 | 09-OCT-11:13 | 0.00 | 0.00 | 0.00 |
November | 0.121277E+12 | 0.00 | 442.25 | 0.800651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 191016.06 | 12-NOV-17:33 | 83857.45 | 05-NOV-14:20 | 0.00 | 0.00 | 0.00 |
December | 0.111420E+12 | 0.00 | 451.64 | 0.805700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 186304.16 | 10-DEC-18:10 | 86138.38 | 03-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153683E+13 | 0.00 | 5443.24 | 0.100629E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.101122E+12 | 0.00 | 415.71 | 0.755599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 172221.01 | 80402.57 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.151754E+12 | 0.00 | 476.16 | 0.903528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 204410.09 | 94006.53 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.684218E+10 | 0.192001E+10 | 744.00 | 0.597778E+10 | 0.864396E+09 | 0.00 | 0.37 | 16-JAN-17:35 | 0.26 | 24-JAN-07:00 | 2975.10 | 30-JAN-17:00 | 2702.61 | 16-JAN-17:40 | 508.04 | 10-JAN-10:10 | 962.67 | 05-JAN-15:00 | 0.00 |
February | 0.108640E+11 | 0.303861E+10 | 672.00 | 0.997949E+10 | 0.884524E+09 | 0.00 | 0.61 | 13-FEB-15:30 | 0.48 | 24-FEB-07:00 | 4963.87 | 13-FEB-17:00 | 4546.05 | 20-FEB-17:15 | 583.57 | 14-FEB-17:00 | 1629.18 | 28-FEB-15:00 | 0.00 |
March | 0.172511E+11 | 0.479648E+10 | 744.00 | 0.161451E+11 | 0.110602E+10 | 0.00 | 0.94 | 31-MAR-23:03 | 0.70 | 03-MAR-06:00 | 8360.49 | 31-MAR-23:03 | 7763.76 | 31-MAR-24:00 | 620.20 | 31-MAR-23:03 | 2240.59 | 21-MAR-14:00 | 0.00 |
April | 0.218896E+11 | 0.604784E+10 | 720.00 | 0.205304E+11 | 0.135923E+10 | 0.00 | 1.00 | 01-APR-15:50 | 0.38 | 30-APR-23:13 | 8850.16 | 02-APR-18:03 | 8297.34 | 23-APR-18:00 | 749.88 | 10-APR-16:10 | 2726.58 | 01-APR-14:00 | 0.00 |
May | 0.757906E+10 | 0.222821E+10 | 744.00 | 0.611055E+10 | 0.146851E+10 | 0.00 | 0.54 | 31-MAY-23:10 | 0.29 | 25-MAY-21:10 | 4703.58 | 31-MAY-23:10 | 3965.26 | 31-MAY-23:50 | 778.93 | 31-MAY-23:10 | 1154.51 | 31-MAY-23:10 | 0.00 |
June | 0.123425E+11 | 0.352699E+10 | 720.00 | 0.107922E+11 | 0.155038E+10 | 0.00 | 0.74 | 30-JUN-23:03 | 0.51 | 21-JUN-06:00 | 6514.05 | 30-JUN-23:03 | 5819.25 | 30-JUN-24:00 | 817.61 | 15-JUN-10:20 | 1744.46 | 13-JUN-15:00 | 0.00 |
July | 0.173479E+11 | 0.466640E+10 | 744.00 | 0.160661E+11 | 0.128171E+10 | 0.00 | 0.93 | 31-JUL-23:05 | 0.71 | 22-JUL-07:00 | 8359.02 | 31-JUL-23:05 | 7736.56 | 31-JUL-23:53 | 724.00 | 10-JUL-15:00 | 2109.80 | 21-JUL-15:00 | 0.00 |
August | 0.226903E+11 | 0.599421E+10 | 744.00 | 0.210735E+11 | 0.161681E+10 | 0.00 | 1.00 | 01-AUG-11:00 | 0.34 | 31-AUG-23:03 | 8992.04 | 14-AUG-16:00 | 8292.24 | 13-AUG-17:30 | 872.40 | 15-AUG-13:50 | 2662.39 | 13-AUG-15:00 | 0.00 |
September | 0.712111E+10 | 0.202121E+10 | 720.00 | 0.581207E+10 | 0.130904E+10 | 0.00 | 0.55 | 30-SEP-23:03 | 0.29 | 15-SEP-21:10 | 4760.99 | 30-SEP-23:03 | 3984.94 | 30-SEP-23:57 | 826.22 | 30-SEP-23:03 | 1239.61 | 30-SEP-23:07 | 0.00 |
October | 0.123991E+11 | 0.337002E+10 | 744.00 | 0.109862E+11 | 0.141289E+10 | 0.00 | 0.74 | 31-OCT-23:05 | 0.51 | 21-OCT-07:00 | 6465.10 | 31-OCT-23:05 | 5842.71 | 31-OCT-23:57 | 700.89 | 16-OCT-10:40 | 1621.66 | 31-OCT-23:05 | 0.00 |
November | 0.167561E+11 | 0.443940E+10 | 720.00 | 0.155040E+11 | 0.125214E+10 | 0.00 | 0.81 | 20-NOV-17:00 | 0.68 | 25-NOV-07:10 | 6921.76 | 20-NOV-17:00 | 6361.51 | 19-NOV-17:10 | 716.22 | 14-NOV-16:50 | 2062.44 | 18-NOV-13:00 | 0.00 |
December | 0.221277E+11 | 0.564916E+10 | 744.00 | 0.210261E+11 | 0.110164E+10 | 0.00 | 1.00 | 08-DEC-14:50 | 0.85 | 21-DEC-07:00 | 8880.79 | 25-DEC-17:33 | 8401.70 | 25-DEC-17:17 | 707.06 | 18-DEC-17:00 | 2608.15 | 08-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.175211E+12 | 0.476986E+11 | 8760.00 | 0.160003E+12 | 0.152073E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.684218E+10 | 0.192001E+10 | 672.00 | 0.581207E+10 | 0.864396E+09 | 0.00 | 0.37 | 0.26 | 2975.10 | 2702.61 | 508.04 | 962.67 | 0.00 | ||||||
Maximum of Months | 0.226903E+11 | 0.604784E+10 | 744.00 | 0.210735E+11 | 0.161681E+10 | 0.00 | 1.00 | 0.85 | 8992.04 | 8401.70 | 872.40 | 2726.58 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.636550E+11 | 0.178833E+11 | 744.00 | 0.551221E+11 | 0.853295E+10 | 0.00 | 0.37 | 03-JAN-17:00 | 0.24 | 24-JAN-07:00 | 28237.90 | 30-JAN-17:00 | 24916.47 | 16-JAN-17:40 | 5041.39 | 10-JAN-10:10 | 9175.22 | 05-JAN-15:00 | 0.00 |
February | 0.103362E+12 | 0.288973E+11 | 672.00 | 0.945460E+11 | 0.881575E+10 | 0.00 | 0.61 | 13-FEB-15:40 | 0.48 | 24-FEB-07:00 | 47514.93 | 13-FEB-17:00 | 42944.06 | 24-FEB-17:00 | 5812.53 | 14-FEB-17:00 | 15562.06 | 28-FEB-15:00 | 0.00 |
March | 0.164799E+12 | 0.457883E+11 | 744.00 | 0.153750E+12 | 0.110484E+11 | 0.00 | 0.95 | 31-MAR-23:03 | 0.70 | 03-MAR-06:50 | 80961.64 | 31-MAR-23:03 | 75144.55 | 31-MAR-24:00 | 6281.39 | 31-MAR-23:03 | 21407.15 | 21-MAR-14:00 | 0.00 |
April | 0.209030E+12 | 0.577044E+11 | 720.00 | 0.195442E+12 | 0.135886E+11 | 0.00 | 1.00 | 01-APR-13:30 | 0.32 | 30-APR-23:13 | 84544.26 | 13-APR-14:50 | 78702.92 | 23-APR-18:00 | 7454.78 | 10-APR-16:10 | 26021.58 | 01-APR-14:00 | 0.00 |
May | 0.711143E+11 | 0.208933E+11 | 744.00 | 0.565929E+11 | 0.145213E+11 | 0.00 | 0.55 | 31-MAY-23:10 | 0.28 | 25-MAY-21:20 | 45664.10 | 31-MAY-23:10 | 38197.16 | 31-MAY-23:53 | 8065.89 | 31-MAY-23:10 | 11161.54 | 31-MAY-23:10 | 0.00 |
June | 0.117555E+12 | 0.335583E+11 | 720.00 | 0.102110E+12 | 0.154451E+11 | 0.00 | 0.74 | 30-JUN-23:03 | 0.51 | 27-JUN-06:00 | 62331.82 | 30-JUN-23:03 | 55467.51 | 30-JUN-24:00 | 8162.40 | 15-JUN-10:10 | 16665.52 | 13-JUN-15:00 | 0.00 |
July | 0.165556E+12 | 0.445043E+11 | 744.00 | 0.152756E+12 | 0.128000E+11 | 0.00 | 0.94 | 31-JUL-23:05 | 0.71 | 22-JUL-07:00 | 80490.75 | 31-JUL-23:05 | 74342.91 | 31-JUL-23:53 | 7222.16 | 10-JUL-15:00 | 20206.53 | 21-JUL-15:00 | 0.00 |
August | 0.216932E+12 | 0.572455E+11 | 744.00 | 0.200771E+12 | 0.161615E+11 | 0.00 | 1.00 | 01-AUG-10:30 | 0.31 | 31-AUG-23:03 | 85854.25 | 14-AUG-16:00 | 78142.22 | 13-AUG-16:45 | 8870.93 | 15-AUG-14:00 | 25366.30 | 13-AUG-15:00 | 0.00 |
September | 0.665036E+11 | 0.188727E+11 | 720.00 | 0.535756E+11 | 0.129280E+11 | 0.00 | 0.57 | 30-SEP-23:03 | 0.27 | 15-SEP-21:20 | 46854.53 | 30-SEP-23:03 | 38832.95 | 30-SEP-23:57 | 8466.89 | 30-SEP-23:03 | 12136.08 | 30-SEP-23:03 | 0.00 |
October | 0.117787E+12 | 0.319962E+11 | 744.00 | 0.103716E+12 | 0.140707E+11 | 0.00 | 0.74 | 31-OCT-23:05 | 0.50 | 30-OCT-21:13 | 61905.93 | 31-OCT-23:05 | 55554.15 | 31-OCT-23:57 | 6987.13 | 16-OCT-10:40 | 15498.09 | 31-OCT-23:05 | 0.00 |
November | 0.159960E+12 | 0.423524E+11 | 720.00 | 0.147455E+12 | 0.125048E+11 | 0.00 | 0.81 | 10-NOV-14:00 | 0.68 | 25-NOV-07:10 | 66038.35 | 20-NOV-17:00 | 60394.43 | 20-NOV-17:00 | 7153.14 | 14-NOV-16:50 | 19646.23 | 13-NOV-14:00 | 0.00 |
December | 0.211304E+12 | 0.539175E+11 | 744.00 | 0.200283E+12 | 0.110212E+11 | 0.00 | 1.00 | 08-DEC-14:30 | 0.85 | 21-DEC-07:00 | 83458.05 | 10-DEC-17:20 | 78965.52 | 25-DEC-17:00 | 7070.28 | 18-DEC-17:00 | 24853.23 | 08-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.166756E+13 | 0.453613E+12 | 8760.00 | 0.151612E+13 | 0.151438E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.636550E+11 | 0.178833E+11 | 672.00 | 0.535756E+11 | 0.853295E+10 | 0.00 | 0.37 | 0.24 | 28237.90 | 24916.47 | 5041.39 | 9175.22 | 0.00 | ||||||
Maximum of Months | 0.216932E+12 | 0.577044E+11 | 744.00 | 0.200771E+12 | 0.161615E+11 | 0.00 | 1.00 | 0.85 | 85854.25 | 78965.52 | 8870.93 | 26021.58 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.647071E+10 | 0.182180E+10 | 744.00 | 0.561572E+10 | 0.854987E+09 | 0.00 | 0.39 | 29-JAN-17:23 | 0.22 | 24-JAN-07:00 | 2994.40 | 16-JAN-17:40 | 2741.84 | 16-JAN-17:40 | 509.83 | 10-JAN-10:20 | 953.06 | 05-JAN-15:00 | 0.00 |
February | 0.104530E+11 | 0.292724E+10 | 672.00 | 0.957136E+10 | 0.881612E+09 | 0.00 | 0.63 | 26-FEB-16:00 | 0.47 | 24-FEB-07:00 | 4912.11 | 20-FEB-16:55 | 4549.03 | 26-FEB-16:00 | 581.98 | 14-FEB-17:00 | 1613.29 | 26-FEB-15:25 | 0.00 |
March | 0.166353E+11 | 0.462938E+10 | 744.00 | 0.155310E+11 | 0.110425E+10 | 0.00 | 0.94 | 31-MAR-23:03 | 0.68 | 04-MAR-07:00 | 8120.76 | 31-MAR-23:03 | 7505.48 | 31-MAR-24:00 | 625.98 | 31-MAR-23:03 | 2222.92 | 19-MAR-15:50 | 0.00 |
April | 0.210835E+11 | 0.582987E+10 | 720.00 | 0.197257E+11 | 0.135773E+10 | 0.00 | 1.00 | 01-APR-13:30 | 0.34 | 30-APR-23:13 | 8626.12 | 02-APR-17:55 | 8077.62 | 23-APR-17:55 | 749.45 | 10-APR-16:20 | 2648.91 | 01-APR-14:00 | 0.00 |
May | 0.732401E+10 | 0.215454E+10 | 744.00 | 0.586447E+10 | 0.145954E+10 | 0.00 | 0.55 | 31-MAY-23:10 | 0.26 | 25-MAY-21:13 | 4593.63 | 31-MAY-23:10 | 3854.29 | 31-MAY-23:53 | 801.44 | 31-MAY-23:10 | 1124.61 | 31-MAY-23:10 | 0.00 |
June | 0.119447E+11 | 0.341333E+10 | 720.00 | 0.103986E+11 | 0.154610E+10 | 0.00 | 0.73 | 30-JUN-23:03 | 0.50 | 30-JUN-21:07 | 6188.74 | 30-JUN-23:03 | 5504.43 | 30-JUN-24:00 | 818.82 | 15-JUN-10:20 | 1710.47 | 13-JUN-15:00 | 0.00 |
July | 0.167100E+11 | 0.449848E+10 | 744.00 | 0.154306E+11 | 0.127942E+10 | 0.00 | 0.92 | 31-JUL-23:05 | 0.69 | 22-JUL-07:00 | 8062.07 | 31-JUL-23:05 | 7449.43 | 31-JUL-23:53 | 722.20 | 10-JUL-15:00 | 2052.90 | 21-JUL-15:00 | 0.00 |
August | 0.218226E+11 | 0.577089E+10 | 744.00 | 0.202076E+11 | 0.161499E+10 | 0.00 | 1.00 | 01-AUG-11:00 | 0.31 | 31-AUG-23:03 | 8712.79 | 14-AUG-16:00 | 8061.66 | 13-AUG-17:10 | 869.15 | 15-AUG-13:50 | 2583.30 | 13-AUG-15:00 | 0.00 |
September | 0.682336E+10 | 0.193848E+10 | 720.00 | 0.552460E+10 | 0.129876E+10 | 0.00 | 0.56 | 30-SEP-23:03 | 0.26 | 16-SEP-07:00 | 4682.26 | 30-SEP-23:03 | 3889.04 | 30-SEP-23:57 | 832.68 | 30-SEP-23:03 | 1216.17 | 30-SEP-23:07 | 0.00 |
October | 0.119066E+11 | 0.323871E+10 | 744.00 | 0.104992E+11 | 0.140741E+10 | 0.00 | 0.73 | 31-OCT-23:05 | 0.48 | 30-OCT-21:13 | 6180.24 | 31-OCT-23:05 | 5547.57 | 31-OCT-23:57 | 701.60 | 16-OCT-10:40 | 1550.73 | 31-OCT-23:05 | 0.00 |
November | 0.160988E+11 | 0.427009E+10 | 720.00 | 0.148492E+11 | 0.124955E+10 | 0.00 | 0.82 | 19-NOV-16:25 | 0.66 | 25-NOV-07:20 | 6812.74 | 19-NOV-16:25 | 6309.36 | 19-NOV-16:55 | 714.65 | 14-NOV-16:50 | 2004.17 | 18-NOV-13:00 | 0.00 |
December | 0.212182E+11 | 0.542676E+10 | 744.00 | 0.201176E+11 | 0.110069E+10 | 0.00 | 1.00 | 08-DEC-14:50 | 0.82 | 21-DEC-07:00 | 8613.59 | 25-DEC-17:33 | 8153.25 | 24-DEC-17:10 | 705.96 | 18-DEC-17:00 | 2529.89 | 08-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.168491E+12 | 0.459196E+11 | 8760.00 | 0.153336E+12 | 0.151550E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.647071E+10 | 0.182180E+10 | 672.00 | 0.552460E+10 | 0.854987E+09 | 0.00 | 0.39 | 0.22 | 2994.40 | 2741.84 | 509.83 | 953.06 | 0.00 | ||||||
Maximum of Months | 0.218226E+11 | 0.582987E+10 | 744.00 | 0.202076E+11 | 0.161499E+10 | 0.00 | 1.00 | 0.82 | 8712.79 | 8153.25 | 869.15 | 2648.91 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.29 | 0.00 | 115.29 | 252.34 | 59.08 | 0.00 | 0.00 | 0.00 |
February | 122.99 | 0.00 | 122.99 | 282.90 | 42.89 | 0.00 | 0.00 | 0.00 |
March | 126.22 | 0.00 | 126.22 | 307.25 | 28.06 | 0.00 | 0.00 | 0.00 |
April | 137.36 | 1.95 | 135.42 | 343.65 | 11.30 | 0.00 | 0.00 | 0.00 |
May | 176.08 | 18.76 | 157.33 | 442.87 | 15.39 | 0.00 | 0.00 | 0.00 |
June | 215.09 | 43.47 | 171.62 | 525.41 | 16.77 | 0.00 | 0.00 | 0.00 |
July | 184.96 | 19.39 | 165.57 | 412.79 | 30.74 | 0.00 | 0.00 | 0.00 |
August | 152.28 | 6.49 | 145.79 | 342.91 | 24.27 | 0.00 | 0.00 | 0.00 |
September | 129.65 | 0.06 | 129.59 | 303.12 | 23.77 | 0.00 | 0.00 | 0.00 |
October | 124.92 | 0.00 | 124.92 | 270.37 | 30.32 | 0.00 | 0.00 | 0.00 |
November | 118.21 | 0.00 | 118.21 | 257.13 | 38.40 | 0.00 | 0.00 | 0.00 |
December | 112.01 | 0.00 | 112.01 | 240.95 | 64.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.01 | 7.53 | 135.48 | 331.93 | 32.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.01 | 0.00 | 112.01 | 240.95 | 11.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.09 | 43.47 | 171.62 | 525.41 | 64.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.29 | 0.00 | 115.29 | 252.34 | 59.08 | 0.00 | 0.00 | 0.00 |
February | 122.99 | 0.00 | 122.99 | 282.90 | 42.89 | 0.00 | 0.00 | 0.00 |
March | 126.22 | 0.00 | 126.22 | 307.25 | 28.06 | 0.00 | 0.00 | 0.00 |
April | 137.36 | 1.95 | 135.42 | 343.65 | 11.30 | 0.00 | 0.00 | 0.00 |
May | 176.08 | 18.76 | 157.32 | 442.86 | 15.39 | 0.00 | 0.00 | 0.00 |
June | 215.09 | 43.47 | 171.62 | 525.40 | 16.77 | 0.00 | 0.00 | 0.00 |
July | 184.96 | 19.39 | 165.57 | 412.79 | 30.74 | 0.00 | 0.00 | 0.00 |
August | 152.28 | 6.49 | 145.79 | 342.91 | 24.26 | 0.00 | 0.00 | 0.00 |
September | 129.65 | 0.06 | 129.59 | 303.11 | 23.77 | 0.00 | 0.00 | 0.00 |
October | 124.92 | 0.00 | 124.92 | 270.37 | 30.32 | 0.00 | 0.00 | 0.00 |
November | 118.20 | 0.00 | 118.20 | 257.13 | 38.40 | 0.00 | 0.00 | 0.00 |
December | 112.01 | 0.00 | 112.01 | 240.95 | 64.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.01 | 7.53 | 135.48 | 331.93 | 32.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.01 | 0.00 | 112.01 | 240.95 | 11.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.09 | 43.47 | 171.62 | 525.40 | 64.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.29 | 0.00 | 115.29 | 252.34 | 59.08 | 0.00 | 0.00 | 0.00 |
February | 122.99 | 0.00 | 122.99 | 282.90 | 42.89 | 0.00 | 0.00 | 0.00 |
March | 126.22 | 0.00 | 126.22 | 307.25 | 28.06 | 0.00 | 0.00 | 0.00 |
April | 137.36 | 1.95 | 135.42 | 343.65 | 11.30 | 0.00 | 0.00 | 0.00 |
May | 176.08 | 18.76 | 157.32 | 442.87 | 15.39 | 0.00 | 0.00 | 0.00 |
June | 215.09 | 43.47 | 171.62 | 525.40 | 16.77 | 0.00 | 0.00 | 0.00 |
July | 184.96 | 19.39 | 165.57 | 412.79 | 30.74 | 0.00 | 0.00 | 0.00 |
August | 152.28 | 6.49 | 145.79 | 342.91 | 24.26 | 0.00 | 0.00 | 0.00 |
September | 129.65 | 0.06 | 129.59 | 303.11 | 23.77 | 0.00 | 0.00 | 0.00 |
October | 124.92 | 0.00 | 124.92 | 270.37 | 30.32 | 0.00 | 0.00 | 0.00 |
November | 118.20 | 0.00 | 118.20 | 257.13 | 38.40 | 0.00 | 0.00 | 0.00 |
December | 112.01 | 0.00 | 112.01 | 240.95 | 64.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.01 | 7.53 | 135.48 | 331.93 | 32.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.01 | 0.00 | 112.01 | 240.95 | 11.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.09 | 43.47 | 171.62 | 525.40 | 64.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.29 | 0.00 | 115.29 | 252.34 | 59.08 | 0.00 | 0.00 | 0.00 |
February | 122.99 | 0.00 | 122.99 | 282.90 | 42.89 | 0.00 | 0.00 | 0.00 |
March | 126.22 | 0.00 | 126.22 | 307.25 | 28.06 | 0.00 | 0.00 | 0.00 |
April | 137.36 | 1.95 | 135.42 | 343.65 | 11.30 | 0.00 | 0.00 | 0.00 |
May | 176.08 | 18.76 | 157.32 | 442.86 | 15.39 | 0.00 | 0.00 | 0.00 |
June | 215.09 | 43.47 | 171.62 | 525.40 | 16.77 | 0.00 | 0.00 | 0.00 |
July | 184.96 | 19.39 | 165.57 | 412.79 | 30.74 | 0.00 | 0.00 | 0.00 |
August | 152.28 | 6.49 | 145.79 | 342.91 | 24.26 | 0.00 | 0.00 | 0.00 |
September | 129.65 | 0.06 | 129.59 | 303.11 | 23.77 | 0.00 | 0.00 | 0.00 |
October | 124.92 | 0.00 | 124.92 | 270.37 | 30.32 | 0.00 | 0.00 | 0.00 |
November | 118.20 | 0.00 | 118.20 | 257.13 | 38.40 | 0.00 | 0.00 | 0.00 |
December | 112.01 | 0.00 | 112.01 | 240.95 | 64.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.01 | 7.53 | 135.48 | 331.93 | 32.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.01 | 0.00 | 112.01 | 240.95 | 11.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.09 | 43.47 | 171.62 | 525.40 | 64.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.29 | 0.00 | 115.29 | 252.33 | 59.08 | 0.00 | 0.00 | 0.00 |
February | 122.98 | 0.00 | 122.98 | 282.89 | 42.88 | 0.00 | 0.00 | 0.00 |
March | 126.22 | 0.00 | 126.22 | 307.24 | 28.06 | 0.00 | 0.00 | 0.00 |
April | 137.36 | 1.95 | 135.41 | 343.64 | 11.30 | 0.00 | 0.00 | 0.00 |
May | 176.07 | 18.76 | 157.32 | 442.85 | 15.39 | 0.00 | 0.00 | 0.00 |
June | 215.08 | 43.47 | 171.61 | 525.38 | 16.77 | 0.00 | 0.00 | 0.00 |
July | 184.95 | 19.39 | 165.56 | 412.77 | 30.74 | 0.00 | 0.00 | 0.00 |
August | 152.27 | 6.49 | 145.78 | 342.89 | 24.26 | 0.00 | 0.00 | 0.00 |
September | 129.64 | 0.06 | 129.58 | 303.10 | 23.77 | 0.00 | 0.00 | 0.00 |
October | 124.92 | 0.00 | 124.92 | 270.36 | 30.32 | 0.00 | 0.00 | 0.00 |
November | 118.20 | 0.00 | 118.20 | 257.12 | 38.40 | 0.00 | 0.00 | 0.00 |
December | 112.00 | 0.00 | 112.00 | 240.94 | 64.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 143.00 | 7.53 | 135.47 | 331.91 | 32.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.00 | 0.00 | 112.00 | 240.94 | 11.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.08 | 43.47 | 171.61 | 525.38 | 64.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 247.02 | 83.25 | 163.77 | 502.03 | 61.55 | 0.00 | 0.00 | 0.00 |
February | 280.12 | 102.71 | 177.42 | 584.03 | 42.26 | 0.00 | 0.00 | 0.00 |
March | 305.39 | 119.59 | 185.80 | 652.70 | 25.21 | 0.00 | 0.00 | 0.00 |
April | 308.64 | 117.91 | 190.73 | 678.26 | 8.09 | 0.00 | 0.00 | 0.00 |
May | 265.30 | 80.31 | 185.00 | 607.10 | 15.06 | 0.00 | 0.00 | 0.00 |
June | 282.57 | 93.06 | 189.51 | 638.61 | 14.68 | 0.00 | 0.00 | 0.00 |
July | 241.35 | 54.07 | 187.28 | 514.03 | 27.83 | 0.00 | 0.00 | 0.00 |
August | 265.61 | 78.08 | 187.54 | 555.90 | 20.58 | 0.00 | 0.00 | 0.00 |
September | 249.44 | 67.97 | 181.47 | 535.10 | 25.33 | 0.00 | 0.00 | 0.00 |
October | 233.79 | 59.81 | 173.97 | 479.19 | 30.47 | 0.00 | 0.00 | 0.00 |
November | 226.26 | 62.53 | 163.73 | 466.52 | 37.91 | 0.00 | 0.00 | 0.00 |
December | 231.54 | 74.30 | 157.24 | 469.96 | 62.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 261.21 | 82.61 | 178.60 | 556.48 | 30.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.26 | 54.07 | 157.24 | 466.52 | 8.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 308.64 | 119.59 | 190.73 | 678.26 | 62.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 247.02 | 83.25 | 163.77 | 502.03 | 61.55 | 0.00 | 0.00 | 0.00 |
February | 280.12 | 102.71 | 177.42 | 584.03 | 42.26 | 0.00 | 0.00 | 0.00 |
March | 305.39 | 119.59 | 185.80 | 652.70 | 25.21 | 0.00 | 0.00 | 0.00 |
April | 308.64 | 117.91 | 190.73 | 678.26 | 8.09 | 0.00 | 0.00 | 0.00 |
May | 265.30 | 80.31 | 185.00 | 607.10 | 15.06 | 0.00 | 0.00 | 0.00 |
June | 282.57 | 93.06 | 189.51 | 638.61 | 14.68 | 0.00 | 0.00 | 0.00 |
July | 241.35 | 54.07 | 187.28 | 514.03 | 27.83 | 0.00 | 0.00 | 0.00 |
August | 265.61 | 78.08 | 187.54 | 555.90 | 20.58 | 0.00 | 0.00 | 0.00 |
September | 249.44 | 67.97 | 181.47 | 535.10 | 25.33 | 0.00 | 0.00 | 0.00 |
October | 233.79 | 59.81 | 173.97 | 479.19 | 30.47 | 0.00 | 0.00 | 0.00 |
November | 226.26 | 62.53 | 163.73 | 466.52 | 37.91 | 0.00 | 0.00 | 0.00 |
December | 231.54 | 74.30 | 157.24 | 469.96 | 62.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 261.21 | 82.61 | 178.60 | 556.48 | 30.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.26 | 54.07 | 157.24 | 466.52 | 8.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 308.64 | 119.59 | 190.73 | 678.26 | 62.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 247.02 | 83.25 | 163.77 | 502.02 | 61.55 | 0.00 | 0.00 | 0.00 |
February | 280.12 | 102.70 | 177.41 | 584.02 | 42.25 | 0.00 | 0.00 | 0.00 |
March | 305.38 | 119.59 | 185.80 | 652.69 | 25.21 | 0.00 | 0.00 | 0.00 |
April | 308.63 | 117.91 | 190.72 | 678.25 | 8.08 | 0.00 | 0.00 | 0.00 |
May | 265.30 | 80.31 | 184.99 | 607.09 | 15.06 | 0.00 | 0.00 | 0.00 |
June | 282.57 | 93.06 | 189.50 | 638.60 | 14.68 | 0.00 | 0.00 | 0.00 |
July | 241.35 | 54.07 | 187.28 | 514.02 | 27.83 | 0.00 | 0.00 | 0.00 |
August | 265.61 | 78.08 | 187.53 | 555.89 | 20.58 | 0.00 | 0.00 | 0.00 |
September | 249.44 | 67.97 | 181.47 | 535.09 | 25.33 | 0.00 | 0.00 | 0.00 |
October | 233.78 | 59.81 | 173.97 | 479.18 | 30.47 | 0.00 | 0.00 | 0.00 |
November | 226.25 | 62.52 | 163.73 | 466.51 | 37.91 | 0.00 | 0.00 | 0.00 |
December | 231.53 | 74.30 | 157.23 | 469.95 | 62.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 261.20 | 82.61 | 178.60 | 556.47 | 30.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.25 | 54.07 | 157.23 | 466.51 | 8.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 308.63 | 119.59 | 190.72 | 678.25 | 62.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 305.25 | 127.35 | 177.90 | 624.55 | 62.78 | 0.00 | 0.00 | 0.00 |
February | 259.21 | 84.51 | 174.70 | 570.63 | 45.58 | 0.00 | 0.00 | 0.00 |
March | 176.89 | 23.76 | 153.14 | 429.55 | 28.34 | 0.00 | 0.00 | 0.00 |
April | 131.88 | 0.06 | 131.82 | 333.89 | 9.93 | 0.00 | 0.00 | 0.00 |
May | 131.97 | 0.00 | 131.97 | 346.44 | 13.83 | 0.00 | 0.00 | 0.00 |
June | 131.50 | 0.00 | 131.50 | 343.32 | 14.21 | 0.00 | 0.00 | 0.00 |
July | 135.46 | 0.00 | 135.46 | 305.93 | 28.41 | 0.00 | 0.00 | 0.00 |
August | 131.87 | 0.20 | 131.67 | 298.36 | 22.06 | 0.00 | 0.00 | 0.00 |
September | 145.99 | 4.77 | 141.23 | 339.46 | 24.15 | 0.00 | 0.00 | 0.00 |
October | 191.00 | 30.45 | 160.55 | 408.43 | 33.17 | 0.00 | 0.00 | 0.00 |
November | 248.36 | 75.77 | 172.59 | 516.21 | 42.86 | 0.00 | 0.00 | 0.00 |
December | 305.10 | 129.81 | 175.29 | 612.99 | 68.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.94 | 39.57 | 151.37 | 426.79 | 32.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.50 | 0.00 | 131.50 | 298.36 | 9.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 305.25 | 129.81 | 177.90 | 624.55 | 68.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 305.25 | 127.35 | 177.90 | 624.55 | 62.78 | 0.00 | 0.00 | 0.00 |
February | 259.20 | 84.51 | 174.69 | 570.63 | 45.58 | 0.00 | 0.00 | 0.00 |
March | 176.89 | 23.76 | 153.14 | 429.55 | 28.34 | 0.00 | 0.00 | 0.00 |
April | 131.88 | 0.06 | 131.82 | 333.89 | 9.93 | 0.00 | 0.00 | 0.00 |
May | 131.97 | 0.00 | 131.97 | 346.44 | 13.83 | 0.00 | 0.00 | 0.00 |
June | 131.50 | 0.00 | 131.50 | 343.32 | 14.21 | 0.00 | 0.00 | 0.00 |
July | 135.46 | 0.00 | 135.46 | 305.93 | 28.41 | 0.00 | 0.00 | 0.00 |
August | 131.87 | 0.20 | 131.67 | 298.36 | 22.06 | 0.00 | 0.00 | 0.00 |
September | 145.99 | 4.77 | 141.22 | 339.45 | 24.15 | 0.00 | 0.00 | 0.00 |
October | 191.00 | 30.45 | 160.55 | 408.43 | 33.17 | 0.00 | 0.00 | 0.00 |
November | 248.36 | 75.77 | 172.59 | 516.20 | 42.86 | 0.00 | 0.00 | 0.00 |
December | 305.09 | 129.80 | 175.29 | 612.99 | 68.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.94 | 39.57 | 151.37 | 426.79 | 32.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.50 | 0.00 | 131.50 | 298.36 | 9.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 305.25 | 129.80 | 177.90 | 624.55 | 68.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 305.25 | 127.35 | 177.90 | 624.55 | 62.78 | 0.00 | 0.00 | 0.00 |
February | 259.21 | 84.51 | 174.70 | 570.63 | 45.58 | 0.00 | 0.00 | 0.00 |
March | 176.89 | 23.76 | 153.14 | 429.55 | 28.34 | 0.00 | 0.00 | 0.00 |
April | 131.88 | 0.06 | 131.82 | 333.89 | 9.93 | 0.00 | 0.00 | 0.00 |
May | 131.97 | 0.00 | 131.97 | 346.44 | 13.83 | 0.00 | 0.00 | 0.00 |
June | 131.50 | 0.00 | 131.50 | 343.32 | 14.21 | 0.00 | 0.00 | 0.00 |
July | 135.46 | 0.00 | 135.46 | 305.93 | 28.41 | 0.00 | 0.00 | 0.00 |
August | 131.87 | 0.20 | 131.67 | 298.36 | 22.06 | 0.00 | 0.00 | 0.00 |
September | 145.99 | 4.77 | 141.23 | 339.46 | 24.15 | 0.00 | 0.00 | 0.00 |
October | 191.00 | 30.45 | 160.55 | 408.43 | 33.17 | 0.00 | 0.00 | 0.00 |
November | 248.36 | 75.77 | 172.59 | 516.21 | 42.86 | 0.00 | 0.00 | 0.00 |
December | 305.10 | 129.81 | 175.29 | 612.99 | 68.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.94 | 39.57 | 151.37 | 426.79 | 32.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.50 | 0.00 | 131.50 | 298.36 | 9.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 305.25 | 129.81 | 177.90 | 624.55 | 68.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 305.25 | 127.35 | 177.90 | 624.55 | 62.78 | 0.00 | 0.00 | 0.00 |
February | 259.20 | 84.51 | 174.69 | 570.63 | 45.58 | 0.00 | 0.00 | 0.00 |
March | 176.89 | 23.76 | 153.14 | 429.55 | 28.34 | 0.00 | 0.00 | 0.00 |
April | 131.88 | 0.06 | 131.82 | 333.89 | 9.93 | 0.00 | 0.00 | 0.00 |
May | 131.97 | 0.00 | 131.97 | 346.44 | 13.83 | 0.00 | 0.00 | 0.00 |
June | 131.50 | 0.00 | 131.50 | 343.32 | 14.21 | 0.00 | 0.00 | 0.00 |
July | 135.46 | 0.00 | 135.46 | 305.93 | 28.41 | 0.00 | 0.00 | 0.00 |
August | 131.87 | 0.20 | 131.67 | 298.36 | 22.06 | 0.00 | 0.00 | 0.00 |
September | 145.99 | 4.77 | 141.22 | 339.45 | 24.15 | 0.00 | 0.00 | 0.00 |
October | 191.00 | 30.45 | 160.55 | 408.43 | 33.17 | 0.00 | 0.00 | 0.00 |
November | 248.36 | 75.77 | 172.59 | 516.20 | 42.86 | 0.00 | 0.00 | 0.00 |
December | 305.09 | 129.80 | 175.29 | 612.99 | 68.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.94 | 39.57 | 151.37 | 426.79 | 32.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.50 | 0.00 | 131.50 | 298.36 | 9.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 305.25 | 129.80 | 177.90 | 624.55 | 68.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 305.24 | 127.35 | 177.89 | 624.53 | 62.78 | 0.00 | 0.00 | 0.00 |
February | 259.19 | 84.51 | 174.69 | 570.61 | 45.57 | 0.00 | 0.00 | 0.00 |
March | 176.89 | 23.76 | 153.13 | 429.53 | 28.34 | 0.00 | 0.00 | 0.00 |
April | 131.88 | 0.06 | 131.82 | 333.87 | 9.93 | 0.00 | 0.00 | 0.00 |
May | 131.97 | 0.00 | 131.97 | 346.43 | 13.83 | 0.00 | 0.00 | 0.00 |
June | 131.49 | 0.00 | 131.49 | 343.31 | 14.21 | 0.00 | 0.00 | 0.00 |
July | 135.46 | 0.00 | 135.46 | 305.92 | 28.41 | 0.00 | 0.00 | 0.00 |
August | 131.87 | 0.20 | 131.66 | 298.34 | 22.06 | 0.00 | 0.00 | 0.00 |
September | 145.99 | 4.77 | 141.22 | 339.44 | 24.15 | 0.00 | 0.00 | 0.00 |
October | 190.99 | 30.45 | 160.54 | 408.42 | 33.17 | 0.00 | 0.00 | 0.00 |
November | 248.35 | 75.77 | 172.58 | 516.18 | 42.86 | 0.00 | 0.00 | 0.00 |
December | 305.08 | 129.80 | 175.28 | 612.97 | 68.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 190.93 | 39.57 | 151.37 | 426.77 | 32.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.49 | 0.00 | 131.49 | 298.34 | 9.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 305.24 | 129.80 | 177.89 | 624.53 | 68.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 250.29 | 88.01 | 162.28 | 504.72 | 83.53 | 0.00 | 0.00 | 0.00 |
February | 274.89 | 97.28 | 177.61 | 564.68 | 69.67 | 0.00 | 0.00 | 0.00 |
March | 308.13 | 121.70 | 186.42 | 642.57 | 57.77 | 0.00 | 0.00 | 0.00 |
April | 309.65 | 118.60 | 191.05 | 647.23 | 37.07 | 0.00 | 0.00 | 0.00 |
May | 263.48 | 78.06 | 185.42 | 584.43 | 25.36 | 0.00 | 0.00 | 0.00 |
June | 285.51 | 98.41 | 187.10 | 620.33 | 30.47 | 0.00 | 0.00 | 0.00 |
July | 243.41 | 57.40 | 186.01 | 495.61 | 54.00 | 0.00 | 0.00 | 0.00 |
August | 264.64 | 78.37 | 186.27 | 525.58 | 52.91 | 0.00 | 0.00 | 0.00 |
September | 247.87 | 68.75 | 179.12 | 517.60 | 40.37 | 0.00 | 0.00 | 0.00 |
October | 232.80 | 60.01 | 172.79 | 460.40 | 54.58 | 0.00 | 0.00 | 0.00 |
November | 227.03 | 61.92 | 165.11 | 448.82 | 68.17 | 0.00 | 0.00 | 0.00 |
December | 232.35 | 76.00 | 156.34 | 456.57 | 104.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 261.50 | 83.56 | 177.94 | 538.62 | 56.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 227.03 | 57.40 | 156.34 | 448.82 | 25.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 309.65 | 121.70 | 191.05 | 647.23 | 104.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 250.29 | 88.01 | 162.28 | 504.72 | 83.53 | 0.00 | 0.00 | 0.00 |
February | 274.89 | 97.28 | 177.61 | 564.68 | 69.67 | 0.00 | 0.00 | 0.00 |
March | 308.13 | 121.70 | 186.42 | 642.57 | 57.77 | 0.00 | 0.00 | 0.00 |
April | 309.65 | 118.60 | 191.05 | 647.23 | 37.07 | 0.00 | 0.00 | 0.00 |
May | 263.48 | 78.06 | 185.42 | 584.43 | 25.36 | 0.00 | 0.00 | 0.00 |
June | 285.51 | 98.41 | 187.10 | 620.33 | 30.47 | 0.00 | 0.00 | 0.00 |
July | 243.41 | 57.40 | 186.01 | 495.61 | 54.00 | 0.00 | 0.00 | 0.00 |
August | 264.64 | 78.37 | 186.27 | 525.58 | 52.91 | 0.00 | 0.00 | 0.00 |
September | 247.87 | 68.75 | 179.12 | 517.60 | 40.37 | 0.00 | 0.00 | 0.00 |
October | 232.80 | 60.01 | 172.79 | 460.40 | 54.58 | 0.00 | 0.00 | 0.00 |
November | 227.03 | 61.92 | 165.11 | 448.82 | 68.17 | 0.00 | 0.00 | 0.00 |
December | 232.35 | 76.00 | 156.34 | 456.57 | 104.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 261.50 | 83.56 | 177.94 | 538.62 | 56.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 227.03 | 57.40 | 156.34 | 448.82 | 25.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 309.65 | 121.70 | 191.05 | 647.23 | 104.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 250.28 | 88.01 | 162.27 | 504.71 | 83.53 | 0.00 | 0.00 | 0.00 |
February | 274.88 | 97.27 | 177.61 | 564.67 | 69.67 | 0.00 | 0.00 | 0.00 |
March | 308.12 | 121.70 | 186.42 | 642.56 | 57.77 | 0.00 | 0.00 | 0.00 |
April | 309.65 | 118.60 | 191.05 | 647.22 | 37.07 | 0.00 | 0.00 | 0.00 |
May | 263.47 | 78.06 | 185.42 | 584.42 | 25.36 | 0.00 | 0.00 | 0.00 |
June | 285.51 | 98.41 | 187.10 | 620.32 | 30.47 | 0.00 | 0.00 | 0.00 |
July | 243.41 | 57.40 | 186.01 | 495.60 | 54.00 | 0.00 | 0.00 | 0.00 |
August | 264.63 | 78.37 | 186.26 | 525.57 | 52.91 | 0.00 | 0.00 | 0.00 |
September | 247.87 | 68.75 | 179.12 | 517.59 | 40.37 | 0.00 | 0.00 | 0.00 |
October | 232.80 | 60.01 | 172.79 | 460.40 | 54.58 | 0.00 | 0.00 | 0.00 |
November | 227.03 | 61.92 | 165.11 | 448.81 | 68.17 | 0.00 | 0.00 | 0.00 |
December | 232.34 | 76.00 | 156.34 | 456.56 | 104.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 261.49 | 83.56 | 177.93 | 538.61 | 56.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 227.03 | 57.40 | 156.34 | 448.81 | 25.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 309.65 | 121.70 | 191.05 | 647.22 | 104.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 576.47 | 0.00 | 576.47 | 1274.38 | 283.88 | 0.00 | 0.00 | 0.00 |
February | 614.94 | 0.00 | 614.94 | 1427.66 | 217.80 | 0.00 | 0.00 | 0.00 |
March | 631.11 | 0.00 | 631.11 | 1555.55 | 137.90 | 0.00 | 0.00 | 0.00 |
April | 686.82 | 9.73 | 677.08 | 1749.65 | 52.84 | 0.00 | 0.00 | 0.00 |
May | 880.42 | 93.79 | 786.63 | 2215.67 | 79.39 | 0.00 | 0.00 | 0.00 |
June | 1075.46 | 217.34 | 858.12 | 2624.66 | 91.62 | 0.00 | 0.00 | 0.00 |
July | 924.80 | 96.94 | 827.86 | 2063.66 | 161.58 | 0.00 | 0.00 | 0.00 |
August | 761.41 | 32.47 | 728.94 | 1728.56 | 119.76 | 0.00 | 0.00 | 0.00 |
September | 648.26 | 0.31 | 647.95 | 1523.29 | 115.63 | 0.00 | 0.00 | 0.00 |
October | 624.62 | 0.00 | 624.62 | 1359.27 | 151.50 | 0.00 | 0.00 | 0.00 |
November | 591.03 | 0.00 | 591.03 | 1298.13 | 191.54 | 0.00 | 0.00 | 0.00 |
December | 560.03 | 0.00 | 560.03 | 1223.89 | 314.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.04 | 37.65 | 677.40 | 1670.95 | 159.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 560.03 | 0.00 | 560.03 | 1223.89 | 52.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1075.46 | 217.34 | 858.12 | 2624.66 | 314.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 741.06 | 249.76 | 491.30 | 1498.63 | 188.18 | 0.00 | 0.00 | 0.00 |
February | 840.36 | 308.12 | 532.24 | 1740.57 | 144.18 | 0.00 | 0.00 | 0.00 |
March | 916.15 | 358.76 | 557.39 | 1944.46 | 91.52 | 0.00 | 0.00 | 0.00 |
April | 925.91 | 353.74 | 572.17 | 2020.74 | 36.04 | 0.00 | 0.00 | 0.00 |
May | 795.90 | 240.92 | 554.98 | 1810.04 | 51.81 | 0.00 | 0.00 | 0.00 |
June | 847.70 | 279.19 | 568.51 | 1900.98 | 56.23 | 0.00 | 0.00 | 0.00 |
July | 724.05 | 162.21 | 561.85 | 1526.92 | 103.85 | 0.00 | 0.00 | 0.00 |
August | 796.84 | 234.24 | 562.60 | 1653.94 | 81.64 | 0.00 | 0.00 | 0.00 |
September | 748.33 | 203.92 | 544.40 | 1594.92 | 83.87 | 0.00 | 0.00 | 0.00 |
October | 701.35 | 179.43 | 521.92 | 1423.82 | 107.36 | 0.00 | 0.00 | 0.00 |
November | 678.76 | 187.57 | 491.19 | 1385.24 | 134.49 | 0.00 | 0.00 | 0.00 |
December | 694.61 | 222.91 | 471.70 | 1396.60 | 211.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 783.62 | 247.82 | 535.80 | 1656.66 | 107.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 678.76 | 162.21 | 471.70 | 1385.24 | 36.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 925.91 | 358.76 | 572.17 | 2020.74 | 211.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1526.29 | 636.78 | 889.50 | 3104.04 | 317.60 | 0.00 | 0.00 | 0.00 |
February | 1296.05 | 422.56 | 873.49 | 2843.46 | 238.14 | 0.00 | 0.00 | 0.00 |
March | 884.48 | 118.79 | 765.69 | 2158.07 | 141.01 | 0.00 | 0.00 | 0.00 |
April | 659.42 | 0.30 | 659.12 | 1707.93 | 45.72 | 0.00 | 0.00 | 0.00 |
May | 659.87 | 0.00 | 659.87 | 1749.45 | 68.60 | 0.00 | 0.00 | 0.00 |
June | 657.50 | 0.00 | 657.50 | 1736.94 | 71.78 | 0.00 | 0.00 | 0.00 |
July | 677.32 | 0.00 | 677.32 | 1542.32 | 144.26 | 0.00 | 0.00 | 0.00 |
August | 659.38 | 1.02 | 658.36 | 1511.62 | 106.26 | 0.00 | 0.00 | 0.00 |
September | 729.98 | 23.84 | 706.13 | 1702.51 | 118.59 | 0.00 | 0.00 | 0.00 |
October | 955.02 | 152.27 | 802.75 | 2037.66 | 171.33 | 0.00 | 0.00 | 0.00 |
November | 1241.84 | 378.87 | 862.97 | 2573.21 | 224.48 | 0.00 | 0.00 | 0.00 |
December | 1525.50 | 649.04 | 876.46 | 3053.15 | 355.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 954.73 | 197.85 | 756.87 | 2139.95 | 166.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 657.50 | 0.00 | 657.50 | 1511.62 | 45.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1526.29 | 649.04 | 889.50 | 3104.04 | 355.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 750.85 | 264.02 | 486.83 | 1528.02 | 224.89 | 0.00 | 0.00 | 0.00 |
February | 824.65 | 291.83 | 532.83 | 1715.94 | 180.52 | 0.00 | 0.00 | 0.00 |
March | 924.37 | 365.11 | 559.26 | 1959.32 | 134.49 | 0.00 | 0.00 | 0.00 |
April | 928.94 | 355.80 | 573.14 | 1993.73 | 64.68 | 0.00 | 0.00 | 0.00 |
May | 790.43 | 234.17 | 556.26 | 1772.18 | 61.57 | 0.00 | 0.00 | 0.00 |
June | 856.53 | 295.23 | 561.30 | 1891.06 | 68.95 | 0.00 | 0.00 | 0.00 |
July | 730.23 | 172.21 | 558.03 | 1521.67 | 124.19 | 0.00 | 0.00 | 0.00 |
August | 793.91 | 235.11 | 558.80 | 1622.89 | 102.63 | 0.00 | 0.00 | 0.00 |
September | 743.61 | 206.25 | 537.37 | 1567.31 | 100.34 | 0.00 | 0.00 | 0.00 |
October | 698.40 | 180.03 | 518.37 | 1404.72 | 130.71 | 0.00 | 0.00 | 0.00 |
November | 681.08 | 185.75 | 495.33 | 1381.22 | 160.01 | 0.00 | 0.00 | 0.00 |
December | 697.03 | 228.01 | 469.02 | 1410.49 | 251.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 784.49 | 250.69 | 533.80 | 1646.15 | 133.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 681.08 | 172.21 | 469.02 | 1381.22 | 61.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 928.94 | 365.11 | 573.14 | 1993.73 | 251.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 576.47 | 0.00 | 576.47 | 1250.49 | 293.01 | 0.00 | 0.00 | 0.00 |
February | 614.94 | 0.00 | 614.94 | 1399.54 | 228.25 | 0.00 | 0.00 | 0.00 |
March | 631.11 | 0.00 | 631.11 | 1525.67 | 150.55 | 0.00 | 0.00 | 0.00 |
April | 686.82 | 9.73 | 677.08 | 1706.29 | 62.59 | 0.00 | 0.00 | 0.00 |
May | 880.42 | 93.79 | 786.63 | 2173.78 | 90.37 | 0.00 | 0.00 | 0.00 |
June | 1075.46 | 217.34 | 858.12 | 2586.43 | 106.77 | 0.00 | 0.00 | 0.00 |
July | 924.80 | 96.94 | 827.86 | 2029.46 | 175.74 | 0.00 | 0.00 | 0.00 |
August | 761.41 | 32.47 | 728.94 | 1699.58 | 131.51 | 0.00 | 0.00 | 0.00 |
September | 648.26 | 0.31 | 647.95 | 1490.97 | 129.52 | 0.00 | 0.00 | 0.00 |
October | 624.62 | 0.00 | 624.62 | 1331.51 | 165.65 | 0.00 | 0.00 | 0.00 |
November | 591.03 | 0.00 | 591.03 | 1271.39 | 202.18 | 0.00 | 0.00 | 0.00 |
December | 560.03 | 0.00 | 560.03 | 1201.23 | 324.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.04 | 37.65 | 677.40 | 1639.46 | 171.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 560.03 | 0.00 | 560.03 | 1201.23 | 62.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1075.46 | 217.34 | 858.12 | 2586.43 | 324.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 741.06 | 249.76 | 491.30 | 1481.15 | 194.68 | 0.00 | 0.00 | 0.00 |
February | 840.36 | 308.12 | 532.24 | 1720.45 | 150.78 | 0.00 | 0.00 | 0.00 |
March | 916.15 | 358.76 | 557.39 | 1921.59 | 99.13 | 0.00 | 0.00 | 0.00 |
April | 925.91 | 353.74 | 572.17 | 1990.67 | 41.83 | 0.00 | 0.00 | 0.00 |
May | 795.90 | 240.92 | 554.98 | 1781.61 | 58.69 | 0.00 | 0.00 | 0.00 |
June | 847.70 | 279.19 | 568.51 | 1874.29 | 65.60 | 0.00 | 0.00 | 0.00 |
July | 724.05 | 162.21 | 561.85 | 1504.37 | 113.11 | 0.00 | 0.00 | 0.00 |
August | 796.84 | 234.24 | 562.60 | 1634.05 | 89.50 | 0.00 | 0.00 | 0.00 |
September | 748.33 | 203.92 | 544.40 | 1573.48 | 93.21 | 0.00 | 0.00 | 0.00 |
October | 701.35 | 179.43 | 521.92 | 1404.54 | 116.57 | 0.00 | 0.00 | 0.00 |
November | 678.76 | 187.57 | 491.19 | 1366.88 | 141.57 | 0.00 | 0.00 | 0.00 |
December | 694.61 | 222.91 | 471.70 | 1380.17 | 217.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 783.62 | 247.82 | 535.80 | 1634.70 | 115.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 678.76 | 162.21 | 471.70 | 1366.88 | 41.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 925.91 | 358.76 | 572.17 | 1990.67 | 217.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1526.29 | 636.78 | 889.50 | 3082.69 | 327.24 | 0.00 | 0.00 | 0.00 |
February | 1296.05 | 422.56 | 873.49 | 2816.47 | 248.48 | 0.00 | 0.00 | 0.00 |
March | 884.48 | 118.79 | 765.69 | 2126.59 | 152.86 | 0.00 | 0.00 | 0.00 |
April | 659.42 | 0.30 | 659.12 | 1663.26 | 53.41 | 0.00 | 0.00 | 0.00 |
May | 659.87 | 0.00 | 659.87 | 1705.63 | 77.84 | 0.00 | 0.00 | 0.00 |
June | 657.50 | 0.00 | 657.50 | 1696.59 | 83.77 | 0.00 | 0.00 | 0.00 |
July | 677.32 | 0.00 | 677.32 | 1507.97 | 157.71 | 0.00 | 0.00 | 0.00 |
August | 659.38 | 1.02 | 658.36 | 1482.00 | 116.87 | 0.00 | 0.00 | 0.00 |
September | 729.98 | 23.84 | 706.13 | 1669.57 | 132.37 | 0.00 | 0.00 | 0.00 |
October | 955.02 | 152.27 | 802.75 | 2009.20 | 185.63 | 0.00 | 0.00 | 0.00 |
November | 1241.84 | 378.87 | 862.97 | 2547.60 | 235.56 | 0.00 | 0.00 | 0.00 |
December | 1525.50 | 649.04 | 876.46 | 3032.43 | 366.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 954.73 | 197.85 | 756.87 | 2108.26 | 178.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 657.50 | 0.00 | 657.50 | 1482.00 | 53.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1526.29 | 649.04 | 889.50 | 3082.69 | 366.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 750.85 | 264.02 | 486.83 | 1513.23 | 229.28 | 0.00 | 0.00 | 0.00 |
February | 824.65 | 291.83 | 532.83 | 1698.33 | 185.87 | 0.00 | 0.00 | 0.00 |
March | 924.37 | 365.11 | 559.26 | 1940.08 | 140.75 | 0.00 | 0.00 | 0.00 |
April | 928.94 | 355.80 | 573.14 | 1970.38 | 70.08 | 0.00 | 0.00 | 0.00 |
May | 790.43 | 234.17 | 556.26 | 1748.25 | 66.78 | 0.00 | 0.00 | 0.00 |
June | 856.53 | 295.23 | 561.30 | 1867.56 | 75.83 | 0.00 | 0.00 | 0.00 |
July | 730.23 | 172.21 | 558.03 | 1501.34 | 130.18 | 0.00 | 0.00 | 0.00 |
August | 793.91 | 235.11 | 558.80 | 1604.04 | 107.87 | 0.00 | 0.00 | 0.00 |
September | 743.61 | 206.25 | 537.37 | 1547.49 | 106.91 | 0.00 | 0.00 | 0.00 |
October | 698.40 | 180.03 | 518.37 | 1388.17 | 137.31 | 0.00 | 0.00 | 0.00 |
November | 681.08 | 185.75 | 495.33 | 1365.27 | 164.62 | 0.00 | 0.00 | 0.00 |
December | 697.03 | 228.01 | 469.02 | 1396.59 | 256.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 784.49 | 250.69 | 533.80 | 1627.17 | 139.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 681.08 | 172.21 | 469.02 | 1365.27 | 66.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 928.94 | 365.11 | 573.14 | 1970.38 | 256.61 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308804E+09 | 0.00 | 0.308804E+09 | 0.675877E+09 | 0.158247E+09 |
February | 0.297531E+09 | 0.00 | 0.297531E+09 | 0.684397E+09 | 0.103749E+09 |
March | 0.338075E+09 | 0.00 | 0.338075E+09 | 0.822948E+09 | 75147954.03 |
April | 0.356047E+09 | 5045816.39 | 0.351001E+09 | 0.890745E+09 | 29281240.74 |
May | 0.471622E+09 | 50241679.84 | 0.421380E+09 | 0.118618E+10 | 41232605.99 |
June | 0.557519E+09 | 0.112670E+09 | 0.444849E+09 | 0.136186E+10 | 43479809.87 |
July | 0.495394E+09 | 51925898.26 | 0.443468E+09 | 0.110562E+10 | 82332906.95 |
August | 0.407871E+09 | 17391842.65 | 0.390479E+09 | 0.918455E+09 | 64991927.58 |
September | 0.336056E+09 | 160920.72 | 0.335895E+09 | 0.785679E+09 | 61620679.79 |
October | 0.334596E+09 | 0.00 | 0.334596E+09 | 0.724157E+09 | 81220748.64 |
November | 0.306389E+09 | 0.00 | 0.306389E+09 | 0.666490E+09 | 99540296.13 |
December | 0.299999E+09 | 0.00 | 0.299999E+09 | 0.645360E+09 | 0.171949E+09 |
Annual Sum or Average | 0.450990E+10 | 0.237436E+09 | 0.427247E+10 | 0.104678E+11 | 0.101279E+10 |
Minimum of Months | 0.297531E+09 | 0.00 | 0.297531E+09 | 0.645360E+09 | 29281240.74 |
Maximum of Months | 0.557519E+09 | 0.112670E+09 | 0.444849E+09 | 0.136186E+10 | 0.171949E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308799E+09 | 0.00 | 0.308799E+09 | 0.675871E+09 | 0.158245E+09 |
February | 0.297527E+09 | 0.00 | 0.297527E+09 | 0.684391E+09 | 0.103748E+09 |
March | 0.338070E+09 | 0.00 | 0.338070E+09 | 0.822942E+09 | 75146228.39 |
April | 0.356042E+09 | 5045705.46 | 0.350996E+09 | 0.890738E+09 | 29280187.64 |
May | 0.471614E+09 | 50240575.34 | 0.421374E+09 | 0.118617E+10 | 41231834.22 |
June | 0.557509E+09 | 0.112667E+09 | 0.444842E+09 | 0.136184E+10 | 43479033.42 |
July | 0.495385E+09 | 51924756.73 | 0.443460E+09 | 0.110560E+10 | 82331362.52 |
August | 0.407865E+09 | 17391460.31 | 0.390473E+09 | 0.918444E+09 | 64990715.47 |
September | 0.336051E+09 | 160917.19 | 0.335890E+09 | 0.785671E+09 | 61619666.75 |
October | 0.334591E+09 | 0.00 | 0.334591E+09 | 0.724149E+09 | 81219689.93 |
November | 0.306384E+09 | 0.00 | 0.306384E+09 | 0.666483E+09 | 99539089.94 |
December | 0.299994E+09 | 0.00 | 0.299994E+09 | 0.645353E+09 | 0.171948E+09 |
Annual Sum or Average | 0.450983E+10 | 0.237431E+09 | 0.427240E+10 | 0.104677E+11 | 0.101278E+10 |
Minimum of Months | 0.297527E+09 | 0.00 | 0.297527E+09 | 0.645353E+09 | 29280187.64 |
Maximum of Months | 0.557509E+09 | 0.112667E+09 | 0.444842E+09 | 0.136184E+10 | 0.171948E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308801E+09 | 0.00 | 0.308801E+09 | 0.675873E+09 | 0.158246E+09 |
February | 0.297528E+09 | 0.00 | 0.297528E+09 | 0.684393E+09 | 0.103748E+09 |
March | 0.338072E+09 | 0.00 | 0.338072E+09 | 0.822944E+09 | 75146803.60 |
April | 0.356044E+09 | 5045742.44 | 0.350998E+09 | 0.890740E+09 | 29280538.68 |
May | 0.471617E+09 | 50240943.51 | 0.421376E+09 | 0.118617E+10 | 41232091.47 |
June | 0.557512E+09 | 0.112668E+09 | 0.444844E+09 | 0.136185E+10 | 43479292.21 |
July | 0.495388E+09 | 51925137.24 | 0.443463E+09 | 0.110561E+10 | 82331763.80 |
August | 0.407867E+09 | 17391587.75 | 0.390475E+09 | 0.918448E+09 | 64991120.62 |
September | 0.336052E+09 | 160918.37 | 0.335892E+09 | 0.785674E+09 | 61620004.43 |
October | 0.334593E+09 | 0.00 | 0.334593E+09 | 0.724152E+09 | 81220042.84 |
November | 0.306386E+09 | 0.00 | 0.306386E+09 | 0.666485E+09 | 99539525.77 |
December | 0.299996E+09 | 0.00 | 0.299996E+09 | 0.645356E+09 | 0.171948E+09 |
Annual Sum or Average | 0.450986E+10 | 0.237432E+09 | 0.427242E+10 | 0.104677E+11 | 0.101278E+10 |
Minimum of Months | 0.297528E+09 | 0.00 | 0.297528E+09 | 0.645356E+09 | 29280538.68 |
Maximum of Months | 0.557512E+09 | 0.112668E+09 | 0.444844E+09 | 0.136185E+10 | 0.171948E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308799E+09 | 0.00 | 0.308799E+09 | 0.675871E+09 | 0.158245E+09 |
February | 0.297527E+09 | 0.00 | 0.297527E+09 | 0.684391E+09 | 0.103748E+09 |
March | 0.338070E+09 | 0.00 | 0.338070E+09 | 0.822942E+09 | 75146228.39 |
April | 0.356042E+09 | 5045705.46 | 0.350996E+09 | 0.890738E+09 | 29280187.64 |
May | 0.471614E+09 | 50240575.34 | 0.421374E+09 | 0.118617E+10 | 41231834.22 |
June | 0.557509E+09 | 0.112667E+09 | 0.444842E+09 | 0.136184E+10 | 43479033.42 |
July | 0.495385E+09 | 51924756.73 | 0.443460E+09 | 0.110560E+10 | 82331362.52 |
August | 0.407865E+09 | 17391460.31 | 0.390473E+09 | 0.918444E+09 | 64990715.47 |
September | 0.336051E+09 | 160917.19 | 0.335890E+09 | 0.785671E+09 | 61619666.75 |
October | 0.334591E+09 | 0.00 | 0.334591E+09 | 0.724149E+09 | 81219689.93 |
November | 0.306384E+09 | 0.00 | 0.306384E+09 | 0.666483E+09 | 99539089.94 |
December | 0.299994E+09 | 0.00 | 0.299994E+09 | 0.645353E+09 | 0.171948E+09 |
Annual Sum or Average | 0.450983E+10 | 0.237431E+09 | 0.427240E+10 | 0.104677E+11 | 0.101278E+10 |
Minimum of Months | 0.297527E+09 | 0.00 | 0.297527E+09 | 0.645353E+09 | 29280187.64 |
Maximum of Months | 0.557509E+09 | 0.112667E+09 | 0.444842E+09 | 0.136184E+10 | 0.171948E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308788E+09 | 0.00 | 0.308788E+09 | 0.675845E+09 | 0.158239E+09 |
February | 0.297515E+09 | 0.00 | 0.297515E+09 | 0.684365E+09 | 0.103744E+09 |
March | 0.338058E+09 | 0.00 | 0.338058E+09 | 0.822910E+09 | 75143487.26 |
April | 0.356028E+09 | 5045520.58 | 0.350983E+09 | 0.890703E+09 | 29279183.03 |
May | 0.471597E+09 | 50238734.50 | 0.421358E+09 | 0.118612E+10 | 41230301.02 |
June | 0.557488E+09 | 0.112663E+09 | 0.444825E+09 | 0.136179E+10 | 43477410.41 |
July | 0.495367E+09 | 51922854.18 | 0.443444E+09 | 0.110556E+10 | 82328244.83 |
August | 0.407849E+09 | 17390823.08 | 0.390458E+09 | 0.918409E+09 | 64988298.51 |
September | 0.336038E+09 | 160911.29 | 0.335877E+09 | 0.785641E+09 | 61617352.04 |
October | 0.334579E+09 | 0.00 | 0.334579E+09 | 0.724121E+09 | 81216592.87 |
November | 0.306373E+09 | 0.00 | 0.306373E+09 | 0.666457E+09 | 99535295.98 |
December | 0.299983E+09 | 0.00 | 0.299983E+09 | 0.645328E+09 | 0.171941E+09 |
Annual Sum or Average | 0.450966E+10 | 0.237422E+09 | 0.427224E+10 | 0.104673E+11 | 0.101274E+10 |
Minimum of Months | 0.297515E+09 | 0.00 | 0.297515E+09 | 0.645328E+09 | 29279183.03 |
Maximum of Months | 0.557488E+09 | 0.112663E+09 | 0.444825E+09 | 0.136179E+10 | 0.171941E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.661625E+09 | 0.222987E+09 | 0.438638E+09 | 0.134464E+10 | 0.164855E+09 |
February | 0.677672E+09 | 0.248468E+09 | 0.429204E+09 | 0.141289E+10 | 0.102224E+09 |
March | 0.817947E+09 | 0.320304E+09 | 0.497643E+09 | 0.174820E+10 | 67534547.20 |
April | 0.799994E+09 | 0.305631E+09 | 0.494363E+09 | 0.175806E+10 | 20956480.98 |
May | 0.710588E+09 | 0.215094E+09 | 0.495494E+09 | 0.162607E+10 | 40333420.42 |
June | 0.732423E+09 | 0.241221E+09 | 0.491201E+09 | 0.165529E+10 | 38051907.71 |
July | 0.646443E+09 | 0.144819E+09 | 0.501624E+09 | 0.137677E+10 | 74540614.42 |
August | 0.711422E+09 | 0.209128E+09 | 0.502294E+09 | 0.148894E+10 | 55114858.62 |
September | 0.646561E+09 | 0.176191E+09 | 0.470371E+09 | 0.138699E+10 | 65650960.54 |
October | 0.626171E+09 | 0.160197E+09 | 0.465974E+09 | 0.128345E+10 | 81611200.69 |
November | 0.586459E+09 | 0.162066E+09 | 0.424393E+09 | 0.120921E+10 | 98258886.58 |
December | 0.620151E+09 | 0.199012E+09 | 0.421139E+09 | 0.125873E+10 | 0.167688E+09 |
Annual Sum or Average | 0.823746E+10 | 0.260512E+10 | 0.563234E+10 | 0.175492E+11 | 0.976820E+09 |
Minimum of Months | 0.586459E+09 | 0.144819E+09 | 0.421139E+09 | 0.120921E+10 | 20956480.98 |
Maximum of Months | 0.817947E+09 | 0.320304E+09 | 0.502294E+09 | 0.175806E+10 | 0.167688E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.661625E+09 | 0.222987E+09 | 0.438638E+09 | 0.134464E+10 | 0.164855E+09 |
February | 0.677672E+09 | 0.248468E+09 | 0.429204E+09 | 0.141289E+10 | 0.102224E+09 |
March | 0.817947E+09 | 0.320304E+09 | 0.497643E+09 | 0.174820E+10 | 67534547.20 |
April | 0.799994E+09 | 0.305631E+09 | 0.494363E+09 | 0.175806E+10 | 20956480.98 |
May | 0.710588E+09 | 0.215094E+09 | 0.495494E+09 | 0.162607E+10 | 40333420.42 |
June | 0.732423E+09 | 0.241221E+09 | 0.491201E+09 | 0.165529E+10 | 38051907.71 |
July | 0.646443E+09 | 0.144819E+09 | 0.501624E+09 | 0.137677E+10 | 74540614.42 |
August | 0.711422E+09 | 0.209128E+09 | 0.502294E+09 | 0.148894E+10 | 55114858.62 |
September | 0.646561E+09 | 0.176191E+09 | 0.470371E+09 | 0.138699E+10 | 65650960.54 |
October | 0.626171E+09 | 0.160197E+09 | 0.465974E+09 | 0.128345E+10 | 81611200.69 |
November | 0.586459E+09 | 0.162066E+09 | 0.424393E+09 | 0.120921E+10 | 98258886.58 |
December | 0.620151E+09 | 0.199012E+09 | 0.421139E+09 | 0.125873E+10 | 0.167688E+09 |
Annual Sum or Average | 0.823746E+10 | 0.260512E+10 | 0.563234E+10 | 0.175492E+11 | 0.976820E+09 |
Minimum of Months | 0.586459E+09 | 0.144819E+09 | 0.421139E+09 | 0.120921E+10 | 20956480.98 |
Maximum of Months | 0.817947E+09 | 0.320304E+09 | 0.502294E+09 | 0.175806E+10 | 0.167688E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.661613E+09 | 0.222983E+09 | 0.438630E+09 | 0.134462E+10 | 0.164852E+09 |
February | 0.677660E+09 | 0.248463E+09 | 0.429196E+09 | 0.141286E+10 | 0.102222E+09 |
March | 0.817932E+09 | 0.320298E+09 | 0.497634E+09 | 0.174817E+10 | 67533313.20 |
April | 0.799979E+09 | 0.305626E+09 | 0.494354E+09 | 0.175803E+10 | 20956098.06 |
May | 0.710575E+09 | 0.215090E+09 | 0.495485E+09 | 0.162604E+10 | 40332683.44 |
June | 0.732409E+09 | 0.241217E+09 | 0.491192E+09 | 0.165526E+10 | 38051212.42 |
July | 0.646431E+09 | 0.144816E+09 | 0.501615E+09 | 0.137675E+10 | 74539252.40 |
August | 0.711409E+09 | 0.209124E+09 | 0.502285E+09 | 0.148891E+10 | 55113851.55 |
September | 0.646549E+09 | 0.176187E+09 | 0.470362E+09 | 0.138696E+10 | 65649760.96 |
October | 0.626159E+09 | 0.160194E+09 | 0.465965E+09 | 0.128343E+10 | 81609709.48 |
November | 0.586448E+09 | 0.162063E+09 | 0.424385E+09 | 0.120919E+10 | 98257091.18 |
December | 0.620140E+09 | 0.199009E+09 | 0.421131E+09 | 0.125871E+10 | 0.167685E+09 |
Annual Sum or Average | 0.823731E+10 | 0.260507E+10 | 0.563224E+10 | 0.175489E+11 | 0.976803E+09 |
Minimum of Months | 0.586448E+09 | 0.144816E+09 | 0.421131E+09 | 0.120919E+10 | 20956098.06 |
Maximum of Months | 0.817932E+09 | 0.320298E+09 | 0.502285E+09 | 0.175803E+10 | 0.167685E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.817587E+09 | 0.341105E+09 | 0.476482E+09 | 0.167280E+10 | 0.168151E+09 |
February | 0.627070E+09 | 0.204447E+09 | 0.422623E+09 | 0.138047E+10 | 0.110259E+09 |
March | 0.473792E+09 | 63629959.28 | 0.410162E+09 | 0.115050E+10 | 75901980.44 |
April | 0.341841E+09 | 153453.04 | 0.341688E+09 | 0.865435E+09 | 25745159.29 |
May | 0.353476E+09 | 0.00 | 0.353476E+09 | 0.927910E+09 | 37032185.10 |
June | 0.340843E+09 | 0.00 | 0.340843E+09 | 0.889884E+09 | 36845225.42 |
July | 0.362823E+09 | 0.00 | 0.362823E+09 | 0.819414E+09 | 76102821.10 |
August | 0.353211E+09 | 545888.88 | 0.352665E+09 | 0.799119E+09 | 59080859.59 |
September | 0.378415E+09 | 12359203.88 | 0.366056E+09 | 0.879868E+09 | 62605317.32 |
October | 0.511579E+09 | 81566659.29 | 0.430012E+09 | 0.109395E+10 | 88839570.61 |
November | 0.643761E+09 | 0.196402E+09 | 0.447359E+09 | 0.133801E+10 | 0.111090E+09 |
December | 0.817168E+09 | 0.347670E+09 | 0.469498E+09 | 0.164184E+10 | 0.184708E+09 |
Annual Sum or Average | 0.602157E+10 | 0.124788E+10 | 0.477369E+10 | 0.134592E+11 | 0.103636E+10 |
Minimum of Months | 0.340843E+09 | 0.00 | 0.340843E+09 | 0.799119E+09 | 25745159.29 |
Maximum of Months | 0.817587E+09 | 0.347670E+09 | 0.476482E+09 | 0.167280E+10 | 0.184708E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.817582E+09 | 0.341103E+09 | 0.476479E+09 | 0.167279E+10 | 0.168151E+09 |
February | 0.627066E+09 | 0.204446E+09 | 0.422620E+09 | 0.138046E+10 | 0.110258E+09 |
March | 0.473789E+09 | 63629493.00 | 0.410160E+09 | 0.115049E+10 | 75901454.16 |
April | 0.341840E+09 | 153451.91 | 0.341686E+09 | 0.865433E+09 | 25744855.15 |
May | 0.353475E+09 | 0.00 | 0.353475E+09 | 0.927907E+09 | 37031958.57 |
June | 0.340841E+09 | 0.00 | 0.340841E+09 | 0.889882E+09 | 36845019.66 |
July | 0.362821E+09 | 0.00 | 0.362821E+09 | 0.819411E+09 | 76102439.22 |
August | 0.353209E+09 | 545884.88 | 0.352663E+09 | 0.799117E+09 | 59080492.95 |
September | 0.378413E+09 | 12359113.31 | 0.366054E+09 | 0.879864E+09 | 62604980.52 |
October | 0.511576E+09 | 81566061.57 | 0.430010E+09 | 0.109394E+10 | 88839201.13 |
November | 0.643757E+09 | 0.196400E+09 | 0.447356E+09 | 0.133800E+10 | 0.111089E+09 |
December | 0.817163E+09 | 0.347668E+09 | 0.469495E+09 | 0.164183E+10 | 0.184707E+09 |
Annual Sum or Average | 0.602153E+10 | 0.124787E+10 | 0.477366E+10 | 0.134591E+11 | 0.103636E+10 |
Minimum of Months | 0.340841E+09 | 0.00 | 0.340841E+09 | 0.799117E+09 | 25744855.15 |
Maximum of Months | 0.817582E+09 | 0.347668E+09 | 0.476479E+09 | 0.167279E+10 | 0.184707E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.817587E+09 | 0.341105E+09 | 0.476482E+09 | 0.167280E+10 | 0.168151E+09 |
February | 0.627070E+09 | 0.204447E+09 | 0.422623E+09 | 0.138047E+10 | 0.110259E+09 |
March | 0.473792E+09 | 63629959.28 | 0.410162E+09 | 0.115050E+10 | 75901980.44 |
April | 0.341841E+09 | 153453.04 | 0.341688E+09 | 0.865435E+09 | 25745159.29 |
May | 0.353476E+09 | 0.00 | 0.353476E+09 | 0.927910E+09 | 37032185.10 |
June | 0.340843E+09 | 0.00 | 0.340843E+09 | 0.889884E+09 | 36845225.42 |
July | 0.362823E+09 | 0.00 | 0.362823E+09 | 0.819414E+09 | 76102821.10 |
August | 0.353211E+09 | 545888.88 | 0.352665E+09 | 0.799119E+09 | 59080859.59 |
September | 0.378415E+09 | 12359203.88 | 0.366056E+09 | 0.879868E+09 | 62605317.32 |
October | 0.511579E+09 | 81566659.29 | 0.430012E+09 | 0.109395E+10 | 88839570.61 |
November | 0.643761E+09 | 0.196402E+09 | 0.447359E+09 | 0.133801E+10 | 0.111090E+09 |
December | 0.817168E+09 | 0.347670E+09 | 0.469498E+09 | 0.164184E+10 | 0.184708E+09 |
Annual Sum or Average | 0.602157E+10 | 0.124788E+10 | 0.477369E+10 | 0.134592E+11 | 0.103636E+10 |
Minimum of Months | 0.340843E+09 | 0.00 | 0.340843E+09 | 0.799119E+09 | 25745159.29 |
Maximum of Months | 0.817587E+09 | 0.347670E+09 | 0.476482E+09 | 0.167280E+10 | 0.184708E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.817582E+09 | 0.341103E+09 | 0.476479E+09 | 0.167279E+10 | 0.168151E+09 |
February | 0.627066E+09 | 0.204446E+09 | 0.422620E+09 | 0.138046E+10 | 0.110258E+09 |
March | 0.473789E+09 | 63629493.00 | 0.410160E+09 | 0.115049E+10 | 75901454.16 |
April | 0.341840E+09 | 153451.91 | 0.341686E+09 | 0.865433E+09 | 25744855.15 |
May | 0.353475E+09 | 0.00 | 0.353475E+09 | 0.927907E+09 | 37031958.57 |
June | 0.340841E+09 | 0.00 | 0.340841E+09 | 0.889882E+09 | 36845019.66 |
July | 0.362821E+09 | 0.00 | 0.362821E+09 | 0.819411E+09 | 76102439.22 |
August | 0.353209E+09 | 545884.88 | 0.352663E+09 | 0.799117E+09 | 59080492.95 |
September | 0.378413E+09 | 12359113.31 | 0.366054E+09 | 0.879864E+09 | 62604980.52 |
October | 0.511576E+09 | 81566061.57 | 0.430010E+09 | 0.109394E+10 | 88839201.13 |
November | 0.643757E+09 | 0.196400E+09 | 0.447356E+09 | 0.133800E+10 | 0.111089E+09 |
December | 0.817163E+09 | 0.347668E+09 | 0.469495E+09 | 0.164183E+10 | 0.184707E+09 |
Annual Sum or Average | 0.602153E+10 | 0.124787E+10 | 0.477366E+10 | 0.134591E+11 | 0.103636E+10 |
Minimum of Months | 0.340841E+09 | 0.00 | 0.340841E+09 | 0.799117E+09 | 25744855.15 |
Maximum of Months | 0.817582E+09 | 0.347668E+09 | 0.476479E+09 | 0.167279E+10 | 0.184707E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.817552E+09 | 0.341090E+09 | 0.476461E+09 | 0.167273E+10 | 0.168144E+09 |
February | 0.627042E+09 | 0.204438E+09 | 0.422604E+09 | 0.138041E+10 | 0.110254E+09 |
March | 0.473771E+09 | 63627161.58 | 0.410144E+09 | 0.115045E+10 | 75898658.13 |
April | 0.341827E+09 | 153446.29 | 0.341673E+09 | 0.865399E+09 | 25743969.58 |
May | 0.353461E+09 | 0.00 | 0.353461E+09 | 0.927871E+09 | 37030579.28 |
June | 0.340828E+09 | 0.00 | 0.340828E+09 | 0.889847E+09 | 36843637.52 |
July | 0.362807E+09 | 0.00 | 0.362807E+09 | 0.819379E+09 | 76099562.89 |
August | 0.353196E+09 | 545864.88 | 0.352650E+09 | 0.799086E+09 | 59078295.06 |
September | 0.378399E+09 | 12358660.47 | 0.366040E+09 | 0.879831E+09 | 62602625.65 |
October | 0.511557E+09 | 81563072.95 | 0.429994E+09 | 0.109390E+10 | 88835805.25 |
November | 0.643733E+09 | 0.196393E+09 | 0.447340E+09 | 0.133795E+10 | 0.111085E+09 |
December | 0.817133E+09 | 0.347655E+09 | 0.469478E+09 | 0.164177E+10 | 0.184700E+09 |
Annual Sum or Average | 0.602131E+10 | 0.124782E+10 | 0.477348E+10 | 0.134586E+11 | 0.103632E+10 |
Minimum of Months | 0.340828E+09 | 0.00 | 0.340828E+09 | 0.799086E+09 | 25743969.58 |
Maximum of Months | 0.817552E+09 | 0.347655E+09 | 0.476461E+09 | 0.167273E+10 | 0.184700E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.670368E+09 | 0.235723E+09 | 0.434645E+09 | 0.135185E+10 | 0.223738E+09 |
February | 0.665006E+09 | 0.235330E+09 | 0.429676E+09 | 0.136608E+10 | 0.168548E+09 |
March | 0.825288E+09 | 0.325973E+09 | 0.499315E+09 | 0.172106E+10 | 0.154723E+09 |
April | 0.802616E+09 | 0.307414E+09 | 0.495202E+09 | 0.167761E+10 | 96079875.61 |
May | 0.705702E+09 | 0.209067E+09 | 0.496635E+09 | 0.156533E+10 | 67937474.52 |
June | 0.740048E+09 | 0.255077E+09 | 0.484971E+09 | 0.160790E+10 | 78983773.86 |
July | 0.651960E+09 | 0.153747E+09 | 0.498213E+09 | 0.132744E+10 | 0.144633E+09 |
August | 0.708811E+09 | 0.209910E+09 | 0.498901E+09 | 0.140771E+10 | 0.141705E+09 |
September | 0.642489E+09 | 0.178198E+09 | 0.464291E+09 | 0.134162E+10 | 0.104647E+09 |
October | 0.623538E+09 | 0.160735E+09 | 0.462803E+09 | 0.123315E+10 | 0.146184E+09 |
November | 0.588460E+09 | 0.160491E+09 | 0.427969E+09 | 0.116334E+10 | 0.176696E+09 |
December | 0.622318E+09 | 0.203571E+09 | 0.418746E+09 | 0.122287E+10 | 0.280130E+09 |
Annual Sum or Average | 0.824660E+10 | 0.263524E+10 | 0.561137E+10 | 0.169860E+11 | 0.178401E+10 |
Minimum of Months | 0.588460E+09 | 0.153747E+09 | 0.418746E+09 | 0.116334E+10 | 67937474.52 |
Maximum of Months | 0.825288E+09 | 0.325973E+09 | 0.499315E+09 | 0.172106E+10 | 0.280130E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.670368E+09 | 0.235723E+09 | 0.434645E+09 | 0.135185E+10 | 0.223738E+09 |
February | 0.665006E+09 | 0.235330E+09 | 0.429676E+09 | 0.136608E+10 | 0.168548E+09 |
March | 0.825288E+09 | 0.325973E+09 | 0.499315E+09 | 0.172106E+10 | 0.154723E+09 |
April | 0.802616E+09 | 0.307414E+09 | 0.495202E+09 | 0.167761E+10 | 96079875.61 |
May | 0.705702E+09 | 0.209067E+09 | 0.496635E+09 | 0.156533E+10 | 67937474.52 |
June | 0.740048E+09 | 0.255077E+09 | 0.484971E+09 | 0.160790E+10 | 78983773.86 |
July | 0.651960E+09 | 0.153747E+09 | 0.498213E+09 | 0.132744E+10 | 0.144633E+09 |
August | 0.708811E+09 | 0.209910E+09 | 0.498901E+09 | 0.140771E+10 | 0.141705E+09 |
September | 0.642489E+09 | 0.178198E+09 | 0.464291E+09 | 0.134162E+10 | 0.104647E+09 |
October | 0.623538E+09 | 0.160735E+09 | 0.462803E+09 | 0.123315E+10 | 0.146184E+09 |
November | 0.588460E+09 | 0.160491E+09 | 0.427969E+09 | 0.116334E+10 | 0.176696E+09 |
December | 0.622318E+09 | 0.203571E+09 | 0.418746E+09 | 0.122287E+10 | 0.280130E+09 |
Annual Sum or Average | 0.824660E+10 | 0.263524E+10 | 0.561137E+10 | 0.169860E+11 | 0.178401E+10 |
Minimum of Months | 0.588460E+09 | 0.153747E+09 | 0.418746E+09 | 0.116334E+10 | 67937474.52 |
Maximum of Months | 0.825288E+09 | 0.325973E+09 | 0.499315E+09 | 0.172106E+10 | 0.280130E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.670355E+09 | 0.235719E+09 | 0.434637E+09 | 0.135183E+10 | 0.223734E+09 |
February | 0.664994E+09 | 0.235326E+09 | 0.429668E+09 | 0.136605E+10 | 0.168545E+09 |
March | 0.825273E+09 | 0.325967E+09 | 0.499306E+09 | 0.172103E+10 | 0.154720E+09 |
April | 0.802601E+09 | 0.307408E+09 | 0.495193E+09 | 0.167758E+10 | 96078120.02 |
May | 0.705689E+09 | 0.209063E+09 | 0.496626E+09 | 0.156530E+10 | 67936233.15 |
June | 0.740035E+09 | 0.255073E+09 | 0.484962E+09 | 0.160787E+10 | 78982330.65 |
July | 0.651948E+09 | 0.153744E+09 | 0.498204E+09 | 0.132741E+10 | 0.144630E+09 |
August | 0.708798E+09 | 0.209906E+09 | 0.498892E+09 | 0.140769E+10 | 0.141702E+09 |
September | 0.642478E+09 | 0.178195E+09 | 0.464283E+09 | 0.134160E+10 | 0.104646E+09 |
October | 0.623526E+09 | 0.160732E+09 | 0.462795E+09 | 0.123312E+10 | 0.146182E+09 |
November | 0.588449E+09 | 0.160488E+09 | 0.427961E+09 | 0.116332E+10 | 0.176692E+09 |
December | 0.622306E+09 | 0.203568E+09 | 0.418739E+09 | 0.122285E+10 | 0.280125E+09 |
Annual Sum or Average | 0.824645E+10 | 0.263519E+10 | 0.561126E+10 | 0.169856E+11 | 0.178397E+10 |
Minimum of Months | 0.588449E+09 | 0.153744E+09 | 0.418739E+09 | 0.116332E+10 | 67936233.15 |
Maximum of Months | 0.825273E+09 | 0.325967E+09 | 0.499306E+09 | 0.172103E+10 | 0.280125E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.154402E+10 | 0.00 | 0.154402E+10 | 0.341330E+10 | 0.760334E+09 |
February | 0.148765E+10 | 0.00 | 0.148765E+10 | 0.345380E+10 | 0.526890E+09 |
March | 0.169037E+10 | 0.00 | 0.169037E+10 | 0.416638E+10 | 0.369359E+09 |
April | 0.178023E+10 | 25229242.72 | 0.175500E+10 | 0.453508E+10 | 0.136958E+09 |
May | 0.235811E+10 | 0.251210E+09 | 0.210690E+10 | 0.593445E+10 | 0.212646E+09 |
June | 0.278760E+10 | 0.563351E+09 | 0.222425E+10 | 0.680311E+10 | 0.237466E+09 |
July | 0.247697E+10 | 0.259631E+09 | 0.221734E+10 | 0.552730E+10 | 0.432764E+09 |
August | 0.203936E+10 | 86959767.40 | 0.195240E+10 | 0.462976E+10 | 0.320774E+09 |
September | 0.168028E+10 | 804608.75 | 0.167948E+10 | 0.394837E+10 | 0.299717E+09 |
October | 0.167298E+10 | 0.00 | 0.167298E+10 | 0.364067E+10 | 0.405765E+09 |
November | 0.153195E+10 | 0.00 | 0.153195E+10 | 0.336475E+10 | 0.496464E+09 |
December | 0.149999E+10 | 0.00 | 0.149999E+10 | 0.327806E+10 | 0.843423E+09 |
Annual Sum or Average | 0.225495E+11 | 0.118719E+10 | 0.213623E+11 | 0.526950E+11 | 0.504256E+10 |
Minimum of Months | 0.148765E+10 | 0.00 | 0.148765E+10 | 0.327806E+10 | 0.136958E+09 |
Maximum of Months | 0.278760E+10 | 0.563351E+09 | 0.222425E+10 | 0.680311E+10 | 0.843423E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198486E+10 | 0.668953E+09 | 0.131590E+10 | 0.401394E+10 | 0.504010E+09 |
February | 0.203300E+10 | 0.745396E+09 | 0.128760E+10 | 0.421078E+10 | 0.348798E+09 |
March | 0.245382E+10 | 0.960903E+09 | 0.149291E+10 | 0.520804E+10 | 0.245131E+09 |
April | 0.239996E+10 | 0.916885E+09 | 0.148307E+10 | 0.523777E+10 | 93410098.24 |
May | 0.213174E+10 | 0.645275E+09 | 0.148647E+10 | 0.484802E+10 | 0.138776E+09 |
June | 0.219725E+10 | 0.723656E+09 | 0.147359E+10 | 0.492735E+10 | 0.145746E+09 |
July | 0.193931E+10 | 0.434453E+09 | 0.150486E+10 | 0.408971E+10 | 0.278142E+09 |
August | 0.213425E+10 | 0.627378E+09 | 0.150687E+10 | 0.442992E+10 | 0.218660E+09 |
September | 0.193966E+10 | 0.528567E+09 | 0.141110E+10 | 0.413403E+10 | 0.217402E+09 |
October | 0.187849E+10 | 0.480585E+09 | 0.139791E+10 | 0.381355E+10 | 0.287555E+09 |
November | 0.175936E+10 | 0.486192E+09 | 0.127317E+10 | 0.359055E+10 | 0.348599E+09 |
December | 0.186043E+10 | 0.597031E+09 | 0.126340E+10 | 0.374064E+10 | 0.565179E+09 |
Annual Sum or Average | 0.247121E+11 | 0.781527E+10 | 0.168968E+11 | 0.522443E+11 | 0.339141E+10 |
Minimum of Months | 0.175936E+10 | 0.434453E+09 | 0.126340E+10 | 0.359055E+10 | 93410098.24 |
Maximum of Months | 0.245382E+10 | 0.960903E+09 | 0.150687E+10 | 0.523777E+10 | 0.565179E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.408800E+10 | 0.170556E+10 | 0.238244E+10 | 0.831386E+10 | 0.850673E+09 |
February | 0.313540E+10 | 0.102226E+10 | 0.211314E+10 | 0.687890E+10 | 0.576120E+09 |
March | 0.236899E+10 | 0.318156E+09 | 0.205083E+10 | 0.578017E+10 | 0.377679E+09 |
April | 0.170922E+10 | 767281.32 | 0.170845E+10 | 0.442696E+10 | 0.118499E+09 |
May | 0.176740E+10 | 0.00 | 0.176740E+10 | 0.468573E+10 | 0.183728E+09 |
June | 0.170423E+10 | 0.00 | 0.170423E+10 | 0.450214E+10 | 0.186046E+09 |
July | 0.181413E+10 | 0.00 | 0.181413E+10 | 0.413095E+10 | 0.386376E+09 |
August | 0.176607E+10 | 2729501.79 | 0.176334E+10 | 0.404873E+10 | 0.284600E+09 |
September | 0.189210E+10 | 61797318.92 | 0.183030E+10 | 0.441291E+10 | 0.307380E+09 |
October | 0.255793E+10 | 0.407842E+09 | 0.215009E+10 | 0.545768E+10 | 0.458883E+09 |
November | 0.321886E+10 | 0.982030E+09 | 0.223683E+10 | 0.666977E+10 | 0.581856E+09 |
December | 0.408591E+10 | 0.173839E+10 | 0.234752E+10 | 0.817757E+10 | 0.953206E+09 |
Annual Sum or Average | 0.301082E+11 | 0.623953E+10 | 0.238687E+11 | 0.674854E+11 | 0.526505E+10 |
Minimum of Months | 0.170423E+10 | 0.00 | 0.170423E+10 | 0.404873E+10 | 0.118499E+09 |
Maximum of Months | 0.408800E+10 | 0.173839E+10 | 0.238244E+10 | 0.831386E+10 | 0.953206E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201108E+10 | 0.707162E+09 | 0.130392E+10 | 0.409265E+10 | 0.602347E+09 |
February | 0.199500E+10 | 0.705983E+09 | 0.128901E+10 | 0.415120E+10 | 0.436702E+09 |
March | 0.247584E+10 | 0.977909E+09 | 0.149793E+10 | 0.524784E+10 | 0.360226E+09 |
April | 0.240782E+10 | 0.922232E+09 | 0.148559E+10 | 0.516776E+10 | 0.167657E+09 |
May | 0.211708E+10 | 0.627195E+09 | 0.148989E+10 | 0.474660E+10 | 0.164917E+09 |
June | 0.222012E+10 | 0.765224E+09 | 0.145490E+10 | 0.490162E+10 | 0.178717E+09 |
July | 0.195586E+10 | 0.461237E+09 | 0.149462E+10 | 0.407564E+10 | 0.332623E+09 |
August | 0.212641E+10 | 0.629723E+09 | 0.149669E+10 | 0.434676E+10 | 0.274897E+09 |
September | 0.192745E+10 | 0.534589E+09 | 0.139286E+10 | 0.406245E+10 | 0.260087E+09 |
October | 0.187059E+10 | 0.482199E+09 | 0.138840E+10 | 0.376239E+10 | 0.350101E+09 |
November | 0.176536E+10 | 0.481468E+09 | 0.128389E+10 | 0.358013E+10 | 0.414741E+09 |
December | 0.186693E+10 | 0.610708E+09 | 0.125623E+10 | 0.377787E+10 | 0.674798E+09 |
Annual Sum or Average | 0.247396E+11 | 0.790563E+10 | 0.168339E+11 | 0.519129E+11 | 0.421781E+10 |
Minimum of Months | 0.176536E+10 | 0.461237E+09 | 0.125623E+10 | 0.358013E+10 | 0.164917E+09 |
Maximum of Months | 0.247584E+10 | 0.977909E+09 | 0.149793E+10 | 0.524784E+10 | 0.674798E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.154402E+10 | 0.00 | 0.154402E+10 | 0.334932E+10 | 0.784802E+09 |
February | 0.148765E+10 | 0.00 | 0.148765E+10 | 0.338578E+10 | 0.552177E+09 |
March | 0.169037E+10 | 0.00 | 0.169037E+10 | 0.408635E+10 | 0.403227E+09 |
April | 0.178023E+10 | 25229242.72 | 0.175500E+10 | 0.442272E+10 | 0.162240E+09 |
May | 0.235811E+10 | 0.251210E+09 | 0.210690E+10 | 0.582225E+10 | 0.242059E+09 |
June | 0.278760E+10 | 0.563351E+09 | 0.222425E+10 | 0.670404E+10 | 0.276739E+09 |
July | 0.247697E+10 | 0.259631E+09 | 0.221734E+10 | 0.543572E+10 | 0.470710E+09 |
August | 0.203936E+10 | 86959767.40 | 0.195240E+10 | 0.455216E+10 | 0.352234E+09 |
September | 0.168028E+10 | 804608.75 | 0.167948E+10 | 0.386458E+10 | 0.335714E+09 |
October | 0.167298E+10 | 0.00 | 0.167298E+10 | 0.356632E+10 | 0.443685E+09 |
November | 0.153195E+10 | 0.00 | 0.153195E+10 | 0.329544E+10 | 0.524050E+09 |
December | 0.149999E+10 | 0.00 | 0.149999E+10 | 0.321739E+10 | 0.868825E+09 |
Annual Sum or Average | 0.225495E+11 | 0.118719E+10 | 0.213623E+11 | 0.517020E+11 | 0.541646E+10 |
Minimum of Months | 0.148765E+10 | 0.00 | 0.148765E+10 | 0.321739E+10 | 0.162240E+09 |
Maximum of Months | 0.278760E+10 | 0.563351E+09 | 0.222425E+10 | 0.670404E+10 | 0.868825E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198486E+10 | 0.668953E+09 | 0.131590E+10 | 0.396711E+10 | 0.521437E+09 |
February | 0.203300E+10 | 0.745396E+09 | 0.128760E+10 | 0.416211E+10 | 0.364777E+09 |
March | 0.245382E+10 | 0.960903E+09 | 0.149291E+10 | 0.514678E+10 | 0.265504E+09 |
April | 0.239996E+10 | 0.916885E+09 | 0.148307E+10 | 0.515980E+10 | 0.108425E+09 |
May | 0.213174E+10 | 0.645275E+09 | 0.148647E+10 | 0.477188E+10 | 0.157184E+09 |
June | 0.219725E+10 | 0.723656E+09 | 0.147359E+10 | 0.485816E+10 | 0.170040E+09 |
July | 0.193931E+10 | 0.434453E+09 | 0.150486E+10 | 0.402930E+10 | 0.302965E+09 |
August | 0.213425E+10 | 0.627378E+09 | 0.150687E+10 | 0.437664E+10 | 0.239722E+09 |
September | 0.193966E+10 | 0.528567E+09 | 0.141110E+10 | 0.407845E+10 | 0.241597E+09 |
October | 0.187849E+10 | 0.480585E+09 | 0.139791E+10 | 0.376191E+10 | 0.312209E+09 |
November | 0.175936E+10 | 0.486192E+09 | 0.127317E+10 | 0.354295E+10 | 0.366937E+09 |
December | 0.186043E+10 | 0.597031E+09 | 0.126340E+10 | 0.369665E+10 | 0.583572E+09 |
Annual Sum or Average | 0.247121E+11 | 0.781527E+10 | 0.168968E+11 | 0.515517E+11 | 0.363437E+10 |
Minimum of Months | 0.175936E+10 | 0.434453E+09 | 0.126340E+10 | 0.354295E+10 | 0.108425E+09 |
Maximum of Months | 0.245382E+10 | 0.960903E+09 | 0.150687E+10 | 0.515980E+10 | 0.583572E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.408800E+10 | 0.170556E+10 | 0.238244E+10 | 0.825667E+10 | 0.876468E+09 |
February | 0.313540E+10 | 0.102226E+10 | 0.211314E+10 | 0.681361E+10 | 0.601129E+09 |
March | 0.236899E+10 | 0.318156E+09 | 0.205083E+10 | 0.569586E+10 | 0.409424E+09 |
April | 0.170922E+10 | 767281.32 | 0.170845E+10 | 0.431116E+10 | 0.138436E+09 |
May | 0.176740E+10 | 0.00 | 0.176740E+10 | 0.456837E+10 | 0.208475E+09 |
June | 0.170423E+10 | 0.00 | 0.170423E+10 | 0.439757E+10 | 0.217129E+09 |
July | 0.181413E+10 | 0.00 | 0.181413E+10 | 0.403894E+10 | 0.422409E+09 |
August | 0.176607E+10 | 2729501.79 | 0.176334E+10 | 0.396938E+10 | 0.313026E+09 |
September | 0.189210E+10 | 61797318.92 | 0.183030E+10 | 0.432753E+10 | 0.343112E+09 |
October | 0.255793E+10 | 0.407842E+09 | 0.215009E+10 | 0.538144E+10 | 0.497199E+09 |
November | 0.321886E+10 | 0.982030E+09 | 0.223683E+10 | 0.660337E+10 | 0.610567E+09 |
December | 0.408591E+10 | 0.173839E+10 | 0.234752E+10 | 0.812206E+10 | 0.981493E+09 |
Annual Sum or Average | 0.301082E+11 | 0.623953E+10 | 0.238687E+11 | 0.664860E+11 | 0.561886E+10 |
Minimum of Months | 0.170423E+10 | 0.00 | 0.170423E+10 | 0.396938E+10 | 0.138436E+09 |
Maximum of Months | 0.408800E+10 | 0.173839E+10 | 0.238244E+10 | 0.825667E+10 | 0.981493E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201108E+10 | 0.707162E+09 | 0.130392E+10 | 0.405305E+10 | 0.614117E+09 |
February | 0.199500E+10 | 0.705983E+09 | 0.128901E+10 | 0.410861E+10 | 0.449665E+09 |
March | 0.247584E+10 | 0.977909E+09 | 0.149793E+10 | 0.519631E+10 | 0.376978E+09 |
April | 0.240782E+10 | 0.922232E+09 | 0.148559E+10 | 0.510723E+10 | 0.181660E+09 |
May | 0.211708E+10 | 0.627195E+09 | 0.148989E+10 | 0.468252E+10 | 0.178873E+09 |
June | 0.222012E+10 | 0.765224E+09 | 0.145490E+10 | 0.484070E+10 | 0.196562E+09 |
July | 0.195586E+10 | 0.461237E+09 | 0.149462E+10 | 0.402118E+10 | 0.348668E+09 |
August | 0.212641E+10 | 0.629723E+09 | 0.149669E+10 | 0.429626E+10 | 0.288932E+09 |
September | 0.192745E+10 | 0.534589E+09 | 0.139286E+10 | 0.401109E+10 | 0.277103E+09 |
October | 0.187059E+10 | 0.482199E+09 | 0.138840E+10 | 0.371806E+10 | 0.367770E+09 |
November | 0.176536E+10 | 0.481468E+09 | 0.128389E+10 | 0.353878E+10 | 0.426682E+09 |
December | 0.186693E+10 | 0.610708E+09 | 0.125623E+10 | 0.374063E+10 | 0.687313E+09 |
Annual Sum or Average | 0.247396E+11 | 0.790563E+10 | 0.168339E+11 | 0.513144E+11 | 0.439432E+10 |
Minimum of Months | 0.176536E+10 | 0.461237E+09 | 0.125623E+10 | 0.353878E+10 | 0.178873E+09 |
Maximum of Months | 0.247584E+10 | 0.977909E+09 | 0.149793E+10 | 0.519631E+10 | 0.687313E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1261.70 | 295.41 | 576.46 | 0.00 | 576.46 | 0.00 | 0.00 |
February | 1414.49 | 214.42 | 614.93 | 0.00 | 614.93 | 0.00 | 0.00 |
March | 1536.25 | 140.28 | 631.10 | 0.00 | 631.10 | 0.00 | 0.00 |
April | 1718.23 | 56.48 | 686.81 | 9.73 | 677.07 | 0.00 | 0.00 |
May | 2214.31 | 76.97 | 880.40 | 93.79 | 786.61 | 0.00 | 0.00 |
June | 2627.00 | 83.87 | 1075.44 | 217.34 | 858.10 | 0.00 | 0.00 |
July | 2063.92 | 153.69 | 924.78 | 96.93 | 827.84 | 0.00 | 0.00 |
August | 1714.53 | 121.32 | 761.39 | 32.47 | 728.93 | 0.00 | 0.00 |
September | 1515.56 | 118.86 | 648.24 | 0.31 | 647.93 | 0.00 | 0.00 |
October | 1351.83 | 151.62 | 624.61 | 0.00 | 624.61 | 0.00 | 0.00 |
November | 1285.65 | 192.01 | 591.02 | 0.00 | 591.02 | 0.00 | 0.00 |
December | 1204.73 | 320.99 | 560.02 | 0.00 | 560.02 | 0.00 | 0.00 |
Annual Sum or Average | 1659.63 | 160.57 | 715.03 | 37.64 | 677.38 | 0.00 | 0.00 |
Minimum of Months | 1204.73 | 56.48 | 560.02 | 0.00 | 560.02 | 0.00 | 0.00 |
Maximum of Months | 2627.00 | 320.99 | 1075.44 | 217.34 | 858.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1506.08 | 184.65 | 741.06 | 249.76 | 491.30 | 0.00 | 0.00 |
February | 1752.08 | 126.76 | 840.36 | 308.12 | 532.24 | 0.00 | 0.00 |
March | 1958.10 | 75.64 | 916.15 | 358.76 | 557.39 | 0.00 | 0.00 |
April | 2034.78 | 24.26 | 925.91 | 353.74 | 572.18 | 0.00 | 0.00 |
May | 1821.30 | 45.18 | 795.90 | 240.92 | 554.99 | 0.00 | 0.00 |
June | 1915.83 | 44.04 | 847.71 | 279.19 | 568.52 | 0.00 | 0.00 |
July | 1542.07 | 83.49 | 724.06 | 162.21 | 561.85 | 0.00 | 0.00 |
August | 1667.70 | 61.73 | 796.84 | 234.24 | 562.60 | 0.00 | 0.00 |
September | 1605.30 | 75.98 | 748.33 | 203.92 | 544.41 | 0.00 | 0.00 |
October | 1437.55 | 91.41 | 701.35 | 179.43 | 521.92 | 0.00 | 0.00 |
November | 1399.54 | 113.72 | 678.77 | 187.57 | 491.19 | 0.00 | 0.00 |
December | 1409.86 | 187.82 | 694.61 | 222.91 | 471.70 | 0.00 | 0.00 |
Annual Sum or Average | 1669.44 | 92.92 | 783.62 | 247.82 | 535.80 | 0.00 | 0.00 |
Minimum of Months | 1399.54 | 24.26 | 678.77 | 162.21 | 471.70 | 0.00 | 0.00 |
Maximum of Months | 2034.78 | 187.82 | 925.91 | 358.76 | 572.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3122.73 | 313.90 | 1526.24 | 636.76 | 889.48 | 0.00 | 0.00 |
February | 2853.12 | 227.88 | 1296.01 | 422.55 | 873.47 | 0.00 | 0.00 |
March | 2147.71 | 141.69 | 884.46 | 118.78 | 765.68 | 0.00 | 0.00 |
April | 1669.42 | 49.66 | 659.41 | 0.30 | 659.11 | 0.00 | 0.00 |
May | 1732.19 | 69.13 | 659.86 | 0.00 | 659.86 | 0.00 | 0.00 |
June | 1716.58 | 71.07 | 657.48 | 0.00 | 657.48 | 0.00 | 0.00 |
July | 1529.66 | 142.07 | 677.30 | 0.00 | 677.30 | 0.00 | 0.00 |
August | 1491.77 | 110.29 | 659.36 | 1.02 | 658.34 | 0.00 | 0.00 |
September | 1697.26 | 120.77 | 729.96 | 23.84 | 706.12 | 0.00 | 0.00 |
October | 2042.14 | 165.84 | 955.00 | 152.27 | 802.73 | 0.00 | 0.00 |
November | 2581.00 | 214.29 | 1241.81 | 378.86 | 862.95 | 0.00 | 0.00 |
December | 3064.93 | 344.81 | 1525.46 | 649.02 | 876.44 | 0.00 | 0.00 |
Annual Sum or Average | 2133.92 | 164.31 | 954.70 | 197.85 | 756.85 | 0.00 | 0.00 |
Minimum of Months | 1491.77 | 49.66 | 657.48 | 0.00 | 657.48 | 0.00 | 0.00 |
Maximum of Months | 3122.73 | 344.81 | 1526.24 | 649.02 | 889.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1514.16 | 250.60 | 750.86 | 264.02 | 486.83 | 0.00 | 0.00 |
February | 1694.03 | 209.01 | 824.66 | 291.83 | 532.83 | 0.00 | 0.00 |
March | 1927.70 | 173.30 | 924.38 | 365.11 | 559.27 | 0.00 | 0.00 |
April | 1941.67 | 111.20 | 928.95 | 355.80 | 573.15 | 0.00 | 0.00 |
May | 1753.27 | 76.09 | 790.43 | 234.17 | 556.26 | 0.00 | 0.00 |
June | 1860.99 | 91.42 | 856.53 | 295.23 | 561.31 | 0.00 | 0.00 |
July | 1486.81 | 162.00 | 730.24 | 172.21 | 558.03 | 0.00 | 0.00 |
August | 1576.73 | 158.72 | 793.91 | 235.11 | 558.80 | 0.00 | 0.00 |
September | 1552.79 | 121.12 | 743.62 | 206.25 | 537.37 | 0.00 | 0.00 |
October | 1381.20 | 163.74 | 698.40 | 180.03 | 518.37 | 0.00 | 0.00 |
November | 1346.45 | 204.51 | 681.08 | 185.75 | 495.33 | 0.00 | 0.00 |
December | 1369.69 | 313.76 | 697.04 | 228.01 | 469.02 | 0.00 | 0.00 |
Annual Sum or Average | 1615.85 | 169.71 | 784.49 | 250.69 | 533.80 | 0.00 | 0.00 |
Minimum of Months | 1346.45 | 76.09 | 681.08 | 172.21 | 469.02 | 0.00 | 0.00 |
Maximum of Months | 1941.67 | 313.76 | 928.95 | 365.11 | 573.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1274.38 | 283.88 | 576.47 | 0.00 | 576.47 | 0.00 | 0.00 |
February | 1427.66 | 217.80 | 614.94 | 0.00 | 614.94 | 0.00 | 0.00 |
March | 1555.55 | 137.90 | 631.11 | 0.00 | 631.11 | 0.00 | 0.00 |
April | 1749.65 | 52.84 | 686.82 | 9.73 | 677.08 | 0.00 | 0.00 |
May | 2215.67 | 79.39 | 880.42 | 93.79 | 786.63 | 0.00 | 0.00 |
June | 2624.66 | 91.62 | 1075.46 | 217.34 | 858.12 | 0.00 | 0.00 |
July | 2063.66 | 161.58 | 924.80 | 96.94 | 827.86 | 0.00 | 0.00 |
August | 1728.56 | 119.76 | 761.41 | 32.47 | 728.94 | 0.00 | 0.00 |
September | 1523.29 | 115.63 | 648.26 | 0.31 | 647.95 | 0.00 | 0.00 |
October | 1359.27 | 151.50 | 624.62 | 0.00 | 624.62 | 0.00 | 0.00 |
November | 1298.13 | 191.54 | 591.03 | 0.00 | 591.03 | 0.00 | 0.00 |
December | 1223.89 | 314.90 | 560.03 | 0.00 | 560.03 | 0.00 | 0.00 |
Annual Sum or Average | 1670.95 | 159.90 | 715.04 | 37.65 | 677.40 | 0.00 | 0.00 |
Minimum of Months | 1223.89 | 52.84 | 560.03 | 0.00 | 560.03 | 0.00 | 0.00 |
Maximum of Months | 2624.66 | 314.90 | 1075.46 | 217.34 | 858.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1498.63 | 188.18 | 741.06 | 249.76 | 491.30 | 0.00 | 0.00 |
February | 1740.57 | 144.18 | 840.36 | 308.12 | 532.24 | 0.00 | 0.00 |
March | 1944.46 | 91.52 | 916.15 | 358.76 | 557.39 | 0.00 | 0.00 |
April | 2020.74 | 36.04 | 925.91 | 353.74 | 572.17 | 0.00 | 0.00 |
May | 1810.04 | 51.81 | 795.90 | 240.92 | 554.98 | 0.00 | 0.00 |
June | 1900.98 | 56.23 | 847.70 | 279.19 | 568.51 | 0.00 | 0.00 |
July | 1526.92 | 103.85 | 724.05 | 162.21 | 561.85 | 0.00 | 0.00 |
August | 1653.94 | 81.64 | 796.84 | 234.24 | 562.60 | 0.00 | 0.00 |
September | 1594.92 | 83.87 | 748.33 | 203.92 | 544.40 | 0.00 | 0.00 |
October | 1423.82 | 107.36 | 701.35 | 179.43 | 521.92 | 0.00 | 0.00 |
November | 1385.24 | 134.49 | 678.76 | 187.57 | 491.19 | 0.00 | 0.00 |
December | 1396.60 | 211.01 | 694.61 | 222.91 | 471.70 | 0.00 | 0.00 |
Annual Sum or Average | 1656.66 | 107.54 | 783.62 | 247.82 | 535.80 | 0.00 | 0.00 |
Minimum of Months | 1385.24 | 36.04 | 678.76 | 162.21 | 471.70 | 0.00 | 0.00 |
Maximum of Months | 2020.74 | 211.01 | 925.91 | 358.76 | 572.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3104.04 | 317.60 | 1526.29 | 636.78 | 889.50 | 0.00 | 0.00 |
February | 2843.46 | 238.14 | 1296.05 | 422.56 | 873.49 | 0.00 | 0.00 |
March | 2158.07 | 141.01 | 884.48 | 118.79 | 765.69 | 0.00 | 0.00 |
April | 1707.93 | 45.72 | 659.42 | 0.30 | 659.12 | 0.00 | 0.00 |
May | 1749.45 | 68.60 | 659.87 | 0.00 | 659.87 | 0.00 | 0.00 |
June | 1736.94 | 71.78 | 657.50 | 0.00 | 657.50 | 0.00 | 0.00 |
July | 1542.32 | 144.26 | 677.32 | 0.00 | 677.32 | 0.00 | 0.00 |
August | 1511.62 | 106.26 | 659.38 | 1.02 | 658.36 | 0.00 | 0.00 |
September | 1702.51 | 118.59 | 729.98 | 23.84 | 706.13 | 0.00 | 0.00 |
October | 2037.66 | 171.33 | 955.02 | 152.27 | 802.75 | 0.00 | 0.00 |
November | 2573.21 | 224.48 | 1241.84 | 378.87 | 862.97 | 0.00 | 0.00 |
December | 3053.15 | 355.89 | 1525.50 | 649.04 | 876.46 | 0.00 | 0.00 |
Annual Sum or Average | 2139.95 | 166.95 | 954.73 | 197.85 | 756.87 | 0.00 | 0.00 |
Minimum of Months | 1511.62 | 45.72 | 657.50 | 0.00 | 657.50 | 0.00 | 0.00 |
Maximum of Months | 3104.04 | 355.89 | 1526.29 | 649.04 | 889.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1528.02 | 224.89 | 750.85 | 264.02 | 486.83 | 0.00 | 0.00 |
February | 1715.94 | 180.52 | 824.65 | 291.83 | 532.83 | 0.00 | 0.00 |
March | 1959.32 | 134.49 | 924.37 | 365.11 | 559.26 | 0.00 | 0.00 |
April | 1993.73 | 64.68 | 928.94 | 355.80 | 573.14 | 0.00 | 0.00 |
May | 1772.18 | 61.57 | 790.43 | 234.17 | 556.26 | 0.00 | 0.00 |
June | 1891.06 | 68.95 | 856.53 | 295.23 | 561.30 | 0.00 | 0.00 |
July | 1521.67 | 124.19 | 730.23 | 172.21 | 558.03 | 0.00 | 0.00 |
August | 1622.89 | 102.63 | 793.91 | 235.11 | 558.80 | 0.00 | 0.00 |
September | 1567.31 | 100.34 | 743.61 | 206.25 | 537.37 | 0.00 | 0.00 |
October | 1404.72 | 130.71 | 698.40 | 180.03 | 518.37 | 0.00 | 0.00 |
November | 1381.22 | 160.01 | 681.08 | 185.75 | 495.33 | 0.00 | 0.00 |
December | 1410.49 | 251.94 | 697.03 | 228.01 | 469.02 | 0.00 | 0.00 |
Annual Sum or Average | 1646.15 | 133.75 | 784.49 | 250.69 | 533.80 | 0.00 | 0.00 |
Minimum of Months | 1381.22 | 61.57 | 681.08 | 172.21 | 469.02 | 0.00 | 0.00 |
Maximum of Months | 1993.73 | 251.94 | 928.94 | 365.11 | 573.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1250.49 | 293.01 | 576.47 | 0.00 | 576.47 | 0.00 | 0.00 |
February | 1399.54 | 228.25 | 614.94 | 0.00 | 614.94 | 0.00 | 0.00 |
March | 1525.67 | 150.55 | 631.11 | 0.00 | 631.11 | 0.00 | 0.00 |
April | 1706.29 | 62.59 | 686.82 | 9.73 | 677.08 | 0.00 | 0.00 |
May | 2173.78 | 90.37 | 880.42 | 93.79 | 786.63 | 0.00 | 0.00 |
June | 2586.43 | 106.77 | 1075.46 | 217.34 | 858.12 | 0.00 | 0.00 |
July | 2029.46 | 175.74 | 924.80 | 96.94 | 827.86 | 0.00 | 0.00 |
August | 1699.58 | 131.51 | 761.41 | 32.47 | 728.94 | 0.00 | 0.00 |
September | 1490.97 | 129.52 | 648.26 | 0.31 | 647.95 | 0.00 | 0.00 |
October | 1331.51 | 165.65 | 624.62 | 0.00 | 624.62 | 0.00 | 0.00 |
November | 1271.39 | 202.18 | 591.03 | 0.00 | 591.03 | 0.00 | 0.00 |
December | 1201.23 | 324.38 | 560.03 | 0.00 | 560.03 | 0.00 | 0.00 |
Annual Sum or Average | 1639.46 | 171.75 | 715.04 | 37.65 | 677.40 | 0.00 | 0.00 |
Minimum of Months | 1201.23 | 62.59 | 560.03 | 0.00 | 560.03 | 0.00 | 0.00 |
Maximum of Months | 2586.43 | 324.38 | 1075.46 | 217.34 | 858.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1481.15 | 194.68 | 741.06 | 249.76 | 491.30 | 0.00 | 0.00 |
February | 1720.45 | 150.78 | 840.36 | 308.12 | 532.24 | 0.00 | 0.00 |
March | 1921.59 | 99.13 | 916.15 | 358.76 | 557.39 | 0.00 | 0.00 |
April | 1990.67 | 41.83 | 925.91 | 353.74 | 572.17 | 0.00 | 0.00 |
May | 1781.61 | 58.69 | 795.90 | 240.92 | 554.98 | 0.00 | 0.00 |
June | 1874.29 | 65.60 | 847.70 | 279.19 | 568.51 | 0.00 | 0.00 |
July | 1504.37 | 113.11 | 724.05 | 162.21 | 561.85 | 0.00 | 0.00 |
August | 1634.05 | 89.50 | 796.84 | 234.24 | 562.60 | 0.00 | 0.00 |
September | 1573.48 | 93.21 | 748.33 | 203.92 | 544.40 | 0.00 | 0.00 |
October | 1404.54 | 116.57 | 701.35 | 179.43 | 521.92 | 0.00 | 0.00 |
November | 1366.88 | 141.57 | 678.76 | 187.57 | 491.19 | 0.00 | 0.00 |
December | 1380.17 | 217.88 | 694.61 | 222.91 | 471.70 | 0.00 | 0.00 |
Annual Sum or Average | 1634.70 | 115.25 | 783.62 | 247.82 | 535.80 | 0.00 | 0.00 |
Minimum of Months | 1366.88 | 41.83 | 678.76 | 162.21 | 471.70 | 0.00 | 0.00 |
Maximum of Months | 1990.67 | 217.88 | 925.91 | 358.76 | 572.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3082.69 | 327.24 | 1526.29 | 636.78 | 889.50 | 0.00 | 0.00 |
February | 2816.47 | 248.48 | 1296.05 | 422.56 | 873.49 | 0.00 | 0.00 |
March | 2126.59 | 152.86 | 884.48 | 118.79 | 765.69 | 0.00 | 0.00 |
April | 1663.26 | 53.41 | 659.42 | 0.30 | 659.12 | 0.00 | 0.00 |
May | 1705.63 | 77.84 | 659.87 | 0.00 | 659.87 | 0.00 | 0.00 |
June | 1696.59 | 83.77 | 657.50 | 0.00 | 657.50 | 0.00 | 0.00 |
July | 1507.97 | 157.71 | 677.32 | 0.00 | 677.32 | 0.00 | 0.00 |
August | 1482.00 | 116.87 | 659.38 | 1.02 | 658.36 | 0.00 | 0.00 |
September | 1669.57 | 132.37 | 729.98 | 23.84 | 706.13 | 0.00 | 0.00 |
October | 2009.20 | 185.63 | 955.02 | 152.27 | 802.75 | 0.00 | 0.00 |
November | 2547.60 | 235.56 | 1241.84 | 378.87 | 862.97 | 0.00 | 0.00 |
December | 3032.43 | 366.45 | 1525.50 | 649.04 | 876.46 | 0.00 | 0.00 |
Annual Sum or Average | 2108.26 | 178.17 | 954.73 | 197.85 | 756.87 | 0.00 | 0.00 |
Minimum of Months | 1482.00 | 53.41 | 657.50 | 0.00 | 657.50 | 0.00 | 0.00 |
Maximum of Months | 3082.69 | 366.45 | 1526.29 | 649.04 | 889.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1513.23 | 229.28 | 750.85 | 264.02 | 486.83 | 0.00 | 0.00 |
February | 1698.33 | 185.87 | 824.65 | 291.83 | 532.83 | 0.00 | 0.00 |
March | 1940.08 | 140.75 | 924.37 | 365.11 | 559.26 | 0.00 | 0.00 |
April | 1970.38 | 70.08 | 928.94 | 355.80 | 573.14 | 0.00 | 0.00 |
May | 1748.25 | 66.78 | 790.43 | 234.17 | 556.26 | 0.00 | 0.00 |
June | 1867.56 | 75.83 | 856.53 | 295.23 | 561.30 | 0.00 | 0.00 |
July | 1501.34 | 130.18 | 730.23 | 172.21 | 558.03 | 0.00 | 0.00 |
August | 1604.04 | 107.87 | 793.91 | 235.11 | 558.80 | 0.00 | 0.00 |
September | 1547.49 | 106.91 | 743.61 | 206.25 | 537.37 | 0.00 | 0.00 |
October | 1388.17 | 137.31 | 698.40 | 180.03 | 518.37 | 0.00 | 0.00 |
November | 1365.27 | 164.62 | 681.08 | 185.75 | 495.33 | 0.00 | 0.00 |
December | 1396.59 | 256.61 | 697.03 | 228.01 | 469.02 | 0.00 | 0.00 |
Annual Sum or Average | 1627.17 | 139.34 | 784.49 | 250.69 | 533.80 | 0.00 | 0.00 |
Minimum of Months | 1365.27 | 66.78 | 681.08 | 172.21 | 469.02 | 0.00 | 0.00 |
Maximum of Months | 1970.38 | 256.61 | 928.94 | 365.11 | 573.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.337934E+10 | 0.791223E+09 | 0.154399E+10 | 0.00 | 0.154399E+10 | 0.00 | 0.00 |
February | 0.342194E+10 | 0.518737E+09 | 0.148763E+10 | 0.00 | 0.148763E+10 | 0.00 | 0.00 |
March | 0.411469E+10 | 0.375731E+09 | 0.169035E+10 | 0.00 | 0.169035E+10 | 0.00 | 0.00 |
April | 0.445366E+10 | 0.146401E+09 | 0.178020E+10 | 25228490.33 | 0.175497E+10 | 0.00 | 0.00 |
May | 0.593081E+10 | 0.206159E+09 | 0.235806E+10 | 0.251203E+09 | 0.210686E+10 | 0.00 | 0.00 |
June | 0.680917E+10 | 0.217395E+09 | 0.278754E+10 | 0.563335E+09 | 0.222420E+10 | 0.00 | 0.00 |
July | 0.552800E+10 | 0.411656E+09 | 0.247692E+10 | 0.259623E+09 | 0.221730E+10 | 0.00 | 0.00 |
August | 0.459220E+10 | 0.324953E+09 | 0.203932E+10 | 86957174.09 | 0.195236E+10 | 0.00 | 0.00 |
September | 0.392834E+10 | 0.308097E+09 | 0.168025E+10 | 804584.76 | 0.167944E+10 | 0.00 | 0.00 |
October | 0.362073E+10 | 0.406097E+09 | 0.167295E+10 | 0.00 | 0.167295E+10 | 0.00 | 0.00 |
November | 0.333240E+10 | 0.497693E+09 | 0.153192E+10 | 0.00 | 0.153192E+10 | 0.00 | 0.00 |
December | 0.322675E+10 | 0.859734E+09 | 0.149997E+10 | 0.00 | 0.149997E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.523380E+11 | 0.506387E+10 | 0.225491E+11 | 0.118715E+10 | 0.213619E+11 | 0.00 | 0.00 |
Minimum of Months | 0.322675E+10 | 0.146401E+09 | 0.148763E+10 | 0.00 | 0.148763E+10 | 0.00 | 0.00 |
Maximum of Months | 0.680917E+10 | 0.859734E+09 | 0.278754E+10 | 0.563335E+09 | 0.222420E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.403390E+10 | 0.494562E+09 | 0.198486E+10 | 0.668956E+09 | 0.131591E+10 | 0.00 | 0.00 |
February | 0.423864E+10 | 0.306670E+09 | 0.203300E+10 | 0.745400E+09 | 0.128760E+10 | 0.00 | 0.00 |
March | 0.524456E+10 | 0.202602E+09 | 0.245383E+10 | 0.960907E+09 | 0.149292E+10 | 0.00 | 0.00 |
April | 0.527414E+10 | 62869060.03 | 0.239997E+10 | 0.916889E+09 | 0.148308E+10 | 0.00 | 0.00 |
May | 0.487818E+10 | 0.121000E+09 | 0.213175E+10 | 0.645277E+09 | 0.148647E+10 | 0.00 | 0.00 |
June | 0.496583E+10 | 0.114155E+09 | 0.219725E+10 | 0.723659E+09 | 0.147359E+10 | 0.00 | 0.00 |
July | 0.413029E+10 | 0.223620E+09 | 0.193932E+10 | 0.434455E+09 | 0.150486E+10 | 0.00 | 0.00 |
August | 0.446678E+10 | 0.165344E+09 | 0.213425E+10 | 0.627380E+09 | 0.150687E+10 | 0.00 | 0.00 |
September | 0.416093E+10 | 0.196952E+09 | 0.193967E+10 | 0.528569E+09 | 0.141110E+10 | 0.00 | 0.00 |
October | 0.385033E+10 | 0.244832E+09 | 0.187850E+10 | 0.480587E+09 | 0.139791E+10 | 0.00 | 0.00 |
November | 0.362760E+10 | 0.294775E+09 | 0.175937E+10 | 0.486194E+09 | 0.127317E+10 | 0.00 | 0.00 |
December | 0.377617E+10 | 0.503062E+09 | 0.186044E+10 | 0.597033E+09 | 0.126341E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.526474E+11 | 0.293044E+10 | 0.247122E+11 | 0.781531E+10 | 0.168969E+11 | 0.00 | 0.00 |
Minimum of Months | 0.362760E+10 | 62869060.03 | 0.175937E+10 | 0.434455E+09 | 0.126341E+10 | 0.00 | 0.00 |
Maximum of Months | 0.527414E+10 | 0.503062E+09 | 0.245383E+10 | 0.960907E+09 | 0.150687E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.836393E+10 | 0.840748E+09 | 0.408789E+10 | 0.170551E+10 | 0.238238E+10 | 0.00 | 0.00 |
February | 0.690227E+10 | 0.551287E+09 | 0.313531E+10 | 0.102222E+10 | 0.211309E+10 | 0.00 | 0.00 |
March | 0.575244E+10 | 0.379506E+09 | 0.236893E+10 | 0.318146E+09 | 0.205079E+10 | 0.00 | 0.00 |
April | 0.432713E+10 | 0.128724E+09 | 0.170919E+10 | 767256.19 | 0.170842E+10 | 0.00 | 0.00 |
May | 0.463950E+10 | 0.185159E+09 | 0.176736E+10 | 0.00 | 0.176736E+10 | 0.00 | 0.00 |
June | 0.444938E+10 | 0.184224E+09 | 0.170420E+10 | 0.00 | 0.170420E+10 | 0.00 | 0.00 |
July | 0.409703E+10 | 0.380510E+09 | 0.181409E+10 | 0.00 | 0.181409E+10 | 0.00 | 0.00 |
August | 0.399556E+10 | 0.295401E+09 | 0.176604E+10 | 2729412.39 | 0.176331E+10 | 0.00 | 0.00 |
September | 0.439929E+10 | 0.313023E+09 | 0.189206E+10 | 61795294.87 | 0.183026E+10 | 0.00 | 0.00 |
October | 0.546968E+10 | 0.444193E+09 | 0.255787E+10 | 0.407829E+09 | 0.215004E+10 | 0.00 | 0.00 |
November | 0.668996E+10 | 0.555443E+09 | 0.321877E+10 | 0.981998E+09 | 0.223677E+10 | 0.00 | 0.00 |
December | 0.820911E+10 | 0.923531E+09 | 0.408580E+10 | 0.173833E+10 | 0.234746E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.672953E+11 | 0.518175E+10 | 0.301075E+11 | 0.623933E+10 | 0.238682E+11 | 0.00 | 0.00 |
Minimum of Months | 0.399556E+10 | 0.128724E+09 | 0.170420E+10 | 0.00 | 0.170420E+10 | 0.00 | 0.00 |
Maximum of Months | 0.836393E+10 | 0.923531E+09 | 0.408789E+10 | 0.173833E+10 | 0.238238E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.405553E+10 | 0.671209E+09 | 0.201109E+10 | 0.707165E+09 | 0.130393E+10 | 0.00 | 0.00 |
February | 0.409821E+10 | 0.505640E+09 | 0.199501E+10 | 0.705986E+09 | 0.128902E+10 | 0.00 | 0.00 |
March | 0.516316E+10 | 0.464167E+09 | 0.247585E+10 | 0.977913E+09 | 0.149794E+10 | 0.00 | 0.00 |
April | 0.503281E+10 | 0.288238E+09 | 0.240783E+10 | 0.922236E+09 | 0.148560E+10 | 0.00 | 0.00 |
May | 0.469596E+10 | 0.203811E+09 | 0.211709E+10 | 0.627197E+09 | 0.148990E+10 | 0.00 | 0.00 |
June | 0.482368E+10 | 0.236950E+09 | 0.222013E+10 | 0.765227E+09 | 0.145490E+10 | 0.00 | 0.00 |
July | 0.398228E+10 | 0.433895E+09 | 0.195587E+10 | 0.461239E+09 | 0.149463E+10 | 0.00 | 0.00 |
August | 0.422311E+10 | 0.425112E+09 | 0.212642E+10 | 0.629725E+09 | 0.149669E+10 | 0.00 | 0.00 |
September | 0.402483E+10 | 0.313941E+09 | 0.192746E+10 | 0.534592E+09 | 0.139286E+10 | 0.00 | 0.00 |
October | 0.369941E+10 | 0.438551E+09 | 0.187060E+10 | 0.482201E+09 | 0.138840E+10 | 0.00 | 0.00 |
November | 0.348999E+10 | 0.530084E+09 | 0.176537E+10 | 0.481470E+09 | 0.128390E+10 | 0.00 | 0.00 |
December | 0.366858E+10 | 0.840386E+09 | 0.186694E+10 | 0.610711E+09 | 0.125623E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.509576E+11 | 0.535198E+10 | 0.247397E+11 | 0.790566E+10 | 0.168340E+11 | 0.00 | 0.00 |
Minimum of Months | 0.348999E+10 | 0.203811E+09 | 0.176537E+10 | 0.461239E+09 | 0.125623E+10 | 0.00 | 0.00 |
Maximum of Months | 0.516316E+10 | 0.840386E+09 | 0.247585E+10 | 0.977913E+09 | 0.149794E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.341330E+10 | 0.760334E+09 | 0.154402E+10 | 0.00 | 0.154402E+10 | 0.00 | 0.00 |
February | 0.345380E+10 | 0.526890E+09 | 0.148765E+10 | 0.00 | 0.148765E+10 | 0.00 | 0.00 |
March | 0.416638E+10 | 0.369359E+09 | 0.169037E+10 | 0.00 | 0.169037E+10 | 0.00 | 0.00 |
April | 0.453508E+10 | 0.136958E+09 | 0.178023E+10 | 25229242.72 | 0.175500E+10 | 0.00 | 0.00 |
May | 0.593445E+10 | 0.212646E+09 | 0.235811E+10 | 0.251210E+09 | 0.210690E+10 | 0.00 | 0.00 |
June | 0.680311E+10 | 0.237466E+09 | 0.278760E+10 | 0.563351E+09 | 0.222425E+10 | 0.00 | 0.00 |
July | 0.552730E+10 | 0.432764E+09 | 0.247697E+10 | 0.259631E+09 | 0.221734E+10 | 0.00 | 0.00 |
August | 0.462976E+10 | 0.320774E+09 | 0.203936E+10 | 86959767.40 | 0.195240E+10 | 0.00 | 0.00 |
September | 0.394837E+10 | 0.299717E+09 | 0.168028E+10 | 804608.75 | 0.167948E+10 | 0.00 | 0.00 |
October | 0.364067E+10 | 0.405765E+09 | 0.167298E+10 | 0.00 | 0.167298E+10 | 0.00 | 0.00 |
November | 0.336475E+10 | 0.496464E+09 | 0.153195E+10 | 0.00 | 0.153195E+10 | 0.00 | 0.00 |
December | 0.327806E+10 | 0.843423E+09 | 0.149999E+10 | 0.00 | 0.149999E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.526950E+11 | 0.504256E+10 | 0.225495E+11 | 0.118719E+10 | 0.213623E+11 | 0.00 | 0.00 |
Minimum of Months | 0.327806E+10 | 0.136958E+09 | 0.148765E+10 | 0.00 | 0.148765E+10 | 0.00 | 0.00 |
Maximum of Months | 0.680311E+10 | 0.843423E+09 | 0.278760E+10 | 0.563351E+09 | 0.222425E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.401394E+10 | 0.504010E+09 | 0.198486E+10 | 0.668953E+09 | 0.131590E+10 | 0.00 | 0.00 |
February | 0.421078E+10 | 0.348798E+09 | 0.203300E+10 | 0.745396E+09 | 0.128760E+10 | 0.00 | 0.00 |
March | 0.520804E+10 | 0.245131E+09 | 0.245382E+10 | 0.960903E+09 | 0.149291E+10 | 0.00 | 0.00 |
April | 0.523777E+10 | 93410098.24 | 0.239996E+10 | 0.916885E+09 | 0.148307E+10 | 0.00 | 0.00 |
May | 0.484802E+10 | 0.138776E+09 | 0.213174E+10 | 0.645275E+09 | 0.148647E+10 | 0.00 | 0.00 |
June | 0.492735E+10 | 0.145746E+09 | 0.219725E+10 | 0.723656E+09 | 0.147359E+10 | 0.00 | 0.00 |
July | 0.408971E+10 | 0.278142E+09 | 0.193931E+10 | 0.434453E+09 | 0.150486E+10 | 0.00 | 0.00 |
August | 0.442992E+10 | 0.218660E+09 | 0.213425E+10 | 0.627378E+09 | 0.150687E+10 | 0.00 | 0.00 |
September | 0.413403E+10 | 0.217402E+09 | 0.193966E+10 | 0.528567E+09 | 0.141110E+10 | 0.00 | 0.00 |
October | 0.381355E+10 | 0.287555E+09 | 0.187849E+10 | 0.480585E+09 | 0.139791E+10 | 0.00 | 0.00 |
November | 0.359055E+10 | 0.348599E+09 | 0.175936E+10 | 0.486192E+09 | 0.127317E+10 | 0.00 | 0.00 |
December | 0.374064E+10 | 0.565179E+09 | 0.186043E+10 | 0.597031E+09 | 0.126340E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.522443E+11 | 0.339141E+10 | 0.247121E+11 | 0.781527E+10 | 0.168968E+11 | 0.00 | 0.00 |
Minimum of Months | 0.359055E+10 | 93410098.24 | 0.175936E+10 | 0.434453E+09 | 0.126340E+10 | 0.00 | 0.00 |
Maximum of Months | 0.523777E+10 | 0.565179E+09 | 0.245382E+10 | 0.960903E+09 | 0.150687E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.831386E+10 | 0.850673E+09 | 0.408800E+10 | 0.170556E+10 | 0.238244E+10 | 0.00 | 0.00 |
February | 0.687890E+10 | 0.576120E+09 | 0.313540E+10 | 0.102226E+10 | 0.211314E+10 | 0.00 | 0.00 |
March | 0.578017E+10 | 0.377679E+09 | 0.236899E+10 | 0.318156E+09 | 0.205083E+10 | 0.00 | 0.00 |
April | 0.442696E+10 | 0.118499E+09 | 0.170922E+10 | 767281.32 | 0.170845E+10 | 0.00 | 0.00 |
May | 0.468573E+10 | 0.183728E+09 | 0.176740E+10 | 0.00 | 0.176740E+10 | 0.00 | 0.00 |
June | 0.450214E+10 | 0.186046E+09 | 0.170423E+10 | 0.00 | 0.170423E+10 | 0.00 | 0.00 |
July | 0.413095E+10 | 0.386376E+09 | 0.181413E+10 | 0.00 | 0.181413E+10 | 0.00 | 0.00 |
August | 0.404873E+10 | 0.284600E+09 | 0.176607E+10 | 2729501.79 | 0.176334E+10 | 0.00 | 0.00 |
September | 0.441291E+10 | 0.307380E+09 | 0.189210E+10 | 61797318.92 | 0.183030E+10 | 0.00 | 0.00 |
October | 0.545768E+10 | 0.458883E+09 | 0.255793E+10 | 0.407842E+09 | 0.215009E+10 | 0.00 | 0.00 |
November | 0.666977E+10 | 0.581856E+09 | 0.321886E+10 | 0.982030E+09 | 0.223683E+10 | 0.00 | 0.00 |
December | 0.817757E+10 | 0.953206E+09 | 0.408591E+10 | 0.173839E+10 | 0.234752E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.674854E+11 | 0.526505E+10 | 0.301082E+11 | 0.623953E+10 | 0.238687E+11 | 0.00 | 0.00 |
Minimum of Months | 0.404873E+10 | 0.118499E+09 | 0.170423E+10 | 0.00 | 0.170423E+10 | 0.00 | 0.00 |
Maximum of Months | 0.831386E+10 | 0.953206E+09 | 0.408800E+10 | 0.173839E+10 | 0.238244E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.409265E+10 | 0.602347E+09 | 0.201108E+10 | 0.707162E+09 | 0.130392E+10 | 0.00 | 0.00 |
February | 0.415120E+10 | 0.436702E+09 | 0.199500E+10 | 0.705983E+09 | 0.128901E+10 | 0.00 | 0.00 |
March | 0.524784E+10 | 0.360226E+09 | 0.247584E+10 | 0.977909E+09 | 0.149793E+10 | 0.00 | 0.00 |
April | 0.516776E+10 | 0.167657E+09 | 0.240782E+10 | 0.922232E+09 | 0.148559E+10 | 0.00 | 0.00 |
May | 0.474660E+10 | 0.164917E+09 | 0.211708E+10 | 0.627195E+09 | 0.148989E+10 | 0.00 | 0.00 |
June | 0.490162E+10 | 0.178717E+09 | 0.222012E+10 | 0.765224E+09 | 0.145490E+10 | 0.00 | 0.00 |
July | 0.407564E+10 | 0.332623E+09 | 0.195586E+10 | 0.461237E+09 | 0.149462E+10 | 0.00 | 0.00 |
August | 0.434676E+10 | 0.274897E+09 | 0.212641E+10 | 0.629723E+09 | 0.149669E+10 | 0.00 | 0.00 |
September | 0.406245E+10 | 0.260087E+09 | 0.192745E+10 | 0.534589E+09 | 0.139286E+10 | 0.00 | 0.00 |
October | 0.376239E+10 | 0.350101E+09 | 0.187059E+10 | 0.482199E+09 | 0.138840E+10 | 0.00 | 0.00 |
November | 0.358013E+10 | 0.414741E+09 | 0.176536E+10 | 0.481468E+09 | 0.128389E+10 | 0.00 | 0.00 |
December | 0.377787E+10 | 0.674798E+09 | 0.186693E+10 | 0.610708E+09 | 0.125623E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.519129E+11 | 0.421781E+10 | 0.247396E+11 | 0.790563E+10 | 0.168339E+11 | 0.00 | 0.00 |
Minimum of Months | 0.358013E+10 | 0.164917E+09 | 0.176536E+10 | 0.461237E+09 | 0.125623E+10 | 0.00 | 0.00 |
Maximum of Months | 0.524784E+10 | 0.674798E+09 | 0.247584E+10 | 0.977909E+09 | 0.149793E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.334932E+10 | 0.784802E+09 | 0.154402E+10 | 0.00 | 0.154402E+10 | 0.00 | 0.00 |
February | 0.338578E+10 | 0.552177E+09 | 0.148765E+10 | 0.00 | 0.148765E+10 | 0.00 | 0.00 |
March | 0.408635E+10 | 0.403227E+09 | 0.169037E+10 | 0.00 | 0.169037E+10 | 0.00 | 0.00 |
April | 0.442272E+10 | 0.162240E+09 | 0.178023E+10 | 25229242.72 | 0.175500E+10 | 0.00 | 0.00 |
May | 0.582225E+10 | 0.242059E+09 | 0.235811E+10 | 0.251210E+09 | 0.210690E+10 | 0.00 | 0.00 |
June | 0.670404E+10 | 0.276739E+09 | 0.278760E+10 | 0.563351E+09 | 0.222425E+10 | 0.00 | 0.00 |
July | 0.543572E+10 | 0.470710E+09 | 0.247697E+10 | 0.259631E+09 | 0.221734E+10 | 0.00 | 0.00 |
August | 0.455216E+10 | 0.352234E+09 | 0.203936E+10 | 86959767.40 | 0.195240E+10 | 0.00 | 0.00 |
September | 0.386458E+10 | 0.335714E+09 | 0.168028E+10 | 804608.75 | 0.167948E+10 | 0.00 | 0.00 |
October | 0.356632E+10 | 0.443685E+09 | 0.167298E+10 | 0.00 | 0.167298E+10 | 0.00 | 0.00 |
November | 0.329544E+10 | 0.524050E+09 | 0.153195E+10 | 0.00 | 0.153195E+10 | 0.00 | 0.00 |
December | 0.321739E+10 | 0.868825E+09 | 0.149999E+10 | 0.00 | 0.149999E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.517020E+11 | 0.541646E+10 | 0.225495E+11 | 0.118719E+10 | 0.213623E+11 | 0.00 | 0.00 |
Minimum of Months | 0.321739E+10 | 0.162240E+09 | 0.148765E+10 | 0.00 | 0.148765E+10 | 0.00 | 0.00 |
Maximum of Months | 0.670404E+10 | 0.868825E+09 | 0.278760E+10 | 0.563351E+09 | 0.222425E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.396711E+10 | 0.521437E+09 | 0.198486E+10 | 0.668953E+09 | 0.131590E+10 | 0.00 | 0.00 |
February | 0.416211E+10 | 0.364777E+09 | 0.203300E+10 | 0.745396E+09 | 0.128760E+10 | 0.00 | 0.00 |
March | 0.514678E+10 | 0.265504E+09 | 0.245382E+10 | 0.960903E+09 | 0.149291E+10 | 0.00 | 0.00 |
April | 0.515980E+10 | 0.108425E+09 | 0.239996E+10 | 0.916885E+09 | 0.148307E+10 | 0.00 | 0.00 |
May | 0.477188E+10 | 0.157184E+09 | 0.213174E+10 | 0.645275E+09 | 0.148647E+10 | 0.00 | 0.00 |
June | 0.485816E+10 | 0.170040E+09 | 0.219725E+10 | 0.723656E+09 | 0.147359E+10 | 0.00 | 0.00 |
July | 0.402930E+10 | 0.302965E+09 | 0.193931E+10 | 0.434453E+09 | 0.150486E+10 | 0.00 | 0.00 |
August | 0.437664E+10 | 0.239722E+09 | 0.213425E+10 | 0.627378E+09 | 0.150687E+10 | 0.00 | 0.00 |
September | 0.407845E+10 | 0.241597E+09 | 0.193966E+10 | 0.528567E+09 | 0.141110E+10 | 0.00 | 0.00 |
October | 0.376191E+10 | 0.312209E+09 | 0.187849E+10 | 0.480585E+09 | 0.139791E+10 | 0.00 | 0.00 |
November | 0.354295E+10 | 0.366937E+09 | 0.175936E+10 | 0.486192E+09 | 0.127317E+10 | 0.00 | 0.00 |
December | 0.369665E+10 | 0.583572E+09 | 0.186043E+10 | 0.597031E+09 | 0.126340E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.515517E+11 | 0.363437E+10 | 0.247121E+11 | 0.781527E+10 | 0.168968E+11 | 0.00 | 0.00 |
Minimum of Months | 0.354295E+10 | 0.108425E+09 | 0.175936E+10 | 0.434453E+09 | 0.126340E+10 | 0.00 | 0.00 |
Maximum of Months | 0.515980E+10 | 0.583572E+09 | 0.245382E+10 | 0.960903E+09 | 0.150687E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.825667E+10 | 0.876468E+09 | 0.408800E+10 | 0.170556E+10 | 0.238244E+10 | 0.00 | 0.00 |
February | 0.681361E+10 | 0.601129E+09 | 0.313540E+10 | 0.102226E+10 | 0.211314E+10 | 0.00 | 0.00 |
March | 0.569586E+10 | 0.409424E+09 | 0.236899E+10 | 0.318156E+09 | 0.205083E+10 | 0.00 | 0.00 |
April | 0.431116E+10 | 0.138436E+09 | 0.170922E+10 | 767281.32 | 0.170845E+10 | 0.00 | 0.00 |
May | 0.456837E+10 | 0.208475E+09 | 0.176740E+10 | 0.00 | 0.176740E+10 | 0.00 | 0.00 |
June | 0.439757E+10 | 0.217129E+09 | 0.170423E+10 | 0.00 | 0.170423E+10 | 0.00 | 0.00 |
July | 0.403894E+10 | 0.422409E+09 | 0.181413E+10 | 0.00 | 0.181413E+10 | 0.00 | 0.00 |
August | 0.396938E+10 | 0.313026E+09 | 0.176607E+10 | 2729501.79 | 0.176334E+10 | 0.00 | 0.00 |
September | 0.432753E+10 | 0.343112E+09 | 0.189210E+10 | 61797318.92 | 0.183030E+10 | 0.00 | 0.00 |
October | 0.538144E+10 | 0.497199E+09 | 0.255793E+10 | 0.407842E+09 | 0.215009E+10 | 0.00 | 0.00 |
November | 0.660337E+10 | 0.610567E+09 | 0.321886E+10 | 0.982030E+09 | 0.223683E+10 | 0.00 | 0.00 |
December | 0.812206E+10 | 0.981493E+09 | 0.408591E+10 | 0.173839E+10 | 0.234752E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.664860E+11 | 0.561886E+10 | 0.301082E+11 | 0.623953E+10 | 0.238687E+11 | 0.00 | 0.00 |
Minimum of Months | 0.396938E+10 | 0.138436E+09 | 0.170423E+10 | 0.00 | 0.170423E+10 | 0.00 | 0.00 |
Maximum of Months | 0.825667E+10 | 0.981493E+09 | 0.408800E+10 | 0.173839E+10 | 0.238244E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.405305E+10 | 0.614117E+09 | 0.201108E+10 | 0.707162E+09 | 0.130392E+10 | 0.00 | 0.00 |
February | 0.410861E+10 | 0.449665E+09 | 0.199500E+10 | 0.705983E+09 | 0.128901E+10 | 0.00 | 0.00 |
March | 0.519631E+10 | 0.376978E+09 | 0.247584E+10 | 0.977909E+09 | 0.149793E+10 | 0.00 | 0.00 |
April | 0.510723E+10 | 0.181660E+09 | 0.240782E+10 | 0.922232E+09 | 0.148559E+10 | 0.00 | 0.00 |
May | 0.468252E+10 | 0.178873E+09 | 0.211708E+10 | 0.627195E+09 | 0.148989E+10 | 0.00 | 0.00 |
June | 0.484070E+10 | 0.196562E+09 | 0.222012E+10 | 0.765224E+09 | 0.145490E+10 | 0.00 | 0.00 |
July | 0.402118E+10 | 0.348668E+09 | 0.195586E+10 | 0.461237E+09 | 0.149462E+10 | 0.00 | 0.00 |
August | 0.429626E+10 | 0.288932E+09 | 0.212641E+10 | 0.629723E+09 | 0.149669E+10 | 0.00 | 0.00 |
September | 0.401109E+10 | 0.277103E+09 | 0.192745E+10 | 0.534589E+09 | 0.139286E+10 | 0.00 | 0.00 |
October | 0.371806E+10 | 0.367770E+09 | 0.187059E+10 | 0.482199E+09 | 0.138840E+10 | 0.00 | 0.00 |
November | 0.353878E+10 | 0.426682E+09 | 0.176536E+10 | 0.481468E+09 | 0.128389E+10 | 0.00 | 0.00 |
December | 0.374063E+10 | 0.687313E+09 | 0.186693E+10 | 0.610708E+09 | 0.125623E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.513144E+11 | 0.439432E+10 | 0.247396E+11 | 0.790563E+10 | 0.168339E+11 | 0.00 | 0.00 |
Minimum of Months | 0.353878E+10 | 0.178873E+09 | 0.176536E+10 | 0.461237E+09 | 0.125623E+10 | 0.00 | 0.00 |
Maximum of Months | 0.519631E+10 | 0.687313E+09 | 0.247584E+10 | 0.977909E+09 | 0.149793E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.243168E+11 | -0.232987E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101804E+10 | 58.99 | 0.00 | 0.00 |
February | 0.219585E+11 | -0.210388E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -919642423.3 | 58.97 | 0.00 | 0.00 |
March | 0.253794E+11 | -0.243576E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102173E+10 | 58.97 | 0.00 | 0.00 |
April | 0.225890E+11 | -0.216038E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985224814.2 | 58.96 | 0.00 | 0.00 |
May | 0.235873E+11 | -0.225677E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101962E+10 | 58.97 | 0.00 | 0.00 |
June | 0.230256E+11 | -0.220374E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988129490.7 | 58.97 | 0.00 | 0.00 |
July | 0.218627E+11 | -0.208465E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101617E+10 | 58.97 | 0.00 | 0.00 |
August | 0.240026E+11 | -0.229816E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102101E+10 | 58.97 | 0.00 | 0.00 |
September | 0.221953E+11 | -0.212096E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985749791.8 | 58.97 | 0.00 | 0.00 |
October | 0.233906E+11 | -0.223731E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101749E+10 | 58.97 | 0.00 | 0.00 |
November | 0.234117E+11 | -0.224273E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -984399836.7 | 58.97 | 0.00 | 0.00 |
December | 0.236681E+11 | -0.226516E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101654E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.279388E+12 | -0.267394E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.119937E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.218627E+11 | -0.243576E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102173E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.253794E+11 | -0.208465E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -919642423.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-07:00 | 1870.45 | 24.46 | 147.00 | 320.00 | 835.55 | 20.94 | 211.67 | 289.17 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-07:19 | 1454.83 | 17.73 | 0.00 | 290.83 | 745.88 | 20.60 | 144.00 | 262.67 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:49 | 1094.36 | 17.33 | 0.00 | 319.50 | 599.95 | 20.18 | 42.00 | 285.83 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:19 | 896.98 | 16.81 | 0.00 | 313.00 | 504.53 | 19.73 | 0.00 | 267.83 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-07:10 | 772.48 | 15.74 | 0.00 | 317.83 | 424.21 | 18.58 | 0.00 | 257.00 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-07:00 | 749.48 | 15.81 | 0.00 | 310.33 | 427.41 | 18.76 | 0.00 | 252.33 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-07:30 | 735.03 | 15.33 | 0.00 | 315.67 | 392.64 | 18.11 | 0.00 | 248.33 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-07:10 | 865.35 | 16.29 | 0.00 | 318.00 | 466.53 | 19.13 | 0.00 | 265.50 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:00 | 982.88 | 16.30 | 0.00 | 304.17 | 506.58 | 19.06 | 9.00 | 258.17 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-07:10 | 1276.17 | 17.92 | 15.00 | 317.17 | 632.44 | 20.35 | 103.50 | 270.33 |
November | 337.67 | 0.50 | 0.48 | 01-NOV-07:10 | 1616.15 | 22.67 | 112.67 | 306.50 | 769.67 | 22.22 | 226.33 | 273.50 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-06:49 | 1866.61 | 23.69 | 136.17 | 314.17 | 871.88 | 22.93 | 251.83 | 290.67 |
Annual Sum or Average | 4292.33 | 0.51 | 1168.21 | 18.26 | 410.83 | 3747.17 | 592.26 | 20.00 | 988.33 | 3221.33 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 735.03 | 15.33 | 0.00 | 290.83 | 392.64 | 18.11 | 0.00 | 248.33 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 1870.45 | 24.46 | 147.00 | 320.00 | 871.88 | 22.93 | 251.83 | 290.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-07:19 | 1553.71 | 19.62 | 87.83 | 295.83 | 815.75 | 22.73 | 126.33 | 253.33 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-06:49 | 1725.77 | 19.60 | 79.33 | 276.50 | 909.43 | 22.90 | 103.33 | 242.83 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:10 | 1951.24 | 19.50 | 87.83 | 311.17 | 791.65 | 21.73 | 92.00 | 276.33 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:19 | 1625.78 | 19.83 | 84.00 | 317.00 | 828.05 | 21.70 | 91.33 | 276.67 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-05:00 | 1404.68 | 19.15 | 87.00 | 324.17 | 703.41 | 20.99 | 86.33 | 273.17 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-06:49 | 1498.80 | 19.50 | 84.00 | 322.00 | 758.60 | 21.39 | 105.00 | 278.17 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-06:30 | 1251.76 | 18.90 | 86.50 | 323.50 | 619.18 | 20.67 | 97.33 | 265.33 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-05:00 | 1424.15 | 19.50 | 86.00 | 324.50 | 715.57 | 21.29 | 98.00 | 274.67 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:10 | 1340.00 | 18.93 | 83.50 | 303.33 | 668.29 | 20.62 | 88.17 | 253.67 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-06:10 | 1345.74 | 19.44 | 86.17 | 304.67 | 666.67 | 21.10 | 100.50 | 255.33 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-06:40 | 1350.34 | 19.78 | 81.33 | 286.50 | 661.56 | 21.41 | 108.00 | 239.67 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-06:40 | 1501.67 | 19.36 | 87.83 | 287.17 | 683.54 | 21.69 | 114.17 | 246.50 |
Annual Sum or Average | 4292.33 | 0.52 | 1494.80 | 19.42 | 1021.33 | 3676.33 | 733.23 | 21.50 | 1210.50 | 3135.67 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1251.76 | 18.90 | 79.33 | 276.50 | 619.18 | 20.62 | 86.33 | 239.67 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 1951.24 | 19.83 | 87.83 | 324.50 | 909.43 | 22.90 | 126.33 | 278.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.54 | 0.48 | 01-JAN-09:09 | 610.42 | 14.70 | 0.00 | 284.83 | 359.20 | 17.65 | 0.00 | 205.17 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-08:09 | 671.60 | 15.22 | 0.00 | 271.33 | 396.69 | 18.15 | 0.00 | 214.83 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:20 | 766.15 | 16.18 | 0.00 | 315.00 | 451.81 | 19.09 | 0.00 | 269.33 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:00 | 941.77 | 17.29 | 0.00 | 324.50 | 528.09 | 20.16 | 0.00 | 283.83 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-06:19 | 1106.55 | 17.33 | 3.33 | 341.33 | 567.86 | 20.11 | 72.83 | 303.33 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:30 | 1320.36 | 21.50 | 101.83 | 340.67 | 658.27 | 22.04 | 160.33 | 311.17 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:49 | 1148.94 | 20.35 | 93.00 | 341.67 | 563.33 | 22.19 | 93.33 | 302.83 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-06:30 | 1022.62 | 17.17 | 0.00 | 332.17 | 539.45 | 19.99 | 25.50 | 291.67 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:00 | 832.53 | 15.90 | 0.00 | 306.17 | 443.06 | 18.65 | 0.00 | 254.17 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-07:49 | 735.29 | 15.60 | 0.00 | 299.50 | 398.06 | 18.39 | 0.00 | 235.00 |
November | 337.67 | 0.53 | 0.48 | 01-NOV-07:00 | 655.58 | 15.17 | 0.00 | 276.50 | 365.53 | 18.01 | 0.00 | 202.00 |
December | 349.33 | 0.54 | 0.48 | 01-DEC-07:49 | 595.67 | 14.50 | 0.00 | 277.50 | 345.70 | 17.43 | 0.00 | 195.83 |
Annual Sum or Average | 4292.33 | 0.52 | 875.33 | 16.81 | 198.17 | 3711.17 | 471.36 | 19.38 | 352.00 | 3069.17 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 595.67 | 14.50 | 0.00 | 271.33 | 345.70 | 17.43 | 0.00 | 195.83 | |
Maximum of Months | 383.17 | 0.54 | 0.48 | 1320.36 | 21.50 | 101.83 | 341.67 | 658.27 | 22.19 | 160.33 | 311.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-09:30 | 1595.85 | 19.58 | 87.33 | 294.50 | 842.78 | 22.89 | 117.83 | 254.00 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-08:30 | 1790.19 | 19.43 | 79.33 | 271.67 | 739.67 | 21.50 | 99.50 | 237.50 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-08:50 | 1987.66 | 19.44 | 87.83 | 318.83 | 807.46 | 21.42 | 88.83 | 276.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:49 | 1926.56 | 15.39 | 0.00 | 315.17 | 797.86 | 19.27 | 41.00 | 275.50 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-07:30 | 1543.20 | 15.18 | 0.00 | 323.50 | 674.27 | 18.75 | 48.33 | 272.67 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-08:30 | 1763.56 | 15.54 | 0.00 | 320.17 | 740.86 | 19.26 | 55.33 | 277.83 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-07:00 | 1264.16 | 15.01 | 0.00 | 323.00 | 618.79 | 18.44 | 33.67 | 267.67 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-07:40 | 1657.18 | 15.75 | 8.50 | 322.67 | 700.65 | 18.96 | 48.83 | 273.83 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-07:49 | 1456.66 | 18.53 | 85.00 | 301.33 | 648.73 | 18.73 | 35.33 | 254.17 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-08:30 | 1397.20 | 19.34 | 87.17 | 303.83 | 707.33 | 22.16 | 104.83 | 255.67 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-08:30 | 1387.28 | 19.83 | 85.00 | 288.00 | 689.85 | 21.46 | 106.67 | 240.50 |
December | 349.33 | 0.52 | 0.48 | 01-DEC-07:00 | 1440.35 | 19.61 | 87.33 | 294.33 | 730.88 | 21.43 | 105.83 | 248.33 |
Annual Sum or Average | 4292.33 | 0.52 | 1599.31 | 17.65 | 607.50 | 3677.00 | 723.97 | 20.31 | 886.00 | 3134.17 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1264.16 | 15.01 | 0.00 | 271.67 | 618.79 | 18.44 | 33.67 | 237.50 | |
Maximum of Months | 383.17 | 0.52 | 0.48 | 1987.66 | 19.83 | 87.83 | 323.50 | 842.78 | 22.89 | 117.83 | 277.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.50 | 0.48 | 01-JAN-07:49 | 1835.26 | 20.57 | 146.67 | 319.50 | 911.18 | 21.03 | 88.50 | 305.33 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-07:10 | 1426.67 | 11.73 | 0.00 | 290.50 | 767.96 | 16.59 | 0.00 | 263.83 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:49 | 1073.14 | 11.98 | 0.00 | 319.00 | 616.81 | 16.72 | 0.00 | 288.33 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:19 | 879.21 | 11.63 | 0.00 | 310.17 | 518.29 | 16.40 | 0.00 | 269.33 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-07:10 | 756.85 | 10.17 | 0.00 | 315.67 | 436.18 | 14.83 | 0.00 | 261.17 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-07:00 | 734.69 | 10.46 | 0.00 | 308.17 | 439.20 | 15.24 | 0.00 | 256.83 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-07:30 | 720.47 | 9.49 | 0.00 | 313.83 | 404.04 | 14.15 | 0.00 | 252.33 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-07:10 | 847.12 | 10.77 | 0.00 | 316.50 | 479.37 | 15.44 | 0.00 | 268.67 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:00 | 960.27 | 10.60 | 0.00 | 302.83 | 520.21 | 15.15 | 0.00 | 261.33 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-06:00 | 1243.61 | 11.95 | 13.00 | 314.33 | 649.09 | 16.18 | 4.50 | 271.67 |
November | 337.67 | 0.50 | 0.48 | 01-NOV-07:10 | 1571.24 | 17.56 | 101.17 | 304.17 | 790.80 | 18.46 | 39.83 | 275.33 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-06:40 | 1825.96 | 19.39 | 133.67 | 313.00 | 911.06 | 20.92 | 87.50 | 298.50 |
Annual Sum or Average | 4292.33 | 0.51 | 1143.00 | 12.94 | 394.50 | 3727.67 | 614.22 | 16.71 | 220.33 | 3272.67 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 720.47 | 9.49 | 0.00 | 290.50 | 404.04 | 14.15 | 0.00 | 252.33 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 1835.26 | 20.57 | 146.67 | 319.50 | 911.18 | 21.03 | 88.50 | 305.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-07:19 | 1546.71 | 16.70 | 87.83 | 295.33 | 834.53 | 20.67 | 77.50 | 256.67 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-06:49 | 1732.08 | 16.64 | 79.33 | 275.67 | 929.87 | 20.79 | 71.17 | 245.50 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:10 | 1936.50 | 16.37 | 87.83 | 310.17 | 814.59 | 19.22 | 52.17 | 278.17 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:19 | 1507.07 | 14.39 | 55.00 | 316.00 | 851.22 | 19.19 | 54.17 | 279.67 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-05:00 | 1403.00 | 15.91 | 86.67 | 324.00 | 722.19 | 18.43 | 56.67 | 277.17 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-06:49 | 1506.23 | 16.30 | 84.00 | 320.83 | 778.05 | 18.90 | 54.50 | 281.33 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-06:30 | 1248.74 | 15.43 | 84.33 | 323.00 | 636.40 | 18.10 | 56.17 | 270.50 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-05:00 | 1349.52 | 14.11 | 56.83 | 323.00 | 735.47 | 18.76 | 55.00 | 278.50 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:10 | 1268.06 | 13.78 | 57.83 | 302.00 | 686.04 | 18.13 | 54.50 | 257.17 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-06:10 | 1334.69 | 15.98 | 82.17 | 303.67 | 684.92 | 18.62 | 55.17 | 259.00 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-06:40 | 1292.80 | 14.75 | 58.33 | 284.33 | 678.63 | 19.01 | 51.33 | 242.33 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-06:40 | 1492.41 | 16.40 | 87.83 | 286.17 | 701.09 | 19.41 | 56.00 | 249.83 |
Annual Sum or Average | 4292.33 | 0.52 | 1465.16 | 15.56 | 908.00 | 3664.17 | 752.50 | 19.08 | 694.33 | 3175.83 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1248.74 | 13.78 | 55.00 | 275.67 | 636.40 | 18.10 | 51.33 | 242.33 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 1936.50 | 16.70 | 87.83 | 324.00 | 929.87 | 20.79 | 77.50 | 281.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.54 | 0.48 | 01-JAN-08:00 | 598.77 | 9.48 | 0.00 | 282.50 | 369.16 | 14.22 | 0.00 | 211.33 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-07:00 | 659.44 | 10.15 | 0.00 | 269.67 | 407.88 | 14.87 | 0.00 | 218.33 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:09 | 752.33 | 11.21 | 0.00 | 313.17 | 464.49 | 15.97 | 0.00 | 272.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:00 | 923.42 | 12.09 | 0.00 | 323.17 | 542.40 | 16.92 | 0.00 | 286.67 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-06:19 | 1083.13 | 11.47 | 3.33 | 341.00 | 583.23 | 16.10 | 1.17 | 305.83 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:30 | 1294.29 | 17.20 | 99.50 | 339.50 | 676.04 | 18.41 | 33.17 | 312.17 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:49 | 1123.54 | 15.82 | 92.33 | 340.17 | 578.44 | 18.70 | 59.17 | 304.83 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-06:19 | 1000.40 | 11.50 | 0.00 | 331.17 | 553.89 | 16.23 | 0.00 | 294.67 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:00 | 815.00 | 10.33 | 0.00 | 303.17 | 455.32 | 14.90 | 0.00 | 258.33 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-07:49 | 720.54 | 9.92 | 0.00 | 297.33 | 409.29 | 14.59 | 0.00 | 238.17 |
November | 337.67 | 0.53 | 0.48 | 01-NOV-07:49 | 642.86 | 9.57 | 0.00 | 274.50 | 375.82 | 14.29 | 0.00 | 207.17 |
December | 349.33 | 0.54 | 0.48 | 01-DEC-07:40 | 583.96 | 9.16 | 0.00 | 275.83 | 355.23 | 13.86 | 0.00 | 202.17 |
Annual Sum or Average | 4292.33 | 0.52 | 857.65 | 11.56 | 195.17 | 3691.17 | 484.29 | 15.80 | 93.50 | 3112.33 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 583.96 | 9.16 | 0.00 | 269.67 | 355.23 | 13.86 | 0.00 | 202.17 | |
Maximum of Months | 383.17 | 0.54 | 0.48 | 1294.29 | 17.20 | 99.50 | 341.00 | 676.04 | 18.70 | 59.17 | 312.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-09:30 | 1589.33 | 16.65 | 87.33 | 294.00 | 861.73 | 20.83 | 77.50 | 258.00 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-08:20 | 1794.73 | 16.46 | 79.33 | 271.33 | 759.95 | 19.12 | 46.67 | 240.50 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-08:39 | 1972.68 | 16.39 | 87.83 | 317.00 | 830.32 | 18.95 | 50.67 | 280.17 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:40 | 1901.68 | 11.01 | 0.00 | 314.33 | 820.81 | 16.16 | 0.00 | 279.00 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-07:30 | 1538.36 | 10.82 | 0.00 | 323.00 | 692.86 | 15.64 | 0.00 | 276.00 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-08:30 | 1700.83 | 11.24 | 0.00 | 319.50 | 760.28 | 16.22 | 0.00 | 280.33 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-07:00 | 1262.67 | 10.61 | 0.00 | 322.50 | 636.18 | 15.33 | 0.00 | 272.33 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-07:40 | 1595.00 | 11.50 | 8.50 | 321.67 | 720.27 | 15.86 | 0.00 | 277.17 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-07:40 | 1438.61 | 15.32 | 85.00 | 299.17 | 663.42 | 15.49 | 5.50 | 257.83 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-08:20 | 1393.03 | 16.12 | 87.17 | 302.83 | 709.60 | 18.57 | 56.50 | 256.00 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-08:20 | 1382.40 | 16.73 | 85.00 | 286.83 | 707.21 | 19.06 | 55.00 | 243.33 |
December | 349.33 | 0.52 | 0.48 | 01-DEC-07:00 | 1431.17 | 16.70 | 87.17 | 292.67 | 744.79 | 18.94 | 56.33 | 251.33 |
Annual Sum or Average | 4292.33 | 0.52 | 1581.48 | 14.04 | 607.33 | 3664.83 | 741.33 | 17.46 | 348.17 | 3172.00 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1262.67 | 10.61 | 0.00 | 271.33 | 636.18 | 15.33 | 0.00 | 240.50 | |
Maximum of Months | 383.17 | 0.52 | 0.48 | 1972.68 | 16.73 | 87.83 | 323.00 | 861.73 | 20.83 | 77.50 | 280.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.50 | 0.48 | 01-JAN-07:49 | 1836.13 | 20.54 | 146.67 | 319.50 | 912.36 | 21.02 | 88.33 | 305.33 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-07:10 | 1427.47 | 11.69 | 0.00 | 290.50 | 768.96 | 16.57 | 0.00 | 263.83 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:49 | 1073.60 | 11.94 | 0.00 | 319.00 | 617.51 | 16.70 | 0.00 | 288.33 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:19 | 879.48 | 11.59 | 0.00 | 310.17 | 518.84 | 16.38 | 0.00 | 269.83 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-07:10 | 757.19 | 10.13 | 0.00 | 315.67 | 436.69 | 14.81 | 0.00 | 261.33 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-07:00 | 734.87 | 10.41 | 0.00 | 308.17 | 439.66 | 15.22 | 0.00 | 256.83 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-07:30 | 720.90 | 9.45 | 0.00 | 313.83 | 404.55 | 14.13 | 0.00 | 252.33 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-07:10 | 847.56 | 10.73 | 0.00 | 316.50 | 479.95 | 15.42 | 0.00 | 268.83 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:00 | 960.94 | 10.56 | 0.00 | 302.83 | 520.92 | 15.13 | 0.00 | 261.67 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-06:00 | 1244.55 | 11.91 | 13.00 | 314.33 | 650.06 | 16.16 | 4.50 | 271.83 |
November | 337.67 | 0.50 | 0.48 | 01-NOV-07:10 | 1572.27 | 17.53 | 101.17 | 304.17 | 791.98 | 18.45 | 39.83 | 275.50 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-06:40 | 1826.82 | 19.36 | 133.67 | 313.00 | 912.27 | 20.91 | 87.50 | 298.83 |
Annual Sum or Average | 4292.33 | 0.51 | 1143.60 | 12.91 | 394.50 | 3727.67 | 615.01 | 16.69 | 220.17 | 3274.50 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 720.90 | 9.45 | 0.00 | 290.50 | 404.55 | 14.13 | 0.00 | 252.33 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 1836.13 | 20.54 | 146.67 | 319.50 | 912.36 | 21.02 | 88.33 | 305.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-07:19 | 1546.74 | 16.66 | 87.83 | 295.33 | 835.29 | 20.66 | 77.50 | 256.83 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-06:49 | 1732.22 | 16.61 | 79.33 | 275.67 | 930.65 | 20.77 | 71.17 | 245.50 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:10 | 1936.60 | 16.33 | 87.83 | 310.00 | 815.38 | 19.21 | 52.17 | 278.17 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:19 | 1507.19 | 14.35 | 55.00 | 316.00 | 852.02 | 19.17 | 54.17 | 279.83 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-05:00 | 1403.36 | 15.87 | 86.67 | 324.00 | 722.98 | 18.42 | 56.67 | 277.17 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-06:49 | 1506.47 | 16.26 | 84.00 | 321.00 | 778.87 | 18.89 | 54.50 | 281.33 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-06:30 | 1249.28 | 15.40 | 84.33 | 323.00 | 637.21 | 18.09 | 56.17 | 270.50 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-05:00 | 1349.95 | 14.07 | 56.83 | 323.00 | 736.32 | 18.74 | 55.00 | 278.50 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:10 | 1264.42 | 13.51 | 55.00 | 301.83 | 686.86 | 18.12 | 54.50 | 257.17 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-06:10 | 1284.37 | 14.01 | 56.33 | 303.17 | 685.78 | 18.61 | 55.17 | 259.00 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-06:40 | 1293.04 | 14.71 | 58.33 | 284.33 | 679.46 | 19.00 | 51.33 | 242.50 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-06:40 | 1492.49 | 16.36 | 87.83 | 286.17 | 701.84 | 19.40 | 56.00 | 250.17 |
Annual Sum or Average | 4292.33 | 0.52 | 1460.87 | 15.34 | 879.33 | 3663.50 | 753.31 | 19.06 | 694.33 | 3176.67 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1249.28 | 13.51 | 55.00 | 275.67 | 637.21 | 18.09 | 51.33 | 242.50 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 1936.60 | 16.66 | 87.83 | 324.00 | 930.65 | 20.77 | 77.50 | 281.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.54 | 0.48 | 01-JAN-08:00 | 598.80 | 9.44 | 0.00 | 282.50 | 369.51 | 14.20 | 0.00 | 211.50 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-07:00 | 659.49 | 10.11 | 0.00 | 269.67 | 408.26 | 14.85 | 0.00 | 218.67 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:09 | 752.39 | 11.16 | 0.00 | 313.17 | 464.92 | 15.95 | 0.00 | 272.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:00 | 923.68 | 12.05 | 0.00 | 323.17 | 542.98 | 16.90 | 0.00 | 286.83 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-06:19 | 1078.92 | 11.44 | 3.33 | 339.50 | 584.00 | 16.08 | 1.17 | 305.83 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:30 | 1294.94 | 17.17 | 99.50 | 339.50 | 676.90 | 18.40 | 33.17 | 312.17 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:49 | 1124.35 | 15.79 | 92.33 | 340.17 | 579.27 | 18.68 | 59.17 | 305.00 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-06:19 | 1000.97 | 11.46 | 0.00 | 331.17 | 554.61 | 16.21 | 0.00 | 294.67 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:00 | 815.44 | 10.29 | 0.00 | 303.17 | 455.90 | 14.88 | 0.00 | 258.33 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-07:49 | 720.86 | 9.88 | 0.00 | 297.33 | 409.81 | 14.57 | 0.00 | 238.33 |
November | 337.67 | 0.53 | 0.48 | 01-NOV-07:49 | 643.05 | 9.53 | 0.00 | 274.50 | 376.26 | 14.27 | 0.00 | 207.33 |
December | 349.33 | 0.54 | 0.48 | 01-DEC-07:40 | 584.02 | 9.12 | 0.00 | 275.83 | 355.60 | 13.84 | 0.00 | 202.33 |
Annual Sum or Average | 4292.33 | 0.52 | 857.57 | 11.52 | 195.17 | 3689.67 | 484.86 | 15.79 | 93.50 | 3113.67 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 584.02 | 9.12 | 0.00 | 269.67 | 355.60 | 13.84 | 0.00 | 202.33 | |
Maximum of Months | 383.17 | 0.54 | 0.48 | 1294.94 | 17.17 | 99.50 | 340.17 | 676.90 | 18.68 | 59.17 | 312.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-09:30 | 1589.35 | 16.61 | 87.33 | 294.00 | 862.48 | 20.81 | 77.50 | 258.00 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-08:20 | 1794.83 | 16.42 | 79.33 | 271.33 | 760.73 | 19.10 | 46.67 | 240.50 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-08:39 | 1972.76 | 16.35 | 87.83 | 317.00 | 831.10 | 18.93 | 50.67 | 280.17 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:40 | 1901.81 | 10.96 | 0.00 | 314.33 | 821.61 | 16.14 | 0.00 | 279.00 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-07:30 | 1538.76 | 10.77 | 0.00 | 323.00 | 693.67 | 15.62 | 0.00 | 276.00 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-08:30 | 1701.02 | 11.20 | 0.00 | 319.50 | 761.07 | 16.20 | 0.00 | 280.33 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-07:00 | 1263.19 | 10.56 | 0.00 | 322.67 | 636.98 | 15.31 | 0.00 | 272.33 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-07:40 | 1595.41 | 11.45 | 8.50 | 321.67 | 721.12 | 15.84 | 0.00 | 277.50 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-07:40 | 1439.10 | 15.29 | 85.00 | 299.00 | 664.23 | 15.48 | 5.50 | 257.83 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-08:20 | 1393.49 | 16.08 | 87.17 | 303.17 | 710.44 | 18.55 | 56.50 | 256.00 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-08:20 | 1382.63 | 16.69 | 85.00 | 286.83 | 708.04 | 19.04 | 55.00 | 243.33 |
December | 349.33 | 0.52 | 0.48 | 01-DEC-07:00 | 1431.22 | 16.66 | 87.17 | 292.67 | 745.52 | 18.92 | 56.33 | 251.33 |
Annual Sum or Average | 4292.33 | 0.52 | 1581.74 | 14.00 | 607.33 | 3665.17 | 742.13 | 17.44 | 348.17 | 3172.33 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1263.19 | 10.56 | 0.00 | 271.33 | 636.98 | 15.31 | 0.00 | 240.50 | |
Maximum of Months | 383.17 | 0.52 | 0.48 | 1972.76 | 16.69 | 87.83 | 323.00 | 862.48 | 20.81 | 77.50 | 280.33 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.151427E+12 | 0.114990E+12 | 236835.24 | 02-JAN-04:02 | 147563.85 | 0.70 |
February | 0.00 | 0.00 | 0.153950E+12 | 0.116973E+12 | 224098.84 | 16-FEB-06:02 | 137103.18 | 0.81 |
March | 0.00 | 0.00 | 0.189252E+12 | 0.145227E+12 | 229173.69 | 13-MAR-05:02 | 141783.84 | 0.87 |
April | 0.00 | 0.00 | 0.194712E+12 | 0.144194E+12 | 234574.02 | 24-APR-05:03 | 141367.30 | 0.88 |
May | 0.00 | 0.00 | 0.188452E+12 | 0.129258E+12 | 241559.61 | 16-MAY-03:02 | 139069.48 | 0.78 |
June | 0.00 | 0.00 | 0.199860E+12 | 0.137055E+12 | 227255.55 | 14-JUN-05:02 | 144449.59 | 0.84 |
July | 0.00 | 0.00 | 0.191014E+12 | 0.134864E+12 | 233761.10 | 24-JUL-04:23 | 143293.62 | 0.85 |
August | 0.00 | 0.00 | 0.214379E+12 | 0.146499E+12 | 242725.38 | 07-AUG-05:03 | 134899.51 | 0.88 |
September | 0.00 | 0.00 | 0.167500E+12 | 0.114701E+12 | 239502.35 | 23-SEP-05:02 | 138319.91 | 0.74 |
October | 0.00 | 0.00 | 0.181851E+12 | 0.122402E+12 | 236127.66 | 20-OCT-05:02 | 137282.99 | 0.78 |
November | 0.00 | 0.00 | 0.183393E+12 | 0.127909E+12 | 234668.66 | 13-NOV-06:02 | 141852.81 | 0.83 |
December | 0.00 | 0.00 | 0.184583E+12 | 0.132749E+12 | 229184.15 | 09-DEC-06:03 | 135315.47 | 0.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.220037E+13 | 0.156682E+13 | 0.82 | |||
Minimum of Months | 0.00 | 0.00 | 0.151427E+12 | 0.114701E+12 | 224098.84 | 134899.51 | 0.70 | |
Maximum of Months | 0.00 | 0.00 | 0.214379E+12 | 0.146499E+12 | 242725.38 | 147563.85 | 0.88 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.129243E+13 | 0.966067E+12 | 2327591.76 | 02-JAN-04:02 | 1382635.26 | 0.64 |
February | 0.00 | 0.00 | 0.122018E+13 | 0.917183E+12 | 2146886.69 | 16-FEB-06:02 | 1266729.47 | 0.66 |
March | 0.00 | 0.00 | 0.145098E+13 | 0.109090E+13 | 2259834.68 | 25-MAR-05:03 | 1286310.75 | 0.71 |
April | 0.00 | 0.00 | 0.146821E+13 | 0.104329E+13 | 2261148.54 | 14-APR-05:03 | 1298958.05 | 0.72 |
May | 0.00 | 0.00 | 0.162371E+13 | 0.107694E+13 | 2339099.99 | 16-MAY-05:03 | 1278962.32 | 0.70 |
June | 0.00 | 0.00 | 0.165051E+13 | 0.109451E+13 | 2282675.57 | 05-JUN-03:02 | 1267672.96 | 0.72 |
July | 0.00 | 0.00 | 0.139514E+13 | 0.967836E+12 | 2248720.85 | 27-JUL-05:03 | 1295899.61 | 0.66 |
August | 0.00 | 0.00 | 0.154845E+13 | 0.102570E+13 | 2294483.33 | 05-AUG-05:03 | 1271429.08 | 0.67 |
September | 0.00 | 0.00 | 0.141743E+13 | 0.945083E+12 | 2329593.37 | 18-SEP-03:02 | 1303450.64 | 0.66 |
October | 0.00 | 0.00 | 0.141216E+13 | 0.935377E+12 | 2285727.77 | 03-OCT-03:02 | 1315509.50 | 0.64 |
November | 0.00 | 0.00 | 0.133898E+13 | 0.929749E+12 | 2291303.09 | 13-NOV-04:02 | 1330502.02 | 0.64 |
December | 0.00 | 0.00 | 0.127122E+13 | 0.921233E+12 | 2206249.23 | 09-DEC-06:03 | 1279816.83 | 0.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.170894E+14 | 0.119139E+14 | 0.67 | |||
Minimum of Months | 0.00 | 0.00 | 0.122018E+13 | 0.917183E+12 | 2146886.69 | 1266729.47 | 0.63 | |
Maximum of Months | 0.00 | 0.00 | 0.165051E+13 | 0.109451E+13 | 2339099.99 | 1382635.26 | 0.72 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.142059E+12 | 0.109392E+12 | 243770.73 | 02-JAN-04:02 | 145782.28 | 0.65 |
February | 0.00 | 0.00 | 0.137586E+12 | 0.106975E+12 | 228477.45 | 06-FEB-04:02 | 139602.49 | 0.67 |
March | 0.00 | 0.00 | 0.167629E+12 | 0.130572E+12 | 236361.48 | 25-MAR-05:03 | 136140.86 | 0.72 |
April | 0.00 | 0.00 | 0.171820E+12 | 0.127345E+12 | 237150.86 | 14-APR-05:03 | 138584.53 | 0.75 |
May | 0.00 | 0.00 | 0.186456E+12 | 0.129820E+12 | 258428.97 | 22-MAY-03:02 | 148254.75 | 0.72 |
June | 0.00 | 0.00 | 0.189425E+12 | 0.132099E+12 | 264150.84 | 28-JUN-03:02 | 147110.71 | 0.74 |
July | 0.00 | 0.00 | 0.159936E+12 | 0.114549E+12 | 247219.40 | 27-JUL-03:02 | 145688.73 | 0.69 |
August | 0.00 | 0.00 | 0.173731E+12 | 0.119463E+12 | 262554.50 | 03-AUG-03:02 | 147435.25 | 0.69 |
September | 0.00 | 0.00 | 0.161667E+12 | 0.111956E+12 | 257752.47 | 07-SEP-03:02 | 147684.05 | 0.68 |
October | 0.00 | 0.00 | 0.156263E+12 | 0.107072E+12 | 243990.75 | 17-OCT-03:02 | 144280.50 | 0.66 |
November | 0.00 | 0.00 | 0.148466E+12 | 0.106593E+12 | 247731.79 | 13-NOV-04:02 | 145328.34 | 0.65 |
December | 0.00 | 0.00 | 0.139608E+12 | 0.104035E+12 | 231962.29 | 11-DEC-04:02 | 138513.11 | 0.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.193465E+13 | 0.139987E+13 | 0.69 | |||
Minimum of Months | 0.00 | 0.00 | 0.137586E+12 | 0.104035E+12 | 228477.45 | 136140.86 | 0.63 | |
Maximum of Months | 0.00 | 0.00 | 0.189425E+12 | 0.132099E+12 | 264150.84 | 148254.75 | 0.75 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.110132E+12 | 0.824332E+11 | 172221.01 | 09-JAN-04:02 | 74248.10 | 0.62 |
February | 0.00 | 0.00 | 0.101122E+12 | 0.755599E+11 | 177494.78 | 12-FEB-16:42 | 83554.83 | 0.62 |
March | 0.00 | 0.00 | 0.123299E+12 | 0.889803E+11 | 173744.57 | 12-MAR-16:30 | 85536.58 | 0.63 |
April | 0.00 | 0.00 | 0.130162E+12 | 0.851313E+11 | 188052.62 | 30-APR-15:29 | 81779.91 | 0.61 |
May | 0.00 | 0.00 | 0.149536E+12 | 0.892060E+11 | 201409.18 | 22-MAY-01:13 | 75800.50 | 0.63 |
June | 0.00 | 0.00 | 0.149316E+12 | 0.887476E+11 | 204410.09 | 04-JUN-14:32 | 79174.24 | 0.64 |
July | 0.00 | 0.00 | 0.124788E+12 | 0.829933E+11 | 178474.77 | 02-JUL-13:43 | 71957.14 | 0.61 |
August | 0.00 | 0.00 | 0.151754E+12 | 0.903528E+11 | 202132.97 | 13-AUG-14:22 | 79777.80 | 0.64 |
September | 0.00 | 0.00 | 0.133022E+12 | 0.811057E+11 | 193623.49 | 10-SEP-14:52 | 78061.37 | 0.62 |
October | 0.00 | 0.00 | 0.131006E+12 | 0.811440E+11 | 190043.92 | 15-OCT-16:02 | 75479.59 | 0.61 |
November | 0.00 | 0.00 | 0.121277E+12 | 0.800651E+11 | 191016.06 | 12-NOV-17:33 | 75555.82 | 0.61 |
December | 0.00 | 0.00 | 0.111420E+12 | 0.805700E+11 | 186304.16 | 10-DEC-18:10 | 76757.63 | 0.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.153683E+13 | 0.100629E+13 | 0.62 | |||
Minimum of Months | 0.00 | 0.00 | 0.101122E+12 | 0.755599E+11 | 172221.01 | 71957.14 | 0.61 | |
Maximum of Months | 0.00 | 0.00 | 0.151754E+12 | 0.903528E+11 | 204410.09 | 85536.58 | 0.64 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.684218E+10 | 0.597778E+10 | 2975.10 | 30-JAN-17:00 | 2527.33 | 0.00 |
February | 0.00 | 0.00 | 0.108640E+11 | 0.997949E+10 | 4963.87 | 13-FEB-17:00 | 4417.01 | 0.00 |
March | 0.00 | 0.00 | 0.172511E+11 | 0.161451E+11 | 8360.49 | 31-MAR-23:03 | 7740.29 | 0.00 |
April | 0.00 | 0.00 | 0.218896E+11 | 0.205304E+11 | 8850.16 | 02-APR-18:03 | 8267.67 | 0.00 |
May | 0.00 | 0.00 | 0.757906E+10 | 0.611055E+10 | 4703.58 | 31-MAY-23:10 | 3924.65 | 0.00 |
June | 0.00 | 0.00 | 0.123425E+11 | 0.107922E+11 | 6514.05 | 30-JUN-23:03 | 5788.13 | 0.00 |
July | 0.00 | 0.00 | 0.173479E+11 | 0.160661E+11 | 8359.02 | 31-JUL-23:05 | 7699.30 | 0.00 |
August | 0.00 | 0.00 | 0.226903E+11 | 0.210735E+11 | 8992.04 | 14-AUG-16:00 | 8158.71 | 0.00 |
September | 0.00 | 0.00 | 0.712111E+10 | 0.581207E+10 | 4760.99 | 30-SEP-23:03 | 3934.76 | 0.00 |
October | 0.00 | 0.00 | 0.123991E+11 | 0.109862E+11 | 6465.10 | 31-OCT-23:05 | 5785.98 | 0.00 |
November | 0.00 | 0.00 | 0.167561E+11 | 0.155040E+11 | 6921.76 | 20-NOV-17:00 | 6355.46 | 0.00 |
December | 0.00 | 0.00 | 0.221277E+11 | 0.210261E+11 | 8880.79 | 25-DEC-17:33 | 8395.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.175211E+12 | 0.160003E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.684218E+10 | 0.581207E+10 | 2975.10 | 2527.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.226903E+11 | 0.210735E+11 | 8992.04 | 8395.72 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.636550E+11 | 0.551221E+11 | 28237.90 | 30-JAN-17:00 | 23799.60 | 0.00 |
February | 0.00 | 0.00 | 0.103362E+12 | 0.945460E+11 | 47514.93 | 13-FEB-17:00 | 42069.33 | 0.00 |
March | 0.00 | 0.00 | 0.164799E+12 | 0.153750E+12 | 80961.64 | 31-MAR-23:03 | 74680.25 | 0.00 |
April | 0.00 | 0.00 | 0.209030E+12 | 0.195442E+12 | 84544.26 | 13-APR-14:50 | 77266.69 | 0.00 |
May | 0.00 | 0.00 | 0.711143E+11 | 0.565929E+11 | 45664.10 | 31-MAY-23:10 | 37598.22 | 0.00 |
June | 0.00 | 0.00 | 0.117555E+12 | 0.102110E+12 | 62331.82 | 30-JUN-23:03 | 54908.57 | 0.00 |
July | 0.00 | 0.00 | 0.165556E+12 | 0.152756E+12 | 80490.75 | 31-JUL-23:05 | 73797.18 | 0.00 |
August | 0.00 | 0.00 | 0.216932E+12 | 0.200771E+12 | 85854.25 | 14-AUG-16:00 | 77528.56 | 0.00 |
September | 0.00 | 0.00 | 0.665036E+11 | 0.535756E+11 | 46854.53 | 30-SEP-23:03 | 38387.64 | 0.00 |
October | 0.00 | 0.00 | 0.117787E+12 | 0.103716E+12 | 61905.93 | 31-OCT-23:05 | 54943.73 | 0.00 |
November | 0.00 | 0.00 | 0.159960E+12 | 0.147455E+12 | 66038.35 | 20-NOV-17:00 | 60394.43 | 0.00 |
December | 0.00 | 0.00 | 0.211304E+12 | 0.200283E+12 | 83458.05 | 10-DEC-17:20 | 77774.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.166756E+13 | 0.151612E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.636550E+11 | 0.535756E+11 | 28237.90 | 23799.60 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216932E+12 | 0.200771E+12 | 85854.25 | 77774.37 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.647071E+10 | 0.561572E+10 | 2994.40 | 16-JAN-17:40 | 2741.84 | 0.00 |
February | 0.00 | 0.00 | 0.104530E+11 | 0.957136E+10 | 4912.11 | 20-FEB-16:55 | 4545.37 | 0.00 |
March | 0.00 | 0.00 | 0.166353E+11 | 0.155310E+11 | 8120.76 | 31-MAR-23:03 | 7494.78 | 0.00 |
April | 0.00 | 0.00 | 0.210835E+11 | 0.197257E+11 | 8626.12 | 02-APR-17:55 | 8041.94 | 0.00 |
May | 0.00 | 0.00 | 0.732401E+10 | 0.586447E+10 | 4593.63 | 31-MAY-23:10 | 3792.19 | 0.00 |
June | 0.00 | 0.00 | 0.119447E+11 | 0.103986E+11 | 6188.74 | 30-JUN-23:03 | 5445.30 | 0.00 |
July | 0.00 | 0.00 | 0.167100E+11 | 0.154306E+11 | 8062.07 | 31-JUL-23:05 | 7394.04 | 0.00 |
August | 0.00 | 0.00 | 0.218226E+11 | 0.202076E+11 | 8712.79 | 14-AUG-16:00 | 7878.06 | 0.00 |
September | 0.00 | 0.00 | 0.682336E+10 | 0.552460E+10 | 4682.26 | 30-SEP-23:03 | 3849.59 | 0.00 |
October | 0.00 | 0.00 | 0.119066E+11 | 0.104992E+11 | 6180.24 | 31-OCT-23:05 | 5484.87 | 0.00 |
November | 0.00 | 0.00 | 0.160988E+11 | 0.148492E+11 | 6812.74 | 19-NOV-16:25 | 6306.65 | 0.00 |
December | 0.00 | 0.00 | 0.212182E+11 | 0.201176E+11 | 8613.59 | 25-DEC-17:33 | 8129.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.168491E+12 | 0.153336E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.647071E+10 | 0.552460E+10 | 2994.40 | 2741.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.218226E+11 | 0.202076E+11 | 8712.79 | 8129.03 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 948815.15 | 3243523.62 | 10-JAN-06:04 | 1.84 | 24659.35 | 22-JAN-07:23 |
February | 997610.90 | 3064456.81 | 16-FEB-06:02 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 1062750.02 | 2852435.86 | 02-MAR-06:03 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 1086272.41 | 3041689.58 | 10-APR-05:02 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1072802.22 | 3249673.71 | 18-MAY-05:04 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1112042.10 | 3079402.32 | 26-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1011804.92 | 3348930.27 | 18-JUL-05:04 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1055168.96 | 3088683.95 | 22-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1010698.49 | 3177539.73 | 20-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 987204.40 | 3167023.72 | 26-OCT-05:03 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 999914.69 | 3350090.74 | 13-NOV-06:04 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 960029.35 | 3258611.38 | 12-DEC-06:04 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 1025360.99 | 0.16 | ||||
Minimum of Months | 948815.15 | 2852435.86 | 0.00 | 0.00 | ||
Maximum of Months | 1112042.10 | 3350090.74 | 1.84 | 24659.35 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 744885.44 | 4406626.30 | 02-JAN-04:02 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 776580.75 | 4342124.25 | 16-FEB-06:02 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 823116.47 | 4309491.78 | 13-MAR-05:02 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 846968.78 | 4311866.33 | 10-APR-05:02 | 0.00 | 0.00 | 01-APR-00:05 |
May | 883981.56 | 4416528.18 | 17-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 921351.64 | 4365417.51 | 20-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 797869.68 | 4358283.89 | 18-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 868694.58 | 4397974.24 | 07-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 814808.67 | 4425694.06 | 21-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 797580.16 | 4361184.74 | 12-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 797797.22 | 4359795.47 | 01-NOV-05:02 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 748041.06 | 4378809.97 | 12-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 818524.08 | 0.00 | ||||
Minimum of Months | 744885.44 | 4309491.78 | 0.00 | 0.00 | ||
Maximum of Months | 921351.64 | 4425694.06 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 122544.54 | 206561.10 | 05-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 166923.80 | 252970.95 | 28-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 208756.24 | 297920.35 | 21-MAR-13:10 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 251291.25 | 320916.28 | 01-APR-14:00 | 0.00 | 0.00 | 01-APR-00:05 |
May | 153932.91 | 240417.28 | 06-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 185662.02 | 268864.37 | 13-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 197539.84 | 265606.53 | 21-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 234161.03 | 307911.51 | 13-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 137613.22 | 209978.89 | 06-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 162537.30 | 232735.04 | 04-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 191278.72 | 270442.09 | 18-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 213598.54 | 295386.63 | 08-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 185573.71 | 0.00 | ||||
Minimum of Months | 122544.54 | 206561.10 | 0.00 | 0.00 | ||
Maximum of Months | 251291.25 | 320916.28 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 10132.07 | 32670.39 | 10-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 10123.62 | 32583.75 | 01-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 10520.51 | 32255.53 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 9763.54 | 31604.92 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 9855.75 | 30978.28 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 9930.83 | 30404.84 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 9215.04 | 30119.60 | 31-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 10011.01 | 30487.13 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 9613.16 | 31055.30 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 9781.65 | 31739.71 | 30-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10081.31 | 32324.39 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 9886.20 | 32632.84 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 9908.48 | ||||
Minimum of Months | 0.00 | 0.00 | 9215.04 | 30119.60 | ||
Maximum of Months | 0.00 | 0.00 | 10520.51 | 32670.39 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1769817.09 | 5991276.34 | 12-JAN-13:20 | 3.34 | 13833.68 | 23-JAN-01:50 |
February | 1997096.57 | 6452978.73 | 14-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 2331815.72 | 6234619.32 | 27-MAR-14:10 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 2990497.53 | 6726331.26 | 21-APR-10:50 | 0.00 | 0.00 | 01-APR-00:05 |
May | 3216763.40 | 7758591.76 | 22-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 3373055.67 | 7544292.44 | 28-JUN-05:04 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 2441360.91 | 6498434.73 | 20-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 3178925.66 | 6930490.98 | 08-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 2834332.05 | 6804625.22 | 05-SEP-05:04 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 2648881.27 | 6715999.81 | 17-OCT-15:50 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 2454395.40 | 6674940.14 | 10-NOV-13:50 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 1895990.38 | 6197029.21 | 11-DEC-13:30 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 2595828.25 | 0.28 | ||||
Minimum of Months | 1769817.09 | 5991276.34 | 0.00 | 0.00 | ||
Maximum of Months | 3373055.67 | 7758591.76 | 3.34 | 13833.68 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148615E+11 | 0.89 | 8511.44 | 01-JAN-00:13 | 1.37 |
February | 0.131113E+11 | 0.87 | 8511.44 | 01-FEB-04:02 | 1.38 |
March | 0.146977E+11 | 0.88 | 8511.44 | 01-MAR-04:02 | 1.38 |
April | 0.138220E+11 | 0.86 | 8511.44 | 01-APR-03:02 | 1.38 |
May | 0.146786E+11 | 0.88 | 8511.44 | 01-MAY-00:03 | 1.36 |
June | 0.143471E+11 | 0.89 | 8511.44 | 01-JUN-03:02 | 1.38 |
July | 0.142253E+11 | 0.86 | 8511.44 | 01-JUL-03:05 | 1.37 |
August | 0.149362E+11 | 0.90 | 8511.44 | 01-AUG-03:02 | 1.38 |
September | 0.141116E+11 | 0.88 | 8511.44 | 01-SEP-03:02 | 1.38 |
October | 0.143920E+11 | 0.87 | 8511.44 | 01-OCT-15:23 | 1.37 |
November | 0.139906E+11 | 0.87 | 8511.44 | 01-NOV-03:03 | 1.38 |
December | 0.144036E+11 | 0.87 | 8511.44 | 01-DEC-04:03 | 1.38 |
Annual Sum or Average | 0.171577E+12 | 0.88 | |||
Minimum of Months | 0.131113E+11 | 0.86 | 8511.44 | 1.36 | |
Maximum of Months | 0.149362E+11 | 0.90 | 8511.44 | 1.38 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.820285E+10 | 0.51 | 18408.95 | 02-JAN-04:02 | 1.76 |
February | 0.830741E+10 | 0.58 | 18408.95 | 01-FEB-06:02 | 1.76 |
March | 0.119836E+11 | 0.69 | 18408.95 | 06-MAR-05:23 | 1.76 |
April | 0.128480E+11 | 0.73 | 18408.95 | 03-APR-05:02 | 1.76 |
May | 0.105904E+11 | 0.61 | 18408.95 | 01-MAY-05:02 | 1.76 |
June | 0.108010E+11 | 0.65 | 18408.95 | 01-JUN-05:02 | 1.76 |
July | 0.113733E+11 | 0.66 | 18408.95 | 01-JUL-05:02 | 1.76 |
August | 0.133037E+11 | 0.73 | 18408.95 | 02-AUG-05:02 | 1.76 |
September | 0.952891E+10 | 0.58 | 18408.95 | 05-SEP-04:12 | 1.76 |
October | 0.991435E+10 | 0.59 | 18408.95 | 06-OCT-05:02 | 1.76 |
November | 0.968631E+10 | 0.62 | 18408.95 | 06-NOV-06:03 | 1.76 |
December | 0.975067E+10 | 0.62 | 18408.95 | 01-DEC-06:02 | 1.76 |
Annual Sum or Average | 0.126290E+12 | 0.63 | |||
Minimum of Months | 0.820285E+10 | 0.51 | 18408.95 | 1.76 | |
Maximum of Months | 0.133037E+11 | 0.73 | 18408.95 | 1.76 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.639387E+11 | 0.45 | 169973.94 | 02-JAN-04:02 | 1.76 |
February | 0.608698E+11 | 0.47 | 169973.94 | 01-FEB-06:02 | 1.76 |
March | 0.836563E+11 | 0.54 | 169973.94 | 01-MAR-04:02 | 1.76 |
April | 0.841654E+11 | 0.55 | 169973.94 | 01-APR-05:02 | 1.76 |
May | 0.838793E+11 | 0.54 | 169973.94 | 02-MAY-05:02 | 1.76 |
June | 0.804013E+11 | 0.54 | 169973.94 | 06-JUN-05:03 | 1.76 |
July | 0.765092E+11 | 0.50 | 169973.94 | 01-JUL-05:02 | 1.76 |
August | 0.856352E+11 | 0.53 | 169973.94 | 02-AUG-05:02 | 1.76 |
September | 0.756524E+11 | 0.50 | 169973.94 | 01-SEP-05:03 | 1.76 |
October | 0.718942E+11 | 0.48 | 169973.94 | 02-OCT-03:02 | 1.76 |
November | 0.649865E+11 | 0.46 | 169973.94 | 01-NOV-05:02 | 1.76 |
December | 0.608158E+11 | 0.44 | 169973.94 | 01-DEC-06:02 | 1.76 |
Annual Sum or Average | 0.892404E+12 | 0.50 | |||
Minimum of Months | 0.608158E+11 | 0.44 | 169973.94 | 1.76 | |
Maximum of Months | 0.856352E+11 | 0.55 | 169973.94 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.740306E+10 | 0.47 | 18664.12 | 02-JAN-04:02 | 1.76 |
February | 0.736147E+10 | 0.50 | 18664.12 | 02-FEB-06:02 | 1.76 |
March | 0.103081E+11 | 0.58 | 18664.12 | 06-MAR-06:02 | 1.76 |
April | 0.103353E+11 | 0.60 | 18664.12 | 01-APR-05:02 | 1.76 |
May | 0.103333E+11 | 0.58 | 18664.12 | 01-MAY-05:02 | 1.76 |
June | 0.101886E+11 | 0.59 | 18664.12 | 01-JUN-05:02 | 1.76 |
July | 0.902272E+10 | 0.53 | 18664.12 | 01-JUL-05:02 | 1.76 |
August | 0.982745E+10 | 0.55 | 18664.12 | 02-AUG-05:02 | 1.76 |
September | 0.891811E+10 | 0.53 | 18664.12 | 05-SEP-05:02 | 1.76 |
October | 0.821853E+10 | 0.49 | 18664.12 | 02-OCT-05:03 | 1.76 |
November | 0.772009E+10 | 0.48 | 18664.12 | 01-NOV-05:02 | 1.76 |
December | 0.697226E+10 | 0.45 | 18664.12 | 01-DEC-06:02 | 1.76 |
Annual Sum or Average | 0.106609E+12 | 0.53 | |||
Minimum of Months | 0.697226E+10 | 0.45 | 18664.12 | 1.76 | |
Maximum of Months | 0.103353E+11 | 0.60 | 18664.12 | 1.76 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137456E+10 | 0.91 | 513.20 | 01-JAN-00:03 | 0.91 |
February | 0.124154E+10 | 0.91 | 513.20 | 01-FEB-00:10 | 0.91 |
March | 0.137456E+10 | 0.91 | 513.20 | 01-MAR-00:05 | 0.91 |
April | 0.133022E+10 | 0.91 | 513.20 | 01-APR-00:05 | 0.91 |
May | 0.137456E+10 | 0.91 | 513.20 | 01-MAY-00:03 | 0.91 |
June | 0.133022E+10 | 0.91 | 513.20 | 01-JUN-00:03 | 0.91 |
July | 0.137456E+10 | 0.91 | 513.20 | 01-JUL-00:10 | 0.91 |
August | 0.137456E+10 | 0.91 | 513.20 | 01-AUG-00:03 | 0.91 |
September | 0.133022E+10 | 0.91 | 513.20 | 01-SEP-00:05 | 0.91 |
October | 0.137456E+10 | 0.91 | 513.20 | 01-OCT-00:03 | 0.91 |
November | 0.133022E+10 | 0.91 | 513.20 | 01-NOV-00:05 | 0.91 |
December | 0.137456E+10 | 0.91 | 513.20 | 01-DEC-00:03 | 0.91 |
Annual Sum or Average | 0.161843E+11 | 0.91 | |||
Minimum of Months | 0.124154E+10 | 0.91 | 513.20 | 0.91 | |
Maximum of Months | 0.137456E+10 | 0.91 | 513.20 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.130568E+11 | 0.91 | 4874.85 | 01-JAN-00:03 | 0.91 |
February | 0.117932E+11 | 0.91 | 4874.85 | 01-FEB-00:10 | 0.91 |
March | 0.130568E+11 | 0.91 | 4874.85 | 01-MAR-00:05 | 0.91 |
April | 0.126356E+11 | 0.91 | 4874.85 | 01-APR-00:05 | 0.91 |
May | 0.130568E+11 | 0.91 | 4874.85 | 01-MAY-00:03 | 0.91 |
June | 0.126356E+11 | 0.91 | 4874.85 | 01-JUN-00:03 | 0.91 |
July | 0.130568E+11 | 0.91 | 4874.85 | 01-JUL-00:10 | 0.91 |
August | 0.130568E+11 | 0.91 | 4874.85 | 01-AUG-00:03 | 0.91 |
September | 0.126356E+11 | 0.91 | 4874.85 | 01-SEP-00:05 | 0.91 |
October | 0.130568E+11 | 0.91 | 4874.85 | 01-OCT-00:03 | 0.91 |
November | 0.126356E+11 | 0.91 | 4874.85 | 01-NOV-00:05 | 0.91 |
December | 0.130568E+11 | 0.91 | 4874.85 | 01-DEC-00:03 | 0.91 |
Annual Sum or Average | 0.153733E+12 | 0.91 | |||
Minimum of Months | 0.117932E+11 | 0.91 | 4874.85 | 0.91 | |
Maximum of Months | 0.130568E+11 | 0.91 | 4874.85 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.133097E+10 | 0.91 | 496.93 | 01-JAN-00:03 | 0.91 |
February | 0.120216E+10 | 0.91 | 496.93 | 01-FEB-00:10 | 0.91 |
March | 0.133097E+10 | 0.91 | 496.93 | 01-MAR-00:05 | 0.91 |
April | 0.128803E+10 | 0.91 | 496.93 | 01-APR-00:05 | 0.91 |
May | 0.133097E+10 | 0.91 | 496.93 | 01-MAY-00:03 | 0.91 |
June | 0.128803E+10 | 0.91 | 496.93 | 01-JUN-00:03 | 0.91 |
July | 0.133097E+10 | 0.91 | 496.93 | 01-JUL-00:10 | 0.91 |
August | 0.133097E+10 | 0.91 | 496.93 | 01-AUG-00:03 | 0.91 |
September | 0.128803E+10 | 0.91 | 496.93 | 01-SEP-00:05 | 0.91 |
October | 0.133097E+10 | 0.91 | 496.93 | 01-OCT-00:03 | 0.91 |
November | 0.128803E+10 | 0.91 | 496.93 | 01-NOV-00:05 | 0.91 |
December | 0.133097E+10 | 0.91 | 496.93 | 01-DEC-00:03 | 0.91 |
Annual Sum or Average | 0.156711E+11 | 0.91 | |||
Minimum of Months | 0.120216E+10 | 0.91 | 496.93 | 0.91 | |
Maximum of Months | 0.133097E+10 | 0.91 | 496.93 | 0.91 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 79.40 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 79.40 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 79.40 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 79.40 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 79.40 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 79.40 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 79.40 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 79.40 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 79.40 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 79.40 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 79.40 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 79.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.40 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.40 | 0.00 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.285899E+10 | 0.259882E+10 | 27126.55 | 02-JAN-06:02 | 24658.03 | 24658.03 | 7.80 | 132.17 |
February | 0.264037E+10 | 0.240010E+10 | 27126.55 | 01-FEB-06:02 | 24658.03 | 24658.03 | 7.82 | 132.17 |
March | 0.231356E+10 | 0.210303E+10 | 27126.55 | 13-MAR-05:02 | 24658.03 | 24658.03 | 7.54 | 132.17 |
April | 0.199534E+10 | 0.181376E+10 | 27126.55 | 13-APR-05:02 | 24658.03 | 24658.03 | 7.64 | 132.17 |
May | 0.236806E+10 | 0.215257E+10 | 27126.55 | 02-MAY-05:02 | 24658.03 | 24658.03 | 7.33 | 132.17 |
June | 0.271143E+10 | 0.246469E+10 | 27126.55 | 01-JUN-05:02 | 24658.03 | 24658.03 | 8.00 | 132.17 |
July | 0.204444E+10 | 0.185840E+10 | 27126.55 | 03-JUL-05:02 | 24658.03 | 24658.03 | 7.56 | 132.17 |
August | 0.226473E+10 | 0.205864E+10 | 27126.55 | 02-AUG-05:02 | 24658.03 | 24658.03 | 7.38 | 132.17 |
September | 0.198289E+10 | 0.180244E+10 | 27126.55 | 06-SEP-05:02 | 24658.03 | 24658.03 | 7.78 | 132.17 |
October | 0.213083E+10 | 0.193692E+10 | 27126.55 | 02-OCT-05:03 | 24658.03 | 24658.03 | 7.64 | 132.17 |
November | 0.264503E+10 | 0.240433E+10 | 27126.55 | 01-NOV-05:02 | 24658.03 | 24658.03 | 7.72 | 132.17 |
December | 0.268479E+10 | 0.244047E+10 | 27126.55 | 01-DEC-06:02 | 24658.03 | 24658.03 | 7.94 | 132.17 |
Annual Sum or Average | 0.286405E+11 | 0.260342E+11 | ||||||
Minimum of Months | 0.198289E+10 | 0.180244E+10 | 27126.55 | 24658.03 | 24658.03 | 7.33 | 132.17 | |
Maximum of Months | 0.285899E+10 | 0.259882E+10 | 27126.55 | 24658.03 | 24658.03 | 8.00 | 132.17 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.378477E+11 | 0.344035E+11 | 18670.47 | 01-JAN-00:03 | 16971.45 | 16971.45 | 7.18 | 132.17 |
February | 0.384864E+11 | 0.349841E+11 | 18670.47 | 01-FEB-00:23 | 16971.45 | 16971.45 | 7.00 | 132.17 |
March | 0.463595E+11 | 0.421408E+11 | 18670.47 | 01-MAR-00:05 | 16971.45 | 16971.45 | 7.05 | 132.17 |
April | 0.457131E+11 | 0.415532E+11 | 18670.47 | 01-APR-00:05 | 16971.45 | 16971.45 | 6.95 | 132.17 |
May | 0.421480E+11 | 0.383126E+11 | 18670.47 | 01-MAY-00:03 | 16971.45 | 16971.45 | 9.03 | 132.17 |
June | 0.433577E+11 | 0.394121E+11 | 18670.47 | 01-JUN-00:43 | 16971.45 | 16971.45 | 7.44 | 132.17 |
July | 0.455503E+11 | 0.414053E+11 | 18670.47 | 01-JUL-00:43 | 16971.45 | 16971.45 | 7.27 | 132.17 |
August | 0.462419E+11 | 0.420339E+11 | 18670.47 | 01-AUG-00:07 | 16971.45 | 16971.45 | 7.21 | 132.17 |
September | 0.387358E+11 | 0.352108E+11 | 18670.47 | 01-SEP-00:05 | 16971.45 | 16971.45 | 6.98 | 132.17 |
October | 0.418517E+11 | 0.380432E+11 | 18670.47 | 01-OCT-00:03 | 16971.45 | 16971.45 | 8.01 | 132.17 |
November | 0.428123E+11 | 0.389164E+11 | 18670.47 | 01-NOV-00:05 | 16971.45 | 16971.45 | 7.26 | 132.17 |
December | 0.456082E+11 | 0.414579E+11 | 18670.47 | 01-DEC-00:03 | 16971.45 | 16971.45 | 7.46 | 132.17 |
Annual Sum or Average | 0.514713E+12 | 0.467874E+12 | ||||||
Minimum of Months | 0.378477E+11 | 0.344035E+11 | 18670.47 | 16971.45 | 16971.45 | 6.95 | 132.17 | |
Maximum of Months | 0.463595E+11 | 0.421408E+11 | 18670.47 | 16971.45 | 16971.45 | 9.03 | 132.17 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.179489E+10 | 0.163155E+10 | 670.13 | 01-JAN-00:03 | 609.15 | 609.15 | 29.62 | 2.83 |
February | 0.162119E+10 | 0.147366E+10 | 670.13 | 01-FEB-00:10 | 609.15 | 609.15 | 33.62 | 2.83 |
March | 0.179489E+10 | 0.163155E+10 | 670.13 | 01-MAR-00:05 | 609.15 | 609.15 | 35.91 | 2.83 |
April | 0.173699E+10 | 0.157892E+10 | 670.13 | 01-APR-00:05 | 609.15 | 609.15 | 41.57 | 2.83 |
May | 0.179489E+10 | 0.163155E+10 | 670.13 | 01-MAY-00:03 | 609.15 | 609.15 | 33.29 | 2.83 |
June | 0.173699E+10 | 0.157892E+10 | 670.13 | 01-JUN-00:03 | 609.15 | 609.15 | 31.67 | 2.83 |
July | 0.179489E+10 | 0.163155E+10 | 670.13 | 01-JUL-00:10 | 609.15 | 609.15 | 35.96 | 2.83 |
August | 0.179489E+10 | 0.163155E+10 | 670.13 | 01-AUG-00:03 | 609.15 | 609.15 | 39.42 | 2.83 |
September | 0.173699E+10 | 0.157892E+10 | 670.13 | 01-SEP-00:05 | 609.15 | 609.15 | 31.01 | 2.83 |
October | 0.179489E+10 | 0.163155E+10 | 670.13 | 01-OCT-00:03 | 609.15 | 609.15 | 34.12 | 2.83 |
November | 0.173699E+10 | 0.157892E+10 | 670.13 | 01-NOV-00:05 | 609.15 | 609.15 | 35.81 | 2.83 |
December | 0.179489E+10 | 0.163155E+10 | 670.13 | 01-DEC-00:03 | 609.15 | 609.15 | 36.26 | 2.83 |
Annual Sum or Average | 0.211333E+11 | 0.192102E+11 | ||||||
Minimum of Months | 0.162119E+10 | 0.147366E+10 | 670.13 | 609.15 | 609.15 | 29.62 | 2.83 | |
Maximum of Months | 0.179489E+10 | 0.163155E+10 | 670.13 | 609.15 | 609.15 | 41.57 | 2.83 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:05 | 1.79 | 1.79 | 56.69 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:02 | 1.79 | 1.79 | 56.81 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:03 | 1.79 | 1.79 | 57.27 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:02 | 1.79 | 1.79 | 57.46 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:02 | 1.79 | 1.79 | 57.85 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:02 | 1.79 | 1.79 | 56.81 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:02 | 1.79 | 1.79 | 57.86 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:03 | 1.79 | 1.79 | 57.56 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 57.05 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 56.68 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:02 | 1.79 | 1.79 | 56.83 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:02 | 1.79 | 1.79 | 56.63 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 56.63 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 57.86 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.605727E+11 | 0.550606E+11 | 46460.77 | 02-JAN-06:04 | 42232.84 | 42232.84 | 29.25 | 155.39 |
February | 0.609973E+11 | 0.554466E+11 | 46460.77 | 01-FEB-13:10 | 42232.84 | 42232.84 | 28.81 | 155.39 |
March | 0.724922E+11 | 0.658954E+11 | 46460.77 | 01-MAR-06:03 | 42232.84 | 42232.84 | 29.29 | 155.39 |
April | 0.727643E+11 | 0.661428E+11 | 46460.77 | 01-APR-05:04 | 42232.84 | 42232.84 | 29.84 | 155.39 |
May | 0.703658E+11 | 0.639625E+11 | 46460.77 | 01-MAY-03:02 | 42232.84 | 42232.84 | 29.17 | 155.39 |
June | 0.723067E+11 | 0.657268E+11 | 46460.77 | 01-JUN-05:02 | 42232.84 | 42232.84 | 29.70 | 155.39 |
July | 0.712499E+11 | 0.647661E+11 | 46460.77 | 01-JUL-05:04 | 42232.84 | 42232.84 | 29.27 | 155.39 |
August | 0.761186E+11 | 0.691918E+11 | 46460.77 | 01-AUG-04:05 | 42232.84 | 42232.84 | 28.89 | 155.39 |
September | 0.637968E+11 | 0.579913E+11 | 46460.77 | 01-SEP-05:03 | 42232.84 | 42232.84 | 29.29 | 155.39 |
October | 0.668062E+11 | 0.607268E+11 | 46460.77 | 02-OCT-05:05 | 42232.84 | 42232.84 | 29.49 | 155.39 |
November | 0.687576E+11 | 0.625007E+11 | 46460.77 | 01-NOV-05:04 | 42232.84 | 42232.84 | 30.05 | 155.39 |
December | 0.690661E+11 | 0.627811E+11 | 46460.77 | 01-DEC-08:50 | 42232.84 | 42232.84 | 29.04 | 155.39 |
Annual Sum or Average | 0.825294E+12 | 0.750192E+12 | ||||||
Minimum of Months | 0.605727E+11 | 0.550606E+11 | 46460.77 | 42232.84 | 42232.84 | 28.81 | 155.39 | |
Maximum of Months | 0.761186E+11 | 0.691918E+11 | 46460.77 | 42232.84 | 42232.84 | 30.05 | 155.39 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 79.40 | 79.40 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 79.40 | 79.40 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 79.40 | 79.40 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 0.00 | 0.00 | 01-APR-00:05 | 79.40 | 79.40 | 0.00 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 79.40 | 79.40 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 79.40 | 79.40 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 79.40 | 79.40 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 79.40 | 79.40 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 79.40 | 79.40 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 79.40 | 79.40 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 79.40 | 79.40 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 79.40 | 79.40 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 79.40 | 79.40 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 79.40 | 79.40 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 948815.15 | 3243523.62 | 10-JAN-06:04 | 13.00 | 7.31 | 1.84 | 24659.35 | 22-JAN-07:23 |
February | 997610.90 | 3064456.81 | 16-FEB-06:02 | 12.48 | 6.95 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 1062750.02 | 2852435.86 | 02-MAR-06:03 | 12.38 | 7.23 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 1086272.41 | 3041689.58 | 10-APR-05:02 | 12.44 | 6.94 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1072802.22 | 3249673.71 | 18-MAY-05:04 | 12.98 | 7.28 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1112042.10 | 3079402.32 | 26-JUN-05:02 | 12.67 | 7.11 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1011804.92 | 3348930.27 | 18-JUL-05:04 | 13.12 | 7.42 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1055168.96 | 3088683.95 | 22-AUG-05:03 | 12.69 | 7.11 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1010698.49 | 3177539.73 | 20-SEP-05:03 | 12.72 | 7.03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 987204.40 | 3167023.72 | 26-OCT-05:03 | 12.68 | 6.98 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 999914.69 | 3350090.74 | 13-NOV-06:04 | 12.99 | 7.29 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 960029.35 | 3258611.38 | 12-DEC-06:04 | 13.13 | 7.44 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 1025360.99 | 0.16 | ||||||
Minimum of Months | 948815.15 | 2852435.86 | 12.38 | 6.94 | 0.00 | 0.00 | ||
Maximum of Months | 1112042.10 | 3350090.74 | 13.13 | 7.44 | 1.84 | 24659.35 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 744885.44 | 4406626.30 | 02-JAN-04:02 | 15.05 | 7.14 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 776580.75 | 4342124.25 | 16-FEB-06:02 | 14.58 | 7.55 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 823116.47 | 4309491.78 | 13-MAR-05:02 | 14.49 | 7.12 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 846968.78 | 4311866.33 | 10-APR-05:02 | 14.53 | 7.53 | 0.00 | 0.00 | 01-APR-00:05 |
May | 883981.56 | 4416528.18 | 17-MAY-05:02 | 14.68 | 7.70 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 921351.64 | 4365417.51 | 20-JUN-05:02 | 14.59 | 7.69 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 797869.68 | 4358283.89 | 18-JUL-05:02 | 14.58 | 7.56 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 868694.58 | 4397974.24 | 07-AUG-05:02 | 14.65 | 7.08 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 814808.67 | 4425694.06 | 21-SEP-05:02 | 14.70 | 7.01 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 797580.16 | 4361184.74 | 12-OCT-05:02 | 14.62 | 7.14 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 797797.22 | 4359795.47 | 01-NOV-05:02 | 14.58 | 7.49 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 748041.06 | 4378809.97 | 12-DEC-06:02 | 14.62 | 7.67 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 818524.08 | 0.00 | ||||||
Minimum of Months | 744885.44 | 4309491.78 | 14.49 | 7.01 | 0.00 | 0.00 | ||
Maximum of Months | 921351.64 | 4425694.06 | 15.05 | 7.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 122544.54 | 206561.10 | 05-JAN-15:00 | 39.02 | 34.58 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 166923.80 | 252970.95 | 28-FEB-15:00 | 43.56 | 35.99 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 208756.24 | 297920.35 | 21-MAR-13:10 | 47.92 | 37.69 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 251291.25 | 320916.28 | 01-APR-14:00 | 50.14 | 37.22 | 0.00 | 0.00 | 01-APR-00:05 |
May | 153932.91 | 240417.28 | 06-MAY-13:00 | 42.34 | 38.15 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 185662.02 | 268864.37 | 13-JUN-15:00 | 45.11 | 37.06 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 197539.84 | 265606.53 | 21-JUL-15:00 | 44.79 | 34.37 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 234161.03 | 307911.51 | 13-AUG-15:00 | 48.88 | 35.75 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 137613.22 | 209978.89 | 06-SEP-14:00 | 39.36 | 34.62 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 162537.30 | 232735.04 | 04-OCT-14:00 | 41.59 | 33.99 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 191278.72 | 270442.09 | 18-NOV-13:00 | 45.26 | 35.58 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 213598.54 | 295386.63 | 08-DEC-15:00 | 47.67 | 34.72 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 185573.71 | 0.00 | ||||||
Minimum of Months | 122544.54 | 206561.10 | 39.02 | 33.99 | 0.00 | 0.00 | ||
Maximum of Months | 251291.25 | 320916.28 | 50.14 | 38.15 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.93 | 57.93 | 10132.07 | 32670.39 | 10-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.11 | 57.11 | 10123.62 | 32583.75 | 01-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 57.65 | 57.65 | 10520.51 | 32255.53 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 58.26 | 58.26 | 9763.54 | 31604.92 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 58.24 | 58.24 | 9855.75 | 30978.28 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 57.19 | 57.19 | 9930.83 | 30404.84 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.14 | 58.14 | 9215.04 | 30119.60 | 31-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.91 | 57.91 | 10011.01 | 30487.13 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 57.39 | 57.39 | 9613.16 | 31055.30 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 57.20 | 57.20 | 9781.65 | 31739.71 | 30-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 57.12 | 57.12 | 10081.31 | 32324.39 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 56.92 | 56.92 | 9886.20 | 32632.84 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 9908.48 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.92 | 56.92 | 9215.04 | 30119.60 | ||
Maximum of Months | 0.00 | 0.00 | 58.26 | 58.26 | 10520.51 | 32670.39 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1769817.09 | 5991276.34 | 12-JAN-13:20 | 30.32 | 27.00 | 3.34 | 13833.68 | 23-JAN-01:50 |
February | 1997096.57 | 6452978.73 | 14-FEB-16:00 | 31.03 | 27.75 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 2331815.72 | 6234619.32 | 27-MAR-14:10 | 30.70 | 27.46 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 2990497.53 | 6726331.26 | 21-APR-10:50 | 31.46 | 28.19 | 0.00 | 0.00 | 01-APR-00:05 |
May | 3216763.40 | 7758591.76 | 22-MAY-05:03 | 33.04 | 28.73 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 3373055.67 | 7544292.44 | 28-JUN-05:04 | 32.71 | 28.23 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 2441360.91 | 6498434.73 | 20-JUL-15:00 | 31.10 | 27.93 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 3178925.66 | 6930490.98 | 08-AUG-05:03 | 31.77 | 27.91 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 2834332.05 | 6804625.22 | 05-SEP-05:04 | 31.58 | 27.95 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 2648881.27 | 6715999.81 | 17-OCT-15:50 | 31.44 | 28.18 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 2454395.40 | 6674940.14 | 10-NOV-13:50 | 31.38 | 28.16 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 1895990.38 | 6197029.21 | 11-DEC-13:30 | 30.64 | 27.40 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 2595828.25 | 0.28 | ||||||
Minimum of Months | 1769817.09 | 5991276.34 | 30.32 | 27.00 | 0.00 | 0.00 | ||
Maximum of Months | 3373055.67 | 7758591.76 | 33.04 | 28.73 | 3.34 | 13833.68 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.151427E+12 | 0.820285E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.153950E+12 | 0.830741E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.189252E+12 | 0.119836E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.194712E+12 | 0.128480E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.188452E+12 | 0.105904E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.199860E+12 | 0.108010E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.191014E+12 | 0.113733E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.214379E+12 | 0.133037E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.167500E+12 | 0.952891E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.181851E+12 | 0.991435E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.183393E+12 | 0.968631E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.184583E+12 | 0.975067E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.220037E+13 | 0.126290E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.151427E+12 | 0.820285E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.214379E+12 | 0.133037E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.129243E+13 | 0.639387E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.122018E+13 | 0.608698E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.145098E+13 | 0.836563E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.146821E+13 | 0.841654E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.162371E+13 | 0.838793E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.165051E+13 | 0.804013E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.139514E+13 | 0.765092E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.154845E+13 | 0.856352E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.141743E+13 | 0.756524E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.141216E+13 | 0.718942E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.133898E+13 | 0.649865E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.127122E+13 | 0.608158E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.170894E+14 | 0.892404E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.122018E+13 | 0.608158E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.165051E+13 | 0.856352E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.142059E+12 | 0.740306E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.137586E+12 | 0.736147E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.167629E+12 | 0.103081E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.171820E+12 | 0.103353E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.186456E+12 | 0.103333E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.189425E+12 | 0.101886E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.159936E+12 | 0.902272E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.173731E+12 | 0.982745E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.161667E+12 | 0.891811E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.156263E+12 | 0.821853E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.148466E+12 | 0.772009E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.139608E+12 | 0.697226E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.193465E+13 | 0.106609E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.137586E+12 | 0.697226E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.189425E+12 | 0.103353E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.110132E+12 | 0.148615E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.101122E+12 | 0.131113E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.123299E+12 | 0.146977E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.130162E+12 | 0.138220E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.149536E+12 | 0.146786E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.149316E+12 | 0.143471E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.124788E+12 | 0.142253E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.151754E+12 | 0.149362E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.133022E+12 | 0.141116E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.131006E+12 | 0.143920E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.121277E+12 | 0.139906E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.111420E+12 | 0.144036E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.153683E+13 | 0.171577E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.101122E+12 | 0.131113E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.151754E+12 | 0.149362E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.876219E+10 | 0.329457E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.139026E+11 | 0.428015E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.220476E+11 | 0.617104E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.279375E+11 | 0.737806E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.980728E+10 | 0.360277E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.158695E+11 | 0.485721E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.220143E+11 | 0.604096E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.286845E+11 | 0.736877E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.914231E+10 | 0.335142E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.157691E+11 | 0.474458E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.211955E+11 | 0.576962E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.277769E+11 | 0.702372E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.222909E+12 | 0.638829E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.876219E+10 | 0.329457E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.286845E+11 | 0.737806E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.815383E+11 | 0.309400E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.132259E+12 | 0.406905E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.210587E+12 | 0.588451E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.266735E+12 | 0.703400E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.920076E+11 | 0.339501E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.151113E+12 | 0.461939E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.210061E+12 | 0.575611E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.274178E+12 | 0.703023E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.853763E+11 | 0.315083E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.149783E+12 | 0.450530E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.202312E+12 | 0.549880E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.265222E+12 | 0.669743E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.212117E+13 | 0.607347E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.815383E+11 | 0.309400E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.274178E+12 | 0.703400E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.829251E+10 | 0.315277E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.133802E+11 | 0.412940E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.212646E+11 | 0.596034E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.269134E+11 | 0.711790E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.947855E+10 | 0.348550E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.153581E+11 | 0.470137E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.212085E+11 | 0.582945E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.275935E+11 | 0.710186E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.876185E+10 | 0.322652E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.151453E+11 | 0.456968E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.203688E+11 | 0.555812E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.266450E+11 | 0.675773E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.214410E+12 | 0.615907E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.829251E+10 | 0.315277E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.275935E+11 | 0.711790E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.820285E+10 | 0.151427E+12 | 0.00 | 0.00 | 0.293921E+11 | 0.00 | 0.00 | 0.00 |
February | 0.830741E+10 | 0.153950E+12 | 0.00 | 0.00 | 0.333559E+11 | 0.00 | 0.00 | 0.00 |
March | 0.119836E+11 | 0.189252E+12 | 0.00 | 0.00 | 0.494620E+11 | 0.00 | 0.00 | 0.00 |
April | 0.128480E+11 | 0.194712E+12 | 0.00 | 0.00 | 0.691139E+11 | 0.00 | 0.00 | 0.00 |
May | 0.105904E+11 | 0.188452E+12 | 0.00 | 0.00 | 0.741984E+11 | 0.00 | 0.00 | 0.00 |
June | 0.108010E+11 | 0.199860E+12 | 0.00 | 0.00 | 0.776901E+11 | 0.00 | 0.00 | 0.00 |
July | 0.113733E+11 | 0.191014E+12 | 0.00 | 0.00 | 0.458959E+11 | 0.00 | 0.00 | 0.00 |
August | 0.133037E+11 | 0.214379E+12 | 0.00 | 0.00 | 0.695185E+11 | 0.00 | 0.00 | 0.00 |
September | 0.952891E+10 | 0.167500E+12 | 0.00 | 0.00 | 0.566380E+11 | 0.00 | 0.00 | 0.00 |
October | 0.991435E+10 | 0.181851E+12 | 0.00 | 0.00 | 0.504548E+11 | 0.00 | 0.00 | 0.00 |
November | 0.968631E+10 | 0.183393E+12 | 0.00 | 0.00 | 0.431723E+11 | 0.00 | 0.00 | 0.00 |
December | 0.975067E+10 | 0.184583E+12 | 0.00 | 0.00 | 0.329710E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126290E+12 | 0.220037E+13 | 0.00 | 0.00 | 0.631863E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.820285E+10 | 0.151427E+12 | 0.00 | 0.00 | 0.293921E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133037E+11 | 0.214379E+12 | 0.00 | 0.00 | 0.776901E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.639387E+11 | 0.129243E+13 | 0.00 | 0.00 | 0.299066E+12 | 0.00 | 0.00 | 0.00 |
February | 0.608698E+11 | 0.122018E+13 | 0.00 | 0.00 | 0.315494E+12 | 0.00 | 0.00 | 0.00 |
March | 0.836563E+11 | 0.145098E+13 | 0.00 | 0.00 | 0.440144E+12 | 0.00 | 0.00 | 0.00 |
April | 0.841654E+11 | 0.146821E+13 | 0.00 | 0.00 | 0.597044E+12 | 0.00 | 0.00 | 0.00 |
May | 0.838793E+11 | 0.162371E+13 | 0.00 | 0.00 | 0.695908E+12 | 0.00 | 0.00 | 0.00 |
June | 0.804013E+11 | 0.165051E+13 | 0.00 | 0.00 | 0.714654E+12 | 0.00 | 0.00 | 0.00 |
July | 0.765092E+11 | 0.139514E+13 | 0.00 | 0.00 | 0.404376E+12 | 0.00 | 0.00 | 0.00 |
August | 0.856352E+11 | 0.154845E+13 | 0.00 | 0.00 | 0.606318E+12 | 0.00 | 0.00 | 0.00 |
September | 0.756524E+11 | 0.141743E+13 | 0.00 | 0.00 | 0.537526E+12 | 0.00 | 0.00 | 0.00 |
October | 0.718942E+11 | 0.141216E+13 | 0.00 | 0.00 | 0.466507E+12 | 0.00 | 0.00 | 0.00 |
November | 0.649865E+11 | 0.133898E+13 | 0.00 | 0.00 | 0.403241E+12 | 0.00 | 0.00 | 0.00 |
December | 0.608158E+11 | 0.127122E+13 | 0.00 | 0.00 | 0.318759E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.892404E+12 | 0.170894E+14 | 0.00 | 0.00 | 0.579904E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.608158E+11 | 0.122018E+13 | 0.00 | 0.00 | 0.299066E+12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.856352E+11 | 0.165051E+13 | 0.00 | 0.00 | 0.714654E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.740306E+10 | 0.142059E+12 | 0.00 | 0.00 | 0.282449E+11 | 0.00 | 0.00 | 0.00 |
February | 0.736147E+10 | 0.137586E+12 | 0.00 | 0.00 | 0.299827E+11 | 0.00 | 0.00 | 0.00 |
March | 0.103081E+11 | 0.167629E+12 | 0.00 | 0.00 | 0.427732E+11 | 0.00 | 0.00 | 0.00 |
April | 0.103353E+11 | 0.171820E+12 | 0.00 | 0.00 | 0.593930E+11 | 0.00 | 0.00 | 0.00 |
May | 0.103333E+11 | 0.186456E+12 | 0.00 | 0.00 | 0.690769E+11 | 0.00 | 0.00 | 0.00 |
June | 0.101886E+11 | 0.189425E+12 | 0.00 | 0.00 | 0.701405E+11 | 0.00 | 0.00 | 0.00 |
July | 0.902272E+10 | 0.159936E+12 | 0.00 | 0.00 | 0.391132E+11 | 0.00 | 0.00 | 0.00 |
August | 0.982745E+10 | 0.173731E+12 | 0.00 | 0.00 | 0.597766E+11 | 0.00 | 0.00 | 0.00 |
September | 0.891811E+10 | 0.161667E+12 | 0.00 | 0.00 | 0.527344E+11 | 0.00 | 0.00 | 0.00 |
October | 0.821853E+10 | 0.156263E+12 | 0.00 | 0.00 | 0.460363E+11 | 0.00 | 0.00 | 0.00 |
November | 0.772009E+10 | 0.148466E+12 | 0.00 | 0.00 | 0.387883E+11 | 0.00 | 0.00 | 0.00 |
December | 0.697226E+10 | 0.139608E+12 | 0.00 | 0.00 | 0.299738E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106609E+12 | 0.193465E+13 | 0.00 | 0.00 | 0.566034E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.697226E+10 | 0.137586E+12 | 0.00 | 0.00 | 0.282449E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103353E+11 | 0.189425E+12 | 0.00 | 0.00 | 0.701405E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148615E+11 | 0.110132E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131113E+11 | 0.101122E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146977E+11 | 0.123299E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138220E+11 | 0.130162E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146786E+11 | 0.149536E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143471E+11 | 0.149316E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142253E+11 | 0.124788E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149362E+11 | 0.151754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141116E+11 | 0.133022E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143920E+11 | 0.131006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139906E+11 | 0.121277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144036E+11 | 0.111420E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171577E+12 | 0.153683E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131113E+11 | 0.101122E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149362E+11 | 0.151754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137456E+10 | 0.684218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124154E+10 | 0.108640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137456E+10 | 0.172511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133022E+10 | 0.218896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137456E+10 | 0.757906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133022E+10 | 0.123425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137456E+10 | 0.173479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137456E+10 | 0.226903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133022E+10 | 0.712111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137456E+10 | 0.123991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133022E+10 | 0.167561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137456E+10 | 0.221277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161843E+11 | 0.175211E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124154E+10 | 0.684218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137456E+10 | 0.226903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.130568E+11 | 0.636550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117932E+11 | 0.103362E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130568E+11 | 0.164799E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126356E+11 | 0.209030E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130568E+11 | 0.711143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126356E+11 | 0.117555E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.130568E+11 | 0.165556E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130568E+11 | 0.216932E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126356E+11 | 0.665036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130568E+11 | 0.117787E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126356E+11 | 0.159960E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130568E+11 | 0.211304E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153733E+12 | 0.166756E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117932E+11 | 0.636550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130568E+11 | 0.216932E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.133097E+10 | 0.647071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120216E+10 | 0.104530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133097E+10 | 0.166353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128803E+10 | 0.210835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133097E+10 | 0.732401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128803E+10 | 0.119447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133097E+10 | 0.167100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133097E+10 | 0.218226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128803E+10 | 0.682336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133097E+10 | 0.119066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128803E+10 | 0.160988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133097E+10 | 0.212182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156711E+11 | 0.168491E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120216E+10 | 0.647071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133097E+10 | 0.218226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.820285E+10 | 0.00 | 0.151427E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.830741E+10 | 0.00 | 0.153950E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119836E+11 | 0.00 | 0.189252E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128480E+11 | 0.00 | 0.194712E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.105904E+11 | 0.00 | 0.188452E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108010E+11 | 0.00 | 0.199860E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113733E+11 | 0.00 | 0.191014E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133037E+11 | 0.00 | 0.214379E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.952891E+10 | 0.00 | 0.167500E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.991435E+10 | 0.00 | 0.181851E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.968631E+10 | 0.00 | 0.183393E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.975067E+10 | 0.00 | 0.184583E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126290E+12 | 0.00 | 0.220037E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.820285E+10 | 0.00 | 0.151427E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133037E+11 | 0.00 | 0.214379E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.639387E+11 | 0.00 | 0.129243E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.608698E+11 | 0.00 | 0.122018E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.836563E+11 | 0.00 | 0.145098E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.841654E+11 | 0.00 | 0.146821E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.838793E+11 | 0.00 | 0.162371E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.804013E+11 | 0.00 | 0.165051E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.765092E+11 | 0.00 | 0.139514E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.856352E+11 | 0.00 | 0.154845E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.756524E+11 | 0.00 | 0.141743E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.718942E+11 | 0.00 | 0.141216E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.649865E+11 | 0.00 | 0.133898E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.608158E+11 | 0.00 | 0.127122E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.892404E+12 | 0.00 | 0.170894E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.608158E+11 | 0.00 | 0.122018E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.856352E+11 | 0.00 | 0.165051E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.740306E+10 | 0.00 | 0.142059E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.736147E+10 | 0.00 | 0.137586E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103081E+11 | 0.00 | 0.167629E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103353E+11 | 0.00 | 0.171820E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103333E+11 | 0.00 | 0.186456E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101886E+11 | 0.00 | 0.189425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.902272E+10 | 0.00 | 0.159936E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.982745E+10 | 0.00 | 0.173731E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.891811E+10 | 0.00 | 0.161667E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.821853E+10 | 0.00 | 0.156263E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.772009E+10 | 0.00 | 0.148466E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.697226E+10 | 0.00 | 0.139608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106609E+12 | 0.00 | 0.193465E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.697226E+10 | 0.00 | 0.137586E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103353E+11 | 0.00 | 0.189425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148615E+11 | 0.00 | 0.110132E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131113E+11 | 0.00 | 0.101122E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146977E+11 | 0.00 | 0.123299E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138220E+11 | 0.00 | 0.130162E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146786E+11 | 0.00 | 0.149536E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143471E+11 | 0.00 | 0.149316E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142253E+11 | 0.00 | 0.124788E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149362E+11 | 0.00 | 0.151754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141116E+11 | 0.00 | 0.133022E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143920E+11 | 0.00 | 0.131006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139906E+11 | 0.00 | 0.121277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144036E+11 | 0.00 | 0.111420E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171577E+12 | 0.00 | 0.153683E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131113E+11 | 0.00 | 0.101122E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149362E+11 | 0.00 | 0.151754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137456E+10 | 0.00 | 0.876219E+10 | 0.00 | 0.192001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124154E+10 | 0.00 | 0.139026E+11 | 0.00 | 0.303861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137456E+10 | 0.00 | 0.220476E+11 | 0.00 | 0.479648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133022E+10 | 0.00 | 0.279375E+11 | 0.00 | 0.604784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137456E+10 | 0.00 | 0.980728E+10 | 0.00 | 0.222821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133022E+10 | 0.00 | 0.158695E+11 | 0.00 | 0.352699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137456E+10 | 0.00 | 0.220143E+11 | 0.00 | 0.466640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137456E+10 | 0.00 | 0.286845E+11 | 0.00 | 0.599421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133022E+10 | 0.00 | 0.914231E+10 | 0.00 | 0.202121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137456E+10 | 0.00 | 0.157691E+11 | 0.00 | 0.337002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133022E+10 | 0.00 | 0.211955E+11 | 0.00 | 0.443940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137456E+10 | 0.00 | 0.277769E+11 | 0.00 | 0.564916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161843E+11 | 0.00 | 0.222909E+12 | 0.00 | 0.476986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124154E+10 | 0.00 | 0.876219E+10 | 0.00 | 0.192001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137456E+10 | 0.00 | 0.286845E+11 | 0.00 | 0.604784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.130568E+11 | 0.00 | 0.815383E+11 | 0.00 | 0.178833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117932E+11 | 0.00 | 0.132259E+12 | 0.00 | 0.288973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130568E+11 | 0.00 | 0.210587E+12 | 0.00 | 0.457883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126356E+11 | 0.00 | 0.266735E+12 | 0.00 | 0.577044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130568E+11 | 0.00 | 0.920076E+11 | 0.00 | 0.208933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126356E+11 | 0.00 | 0.151113E+12 | 0.00 | 0.335583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.130568E+11 | 0.00 | 0.210061E+12 | 0.00 | 0.445043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130568E+11 | 0.00 | 0.274178E+12 | 0.00 | 0.572455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126356E+11 | 0.00 | 0.853763E+11 | 0.00 | 0.188727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130568E+11 | 0.00 | 0.149783E+12 | 0.00 | 0.319962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126356E+11 | 0.00 | 0.202312E+12 | 0.00 | 0.423524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130568E+11 | 0.00 | 0.265222E+12 | 0.00 | 0.539175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153733E+12 | 0.00 | 0.212117E+13 | 0.00 | 0.453613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117932E+11 | 0.00 | 0.815383E+11 | 0.00 | 0.178833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130568E+11 | 0.00 | 0.274178E+12 | 0.00 | 0.577044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.133097E+10 | 0.00 | 0.829251E+10 | 0.00 | 0.182180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120216E+10 | 0.00 | 0.133802E+11 | 0.00 | 0.292724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133097E+10 | 0.00 | 0.212646E+11 | 0.00 | 0.462938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128803E+10 | 0.00 | 0.269134E+11 | 0.00 | 0.582987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133097E+10 | 0.00 | 0.947855E+10 | 0.00 | 0.215454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128803E+10 | 0.00 | 0.153581E+11 | 0.00 | 0.341333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133097E+10 | 0.00 | 0.212085E+11 | 0.00 | 0.449848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133097E+10 | 0.00 | 0.275935E+11 | 0.00 | 0.577089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128803E+10 | 0.00 | 0.876185E+10 | 0.00 | 0.193848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133097E+10 | 0.00 | 0.151453E+11 | 0.00 | 0.323871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128803E+10 | 0.00 | 0.203688E+11 | 0.00 | 0.427009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133097E+10 | 0.00 | 0.266450E+11 | 0.00 | 0.542676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156711E+11 | 0.00 | 0.214410E+12 | 0.00 | 0.459196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120216E+10 | 0.00 | 0.829251E+10 | 0.00 | 0.182180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133097E+10 | 0.00 | 0.275935E+11 | 0.00 | 0.582987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117678E+09 | 0.298900E+11 | 0.00 | 13637275.67 | 0.616678E+09 | 0.00 | 0.494987E+09 | 0.00 | 0.43 |
February | 6664507.32 | 0.293144E+11 | 0.00 | 3195143.06 | 0.639506E+09 | 0.00 | 69734602.55 | 0.00 | 0.42 |
March | 0.00 | 0.410109E+11 | 0.00 | 589262.09 | 0.887912E+09 | 0.00 | 2479564.08 | 0.00 | 0.43 |
April | 0.00 | 0.528534E+11 | 0.00 | 0.00 | 0.132757E+10 | 0.00 | 0.00 | 0.00 | 0.41 |
May | 0.00 | 0.679197E+11 | 0.00 | 0.00 | 0.166858E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 1285711.61 | 0.680963E+11 | 0.00 | 632812.39 | 0.151709E+10 | 0.00 | 7743212.53 | 0.00 | 0.43 |
July | 0.00 | 0.446409E+11 | 0.00 | 0.00 | 0.107981E+10 | 0.00 | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.656824E+11 | 0.00 | 0.00 | 0.124636E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.558966E+11 | 0.00 | 62776.04 | 0.138458E+10 | 0.00 | 253973.39 | 0.00 | 0.42 |
October | 1595890.95 | 0.516054E+11 | 0.00 | 354284.67 | 0.117067E+10 | 0.00 | 10127350.06 | 0.00 | 0.42 |
November | 11542199.86 | 0.430928E+11 | 0.00 | 4353714.41 | 0.865071E+09 | 0.00 | 77027362.91 | 0.00 | 0.42 |
December | 43536797.98 | 0.319452E+11 | 0.00 | 9155706.27 | 0.723820E+09 | 0.00 | 0.258186E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.182303E+09 | 0.581948E+12 | 0.00 | 31980974.60 | 0.131276E+11 | 0.00 | 0.920539E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.293144E+11 | 0.00 | 0.00 | 0.616678E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.117678E+09 | 0.680963E+11 | 0.00 | 13637275.67 | 0.166858E+10 | 0.00 | 0.494987E+09 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 58661797.67 | 0.108042E+11 | 0.00 | 2872349.18 | 0.609775E+10 | 0.00 | 98264684.67 | 0.00 | 0.37 |
February | 1997507.29 | 0.100223E+11 | 0.00 | 180044.08 | 0.847445E+10 | 0.00 | 2915094.35 | 0.00 | 0.43 |
March | 0.00 | 0.125971E+11 | 0.00 | 0.00 | 0.101557E+11 | 0.00 | 0.00 | 0.00 | 0.46 |
April | 0.00 | 0.148735E+11 | 0.00 | 0.00 | 0.129765E+11 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 0.00 | 0.201352E+11 | 0.00 | 0.00 | 0.123305E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
June | 0.00 | 0.200978E+11 | 0.00 | 0.00 | 0.139450E+11 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.152415E+11 | 0.00 | 0.00 | 0.153566E+11 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.205828E+11 | 0.00 | 0.00 | 0.165785E+11 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.178455E+11 | 0.00 | 0.00 | 0.107181E+11 | 0.00 | 0.00 | 0.00 | 0.40 |
October | 0.00 | 0.180200E+11 | 0.00 | 0.00 | 0.143668E+11 | 0.00 | 0.00 | 0.00 | 0.42 |
November | 4378.25 | 0.147861E+11 | 0.00 | 0.00 | 0.146742E+11 | 0.00 | 0.00 | 0.00 | 0.45 |
December | 55474141.89 | 0.118299E+11 | 0.00 | 709155.65 | 0.138077E+11 | 0.00 | 22788813.57 | 0.00 | 0.46 |
Annual Sum or Average | 0.116138E+09 | 0.186836E+12 | 0.00 | 3761548.91 | 0.149482E+12 | 0.00 | 0.123969E+09 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.100223E+11 | 0.00 | 0.00 | 0.609775E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 58661797.67 | 0.205828E+11 | 0.00 | 2872349.18 | 0.165785E+11 | 0.00 | 98264684.67 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.490649E+09 | 0.106563E+12 | 0.00 | 24243211.37 | 0.388743E+11 | 0.00 | 0.931716E+09 | 0.00 | 0.34 |
February | 0.00 | 0.991248E+11 | 0.00 | 1753214.95 | 0.411329E+11 | 0.00 | 24429465.97 | 0.00 | 0.35 |
March | 0.00 | 0.121600E+12 | 0.00 | 0.00 | 0.496785E+11 | 0.00 | 0.00 | 0.00 | 0.37 |
April | 0.00 | 0.142081E+12 | 0.00 | 0.00 | 0.767978E+11 | 0.00 | 0.00 | 0.00 | 0.38 |
May | 0.00 | 0.196862E+12 | 0.00 | 0.00 | 0.873603E+11 | 0.00 | 0.00 | 0.00 | 0.37 |
June | 0.00 | 0.198330E+12 | 0.00 | 0.00 | 0.844650E+11 | 0.00 | 0.00 | 0.00 | 0.37 |
July | 0.00 | 0.146259E+12 | 0.00 | 0.00 | 0.700046E+11 | 0.00 | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.198585E+12 | 0.00 | 0.00 | 0.663694E+11 | 0.00 | 0.00 | 0.00 | 0.36 |
September | 0.00 | 0.174198E+12 | 0.00 | 0.00 | 0.701959E+11 | 0.00 | 0.00 | 0.00 | 0.35 |
October | 0.00 | 0.176069E+12 | 0.00 | 0.00 | 0.691561E+11 | 0.00 | 0.00 | 0.00 | 0.34 |
November | 2495444.32 | 0.145539E+12 | 0.00 | 252700.89 | 0.556276E+11 | 0.00 | 753748.72 | 0.00 | 0.34 |
December | 0.179672E+09 | 0.113790E+12 | 0.00 | 11128626.59 | 0.474019E+11 | 0.00 | 0.193415E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.672817E+09 | 0.181900E+13 | 0.00 | 37377753.80 | 0.757064E+12 | 0.00 | 0.115031E+10 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.991248E+11 | 0.00 | 0.00 | 0.388743E+11 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.490649E+09 | 0.198585E+12 | 0.00 | 24243211.37 | 0.873603E+11 | 0.00 | 0.931716E+09 | 0.00 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 31905637.69 | 0.100815E+11 | 0.00 | 1663898.52 | 0.405918E+10 | 0.00 | 65655156.45 | 0.00 | 0.34 |
February | 0.00 | 0.945368E+10 | 0.00 | 95226.05 | 0.436871E+10 | 0.00 | 1610193.30 | 0.00 | 0.35 |
March | 0.00 | 0.117862E+11 | 0.00 | 0.00 | 0.535852E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
April | 0.00 | 0.140828E+11 | 0.00 | 0.00 | 0.835584E+10 | 0.00 | 0.00 | 0.00 | 0.39 |
May | 0.00 | 0.194596E+11 | 0.00 | 0.00 | 0.947019E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.195282E+11 | 0.00 | 0.00 | 0.926194E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.144616E+11 | 0.00 | 0.00 | 0.820499E+10 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.197372E+11 | 0.00 | 0.00 | 0.731009E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
September | 0.00 | 0.173328E+11 | 0.00 | 0.00 | 0.805773E+10 | 0.00 | 0.00 | 0.00 | 0.36 |
October | 0.00 | 0.169597E+11 | 0.00 | 0.00 | 0.793887E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
November | 47969.90 | 0.139278E+11 | 0.00 | 0.00 | 0.623814E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
December | 2946206.55 | 0.108290E+11 | 0.00 | 467637.22 | 0.532633E+10 | 0.00 | 11401778.20 | 0.00 | 0.33 |
Annual Sum or Average | 34899814.14 | 0.177640E+12 | 0.00 | 2226761.78 | 0.839505E+11 | 0.00 | 78667127.96 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.945368E+10 | 0.00 | 0.00 | 0.405918E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 31905637.69 | 0.197372E+11 | 0.00 | 1663898.52 | 0.947019E+10 | 0.00 | 65655156.45 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 9802815.56 | 0.192681E+10 | 0.00 | 263267.45 | 0.709379E+09 | 0.00 | 9119912.96 | 0.00 | 0.47 |
February | 251337.84 | 0.191942E+10 | 0.00 | 25892.74 | 0.974571E+09 | 0.00 | 412695.57 | 0.00 | 0.54 |
March | 0.00 | 0.254020E+10 | 0.00 | 0.00 | 0.111482E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.00 | 0.325460E+10 | 0.00 | 0.00 | 0.138791E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
May | 0.00 | 0.488035E+10 | 0.00 | 0.00 | 0.114927E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
June | 0.00 | 0.544327E+10 | 0.00 | 0.00 | 0.126763E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
July | 0.00 | 0.356901E+10 | 0.00 | 0.00 | 0.155525E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
August | 0.00 | 0.431280E+10 | 0.00 | 0.00 | 0.178860E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
September | 0.00 | 0.359923E+10 | 0.00 | 0.00 | 0.115554E+10 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.00 | 0.329517E+10 | 0.00 | 0.00 | 0.166936E+10 | 0.00 | 0.00 | 0.00 | 0.53 |
November | 550.90 | 0.270244E+10 | 0.00 | 0.00 | 0.172123E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
December | 7797526.27 | 0.207829E+10 | 0.00 | 51124.54 | 0.165361E+10 | 0.00 | 1688389.75 | 0.00 | 0.55 |
Annual Sum or Average | 17852230.58 | 0.395216E+11 | 0.00 | 340284.73 | 0.161472E+11 | 0.00 | 11220998.28 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.191942E+10 | 0.00 | 0.00 | 0.709379E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 9802815.56 | 0.544327E+10 | 0.00 | 263267.45 | 0.178860E+10 | 0.00 | 9119912.96 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 7199590.68 | 0.150127E+10 | 0.00 | 235164.16 | 0.507849E+09 | 0.00 | 8709757.14 | 0.00 | 0.56 |
February | 181191.42 | 0.150692E+10 | 0.00 | 32982.14 | 0.677015E+09 | 0.00 | 504192.58 | 0.00 | 0.64 |
March | 0.00 | 0.191654E+10 | 0.00 | 0.00 | 0.811353E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
April | 0.00 | 0.237161E+10 | 0.00 | 0.00 | 0.101159E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
May | 0.00 | 0.326305E+10 | 0.00 | 0.00 | 0.888741E+09 | 0.00 | 0.00 | 0.00 | 0.66 |
June | 0.00 | 0.328759E+10 | 0.00 | 0.00 | 0.105604E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
July | 0.00 | 0.200314E+10 | 0.00 | 0.00 | 0.131056E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
August | 0.00 | 0.274279E+10 | 0.00 | 0.00 | 0.139263E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
September | 0.00 | 0.271841E+10 | 0.00 | 0.00 | 0.790299E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
October | 0.00 | 0.233146E+10 | 0.00 | 0.00 | 0.119875E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
November | 397.15 | 0.183699E+10 | 0.00 | 0.00 | 0.128602E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
December | 5813305.91 | 0.141182E+10 | 0.00 | 25992.48 | 0.122903E+10 | 0.00 | 1207447.33 | 0.00 | 0.60 |
Annual Sum or Average | 13194485.15 | 0.268916E+11 | 0.00 | 294138.77 | 0.121599E+11 | 0.00 | 10421397.04 | 0.00 | 0.64 |
Minimum of Months | 0.00 | 0.141182E+10 | 0.00 | 0.00 | 0.507849E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 7199590.68 | 0.328759E+10 | 0.00 | 235164.16 | 0.139263E+10 | 0.00 | 8709757.14 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 7010910.90 | 0.300376E+10 | 0.00 | 436873.61 | 0.472733E+09 | 0.00 | 15667154.00 | 0.00 | 0.64 |
February | 251433.20 | 0.277658E+10 | 0.00 | 36190.71 | 0.800876E+09 | 0.00 | 569330.69 | 0.00 | 0.68 |
March | 0.00 | 0.297703E+10 | 0.00 | 0.00 | 0.102626E+10 | 0.00 | 0.00 | 0.00 | 0.66 |
April | 0.00 | 0.316673E+10 | 0.00 | 0.00 | 0.139969E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
May | 0.00 | 0.425373E+10 | 0.00 | 0.00 | 0.129713E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.00 | 0.430377E+10 | 0.00 | 0.00 | 0.146576E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.304769E+10 | 0.00 | 0.00 | 0.167371E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.398936E+10 | 0.00 | 0.00 | 0.185058E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.380197E+10 | 0.00 | 0.00 | 0.111374E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.00 | 0.402344E+10 | 0.00 | 0.00 | 0.148345E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 551.10 | 0.376503E+10 | 0.00 | 0.00 | 0.147315E+10 | 0.00 | 0.00 | 0.00 | 0.66 |
December | 7093935.81 | 0.326852E+10 | 0.00 | 107800.57 | 0.136395E+10 | 0.00 | 3166329.86 | 0.00 | 0.70 |
Annual Sum or Average | 14356831.01 | 0.423776E+11 | 0.00 | 580864.88 | 0.154210E+11 | 0.00 | 19402814.54 | 0.00 | 0.62 |
Minimum of Months | 0.00 | 0.277658E+10 | 0.00 | 0.00 | 0.472733E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 7093935.81 | 0.430377E+10 | 0.00 | 436873.61 | 0.185058E+10 | 0.00 | 15667154.00 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5579839.97 | 0.218178E+10 | 0.00 | 364547.25 | 0.472139E+09 | 0.00 | 13351230.20 | 0.00 | 0.74 |
February | 169300.98 | 0.264025E+10 | 0.00 | 35755.13 | 0.556274E+09 | 0.00 | 599228.15 | 0.00 | 0.93 |
March | 0.00 | 0.392570E+10 | 0.00 | 0.00 | 0.428336E+09 | 0.00 | 0.00 | 0.00 | 1.10 |
April | 0.00 | 0.540013E+10 | 0.00 | 0.00 | 0.284443E+09 | 0.00 | 0.00 | 0.00 | 1.17 |
May | 0.00 | 0.465188E+10 | 0.00 | 0.00 | 0.808444E+09 | 0.00 | 0.00 | 0.00 | 0.86 |
June | 0.00 | 0.540045E+10 | 0.00 | 0.00 | 0.828257E+09 | 0.00 | 0.00 | 0.00 | 1.00 |
July | 0.00 | 0.459476E+10 | 0.00 | 0.00 | 0.736045E+09 | 0.00 | 0.00 | 0.00 | 1.01 |
August | 0.00 | 0.656095E+10 | 0.00 | 0.00 | 0.440822E+09 | 0.00 | 0.00 | 0.00 | 1.11 |
September | 0.00 | 0.397856E+10 | 0.00 | 0.00 | 0.712671E+09 | 0.00 | 0.00 | 0.00 | 0.81 |
October | 0.00 | 0.431188E+10 | 0.00 | 0.00 | 0.973358E+09 | 0.00 | 0.00 | 0.00 | 0.87 |
November | 0.00 | 0.418060E+10 | 0.00 | 620.96 | 0.785501E+09 | 0.00 | 0.00 | 0.00 | 0.96 |
December | 3014746.03 | 0.402515E+10 | 0.00 | 344715.04 | 0.439550E+09 | 0.00 | 8876278.10 | 0.00 | 1.03 |
Annual Sum or Average | 8763886.98 | 0.518521E+11 | 0.00 | 745638.38 | 0.746584E+10 | 0.00 | 22826736.45 | 0.00 | 0.97 |
Minimum of Months | 0.00 | 0.218178E+10 | 0.00 | 0.00 | 0.284443E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
Maximum of Months | 5579839.97 | 0.656095E+10 | 0.00 | 364547.25 | 0.973358E+09 | 0.00 | 13351230.20 | 0.00 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 68363446.05 | 0.192977E+11 | 0.00 | 2003775.25 | 0.465328E+10 | 0.00 | 95463770.68 | 0.00 | 0.44 |
February | 0.00 | 0.193106E+11 | 0.00 | 250052.16 | 0.484139E+10 | 0.00 | 3431121.87 | 0.00 | 0.48 |
March | 0.00 | 0.255569E+11 | 0.00 | 0.00 | 0.538669E+10 | 0.00 | 0.00 | 0.00 | 0.53 |
April | 0.00 | 0.333775E+11 | 0.00 | 0.00 | 0.815429E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
May | 0.00 | 0.518937E+11 | 0.00 | 0.00 | 0.716271E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
June | 0.00 | 0.594994E+11 | 0.00 | 0.00 | 0.587843E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
July | 0.00 | 0.367706E+11 | 0.00 | 0.00 | 0.581981E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
August | 0.00 | 0.438907E+11 | 0.00 | 0.00 | 0.666549E+10 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.364923E+11 | 0.00 | 0.00 | 0.758555E+10 | 0.00 | 0.00 | 0.00 | 0.51 |
October | 0.00 | 0.328923E+11 | 0.00 | 0.00 | 0.793860E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
November | 313536.80 | 0.267186E+11 | 0.00 | 6631.16 | 0.669292E+10 | 0.00 | 101546.39 | 0.00 | 0.45 |
December | 26442098.69 | 0.198015E+11 | 0.00 | 490555.51 | 0.591235E+10 | 0.00 | 15071566.90 | 0.00 | 0.43 |
Annual Sum or Average | 95119081.54 | 0.405502E+12 | 0.00 | 2751014.07 | 0.766915E+11 | 0.00 | 0.114068E+09 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 0.192977E+11 | 0.00 | 0.00 | 0.465328E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 68363446.05 | 0.594994E+11 | 0.00 | 2003775.25 | 0.815429E+10 | 0.00 | 95463770.68 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 48832182.19 | 0.165782E+11 | 0.00 | 2343965.26 | 0.318952E+10 | 0.00 | 0.116300E+09 | 0.00 | 0.58 |
February | 0.00 | 0.176747E+11 | 0.00 | 373305.75 | 0.269683E+10 | 0.00 | 4923921.55 | 0.00 | 0.64 |
March | 0.00 | 0.230545E+11 | 0.00 | 0.00 | 0.329533E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
April | 0.00 | 0.299096E+11 | 0.00 | 0.00 | 0.497626E+10 | 0.00 | 0.00 | 0.00 | 0.74 |
May | 0.00 | 0.371518E+11 | 0.00 | 0.00 | 0.552119E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
June | 0.00 | 0.391832E+11 | 0.00 | 0.00 | 0.536760E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
July | 0.00 | 0.243919E+11 | 0.00 | 0.00 | 0.502821E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.340097E+11 | 0.00 | 0.00 | 0.461956E+10 | 0.00 | 0.00 | 0.00 | 0.64 |
September | 0.00 | 0.306324E+11 | 0.00 | 0.00 | 0.449530E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
October | 0.00 | 0.268913E+11 | 0.00 | 0.00 | 0.504224E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
November | 236186.48 | 0.219514E+11 | 0.00 | 11899.27 | 0.445286E+10 | 0.00 | 69590.61 | 0.00 | 0.56 |
December | 17960000.97 | 0.173794E+11 | 0.00 | 556502.34 | 0.372998E+10 | 0.00 | 17486397.86 | 0.00 | 0.55 |
Annual Sum or Average | 67028369.64 | 0.318808E+12 | 0.00 | 3285672.62 | 0.524149E+11 | 0.00 | 0.138780E+09 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.165782E+11 | 0.00 | 0.00 | 0.269683E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 48832182.19 | 0.391832E+11 | 0.00 | 2343965.26 | 0.552119E+10 | 0.00 | 0.116300E+09 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 48078342.15 | 0.321250E+11 | 0.00 | 4289018.49 | 0.226272E+10 | 0.00 | 0.188443E+09 | 0.00 | 0.65 |
February | 0.00 | 0.301518E+11 | 0.00 | 380868.16 | 0.252115E+10 | 0.00 | 5141951.79 | 0.00 | 0.65 |
March | 0.00 | 0.312242E+11 | 0.00 | 0.00 | 0.415095E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
April | 0.00 | 0.325570E+11 | 0.00 | 0.00 | 0.825448E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
May | 0.00 | 0.438535E+11 | 0.00 | 0.00 | 0.924025E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
June | 0.00 | 0.446593E+11 | 0.00 | 0.00 | 0.876585E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.299078E+11 | 0.00 | 0.00 | 0.767373E+10 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.402210E+11 | 0.00 | 0.00 | 0.725391E+10 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.389532E+11 | 0.00 | 0.00 | 0.711172E+10 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.00 | 0.418080E+11 | 0.00 | 0.00 | 0.590222E+10 | 0.00 | 0.00 | 0.00 | 0.54 |
November | 313043.44 | 0.404223E+11 | 0.00 | 44973.43 | 0.381802E+10 | 0.00 | 131863.35 | 0.00 | 0.61 |
December | 22879203.56 | 0.348923E+11 | 0.00 | 1312939.58 | 0.291641E+10 | 0.00 | 26643123.57 | 0.00 | 0.64 |
Annual Sum or Average | 71270589.15 | 0.440775E+12 | 0.00 | 6027799.66 | 0.698714E+11 | 0.00 | 0.220360E+09 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.299078E+11 | 0.00 | 0.00 | 0.226272E+10 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 48078342.15 | 0.446593E+11 | 0.00 | 4289018.49 | 0.924025E+10 | 0.00 | 0.188443E+09 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 47690018.47 | 0.185009E+11 | 0.00 | 2179840.98 | 0.273257E+10 | 0.00 | 96281605.41 | 0.00 | 0.62 |
February | 0.00 | 0.199169E+11 | 0.00 | 231420.98 | 0.249446E+10 | 0.00 | 3189013.16 | 0.00 | 0.69 |
March | 0.00 | 0.274663E+11 | 0.00 | 0.00 | 0.241351E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
April | 0.00 | 0.349295E+11 | 0.00 | 0.00 | 0.389442E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
May | 0.00 | 0.404708E+11 | 0.00 | 0.00 | 0.507228E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
June | 0.00 | 0.430746E+11 | 0.00 | 0.00 | 0.468532E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
July | 0.00 | 0.282393E+11 | 0.00 | 0.00 | 0.420413E+10 | 0.00 | 0.00 | 0.00 | 0.66 |
August | 0.00 | 0.388008E+11 | 0.00 | 0.00 | 0.370983E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
September | 0.00 | 0.330236E+11 | 0.00 | 0.00 | 0.448110E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 0.00 | 0.304053E+11 | 0.00 | 0.00 | 0.479272E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
November | 256699.19 | 0.255110E+11 | 0.00 | 32129.79 | 0.376600E+10 | 0.00 | 93703.53 | 0.00 | 0.61 |
December | 19519820.18 | 0.199871E+11 | 0.00 | 751574.39 | 0.342948E+10 | 0.00 | 15765277.52 | 0.00 | 0.61 |
Annual Sum or Average | 67466537.84 | 0.360326E+12 | 0.00 | 3194966.14 | 0.456758E+11 | 0.00 | 0.115330E+09 | 0.00 | 0.69 |
Minimum of Months | 0.00 | 0.185009E+11 | 0.00 | 0.00 | 0.241351E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
Maximum of Months | 47690018.47 | 0.430746E+11 | 0.00 | 2179840.98 | 0.507228E+10 | 0.00 | 96281605.41 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4856245.77 | 0.181066E+10 | 0.00 | 112827.42 | 0.480721E+09 | 0.00 | 6767413.74 | 0.00 | 0.44 |
February | 0.00 | 0.186361E+10 | 0.00 | 13693.95 | 0.463494E+09 | 0.00 | 224728.61 | 0.00 | 0.47 |
March | 0.00 | 0.246874E+10 | 0.00 | 0.00 | 0.532212E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
April | 0.00 | 0.333201E+10 | 0.00 | 0.00 | 0.785218E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
May | 0.00 | 0.515811E+10 | 0.00 | 0.00 | 0.660939E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
June | 0.00 | 0.580723E+10 | 0.00 | 0.00 | 0.564482E+09 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.374417E+10 | 0.00 | 0.00 | 0.590372E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.437927E+10 | 0.00 | 0.00 | 0.655562E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.367376E+10 | 0.00 | 0.00 | 0.770174E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
October | 0.00 | 0.323201E+10 | 0.00 | 0.00 | 0.825098E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
November | 6017.40 | 0.257222E+10 | 0.00 | 0.00 | 0.712324E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
December | 1418139.76 | 0.190119E+10 | 0.00 | 8471.68 | 0.629055E+09 | 0.00 | 281522.45 | 0.00 | 0.42 |
Annual Sum or Average | 6280402.94 | 0.399430E+11 | 0.00 | 134993.05 | 0.766965E+10 | 0.00 | 7273664.80 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 0.181066E+10 | 0.00 | 0.00 | 0.463494E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 4856245.77 | 0.580723E+10 | 0.00 | 112827.42 | 0.825098E+09 | 0.00 | 6767413.74 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3225847.68 | 0.161491E+10 | 0.00 | 173626.02 | 0.309609E+09 | 0.00 | 8730763.31 | 0.00 | 0.58 |
February | 0.00 | 0.173079E+10 | 0.00 | 20984.82 | 0.263230E+09 | 0.00 | 338436.83 | 0.00 | 0.65 |
March | 0.00 | 0.223044E+10 | 0.00 | 0.00 | 0.338910E+09 | 0.00 | 0.00 | 0.00 | 0.71 |
April | 0.00 | 0.297476E+10 | 0.00 | 0.00 | 0.503903E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
May | 0.00 | 0.371880E+10 | 0.00 | 0.00 | 0.532574E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
June | 0.00 | 0.387502E+10 | 0.00 | 0.00 | 0.528134E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
July | 0.00 | 0.251605E+10 | 0.00 | 0.00 | 0.520198E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
August | 0.00 | 0.343302E+10 | 0.00 | 0.00 | 0.468112E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
September | 0.00 | 0.309881E+10 | 0.00 | 0.00 | 0.484745E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
October | 0.00 | 0.269281E+10 | 0.00 | 0.00 | 0.528724E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
November | 4536.05 | 0.219874E+10 | 0.00 | 0.00 | 0.443537E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
December | 307607.24 | 0.171638E+10 | 0.00 | 21750.76 | 0.394029E+09 | 0.00 | 1046430.23 | 0.00 | 0.55 |
Annual Sum or Average | 3537990.97 | 0.318005E+11 | 0.00 | 216361.60 | 0.531570E+10 | 0.00 | 10115630.37 | 0.00 | 0.64 |
Minimum of Months | 0.00 | 0.161491E+10 | 0.00 | 0.00 | 0.263230E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 3225847.68 | 0.387502E+10 | 0.00 | 173626.02 | 0.532574E+09 | 0.00 | 8730763.31 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3905973.51 | 0.306792E+10 | 0.00 | 310964.99 | 0.237258E+09 | 0.00 | 12845876.34 | 0.00 | 0.66 |
February | 0.00 | 0.286510E+10 | 0.00 | 21612.18 | 0.275294E+09 | 0.00 | 352589.36 | 0.00 | 0.65 |
March | 0.00 | 0.297297E+10 | 0.00 | 0.00 | 0.432070E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.00 | 0.323779E+10 | 0.00 | 0.00 | 0.805718E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
May | 0.00 | 0.438669E+10 | 0.00 | 0.00 | 0.850541E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
June | 0.00 | 0.437740E+10 | 0.00 | 0.00 | 0.861732E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.304260E+10 | 0.00 | 0.00 | 0.792614E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 0.00 | 0.398278E+10 | 0.00 | 0.00 | 0.747907E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.389642E+10 | 0.00 | 0.00 | 0.735834E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.00 | 0.410703E+10 | 0.00 | 0.00 | 0.619863E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
November | 6036.54 | 0.394886E+10 | 0.00 | 0.00 | 0.405088E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
December | 409361.31 | 0.342200E+10 | 0.00 | 47696.17 | 0.307648E+09 | 0.00 | 1505773.16 | 0.00 | 0.64 |
Annual Sum or Average | 4321371.36 | 0.433076E+11 | 0.00 | 380273.34 | 0.707157E+10 | 0.00 | 14704238.86 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.286510E+10 | 0.00 | 0.00 | 0.237258E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 3905973.51 | 0.438669E+10 | 0.00 | 310964.99 | 0.861732E+09 | 0.00 | 12845876.34 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3788754.96 | 0.171922E+10 | 0.00 | 143346.36 | 0.325104E+09 | 0.00 | 6362690.64 | 0.00 | 0.62 |
February | 0.00 | 0.186319E+10 | 0.00 | 13323.80 | 0.295474E+09 | 0.00 | 219759.84 | 0.00 | 0.68 |
March | 0.00 | 0.256180E+10 | 0.00 | 0.00 | 0.298065E+09 | 0.00 | 0.00 | 0.00 | 0.78 |
April | 0.00 | 0.333302E+10 | 0.00 | 0.00 | 0.474849E+09 | 0.00 | 0.00 | 0.00 | 0.82 |
May | 0.00 | 0.387881E+10 | 0.00 | 0.00 | 0.597452E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
June | 0.00 | 0.407547E+10 | 0.00 | 0.00 | 0.559615E+09 | 0.00 | 0.00 | 0.00 | 0.76 |
July | 0.00 | 0.277161E+10 | 0.00 | 0.00 | 0.543505E+09 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.376062E+10 | 0.00 | 0.00 | 0.445350E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
September | 0.00 | 0.322326E+10 | 0.00 | 0.00 | 0.555791E+09 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 0.00 | 0.293913E+10 | 0.00 | 0.00 | 0.583856E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
November | 5328.06 | 0.244112E+10 | 0.00 | 0.00 | 0.459598E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
December | 477479.91 | 0.190390E+10 | 0.00 | 21426.68 | 0.420958E+09 | 0.00 | 1042261.62 | 0.00 | 0.61 |
Annual Sum or Average | 4271562.93 | 0.344711E+11 | 0.00 | 178096.84 | 0.555962E+10 | 0.00 | 7624712.09 | 0.00 | 0.69 |
Minimum of Months | 0.00 | 0.171922E+10 | 0.00 | 0.00 | 0.295474E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
Maximum of Months | 3788754.96 | 0.407547E+10 | 0.00 | 143346.36 | 0.597452E+09 | 0.00 | 6362690.64 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.734985E+09 | 0.00 | 99038.02 | 0.00 | 0.00 | 113168.60 | 0.00 | 0.59 |
February | 0.00 | 0.816752E+09 | 0.00 | 3547.20 | 0.00 | 0.00 | 19282.46 | 0.00 | 0.59 |
March | 0.00 | 0.107066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 0.00 | 0.138743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
May | 0.00 | 0.147626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.154705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.120353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.155524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.124831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.131073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.114252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
December | 0.00 | 0.964225E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.00 | 0.144577E+11 | 0.00 | 102585.23 | 0.00 | 0.00 | 132451.06 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.734985E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.00 | 0.155524E+10 | 0.00 | 99038.02 | 0.00 | 0.00 | 113168.60 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.724897E+10 | 0.00 | 997743.26 | 0.00 | 0.00 | 1584228.99 | 0.00 | 0.59 |
February | 0.00 | 0.814435E+10 | 0.00 | 33627.65 | 0.00 | 0.00 | 198626.75 | 0.00 | 0.59 |
March | 0.00 | 0.107001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 0.00 | 0.138651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
May | 0.00 | 0.146048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.154187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.120239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.155386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.123281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.130577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.114144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
December | 0.00 | 0.964820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.00 | 0.143993E+12 | 0.00 | 1031370.91 | 0.00 | 0.00 | 1782855.74 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.724897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.00 | 0.155386E+11 | 0.00 | 997743.26 | 0.00 | 0.00 | 1584228.99 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.726243E+09 | 0.00 | 104572.25 | 0.00 | 0.00 | 194540.14 | 0.00 | 0.59 |
February | 0.00 | 0.814264E+09 | 0.00 | 3344.73 | 0.00 | 0.00 | 20300.95 | 0.00 | 0.59 |
March | 0.00 | 0.106927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 0.00 | 0.138542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
May | 0.00 | 0.146737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.154315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.120164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.155333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.123825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.130588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.114043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
December | 0.00 | 0.963344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.00 | 0.144086E+11 | 0.00 | 107916.99 | 0.00 | 0.00 | 214841.08 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.726243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.00 | 0.155333E+10 | 0.00 | 104572.25 | 0.00 | 0.00 | 194540.14 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:07:05
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.446285E+12 | -0.222732E+10 | 0.00 | -0.913925E+12 | 0.227774E+13 |
February | 0.435137E+12 | -0.254407E+10 | 0.00 | -0.943796E+12 | 0.225389E+13 |
March | 0.573546E+12 | -0.494670E+10 | 0.00 | -0.121135E+13 | 0.268721E+13 |
April | 0.572598E+12 | -0.555745E+10 | 0.00 | -0.161396E+13 | 0.277905E+13 |
May | 0.572598E+12 | -0.699291E+10 | 0.00 | -0.200339E+13 | 0.269772E+13 |
June | 0.589645E+12 | -0.667850E+10 | 0.00 | -0.197019E+13 | 0.280206E+13 |
July | 0.482598E+12 | -0.356246E+10 | 0.00 | -0.135819E+13 | 0.256959E+13 |
August | 0.608245E+12 | -0.610802E+10 | 0.00 | -0.179887E+13 | 0.293285E+13 |
September | 0.480943E+12 | -0.409152E+10 | 0.00 | -0.165062E+13 | 0.241706E+13 |
October | 0.531049E+12 | -0.393450E+10 | 0.00 | -0.156171E+13 | 0.249854E+13 |
November | 0.430028E+12 | -0.280307E+10 | 0.00 | -0.130407E+13 | 0.253971E+13 |
December | 0.417720E+12 | -0.221760E+10 | 0.00 | -0.102955E+13 | 0.249307E+13 |
Annual Sum or Average | 0.614039E+13 | -0.516641E+11 | 0.00 | -0.173596E+14 | 0.309485E+14 |
Minimum of Months | 0.417720E+12 | -0.699291E+10 | 0.00 | -0.200339E+13 | 0.225389E+13 |
Maximum of Months | 0.608245E+12 | -0.221760E+10 | 0.00 | -0.913925E+12 | 0.293285E+13 |