Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:06

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700

Simulation Timestamp: 2023-10-16 09:06:30


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 32271.11 696.69 696.69
Net Site Energy 32271.11 696.69 696.69
Total Source Energy 85115.64 1837.54 1837.54
Net Source Energy 85115.64 1837.54 1837.54


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 288.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1598.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7175.32 0.00 0.00
Interior Lighting 2025.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 322.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 3258.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1303.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 600.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 380.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7967.46
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 641.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 24165.65 930.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7175.32 0.00 10247.63
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 288.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 1598.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7175.32 0.00 0.00
Interior Lighting LightsWired 2025.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 322.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5334.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 54.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ComputerHVAC 1349.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 1303.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 600.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 380.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7967.46
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 641.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 288.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 1598.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7175.32 0.00 0.00
Interior Lighting GENERAL 2025.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 322.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 3258.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 1303.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 600.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 380.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7967.46
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 641.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 83.84 20.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 154.91 0.00 0.22
Other 387.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 521.71 20.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 154.91 0.00 0.22


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 83.84 20.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 154.91 0.00 0.22
Other 387.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 521.71 20.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 154.91 0.00 0.22


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 24165.654 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 24165.654 100.00
     
Total On-Site and Utility Electric Sources 24165.654 100.00
Total Electricity End Uses 24165.654 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 10247.63 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 10247.63 100.00
Total Water End Uses 10247.63 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 1.17
Time Setpoint Not Met During Occupied Cooling 253.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 5943.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EnergyConsumptionDistrictHeatingCoolingMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:06
RunPeriod RUNPERIOD 1
Weather File El Paso International Ap Ut TX USA TMY3 WMO#=722700
Latitude [deg] 31.77
Longitude [deg] -106.5
Elevation [m] 1186.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 5.8895 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 5.8895 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 5.8895 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 5.8895 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 8.8011 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 8.8011 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 8.8011 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 5.8895 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 5.9168 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 5.9168 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 5.8895 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 5.8895 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 5.8895 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 5.8895 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 5.8895 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 5.8895 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 5.8895 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 5.8895 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 5.8895 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 5.8895 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 5.8895 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 5.8895 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 5.8895 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 5.8895 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 5.8895 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 5.8895 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 8.8011 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 8.8011 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 8.8011 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 5.8895 18.58 484.4232  
Total 46320.38             5.9168 9.29 17.8789  
Conditioned Total 46320.38             5.9168 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 1.8190 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] District Heating [W] Water [m3/s]
Time of Peak 02-AUG-07:00 27-DEC-07:10 - - - - - - - - 07-AUG-13:00 01-FEB-00:40 15-JUN-12:00
Heating 0.00 601708.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.25 0.00
Cooling 267564.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370232.07 0.00 0.00
Interior Lighting 171235.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 778371.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 185184.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 113032.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 49441.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 45559.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 28923.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1610390.17 630632.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370232.07 12.25 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] District Heating [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.25 0.00
  Boiler 0.00 601708.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 267564.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370232.07 0.00 0.00
Interior Lighting LightsWired 171235.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 3372.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ComputerHVAC 68333.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 113032.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 49441.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 45559.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 28923.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 312.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01
Cooling 5063.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7574.75 0.00
Interior Lighting 6413.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1021.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 46480.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 10318.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 4128.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1902.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1204.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 695.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 76532.63 1008.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7574.75 0.01


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 6.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 109.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 163.53 0.00
Interior Lighting 138.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 22.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 222.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 89.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 41.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 26.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1652.25 21.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 163.53 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 6.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 109.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 163.53 0.00
Interior Lighting 138.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 22.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 222.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 89.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 41.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 26.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1652.25 21.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 163.53 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 5.59
DATACENTER_BOT_ZN_6 DIRECT AIR 0.528882
DATACENTER_MID_ZN_6 DIRECT AIR 5.03
DATACENTER_TOP_ZN_6 DIRECT AIR 0.510649
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 6.07 0.313098 0.320000 1.94 0.834928 0.500000 0.001217 0.000149 1.94 12.80 0.008000
CORE_MID VAV BOX COMPONENT 57.06 0.333315 0.333000 19.00 0.888839 0.500000 0.001143 0.003413 19.00 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 5.68 0.334827 0.343000 1.95 0.892872 0.500000 0.001138 0.000710 2.78 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 1.05 0.227332 0.232000 0.243724 0.606219 0.500000 0.001676 0.000077 0.302566 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 0.984210 0.156374 0.200000 0.196842 0.416998 0.500000 0.002436 0.000056 0.218614 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.17 0.204978 0.209000 0.243512 0.546607 0.500000 0.001859 0.000098 0.384609 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.31 0.117631 0.200000 0.261675 0.313682 0.500000 0.003239 0.000044 0.261675 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 9.74 0.245182 0.245000 2.39 0.653819 0.500000 0.001554 0.001583 6.22 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 10.16 0.151516 0.200000 2.03 0.404042 0.500000 0.002515 0.001051 4.13 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 10.86 0.219882 0.220000 2.39 0.586353 0.500000 0.001733 0.001568 6.16 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 10.91 0.141007 0.200000 2.18 0.376018 0.500000 0.002702 0.000970 3.81 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.13 0.210815 0.216000 0.244695 0.562173 0.500000 0.001807 0.000212 0.833514 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.05 0.147167 0.200000 0.209157 0.392446 0.500000 0.002589 0.000140 0.549558 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.23 0.193489 0.200000 0.246862 0.515971 0.500000 0.001969 0.000210 0.826453 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.20 0.128204 0.200000 0.240095 0.341876 0.500000 0.002972 0.000133 0.524039 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 16975.39 0.000149 342.21
CORE_MID VAV BOX REHEAT COIL 390168.79 0.003413 9089.93
CORE_TOP VAV BOX REHEAT COIL 81119.37 0.000710 2141.35
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 8820.25 0.000077 232.89
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 6369.50 0.000056 168.14
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 11201.06 0.000098 295.62
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 5057.62 0.000044 115.95
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 180949.54 0.001583 4772.81
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 120166.30 0.001051 3169.47
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 179251.00 0.001568 4728.05
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 110884.12 0.000970 2924.87
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 24229.60 0.000212 638.93
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 15974.60 0.000140 421.24
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 24024.67 0.000210 633.53
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 15233.91 0.000133 401.72
VAV_BOT WITH REHEAT HEATING COIL 49032.24 0.000429 808.08
VAV_MID WITH REHEAT HEATING COIL 462307.90 0.004044 7608.24
VAV_TOP WITH REHEAT HEATING COIL 45539.30 0.000398 756.42
CAV_BAS HEATING COIL 241179.50 0.002110 5359.89
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:IdealLoadsAirSystem

Design Size Maximum Heating Air Flow Rate [m3/s] Design Size Maximum Cooling Air Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT 0.338402 24.50
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 5.29 2.89 10.58 2.89 9.83 9.83 0.300000 0.294044 9.83
VAV_MID WITH REHEAT 49.37 27.99 98.74 31.22 91.25 91.25 0.300000 0.342182 91.25
VAV_TOP WITH REHEAT 5.15 2.89 10.29 5.52 9.98 9.98 0.300000 0.552667 9.98
CAV_BAS 5.59 5.59 5.59 5.59 5.59 5.59 1.00 1.00 5.59
AIRLOOP DATACENTER BOT 0.528882 0.528882 0.528882 0.528882 0.528882 0.528882 1.00 1.00 0.528882
AIRLOOP DATACENTER MID 5.03 5.03 5.03 5.03 5.03 5.03 1.00 1.00 5.03
AIRLOOP DATACENTER TOP 0.510649 0.510649 0.510649 0.510649 0.510649 0.510649 1.00 1.00 0.510649
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 9.83  
VAV_MID WITH REHEAT_OA_CONTROLLER 91.25  
VAV_TOP WITH REHEAT_OA_CONTROLLER 9.98  
CAV_BAS_OA_CONTROLLER 5.59  
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.528882 0.015633
AIRLOOP DATACENTER MID_OA_CONTROLLER 5.03 0.156328
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.510649 0.015633
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 27.81 6.67 10.77 0.007244 0.007000 184465.95 0.007848 9.83
VAV_MID WITH REHEAT COOLING COIL 28.29 6.67 10.77 0.007259 0.007000 1762325.80 0.074973 91.25
VAV_TOP WITH REHEAT COOLING COIL 27.59 6.67 10.77 0.007235 0.007000 184830.58 0.007863 9.98
CAV_BAS COOLING COIL 27.28 6.67 11.21 0.007404 0.007000 101506.47 0.004318 5.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 9.83
VAV_MID WITH REHEAT FAN 91.25
VAV_TOP WITH REHEAT FAN 9.98
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.007848 0.000061
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000429  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.074973 0.000006
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.004044  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.007863 0.000061
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000398  
CAV_BAS_COOLC_CONTROLLER 0.004318 0.000110
CAV_BAS_HEATC_CONTROLLER 0.002110  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 5.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BOT COOLING COIL 0.528882 9863.77 5526.29 0.000242
AIRLOOP DATACENTER MID COOLING COIL 5.03 93887.76 52572.29 0.002299
AIRLOOP DATACENTER TOP COOLING COIL 0.510649 9534.03 5338.85 0.000233
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.528882 0.528882 0.528882 0.528882 9863.77 9863.77 741.51 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 5.03 5.03 5.03 5.03 93887.76 93887.76 7415.12 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.510649 0.510649 0.510649 0.510649 9534.03 9534.03 741.51 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BOT SUPPLY FAN 0.528882
AIRLOOP DATACENTER MID SUPPLY FAN 5.03
AIRLOOP DATACENTER TOP SUPPLY FAN 0.510649
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BOT HEATING COIL 0.528882 9863.77 0.000242
AIRLOOP DATACENTER MID HEATING COIL 5.03 93887.76 0.002299
AIRLOOP DATACENTER TOP HEATING COIL 0.510649 9534.03 0.000233
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 741.51
AIRLOOP DATACENTER MID_SUPPHEATCOIL 7415.12
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 741.51
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.095002 19382.66  
HEATSYS1 PUMP 0.017396 5187.08 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.095002 11.40
HEATSYS1 0.017396 2.09
COOLSYS1_SUPPLY 0.095002 11.40
SINGLE WATER PLANT LOOP 0.002774 0.332923
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.095002 0.095002 398773.00 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 1988484.66 1988484.66 0.017396
CENTRAL BOILER 114279.68 114279.68 0.002774
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.095002 13419.27
PLANT CIRC PUMP 0.002774 700.59
SWHSYS1 PUMP 0.000440 5.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.095002 0.048076 1132845.03 1138218.22 0.056326
COOLSYS1 CHILLER2 0.095002 0.048076 1132845.03 1138218.22 0.056326
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.002774 35644.39 19607.73 17822.20 1996.20 5788.54
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.112652 13.52
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.112652 33592.53
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 50.20 1351589.95 10.04 168948.74
TOWERWATERSYS COOLTOWER 2 50.20 1351589.95 10.04 168948.74
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 45
WSHPPLANT OPERATION SCHEME 0.058505
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.30 11.20 6.80 8.10 10.30 12.50 19.20 23.80 27.90 27.50 26.30 23.40


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 El Paso International Ap Ut TX USA TMY3 WMO#=722700 31.77 -106.50 -7.00 1186.00 87865 1.0443


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 17.94 21.10 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 105.88 86.92 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 105.88 86.92 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 5.889 4.842 0.000 0.000 0.000 0.000 10.731 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 8.801 215.299 0.000 0.000 0.000 0.000 224.100 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 8.801 215.299 0.000 0.000 0.000 0.000 224.100 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 8.801 215.299 0.000 0.000 0.000 0.000 224.100 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 5.889 484.423 0.000 0.000 0.000 0.000 490.313 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 16369.361 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16369.361
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 14700.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14700.837
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 14700.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14700.837
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 14700.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14700.837
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 1845.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.837
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 1845.877 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.877
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 1845.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.837
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 1845.877 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.877
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 1845.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.837
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 1845.877 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.877
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 4615.459 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4615.459
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 318.624 8.801 163.514 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 318.624
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 318.624 8.801 163.514 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 318.624
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 318.624 8.801 163.514 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 318.624


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.498 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.416 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.867 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.5004
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.5391
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.3683
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 0.9868
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 0.9868
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
47 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
48 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
49 0 21.361010 0.87247630E-01 5.4456762  
50 9 0.14091426E-14 0.48101397E-16 -0.12271849E-09 -0.49605034E-17
51 8 0.18065296E-07 0.19413100E-12 0.33649602E-03 -0.20540863E-09
52 7 -0.11004888E-01 0.10546945E-07 -0.21303752E-01 0.12512956E-03
53 6 0.37174157 0.37425545E-05 0.44335749 -0.43515980E-02
54 5 -4.8625044 0.14213861E-03 -4.2200868 0.59116134E-01
55 4 31.551289 0.11806248E-02 20.574731 -0.40285082
56 3 -108.13650 0.26081321E-02 -53.912227 1.4705586
57 2 194.06739 0.14847903E-02 76.306869 -2.8520668
58 1 -170.03224 0.16027253E-03 -54.802483 2.7257428
59 0 57.057407 0.92345258E-06 15.636386  
60 9 0.11726792E-14 0.46876770E-16 -0.12664795E-09 -0.40425794E-17
61 8 0.18621286E-07 0.18477046E-12 0.34269676E-03 -0.21173044E-09
62 7 -0.11191167E-01 0.99660246E-08 -0.21572393E-01 0.12724763E-03
63 6 0.37680492 0.35261678E-05 0.44770143 -0.44112820E-02
64 5 -4.9119389 0.13358806E-03 -4.2535898 0.59729078E-01
65 4 31.770087 0.11071467E-02 20.706000 -0.40575564
66 3 -108.60241 0.24410452E-02 -54.171883 1.4772891
67 2 194.52961 0.13872791E-02 76.544434 -2.8594062
68 1 -170.20315 0.14950961E-03 -54.870487 2.7287383
69 0 57.057407 0.85997654E-06 15.624277  
70 9 0.98458787E-15 0.55454857E-16 -0.10492535E-09 -0.15601002E-17
71 8 0.15540463E-07 0.23311053E-12 0.30746206E-03 -0.17670042E-09
72 7 -0.10129638E-01 0.13130386E-07 -0.20040359E-01 0.11517765E-03
73 6 0.34794661 0.47273228E-05 0.42286390 -0.40711180E-02
74 5 -4.6301347 0.18177508E-03 -4.0616887 0.56235001E-01
75 4 30.522476 0.15264987E-02 19.953355 -0.38919251
76 3 -105.94476 0.34047073E-02 -52.682811 1.4388992
77 2 191.89184 0.19546755E-02 75.183526 -2.8175246
78 1 -169.22736 0.21263380E-03 -54.483619 2.7116363
79 0 57.057407 0.12355163E-05 15.695393  
80 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
81 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
82 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
83 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
84 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
85 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
86 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
87 0 1.0055995 0.48413807E-04 60.838472  
88 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
89 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
90 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
91 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
92 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
93 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
94 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
95 0 1.0055995 0.48413807E-04 60.838472  
96 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
97 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
98 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
99 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
100 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
101 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
102 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
103 0 1.0055995 0.48413807E-04 60.838472  
104 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
105 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
106 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
107 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
108 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
109 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
110 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
111 0 1.0055995 0.48413807E-04 60.838472  
112 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
113 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
114 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
115 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
116 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
117 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
118 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
119 0 1.0055995 0.48413807E-04 60.838472  
120 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
121 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
122 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
123 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
124 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
125 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
126 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
127 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.4237_SHGC_EAST_0.25 35 1 VerySmooth 2.408 2.408 1.000 0.251    
2 WINDOW_U_0.4237_SHGC_SOUTH_0.25 36 1 VerySmooth 2.408 2.408 1.000 0.251    
3 WINDOW_U_0.4237_SHGC_WEST_0.25 37 1 VerySmooth 2.408 2.408 1.000 0.251    
4 WINDOW_U_0.4237_SHGC_NORTH_0.25 38 1 VerySmooth 2.408 2.408 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   2.98522E-002 0.16139 0.62038 0.62038 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.12245 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   2.98522E-002 0.16139 0.62038 0.62038 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.12245 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   2.98522E-002 0.16139 0.62038 0.62038 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.12245 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   2.98522E-002 0.16139 0.62038 0.62038 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.12245 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.496 7.5104E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 2.856E-002 9.114E-005 1.371E-004 0.120 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 1.904E-002 9.429E-005 1.384E-004 0.124 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 2.856E-002 9.114E-005 1.371E-004 0.120 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 1.904E-002 9.429E-005 1.384E-004 0.124 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 2.856E-002 9.114E-005 1.424E-004 0.120 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 1.904E-002 9.429E-005 1.424E-004 0.124 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 2.856E-002 9.114E-005 1.424E-004 0.120 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 1.904E-002 9.429E-005 1.424E-004 0.124 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 2.856E-002 9.114E-005 1.424E-004 0.120 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 1.904E-002 9.429E-005 1.424E-004 0.124 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 2.856E-002 9.114E-005 1.424E-004 0.120 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 1.904E-002 9.429E-005 1.424E-004 0.124 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 4.231E-002 1.187E-005 1.424E-004 3.506E-002 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 4.231E-002 1.187E-005 1.424E-004 3.506E-002 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 4.231E-002 1.187E-005 1.096E-005 3.506E-002 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9226E-003
2 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9238E-003
3 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1412E-003
4 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.1422E-003
5 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.2295E-003
6 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2303E-003
7 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2447E-003
8 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2452E-003
9 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9511E-003
10 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0348E-003
11 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1652E-003
12 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.2379E-003
13 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.2499E-003
14 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.3097E-003
15 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2574E-003
16 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2891E-003
17 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.1305E-002
18 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.7294E-002
19 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 9.1591E-002
20 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.0913E-002
21 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.3066E-002
22 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.4553E-002
23 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6042E-002
24 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.1095E-003
25 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9523E-003
26 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0398E-003
27 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1664E-003
28 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.2429E-003
29 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.2509E-003
30 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.3134E-003
31 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2577E-003
32 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2900E-003
33 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9225E-003
34 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9237E-003
35 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1411E-003
36 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.1422E-003
37 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.2294E-003
38 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2302E-003
39 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2447E-003
40 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2451E-003
41 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6475E-003
42 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.7899E-003
43 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.4897E-003
44 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.6398E-003
45 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.4121E-003
46 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.4832E-003
47 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.1302E-003
48 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1521E-003
49 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.9914E-002
50 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.5128E-002
51 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.7649E-002
52 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.3486E-002
53 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.1333E-002
54 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.3044E-002
55 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6787E-002
56 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 9.9865E-003
57 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6081E-003
58 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.6643E-003
59 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.4394E-003
60 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.4801E-003
61 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.3895E-003
62 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.4054E-003
63 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.1303E-003
64 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1525E-003
65 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2520E-003
66 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2532E-003
67 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0683E-003
68 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0693E-003
69 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.4647E-004
70 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.4715E-004
71 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2447E-003
72 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2452E-003
73 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2785E-003
74 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3466E-003
75 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0898E-003
76 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1431E-003
77 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.6337E-004
78 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0002E-003
79 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2577E-003
80 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2900E-003
81 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.9710E-002
82 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1317E-002
83 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5282E-002
84 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 8.5965E-003
85 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5263E-002
86 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 6.0508E-003
87 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6042E-002
88 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.1067E-003
89 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2779E-003
90 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3448E-003
91 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0891E-003
92 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1415E-003
93 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.6260E-004
94 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.9799E-004
95 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2574E-003
96 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2891E-003
97 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2519E-003
98 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2531E-003
99 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0683E-003
100 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0692E-003
101 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.4643E-004
102 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.4708E-004
103 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2447E-003
104 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2451E-003
105 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.5674E-003
106 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.6239E-003
107 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.3893E-003
108 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.4302E-003
109 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.3538E-003
110 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.3696E-003
111 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1303E-003
112 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1525E-003
113 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9124E-002
114 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.4820E-002
115 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.6688E-002
116 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.3112E-002
117 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0597E-002
118 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.2753E-002
119 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.6787E-002
120 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 9.9865E-003
121 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.6057E-003
122 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.7434E-003
123 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.4382E-003
124 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.5826E-003
125 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.3762E-003
126 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.4462E-003
127 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1302E-003
128 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1521E-003
129 Clear Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 7.4533E-002
130 Clear Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 4.8801E-002
131 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 8.1027E-002
132 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.3117E-002
133 Intermediate Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 6.5013E-002
134 Intermediate Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 3.4003E-002
135 Overcast Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 3.0133E-002
136 Overcast Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 1.4574E-002
137 Clear Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.4531E-002
138 Clear Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.0987E-002
139 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.2066E-002
140 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.9027E-002
141 Intermediate Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.5685E-002
142 Intermediate Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.8381E-002
143 Overcast Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.0820E-002
144 Overcast Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.4729E-002
145 Clear Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.3667E-002
146 Clear Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.6629E-002
147 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 1.8837E-002
148 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.3168E-002
149 Intermediate Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 1.8766E-002
150 Intermediate Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.0248E-002
151 Overcast Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.0133E-002
152 Overcast Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.4571E-002
153 Clear Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.3673E-002
154 Clear Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.0583E-002
155 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.1021E-002
156 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.8535E-002
157 Intermediate Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.4893E-002
158 Intermediate Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.8013E-002
159 Overcast Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.0820E-002
160 Overcast Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.4729E-002
161 Clear Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 7.4490E-002
162 Clear Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 4.8875E-002
163 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 8.0988E-002
164 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.3205E-002
165 Intermediate Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 6.5036E-002
166 Intermediate Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 3.4073E-002
167 Overcast Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 3.0168E-002
168 Overcast Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 1.4602E-002
169 Clear Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.4514E-002
170 Clear Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.1005E-002
171 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.2057E-002
172 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.9045E-002
173 Intermediate Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.5699E-002
174 Intermediate Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.8413E-002
175 Overcast Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.0854E-002
176 Overcast Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.4757E-002
177 Clear Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.3638E-002
178 Clear Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.6636E-002
179 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 1.8817E-002
180 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.3174E-002
181 Intermediate Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 1.8776E-002
182 Intermediate Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.0263E-002
183 Overcast Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.0168E-002
184 Overcast Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.4599E-002
185 Clear Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.3656E-002
186 Clear Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.0601E-002
187 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.1012E-002
188 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.8552E-002
189 Intermediate Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.4906E-002
190 Intermediate Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.8043E-002
191 Overcast Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.0854E-002
192 Overcast Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.4757E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 67144.14640 67144.14640 5.58960 5.58960 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.48000 6.85626E-003 2779.42662 149.60210 1.20019 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20019 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:10:00 -5.20000 2.80840E-003 2779.42662 149.60210 1.20019 0.00000
3 CORE_BOTTOM Cooling 72971.55349 72971.55349 6.07491 6.07491 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.48000 6.85626E-003 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:30:00 -5.20000 2.80840E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 685633.48863 685633.48863 57.06449 57.06449 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.48000 6.85626E-003 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 224233.06136 224233.06136 10.89469 10.89469 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 68252.50582 68252.50582 5.68068 5.68068 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 28.48000 6.85626E-003 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 56807.06045 56807.06045 2.78418 2.78418 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 12505.62529 12505.62529 1.05054 1.05054 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 38.10000 6.87148E-003 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 6179.06887 6179.06887 0.30257 0.30257 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 11716.14782 11716.14782 0.98421 0.98421 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 32.05500 6.86186E-003 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 4461.05375 4461.05375 0.21861 0.21861 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 13869.78726 13869.78726 1.16513 1.16513 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 37.77500 6.87096E-003 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 7843.24976 7843.24976 0.38461 0.38461 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 15575.11947 15575.11947 1.30837 1.30837 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 36.62667 6.86912E-003 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 2774.04895 2774.04895 0.13546 0.13546 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 115951.78154 115951.78154 9.74053 9.74053 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 38.10000 6.87148E-003 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 126632.36678 126632.36678 6.22136 6.22136 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 120918.46025 120918.46025 10.15769 10.15769 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 32.42333 6.86244E-003 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 84092.48450 84092.48450 4.13180 4.13180 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 129296.38666 129296.38666 10.86153 10.86153 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 37.88333 6.87114E-003 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 125445.00252 125445.00252 6.16283 6.16283 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 129930.35564 129930.35564 10.91472 10.91472 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 36.45333 6.86884E-003 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 77603.45925 77603.45925 3.81199 3.81199 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 13485.48710 13485.48710 1.13285 1.13285 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 37.84000 6.87107E-003 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 16952.22344 16952.22344 0.83351 0.83351 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 12449.16157 12449.16157 1.04578 1.04578 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 33.16000 6.86360E-003 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 11176.44615 11176.44615 0.54956 0.54956 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 14693.35467 14693.35467 1.23431 1.23431 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 38.10000 6.87148E-003 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 16808.96237 16808.96237 0.82645 0.82645 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 14290.62797 14290.62797 1.20047 1.20047 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 36.62667 6.86912E-003 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 10658.59075 10658.59075 0.52404 0.52404 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -5.20000 2.80840E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 7983.08465 7983.08465 0.52888 0.52888 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 25.18667 6.85117E-003 36.20274 1.94861 1.56328E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56328E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:30:00 -5.20000 2.80840E-003 36.20274 1.94861 1.56328E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 75904.00681 75904.00681 5.02867 5.02867 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 25.18667 6.85117E-003 36.20274 1.94861 0.15633 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15633 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 05:40:00 -5.20000 2.80840E-003 36.20274 1.94861 0.15633 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 7706.87511 7706.87511 0.51065 0.51065 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 34.33000 6.86546E-003 36.20274 1.94861 1.56328E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56328E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 05:40:00 -5.20000 2.80840E-003 36.20274 1.94861 1.56328E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 369705.81530 369705.81530 24.49562 24.49562 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 26.27000 6.85284E-003 783.67941 42.18139 0.33840 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33840 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 01:00:00 -5.20000 2.80840E-003 783.67941 42.18139 0.33840 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 147828.70 9.82752 9.82752 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 40027.75 2.11907 2.11907 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1356411.74 91.24587 91.24587 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 479226.33 31.22268 31.22268 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 14:50:00
5 VAV_TOP WITH REHEAT Cooling Sensible 154543.68 9.98385 9.98385 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 47718.24 5.51774 5.51774 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:10:00
7 CAV_BAS Cooling Sensible 74790.05 5.58960 5.58960 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 56928.82 1.20019 1.20019 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00
9 AIRLOOP DATACENTER BOT Cooling Sensible 7927.27 0.52888 0.52888 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BOT Heating Sensible 741.51 1.56328E-002 1.56328E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00
11 AIRLOOP DATACENTER MID Cooling Sensible 75558.34 5.02867 5.02867 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER MID Heating Sensible 7415.12 0.15633 0.15633 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00
13 AIRLOOP DATACENTER TOP Cooling Sensible 7731.80 0.51065 0.51065 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER TOP Heating Sensible 741.51 1.56328E-002 1.56328E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.58960
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.07491
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.31310
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.32000
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.94397
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.83493
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.21687E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.48508E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.94397
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16975.38746
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.48508E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 342.21049
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 57.06449
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33331
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33300
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 19.00247
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.88884
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.14306E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.41337E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 19.00247
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 390168.79497
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.41337E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 9089.93442
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.68068
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33483
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.34300
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.94847
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.89287
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.13790E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.09668E-004
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.78418
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 81119.37269
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.09668E-004
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2141.34905
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.05054
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22733
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.23200
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24372
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.60622
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.67596E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.71634E-005
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.30257
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8820.24500
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.71634E-005
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 232.88983
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.98421
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15637
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.19684
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.41700
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.43646E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.57232E-005
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.21861
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6369.49866
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.57232E-005
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 168.13868
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.16513
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20498
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20900
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24351
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54661
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.85874E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.79917E-005
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.38461
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11201.05544
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.79917E-005
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 295.62112
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.30837
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11763
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.26167
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.31368
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.23895E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.42463E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.26167
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5057.62043
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.42463E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 115.95436
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.74053
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24518
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.24500
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.38643
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65382
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.55395E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.58303E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.22136
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 180949.54273
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.58303E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4772.80804
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.15769
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15152
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.03154
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.40404
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.51459E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.05127E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.13180
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 120166.30104
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.05127E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3169.46578
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.86153
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21988
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.38954
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58635
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.73275E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.56817E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 6.16283
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 179251.00021
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.56817E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4728.05303
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.91472
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14101
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.18294
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37602
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.70199E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.70063E-004
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.81199
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 110884.12255
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.70063E-004
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2924.87178
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.13285
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21081
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.21600
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24469
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.56217
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.80727E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.11971E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.83351
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 24229.59621
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.11971E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 638.93038
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.04578
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14717
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20916
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.39245
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.58889E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.39753E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.54956
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15974.59949
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.39753E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 421.24017
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.23431
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19349
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24686
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51597
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.96910E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.10178E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.82645
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 24024.67413
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.10178E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 633.53080
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.20047
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12820
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24009
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34188
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.97183E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.33273E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.52404
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15233.91006
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.33273E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 401.72174
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.52888
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.02867
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.51065
215 ZoneHVAC:IdealLoadsAirSystem AIRLOOP DATACENTER BASEMENT Design Size Maximum Heating Air Flow Rate [m3/s] 0.33840
216 ZoneHVAC:IdealLoadsAirSystem AIRLOOP DATACENTER BASEMENT Design Size Maximum Cooling Air Flow Rate [m3/s] 24.49562
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.29158
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.88973
219 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.58316
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 2.88973
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.82752
222 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.82752
223 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
224 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.29404
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 49.36948
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 27.99292
227 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 98.73896
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 31.22268
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 91.24587
230 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 91.24587
231 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
232 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.34218
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.14705
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.88928
235 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.29409
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 5.51774
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.98385
238 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.98385
239 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
240 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.55267
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.58960
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.58960
243 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 5.58960
244 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 5.58960
245 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 5.58960
246 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 5.58960
247 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
249 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.52888
250 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.52888
251 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.52888
252 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.52888
253 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.52888
254 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.52888
255 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
256 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
257 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.02867
258 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.02867
259 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 5.02867
260 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 5.02867
261 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 5.02867
262 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 5.02867
263 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
265 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.51065
266 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.51065
267 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.51065
268 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.51065
269 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.51065
270 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.51065
271 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
273 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.82752
274 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 91.24587
275 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.98385
276 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 5.58960
277 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.52888
278 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 5.02867
279 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.51065
280 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.82752
281 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.81324
282 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
283 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.76799
284 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.24445E-003
285 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
286 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 184465.94795
287 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.84761E-003
288 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.82752
289 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 49032.24098
290 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.28955E-004
291 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 808.07782
292 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.82752
293 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 7.84761E-003
294 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 6.06797E-005
295 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 4.28955E-004
296 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 91.24587
297 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 28.28723
298 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
299 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.76804
300 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.25933E-003
301 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
302 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 1762325.80285
303 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.49734E-002
304 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 91.24587
305 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 462307.89916
306 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.04447E-003
307 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 7608.23645
308 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 91.24587
309 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 7.49734E-002
310 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 6.35146E-006
311 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 4.04447E-003
312 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.98385
313 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.59429
314 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
315 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.76795
316 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.23523E-003
317 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
318 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 184830.57900
319 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.86312E-003
320 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.98385
321 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 45539.29707
322 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.98398E-004
323 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 756.42192
324 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.98385
325 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 7.86312E-003
326 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 6.05600E-005
327 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 3.98398E-004
328 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.58960
329 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 27.27826
330 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
331 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.20598
332 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.40358E-003
333 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
334 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 101506.46713
335 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.31832E-003
336 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.58960
337 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 241179.49710
338 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.10994E-003
339 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 5359.88546
340 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 5.58960
341 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 4.31832E-003
342 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.10272E-004
343 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.10994E-003
344 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.52888
345 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56328E-002
346 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.52888
347 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9863.76846
348 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 5526.29101
349 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.41563E-004
350 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.52888
351 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.52888
352 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.52888
353 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.52888
354 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9863.76846
355 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9863.76846
356 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 741.51240
357 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
358 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.52888
359 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.52888
360 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9863.76846
361 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.41563E-004
362 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 741.51240
363 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.02867
364 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15633
365 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 5.02867
366 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 93887.75706
367 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 52572.29061
368 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.29931E-003
369 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 5.02867
370 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 5.02867
371 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 5.02867
372 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 5.02867
373 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 93887.75706
374 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 93887.75706
375 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 7415.12401
376 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
377 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 5.02867
378 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 5.02867
379 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 93887.75706
380 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.29931E-003
381 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 7415.12401
382 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.51065
383 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56328E-002
384 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.51065
385 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9534.02650
386 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 5338.84696
387 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.33488E-004
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.51065
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.51065
390 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.51065
391 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.51065
392 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9534.02650
393 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9534.02650
394 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 741.51240
395 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
396 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.51065
397 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.51065
398 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9534.02650
399 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.33488E-004
400 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 741.51240
401 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 9.50025E-002
402 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 19382.65956
403 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 9.50025E-002
404 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 11.40030
405 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 9.50025E-002
406 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 9.50025E-002
407 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 398772.99945
408 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
409 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 1.73961E-002
410 PlantLoop HEATSYS1 Plant Loop Volume [m3] 2.08754
411 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 1.73961E-002
412 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 5187.07997
413 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
414 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 1988484.65539
415 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 1988484.66000
416 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 1.73961E-002
417 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 9.50025E-002
418 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 11.40030
419 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 9.50025E-002
420 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 13419.26904
421 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 9.50025E-002
422 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 4.80758E-002
423 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1132845.03482
424 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1138218.22000
425 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 5.63262E-002
426 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 9.50025E-002
427 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 4.80758E-002
428 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1132845.03482
429 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1138218.22000
430 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 5.63262E-002
431 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 2.77436E-003
432 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 0.33292
433 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 2.77436E-003
434 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 700.59355
435 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 2.77436E-003
436 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 35644.39112
437 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 19607.72920
438 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 17822.19556
439 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 1996.19659
440 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 5788.53875
441 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 114279.67748
442 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 114279.68000
443 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 2.77436E-003
444 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
445 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
446 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
447 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 5.95776
448 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
449 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.11265
450 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 13.51829
451 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.11265
452 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 33592.52659
453 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 50.19929
454 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1351589.95241
455 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 10.03986
456 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 168948.74405
457 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 50.19929
458 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1351589.95241
459 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 10.03986
460 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 168948.74405
461 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 45 5.85050E-002
462 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 45 5.85050E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 16097.85
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 369765.68
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 76890.46
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 8360.81
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 6037.44
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 10616.73
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 4793.42
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 171490.63
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 113884.11
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 169881.19
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 105088.75
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 22961.94
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 15138.78
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 22767.77
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 14436.94
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 37854.62
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 355889.02
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 35725.18
19 Coil:Heating:Water CAV_BAS HEATING COIL 190840.96


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 286133.58 172668.32 113465.26 0.60 53011.55 537.67
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2675770.07 1610809.07 1064961.00 0.60 486257.13 4931.89
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 289655.30 175004.37 114650.94 0.60 54184.85 549.57
4 Coil:Cooling:Water CAV_BAS COOLING COIL 158250.09 96376.25 61873.84 0.61 27672.21 280.67


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.84 23.33
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.84 23.33


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   105.88 200.61 105.88 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_NORTH_0.25 N/A 2.408 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_NORTH_0.25 N/A 2.408 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_NORTH_0.25 N/A 2.408 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_NORTH_0.25 N/A 2.408 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_NORTH_0.25 N/A 2.408 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   71.89 133.74 71.89 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_EAST_0.25 N/A 2.408 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_EAST_0.25 N/A 2.408 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_EAST_0.25 N/A 2.408 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   105.88 200.61 105.88 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_SOUTH_0.25 N/A 2.408 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_SOUTH_0.25 N/A 2.408 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_SOUTH_0.25 N/A 2.408 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_SOUTH_0.25 N/A 2.408 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_SOUTH_0.25 N/A 2.408 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   71.89 133.74 71.89 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_WEST_0.25 N/A 2.408 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_WEST_0.25 N/A 2.408 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_WEST_0.25 N/A 2.408 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_NORTH_0.25 N/A 2.408 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_EAST_0.25 N/A 2.408 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_SOUTH_0.25 N/A 2.408 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_WEST_0.25 N/A 2.408 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_NORTH_0.25 N/A 2.408 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_EAST_0.25 N/A 2.408 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_SOUTH_0.25 N/A 2.408 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4237_SHGC_WEST_0.25 N/A 2.408 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.940 0.824   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.2875386010 0.2440334597 Pass Pass 0.9611801083 1.5387721071 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 9.2492859808E-002 0.1700436386 Pass Pass 0.1329363518 0.3386375369 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 5.5453932591E-002 0.1125712522 Pass Pass 0.1052075721 0.3064867333 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 3.3835845946E-002 5.4312810988E-002 Pass Pass 7.7463595221E-003 8.7933402173E-002 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 8.0110815104E-002 0.1231471448 Pass Pass 0.1324062070 0.3380833530 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.1233053131 0.1769382731 Pass Pass 0.1337823053 0.3403949398 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.1758846669 0.2958156003 Pass Pass 0.1462179922 0.3582340500 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 0.1287258057 0.2400854459 Pass Pass 0.1318078406 0.3346365916 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 4.9808062168E-002 7.0886997472E-002 Pass Pass 0.1045269505 0.3052608366 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 8.9223881145E-002 0.1270987819 Pass Pass 0.1056978097 0.3077593115 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.1745158001 0.2708771377 Pass Pass 0.1191406133 0.3325214668 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 9.7220118953E-002 0.1570992797 Pass Pass 0.1030592683 0.2991897958 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 3.8490174466E-002 3.3540537594E-002 Pass Pass 7.2987209305E-003 8.5176226557E-002 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 5.8399361538E-002 8.0425630935E-002 Pass Pass 7.3995605226E-003 8.5786592245E-002 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.1238412454 0.1163250068 Pass Pass 6.9489401096E-003 8.3070068883E-002 Pass Fail
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 8.3369708163E-002 9.9489691940E-002 Pass Pass 6.9433894094E-003 8.2363806654E-002 Pass Fail
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 1.7714882326E-002 2.5769559603E-002 Pass Pass 0.1623619555 0.3859237774 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 1.4647570333E-002 2.3933614633E-002 Pass Pass 0.1314417939 0.3612527895 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.3270473662E-002 5.6213992300E-002 Pass Pass 6.9901636309E-003 6.9786249126E-002 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 4.5905517247E-006 5.7363815842E-006 Pass Pass 4.0434983984E-003 5.0822249104E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 3.9146729153E-006 4.5314322994E-006 Pass Pass 1.3819506869E-002 1.1954244779E-002 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 8.5168228550E-003 2.4910959762E-002 Fail Pass 0.5123196490 3.7825439317 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 2.3931474086E-015 2.8956330159E-015 Pass Pass 4.6290931426E-005 1.0801367260E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 6247.79 22.45 0.00 12535.76 12136.59 30942.57



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB -5.20 0.00 -5.20 Wetbulb [C] 2.20 20.00
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 38.10 13.00 18.10 Wetbulb [C] 3.90 280.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 3.00 6      
Feb 3.00 4      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 18.00 7      
Jul 27.00 16      
Aug 41.00 15      
Sep 0.00 0      
Oct 23.00 18      
Nov 0.00 0      
Dec 7.00 7      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.223 1.498 200.61 105.88 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.223 1.498 133.74 71.89 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.223 1.498 200.61 105.88 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.223 1.498 133.74 71.89 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.168 1.416 2006.06 1136.85 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.168 1.416 1337.37 757.90 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.168 1.416 2006.06 1136.85 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.168 1.416 1337.37 757.90 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.459 1.867 200.61 113.68 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.459 1.867 133.74 75.79 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.459 1.867 200.61 113.68 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.459 1.867 133.74 75.79 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.223 1.498 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 1.223 1.498 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.223 1.498 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.223 1.498 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.168 1.416 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.168 1.416 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.168 1.416 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.168 1.416 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.459 1.867 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.459 1.867 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.459 1.867 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.459 1.867 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.55 0.221 0.228 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.845 0.940 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.4237_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.408 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.4237_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.408 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.4237_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.408 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.4237_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.408 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.4237_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.408 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.4237_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.408 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.4237_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.408 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.4237_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.408 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.4237_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.408 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.4237_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.408 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.4237_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.408 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.4237_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.408 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.4237_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.408 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.4237_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.408 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.4237_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.408 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.4237_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.408 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.4237_SHGC_NORTH_0.25   86.92 0.00 0.00 86.92 869.21 2.408 0.251 0.251             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.4237_SHGC_EAST_0.25   57.95 0.00 0.00 57.95 579.48 2.408 0.251 0.251             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.4237_SHGC_SOUTH_0.25   86.92 0.00 0.00 86.92 869.21 2.408 0.251 0.251             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.4237_SHGC_WEST_0.25   57.95 0.00 0.00 57.95 579.48 2.408 0.251 0.251             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.4237_SHGC_NORTH_0.25   86.92 0.00 0.00 86.92 86.92 2.408 0.251 0.251             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.4237_SHGC_EAST_0.25   57.95 0.00 0.00 57.95 57.95 2.408 0.251 0.251             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.4237_SHGC_SOUTH_0.25   86.92 0.00 0.00 86.92 86.92 2.408 0.251 0.251             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.4237_SHGC_WEST_0.25   57.95 0.00 0.00 57.95 57.95 2.408 0.251 0.251             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             3476.85 2.408 0.251 0.251                      
North Total or Average             1043.06 2.408 0.251 0.251                      
Non-North Total or Average             2433.80 2.408 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 5.8895 2779.43 16369.36 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 135.58
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 5.8895 2496.12 14700.84 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 121.76
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 5.8895 24961.20 147008.37 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 1217.57
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 5.8895 2496.12 14700.84 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 121.76
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 5.8895 313.41 1845.84 LightsWired LTG_SCH_OFFICE 45.29 168.00 26.01 0.0000 Y 9.01
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 5.8895 201.98 1189.53 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.84 0.0000 Y 5.77
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 5.8895 313.42 1845.88 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.33 0.0000 Y 8.78
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 5.8895 201.98 1189.53 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.54 0.0000 Y 5.70
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 5.8895 3134.13 18458.37 LightsWired LTG_SCH_OFFICE 45.29 168.00 26.00 0.0000 Y 90.09
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 5.8895 2019.75 11895.27 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.83 0.0000 Y 57.67
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 5.8895 3134.20 18458.77 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.35 0.0000 Y 87.82
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 5.8895 2019.75 11895.27 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.53 0.0000 Y 57.00
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 5.8895 313.41 1845.84 LightsWired LTG_SCH_OFFICE 45.29 168.00 26.00 0.0000 Y 9.01
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 5.8895 201.98 1189.53 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.83 0.0000 Y 5.77
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 5.8895 313.42 1845.88 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.34 0.0000 Y 8.78
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 5.8895 201.98 1189.53 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.53 0.0000 Y 5.70
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 5.8895 783.68 4615.46 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 38.23
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 8.8011 36.20 318.62 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 3.26
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 8.8011 362.03 3186.24 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 32.64
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 8.8011 36.20 318.62 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 3.26
Interior Lighting Total       5.9168 46320.38 274067.57               636.65


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.88 711.95
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.88 255.65
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.84 711.94
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.84 255.65
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.88 711.95
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.88 255.65
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.84 711.94
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.84 255.65
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.88 711.95
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.88 255.65
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.84 711.94
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.84 255.65
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 9973.05 AstronomicalClock -   41.77 41.77 78.19
EXTERIOR_LIGHTS_B 991.40 AstronomicalClock -   83.77 62.77 11.68
EXTERIOR_LIGHTS_C 26646.63 AstronomicalClock -   83.77 46.49 232.53
Exterior Lighting Total 37611.08           322.40



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2227993.26          
HEATSYS1 BOILER Boiler:HotWater 1988484.66 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1138218.22 6.28 1089423.99 5.98 6.84 23.33
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1138218.22 6.28 1089423.99 5.98 6.84 23.33
CENTRAL TOWER FluidCooler:TwoSpeed 148548.00          
CENTRAL BOILER Boiler:HotWater 114279.68 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1351589.95          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1351589.95          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 184465.95 286133.58 172668.32 113465.26 0.60 - 53011.55 537.67
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 1762325.80 2675770.07 1610809.07 1064961.00 0.60 - 486257.13 4931.89
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 184830.58 289655.30 175004.37 114650.94 0.60 - 54184.85 549.57
CAV_BAS COOLING COIL Coil:Cooling:Water 101506.47 158250.09 96376.25 61873.84 0.61 - 27672.21 280.67
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9863.77 5526.29 4337.48 0.56 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   93887.76 52572.29 41315.47 0.56 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9534.03 5338.85 4195.18 0.56 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 16975.39 16097.85 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 390168.79 369765.68 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 81119.37 76890.46 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 8820.25 8360.81 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 6369.50 6037.44 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 11201.06 10616.73 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 5057.62 4793.42 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 180949.54 171490.63 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 120166.30 113884.11 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 179251.00 169881.19 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 110884.12 105088.75 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 24229.60 22961.94 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 15974.60 15138.78 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 24024.67 22767.77 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 15233.91 14436.94 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 49032.24 37854.62 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 462307.90 355889.02 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 45539.30 35725.18 -
CAV_BAS HEATING COIL Coil:Heating:Water 241179.50 190840.96 -
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9863.77 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   93887.76 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9534.03 0.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   741.51 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   7415.12 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   741.51 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 9.83 21236.74 2160.95 1.00 1.12 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 91.25 197177.46 2160.95 1.00 1.08 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 9.98 21574.57 2160.95 1.00 1.12 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 5.59 9478.02 1695.65 1.00 1.16 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.53 592.41 1120.11 1.00 1.58 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 5.03 5632.65 1120.11 1.00 1.15 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.51 571.98 1120.11 1.00 1.60 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.095002 19382.66 204022.71 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.017396 5187.08 298174.34 0.91 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.095002 13419.27 141251.81 0.91 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.002774 700.59 252524.76 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 3168.45 0.000440 5.96 13540.37 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 180718.98 0.112652 33592.53 298196.27 0.91 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.50 0.08



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 67144.15 67144.15 24.16 5.590 5.590 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00752 28.48 0.00686 1.200 0.00
CORE_BOTTOM 72971.55 72971.55 29.23 6.075 6.075 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00743 28.48 0.00686 1.078 0.00
CORE_MID 685633.49 685633.49 274.68 57.064 57.064 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00745 28.48 0.00686 10.778 0.00
CORE_TOP 68252.51 68252.51 27.34 5.681 5.681 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00746 28.48 0.00686 1.078 0.00
PERIMETER_BOT_ZN_3 12505.63 12505.63 39.90 1.051 1.051 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 24.00 0.00730 38.10 0.00687 0.135 0.00
PERIMETER_BOT_ZN_2 11716.15 11716.15 58.01 0.984 0.984 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 24.00 24.00 0.00721 32.05 0.00686 0.087 0.00
PERIMETER_BOT_ZN_1 13869.79 13869.79 44.25 1.165 1.165 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 24.00 24.00 0.00727 37.77 0.00687 0.135 0.00
PERIMETER_BOT_ZN_4 15575.12 15575.12 77.11 1.308 1.308 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 24.00 24.00 0.00716 36.63 0.00687 0.087 0.00
PERIMETER_MID_ZN_3 115951.78 115951.78 369.97 9.741 9.741 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 24.00 0.00732 38.10 0.00687 1.353 0.00
PERIMETER_MID_ZN_2 120918.46 120918.46 598.68 10.158 10.158 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 24.00 24.00 0.00720 32.42 0.00686 0.872 0.00
PERIMETER_MID_ZN_1 129296.39 129296.39 412.53 10.862 10.862 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 24.00 24.00 0.00729 37.88 0.00687 1.353 0.00
PERIMETER_MID_ZN_4 129930.36 129930.36 643.30 10.915 10.915 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 24.00 24.00 0.00719 36.45 0.00687 0.872 0.00
PERIMETER_TOP_ZN_3 13485.49 13485.49 43.03 1.133 1.133 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 24.00 24.00 0.00728 37.84 0.00687 0.135 0.00
PERIMETER_TOP_ZN_2 12449.16 12449.16 61.64 1.046 1.046 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 24.00 24.00 0.00719 33.16 0.00686 0.087 0.00
PERIMETER_TOP_ZN_1 14693.35 14693.35 46.88 1.234 1.234 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 24.00 0.00725 38.10 0.00687 0.135 0.00
PERIMETER_TOP_ZN_4 14290.63 14290.63 70.75 1.200 1.200 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 24.00 24.00 0.00717 36.63 0.00687 0.087 0.00
DATACENTER_BOT_ZN_6 7983.08 7983.08 220.51 0.529 0.529 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 27.00 27.00 0.00700 25.19 0.00685 0.016 0.00
DATACENTER_MID_ZN_6 75904.01 75904.01 2096.64 5.029 5.029 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 27.00 27.00 0.00700 25.19 0.00685 0.156 0.00
DATACENTER_TOP_ZN_6 7706.88 7706.88 212.88 0.511 0.511 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 27.00 27.00 0.00709 34.33 0.00687 0.016 0.00
DATACENTER_BASEMENT_ZN_6 369705.82 369705.82 471.76 24.496 24.496 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.00 27.00 0.00704 26.27 0.00685 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:10:00 21.00 24.57 0.00281 -5.20 0.00281 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:30:00 19.60 22.00 0.00281 -5.20 0.00281 1.078 0.00
CORE_MID 224233.06 224233.06 89.83 10.895 10.895 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -5.20 0.00281 10.778 0.00
CORE_TOP 56807.06 56807.06 22.76 2.784 2.784 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -5.20 0.00281 1.078 0.00
PERIMETER_BOT_ZN_3 6179.07 6179.07 19.72 0.303 0.303 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00783 -5.20 0.00281 0.135 0.00
PERIMETER_BOT_ZN_2 4461.05 4461.05 22.09 0.219 0.219 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00786 -5.20 0.00281 0.087 0.00
PERIMETER_BOT_ZN_1 7843.25 7843.25 25.02 0.385 0.385 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00790 -5.20 0.00281 0.135 0.00
PERIMETER_BOT_ZN_4 2774.05 2774.05 13.73 0.135 0.135 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00768 -5.20 0.00281 0.087 0.00
PERIMETER_MID_ZN_3 126632.37 126632.37 404.04 6.221 6.221 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00792 -5.20 0.00281 1.353 0.00
PERIMETER_MID_ZN_2 84092.48 84092.48 416.35 4.132 4.132 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00792 -5.20 0.00281 0.872 0.00
PERIMETER_MID_ZN_1 125445.00 125445.00 400.25 6.163 6.163 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00792 -5.20 0.00281 1.353 0.00
PERIMETER_MID_ZN_4 77603.46 77603.46 384.22 3.812 3.812 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00791 -5.20 0.00281 0.872 0.00
PERIMETER_TOP_ZN_3 16952.22 16952.22 54.09 0.834 0.834 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00793 -5.20 0.00281 0.135 0.00
PERIMETER_TOP_ZN_2 11176.45 11176.45 55.34 0.550 0.550 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00793 -5.20 0.00281 0.087 0.00
PERIMETER_TOP_ZN_1 16808.96 16808.96 53.63 0.826 0.826 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00793 -5.20 0.00281 0.135 0.00
PERIMETER_TOP_ZN_4 10658.59 10658.59 52.77 0.524 0.524 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00793 -5.20 0.00281 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:30:00 18.00 26.47 0.00700 -5.20 0.00281 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 05:40:00 18.00 23.28 0.00512 -5.20 0.00281 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 05:40:00 18.00 21.32 0.00318 -5.20 0.00281 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 01:00:00 18.00 27.00 0.00700 -5.20 0.00281 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 9.83 9.83 2.12 2.12 9.8275 2.8897 9.8275 0.2940 0.3000
VAV_MID WITH REHEAT 91.25 91.25 31.22 31.22 91.2459 31.2227 91.2459 0.3422 0.3000
VAV_TOP WITH REHEAT 9.98 9.98 5.52 5.52 9.9838 5.5177 9.9838 0.5527 0.3000
CAV_BAS 5.59 5.59 1.20 1.20 5.5896 5.5896 5.5896 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.53 0.53 0.02 0.02 0.5289 0.5289 0.5289 1.0000 1.0000
AIRLOOP DATACENTER MID 5.03 5.03 0.16 0.16 5.0287 5.0287 5.0287 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.51 0.51 0.02 0.02 0.5106 0.5106 0.5106 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 16975.387 16975.387 1.943972 0.00014851 342.210 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:30:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:30:00 16975.39 16975.39 1.943972 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00800000 44.8527 0.00 0.00 17037.98 17037.98
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 390168.795 390168.795 19.002474 0.00341337 9089.934 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 390168.79 390168.79 19.002474 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00800000 44.8527 224233.06 0.00 391453.73 391453.73
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 81119.373 81119.373 2.784175 0.00070967 2141.349 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 81119.37 81119.37 2.784175 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00800000 44.8527 56807.06 0.00 81400.02 81400.02
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 8820.245 8820.245 0.302566 0.00007716 232.890 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 8820.25 8820.25 0.302566 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00783448 43.9373 6179.07 0.00 8851.17 8851.17
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 6369.499 6369.499 0.218614 0.00005572 168.139 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 6369.50 6369.50 0.218614 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00786226 44.0911 4461.05 0.00 6391.53 6391.53
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 11201.055 11201.055 0.384609 0.00009799 295.621 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 11201.06 11201.06 0.384609 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00790117 44.3063 7843.25 0.00 11239.39 11239.39
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 5057.620 5057.620 0.261675 0.00004425 115.954 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 5057.62 5057.62 0.261675 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00768343 43.1008 2774.05 0.00 5074.44 5074.44
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 180949.543 180949.543 6.221365 0.00158303 4772.808 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 180949.54 180949.54 6.221365 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00792197 44.4215 126632.37 0.00 181548.19 181548.19
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 120166.301 120166.301 4.131802 0.00105127 3169.466 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 120166.30 120166.30 4.131802 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00792321 44.4284 84092.48 0.00 120563.17 120563.17
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 179251.000 179251.000 6.162833 0.00156817 4728.053 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 179251.00 179251.00 6.162833 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00792063 44.4141 125445.00 0.00 179844.37 179844.37
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 110884.123 110884.123 3.811989 0.00097006 2924.872 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 110884.12 110884.12 3.811989 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00791041 44.3576 77603.46 0.00 111251.99 111251.99
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 24229.596 24229.596 0.833514 0.00021197 638.930 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 24229.60 24229.60 0.833514 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00793475 44.4923 16952.22 0.00 24308.60 24308.60
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 15974.599 15974.599 0.549558 0.00013975 421.240 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 15974.60 15974.60 0.549558 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00793414 44.4889 11176.45 0.00 16026.63 16026.63
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 24024.674 24024.674 0.826453 0.00021018 633.531 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 24024.67 24024.67 0.826453 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00793416 44.4890 16808.96 0.00 24103.04 24103.04
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 15233.910 15233.910 0.524039 0.00013327 401.722 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 15233.91 15233.91 0.524039 12.80 10.33 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00793059 44.4693 10658.59 0.00 15283.63 15283.63
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 184465.948 -999.000 9.827517 0.00784761 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 184465.95 179273.85 9.827517 27.81 15.19 0.00724445 10.77 8.47 0.00700000 38.10 0.00687148 18.17 25.8274 24.00 0.00738276 34.5307 111694.51 0.00 207323.11 199924.24
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 49032.241 49032.241 2.948255 0.00042896 808.078 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 49032.24 49032.24 2.948255 -3.05 -3.40 0.00315263 12.80 10.33 0.00800000 -5.20 0.00280840 -5.20 86.0913 21.37 0.00604745 33.2412 21257.42 0.00 45793.14 45793.14
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 1762325.803 -999.000 91.245866 0.07497341 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 1762325.80 1710892.68 91.245866 28.29 15.36 0.00725933 10.77 8.47 0.00700000 38.10 0.00687148 18.17 27.8171 24.00 0.00742884 34.7437 993492.63 0.00 1975513.35 1902586.28
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 462307.899 462307.899 27.373760 0.00404447 7608.236 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 14:50:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 462307.90 462307.90 27.373760 -3.29 -3.49 0.00318210 12.80 10.33 0.00800000 -5.20 0.00280840 -5.20 92.7237 21.00 0.00793475 44.4920 438576.71 0.00 430520.78 430520.78
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 184830.579 -999.000 9.983849 0.00786312 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 184830.58 179769.04 9.983849 27.59 15.11 0.00723523 10.77 8.47 0.00700000 38.10 0.00687148 18.17 25.4230 24.00 0.00735972 34.4242 118496.35 0.00 207999.54 200760.05
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 45539.297 45539.297 2.995155 0.00039840 756.422 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 45539.30 45539.30 2.995155 -1.69 -1.98 0.00358758 12.80 10.33 0.00800000 -5.20 0.00280840 -5.20 84.7432 19.38 0.00790581 48.9953 54327.57 0.00 43223.71 43223.71
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 101506.467 -999.000 5.589596 0.00431832 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 101506.47 96761.68 5.589596 27.28 15.14 0.00740358 11.21 8.66 0.00700000 37.45 0.00687043 17.97 21.4719 24.00 0.00757548 35.4216 58596.17 0.00 114259.95 109206.35
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 241179.497 241179.497 5.589596 0.00210994 5359.885 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 241179.50 241179.50 5.589596 -1.12 -2.86 0.00280840 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 21.4719 24.63 0.00280840 12.7410 0.00 0.00 201577.83 201577.83
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9863.768 5526.291 0.528882 0.00024156 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 8528.78 8446.06 -999.0 28.31 15.22 0.00708457 12.80 9.33 0.00700000 34.33 0.00686546 17.01 -999.0000 27.00 0.00709131 27.7682 7907.94 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 93887.757 52572.291 5.028668 0.00229931 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 81197.34 80372.80 -999.0 28.32 15.23 0.00708863 12.80 9.33 0.00700000 34.33 0.00686546 17.01 -999.0000 27.00 0.00709585 27.7860 75317.04 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9534.027 5338.847 0.510649 0.00023349 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 8245.38 8163.43 -999.0 28.32 15.23 0.00708674 12.80 9.33 0.00700000 34.66 0.00686598 17.11 -999.0000 27.00 0.00709371 27.7776 7704.54 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9863.768 9863.768 0.528882 0.00024156 -999.000 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 9863.77 9863.77 0.528882 -5.20 -5.20 0.00280840 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 2.9558 26.80 0.00699999 27.7417 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 93887.757 93887.757 5.028668 0.00229931 -999.000 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 93887.76 93887.76 5.028668 -5.20 -5.20 0.00280840 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 3.1087 24.49 0.00512210 23.3456 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9534.027 9534.027 0.510649 0.00023349 -999.000 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 9534.03 9534.03 0.510649 -5.20 -5.20 0.00280840 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 3.0614 23.20 0.00317768 15.6979 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 741.512 741.512 -999.0 -999.0 -999.000 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 741.51 741.51 0.528882 -0.15 -0.15 0.00687610 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 2.9558 26.80 0.00699999 27.7417 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 7415.124 7415.124 -999.0 -999.0 -999.000 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 7415.12 7415.12 5.028668 -0.16 -0.16 0.00505017 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 3.1087 24.49 0.00512210 23.3456 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 741.512 741.512 -999.0 -999.0 -999.000 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 741.51 741.51 0.510649 -0.16 -1.79 0.00316638 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 3.0614 23.20 0.00317768 15.6979 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 16975.387 16975.387 1.943972 0.00014851 342.210 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 0.8368 0.853685 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:30:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:30:00 Sensible 16975.39 16975.39 1.0000 2.03015166 1.943972 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.14849295 60.00 32.22 27.78 0.000 16975.39 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 44.8527 0.00 0.00 17037.98 17037.98 2.03015166 12.80 11.60 0.00800000 33059.8 21.03 14.86 0.00800000 41452.3
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 390168.795 390168.795 19.002474 0.00341337 9089.934 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 19.2343 19.621413 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 390168.79 390168.79 1.0000 19.84488709 19.002474 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 3.41301863 60.00 32.22 27.78 0.000 390168.79 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.84 0.00800000 21.00 0.00800000 44.8527 224233.06 0.00 391453.73 391453.73 19.84488709 12.80 11.60 0.00800000 33059.8 32.14 18.74 0.00800000 52785.5
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 81119.373 81119.373 2.784175 0.00070967 2141.349 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 3.9990 4.079457 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 81119.37 81119.37 1.0000 2.90760263 2.784175 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.70959527 60.00 32.22 27.78 0.000 81119.37 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 44.8527 56807.06 0.00 81400.02 81400.02 2.90760263 12.80 11.60 0.00800000 33059.8 40.25 21.26 0.00800000 61055.4
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 8820.245 8820.245 0.302566 0.00007716 232.890 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 0.4348 0.443566 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 8820.25 8820.25 1.0000 0.31597883 0.302566 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.07715548 60.00 32.22 27.78 0.000 8820.25 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.91 0.00783448 21.00 0.00783448 43.9373 6179.07 0.00 8851.17 8851.17 0.31597883 12.80 11.60 0.00800000 33059.8 40.27 21.26 0.00800000 61071.7
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 6369.499 6369.499 0.218614 0.00005572 168.139 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 0.3140 0.320319 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 6369.50 6369.50 1.0000 0.22830571 0.218614 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.05571747 60.00 32.22 27.78 0.000 6369.50 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.91 0.00786226 21.00 0.00786226 44.0911 4461.05 0.00 6391.53 6391.53 0.22830571 12.80 11.60 0.00800000 33059.8 40.25 21.26 0.00800000 61055.3
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 11201.055 11201.055 0.384609 0.00009799 295.621 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 0.5522 0.563296 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 11201.06 11201.06 1.0000 0.40165923 0.384609 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.09798172 60.00 32.22 27.78 0.000 11201.06 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.91 0.00790117 21.00 0.00790117 44.3063 7843.25 0.00 11239.39 11239.39 0.40165923 12.80 11.60 0.00800000 33059.8 40.24 21.25 0.00800000 61042.2
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 5057.620 5057.620 0.261675 0.00004425 115.954 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 0.2493 0.254345 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 5057.62 5057.62 1.0000 0.27327545 0.261675 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.04424176 60.00 32.22 27.78 0.000 5057.62 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.87 0.00768343 21.00 0.00768343 43.1008 2774.05 0.00 5074.44 5074.44 0.27327545 12.80 11.60 0.00800000 33059.8 31.01 18.37 0.00800000 51628.8
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 180949.543 180949.543 6.221365 0.00158303 4772.808 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 8.9203 9.099871 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 180949.54 180949.54 1.0000 6.49716837 6.221365 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 1.58286405 60.00 32.22 27.78 0.000 180949.54 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.95 0.00792197 21.00 0.00792197 44.4215 126632.37 0.00 181548.19 181548.19 6.49716837 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61002.5
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 120166.301 120166.301 4.131802 0.00105127 3169.466 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 5.9239 6.043109 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 120166.30 120166.30 1.0000 4.31497187 4.131802 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 1.05115998 60.00 32.22 27.78 0.000 120166.30 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.95 0.00792321 21.00 0.00792321 44.4284 84092.48 0.00 120563.17 120563.17 4.31497187 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61000.5
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 179251.000 179251.000 6.162833 0.00156817 4728.053 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 8.8366 9.014452 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 179251.00 179251.00 1.0000 6.43604213 6.162833 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 1.56800598 60.00 32.22 27.78 0.000 179251.00 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.95 0.00792063 21.00 0.00792063 44.4141 125445.00 0.00 179844.37 179844.37 6.43604213 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61003.1
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 110884.123 110884.123 3.811989 0.00097006 2924.872 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 5.4663 5.576313 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 110884.12 110884.12 1.0000 3.98098111 3.811989 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.96996372 60.00 32.22 27.78 0.000 110884.12 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.95 0.00791041 21.00 0.00791041 44.3576 77603.46 0.00 111251.99 111251.99 3.98098111 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61005.7
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 24229.596 24229.596 0.833514 0.00021197 638.930 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 1.1945 1.218496 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 24229.60 24229.60 1.0000 0.87046522 0.833514 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.21194945 60.00 32.22 27.78 0.000 24229.60 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.95 0.00793475 21.00 0.00793475 44.4923 16952.22 0.00 24308.60 24308.60 0.87046522 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60985.8
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 15974.599 15974.599 0.549558 0.00013975 421.240 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 0.7875 0.803355 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 15974.60 15974.60 1.0000 0.57392055 0.549558 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.13973851 60.00 32.22 27.78 0.000 15974.60 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.95 0.00793414 21.00 0.00793414 44.4889 11176.45 0.00 16026.63 16026.63 0.57392055 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60984.7
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 24024.674 24024.674 0.826453 0.00021018 633.531 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 1.1844 1.208190 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 24024.67 24024.67 1.0000 0.86309079 0.826453 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.21015689 60.00 32.22 27.78 0.000 24024.67 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.95 0.00793416 21.00 0.00793416 44.4890 16808.96 0.00 24103.04 24103.04 0.86309079 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60986.3
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 15233.910 15233.910 0.524039 0.00013327 401.722 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 0.7510 0.766106 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 15233.91 15233.91 1.0000 0.54727075 0.524039 12.80 10.33 0.00800000 33059.8 40.00 19.53 0.00800000 60796.0 0.13325930 60.00 32.22 27.78 0.000 15233.91 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.95 0.00793059 21.00 0.00793059 44.4693 10658.59 0.00 15283.63 15283.63 0.54727075 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60986.8
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 184465.948 -999.000 9.827517 0.00784761 -999.000 -999.0000 1.00000 1.00000 1018.3071 1004.8586 1.0443 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.827517 10.26318794   4197.9300 999.8980 94.99277012 12.27 6.67 5.60 2233128.80 8.2604 8.260426 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 184465.95 179273.85 1.0000 10.26318794 9.827517 27.81 15.19 0.00724445 46440.4 10.77 8.47 0.00700000 28466.8 7.84680732 6.67 12.27 5.60 21236.741 163229.21 38.10 0.00687148 18.17 2.53819000 25.8274 24.00 0.00738276 24.00 0.00738276 34.5307 111694.51 0.00 207323.11 199924.24 10.26318794 27.81 16.66 0.00724445 46440.4 8.68 8.66 0.00695804 26239.7
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 49032.241 49032.241 2.948255 0.00042896 808.078 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.827517 10.26318794   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 2.4172 2.465809 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 49032.24 49032.24 1.0000 3.07895638 2.948255 -3.05 -3.40 0.00315263 4804.0 12.80 10.33 0.00800000 33059.8 0.42891168 60.00 32.22 27.78 0.000 49032.24 -5.20 0.00280840 -5.20 2.53819000 86.0913 10.27 0.00528337 21.37 0.00604745 33.2412 21257.42 0.00 45793.14 45793.14 3.07895638 2.80 0.74 0.00315263 10714.5 17.52 8.43 0.00315263 25587.5
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 1762325.803 -999.000 91.245866 0.07497341 -999.000 -999.0000 1.00000 1.00000 1018.3347 1004.8586 1.0443 VAV_MID WITH REHEAT FAN Fan:VariableVolume 91.245866 95.29095369   4197.9300 999.8980 94.99277012 12.27 6.67 5.60 2233128.80 78.9173 78.917338 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 1762325.80 1710892.68 1.0000 95.29095369 91.245866 28.29 15.36 0.00725933 46961.0 10.77 8.47 0.00700000 28466.9 74.96576556 6.67 12.27 5.60 197177.458 1565148.34 38.10 0.00687148 18.17 25.38195000 27.8171 24.00 0.00742884 24.00 0.00742884 34.7437 993492.63 0.00 1975513.35 1902586.28 95.29095369 28.29 16.84 0.00725933 46961.0 8.68 8.66 0.00695528 26229.6
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 462307.899 462307.899 27.373760 0.00404447 7608.236 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 VAV_MID WITH REHEAT FAN Fan:VariableVolume 91.245866 95.29095369   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 22.7906 23.249257 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 14:50:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 462307.90 462307.90 1.0000 28.58728611 27.373760 -3.29 -3.49 0.00318210 4629.2 12.80 10.33 0.00800000 33059.8 4.04405860 60.00 32.22 27.78 0.000 462307.90 -5.20 0.00280840 -5.20 25.38195000 92.7237 21.00 0.00794434 21.00 0.00793475 44.4920 438576.71 0.00 430520.78 430520.78 28.58728611 2.80 0.79 0.00318210 10788.4 17.70 8.55 0.00318210 25848.2
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 184830.579 -999.000 9.983849 0.00786312 -999.000 -999.0000 1.00000 1.00000 1018.2899 1004.8586 1.0443 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 9.983849 10.42645015   4197.9300 999.8980 94.99277012 12.27 6.67 5.60 2233128.80 8.2768 8.276754 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 Sensible 184830.58 179769.04 1.0000 10.42645015 9.983849 27.59 15.11 0.00723523 46193.9 10.77 8.47 0.00700000 28466.8 7.86231798 6.67 12.27 5.60 21574.566 163256.01 38.10 0.00687148 18.17 2.53819000 25.4230 24.00 0.00735972 24.00 0.00735972 34.4242 118496.35 0.00 207999.54 200760.05 10.42645015 27.59 16.57 0.00723523 46193.9 8.69 8.67 0.00695938 26244.6
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 45539.297 45539.297 2.995155 0.00039840 756.422 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 9.983849 10.42645015   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 2.2450 2.290151 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 06:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 45539.30 45539.30 1.0000 3.12793504 2.995155 -1.69 -1.98 0.00358758 7264.4 12.80 10.33 0.00800000 33059.8 0.39835700 60.00 32.22 27.78 0.000 45539.30 -5.20 0.00280840 -5.20 2.53819000 84.7432 17.82 0.00791552 19.38 0.00790581 48.9953 54327.57 0.00 43223.71 43223.71 3.12793504 2.80 1.37 0.00358758 11804.5 16.46 8.44 0.00358758 25623.2
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 101506.467 -999.000 5.589596 0.00431832 -999.000 -999.0000 1.00000 1.00000 1018.6029 1004.8586 1.0443 CAV_BAS FAN Fan:ConstantVolume 5.589596 5.83739261   4197.9300 999.8980 94.99277012 12.27 6.67 5.60 2233128.80 4.5455 4.545482 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 101506.47 96761.68 1.0000 5.83739261 5.589596 27.28 15.14 0.00740358 46301.6 11.21 8.66 0.00700000 28912.6 4.31787925 6.67 12.27 5.60 9478.023 92028.44 37.45 0.00687043 17.97 1.20019084 21.4719 24.00 0.00757548 24.00 0.00757548 35.4216 58596.17 0.00 114259.95 109206.35 5.83739261 27.28 16.61 0.00740358 46301.6 8.91 8.88 0.00705970 26727.8
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 241179.497 241179.497 5.589596 0.00210994 5359.885 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 CAV_BAS FAN Fan:ConstantVolume 5.589596 5.83739261   4197.9300 999.8980 17.39435663 54.44 82.22 27.78 2028503.70 11.8895 12.128809 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 241179.50 241179.50 1.0000 5.83739261 5.589596 -1.12 -2.86 0.00280840 5895.9 40.00 19.53 0.00800000 60796.0 2.10972822 60.00 32.22 27.78 0.000 241179.50 -5.20 0.00280840 -5.20 1.20019084 21.4719 0.00 0.00280840 24.63 0.00280840 12.7410 0.00 0.00 201577.83 201577.83 5.83739261 12.80 5.73 0.00280840 19952.4 46.99 19.42 0.00280840 54484.6
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9863.768 5526.291 0.528882 0.00024156 -999.000 -999.0000 -999.00000 -999.00000 1018.0099 1004.8586 1.0443 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 Sensible 8528.78 8446.06 0.8647 -999.0 -999.0 28.31 15.22 0.00708457 46536.7 12.80 9.33 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 8528.78 34.33 0.00686546 17.01 0.01563279 -999.0000 27.00 0.00709131 27.00 0.00709131 27.7682 7907.94 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 93887.757 52572.291 5.028668 0.00229931 -999.000 -999.0000 -999.00000 -999.00000 1018.0174 1004.8586 1.0443 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 Sensible 81197.34 80372.80 0.8648 -999.0 -999.0 28.32 15.23 0.00708863 46558.1 12.80 9.33 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 81197.34 34.33 0.00686546 17.01 0.15632792 -999.0000 27.00 0.00709585 27.00 0.00709585 27.7860 75317.04 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9534.027 5338.847 0.510649 0.00023349 -999.000 -999.0000 -999.00000 -999.00000 1018.0139 1004.8586 1.0443 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 Sensible 8245.38 8163.43 0.8648 -999.0 -999.0 28.32 15.23 0.00708674 46558.2 12.80 9.33 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 8245.38 34.66 0.00686598 17.11 0.01563279 -999.0000 27.00 0.00709371 27.00 0.00709371 27.7776 7704.54 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9863.768 9863.768 0.528882 0.00024156 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 9863.77 9863.77 1.0000 0.55232853 0.528882 -5.20 -5.20 0.00280840 1771.3 40.00 19.53 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9863.77 -5.20 0.00280840 -5.20 0.01563279 2.9558 0.00 0.00699999 26.80 0.00699999 27.7417 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 93887.757 93887.757 5.028668 0.00229931 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 93887.76 93887.76 1.0000 5.25159766 5.028668 -5.20 -5.20 0.00280840 1771.3 40.00 19.53 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 93887.76 -5.20 0.00280840 -5.20 0.15632792 3.1087 0.00 0.00512210 24.49 0.00512210 23.3456 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9534.027 9534.027 0.510649 0.00023349 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 9534.03 9534.03 1.0000 0.53328697 0.510649 -5.20 -5.20 0.00280840 1771.3 40.00 19.53 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9534.03 -5.20 0.00280840 -5.20 0.01563279 3.0614 0.00 0.00317768 23.20 0.00317768 15.6979 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 741.512 741.512 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.528882 0.55232853   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 741.51 741.51 1.0000 0.55232853 0.528882 -0.15 -0.15 0.00687610 17040.3 40.00 19.53 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 741.51 -5.20 0.00280840 -5.20 0.01563279 2.9558 0.00 0.00699999 26.80 0.00699999 27.7417 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 7415.124 7415.124 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 5.028668 5.25159766   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 7415.12 7415.12 1.0000 5.25159766 5.028668 -0.16 -0.16 0.00505017 12466.2 40.00 19.53 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 7415.12 -5.20 0.00280840 -5.20 0.15632792 3.1087 0.00 0.00512210 24.49 0.00512210 23.3456 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 741.512 741.512 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.510649 0.53328697   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 741.51 741.51 1.0000 0.53328697 0.510649 -0.16 -1.79 0.00316638 7758.0 40.00 19.53 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 741.51 -5.20 0.00280840 -5.20 0.01563279 3.0614 0.00 0.00317768 23.20 0.00317768 15.6979 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 9.83 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 91.25 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 9.98 -      
CAV_BAS_OA_CONTROLLER DifferentialDryBulb 0.00 5.59 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT BASEMENT_DCV 0.002360 0.000305 0.000000 0.000000 Sum   1.00 1.00  
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 2818.67 1876.50 746.67
CORE_BOTTOM 2560.83 1772.83 698.33
CORE_MID 2030.67 3351.33 740.33
CORE_TOP 2295.67 3779.33 1035.83
PERIMETER_BOT_ZN_3 2271.67 3242.33 507.33
PERIMETER_BOT_ZN_2 2644.33 2802.33 572.33
PERIMETER_BOT_ZN_1 2826.00 2130.17 549.00
PERIMETER_BOT_ZN_4 3399.83 1601.33 645.00
PERIMETER_MID_ZN_3 2636.33 3812.00 1176.00
PERIMETER_MID_ZN_2 2392.00 2829.00 802.50
PERIMETER_MID_ZN_1 2729.33 2496.33 694.33
PERIMETER_MID_ZN_4 2742.67 3177.83 809.50
PERIMETER_TOP_ZN_3 3513.17 3919.00 2039.50
PERIMETER_TOP_ZN_2 3391.50 3438.33 1529.17
PERIMETER_TOP_ZN_1 3007.50 2928.83 1091.33
PERIMETER_TOP_ZN_4 3325.67 3448.00 1462.00
DATACENTER_BOT_ZN_6 5943.00 234.00 234.00
DATACENTER_MID_ZN_6 5923.00 34.83 34.83
DATACENTER_TOP_ZN_6 5457.50 126.00 79.50
DATACENTER_BASEMENT_ZN_6 5943.00 5943.00 5943.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5943.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 83.67 0.00 3.50
CORE_BOTTOM 0.00 2.83 0.00 0.00
CORE_MID 0.00 0.17 0.00 0.00
CORE_TOP 0.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 4.67 0.00 1.67
PERIMETER_BOT_ZN_2 0.00 43.83 0.00 42.33
PERIMETER_BOT_ZN_1 0.00 51.50 0.00 47.33
PERIMETER_BOT_ZN_4 0.00 189.67 0.00 67.67
PERIMETER_MID_ZN_3 0.17 0.67 0.00 0.33
PERIMETER_MID_ZN_2 0.17 52.67 0.00 51.50
PERIMETER_MID_ZN_1 0.00 50.50 0.00 49.00
PERIMETER_MID_ZN_4 0.00 64.17 0.00 31.83
PERIMETER_TOP_ZN_3 17.50 14.17 1.17 7.83
PERIMETER_TOP_ZN_2 14.00 69.17 0.00 59.00
PERIMETER_TOP_ZN_1 7.83 48.83 0.00 39.83
PERIMETER_TOP_ZN_4 7.83 73.50 0.00 32.83
DATACENTER_BOT_ZN_6 0.00 34.00 0.00 21.50
DATACENTER_MID_ZN_6 0.00 31.17 0.00 22.00
DATACENTER_TOP_ZN_6 0.00 36.67 0.00 24.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 17.67 491.50 1.17 253.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 60.99 149.60 6779.02 1.264 0.000 0.000 0.000
CORE_BOTTOM 54.77 134.35 6849.35 0.966 0.000 0.000 0.000
CORE_MID 54.77 134.35 6849.35 0.741 0.000 0.000 0.000
CORE_TOP 54.77 134.35 6849.35 0.682 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.88 16.87 860.00 0.877 0.010 0.000 0.000
PERIMETER_BOT_ZN_2 4.43 10.87 554.22 1.287 0.010 0.000 0.000
PERIMETER_BOT_ZN_1 6.88 16.87 860.02 1.362 0.010 0.000 0.000
PERIMETER_BOT_ZN_4 4.43 10.87 554.22 1.906 0.010 0.000 0.000
PERIMETER_MID_ZN_3 6.88 16.87 860.00 0.743 0.023 0.000 0.000
PERIMETER_MID_ZN_2 3.86 10.87 554.22 1.164 0.026 0.000 0.000
PERIMETER_MID_ZN_1 6.88 16.87 860.02 1.230 0.024 0.000 0.000
PERIMETER_MID_ZN_4 4.43 10.87 554.22 1.225 0.024 0.000 0.000
PERIMETER_TOP_ZN_3 6.88 16.87 860.00 0.728 0.029 0.000 0.000
PERIMETER_TOP_ZN_2 4.43 10.87 554.22 1.200 0.030 0.000 0.000
PERIMETER_TOP_ZN_1 6.88 16.87 860.02 1.130 0.029 0.000 0.000
PERIMETER_TOP_ZN_4 4.43 10.87 554.22 1.210 0.030 0.000 0.000
DATACENTER_BOT_ZN_6 0.79 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.79 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.79 1.95 99.34 0.426 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.20 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 60.99 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 54.77 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 54.77 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 54.77 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.88 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 6.88 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 6.88 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.86 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 6.88 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 6.88 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 6.88 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.43 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.79 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.79 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.79 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.20 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 60.99 149.60 6779.02 2779.43 1.2002 0.847
CORE_BOTTOM VAV_BOT WITH REHEAT 54.77 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 54.77 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 54.77 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 6.88 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 6.88 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 6.88 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.86 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 6.88 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 6.88 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 6.88 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.79 1.95 99.34 36.20 0.0156 0.011
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.79 1.95 99.34 36.20 0.1563 0.110
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.79 1.95 99.34 36.20 0.0156 0.011
DATACENTER_BASEMENT_ZN_6   17.20 42.18 1911.37 783.68   0.239
Total Facility   1010.73 2493.19 126016.35 46320.38 1.3878 157.549


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 54488118.69 0.00 54488118.69 0.00 54488118.69 29876159.83 3733.32 1721.88 3304.80 442.11
CORE_BOTTOM 43176638.95 0.00 43176638.95 0.00 43176638.95 33990283.35 4837.91 43.47 3878.62 689.76
CORE_MID 0.31E+09 0.00 0.31E+09 0.00 0.31E+09 0.34E+09 5555.65 254.88 2949.47 212.37
CORE_TOP 28780830.10 0.00 28780830.10 0.00 28780830.10 33990283.35 5927.43 134.21 2698.36 283.19
PERIMETER_BOT_ZN_3 4959297.35 0.00 4959297.35 99580.51 5058877.86 4267819.30 3836.69 70.00 4853.30 689.76
PERIMETER_BOT_ZN_2 4613293.20 0.00 4613293.20 66386.96 4679680.16 2750345.05 3260.24 22.25 5477.51 689.76
PERIMETER_BOT_ZN_1 7401772.21 0.00 7401772.21 99580.51 7501352.72 4267912.63 3652.14 31.11 5076.75 689.76
PERIMETER_BOT_ZN_4 6835082.54 0.00 6835082.54 66386.96 6901469.50 2750345.05 3156.99 3.12 5599.89 689.76
PERIMETER_MID_ZN_3 39086699.20 0.00 39086699.20 233540.94 39320240.14 42678193.03 4363.53 284.03 4112.45 212.37
PERIMETER_MID_ZN_2 41250318.50 0.00 41250318.50 155693.86 41406012.36 27503450.52 3816.83 5.34 4937.82 1121.37
PERIMETER_MID_ZN_1 63544140.88 0.00 63544140.88 233540.94 63777681.82 42679126.28 4089.65 292.17 4378.18 212.37
PERIMETER_MID_ZN_4 41366998.79 0.00 41366998.79 155693.86 41522692.64 27503450.52 3799.73 5.10 4955.16 212.37
PERIMETER_TOP_ZN_3 3853544.79 0.00 3853544.79 289961.94 4143506.72 4267819.30 4592.94 161.45 4005.62 283.19
PERIMETER_TOP_ZN_2 4044415.65 0.00 4044415.65 193307.83 4237723.48 2750345.05 3893.46 2.40 4864.14 283.19
PERIMETER_TOP_ZN_1 5868278.56 0.00 5868278.56 289961.94 6158240.50 4267912.63 4074.57 506.72 4178.71 283.19
PERIMETER_TOP_ZN_4 4115533.49 0.00 4115533.49 193307.83 4308841.31 2750345.05 3880.00 3.49 4876.50 283.19
DATACENTER_BOT_ZN_6 244303.03 0.00 244303.03 0.00 244303.03 389144.62 4419.00 504.00 3837.00 0.00
DATACENTER_MID_ZN_6 2443030.26 0.00 2443030.26 0.00 2443030.26 3891446.16 4419.00 504.00 3837.00 0.00
DATACENTER_TOP_ZN_6 244303.03 0.00 244303.03 0.00 244303.03 389144.62 4419.00 504.00 3837.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00 0.00 8423799.00 8760.00 0.00 0.00 0.00
Total Facility 0.51E+10 0.00 0.51E+10 9083170.42 0.52E+10 0.50E+10 8760.00 2540.61 5861.29 1853.47


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.3354 0.0000 2.3354 0.0000 2.3354 0.9949 1282.97 1718.80 2941.23
CORE_BOTTOM 1.8025 0.0000 1.8025 0.0000 1.8025 1.0778 2664.69 41.28 3237.03
CORE_MID 13.8314 0.0000 13.8314 0.0000 13.8314 10.7782 2936.74 254.88 2751.38
CORE_TOP 1.2740 0.0000 1.2740 0.0000 1.2740 1.0778 3302.54 134.21 2506.25
PERIMETER_BOT_ZN_3 0.2054 0.0000 0.2054 0.0023 0.2077 0.1353 1658.19 67.42 4217.39
PERIMETER_BOT_ZN_2 0.1944 0.0000 0.1944 0.0016 0.1960 0.0872 1112.55 20.45 4810.01
PERIMETER_BOT_ZN_1 0.3194 0.0000 0.3194 0.0023 0.3218 0.1353 1473.46 28.62 4440.92
PERIMETER_BOT_ZN_4 0.2879 0.0000 0.2879 0.0016 0.2894 0.0872 1028.74 2.12 4912.14
PERIMETER_MID_ZN_3 1.7449 0.0000 1.7449 0.0055 1.7504 1.3533 1744.98 284.00 3914.01
PERIMETER_MID_ZN_2 1.7591 0.0000 1.7591 0.0039 1.7630 0.8721 1198.44 3.67 3831.89
PERIMETER_MID_ZN_1 2.8859 0.0000 2.8859 0.0055 2.8914 1.3533 1470.68 292.17 4180.15
PERIMETER_MID_ZN_4 1.8513 0.0000 1.8513 0.0037 1.8550 0.8721 1181.77 5.10 4756.13
PERIMETER_TOP_ZN_3 0.1710 0.0000 0.1710 0.0068 0.1779 0.1353 1969.99 161.24 3811.77
PERIMETER_TOP_ZN_2 0.1813 0.0000 0.1813 0.0046 0.1859 0.0872 1273.86 1.86 4667.28
PERIMETER_TOP_ZN_1 0.2651 0.0000 0.2651 0.0068 0.2719 0.1353 1450.06 506.72 3986.21
PERIMETER_TOP_ZN_4 0.1830 0.0000 0.1830 0.0046 0.1875 0.0872 1264.66 1.20 4677.14
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0130 1602.00 504.00 3837.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1296 1602.00 504.00 3837.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0130 1602.00 504.00 3837.00
DATACENTER_BASEMENT_ZN_6 0.0000 0.0000 0.0000 0.0000 0.0000 0.2805 5943.00 0.00 0.00
Total Facility 229.1092 0.0000 229.1092 0.2164 229.3255 157.9346 5943.00 2529.12 4994.93


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 73056960.56 0.00 73056960.56 48026705.38 3222.92 5.62 5531.46 689.76
VAV_MID WITH REHEAT 0.54E+09 0.00 0.54E+09 0.48E+09 3839.63 2.00 4918.37 212.37
VAV_TOP WITH REHEAT 50891581.10 0.00 50891581.10 48026705.38 3911.90 2.19 4845.90 283.19
CAV_BAS 59426309.65 0.00 59426309.65 29876159.83 3720.74 2.35 5036.91 442.11
AIRLOOP DATACENTER BOT 266443.91 0.00 266443.91 389144.62 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 2664439.08 0.00 2664439.08 3891446.16 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 266443.91 0.00 266443.91 389144.62 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 3.0642 0.0000 3.0642 1.5229 1064.39 3.13 4875.48
VAV_MID WITH REHEAT 24.1807 0.0000 24.1807 15.2292 1221.54 1.93 4719.53
VAV_TOP WITH REHEAT 2.2624 0.0000 2.2624 1.5229 1287.68 1.81 4653.51
CAV_BAS 2.5471 0.0000 2.5471 0.9949 1281.55 0.26 4661.19
AIRLOOP DATACENTER BOT 0.0125 0.0000 0.0125 0.0130 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1245 0.0000 0.1245 0.1296 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0125 0.0000 0.0125 0.0130 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 0.50 3923.35 0.00 0.00 0.00 1687.42 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 0.89 3163.01 0.00 0.00 0.00 1855.06 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 0.23 2960.46 0.00 0.00 0.00 2089.00 0.00 0.00 0.00
CAV_BAS 0.00 0.00 3393.39 0.00 0.00 0.00 1717.99 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 0.0000 4.6965 0.0000 0.0000 0.0000 1.7911 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 0.0000 37.2684 0.0000 0.0000 0.0000 18.1575 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 0.0000 3.6349 0.0000 0.0000 0.0000 1.7773 0.0000 0.0000 0.0000
CAV_BAS 0.0000 0.0000 4.4726 0.0000 0.0000 0.0000 1.1291 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0171 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.1705 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0171 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 7
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1352
Defaulted Fields 1168
Fields with Defaults 3820
Autosized Fields 313
Autosizable Fields 391
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 24165.65 287830.88 16-JAN-04:00 1610390.17 02-AUG-08:00
Electricity:Building 16701.57 216803.93 21-MAY-17:10 977223.71 01-DEC-17:00
Electricity:Zone:BASEMENT 559.97 14115.26 01-JAN-00:10 25295.37 02-JAN-08:10
Electricity:SpaceType:GENERAL 16701.57 216803.93 21-MAY-17:10 977223.71 01-DEC-17:00
InteriorLights:Electricity 2025.18 9514.02 01-JAN-09:30 198852.03 22-NOV-17:00
InteriorLights:Electricity:Zone:BASEMENT 135.58 657.72 01-JAN-00:10 11837.83 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 2025.18 9514.02 01-JAN-09:30 198852.03 22-NOV-17:00
LightsWired:InteriorLights:Electricity 2025.18 9514.02 01-JAN-09:30 198852.03 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 135.58 657.72 01-JAN-00:10 11837.83 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 2025.18 9514.02 01-JAN-09:30 198852.03 22-NOV-17:00
Electricity:Zone:CORE_BOTTOM 411.37 5043.91 01-JAN-00:10 27837.83 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 121.76 590.68 01-JAN-00:10 10631.20 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 121.76 590.68 01-JAN-00:10 10631.20 02-JAN-08:10
Electricity:Zone:CORE_MID 4113.71 50438.97 01-JAN-00:10 278377.67 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 1217.58 5906.80 01-JAN-00:10 106312.04 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 1217.58 5906.80 01-JAN-00:10 106312.04 02-JAN-08:10
Electricity:Zone:CORE_TOP 411.37 5043.90 01-JAN-00:10 27837.77 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 121.76 590.68 01-JAN-00:10 10631.20 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 121.76 590.68 01-JAN-00:10 10631.20 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 45.38 594.46 07-MAY-17:10 3495.41 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 9.01 35.29 01-JAN-09:30 1334.85 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 9.01 35.29 01-JAN-09:30 1334.85 22-NOV-17:00
Electricity:Zone:PERIMETER_BOT_ZN_2 29.21 385.02 23-JUL-17:10 2252.57 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 5.77 22.74 01-JAN-08:10 860.23 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 5.77 22.74 01-JAN-08:10 860.23 22-NOV-17:00
Electricity:Zone:PERIMETER_BOT_ZN_1 45.14 594.47 02-JUL-17:10 3495.47 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 8.78 35.29 01-JAN-08:20 1334.88 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 8.78 35.29 01-JAN-08:20 1334.88 22-NOV-17:00
Electricity:Zone:PERIMETER_BOT_ZN_4 29.14 383.09 12-MAR-17:10 2252.56 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 5.70 22.74 01-JAN-09:20 860.23 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 5.70 22.74 01-JAN-09:20 860.23 22-NOV-17:00
Electricity:Zone:PERIMETER_MID_ZN_3 453.75 5944.59 07-MAY-17:10 34954.06 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 90.09 352.88 01-JAN-09:20 13348.54 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 90.09 352.88 01-JAN-09:20 13348.54 22-NOV-17:00
Electricity:Zone:PERIMETER_MID_ZN_2 292.03 3848.90 23-JUL-17:10 22525.72 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 57.67 227.41 01-JAN-08:10 8602.31 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 57.67 227.41 01-JAN-08:10 8602.31 22-NOV-17:00
Electricity:Zone:PERIMETER_MID_ZN_1 451.48 5944.68 21-MAY-17:10 34954.68 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 87.82 352.89 01-JAN-08:20 13348.83 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 87.82 352.89 01-JAN-08:20 13348.83 22-NOV-17:00
Electricity:Zone:PERIMETER_MID_ZN_4 291.35 3830.90 12-MAR-17:10 22525.63 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 57.00 227.41 01-JAN-09:20 8602.31 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 57.00 227.41 01-JAN-09:20 8602.31 22-NOV-17:00
Electricity:Zone:PERIMETER_TOP_ZN_3 45.37 594.46 07-MAY-17:10 3495.41 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 9.01 35.29 01-JAN-09:20 1334.85 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 9.01 35.29 01-JAN-09:20 1334.85 22-NOV-17:00
Electricity:Zone:PERIMETER_TOP_ZN_2 29.20 384.89 23-JUL-17:10 2252.57 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 5.77 22.74 01-JAN-08:10 860.23 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 5.77 22.74 01-JAN-08:10 860.23 22-NOV-17:00
Electricity:Zone:PERIMETER_TOP_ZN_1 45.15 594.47 21-MAY-17:10 3495.47 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 8.78 35.29 01-JAN-08:20 1334.88 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 8.78 35.29 01-JAN-08:20 1334.88 22-NOV-17:00
Electricity:Zone:PERIMETER_TOP_ZN_4 29.14 383.09 12-MAR-17:10 2252.56 22-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 5.70 22.74 01-JAN-09:20 860.23 22-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 5.70 22.74 01-JAN-09:20 860.23 22-NOV-17:00
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7533.08 95093.58 01-JAN-00:10 382970.28 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 38.23 185.45 01-JAN-00:10 3337.76 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 38.23 185.45 01-JAN-00:10 3337.76 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 157.14 1964.44 01-JAN-00:10 8079.39 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 3.26 15.83 01-JAN-00:10 284.97 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 3.26 15.83 01-JAN-00:10 284.97 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1571.44 19644.38 01-JAN-00:10 80793.90 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 32.64 158.32 01-JAN-00:10 2849.68 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 32.64 158.32 01-JAN-00:10 2849.68 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 157.14 1964.44 01-JAN-00:10 8079.39 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 3.26 15.83 01-JAN-00:10 284.97 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 3.26 15.83 01-JAN-00:10 284.97 02-JAN-08:10
InteriorEquipment:Electricity 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 2130.43 997.90 28-JAN-04:40 434091.50 21-JUL-10:20
HeatRejection:Electricity 380.45 138.37 28-JAN-07:20 45559.75 21-APR-14:30
General:HeatRejection:Electricity 380.45 138.37 28-JAN-07:20 45559.75 21-APR-14:30
Electricity:HVAC 1807.56 10196.30 16-JAN-06:00 213800.90 08-AUG-15:00
ExteriorEquipment:Electricity 3258.17 45245.36 01-JAN-00:10 185189.52 20-APR-07:20
Transformer:ExteriorEquipment:Electricity 54.48 979.82 01-JAN-00:10 3387.06 11-DEC-17:00
ElectricityPurchased:Facility 24165.65 287830.88 16-JAN-04:00 1610390.17 02-AUG-08:00
ElectricityPurchased:Plant 24165.65 287830.88 16-JAN-04:00 1610390.17 02-AUG-08:00
Cogeneration:ElectricityPurchased 24165.65 287830.88 16-JAN-04:00 1610390.17 02-AUG-08:00
General:Cogeneration:ElectricityPurchased 24165.65 287830.88 16-JAN-04:00 1610390.17 02-AUG-08:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 24165.65 287830.88 16-JAN-04:00 1610390.17 02-AUG-08:00
ElectricityNet:Plant 24165.65 287830.88 16-JAN-04:00 1610390.17 02-AUG-08:00
Cogeneration:ElectricityNet 24165.65 287830.88 16-JAN-04:00 1610390.17 02-AUG-08:00
General:Cogeneration:ElectricityNet 24165.65 287830.88 16-JAN-04:00 1610390.17 02-AUG-08:00
Fans:Electricity 1303.60 6797.04 01-JAN-09:40 183130.10 15-JUN-14:30
General:Fans:Electricity 1303.60 6797.04 01-JAN-09:40 183130.10 15-JUN-14:30
ExteriorLights:Electricity 322.40 0.00 01-JAN-07:20 37611.08 01-JAN-06:10
General:ExteriorLights:Electricity 322.40 0.00 01-JAN-07:20 37611.08 01-JAN-06:10
ComputerHVAC:ExteriorEquipment:Electricity 1349.07 17083.47 01-JAN-00:10 68333.87 31-MAR-23:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
Cooling:Electricity 1598.84 1380.90 28-JAN-07:10 358019.12 21-JUL-10:20
General:Cooling:Electricity 1598.84 1380.90 28-JAN-07:10 358019.12 21-JUL-10:20
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 600.62 700.59 01-JAN-00:40 52582.69 20-JUL-15:00
General:Pumps:Electricity 600.62 700.59 01-JAN-00:40 52582.69 20-JUL-15:00
WIRED_LTG_ELECTRICITY 56.91 0.00 01-JAN-00:10 5587.74 22-NOV-17:10
WIRED_INT_EQUIP 5334.97 88964.76 31-MAR-23:10 305206.10 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 930.13 5695.87 16-APR-16:30 630632.51 27-DEC-07:10
NaturalGas:Plant 930.13 5695.87 16-APR-16:30 630632.51 27-DEC-07:10
Heating:NaturalGas 288.39 0.00 01-JAN-00:10 601708.83 27-DEC-07:10
Boiler:Heating:NaturalGas 288.39 0.00 01-JAN-00:10 601708.83 27-DEC-07:10
WaterSystems:NaturalGas 641.74 5695.87 16-APR-16:30 78522.57 30-JAN-12:40
Water Heater:WaterSystems:NaturalGas 641.74 5695.87 16-APR-16:30 78522.57 30-JAN-12:40


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 10464.99 5912.19 28-JAN-07:10 2669511.49 20-JUL-15:00
PlantLoopCoolingDemand:HVAC 10464.99 5912.19 28-JAN-07:10 2669511.49 20-JUL-15:00
CoolingCoils:PlantLoopCoolingDemand 10464.99 5912.19 28-JAN-07:10 2669511.49 20-JUL-15:00
DistrictCooling:Facility 7175.32 87017.56 15-JAN-06:00 370232.07 07-AUG-14:00
DistrictCooling:HVAC 7175.32 87017.56 15-JAN-06:00 370232.07 07-AUG-14:00
Cooling:DistrictCooling 7175.32 87017.56 15-JAN-06:00 370232.07 07-AUG-14:00
General:Cooling:DistrictCooling 7175.32 87017.56 15-JAN-06:00 370232.07 07-AUG-14:00


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 10247.63 0.00 01-JAN-00:10 0.00 15-JUN-13:00
Water:Plant 10247.63 0.00 01-JAN-00:10 0.00 15-JUN-13:00
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Facility 10247.63 0.00 01-JAN-00:10 0.00 15-JUN-13:00
MainsWater:Plant 10247.63 0.00 01-JAN-00:10 0.00 15-JUN-13:00
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 7967.46 0.00 01-JAN-00:10 0.00 01-JUN-14:40
General:HeatRejection:Water 7967.46 0.00 01-JAN-00:10 0.00 01-JUN-14:40
HeatRejection:MainsWater 7967.46 0.00 01-JAN-00:10 0.00 01-JUN-14:40
General:HeatRejection:MainsWater 7967.46 0.00 01-JAN-00:10 0.00 01-JUN-14:40


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 54707.37 100216.92 16-JAN-06:00 11165807.06 20-JUL-15:00
EnergyTransfer:Building 18919.59 90819.43 16-JAN-06:00 1484033.67 07-AUG-16:00
EnergyTransfer:Zone:BASEMENT 618.58 0.00 01-JAN-00:10 71255.65 13-NOV-06:10
Heating:EnergyTransfer 81.27 0.00 01-JAN-15:40 251904.72 04-DEC-06:10
Heating:EnergyTransfer:Zone:BASEMENT 4.88 0.00 01-JAN-00:10 19305.31 01-JUL-16:30
General:Heating:EnergyTransfer 81.27 0.00 01-JAN-15:40 251904.72 04-DEC-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 4.88 0.00 01-JAN-00:10 19305.31 01-JUL-16:30
Cooling:EnergyTransfer 18838.33 90240.20 16-JAN-06:00 1484033.67 07-AUG-16:00
Cooling:EnergyTransfer:Zone:BASEMENT 613.70 0.00 01-JAN-00:10 71255.65 13-NOV-06:10
General:Cooling:EnergyTransfer 18838.33 90240.20 16-JAN-06:00 1484033.67 07-AUG-16:00
General:Cooling:EnergyTransfer:Zone:BASEMENT 613.70 0.00 01-JAN-00:10 71255.65 13-NOV-06:10
EnergyTransfer:Zone:CORE_BOTTOM 621.55 0.00 01-JAN-00:10 50454.84 07-AUG-09:10
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 621.55 0.00 01-JAN-00:10 50454.84 07-AUG-09:10
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 621.55 0.00 01-JAN-00:10 50454.84 07-AUG-09:10
EnergyTransfer:Zone:CORE_MID 4461.58 0.00 01-JAN-00:10 382728.18 30-AUG-05:10
Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_MID 4461.58 0.00 01-JAN-00:10 382728.18 30-AUG-05:10
General:Cooling:EnergyTransfer:Zone:CORE_MID 4461.58 0.00 01-JAN-00:10 382728.18 30-AUG-05:10
EnergyTransfer:Zone:CORE_TOP 426.29 0.00 01-JAN-00:10 47272.08 03-JUL-13:10
Heating:EnergyTransfer:Zone:CORE_TOP 1.86 0.00 01-JAN-00:10 43514.79 04-DEC-05:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 1.86 0.00 01-JAN-00:10 43514.79 04-DEC-05:10
Cooling:EnergyTransfer:Zone:CORE_TOP 424.43 0.00 01-JAN-00:10 47272.08 03-JUL-13:10
General:Cooling:EnergyTransfer:Zone:CORE_TOP 424.43 0.00 01-JAN-00:10 47272.08 03-JUL-13:10
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 77.85 0.00 01-JAN-00:10 10375.13 03-JUL-13:50
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 77.85 0.00 01-JAN-00:10 10375.13 03-JUL-13:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 77.85 0.00 01-JAN-00:10 10375.13 03-JUL-13:50
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 69.89 0.00 01-JAN-00:10 10640.23 03-JUL-08:50
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 69.89 0.00 01-JAN-00:10 10640.23 03-JUL-08:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 69.89 0.00 01-JAN-00:10 10640.23 03-JUL-08:50
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 110.68 0.00 01-JAN-00:10 14456.13 30-OCT-13:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 684.24 27-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 684.24 27-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 110.68 0.00 01-JAN-00:10 14456.13 30-OCT-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 110.68 0.00 01-JAN-00:10 14456.13 30-OCT-13:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 108.17 0.00 01-JAN-00:10 14360.92 07-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 108.17 0.00 01-JAN-00:10 14360.92 07-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 108.17 0.00 01-JAN-00:10 14360.92 07-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 588.14 0.00 01-JAN-00:10 91971.61 03-JUL-13:50
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 9.81 0.00 01-JAN-00:10 51432.85 28-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 9.81 0.00 01-JAN-00:10 51432.85 28-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 578.33 0.00 01-JAN-00:10 91971.61 03-JUL-13:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 578.33 0.00 01-JAN-00:10 91971.61 03-JUL-13:50
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 616.11 0.00 01-JAN-00:10 106343.67 03-JUL-09:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 3.94 0.00 01-JAN-00:10 37000.33 04-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 3.94 0.00 01-JAN-00:10 37000.33 04-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 612.17 0.00 01-JAN-00:10 106343.67 03-JUL-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 612.17 0.00 01-JAN-00:10 106343.67 03-JUL-09:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 943.84 0.00 01-JAN-00:10 138271.67 30-OCT-13:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1.21 0.00 01-JAN-00:10 46095.36 27-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1.21 0.00 01-JAN-00:10 46095.36 27-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 942.63 0.00 01-JAN-00:10 138271.67 30-OCT-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 942.63 0.00 01-JAN-00:10 138271.67 30-OCT-13:20
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 657.25 0.00 01-JAN-00:10 121338.36 15-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 1.51 0.00 01-JAN-00:10 27423.17 27-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 1.51 0.00 01-JAN-00:10 27423.17 27-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 655.74 0.00 01-JAN-00:10 121338.36 15-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 655.74 0.00 01-JAN-00:10 121338.36 15-JUN-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 64.39 0.00 01-JAN-00:10 12678.13 04-DEC-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 7.70 0.00 01-JAN-00:10 12678.13 04-DEC-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 7.70 0.00 01-JAN-00:10 12678.13 04-DEC-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 56.69 0.00 01-JAN-00:10 10696.81 03-JUL-14:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 56.69 0.00 01-JAN-00:10 10696.81 03-JUL-14:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 64.43 0.00 01-JAN-00:10 11388.30 03-JUL-09:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 3.09 0.00 01-JAN-00:10 9880.26 04-DEC-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 3.09 0.00 01-JAN-00:10 9880.26 04-DEC-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 61.35 0.00 01-JAN-00:10 11388.30 03-JUL-09:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 61.35 0.00 01-JAN-00:10 11388.30 03-JUL-09:20
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 92.25 0.00 01-JAN-00:10 15145.42 03-OCT-13:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 2.61 0.00 01-JAN-00:10 11821.10 04-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 2.61 0.00 01-JAN-00:10 11821.10 04-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 89.64 0.00 01-JAN-00:10 15145.42 03-OCT-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 89.64 0.00 01-JAN-00:10 15145.42 03-OCT-13:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 67.82 0.00 01-JAN-00:10 13125.55 15-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 2.11 0.00 01-JAN-00:10 6810.10 27-DEC-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 2.11 0.00 01-JAN-00:10 6810.10 27-DEC-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 65.71 0.00 01-JAN-00:10 13125.55 15-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 65.71 0.00 01-JAN-00:10 13125.55 15-JUN-16:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 69.98 0.00 01-JAN-00:10 10777.04 07-AUG-07:10
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.85 0.00 01-JAN-00:10 3215.20 10-DEC-10:50
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.85 0.00 01-JAN-00:10 3215.20 10-DEC-10:50
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 69.13 0.00 01-JAN-00:10 10777.04 07-AUG-07:10
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 69.13 0.00 01-JAN-00:10 10777.04 07-AUG-07:10
EnergyTransfer:Zone:MIDFLOOR_PLENUM 488.93 0.00 01-JAN-00:10 69254.60 03-JUL-15:00
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 24.48 0.00 01-JAN-00:10 29081.70 04-DEC-15:00
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 24.48 0.00 01-JAN-00:10 29081.70 04-DEC-15:00
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 464.45 0.00 01-JAN-00:10 69254.60 03-JUL-15:00
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 464.45 0.00 01-JAN-00:10 69254.60 03-JUL-15:00
EnergyTransfer:Zone:TOPFLOOR_PLENUM 96.93 0.00 01-JAN-00:10 20660.78 03-JUL-12:50
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 16.72 0.00 01-JAN-00:10 16087.98 04-DEC-06:10
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 16.72 0.00 01-JAN-00:10 16087.98 04-DEC-06:10
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 80.21 0.00 01-JAN-00:10 20660.78 03-JUL-12:50
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 80.21 0.00 01-JAN-00:10 20660.78 03-JUL-12:50
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 140.06 872.48 28-JAN-08:00 7772.11 30-APR-19:00
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 140.06 872.48 28-JAN-08:00 7772.11 30-APR-19:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 140.06 872.48 28-JAN-08:00 7772.11 30-APR-19:00
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1264.81 2007.99 16-JAN-08:20 73800.35 30-APR-18:50
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1264.81 2007.99 16-JAN-08:20 73800.35 30-APR-18:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1264.81 2007.99 16-JAN-08:20 73800.35 30-APR-18:50
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 119.29 0.43 14-JAN-13:30 7512.96 30-APR-19:00
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.49 0.00 01-JAN-14:10 591.80 28-JAN-05:00
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.49 0.00 01-JAN-14:10 591.80 28-JAN-05:00
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 118.80 0.00 01-JAN-00:10 7512.96 30-APR-19:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 118.80 0.00 01-JAN-00:10 7512.96 30-APR-19:00
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7150.75 87017.56 15-JAN-06:00 367614.02 07-AUG-16:00
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7150.75 87017.56 15-JAN-06:00 367614.02 07-AUG-16:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7150.75 87017.56 15-JAN-06:00 367614.02 07-AUG-16:00
PlantLoopHeatingDemand:Facility 563.22 0.00 01-JAN-00:10 520946.63 27-DEC-07:10
PlantLoopHeatingDemand:Plant 359.12 0.00 01-JAN-00:10 46361.03 31-JAN-12:20
WaterSystems:PlantLoopHeatingDemand 359.12 0.00 01-JAN-00:10 46361.03 31-JAN-12:20
General:WaterSystems:PlantLoopHeatingDemand 359.12 0.00 01-JAN-00:10 46361.03 31-JAN-12:20
EnergyTransfer:HVAC 10219.60 9367.76 16-JAN-08:10 2648908.81 20-JUL-15:00
HeatingCoils:EnergyTransfer 204.10 0.00 01-JAN-00:10 505934.45 27-DEC-07:10
PlantLoopHeatingDemand:HVAC 204.10 0.00 01-JAN-00:10 505934.45 27-DEC-07:10
HeatingCoils:PlantLoopHeatingDemand 204.10 0.00 01-JAN-00:10 505934.45 27-DEC-07:10
CoolingCoils:EnergyTransfer 10015.50 4531.29 28-JAN-07:10 2648908.81 20-JUL-15:00
DistrictHeating:Facility 0.00 0.00 01-JAN-00:20 12.25 01-FEB-00:40
DistrictHeating:HVAC 0.00 0.00 01-JAN-00:20 12.25 01-FEB-00:40
Heating:DistrictHeating 0.00 0.00 01-JAN-00:20 12.25 01-FEB-00:40
General:Heating:DistrictHeating 0.00 0.00 01-JAN-00:20 12.25 01-FEB-00:40
EnergyTransfer:Plant 25568.18 0.00 01-JAN-00:10 7355972.89 20-JUL-15:00
LoopToLoop:EnergyTransfer 8558.78 0.00 01-JAN-00:10 2464132.24 20-JUL-15:00
WaterSystems:EnergyTransfer 359.12 0.00 01-JAN-00:10 46361.03 31-JAN-12:20
WaterUse:WaterSystems:EnergyTransfer 359.12 0.00 01-JAN-00:10 46361.03 31-JAN-12:20
Boilers:EnergyTransfer 202.05 0.00 01-JAN-00:10 499801.08 27-DEC-07:10
Chillers:EnergyTransfer 7649.44 0.00 01-JAN-00:10 2276436.44 20-JUL-15:00
HeatRejection:EnergyTransfer 8798.80 0.00 01-JAN-00:10 2614353.45 21-JUL-10:20
General:HeatRejection:EnergyTransfer 8798.80 0.00 01-JAN-00:10 2614353.45 21-JUL-10:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 4.883 -613.701 0.000 0.000 92.627 135.577 424.397 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.000 -43.783
CORE_BOTTOM 0.000 0.000 0.000 -621.547 0.000 0.000 83.421 121.758 289.614 0.000 0.000 0.000 126.754 0.000 0.000 0.000 0.000 -0.001
CORE_MID 0.000 0.000 0.000 -4461.569 0.000 0.000 838.284 1217.578 2896.128 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -490.421
CORE_TOP 0.000 0.000 1.859 -424.424 0.000 0.000 86.177 121.758 289.613 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -74.982
PERIMETER_BOT_ZN_3 0.000 0.000 0.000 -77.854 0.000 0.000 10.628 9.014 36.365 24.642 0.000 0.103 35.374 0.000 -37.492 0.000 -0.781 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.000 -69.892 0.000 0.000 6.814 5.771 23.435 50.675 0.000 0.069 6.362 0.000 -22.713 0.000 -0.521 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.001 -110.680 0.000 0.000 10.521 8.776 36.366 86.646 0.000 0.099 3.825 0.000 -34.739 0.000 -0.814 -0.001
PERIMETER_BOT_ZN_4 0.000 0.000 0.000 -108.170 0.000 0.000 6.761 5.703 23.435 49.949 0.000 0.059 50.409 0.000 -27.550 0.000 -0.596 0.000
PERIMETER_MID_ZN_3 0.000 0.000 9.810 -578.326 0.000 0.000 110.210 90.095 363.654 256.593 0.000 2.397 100.379 0.000 -338.362 0.000 -16.450 0.000
PERIMETER_MID_ZN_2 0.000 0.000 3.943 -612.168 0.000 0.000 51.131 57.674 234.352 507.017 0.000 1.492 0.001 0.000 -215.375 0.000 -11.624 -16.442
PERIMETER_MID_ZN_1 0.000 0.000 1.206 -942.619 0.000 0.000 105.811 87.821 363.660 864.836 0.000 2.253 0.041 0.000 -339.806 0.000 -18.765 -124.397
PERIMETER_MID_ZN_4 0.000 0.000 1.514 -655.724 0.000 0.000 69.886 57.001 234.351 509.387 0.000 1.391 34.980 0.000 -240.532 0.000 -12.255 -0.009
PERIMETER_TOP_ZN_3 0.000 0.000 7.699 -56.693 0.000 0.000 11.224 9.009 36.365 25.915 0.000 0.279 0.003 0.000 -31.228 0.000 -1.867 -0.705
PERIMETER_TOP_ZN_2 0.000 0.000 3.088 -61.347 0.000 0.000 7.073 5.767 23.435 50.982 0.000 0.176 0.001 0.000 -20.093 0.000 -1.335 -7.746
PERIMETER_TOP_ZN_1 0.000 0.000 2.613 -89.635 0.000 0.000 10.732 8.782 36.366 86.825 0.000 0.264 0.002 0.000 -31.939 0.000 -2.175 -21.832
PERIMETER_TOP_ZN_4 0.000 0.000 2.107 -65.710 0.000 0.000 7.115 5.700 23.435 51.039 0.000 0.168 0.185 0.000 -22.615 0.000 -1.424 -0.000
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -140.063 0.000 0.000 0.950 3.264 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -18.031
DATACENTER_MID_ZN_6 0.000 0.000 0.000 -1264.813 0.000 0.000 9.495 32.637 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -316.125
DATACENTER_TOP_ZN_6 0.000 0.000 0.491 -118.803 0.000 0.000 0.950 3.264 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -39.782
DATACENTER_BASEMENT_ZN_6 0.000 -7150.752 0.000 0.000 0.000 0.000 20.569 38.227 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -402.901
GROUNDFLOOR_PLENUM 0.849 -69.134 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.189 69.792 0.000 0.000 0.000 -1.696 0.000
MIDFLOOR_PLENUM 24.479 -464.452 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 3.495 465.468 0.000 0.000 0.000 -28.990 -0.002
TOPFLOOR_PLENUM 16.725 -80.205 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.324 66.099 0.000 0.000 0.000 -2.943 -0.004
Total Facility 42.052 -7764.543 39.213 -11073.737 0.000 0.000 1540.379 2025.176 14676.396 2564.506 0.000 12.757 959.677 0.000 -1362.445 0.000 -102.235 -1557.164


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 27-NOV-04:01 0.00 0.00 0.00 -98062.19 0.00 0.00 0.00 657.72 13457.54 0.00 0.00 0.00 83946.93 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 13-NOV-04:02 0.00 0.00 0.00 -84516.87 0.00 0.00 0.00 590.68 5937.65 0.00 0.00 0.00 77988.55 0.00 -0.00 0.00 0.00 0.00
CORE_MID 30-AUG-05:04 0.00 0.00 0.00 -739244.22 0.00 0.00 8276.74 11812.12 76473.61 0.00 0.00 0.00 642681.74 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 05-JUL-03:02 0.00 0.00 0.00 -75384.10 0.00 0.00 0.00 590.68 5937.62 0.00 0.00 0.00 68855.80 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 03-JUL-03:02 0.00 0.00 0.00 -14271.92 0.00 0.00 0.00 74.17 745.56 0.00 0.00 17.36 13442.09 0.00 -7.25 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 04-SEP-08:12 0.00 0.00 0.00 -15726.44 0.00 0.00 23.40 22.74 464.11 10977.14 0.00 0.00 4257.09 0.00 -0.00 0.00 -18.05 0.00
PERIMETER_BOT_ZN_1 01-OCT-12:42 0.00 0.00 0.00 -19125.09 0.00 0.00 35.77 35.29 720.19 15467.29 0.00 6.67 2859.87 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 29-MAY-15:31 0.00 0.00 0.00 -21474.19 0.00 0.00 21.06 22.74 464.11 12301.04 0.00 24.91 8640.32 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 04-JUL-16:01 0.00 0.00 0.00 -141661.89 0.00 0.00 444.64 352.88 7201.84 35487.28 0.00 676.99 97498.26 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 29-MAY-09:32 0.00 0.00 0.00 -161661.73 0.00 0.00 232.14 227.41 4641.14 83472.78 0.00 0.00 73417.58 0.00 -0.00 0.00 -329.32 0.00
PERIMETER_MID_ZN_1 22-OCT-12:42 0.00 0.00 0.00 -177116.17 0.00 0.00 363.43 352.89 7201.95 145917.80 0.00 0.00 23317.28 0.00 -0.00 0.00 -37.18 0.00
PERIMETER_MID_ZN_4 04-JUL-16:01 0.00 0.00 0.00 -180711.71 0.00 0.00 214.00 227.41 4641.11 94245.99 0.00 316.63 81066.57 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 04-JUL-16:01 0.00 0.00 0.00 -17267.03 0.00 0.00 41.08 35.29 720.18 3386.33 0.00 74.47 13009.67 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 02-JUL-09:22 0.00 0.00 0.00 -17320.39 0.00 0.00 21.84 22.74 464.11 9439.73 0.00 0.00 7371.96 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 01-OCT-13:32 0.00 0.00 0.00 -20657.58 0.00 0.00 34.04 35.29 720.19 13969.32 0.00 29.55 5869.20 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 04-JUL-16:01 0.00 0.00 0.00 -20379.13 0.00 0.00 19.83 22.74 464.11 9326.50 0.00 35.27 10510.68 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 30-APR-19:03 0.00 0.00 0.00 -7794.88 0.00 0.00 0.00 15.83 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -15.38
DATACENTER_MID_ZN_6 30-APR-18:43 0.00 0.00 0.00 -73866.47 0.00 0.00 0.00 158.32 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -4236.08
DATACENTER_TOP_ZN_6 30-APR-19:03 0.00 0.00 0.00 -7537.34 0.00 0.00 0.00 15.83 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -272.91
DATACENTER_BASEMENT_ZN_6 07-AUG-16:00 0.00 -367614.02 0.00 0.00 0.00 0.00 2183.10 3337.76 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -17539.37
GROUNDFLOOR_PLENUM 07-AUG-05:15 0.00 -14033.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29 14033.12 0.00 -0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 02-JUN-05:02 0.00 -77200.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 77460.73 0.00 -0.00 0.00 -260.15 0.00
TOPFLOOR_PLENUM 03-JUL-12:50 0.00 -20660.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.25 20631.10 0.00 -0.00 0.00 0.00 0.00
Total Facility 07-AUG-05:02 0.00 -427969.32 0.00 -1467773.53 0.00 0.00 16002.88 22094.05 616289.16 0.00 0.00 155.42 1256670.01 0.00 -15467.23 0.00 -1.43 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 01-JUL-16:13 0.00 0.00 20137.43 0.00 0.00 0.00 424.77 657.72 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -34677.47
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_TOP 04-DEC-05:01 0.00 0.00 65373.16 0.00 0.00 0.00 0.00 1181.21 5937.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -72492.00
PERIMETER_BOT_ZN_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 27-DEC-06:01 0.00 0.00 4701.67 0.00 0.00 0.00 140.70 148.32 960.26 0.00 0.00 0.00 0.00 0.00 -4536.36 0.00 -26.38 -1388.21
PERIMETER_BOT_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 28-DEC-05:01 0.00 0.00 107245.87 0.00 0.00 0.00 0.00 1483.13 7455.61 0.00 0.00 0.00 0.00 0.00 -41547.68 0.00 -1936.74 -72700.19
PERIMETER_MID_ZN_2 27-DEC-05:01 0.00 0.00 107026.55 0.00 0.00 0.00 0.00 955.79 4804.68 0.00 0.00 0.00 0.00 0.00 -27912.94 0.00 -272.28 -84601.80
PERIMETER_MID_ZN_1 27-DEC-05:01 0.00 0.00 116165.31 0.00 0.00 0.00 0.00 1483.16 7455.72 0.00 0.00 0.00 0.00 0.00 -42251.42 0.00 -414.01 -82438.78
PERIMETER_MID_ZN_4 27-DEC-06:01 0.00 0.00 99050.26 0.00 0.00 0.00 941.51 955.79 6188.15 0.00 0.00 0.00 0.00 0.00 -28600.54 0.00 -407.51 -78127.64
PERIMETER_TOP_ZN_3 26-DEC-04:01 0.00 0.00 14634.26 0.00 0.00 0.00 0.00 74.17 745.56 0.00 0.00 0.00 0.00 0.00 -2862.17 0.00 -319.76 -12272.05
PERIMETER_TOP_ZN_2 26-DEC-04:01 0.00 0.00 13233.15 0.00 0.00 0.00 0.00 47.80 480.47 0.00 0.00 0.00 0.00 0.00 -1946.52 0.00 -220.01 -11594.88
PERIMETER_TOP_ZN_1 04-DEC-04:11 0.00 0.00 15328.76 0.00 0.00 0.00 0.00 74.17 745.57 0.00 0.00 0.00 0.00 0.00 -3018.60 0.00 0.00 -13129.90
PERIMETER_TOP_ZN_4 04-DEC-04:11 0.00 0.00 13991.96 0.00 0.00 0.00 0.00 47.80 480.46 0.00 0.00 0.00 0.00 0.00 -2115.94 0.00 0.00 -12404.28
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 28-JAN-04:45 0.00 0.00 595.53 0.00 0.00 0.00 0.00 15.83 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2559.97
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 26-DEC-04:01 10132.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -343.79 -9788.64
MIDFLOOR_PLENUM 02-JUL-16:11 57720.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1987.09 0.00 0.00 -0.00 0.00 0.00 -59707.28
TOPFLOOR_PLENUM 26-DEC-06:13 18027.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -148.53 -17879.23
Total Facility 27-DEC-05:01 -774162.96 398798.22 536565.69 -398798.22 0.00 0.00 0.00 22094.05 587299.42 0.00 0.00 0.00 0.00 0.00 -169139.07 0.00 -2401.29 -200255.85



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 10.5832 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 9.8275 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 98.7390 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 91.2459 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 10.2941 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 9.9838 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.5896 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.5896 0.2147 1.0000 Not calculated 1.2002 0.2147    
AIRLOOP DATACENTER BOT 0.5289 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5289 0.0296 1.0000 Not calculated 0.0156 0.0296    
AIRLOOP DATACENTER MID 5.0287 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 5.0287 0.0311 1.0000 Not calculated 0.1563 0.0311    
AIRLOOP DATACENTER TOP 0.5106 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5106 0.0306 1.0000 Not calculated 0.0156 0.0306    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 5.2916 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.8897 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 49.3695 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 27.9929 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.1470 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.8893 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.5896 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.5896 1.0000 1.0000 Not calculated 1.2002 0.2147    
AIRLOOP DATACENTER BOT 0.5289 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5289 1.0000 1.0000 Not calculated 0.0156 0.0296    
AIRLOOP DATACENTER MID 5.0287 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 5.0287 1.0000 1.0000 Not calculated 0.1563 0.0311    
AIRLOOP DATACENTER TOP 0.5106 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5106 1.0000 1.0000 Not calculated 0.0156 0.0306    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.002360 149.6021 0.000305 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.002360 1.9486 0.000305 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.002360 19.4861 0.000305 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.002360 1.9486 0.000305 36.20 0.0156 1.0000 0.0156 1.000 0.0156


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.002360 149.60 0.000305 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BOT 0.002360 1.95 0.000305 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.002360 19.49 0.000305 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.002360 1.95 0.000305 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.5896 5.5896 5.5896 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.0749 6.0749 1.9440 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 57.0645 57.0645 19.0025 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.6807 5.6807 1.9485 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0505 1.0505 0.2437 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9842 0.9842 0.1968 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1651 1.1651 0.2435 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3084 1.3084 0.2617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.7405 9.7405 2.3864 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.1577 10.1577 2.0315 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.8615 10.8615 2.3895 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.9147 10.9147 2.1829 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1328 1.1328 0.2447 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0458 1.0458 0.2092 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2343 1.2343 0.2469 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2005 1.2005 0.2401 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5289 0.5289 0.5289 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.0287 5.0287 5.0287 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5106 0.5106 0.5106 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 10.5832 9.8275 10.5832 2.8897 0.0000 1.0000
VAV_MID WITH REHEAT 98.7390 91.2459 98.7390 27.9929 0.0000 1.0000
VAV_TOP WITH REHEAT 10.2941 9.9838 10.2941 2.8893 0.0000 1.0000
CAV_BAS 5.5896 5.5896 5.5896 5.5896 1.2002 1.0000
AIRLOOP DATACENTER BOT 0.5289 0.5289 0.5289 0.5289 0.0156 1.0000
AIRLOOP DATACENTER MID 5.0287 5.0287 5.0287 5.0287 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.5106 0.5106 0.5106 0.5106 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.5896 5.5896 5.5896 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.0375 3.0375 1.9440 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 28.5322 28.5322 19.0025 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.8403 2.8403 1.9485 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5253 0.5253 0.2437 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4921 0.4921 0.1968 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5826 0.5826 0.2435 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6542 0.6542 0.2617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.8703 4.8703 2.3864 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.0788 5.0788 2.0315 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.4308 5.4308 2.3895 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.4574 5.4574 2.1829 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5664 0.5664 0.2447 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5229 0.5229 0.2092 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6172 0.6172 0.2469 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6002 0.6002 0.2401 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5289 0.5289 0.5289 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.0287 5.0287 5.0287 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5106 0.5106 0.5106 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 5.2916 2.8897 2.8897 2.8897 0.0000 1.0000
VAV_MID WITH REHEAT 49.3695 27.9929 27.9929 27.9929 0.0000 1.0000
VAV_TOP WITH REHEAT 5.1470 2.8893 2.8893 2.8893 0.0000 1.0000
CAV_BAS 5.5896 5.5896 5.5896 5.5896 1.2002 1.0000
AIRLOOP DATACENTER BOT 0.5289 0.5289 0.5289 0.5289 0.0156 1.0000
AIRLOOP DATACENTER MID 5.0287 5.0287 5.0287 5.0287 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.5106 0.5106 0.5106 0.5106 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 1.17
Number of hours cooling loads not met 253.83
Number of hours not met 255.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.25
Heating -- Boiler 0.00 0.00 288.39 601708.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 1598.84 358019.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7175.32 370232.07 0.00 0.00
Interior Lighting -- LightsWired 2025.18 198852.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 322.40 37611.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5334.97 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 54.48 3387.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ComputerHVAC 1349.07 68333.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 1303.60 183130.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 600.62 52582.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 380.45 45559.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 641.74 78522.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 14676.40 24165.65
Natural Gas 0.00 930.13
Additional 0.00 7175.32
Total 14676.40 32271.11


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 43.72
Space Heating 0.00
Space Cooling 34.52
Fans (All) 28.14
Service Water Heating 0.00
Receptacle Equipment 316.85
Miscellaneous (All) 521.71
Subtotal 521.71


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 6.23
Service Water Heating 13.85
Miscellaneous (All) 20.08
Subtotal 20.08


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.28
Space Heating 0.89
Space Cooling 27.19
Fans (All) 4.04
Service Water Heating 1.99
Receptacle Equipment 45.48
Miscellaneous 14.14


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2362. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4049. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 1565. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8434.83 325.17 0.00 0.00 0.00
CORE_BOTTOM 8753.17 6.83 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8738.83 21.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8669.83 90.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8674.67 85.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8302.17 457.83 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8754.83 5.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8642.50 117.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8687.83 72.17 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8452.00 308.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8717.50 42.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8601.17 158.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8648.50 111.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8437.83 322.17 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8731.33 28.67 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8729.83 30.17 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8727.50 32.50 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 8760.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8573.17 186.83 0.00 0.00 0.00
Min 8302.17 0.00 0.00 0.00 0.00
Max 8760.00 457.83 0.00 0.00 0.00
Average 8655.54 104.46 0.00 0.00 0.00
Sum 199077.50 2402.50 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 367416.67 1199.33 0.00 0.00 0.00
CORE_BOTTOM 330789.00 24.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2258.83 9.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2255.17 12.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2256.50 11.50 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 103395.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 367416.67 1199.33 0.00 0.00 0.00
Average 80280.27 54.64 0.00 0.00 0.00
Sum 1846446.17 1256.83 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 7918.83 841.17 0.00 0.00 0.00
CORE_BOTTOM 8453.50 306.50 0.00 0.00 0.00
CORE_MID 8455.00 305.00 0.00 0.00 0.00
CORE_TOP 8432.33 327.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8359.83 400.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8389.83 370.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8263.17 496.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7899.33 860.67 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8371.17 388.83 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8236.50 523.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8251.50 508.50 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8090.50 669.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8324.67 435.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8213.33 546.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8213.17 546.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8088.67 671.33 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 8760.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8223.83 536.17 0.00 0.00 0.00
MIDFLOOR_PLENUM 8346.67 413.33 0.00 0.00 0.00
TOPFLOOR_PLENUM 7759.00 1001.00 0.00 0.00 0.00
Min 7759.00 0.00 0.00 0.00 0.00
Max 8760.00 1001.00 0.00 0.00 0.00
Average 8318.73 441.27 0.00 0.00 0.00
Sum 191330.83 10149.17 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 364657.50 3958.50 0.00 0.00 0.00
CORE_BOTTOM 330188.00 625.00 0.00 0.00 0.00
CORE_MID 330405.00 408.00 0.00 0.00 0.00
CORE_TOP 330250.00 563.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38924.83 0.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24908.83 0.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38924.50 0.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24903.00 6.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18353.67 0.33 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38924.83 0.17 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24908.33 0.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38924.83 0.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24908.83 0.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38924.83 0.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24908.33 0.67 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 103395.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 364657.50 3958.50 0.00 0.00 0.00
Average 80093.01 241.90 0.00 0.00 0.00
Sum 1842139.33 5563.67 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:30

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

For: Environment

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B

For: Environment

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO

For: Environment

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.458228E+11 95628.38 17-JAN-04:02 5.60 4.12 0.566998E+10 7499.09 02-JAN-10:20 5.60 4.12
February 0.396172E+11 93229.87 13-FEB-04:12 10.57 6.17 0.514185E+10 7499.38 13-FEB-10:20 10.73 9.09
March 0.462286E+11 89680.53 23-MAR-04:12 8.13 2.61 0.613602E+10 7499.05 22-MAR-09:09 8.13 2.61
April 0.449742E+11 93253.36 03-APR-03:02 20.00 8.11 0.545354E+10 7499.10 10-APR-13:39 23.33 9.34
May 0.486649E+11 94455.52 15-MAY-03:02 23.12 10.24 0.590657E+10 7499.06 05-MAY-13:50 23.12 10.24
June 0.500744E+11 94964.22 12-JUN-03:02 17.38 6.37 0.588707E+10 7499.03 29-JUN-13:09 25.68 17.54
July 0.538979E+11 87525.15 11-JUL-03:02 23.80 15.76 0.547989E+10 7498.97 11-JUL-09:09 29.18 18.50
August 0.618807E+11 94066.56 28-AUG-03:02 22.20 12.84 0.614569E+10 7499.08 11-AUG-09:09 22.20 12.84
September 0.574128E+11 95430.64 11-SEP-03:02 18.03 11.88 0.546095E+10 7499.23 06-SEP-09:20 18.03 11.88
October 0.587947E+11 95939.89 30-OCT-03:02 11.10 6.82 0.567945E+10 7499.22 17-OCT-09:00 11.10 6.82
November 0.550375E+11 98069.63 27-NOV-04:01 3.80 -0.8 0.562202E+10 7498.87 03-NOV-09:20 3.80 -0.8
December 0.512956E+11 95764.54 18-DEC-04:03 5.40 -1.6 0.547711E+10 7498.92 12-DEC-10:30 5.40 -1.6
                     
Annual Sum or Average 0.613701E+12         0.680601E+11        
Minimum of Months 0.396172E+11 87525.15   3.80 -1.6 0.514185E+10 7498.87   3.80 -1.6
Maximum of Months 0.618807E+11 98069.63   23.80 15.76 0.614569E+10 7499.38   29.18 18.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.369177E+11 80524.87 02-JAN-04:03 2.98 1.95 0.506941E+10 6734.82 02-JAN-10:09 10.97 7.20
February 0.373840E+11 77624.49 27-FEB-05:02 8.90 7.68 0.460151E+10 6735.09 13-FEB-10:09 8.90 7.68
March 0.489461E+11 76469.11 28-MAR-04:03 7.70 2.92 0.549850E+10 6734.72 22-MAR-09:09 7.70 2.92
April 0.565843E+11 78533.24 18-APR-03:02 8.80 5.96 0.487966E+10 6734.82 27-APR-09:09 20.87 11.97
May 0.530330E+11 77747.37 22-MAY-03:02 18.80 14.03 0.528497E+10 6734.85 08-MAY-09:09 18.80 14.03
June 0.598448E+11 70839.36 29-JUN-05:03 17.67 15.22 0.526647E+10 6734.77 12-JUN-09:00 17.67 15.22
July 0.638841E+11 77510.12 17-JUL-05:04 20.50 20.11 0.489329E+10 6734.71 11-JUL-09:09 20.50 20.11
August 0.692593E+11 78956.25 14-AUG-05:04 17.30 16.19 0.549627E+10 6734.75 28-AUG-09:09 25.28 16.40
September 0.523687E+11 81319.50 25-SEP-03:02 11.02 9.18 0.488344E+10 6734.76 12-SEP-09:20 11.02 9.18
October 0.524398E+11 83572.02 10-OCT-03:02 12.30 8.79 0.507970E+10 6735.01 17-OCT-09:00 21.10 16.29
November 0.471249E+11 84521.39 13-NOV-04:02 3.30 0.86 0.503115E+10 6734.66 24-NOV-10:09 17.48 6.61
December 0.437605E+11 83889.43 26-DEC-04:01 -0.1 -2.0 0.490278E+10 6734.67 04-DEC-10:09 -0.1 -2.0
                     
Annual Sum or Average 0.621547E+12         0.608871E+11        
Minimum of Months 0.369177E+11 70839.36   -0.1 -2.0 0.460151E+10 6734.66   -0.1 -2.0
Maximum of Months 0.692593E+11 84521.39   20.50 20.11 0.549850E+10 6735.09   25.28 20.11



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.257304E+11 64880.59 13-JAN-06:03 3.22 0.84 0.497713E+10 6734.63 06-JAN-10:09 3.22 0.84
February 0.262296E+11 68893.60 23-FEB-06:02 10.60 5.29 0.454596E+10 6735.00 13-FEB-10:09 10.60 5.29
March 0.340104E+11 71226.64 17-MAR-05:02 3.72 -1.9 0.546038E+10 6734.71 22-MAR-09:09 15.15 5.68
April 0.376707E+11 71556.12 11-APR-05:02 4.90 0.49 0.486805E+10 6734.80 27-APR-09:09 20.87 11.97
May 0.446072E+11 72039.15 25-MAY-04:03 15.50 13.40 0.527904E+10 6734.81 08-MAY-09:09 15.50 13.40
June 0.475086E+11 71478.90 28-JUN-04:03 17.38 15.76 0.526375E+10 6734.77 22-JUN-09:09 17.38 15.76
July 0.463888E+11 72075.33 19-JUL-04:03 20.00 20.00 0.488822E+10 6734.70 24-JUL-09:20 27.07 18.10
August 0.480615E+11 73933.50 30-AUG-05:04 18.62 14.19 0.549138E+10 6734.78 11-AUG-09:09 18.62 14.19
September 0.422690E+11 71547.37 05-SEP-05:04 16.20 15.65 0.487613E+10 6734.79 06-SEP-09:20 25.57 18.61
October 0.384144E+11 72349.66 07-OCT-05:02 10.10 8.79 0.506122E+10 6734.95 17-OCT-09:00 21.10 16.29
November 0.304147E+11 69677.44 09-NOV-06:03 13.40 5.90 0.498326E+10 6734.61 02-NOV-09:09 13.40 5.90
December 0.248522E+11 48104.39 14-DEC-06:02 2.70 1.71 0.478551E+10 6734.65 12-DEC-10:30 2.70 1.71
                     
Annual Sum or Average 0.446158E+12         0.604800E+11        
Minimum of Months 0.248522E+11 48104.39   2.70 -1.9 0.454596E+10 6734.61   2.70 0.84
Maximum of Months 0.480615E+11 73933.50   20.00 20.00 0.549138E+10 6735.00   27.07 18.61



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.182648E+11 21780.73 12-JAN-17:00 17.80 9.80 0.437758E+10 6734.21 13-JAN-14:00 18.30 8.81
February 0.194885E+11 27462.56 08-FEB-15:00 11.70 2.53 0.415953E+10 6734.36 07-FEB-14:09 11.70 2.53
March 0.270560E+11 61035.88 16-MAR-05:02 14.43 5.41 0.522085E+10 6734.54 17-MAR-09:50 8.12 1.75
April 0.357750E+11 69652.57 21-APR-05:02 15.10 5.09 0.482765E+10 6734.78 27-APR-09:09 20.87 11.97
May 0.466339E+11 70592.43 25-MAY-05:02 15.10 13.30 0.527342E+10 6734.78 08-MAY-09:09 15.10 13.30
June 0.538769E+11 71568.52 28-JUN-04:03 17.38 15.76 0.526675E+10 6734.76 22-JUN-09:09 17.38 15.76
July 0.530973E+11 75399.75 05-JUL-03:02 18.90 16.84 0.489455E+10 6734.70 11-JUL-09:09 29.18 18.50
August 0.527496E+11 67793.29 17-AUG-05:03 17.20 16.10 0.549330E+10 6734.79 11-AUG-09:09 17.20 16.10
September 0.433831E+11 69576.53 08-SEP-05:03 15.78 14.67 0.487149E+10 6734.79 06-SEP-09:20 15.78 14.67
October 0.345379E+11 69453.30 19-OCT-05:02 18.22 11.67 0.500086E+10 6734.85 17-OCT-09:00 18.22 11.67
November 0.225185E+11 55948.13 10-NOV-06:03 17.87 11.05 0.461633E+10 6734.60 01-NOV-09:50 17.87 11.05
December 0.170449E+11 17289.76 01-DEC-17:00 10.60 4.87 0.412921E+10 6617.57 01-DEC-14:00 10.60 4.87
                     
Annual Sum or Average 0.424426E+12         0.581315E+11        
Minimum of Months 0.170449E+11 17289.76   10.60 2.53 0.412921E+10 6617.57   8.12 1.75
Maximum of Months 0.538769E+11 75399.75   18.90 16.84 0.549330E+10 6734.85   29.18 18.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.270939E+10 3003.47 02-JAN-15:00 17.80 9.34 0.585921E+09 845.60 13-JAN-14:09 17.88 8.77
February 0.298442E+10 4712.91 21-FEB-15:00 22.80 8.17 0.547576E+09 845.61 13-FEB-14:09 22.80 8.17
March 0.439458E+10 5446.07 15-MAR-13:50 23.22 9.65 0.674369E+09 845.62 22-MAR-09:09 15.15 5.68
April 0.687276E+10 10484.41 03-APR-05:02 17.48 7.89 0.610608E+09 845.63 27-APR-09:09 20.87 11.97
May 0.820560E+10 11671.95 15-MAY-05:02 21.05 9.61 0.664180E+09 845.64 08-MAY-09:09 21.05 9.61
June 0.108346E+11 12145.27 26-JUN-05:02 21.10 14.86 0.662957E+09 845.63 30-JUN-09:39 25.17 17.65
July 0.110759E+11 14274.11 03-JUL-03:02 28.90 17.76 0.616488E+09 845.63 03-JUL-09:00 32.20 18.73
August 0.108878E+11 14190.55 07-AUG-03:02 27.02 16.26 0.691328E+09 845.64 17-AUG-13:20 24.80 17.12
September 0.740764E+10 11949.89 11-SEP-05:03 15.60 11.05 0.613091E+09 845.63 11-SEP-09:50 25.32 12.16
October 0.579958E+10 11989.48 02-OCT-05:02 23.72 15.10 0.633879E+09 845.65 17-OCT-09:00 21.10 16.29
November 0.375450E+10 4854.15 09-NOV-15:00 23.30 12.64 0.614768E+09 845.61 30-NOV-14:00 17.80 10.67
December 0.292737E+10 3534.15 11-DEC-12:00 14.40 7.20 0.575738E+09 845.61 11-DEC-14:09 13.90 7.45
                     
Annual Sum or Average 0.778541E+11         0.749090E+10        
Minimum of Months 0.270939E+10 3003.47   14.40 7.20 0.547576E+09 845.60   13.90 5.68
Maximum of Months 0.110759E+11 14274.11   28.90 17.76 0.691328E+09 845.65   32.20 18.73



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.247543E+10 4675.73 04-JAN-09:20 9.07 3.28 0.392024E+09 544.96 02-JAN-10:09 9.07 3.28
February 0.287731E+10 6775.01 21-FEB-08:40 10.57 3.84 0.362602E+09 544.95 07-FEB-10:09 10.57 3.84
March 0.437092E+10 7005.87 07-MAR-09:00 15.00 7.11 0.437762E+09 544.95 06-MAR-10:09 15.00 7.11
April 0.649875E+10 15362.94 30-APR-08:32 19.43 12.60 0.394247E+09 545.33 19-APR-09:09 19.43 12.60
May 0.792253E+10 15632.32 29-MAY-08:12 20.73 15.00 0.428671E+09 545.75 15-MAY-09:00 20.73 15.00
June 0.941472E+10 15064.47 04-JUN-07:53 23.90 16.83 0.427452E+09 545.60 09-JUN-09:00 28.30 16.64
July 0.908058E+10 15055.55 04-JUL-07:33 24.27 18.48 0.397451E+09 545.80 03-JUL-09:00 24.27 18.48
August 0.898844E+10 15281.20 20-AUG-09:02 26.47 16.50 0.445362E+09 545.69 01-AUG-09:00 26.47 16.50
September 0.716953E+10 15736.90 04-SEP-08:12 21.83 17.83 0.395704E+09 545.84 11-SEP-09:00 25.60 12.20
October 0.521332E+10 9767.22 22-OCT-08:53 19.40 11.77 0.408454E+09 544.98 17-OCT-09:00 19.40 11.77
November 0.344287E+10 7399.90 10-NOV-08:40 18.13 11.62 0.397069E+09 544.95 24-NOV-10:09 17.48 6.61
December 0.243703E+10 3670.41 07-DEC-09:15 4.83 0.28 0.376108E+09 544.95 04-DEC-10:09 4.83 0.28
                     
Annual Sum or Average 0.698914E+11         0.486290E+10        
Minimum of Months 0.243703E+10 3670.41   4.83 0.28 0.362602E+09 544.95   4.83 0.28
Maximum of Months 0.941472E+10 15736.90   26.47 18.48 0.445362E+09 545.84   28.30 18.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.649547E+10 17696.01 01-JAN-13:53 15.60 9.33 0.620862E+09 846.38 03-JAN-14:00 20.60 8.39
February 0.627722E+10 18038.60 20-FEB-13:13 21.47 8.42 0.568262E+09 847.25 07-FEB-14:00 21.47 8.42
March 0.767824E+10 13565.46 26-MAR-14:32 21.70 8.67 0.681986E+09 846.79 22-MAR-13:00 21.70 8.67
April 0.895327E+10 17323.78 30-APR-13:13 29.40 12.37 0.611633E+09 846.27 04-APR-13:50 29.40 12.37
May 0.879112E+10 14732.33 29-MAY-14:52 32.20 16.37 0.664250E+09 845.66 05-MAY-13:00 32.20 16.37
June 0.106865E+11 13278.74 26-JUN-05:02 21.10 14.86 0.662909E+09 845.65 12-JUN-09:00 21.10 14.86
July 0.112447E+11 17308.08 30-JUL-13:02 30.78 19.90 0.616593E+09 846.18 31-JUL-13:00 32.20 19.72
August 0.126494E+11 17523.55 27-AUG-13:02 34.40 16.78 0.691912E+09 846.89 29-AUG-13:00 31.70 19.58
September 0.113295E+11 18115.47 17-SEP-12:32 31.50 15.75 0.614973E+09 851.27 29-SEP-13:39 28.13 14.71
October 0.109139E+11 19125.15 01-OCT-12:42 30.92 14.35 0.638530E+09 886.86 30-OCT-13:20 23.30 11.27
November 0.882879E+10 18616.62 11-NOV-13:02 18.30 8.11 0.624745E+09 874.35 09-NOV-14:09 18.30 8.11
December 0.683300E+10 15573.05 17-DEC-12:53 12.80 3.46 0.602069E+09 846.37 01-DEC-14:39 12.80 3.46
                     
Annual Sum or Average 0.110681E+12         0.759872E+10        
Minimum of Months 0.627722E+10 13278.74   12.80 3.46 0.568262E+09 845.65   12.80 3.46
Maximum of Months 0.126494E+11 19125.15   34.40 19.90 0.691912E+09 886.86   32.20 19.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.380885E+10 7005.85 02-JAN-15:30 17.80 9.19 0.392673E+09 544.94 11-JAN-14:09 15.18 6.16
February 0.450090E+10 16464.83 19-FEB-15:23 22.80 8.58 0.366891E+09 544.98 13-FEB-10:09 22.80 8.58
March 0.763467E+10 17663.12 26-MAR-16:32 22.60 9.13 0.445101E+09 544.95 06-MAR-10:09 22.60 9.13
April 0.112908E+11 20902.46 30-APR-16:31 30.20 12.69 0.396902E+09 544.98 24-APR-13:39 30.20 12.69
May 0.988888E+10 21474.65 29-MAY-15:31 32.93 16.65 0.429344E+09 544.97 05-MAY-13:00 32.93 16.65
June 0.127609E+11 20507.62 25-JUN-16:22 31.40 16.79 0.428149E+09 544.97 30-JUN-09:39 25.17 17.65
July 0.136645E+11 20701.02 09-JUL-16:42 32.88 19.22 0.398482E+09 544.96 03-JUL-09:00 32.88 19.22
August 0.149525E+11 21300.80 13-AUG-16:21 31.40 18.54 0.446894E+09 544.98 17-AUG-13:20 24.80 17.12
September 0.932598E+10 21405.78 10-SEP-15:41 31.10 16.81 0.396567E+09 544.97 25-SEP-13:50 24.90 13.77
October 0.830732E+10 20807.93 01-OCT-14:42 32.70 15.84 0.412227E+09 544.98 17-OCT-09:00 21.10 16.29
November 0.650824E+10 16821.08 19-NOV-15:43 18.22 6.60 0.406936E+09 544.95 30-NOV-14:00 17.80 10.67
December 0.552748E+10 11434.12 11-DEC-05:02 11.02 5.91 0.395599E+09 544.95 11-DEC-14:09 13.90 7.45
                     
Annual Sum or Average 0.108171E+12         0.491577E+10        
Minimum of Months 0.380885E+10 7005.85   11.02 5.91 0.366891E+09 544.94   13.90 6.16
Maximum of Months 0.149525E+11 21474.65   32.93 19.22 0.446894E+09 544.98   32.93 19.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.170083E+10 2491.49 12-JAN-15:10 18.90 10.04 0.505468E+09 784.41 13-JAN-14:00 18.30 8.81
February 0.192801E+10 2649.95 22-FEB-13:40 21.33 7.78 0.486628E+09 845.58 23-FEB-14:00 21.10 7.10
March 0.282805E+10 3833.86 22-MAR-14:40 24.07 8.96 0.623209E+09 845.60 09-MAR-14:09 24.07 8.96
April 0.436867E+10 8870.73 20-APR-05:02 20.10 9.51 0.598786E+09 845.63 27-APR-09:09 20.87 11.97
May 0.702695E+10 10690.03 23-MAY-05:03 20.10 14.79 0.662940E+09 845.63 15-MAY-09:39 20.10 14.79
June 0.929288E+10 11496.68 15-JUN-05:02 27.02 11.23 0.662969E+09 845.63 27-JUN-09:09 25.10 15.77
July 0.880008E+10 14168.37 04-JUL-16:01 33.18 18.80 0.616318E+09 845.63 24-JUL-09:20 27.07 18.10
August 0.799473E+10 12999.85 07-AUG-05:03 25.92 16.23 0.690677E+09 845.63 11-AUG-09:09 27.57 18.90
September 0.599066E+10 10428.71 14-SEP-05:02 19.32 18.21 0.610994E+09 845.63 06-SEP-09:20 19.32 18.21
October 0.406228E+10 9453.43 05-OCT-05:03 21.32 16.10 0.618590E+09 845.64 17-OCT-09:00 21.10 16.29
November 0.240480E+10 3149.37 09-NOV-16:00 23.30 13.01 0.543896E+09 845.60 09-NOV-14:39 23.30 13.01
December 0.143501E+10 2119.21 07-DEC-14:20 15.77 6.80 0.477922E+09 751.07 08-DEC-14:00 17.20 7.54
                     
Annual Sum or Average 0.578329E+11         0.709840E+10        
Minimum of Months 0.143501E+10 2119.21   15.77 6.80 0.477922E+09 751.07   17.20 7.10
Maximum of Months 0.929288E+10 14168.37   33.18 18.80 0.690677E+09 845.64   27.57 18.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.178068E+10 2876.06 04-JAN-09:50 9.32 3.11 0.258664E+09 521.18 31-JAN-09:20 10.97 4.21
February 0.214260E+10 4642.07 21-FEB-10:00 16.70 6.62 0.251424E+09 521.20 22-FEB-11:20 17.03 6.18
March 0.346024E+10 6193.69 07-MAR-09:30 15.55 7.24 0.311953E+09 521.21 22-MAR-12:20 24.60 9.35
April 0.546616E+10 16110.23 30-APR-09:02 20.37 12.82 0.289499E+09 521.31 27-APR-08:00 20.37 12.82
May 0.764833E+10 16165.86 29-MAY-09:32 24.07 16.06 0.315441E+09 523.23 30-MAY-07:19 25.97 12.58
June 0.910658E+10 15962.88 11-JUN-09:02 26.28 11.67 0.314621E+09 526.41 07-JUN-07:19 26.28 11.67
July 0.841657E+10 16091.23 02-JUL-08:12 27.77 19.28 0.293594E+09 526.54 03-JUL-07:19 28.17 16.54
August 0.803837E+10 16149.03 06-AUG-10:12 31.13 17.83 0.327500E+09 521.98 04-AUG-10:30 31.13 17.83
September 0.665731E+10 16164.00 04-SEP-09:02 23.77 18.19 0.291199E+09 521.39 15-SEP-08:00 25.60 19.42
October 0.436002E+10 8766.12 05-OCT-08:30 23.90 17.39 0.296943E+09 521.24 17-OCT-10:09 21.47 16.47
November 0.255534E+10 6514.21 10-NOV-08:50 18.22 11.69 0.275116E+09 521.21 09-NOV-11:20 18.22 11.69
December 0.158449E+10 1999.83 07-DEC-13:50 15.40 6.66 0.242651E+09 520.70 01-DEC-09:00 15.40 6.66
                     
Annual Sum or Average 0.612167E+11         0.346861E+10        
Minimum of Months 0.158449E+10 1999.83   9.32 3.11 0.242651E+09 520.70   10.97 4.21
Maximum of Months 0.910658E+10 16165.86   31.13 19.28 0.327500E+09 526.54   31.13 19.42



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.601463E+10 15419.25 01-JAN-12:43 14.90 8.94 0.610896E+09 860.20 12-JAN-14:39 18.70 9.92
February 0.562698E+10 17304.53 20-FEB-14:22 22.75 8.67 0.558872E+09 846.57 23-FEB-14:00 21.10 7.10
March 0.639390E+10 12613.21 19-MAR-13:43 23.12 8.89 0.671385E+09 846.25 22-MAR-13:00 24.40 9.14
April 0.671112E+10 16180.39 30-APR-13:02 29.40 12.33 0.607159E+09 845.93 03-APR-13:00 29.40 12.33
May 0.777199E+10 11879.95 01-MAY-05:02 14.40 5.02 0.663310E+09 845.66 05-MAY-13:00 25.00 11.34
June 0.913648E+10 12670.42 15-JUN-05:02 27.02 11.23 0.662855E+09 845.65 12-JUN-09:00 27.02 11.23
July 0.901240E+10 15948.94 04-JUL-16:01 33.18 18.80 0.616466E+09 845.98 31-JUL-13:00 32.20 19.72
August 0.993718E+10 16148.61 06-AUG-14:51 36.10 18.55 0.691715E+09 846.47 29-AUG-13:00 31.70 19.58
September 0.103961E+11 17085.21 17-SEP-12:32 31.50 15.75 0.614805E+09 880.28 29-SEP-13:50 28.22 14.76
October 0.983648E+10 17709.30 22-OCT-12:42 25.32 14.38 0.637953E+09 911.71 30-OCT-13:30 23.30 11.23
November 0.784692E+10 17621.04 11-NOV-12:52 18.30 8.13 0.616035E+09 902.71 09-NOV-14:09 18.30 8.13
December 0.557903E+10 16496.86 17-DEC-14:02 15.10 4.36 0.587240E+09 845.85 01-DEC-14:39 15.10 4.36
                     
Annual Sum or Average 0.942632E+11         0.753869E+10        
Minimum of Months 0.557903E+10 11879.95   14.40 4.36 0.558872E+09 845.65   15.10 4.36
Maximum of Months 0.103961E+11 17709.30   36.10 18.80 0.691715E+09 911.71   32.20 19.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.213451E+10 4709.38 12-JAN-15:30 18.90 10.10 0.348994E+09 544.93 13-JAN-14:00 18.30 8.81
February 0.234443E+10 6811.38 21-FEB-16:50 22.30 7.87 0.329031E+09 544.93 22-FEB-14:00 22.20 8.00
March 0.381123E+10 8407.45 21-MAR-16:00 25.00 9.53 0.416271E+09 544.94 09-MAR-14:09 25.00 9.53
April 0.567865E+10 17270.99 30-APR-16:21 30.30 12.75 0.390374E+09 544.96 24-APR-13:20 30.30 12.75
May 0.781022E+10 18042.14 29-MAY-15:31 32.93 16.65 0.428365E+09 544.96 05-MAY-13:00 32.93 16.65
June 0.934355E+10 17955.67 11-JUN-17:41 31.78 14.70 0.427927E+09 544.96 30-JUN-09:39 25.17 17.65
July 0.877703E+10 18075.95 04-JUL-16:01 33.18 18.80 0.397972E+09 544.96 24-JUL-09:20 27.07 18.10
August 0.853735E+10 17628.59 06-AUG-16:51 36.10 18.82 0.446181E+09 544.97 29-AUG-13:00 31.70 19.58
September 0.703476E+10 17775.62 10-SEP-15:41 31.10 16.81 0.395497E+09 544.96 25-SEP-13:39 24.80 13.70
October 0.503419E+10 15139.38 22-OCT-15:22 26.95 14.70 0.404366E+09 544.97 17-OCT-09:00 26.95 14.70
November 0.312304E+10 7558.71 09-NOV-15:30 23.30 12.82 0.369747E+09 544.93 02-NOV-13:00 23.30 12.82
December 0.194462E+10 4058.82 15-DEC-16:00 15.60 6.14 0.333483E+09 544.93 01-DEC-14:00 15.60 6.14
                     
Annual Sum or Average 0.655736E+11         0.468821E+10        
Minimum of Months 0.194462E+10 4058.82   15.60 6.14 0.329031E+09 544.93   15.60 6.14
Maximum of Months 0.934355E+10 18075.95   36.10 18.82 0.446181E+09 544.97   32.93 19.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.773195E+09 2048.76 12-JAN-14:30 18.60 9.87 0.475839E+09 726.90 13-JAN-14:00 18.30 8.81
February 0.116384E+10 2231.42 07-FEB-14:20 20.00 9.36 0.453071E+09 822.16 23-FEB-14:00 21.10 7.10
March 0.221681E+10 3808.45 16-MAR-15:40 22.40 8.49 0.584100E+09 845.60 09-MAR-14:09 22.40 8.49
April 0.422784E+10 7774.72 20-APR-05:02 20.10 9.51 0.584580E+09 845.63 03-APR-13:09 20.10 9.51
May 0.735187E+10 12563.09 31-MAY-05:02 24.22 11.57 0.660976E+09 845.63 15-MAY-09:00 24.22 11.57
June 0.103262E+11 16513.35 18-JUN-15:32 37.03 16.78 0.663209E+09 845.63 27-JUN-09:39 25.40 15.72
July 0.986711E+10 17270.07 04-JUL-16:01 33.18 18.80 0.616842E+09 846.26 03-JUL-13:20 33.18 18.80
August 0.869614E+10 16607.03 06-AUG-16:41 36.10 18.73 0.690377E+09 845.63 11-AUG-09:09 27.57 18.90
September 0.619490E+10 8608.07 14-SEP-05:02 19.32 18.21 0.608216E+09 845.63 06-SEP-09:20 19.32 18.21
October 0.376755E+10 7497.44 05-OCT-05:03 21.32 16.10 0.597537E+09 845.63 02-OCT-09:09 21.32 16.10
November 0.159050E+10 2977.79 09-NOV-16:00 23.30 13.01 0.507362E+09 840.06 09-NOV-14:00 23.30 13.01
December 0.517383E+09 1663.39 01-DEC-15:00 13.30 5.89 0.453474E+09 696.20 01-DEC-14:00 13.30 5.89
                     
Annual Sum or Average 0.566933E+11         0.689558E+10        
Minimum of Months 0.517383E+09 1663.39   13.30 5.89 0.453071E+09 696.20   13.30 5.89
Maximum of Months 0.103262E+11 17270.07   37.03 18.80 0.690377E+09 846.26   33.18 18.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.118637E+10 1920.51 12-JAN-14:30 18.60 9.87 0.323996E+09 520.46 04-JAN-10:30 18.60 9.87
February 0.160901E+10 3084.57 21-FEB-10:30 18.35 7.04 0.320951E+09 544.94 07-FEB-10:09 18.35 7.04
March 0.284516E+10 5377.92 16-MAR-10:00 18.90 7.68 0.414386E+09 544.95 17-MAR-09:00 8.30 1.95
April 0.535738E+10 15794.16 30-APR-08:62 18.58 12.41 0.392210E+09 544.98 19-APR-09:09 18.58 12.41
May 0.805153E+10 15587.18 29-MAY-11:02 26.97 16.73 0.428343E+09 545.56 17-MAY-09:50 26.97 16.73
June 0.100809E+11 15867.62 18-JUN-09:32 30.57 16.80 0.427864E+09 545.44 09-JUN-09:00 30.57 16.80
July 0.943262E+10 17323.16 02-JUL-09:22 30.00 19.75 0.398053E+09 545.64 28-JUL-09:00 30.60 19.45
August 0.880099E+10 17139.43 06-AUG-09:22 29.45 17.83 0.445330E+09 545.47 09-AUG-09:39 29.43 19.02
September 0.697980E+10 15862.86 04-SEP-07:53 21.10 17.67 0.395145E+09 545.55 18-SEP-09:00 27.20 17.67
October 0.412538E+10 8480.59 05-OCT-08:40 24.27 17.57 0.398927E+09 544.98 17-OCT-09:00 21.10 16.29
November 0.192745E+10 5725.27 10-NOV-09:20 18.67 11.91 0.355890E+09 544.95 09-NOV-10:00 18.67 11.91
December 0.950533E+09 1570.37 01-DEC-10:20 12.77 4.87 0.302457E+09 480.81 01-DEC-10:30 13.05 5.08
                     
Annual Sum or Average 0.613471E+11         0.460355E+10        
Minimum of Months 0.950533E+09 1570.37   12.77 4.87 0.302457E+09 480.81   8.30 1.95
Maximum of Months 0.100809E+11 17323.16   30.57 19.75 0.445330E+09 545.64   30.60 19.45



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.421531E+10 12762.26 12-JAN-14:30 18.60 9.87 0.583731E+09 845.63 03-JAN-14:09 18.60 9.87
February 0.417455E+10 18382.61 20-FEB-13:13 21.47 8.42 0.535222E+09 846.09 07-FEB-14:50 21.47 8.42
March 0.526912E+10 11725.15 16-MAR-14:10 22.80 9.24 0.646592E+09 845.84 16-MAR-13:00 22.80 9.24
April 0.653073E+10 16907.70 16-APR-15:32 29.80 11.65 0.598013E+09 846.08 21-APR-13:39 32.03 15.02
May 0.814587E+10 13721.60 31-MAY-05:02 24.22 11.57 0.661229E+09 845.65 15-MAY-09:00 24.22 11.57
June 0.101732E+11 16996.95 18-JUN-12:53 35.60 15.66 0.662999E+09 845.65 28-JUN-13:09 25.87 17.21
July 0.101272E+11 18846.28 04-JUL-16:01 33.18 18.80 0.616847E+09 846.17 31-JUL-13:00 32.20 19.72
August 0.107926E+11 19009.77 06-AUG-14:02 35.18 17.96 0.691377E+09 846.73 29-AUG-13:00 31.70 19.58
September 0.107779E+11 19209.64 04-SEP-12:32 29.83 18.72 0.613582E+09 857.44 29-SEP-13:00 28.30 14.82
October 0.940024E+10 20657.82 01-OCT-13:32 31.83 15.11 0.627705E+09 868.68 03-OCT-13:39 32.07 19.44
November 0.628216E+10 18991.06 11-NOV-12:32 17.93 8.04 0.592212E+09 862.52 09-NOV-14:09 17.93 8.04
December 0.374808E+10 10440.49 07-DEC-14:30 15.85 6.83 0.558300E+09 845.64 01-DEC-14:09 15.85 6.83
                     
Annual Sum or Average 0.896369E+11         0.738781E+10        
Minimum of Months 0.374808E+10 10440.49   15.85 6.83 0.535222E+09 845.63   15.85 6.83
Maximum of Months 0.107926E+11 20657.82   35.60 18.80 0.691377E+09 868.68   32.20 19.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.148580E+10 4128.43 12-JAN-15:30 18.90 10.10 0.329775E+09 544.88 12-JAN-14:00 18.90 10.10
February 0.182825E+10 6367.73 21-FEB-16:50 22.30 7.87 0.309247E+09 544.93 22-FEB-14:00 22.20 8.00
March 0.336078E+10 9401.81 26-MAR-17:02 22.52 9.15 0.392677E+09 544.94 09-MAR-14:09 22.52 9.15
April 0.566920E+10 19109.07 16-APR-15:32 29.80 11.65 0.382541E+09 544.96 03-APR-13:09 29.80 11.65
May 0.815641E+10 18929.32 29-MAY-16:22 33.05 16.61 0.426683E+09 544.96 15-MAY-09:00 33.05 16.61
June 0.102248E+11 18972.93 25-JUN-17:02 31.60 16.78 0.427887E+09 544.96 28-JUN-13:09 25.87 17.21
July 0.973203E+10 20384.66 04-JUL-16:01 33.18 18.80 0.397989E+09 544.95 11-JUL-09:09 29.18 18.50
August 0.921999E+10 19422.53 06-AUG-16:41 36.10 18.73 0.445686E+09 544.96 29-AUG-13:00 31.70 19.58
September 0.732209E+10 18283.15 17-SEP-15:32 32.80 15.98 0.394031E+09 544.96 11-SEP-09:50 32.80 15.98
October 0.487837E+10 18594.99 01-OCT-14:52 32.80 15.90 0.392956E+09 544.96 02-OCT-09:09 22.35 16.60
November 0.254709E+10 7469.31 09-NOV-15:40 23.30 12.89 0.348545E+09 544.93 09-NOV-14:09 23.30 12.89
December 0.128658E+10 3065.79 15-DEC-16:10 15.50 6.10 0.314168E+09 540.27 07-DEC-14:00 15.50 6.10
                     
Annual Sum or Average 0.657114E+11         0.456218E+10        
Minimum of Months 0.128658E+10 3065.79   15.50 6.10 0.309247E+09 540.27   15.50 6.10
Maximum of Months 0.102248E+11 20384.66   36.10 18.80 0.445686E+09 544.96   33.05 19.58



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.171237E+10 5469.12 02-JAN-06:15 -0.2 -1.0 0.00 0.00 01-JAN-00:10 -0.2 -1.0
February 0.218688E+10 5021.21 21-FEB-06:15 5.20 0.40 0.00 0.00 01-FEB-00:10 5.20 0.40
March 0.379979E+10 4586.56 14-MAR-05:15 3.13 0.63 0.00 0.00 01-MAR-00:10 3.13 0.63
April 0.594594E+10 6491.43 03-APR-05:15 17.77 7.96 0.00 0.00 01-APR-00:10 17.77 7.96
May 0.731366E+10 8583.08 30-MAY-05:10 25.00 11.62 0.00 0.00 01-MAY-00:10 25.00 11.62
June 0.925807E+10 9063.52 19-JUN-05:08 22.80 15.92 0.00 0.00 01-JUN-00:10 22.80 15.92
July 0.952385E+10 12698.17 31-JUL-05:15 21.70 17.81 0.00 0.00 01-JUL-00:10 21.70 17.81
August 0.994085E+10 14035.15 07-AUG-05:15 25.73 16.21 0.00 0.00 01-AUG-00:10 25.73 16.21
September 0.756391E+10 12408.56 05-SEP-05:15 16.30 15.51 0.00 0.00 01-SEP-00:10 16.30 15.51
October 0.602720E+10 8795.80 10-OCT-05:15 12.97 8.53 0.00 0.00 01-OCT-00:10 12.97 8.53
November 0.372269E+10 6983.34 13-NOV-06:15 2.40 0.12 0.00 0.00 01-NOV-00:10 2.40 0.12
December 0.213881E+10 4552.42 11-DEC-06:15 10.77 5.99 0.00 0.00 01-DEC-00:10 10.77 5.99
                     
Annual Sum or Average 0.691340E+11         0.00        
Minimum of Months 0.171237E+10 4552.42   -0.2 -1.0 0.00 0.00   -0.2 -1.0
Maximum of Months 0.994085E+10 14035.15   25.73 17.81 0.00 0.00   25.73 17.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.663822E+09 4509.08 28-JAN-06:01 -3.3 -6.4 0.00 0.00 01-JAN-00:10 -3.3 -6.4
February 0.895925E+09 4778.94 02-FEB-06:01 -3.5 -5.9 0.00 0.00 01-FEB-00:10 -3.5 -5.9
March 0.167303E+10 4986.38 02-MAR-06:01 -3.5 -6.2 0.00 0.00 01-MAR-00:10 -3.5 -6.2
April 0.362155E+10 4749.87 21-APR-15:50 31.28 14.93 0.00 0.00 01-APR-00:10 31.28 14.93
May 0.587855E+10 6367.77 30-MAY-16:00 33.90 17.46 0.00 0.00 01-MAY-00:10 33.90 17.46
June 0.758080E+10 7719.60 02-JUN-05:02 19.08 9.94 0.00 0.00 01-JUN-00:10 19.08 9.94
July 0.722318E+10 7327.87 14-JUL-05:03 21.70 17.80 0.00 0.00 01-JUL-00:10 21.70 17.80
August 0.712423E+10 6704.89 09-AUG-05:03 23.12 18.31 0.00 0.00 01-AUG-00:10 23.12 18.31
September 0.590138E+10 7652.33 05-SEP-05:15 16.30 15.51 0.00 0.00 01-SEP-00:10 16.30 15.51
October 0.373216E+10 5591.05 05-OCT-05:15 20.93 15.98 0.00 0.00 01-OCT-00:10 20.93 15.98
November 0.153738E+10 3919.90 28-NOV-06:01 1.02 -0.5 0.00 0.00 01-NOV-00:10 1.02 -0.5
December 0.613261E+09 4422.82 19-DEC-06:01 -2.8 -6.7 0.00 0.00 01-DEC-00:10 -2.8 -6.7
                     
Annual Sum or Average 0.464453E+11         0.00        
Minimum of Months 0.613261E+09 3919.90   -3.5 -6.7 0.00 0.00   -3.5 -6.7
Maximum of Months 0.758080E+10 7719.60   33.90 18.31 0.00 0.00   33.90 18.31



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.188395E+09 2760.93 01-JAN-14:43 16.02 9.44 0.00 0.00 01-JAN-00:10 16.02 9.44
February 0.809485E+09 5441.27 07-FEB-14:40 20.00 9.31 0.00 0.00 01-FEB-00:10 20.00 9.31
March 0.243138E+10 9033.83 16-MAR-15:10 22.70 8.66 0.00 0.00 01-MAR-00:10 22.70 8.66
April 0.653862E+10 15292.02 28-APR-14:30 28.90 14.03 0.00 0.00 01-APR-00:10 28.90 14.03
May 0.110000E+11 18497.02 30-MAY-14:20 34.40 17.58 0.00 0.00 01-MAY-00:10 34.40 17.58
June 0.152465E+11 20124.53 15-JUN-14:30 38.05 15.77 0.00 0.00 01-JUN-00:10 38.05 15.77
July 0.143565E+11 20660.78 03-JUL-12:50 36.52 18.58 0.00 0.00 01-JUL-00:10 36.52 18.58
August 0.131532E+11 19225.22 07-AUG-14:50 35.00 18.73 0.00 0.00 01-AUG-00:10 35.00 18.73
September 0.100355E+11 16048.63 15-SEP-14:00 32.20 17.96 0.00 0.00 01-SEP-00:10 32.20 17.96
October 0.506280E+10 13837.79 03-OCT-14:20 32.43 19.47 0.00 0.00 01-OCT-00:10 32.43 19.47
November 0.128494E+10 6854.05 09-NOV-15:10 23.30 12.70 0.00 0.00 01-NOV-00:10 23.30 12.70
December 98642343.20 1899.50 09-DEC-13:30 17.50 7.28 0.00 0.00 01-DEC-00:10 17.50 7.28
                     
Annual Sum or Average 0.802059E+11         0.00        
Minimum of Months 98642343.20 1899.50   16.02 7.28 0.00 0.00   16.02 7.28
Maximum of Months 0.152465E+11 20660.78   38.05 19.47 0.00 0.00   38.05 19.47



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.354975E+10 1961.02 01-JAN-16:45 14.60 8.58 95231194.56 126.83 17-JAN-10:00 8.90 5.56
February 0.807332E+10 3982.11 20-FEB-17:30 21.65 8.03 86397379.77 126.84 13-FEB-14:00 21.65 8.03
March 0.142998E+11 7120.68 31-MAR-24:00 11.20 2.36 0.103236E+09 126.82 13-MAR-09:09 11.20 2.36
April 0.188718E+11 7794.88 30-APR-19:03 27.62 11.57 91651564.80 129.35 21-APR-13:00 27.62 11.57
May 0.452416E+10 3464.77 31-MAY-24:00 25.20 11.70 99236980.43 126.85 23-MAY-09:50 25.20 11.70
June 0.932267E+10 5329.71 30-JUN-23:45 27.77 17.13 98963356.78 126.85 29-JUN-09:39 27.77 17.13
July 0.147066E+11 7276.26 31-JUL-23:53 27.50 18.10 91890353.64 126.85 19-JUL-09:09 27.50 18.10
August 0.196779E+11 7740.74 27-AUG-19:42 28.95 15.04 0.103687E+09 131.52 07-AUG-13:00 28.95 15.04
September 0.445897E+10 3494.76 30-SEP-24:00 16.10 8.62 91614524.99 126.85 01-SEP-13:00 16.10 8.62
October 0.952959E+10 5296.49 31-OCT-24:00 10.60 4.98 95238498.42 126.86 04-OCT-09:00 10.60 4.98
November 0.138812E+11 5948.04 12-NOV-16:50 14.50 6.90 94302006.12 126.84 01-NOV-13:00 14.50 6.90
December 0.191675E+11 7646.95 18-DEC-16:40 9.27 0.10 91880991.11 126.82 14-DEC-14:00 9.27 0.10
                     
Annual Sum or Average 0.140063E+12         0.114333E+10        
Minimum of Months 0.354975E+10 1961.02   9.27 0.10 86397379.77 126.82   8.90 0.10
Maximum of Months 0.196779E+11 7794.88   28.95 18.10 0.103687E+09 131.52   28.95 18.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.196916E+10 1674.38 19-JAN-17:00 12.80 6.10 95231034.19 126.83 02-JAN-14:50 12.80 6.10
February 0.665840E+10 3593.75 21-FEB-17:00 22.20 7.81 86397341.57 126.84 13-FEB-14:00 22.20 7.81
March 0.128788E+11 6608.25 31-MAR-24:00 11.20 2.36 0.103236E+09 126.82 13-MAR-09:09 11.20 2.36
April 0.178323E+11 7386.65 30-APR-18:43 28.17 11.84 91661989.79 130.32 21-APR-13:00 28.17 11.84
May 0.414453E+10 3401.19 31-MAY-24:00 25.20 11.70 99236246.14 126.84 23-MAY-13:00 25.20 11.70
June 0.886174E+10 5181.51 30-JUN-23:53 27.70 17.05 98963051.43 126.85 29-JUN-09:39 27.70 17.05
July 0.139858E+11 6988.19 31-JUL-23:53 27.50 18.10 91889723.53 126.85 19-JUL-09:09 27.50 18.10
August 0.187319E+11 7329.35 31-AUG-17:50 27.98 16.89 0.103826E+09 132.50 04-AUG-13:00 27.98 16.89
September 0.401579E+10 3261.65 30-SEP-24:00 16.10 8.62 91611891.24 126.85 22-SEP-13:00 16.10 8.62
October 0.859516E+10 4869.65 31-OCT-24:00 10.60 4.98 95237960.95 126.85 04-OCT-09:00 10.60 4.98
November 0.122043E+11 5529.44 09-NOV-16:50 22.88 12.85 94301898.10 126.83 01-NOV-13:00 22.88 12.85
December 0.166033E+11 7124.72 15-DEC-16:50 15.10 5.92 91881013.65 126.82 14-DEC-14:00 15.10 5.92
                     
Annual Sum or Average 0.126481E+12         0.114347E+10        
Minimum of Months 0.196916E+10 1674.38   10.60 2.36 86397341.57 126.82   10.60 2.36
Maximum of Months 0.187319E+11 7386.65   28.17 18.10 0.103826E+09 132.50   28.17 18.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.662656E+09 1580.88 12-JAN-16:50 17.98 9.87 94718280.54 128.79 30-JAN-10:50 9.03 2.61
February 0.527906E+10 3562.25 21-FEB-17:00 22.20 7.81 86397315.43 126.84 13-FEB-14:00 22.20 7.81
March 0.118720E+11 6297.68 31-MAR-23:20 11.33 2.45 0.103236E+09 126.82 13-MAR-09:09 11.33 2.45
April 0.175655E+11 7537.34 30-APR-19:03 27.62 11.57 91637982.60 129.54 21-APR-13:00 27.62 11.57
May 0.413708E+10 3400.79 31-MAY-24:00 25.20 11.70 99236596.39 126.84 24-MAY-13:00 25.20 11.70
June 0.898395E+10 5192.68 30-JUN-23:45 27.77 17.13 98963299.43 126.85 29-JUN-09:39 27.77 17.13
July 0.141399E+11 7010.65 31-JUL-23:53 27.50 18.10 91890258.54 126.85 19-JUL-09:09 27.50 18.10
August 0.188074E+11 7517.73 27-AUG-19:53 28.30 14.84 0.103748E+09 132.38 04-AUG-13:00 28.30 14.84
September 0.399241E+10 3117.01 30-SEP-23:30 16.40 9.13 91612941.54 126.85 05-SEP-13:00 16.40 9.13
October 0.809484E+10 4544.21 31-OCT-23:30 10.60 4.77 95238047.57 126.85 04-OCT-09:00 10.60 4.77
November 0.107774E+11 5545.72 09-NOV-16:50 22.88 12.85 94301946.08 126.83 03-NOV-09:00 22.88 12.85
December 0.144912E+11 6970.41 15-DEC-16:50 15.10 5.92 91881048.57 126.82 14-DEC-14:00 15.10 5.92
                     
Annual Sum or Average 0.118803E+12         0.114286E+10        
Minimum of Months 0.662656E+09 1580.88   10.60 2.45 86397315.43 126.82   9.03 2.45
Maximum of Months 0.188074E+11 7537.34   28.30 18.10 0.103748E+09 132.38   28.30 18.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.237057E+12 91307.30 02-JAN-17:00 16.70 8.66 0.206144E+10 2745.29 13-JAN-10:39 12.07 5.50
February 0.432999E+12 181865.75 21-FEB-17:00 22.20 7.81 0.187022E+10 2745.29 09-FEB-14:09 22.20 7.81
March 0.724353E+12 356949.97 31-MAR-24:00 11.20 2.36 0.223475E+10 2745.29 21-MAR-13:09 11.20 2.36
April 0.938483E+12 364885.51 17-APR-16:00 17.20 10.20 0.198297E+10 2745.29 05-APR-09:50 17.20 10.20
May 0.238393E+12 174929.66 31-MAY-24:00 25.20 11.70 0.214810E+10 2745.29 22-MAY-13:20 25.20 11.70
June 0.467067E+12 266467.37 30-JUN-23:57 27.70 17.05 0.214213E+10 2745.29 01-JUN-13:00 27.70 17.05
July 0.730046E+12 359385.01 31-JUL-23:57 27.50 18.10 0.198894E+10 2745.29 28-JUL-13:50 27.50 18.10
August 0.976622E+12 367614.02 07-AUG-16:00 37.20 17.89 0.223475E+10 2745.29 01-AUG-09:30 37.20 17.89
September 0.236147E+12 176624.28 30-SEP-24:00 16.10 8.62 0.198297E+10 2745.29 05-SEP-13:09 16.10 8.62
October 0.487350E+12 268337.36 31-OCT-24:00 10.60 4.98 0.206144E+10 2745.29 05-OCT-09:39 10.60 4.98
November 0.707568E+12 275713.80 13-NOV-17:00 18.30 9.24 0.204131E+10 2745.29 02-NOV-09:09 18.30 9.24
December 0.974671E+12 366694.53 18-DEC-16:55 8.90 -0.7 0.198894E+10 2745.29 08-DEC-10:09 8.90 -0.7
                     
Annual Sum or Average 0.715075E+13         0.247380E+11        
Minimum of Months 0.236147E+12 91307.30   8.90 -0.7 0.187022E+10 2745.29   8.90 -0.7
Maximum of Months 0.976622E+12 367614.02   37.20 18.10 0.223475E+10 2745.29   37.20 18.10



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.228988E+09 11148.99 14-JAN-05:15 8.90
February 0.160737E+09 11243.22 13-FEB-04:15 10.57
March 0.208161E+09 11152.74 23-MAR-04:15 8.13
April 0.341450E+09 13638.38 29-APR-16:03 31.02
May 0.452479E+09 15098.86 20-MAY-16:02 32.20
June 0.442138E+09 18185.92 17-JUN-16:13 35.77
July 0.561764E+09 20137.83 01-JUL-16:13 37.97
August 0.566267E+09 16558.70 26-AUG-15:02 34.32
September 0.603348E+09 14787.65 02-SEP-15:02 32.30
October 0.443009E+09 12547.46 02-OCT-00:23 27.80
November 0.440037E+09 12836.24 08-NOV-04:53 15.00
December 0.434311E+09 11325.68 26-DEC-04:55 -0.6
         
Annual Sum or Average 0.488269E+10      
Minimum of Months 0.160737E+09 11148.99   -0.6
Maximum of Months 0.603348E+09 20137.83   37.97



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 6.70
February 0.00 0.00 01-FEB-00:10 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:10 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 6.70
February 0.00 0.00 01-FEB-00:10 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:10 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.568690E+09 64659.20 17-JAN-05:01 5.40
February 58214991.38 58036.08 03-FEB-06:01 -3.7
March 7556192.59 56962.76 02-MAR-06:01 -3.5
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.240536E+09 62549.03 27-NOV-05:01 3.30
December 0.984199E+09 65373.20 04-DEC-05:01 -0.7
         
Annual Sum or Average 0.185920E+10      
Minimum of Months 0.00 0.00   -3.7
Maximum of Months 0.984199E+09 65373.20   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 6.70
February 0.00 0.00 01-FEB-00:10 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:10 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 6.70
February 0.00 0.00 01-FEB-00:10 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:10 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 6.70
February 0.00 0.00 01-FEB-00:10 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 746460.96 4701.69 27-DEC-06:01 -3.5
         
Annual Sum or Average 746460.96      
Minimum of Months 0.00 0.00   -3.5
Maximum of Months 746460.96 4701.69   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 6.70
February 0.00 0.00 01-FEB-00:10 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:10 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.297757E+09 10559.40 28-JAN-05:01 -2.9
February 0.133732E+09 10435.58 03-FEB-05:01 -3.8
March 27251021.63 10260.28 02-MAR-05:06 -3.9
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 61916078.52 10484.20 28-NOV-05:01 -0.3
December 0.460299E+09 10724.66 28-DEC-05:01 -3.0
         
Annual Sum or Average 0.980955E+09      
Minimum of Months 0.00 0.00   -3.9
Maximum of Months 0.460299E+09 10724.66   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.120156E+09 10197.88 28-JAN-05:01 -2.9
February 43365175.46 10066.18 02-FEB-06:01 -3.5
March 11369268.03 10083.90 02-MAR-06:01 -3.5
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 23189355.92 10368.01 28-NOV-05:01 -0.3
December 0.196226E+09 10702.68 27-DEC-05:01 -3.8
         
Annual Sum or Average 0.394306E+09      
Minimum of Months 0.00 0.00   -3.8
Maximum of Months 0.196226E+09 10702.68   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 17184430.73 11013.50 28-JAN-06:01 -3.3
February 12775616.53 11061.86 02-FEB-06:01 -3.5
March 4076580.72 10974.38 02-MAR-06:01 -3.5
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 10585409.03 11180.32 28-NOV-06:01 1.02
December 75958990.18 11616.60 27-DEC-05:01 -3.8
         
Annual Sum or Average 0.120581E+09      
Minimum of Months 0.00 0.00   -3.8
Maximum of Months 75958990.18 11616.60   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 42361321.85 9786.67 28-JAN-06:01 -3.3
February 20725909.97 9776.79 02-FEB-06:01 -3.5
March 3715076.68 9730.10 02-MAR-06:01 -3.5
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 7276133.94 9679.25 28-NOV-06:01 1.02
December 77355847.59 9905.00 27-DEC-06:01 -3.5
         
Annual Sum or Average 0.151434E+09      
Minimum of Months 0.00 0.00   -3.5
Maximum of Months 77355847.59 9905.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.218510E+10 13876.42 09-JAN-04:02 0.55
February 0.119341E+10 13137.95 10-FEB-05:01 -2.8
March 0.501404E+09 12951.60 02-MAR-05:01 -3.9
April 13222378.91 9217.20 12-APR-05:03 4.22
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 4351277.45 5622.70 25-OCT-05:02 7.12
November 0.939130E+09 14103.67 27-NOV-04:01 3.80
December 0.286263E+10 14634.81 26-DEC-04:01 -0.1
         
Annual Sum or Average 0.769925E+10      
Minimum of Months 0.00 0.00   -3.9
Maximum of Months 0.286263E+10 14634.81   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.912943E+09 12382.63 09-JAN-04:02 0.55
February 0.412231E+09 11920.71 10-FEB-05:01 -2.8
March 0.171931E+09 11810.88 02-MAR-05:01 -3.9
April 1950058.39 3057.04 11-APR-05:02 4.90
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 2262635.89 3787.59 25-OCT-05:02 7.12
November 0.382575E+09 12755.55 27-NOV-04:01 3.80
December 0.120371E+10 13233.89 26-DEC-04:01 -0.1
         
Annual Sum or Average 0.308760E+10      
Minimum of Months 0.00 0.00   -3.9
Maximum of Months 0.120371E+10 13233.89   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.718449E+09 14109.00 17-JAN-05:01 5.40
February 0.397240E+09 13810.79 03-FEB-05:01 -3.8
March 0.165459E+09 13809.20 02-MAR-05:01 -3.9
April 4034020.29 3887.79 11-APR-05:02 4.90
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.320765E+09 14701.94 27-NOV-04:01 3.80
December 0.100680E+10 15328.72 04-DEC-04:11 -0.2
         
Annual Sum or Average 0.261275E+10      
Minimum of Months 0.00 0.00   -3.9
Maximum of Months 0.100680E+10 15328.72   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.641096E+09 13402.81 28-JAN-05:01 -2.9
February 0.336343E+09 13419.88 02-FEB-05:01 -2.4
March 90423723.18 13195.80 02-MAR-05:01 -3.9
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.218058E+09 13488.50 28-NOV-05:01 -0.3
December 0.821424E+09 13991.92 04-DEC-04:11 -0.2
         
Annual Sum or Average 0.210735E+10      
Minimum of Months 0.00 0.00   -3.9
Maximum of Months 0.821424E+09 13991.92   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 49318441.04 8453.57 17-JAN-05:01 5.40
February 79219322.04 8012.55 27-FEB-05:02 8.90
March 87549583.93 7820.39 03-MAR-05:02 7.30
April 99582940.00 7905.27 14-APR-03:02 15.50
May 49910154.66 5269.55 09-MAY-03:02 23.22
June 38038224.58 5860.69 29-JUN-03:02 18.23
July 52219689.71 5806.37 02-JUL-15:42 38.22
August 60271267.46 6516.27 27-AUG-15:41 35.00
September 54822966.18 5442.93 13-SEP-03:02 23.30
October 90857899.32 7649.98 16-OCT-03:02 13.98
November 92090331.35 9408.46 27-NOV-04:01 3.80
December 94997738.04 10131.87 26-DEC-04:01 -0.1
         
Annual Sum or Average 0.848879E+09      
Minimum of Months 38038224.58 5269.55   -0.1
Maximum of Months 99582940.00 10131.87   38.22



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.734069E+09 5221.16 04-JAN-06:03 7.80
February 0.324572E+09 5187.99 07-FEB-06:03 13.72
March 0.110329E+09 4996.81 01-MAR-06:03 1.60
April 37350773.13 4210.83 14-APR-05:02 13.22
May 36210089.12 4813.30 31-MAY-03:02 26.70
June 31478062.17 5035.17 22-JUN-03:02 25.10
July 35480710.23 5772.05 02-JUL-16:11 38.13
August 32939355.74 4969.05 06-AUG-15:31 36.10
September 34616376.55 4318.46 10-SEP-15:41 31.10
October 49208242.72 5077.81 08-OCT-15:42 26.20
November 0.198510E+09 4825.75 08-NOV-06:03 12.30
December 0.823084E+09 4666.18 14-DEC-06:02 2.70
         
Annual Sum or Average 0.244785E+10      
Minimum of Months 31478062.17 4210.83   1.60
Maximum of Months 0.823084E+09 5772.05   38.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.374869E+10 13383.43 09-JAN-06:03 2.98
February 0.252060E+10 12087.03 03-FEB-06:01 -3.7
March 0.186392E+10 11822.58 02-MAR-06:01 -3.5
April 0.594818E+09 13178.62 26-APR-05:02 12.02
May 0.212308E+09 13854.91 02-MAY-05:02 9.90
June 64862845.86 8250.55 05-JUN-03:02 22.38
July 41324900.62 9481.58 05-JUL-03:02 18.90
August 64889862.15 9206.66 17-AUG-05:03 17.20
September 0.198272E+09 14040.28 25-SEP-05:03 9.08
October 0.632047E+09 12396.73 23-OCT-05:03 12.80
November 0.218738E+10 13396.87 28-NOV-06:03 1.02
December 0.459511E+10 18027.73 26-DEC-06:13 -0.6
         
Annual Sum or Average 0.167242E+11      
Minimum of Months 41324900.62 8250.55   -3.7
Maximum of Months 0.459511E+10 18027.73   22.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 6.70
February 0.00 0.00 01-FEB-00:10 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:10 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 6.70
February 0.00 0.00 01-FEB-00:10 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:10 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.491352E+09 595.53 28-JAN-04:45 -2.7
February 0.00 0.00 01-FEB-00:10 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:10 8.95
         
Annual Sum or Average 0.491352E+09      
Minimum of Months 0.00 0.00   -2.7
Maximum of Months 0.491352E+09 595.53   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 6.70
February 0.00 0.00 01-FEB-00:10 6.42
March 0.00 0.00 01-MAR-00:10 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:05 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:03 27.63
August 0.00 0.00 01-AUG-00:03 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:10 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.113123E+11 11837.83 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.102611E+11 11837.83 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.121930E+11 11837.83 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.108909E+11 11837.83 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.117527E+11 11837.83 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.116958E+11 11837.83 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.109477E+11 11837.83 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.121930E+11 11837.83 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.108909E+11 11837.83 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.113123E+11 11837.83 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.111797E+11 11837.83 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.109477E+11 11837.83 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.135577E+12     0.424397E+12    
Minimum of Months 0.102611E+11 11837.83   0.325565E+11 13457.54  
Maximum of Months 0.121930E+11 11837.83   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101592E+11 10631.20 02-JAN-08:09 0.243681E+11 17206.63 02-JAN-08:09
February 0.921518E+10 10631.20 01-FEB-08:09 0.220609E+11 17206.63 01-FEB-08:09
March 0.109502E+11 10631.20 01-MAR-08:09 0.253549E+11 17206.63 01-MAR-08:09
April 0.978077E+10 10631.20 03-APR-07:10 0.235306E+11 17206.63 03-APR-07:10
May 0.105547E+11 10631.20 01-MAY-07:10 0.248615E+11 17206.63 01-MAY-07:10
June 0.105037E+11 10631.20 01-JUN-07:10 0.244160E+11 17206.63 01-JUN-07:10
July 0.983180E+10 10631.20 03-JUL-07:10 0.239708E+11 17206.63 03-JUL-07:10
August 0.109502E+11 10631.20 01-AUG-07:10 0.253549E+11 17206.63 01-AUG-07:10
September 0.978077E+10 10631.20 01-SEP-07:10 0.235199E+11 17206.63 01-SEP-07:10
October 0.101592E+11 10631.20 02-OCT-07:10 0.243735E+11 17206.63 02-OCT-07:10
November 0.100402E+11 10631.20 01-NOV-07:10 0.238373E+11 17206.63 01-NOV-07:10
December 0.983180E+10 10631.20 01-DEC-08:09 0.239654E+11 17206.63 01-DEC-08:09
             
Annual Sum or Average 0.121758E+12     0.289614E+12    
Minimum of Months 0.921518E+10 10631.20   0.220609E+11 17206.63  
Maximum of Months 0.109502E+11 10631.20   0.253549E+11 17206.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101592E+11 10631.20 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.921518E+10 10631.20 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.109502E+11 10631.20 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.978077E+10 10631.20 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.105547E+11 10631.20 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.105037E+11 10631.20 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.983180E+10 10631.20 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.109502E+11 10631.20 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.978077E+10 10631.20 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.101592E+11 10631.20 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.100402E+11 10631.20 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.983180E+10 10631.20 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.121758E+12     0.289613E+12    
Minimum of Months 0.921518E+10 10631.20   0.220609E+11 17206.56  
Maximum of Months 0.109502E+11 10631.20   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101592E+11 10631.20 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.921518E+10 10631.20 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.109502E+11 10631.20 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.978077E+10 10631.20 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.105547E+11 10631.20 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.105037E+11 10631.20 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.983180E+10 10631.20 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.109502E+11 10631.20 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.978077E+10 10631.20 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.101592E+11 10631.20 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.100402E+11 10631.20 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.983180E+10 10631.20 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.121758E+12     0.289613E+12    
Minimum of Months 0.921518E+10 10631.20   0.220609E+11 17206.56  
Maximum of Months 0.109502E+11 10631.20   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.837312E+09 1261.48 17-JAN-16:00 0.305979E+10 2160.55 02-JAN-08:09
February 0.723778E+09 1146.45 01-FEB-16:00 0.277008E+10 2160.55 01-FEB-08:09
March 0.800900E+09 1103.56 10-MAR-16:00 0.318369E+10 2160.55 01-MAR-08:09
April 0.680485E+09 878.43 20-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.720019E+09 705.39 23-MAY-12:30 0.312174E+10 2160.55 01-MAY-07:10
June 0.707439E+09 635.12 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.670944E+09 845.81 07-JUL-07:30 0.300989E+10 2160.55 03-JUL-07:10
August 0.760310E+09 834.99 17-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.703897E+09 927.96 29-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.769206E+09 1173.73 13-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.818318E+09 1334.85 22-NOV-16:00 0.299314E+10 2160.55 01-NOV-07:10
December 0.821371E+09 1334.85 01-DEC-16:00 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.901398E+10     0.363654E+11    
Minimum of Months 0.670944E+09 635.12   0.277008E+10 2160.55  
Maximum of Months 0.837312E+09 1334.85   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.523615E+09 814.06 17-JAN-16:00 0.197184E+10 1392.34 02-JAN-08:09
February 0.458661E+09 750.42 13-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.511526E+09 721.12 10-MAR-16:00 0.205169E+10 1392.34 01-MAR-08:09
April 0.441698E+09 472.56 20-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.470244E+09 463.36 24-MAY-15:39 0.201177E+10 1392.34 01-MAY-07:10
June 0.463103E+09 448.61 19-JUN-15:00 0.197572E+10 1392.34 01-JUN-07:10
July 0.439194E+09 476.25 03-JUL-15:00 0.193969E+10 1392.34 03-JUL-07:10
August 0.493273E+09 480.56 16-AUG-15:00 0.205169E+10 1392.34 01-AUG-07:10
September 0.448566E+09 528.80 29-SEP-15:00 0.190321E+10 1392.34 01-SEP-07:10
October 0.488644E+09 745.86 13-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.516143E+09 860.23 22-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.516255E+09 860.23 01-DEC-16:00 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.577092E+10     0.234352E+11    
Minimum of Months 0.439194E+09 448.61   0.178515E+10 1392.34  
Maximum of Months 0.523615E+09 860.23   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.770987E+09 1256.54 17-JAN-16:00 0.305983E+10 2160.58 02-JAN-08:09
February 0.685855E+09 1094.05 23-FEB-16:00 0.277013E+10 2160.58 01-FEB-08:09
March 0.782926E+09 1092.53 10-MAR-16:00 0.318374E+10 2160.58 01-MAR-08:09
April 0.684664E+09 877.62 20-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.729390E+09 709.76 03-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.718821E+09 667.41 29-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.682774E+09 870.14 07-JUL-07:30 0.300994E+10 2160.58 03-JUL-07:10
August 0.765606E+09 855.15 17-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.693549E+09 820.66 18-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.741376E+09 1167.32 13-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.758948E+09 1334.88 22-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.761062E+09 1334.88 01-DEC-16:00 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.877596E+10     0.363660E+11    
Minimum of Months 0.682774E+09 667.41   0.277013E+10 2160.58  
Maximum of Months 0.782926E+09 1334.88   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.511054E+09 807.90 17-JAN-16:00 0.197183E+10 1392.33 02-JAN-08:09
February 0.450605E+09 703.28 03-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.509385E+09 685.19 10-MAR-16:00 0.205168E+10 1392.33 01-MAR-08:09
April 0.440471E+09 610.58 20-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.465830E+09 472.49 03-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.458248E+09 453.16 29-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.435228E+09 598.90 07-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.492786E+09 617.33 24-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.451428E+09 613.21 18-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.485026E+09 759.77 13-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.499489E+09 860.23 22-NOV-16:00 0.192888E+10 1392.33 01-NOV-07:10
December 0.503910E+09 860.23 01-DEC-16:00 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.570346E+10     0.234351E+11    
Minimum of Months 0.435228E+09 453.16   0.178514E+10 1392.33  
Maximum of Months 0.511054E+09 860.23   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.836610E+09 1263.05 17-JAN-16:00 0.305979E+10 2160.55 02-JAN-08:09
February 0.723330E+09 1149.77 01-FEB-16:00 0.277008E+10 2160.55 01-FEB-08:09
March 0.800468E+09 1108.48 10-MAR-16:00 0.318369E+10 2160.55 01-MAR-08:09
April 0.680326E+09 887.98 20-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.719987E+09 701.98 23-MAY-12:30 0.312174E+10 2160.55 01-MAY-07:10
June 0.707525E+09 635.12 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.670935E+09 855.90 07-JUL-07:30 0.300989E+10 2160.55 03-JUL-07:10
August 0.760016E+09 845.34 17-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.703543E+09 932.07 29-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.768509E+09 1177.14 13-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.817760E+09 1334.85 22-NOV-16:00 0.299314E+10 2160.55 01-NOV-07:10
December 0.820490E+09 1334.85 01-DEC-16:00 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.900950E+10     0.363654E+11    
Minimum of Months 0.670935E+09 635.12   0.277008E+10 2160.55  
Maximum of Months 0.836610E+09 1334.85   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.523080E+09 814.16 17-JAN-16:00 0.197184E+10 1392.34 02-JAN-08:09
February 0.458154E+09 750.64 13-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.511253E+09 721.39 10-MAR-16:00 0.205169E+10 1392.34 01-MAR-08:09
April 0.441585E+09 471.34 20-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.470140E+09 461.12 24-MAY-15:39 0.201177E+10 1392.34 01-MAY-07:10
June 0.462958E+09 446.07 19-JUN-15:00 0.197572E+10 1392.34 01-JUN-07:10
July 0.438990E+09 474.63 03-JUL-15:00 0.193969E+10 1392.34 03-JUL-07:10
August 0.493159E+09 529.15 16-AUG-15:00 0.205169E+10 1392.34 01-AUG-07:10
September 0.448435E+09 526.28 29-SEP-15:00 0.190321E+10 1392.34 01-SEP-07:10
October 0.488204E+09 746.37 13-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.515570E+09 860.23 22-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.515861E+09 860.23 01-DEC-16:00 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.576739E+10     0.234352E+11    
Minimum of Months 0.438990E+09 446.07   0.178515E+10 1392.34  
Maximum of Months 0.523080E+09 860.23   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.773229E+09 1258.31 17-JAN-16:00 0.305983E+10 2160.58 02-JAN-08:09
February 0.686027E+09 1099.53 23-FEB-16:00 0.277013E+10 2160.58 01-FEB-08:09
March 0.783014E+09 1097.82 10-MAR-16:00 0.318374E+10 2160.58 01-MAR-08:09
April 0.684816E+09 887.18 20-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.729431E+09 707.08 03-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.718744E+09 663.69 29-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.682843E+09 879.57 07-JUL-07:30 0.300994E+10 2160.58 03-JUL-07:10
August 0.765658E+09 864.90 17-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.693389E+09 822.65 18-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.739671E+09 1170.94 13-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.759435E+09 1334.88 22-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.765828E+09 1334.88 01-DEC-16:00 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.878209E+10     0.363660E+11    
Minimum of Months 0.682843E+09 663.69   0.277013E+10 2160.58  
Maximum of Months 0.783014E+09 1334.88   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.510552E+09 808.14 17-JAN-16:00 0.197183E+10 1392.33 02-JAN-08:09
February 0.450232E+09 703.20 03-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.509133E+09 686.39 10-MAR-16:00 0.205168E+10 1392.33 01-MAR-08:09
April 0.440270E+09 611.02 20-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.465649E+09 470.75 03-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.458124E+09 450.77 29-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.435063E+09 598.93 07-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.492601E+09 617.31 24-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.451100E+09 613.04 18-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.484698E+09 759.96 13-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.499269E+09 860.23 22-NOV-16:00 0.192888E+10 1392.33 01-NOV-07:10
December 0.503455E+09 860.23 01-DEC-16:00 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.570015E+10     0.234351E+11    
Minimum of Months 0.435063E+09 450.77   0.178514E+10 1392.33  
Maximum of Months 0.510552E+09 860.23   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.836601E+09 1262.96 17-JAN-16:00 0.305979E+10 2160.55 02-JAN-08:09
February 0.723313E+09 1149.90 01-FEB-16:00 0.277008E+10 2160.55 01-FEB-08:09
March 0.800416E+09 1108.23 10-MAR-16:00 0.318369E+10 2160.55 01-MAR-08:09
April 0.680306E+09 887.54 20-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.719984E+09 701.77 23-MAY-12:30 0.312174E+10 2160.55 01-MAY-07:10
June 0.707525E+09 635.12 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.670923E+09 855.39 07-JUL-07:30 0.300989E+10 2160.55 03-JUL-07:10
August 0.759998E+09 844.88 17-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.703525E+09 932.30 29-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.768546E+09 1176.95 13-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.817806E+09 1334.85 22-NOV-16:00 0.299314E+10 2160.55 01-NOV-07:10
December 0.820457E+09 1334.85 01-DEC-16:00 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.900940E+10     0.363654E+11    
Minimum of Months 0.670923E+09 635.12   0.277008E+10 2160.55  
Maximum of Months 0.836601E+09 1334.85   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.523088E+09 814.11 17-JAN-16:00 0.197184E+10 1392.34 02-JAN-08:09
February 0.458147E+09 750.55 13-FEB-16:00 0.178515E+10 1392.34 01-FEB-08:09
March 0.511254E+09 721.24 10-MAR-16:00 0.205169E+10 1392.34 01-MAR-08:09
April 0.441580E+09 471.24 20-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.470141E+09 461.02 24-MAY-15:39 0.201177E+10 1392.34 01-MAY-07:10
June 0.462960E+09 445.93 19-JUN-15:00 0.197572E+10 1392.34 01-JUN-07:10
July 0.439026E+09 474.53 03-JUL-15:00 0.193969E+10 1392.34 03-JUL-07:10
August 0.493143E+09 528.78 16-AUG-15:00 0.205169E+10 1392.34 01-AUG-07:10
September 0.448447E+09 526.52 29-SEP-15:00 0.190321E+10 1392.34 01-SEP-07:10
October 0.488187E+09 746.26 13-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.515609E+09 860.23 22-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.515876E+09 860.23 01-DEC-16:00 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.576746E+10     0.234352E+11    
Minimum of Months 0.439026E+09 445.93   0.178515E+10 1392.34  
Maximum of Months 0.523088E+09 860.23   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.773230E+09 1258.23 17-JAN-16:00 0.305983E+10 2160.58 02-JAN-08:09
February 0.686010E+09 1099.30 23-FEB-16:00 0.277013E+10 2160.58 01-FEB-08:09
March 0.783005E+09 1097.57 10-MAR-16:00 0.318374E+10 2160.58 01-MAR-08:09
April 0.684809E+09 886.73 20-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.729419E+09 706.88 03-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.718741E+09 663.42 29-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.682830E+09 879.06 07-JUL-07:30 0.300994E+10 2160.58 03-JUL-07:10
August 0.765628E+09 864.44 17-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.693372E+09 822.86 18-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.739638E+09 1170.75 13-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.759436E+09 1334.88 22-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.765836E+09 1334.88 01-DEC-16:00 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.878195E+10     0.363660E+11    
Minimum of Months 0.682830E+09 663.42   0.277013E+10 2160.58  
Maximum of Months 0.783005E+09 1334.88   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.510558E+09 808.09 17-JAN-16:00 0.197183E+10 1392.33 02-JAN-08:09
February 0.450260E+09 703.32 03-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.509135E+09 686.25 10-MAR-16:00 0.205168E+10 1392.33 01-MAR-08:09
April 0.440269E+09 610.75 20-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.465651E+09 470.65 03-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.458115E+09 450.64 29-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.435079E+09 598.74 07-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.492592E+09 617.15 24-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.451120E+09 613.24 18-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.484686E+09 759.85 13-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.499267E+09 860.23 22-NOV-16:00 0.192888E+10 1392.33 01-NOV-07:10
December 0.503458E+09 860.23 01-DEC-16:00 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.570019E+10     0.234351E+11    
Minimum of Months 0.435079E+09 450.64   0.178514E+10 1392.33  
Maximum of Months 0.510558E+09 860.23   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272315E+09 284.97 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.247010E+09 284.97 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.293517E+09 284.97 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.262171E+09 284.97 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.282916E+09 284.97 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.281548E+09 284.97 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.263538E+09 284.97 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.293517E+09 284.97 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.262171E+09 284.97 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.272315E+09 284.97 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.269124E+09 284.97 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.263538E+09 284.97 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.326368E+10     0.153881E+12    
Minimum of Months 0.247010E+09 284.97   0.505780E+10 1948.61  
Maximum of Months 0.293517E+09 284.97   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272315E+09 284.97 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.247010E+09 284.97 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.293517E+09 284.97 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.262171E+09 284.97 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.282916E+09 284.97 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.281548E+09 284.97 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.263538E+09 284.97 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.293517E+09 284.97 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.262171E+09 284.97 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.272315E+09 284.97 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.269124E+09 284.97 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.263538E+09 284.97 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.326368E+10     0.153881E+12    
Minimum of Months 0.247010E+09 284.97   0.505780E+10 1948.61  
Maximum of Months 0.293517E+09 284.97   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272315E+09 284.97 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.247010E+09 284.97 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.293517E+09 284.97 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.262171E+09 284.97 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.282916E+09 284.97 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.281548E+09 284.97 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.263538E+09 284.97 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.293517E+09 284.97 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.262171E+09 284.97 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.272315E+09 284.97 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.269124E+09 284.97 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.263538E+09 284.97 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.326368E+10     0.153881E+12    
Minimum of Months 0.247010E+09 284.97   0.505780E+10 1948.61  
Maximum of Months 0.293517E+09 284.97   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.318958E+10 3337.76 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.289319E+10 3337.76 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.343791E+10 3337.76 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.307076E+10 3337.76 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.331375E+10 3337.76 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.329773E+10 3337.76 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.308678E+10 3337.76 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.343791E+10 3337.76 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.307076E+10 3337.76 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.318958E+10 3337.76 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.315220E+10 3337.76 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.308678E+10 3337.76 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.382269E+11     0.749486E+13    
Minimum of Months 0.289319E+10 3337.76   0.246344E+12 94908.13  
Maximum of Months 0.343791E+10 3337.76   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.113123E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.102611E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.121930E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.108909E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.117527E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.116958E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.109477E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.121930E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.108909E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.113123E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.111797E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.109477E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.135577E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.102611E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.121930E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.101592E+11 0.243681E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.109502E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.978077E+10 0.235306E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.105547E+11 0.248615E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.105037E+11 0.244160E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.983180E+10 0.239708E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.109502E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.978077E+10 0.235199E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.101592E+11 0.243735E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.100402E+11 0.238373E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.983180E+10 0.239654E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.121758E+12 0.289614E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.109502E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.101592E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.978077E+10 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.105547E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.105037E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.983180E+10 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.978077E+10 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.101592E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.100402E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.983180E+10 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.121758E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.101592E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.978077E+10 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.105547E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.105037E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.983180E+10 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.978077E+10 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.101592E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.100402E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.983180E+10 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.121758E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.837312E+09 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.131875E+09
February 0.136985E+10 0.723778E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.111599E+09
March 0.163685E+10 0.800900E+09 0.318369E+10 0.00 0.00 0.00 0.00 35196.34 0.117308E+09
April 0.145243E+10 0.680485E+09 0.295462E+10 0.00 0.00 0.00 0.00 6072653.36 59975370.79
May 0.157338E+10 0.720019E+09 0.312174E+10 0.00 0.00 0.00 0.00 18087021.54 33535859.56
June 0.156900E+10 0.707439E+09 0.306580E+10 0.00 0.00 0.00 0.00 28305032.02 10210657.85
July 0.145680E+10 0.670944E+09 0.300989E+10 0.00 0.00 0.00 0.00 23363169.51 7053086.74
August 0.163685E+10 0.760310E+09 0.318369E+10 0.00 0.00 0.00 0.00 18636857.27 10251670.69
September 0.145243E+10 0.703897E+09 0.295328E+10 0.00 0.00 0.00 0.00 5940204.09 16551649.41
October 0.150991E+10 0.769206E+09 0.306046E+10 0.00 0.00 0.00 0.00 2290038.54 55205617.34
November 0.149516E+10 0.818318E+09 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.109374E+09
December 0.145680E+10 0.821371E+09 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.117821E+09
                   
Annual Sum or Average 0.181194E+11 0.901398E+10 0.363654E+11 0.00 0.00 0.00 0.00 0.102730E+09 0.780761E+09
Minimum of Months 0.136985E+10 0.670944E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 7053086.74
Maximum of Months 0.163685E+10 0.837312E+09 0.318369E+10 0.00 0.00 0.00 0.00 28305032.02 0.131875E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.523615E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 88700138.72
February 0.882782E+09 0.458661E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 74831817.09
March 0.105485E+10 0.511526E+09 0.205169E+10 0.00 0.00 0.00 0.00 23462.00 78857820.15
April 0.936002E+09 0.441698E+09 0.190407E+10 0.00 0.00 0.00 0.00 3926687.22 39449594.68
May 0.101394E+10 0.470244E+09 0.201177E+10 0.00 0.00 0.00 0.00 11680032.17 22936105.37
June 0.101113E+10 0.463103E+09 0.197572E+10 0.00 0.00 0.00 0.00 19063298.06 6420839.87
July 0.938820E+09 0.439194E+09 0.193969E+10 0.00 0.00 0.00 0.00 16026790.64 4118507.50
August 0.105485E+10 0.493273E+09 0.205169E+10 0.00 0.00 0.00 0.00 12734872.08 6184422.16
September 0.936002E+09 0.448566E+09 0.190321E+10 0.00 0.00 0.00 0.00 3724420.02 11497179.26
October 0.973041E+09 0.488644E+09 0.197228E+10 0.00 0.00 0.00 0.00 1437361.93 36924196.27
November 0.963541E+09 0.516143E+09 0.192889E+10 0.00 0.00 0.00 0.00 0.00 73024333.80
December 0.938820E+09 0.516255E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 77605410.48
                   
Annual Sum or Average 0.116768E+11 0.577092E+10 0.234352E+11 0.00 0.00 0.00 0.00 68616924.11 0.520550E+09
Minimum of Months 0.882782E+09 0.439194E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 4118507.50
Maximum of Months 0.105485E+10 0.523615E+09 0.205169E+10 0.00 0.00 0.00 0.00 19063298.06 88700138.72



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.770987E+09 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.137089E+09
February 0.136988E+10 0.685855E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.116274E+09
March 0.163688E+10 0.782926E+09 0.318374E+10 0.00 0.00 0.00 0.00 35014.09 0.122716E+09
April 0.145246E+10 0.684664E+09 0.295467E+10 0.00 0.00 0.00 0.00 5108646.12 62116512.26
May 0.157341E+10 0.729390E+09 0.312179E+10 0.00 0.00 0.00 0.00 17561926.87 33691244.57
June 0.156904E+10 0.718821E+09 0.306585E+10 0.00 0.00 0.00 0.00 28370713.25 10133697.39
July 0.145684E+10 0.682774E+09 0.300994E+10 0.00 0.00 0.00 0.00 23219861.93 7033752.45
August 0.163688E+10 0.765606E+09 0.318374E+10 0.00 0.00 0.00 0.00 17876464.23 10814278.98
September 0.145246E+10 0.693549E+09 0.295333E+10 0.00 0.00 0.00 0.00 5184800.19 18455866.77
October 0.150994E+10 0.741376E+09 0.306051E+10 0.00 0.00 0.00 0.00 1729610.87 59803267.09
November 0.149520E+10 0.758948E+09 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.115075E+09
December 0.145684E+10 0.761062E+09 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.121178E+09
                   
Annual Sum or Average 0.181198E+11 0.877596E+10 0.363660E+11 0.00 0.00 0.00 0.00 99087037.56 0.814381E+09
Minimum of Months 0.136988E+10 0.682774E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 7033752.45
Maximum of Months 0.163688E+10 0.782926E+09 0.318374E+10 0.00 0.00 0.00 0.00 28370713.25 0.137089E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.511054E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 94501806.01
February 0.882782E+09 0.450605E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 82491297.99
March 0.105485E+10 0.509385E+09 0.205168E+10 0.00 0.00 0.00 0.00 23461.15 90120113.41
April 0.936002E+09 0.440471E+09 0.190406E+10 0.00 0.00 0.00 0.00 3023831.36 48589736.83
May 0.101394E+10 0.465830E+09 0.201175E+10 0.00 0.00 0.00 0.00 10511083.53 26754923.93
June 0.101113E+10 0.458248E+09 0.197570E+10 0.00 0.00 0.00 0.00 17009582.70 8976826.23
July 0.938820E+09 0.435228E+09 0.193968E+10 0.00 0.00 0.00 0.00 13575580.36 7047845.12
August 0.105485E+10 0.492786E+09 0.205168E+10 0.00 0.00 0.00 0.00 10623549.12 9732067.78
September 0.936002E+09 0.451428E+09 0.190319E+10 0.00 0.00 0.00 0.00 3498195.74 13381024.15
October 0.973041E+09 0.485026E+09 0.197226E+10 0.00 0.00 0.00 0.00 1192400.63 42959641.03
November 0.963541E+09 0.499489E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 82825011.17
December 0.938820E+09 0.503910E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 88853364.88
                   
Annual Sum or Average 0.116768E+11 0.570346E+10 0.234351E+11 0.00 0.00 0.00 0.00 59457684.58 0.596234E+09
Minimum of Months 0.882782E+09 0.435228E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 7047845.12
Maximum of Months 0.105485E+10 0.511054E+09 0.205168E+10 0.00 0.00 0.00 0.00 17009582.70 94501806.01



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.836610E+09 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.269668E+09
February 0.136985E+10 0.723330E+09 0.277008E+10 0.00 0.00 0.00 0.00 174432.93 0.230817E+09
March 0.163685E+10 0.800468E+09 0.318369E+10 0.00 0.00 0.00 0.00 198278.56 0.244407E+09
April 0.145243E+10 0.680326E+09 0.295462E+10 0.00 0.00 0.00 0.00 15763352.52 0.135189E+09
May 0.157338E+10 0.719987E+09 0.312174E+10 0.00 0.00 0.00 0.00 41827313.81 77509487.67
June 0.156900E+10 0.707525E+09 0.306580E+10 0.00 0.00 0.00 0.00 63426450.57 27748292.20
July 0.145680E+10 0.670935E+09 0.300989E+10 0.00 0.00 0.00 0.00 53580956.21 20664508.62
August 0.163685E+10 0.760016E+09 0.318369E+10 0.00 0.00 0.00 0.00 43871523.73 27473471.59
September 0.145243E+10 0.703543E+09 0.295328E+10 0.00 0.00 0.00 0.00 14400437.46 37621797.33
October 0.150991E+10 0.768509E+09 0.306046E+10 0.00 0.00 0.00 0.00 6411880.25 0.116993E+09
November 0.149516E+10 0.817760E+09 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.222267E+09
December 0.145680E+10 0.820490E+09 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.234641E+09
                   
Annual Sum or Average 0.181194E+11 0.900950E+10 0.363654E+11 0.00 0.00 0.00 0.00 0.239655E+09 0.164500E+10
Minimum of Months 0.136985E+10 0.670935E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 20664508.62
Maximum of Months 0.163685E+10 0.836610E+09 0.318369E+10 0.00 0.00 0.00 0.00 63426450.57 0.269668E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.523080E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.186582E+09
February 0.649041E+09 0.458154E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.161986E+09
March 0.773965E+09 0.511253E+09 0.205169E+10 0.00 0.00 0.00 0.00 43768.31 0.175719E+09
April 0.688021E+09 0.441585E+09 0.190407E+10 0.00 0.00 0.00 0.00 8497268.45 97376473.43
May 0.744847E+09 0.470140E+09 0.201177E+10 0.00 0.00 0.00 0.00 25864659.97 55670081.48
June 0.742030E+09 0.462958E+09 0.197572E+10 0.00 0.00 0.00 0.00 41092073.68 19609517.14
July 0.690839E+09 0.438990E+09 0.193969E+10 0.00 0.00 0.00 0.00 34452212.25 14784774.66
August 0.773965E+09 0.493159E+09 0.205169E+10 0.00 0.00 0.00 0.00 27488439.63 19869534.05
September 0.688021E+09 0.448435E+09 0.190321E+10 0.00 0.00 0.00 0.00 8400820.38 27952845.46
October 0.715730E+09 0.488204E+09 0.197228E+10 0.00 0.00 0.00 0.00 3348009.70 83210551.99
November 0.708685E+09 0.515570E+09 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.157170E+09
December 0.690839E+09 0.515861E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.162517E+09
                   
Annual Sum or Average 0.858171E+10 0.576739E+10 0.234352E+11 0.00 0.00 0.00 0.00 0.149187E+09 0.116245E+10
Minimum of Months 0.649041E+09 0.438990E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 14784774.66
Maximum of Months 0.773965E+09 0.523080E+09 0.205169E+10 0.00 0.00 0.00 0.00 41092073.68 0.186582E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.773229E+09 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.312060E+09
February 0.136988E+10 0.686027E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.264711E+09
March 0.163688E+10 0.783014E+09 0.318374E+10 0.00 0.00 0.00 0.00 65013.94 0.280059E+09
April 0.145246E+10 0.684816E+09 0.295467E+10 0.00 0.00 0.00 0.00 11574788.47 0.146641E+09
May 0.157341E+10 0.729431E+09 0.312179E+10 0.00 0.00 0.00 0.00 40098944.33 79142535.13
June 0.156904E+10 0.718744E+09 0.306585E+10 0.00 0.00 0.00 0.00 63923446.25 27343153.15
July 0.145684E+10 0.682843E+09 0.300994E+10 0.00 0.00 0.00 0.00 53246179.94 20597246.36
August 0.163688E+10 0.765658E+09 0.318374E+10 0.00 0.00 0.00 0.00 40941222.98 29736319.06
September 0.145246E+10 0.693389E+09 0.295333E+10 0.00 0.00 0.00 0.00 11700216.41 44169813.54
October 0.150994E+10 0.739671E+09 0.306051E+10 0.00 0.00 0.00 0.00 3746564.35 0.138756E+09
November 0.149520E+10 0.759435E+09 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.261602E+09
December 0.145684E+10 0.765828E+09 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.271691E+09
                   
Annual Sum or Average 0.181198E+11 0.878209E+10 0.363660E+11 0.00 0.00 0.00 0.00 0.225296E+09 0.187651E+10
Minimum of Months 0.136988E+10 0.682843E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 20597246.36
Maximum of Months 0.163688E+10 0.783014E+09 0.318374E+10 0.00 0.00 0.00 0.00 63923446.25 0.312060E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.510552E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.193739E+09
February 0.882782E+09 0.450232E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.167594E+09
March 0.105485E+10 0.509133E+09 0.205168E+10 0.00 0.00 0.00 0.00 43569.38 0.183682E+09
April 0.936002E+09 0.440270E+09 0.190406E+10 0.00 0.00 0.00 0.00 7295785.69 0.104111E+09
May 0.101394E+10 0.465649E+09 0.201175E+10 0.00 0.00 0.00 0.00 23926294.27 60241181.23
June 0.101113E+10 0.458124E+09 0.197570E+10 0.00 0.00 0.00 0.00 39018685.74 22716629.87
July 0.938820E+09 0.435063E+09 0.193968E+10 0.00 0.00 0.00 0.00 32222213.52 17819616.55
August 0.105485E+10 0.492601E+09 0.205168E+10 0.00 0.00 0.00 0.00 25543408.90 22780604.73
September 0.936002E+09 0.451100E+09 0.190319E+10 0.00 0.00 0.00 0.00 8204558.78 30050579.03
October 0.973041E+09 0.484698E+09 0.197226E+10 0.00 0.00 0.00 0.00 2859733.41 89609100.29
November 0.963541E+09 0.499269E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.163857E+09
December 0.938820E+09 0.503455E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.169340E+09
                   
Annual Sum or Average 0.116768E+11 0.570015E+10 0.234351E+11 0.00 0.00 0.00 0.00 0.139114E+09 0.122554E+10
Minimum of Months 0.882782E+09 0.435063E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 17819616.55
Maximum of Months 0.105485E+10 0.510552E+09 0.205168E+10 0.00 0.00 0.00 0.00 39018685.74 0.193739E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.836601E+09 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.295339E+09
February 0.136985E+10 0.723313E+09 0.277008E+10 0.00 0.00 0.00 0.00 748646.98 0.257669E+09
March 0.163685E+10 0.800416E+09 0.318369E+10 0.00 0.00 0.00 0.00 432074.99 0.276358E+09
April 0.145243E+10 0.680306E+09 0.295462E+10 0.00 0.00 0.00 0.00 18376424.62 0.161064E+09
May 0.157338E+10 0.719984E+09 0.312174E+10 0.00 0.00 0.00 0.00 48126007.92 95970261.05
June 0.156900E+10 0.707525E+09 0.306580E+10 0.00 0.00 0.00 0.00 75000861.12 36035417.78
July 0.145680E+10 0.670923E+09 0.300989E+10 0.00 0.00 0.00 0.00 61275801.10 27236998.19
August 0.163685E+10 0.759998E+09 0.318369E+10 0.00 0.00 0.00 0.00 50832360.44 34836128.19
September 0.145243E+10 0.703525E+09 0.295328E+10 0.00 0.00 0.00 0.00 16399684.28 47033047.61
October 0.150991E+10 0.768546E+09 0.306046E+10 0.00 0.00 0.00 0.00 8051063.18 0.134917E+09
November 0.149516E+10 0.817806E+09 0.299314E+10 0.00 0.00 0.00 0.00 13061.31 0.243150E+09
December 0.145680E+10 0.820457E+09 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.257138E+09
                   
Annual Sum or Average 0.181194E+11 0.900940E+10 0.363654E+11 0.00 0.00 0.00 0.00 0.279256E+09 0.186675E+10
Minimum of Months 0.136985E+10 0.670923E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 27236998.19
Maximum of Months 0.163685E+10 0.836601E+09 0.318369E+10 0.00 0.00 0.00 0.00 75000861.12 0.295339E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.523088E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.205052E+09
February 0.882782E+09 0.458147E+09 0.178515E+10 0.00 0.00 0.00 0.00 6240.12 0.182152E+09
March 0.105485E+10 0.511254E+09 0.205169E+10 0.00 0.00 0.00 0.00 41310.58 0.203255E+09
April 0.936002E+09 0.441580E+09 0.190407E+10 0.00 0.00 0.00 0.00 9719744.84 0.118574E+09
May 0.101394E+10 0.470141E+09 0.201177E+10 0.00 0.00 0.00 0.00 30338672.88 69584339.40
June 0.101113E+10 0.462960E+09 0.197572E+10 0.00 0.00 0.00 0.00 49130181.74 25327425.74
July 0.938820E+09 0.439026E+09 0.193969E+10 0.00 0.00 0.00 0.00 40192734.59 19283095.19
August 0.105485E+10 0.493143E+09 0.205169E+10 0.00 0.00 0.00 0.00 32389833.66 25139870.76
September 0.936002E+09 0.448447E+09 0.190321E+10 0.00 0.00 0.00 0.00 9781991.90 35303406.09
October 0.973041E+09 0.488187E+09 0.197228E+10 0.00 0.00 0.00 0.00 4036507.98 97948094.34
November 0.963541E+09 0.515609E+09 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.174670E+09
December 0.938820E+09 0.515876E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.178290E+09
                   
Annual Sum or Average 0.116768E+11 0.576746E+10 0.234352E+11 0.00 0.00 0.00 0.00 0.175637E+09 0.133458E+10
Minimum of Months 0.882782E+09 0.439026E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 19283095.19
Maximum of Months 0.105485E+10 0.523088E+09 0.205169E+10 0.00 0.00 0.00 0.00 49130181.74 0.205052E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.773230E+09 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.349204E+09
February 0.136988E+10 0.686010E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.302875E+09
March 0.163688E+10 0.783005E+09 0.318374E+10 0.00 0.00 0.00 0.00 61794.66 0.325777E+09
April 0.145246E+10 0.684809E+09 0.295467E+10 0.00 0.00 0.00 0.00 13562969.87 0.177134E+09
May 0.157341E+10 0.729419E+09 0.312179E+10 0.00 0.00 0.00 0.00 46635665.03 98042645.98
June 0.156904E+10 0.718741E+09 0.306585E+10 0.00 0.00 0.00 0.00 75635310.24 35462858.14
July 0.145684E+10 0.682830E+09 0.300994E+10 0.00 0.00 0.00 0.00 61286061.88 27128909.08
August 0.163688E+10 0.765628E+09 0.318374E+10 0.00 0.00 0.00 0.00 48116079.50 37854611.03
September 0.145246E+10 0.693372E+09 0.295333E+10 0.00 0.00 0.00 0.00 13853236.29 55677056.35
October 0.150994E+10 0.739638E+09 0.306051E+10 0.00 0.00 0.00 0.00 4490166.16 0.165314E+09
November 0.149520E+10 0.759436E+09 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.297203E+09
December 0.145684E+10 0.765836E+09 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.302930E+09
                   
Annual Sum or Average 0.181198E+11 0.878195E+10 0.363660E+11 0.00 0.00 0.00 0.00 0.263641E+09 0.217460E+10
Minimum of Months 0.136988E+10 0.682830E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 27128909.08
Maximum of Months 0.163688E+10 0.783005E+09 0.318374E+10 0.00 0.00 0.00 0.00 75635310.24 0.349204E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.510558E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.218404E+09
February 0.882782E+09 0.450260E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.191694E+09
March 0.105485E+10 0.509135E+09 0.205168E+10 0.00 0.00 0.00 0.00 44236.43 0.214064E+09
April 0.936002E+09 0.440269E+09 0.190406E+10 0.00 0.00 0.00 0.00 8727790.54 0.125871E+09
May 0.101394E+10 0.465651E+09 0.201175E+10 0.00 0.00 0.00 0.00 28747569.09 74582630.81
June 0.101113E+10 0.458115E+09 0.197570E+10 0.00 0.00 0.00 0.00 47538562.44 28675187.05
July 0.938820E+09 0.435079E+09 0.193968E+10 0.00 0.00 0.00 0.00 38511042.82 22379240.28
August 0.105485E+10 0.492592E+09 0.205168E+10 0.00 0.00 0.00 0.00 30814310.44 28339380.17
September 0.936002E+09 0.451120E+09 0.190319E+10 0.00 0.00 0.00 0.00 9839093.90 37593840.33
October 0.973041E+09 0.484686E+09 0.197226E+10 0.00 0.00 0.00 0.00 3496363.20 0.106241E+09
November 0.963541E+09 0.499267E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.185420E+09
December 0.938820E+09 0.503458E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.190459E+09
                   
Annual Sum or Average 0.116768E+11 0.570019E+10 0.234351E+11 0.00 0.00 0.00 0.00 0.167719E+09 0.142372E+10
Minimum of Months 0.882782E+09 0.435079E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 22379240.28
Maximum of Months 0.105485E+10 0.510558E+09 0.205168E+10 0.00 0.00 0.00 0.00 47538562.44 0.218404E+09



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.272315E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.247010E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.293517E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.262171E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.282916E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.281548E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.263538E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.293517E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.262171E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.272315E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.269124E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.263538E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.326368E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.247010E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.293517E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.272315E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.247010E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.293517E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.262171E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.282916E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.281548E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.263538E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.293517E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.262171E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.272315E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.269124E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.263538E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.326368E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.247010E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.293517E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.272315E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.247010E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.293517E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.262171E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.282916E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.281548E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.263538E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.293517E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.262171E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.272315E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.269124E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.263538E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.326368E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.247010E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.293517E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.318958E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.289319E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.343791E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.307076E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.331375E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.329773E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.308678E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.343791E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.307076E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.318958E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.315220E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.308678E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.382269E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.289319E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.343791E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.286129E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.241478E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15633.38 0.253044E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10106559.07 0.132048E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33084315.80 71392921.62
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53072903.13 23184746.76
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 44257778.87 16714291.44
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34378794.00 24565449.94
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10249235.13 36013086.46
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3644849.97 0.120173E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.237241E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.254153E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.188810E+09 0.169614E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16714291.44
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53072903.13 0.286129E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.484184E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.411812E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 47728.79 0.432079E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20224326.39 0.231203E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 60835201.26 0.126515E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 95679478.22 42624382.69
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 81852770.01 30530065.92
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 64298106.32 44117207.35
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19199328.03 63409091.73
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7379711.26 0.206265E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.403333E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.422881E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.349517E+09 0.289895E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30530065.92
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 95679478.22 0.484184E+09



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.467776E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.410880E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.450894E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14827971.43 0.250628E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53715197.15 0.137638E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 95156665.65 50047604.09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76188938.30 37994097.87
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 61720534.99 50965612.34
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15560114.91 72239717.36
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6706004.09 0.217705E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.393887E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.402447E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.323875E+09 0.294310E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 37994097.87
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 95156665.65 0.467776E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 11837.83 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 11837.83 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 11837.83 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 11837.83 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 11837.83 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 11837.83 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 11837.83 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 11837.83 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 11837.83 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 11837.83 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 11837.83 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 11837.83 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   11837.83   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   11837.83   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 10631.20 02-JAN-08:09 17206.63 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 10631.20 01-FEB-08:09 17206.63 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 10631.20 01-MAR-08:09 17206.63 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 10631.20 03-APR-07:10 17206.63 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 10631.20 01-MAY-07:10 17206.63 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 10631.20 01-JUN-07:10 17206.63 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 10631.20 03-JUL-07:10 17206.63 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 10631.20 01-AUG-07:10 17206.63 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 10631.20 01-SEP-07:10 17206.63 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 10631.20 02-OCT-07:10 17206.63 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 10631.20 01-NOV-07:10 17206.63 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 10631.20 01-DEC-08:09 17206.63 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   10631.20   17206.63   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   10631.20   17206.63   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 10631.20 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 10631.20 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 10631.20 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 10631.20 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 10631.20 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 10631.20 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 10631.20 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 10631.20 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 10631.20 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 10631.20 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 10631.20 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 10631.20 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   10631.20   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   10631.20   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 10631.20 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 10631.20 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 10631.20 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 10631.20 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 10631.20 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 10631.20 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 10631.20 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 10631.20 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 10631.20 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 10631.20 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 10631.20 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 10631.20 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   10631.20   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   10631.20   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1261.48 17-JAN-16:00 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 361.37 25-JAN-24:00
February 2010.79 01-FEB-10:09 1146.45 01-FEB-16:00 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 446.36 09-FEB-01:00
March 2010.79 01-MAR-10:09 1103.56 10-MAR-16:00 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 3.13 22-MAR-13:00 363.25 19-MAR-24:00
April 2010.79 03-APR-09:09 878.43 20-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 55.18 01-APR-17:02 366.17 10-APR-24:00
May 2010.79 01-MAY-09:09 705.39 23-MAY-12:30 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 112.02 14-MAY-16:00 173.58 04-MAY-02:00
June 2010.79 01-JUN-09:09 635.12 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 106.37 04-JUN-19:00 121.00 28-JUN-01:53
July 2010.79 03-JUL-09:09 845.81 07-JUL-07:30 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 125.98 02-JUL-21:10 63.13 18-JUL-21:10
August 2010.79 01-AUG-09:09 834.99 17-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 78.56 26-AUG-18:00 99.72 14-AUG-01:00
September 2010.79 01-SEP-09:09 927.96 29-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 45.48 10-SEP-15:10 62.73 24-SEP-07:00
October 2010.79 02-OCT-09:09 1173.73 13-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 63.70 01-OCT-14:53 163.64 24-OCT-02:00
November 2010.79 01-NOV-09:09 1334.85 22-NOV-16:00 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 227.55 26-NOV-09:00
December 2010.79 01-DEC-10:09 1334.85 01-DEC-16:00 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 306.75 18-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   635.12   2160.55   0.00 0.00 0.00 0.00 0.00   62.73  
Maximum of Months 2010.79   1334.85   2160.55   0.00 0.00 0.00 0.00 125.98   446.36  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 814.06 17-JAN-16:00 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 237.81 25-JAN-24:00
February 1295.83 01-FEB-10:09 750.42 13-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 295.88 09-FEB-01:00
March 1295.83 01-MAR-10:09 721.12 10-MAR-16:00 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 2.09 22-MAR-13:00 245.90 19-MAR-24:00
April 1295.83 03-APR-09:09 472.56 20-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 36.20 01-APR-17:02 240.28 10-APR-24:00
May 1295.83 01-MAY-09:09 463.36 24-MAY-15:39 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 71.47 14-MAY-15:50 112.90 04-MAY-02:00
June 1295.83 01-JUN-09:09 448.61 19-JUN-15:00 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 70.71 04-JUN-19:00 78.70 28-JUN-01:53
July 1295.83 03-JUL-09:09 476.25 03-JUL-15:00 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 86.13 02-JUL-21:10 39.63 18-JUL-21:10
August 1295.83 01-AUG-09:09 480.56 16-AUG-15:00 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 54.10 26-AUG-17:50 64.37 14-AUG-01:00
September 1295.83 01-SEP-09:09 528.80 29-SEP-15:00 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 28.62 10-SEP-15:10 45.85 24-SEP-07:00
October 1295.83 02-OCT-09:09 745.86 13-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 40.52 01-OCT-14:52 108.73 24-OCT-02:00
November 1295.83 01-NOV-09:09 860.23 22-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 166.27 26-NOV-09:00
December 1295.83 01-DEC-10:09 860.23 01-DEC-16:00 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 201.18 18-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   448.61   1392.34   0.00 0.00 0.00 0.00 0.00   39.63  
Maximum of Months 1295.83   860.23   1392.34   0.00 0.00 0.00 0.00 86.13   295.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1256.54 17-JAN-16:00 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 355.86 25-JAN-23:00
February 2010.83 01-FEB-10:09 1094.05 23-FEB-16:00 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 452.14 09-FEB-01:00
March 2010.83 01-MAR-10:09 1092.53 10-MAR-16:00 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 3.12 22-MAR-13:00 376.02 19-MAR-24:00
April 2010.83 03-APR-09:09 877.62 20-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 46.88 01-APR-17:02 366.19 10-APR-24:00
May 2010.83 01-MAY-09:09 709.76 03-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 106.02 14-MAY-16:00 172.41 04-MAY-02:00
June 2010.83 01-JUN-09:09 667.41 29-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 104.44 04-JUN-19:00 120.43 28-JUN-01:53
July 2010.83 03-JUL-09:09 870.14 07-JUL-07:30 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 125.97 02-JUL-21:10 63.74 18-JUL-21:10
August 2010.83 01-AUG-09:09 855.15 17-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 75.05 26-AUG-18:00 102.92 14-AUG-01:00
September 2010.83 01-SEP-09:09 820.66 18-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 40.54 10-SEP-15:05 66.59 24-SEP-10:33
October 2010.83 02-OCT-09:09 1167.32 13-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 52.42 01-OCT-14:58 169.59 24-OCT-02:00
November 2010.83 01-NOV-09:09 1334.88 22-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 244.60 26-NOV-09:00
December 2010.83 01-DEC-10:09 1334.88 01-DEC-16:00 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 307.95 18-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   667.41   2160.58   0.00 0.00 0.00 0.00 0.00   63.74  
Maximum of Months 2010.83   1334.88   2160.58   0.00 0.00 0.00 0.00 125.97   452.14  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 807.90 17-JAN-16:00 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 253.78 25-JAN-24:00
February 1295.83 01-FEB-10:09 703.28 03-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 319.41 09-FEB-01:00
March 1295.83 01-MAR-10:09 685.19 10-MAR-16:00 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 2.09 22-MAR-13:00 280.96 19-MAR-24:00
April 1295.83 03-APR-09:09 610.58 20-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 30.52 21-APR-15:00 273.77 10-APR-24:00
May 1295.83 01-MAY-09:09 472.49 03-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 67.77 14-MAY-15:44 133.94 04-MAY-02:00
June 1295.83 01-JUN-09:09 453.16 29-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 63.30 04-JUN-18:53 94.36 28-JUN-01:53
July 1295.83 03-JUL-09:09 598.90 07-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 87.44 02-JUL-21:08 53.25 04-JUL-19:30
August 1295.83 01-AUG-09:09 617.33 24-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 47.44 27-AUG-13:06 81.24 14-AUG-01:00
September 1295.83 01-SEP-09:09 613.21 18-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 27.05 10-SEP-15:03 45.80 24-SEP-07:00
October 1295.83 02-OCT-09:09 759.77 13-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 34.95 01-OCT-14:58 122.45 24-OCT-02:00
November 1295.83 01-NOV-09:09 860.23 22-NOV-16:00 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 171.00 26-NOV-14:00
December 1295.83 01-DEC-10:09 860.23 01-DEC-16:00 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 231.31 18-DEC-05:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   453.16   1392.33   0.00 0.00 0.00 0.00 0.00   45.80  
Maximum of Months 1295.83   860.23   1392.33   0.00 0.00 0.00 0.00 87.44   319.41  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1263.05 17-JAN-16:00 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 754.95 25-JAN-23:00
February 2010.79 01-FEB-10:09 1149.77 01-FEB-16:00 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 24.12 20-FEB-15:50 963.63 09-FEB-01:00
March 2010.79 01-MAR-10:09 1108.48 10-MAR-16:00 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 24.34 19-MAR-14:35 733.93 19-MAR-24:00
April 2010.79 03-APR-09:09 887.98 20-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 158.65 01-APR-17:02 793.41 10-APR-24:00
May 2010.79 01-MAY-09:09 701.98 23-MAY-12:30 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 260.98 14-MAY-16:00 375.69 04-MAY-02:00
June 2010.79 01-JUN-09:09 635.12 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 244.53 04-JUN-19:00 287.33 28-JUN-01:53
July 2010.79 03-JUL-09:09 855.90 07-JUL-07:30 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 292.19 02-JUL-21:00 138.93 18-JUL-21:10
August 2010.79 01-AUG-09:09 845.34 17-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 190.31 26-AUG-18:00 221.53 14-AUG-01:00
September 2010.79 01-SEP-09:09 932.07 29-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 112.15 10-SEP-15:10 135.99 24-SEP-07:00
October 2010.79 02-OCT-09:09 1177.14 13-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 163.67 01-OCT-14:52 351.93 24-OCT-02:00
November 2010.79 01-NOV-09:09 1334.85 22-NOV-16:00 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 449.71 26-NOV-09:00
December 2010.79 01-DEC-10:09 1334.85 01-DEC-16:00 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 599.97 18-DEC-05:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   635.12   2160.55   0.00 0.00 0.00 0.00 0.00   135.99  
Maximum of Months 2010.79   1334.85   2160.55   0.00 0.00 0.00 0.00 292.19   963.63  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 814.16 17-JAN-16:00 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 503.79 25-JAN-23:00
February 1239.33 01-FEB-08:09 750.64 13-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 651.90 09-FEB-01:00
March 1239.33 01-MAR-08:09 721.39 10-MAR-16:00 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 4.36 22-MAR-13:00 530.17 19-MAR-24:00
April 1239.33 03-APR-07:10 471.34 20-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 88.92 01-APR-17:02 537.36 10-APR-24:00
May 1239.33 01-MAY-07:10 461.12 24-MAY-15:39 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 168.73 14-MAY-15:50 251.49 04-MAY-02:00
June 1239.33 01-JUN-07:10 446.07 19-JUN-15:00 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 166.77 04-JUN-19:00 195.20 28-JUN-01:53
July 1239.33 03-JUL-07:10 474.63 03-JUL-15:00 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 194.39 02-JUL-21:00 91.76 18-JUL-21:10
August 1239.33 01-AUG-07:10 529.15 16-AUG-15:00 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 124.69 26-AUG-17:50 155.58 14-AUG-01:00
September 1239.33 01-SEP-07:10 526.28 29-SEP-15:00 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 66.31 10-SEP-15:10 107.90 24-SEP-10:00
October 1239.33 02-OCT-07:10 746.37 13-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 91.22 01-OCT-14:52 240.42 24-OCT-02:00
November 1239.33 01-NOV-07:10 860.23 22-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 345.67 26-NOV-09:00
December 1239.33 01-DEC-08:09 860.23 01-DEC-16:00 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 411.49 18-DEC-05:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   446.07   1392.34   0.00 0.00 0.00 0.00 0.00   91.76  
Maximum of Months 1239.33   860.23   1392.34   0.00 0.00 0.00 0.00 194.39   651.90  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1258.31 17-JAN-16:00 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 787.29 25-JAN-23:00
February 2010.83 01-FEB-10:09 1099.53 23-FEB-16:00 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1011.57 09-FEB-01:00
March 2010.83 01-MAR-10:09 1097.82 10-MAR-16:00 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 6.53 22-MAR-13:00 837.24 19-MAR-24:00
April 2010.83 03-APR-09:09 887.18 20-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 116.21 01-APR-17:02 811.85 10-APR-24:00
May 2010.83 01-MAY-09:09 707.08 03-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 243.50 14-MAY-16:00 381.33 04-MAY-02:00
June 2010.83 01-JUN-09:09 663.69 29-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 243.59 04-JUN-19:00 284.58 28-JUN-01:53
July 2010.83 03-JUL-09:09 879.57 07-JUL-07:30 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 292.50 02-JUL-21:00 141.01 18-JUL-21:10
August 2010.83 01-AUG-09:09 864.90 17-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 179.92 26-AUG-18:00 236.35 14-AUG-00:57
September 2010.83 01-SEP-09:09 822.65 18-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 90.52 10-SEP-15:05 153.26 24-SEP-10:47
October 2010.83 02-OCT-09:09 1170.94 13-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 111.94 01-OCT-14:52 382.52 23-OCT-21:10
November 2010.83 01-NOV-09:09 1334.88 22-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 539.21 26-NOV-09:00
December 2010.83 01-DEC-10:09 1334.88 01-DEC-16:00 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 683.65 18-DEC-05:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   663.69   2160.58   0.00 0.00 0.00 0.00 0.00   141.01  
Maximum of Months 2010.83   1334.88   2160.58   0.00 0.00 0.00 0.00 292.50   1011.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 808.14 17-JAN-16:00 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 512.96 25-JAN-23:00
February 1295.83 01-FEB-10:09 703.20 03-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 665.20 09-FEB-01:00
March 1295.83 01-MAR-10:09 686.39 10-MAR-16:00 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 4.36 22-MAR-13:00 548.79 19-MAR-24:00
April 1295.83 03-APR-09:09 611.02 20-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 70.61 21-APR-15:00 548.68 10-APR-24:00
May 1295.83 01-MAY-09:09 470.75 03-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 149.63 14-MAY-16:00 270.03 04-MAY-02:00
June 1295.83 01-JUN-09:09 450.77 29-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 168.25 04-JUN-18:57 214.53 28-JUN-01:53
July 1295.83 03-JUL-09:09 598.93 07-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 190.48 02-JUL-21:00 112.21 04-JUL-19:20
August 1295.83 01-AUG-09:09 617.31 24-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 120.13 27-AUG-12:52 173.11 14-AUG-01:00
September 1295.83 01-SEP-09:09 613.04 18-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 61.34 10-SEP-15:03 93.89 24-SEP-07:00
October 1295.83 02-OCT-09:09 759.96 13-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 77.01 01-OCT-15:05 253.02 24-OCT-02:00
November 1295.83 01-NOV-09:09 860.23 22-NOV-16:00 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 322.36 26-NOV-09:00
December 1295.83 01-DEC-10:09 860.23 01-DEC-16:00 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 434.94 18-DEC-05:22
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   450.77   1392.33   0.00 0.00 0.00 0.00 0.00   93.89  
Maximum of Months 1295.83   860.23   1392.33   0.00 0.00 0.00 0.00 190.48   665.20  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1262.96 17-JAN-16:00 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 854.60 25-JAN-23:00
February 2010.79 01-FEB-10:09 1149.90 01-FEB-16:00 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 49.85 20-FEB-16:00 1108.70 09-FEB-01:00
March 2010.79 01-MAR-10:09 1108.23 10-MAR-16:00 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 54.69 19-MAR-14:48 811.54 19-MAR-24:00
April 2010.79 03-APR-09:09 887.54 20-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 198.05 01-APR-17:02 932.80 10-APR-24:00
May 2010.79 01-MAY-09:09 701.77 23-MAY-12:30 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 293.28 14-MAY-15:50 445.07 04-MAY-02:00
June 2010.79 01-JUN-09:09 635.12 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 305.20 04-JUN-19:00 364.44 28-JUN-01:53
July 2010.79 03-JUL-09:09 855.39 07-JUL-07:30 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 337.24 02-JUL-21:30 182.72 04-JUL-19:20
August 2010.79 01-AUG-09:09 844.88 17-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 219.67 26-AUG-17:50 290.17 14-AUG-01:00
September 2010.79 01-SEP-09:09 932.30 29-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 120.68 10-SEP-15:00 166.30 23-SEP-17:10
October 2010.79 02-OCT-09:09 1176.95 13-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 194.54 01-OCT-15:00 413.48 23-OCT-21:10
November 2010.79 01-NOV-09:09 1334.85 22-NOV-16:00 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 5.14 23-NOV-15:40 463.09 04-NOV-03:55
December 2010.79 01-DEC-10:09 1334.85 01-DEC-16:00 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 765.10 18-DEC-05:45
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   635.12   2160.55   0.00 0.00 0.00 0.00 0.00   166.30  
Maximum of Months 2010.79   1334.85   2160.55   0.00 0.00 0.00 0.00 337.24   1108.70  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 814.11 17-JAN-16:00 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 572.46 25-JAN-23:00
February 1295.83 01-FEB-10:09 750.55 13-FEB-16:00 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 3.95 20-FEB-16:00 755.23 09-FEB-01:00
March 1295.83 01-MAR-10:09 721.24 10-MAR-16:00 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 4.75 22-MAR-13:00 597.43 19-MAR-24:00
April 1295.83 03-APR-09:09 471.24 20-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 105.28 01-APR-17:02 634.74 10-APR-24:00
May 1295.83 01-MAY-09:09 461.02 24-MAY-15:39 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 204.87 14-MAY-15:48 298.83 04-MAY-02:00
June 1295.83 01-JUN-09:09 445.93 19-JUN-15:00 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 209.25 04-JUN-18:57 247.89 28-JUN-01:53
July 1295.83 03-JUL-09:09 474.53 03-JUL-15:00 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 226.44 02-JUL-21:30 131.79 04-JUL-19:20
August 1295.83 01-AUG-09:09 528.78 16-AUG-15:00 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 143.82 26-AUG-17:50 200.08 14-AUG-01:00
September 1295.83 01-SEP-09:09 526.52 29-SEP-15:00 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 81.44 10-SEP-14:40 134.01 24-SEP-10:30
October 1295.83 02-OCT-09:09 746.26 13-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 115.41 01-OCT-15:00 285.53 23-OCT-21:10
November 1295.83 01-NOV-09:09 860.23 22-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 357.03 26-NOV-09:00
December 1295.83 01-DEC-10:09 860.23 01-DEC-16:00 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 510.03 18-DEC-05:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   445.93   1392.34   0.00 0.00 0.00 0.00 0.00   131.79  
Maximum of Months 1295.83   860.23   1392.34   0.00 0.00 0.00 0.00 226.44   755.23  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1258.23 17-JAN-16:00 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 883.73 25-JAN-23:00
February 2010.83 01-FEB-10:09 1099.30 23-FEB-16:00 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1176.40 09-FEB-01:00
March 2010.83 01-MAR-10:09 1097.57 10-MAR-16:00 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 7.13 22-MAR-13:00 950.61 19-MAR-24:00
April 2010.83 03-APR-09:09 886.73 20-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 139.57 01-APR-17:02 958.00 10-APR-24:00
May 2010.83 01-MAY-09:09 706.88 03-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 293.25 14-MAY-15:48 452.35 04-MAY-02:00
June 2010.83 01-JUN-09:09 663.42 29-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 305.01 04-JUN-19:00 360.70 28-JUN-01:53
July 2010.83 03-JUL-09:09 879.06 07-JUL-07:30 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 337.33 02-JUL-21:30 182.56 18-JUL-21:10
August 2010.83 01-AUG-09:09 864.44 17-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 206.47 26-AUG-17:50 305.47 14-AUG-01:00
September 2010.83 01-SEP-09:09 822.86 18-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 108.56 10-SEP-15:15 189.87 24-SEP-10:50
October 2010.83 02-OCT-09:09 1170.75 13-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 147.18 01-OCT-15:00 466.30 23-OCT-21:10
November 2010.83 01-NOV-09:09 1334.88 22-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 566.22 26-NOV-09:00
December 2010.83 01-DEC-10:09 1334.88 01-DEC-16:00 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 765.07 18-DEC-05:45
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   663.42   2160.58   0.00 0.00 0.00 0.00 0.00   182.56  
Maximum of Months 2010.83   1334.88   2160.58   0.00 0.00 0.00 0.00 337.33   1176.40  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 808.09 17-JAN-16:00 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 589.63 25-JAN-23:00
February 1295.83 01-FEB-10:09 703.32 03-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 773.96 09-FEB-01:00
March 1295.83 01-MAR-10:09 686.25 10-MAR-16:00 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 4.75 22-MAR-13:00 630.46 19-MAR-24:00
April 1295.83 03-APR-09:09 610.75 20-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 86.49 21-APR-15:00 649.08 10-APR-24:00
May 1295.83 01-MAY-09:09 470.65 03-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 182.00 14-MAY-16:00 322.40 04-MAY-02:00
June 1295.83 01-JUN-09:09 450.64 29-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 209.33 04-JUN-18:57 272.21 28-JUN-01:53
July 1295.83 03-JUL-09:09 598.74 07-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 227.68 02-JUL-21:30 152.16 04-JUL-19:20
August 1295.83 01-AUG-09:09 617.15 24-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 146.59 27-AUG-12:52 217.85 14-AUG-01:00
September 1295.83 01-SEP-09:09 613.24 18-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 77.46 10-SEP-14:38 119.52 04-SEP-19:57
October 1295.83 02-OCT-09:09 759.85 13-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 99.88 01-OCT-14:55 303.72 23-OCT-21:10
November 1295.83 01-NOV-09:09 860.23 22-NOV-16:00 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 342.21 26-NOV-09:00
December 1295.83 01-DEC-10:09 860.23 01-DEC-16:00 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 510.05 18-DEC-05:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   450.64   1392.33   0.00 0.00 0.00 0.00 0.00   119.52  
Maximum of Months 1295.83   860.23   1392.33   0.00 0.00 0.00 0.00 227.68   773.96  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 284.97 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 284.97 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 284.97 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 284.97 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 284.97 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 284.97 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 284.97 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 284.97 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 284.97 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 284.97 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 284.97 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 284.97 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   284.97   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   284.97   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 284.97 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 284.97 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 284.97 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 284.97 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 284.97 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 284.97 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 284.97 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 284.97 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 284.97 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 284.97 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 284.97 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 284.97 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   284.97   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   284.97   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 284.97 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 284.97 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 284.97 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 284.97 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 284.97 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 284.97 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 284.97 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 284.97 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 284.97 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 284.97 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 284.97 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 284.97 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   284.97   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   284.97   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 3337.76 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 3337.76 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 3337.76 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 3337.76 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 3337.76 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 3337.76 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 3337.76 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 3337.76 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 3337.76 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 3337.76 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 3337.76 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 3337.76 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   3337.76   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   3337.76   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 772.08 25-JAN-24:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 962.12 09-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.98 22-MAR-13:00 775.99 19-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 102.28 01-APR-17:02 772.29 10-APR-24:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 227.85 14-MAY-16:00 353.34 04-MAY-02:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 214.15 04-JUN-19:00 252.30 28-JUN-01:55
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 247.15 02-JUL-20:53 125.71 18-JUL-21:10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 157.71 27-AUG-12:52 200.94 14-AUG-01:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 89.48 10-SEP-14:52 128.82 24-SEP-07:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 118.85 01-OCT-15:00 350.07 24-OCT-02:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 483.75 26-NOV-09:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 668.98 18-DEC-05:04
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   125.71  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 247.15   962.12  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 1324.03 25-JAN-24:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1685.24 09-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.75 22-MAR-13:00 1310.71 19-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 214.87 01-APR-17:02 1356.49 10-APR-24:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 420.06 14-MAY-16:00 617.79 04-MAY-02:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 383.03 04-JUN-19:00 451.33 28-JUN-01:53
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 474.70 02-JUL-21:10 219.87 18-JUL-21:10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 294.02 27-AUG-13:00 346.91 14-AUG-01:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 170.29 10-SEP-14:52 227.00 24-SEP-07:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 228.51 01-OCT-14:52 612.66 24-OCT-02:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 815.39 26-NOV-09:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1097.06 18-DEC-05:52
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   219.87  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 474.70   1685.24  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 1314.24 25-JAN-23:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1717.47 09-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1277.82 19-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 209.23 01-APR-17:02 1390.99 10-APR-24:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 340.56 14-MAY-16:00 639.78 04-MAY-02:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 354.65 04-JUN-19:00 539.67 28-JUN-01:53
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 476.28 02-JUL-21:10 270.61 18-JUL-21:10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 286.59 26-AUG-18:00 429.08 14-AUG-00:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 131.61 10-SEP-15:00 260.74 23-SEP-17:10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 205.60 01-OCT-15:00 648.33 23-OCT-21:03
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 735.61 26-NOV-14:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1027.74 18-DEC-05:50
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   260.74  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 476.28   1717.47  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 95628.38 17-JAN-04:02 0.00 3288.60 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
February 93229.87 13-FEB-04:12 0.00 2630.88 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
March 89680.53 23-MAR-04:12 0.00 5261.11 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
April 93253.36 03-APR-03:02 0.00 2630.88 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
May 94455.52 15-MAY-03:02 0.00 3288.60 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
June 94964.22 12-JUN-03:02 0.00 2630.88 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
July 87525.15 11-JUL-03:02 0.00 3288.60 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
August 94066.56 28-AUG-03:02 0.00 3288.60 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
September 95430.64 11-SEP-03:02 0.00 3288.60 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
October 95939.89 30-OCT-03:02 0.00 2630.88 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
November 98069.63 27-NOV-04:01 0.00 4604.05 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
December 95764.54 18-DEC-04:03 0.00 2630.88 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 87525.15   0.00 2630.88 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 98069.63   0.00 5261.11 94202.81 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 80524.87 02-JAN-04:03 0.00 2362.72 23750.58 0.00 0.00 0.00 0.00 0.00 0.00
February 77624.49 27-FEB-05:02 0.00 7087.27 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
March 76469.11 28-MAR-04:03 0.00 4724.85 23750.58 0.00 0.00 0.00 0.00 0.00 0.00
April 78533.24 18-APR-03:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
May 77747.37 22-MAY-03:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
June 70839.36 29-JUN-05:03 6448.95 4724.85 30589.56 0.00 0.00 0.00 0.00 0.00 0.00
July 77510.12 17-JUL-05:04 8061.19 5906.06 38236.95 0.00 0.00 0.00 0.00 0.00 0.00
August 78956.25 14-AUG-05:04 8061.19 5906.06 38236.95 0.00 0.00 0.00 0.00 0.00 0.00
September 81319.50 25-SEP-03:02 0.00 2362.72 23750.58 0.00 0.00 0.00 0.00 0.00 0.00
October 83572.02 10-OCT-03:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
November 84521.39 13-NOV-04:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
December 83889.43 26-DEC-04:01 0.00 5316.12 53438.81 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 70839.36   0.00 2362.72 23750.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 84521.39   8061.19 7087.27 53438.81 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 64880.59 13-JAN-06:03 6448.95 4724.85 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
February 68893.60 23-FEB-06:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
March 71226.64 17-MAR-05:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
April 71556.12 11-APR-05:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
May 72039.15 25-MAY-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
June 71478.90 28-JUN-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
July 72075.33 19-JUL-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
August 73933.50 30-AUG-05:04 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
September 71547.37 05-SEP-05:04 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
October 72349.66 07-OCT-05:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
November 69677.44 09-NOV-06:03 6448.95 4724.85 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
December 48104.39 14-DEC-06:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 48104.39   0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 73933.50   8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 21780.73 12-JAN-17:00 15316.26 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
February 27462.56 08-FEB-15:00 16014.58 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
March 61035.88 16-MAR-05:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
April 69652.57 21-APR-05:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
May 70592.43 25-MAY-05:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
June 71568.52 28-JUN-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
July 75399.75 05-JUL-03:02 0.00 2953.40 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
August 67793.29 17-AUG-05:03 6448.95 4724.85 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
September 69576.53 08-SEP-05:03 6448.95 4724.85 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
October 69453.30 19-OCT-05:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
November 55948.13 10-NOV-06:03 6448.95 4724.85 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
December 17289.76 01-DEC-17:00 15316.26 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17289.76   0.00 2953.40 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 75399.75   16014.58 10631.20 38236.81 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3003.47 02-JAN-15:00 2010.79 827.14 2160.55 0.00 0.00 0.00 0.00 0.00 10.07
February 4712.91 21-FEB-15:00 2010.79 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 3.14
March 5446.07 15-MAR-13:50 2010.79 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 2.43
April 10484.41 03-APR-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 4.35
May 11671.95 15-MAY-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 0.33
June 12145.27 26-JUN-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 3.33
July 14274.11 03-JUL-03:02 0.00 444.99 4473.37 0.00 0.00 0.00 0.00 17.36 0.00
August 14190.55 07-AUG-03:02 0.00 444.99 4473.37 0.00 0.00 0.00 0.00 8.49 0.00
September 11949.89 11-SEP-05:03 809.73 593.25 3840.98 0.00 0.00 0.00 0.00 0.00 8.82
October 11989.48 02-OCT-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 0.36
November 4854.15 09-NOV-15:00 2010.79 797.31 2160.55 0.00 0.00 0.00 0.00 0.00 1.41
December 3534.15 11-DEC-12:00 1923.11 674.78 2160.55 0.00 0.00 0.00 0.00 0.00 41.46
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3003.47   0.00 444.99 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14274.11   2010.79 827.14 4801.23 0.00 0.00 0.00 0.00 17.36 41.46



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4675.73 04-JAN-09:20 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 23.10
February 6775.01 21-FEB-08:40 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 3.65
March 7005.87 07-MAR-09:00 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 17.22
April 15362.94 30-APR-08:32 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 0.00 12.75
May 15632.32 29-MAY-08:12 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 0.00 23.79
June 15064.47 04-JUN-07:53 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 0.00
July 15055.55 04-JUL-07:33 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 6.12
August 15281.20 20-AUG-09:02 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 0.00 1.61
September 15736.90 04-SEP-08:12 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 0.00 18.05
October 9767.22 22-OCT-08:53 195.68 68.22 1392.34 0.00 0.00 0.00 0.00 0.00 20.25
November 7399.90 10-NOV-08:40 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 17.72
December 3670.41 07-DEC-09:15 2478.65 818.60 2784.68 0.00 0.00 0.00 0.00 0.00 2.65
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3670.41   195.68 68.22 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15736.90   2478.65 818.60 2784.68 0.00 0.00 0.00 0.00 0.00 23.79



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 17696.01 01-JAN-13:53 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 85.12
February 18038.60 20-FEB-13:13 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 52.45
March 13565.46 26-MAR-14:32 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 69.81
April 17323.78 30-APR-13:13 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 8.49 0.00
May 14732.33 29-MAY-14:52 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 25.64 0.00
June 13278.74 26-JUN-05:02 1012.19 741.58 4801.30 0.00 0.00 0.00 0.00 0.00 3.17
July 17308.08 30-JUL-13:02 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 15.76 0.00
August 17523.55 27-AUG-13:02 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 61.91 0.00
September 18115.47 17-SEP-12:32 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 13.09 0.00
October 19125.15 01-OCT-12:42 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 6.67 0.00
November 18616.62 11-NOV-13:02 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 65.23
December 15573.05 17-DEC-12:53 303.66 105.87 2160.58 0.00 0.00 0.00 0.00 0.00 47.46
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 13278.74   303.66 105.87 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19125.15   1012.19 741.58 4801.30 0.00 0.00 0.00 0.00 61.91 85.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7005.85 02-JAN-15:30 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 8.02
February 16464.83 19-FEB-15:23 260.91 90.96 1856.44 0.00 0.00 0.00 0.00 0.00 20.62
March 17663.12 26-MAR-16:32 326.14 113.70 2320.55 0.00 0.00 0.00 0.00 0.00 26.09
April 20902.46 30-APR-16:31 456.59 159.19 3248.78 0.00 0.00 0.00 0.00 9.69 0.00
May 21474.65 29-MAY-15:31 456.59 159.19 3248.78 0.00 0.00 0.00 0.00 24.91 0.00
June 20507.62 25-JUN-16:22 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 15.21 0.00
July 20701.02 09-JUL-16:42 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 12.53 0.00
August 21300.80 13-AUG-16:21 521.82 181.93 3712.89 0.00 0.00 0.00 0.00 9.41 0.00
September 21405.78 10-SEP-15:41 456.59 159.19 3248.78 0.00 0.00 0.00 0.00 15.02 0.00
October 20807.93 01-OCT-14:42 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 25.11 0.00
November 16821.08 19-NOV-15:43 260.91 90.96 1856.44 0.00 0.00 0.00 0.00 0.00 2.30
December 11434.12 11-DEC-05:02 0.00 573.47 2882.79 0.00 0.00 0.00 0.00 0.00 58.42
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7005.85   0.00 90.96 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21474.65   1239.33 573.47 3712.89 0.00 0.00 0.00 0.00 25.11 58.42



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2491.49 12-JAN-15:10 1923.11 684.25 2160.55 0.00 0.00 0.00 0.00 0.00 2.15
February 2649.95 22-FEB-13:40 1923.11 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 0.96
March 3833.86 22-MAR-14:40 1923.11 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 0.34
April 8870.73 20-APR-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 17.84
May 10690.03 23-MAY-05:03 809.73 593.25 3840.98 0.00 0.00 0.00 0.00 0.00 6.80
June 11496.68 15-JUN-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 6.90 0.00
July 14168.37 04-JUL-16:01 809.73 282.30 5761.47 0.00 0.00 0.00 0.00 67.70 0.00
August 12999.85 07-AUG-05:03 1214.60 889.88 5761.47 0.00 0.00 0.00 0.00 7.76 0.00
September 10428.71 14-SEP-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 6.84
October 9453.43 05-OCT-05:03 809.73 593.25 3840.98 0.00 0.00 0.00 0.00 0.00 3.25
November 3149.37 09-NOV-16:00 1923.11 993.82 2160.55 0.00 0.00 0.00 0.00 0.00 7.19
December 2119.21 07-DEC-14:20 2010.79 677.23 2160.55 0.00 0.00 0.00 0.00 0.00 31.97
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2119.21   809.73 282.30 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14168.37   2010.79 993.82 5761.47 0.00 0.00 0.00 0.00 67.70 31.97



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2876.06 04-JAN-09:50 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 60.69
February 4642.07 21-FEB-10:00 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 14.35
March 6193.69 07-MAR-09:30 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 46.55
April 16110.23 30-APR-09:02 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 0.00 27.64
May 16165.86 29-MAY-09:32 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 0.00 32.93
June 15962.88 11-JUN-09:02 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 0.00 11.08
July 16091.23 02-JUL-08:12 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 0.21 0.00
August 16149.03 06-AUG-10:12 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 27.19 0.00
September 16164.00 04-SEP-09:02 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 0.00 26.13
October 8766.12 05-OCT-08:30 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 0.26
November 6514.21 10-NOV-08:50 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 38.65
December 1999.83 07-DEC-13:50 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 28.50
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1999.83   326.14 113.70 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16165.86   1239.33 409.30 2320.57 0.00 0.00 0.00 0.00 27.19 60.69



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 15419.25 01-JAN-12:43 303.66 105.87 2160.58 0.00 0.00 0.00 0.00 0.00 193.03
February 17304.53 20-FEB-14:22 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 90.14
March 12613.21 19-MAR-13:43 303.66 105.87 2160.58 0.00 0.00 0.00 0.00 0.00 104.51
April 16180.39 30-APR-13:02 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 20.87 0.00
May 11879.95 01-MAY-05:02 1012.19 741.58 4801.30 0.00 0.00 0.00 0.00 0.00 23.29
June 12670.42 15-JUN-05:02 1012.19 741.58 4801.30 0.00 0.00 0.00 0.00 7.24 0.00
July 15948.94 04-JUL-16:01 809.75 282.31 5761.56 0.00 0.00 0.00 0.00 66.30 0.00
August 16148.61 06-AUG-14:51 809.75 282.31 5761.56 0.00 0.00 0.00 0.00 114.93 0.00
September 17085.21 17-SEP-12:32 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 28.60 0.00
October 17709.30 22-OCT-12:42 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 3.72
November 17621.04 11-NOV-12:52 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 151.29
December 16496.86 17-DEC-14:02 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 197.08
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11879.95   303.66 105.87 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17709.30   1012.19 741.58 5761.56 0.00 0.00 0.00 0.00 114.93 197.08



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4709.38 12-JAN-15:30 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 5.82
February 6811.38 21-FEB-16:50 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 3.90
March 8407.45 21-MAR-16:00 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 3.31 0.00
April 17270.99 30-APR-16:21 587.05 204.67 4177.00 0.00 0.00 0.00 0.00 25.32 0.00
May 18042.14 29-MAY-15:31 456.59 159.19 3248.78 0.00 0.00 0.00 0.00 56.66 0.00
June 17955.67 11-JUN-17:41 0.00 159.19 2522.44 0.00 0.00 0.00 0.00 50.00 0.00
July 18075.95 04-JUL-16:01 521.82 181.93 3712.89 0.00 0.00 0.00 0.00 31.66 0.00
August 17628.59 06-AUG-16:51 587.05 204.67 4177.00 0.00 0.00 0.00 0.00 75.28 0.00
September 17775.62 10-SEP-15:41 456.59 159.19 3248.78 0.00 0.00 0.00 0.00 35.12 0.00
October 15139.38 22-OCT-15:22 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 0.15 0.00
November 7558.71 09-NOV-15:30 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 3.67
December 4058.82 15-DEC-16:00 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 30.22
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4058.82   0.00 136.45 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18075.95   1239.33 409.30 4177.00 0.00 0.00 0.00 0.00 75.28 30.22



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2048.76 12-JAN-14:30 2010.79 687.84 2160.55 0.00 0.00 0.00 0.00 0.00 3.25
February 2231.42 07-FEB-14:20 2010.79 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 22.81
March 3808.45 16-MAR-15:40 1923.11 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 18.52
April 7774.72 20-APR-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 22.57
May 12563.09 31-MAY-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 0.59
June 16513.35 18-JUN-15:32 607.30 211.73 4321.10 0.00 0.00 0.00 0.00 97.37 0.00
July 17270.07 04-JUL-16:01 809.73 282.30 5761.47 0.00 0.00 0.00 0.00 74.47 0.00
August 16607.03 06-AUG-16:41 809.73 282.30 5761.47 0.00 0.00 0.00 0.00 143.64 0.00
September 8608.07 14-SEP-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 8.52
October 7497.44 05-OCT-05:03 809.73 593.25 3840.98 0.00 0.00 0.00 0.00 0.00 4.17
November 2977.79 09-NOV-16:00 1923.11 994.03 2160.55 0.00 0.00 0.00 0.00 0.00 10.13
December 1663.39 01-DEC-15:00 2010.79 684.04 2160.55 0.00 0.00 0.00 0.00 0.00 60.01
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1663.39   607.30 211.73 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17270.07   2010.79 994.03 5761.47 0.00 0.00 0.00 0.00 143.64 60.01



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1920.51 12-JAN-14:30 1295.83 441.48 1392.34 0.00 0.00 0.00 0.00 0.00 2.61
February 3084.57 21-FEB-10:30 1295.83 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 17.42
March 5377.92 16-MAR-10:00 1295.83 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 31.17
April 15794.16 30-APR-08:62 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 39.93
May 15587.18 29-MAY-11:02 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 0.96
June 15867.62 18-JUN-09:32 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 33.88 0.00
July 17323.16 02-JUL-09:22 391.37 136.45 2784.68 0.00 0.00 0.00 0.00 0.00 0.00
August 17139.43 06-AUG-09:22 391.37 136.45 2784.68 0.00 0.00 0.00 0.00 8.35 0.00
September 15862.86 04-SEP-07:53 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 57.43
October 8480.59 05-OCT-08:40 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.08 0.00
November 5725.27 10-NOV-09:20 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 38.57
December 1570.37 01-DEC-10:20 1295.83 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 37.31
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1570.37   260.91 90.96 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17323.16   1295.83 441.48 2784.68 0.00 0.00 0.00 0.00 33.88 57.43



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 12762.26 12-JAN-14:30 2010.83 635.14 2160.58 0.00 0.00 0.00 0.00 0.00 4.87
February 18382.61 20-FEB-13:13 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 144.42
March 11725.15 16-MAR-14:10 1923.15 635.14 2160.58 0.00 0.00 0.00 0.00 0.00 19.31
April 16907.70 16-APR-15:32 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 24.04 0.00
May 13721.60 31-MAY-05:02 1012.19 741.58 4801.30 0.00 0.00 0.00 0.00 0.00 0.66
June 16996.95 18-JUN-12:53 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 116.68 0.00
July 18846.28 04-JUL-16:01 809.75 282.31 5761.56 0.00 0.00 0.00 0.00 74.17 0.00
August 19009.77 06-AUG-14:02 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 89.18 0.00
September 19209.64 04-SEP-12:32 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 14.92 0.00
October 20657.82 01-OCT-13:32 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 29.55 0.00
November 18991.06 11-NOV-12:32 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 167.60
December 10440.49 07-DEC-14:30 2010.83 635.14 2160.58 0.00 0.00 0.00 0.00 0.00 50.05
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10440.49   404.87 141.16 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20657.82   2010.83 741.58 5761.56 0.00 0.00 0.00 0.00 116.68 167.60



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4128.43 12-JAN-15:30 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 7.38
February 6367.73 21-FEB-16:50 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 5.13
March 9401.81 26-MAR-17:02 0.00 136.45 2162.09 0.00 0.00 0.00 0.00 0.00 66.56
April 19109.07 16-APR-15:32 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 8.87 0.00
May 18929.32 29-MAY-16:22 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 104.71 0.00
June 18972.93 25-JUN-17:02 0.00 136.45 2162.09 0.00 0.00 0.00 0.00 44.58 0.00
July 20384.66 04-JUL-16:01 521.82 181.93 3712.89 0.00 0.00 0.00 0.00 35.27 0.00
August 19422.53 06-AUG-16:41 521.82 181.93 3712.89 0.00 0.00 0.00 0.00 80.74 0.00
September 18283.15 17-SEP-15:32 326.14 113.70 2320.55 0.00 0.00 0.00 0.00 51.68 0.00
October 18594.99 01-OCT-14:52 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 84.72 0.00
November 7469.31 09-NOV-15:40 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 5.70
December 3065.79 15-DEC-16:10 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 39.01
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3065.79   0.00 113.70 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20384.66   1239.33 409.30 3712.89 0.00 0.00 0.00 0.00 104.71 66.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5469.12 02-JAN-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.10
February 5021.21 21-FEB-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35.98
March 4586.56 14-MAR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 46.36
April 6491.43 03-APR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.59
May 8583.08 30-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.25
June 9063.52 19-JUN-05:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.96
July 12698.17 31-JUL-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.30
August 14035.15 07-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29 0.00
September 12408.56 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.82
October 8795.80 10-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31.85
November 6983.34 13-NOV-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 61.82
December 4552.42 11-DEC-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27.22
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4552.42   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14035.15   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29 61.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4509.08 28-JAN-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 178.62
February 4778.94 02-FEB-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 122.32
March 4986.38 02-MAR-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 89.87
April 4749.87 21-APR-15:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 120.59 0.00
May 6367.77 30-MAY-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 55.97 0.00
June 7719.60 02-JUN-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.02
July 7327.87 14-JUL-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.20
August 6704.89 09-AUG-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.21
September 7652.33 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.42
October 5591.05 05-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.91
November 3919.90 28-NOV-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 133.99
December 4422.82 19-DEC-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3919.90   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7719.60   0.00 0.00 0.00 0.00 0.00 0.00 0.00 120.59 178.62



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2760.93 01-JAN-14:43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 277.90
February 5441.27 07-FEB-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 48.09
March 9033.83 16-MAR-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 48.67
April 15292.02 28-APR-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.03 0.00
May 18497.02 30-MAY-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.20 0.00
June 20124.53 15-JUN-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 118.48 0.00
July 20660.78 03-JUL-12:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.25 0.00
August 19225.22 07-AUG-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.34 0.00
September 16048.63 15-SEP-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.92 0.00
October 13837.79 03-OCT-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.28 0.00
November 6854.05 09-NOV-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.82
December 1899.50 09-DEC-13:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.94
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1899.50   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20660.78   0.00 0.00 0.00 0.00 0.00 0.00 0.00 118.48 277.90



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1961.02 01-JAN-16:45 23.38 31.66 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
February 3982.11 20-FEB-17:30 23.38 31.66 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
March 7120.68 31-MAR-24:00 0.00 15.83 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7794.88 30-APR-19:03 0.00 63.33 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
May 3464.77 31-MAY-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5329.71 30-JUN-23:45 0.00 31.66 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
July 7276.26 31-JUL-23:53 0.00 47.50 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7740.74 27-AUG-19:42 0.00 63.33 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
September 3494.76 30-SEP-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5296.49 31-OCT-24:00 0.00 15.83 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5948.04 12-NOV-16:50 23.38 31.66 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
December 7646.95 18-DEC-16:40 222.14 284.97 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1961.02   0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7794.88   222.14 284.97 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1674.38 19-JAN-17:00 222.14 284.97 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3593.75 21-FEB-17:00 222.14 284.97 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6608.25 31-MAR-24:00 0.00 15.83 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7386.65 30-APR-18:43 0.00 47.50 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
May 3401.19 31-MAY-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5181.51 30-JUN-23:53 0.00 63.33 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
July 6988.19 31-JUL-23:53 0.00 47.50 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7329.35 31-AUG-17:50 23.38 94.99 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3261.65 30-SEP-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4869.65 31-OCT-24:00 0.00 15.83 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5529.44 09-NOV-16:50 222.14 284.97 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7124.72 15-DEC-16:50 222.14 284.97 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1674.38   0.00 15.83 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7386.65   222.14 284.97 23383.27 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1580.88 12-JAN-16:50 222.14 284.97 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3562.25 21-FEB-17:00 222.14 284.97 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6297.68 31-MAR-23:20 0.00 15.83 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7537.34 30-APR-19:03 0.00 63.33 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
May 3400.79 31-MAY-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5192.68 30-JUN-23:45 0.00 31.66 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
July 7010.65 31-JUL-23:53 0.00 47.50 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7517.73 27-AUG-19:53 0.00 47.50 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
September 3117.01 30-SEP-23:30 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4544.21 31-OCT-23:30 0.00 15.83 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5545.72 09-NOV-16:50 222.14 284.97 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 6970.41 15-DEC-16:50 222.14 284.97 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1580.88   0.00 15.83 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7537.34   222.14 284.97 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 91307.30 02-JAN-17:00 4808.68 3337.76 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 181865.75 21-FEB-17:00 4808.68 3337.76 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 356949.97 31-MAR-24:00 0.00 185.45 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 364885.51 17-APR-16:00 4808.68 3337.76 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
May 174929.66 31-MAY-24:00 0.00 185.45 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 266467.37 30-JUN-23:57 0.00 741.80 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
July 359385.01 31-JUL-23:57 0.00 556.35 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
August 367614.02 07-AUG-16:00 4808.68 3337.76 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
September 176624.28 30-SEP-24:00 0.00 185.45 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 268337.36 31-OCT-24:00 0.00 185.45 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 275713.80 13-NOV-17:00 4808.68 3337.76 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 366694.53 18-DEC-16:55 9617.36 6675.52 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 91307.30   0.00 185.45 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 367614.02   9617.36 6675.52 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.128365E+13 876592.18 03-JAN-16:00 0.137811E+12 553633.73 27-JAN-07:10
February 0.152772E+13 1071592.43 21-FEB-16:10 0.998135E+11 575714.53 03-FEB-07:10
March 0.213681E+13 1237365.24 16-MAR-15:00 0.833897E+11 439123.63 02-MAR-07:19
April 0.250839E+13 1547871.47 21-APR-15:09 0.549727E+11 146465.52 12-APR-06:19
May 0.157579E+13 1156162.65 30-MAY-15:00 0.535889E+11 71895.50 05-MAY-11:00
June 0.202059E+13 1309790.80 21-JUN-15:20 0.498184E+11 68446.56 01-JUN-11:30
July 0.246535E+13 1487812.99 21-JUL-07:00 0.470911E+11 64998.92 03-JUL-11:30
August 0.284477E+13 1610390.17 02-AUG-07:00 0.500406E+11 64974.37 28-AUG-11:30
September 0.154087E+13 1138201.11 21-SEP-15:00 0.480002E+11 67430.33 28-SEP-11:09
October 0.182772E+13 1249945.27 03-OCT-15:00 0.525836E+11 71719.71 25-OCT-11:39
November 0.203184E+13 1252597.14 09-NOV-16:49 0.805888E+11 370917.43 28-NOV-07:19
December 0.240215E+13 1297429.58 08-DEC-16:00 0.172430E+12 630632.51 27-DEC-07:10
             
Annual Sum or Average 0.241657E+14     0.930129E+12    
Minimum of Months 0.128365E+13 876592.18   0.470911E+11 64974.37  
Maximum of Months 0.284477E+13 1610390.17   0.172430E+12 630632.51  



Table of Contents

Report: EnergyConsumptionDistrictHeatingCoolingMonthly

For: Meter

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

DISTRICTCOOLING:FACILITY [J] DISTRICTCOOLING:FACILITY {Maximum} [W] DISTRICTCOOLING:FACILITY {TIMESTAMP} DISTRICTHEATING:FACILITY [J] DISTRICTHEATING:FACILITY {Maximum} [W] DISTRICTHEATING:FACILITY {TIMESTAMP}
January 0.239101E+12 93933.13 02-JAN-14:00 155035.23 6.37 19-JAN-00:40
February 0.434858E+12 184489.03 21-FEB-14:00 179199.23 12.25 01-FEB-00:40
March 0.726579E+12 356950.64 31-MAR-23:00 197487.83 11.85 01-MAR-00:30
April 0.940458E+12 367484.45 17-APR-15:00 71619.53 10.51 25-APR-23:30
May 0.240525E+12 174931.02 31-MAY-23:00 89225.25 6.43 10-MAY-23:40
June 0.469188E+12 266467.37 30-JUN-23:00 13880.36 1.54 25-JUN-17:30
July 0.732015E+12 359385.01 31-JUL-23:00 18560.86 6.10 13-JUL-23:19
August 0.978838E+12 370232.07 07-AUG-13:00 48837.50 8.45 16-AUG-23:30
September 0.238118E+12 176624.28 30-SEP-23:00 85151.75 6.09 28-SEP-23:40
October 0.489402E+12 268338.83 31-OCT-23:00 155341.88 11.76 31-OCT-23:30
November 0.709596E+12 278357.09 13-NOV-14:00 190063.12 8.09 10-NOV-00:30
December 0.976644E+12 369306.47 18-DEC-14:00 201341.80 11.15 01-DEC-00:30
             
Annual Sum or Average 0.717532E+13     1405744.33    
Minimum of Months 0.238118E+12 93933.13   13880.36 1.54  
Maximum of Months 0.978838E+12 370232.07   201341.80 12.25  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.171402E+12 0.347210E+11 0.766053E+12 0.207862E+12 0.713850E+11 0.140705E+11 0.00 0.151389E+11 0.302257E+10 0.00 0.00 0.00 0.00
February 0.154515E+12 0.285874E+11 0.978954E+12 0.229081E+12 0.690112E+11 0.195379E+11 0.00 0.386964E+11 0.933759E+10 0.00 0.00 0.00 0.00
March 0.181803E+12 0.278307E+11 0.141687E+13 0.299605E+12 0.891328E+11 0.301489E+11 0.00 0.739089E+11 0.175082E+11 0.00 0.00 0.00 0.00
April 0.161441E+12 0.234529E+11 0.165903E+13 0.333797E+12 0.107291E+12 0.552928E+11 0.00 0.139136E+12 0.289582E+11 0.00 0.00 0.00 0.00
May 0.173741E+12 0.213312E+11 0.774844E+12 0.208007E+12 0.134243E+12 0.670611E+11 0.00 0.159231E+12 0.373328E+11 0.00 0.00 0.00 0.00
June 0.172585E+12 0.193305E+11 0.106252E+13 0.245640E+12 0.153995E+12 0.833944E+11 0.00 0.234515E+12 0.486120E+11 0.00 0.00 0.00 0.00
July 0.161913E+12 0.207314E+11 0.139340E+13 0.299361E+12 0.147511E+12 0.907100E+11 0.00 0.278832E+12 0.728877E+11 0.00 0.00 0.00 0.00
August 0.180693E+12 0.230749E+11 0.173200E+13 0.345115E+12 0.152604E+12 0.884562E+11 0.00 0.263104E+12 0.597228E+11 0.00 0.00 0.00 0.00
September 0.162035E+12 0.252168E+11 0.740713E+12 0.201201E+12 0.125103E+12 0.664123E+11 0.00 0.171907E+12 0.482856E+11 0.00 0.00 0.00 0.00
October 0.169457E+12 0.300271E+11 0.108340E+13 0.253679E+12 0.101365E+12 0.482565E+11 0.00 0.111716E+12 0.298155E+11 0.00 0.00 0.00 0.00
November 0.169149E+12 0.325185E+11 0.135889E+13 0.289765E+12 0.798035E+11 0.244478E+11 0.00 0.627254E+11 0.145362E+11 0.00 0.00 0.00 0.00
December 0.166443E+12 0.355785E+11 0.170972E+13 0.345057E+12 0.721517E+11 0.128348E+11 0.00 0.499333E+11 0.104305E+11 0.00 0.00 0.00 0.00
                           
Annual Sum or Average 0.202518E+13 0.322401E+12 0.146764E+14 0.325817E+13 0.130360E+13 0.600623E+12 0.00 0.159884E+13 0.380450E+12 0.00 0.00 0.00 0.00
Minimum of Months 0.154515E+12 0.193305E+11 0.740713E+12 0.201201E+12 0.690112E+11 0.128348E+11 0.00 0.151389E+11 0.302257E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.181803E+12 0.355785E+11 0.173200E+13 0.345115E+12 0.153995E+12 0.907100E+11 0.00 0.278832E+12 0.728877E+11 0.00 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.778853E+11 0.00 0.599257E+11 0.00 0.00
February 0.00 0.00 0.454784E+11 0.00 0.543351E+11 0.00 0.00
March 0.00 0.00 0.222055E+11 0.00 0.611842E+11 0.00 0.00
April 0.00 0.00 0.118535E+10 0.00 0.537874E+11 0.00 0.00
May 0.00 0.00 0.00 0.00 0.535889E+11 0.00 0.00
June 0.00 0.00 0.00 0.00 0.498184E+11 0.00 0.00
July 0.00 0.00 0.00 0.00 0.470911E+11 0.00 0.00
August 0.00 0.00 0.00 0.00 0.500406E+11 0.00 0.00
September 0.00 0.00 0.00 0.00 0.480002E+11 0.00 0.00
October 0.00 0.00 0.236056E+09 0.00 0.523476E+11 0.00 0.00
November 0.00 0.00 0.262970E+11 0.00 0.542918E+11 0.00 0.00
December 0.00 0.00 0.115104E+12 0.00 0.573257E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.288392E+12 0.00 0.641737E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.470911E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.115104E+12 0.00 0.611842E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 195889.64 17-JAN-16:00 37611.08 01-JAN-06:10 423497.50 02-JAN-08:09 133940.29 09-JAN-08:20 70544.62 12-JAN-16:10 31861.36 07-JAN-06:10 0.00 01-JAN-00:10
February 189829.95 23-FEB-16:00 37611.08 01-FEB-06:10 541788.89 01-FEB-08:09 151026.57 13-FEB-08:20 91116.39 21-FEB-16:30 47739.80 21-FEB-14:30 0.00 01-FEB-00:10
March 189526.22 10-MAR-16:00 37611.08 01-MAR-06:10 660080.29 01-MAR-08:09 168108.48 22-MAR-07:19 116008.70 16-MAR-15:50 47814.32 16-MAR-14:39 0.00 01-MAR-00:10
April 180440.33 20-APR-07:10 37611.08 01-APR-05:10 778371.69 03-APR-07:10 185189.52 20-APR-07:19 153696.50 21-APR-14:50 50307.96 28-APR-14:20 0.00 01-APR-00:10
May 173661.56 23-MAY-12:30 37611.08 01-MAY-05:10 423497.50 01-MAY-07:10 133935.50 03-MAY-07:19 172376.59 30-MAY-14:50 50086.19 26-MAY-15:39 0.00 01-MAY-00:10
June 172081.85 29-JUN-07:10 24287.76 01-JUN-19:10 541788.89 01-JUN-07:10 151018.19 29-JUN-07:19 183130.10 15-JUN-14:30 50456.40 07-JUN-14:39 0.00 01-JUN-00:10
July 179704.12 07-JUL-07:30 37611.08 06-JUL-05:10 660080.29 03-JUL-07:10 168105.66 07-JUL-07:40 175670.34 03-JUL-14:00 52582.69 20-JUL-14:00 0.00 01-JUL-00:10
August 179309.67 17-AUG-07:10 37611.08 01-AUG-05:10 778371.69 01-AUG-07:10 185188.92 17-AUG-07:19 177062.39 08-AUG-14:00 50136.87 23-AUG-09:39 0.00 01-AUG-00:10
September 179035.92 18-SEP-07:10 37611.08 01-SEP-05:10 423497.50 01-SEP-07:10 133938.38 18-SEP-07:19 158781.81 21-SEP-15:00 50173.04 29-SEP-15:09 0.00 01-SEP-00:10
October 192414.26 13-OCT-07:10 37611.08 01-OCT-05:10 541788.89 02-OCT-07:10 151028.89 13-OCT-07:19 137048.63 03-OCT-15:00 49210.76 23-OCT-10:39 0.00 01-OCT-00:10
November 198852.03 22-NOV-16:00 37611.08 01-NOV-05:10 660080.29 01-NOV-07:10 168111.99 01-NOV-07:19 104985.68 09-NOV-16:49 47884.18 03-NOV-14:30 0.00 01-NOV-00:10
December 198852.03 01-DEC-16:00 37611.08 01-DEC-06:10 778371.69 01-DEC-08:09 185188.38 13-DEC-08:20 68115.67 15-DEC-15:20 32262.22 27-DEC-06:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 172081.85   24287.76   423497.50   133935.50   68115.67   31861.36   0.00  
Maximum of Months 198852.03   37611.08   778371.69   185189.52   183130.10   52582.69   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 65832.35 03-JAN-14:39 13099.59 03-JAN-13:00 0.00 0.00 0.00 0.00
February 93550.35 21-FEB-16:10 13251.11 06-FEB-12:00 0.00 0.00 0.00 0.00
March 103669.99 22-MAR-14:50 13550.10 14-MAR-15:30 0.00 0.00 0.00 0.00
April 213892.45 28-APR-15:39 45559.75 21-APR-14:30 0.00 0.00 0.00 0.00
May 207621.54 12-MAY-15:50 45559.75 08-MAY-14:20 0.00 0.00 0.00 0.00
June 222529.41 15-JUN-14:20 45559.75 01-JUN-14:39 0.00 0.00 0.00 0.00
July 358019.12 21-JUL-10:20 45559.75 01-JUL-13:50 0.00 0.00 0.00 0.00
August 278282.56 02-AUG-08:20 45559.75 01-AUG-07:49 0.00 0.00 0.00 0.00
September 252604.06 14-SEP-09:50 45559.75 01-SEP-07:19 0.00 0.00 0.00 0.00
October 211054.63 03-OCT-13:00 45559.75 02-OCT-10:09 0.00 0.00 0.00 0.00
November 103475.80 09-NOV-16:19 14400.06 03-NOV-15:09 0.00 0.00 0.00 0.00
December 59675.08 20-DEC-14:00 12552.96 08-DEC-14:09 0.00 0.00 0.00 0.00
                 
Annual Sum or Average         0.00 0.00 0.00 0.00
Minimum of Months 59675.08   12552.96   0.00 0.00 0.00 0.00
Maximum of Months 358019.12   45559.75   0.00 0.00 0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 876592.18 03-JAN-16:00 189923.84 423497.50 0.00 99898.11 57368.09 30906.65 0.00 62362.83 12635.14
February 1071592.43 21-FEB-16:10 171995.52 541788.89 0.00 116974.47 86904.53 47726.14 0.00 93550.35 12652.52
March 1237365.24 16-MAR-15:00 171458.81 660080.29 0.00 134057.82 112974.76 47782.26 0.00 98082.93 12928.37
April 1547871.47 21-APR-15:09 171235.93 778371.69 0.00 151141.29 152896.29 48030.79 0.00 200635.73 45559.75
May 1156162.65 30-MAY-15:00 171235.93 423497.50 0.00 99890.88 170344.99 49462.12 0.00 196171.47 45559.75
June 1309790.80 21-JUN-15:20 171235.93 541788.89 0.00 116974.35 176774.67 49813.71 0.00 207643.49 45559.75
July 1487812.99 21-JUL-07:00 171235.93 660080.29 0.00 168101.21 99747.58 49915.01 0.00 293173.21 45559.75
August 1610390.17 02-AUG-07:00 171235.93 778371.69 0.00 185184.68 113032.28 49441.58 0.00 267564.27 45559.75
September 1138201.11 21-SEP-15:00 171456.69 423497.50 0.00 99890.88 158781.81 48681.86 0.00 190332.61 45559.75
October 1249945.27 03-OCT-15:00 172616.55 541788.89 0.00 116974.82 137048.63 48603.46 0.00 187353.16 45559.75
November 1252597.14 09-NOV-16:49 190792.04 660080.29 0.00 134064.54 104985.68 47775.30 0.00 101063.47 13835.81
December 1297429.58 08-DEC-16:00 198852.03 778371.69 37611.08 151155.46 52457.68 30811.04 0.00 36387.58 11783.03
                       
Annual Sum or Average                      
Minimum of Months 876592.18   171235.93 423497.50 0.00 99890.88 52457.68 30811.04 0.00 36387.58 11783.03
Maximum of Months 1610390.17   198852.03 778371.69 37611.08 185184.68 176774.67 49915.01 0.00 293173.21 45559.75



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 524831.78 27-JAN-07:10 0.00 78522.57 30-JAN-12:39 0.00
February 0.00 0.00 546692.71 03-FEB-07:10 0.00 78501.26 02-FEB-12:00 0.00
March 0.00 0.00 418477.64 02-MAR-07:10 0.00 77746.48 02-MAR-12:30 0.00
April 0.00 0.00 138204.52 12-APR-06:10 0.00 75352.19 04-APR-11:39 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 71895.50 05-MAY-11:00 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 68446.56 01-JUN-11:30 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 64998.92 03-JUL-11:30 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 64974.37 28-AUG-11:30 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 67430.33 28-SEP-11:09 0.00
October 0.00 0.00 41298.83 25-OCT-06:10 0.00 71719.71 25-OCT-11:39 0.00
November 0.00 0.00 360951.65 28-NOV-07:10 0.00 75595.61 29-NOV-12:20 0.00
December 0.00 0.00 601708.83 27-DEC-07:10 0.00 77729.21 29-DEC-12:20 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 0.00   0.00 64974.37   0.00
Maximum of Months 0.00 0.00 601708.83   0.00 78522.57   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 7.00 26.63 0.83 26.72
February 0.00 0.00 0.00 0.00 3.17 26.04 0.00 26.04
March 0.00 0.00 0.00 0.00 4.17 25.81 0.00 25.81
April 0.00 0.00 0.00 0.00 2.33 25.89 0.00 25.89
May 0.00 0.00 0.00 0.00 3.50 25.99 0.17 26.06
June 0.00 0.00 0.00 0.00 2.17 25.90 0.00 25.90
July 0.00 0.00 0.00 0.00 7.33 26.43 0.00 26.43
August 0.00 0.00 0.00 0.00 7.00 25.98 0.17 26.01
September 0.00 0.00 0.00 0.00 9.00 26.39 0.17 26.41
October 0.00 0.00 0.00 0.00 12.00 26.47 0.50 26.51
November 0.00 0.00 0.00 0.00 13.33 26.62 0.50 26.66
December 0.00 0.00 0.00 0.00 12.67 26.67 1.17 26.74
                 
Annual Sum or Average 0.00   0.00   83.67 26.39 3.50 26.43
Minimum of Months 0.00 0.00 0.00 0.00 2.17 25.81 0.00 25.81
Maximum of Months 0.00 0.00 0.00 0.00 13.33 26.67 1.17 26.74



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.67 25.60 0.00 25.60
September 0.00 0.00 0.00 0.00 0.50 25.57 0.00 25.57
October 0.00 0.00 0.00 0.00 0.33 25.58 0.00 25.58
November 0.00 0.00 0.00 0.00 0.83 25.73 0.00 25.73
December 0.00 0.00 0.00 0.00 0.33 25.57 0.00 25.57
                 
Annual Sum or Average 0.00   0.00   2.83 25.63 0.00 25.63
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.83 25.73 0.00 25.73



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.17 25.56 0.00 25.56
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.26 0.00 19.26 0.00 19.26 0.00 19.26
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.33 19.18 0.00 19.18 0.00 19.18 0.00 19.18
                 
Annual Sum or Average 0.50 19.21 0.00 19.21 0.00 19.21 0.00 19.21
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 19.26 0.00 19.26 0.00 19.26 0.00 19.26



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.50 26.73 0.33 26.95
July 0.00 0.00 0.00 0.00 2.17 26.67 0.67 26.84
August 0.00 0.00 0.00 0.00 2.00 26.57 0.67 26.76
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.67 26.63 1.67 26.82
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.17 26.73 0.67 26.95



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 27.32 0.17 27.32
March 0.00 0.00 0.00 0.00 0.33 27.27 0.33 27.27
April 0.00 0.00 0.00 0.00 3.50 27.65 3.50 27.65
May 0.00 0.00 0.00 0.00 7.33 27.70 7.33 27.70
June 0.00 0.00 0.00 0.00 7.50 27.65 7.17 27.68
July 0.00 0.00 0.00 0.00 10.00 27.61 9.33 27.66
August 0.00 0.00 0.00 0.00 8.33 27.56 7.83 27.60
September 0.00 0.00 0.00 0.00 4.50 27.74 4.50 27.74
October 0.00 0.00 0.00 0.00 2.17 27.52 2.17 27.52
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   43.83 27.63 42.33 27.65
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 10.00 27.74 9.33 27.74



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 2.33 27.48 2.33 27.48
February 0.00 0.00 0.00 0.00 4.50 27.55 4.50 27.55
March 0.00 0.00 0.00 0.00 1.83 27.33 1.83 27.33
April 0.00 0.00 0.00 0.00 2.67 27.43 2.67 27.43
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.83 26.96 0.67 27.11
July 0.00 0.00 0.00 0.00 4.67 27.09 3.33 27.23
August 0.00 0.00 0.00 0.00 8.50 27.25 6.50 27.38
September 0.00 0.00 0.00 0.00 7.67 27.65 7.50 27.65
October 0.00 0.00 0.00 0.00 9.00 27.78 8.50 27.82
November 0.00 0.00 0.00 0.00 7.33 27.71 7.33 27.71
December 0.00 0.00 0.00 0.00 2.17 27.48 2.17 27.48
                 
Annual Sum or Average 0.00   0.00   51.50 27.51 47.33 27.56
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 9.00 27.78 8.50 27.82



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 2.67 27.78 2.67 27.78
March 0.00 0.00 0.00 0.00 5.00 27.83 3.33 27.92
April 0.00 0.00 0.00 0.00 24.33 27.30 7.17 27.53
May 0.00 0.00 0.00 0.00 12.67 27.61 6.33 27.78
June 0.00 0.00 0.00 0.00 26.33 27.13 5.67 27.33
July 0.00 0.00 0.00 0.00 43.00 27.47 13.00 27.61
August 0.00 0.00 0.00 0.00 48.33 27.50 13.33 27.63
September 0.00 0.00 0.00 0.00 12.83 27.16 6.00 27.41
October 0.00 0.00 0.00 0.00 9.33 27.39 5.50 27.64
November 0.00 0.00 0.00 0.00 4.00 27.68 3.50 27.78
December 0.00 0.00 0.00 0.00 1.17 27.58 1.17 27.58
                 
Annual Sum or Average 0.00   0.00   189.67 27.41 67.67 27.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 48.33 27.83 13.33 27.92



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.67 26.47 0.33 26.74
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.44 0.00 19.44 0.00 19.44 0.00 19.44
                 
Annual Sum or Average 0.17 19.44 0.00 19.44 0.67 25.06 0.33 25.69
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.44 0.00 19.44 0.67 26.47 0.33 26.74



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 3.67 27.70 3.67 27.70
May 0.00 0.00 0.00 0.00 10.67 27.67 10.67 27.67
June 0.00 0.00 0.00 0.00 10.33 27.78 10.17 27.78
July 0.00 0.00 0.00 0.00 13.50 27.71 12.67 27.74
August 0.00 0.00 0.00 0.00 8.00 27.78 7.83 27.78
September 0.00 0.00 0.00 0.00 5.33 27.71 5.33 27.71
October 0.00 0.00 0.00 0.00 1.17 27.46 1.17 27.46
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.38 0.00 19.38 0.00 19.38 0.00 19.38
                 
Annual Sum or Average 0.17 19.38 0.00 19.38 52.67 27.69 51.50 27.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.38 0.00 19.38 13.50 27.78 12.67 27.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 2.33 27.54 2.33 27.54
February 0.00 0.00 0.00 0.00 4.67 27.62 4.67 27.62
March 0.00 0.00 0.00 0.00 1.00 27.35 1.00 27.35
April 0.00 0.00 0.00 0.00 1.33 27.41 1.33 27.41
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 2.17 27.11 1.83 27.23
August 0.00 0.00 0.00 0.00 4.33 27.36 4.00 27.40
September 0.00 0.00 0.00 0.00 7.17 27.66 7.00 27.67
October 0.00 0.00 0.00 0.00 14.00 26.66 13.33 26.67
November 0.00 0.00 0.00 0.00 11.67 26.56 11.67 26.56
December 0.00 0.00 0.00 0.00 1.83 27.48 1.83 27.48
                 
Annual Sum or Average 0.00   0.00   50.50 27.05 49.00 27.06
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 14.00 27.66 13.33 27.67



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.33 27.33 0.33 27.33
March 0.00 0.00 0.00 0.00 1.33 27.45 1.00 27.44
April 0.00 0.00 0.00 0.00 5.50 27.98 4.00 27.99
May 0.00 0.00 0.00 0.00 8.83 27.87 5.00 27.98
June 0.00 0.00 0.00 0.00 11.83 27.46 4.17 27.70
July 0.00 0.00 0.00 0.00 16.17 27.45 6.00 27.64
August 0.00 0.00 0.00 0.00 11.17 27.44 4.00 27.68
September 0.00 0.00 0.00 0.00 5.83 27.86 4.33 27.88
October 0.00 0.00 0.00 0.00 3.17 27.73 3.00 27.74
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   64.17 27.61 31.83 27.76
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 16.17 27.98 6.00 27.99



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.67 18.73 0.00 18.73 0.00 18.73 0.00 18.73
February 2.33 19.02 0.00 19.02 0.00 19.02 0.00 19.02
March 0.50 18.83 0.00 18.83 0.00 18.83 0.00 18.83
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 4.67 27.38 2.50 27.42
July 0.00 0.00 0.00 0.00 7.67 27.37 4.33 27.40
August 0.00 0.00 0.00 0.00 1.83 27.29 1.00 27.35
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 2.33 18.74 0.17 18.85 0.00 18.85 0.00 18.85
December 7.67 18.46 1.00 18.57 0.00 18.57 0.00 18.57
                 
Annual Sum or Average 17.50 18.66 1.17 18.71 14.17 22.44 7.83 23.41
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7.67 19.02 1.00 19.02 7.67 27.38 4.33 27.42



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.00 18.82 0.00 18.82 0.00 18.82 0.00 18.82
February 1.83 19.04 0.00 19.04 0.00 19.04 0.00 19.04
March 0.50 18.94 0.00 18.94 0.00 18.94 0.00 18.94
April 0.00 0.00 0.00 0.00 3.33 27.68 3.33 27.68
May 0.00 0.00 0.00 0.00 11.67 27.77 10.83 27.78
June 0.00 0.00 0.00 0.00 13.33 27.82 10.50 27.88
July 0.00 0.00 0.00 0.00 19.17 27.83 15.33 27.88
August 0.00 0.00 0.00 0.00 12.17 27.80 9.67 27.85
September 0.00 0.00 0.00 0.00 9.17 27.67 9.00 27.67
October 0.00 0.00 0.00 0.00 0.33 27.37 0.33 27.37
November 1.83 18.56 0.00 18.56 0.00 18.56 0.00 18.56
December 5.83 18.28 0.00 18.28 0.00 18.28 0.00 18.28
                 
Annual Sum or Average 14.00 18.60 0.00 18.60 69.17 26.23 59.00 26.91
Minimum of Months 0.00 0.00 0.00 0.00 0.00 18.28 0.00 18.28
Maximum of Months 5.83 19.04 0.00 19.04 19.17 27.83 15.33 27.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.00 19.04 0.00 19.04 0.00 19.04 0.00 19.04
February 0.83 19.20 0.00 19.20 1.50 24.59 1.50 25.76
March 0.33 19.12 0.00 19.12 0.00 19.12 0.00 19.12
April 0.00 0.00 0.00 0.00 2.33 27.47 2.17 27.48
May 0.00 0.00 0.00 0.00 3.50 27.37 3.50 27.37
June 0.00 0.00 0.00 0.00 3.67 27.41 2.67 27.46
July 0.00 0.00 0.00 0.00 9.67 27.45 6.83 27.49
August 0.00 0.00 0.00 0.00 8.50 27.56 5.83 27.61
September 0.00 0.00 0.00 0.00 8.83 27.76 7.50 27.79
October 0.00 0.00 0.00 0.00 7.50 27.85 6.50 27.92
November 0.67 18.54 0.00 18.54 3.33 26.07 3.33 26.76
December 4.00 18.60 0.00 18.60 0.00 18.60 0.00 18.60
                 
Annual Sum or Average 7.83 18.79 0.00 18.79 48.83 26.38 39.83 26.91
Minimum of Months 0.00 0.00 0.00 0.00 0.00 18.60 0.00 18.60
Maximum of Months 4.00 19.20 0.00 19.20 9.67 27.85 7.50 27.92



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.50 19.05 0.00 19.05 0.00 19.05 0.00 19.05
February 0.83 19.12 0.00 19.12 0.00 19.12 0.00 19.12
March 0.33 19.20 0.00 19.20 0.50 24.12 0.33 25.06
April 0.00 0.00 0.00 0.00 5.83 28.03 4.00 28.02
May 0.00 0.00 0.00 0.00 9.83 28.09 5.17 28.19
June 0.00 0.00 0.00 0.00 14.00 27.67 4.67 27.88
July 0.00 0.00 0.00 0.00 20.17 27.72 7.17 27.88
August 0.00 0.00 0.00 0.00 14.67 27.71 5.33 27.87
September 0.00 0.00 0.00 0.00 6.17 28.04 4.17 28.07
October 0.00 0.00 0.00 0.00 2.33 27.78 2.00 27.81
November 0.67 18.80 0.00 18.80 0.00 18.80 0.00 18.80
December 3.50 18.84 0.00 18.84 0.00 18.84 0.00 18.84
                 
Annual Sum or Average 7.83 18.95 0.00 18.95 73.50 26.96 32.83 27.33
Minimum of Months 0.00 0.00 0.00 0.00 0.00 18.80 0.00 18.80
Maximum of Months 3.50 19.20 0.00 19.20 20.17 28.09 7.17 28.19



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 11.67 27.97 5.83 27.96
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 22.33 27.89 15.67 27.85
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   34.00 27.92 21.50 27.88
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 22.33 27.97 15.67 27.96



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 6.50 27.93 2.83 27.89
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 24.67 27.82 19.17 27.79
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   31.17 27.84 22.00 27.80
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 24.67 27.93 19.17 27.89



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 6.83 28.01 2.83 27.97
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 29.83 27.94 21.17 27.90
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   36.67 27.95 24.00 27.91
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 29.83 28.01 21.17 27.97



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 190.00 24.01 94.00 24.72 0.00 24.72
February 230.17 24.01 69.50 24.44 0.00 24.44
March 310.50 24.00 54.50 24.31 0.00 24.31
April 136.67 24.00 89.33 24.83 0.00 24.83
May 51.67 24.00 211.17 24.91 16.00 24.86
June 42.33 24.31 307.33 24.71 32.83 24.68
July 255.00 24.47 493.00 24.60 255.00 24.57
August 204.50 24.24 500.67 24.47 204.50 24.42
September 185.17 24.75 441.67 24.70 185.17 24.71
October 58.50 24.58 309.83 24.99 53.17 24.94
November 54.17 24.00 151.50 25.42 0.00 25.42
December 157.83 24.00 96.17 24.95 0.00 24.95
             
Annual Sum or Average 1876.50 24.19 2818.67 24.69 746.67 24.66
Minimum of Months 42.33 24.00 54.50 24.31 0.00 24.31
Maximum of Months 310.50 24.75 500.67 25.42 255.00 25.42



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 256.67 23.93 52.50 24.20 0.00 24.20
February 228.17 23.99 27.67 24.10 0.00 24.10
March 214.00 24.01 37.00 24.28 0.00 24.28
April 95.00 24.02 64.50 24.32 0.00 24.32
May 53.33 24.00 175.67 24.41 21.00 24.38
June 37.00 24.00 303.67 24.20 32.17 24.18
July 284.00 24.24 495.00 24.23 284.00 24.23
August 170.00 24.11 502.33 24.19 170.00 24.17
September 160.00 24.44 425.50 24.38 160.00 24.39
October 35.33 24.49 289.33 24.60 31.17 24.59
November 70.67 24.01 121.33 24.82 0.00 24.82
December 168.67 24.01 66.33 24.57 0.00 24.57
             
Annual Sum or Average 1772.83 24.09 2560.83 24.32 698.33 24.31
Minimum of Months 35.33 23.93 27.67 24.10 0.00 24.10
Maximum of Months 284.00 24.49 502.33 24.82 284.00 24.82



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 488.67 23.59 0.00 23.59 0.00 23.59
February 403.83 23.71 3.83 23.71 0.00 23.71
March 466.17 23.85 1.50 23.85 0.00 23.85
April 228.83 23.92 20.00 24.00 0.00 24.00
May 105.83 23.95 154.67 24.23 19.17 24.22
June 63.00 24.03 261.17 24.20 35.33 24.19
July 297.50 24.13 488.33 24.15 297.50 24.14
August 209.33 24.10 466.17 24.14 209.17 24.14
September 154.50 24.23 396.50 24.25 147.50 24.25
October 105.33 23.92 210.67 24.20 31.67 24.21
November 338.83 23.78 27.83 23.83 0.00 23.83
December 489.50 23.55 0.00 23.55 0.00 23.55
             
Annual Sum or Average 3351.33 23.81 2030.67 23.98 740.33 24.00
Minimum of Months 63.00 23.55 0.00 23.55 0.00 23.55
Maximum of Months 489.50 24.23 488.33 24.25 297.50 24.25



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.95 90.00 21.73 90.00 21.57
February 453.83 22.49 37.83 22.37 37.83 22.27
March 511.83 23.20 4.17 23.18 4.17 23.16
April 269.50 23.72 24.67 23.79 0.00 23.79
May 110.83 23.87 171.50 24.18 21.33 24.17
June 49.50 24.05 301.67 24.25 30.83 24.23
July 293.00 24.23 493.00 24.25 293.00 24.24
August 202.67 24.08 483.33 24.17 202.67 24.15
September 191.17 24.20 390.17 24.25 165.17 24.26
October 256.33 23.48 148.33 23.70 42.50 23.74
November 441.67 22.63 24.17 22.56 21.50 22.49
December 497.00 21.70 126.83 21.45 126.83 21.29
             
Annual Sum or Average 3779.33 22.95 2295.67 23.27 1035.83 23.26
Minimum of Months 49.50 21.70 4.17 21.45 0.00 21.29
Maximum of Months 511.83 24.23 493.00 24.25 293.00 24.26



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 501.50 22.81 6.33 22.78 6.33 22.76
February 438.83 23.16 3.83 23.14 3.83 23.12
March 496.50 23.61 0.00 23.61 0.00 23.61
April 207.33 23.91 52.67 24.06 0.00 24.06
May 66.83 23.96 223.33 24.48 12.83 24.46
June 26.50 24.34 386.00 24.47 23.00 24.46
July 192.67 24.74 495.83 24.55 192.67 24.59
August 109.50 24.36 508.00 24.36 109.50 24.36
September 144.33 24.53 397.50 24.43 133.83 24.46
October 139.17 23.81 196.67 24.12 25.33 24.13
November 424.00 23.48 1.50 23.48 0.00 23.48
December 495.17 23.03 0.00 23.03 0.00 23.03
             
Annual Sum or Average 3242.33 23.49 2271.67 23.88 507.33 23.93
Minimum of Months 26.50 22.81 0.00 22.78 0.00 22.76
Maximum of Months 501.50 24.74 508.00 24.55 192.67 24.59



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 457.83 22.95 9.00 22.95 5.17 22.93
February 365.83 23.22 16.67 23.30 3.83 23.27
March 340.50 23.44 20.33 23.59 1.67 23.58
April 131.33 23.88 126.33 24.38 4.50 24.43
May 59.83 25.15 317.67 24.75 36.00 24.86
June 48.67 25.70 433.67 24.59 45.00 24.70
July 191.00 24.98 496.17 24.64 191.00 24.71
August 126.67 24.79 507.67 24.43 126.67 24.49
September 134.00 25.01 436.67 24.61 126.67 24.70
October 149.00 23.70 247.83 24.20 29.33 24.25
November 331.83 23.29 27.67 23.44 0.00 23.44
December 465.83 22.93 4.67 22.93 2.50 22.92
             
Annual Sum or Average 2802.33 23.58 2644.33 24.04 572.33 24.13
Minimum of Months 48.67 22.93 4.67 22.93 0.00 22.92
Maximum of Months 465.83 25.70 507.67 24.75 191.00 24.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 310.83 23.07 57.33 23.39 4.67 23.39
February 255.67 23.34 42.17 23.70 3.17 23.69
March 279.00 23.60 28.33 23.86 0.00 23.86
April 134.67 23.89 120.67 24.38 1.33 24.40
May 74.00 24.06 241.33 24.53 16.33 24.53
June 34.33 24.58 383.67 24.47 26.33 24.49
July 193.00 24.78 495.33 24.57 193.00 24.61
August 118.17 24.80 509.00 24.48 118.17 24.53
September 133.50 25.07 441.33 24.69 127.83 24.77
October 96.67 24.86 339.83 24.71 50.00 24.86
November 207.00 23.62 129.00 24.20 6.50 24.26
December 293.33 23.21 38.00 23.47 1.67 23.46
             
Annual Sum or Average 2130.17 23.81 2826.00 24.28 549.00 24.35
Minimum of Months 34.33 23.07 28.33 23.39 0.00 23.39
Maximum of Months 310.83 25.07 509.00 24.71 193.00 24.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 374.50 23.25 24.83 23.39 0.00 23.39
February 225.00 23.65 42.67 23.99 1.83 24.01
March 98.67 24.11 130.67 24.88 7.83 24.96
April 32.00 26.31 292.83 25.16 23.33 25.29
May 43.67 25.73 359.17 24.87 34.67 24.98
June 43.00 26.26 460.83 24.73 43.00 24.85
July 204.33 25.46 497.00 24.91 204.33 25.04
August 137.83 25.70 514.00 24.82 137.83 24.97
September 136.50 25.24 455.33 24.76 136.50 24.85
October 51.50 26.04 368.00 24.95 50.17 25.08
November 85.83 24.04 177.33 24.76 5.50 24.81
December 168.50 23.84 77.17 24.49 0.00 24.49
             
Annual Sum or Average 1601.33 24.43 3399.83 24.68 645.00 24.80
Minimum of Months 32.00 23.25 24.83 23.39 0.00 23.39
Maximum of Months 374.50 26.31 514.00 25.16 204.33 25.29



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.28 169.17 21.14 169.17 21.05
February 454.00 21.83 99.83 21.66 99.83 21.54
March 514.00 22.60 27.50 22.51 27.50 22.44
April 319.17 23.49 16.33 23.55 0.00 23.55
May 109.50 23.87 195.50 24.34 11.83 24.33
June 25.67 24.13 365.67 24.50 20.33 24.48
July 244.83 24.44 494.83 24.46 244.83 24.46
August 158.17 24.10 492.00 24.27 158.17 24.24
September 162.67 24.12 369.50 24.24 123.00 24.25
October 348.00 23.30 113.17 23.49 28.50 23.51
November 477.00 22.04 46.67 21.93 46.67 21.83
December 497.00 21.08 246.17 20.93 246.17 20.85
             
Annual Sum or Average 3812.00 22.50 2636.33 22.94 1176.00 22.87
Minimum of Months 25.67 21.08 16.33 20.93 0.00 20.85
Maximum of Months 514.00 24.44 494.83 24.50 246.17 24.48



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 21.78 78.00 21.62 78.00 21.50
February 362.17 22.46 38.17 22.39 32.83 22.28
March 359.83 22.96 29.00 23.02 13.50 22.95
April 145.83 23.70 105.33 24.36 5.17 24.42
May 62.67 25.18 261.50 24.93 32.17 25.07
June 47.00 26.13 360.83 24.84 43.83 24.98
July 195.50 25.10 421.17 24.83 195.50 24.89
August 129.83 24.85 424.17 24.59 129.83 24.64
September 118.00 25.06 351.83 24.70 105.33 24.81
October 191.67 23.28 167.67 23.87 23.67 23.90
November 367.50 22.52 29.67 22.51 18.00 22.44
December 422.00 21.59 124.67 21.37 124.67 21.23
             
Annual Sum or Average 2829.00 22.94 2392.00 23.54 802.50 23.57
Minimum of Months 47.00 21.59 29.00 21.37 5.17 21.23
Maximum of Months 427.00 26.13 424.17 24.93 195.50 25.07



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 326.67 22.66 69.50 22.89 22.50 22.80
February 284.67 22.98 45.83 23.30 11.17 23.25
March 325.83 23.28 29.17 23.51 2.50 23.49
April 192.67 23.66 90.00 24.09 1.00 24.10
May 93.17 23.89 222.00 24.43 13.00 24.43
June 32.00 24.17 358.50 24.48 21.17 24.47
July 236.67 24.53 493.83 24.50 236.67 24.51
August 151.33 24.42 503.50 24.42 151.33 24.42
September 140.67 24.91 432.33 24.65 130.17 24.72
October 135.00 24.32 303.50 24.57 51.67 24.71
November 244.17 23.18 110.17 23.80 11.50 23.86
December 333.50 22.64 71.00 22.69 41.67 22.51
             
Annual Sum or Average 2496.33 23.47 2729.33 24.03 694.33 24.07
Minimum of Months 32.00 22.64 29.17 22.69 1.00 22.51
Maximum of Months 333.50 24.91 503.50 24.65 236.67 24.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 482.83 21.99 49.33 21.90 48.83 21.82
February 417.33 22.42 33.33 22.40 25.67 22.33
March 403.17 23.03 22.33 23.15 3.33 23.13
April 165.83 23.72 129.50 24.27 7.33 24.34
May 77.00 24.67 310.33 24.72 31.67 24.82
June 37.17 25.61 420.33 24.69 34.83 24.76
July 236.67 24.83 496.17 24.68 236.67 24.71
August 159.67 24.64 509.83 24.53 159.67 24.55
September 149.83 24.63 426.00 24.55 134.33 24.59
October 169.00 23.61 226.83 24.11 34.33 24.17
November 387.83 22.57 31.00 22.68 5.17 22.66
December 491.50 21.92 87.67 21.75 87.67 21.62
             
Annual Sum or Average 3177.83 22.99 2742.67 23.63 809.50 23.68
Minimum of Months 37.17 21.92 22.33 21.75 3.33 21.62
Maximum of Months 491.50 25.61 509.83 24.72 236.67 24.82



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.48 371.83 20.35 371.83 20.30
February 454.00 21.06 262.17 20.85 262.17 20.75
March 514.00 21.92 138.00 21.67 138.00 21.50
April 330.00 23.11 37.33 23.15 11.83 23.08
May 126.50 23.73 214.00 24.27 13.67 24.27
June 37.00 24.84 393.67 24.55 29.17 24.58
July 234.50 24.69 495.67 24.58 234.50 24.61
August 162.83 24.23 492.50 24.32 161.50 24.30
September 199.17 24.05 362.83 24.22 142.50 24.25
October 378.50 22.74 102.33 23.01 31.50 23.06
November 483.50 21.21 220.50 20.94 220.50 20.80
December 497.00 20.29 422.33 20.21 422.33 20.18
             
Annual Sum or Average 3919.00 21.98 3513.17 22.35 2039.50 22.17
Minimum of Months 37.00 20.29 37.33 20.21 11.83 20.18
Maximum of Months 514.00 24.84 495.67 24.58 422.33 24.61



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.91 264.00 20.67 264.00 20.55
February 449.33 21.81 123.50 21.52 123.50 21.33
March 458.17 22.65 57.00 22.44 57.00 22.27
April 165.33 23.48 127.33 24.12 9.50 24.14
May 78.67 24.92 336.33 24.73 37.83 24.86
June 55.33 25.97 452.83 24.71 51.00 24.84
July 225.50 25.02 496.17 24.75 225.50 24.82
August 161.83 24.77 506.00 24.52 161.83 24.57
September 162.33 24.78 418.50 24.58 144.83 24.66
October 232.83 22.76 175.83 23.46 25.83 23.49
November 450.00 21.84 112.67 21.60 107.00 21.41
December 497.00 20.66 321.33 20.48 321.33 20.40
             
Annual Sum or Average 3438.33 22.40 3391.50 22.93 1529.17 22.82
Minimum of Months 55.33 20.66 57.00 20.48 9.50 20.40
Maximum of Months 502.00 25.97 506.00 24.75 321.33 24.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 390.50 21.93 139.17 21.69 118.17 21.41
February 340.00 22.31 90.83 22.30 66.17 22.08
March 371.33 22.71 75.67 22.66 55.00 22.46
April 219.83 23.31 101.33 23.75 9.83 23.72
May 119.67 23.87 237.50 24.38 20.00 24.42
June 45.67 24.81 385.00 24.54 31.50 24.59
July 230.83 24.71 495.17 24.59 230.83 24.62
August 160.50 24.55 500.33 24.46 160.50 24.48
September 157.83 24.75 426.50 24.60 140.67 24.67
October 184.83 23.63 265.33 24.22 50.17 24.37
November 295.33 22.34 142.67 22.59 66.33 22.34
December 412.50 21.92 148.00 21.56 142.17 21.31
             
Annual Sum or Average 2928.83 22.96 3007.50 23.48 1091.33 23.41
Minimum of Months 45.67 21.92 75.67 21.56 9.83 21.31
Maximum of Months 412.50 24.81 500.33 24.60 230.83 24.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 494.67 21.26 223.50 20.99 223.50 20.85
February 432.50 21.74 142.33 21.54 137.33 21.39
March 422.67 22.36 74.50 22.30 60.00 22.15
April 204.83 23.32 131.50 23.91 12.67 23.95
May 100.67 24.41 310.67 24.63 33.33 24.74
June 41.33 25.72 433.17 24.68 37.17 24.77
July 236.00 24.95 496.17 24.73 236.00 24.78
August 167.00 24.66 505.33 24.53 167.00 24.55
September 174.50 24.48 420.50 24.50 149.00 24.54
October 251.33 23.12 200.33 23.70 35.00 23.77
November 425.50 21.87 117.50 21.71 100.83 21.54
December 497.00 21.11 270.17 20.86 270.17 20.74
             
Annual Sum or Average 3448.00 22.49 3325.67 23.04 1462.00 22.96
Minimum of Months 41.33 21.11 74.50 20.86 12.67 20.74
Maximum of Months 497.00 25.72 505.33 24.73 270.17 24.78



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 27.00 0.00 27.00
February 0.00 0.00 454.00 27.00 0.00 27.00
March 0.33 27.00 514.00 27.00 0.33 27.00
April 30.67 27.24 485.00 27.04 30.67 27.05
May 0.00 0.00 508.00 27.00 0.00 27.00
June 0.00 0.00 496.00 27.00 0.00 27.00
July 53.50 27.00 497.00 27.00 53.50 27.00
August 135.83 27.21 514.00 27.09 135.83 27.11
September 0.50 27.00 485.00 27.00 0.50 27.00
October 5.17 27.00 502.00 27.00 5.17 27.00
November 8.00 27.00 489.00 27.00 8.00 27.00
December 0.00 0.00 497.00 27.00 0.00 27.00
             
Annual Sum or Average 234.00 27.15 5943.00 27.01 234.00 27.02
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 135.83 27.24 514.00 27.09 135.83 27.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 482.00 27.00 0.00 27.00
February 0.00 0.00 454.00 27.00 0.00 27.00
March 0.00 0.00 514.00 27.00 0.00 27.00
April 0.83 27.99 485.00 27.01 0.83 27.02
May 0.00 0.00 508.00 27.00 0.00 27.00
June 0.00 0.00 496.00 27.00 0.00 27.00
July 0.00 0.00 497.00 27.00 0.00 27.00
August 34.00 27.59 514.00 27.09 34.00 27.12
September 0.00 0.00 485.00 27.00 0.00 27.00
October 0.00 0.00 502.00 27.00 0.00 27.00
November 0.00 0.00 489.00 27.00 0.00 27.00
December 0.00 0.00 497.00 27.00 0.00 27.00
             
Annual Sum or Average 34.83 27.60 5923.00 27.01 34.83 27.01
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 34.00 27.99 514.00 27.09 34.00 27.12



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 46.50 26.01 330.17 26.88 0.00 26.88
February 0.00 0.00 344.33 27.00 0.00 27.00
March 0.00 0.00 492.83 27.00 0.00 27.00
April 3.00 27.68 485.00 27.01 3.00 27.02
May 0.00 0.00 508.00 27.00 0.00 27.00
June 4.17 27.00 496.00 27.00 4.17 27.00
July 15.00 27.00 497.00 27.00 15.00 27.00
August 57.33 27.50 514.00 27.11 57.33 27.14
September 0.00 0.00 485.00 27.00 0.00 27.00
October 0.00 0.00 502.00 27.00 0.00 27.00
November 0.00 0.00 450.33 27.00 0.00 27.00
December 0.00 0.00 352.83 27.00 0.00 27.00
             
Annual Sum or Average 126.00 26.88 5457.50 27.00 79.50 27.01
Minimum of Months 0.00 0.00 330.17 26.88 0.00 26.88
Maximum of Months 57.33 27.68 514.00 27.11 57.33 27.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 27.00 502.00 27.00 502.00 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.00 485.00 27.00 485.00 27.00
May 508.00 27.00 508.00 27.00 508.00 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 27.00 514.00 27.00 514.00 27.00
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.00 497.00 27.00 497.00 27.00
             
Annual Sum or Average 5943.00 27.00 5943.00 27.00 5943.00 27.00
Minimum of Months 454.00 27.00 454.00 27.00 454.00 27.00
Maximum of Months 514.00 27.00 514.00 27.00 514.00 27.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00009 19.42298 0.74641 16.81173
February 454.00000 27.00008 17.58381 0.77816 17.82202
March 514.00000 27.00001 18.42257 0.83508 19.75438
April 485.00000 27.02261 20.07344 0.90428 22.33184
May 508.00000 27.00032 25.19066 0.19127 5.82034
June 496.00000 27.00049 26.24862 0.25670 6.41333
July 497.00000 27.00085 28.31570 0.32266 7.20200
August 514.00000 27.05553 27.44718 0.36800 7.93458
September 485.00000 27.00093 28.20553 0.22717 6.12381
October 502.00000 27.00074 25.30443 0.88711 21.64810
November 489.00000 27.00014 20.95149 0.86098 20.70309
December 497.00000 27.00001 17.75998 0.84388 20.07631
           
Annual Sum or Average 5943.00000 27.00695 22.94963 0.59999 14.34461
Minimum of Months 454.00000 27.00001 17.58381 0.19127 5.82034
Maximum of Months 514.00000 27.05553 28.31570 0.90428 22.33184



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00007 19.46212 0.65180 14.02161
February 454.00000 27.00008 17.57623 0.67453 14.65793
March 514.00000 27.00001 18.40146 0.73134 16.32950
April 485.00000 27.01245 20.05641 0.80794 18.85258
May 508.00000 27.00027 25.20136 0.14107 5.49003
June 496.00000 27.00047 26.25766 0.18922 5.78985
July 497.00000 27.00080 28.34589 0.22598 6.09872
August 514.00000 27.05953 27.45894 0.24907 6.41254
September 485.00000 27.00071 28.33575 0.16845 5.65347
October 502.00000 27.00070 25.33788 0.81303 18.98940
November 489.00000 27.00013 20.93968 0.73816 16.57779
December 497.00000 27.00001 17.72614 0.67133 14.57745
           
Annual Sum or Average 5943.00000 27.00644 22.96400 0.50336 11.92064
Minimum of Months 454.00000 27.00001 17.57623 0.14107 5.49003
Maximum of Months 514.00000 27.05953 28.34589 0.81303 18.98940



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.87061 19.83288 0.54251 11.54195
February 454.00000 27.00008 17.60830 0.60084 12.76725
March 514.00000 27.00001 18.41069 0.67988 14.89165
April 485.00000 27.01027 20.06473 0.79491 18.49351
May 508.00000 27.00030 25.19948 0.14884 5.61519
June 496.00000 27.00049 26.25354 0.21299 6.03811
July 497.00000 27.00084 28.33985 0.25273 6.41620
August 514.00000 27.06249 27.45023 0.26711 6.70822
September 485.00000 27.00080 28.32031 0.17397 5.76531
October 502.00000 27.00070 25.37853 0.78768 18.20171
November 489.00000 27.00013 20.95800 0.66576 14.55078
December 497.00000 27.00001 17.73860 0.57264 12.08207
           
Annual Sum or Average 5943.00000 26.99559 23.00220 0.47353 11.06376
Minimum of Months 454.00000 26.87061 17.60830 0.14884 5.61519
Maximum of Months 514.00000 27.06249 28.33985 0.79491 18.49351



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00000 35.55106 1.08300 29.74801
February 454.00000 27.00000 35.38736 1.22523 36.49321
March 514.00000 27.00000 35.25915 1.36390 43.59972
April 485.00000 27.00000 35.32117 1.50900 51.39002
May 508.00000 27.00000 35.48942 0.48785 10.00478
June 496.00000 27.00000 35.41571 0.71652 15.81038
July 497.00000 27.00000 35.45593 0.94518 23.87866
August 514.00000 27.00000 35.44558 1.15165 32.92355
September 485.00000 27.00000 35.50603 0.58114 12.10114
October 502.00000 27.00000 35.46521 1.29553 40.04090
November 489.00000 27.00000 35.48253 1.42318 46.75221
December 497.00000 27.00000 35.43650 1.53672 52.89804
           
Annual Sum or Average 5943.00000 27.00000 35.43476 1.10881 32.92484
Minimum of Months 454.00000 27.00000 35.25915 0.48785 10.00478
Maximum of Months 514.00000 27.00000 35.55106 1.53672 52.89804



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.54295 18.64539 0.32962 7.87781
February 454.00000 24.50952 16.59561 0.30143 7.32884
March 514.00000 24.42011 16.02033 0.28078 6.97987
April 485.00000 24.52540 20.68188 0.34056 7.84497
May 508.00000 24.52854 30.60651 -0.4426 10.09746
June 496.00000 24.49267 37.41652 -0.3964 9.16181
July 497.00000 24.66036 54.89836 -0.2065 7.08935
August 514.00000 24.54739 50.56043 -0.2577 7.29428
September 485.00000 24.62898 47.72744 -0.2524 7.80277
October 502.00000 24.67087 36.04828 0.50955 11.29750
November 489.00000 24.65596 21.11064 0.39422 8.93616
December 497.00000 24.62206 15.93026 0.34008 7.99538
           
Annual Sum or Average 5943.00000 24.56686 30.62818 0.07580 8.31567
Minimum of Months 454.00000 24.42011 15.93026 -0.4426 6.97987
Maximum of Months 514.00000 24.67087 54.89836 0.50955 11.29750



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.25218 20.75309 0.27737 6.94408
February 454.00000 24.26080 17.53351 0.26844 6.70909
March 514.00000 24.26168 16.71884 0.27751 6.79905
April 485.00000 24.24436 21.31448 0.32257 7.34075
May 508.00000 24.24586 31.47462 -0.4821 10.31300
June 496.00000 24.17727 38.69375 -0.4360 9.25672
July 497.00000 24.21889 54.05476 -0.3057 7.11491
August 514.00000 24.20695 50.90567 -0.3226 7.34080
September 485.00000 24.31516 47.81253 -0.3357 7.89981
October 502.00000 24.36703 37.04036 0.45763 9.82443
November 489.00000 24.39795 22.22212 0.35012 7.90340
December 497.00000 24.39226 17.44815 0.30424 7.24770
           
Annual Sum or Average 5943.00000 24.27808 31.43915 0.02871 7.90116
Minimum of Months 454.00000 24.17727 16.71884 -0.4821 6.70909
Maximum of Months 514.00000 24.39795 54.05476 0.45763 10.31300



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.60473 22.80328 0.10120 5.50895
February 454.00000 23.75624 18.93475 0.12418 5.61827
March 514.00000 23.93069 18.00025 0.17214 5.77305
April 485.00000 24.10641 22.10489 0.26085 6.61162
May 508.00000 24.16350 31.85783 -0.5324 11.32403
June 496.00000 24.15104 38.68343 -0.4777 10.10015
July 497.00000 24.15459 54.60298 -0.3693 8.04246
August 514.00000 24.14903 51.35271 -0.3935 8.45028
September 485.00000 24.20707 48.02058 -0.4016 8.76765
October 502.00000 24.12679 38.03844 0.37475 8.20684
November 489.00000 23.93255 23.99734 0.20803 6.18814
December 497.00000 23.55395 20.04878 0.06851 5.43233
           
Annual Sum or Average 5943.00000 23.98784 32.47595 -0.0744 7.51994
Minimum of Months 454.00000 23.55395 18.00025 -0.5324 5.43233
Maximum of Months 514.00000 24.20707 54.60298 0.37475 11.32403



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.95334 25.89363 -0.3101 8.25039
February 454.00000 22.49026 21.05687 -0.1940 7.02643
March 514.00000 23.19966 19.55125 -0.0167 5.86603
April 485.00000 23.92815 22.26917 0.21504 6.39232
May 508.00000 24.15422 31.88205 -0.5230 11.24580
June 496.00000 24.20298 38.68016 -0.4337 9.34256
July 497.00000 24.25914 54.20993 -0.3106 7.32626
August 514.00000 24.19925 51.38228 -0.3579 7.91815
September 485.00000 24.20819 48.25476 -0.3923 8.74497
October 502.00000 23.78249 39.07907 0.28561 7.24226
November 489.00000 22.76650 26.09980 -0.0893 6.69313
December 497.00000 21.70104 22.49771 -0.3935 9.65697
           
Annual Sum or Average 5943.00000 23.41060 33.50294 -0.2109 7.98491
Minimum of Months 454.00000 21.70104 19.55125 -0.5230 5.86603
Maximum of Months 514.00000 24.25914 54.20993 0.28561 11.24580



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.80817 22.05362 -0.0992 5.97355
February 454.00000 23.18314 18.41486 -0.0244 5.79452
March 514.00000 23.63537 17.08571 0.08788 5.58561
April 485.00000 24.12234 20.89494 0.26929 6.85000
May 508.00000 24.33245 30.37815 -0.4463 9.96567
June 496.00000 24.38167 37.25738 -0.3264 7.90919
July 497.00000 24.47553 52.47791 -0.1868 6.54884
August 514.00000 24.34969 49.72437 -0.2631 7.04565
September 485.00000 24.33015 46.89629 -0.3395 8.19534
October 502.00000 24.09237 37.07062 0.36081 8.17584
November 489.00000 23.55327 23.13739 0.10220 5.70125
December 497.00000 23.03250 18.85725 -0.0645 5.68295
           
Annual Sum or Average 5943.00000 23.86273 31.28712 -0.0787 6.96210
Minimum of Months 454.00000 22.80817 17.08571 -0.4463 5.58561
Maximum of Months 514.00000 24.47553 52.47791 0.36081 9.96567



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.06774 21.20060 -0.0221 6.05336
February 454.00000 23.46462 17.57669 0.06695 6.17419
March 514.00000 23.74871 16.33994 0.15187 6.39721
April 485.00000 24.21985 20.43127 0.34164 8.23255
May 508.00000 24.45290 29.89114 -0.3267 8.81644
June 496.00000 24.41798 36.98936 -0.2443 7.50063
July 497.00000 24.50499 52.23515 -0.1214 6.81376
August 514.00000 24.33770 49.61719 -0.2105 7.05252
September 485.00000 24.44224 46.20712 -0.2257 7.64172
October 502.00000 24.13644 36.63253 0.40615 9.36263
November 489.00000 23.62129 22.56650 0.14490 6.35564
December 497.00000 23.02639 18.34405 -0.0507 6.07770
           
Annual Sum or Average 5943.00000 23.95663 30.77199 -0.0088 7.21321
Minimum of Months 454.00000 23.02639 16.33994 -0.3267 6.05336
Maximum of Months 514.00000 24.50499 52.23515 0.40615 9.36263



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.57865 20.11056 0.13152 7.15369
February 454.00000 23.84436 16.80172 0.17911 7.12687
March 514.00000 23.96716 15.97769 0.21111 6.86777
April 485.00000 24.27530 20.44641 0.33586 8.06714
May 508.00000 24.35573 30.26693 -0.4274 9.86264
June 496.00000 24.37315 37.27685 -0.3333 8.07405
July 497.00000 24.48305 52.42306 -0.1816 6.66655
August 514.00000 24.40412 49.44281 -0.2115 6.82294
September 485.00000 24.52462 45.92675 -0.1936 7.30470
October 502.00000 24.44070 35.69690 0.51456 11.67466
November 489.00000 24.12155 21.47420 0.30763 8.48977
December 497.00000 23.70221 17.06066 0.14472 6.96541
           
Annual Sum or Average 5943.00000 24.17418 30.34825 0.03772 7.92888
Minimum of Months 454.00000 23.57865 15.97769 -0.4274 6.66655
Maximum of Months 514.00000 24.52462 52.42306 0.51456 11.67466



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.54879 20.03229 0.11590 6.18204
February 454.00000 24.07899 16.45725 0.24300 7.05788
March 514.00000 24.39889 15.22737 0.36363 8.45879
April 485.00000 24.63123 19.64463 0.52274 11.73747
May 508.00000 24.55185 29.57177 -0.2454 8.04190
June 496.00000 24.54203 36.58807 -0.1226 6.86865
July 497.00000 24.69026 51.52730 0.04757 6.93867
August 514.00000 24.58780 48.67283 0.01013 6.70607
September 485.00000 24.57646 45.78713 -0.1228 6.94790
October 502.00000 24.59163 35.33668 0.57177 12.87322
November 489.00000 24.44440 20.81838 0.39553 8.98367
December 497.00000 24.36545 16.16683 0.31638 7.66596
           
Annual Sum or Average 5943.00000 24.41905 29.75605 0.17339 8.20643
Minimum of Months 454.00000 23.54879 15.22737 -0.2454 6.18204
Maximum of Months 514.00000 24.69026 51.52730 0.57177 12.87322



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.27876 24.14218 -0.4760 10.35629
February 454.00000 21.83481 20.22212 -0.3546 8.68783
March 514.00000 22.59787 18.72842 -0.1703 6.60227
April 485.00000 23.73009 21.75975 0.15212 6.18345
May 508.00000 24.24874 30.48981 -0.4965 10.99280
June 496.00000 24.39549 36.92694 -0.3497 8.24590
July 497.00000 24.46629 52.78845 -0.2245 6.79434
August 514.00000 24.30932 49.94285 -0.3231 7.64610
September 485.00000 24.19188 47.09887 -0.4137 9.32336
October 502.00000 23.52770 38.84228 0.20980 6.67360
November 489.00000 22.08409 25.44597 -0.2545 7.58437
December 497.00000 21.08479 21.23061 -0.5456 11.96293
           
Annual Sum or Average 5943.00000 23.15578 32.39570 -0.2706 8.42052
Minimum of Months 454.00000 21.08479 18.72842 -0.5456 6.18345
Maximum of Months 514.00000 24.46629 52.78845 0.20980 11.96293



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 21.77873 22.57408 -0.3440 8.54738
February 385.00000 22.60006 18.09276 -0.1573 7.12927
March 433.00000 23.24020 16.67592 0.00969 6.55848
April 410.00000 24.24564 20.14859 0.32254 8.39263
May 430.00000 24.54142 29.32645 -0.3223 9.24988
June 418.00000 24.58818 35.83786 -0.2149 7.71634
July 422.00000 24.70284 51.54480 -0.0831 7.21856
August 433.00000 24.50372 48.62122 -0.1931 7.33630
September 410.00000 24.50298 45.36701 -0.2400 8.23452
October 427.00000 23.86399 37.11215 0.31909 8.44122
November 417.00000 22.73914 23.40168 -0.0828 6.81133
December 422.00000 21.58837 19.58113 -0.4134 9.72684
           
Annual Sum or Average 5034.00000 23.57932 30.78090 -0.1171 7.95126
Minimum of Months 385.00000 21.58837 16.67592 -0.4134 6.55848
Maximum of Months 433.00000 24.70284 51.54480 0.32254 9.72684



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.27908 20.78146 0.05777 7.61464
February 454.00000 23.56167 17.43387 0.10740 7.34499
March 514.00000 23.69108 16.55895 0.13449 6.80132
April 485.00000 24.12962 20.78172 0.28056 7.57518
May 508.00000 24.30132 30.29684 -0.4641 10.58080
June 496.00000 24.38135 36.96157 -0.3586 8.42387
July 497.00000 24.47966 52.71135 -0.2165 6.88893
August 514.00000 24.40935 49.46979 -0.2512 7.18445
September 485.00000 24.49790 45.66745 -0.2201 7.59756
October 502.00000 24.32529 36.00962 0.47655 11.14812
November 489.00000 23.83169 22.12704 0.23134 8.47442
December 497.00000 23.22774 18.13261 0.02079 7.58104
           
Annual Sum or Average 5943.00000 24.01226 30.68215 -0.0187 8.10867
Minimum of Months 454.00000 23.22774 16.55895 -0.4641 6.80132
Maximum of Months 514.00000 24.49790 52.71135 0.47655 11.14812



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.07303 22.42714 -0.2616 7.78473
February 454.00000 22.60247 18.69893 -0.1460 7.03939
March 514.00000 23.32454 17.05312 0.04335 6.41694
April 485.00000 24.18924 20.54314 0.32387 8.35416
May 508.00000 24.45304 29.76967 -0.3336 9.20934
June 496.00000 24.51534 36.44365 -0.2166 7.48808
July 497.00000 24.60480 52.16194 -0.0920 6.79665
August 514.00000 24.48875 49.16086 -0.1676 7.00614
September 485.00000 24.44258 45.96042 -0.2309 7.64147
October 502.00000 24.04778 36.92175 0.38441 9.15862
November 489.00000 22.91863 23.45043 -0.0229 6.71570
December 497.00000 21.94015 19.64734 -0.3160 8.47372
           
Annual Sum or Average 5943.00000 23.64100 31.11664 -0.0865 7.67703
Minimum of Months 454.00000 21.94015 17.05312 -0.3336 6.41694
Maximum of Months 514.00000 24.60480 52.16194 0.38441 9.20934



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.47992 25.52875 -0.7144 17.15750
February 454.00000 21.05728 21.18701 -0.5754 13.45756
March 514.00000 21.92168 19.48370 -0.3503 9.20774
April 485.00000 23.46262 21.91312 0.08656 6.60539
May 508.00000 24.21267 30.59772 -0.4976 11.56769
June 496.00000 24.42614 37.14435 -0.3132 8.00424
July 497.00000 24.53231 52.64020 -0.1789 6.83212
August 514.00000 24.33304 50.12086 -0.2975 7.66134
September 485.00000 24.14804 47.52176 -0.4194 10.03018
October 502.00000 23.06454 39.90767 0.09642 6.79290
November 489.00000 21.23956 26.63978 -0.4857 12.13669
December 497.00000 20.29173 22.25182 -0.7909 19.98378
           
Annual Sum or Average 5943.00000 22.77713 33.00287 -0.3691 10.76571
Minimum of Months 454.00000 20.29173 19.48370 -0.7909 6.60539
Maximum of Months 514.00000 24.53231 52.64020 0.09642 19.98378



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.91274 24.45510 -0.5804 13.76326
February 454.00000 21.83712 19.85080 -0.3570 9.82155
March 514.00000 22.82517 17.73612 -0.1013 7.33454
April 485.00000 24.10676 20.44881 0.29944 8.32781
May 508.00000 24.44687 29.80522 -0.3172 9.18312
June 496.00000 24.50771 36.71229 -0.1861 7.35270
July 497.00000 24.62797 52.08408 -0.0578 7.12689
August 514.00000 24.43079 49.55258 -0.1706 7.21575
September 485.00000 24.41074 46.24565 -0.2340 8.24859
October 502.00000 23.55749 38.10048 0.25048 8.19447
November 489.00000 22.01707 25.09655 -0.2753 9.08080
December 497.00000 20.66187 21.32365 -0.6694 16.16743
           
Annual Sum or Average 5943.00000 23.20526 31.87861 -0.1994 9.31010
Minimum of Months 454.00000 20.66187 17.73612 -0.6694 7.12689
Maximum of Months 514.00000 24.62797 52.08408 0.29944 16.16743



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.47479 22.39341 -0.1748 9.86717
February 454.00000 22.88629 18.61174 -0.0864 8.67881
March 514.00000 23.17753 17.35439 -0.0083 7.55287
April 485.00000 23.92640 20.93117 0.23019 7.76232
May 508.00000 24.25674 30.43176 -0.4665 11.20183
June 496.00000 24.40631 37.19452 -0.3238 8.20777
July 497.00000 24.52999 52.61793 -0.1749 6.93307
August 514.00000 24.41850 49.70650 -0.2277 7.26441
September 485.00000 24.46828 46.09616 -0.2170 8.02052
October 502.00000 24.04007 36.76758 0.40272 10.53944
November 489.00000 23.19187 23.18952 0.04734 9.01552
December 497.00000 22.31776 19.50677 -0.2396 10.39630
           
Annual Sum or Average 5943.00000 23.67974 31.33427 -0.1043 8.78982
Minimum of Months 454.00000 22.31776 17.35439 -0.4665 6.93307
Maximum of Months 514.00000 24.52999 52.61793 0.40272 11.20183



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.30132 23.68552 -0.4801 11.93268
February 454.00000 21.87894 19.59987 -0.3430 9.70229
March 514.00000 22.71842 17.70450 -0.1133 7.64027
April 485.00000 23.95112 20.66227 0.26823 8.43537
May 508.00000 24.38752 29.95360 -0.3405 9.85022
June 496.00000 24.50948 36.75823 -0.1899 7.46714
July 497.00000 24.61733 52.19224 -0.0615 6.98661
August 514.00000 24.47277 49.46971 -0.1519 7.19979
September 485.00000 24.38809 46.43911 -0.2352 8.20324
October 502.00000 23.68044 37.71531 0.29519 8.65349
November 489.00000 22.16952 24.47496 -0.2223 8.74898
December 497.00000 21.10670 20.66450 -0.5526 13.50347
           
Annual Sum or Average 5943.00000 23.27545 31.70450 -0.1767 9.02003
Minimum of Months 454.00000 21.10670 17.70450 -0.5526 6.98661
Maximum of Months 514.00000 24.61733 52.19224 0.29519 13.50347



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.555339E+10 60374.59 03-JAN-14:30 110.20 0.283776E+11 0.00 0.339309E+11 0.70 6.68 03-JAN-14:30 0.00 0.00
February 0.161844E+11 80489.40 21-FEB-16:10 162.49 0.903221E+11 0.00 0.106507E+12 1.20 7.28 21-FEB-16:10 0.00 0.00
March 0.344395E+11 84502.06 14-MAR-15:00 256.22 0.202264E+12 0.00 0.236704E+12 1.83 7.35 16-MAR-15:00 0.00 0.00
April 0.762978E+11 93529.64 28-APR-12:00 473.58 0.483985E+12 0.00 0.560282E+12 3.74 7.36 28-APR-10:00 0.00 0.00
May 0.114998E+12 98812.99 12-MAY-15:50 534.92 0.762658E+12 0.00 0.877656E+12 4.50 7.40 30-MAY-12:30 0.00 0.00
June 0.140906E+12 101216.62 05-JUN-17:20 637.73 0.944539E+12 0.00 0.108545E+13 5.55 7.44 06-JUN-12:30 0.00 0.00
July 0.156026E+12 168958.50 21-JUL-10:20 687.72 0.104017E+13 0.00 0.119619E+13 5.73 7.74 31-JUL-05:02 0.00 0.00
August 0.144000E+12 144251.95 02-AUG-05:02 690.49 0.957030E+12 0.00 0.110103E+13 5.68 7.94 02-AUG-05:04 0.00 0.00
September 0.113061E+12 147564.85 22-SEP-05:02 508.79 0.755612E+12 0.00 0.868673E+12 4.44 7.85 05-SEP-05:04 0.00 0.00
October 0.722808E+11 96380.06 03-OCT-14:00 399.84 0.460134E+12 0.00 0.532415E+12 3.14 7.43 05-OCT-05:03 0.00 0.00
November 0.261890E+11 84546.78 08-NOV-14:40 205.52 0.154769E+12 0.00 0.180958E+12 1.52 7.36 09-NOV-16:20 0.00 0.00
December 0.296781E+10 39926.16 08-DEC-14:10 97.73 0.134141E+11 0.00 0.163819E+11 0.60 4.56 18-DEC-11:20 0.00 0.00
                         
Annual Sum or Average 0.902904E+12     4765.24 0.589327E+13 0.00 0.679618E+13 3.23     0.00 0.00
Minimum of Months 0.296781E+10 39926.16   97.73 0.134141E+11 0.00 0.163819E+11 0.60 4.56   0.00 0.00
Maximum of Months 0.156026E+12 168958.50   690.49 0.104017E+13 0.00 0.119619E+13 5.73 7.94   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.552135E+10 92892.78 28-APR-15:40 18.50 0.393834E+11 0.00 0.449048E+11 0.18 7.35 28-APR-15:40 0.00 0.00
May 0.238429E+11 98812.99 12-MAY-15:50 78.97 0.169940E+12 0.00 0.193783E+12 0.76 7.40 30-MAY-12:30 0.00 0.00
June 0.537236E+11 100834.49 06-JUN-12:30 172.41 0.385766E+12 0.00 0.439489E+12 1.72 7.44 06-JUN-12:30 0.00 0.00
July 0.657174E+11 168958.50 21-JUL-10:20 197.90 0.465244E+12 0.00 0.530962E+12 1.88 7.74 31-JUL-05:02 0.00 0.00
August 0.493523E+11 144251.95 02-AUG-05:02 155.02 0.351102E+12 0.00 0.400454E+12 1.48 7.94 02-AUG-05:04 0.00 0.00
September 0.391298E+11 147564.85 22-SEP-05:02 125.83 0.279425E+12 0.00 0.318555E+12 1.25 7.85 05-SEP-05:04 0.00 0.00
October 0.916691E+10 96380.06 03-OCT-14:00 29.71 0.653047E+11 0.00 0.744716E+11 0.28 7.43 05-OCT-05:03 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.246454E+12     778.33 0.175617E+13 0.00 0.200262E+13 0.63     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.657174E+11 168958.50   197.90 0.465244E+12 0.00 0.530962E+12 1.88 7.94   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.301282E+10 744.00 12476.23 03-JAN-12:40 32873.28 12-JAN-16:40 20.13 18.35 2.96
February 0.929376E+10 672.00 12476.23 04-FEB-14:30 64011.94 20-FEB-17:12 23.40 18.67 2.96
March 0.173849E+11 744.00 12476.23 03-MAR-12:20 107109.68 31-MAR-24:00 26.87 19.17 2.96
April 0.280617E+11 720.00 12476.23 01-APR-08:20 129599.54 30-APR-18:22 33.49 22.60 2.96
May 0.306658E+11 744.00 12476.23 01-MAY-00:05 63233.01 31-MAY-23:23 28.06 24.76 2.96
June 0.322933E+11 720.00 12476.23 01-JUN-00:10 91691.21 30-JUN-23:53 35.27 28.99 2.96
July 0.334163E+11 744.00 12476.23 01-JUL-00:03 120645.72 31-JUL-23:42 38.22 29.17 2.96
August 0.334163E+11 744.00 12476.23 01-AUG-00:03 132246.59 08-AUG-16:00 39.89 28.36 2.96
September 0.297040E+11 720.00 12476.23 01-SEP-00:10 57464.52 30-SEP-24:00 27.71 24.34 2.96
October 0.245239E+11 744.00 12476.23 01-OCT-07:43 81266.75 31-OCT-24:00 26.64 21.04 2.96
November 0.143870E+11 720.00 12476.23 02-NOV-13:30 95007.16 09-NOV-16:40 26.29 18.77 2.96
December 0.104297E+11 744.00 12476.23 08-DEC-13:20 111042.32 15-DEC-16:50 27.91 18.35 2.96
                   
Annual Sum or Average 0.266589E+12 8760.00         29.53 22.74 2.96
Minimum of Months 0.301282E+10 672.00 12476.23   32873.28   20.13 18.35 2.96
Maximum of Months 0.334163E+11 744.00 12476.23   132246.59   39.89 29.17 2.96



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 9745442.11 15.33 623.36 03-JAN-14:00 478378.74 03-JAN-14:30 21.00 20.94 3.54
February 43828059.72 73.12 774.89 06-FEB-13:00 801665.96 21-FEB-15:20 21.24 21.04 9.41
March 0.123316E+09 158.63 1073.87 14-MAR-15:30 892158.40 21-MAR-16:00 21.45 21.04 15.82
April 0.791444E+09 324.70 16541.76 21-APR-14:30 1099027.64 27-APR-14:30 22.11 21.03 31.20
May 0.496828E+10 476.77 16541.76 08-MAY-14:20 1066805.71 08-MAY-14:20 22.93 21.30 39.16
June 0.113672E+11 576.92 16541.76 01-JUN-14:40 1156453.60 06-JUN-09:20 23.35 21.24 48.92
July 0.277153E+11 685.58 16541.76 01-JUL-05:04 1306298.38 21-JUL-10:20 24.13 22.12 51.91
August 0.184420E+11 631.18 16541.76 01-AUG-05:04 1049044.92 23-AUG-09:00 23.44 21.51 51.42
September 0.131555E+11 481.11 16541.76 01-SEP-07:00 1079738.20 25-SEP-16:00 23.15 21.54 39.35
October 0.385247E+10 339.57 16541.76 02-OCT-09:10 1030502.10 19-OCT-14:30 22.22 21.26 28.66
November 0.149204E+09 121.35 1923.83 03-NOV-15:10 859266.42 09-NOV-15:30 21.30 20.98 12.76
December 792605.22 7.17 76.73 08-DEC-14:10 233021.15 08-DEC-14:10 20.95 20.92 2.56
                   
Annual Sum or Average 0.806191E+11 3891.44         22.28 21.24 27.99
Minimum of Months 792605.22 7.17 76.73   233021.15   20.95 20.92 2.56
Maximum of Months 0.277153E+11 685.58 16541.76   1306298.38   24.13 22.12 51.91



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 21.00 21.00 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 21.24 21.24 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 21.45 21.45 0.00
April 0.105125E+09 7.83 16541.76 21-APR-14:30 1099027.64 27-APR-14:30 22.11 22.06 0.61
May 0.169871E+10 38.53 16541.76 08-MAY-14:20 1066805.71 08-MAY-14:20 22.93 22.73 2.91
June 0.495154E+10 117.45 16541.76 01-JUN-14:40 1156453.60 06-JUN-09:20 23.35 22.72 9.15
July 0.117561E+11 197.41 16541.76 01-JUL-13:50 1306298.38 21-JUL-10:20 24.13 23.26 14.88
August 0.786448E+10 134.61 16541.76 01-AUG-05:04 1049044.92 23-AUG-09:00 23.44 22.84 10.15
September 0.542614E+10 96.71 16541.76 01-SEP-07:20 1079738.20 25-SEP-16:00 23.15 22.70 7.53
October 0.143913E+10 24.17 16541.76 02-OCT-10:10 975187.54 17-OCT-15:00 22.22 22.11 1.82
November 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 21.30 21.30 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 20.95 20.95 0.00
                   
Annual Sum or Average 0.332412E+11 616.72         22.28 22.03 3.95
Minimum of Months 0.00 0.00 0.00   0.00   20.95 20.95 0.00
Maximum of Months 0.117561E+11 197.41 16541.76   1306298.38   24.13 23.26 14.88



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.545275E+11 0.00 311.23 925092.92 28-JAN-06:01 0.00 27.34 49.53 0.10 0.00 0.01 0.47 28-JAN-06:01
February 0.315540E+11 0.00 219.37 956412.37 02-FEB-06:01 0.00 25.60 42.98 0.06 0.00 0.01 0.48 02-FEB-06:01
March 0.152253E+11 0.00 123.11 942785.95 02-MAR-06:01 0.00 25.59 34.44 0.03 0.00 0.00 0.47 02-MAR-06:01
April 0.759453E+09 0.00 18.61 88571.08 12-APR-06:05 0.00 24.96 26.37 0.00 0.00 0.00 0.04 12-APR-06:05
May 0.00 0.00 0.00 0.00 01-MAY-00:05 0.00 24.42 24.42 0.00 0.00 0.00 0.00 01-MAY-00:05
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 24.42 24.42 0.00 0.00 0.00 0.00 01-JUN-00:10
July 0.00 0.00 0.00 0.00 01-JUL-00:03 0.00 24.42 24.42 0.00 0.00 0.00 0.00 01-JUL-00:03
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 24.42 24.42 0.00 0.00 0.00 0.00 01-AUG-00:03
September 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 24.42 24.42 0.00 0.00 0.00 0.00 01-SEP-00:10
October 0.151242E+09 0.00 20.51 26460.26 25-OCT-06:10 0.00 23.67 25.21 0.00 0.00 0.00 0.01 25-OCT-06:10
November 0.177575E+11 0.00 175.47 917738.02 28-NOV-06:01 0.00 25.27 38.34 0.03 0.00 0.00 0.46 28-NOV-06:01
December 0.820720E+11 0.00 353.60 975525.82 27-DEC-05:01 0.00 26.05 51.05 0.15 0.00 0.02 0.49 27-DEC-05:01
                           
Annual Sum or Average 0.202047E+12 0.00 1221.91     0.00 25.05 32.46 0.03 0.00 0.00    
Minimum of Months 0.00 0.00 0.00 0.00   0.00 23.67 24.42 0.00 0.00 0.00 0.00  
Maximum of Months 0.820720E+11 0.00 353.60 975525.82   0.00 27.34 51.05 0.15 0.00 0.02 0.49  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 20.13 20.13 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 23.40 23.40 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 26.87 26.87 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 33.49 33.49 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:05 0.00 28.06 28.06 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 35.27 35.27 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:03 0.00 38.22 38.22 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 39.89 39.89 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 27.71 27.71 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 26.64 26.64 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 26.29 26.29 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 27.91 27.91 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 29.53 29.53 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 20.13 20.13 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 39.89 39.89 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.248598E+10 0.00 56.20 0.248598E+10 0.00 0.00 0.00 0.00 42006.65 03-JAN-15:00 42006.65 03-JAN-15:00 0.00 0.00 0.00
February 0.893686E+10 0.00 122.69 0.893686E+10 0.00 0.00 0.00 0.00 69853.87 21-FEB-16:00 69853.87 21-FEB-16:00 0.00 0.00 0.00
March 0.223285E+11 0.00 233.40 0.223285E+11 0.00 0.00 0.00 0.00 82916.34 21-MAR-16:00 82916.34 21-MAR-16:00 0.00 0.00 0.00
April 0.635891E+11 0.00 454.11 0.635891E+11 0.00 0.00 0.00 0.00 109641.80 21-APR-14:40 109641.80 21-APR-14:40 0.00 0.00 0.00
May 0.937041E+11 0.00 512.29 0.935907E+11 0.00 0.00 0.00 0.00 138677.38 30-MAY-05:02 138677.38 30-MAY-05:02 0.00 0.00 0.00
June 0.131273E+12 0.00 601.30 0.130873E+12 0.00 0.00 0.00 0.00 148145.89 08-JUN-05:02 148145.89 08-JUN-05:02 0.00 0.00 0.00
July 0.160633E+12 0.00 639.82 0.135572E+12 0.00 0.00 0.00 0.00 277627.99 21-JUL-05:02 159742.00 03-JUL-05:02 0.00 0.00 0.00
August 0.145010E+12 0.00 654.06 0.135565E+12 0.00 0.00 0.00 0.00 236041.98 02-AUG-05:02 158815.78 07-AUG-05:02 0.00 0.00 0.00
September 0.101219E+12 0.00 484.28 0.940994E+11 0.00 0.00 0.00 0.00 237531.91 22-SEP-05:02 124096.95 13-SEP-05:02 0.00 0.00 0.00
October 0.564725E+11 0.00 377.09 0.546715E+11 0.00 0.00 0.00 0.00 131118.94 02-OCT-05:02 131118.94 02-OCT-05:02 0.00 0.00 0.00
November 0.165289E+11 0.00 177.43 0.165289E+11 0.00 0.00 0.00 0.00 77675.94 03-NOV-16:00 77675.94 03-NOV-16:00 0.00 0.00 0.00
December 0.117080E+10 0.00 43.28 0.117080E+10 0.00 0.00 0.00 0.00 23769.35 20-DEC-15:00 23769.35 20-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.803351E+12 0.00 4355.95 0.759411E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.117080E+10 0.00 43.28 0.117080E+10 0.00 0.00 0.00 0.00 23769.35   23769.35   0.00 0.00 0.00
Maximum of Months 0.160633E+12 0.00 654.06 0.135572E+12 0.00 0.00 0.00 0.00 277627.99   159742.00   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.184799E+11 0.00 107.22 0.184799E+11 0.00 0.00 0.00 0.00 307960.66 03-JAN-14:30 307960.66 03-JAN-14:30 0.00 0.00 0.00
February 0.664567E+11 0.00 149.21 0.664567E+11 0.00 0.00 0.00 0.00 480575.53 21-FEB-16:00 480575.53 21-FEB-16:00 0.00 0.00 0.00
March 0.160573E+12 0.00 235.24 0.160573E+12 0.00 0.00 0.00 0.00 631219.85 21-MAR-16:00 631219.85 21-MAR-16:00 0.00 0.00 0.00
April 0.455301E+12 0.00 359.85 0.455301E+12 0.00 0.00 0.00 0.00 941838.39 21-APR-14:50 941838.39 21-APR-14:50 0.00 0.00 0.00
May 0.818990E+12 0.00 478.85 0.818055E+12 0.00 0.00 0.00 0.00 1287962.49 30-MAY-05:02 1287962.49 30-MAY-05:02 0.00 0.00 0.00
June 0.110613E+13 0.00 520.07 0.110372E+13 0.00 0.00 0.00 0.00 1376388.28 08-JUN-05:02 1376388.28 08-JUN-05:02 0.00 0.00 0.00
July 0.122677E+13 0.00 525.63 0.105488E+13 0.00 0.00 0.00 0.00 2606947.46 21-JUL-05:02 1315382.95 01-JUL-05:02 0.00 0.00 0.00
August 0.106085E+13 0.00 523.72 0.100255E+13 0.00 0.00 0.00 0.00 2306519.97 02-AUG-05:02 1320859.00 07-AUG-05:02 0.00 0.00 0.00
September 0.858480E+12 0.00 442.15 0.800010E+12 0.00 0.00 0.00 0.00 2123298.89 22-SEP-05:02 1087212.23 13-SEP-05:02 0.00 0.00 0.00
October 0.442585E+12 0.00 350.87 0.427627E+12 0.00 0.00 0.00 0.00 1247106.22 05-OCT-05:03 949007.53 05-OCT-05:03 0.00 0.00 0.00
November 0.119447E+12 0.00 188.38 0.119447E+12 0.00 0.00 0.00 0.00 600477.10 03-NOV-16:00 600477.10 03-NOV-16:00 0.00 0.00 0.00
December 0.721307E+10 0.00 86.75 0.721307E+10 0.00 0.00 0.00 0.00 136131.25 20-DEC-15:00 136131.25 20-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.634128E+13 0.00 3967.93 0.603431E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.721307E+10 0.00 86.75 0.721307E+10 0.00 0.00 0.00 0.00 136131.25   136131.25   0.00 0.00 0.00
Maximum of Months 0.122677E+13 0.00 525.63 0.110372E+13 0.00 0.00 0.00 0.00 2606947.46   1376388.28   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.125096E+10 0.00 48.83 0.125096E+10 0.00 0.00 0.00 0.00 21723.10 03-JAN-15:00 21723.10 03-JAN-15:00 0.00 0.00 0.00
February 0.527178E+10 0.00 105.78 0.527178E+10 0.00 0.00 0.00 0.00 40215.97 21-FEB-16:20 40215.97 21-FEB-16:20 0.00 0.00 0.00
March 0.141380E+11 0.00 205.05 0.141380E+11 0.00 0.00 0.00 0.00 63977.73 21-MAR-16:00 63977.73 21-MAR-16:00 0.00 0.00 0.00
April 0.488827E+11 0.00 350.83 0.488827E+11 0.00 0.00 0.00 0.00 112516.25 21-APR-14:40 112516.25 21-APR-14:40 0.00 0.00 0.00
May 0.916710E+11 0.00 475.12 0.915640E+11 0.00 0.00 0.00 0.00 135874.88 30-MAY-05:02 135874.88 30-MAY-05:02 0.00 0.00 0.00
June 0.128898E+12 0.00 533.80 0.128608E+12 0.00 0.00 0.00 0.00 142583.53 15-JUN-14:30 142583.53 15-JUN-14:30 0.00 0.00 0.00
July 0.141861E+12 0.00 543.20 0.123545E+12 0.00 0.00 0.00 0.00 267755.16 17-JUL-05:02 157763.77 03-JUL-05:02 0.00 0.00 0.00
August 0.120285E+12 0.00 533.94 0.114372E+12 0.00 0.00 0.00 0.00 249467.46 02-AUG-05:02 147891.61 07-AUG-05:02 0.00 0.00 0.00
September 0.935412E+11 0.00 440.42 0.880213E+11 0.00 0.00 0.00 0.00 207105.33 22-SEP-05:02 122480.82 20-SEP-15:50 0.00 0.00 0.00
October 0.445335E+11 0.00 339.01 0.432296E+11 0.00 0.00 0.00 0.00 124837.92 03-OCT-14:00 111307.70 05-OCT-16:00 0.00 0.00 0.00
November 0.928344E+10 0.00 157.19 0.928344E+10 0.00 0.00 0.00 0.00 61812.88 09-NOV-15:00 61812.88 09-NOV-15:00 0.00 0.00 0.00
December 0.447675E+09 0.00 28.35 0.447675E+09 0.00 0.00 0.00 0.00 10907.30 23-DEC-15:00 10907.30 23-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.700064E+12 0.00 3761.53 0.668614E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.447675E+09 0.00 28.35 0.447675E+09 0.00 0.00 0.00 0.00 10907.30   10907.30   0.00 0.00 0.00
Maximum of Months 0.141861E+12 0.00 543.20 0.128608E+12 0.00 0.00 0.00 0.00 267755.16   157763.77   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.122315E+10 0.00 28.27 0.122315E+10 0.00 0.00 0.00 0.00 29395.47 03-JAN-15:00 29395.47 03-JAN-15:00 0.00 0.00 0.00
February 0.405938E+10 0.00 55.59 0.405938E+10 0.00 0.00 0.00 0.00 49187.97 21-FEB-15:00 49187.97 21-FEB-15:00 0.00 0.00 0.00
March 0.105637E+11 0.00 140.60 0.105637E+11 0.00 0.00 0.00 0.00 46577.82 21-MAR-16:00 46577.82 21-MAR-16:00 0.00 0.00 0.00
April 0.306894E+11 0.00 261.46 0.306894E+11 0.00 0.00 0.00 0.00 68430.28 03-APR-03:02 68430.28 03-APR-03:02 0.00 0.00 0.00
May 0.535422E+11 0.00 376.90 0.535217E+11 0.00 0.00 0.00 0.00 109075.90 29-MAY-15:31 103673.04 29-MAY-16:41 0.00 0.00 0.00
June 0.686182E+11 0.00 409.27 0.685384E+11 0.00 0.00 0.00 0.00 105287.29 19-JUN-03:02 103743.31 15-JUN-04:03 0.00 0.00 0.00
July 0.819950E+11 0.00 407.88 0.713148E+11 0.00 0.00 0.00 0.00 157583.88 21-JUL-04:03 100025.63 03-JUL-03:13 0.00 0.00 0.00
August 0.783016E+11 0.00 451.45 0.744816E+11 0.00 0.00 0.00 0.00 148292.44 02-AUG-03:02 103724.65 20-AUG-15:36 0.00 0.00 0.00
September 0.640514E+11 0.00 385.98 0.610235E+11 0.00 0.00 0.00 0.00 146286.35 10-SEP-17:07 96525.95 10-SEP-17:07 0.00 0.00 0.00
October 0.360607E+11 0.00 287.27 0.354924E+11 0.00 0.00 0.00 0.00 105648.24 04-OCT-03:02 94045.38 01-OCT-14:05 0.00 0.00 0.00
November 0.986823E+10 0.00 128.82 0.986795E+10 0.00 0.00 0.00 0.00 54919.96 10-NOV-04:02 54919.96 10-NOV-04:02 0.00 0.00 0.00
December 0.264991E+09 0.00 15.39 0.264991E+09 0.00 0.00 0.00 0.00 13072.44 11-DEC-06:03 13072.44 11-DEC-06:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.439238E+12 0.00 2948.87 0.421041E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.264991E+09 0.00 15.39 0.264991E+09 0.00 0.00 0.00 0.00 13072.44   13072.44   0.00 0.00 0.00
Maximum of Months 0.819950E+11 0.00 451.45 0.744816E+11 0.00 0.00 0.00 0.00 157583.88   103743.31   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.478448E+10 0.119185E+10 744.00 0.477237E+10 12109771.67 0.00 0.32 01-JAN-16:50 0.15 28-JAN-08:00 2559.03 01-JAN-16:50 2553.48 01-JAN-16:45 77.48 12-JAN-17:00 601.12 01-JAN-16:50 0.00
February 0.922526E+10 0.220530E+10 672.00 0.921072E+10 14531638.69 0.00 0.58 20-FEB-17:03 0.40 01-FEB-07:50 4574.52 20-FEB-17:30 4574.52 20-FEB-17:30 219.23 13-FEB-16:10 1228.99 20-FEB-16:53 0.00
March 0.156064E+11 0.360124E+10 744.00 0.156031E+11 3273606.56 0.00 0.91 31-MAR-24:00 0.61 01-MAR-07:05 7713.09 31-MAR-24:00 7713.09 31-MAR-24:00 112.62 11-MAR-10:20 1768.16 21-MAR-16:00 0.00
April 0.203006E+11 0.502387E+10 720.00 0.202814E+11 19187309.31 0.00 1.00 01-APR-13:50 0.33 30-APR-24:00 8414.12 30-APR-19:03 8414.12 30-APR-19:03 154.80 18-APR-11:10 2698.90 21-APR-15:00 0.00
May 0.615046E+10 0.181585E+10 744.00 0.608656E+10 63895167.11 0.00 0.51 31-MAY-24:00 0.23 06-MAY-06:10 4082.86 31-MAY-24:00 4057.23 31-MAY-24:00 257.85 24-MAY-13:10 1191.93 31-MAY-23:10 0.00
June 0.110482E+11 0.347402E+10 720.00 0.109314E+11 0.116788E+09 0.00 0.73 30-JUN-23:33 0.47 13-JUN-06:10 5922.12 30-JUN-23:45 5922.12 30-JUN-23:45 325.64 19-JUN-18:00 1929.16 02-JUN-16:00 0.00
July 0.166954E+11 0.497174E+10 744.00 0.163489E+11 0.346506E+09 0.00 0.94 31-JUL-23:23 0.69 05-JUL-06:10 7893.15 31-JUL-23:53 7868.68 31-JUL-23:53 636.74 20-JUL-15:00 2553.64 02-JUL-16:01 0.00
August 0.215762E+11 0.607468E+10 744.00 0.212811E+11 0.295142E+09 0.00 1.00 01-AUG-14:20 0.33 31-AUG-24:00 8566.76 08-AUG-16:30 8371.19 27-AUG-19:45 486.65 01-AUG-21:00 2961.58 07-AUG-16:00 0.00
September 0.619380E+10 0.177290E+10 720.00 0.597764E+10 0.216169E+09 0.00 0.50 30-SEP-24:00 0.23 30-SEP-06:40 4087.16 30-SEP-24:00 4087.16 30-SEP-24:00 353.17 14-SEP-10:20 1013.48 01-SEP-16:00 0.00
October 0.111228E+11 0.274585E+10 744.00 0.109660E+11 0.156737E+09 0.00 0.70 31-OCT-24:00 0.44 25-OCT-07:00 5888.90 31-OCT-24:00 5888.90 31-OCT-24:00 379.67 04-OCT-10:00 1597.37 03-OCT-14:00 0.00
November 0.151783E+11 0.340282E+10 720.00 0.151400E+11 38217440.48 0.00 0.79 19-NOV-16:35 0.62 28-NOV-07:05 6544.47 12-NOV-16:50 6540.46 12-NOV-16:50 214.34 02-NOV-15:40 1698.31 03-NOV-16:00 0.00
December 0.203744E+11 0.442976E+10 744.00 0.203687E+11 5679756.30 0.00 0.97 17-DEC-16:40 0.81 05-DEC-07:05 8231.89 17-DEC-16:40 8231.89 17-DEC-16:40 91.18 14-DEC-15:10 1815.88 17-DEC-16:40 0.00
                                       
Annual Sum or Average 0.158256E+12 0.407099E+11 8760.00 0.156968E+12 0.128824E+10 0.00                         0.00
Minimum of Months 0.478448E+10 0.119185E+10 672.00 0.477237E+10 3273606.56 0.00 0.32   0.15   2559.03   2553.48   77.48   601.12   0.00
Maximum of Months 0.215762E+11 0.607468E+10 744.00 0.212811E+11 0.346506E+09 0.00 1.00   0.81   8566.76   8414.12   636.74   2961.58   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.312502E+11 0.802871E+10 744.00 0.311377E+11 0.112546E+09 0.00 0.28 30-JAN-17:00 0.06 28-JAN-07:05 21199.08 12-JAN-16:40 20506.03 02-JAN-17:00 758.34 12-JAN-17:00 5246.55 03-JAN-17:00 0.00
February 0.773980E+11 0.187339E+11 672.00 0.772535E+11 0.144535E+09 0.00 0.55 21-FEB-17:00 0.32 02-FEB-07:10 40773.85 21-FEB-17:00 40773.85 21-FEB-17:00 2152.98 13-FEB-16:30 11107.50 21-FEB-17:00 0.00
March 0.141075E+12 0.327846E+11 744.00 0.141041E+12 33222222.36 0.00 0.89 31-MAR-24:00 0.55 01-MAR-07:05 71715.20 31-MAR-24:00 71715.20 31-MAR-24:00 1116.49 11-MAR-10:20 16736.72 21-MAR-16:00 0.00
April 0.191859E+12 0.475697E+11 720.00 0.191665E+12 0.194391E+09 0.00 1.00 01-APR-14:50 0.30 30-APR-24:00 79953.39 30-APR-18:53 79953.39 30-APR-18:53 1549.17 18-APR-11:10 25693.26 21-APR-15:00 0.00
May 0.569199E+11 0.168729E+11 744.00 0.562888E+11 0.631173E+09 0.00 0.53 31-MAY-24:00 0.21 06-MAY-06:20 39892.61 31-MAY-24:00 39645.13 31-MAY-24:00 2560.64 24-MAY-13:10 11571.79 31-MAY-23:13 0.00
June 0.105110E+12 0.330540E+11 720.00 0.103949E+12 0.116055E+10 0.00 0.74 30-JUN-23:53 0.46 13-JUN-06:10 57447.76 30-JUN-23:53 57447.76 30-JUN-23:53 3213.02 28-JUN-11:00 18438.27 02-JUN-16:00 0.00
July 0.158954E+12 0.473245E+11 744.00 0.155500E+12 0.345443E+10 0.00 0.95 31-JUL-23:13 0.69 05-JUL-06:10 75752.83 31-JUL-23:53 75514.74 31-JUL-23:53 6337.70 20-JUL-15:00 24103.18 03-JUL-16:00 0.00
August 0.205514E+12 0.578511E+11 744.00 0.202567E+12 0.294787E+10 0.00 1.00 01-AUG-12:10 0.30 31-AUG-24:00 81774.95 08-AUG-16:30 79116.90 31-AUG-17:40 4803.61 01-AUG-21:00 28191.83 07-AUG-16:00 0.00
September 0.567156E+11 0.163043E+11 720.00 0.545882E+11 0.212740E+10 0.00 0.49 30-SEP-24:00 0.21 30-SEP-06:40 38249.15 30-SEP-24:00 38249.15 30-SEP-24:00 3491.41 14-SEP-10:20 9471.96 19-SEP-16:00 0.00
October 0.101087E+12 0.251075E+11 744.00 0.995356E+11 0.155097E+10 0.00 0.68 31-OCT-24:00 0.40 25-OCT-07:00 54329.17 31-OCT-24:00 54329.17 31-OCT-24:00 3769.39 04-OCT-10:00 15152.90 03-OCT-14:00 0.00
November 0.134258E+12 0.303754E+11 720.00 0.133876E+12 0.381540E+09 0.00 0.76 09-NOV-16:40 0.53 28-NOV-07:05 61456.64 09-NOV-16:40 60253.38 09-NOV-16:40 2138.05 02-NOV-15:40 16031.91 03-NOV-16:00 0.00
December 0.177324E+12 0.390330E+11 744.00 0.177265E+12 58698710.82 0.00 0.92 20-DEC-16:50 0.71 27-DEC-07:10 74905.29 15-DEC-16:50 74905.29 15-DEC-16:50 912.70 14-DEC-16:00 16603.08 20-DEC-15:00 0.00
                                       
Annual Sum or Average 0.143747E+13 0.373040E+12 8760.00 0.142467E+13 0.127973E+11 0.00                         0.00
Minimum of Months 0.312502E+11 0.802871E+10 672.00 0.311377E+11 33222222.36 0.00 0.28   0.06   21199.08   20506.03   758.34   5246.55   0.00
Maximum of Months 0.205514E+12 0.578511E+11 744.00 0.202567E+12 0.345443E+10 0.00 1.00   0.71   81774.95   79953.39   6337.70   28191.83   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.134996E+10 0.364965E+09 563.47 0.134126E+10 8705378.54 0.00 0.27 12-JAN-16:40 0.00 01-JAN-04:33 2077.31 12-JAN-16:40 2006.35 12-JAN-16:40 74.76 12-JAN-17:00 500.82 12-JAN-16:30 0.00
February 0.638112E+10 0.157273E+10 672.00 0.636713E+10 13994324.22 0.00 0.54 21-FEB-17:00 0.19 03-FEB-07:10 4054.62 21-FEB-17:00 4054.62 21-FEB-17:00 210.42 13-FEB-17:00 1106.93 21-FEB-17:00 0.00
March 0.131239E+11 0.308355E+10 744.00 0.131207E+11 3259480.23 0.00 0.85 31-MAR-23:20 0.44 02-MAR-07:10 6869.66 31-MAR-23:20 6869.66 31-MAR-23:20 109.74 11-MAR-10:20 1684.96 21-MAR-16:00 0.00
April 0.189418E+11 0.472312E+10 720.00 0.189224E+11 19344212.35 0.00 1.00 01-APR-15:40 0.29 30-APR-24:00 8136.71 30-APR-19:05 8136.71 30-APR-19:05 155.29 18-APR-11:10 2608.80 21-APR-15:00 0.00
May 0.570805E+10 0.170174E+10 744.00 0.564479E+10 63259412.13 0.00 0.52 31-MAY-24:00 0.16 02-MAY-06:40 3997.71 31-MAY-24:00 3972.83 31-MAY-24:00 260.53 24-MAY-13:10 1160.58 31-MAY-23:10 0.00
June 0.106560E+11 0.335679E+10 720.00 0.105398E+11 0.116231E+09 0.00 0.74 30-JUN-23:33 0.45 13-JUN-06:10 5764.66 30-JUN-23:45 5764.66 30-JUN-23:45 322.37 28-JUN-11:00 1883.23 02-JUN-16:00 0.00
July 0.160730E+11 0.479236E+10 744.00 0.157274E+11 0.345566E+09 0.00 0.94 31-JUL-23:13 0.67 05-JUL-06:10 7606.60 31-JUL-23:53 7582.65 31-JUL-23:53 634.30 20-JUL-15:00 2536.84 02-JUL-16:11 0.00
August 0.206505E+11 0.582620E+10 744.00 0.203557E+11 0.294751E+09 0.00 1.00 01-AUG-14:10 0.30 31-AUG-24:00 8296.20 08-AUG-16:30 8125.22 27-AUG-19:53 480.19 01-AUG-21:00 2862.83 07-AUG-16:00 0.00
September 0.567119E+10 0.163930E+10 720.00 0.545808E+10 0.213115E+09 0.00 0.47 30-SEP-23:30 0.16 30-SEP-07:00 3688.99 30-SEP-23:30 3688.99 30-SEP-23:30 354.90 14-SEP-10:30 981.60 19-SEP-16:00 0.00
October 0.963091E+10 0.241495E+10 744.00 0.947660E+10 0.154316E+09 0.00 0.64 31-OCT-23:30 0.32 25-OCT-07:00 5116.19 31-OCT-23:30 5116.19 31-OCT-23:30 377.58 04-OCT-10:00 1544.24 03-OCT-14:00 0.00
November 0.120213E+11 0.275822E+10 720.00 0.119834E+11 37858346.15 0.00 0.75 09-NOV-16:40 0.39 27-NOV-05:01 6170.39 09-NOV-16:50 6049.93 09-NOV-16:40 214.64 02-NOV-15:40 1609.68 03-NOV-16:00 0.00
December 0.156436E+11 0.350275E+10 744.00 0.156379E+11 5772192.08 0.00 0.89 20-DEC-16:50 0.57 04-DEC-04:30 7344.98 15-DEC-16:50 7344.98 15-DEC-16:50 90.95 14-DEC-16:00 1602.81 20-DEC-16:50 0.00
                                       
Annual Sum or Average 0.135851E+12 0.357367E+11 8579.47 0.134575E+12 0.127617E+10 0.00                         0.00
Minimum of Months 0.134996E+10 0.364965E+09 563.47 0.134126E+10 3259480.23 0.00 0.27   0.00   2077.31   2006.35   74.76   500.82   0.00
Maximum of Months 0.206505E+11 0.582620E+10 744.00 0.203557E+11 0.345566E+09 0.00 1.00   0.67   8296.20   8136.71   634.30   2862.83   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.11 0.00 77.11 9.87 444.81 0.00 0.00 0.00
February 94.16 0.00 94.16 33.88 395.32 0.00 0.00 0.00
March 123.22 0.00 123.22 76.68 332.62 0.00 0.00 0.00
April 142.27 1.12 141.15 157.76 188.86 0.00 0.00 0.00
May 168.74 12.20 156.54 270.51 106.90 0.00 0.00 0.00
June 179.43 22.09 157.34 375.99 54.38 0.00 0.00 0.00
July 165.83 16.14 149.68 344.90 43.57 0.00 0.00 0.00
August 139.83 2.86 136.97 266.58 61.45 0.00 0.00 0.00
September 122.01 0.05 121.96 202.88 127.27 0.00 0.00 0.00
October 101.30 0.00 101.30 101.76 214.96 0.00 0.00 0.00
November 81.78 0.00 81.78 21.37 386.01 0.00 0.00 0.00
December 76.51 0.00 76.51 5.64 506.15 0.00 0.00 0.00
                 
Annual Sum or Average 122.82 4.56 118.26 156.28 237.78 0.00 0.00 0.00
Minimum of Months 76.51 0.00 76.51 5.64 43.57 0.00 0.00 0.00
Maximum of Months 179.43 22.09 157.34 375.99 506.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.11 0.00 77.11 9.87 444.81 0.00 0.00 0.00
February 94.16 0.00 94.16 33.88 395.32 0.00 0.00 0.00
March 123.22 0.00 123.22 76.68 332.62 0.00 0.00 0.00
April 142.27 1.12 141.15 157.76 188.86 0.00 0.00 0.00
May 168.74 12.20 156.54 270.51 106.90 0.00 0.00 0.00
June 179.43 22.09 157.34 375.98 54.38 0.00 0.00 0.00
July 165.82 16.14 149.68 344.90 43.57 0.00 0.00 0.00
August 139.83 2.86 136.97 266.57 61.45 0.00 0.00 0.00
September 122.01 0.05 121.96 202.88 127.27 0.00 0.00 0.00
October 101.30 0.00 101.30 101.76 214.96 0.00 0.00 0.00
November 81.78 0.00 81.78 21.37 386.01 0.00 0.00 0.00
December 76.51 0.00 76.51 5.64 506.15 0.00 0.00 0.00
                 
Annual Sum or Average 122.82 4.56 118.26 156.28 237.78 0.00 0.00 0.00
Minimum of Months 76.51 0.00 76.51 5.64 43.57 0.00 0.00 0.00
Maximum of Months 179.43 22.09 157.34 375.98 506.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.11 0.00 77.11 9.87 444.81 0.00 0.00 0.00
February 94.16 0.00 94.16 33.88 395.32 0.00 0.00 0.00
March 123.22 0.00 123.22 76.68 332.62 0.00 0.00 0.00
April 142.27 1.12 141.15 157.76 188.86 0.00 0.00 0.00
May 168.74 12.20 156.54 270.51 106.90 0.00 0.00 0.00
June 179.43 22.09 157.34 375.99 54.38 0.00 0.00 0.00
July 165.82 16.14 149.68 344.90 43.57 0.00 0.00 0.00
August 139.83 2.86 136.97 266.58 61.45 0.00 0.00 0.00
September 122.01 0.05 121.96 202.88 127.27 0.00 0.00 0.00
October 101.30 0.00 101.30 101.76 214.96 0.00 0.00 0.00
November 81.78 0.00 81.78 21.37 386.01 0.00 0.00 0.00
December 76.51 0.00 76.51 5.64 506.15 0.00 0.00 0.00
                 
Annual Sum or Average 122.82 4.56 118.26 156.28 237.78 0.00 0.00 0.00
Minimum of Months 76.51 0.00 76.51 5.64 43.57 0.00 0.00 0.00
Maximum of Months 179.43 22.09 157.34 375.99 506.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.11 0.00 77.11 9.87 444.81 0.00 0.00 0.00
February 94.16 0.00 94.16 33.88 395.32 0.00 0.00 0.00
March 123.22 0.00 123.22 76.68 332.62 0.00 0.00 0.00
April 142.27 1.12 141.15 157.76 188.86 0.00 0.00 0.00
May 168.74 12.20 156.54 270.51 106.90 0.00 0.00 0.00
June 179.43 22.09 157.34 375.98 54.38 0.00 0.00 0.00
July 165.82 16.14 149.68 344.90 43.57 0.00 0.00 0.00
August 139.83 2.86 136.97 266.57 61.45 0.00 0.00 0.00
September 122.01 0.05 121.96 202.88 127.27 0.00 0.00 0.00
October 101.30 0.00 101.30 101.76 214.96 0.00 0.00 0.00
November 81.78 0.00 81.78 21.37 386.01 0.00 0.00 0.00
December 76.51 0.00 76.51 5.64 506.15 0.00 0.00 0.00
                 
Annual Sum or Average 122.82 4.56 118.26 156.28 237.78 0.00 0.00 0.00
Minimum of Months 76.51 0.00 76.51 5.64 43.57 0.00 0.00 0.00
Maximum of Months 179.43 22.09 157.34 375.98 506.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.10 0.00 77.10 9.87 444.79 0.00 0.00 0.00
February 94.15 0.00 94.15 33.87 395.31 0.00 0.00 0.00
March 123.22 0.00 123.22 76.67 332.61 0.00 0.00 0.00
April 142.27 1.12 141.15 157.75 188.85 0.00 0.00 0.00
May 168.73 12.20 156.53 270.50 106.89 0.00 0.00 0.00
June 179.42 22.09 157.33 375.97 54.38 0.00 0.00 0.00
July 165.82 16.14 149.68 344.89 43.57 0.00 0.00 0.00
August 139.82 2.86 136.96 266.56 61.45 0.00 0.00 0.00
September 122.01 0.05 121.96 202.87 127.26 0.00 0.00 0.00
October 101.30 0.00 101.30 101.76 214.95 0.00 0.00 0.00
November 81.78 0.00 81.78 21.37 385.99 0.00 0.00 0.00
December 76.51 0.00 76.51 5.64 506.13 0.00 0.00 0.00
                 
Annual Sum or Average 122.82 4.56 118.25 156.27 237.77 0.00 0.00 0.00
Minimum of Months 76.51 0.00 76.51 5.64 43.57 0.00 0.00 0.00
Maximum of Months 179.42 22.09 157.33 375.97 506.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 229.15 124.31 104.85 213.13 450.36 0.00 0.00 0.00
February 306.59 174.75 131.83 337.64 397.00 0.00 0.00 0.00
March 378.53 208.56 169.97 460.33 332.31 0.00 0.00 0.00
April 456.11 253.04 203.07 665.89 191.87 0.00 0.00 0.00
May 470.68 255.80 214.88 773.12 118.81 0.00 0.00 0.00
June 470.95 262.00 208.95 872.09 57.35 0.00 0.00 0.00
July 422.34 220.79 201.55 785.50 44.79 0.00 0.00 0.00
August 401.88 205.68 196.20 720.51 62.85 0.00 0.00 0.00
September 398.15 227.17 170.98 665.65 132.80 0.00 0.00 0.00
October 306.20 165.26 140.95 430.53 222.85 0.00 0.00 0.00
November 274.48 159.80 114.69 296.31 382.10 0.00 0.00 0.00
December 228.96 121.31 107.65 199.33 496.72 0.00 0.00 0.00
                 
Annual Sum or Average 362.04 198.10 163.94 535.64 240.08 0.00 0.00 0.00
Minimum of Months 228.96 121.31 104.85 199.33 44.79 0.00 0.00 0.00
Maximum of Months 470.95 262.00 214.88 872.09 496.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 229.15 124.31 104.85 213.13 450.36 0.00 0.00 0.00
February 306.59 174.75 131.83 337.64 397.00 0.00 0.00 0.00
March 378.53 208.56 169.97 460.33 332.31 0.00 0.00 0.00
April 456.11 253.04 203.07 665.89 191.87 0.00 0.00 0.00
May 470.68 255.80 214.88 773.12 118.81 0.00 0.00 0.00
June 470.95 262.00 208.95 872.09 57.35 0.00 0.00 0.00
July 422.34 220.79 201.55 785.50 44.79 0.00 0.00 0.00
August 401.88 205.68 196.20 720.51 62.85 0.00 0.00 0.00
September 398.15 227.17 170.98 665.65 132.80 0.00 0.00 0.00
October 306.20 165.26 140.95 430.53 222.85 0.00 0.00 0.00
November 274.48 159.80 114.69 296.31 382.10 0.00 0.00 0.00
December 228.96 121.31 107.65 199.33 496.72 0.00 0.00 0.00
                 
Annual Sum or Average 362.04 198.10 163.94 535.64 240.08 0.00 0.00 0.00
Minimum of Months 228.96 121.31 104.85 199.33 44.79 0.00 0.00 0.00
Maximum of Months 470.95 262.00 214.88 872.09 496.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 229.15 124.31 104.84 213.12 450.35 0.00 0.00 0.00
February 306.58 174.75 131.83 337.63 396.99 0.00 0.00 0.00
March 378.53 208.56 169.97 460.32 332.30 0.00 0.00 0.00
April 456.10 253.04 203.07 665.88 191.87 0.00 0.00 0.00
May 470.68 255.79 214.88 773.10 118.81 0.00 0.00 0.00
June 470.94 261.99 208.95 872.07 57.34 0.00 0.00 0.00
July 422.33 220.79 201.54 785.49 44.79 0.00 0.00 0.00
August 401.87 205.67 196.20 720.50 62.85 0.00 0.00 0.00
September 398.14 227.17 170.97 665.63 132.80 0.00 0.00 0.00
October 306.20 165.25 140.95 430.52 222.85 0.00 0.00 0.00
November 274.48 159.79 114.69 296.31 382.09 0.00 0.00 0.00
December 228.95 121.30 107.65 199.33 496.71 0.00 0.00 0.00
                 
Annual Sum or Average 362.04 198.09 163.94 535.63 240.08 0.00 0.00 0.00
Minimum of Months 228.95 121.30 104.84 199.33 44.79 0.00 0.00 0.00
Maximum of Months 470.94 261.99 214.88 872.07 496.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 527.48 399.62 127.86 702.28 391.37 0.00 0.00 0.00
February 489.30 344.95 144.35 662.27 354.84 0.00 0.00 0.00
March 397.66 229.29 168.37 554.23 314.75 0.00 0.00 0.00
April 269.61 100.60 169.01 424.40 195.60 0.00 0.00 0.00
May 190.53 26.67 163.86 334.38 115.00 0.00 0.00 0.00
June 164.38 10.43 153.95 354.44 56.10 0.00 0.00 0.00
July 167.57 15.53 152.04 358.09 45.63 0.00 0.00 0.00
August 213.60 56.54 157.06 429.51 65.85 0.00 0.00 0.00
September 333.41 173.22 160.19 612.40 132.71 0.00 0.00 0.00
October 453.01 306.26 146.74 711.50 210.97 0.00 0.00 0.00
November 545.15 415.61 129.54 758.75 341.22 0.00 0.00 0.00
December 540.26 405.55 134.72 701.25 427.74 0.00 0.00 0.00
                 
Annual Sum or Average 356.91 206.24 150.67 549.51 220.32 0.00 0.00 0.00
Minimum of Months 164.38 10.43 127.86 334.38 45.63 0.00 0.00 0.00
Maximum of Months 545.15 415.61 169.01 758.75 427.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 527.48 399.62 127.86 702.27 391.37 0.00 0.00 0.00
February 489.30 344.95 144.35 662.27 354.84 0.00 0.00 0.00
March 397.66 229.29 168.37 554.22 314.75 0.00 0.00 0.00
April 269.61 100.60 169.01 424.40 195.60 0.00 0.00 0.00
May 190.53 26.67 163.86 334.37 115.00 0.00 0.00 0.00
June 164.38 10.43 153.95 354.44 56.10 0.00 0.00 0.00
July 167.57 15.53 152.03 358.09 45.63 0.00 0.00 0.00
August 213.60 56.54 157.06 429.51 65.85 0.00 0.00 0.00
September 333.41 173.22 160.19 612.39 132.71 0.00 0.00 0.00
October 453.00 306.26 146.74 711.49 210.97 0.00 0.00 0.00
November 545.15 415.61 129.54 758.75 341.22 0.00 0.00 0.00
December 540.26 405.54 134.72 701.24 427.74 0.00 0.00 0.00
                 
Annual Sum or Average 356.90 206.24 150.67 549.51 220.32 0.00 0.00 0.00
Minimum of Months 164.38 10.43 127.86 334.37 45.63 0.00 0.00 0.00
Maximum of Months 545.15 415.61 169.01 758.75 427.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 527.48 399.62 127.86 702.28 391.37 0.00 0.00 0.00
February 489.30 344.95 144.35 662.27 354.84 0.00 0.00 0.00
March 397.66 229.29 168.37 554.23 314.75 0.00 0.00 0.00
April 269.61 100.60 169.01 424.40 195.60 0.00 0.00 0.00
May 190.53 26.67 163.86 334.38 115.00 0.00 0.00 0.00
June 164.38 10.43 153.95 354.44 56.10 0.00 0.00 0.00
July 167.57 15.53 152.04 358.09 45.63 0.00 0.00 0.00
August 213.60 56.54 157.06 429.51 65.85 0.00 0.00 0.00
September 333.41 173.22 160.19 612.40 132.71 0.00 0.00 0.00
October 453.01 306.26 146.74 711.50 210.97 0.00 0.00 0.00
November 545.15 415.61 129.54 758.75 341.22 0.00 0.00 0.00
December 540.26 405.55 134.72 701.25 427.74 0.00 0.00 0.00
                 
Annual Sum or Average 356.91 206.24 150.67 549.51 220.32 0.00 0.00 0.00
Minimum of Months 164.38 10.43 127.86 334.38 45.63 0.00 0.00 0.00
Maximum of Months 545.15 415.61 169.01 758.75 427.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 527.48 399.62 127.86 702.27 391.37 0.00 0.00 0.00
February 489.30 344.95 144.35 662.27 354.84 0.00 0.00 0.00
March 397.66 229.29 168.37 554.22 314.75 0.00 0.00 0.00
April 269.61 100.60 169.01 424.40 195.60 0.00 0.00 0.00
May 190.53 26.67 163.86 334.37 115.00 0.00 0.00 0.00
June 164.38 10.43 153.95 354.44 56.10 0.00 0.00 0.00
July 167.57 15.53 152.03 358.09 45.63 0.00 0.00 0.00
August 213.60 56.54 157.06 429.51 65.85 0.00 0.00 0.00
September 333.41 173.22 160.19 612.39 132.71 0.00 0.00 0.00
October 453.00 306.26 146.74 711.49 210.97 0.00 0.00 0.00
November 545.15 415.61 129.54 758.75 341.22 0.00 0.00 0.00
December 540.26 405.54 134.72 701.24 427.74 0.00 0.00 0.00
                 
Annual Sum or Average 356.90 206.24 150.67 549.51 220.32 0.00 0.00 0.00
Minimum of Months 164.38 10.43 127.86 334.37 45.63 0.00 0.00 0.00
Maximum of Months 545.15 415.61 169.01 758.75 427.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 527.46 399.61 127.86 702.24 391.36 0.00 0.00 0.00
February 489.28 344.93 144.35 662.24 354.82 0.00 0.00 0.00
March 397.64 229.28 168.36 554.20 314.74 0.00 0.00 0.00
April 269.60 100.59 169.01 424.38 195.60 0.00 0.00 0.00
May 190.52 26.67 163.86 334.36 114.99 0.00 0.00 0.00
June 164.38 10.43 153.95 354.43 56.09 0.00 0.00 0.00
July 167.56 15.53 152.03 358.08 45.63 0.00 0.00 0.00
August 213.59 56.54 157.06 429.49 65.85 0.00 0.00 0.00
September 333.40 173.21 160.19 612.37 132.70 0.00 0.00 0.00
October 452.99 306.25 146.74 711.47 210.96 0.00 0.00 0.00
November 545.13 415.59 129.54 758.72 341.21 0.00 0.00 0.00
December 540.24 405.53 134.71 701.21 427.72 0.00 0.00 0.00
                 
Annual Sum or Average 356.89 206.23 150.66 549.49 220.31 0.00 0.00 0.00
Minimum of Months 164.38 10.43 127.86 334.36 45.63 0.00 0.00 0.00
Maximum of Months 545.13 415.59 169.01 758.72 427.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 241.39 135.94 105.44 250.76 502.22 0.00 0.00 0.00
February 272.38 144.78 127.60 301.35 465.37 0.00 0.00 0.00
March 371.18 198.94 172.24 458.11 403.88 0.00 0.00 0.00
April 426.64 230.43 196.20 618.98 251.76 0.00 0.00 0.00
May 459.53 245.87 213.66 758.44 146.88 0.00 0.00 0.00
June 447.32 240.26 207.06 824.80 80.68 0.00 0.00 0.00
July 396.96 197.26 199.70 728.24 70.64 0.00 0.00 0.00
August 384.44 195.92 188.51 676.08 97.54 0.00 0.00 0.00
September 393.15 219.02 174.12 666.19 163.81 0.00 0.00 0.00
October 338.43 197.52 140.91 491.59 267.93 0.00 0.00 0.00
November 284.07 172.97 111.10 332.80 459.42 0.00 0.00 0.00
December 228.92 124.35 104.56 216.88 594.46 0.00 0.00 0.00
                 
Annual Sum or Average 353.99 192.07 161.93 527.96 291.21 0.00 0.00 0.00
Minimum of Months 228.92 124.35 104.56 216.88 70.64 0.00 0.00 0.00
Maximum of Months 459.53 245.87 213.66 824.80 594.46 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 241.39 135.94 105.44 250.76 502.22 0.00 0.00 0.00
February 272.38 144.78 127.60 301.35 465.37 0.00 0.00 0.00
March 371.18 198.94 172.24 458.11 403.88 0.00 0.00 0.00
April 426.64 230.43 196.20 618.98 251.76 0.00 0.00 0.00
May 459.53 245.87 213.66 758.44 146.88 0.00 0.00 0.00
June 447.32 240.26 207.06 824.80 80.68 0.00 0.00 0.00
July 396.96 197.26 199.70 728.24 70.64 0.00 0.00 0.00
August 384.44 195.92 188.51 676.08 97.54 0.00 0.00 0.00
September 393.15 219.02 174.12 666.19 163.81 0.00 0.00 0.00
October 338.43 197.52 140.91 491.59 267.93 0.00 0.00 0.00
November 284.07 172.97 111.10 332.80 459.42 0.00 0.00 0.00
December 228.92 124.35 104.56 216.88 594.46 0.00 0.00 0.00
                 
Annual Sum or Average 353.99 192.07 161.93 527.96 291.21 0.00 0.00 0.00
Minimum of Months 228.92 124.35 104.56 216.88 70.64 0.00 0.00 0.00
Maximum of Months 459.53 245.87 213.66 824.80 594.46 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 241.38 135.94 105.44 250.76 502.21 0.00 0.00 0.00
February 272.38 144.77 127.60 301.34 465.36 0.00 0.00 0.00
March 371.17 198.93 172.24 458.10 403.88 0.00 0.00 0.00
April 426.63 230.43 196.20 618.97 251.75 0.00 0.00 0.00
May 459.52 245.86 213.66 758.43 146.88 0.00 0.00 0.00
June 447.31 240.25 207.05 824.79 80.68 0.00 0.00 0.00
July 396.95 197.25 199.70 728.23 70.64 0.00 0.00 0.00
August 384.43 195.92 188.51 676.07 97.54 0.00 0.00 0.00
September 393.14 219.02 174.12 666.18 163.81 0.00 0.00 0.00
October 338.43 197.52 140.91 491.58 267.92 0.00 0.00 0.00
November 284.06 172.96 111.10 332.79 459.41 0.00 0.00 0.00
December 228.91 124.35 104.56 216.88 594.45 0.00 0.00 0.00
                 
Annual Sum or Average 353.99 192.06 161.92 527.95 291.20 0.00 0.00 0.00
Minimum of Months 228.91 124.35 104.56 216.88 70.64 0.00 0.00 0.00
Maximum of Months 459.52 245.86 213.66 824.79 594.45 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 385.54 0.00 385.54 86.16 1972.65 0.00 0.00 0.00
February 470.79 0.00 470.79 218.63 1773.32 0.00 0.00 0.00
March 616.11 0.00 616.11 433.07 1511.20 0.00 0.00 0.00
April 711.37 5.60 705.76 825.39 886.54 0.00 0.00 0.00
May 843.71 61.01 782.69 1367.66 516.38 0.00 0.00 0.00
June 897.14 110.45 786.69 1896.08 274.43 0.00 0.00 0.00
July 829.13 80.71 748.42 1746.73 216.24 0.00 0.00 0.00
August 699.14 14.30 684.84 1364.46 294.68 0.00 0.00 0.00
September 610.06 0.24 609.81 1032.80 610.43 0.00 0.00 0.00
October 506.52 0.00 506.52 545.29 984.60 0.00 0.00 0.00
November 408.91 0.00 408.91 152.06 1698.04 0.00 0.00 0.00
December 382.56 0.00 382.56 58.93 2177.99 0.00 0.00 0.00
                 
Annual Sum or Average 614.11 22.81 591.30 813.65 1072.94 0.00 0.00 0.00
Minimum of Months 382.56 0.00 382.56 58.93 216.24 0.00 0.00 0.00
Maximum of Months 897.14 110.45 786.69 1896.08 2177.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 687.45 372.92 314.53 663.35 1232.79 0.00 0.00 0.00
February 919.75 524.25 395.50 1028.36 1113.48 0.00 0.00 0.00
March 1135.59 625.67 509.91 1385.30 953.49 0.00 0.00 0.00
April 1368.33 759.12 609.21 1982.90 579.01 0.00 0.00 0.00
May 1412.04 767.39 644.65 2304.69 356.03 0.00 0.00 0.00
June 1412.83 785.99 626.85 2601.10 184.91 0.00 0.00 0.00
July 1267.00 662.37 604.64 2343.13 148.73 0.00 0.00 0.00
August 1205.62 617.03 588.60 2150.53 202.03 0.00 0.00 0.00
September 1194.44 681.52 512.93 1986.87 397.87 0.00 0.00 0.00
October 918.60 495.76 422.84 1292.33 640.42 0.00 0.00 0.00
November 823.45 479.38 344.06 905.50 1063.30 0.00 0.00 0.00
December 686.86 363.92 322.95 626.48 1348.67 0.00 0.00 0.00
                 
Annual Sum or Average 1086.12 594.29 491.83 1607.74 682.95 0.00 0.00 0.00
Minimum of Months 686.86 363.92 314.53 626.48 148.73 0.00 0.00 0.00
Maximum of Months 1412.83 785.99 644.65 2601.10 1348.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2637.47 1998.16 639.31 3485.39 1922.93 0.00 0.00 0.00
February 2446.55 1724.78 721.77 3288.26 1740.64 0.00 0.00 0.00
March 1988.33 1146.46 841.86 2752.21 1534.88 0.00 0.00 0.00
April 1348.08 503.00 845.08 2119.36 955.70 0.00 0.00 0.00
May 952.67 133.34 819.33 1678.14 561.66 0.00 0.00 0.00
June 821.92 52.15 769.77 1793.68 280.22 0.00 0.00 0.00
July 837.85 77.67 760.18 1812.45 225.96 0.00 0.00 0.00
August 1068.03 282.71 785.32 2162.18 322.97 0.00 0.00 0.00
September 1667.08 866.10 800.97 3048.71 659.07 0.00 0.00 0.00
October 2265.07 1531.34 733.73 3535.66 1037.27 0.00 0.00 0.00
November 2725.80 2078.09 647.71 3775.11 1665.23 0.00 0.00 0.00
December 2701.37 2027.77 673.60 3502.72 2063.65 0.00 0.00 0.00
                 
Annual Sum or Average 1784.56 1031.22 753.34 2742.38 1077.52 0.00 0.00 0.00
Minimum of Months 821.92 52.15 639.31 1678.14 225.96 0.00 0.00 0.00
Maximum of Months 2725.80 2078.09 845.08 3775.11 2063.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 724.16 407.82 316.33 782.68 1339.80 0.00 0.00 0.00
February 817.13 434.32 382.81 942.61 1223.54 0.00 0.00 0.00
March 1113.52 596.81 516.71 1412.54 1063.09 0.00 0.00 0.00
April 1279.90 691.30 588.60 1893.19 669.16 0.00 0.00 0.00
May 1378.57 737.60 640.97 2279.41 415.07 0.00 0.00 0.00
June 1341.93 720.77 621.17 2497.05 223.53 0.00 0.00 0.00
July 1190.87 591.77 599.10 2220.41 182.58 0.00 0.00 0.00
August 1153.30 587.77 565.53 2068.48 242.92 0.00 0.00 0.00
September 1179.43 657.06 522.37 2008.50 461.72 0.00 0.00 0.00
October 1015.29 592.56 422.74 1501.02 717.58 0.00 0.00 0.00
November 852.19 518.89 333.30 1040.32 1175.48 0.00 0.00 0.00
December 686.74 373.06 313.68 703.32 1465.99 0.00 0.00 0.00
                 
Annual Sum or Average 1061.97 576.19 485.78 1615.26 762.72 0.00 0.00 0.00
Minimum of Months 686.74 373.06 313.68 703.32 182.58 0.00 0.00 0.00
Maximum of Months 1378.57 737.60 640.97 2497.05 1465.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 385.54 0.00 385.54 120.58 1760.99 0.00 0.00 0.00
February 470.79 0.00 470.79 258.33 1603.91 0.00 0.00 0.00
March 616.11 0.00 616.11 472.88 1392.24 0.00 0.00 0.00
April 711.37 5.60 705.76 832.92 849.15 0.00 0.00 0.00
May 843.71 61.01 782.69 1354.80 514.55 0.00 0.00 0.00
June 897.14 110.45 786.69 1868.54 283.04 0.00 0.00 0.00
July 829.13 80.71 748.42 1712.58 227.59 0.00 0.00 0.00
August 699.14 14.30 684.84 1339.24 299.79 0.00 0.00 0.00
September 610.06 0.24 609.81 1021.84 606.32 0.00 0.00 0.00
October 506.52 0.00 506.52 565.81 918.03 0.00 0.00 0.00
November 408.91 0.00 408.91 188.86 1514.50 0.00 0.00 0.00
December 382.56 0.00 382.56 90.36 1949.12 0.00 0.00 0.00
                 
Annual Sum or Average 614.11 22.81 591.30 821.76 990.22 0.00 0.00 0.00
Minimum of Months 382.56 0.00 382.56 90.36 227.59 0.00 0.00 0.00
Maximum of Months 897.14 110.45 786.69 1868.54 1949.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 687.45 372.92 314.53 704.25 1103.55 0.00 0.00 0.00
February 919.75 524.25 395.50 1068.51 1014.57 0.00 0.00 0.00
March 1135.59 625.67 509.91 1411.38 894.67 0.00 0.00 0.00
April 1368.33 759.12 609.21 1980.45 565.57 0.00 0.00 0.00
May 1412.04 767.39 644.65 2291.20 356.92 0.00 0.00 0.00
June 1412.83 785.99 626.85 2580.29 190.44 0.00 0.00 0.00
July 1267.00 662.37 604.64 2319.16 155.61 0.00 0.00 0.00
August 1205.62 617.03 588.60 2132.32 206.43 0.00 0.00 0.00
September 1194.44 681.52 512.93 1976.06 399.24 0.00 0.00 0.00
October 918.60 495.76 422.84 1301.41 607.98 0.00 0.00 0.00
November 823.45 479.38 344.06 942.18 963.63 0.00 0.00 0.00
December 686.86 363.92 322.95 671.85 1209.87 0.00 0.00 0.00
                 
Annual Sum or Average 1086.12 594.29 491.83 1616.62 637.15 0.00 0.00 0.00
Minimum of Months 686.86 363.92 314.53 671.85 155.61 0.00 0.00 0.00
Maximum of Months 1412.83 785.99 644.65 2580.29 1209.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2637.47 1998.16 639.31 3538.08 1745.31 0.00 0.00 0.00
February 2446.55 1724.78 721.77 3332.31 1602.73 0.00 0.00 0.00
March 1988.33 1146.46 841.86 2783.10 1441.08 0.00 0.00 0.00
April 1348.08 503.00 845.08 2117.45 924.73 0.00 0.00 0.00
May 952.67 133.34 819.33 1662.37 558.14 0.00 0.00 0.00
June 821.92 52.15 769.77 1767.03 288.20 0.00 0.00 0.00
July 837.85 77.67 760.18 1779.19 236.94 0.00 0.00 0.00
August 1068.03 282.71 785.32 2137.12 329.64 0.00 0.00 0.00
September 1667.08 866.10 800.97 3031.70 660.02 0.00 0.00 0.00
October 2265.07 1531.34 733.73 3543.50 992.70 0.00 0.00 0.00
November 2725.80 2078.09 647.71 3821.27 1534.94 0.00 0.00 0.00
December 2701.37 2027.77 673.60 3572.37 1875.19 0.00 0.00 0.00
                 
Annual Sum or Average 1784.56 1031.22 753.34 2753.19 1012.77 0.00 0.00 0.00
Minimum of Months 821.92 52.15 639.31 1662.37 236.94 0.00 0.00 0.00
Maximum of Months 2725.80 2078.09 845.08 3821.27 1875.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 724.16 407.82 316.33 805.45 1222.66 0.00 0.00 0.00
February 817.13 434.32 382.81 964.04 1129.03 0.00 0.00 0.00
March 1113.52 596.81 516.71 1429.84 997.04 0.00 0.00 0.00
April 1279.90 691.30 588.60 1891.34 648.42 0.00 0.00 0.00
May 1378.57 737.60 640.97 2267.07 412.42 0.00 0.00 0.00
June 1341.93 720.77 621.17 2479.67 227.41 0.00 0.00 0.00
July 1190.87 591.77 599.10 2201.45 187.56 0.00 0.00 0.00
August 1153.30 587.77 565.53 2053.43 245.37 0.00 0.00 0.00
September 1179.43 657.06 522.37 1998.72 460.67 0.00 0.00 0.00
October 1015.29 592.56 422.74 1507.53 683.92 0.00 0.00 0.00
November 852.19 518.89 333.30 1061.59 1077.86 0.00 0.00 0.00
December 686.74 373.06 313.68 728.52 1338.26 0.00 0.00 0.00
                 
Annual Sum or Average 1061.97 576.19 485.78 1618.42 717.12 0.00 0.00 0.00
Minimum of Months 686.74 373.06 313.68 728.52 187.56 0.00 0.00 0.00
Maximum of Months 1378.57 737.60 640.97 2479.67 1338.26 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.206527E+09 0.00 0.206527E+09 26435335.94 0.119137E+10
February 0.227786E+09 0.00 0.227786E+09 81954944.10 0.956368E+09
March 0.330037E+09 0.00 0.330037E+09 0.205372E+09 0.890894E+09
April 0.368773E+09 2905369.36 0.365867E+09 0.408916E+09 0.489520E+09
May 0.451957E+09 32682516.96 0.419274E+09 0.724531E+09 0.286318E+09
June 0.465076E+09 57255850.15 0.407820E+09 0.974558E+09 0.140956E+09
July 0.444148E+09 43234059.10 0.400914E+09 0.923793E+09 0.116697E+09
August 0.374514E+09 7657767.65 0.366856E+09 0.713999E+09 0.164599E+09
September 0.316255E+09 126196.05 0.316129E+09 0.525871E+09 0.329875E+09
October 0.271332E+09 0.00 0.271332E+09 0.272565E+09 0.575754E+09
November 0.211979E+09 0.00 0.211979E+09 55399314.60 0.100053E+10
December 0.204928E+09 0.00 0.204928E+09 15102382.71 0.135567E+10
           
Annual Sum or Average 0.387331E+10 0.143862E+09 0.372945E+10 0.492850E+10 0.749855E+10
Minimum of Months 0.204928E+09 0.00 0.204928E+09 15102382.71 0.116697E+09
Maximum of Months 0.465076E+09 57255850.15 0.419274E+09 0.974558E+09 0.135567E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.206524E+09 0.00 0.206524E+09 26433984.06 0.119137E+10
February 0.227783E+09 0.00 0.227783E+09 81953061.49 0.956367E+09
March 0.330033E+09 0.00 0.330033E+09 0.205368E+09 0.890892E+09
April 0.368768E+09 2905305.49 0.365863E+09 0.408912E+09 0.489517E+09
May 0.451951E+09 32681798.47 0.419269E+09 0.724524E+09 0.286316E+09
June 0.465070E+09 57254591.45 0.407816E+09 0.974551E+09 0.140954E+09
July 0.444142E+09 43233108.65 0.400909E+09 0.923785E+09 0.116696E+09
August 0.374509E+09 7657599.30 0.366851E+09 0.713994E+09 0.164598E+09
September 0.316252E+09 126193.27 0.316125E+09 0.525867E+09 0.329873E+09
October 0.271328E+09 0.00 0.271328E+09 0.272562E+09 0.575752E+09
November 0.211976E+09 0.00 0.211976E+09 55398107.86 0.100053E+10
December 0.204925E+09 0.00 0.204925E+09 15101589.02 0.135567E+10
           
Annual Sum or Average 0.387326E+10 0.143859E+09 0.372940E+10 0.492845E+10 0.749853E+10
Minimum of Months 0.204925E+09 0.00 0.204925E+09 15101589.02 0.116696E+09
Maximum of Months 0.465070E+09 57254591.45 0.419269E+09 0.974551E+09 0.135567E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.206525E+09 0.00 0.206525E+09 26434434.68 0.119137E+10
February 0.227784E+09 0.00 0.227784E+09 81953689.03 0.956367E+09
March 0.330035E+09 0.00 0.330035E+09 0.205369E+09 0.890892E+09
April 0.368770E+09 2905326.78 0.365865E+09 0.408913E+09 0.489518E+09
May 0.451953E+09 32682037.96 0.419271E+09 0.724526E+09 0.286317E+09
June 0.465072E+09 57255011.02 0.407817E+09 0.974553E+09 0.140955E+09
July 0.444144E+09 43233425.47 0.400911E+09 0.923788E+09 0.116696E+09
August 0.374511E+09 7657655.41 0.366853E+09 0.713996E+09 0.164598E+09
September 0.316253E+09 126194.20 0.316127E+09 0.525868E+09 0.329873E+09
October 0.271329E+09 0.00 0.271329E+09 0.272563E+09 0.575753E+09
November 0.211977E+09 0.00 0.211977E+09 55398510.11 0.100053E+10
December 0.204926E+09 0.00 0.204926E+09 15101853.58 0.135567E+10
           
Annual Sum or Average 0.387328E+10 0.143860E+09 0.372942E+10 0.492847E+10 0.749854E+10
Minimum of Months 0.204926E+09 0.00 0.204926E+09 15101853.58 0.116696E+09
Maximum of Months 0.465072E+09 57255011.02 0.419271E+09 0.974553E+09 0.135567E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.206524E+09 0.00 0.206524E+09 26433984.06 0.119137E+10
February 0.227783E+09 0.00 0.227783E+09 81953061.49 0.956367E+09
March 0.330033E+09 0.00 0.330033E+09 0.205368E+09 0.890892E+09
April 0.368768E+09 2905305.49 0.365863E+09 0.408912E+09 0.489517E+09
May 0.451951E+09 32681798.47 0.419269E+09 0.724524E+09 0.286316E+09
June 0.465070E+09 57254591.45 0.407816E+09 0.974551E+09 0.140954E+09
July 0.444142E+09 43233108.65 0.400909E+09 0.923785E+09 0.116696E+09
August 0.374509E+09 7657599.30 0.366851E+09 0.713994E+09 0.164598E+09
September 0.316252E+09 126193.27 0.316125E+09 0.525867E+09 0.329873E+09
October 0.271328E+09 0.00 0.271328E+09 0.272562E+09 0.575752E+09
November 0.211976E+09 0.00 0.211976E+09 55398107.86 0.100053E+10
December 0.204925E+09 0.00 0.204925E+09 15101589.02 0.135567E+10
           
Annual Sum or Average 0.387326E+10 0.143859E+09 0.372940E+10 0.492845E+10 0.749853E+10
Minimum of Months 0.204925E+09 0.00 0.204925E+09 15101589.02 0.116696E+09
Maximum of Months 0.465070E+09 57254591.45 0.419269E+09 0.974551E+09 0.135567E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.206517E+09 0.00 0.206517E+09 26433143.95 0.119132E+10
February 0.227774E+09 0.00 0.227774E+09 81950072.18 0.956328E+09
March 0.330021E+09 0.00 0.330021E+09 0.205360E+09 0.890856E+09
April 0.368754E+09 2905199.04 0.365849E+09 0.408896E+09 0.489498E+09
May 0.451934E+09 32680600.99 0.419253E+09 0.724496E+09 0.286305E+09
June 0.465053E+09 57252493.61 0.407800E+09 0.974513E+09 0.140949E+09
July 0.444125E+09 43231524.57 0.400894E+09 0.923749E+09 0.116691E+09
August 0.374495E+09 7657318.72 0.366837E+09 0.713966E+09 0.164591E+09
September 0.316239E+09 126188.65 0.316113E+09 0.525847E+09 0.329860E+09
October 0.271318E+09 0.00 0.271318E+09 0.272551E+09 0.575729E+09
November 0.211968E+09 0.00 0.211968E+09 55396076.19 0.100049E+10
December 0.204917E+09 0.00 0.204917E+09 15101112.64 0.135561E+10
           
Annual Sum or Average 0.387311E+10 0.143853E+09 0.372926E+10 0.492826E+10 0.749823E+10
Minimum of Months 0.204917E+09 0.00 0.204917E+09 15101112.64 0.116691E+09
Maximum of Months 0.465053E+09 57252493.61 0.419253E+09 0.974513E+09 0.135561E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.613765E+09 0.332946E+09 0.280820E+09 0.570841E+09 0.120624E+10
February 0.741692E+09 0.422760E+09 0.318932E+09 0.816810E+09 0.960424E+09
March 0.101386E+10 0.558606E+09 0.455257E+09 0.123294E+10 0.890058E+09
April 0.118225E+10 0.655882E+09 0.526363E+09 0.172598E+10 0.497328E+09
May 0.126068E+10 0.685133E+09 0.575547E+09 0.207071E+10 0.318228E+09
June 0.122070E+10 0.679099E+09 0.541601E+09 0.226045E+10 0.148640E+09
July 0.113119E+10 0.591368E+09 0.539824E+09 0.210390E+10 0.119974E+09
August 0.107639E+10 0.550887E+09 0.525504E+09 0.192982E+10 0.168348E+09
September 0.103201E+10 0.588837E+09 0.443173E+09 0.172536E+10 0.344219E+09
October 0.820137E+09 0.442620E+09 0.377517E+09 0.115313E+10 0.596891E+09
November 0.711465E+09 0.414192E+09 0.297273E+09 0.768042E+09 0.990405E+09
December 0.613238E+09 0.324907E+09 0.288331E+09 0.533883E+09 0.133042E+10
           
Annual Sum or Average 0.114174E+11 0.624724E+10 0.517014E+10 0.168919E+11 0.757118E+10
Minimum of Months 0.613238E+09 0.324907E+09 0.280820E+09 0.533883E+09 0.119974E+09
Maximum of Months 0.126068E+10 0.685133E+09 0.575547E+09 0.226045E+10 0.133042E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.613765E+09 0.332946E+09 0.280820E+09 0.570841E+09 0.120624E+10
February 0.741692E+09 0.422760E+09 0.318932E+09 0.816810E+09 0.960424E+09
March 0.101386E+10 0.558606E+09 0.455257E+09 0.123294E+10 0.890058E+09
April 0.118225E+10 0.655882E+09 0.526363E+09 0.172598E+10 0.497328E+09
May 0.126068E+10 0.685133E+09 0.575547E+09 0.207071E+10 0.318228E+09
June 0.122070E+10 0.679099E+09 0.541601E+09 0.226045E+10 0.148640E+09
July 0.113119E+10 0.591368E+09 0.539824E+09 0.210390E+10 0.119974E+09
August 0.107639E+10 0.550887E+09 0.525504E+09 0.192982E+10 0.168348E+09
September 0.103201E+10 0.588837E+09 0.443173E+09 0.172536E+10 0.344219E+09
October 0.820137E+09 0.442620E+09 0.377517E+09 0.115313E+10 0.596891E+09
November 0.711465E+09 0.414192E+09 0.297273E+09 0.768042E+09 0.990405E+09
December 0.613238E+09 0.324907E+09 0.288331E+09 0.533883E+09 0.133042E+10
           
Annual Sum or Average 0.114174E+11 0.624724E+10 0.517014E+10 0.168919E+11 0.757118E+10
Minimum of Months 0.613238E+09 0.324907E+09 0.280820E+09 0.533883E+09 0.119974E+09
Maximum of Months 0.126068E+10 0.685133E+09 0.575547E+09 0.226045E+10 0.133042E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.613754E+09 0.332939E+09 0.280815E+09 0.570830E+09 0.120622E+10
February 0.741678E+09 0.422752E+09 0.318926E+09 0.816795E+09 0.960407E+09
March 0.101384E+10 0.558595E+09 0.455248E+09 0.123292E+10 0.890042E+09
April 0.118222E+10 0.655870E+09 0.526354E+09 0.172595E+10 0.497319E+09
May 0.126066E+10 0.685120E+09 0.575537E+09 0.207067E+10 0.318223E+09
June 0.122068E+10 0.679086E+09 0.541591E+09 0.226041E+10 0.148637E+09
July 0.113117E+10 0.591357E+09 0.539814E+09 0.210386E+10 0.119972E+09
August 0.107637E+10 0.550877E+09 0.525494E+09 0.192979E+10 0.168345E+09
September 0.103199E+10 0.588826E+09 0.443165E+09 0.172533E+10 0.344213E+09
October 0.820122E+09 0.442612E+09 0.377510E+09 0.115311E+10 0.596880E+09
November 0.711452E+09 0.414185E+09 0.297267E+09 0.768028E+09 0.990387E+09
December 0.613227E+09 0.324901E+09 0.288326E+09 0.533874E+09 0.133040E+10
           
Annual Sum or Average 0.114172E+11 0.624712E+10 0.517005E+10 0.168916E+11 0.757104E+10
Minimum of Months 0.613227E+09 0.324901E+09 0.280815E+09 0.533874E+09 0.119972E+09
Maximum of Months 0.126066E+10 0.685120E+09 0.575537E+09 0.226041E+10 0.133040E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141281E+10 0.107035E+10 0.342462E+09 0.188097E+10 0.104825E+10
February 0.118372E+10 0.834499E+09 0.349217E+09 0.160217E+10 0.858427E+09
March 0.106509E+10 0.614125E+09 0.450965E+09 0.148444E+10 0.843033E+09
April 0.698835E+09 0.260751E+09 0.438084E+09 0.110005E+10 0.507006E+09
May 0.510323E+09 71427610.45 0.438896E+09 0.895592E+09 0.308008E+09
June 0.426079E+09 27034416.55 0.399045E+09 0.918712E+09 0.145401E+09
July 0.448818E+09 41605610.16 0.407212E+09 0.959119E+09 0.122229E+09
August 0.572117E+09 0.151441E+09 0.420675E+09 0.115040E+10 0.176374E+09
September 0.864199E+09 0.448979E+09 0.415220E+09 0.158733E+10 0.343980E+09
October 0.121333E+10 0.820289E+09 0.393040E+09 0.190568E+10 0.565052E+09
November 0.141303E+10 0.107726E+10 0.335770E+09 0.196669E+10 0.884450E+09
December 0.144704E+10 0.108621E+10 0.360829E+09 0.187822E+10 0.114566E+10
           
Annual Sum or Average 0.112554E+11 0.650398E+10 0.475142E+10 0.173294E+11 0.694787E+10
Minimum of Months 0.426079E+09 27034416.55 0.335770E+09 0.895592E+09 0.122229E+09
Maximum of Months 0.144704E+10 0.108621E+10 0.450965E+09 0.196669E+10 0.114566E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141280E+10 0.107034E+10 0.342460E+09 0.188096E+10 0.104825E+10
February 0.118371E+10 0.834493E+09 0.349215E+09 0.160216E+10 0.858426E+09
March 0.106508E+10 0.614120E+09 0.450963E+09 0.148443E+10 0.843032E+09
April 0.698831E+09 0.260749E+09 0.438082E+09 0.110004E+10 0.507005E+09
May 0.510321E+09 71427087.03 0.438894E+09 0.895588E+09 0.308007E+09
June 0.426077E+09 27034218.44 0.399043E+09 0.918710E+09 0.145400E+09
July 0.448816E+09 41605305.28 0.407210E+09 0.959116E+09 0.122228E+09
August 0.572114E+09 0.151440E+09 0.420674E+09 0.115040E+10 0.176373E+09
September 0.864194E+09 0.448976E+09 0.415218E+09 0.158733E+10 0.343979E+09
October 0.121332E+10 0.820283E+09 0.393038E+09 0.190567E+10 0.565051E+09
November 0.141302E+10 0.107725E+10 0.335768E+09 0.196668E+10 0.884449E+09
December 0.144703E+10 0.108621E+10 0.360827E+09 0.187820E+10 0.114566E+10
           
Annual Sum or Average 0.112553E+11 0.650393E+10 0.475139E+10 0.173293E+11 0.694786E+10
Minimum of Months 0.426077E+09 27034218.44 0.335768E+09 0.895588E+09 0.122228E+09
Maximum of Months 0.144703E+10 0.108621E+10 0.450963E+09 0.196668E+10 0.114566E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141281E+10 0.107035E+10 0.342462E+09 0.188097E+10 0.104825E+10
February 0.118372E+10 0.834499E+09 0.349217E+09 0.160217E+10 0.858427E+09
March 0.106509E+10 0.614125E+09 0.450965E+09 0.148444E+10 0.843033E+09
April 0.698835E+09 0.260751E+09 0.438084E+09 0.110005E+10 0.507006E+09
May 0.510323E+09 71427610.45 0.438896E+09 0.895592E+09 0.308008E+09
June 0.426079E+09 27034416.55 0.399045E+09 0.918712E+09 0.145401E+09
July 0.448818E+09 41605610.16 0.407212E+09 0.959119E+09 0.122229E+09
August 0.572117E+09 0.151441E+09 0.420675E+09 0.115040E+10 0.176374E+09
September 0.864199E+09 0.448979E+09 0.415220E+09 0.158733E+10 0.343980E+09
October 0.121333E+10 0.820289E+09 0.393040E+09 0.190568E+10 0.565052E+09
November 0.141303E+10 0.107726E+10 0.335770E+09 0.196669E+10 0.884450E+09
December 0.144704E+10 0.108621E+10 0.360829E+09 0.187822E+10 0.114566E+10
           
Annual Sum or Average 0.112554E+11 0.650398E+10 0.475142E+10 0.173294E+11 0.694787E+10
Minimum of Months 0.426079E+09 27034416.55 0.335770E+09 0.895592E+09 0.122229E+09
Maximum of Months 0.144704E+10 0.108621E+10 0.450965E+09 0.196669E+10 0.114566E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141280E+10 0.107034E+10 0.342460E+09 0.188096E+10 0.104825E+10
February 0.118371E+10 0.834493E+09 0.349215E+09 0.160216E+10 0.858426E+09
March 0.106508E+10 0.614120E+09 0.450963E+09 0.148443E+10 0.843032E+09
April 0.698831E+09 0.260749E+09 0.438082E+09 0.110004E+10 0.507005E+09
May 0.510321E+09 71427087.03 0.438894E+09 0.895588E+09 0.308007E+09
June 0.426077E+09 27034218.44 0.399043E+09 0.918710E+09 0.145400E+09
July 0.448816E+09 41605305.28 0.407210E+09 0.959116E+09 0.122228E+09
August 0.572114E+09 0.151440E+09 0.420674E+09 0.115040E+10 0.176373E+09
September 0.864194E+09 0.448976E+09 0.415218E+09 0.158733E+10 0.343979E+09
October 0.121332E+10 0.820283E+09 0.393038E+09 0.190567E+10 0.565051E+09
November 0.141302E+10 0.107725E+10 0.335768E+09 0.196668E+10 0.884449E+09
December 0.144703E+10 0.108621E+10 0.360827E+09 0.187820E+10 0.114566E+10
           
Annual Sum or Average 0.112553E+11 0.650393E+10 0.475139E+10 0.173293E+11 0.694786E+10
Minimum of Months 0.426077E+09 27034218.44 0.335768E+09 0.895588E+09 0.122228E+09
Maximum of Months 0.144703E+10 0.108621E+10 0.450963E+09 0.196668E+10 0.114566E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.141275E+10 0.107030E+10 0.342447E+09 0.188089E+10 0.104821E+10
February 0.118366E+10 0.834462E+09 0.349202E+09 0.160210E+10 0.858392E+09
March 0.106504E+10 0.614098E+09 0.450946E+09 0.148437E+10 0.842998E+09
April 0.698805E+09 0.260739E+09 0.438066E+09 0.110000E+10 0.506985E+09
May 0.510301E+09 71424469.90 0.438877E+09 0.895554E+09 0.307995E+09
June 0.426061E+09 27033227.90 0.399028E+09 0.918674E+09 0.145395E+09
July 0.448799E+09 41603780.84 0.407195E+09 0.959079E+09 0.122224E+09
August 0.572092E+09 0.151435E+09 0.420658E+09 0.115036E+10 0.176366E+09
September 0.864162E+09 0.448959E+09 0.415203E+09 0.158727E+10 0.343965E+09
October 0.121328E+10 0.820253E+09 0.393024E+09 0.190560E+10 0.565029E+09
November 0.141297E+10 0.107721E+10 0.335756E+09 0.196661E+10 0.884414E+09
December 0.144698E+10 0.108617E+10 0.360813E+09 0.187813E+10 0.114562E+10
           
Annual Sum or Average 0.112549E+11 0.650369E+10 0.475121E+10 0.173286E+11 0.694759E+10
Minimum of Months 0.426061E+09 27033227.90 0.335756E+09 0.895554E+09 0.122224E+09
Maximum of Months 0.144698E+10 0.108617E+10 0.450946E+09 0.196661E+10 0.114562E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.646533E+09 0.364109E+09 0.282424E+09 0.671642E+09 0.134515E+10
February 0.658944E+09 0.350243E+09 0.308701E+09 0.729015E+09 0.112582E+10
March 0.994160E+09 0.532836E+09 0.461325E+09 0.122701E+10 0.108176E+10
April 0.110584E+10 0.597286E+09 0.508558E+09 0.160439E+10 0.652561E+09
May 0.123080E+10 0.658535E+09 0.572268E+09 0.203142E+10 0.393409E+09
June 0.115944E+10 0.622749E+09 0.536695E+09 0.213789E+10 0.209135E+09
July 0.106322E+10 0.528336E+09 0.534886E+09 0.195051E+10 0.189200E+09
August 0.102968E+10 0.524762E+09 0.504913E+09 0.181081E+10 0.261260E+09
September 0.101904E+10 0.567706E+09 0.451330E+09 0.172677E+10 0.424608E+09
October 0.906464E+09 0.529042E+09 0.377422E+09 0.131668E+10 0.717617E+09
November 0.736300E+09 0.448328E+09 0.287971E+09 0.862608E+09 0.119082E+10
December 0.613128E+09 0.333071E+09 0.280057E+09 0.580902E+09 0.159219E+10
           
Annual Sum or Average 0.111636E+11 0.605700E+10 0.510655E+10 0.166496E+11 0.918354E+10
Minimum of Months 0.613128E+09 0.333071E+09 0.280057E+09 0.580902E+09 0.189200E+09
Maximum of Months 0.123080E+10 0.658535E+09 0.572268E+09 0.213789E+10 0.159219E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.646533E+09 0.364109E+09 0.282424E+09 0.671642E+09 0.134515E+10
February 0.658944E+09 0.350243E+09 0.308701E+09 0.729015E+09 0.112582E+10
March 0.994160E+09 0.532836E+09 0.461325E+09 0.122701E+10 0.108176E+10
April 0.110584E+10 0.597286E+09 0.508558E+09 0.160439E+10 0.652561E+09
May 0.123080E+10 0.658535E+09 0.572268E+09 0.203142E+10 0.393409E+09
June 0.115944E+10 0.622749E+09 0.536695E+09 0.213789E+10 0.209135E+09
July 0.106322E+10 0.528336E+09 0.534886E+09 0.195051E+10 0.189200E+09
August 0.102968E+10 0.524762E+09 0.504913E+09 0.181081E+10 0.261260E+09
September 0.101904E+10 0.567706E+09 0.451330E+09 0.172677E+10 0.424608E+09
October 0.906464E+09 0.529042E+09 0.377422E+09 0.131668E+10 0.717617E+09
November 0.736300E+09 0.448328E+09 0.287971E+09 0.862608E+09 0.119082E+10
December 0.613128E+09 0.333071E+09 0.280057E+09 0.580902E+09 0.159219E+10
           
Annual Sum or Average 0.111636E+11 0.605700E+10 0.510655E+10 0.166496E+11 0.918354E+10
Minimum of Months 0.613128E+09 0.333071E+09 0.280057E+09 0.580902E+09 0.189200E+09
Maximum of Months 0.123080E+10 0.658535E+09 0.572268E+09 0.213789E+10 0.159219E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.646521E+09 0.364102E+09 0.282419E+09 0.671629E+09 0.134513E+10
February 0.658932E+09 0.350237E+09 0.308695E+09 0.729002E+09 0.112580E+10
March 0.994142E+09 0.532826E+09 0.461316E+09 0.122699E+10 0.108174E+10
April 0.110582E+10 0.597276E+09 0.508549E+09 0.160436E+10 0.652549E+09
May 0.123078E+10 0.658523E+09 0.572257E+09 0.203138E+10 0.393402E+09
June 0.115942E+10 0.622737E+09 0.536685E+09 0.213785E+10 0.209131E+09
July 0.106320E+10 0.528326E+09 0.534876E+09 0.195048E+10 0.189197E+09
August 0.102966E+10 0.524753E+09 0.504904E+09 0.181078E+10 0.261255E+09
September 0.101902E+10 0.567695E+09 0.451321E+09 0.172673E+10 0.424600E+09
October 0.906447E+09 0.529032E+09 0.377415E+09 0.131665E+10 0.717603E+09
November 0.736286E+09 0.448320E+09 0.287966E+09 0.862592E+09 0.119080E+10
December 0.613117E+09 0.333065E+09 0.280052E+09 0.580892E+09 0.159216E+10
           
Annual Sum or Average 0.111633E+11 0.605689E+10 0.510646E+10 0.166493E+11 0.918337E+10
Minimum of Months 0.613117E+09 0.333065E+09 0.280052E+09 0.580892E+09 0.189197E+09
Maximum of Months 0.123078E+10 0.658523E+09 0.572257E+09 0.213785E+10 0.159216E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.103263E+10 0.00 0.103263E+10 0.230765E+09 0.528355E+10
February 0.113893E+10 0.00 0.113893E+10 0.528916E+09 0.429002E+10
March 0.165018E+10 0.00 0.165018E+10 0.115995E+10 0.404761E+10
April 0.184386E+10 14526939.37 0.182933E+10 0.213942E+10 0.229792E+10
May 0.225978E+10 0.163414E+09 0.209637E+10 0.366315E+10 0.138307E+10
June 0.232538E+10 0.286281E+09 0.203910E+10 0.491463E+10 0.711326E+09
July 0.222074E+10 0.216172E+09 0.200456E+10 0.467844E+10 0.579186E+09
August 0.187256E+10 38289082.23 0.183427E+10 0.365456E+10 0.789273E+09
September 0.158127E+10 630984.26 0.158064E+10 0.267701E+10 0.158223E+10
October 0.135666E+10 0.00 0.135666E+10 0.146049E+10 0.263714E+10
November 0.105989E+10 0.00 0.105989E+10 0.394140E+09 0.440131E+10
December 0.102464E+10 0.00 0.102464E+10 0.157845E+09 0.583352E+10
           
Annual Sum or Average 0.193665E+11 0.719313E+09 0.186472E+11 0.256593E+11 0.338362E+11
Minimum of Months 0.102464E+10 0.00 0.102464E+10 0.157845E+09 0.579186E+09
Maximum of Months 0.232538E+10 0.286281E+09 0.209637E+10 0.491463E+10 0.583352E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.184128E+10 0.998827E+09 0.842450E+09 0.177672E+10 0.330190E+10
February 0.222505E+10 0.126827E+10 0.956787E+09 0.248781E+10 0.269372E+10
March 0.304156E+10 0.167580E+10 0.136576E+10 0.371040E+10 0.255382E+10
April 0.354670E+10 0.196763E+10 0.157907E+10 0.513968E+10 0.150080E+10
May 0.378200E+10 0.205538E+10 0.172662E+10 0.617287E+10 0.953590E+09
June 0.366206E+10 0.203728E+10 0.162479E+10 0.674206E+10 0.479290E+09
July 0.339354E+10 0.177408E+10 0.161946E+10 0.627583E+10 0.398353E+09
August 0.322914E+10 0.165264E+10 0.157649E+10 0.575997E+10 0.541123E+09
September 0.309600E+10 0.176649E+10 0.132951E+10 0.514996E+10 0.103128E+10
October 0.246039E+10 0.132785E+10 0.113254E+10 0.346139E+10 0.171530E+10
November 0.213437E+10 0.124256E+10 0.891809E+09 0.234706E+10 0.275607E+10
December 0.183970E+10 0.974712E+09 0.864984E+09 0.167795E+10 0.361228E+10
           
Annual Sum or Average 0.342518E+11 0.187415E+11 0.155103E+11 0.507017E+11 0.215375E+11
Minimum of Months 0.183970E+10 0.974712E+09 0.842450E+09 0.167795E+10 0.398353E+09
Maximum of Months 0.378200E+10 0.205538E+10 0.172662E+10 0.674206E+10 0.361228E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.706420E+10 0.535187E+10 0.171233E+10 0.933526E+10 0.515038E+10
February 0.591869E+10 0.417258E+10 0.174610E+10 0.795495E+10 0.421096E+10
March 0.532554E+10 0.307069E+10 0.225485E+10 0.737152E+10 0.411103E+10
April 0.349422E+10 0.130378E+10 0.219044E+10 0.549338E+10 0.247718E+10
May 0.255164E+10 0.357146E+09 0.219449E+10 0.449474E+10 0.150436E+10
June 0.213041E+10 0.135175E+09 0.199523E+10 0.464921E+10 0.726328E+09
July 0.224411E+10 0.208032E+09 0.203607E+10 0.485446E+10 0.605224E+09
August 0.286062E+10 0.757222E+09 0.210339E+10 0.579117E+10 0.865045E+09
September 0.432106E+10 0.224494E+10 0.207612E+10 0.790227E+10 0.170831E+10
October 0.606675E+10 0.410153E+10 0.196522E+10 0.946990E+10 0.277821E+10
November 0.706527E+10 0.538640E+10 0.167887E+10 0.978509E+10 0.431628E+10
December 0.723536E+10 0.543119E+10 0.180417E+10 0.938168E+10 0.552727E+10
           
Annual Sum or Average 0.562779E+11 0.325206E+11 0.237573E+11 0.864836E+11 0.339806E+11
Minimum of Months 0.213041E+10 0.135175E+09 0.167887E+10 0.449474E+10 0.605224E+09
Maximum of Months 0.723536E+10 0.543119E+10 0.225485E+10 0.978509E+10 0.552727E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.193958E+10 0.109232E+10 0.847263E+09 0.209634E+10 0.358852E+10
February 0.197681E+10 0.105072E+10 0.926094E+09 0.228036E+10 0.295999E+10
March 0.298245E+10 0.159849E+10 0.138396E+10 0.378335E+10 0.284738E+10
April 0.331750E+10 0.179184E+10 0.152566E+10 0.490715E+10 0.173447E+10
May 0.369237E+10 0.197559E+10 0.171679E+10 0.610516E+10 0.111172E+10
June 0.347829E+10 0.186823E+10 0.161007E+10 0.647236E+10 0.579395E+09
July 0.318963E+10 0.158499E+10 0.160464E+10 0.594716E+10 0.489014E+09
August 0.308900E+10 0.157427E+10 0.151472E+10 0.554021E+10 0.650636E+09
September 0.305708E+10 0.170310E+10 0.135398E+10 0.520604E+10 0.119679E+10
October 0.271936E+10 0.158711E+10 0.113225E+10 0.402035E+10 0.192196E+10
November 0.220888E+10 0.134497E+10 0.863906E+09 0.269650E+10 0.304686E+10
December 0.183936E+10 0.999202E+09 0.840163E+09 0.188376E+10 0.392651E+10
           
Annual Sum or Average 0.334903E+11 0.181708E+11 0.153195E+11 0.509387E+11 0.240532E+11
Minimum of Months 0.183936E+10 0.999202E+09 0.840163E+09 0.188376E+10 0.489014E+09
Maximum of Months 0.369237E+10 0.197559E+10 0.171679E+10 0.647236E+10 0.392651E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.103263E+10 0.00 0.103263E+10 0.322958E+09 0.471662E+10
February 0.113893E+10 0.00 0.113893E+10 0.624943E+09 0.388018E+10
March 0.165018E+10 0.00 0.165018E+10 0.126656E+10 0.372897E+10
April 0.184386E+10 14526939.37 0.182933E+10 0.215894E+10 0.220100E+10
May 0.225978E+10 0.163414E+09 0.209637E+10 0.362871E+10 0.137818E+10
June 0.232538E+10 0.286281E+09 0.203910E+10 0.484326E+10 0.733637E+09
July 0.222074E+10 0.216172E+09 0.200456E+10 0.458696E+10 0.609585E+09
August 0.187256E+10 38289082.23 0.183427E+10 0.358703E+10 0.802968E+09
September 0.158127E+10 630984.26 0.158064E+10 0.264860E+10 0.157159E+10
October 0.135666E+10 0.00 0.135666E+10 0.151548E+10 0.245885E+10
November 0.105989E+10 0.00 0.105989E+10 0.489534E+09 0.392559E+10
December 0.102464E+10 0.00 0.102464E+10 0.242010E+09 0.522051E+10
           
Annual Sum or Average 0.193665E+11 0.719313E+09 0.186472E+11 0.259150E+11 0.312277E+11
Minimum of Months 0.102464E+10 0.00 0.102464E+10 0.242010E+09 0.609585E+09
Maximum of Months 0.232538E+10 0.286281E+09 0.209637E+10 0.484326E+10 0.522051E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.184128E+10 0.998827E+09 0.842450E+09 0.188626E+10 0.295576E+10
February 0.222505E+10 0.126827E+10 0.956787E+09 0.258494E+10 0.245444E+10
March 0.304156E+10 0.167580E+10 0.136576E+10 0.378024E+10 0.239627E+10
April 0.354670E+10 0.196763E+10 0.157907E+10 0.513332E+10 0.146595E+10
May 0.378200E+10 0.205538E+10 0.172662E+10 0.613675E+10 0.955961E+09
June 0.366206E+10 0.203728E+10 0.162479E+10 0.668812E+10 0.493631E+09
July 0.339354E+10 0.177408E+10 0.161946E+10 0.621164E+10 0.416785E+09
August 0.322914E+10 0.165264E+10 0.157649E+10 0.571122E+10 0.552907E+09
September 0.309600E+10 0.176649E+10 0.132951E+10 0.512195E+10 0.103483E+10
October 0.246039E+10 0.132785E+10 0.113254E+10 0.348569E+10 0.162841E+10
November 0.213437E+10 0.124256E+10 0.891809E+09 0.244214E+10 0.249772E+10
December 0.183970E+10 0.974712E+09 0.864984E+09 0.179950E+10 0.324052E+10
           
Annual Sum or Average 0.342518E+11 0.187415E+11 0.155103E+11 0.509818E+11 0.200932E+11
Minimum of Months 0.183970E+10 0.974712E+09 0.842450E+09 0.179950E+10 0.416785E+09
Maximum of Months 0.378200E+10 0.205538E+10 0.172662E+10 0.668812E+10 0.324052E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.706420E+10 0.535187E+10 0.171233E+10 0.947641E+10 0.467464E+10
February 0.591869E+10 0.417258E+10 0.174610E+10 0.806153E+10 0.387733E+10
March 0.532554E+10 0.307069E+10 0.225485E+10 0.745426E+10 0.385979E+10
April 0.349422E+10 0.130378E+10 0.219044E+10 0.548842E+10 0.239691E+10
May 0.255164E+10 0.357146E+09 0.219449E+10 0.445249E+10 0.149492E+10
June 0.213041E+10 0.135175E+09 0.199523E+10 0.458014E+10 0.747008E+09
July 0.224411E+10 0.208032E+09 0.203607E+10 0.476537E+10 0.634627E+09
August 0.286062E+10 0.757222E+09 0.210339E+10 0.572405E+10 0.882900E+09
September 0.432106E+10 0.224494E+10 0.207612E+10 0.785816E+10 0.171077E+10
October 0.606675E+10 0.410153E+10 0.196522E+10 0.949092E+10 0.265884E+10
November 0.706527E+10 0.538640E+10 0.167887E+10 0.990472E+10 0.397856E+10
December 0.723536E+10 0.543119E+10 0.180417E+10 0.956824E+10 0.502251E+10
           
Annual Sum or Average 0.562779E+11 0.325206E+11 0.237573E+11 0.868247E+11 0.319388E+11
Minimum of Months 0.213041E+10 0.135175E+09 0.167887E+10 0.445249E+10 0.634627E+09
Maximum of Months 0.723536E+10 0.543119E+10 0.225485E+10 0.990472E+10 0.502251E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.193958E+10 0.109232E+10 0.847263E+09 0.215732E+10 0.327476E+10
February 0.197681E+10 0.105072E+10 0.926094E+09 0.233219E+10 0.273134E+10
March 0.298245E+10 0.159849E+10 0.138396E+10 0.382970E+10 0.267047E+10
April 0.331750E+10 0.179184E+10 0.152566E+10 0.490236E+10 0.168071E+10
May 0.369237E+10 0.197559E+10 0.171679E+10 0.607212E+10 0.110464E+10
June 0.347829E+10 0.186823E+10 0.161007E+10 0.642731E+10 0.589459E+09
July 0.318963E+10 0.158499E+10 0.160464E+10 0.589635E+10 0.502360E+09
August 0.308900E+10 0.157427E+10 0.151472E+10 0.549991E+10 0.657197E+09
September 0.305708E+10 0.170310E+10 0.135398E+10 0.518067E+10 0.119405E+10
October 0.271936E+10 0.158711E+10 0.113225E+10 0.403777E+10 0.183180E+10
November 0.220888E+10 0.134497E+10 0.863906E+09 0.275165E+10 0.279380E+10
December 0.183936E+10 0.999202E+09 0.840163E+09 0.195128E+10 0.358439E+10
           
Annual Sum or Average 0.334903E+11 0.181708E+11 0.153195E+11 0.510386E+11 0.226150E+11
Minimum of Months 0.183936E+10 0.999202E+09 0.840163E+09 0.195128E+10 0.502360E+09
Maximum of Months 0.369237E+10 0.197559E+10 0.171679E+10 0.642731E+10 0.358439E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 49.35 2224.02 385.54 0.00 385.54 0.00 0.00
February 169.38 1976.60 470.78 0.00 470.78 0.00 0.00
March 383.38 1663.09 616.10 0.00 616.10 0.00 0.00
April 788.79 944.28 711.36 5.60 705.75 0.00 0.00
May 1352.52 534.49 843.69 61.01 782.68 0.00 0.00
June 1879.91 271.90 897.12 110.44 786.68 0.00 0.00
July 1724.50 217.84 829.11 80.71 748.41 0.00 0.00
August 1332.87 307.27 699.13 14.30 684.83 0.00 0.00
September 1014.40 636.32 610.05 0.24 609.81 0.00 0.00
October 508.81 1074.80 506.51 0.00 506.51 0.00 0.00
November 106.86 1930.02 408.90 0.00 408.90 0.00 0.00
December 28.19 2530.72 382.55 0.00 382.55 0.00 0.00
               
Annual Sum or Average 781.40 1188.88 614.10 22.81 591.29 0.00 0.00
Minimum of Months 28.19 217.84 382.55 0.00 382.55 0.00 0.00
Maximum of Months 1879.91 2530.72 897.12 110.44 786.68 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 639.38 1351.07 687.46 372.92 314.54 0.00 0.00
February 1012.90 1191.00 919.75 524.25 395.50 0.00 0.00
March 1380.98 996.92 1135.59 625.67 509.92 0.00 0.00
April 1997.65 575.61 1368.33 759.12 609.21 0.00 0.00
May 2319.33 356.44 1412.04 767.39 644.65 0.00 0.00
June 2616.25 172.04 1412.84 785.99 626.85 0.00 0.00
July 2356.50 134.38 1267.01 662.37 604.64 0.00 0.00
August 2161.53 188.56 1205.63 617.03 588.60 0.00 0.00
September 1996.93 398.40 1194.45 681.52 512.93 0.00 0.00
October 1291.58 668.56 918.61 495.76 422.84 0.00 0.00
November 888.93 1146.30 823.45 479.39 344.06 0.00 0.00
December 597.98 1490.16 686.87 363.92 322.95 0.00 0.00
               
Annual Sum or Average 1606.90 720.24 1086.12 594.29 491.83 0.00 0.00
Minimum of Months 597.98 134.38 686.87 363.92 314.54 0.00 0.00
Maximum of Months 2616.25 1490.16 1412.84 785.99 644.65 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3511.33 1956.84 2637.39 1998.09 639.30 0.00 0.00
February 3311.32 1774.18 2446.48 1724.72 721.75 0.00 0.00
March 2771.09 1573.75 1988.27 1146.43 841.85 0.00 0.00
April 2121.98 978.01 1348.05 502.99 845.06 0.00 0.00
May 1671.86 574.98 952.65 133.34 819.32 0.00 0.00
June 1772.19 280.48 821.90 52.15 769.75 0.00 0.00
July 1790.45 228.17 837.84 77.67 760.17 0.00 0.00
August 2147.54 329.25 1068.01 282.71 785.30 0.00 0.00
September 3061.96 663.53 1667.03 866.08 800.96 0.00 0.00
October 3557.46 1054.82 2265.00 1531.29 733.71 0.00 0.00
November 3793.73 1706.10 2725.72 2078.02 647.70 0.00 0.00
December 3506.19 2138.69 2701.29 2027.71 673.58 0.00 0.00
               
Annual Sum or Average 2747.52 1101.57 1784.51 1031.19 753.32 0.00 0.00
Minimum of Months 1671.86 228.17 821.90 52.15 639.30 0.00 0.00
Maximum of Months 3793.73 2138.69 2725.72 2078.02 845.06 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 752.28 1506.66 724.16 407.83 316.33 0.00 0.00
February 904.03 1396.09 817.14 434.33 382.81 0.00 0.00
March 1374.33 1211.65 1113.52 596.81 516.71 0.00 0.00
April 1856.92 755.27 1279.90 691.30 588.61 0.00 0.00
May 2275.32 440.64 1378.58 737.60 640.98 0.00 0.00
June 2474.39 242.05 1341.94 720.77 621.17 0.00 0.00
July 2184.70 211.92 1190.88 591.77 599.11 0.00 0.00
August 2028.23 292.63 1153.30 587.77 565.54 0.00 0.00
September 1998.56 491.44 1179.43 657.06 522.37 0.00 0.00
October 1474.76 803.78 1015.30 592.56 422.74 0.00 0.00
November 998.38 1378.26 852.19 518.90 333.30 0.00 0.00
December 650.65 1783.36 686.74 373.06 313.68 0.00 0.00
               
Annual Sum or Average 1583.86 873.62 1061.98 576.20 485.78 0.00 0.00
Minimum of Months 650.65 211.92 686.74 373.06 313.68 0.00 0.00
Maximum of Months 2474.39 1783.36 1378.58 737.60 640.98 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 86.16 1972.65 385.54 0.00 385.54 0.00 0.00
February 218.63 1773.32 470.79 0.00 470.79 0.00 0.00
March 433.07 1511.20 616.11 0.00 616.11 0.00 0.00
April 825.39 886.54 711.37 5.60 705.76 0.00 0.00
May 1367.66 516.38 843.71 61.01 782.69 0.00 0.00
June 1896.08 274.43 897.14 110.45 786.69 0.00 0.00
July 1746.73 216.24 829.13 80.71 748.42 0.00 0.00
August 1364.46 294.68 699.14 14.30 684.84 0.00 0.00
September 1032.80 610.43 610.06 0.24 609.81 0.00 0.00
October 545.29 984.60 506.52 0.00 506.52 0.00 0.00
November 152.06 1698.04 408.91 0.00 408.91 0.00 0.00
December 58.93 2177.99 382.56 0.00 382.56 0.00 0.00
               
Annual Sum or Average 813.65 1072.94 614.11 22.81 591.30 0.00 0.00
Minimum of Months 58.93 216.24 382.56 0.00 382.56 0.00 0.00
Maximum of Months 1896.08 2177.99 897.14 110.45 786.69 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 663.35 1232.79 687.45 372.92 314.53 0.00 0.00
February 1028.36 1113.48 919.75 524.25 395.50 0.00 0.00
March 1385.30 953.49 1135.59 625.67 509.91 0.00 0.00
April 1982.90 579.01 1368.33 759.12 609.21 0.00 0.00
May 2304.69 356.03 1412.04 767.39 644.65 0.00 0.00
June 2601.10 184.91 1412.83 785.99 626.85 0.00 0.00
July 2343.13 148.73 1267.00 662.37 604.64 0.00 0.00
August 2150.53 202.03 1205.62 617.03 588.60 0.00 0.00
September 1986.87 397.87 1194.44 681.52 512.93 0.00 0.00
October 1292.33 640.42 918.60 495.76 422.84 0.00 0.00
November 905.50 1063.30 823.45 479.38 344.06 0.00 0.00
December 626.48 1348.67 686.86 363.92 322.95 0.00 0.00
               
Annual Sum or Average 1607.74 682.95 1086.12 594.29 491.83 0.00 0.00
Minimum of Months 626.48 148.73 686.86 363.92 314.53 0.00 0.00
Maximum of Months 2601.10 1348.67 1412.83 785.99 644.65 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3485.39 1922.93 2637.47 1998.16 639.31 0.00 0.00
February 3288.26 1740.64 2446.55 1724.78 721.77 0.00 0.00
March 2752.21 1534.88 1988.33 1146.46 841.86 0.00 0.00
April 2119.36 955.70 1348.08 503.00 845.08 0.00 0.00
May 1678.14 561.66 952.67 133.34 819.33 0.00 0.00
June 1793.68 280.22 821.92 52.15 769.77 0.00 0.00
July 1812.45 225.96 837.85 77.67 760.18 0.00 0.00
August 2162.18 322.97 1068.03 282.71 785.32 0.00 0.00
September 3048.71 659.07 1667.08 866.10 800.97 0.00 0.00
October 3535.66 1037.27 2265.07 1531.34 733.73 0.00 0.00
November 3775.11 1665.23 2725.80 2078.09 647.71 0.00 0.00
December 3502.72 2063.65 2701.37 2027.77 673.60 0.00 0.00
               
Annual Sum or Average 2742.38 1077.52 1784.56 1031.22 753.34 0.00 0.00
Minimum of Months 1678.14 225.96 821.92 52.15 639.31 0.00 0.00
Maximum of Months 3775.11 2063.65 2725.80 2078.09 845.08 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 782.68 1339.80 724.16 407.82 316.33 0.00 0.00
February 942.61 1223.54 817.13 434.32 382.81 0.00 0.00
March 1412.54 1063.09 1113.52 596.81 516.71 0.00 0.00
April 1893.19 669.16 1279.90 691.30 588.60 0.00 0.00
May 2279.41 415.07 1378.57 737.60 640.97 0.00 0.00
June 2497.05 223.53 1341.93 720.77 621.17 0.00 0.00
July 2220.41 182.58 1190.87 591.77 599.10 0.00 0.00
August 2068.48 242.92 1153.30 587.77 565.53 0.00 0.00
September 2008.50 461.72 1179.43 657.06 522.37 0.00 0.00
October 1501.02 717.58 1015.29 592.56 422.74 0.00 0.00
November 1040.32 1175.48 852.19 518.89 333.30 0.00 0.00
December 703.32 1465.99 686.74 373.06 313.68 0.00 0.00
               
Annual Sum or Average 1615.26 762.72 1061.97 576.19 485.78 0.00 0.00
Minimum of Months 703.32 182.58 686.74 373.06 313.68 0.00 0.00
Maximum of Months 2497.05 1465.99 1378.57 737.60 640.97 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 120.58 1760.99 385.54 0.00 385.54 0.00 0.00
February 258.33 1603.91 470.79 0.00 470.79 0.00 0.00
March 472.88 1392.24 616.11 0.00 616.11 0.00 0.00
April 832.92 849.15 711.37 5.60 705.76 0.00 0.00
May 1354.80 514.55 843.71 61.01 782.69 0.00 0.00
June 1868.54 283.04 897.14 110.45 786.69 0.00 0.00
July 1712.58 227.59 829.13 80.71 748.42 0.00 0.00
August 1339.24 299.79 699.14 14.30 684.84 0.00 0.00
September 1021.84 606.32 610.06 0.24 609.81 0.00 0.00
October 565.81 918.03 506.52 0.00 506.52 0.00 0.00
November 188.86 1514.50 408.91 0.00 408.91 0.00 0.00
December 90.36 1949.12 382.56 0.00 382.56 0.00 0.00
               
Annual Sum or Average 821.76 990.22 614.11 22.81 591.30 0.00 0.00
Minimum of Months 90.36 227.59 382.56 0.00 382.56 0.00 0.00
Maximum of Months 1868.54 1949.12 897.14 110.45 786.69 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 704.25 1103.55 687.45 372.92 314.53 0.00 0.00
February 1068.51 1014.57 919.75 524.25 395.50 0.00 0.00
March 1411.38 894.67 1135.59 625.67 509.91 0.00 0.00
April 1980.45 565.57 1368.33 759.12 609.21 0.00 0.00
May 2291.20 356.92 1412.04 767.39 644.65 0.00 0.00
June 2580.29 190.44 1412.83 785.99 626.85 0.00 0.00
July 2319.16 155.61 1267.00 662.37 604.64 0.00 0.00
August 2132.32 206.43 1205.62 617.03 588.60 0.00 0.00
September 1976.06 399.24 1194.44 681.52 512.93 0.00 0.00
October 1301.41 607.98 918.60 495.76 422.84 0.00 0.00
November 942.18 963.63 823.45 479.38 344.06 0.00 0.00
December 671.85 1209.87 686.86 363.92 322.95 0.00 0.00
               
Annual Sum or Average 1616.62 637.15 1086.12 594.29 491.83 0.00 0.00
Minimum of Months 671.85 155.61 686.86 363.92 314.53 0.00 0.00
Maximum of Months 2580.29 1209.87 1412.83 785.99 644.65 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3538.08 1745.31 2637.47 1998.16 639.31 0.00 0.00
February 3332.31 1602.73 2446.55 1724.78 721.77 0.00 0.00
March 2783.10 1441.08 1988.33 1146.46 841.86 0.00 0.00
April 2117.45 924.73 1348.08 503.00 845.08 0.00 0.00
May 1662.37 558.14 952.67 133.34 819.33 0.00 0.00
June 1767.03 288.20 821.92 52.15 769.77 0.00 0.00
July 1779.19 236.94 837.85 77.67 760.18 0.00 0.00
August 2137.12 329.64 1068.03 282.71 785.32 0.00 0.00
September 3031.70 660.02 1667.08 866.10 800.97 0.00 0.00
October 3543.50 992.70 2265.07 1531.34 733.73 0.00 0.00
November 3821.27 1534.94 2725.80 2078.09 647.71 0.00 0.00
December 3572.37 1875.19 2701.37 2027.77 673.60 0.00 0.00
               
Annual Sum or Average 2753.19 1012.77 1784.56 1031.22 753.34 0.00 0.00
Minimum of Months 1662.37 236.94 821.92 52.15 639.31 0.00 0.00
Maximum of Months 3821.27 1875.19 2725.80 2078.09 845.08 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 805.45 1222.66 724.16 407.82 316.33 0.00 0.00
February 964.04 1129.03 817.13 434.32 382.81 0.00 0.00
March 1429.84 997.04 1113.52 596.81 516.71 0.00 0.00
April 1891.34 648.42 1279.90 691.30 588.60 0.00 0.00
May 2267.07 412.42 1378.57 737.60 640.97 0.00 0.00
June 2479.67 227.41 1341.93 720.77 621.17 0.00 0.00
July 2201.45 187.56 1190.87 591.77 599.10 0.00 0.00
August 2053.43 245.37 1153.30 587.77 565.53 0.00 0.00
September 1998.72 460.67 1179.43 657.06 522.37 0.00 0.00
October 1507.53 683.92 1015.29 592.56 422.74 0.00 0.00
November 1061.59 1077.86 852.19 518.89 333.30 0.00 0.00
December 728.52 1338.26 686.74 373.06 313.68 0.00 0.00
               
Annual Sum or Average 1618.42 717.12 1061.97 576.19 485.78 0.00 0.00
Minimum of Months 728.52 187.56 686.74 373.06 313.68 0.00 0.00
Maximum of Months 2479.67 1338.26 1378.57 737.60 640.97 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.132171E+09 0.595680E+10 0.103262E+10 0.00 0.103262E+10 0.00 0.00
February 0.409765E+09 0.478180E+10 0.113891E+10 0.00 0.113891E+10 0.00 0.00
March 0.102684E+10 0.445443E+10 0.165016E+10 0.00 0.165016E+10 0.00 0.00
April 0.204455E+10 0.244757E+10 0.184383E+10 14526506.15 0.182931E+10 0.00 0.00
May 0.362260E+10 0.143157E+10 0.225975E+10 0.163409E+09 0.209634E+10 0.00 0.00
June 0.487273E+10 0.704769E+09 0.232534E+10 0.286273E+09 0.203907E+10 0.00 0.00
July 0.461890E+10 0.583476E+09 0.222070E+10 0.216165E+09 0.200454E+10 0.00 0.00
August 0.356995E+10 0.822985E+09 0.187254E+10 38287940.38 0.183425E+10 0.00 0.00
September 0.262932E+10 0.164935E+10 0.158125E+10 630965.44 0.158062E+10 0.00 0.00
October 0.136280E+10 0.287874E+10 0.135664E+10 0.00 0.135664E+10 0.00 0.00
November 0.276990E+09 0.500261E+10 0.105988E+10 0.00 0.105988E+10 0.00 0.00
December 75508526.98 0.677828E+10 0.102462E+10 0.00 0.102462E+10 0.00 0.00
               
Annual Sum or Average 0.246421E+11 0.374924E+11 0.193662E+11 0.719292E+09 0.186469E+11 0.00 0.00
Minimum of Months 75508526.98 0.583476E+09 0.102462E+10 0.00 0.102462E+10 0.00 0.00
Maximum of Months 0.487273E+10 0.677828E+10 0.232534E+10 0.286273E+09 0.209634E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.171251E+10 0.361871E+10 0.184128E+10 0.998831E+09 0.842454E+09 0.00 0.00
February 0.245041E+10 0.288126E+10 0.222506E+10 0.126827E+10 0.956791E+09 0.00 0.00
March 0.369881E+10 0.267016E+10 0.304157E+10 0.167581E+10 0.136576E+10 0.00 0.00
April 0.517791E+10 0.149197E+10 0.354671E+10 0.196763E+10 0.157908E+10 0.00 0.00
May 0.621210E+10 0.954679E+09 0.378202E+10 0.205539E+10 0.172663E+10 0.00 0.00
June 0.678132E+10 0.445918E+09 0.366208E+10 0.203728E+10 0.162479E+10 0.00 0.00
July 0.631165E+10 0.359920E+09 0.339355E+10 0.177409E+10 0.161946E+10 0.00 0.00
August 0.578944E+10 0.505042E+09 0.322915E+10 0.165265E+10 0.157650E+10 0.00 0.00
September 0.517604E+10 0.103265E+10 0.309601E+10 0.176650E+10 0.132951E+10 0.00 0.00
October 0.345937E+10 0.179066E+10 0.246040E+10 0.132785E+10 0.113254E+10 0.00 0.00
November 0.230411E+10 0.297120E+10 0.213438E+10 0.124257E+10 0.891813E+09 0.00 0.00
December 0.160164E+10 0.399125E+10 0.183970E+10 0.974716E+09 0.864987E+09 0.00 0.00
               
Annual Sum or Average 0.506753E+11 0.227134E+11 0.342519E+11 0.187416E+11 0.155103E+11 0.00 0.00
Minimum of Months 0.160164E+10 0.359920E+09 0.183970E+10 0.974716E+09 0.842454E+09 0.00 0.00
Maximum of Months 0.678132E+10 0.399125E+10 0.378202E+10 0.205539E+10 0.172663E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.940476E+10 0.524121E+10 0.706398E+10 0.535169E+10 0.171229E+10 0.00 0.00
February 0.801076E+10 0.429210E+10 0.591851E+10 0.417245E+10 0.174607E+10 0.00 0.00
March 0.742210E+10 0.421513E+10 0.532539E+10 0.307059E+10 0.225480E+10 0.00 0.00
April 0.550017E+10 0.253501E+10 0.349414E+10 0.130374E+10 0.219040E+10 0.00 0.00
May 0.447791E+10 0.154002E+10 0.255159E+10 0.357134E+09 0.219446E+10 0.00 0.00
June 0.459352E+10 0.726998E+09 0.213037E+10 0.135170E+09 0.199520E+10 0.00 0.00
July 0.479555E+10 0.611138E+09 0.224407E+10 0.208026E+09 0.203604E+10 0.00 0.00
August 0.575196E+10 0.881860E+09 0.286055E+10 0.757197E+09 0.210336E+10 0.00 0.00
September 0.793659E+10 0.171988E+10 0.432095E+10 0.224487E+10 0.207608E+10 0.00 0.00
October 0.952829E+10 0.282524E+10 0.606658E+10 0.410140E+10 0.196518E+10 0.00 0.00
November 0.983334E+10 0.442221E+10 0.706506E+10 0.538623E+10 0.167883E+10 0.00 0.00
December 0.939097E+10 0.572827E+10 0.723513E+10 0.543101E+10 0.180412E+10 0.00 0.00
               
Annual Sum or Average 0.866459E+11 0.347391E+11 0.562763E+11 0.325195E+11 0.237568E+11 0.00 0.00
Minimum of Months 0.447791E+10 0.611138E+09 0.213037E+10 0.135170E+09 0.167883E+10 0.00 0.00
Maximum of Months 0.983334E+10 0.572827E+10 0.723513E+10 0.543101E+10 0.225480E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.201491E+10 0.403544E+10 0.193959E+10 0.109232E+10 0.847266E+09 0.00 0.00
February 0.218703E+10 0.337743E+10 0.197682E+10 0.105072E+10 0.926098E+09 0.00 0.00
March 0.368101E+10 0.324527E+10 0.298246E+10 0.159850E+10 0.138397E+10 0.00 0.00
April 0.481313E+10 0.195767E+10 0.331751E+10 0.179185E+10 0.152566E+10 0.00 0.00
May 0.609421E+10 0.118022E+10 0.369239E+10 0.197559E+10 0.171679E+10 0.00 0.00
June 0.641362E+10 0.627400E+09 0.347831E+10 0.186823E+10 0.161007E+10 0.00 0.00
July 0.585151E+10 0.567598E+09 0.318965E+10 0.158500E+10 0.160465E+10 0.00 0.00
August 0.543240E+10 0.783774E+09 0.308901E+10 0.157428E+10 0.151473E+10 0.00 0.00
September 0.518027E+10 0.127382E+10 0.305709E+10 0.170311E+10 0.135398E+10 0.00 0.00
October 0.395000E+10 0.215284E+10 0.271937E+10 0.158712E+10 0.113226E+10 0.00 0.00
November 0.258781E+10 0.357245E+10 0.220889E+10 0.134498E+10 0.863909E+09 0.00 0.00
December 0.174270E+10 0.477655E+10 0.183937E+10 0.999206E+09 0.840166E+09 0.00 0.00
               
Annual Sum or Average 0.499486E+11 0.275505E+11 0.334905E+11 0.181709E+11 0.153196E+11 0.00 0.00
Minimum of Months 0.174270E+10 0.567598E+09 0.183937E+10 0.999206E+09 0.840166E+09 0.00 0.00
Maximum of Months 0.641362E+10 0.477655E+10 0.369239E+10 0.197559E+10 0.171679E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.230765E+09 0.528355E+10 0.103263E+10 0.00 0.103263E+10 0.00 0.00
February 0.528916E+09 0.429002E+10 0.113893E+10 0.00 0.113893E+10 0.00 0.00
March 0.115995E+10 0.404761E+10 0.165018E+10 0.00 0.165018E+10 0.00 0.00
April 0.213942E+10 0.229792E+10 0.184386E+10 14526939.37 0.182933E+10 0.00 0.00
May 0.366315E+10 0.138307E+10 0.225978E+10 0.163414E+09 0.209637E+10 0.00 0.00
June 0.491463E+10 0.711326E+09 0.232538E+10 0.286281E+09 0.203910E+10 0.00 0.00
July 0.467844E+10 0.579186E+09 0.222074E+10 0.216172E+09 0.200456E+10 0.00 0.00
August 0.365456E+10 0.789273E+09 0.187256E+10 38289082.23 0.183427E+10 0.00 0.00
September 0.267701E+10 0.158223E+10 0.158127E+10 630984.26 0.158064E+10 0.00 0.00
October 0.146049E+10 0.263714E+10 0.135666E+10 0.00 0.135666E+10 0.00 0.00
November 0.394140E+09 0.440131E+10 0.105989E+10 0.00 0.105989E+10 0.00 0.00
December 0.157845E+09 0.583352E+10 0.102464E+10 0.00 0.102464E+10 0.00 0.00
               
Annual Sum or Average 0.256593E+11 0.338362E+11 0.193665E+11 0.719313E+09 0.186472E+11 0.00 0.00
Minimum of Months 0.157845E+09 0.579186E+09 0.102464E+10 0.00 0.102464E+10 0.00 0.00
Maximum of Months 0.491463E+10 0.583352E+10 0.232538E+10 0.286281E+09 0.209637E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.177672E+10 0.330190E+10 0.184128E+10 0.998827E+09 0.842450E+09 0.00 0.00
February 0.248781E+10 0.269372E+10 0.222505E+10 0.126827E+10 0.956787E+09 0.00 0.00
March 0.371040E+10 0.255382E+10 0.304156E+10 0.167580E+10 0.136576E+10 0.00 0.00
April 0.513968E+10 0.150080E+10 0.354670E+10 0.196763E+10 0.157907E+10 0.00 0.00
May 0.617287E+10 0.953590E+09 0.378200E+10 0.205538E+10 0.172662E+10 0.00 0.00
June 0.674206E+10 0.479290E+09 0.366206E+10 0.203728E+10 0.162479E+10 0.00 0.00
July 0.627583E+10 0.398353E+09 0.339354E+10 0.177408E+10 0.161946E+10 0.00 0.00
August 0.575997E+10 0.541123E+09 0.322914E+10 0.165264E+10 0.157649E+10 0.00 0.00
September 0.514996E+10 0.103128E+10 0.309600E+10 0.176649E+10 0.132951E+10 0.00 0.00
October 0.346139E+10 0.171530E+10 0.246039E+10 0.132785E+10 0.113254E+10 0.00 0.00
November 0.234706E+10 0.275607E+10 0.213437E+10 0.124256E+10 0.891809E+09 0.00 0.00
December 0.167795E+10 0.361228E+10 0.183970E+10 0.974712E+09 0.864984E+09 0.00 0.00
               
Annual Sum or Average 0.507017E+11 0.215375E+11 0.342518E+11 0.187415E+11 0.155103E+11 0.00 0.00
Minimum of Months 0.167795E+10 0.398353E+09 0.183970E+10 0.974712E+09 0.842450E+09 0.00 0.00
Maximum of Months 0.674206E+10 0.361228E+10 0.378200E+10 0.205538E+10 0.172662E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.933526E+10 0.515038E+10 0.706420E+10 0.535187E+10 0.171233E+10 0.00 0.00
February 0.795495E+10 0.421096E+10 0.591869E+10 0.417258E+10 0.174610E+10 0.00 0.00
March 0.737152E+10 0.411103E+10 0.532554E+10 0.307069E+10 0.225485E+10 0.00 0.00
April 0.549338E+10 0.247718E+10 0.349422E+10 0.130378E+10 0.219044E+10 0.00 0.00
May 0.449474E+10 0.150436E+10 0.255164E+10 0.357146E+09 0.219449E+10 0.00 0.00
June 0.464921E+10 0.726328E+09 0.213041E+10 0.135175E+09 0.199523E+10 0.00 0.00
July 0.485446E+10 0.605224E+09 0.224411E+10 0.208032E+09 0.203607E+10 0.00 0.00
August 0.579117E+10 0.865045E+09 0.286062E+10 0.757222E+09 0.210339E+10 0.00 0.00
September 0.790227E+10 0.170831E+10 0.432106E+10 0.224494E+10 0.207612E+10 0.00 0.00
October 0.946990E+10 0.277821E+10 0.606675E+10 0.410153E+10 0.196522E+10 0.00 0.00
November 0.978509E+10 0.431628E+10 0.706527E+10 0.538640E+10 0.167887E+10 0.00 0.00
December 0.938168E+10 0.552727E+10 0.723536E+10 0.543119E+10 0.180417E+10 0.00 0.00
               
Annual Sum or Average 0.864836E+11 0.339806E+11 0.562779E+11 0.325206E+11 0.237573E+11 0.00 0.00
Minimum of Months 0.449474E+10 0.605224E+09 0.213041E+10 0.135175E+09 0.167887E+10 0.00 0.00
Maximum of Months 0.978509E+10 0.552727E+10 0.723536E+10 0.543119E+10 0.225485E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.209634E+10 0.358852E+10 0.193958E+10 0.109232E+10 0.847263E+09 0.00 0.00
February 0.228036E+10 0.295999E+10 0.197681E+10 0.105072E+10 0.926094E+09 0.00 0.00
March 0.378335E+10 0.284738E+10 0.298245E+10 0.159849E+10 0.138396E+10 0.00 0.00
April 0.490715E+10 0.173447E+10 0.331750E+10 0.179184E+10 0.152566E+10 0.00 0.00
May 0.610516E+10 0.111172E+10 0.369237E+10 0.197559E+10 0.171679E+10 0.00 0.00
June 0.647236E+10 0.579395E+09 0.347829E+10 0.186823E+10 0.161007E+10 0.00 0.00
July 0.594716E+10 0.489014E+09 0.318963E+10 0.158499E+10 0.160464E+10 0.00 0.00
August 0.554021E+10 0.650636E+09 0.308900E+10 0.157427E+10 0.151472E+10 0.00 0.00
September 0.520604E+10 0.119679E+10 0.305708E+10 0.170310E+10 0.135398E+10 0.00 0.00
October 0.402035E+10 0.192196E+10 0.271936E+10 0.158711E+10 0.113225E+10 0.00 0.00
November 0.269650E+10 0.304686E+10 0.220888E+10 0.134497E+10 0.863906E+09 0.00 0.00
December 0.188376E+10 0.392651E+10 0.183936E+10 0.999202E+09 0.840163E+09 0.00 0.00
               
Annual Sum or Average 0.509387E+11 0.240532E+11 0.334903E+11 0.181708E+11 0.153195E+11 0.00 0.00
Minimum of Months 0.188376E+10 0.489014E+09 0.183936E+10 0.999202E+09 0.840163E+09 0.00 0.00
Maximum of Months 0.647236E+10 0.392651E+10 0.369237E+10 0.197559E+10 0.171679E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.322958E+09 0.471662E+10 0.103263E+10 0.00 0.103263E+10 0.00 0.00
February 0.624943E+09 0.388018E+10 0.113893E+10 0.00 0.113893E+10 0.00 0.00
March 0.126656E+10 0.372897E+10 0.165018E+10 0.00 0.165018E+10 0.00 0.00
April 0.215894E+10 0.220100E+10 0.184386E+10 14526939.37 0.182933E+10 0.00 0.00
May 0.362871E+10 0.137818E+10 0.225978E+10 0.163414E+09 0.209637E+10 0.00 0.00
June 0.484326E+10 0.733637E+09 0.232538E+10 0.286281E+09 0.203910E+10 0.00 0.00
July 0.458696E+10 0.609585E+09 0.222074E+10 0.216172E+09 0.200456E+10 0.00 0.00
August 0.358703E+10 0.802968E+09 0.187256E+10 38289082.23 0.183427E+10 0.00 0.00
September 0.264860E+10 0.157159E+10 0.158127E+10 630984.26 0.158064E+10 0.00 0.00
October 0.151548E+10 0.245885E+10 0.135666E+10 0.00 0.135666E+10 0.00 0.00
November 0.489534E+09 0.392559E+10 0.105989E+10 0.00 0.105989E+10 0.00 0.00
December 0.242010E+09 0.522051E+10 0.102464E+10 0.00 0.102464E+10 0.00 0.00
               
Annual Sum or Average 0.259150E+11 0.312277E+11 0.193665E+11 0.719313E+09 0.186472E+11 0.00 0.00
Minimum of Months 0.242010E+09 0.609585E+09 0.102464E+10 0.00 0.102464E+10 0.00 0.00
Maximum of Months 0.484326E+10 0.522051E+10 0.232538E+10 0.286281E+09 0.209637E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.188626E+10 0.295576E+10 0.184128E+10 0.998827E+09 0.842450E+09 0.00 0.00
February 0.258494E+10 0.245444E+10 0.222505E+10 0.126827E+10 0.956787E+09 0.00 0.00
March 0.378024E+10 0.239627E+10 0.304156E+10 0.167580E+10 0.136576E+10 0.00 0.00
April 0.513332E+10 0.146595E+10 0.354670E+10 0.196763E+10 0.157907E+10 0.00 0.00
May 0.613675E+10 0.955961E+09 0.378200E+10 0.205538E+10 0.172662E+10 0.00 0.00
June 0.668812E+10 0.493631E+09 0.366206E+10 0.203728E+10 0.162479E+10 0.00 0.00
July 0.621164E+10 0.416785E+09 0.339354E+10 0.177408E+10 0.161946E+10 0.00 0.00
August 0.571122E+10 0.552907E+09 0.322914E+10 0.165264E+10 0.157649E+10 0.00 0.00
September 0.512195E+10 0.103483E+10 0.309600E+10 0.176649E+10 0.132951E+10 0.00 0.00
October 0.348569E+10 0.162841E+10 0.246039E+10 0.132785E+10 0.113254E+10 0.00 0.00
November 0.244214E+10 0.249772E+10 0.213437E+10 0.124256E+10 0.891809E+09 0.00 0.00
December 0.179950E+10 0.324052E+10 0.183970E+10 0.974712E+09 0.864984E+09 0.00 0.00
               
Annual Sum or Average 0.509818E+11 0.200932E+11 0.342518E+11 0.187415E+11 0.155103E+11 0.00 0.00
Minimum of Months 0.179950E+10 0.416785E+09 0.183970E+10 0.974712E+09 0.842450E+09 0.00 0.00
Maximum of Months 0.668812E+10 0.324052E+10 0.378200E+10 0.205538E+10 0.172662E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.947641E+10 0.467464E+10 0.706420E+10 0.535187E+10 0.171233E+10 0.00 0.00
February 0.806153E+10 0.387733E+10 0.591869E+10 0.417258E+10 0.174610E+10 0.00 0.00
March 0.745426E+10 0.385979E+10 0.532554E+10 0.307069E+10 0.225485E+10 0.00 0.00
April 0.548842E+10 0.239691E+10 0.349422E+10 0.130378E+10 0.219044E+10 0.00 0.00
May 0.445249E+10 0.149492E+10 0.255164E+10 0.357146E+09 0.219449E+10 0.00 0.00
June 0.458014E+10 0.747008E+09 0.213041E+10 0.135175E+09 0.199523E+10 0.00 0.00
July 0.476537E+10 0.634627E+09 0.224411E+10 0.208032E+09 0.203607E+10 0.00 0.00
August 0.572405E+10 0.882900E+09 0.286062E+10 0.757222E+09 0.210339E+10 0.00 0.00
September 0.785816E+10 0.171077E+10 0.432106E+10 0.224494E+10 0.207612E+10 0.00 0.00
October 0.949092E+10 0.265884E+10 0.606675E+10 0.410153E+10 0.196522E+10 0.00 0.00
November 0.990472E+10 0.397856E+10 0.706527E+10 0.538640E+10 0.167887E+10 0.00 0.00
December 0.956824E+10 0.502251E+10 0.723536E+10 0.543119E+10 0.180417E+10 0.00 0.00
               
Annual Sum or Average 0.868247E+11 0.319388E+11 0.562779E+11 0.325206E+11 0.237573E+11 0.00 0.00
Minimum of Months 0.445249E+10 0.634627E+09 0.213041E+10 0.135175E+09 0.167887E+10 0.00 0.00
Maximum of Months 0.990472E+10 0.502251E+10 0.723536E+10 0.543119E+10 0.225485E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.215732E+10 0.327476E+10 0.193958E+10 0.109232E+10 0.847263E+09 0.00 0.00
February 0.233219E+10 0.273134E+10 0.197681E+10 0.105072E+10 0.926094E+09 0.00 0.00
March 0.382970E+10 0.267047E+10 0.298245E+10 0.159849E+10 0.138396E+10 0.00 0.00
April 0.490236E+10 0.168071E+10 0.331750E+10 0.179184E+10 0.152566E+10 0.00 0.00
May 0.607212E+10 0.110464E+10 0.369237E+10 0.197559E+10 0.171679E+10 0.00 0.00
June 0.642731E+10 0.589459E+09 0.347829E+10 0.186823E+10 0.161007E+10 0.00 0.00
July 0.589635E+10 0.502360E+09 0.318963E+10 0.158499E+10 0.160464E+10 0.00 0.00
August 0.549991E+10 0.657197E+09 0.308900E+10 0.157427E+10 0.151472E+10 0.00 0.00
September 0.518067E+10 0.119405E+10 0.305708E+10 0.170310E+10 0.135398E+10 0.00 0.00
October 0.403777E+10 0.183180E+10 0.271936E+10 0.158711E+10 0.113225E+10 0.00 0.00
November 0.275165E+10 0.279380E+10 0.220888E+10 0.134497E+10 0.863906E+09 0.00 0.00
December 0.195128E+10 0.358439E+10 0.183936E+10 0.999202E+09 0.840163E+09 0.00 0.00
               
Annual Sum or Average 0.510386E+11 0.226150E+11 0.334903E+11 0.181708E+11 0.153195E+11 0.00 0.00
Minimum of Months 0.195128E+10 0.502360E+09 0.183936E+10 0.999202E+09 0.840163E+09 0.00 0.00
Maximum of Months 0.642731E+10 0.358439E+10 0.369237E+10 0.197559E+10 0.171679E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 8.14 3.28 -3.0 3.49 -5.4 41.12 223.64 0.00
February 10.27 3.71 -4.6 3.82 -5.0 51.61 245.22 0.00
March 12.55 4.68 -5.5 4.62 -3.1 72.41 273.25 0.00
April 19.23 8.50 -2.7 4.72 3.38 79.21 314.56 0.00
May 23.84 12.23 2.64 5.25 8.38 86.83 326.20 0.00
June 27.86 15.03 5.88 4.15 14.09 80.19 344.14 0.01
July 27.54 18.92 14.64 3.53 17.44 86.25 283.04 0.01
August 26.28 17.11 12.00 3.28 15.48 80.55 269.68 0.02
September 23.38 15.82 11.20 2.23 11.29 66.71 294.09 0.00
October 18.30 12.02 7.27 3.24 6.21 54.59 257.93 0.01
November 11.18 5.22 -1.5 3.40 -3.3 40.23 258.80 0.00
December 6.79 1.84 -4.8 2.82 -8.9 42.65 217.21 0.00
                 
Annual Sum or Average 17.98 9.90 2.67 3.71 4.26 65.29 275.60 0.00
Minimum of Months 6.79 1.84 -5.5 2.23 -8.9 40.23 217.21 0.00
Maximum of Months 27.86 18.92 14.64 5.25 17.44 86.83 344.14 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 20.60 03-JAN-14:00 8.39 -5.0 9.80 2.22 118.50 530.50
February 23.30 20-FEB-14:00 8.88 -7.8 4.10 4.10 55.00 955.00
March 25.00 21-MAR-15:00 9.53 -8.3 6.20 5.54 50.00 873.00
April 32.20 21-APR-13:00 15.21 2.80 13.90 18.28 265.50 638.50
May 35.00 19-MAY-13:00 17.23 6.10 10.30 21.78 145.00 874.50
June 38.90 02-JUN-15:00 16.22 -1.1 4.60 20.40 234.50 284.00
July 38.30 01-JUL-16:00 19.19 8.90 3.60 26.81 165.50 256.50
August 37.20 07-AUG-15:00 17.89 6.70 5.70 24.66 143.50 615.00
September 33.90 19-SEP-13:00 16.85 6.70 3.10 17.75 113.00 912.00
October 32.80 01-OCT-14:00 15.90 4.40 5.70 16.12 127.50 736.50
November 23.90 03-NOV-15:00 13.45 6.10 5.70 12.22 48.50 648.50
December 18.30 10-DEC-14:00 7.97 -2.8 7.20 4.10 123.00 52.50
                 
Annual Sum or Average                
Minimum of Months 18.30   7.97 -8.3 3.10 2.22 48.50 52.50
Maximum of Months 38.90   19.19 8.90 13.90 26.81 265.50 955.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -4.4 27-JAN-06:00 -7.5 -15.0 3.60 -23.6 0.00 0.00
February -5.6 03-FEB-06:00 -7.5 -11.7 1.50 -23.9 0.00 0.00
March -3.9 02-MAR-04:00 -6.5 -12.8 1.50 -21.3 0.00 0.00
April 3.30 12-APR-05:00 -1.8 -9.4 2.10 -14.9 37.00 217.50
May 9.40 02-MAY-05:00 3.98 -2.2 3.60 -7.6 51.00 277.50
June 15.00 13-JUN-04:00 4.43 -10.6 2.10 -4.3 0.00 0.00
July 17.80 05-JUL-05:00 15.98 15.00 4.10 4.31 39.00 249.00
August 16.70 31-AUG-05:00 13.89 12.20 4.10 2.64 36.00 126.50
September 8.30 30-SEP-05:00 5.77 3.30 1.50 -7.3 0.00 0.00
October 6.70 11-OCT-05:00 5.82 5.00 1.50 -5.5 0.00 0.00
November -0.6 17-NOV-03:00 -3.1 -6.7 1.50 -18.1 0.00 0.00
December -4.4 27-DEC-06:00 -5.1 -6.1 2.10 -18.6 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -5.6   -7.5 -15.0 1.50 -23.9 0.00 0.00
Maximum of Months 17.80   15.98 15.00 4.10 4.31 51.00 277.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.18 12-JAN-15:00 18.90 2.80 3.60 6.15 70.50 491.50
February 11.42 13-FEB-16:00 12.80 10.60 4.10 6.55 34.00 18.50
March 10.75 10-MAR-18:00 13.30 8.90 1.50 8.54 0.00 0.00
April 15.74 29-APR-13:00 30.00 6.70 4.10 18.28 336.50 432.50
May 19.12 24-MAY-12:00 27.80 15.00 5.20 17.57 188.50 862.00
June 20.21 03-JUN-14:00 33.90 13.90 8.80 23.66 264.50 316.00
July 22.88 20-JUL-15:39 25.53 21.87 2.93 18.99 184.00 15.83
August 21.18 02-AUG-11:00 30.60 17.20 3.60 20.75 154.50 850.00
September 20.65 14-SEP-09:00 25.00 18.90 2.10 14.47 126.50 835.50
October 19.64 03-OCT-13:00 32.80 13.30 2.60 21.44 224.50 577.50
November 13.57 03-NOV-14:00 23.30 7.20 0.00 10.88 72.50 802.00
December 8.30 10-DEC-12:00 17.20 -0.6 5.70 1.58 198.50 507.50
                 
Annual Sum or Average                
Minimum of Months 8.30   12.80 -0.6 0.00 1.58 0.00 0.00
Maximum of Months 22.88   33.90 21.87 8.80 23.66 336.50 862.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 9.00 16-JAN-01:00 9.00 9.00 2.10 4.51 0.00 0.00
February 10.60 13-FEB-13:09 12.20 11.24 5.53 5.71 147.33 0.00
March 10.00 11-MAR-00:00 10.60 10.24 2.10 6.15 0.00 0.00
April 10.60 17-APR-01:00 17.80 13.38 7.20 3.48 0.00 0.00
May 15.00 24-MAY-10:00 25.60 18.41 7.20 15.39 171.00 872.50
June 17.20 19-JUN-17:00 23.90 19.20 3.60 15.39 86.00 324.00
July 22.20 20-JUL-14:00 24.40 22.82 4.60 17.93 283.00 59.50
August 18.90 01-AUG-20:00 22.20 19.91 4.60 17.75 0.00 0.00
September 19.40 22-SEP-01:00 20.60 19.76 1.50 16.30 0.00 0.00
October 17.20 03-OCT-19:00 23.30 19.11 4.60 18.46 0.00 0.00
November 10.00 01-NOV-09:00 13.30 11.28 3.10 8.94 123.50 0.00
December 6.10 13-DEC-00:00 8.30 7.10 7.70 3.06 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.10   8.30 7.10 1.50 3.06 0.00 0.00
Maximum of Months 22.20   25.60 22.82 7.70 18.46 283.00 872.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 15.16 28.38 0.00
February 18.00 13.00 16.00 15.21 35.58 0.00
March 18.00 13.00 16.00 16.80 47.71 0.00
April 18.00 13.00 16.00 19.62 58.45 0.00
May 18.00 13.00 16.00 22.88 63.58 0.00
June 18.00 13.00 16.00 25.71 66.73 0.00
July 18.00 13.00 16.00 27.35 58.19 0.00
August 18.00 13.00 16.00 27.33 54.44 0.00
September 18.00 13.00 16.00 25.68 50.89 0.00
October 18.00 13.00 16.00 22.83 39.37 0.00
November 18.00 13.00 16.00 19.57 32.11 0.00
December 18.00 13.00 16.00 16.77 26.90 0.00
             
Annual Sum or Average 18.00 13.00 16.00 21.28 46.90 0.00
Minimum of Months 18.00 13.00 16.00 15.16 26.90 0.00
Maximum of Months 18.00 13.00 16.00 27.35 66.73 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.359153E+11 -0.348914E+11 0.00 0.00 744.00 0.00 -0.102391E+10 58.98 0.00 0.00
February 0.326066E+11 -0.316804E+11 0.00 0.00 672.00 0.00 -926146087.9 58.98 0.00 0.00
March 0.369198E+11 -0.358913E+11 0.00 0.00 744.00 0.00 -0.102851E+10 58.98 0.00 0.00
April 0.313741E+11 -0.303831E+11 0.00 0.00 720.00 0.00 -990993135.4 58.97 0.00 0.00
May 0.308179E+11 -0.297940E+11 0.00 0.00 744.00 0.00 -0.102384E+10 58.97 0.00 0.00
June 0.281764E+11 -0.271848E+11 0.00 0.00 720.00 0.00 -991615633.5 58.98 0.00 0.00
July 0.255974E+11 -0.245793E+11 0.00 0.00 744.00 0.00 -0.101814E+10 58.97 0.00 0.00
August 0.279608E+11 -0.269389E+11 0.00 0.00 744.00 0.00 -0.102196E+10 58.97 0.00 0.00
September 0.267210E+11 -0.257348E+11 0.00 0.00 720.00 0.00 -986179360.4 58.97 0.00 0.00
October 0.298217E+11 -0.288039E+11 0.00 0.00 744.00 0.00 -0.101788E+10 58.97 0.00 0.00
November 0.317716E+11 -0.307860E+11 0.00 0.00 720.00 0.00 -985639553.8 58.97 0.00 0.00
December 0.338230E+11 -0.328032E+11 0.00 0.00 744.00 0.00 -0.101980E+10 58.97 0.00 0.00
                     
Annual Sum or Average 0.371506E+12 -0.359471E+12 0.00 0.00 8760.00 0.00 -0.120346E+11 58.97 0.00 0.00
Minimum of Months 0.255974E+11 -0.358913E+11 0.00 0.00 672.00 0.00 -0.102851E+10 58.97 0.00 0.00
Maximum of Months 0.369198E+11 -0.245793E+11 0.00 0.00 744.00 0.00 -926146087.9 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.50 0.48 01-JAN-08:20 7632.87 36.80 265.17 273.17 1471.33 26.29 152.50 256.83
February 268.33 0.50 0.48 01-FEB-08:09 8317.43 36.28 261.50 263.83 1040.74 21.94 101.50 235.83
March 351.83 0.51 0.48 01-MAR-07:30 1578.99 16.90 10.67 309.00 783.54 19.31 73.83 272.83
April 373.83 0.52 0.48 01-APR-07:30 969.56 16.09 0.00 321.33 591.14 19.01 13.00 271.33
May 408.83 0.53 0.48 01-MAY-06:00 796.43 15.65 0.00 345.00 486.66 18.59 0.17 285.00
June 398.00 0.52 0.48 01-JUN-07:10 711.75 15.45 0.00 337.00 448.17 18.52 0.00 266.67
July 400.17 0.53 0.48 01-JUL-07:10 761.56 15.53 0.00 341.17 459.64 18.52 0.67 256.83
August 377.83 0.52 0.48 01-AUG-07:10 899.52 16.02 0.00 330.83 538.97 18.93 7.00 268.83
September 365.83 0.52 0.48 01-SEP-07:40 1148.48 16.56 11.00 302.00 663.64 18.99 43.33 259.00
October 318.83 0.51 0.48 01-OCT-07:10 2977.83 23.65 128.33 302.50 917.04 19.95 65.83 269.50
November 295.83 0.50 0.48 01-NOV-12:39 7831.14 35.91 278.50 279.00 1148.67 22.89 94.67 263.33
December 289.50 0.50 0.48 01-DEC-07:19 6907.55 37.20 284.00 272.17 1450.99 26.32 160.00 264.33
                         
Annual Sum or Average 4125.67 0.51     2957.68 22.23 1239.17 3677.00 786.10 20.43 712.50 3170.33
Minimum of Months 268.33 0.50 0.48   711.75 15.45 0.00 263.83 448.17 18.52 0.00 235.83
Maximum of Months 408.83 0.53 0.48   8317.43 37.20 284.00 345.00 1471.33 26.32 160.00 285.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.54 0.48 01-JAN-08:09 1903.85 19.88 79.33 223.00 1089.13 22.44 73.67 158.83
February 268.33 0.53 0.48 01-FEB-07:49 2210.92 19.44 68.67 229.00 850.09 20.91 57.83 169.17
March 351.83 0.52 0.48 01-MAR-06:00 2085.96 18.81 81.50 284.33 1140.36 21.96 83.83 241.67
April 373.83 0.52 0.48 01-APR-06:10 2794.88 20.47 109.83 318.83 1000.78 20.55 55.67 277.83
May 408.83 0.52 0.48 01-MAY-05:49 2121.79 18.48 87.00 347.33 1174.42 21.57 77.67 303.00
June 398.00 0.51 0.48 01-JUN-05:49 2164.46 18.60 85.00 341.83 1208.59 21.64 72.33 298.00
July 400.17 0.52 0.48 01-JUL-05:49 1921.68 18.46 84.17 345.17 1035.80 21.49 75.33 291.17
August 377.83 0.52 0.48 01-AUG-05:00 2493.94 19.98 106.67 328.00 925.69 20.59 58.67 280.17
September 365.83 0.52 0.48 01-SEP-06:10 2258.49 18.67 84.83 291.50 888.57 20.87 73.17 253.17
October 318.83 0.53 0.48 01-OCT-06:49 2012.36 19.02 77.67 266.00 1108.43 21.69 74.00 203.50
November 295.83 0.54 0.48 01-NOV-12:00 1651.92 18.90 73.50 225.83 838.99 20.65 55.50 160.83
December 289.50 0.54 0.48 01-DEC-07:19 1347.52 18.47 61.83 225.17 748.27 21.28 71.17 169.50
                         
Annual Sum or Average 4125.67 0.52     2105.33 19.08 1000.00 3426.00 1011.63 21.30 828.83 2806.83
Minimum of Months 268.33 0.51 0.48   1347.52 18.46 61.83 223.00 748.27 20.55 55.50 158.83
Maximum of Months 408.83 0.54 0.48   2794.88 20.47 109.83 347.33 1208.59 22.44 83.83 303.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.57 0.48 01-JAN-09:30 391.59 12.34 0.00 170.83 265.12 15.92 0.00 36.50
February 268.33 0.55 0.48 01-FEB-10:20 446.95 13.15 0.00 193.00 301.59 16.55 0.00 83.17
March 351.83 0.54 0.48 01-MAR-08:30 531.99 14.10 0.00 269.67 344.07 17.23 0.00 168.33
April 373.83 0.51 0.48 01-APR-07:40 631.42 15.39 0.00 341.50 406.26 18.37 0.00 262.33
May 408.83 0.50 0.48 01-MAY-06:19 786.06 16.33 3.00 379.33 452.06 19.08 0.50 337.00
June 398.00 0.49 0.48 01-JUN-06:10 846.77 19.81 83.17 377.00 475.03 19.53 3.17 342.50
July 400.17 0.50 0.48 01-JUL-05:00 799.66 17.90 37.17 381.00 482.02 20.69 37.67 326.33
August 377.83 0.51 0.48 01-AUG-06:10 669.30 15.75 0.00 349.17 422.76 18.67 0.00 282.33
September 365.83 0.53 0.48 01-SEP-08:39 526.42 14.47 0.00 276.83 348.06 17.56 0.00 175.83
October 318.83 0.54 0.48 01-OCT-08:39 471.23 13.51 0.00 248.33 314.64 16.80 0.00 109.67
November 295.83 0.57 0.48 01-NOV-13:30 379.77 12.32 0.00 171.83 260.10 15.86 0.00 29.67
December 289.50 0.57 0.48 01-DEC-09:30 392.01 12.39 0.00 180.00 260.50 15.90 0.00 24.67
                         
Annual Sum or Average 4125.67 0.53     594.20 15.07 123.33 3338.50 371.76 17.88 41.33 2178.33
Minimum of Months 268.33 0.49 0.48   379.77 12.32 0.00 170.83 260.10 15.86 0.00 24.67
Maximum of Months 408.83 0.57 0.48   846.77 19.81 83.17 381.00 482.02 20.69 37.67 342.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.52 0.48 01-JAN-09:20 1622.75 20.41 81.17 231.17 830.85 21.57 69.33 166.50
February 268.33 0.52 0.48 01-FEB-10:09 1838.02 19.51 70.83 226.33 1024.39 22.78 74.50 177.33
March 351.83 0.52 0.48 01-MAR-08:30 2270.20 18.95 84.33 293.83 882.81 20.79 78.67 244.50
April 373.83 0.51 0.48 01-APR-08:30 2748.34 20.44 111.83 320.67 983.79 20.70 59.00 277.67
May 408.83 0.51 0.48 01-MAY-07:40 2017.87 13.83 0.00 355.67 1145.36 18.13 10.83 315.33
June 398.00 0.50 0.48 01-JUN-07:30 2095.22 13.91 0.00 351.83 1182.72 18.21 2.50 305.33
July 400.17 0.51 0.48 01-JUL-07:40 1867.11 14.20 3.67 352.83 1053.40 18.23 7.00 290.50
August 377.83 0.52 0.48 01-AUG-07:49 1928.99 16.96 55.17 326.83 1008.71 18.31 12.50 280.67
September 365.83 0.52 0.48 01-SEP-08:00 2252.86 18.64 84.50 289.83 880.24 20.59 59.67 245.17
October 318.83 0.52 0.48 01-OCT-08:39 1967.08 19.74 82.17 276.33 1008.48 21.38 64.33 220.83
November 295.83 0.53 0.48 01-NOV-12:39 1314.11 17.60 56.50 226.83 739.61 21.26 60.33 172.00
December 289.50 0.53 0.48 01-DEC-09:30 1543.30 19.39 77.83 226.83 660.17 21.75 68.33 166.67
                         
Annual Sum or Average 4125.67 0.52     1985.21 17.55 708.00 3479.00 964.30 20.10 567.00 2862.50
Minimum of Months 268.33 0.50 0.48   1314.11 13.83 0.00 226.33 660.17 18.13 2.50 166.50
Maximum of Months 408.83 0.53 0.48   2748.34 20.44 111.83 355.67 1182.72 22.78 78.67 315.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.50 0.48 01-JAN-08:20 7535.71 34.77 252.50 268.33 1483.35 20.92 86.33 253.67
February 268.33 0.50 0.48 01-FEB-08:09 8317.29 35.93 261.17 263.17 1085.69 17.56 34.67 236.67
March 351.83 0.51 0.48 01-MAR-07:30 1571.59 10.89 10.67 308.00 817.29 15.17 1.83 274.83
April 373.83 0.52 0.48 01-APR-07:19 961.24 10.59 0.00 319.33 613.76 15.49 0.00 273.33
May 408.83 0.53 0.48 01-MAY-06:00 786.60 10.51 0.00 343.00 503.10 15.33 0.00 290.17
June 398.00 0.52 0.48 01-JUN-07:10 703.58 10.19 0.00 336.50 463.24 15.17 0.00 274.00
July 400.17 0.53 0.48 01-JUL-07:10 750.69 10.27 0.00 340.17 474.47 15.16 0.00 263.33
August 377.83 0.52 0.48 01-AUG-06:00 888.79 10.65 0.00 328.00 557.73 15.48 0.00 271.83
September 365.83 0.52 0.48 01-SEP-07:40 1147.76 10.87 11.00 302.17 691.15 15.19 0.00 261.67
October 318.83 0.50 0.48 01-OCT-07:10 2999.59 19.41 127.83 306.17 966.81 15.90 13.33 272.00
November 295.83 0.50 0.48 01-NOV-12:39 7823.79 34.96 274.83 278.33 1228.71 20.37 90.00 269.00
December 289.50 0.50 0.48 01-DEC-07:19 6766.92 34.14 259.83 265.33 1497.47 22.17 101.33 264.83
                         
Annual Sum or Average 4125.67 0.51     2937.19 17.92 1197.83 3658.50 816.28 16.71 327.50 3205.33
Minimum of Months 268.33 0.50 0.48   703.58 10.19 0.00 263.17 463.24 15.16 0.00 236.67
Maximum of Months 408.83 0.53 0.48   8317.29 35.93 274.83 343.00 1497.47 22.17 101.33 290.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.54 0.48 01-JAN-08:09 1906.76 17.26 79.33 223.00 1111.17 20.64 63.33 163.50
February 268.33 0.53 0.48 01-FEB-07:49 2214.48 16.58 68.67 228.50 874.39 18.67 41.00 174.83
March 351.83 0.52 0.48 01-MAR-06:00 2098.34 15.65 81.00 284.67 1074.90 17.96 51.50 245.17
April 373.83 0.52 0.48 01-APR-06:10 2569.91 15.29 82.33 318.50 1032.08 17.89 50.83 283.17
May 408.83 0.52 0.48 01-MAY-05:49 2111.61 15.24 87.00 346.83 1207.13 19.10 72.67 309.50
June 398.00 0.51 0.48 01-JUN-05:49 2165.07 15.20 85.00 340.67 1240.14 19.11 70.00 303.17
July 400.17 0.52 0.48 01-JUL-05:49 1900.26 14.94 82.17 344.00 1064.33 18.97 69.00 295.17
August 377.83 0.52 0.48 01-AUG-05:00 2318.44 15.11 80.17 328.00 953.96 17.96 52.33 285.50
September 365.83 0.52 0.48 01-SEP-06:10 2268.97 15.44 84.83 290.50 916.41 18.32 57.67 258.83
October 318.83 0.53 0.48 01-OCT-06:49 2020.19 16.10 77.67 266.17 1133.49 19.53 60.67 210.17
November 295.83 0.54 0.48 01-NOV-12:00 1656.59 16.02 73.50 227.00 861.93 18.48 50.67 166.00
December 289.50 0.54 0.48 01-DEC-07:19 1347.85 15.62 61.83 224.67 767.56 19.37 50.33 174.17
                         
Annual Sum or Average 4125.67 0.52     2069.22 15.62 943.50 3422.50 1030.99 18.79 690.00 2869.17
Minimum of Months 268.33 0.51 0.48   1347.85 14.94 61.83 223.00 767.56 17.89 41.00 163.50
Maximum of Months 408.83 0.54 0.48   2569.91 17.26 87.00 346.83 1240.14 20.64 72.67 309.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.57 0.48 01-JAN-09:20 385.15 6.98 0.00 164.67 272.80 12.24 0.00 46.50
February 268.33 0.55 0.48 01-FEB-10:09 440.54 8.03 0.00 190.83 310.78 13.18 0.00 92.17
March 351.83 0.54 0.48 01-MAR-08:30 525.60 9.02 0.00 267.67 355.35 14.05 0.00 183.17
April 373.83 0.51 0.48 01-APR-06:40 624.51 10.55 0.00 340.50 419.48 15.54 0.00 270.67
May 408.83 0.50 0.48 01-MAY-06:19 777.86 11.23 3.00 379.17 467.21 16.07 0.00 341.67
June 398.00 0.49 0.48 01-JUN-06:10 839.33 15.52 82.83 376.50 491.41 16.22 1.33 345.17
July 400.17 0.50 0.48 01-JUL-05:00 791.37 13.00 37.17 380.50 496.79 17.74 37.50 332.00
August 377.83 0.51 0.48 01-AUG-06:10 668.86 10.75 0.00 351.00 436.01 15.71 0.00 289.67
September 365.83 0.53 0.48 01-SEP-08:30 520.30 9.59 0.00 275.00 359.36 14.63 0.00 191.33
October 318.83 0.54 0.48 01-OCT-08:30 464.98 8.48 0.00 243.83 324.50 13.57 0.00 129.33
November 295.83 0.57 0.48 01-NOV-13:30 374.21 6.99 0.00 168.33 267.95 12.29 0.00 40.67
December 289.50 0.57 0.48 01-DEC-09:30 384.65 7.06 0.00 175.33 267.63 12.23 0.00 33.33
                         
Annual Sum or Average 4125.67 0.53     587.87 10.07 123.00 3313.33 383.59 14.69 38.83 2295.67
Minimum of Months 268.33 0.49 0.48   374.21 6.98 0.00 164.67 267.63 12.23 0.00 33.33
Maximum of Months 408.83 0.57 0.48   839.33 15.52 82.83 380.50 496.79 17.74 37.50 345.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.52 0.48 01-JAN-09:20 1348.87 14.74 54.67 230.33 853.90 19.58 52.33 173.50
February 268.33 0.52 0.48 01-FEB-09:00 1841.59 16.71 70.83 226.17 1048.22 20.83 61.33 181.67
March 351.83 0.52 0.48 01-MAR-08:30 2281.14 15.83 84.33 293.50 910.51 18.28 52.33 252.33
April 373.83 0.51 0.48 01-APR-08:20 2750.82 17.60 111.67 319.50 1013.32 18.04 51.83 283.17
May 408.83 0.51 0.48 01-MAY-07:30 2010.90 9.41 0.00 354.00 1176.65 14.81 0.00 319.50
June 398.00 0.50 0.48 01-JUN-07:30 2095.88 9.41 0.00 350.50 1213.12 14.92 0.00 309.67
July 400.17 0.51 0.48 01-JUL-07:30 1861.46 9.81 3.67 351.83 1080.27 14.97 0.00 296.00
August 377.83 0.51 0.48 01-AUG-07:40 1921.87 13.35 55.17 326.33 1036.19 15.11 3.67 284.00
September 365.83 0.52 0.48 01-SEP-08:39 2262.55 15.38 84.50 289.50 907.52 17.99 53.33 251.67
October 318.83 0.52 0.48 01-OCT-08:30 2100.88 17.19 86.17 275.83 1035.62 19.05 55.17 226.67
November 295.83 0.53 0.48 01-NOV-12:39 2034.17 16.66 82.17 227.00 762.38 19.13 54.00 179.50
December 289.50 0.53 0.48 01-DEC-09:20 1544.64 16.75 77.83 227.83 678.97 19.86 52.00 173.17
                         
Annual Sum or Average 4125.67 0.52     2029.32 14.10 711.00 3472.33 991.06 17.44 436.00 2930.83
Minimum of Months 268.33 0.50 0.48   1348.87 9.41 0.00 226.17 678.97 14.81 0.00 173.17
Maximum of Months 408.83 0.53 0.48   2750.82 17.60 111.67 354.00 1213.12 20.83 61.33 319.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.50 0.48 01-JAN-08:20 7535.20 34.76 252.50 268.50 1484.27 20.90 86.33 253.67
February 268.33 0.50 0.48 01-FEB-08:09 8317.42 35.91 261.17 263.17 1086.56 17.55 34.67 237.00
March 351.83 0.51 0.48 01-MAR-07:30 1572.06 10.85 10.67 308.00 818.04 15.15 1.83 274.83
April 373.83 0.52 0.48 01-APR-07:19 961.49 10.55 0.00 319.17 614.29 15.47 0.00 273.33
May 408.83 0.53 0.48 01-MAY-06:00 786.73 10.47 0.00 342.83 503.52 15.31 0.00 290.33
June 398.00 0.52 0.48 01-JUN-07:10 703.60 10.14 0.00 336.67 463.58 15.15 0.00 274.17
July 400.17 0.53 0.48 01-JUL-07:10 750.83 10.23 0.00 340.17 474.87 15.14 0.00 263.33
August 377.83 0.52 0.48 01-AUG-06:00 889.02 10.61 0.00 328.00 558.23 15.46 0.00 272.00
September 365.83 0.52 0.48 01-SEP-07:40 1148.10 10.83 11.00 302.17 691.74 15.18 0.00 261.67
October 318.83 0.50 0.48 01-OCT-07:10 2999.82 19.38 127.83 306.17 967.58 15.88 13.33 272.17
November 295.83 0.50 0.48 01-NOV-12:39 7823.42 34.94 274.83 278.33 1229.46 20.35 90.00 269.00
December 289.50 0.50 0.48 01-DEC-07:19 6765.97 34.12 259.83 265.33 1498.45 22.15 101.33 265.00
                         
Annual Sum or Average 4125.67 0.51     2937.23 17.89 1197.83 3658.50 816.91 16.69 327.50 3206.50
Minimum of Months 268.33 0.50 0.48   703.60 10.14 0.00 263.17 463.58 15.14 0.00 237.00
Maximum of Months 408.83 0.53 0.48   8317.42 35.91 274.83 342.83 1498.45 22.15 101.33 290.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.54 0.48 01-JAN-08:09 1906.41 17.22 79.33 223.17 1111.55 20.62 63.33 163.50
February 268.33 0.53 0.48 01-FEB-07:49 2214.03 16.54 68.67 228.50 874.82 18.65 41.00 175.33
March 351.83 0.52 0.48 01-MAR-06:00 2098.04 15.61 81.00 284.67 1075.39 17.95 51.50 245.17
April 373.83 0.52 0.48 01-APR-06:10 2569.62 15.25 82.33 318.50 1032.62 17.87 50.83 283.17
May 408.83 0.52 0.48 01-MAY-05:49 2111.25 15.20 87.00 346.83 1207.66 19.08 72.67 309.50
June 398.00 0.51 0.48 01-JUN-05:49 2164.67 15.16 85.00 340.67 1237.62 19.05 69.50 303.17
July 400.17 0.52 0.48 01-JUL-05:49 1899.94 14.90 82.17 343.83 1013.64 17.76 53.83 291.83
August 377.83 0.52 0.48 01-AUG-05:00 2318.16 15.06 80.17 327.83 954.54 17.94 52.33 285.50
September 365.83 0.52 0.48 01-SEP-06:10 2268.70 15.39 84.83 290.50 916.88 18.30 57.67 258.83
October 318.83 0.53 0.48 01-OCT-06:49 2019.76 16.06 77.67 266.17 1133.94 19.51 60.67 210.33
November 295.83 0.54 0.48 01-NOV-12:00 1683.66 16.17 76.50 226.67 862.26 18.46 50.67 166.00
December 289.50 0.54 0.48 01-DEC-07:19 1812.16 17.54 87.33 224.67 767.96 19.36 50.33 174.33
                         
Annual Sum or Average 4125.67 0.52     2103.45 15.73 972.00 3422.00 1026.21 18.65 674.33 2866.67
Minimum of Months 268.33 0.51 0.48   1683.66 14.90 68.67 223.17 767.96 17.76 41.00 163.50
Maximum of Months 408.83 0.54 0.48   2569.62 17.54 87.33 346.83 1237.62 20.62 72.67 309.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.57 0.48 01-JAN-09:20 384.95 6.94 0.00 164.33 272.94 12.22 0.00 46.50
February 268.33 0.55 0.48 01-FEB-10:09 440.34 7.98 0.00 190.33 310.95 13.16 0.00 92.50
March 351.83 0.54 0.48 01-MAR-08:20 525.51 8.98 0.00 267.67 355.60 14.03 0.00 183.33
April 373.83 0.51 0.48 01-APR-06:40 624.37 10.50 0.00 340.50 419.76 15.52 0.00 271.00
May 408.83 0.50 0.48 01-MAY-06:19 777.77 11.19 3.00 379.17 467.57 16.05 0.00 342.00
June 398.00 0.49 0.48 01-JUN-06:10 839.22 15.48 82.83 376.50 491.77 16.20 1.33 345.33
July 400.17 0.50 0.48 01-JUL-05:00 791.31 12.96 37.17 380.33 497.16 17.72 37.50 332.17
August 377.83 0.51 0.48 01-AUG-06:10 668.76 10.70 0.00 351.00 436.33 15.69 0.00 289.83
September 365.83 0.53 0.48 01-SEP-08:30 520.14 9.55 0.00 275.00 359.58 14.61 0.00 191.50
October 318.83 0.54 0.48 01-OCT-08:30 464.81 8.44 0.00 243.83 324.69 13.55 0.00 129.50
November 295.83 0.57 0.48 01-NOV-13:30 374.02 6.95 0.00 168.33 268.09 12.27 0.00 40.83
December 289.50 0.57 0.48 01-DEC-09:30 384.46 7.02 0.00 175.33 267.79 12.21 0.00 33.83
                         
Annual Sum or Average 4125.67 0.53     587.73 10.03 123.00 3312.33 383.85 14.67 38.83 2298.33
Minimum of Months 268.33 0.49 0.48   374.02 6.94 0.00 164.33 267.79 12.21 0.00 33.83
Maximum of Months 408.83 0.57 0.48   839.22 15.48 82.83 380.33 497.16 17.72 37.50 345.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.83 0.52 0.48 01-JAN-09:20 1348.48 14.70 54.67 230.33 854.26 19.56 52.33 173.50
February 268.33 0.52 0.48 01-FEB-09:00 1841.27 16.67 70.83 226.00 1048.64 20.81 61.33 181.67
March 351.83 0.52 0.48 01-MAR-08:30 2280.96 15.79 84.33 293.17 911.04 18.26 52.33 252.33
April 373.83 0.51 0.48 01-APR-08:20 2750.64 17.56 111.67 319.50 1013.85 18.02 51.83 283.17
May 408.83 0.51 0.48 01-MAY-07:30 2010.62 9.36 0.00 353.67 1177.18 14.79 0.00 319.67
June 398.00 0.50 0.48 01-JUN-07:30 2095.57 9.36 0.00 350.50 1213.64 14.89 0.00 309.67
July 400.17 0.51 0.48 01-JUL-07:30 1861.26 9.76 3.67 351.67 1080.82 14.95 0.00 296.17
August 377.83 0.51 0.48 01-AUG-07:40 1921.69 13.30 55.17 326.33 1036.73 15.09 3.67 284.00
September 365.83 0.52 0.48 01-SEP-08:39 2262.25 15.33 84.50 289.17 908.01 17.97 53.33 251.83
October 318.83 0.52 0.48 01-OCT-08:30 2100.40 17.15 86.17 275.83 1036.06 19.04 55.17 226.67
November 295.83 0.53 0.48 01-NOV-12:39 2033.82 16.62 82.17 226.83 762.70 19.12 54.00 179.67
December 289.50 0.53 0.48 01-DEC-09:20 1544.32 16.71 77.83 227.67 679.34 19.84 52.00 173.67
                         
Annual Sum or Average 4125.67 0.52     2029.04 14.05 711.00 3470.67 991.54 17.42 436.00 2932.00
Minimum of Months 268.33 0.50 0.48   1348.48 9.36 0.00 226.00 679.34 14.79 0.00 173.50
Maximum of Months 408.83 0.53 0.48   2750.64 17.56 111.67 353.67 1213.64 20.81 61.33 319.67



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.127634E+10 20564.68 27-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.905951E+09 21738.46 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.453052E+09 15848.26 02-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 1283636.22 1670.71 12-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.176621E+09 10613.05 28-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.140539E+10 19636.71 27-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.421864E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140539E+10 21738.46   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 13021974.24 1278.44 28-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 3761185.99 649.53 03-FEB-07:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 16783160.23     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 13021974.24 1278.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 11328506.77 1159.36 28-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 7722962.46 1006.59 03-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 1199498.83 689.94 02-MAR-06:04 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 204669.96 232.74 28-NOV-06:10 0.00 0.00 0.00 0.00 0.00
December 13833786.08 1698.03 28-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 34289424.10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 13833786.08 1698.03   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 4395932.51 499.43 28-JAN-07:30 0.00 0.00 0.00 0.00 0.00
February 1845209.61 401.66 03-FEB-07:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 721941.07 494.65 28-NOV-06:06 0.00 0.00 0.00 0.00 0.00
December 10404533.23 6743.45 27-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 17367616.42     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 10404533.23 6743.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.252899E+11 222961.66 27-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.164436E+11 235611.15 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.912402E+10 177045.64 02-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.500743E+09 69092.12 12-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 57183439.28 17897.17 25-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.772346E+10 140472.68 28-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.411837E+11 232329.52 27-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.100323E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.411837E+11 235611.15   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.748734E+10 126400.17 05-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.369161E+10 125222.05 02-FEB-05:01 0.00 0.00 0.00 0.00 0.00
March 0.113359E+10 124774.54 02-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.214716E+10 126840.44 27-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.108047E+11 126117.48 26-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.252644E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.108047E+11 126840.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.351906E+10 127596.63 28-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.132798E+10 127524.31 02-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.459958E+09 127664.26 02-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.991566E+09 126689.84 28-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.509368E+10 128154.58 27-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.113922E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.509368E+10 128154.58   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.105895E+10 139034.99 28-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.566295E+09 139275.49 02-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.168722E+09 139108.68 02-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.414236E+09 139612.82 28-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.207986E+10 139688.65 04-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.428806E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.207986E+10 139688.65   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.251489E+10 126821.20 28-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.117773E+10 126746.65 02-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.218263E+09 126887.03 02-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.516229E+09 125899.66 28-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.336920E+10 127368.07 27-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.779632E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.336920E+10 127368.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.433844E+10 27663.08 27-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.280878E+10 29396.14 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.172846E+10 23190.60 02-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.155398E+09 10887.61 12-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 37506335.56 5336.66 25-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.169049E+10 18837.95 28-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.624389E+10 29175.93 27-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.170030E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.624389E+10 29396.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.203948E+10 74209.92 17-JAN-05:04 0.00 0.00 0.00 0.00 0.00
February 0.584525E+09 73029.80 27-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 95903543.03 72478.91 02-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.726217E+09 73572.77 27-NOV-05:03 0.00 0.00 0.00 0.00 0.00
December 0.288076E+10 73439.67 26-DEC-05:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.632688E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.288076E+10 74209.92   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.354247E+10 14782.31 17-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.207343E+10 14713.85 14-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.937374E+09 14627.97 02-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 62579335.66 11816.99 12-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 34573838.17 7213.28 25-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.164152E+10 14709.22 27-NOV-06:04 0.00 0.00 0.00 0.00 0.00
December 0.446663E+10 14722.50 28-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.127586E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.446663E+10 14782.31   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.159332E+10 13590.01 17-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.758942E+09 13517.19 02-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.371692E+09 13530.17 02-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 14739643.22 4246.92 11-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 27688462.56 4982.55 25-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.733073E+09 13584.83 28-NOV-05:03 0.00 0.00 0.00 0.00 0.00
December 0.205828E+10 13573.04 27-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.555774E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.205828E+10 13590.01   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.116281E+10 16024.00 17-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.674037E+09 16005.22 14-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.359244E+09 15942.26 02-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 30114831.38 5292.74 11-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 1007366.56 301.03 25-OCT-06:00 0.00 0.00 0.00 0.00 0.00
November 0.568281E+09 16029.54 27-NOV-06:04 0.00 0.00 0.00 0.00 0.00
December 0.150856E+10 16023.52 04-DEC-05:33 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.430405E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.150856E+10 16029.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.140442E+10 15368.51 28-JAN-05:01 0.00 0.00 0.00 0.00 0.00
February 0.808410E+09 15398.55 02-FEB-05:01 0.00 0.00 0.00 0.00 0.00
March 0.297721E+09 15381.52 02-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 11432477.90 1196.13 11-APR-05:04 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 1647964.75 361.27 25-OCT-06:35 0.00 0.00 0.00 0.00 0.00
November 0.578390E+09 15448.82 28-NOV-05:22 0.00 0.00 0.00 0.00 0.00
December 0.169577E+10 15499.07 27-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.479779E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.169577E+10 15499.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.248598E+10 0.248598E+10 42006.65 03-JAN-15:00 42006.65 0.00
February 0.00 0.00 0.893686E+10 0.893686E+10 69853.87 21-FEB-16:00 69853.87 0.00
March 0.00 0.00 0.223285E+11 0.223285E+11 82916.34 21-MAR-16:00 82916.34 0.00
April 0.00 0.00 0.635891E+11 0.635891E+11 109641.80 21-APR-14:40 109641.80 0.04
May 0.00 0.00 0.937041E+11 0.935907E+11 138677.38 30-MAY-05:02 138677.38 0.21
June 0.00 0.00 0.131273E+12 0.130873E+12 148145.89 08-JUN-05:02 148145.89 0.47
July 0.00 0.00 0.160633E+12 0.135572E+12 277627.99 21-JUL-05:02 88296.47 0.85
August 0.00 0.00 0.145010E+12 0.135565E+12 236041.98 02-AUG-05:02 94901.29 0.83
September 0.00 0.00 0.101219E+12 0.940994E+11 237531.91 22-SEP-05:02 87066.20 0.56
October 0.00 0.00 0.564725E+11 0.546715E+11 131118.94 02-OCT-05:02 131118.94 0.24
November 0.00 0.00 0.165289E+11 0.165289E+11 77675.94 03-NOV-16:00 77675.94 0.01
December 0.00 0.00 0.117080E+10 0.117080E+10 23769.35 20-DEC-15:00 23769.35 0.00
                 
Annual Sum or Average 0.00 0.00 0.803351E+12 0.759411E+12       0.27
Minimum of Months 0.00 0.00 0.117080E+10 0.117080E+10 23769.35   23769.35 0.00
Maximum of Months 0.00 0.00 0.160633E+12 0.135572E+12 277627.99   148145.89 0.85



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.184799E+11 0.184799E+11 307960.66 03-JAN-14:30 307960.66 0.00
February 0.00 0.00 0.664567E+11 0.664567E+11 480575.53 21-FEB-16:00 480575.53 0.00
March 0.00 0.00 0.160573E+12 0.160573E+12 631219.85 21-MAR-16:00 631219.85 0.00
April 0.00 0.00 0.455301E+12 0.455301E+12 941838.39 21-APR-14:50 941838.39 0.03
May 0.00 0.00 0.818990E+12 0.818055E+12 1287962.49 30-MAY-05:02 1287962.49 0.19
June 0.00 0.00 0.110613E+13 0.110372E+13 1376388.28 08-JUN-05:02 1376388.28 0.41
July 0.00 0.00 0.122677E+13 0.105488E+13 2606947.46 21-JUL-05:02 829931.42 0.70
August 0.00 0.00 0.106085E+13 0.100255E+13 2306519.97 02-AUG-05:02 927250.08 0.65
September 0.00 0.00 0.858480E+12 0.800010E+12 2123298.89 22-SEP-05:02 777733.55 0.51
October 0.00 0.00 0.442585E+12 0.427627E+12 1247106.22 05-OCT-05:03 949007.53 0.22
November 0.00 0.00 0.119447E+12 0.119447E+12 600477.10 03-NOV-16:00 600477.10 0.02
December 0.00 0.00 0.721307E+10 0.721307E+10 136131.25 20-DEC-15:00 136131.25 0.00
                 
Annual Sum or Average 0.00 0.00 0.634128E+13 0.603431E+13       0.23
Minimum of Months 0.00 0.00 0.721307E+10 0.721307E+10 136131.25   136131.25 0.00
Maximum of Months 0.00 0.00 0.122677E+13 0.110372E+13 2606947.46   1376388.28 0.70



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.125096E+10 0.125096E+10 21723.10 03-JAN-15:00 21723.10 0.00
February 0.00 0.00 0.527178E+10 0.527178E+10 40215.97 21-FEB-16:20 40215.97 0.00
March 0.00 0.00 0.141380E+11 0.141380E+11 63977.73 21-MAR-16:00 63977.73 0.00
April 0.00 0.00 0.488827E+11 0.488827E+11 112516.25 21-APR-14:40 112516.25 0.02
May 0.00 0.00 0.916710E+11 0.915640E+11 135874.88 30-MAY-05:02 135874.88 0.20
June 0.00 0.00 0.128898E+12 0.128608E+12 142583.53 15-JUN-14:30 142583.53 0.42
July 0.00 0.00 0.141861E+12 0.123545E+12 267755.16 17-JUL-05:02 90485.43 0.73
August 0.00 0.00 0.120285E+12 0.114372E+12 249467.46 02-AUG-05:02 100346.06 0.66
September 0.00 0.00 0.935412E+11 0.880213E+11 207105.33 22-SEP-05:02 75810.76 0.51
October 0.00 0.00 0.445335E+11 0.432296E+11 124837.92 03-OCT-14:00 110378.79 0.21
November 0.00 0.00 0.928344E+10 0.928344E+10 61812.88 09-NOV-15:00 61812.88 0.01
December 0.00 0.00 0.447675E+09 0.447675E+09 10907.30 23-DEC-15:00 10907.30 0.00
                 
Annual Sum or Average 0.00 0.00 0.700064E+12 0.668614E+12       0.23
Minimum of Months 0.00 0.00 0.447675E+09 0.447675E+09 10907.30   10907.30 0.00
Maximum of Months 0.00 0.00 0.141861E+12 0.128608E+12 267755.16   142583.53 0.73



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.122315E+10 0.122315E+10 29395.47 03-JAN-15:00 29395.47 0.00
February 0.00 0.00 0.405938E+10 0.405938E+10 49187.97 21-FEB-15:00 49187.97 0.00
March 0.00 0.00 0.105637E+11 0.105637E+11 46577.82 21-MAR-16:00 46577.82 0.00
April 0.00 0.00 0.306894E+11 0.306894E+11 68430.28 03-APR-03:02 68430.28 0.03
May 0.00 0.00 0.535422E+11 0.535217E+11 109075.90 29-MAY-15:31 103186.28 0.16
June 0.00 0.00 0.686182E+11 0.685384E+11 105287.29 19-JUN-03:02 78865.33 0.34
July 0.00 0.00 0.819950E+11 0.713148E+11 157583.88 21-JUL-04:03 50051.48 0.54
August 0.00 0.00 0.783016E+11 0.744816E+11 148292.44 02-AUG-03:02 66454.27 0.58
September 0.00 0.00 0.640514E+11 0.610235E+11 146286.35 10-SEP-17:07 96525.95 0.45
October 0.00 0.00 0.360607E+11 0.354924E+11 105648.24 04-OCT-03:02 46031.38 0.17
November 0.00 0.00 0.986823E+10 0.986795E+10 54919.96 10-NOV-04:02 54919.96 0.01
December 0.00 0.00 0.264991E+09 0.264991E+09 13072.44 11-DEC-06:03 13072.44 0.00
                 
Annual Sum or Average 0.00 0.00 0.439238E+12 0.421041E+12       0.19
Minimum of Months 0.00 0.00 0.264991E+09 0.264991E+09 13072.44   13072.44 0.00
Maximum of Months 0.00 0.00 0.819950E+11 0.744816E+11 157583.88   103186.28 0.58



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.478448E+10 0.477237E+10 2559.03 01-JAN-16:50 2553.47 0.00
February 0.00 0.00 0.922526E+10 0.921072E+10 4574.52 20-FEB-17:30 4574.52 0.00
March 0.00 0.00 0.156064E+11 0.156031E+11 7713.09 31-MAR-24:00 7713.09 0.00
April 0.00 0.00 0.203006E+11 0.202814E+11 8414.12 30-APR-19:03 8414.12 0.00
May 0.00 0.00 0.615046E+10 0.608656E+10 4082.86 31-MAY-24:00 4057.23 0.00
June 0.00 0.00 0.110482E+11 0.109314E+11 5922.12 30-JUN-23:45 5922.12 0.00
July 0.00 0.00 0.166954E+11 0.163489E+11 7893.15 31-JUL-23:53 7868.68 0.00
August 0.00 0.00 0.215762E+11 0.212811E+11 8566.76 08-AUG-16:30 8161.54 0.00
September 0.00 0.00 0.619380E+10 0.597764E+10 4087.16 30-SEP-24:00 4087.16 0.00
October 0.00 0.00 0.111228E+11 0.109660E+11 5888.90 31-OCT-24:00 5888.90 0.00
November 0.00 0.00 0.151783E+11 0.151400E+11 6544.47 12-NOV-16:50 6540.46 0.00
December 0.00 0.00 0.203744E+11 0.203687E+11 8231.89 17-DEC-16:40 8231.89 0.00
                 
Annual Sum or Average 0.00 0.00 0.158256E+12 0.156968E+12       0.00
Minimum of Months 0.00 0.00 0.478448E+10 0.477237E+10 2559.03   2553.47 0.00
Maximum of Months 0.00 0.00 0.215762E+11 0.212811E+11 8566.76   8414.12 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.312502E+11 0.311377E+11 21199.08 12-JAN-16:40 20479.21 0.00
February 0.00 0.00 0.773980E+11 0.772535E+11 40773.85 21-FEB-17:00 40773.85 0.00
March 0.00 0.00 0.141075E+12 0.141041E+12 71715.20 31-MAR-24:00 71715.20 0.00
April 0.00 0.00 0.191859E+12 0.191665E+12 79953.39 30-APR-18:53 79953.39 0.00
May 0.00 0.00 0.569199E+11 0.562888E+11 39892.61 31-MAY-24:00 39645.13 0.00
June 0.00 0.00 0.105110E+12 0.103949E+12 57447.76 30-JUN-23:53 57447.76 0.00
July 0.00 0.00 0.158954E+12 0.155500E+12 75752.83 31-JUL-23:53 75514.74 0.00
August 0.00 0.00 0.205514E+12 0.202567E+12 81774.95 08-AUG-16:30 77768.36 0.00
September 0.00 0.00 0.567156E+11 0.545882E+11 38249.15 30-SEP-24:00 38249.15 0.00
October 0.00 0.00 0.101087E+12 0.995356E+11 54329.17 31-OCT-24:00 54329.17 0.00
November 0.00 0.00 0.134258E+12 0.133876E+12 61456.64 09-NOV-16:40 60253.38 0.00
December 0.00 0.00 0.177324E+12 0.177265E+12 74905.29 15-DEC-16:50 74905.29 0.00
                 
Annual Sum or Average 0.00 0.00 0.143747E+13 0.142467E+13       0.00
Minimum of Months 0.00 0.00 0.312502E+11 0.311377E+11 21199.08   20479.21 0.00
Maximum of Months 0.00 0.00 0.205514E+12 0.202567E+12 81774.95   79953.39 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.134996E+10 0.134126E+10 2077.31 12-JAN-16:40 2006.35 0.00
February 0.00 0.00 0.638112E+10 0.636713E+10 4054.62 21-FEB-17:00 4054.62 0.00
March 0.00 0.00 0.131239E+11 0.131207E+11 6869.66 31-MAR-23:20 6869.66 0.00
April 0.00 0.00 0.189418E+11 0.189224E+11 8136.71 30-APR-19:05 8136.71 0.00
May 0.00 0.00 0.570805E+10 0.564479E+10 3997.71 31-MAY-24:00 3972.83 0.00
June 0.00 0.00 0.106560E+11 0.105398E+11 5764.66 30-JUN-23:45 5764.66 0.00
July 0.00 0.00 0.160730E+11 0.157274E+11 7606.60 31-JUL-23:53 7582.65 0.00
August 0.00 0.00 0.206505E+11 0.203557E+11 8296.20 08-AUG-16:30 7890.80 0.00
September 0.00 0.00 0.567119E+10 0.545808E+10 3688.99 30-SEP-23:30 3688.99 0.00
October 0.00 0.00 0.963091E+10 0.947660E+10 5116.19 31-OCT-23:30 5116.19 0.00
November 0.00 0.00 0.120213E+11 0.119834E+11 6170.39 09-NOV-16:50 6049.61 0.00
December 0.00 0.00 0.156436E+11 0.156379E+11 7344.98 15-DEC-16:50 7344.98 0.00
                 
Annual Sum or Average 0.00 0.00 0.135851E+12 0.134575E+12       0.00
Minimum of Months 0.00 0.00 0.134996E+10 0.134126E+10 2077.31   2006.35 0.00
Maximum of Months 0.00 0.00 0.206505E+11 0.203557E+11 8296.20   8136.71 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 20358.24 925092.92 28-JAN-06:01
February 0.00 0.00 01-FEB-00:10 13043.15 956412.37 02-FEB-06:01
March 0.00 0.00 01-MAR-00:10 5684.46 942785.95 02-MAR-06:01
April 0.00 0.00 01-APR-00:10 293.00 88571.08 12-APR-06:05
May 0.00 0.00 01-MAY-00:05 0.00 0.00 01-MAY-00:05
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:03 0.00 0.00 01-JUL-00:03
August 0.00 0.00 01-AUG-00:03 0.00 0.00 01-AUG-00:03
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 56.47 26460.26 25-OCT-06:10
November 0.00 0.00 01-NOV-00:10 6850.89 917738.02 28-NOV-06:01
December 0.00 0.00 01-DEC-00:10 30642.16 975525.82 27-DEC-05:01
             
Annual Sum or Average 0.00     6406.87    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   30642.16 975525.82  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 20936.71 797374.83 03-JAN-14:30 0.00 0.00 01-JAN-00:10
February 73792.38 1172245.64 21-FEB-16:10 74.52 191133.16 20-FEB-10:05
March 149333.57 1238577.62 14-MAR-15:00 75.64 182014.99 19-MAR-09:10
April 369589.76 1364951.67 28-APR-15:40 36.25 149474.57 15-APR-04:03
May 564751.81 1440194.11 30-MAY-12:30 376.51 325501.52 26-MAY-03:02
June 723981.93 1499765.17 06-JUN-12:30 51.16 180531.81 29-JUN-03:02
July 772141.85 2932118.42 20-JUL-15:00 0.00 0.00 01-JUL-00:03
August 709690.07 2866288.82 02-AUG-05:04 0.00 0.00 01-AUG-00:03
September 578951.19 2346626.27 22-SEP-05:02 87.41 295656.48 17-SEP-06:33
October 340323.12 1372030.92 03-OCT-14:00 133.87 201735.77 22-OCT-07:33
November 118059.90 1240971.23 08-NOV-14:40 7.94 92964.33 24-NOV-01:53
December 9896.80 352353.21 08-DEC-14:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 370857.43     70.51    
Minimum of Months 9896.80 352353.21   0.00 0.00  
Maximum of Months 772141.85 2932118.42   376.51 325501.52  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 10700.03 471838.62 03-JAN-14:30 0.00 0.00 01-JAN-00:10
February 40855.95 741572.00 21-FEB-16:00 0.00 0.00 01-FEB-00:10
March 89520.81 905869.11 21-MAR-16:00 0.00 0.00 01-MAR-00:10
April 255460.56 1519878.50 20-APR-05:02 0.00 0.00 01-APR-00:10
May 432525.71 2308808.36 31-MAY-05:02 0.00 0.00 01-MAY-00:05
June 594693.90 2460429.22 08-JUN-05:02 0.00 0.00 01-JUN-00:10
July 640773.97 4288660.17 21-JUL-05:02 0.00 0.00 01-JUL-00:03
August 570146.12 4138198.82 02-AUG-05:02 0.00 0.00 01-AUG-00:03
September 473041.86 3805589.94 22-SEP-05:02 0.00 0.00 01-SEP-00:10
October 247165.02 1976046.12 05-OCT-05:03 0.00 0.00 01-OCT-00:10
November 73083.91 927793.14 03-NOV-12:40 0.00 0.00 01-NOV-00:10
December 4166.66 203002.10 20-DEC-15:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 287335.13     0.00    
Minimum of Months 4166.66 203002.10   0.00 0.00  
Maximum of Months 640773.97 4288660.17   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 18419.02 59569.98 03-JAN-17:00 0.00 0.00 01-JAN-00:10
February 52171.14 120458.42 20-FEB-16:00 0.00 0.00 01-FEB-00:10
March 88109.90 177002.69 21-MAR-16:00 0.00 0.00 01-MAR-00:10
April 157682.94 294780.10 21-APR-15:00 0.00 0.00 01-APR-00:10
May 100751.41 225420.09 19-MAY-16:00 0.00 0.00 01-MAY-00:05
June 176504.28 305496.73 02-JUN-16:00 0.00 0.00 01-JUN-00:10
July 207660.34 335365.87 03-JUL-16:00 0.00 0.00 01-JUL-00:03
August 225530.95 351508.08 07-AUG-16:10 0.00 0.00 01-AUG-00:03
September 97125.43 212982.57 19-SEP-16:00 0.00 0.00 01-SEP-00:10
October 85865.22 235801.29 03-OCT-14:00 0.00 0.00 01-OCT-00:10
November 82117.59 167448.04 03-NOV-16:00 0.00 0.00 01-NOV-00:10
December 98913.44 121349.54 10-DEC-15:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 116291.66     0.00    
Minimum of Months 18419.02 59569.98   0.00 0.00  
Maximum of Months 225530.95 351508.08   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 14445.38 48143.18 30-JAN-13:00
February 0.00 0.00 01-FEB-00:10 14509.82 48133.18 01-FEB-12:30
March 0.00 0.00 01-MAR-00:10 14811.75 47250.48 01-MAR-12:30
April 0.00 0.00 01-APR-00:10 13134.32 44548.22 03-APR-12:00
May 0.00 0.00 01-MAY-00:05 12540.97 41469.24 01-MAY-11:30
June 0.00 0.00 01-JUN-00:10 11907.61 38087.18 01-JUN-11:50
July 0.00 0.00 01-JUL-00:03 10600.10 35575.53 03-JUL-11:50
August 0.00 0.00 01-AUG-00:03 11479.76 35727.41 31-AUG-11:40
September 0.00 0.00 01-SEP-00:10 11353.06 38039.43 29-SEP-11:30
October 0.00 0.00 01-OCT-00:10 12173.85 41527.12 31-OCT-11:30
November 0.00 0.00 01-NOV-00:10 13295.25 44798.02 30-NOV-13:00
December 0.00 0.00 01-DEC-00:10 13665.55 47166.44 29-DEC-12:40
             
Annual Sum or Average 0.00     12817.04    
Minimum of Months 0.00 0.00   10600.10 35575.53  
Maximum of Months 0.00 0.00   14811.75 48143.18  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 9907.87 478378.74 03-JAN-14:30 2954.54 119896.62 27-JAN-15:20
February 41595.51 801665.96 21-FEB-15:20 2486.13 119242.53 02-FEB-13:20
March 91642.34 892158.40 21-MAR-16:00 1941.22 118771.33 17-MAR-05:50
April 271040.89 2198055.29 27-APR-14:30 2515.64 104375.60 10-APR-17:30
May 490661.42 2333571.78 08-MAY-14:20 524.72 87206.70 04-MAY-07:00
June 739232.58 2344929.12 20-JUN-15:00 179.14 59459.35 13-JUN-05:20
July 1046541.93 5425268.64 20-JUL-15:00 0.00 0.00 01-JUL-00:03
August 774572.02 3963118.08 02-AUG-08:20 75.33 23229.08 30-AUG-03:25
September 611479.61 3673277.59 14-SEP-09:50 101.54 44491.03 12-SEP-04:50
October 279055.87 2675489.10 03-OCT-14:00 565.82 69012.66 21-OCT-06:40
November 70711.09 859266.42 09-NOV-15:30 1574.02 133037.27 21-NOV-06:40
December 3096.17 233021.15 08-DEC-14:10 3158.35 120407.84 12-DEC-13:10
             
Annual Sum or Average 371228.51     1332.99    
Minimum of Months 3096.17 233021.15   0.00 0.00  
Maximum of Months 1046541.93 5425268.64   3158.35 133037.27  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.145810E+11 0.92 9478.02 01-JAN-00:30 1.60
February 0.127446E+11 0.89 9478.02 01-FEB-05:02 1.61
March 0.149999E+11 0.95 9478.02 01-MAR-05:02 1.61
April 0.138408E+11 0.90 9478.02 01-APR-04:03 1.61
May 0.148079E+11 0.93 9478.02 01-MAY-03:03 1.61
June 0.146610E+11 0.95 9478.02 01-JUN-04:00 1.60
July 0.147807E+11 0.92 9478.02 01-JUL-04:05 1.60
August 0.164464E+11 1.03 9478.02 01-AUG-03:02 1.59
September 0.158396E+11 1.02 9478.02 01-SEP-03:02 1.59
October 0.159498E+11 1.00 9478.02 01-OCT-14:03 1.60
November 0.151516E+11 0.99 9478.02 01-NOV-03:03 1.59
December 0.149397E+11 0.95 9478.02 01-DEC-04:10 1.60
           
Annual Sum or Average 0.178743E+12 0.95      
Minimum of Months 0.127446E+11 0.89 9478.02   1.59
Maximum of Months 0.164464E+11 1.03 9478.02   1.61



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.468016E+10 0.38 9097.93 02-JAN-15:50 1.20
February 0.506591E+10 0.43 11420.97 21-FEB-16:20 1.39
March 0.767419E+10 0.52 11675.97 28-MAR-05:02 1.40
April 0.101618E+11 0.67 21145.29 03-APR-05:02 2.04
May 0.997742E+10 0.62 21228.25 15-MAY-05:02 2.04
June 0.123676E+11 0.75 21228.25 02-JUN-05:02 2.04
July 0.130683E+11 0.77 21228.25 01-JUL-05:02 2.03
August 0.144952E+11 0.82 21228.25 01-AUG-05:02 2.02
September 0.974685E+10 0.61 21228.25 05-SEP-05:02 2.02
October 0.850617E+10 0.54 21228.25 02-OCT-04:33 2.03
November 0.678738E+10 0.48 12514.37 10-NOV-06:03 1.46
December 0.607201E+10 0.43 11001.40 16-DEC-06:03 1.36
           
Annual Sum or Average 0.108603E+12 0.58      
Minimum of Months 0.468016E+10 0.38 9097.93   1.20
Maximum of Months 0.144952E+11 0.82 21228.25   2.04



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.310885E+11 0.33 101079.45 06-JAN-06:02 1.35
February 0.320631E+11 0.36 91828.90 17-FEB-06:03 1.27
March 0.447015E+11 0.40 86078.26 01-MAR-06:03 1.22
April 0.600778E+11 0.47 197098.59 20-APR-05:02 2.04
May 0.825717E+11 0.56 197098.59 15-MAY-05:02 2.04
June 0.979588E+11 0.65 197098.59 02-JUN-05:02 2.04
July 0.908585E+11 0.60 197098.59 01-JUL-05:02 2.03
August 0.930891E+11 0.61 197098.59 01-AUG-05:02 2.02
September 0.741169E+11 0.52 197098.59 05-SEP-05:02 2.02
October 0.538212E+11 0.43 197098.59 05-OCT-05:03 2.02
November 0.371307E+11 0.37 85315.61 17-NOV-06:03 1.21
December 0.301179E+11 0.33 89382.16 14-DEC-06:02 1.25
           
Annual Sum or Average 0.727596E+12 0.47      
Minimum of Months 0.301179E+11 0.33 85315.61   1.21
Maximum of Months 0.979588E+11 0.65 197098.59   2.04



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.283020E+10 0.33 4230.70 09-JAN-05:01 0.78
February 0.269419E+10 0.34 4230.70 02-FEB-06:01 0.78
March 0.355201E+10 0.36 8451.15 16-MAR-15:20 1.15
April 0.559296E+10 0.44 18756.02 20-APR-05:02 1.87
May 0.868085E+10 0.55 21565.94 30-MAY-05:02 2.04
June 0.113900E+11 0.68 21565.94 05-JUN-05:02 2.03
July 0.105983E+11 0.63 21565.94 01-JUL-05:02 2.03
August 0.103677E+11 0.62 21565.94 01-AUG-05:02 2.02
September 0.778195E+10 0.51 18744.32 05-SEP-05:02 1.85
October 0.488253E+10 0.40 15821.77 05-OCT-05:03 1.66
November 0.311599E+10 0.34 7387.08 10-NOV-06:03 1.05
December 0.281688E+10 0.33 4230.70 04-DEC-05:01 0.78
           
Annual Sum or Average 0.743035E+11 0.46      
Minimum of Months 0.269419E+10 0.33 4230.70   0.78
Maximum of Months 0.113900E+11 0.68 21565.94   2.04



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.158670E+10 1.06 592.41 01-JAN-00:10 1.06
February 0.143315E+10 1.06 592.41 01-FEB-00:10 1.06
March 0.158670E+10 1.06 592.41 01-MAR-00:10 1.06
April 0.153551E+10 1.06 592.41 01-APR-00:10 1.06
May 0.158670E+10 1.06 592.41 01-MAY-00:05 1.05
June 0.153551E+10 1.05 592.41 01-JUN-00:10 1.05
July 0.158670E+10 1.05 592.41 01-JUL-00:03 1.05
August 0.158670E+10 1.05 592.41 01-AUG-00:03 1.05
September 0.153551E+10 1.05 592.41 01-SEP-00:10 1.05
October 0.158670E+10 1.06 592.41 01-OCT-00:10 1.06
November 0.153551E+10 1.06 592.41 01-NOV-00:10 1.06
December 0.158670E+10 1.06 592.41 01-DEC-00:10 1.06
           
Annual Sum or Average 0.186821E+11 1.06      
Minimum of Months 0.143315E+10 1.05 592.41   1.05
Maximum of Months 0.158670E+10 1.06 592.41   1.06



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.150865E+11 1.06 5632.65 01-JAN-00:10 1.06
February 0.136265E+11 1.06 5632.65 01-FEB-00:10 1.06
March 0.150865E+11 1.06 5632.65 01-MAR-00:10 1.06
April 0.145998E+11 1.06 5632.65 01-APR-00:10 1.06
May 0.150865E+11 1.06 5632.65 01-MAY-00:05 1.05
June 0.145998E+11 1.05 5632.65 01-JUN-00:10 1.05
July 0.150865E+11 1.05 5632.65 01-JUL-00:03 1.05
August 0.150865E+11 1.05 5632.65 01-AUG-00:03 1.05
September 0.145998E+11 1.05 5632.65 01-SEP-00:10 1.05
October 0.150865E+11 1.06 5632.65 01-OCT-00:10 1.06
November 0.145998E+11 1.06 5632.65 01-NOV-00:10 1.06
December 0.150865E+11 1.06 5632.65 01-DEC-00:10 1.06
           
Annual Sum or Average 0.177631E+12 1.06      
Minimum of Months 0.136265E+11 1.05 5632.65   1.05
Maximum of Months 0.150865E+11 1.06 5632.65   1.06



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.153200E+10 1.06 571.98 01-JAN-00:10 1.06
February 0.138374E+10 1.06 571.98 01-FEB-00:10 1.06
March 0.153200E+10 1.06 571.98 01-MAR-00:10 1.06
April 0.148258E+10 1.06 571.98 01-APR-00:10 1.06
May 0.153200E+10 1.06 571.98 01-MAY-00:05 1.05
June 0.148258E+10 1.05 571.98 01-JUN-00:10 1.05
July 0.153200E+10 1.05 571.98 01-JUL-00:03 1.05
August 0.153200E+10 1.05 571.98 01-AUG-00:03 1.05
September 0.148258E+10 1.05 571.98 01-SEP-00:10 1.05
October 0.153200E+10 1.06 571.98 01-OCT-00:10 1.06
November 0.148258E+10 1.06 571.98 01-NOV-00:10 1.06
December 0.153200E+10 1.06 571.98 01-DEC-00:10 1.06
           
Annual Sum or Average 0.180380E+11 1.06      
Minimum of Months 0.138374E+10 1.05 571.98   1.05
Maximum of Months 0.153200E+10 1.06 571.98   1.06



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.236275E+09 0.214774E+09 3167.64 28-JAN-06:01 2879.39 2879.39 38.24 5.10
February 0.136214E+09 0.123818E+09 3170.50 03-FEB-06:01 2881.98 2881.98 37.01 5.11
March 65217296.70 59282522.70 3163.97 02-MAR-06:01 2876.05 2876.05 37.37 5.09
April 3163228.05 2875374.30 362.55 12-APR-06:10 329.56 329.56 25.48 0.39
May 0.00 0.00 0.00 01-MAY-00:05 0.00 0.00 24.42 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 24.42 0.00
July 0.00 0.00 0.00 01-JUL-00:03 0.00 0.00 24.42 0.00
August 0.00 0.00 0.00 01-AUG-00:03 0.00 0.00 24.42 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 24.42 0.00
October 622375.03 565738.90 107.68 25-OCT-06:10 97.88 97.88 23.36 0.11
November 76724839.46 69742879.07 3194.88 28-NOV-06:01 2904.15 2904.15 38.54 5.18
December 0.356993E+09 0.324507E+09 3187.46 26-DEC-06:01 2897.40 2897.40 37.72 5.16
                 
Annual Sum or Average 0.875210E+09 0.795566E+09            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 23.36 0.00
Maximum of Months 0.356993E+09 0.324507E+09 3194.88   2904.15 2904.15 38.54 5.18



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 6447437.29 5860720.50 170.27 12-JAN-15:00 154.77 154.77 8.82 11.01
February 22233774.70 20210501.21 256.29 22-FEB-13:40 232.97 232.97 8.76 13.70
March 55969641.04 50876403.71 305.16 16-MAR-14:50 277.39 277.39 7.87 15.01
April 0.222298E+09 0.202069E+09 2757.61 28-APR-14:20 2506.67 2506.67 6.72 42.43
May 0.581312E+09 0.528412E+09 3004.46 18-MAY-05:02 2731.05 2731.05 8.53 44.04
June 0.102028E+10 0.927430E+09 11052.45 05-JUN-05:02 10046.68 10046.68 8.23 75.81
July 0.109033E+10 0.991110E+09 19497.02 17-JUL-05:02 17722.79 17722.79 8.25 94.99
August 0.101424E+10 0.921946E+09 19344.08 02-AUG-05:02 17583.76 17583.76 8.45 94.69
September 0.874177E+09 0.794627E+09 16076.00 22-SEP-05:02 14613.09 14613.09 8.52 88.03
October 0.344399E+09 0.313058E+09 4483.37 05-OCT-05:03 4075.38 4075.38 7.83 52.27
November 65375893.91 59426687.56 1455.11 03-NOV-12:40 1322.69 1322.69 8.79 31.92
December 1913685.78 1739540.38 48.30 07-DEC-14:30 43.90 43.90 8.71 5.26
                 
Annual Sum or Average 0.529897E+10 0.481677E+10            
Minimum of Months 1913685.78 1739540.38 48.30   43.90 43.90 6.72 5.26
Maximum of Months 0.109033E+10 0.991110E+09 19497.02   17722.79 17722.79 8.82 94.99



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.532390E+10 0.483943E+10 13419.27 01-JAN-11:40 12198.12 12198.12 8.43 94.99
February 0.787604E+10 0.715932E+10 13419.27 01-FEB-11:00 12198.12 12198.12 8.43 94.99
March 0.124184E+11 0.112883E+11 13419.27 01-MAR-06:03 12198.12 12198.12 8.43 94.99
April 0.229289E+11 0.208424E+11 13419.27 01-APR-05:03 12198.12 12198.12 8.72 94.99
May 0.259424E+11 0.235816E+11 13419.27 01-MAY-00:05 12198.12 12198.12 7.78 94.99
June 0.308444E+11 0.280375E+11 13419.27 01-JUN-00:12 12198.12 12198.12 7.07 94.99
July 0.332234E+11 0.302001E+11 13419.27 01-JUL-00:23 12198.12 12198.12 7.01 94.99
August 0.333570E+11 0.303215E+11 13419.27 01-AUG-00:03 12198.12 12198.12 8.30 94.99
September 0.246128E+11 0.223731E+11 13419.27 01-SEP-00:10 12198.12 12198.12 7.47 94.99
October 0.193927E+11 0.176280E+11 13419.27 01-OCT-07:30 12198.12 12198.12 8.37 94.99
November 0.993338E+10 0.902945E+10 13419.27 01-NOV-05:03 12198.12 12198.12 8.84 94.99
December 0.472143E+10 0.429178E+10 13419.27 01-DEC-06:15 12198.12 12198.12 8.45 94.99
                 
Annual Sum or Average 0.230575E+12 0.209592E+12            
Minimum of Months 0.472143E+10 0.429178E+10 13419.27   12198.12 12198.12 7.01 94.99
Maximum of Months 0.333570E+11 0.303215E+11 13419.27   12198.12 12198.12 8.84 94.99



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.187647E+10 0.170571E+10 700.59 01-JAN-00:10 636.84 636.84 20.18 2.96
February 0.169488E+10 0.154064E+10 700.59 01-FEB-00:10 636.84 636.84 22.59 2.96
March 0.187647E+10 0.170571E+10 700.59 01-MAR-00:10 636.84 636.84 25.19 2.96
April 0.181594E+10 0.165069E+10 700.59 01-APR-00:10 636.84 636.84 28.69 2.96
May 0.187647E+10 0.170571E+10 700.59 01-MAY-00:05 636.84 636.84 24.47 2.96
June 0.181594E+10 0.165069E+10 700.59 01-JUN-00:10 636.84 636.84 32.21 2.96
July 0.187647E+10 0.170571E+10 700.59 01-JUL-00:03 636.84 636.84 38.01 2.96
August 0.187647E+10 0.170571E+10 700.59 01-AUG-00:03 636.84 636.84 40.94 2.96
September 0.181594E+10 0.165069E+10 700.59 01-SEP-00:10 636.84 636.84 26.63 2.96
October 0.187647E+10 0.170571E+10 700.59 01-OCT-00:10 636.84 636.84 23.92 2.96
November 0.181594E+10 0.165069E+10 700.59 01-NOV-00:10 636.84 636.84 26.21 2.96
December 0.187647E+10 0.170571E+10 700.59 01-DEC-00:10 636.84 636.84 27.76 2.96
                 
Annual Sum or Average 0.220939E+11 0.200834E+11            
Minimum of Months 0.169488E+10 0.154064E+10 700.59   636.84 636.84 20.18 2.96
Maximum of Months 0.187647E+10 0.170571E+10 700.59   636.84 636.84 40.94 2.96



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 11967951.72 3590385.52 5.96 01-JAN-06:10 1.79 1.79 55.97 0.44
February 10809762.85 3242928.85 5.96 01-FEB-06:03 1.79 1.79 56.54 0.44
March 11967951.72 3590385.52 5.96 01-MAR-06:03 1.79 1.79 55.58 0.44
April 11581888.76 3474566.63 5.96 01-APR-05:03 1.79 1.79 57.02 0.44
May 11967951.72 3590385.52 5.96 01-MAY-05:02 1.79 1.79 57.01 0.44
June 11581888.76 3474566.63 5.96 01-JUN-05:03 1.79 1.79 56.81 0.44
July 11967951.72 3590385.52 5.96 01-JUL-05:02 1.79 1.79 56.62 0.44
August 11967951.72 3590385.52 5.96 01-AUG-05:02 1.79 1.79 57.18 0.44
September 11581888.76 3474566.63 5.96 01-SEP-05:02 1.79 1.79 57.15 0.44
October 11967951.72 3590385.52 5.96 01-OCT-05:10 1.79 1.79 57.11 0.44
November 11581888.76 3474566.63 5.96 01-NOV-05:03 1.79 1.79 56.63 0.44
December 11967951.72 3590385.52 5.96 01-DEC-06:03 1.79 1.79 55.94 0.44
                 
Annual Sum or Average 0.140913E+09 42273893.99            
Minimum of Months 10809762.85 3242928.85 5.96   1.79 1.79 55.58 0.44
Maximum of Months 11967951.72 3590385.52 5.96   1.79 1.79 57.18 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.661547E+10 0.601347E+10 16696.84 03-JAN-14:30 15177.43 15177.43 23.14 56.10
February 0.979769E+10 0.890610E+10 33383.66 21-FEB-16:00 30345.75 30345.75 22.71 112.19
March 0.157209E+11 0.142903E+11 33386.78 14-MAR-15:00 30348.58 30348.58 22.84 112.19
April 0.303109E+11 0.275526E+11 33460.59 27-APR-14:30 30415.67 30415.67 25.79 112.19
May 0.386490E+11 0.351320E+11 33468.69 08-MAY-14:20 30423.04 30423.04 26.08 112.19
June 0.497022E+11 0.451793E+11 33469.37 20-JUN-15:00 30423.66 30423.66 26.10 112.19
July 0.545078E+11 0.495476E+11 33545.50 17-JUL-07:20 30492.86 30492.86 28.98 112.19
August 0.521965E+11 0.474466E+11 33545.50 02-AUG-08:00 30492.86 30492.86 29.11 112.19
September 0.390978E+11 0.355399E+11 33545.50 14-SEP-09:50 30492.86 30492.86 28.93 112.19
October 0.266303E+11 0.242070E+11 33489.16 03-OCT-14:00 30441.65 30441.65 26.81 112.19
November 0.125448E+11 0.114033E+11 33387.09 08-NOV-14:40 30348.86 30348.86 22.86 112.19
December 0.586598E+10 0.533218E+10 16684.28 08-DEC-14:10 15166.01 15166.01 22.09 56.10
                 
Annual Sum or Average 0.341639E+12 0.310550E+12            
Minimum of Months 0.586598E+10 0.533218E+10 16684.28   15166.01 15166.01 22.09 56.10
Maximum of Months 0.545078E+11 0.495476E+11 33545.50   30492.86 30492.86 29.11 112.19



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 79.95 79.95 20358.24 925092.92 28-JAN-06:01
February 0.00 0.00 01-FEB-00:10 24.42 24.42 13043.15 956412.37 02-FEB-06:01
March 0.00 0.00 01-MAR-00:10 24.37 24.37 5684.46 942785.95 02-MAR-06:01
April 0.00 0.00 01-APR-00:10 26.57 26.57 293.00 88571.08 12-APR-06:05
May 0.00 0.00 01-MAY-00:05 24.42 24.42 0.00 0.00 01-MAY-00:05
June 0.00 0.00 01-JUN-00:10 24.42 24.42 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:03 24.42 24.42 0.00 0.00 01-JUL-00:03
August 0.00 0.00 01-AUG-00:03 24.42 24.42 0.00 0.00 01-AUG-00:03
September 0.00 0.00 01-SEP-00:10 24.42 24.42 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 24.42 24.42 56.47 26460.26 25-OCT-06:10
November 0.00 0.00 01-NOV-00:10 22.98 22.98 6850.89 917738.02 28-NOV-06:01
December 0.00 0.00 01-DEC-00:10 24.48 24.48 30642.16 975525.82 27-DEC-05:01
                 
Annual Sum or Average 0.00         6406.87    
Minimum of Months 0.00 0.00   22.98 22.98 0.00 0.00  
Maximum of Months 0.00 0.00   79.95 79.95 30642.16 975525.82  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 20936.71 797374.83 03-JAN-14:30 9.67 8.65 0.00 0.00 01-JAN-00:10
February 73792.38 1172245.64 21-FEB-16:10 10.25 8.65 74.52 191133.16 20-FEB-10:05
March 149333.57 1238577.62 14-MAR-15:00 10.23 8.54 75.64 182014.99 19-MAR-09:10
April 369589.76 1364951.67 28-APR-15:40 10.13 6.70 36.25 149474.57 15-APR-04:03
May 564751.81 1440194.11 30-MAY-12:30 10.32 6.70 376.51 325501.52 26-MAY-03:02
June 723981.93 1499765.17 06-JUN-12:30 10.47 6.70 51.16 180531.81 29-JUN-03:02
July 772141.85 2932118.42 20-JUL-15:00 14.42 8.70 0.00 0.00 01-JUL-00:03
August 709690.07 2866288.82 02-AUG-05:04 14.74 9.01 0.00 0.00 01-AUG-00:03
September 578951.19 2346626.27 22-SEP-05:02 13.61 7.88 87.41 295656.48 17-SEP-06:33
October 340323.12 1372030.92 03-OCT-14:00 10.15 6.70 133.87 201735.77 22-OCT-07:33
November 118059.90 1240971.23 08-NOV-14:40 10.27 8.58 7.94 92964.33 24-NOV-01:53
December 9896.80 352353.21 08-DEC-14:10 8.94 8.49 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 370857.43         70.51    
Minimum of Months 9896.80 352353.21   8.94 6.70 0.00 0.00  
Maximum of Months 772141.85 2932118.42   14.74 9.01 376.51 325501.52  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 10700.03 471838.62 03-JAN-14:30 18.33 8.64 0.00 0.00 01-JAN-00:10
February 40855.95 741572.00 21-FEB-16:00 20.64 8.62 0.00 0.00 01-FEB-00:10
March 89520.81 905869.11 21-MAR-16:00 21.66 8.09 0.00 0.00 01-MAR-00:10
April 255460.56 1519878.50 20-APR-05:02 18.45 8.39 0.00 0.00 01-APR-00:10
May 432525.71 2308808.36 31-MAY-05:02 21.17 7.13 0.00 0.00 01-MAY-00:05
June 594693.90 2460429.22 08-JUN-05:02 21.16 6.93 0.00 0.00 01-JUN-00:10
July 640773.97 4288660.17 21-JUL-05:02 17.57 7.74 0.00 0.00 01-JUL-00:03
August 570146.12 4138198.82 02-AUG-05:02 17.15 8.41 0.00 0.00 01-AUG-00:03
September 473041.86 3805589.94 22-SEP-05:02 17.03 8.33 0.00 0.00 01-SEP-00:10
October 247165.02 1976046.12 05-OCT-05:03 15.74 7.66 0.00 0.00 01-OCT-00:10
November 73083.91 927793.14 03-NOV-12:40 13.64 8.87 0.00 0.00 01-NOV-00:10
December 4166.66 203002.10 20-DEC-15:00 16.81 8.48 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 287335.13         0.00    
Minimum of Months 4166.66 203002.10   13.64 6.93 0.00 0.00  
Maximum of Months 640773.97 4288660.17   21.66 8.87 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 18419.02 59569.98 03-JAN-17:00 24.12 21.12 0.00 0.00 01-JAN-00:10
February 52171.14 120458.42 20-FEB-16:00 29.97 24.30 0.00 0.00 01-FEB-00:10
March 88109.90 177002.69 21-MAR-16:00 35.35 26.57 0.00 0.00 01-MAR-00:10
April 157682.94 294780.10 21-APR-15:00 46.38 34.40 0.00 0.00 01-APR-00:10
May 100751.41 225420.09 19-MAY-16:00 39.91 35.75 0.00 0.00 01-MAY-00:05
June 176504.28 305496.73 02-JUN-16:00 47.37 40.21 0.00 0.00 01-JUN-00:10
July 207660.34 335365.87 03-JUL-16:00 50.12 40.14 0.00 0.00 01-JUL-00:03
August 225530.95 351508.08 07-AUG-16:10 51.61 39.38 0.00 0.00 01-AUG-00:03
September 97125.43 212982.57 19-SEP-16:00 38.74 34.64 0.00 0.00 01-SEP-00:10
October 85865.22 235801.29 03-OCT-14:00 40.88 34.04 0.00 0.00 01-OCT-00:10
November 82117.59 167448.04 03-NOV-16:00 34.44 25.50 0.00 0.00 01-NOV-00:10
December 98913.44 121349.54 10-DEC-15:00 30.05 20.07 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 116291.66         0.00    
Minimum of Months 18419.02 59569.98   24.12 20.07 0.00 0.00  
Maximum of Months 225530.95 351508.08   51.61 40.21 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 57.72 57.72 14445.38 48143.18 30-JAN-13:00
February 0.00 0.00 01-FEB-00:10 57.11 57.11 14509.82 48133.18 01-FEB-12:30
March 0.00 0.00 01-MAR-00:10 56.16 56.16 14811.75 47250.48 01-MAR-12:30
April 0.00 0.00 01-APR-00:10 57.48 57.48 13134.32 44548.22 03-APR-12:00
May 0.00 0.00 01-MAY-00:05 57.63 57.63 12540.97 41469.24 01-MAY-11:30
June 0.00 0.00 01-JUN-00:10 57.21 57.21 11907.61 38087.18 01-JUN-11:50
July 0.00 0.00 01-JUL-00:03 57.12 57.12 10600.10 35575.53 03-JUL-11:50
August 0.00 0.00 01-AUG-00:03 57.50 57.50 11479.76 35727.41 31-AUG-11:40
September 0.00 0.00 01-SEP-00:10 57.88 57.88 11353.06 38039.43 29-SEP-11:30
October 0.00 0.00 01-OCT-00:10 57.81 57.81 12173.85 41527.12 31-OCT-11:30
November 0.00 0.00 01-NOV-00:10 57.22 57.22 13295.25 44798.02 30-NOV-13:00
December 0.00 0.00 01-DEC-00:10 56.64 56.64 13665.55 47166.44 29-DEC-12:40
                 
Annual Sum or Average 0.00         12817.04    
Minimum of Months 0.00 0.00   56.16 56.16 10600.10 35575.53  
Maximum of Months 0.00 0.00   57.88 57.88 14811.75 48143.18  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 9907.87 478378.74 03-JAN-14:30 23.14 21.10 2954.54 119896.62 27-JAN-15:20
February 41595.51 801665.96 21-FEB-15:20 24.52 21.10 2486.13 119242.53 02-FEB-13:20
March 91642.34 892158.40 21-MAR-16:00 24.91 21.10 1941.22 118771.33 17-MAR-05:50
April 271040.89 2198055.29 27-APR-14:30 25.79 21.10 2515.64 104375.60 10-APR-17:30
May 490661.42 2333571.78 08-MAY-14:20 26.08 21.53 524.72 87206.70 04-MAY-07:00
June 739232.58 2344929.12 20-JUN-15:00 26.10 22.75 179.14 59459.35 13-JUN-05:20
July 1046541.93 5425268.64 20-JUL-15:00 32.67 27.47 0.00 0.00 01-JUL-00:03
August 774572.02 3963118.08 02-AUG-08:20 29.55 25.13 75.33 23229.08 30-AUG-03:25
September 611479.61 3673277.59 14-SEP-09:50 28.93 24.73 101.54 44491.03 12-SEP-04:50
October 279055.87 2675489.10 03-OCT-14:00 26.81 23.42 565.82 69012.66 21-OCT-06:40
November 70711.09 859266.42 09-NOV-15:30 24.77 21.10 1574.02 133037.27 21-NOV-06:40
December 3096.17 233021.15 08-DEC-14:10 22.09 21.10 3158.35 120407.84 12-DEC-13:10
                 
Annual Sum or Average 371228.51         1332.99    
Minimum of Months 3096.17 233021.15   22.09 21.10 0.00 0.00  
Maximum of Months 1046541.93 5425268.64   32.67 27.47 3158.35 133037.27  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.130509E+10 0.00 0.248598E+10 0.468016E+10 0.00 0.00
February 0.919281E+09 0.00 0.893686E+10 0.506591E+10 0.00 0.00
March 0.454251E+09 0.00 0.223285E+11 0.767419E+10 0.00 0.00
April 1283636.22 0.00 0.635891E+11 0.101618E+11 0.00 0.00
May 0.00 0.00 0.937041E+11 0.997742E+10 0.00 0.00
June 0.00 0.00 0.131273E+12 0.123676E+11 0.00 0.00
July 0.00 0.00 0.160633E+12 0.130683E+11 0.00 0.00
August 0.00 0.00 0.145010E+12 0.144952E+11 0.00 0.00
September 0.00 0.00 0.101219E+12 0.974685E+10 0.00 0.00
October 0.00 0.00 0.564725E+11 0.850617E+10 0.00 0.00
November 0.177548E+09 0.00 0.165289E+11 0.678738E+10 0.00 0.00
December 0.142962E+10 0.00 0.117080E+10 0.607201E+10 0.00 0.00
             
Annual Sum or Average 0.428708E+10 0.00 0.803351E+12 0.108603E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.117080E+10 0.468016E+10 0.00 0.00
Maximum of Months 0.142962E+10 0.00 0.160633E+12 0.144952E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.398701E+11 0.00 0.184799E+11 0.310885E+11 0.00 0.00
February 0.232072E+11 0.00 0.664567E+11 0.320631E+11 0.00 0.00
March 0.111046E+11 0.00 0.160573E+12 0.447015E+11 0.00 0.00
April 0.500743E+09 0.00 0.455301E+12 0.600778E+11 0.00 0.00
May 0.00 0.00 0.818990E+12 0.825717E+11 0.00 0.00
June 0.00 0.00 0.110613E+13 0.979588E+11 0.00 0.00
July 0.00 0.00 0.122677E+13 0.908585E+11 0.00 0.00
August 0.00 0.00 0.106085E+13 0.930891E+11 0.00 0.00
September 0.00 0.00 0.858480E+12 0.741169E+11 0.00 0.00
October 57183439.28 0.00 0.442585E+12 0.538212E+11 0.00 0.00
November 0.117926E+11 0.00 0.119447E+12 0.371307E+11 0.00 0.00
December 0.625311E+11 0.00 0.721307E+10 0.301179E+11 0.00 0.00
             
Annual Sum or Average 0.149064E+12 0.00 0.634128E+13 0.727596E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.721307E+10 0.301179E+11 0.00 0.00
Maximum of Months 0.625311E+11 0.00 0.122677E+13 0.979588E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.140809E+11 0.00 0.125096E+10 0.283020E+10 0.00 0.00
February 0.770812E+10 0.00 0.527178E+10 0.269419E+10 0.00 0.00
March 0.379040E+10 0.00 0.141380E+11 0.355201E+10 0.00 0.00
April 0.274264E+09 0.00 0.488827E+11 0.559296E+10 0.00 0.00
May 0.00 0.00 0.916710E+11 0.868085E+10 0.00 0.00
June 0.00 0.00 0.128898E+12 0.113900E+11 0.00 0.00
July 0.00 0.00 0.141861E+12 0.105983E+11 0.00 0.00
August 0.00 0.00 0.120285E+12 0.103677E+11 0.00 0.00
September 0.00 0.00 0.935412E+11 0.778195E+10 0.00 0.00
October 0.102424E+09 0.00 0.445335E+11 0.488253E+10 0.00 0.00
November 0.593798E+10 0.00 0.928344E+10 0.311599E+10 0.00 0.00
December 0.188539E+11 0.00 0.447675E+09 0.281688E+10 0.00 0.00
             
Annual Sum or Average 0.507480E+11 0.00 0.700064E+12 0.743035E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.447675E+09 0.269419E+10 0.00 0.00
Maximum of Months 0.188539E+11 0.00 0.141861E+12 0.113900E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.122315E+10 0.145810E+11 0.00 0.00
February 0.00 0.00 0.405938E+10 0.127446E+11 0.00 0.00
March 0.00 0.00 0.105637E+11 0.149999E+11 0.00 0.00
April 0.00 0.00 0.306894E+11 0.138408E+11 0.00 0.00
May 0.00 0.00 0.535422E+11 0.148079E+11 0.00 0.00
June 0.00 0.00 0.686182E+11 0.146610E+11 0.00 0.00
July 0.00 0.00 0.819950E+11 0.147807E+11 0.00 0.00
August 0.00 0.00 0.783016E+11 0.164464E+11 0.00 0.00
September 0.00 0.00 0.640514E+11 0.158396E+11 0.00 0.00
October 0.00 0.00 0.360607E+11 0.159498E+11 0.00 0.00
November 0.00 0.00 0.986823E+10 0.151516E+11 0.00 0.00
December 0.00 0.00 0.264991E+09 0.149397E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.439238E+12 0.178743E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.264991E+09 0.127446E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.819950E+11 0.164464E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.597633E+10 0.277855E+10 0.00 0.00
February 0.00 0.00 0.114306E+11 0.363844E+10 0.00 0.00
March 0.00 0.00 0.192077E+11 0.518794E+10 0.00 0.00
April 0.00 0.00 0.253245E+11 0.655939E+10 0.00 0.00
May 0.00 0.00 0.796631E+10 0.340255E+10 0.00 0.00
June 0.00 0.00 0.145222E+11 0.500953E+10 0.00 0.00
July 0.00 0.00 0.216671E+11 0.655844E+10 0.00 0.00
August 0.00 0.00 0.276509E+11 0.766138E+10 0.00 0.00
September 0.00 0.00 0.796671E+10 0.330842E+10 0.00 0.00
October 0.00 0.00 0.138686E+11 0.433254E+10 0.00 0.00
November 0.00 0.00 0.185811E+11 0.493834E+10 0.00 0.00
December 0.00 0.00 0.248041E+11 0.601645E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.198966E+12 0.593920E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.597633E+10 0.277855E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.276509E+11 0.766138E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.392790E+11 0.231152E+11 0.00 0.00
February 0.00 0.00 0.961319E+11 0.323604E+11 0.00 0.00
March 0.00 0.00 0.173859E+12 0.478711E+11 0.00 0.00
April 0.00 0.00 0.239429E+12 0.621695E+11 0.00 0.00
May 0.00 0.00 0.737929E+11 0.319594E+11 0.00 0.00
June 0.00 0.00 0.138164E+12 0.476538E+11 0.00 0.00
July 0.00 0.00 0.206279E+12 0.624110E+11 0.00 0.00
August 0.00 0.00 0.263365E+12 0.729376E+11 0.00 0.00
September 0.00 0.00 0.730199E+11 0.309041E+11 0.00 0.00
October 0.00 0.00 0.126194E+12 0.401940E+11 0.00 0.00
November 0.00 0.00 0.164633E+12 0.449753E+11 0.00 0.00
December 0.00 0.00 0.216357E+12 0.541195E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.181050E+13 0.550671E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.392790E+11 0.231152E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.263365E+12 0.729376E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.171493E+10 0.189696E+10 0.00 0.00
February 0.00 0.00 0.795385E+10 0.295647E+10 0.00 0.00
March 0.00 0.00 0.162075E+11 0.461554E+10 0.00 0.00
April 0.00 0.00 0.236649E+11 0.620569E+10 0.00 0.00
May 0.00 0.00 0.740979E+10 0.323373E+10 0.00 0.00
June 0.00 0.00 0.140128E+11 0.483937E+10 0.00 0.00
July 0.00 0.00 0.208654E+11 0.632435E+10 0.00 0.00
August 0.00 0.00 0.264767E+11 0.735820E+10 0.00 0.00
September 0.00 0.00 0.731050E+10 0.312188E+10 0.00 0.00
October 0.00 0.00 0.120459E+11 0.394695E+10 0.00 0.00
November 0.00 0.00 0.147795E+11 0.424079E+10 0.00 0.00
December 0.00 0.00 0.191464E+11 0.503475E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.171588E+12 0.537747E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.171493E+10 0.189696E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.264767E+11 0.735820E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.468016E+10 0.248598E+10 0.130509E+10 0.00 0.00 0.00 0.00 0.00
February 0.506591E+10 0.893686E+10 0.919281E+09 0.00 0.00 0.00 0.00 0.00
March 0.767419E+10 0.223285E+11 0.454251E+09 0.00 0.00 0.00 0.00 0.00
April 0.101618E+11 0.635891E+11 1283636.22 0.00 0.00 0.00 0.00 0.00
May 0.997742E+10 0.937041E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.123676E+11 0.131273E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.130683E+11 0.160633E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.144952E+11 0.145010E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.974685E+10 0.101219E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.850617E+10 0.564725E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.678738E+10 0.165289E+11 0.177548E+09 0.00 0.00 0.00 0.00 0.00
December 0.607201E+10 0.117080E+10 0.142962E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.108603E+12 0.803351E+12 0.428708E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.468016E+10 0.117080E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144952E+11 0.160633E+12 0.142962E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.310885E+11 0.184799E+11 0.398701E+11 0.00 0.00 0.00 0.00 0.00
February 0.320631E+11 0.664567E+11 0.232072E+11 0.00 0.00 0.00 0.00 0.00
March 0.447015E+11 0.160573E+12 0.111046E+11 0.00 0.00 0.00 0.00 0.00
April 0.600778E+11 0.455301E+12 0.500743E+09 0.00 0.00 0.00 0.00 0.00
May 0.825717E+11 0.818990E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.979588E+11 0.110613E+13 0.00 0.00 0.00 0.00 0.00 0.00
July 0.908585E+11 0.122677E+13 0.00 0.00 0.00 0.00 0.00 0.00
August 0.930891E+11 0.106085E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.741169E+11 0.858480E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.538212E+11 0.442585E+12 57183439.28 0.00 0.00 0.00 0.00 0.00
November 0.371307E+11 0.119447E+12 0.117926E+11 0.00 0.00 0.00 0.00 0.00
December 0.301179E+11 0.721307E+10 0.625311E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.727596E+12 0.634128E+13 0.149064E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.301179E+11 0.721307E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.979588E+11 0.122677E+13 0.625311E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.283020E+10 0.125096E+10 0.140809E+11 0.00 0.00 0.00 0.00 0.00
February 0.269419E+10 0.527178E+10 0.770812E+10 0.00 0.00 0.00 0.00 0.00
March 0.355201E+10 0.141380E+11 0.379040E+10 0.00 0.00 0.00 0.00 0.00
April 0.559296E+10 0.488827E+11 0.274264E+09 0.00 0.00 0.00 0.00 0.00
May 0.868085E+10 0.916710E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.113900E+11 0.128898E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.105983E+11 0.141861E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.103677E+11 0.120285E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.778195E+10 0.935412E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.488253E+10 0.445335E+11 0.102424E+09 0.00 0.00 0.00 0.00 0.00
November 0.311599E+10 0.928344E+10 0.593798E+10 0.00 0.00 0.00 0.00 0.00
December 0.281688E+10 0.447675E+09 0.188539E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.743035E+11 0.700064E+12 0.507480E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.269419E+10 0.447675E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.113900E+11 0.141861E+12 0.188539E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.145810E+11 0.122315E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.127446E+11 0.405938E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.149999E+11 0.105637E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.138408E+11 0.306894E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.148079E+11 0.535422E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.146610E+11 0.686182E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.147807E+11 0.819950E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.164464E+11 0.783016E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.158396E+11 0.640514E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.159498E+11 0.360607E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.151516E+11 0.986832E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.149397E+11 0.264991E+09 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.178743E+12 0.439238E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.127446E+11 0.264991E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.164464E+11 0.819950E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.158670E+10 0.478448E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.143315E+10 0.922526E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.158670E+10 0.156064E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.153551E+10 0.203006E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.158670E+10 0.615046E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.153551E+10 0.110482E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.158670E+10 0.166954E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.158670E+10 0.215762E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.153551E+10 0.619380E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.158670E+10 0.111228E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.153551E+10 0.151783E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.158670E+10 0.203744E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.186821E+11 0.158256E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.143315E+10 0.478448E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.158670E+10 0.215762E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.150865E+11 0.312502E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.136265E+11 0.773980E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.150865E+11 0.141075E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.145998E+11 0.191859E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.150865E+11 0.569199E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.145998E+11 0.105110E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.150865E+11 0.158954E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.150865E+11 0.205514E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.145998E+11 0.567156E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.150865E+11 0.101087E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.145998E+11 0.134258E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.150865E+11 0.177324E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.177631E+12 0.143747E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.136265E+11 0.312502E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.150865E+11 0.205514E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.153200E+10 0.134996E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.138374E+10 0.638112E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.153200E+10 0.131239E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.148258E+10 0.189418E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.153200E+10 0.570805E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.148258E+10 0.106560E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.153200E+10 0.160730E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.153200E+10 0.206505E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.148258E+10 0.567119E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.153200E+10 0.963091E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.148258E+10 0.120213E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.153200E+10 0.156436E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.180380E+11 0.135851E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.138374E+10 0.134996E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.153200E+10 0.206505E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.468016E+10 0.130509E+10 0.248598E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.506591E+10 0.919281E+09 0.893686E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.767419E+10 0.454251E+09 0.223285E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.101618E+11 1283636.22 0.635891E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.997742E+10 0.00 0.937041E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.123676E+11 0.00 0.131273E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.130683E+11 0.00 0.160633E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.144952E+11 0.00 0.145010E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.974685E+10 0.00 0.101219E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.850617E+10 0.00 0.564725E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.678738E+10 0.177548E+09 0.165289E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.607201E+10 0.142962E+10 0.117080E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.108603E+12 0.428708E+10 0.803351E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.468016E+10 0.00 0.117080E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144952E+11 0.142962E+10 0.160633E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.310885E+11 0.398701E+11 0.184799E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.320631E+11 0.232072E+11 0.664567E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.447015E+11 0.111046E+11 0.160573E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.600778E+11 0.500743E+09 0.455301E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.825717E+11 0.00 0.818990E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.979588E+11 0.00 0.110613E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.908585E+11 0.00 0.122677E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.930891E+11 0.00 0.106085E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.741169E+11 0.00 0.858480E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.538212E+11 57183439.28 0.442585E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.371307E+11 0.117926E+11 0.119447E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.301179E+11 0.625311E+11 0.721307E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.727596E+12 0.149064E+12 0.634128E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.301179E+11 0.00 0.721307E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.979588E+11 0.625311E+11 0.122677E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.283020E+10 0.140809E+11 0.125096E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.269419E+10 0.770812E+10 0.527178E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.355201E+10 0.379040E+10 0.141380E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.559296E+10 0.274264E+09 0.488827E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.868085E+10 0.00 0.916710E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.113900E+11 0.00 0.128898E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.105983E+11 0.00 0.141861E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.103677E+11 0.00 0.120285E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.778195E+10 0.00 0.935412E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.488253E+10 0.102424E+09 0.445335E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.311599E+10 0.593798E+10 0.928344E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.281688E+10 0.188539E+11 0.447675E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.743035E+11 0.507480E+11 0.700064E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.269419E+10 0.00 0.447675E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.113900E+11 0.188539E+11 0.141861E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.145810E+11 0.00 0.122315E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.127446E+11 0.00 0.405938E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.149999E+11 0.00 0.105637E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.138408E+11 0.00 0.306894E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.148079E+11 0.00 0.535422E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.146610E+11 0.00 0.686182E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.147807E+11 0.00 0.819950E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.164464E+11 0.00 0.783016E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.158396E+11 0.00 0.640514E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.159498E+11 0.00 0.360607E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.151516E+11 0.00 0.986823E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.149397E+11 0.00 0.264991E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.178743E+12 0.00 0.439238E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.127446E+11 0.00 0.264991E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.164464E+11 0.00 0.819950E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.158670E+10 0.00 0.597633E+10 0.00 0.119185E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.143315E+10 0.00 0.114306E+11 0.00 0.220530E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.158670E+10 0.00 0.192077E+11 0.00 0.360124E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.153551E+10 0.00 0.253245E+11 0.00 0.502387E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.158670E+10 0.00 0.796631E+10 0.00 0.181585E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.153551E+10 0.00 0.145222E+11 0.00 0.347402E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.158670E+10 0.00 0.216671E+11 0.00 0.497174E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.158670E+10 0.00 0.276509E+11 0.00 0.607468E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.153551E+10 0.00 0.796671E+10 0.00 0.177290E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.158670E+10 0.00 0.138686E+11 0.00 0.274585E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.153551E+10 0.00 0.185811E+11 0.00 0.340282E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.158670E+10 0.00 0.248041E+11 0.00 0.442976E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.186821E+11 0.00 0.198966E+12 0.00 0.407099E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.143315E+10 0.00 0.597633E+10 0.00 0.119185E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.158670E+10 0.00 0.276509E+11 0.00 0.607468E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.150865E+11 0.00 0.392790E+11 0.00 0.802871E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.136265E+11 0.00 0.961319E+11 0.00 0.187339E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.150865E+11 0.00 0.173859E+12 0.00 0.327846E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.145998E+11 0.00 0.239429E+12 0.00 0.475697E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.150865E+11 0.00 0.737929E+11 0.00 0.168729E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.145998E+11 0.00 0.138164E+12 0.00 0.330540E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.150865E+11 0.00 0.206279E+12 0.00 0.473245E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.150865E+11 0.00 0.263365E+12 0.00 0.578511E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.145998E+11 0.00 0.730199E+11 0.00 0.163043E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.150865E+11 0.00 0.126194E+12 0.00 0.251075E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.145998E+11 0.00 0.164633E+12 0.00 0.303754E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.150865E+11 0.00 0.216357E+12 0.00 0.390330E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.177631E+12 0.00 0.181050E+13 0.00 0.373040E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.136265E+11 0.00 0.392790E+11 0.00 0.802871E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.150865E+11 0.00 0.263365E+12 0.00 0.578511E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.153200E+10 0.00 0.171493E+10 0.00 0.364965E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.138374E+10 0.00 0.795385E+10 0.00 0.157273E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.153200E+10 0.00 0.162075E+11 0.00 0.308355E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.148258E+10 0.00 0.236649E+11 0.00 0.472312E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.153200E+10 0.00 0.740979E+10 0.00 0.170174E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.148258E+10 0.00 0.140128E+11 0.00 0.335679E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.153200E+10 0.00 0.208654E+11 0.00 0.479236E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.153200E+10 0.00 0.264767E+11 0.00 0.582620E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.148258E+10 0.00 0.731050E+10 0.00 0.163930E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.153200E+10 0.00 0.120459E+11 0.00 0.241495E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.148258E+10 0.00 0.147795E+11 0.00 0.275822E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.153200E+10 0.00 0.191464E+11 0.00 0.350275E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.180380E+11 0.00 0.171588E+12 0.00 0.357367E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.138374E+10 0.00 0.171493E+10 0.00 0.364965E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.153200E+10 0.00 0.264767E+11 0.00 0.582620E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.672397E+09 0.00 0.00 0.100622E+09 0.00 0.00 0.640030E+11 0.00 0.85
February 0.422503E+09 0.00 0.00 81914584.96 0.00 0.00 0.528153E+11 0.00 0.94
March 0.387089E+09 0.00 0.00 92802211.81 0.00 0.00 0.562360E+11 0.00 1.17
April 0.125789E+09 0.375707E+09 0.00 82050799.11 24414257.15 0.00 0.333576E+11 0.00 1.01
May 56157432.19 0.131242E+10 0.00 62281157.45 78680938.15 0.00 0.168710E+11 0.00 0.82
June 24983448.00 0.484863E+10 0.00 42083487.38 0.146375E+09 0.00 0.650775E+10 0.00 0.64
July 31494135.81 0.108561E+11 0.00 22512182.81 0.126383E+09 0.00 0.205289E+10 0.00 0.66
August 47420305.89 0.378103E+10 0.00 64809805.92 88647047.05 0.00 0.907388E+10 0.00 0.85
September 0.161105E+09 0.189729E+10 0.00 81352853.85 31934641.26 0.00 0.157401E+11 0.00 0.91
October 0.286089E+09 0.302914E+09 0.00 0.113774E+09 9823474.50 0.00 0.440715E+11 0.00 1.31
November 0.551642E+09 0.00 0.00 0.117533E+09 0.00 0.00 0.649439E+11 0.00 1.20
December 0.814483E+09 0.00 0.00 0.113268E+09 0.00 0.00 0.702220E+11 0.00 0.86
                   
Annual Sum or Average 0.358115E+10 0.233741E+11 0.00 0.975004E+09 0.506258E+09 0.00 0.435895E+12 0.00 0.94
Minimum of Months 24983448.00 0.00 0.00 22512182.81 0.00 0.00 0.205289E+10 0.00 0.64
Maximum of Months 0.814483E+09 0.108561E+11 0.00 0.117533E+09 0.146375E+09 0.00 0.702220E+11 0.00 1.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.373020E+10 0.00 0.00 65676531.99 0.00 0.00 0.423559E+11 0.00 0.58
February 0.359477E+10 0.00 0.00 65172476.90 0.00 0.00 0.387359E+11 0.00 0.71
March 0.514466E+10 0.00 0.00 84160389.96 0.00 0.00 0.440465E+11 0.00 0.92
April 0.859483E+10 0.246919E+09 0.00 71527766.88 0.143781E+09 0.00 0.257334E+11 0.00 0.95
May 0.382003E+10 0.856194E+09 0.00 52717273.95 0.353629E+09 0.00 0.111944E+11 0.00 0.66
June 0.268508E+10 0.315031E+10 0.00 33149024.59 0.640303E+09 0.00 0.395086E+10 0.00 0.57
July 0.674211E+09 0.101196E+11 0.00 9580931.64 0.325956E+10 0.00 0.625772E+09 0.00 0.58
August 0.266314E+10 0.337998E+10 0.00 44789938.33 0.100375E+10 0.00 0.611782E+10 0.00 0.77
September 0.251208E+10 0.180046E+10 0.00 49081055.58 0.450442E+09 0.00 0.842631E+10 0.00 0.66
October 0.481049E+10 0.486058E+09 0.00 75689246.22 25630553.98 0.00 0.293259E+11 0.00 0.92
November 0.557655E+10 0.00 0.00 82280795.94 0.00 0.00 0.441328E+11 0.00 0.85
December 0.458145E+10 0.00 0.00 82690092.91 0.00 0.00 0.506153E+11 0.00 0.64
                   
Annual Sum or Average 0.483875E+11 0.200395E+11 0.00 0.716516E+09 0.587710E+10 0.00 0.305261E+12 0.00 0.73
Minimum of Months 0.674211E+09 0.00 0.00 9580931.64 0.00 0.00 0.625772E+09 0.00 0.57
Maximum of Months 0.859483E+10 0.101196E+11 0.00 84160389.96 0.325956E+10 0.00 0.506153E+11 0.00 0.95



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.128778E+12 0.00 0.00 0.252556E+09 0.00 0.00 0.198221E+12 0.00 0.41
February 0.911314E+11 0.00 0.00 0.298041E+09 0.00 0.00 0.209801E+12 0.00 0.51
March 0.646957E+11 0.00 0.00 0.469537E+09 0.00 0.00 0.277819E+12 0.00 0.65
April 0.255550E+11 0.223852E+10 0.00 0.528347E+09 0.115074E+10 0.00 0.192568E+12 0.00 0.63
May 0.243139E+11 0.890866E+10 0.00 0.448100E+09 0.278874E+10 0.00 0.953909E+11 0.00 0.55
June 0.142569E+11 0.325359E+11 0.00 0.272339E+09 0.610905E+10 0.00 0.335496E+11 0.00 0.46
July 0.284428E+10 0.876112E+11 0.00 67903776.73 0.157388E+11 0.00 0.422954E+10 0.00 0.42
August 0.664036E+10 0.292577E+11 0.00 0.340026E+09 0.697269E+10 0.00 0.492107E+11 0.00 0.53
September 0.164923E+11 0.181798E+11 0.00 0.387019E+09 0.340480E+10 0.00 0.635492E+11 0.00 0.53
October 0.291898E+11 0.453021E+10 0.00 0.520604E+09 0.470790E+09 0.00 0.211288E+12 0.00 0.68
November 0.748083E+11 0.00 0.00 0.392917E+09 0.00 0.00 0.243265E+12 0.00 0.56
December 0.145435E+12 0.00 0.00 0.223629E+09 0.00 0.00 0.186066E+12 0.00 0.39
                   
Annual Sum or Average 0.624140E+12 0.183262E+12 0.00 0.420102E+10 0.366357E+11 0.00 0.176496E+13 0.00 0.53
Minimum of Months 0.284428E+10 0.00 0.00 67903776.73 0.00 0.00 0.422954E+10 0.00 0.39
Maximum of Months 0.145435E+12 0.876112E+11 0.00 0.528347E+09 0.157388E+11 0.00 0.277819E+12 0.00 0.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.222475E+11 0.00 0.00 2091877.92 0.00 0.774106E+09 0.296479E+10 0.00 0.35
February 0.166504E+11 0.00 0.00 7235728.91 0.00 57959366.25 0.680844E+10 0.00 0.43
March 0.129334E+11 0.00 0.00 21416298.03 0.00 8914699.02 0.145220E+11 0.00 0.55
April 0.431721E+10 0.122570E+09 0.00 42631402.29 87549220.25 0.00 0.144892E+11 0.00 0.60
May 0.249119E+10 0.534139E+09 0.00 48529216.45 0.283363E+09 0.00 0.820123E+10 0.00 0.55
June 0.137974E+10 0.258483E+10 0.00 33432591.94 0.542134E+09 0.00 0.331985E+10 0.00 0.46
July 0.326642E+09 0.836468E+10 0.00 8754666.41 0.170043E+10 0.00 0.410308E+09 0.00 0.44
August 0.693870E+09 0.239415E+10 0.00 38777766.70 0.695990E+09 0.00 0.480462E+10 0.00 0.53
September 0.189953E+10 0.138018E+10 0.00 40381477.30 0.326357E+09 0.00 0.492781E+10 0.00 0.51
October 0.561432E+10 0.323911E+09 0.00 36323470.04 80882310.26 0.00 0.142133E+11 0.00 0.62
November 0.156499E+11 359062.42 0.00 12949574.40 2907217.42 0.282563E+09 0.870879E+10 0.00 0.47
December 0.232587E+11 0.00 0.00 915638.72 0.00 0.112277E+10 0.180178E+10 0.00 0.34
                   
Annual Sum or Average 0.107463E+12 0.157048E+11 0.00 0.293440E+09 0.371961E+10 0.224631E+10 0.851721E+11 0.00 0.49
Minimum of Months 0.326642E+09 0.00 0.00 915638.72 0.00 0.00 0.410308E+09 0.00 0.34
Maximum of Months 0.232587E+11 0.836468E+10 0.00 48529216.45 0.170043E+10 0.112277E+10 0.145220E+11 0.00 0.62



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.310880E+10 0.00 0.00 644448.11 0.00 0.00 0.830666E+09 0.00 0.39
February 0.231885E+10 0.00 0.00 1828191.81 0.00 0.00 0.133125E+10 0.00 0.50
March 0.192849E+10 0.00 0.00 4313842.73 0.00 0.00 0.250099E+10 0.00 0.70
April 0.133059E+10 44047728.84 0.00 7136150.34 16491625.28 0.00 0.235218E+10 0.00 0.89
May 0.539590E+09 0.179419E+09 0.00 7165816.93 36892085.24 0.00 0.131484E+10 0.00 0.74
June 0.328161E+09 0.750738E+09 0.00 5722391.53 45904324.49 0.00 0.626817E+09 0.00 0.76
July 78975239.33 0.188763E+10 0.00 1705816.11 0.350889E+09 0.00 0.104263E+09 0.00 0.75
August 0.344491E+09 0.605528E+09 0.00 6577968.06 0.110091E+09 0.00 0.800509E+09 0.00 0.88
September 0.412818E+09 0.292451E+09 0.00 5589848.05 51655900.39 0.00 0.801851E+09 0.00 0.68
October 0.106470E+10 75616149.66 0.00 6032942.75 3213413.33 0.00 0.231036E+10 0.00 0.79
November 0.212907E+10 0.00 0.00 3254930.35 0.00 0.00 0.199215E+10 0.00 0.58
December 0.312675E+10 0.00 0.00 1010178.21 0.00 0.00 0.105946E+10 0.00 0.39
                   
Annual Sum or Average 0.167113E+11 0.383543E+10 0.00 50982524.98 0.615137E+09 0.00 0.160253E+11 0.00 0.67
Minimum of Months 78975239.33 0.00 0.00 644448.11 0.00 0.00 0.104263E+09 0.00 0.39
Maximum of Months 0.312675E+10 0.188763E+10 0.00 7165816.93 0.350889E+09 0.00 0.250099E+10 0.00 0.89



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.188189E+10 0.00 0.00 1841506.98 0.00 0.00 0.157548E+10 0.00 0.52
February 0.138339E+10 0.00 0.00 2970499.00 0.00 0.00 0.206971E+10 0.00 0.71
March 0.131181E+10 0.00 0.00 5608544.87 0.00 0.00 0.327932E+10 0.00 1.06
April 0.104195E+10 35039615.29 0.00 8193107.93 12414921.27 0.00 0.286137E+10 0.00 1.37
May 0.407055E+09 0.158233E+09 0.00 8369165.32 27983641.00 0.00 0.171438E+10 0.00 1.23
June 0.269561E+09 0.583055E+09 0.00 5439722.40 38152356.50 0.00 0.579589E+09 0.00 1.05
July 69472569.80 0.147452E+10 0.00 1442415.84 0.306472E+09 0.00 81666847.53 0.00 0.96
August 0.298101E+09 0.510941E+09 0.00 5162097.67 95449857.86 0.00 0.643731E+09 0.00 1.14
September 0.305307E+09 0.301272E+09 0.00 6451680.09 37092165.27 0.00 0.104055E+10 0.00 1.11
October 0.927699E+09 54984586.42 0.00 6126025.45 2326695.03 0.00 0.236823E+10 0.00 1.14
November 0.162286E+10 0.00 0.00 3836910.03 0.00 0.00 0.220478E+10 0.00 0.81
December 0.213314E+10 0.00 0.00 1486405.54 0.00 0.00 0.137780E+10 0.00 0.50
                   
Annual Sum or Average 0.116522E+11 0.311804E+10 0.00 56928081.14 0.519891E+09 0.00 0.197966E+11 0.00 0.97
Minimum of Months 69472569.80 0.00 0.00 1442415.84 0.00 0.00 81666847.53 0.00 0.50
Maximum of Months 0.213314E+10 0.147452E+10 0.00 8369165.32 0.306472E+09 0.00 0.327932E+10 0.00 1.37



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.147786E+10 0.00 0.00 9607921.95 0.00 0.00 0.677624E+10 0.00 0.87
February 0.125015E+10 0.00 0.00 9593185.35 0.00 0.00 0.576188E+10 0.00 1.01
March 0.142273E+10 0.00 0.00 11000115.49 0.00 0.00 0.587368E+10 0.00 1.22
April 0.130231E+10 72914898.54 0.00 9983686.65 14463776.90 0.00 0.315748E+10 0.00 1.12
May 0.562668E+09 0.209691E+09 0.00 7475498.17 35149605.84 0.00 0.131061E+10 0.00 0.77
June 0.332381E+09 0.750461E+09 0.00 5432672.97 46523573.67 0.00 0.569365E+09 0.00 0.73
July 79080316.03 0.188075E+10 0.00 1662933.07 0.352433E+09 0.00 95324551.00 0.00 0.74
August 0.335740E+09 0.725153E+09 0.00 7494873.99 0.103901E+09 0.00 0.864496E+09 0.00 0.96
September 0.283777E+09 0.481217E+09 0.00 9309301.76 42759968.85 0.00 0.128690E+10 0.00 0.94
October 0.815091E+09 0.142129E+09 0.00 15019851.30 1272246.66 0.00 0.483118E+10 0.00 1.44
November 0.121960E+10 0.00 0.00 15431732.78 0.00 0.00 0.737925E+10 0.00 1.33
December 0.156266E+10 0.00 0.00 10006510.51 0.00 8086915.45 0.732779E+10 0.00 0.88
                   
Annual Sum or Average 0.106440E+11 0.426231E+10 0.00 0.112018E+09 0.596502E+09 8086915.45 0.452342E+11 0.00 1.00
Minimum of Months 79080316.03 0.00 0.00 1662933.07 0.00 0.00 95324551.00 0.00 0.73
Maximum of Months 0.156266E+10 0.188075E+10 0.00 15431732.78 0.352433E+09 8086915.45 0.737925E+10 0.00 1.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.210494E+10 0.00 0.00 3409780.33 0.00 0.00 0.291669E+10 0.00 0.80
February 0.100862E+10 0.00 0.00 6180216.77 0.00 0.00 0.399600E+10 0.00 1.10
March 0.554672E+09 0.00 0.00 13251156.93 0.00 0.00 0.654567E+10 0.00 1.83
April 0.545053E+09 98062324.65 0.00 17182660.27 826919.62 0.00 0.516358E+10 0.00 2.13
May 0.345090E+09 0.251281E+09 0.00 9395939.00 21852517.46 0.00 0.172448E+10 0.00 1.31
June 0.210791E+09 0.961462E+09 0.00 7822667.37 25369353.02 0.00 0.857956E+09 0.00 1.33
July 31796676.86 0.252321E+10 0.00 3002550.08 0.160257E+09 0.00 0.181311E+09 0.00 1.37
August 0.117756E+09 0.937694E+09 0.00 11845246.06 14448156.13 0.00 0.136478E+10 0.00 1.79
September 0.241945E+09 0.362540E+09 0.00 8577453.37 35441477.05 0.00 0.120995E+10 0.00 1.25
October 0.428312E+09 0.101651E+09 0.00 12081353.09 1374292.40 0.00 0.415438E+10 0.00 1.72
November 0.677384E+09 0.00 0.00 11001865.89 0.00 0.00 0.581079E+10 0.00 1.50
December 0.756215E+09 0.00 0.00 8764070.42 0.00 0.00 0.620148E+10 0.00 1.07
                   
Annual Sum or Average 0.702257E+10 0.523590E+10 0.00 0.112515E+09 0.259570E+09 0.00 0.401271E+11 0.00 1.44
Minimum of Months 31796676.86 0.00 0.00 3002550.08 0.00 0.00 0.181311E+09 0.00 0.80
Maximum of Months 0.210494E+10 0.252321E+10 0.00 17182660.27 0.160257E+09 0.00 0.654567E+10 0.00 2.13



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.312188E+11 0.00 0.00 0.00 0.00 0.592908E+10 0.00 0.00 0.37
February 0.277472E+11 0.00 0.00 1327298.43 0.00 0.276285E+10 0.103521E+10 0.00 0.42
March 0.273703E+11 0.00 0.00 10697422.42 0.00 0.786749E+09 0.565796E+10 0.00 0.51
April 0.115143E+11 0.371014E+09 0.00 38896920.84 0.150188E+09 0.00 0.108050E+11 0.00 0.55
May 0.442946E+10 0.191817E+10 0.00 57314590.21 0.274941E+09 0.00 0.995967E+10 0.00 0.63
June 0.169284E+10 0.842569E+10 0.00 48856004.36 0.416117E+09 0.00 0.544985E+10 0.00 0.67
July 0.315894E+09 0.175329E+11 0.00 13561761.18 0.160966E+10 0.00 0.757578E+09 0.00 0.61
August 0.101039E+10 0.565993E+10 0.00 48531237.54 0.700343E+09 0.00 0.612441E+10 0.00 0.64
September 0.340410E+10 0.293218E+10 0.00 39907819.52 0.411900E+09 0.00 0.534807E+10 0.00 0.54
October 0.136157E+11 0.714654E+09 0.00 28878122.86 59124269.90 0.00 0.101233E+11 0.00 0.57
November 0.294641E+11 0.00 0.00 3291824.98 0.00 0.164931E+10 0.211530E+10 0.00 0.46
December 0.294496E+11 0.00 0.00 0.00 0.00 0.870959E+10 0.00 0.00 0.35
                   
Annual Sum or Average 0.181233E+12 0.375545E+11 0.00 0.291263E+09 0.362227E+10 0.198376E+11 0.573764E+11 0.00 0.53
Minimum of Months 0.315894E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.35
Maximum of Months 0.312188E+11 0.175329E+11 0.00 57314590.21 0.160966E+10 0.870959E+10 0.108050E+11 0.00 0.67



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.264752E+11 0.00 0.00 1705706.22 0.00 0.294485E+10 0.228653E+10 0.00 0.49
February 0.179723E+11 0.00 0.00 12353653.89 0.00 0.869453E+09 0.981419E+10 0.00 0.60
March 0.150800E+11 0.00 0.00 37650359.44 0.00 0.292191E+09 0.220604E+11 0.00 0.87
April 0.509174E+10 0.433653E+09 0.00 76772209.69 63540028.87 0.00 0.256662E+11 0.00 1.13
May 0.269130E+10 0.189509E+10 0.00 79333210.89 0.198773E+09 0.00 0.167055E+11 0.00 1.19
June 0.126428E+10 0.725458E+10 0.00 55341701.92 0.322615E+09 0.00 0.608864E+10 0.00 1.05
July 0.266613E+09 0.161762E+11 0.00 14620239.95 0.127078E+10 0.00 0.828927E+09 0.00 0.90
August 0.887095E+09 0.580534E+10 0.00 50221223.66 0.531932E+09 0.00 0.638214E+10 0.00 1.02
September 0.220161E+10 0.340599E+10 0.00 58365031.36 0.257448E+09 0.00 0.918950E+10 0.00 1.03
October 0.885388E+10 0.594236E+09 0.00 46431172.40 43790737.75 0.00 0.179168E+11 0.00 0.95
November 0.195383E+11 0.00 0.00 17363740.59 0.00 0.674595E+09 0.106720E+11 0.00 0.67
December 0.275142E+11 0.00 0.00 481913.79 0.00 0.405129E+10 0.888183E+09 0.00 0.46
                   
Annual Sum or Average 0.127836E+12 0.355651E+11 0.00 0.450640E+09 0.268888E+10 0.883239E+10 0.128499E+12 0.00 0.87
Minimum of Months 0.266613E+09 0.00 0.00 481913.79 0.00 0.00 0.828927E+09 0.00 0.46
Maximum of Months 0.275142E+11 0.161762E+11 0.00 79333210.89 0.127078E+10 0.405129E+10 0.256662E+11 0.00 1.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.150213E+11 0.00 0.00 87642342.26 0.00 0.745437E+09 0.602379E+11 0.00 0.82
February 0.128555E+11 0.00 0.00 87223326.02 0.00 0.524357E+09 0.489909E+11 0.00 0.91
March 0.130426E+11 0.00 0.00 89240799.21 0.00 0.201255E+09 0.471960E+11 0.00 1.02
April 0.794125E+10 0.838635E+09 0.00 76911227.83 57701415.72 0.00 0.229701E+11 0.00 0.82
May 0.458910E+10 0.229248E+10 0.00 63531601.29 0.266125E+09 0.00 0.106836E+11 0.00 0.68
June 0.171823E+10 0.838349E+10 0.00 46051624.30 0.421258E+09 0.00 0.497390E+10 0.00 0.64
July 0.314558E+09 0.176957E+11 0.00 13491133.46 0.159492E+10 0.00 0.696654E+09 0.00 0.60
August 0.937954E+09 0.729822E+10 0.00 61267261.24 0.585781E+09 0.00 0.716155E+10 0.00 0.76
September 0.206923E+10 0.548470E+10 0.00 81780150.72 0.271067E+09 0.00 0.106897E+11 0.00 0.86
October 0.695994E+10 0.161271E+10 0.00 0.134898E+09 20278646.41 0.00 0.408450E+11 0.00 1.27
November 0.115026E+11 0.00 0.00 0.143898E+09 0.00 0.278507E+09 0.620908E+11 0.00 1.18
December 0.161502E+11 0.00 0.00 79310865.50 0.00 0.182528E+10 0.569102E+11 0.00 0.75
                   
Annual Sum or Average 0.931025E+11 0.436059E+11 0.00 0.965247E+09 0.321713E+10 0.357483E+10 0.373446E+12 0.00 0.86
Minimum of Months 0.314558E+09 0.00 0.00 13491133.46 0.00 0.00 0.696654E+09 0.00 0.60
Maximum of Months 0.161502E+11 0.176957E+11 0.00 0.143898E+09 0.159492E+10 0.182528E+10 0.620908E+11 0.00 1.27



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.268774E+11 0.00 0.00 8663689.46 0.00 0.216147E+10 0.670523E+10 0.00 0.56
February 0.220046E+11 0.00 0.00 12767030.28 0.00 0.881373E+09 0.846611E+10 0.00 0.67
March 0.182728E+11 0.00 0.00 38817897.00 0.00 0.210254E+09 0.194352E+11 0.00 0.97
April 0.648242E+10 0.679925E+09 0.00 67986401.56 20133949.72 0.00 0.193622E+11 0.00 1.05
May 0.332392E+10 0.247770E+10 0.00 64768862.65 0.113644E+09 0.00 0.104953E+11 0.00 1.01
June 0.107349E+10 0.943732E+10 0.00 47560330.44 0.171702E+09 0.00 0.530510E+10 0.00 0.99
July 0.219691E+09 0.176607E+11 0.00 13699548.90 0.868315E+09 0.00 0.716908E+09 0.00 0.89
August 0.766559E+09 0.643106E+10 0.00 53647210.37 0.280809E+09 0.00 0.587531E+10 0.00 1.00
September 0.208959E+10 0.338816E+10 0.00 55145435.25 0.213568E+09 0.00 0.715515E+10 0.00 0.92
October 0.828990E+10 0.889568E+09 0.00 53472051.52 39075157.26 0.00 0.176654E+11 0.00 1.03
November 0.214471E+11 0.00 0.00 23600771.06 0.00 0.368879E+09 0.130544E+11 0.00 0.80
December 0.273949E+11 0.00 0.00 6832575.95 0.00 0.287810E+10 0.583576E+10 0.00 0.52
                   
Annual Sum or Average 0.138242E+12 0.409644E+11 0.00 0.446962E+09 0.170725E+10 0.650007E+10 0.120072E+12 0.00 0.87
Minimum of Months 0.219691E+09 0.00 0.00 6832575.95 0.00 0.00 0.716908E+09 0.00 0.52
Maximum of Months 0.273949E+11 0.176607E+11 0.00 67986401.56 0.868315E+09 0.287810E+10 0.194352E+11 0.00 1.05



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.169131E+10 0.00 0.00 0.00 0.00 0.166478E+10 0.00 0.00 0.36
February 0.191526E+10 0.00 0.00 21494.49 0.00 0.946780E+09 48476474.89 0.00 0.41
March 0.244008E+10 0.00 0.00 591871.28 0.00 0.458337E+09 0.280611E+09 0.00 0.50
April 0.118079E+10 21521445.76 0.00 3826512.20 10320395.36 31693910.91 0.878606E+09 0.00 0.55
May 0.473155E+09 0.114140E+09 0.00 6890851.53 29918106.84 0.00 0.866122E+09 0.00 0.63
June 0.162784E+09 0.646030E+09 0.00 6115745.78 33956428.63 0.00 0.545130E+09 0.00 0.66
July 35314399.13 0.161086E+10 0.00 1748589.69 0.166145E+09 0.00 73058841.09 0.00 0.61
August 0.136341E+09 0.442386E+09 0.00 5731849.57 73062668.32 0.00 0.591183E+09 0.00 0.63
September 0.370121E+09 0.208062E+09 0.00 4831760.99 40872910.94 0.00 0.441945E+09 0.00 0.53
October 0.145179E+10 49545169.27 0.00 2268419.39 10480333.81 13953337.79 0.688113E+09 0.00 0.55
November 0.217746E+10 0.00 0.00 172565.68 410188.51 0.710323E+09 0.104076E+09 0.00 0.45
December 0.134023E+10 0.00 0.00 0.00 0.00 0.208980E+10 0.00 0.00 0.35
                   
Annual Sum or Average 0.133746E+11 0.309254E+10 0.00 32199660.62 0.365166E+09 0.591567E+10 0.451732E+10 0.00 0.52
Minimum of Months 35314399.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.35
Maximum of Months 0.244008E+10 0.161086E+10 0.00 6890851.53 0.166145E+09 0.208980E+10 0.878606E+09 0.00 0.66



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.207249E+10 0.00 0.00 1705.90 0.00 0.719546E+09 10549235.32 0.00 0.47
February 0.182134E+10 0.00 0.00 495474.55 0.00 0.292624E+09 0.384193E+09 0.00 0.56
March 0.137353E+10 0.00 0.00 2762999.02 0.00 0.182805E+09 0.165652E+10 0.00 0.80
April 0.481424E+09 26476068.02 0.00 7438275.97 3923660.51 5072200.08 0.228371E+10 0.00 1.11
May 0.238651E+09 0.118956E+09 0.00 9374220.93 21606563.10 0.00 0.159130E+10 0.00 1.21
June 0.126426E+09 0.567231E+09 0.00 6729071.22 25021349.90 0.00 0.613984E+09 0.00 1.04
July 28490036.83 0.151521E+10 0.00 1879525.92 0.132489E+09 0.00 79707228.47 0.00 0.91
August 0.106245E+09 0.476763E+09 0.00 6240418.23 50608779.18 0.00 0.638491E+09 0.00 1.03
September 0.218182E+09 0.274543E+09 0.00 6922841.87 23242062.05 0.00 0.811253E+09 0.00 1.03
October 0.827600E+09 42725421.95 0.00 4173815.88 7260511.87 7877102.14 0.153969E+10 0.00 0.93
November 0.178450E+10 0.00 0.00 947222.82 350615.32 0.324627E+09 0.532174E+09 0.00 0.63
December 0.188726E+10 0.00 0.00 0.00 0.00 0.956189E+09 0.00 0.00 0.45
                   
Annual Sum or Average 0.109661E+11 0.302191E+10 0.00 46965572.31 0.264502E+09 0.248874E+10 0.101416E+11 0.00 0.85
Minimum of Months 28490036.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
Maximum of Months 0.207249E+10 0.151521E+10 0.00 9374220.93 0.132489E+09 0.956189E+09 0.228371E+10 0.00 1.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.138207E+10 0.00 0.00 5334428.50 0.00 0.471763E+09 0.374371E+10 0.00 0.64
February 0.120109E+10 0.00 0.00 5528285.01 0.00 0.273617E+09 0.339762E+10 0.00 0.74
March 0.137787E+10 0.00 0.00 6750031.36 0.00 0.167784E+09 0.378673E+10 0.00 0.91
April 0.807455E+09 48281121.38 0.00 7821292.98 3632845.57 18884215.40 0.209160E+10 0.00 0.81
May 0.463531E+09 0.137881E+09 0.00 7714019.25 28122984.15 0.00 0.993698E+09 0.00 0.68
June 0.171523E+09 0.636698E+09 0.00 5839331.61 36477909.79 0.00 0.508212E+09 0.00 0.64
July 35442490.99 0.160695E+10 0.00 1777132.97 0.170697E+09 0.00 69968688.17 0.00 0.60
August 0.100093E+09 0.562139E+09 0.00 7405008.08 57445038.96 0.00 0.741918E+09 0.00 0.75
September 0.196717E+09 0.384895E+09 0.00 10247694.47 23100893.28 0.00 0.102921E+10 0.00 0.85
October 0.676497E+09 0.113944E+09 0.00 12220054.88 4435551.01 0.00 0.385464E+10 0.00 1.26
November 0.109610E+10 0.00 0.00 9868670.60 413822.00 0.261201E+09 0.487859E+10 0.00 1.06
December 0.144594E+10 0.00 0.00 4514836.21 0.00 0.568857E+09 0.323788E+10 0.00 0.56
                   
Annual Sum or Average 0.895432E+10 0.349078E+10 0.00 85020785.91 0.324326E+09 0.176211E+10 0.283338E+11 0.00 0.79
Minimum of Months 35442490.99 0.00 0.00 1777132.97 0.00 0.00 69968688.17 0.00 0.56
Maximum of Months 0.144594E+10 0.160695E+10 0.00 12220054.88 0.170697E+09 0.568857E+09 0.487859E+10 0.00 1.26



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.209171E+10 0.00 0.00 447529.06 0.00 0.751941E+09 0.406602E+09 0.00 0.55
February 0.200395E+10 0.00 0.00 793836.33 0.00 0.403500E+09 0.539950E+09 0.00 0.66
March 0.200595E+10 0.00 0.00 2915391.98 0.00 0.153228E+09 0.154669E+10 0.00 0.96
April 0.820848E+09 36993459.91 0.00 6983405.96 2243412.71 0.00 0.172129E+10 0.00 1.07
May 0.333059E+09 0.149061E+09 0.00 7933600.58 14737853.12 0.00 0.101388E+10 0.00 1.01
June 0.128237E+09 0.685377E+09 0.00 6000622.92 19027196.86 0.00 0.519587E+09 0.00 0.96
July 26280749.72 0.155719E+10 0.00 1844154.36 0.110550E+09 0.00 73078250.12 0.00 0.88
August 84653845.34 0.484118E+09 0.00 6325623.08 40872847.15 0.00 0.612333E+09 0.00 0.99
September 0.230464E+09 0.234763E+09 0.00 6767543.96 23772918.65 0.00 0.669979E+09 0.00 0.92
October 0.103787E+10 62111437.89 0.00 4581086.80 8350524.12 0.00 0.146818E+10 0.00 1.04
November 0.199195E+10 0.00 0.00 1690374.30 402477.33 0.309051E+09 0.962453E+09 0.00 0.79
December 0.205112E+10 0.00 0.00 244524.25 0.00 0.909514E+09 0.289894E+09 0.00 0.52
                   
Annual Sum or Average 0.128061E+11 0.320962E+10 0.00 46527693.58 0.219957E+09 0.252723E+10 0.982391E+10 0.00 0.86
Minimum of Months 26280749.72 0.00 0.00 244524.25 0.00 0.00 73078250.12 0.00 0.52
Maximum of Months 0.209171E+10 0.155719E+10 0.00 7933600.58 0.110550E+09 0.909514E+09 0.172129E+10 0.00 1.07



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 3417371.52 0.00 0.00 0.447067E+09 0.00 0.28
February 0.00 0.00 0.00 7466838.30 0.00 0.00 0.359216E+09 0.00 0.29
March 0.00 0.00 0.00 13831386.51 0.00 0.00 0.372022E+09 0.00 0.31
April 0.00 1427572.10 0.00 15650124.58 0.00 0.00 0.181870E+09 0.00 0.29
May 0.00 30469574.79 0.00 2668988.67 0.00 0.00 95080802.95 0.00 0.29
June 0.00 93224351.15 0.00 1093277.74 0.00 0.00 11463192.39 0.00 0.30
July 0.00 0.299682E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.207760E+09 0.00 321253.93 0.00 0.00 593013.60 0.00 0.30
September 0.00 0.118766E+09 0.00 1051776.15 0.00 0.00 25952175.42 0.00 0.29
October 0.00 41045649.91 0.00 5966324.00 0.00 0.00 0.137862E+09 0.00 0.28
November 0.00 0.00 0.00 12374683.55 0.00 0.00 0.320763E+09 0.00 0.28
December 0.00 0.00 0.00 17271689.50 0.00 0.00 0.455886E+09 0.00 0.28
                   
Annual Sum or Average 0.00 0.792375E+09 0.00 81113714.44 0.00 0.00 0.240778E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.00 0.299682E+09 0.00 17271689.50 0.00 0.00 0.455886E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 22304319.70 0.00 0.00 0.448997E+10 0.00 0.28
February 0.00 0.00 0.00 63486020.18 0.00 0.00 0.360457E+10 0.00 0.29
March 0.00 0.00 0.00 0.126210E+09 0.00 0.00 0.373107E+10 0.00 0.31
April 0.00 14126933.41 0.00 0.148125E+09 0.00 0.00 0.182526E+10 0.00 0.29
May 0.00 0.300150E+09 0.00 24599816.64 0.00 0.00 0.951772E+09 0.00 0.29
June 0.00 0.928406E+09 0.00 10336982.62 0.00 0.00 0.114421E+09 0.00 0.30
July 0.00 0.299050E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.206866E+10 0.00 3084734.42 0.00 0.00 6000607.02 0.00 0.30
September 0.00 0.116718E+10 0.00 9555836.14 0.00 0.00 0.262505E+09 0.00 0.29
October 0.00 0.405652E+09 0.00 54404913.04 0.00 0.00 0.138643E+10 0.00 0.28
November 0.00 0.00 0.00 0.110993E+09 0.00 0.00 0.322046E+10 0.00 0.28
December 0.00 0.00 0.00 0.153257E+09 0.00 0.00 0.457576E+10 0.00 0.28
                   
Annual Sum or Average 0.00 0.787468E+10 0.00 0.726357E+09 0.00 0.00 0.241682E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.00 0.299050E+10 0.00 0.153257E+09 0.00 0.00 0.457576E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.120819E+09 0.00 0.00 1085854.22 0.00 0.00 0.330002E+09 0.00 0.28
February 0.00 0.00 0.00 5359988.36 0.00 0.00 0.361870E+09 0.00 0.29
March 0.00 0.00 0.00 11850407.03 0.00 0.00 0.373966E+09 0.00 0.31
April 0.00 1458621.48 0.00 14629175.24 0.00 0.00 0.182726E+09 0.00 0.29
May 0.00 30144798.09 0.00 2456833.98 0.00 0.00 95216719.22 0.00 0.29
June 0.00 92971970.67 0.00 1032291.91 0.00 0.00 11466025.18 0.00 0.30
July 0.00 0.299163E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.207224E+09 0.00 306548.31 0.00 0.00 600638.02 0.00 0.30
September 0.00 0.117097E+09 0.00 921962.14 0.00 0.00 26384425.36 0.00 0.29
October 0.00 40458030.19 0.00 5149839.78 0.00 0.00 0.139487E+09 0.00 0.28
November 0.00 0.00 0.00 10165690.85 0.00 0.00 0.323233E+09 0.00 0.28
December 0.00 0.00 0.00 13978155.45 0.00 0.00 0.459042E+09 0.00 0.28
                   
Annual Sum or Average 0.120819E+09 0.788517E+09 0.00 66936747.28 0.00 0.00 0.230399E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.120819E+09 0.299163E+09 0.00 14629175.24 0.00 0.00 0.459042E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:06:30

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.392761E+12 0.404853E+10 0.00 0.178281E+13 0.113713E+12
February 0.405781E+12 0.324734E+10 0.00 0.149853E+13 0.256100E+12
March 0.587600E+12 0.370047E+10 0.00 0.176726E+13 0.493931E+12
April 0.612772E+12 0.207460E+10 0.00 0.125148E+13 0.100935E+13
May 0.644857E+12 0.127271E+10 0.00 0.875372E+12 0.127622E+13
June 0.632426E+12 -90030935.6 0.00 0.187833E+12 0.188636E+13
July 0.626439E+12 -764777293.4 0.00 -0.373837E+12 0.213287E+13
August 0.586622E+12 -43072110.3 0.00 0.132236E+12 0.197609E+13
September 0.532954E+12 0.413571E+09 0.00 0.439017E+12 0.139089E+13
October 0.492385E+12 0.174838E+10 0.00 0.141410E+13 0.853066E+12
November 0.397133E+12 0.341555E+10 0.00 0.182442E+13 0.418879E+12
December 0.336061E+12 0.342361E+10 0.00 0.173592E+13 0.329102E+12
           
Annual Sum or Average 0.624779E+13 0.224469E+11 0.00 0.125351E+14 0.121366E+14
Minimum of Months 0.336061E+12 -764777293.4 0.00 -0.373837E+12 0.113713E+12
Maximum of Months 0.644857E+12 0.404853E+10 0.00 0.182442E+13 0.213287E+13