Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:06

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610

Simulation Timestamp: 2023-10-16 09:06:40


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 34559.09 746.09 746.09
Net Site Energy 34559.09 746.09 746.09
Total Source Energy 83459.85 1801.80 1801.80
Net Source Energy 83459.85 1801.80 1801.80


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 4368.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 507.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7145.61 0.00 0.00
Interior Lighting 2073.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 357.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 3108.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1070.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 229.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 98.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1049.60
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 58.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 865.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 22179.67 5233.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7145.61 0.00 3329.77
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 4368.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 507.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7145.61 0.00 0.00
Interior Lighting LightsWired 2073.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 357.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5334.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 54.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ComputerHVAC 1199.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 1070.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 229.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 98.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1049.60
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 58.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 865.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 4368.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 507.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7145.61 0.00 0.00
Interior Lighting GENERAL 2073.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 357.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 3108.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 1070.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 229.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 98.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1049.60
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 58.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 865.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 52.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 41.13 112.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 154.26 0.00 0.07
Other 385.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 478.83 112.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 154.26 0.00 0.07


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 52.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 41.13 112.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 154.26 0.00 0.07
Other 385.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 478.83 112.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 154.26 0.00 0.07


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 22179.672 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 22179.672 100.00
     
Total On-Site and Utility Electric Sources 22179.672 100.00
Total Electricity End Uses 22179.672 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 1.65 0.04
Air to Air Heat Recovery for Heating 3944.51 99.96
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 3946.17 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 3329.77 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 3329.77 100.00
Total Water End Uses 3329.77 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 232.83
Time Setpoint Not Met During Occupied Cooling 67.67
Time Not Comfortable Based on Simple ASHRAE 55-2004 5943.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EnergyConsumptionDistrictHeatingCoolingMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:06
RunPeriod RUNPERIOD 1
Weather File Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Latitude [deg] 64.82
Longitude [deg] -147.8
Elevation [m] 133.00
Time Zone -9.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 5.8895 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 5.8895 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 5.8895 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 5.8895 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 8.8011 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 8.8011 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 8.8011 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 5.8895 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 5.9168 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 5.9168 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 5.8895 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 5.8895 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 5.8895 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 5.8895 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 5.8895 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 5.8895 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 5.8895 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 5.8895 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 5.8895 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 5.8895 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 5.8895 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 5.8895 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 5.8895 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 5.8895 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 5.8895 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 5.8895 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 8.8011 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 8.8011 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 8.8011 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 5.8895 18.58 484.4232  
Total 46320.38             5.9168 9.29 17.8789  
Conditioned Total 46320.38             5.9168 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 1.8190 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] District Heating [W] Water [m3/s]
Time of Peak 11-AUG-15:39 27-FEB-07:10 - - - - - - - - 28-AUG-15:00 31-MAY-23:40 21-JUL-15:50
Heating 0.00 2476903.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.36 0.00
Cooling 181652.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370149.39 0.00 0.00
Interior Lighting 171235.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 778371.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 143548.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 181084.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 44500.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 14655.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 6524.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 31388.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1521573.26 2508292.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370149.39 13.36 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] District Heating [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.36 0.00
  Boiler 0.00 2476903.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 181652.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370149.39 0.00 0.00
Interior Lighting LightsWired 171235.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 3372.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ComputerHVAC 60741.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 263.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 181084.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 44500.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 14655.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 6524.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 31388.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 4735.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.01
Cooling 1605.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7543.38 0.00
Interior Lighting 6565.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1133.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 46480.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 9843.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 3388.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 728.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 311.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 185.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 938.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 70243.02 5673.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7543.38 0.01


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 102.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 34.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 162.85 0.00
Interior Lighting 141.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 24.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 212.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 73.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 15.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 6.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 4.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 20.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1516.46 122.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 162.85 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 102.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 34.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 162.85 0.00
Interior Lighting 141.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 24.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 212.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 73.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 15.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 6.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 4.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 20.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1516.46 122.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 162.85 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 4.93
DATACENTER_BOT_ZN_6 DIRECT AIR 0.495152
DATACENTER_MID_ZN_6 DIRECT AIR 4.75
DATACENTER_TOP_ZN_6 DIRECT AIR 0.479504
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 5.35 0.355332 0.351000 1.88 0.947551 0.500000 0.001072 0.000227 1.88 12.80 0.008000
CORE_MID VAV BOX COMPONENT 50.15 0.379268 0.367000 18.41 1.00 0.500000 0.001005 0.004246 18.41 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 4.93 0.385442 0.378000 1.87 1.00 0.500000 0.000988 0.001031 3.57 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.854413 0.279514 0.276000 0.235818 0.745372 0.500000 0.001363 0.000160 0.552065 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.12 0.138028 0.200000 0.223006 0.368074 0.500000 0.002760 0.000110 0.379962 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.70 0.140454 0.200000 0.340076 0.374545 0.500000 0.002713 0.000175 0.605676 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.34 0.115005 0.200000 0.267650 0.306679 0.500000 0.003313 0.000085 0.294928 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 7.95 0.300391 0.290000 2.31 0.801042 0.500000 0.001268 0.002133 7.39 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 11.76 0.130883 0.200000 2.35 0.349022 0.500000 0.002911 0.001415 4.90 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 17.63 0.135491 0.200000 3.53 0.361309 0.500000 0.002812 0.002121 7.35 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 11.90 0.129361 0.200000 2.38 0.344963 0.500000 0.002945 0.001350 4.67 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.04 0.229277 0.288000 0.299988 0.611405 0.500000 0.001662 0.000301 1.04 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.17 0.131149 0.200000 0.234703 0.349729 0.500000 0.002905 0.000198 0.686294 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.84 0.130041 0.200000 0.367308 0.346776 0.500000 0.002930 0.000299 1.04 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.24 0.124146 0.200000 0.247942 0.331056 0.500000 0.003069 0.000194 0.672082 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 25919.81 0.000227 543.52
CORE_MID VAV BOX REHEAT COIL 485386.65 0.004246 11736.87
CORE_TOP VAV BOX REHEAT COIL 117890.62 0.001031 3110.92
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 18232.25 0.000160 480.97
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 12546.38 0.000110 330.95
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 19998.58 0.000175 527.52
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 9745.39 0.000085 257.15
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 243796.19 0.002133 6429.55
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 161779.42 0.001415 4266.45
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 242427.91 0.002121 6393.50
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 154287.12 0.001350 4069.02
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 34360.18 0.000301 905.95
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 22638.20 0.000198 596.88
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 34173.68 0.000299 901.03
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 22169.86 0.000194 584.53
VAV_BOT WITH REHEAT HEATING COIL 164406.21 0.001438 2132.27
VAV_MID WITH REHEAT HEATING COIL 1599918.92 0.013997 20456.88
VAV_TOP WITH REHEAT HEATING COIL 165266.01 0.001446 2122.49
CAV_BAS HEATING COIL 294985.31 0.002581 6017.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:IdealLoadsAirSystem

Design Size Maximum Heating Air Flow Rate [m3/s] Design Size Maximum Cooling Air Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT 0.338402 21.63
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 5.18 2.95 10.36 2.95 8.79 8.79 0.300000 0.334911 8.79
VAV_MID WITH REHEAT 49.69 28.97 99.38 37.30 81.85 81.85 0.300000 0.455720 81.85
VAV_TOP WITH REHEAT 5.11 3.02 10.23 7.00 8.57 8.57 0.300000 0.816983 8.57
CAV_BAS 4.93 4.93 4.93 4.93 4.93 4.93 1.00 1.00 4.93
AIRLOOP DATACENTER BOT 0.495152 0.495152 0.495152 0.495152 0.495152 0.495152 1.00 1.00 0.495152
AIRLOOP DATACENTER MID 4.75 4.75 4.75 4.75 4.75 4.75 1.00 1.00 4.75
AIRLOOP DATACENTER TOP 0.479504 0.479504 0.479504 0.479504 0.479504 0.479504 1.00 1.00 0.479504
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 8.79  
VAV_MID WITH REHEAT_OA_CONTROLLER 81.85  
VAV_TOP WITH REHEAT_OA_CONTROLLER 8.57  
CAV_BAS_OA_CONTROLLER 4.93  
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.495152 0.015633
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.75 0.156328
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.479504 0.015633
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT OA HEAT RECOVERY 2.54
VAV_MID WITH REHEAT OA HEAT RECOVERY 25.38
VAV_TOP WITH REHEAT OA HEAT RECOVERY 2.54
CAV_BAS OA HEAT RECOVERY 1.20
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 25.01 6.67 10.91 0.007262 0.007000 156568.91 0.006661 8.79
VAV_MID WITH REHEAT COOLING COIL 25.11 6.67 10.91 0.007276 0.007000 1470729.92 0.062568 81.85
VAV_TOP WITH REHEAT COOLING COIL 25.01 6.67 10.91 0.007262 0.007000 152639.27 0.006494 8.57
CAV_BAS COOLING COIL 24.79 6.67 11.40 0.007416 0.007000 85946.59 0.003656 4.93
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 8.79
VAV_MID WITH REHEAT FAN 81.85
VAV_TOP WITH REHEAT FAN 8.57
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.006661 0.000071
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.001438  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.062568 0.000008
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.013997  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.006494 0.000073
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.001446  
CAV_BAS_COOLC_CONTROLLER 0.003656 0.000130
CAV_BAS_HEATC_CONTROLLER 0.002581  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 4.93
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BOT COOLING COIL 0.495152 9827.07 6297.93 0.000241
AIRLOOP DATACENTER MID COOLING COIL 4.75 94202.48 60365.04 0.002307
AIRLOOP DATACENTER TOP COOLING COIL 0.479504 9517.43 6098.92 0.000233
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.495152 0.495152 0.495152 0.495152 9827.07 9827.07 1525.12 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.75 4.75 4.75 4.75 94202.48 94202.48 15251.23 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.479504 0.479504 0.479504 0.479504 9517.43 9517.43 1525.12 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BOT SUPPLY FAN 0.495152
AIRLOOP DATACENTER MID SUPPLY FAN 4.75
AIRLOOP DATACENTER TOP SUPPLY FAN 0.479504
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BOT HEATING COIL 0.495152 9827.07 0.000241
AIRLOOP DATACENTER MID HEATING COIL 4.75 94202.48 0.002307
AIRLOOP DATACENTER TOP HEATING COIL 0.479504 9517.43 0.000233
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 1525.12
AIRLOOP DATACENTER MID_SUPPHEATCOIL 15251.23
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 1525.12
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.079379 16195.13  
HEATSYS1 PUMP 0.033506 9990.60 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.079379 9.53
HEATSYS1 0.033506 4.02
COOLSYS1_SUPPLY 0.079379 9.53
SINGLE WATER PLANT LOOP 0.002781 0.333691
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.079379 0.079379 333193.70 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 3829928.71 3829928.71 0.033506
CENTRAL BOILER 114543.40 114543.40 0.002781
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.079379 11212.43
PLANT CIRC PUMP 0.002781 702.21
SWHSYS1 PUMP 0.000440 5.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.079379 0.039943 939948.06 945669.18 0.047943
COOLSYS1 CHILLER2 0.079379 0.039943 939948.06 945669.18 0.047943
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.002781 35644.39 19523.09 17822.20 1996.20 5783.98
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.095887 11.51
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.095887 28593.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 36.98 1123406.22 7.40 140425.78
TOWERWATERSYS COOLTOWER 2 36.98 1123406.22 7.40 140425.78
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 45
WSHPPLANT OPERATION SCHEME 0.048607
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 -3.10 -17.70 -19.30 -17.60 -15.40 -10.30 0.70 10.60 16.00 16.90 14.20 6.70


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 64.82 -147.85 -9.00 133.00 99737 1.1854


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA -1.53 36.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 105.88 86.92 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 105.88 86.92 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 5.889 4.842 0.000 0.000 0.000 0.000 10.731 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 8.801 215.299 0.000 0.000 0.000 0.000 224.100 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 8.801 215.299 0.000 0.000 0.000 0.000 224.100 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 8.801 215.299 0.000 0.000 0.000 0.000 224.100 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 5.889 484.423 0.000 0.000 0.000 0.000 490.313 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 16369.361 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16369.361
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 14700.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14700.837
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 14700.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14700.837
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 14700.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14700.837
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 1845.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.837
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 1845.877 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.877
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 1845.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.837
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 1845.877 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.877
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 1845.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.837
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 1845.877 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.877
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 4615.459 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4615.459
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 318.624 8.801 163.514 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 318.624
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 318.624 8.801 163.514 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 318.624
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 318.624 8.801 163.514 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 318.624


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.1625 0.900 0.900 0.700 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 0.8258 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 0.7568 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.136 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.2699 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.2699 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.2699 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.2699 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.2699 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.2699 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 6.093
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.044
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 1.154
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.7130
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 3.628
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 3.628
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 3.628
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 3.628
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 3.628
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 3.628
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.63083111E-06 0.74112372E-09 -0.38647046E-05 0.15329585E-16
47 2 0.78415922 0.99752939E-03 1.0633801 -0.74093433E-06
48 1 -22.010056 0.66447931E-01 -6.3131541 0.20386814
49 0 21.355302 0.61958938E-01 5.3791822  
50 9 -0.15599613E-14 0.30603975E-16 -0.15457477E-09 0.41291095E-16
51 8 0.22556852E-07 0.11178367E-12 0.38492375E-03 -0.25647914E-09
52 7 -0.12454226E-01 0.57615883E-08 -0.23391987E-01 0.14160910E-03
53 6 0.41112889 0.20017317E-05 0.47700961 -0.48158773E-02
54 5 -5.2469534 0.74656960E-04 -4.4790264 0.63883058E-01
55 4 33.252272 0.61009338E-03 21.587931 -0.42543446
56 3 -111.75687 0.13284528E-02 -55.915802 1.5228611
57 2 197.65712 0.74665727E-03 78.142485 -2.9090693
58 1 -171.35881 0.79649450E-04 -55.332598 2.7489926
59 0 57.057407 0.45301765E-06 15.545850  
60 9 -0.41232255E-14 0.25174500E-16 -0.15779363E-09 0.79825359E-16
61 8 0.23007895E-07 0.10274112E-12 0.38959709E-03 -0.26160767E-09
62 7 -0.12593457E-01 0.52712401E-08 -0.23592386E-01 0.14319220E-03
63 6 0.41491174 0.18279492E-05 0.48022593 -0.48604681E-02
64 5 -5.2838657 0.68065824E-04 -4.5037053 0.64340758E-01
65 4 33.415521 0.55542031E-03 21.684341 -0.42760200
66 3 -112.10413 0.12078296E-02 -56.106379 1.5278783
67 2 198.00122 0.67807137E-03 78.317366 -2.9145338
68 1 -171.48588 0.72255287E-04 -55.383628 2.7512197
69 0 57.057407 0.41044453E-06 15.537566  
70 9 0.14724012E-14 0.43042003E-16 -0.13998939E-09 -0.39549036E-17
71 8 0.20504295E-07 0.15124232E-12 0.36324376E-03 -0.23314089E-09
72 7 -0.11806914E-01 0.79726262E-08 -0.22459843E-01 0.13424890E-03
73 6 0.39353963 0.27950707E-05 0.46201977 -0.46085424E-02
74 5 -5.0752962 0.10505945E-03 -4.3638537 0.61754592E-01
75 4 32.492944 0.86458417E-03 21.137652 -0.41535275
76 3 -110.14119 0.18943840E-02 -55.025553 1.4995189
77 2 196.05567 0.10706719E-02 77.326175 -2.8836384
78 1 -170.76722 0.11480160E-03 -55.095566 2.7386241
79 0 57.057407 0.65670313E-06 15.585276  
80 7 -0.15524988E-08 -0.27599222E-15 0.12191615E-13 -0.17961055E-15
81 6 0.75408527E-05 0.51820635E-08 0.31843202E-02 -0.26712746E-04
82 5 -0.54428247E-03 0.30714476E-05 -0.22340912 0.19533659E-02
83 4 0.12532102E-01 0.13984121E-03 4.8242913 -0.45214473E-01
84 3 -0.11008570 0.11123587E-02 -37.991733 0.39832565
85 2 0.39093855 0.18508074E-02 116.42617 -1.4171665
86 1 -0.56428968 0.56416853E-03 -143.87330 2.0484809
87 0 0.27512533 0.13606908E-04 60.838472  
88 7 -0.15524988E-08 -0.27599222E-15 0.12191615E-13 -0.17961055E-15
89 6 0.75408527E-05 0.51820635E-08 0.31843202E-02 -0.26712746E-04
90 5 -0.54428247E-03 0.30714476E-05 -0.22340912 0.19533659E-02
91 4 0.12532102E-01 0.13984121E-03 4.8242913 -0.45214473E-01
92 3 -0.11008570 0.11123587E-02 -37.991733 0.39832565
93 2 0.39093855 0.18508074E-02 116.42617 -1.4171665
94 1 -0.56428968 0.56416853E-03 -143.87330 2.0484809
95 0 0.27512533 0.13606908E-04 60.838472  
96 7 -0.15524988E-08 -0.27599222E-15 0.12191615E-13 -0.17961055E-15
97 6 0.75408527E-05 0.51820635E-08 0.31843202E-02 -0.26712746E-04
98 5 -0.54428247E-03 0.30714476E-05 -0.22340912 0.19533659E-02
99 4 0.12532102E-01 0.13984121E-03 4.8242913 -0.45214473E-01
100 3 -0.11008570 0.11123587E-02 -37.991733 0.39832565
101 2 0.39093855 0.18508074E-02 116.42617 -1.4171665
102 1 -0.56428968 0.56416853E-03 -143.87330 2.0484809
103 0 0.27512533 0.13606908E-04 60.838472  
104 7 -0.15524988E-08 -0.27599222E-15 0.12191615E-13 -0.17961055E-15
105 6 0.75408527E-05 0.51820635E-08 0.31843202E-02 -0.26712746E-04
106 5 -0.54428247E-03 0.30714476E-05 -0.22340912 0.19533659E-02
107 4 0.12532102E-01 0.13984121E-03 4.8242913 -0.45214473E-01
108 3 -0.11008570 0.11123587E-02 -37.991733 0.39832565
109 2 0.39093855 0.18508074E-02 116.42617 -1.4171665
110 1 -0.56428968 0.56416853E-03 -143.87330 2.0484809
111 0 0.27512533 0.13606908E-04 60.838472  
112 7 -0.15524988E-08 -0.27599222E-15 0.12191615E-13 -0.17961055E-15
113 6 0.75408527E-05 0.51820635E-08 0.31843202E-02 -0.26712746E-04
114 5 -0.54428247E-03 0.30714476E-05 -0.22340912 0.19533659E-02
115 4 0.12532102E-01 0.13984121E-03 4.8242913 -0.45214473E-01
116 3 -0.11008570 0.11123587E-02 -37.991733 0.39832565
117 2 0.39093855 0.18508074E-02 116.42617 -1.4171665
118 1 -0.56428968 0.56416853E-03 -143.87330 2.0484809
119 0 0.27512533 0.13606908E-04 60.838472  
120 7 -0.15524988E-08 -0.27599222E-15 0.12191615E-13 -0.17961055E-15
121 6 0.75408527E-05 0.51820635E-08 0.31843202E-02 -0.26712746E-04
122 5 -0.54428247E-03 0.30714476E-05 -0.22340912 0.19533659E-02
123 4 0.12532102E-01 0.13984121E-03 4.8242913 -0.45214473E-01
124 3 -0.11008570 0.11123587E-02 -37.991733 0.39832565
125 2 0.39093855 0.18508074E-02 116.42617 -1.4171665
126 1 -0.56428968 0.56416853E-03 -143.87330 2.0484809
127 0 0.27512533 0.13606908E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.2619_SHGC_EAST_0.4 35 1 VerySmooth 1.487 1.487 1.000 0.401    
2 WINDOW_U_0.2619_SHGC_SOUTH_0.4 36 1 VerySmooth 1.487 1.487 1.000 0.401    
3 WINDOW_U_0.2619_SHGC_WEST_0.4 37 1 VerySmooth 1.487 1.487 1.000 0.401    
4 WINDOW_U_0.2619_SHGC_NORTH_0.4 38 1 VerySmooth 1.487 1.487 1.000 0.401    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   4.47794E-002 0.31435 0.49157 0.49157 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 9.00644E-002 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   4.47794E-002 0.31435 0.49157 0.49157 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 9.00644E-002 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   4.47794E-002 0.31435 0.49157 0.49157 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 9.00644E-002 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   4.47794E-002 0.31435 0.49157 0.49157 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 9.00644E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.496 7.5104E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 2.856E-002 9.114E-005 1.371E-004 0.120 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 1.904E-002 9.429E-005 1.384E-004 0.124 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 2.856E-002 9.114E-005 1.371E-004 0.120 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 1.904E-002 9.429E-005 1.384E-004 0.124 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 2.856E-002 9.114E-005 1.424E-004 0.120 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 1.904E-002 9.429E-005 1.424E-004 0.124 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 2.856E-002 9.114E-005 1.424E-004 0.120 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 1.904E-002 9.429E-005 1.424E-004 0.124 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 2.856E-002 9.114E-005 1.424E-004 0.120 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 1.904E-002 9.429E-005 1.424E-004 0.124 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 2.856E-002 9.114E-005 1.424E-004 0.120 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 1.904E-002 9.429E-005 1.424E-004 0.124 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 4.231E-002 1.187E-005 1.424E-004 3.506E-002 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 4.231E-002 1.187E-005 1.424E-004 3.506E-002 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 4.231E-002 1.187E-005 1.096E-005 3.506E-002 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.9444E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.9465E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.9984E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.0003E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.0494E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0506E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.9551E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.9558E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.9928E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 6.1357E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.0410E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.1706E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.0789E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.1678E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.9732E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.0218E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1091
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.9899E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1254
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.6502E-002
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.4907E-002
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.2909E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.1221E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.4470E-002
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.0107E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 6.2419E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.0627E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.2990E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.0885E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.2054E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.9737E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.0232E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.9443E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.9471E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.9983E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.0011E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.0494E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0509E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.9550E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.9557E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.8118E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.7714E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.0728E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 7.3511E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.2374E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.3609E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.3447E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.3780E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.8278E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.7915E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 7.1122E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.9227E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.7657E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.5002E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.2388E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.5844E-002
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.5758E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.6942E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.7387E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.8309E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.2071E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.2434E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.3448E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.3785E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.5133E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5157E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1505E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.1526E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7507E-003
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7520E-003
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.9551E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.9558E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.5654E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.7017E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1976E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.3166E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7836E-003
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8640E-003
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.9737E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.0233E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.5765E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.6359E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.6640E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.0828E-002
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.2985E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2818E-002
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.1221E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4465E-002
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.5629E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.7099E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1918E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.3110E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7756E-003
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8368E-003
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.9733E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.0218E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.5132E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5154E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1503E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.1522E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7505E-003
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7516E-003
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.9551E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.9557E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.3688E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.5001E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.0349E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.1345E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.6442E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.6733E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3449E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.3785E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.9086E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.7340E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.4165E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.4319E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.6594E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.9925E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.2388E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.5844E-002
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.4644E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.7396E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.1729E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.4882E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.6699E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.7639E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3446E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.3779E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1215
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1037
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1393
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1243
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 8.2934E-002
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 4.5927E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 4.7610E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 2.3039E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 7.7605E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 5.1345E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 8.0790E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 5.3556E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.5040E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.4327E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.8701E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.3283E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 5.2997E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.6891E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.3162E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.9923E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.9188E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.0556E-002
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.7610E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.3035E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.6581E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.7158E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.1246E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.3542E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.3178E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.8016E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 4.8701E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.3283E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1212
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1036
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1389
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1242
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 8.2927E-002
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 4.5998E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 4.7664E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 2.3083E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 7.7497E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 5.1379E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 8.0673E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 5.3592E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.5049E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.4383E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.8752E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.3327E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 5.2924E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.6908E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.3107E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.9938E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.9211E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.0589E-002
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.7664E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.3079E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.6517E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.7181E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.1191E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.3564E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.3192E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.8061E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 4.8752E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.3327E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 67310.22387 67310.22387 4.93377 4.93377 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 19.85200 6.99585E-003 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 73023.10782 73023.10782 5.35287 5.35287 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 19.85200 6.99585E-003 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 7296.22783 7296.22783 0.31373 1.07782 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 684352.73220 684352.73220 50.15036 50.15036 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 19.85200 6.99585E-003 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 302950.62261 302950.62261 12.99108 12.99108 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 67342.06722 67342.06722 4.93471 4.93471 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 19.85200 6.99585E-003 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 82530.45199 82530.45199 3.56733 3.56733 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 11545.28502 11545.28502 0.85441 0.85441 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 21.38200 6.99811E-003 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 12760.20607 12760.20607 0.55206 0.55206 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 15067.07837 15067.07837 1.11503 1.11503 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 21.79000 6.99871E-003 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 8780.19735 8780.19735 0.37996 0.37996 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 22976.71891 22976.71891 1.70038 1.70038 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 27.40000 7.00714E-003 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 13995.10674 13995.10674 0.60568 0.60568 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 18083.43878 18083.43878 1.33825 1.33825 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 24.69700 7.00305E-003 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 6822.13139 6822.13139 0.29493 0.29493 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 108411.03638 108411.03638 7.95033 7.95033 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 19.85200 6.99585E-003 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 170580.19339 170580.19339 7.38671 7.38671 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 158895.53772 158895.53772 11.75896 11.75896 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 22.36800 6.99957E-003 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 113191.77092 113191.77092 4.90197 4.90197 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 238184.37924 238184.37924 17.62671 17.62671 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 27.40000 7.00714E-003 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 169623.64791 169623.64791 7.34517 7.34517 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 160764.84549 160764.84549 11.89730 11.89730 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 24.44200 7.00266E-003 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 107953.67145 107953.67145 4.67456 4.67456 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 10976.81894 10976.81894 0.81234 0.81234 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 21.38200 6.99811E-003 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 24035.70531 24035.70531 1.04162 1.04162 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 15857.40485 15857.40485 1.17352 1.17352 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 22.65700 7.00000E-003 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 15835.73359 15835.73359 0.68629 0.68629 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 24816.66059 24816.66059 1.83654 1.83654 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 27.40000 7.00714E-003 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 23905.32861 23905.32861 1.03596 1.03596 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 16751.88058 16751.88058 1.23971 1.23971 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 24.44200 7.00266E-003 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 15508.27315 15508.27315 0.67208 0.67208 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8482.89795 8482.89795 0.49515 0.49515 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:30:00 21.84100 6.99878E-003 36.20274 1.94861 1.56328E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56328E-002 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 -41.90000 6.45023E-005 36.20274 1.94861 1.56328E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 81307.27397 81307.27397 4.74599 4.74599 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 21.99400 6.99901E-003 36.20274 1.94861 0.15633 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15633 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -41.90000 6.45023E-005 36.20274 1.94861 0.15633 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 8214.78179 8214.78179 0.47950 0.47950 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 21.99400 6.99901E-003 36.20274 1.94861 1.56328E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56328E-002 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 -41.90000 6.45023E-005 36.20274 1.94861 1.56328E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 370536.42564 370536.42564 21.62816 21.62816 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.11800 6.99333E-003 783.67941 42.18139 0.33840 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33840 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 02:50:00 -41.90000 6.45023E-005 783.67941 42.18139 0.33840 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 124552.98 8.79460 8.79460 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 165363.27 2.91046 2.91046 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 14:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1139562.87 81.84744 81.84744 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 1653173.59 37.29949 37.29949 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:20:00
5 VAV_TOP WITH REHEAT Cooling Sensible 124273.66 8.57215 8.57215 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 165336.82 7.00330 7.00330 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:10:00
7 CAV_BAS Cooling Sensible 62427.72 4.93377 4.93377 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 117086.28 1.20016 1.20016 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BOT Cooling Sensible 8281.06 0.49515 0.49515 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BOT Heating Sensible 1525.12 1.56328E-002 1.56328E-002 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER MID Cooling Sensible 79337.39 4.74599 4.74599 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER MID Heating Sensible 15251.23 0.15633 0.15633 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER TOP Cooling Sensible 8016.72 0.47950 0.47950 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER TOP Heating Sensible 1525.12 1.56328E-002 1.56328E-002 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.93377
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.35287
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.35533
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.35100
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.87886
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.94755
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.07224E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.26758E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.87886
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 25919.80624
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.26758E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 543.51640
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 50.15036
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.37927
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.36700
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 18.40518
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.00457E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.24637E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 18.40518
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 485386.65101
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.24637E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 11736.86882
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.93471
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.38544
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.37800
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.86532
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.88477E-004
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.03136E-003
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.56733
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 117890.62261
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.03136E-003
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3110.92319
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.85441
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27951
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.27600
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23582
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.74537
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.36308E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.59504E-004
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.55206
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18232.25490
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.59504E-004
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 480.97209
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.11503
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13803
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.22301
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36807
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.76032E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.09761E-004
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.37996
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12546.38079
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.09761E-004
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 330.95189
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.70038
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14045
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.34008
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37454
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.71263E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.74956E-004
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.60568
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19998.57919
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.74956E-004
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 527.51719
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.33825
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11500
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.26765
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30668
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.31291E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.52570E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.29493
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9745.39437
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.52570E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 257.14964
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.95033
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.30039
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.29000
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.30559
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.80104
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.26835E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.13284E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.38671
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 243796.18822
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.13284E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 6429.55427
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.75896
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13088
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.35179
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34902
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.91099E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.41532E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.90197
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 161779.42315
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.41532E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4266.44784
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 17.62671
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13549
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.52534
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36131
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.81200E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.12087E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.34517
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 242427.91355
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.12087E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 6393.50128
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.89730
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12936
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.37946
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34496
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.94524E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.34977E-003
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.67456
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 154287.12329
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.34977E-003
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4069.01857
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.04162
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22928
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.28800
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.29999
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.61141
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.66175E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.00598E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.04162
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 34360.17520
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.00598E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 905.94803
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.17352
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13115
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23470
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34973
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.90510E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.98049E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.68629
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 22638.20368
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.98049E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 596.87607
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.83654
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13004
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.36731
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34678
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.92984E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.98966E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.03596
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 34173.68430
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.98966E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 901.03404
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.23971
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12415
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24794
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33106
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.06897E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.93952E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.67208
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 22169.86296
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.93952E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 584.53373
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.49515
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.74599
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.47950
215 ZoneHVAC:IdealLoadsAirSystem AIRLOOP DATACENTER BASEMENT Design Size Maximum Heating Air Flow Rate [m3/s] 0.33840
216 ZoneHVAC:IdealLoadsAirSystem AIRLOOP DATACENTER BASEMENT Design Size Maximum Cooling Air Flow Rate [m3/s] 21.62816
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.18047
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.94541
219 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.36094
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 2.94541
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 8.79460
222 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 8.79460
223 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
224 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.33491
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 49.69183
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 28.96737
227 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 99.38366
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 37.29949
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 81.84744
230 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 81.84744
231 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
232 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.45572
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.11305
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.01526
235 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.22611
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 7.00330
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 8.57215
238 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 8.57215
239 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
240 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.81698
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.93377
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.93377
243 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 4.93377
244 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 4.93377
245 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 4.93377
246 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 4.93377
247 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
249 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.49515
250 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.49515
251 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.49515
252 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.49515
253 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.49515
254 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.49515
255 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
256 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
257 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.74599
258 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.74599
259 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.74599
260 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.74599
261 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.74599
262 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.74599
263 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
265 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.47950
266 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.47950
267 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.47950
268 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.47950
269 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.47950
270 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.47950
271 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
273 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 8.79460
274 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 81.84744
275 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 8.57215
276 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 4.93377
277 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.49515
278 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.74599
279 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.47950
280 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 8.79460
281 HeatExchanger:AirToAir:SensibleAndLatent VAV_BOT WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
282 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.00661
283 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
284 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.90821
285 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.26216E-003
286 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
287 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 156568.91297
288 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.66080E-003
289 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.79460
290 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 164406.21041
291 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.43830E-003
292 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 2132.27148
293 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 8.79460
294 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 6.66080E-003
295 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 7.14914E-005
296 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.43830E-003
297 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 81.84744
298 HeatExchanger:AirToAir:SensibleAndLatent VAV_MID WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 25.38195
299 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.10962
300 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
301 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.90826
302 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.27608E-003
303 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
304 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 1470729.92229
305 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.25683E-002
306 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 81.84744
307 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 1599918.91862
308 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.39968E-002
309 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 20456.87531
310 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 81.84744
311 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 6.25683E-002
312 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 7.61074E-006
313 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.39968E-002
314 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 8.57215
315 HeatExchanger:AirToAir:SensibleAndLatent VAV_TOP WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
316 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.00908
317 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
318 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.90821
319 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.26236E-003
320 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
321 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 152639.26830
322 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.49363E-003
323 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.57215
324 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 165266.00908
325 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.44582E-003
326 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 2122.49062
327 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 8.57215
328 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 6.49363E-003
329 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 7.33320E-005
330 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.44582E-003
331 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.93377
332 HeatExchanger:AirToAir:SensibleAndLatent CAV_BAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 1.20016
333 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 24.79273
334 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
335 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.39575
336 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.41573E-003
337 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
338 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 85946.59474
339 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.65637E-003
340 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 4.93377
341 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 294985.31289
342 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.58066E-003
343 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 6017.20826
344 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 4.93377
345 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 3.65637E-003
346 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.30236E-004
347 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.58066E-003
348 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.49515
349 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56328E-002
350 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.49515
351 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9827.06755
352 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6297.92637
353 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.40664E-004
354 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.49515
355 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.49515
356 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.49515
357 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.49515
358 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9827.06755
359 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9827.06755
360 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 1525.12251
361 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
362 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.49515
363 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.49515
364 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9827.06755
365 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.40664E-004
366 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 1525.12251
367 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.74599
368 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15633
369 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.74599
370 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 94202.48267
371 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 60365.04296
372 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.30701E-003
373 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.74599
374 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.74599
375 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.74599
376 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.74599
377 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 94202.48267
378 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 94202.48267
379 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 15251.22507
380 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
381 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.74599
382 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.74599
383 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 94202.48267
384 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.30701E-003
385 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 15251.22507
386 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.47950
387 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56328E-002
388 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.47950
389 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9517.42669
390 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6098.92140
391 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.33081E-004
392 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.47950
393 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.47950
394 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.47950
395 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.47950
396 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9517.42669
397 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9517.42669
398 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 1525.12251
399 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
400 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.47950
401 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.47950
402 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9517.42669
403 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.33081E-004
404 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 1525.12251
405 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 7.93790E-002
406 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 16195.12853
407 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 7.93790E-002
408 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 9.52549
409 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 7.93790E-002
410 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 7.93790E-002
411 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 333193.69612
412 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
413 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 3.35059E-002
414 PlantLoop HEATSYS1 Plant Loop Volume [m3] 4.02071
415 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 3.35059E-002
416 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 9990.59585
417 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
418 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 3829928.71443
419 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 3829928.71000
420 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 3.35059E-002
421 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 7.93790E-002
422 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 9.52549
423 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 7.93790E-002
424 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 11212.43378
425 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 7.93790E-002
426 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 3.99429E-002
427 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 939948.05728
428 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 945669.18000
429 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 4.79434E-002
430 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 7.93790E-002
431 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 3.99429E-002
432 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 939948.05728
433 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 945669.18000
434 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 4.79434E-002
435 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 2.78076E-003
436 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 0.33369
437 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 2.78076E-003
438 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 702.21029
439 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 2.78076E-003
440 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 35644.39112
441 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 19523.09239
442 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 17822.19556
443 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 1996.19659
444 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 5783.98299
445 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 114543.39647
446 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 114543.40000
447 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 2.78076E-003
448 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
449 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
450 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
451 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 5.95776
452 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
453 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 9.58868E-002
454 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 11.50642
455 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 9.58868E-002
456 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 28593.09301
457 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 36.97940
458 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1123406.21841
459 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 7.39588
460 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 140425.77730
461 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 36.97940
462 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1123406.21841
463 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 7.39588
464 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 140425.77730
465 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 45 4.86075E-002
466 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 45 4.86075E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 24572.91
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 459811.47
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 111708.47
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 17275.19
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 11887.62
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 18948.45
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 9234.26
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 230986.16
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 153278.17
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 229690.00
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 146180.64
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 32553.27
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 21447.67
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 32376.61
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 21004.00
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 89008.63
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 849659.99
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 88295.65
19 Coil:Heating:Water CAV_BAS HEATING COIL 210691.80


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 233162.35 159651.60 73510.75 0.68 32800.80 332.68
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2177237.50 1488854.05 688383.46 0.68 305359.15 3097.12
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 227280.87 155620.06 71660.81 0.68 31971.16 324.27
4 Coil:Cooling:Water CAV_BAS COOLING COIL 127092.96 87809.22 39283.74 0.69 17086.12 173.30


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 7.08 24.14
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 7.08 24.14


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.270 0.259   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.270 0.259   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.270 0.259   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.826 0.735   105.88 200.61 105.88 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_NORTH_0.4 N/A 1.487 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_NORTH_0.4 N/A 1.487 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_NORTH_0.4 N/A 1.487 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_NORTH_0.4 N/A 1.487 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_NORTH_0.4 N/A 1.487 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.826 0.735   71.89 133.74 71.89 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_EAST_0.4 N/A 1.487 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_EAST_0.4 N/A 1.487 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_EAST_0.4 N/A 1.487 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.826 0.735   105.88 200.61 105.88 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_SOUTH_0.4 N/A 1.487 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_SOUTH_0.4 N/A 1.487 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_SOUTH_0.4 N/A 1.487 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_SOUTH_0.4 N/A 1.487 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_SOUTH_0.4 N/A 1.487 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.826 0.735   71.89 133.74 71.89 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_WEST_0.4 N/A 1.487 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_WEST_0.4 N/A 1.487 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_WEST_0.4 N/A 1.487 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.757 0.680   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_NORTH_0.4 N/A 1.487 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.757 0.680   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_EAST_0.4 N/A 1.487 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.757 0.680   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_SOUTH_0.4 N/A 1.487 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.757 0.680   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_WEST_0.4 N/A 1.487 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.136 0.971   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_NORTH_0.4 N/A 1.487 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.136 0.971   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_EAST_0.4 N/A 1.487 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.136 0.971   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_SOUTH_0.4 N/A 1.487 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.136 0.971   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.2619_SHGC_WEST_0.4 N/A 1.487 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.826 0.735   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.826 0.735   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.826 0.735   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.826 0.735   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.757 0.680   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.757 0.680   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.757 0.680   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.757 0.680   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.136 0.971   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.136 0.971   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.136 0.971   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.136 0.971   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.270 0.259   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.270 0.259   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.270 0.259   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 6.6539538054E-004 1.4070460855E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 2.3387105988E-003 5.2642682962E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 1.2977376464E-002 8.0461837795E-003 Pass Pass 0.4847372570 0.4910224282 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 0.1727474279 0.1493462287 Pass Pass 0.9788504759 1.2207945452 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 6.5128409947E-003 6.8918797400E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 7.4583248738E-003 9.2239424949E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 8.9280243545E-003 1.7482449664E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 6.7465781769E-003 6.5339753453E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.4723558645 0.4135941248 Pass Pass 0.7010448816 0.5827275252 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.5717227667 0.5084846845 Pass Pass 0.7243944162 0.7506406788 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.5429608888 0.4758530882 Pass Pass 0.7307748696 0.7718574370 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.4661272018 0.4042097147 Pass Pass 0.7929516664 0.7499815032 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.7063192199 0.5820878550 Pass Pass 0.6138004444 0.5738367427 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.7228106060 0.6598847950 Pass Pass 0.6332190571 0.6464023441 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.6853233365 0.6349641476 Pass Pass 0.6411218957 0.6591366083 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.6317467911 0.6079357459 Pass Pass 0.6380570411 0.6358139734 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 2.2352675655E-003 2.1416006847E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.9898664612E-002 4.2528331809E-002 Pass Pass 0.4862692266 0.4781762656 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 0.2040990171 0.1220381748 Pass Pass 0.4822621896 0.4919763527 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 3.9553338826E-008 6.2229942898E-008 Pass Pass 3.6861555283E-003 3.9192312277E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 2.5771046706E-003 1.5414857957E-003 Pass Pass 1.3068327073E-003 9.8064071970E-004 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 4.7714817236E-003 2.4906199878E-003 Pass Pass 2.7560637217E-003 1.4667722101E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 2.8865798640E-015 2.8694486750E-015 Pass Pass 2.0941499363E-005 1.1351621970E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 4424.04 58.89 0.00 23550.30 4574.91 32608.15



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB -41.90 0.00 -41.90 Wetbulb [C] 0.30 20.00
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 27.40 10.20 16.10 Wetbulb [C] 3.10 180.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 0.00 0      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.261 0.270 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.261 0.270 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.261 0.270 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.735 0.826 200.61 105.88 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.735 0.826 133.74 71.89 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.735 0.826 200.61 105.88 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.735 0.826 133.74 71.89 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.680 0.757 2006.06 1136.85 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.680 0.757 1337.37 757.90 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.680 0.757 2006.06 1136.85 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.680 0.757 1337.37 757.90 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.971 1.136 200.61 113.68 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.971 1.136 133.74 75.79 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.971 1.136 200.61 113.68 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.971 1.136 133.74 75.79 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.735 0.826 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 0.735 0.826 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.735 0.826 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.735 0.826 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.680 0.757 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.680 0.757 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.680 0.757 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.680 0.757 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.971 1.136 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.971 1.136 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.971 1.136 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.971 1.136 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.30 0.159 0.163 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.261 0.270 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.261 0.270 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.261 0.270 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.2619_SHGC_NORTH_0.4   17.38 0.00 0.00 17.38 17.38 1.487 0.401 0.401             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.2619_SHGC_NORTH_0.4   17.38 0.00 0.00 17.38 17.38 1.487 0.401 0.401             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.2619_SHGC_NORTH_0.4   17.38 0.00 0.00 17.38 17.38 1.487 0.401 0.401             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.2619_SHGC_NORTH_0.4   17.38 0.00 0.00 17.38 17.38 1.487 0.401 0.401             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.2619_SHGC_NORTH_0.4   17.38 0.00 0.00 17.38 17.38 1.487 0.401 0.401             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.2619_SHGC_EAST_0.4   19.32 0.00 0.00 19.32 19.32 1.487 0.401 0.401             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.2619_SHGC_EAST_0.4   19.32 0.00 0.00 19.32 19.32 1.487 0.401 0.401             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.2619_SHGC_EAST_0.4   19.32 0.00 0.00 19.32 19.32 1.487 0.401 0.401             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.2619_SHGC_SOUTH_0.4   17.38 0.00 0.00 17.38 17.38 1.487 0.401 0.401             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.2619_SHGC_SOUTH_0.4   17.38 0.00 0.00 17.38 17.38 1.487 0.401 0.401             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.2619_SHGC_SOUTH_0.4   17.38 0.00 0.00 17.38 17.38 1.487 0.401 0.401             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.2619_SHGC_SOUTH_0.4   17.38 0.00 0.00 17.38 17.38 1.487 0.401 0.401             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.2619_SHGC_SOUTH_0.4   17.38 0.00 0.00 17.38 17.38 1.487 0.401 0.401             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.2619_SHGC_WEST_0.4   19.32 0.00 0.00 19.32 19.32 1.487 0.401 0.401             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.2619_SHGC_WEST_0.4   19.32 0.00 0.00 19.32 19.32 1.487 0.401 0.401             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.2619_SHGC_WEST_0.4   19.32 0.00 0.00 19.32 19.32 1.487 0.401 0.401             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.2619_SHGC_NORTH_0.4   86.92 0.00 0.00 86.92 869.21 1.487 0.401 0.401             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.2619_SHGC_EAST_0.4   57.95 0.00 0.00 57.95 579.48 1.487 0.401 0.401             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.2619_SHGC_SOUTH_0.4   86.92 0.00 0.00 86.92 869.21 1.487 0.401 0.401             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.2619_SHGC_WEST_0.4   57.95 0.00 0.00 57.95 579.48 1.487 0.401 0.401             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.2619_SHGC_NORTH_0.4   86.92 0.00 0.00 86.92 86.92 1.487 0.401 0.401             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.2619_SHGC_EAST_0.4   57.95 0.00 0.00 57.95 57.95 1.487 0.401 0.401             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.2619_SHGC_SOUTH_0.4   86.92 0.00 0.00 86.92 86.92 1.487 0.401 0.401             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.2619_SHGC_WEST_0.4   57.95 0.00 0.00 57.95 57.95 1.487 0.401 0.401             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             3476.85 1.487 0.401 0.401                      
North Total or Average             1043.06 1.487 0.401 0.401                      
Non-North Total or Average             2433.80 1.487 0.401 0.401                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 5.8895 2779.43 16369.36 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 135.58
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 5.8895 2496.12 14700.84 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 121.76
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 5.8895 24961.20 147008.37 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 1217.57
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 5.8895 2496.12 14700.84 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 121.76
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 5.8895 313.41 1845.84 LightsWired LTG_SCH_OFFICE 45.29 168.00 29.71 0.0000 Y 10.30
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 5.8895 201.98 1189.53 LightsWired LTG_SCH_OFFICE 45.29 168.00 29.24 0.0000 Y 6.53
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 5.8895 313.42 1845.88 LightsWired LTG_SCH_OFFICE 45.29 168.00 28.55 0.0000 Y 9.89
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 5.8895 201.98 1189.53 LightsWired LTG_SCH_OFFICE 45.29 168.00 29.17 0.0000 Y 6.51
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 5.8895 3134.13 18458.37 LightsWired LTG_SCH_OFFICE 45.29 168.00 29.74 0.0000 Y 103.05
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 5.8895 2019.75 11895.27 LightsWired LTG_SCH_OFFICE 45.29 168.00 29.24 0.0000 Y 65.28
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 5.8895 3134.20 18458.77 LightsWired LTG_SCH_OFFICE 45.29 168.00 28.59 0.0000 Y 99.08
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 5.8895 2019.75 11895.27 LightsWired LTG_SCH_OFFICE 45.29 168.00 29.18 0.0000 Y 65.15
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 5.8895 313.41 1845.84 LightsWired LTG_SCH_OFFICE 45.29 168.00 29.74 0.0000 Y 10.30
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 5.8895 201.98 1189.53 LightsWired LTG_SCH_OFFICE 45.29 168.00 29.23 0.0000 Y 6.53
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 5.8895 313.42 1845.88 LightsWired LTG_SCH_OFFICE 45.29 168.00 28.59 0.0000 Y 9.91
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 5.8895 201.98 1189.53 LightsWired LTG_SCH_OFFICE 45.29 168.00 29.18 0.0000 Y 6.52
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 5.8895 783.68 4615.46 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 38.23
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 8.8011 36.20 318.62 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 3.26
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 8.8011 362.03 3186.24 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 32.64
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 8.8011 36.20 318.62 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 3.26
Interior Lighting Total       5.9168 46320.38 274067.57               648.61


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.88 711.95
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.88 255.65
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.84 711.94
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.84 255.65
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.88 711.95
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.88 255.65
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.84 711.94
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.84 255.65
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.88 711.95
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.88 255.65
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.84 711.94
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.84 255.65
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 9973.05 AstronomicalClock -   44.84 44.84 83.95
EXTERIOR_LIGHTS_B 991.40 AstronomicalClock -   83.06 63.95 11.90
EXTERIOR_LIGHTS_C 26646.63 AstronomicalClock -   83.06 52.41 262.13
Exterior Lighting Total 37611.08           357.99



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 1861593.71          
HEATSYS1 BOILER Boiler:HotWater 3829928.71 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 945669.18 5.33 935020.46 4.98 7.08 24.14
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 945669.18 5.33 935020.46 4.98 7.08 24.14
CENTRAL TOWER FluidCooler:TwoSpeed 148548.00          
CENTRAL BOILER Boiler:HotWater 114543.40 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1123406.22          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1123406.22          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 156568.91 233162.35 159651.60 73510.75 0.68 - 32800.80 332.68
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 1470729.92 2177237.50 1488854.05 688383.46 0.68 - 305359.15 3097.12
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 152639.27 227280.87 155620.06 71660.81 0.68 - 31971.16 324.27
CAV_BAS COOLING COIL Coil:Cooling:Water 85946.59 127092.96 87809.22 39283.74 0.69 - 17086.12 173.30
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9827.07 6297.93 3529.14 0.64 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   94202.48 60365.04 33837.44 0.64 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9517.43 6098.92 3418.51 0.64 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 25919.81 24572.91 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 485386.65 459811.47 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 117890.62 111708.47 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 18232.25 17275.19 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 12546.38 11887.62 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 19998.58 18948.45 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 9745.39 9234.26 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 243796.19 230986.16 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 161779.42 153278.17 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 242427.91 229690.00 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 154287.12 146180.64 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 34360.18 32553.27 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 22638.20 21447.67 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 34173.68 32376.61 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 22169.86 21004.00 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 164406.21 89008.63 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 1599918.92 849659.99 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 165266.01 88295.65 -
CAV_BAS HEATING COIL Coil:Heating:Water 294985.31 210691.80 -
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9827.07 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   94202.48 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9517.43 0.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   1525.12 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   15251.23 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   1525.12 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 8.79 20084.47 2283.73 1.00 1.12 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 81.85 186917.29 2283.73 1.00 1.07 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 8.57 19576.45 2283.73 1.00 1.12 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 4.93 8365.97 1695.65 1.00 1.16 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.50 554.62 1120.11 1.00 1.61 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.75 5316.02 1120.11 1.00 1.16 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.48 537.10 1120.11 1.00 1.62 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.079379 16195.13 204022.71 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.033506 9990.60 298174.34 0.91 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.079379 11212.43 141251.81 0.91 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.002781 702.21 252524.76 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 3168.45 0.000440 5.96 13540.37 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 180718.98 0.095887 28593.09 298196.27 0.91 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.50 0.08



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 67310.22 67310.22 24.22 4.934 4.934 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00752 19.85 0.00700 1.200 0.00
CORE_BOTTOM 73023.11 73023.11 29.25 5.353 5.353 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00743 19.85 0.00700 1.078 0.00
CORE_MID 684352.73 684352.73 274.17 50.150 50.150 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00746 19.85 0.00700 10.778 0.00
CORE_TOP 67342.07 67342.07 26.98 4.935 4.935 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00746 19.85 0.00700 1.078 0.00
PERIMETER_BOT_ZN_3 11545.29 11545.29 36.84 0.854 0.854 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 24.00 24.00 0.00733 21.38 0.00700 0.135 0.00
PERIMETER_BOT_ZN_2 15067.08 15067.08 74.60 1.115 1.115 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 24.00 24.00 0.00716 21.79 0.00700 0.087 0.00
PERIMETER_BOT_ZN_1 22976.72 22976.72 73.31 1.700 1.700 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 24.00 24.00 0.00717 27.40 0.00701 0.135 0.00
PERIMETER_BOT_ZN_4 18083.44 18083.44 89.53 1.338 1.338 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 24.00 24.00 0.00714 24.70 0.00700 0.087 0.00
PERIMETER_MID_ZN_3 108411.04 108411.04 345.90 7.950 7.950 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00736 19.85 0.00700 1.353 0.00
PERIMETER_MID_ZN_2 158895.54 158895.54 786.71 11.759 11.759 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 24.00 24.00 0.00715 22.37 0.00700 0.872 0.00
PERIMETER_MID_ZN_1 238184.38 238184.38 759.95 17.627 17.627 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 24.00 0.00716 27.40 0.00701 1.353 0.00
PERIMETER_MID_ZN_4 160764.85 160764.85 795.96 11.897 11.897 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 24.00 24.00 0.00715 24.44 0.00700 0.872 0.00
PERIMETER_TOP_ZN_3 10976.82 10976.82 35.02 0.812 0.812 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 24.00 24.00 0.00734 21.38 0.00700 0.135 0.00
PERIMETER_TOP_ZN_2 15857.40 15857.40 78.51 1.174 1.174 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 24.00 24.00 0.00715 22.66 0.00700 0.087 0.00
PERIMETER_TOP_ZN_1 24816.66 24816.66 79.18 1.837 1.837 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 24.00 0.00715 27.40 0.00701 0.135 0.00
PERIMETER_TOP_ZN_4 16751.88 16751.88 82.94 1.240 1.240 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 24.00 24.00 0.00715 24.44 0.00700 0.087 0.00
DATACENTER_BOT_ZN_6 8482.90 8482.90 234.32 0.495 0.495 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:30:00 27.00 27.00 0.00709 21.84 0.00700 0.016 0.00
DATACENTER_MID_ZN_6 81307.27 81307.27 2245.89 4.746 4.746 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 27.00 27.00 0.00709 21.99 0.00700 0.156 0.00
DATACENTER_TOP_ZN_6 8214.78 8214.78 226.91 0.480 0.480 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 27.00 27.00 0.00709 21.99 0.00700 0.016 0.00
DATACENTER_BASEMENT_ZN_6 370536.43 370536.43 472.82 21.628 21.628 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.00 27.00 0.00704 18.12 0.00699 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 22.71 0.00006 -41.90 0.00006 1.200 0.00
CORE_BOTTOM 7296.23 7296.23 2.92 0.314 1.078 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -41.90 0.00006 1.078 0.00
CORE_MID 302950.62 302950.62 121.37 12.991 12.991 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -41.90 0.00006 10.778 0.00
CORE_TOP 82530.45 82530.45 33.06 3.567 3.567 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -41.90 0.00006 1.078 0.00
PERIMETER_BOT_ZN_3 12760.21 12760.21 40.71 0.552 0.552 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00799 -41.90 0.00006 0.135 0.00
PERIMETER_BOT_ZN_2 8780.20 8780.20 43.47 0.380 0.380 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00799 -41.90 0.00006 0.087 0.00
PERIMETER_BOT_ZN_1 13995.11 13995.11 44.65 0.606 0.606 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00799 -41.90 0.00006 0.135 0.00
PERIMETER_BOT_ZN_4 6822.13 6822.13 33.78 0.295 0.295 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00798 -41.90 0.00006 0.087 0.00
PERIMETER_MID_ZN_3 170580.19 170580.19 544.27 7.387 7.387 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00799 -41.90 0.00006 1.353 0.00
PERIMETER_MID_ZN_2 113191.77 113191.77 560.42 4.902 4.902 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00799 -41.90 0.00006 0.872 0.00
PERIMETER_MID_ZN_1 169623.65 169623.65 541.20 7.345 7.345 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00798 -41.90 0.00006 1.353 0.00
PERIMETER_MID_ZN_4 107953.67 107953.67 534.49 4.675 4.675 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00798 -41.90 0.00006 0.872 0.00
PERIMETER_TOP_ZN_3 24035.71 24035.71 76.69 1.042 1.042 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00799 -41.90 0.00006 0.135 0.00
PERIMETER_TOP_ZN_2 15835.73 15835.73 78.40 0.686 0.686 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00799 -41.90 0.00006 0.087 0.00
PERIMETER_TOP_ZN_1 23905.33 23905.33 76.27 1.036 1.036 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00799 -41.90 0.00006 0.135 0.00
PERIMETER_TOP_ZN_4 15508.27 15508.27 76.78 0.672 0.672 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00799 -41.90 0.00006 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 18.00 24.51 0.00073 -41.90 0.00006 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 22.54 0.00093 -41.90 0.00006 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 18.00 19.60 0.00054 -41.90 0.00006 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 02:50:00 18.00 27.00 0.00700 -41.90 0.00006 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 8.79 8.79 2.91 2.91 8.7946 2.9454 8.7946 0.3349 0.3000
VAV_MID WITH REHEAT 81.85 81.85 37.30 37.30 81.8474 37.2995 81.8474 0.4557 0.3000
VAV_TOP WITH REHEAT 8.57 8.57 7.00 7.00 8.5721 7.0033 8.5721 0.8170 0.3000
CAV_BAS 4.93 4.93 1.20 1.20 4.9338 4.9338 4.9338 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.50 0.50 0.02 0.02 0.4952 0.4952 0.4952 1.0000 1.0000
AIRLOOP DATACENTER MID 4.75 4.75 0.16 0.16 4.7460 4.7460 4.7460 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.48 0.48 0.02 0.02 0.4795 0.4795 0.4795 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 25919.806 25919.806 1.878857 0.00022676 543.516 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 25919.81 25919.81 1.878857 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00799864 50.9045 7296.23 0.00 26013.59 26013.59
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 485386.651 485386.651 18.405180 0.00424637 11736.869 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 485386.65 485386.65 18.405180 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00800000 50.9130 302950.62 0.00 486955.86 486955.86
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 117890.623 117890.623 3.567334 0.00103136 3110.923 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 117890.62 117890.62 3.567334 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00800000 50.9130 82530.45 0.00 118290.62 118290.62
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 18232.255 18232.255 0.552065 0.00015950 480.972 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 18232.25 18232.25 0.552065 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00798950 50.8472 12760.21 0.00 18293.08 18293.08
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 12546.381 12546.381 0.379962 0.00010976 330.952 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12546.38 12546.38 0.379962 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00799066 50.8545 8780.20 0.00 12588.05 12588.05
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 19998.579 19998.579 0.605676 0.00017496 527.517 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 19998.58 19998.58 0.605676 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00799152 50.8599 13995.11 0.00 20064.93 20064.93
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 9745.394 9745.394 0.294928 0.00008526 257.150 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 9745.39 9745.39 0.294928 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00798180 50.7989 6822.13 0.00 9778.36 9778.36
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 243796.188 243796.188 7.386708 0.00213284 6429.554 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 243796.19 243796.19 7.386708 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00798508 50.8195 170580.19 0.00 244596.09 244596.09
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 161779.423 161779.423 4.901973 0.00141532 4266.448 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 161779.42 161779.42 4.901973 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00798510 50.8196 113191.77 0.00 162309.46 162309.46
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 242427.914 242427.914 7.345170 0.00212087 6393.501 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 242427.91 242427.91 7.345170 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00798498 50.8189 169623.65 0.00 243223.56 243223.56
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 154287.123 154287.123 4.674557 0.00134977 4069.019 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 154287.12 154287.12 4.674557 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00798418 50.8139 107953.67 0.00 154793.75 154793.75
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 34360.175 34360.175 1.041625 0.00030060 905.948 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 34360.18 34248.14 1.041625 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00798726 50.8332 24035.71 0.00 34471.32 34471.32
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 22638.204 22638.204 0.686294 0.00019805 596.876 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 22638.20 22638.20 0.686294 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00798711 50.8323 15835.73 0.00 22711.37 22711.37
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 34173.684 34173.684 1.035964 0.00029897 901.034 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 34173.68 34173.68 1.035964 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00798719 50.8328 23905.33 0.00 34284.25 34284.25
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 22169.863 22169.863 0.672082 0.00019395 584.534 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 22169.86 22169.86 0.672082 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00798684 50.8306 15508.27 0.00 22241.56 22241.56
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 156568.913 -999.000 8.794601 0.00666080 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 156568.91 150583.01 8.794601 25.01 15.51 0.00726216 10.91 9.59 0.00700000 27.40 0.00700714 16.15 28.8608 24.00 0.00736954 39.1269 115747.12 0.00 158795.45 158795.45
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 164406.210 164406.210 2.638380 0.00143830 2132.271 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 14:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 164406.21 164406.21 2.638380 -39.51 -39.51 0.00036561 12.80 11.46 0.00800000 -41.90 0.00006450 -41.90 96.2026 21.00 0.00799092 50.8561 38018.01 0.00 107512.20 107512.20
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 1470729.922 -999.000 81.847445 0.06256825 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 1470729.92 1411984.23 81.847445 25.11 15.56 0.00727608 10.91 9.59 0.00700000 27.40 0.00700714 16.15 31.0113 24.00 0.00740651 39.3209 1050133.54 0.00 1491513.88 1491513.88
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 1599918.919 1599918.919 24.554233 0.01399679 20456.875 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:20:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1599918.92 1599918.92 24.554233 -41.90 -41.90 0.00006450 12.80 11.46 0.00800000 -41.90 0.00006450 -41.90 103.3710 19.61 0.00797407 55.3190 436019.15 0.00 1026065.20 1026065.20
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 152639.268 -999.000 8.572147 0.00649363 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 152639.27 146800.18 8.572147 25.01 15.51 0.00726236 10.91 9.59 0.00700000 27.40 0.00700714 16.15 29.6097 24.00 0.00737020 39.1303 115464.19 0.00 154809.63 154809.63
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 165266.009 165266.009 2.571644 0.00144582 2122.491 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 165266.01 165266.01 2.571644 -41.15 -41.15 0.00016750 12.80 11.46 0.00800000 -41.90 0.00006450 -41.90 98.6991 17.41 0.00797827 63.4927 61184.44 0.00 106635.33 106635.33
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 85946.595 -999.000 4.933770 0.00365637 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 85946.59 80787.85 4.933770 24.79 15.57 0.00741573 11.40 9.81 0.00700000 26.89 0.00700637 15.97 24.3253 24.00 0.00757073 40.1826 59047.99 0.00 87164.77 87164.77
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 294985.313 294985.313 4.933770 0.00258066 6017.208 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 294985.31 294985.31 4.933770 -10.19 -13.38 0.00006450 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 24.3253 22.82 0.00006450 0.3721 0.00 0.00 222227.97 222227.97
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9827.068 6297.926 0.495152 0.00024066 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:30:00 8778.85 8685.88 -999.0 27.80 16.35 0.00708237 12.80 10.42 0.00700000 21.99 0.00699901 14.15 -999.0000 27.00 0.00708509 31.4924 8482.55 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 94202.483 60365.043 4.745988 0.00230701 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 84155.48 83226.96 -999.0 27.79 16.35 0.00708583 12.80 10.42 0.00700000 21.99 0.00699901 14.15 -999.0000 27.00 0.00708879 31.5088 81307.27 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9517.427 6098.921 0.479504 0.00023308 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 8502.35 8409.40 -999.0 27.80 16.35 0.00708504 12.80 10.42 0.00700000 21.99 0.00699901 14.15 -999.0000 27.00 0.00708794 31.5050 8214.78 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9827.068 9827.068 0.495152 0.00024066 -999.000 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9827.07 9827.07 0.495152 -41.90 -41.90 0.00006450 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 3.1572 25.29 0.00072609 3.6066 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 94202.483 94202.483 4.745988 0.00230701 -999.000 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 94202.48 94202.48 4.745988 -41.90 -41.90 0.00006450 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 3.2939 23.78 0.00092890 5.0496 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9517.427 9517.427 0.479504 0.00023308 -999.000 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9517.43 9517.43 0.479504 -41.90 -41.90 0.00006450 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 3.2602 21.90 0.00053768 3.2779 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 1525.123 1525.123 -999.0 -999.0 -999.000 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1525.12 1525.12 0.495152 -1.32 -5.89 0.00070521 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 3.1572 25.29 0.00072609 3.6066 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 15251.225 15251.225 -999.0 -999.0 -999.000 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 15251.23 15251.23 4.745988 -1.38 -5.58 0.00090043 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 3.2939 23.78 0.00092890 5.0496 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 1525.123 1525.123 -999.0 -999.0 -999.000 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1525.12 1525.12 0.479504 -1.37 -6.25 0.00052225 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 3.2602 21.90 0.00053768 3.2779 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 25919.806 25919.806 1.878857 0.00022676 543.516 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 0.6634 0.676770 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 25919.81 25919.81 1.0000 2.22727073 1.878857 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 0.22673464 60.00 32.22 27.78 0.000 25919.81 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.82 0.00799864 21.00 0.00799864 50.9045 7296.23 0.00 26013.59 26013.59 2.22727073 12.80 11.60 0.00800000 33059.8 24.25 16.05 0.00800000 44739.4
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 485386.651 485386.651 18.405180 0.00424637 11736.869 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 12.4235 12.673517 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 485386.65 485386.65 1.0000 21.81822404 18.405180 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 4.24594099 60.00 32.22 27.78 0.000 485386.65 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.87 0.00800000 21.00 0.00800000 50.9130 302950.62 0.00 486955.86 486955.86 21.81822404 12.80 11.60 0.00800000 33059.8 34.69 19.56 0.00800000 55378.6
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 117890.623 117890.623 3.567334 0.00103136 3110.923 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 3.0174 3.078141 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 117890.62 117890.62 1.0000 4.22885836 3.567334 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 1.03125339 60.00 32.22 27.78 0.000 117890.62 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 50.9130 82530.45 0.00 118290.62 118290.62 4.22885836 12.80 11.60 0.00800000 33059.8 40.23 21.25 0.00800000 61032.1
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 18232.255 18232.255 0.552065 0.00015950 480.972 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 0.4667 0.476047 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 18232.25 18232.25 1.0000 0.65443919 0.552065 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 0.15948745 60.00 32.22 27.78 0.000 18232.25 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00798950 21.00 0.00798950 50.8472 12760.21 0.00 18293.08 18293.08 0.65443919 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61012.1
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 12546.381 12546.381 0.379962 0.00010976 330.952 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 0.3211 0.327588 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12546.38 12546.38 1.0000 0.45042209 0.379962 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 0.10975002 60.00 32.22 27.78 0.000 12546.38 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00799066 21.00 0.00799066 50.8545 8780.20 0.00 12588.05 12588.05 0.45042209 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61007.1
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 19998.579 19998.579 0.605676 0.00017496 527.517 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 0.5119 0.522166 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 19998.58 19998.58 1.0000 0.71799245 0.605676 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 0.17493845 60.00 32.22 27.78 0.000 19998.58 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00799152 21.00 0.00799152 50.8599 13995.11 0.00 20064.93 20064.93 0.71799245 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61005.7
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 9745.394 9745.394 0.294928 0.00008526 257.150 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 0.2494 0.254454 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 9745.39 9745.39 1.0000 0.34961869 0.294928 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 0.08524826 60.00 32.22 27.78 0.000 9745.39 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.91 0.00798180 21.00 0.00798180 50.7989 6822.13 0.00 9778.36 9778.36 0.34961869 12.80 11.60 0.00800000 33059.8 40.23 21.25 0.00800000 61028.5
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 243796.188 243796.188 7.386708 0.00213284 6429.554 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 6.2400 6.365554 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 243796.19 243796.19 1.0000 8.75649380 7.386708 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 2.13261784 60.00 32.22 27.78 0.000 243796.19 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00798508 21.00 0.00798508 50.8195 170580.19 0.00 244596.09 244596.09 8.75649380 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60992.9
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 161779.423 161779.423 4.901973 0.00141532 4266.448 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 4.1408 4.224084 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 161779.42 161779.42 1.0000 5.81099137 4.901973 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 1.41517259 60.00 32.22 27.78 0.000 161779.42 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00798510 21.00 0.00798510 50.8196 113191.77 0.00 162309.46 162309.46 5.81099137 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60991.3
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 242427.914 242427.914 7.345170 0.00212087 6393.501 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 6.2050 6.329828 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 242427.91 242427.91 1.0000 8.70725363 7.345170 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 2.12064879 60.00 32.22 27.78 0.000 242427.91 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00798498 21.00 0.00798498 50.8189 169623.65 0.00 243223.56 243223.56 8.70725363 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60993.3
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 154287.123 154287.123 4.674557 0.00134977 4069.019 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 3.9490 4.028459 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 154287.12 154287.12 1.0000 5.54140404 4.674557 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 1.34963337 60.00 32.22 27.78 0.000 154287.12 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00798418 21.00 0.00798418 50.8139 107953.67 0.00 154793.75 154793.75 5.54140404 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60993.9
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 34360.175 34360.175 1.041625 0.00030060 905.948 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 0.8794 0.897149 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 34360.18 34248.14 1.0000 1.23478318 1.041625 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 0.30056714 60.00 32.22 27.78 0.000 34360.18 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00798726 21.00 0.00798726 50.8332 24035.71 0.00 34471.32 34471.32 1.23478318 12.80 11.60 0.00800000 33059.8 40.18 21.23 0.00800000 60976.7
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 22638.204 22638.204 0.686294 0.00019805 596.876 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 0.5794 0.591087 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 22638.20 22638.20 1.0000 0.81356040 0.686294 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 0.19802868 60.00 32.22 27.78 0.000 22638.20 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00798711 21.00 0.00798711 50.8323 15835.73 0.00 22711.37 22711.37 0.81356040 12.80 11.60 0.00800000 33059.8 40.18 21.23 0.00800000 60975.9
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 34173.684 34173.684 1.035964 0.00029897 901.034 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 0.8747 0.892280 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 34173.68 34173.68 1.0000 1.22807221 1.035964 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 0.29893580 60.00 32.22 27.78 0.000 34173.68 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00798719 21.00 0.00798719 50.8328 23905.33 0.00 34284.25 34284.25 1.22807221 12.80 11.60 0.00800000 33059.8 40.18 21.23 0.00800000 60977.0
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 22169.863 22169.863 0.672082 0.00019395 584.534 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 0.5674 0.578858 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 22169.86 22169.86 1.0000 0.79671189 0.672082 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 0.19393185 60.00 32.22 27.78 0.000 22169.86 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00798684 21.00 0.00798684 50.8306 15508.27 0.00 22241.56 22241.56 0.79671189 12.80 11.60 0.00800000 33059.8 40.18 21.23 0.00800000 60976.5
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 156568.913 -999.000 8.794601 0.00666080 -999.000 -999.0000 1.00000 1.00000 1018.3400 1004.8586 1.1854 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 8.794601 10.42546544   4197.9300 999.8980 79.37095095 12.27 6.67 5.60 1865884.70 8.3911 8.391135 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 156568.91 150583.01 1.0000 10.42546544 8.794601 25.01 15.51 0.00726216 43627.5 10.91 9.59 0.00700000 28609.5 6.66012403 6.67 12.27 5.60 20084.475 136484.44 27.40 0.00700714 16.15 2.53819000 28.8608 24.00 0.00736954 24.00 0.00736954 39.1269 115747.12 0.00 158795.45 158795.45 10.42546544 25.01 15.67 0.00726216 43627.5 10.05 9.62 0.00726216 28396.0
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 164406.210 164406.210 2.638380 0.00143830 2132.271 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 8.794601 10.42546544   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 4.2080 4.292670 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 14:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 164406.21 164406.21 1.0000 3.12763963 2.638380 -39.51 -39.51 0.00036561 -38815.1 12.80 11.46 0.00800000 33059.8 1.43815053 60.00 32.22 27.78 0.000 164406.21 -41.90 0.00006450 -41.90 2.53819000 96.2026 21.00 0.00799385 21.00 0.00799092 50.8561 38018.01 0.00 107512.20 107512.20 3.12763963 2.80 -3.85 0.00036561 3729.8 36.99 13.78 0.00036561 38104.7
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 1470729.922 -999.000 81.847445 0.06256825 -999.000 -999.0000 1.00000 1.00000 1018.3659 1004.8586 1.1854 VAV_MID WITH REHEAT FAN Fan:VariableVolume 81.847445 97.02517698   4197.9300 999.8980 79.37095095 12.27 6.67 5.60 1865884.70 78.8221 78.822122 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 1470729.92 1411984.23 1.0000 97.02517698 81.847445 25.11 15.56 0.00727608 43767.8 10.91 9.59 0.00700000 28609.6 62.56186817 6.67 12.27 5.60 186917.286 1283812.64 27.40 0.00700714 16.15 25.38195000 31.0113 24.00 0.00740651 24.00 0.00740651 39.3209 1050133.54 0.00 1491513.88 1491513.88 97.02517698 25.11 15.72 0.00727608 43767.8 10.01 9.62 0.00727608 28395.4
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 1599918.919 1599918.919 24.554233 0.01399679 20456.875 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 VAV_MID WITH REHEAT FAN Fan:VariableVolume 81.847445 97.02517698   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 40.9500 41.774117 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:20:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1599918.92 1599918.92 1.0000 29.10755309 24.554233 -41.90 -41.90 0.00006450 -41946.5 12.80 11.46 0.00800000 33059.8 13.99536083 60.00 32.22 27.78 0.000 1599918.92 -41.90 0.00006450 -41.90 25.38195000 103.3710 19.01 0.00798309 19.61 0.00797407 55.3190 436019.15 0.00 1026065.20 1026065.20 29.10755309 2.80 -4.37 0.00006450 2975.2 37.88 13.83 0.00006450 38226.0
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 152639.268 -999.000 8.572147 0.00649363 -999.000 -999.0000 1.00000 1.00000 1018.3404 1004.8586 1.1854 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 8.572147 10.16176014   4197.9300 999.8980 79.37095095 12.27 6.67 5.60 1865884.70 8.1805 8.180531 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 Sensible 152639.27 146800.18 1.0000 10.16176014 8.572147 25.01 15.51 0.00726236 43630.5 10.91 9.59 0.00700000 28609.5 6.49296491 6.67 12.27 5.60 19576.451 133062.82 27.40 0.00700714 16.15 2.53819000 29.6097 24.00 0.00737020 24.00 0.00737020 39.1303 115464.19 0.00 154809.63 154809.63 10.16176014 25.01 15.67 0.00726236 43630.5 10.05 9.62 0.00726236 28396.0
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 165266.009 165266.009 2.571644 0.00144582 2122.491 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 8.572147 10.16176014   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 4.2300 4.315120 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 165266.01 165266.01 1.0000 3.04852804 2.571644 -41.15 -41.15 0.00016750 -40942.7 12.80 11.46 0.00800000 33059.8 1.44567165 60.00 32.22 27.78 0.000 165266.01 -41.90 0.00006450 -41.90 2.53819000 98.6991 15.78 0.00798211 17.41 0.00797827 63.4927 61184.44 0.00 106635.33 106635.33 3.04852804 2.80 -4.19 0.00016750 3233.3 37.60 13.83 0.00016750 38212.6
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 85946.595 -999.000 4.933770 0.00365637 -999.000 -999.0000 1.00000 1.00000 1018.6255 1004.8586 1.1854 CAV_BAS FAN Fan:ConstantVolume 4.933770 5.84868433   4197.9300 999.8980 79.37095095 12.27 6.67 5.60 1865884.70 4.6062 4.606211 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 85946.59 80787.85 1.0000 5.84868433 4.933770 24.79 15.57 0.00741573 43800.8 11.40 9.81 0.00700000 29105.8 3.65599384 6.67 12.27 5.60 8365.968 77580.63 26.89 0.00700637 15.97 1.20015641 24.3253 24.00 0.00757073 24.00 0.00757073 40.1826 59047.99 0.00 87164.77 87164.77 5.84868433 24.79 15.73 0.00741573 43800.8 10.16 9.84 0.00741573 28897.5
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 294985.313 294985.313 4.933770 0.00258066 6017.208 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 CAV_BAS FAN Fan:ConstantVolume 4.933770 5.84868433   4197.9300 999.8980 33.50246921 54.44 82.22 27.78 3907007.55 7.5502 7.702110 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 294985.31 294985.31 1.0000 5.84868433 4.933770 -10.19 -13.38 0.00006450 -10081.6 40.00 21.00 0.00800000 60796.0 2.58039695 60.00 32.22 27.78 0.000 294985.31 -41.90 0.00006450 -41.90 1.20015641 24.3253 0.00 0.00006450 22.82 0.00006450 0.3721 0.00 0.00 222227.97 222227.97 5.84868433 12.80 2.07 0.00006450 13024.8 50.61 18.38 0.00006450 51021.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9827.068 6297.926 0.495152 0.00024066 -999.000 -999.0000 -999.00000 -999.00000 1018.0058 1004.8586 1.1854 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:30:00 Sensible 8778.85 8685.88 0.8933 -999.0 -999.0 27.80 16.35 0.00708237 46014.2 12.80 10.42 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 8778.85 21.99 0.00699901 14.15 0.01563279 -999.0000 27.00 0.00708509 27.00 0.00708509 31.4924 8482.55 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 94202.483 60365.043 4.745988 0.00230701 -999.000 -999.0000 -999.00000 -999.00000 1018.0122 1004.8586 1.1854 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 Sensible 84155.48 83226.96 0.8933 -999.0 -999.0 27.79 16.35 0.00708583 46016.0 12.80 10.42 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 84155.48 21.99 0.00699901 14.15 0.15632792 -999.0000 27.00 0.00708879 27.00 0.00708879 31.5088 81307.27 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9517.427 6098.921 0.479504 0.00023308 -999.000 -999.0000 -999.00000 -999.00000 1018.0107 1004.8586 1.1854 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 Sensible 8502.35 8409.40 0.8933 -999.0 -999.0 27.80 16.35 0.00708504 46015.7 12.80 10.42 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 8502.35 21.99 0.00699901 14.15 0.01563279 -999.0000 27.00 0.00708794 27.00 0.00708794 31.5050 8214.78 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9827.068 9827.068 0.495152 0.00024066 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9827.07 9827.07 1.0000 0.58697318 0.495152 -41.90 -41.90 0.00006450 -41946.5 40.00 21.00 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9827.07 -41.90 0.00006450 -41.90 0.01563279 3.1572 0.00 0.00072609 25.29 0.00072609 3.6066 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 94202.483 94202.483 4.745988 0.00230701 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 94202.48 94202.48 1.0000 5.62608094 4.745988 -41.90 -41.90 0.00006450 -41946.5 40.00 21.00 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 94202.48 -41.90 0.00006450 -41.90 0.15632792 3.2939 0.00 0.00092890 23.78 0.00092890 5.0496 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9517.427 9517.427 0.479504 0.00023308 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9517.43 9517.43 1.0000 0.56842319 0.479504 -41.90 -41.90 0.00006450 -41946.5 40.00 21.00 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9517.43 -41.90 0.00006450 -41.90 0.01563279 3.2602 0.00 0.00053768 21.90 0.00053768 3.2779 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 1525.123 1525.123 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.495152 0.58697318   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 1525.12 1525.12 1.0000 0.58697318 0.495152 -1.32 -5.89 0.00070521 432.7 40.00 21.00 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1525.12 -41.90 0.00006450 -41.90 0.01563279 3.1572 0.00 0.00072609 25.29 0.00072609 3.6066 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 15251.225 15251.225 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.745988 5.62608094   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 15251.23 15251.23 1.0000 5.62608094 4.745988 -1.38 -5.58 0.00090043 862.8 40.00 21.00 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 15251.23 -41.90 0.00006450 -41.90 0.15632792 3.2939 0.00 0.00092890 23.78 0.00092890 5.0496 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 1525.123 1525.123 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.479504 0.56842319   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 1525.12 1525.12 1.0000 0.56842319 0.479504 -1.37 -6.25 0.00052225 -67.8 40.00 21.00 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1525.12 -41.90 0.00006450 -41.90 0.01563279 3.2602 0.00 0.00053768 21.90 0.00053768 3.2779 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 8.79 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 81.85 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 8.57 -      
CAV_BAS_OA_CONTROLLER DifferentialDryBulb 0.00 4.93 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT BASEMENT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 1127.00 2897.50 13.50
CORE_BOTTOM 965.33 3167.33 12.00
CORE_MID 1403.33 4166.67 900.17
CORE_TOP 2908.83 4644.17 2515.33
PERIMETER_BOT_ZN_3 2614.50 4130.17 1788.33
PERIMETER_BOT_ZN_2 3068.17 3835.33 1958.50
PERIMETER_BOT_ZN_1 3130.67 3704.33 1873.00
PERIMETER_BOT_ZN_4 2414.33 3274.33 765.67
PERIMETER_MID_ZN_3 3425.67 4531.00 2889.67
PERIMETER_MID_ZN_2 3111.83 3555.00 2293.00
PERIMETER_MID_ZN_1 3476.83 3950.67 2349.00
PERIMETER_MID_ZN_4 3557.50 4204.67 2645.83
PERIMETER_TOP_ZN_3 3825.00 4832.83 3409.83
PERIMETER_TOP_ZN_2 4040.83 4353.00 3125.50
PERIMETER_TOP_ZN_1 3842.00 4316.17 2879.67
PERIMETER_TOP_ZN_4 3905.17 4521.33 3113.17
DATACENTER_BOT_ZN_6 5530.83 63.50 59.17
DATACENTER_MID_ZN_6 3627.50 510.33 17.67
DATACENTER_TOP_ZN_6 3102.33 1067.67 89.17
DATACENTER_BASEMENT_ZN_6 5943.00 5511.83 5511.83
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5943.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 33.83 0.00 2.17
CORE_BOTTOM 0.00 0.17 0.00 0.00
CORE_MID 4.00 0.00 1.67 0.00
CORE_TOP 65.33 0.00 16.00 0.00
PERIMETER_BOT_ZN_3 4.33 9.00 0.33 0.00
PERIMETER_BOT_ZN_2 7.50 13.33 0.00 9.00
PERIMETER_BOT_ZN_1 10.33 17.33 0.00 17.00
PERIMETER_BOT_ZN_4 0.83 69.67 0.00 16.83
PERIMETER_MID_ZN_3 175.83 4.67 72.33 0.00
PERIMETER_MID_ZN_2 79.50 12.67 10.67 10.17
PERIMETER_MID_ZN_1 59.50 18.17 4.83 17.83
PERIMETER_MID_ZN_4 49.83 17.17 3.50 5.50
PERIMETER_TOP_ZN_3 522.67 1.50 227.00 0.00
PERIMETER_TOP_ZN_2 292.67 9.33 70.83 8.17
PERIMETER_TOP_ZN_1 241.83 13.00 54.33 12.33
PERIMETER_TOP_ZN_4 204.67 14.17 47.83 4.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 556.83 170.00 232.83 67.67
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.91 149.60 6779.02 0.951 0.000 0.000 0.000
CORE_BOTTOM 55.60 134.35 6849.35 0.783 0.000 0.000 0.000
CORE_MID 55.60 134.35 6849.35 0.643 0.000 0.000 0.000
CORE_TOP 55.60 134.35 6849.35 0.602 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.98 16.87 860.00 0.799 0.007 0.000 0.000
PERIMETER_BOT_ZN_2 4.50 10.87 554.22 1.242 0.007 0.000 0.000
PERIMETER_BOT_ZN_1 6.98 16.87 860.02 1.317 0.007 0.000 0.000
PERIMETER_BOT_ZN_4 4.50 10.87 554.22 1.559 0.007 0.000 0.000
PERIMETER_MID_ZN_3 6.98 16.87 860.00 0.700 0.016 0.000 0.000
PERIMETER_MID_ZN_2 3.93 10.87 554.22 1.138 0.018 0.000 0.000
PERIMETER_MID_ZN_1 6.98 16.87 860.02 1.309 0.016 0.000 0.000
PERIMETER_MID_ZN_4 4.50 10.87 554.22 1.114 0.017 0.000 0.000
PERIMETER_TOP_ZN_3 6.98 16.87 860.00 0.789 0.020 0.000 0.000
PERIMETER_TOP_ZN_2 4.50 10.87 554.22 1.211 0.021 0.000 0.000
PERIMETER_TOP_ZN_1 6.98 16.87 860.02 1.257 0.020 0.000 0.000
PERIMETER_TOP_ZN_4 4.50 10.87 554.22 1.095 0.021 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.429 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.428 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.428 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.46 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.91 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 55.60 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 55.60 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 55.60 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.98 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.50 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 6.98 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.50 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 6.98 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.93 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 6.98 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.50 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 6.98 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.50 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 6.98 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.50 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.46 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 61.91 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 55.60 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 55.60 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 55.60 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 6.98 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.50 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 6.98 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.50 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 6.98 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.93 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 6.98 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.50 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 6.98 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.50 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 6.98 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.50 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.81 1.95 99.34 36.20 0.0156 0.011
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.81 1.95 99.34 36.20 0.1563 0.110
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.81 1.95 99.34 36.20 0.0156 0.011
DATACENTER_BASEMENT_ZN_6   17.46 42.18 1911.37 783.68   0.239
Total Facility   1026.00 2493.19 126016.35 46320.38 1.3877 157.902


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 38476301.40 0.00 38476301.40 0.00 38476301.40 37848132.68 4164.22 2143.18 2452.60 241.72
CORE_BOTTOM 33312318.26 0.00 33312318.26 0.00 33312318.26 33990283.35 5370.24 58.84 3330.92 482.00
CORE_MID 0.26E+09 0.00 0.26E+09 0.00 0.26E+09 0.34E+09 6643.02 23.98 2093.00 437.57
CORE_TOP 24553631.90 0.00 24553631.90 0.00 24553631.90 33990283.35 6930.17 18.91 1810.92 315.32
PERIMETER_BOT_ZN_3 4276225.75 0.00 4276225.75 72145.69 4348371.45 4267819.30 6319.34 24.56 2416.10 482.00
PERIMETER_BOT_ZN_2 4259346.79 0.00 4259346.79 48097.10 4307443.89 2750345.05 3710.90 11.91 5037.19 482.00
PERIMETER_BOT_ZN_1 6973211.32 0.00 6973211.32 72145.69 7045357.01 4267912.63 3708.14 5.69 5046.17 482.00
PERIMETER_BOT_ZN_4 5366976.81 0.00 5366976.81 48097.10 5415073.91 2750345.05 3646.44 5.48 5108.08 482.00
PERIMETER_MID_ZN_3 36277777.45 0.00 36277777.45 169203.33 36446980.78 42678193.03 6375.20 45.80 2339.00 437.57
PERIMETER_MID_ZN_2 41485836.14 0.00 41485836.14 112802.15 41598638.29 27503450.52 4041.08 3.94 4714.98 1346.57
PERIMETER_MID_ZN_1 67199096.48 0.00 67199096.48 169203.33 67368299.81 42679126.28 4047.33 1.47 4711.20 437.57
PERIMETER_MID_ZN_4 37239086.80 0.00 37239086.80 112802.15 37351888.94 27503450.52 4041.99 1.63 4716.38 437.57
PERIMETER_TOP_ZN_3 4051616.75 0.00 4051616.75 210085.80 4261702.55 4267819.30 4149.48 3.47 4607.05 315.32
PERIMETER_TOP_ZN_2 3978903.80 0.00 3978903.80 140057.11 4118960.91 2750345.05 4127.96 1.81 4630.24 315.32
PERIMETER_TOP_ZN_1 6405033.12 0.00 6405033.12 210085.80 6615118.93 4267912.63 4127.12 2.53 4630.34 315.32
PERIMETER_TOP_ZN_4 3619893.13 0.00 3619893.13 140057.11 3759950.24 2750345.05 4123.00 1.77 4635.23 315.32
DATACENTER_BOT_ZN_6 244303.03 0.00 244303.03 0.00 244303.03 389144.62 4419.00 504.00 3837.00 0.00
DATACENTER_MID_ZN_6 2443030.26 0.00 2443030.26 0.00 2443030.26 3891446.16 4419.00 504.00 3837.00 0.00
DATACENTER_TOP_ZN_6 244303.03 0.00 244303.03 0.00 244303.03 389144.62 4419.00 504.00 3837.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00 0.00 8423799.00 8760.00 0.00 0.00 0.00
Total Facility 0.46E+10 0.00 0.46E+10 6580880.97 0.46E+10 0.50E+10 8760.00 2544.74 5217.86 1879.61


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.7462 0.0000 1.7462 0.0000 1.7462 1.2002 1449.30 2140.50 2353.20
CORE_BOTTOM 1.4539 0.0000 1.4539 0.0000 1.4539 1.0778 2875.12 52.57 3015.31
CORE_MID 11.9501 0.0000 11.9501 0.0000 11.9501 10.7782 3932.55 22.63 1987.82
CORE_TOP 1.1203 0.0000 1.1203 0.0000 1.1203 1.0778 4189.31 18.57 1735.11
PERIMETER_BOT_ZN_3 0.1867 0.0000 0.1867 0.0016 0.1883 0.1353 3820.93 19.59 2102.48
PERIMETER_BOT_ZN_2 0.1870 0.0000 0.1870 0.0011 0.1881 0.0872 1264.02 9.97 4669.01
PERIMETER_BOT_ZN_1 0.3076 0.0000 0.3076 0.0016 0.3093 0.1353 1260.08 3.66 4679.26
PERIMETER_BOT_ZN_4 0.2345 0.0000 0.2345 0.0011 0.2356 0.0872 1223.37 3.08 4716.55
PERIMETER_MID_ZN_3 1.6376 0.0000 1.6376 0.0038 1.6414 1.3533 3665.59 45.01 2232.40
PERIMETER_MID_ZN_2 1.7152 0.0000 1.7152 0.0027 1.7179 0.8721 1344.96 3.63 3685.42
PERIMETER_MID_ZN_1 3.0594 0.0000 3.0594 0.0038 3.0632 1.3533 1350.39 1.44 4591.17
PERIMETER_MID_ZN_4 1.6787 0.0000 1.6787 0.0025 1.6813 0.8721 1345.05 1.56 4596.40
PERIMETER_TOP_ZN_3 0.1848 0.0000 0.1848 0.0047 0.1895 0.1353 1413.82 3.25 4525.93
PERIMETER_TOP_ZN_2 0.1824 0.0000 0.1824 0.0031 0.1856 0.0872 1393.96 1.78 4547.25
PERIMETER_TOP_ZN_1 0.2939 0.0000 0.2939 0.0047 0.2987 0.1353 1392.95 2.51 4547.54
PERIMETER_TOP_ZN_4 0.1650 0.0000 0.1650 0.0031 0.1682 0.0872 1388.97 1.72 4552.31
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0130 1602.00 504.00 3837.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1296 1602.00 504.00 3837.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0130 1602.00 504.00 3837.00
DATACENTER_BASEMENT_ZN_6 0.0000 0.0000 0.0000 0.0000 0.0000 0.2805 5943.00 0.00 0.00
Total Facility 207.6377 0.0000 207.6377 0.1498 207.7875 158.1399 5943.00 2527.04 4767.35


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 76149313.19 0.00 76149313.19 48026705.38 3669.59 5.65 5084.76 482.00
VAV_MID WITH REHEAT 0.63E+09 0.00 0.63E+09 0.48E+09 4044.31 3.98 4711.71 437.57
VAV_TOP WITH REHEAT 59877133.38 0.00 59877133.38 48026705.38 4125.05 2.11 4632.84 314.80
CAV_BAS 54069450.45 0.00 54069450.45 37848132.68 4090.09 4.00 4665.91 241.72
AIRLOOP DATACENTER BOT 343310.81 0.00 343310.81 389144.62 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 3433108.15 0.00 3433108.15 3891446.16 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 343310.81 0.00 343310.81 389144.62 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 3.3301 0.0000 3.3301 1.5229 1233.06 1.97 4707.97
VAV_MID WITH REHEAT 28.3999 0.0000 28.3999 15.2292 1346.25 3.98 4592.77
VAV_TOP WITH REHEAT 2.7353 0.0000 2.7353 1.5229 1390.88 1.94 4550.18
CAV_BAS 2.4538 0.0000 2.4538 1.2002 1415.15 1.31 4526.54
AIRLOOP DATACENTER BOT 0.0160 0.0000 0.0160 0.0130 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1605 0.0000 0.1605 0.1296 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0160 0.0000 0.0160 0.0130 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 0.24 2986.72 0.00 0.00 0.00 2369.63 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 0.03 2831.16 0.00 0.00 0.00 2473.15 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 0.03 2425.41 0.00 0.00 0.00 2674.50 0.00 0.00 0.00
CAV_BAS 0.00 0.00 2747.68 0.00 0.00 0.00 2131.61 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 0.0000 5.6363 0.0000 0.0000 0.0000 2.3952 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 0.0000 46.6319 0.0000 0.0000 0.0000 23.1247 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 0.0000 4.7524 0.0000 0.0000 0.0000 2.3290 0.0000 0.0000 0.0000
CAV_BAS 0.0000 0.0000 4.3864 0.0000 0.0000 0.0000 1.6870 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0220 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2197 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0220 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 7
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1360
Defaulted Fields 1169
Fields with Defaults 3900
Autosized Fields 317
Autosizable Fields 395
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 22179.67 271922.07 28-MAY-04:00 1521573.26 11-AUG-15:40
Electricity:Building 16749.51 216770.18 07-MAY-17:10 977223.71 01-DEC-08:10
Electricity:Zone:BASEMENT 559.97 14115.26 01-JAN-00:10 25295.37 02-JAN-08:10
Electricity:SpaceType:GENERAL 16749.51 216770.18 07-MAY-17:10 977223.71 01-DEC-08:10
InteriorLights:Electricity 2073.11 9514.02 19-FEB-11:30 198852.03 02-JAN-08:10
InteriorLights:Electricity:Zone:BASEMENT 135.58 657.72 01-JAN-00:10 11837.83 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 2073.11 9514.02 19-FEB-11:30 198852.03 02-JAN-08:10
LightsWired:InteriorLights:Electricity 2073.11 9514.02 19-FEB-11:30 198852.03 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 135.58 657.72 01-JAN-00:10 11837.83 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 2073.11 9514.02 19-FEB-11:30 198852.03 02-JAN-08:10
Electricity:Zone:CORE_BOTTOM 411.37 5043.91 01-JAN-00:10 27837.83 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 121.76 590.68 01-JAN-00:10 10631.20 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 121.76 590.68 01-JAN-00:10 10631.20 02-JAN-08:10
Electricity:Zone:CORE_MID 4113.71 50438.97 01-JAN-00:10 278377.67 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 1217.58 5906.80 01-JAN-00:10 106312.04 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 1217.58 5906.80 01-JAN-00:10 106312.04 02-JAN-08:10
Electricity:Zone:CORE_TOP 411.37 5043.90 01-JAN-00:10 27837.77 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 121.76 590.68 01-JAN-00:10 10631.20 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 121.76 590.68 01-JAN-00:10 10631.20 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 46.66 594.46 09-APR-17:10 3495.41 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 10.30 35.29 19-FEB-11:30 1334.85 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 10.30 35.29 19-FEB-11:30 1334.85 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_2 29.96 383.09 09-APR-17:10 2252.57 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 6.53 22.74 05-FEB-10:00 860.23 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 6.53 22.74 05-FEB-10:00 860.23 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_1 46.26 594.47 12-MAR-17:10 3495.47 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 9.89 35.29 16-JAN-11:40 1334.88 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 9.89 35.29 16-JAN-11:40 1334.88 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_4 29.95 383.09 12-MAR-17:10 2252.56 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 6.51 22.74 12-FEB-12:30 860.23 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 6.51 22.74 12-FEB-12:30 860.23 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_3 466.70 5944.59 09-APR-17:10 34954.06 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 103.05 352.88 19-FEB-11:20 13348.54 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 103.05 352.88 19-FEB-11:20 13348.54 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_2 299.63 3830.92 09-APR-17:10 22525.72 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 65.28 227.41 05-FEB-10:00 8602.31 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 65.28 227.41 05-FEB-10:00 8602.31 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_1 462.74 5944.68 12-MAR-17:10 34954.68 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 99.08 352.89 16-JAN-11:40 13348.83 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 99.08 352.89 16-JAN-11:40 13348.83 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_4 299.50 3830.90 12-MAR-17:10 22525.63 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 65.15 227.41 05-FEB-13:30 8602.31 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 65.15 227.41 05-FEB-13:30 8602.31 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 46.67 594.46 09-APR-17:10 3495.41 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 10.30 35.29 19-FEB-11:20 1334.85 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 10.30 35.29 19-FEB-11:20 1334.85 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_2 29.96 383.09 09-APR-17:10 2252.57 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 6.53 22.74 05-FEB-10:00 860.23 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 6.53 22.74 05-FEB-10:00 860.23 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_1 46.27 594.47 12-MAR-17:10 3495.47 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 9.91 35.29 16-JAN-11:40 1334.88 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 9.91 35.29 16-JAN-11:40 1334.88 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_4 29.95 383.09 12-MAR-17:10 2252.56 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 6.52 22.74 05-FEB-13:30 860.23 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 6.52 22.74 05-FEB-13:30 860.23 02-JAN-08:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7533.08 95093.58 01-JAN-00:10 382970.28 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 38.23 185.45 01-JAN-00:10 3337.76 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 38.23 185.45 01-JAN-00:10 3337.76 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 157.14 1964.44 01-JAN-00:10 8079.39 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 3.26 15.83 01-JAN-00:10 284.97 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 3.26 15.83 01-JAN-00:10 284.97 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1571.44 19644.38 01-JAN-00:10 80793.90 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 32.64 158.32 01-JAN-00:10 2849.68 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 32.64 158.32 01-JAN-00:10 2849.68 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 157.14 1964.44 01-JAN-00:10 8079.39 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 3.26 15.83 01-JAN-00:10 284.97 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 3.26 15.83 01-JAN-00:10 284.97 02-JAN-08:10
InteriorEquipment:Electricity 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 520.14 8.76 28-JAN-17:10 252519.15 30-JUN-12:20
HeatRejection:Electricity 98.36 0.00 02-JAN-07:10 40140.23 29-JUN-10:50
General:HeatRejection:Electricity 98.36 0.00 02-JAN-07:10 40140.23 29-JUN-10:50
Electricity:HVAC 1498.25 7482.68 15-JAN-20:50 216120.88 21-JUL-14:40
ExteriorEquipment:Electricity 3108.30 43347.20 01-JAN-00:10 177606.57 01-DEC-08:20
Transformer:ExteriorEquipment:Electricity 54.51 979.82 01-JAN-00:10 3387.38 01-DEC-08:20
ElectricityPurchased:Facility 22179.67 271922.07 28-MAY-04:00 1521573.26 11-AUG-15:40
ElectricityPurchased:Plant 22179.67 271922.07 28-MAY-04:00 1521573.26 11-AUG-15:40
Cogeneration:ElectricityPurchased 22179.67 271922.07 28-MAY-04:00 1521573.26 11-AUG-15:40
General:Cogeneration:ElectricityPurchased 22179.67 271922.07 28-MAY-04:00 1521573.26 11-AUG-15:40
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 22179.67 271922.07 28-MAY-04:00 1521573.26 11-AUG-15:40
ElectricityNet:Plant 22179.67 271922.07 28-MAY-04:00 1521573.26 11-AUG-15:40
Cogeneration:ElectricityNet 22179.67 271922.07 28-MAY-04:00 1521573.26 11-AUG-15:40
General:Cogeneration:ElectricityNet 22179.67 271922.07 28-MAY-04:00 1521573.26 11-AUG-15:40
Fans:Electricity 1070.08 6407.74 22-FEB-04:40 187307.75 12-JUL-12:10
General:Fans:Electricity 1070.08 6407.74 22-FEB-04:40 187307.75 12-JUL-12:10
ExteriorLights:Electricity 357.99 0.00 01-JAN-11:20 37611.08 01-JAN-06:10
General:ExteriorLights:Electricity 357.99 0.00 01-JAN-11:20 37611.08 01-JAN-06:10
ComputerHVAC:ExteriorEquipment:Electricity 1199.18 15185.30 01-JAN-00:10 60741.22 31-MAR-23:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
HeatRecovery:Electricity 58.50 0.00 01-JAN-00:10 6524.59 02-JAN-07:10
General:HeatRecovery:Electricity 58.50 0.00 01-JAN-00:10 6524.59 02-JAN-07:10
Cooling:Electricity 507.02 0.00 02-JAN-07:10 195973.17 11-AUG-15:10
General:Cooling:Electricity 507.02 0.00 02-JAN-07:10 195973.17 11-AUG-15:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 229.93 8.76 28-JAN-17:10 44519.74 21-JUL-13:40
General:Pumps:Electricity 229.93 8.76 28-JAN-17:10 44519.74 21-JUL-13:40
WIRED_LTG_ELECTRICITY 58.25 0.00 01-JAN-00:10 5587.74 02-JAN-08:20
WIRED_INT_EQUIP 5334.97 88964.76 31-MAR-23:10 305206.10 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 5233.81 5695.87 02-JAN-06:00 2508292.19 27-FEB-07:10
NaturalGas:Plant 5233.81 5695.87 02-JAN-06:00 2508292.19 27-FEB-07:10
Heating:NaturalGas 4368.38 0.00 01-JAN-00:40 2476903.95 27-FEB-07:10
Boiler:Heating:NaturalGas 4368.38 0.00 01-JAN-00:40 2476903.95 27-FEB-07:10
WaterSystems:NaturalGas 865.42 5695.87 02-JAN-05:30 87751.33 06-APR-11:30
Water Heater:WaterSystems:NaturalGas 865.42 5695.87 02-JAN-05:30 87751.33 06-APR-11:30


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 3064.77 0.00 02-JAN-07:10 1303158.57 21-JUL-14:40
PlantLoopCoolingDemand:HVAC 3064.77 0.00 02-JAN-07:10 1303158.57 21-JUL-14:40
CoolingCoils:PlantLoopCoolingDemand 3064.77 0.00 02-JAN-07:10 1303158.57 21-JUL-14:40
DistrictCooling:Facility 7145.61 83089.46 16-JAN-06:00 370149.39 28-AUG-16:00
DistrictCooling:HVAC 7145.61 83089.46 16-JAN-06:00 370149.39 28-AUG-16:00
Cooling:DistrictCooling 7145.61 83089.46 16-JAN-06:00 370149.39 28-AUG-16:00
General:Cooling:DistrictCooling 7145.61 83089.46 16-JAN-06:00 370149.39 28-AUG-16:00


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 3329.77 0.00 01-JAN-00:10 0.00 21-JUL-15:50
Water:Plant 3329.77 0.00 01-JAN-00:10 0.00 21-JUL-15:50
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Facility 3329.77 0.00 01-JAN-00:10 0.00 21-JUL-15:50
MainsWater:Plant 3329.77 0.00 01-JAN-00:10 0.00 21-JUL-15:50
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 1049.60 0.00 01-JAN-00:10 0.00 21-JUL-15:50
General:HeatRejection:Water 1049.60 0.00 01-JAN-00:10 0.00 21-JUL-15:50
HeatRejection:MainsWater 1049.60 0.00 01-JAN-00:10 0.00 21-JUL-15:50
General:HeatRejection:MainsWater 1049.60 0.00 01-JAN-00:10 0.00 21-JUL-15:50


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 35496.15 89413.63 02-JAN-06:00 6898556.12 11-AUG-15:10
EnergyTransfer:Building 17256.59 87547.25 14-JAN-18:10 1525328.25 04-DEC-06:20
EnergyTransfer:Zone:BASEMENT 533.38 0.00 01-JAN-00:10 67407.92 05-SEP-05:10
Heating:EnergyTransfer 1751.31 0.00 01-FEB-22:10 1342992.46 02-JAN-06:20
Heating:EnergyTransfer:Zone:BASEMENT 2.58 0.00 01-JAN-00:10 13325.41 29-JUL-16:10
General:Heating:EnergyTransfer 1751.31 0.00 01-FEB-22:10 1342992.46 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:BASEMENT 2.58 0.00 01-JAN-00:10 13325.41 29-JUL-16:10
Cooling:EnergyTransfer 15505.28 83090.87 16-JAN-05:30 1460988.92 11-AUG-15:30
Cooling:EnergyTransfer:Zone:BASEMENT 530.80 0.00 01-JAN-00:10 67407.92 05-SEP-05:10
General:Cooling:EnergyTransfer 15505.28 83090.87 16-JAN-05:30 1460988.92 11-AUG-15:30
General:Cooling:EnergyTransfer:Zone:BASEMENT 530.80 0.00 01-JAN-00:10 67407.92 05-SEP-05:10
EnergyTransfer:Zone:CORE_BOTTOM 488.47 0.00 01-JAN-00:10 46518.00 24-JUL-09:20
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 488.47 0.00 01-JAN-00:10 46518.00 24-JUL-09:20
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 488.47 0.00 01-JAN-00:10 46518.00 24-JUL-09:20
EnergyTransfer:Zone:CORE_MID 3465.67 0.00 01-JAN-00:40 457865.18 02-JAN-05:10
Heating:EnergyTransfer:Zone:CORE_MID 38.68 0.00 01-JAN-00:20 457865.18 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:CORE_MID 38.68 0.00 01-JAN-00:20 457865.18 02-JAN-05:10
Cooling:EnergyTransfer:Zone:CORE_MID 3426.98 0.00 01-JAN-00:40 394357.15 17-MAY-05:10
General:Cooling:EnergyTransfer:Zone:CORE_MID 3426.98 0.00 01-JAN-00:40 394357.15 17-MAY-05:10
EnergyTransfer:Zone:CORE_TOP 314.89 0.00 01-JAN-00:40 64714.30 27-NOV-05:30
Heating:EnergyTransfer:Zone:CORE_TOP 64.90 0.00 01-JAN-00:40 64714.30 27-NOV-05:30
General:Heating:EnergyTransfer:Zone:CORE_TOP 64.90 0.00 01-JAN-00:40 64714.30 27-NOV-05:30
Cooling:EnergyTransfer:Zone:CORE_TOP 249.99 0.00 01-JAN-00:20 41089.95 21-JUL-15:20
General:Cooling:EnergyTransfer:Zone:CORE_TOP 249.99 0.00 01-JAN-00:20 41089.95 21-JUL-15:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 53.54 0.00 01-JAN-00:10 10784.31 11-JUL-05:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 5.62 0.00 01-JAN-00:10 9082.12 12-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 5.62 0.00 01-JAN-00:10 9082.12 12-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 47.92 0.00 01-JAN-00:10 10784.31 11-JUL-05:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 47.92 0.00 01-JAN-00:10 10784.31 11-JUL-05:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 52.68 0.00 01-JAN-00:10 13465.76 11-JUL-08:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 5.44 0.00 01-JAN-00:10 6843.04 12-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 5.44 0.00 01-JAN-00:10 6843.04 12-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 47.24 0.00 01-JAN-00:10 13465.76 11-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 47.24 0.00 01-JAN-00:10 13465.76 11-JUL-08:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 88.30 0.00 01-JAN-00:10 20149.88 10-AUG-13:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 8.78 0.00 01-JAN-00:10 11555.65 30-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 8.78 0.00 01-JAN-00:10 11555.65 30-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 79.51 0.00 01-JAN-00:10 20149.88 10-AUG-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 79.51 0.00 01-JAN-00:10 20149.88 10-AUG-13:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 69.69 0.00 01-JAN-00:10 13590.10 10-AUG-17:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.52 0.00 01-JAN-00:10 4596.89 13-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.52 0.00 01-JAN-00:10 4596.89 13-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 69.17 0.00 01-JAN-00:10 13590.10 10-AUG-17:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 69.17 0.00 01-JAN-00:10 13590.10 10-AUG-17:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 648.40 0.00 01-JAN-00:40 110947.10 30-JAN-04:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 342.39 0.00 01-JAN-00:40 110947.10 30-JAN-04:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 342.39 0.00 01-JAN-00:40 110947.10 30-JAN-04:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 306.01 0.00 01-JAN-00:10 104453.79 11-JUL-05:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 306.01 0.00 01-JAN-00:10 104453.79 11-JUL-05:10
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 613.89 0.00 01-JAN-00:40 143005.18 07-JUL-08:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 221.11 0.00 01-JAN-00:40 127286.03 27-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 221.11 0.00 01-JAN-00:40 127286.03 27-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 392.79 0.00 01-JAN-00:20 143005.18 07-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 392.79 0.00 01-JAN-00:20 143005.18 07-JUL-08:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 950.74 0.00 01-JAN-00:40 214926.78 10-AUG-13:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 258.17 0.00 01-JAN-00:40 189571.92 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 258.17 0.00 01-JAN-00:40 189571.92 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 692.57 0.00 01-JAN-00:20 214926.78 10-AUG-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 692.57 0.00 01-JAN-00:20 214926.78 10-AUG-13:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 506.98 0.00 01-JAN-00:40 117006.30 06-JUL-17:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 167.66 0.00 01-JAN-00:40 116342.45 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 167.66 0.00 01-JAN-00:40 116342.45 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 339.32 0.00 01-JAN-00:20 117006.30 06-JUL-17:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 339.32 0.00 01-JAN-00:20 117006.30 06-JUL-17:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 104.59 0.00 01-JAN-00:40 15012.33 27-FEB-04:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 77.53 0.00 01-JAN-00:40 15012.33 27-FEB-04:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 77.53 0.00 01-JAN-00:40 15012.33 27-FEB-04:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 27.07 0.00 01-JAN-00:10 8423.09 11-JUL-05:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 27.07 0.00 01-JAN-00:10 8423.09 11-JUL-05:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 81.76 0.00 01-JAN-00:40 14914.65 30-JAN-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 47.47 0.00 01-JAN-00:40 14914.65 30-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 47.47 0.00 01-JAN-00:40 14914.65 30-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 34.29 0.00 01-JAN-00:10 14317.92 07-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 34.29 0.00 01-JAN-00:10 14317.92 07-JUL-08:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 120.30 0.00 01-JAN-00:40 23204.61 30-JAN-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 61.24 0.00 01-JAN-00:40 23204.61 30-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 61.24 0.00 01-JAN-00:40 23204.61 30-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 59.06 0.00 01-JAN-00:20 21802.35 10-AUG-13:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 59.06 0.00 01-JAN-00:20 21802.35 10-AUG-13:50
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 68.77 0.00 01-JAN-00:40 15474.59 30-JAN-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 39.35 0.00 01-JAN-00:40 15474.59 30-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 39.35 0.00 01-JAN-00:40 15474.59 30-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 29.42 0.00 01-JAN-00:20 12026.39 11-JUL-17:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 29.42 0.00 01-JAN-00:20 12026.39 11-JUL-17:40
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 45.71 0.00 01-JAN-00:10 7613.18 24-JUL-07:10
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 11.12 0.00 01-JAN-00:10 4914.47 02-JAN-10:40
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 11.12 0.00 01-JAN-00:10 4914.47 02-JAN-10:40
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 34.59 0.00 01-JAN-00:10 7613.18 24-JUL-07:10
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 34.59 0.00 01-JAN-00:10 7613.18 24-JUL-07:10
EnergyTransfer:Zone:MIDFLOOR_PLENUM 498.94 0.00 01-JAN-00:40 182021.05 02-JAN-06:20
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 265.99 0.00 01-JAN-00:40 182021.05 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 265.99 0.00 01-JAN-00:40 182021.05 02-JAN-06:20
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 232.95 0.00 01-JAN-00:10 57758.69 24-JUL-15:30
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 232.95 0.00 01-JAN-00:10 57758.69 24-JUL-15:30
EnergyTransfer:Zone:TOPFLOOR_PLENUM 148.14 0.00 01-JAN-00:40 32076.15 27-FEB-05:30
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 124.16 0.00 01-JAN-00:40 32076.15 27-FEB-05:30
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 124.16 0.00 01-JAN-00:40 32076.15 27-FEB-05:30
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 23.98 0.00 01-JAN-00:10 13296.40 21-JUL-14:40
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 23.98 0.00 01-JAN-00:10 13296.40 21-JUL-14:40
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 128.43 5.54 12-JAN-02:40 8268.29 20-APR-18:50
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.08 0.00 02-JAN-07:10 280.93 14-JAN-18:20
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.08 0.00 02-JAN-07:10 280.93 14-JAN-18:20
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 128.36 0.00 01-JAN-00:10 8268.29 20-APR-18:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 128.36 0.00 01-JAN-00:10 8268.29 20-APR-18:50
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1060.84 11.95 06-JAN-20:00 78479.21 20-APR-18:50
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 7.25 0.00 02-JAN-07:10 5478.71 03-JAN-01:00
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 7.25 0.00 02-JAN-07:10 5478.71 03-JAN-01:00
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1053.58 0.00 01-JAN-00:10 78479.21 20-APR-18:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1053.58 0.00 01-JAN-00:10 78479.21 20-APR-18:50
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 91.50 0.05 25-SEP-08:20 7796.33 20-APR-18:50
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 1.28 0.00 02-JAN-07:10 580.30 12-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 1.28 0.00 02-JAN-07:10 580.30 12-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 90.23 0.00 01-JAN-00:10 7796.33 20-APR-18:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 90.23 0.00 01-JAN-00:10 7796.33 20-APR-18:50
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7120.98 83089.46 16-JAN-06:00 367550.47 28-AUG-16:00
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7120.98 83089.46 16-JAN-06:00 367550.47 28-AUG-16:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7120.98 83089.46 16-JAN-06:00 367550.47 28-AUG-16:00
PlantLoopHeatingDemand:Facility 3912.10 0.00 01-JAN-00:40 2119697.84 27-FEB-07:10
PlantLoopHeatingDemand:Plant 538.62 0.00 01-JAN-00:10 61986.78 30-MAR-11:10
WaterSystems:PlantLoopHeatingDemand 538.62 0.00 01-JAN-00:10 61986.78 30-MAR-11:10
General:WaterSystems:PlantLoopHeatingDemand 538.62 0.00 01-JAN-00:10 61986.78 30-MAR-11:10
EnergyTransfer:HVAC 10069.25 126.57 14-JAN-18:10 2101276.32 27-FEB-07:10
HeatingCoils:EnergyTransfer 3373.47 0.00 01-JAN-00:40 2099093.97 27-FEB-07:10
PlantLoopHeatingDemand:HVAC 3373.47 0.00 01-JAN-00:40 2099093.97 27-FEB-07:10
HeatingCoils:PlantLoopHeatingDemand 3373.47 0.00 01-JAN-00:40 2099093.97 27-FEB-07:10
CoolingCoils:EnergyTransfer 2749.60 0.00 02-JAN-07:10 1288177.42 30-JUN-12:30
DistrictHeating:Facility 0.00 0.00 01-JAN-00:10 13.36 31-MAY-23:40
DistrictHeating:HVAC 0.00 0.00 01-JAN-00:10 13.36 31-MAY-23:40
Heating:DistrictHeating 0.00 0.00 01-JAN-00:10 13.36 31-MAY-23:40
General:Heating:DistrictHeating 0.00 0.00 01-JAN-00:10 13.36 31-MAY-23:40
HeatRecoveryForHeating:EnergyTransfer 3944.51 0.00 01-JAN-00:10 869409.54 26-JAN-18:00
HeatRecoveryForCooling:EnergyTransfer 1.65 0.00 01-JAN-00:10 118067.19 29-JUL-16:00
EnergyTransfer:Plant 8170.31 0.00 01-JAN-00:40 4180997.18 11-AUG-15:10
LoopToLoop:EnergyTransfer 1436.29 -123.19 07-JAN-12:10 1329134.17 11-AUG-15:10
WaterSystems:EnergyTransfer 538.62 0.00 01-JAN-00:10 61986.78 30-MAR-11:10
WaterUse:WaterSystems:EnergyTransfer 538.62 0.00 01-JAN-00:10 61986.78 30-MAR-11:10
Boilers:EnergyTransfer 3355.88 0.00 01-JAN-00:40 2063366.57 27-FEB-07:10
Chillers:EnergyTransfer 1323.83 0.00 01-JAN-00:10 1318524.80 11-AUG-15:10
HeatRejection:EnergyTransfer 1515.68 0.00 01-JAN-00:10 1490494.74 11-AUG-15:10
General:HeatRejection:EnergyTransfer 1515.68 0.00 01-JAN-00:10 1490494.74 11-AUG-15:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 2.582 -530.798 0.000 0.000 94.051 135.577 424.397 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -125.809
CORE_BOTTOM 0.000 0.000 0.000 -488.470 0.000 0.000 84.211 121.758 289.614 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.000 -7.113
CORE_MID 0.000 0.000 38.684 -3426.983 0.000 0.000 884.629 1217.578 2896.128 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1610.036
CORE_TOP 0.000 0.000 64.898 -249.988 0.000 0.000 92.406 121.758 289.613 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -318.687
PERIMETER_BOT_ZN_3 0.000 0.000 5.617 -47.923 0.000 0.000 11.351 10.295 36.365 19.042 0.000 0.001 38.769 0.000 -71.679 0.000 -1.840 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 5.442 -47.237 0.000 0.000 7.308 6.529 23.435 44.596 0.000 0.001 6.095 0.000 -44.952 0.000 -1.217 -0.001
PERIMETER_BOT_ZN_1 0.000 0.000 8.784 -79.514 0.000 0.000 11.310 9.894 36.366 87.759 0.000 0.001 0.009 0.000 -63.811 0.000 -1.834 -8.955
PERIMETER_BOT_ZN_4 0.000 0.000 0.518 -69.172 0.000 0.000 7.161 6.513 23.435 30.341 0.000 0.001 51.682 0.000 -49.173 0.000 -1.306 0.000
PERIMETER_MID_ZN_3 0.000 0.000 342.392 -306.009 0.000 0.000 116.660 103.051 363.654 194.426 0.000 0.022 0.008 0.000 -675.248 0.000 -40.451 -98.496
PERIMETER_MID_ZN_2 0.000 0.000 221.104 -392.787 0.000 0.000 54.826 65.281 234.352 446.298 0.000 0.014 0.005 0.000 -430.322 0.000 -27.374 -171.393
PERIMETER_MID_ZN_1 0.000 0.000 258.167 -692.569 0.000 0.000 114.567 99.080 363.660 877.175 0.000 0.019 0.008 0.000 -622.572 0.000 -42.097 -355.428
PERIMETER_MID_ZN_4 0.000 0.000 167.658 -339.321 0.000 0.000 75.021 65.151 234.351 309.445 0.000 0.012 0.004 0.000 -449.659 0.000 -28.012 -34.648
PERIMETER_TOP_ZN_3 0.000 0.000 77.526 -27.067 0.000 0.000 11.894 10.305 36.365 20.043 0.000 0.003 0.001 0.000 -64.677 0.000 -4.780 -59.612
PERIMETER_TOP_ZN_2 0.000 0.000 47.473 -34.290 0.000 0.000 7.537 6.528 23.435 45.003 0.000 0.002 0.001 0.000 -41.392 0.000 -3.259 -51.036
PERIMETER_TOP_ZN_1 0.000 0.000 61.240 -59.062 0.000 0.000 11.643 9.908 36.366 88.387 0.000 0.002 0.001 0.000 -59.684 0.000 -4.997 -83.803
PERIMETER_TOP_ZN_4 0.000 0.000 39.353 -29.415 0.000 0.000 7.612 6.515 23.435 31.225 0.000 0.001 0.001 0.000 -43.273 0.000 -3.337 -32.117
DATACENTER_BOT_ZN_6 0.000 0.000 0.077 -128.356 0.000 0.000 0.951 3.264 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -29.816
DATACENTER_MID_ZN_6 0.000 0.000 7.253 -1053.582 0.000 0.000 9.595 32.637 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -534.709
DATACENTER_TOP_ZN_6 0.000 0.000 1.276 -90.227 0.000 0.000 0.969 3.264 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -69.161
DATACENTER_BASEMENT_ZN_6 0.000 -7120.977 0.000 0.000 0.000 0.000 20.569 38.227 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -432.676
GROUNDFLOOR_PLENUM 11.118 -34.590 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.001 27.304 0.000 0.000 0.000 -3.834 -0.000
MIDFLOOR_PLENUM 265.991 -232.949 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.024 33.038 0.000 0.000 0.000 -66.105 -0.004
TOPFLOOR_PLENUM 124.156 -23.981 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.002 0.000 0.000 0.000 0.000 -7.134 -93.043
Total Facility 401.266 -7412.497 1350.046 -8092.771 0.000 0.000 1624.269 2073.110 14676.396 2193.743 0.000 0.105 156.926 0.000 -2616.442 0.000 -237.577 -4116.541


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 31-JUL-03:02 0.00 0.00 0.00 -100098.08 0.00 0.00 0.00 657.72 13457.54 0.00 0.00 0.00 85982.81 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 05-SEP-03:02 0.00 0.00 0.00 -82912.60 0.00 0.00 0.00 590.68 5937.65 0.00 0.00 0.00 76384.28 0.00 -0.00 0.00 0.00 0.00
CORE_MID 05-JUL-03:02 0.00 0.00 0.00 -754403.16 0.00 0.00 0.00 5906.80 59376.23 0.00 0.00 0.00 689120.14 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 24-JUN-05:04 0.00 0.00 0.00 -72293.79 0.00 0.00 840.00 1181.21 7647.36 0.00 0.00 0.00 62625.22 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 29-JUN-05:03 0.00 0.00 0.00 -13348.34 0.00 0.00 95.61 70.57 960.25 9174.41 0.00 0.00 3059.27 0.00 -0.00 0.00 -11.76 0.00
PERIMETER_BOT_ZN_2 23-JUL-09:51 0.00 0.00 0.00 -20692.76 0.00 0.00 21.86 22.74 464.11 14341.68 0.00 0.00 5860.32 0.00 -0.00 0.00 -17.96 0.00
PERIMETER_BOT_ZN_1 23-JUL-13:11 0.00 0.00 0.00 -32295.71 0.00 0.00 32.16 35.29 720.19 23455.85 0.00 0.00 8066.37 0.00 -0.00 0.00 -14.16 0.00
PERIMETER_BOT_ZN_4 23-JUL-15:11 0.00 0.00 0.00 -23712.13 0.00 0.00 22.87 22.74 464.11 9134.81 0.00 0.00 14073.35 0.00 -0.00 0.00 -5.75 0.00
PERIMETER_MID_ZN_3 11-JUL-04:52 0.00 0.00 0.00 -126990.79 0.00 0.00 0.00 705.67 7455.61 116003.02 0.00 0.00 4062.51 0.00 -0.00 0.00 -1236.02 0.00
PERIMETER_MID_ZN_2 23-JUL-09:51 0.00 0.00 0.00 -225566.98 0.00 0.00 203.00 227.41 4641.14 142561.08 0.00 0.00 78385.38 0.00 -0.00 0.00 -451.02 0.00
PERIMETER_MID_ZN_1 23-JUL-13:51 0.00 0.00 0.00 -344771.22 0.00 0.00 299.82 352.89 7201.95 214269.52 0.00 0.00 123020.12 0.00 -0.00 0.00 -373.08 0.00
PERIMETER_MID_ZN_4 11-JUN-17:32 0.00 0.00 0.00 -213788.07 0.00 0.00 0.00 227.41 3603.49 105915.09 0.00 0.00 105985.45 0.00 -0.00 0.00 -1943.37 0.00
PERIMETER_TOP_ZN_3 11-JUL-05:02 0.00 0.00 0.00 -15226.80 0.00 0.00 96.67 70.57 960.25 11116.75 0.00 0.00 3017.59 0.00 -0.00 0.00 -35.03 0.00
PERIMETER_TOP_ZN_2 21-MAY-09:12 0.00 0.00 0.00 -21234.32 0.00 0.00 22.60 22.74 464.11 16111.74 0.00 0.00 4943.25 0.00 -0.00 0.00 -330.12 0.00
PERIMETER_TOP_ZN_1 27-AUG-14:01 0.00 0.00 0.00 -34950.30 0.00 0.00 32.26 35.29 720.19 20393.39 0.00 0.00 13925.89 0.00 -0.00 0.00 -156.72 0.00
PERIMETER_TOP_ZN_4 11-JUN-16:42 0.00 0.00 0.00 -22327.34 0.00 0.00 21.88 22.74 464.11 14196.72 0.00 0.00 7866.05 0.00 -0.00 0.00 -244.16 0.00
DATACENTER_BOT_ZN_6 20-APR-18:50 0.00 0.00 0.00 -8267.76 0.00 0.00 10.62 94.99 7794.42 0.00 0.00 0.00 367.73 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 20-APR-18:50 0.00 0.00 0.00 -78473.98 0.00 0.00 106.16 949.88 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -526.28
DATACENTER_TOP_ZN_6 20-APR-18:50 0.00 0.00 0.00 -7795.82 0.00 0.00 10.62 94.99 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -104.21
DATACENTER_BASEMENT_ZN_6 28-AUG-16:00 0.00 -367550.47 0.00 0.00 0.00 0.00 2183.10 3337.76 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -17602.91
GROUNDFLOOR_PLENUM 31-JUL-05:15 0.00 -8556.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8580.03 0.00 -0.00 0.00 -23.77 0.00
MIDFLOOR_PLENUM 12-JAN-04:01 0.00 -77538.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85420.39 0.00 -0.00 0.00 -7881.92 0.00
TOPFLOOR_PLENUM 21-JUL-14:40 0.00 -13298.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.42 13291.66 0.00 -0.00 0.00 0.00 0.00
Total Facility 01-AUG-05:02 0.00 -347997.60 0.00 -1442388.03 0.00 0.00 15871.35 19282.32 616289.16 58163.26 0.00 0.00 1100490.69 0.00 -18139.50 0.00 -1571.65 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 29-JUL-16:03 0.00 0.00 14241.00 0.00 0.00 0.00 484.19 657.72 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -28840.45
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID 02-JAN-04:01 0.00 0.00 531590.79 0.00 0.00 0.00 0.00 5906.80 59376.23 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -596873.82
CORE_TOP 30-JAN-03:32 0.00 0.00 72510.78 0.00 0.00 0.00 0.00 590.68 5937.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -79039.09
PERIMETER_BOT_ZN_3 13-JAN-04:01 0.00 0.00 11450.68 0.00 0.00 0.00 0.00 74.17 745.56 0.00 0.00 0.00 0.00 0.00 -5692.74 0.00 0.00 -6577.67
PERIMETER_BOT_ZN_2 13-JAN-04:01 0.00 0.00 13523.05 0.00 0.00 0.00 0.00 47.80 480.47 0.00 0.00 0.00 0.00 0.00 -3763.21 0.00 0.00 -10288.10
PERIMETER_BOT_ZN_1 30-JAN-04:01 0.00 0.00 21862.11 0.00 0.00 0.00 0.00 74.17 745.57 0.00 0.00 0.00 0.00 0.00 -4815.11 0.00 -267.99 -17598.75
PERIMETER_BOT_ZN_4 12-JAN-05:01 0.00 0.00 11255.27 0.00 0.00 0.00 0.00 95.58 480.46 0.00 0.00 0.00 0.00 0.00 -4208.94 0.00 0.00 -7622.37
PERIMETER_MID_ZN_3 01-JAN-19:22 0.00 0.00 121234.33 0.00 0.00 0.00 0.00 741.66 5591.71 0.00 0.00 0.00 0.00 0.00 -33963.42 0.00 -6522.96 -87081.31
PERIMETER_MID_ZN_2 01-JAN-19:22 0.00 0.00 173827.01 0.00 0.00 0.00 0.00 477.95 3603.51 0.00 0.00 0.00 0.00 0.00 -22643.10 0.00 -4470.53 -150794.84
PERIMETER_MID_ZN_1 01-JAN-19:22 0.00 0.00 259940.00 0.00 0.00 0.00 0.00 741.67 5591.79 0.00 0.00 0.00 0.00 0.00 -33233.21 0.00 -6718.50 -226321.76
PERIMETER_MID_ZN_4 02-JAN-04:01 0.00 0.00 169640.76 0.00 0.00 0.00 0.00 477.95 4804.65 0.00 0.00 0.00 0.00 0.00 -22612.28 0.00 -1899.10 -150411.98
PERIMETER_TOP_ZN_3 30-JAN-03:32 0.00 0.00 16608.39 0.00 0.00 0.00 0.00 74.17 745.56 0.00 0.00 0.00 0.00 0.00 -4547.81 0.00 -756.78 -12123.52
PERIMETER_TOP_ZN_2 30-JAN-03:32 0.00 0.00 18358.17 0.00 0.00 0.00 0.00 47.80 480.47 0.00 0.00 0.00 0.00 0.00 -2965.45 0.00 -511.54 -15409.44
PERIMETER_TOP_ZN_1 30-JAN-03:32 0.00 0.00 28541.09 0.00 0.00 0.00 0.00 74.17 745.57 0.00 0.00 0.00 0.00 0.00 -4460.58 0.00 -770.21 -24130.04
PERIMETER_TOP_ZN_4 30-JAN-03:32 0.00 0.00 19171.10 0.00 0.00 0.00 0.00 47.80 480.46 0.00 0.00 0.00 0.00 0.00 -3053.61 0.00 -515.45 -16130.31
DATACENTER_BOT_ZN_6 12-JAN-22:13 0.00 0.00 542.57 0.00 0.00 0.00 5.22 31.66 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2528.05
DATACENTER_MID_ZN_6 12-JAN-22:13 0.00 0.00 5580.16 0.00 0.00 0.00 57.46 316.62 19486.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -25440.29
DATACENTER_TOP_ZN_6 12-JAN-00:10 0.00 0.00 580.30 0.00 0.00 0.00 0.00 15.83 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2544.73
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 07-MAR-06:01 10664.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -10664.67
MIDFLOOR_PLENUM 02-JAN-06:25 187162.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -727.16 -186435.18
TOPFLOOR_PLENUM 27-FEB-05:22 33457.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -33457.55
Total Facility 02-JAN-06:01 61400.09 13542.17 1358656.29 -13542.17 0.00 0.00 23146.62 22094.05 261414.96 0.00 0.00 0.00 0.00 0.00 -144083.83 0.00 -912.78 -1581715.41



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 10.3609 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 8.7946 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 99.3837 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 81.8474 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 10.2261 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 8.5721 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 4.9338 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 4.9338 0.2433 1.0000 Not calculated 1.2002 0.2433    
AIRLOOP DATACENTER BOT 0.4952 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4952 0.0316 1.0000 Not calculated 0.0156 0.0316    
AIRLOOP DATACENTER MID 4.7460 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.7460 0.0329 1.0000 Not calculated 0.1563 0.0329    
AIRLOOP DATACENTER TOP 0.4795 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4795 0.0326 1.0000 Not calculated 0.0156 0.0326    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 5.1805 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.9454 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 49.6918 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 28.9674 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.1131 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.0153 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 4.9338 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 4.9338 1.0000 1.0000 Not calculated 1.2002 0.2433    
AIRLOOP DATACENTER BOT 0.4952 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4952 1.0000 1.0000 Not calculated 0.0156 0.0316    
AIRLOOP DATACENTER MID 4.7460 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.7460 1.0000 1.0000 Not calculated 0.1563 0.0329    
AIRLOOP DATACENTER TOP 0.4795 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4795 1.0000 1.0000 Not calculated 0.0156 0.0326    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.002360 1.9486 0.000305 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.002360 19.4861 0.000305 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.002360 1.9486 0.000305 36.20 0.0156 1.0000 0.0156 1.000 0.0156


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BOT 0.002360 1.95 0.000305 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.002360 19.49 0.000305 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.002360 1.95 0.000305 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.9338 4.9338 4.9338 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.3529 5.3529 1.8789 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 50.1504 50.1504 18.4052 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.9347 4.9347 1.8653 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8544 0.8544 0.2358 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1150 1.1150 0.2230 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.7004 1.7004 0.3401 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3383 1.3383 0.2677 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.9503 7.9503 2.3056 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.7590 11.7590 2.3518 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 17.6267 17.6267 3.5253 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.8973 11.8973 2.3795 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0416 1.0416 0.3000 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1735 1.1735 0.2347 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8365 1.8365 0.3673 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2397 1.2397 0.2479 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4952 0.4952 0.4952 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.7460 4.7460 4.7460 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4795 0.4795 0.4795 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 10.3609 8.7946 10.3609 2.9454 0.0000 1.0000
VAV_MID WITH REHEAT 99.3837 81.8474 99.3837 28.9674 0.0000 1.0000
VAV_TOP WITH REHEAT 10.2261 8.5721 10.2261 3.0153 0.0000 1.0000
CAV_BAS 4.9338 4.9338 4.9338 4.9338 1.2002 1.0000
AIRLOOP DATACENTER BOT 0.4952 0.4952 0.4952 0.4952 0.0156 1.0000
AIRLOOP DATACENTER MID 4.7460 4.7460 4.7460 4.7460 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4795 0.4795 0.4795 0.4795 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.9338 4.9338 4.9338 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6764 2.6764 1.8789 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 25.0752 25.0752 18.4052 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4674 2.4674 1.8653 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4272 0.4272 0.2358 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5575 0.5575 0.2230 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8502 0.8502 0.3401 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6691 0.6691 0.2677 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.9752 3.9752 2.3056 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.8795 5.8795 2.3518 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 8.8134 8.8134 3.5253 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.9487 5.9487 2.3795 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5208 0.5208 0.3000 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5868 0.5868 0.2347 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9183 0.9183 0.3673 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6199 0.6199 0.2479 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4952 0.4952 0.4952 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.7460 4.7460 4.7460 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4795 0.4795 0.4795 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 5.1805 2.9454 2.9454 2.9454 0.0000 1.0000
VAV_MID WITH REHEAT 49.6918 28.9674 28.9674 28.9674 0.0000 1.0000
VAV_TOP WITH REHEAT 5.1131 3.0153 3.0153 3.0153 0.0000 1.0000
CAV_BAS 4.9338 4.9338 4.9338 4.9338 1.2002 1.0000
AIRLOOP DATACENTER BOT 0.4952 0.4952 0.4952 0.4952 0.0156 1.0000
AIRLOOP DATACENTER MID 4.7460 4.7460 4.7460 4.7460 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4795 0.4795 0.4795 0.4795 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 232.83
Number of hours cooling loads not met 67.67
Number of hours not met 300.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.36
Heating -- Boiler 0.00 0.00 4368.38 2476903.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 507.02 195973.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7145.61 370149.39 0.00 0.00
Interior Lighting -- LightsWired 2073.11 198852.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 357.99 37611.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5334.97 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 54.51 3387.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ComputerHVAC 1199.18 60741.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 1070.08 187307.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 229.93 44519.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 98.36 40140.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 58.50 6524.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 865.42 87751.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 14676.40 22179.67
Natural Gas 0.00 5233.81
Additional 0.00 7145.61
Total 14676.40 34559.09


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 44.76
Space Heating 0.00
Space Cooling 10.95
Fans (All) 23.10
Service Water Heating 0.00
Receptacle Equipment 316.85
Miscellaneous (All) 478.83
Subtotal 478.83


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 94.31
Service Water Heating 18.68
Miscellaneous (All) 112.99
Subtotal 112.99


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.00
Space Heating 12.64
Space Cooling 22.14
Fans (All) 3.10
Service Water Heating 2.50
Receptacle Equipment 42.47
Miscellaneous 11.15


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2362. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4049. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 1565. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8640.00 120.00 0.00 0.00 0.00
CORE_BOTTOM 8760.00 0.00 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8759.83 0.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8752.83 7.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8750.83 9.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8605.17 154.83 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8759.50 0.50 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8741.50 18.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8738.17 21.83 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8739.33 20.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8748.17 11.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8740.17 19.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8741.17 18.83 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 8760.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 8760.00 0.00 0.00 0.00
Average 8361.59 398.41 0.00 0.00 0.00
Sum 192316.67 9163.33 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 368316.17 299.83 0.00 0.00 0.00
CORE_BOTTOM 330813.00 0.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 103395.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 368316.17 103395.00 0.00 0.00 0.00
Average 75826.44 4508.47 0.00 0.00 0.00
Sum 1744008.17 103694.83 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8577.67 182.33 0.00 0.00 0.00
CORE_BOTTOM 8685.67 74.33 0.00 0.00 0.00
CORE_MID 8717.50 42.50 0.00 0.00 0.00
CORE_TOP 8748.17 11.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8752.17 7.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8751.50 8.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8750.67 9.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8629.83 130.17 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8758.00 2.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8741.67 18.33 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8740.33 19.67 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8732.83 27.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8746.67 13.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8742.17 17.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8740.50 19.50 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 8760.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8746.50 13.50 0.00 0.00 0.00
MIDFLOOR_PLENUM 8757.50 2.50 0.00 0.00 0.00
TOPFLOOR_PLENUM 8756.50 3.50 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 8760.00 0.00 0.00 0.00
Average 8352.86 407.14 0.00 0.00 0.00
Sum 192115.83 9364.17 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 368098.00 518.00 0.00 0.00 0.00
CORE_BOTTOM 330678.00 135.00 0.00 0.00 0.00
CORE_MID 330752.00 61.00 0.00 0.00 0.00
CORE_TOP 330798.00 15.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 103395.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 368098.00 103395.00 0.00 0.00 0.00
Average 75807.78 4527.13 0.00 0.00 0.00
Sum 1743579.00 104124.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:06:40

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

For: Environment

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8

For: Environment

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS

For: Environment

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.299613E+11 87457.37 25-JAN-06:01 -22.1 -22.4 0.530691E+10 7621.40 10-JAN-14:09 -22.1 -22.4
February 0.305520E+11 89650.28 13-FEB-05:01 -16.1 -16.4 0.495319E+10 7500.59 17-FEB-14:00 -11.1 -12.7
March 0.387310E+11 92937.75 20-MAR-04:01 -4.5 -5.7 0.607629E+10 7500.69 28-MAR-13:00 -6.7 -9.6
April 0.444424E+11 95518.54 10-APR-03:01 -4.5 -7.4 0.545183E+10 7501.00 07-APR-09:09 -4.5 -7.4
May 0.491184E+11 96218.64 30-MAY-03:02 3.90 2.96 0.590539E+10 7499.02 19-MAY-09:20 3.90 2.96
June 0.518466E+11 97145.13 19-JUN-03:02 7.62 7.07 0.588711E+10 7499.07 13-JUN-13:39 7.62 7.07
July 0.532956E+11 100116.50 31-JUL-03:02 7.20 6.67 0.547902E+10 7500.47 19-JUL-09:20 7.20 6.67
August 0.589649E+11 98111.28 28-AUG-03:02 8.72 7.37 0.614372E+10 7499.01 18-AUG-13:20 8.72 7.37
September 0.484224E+11 94760.50 18-SEP-03:03 3.03 1.93 0.545587E+10 7499.18 08-SEP-13:20 3.03 1.93
October 0.444621E+11 97468.45 10-OCT-03:01 -0.6 -0.9 0.566914E+10 7500.75 30-OCT-13:00 -11.1 -12.2
November 0.417252E+11 91966.10 13-NOV-05:01 -20.2 -20.4 0.532682E+10 7755.04 07-NOV-10:09 -20.2 -20.4
December 0.392770E+11 93594.19 26-DEC-04:01 -12.7 -12.9 0.498109E+10 7600.22 22-DEC-10:30 -12.7 -12.9
                     
Annual Sum or Average 0.530799E+12         0.666364E+11        
Minimum of Months 0.299613E+11 87457.37   -22.1 -22.4 0.495319E+10 7499.01   -22.1 -22.4
Maximum of Months 0.589649E+11 100116.50   8.72 7.37 0.614372E+10 7755.04   8.72 7.37



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.242461E+11 22260.88 25-JAN-13:20 -20.0 -20.3 0.472614E+10 6734.56 26-JAN-14:09 -18.3 -18.6
February 0.251954E+11 72001.02 10-FEB-06:01 -9.5 -10.1 0.447555E+10 6734.67 15-FEB-14:30 -7.8 -8.9
March 0.365674E+11 76669.72 30-MAR-05:01 -16.8 -18.0 0.544568E+10 6734.81 29-MAR-13:09 -16.8 -18.0
April 0.465608E+11 78815.08 24-APR-03:02 -2.8 -5.4 0.487902E+10 6905.53 07-APR-13:39 -2.8 -5.4
May 0.483673E+11 79268.71 01-MAY-03:02 6.70 2.21 0.528319E+10 6734.74 19-MAY-13:00 13.30 8.13
June 0.549016E+11 81847.79 26-JUN-03:02 12.70 11.22 0.526993E+10 6734.79 29-JUN-13:30 25.00 15.96
July 0.592759E+11 82540.04 05-JUL-03:02 8.30 7.78 0.489556E+10 6735.80 19-JUL-09:09 17.38 14.45
August 0.631402E+11 78698.28 08-AUG-03:02 12.70 11.82 0.549723E+10 6734.72 25-AUG-09:00 15.60 11.89
September 0.399045E+11 82935.70 05-SEP-03:02 5.50 5.03 0.487694E+10 6734.81 08-SEP-13:09 11.28 7.64
October 0.351291E+11 81061.72 10-OCT-04:01 -0.6 -1.1 0.505592E+10 6745.78 10-OCT-09:00 0.00 -1.1
November 0.285173E+11 70697.72 02-NOV-05:01 -11.0 -11.4 0.494353E+10 6734.75 07-NOV-10:09 -22.9 -23.1
December 0.266640E+11 30407.55 26-DEC-08:15 -9.7 -10.1 0.474868E+10 6734.76 22-DEC-14:50 -9.7 -10.1
                     
Annual Sum or Average 0.488470E+12         0.600974E+11        
Minimum of Months 0.242461E+11 22260.88   -20.0 -20.3 0.447555E+10 6734.56   -22.9 -23.1
Maximum of Months 0.631402E+11 82935.70   12.70 11.82 0.549723E+10 6905.53   25.00 15.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.171091E+11 15931.34 27-JAN-17:00 -12.2 -12.5 0.400375E+10 5944.70 25-JAN-14:00 -12.2 -12.5
February 0.183743E+11 22208.07 16-FEB-13:40 -8.7 -9.8 0.381610E+10 6465.19 15-FEB-14:30 -8.7 -9.8
March 0.239498E+11 22985.50 29-MAR-10:25 -10.2 -12.4 0.492834E+10 6734.50 24-MAR-13:50 -10.2 -12.4
April 0.285346E+11 69354.35 28-APR-05:03 -1.5 -2.2 0.473489E+10 6782.64 13-APR-09:50 -1.5 -2.2
May 0.393993E+11 72283.06 15-MAY-05:04 6.88 1.81 0.526305E+10 6734.73 16-MAY-09:09 5.97 4.63
June 0.428825E+11 72002.37 24-JUN-05:04 12.80 12.21 0.526150E+10 6734.78 29-JUN-13:20 24.80 15.87
July 0.417724E+11 75453.35 05-JUL-03:02 8.30 7.78 0.488897E+10 6735.60 19-JUL-09:09 17.38 14.45
August 0.417085E+11 73436.68 07-AUG-04:03 11.02 10.45 0.548511E+10 6734.71 18-AUG-13:09 13.62 12.18
September 0.300752E+11 73188.13 05-SEP-05:02 5.00 4.09 0.482000E+10 6736.13 22-SEP-13:39 6.13 3.62
October 0.231713E+11 48465.64 06-OCT-05:03 6.60 2.71 0.467259E+10 6734.70 03-OCT-09:00 6.60 2.71
November 0.184232E+11 16577.86 03-NOV-16:00 -11.1 -11.5 0.409473E+10 6109.99 03-NOV-13:00 -11.1 -11.5
December 0.172981E+11 15564.76 22-DEC-17:00 -21.7 -22.0 0.387654E+10 5845.94 22-DEC-14:00 -21.7 -22.0
                     
Annual Sum or Average 0.342698E+12         0.558456E+11        
Minimum of Months 0.171091E+11 15564.76   -21.7 -22.0 0.381610E+10 5845.94   -21.7 -22.0
Maximum of Months 0.428825E+11 75453.35   12.80 12.21 0.548511E+10 6782.64   24.80 15.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.598024E+10 13178.34 20-JAN-17:00 -11.1 -11.2 0.370631E+10 5178.08 20-JAN-14:00 -11.1 -11.2
February 0.844229E+10 15227.75 09-FEB-17:00 -2.2 -2.6 0.342008E+10 5709.57 09-FEB-14:00 -2.2 -2.6
March 0.146578E+11 17100.33 22-MAR-16:00 5.60 2.61 0.424522E+10 6064.62 22-MAR-13:00 5.60 2.61
April 0.206052E+11 29607.97 21-APR-16:00 14.40 5.45 0.423480E+10 6734.43 27-APR-13:00 11.10 4.54
May 0.332871E+11 63346.86 11-MAY-05:02 4.68 1.21 0.517443E+10 6734.72 16-MAY-09:09 5.97 4.63
June 0.418606E+11 72265.35 24-JUN-05:04 12.80 12.21 0.524466E+10 6734.75 29-JUN-13:00 25.60 16.24
July 0.403849E+11 69305.06 05-JUL-05:02 8.30 7.78 0.487557E+10 6735.43 19-JUL-09:09 17.38 14.45
August 0.369496E+11 70604.14 07-AUG-05:02 10.60 10.26 0.543071E+10 6734.66 18-AUG-13:09 13.62 12.18
September 0.210817E+11 27322.05 01-SEP-16:00 15.60 10.82 0.436120E+10 6734.64 08-SEP-13:09 11.28 7.64
October 0.139338E+11 17548.25 04-OCT-16:00 10.00 4.57 0.395686E+10 6272.25 04-OCT-13:00 10.00 4.57
November 0.706708E+10 13465.13 02-NOV-16:00 -8.9 -9.4 0.368274E+10 5216.19 02-NOV-13:00 -8.9 -9.4
December 0.573774E+10 12472.04 21-DEC-17:00 -16.7 -17.3 0.357029E+10 5016.11 21-DEC-14:00 -16.7 -17.3
                     
Annual Sum or Average 0.249988E+12         0.519029E+11        
Minimum of Months 0.573774E+10 12472.04   -16.7 -17.3 0.342008E+10 5016.11   -16.7 -17.3
Maximum of Months 0.418606E+11 72265.35   15.60 12.21 0.543071E+10 6735.43   25.60 16.24



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.361462E+09 1609.67 20-JAN-14:30 -10.0 -10.3 0.467188E+09 645.14 20-JAN-14:39 -10.4 -10.6
February 0.105767E+10 2404.18 09-FEB-06:03 0.00 -0.5 0.439588E+09 740.08 09-FEB-14:00 0.00 -1.0
March 0.230321E+10 2761.93 22-MAR-14:00 5.60 1.90 0.574640E+09 845.60 22-MAR-13:20 5.60 1.90
April 0.408545E+10 5072.51 28-APR-14:00 11.70 4.88 0.587465E+09 847.35 07-APR-13:00 11.70 4.88
May 0.615501E+10 12173.82 31-MAY-04:33 11.87 7.50 0.661542E+09 845.63 19-MAY-13:39 11.87 7.50
June 0.906536E+10 13348.92 29-JUN-05:03 12.38 11.04 0.662280E+09 845.65 29-JUN-13:30 25.00 15.96
July 0.922398E+10 13136.33 07-JUL-04:23 14.15 11.07 0.615599E+09 845.76 19-JUL-09:09 17.38 14.45
August 0.800392E+10 11387.43 07-AUG-05:02 10.60 10.26 0.689127E+09 845.63 18-AUG-13:09 13.62 12.18
September 0.362822E+10 4910.82 01-SEP-13:40 14.63 10.60 0.591280E+09 845.63 08-SEP-13:09 11.28 7.64
October 0.250598E+10 3030.24 04-OCT-14:30 11.10 4.80 0.553918E+09 845.60 02-OCT-13:09 11.10 4.80
November 0.106690E+10 2154.57 02-NOV-05:01 -11.0 -11.4 0.472030E+09 698.81 02-NOV-13:00 -8.9 -9.5
December 0.465807E+09 1773.04 26-DEC-12:00 -10.6 -11.5 0.453509E+09 685.25 26-DEC-10:00 -10.6 -11.5
                     
Annual Sum or Average 0.479230E+11         0.676817E+10        
Minimum of Months 0.361462E+09 1609.67   -11.0 -11.5 0.439588E+09 645.14   -10.6 -11.5
Maximum of Months 0.922398E+10 13348.92   14.63 11.07 0.689127E+09 847.35   25.00 15.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.188542E+09 1493.64 27-JAN-06:03 -13.8 -14.1 0.300361E+09 403.39 13-JAN-10:50 -13.8 -14.1
February 0.880885E+09 2117.66 09-FEB-06:03 0.00 -0.5 0.282819E+09 509.86 15-FEB-10:00 -15.6 -15.8
March 0.256753E+10 6488.17 27-MAR-09:40 -10.2 -12.2 0.390939E+09 544.95 27-MAR-09:00 -9.4 -11.6
April 0.452488E+10 9229.39 22-APR-09:20 8.87 3.75 0.380639E+09 545.80 10-APR-09:30 8.87 3.75
May 0.777651E+10 20173.07 14-MAY-08:12 13.53 7.00 0.426836E+09 545.79 30-MAY-09:00 15.00 8.95
June 0.848379E+10 15328.52 07-JUN-05:02 7.30 5.47 0.426251E+09 546.04 08-JUN-09:20 15.97 10.22
July 0.874234E+10 20690.78 23-JUL-09:51 21.10 14.79 0.396157E+09 546.49 07-JUL-09:30 21.10 14.79
August 0.752444E+10 12701.42 10-AUG-08:50 14.22 9.95 0.443065E+09 545.87 10-AUG-09:00 17.80 11.30
September 0.368173E+10 18774.27 10-SEP-08:53 11.10 6.28 0.380770E+09 544.96 08-SEP-13:09 11.10 6.28
October 0.223170E+10 5911.43 03-OCT-09:40 2.97 2.01 0.352037E+09 545.76 10-OCT-09:00 0.00 -1.1
November 0.502248E+09 2072.16 03-NOV-05:02 -16.4 -16.8 0.298781E+09 431.96 08-NOV-10:00 -17.8 -18.2
December 0.132072E+09 1537.23 26-DEC-06:04 -12.1 -12.4 0.290207E+09 403.39 15-DEC-14:39 -12.1 -12.4
                     
Annual Sum or Average 0.472367E+11         0.436886E+10        
Minimum of Months 0.132072E+09 1493.64   -16.4 -16.8 0.282819E+09 403.39   -17.8 -18.2
Maximum of Months 0.874234E+10 20690.78   21.10 14.79 0.443065E+09 546.49   21.10 14.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.441828E+09 3049.56 25-JAN-13:30 -19.8 -20.0 0.469610E+09 755.66 25-JAN-14:09 -18.9 -19.2
February 0.195405E+10 8859.03 15-FEB-13:30 -8.9 -9.7 0.461956E+09 845.64 15-FEB-14:30 -7.8 -8.9
March 0.546361E+10 14498.98 31-MAR-13:30 -11.4 -13.3 0.613855E+09 845.65 29-MAR-13:09 -11.4 -13.3
April 0.974711E+10 22484.71 09-APR-14:53 3.90 -1.8 0.586830E+09 877.42 07-APR-13:00 3.90 -1.8
May 0.107407E+11 30511.42 14-MAY-12:12 18.17 9.44 0.657532E+09 847.08 12-MAY-13:50 18.17 9.44
June 0.123879E+11 23927.91 11-JUN-15:02 18.40 10.87 0.661178E+09 845.73 29-JUN-13:30 25.00 15.96
July 0.131771E+11 32291.04 23-JUL-13:11 25.00 15.26 0.614770E+09 846.42 12-JUL-13:00 25.00 15.26
August 0.133690E+11 29210.86 27-AUG-13:32 18.87 14.02 0.687551E+09 846.86 31-AUG-13:00 13.30 4.88
September 0.685367E+10 18838.75 10-SEP-11:32 15.20 8.17 0.581838E+09 845.68 08-SEP-13:09 15.20 8.17
October 0.399303E+10 15112.86 03-OCT-13:30 10.85 6.24 0.549336E+09 845.65 12-OCT-13:09 -1.1 -3.6
November 0.116643E+10 6188.00 08-NOV-13:30 -13.6 -14.4 0.475960E+09 845.63 08-NOV-14:00 -13.9 -14.6
December 0.220287E+09 2382.68 27-DEC-12:40 -22.6 -22.8 0.449748E+09 625.95 07-DEC-10:20 -22.6 -22.8
                     
Annual Sum or Average 0.795146E+11         0.681017E+10        
Minimum of Months 0.220287E+09 2382.68   -22.6 -22.8 0.449748E+09 625.95   -22.6 -22.8
Maximum of Months 0.133690E+11 32291.04   25.00 15.26 0.687551E+09 877.42   25.00 15.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.958587E+09 1950.15 23-JAN-14:20 -9.5 -10.0 0.302897E+09 433.43 23-JAN-14:39 -10.0 -10.5
February 0.208444E+10 3170.01 09-FEB-06:03 0.00 -0.5 0.299655E+09 535.06 09-FEB-14:00 0.00 -1.0
March 0.398914E+10 7572.19 27-MAR-16:00 -4.4 -7.8 0.410820E+09 544.95 29-MAR-13:39 -7.2 -9.9
April 0.836976E+10 21765.56 22-APR-17:04 14.13 6.18 0.394733E+09 550.46 07-APR-13:00 14.13 6.18
May 0.738518E+10 23001.57 14-MAY-19:32 15.97 8.06 0.427435E+09 544.96 19-MAY-13:39 13.87 8.18
June 0.104333E+11 21986.36 11-JUN-17:02 18.80 10.99 0.427955E+09 544.99 29-JUN-13:30 25.00 15.96
July 0.112831E+11 23709.30 23-JUL-15:11 25.60 15.27 0.398152E+09 545.06 19-JUL-09:09 25.60 15.27
August 0.116554E+11 23466.55 27-AUG-16:52 21.10 12.86 0.446438E+09 544.96 18-AUG-13:09 21.10 12.86
September 0.455403E+10 12193.68 02-SEP-17:08 16.70 10.21 0.384827E+09 544.96 08-SEP-13:09 11.28 7.64
October 0.338382E+10 7319.28 04-OCT-05:03 7.70 2.90 0.375762E+09 544.95 02-OCT-09:09 7.70 2.90
November 0.254973E+10 3046.57 02-NOV-05:01 -11.0 -11.4 0.330790E+09 519.96 08-NOV-14:00 -13.9 -14.6
December 0.252567E+10 2531.94 26-DEC-05:01 -12.2 -12.5 0.316177E+09 498.25 26-DEC-10:00 -10.0 -10.8
                     
Annual Sum or Average 0.691721E+11         0.451564E+10        
Minimum of Months 0.958587E+09 1950.15   -12.2 -12.5 0.299655E+09 433.43   -13.9 -14.6
Maximum of Months 0.116554E+11 23709.30   25.60 15.27 0.446438E+09 550.46   25.60 15.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 21623173.11 1401.99 20-JAN-21:03 -13.0 -13.1 0.462086E+09 626.00 03-JAN-10:50 -13.0 -13.1
February 67371391.73 1929.16 08-FEB-21:05 -0.7 -2.6 0.420347E+09 627.22 15-FEB-14:30 -7.8 -8.9
March 0.546296E+09 2000.06 17-MAR-20:03 -0.8 -2.5 0.510909E+09 721.65 22-MAR-13:00 5.60 1.90
April 0.221316E+10 3261.54 28-APR-15:20 12.20 4.90 0.517192E+09 845.60 27-APR-13:50 12.20 4.90
May 0.478594E+10 10797.61 31-MAY-05:03 12.07 7.63 0.655640E+09 845.63 19-MAY-13:39 12.07 7.63
June 0.745493E+10 12399.01 19-JUN-05:03 8.27 7.22 0.661429E+09 845.65 29-JUN-13:20 24.80 15.87
July 0.685047E+10 12698.53 11-JUL-04:52 15.00 11.90 0.614794E+09 845.73 19-JUL-09:09 17.38 14.45
August 0.509722E+10 9319.60 01-AUG-05:02 10.00 9.66 0.680745E+09 845.62 18-AUG-13:09 13.62 12.18
September 0.255982E+10 3310.68 01-SEP-13:50 14.82 10.69 0.543194E+09 845.60 01-SEP-13:09 14.82 10.69
October 0.962170E+09 2116.55 05-OCT-09:20 1.67 0.09 0.482284E+09 761.06 04-OCT-13:00 1.67 0.09
November 20743015.04 1416.37 02-NOV-20:03 -9.4 -9.7 0.458651E+09 625.99 27-NOV-10:39 -27.2 -27.4
December 21227453.67 1393.01 23-DEC-16:03 -3.1 -4.1 0.446144E+09 626.01 27-DEC-14:20 -23.9 -24.1
                     
Annual Sum or Average 0.306010E+11         0.645342E+10        
Minimum of Months 20743015.04 1393.01   -13.0 -13.1 0.420347E+09 625.99   -27.2 -27.4
Maximum of Months 0.745493E+10 12698.53   15.00 11.90 0.680745E+09 845.73   24.80 15.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 27388807.21 1613.17 05-JAN-06:04 -13.3 -13.4 0.218556E+09 385.82 03-JAN-08:39 -13.3 -13.4
February 0.146237E+09 1994.62 09-FEB-11:05 -3.0 -3.1 0.198983E+09 407.17 15-FEB-11:39 -13.0 -13.4
March 0.139304E+10 4665.76 29-MAR-10:25 -10.2 -12.4 0.255991E+09 531.11 29-MAR-10:30 -10.2 -12.4
April 0.337975E+10 13184.31 23-APR-10:13 9.60 3.55 0.264052E+09 544.80 13-APR-10:30 9.60 3.55
May 0.750159E+10 20460.83 21-MAY-09:02 12.30 5.76 0.312483E+09 522.35 12-MAY-10:30 12.30 5.76
June 0.818639E+10 17352.62 18-JUN-10:13 14.23 11.41 0.312766E+09 525.51 08-JUN-07:19 14.23 11.41
July 0.804951E+10 22554.45 23-JUL-09:51 21.10 14.79 0.291929E+09 525.56 21-JUL-07:19 21.10 14.79
August 0.639099E+10 13357.91 10-AUG-09:00 14.40 10.07 0.324049E+09 522.30 10-AUG-10:30 18.60 11.60
September 0.304518E+10 16169.18 10-SEP-09:23 11.95 6.71 0.261813E+09 521.51 12-SEP-08:30 5.80 4.93
October 0.110761E+10 3947.64 03-OCT-10:10 4.27 2.93 0.231139E+09 521.20 03-OCT-10:20 4.63 3.18
November 24622286.14 1631.28 14-NOV-06:04 -15.6 -15.9 0.216603E+09 385.85 17-NOV-08:09 -24.4 -24.6
December 26285012.50 1612.78 30-DEC-06:04 -16.7 -17.0 0.210741E+09 385.82 13-DEC-08:50 -16.7 -17.0
                     
Annual Sum or Average 0.392786E+11         0.309910E+10        
Minimum of Months 24622286.14 1612.78   -16.7 -17.0 0.198983E+09 385.82   -24.4 -24.6
Maximum of Months 0.818639E+10 22554.45   21.10 14.79 0.324049E+09 544.80   21.10 14.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.197854E+09 2799.85 25-JAN-13:40 -19.5 -19.7 0.464633E+09 701.66 25-JAN-14:09 -18.9 -19.2
February 0.118394E+10 7705.00 15-FEB-14:30 -7.8 -8.9 0.445396E+09 878.98 15-FEB-14:30 -7.8 -8.9
March 0.438708E+10 20123.59 29-MAR-13:28 -7.5 -10.1 0.582923E+09 881.17 14-MAR-13:30 -7.5 -10.1
April 0.868852E+10 30582.12 23-APR-13:32 10.00 3.85 0.568916E+09 852.43 13-APR-09:50 10.00 3.85
May 0.106656E+11 32209.60 21-MAY-13:02 14.60 6.77 0.652094E+09 847.21 12-MAY-13:00 14.60 6.77
June 0.115142E+11 30860.76 18-JUN-12:52 16.70 11.52 0.658611E+09 845.95 16-JUN-13:00 16.70 11.52
July 0.114218E+11 34474.66 23-JUL-13:51 25.00 15.26 0.612591E+09 846.79 20-JUL-13:50 25.00 15.26
August 0.113133E+11 30650.18 27-AUG-13:32 18.87 14.02 0.682002E+09 846.03 31-AUG-13:00 13.30 4.88
September 0.657394E+10 30432.82 10-SEP-11:22 15.00 8.08 0.566261E+09 845.68 08-SEP-13:09 15.00 8.08
October 0.288332E+10 14732.50 03-OCT-13:30 10.85 6.24 0.517994E+09 845.63 04-OCT-13:39 11.30 4.92
November 0.387249E+09 4064.28 08-NOV-13:30 -13.6 -14.4 0.464718E+09 845.63 08-NOV-14:50 -13.8 -14.5
December 40684586.86 2416.02 30-DEC-06:04 -16.7 -17.0 0.446965E+09 626.00 15-DEC-10:09 -16.7 -17.0
                     
Annual Sum or Average 0.692575E+11         0.666310E+10        
Minimum of Months 40684586.86 2416.02   -19.5 -19.7 0.445396E+09 626.00   -18.9 -19.2
Maximum of Months 0.115142E+11 34474.66   25.00 15.26 0.682002E+09 881.17   25.00 15.26



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 31633392.53 1683.93 05-JAN-06:04 -13.3 -13.4 0.298893E+09 403.40 03-JAN-10:50 -13.3 -13.4
February 0.196636E+09 1976.59 08-FEB-21:05 -0.7 -2.6 0.272078E+09 419.29 09-FEB-14:00 0.00 -1.0
March 0.109264E+10 4067.18 31-MAR-16:00 -9.4 -11.8 0.335432E+09 512.75 29-MAR-15:00 -9.4 -11.8
April 0.380217E+10 14954.76 22-APR-17:04 14.13 6.18 0.347343E+09 544.94 26-APR-13:00 10.60 4.23
May 0.539294E+10 20669.00 21-MAY-17:42 16.10 7.34 0.418159E+09 544.95 19-MAY-13:39 16.10 7.34
June 0.717190E+10 21378.89 11-JUN-17:32 18.50 10.90 0.425874E+09 544.97 29-JUN-13:20 24.80 15.87
July 0.649914E+10 19713.64 23-JUL-15:52 25.60 14.77 0.395696E+09 545.02 19-JUL-09:09 25.60 14.77
August 0.562689E+10 20157.63 27-AUG-17:32 20.77 12.41 0.438133E+09 544.95 18-AUG-13:09 20.77 12.41
September 0.289744E+10 8281.08 02-SEP-17:10 16.70 10.21 0.346592E+09 544.93 01-SEP-13:00 16.70 10.21
October 0.112276E+10 2365.19 03-OCT-15:20 12.43 6.74 0.311610E+09 514.19 03-OCT-15:30 12.25 6.65
November 60679929.80 1660.48 14-NOV-06:04 -15.6 -15.9 0.296428E+09 403.38 09-NOV-10:20 -15.6 -15.9
December 37473212.85 1682.18 27-DEC-06:04 -20.8 -21.0 0.288426E+09 403.40 07-DEC-10:39 -20.8 -21.0
                     
Annual Sum or Average 0.339323E+11         0.417466E+10        
Minimum of Months 31633392.53 1660.48   -20.8 -21.0 0.272078E+09 403.38   -20.8 -21.0
Maximum of Months 0.717190E+10 21378.89   25.60 14.77 0.438133E+09 545.02   25.60 15.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 17690306.81 1764.90 19-JAN-21:03 -10.0 -10.4 0.459459E+09 626.05 12-JAN-14:39 -10.0 -10.4
February 20209689.98 1813.23 08-FEB-21:03 -0.7 -2.6 0.417835E+09 626.05 22-FEB-10:20 -26.9 -27.1
March 0.111023E+09 2043.58 22-MAR-16:00 5.60 2.61 0.503248E+09 635.05 22-MAR-13:00 5.60 2.61
April 0.156342E+10 2815.31 28-APR-16:00 12.20 5.13 0.467256E+09 780.17 28-APR-13:00 12.20 5.13
May 0.439268E+10 12770.65 31-MAY-05:03 12.07 7.63 0.618508E+09 845.62 19-MAY-13:39 12.07 7.63
June 0.727899E+10 14967.49 08-JUN-05:02 8.48 6.28 0.658292E+09 845.64 29-JUN-13:00 25.60 16.24
July 0.674119E+10 15226.97 11-JUL-05:02 15.18 11.97 0.610256E+09 845.66 19-JUL-09:20 17.57 14.42
August 0.486036E+10 8822.75 05-AUG-05:03 13.98 12.01 0.652972E+09 845.61 25-AUG-13:00 22.80 15.44
September 0.178870E+10 2816.13 01-SEP-16:00 15.60 10.82 0.473754E+09 781.50 01-SEP-13:00 15.60 10.82
October 0.257082E+09 2132.69 04-OCT-16:00 10.00 4.57 0.464566E+09 651.51 04-OCT-13:00 10.00 4.57
November 16149573.07 1774.60 02-NOV-20:03 -9.4 -9.7 0.456128E+09 626.03 27-NOV-14:50 -23.9 -24.2
December 19716467.04 1750.98 23-DEC-16:03 -3.1 -4.1 0.443259E+09 626.09 27-DEC-14:50 -23.9 -24.1
                     
Annual Sum or Average 0.270672E+11         0.622553E+10        
Minimum of Months 16149573.07 1750.98   -10.0 -10.4 0.417835E+09 626.03   -26.9 -27.1
Maximum of Months 0.727899E+10 15226.97   15.60 12.01 0.658292E+09 845.66   25.60 16.24



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 18018118.68 1547.45 05-JAN-06:05 -13.3 -13.4 0.298155E+09 403.45 11-JAN-10:00 -34.4 -34.5
February 30066482.18 1631.14 08-FEB-06:04 -10.5 -10.7 0.270850E+09 403.40 01-FEB-10:30 -10.5 -10.7
March 0.635526E+09 2277.33 22-MAR-10:40 2.43 0.50 0.332964E+09 517.66 22-MAR-09:00 2.43 0.50
April 0.236556E+10 7257.21 22-APR-09:30 9.15 3.96 0.342199E+09 544.95 13-APR-09:00 9.15 3.96
May 0.669374E+10 21233.94 21-MAY-09:12 12.40 5.80 0.422243E+09 545.51 31-MAY-09:00 17.20 9.87
June 0.813221E+10 16645.71 08-JUN-05:02 8.48 6.28 0.425054E+09 545.80 08-JUN-09:39 16.33 10.32
July 0.797362E+10 20417.81 23-JUL-10:02 21.38 14.90 0.394857E+09 546.06 07-JUL-09:50 21.38 14.90
August 0.593708E+10 13894.21 27-AUG-10:43 13.53 10.98 0.438729E+09 545.49 10-AUG-09:00 13.53 10.98
September 0.203170E+10 5550.07 10-SEP-10:05 13.07 7.24 0.328768E+09 544.96 08-SEP-13:09 13.07 7.24
October 0.434402E+09 2197.95 03-OCT-10:30 5.00 3.43 0.303498E+09 513.57 03-OCT-09:00 5.00 3.43
November 18254985.90 1378.35 02-NOV-20:03 -9.4 -9.7 0.295387E+09 403.45 29-NOV-10:20 -29.4 -29.6
December 20092191.95 1359.78 23-DEC-16:03 -3.1 -4.1 0.287416E+09 403.48 27-DEC-14:39 -23.9 -24.1
                     
Annual Sum or Average 0.342903E+11         0.414012E+10        
Minimum of Months 18018118.68 1359.78   -13.3 -13.4 0.270850E+09 403.40   -34.4 -34.5
Maximum of Months 0.813221E+10 21233.94   21.38 14.90 0.438729E+09 546.06   21.38 14.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 50332449.67 2153.73 21-JAN-16:03 -5.6 -5.8 0.462792E+09 626.07 12-JAN-10:30 -5.6 -5.8
February 0.558330E+09 4152.21 15-FEB-14:00 -8.3 -9.2 0.430389E+09 845.64 15-FEB-14:30 -7.8 -8.9
March 0.267539E+10 11288.76 31-MAR-14:20 -10.7 -12.8 0.558063E+09 845.65 29-MAR-13:09 -10.7 -12.8
April 0.662825E+10 21046.67 23-APR-16:03 8.03 2.47 0.543407E+09 845.75 20-APR-13:20 8.03 2.47
May 0.955320E+10 32927.29 21-MAY-13:12 14.80 6.89 0.634567E+09 846.80 12-MAY-13:50 14.80 6.89
June 0.113294E+11 29508.85 11-JUN-16:02 18.90 11.02 0.653419E+09 845.71 29-JUN-13:00 25.60 16.24
July 0.112575E+11 32839.98 23-JUL-13:22 25.00 15.26 0.607034E+09 846.24 12-JUL-13:00 25.00 15.26
August 0.106160E+11 34946.67 27-AUG-14:01 19.68 14.05 0.668682E+09 846.09 25-AUG-13:00 19.68 14.05
September 0.471644E+10 15172.35 08-SEP-14:30 13.05 8.68 0.523195E+09 845.67 08-SEP-13:09 13.05 8.68
October 0.151555E+10 11616.01 03-OCT-13:40 11.13 6.36 0.489495E+09 845.62 13-OCT-13:00 1.10 -2.4
November 0.130368E+09 3113.03 08-NOV-14:00 -13.3 -14.1 0.459774E+09 744.08 08-NOV-14:09 -13.4 -14.2
December 32495647.62 2134.35 23-DEC-16:03 -3.1 -4.1 0.446081E+09 626.08 27-DEC-14:50 -23.9 -24.1
                     
Annual Sum or Average 0.590632E+11         0.647690E+10        
Minimum of Months 32495647.62 2134.35   -13.3 -14.1 0.430389E+09 626.07   -23.9 -24.1
Maximum of Months 0.113294E+11 34946.67   25.00 15.26 0.668682E+09 846.80   25.60 16.24



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 21032791.12 1458.32 19-JAN-21:03 -10.0 -10.4 0.298276E+09 403.46 30-JAN-10:00 -25.0 -25.4
February 51008085.84 1738.01 03-FEB-06:04 -10.5 -10.7 0.271036E+09 403.44 27-FEB-10:00 -33.3 -33.4
March 0.503204E+09 2236.55 27-MAR-17:00 -5.0 -8.2 0.328051E+09 470.84 22-MAR-15:00 -5.0 -8.2
April 0.290062E+10 15120.71 22-APR-17:06 14.13 6.18 0.322763E+09 544.12 21-APR-13:00 14.13 6.18
May 0.481256E+10 21153.83 21-MAY-17:52 16.10 7.32 0.401254E+09 544.95 19-MAY-13:39 16.10 7.32
June 0.703620E+10 22326.68 11-JUN-16:42 18.90 11.02 0.423036E+09 544.97 29-JUN-13:00 25.60 16.24
July 0.635697E+10 13158.56 29-JUL-18:23 26.95 18.21 0.392439E+09 544.97 07-JUL-13:09 26.95 18.21
August 0.521097E+10 21215.39 27-AUG-17:21 20.85 12.52 0.426219E+09 544.95 25-AUG-13:00 20.85 12.52
September 0.202993E+10 5867.61 08-SEP-16:00 14.40 9.03 0.316450E+09 526.95 01-SEP-13:00 14.40 9.03
October 0.441826E+09 2175.00 03-OCT-15:20 12.43 6.74 0.301879E+09 468.67 03-OCT-15:30 12.25 6.65
November 24351858.50 1681.73 02-NOV-05:04 -11.0 -11.4 0.295614E+09 403.41 28-NOV-10:09 -28.9 -29.1
December 26778066.62 1457.03 23-DEC-16:03 -3.1 -4.1 0.287650E+09 403.44 27-DEC-14:30 -23.9 -24.1
                     
Annual Sum or Average 0.294155E+11         0.406467E+10        
Minimum of Months 21032791.12 1457.03   -11.0 -11.4 0.271036E+09 403.41   -33.3 -33.4
Maximum of Months 0.703620E+10 22326.68   26.95 18.21 0.426219E+09 544.97   26.95 18.21



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 35028632.93 5514.25 12-JAN-05:01 -37.9 -38.0 0.00 0.00 01-JAN-00:10 -37.9 -38.0
February 0.199242E+09 5061.96 18-FEB-06:01 -21.9 -22.4 0.00 0.00 01-FEB-00:10 -21.9 -22.4
March 0.641025E+09 3394.65 21-MAR-05:08 -4.3 -5.7 0.00 0.00 01-MAR-00:10 -4.3 -5.7
April 0.297783E+10 5438.09 24-APR-05:15 -3.5 -6.1 0.00 0.00 01-APR-00:10 -3.5 -6.1
May 0.507549E+10 6713.03 15-MAY-05:02 6.88 1.81 0.00 0.00 01-MAY-00:10 6.88 1.81
June 0.710577E+10 7797.75 26-JUN-05:15 12.57 11.27 0.00 0.00 01-JUN-00:10 12.57 11.27
July 0.738412E+10 8556.60 31-JUL-05:15 8.13 7.10 0.00 0.00 01-JUL-00:10 8.13 7.10
August 0.689330E+10 7810.09 07-AUG-05:15 10.60 10.26 0.00 0.00 01-AUG-00:10 10.60 10.26
September 0.297029E+10 7148.63 05-SEP-05:15 5.00 4.17 0.00 0.00 01-SEP-00:10 5.00 4.17
October 0.120999E+10 3924.96 03-OCT-05:10 -1.1 -1.4 0.00 0.00 01-OCT-00:10 -1.1 -1.4
November 77851359.97 3479.43 09-NOV-06:01 -27.1 -27.3 0.00 0.00 01-NOV-00:10 -27.1 -27.3
December 20178550.62 3777.29 15-DEC-05:01 -33.2 -33.3 0.00 0.00 01-DEC-00:10 -33.2 -33.3
                     
Annual Sum or Average 0.345901E+11         0.00        
Minimum of Months 20178550.62 3394.65   -37.9 -38.0 0.00 0.00   -37.9 -38.0
Maximum of Months 0.738412E+10 8556.60   12.57 11.27 0.00 0.00   12.57 11.27



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.300135E+09 7753.87 12-JAN-04:01 -37.3 -37.4 0.00 0.00 01-JAN-00:10 -37.3 -37.4
February 0.292699E+09 6844.26 18-FEB-05:01 -23.9 -24.3 0.00 0.00 01-FEB-00:10 -23.9 -24.3
March 0.227999E+09 6891.15 16-MAR-04:01 -25.1 -25.6 0.00 0.00 01-MAR-00:10 -25.1 -25.6
April 0.111838E+10 6391.06 03-APR-04:01 -21.1 -21.6 0.00 0.00 01-APR-00:10 -21.1 -21.6
May 0.346594E+10 4257.12 15-MAY-05:10 6.88 1.81 0.00 0.00 01-MAY-00:10 6.88 1.81
June 0.529086E+10 5383.14 24-JUN-05:10 12.80 12.21 0.00 0.00 01-JUN-00:10 12.80 12.21
July 0.531220E+10 6180.38 05-JUL-05:15 8.30 7.82 0.00 0.00 01-JUL-00:10 8.30 7.82
August 0.443710E+10 5384.49 14-AUG-05:15 11.10 10.22 0.00 0.00 01-AUG-00:10 11.10 10.22
September 0.178726E+10 4300.71 05-SEP-05:10 5.00 4.09 0.00 0.00 01-SEP-00:10 5.00 4.09
October 0.489076E+09 6904.14 30-OCT-03:01 -13.5 -14.2 0.00 0.00 01-OCT-00:10 -13.5 -14.2
November 0.271089E+09 6996.53 20-NOV-04:11 -19.4 -19.7 0.00 0.00 01-NOV-00:10 -19.4 -19.7
December 0.302239E+09 6939.72 15-DEC-04:01 -32.4 -32.5 0.00 0.00 01-DEC-00:10 -32.4 -32.5
                     
Annual Sum or Average 0.232950E+11         0.00        
Minimum of Months 0.227999E+09 4257.12   -37.3 -37.4 0.00 0.00   -37.3 -37.4
Maximum of Months 0.531220E+10 7753.87   12.80 12.21 0.00 0.00   12.80 12.21



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:02 -14.9 -15.4 0.00 0.00 01-JAN-00:10 -14.9 -15.4
February 0.00 0.00 01-FEB-00:03 -20.2 -20.7 0.00 0.00 01-FEB-00:10 -20.2 -20.7
March 1101939.75 423.23 22-MAR-16:30 5.60 2.18 0.00 0.00 01-MAR-00:10 5.60 2.18
April 0.794018E+09 5339.58 21-APR-15:30 14.15 5.54 0.00 0.00 01-APR-00:10 14.15 5.54
May 0.380747E+10 11279.42 31-MAY-14:40 20.73 10.55 0.00 0.00 01-MAY-00:10 20.73 10.55
June 0.730875E+10 12750.06 29-JUN-14:50 26.02 16.10 0.00 0.00 01-JUN-00:10 26.02 16.10
July 0.716796E+10 13296.40 21-JUL-14:40 27.23 14.65 0.00 0.00 01-JUL-00:10 27.23 14.65
August 0.448083E+10 10735.29 11-AUG-15:30 25.00 14.43 0.00 0.00 01-AUG-00:10 25.00 14.43
September 0.420585E+09 2857.46 07-SEP-16:30 16.10 8.44 0.00 0.00 01-SEP-00:10 16.10 8.44
October 567979.43 203.88 04-OCT-16:30 9.70 4.43 0.00 0.00 01-OCT-00:10 9.70 4.43
November 0.00 0.00 01-NOV-00:10 -10.0 -10.9 0.00 0.00 01-NOV-00:10 -10.0 -10.9
December 0.00 0.00 01-DEC-00:10 -25.8 -26.0 0.00 0.00 01-DEC-00:10 -25.8 -26.0
                     
Annual Sum or Average 0.239813E+11         0.00        
Minimum of Months 0.00 0.00   -25.8 -26.0 0.00 0.00   -25.8 -26.0
Maximum of Months 0.730875E+10 13296.40   27.23 16.10 0.00 0.00   27.23 16.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.104176E+10 1019.60 23-JAN-15:20 -10.4 -10.8 94833097.16 126.82 24-JAN-14:00 -15.6 -15.9
February 0.632939E+10 3450.98 15-FEB-16:20 -7.4 -8.8 86396480.28 126.82 01-FEB-14:09 -7.4 -8.8
March 0.132355E+11 6786.26 31-MAR-24:00 -11.8 -13.4 0.103236E+09 126.82 03-MAR-14:20 -11.8 -13.4
April 0.187361E+11 8268.29 20-APR-18:50 11.28 4.73 91605025.55 126.82 06-APR-13:09 11.28 4.73
May 0.432074E+10 3441.52 31-MAY-24:00 12.40 8.53 99233128.56 126.82 17-MAY-09:00 12.40 8.53
June 0.929679E+10 5340.70 30-JUN-24:00 15.10 14.10 98962414.48 126.85 27-JUN-13:00 15.10 14.10
July 0.146341E+11 7234.33 31-JUL-23:45 16.85 11.67 91886895.55 126.84 25-JUL-09:00 16.85 11.67
August 0.195595E+11 8194.03 27-AUG-18:34 19.80 11.87 0.103239E+09 126.83 04-AUG-09:09 19.80 11.87
September 0.377888E+10 2943.83 30-SEP-24:00 1.30 -0.1 91606628.40 126.83 05-SEP-13:00 1.30 -0.1
October 0.827363E+10 4513.53 31-OCT-24:00 -10.1 -11.0 95230026.18 126.82 04-OCT-13:09 -10.1 -11.0
November 0.119858E+11 5391.71 08-NOV-16:00 -16.1 -16.4 94300268.68 126.82 28-NOV-14:39 -25.4 -25.6
December 0.171636E+11 6973.04 26-DEC-17:00 -15.6 -15.9 91880853.18 126.82 28-DEC-14:50 -23.9 -24.1
                     
Annual Sum or Average 0.128356E+12         0.114241E+10        
Minimum of Months 0.104176E+10 1019.60   -16.1 -16.4 86396480.28 126.82   -25.4 -25.6
Maximum of Months 0.195595E+11 8268.29   19.80 14.10 0.103239E+09 126.85   19.80 14.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.371860E+09 656.67 12-JAN-08:65 -38.2 -38.3 85873874.65 126.82 20-JAN-14:00 -11.1 -11.3
February 0.357990E+10 2731.24 16-FEB-16:20 -4.8 -7.1 86396483.71 126.82 08-FEB-14:30 -4.8 -7.1
March 0.102679E+11 5847.35 31-MAR-23:20 -12.1 -13.7 0.103236E+09 126.82 09-MAR-14:50 -12.1 -13.7
April 0.167195E+11 7847.92 20-APR-18:50 11.28 4.73 91605050.62 126.82 06-APR-13:09 11.28 4.73
May 0.365105E+10 3204.88 31-MAY-24:00 12.40 8.53 99233131.74 126.82 17-MAY-09:00 12.40 8.53
June 0.865127E+10 5105.62 30-JUN-24:00 15.10 14.10 98962085.66 126.84 27-JUN-13:00 15.10 14.10
July 0.137999E+11 7008.30 31-JUL-23:53 16.60 11.46 91886472.40 126.84 25-JUL-13:00 16.60 11.46
August 0.184238E+11 7643.29 27-AUG-18:48 19.60 11.80 0.103239E+09 126.83 04-AUG-09:09 19.60 11.80
September 0.259565E+10 2224.12 30-SEP-24:00 1.30 -0.1 91606472.54 126.83 05-SEP-13:00 1.30 -0.1
October 0.567183E+10 3323.92 31-OCT-23:30 -10.2 -11.1 95230033.66 126.82 04-OCT-13:09 -10.2 -11.1
November 0.840942E+10 4494.53 08-NOV-15:50 -15.7 -16.1 94300274.00 126.82 21-NOV-14:30 -17.2 -17.6
December 0.132162E+11 5762.35 21-DEC-17:00 -16.7 -17.3 91880860.08 126.82 18-DEC-14:50 -16.7 -17.3
                     
Annual Sum or Average 0.105358E+12         0.113345E+10        
Minimum of Months 0.371860E+09 656.67   -38.2 -38.3 85873874.65 126.82   -17.2 -17.6
Maximum of Months 0.184238E+11 7847.92   19.60 14.10 0.103239E+09 126.84   19.60 14.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.341602E+09 635.17 12-JAN-08:15 -38.1 -38.2 77309220.89 118.63 19-JAN-14:00 -6.1 -6.7
February 0.199757E+10 2287.73 09-FEB-16:00 0.60 -0.5 86286098.59 126.82 01-FEB-14:39 0.60 -0.5
March 0.802733E+10 4810.15 31-MAR-23:10 -12.2 -13.8 0.103236E+09 126.82 17-MAR-13:50 -12.2 -13.8
April 0.150140E+11 7796.33 20-APR-18:50 11.28 4.73 91605061.02 126.82 06-APR-13:09 11.28 4.73
May 0.294679E+10 3153.81 31-MAY-24:00 12.40 8.53 99233165.80 126.82 17-MAY-09:00 12.40 8.53
June 0.847187E+10 5075.34 30-JUN-23:50 15.32 13.53 98962122.64 126.84 27-JUN-13:00 15.32 13.53
July 0.136339E+11 6978.61 31-JUL-23:37 17.10 11.88 91886564.12 126.84 25-JUL-13:00 17.10 11.88
August 0.180195E+11 7664.87 27-AUG-18:42 19.60 11.80 0.103239E+09 126.83 04-AUG-09:00 19.60 11.80
September 0.118529E+10 1681.82 08-SEP-17:30 13.85 8.80 91216859.31 127.02 26-SEP-09:20 0.77 -0.7
October 0.328477E+10 2933.62 03-OCT-16:00 11.70 6.37 95229995.79 126.82 04-OCT-13:09 11.60 5.09
November 0.621228E+10 3994.16 08-NOV-15:50 -15.7 -16.1 94300276.07 126.82 01-NOV-13:50 -15.7 -16.1
December 0.110925E+11 5268.69 21-DEC-17:00 -16.7 -17.3 91880862.64 126.82 01-DEC-14:39 -16.7 -17.3
                     
Annual Sum or Average 0.902274E+11         0.112439E+10        
Minimum of Months 0.341602E+09 635.17   -38.1 -38.2 77309220.89 118.63   -16.7 -17.3
Maximum of Months 0.180195E+11 7796.33   19.60 13.53 0.103239E+09 127.02   19.60 13.53



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.229573E+12 88695.84 25-JAN-17:00 -20.6 -20.9 0.206144E+10 2745.29 02-JAN-10:00 -20.6 -20.9
February 0.428405E+12 180525.55 09-FEB-17:00 -2.2 -2.6 0.187022E+10 2745.29 01-FEB-10:00 -2.2 -2.6
March 0.723268E+12 357160.31 31-MAR-24:00 -11.8 -13.4 0.223475E+10 2745.29 02-MAR-14:09 -11.8 -13.4
April 0.940816E+12 366184.45 21-APR-16:00 14.40 5.45 0.198297E+10 2745.29 03-APR-13:20 14.40 5.45
May 0.239222E+12 175474.50 31-MAY-24:00 12.40 8.53 0.214810E+10 2745.29 01-MAY-09:09 12.40 8.53
June 0.468875E+12 267228.23 30-JUN-24:00 15.10 14.10 0.214213E+10 2745.29 08-JUN-09:20 15.10 14.10
July 0.731046E+12 359866.43 31-JUL-23:57 16.60 11.46 0.198894E+10 2745.29 06-JUL-09:20 16.60 11.46
August 0.976981E+12 367550.47 28-AUG-16:00 20.00 12.62 0.223475E+10 2745.29 10-AUG-09:39 20.00 12.62
September 0.233120E+12 174609.41 30-SEP-24:00 1.30 -0.1 0.198297E+10 2745.29 14-SEP-13:20 1.30 -0.1
October 0.482325E+12 265540.68 31-OCT-24:00 -10.1 -11.0 0.206144E+10 2745.29 04-OCT-13:39 -10.1 -11.0
November 0.700357E+12 273142.11 03-NOV-16:00 -11.1 -11.5 0.204131E+10 2745.29 17-NOV-14:20 -21.3 -21.6
December 0.966991E+12 364746.61 26-DEC-17:00 -15.6 -15.9 0.198894E+10 2745.29 04-DEC-14:00 -15.6 -15.9
                     
Annual Sum or Average 0.712098E+13         0.247380E+11        
Minimum of Months 0.229573E+12 88695.84   -20.6 -20.9 0.187022E+10 2745.29   -21.3 -21.6
Maximum of Months 0.976981E+12 367550.47   20.00 14.10 0.223475E+10 2745.29   20.00 14.10



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.162769E+09 9531.16 23-JAN-06:04 -11.2
February 44129089.79 9565.76 02-FEB-06:03 -6.5
March 91668325.97 9623.24 20-MAR-03:03 -4.0
April 0.119981E+09 9989.39 27-APR-04:07 -2.2
May 0.216541E+09 10080.27 22-MAY-03:05 2.80
June 0.285304E+09 11555.73 13-JUN-03:53 11.70
July 0.405992E+09 14240.95 29-JUL-16:03 30.00
August 0.394682E+09 11165.14 14-AUG-02:63 12.20
September 0.437570E+09 10116.73 06-SEP-03:15 6.10
October 0.181330E+09 10000.87 04-OCT-04:07 7.80
November 93734966.44 9567.55 02-NOV-04:03 -11.6
December 0.148501E+09 9531.44 26-DEC-04:02 -12.7
         
Annual Sum or Average 0.258220E+10      
Minimum of Months 44129089.79 9531.16   -12.7
Maximum of Months 0.437570E+09 14240.95   30.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:02 -14.9
February 0.00 0.00 01-FEB-00:03 -20.2
March 0.00 0.00 01-MAR-00:10 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:03 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:10 -25.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.00 0.00   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.191530E+10 53159.12 02-JAN-04:01 -15.1
February 0.499577E+09 45787.49 27-FEB-05:11 -36.1
March 26502078.76 40570.52 06-MAR-06:01 -21.1
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:03 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 14771286.12 40518.76 30-OCT-05:01 -14.5
November 0.545168E+09 45658.77 27-NOV-05:01 -25.8
December 0.867096E+09 45919.88 04-DEC-05:01 -19.9
         
Annual Sum or Average 0.386841E+10      
Minimum of Months 0.00 0.00   -36.1
Maximum of Months 0.191530E+10 53159.12   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.159043E+11 72510.58 30-JAN-03:32 -25.0
February 0.102996E+11 72452.79 27-FEB-03:52 -34.4
March 0.585011E+10 71200.45 06-MAR-04:11 -20.0
April 0.124994E+10 67427.51 03-APR-03:01 -21.1
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:03 16.35
September 0.208714E+09 61872.48 25-SEP-04:01 -1.1
October 0.411263E+10 71127.89 30-OCT-03:11 -13.7
November 0.124882E+11 72169.60 13-NOV-04:11 -20.2
December 0.147849E+11 71847.31 04-DEC-04:01 -20.0
         
Annual Sum or Average 0.648985E+11      
Minimum of Months 0.00 0.00   -34.4
Maximum of Months 0.159043E+11 72510.58   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.214051E+10 11450.67 13-JAN-04:01 -33.2
February 0.894405E+09 11347.22 27-FEB-04:01 -34.7
March 0.307544E+09 11027.96 01-MAR-05:01 -28.3
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:03 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 28794634.05 9974.87 30-OCT-05:01 -14.5
November 0.720079E+09 10926.58 30-NOV-05:01 -27.8
December 0.152614E+10 10949.45 15-DEC-05:01 -33.2
         
Annual Sum or Average 0.561748E+10      
Minimum of Months 0.00 0.00   -34.7
Maximum of Months 0.214051E+10 11450.67   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.175462E+10 13522.94 13-JAN-04:01 -33.2
February 0.697731E+09 13394.08 27-FEB-04:01 -34.7
March 0.220414E+09 13004.55 01-MAR-05:01 -28.3
April 1676132.94 3858.06 03-APR-05:02 -21.2
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:03 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 39810467.32 11340.59 30-OCT-05:01 -14.5
November 0.851498E+09 13049.56 30-NOV-05:01 -27.8
December 0.187630E+10 12981.21 15-DEC-05:01 -33.2
         
Annual Sum or Average 0.544205E+10      
Minimum of Months 0.00 0.00   -34.7
Maximum of Months 0.187630E+10 13522.94   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.304351E+10 21861.87 30-JAN-04:01 -25.1
February 0.106452E+10 21382.64 27-FEB-04:01 -34.7
March 0.311075E+09 20334.91 01-MAR-05:01 -28.3
April 5623646.24 11442.05 03-APR-05:02 -21.2
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:03 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.116037E+09 19183.11 30-OCT-04:01 -14.4
November 0.133076E+10 20503.75 30-NOV-05:01 -27.8
December 0.291307E+10 21139.14 04-DEC-04:01 -20.0
         
Annual Sum or Average 0.878459E+10      
Minimum of Months 0.00 0.00   -34.7
Maximum of Months 0.304351E+10 21861.87   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.432164E+09 11255.22 12-JAN-05:01 -37.9
February 61934565.20 10753.24 27-FEB-05:01 -36.1
March 9116097.09 9694.20 01-MAR-06:01 -28.4
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:03 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 72986.76 851.51 30-OCT-05:01 -14.5
November 8563164.41 9711.94 29-NOV-06:01 -28.9
December 6388833.51 9624.17 15-DEC-06:01 -32.9
         
Annual Sum or Average 0.518240E+09      
Minimum of Months 0.00 0.00   -37.9
Maximum of Months 0.432164E+09 11255.22   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.864484E+10 12123.52 01-JAN-19:22 -14.4
February 0.541937E+10 12010.68 27-FEB-03:52 -34.4
March 0.303452E+10 11509.61 01-MAR-04:01 -27.9
April 0.384413E+09 10891.75 03-APR-03:01 -21.1
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:03 16.35
September 30011342.73 9217.97 30-SEP-05:03 -4.5
October 0.160054E+10 11447.30 30-OCT-03:01 -13.5
November 0.656643E+10 11760.25 27-NOV-04:01 -26.0
December 0.855916E+10 11778.17 11-DEC-01:42 -20.3
         
Annual Sum or Average 0.342393E+11      
Minimum of Months 0.00 0.00   -34.4
Maximum of Months 0.864484E+10 12123.52   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.600731E+10 17382.71 01-JAN-19:22 -14.4
February 0.319096E+10 17256.90 27-FEB-03:52 -34.4
March 0.122968E+10 16691.10 01-MAR-04:01 -27.9
April 0.147106E+09 14948.57 03-APR-04:01 -21.1
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:03 16.35
September 16202054.86 8265.87 30-SEP-05:03 -4.5
October 0.898804E+09 16590.99 30-OCT-03:01 -13.5
November 0.453950E+10 17139.14 27-NOV-04:01 -26.0
December 0.608100E+10 17074.27 04-DEC-04:01 -20.0
         
Annual Sum or Average 0.221106E+11      
Minimum of Months 0.00 0.00   -34.4
Maximum of Months 0.608100E+10 17382.71   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.749760E+10 25994.01 01-JAN-19:22 -14.4
February 0.313208E+10 25070.02 21-FEB-04:11 -22.8
March 0.118438E+10 24379.65 01-MAR-04:01 -27.9
April 95084171.28 21494.02 03-APR-04:01 -21.1
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:03 16.35
September 8395720.52 7681.92 28-SEP-05:03 -2.3
October 0.830738E+09 24384.24 30-OCT-03:01 -13.5
November 0.487856E+10 25576.17 27-NOV-04:01 -26.0
December 0.819000E+10 25628.57 04-DEC-04:01 -20.0
         
Annual Sum or Average 0.258168E+11      
Minimum of Months 0.00 0.00   -27.9
Maximum of Months 0.819000E+10 25994.01   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.488481E+10 16964.03 02-JAN-04:01 -15.1
February 0.247061E+10 16614.74 21-FEB-04:11 -22.8
March 0.109495E+10 15987.80 01-MAR-04:01 -27.9
April 62788229.23 14091.23 03-APR-04:01 -21.1
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:03 16.35
September 5790896.00 5877.69 30-SEP-05:03 -4.5
October 0.663501E+09 15792.31 30-OCT-03:01 -13.5
November 0.313453E+10 16712.49 27-NOV-04:01 -26.0
December 0.444894E+10 16682.68 04-DEC-04:01 -20.0
         
Annual Sum or Average 0.167659E+11      
Minimum of Months 0.00 0.00   -27.9
Maximum of Months 0.488481E+10 16964.03   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.160875E+11 16608.50 30-JAN-03:32 -25.0
February 0.122657E+11 16582.43 27-FEB-03:52 -34.4
March 0.884205E+10 15770.17 06-MAR-03:32 -19.6
April 0.231829E+10 15679.72 03-APR-02:53 -21.1
May 8378051.24 11979.35 27-MAY-05:03 0.10
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 20694606.33 12310.65 31-AUG-05:02 -1.2
September 0.843877E+09 13871.33 30-SEP-04:01 -4.0
October 0.617213E+10 15844.13 22-OCT-22:33 -15.8
November 0.143141E+11 16238.36 26-NOV-18:42 -24.1
December 0.166536E+11 16216.78 03-DEC-21:22 -22.2
         
Annual Sum or Average 0.775263E+11      
Minimum of Months 0.00 0.00   -34.4
Maximum of Months 0.166536E+11 16608.50   14.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.107753E+11 18358.27 30-JAN-03:32 -25.0
February 0.735010E+10 18320.23 27-FEB-03:52 -34.4
March 0.380203E+10 17467.29 06-MAR-04:11 -20.0
April 0.932740E+09 16706.43 04-APR-03:01 -10.5
May 1377941.16 6030.67 27-MAY-05:03 0.10
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 5964254.81 7288.19 31-AUG-05:02 -1.2
September 0.343292E+09 15258.46 30-SEP-04:01 -4.0
October 0.339189E+10 17446.99 30-OCT-03:11 -13.7
November 0.951593E+10 17885.97 26-NOV-18:42 -24.1
December 0.113546E+11 17877.23 03-DEC-17:22 -22.2
         
Annual Sum or Average 0.474733E+11      
Minimum of Months 0.00 0.00   -34.4
Maximum of Months 0.113546E+11 18358.27   14.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.146900E+11 28541.21 30-JAN-03:32 -25.0
February 0.836342E+10 28255.67 27-FEB-03:52 -34.4
March 0.441073E+10 27175.92 06-MAR-04:11 -20.0
April 0.100023E+10 25621.06 03-APR-03:01 -21.1
May 5941331.22 10770.48 27-MAY-05:03 0.10
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 2653666.79 5582.25 30-AUG-05:03 0.00
September 0.435076E+09 23528.18 28-SEP-04:01 -1.8
October 0.401120E+10 27177.72 30-OCT-03:11 -13.7
November 0.119473E+11 27691.09 13-NOV-01:32 -19.4
December 0.163740E+11 27846.21 03-DEC-17:22 -22.2
         
Annual Sum or Average 0.612406E+11      
Minimum of Months 0.00 0.00   -34.4
Maximum of Months 0.163740E+11 28541.21   14.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.971019E+10 19171.18 30-JAN-03:32 -25.0
February 0.614556E+10 18892.36 27-FEB-03:52 -34.4
March 0.359675E+10 18123.37 06-MAR-04:11 -20.0
April 0.605378E+09 17279.72 03-APR-03:01 -21.1
May 2857863.25 6091.08 27-MAY-05:03 0.10
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 158918.14 967.00 30-AUG-05:03 0.00
September 0.265118E+09 15754.15 25-SEP-04:01 -1.1
October 0.269816E+10 18125.12 30-OCT-03:11 -13.7
November 0.734018E+10 18415.07 27-NOV-04:01 -26.0
December 0.898891E+10 18354.09 04-DEC-04:01 -20.0
         
Annual Sum or Average 0.393533E+11      
Minimum of Months 0.00 0.00   -34.4
Maximum of Months 0.971019E+10 19171.18   14.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.302288E+10 4914.47 02-JAN-10:40 -17.6
February 0.166286E+10 9429.80 09-FEB-06:03 0.00
March 0.106921E+10 10664.51 07-MAR-06:01 -8.0
April 0.182913E+09 10503.62 10-APR-04:01 -5.3
May 88992554.15 8533.61 01-MAY-03:02 6.70
June 77607348.44 7755.74 26-JUN-03:02 12.70
July 0.112397E+09 8574.89 23-JUL-14:31 25.40
August 0.123121E+09 8746.30 27-AUG-15:32 20.77
September 52657855.18 7850.76 01-SEP-03:02 7.88
October 0.334105E+09 9644.26 24-OCT-05:01 -4.4
November 0.166366E+10 9423.63 01-NOV-05:03 -9.6
December 0.272759E+10 4146.17 04-DEC-06:05 -19.4
         
Annual Sum or Average 0.111180E+11      
Minimum of Months 52657855.18 4146.17   -19.4
Maximum of Months 0.302288E+10 10664.51   25.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.669901E+10 18716.26 02-JAN-06:25 -15.0
February 0.395689E+10 11224.88 27-FEB-06:15 -35.7
March 0.286597E+10 7339.30 27-MAR-13:20 -5.7
April 0.669518E+09 9735.17 09-APR-15:02 3.90
May 76002518.67 9758.13 28-MAY-16:22 16.40
June 43965732.28 6868.63 11-JUN-16:11 18.90
July 50020032.81 8474.48 23-JUL-15:11 25.60
August 41163137.67 7984.16 27-AUG-16:12 20.77
September 0.142040E+09 8422.23 10-SEP-10:43 14.13
October 0.143693E+10 5342.25 30-OCT-13:30 -11.6
November 0.471617E+10 11459.59 27-NOV-06:12 -26.7
December 0.590092E+10 11708.73 04-DEC-06:12 -19.4
         
Annual Sum or Average 0.265986E+11      
Minimum of Months 41163137.67 5342.25   -35.7
Maximum of Months 0.669901E+10 18716.26   25.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.247154E+11 32920.23 12-JAN-05:22 -38.0
February 0.186395E+11 33457.55 27-FEB-05:22 -36.1
March 0.137963E+11 29447.00 01-MAR-06:13 -28.5
April 0.439261E+10 26897.24 03-APR-04:23 -21.1
May 0.567321E+09 16238.64 11-MAY-05:02 4.68
June 0.127022E+09 16954.04 02-JUN-05:03 5.78
July 0.106945E+09 17221.44 06-JUL-05:02 8.77
August 0.406309E+09 13323.57 11-AUG-05:02 11.02
September 0.263644E+10 11742.18 25-SEP-05:15 -1.3
October 0.103338E+11 26300.40 30-OCT-04:13 -14.4
November 0.224939E+11 30564.53 27-NOV-06:12 -26.7
December 0.259404E+11 30402.97 06-DEC-05:32 -28.5
         
Annual Sum or Average 0.124156E+12      
Minimum of Months 0.106945E+09 11742.18   -38.0
Maximum of Months 0.259404E+11 33457.55   11.02



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 77126373.99 542.57 12-JAN-22:13 -36.3
February 0.00 0.00 01-FEB-00:03 -20.2
March 0.00 0.00 01-MAR-00:10 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:03 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:10 -25.8
         
Annual Sum or Average 77126373.99      
Minimum of Months 0.00 0.00   -36.3
Maximum of Months 77126373.99 542.57   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.725339E+09 558.01 12-JAN-22:13 -36.3
February 0.00 0.00 01-FEB-00:03 -20.2
March 0.00 0.00 01-MAR-00:10 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:03 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:10 -25.8
         
Annual Sum or Average 0.725339E+09      
Minimum of Months 0.00 0.00   -36.3
Maximum of Months 0.725339E+09 558.01   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.750362E+09 580.30 12-JAN-00:10 -36.1
February 0.268984E+09 569.54 26-FEB-17:40 -24.8
March 0.00 0.00 01-MAR-00:10 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 6345217.35 370.06 28-MAY-09:35 9.23
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:03 16.35
September 0.164155E+09 556.53 30-SEP-04:00 -3.9
October 85791774.58 547.49 22-OCT-22:20 -15.9
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:10 -25.8
         
Annual Sum or Average 0.127564E+10      
Minimum of Months 0.00 0.00   -36.1
Maximum of Months 0.750362E+09 580.30   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:02 -14.9
February 0.00 0.00 01-FEB-00:03 -20.2
March 0.00 0.00 01-MAR-00:10 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:03 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:10 -25.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.00 0.00   16.35



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.113123E+11 11837.83 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.102611E+11 11837.83 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.121930E+11 11837.83 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.108909E+11 11837.83 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.117527E+11 11837.83 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.116958E+11 11837.83 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.109477E+11 11837.83 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.121930E+11 11837.83 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.108909E+11 11837.83 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.113123E+11 11837.83 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.111797E+11 11837.83 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.109477E+11 11837.83 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.135577E+12     0.424397E+12    
Minimum of Months 0.102611E+11 11837.83   0.325565E+11 13457.54  
Maximum of Months 0.121930E+11 11837.83   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101592E+11 10631.20 02-JAN-08:09 0.243681E+11 17206.63 02-JAN-08:09
February 0.921518E+10 10631.20 01-FEB-08:09 0.220609E+11 17206.63 01-FEB-08:09
March 0.109502E+11 10631.20 01-MAR-08:09 0.253549E+11 17206.63 01-MAR-08:09
April 0.978077E+10 10631.20 03-APR-07:10 0.235306E+11 17206.63 03-APR-07:10
May 0.105547E+11 10631.20 01-MAY-07:10 0.248615E+11 17206.63 01-MAY-07:10
June 0.105037E+11 10631.20 01-JUN-07:10 0.244160E+11 17206.63 01-JUN-07:10
July 0.983180E+10 10631.20 03-JUL-07:10 0.239708E+11 17206.63 03-JUL-07:10
August 0.109502E+11 10631.20 01-AUG-07:10 0.253549E+11 17206.63 01-AUG-07:10
September 0.978077E+10 10631.20 01-SEP-07:10 0.235199E+11 17206.63 01-SEP-07:10
October 0.101592E+11 10631.20 02-OCT-07:10 0.243735E+11 17206.63 02-OCT-07:10
November 0.100402E+11 10631.20 01-NOV-07:10 0.238373E+11 17206.63 01-NOV-07:10
December 0.983180E+10 10631.20 01-DEC-08:09 0.239654E+11 17206.63 01-DEC-08:09
             
Annual Sum or Average 0.121758E+12     0.289614E+12    
Minimum of Months 0.921518E+10 10631.20   0.220609E+11 17206.63  
Maximum of Months 0.109502E+11 10631.20   0.253549E+11 17206.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101592E+11 10631.20 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.921518E+10 10631.20 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.109502E+11 10631.20 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.978077E+10 10631.20 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.105547E+11 10631.20 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.105037E+11 10631.20 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.983180E+10 10631.20 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.109502E+11 10631.20 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.978077E+10 10631.20 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.101592E+11 10631.20 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.100402E+11 10631.20 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.983180E+10 10631.20 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.121758E+12     0.289613E+12    
Minimum of Months 0.921518E+10 10631.20   0.220609E+11 17206.56  
Maximum of Months 0.109502E+11 10631.20   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101592E+11 10631.20 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.921518E+10 10631.20 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.109502E+11 10631.20 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.978077E+10 10631.20 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.105547E+11 10631.20 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.105037E+11 10631.20 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.983180E+10 10631.20 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.109502E+11 10631.20 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.978077E+10 10631.20 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.101592E+11 10631.20 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.100402E+11 10631.20 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.983180E+10 10631.20 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.121758E+12     0.289613E+12    
Minimum of Months 0.921518E+10 10631.20   0.220609E+11 17206.56  
Maximum of Months 0.109502E+11 10631.20   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.120591E+10 1334.85 02-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.922750E+09 1334.85 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.850660E+09 1334.85 01-MAR-08:09 0.318369E+10 2160.55 01-MAR-08:09
April 0.655061E+09 883.98 04-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.675519E+09 674.82 08-MAY-14:30 0.312174E+10 2160.55 01-MAY-07:10
June 0.655316E+09 635.12 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.624721E+09 698.73 26-JUL-14:30 0.300989E+10 2160.55 03-JUL-07:10
August 0.724584E+09 715.66 18-AUG-15:00 0.318369E+10 2160.55 01-AUG-07:10
September 0.723977E+09 1280.12 28-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.914414E+09 1334.85 03-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.113051E+10 1334.85 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.121196E+10 1334.85 01-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.102954E+11     0.363654E+11    
Minimum of Months 0.624721E+09 635.12   0.277008E+10 2160.55  
Maximum of Months 0.121196E+10 1334.85   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.754763E+09 860.23 02-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.566025E+09 860.23 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.536232E+09 860.23 01-MAR-08:09 0.205169E+10 1392.34 01-MAR-08:09
April 0.422324E+09 446.78 04-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.443355E+09 427.98 26-MAY-15:00 0.201177E+10 1392.34 01-MAY-07:10
June 0.429592E+09 409.30 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.408819E+09 434.31 26-JUL-14:30 0.193969E+10 1392.34 03-JUL-07:10
August 0.471257E+09 462.72 18-AUG-15:00 0.205169E+10 1392.34 01-AUG-07:10
September 0.458988E+09 760.99 28-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.563127E+09 860.23 03-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.699304E+09 860.23 01-NOV-07:10 0.192889E+10 1392.34 01-NOV-07:10
December 0.774826E+09 860.23 01-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.652861E+10     0.234352E+11    
Minimum of Months 0.408819E+09 409.30   0.178515E+10 1392.34  
Maximum of Months 0.774826E+09 860.23   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.112631E+10 1334.88 02-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.836193E+09 1334.88 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.812931E+09 1334.88 01-MAR-08:09 0.318374E+10 2160.58 01-MAR-08:09
April 0.657580E+09 882.32 04-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.686327E+09 635.14 01-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.666956E+09 635.14 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.634220E+09 684.62 25-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.728051E+09 688.71 18-AUG-15:00 0.318374E+10 2160.58 01-AUG-07:10
September 0.700861E+09 1237.68 28-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.844074E+09 1334.88 03-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.102183E+10 1334.88 01-NOV-07:10 0.299318E+10 2160.58 01-NOV-07:10
December 0.117865E+10 1334.88 01-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.989398E+10     0.363660E+11    
Minimum of Months 0.634220E+09 635.14   0.277013E+10 2160.58  
Maximum of Months 0.117865E+10 1334.88   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.762482E+09 860.23 02-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.560670E+09 860.23 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.535321E+09 860.23 01-MAR-08:09 0.205168E+10 1392.33 01-MAR-08:09
April 0.426548E+09 644.33 04-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.436149E+09 434.10 23-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.424330E+09 446.80 27-JUN-07:30 0.197570E+10 1392.33 01-JUN-07:10
July 0.403924E+09 460.29 25-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.466281E+09 460.45 07-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.458338E+09 827.29 29-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.562895E+09 860.23 03-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.698558E+09 860.23 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.777447E+09 860.23 01-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.651294E+10     0.234351E+11    
Minimum of Months 0.403924E+09 434.10   0.178514E+10 1392.33  
Maximum of Months 0.777447E+09 860.23   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.120773E+10 1334.85 02-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.925523E+09 1334.85 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.850968E+09 1334.85 01-MAR-08:09 0.318369E+10 2160.55 01-MAR-08:09
April 0.655043E+09 893.95 04-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.674777E+09 670.68 08-MAY-14:30 0.312174E+10 2160.55 01-MAY-07:10
June 0.655433E+09 635.12 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.624851E+09 694.97 26-JUL-14:30 0.300989E+10 2160.55 03-JUL-07:10
August 0.725185E+09 712.86 18-AUG-15:00 0.318369E+10 2160.55 01-AUG-07:10
September 0.723403E+09 1281.64 28-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.915836E+09 1334.85 03-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.113370E+10 1334.85 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.121262E+10 1334.85 01-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.103051E+11     0.363654E+11    
Minimum of Months 0.624851E+09 635.12   0.277008E+10 2160.55  
Maximum of Months 0.121262E+10 1334.85   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.755245E+09 860.23 02-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.566141E+09 860.23 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.536057E+09 860.23 01-MAR-08:09 0.205169E+10 1392.34 01-MAR-08:09
April 0.422327E+09 445.29 04-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.443270E+09 409.30 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.429527E+09 409.30 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.408752E+09 431.40 26-JUL-14:30 0.193969E+10 1392.34 03-JUL-07:10
August 0.471104E+09 460.73 18-AUG-15:00 0.205169E+10 1392.34 01-AUG-07:10
September 0.458818E+09 764.05 28-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.563132E+09 860.23 03-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.698585E+09 860.23 01-NOV-07:10 0.192889E+10 1392.34 01-NOV-07:10
December 0.775102E+09 860.23 01-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.652806E+10     0.234352E+11    
Minimum of Months 0.408752E+09 409.30   0.178515E+10 1392.34  
Maximum of Months 0.775102E+09 860.23   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.112869E+10 1334.88 02-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.836808E+09 1334.88 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.814869E+09 1334.88 01-MAR-08:09 0.318374E+10 2160.58 01-MAR-08:09
April 0.657839E+09 892.30 04-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.686560E+09 635.14 01-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.667202E+09 635.14 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.634408E+09 681.45 25-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.728146E+09 685.62 18-AUG-15:00 0.318374E+10 2160.58 01-AUG-07:10
September 0.701147E+09 1240.61 28-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.845188E+09 1334.88 03-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.102445E+10 1334.88 01-NOV-07:10 0.299318E+10 2160.58 01-NOV-07:10
December 0.118267E+10 1334.88 01-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.990797E+10     0.363660E+11    
Minimum of Months 0.634408E+09 635.14   0.277013E+10 2160.58  
Maximum of Months 0.118267E+10 1334.88   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.762989E+09 860.23 02-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.560706E+09 860.23 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.535204E+09 860.23 01-MAR-08:09 0.205168E+10 1392.33 01-MAR-08:09
April 0.426361E+09 644.77 04-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.436095E+09 431.22 23-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.424300E+09 444.29 27-JUN-07:30 0.197570E+10 1392.33 01-JUN-07:10
July 0.404040E+09 458.21 25-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.466089E+09 458.39 07-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.458463E+09 827.88 29-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.562660E+09 860.23 03-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.700547E+09 860.23 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.777658E+09 860.23 01-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.651511E+10     0.234351E+11    
Minimum of Months 0.404040E+09 431.22   0.178514E+10 1392.33  
Maximum of Months 0.777658E+09 860.23   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.120773E+10 1334.85 02-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.925495E+09 1334.85 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.850929E+09 1334.85 01-MAR-08:09 0.318369E+10 2160.55 01-MAR-08:09
April 0.655008E+09 893.63 04-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.674763E+09 670.42 08-MAY-14:30 0.312174E+10 2160.55 01-MAY-07:10
June 0.655424E+09 635.12 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.624845E+09 694.80 26-JUL-14:30 0.300989E+10 2160.55 03-JUL-07:10
August 0.725172E+09 712.66 18-AUG-15:00 0.318369E+10 2160.55 01-AUG-07:10
September 0.723320E+09 1281.68 28-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.915762E+09 1334.85 03-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.113368E+10 1334.85 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.121262E+10 1334.85 01-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.103048E+11     0.363654E+11    
Minimum of Months 0.624845E+09 635.12   0.277008E+10 2160.55  
Maximum of Months 0.121262E+10 1334.85   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.755252E+09 860.23 02-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.566135E+09 860.23 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.536051E+09 860.23 01-MAR-08:09 0.205169E+10 1392.34 01-MAR-08:09
April 0.422320E+09 445.18 04-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.443268E+09 409.30 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.429521E+09 409.30 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.408745E+09 431.26 26-JUL-14:30 0.193969E+10 1392.34 03-JUL-07:10
August 0.471098E+09 460.61 18-AUG-15:00 0.205169E+10 1392.34 01-AUG-07:10
September 0.458783E+09 764.29 28-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.563086E+09 860.23 03-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.698582E+09 860.23 01-NOV-07:10 0.192889E+10 1392.34 01-NOV-07:10
December 0.775109E+09 860.23 01-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.652795E+10     0.234352E+11    
Minimum of Months 0.408745E+09 409.30   0.178515E+10 1392.34  
Maximum of Months 0.775109E+09 860.23   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.112871E+10 1334.88 02-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.836817E+09 1334.88 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.814847E+09 1334.88 01-MAR-08:09 0.318374E+10 2160.58 01-MAR-08:09
April 0.657844E+09 891.99 04-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.686548E+09 635.14 01-MAY-07:10 0.312179E+10 2160.58 01-MAY-07:10
June 0.667196E+09 635.14 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.634396E+09 681.20 25-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.728137E+09 685.36 18-AUG-15:00 0.318374E+10 2160.58 01-AUG-07:10
September 0.701110E+09 1240.73 28-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.845176E+09 1334.88 03-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.102447E+10 1334.88 01-NOV-07:10 0.299318E+10 2160.58 01-NOV-07:10
December 0.118273E+10 1334.88 01-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.990799E+10     0.363660E+11    
Minimum of Months 0.634396E+09 635.14   0.277013E+10 2160.58  
Maximum of Months 0.118273E+10 1334.88   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.762997E+09 860.23 02-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.560695E+09 860.23 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.535191E+09 860.23 01-MAR-08:09 0.205168E+10 1392.33 01-MAR-08:09
April 0.426355E+09 644.58 04-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.436095E+09 431.06 23-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.424298E+09 444.14 27-JUN-07:30 0.197570E+10 1392.33 01-JUN-07:10
July 0.404031E+09 458.08 25-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.466094E+09 458.27 07-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.458424E+09 827.92 29-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.562678E+09 860.23 03-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.700546E+09 860.23 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.777661E+09 860.23 01-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.651507E+10     0.234351E+11    
Minimum of Months 0.404031E+09 431.06   0.178514E+10 1392.33  
Maximum of Months 0.777661E+09 860.23   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272315E+09 284.97 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.247010E+09 284.97 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.293517E+09 284.97 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.262171E+09 284.97 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.282916E+09 284.97 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.281548E+09 284.97 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.263538E+09 284.97 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.293517E+09 284.97 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.262171E+09 284.97 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.272315E+09 284.97 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.269124E+09 284.97 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.263538E+09 284.97 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.326368E+10     0.153881E+12    
Minimum of Months 0.247010E+09 284.97   0.505780E+10 1948.61  
Maximum of Months 0.293517E+09 284.97   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272315E+09 284.97 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.247010E+09 284.97 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.293517E+09 284.97 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.262171E+09 284.97 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.282916E+09 284.97 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.281548E+09 284.97 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.263538E+09 284.97 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.293517E+09 284.97 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.262171E+09 284.97 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.272315E+09 284.97 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.269124E+09 284.97 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.263538E+09 284.97 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.326368E+10     0.153881E+12    
Minimum of Months 0.247010E+09 284.97   0.505780E+10 1948.61  
Maximum of Months 0.293517E+09 284.97   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272315E+09 284.97 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.247010E+09 284.97 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.293517E+09 284.97 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.262171E+09 284.97 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.282916E+09 284.97 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.281548E+09 284.97 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.263538E+09 284.97 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.293517E+09 284.97 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.262171E+09 284.97 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.272315E+09 284.97 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.269124E+09 284.97 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.263538E+09 284.97 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.326368E+10     0.153881E+12    
Minimum of Months 0.247010E+09 284.97   0.505780E+10 1948.61  
Maximum of Months 0.293517E+09 284.97   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.318958E+10 3337.76 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.289319E+10 3337.76 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.343791E+10 3337.76 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.307076E+10 3337.76 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.331375E+10 3337.76 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.329773E+10 3337.76 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.308678E+10 3337.76 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.343791E+10 3337.76 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.307076E+10 3337.76 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.318958E+10 3337.76 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.315220E+10 3337.76 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.308678E+10 3337.76 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.382269E+11     0.749486E+13    
Minimum of Months 0.289319E+10 3337.76   0.246344E+12 94908.13  
Maximum of Months 0.343791E+10 3337.76   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.113123E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.102611E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.121930E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.108909E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.117527E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.116958E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.109477E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.121930E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.108909E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.113123E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.111797E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.109477E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.135577E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.102611E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.121930E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.101592E+11 0.243681E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.109502E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.978077E+10 0.235306E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.105547E+11 0.248615E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.105037E+11 0.244160E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.983180E+10 0.239708E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.109502E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.978077E+10 0.235199E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.101592E+11 0.243735E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.100402E+11 0.238373E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.983180E+10 0.239654E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.121758E+12 0.289614E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.109502E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.101592E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.978077E+10 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.105547E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.105037E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.983180E+10 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.978077E+10 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.101592E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.100402E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.983180E+10 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.121758E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.101592E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.978077E+10 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.105547E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.105037E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.983180E+10 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.978077E+10 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.101592E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.100402E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.983180E+10 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.121758E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.120591E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.197346E+09
February 0.136985E+10 0.922750E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.160175E+09
March 0.163685E+10 0.850660E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.245409E+09
April 0.145243E+10 0.655061E+09 0.295462E+10 0.00 0.00 0.00 0.00 0.00 0.281751E+09
May 0.157338E+10 0.675519E+09 0.312174E+10 0.00 0.00 0.00 0.00 0.00 0.163548E+09
June 0.156900E+10 0.655316E+09 0.306580E+10 0.00 0.00 0.00 0.00 200320.76 95359559.35
July 0.145680E+10 0.624721E+09 0.300989E+10 0.00 0.00 0.00 0.00 643307.43 68457771.91
August 0.163685E+10 0.724584E+09 0.318369E+10 0.00 0.00 0.00 0.00 95044.02 82952734.39
September 0.145243E+10 0.723977E+09 0.295328E+10 0.00 0.00 0.00 0.00 0.00 0.102632E+09
October 0.150991E+10 0.914414E+09 0.306046E+10 0.00 0.00 0.00 0.00 0.00 0.220418E+09
November 0.149516E+10 0.113051E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 75111088.96
December 0.145680E+10 0.121196E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.146676E+09
                   
Annual Sum or Average 0.181194E+11 0.102954E+11 0.363654E+11 0.00 0.00 0.00 0.00 938672.20 0.183984E+10
Minimum of Months 0.136985E+10 0.624721E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 68457771.91
Maximum of Months 0.163685E+10 0.121196E+10 0.318369E+10 0.00 0.00 0.00 0.00 643307.43 0.281751E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.754763E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.130661E+09
February 0.882782E+09 0.566025E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.106167E+09
March 0.105485E+10 0.536232E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.163692E+09
April 0.936002E+09 0.422324E+09 0.190407E+10 0.00 0.00 0.00 0.00 0.00 0.187130E+09
May 0.101394E+10 0.443355E+09 0.201177E+10 0.00 0.00 0.00 0.00 0.00 0.109855E+09
June 0.101113E+10 0.429592E+09 0.197572E+10 0.00 0.00 0.00 0.00 135062.90 62036669.81
July 0.938820E+09 0.408819E+09 0.193969E+10 0.00 0.00 0.00 0.00 456579.37 43852936.51
August 0.105485E+10 0.471257E+09 0.205169E+10 0.00 0.00 0.00 0.00 63467.57 53081412.12
September 0.936002E+09 0.458988E+09 0.190321E+10 0.00 0.00 0.00 0.00 0.00 68828045.87
October 0.973041E+09 0.563127E+09 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.145818E+09
November 0.963541E+09 0.699304E+09 0.192889E+10 0.00 0.00 0.00 0.00 0.00 49419004.33
December 0.938820E+09 0.774826E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 96279407.17
                   
Annual Sum or Average 0.116768E+11 0.652861E+10 0.234352E+11 0.00 0.00 0.00 0.00 655109.84 0.121682E+10
Minimum of Months 0.882782E+09 0.408819E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 43852936.51
Maximum of Months 0.105485E+10 0.774826E+09 0.205169E+10 0.00 0.00 0.00 0.00 456579.37 0.187130E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.112631E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.193679E+09
February 0.136988E+10 0.836193E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.159401E+09
March 0.163688E+10 0.812931E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.247061E+09
April 0.145246E+10 0.657580E+09 0.295467E+10 0.00 0.00 0.00 0.00 0.00 0.286650E+09
May 0.157341E+10 0.686327E+09 0.312179E+10 0.00 0.00 0.00 0.00 0.00 0.165158E+09
June 0.156904E+10 0.666956E+09 0.306585E+10 0.00 0.00 0.00 0.00 201143.56 94515123.92
July 0.145684E+10 0.634220E+09 0.300994E+10 0.00 0.00 0.00 0.00 593986.32 68039037.26
August 0.163688E+10 0.728051E+09 0.318374E+10 0.00 0.00 0.00 0.00 94841.27 83128138.22
September 0.145246E+10 0.700861E+09 0.295333E+10 0.00 0.00 0.00 0.00 0.00 0.103066E+09
October 0.150994E+10 0.844074E+09 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.216586E+09
November 0.149520E+10 0.102183E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 73525401.27
December 0.145684E+10 0.117865E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.142788E+09
                   
Annual Sum or Average 0.181198E+11 0.989398E+10 0.363660E+11 0.00 0.00 0.00 0.00 889971.15 0.183360E+10
Minimum of Months 0.136988E+10 0.634220E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 68039037.26
Maximum of Months 0.163688E+10 0.117865E+10 0.318374E+10 0.00 0.00 0.00 0.00 593986.32 0.286650E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.762482E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.134613E+09
February 0.882782E+09 0.560670E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.110568E+09
March 0.105485E+10 0.535321E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.173781E+09
April 0.936002E+09 0.426548E+09 0.190406E+10 0.00 0.00 0.00 0.00 0.00 0.206888E+09
May 0.101394E+10 0.436149E+09 0.201175E+10 0.00 0.00 0.00 0.00 0.00 0.116383E+09
June 0.101113E+10 0.424330E+09 0.197570E+10 0.00 0.00 0.00 0.00 133140.34 69135508.96
July 0.938820E+09 0.403924E+09 0.193968E+10 0.00 0.00 0.00 0.00 334440.09 50714042.13
August 0.105485E+10 0.466281E+09 0.205168E+10 0.00 0.00 0.00 0.00 63350.33 61544704.03
September 0.936002E+09 0.458338E+09 0.190319E+10 0.00 0.00 0.00 0.00 0.00 72273494.02
October 0.973041E+09 0.562895E+09 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.154579E+09
November 0.963541E+09 0.698558E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 52547876.37
December 0.938820E+09 0.777447E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.103208E+09
                   
Annual Sum or Average 0.116768E+11 0.651294E+10 0.234351E+11 0.00 0.00 0.00 0.00 530930.76 0.130624E+10
Minimum of Months 0.882782E+09 0.403924E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 50714042.13
Maximum of Months 0.105485E+10 0.777447E+09 0.205168E+10 0.00 0.00 0.00 0.00 334440.09 0.206888E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.120773E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.439871E+09
February 0.136985E+10 0.925523E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.355348E+09
March 0.163685E+10 0.850968E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.534267E+09
April 0.145243E+10 0.655043E+09 0.295462E+10 0.00 0.00 0.00 0.00 0.00 0.604850E+09
May 0.157338E+10 0.674777E+09 0.312174E+10 0.00 0.00 0.00 0.00 0.00 0.367648E+09
June 0.156900E+10 0.655433E+09 0.306580E+10 0.00 0.00 0.00 0.00 436880.74 0.218267E+09
July 0.145680E+10 0.624851E+09 0.300989E+10 0.00 0.00 0.00 0.00 1544660.41 0.161175E+09
August 0.163685E+10 0.725185E+09 0.318369E+10 0.00 0.00 0.00 0.00 195105.02 0.189649E+09
September 0.145243E+10 0.723403E+09 0.295328E+10 0.00 0.00 0.00 0.00 0.00 0.222501E+09
October 0.150991E+10 0.915836E+09 0.306046E+10 0.00 0.00 0.00 0.00 0.00 0.468189E+09
November 0.149516E+10 0.113370E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.163269E+09
December 0.145680E+10 0.121262E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.320048E+09
                   
Annual Sum or Average 0.181194E+11 0.103051E+11 0.363654E+11 0.00 0.00 0.00 0.00 2176646.16 0.404508E+10
Minimum of Months 0.136985E+10 0.624851E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.161175E+09
Maximum of Months 0.163685E+10 0.121262E+10 0.318369E+10 0.00 0.00 0.00 0.00 1544660.41 0.604850E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.755245E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.293337E+09
February 0.649041E+09 0.566141E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.237441E+09
March 0.773965E+09 0.536057E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.362481E+09
April 0.688021E+09 0.422327E+09 0.190407E+10 0.00 0.00 0.00 0.00 0.00 0.418023E+09
May 0.744847E+09 0.443270E+09 0.201177E+10 0.00 0.00 0.00 0.00 0.00 0.252226E+09
June 0.742030E+09 0.429527E+09 0.197572E+10 0.00 0.00 0.00 0.00 294564.92 0.146069E+09
July 0.690839E+09 0.408752E+09 0.193969E+10 0.00 0.00 0.00 0.00 1016263.55 0.109062E+09
August 0.773965E+09 0.471104E+09 0.205169E+10 0.00 0.00 0.00 0.00 131600.28 0.128445E+09
September 0.688021E+09 0.458818E+09 0.190321E+10 0.00 0.00 0.00 0.00 0.00 0.153094E+09
October 0.715730E+09 0.563132E+09 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.315481E+09
November 0.708685E+09 0.698585E+09 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.108698E+09
December 0.690839E+09 0.775102E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.213068E+09
                   
Annual Sum or Average 0.858171E+10 0.652806E+10 0.234352E+11 0.00 0.00 0.00 0.00 1442428.75 0.273742E+10
Minimum of Months 0.649041E+09 0.408752E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.108698E+09
Maximum of Months 0.773965E+09 0.775102E+09 0.205169E+10 0.00 0.00 0.00 0.00 1016263.55 0.418023E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.112869E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.441612E+09
February 0.136988E+10 0.836808E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.361977E+09
March 0.163688E+10 0.814869E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.561661E+09
April 0.145246E+10 0.657839E+09 0.295467E+10 0.00 0.00 0.00 0.00 0.00 0.661108E+09
May 0.157341E+10 0.686560E+09 0.312179E+10 0.00 0.00 0.00 0.00 0.00 0.384548E+09
June 0.156904E+10 0.667202E+09 0.306585E+10 0.00 0.00 0.00 0.00 438908.87 0.221328E+09
July 0.145684E+10 0.634408E+09 0.300994E+10 0.00 0.00 0.00 0.00 1304950.22 0.166209E+09
August 0.163688E+10 0.728146E+09 0.318374E+10 0.00 0.00 0.00 0.00 194557.89 0.199378E+09
September 0.145246E+10 0.701147E+09 0.295333E+10 0.00 0.00 0.00 0.00 0.00 0.238349E+09
October 0.150994E+10 0.845188E+09 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.488068E+09
November 0.149520E+10 0.102445E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.164763E+09
December 0.145684E+10 0.118267E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.320702E+09
                   
Annual Sum or Average 0.181198E+11 0.990797E+10 0.363660E+11 0.00 0.00 0.00 0.00 1938416.98 0.420970E+10
Minimum of Months 0.136988E+10 0.634408E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.164763E+09
Maximum of Months 0.163688E+10 0.118267E+10 0.318374E+10 0.00 0.00 0.00 0.00 1304950.22 0.661108E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.762989E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.295277E+09
February 0.882782E+09 0.560706E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.239576E+09
March 0.105485E+10 0.535204E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.365752E+09
April 0.936002E+09 0.426361E+09 0.190406E+10 0.00 0.00 0.00 0.00 0.00 0.438271E+09
May 0.101394E+10 0.436095E+09 0.201175E+10 0.00 0.00 0.00 0.00 0.00 0.260250E+09
June 0.101113E+10 0.424300E+09 0.197570E+10 0.00 0.00 0.00 0.00 290223.43 0.152665E+09
July 0.938820E+09 0.404040E+09 0.193968E+10 0.00 0.00 0.00 0.00 756620.75 0.114453E+09
August 0.105485E+10 0.466089E+09 0.205168E+10 0.00 0.00 0.00 0.00 130001.43 0.134256E+09
September 0.936002E+09 0.458463E+09 0.190319E+10 0.00 0.00 0.00 0.00 0.00 0.154578E+09
October 0.973041E+09 0.562660E+09 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.319290E+09
November 0.963541E+09 0.700547E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.110461E+09
December 0.938820E+09 0.777658E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.216360E+09
                   
Annual Sum or Average 0.116768E+11 0.651511E+10 0.234351E+11 0.00 0.00 0.00 0.00 1176845.61 0.280119E+10
Minimum of Months 0.882782E+09 0.404040E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.110461E+09
Maximum of Months 0.105485E+10 0.777658E+09 0.205168E+10 0.00 0.00 0.00 0.00 756620.75 0.438271E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.120773E+10 0.305979E+10 0.00 0.00 0.00 0.00 0.00 0.538883E+09
February 0.136985E+10 0.925495E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.432902E+09
March 0.163685E+10 0.850929E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.00 0.636103E+09
April 0.145243E+10 0.655008E+09 0.295462E+10 0.00 0.00 0.00 0.00 0.00 0.694605E+09
May 0.157338E+10 0.674763E+09 0.312174E+10 0.00 0.00 0.00 0.00 0.00 0.424498E+09
June 0.156900E+10 0.655424E+09 0.306580E+10 0.00 0.00 0.00 0.00 503034.15 0.261713E+09
July 0.145680E+10 0.624845E+09 0.300989E+10 0.00 0.00 0.00 0.00 1846606.97 0.194931E+09
August 0.163685E+10 0.725172E+09 0.318369E+10 0.00 0.00 0.00 0.00 220840.66 0.222984E+09
September 0.145243E+10 0.723320E+09 0.295328E+10 0.00 0.00 0.00 0.00 0.00 0.246541E+09
October 0.150991E+10 0.915762E+09 0.306046E+10 0.00 0.00 0.00 0.00 0.00 0.538386E+09
November 0.149516E+10 0.113368E+10 0.299314E+10 0.00 0.00 0.00 0.00 0.00 0.198174E+09
December 0.145680E+10 0.121262E+10 0.300922E+10 0.00 0.00 0.00 0.00 0.00 0.390344E+09
                   
Annual Sum or Average 0.181194E+11 0.103048E+11 0.363654E+11 0.00 0.00 0.00 0.00 2570481.78 0.478006E+10
Minimum of Months 0.136985E+10 0.624845E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.194931E+09
Maximum of Months 0.163685E+10 0.121262E+10 0.318369E+10 0.00 0.00 0.00 0.00 1846606.97 0.694605E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.755252E+09 0.197184E+10 0.00 0.00 0.00 0.00 0.00 0.360117E+09
February 0.882782E+09 0.566135E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.289443E+09
March 0.105485E+10 0.536051E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.00 0.428922E+09
April 0.936002E+09 0.422320E+09 0.190407E+10 0.00 0.00 0.00 0.00 0.00 0.483370E+09
May 0.101394E+10 0.443268E+09 0.201177E+10 0.00 0.00 0.00 0.00 0.00 0.300109E+09
June 0.101113E+10 0.429521E+09 0.197572E+10 0.00 0.00 0.00 0.00 337194.80 0.178270E+09
July 0.938820E+09 0.408745E+09 0.193969E+10 0.00 0.00 0.00 0.00 1109303.18 0.134719E+09
August 0.105485E+10 0.471098E+09 0.205169E+10 0.00 0.00 0.00 0.00 139786.14 0.155059E+09
September 0.936002E+09 0.458783E+09 0.190321E+10 0.00 0.00 0.00 0.00 0.00 0.173609E+09
October 0.973041E+09 0.563086E+09 0.197228E+10 0.00 0.00 0.00 0.00 0.00 0.362468E+09
November 0.963541E+09 0.698582E+09 0.192889E+10 0.00 0.00 0.00 0.00 0.00 0.132333E+09
December 0.938820E+09 0.775109E+09 0.193926E+10 0.00 0.00 0.00 0.00 0.00 0.260766E+09
                   
Annual Sum or Average 0.116768E+11 0.652795E+10 0.234352E+11 0.00 0.00 0.00 0.00 1586284.12 0.325919E+10
Minimum of Months 0.882782E+09 0.408745E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.132333E+09
Maximum of Months 0.105485E+10 0.775109E+09 0.205169E+10 0.00 0.00 0.00 0.00 1109303.18 0.483370E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.112871E+10 0.305983E+10 0.00 0.00 0.00 0.00 0.00 0.541095E+09
February 0.136988E+10 0.836817E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.437164E+09
March 0.163688E+10 0.814847E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.00 0.661093E+09
April 0.145246E+10 0.657844E+09 0.295467E+10 0.00 0.00 0.00 0.00 0.00 0.767603E+09
May 0.157341E+10 0.686548E+09 0.312179E+10 0.00 0.00 0.00 0.00 0.00 0.457038E+09
June 0.156904E+10 0.667196E+09 0.306585E+10 0.00 0.00 0.00 0.00 503710.13 0.268725E+09
July 0.145684E+10 0.634396E+09 0.300994E+10 0.00 0.00 0.00 0.00 1452157.15 0.204052E+09
August 0.163688E+10 0.728137E+09 0.318374E+10 0.00 0.00 0.00 0.00 208965.90 0.240411E+09
September 0.145246E+10 0.701110E+09 0.295333E+10 0.00 0.00 0.00 0.00 0.00 0.272341E+09
October 0.150994E+10 0.845176E+09 0.306051E+10 0.00 0.00 0.00 0.00 0.00 0.556910E+09
November 0.149520E+10 0.102447E+10 0.299318E+10 0.00 0.00 0.00 0.00 0.00 0.199141E+09
December 0.145684E+10 0.118273E+10 0.300927E+10 0.00 0.00 0.00 0.00 0.00 0.391533E+09
                   
Annual Sum or Average 0.181198E+11 0.990799E+10 0.363660E+11 0.00 0.00 0.00 0.00 2164833.18 0.499711E+10
Minimum of Months 0.136988E+10 0.634396E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.199141E+09
Maximum of Months 0.163688E+10 0.118273E+10 0.318374E+10 0.00 0.00 0.00 0.00 1452157.15 0.767603E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.762997E+09 0.197183E+10 0.00 0.00 0.00 0.00 0.00 0.361383E+09
February 0.882782E+09 0.560695E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.291452E+09
March 0.105485E+10 0.535191E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.00 0.434017E+09
April 0.936002E+09 0.426355E+09 0.190406E+10 0.00 0.00 0.00 0.00 0.00 0.510741E+09
May 0.101394E+10 0.436095E+09 0.201175E+10 0.00 0.00 0.00 0.00 0.00 0.309771E+09
June 0.101113E+10 0.424298E+09 0.197570E+10 0.00 0.00 0.00 0.00 334012.48 0.185582E+09
July 0.938820E+09 0.404031E+09 0.193968E+10 0.00 0.00 0.00 0.00 870536.10 0.140387E+09
August 0.105485E+10 0.466094E+09 0.205168E+10 0.00 0.00 0.00 0.00 139618.31 0.161561E+09
September 0.936002E+09 0.458424E+09 0.190319E+10 0.00 0.00 0.00 0.00 0.00 0.177158E+09
October 0.973041E+09 0.562678E+09 0.197226E+10 0.00 0.00 0.00 0.00 0.00 0.369777E+09
November 0.963541E+09 0.700546E+09 0.192888E+10 0.00 0.00 0.00 0.00 0.00 0.133324E+09
December 0.938820E+09 0.777661E+09 0.193924E+10 0.00 0.00 0.00 0.00 0.00 0.262229E+09
                   
Annual Sum or Average 0.116768E+11 0.651507E+10 0.234351E+11 0.00 0.00 0.00 0.00 1344166.88 0.333738E+10
Minimum of Months 0.882782E+09 0.404031E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.133324E+09
Maximum of Months 0.105485E+10 0.777661E+09 0.205168E+10 0.00 0.00 0.00 0.00 870536.10 0.510741E+09



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.272315E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.247010E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.293517E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.262171E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.282916E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.281548E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.263538E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.293517E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.262171E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.272315E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.269124E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.263538E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.326368E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.247010E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.293517E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.272315E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.247010E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.293517E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.262171E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.282916E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.281548E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.263538E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.293517E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.262171E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.272315E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.269124E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.263538E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.326368E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.247010E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.293517E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.272315E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.247010E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.293517E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.262171E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.282916E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.281548E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.263538E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.293517E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.262171E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.272315E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.269124E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.263538E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.326368E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.247010E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.293517E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.318958E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.289319E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.343791E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.307076E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.331375E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.329773E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.308678E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.343791E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.307076E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.318958E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.315220E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.308678E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.382269E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.289319E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.343791E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.412054E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.335532E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.514892E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.589147E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.336833E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 240250.76 0.193216E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 955663.36 0.140938E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 68306.39 0.173972E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.213747E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.461271E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.157554E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.304829E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1264220.50 0.383399E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.140938E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 955663.36 0.589147E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.702270E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.575312E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.882251E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.101460E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.595319E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 419808.54 0.342201E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1830277.81 0.251047E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 119076.74 0.308323E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.372464E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.783862E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.267049E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.515770E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2369163.09 0.661047E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.251047E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1830277.81 0.101460E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.767416E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.624733E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.943231E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.107593E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.657590E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 246116.37 0.396712E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1265237.64 0.296581E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21781.32 0.346585E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.383126E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.798800E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.284806E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.558644E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1533135.33 0.713415E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.284806E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1265237.64 0.107593E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 11837.83 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 11837.83 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 11837.83 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 11837.83 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 11837.83 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 11837.83 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 11837.83 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 11837.83 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 11837.83 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 11837.83 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 11837.83 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 11837.83 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   11837.83   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   11837.83   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 10631.20 02-JAN-08:09 17206.63 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 10631.20 01-FEB-08:09 17206.63 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 10631.20 01-MAR-08:09 17206.63 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 10631.20 03-APR-07:10 17206.63 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 10631.20 01-MAY-07:10 17206.63 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 10631.20 01-JUN-07:10 17206.63 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 10631.20 03-JUL-07:10 17206.63 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 10631.20 01-AUG-07:10 17206.63 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 10631.20 01-SEP-07:10 17206.63 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 10631.20 02-OCT-07:10 17206.63 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 10631.20 01-NOV-07:10 17206.63 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 10631.20 01-DEC-08:09 17206.63 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   10631.20   17206.63   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   10631.20   17206.63   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 10631.20 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 10631.20 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 10631.20 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 10631.20 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 10631.20 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 10631.20 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 10631.20 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 10631.20 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 10631.20 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 10631.20 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 10631.20 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 10631.20 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   10631.20   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   10631.20   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 10631.20 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 10631.20 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 10631.20 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 10631.20 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 10631.20 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 10631.20 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 10631.20 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 10631.20 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 10631.20 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 10631.20 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 10631.20 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 10631.20 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   10631.20   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   10631.20   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1334.85 02-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 878.07 28-JAN-23:55
February 2010.79 01-FEB-10:09 1334.85 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 528.16 25-FEB-00:53
March 2010.79 01-MAR-10:09 1334.85 01-MAR-08:09 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 383.09 25-MAR-04:00
April 2010.79 03-APR-09:09 883.98 04-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 592.05 01-APR-19:00
May 2010.79 01-MAY-09:09 674.82 08-MAY-14:30 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 278.66 26-MAY-02:00
June 2010.79 01-JUN-09:09 635.12 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 11.46 30-JUN-15:00 287.88 25-JUN-06:00
July 2010.79 03-JUL-09:09 698.73 26-JUL-14:30 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 28.41 21-JUL-16:00 181.09 04-JUL-17:10
August 2010.79 01-AUG-09:09 715.66 18-AUG-15:00 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 4.31 11-AUG-16:00 219.26 30-AUG-01:00
September 2010.79 01-SEP-09:09 1280.12 28-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 184.99 04-SEP-14:00
October 2010.79 02-OCT-09:09 1334.85 03-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 355.26 21-OCT-04:01
November 2010.79 01-NOV-09:09 1334.85 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 290.62 10-NOV-02:00
December 2010.79 01-DEC-10:09 1334.85 01-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 308.36 28-DEC-02:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   635.12   2160.55   0.00 0.00 0.00 0.00 0.00   181.09  
Maximum of Months 2010.79   1334.85   2160.55   0.00 0.00 0.00 0.00 28.41   878.07  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 860.23 02-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 581.00 28-JAN-23:55
February 1295.83 01-FEB-10:09 860.23 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 349.97 25-FEB-00:53
March 1295.83 01-MAR-10:09 860.23 01-MAR-08:09 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 251.33 25-MAR-04:00
April 1295.83 03-APR-09:09 446.78 04-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 388.52 01-APR-19:00
May 1295.83 01-MAY-09:09 427.98 26-MAY-15:00 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 185.84 26-MAY-02:00
June 1295.83 01-JUN-09:09 409.30 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 7.64 30-JUN-15:00 187.44 25-JUN-06:00
July 1295.83 03-JUL-09:09 434.31 26-JUL-14:30 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 20.55 29-JUL-20:00 115.56 04-JUL-17:10
August 1295.83 01-AUG-09:09 462.72 18-AUG-15:00 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 2.87 11-AUG-16:00 142.63 30-AUG-01:00
September 1295.83 01-SEP-09:09 760.99 28-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 123.42 04-SEP-14:00
October 1295.83 02-OCT-09:09 860.23 03-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 233.28 21-OCT-04:01
November 1295.83 01-NOV-09:09 860.23 01-NOV-07:10 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 191.26 10-NOV-02:00
December 1295.83 01-DEC-10:09 860.23 01-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 202.49 28-DEC-02:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   409.30   1392.34   0.00 0.00 0.00 0.00 0.00   115.56  
Maximum of Months 1295.83   860.23   1392.34   0.00 0.00 0.00 0.00 20.55   581.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1334.88 02-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 864.86 28-JAN-23:55
February 2010.83 01-FEB-10:09 1334.88 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 524.06 25-FEB-00:53
March 2010.83 01-MAR-10:09 1334.88 01-MAR-08:09 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 410.38 12-MAR-14:55
April 2010.83 03-APR-09:09 882.32 04-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 618.12 01-APR-19:00
May 2010.83 01-MAY-09:09 635.14 01-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 279.39 26-MAY-02:00
June 2010.83 01-JUN-09:09 635.14 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 11.46 30-JUN-15:00 275.47 25-JUN-06:00
July 2010.83 03-JUL-09:09 684.62 25-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 28.41 21-JUL-16:00 178.90 04-JUL-17:10
August 2010.83 01-AUG-09:09 688.71 18-AUG-15:00 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 4.31 11-AUG-16:00 216.68 30-AUG-01:00
September 2010.83 01-SEP-09:09 1237.68 28-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 176.73 04-SEP-14:00
October 2010.83 02-OCT-09:09 1334.88 03-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 345.65 22-OCT-17:53
November 2010.83 01-NOV-09:09 1334.88 01-NOV-07:10 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 287.38 10-NOV-02:00
December 2010.83 01-DEC-10:09 1334.88 01-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 301.71 28-DEC-02:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   635.14   2160.58   0.00 0.00 0.00 0.00 0.00   176.73  
Maximum of Months 2010.83   1334.88   2160.58   0.00 0.00 0.00 0.00 28.41   864.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 860.23 02-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 599.88 28-JAN-23:55
February 1295.83 01-FEB-10:09 860.23 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 364.07 25-FEB-00:53
March 1295.83 01-MAR-10:09 860.23 01-MAR-08:09 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 269.33 25-MAR-04:00
April 1295.83 03-APR-09:09 644.33 04-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 480.61 01-APR-19:00
May 1295.83 01-MAY-09:09 434.10 23-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 196.30 26-MAY-02:00
June 1295.83 01-JUN-09:09 446.80 27-JUN-07:30 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 7.64 30-JUN-15:00 208.82 25-JUN-06:00
July 1295.83 03-JUL-09:09 460.29 25-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 18.94 21-JUL-16:00 133.45 04-JUL-17:10
August 1295.83 01-AUG-09:09 460.45 07-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 2.87 11-AUG-16:00 160.57 30-AUG-01:00
September 1295.83 01-SEP-09:09 827.29 29-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 128.80 04-SEP-14:00
October 1295.83 02-OCT-09:09 860.23 03-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 250.13 21-OCT-04:01
November 1295.83 01-NOV-09:09 860.23 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 203.83 10-NOV-02:00
December 1295.83 01-DEC-10:09 860.23 01-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 216.31 28-DEC-02:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   434.10   1392.33   0.00 0.00 0.00 0.00 0.00   128.80  
Maximum of Months 1295.83   860.23   1392.33   0.00 0.00 0.00 0.00 18.94   599.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1334.85 02-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1929.77 28-JAN-23:55
February 2010.79 01-FEB-10:09 1334.85 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 1168.16 25-FEB-00:53
March 2010.79 01-MAR-10:09 1334.85 01-MAR-08:09 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 858.29 25-MAR-04:10
April 2010.79 03-APR-09:09 893.95 04-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1278.93 01-APR-18:53
May 2010.79 01-MAY-09:09 670.68 08-MAY-14:30 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 623.74 26-MAY-02:00
June 2010.79 01-JUN-09:09 635.12 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 26.21 30-JUN-15:00 616.13 25-JUN-06:00
July 2010.79 03-JUL-09:09 694.97 26-JUL-14:30 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 65.46 29-JUL-20:00 452.00 04-JUL-16:55
August 2010.79 01-AUG-09:09 712.86 18-AUG-15:00 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 9.42 11-AUG-16:00 481.65 30-AUG-01:00
September 2010.79 01-SEP-09:09 1281.64 28-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 384.89 04-SEP-14:00
October 2010.79 02-OCT-09:09 1334.85 03-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 781.97 21-OCT-04:04
November 2010.79 01-NOV-09:09 1334.85 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 633.42 10-NOV-05:10
December 2010.79 01-DEC-10:09 1334.85 01-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 665.76 28-DEC-02:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   635.12   2160.55   0.00 0.00 0.00 0.00 0.00   384.89  
Maximum of Months 2010.79   1334.85   2160.55   0.00 0.00 0.00 0.00 65.46   1929.77  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 860.23 02-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1285.35 28-JAN-23:55
February 1239.33 01-FEB-08:09 860.23 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 779.71 25-FEB-00:53
March 1239.33 01-MAR-08:09 860.23 01-MAR-08:09 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 572.20 25-MAR-04:22
April 1239.33 03-APR-07:10 445.29 04-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 861.68 01-APR-18:53
May 1239.33 01-MAY-07:10 409.30 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 420.77 26-MAY-02:00
June 1239.33 01-JUN-07:10 409.30 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 17.47 30-JUN-15:00 409.28 25-JUN-06:00
July 1239.33 03-JUL-07:10 431.40 26-JUL-14:30 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 48.96 29-JUL-20:00 306.85 04-JUL-16:55
August 1239.33 01-AUG-07:10 460.73 18-AUG-15:00 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 6.28 11-AUG-16:00 320.52 30-AUG-01:00
September 1239.33 01-SEP-07:10 764.05 28-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 264.18 04-SEP-14:00
October 1239.33 02-OCT-07:10 860.23 03-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 524.25 21-OCT-04:03
November 1239.33 01-NOV-07:10 860.23 01-NOV-07:10 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 423.55 10-NOV-05:04
December 1239.33 01-DEC-08:09 860.23 01-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 442.13 28-DEC-02:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   409.30   1392.34   0.00 0.00 0.00 0.00 0.00   264.18  
Maximum of Months 1239.33   860.23   1392.34   0.00 0.00 0.00 0.00 48.96   1285.35  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1334.88 02-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1935.57 28-JAN-23:55
February 2010.83 01-FEB-10:09 1334.88 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 1182.57 25-FEB-00:53
March 2010.83 01-MAR-10:09 1334.88 01-MAR-08:09 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 975.55 12-MAR-14:55
April 2010.83 03-APR-09:09 892.30 04-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1464.18 01-APR-18:53
May 2010.83 01-MAY-09:09 635.14 01-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 637.68 26-MAY-02:00
June 2010.83 01-JUN-09:09 635.14 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 26.21 30-JUN-15:00 607.86 25-JUN-06:00
July 2010.83 03-JUL-09:09 681.45 25-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 65.28 21-JUL-16:00 467.83 04-JUL-16:55
August 2010.83 01-AUG-09:09 685.62 18-AUG-15:00 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 9.41 11-AUG-16:00 485.51 30-AUG-01:00
September 2010.83 01-SEP-09:09 1240.61 28-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 400.89 04-SEP-14:00
October 2010.83 02-OCT-09:09 1334.88 03-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 797.85 22-OCT-17:53
November 2010.83 01-NOV-09:09 1334.88 01-NOV-07:10 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 642.62 10-NOV-02:00
December 2010.83 01-DEC-10:09 1334.88 01-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 668.75 28-DEC-02:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   635.14   2160.58   0.00 0.00 0.00 0.00 0.00   400.89  
Maximum of Months 2010.83   1334.88   2160.58   0.00 0.00 0.00 0.00 65.28   1935.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 860.23 02-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1290.55 28-JAN-23:55
February 1295.83 01-FEB-10:09 860.23 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 787.99 25-FEB-00:53
March 1295.83 01-MAR-10:09 860.23 01-MAR-08:09 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 573.58 25-MAR-04:03
April 1295.83 03-APR-09:09 644.77 04-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1075.29 01-APR-18:53
May 1295.83 01-MAY-09:09 431.22 23-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 425.25 26-MAY-02:00
June 1295.83 01-JUN-09:09 444.29 27-JUN-07:30 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 17.47 30-JUN-15:00 413.44 25-JUN-06:00
July 1295.83 03-JUL-09:09 458.21 25-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 43.52 21-JUL-16:00 317.75 04-JUL-16:55
August 1295.83 01-AUG-09:09 458.39 07-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 6.28 11-AUG-16:00 326.85 30-AUG-01:00
September 1295.83 01-SEP-09:09 827.88 29-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 263.48 04-SEP-14:00
October 1295.83 02-OCT-09:09 860.23 03-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 524.60 21-OCT-04:03
November 1295.83 01-NOV-09:09 860.23 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 428.06 10-NOV-02:00
December 1295.83 01-DEC-10:09 860.23 01-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 450.93 28-DEC-02:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   431.22   1392.33   0.00 0.00 0.00 0.00 0.00   263.48  
Maximum of Months 1295.83   860.23   1392.33   0.00 0.00 0.00 0.00 43.52   1290.55  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1334.85 02-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 2421.58 28-JAN-24:00
February 2010.79 01-FEB-10:09 1334.85 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 1422.80 25-FEB-00:53
March 2010.79 01-MAR-10:09 1334.85 01-MAR-08:09 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1069.29 25-MAR-04:10
April 2010.79 03-APR-09:09 893.63 04-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1492.44 01-APR-18:53
May 2010.79 01-MAY-09:09 670.42 08-MAY-14:30 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 722.53 26-MAY-02:00
June 2010.79 01-JUN-09:09 635.12 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 31.69 30-JUN-15:00 688.30 24-JUN-21:00
July 2010.79 03-JUL-09:09 694.80 26-JUL-14:30 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 80.64 29-JUL-20:00 538.47 04-JUL-16:55
August 2010.79 01-AUG-09:09 712.66 18-AUG-15:00 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 10.84 11-AUG-16:00 556.09 30-AUG-01:00
September 2010.79 01-SEP-09:09 1281.68 28-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 431.95 30-SEP-05:00
October 2010.79 02-OCT-09:09 1334.85 03-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 974.27 21-OCT-04:45
November 2010.79 01-NOV-09:09 1334.85 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 782.94 10-NOV-05:00
December 2010.79 01-DEC-10:09 1334.85 01-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 825.36 28-DEC-03:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   635.12   2160.55   0.00 0.00 0.00 0.00 0.00   431.95  
Maximum of Months 2010.79   1334.85   2160.55   0.00 0.00 0.00 0.00 80.64   2421.58  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 860.23 02-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1614.29 28-JAN-24:00
February 1295.83 01-FEB-10:09 860.23 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 955.12 24-FEB-05:18
March 1295.83 01-MAR-10:09 860.23 01-MAR-08:09 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 712.86 25-MAR-04:45
April 1295.83 03-APR-09:09 445.18 04-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1006.14 01-APR-18:53
May 1295.83 01-MAY-09:09 409.30 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 493.60 26-MAY-02:00
June 1295.83 01-JUN-09:09 409.30 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 21.13 30-JUN-15:00 459.16 24-JUN-21:00
July 1295.83 03-JUL-09:09 431.26 26-JUL-14:30 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 52.92 21-JUL-16:00 367.06 04-JUL-16:55
August 1295.83 01-AUG-09:09 460.61 18-AUG-15:00 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 7.22 11-AUG-16:00 373.71 30-AUG-01:00
September 1295.83 01-SEP-09:09 764.29 28-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 287.94 30-SEP-05:00
October 1295.83 02-OCT-09:09 860.23 03-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 652.70 21-OCT-04:04
November 1295.83 01-NOV-09:09 860.23 01-NOV-07:10 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 525.80 10-NOV-05:07
December 1295.83 01-DEC-10:09 860.23 01-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 554.03 28-DEC-02:57
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   409.30   1392.34   0.00 0.00 0.00 0.00 0.00   287.94  
Maximum of Months 1295.83   860.23   1392.34   0.00 0.00 0.00 0.00 52.92   1614.29  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1334.88 02-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 2421.58 28-JAN-24:00
February 2010.83 01-FEB-10:09 1334.88 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 1432.68 24-FEB-05:38
March 2010.83 01-MAR-10:09 1334.88 01-MAR-08:09 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1094.39 12-MAR-14:55
April 2010.83 03-APR-09:09 891.99 04-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1717.94 01-APR-18:53
May 2010.83 01-MAY-09:09 635.14 01-MAY-07:10 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 748.17 26-MAY-02:00
June 2010.83 01-JUN-09:09 635.14 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 31.69 30-JUN-15:00 696.49 18-JUN-14:20
July 2010.83 03-JUL-09:09 681.20 25-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 79.38 21-JUL-16:00 559.48 04-JUL-16:55
August 2010.83 01-AUG-09:09 685.36 18-AUG-15:00 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 10.83 11-AUG-16:10 567.12 30-AUG-01:00
September 2010.83 01-SEP-09:09 1240.73 28-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 446.12 30-SEP-21:00
October 2010.83 02-OCT-09:09 1334.88 03-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 982.16 21-OCT-04:04
November 2010.83 01-NOV-09:09 1334.88 01-NOV-07:10 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 788.71 10-NOV-05:09
December 2010.83 01-DEC-10:09 1334.88 01-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 830.79 28-DEC-02:57
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   635.14   2160.58   0.00 0.00 0.00 0.00 0.00   446.12  
Maximum of Months 2010.83   1334.88   2160.58   0.00 0.00 0.00 0.00 79.38   2421.58  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 860.23 02-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1614.40 28-JAN-23:55
February 1295.83 01-FEB-10:09 860.23 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 955.12 24-FEB-05:18
March 1295.83 01-MAR-10:09 860.23 01-MAR-08:09 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 715.43 25-MAR-04:04
April 1295.83 03-APR-09:09 644.58 04-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1270.85 01-APR-18:53
May 1295.83 01-MAY-09:09 431.06 23-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 498.44 26-MAY-02:00
June 1295.83 01-JUN-09:09 444.14 27-JUN-07:30 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 21.13 30-JUN-15:00 473.43 24-JUN-21:00
July 1295.83 03-JUL-09:09 458.08 25-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 52.92 21-JUL-16:00 380.85 04-JUL-16:55
August 1295.83 01-AUG-09:09 458.27 07-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 7.22 11-AUG-16:00 382.39 30-AUG-01:00
September 1295.83 01-SEP-09:09 827.92 29-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 287.96 30-SEP-05:00
October 1295.83 02-OCT-09:09 860.23 03-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 653.38 21-OCT-04:04
November 1295.83 01-NOV-09:09 860.23 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 525.82 10-NOV-05:07
December 1295.83 01-DEC-10:09 860.23 01-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 553.27 28-DEC-02:57
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   431.06   1392.33   0.00 0.00 0.00 0.00 0.00   287.96  
Maximum of Months 1295.83   860.23   1392.33   0.00 0.00 0.00 0.00 52.92   1614.40  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 284.97 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 284.97 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 284.97 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 284.97 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 284.97 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 284.97 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 284.97 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 284.97 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 284.97 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 284.97 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 284.97 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 284.97 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   284.97   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   284.97   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 284.97 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 284.97 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 284.97 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 284.97 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 284.97 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 284.97 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 284.97 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 284.97 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 284.97 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 284.97 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 284.97 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 284.97 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   284.97   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   284.97   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 284.97 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 284.97 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 284.97 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 284.97 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 284.97 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 284.97 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 284.97 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 284.97 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 284.97 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 284.97 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 284.97 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 284.97 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   284.97   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   284.97   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 3337.76 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 3337.76 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 3337.76 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 3337.76 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 3337.76 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 3337.76 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 3337.76 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 3337.76 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 3337.76 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 3337.76 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 3337.76 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 3337.76 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   3337.76   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   3337.76   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1868.73 28-JAN-23:55
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 1116.89 25-FEB-00:53
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 805.19 25-MAR-04:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1256.34 01-APR-18:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 576.55 26-MAY-02:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.22 30-JUN-15:00 573.45 25-JUN-06:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50.25 29-JUL-17:02 367.23 04-JUL-16:55
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.17 11-AUG-16:00 452.05 30-AUG-01:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 360.21 04-SEP-14:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 747.73 21-OCT-04:52
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 615.90 10-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 650.25 28-DEC-02:53
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   360.21  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50.25   1868.73  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 3227.30 28-JAN-24:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 1940.81 25-FEB-00:53
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1396.31 25-MAR-04:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2161.68 01-APR-18:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1026.27 26-MAY-02:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34.11 30-JUN-15:00 1001.77 25-JUN-06:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 95.89 29-JUL-17:02 664.51 04-JUL-16:55
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.80 11-AUG-16:00 797.47 30-AUG-01:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 609.16 04-SEP-14:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1279.56 21-OCT-04:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1061.99 10-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1106.29 28-DEC-02:53
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   609.16  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 95.89   3227.30  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 3466.14 28-JAN-24:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 2124.92 25-FEB-00:53
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1512.08 14-MAR-21:03
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2393.69 01-APR-18:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1094.06 26-MAY-02:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32.50 30-JUN-15:00 1036.72 24-JUN-21:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 90.34 21-JUL-16:00 810.56 04-JUL-16:55
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.94 11-AUG-18:00 834.61 30-AUG-01:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 629.43 04-SEP-14:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1340.04 21-OCT-04:50
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1130.58 10-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1200.77 28-DEC-03:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   629.43  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 90.34   3466.14  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 87457.37 25-JAN-06:01 16157.03 11837.50 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
February 89650.28 13-FEB-05:01 0.00 9206.95 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
March 92937.75 20-MAR-04:01 0.00 11837.50 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
April 95518.54 10-APR-03:01 0.00 5919.49 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
May 96218.64 30-MAY-03:02 0.00 2630.88 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
June 97145.13 19-JUN-03:02 0.00 3288.60 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
July 100116.50 31-JUL-03:02 0.00 3946.33 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
August 98111.28 28-AUG-03:02 0.00 3288.60 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
September 94760.50 18-SEP-03:03 0.00 1973.16 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
October 97468.45 10-OCT-03:01 0.00 4604.05 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
November 91966.10 13-NOV-05:01 0.00 9206.95 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
December 93594.19 26-DEC-04:01 0.00 5261.77 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 87457.37   0.00 1973.16 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 100116.50   16157.03 11837.50 121117.90 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 22260.88 25-JAN-13:20 15316.26 10631.20 17206.63 0.00 0.00 0.00 0.00 0.00 0.00
February 72001.02 10-FEB-06:01 11285.67 8268.49 53531.73 0.00 0.00 0.00 0.00 0.00 0.00
March 76669.72 30-MAR-05:01 12897.91 9449.70 61179.12 0.00 0.00 0.00 0.00 0.00 0.00
April 78815.08 24-APR-03:02 0.00 2362.72 23750.58 0.00 0.00 0.00 0.00 0.00 0.00
May 79268.71 01-MAY-03:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
June 81847.79 26-JUN-03:02 0.00 2362.72 23750.58 0.00 0.00 0.00 0.00 0.00 0.00
July 82540.04 05-JUL-03:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
August 78698.28 08-AUG-03:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
September 82935.70 05-SEP-03:02 0.00 2362.72 23750.58 0.00 0.00 0.00 0.00 0.00 0.00
October 81061.72 10-OCT-04:01 0.00 11812.12 59376.45 0.00 0.00 0.00 0.00 0.00 0.00
November 70697.72 02-NOV-05:01 12897.91 9449.70 61179.12 0.00 0.00 0.00 0.00 0.00 0.00
December 30407.55 26-DEC-08:15 30632.53 21262.41 34413.26 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 22260.88   0.00 2362.72 17206.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 82935.70   30632.53 21262.41 61179.12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 15931.34 27-JAN-17:00 15316.26 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
February 22208.07 16-FEB-13:40 15316.26 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
March 22985.50 29-MAR-10:25 30632.53 21262.41 34413.13 0.00 0.00 0.00 0.00 0.00 0.00
April 69354.35 28-APR-05:03 6448.95 4724.85 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
May 72283.06 15-MAY-05:04 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
June 72002.37 24-JUN-05:04 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
July 75453.35 05-JUL-03:02 0.00 2953.40 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
August 73436.68 07-AUG-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
September 73188.13 05-SEP-05:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
October 48465.64 06-OCT-05:03 6448.95 4724.85 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
November 16577.86 03-NOV-16:00 15316.26 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
December 15564.76 22-DEC-17:00 15316.26 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 15564.76   0.00 2953.40 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 75453.35   30632.53 21262.41 38236.81 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 13178.34 20-JAN-17:00 15316.26 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
February 15227.75 09-FEB-17:00 15316.26 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
March 17100.33 22-MAR-16:00 15316.26 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
April 29607.97 21-APR-16:00 15316.26 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
May 63346.86 11-MAY-05:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
June 72265.35 24-JUN-05:04 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
July 69305.06 05-JUL-05:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
August 70604.14 07-AUG-05:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
September 27322.05 01-SEP-16:00 15316.26 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
October 17548.25 04-OCT-16:00 15316.26 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
November 13465.13 02-NOV-16:00 15316.26 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
December 12472.04 21-DEC-17:00 15316.26 10631.20 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 12472.04   8061.19 5906.06 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 72265.35   15316.26 10631.20 38236.81 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1609.67 20-JAN-14:30 2010.79 1318.34 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
February 2404.18 09-FEB-06:03 809.73 593.25 3840.98 0.00 0.00 0.00 0.00 0.00 20.87
March 2761.93 22-MAR-14:00 2010.79 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
April 5072.51 28-APR-14:00 2010.79 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
May 12173.82 31-MAY-04:33 0.00 211.70 2236.68 0.00 0.00 0.00 0.00 0.00 0.00
June 13348.92 29-JUN-05:03 1214.60 423.40 5761.47 0.00 0.00 0.00 0.00 0.00 11.76
July 13136.33 07-JUL-04:23 0.00 282.27 2982.24 0.00 0.00 0.00 0.00 0.00 43.08
August 11387.43 07-AUG-05:02 1012.16 499.15 4801.23 0.00 0.00 0.00 0.00 0.00 18.80
September 4910.82 01-SEP-13:40 2010.79 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 9.51
October 3030.24 04-OCT-14:30 1923.11 679.98 2160.55 0.00 0.00 0.00 0.00 0.00 34.27
November 2154.57 02-NOV-05:01 1619.46 1186.50 7681.96 0.00 0.00 0.00 0.00 0.00 19.43
December 1773.04 26-DEC-12:00 1923.11 1258.79 2160.55 0.00 0.00 0.00 0.00 0.00 65.92
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1609.67   0.00 211.70 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13348.92   2010.79 1318.34 7681.96 0.00 0.00 0.00 0.00 0.00 65.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1493.64 27-JAN-06:03 782.73 573.47 3712.91 0.00 0.00 0.00 0.00 0.00 2.92
February 2117.66 09-FEB-06:03 521.82 382.31 2475.27 0.00 0.00 0.00 0.00 0.00 13.54
March 6488.17 27-MAR-09:40 2591.66 818.60 2784.68 0.00 0.00 0.00 0.00 0.00 36.67
April 9229.39 22-APR-09:20 409.21 136.43 773.52 0.00 0.00 0.00 0.00 0.00 8.76
May 20173.07 14-MAY-08:12 391.37 136.45 2784.68 0.00 0.00 0.00 0.00 0.00 59.41
June 15328.52 07-JUN-05:02 782.73 272.86 3712.91 0.00 0.00 0.00 0.00 0.00 16.44
July 20690.78 23-JUL-09:51 456.59 159.19 3248.80 0.00 0.00 0.00 0.00 0.00 17.96
August 12701.42 10-AUG-08:50 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 3.73
September 18774.27 10-SEP-08:53 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 58.98
October 5911.43 03-OCT-09:40 2591.66 818.60 2784.68 0.00 0.00 0.00 0.00 0.00 20.42
November 2072.16 03-NOV-05:02 1043.64 764.63 4950.55 0.00 0.00 0.00 0.00 0.00 20.97
December 1537.23 26-DEC-06:04 652.28 477.89 3094.09 0.00 0.00 0.00 0.00 0.00 16.55
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1493.64   260.91 90.96 773.52 0.00 0.00 0.00 0.00 0.00 2.92
Maximum of Months 20690.78   2591.66 818.60 4950.55 0.00 0.00 0.00 0.00 0.00 59.41



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3049.56 25-JAN-13:30 1923.15 635.14 2160.58 0.00 0.00 0.00 0.00 0.00 22.90
February 8859.03 15-FEB-13:30 1923.15 635.14 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
March 14498.98 31-MAR-13:30 2010.83 635.14 2160.58 0.00 0.00 0.00 0.00 0.00 45.81
April 22484.71 09-APR-14:53 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 0.00
May 30511.42 14-MAY-12:12 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 0.00 62.23
June 23927.91 11-JUN-15:02 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 107.45
July 32291.04 23-JUL-13:11 809.75 282.31 5761.56 0.00 0.00 0.00 0.00 0.00 14.16
August 29210.86 27-AUG-13:32 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 32.92
September 18838.75 10-SEP-11:32 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 60.77
October 15112.86 03-OCT-13:30 2010.83 635.14 2160.58 0.00 0.00 0.00 0.00 0.00 32.69
November 6188.00 08-NOV-13:30 1923.15 635.14 2160.58 0.00 0.00 0.00 0.00 0.00 33.60
December 2382.68 27-DEC-12:40 1058.33 1059.32 1920.52 0.00 0.00 0.00 0.00 0.00 34.77
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2382.68   404.87 141.16 1920.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 32291.04   2010.83 1059.32 5761.56 0.00 0.00 0.00 0.00 0.00 107.45



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1950.15 23-JAN-14:20 1295.83 623.63 1392.33 0.00 0.00 0.00 0.00 0.00 18.65
February 3170.01 09-FEB-06:03 521.82 382.31 2475.26 0.00 0.00 0.00 0.00 0.00 14.79
March 7572.19 27-MAR-16:00 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 41.88
April 21765.56 22-APR-17:04 456.59 159.19 3248.78 0.00 0.00 0.00 0.00 0.00 113.01
May 23001.57 14-MAY-19:32 0.00 113.70 1801.74 0.00 0.00 0.00 0.00 0.00 84.87
June 21986.36 11-JUN-17:02 0.00 113.70 1801.74 0.00 0.00 0.00 0.00 0.00 73.93
July 23709.30 23-JUL-15:11 456.59 159.19 3248.78 0.00 0.00 0.00 0.00 0.00 5.75
August 23466.55 27-AUG-16:52 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 0.00 66.95
September 12193.68 02-SEP-17:08 260.91 90.96 1856.44 0.00 0.00 0.00 0.00 0.00 29.51
October 7319.28 04-OCT-05:03 521.82 382.31 2475.26 0.00 0.00 0.00 0.00 0.00 21.70
November 3046.57 02-NOV-05:01 1043.64 764.63 4950.52 0.00 0.00 0.00 0.00 0.00 13.71
December 2531.94 26-DEC-05:01 0.00 669.05 3363.25 0.00 0.00 0.00 0.00 0.00 94.29
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1950.15   0.00 90.96 1392.33 0.00 0.00 0.00 0.00 0.00 5.75
Maximum of Months 23709.30   1295.83 764.63 4950.52 0.00 0.00 0.00 0.00 0.00 113.01



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1401.99 20-JAN-21:03 809.73 1186.50 3840.98 0.00 0.00 0.00 0.00 0.00 69.16
February 1929.16 08-FEB-21:05 809.73 1186.50 3840.98 0.00 0.00 0.00 0.00 0.00 29.62
March 2000.06 17-MAR-20:03 809.73 1186.50 3840.98 0.00 0.00 0.00 0.00 0.00 35.93
April 3261.54 28-APR-15:20 1923.11 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 44.12
May 10797.61 31-MAY-05:03 809.73 282.27 3840.98 0.00 0.00 0.00 0.00 0.00 4.57
June 12399.01 19-JUN-05:03 1214.60 423.40 5761.47 0.00 0.00 0.00 0.00 0.00 26.64
July 12698.53 11-JUL-04:52 0.00 352.84 3727.80 0.00 0.00 0.00 0.00 0.00 123.60
August 9319.60 01-AUG-05:02 1012.16 375.00 4801.23 0.00 0.00 0.00 0.00 0.00 27.11
September 3310.68 01-SEP-13:50 2010.79 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 21.29
October 2116.55 05-OCT-09:20 2010.79 668.27 2160.55 0.00 0.00 0.00 0.00 0.00 65.05
November 1416.37 02-NOV-20:03 809.73 1186.50 3840.98 0.00 0.00 0.00 0.00 0.00 0.00
December 1393.01 23-DEC-16:03 809.73 889.91 3360.86 0.00 0.00 0.00 0.00 0.00 93.22
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1393.01   0.00 282.27 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12698.53   2010.79 1186.50 5761.47 0.00 0.00 0.00 0.00 0.00 123.60



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1613.17 05-JAN-06:04 1043.64 764.63 4950.55 0.00 0.00 0.00 0.00 0.00 68.65
February 1994.62 09-FEB-11:05 2478.65 818.60 2784.68 0.00 0.00 0.00 0.00 0.00 47.35
March 4665.76 29-MAR-10:25 2478.65 818.60 2784.68 0.00 0.00 0.00 0.00 0.00 0.00
April 13184.31 23-APR-10:13 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 286.49
May 20460.83 21-MAY-09:02 391.37 136.45 2784.68 0.00 0.00 0.00 0.00 0.00 252.29
June 17352.62 18-JUN-10:13 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 153.34
July 22554.45 23-JUL-09:51 456.59 159.19 3248.80 0.00 0.00 0.00 0.00 0.00 45.10
August 13357.91 10-AUG-09:00 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 10.41
September 16169.18 10-SEP-09:23 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 131.16
October 3947.64 03-OCT-10:10 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 44.98
November 1631.28 14-NOV-06:04 913.19 669.05 4331.73 0.00 0.00 0.00 0.00 0.00 42.79
December 1612.78 30-DEC-06:04 913.19 669.05 4331.73 0.00 0.00 0.00 0.00 0.00 53.30
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1612.78   260.91 90.96 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22554.45   2478.65 818.60 4950.55 0.00 0.00 0.00 0.00 0.00 286.49



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2799.85 25-JAN-13:40 1923.15 635.14 2160.58 0.00 0.00 0.00 0.00 0.00 34.92
February 7705.00 15-FEB-14:30 2010.83 635.14 2160.58 0.00 0.00 0.00 0.00 0.00 27.69
March 20123.59 29-MAR-13:28 10054.17 3175.69 10802.92 0.00 0.00 0.00 0.00 0.00 111.91
April 30582.12 23-APR-13:32 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 370.02
May 32209.60 21-MAY-13:02 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 0.00 342.68
June 30860.76 18-JUN-12:52 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 209.18
July 34474.66 23-JUL-13:51 809.75 282.31 5761.56 0.00 0.00 0.00 0.00 0.00 37.31
August 30650.18 27-AUG-13:32 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 79.88
September 30432.82 10-SEP-11:22 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 161.73
October 14732.50 03-OCT-13:30 2010.83 635.14 2160.58 0.00 0.00 0.00 0.00 0.00 77.29
November 4064.28 08-NOV-13:30 1923.15 635.14 2160.58 0.00 0.00 0.00 0.00 0.00 79.03
December 2416.02 30-DEC-06:04 1417.06 1038.21 6721.82 0.00 0.00 0.00 0.00 0.00 79.94
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2416.02   506.09 176.44 2160.58 0.00 0.00 0.00 0.00 0.00 27.69
Maximum of Months 34474.66   10054.17 3175.69 10802.92 0.00 0.00 0.00 0.00 0.00 370.02



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1683.93 05-JAN-06:04 1043.64 764.63 4950.52 0.00 0.00 0.00 0.00 0.00 69.01
February 1976.59 08-FEB-21:05 521.82 764.63 2475.26 0.00 0.00 0.00 0.00 0.00 19.70
March 4067.18 31-MAR-16:00 3717.98 1227.89 4177.00 0.00 0.00 0.00 0.00 0.00 104.89
April 14954.76 22-APR-17:04 456.59 159.19 3248.78 0.00 0.00 0.00 0.00 0.00 262.70
May 20669.00 21-MAY-17:42 0.00 113.70 1801.74 0.00 0.00 0.00 0.00 0.00 105.47
June 21378.89 11-JUN-17:32 0.00 136.45 2162.09 0.00 0.00 0.00 0.00 0.00 194.34
July 19713.64 23-JUL-15:52 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 0.00 6.05
August 20157.63 27-AUG-17:32 0.00 136.45 2162.09 0.00 0.00 0.00 0.00 0.00 119.35
September 8281.08 02-SEP-17:10 260.91 90.96 1856.44 0.00 0.00 0.00 0.00 0.00 69.62
October 2365.19 03-OCT-15:20 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 34.82
November 1660.48 14-NOV-06:04 913.19 669.05 4331.70 0.00 0.00 0.00 0.00 0.00 42.83
December 1682.18 27-DEC-06:04 913.19 669.05 4331.70 0.00 0.00 0.00 0.00 0.00 54.88
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1660.48   0.00 90.96 1392.33 0.00 0.00 0.00 0.00 0.00 6.05
Maximum of Months 21378.89   3717.98 1227.89 4950.52 0.00 0.00 0.00 0.00 0.00 262.70



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1764.90 19-JAN-21:03 809.73 1186.50 3840.98 0.00 0.00 0.00 0.00 0.00 149.86
February 1813.23 08-FEB-21:03 809.73 1186.50 3840.98 0.00 0.00 0.00 0.00 0.00 37.30
March 2043.58 22-MAR-16:00 1923.11 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
April 2815.31 28-APR-16:00 1923.11 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 93.96
May 12770.65 31-MAY-05:03 809.73 282.27 3840.98 0.00 0.00 0.00 0.00 0.00 5.70
June 14967.49 08-JUN-05:02 1214.60 423.40 5761.47 0.00 0.00 0.00 0.00 0.00 46.91
July 15226.97 11-JUL-05:02 1214.60 423.40 5761.47 0.00 0.00 0.00 0.00 0.00 35.03
August 8822.75 05-AUG-05:03 809.73 282.27 3840.98 0.00 0.00 0.00 0.00 0.00 33.73
September 2816.13 01-SEP-16:00 1923.11 635.12 2160.55 0.00 0.00 0.00 0.00 0.00 27.01
October 2132.69 04-OCT-16:00 1923.11 894.62 2160.55 0.00 0.00 0.00 0.00 0.00 40.22
November 1774.60 02-NOV-20:03 809.73 1186.50 3840.98 0.00 0.00 0.00 0.00 0.00 0.00
December 1750.98 23-DEC-16:03 809.73 889.91 3360.86 0.00 0.00 0.00 0.00 0.00 115.44
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1750.98   809.73 282.27 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15226.97   1923.11 1186.50 5761.47 0.00 0.00 0.00 0.00 0.00 149.86



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1547.45 05-JAN-06:05 1043.64 764.63 4950.55 0.00 0.00 0.00 0.00 0.00 85.45
February 1631.14 08-FEB-06:04 913.19 669.05 4331.73 0.00 0.00 0.00 0.00 0.00 64.06
March 2277.33 22-MAR-10:40 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 27.60
April 7257.21 22-APR-09:30 409.21 136.43 773.52 0.00 0.00 0.00 0.00 0.00 24.04
May 21233.94 21-MAY-09:12 391.37 136.45 2784.68 0.00 0.00 0.00 0.00 0.00 330.12
June 16645.71 08-JUN-05:02 782.73 272.86 3712.91 0.00 0.00 0.00 0.00 0.00 30.98
July 20417.81 23-JUL-10:02 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 0.00 36.34
August 13894.21 27-AUG-10:43 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 59.82
September 5550.07 10-SEP-10:05 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 153.92
October 2197.95 03-OCT-10:30 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 52.37
November 1378.35 02-NOV-20:03 521.82 764.63 2475.27 0.00 0.00 0.00 0.00 0.00 0.00
December 1359.78 23-DEC-16:03 521.82 573.49 2165.87 0.00 0.00 0.00 0.00 0.00 76.84
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1359.78   260.91 90.96 773.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21233.94   1239.33 764.63 4950.55 0.00 0.00 0.00 0.00 0.00 330.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2153.73 21-JAN-16:03 809.75 889.93 3360.91 0.00 0.00 0.00 0.00 0.00 0.00
February 4152.21 15-FEB-14:00 1923.15 635.14 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
March 11288.76 31-MAR-14:20 1923.15 635.14 2160.58 0.00 0.00 0.00 0.00 0.00 122.95
April 21046.67 23-APR-16:03 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 855.78
May 32927.29 21-MAY-13:12 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 0.00 387.30
June 29508.85 11-JUN-16:02 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 289.53
July 32839.98 23-JUL-13:22 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 0.00 31.47
August 34946.67 27-AUG-14:01 708.53 247.02 5041.36 0.00 0.00 0.00 0.00 0.00 156.72
September 15172.35 08-SEP-14:30 1923.15 635.14 2160.58 0.00 0.00 0.00 0.00 0.00 46.00
October 11616.01 03-OCT-13:40 2010.83 635.14 2160.58 0.00 0.00 0.00 0.00 0.00 93.15
November 3113.03 08-NOV-14:00 1923.15 635.14 2160.58 0.00 0.00 0.00 0.00 0.00 109.73
December 2134.35 23-DEC-16:03 809.75 889.93 3360.91 0.00 0.00 0.00 0.00 0.00 115.33
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2134.35   404.87 141.16 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 34946.67   2010.83 889.93 5041.36 0.00 0.00 0.00 0.00 0.00 855.78



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1458.32 19-JAN-21:03 521.82 764.63 2475.26 0.00 0.00 0.00 0.00 0.00 99.90
February 1738.01 03-FEB-06:04 913.19 669.05 4331.70 0.00 0.00 0.00 0.00 0.00 48.63
March 2236.55 27-MAR-17:00 391.37 227.39 773.52 0.00 0.00 0.00 0.00 0.00 137.92
April 15120.71 22-APR-17:06 456.59 159.19 3248.78 0.00 0.00 0.00 0.00 0.00 327.92
May 21153.83 21-MAY-17:52 0.00 113.70 1801.74 0.00 0.00 0.00 0.00 0.00 122.17
June 22326.68 11-JUN-16:42 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 0.00 244.16
July 13158.56 29-JUL-18:23 0.00 90.96 1441.39 0.00 0.00 0.00 0.00 0.00 0.76
August 21215.39 27-AUG-17:21 0.00 181.93 2882.79 0.00 0.00 0.00 0.00 0.00 165.79
September 5867.61 08-SEP-16:00 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 31.15
October 2175.00 03-OCT-15:20 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 0.00 40.02
November 1681.73 02-NOV-05:04 1043.64 764.63 4950.52 0.00 0.00 0.00 0.00 0.00 37.92
December 1457.03 23-DEC-16:03 521.82 573.49 2165.85 0.00 0.00 0.00 0.00 0.00 77.07
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1457.03   0.00 90.96 773.52 0.00 0.00 0.00 0.00 0.00 0.76
Maximum of Months 22326.68   1239.33 764.63 4950.52 0.00 0.00 0.00 0.00 0.00 327.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5514.25 12-JAN-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 5061.96 18-FEB-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 165.66
March 3394.65 21-MAR-05:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 5438.09 24-APR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 142.17
May 6713.03 15-MAY-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83.48
June 7797.75 26-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.96
July 8556.60 31-JUL-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.77
August 7810.09 07-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38.77
September 7148.63 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31.31
October 3924.96 03-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.27
November 3479.43 09-NOV-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 3777.29 15-DEC-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3394.65   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8556.60   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 165.66



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7753.87 12-JAN-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 788.19
February 6844.26 18-FEB-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 627.57
March 6891.15 16-MAR-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 526.64
April 6391.06 03-APR-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 810.81
May 4257.12 15-MAY-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 148.12
June 5383.14 24-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 46.71
July 6180.38 05-JUL-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.69
August 5384.49 14-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 97.21
September 4300.71 05-SEP-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.80
October 6904.14 30-OCT-03:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 950.05
November 6996.53 20-NOV-04:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 6939.72 15-DEC-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4257.12   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7753.87   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 950.05



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 677.55
February 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 559.99
March 423.23 22-MAR-16:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 5339.58 21-APR-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 55.47
May 11279.42 31-MAY-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.01
June 12750.06 29-JUN-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.12 0.00
July 13296.40 21-JUL-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.42 0.00
August 10735.29 11-AUG-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.56
September 2857.46 07-SEP-16:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 60.04
October 203.88 04-OCT-16:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 52.96
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 632.34
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13296.40   0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.42 677.55



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1019.60 23-JAN-15:20 222.14 284.97 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3450.98 15-FEB-16:20 222.14 284.97 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6786.26 31-MAR-24:00 0.00 15.83 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 8268.29 20-APR-18:50 23.38 94.99 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3441.52 31-MAY-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5340.70 30-JUN-24:00 0.00 15.83 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7234.33 31-JUL-23:45 0.00 31.66 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
August 8194.03 27-AUG-18:34 0.00 79.16 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
September 2943.83 30-SEP-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4513.53 31-OCT-24:00 0.00 15.83 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5391.71 08-NOV-16:00 444.28 569.94 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
December 6973.04 26-DEC-17:00 222.14 284.97 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1019.60   0.00 15.83 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8268.29   444.28 569.94 38972.11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 656.67 12-JAN-08:65 444.28 569.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
February 2731.24 16-FEB-16:20 222.14 284.97 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 5847.35 31-MAR-23:20 0.00 15.83 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7847.92 20-APR-18:50 23.38 94.99 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3204.88 31-MAY-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5105.62 30-JUN-24:00 0.00 15.83 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7008.30 31-JUL-23:53 0.00 47.50 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7643.29 27-AUG-18:48 0.00 94.99 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
September 2224.12 30-SEP-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 3323.92 31-OCT-23:30 0.00 15.83 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 4494.53 08-NOV-15:50 222.14 284.97 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 5762.35 21-DEC-17:00 222.14 284.97 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 656.67   0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7847.92   444.28 569.94 46766.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 635.17 12-JAN-08:15 444.28 569.94 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
February 2287.73 09-FEB-16:00 222.14 284.97 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 4810.15 31-MAR-23:10 0.00 15.83 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7796.33 20-APR-18:50 23.38 94.99 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3153.81 31-MAY-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5075.34 30-JUN-23:50 0.00 15.83 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6978.61 31-JUL-23:37 0.00 47.50 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7664.87 27-AUG-18:42 0.00 94.99 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
September 1681.82 08-SEP-17:30 23.38 94.99 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
October 2933.62 03-OCT-16:00 222.14 284.97 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
November 3994.16 08-NOV-15:50 222.14 284.97 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 5268.69 21-DEC-17:00 222.14 284.97 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 635.17   0.00 15.83 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7796.33   444.28 569.94 46766.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 88695.84 25-JAN-17:00 4808.68 3337.76 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 180525.55 09-FEB-17:00 4808.68 3337.76 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 357160.31 31-MAR-24:00 0.00 185.45 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 366184.45 21-APR-16:00 4808.68 3337.76 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
May 175474.50 31-MAY-24:00 0.00 185.45 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 267228.23 30-JUN-24:00 0.00 185.45 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
July 359866.43 31-JUL-23:57 0.00 556.35 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
August 367550.47 28-AUG-16:00 4808.68 3337.76 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
September 174609.41 30-SEP-24:00 0.00 185.45 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 265540.68 31-OCT-24:00 0.00 185.45 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 273142.11 03-NOV-16:00 4808.68 3337.76 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 364746.61 26-DEC-17:00 4808.68 3337.76 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 88695.84   0.00 185.45 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 367550.47   4808.68 3337.76 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.130692E+13 866729.99 09-JAN-08:20 0.115857E+13 2310304.04 12-JAN-07:10
February 0.149938E+13 1004915.74 09-FEB-08:20 0.712162E+12 2508292.19 27-FEB-07:10
March 0.204782E+13 1143491.53 14-MAR-07:19 0.392101E+12 1893703.75 01-MAR-07:19
April 0.230075E+13 1286529.89 21-APR-15:39 0.125891E+12 879235.64 04-APR-06:10
May 0.132504E+13 1029099.01 31-MAY-15:50 0.778124E+11 325296.17 27-MAY-06:10
June 0.175111E+13 1240248.22 20-JUN-15:20 0.733265E+11 87006.54 01-JUN-11:30
July 0.215871E+13 1388921.87 11-JUL-15:39 0.689801E+11 85768.17 03-JUL-11:20
August 0.251944E+13 1521573.26 11-AUG-15:39 0.736225E+11 401971.86 31-AUG-06:10
September 0.122350E+13 864326.93 07-SEP-15:00 0.882190E+11 515663.94 25-SEP-06:10
October 0.164745E+13 1006749.51 13-OCT-07:40 0.267872E+12 1065412.91 23-OCT-06:10
November 0.198781E+13 1143228.10 13-NOV-08:30 0.928776E+12 2207515.28 27-NOV-07:19
December 0.241175E+13 1281620.62 11-DEC-08:20 0.126647E+13 2052122.07 15-DEC-07:40
             
Annual Sum or Average 0.221797E+14     0.523381E+13    
Minimum of Months 0.122350E+13 864326.93   0.689801E+11 85768.17  
Maximum of Months 0.251944E+13 1521573.26   0.126647E+13 2508292.19  



Table of Contents

Report: EnergyConsumptionDistrictHeatingCoolingMonthly

For: Meter

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

DISTRICTCOOLING:FACILITY [J] DISTRICTCOOLING:FACILITY {Maximum} [W] DISTRICTCOOLING:FACILITY {TIMESTAMP} DISTRICTHEATING:FACILITY [J] DISTRICTHEATING:FACILITY {Maximum} [W] DISTRICTHEATING:FACILITY {TIMESTAMP}
January 0.231630E+12 91327.75 25-JAN-14:00 89891.93 6.86 13-JAN-00:40
February 0.430265E+12 183124.65 09-FEB-16:00 133646.69 7.30 22-FEB-00:30
March 0.725495E+12 357161.25 31-MAR-23:00 207677.26 11.09 31-MAR-23:30
April 0.942792E+12 368783.49 21-APR-15:00 152651.33 10.67 29-APR-18:30
May 0.241360E+12 175477.99 31-MAY-23:00 119185.60 13.36 31-MAY-23:40
June 0.471005E+12 267230.01 30-JUN-23:00 106856.41 10.98 30-JUN-23:30
July 0.733022E+12 359866.51 31-JUL-23:00 83195.35 11.32 18-JUL-23:30
August 0.979206E+12 370149.39 28-AUG-15:00 69098.11 11.50 07-AUG-23:30
September 0.235095E+12 174609.41 30-SEP-23:00 131021.10 4.88 01-SEP-23:40
October 0.484376E+12 265542.48 31-OCT-23:00 189322.13 10.96 31-OCT-23:30
November 0.702391E+12 275759.40 03-NOV-13:00 147241.19 7.61 01-NOV-23:30
December 0.968973E+12 367355.30 26-DEC-14:00 170437.48 11.52 31-DEC-18:30
             
Annual Sum or Average 0.714561E+13     1600224.59    
Minimum of Months 0.231630E+12 91327.75   69098.11 4.88  
Maximum of Months 0.979206E+12 370149.39   207677.26 13.36  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.185931E+12 0.575584E+11 0.766053E+12 0.202785E+12 0.740772E+11 0.108903E+11 0.00 0.114819E+10 47638160.69 0.00 0.843238E+10 0.00 0.00
February 0.161367E+12 0.394419E+11 0.978954E+12 0.219900E+12 0.641250E+11 0.136958E+11 0.00 0.133763E+11 0.863999E+09 0.00 0.765963E+10 0.00 0.00
March 0.183399E+12 0.303423E+11 0.141687E+13 0.284346E+12 0.720356E+11 0.177082E+11 0.00 0.320342E+11 0.225519E+10 0.00 0.882590E+10 0.00 0.00
April 0.160416E+12 0.179577E+11 0.165903E+13 0.314137E+12 0.822943E+11 0.942531E+10 0.00 0.468897E+11 0.627761E+10 0.00 0.432700E+10 0.00 0.00
May 0.172007E+12 0.102992E+11 0.774844E+12 0.202915E+12 0.111231E+12 0.174503E+11 0.00 0.284978E+11 0.708731E+10 0.00 0.708156E+09 0.00 0.00
June 0.170534E+12 0.502510E+10 0.106252E+13 0.235793E+12 0.134161E+12 0.370937E+11 0.00 0.834689E+11 0.219786E+11 0.00 0.536767E+09 0.00 0.00
July 0.160043E+12 0.737985E+10 0.139340E+13 0.284101E+12 0.130036E+12 0.433289E+11 0.00 0.112137E+12 0.274668E+11 0.00 0.811069E+09 0.00 0.00
August 0.179241E+12 0.145135E+11 0.173200E+13 0.324799E+12 0.120466E+12 0.316638E+11 0.00 0.919899E+11 0.242946E+11 0.00 0.469216E+09 0.00 0.00
September 0.162579E+12 0.241828E+11 0.740713E+12 0.196274E+12 0.755191E+11 0.693300E+10 0.00 0.115772E+11 0.242043E+10 0.00 0.330520E+10 0.00 0.00
October 0.174320E+12 0.375578E+11 0.108340E+13 0.243507E+12 0.666256E+11 0.136536E+11 0.00 0.194346E+11 0.202732E+10 0.00 0.692002E+10 0.00 0.00
November 0.180724E+12 0.504364E+11 0.135889E+13 0.275011E+12 0.679967E+11 0.178399E+11 0.00 0.272156E+11 0.151782E+10 0.00 0.817401E+10 0.00 0.00
December 0.182550E+12 0.632904E+11 0.170972E+13 0.324728E+12 0.715110E+11 0.102458E+11 0.00 0.392468E+11 0.212257E+10 0.00 0.833077E+10 0.00 0.00
                           
Annual Sum or Average 0.207311E+13 0.357985E+12 0.146764E+14 0.310830E+13 0.107008E+13 0.229929E+12 0.00 0.507016E+12 0.983598E+11 0.00 0.585001E+11 0.00 0.00
Minimum of Months 0.160043E+12 0.502510E+10 0.740713E+12 0.196274E+12 0.641250E+11 0.693300E+10 0.00 0.114819E+10 47638160.69 0.00 0.469216E+09 0.00 0.00
Maximum of Months 0.185931E+12 0.632904E+11 0.173200E+13 0.324799E+12 0.134161E+12 0.433289E+11 0.00 0.112137E+12 0.274668E+11 0.00 0.882590E+10 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.108357E+13 0.00 0.749993E+11 0.00 0.00
February 0.00 0.00 0.644113E+12 0.00 0.680493E+11 0.00 0.00
March 0.00 0.00 0.313086E+12 0.00 0.790153E+11 0.00 0.00
April 0.00 0.00 0.532632E+11 0.00 0.726277E+11 0.00 0.00
May 0.00 0.00 0.125504E+10 0.00 0.765573E+11 0.00 0.00
June 0.00 0.00 5853628.42 0.00 0.733207E+11 0.00 0.00
July 0.00 0.00 45530.43 0.00 0.689801E+11 0.00 0.00
August 0.00 0.00 0.107454E+10 0.00 0.725479E+11 0.00 0.00
September 0.00 0.00 0.215722E+11 0.00 0.666468E+11 0.00 0.00
October 0.00 0.00 0.198067E+12 0.00 0.698055E+11 0.00 0.00
November 0.00 0.00 0.858604E+12 0.00 0.701720E+11 0.00 0.00
December 0.00 0.00 0.119377E+13 0.00 0.727024E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.436838E+13 0.00 0.865424E+12 0.00 0.00
Minimum of Months 0.00 0.00 45530.43 0.00 0.666468E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.119377E+13 0.00 0.790153E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 198852.03 02-JAN-08:09 37611.08 01-JAN-06:10 423497.50 02-JAN-08:09 132050.65 02-JAN-08:20 70225.76 02-JAN-06:19 26320.96 19-JAN-06:10 0.00 01-JAN-00:10
February 198852.03 01-FEB-08:09 37611.08 01-FEB-06:10 541788.89 01-FEB-08:09 147235.96 01-FEB-08:20 63889.79 27-FEB-06:10 26409.73 06-FEB-06:10 0.00 01-FEB-00:10
March 198852.03 01-MAR-08:09 37611.08 01-MAR-06:10 660080.29 01-MAR-08:09 162421.26 01-MAR-08:20 93441.31 31-MAR-15:00 26366.85 01-MAR-06:10 0.00 01-MAR-00:10
April 180665.46 04-APR-07:10 37611.08 01-APR-05:10 778371.69 03-APR-07:10 177596.98 04-APR-07:19 136991.44 21-APR-15:39 26142.88 03-APR-06:10 0.00 01-APR-00:10
May 171684.52 08-MAY-14:30 24287.76 01-MAY-21:10 423497.50 01-MAY-07:10 132036.25 23-MAY-07:19 156876.85 31-MAY-14:50 41025.40 31-MAY-15:50 0.00 01-MAY-00:10
June 171658.20 27-JUN-07:30 24287.76 01-JUN-22:49 541788.89 01-JUN-07:10 147221.64 27-JUN-07:40 174427.28 30-JUN-12:09 43579.01 21-JUN-14:00 0.00 01-JUN-00:10
July 172814.03 25-JUL-07:10 24287.76 11-JUL-22:00 660080.29 03-JUL-07:10 162407.55 25-JUL-07:19 187307.75 12-JUL-12:09 44519.74 21-JUL-13:39 0.00 01-JUL-00:10
August 173709.30 18-AUG-15:00 37611.08 24-AUG-05:10 778371.69 01-AUG-07:10 177592.84 31-AUG-07:19 184370.80 10-AUG-15:50 44500.26 11-AUG-15:39 0.00 01-AUG-00:10
September 195531.25 28-SEP-07:10 37611.08 01-SEP-05:10 423497.50 01-SEP-07:10 132048.90 28-SEP-07:19 103218.18 08-SEP-15:30 26203.15 07-SEP-15:00 0.00 01-SEP-00:10
October 198852.03 03-OCT-07:10 37611.08 01-OCT-05:10 541788.89 02-OCT-07:10 147235.96 03-OCT-07:19 69423.69 03-OCT-13:39 26192.77 30-OCT-06:10 0.00 01-OCT-00:10
November 198852.03 01-NOV-07:10 37611.08 01-NOV-05:10 660080.29 01-NOV-07:10 162421.26 01-NOV-07:19 58556.74 27-NOV-05:10 26295.43 18-NOV-06:10 0.00 01-NOV-00:10
December 198852.03 01-DEC-08:09 37611.08 01-DEC-06:10 778371.69 01-DEC-08:09 177606.57 01-DEC-08:20 59508.42 04-DEC-06:10 26317.31 04-DEC-07:30 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 171658.20   24287.76   423497.50   132036.25   58556.74   26142.88   0.00  
Maximum of Months 198852.03   37611.08   778371.69   177606.57   187307.75   44519.74   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 2621.67 19-JAN-16:10 89.92 06-JAN-22:00 0.00 6524.59 02-JAN-07:10 0.00 0.00
February 9393.07 16-FEB-15:20 894.23 10-FEB-15:00 0.00 6524.59 01-FEB-07:10 0.00 0.00
March 17430.17 31-MAR-23:19 1727.73 20-MAR-14:00 0.00 6524.59 01-MAR-07:10 0.00 0.00
April 34234.12 20-APR-14:09 10881.16 22-APR-13:00 0.00 6524.59 01-APR-06:10 0.00 0.00
May 131708.19 31-MAY-15:50 13409.96 31-MAY-14:00 0.00 6524.59 01-MAY-20:40 0.00 0.00
June 184684.84 30-JUN-12:20 40140.23 29-JUN-10:50 0.00 6524.59 20-JUN-15:39 0.00 0.00
July 189861.63 21-JUL-13:09 40140.23 03-JUL-14:00 0.00 6524.59 11-JUL-12:50 0.00 0.00
August 195973.17 11-AUG-15:09 40140.23 23-AUG-14:50 0.00 6524.59 11-AUG-15:39 0.00 0.00
September 40061.18 07-SEP-15:00 9371.55 07-SEP-15:00 0.00 6524.59 05-SEP-20:30 0.00 0.00
October 11370.06 05-OCT-09:39 3823.28 01-OCT-14:00 0.00 6524.59 02-OCT-20:10 0.00 0.00
November 14012.29 08-NOV-15:20 925.45 03-NOV-21:00 0.00 6524.59 01-NOV-06:10 0.00 0.00
December 17405.82 27-DEC-12:00 1488.77 24-DEC-11:00 0.00 6524.59 01-DEC-07:10 0.00 0.00
                   
Annual Sum or Average         0.00     0.00 0.00
Minimum of Months 2621.67   89.92   0.00 6524.59   0.00 0.00
Maximum of Months 195973.17   40140.23   0.00 6524.59   0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 866729.99 09-JAN-08:20 198852.03 423497.50 37611.08 132050.65 40005.65 26170.74 0.00 2008.78 8.98
February 1004915.74 09-FEB-08:20 198852.03 541788.89 37611.08 147235.96 38520.94 26114.04 0.00 7686.66 581.55
March 1143491.53 14-MAR-07:19 198852.03 660080.29 37611.08 162421.26 39267.16 26123.07 0.00 12037.24 574.82
April 1286529.89 21-APR-15:39 171235.93 778371.69 0.00 143548.64 136991.44 26108.74 0.00 20977.20 9296.27
May 1029099.01 31-MAY-15:50 171235.93 423497.50 0.00 97992.72 150252.24 41025.40 0.00 131708.19 13387.04
June 1240248.22 20-JUN-15:20 171235.93 541788.89 0.00 113178.03 173570.47 43190.76 0.00 175573.55 17057.16
July 1388921.87 11-JUL-15:39 171235.93 660080.29 0.00 128363.33 178013.19 41873.12 0.00 186385.42 16446.00
August 1521573.26 11-AUG-15:39 171235.93 778371.69 0.00 143548.64 181084.70 44500.26 0.00 181652.18 14655.28
September 864326.93 07-SEP-15:00 171235.93 423497.50 0.00 97992.72 95964.91 26203.15 0.00 40061.18 9371.55
October 1006749.51 13-OCT-07:40 198852.03 541788.89 37611.08 147235.96 39534.77 26114.85 0.00 8616.86 470.49
November 1143228.10 13-NOV-08:30 198852.03 660080.29 37611.08 162421.26 40256.00 26165.03 0.00 10810.98 506.84
December 1281620.62 11-DEC-08:20 198852.03 778371.69 37611.08 177606.57 40464.08 26190.36 0.00 15307.30 692.94
                       
Annual Sum or Average                      
Minimum of Months 864326.93   171235.93 423497.50 0.00 97992.72 38520.94 26108.74 0.00 2008.78 8.98
Maximum of Months 1521573.26   198852.03 778371.69 37611.08 177606.57 181084.70 44500.26 0.00 186385.42 17057.16



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 2278319.81 12-JAN-07:10 0.00 87727.10 11-JAN-12:20 0.00
February 0.00 0.00 2476903.95 27-FEB-07:10 0.00 87724.88 27-FEB-12:00 0.00
March 0.00 0.00 1860012.77 01-MAR-07:19 0.00 87717.76 29-MAR-11:39 0.00
April 0.00 0.00 848561.12 04-APR-06:10 0.00 87751.33 06-APR-11:30 0.00
May 0.00 0.00 297263.40 27-MAY-06:10 0.00 87712.84 12-MAY-11:39 0.00
June 0.00 0.00 9349.62 02-JUN-06:10 0.00 87006.54 01-JUN-11:30 0.00
July 0.00 0.00 35.90 05-JUL-06:00 0.00 85768.17 03-JUL-11:20 0.00
August 0.00 0.00 371979.06 31-AUG-06:10 0.00 84860.31 01-AUG-11:30 0.00
September 0.00 0.00 493470.65 25-SEP-06:10 0.00 84665.62 29-SEP-11:30 0.00
October 0.00 0.00 1035258.31 23-OCT-06:10 0.00 85536.90 31-OCT-11:20 0.00
November 0.00 0.00 2176563.45 27-NOV-07:19 0.00 86684.41 30-NOV-12:30 0.00
December 0.00 0.00 2021079.39 15-DEC-07:40 0.00 87712.05 28-DEC-12:30 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 35.90   0.00 84665.62   0.00
Maximum of Months 0.00 0.00 2476903.95   0.00 87751.33   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.50 25.69 0.00 25.69
April 0.00 0.00 0.00 0.00 2.17 25.95 0.00 25.95
May 0.00 0.00 0.00 0.00 3.50 26.01 0.00 26.01
June 0.00 0.00 0.00 0.00 1.83 25.79 0.00 25.79
July 0.00 0.00 0.00 0.00 5.67 26.32 0.00 26.32
August 0.00 0.00 0.00 0.00 6.00 26.24 0.00 26.24
September 0.00 0.00 0.00 0.00 9.00 26.62 2.00 26.77
October 0.00 0.00 0.00 0.00 4.67 26.42 0.17 26.45
November 0.00 0.00 0.00 0.00 0.50 25.59 0.00 25.59
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   33.83 26.29 2.17 26.36
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 9.00 26.62 2.00 26.77



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.17 25.63 0.00 25.63
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.17 25.63 0.00 25.63
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 25.63 0.00 25.63



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.50 19.19 1.67 19.39 0.00 19.39 0.00 19.39
February 0.17 18.48 0.00 18.48 0.00 18.48 0.00 18.48
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.33 19.18 0.00 19.18 0.00 19.18 0.00 19.18
                 
Annual Sum or Average 4.00 19.16 1.67 19.35 0.00 19.35 0.00 19.35
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.50 19.19 1.67 19.39 0.00 19.39 0.00 19.39



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 16.33 18.85 4.33 19.08 0.00 19.08 0.00 19.08
February 11.50 18.80 3.33 19.04 0.00 19.04 0.00 19.04
March 4.00 18.60 0.50 18.79 0.00 18.79 0.00 18.79
April 0.83 19.09 0.17 19.31 0.00 19.31 0.00 19.31
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 3.50 18.64 0.50 18.85 0.00 18.85 0.00 18.85
November 13.00 18.77 3.50 19.02 0.00 19.02 0.00 19.02
December 16.17 18.97 3.67 19.13 0.00 19.13 0.00 19.13
                 
Annual Sum or Average 65.33 18.83 16.00 19.05 0.00 19.05 0.00 19.05
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16.33 19.09 4.33 19.31 0.00 19.31 0.00 19.31



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.33 19.17 0.33 19.33 0.00 19.33 0.00 19.33
February 0.67 19.01 0.00 19.01 0.00 19.01 0.00 19.01
March 0.33 19.32 0.00 19.32 0.00 19.32 0.00 19.32
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 25.65 0.00 25.65
June 0.00 0.00 0.00 0.00 5.67 25.91 0.00 25.91
July 0.00 0.00 0.00 0.00 3.17 25.85 0.00 25.85
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.33 19.34 0.00 19.34 0.00 19.34 0.00 19.34
December 0.67 19.32 0.00 19.32 0.00 19.32 0.00 19.32
                 
Annual Sum or Average 4.33 19.20 0.33 19.28 9.00 23.63 0.00 23.63
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.33 19.34 0.33 19.34 5.67 25.91 0.00 25.91



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.50 18.96 0.00 18.96 0.00 18.96 0.00 18.96
February 1.17 19.08 0.00 19.08 0.00 19.08 0.00 19.08
March 0.33 19.14 0.00 19.14 0.00 19.14 0.00 19.14
April 0.00 0.00 0.00 0.00 0.67 27.58 0.67 27.58
May 0.00 0.00 0.00 0.00 3.00 28.11 3.00 28.11
June 0.00 0.00 0.00 0.00 3.67 26.50 1.00 26.77
July 0.00 0.00 0.00 0.00 4.67 27.19 3.00 27.46
August 0.00 0.00 0.00 0.00 0.33 27.55 0.33 27.55
September 0.00 0.00 0.00 0.00 1.00 27.64 1.00 27.64
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.67 19.18 0.00 19.18 0.00 19.18 0.00 19.18
December 2.83 19.21 0.00 19.21 0.00 19.21 0.00 19.21
                 
Annual Sum or Average 7.50 19.10 0.00 19.10 13.33 24.33 9.00 25.40
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.83 19.21 0.00 19.21 4.67 28.11 3.00 28.11



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.00 18.68 0.00 18.68 0.00 18.68 0.00 18.68
February 1.67 18.87 0.00 18.87 0.00 18.87 0.00 18.87
March 0.50 19.29 0.00 19.29 0.17 21.29 0.17 22.49
April 0.00 0.00 0.00 0.00 2.50 27.84 2.50 27.84
May 0.00 0.00 0.00 0.00 4.83 27.77 4.83 27.77
June 0.00 0.00 0.00 0.00 2.83 27.78 2.83 27.78
July 0.00 0.00 0.00 0.00 4.00 27.93 3.83 27.95
August 0.00 0.00 0.00 0.00 2.50 28.02 2.33 28.05
September 0.00 0.00 0.00 0.00 0.50 27.71 0.50 27.71
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.00 19.14 0.00 19.14 0.00 19.14 0.00 19.14
December 3.17 19.11 0.00 19.11 0.00 19.11 0.00 19.11
                 
Annual Sum or Average 10.33 18.92 0.00 18.92 17.33 24.51 17.00 25.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.00 19.29 0.00 19.29 4.83 28.02 4.83 28.05



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.83 19.25 0.00 19.25 0.00 19.25 0.00 19.25
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 7.50 27.86 3.17 27.90
May 0.00 0.00 0.00 0.00 6.00 28.04 2.17 28.02
June 0.00 0.00 0.00 0.00 13.00 27.22 3.33 27.35
July 0.00 0.00 0.00 0.00 23.67 27.02 5.00 27.15
August 0.00 0.00 0.00 0.00 19.17 26.89 3.00 27.03
September 0.00 0.00 0.00 0.00 0.33 27.65 0.17 27.70
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.83 19.25 0.00 19.25 69.67 27.11 16.83 27.26
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.83 19.25 0.00 19.25 23.67 28.04 5.00 28.02



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 55.67 17.79 26.50 18.03 0.00 18.03 0.00 18.03
February 30.33 18.11 11.67 18.44 0.00 18.44 0.00 18.44
March 12.50 19.01 3.67 19.26 0.00 19.26 0.00 19.26
April 1.00 19.23 0.17 19.39 0.00 19.39 0.00 19.39
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 3.33 25.87 0.00 25.87
July 0.00 0.00 0.00 0.00 1.33 25.82 0.00 25.82
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 4.33 19.06 1.00 19.28 0.00 19.28 0.00 19.28
November 29.33 18.64 11.50 18.99 0.00 18.99 0.00 18.99
December 42.67 18.63 17.83 18.98 0.00 18.98 0.00 18.98
                 
Annual Sum or Average 175.83 18.32 72.33 18.60 4.67 18.73 0.00 18.73
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 55.67 19.23 26.50 19.39 3.33 25.87 0.00 25.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 29.83 15.94 7.50 15.76 0.00 15.76 0.00 15.76
February 11.33 16.90 0.67 16.79 0.00 16.79 0.00 16.79
March 5.50 18.64 0.17 18.70 0.00 18.70 0.00 18.70
April 0.50 19.05 0.00 19.05 0.50 23.24 0.50 24.64
May 0.00 0.00 0.00 0.00 3.17 28.25 3.17 28.25
June 0.00 0.00 0.00 0.00 3.17 26.72 1.33 27.04
July 0.00 0.00 0.00 0.00 4.67 27.67 4.00 27.80
August 0.00 0.00 0.00 0.00 0.50 27.59 0.50 27.59
September 0.00 0.00 0.00 0.00 0.67 27.66 0.67 27.66
October 2.17 18.66 0.00 18.66 0.00 18.66 0.00 18.66
November 12.17 17.24 0.17 17.21 0.00 17.21 0.00 17.21
December 18.00 16.93 2.17 16.81 0.00 16.81 0.00 16.81
                 
Annual Sum or Average 79.50 16.78 10.67 16.60 12.67 17.95 10.17 18.85
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.76 0.00 15.76
Maximum of Months 29.83 19.05 7.50 19.05 4.67 28.25 4.00 28.25



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 20.67 16.39 3.83 16.17 0.00 16.17 0.00 16.17
February 7.83 17.87 0.17 17.81 0.00 17.81 0.00 17.81
March 3.83 18.85 0.00 18.85 0.17 19.20 0.17 19.53
April 0.17 19.40 0.00 19.40 2.67 27.43 2.67 27.67
May 0.00 0.00 0.00 0.00 5.17 27.99 5.17 27.99
June 0.00 0.00 0.00 0.00 3.00 27.84 3.00 27.84
July 0.00 0.00 0.00 0.00 4.00 28.05 3.83 28.06
August 0.00 0.00 0.00 0.00 2.67 28.06 2.50 28.07
September 0.00 0.00 0.00 0.00 0.50 27.79 0.50 27.79
October 2.00 18.87 0.00 18.87 0.00 18.87 0.00 18.87
November 9.17 18.07 0.00 18.07 0.00 18.07 0.00 18.07
December 15.83 17.25 0.83 17.24 0.00 17.24 0.00 17.24
                 
Annual Sum or Average 59.50 17.32 4.83 17.18 18.17 19.55 17.83 21.05
Minimum of Months 0.00 0.00 0.00 0.00 0.00 16.17 0.00 16.17
Maximum of Months 20.67 19.40 3.83 19.40 5.17 28.06 5.17 28.07



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 19.33 16.56 3.17 16.35 0.00 16.35 0.00 16.35
February 6.50 18.13 0.00 18.13 0.00 18.13 0.00 18.13
March 4.00 18.77 0.00 18.77 0.00 18.77 0.00 18.77
April 0.00 0.00 0.00 0.00 1.17 27.73 0.33 27.75
May 0.00 0.00 0.00 0.00 5.00 27.95 1.67 27.91
June 0.00 0.00 0.00 0.00 4.67 27.95 1.17 27.97
July 0.00 0.00 0.00 0.00 4.17 27.67 1.50 27.65
August 0.00 0.00 0.00 0.00 2.00 27.84 0.67 27.85
September 0.00 0.00 0.00 0.00 0.17 27.29 0.17 27.29
October 1.67 18.91 0.00 18.91 0.00 18.91 0.00 18.91
November 8.00 18.37 0.00 18.37 0.00 18.37 0.00 18.37
December 10.33 18.25 0.33 18.32 0.00 18.32 0.00 18.32
                 
Annual Sum or Average 49.83 17.66 3.50 17.53 17.17 20.04 5.50 20.60
Minimum of Months 0.00 0.00 0.00 0.00 0.00 16.35 0.00 16.35
Maximum of Months 19.33 18.91 3.17 18.91 5.00 27.95 1.67 27.97



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 111.17 16.84 50.33 17.17 0.00 17.17 0.00 17.17
February 88.50 16.76 38.33 17.09 0.00 17.09 0.00 17.09
March 56.00 17.73 21.33 18.16 0.00 18.16 0.00 18.16
April 11.00 17.61 3.50 17.81 0.00 17.81 0.00 17.81
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.83 25.63 0.00 25.63
July 0.00 0.00 0.00 0.00 0.67 25.79 0.00 25.79
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 1.17 19.00 0.00 19.00 0.00 19.00 0.00 19.00
October 30.83 17.01 11.50 17.12 0.00 17.12 0.00 17.12
November 100.67 16.83 46.50 17.10 0.00 17.10 0.00 17.10
December 123.33 17.05 55.50 17.44 0.00 17.44 0.00 17.44
                 
Annual Sum or Average 522.67 17.00 227.00 17.32 1.50 17.34 0.00 17.34
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 123.33 19.00 55.50 19.00 0.83 25.79 0.00 25.79



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 63.50 15.06 17.50 14.95 0.00 14.95 0.00 14.95
February 49.50 15.33 12.00 15.25 0.00 15.25 0.00 15.25
March 22.83 16.32 1.00 16.26 0.00 16.26 0.00 16.26
April 5.33 17.07 0.33 16.95 0.00 16.95 0.00 16.95
May 0.00 0.00 0.00 0.00 2.67 28.10 2.67 28.10
June 0.00 0.00 0.00 0.00 1.67 27.16 1.17 27.39
July 0.00 0.00 0.00 0.00 4.67 27.63 4.00 27.77
August 0.00 0.00 0.00 0.00 0.33 27.45 0.33 27.45
September 1.17 19.06 0.00 19.06 0.00 19.06 0.00 19.06
October 17.83 16.17 3.00 15.98 0.00 15.98 0.00 15.98
November 61.67 15.20 19.00 15.09 0.00 15.09 0.00 15.09
December 70.83 15.20 18.00 15.16 0.00 15.16 0.00 15.16
                 
Annual Sum or Average 292.67 15.39 70.83 15.27 9.33 15.58 8.17 15.85
Minimum of Months 0.00 0.00 0.00 0.00 0.00 14.95 0.00 14.95
Maximum of Months 70.83 19.06 19.00 19.06 4.67 28.10 4.00 28.10



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 57.33 15.10 15.17 14.99 0.00 14.99 0.00 14.99
February 37.17 15.51 5.83 15.43 0.00 15.43 0.00 15.43
March 15.17 17.03 0.67 16.94 0.00 16.94 0.00 16.94
April 2.50 18.39 0.00 18.39 1.17 21.36 1.17 22.89
May 0.00 0.00 0.00 0.00 3.67 27.89 3.67 27.89
June 0.00 0.00 0.00 0.00 2.67 27.87 2.50 27.89
July 0.00 0.00 0.00 0.00 3.67 28.16 3.33 28.19
August 0.00 0.00 0.00 0.00 1.67 28.34 1.50 28.37
September 0.83 19.06 0.00 19.06 0.17 20.47 0.17 21.48
October 14.67 16.51 2.17 16.30 0.00 16.30 0.00 16.30
November 51.00 15.37 14.83 15.25 0.00 15.25 0.00 15.25
December 63.17 15.16 15.67 15.07 0.00 15.07 0.00 15.07
                 
Annual Sum or Average 241.83 15.49 54.33 15.35 13.00 15.89 12.33 16.35
Minimum of Months 0.00 0.00 0.00 0.00 0.00 14.99 0.00 14.99
Maximum of Months 63.17 19.06 15.67 19.06 3.67 28.34 3.67 28.37



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 54.17 15.11 15.17 14.97 0.00 14.97 0.00 14.97
February 38.67 15.45 10.67 15.32 0.00 15.32 0.00 15.32
March 13.00 17.30 0.00 17.30 0.00 17.30 0.00 17.30
April 2.17 18.35 0.00 18.35 0.50 20.12 0.17 20.58
May 0.00 0.00 0.00 0.00 4.00 27.80 0.83 27.77
June 0.00 0.00 0.00 0.00 4.33 27.99 1.00 28.01
July 0.00 0.00 0.00 0.00 4.00 27.68 1.50 27.66
August 0.00 0.00 0.00 0.00 1.33 27.94 0.50 27.93
September 0.67 19.12 0.00 19.12 0.00 19.12 0.00 19.12
October 11.00 16.87 0.83 16.73 0.00 16.73 0.00 16.73
November 40.67 15.56 9.33 15.43 0.00 15.43 0.00 15.43
December 44.33 15.49 11.83 15.38 0.00 15.38 0.00 15.38
                 
Annual Sum or Average 204.67 15.63 47.83 15.46 14.17 16.12 4.00 16.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 14.97 0.00 14.97
Maximum of Months 54.17 19.12 15.17 19.12 4.33 27.99 1.50 28.01



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 481.33 23.51 3.67 23.49 3.67 23.46
February 394.50 23.69 2.17 23.67 2.17 23.65
March 411.17 23.95 4.17 23.97 0.00 23.97
April 305.83 24.01 45.00 24.31 0.00 24.31
May 150.83 24.00 84.67 24.81 0.00 24.81
June 11.50 24.00 190.33 25.13 0.17 25.13
July 0.00 0.00 348.00 24.92 0.00 24.92
August 20.00 24.00 251.17 24.96 0.00 24.96
September 64.33 24.00 109.50 25.36 0.00 25.36
October 230.17 24.01 63.00 24.52 0.00 24.52
November 380.00 23.51 9.00 23.52 3.17 23.49
December 447.83 23.25 16.33 23.29 4.33 23.26
             
Annual Sum or Average 2897.50 23.69 1127.00 24.15 13.50 24.13
Minimum of Months 0.00 0.00 2.17 23.29 0.00 23.26
Maximum of Months 481.33 24.01 348.00 25.36 4.33 25.36



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 22.94 12.00 22.92 12.00 22.90
February 443.83 23.54 0.00 23.54 0.00 23.54
March 433.50 23.81 0.50 23.81 0.00 23.81
April 259.17 23.99 22.67 24.15 0.00 24.15
May 138.83 23.97 37.83 24.38 0.00 24.38
June 1.50 24.00 170.33 24.64 0.00 24.64
July 0.00 0.00 358.00 24.36 0.00 24.36
August 11.50 24.03 273.50 24.40 0.00 24.40
September 109.83 23.83 60.83 24.55 0.00 24.55
October 297.83 23.87 29.67 24.04 0.00 24.04
November 487.50 23.78 0.00 23.78 0.00 23.78
December 481.83 23.47 0.00 23.47 0.00 23.47
             
Annual Sum or Average 3167.33 23.61 965.33 23.85 12.00 23.84
Minimum of Months 0.00 0.00 0.00 22.92 0.00 22.90
Maximum of Months 502.00 24.03 358.00 24.64 12.00 24.64



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.05 268.67 20.83 268.67 20.73
February 454.00 21.64 138.17 21.42 138.17 21.29
March 514.00 22.49 34.33 22.40 34.33 22.33
April 462.17 23.46 0.00 23.46 0.00 23.46
May 310.50 23.84 1.50 23.84 0.00 23.84
June 62.33 23.80 111.83 24.34 0.00 24.34
July 3.67 23.61 238.50 24.45 0.00 24.45
August 77.17 23.75 136.33 24.29 0.00 24.29
September 295.67 23.55 15.00 23.64 0.00 23.64
October 499.17 22.86 8.17 22.83 8.17 22.80
November 489.00 21.51 170.33 21.33 170.33 21.22
December 497.00 21.20 280.50 21.03 280.50 20.95
             
Annual Sum or Average 4166.67 22.33 1403.33 22.26 900.17 22.04
Minimum of Months 3.67 21.05 0.00 20.83 0.00 20.73
Maximum of Months 514.00 23.84 280.50 24.45 280.50 24.45



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.11 483.50 20.09 483.50 20.08
February 454.00 20.30 368.50 20.19 368.50 20.15
March 514.00 20.90 313.67 20.72 313.67 20.63
April 485.00 22.11 115.83 21.77 115.83 21.54
May 415.33 23.45 0.00 23.45 0.00 23.45
June 114.83 23.67 71.33 23.94 0.00 23.94
July 33.17 23.44 216.83 24.27 0.00 24.27
August 163.83 23.34 105.33 23.78 0.00 23.78
September 474.00 22.48 32.33 22.37 32.33 22.27
October 502.00 20.93 249.00 20.68 249.00 20.56
November 489.00 20.18 457.83 20.15 457.83 20.14
December 497.00 20.11 494.67 20.11 494.67 20.11
             
Annual Sum or Average 4644.17 21.29 2908.83 21.08 2515.33 20.85
Minimum of Months 33.17 20.11 0.00 20.09 0.00 20.08
Maximum of Months 514.00 23.67 494.67 24.27 494.67 24.27



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.47 467.17 20.45 467.17 20.44
February 454.00 20.87 290.50 20.73 290.50 20.67
March 514.00 21.80 144.67 21.60 144.67 21.47
April 471.83 23.33 9.83 23.29 9.83 23.24
May 266.50 23.92 10.00 23.99 0.00 23.99
June 4.17 24.00 216.50 24.59 0.00 24.59
July 0.00 0.00 389.50 24.46 0.00 24.46
August 43.33 23.79 196.33 24.28 0.00 24.28
September 388.83 23.29 13.83 23.37 0.00 23.37
October 499.50 22.28 79.17 22.09 79.17 21.94
November 489.00 20.85 359.50 20.78 359.50 20.76
December 497.00 20.72 437.50 20.68 437.50 20.67
             
Annual Sum or Average 4130.17 21.83 2614.50 21.83 1788.33 21.57
Minimum of Months 0.00 0.00 9.83 20.45 0.00 20.44
Maximum of Months 514.00 24.00 467.17 24.59 467.17 24.59



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.39 482.00 20.37 482.00 20.37
February 454.00 20.86 301.33 20.73 301.33 20.67
March 490.50 21.99 120.83 21.77 119.00 21.62
April 348.50 23.00 34.17 23.10 10.83 23.05
May 134.00 23.86 134.00 24.34 8.33 24.42
June 17.67 24.40 281.33 24.37 3.83 24.40
July 17.83 26.02 393.17 24.44 13.17 24.52
August 77.00 23.51 254.17 24.04 1.17 24.05
September 316.33 23.03 49.17 23.38 0.83 23.39
October 491.50 22.09 81.50 21.90 81.50 21.75
November 489.00 20.65 447.67 20.63 447.67 20.62
December 497.00 20.52 488.83 20.52 488.83 20.52
             
Annual Sum or Average 3835.33 21.60 3068.17 21.77 1958.50 21.52
Minimum of Months 17.67 20.39 34.17 20.37 0.83 20.37
Maximum of Months 502.00 26.02 488.83 24.44 488.83 24.52



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.31 465.00 20.26 465.00 20.24
February 443.17 21.12 257.50 20.89 257.50 20.78
March 427.67 21.92 119.67 21.80 107.83 21.64
April 269.67 22.96 96.50 23.31 16.50 23.24
May 193.17 23.63 116.00 24.11 7.17 24.18
June 35.67 24.47 290.00 24.46 9.17 24.53
July 21.67 26.05 402.17 24.51 15.83 24.60
August 76.83 23.84 306.17 24.26 8.33 24.32
September 292.67 22.87 84.83 23.29 0.50 23.29
October 457.00 21.92 93.33 21.76 85.67 21.60
November 487.83 20.71 404.67 20.61 404.67 20.58
December 497.00 20.40 494.83 20.39 494.83 20.39
             
Annual Sum or Average 3704.33 21.57 3130.67 21.83 1873.00 21.56
Minimum of Months 21.67 20.31 84.83 20.26 0.50 20.24
Maximum of Months 502.00 26.05 494.83 24.51 494.83 24.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.75 351.00 20.69 351.00 20.66
February 454.00 21.58 135.50 21.41 135.50 21.30
March 445.00 22.91 24.17 22.91 15.83 22.84
April 116.50 23.99 139.17 24.76 5.83 24.82
May 79.17 23.89 119.67 24.79 5.67 24.86
June 10.33 27.04 400.83 24.71 10.33 24.77
July 24.83 26.94 497.00 24.74 24.83 24.84
August 17.83 26.69 466.83 24.65 16.17 24.72
September 225.17 23.25 72.33 23.73 0.67 23.74
October 413.50 22.75 8.33 22.81 0.33 22.81
November 489.00 21.82 72.83 21.71 72.83 21.63
December 497.00 21.73 126.67 21.58 126.67 21.48
             
Annual Sum or Average 3274.33 22.18 2414.33 22.79 765.67 22.61
Minimum of Months 10.33 20.75 8.33 20.69 0.33 20.66
Maximum of Months 502.00 27.04 497.00 24.79 351.00 24.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.84 502.00 19.84 502.00 19.84
February 454.00 19.98 450.50 19.98 450.50 19.98
March 514.00 20.52 459.50 20.47 459.50 20.45
April 485.00 21.86 146.83 21.53 146.83 21.33
May 419.50 23.70 0.00 23.70 0.00 23.70
June 20.00 23.90 153.67 24.46 0.00 24.46
July 4.00 23.65 304.00 24.49 0.00 24.49
August 165.33 23.35 78.33 23.72 0.00 23.72
September 479.17 22.43 32.00 22.33 32.00 22.25
October 502.00 20.76 312.83 20.59 312.83 20.52
November 489.00 19.89 489.00 19.89 489.00 19.89
December 497.00 19.83 497.00 19.83 497.00 19.83
             
Annual Sum or Average 4531.00 21.03 3425.67 20.91 2889.67 20.68
Minimum of Months 4.00 19.83 0.00 19.83 0.00 19.83
Maximum of Months 514.00 23.90 502.00 24.49 502.00 24.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 19.69 427.00 19.69 427.00 19.69
February 385.00 19.94 378.83 19.93 378.83 19.93
March 432.00 20.90 286.33 20.70 286.33 20.62
April 353.00 22.25 85.67 22.07 73.33 21.85
May 173.00 23.67 99.17 24.14 9.33 24.24
June 41.50 23.98 212.33 24.40 5.17 24.45
July 31.00 25.31 321.33 24.69 16.83 24.79
August 110.00 23.29 181.00 24.02 1.50 24.04
September 337.67 22.33 42.83 22.51 17.33 22.45
October 425.83 20.85 238.33 20.66 238.33 20.57
November 417.00 19.73 417.00 19.73 417.00 19.73
December 422.00 19.64 422.00 19.64 422.00 19.64
             
Annual Sum or Average 3555.00 20.91 3111.83 21.05 2293.00 20.79
Minimum of Months 31.00 19.64 42.83 19.64 1.50 19.64
Maximum of Months 432.00 25.31 427.00 24.69 427.00 24.79



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.94 493.17 19.93 493.17 19.92
February 449.33 20.61 359.83 20.45 359.83 20.38
March 439.83 21.32 237.67 21.14 224.17 20.98
April 293.33 22.46 136.33 22.74 54.00 22.57
May 223.67 23.47 116.83 23.95 11.17 24.06
June 80.67 23.85 256.83 24.33 10.17 24.40
July 59.00 24.32 358.50 24.52 15.67 24.61
August 129.00 23.46 258.00 24.15 8.83 24.22
September 316.00 22.55 89.83 22.98 6.67 22.96
October 471.83 21.32 208.50 21.07 204.00 20.93
November 489.00 20.12 464.33 20.07 464.33 20.06
December 497.00 19.88 497.00 19.88 497.00 19.88
             
Annual Sum or Average 3950.67 21.21 3476.83 21.40 2349.00 21.13
Minimum of Months 59.00 19.88 89.83 19.88 6.67 19.88
Maximum of Months 502.00 24.32 497.00 24.52 497.00 24.61



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.96 502.00 19.96 502.00 19.96
February 454.00 20.16 432.83 20.14 432.83 20.13
March 514.00 20.87 364.67 20.74 364.67 20.68
April 383.17 22.31 95.67 22.19 71.67 22.01
May 251.00 23.38 61.83 23.72 2.17 23.75
June 46.83 23.86 241.50 24.55 5.00 24.60
July 20.00 24.33 368.67 24.55 6.00 24.58
August 124.33 23.31 220.17 24.07 3.17 24.10
September 421.33 22.40 21.17 22.44 9.33 22.41
October 502.00 20.94 264.00 20.77 264.00 20.69
November 489.00 20.08 488.00 20.08 488.00 20.08
December 497.00 20.01 497.00 20.01 497.00 20.01
             
Annual Sum or Average 4204.67 21.06 3557.50 21.18 2645.83 20.94
Minimum of Months 20.00 19.96 21.17 19.96 2.17 19.96
Maximum of Months 514.00 24.33 502.00 24.55 502.00 24.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.61 502.00 19.61 502.00 19.61
February 454.00 19.72 454.00 19.72 454.00 19.72
March 514.00 20.07 506.50 20.07 506.50 20.06
April 485.00 20.75 297.83 20.52 297.83 20.42
May 478.67 22.89 16.67 22.82 16.67 22.74
June 76.17 23.43 104.17 23.99 0.00 23.99
July 58.67 23.33 257.00 24.17 0.00 24.17
August 291.33 22.76 63.17 22.96 9.17 22.91
September 485.00 21.14 173.17 20.97 173.17 20.88
October 502.00 20.01 464.50 19.97 464.50 19.95
November 489.00 19.64 489.00 19.64 489.00 19.64
December 497.00 19.56 497.00 19.56 497.00 19.56
             
Annual Sum or Average 4832.83 20.60 3825.00 20.48 3409.83 20.29
Minimum of Months 58.67 19.56 16.67 19.56 0.00 19.56
Maximum of Months 514.00 23.43 506.50 24.17 506.50 24.17



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.71 502.00 19.71 502.00 19.71
February 454.00 19.82 453.33 19.82 453.33 19.82
March 514.00 20.35 437.33 20.25 437.33 20.20
April 448.33 21.63 192.17 21.24 188.83 21.01
May 223.33 23.22 99.33 23.59 12.67 23.62
June 63.33 23.53 268.67 24.20 4.17 24.23
July 62.00 24.25 375.83 24.45 17.67 24.55
August 159.67 22.96 200.83 23.72 3.00 23.71
September 438.33 21.60 105.33 21.42 100.50 21.26
October 502.00 20.17 420.00 20.07 420.00 20.03
November 489.00 19.72 489.00 19.72 489.00 19.72
December 497.00 19.66 497.00 19.66 497.00 19.66
             
Annual Sum or Average 4353.00 20.65 4040.83 20.79 3125.50 20.56
Minimum of Months 62.00 19.66 99.33 19.66 3.00 19.66
Maximum of Months 514.00 24.25 502.00 24.45 502.00 24.55



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.73 502.00 19.73 502.00 19.73
February 454.00 20.06 416.17 19.97 416.17 19.94
March 482.17 20.81 343.33 20.54 343.33 20.43
April 349.50 21.75 186.00 21.69 135.17 21.42
May 265.50 22.82 103.33 23.29 14.50 23.30
June 118.00 23.38 237.50 24.08 8.67 24.15
July 104.33 23.60 333.67 24.29 13.83 24.38
August 184.67 22.94 233.17 23.76 10.17 23.78
September 381.33 21.71 128.33 21.82 79.67 21.64
October 488.67 20.47 377.00 20.30 374.67 20.23
November 489.00 19.78 484.50 19.77 484.50 19.77
December 497.00 19.68 497.00 19.68 497.00 19.68
             
Annual Sum or Average 4316.17 20.83 3842.00 20.96 2879.67 20.70
Minimum of Months 104.33 19.68 103.33 19.68 8.67 19.68
Maximum of Months 502.00 23.60 502.00 24.29 502.00 24.38



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.75 502.00 19.75 502.00 19.75
February 454.00 19.89 450.83 19.88 450.83 19.88
March 514.00 20.36 454.67 20.28 454.67 20.26
April 416.00 21.49 186.67 21.22 172.00 21.01
May 328.83 22.86 54.50 23.08 7.17 23.05
June 92.33 23.42 219.67 24.28 4.83 24.32
July 69.83 23.53 334.67 24.34 6.50 24.38
August 198.50 22.87 186.67 23.62 4.33 23.62
September 457.83 21.58 102.83 21.44 98.17 21.31
October 502.00 20.27 426.67 20.19 426.67 20.16
November 489.00 19.80 489.00 19.80 489.00 19.80
December 497.00 19.74 497.00 19.74 497.00 19.74
             
Annual Sum or Average 4521.33 20.74 3905.17 20.81 3113.17 20.59
Minimum of Months 69.83 19.74 54.50 19.74 4.33 19.74
Maximum of Months 514.00 23.53 502.00 24.34 502.00 24.38



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.33 26.03 219.17 26.98 0.00 26.98
February 0.00 0.00 352.67 27.00 0.00 27.00
March 0.00 0.00 508.67 27.00 0.00 27.00
April 11.67 27.00 485.00 27.00 11.67 27.00
May 0.00 0.00 508.00 27.00 0.00 27.00
June 2.17 27.00 496.00 27.00 2.17 27.00
July 15.17 27.00 497.00 27.00 15.17 27.00
August 30.17 27.00 514.00 27.00 30.17 27.00
September 0.00 0.00 485.00 27.00 0.00 27.00
October 0.00 0.00 502.00 27.00 0.00 27.00
November 0.00 0.00 473.50 27.00 0.00 27.00
December 0.00 0.00 489.83 27.00 0.00 27.00
             
Annual Sum or Average 63.50 26.93 5530.83 27.00 59.17 27.00
Minimum of Months 0.00 0.00 219.17 26.98 0.00 26.98
Maximum of Months 30.17 27.00 514.00 27.00 30.17 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 385.17 25.32 12.83 25.23 12.00 25.14
February 53.00 27.00 73.17 27.00 0.00 27.00
March 0.00 0.00 239.83 27.00 0.00 27.00
April 1.17 27.00 439.33 27.00 1.17 27.00
May 0.00 0.00 508.00 27.00 0.00 27.00
June 0.00 0.00 496.00 27.00 0.00 27.00
July 3.33 27.00 497.00 27.00 3.33 27.00
August 1.17 27.00 514.00 27.00 1.17 27.00
September 0.00 0.00 485.00 27.00 0.00 27.00
October 0.00 0.00 337.17 27.00 0.00 27.00
November 26.83 27.00 23.00 27.00 0.00 27.00
December 39.67 27.00 2.17 27.00 0.00 27.00
             
Annual Sum or Average 510.33 25.73 3627.50 26.83 17.67 26.82
Minimum of Months 0.00 0.00 2.17 25.23 0.00 25.14
Maximum of Months 385.17 27.00 514.00 27.00 12.00 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 498.50 24.21 82.00 23.87 82.00 23.61
February 123.33 26.73 15.17 26.76 0.00 26.76
March 69.67 27.00 89.33 27.00 0.00 27.00
April 24.00 27.00 333.83 27.00 0.67 27.00
May 0.00 0.00 502.50 27.00 0.00 27.00
June 0.00 0.00 496.00 27.00 0.00 27.00
July 5.00 27.00 497.00 27.00 5.00 27.00
August 1.50 27.00 514.00 27.00 1.50 27.00
September 14.50 26.01 410.50 26.97 0.00 26.97
October 49.83 27.00 162.00 27.00 0.00 27.00
November 135.00 27.00 0.00 27.00 0.00 27.00
December 146.33 27.00 0.00 27.00 0.00 27.00
             
Annual Sum or Average 1067.67 25.65 3102.33 26.55 89.17 26.46
Minimum of Months 0.00 0.00 0.00 23.87 0.00 23.61
Maximum of Months 498.50 27.00 514.00 27.00 82.00 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 70.83 27.00 502.00 27.00 70.83 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.00 485.00 27.00 485.00 27.00
May 508.00 27.00 508.00 27.00 508.00 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 27.00 514.00 27.00 514.00 27.00
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.00 497.00 27.00 497.00 27.00
             
Annual Sum or Average 5511.83 27.00 5943.00 27.00 5511.83 27.00
Minimum of Months 70.83 27.00 454.00 27.00 70.83 27.00
Maximum of Months 514.00 27.00 514.00 27.00 514.00 27.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.94685 10.83000 0.51817 10.71695
February 454.00000 27.00000 11.32104 0.61081 12.94302
March 514.00000 27.00000 12.13817 0.71082 15.74685
April 485.00000 26.99999 15.37054 0.84414 20.14214
May 508.00000 27.00000 22.35755 0.14358 5.48497
June 496.00000 27.00039 28.40628 0.26841 6.53928
July 497.00000 27.00052 29.87289 0.32475 7.22978
August 514.00000 27.00021 28.39844 0.34259 7.48775
September 485.00000 27.00012 25.26418 0.12518 5.44457
October 502.00000 27.00000 17.55822 0.73360 16.45685
November 489.00000 27.00000 9.93675 0.63719 13.56816
December 497.00000 27.00000 8.99329 0.63441 13.50715
           
Annual Sum or Average 5943.00000 26.99561 18.43463 0.48993 11.24692
Minimum of Months 454.00000 26.94685 8.99329 0.12518 5.44457
Maximum of Months 514.00000 27.00052 29.87289 0.84414 20.14214



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 25.64225 10.82359 0.15627 6.67960
February 454.00000 27.00000 11.29965 0.45878 9.55298
March 514.00000 27.00000 12.12812 0.53971 11.24424
April 485.00000 27.00000 15.36169 0.69507 15.41248
May 508.00000 27.00000 22.34482 0.06954 5.20057
June 496.00000 27.00037 28.41365 0.18498 5.77461
July 497.00000 27.00049 29.89419 0.21684 6.02844
August 514.00000 27.00021 28.39773 0.20193 5.93243
September 485.00000 27.00011 25.30161 0.00892 5.18732
October 502.00000 27.00000 17.54388 0.58380 12.32298
November 489.00000 27.00000 9.92509 0.44788 9.27097
December 497.00000 27.00000 8.98958 0.43400 9.00921
           
Annual Sum or Average 5943.00000 26.88541 18.43268 0.33182 8.44849
Minimum of Months 454.00000 25.64225 8.98958 0.00892 5.18732
Maximum of Months 514.00000 27.00049 29.89419 0.69507 15.41248



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.22234 10.91601 -0.1732 7.79526
February 454.00000 26.92780 11.30641 0.36738 8.24790
March 514.00000 27.00000 12.13051 0.45147 9.47341
April 485.00000 27.00000 15.36385 0.60858 13.21569
May 508.00000 27.00008 22.34868 0.01733 5.25944
June 496.00000 27.00037 28.42308 0.17492 5.76243
July 497.00000 27.00050 29.90309 0.20603 5.98778
August 514.00000 27.00022 28.40999 0.16714 5.78552
September 485.00000 26.94425 25.45430 -0.1251 5.84438
October 502.00000 26.99999 17.54659 0.48293 10.10566
November 489.00000 27.00000 9.92792 0.36709 7.97861
December 497.00000 27.00000 8.99049 0.35916 7.83966
           
Annual Sum or Average 5943.00000 26.75541 18.45731 0.24074 7.76069
Minimum of Months 454.00000 24.22234 8.99049 -0.1732 5.25944
Maximum of Months 514.00000 27.00050 29.90309 0.60858 13.21569



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00000 39.69749 1.01260 26.67369
February 454.00000 27.00000 39.94177 1.20711 35.61191
March 514.00000 27.00000 39.88549 1.38957 44.96344
April 485.00000 27.00000 39.64953 1.56159 54.25339
May 508.00000 27.00000 40.01577 0.54186 11.18360
June 496.00000 27.00000 39.98237 0.77859 17.78345
July 497.00000 27.00000 39.83069 0.99257 25.81649
August 514.00000 27.00000 40.18193 1.19406 34.96154
September 485.00000 27.00000 40.01378 0.56655 11.76775
October 502.00000 27.00000 39.78337 1.28246 39.37571
November 489.00000 27.00000 39.68241 1.38965 44.96327
December 497.00000 27.00000 39.62162 1.50665 51.26323
           
Annual Sum or Average 5943.00000 27.00000 39.85800 1.11785 33.18590
Minimum of Months 454.00000 27.00000 39.62162 0.54186 11.18360
Maximum of Months 514.00000 27.00000 40.18193 1.56159 54.25339



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.57571 15.46385 0.03563 6.18631
February 454.00000 23.89517 13.98229 0.11358 6.22115
March 514.00000 24.23182 13.79555 0.20131 6.21424
April 485.00000 24.50123 14.40031 0.28961 7.11171
May 508.00000 24.51198 20.88828 -0.5144 11.33186
June 496.00000 24.49357 33.38761 -0.4190 9.50505
July 497.00000 24.64725 42.37024 -0.3007 8.17006
August 514.00000 24.52384 36.55767 -0.3718 8.91231
September 485.00000 24.55981 26.21812 -0.4556 10.44394
October 502.00000 24.53003 18.22966 0.31905 7.62588
November 489.00000 23.96518 11.70947 0.13643 6.68349
December 497.00000 23.47647 11.59361 0.01076 6.52982
           
Annual Sum or Average 5943.00000 24.24531 21.63235 -0.0816 7.92408
Minimum of Months 454.00000 23.47647 11.59361 -0.5144 6.18631
Maximum of Months 514.00000 24.64725 42.37024 0.31905 11.33186



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.93769 20.62477 -0.0857 5.77627
February 454.00000 23.55800 18.05084 0.05938 5.59472
March 514.00000 23.96085 16.53734 0.16946 5.90703
April 485.00000 24.26416 15.50759 0.26652 6.68397
May 508.00000 24.23183 21.84745 -0.5676 12.07010
June 496.00000 24.24523 34.72687 -0.4509 9.65755
July 497.00000 24.26153 43.13580 -0.3772 8.26680
August 514.00000 24.23516 37.94748 -0.4204 9.00763
September 485.00000 24.26814 28.18582 -0.5333 11.62471
October 502.00000 24.16570 21.92085 0.25619 6.75019
November 489.00000 23.78839 16.66101 0.10642 5.56017
December 497.00000 23.50942 15.07553 0.02016 5.52770
           
Annual Sum or Average 5943.00000 23.95461 24.25556 -0.1318 7.71844
Minimum of Months 454.00000 22.93769 15.07553 -0.5676 5.52770
Maximum of Months 514.00000 24.26814 43.13580 0.26652 12.07010



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.05012 18.95511 -0.5765 13.63865
February 454.00000 21.63587 19.86632 -0.4163 9.86321
March 514.00000 22.48942 20.11063 -0.1981 6.69484
April 485.00000 23.52780 18.17139 0.06505 5.72717
May 508.00000 24.02312 22.66048 -0.6617 14.46894
June 496.00000 24.14706 35.18668 -0.5182 10.95234
July 497.00000 24.19592 44.09554 -0.4411 9.45210
August 514.00000 24.12424 38.83383 -0.5072 10.78124
September 485.00000 23.83963 29.94617 -0.7039 16.13147
October 502.00000 22.86295 25.57110 -0.0709 6.09608
November 489.00000 21.51248 19.35318 -0.4558 10.12399
December 497.00000 21.19875 16.07513 -0.5550 12.13615
           
Annual Sum or Average 5943.00000 22.89435 25.80154 -0.4202 10.50504
Minimum of Months 454.00000 21.05012 16.07513 -0.7039 5.72717
Maximum of Months 514.00000 24.19592 44.09554 0.06505 16.13147



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.10848 20.28040 -0.8566 22.86327
February 454.00000 20.30403 22.01564 -0.7794 20.39448
March 514.00000 20.89732 22.22929 -0.6133 14.51962
April 485.00000 22.11040 20.27780 -0.2922 9.20481
May 508.00000 23.58168 23.82589 -0.8255 20.50101
June 496.00000 24.04143 35.30035 -0.5539 11.73413
July 497.00000 24.10552 44.29353 -0.4726 9.99823
August 514.00000 23.88876 39.74290 -0.5992 13.46279
September 485.00000 22.51438 33.54512 -1.1793 35.67986
October 502.00000 20.92589 28.89552 -0.5624 13.53414
November 489.00000 20.18336 21.02591 -0.8261 21.54949
December 497.00000 20.11357 16.99882 -0.8747 23.17697
           
Annual Sum or Average 5943.00000 21.91333 27.42651 -0.7018 17.99479
Minimum of Months 454.00000 20.10848 16.99882 -1.1793 9.20481
Maximum of Months 514.00000 24.10552 44.29353 -0.2922 35.67986



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.46917 18.93450 -0.7453 17.75760
February 454.00000 20.87112 18.72452 -0.6153 14.02696
March 514.00000 21.80025 17.44418 -0.3756 9.12950
April 485.00000 23.36830 15.76800 0.01631 5.99844
May 508.00000 24.09043 21.19232 -0.6360 13.84183
June 496.00000 24.29469 33.58066 -0.4149 8.96191
July 497.00000 24.36192 42.05036 -0.3337 7.81645
August 514.00000 24.15573 37.47007 -0.4739 10.14195
September 485.00000 23.49598 28.88194 -0.8391 21.18346
October 502.00000 22.29200 22.87256 -0.2181 7.42935
November 489.00000 20.85292 17.64436 -0.6250 13.62853
December 497.00000 20.72353 15.29695 -0.6944 15.70200
           
Annual Sum or Average 5943.00000 22.57863 24.21683 -0.4954 12.10342
Minimum of Months 454.00000 20.46917 15.29695 -0.8391 5.99844
Maximum of Months 514.00000 24.36192 42.05036 0.01631 21.18346



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.38618 18.18144 -0.7787 18.98151
February 454.00000 20.85668 17.93914 -0.6199 14.17430
March 514.00000 22.09560 16.37586 -0.2838 8.64398
April 485.00000 23.38669 15.01533 0.06731 6.78129
May 508.00000 24.18423 20.48301 -0.4858 11.58674
June 496.00000 24.22040 33.46887 -0.3597 8.48041
July 497.00000 24.28061 41.92114 -0.2786 7.73791
August 514.00000 24.01388 37.43034 -0.4477 10.06128
September 485.00000 23.53228 28.16366 -0.7774 20.38546
October 502.00000 22.13089 22.29323 -0.2425 7.90418
November 489.00000 20.64742 16.93372 -0.6913 15.52193
December 497.00000 20.52306 14.64888 -0.7702 18.21033
           
Annual Sum or Average 5943.00000 22.53599 23.63498 -0.4710 12.33400
Minimum of Months 454.00000 20.38618 14.64888 -0.7787 6.78129
Maximum of Months 514.00000 24.28061 41.92114 0.06731 20.38546



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.30502 18.26890 -0.8024 20.34896
February 454.00000 21.18928 17.64971 -0.5362 13.39475
March 514.00000 22.33480 15.97863 -0.2121 8.90353
April 485.00000 23.59470 14.55468 0.14823 7.84023
May 508.00000 24.07879 20.65225 -0.5469 13.40603
June 496.00000 24.25892 33.39319 -0.3624 8.74786
July 497.00000 24.32612 41.83531 -0.2732 7.74823
August 514.00000 24.15359 37.00571 -0.3761 9.43171
September 485.00000 23.46772 28.09180 -0.7780 20.96699
October 502.00000 22.13269 22.27107 -0.2394 8.44889
November 489.00000 20.72090 16.91174 -0.6731 15.71860
December 497.00000 20.39583 14.79723 -0.8051 19.62398
           
Annual Sum or Average 5943.00000 22.59259 23.51541 -0.4538 12.85094
Minimum of Months 454.00000 20.30502 14.55468 -0.8051 7.74823
Maximum of Months 514.00000 24.32612 41.83531 0.14823 20.96699



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.75495 17.63290 -0.6420 14.22448
February 454.00000 21.57711 16.97171 -0.4083 9.49645
March 514.00000 23.11316 15.14617 -0.0222 6.31338
April 485.00000 24.43731 13.77246 0.38026 8.95711
May 508.00000 24.33996 20.35095 -0.4534 10.53076
June 496.00000 24.52321 32.83087 -0.2122 7.24308
July 497.00000 24.63061 40.95763 -0.1056 6.67619
August 514.00000 24.52041 36.02998 -0.1842 7.05343
September 485.00000 23.89039 27.29528 -0.6381 15.38709
October 502.00000 23.07301 20.86964 -0.0046 6.39744
November 489.00000 21.82215 15.63028 -0.3550 8.20354
December 497.00000 21.72614 13.49261 -0.3944 8.98476
           
Annual Sum or Average 5943.00000 23.21366 22.64567 -0.2522 9.09949
Minimum of Months 454.00000 20.75495 13.49261 -0.6420 6.31338
Maximum of Months 514.00000 24.63061 40.95763 0.38026 15.38709



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.84052 18.24397 -1.0034 28.30190
February 454.00000 19.98070 19.57624 -0.9245 25.24660
March 514.00000 20.51722 19.82124 -0.7452 17.98816
April 485.00000 21.86318 18.16411 -0.3558 9.91083
May 508.00000 23.77582 21.97067 -0.7626 17.88002
June 496.00000 24.20843 33.79733 -0.4710 9.92073
July 497.00000 24.30273 42.62304 -0.3901 8.62587
August 514.00000 23.88564 38.48080 -0.6067 13.74079
September 485.00000 22.44478 31.27530 -1.2017 36.75175
October 502.00000 20.75662 25.73545 -0.6256 14.85252
November 489.00000 19.89391 18.95863 -0.9659 26.71334
December 497.00000 19.83004 15.08000 -1.0253 28.97736
           
Annual Sum or Average 5943.00000 21.79220 25.37177 -0.7546 19.82515
Minimum of Months 454.00000 19.83004 15.08000 -1.2017 8.62587
Maximum of Months 514.00000 24.30273 42.62304 -0.3558 36.75175



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 19.68628 17.20744 -1.0424 30.03541
February 385.00000 19.93801 18.27478 -0.9243 25.16825
March 433.00000 20.90512 18.13783 -0.6158 14.81043
April 410.00000 22.56996 16.05234 -0.1520 8.51112
May 430.00000 24.05620 20.48133 -0.5511 13.80739
June 418.00000 24.24722 33.19407 -0.3747 9.04538
July 422.00000 24.42603 41.79988 -0.2594 8.16796
August 433.00000 24.00133 37.21730 -0.4871 11.59897
September 410.00000 22.75228 29.36304 -1.0581 32.06629
October 427.00000 20.85992 24.21415 -0.5910 14.09676
November 417.00000 19.72831 17.84941 -1.0065 28.48636
December 422.00000 19.64212 14.09793 -1.0726 31.13067
           
Annual Sum or Average 5034.00000 21.91477 24.04173 -0.6759 18.82940
Minimum of Months 385.00000 19.64212 14.09793 -1.0726 8.16796
Maximum of Months 433.00000 24.42603 41.79988 -0.1520 32.06629



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.94286 17.48640 -0.9617 26.67591
February 454.00000 20.64600 18.19659 -0.7152 18.56190
March 514.00000 21.75509 17.73238 -0.3687 11.87354
April 485.00000 23.22391 15.67136 0.05910 8.81596
May 508.00000 23.94027 20.89958 -0.5880 15.16978
June 496.00000 24.17994 33.48950 -0.3993 9.67445
July 497.00000 24.30783 42.19941 -0.2979 8.57232
August 514.00000 24.06191 37.31193 -0.4260 11.10750
September 485.00000 23.19039 28.94325 -0.8668 25.01465
October 502.00000 21.49513 24.01174 -0.4115 11.41396
November 489.00000 20.11842 17.89442 -0.8850 23.65395
December 497.00000 19.88255 14.36425 -1.0108 28.36792
           
Annual Sum or Average 5943.00000 22.24322 24.08118 -0.5711 16.52350
Minimum of Months 454.00000 19.88255 14.36425 -1.0108 8.57232
Maximum of Months 514.00000 24.30783 42.19941 0.05910 28.36792



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.95823 17.38937 -0.9626 26.54420
February 454.00000 20.16212 18.55975 -0.8549 22.38467
March 514.00000 20.87458 18.60300 -0.6234 14.60832
April 485.00000 22.73162 16.40422 -0.0939 8.14392
May 508.00000 23.88189 21.30901 -0.6561 15.91128
June 496.00000 24.29554 33.46526 -0.3720 9.11536
July 497.00000 24.36802 42.21797 -0.3057 8.08860
August 514.00000 24.02895 37.66012 -0.4859 11.47043
September 485.00000 22.65048 29.96560 -1.0884 32.36874
October 502.00000 20.93770 24.63447 -0.5630 13.03502
November 489.00000 20.07637 17.84078 -0.9004 23.84868
December 497.00000 20.00629 14.16443 -0.9627 26.16832
           
Annual Sum or Average 5943.00000 22.01381 24.41539 -0.6539 17.56291
Minimum of Months 454.00000 19.95823 14.16443 -1.0884 8.08860
Maximum of Months 514.00000 24.36802 42.21797 -0.0939 32.36874



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.60825 18.63488 -1.1343 33.90012
February 454.00000 19.72153 20.56268 -1.0680 31.22891
March 514.00000 20.07283 20.85874 -0.9285 25.22936
April 485.00000 20.75062 19.35025 -0.6554 16.70085
May 508.00000 22.95960 23.08601 -1.0368 29.30819
June 496.00000 24.03939 34.06460 -0.5282 11.37761
July 497.00000 24.10001 43.00687 -0.4573 9.90344
August 514.00000 23.33471 39.67821 -0.7914 20.58931
September 485.00000 21.13691 33.73689 -1.6784 59.85925
October 502.00000 20.00931 27.73753 -0.8755 23.51863
November 489.00000 19.63823 19.52894 -1.1144 33.07065
December 497.00000 19.56137 15.29694 -1.1724 35.46637
           
Annual Sum or Average 5943.00000 21.26171 26.35505 -0.9512 27.41659
Minimum of Months 454.00000 19.56137 15.29694 -1.6784 9.90344
Maximum of Months 514.00000 24.10001 43.00687 -0.4573 59.85925



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.70749 18.40341 -1.1145 32.98475
February 454.00000 19.82461 20.26936 -1.0260 29.49956
March 514.00000 20.35419 20.28147 -0.7994 20.89188
April 485.00000 21.82481 17.90768 -0.3564 12.09125
May 508.00000 23.75543 21.23139 -0.6537 17.08239
June 496.00000 24.13489 33.40795 -0.3917 9.47579
July 497.00000 24.28519 42.01981 -0.2854 8.48744
August 514.00000 23.80568 38.06529 -0.5473 13.60420
September 485.00000 21.87335 32.13143 -1.3925 46.85209
October 502.00000 20.17456 27.19942 -0.8132 21.40716
November 489.00000 19.71935 19.25511 -1.0975 32.30997
December 497.00000 19.66434 15.11522 -1.1553 34.65463
           
Annual Sum or Average 5943.00000 21.61153 25.49585 -0.7998 23.15919
Minimum of Months 454.00000 19.66434 15.11522 -1.3925 8.48744
Maximum of Months 514.00000 24.28519 42.01981 -0.2854 46.85209



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.73373 18.39966 -1.0856 31.86887
February 454.00000 20.05731 19.99202 -0.9194 25.85242
March 514.00000 21.00388 19.53745 -0.6074 17.35136
April 485.00000 22.46629 16.98842 -0.1639 11.31688
May 508.00000 23.51715 21.58995 -0.7487 21.28697
June 496.00000 24.03329 33.68372 -0.4489 11.21165
July 497.00000 24.15565 42.46553 -0.3486 9.81054
August 514.00000 23.79254 38.03398 -0.5275 14.48523
September 485.00000 22.29213 31.22203 -1.2200 40.40318
October 502.00000 20.56023 26.64852 -0.6944 18.51561
November 489.00000 19.78202 19.19797 -1.0460 30.34933
December 497.00000 19.68118 15.13252 -1.1404 34.04118
           
Annual Sum or Average 5943.00000 21.77256 25.29921 -0.7437 22.12487
Minimum of Months 454.00000 19.68118 15.13252 -1.2200 9.81054
Maximum of Months 514.00000 24.15565 42.46553 -0.1639 40.40318



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.74765 18.31515 -1.0879 31.86549
February 454.00000 19.88790 20.13575 -0.9889 27.96734
March 514.00000 20.35788 20.19159 -0.8058 20.81214
April 485.00000 21.87954 17.77633 -0.3283 11.90211
May 508.00000 23.37954 22.07386 -0.8374 22.86562
June 496.00000 24.15414 33.65061 -0.4205 10.41525
July 497.00000 24.21749 42.49284 -0.3572 9.13911
August 514.00000 23.70795 38.47276 -0.6033 15.34574
September 485.00000 21.73467 32.23888 -1.4365 48.68493
October 502.00000 20.26671 26.96102 -0.7803 19.87144
November 489.00000 19.79519 19.13018 -1.0401 29.91524
December 497.00000 19.74202 15.05054 -1.0977 32.17732
           
Annual Sum or Average 5943.00000 21.58910 25.59971 -0.8132 23.31878
Minimum of Months 454.00000 19.74202 15.05054 -1.4365 9.13911
Maximum of Months 514.00000 24.21749 42.49284 -0.3283 48.68493



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.701059E+09 2092.65 19-JAN-07:50 98.78 0.361983E+10 0.00 0.432089E+10 0.69 5.27 06-JAN-17:40 0.00 0.00
February 0.926933E+09 2085.18 15-FEB-12:20 130.23 0.479097E+10 0.00 0.571791E+10 1.00 5.29 21-FEB-00:30 0.00 0.00
March 0.126227E+10 4486.16 29-MAR-13:20 172.67 0.652396E+10 0.00 0.778623E+10 1.20 5.27 15-MAR-14:20 0.00 0.00
April 0.713934E+09 15935.12 20-APR-14:10 83.02 0.368568E+10 0.00 0.439961E+10 0.60 5.27 11-APR-06:40 0.00 0.00
May 0.147210E+11 66057.13 30-MAY-16:00 168.60 0.929235E+11 0.00 0.107645E+12 1.30 7.80 31-MAY-14:00 0.00 0.00
June 0.493156E+11 85296.97 30-JUN-12:20 361.58 0.340495E+12 0.00 0.389811E+12 3.21 7.80 16-JUN-14:40 0.00 0.00
July 0.577354E+11 85624.25 21-JUL-13:10 410.78 0.404872E+12 0.00 0.462607E+12 3.54 7.78 21-JUL-08:50 0.00 0.00
August 0.360497E+11 85984.97 11-AUG-15:10 305.28 0.247732E+12 0.00 0.283781E+12 2.55 7.78 01-AUG-13:00 0.00 0.00
September 0.139384E+10 34507.76 07-SEP-16:00 55.76 0.715483E+10 0.00 0.854867E+10 0.40 6.41 07-SEP-16:00 0.00 0.00
October 0.938198E+09 2822.97 05-OCT-10:00 128.51 0.485099E+10 0.00 0.578919E+10 0.89 5.27 31-OCT-17:00 0.00 0.00
November 0.125284E+10 2481.56 07-NOV-08:00 173.90 0.648034E+10 0.00 0.773318E+10 1.25 5.27 02-NOV-16:30 0.00 0.00
December 0.641419E+09 2906.81 27-DEC-13:00 89.56 0.331259E+10 0.00 0.395401E+10 0.62 5.28 03-DEC-16:20 0.00 0.00
                         
Annual Sum or Average 0.165652E+12     2178.67 0.112644E+13 0.00 0.129209E+13 1.44     0.00 0.00
Minimum of Months 0.641419E+09 2085.18   55.76 0.331259E+10 0.00 0.395401E+10 0.40 5.27   0.00 0.00
Maximum of Months 0.577354E+11 85984.97   410.78 0.404872E+12 0.00 0.462607E+12 3.54 7.80   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 37417841.14 62363.07 31-MAY-15:50 0.17 0.286740E+09 0.00 0.324158E+09 0.00 7.66 31-MAY-15:50 0.00 0.00
June 0.686995E+10 85296.97 30-JUN-12:20 26.83 0.514629E+11 0.00 0.583328E+11 0.28 7.70 20-JUN-12:50 0.00 0.00
July 0.134150E+11 85624.25 21-JUL-13:10 53.98 0.101026E+12 0.00 0.114441E+12 0.55 7.74 06-JUL-13:10 0.00 0.00
August 0.587227E+10 85984.97 11-AUG-15:10 24.17 0.446161E+11 0.00 0.504884E+11 0.25 7.71 25-AUG-13:50 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.261947E+11     105.15 0.197392E+12 0.00 0.223586E+12 0.09     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.134150E+11 85984.97   53.98 0.101026E+12 0.00 0.114441E+12 0.55 7.74   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 47638160.69 667.43 89.92 06-JAN-23:00 4718.65 27-JAN-22:10 18.47 18.34 2.66
February 0.863999E+09 672.00 894.23 10-FEB-16:00 40873.33 16-FEB-16:10 20.85 18.33 2.96
March 0.225519E+10 744.00 1727.73 20-MAR-15:00 95355.99 31-MAR-23:20 24.25 18.33 2.96
April 0.627761E+10 720.00 10881.16 22-APR-14:00 122160.17 22-APR-18:50 28.08 18.33 2.96
May 0.704151E+10 744.00 12476.23 07-MAY-15:02 56012.74 31-MAY-24:00 21.06 18.43 2.96
June 0.206918E+11 720.00 12476.23 02-JUN-11:40 83539.13 30-JUN-23:40 25.09 19.53 2.96
July 0.255278E+11 744.00 12476.23 02-JUL-14:32 113010.13 31-JUL-23:13 28.53 20.32 2.96
August 0.235812E+11 744.00 12476.23 01-AUG-11:00 124120.64 27-AUG-18:42 29.95 19.44 2.96
September 0.241989E+10 720.00 9263.11 07-SEP-16:00 41333.27 30-SEP-24:00 20.39 18.33 2.95
October 0.202732E+10 744.00 3823.28 01-OCT-15:00 58792.60 31-OCT-23:30 21.90 18.33 2.95
November 0.151782E+10 720.00 925.45 03-NOV-22:00 64329.50 08-NOV-15:50 23.37 18.33 2.96
December 0.212257E+10 744.00 1488.79 24-DEC-12:00 87724.81 29-DEC-22:10 25.77 18.33 2.96
                   
Annual Sum or Average 0.943744E+11 8683.42         24.00 18.70 2.93
Minimum of Months 47638160.69 667.43 89.92   4718.65   18.47 18.33 2.66
Maximum of Months 0.255278E+11 744.00 12476.23   124120.64   29.95 20.32 2.96



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:02 186867.85 25-JAN-19:10 20.99 20.97 0.87
February 0.00 0.00 0.00 01-FEB-00:03 186883.96 21-FEB-07:40 20.98 20.96 1.29
March 0.00 0.00 0.00 01-MAR-00:10 186908.89 07-MAR-19:30 20.99 20.97 1.20
April 0.00 0.00 0.00 01-APR-00:10 186943.93 05-APR-10:40 21.01 20.99 0.74
May 45521054.37 67.08 933.73 31-MAY-15:00 859742.56 31-MAY-16:00 21.18 20.96 8.54
June 0.919236E+09 290.59 13832.00 29-JUN-10:50 976583.58 21-JUN-16:00 22.05 21.17 22.63
July 0.166136E+10 334.69 13832.00 03-JUL-14:50 974401.38 21-JUL-14:50 22.18 21.12 24.57
August 0.583128E+09 214.86 13832.00 23-AUG-14:50 973640.16 11-AUG-15:40 21.70 21.08 17.09
September 538830.42 4.00 108.44 07-SEP-16:00 265703.95 07-SEP-16:00 21.03 21.00 1.59
October 0.00 0.00 0.00 01-OCT-00:10 186928.26 26-OCT-17:40 20.98 20.96 0.82
November 0.00 0.00 0.00 01-NOV-00:10 186920.57 18-NOV-12:10 20.97 20.94 1.49
December 0.00 0.00 0.00 01-DEC-00:10 186905.80 26-DEC-13:40 20.97 20.95 0.76
                   
Annual Sum or Average 0.320979E+10 911.21         21.25 21.01 6.85
Minimum of Months 0.00 0.00 0.00   186867.85   20.97 20.94 0.74
Maximum of Months 0.166136E+10 334.69 13832.00   976583.58   22.18 21.17 24.57



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:02 0.00 01-JAN-00:02 20.99 20.99 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 20.98 20.98 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 20.99 20.99 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 21.01 21.01 0.00
May 273244.56 0.17 455.41 31-MAY-15:50 825965.95 31-MAY-15:50 21.18 21.18 0.01
June 0.367502E+09 18.17 13832.00 29-JUN-10:50 976583.58 21-JUN-16:00 22.05 21.95 1.20
July 0.277649E+09 29.03 13832.00 03-JUL-15:00 974401.38 21-JUL-14:50 22.18 22.01 1.86
August 0.130255E+09 13.33 13832.00 23-AUG-14:50 973640.16 11-AUG-15:40 21.70 21.62 0.86
September 0.00 0.00 0.00 01-SEP-00:10 0.00 01-SEP-00:10 21.03 21.03 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 20.98 20.98 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 20.97 20.97 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 20.97 20.97 0.00
                   
Annual Sum or Average 0.775679E+09 60.70         21.25 21.22 0.33
Minimum of Months 0.00 0.00 0.00   0.00   20.97 20.97 0.00
Maximum of Months 0.367502E+09 29.03 13832.00   976583.58   22.18 22.01 1.86



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.841876E+12 0.00 610.46 2180992.49 18-JAN-05:01 0.00 34.50 72.96 1.79 0.00 0.08 0.57 18-JAN-05:01
February 0.490258E+12 0.00 532.35 2096358.65 27-FEB-07:10 0.00 34.53 72.09 1.12 0.00 0.05 0.55 27-FEB-07:10
March 0.225897E+12 0.00 537.51 1745918.47 02-MAR-06:01 0.00 32.40 68.15 0.45 0.00 0.02 0.46 02-MAR-06:01
April 0.360766E+11 0.00 300.74 1343009.51 05-APR-05:01 0.00 30.02 50.96 0.07 0.00 0.00 0.35 05-APR-05:01
May 0.815197E+09 0.00 36.01 193573.76 27-MAY-06:10 0.00 27.92 30.48 0.00 0.00 0.00 0.05 27-MAY-06:10
June 3800113.27 0.00 0.83 6069.67 02-JUN-06:10 0.00 25.46 25.52 0.00 0.00 0.00 0.00 02-JUN-06:10
July 35481.13 0.00 0.50 29.17 05-JUL-07:00 0.00 25.45 25.49 0.00 0.00 0.00 0.00 05-JUL-07:00
August 0.714733E+09 0.00 19.08 261480.21 31-AUG-06:10 0.00 25.42 26.83 0.00 0.00 0.00 0.07 31-AUG-06:10
September 0.141922E+11 0.00 221.42 679198.10 28-SEP-05:03 0.00 29.36 44.84 0.03 0.00 0.00 0.18 28-SEP-05:03
October 0.135379E+12 0.00 460.86 1639136.04 30-OCT-05:01 0.00 30.70 61.19 0.26 0.00 0.01 0.43 30-OCT-05:01
November 0.661783E+12 0.00 581.72 1843969.32 18-NOV-06:02 0.00 34.69 72.60 1.42 0.00 0.07 0.48 18-NOV-06:02
December 0.948884E+12 0.00 618.73 1891166.72 26-DEC-05:11 0.00 36.05 73.89 2.00 0.00 0.09 0.49 26-DEC-05:11
                           
Annual Sum or Average 0.335588E+13 0.00 3920.22     0.00 30.52 51.96 0.59 0.00 0.03    
Minimum of Months 35481.13 0.00 0.50 29.17   0.00 25.42 25.49 0.00 0.00 0.00 0.00  
Maximum of Months 0.948884E+12 0.00 618.73 2180992.49   0.00 36.05 73.89 2.00 0.00 0.09 0.57  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 18.47 18.47 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 20.85 20.85 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 24.25 24.25 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 28.08 28.08 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 21.06 21.06 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 25.09 25.09 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 28.53 28.53 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 29.95 29.95 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 20.39 20.39 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 21.90 21.90 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 23.37 23.37 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 25.77 25.77 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 24.00 24.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 18.47 18.47 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 29.95 29.95 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 4198159.85 0.00 51.93 4198159.85 0.00 0.00 0.00 0.00 380.49 25-JAN-11:10 380.49 25-JAN-11:10 0.00 0.00 0.00
February 15114321.99 0.00 85.83 15114321.99 0.00 0.00 0.00 0.00 1982.55 09-FEB-08:20 1982.55 09-FEB-08:20 0.00 0.00 0.00
March 40584701.93 0.00 98.57 40584701.93 0.00 0.00 0.00 0.00 5323.52 24-MAR-07:10 5323.52 24-MAR-07:10 0.00 0.00 0.00
April 73221186.88 0.00 40.50 73221186.88 0.00 0.00 0.00 0.00 8505.50 20-APR-14:00 8505.50 20-APR-14:00 0.00 0.00 0.00
May 0.843258E+10 0.00 155.32 0.843258E+10 0.00 0.00 0.00 0.00 69603.21 31-MAY-16:00 69603.21 31-MAY-16:00 0.00 0.00 0.00
June 0.389659E+11 0.00 352.92 0.388389E+11 0.00 0.00 0.00 0.00 106565.15 30-JUN-12:20 100356.55 20-JUN-15:30 0.00 0.00 0.00
July 0.526532E+11 0.00 391.36 0.524836E+11 0.00 0.00 0.00 0.00 113359.44 03-JUL-15:00 106685.45 11-JUL-15:30 0.00 0.00 0.00
August 0.300603E+11 0.00 296.16 0.300603E+11 0.00 0.00 0.00 0.00 107175.13 11-AUG-15:20 107175.13 11-AUG-15:20 0.00 0.00 0.00
September 0.499455E+09 0.00 41.54 0.499455E+09 0.00 0.00 0.00 0.00 20738.13 07-SEP-16:00 20738.13 07-SEP-16:00 0.00 0.00 0.00
October 30516028.97 0.00 90.46 30516028.97 0.00 0.00 0.00 0.00 4023.77 12-OCT-07:20 4023.77 12-OCT-07:20 0.00 0.00 0.00
November 29350106.65 0.00 126.40 29350106.65 0.00 0.00 0.00 0.00 2741.75 06-NOV-08:20 2741.75 06-NOV-08:20 0.00 0.00 0.00
December 5485206.33 0.00 44.53 5485206.33 0.00 0.00 0.00 0.00 743.72 27-DEC-08:50 743.72 27-DEC-08:50 0.00 0.00 0.00
                               
Annual Sum or Average 0.130810E+12 0.00 1775.52 0.130513E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 4198159.85 0.00 40.50 4198159.85 0.00 0.00 0.00 0.00 380.49   380.49   0.00 0.00 0.00
Maximum of Months 0.526532E+11 0.00 391.36 0.524836E+11 0.00 0.00 0.00 0.00 113359.44   107175.13   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 15396889.47 0.00 39.64 15396889.47 0.00 0.00 0.00 0.00 788.10 21-JAN-12:10 788.10 21-JAN-12:10 0.00 0.00 0.00
February 37337995.78 0.00 63.01 37337995.78 0.00 0.00 0.00 0.00 2103.31 15-FEB-12:20 2103.31 15-FEB-12:20 0.00 0.00 0.00
March 0.182132E+09 0.00 90.06 0.182132E+09 0.00 0.00 0.00 0.00 18474.58 29-MAR-13:20 18474.58 29-MAR-13:20 0.00 0.00 0.00
April 0.517552E+09 0.00 43.07 0.517552E+09 0.00 0.00 0.00 0.00 66251.76 20-APR-14:00 66251.76 20-APR-14:00 0.00 0.00 0.00
May 0.750780E+11 0.00 153.89 0.750780E+11 0.00 0.00 0.00 0.00 639156.97 31-MAY-16:00 639156.97 31-MAY-16:00 0.00 0.00 0.00
June 0.331807E+12 0.00 328.59 0.330785E+12 0.00 0.00 0.00 0.00 970716.34 30-JUN-12:30 907640.23 20-JUN-15:30 0.00 0.00 0.00
July 0.429244E+12 0.00 346.73 0.428123E+12 0.00 0.00 0.00 0.00 989537.09 23-JUL-15:11 989537.09 23-JUL-15:11 0.00 0.00 0.00
August 0.231058E+12 0.00 253.22 0.231058E+12 0.00 0.00 0.00 0.00 924143.19 11-AUG-15:40 924143.19 11-AUG-15:40 0.00 0.00 0.00
September 0.426428E+10 0.00 38.04 0.426428E+10 0.00 0.00 0.00 0.00 176677.56 07-SEP-16:00 176677.56 07-SEP-16:00 0.00 0.00 0.00
October 57149762.41 0.00 72.43 57149762.41 0.00 0.00 0.00 0.00 2902.56 05-OCT-10:00 2902.56 05-OCT-10:00 0.00 0.00 0.00
November 30054792.72 0.00 46.57 30054792.72 0.00 0.00 0.00 0.00 1287.63 02-NOV-17:40 1287.63 02-NOV-17:40 0.00 0.00 0.00
December 5115440.41 0.00 36.33 5115440.41 0.00 0.00 0.00 0.00 657.05 23-DEC-12:10 657.05 23-DEC-12:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.107230E+13 0.00 1511.58 0.107015E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 5115440.41 0.00 36.33 5115440.41 0.00 0.00 0.00 0.00 657.05   657.05   0.00 0.00 0.00
Maximum of Months 0.429244E+12 0.00 346.73 0.428123E+12 0.00 0.00 0.00 0.00 989537.09   989537.09   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 425207.57 0.00 2.60 425207.57 0.00 0.00 0.00 0.00 623.75 02-JAN-06:07 623.75 02-JAN-06:07 0.00 0.00 0.00
February 3476096.06 0.00 19.06 3476096.06 0.00 0.00 0.00 0.00 1306.01 06-FEB-06:01 1306.01 06-FEB-06:01 0.00 0.00 0.00
March 13933196.64 0.00 43.47 13933196.64 0.00 0.00 0.00 0.00 426.96 27-MAR-11:50 426.96 27-MAR-11:50 0.00 0.00 0.00
April 39322996.83 0.00 45.89 39322996.83 0.00 0.00 0.00 0.00 3495.34 22-APR-14:00 3495.34 22-APR-14:00 0.00 0.00 0.00
May 0.719992E+10 0.00 146.44 0.719992E+10 0.00 0.00 0.00 0.00 70434.78 31-MAY-16:00 70434.78 31-MAY-16:00 0.00 0.00 0.00
June 0.347188E+11 0.00 325.19 0.345972E+11 0.00 0.00 0.00 0.00 113085.75 30-JUN-12:30 106856.31 29-JUN-14:40 0.00 0.00 0.00
July 0.447259E+11 0.00 343.01 0.446237E+11 0.00 0.00 0.00 0.00 111174.71 21-JUL-14:40 111174.71 21-JUL-14:40 0.00 0.00 0.00
August 0.232185E+11 0.00 245.99 0.232185E+11 0.00 0.00 0.00 0.00 102607.66 11-AUG-15:40 102607.66 11-AUG-15:40 0.00 0.00 0.00
September 0.304765E+09 0.00 34.61 0.304765E+09 0.00 0.00 0.00 0.00 13052.05 07-SEP-16:00 13052.05 07-SEP-16:00 0.00 0.00 0.00
October 7962375.04 0.00 26.64 7962375.04 0.00 0.00 0.00 0.00 560.83 03-OCT-10:50 560.83 03-OCT-10:50 0.00 0.00 0.00
November 103733.72 0.00 1.08 103733.72 0.00 0.00 0.00 0.00 47.22 01-NOV-16:20 47.22 01-NOV-16:20 0.00 0.00 0.00
December 656271.04 0.00 8.55 656271.04 0.00 0.00 0.00 0.00 216.35 19-DEC-05:37 216.35 19-DEC-05:37 0.00 0.00 0.00
                               
Annual Sum or Average 0.110234E+12 0.00 1242.53 0.110010E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 103733.72 0.00 1.08 103733.72 0.00 0.00 0.00 0.00 47.22   47.22   0.00 0.00 0.00
Maximum of Months 0.447259E+11 0.00 343.01 0.446237E+11 0.00 0.00 0.00 0.00 113085.75   111174.71   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 11359025.64 0.00 88.53 11359025.64 0.00 0.00 0.00 0.00 1066.57 26-JAN-10:00 1066.57 26-JAN-10:00 0.00 0.00 0.00
February 23090215.37 0.00 121.64 23090215.37 0.00 0.00 0.00 0.00 2073.75 10-FEB-17:10 2073.75 10-FEB-17:10 0.00 0.00 0.00
March 38291662.31 0.00 161.93 38291662.31 0.00 0.00 0.00 0.00 4540.09 23-MAR-16:10 4540.09 23-MAR-16:10 0.00 0.00 0.00
April 17735853.64 0.00 52.92 17735853.64 0.00 0.00 0.00 0.00 3251.59 03-APR-16:10 3251.59 03-APR-16:10 0.00 0.00 0.00
May 0.274365E+10 0.00 69.74 0.274365E+10 0.00 0.00 0.00 0.00 36994.63 31-MAY-16:00 36994.63 31-MAY-16:00 0.00 0.00 0.00
June 0.172795E+11 0.00 232.41 0.172602E+11 0.00 0.00 0.00 0.00 49979.18 13-JUN-13:20 49979.18 13-JUN-13:20 0.00 0.00 0.00
July 0.262407E+11 0.00 253.23 0.261277E+11 0.00 0.00 0.00 0.00 63897.43 03-JUL-15:00 56041.35 31-JUL-15:00 0.00 0.00 0.00
August 0.141080E+11 0.00 186.48 0.140831E+11 0.00 0.00 0.00 0.00 50489.07 11-AUG-16:00 50489.07 11-AUG-16:00 0.00 0.00 0.00
September 46509867.81 0.00 18.51 46509867.81 0.00 0.00 0.00 0.00 7289.20 07-SEP-16:00 7289.20 07-SEP-16:00 0.00 0.00 0.00
October 38196331.69 0.00 110.89 38196331.69 0.00 0.00 0.00 0.00 4463.19 19-OCT-16:10 4463.19 19-OCT-16:10 0.00 0.00 0.00
November 41158273.76 0.00 170.33 41158273.76 0.00 0.00 0.00 0.00 5269.97 07-NOV-08:00 5269.97 07-NOV-08:00 0.00 0.00 0.00
December 17896533.94 0.00 65.56 17896533.94 0.00 0.00 0.00 0.00 9511.82 27-DEC-13:00 9511.82 27-DEC-13:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.606060E+11 0.00 1532.17 0.604488E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 11359025.64 0.00 18.51 11359025.64 0.00 0.00 0.00 0.00 1066.57   1066.57   0.00 0.00 0.00
Maximum of Months 0.262407E+11 0.00 253.23 0.261277E+11 0.00 0.00 0.00 0.00 63897.43   56041.35   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.136356E+10 0.390796E+09 667.43 0.136356E+10 0.00 0.00 0.18 31-JAN-05:14 0.00 02-JAN-07:03 1222.90 31-JAN-05:14 1222.90 31-JAN-05:14 0.00 01-JAN-09:52 331.49 31-JAN-05:14 0.00
February 0.677844E+10 0.167686E+10 672.00 0.677844E+10 -0.0 0.00 0.45 20-FEB-16:03 0.20 27-FEB-07:02 3542.34 12-FEB-15:50 3542.34 12-FEB-15:50 0.00 09-FEB-14:10 841.49 20-FEB-16:03 0.00
March 0.137858E+11 0.319600E+10 744.00 0.137858E+11 0.00 0.00 0.89 31-MAR-24:00 0.47 01-MAR-07:02 7340.88 31-MAR-24:00 7340.88 31-MAR-24:00 0.00 06-MAR-15:30 1649.92 31-MAR-24:00 0.00
April 0.196094E+11 0.425614E+10 720.00 0.196094E+11 -0.0 0.00 1.00 01-APR-18:05 0.31 30-APR-24:00 8776.48 22-APR-18:40 8776.48 22-APR-18:40 0.00 10-APR-07:07 1860.28 08-APR-18:53 0.00
May 0.544636E+10 0.131056E+10 744.00 0.544619E+10 173580.88 0.00 0.47 31-MAY-24:00 0.17 27-MAY-07:00 3996.14 31-MAY-24:00 3996.14 31-MAY-24:00 18.73 16-MAY-16:10 887.76 31-MAY-24:00 0.00
June 0.105824E+11 0.241732E+10 720.00 0.105065E+11 75917076.68 0.00 0.66 30-JUN-24:00 0.43 01-JUN-06:10 5904.53 30-JUN-24:00 5895.38 30-JUN-24:00 246.30 27-JUN-16:00 1324.19 30-JUN-15:00 0.00
July 0.160921E+11 0.359473E+10 744.00 0.159355E+11 0.156631E+09 0.00 0.85 31-JUL-23:05 0.63 01-JUL-06:10 7815.25 31-JUL-23:05 7789.01 31-JUL-23:45 323.57 26-JUL-15:00 1898.34 29-JUL-17:00 0.00
August 0.208821E+11 0.439914E+10 744.00 0.207522E+11 0.129913E+09 0.00 0.95 27-AUG-18:32 0.32 31-AUG-24:00 8748.65 27-AUG-18:34 8748.65 27-AUG-18:34 261.77 03-AUG-14:00 2169.13 11-AUG-18:10 0.00
September 0.476566E+10 0.113426E+10 720.00 0.474931E+10 16357103.33 0.00 0.44 30-SEP-24:00 0.13 30-SEP-07:00 3498.46 30-SEP-24:00 3498.46 30-SEP-24:00 97.68 05-SEP-15:40 827.92 30-SEP-24:00 0.00
October 0.904364E+10 0.212575E+10 744.00 0.904334E+10 299112.01 0.00 0.64 31-OCT-24:00 0.32 31-OCT-07:00 5068.16 31-OCT-24:00 5068.16 31-OCT-24:00 43.13 02-OCT-16:00 1183.20 31-OCT-24:00 0.00
November 0.123807E+11 0.293168E+10 720.00 0.123807E+11 0.00 0.00 0.68 19-NOV-15:25 0.49 30-NOV-07:02 5418.73 19-NOV-15:30 5418.73 19-NOV-15:30 0.00 26-NOV-08:62 1265.49 19-NOV-15:25 0.00
December 0.175148E+11 0.401611E+10 744.00 0.175148E+11 -0.0 0.00 0.86 24-DEC-13:00 0.71 15-DEC-07:02 7324.39 24-DEC-17:55 7324.39 24-DEC-17:55 0.00 17-DEC-19:56 1608.96 24-DEC-13:05 0.00
                                       
Annual Sum or Average 0.138245E+12 0.314493E+11 8683.42 0.137866E+12 0.379291E+09 0.00                         0.00
Minimum of Months 0.136356E+10 0.390796E+09 667.43 0.136356E+10 -0.0 0.00 0.18   0.00   1222.90   1222.90   0.00   331.49   0.00
Maximum of Months 0.208821E+11 0.439914E+10 744.00 0.207522E+11 0.156631E+09 0.00 1.00   0.71   8776.48   8776.48   323.57   2169.13   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.117589E+09 56336011.91 40.94 0.117589E+09 0.00 0.00 0.05 27-JAN-22:10 0.00 01-JAN-00:02 2532.93 27-JAN-22:10 2532.93 27-JAN-22:10 0.00 07-JAN-02:50 828.49 27-JAN-22:10 0.00
February 0.397329E+11 0.102073E+11 672.00 0.397329E+11 -0.0 0.00 0.37 16-FEB-16:10 0.02 27-FEB-07:02 26712.30 16-FEB-16:10 26712.30 16-FEB-16:10 0.00 10-FEB-17:30 6535.27 16-FEB-16:10 0.00
March 0.107566E+12 0.255093E+11 744.00 0.107566E+12 -0.0 0.00 0.82 31-MAR-23:20 0.36 01-MAR-07:02 63789.57 31-MAR-23:20 63789.57 31-MAR-23:20 0.00 20-MAR-08:65 14537.97 31-MAR-23:20 0.00
April 0.175332E+12 0.384056E+11 720.00 0.175332E+12 -0.0 0.00 0.98 22-APR-18:50 0.25 30-APR-24:00 82240.03 22-APR-18:50 82240.03 22-APR-18:50 0.00 10-APR-04:04 17460.30 22-APR-18:50 0.00
May 0.471505E+11 0.114418E+11 744.00 0.471485E+11 1983823.67 0.00 0.46 31-MAY-24:00 0.12 27-MAY-07:00 37364.83 31-MAY-24:00 37364.83 31-MAY-24:00 208.65 16-MAY-16:10 8322.44 31-MAY-24:00 0.00
June 0.987670E+11 0.226329E+11 720.00 0.980127E+11 0.754206E+09 0.00 0.66 30-JUN-24:00 0.40 24-JUN-17:00 56491.46 30-JUN-23:20 56372.76 30-JUN-24:00 2453.91 27-JUN-16:00 12640.20 30-JUN-15:00 0.00
July 0.151954E+12 0.340135E+11 744.00 0.150396E+12 0.155805E+10 0.00 0.85 31-JUL-23:05 0.61 06-JUL-06:10 75671.92 31-JUL-23:53 75399.55 31-JUL-23:53 3212.25 26-JUL-15:00 17969.65 21-JUL-16:00 0.00
August 0.196844E+12 0.415753E+11 744.00 0.195548E+12 0.129630E+10 0.00 0.93 10-AUG-18:50 0.25 31-AUG-24:00 81748.88 27-AUG-18:43 81748.88 27-AUG-18:43 2610.16 03-AUG-14:00 20728.27 11-AUG-18:00 0.00
September 0.352204E+11 0.855622E+10 720.00 0.350643E+11 0.156128E+09 0.00 0.37 30-SEP-24:00 0.05 30-SEP-07:00 27557.19 30-SEP-24:00 27557.19 30-SEP-24:00 958.55 05-SEP-15:50 6643.27 30-SEP-24:00 0.00
October 0.638031E+11 0.153934E+11 744.00 0.637997E+11 3357481.95 0.00 0.52 31-OCT-23:30 0.14 30-OCT-06:05 38555.25 31-OCT-23:30 38555.25 31-OCT-23:30 428.89 02-OCT-16:00 9232.31 31-OCT-23:30 0.00
November 0.874471E+11 0.213852E+11 720.00 0.874471E+11 -0.0 0.00 0.56 08-NOV-15:50 0.31 27-NOV-07:03 42286.62 08-NOV-15:50 42286.62 08-NOV-15:50 0.00 01-NOV-17:40 10057.80 08-NOV-15:50 0.00
December 0.135059E+12 0.318481E+11 744.00 0.135059E+12 0.00 0.00 0.75 22-DEC-22:02 0.57 04-DEC-07:03 57995.14 29-DEC-22:08 57995.14 29-DEC-22:08 0.00 04-DEC-17:50 13410.27 22-DEC-22:02 0.00
                                       
Annual Sum or Average 0.113899E+13 0.261025E+12 8056.94 0.113522E+13 0.377003E+10 0.00                         0.00
Minimum of Months 0.117589E+09 56336011.91 40.94 0.117589E+09 -0.0 0.00 0.05   0.00   2532.93   2532.93   0.00   828.49   0.00
Maximum of Months 0.196844E+12 0.415753E+11 744.00 0.195548E+12 0.155805E+10 0.00 0.98   0.61   82240.03   82240.03   3212.25   20728.27   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00
February 0.213543E+10 0.565182E+09 554.43 0.213543E+10 -0.0 0.00 0.30 09-FEB-16:00 0.00 01-FEB-00:03 2330.03 09-FEB-16:00 2330.03 09-FEB-16:00 0.00 07-FEB-13:30 552.31 09-FEB-16:00 0.00
March 0.853085E+10 0.206659E+10 744.00 0.853085E+10 -0.0 0.00 0.69 31-MAR-23:10 0.22 06-MAR-04:11 5347.24 31-MAR-23:10 5347.24 31-MAR-23:10 0.00 25-MAR-07:30 1247.91 31-MAR-23:10 0.00
April 0.158419E+11 0.351410E+10 720.00 0.158419E+11 -0.0 0.00 0.95 22-APR-18:35 0.17 30-APR-24:00 8081.93 22-APR-18:40 8081.93 22-APR-18:40 0.00 13-APR-03:00 1722.76 22-APR-18:35 0.00
May 0.401918E+10 0.987146E+09 743.92 0.401900E+10 177738.78 0.00 0.45 31-MAY-24:00 0.00 28-MAY-09:35 3690.90 31-MAY-24:00 3690.90 31-MAY-24:00 19.86 16-MAY-16:10 823.85 31-MAY-24:00 0.00
June 0.971143E+10 0.223307E+10 720.00 0.963613E+10 75306410.23 0.00 0.65 30-JUN-23:30 0.36 26-JUN-06:30 5633.29 30-JUN-23:20 5612.51 30-JUN-23:50 245.58 27-JUN-16:00 1282.61 30-JUN-15:00 0.00
July 0.150440E+11 0.337839E+10 744.00 0.148883E+11 0.155644E+09 0.00 0.84 31-JUL-23:05 0.57 06-JUL-06:10 7546.63 31-JUL-23:05 7515.80 31-JUL-23:37 320.94 26-JUL-15:00 1821.06 29-JUL-17:00 0.00
August 0.192946E+11 0.409352E+10 744.00 0.191652E+11 0.129419E+09 0.00 0.93 10-AUG-18:50 0.19 31-AUG-24:00 8201.96 27-AUG-18:47 8201.96 27-AUG-18:45 261.01 03-AUG-14:00 2085.95 11-AUG-18:10 0.00
September 0.196165E+10 0.492884E+09 630.94 0.194777E+10 13870601.18 0.00 0.28 02-SEP-17:55 0.00 05-SEP-02:45 2209.62 02-SEP-17:55 2209.62 02-SEP-17:55 91.96 05-SEP-16:00 509.40 02-SEP-17:55 0.00
October 0.392240E+10 0.977249E+09 722.99 0.392212E+10 286088.12 0.00 0.42 31-OCT-23:10 0.00 22-OCT-00:55 3183.32 03-OCT-16:00 3183.32 03-OCT-16:00 37.94 02-OCT-16:00 757.68 31-OCT-23:10 0.00
November 0.656189E+10 0.164593E+10 720.00 0.656189E+10 -0.0 0.00 0.50 08-NOV-15:50 0.17 27-NOV-03:40 3733.85 08-NOV-15:50 3733.85 08-NOV-15:50 0.00 07-NOV-07:03 900.57 08-NOV-15:50 0.00
December 0.113970E+11 0.274116E+10 744.00 0.113970E+11 -0.0 0.00 0.69 20-DEC-22:03 0.43 26-DEC-04:01 5418.05 19-DEC-22:10 5418.05 19-DEC-22:10 0.00 14-DEC-01:50 1242.62 19-DEC-22:03 0.00
                                       
Annual Sum or Average 0.984204E+11 0.226952E+11 7788.28 0.980457E+11 0.374704E+09 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 -0.0 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.192946E+11 0.409352E+10 744.00 0.191652E+11 0.155644E+09 0.00 0.95   0.57   8201.96   8201.96   320.94   2085.95   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.69 0.00 10.69 0.00 848.07 0.00 0.00 0.00
February 47.25 0.00 47.25 0.00 772.04 0.00 0.00 0.00
March 126.38 0.00 126.38 6.79 587.98 0.00 0.00 0.00
April 228.36 4.74 223.62 80.65 324.80 0.00 0.00 0.00
May 349.39 54.66 294.73 266.21 135.84 0.00 0.00 0.00
June 456.52 100.97 355.55 453.72 62.24 0.00 0.00 0.00
July 383.03 61.66 321.37 388.39 75.40 0.00 0.00 0.00
August 244.57 13.22 231.35 197.27 128.74 0.00 0.00 0.00
September 136.69 0.12 136.57 45.18 274.71 0.00 0.00 0.00
October 66.52 0.00 66.52 2.42 515.32 0.00 0.00 0.00
November 20.64 0.00 20.64 0.00 847.95 0.00 0.00 0.00
December 3.24 0.00 3.24 0.00 902.70 0.00 0.00 0.00
                 
Annual Sum or Average 173.39 19.70 153.69 120.77 454.59 0.00 0.00 0.00
Minimum of Months 3.24 0.00 3.24 0.00 62.24 0.00 0.00 0.00
Maximum of Months 456.52 100.97 355.55 453.72 902.70 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.69 0.00 10.69 0.00 848.07 0.00 0.00 0.00
February 47.25 0.00 47.25 0.00 772.04 0.00 0.00 0.00
March 126.38 0.00 126.38 6.79 587.98 0.00 0.00 0.00
April 228.36 4.74 223.61 80.65 324.80 0.00 0.00 0.00
May 349.39 54.66 294.73 266.20 135.84 0.00 0.00 0.00
June 456.52 100.97 355.54 453.71 62.24 0.00 0.00 0.00
July 383.03 61.66 321.37 388.39 75.40 0.00 0.00 0.00
August 244.56 13.22 231.34 197.26 128.74 0.00 0.00 0.00
September 136.69 0.12 136.57 45.18 274.71 0.00 0.00 0.00
October 66.52 0.00 66.52 2.42 515.32 0.00 0.00 0.00
November 20.64 0.00 20.64 0.00 847.95 0.00 0.00 0.00
December 3.24 0.00 3.24 0.00 902.70 0.00 0.00 0.00
                 
Annual Sum or Average 173.39 19.70 153.69 120.76 454.59 0.00 0.00 0.00
Minimum of Months 3.24 0.00 3.24 0.00 62.24 0.00 0.00 0.00
Maximum of Months 456.52 100.97 355.54 453.71 902.70 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.69 0.00 10.69 0.00 848.07 0.00 0.00 0.00
February 47.25 0.00 47.25 0.00 772.04 0.00 0.00 0.00
March 126.38 0.00 126.38 6.79 587.98 0.00 0.00 0.00
April 228.36 4.74 223.62 80.65 324.80 0.00 0.00 0.00
May 349.39 54.66 294.73 266.20 135.84 0.00 0.00 0.00
June 456.52 100.97 355.55 453.72 62.24 0.00 0.00 0.00
July 383.03 61.66 321.37 388.39 75.40 0.00 0.00 0.00
August 244.56 13.22 231.34 197.26 128.74 0.00 0.00 0.00
September 136.69 0.12 136.57 45.18 274.71 0.00 0.00 0.00
October 66.52 0.00 66.52 2.42 515.32 0.00 0.00 0.00
November 20.64 0.00 20.64 0.00 847.95 0.00 0.00 0.00
December 3.24 0.00 3.24 0.00 902.70 0.00 0.00 0.00
                 
Annual Sum or Average 173.39 19.70 153.69 120.77 454.59 0.00 0.00 0.00
Minimum of Months 3.24 0.00 3.24 0.00 62.24 0.00 0.00 0.00
Maximum of Months 456.52 100.97 355.55 453.72 902.70 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.69 0.00 10.69 0.00 848.07 0.00 0.00 0.00
February 47.25 0.00 47.25 0.00 772.04 0.00 0.00 0.00
March 126.38 0.00 126.38 6.79 587.98 0.00 0.00 0.00
April 228.36 4.74 223.61 80.65 324.80 0.00 0.00 0.00
May 349.39 54.66 294.73 266.20 135.84 0.00 0.00 0.00
June 456.52 100.97 355.54 453.71 62.24 0.00 0.00 0.00
July 383.03 61.66 321.37 388.39 75.40 0.00 0.00 0.00
August 244.56 13.22 231.34 197.26 128.74 0.00 0.00 0.00
September 136.69 0.12 136.57 45.18 274.71 0.00 0.00 0.00
October 66.52 0.00 66.52 2.42 515.32 0.00 0.00 0.00
November 20.64 0.00 20.64 0.00 847.95 0.00 0.00 0.00
December 3.24 0.00 3.24 0.00 902.70 0.00 0.00 0.00
                 
Annual Sum or Average 173.39 19.70 153.69 120.76 454.59 0.00 0.00 0.00
Minimum of Months 3.24 0.00 3.24 0.00 62.24 0.00 0.00 0.00
Maximum of Months 456.52 100.97 355.54 453.71 902.70 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.69 0.00 10.69 0.00 848.03 0.00 0.00 0.00
February 47.25 0.00 47.25 0.00 772.01 0.00 0.00 0.00
March 126.37 0.00 126.37 6.79 587.96 0.00 0.00 0.00
April 228.35 4.74 223.61 80.64 324.79 0.00 0.00 0.00
May 349.37 54.66 294.71 266.19 135.83 0.00 0.00 0.00
June 456.50 100.97 355.53 453.70 62.24 0.00 0.00 0.00
July 383.01 61.65 321.36 388.37 75.40 0.00 0.00 0.00
August 244.55 13.22 231.33 197.25 128.73 0.00 0.00 0.00
September 136.68 0.12 136.56 45.18 274.70 0.00 0.00 0.00
October 66.52 0.00 66.52 2.42 515.30 0.00 0.00 0.00
November 20.64 0.00 20.64 0.00 847.91 0.00 0.00 0.00
December 3.24 0.00 3.24 0.00 902.67 0.00 0.00 0.00
                 
Annual Sum or Average 173.38 19.70 153.68 120.76 454.57 0.00 0.00 0.00
Minimum of Months 3.24 0.00 3.24 0.00 62.24 0.00 0.00 0.00
Maximum of Months 456.50 100.97 355.53 453.70 902.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 31.01 9.57 21.44 2.57 910.19 0.00 0.00 0.00
February 172.47 82.09 90.38 88.17 770.99 0.00 0.00 0.00
March 493.67 250.30 243.38 413.92 577.45 0.00 0.00 0.00
April 678.89 344.01 334.88 627.40 321.15 0.00 0.00 0.00
May 987.57 557.25 430.31 1099.43 161.98 0.00 0.00 0.00
June 907.83 423.99 483.83 1049.70 77.40 0.00 0.00 0.00
July 862.49 418.73 443.76 1023.06 87.03 0.00 0.00 0.00
August 682.95 332.87 350.08 772.51 138.24 0.00 0.00 0.00
September 422.14 185.09 237.05 391.34 279.51 0.00 0.00 0.00
October 222.59 89.26 133.34 154.11 511.64 0.00 0.00 0.00
November 47.01 16.20 30.82 3.30 899.13 0.00 0.00 0.00
December 6.69 1.54 5.15 0.00 985.22 0.00 0.00 0.00
                 
Annual Sum or Average 461.37 226.91 234.46 471.38 475.14 0.00 0.00 0.00
Minimum of Months 6.69 1.54 5.15 0.00 77.40 0.00 0.00 0.00
Maximum of Months 987.57 557.25 483.83 1099.43 985.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 31.01 9.57 21.44 2.57 910.19 0.00 0.00 0.00
February 172.47 82.09 90.38 88.17 770.99 0.00 0.00 0.00
March 493.67 250.30 243.38 413.92 577.45 0.00 0.00 0.00
April 678.89 344.01 334.88 627.40 321.15 0.00 0.00 0.00
May 987.57 557.25 430.31 1099.43 161.98 0.00 0.00 0.00
June 907.83 423.99 483.83 1049.70 77.40 0.00 0.00 0.00
July 862.49 418.73 443.76 1023.06 87.03 0.00 0.00 0.00
August 682.95 332.87 350.08 772.51 138.24 0.00 0.00 0.00
September 422.14 185.09 237.05 391.34 279.51 0.00 0.00 0.00
October 222.59 89.26 133.34 154.11 511.64 0.00 0.00 0.00
November 47.01 16.20 30.82 3.30 899.13 0.00 0.00 0.00
December 6.69 1.54 5.15 0.00 985.22 0.00 0.00 0.00
                 
Annual Sum or Average 461.37 226.91 234.46 471.38 475.14 0.00 0.00 0.00
Minimum of Months 6.69 1.54 5.15 0.00 77.40 0.00 0.00 0.00
Maximum of Months 987.57 557.25 483.83 1099.43 985.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 31.01 9.57 21.44 2.57 910.17 0.00 0.00 0.00
February 172.46 82.09 90.38 88.17 770.98 0.00 0.00 0.00
March 493.66 250.29 243.37 413.92 577.44 0.00 0.00 0.00
April 678.88 344.00 334.88 627.39 321.14 0.00 0.00 0.00
May 987.55 557.24 430.31 1099.41 161.98 0.00 0.00 0.00
June 907.81 423.99 483.83 1049.68 77.40 0.00 0.00 0.00
July 862.47 418.72 443.75 1023.04 87.03 0.00 0.00 0.00
August 682.94 332.86 350.07 772.50 138.24 0.00 0.00 0.00
September 422.13 185.09 237.04 391.33 279.50 0.00 0.00 0.00
October 222.59 89.25 133.33 154.11 511.63 0.00 0.00 0.00
November 47.01 16.20 30.82 3.30 899.11 0.00 0.00 0.00
December 6.69 1.54 5.15 0.00 985.20 0.00 0.00 0.00
                 
Annual Sum or Average 461.36 226.91 234.46 471.38 475.13 0.00 0.00 0.00
Minimum of Months 6.69 1.54 5.15 0.00 77.40 0.00 0.00 0.00
Maximum of Months 987.55 557.24 483.83 1099.41 985.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 129.08 85.33 43.75 75.15 749.30 0.00 0.00 0.00
February 444.01 309.69 134.32 377.71 612.13 0.00 0.00 0.00
March 760.78 516.64 244.14 751.87 477.26 0.00 0.00 0.00
April 926.08 576.74 349.34 1025.46 317.45 0.00 0.00 0.00
May 760.96 393.67 367.29 870.92 169.60 0.00 0.00 0.00
June 693.95 283.24 410.71 817.83 89.48 0.00 0.00 0.00
July 669.19 290.66 378.53 807.72 94.25 0.00 0.00 0.00
August 695.00 383.28 311.72 824.99 140.79 0.00 0.00 0.00
September 562.84 339.61 223.22 602.57 251.03 0.00 0.00 0.00
October 406.09 258.38 147.70 369.57 414.57 0.00 0.00 0.00
November 218.14 152.77 65.37 142.85 711.23 0.00 0.00 0.00
December 38.74 27.39 11.35 6.63 841.25 0.00 0.00 0.00
                 
Annual Sum or Average 525.25 300.98 224.27 556.57 404.69 0.00 0.00 0.00
Minimum of Months 38.74 27.39 11.35 6.63 89.48 0.00 0.00 0.00
Maximum of Months 926.08 576.74 410.71 1025.46 841.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 129.08 85.33 43.75 75.14 749.30 0.00 0.00 0.00
February 444.01 309.69 134.32 377.70 612.13 0.00 0.00 0.00
March 760.77 516.64 244.13 751.87 477.26 0.00 0.00 0.00
April 926.08 576.74 349.34 1025.45 317.45 0.00 0.00 0.00
May 760.95 393.66 367.29 870.91 169.60 0.00 0.00 0.00
June 693.95 283.23 410.71 817.82 89.48 0.00 0.00 0.00
July 669.19 290.66 378.52 807.72 94.25 0.00 0.00 0.00
August 694.99 383.28 311.72 824.99 140.79 0.00 0.00 0.00
September 562.83 339.61 223.22 602.56 251.03 0.00 0.00 0.00
October 406.08 258.38 147.70 369.57 414.57 0.00 0.00 0.00
November 218.14 152.77 65.37 142.85 711.23 0.00 0.00 0.00
December 38.74 27.39 11.35 6.63 841.25 0.00 0.00 0.00
                 
Annual Sum or Average 525.25 300.98 224.27 556.57 404.69 0.00 0.00 0.00
Minimum of Months 38.74 27.39 11.35 6.63 89.48 0.00 0.00 0.00
Maximum of Months 926.08 576.74 410.71 1025.45 841.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 129.08 85.33 43.75 75.15 749.30 0.00 0.00 0.00
February 444.01 309.69 134.32 377.71 612.13 0.00 0.00 0.00
March 760.78 516.64 244.14 751.87 477.26 0.00 0.00 0.00
April 926.08 576.74 349.34 1025.46 317.45 0.00 0.00 0.00
May 760.96 393.67 367.29 870.92 169.60 0.00 0.00 0.00
June 693.95 283.24 410.71 817.83 89.48 0.00 0.00 0.00
July 669.19 290.66 378.53 807.72 94.25 0.00 0.00 0.00
August 695.00 383.28 311.72 824.99 140.79 0.00 0.00 0.00
September 562.84 339.61 223.22 602.57 251.03 0.00 0.00 0.00
October 406.09 258.38 147.70 369.57 414.57 0.00 0.00 0.00
November 218.14 152.77 65.37 142.85 711.23 0.00 0.00 0.00
December 38.74 27.39 11.35 6.63 841.25 0.00 0.00 0.00
                 
Annual Sum or Average 525.25 300.98 224.27 556.57 404.69 0.00 0.00 0.00
Minimum of Months 38.74 27.39 11.35 6.63 89.48 0.00 0.00 0.00
Maximum of Months 926.08 576.74 410.71 1025.46 841.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 129.08 85.33 43.75 75.14 749.30 0.00 0.00 0.00
February 444.01 309.69 134.32 377.70 612.13 0.00 0.00 0.00
March 760.77 516.64 244.13 751.87 477.26 0.00 0.00 0.00
April 926.08 576.74 349.34 1025.45 317.45 0.00 0.00 0.00
May 760.95 393.66 367.29 870.91 169.60 0.00 0.00 0.00
June 693.95 283.23 410.71 817.82 89.48 0.00 0.00 0.00
July 669.19 290.66 378.52 807.72 94.25 0.00 0.00 0.00
August 694.99 383.28 311.72 824.99 140.79 0.00 0.00 0.00
September 562.83 339.61 223.22 602.56 251.03 0.00 0.00 0.00
October 406.08 258.38 147.70 369.57 414.57 0.00 0.00 0.00
November 218.14 152.77 65.37 142.85 711.23 0.00 0.00 0.00
December 38.74 27.39 11.35 6.63 841.25 0.00 0.00 0.00
                 
Annual Sum or Average 525.25 300.98 224.27 556.57 404.69 0.00 0.00 0.00
Minimum of Months 38.74 27.39 11.35 6.63 89.48 0.00 0.00 0.00
Maximum of Months 926.08 576.74 410.71 1025.45 841.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 129.08 85.33 43.75 75.14 749.27 0.00 0.00 0.00
February 443.99 309.68 134.31 377.69 612.10 0.00 0.00 0.00
March 760.75 516.62 244.13 751.84 477.24 0.00 0.00 0.00
April 926.04 576.72 349.32 1025.41 317.43 0.00 0.00 0.00
May 760.93 393.65 367.28 870.88 169.59 0.00 0.00 0.00
June 693.92 283.22 410.70 817.79 89.47 0.00 0.00 0.00
July 669.16 290.65 378.51 807.69 94.24 0.00 0.00 0.00
August 694.97 383.26 311.70 824.96 140.78 0.00 0.00 0.00
September 562.81 339.60 223.22 602.54 251.02 0.00 0.00 0.00
October 406.07 258.37 147.70 369.55 414.55 0.00 0.00 0.00
November 218.13 152.76 65.37 142.84 711.20 0.00 0.00 0.00
December 38.74 27.39 11.35 6.63 841.22 0.00 0.00 0.00
                 
Annual Sum or Average 525.23 300.97 224.26 556.55 404.68 0.00 0.00 0.00
Minimum of Months 38.74 27.39 11.35 6.63 89.47 0.00 0.00 0.00
Maximum of Months 926.04 576.72 410.70 1025.41 841.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.34 2.81 13.52 0.00 952.81 0.00 0.00 0.00
February 96.67 33.30 63.37 16.75 837.99 0.00 0.00 0.00
March 291.31 125.06 166.25 155.96 637.65 0.00 0.00 0.00
April 693.15 359.77 333.39 651.57 382.92 0.00 0.00 0.00
May 674.07 307.65 366.42 686.29 185.23 0.00 0.00 0.00
June 738.62 315.63 422.99 820.13 102.70 0.00 0.00 0.00
July 617.74 234.15 383.59 687.22 112.57 0.00 0.00 0.00
August 507.63 215.27 292.36 530.03 171.46 0.00 0.00 0.00
September 307.04 128.67 178.38 243.43 306.35 0.00 0.00 0.00
October 119.83 35.78 84.06 37.88 571.48 0.00 0.00 0.00
November 47.75 17.13 30.62 3.86 946.49 0.00 0.00 0.00
December 4.29 0.42 3.86 0.00 1049.30 0.00 0.00 0.00
                 
Annual Sum or Average 343.76 148.28 195.47 320.71 519.76 0.00 0.00 0.00
Minimum of Months 4.29 0.42 3.86 0.00 102.70 0.00 0.00 0.00
Maximum of Months 738.62 359.77 422.99 820.13 1049.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.34 2.81 13.52 0.00 952.81 0.00 0.00 0.00
February 96.67 33.30 63.37 16.75 837.99 0.00 0.00 0.00
March 291.31 125.06 166.25 155.96 637.65 0.00 0.00 0.00
April 693.15 359.77 333.39 651.57 382.92 0.00 0.00 0.00
May 674.07 307.65 366.42 686.29 185.23 0.00 0.00 0.00
June 738.62 315.63 422.99 820.13 102.70 0.00 0.00 0.00
July 617.74 234.15 383.59 687.22 112.57 0.00 0.00 0.00
August 507.63 215.27 292.36 530.03 171.46 0.00 0.00 0.00
September 307.04 128.67 178.38 243.43 306.35 0.00 0.00 0.00
October 119.83 35.78 84.06 37.88 571.48 0.00 0.00 0.00
November 47.75 17.13 30.62 3.86 946.49 0.00 0.00 0.00
December 4.29 0.42 3.86 0.00 1049.30 0.00 0.00 0.00
                 
Annual Sum or Average 343.76 148.28 195.47 320.71 519.76 0.00 0.00 0.00
Minimum of Months 4.29 0.42 3.86 0.00 102.70 0.00 0.00 0.00
Maximum of Months 738.62 359.77 422.99 820.13 1049.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.34 2.81 13.52 0.00 952.79 0.00 0.00 0.00
February 96.67 33.30 63.37 16.75 837.97 0.00 0.00 0.00
March 291.31 125.06 166.25 155.95 637.64 0.00 0.00 0.00
April 693.14 359.76 333.38 651.56 382.91 0.00 0.00 0.00
May 674.06 307.64 366.42 686.28 185.22 0.00 0.00 0.00
June 738.60 315.62 422.98 820.12 102.70 0.00 0.00 0.00
July 617.73 234.15 383.59 687.21 112.57 0.00 0.00 0.00
August 507.62 215.27 292.36 530.02 171.45 0.00 0.00 0.00
September 307.04 128.66 178.37 243.43 306.35 0.00 0.00 0.00
October 119.83 35.78 84.05 37.88 571.47 0.00 0.00 0.00
November 47.75 17.13 30.62 3.86 946.47 0.00 0.00 0.00
December 4.29 0.42 3.86 0.00 1049.28 0.00 0.00 0.00
                 
Annual Sum or Average 343.75 148.28 195.47 320.70 519.75 0.00 0.00 0.00
Minimum of Months 4.29 0.42 3.86 0.00 102.70 0.00 0.00 0.00
Maximum of Months 738.60 359.76 422.98 820.12 1049.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 53.45 0.00 53.45 0.00 4068.14 0.00 0.00 0.00
February 236.26 0.00 236.26 0.00 3657.13 0.00 0.00 0.00
March 631.89 0.00 631.89 49.85 2737.13 0.00 0.00 0.00
April 1141.80 23.71 1118.09 454.21 1481.62 0.00 0.00 0.00
May 1746.97 273.32 1473.65 1350.50 655.36 0.00 0.00 0.00
June 2282.62 504.87 1777.75 2273.63 303.08 0.00 0.00 0.00
July 1915.17 308.29 1606.87 1950.47 369.47 0.00 0.00 0.00
August 1222.83 66.10 1156.73 1006.22 616.58 0.00 0.00 0.00
September 683.44 0.61 682.84 250.05 1269.73 0.00 0.00 0.00
October 332.60 0.00 332.60 20.18 2355.02 0.00 0.00 0.00
November 103.22 0.00 103.22 0.00 3990.91 0.00 0.00 0.00
December 16.21 0.00 16.21 0.00 4287.90 0.00 0.00 0.00
                 
Annual Sum or Average 866.96 98.51 768.45 616.52 2141.20 0.00 0.00 0.00
Minimum of Months 16.21 0.00 16.21 0.00 303.08 0.00 0.00 0.00
Maximum of Months 2282.62 504.87 1777.75 2273.63 4287.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 93.02 28.70 64.32 7.87 2631.53 0.00 0.00 0.00
February 517.39 246.26 271.13 274.34 2208.63 0.00 0.00 0.00
March 1481.00 750.88 730.12 1261.53 1647.20 0.00 0.00 0.00
April 2036.66 1032.02 1004.64 1893.92 918.96 0.00 0.00 0.00
May 2962.68 1671.75 1290.93 3285.68 475.82 0.00 0.00 0.00
June 2723.46 1271.97 1451.49 3134.86 231.72 0.00 0.00 0.00
July 2587.45 1256.18 1331.27 3052.13 266.66 0.00 0.00 0.00
August 2048.83 998.59 1050.23 2307.39 417.48 0.00 0.00 0.00
September 1266.40 555.26 711.14 1184.16 796.63 0.00 0.00 0.00
October 667.77 267.76 400.00 477.27 1431.15 0.00 0.00 0.00
November 141.04 48.59 92.45 11.04 2561.22 0.00 0.00 0.00
December 20.06 4.62 15.44 0.00 2838.54 0.00 0.00 0.00
                 
Annual Sum or Average 1384.11 680.72 703.38 1415.20 1364.54 0.00 0.00 0.00
Minimum of Months 20.06 4.62 15.44 0.00 231.72 0.00 0.00 0.00
Maximum of Months 2962.68 1671.75 1451.49 3285.68 2838.54 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 645.43 426.68 218.75 380.90 3659.91 0.00 0.00 0.00
February 2220.10 1548.49 671.61 1905.66 2977.48 0.00 0.00 0.00
March 3803.97 2583.27 1220.70 3767.81 2328.55 0.00 0.00 0.00
April 4630.49 2883.78 1746.71 5114.16 1560.66 0.00 0.00 0.00
May 3804.86 1968.37 1836.49 4334.41 842.82 0.00 0.00 0.00
June 3469.80 1416.21 2053.60 4075.04 444.75 0.00 0.00 0.00
July 3346.01 1453.35 1892.66 4026.17 474.51 0.00 0.00 0.00
August 3475.05 1916.44 1558.61 4114.38 703.25 0.00 0.00 0.00
September 2814.23 1698.09 1116.14 3007.04 1241.19 0.00 0.00 0.00
October 2030.46 1291.94 738.52 1860.97 2008.14 0.00 0.00 0.00
November 1090.73 763.86 326.87 730.71 3427.94 0.00 0.00 0.00
December 193.69 136.94 56.75 34.13 4078.42 0.00 0.00 0.00
                 
Annual Sum or Average 2626.31 1504.94 1121.37 2781.50 1974.16 0.00 0.00 0.00
Minimum of Months 193.69 136.94 56.75 34.13 444.75 0.00 0.00 0.00
Maximum of Months 4630.49 2883.78 2053.60 5114.16 4078.42 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 49.01 8.44 40.56 0.00 2705.29 0.00 0.00 0.00
February 290.02 99.91 190.11 57.97 2323.34 0.00 0.00 0.00
March 873.93 375.18 498.75 499.59 1710.22 0.00 0.00 0.00
April 2079.44 1079.29 1000.15 2003.55 1020.73 0.00 0.00 0.00
May 2022.19 922.93 1099.26 2074.10 526.68 0.00 0.00 0.00
June 2215.83 946.88 1268.95 2478.11 284.92 0.00 0.00 0.00
July 1853.21 702.44 1150.77 2089.57 308.31 0.00 0.00 0.00
August 1522.88 645.80 877.08 1624.08 459.10 0.00 0.00 0.00
September 921.12 385.99 535.13 756.69 835.26 0.00 0.00 0.00
October 359.50 107.33 252.16 130.10 1517.50 0.00 0.00 0.00
November 143.24 51.40 91.85 14.67 2589.11 0.00 0.00 0.00
December 12.86 1.27 11.59 0.00 2885.29 0.00 0.00 0.00
                 
Annual Sum or Average 1031.26 444.85 586.41 981.24 1425.86 0.00 0.00 0.00
Minimum of Months 12.86 1.27 11.59 0.00 284.92 0.00 0.00 0.00
Maximum of Months 2215.83 1079.29 1268.95 2478.11 2885.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 53.45 0.00 53.45 0.00 3974.34 0.00 0.00 0.00
February 236.26 0.00 236.26 0.00 3546.05 0.00 0.00 0.00
March 631.89 0.00 631.89 59.38 2606.13 0.00 0.00 0.00
April 1141.80 23.71 1118.09 509.73 1356.10 0.00 0.00 0.00
May 1746.97 273.32 1473.65 1409.34 614.51 0.00 0.00 0.00
June 2282.62 504.87 1777.75 2280.90 293.26 0.00 0.00 0.00
July 1915.17 308.29 1606.87 1958.41 358.51 0.00 0.00 0.00
August 1222.83 66.10 1156.73 1033.50 582.90 0.00 0.00 0.00
September 683.44 0.61 682.84 298.49 1128.79 0.00 0.00 0.00
October 332.60 0.00 332.60 33.15 2184.35 0.00 0.00 0.00
November 103.22 0.00 103.22 0.00 3875.90 0.00 0.00 0.00
December 16.21 0.00 16.21 0.00 4184.63 0.00 0.00 0.00
                 
Annual Sum or Average 866.96 98.51 768.45 635.56 2050.90 0.00 0.00 0.00
Minimum of Months 16.21 0.00 16.21 0.00 293.26 0.00 0.00 0.00
Maximum of Months 2282.62 504.87 1777.75 2280.90 4184.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 93.02 28.70 64.32 8.13 2573.43 0.00 0.00 0.00
February 517.39 246.26 271.13 281.12 2140.18 0.00 0.00 0.00
March 1481.00 750.88 730.12 1285.68 1563.94 0.00 0.00 0.00
April 2036.66 1032.02 1004.64 1931.99 852.19 0.00 0.00 0.00
May 2962.68 1671.75 1290.93 3301.24 456.91 0.00 0.00 0.00
June 2723.46 1271.97 1451.49 3133.29 227.86 0.00 0.00 0.00
July 2587.45 1256.18 1331.27 3050.21 262.68 0.00 0.00 0.00
August 2048.83 998.59 1050.23 2313.63 403.99 0.00 0.00 0.00
September 1266.40 555.26 711.14 1217.91 725.12 0.00 0.00 0.00
October 667.77 267.76 400.00 497.71 1327.69 0.00 0.00 0.00
November 141.04 48.59 92.45 11.75 2489.53 0.00 0.00 0.00
December 20.06 4.62 15.44 0.00 2776.28 0.00 0.00 0.00
                 
Annual Sum or Average 1384.11 680.72 703.38 1427.05 1312.55 0.00 0.00 0.00
Minimum of Months 20.06 4.62 15.44 0.00 227.86 0.00 0.00 0.00
Maximum of Months 2962.68 1671.75 1451.49 3301.24 2776.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 645.43 426.68 218.75 387.64 3572.47 0.00 0.00 0.00
February 2220.10 1548.49 671.61 1936.17 2864.80 0.00 0.00 0.00
March 3803.97 2583.27 1220.70 3812.43 2202.70 0.00 0.00 0.00
April 4630.49 2883.78 1746.71 5156.26 1456.33 0.00 0.00 0.00
May 3804.86 1968.37 1836.49 4352.87 800.89 0.00 0.00 0.00
June 3469.80 1416.21 2053.60 4074.23 434.83 0.00 0.00 0.00
July 3346.01 1453.35 1892.66 4025.28 465.15 0.00 0.00 0.00
August 3475.05 1916.44 1558.61 4121.78 678.42 0.00 0.00 0.00
September 2814.23 1698.09 1116.14 3051.61 1135.87 0.00 0.00 0.00
October 2030.46 1291.94 738.52 1908.78 1856.54 0.00 0.00 0.00
November 1090.73 763.86 326.87 745.63 3316.54 0.00 0.00 0.00
December 193.69 136.94 56.75 34.97 3980.69 0.00 0.00 0.00
                 
Annual Sum or Average 2626.31 1504.94 1121.37 2802.74 1892.56 0.00 0.00 0.00
Minimum of Months 193.69 136.94 56.75 34.97 434.83 0.00 0.00 0.00
Maximum of Months 4630.49 2883.78 2053.60 5156.26 3980.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 49.01 8.44 40.56 0.00 2640.90 0.00 0.00 0.00
February 290.02 99.91 190.11 60.34 2253.62 0.00 0.00 0.00
March 873.93 375.18 498.75 512.49 1630.80 0.00 0.00 0.00
April 2079.44 1079.29 1000.15 2032.66 953.53 0.00 0.00 0.00
May 2022.19 922.93 1099.26 2090.87 500.91 0.00 0.00 0.00
June 2215.83 946.88 1268.95 2477.95 278.71 0.00 0.00 0.00
July 1853.21 702.44 1150.77 2089.72 301.70 0.00 0.00 0.00
August 1522.88 645.80 877.08 1631.76 441.90 0.00 0.00 0.00
September 921.12 385.99 535.13 782.61 765.91 0.00 0.00 0.00
October 359.50 107.33 252.16 141.22 1420.73 0.00 0.00 0.00
November 143.24 51.40 91.85 15.73 2514.25 0.00 0.00 0.00
December 12.86 1.27 11.59 0.00 2816.93 0.00 0.00 0.00
                 
Annual Sum or Average 1031.26 444.85 586.41 990.15 1372.17 0.00 0.00 0.00
Minimum of Months 12.86 1.27 11.59 0.00 278.71 0.00 0.00 0.00
Maximum of Months 2215.83 1079.29 1268.95 2477.95 2816.93 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 28629943.92 0.00 28629943.92 0.00 0.227146E+10
February 0.114311E+09 0.00 0.114311E+09 0.00 0.186773E+10
March 0.338489E+09 0.00 0.338489E+09 18188245.30 0.157485E+10
April 0.591910E+09 12291817.08 0.579618E+09 0.209039E+09 0.841877E+09
May 0.935816E+09 0.146413E+09 0.789403E+09 0.713010E+09 0.363825E+09
June 0.118331E+10 0.261722E+09 0.921586E+09 0.117605E+10 0.161337E+09
July 0.102591E+10 0.165145E+09 0.860770E+09 0.104027E+10 0.201965E+09
August 0.655047E+09 35410722.51 0.619636E+09 0.528356E+09 0.344815E+09
September 0.354297E+09 314063.07 0.353983E+09 0.117108E+09 0.712050E+09
October 0.178165E+09 0.00 0.178165E+09 6490391.87 0.138023E+10
November 53507324.75 0.00 53507324.75 0.00 0.219788E+10
December 8684824.83 0.00 8684824.83 0.00 0.241780E+10
           
Annual Sum or Average 0.546808E+10 0.621296E+09 0.484678E+10 0.380851E+10 0.143358E+11
Minimum of Months 8684824.83 0.00 8684824.83 0.00 0.161337E+09
Maximum of Months 0.118331E+10 0.261722E+09 0.921586E+09 0.117605E+10 0.241780E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 28629458.55 0.00 28629458.55 0.00 0.227146E+10
February 0.114309E+09 0.00 0.114309E+09 0.00 0.186773E+10
March 0.338484E+09 0.00 0.338484E+09 18186603.48 0.157485E+10
April 0.591901E+09 12291546.86 0.579610E+09 0.209032E+09 0.841879E+09
May 0.935801E+09 0.146409E+09 0.789392E+09 0.712991E+09 0.363825E+09
June 0.118329E+10 0.261716E+09 0.921572E+09 0.117602E+10 0.161337E+09
July 0.102590E+10 0.165141E+09 0.860756E+09 0.104025E+10 0.201964E+09
August 0.655037E+09 35409944.05 0.619627E+09 0.528344E+09 0.344815E+09
September 0.354291E+09 314056.16 0.353977E+09 0.117103E+09 0.712051E+09
October 0.178162E+09 0.00 0.178162E+09 6489802.78 0.138023E+10
November 53506417.66 0.00 53506417.66 0.00 0.219788E+10
December 8684671.14 0.00 8684671.14 0.00 0.241780E+10
           
Annual Sum or Average 0.546799E+10 0.621282E+09 0.484671E+10 0.380842E+10 0.143358E+11
Minimum of Months 8684671.14 0.00 8684671.14 0.00 0.161337E+09
Maximum of Months 0.118329E+10 0.261716E+09 0.921572E+09 0.117602E+10 0.241780E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 28629620.34 0.00 28629620.34 0.00 0.227146E+10
February 0.114309E+09 0.00 0.114309E+09 0.00 0.186773E+10
March 0.338485E+09 0.00 0.338485E+09 18187150.76 0.157485E+10
April 0.591904E+09 12291636.93 0.579612E+09 0.209035E+09 0.841878E+09
May 0.935806E+09 0.146410E+09 0.789396E+09 0.712997E+09 0.363825E+09
June 0.118329E+10 0.261718E+09 0.921577E+09 0.117603E+10 0.161337E+09
July 0.102590E+10 0.165142E+09 0.860761E+09 0.104026E+10 0.201964E+09
August 0.655040E+09 35410203.54 0.619630E+09 0.528348E+09 0.344815E+09
September 0.354293E+09 314058.46 0.353979E+09 0.117105E+09 0.712051E+09
October 0.178163E+09 0.00 0.178163E+09 6489999.14 0.138023E+10
November 53506720.02 0.00 53506720.02 0.00 0.219788E+10
December 8684722.37 0.00 8684722.37 0.00 0.241780E+10
           
Annual Sum or Average 0.546802E+10 0.621286E+09 0.484673E+10 0.380845E+10 0.143358E+11
Minimum of Months 8684722.37 0.00 8684722.37 0.00 0.161337E+09
Maximum of Months 0.118329E+10 0.261718E+09 0.921577E+09 0.117603E+10 0.241780E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 28629458.55 0.00 28629458.55 0.00 0.227146E+10
February 0.114309E+09 0.00 0.114309E+09 0.00 0.186773E+10
March 0.338484E+09 0.00 0.338484E+09 18186603.48 0.157485E+10
April 0.591901E+09 12291546.86 0.579610E+09 0.209032E+09 0.841879E+09
May 0.935801E+09 0.146409E+09 0.789392E+09 0.712991E+09 0.363825E+09
June 0.118329E+10 0.261716E+09 0.921572E+09 0.117602E+10 0.161337E+09
July 0.102590E+10 0.165141E+09 0.860756E+09 0.104025E+10 0.201964E+09
August 0.655037E+09 35409944.05 0.619627E+09 0.528344E+09 0.344815E+09
September 0.354291E+09 314056.16 0.353977E+09 0.117103E+09 0.712051E+09
October 0.178162E+09 0.00 0.178162E+09 6489802.78 0.138023E+10
November 53506417.66 0.00 53506417.66 0.00 0.219788E+10
December 8684671.14 0.00 8684671.14 0.00 0.241780E+10
           
Annual Sum or Average 0.546799E+10 0.621282E+09 0.484671E+10 0.380842E+10 0.143358E+11
Minimum of Months 8684671.14 0.00 8684671.14 0.00 0.161337E+09
Maximum of Months 0.118329E+10 0.261716E+09 0.921572E+09 0.117602E+10 0.241780E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 28628385.55 0.00 28628385.55 0.00 0.227137E+10
February 0.114304E+09 0.00 0.114304E+09 0.00 0.186765E+10
March 0.338471E+09 0.00 0.338471E+09 18186144.11 0.157479E+10
April 0.591879E+09 12291096.49 0.579588E+09 0.209025E+09 0.841845E+09
May 0.935766E+09 0.146404E+09 0.789362E+09 0.712966E+09 0.363810E+09
June 0.118324E+10 0.261707E+09 0.921537E+09 0.117598E+10 0.161330E+09
July 0.102586E+10 0.165135E+09 0.860724E+09 0.104021E+10 0.201956E+09
August 0.655012E+09 35408646.61 0.619604E+09 0.528325E+09 0.344801E+09
September 0.354278E+09 314044.66 0.353964E+09 0.117099E+09 0.712022E+09
October 0.178155E+09 0.00 0.178155E+09 6489639.39 0.138018E+10
November 53504412.29 0.00 53504412.29 0.00 0.219779E+10
December 8684346.72 0.00 8684346.72 0.00 0.241770E+10
           
Annual Sum or Average 0.546779E+10 0.621259E+09 0.484653E+10 0.380829E+10 0.143352E+11
Minimum of Months 8684346.72 0.00 8684346.72 0.00 0.161330E+09
Maximum of Months 0.118324E+10 0.261707E+09 0.921537E+09 0.117598E+10 0.241770E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 83052397.83 25625282.17 57427115.66 6890295.76 0.243784E+10
February 0.417231E+09 0.198586E+09 0.218645E+09 0.213297E+09 0.186518E+10
March 0.132225E+10 0.670392E+09 0.651860E+09 0.110865E+10 0.154665E+10
April 0.175969E+10 0.891676E+09 0.868018E+09 0.162621E+10 0.832413E+09
May 0.264511E+10 0.149255E+10 0.115256E+10 0.294473E+10 0.433849E+09
June 0.235309E+10 0.109899E+10 0.125410E+10 0.272083E+10 0.200612E+09
July 0.231009E+10 0.112153E+10 0.118857E+10 0.274017E+10 0.233108E+09
August 0.182921E+10 0.891554E+09 0.937656E+09 0.206909E+10 0.370268E+09
September 0.109418E+10 0.479750E+09 0.614431E+09 0.101435E+10 0.724479E+09
October 0.596190E+09 0.239063E+09 0.357127E+09 0.412773E+09 0.137038E+10
November 0.121859E+09 41980480.15 79878233.04 8559534.11 0.233054E+10
December 17908848.30 4121382.59 13787465.71 0.00 0.263881E+10
           
Annual Sum or Average 0.145499E+11 0.715581E+10 0.739405E+10 0.148656E+11 0.149841E+11
Minimum of Months 17908848.30 4121382.59 13787465.71 0.00 0.200612E+09
Maximum of Months 0.264511E+10 0.149255E+10 0.125410E+10 0.294473E+10 0.263881E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 83052397.83 25625282.17 57427115.66 6890295.76 0.243784E+10
February 0.417231E+09 0.198586E+09 0.218645E+09 0.213297E+09 0.186518E+10
March 0.132225E+10 0.670392E+09 0.651860E+09 0.110865E+10 0.154665E+10
April 0.175969E+10 0.891676E+09 0.868018E+09 0.162621E+10 0.832413E+09
May 0.264511E+10 0.149255E+10 0.115256E+10 0.294473E+10 0.433849E+09
June 0.235309E+10 0.109899E+10 0.125410E+10 0.272083E+10 0.200612E+09
July 0.231009E+10 0.112153E+10 0.118857E+10 0.274017E+10 0.233108E+09
August 0.182921E+10 0.891554E+09 0.937656E+09 0.206909E+10 0.370268E+09
September 0.109418E+10 0.479750E+09 0.614431E+09 0.101435E+10 0.724479E+09
October 0.596190E+09 0.239063E+09 0.357127E+09 0.412773E+09 0.137038E+10
November 0.121859E+09 41980480.15 79878233.04 8559534.11 0.233054E+10
December 17908848.30 4121382.59 13787465.71 0.00 0.263881E+10
           
Annual Sum or Average 0.145499E+11 0.715581E+10 0.739405E+10 0.148656E+11 0.149841E+11
Minimum of Months 17908848.30 4121382.59 13787465.71 0.00 0.200612E+09
Maximum of Months 0.264511E+10 0.149255E+10 0.125410E+10 0.294473E+10 0.263881E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 83050880.28 25624813.94 57426066.34 6890169.86 0.243780E+10
February 0.417224E+09 0.198583E+09 0.218641E+09 0.213293E+09 0.186515E+10
March 0.132223E+10 0.670380E+09 0.651848E+09 0.110863E+10 0.154662E+10
April 0.175966E+10 0.891659E+09 0.868003E+09 0.162618E+10 0.832398E+09
May 0.264506E+10 0.149252E+10 0.115253E+10 0.294467E+10 0.433841E+09
June 0.235305E+10 0.109897E+10 0.125408E+10 0.272078E+10 0.200608E+09
July 0.231005E+10 0.112151E+10 0.118855E+10 0.274012E+10 0.233103E+09
August 0.182918E+10 0.891538E+09 0.937639E+09 0.206905E+10 0.370262E+09
September 0.109416E+10 0.479741E+09 0.614420E+09 0.101433E+10 0.724465E+09
October 0.596179E+09 0.239058E+09 0.357121E+09 0.412766E+09 0.137036E+10
November 0.121856E+09 41979713.08 79876773.49 8559377.71 0.233050E+10
December 17908521.06 4121307.28 13787213.78 0.00 0.263876E+10
           
Annual Sum or Average 0.145496E+11 0.715568E+10 0.739392E+10 0.148653E+11 0.149839E+11
Minimum of Months 17908521.06 4121307.28 13787213.78 0.00 0.200608E+09
Maximum of Months 0.264506E+10 0.149252E+10 0.125408E+10 0.294467E+10 0.263876E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.345736E+09 0.228559E+09 0.117177E+09 0.201270E+09 0.200692E+10
February 0.107415E+10 0.749207E+09 0.324945E+09 0.913752E+09 0.148085E+10
March 0.203767E+10 0.138378E+10 0.653893E+09 0.201382E+10 0.127830E+10
April 0.240040E+10 0.149492E+10 0.905484E+09 0.265798E+10 0.822820E+09
May 0.203815E+10 0.105440E+10 0.983758E+09 0.233267E+10 0.454259E+09
June 0.179872E+10 0.734146E+09 0.106457E+10 0.211981E+10 0.231920E+09
July 0.179236E+10 0.778516E+09 0.101385E+10 0.216341E+10 0.252429E+09
August 0.186148E+10 0.102658E+10 0.834904E+09 0.220966E+10 0.377086E+09
September 0.145887E+10 0.880272E+09 0.578599E+09 0.156186E+10 0.650671E+09
October 0.108766E+10 0.692052E+09 0.395606E+09 0.989854E+09 0.111038E+10
November 0.565424E+09 0.395977E+09 0.169448E+09 0.370267E+09 0.184351E+10
December 0.103753E+09 73352279.58 30400728.39 17748750.36 0.225321E+10
           
Annual Sum or Average 0.165644E+11 0.949175E+10 0.707263E+10 0.175521E+11 0.127624E+11
Minimum of Months 0.103753E+09 73352279.58 30400728.39 17748750.36 0.231920E+09
Maximum of Months 0.240040E+10 0.149492E+10 0.106457E+10 0.265798E+10 0.225321E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.345733E+09 0.228557E+09 0.117176E+09 0.201267E+09 0.200692E+10
February 0.107414E+10 0.749202E+09 0.324943E+09 0.913742E+09 0.148085E+10
March 0.203766E+10 0.138377E+10 0.653889E+09 0.201380E+10 0.127830E+10
April 0.240039E+10 0.149491E+10 0.905479E+09 0.265796E+10 0.822820E+09
May 0.203814E+10 0.105439E+10 0.983753E+09 0.233265E+10 0.454260E+09
June 0.179871E+10 0.734140E+09 0.106457E+10 0.211980E+10 0.231920E+09
July 0.179235E+10 0.778511E+09 0.101384E+10 0.216339E+10 0.252429E+09
August 0.186147E+10 0.102657E+10 0.834899E+09 0.220964E+10 0.377086E+09
September 0.145886E+10 0.880265E+09 0.578596E+09 0.156184E+10 0.650671E+09
October 0.108765E+10 0.692047E+09 0.395603E+09 0.989844E+09 0.111038E+10
November 0.565420E+09 0.395974E+09 0.169447E+09 0.370262E+09 0.184351E+10
December 0.103752E+09 73351742.06 30400518.02 17748374.48 0.225320E+10
           
Annual Sum or Average 0.165643E+11 0.949168E+10 0.707259E+10 0.175520E+11 0.127624E+11
Minimum of Months 0.103752E+09 73351742.06 30400518.02 17748374.48 0.231920E+09
Maximum of Months 0.240039E+10 0.149491E+10 0.106457E+10 0.265796E+10 0.225320E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.345736E+09 0.228559E+09 0.117177E+09 0.201270E+09 0.200692E+10
February 0.107415E+10 0.749207E+09 0.324945E+09 0.913752E+09 0.148085E+10
March 0.203767E+10 0.138378E+10 0.653893E+09 0.201382E+10 0.127830E+10
April 0.240040E+10 0.149492E+10 0.905484E+09 0.265798E+10 0.822820E+09
May 0.203815E+10 0.105440E+10 0.983758E+09 0.233267E+10 0.454259E+09
June 0.179872E+10 0.734146E+09 0.106457E+10 0.211981E+10 0.231920E+09
July 0.179236E+10 0.778516E+09 0.101385E+10 0.216341E+10 0.252429E+09
August 0.186148E+10 0.102658E+10 0.834904E+09 0.220966E+10 0.377086E+09
September 0.145887E+10 0.880272E+09 0.578599E+09 0.156186E+10 0.650671E+09
October 0.108766E+10 0.692052E+09 0.395606E+09 0.989854E+09 0.111038E+10
November 0.565424E+09 0.395977E+09 0.169448E+09 0.370267E+09 0.184351E+10
December 0.103753E+09 73352279.58 30400728.39 17748750.36 0.225321E+10
           
Annual Sum or Average 0.165644E+11 0.949175E+10 0.707263E+10 0.175521E+11 0.127624E+11
Minimum of Months 0.103753E+09 73352279.58 30400728.39 17748750.36 0.231920E+09
Maximum of Months 0.240040E+10 0.149492E+10 0.106457E+10 0.265798E+10 0.225321E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.345733E+09 0.228557E+09 0.117176E+09 0.201267E+09 0.200692E+10
February 0.107414E+10 0.749202E+09 0.324943E+09 0.913742E+09 0.148085E+10
March 0.203766E+10 0.138377E+10 0.653889E+09 0.201380E+10 0.127830E+10
April 0.240039E+10 0.149491E+10 0.905479E+09 0.265796E+10 0.822820E+09
May 0.203814E+10 0.105439E+10 0.983753E+09 0.233265E+10 0.454260E+09
June 0.179871E+10 0.734140E+09 0.106457E+10 0.211980E+10 0.231920E+09
July 0.179235E+10 0.778511E+09 0.101384E+10 0.216339E+10 0.252429E+09
August 0.186147E+10 0.102657E+10 0.834899E+09 0.220964E+10 0.377086E+09
September 0.145886E+10 0.880265E+09 0.578596E+09 0.156184E+10 0.650671E+09
October 0.108765E+10 0.692047E+09 0.395603E+09 0.989844E+09 0.111038E+10
November 0.565420E+09 0.395974E+09 0.169447E+09 0.370262E+09 0.184351E+10
December 0.103752E+09 73351742.06 30400518.02 17748374.48 0.225320E+10
           
Annual Sum or Average 0.165643E+11 0.949168E+10 0.707259E+10 0.175520E+11 0.127624E+11
Minimum of Months 0.103752E+09 73351742.06 30400518.02 17748374.48 0.231920E+09
Maximum of Months 0.240039E+10 0.149491E+10 0.106457E+10 0.265796E+10 0.225320E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.345721E+09 0.228548E+09 0.117172E+09 0.201261E+09 0.200684E+10
February 0.107411E+10 0.749174E+09 0.324931E+09 0.913710E+09 0.148079E+10
March 0.203758E+10 0.138372E+10 0.653865E+09 0.201373E+10 0.127825E+10
April 0.240030E+10 0.149485E+10 0.905445E+09 0.265786E+10 0.822787E+09
May 0.203807E+10 0.105435E+10 0.983716E+09 0.233257E+10 0.454241E+09
June 0.179864E+10 0.734113E+09 0.106453E+10 0.211972E+10 0.231910E+09
July 0.179229E+10 0.778482E+09 0.101380E+10 0.216331E+10 0.252419E+09
August 0.186140E+10 0.102653E+10 0.834868E+09 0.220956E+10 0.377071E+09
September 0.145881E+10 0.880233E+09 0.578574E+09 0.156179E+10 0.650645E+09
October 0.108761E+10 0.692022E+09 0.395589E+09 0.989809E+09 0.111034E+10
November 0.565399E+09 0.395959E+09 0.169440E+09 0.370249E+09 0.184344E+10
December 0.103748E+09 73349054.41 30399397.92 17747847.08 0.225311E+10
           
Annual Sum or Average 0.165637E+11 0.949133E+10 0.707233E+10 0.175513E+11 0.127618E+11
Minimum of Months 0.103748E+09 73349054.41 30399397.92 17747847.08 0.231910E+09
Maximum of Months 0.240030E+10 0.149485E+10 0.106453E+10 0.265786E+10 0.225311E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 43752760.67 7537859.59 36214901.08 0.00 0.255201E+10
February 0.233874E+09 80564889.92 0.153309E+09 40526277.21 0.202726E+10
March 0.780252E+09 0.334961E+09 0.445291E+09 0.417717E+09 0.170788E+10
April 0.179665E+10 0.932515E+09 0.864140E+09 0.168887E+10 0.992527E+09
May 0.180543E+10 0.824004E+09 0.981426E+09 0.183816E+10 0.496112E+09
June 0.191449E+10 0.818114E+09 0.109638E+10 0.212579E+10 0.266193E+09
July 0.165457E+10 0.627148E+09 0.102742E+10 0.184065E+10 0.301502E+09
August 0.135964E+10 0.576577E+09 0.783064E+09 0.141964E+10 0.459231E+09
September 0.795853E+09 0.333500E+09 0.462353E+09 0.630979E+09 0.794066E+09
October 0.320962E+09 95828081.28 0.225134E+09 0.101467E+09 0.153064E+10
November 0.123762E+09 44406527.85 79355872.31 10017765.35 0.245329E+10
December 11485657.37 1138115.94 10347541.43 0.00 0.281045E+10
           
Annual Sum or Average 0.108407E+11 0.467630E+10 0.616443E+10 0.101138E+11 0.163912E+11
Minimum of Months 11485657.37 1138115.94 10347541.43 0.00 0.266193E+09
Maximum of Months 0.191449E+10 0.932515E+09 0.109638E+10 0.212579E+10 0.281045E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 43752760.67 7537859.59 36214901.08 0.00 0.255201E+10
February 0.233874E+09 80564889.92 0.153309E+09 40526277.21 0.202726E+10
March 0.780252E+09 0.334961E+09 0.445291E+09 0.417717E+09 0.170788E+10
April 0.179665E+10 0.932515E+09 0.864140E+09 0.168887E+10 0.992527E+09
May 0.180543E+10 0.824004E+09 0.981426E+09 0.183816E+10 0.496112E+09
June 0.191449E+10 0.818114E+09 0.109638E+10 0.212579E+10 0.266193E+09
July 0.165457E+10 0.627148E+09 0.102742E+10 0.184065E+10 0.301502E+09
August 0.135964E+10 0.576577E+09 0.783064E+09 0.141964E+10 0.459231E+09
September 0.795853E+09 0.333500E+09 0.462353E+09 0.630979E+09 0.794066E+09
October 0.320962E+09 95828081.28 0.225134E+09 0.101467E+09 0.153064E+10
November 0.123762E+09 44406527.85 79355872.31 10017765.35 0.245329E+10
December 11485657.37 1138115.94 10347541.43 0.00 0.281045E+10
           
Annual Sum or Average 0.108407E+11 0.467630E+10 0.616443E+10 0.101138E+11 0.163912E+11
Minimum of Months 11485657.37 1138115.94 10347541.43 0.00 0.266193E+09
Maximum of Months 0.191449E+10 0.932515E+09 0.109638E+10 0.212579E+10 0.281045E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 43751961.21 7537721.86 36214239.36 0.00 0.255196E+10
February 0.233870E+09 80563417.83 0.153306E+09 40525536.71 0.202723E+10
March 0.780238E+09 0.334955E+09 0.445283E+09 0.417710E+09 0.170785E+10
April 0.179662E+10 0.932498E+09 0.864124E+09 0.168884E+10 0.992509E+09
May 0.180540E+10 0.823989E+09 0.981408E+09 0.183813E+10 0.496102E+09
June 0.191446E+10 0.818099E+09 0.109636E+10 0.212575E+10 0.266189E+09
July 0.165454E+10 0.627136E+09 0.102740E+10 0.184062E+10 0.301497E+09
August 0.135962E+10 0.576567E+09 0.783050E+09 0.141961E+10 0.459223E+09
September 0.795839E+09 0.333494E+09 0.462345E+09 0.630968E+09 0.794051E+09
October 0.320956E+09 95826330.30 0.225130E+09 0.101465E+09 0.153061E+10
November 0.123760E+09 44405716.45 79354422.31 10017582.30 0.245325E+10
December 11485447.50 1138095.14 10347352.36 0.00 0.281040E+10
           
Annual Sum or Average 0.108405E+11 0.467621E+10 0.616432E+10 0.101136E+11 0.163909E+11
Minimum of Months 11485447.50 1138095.14 10347352.36 0.00 0.266189E+09
Maximum of Months 0.191446E+10 0.932498E+09 0.109636E+10 0.212575E+10 0.281040E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.143150E+09 0.00 0.143150E+09 0.00 0.108961E+11
February 0.571554E+09 0.00 0.571554E+09 0.00 0.884732E+10
March 0.169244E+10 0.00 0.169244E+10 0.133516E+09 0.733114E+10
April 0.295955E+10 61459477.06 0.289809E+10 0.117732E+10 0.384035E+10
May 0.467909E+10 0.732068E+09 0.394702E+10 0.361719E+10 0.175532E+10
June 0.591655E+10 0.130862E+10 0.460794E+10 0.589324E+10 0.785592E+09
July 0.512958E+10 0.825728E+09 0.430385E+10 0.522415E+10 0.989577E+09
August 0.327524E+10 0.177055E+09 0.309818E+10 0.269506E+10 0.165145E+10
September 0.177149E+10 1570325.35 0.176992E+10 0.648121E+09 0.329115E+10
October 0.890826E+09 0.00 0.890826E+09 54058950.21 0.630767E+10
November 0.267537E+09 0.00 0.267537E+09 0.00 0.103444E+11
December 43424244.47 0.00 43424244.47 0.00 0.114847E+11
           
Annual Sum or Average 0.273404E+11 0.310650E+10 0.242339E+11 0.194426E+11 0.675248E+11
Minimum of Months 43424244.47 0.00 43424244.47 0.00 0.785592E+09
Maximum of Months 0.591655E+10 0.130862E+10 0.460794E+10 0.589324E+10 0.114847E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.249155E+09 76875062.93 0.172280E+09 21075318.51 0.704830E+10
February 0.125168E+10 0.595752E+09 0.655929E+09 0.663686E+09 0.534311E+10
March 0.396671E+10 0.201116E+10 0.195556E+10 0.337887E+10 0.441187E+10
April 0.527903E+10 0.267500E+10 0.260403E+10 0.490904E+10 0.238194E+10
May 0.793524E+10 0.447761E+10 0.345763E+10 0.880036E+10 0.127445E+10
June 0.705920E+10 0.329694E+10 0.376226E+10 0.812556E+10 0.600626E+09
July 0.693021E+10 0.336454E+10 0.356567E+10 0.817482E+10 0.714232E+09
August 0.548758E+10 0.267464E+10 0.281294E+10 0.618011E+10 0.111817E+10
September 0.328251E+10 0.143924E+10 0.184327E+10 0.306933E+10 0.206487E+10
October 0.178855E+10 0.717181E+09 0.107137E+10 0.127831E+10 0.383320E+10
November 0.365572E+09 0.125940E+09 0.239632E+09 28606390.38 0.663867E+10
December 53725997.27 12364021.73 41361975.53 0.00 0.760274E+10
           
Annual Sum or Average 0.436492E+11 0.214672E+11 0.221819E+11 0.446298E+11 0.430322E+11
Minimum of Months 53725997.27 12364021.73 41361975.53 0.00 0.600626E+09
Maximum of Months 0.793524E+10 0.447761E+10 0.376226E+10 0.880036E+10 0.760274E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.172871E+10 0.114282E+10 0.585898E+09 0.102020E+10 0.980271E+10
February 0.537087E+10 0.374612E+10 0.162475E+10 0.461018E+10 0.720313E+10
March 0.101886E+11 0.691904E+10 0.326952E+10 0.100917E+11 0.623679E+10
April 0.120022E+11 0.747475E+10 0.452748E+10 0.132559E+11 0.404523E+10
May 0.101909E+11 0.527209E+10 0.491885E+10 0.116093E+11 0.225741E+10
June 0.899373E+10 0.367081E+10 0.532292E+10 0.105625E+11 0.115280E+10
July 0.896196E+10 0.389266E+10 0.506930E+10 0.107837E+11 0.127093E+10
August 0.930757E+10 0.513300E+10 0.417458E+10 0.110199E+11 0.188358E+10
September 0.729449E+10 0.440145E+10 0.289304E+10 0.779424E+10 0.321716E+10
October 0.543840E+10 0.346033E+10 0.197806E+10 0.498443E+10 0.537861E+10
November 0.282718E+10 0.197992E+10 0.847254E+09 0.189399E+10 0.888521E+10
December 0.518776E+09 0.366769E+09 0.152007E+09 91426012.19 0.109237E+11
           
Annual Sum or Average 0.828234E+11 0.474598E+11 0.353637E+11 0.877175E+11 0.622572E+11
Minimum of Months 0.518776E+09 0.366769E+09 0.152007E+09 91426012.19 0.115280E+10
Maximum of Months 0.120022E+11 0.747475E+10 0.532292E+10 0.132559E+11 0.109237E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.131257E+09 22613348.27 0.108644E+09 0.00 0.724584E+10
February 0.701615E+09 0.241692E+09 0.459923E+09 0.140251E+09 0.562063E+10
March 0.234073E+10 0.100487E+10 0.133586E+10 0.133811E+10 0.458066E+10
April 0.538991E+10 0.279752E+10 0.259239E+10 0.519321E+10 0.264574E+10
May 0.541623E+10 0.247199E+10 0.294425E+10 0.555526E+10 0.141067E+10
June 0.574343E+10 0.245432E+10 0.328911E+10 0.642325E+10 0.738510E+09
July 0.496365E+10 0.188142E+10 0.308222E+10 0.559670E+10 0.825780E+09
August 0.407888E+10 0.172971E+10 0.234917E+10 0.434993E+10 0.122965E+10
September 0.238754E+10 0.100049E+10 0.138705E+10 0.196134E+10 0.216499E+10
October 0.962876E+09 0.287481E+09 0.675395E+09 0.348453E+09 0.406446E+10
November 0.371283E+09 0.133218E+09 0.238065E+09 38028643.24 0.671098E+10
December 34456620.89 3414313.01 31042307.88 0.00 0.772796E+10
           
Annual Sum or Average 0.325219E+11 0.140287E+11 0.184931E+11 0.309445E+11 0.449659E+11
Minimum of Months 34456620.89 3414313.01 31042307.88 0.00 0.738510E+09
Maximum of Months 0.574343E+10 0.279752E+10 0.328911E+10 0.642325E+10 0.772796E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.143150E+09 0.00 0.143150E+09 0.00 0.106449E+11
February 0.571554E+09 0.00 0.571554E+09 0.00 0.857859E+10
March 0.169244E+10 0.00 0.169244E+10 0.159043E+09 0.698027E+10
April 0.295955E+10 61459477.06 0.289809E+10 0.132121E+10 0.351502E+10
May 0.467909E+10 0.732068E+09 0.394702E+10 0.377478E+10 0.164591E+10
June 0.591655E+10 0.130862E+10 0.460794E+10 0.591209E+10 0.760137E+09
July 0.512958E+10 0.825728E+09 0.430385E+10 0.524540E+10 0.960243E+09
August 0.327524E+10 0.177055E+09 0.309818E+10 0.276814E+10 0.156123E+10
September 0.177149E+10 1570325.35 0.176992E+10 0.773689E+09 0.292583E+10
October 0.890826E+09 0.00 0.890826E+09 88784537.19 0.585057E+10
November 0.267537E+09 0.00 0.267537E+09 0.00 0.100463E+11
December 43424244.47 0.00 43424244.47 0.00 0.112081E+11
           
Annual Sum or Average 0.273404E+11 0.310650E+10 0.242339E+11 0.200431E+11 0.646771E+11
Minimum of Months 43424244.47 0.00 43424244.47 0.00 0.760137E+09
Maximum of Months 0.591655E+10 0.130862E+10 0.460794E+10 0.591209E+10 0.112081E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.249155E+09 76875062.93 0.172280E+09 21784711.36 0.689266E+10
February 0.125168E+10 0.595752E+09 0.655929E+09 0.680083E+09 0.517753E+10
March 0.396671E+10 0.201116E+10 0.195556E+10 0.344356E+10 0.418887E+10
April 0.527903E+10 0.267500E+10 0.260403E+10 0.500772E+10 0.220889E+10
May 0.793524E+10 0.447761E+10 0.345763E+10 0.884205E+10 0.122380E+10
June 0.705920E+10 0.329694E+10 0.376226E+10 0.812148E+10 0.590609E+09
July 0.693021E+10 0.336454E+10 0.356567E+10 0.816968E+10 0.703569E+09
August 0.548758E+10 0.267464E+10 0.281294E+10 0.619682E+10 0.108206E+10
September 0.328251E+10 0.143924E+10 0.184327E+10 0.315681E+10 0.187951E+10
October 0.178855E+10 0.717181E+09 0.107137E+10 0.133305E+10 0.355610E+10
November 0.365572E+09 0.125940E+09 0.239632E+09 30446498.91 0.645287E+10
December 53725997.27 12364021.73 41361975.53 0.00 0.743599E+10
           
Annual Sum or Average 0.436492E+11 0.214672E+11 0.221819E+11 0.450035E+11 0.413925E+11
Minimum of Months 53725997.27 12364021.73 41361975.53 0.00 0.590609E+09
Maximum of Months 0.793524E+10 0.447761E+10 0.376226E+10 0.884205E+10 0.743599E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.172871E+10 0.114282E+10 0.585898E+09 0.103825E+10 0.956851E+10
February 0.537087E+10 0.374612E+10 0.162475E+10 0.468397E+10 0.693053E+10
March 0.101886E+11 0.691904E+10 0.326952E+10 0.102112E+11 0.589970E+10
April 0.120022E+11 0.747475E+10 0.452748E+10 0.133650E+11 0.377481E+10
May 0.101909E+11 0.527209E+10 0.491885E+10 0.116587E+11 0.214510E+10
June 0.899373E+10 0.367081E+10 0.532292E+10 0.105604E+11 0.112709E+10
July 0.896196E+10 0.389266E+10 0.506930E+10 0.107813E+11 0.124586E+10
August 0.930757E+10 0.513300E+10 0.417458E+10 0.110398E+11 0.181708E+10
September 0.729449E+10 0.440145E+10 0.289304E+10 0.790978E+10 0.294417E+10
October 0.543840E+10 0.346033E+10 0.197806E+10 0.511248E+10 0.497256E+10
November 0.282718E+10 0.197992E+10 0.847254E+09 0.193268E+10 0.859648E+10
December 0.518776E+09 0.366769E+09 0.152007E+09 93658846.80 0.106619E+11
           
Annual Sum or Average 0.828234E+11 0.474598E+11 0.353637E+11 0.883873E+11 0.596838E+11
Minimum of Months 0.518776E+09 0.366769E+09 0.152007E+09 93658846.80 0.112709E+10
Maximum of Months 0.120022E+11 0.747475E+10 0.532292E+10 0.133650E+11 0.106619E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.131257E+09 22613348.27 0.108644E+09 0.00 0.707340E+10
February 0.701615E+09 0.241692E+09 0.459923E+09 0.145970E+09 0.545196E+10
March 0.234073E+10 0.100487E+10 0.133586E+10 0.137265E+10 0.436794E+10
April 0.538991E+10 0.279752E+10 0.259239E+10 0.526865E+10 0.247155E+10
May 0.541623E+10 0.247199E+10 0.294425E+10 0.560018E+10 0.134163E+10
June 0.574343E+10 0.245432E+10 0.328911E+10 0.642285E+10 0.722426E+09
July 0.496365E+10 0.188142E+10 0.308222E+10 0.559710E+10 0.808078E+09
August 0.407888E+10 0.172971E+10 0.234917E+10 0.437052E+10 0.118357E+10
September 0.238754E+10 0.100049E+10 0.138705E+10 0.202852E+10 0.198523E+10
October 0.962876E+09 0.287481E+09 0.675395E+09 0.378255E+09 0.380530E+10
November 0.371283E+09 0.133218E+09 0.238065E+09 40760115.41 0.651694E+10
December 34456620.89 3414313.01 31042307.88 0.00 0.754487E+10
           
Annual Sum or Average 0.325219E+11 0.140287E+11 0.184931E+11 0.312255E+11 0.432729E+11
Minimum of Months 34456620.89 3414313.01 31042307.88 0.00 0.722426E+09
Maximum of Months 0.574343E+10 0.279752E+10 0.328911E+10 0.642285E+10 0.754487E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 4240.30 53.44 0.00 53.44 0.00 0.00
February 0.00 3860.18 236.25 0.00 236.25 0.00 0.00
March 33.95 2939.89 631.87 0.00 631.87 0.00 0.00
April 403.23 1623.98 1141.78 23.71 1118.07 0.00 0.00
May 1331.00 679.18 1746.93 273.31 1473.62 0.00 0.00
June 2268.56 311.22 2282.57 504.85 1777.72 0.00 0.00
July 1941.92 377.02 1915.12 308.28 1606.84 0.00 0.00
August 986.30 643.69 1222.81 66.10 1156.71 0.00 0.00
September 225.89 1373.54 683.43 0.61 682.82 0.00 0.00
October 12.12 2576.58 332.59 0.00 332.59 0.00 0.00
November 0.00 4239.71 103.21 0.00 103.21 0.00 0.00
December 0.00 4513.48 16.21 0.00 16.21 0.00 0.00
               
Annual Sum or Average 603.82 2272.91 866.94 98.50 768.44 0.00 0.00
Minimum of Months 0.00 311.22 16.21 0.00 16.21 0.00 0.00
Maximum of Months 2268.56 4513.48 2282.57 504.85 1777.72 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 7.72 2730.54 93.02 28.70 64.32 0.00 0.00
February 264.50 2312.96 517.40 246.26 271.14 0.00 0.00
March 1241.76 1732.34 1481.01 750.88 730.13 0.00 0.00
April 1882.18 963.44 2036.67 1032.03 1004.64 0.00 0.00
May 3298.28 485.94 2962.69 1671.75 1290.94 0.00 0.00
June 3149.09 232.19 2723.47 1271.97 1451.49 0.00 0.00
July 3069.17 261.10 2587.46 1256.18 1331.27 0.00 0.00
August 2317.52 414.72 2048.83 998.60 1050.24 0.00 0.00
September 1174.01 838.51 1266.41 555.26 711.14 0.00 0.00
October 462.33 1534.92 667.77 267.77 400.01 0.00 0.00
November 9.91 2697.37 141.04 48.59 92.45 0.00 0.00
December 0.00 2955.64 20.06 4.62 15.44 0.00 0.00
               
Annual Sum or Average 1414.14 1425.42 1384.11 680.72 703.39 0.00 0.00
Minimum of Months 0.00 232.19 20.06 4.62 15.44 0.00 0.00
Maximum of Months 3298.28 2955.64 2962.69 1671.75 1451.49 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 375.72 3746.45 645.41 426.66 218.74 0.00 0.00
February 1888.52 3060.60 2220.03 1548.44 671.59 0.00 0.00
March 3759.32 2386.30 3803.85 2583.19 1220.66 0.00 0.00
April 5127.22 1587.22 4630.35 2883.68 1746.67 0.00 0.00
May 4354.55 848.00 3804.76 1968.31 1836.45 0.00 0.00
June 4089.10 447.37 3469.71 1416.16 2053.55 0.00 0.00
July 4038.57 471.23 3345.92 1453.31 1892.61 0.00 0.00
August 4124.92 703.93 3474.95 1916.38 1558.57 0.00 0.00
September 3012.80 1255.14 2814.15 1698.04 1116.11 0.00 0.00
October 1847.82 2072.83 2030.40 1291.90 738.50 0.00 0.00
November 714.24 3556.13 1090.70 763.83 326.86 0.00 0.00
December 33.13 4206.22 193.68 136.93 56.75 0.00 0.00
               
Annual Sum or Average 2782.83 2023.44 2626.24 1504.89 1121.35 0.00 0.00
Minimum of Months 33.13 447.37 193.68 136.93 56.75 0.00 0.00
Maximum of Months 5127.22 4206.22 4630.35 2883.68 2053.55 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 2858.42 49.01 8.44 40.56 0.00 0.00
February 50.26 2513.95 290.02 99.91 190.11 0.00 0.00
March 467.87 1912.94 873.93 375.18 498.75 0.00 0.00
April 1954.70 1148.75 2079.45 1079.29 1000.16 0.00 0.00
May 2058.86 555.68 2022.20 922.94 1099.26 0.00 0.00
June 2460.39 308.09 2215.84 946.89 1268.95 0.00 0.00
July 2061.65 337.70 1853.22 702.45 1150.77 0.00 0.00
August 1590.09 514.37 1522.89 645.80 877.08 0.00 0.00
September 730.30 919.05 921.12 385.99 535.13 0.00 0.00
October 113.65 1714.42 359.50 107.33 252.16 0.00 0.00
November 11.59 2839.44 143.24 51.40 91.85 0.00 0.00
December 0.00 3147.89 12.86 1.27 11.59 0.00 0.00
               
Annual Sum or Average 962.12 1559.27 1031.27 444.85 586.42 0.00 0.00
Minimum of Months 0.00 308.09 12.86 1.27 11.59 0.00 0.00
Maximum of Months 2460.39 3147.89 2215.84 1079.29 1268.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 4068.14 53.45 0.00 53.45 0.00 0.00
February 0.00 3657.13 236.26 0.00 236.26 0.00 0.00
March 49.85 2737.13 631.89 0.00 631.89 0.00 0.00
April 454.21 1481.62 1141.80 23.71 1118.09 0.00 0.00
May 1350.50 655.36 1746.97 273.32 1473.65 0.00 0.00
June 2273.63 303.08 2282.62 504.87 1777.75 0.00 0.00
July 1950.47 369.47 1915.17 308.29 1606.87 0.00 0.00
August 1006.22 616.58 1222.83 66.10 1156.73 0.00 0.00
September 250.05 1269.73 683.44 0.61 682.84 0.00 0.00
October 20.18 2355.02 332.60 0.00 332.60 0.00 0.00
November 0.00 3990.91 103.22 0.00 103.22 0.00 0.00
December 0.00 4287.90 16.21 0.00 16.21 0.00 0.00
               
Annual Sum or Average 616.52 2141.20 866.96 98.51 768.45 0.00 0.00
Minimum of Months 0.00 303.08 16.21 0.00 16.21 0.00 0.00
Maximum of Months 2273.63 4287.90 2282.62 504.87 1777.75 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 7.87 2631.53 93.02 28.70 64.32 0.00 0.00
February 274.34 2208.63 517.39 246.26 271.13 0.00 0.00
March 1261.53 1647.20 1481.00 750.88 730.12 0.00 0.00
April 1893.92 918.96 2036.66 1032.02 1004.64 0.00 0.00
May 3285.68 475.82 2962.68 1671.75 1290.93 0.00 0.00
June 3134.86 231.72 2723.46 1271.97 1451.49 0.00 0.00
July 3052.13 266.66 2587.45 1256.18 1331.27 0.00 0.00
August 2307.39 417.48 2048.83 998.59 1050.23 0.00 0.00
September 1184.16 796.63 1266.40 555.26 711.14 0.00 0.00
October 477.27 1431.15 667.77 267.76 400.00 0.00 0.00
November 11.04 2561.22 141.04 48.59 92.45 0.00 0.00
December 0.00 2838.54 20.06 4.62 15.44 0.00 0.00
               
Annual Sum or Average 1415.20 1364.54 1384.11 680.72 703.38 0.00 0.00
Minimum of Months 0.00 231.72 20.06 4.62 15.44 0.00 0.00
Maximum of Months 3285.68 2838.54 2962.68 1671.75 1451.49 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 380.90 3659.91 645.43 426.68 218.75 0.00 0.00
February 1905.66 2977.48 2220.10 1548.49 671.61 0.00 0.00
March 3767.81 2328.55 3803.97 2583.27 1220.70 0.00 0.00
April 5114.16 1560.66 4630.49 2883.78 1746.71 0.00 0.00
May 4334.41 842.82 3804.86 1968.37 1836.49 0.00 0.00
June 4075.04 444.75 3469.80 1416.21 2053.60 0.00 0.00
July 4026.17 474.51 3346.01 1453.35 1892.66 0.00 0.00
August 4114.38 703.25 3475.05 1916.44 1558.61 0.00 0.00
September 3007.04 1241.19 2814.23 1698.09 1116.14 0.00 0.00
October 1860.97 2008.14 2030.46 1291.94 738.52 0.00 0.00
November 730.71 3427.94 1090.73 763.86 326.87 0.00 0.00
December 34.13 4078.42 193.69 136.94 56.75 0.00 0.00
               
Annual Sum or Average 2781.50 1974.16 2626.31 1504.94 1121.37 0.00 0.00
Minimum of Months 34.13 444.75 193.69 136.94 56.75 0.00 0.00
Maximum of Months 5114.16 4078.42 4630.49 2883.78 2053.60 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 2705.29 49.01 8.44 40.56 0.00 0.00
February 57.97 2323.34 290.02 99.91 190.11 0.00 0.00
March 499.59 1710.22 873.93 375.18 498.75 0.00 0.00
April 2003.55 1020.73 2079.44 1079.29 1000.15 0.00 0.00
May 2074.10 526.68 2022.19 922.93 1099.26 0.00 0.00
June 2478.11 284.92 2215.83 946.88 1268.95 0.00 0.00
July 2089.57 308.31 1853.21 702.44 1150.77 0.00 0.00
August 1624.08 459.10 1522.88 645.80 877.08 0.00 0.00
September 756.69 835.26 921.12 385.99 535.13 0.00 0.00
October 130.10 1517.50 359.50 107.33 252.16 0.00 0.00
November 14.67 2589.11 143.24 51.40 91.85 0.00 0.00
December 0.00 2885.29 12.86 1.27 11.59 0.00 0.00
               
Annual Sum or Average 981.24 1425.86 1031.26 444.85 586.41 0.00 0.00
Minimum of Months 0.00 284.92 12.86 1.27 11.59 0.00 0.00
Maximum of Months 2478.11 2885.29 2215.83 1079.29 1268.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 3974.34 53.45 0.00 53.45 0.00 0.00
February 0.00 3546.05 236.26 0.00 236.26 0.00 0.00
March 59.38 2606.13 631.89 0.00 631.89 0.00 0.00
April 509.73 1356.10 1141.80 23.71 1118.09 0.00 0.00
May 1409.34 614.51 1746.97 273.32 1473.65 0.00 0.00
June 2280.90 293.26 2282.62 504.87 1777.75 0.00 0.00
July 1958.41 358.51 1915.17 308.29 1606.87 0.00 0.00
August 1033.50 582.90 1222.83 66.10 1156.73 0.00 0.00
September 298.49 1128.79 683.44 0.61 682.84 0.00 0.00
October 33.15 2184.35 332.60 0.00 332.60 0.00 0.00
November 0.00 3875.90 103.22 0.00 103.22 0.00 0.00
December 0.00 4184.63 16.21 0.00 16.21 0.00 0.00
               
Annual Sum or Average 635.56 2050.90 866.96 98.51 768.45 0.00 0.00
Minimum of Months 0.00 293.26 16.21 0.00 16.21 0.00 0.00
Maximum of Months 2280.90 4184.63 2282.62 504.87 1777.75 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 8.13 2573.43 93.02 28.70 64.32 0.00 0.00
February 281.12 2140.18 517.39 246.26 271.13 0.00 0.00
March 1285.68 1563.94 1481.00 750.88 730.12 0.00 0.00
April 1931.99 852.19 2036.66 1032.02 1004.64 0.00 0.00
May 3301.24 456.91 2962.68 1671.75 1290.93 0.00 0.00
June 3133.29 227.86 2723.46 1271.97 1451.49 0.00 0.00
July 3050.21 262.68 2587.45 1256.18 1331.27 0.00 0.00
August 2313.63 403.99 2048.83 998.59 1050.23 0.00 0.00
September 1217.91 725.12 1266.40 555.26 711.14 0.00 0.00
October 497.71 1327.69 667.77 267.76 400.00 0.00 0.00
November 11.75 2489.53 141.04 48.59 92.45 0.00 0.00
December 0.00 2776.28 20.06 4.62 15.44 0.00 0.00
               
Annual Sum or Average 1427.05 1312.55 1384.11 680.72 703.38 0.00 0.00
Minimum of Months 0.00 227.86 20.06 4.62 15.44 0.00 0.00
Maximum of Months 3301.24 2776.28 2962.68 1671.75 1451.49 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 387.64 3572.47 645.43 426.68 218.75 0.00 0.00
February 1936.17 2864.80 2220.10 1548.49 671.61 0.00 0.00
March 3812.43 2202.70 3803.97 2583.27 1220.70 0.00 0.00
April 5156.26 1456.33 4630.49 2883.78 1746.71 0.00 0.00
May 4352.87 800.89 3804.86 1968.37 1836.49 0.00 0.00
June 4074.23 434.83 3469.80 1416.21 2053.60 0.00 0.00
July 4025.28 465.15 3346.01 1453.35 1892.66 0.00 0.00
August 4121.78 678.42 3475.05 1916.44 1558.61 0.00 0.00
September 3051.61 1135.87 2814.23 1698.09 1116.14 0.00 0.00
October 1908.78 1856.54 2030.46 1291.94 738.52 0.00 0.00
November 745.63 3316.54 1090.73 763.86 326.87 0.00 0.00
December 34.97 3980.69 193.69 136.94 56.75 0.00 0.00
               
Annual Sum or Average 2802.74 1892.56 2626.31 1504.94 1121.37 0.00 0.00
Minimum of Months 34.97 434.83 193.69 136.94 56.75 0.00 0.00
Maximum of Months 5156.26 3980.69 4630.49 2883.78 2053.60 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 2640.90 49.01 8.44 40.56 0.00 0.00
February 60.34 2253.62 290.02 99.91 190.11 0.00 0.00
March 512.49 1630.80 873.93 375.18 498.75 0.00 0.00
April 2032.66 953.53 2079.44 1079.29 1000.15 0.00 0.00
May 2090.87 500.91 2022.19 922.93 1099.26 0.00 0.00
June 2477.95 278.71 2215.83 946.88 1268.95 0.00 0.00
July 2089.72 301.70 1853.21 702.44 1150.77 0.00 0.00
August 1631.76 441.90 1522.88 645.80 877.08 0.00 0.00
September 782.61 765.91 921.12 385.99 535.13 0.00 0.00
October 141.22 1420.73 359.50 107.33 252.16 0.00 0.00
November 15.73 2514.25 143.24 51.40 91.85 0.00 0.00
December 0.00 2816.93 12.86 1.27 11.59 0.00 0.00
               
Annual Sum or Average 990.15 1372.17 1031.26 444.85 586.41 0.00 0.00
Minimum of Months 0.00 278.71 12.86 1.27 11.59 0.00 0.00
Maximum of Months 2477.95 2816.93 2215.83 1079.29 1268.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.113572E+11 0.143147E+09 0.00 0.143147E+09 0.00 0.00
February 0.00 0.933855E+10 0.571542E+09 0.00 0.571542E+09 0.00 0.00
March 90934747.13 0.787420E+10 0.169241E+10 0.00 0.169241E+10 0.00 0.00
April 0.104516E+10 0.420936E+10 0.295949E+10 61457644.22 0.289804E+10 0.00 0.00
May 0.356496E+10 0.181911E+10 0.467899E+10 0.732046E+09 0.394694E+10 0.00 0.00
June 0.588011E+10 0.806679E+09 0.591642E+10 0.130858E+10 0.460784E+10 0.00 0.00
July 0.520125E+10 0.100981E+10 0.512947E+10 0.825703E+09 0.430377E+10 0.00 0.00
August 0.264172E+10 0.172406E+10 0.327517E+10 0.177049E+09 0.309812E+10 0.00 0.00
September 0.585519E+09 0.356022E+10 0.177145E+10 1570278.51 0.176988E+10 0.00 0.00
October 32449635.96 0.690110E+10 0.890808E+09 0.00 0.890808E+09 0.00 0.00
November 0.00 0.109893E+11 0.267531E+09 0.00 0.267531E+09 0.00 0.00
December 0.00 0.120889E+11 43423236.19 0.00 43423236.19 0.00 0.00
               
Annual Sum or Average 0.190421E+11 0.716786E+11 0.273399E+11 0.310641E+10 0.242335E+11 0.00 0.00
Minimum of Months 0.00 0.806679E+09 43423236.19 0.00 43423236.19 0.00 0.00
Maximum of Months 0.588011E+10 0.120889E+11 0.591642E+10 0.130858E+10 0.460784E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 20670761.37 0.731348E+10 0.249156E+09 76875378.28 0.172280E+09 0.00 0.00
February 0.639887E+09 0.559551E+10 0.125169E+10 0.595755E+09 0.655931E+09 0.00 0.00
March 0.332594E+10 0.463991E+10 0.396673E+10 0.201116E+10 0.195557E+10 0.00 0.00
April 0.487861E+10 0.249722E+10 0.527905E+10 0.267501E+10 0.260404E+10 0.00 0.00
May 0.883412E+10 0.130154E+10 0.793527E+10 0.447762E+10 0.345764E+10 0.00 0.00
June 0.816245E+10 0.601831E+09 0.705923E+10 0.329695E+10 0.376227E+10 0.00 0.00
July 0.822047E+10 0.699319E+09 0.693024E+10 0.336456E+10 0.356569E+10 0.00 0.00
August 0.620724E+10 0.111080E+10 0.548760E+10 0.267465E+10 0.281295E+10 0.00 0.00
September 0.304304E+10 0.217342E+10 0.328252E+10 0.143924E+10 0.184328E+10 0.00 0.00
October 0.123831E+10 0.411113E+10 0.178856E+10 0.717184E+09 0.107137E+10 0.00 0.00
November 25678445.92 0.699157E+10 0.365574E+09 0.125941E+09 0.239633E+09 0.00 0.00
December 0.00 0.791638E+10 53726217.66 12364072.45 41362145.21 0.00 0.00
               
Annual Sum or Average 0.445964E+11 0.449521E+11 0.436493E+11 0.214673E+11 0.221820E+11 0.00 0.00
Minimum of Months 0.00 0.601831E+09 53726217.66 12364072.45 41362145.21 0.00 0.00
Maximum of Months 0.883412E+10 0.791638E+10 0.793527E+10 0.447762E+10 0.376227E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.100634E+10 0.100345E+11 0.172866E+10 0.114278E+10 0.585880E+09 0.00 0.00
February 0.456870E+10 0.740421E+10 0.537070E+10 0.374599E+10 0.162471E+10 0.00 0.00
March 0.100690E+11 0.639145E+10 0.101882E+11 0.691881E+10 0.326943E+10 0.00 0.00
April 0.132897E+11 0.411407E+10 0.120019E+11 0.747451E+10 0.452737E+10 0.00 0.00
May 0.116632E+11 0.227128E+10 0.101907E+11 0.527192E+10 0.491874E+10 0.00 0.00
June 0.105989E+11 0.115959E+10 0.899348E+10 0.367069E+10 0.532280E+10 0.00 0.00
July 0.108169E+11 0.126214E+10 0.896172E+10 0.389254E+10 0.506918E+10 0.00 0.00
August 0.110482E+11 0.188541E+10 0.930730E+10 0.513283E+10 0.417447E+10 0.00 0.00
September 0.780918E+10 0.325333E+10 0.729427E+10 0.440131E+10 0.289296E+10 0.00 0.00
October 0.494920E+10 0.555188E+10 0.543823E+10 0.346022E+10 0.197801E+10 0.00 0.00
November 0.185131E+10 0.921748E+10 0.282709E+10 0.197986E+10 0.847229E+09 0.00 0.00
December 88742096.76 0.112659E+11 0.518759E+09 0.366757E+09 0.152002E+09 0.00 0.00
               
Annual Sum or Average 0.877594E+11 0.638113E+11 0.828210E+11 0.474582E+11 0.353628E+11 0.00 0.00
Minimum of Months 88742096.76 0.115959E+10 0.518759E+09 0.366757E+09 0.152002E+09 0.00 0.00
Maximum of Months 0.132897E+11 0.112659E+11 0.120019E+11 0.747451E+10 0.532280E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.765598E+10 0.131257E+09 22613441.04 0.108644E+09 0.00 0.00
February 0.121578E+09 0.608175E+10 0.701618E+09 0.241693E+09 0.459925E+09 0.00 0.00
March 0.125314E+10 0.512362E+10 0.234074E+10 0.100488E+10 0.133586E+10 0.00 0.00
April 0.506658E+10 0.297756E+10 0.538993E+10 0.279753E+10 0.259240E+10 0.00 0.00
May 0.551444E+10 0.148833E+10 0.541626E+10 0.247200E+10 0.294426E+10 0.00 0.00
June 0.637732E+10 0.798576E+09 0.574345E+10 0.245433E+10 0.328912E+10 0.00 0.00
July 0.552193E+10 0.904502E+09 0.496367E+10 0.188143E+10 0.308223E+10 0.00 0.00
August 0.425889E+10 0.137768E+10 0.407890E+10 0.172972E+10 0.234918E+10 0.00 0.00
September 0.189293E+10 0.238218E+10 0.238755E+10 0.100049E+10 0.138705E+10 0.00 0.00
October 0.304399E+09 0.459189E+10 0.962880E+09 0.287482E+09 0.675398E+09 0.00 0.00
November 30053113.00 0.735983E+10 0.371285E+09 0.133219E+09 0.238066E+09 0.00 0.00
December 0.00 0.843131E+10 34456762.24 3414327.02 31042435.22 0.00 0.00
               
Annual Sum or Average 0.303413E+11 0.491732E+11 0.325220E+11 0.140288E+11 0.184932E+11 0.00 0.00
Minimum of Months 0.00 0.798576E+09 34456762.24 3414327.02 31042435.22 0.00 0.00
Maximum of Months 0.637732E+10 0.843131E+10 0.574345E+10 0.279753E+10 0.328912E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.108961E+11 0.143150E+09 0.00 0.143150E+09 0.00 0.00
February 0.00 0.884732E+10 0.571554E+09 0.00 0.571554E+09 0.00 0.00
March 0.133516E+09 0.733114E+10 0.169244E+10 0.00 0.169244E+10 0.00 0.00
April 0.117732E+10 0.384035E+10 0.295955E+10 61459477.06 0.289809E+10 0.00 0.00
May 0.361719E+10 0.175532E+10 0.467909E+10 0.732068E+09 0.394702E+10 0.00 0.00
June 0.589324E+10 0.785592E+09 0.591655E+10 0.130862E+10 0.460794E+10 0.00 0.00
July 0.522415E+10 0.989577E+09 0.512958E+10 0.825728E+09 0.430385E+10 0.00 0.00
August 0.269506E+10 0.165145E+10 0.327524E+10 0.177055E+09 0.309818E+10 0.00 0.00
September 0.648121E+09 0.329115E+10 0.177149E+10 1570325.35 0.176992E+10 0.00 0.00
October 54058950.21 0.630767E+10 0.890826E+09 0.00 0.890826E+09 0.00 0.00
November 0.00 0.103444E+11 0.267537E+09 0.00 0.267537E+09 0.00 0.00
December 0.00 0.114847E+11 43424244.47 0.00 43424244.47 0.00 0.00
               
Annual Sum or Average 0.194426E+11 0.675248E+11 0.273404E+11 0.310650E+10 0.242339E+11 0.00 0.00
Minimum of Months 0.00 0.785592E+09 43424244.47 0.00 43424244.47 0.00 0.00
Maximum of Months 0.589324E+10 0.114847E+11 0.591655E+10 0.130862E+10 0.460794E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 21075318.51 0.704830E+10 0.249155E+09 76875062.93 0.172280E+09 0.00 0.00
February 0.663686E+09 0.534311E+10 0.125168E+10 0.595752E+09 0.655929E+09 0.00 0.00
March 0.337887E+10 0.441187E+10 0.396671E+10 0.201116E+10 0.195556E+10 0.00 0.00
April 0.490904E+10 0.238194E+10 0.527903E+10 0.267500E+10 0.260403E+10 0.00 0.00
May 0.880036E+10 0.127445E+10 0.793524E+10 0.447761E+10 0.345763E+10 0.00 0.00
June 0.812556E+10 0.600626E+09 0.705920E+10 0.329694E+10 0.376226E+10 0.00 0.00
July 0.817482E+10 0.714232E+09 0.693021E+10 0.336454E+10 0.356567E+10 0.00 0.00
August 0.618011E+10 0.111817E+10 0.548758E+10 0.267464E+10 0.281294E+10 0.00 0.00
September 0.306933E+10 0.206487E+10 0.328251E+10 0.143924E+10 0.184327E+10 0.00 0.00
October 0.127831E+10 0.383320E+10 0.178855E+10 0.717181E+09 0.107137E+10 0.00 0.00
November 28606390.38 0.663867E+10 0.365572E+09 0.125940E+09 0.239632E+09 0.00 0.00
December 0.00 0.760274E+10 53725997.27 12364021.73 41361975.53 0.00 0.00
               
Annual Sum or Average 0.446298E+11 0.430322E+11 0.436492E+11 0.214672E+11 0.221819E+11 0.00 0.00
Minimum of Months 0.00 0.600626E+09 53725997.27 12364021.73 41361975.53 0.00 0.00
Maximum of Months 0.880036E+10 0.760274E+10 0.793524E+10 0.447761E+10 0.376226E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.102020E+10 0.980271E+10 0.172871E+10 0.114282E+10 0.585898E+09 0.00 0.00
February 0.461018E+10 0.720313E+10 0.537087E+10 0.374612E+10 0.162475E+10 0.00 0.00
March 0.100917E+11 0.623679E+10 0.101886E+11 0.691904E+10 0.326952E+10 0.00 0.00
April 0.132559E+11 0.404523E+10 0.120022E+11 0.747475E+10 0.452748E+10 0.00 0.00
May 0.116093E+11 0.225741E+10 0.101909E+11 0.527209E+10 0.491885E+10 0.00 0.00
June 0.105625E+11 0.115280E+10 0.899373E+10 0.367081E+10 0.532292E+10 0.00 0.00
July 0.107837E+11 0.127093E+10 0.896196E+10 0.389266E+10 0.506930E+10 0.00 0.00
August 0.110199E+11 0.188358E+10 0.930757E+10 0.513300E+10 0.417458E+10 0.00 0.00
September 0.779424E+10 0.321716E+10 0.729449E+10 0.440145E+10 0.289304E+10 0.00 0.00
October 0.498443E+10 0.537861E+10 0.543840E+10 0.346033E+10 0.197806E+10 0.00 0.00
November 0.189399E+10 0.888521E+10 0.282718E+10 0.197992E+10 0.847254E+09 0.00 0.00
December 91426012.19 0.109237E+11 0.518776E+09 0.366769E+09 0.152007E+09 0.00 0.00
               
Annual Sum or Average 0.877175E+11 0.622572E+11 0.828234E+11 0.474598E+11 0.353637E+11 0.00 0.00
Minimum of Months 91426012.19 0.115280E+10 0.518776E+09 0.366769E+09 0.152007E+09 0.00 0.00
Maximum of Months 0.132559E+11 0.109237E+11 0.120022E+11 0.747475E+10 0.532292E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.724584E+10 0.131257E+09 22613348.27 0.108644E+09 0.00 0.00
February 0.140251E+09 0.562063E+10 0.701615E+09 0.241692E+09 0.459923E+09 0.00 0.00
March 0.133811E+10 0.458066E+10 0.234073E+10 0.100487E+10 0.133586E+10 0.00 0.00
April 0.519321E+10 0.264574E+10 0.538991E+10 0.279752E+10 0.259239E+10 0.00 0.00
May 0.555526E+10 0.141067E+10 0.541623E+10 0.247199E+10 0.294425E+10 0.00 0.00
June 0.642325E+10 0.738510E+09 0.574343E+10 0.245432E+10 0.328911E+10 0.00 0.00
July 0.559670E+10 0.825780E+09 0.496365E+10 0.188142E+10 0.308222E+10 0.00 0.00
August 0.434993E+10 0.122965E+10 0.407888E+10 0.172971E+10 0.234917E+10 0.00 0.00
September 0.196134E+10 0.216499E+10 0.238754E+10 0.100049E+10 0.138705E+10 0.00 0.00
October 0.348453E+09 0.406446E+10 0.962876E+09 0.287481E+09 0.675395E+09 0.00 0.00
November 38028643.24 0.671098E+10 0.371283E+09 0.133218E+09 0.238065E+09 0.00 0.00
December 0.00 0.772796E+10 34456620.89 3414313.01 31042307.88 0.00 0.00
               
Annual Sum or Average 0.309445E+11 0.449659E+11 0.325219E+11 0.140287E+11 0.184931E+11 0.00 0.00
Minimum of Months 0.00 0.738510E+09 34456620.89 3414313.01 31042307.88 0.00 0.00
Maximum of Months 0.642325E+10 0.772796E+10 0.574343E+10 0.279752E+10 0.328911E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.106449E+11 0.143150E+09 0.00 0.143150E+09 0.00 0.00
February 0.00 0.857859E+10 0.571554E+09 0.00 0.571554E+09 0.00 0.00
March 0.159043E+09 0.698027E+10 0.169244E+10 0.00 0.169244E+10 0.00 0.00
April 0.132121E+10 0.351502E+10 0.295955E+10 61459477.06 0.289809E+10 0.00 0.00
May 0.377478E+10 0.164591E+10 0.467909E+10 0.732068E+09 0.394702E+10 0.00 0.00
June 0.591209E+10 0.760137E+09 0.591655E+10 0.130862E+10 0.460794E+10 0.00 0.00
July 0.524540E+10 0.960243E+09 0.512958E+10 0.825728E+09 0.430385E+10 0.00 0.00
August 0.276814E+10 0.156123E+10 0.327524E+10 0.177055E+09 0.309818E+10 0.00 0.00
September 0.773689E+09 0.292583E+10 0.177149E+10 1570325.35 0.176992E+10 0.00 0.00
October 88784537.19 0.585057E+10 0.890826E+09 0.00 0.890826E+09 0.00 0.00
November 0.00 0.100463E+11 0.267537E+09 0.00 0.267537E+09 0.00 0.00
December 0.00 0.112081E+11 43424244.47 0.00 43424244.47 0.00 0.00
               
Annual Sum or Average 0.200431E+11 0.646771E+11 0.273404E+11 0.310650E+10 0.242339E+11 0.00 0.00
Minimum of Months 0.00 0.760137E+09 43424244.47 0.00 43424244.47 0.00 0.00
Maximum of Months 0.591209E+10 0.112081E+11 0.591655E+10 0.130862E+10 0.460794E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 21784711.36 0.689266E+10 0.249155E+09 76875062.93 0.172280E+09 0.00 0.00
February 0.680083E+09 0.517753E+10 0.125168E+10 0.595752E+09 0.655929E+09 0.00 0.00
March 0.344356E+10 0.418887E+10 0.396671E+10 0.201116E+10 0.195556E+10 0.00 0.00
April 0.500772E+10 0.220889E+10 0.527903E+10 0.267500E+10 0.260403E+10 0.00 0.00
May 0.884205E+10 0.122380E+10 0.793524E+10 0.447761E+10 0.345763E+10 0.00 0.00
June 0.812148E+10 0.590609E+09 0.705920E+10 0.329694E+10 0.376226E+10 0.00 0.00
July 0.816968E+10 0.703569E+09 0.693021E+10 0.336454E+10 0.356567E+10 0.00 0.00
August 0.619682E+10 0.108206E+10 0.548758E+10 0.267464E+10 0.281294E+10 0.00 0.00
September 0.315681E+10 0.187951E+10 0.328251E+10 0.143924E+10 0.184327E+10 0.00 0.00
October 0.133305E+10 0.355610E+10 0.178855E+10 0.717181E+09 0.107137E+10 0.00 0.00
November 30446498.91 0.645287E+10 0.365572E+09 0.125940E+09 0.239632E+09 0.00 0.00
December 0.00 0.743599E+10 53725997.27 12364021.73 41361975.53 0.00 0.00
               
Annual Sum or Average 0.450035E+11 0.413925E+11 0.436492E+11 0.214672E+11 0.221819E+11 0.00 0.00
Minimum of Months 0.00 0.590609E+09 53725997.27 12364021.73 41361975.53 0.00 0.00
Maximum of Months 0.884205E+10 0.743599E+10 0.793524E+10 0.447761E+10 0.376226E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.103825E+10 0.956851E+10 0.172871E+10 0.114282E+10 0.585898E+09 0.00 0.00
February 0.468397E+10 0.693053E+10 0.537087E+10 0.374612E+10 0.162475E+10 0.00 0.00
March 0.102112E+11 0.589970E+10 0.101886E+11 0.691904E+10 0.326952E+10 0.00 0.00
April 0.133650E+11 0.377481E+10 0.120022E+11 0.747475E+10 0.452748E+10 0.00 0.00
May 0.116587E+11 0.214510E+10 0.101909E+11 0.527209E+10 0.491885E+10 0.00 0.00
June 0.105604E+11 0.112709E+10 0.899373E+10 0.367081E+10 0.532292E+10 0.00 0.00
July 0.107813E+11 0.124586E+10 0.896196E+10 0.389266E+10 0.506930E+10 0.00 0.00
August 0.110398E+11 0.181708E+10 0.930757E+10 0.513300E+10 0.417458E+10 0.00 0.00
September 0.790978E+10 0.294417E+10 0.729449E+10 0.440145E+10 0.289304E+10 0.00 0.00
October 0.511248E+10 0.497256E+10 0.543840E+10 0.346033E+10 0.197806E+10 0.00 0.00
November 0.193268E+10 0.859648E+10 0.282718E+10 0.197992E+10 0.847254E+09 0.00 0.00
December 93658846.80 0.106619E+11 0.518776E+09 0.366769E+09 0.152007E+09 0.00 0.00
               
Annual Sum or Average 0.883873E+11 0.596838E+11 0.828234E+11 0.474598E+11 0.353637E+11 0.00 0.00
Minimum of Months 93658846.80 0.112709E+10 0.518776E+09 0.366769E+09 0.152007E+09 0.00 0.00
Maximum of Months 0.133650E+11 0.106619E+11 0.120022E+11 0.747475E+10 0.532292E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.707340E+10 0.131257E+09 22613348.27 0.108644E+09 0.00 0.00
February 0.145970E+09 0.545196E+10 0.701615E+09 0.241692E+09 0.459923E+09 0.00 0.00
March 0.137265E+10 0.436794E+10 0.234073E+10 0.100487E+10 0.133586E+10 0.00 0.00
April 0.526865E+10 0.247155E+10 0.538991E+10 0.279752E+10 0.259239E+10 0.00 0.00
May 0.560018E+10 0.134163E+10 0.541623E+10 0.247199E+10 0.294425E+10 0.00 0.00
June 0.642285E+10 0.722426E+09 0.574343E+10 0.245432E+10 0.328911E+10 0.00 0.00
July 0.559710E+10 0.808078E+09 0.496365E+10 0.188142E+10 0.308222E+10 0.00 0.00
August 0.437052E+10 0.118357E+10 0.407888E+10 0.172971E+10 0.234917E+10 0.00 0.00
September 0.202852E+10 0.198523E+10 0.238754E+10 0.100049E+10 0.138705E+10 0.00 0.00
October 0.378255E+09 0.380530E+10 0.962876E+09 0.287481E+09 0.675395E+09 0.00 0.00
November 40760115.41 0.651694E+10 0.371283E+09 0.133218E+09 0.238065E+09 0.00 0.00
December 0.00 0.754487E+10 34456620.89 3414313.01 31042307.88 0.00 0.00
               
Annual Sum or Average 0.312255E+11 0.432729E+11 0.325219E+11 0.140287E+11 0.184931E+11 0.00 0.00
Minimum of Months 0.00 0.722426E+09 34456620.89 3414313.01 31042307.88 0.00 0.00
Maximum of Months 0.642285E+10 0.754487E+10 0.574343E+10 0.279752E+10 0.328911E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January -17.6 -17.9 -19.9 1.62 -32.2 4.20 17.57 0.00
February -15.4 -16.0 -18.9 1.58 -31.2 17.68 68.90 0.00
March -10.3 -11.6 -17.1 2.46 -25.4 47.11 147.56 0.00
April 0.73 -2.7 -8.8 3.74 -14.2 75.81 230.75 0.00
May 10.60 5.25 -1.5 3.99 -2.1 92.54 252.99 0.00
June 15.96 10.88 6.41 3.45 5.66 116.77 222.76 0.00
July 16.86 12.85 9.90 2.85 7.58 107.92 197.90 0.00
August 14.24 10.70 7.59 2.94 4.33 81.01 176.65 0.00
September 6.72 4.45 1.76 2.11 -4.1 51.38 110.92 0.00
October -3.1 -4.4 -7.1 2.79 -14.3 26.50 62.95 0.00
November -17.6 -18.1 -20.3 0.70 -32.8 8.03 31.72 0.00
December -19.3 -19.6 -21.9 1.25 -33.6 1.27 5.23 0.00
                 
Annual Sum or Average -1.4 -3.8 -7.4 2.46 -14.3 52.69 127.40 0.00
Minimum of Months -19.3 -19.6 -21.9 0.70 -33.6 1.27 5.23 0.00
Maximum of Months 16.86 12.85 9.90 3.99 7.58 116.77 252.99 0.00



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -1.1 21-JAN-20:00 -2.7 -5.6 0.00 -9.0 0.00 0.00
February 2.80 08-FEB-15:09 -0.7 -6.5 2.68 -7.9 21.67 32.33
March 6.70 20-MAR-14:09 2.60 -3.5 1.37 -7.5 138.33 487.67
April 15.60 22-APR-13:00 7.03 -3.3 4.10 -0.8 117.50 760.50
May 22.20 31-MAY-15:00 10.79 -1.1 3.10 7.75 143.50 516.50
June 28.30 30-JUN-14:00 17.30 10.60 6.20 17.57 223.50 277.50
July 30.00 29-JUL-16:19 18.34 11.70 4.67 18.88 163.67 322.83
August 25.60 11-AUG-15:00 14.77 6.70 6.20 12.22 99.50 604.00
September 17.20 07-SEP-15:00 8.91 0.00 1.50 2.64 77.00 480.50
October 13.90 01-OCT-14:00 8.01 1.70 2.60 1.58 78.50 227.50
November -3.9 18-NOV-03:00 -5.6 -8.9 1.50 -12.4 0.00 0.00
December 1.70 24-DEC-11:00 -0.1 -2.8 2.60 -8.8 13.50 31.50
                 
Annual Sum or Average                
Minimum of Months -3.9   -5.6 -8.9 0.00 -12.4 0.00 0.00
Maximum of Months 30.00   18.34 11.70 6.20 18.88 223.50 760.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -38.3 12-JAN-05:00 -38.4 -40.4 0.00 -60.9 0.00 0.00
February -36.1 27-FEB-04:00 -36.2 -39.4 0.00 -58.7 0.00 0.00
March -28.9 01-MAR-00:10 -29.2 -34.0 0.65 -51.0 0.00 0.00
April -21.7 03-APR-05:00 -22.3 -27.2 2.60 -42.7 0.00 0.00
May 0.00 27-MAY-03:00 -1.1 -2.8 6.20 -7.1 29.00 14.00
June 3.30 02-JUN-03:00 2.38 1.10 1.50 -11.2 45.50 266.00
July 7.20 31-JUL-03:49 6.67 6.10 2.18 -7.6 0.00 0.00
August -1.7 31-AUG-05:00 -2.9 -5.0 2.60 -18.6 25.00 538.50
September -5.6 29-SEP-06:00 -6.1 -7.2 2.60 -21.6 0.00 0.00
October -20.6 22-OCT-05:00 -20.8 -22.2 2.60 -40.2 0.00 0.00
November -30.0 29-NOV-09:00 -30.2 -33.3 0.00 -51.8 0.00 0.00
December -33.9 15-DEC-07:00 -34.0 -37.8 0.00 -56.5 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -38.3   -38.4 -40.4 0.00 -60.9 0.00 0.00
Maximum of Months 7.20   6.67 6.10 6.20 -7.1 45.50 538.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -2.7 21-JAN-20:00 -1.1 -5.6 0.00 -9.0 0.00 0.00
February 1.24 09-FEB-01:00 2.80 -1.1 8.80 -4.1 0.00 0.00
March 2.65 20-MAR-13:00 6.70 -3.3 0.00 -7.6 139.00 515.00
April 7.03 22-APR-13:00 15.60 -3.3 4.10 -0.8 117.50 760.50
May 10.97 31-MAY-17:00 21.70 0.00 2.60 11.07 73.50 187.00
June 18.33 30-JUN-11:00 25.60 14.40 1.50 15.21 221.00 616.00
July 18.36 29-JUL-17:19 29.07 12.23 3.10 19.29 141.00 225.33
August 16.14 04-AUG-19:00 21.70 12.80 3.10 14.28 25.50 28.50
September 10.82 01-SEP-15:00 15.60 6.70 2.60 4.31 145.50 176.00
October 8.01 01-OCT-14:00 13.90 1.70 2.60 1.58 78.50 227.50
November -5.6 18-NOV-03:00 -3.9 -8.9 1.50 -12.4 0.00 0.00
December -0.1 24-DEC-11:00 1.70 -2.8 2.60 -8.8 13.50 31.50
                 
Annual Sum or Average                
Minimum of Months -5.6   -3.9 -8.9 0.00 -12.4 0.00 0.00
Maximum of Months 18.36   29.07 14.40 8.80 19.29 221.00 760.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -4.4 06-JAN-19:00 -1.7 -2.7 2.60 -12.4 0.00 0.00
February -0.6 09-FEB-00:00 1.70 0.78 3.60 -5.0 0.00 0.00
March 0.00 21-MAR-15:00 1.10 0.62 2.10 -5.5 70.50 4.00
April 0.00 30-APR-07:00 3.30 1.91 2.60 -8.3 198.00 170.00
May 6.10 16-MAY-19:00 8.90 7.49 5.20 3.69 16.00 15.00
June 15.60 30-JUN-17:00 18.90 16.75 3.60 12.22 99.50 223.00
July 17.80 03-JUL-14:00 19.40 18.27 1.50 10.11 223.00 401.50
August 15.00 12-AUG-22:00 16.10 15.38 0.00 12.79 0.00 0.00
September 8.90 04-SEP-11:00 10.00 9.41 2.60 5.33 238.50 0.50
October 5.60 02-OCT-11:09 7.30 6.41 4.95 0.30 123.67 16.00
November -8.3 18-NOV-04:00 -5.0 -6.1 1.50 -13.4 0.00 0.00
December -2.8 24-DEC-09:00 1.10 -0.5 3.10 -6.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -8.3   -5.0 -6.1 0.00 -13.4 0.00 0.00
Maximum of Months 17.80   19.40 18.27 5.20 12.79 238.50 401.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 0.00 1.10 0.00
February 18.00 13.00 16.00 0.00 5.89 0.00
March 18.00 13.00 16.00 0.00 18.25 0.00
April 18.00 13.00 16.00 0.00 35.02 0.00
May 18.00 13.00 16.00 0.44 43.39 0.00
June 18.00 13.00 16.00 2.62 46.67 0.00
July 18.00 13.00 16.00 4.74 42.09 0.00
August 18.00 13.00 16.00 6.08 32.30 0.00
September 18.00 13.00 16.00 6.25 18.21 0.00
October 18.00 13.00 16.00 5.21 8.04 0.00
November 18.00 13.00 16.00 3.27 2.12 0.00
December 18.00 13.00 16.00 0.94 0.28 0.00
             
Annual Sum or Average 18.00 13.00 16.00 2.48 21.19 0.00
Minimum of Months 18.00 13.00 16.00 0.00 0.28 0.00
Maximum of Months 18.00 13.00 16.00 6.25 46.67 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.480322E+11 -0.469734E+11 0.00 0.00 744.00 0.00 -0.105877E+10 58.97 0.00 0.00
February 0.436304E+11 -0.426848E+11 0.00 0.00 672.00 0.00 -945664538.6 58.97 0.00 0.00
March 0.512561E+11 -0.502198E+11 0.00 0.00 744.00 0.00 -0.103630E+10 58.96 0.00 0.00
April 0.465232E+11 -0.455315E+11 0.00 0.00 720.00 0.00 -991758474.8 58.97 0.00 0.00
May 0.492837E+11 -0.482594E+11 0.00 0.00 744.00 0.00 -0.102436E+10 58.97 0.00 0.00
June 0.470782E+11 -0.460862E+11 0.00 0.00 720.00 0.00 -992052133.5 58.99 0.00 0.00
July 0.431843E+11 -0.421653E+11 0.00 0.00 744.00 0.00 -0.101906E+10 58.99 0.00 0.00
August 0.460683E+11 -0.450450E+11 0.00 0.00 744.00 0.00 -0.102332E+10 58.99 0.00 0.00
September 0.417026E+11 -0.407130E+11 0.00 0.00 720.00 0.00 -989561614.3 58.99 0.00 0.00
October 0.438573E+11 -0.428325E+11 0.00 0.00 744.00 0.00 -0.102480E+10 58.98 0.00 0.00
November 0.445465E+11 -0.435385E+11 0.00 0.00 720.00 0.00 -0.100797E+10 58.98 0.00 0.00
December 0.461819E+11 -0.451244E+11 0.00 0.00 744.00 0.00 -0.105754E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.551345E+12 -0.539174E+12 0.00 0.00 8760.00 0.00 -0.121712E+11 58.98 0.00 0.00
Minimum of Months 0.417026E+11 -0.502198E+11 0.00 0.00 672.00 0.00 -0.105877E+10 58.96 0.00 0.00
Maximum of Months 0.512561E+11 -0.407130E+11 0.00 0.00 744.00 0.00 -945664538.6 58.99 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.65 0.48 10-JAN-11:20 433.30 9.03 0.00 48.33 349.45 14.92 5.50 30.00
February 205.83 0.55 0.48 01-FEB-12:09 1059.34 13.15 0.00 159.67 1813.59 31.94 157.50 139.50
March 329.50 0.52 0.48 01-MAR-09:20 4954.74 31.18 267.50 291.33 4462.78 33.44 280.67 271.83
April 421.83 0.53 0.48 01-APR-07:00 7255.49 29.89 283.67 365.33 1267.71 20.53 223.50 316.33
May 545.00 0.55 0.48 01-MAY-06:40 4067.53 20.92 144.67 428.50 924.92 19.18 221.33 361.17
June 583.50 0.55 0.48 01-JUN-05:40 1568.73 15.89 0.00 448.33 850.65 18.91 234.00 371.67
July 562.83 0.55 0.48 01-JUL-05:10 1908.23 16.57 15.67 444.50 869.13 18.99 230.33 366.50
August 467.17 0.53 0.48 01-AUG-06:10 5169.07 25.32 239.83 388.00 980.28 19.64 200.33 327.00
September 356.33 0.53 0.48 01-SEP-06:00 4094.35 29.13 262.50 306.83 1345.90 21.10 173.67 258.17
October 265.50 0.53 0.48 01-OCT-08:09 2105.20 26.23 170.17 221.33 1843.03 31.35 216.50 196.50
November 135.83 0.58 0.48 01-NOV-10:09 546.77 10.99 0.00 95.33 479.22 20.91 35.83 59.83
December 71.17 0.83 0.50 08-DEC-12:09 128.87 4.43 0.00 0.00 93.30 9.11 0.00 0.00
                         
Annual Sum or Average 4053.17 0.55     3375.30 21.60 1384.00 3197.50 1333.46 21.85 1979.17 2698.50
Minimum of Months 71.17 0.52 0.48   128.87 4.43 0.00 0.00 93.30 9.11 0.00 0.00
Maximum of Months 583.50 0.83 0.50   7255.49 31.18 283.67 448.33 4462.78 33.44 280.67 371.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.76 0.48 23-JAN-11:20 205.45 9.32 1.67 15.83 137.48 12.21 1.83 7.00
February 205.83 0.61 0.48 02-FEB-10:30 750.83 16.25 45.50 121.67 454.78 19.08 50.83 71.00
March 329.50 0.55 0.48 01-MAR-09:20 1774.35 18.81 83.17 260.17 1198.38 22.20 130.50 209.33
April 421.83 0.52 0.48 01-APR-06:00 2253.63 19.14 80.83 364.00 1549.62 24.14 189.00 317.67
May 545.00 0.54 0.48 01-MAY-04:40 3285.79 20.49 150.17 437.17 1713.40 22.64 205.83 382.50
June 583.50 0.54 0.48 01-JUN-04:19 2868.82 20.30 167.00 469.00 1239.89 21.79 235.33 398.83
July 562.83 0.54 0.48 01-JUL-04:10 2784.83 19.48 144.67 455.17 1478.27 22.42 237.50 388.17
August 467.17 0.54 0.48 01-AUG-05:10 2248.14 19.33 116.17 387.83 1143.47 21.61 183.67 326.33
September 356.33 0.55 0.48 01-SEP-06:30 1737.63 19.07 104.00 279.50 923.33 21.22 131.17 217.67
October 265.50 0.57 0.48 01-OCT-07:00 890.99 17.20 64.50 189.17 546.85 20.21 74.83 119.17
November 135.83 0.70 0.48 01-NOV-10:20 277.69 10.64 0.00 41.00 151.75 13.96 0.00 3.83
December 71.17 0.91 0.70 04-DEC-11:30 74.77 4.88 0.00 0.00 43.82 7.08 0.00 0.00
                         
Annual Sum or Average 4053.17 0.56     2144.82 18.45 957.67 3020.50 1154.29 21.18 1440.50 2441.50
Minimum of Months 71.17 0.52 0.48   74.77 4.88 0.00 0.00 43.82 7.08 0.00 0.00
Maximum of Months 583.50 0.91 0.70   3285.79 20.49 167.00 469.00 1713.40 24.14 237.50 398.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.84 0.54 31-JAN-11:30 130.35 6.05 0.00 0.50 76.15 9.15 0.00 0.00
February 205.83 0.67 0.48 19-FEB-11:30 287.94 10.24 0.00 57.33 170.24 13.46 0.00 1.00
March 329.50 0.56 0.48 01-MAR-10:50 532.59 13.59 0.00 242.00 316.40 16.75 0.00 120.50
April 421.83 0.52 0.48 01-APR-08:20 691.77 15.82 0.00 375.50 435.76 18.99 2.83 287.50
May 545.00 0.52 0.48 01-MAY-04:49 849.87 19.05 103.50 486.83 499.94 20.53 85.67 415.17
June 583.50 0.52 0.48 01-JUN-04:30 1032.39 19.49 123.83 515.67 587.38 21.99 155.50 471.67
July 562.83 0.52 0.48 01-JUL-04:10 913.28 18.43 92.67 500.17 532.63 21.61 132.17 429.83
August 467.17 0.52 0.48 01-AUG-05:49 728.91 17.76 62.00 404.67 433.40 20.50 72.33 312.67
September 356.33 0.56 0.48 01-SEP-06:00 523.39 13.72 0.00 270.17 301.71 16.70 0.00 115.50
October 265.50 0.61 0.48 01-OCT-08:00 367.07 11.77 0.00 135.83 202.52 14.76 0.00 3.17
November 135.83 0.78 0.52 06-NOV-13:30 175.10 7.71 0.00 5.50 100.58 11.11 0.00 0.00
December 71.17 0.94 0.82 04-DEC-11:30 51.13 2.02 0.00 0.00 30.27 4.46 0.00 0.00
                         
Annual Sum or Average 4053.17 0.56     683.97 15.68 382.00 2994.17 401.15 18.44 448.50 2157.00
Minimum of Months 71.17 0.52 0.48   51.13 2.02 0.00 0.00 30.27 4.46 0.00 0.00
Maximum of Months 583.50 0.94 0.82   1032.39 19.49 123.83 515.67 587.38 21.99 155.50 471.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.78 0.48 28-JAN-13:20 176.37 8.97 1.33 8.33 113.92 11.94 1.33 2.33
February 205.83 0.60 0.48 09-FEB-14:09 610.46 16.49 44.50 120.67 363.14 19.43 46.67 56.83
March 329.50 0.53 0.48 01-MAR-10:50 1375.23 18.60 74.67 271.50 858.81 21.95 105.83 214.50
April 421.83 0.52 0.48 01-APR-09:39 2727.34 20.62 111.00 364.50 1381.40 22.95 168.00 314.67
May 545.00 0.53 0.48 01-MAY-06:00 2166.55 19.15 117.83 452.00 1107.14 20.58 156.67 396.50
June 583.50 0.53 0.48 01-JUN-05:00 2371.61 18.65 111.00 478.67 1201.26 20.29 157.33 411.00
July 562.83 0.53 0.48 01-JUL-05:30 2040.42 18.60 114.67 470.00 1056.65 20.19 171.17 400.00
August 467.17 0.52 0.48 01-AUG-06:49 1836.58 19.58 114.33 398.00 1128.42 21.89 160.00 330.17
September 356.33 0.54 0.48 01-SEP-07:40 1463.68 19.80 100.00 295.17 912.39 22.98 116.83 221.50
October 265.50 0.56 0.48 01-OCT-09:09 719.00 17.44 67.00 188.83 428.10 20.46 62.17 87.17
November 135.83 0.69 0.48 01-NOV-12:00 293.41 14.62 33.83 43.83 184.20 16.91 33.83 12.67
December 71.17 0.92 0.77 04-DEC-11:30 65.40 4.36 0.00 0.00 37.88 6.67 0.00 0.00
                         
Annual Sum or Average 4053.17 0.55     1745.90 18.28 890.17 3091.50 948.77 20.54 1179.83 2447.33
Minimum of Months 71.17 0.52 0.48   65.40 4.36 0.00 0.00 37.88 6.67 0.00 0.00
Maximum of Months 583.50 0.92 0.77   2727.34 20.62 117.83 478.67 1381.40 22.98 171.17 411.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.65 0.48 10-JAN-11:20 417.06 2.37 0.00 45.00 356.61 8.88 5.50 30.00
February 205.83 0.56 0.48 01-FEB-12:09 1030.39 5.79 0.00 158.67 1836.45 30.56 154.33 140.00
March 329.50 0.52 0.48 01-MAR-09:20 4886.16 30.19 264.17 287.50 4505.65 32.79 275.50 272.33
April 421.83 0.53 0.48 01-APR-07:00 7210.04 28.17 283.50 363.50 1312.37 16.08 0.00 318.00
May 545.00 0.55 0.48 01-MAY-06:40 4036.63 16.98 144.17 425.50 956.79 15.02 0.00 364.50
June 583.50 0.55 0.48 01-JUN-05:40 1532.16 9.99 0.00 445.33 876.93 14.65 0.00 375.83
July 562.83 0.55 0.48 01-JUL-05:10 1871.27 10.78 15.67 440.67 896.27 14.67 0.00 370.17
August 467.17 0.53 0.48 01-AUG-06:10 5129.09 22.69 236.33 386.17 1012.96 15.11 0.00 329.83
September 356.33 0.53 0.48 01-SEP-06:00 3711.16 25.93 237.83 305.17 1376.47 16.70 26.00 260.17
October 265.50 0.53 0.48 01-OCT-08:09 1034.59 7.25 0.00 219.00 1844.24 29.64 206.17 197.50
November 135.83 0.58 0.48 01-NOV-10:09 524.91 3.74 0.00 93.33 408.66 9.73 0.00 57.00
December 71.17 0.85 0.51 08-DEC-12:09 117.59 0.24 0.00 0.00 91.95 3.45 0.00 0.00
                         
Annual Sum or Average 4053.17 0.55     3239.18 16.46 1181.67 3169.83 1358.93 17.84 667.50 2715.33
Minimum of Months 71.17 0.52 0.48   117.59 0.24 0.00 0.00 91.95 3.45 0.00 0.00
Maximum of Months 583.50 0.85 0.51   7210.04 30.19 283.50 445.33 4505.65 32.79 275.50 375.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.76 0.48 23-JAN-11:20 201.00 6.07 0.00 14.83 140.15 10.62 1.67 7.00
February 205.83 0.61 0.48 02-FEB-10:30 621.21 9.03 0.00 120.50 464.94 17.41 46.50 73.50
March 329.50 0.55 0.48 01-MAR-09:20 1757.14 15.81 79.83 259.50 1222.68 20.34 88.00 212.50
April 421.83 0.52 0.48 01-APR-06:00 2249.16 15.81 80.83 362.67 1579.52 22.13 106.33 322.67
May 545.00 0.54 0.48 01-MAY-04:40 3034.40 15.90 117.83 435.83 1747.44 20.39 118.50 387.50
June 583.50 0.54 0.48 01-JUN-04:19 2747.85 16.23 137.00 466.83 1268.70 19.45 111.00 405.33
July 562.83 0.54 0.48 01-JUL-04:10 2779.70 16.45 143.33 453.50 1507.64 20.25 138.50 393.50
August 467.17 0.54 0.48 01-AUG-05:10 2241.62 16.24 115.17 387.33 1170.20 19.23 85.83 330.50
September 356.33 0.55 0.48 01-SEP-06:30 1729.44 16.30 102.33 279.33 917.88 18.87 76.00 222.33
October 265.50 0.57 0.48 01-OCT-07:00 884.84 14.33 62.83 188.17 512.99 17.10 51.17 122.33
November 135.83 0.70 0.48 01-NOV-10:20 273.52 7.23 0.00 39.67 184.85 16.23 34.50 9.17
December 71.17 0.91 0.70 04-DEC-11:30 73.19 3.06 0.00 0.00 44.69 6.24 0.00 0.00
                         
Annual Sum or Average 4053.17 0.56     2082.28 14.85 839.17 3008.17 1174.27 19.13 858.00 2486.33
Minimum of Months 71.17 0.52 0.48   73.19 3.06 0.00 0.00 44.69 6.24 0.00 0.00
Maximum of Months 583.50 0.91 0.70   3034.40 16.45 143.33 466.83 1747.44 22.13 138.50 405.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.84 0.54 31-JAN-11:30 125.79 1.22 0.00 0.17 77.29 4.90 0.00 0.00
February 205.83 0.67 0.48 19-FEB-11:20 279.39 4.58 0.00 51.50 173.53 9.27 0.00 2.17
March 329.50 0.56 0.48 01-MAR-10:50 519.71 8.14 0.00 238.67 323.92 13.03 0.00 130.50
April 421.83 0.52 0.48 01-APR-08:09 677.31 10.71 0.00 372.67 446.98 15.81 0.00 293.50
May 545.00 0.51 0.48 01-MAY-04:49 833.68 14.75 102.33 484.33 531.02 19.12 98.67 436.67
June 583.50 0.52 0.48 01-JUN-04:30 969.62 14.03 96.33 514.50 601.93 18.79 95.33 474.67
July 562.83 0.52 0.48 01-JUL-03:00 894.61 13.79 87.67 497.33 546.41 18.48 88.17 433.33
August 467.17 0.52 0.48 01-AUG-05:40 709.92 11.53 34.67 400.33 444.48 17.45 64.50 320.50
September 356.33 0.56 0.48 01-SEP-06:00 511.22 8.18 0.00 267.50 309.21 12.96 0.00 126.00
October 265.50 0.61 0.48 01-OCT-08:50 357.70 5.70 0.00 129.67 207.29 10.47 0.00 4.17
November 135.83 0.79 0.52 06-NOV-13:30 169.41 2.04 0.00 5.00 102.30 6.56 0.00 0.00
December 71.17 0.94 0.82 04-DEC-11:30 49.13 0.01 0.00 0.00 30.62 1.35 0.00 0.00
                         
Annual Sum or Average 4053.17 0.56     662.96 10.45 321.00 2961.67 413.63 15.23 346.67 2221.50
Minimum of Months 71.17 0.51 0.48   49.13 0.01 0.00 0.00 30.62 1.35 0.00 0.00
Maximum of Months 583.50 0.94 0.82   969.62 14.75 102.33 514.50 601.93 19.12 98.67 474.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.78 0.48 28-JAN-13:20 173.50 5.91 1.33 7.50 116.28 10.25 1.33 2.33
February 205.83 0.60 0.48 05-FEB-13:30 606.07 13.86 44.17 120.00 371.16 17.67 45.33 58.00
March 329.50 0.53 0.48 01-MAR-10:39 1371.65 15.85 72.67 270.33 877.55 20.11 71.17 221.00
April 421.83 0.52 0.48 01-APR-09:39 2725.58 17.62 111.00 363.17 1410.97 20.70 81.67 318.67
May 545.00 0.53 0.48 01-MAY-06:00 2161.71 15.98 117.50 451.00 1132.56 17.91 56.50 400.33
June 583.50 0.53 0.48 01-JUN-05:00 2363.97 15.31 110.00 477.33 1226.20 17.56 53.17 416.33
July 562.83 0.53 0.48 01-JUL-05:19 2033.31 15.34 113.83 469.33 1070.62 17.50 56.17 401.67
August 467.17 0.52 0.48 01-AUG-06:49 1811.42 16.35 110.50 396.67 1140.79 19.37 85.00 335.83
September 356.33 0.54 0.48 01-SEP-07:40 1354.26 15.09 77.33 293.17 899.15 19.61 76.83 222.67
October 265.50 0.56 0.48 01-OCT-09:09 708.78 14.10 59.83 187.33 437.04 18.59 62.17 94.17
November 135.83 0.70 0.48 01-NOV-12:00 261.16 7.19 0.00 37.00 188.28 15.96 34.00 13.33
December 71.17 0.92 0.78 04-DEC-11:30 64.14 2.49 0.00 0.00 38.65 5.75 0.00 0.00
                         
Annual Sum or Average 4053.17 0.55     1728.09 14.89 818.17 3072.83 963.79 18.14 623.33 2484.33
Minimum of Months 71.17 0.52 0.48   64.14 2.49 0.00 0.00 38.65 5.75 0.00 0.00
Maximum of Months 583.50 0.92 0.78   2725.58 17.62 117.50 477.33 1410.97 20.70 85.00 416.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.65 0.48 10-JAN-11:20 416.54 2.34 0.00 44.83 356.63 8.86 5.50 30.00
February 205.83 0.56 0.48 01-FEB-12:09 1029.17 5.75 0.00 158.67 1836.66 30.55 154.33 140.00
March 329.50 0.52 0.48 01-MAR-09:20 4884.64 30.17 264.17 287.50 4506.70 32.79 275.50 272.33
April 421.83 0.53 0.48 01-APR-07:00 7209.47 28.15 283.50 363.50 1313.82 16.06 0.00 318.00
May 545.00 0.55 0.48 01-MAY-06:40 4037.05 16.95 144.17 425.50 957.90 15.00 0.00 364.67
June 583.50 0.55 0.48 01-JUN-05:40 1532.84 9.95 0.00 445.33 878.06 14.64 0.00 375.83
July 562.83 0.55 0.48 01-JUL-05:10 1871.91 10.75 15.67 440.67 897.44 14.65 0.00 370.33
August 467.17 0.53 0.48 01-AUG-06:10 5129.27 22.67 236.17 386.17 1014.22 15.10 0.00 329.83
September 356.33 0.53 0.48 01-SEP-06:00 3710.48 25.91 237.83 305.17 1377.61 16.69 26.00 260.17
October 265.50 0.53 0.48 01-OCT-08:09 1033.89 7.20 0.00 219.00 1844.84 29.63 206.17 197.50
November 135.83 0.58 0.48 01-NOV-10:09 524.29 3.70 0.00 93.33 408.75 9.71 0.00 57.00
December 71.17 0.85 0.51 08-DEC-12:09 117.37 0.23 0.00 0.00 91.94 3.43 0.00 0.00
                         
Annual Sum or Average 4053.17 0.55     3239.05 16.43 1181.50 3169.67 1359.94 17.82 667.50 2715.67
Minimum of Months 71.17 0.52 0.48   117.37 0.23 0.00 0.00 91.94 3.43 0.00 0.00
Maximum of Months 583.50 0.85 0.51   7209.47 30.17 283.50 445.33 4506.70 32.79 275.50 375.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.76 0.48 23-JAN-11:20 200.88 6.03 0.00 14.83 140.28 10.60 1.67 7.00
February 205.83 0.61 0.48 02-FEB-10:30 620.89 8.98 0.00 120.50 465.23 17.39 46.50 73.83
March 329.50 0.55 0.48 01-MAR-09:20 1756.48 15.77 79.83 259.50 1223.25 20.32 87.83 212.50
April 421.83 0.52 0.48 01-APR-06:00 2248.31 15.76 80.83 362.67 1580.27 22.11 106.33 322.67
May 545.00 0.54 0.48 01-MAY-04:40 3033.68 15.86 117.83 435.83 1748.28 20.37 118.50 387.67
June 583.50 0.54 0.48 01-JUN-04:19 2747.53 16.19 136.83 467.00 1269.67 19.44 111.00 405.50
July 562.83 0.54 0.48 01-JUL-04:10 2779.31 16.41 143.33 453.50 1508.58 20.23 138.50 393.67
August 467.17 0.54 0.48 01-AUG-04:00 2241.22 16.20 115.17 387.33 1171.04 19.21 85.83 330.83
September 356.33 0.55 0.48 01-SEP-06:30 1728.98 16.27 102.33 279.17 918.52 18.86 76.00 222.33
October 265.50 0.57 0.48 01-OCT-07:00 884.65 14.29 62.83 188.17 513.42 17.08 51.17 122.67
November 135.83 0.70 0.48 01-NOV-10:20 273.40 7.19 0.00 39.67 185.01 16.22 34.50 9.17
December 71.17 0.91 0.70 04-DEC-11:30 73.13 3.03 0.00 0.00 44.73 6.22 0.00 0.00
                         
Annual Sum or Average 4053.17 0.56     2081.82 14.81 839.00 3008.17 1174.99 19.11 857.83 2487.83
Minimum of Months 71.17 0.52 0.48   73.13 3.03 0.00 0.00 44.73 6.22 0.00 0.00
Maximum of Months 583.50 0.91 0.70   3033.68 16.41 143.33 467.00 1748.28 22.11 138.50 405.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.84 0.54 31-JAN-11:30 125.75 1.20 0.00 0.17 77.36 4.88 0.00 0.00
February 205.83 0.67 0.48 19-FEB-11:20 279.32 4.54 0.00 51.33 173.69 9.25 0.00 2.17
March 329.50 0.56 0.48 01-MAR-10:50 519.62 8.10 0.00 238.67 324.23 13.01 0.00 131.00
April 421.83 0.52 0.48 01-APR-08:09 677.07 10.67 0.00 372.67 447.34 15.79 0.00 293.67
May 545.00 0.51 0.48 01-MAY-04:49 833.46 14.71 102.33 484.33 531.44 19.10 98.67 436.67
June 583.50 0.52 0.48 01-JUN-04:19 969.45 13.99 96.33 514.50 602.45 18.78 95.33 474.83
July 562.83 0.52 0.48 01-JUL-03:00 894.53 13.76 87.67 497.33 546.93 18.47 88.17 433.67
August 467.17 0.52 0.48 01-AUG-05:40 709.88 11.49 34.67 400.17 444.92 17.44 64.50 321.00
September 356.33 0.56 0.48 01-SEP-06:00 511.20 8.14 0.00 267.50 309.54 12.94 0.00 126.50
October 265.50 0.61 0.48 01-OCT-08:50 357.75 5.66 0.00 129.33 207.54 10.45 0.00 4.17
November 135.83 0.79 0.52 06-NOV-13:30 169.38 2.01 0.00 5.00 102.40 6.54 0.00 0.00
December 71.17 0.94 0.82 04-DEC-11:30 49.10 0.00 0.00 0.00 30.64 1.34 0.00 0.00
                         
Annual Sum or Average 4053.17 0.56     662.85 10.41 321.00 2961.00 414.01 15.21 346.67 2223.67
Minimum of Months 71.17 0.51 0.48   49.10 0.00 0.00 0.00 30.64 1.34 0.00 0.00
Maximum of Months 583.50 0.94 0.82   969.45 14.71 102.33 514.50 602.45 19.10 98.67 474.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.78 0.48 28-JAN-13:20 173.42 5.87 1.33 7.50 116.38 10.24 1.33 2.50
February 205.83 0.60 0.48 05-FEB-13:30 605.86 13.83 44.00 119.83 371.41 17.66 45.33 58.00
March 329.50 0.53 0.48 01-MAR-10:39 1371.31 15.81 72.67 270.50 878.04 20.10 70.83 221.17
April 421.83 0.52 0.48 01-APR-09:39 2724.72 17.58 111.00 363.17 1411.68 20.68 81.67 318.83
May 545.00 0.53 0.48 01-MAY-06:00 2161.32 15.94 117.50 451.00 1133.29 17.90 56.50 400.50
June 583.50 0.53 0.48 01-JUN-05:00 2363.73 15.27 110.00 477.17 1227.03 17.54 53.17 416.67
July 562.83 0.53 0.48 01-JUL-05:19 2033.16 15.30 113.67 469.17 1071.46 17.48 56.17 401.83
August 467.17 0.52 0.48 01-AUG-06:49 1811.21 16.31 110.50 396.67 1141.50 19.36 85.00 336.17
September 356.33 0.54 0.48 01-SEP-07:40 1353.99 15.05 77.33 293.17 899.68 19.60 76.83 223.00
October 265.50 0.56 0.48 01-OCT-09:09 708.71 14.07 59.67 187.50 437.40 18.58 62.17 94.50
November 135.83 0.70 0.48 01-NOV-12:00 261.04 7.14 0.00 37.00 188.44 15.95 34.00 13.33
December 71.17 0.92 0.78 04-DEC-11:30 64.10 2.46 0.00 0.00 38.69 5.73 0.00 0.00
                         
Annual Sum or Average 4053.17 0.55     1727.80 14.85 817.67 3072.67 964.41 18.12 623.00 2486.50
Minimum of Months 71.17 0.52 0.48   64.10 2.46 0.00 0.00 38.69 5.73 0.00 0.00
Maximum of Months 583.50 0.92 0.78   2724.72 17.58 117.50 477.17 1411.68 20.68 85.00 416.67



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.209736E+11 95581.51 12-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.122177E+11 87835.71 27-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.369491E+10 76207.17 01-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.458419E+09 36356.89 04-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 28572665.10 13480.35 27-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 101.99 0.16 09-JUN-20:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 19769940.67 16014.38 31-AUG-06:10 0.00 0.00 0.00 0.00 0.00
September 0.197919E+09 18471.47 25-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.396684E+09 36900.40 23-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.184742E+11 76659.14 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.302783E+11 85476.12 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.867400E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.302783E+11 95581.51   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.397486E+10 12563.10 18-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.187758E+10 13472.80 14-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.717413E+09 13530.33 14-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 15368540.94 2064.32 03-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.186822E+09 13476.09 27-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.178206E+10 12515.00 27-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.322533E+10 12515.31 01-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.117794E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.397486E+10 13530.33   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.363085E+10 14751.39 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.173022E+10 15111.59 14-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.589811E+09 15135.65 16-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 28888499.63 5977.89 03-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 865225.15 292.60 30-SEP-07:00 0.00 0.00 0.00 0.00 0.00
October 0.293281E+09 15115.78 27-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.232252E+10 15136.98 03-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.377645E+10 14722.48 11-DEC-05:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.123729E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.377645E+10 15136.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.578620E+10 23035.43 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.236092E+10 23599.23 08-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.812515E+09 23701.15 13-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 52265857.69 16220.46 03-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 17824485.58 2169.03 28-SEP-05:08 0.00 0.00 0.00 0.00 0.00
October 0.541482E+09 23667.68 23-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.329035E+10 23650.88 02-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.579752E+10 23004.29 11-DEC-05:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.186591E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.579752E+10 23701.15   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.196968E+10 13644.01 30-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.461414E+09 13624.97 27-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 60270652.49 13619.72 02-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 8492152.44 2550.80 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.161836E+09 13619.89 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.199908E+09 13616.77 15-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.286160E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196968E+10 13644.01   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.250526E+12 1025975.90 12-JAN-07:03 0.00 0.00 0.00 0.00 0.00
February 0.145326E+12 959528.72 27-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.447481E+11 810761.08 01-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 0.551122E+10 401019.28 04-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.499227E+09 148135.19 27-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 2326720.55 3871.09 02-JUN-06:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.509227E+09 194993.96 31-AUG-06:10 0.00 0.00 0.00 0.00 0.00
September 0.311138E+10 210520.93 25-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.748914E+10 412216.81 23-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.217141E+12 809565.52 29-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.353103E+12 911531.54 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.102797E+13     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.353103E+12 1025975.90   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.571846E+11 547049.40 02-JAN-04:43 0.00 0.00 0.00 0.00 0.00
February 0.202242E+11 546894.45 06-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.290821E+10 545338.23 06-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.141493E+10 545438.44 30-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.246094E+11 546734.08 13-NOV-06:05 0.00 0.00 0.00 0.00 0.00
December 0.411090E+11 546683.28 06-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.147450E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.571846E+11 547049.40   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.110138E+12 117697.42 20-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.744685E+11 117648.78 07-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.489208E+11 117342.44 06-MAR-06:04 0.00 0.00 0.00 0.00 0.00
April 0.788882E+10 116977.58 05-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.155128E+10 116383.55 28-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.284984E+11 117370.63 30-OCT-05:04 0.00 0.00 0.00 0.00 0.00
November 0.879122E+11 117617.31 15-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.109324E+12 117655.33 26-DEC-05:14 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.468702E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.110138E+12 117697.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.824694E+11 172490.73 06-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.509615E+11 172577.89 13-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.243288E+11 172380.26 02-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.411186E+10 171307.01 08-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.116838E+10 105778.56 30-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.206890E+11 172305.23 30-OCT-03:03 0.00 0.00 0.00 0.00 0.00
November 0.668649E+11 172487.90 22-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.829503E+11 172495.48 30-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.333544E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.829503E+11 172577.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.106979E+12 258531.74 06-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.529533E+11 258380.64 01-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.244237E+11 258366.17 02-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.340325E+10 255355.38 05-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.114535E+10 99478.32 28-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.210082E+11 257201.04 30-OCT-04:22 0.00 0.00 0.00 0.00 0.00
November 0.777778E+11 258527.50 22-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.114975E+12 258538.85 30-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.402666E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.114975E+12 258538.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.711831E+11 169478.38 18-JAN-05:02 0.00 0.00 0.00 0.00 0.00
February 0.433103E+11 169414.33 01-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.250758E+11 169405.25 02-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.265426E+10 168689.31 04-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.109755E+10 75271.78 30-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.180773E+11 169248.00 28-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.524717E+11 169349.50 27-NOV-05:24 0.00 0.00 0.00 0.00 0.00
December 0.664149E+11 169419.13 02-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.280285E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.711831E+11 169478.38   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.354365E+11 114239.25 12-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.215274E+11 101230.17 27-FEB-08:10 0.00 0.00 0.00 0.00 0.00
March 0.768192E+10 90477.06 01-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 0.756715E+09 45347.53 04-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 77977829.10 19041.90 27-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 1903402.42 2877.86 02-JUN-06:10 0.00 0.00 0.00 0.00 0.00
July 35379.67 34.96 05-JUL-07:00 0.00 0.00 0.00 0.00 0.00
August 51783902.45 24313.70 31-AUG-06:10 0.00 0.00 0.00 0.00 0.00
September 0.200257E+09 26150.77 25-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.248603E+10 44135.42 23-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.316254E+11 90366.76 29-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.459002E+11 101396.98 15-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.145746E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 35379.67 34.96   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.459002E+11 114239.25   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.289424E+11 72967.29 20-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.195223E+11 72844.84 07-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.127055E+11 72912.87 20-MAR-05:05 0.00 0.00 0.00 0.00 0.00
April 0.305291E+10 72674.16 04-APR-05:04 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.966454E+09 72989.47 25-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.980144E+10 72996.31 10-OCT-04:45 0.00 0.00 0.00 0.00 0.00
November 0.240932E+11 72717.15 02-NOV-05:04 0.00 0.00 0.00 0.00 0.00
December 0.284514E+11 72719.19 26-DEC-05:54 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.127536E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.289424E+11 72996.31   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.193880E+11 15421.70 20-JAN-05:23 0.00 0.00 0.00 0.00 0.00
February 0.151272E+11 15420.19 04-FEB-05:33 0.00 0.00 0.00 0.00 0.00
March 0.119799E+11 15424.47 20-MAR-04:44 0.00 0.00 0.00 0.00 0.00
April 0.373545E+10 15371.10 01-APR-05:05 0.00 0.00 0.00 0.00 0.00
May 85607188.92 15240.36 27-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 59759826.85 15209.67 31-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.192703E+10 15381.54 25-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.882333E+10 15444.14 20-OCT-05:04 0.00 0.00 0.00 0.00 0.00
November 0.174432E+11 15421.73 02-NOV-04:23 0.00 0.00 0.00 0.00 0.00
December 0.200623E+11 15417.52 20-DEC-05:33 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.986318E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.200623E+11 15444.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.132846E+11 17264.35 28-JAN-05:24 0.00 0.00 0.00 0.00 0.00
February 0.953892E+10 17306.13 10-FEB-05:03 0.00 0.00 0.00 0.00 0.00
March 0.575648E+10 17293.90 10-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.159051E+10 17268.24 01-APR-04:03 0.00 0.00 0.00 0.00 0.00
May 27480929.61 7727.07 27-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 18308963.80 9339.08 31-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.877731E+09 17242.88 28-SEP-04:02 0.00 0.00 0.00 0.00 0.00
October 0.524480E+10 17353.59 02-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.119040E+11 17210.95 08-NOV-05:53 0.00 0.00 0.00 0.00 0.00
December 0.139105E+11 17206.89 06-DEC-05:33 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.621532E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.139105E+11 17353.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.184763E+11 26946.78 05-JAN-05:23 0.00 0.00 0.00 0.00 0.00
February 0.113080E+11 26968.18 02-FEB-05:43 0.00 0.00 0.00 0.00 0.00
March 0.675047E+10 27014.76 09-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.185018E+10 26776.35 01-APR-04:02 0.00 0.00 0.00 0.00 0.00
May 83343564.31 13798.55 27-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 34256382.74 7958.81 30-AUG-05:03 0.00 0.00 0.00 0.00 0.00
September 0.114443E+10 26970.92 28-SEP-04:02 0.00 0.00 0.00 0.00 0.00
October 0.644620E+10 26968.98 10-OCT-04:43 0.00 0.00 0.00 0.00 0.00
November 0.154919E+11 26957.08 08-NOV-05:53 0.00 0.00 0.00 0.00 0.00
December 0.202329E+11 26947.02 29-DEC-05:33 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.818179E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.202329E+11 27014.76   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.122369E+11 18147.72 10-JAN-05:43 0.00 0.00 0.00 0.00 0.00
February 0.834248E+10 18152.19 24-FEB-05:53 0.00 0.00 0.00 0.00 0.00
March 0.574398E+10 18133.53 08-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.126344E+10 18084.23 01-APR-04:02 0.00 0.00 0.00 0.00 0.00
May 49481155.87 7806.19 27-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 18848380.50 2571.59 30-AUG-05:03 0.00 0.00 0.00 0.00 0.00
September 0.870246E+09 18054.48 28-SEP-04:01 0.00 0.00 0.00 0.00 0.00
October 0.462862E+10 18196.74 10-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.969911E+10 18142.77 28-NOV-04:02 0.00 0.00 0.00 0.00 0.00
December 0.114356E+11 18134.36 26-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.542887E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.122369E+11 18196.74   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.379084E+10 53394.42 12-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.146934E+10 30901.71 28-FEB-21:00 0.00 0.00 0.00 0.00 0.00
March 0.180762E+09 33632.23 01-MAR-07:30 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.207940E+10 31075.11 30-NOV-21:00 0.00 0.00 0.00 0.00 0.00
December 0.275334E+10 36278.45 15-DEC-07:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.102737E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.379084E+10 53394.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 4198159.85 4198159.85 380.49 25-JAN-11:10 380.49 0.00
February 0.00 0.00 15114321.99 15114321.99 1982.55 09-FEB-08:20 1982.55 0.00
March 0.00 0.00 40584701.93 40584701.93 5323.52 24-MAR-07:10 5323.52 0.00
April 0.00 0.00 73221186.88 73221186.88 8505.50 20-APR-14:00 8505.50 0.00
May 0.00 0.00 0.843258E+10 0.843258E+10 69603.21 31-MAY-16:00 69603.21 0.00
June 0.00 0.00 0.389659E+11 0.388389E+11 106565.15 30-JUN-12:20 96938.62 0.12
July 0.00 0.00 0.526532E+11 0.524836E+11 113359.44 03-JUL-15:00 49744.46 0.38
August 0.00 0.00 0.300603E+11 0.300603E+11 107175.13 11-AUG-15:20 107175.13 0.24
September 0.00 0.00 0.499455E+09 0.499455E+09 20738.13 07-SEP-16:00 20738.13 0.00
October 0.00 0.00 30516028.97 30516028.97 4023.77 12-OCT-07:20 4023.77 0.00
November 0.00 0.00 29350106.65 29350106.65 2741.75 06-NOV-08:20 2741.75 0.00
December 0.00 0.00 5485206.33 5485206.33 743.72 27-DEC-08:50 743.72 0.00
                 
Annual Sum or Average 0.00 0.00 0.130810E+12 0.130513E+12       0.06
Minimum of Months 0.00 0.00 4198159.85 4198159.85 380.49   380.49 0.00
Maximum of Months 0.00 0.00 0.526532E+11 0.524836E+11 113359.44   107175.13 0.38



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 15396889.47 15396889.47 788.10 21-JAN-12:10 788.10 0.00
February 0.00 0.00 37337995.78 37337995.78 2103.31 15-FEB-12:20 2103.31 0.00
March 0.00 0.00 0.182132E+09 0.182132E+09 18474.58 29-MAR-13:20 18474.58 0.00
April 0.00 0.00 0.517552E+09 0.517552E+09 66251.76 20-APR-14:00 66251.76 0.00
May 0.00 0.00 0.750780E+11 0.750780E+11 639156.97 31-MAY-16:00 639156.97 0.00
June 0.00 0.00 0.331807E+12 0.330785E+12 970716.34 30-JUN-12:30 900573.40 0.11
July 0.00 0.00 0.429244E+12 0.428123E+12 989537.09 23-JUL-15:11 989537.09 0.33
August 0.00 0.00 0.231058E+12 0.231058E+12 924143.19 11-AUG-15:40 924143.19 0.20
September 0.00 0.00 0.426428E+10 0.426428E+10 176677.56 07-SEP-16:00 176677.56 0.00
October 0.00 0.00 57149762.41 57149762.41 2902.56 05-OCT-10:00 2902.56 0.00
November 0.00 0.00 30054792.72 30054792.72 1287.63 02-NOV-17:40 1287.63 0.00
December 0.00 0.00 5115440.41 5115440.41 657.05 23-DEC-12:10 657.05 0.00
                 
Annual Sum or Average 0.00 0.00 0.107230E+13 0.107015E+13       0.05
Minimum of Months 0.00 0.00 5115440.41 5115440.41 657.05   657.05 0.00
Maximum of Months 0.00 0.00 0.429244E+12 0.428123E+12 989537.09   989537.09 0.33



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 425207.57 425207.57 623.75 02-JAN-06:07 623.75 0.00
February 0.00 0.00 3476096.06 3476096.06 1306.01 06-FEB-06:01 1306.01 0.00
March 0.00 0.00 13933196.64 13933196.64 426.96 27-MAR-11:50 426.96 0.00
April 0.00 0.00 39322996.83 39322996.83 3495.34 22-APR-14:00 3495.34 0.00
May 0.00 0.00 0.719992E+10 0.719992E+10 70434.78 31-MAY-16:00 70434.78 0.00
June 0.00 0.00 0.347188E+11 0.345972E+11 113085.75 30-JUN-12:30 103657.62 0.10
July 0.00 0.00 0.447259E+11 0.446237E+11 111174.71 21-JUL-14:40 111174.71 0.32
August 0.00 0.00 0.232185E+11 0.232185E+11 102607.66 11-AUG-15:40 102607.66 0.19
September 0.00 0.00 0.304765E+09 0.304765E+09 13052.05 07-SEP-16:00 13052.05 0.00
October 0.00 0.00 7962375.04 7962375.04 560.83 03-OCT-10:50 560.83 0.00
November 0.00 0.00 103733.72 103733.72 47.22 01-NOV-16:20 47.22 0.00
December 0.00 0.00 656271.04 656271.04 216.35 19-DEC-05:37 216.35 0.00
                 
Annual Sum or Average 0.00 0.00 0.110234E+12 0.110010E+12       0.05
Minimum of Months 0.00 0.00 103733.72 103733.72 47.22   47.22 0.00
Maximum of Months 0.00 0.00 0.447259E+11 0.446237E+11 113085.75   111174.71 0.32



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 11359025.64 11359025.64 1066.57 26-JAN-10:00 1066.57 0.00
February 0.00 0.00 23090215.37 23090215.37 2073.75 10-FEB-17:10 2073.75 0.00
March 0.00 0.00 38291662.31 38291662.31 4540.09 23-MAR-16:10 4540.09 0.00
April 0.00 0.00 17735853.64 17735853.64 3251.59 03-APR-16:10 3251.59 0.00
May 0.00 0.00 0.274365E+10 0.274365E+10 36994.63 31-MAY-16:00 36994.63 0.00
June 0.00 0.00 0.172795E+11 0.172602E+11 49979.18 13-JUN-13:20 49979.18 0.09
July 0.00 0.00 0.262407E+11 0.261277E+11 63897.43 03-JUL-15:00 28574.78 0.23
August 0.00 0.00 0.141080E+11 0.140831E+11 50489.07 11-AUG-16:00 50489.07 0.15
September 0.00 0.00 46509867.81 46509867.81 7289.20 07-SEP-16:00 7289.20 0.00
October 0.00 0.00 38196331.69 38196331.69 4463.19 19-OCT-16:10 4463.19 0.00
November 0.00 0.00 41158273.76 41158273.76 5269.97 07-NOV-08:00 5269.97 0.00
December 0.00 0.00 17896533.94 17896533.94 9511.82 27-DEC-13:00 9511.82 0.00
                 
Annual Sum or Average 0.00 0.00 0.606060E+11 0.604488E+11       0.04
Minimum of Months 0.00 0.00 11359025.64 11359025.64 1066.57   1066.57 0.00
Maximum of Months 0.00 0.00 0.262407E+11 0.261277E+11 63897.43   50489.07 0.23



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.136356E+10 0.136356E+10 1222.90 31-JAN-05:14 1222.90 0.00
February 0.00 0.00 0.677844E+10 0.677844E+10 3542.34 12-FEB-15:50 3542.34 0.00
March 0.00 0.00 0.137858E+11 0.137858E+11 7340.88 31-MAR-24:00 7340.88 0.00
April 0.00 0.00 0.196094E+11 0.196094E+11 8776.48 22-APR-18:40 8776.48 0.00
May 0.00 0.00 0.544636E+10 0.544619E+10 3996.14 31-MAY-24:00 3996.14 0.00
June 0.00 0.00 0.105824E+11 0.105065E+11 5904.53 30-JUN-24:00 5895.38 0.00
July 0.00 0.00 0.160921E+11 0.159355E+11 7815.25 31-JUL-23:05 7777.37 0.00
August 0.00 0.00 0.208821E+11 0.207522E+11 8748.65 27-AUG-18:34 8748.65 0.00
September 0.00 0.00 0.476566E+10 0.474931E+10 3498.46 30-SEP-24:00 3498.46 0.00
October 0.00 0.00 0.904364E+10 0.904334E+10 5068.16 31-OCT-24:00 5068.16 0.00
November 0.00 0.00 0.123807E+11 0.123807E+11 5418.73 19-NOV-15:30 5418.73 0.00
December 0.00 0.00 0.175148E+11 0.175148E+11 7324.39 24-DEC-17:55 7324.39 0.00
                 
Annual Sum or Average 0.00 0.00 0.138245E+12 0.137866E+12       0.00
Minimum of Months 0.00 0.00 0.136356E+10 0.136356E+10 1222.90   1222.90 0.00
Maximum of Months 0.00 0.00 0.208821E+11 0.207522E+11 8776.48   8776.48 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.117589E+09 0.117589E+09 2532.93 27-JAN-22:10 2532.93 0.00
February 0.00 0.00 0.397329E+11 0.397329E+11 26712.30 16-FEB-16:10 26712.30 0.00
March 0.00 0.00 0.107566E+12 0.107566E+12 63789.57 31-MAR-23:20 63789.57 0.00
April 0.00 0.00 0.175332E+12 0.175332E+12 82240.03 22-APR-18:50 82240.03 0.00
May 0.00 0.00 0.471505E+11 0.471485E+11 37364.83 31-MAY-24:00 37364.83 0.00
June 0.00 0.00 0.987670E+11 0.980127E+11 56491.46 30-JUN-23:20 56198.19 0.00
July 0.00 0.00 0.151954E+12 0.150396E+12 75671.92 31-JUL-23:53 75399.55 0.00
August 0.00 0.00 0.196844E+12 0.195548E+12 81748.88 27-AUG-18:43 81748.88 0.00
September 0.00 0.00 0.352204E+11 0.350643E+11 27557.19 30-SEP-24:00 27557.19 0.00
October 0.00 0.00 0.638031E+11 0.637997E+11 38555.25 31-OCT-23:30 38555.25 0.00
November 0.00 0.00 0.874471E+11 0.874471E+11 42286.62 08-NOV-15:50 42286.62 0.00
December 0.00 0.00 0.135059E+12 0.135059E+12 57995.14 29-DEC-22:08 57995.14 0.00
                 
Annual Sum or Average 0.00 0.00 0.113899E+13 0.113522E+13       0.00
Minimum of Months 0.00 0.00 0.117589E+09 0.117589E+09 2532.93   2532.93 0.00
Maximum of Months 0.00 0.00 0.196844E+12 0.195548E+12 82240.03   82240.03 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00
February 0.00 0.00 0.213543E+10 0.213543E+10 2330.03 09-FEB-16:00 2330.03 0.00
March 0.00 0.00 0.853085E+10 0.853085E+10 5347.24 31-MAR-23:10 5347.24 0.00
April 0.00 0.00 0.158419E+11 0.158419E+11 8081.93 22-APR-18:40 8081.93 0.00
May 0.00 0.00 0.401918E+10 0.401900E+10 3690.90 31-MAY-24:00 3690.90 0.00
June 0.00 0.00 0.971143E+10 0.963613E+10 5633.29 30-JUN-23:20 5603.70 0.00
July 0.00 0.00 0.150440E+11 0.148883E+11 7546.63 31-JUL-23:05 7508.96 0.00
August 0.00 0.00 0.192946E+11 0.191652E+11 8201.96 27-AUG-18:47 8201.96 0.00
September 0.00 0.00 0.196165E+10 0.194777E+10 2209.62 02-SEP-17:55 2209.62 0.00
October 0.00 0.00 0.392240E+10 0.392212E+10 3183.32 03-OCT-16:00 3183.32 0.00
November 0.00 0.00 0.656189E+10 0.656189E+10 3733.85 08-NOV-15:50 3733.85 0.00
December 0.00 0.00 0.113970E+11 0.113970E+11 5418.05 19-DEC-22:10 5418.05 0.00
                 
Annual Sum or Average 0.00 0.00 0.984204E+11 0.980457E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.192946E+11 0.191652E+11 8201.96   8201.96 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 314320.42 2180992.49 18-JAN-05:01
February 0.00 0.00 01-FEB-00:03 202652.91 2096358.65 27-FEB-07:10
March 0.00 0.00 01-MAR-00:10 84340.43 1745918.47 02-MAR-06:01
April 0.00 0.00 01-APR-00:10 13918.45 1343009.51 05-APR-05:01
May 0.00 0.00 01-MAY-00:10 304.36 193573.76 27-MAY-06:10
June 0.00 0.00 01-JUN-00:10 1.47 6069.67 02-JUN-06:10
July 0.00 0.00 01-JUL-00:10 0.01 29.17 05-JUL-07:00
August 0.00 0.00 01-AUG-00:03 266.85 261480.21 31-AUG-06:10
September 0.00 0.00 01-SEP-00:10 5475.37 679198.10 28-SEP-05:03
October 0.00 0.00 01-OCT-00:10 50544.76 1639136.04 30-OCT-05:01
November 0.00 0.00 01-NOV-00:10 255317.50 1843969.32 18-NOV-06:02
December 0.00 0.00 01-DEC-00:10 354272.77 1891166.72 26-DEC-05:11
             
Annual Sum or Average 0.00     106414.25    
Minimum of Months 0.00 0.00   0.01 29.17  
Maximum of Months 0.00 0.00   354272.77 2180992.49  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 2683.40 20276.19 23-JAN-07:05 0.00 0.00 01-JAN-00:02
February 3935.67 21393.83 15-FEB-12:20 0.00 0.00 01-FEB-00:03
March 4836.71 45400.43 29-MAR-13:20 0.00 0.00 01-MAR-00:10
April 2812.83 161597.87 20-APR-14:10 0.00 0.00 01-APR-00:10
May 68962.46 1024696.01 31-MAY-14:00 3.06 81933.37 14-MAY-08:12
June 261387.16 1285174.53 20-JUN-14:40 23.85 92814.76 24-JUN-03:02
July 300945.89 1312557.09 21-JUL-13:10 14.51 37090.85 10-JUL-22:42
August 184056.17 1318524.80 11-AUG-15:10 0.96 10482.03 05-AUG-21:42
September 5485.68 439721.34 07-SEP-16:00 0.00 0.00 01-SEP-00:10
October 3596.82 28829.35 05-OCT-10:00 0.00 0.00 01-OCT-00:10
November 4968.55 25508.06 07-NOV-08:00 0.00 0.00 01-NOV-00:10
December 2457.87 30303.87 27-DEC-13:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 71078.20     3.53    
Minimum of Months 2457.87 20276.19   0.00 0.00  
Maximum of Months 300945.89 1318524.80   23.85 92814.76  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.92 105.93 26-JAN-10:00 0.00 0.00 01-JAN-00:02
February 11.31 1247.76 15-FEB-12:20 0.00 0.00 01-FEB-00:03
March 92.79 20791.56 29-MAR-13:20 0.00 0.00 01-MAR-00:10
April 319.36 101663.51 20-APR-14:00 0.00 0.00 01-APR-00:10
May 43229.13 969387.84 31-MAY-15:50 0.00 0.00 01-MAY-00:10
June 195157.31 1342462.24 20-JUN-14:40 0.00 0.00 01-JUN-00:10
July 250375.28 1765309.90 23-JUL-15:11 0.00 0.00 01-JUL-00:10
August 140964.22 1387079.14 11-AUG-15:10 0.00 0.00 01-AUG-00:03
September 2450.56 270109.34 07-SEP-16:00 0.00 0.00 01-SEP-00:10
October 59.89 5671.56 05-OCT-10:00 0.00 0.00 01-OCT-00:10
November 45.48 4317.28 07-NOV-08:00 0.00 0.00 01-NOV-00:10
December 11.87 8157.07 27-DEC-13:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 53195.22     0.00    
Minimum of Months 0.92 105.93   0.00 0.00  
Maximum of Months 250375.28 1765309.90   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1292.66 4718.65 27-JAN-22:10 0.00 0.00 01-JAN-00:02
February 25958.94 40873.33 16-FEB-16:10 0.00 0.00 01-FEB-00:03
March 60965.21 95355.99 31-MAR-23:20 0.00 0.00 01-MAR-00:10
April 100724.30 122160.17 22-APR-18:50 0.00 0.00 01-APR-00:10
May 27993.56 79855.95 31-MAY-16:00 0.00 0.00 01-MAY-00:10
June 69849.38 182908.37 30-JUN-15:00 0.00 0.00 01-JUN-00:10
July 105718.83 232794.02 29-JUL-17:00 0.00 0.00 01-JUL-00:10
August 120528.44 218314.81 11-AUG-18:00 0.00 0.00 01-AUG-00:03
September 20785.75 41333.27 30-SEP-24:00 0.00 0.00 01-SEP-00:10
October 36322.05 58792.60 31-OCT-23:30 0.00 0.00 01-OCT-00:10
November 51955.46 64329.50 08-NOV-15:50 0.00 0.00 01-NOV-00:10
December 76825.28 87724.81 29-DEC-22:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 58480.34     0.00    
Minimum of Months 1292.66 4718.65   0.00 0.00  
Maximum of Months 120528.44 232794.02   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 18931.13 63786.40 03-JAN-12:57
February 0.00 0.00 01-FEB-00:03 19037.22 63850.74 28-FEB-12:55
March 0.00 0.00 01-MAR-00:10 20139.72 63788.52 29-MAR-11:23
April 0.00 0.00 01-APR-00:10 18959.23 63838.72 04-APR-11:45
May 0.00 0.00 01-MAY-00:10 19409.32 63741.45 01-MAY-11:20
June 0.00 0.00 01-JUN-00:10 19173.96 62175.93 01-JUN-11:20
July 0.00 0.00 01-JUL-00:10 17143.28 59651.08 03-JUL-11:50
August 0.00 0.00 01-AUG-00:03 18214.92 57892.04 01-AUG-12:00
September 0.00 0.00 01-SEP-00:10 17113.67 57537.35 29-SEP-11:30
October 0.00 0.00 01-OCT-00:10 17396.59 59183.71 31-OCT-11:50
November 0.00 0.00 01-NOV-00:10 18195.23 61483.57 30-NOV-12:20
December 0.00 0.00 01-DEC-00:10 18244.08 63739.71 29-DEC-12:20
             
Annual Sum or Average 0.00     18493.58    
Minimum of Months 0.00 0.00   17113.67 57537.35  
Maximum of Months 0.00 0.00   20139.72 63850.74  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 128.97 21373.44 25-JAN-19:10 3682.18 118236.41 20-JAN-18:00
February 216.85 21687.43 21-FEB-07:40 5333.51 118375.21 15-FEB-19:00
March 192.41 22173.34 07-MAR-19:30 6545.47 118520.76 30-MAR-07:00
April 191.20 56037.02 20-APR-13:50 3211.45 117802.94 03-APR-08:30
May 39176.81 1651931.89 31-MAY-15:50 1129.32 110281.76 27-MAY-11:10
June 203337.11 1957581.81 30-JUN-13:40 385.31 59675.02 07-JUN-08:30
July 266688.68 1948802.75 21-JUL-14:50 505.50 49393.10 11-JUL-23:10
August 145684.71 1947280.32 11-AUG-15:40 821.86 93395.07 31-AUG-20:30
September 1614.72 265703.95 07-SEP-16:00 1085.06 118018.35 30-SEP-07:40
October 122.86 22550.70 26-OCT-17:40 4832.04 118603.90 27-OCT-19:40
November 286.90 22400.84 18-NOV-12:10 6771.06 124744.79 27-NOV-04:01
December 117.27 22113.03 26-DEC-13:40 3256.44 117980.48 19-DEC-21:00
             
Annual Sum or Average 55299.82     3114.74    
Minimum of Months 117.27 21373.44   385.31 49393.10  
Maximum of Months 266688.68 1957581.81   6771.06 124744.79  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.115651E+11 0.73 8365.97 02-JAN-06:01 1.40
February 0.106164E+11 0.74 8365.97 01-FEB-06:01 1.42
March 0.129531E+11 0.82 8365.97 01-MAR-06:01 1.42
April 0.121984E+11 0.80 8365.97 01-APR-04:01 1.42
May 0.128853E+11 0.81 8365.97 01-MAY-03:02 1.42
June 0.131425E+11 0.85 8365.97 01-JUN-03:02 1.41
July 0.127648E+11 0.80 8365.97 01-JUL-03:02 1.40
August 0.140297E+11 0.88 8365.97 01-AUG-03:02 1.40
September 0.128560E+11 0.84 8365.97 01-SEP-03:02 1.41
October 0.124569E+11 0.79 8365.97 02-OCT-03:05 1.41
November 0.115347E+11 0.75 8365.97 01-NOV-04:01 1.42
December 0.115049E+11 0.73 8365.97 01-DEC-06:01 1.42
           
Annual Sum or Average 0.148508E+12 0.80      
Minimum of Months 0.106164E+11 0.73 8365.97   1.40
Maximum of Months 0.140297E+11 0.88 8365.97   1.42



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.290841E+10 0.31 3682.63 02-JAN-05:01 0.70
February 0.281740E+10 0.31 12812.41 14-FEB-06:01 1.44
March 0.441750E+10 0.36 12812.41 16-MAR-05:02 1.44
April 0.757680E+10 0.49 20076.44 07-APR-13:30 1.91
May 0.846443E+10 0.51 18239.54 01-MAY-05:03 1.79
June 0.110868E+11 0.63 20076.44 07-JUN-05:02 1.90
July 0.117090E+11 0.65 20076.44 06-JUL-05:02 1.89
August 0.117810E+11 0.66 18815.56 01-AUG-05:02 1.81
September 0.517346E+10 0.39 10810.83 01-SEP-03:02 1.29
October 0.400988E+10 0.33 14357.33 12-OCT-12:10 1.54
November 0.308510E+10 0.31 12812.41 07-NOV-06:02 1.44
December 0.299294E+10 0.30 3682.63 01-DEC-06:01 0.70
           
Annual Sum or Average 0.760227E+11 0.44      
Minimum of Months 0.281740E+10 0.30 3682.63   0.70
Maximum of Months 0.117810E+11 0.66 20076.44   1.91



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.376272E+11 0.39 52065.08 02-JAN-04:01 0.88
February 0.310700E+11 0.36 52065.08 01-FEB-06:01 0.88
March 0.333442E+11 0.34 152942.40 31-MAR-16:00 1.68
April 0.422128E+11 0.37 186842.52 13-APR-10:20 1.91
May 0.673669E+11 0.46 179996.72 15-MAY-05:02 1.86
June 0.852011E+11 0.54 186842.52 24-JUN-05:02 1.89
July 0.807634E+11 0.50 186842.52 03-JUL-05:02 1.89
August 0.714200E+11 0.48 186842.52 11-AUG-05:02 1.90
September 0.378276E+11 0.34 98779.04 08-SEP-07:20 1.27
October 0.294034E+11 0.31 84325.05 05-OCT-05:03 1.16
November 0.322409E+11 0.35 52065.08 06-NOV-06:01 0.88
December 0.349080E+11 0.37 52065.08 02-DEC-06:01 0.88
           
Annual Sum or Average 0.583385E+12 0.40      
Minimum of Months 0.294034E+11 0.31 52065.08   0.88
Maximum of Months 0.852011E+11 0.54 186842.52   1.91



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.481402E+10 0.46 5239.03 01-JAN-00:42 0.86
February 0.411950E+10 0.45 5239.03 01-FEB-05:11 0.86
March 0.415823E+10 0.41 5239.03 01-MAR-05:11 0.86
April 0.369741E+10 0.35 7821.61 21-APR-16:00 1.08
May 0.535243E+10 0.40 13356.12 31-MAY-15:20 1.49
June 0.812215E+10 0.51 19568.62 24-JUN-05:02 1.89
July 0.763613E+10 0.47 19232.41 28-JUL-05:02 1.87
August 0.607261E+10 0.42 15618.87 05-AUG-05:03 1.64
September 0.305320E+10 0.31 5239.03 25-SEP-04:01 0.85
October 0.359286E+10 0.36 5239.03 02-OCT-04:01 0.85
November 0.452707E+10 0.46 5239.03 01-NOV-04:01 0.86
December 0.494275E+10 0.48 5239.03 01-DEC-05:11 0.86
           
Annual Sum or Average 0.600884E+11 0.42      
Minimum of Months 0.305320E+10 0.31 5239.03   0.85
Maximum of Months 0.812215E+10 0.51 19568.62   1.89



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.148551E+10 0.94 554.62 01-JAN-00:02 0.93
February 0.134175E+10 0.94 554.62 01-FEB-00:03 0.94
March 0.148551E+10 0.94 554.62 01-MAR-00:10 0.94
April 0.143759E+10 0.93 554.62 01-APR-00:10 0.94
May 0.148551E+10 0.93 554.62 01-MAY-00:10 0.93
June 0.143759E+10 0.93 554.62 01-JUN-00:10 0.93
July 0.148551E+10 0.93 554.62 01-JUL-00:10 0.93
August 0.148551E+10 0.93 554.62 01-AUG-00:03 0.93
September 0.143759E+10 0.93 554.62 01-SEP-00:10 0.93
October 0.148551E+10 0.93 554.62 01-OCT-00:10 0.93
November 0.143759E+10 0.94 554.62 01-NOV-00:10 0.94
December 0.148551E+10 0.94 554.62 01-DEC-00:10 0.94
           
Annual Sum or Average 0.174906E+11 0.93      
Minimum of Months 0.134175E+10 0.93 554.62   0.93
Maximum of Months 0.148551E+10 0.94 554.62   0.94



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.142384E+11 0.94 5316.02 01-JAN-00:02 0.93
February 0.128605E+11 0.94 5316.02 01-FEB-00:03 0.94
March 0.142384E+11 0.94 5316.02 01-MAR-00:10 0.94
April 0.137791E+11 0.93 5316.02 01-APR-00:10 0.94
May 0.142384E+11 0.93 5316.02 01-MAY-00:10 0.93
June 0.137791E+11 0.93 5316.02 01-JUN-00:10 0.93
July 0.142384E+11 0.93 5316.02 01-JUL-00:10 0.93
August 0.142384E+11 0.93 5316.02 01-AUG-00:03 0.93
September 0.137791E+11 0.93 5316.02 01-SEP-00:10 0.93
October 0.142384E+11 0.93 5316.02 01-OCT-00:10 0.93
November 0.137791E+11 0.94 5316.02 01-NOV-00:20 0.94
December 0.142384E+11 0.94 5316.02 01-DEC-00:10 0.94
           
Annual Sum or Average 0.167646E+12 0.93      
Minimum of Months 0.128605E+11 0.93 5316.02   0.93
Maximum of Months 0.142384E+11 0.94 5316.02   0.94



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.143856E+10 0.94 537.10 01-JAN-00:02 0.93
February 0.129934E+10 0.94 537.10 01-FEB-00:03 0.94
March 0.143856E+10 0.94 537.10 01-MAR-00:10 0.94
April 0.139215E+10 0.93 537.10 01-APR-00:10 0.94
May 0.143856E+10 0.93 537.10 01-MAY-00:10 0.93
June 0.139215E+10 0.93 537.10 01-JUN-00:10 0.93
July 0.143856E+10 0.93 537.10 01-JUL-00:10 0.93
August 0.143856E+10 0.93 537.10 01-AUG-00:03 0.93
September 0.139215E+10 0.93 537.10 01-SEP-00:10 0.93
October 0.143856E+10 0.93 537.10 01-OCT-00:10 0.94
November 0.139215E+10 0.94 537.10 01-NOV-00:10 0.94
December 0.143856E+10 0.94 537.10 01-DEC-00:10 0.94
           
Annual Sum or Average 0.169379E+11 0.93      
Minimum of Months 0.129934E+10 0.93 537.10   0.93
Maximum of Months 0.143856E+10 0.94 537.10   0.94



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.157992E+09 0.143614E+09 1024.77 12-JAN-07:10 931.51 931.51 46.29 12.83
February 76993089.26 69986718.13 1180.37 27-FEB-07:10 1072.95 1072.95 45.48 13.66
March 24709717.82 22461133.50 783.92 02-MAR-06:01 712.59 712.59 45.48 11.38
April 1866767.22 1696891.40 266.09 03-APR-05:02 241.87 241.87 43.15 6.84
May 26790.01 24352.12 8.10 27-MAY-06:10 7.36 7.36 27.16 0.86
June 104.07 94.60 0.17 02-JUN-06:10 0.15 0.15 25.47 0.03
July 0.96 0.87 0.00 05-JUL-07:00 0.00 0.00 25.45 0.00
August 25168.57 22878.23 11.93 31-AUG-06:10 10.84 10.84 26.24 1.14
September 585867.25 532553.33 75.61 30-SEP-05:03 68.73 68.73 37.34 3.55
October 8535486.87 7758757.57 774.29 30-OCT-05:01 703.83 703.83 47.51 11.30
November 0.105382E+09 95792562.30 805.38 27-NOV-07:03 732.09 732.09 45.53 11.52
December 0.163339E+09 0.148475E+09 788.46 11-DEC-05:02 716.71 716.71 46.29 11.40
                 
Annual Sum or Average 0.539456E+09 0.490365E+09            
Minimum of Months 0.96 0.87 0.00   0.00 0.00 25.45 0.00
Maximum of Months 0.163339E+09 0.148475E+09 1180.37   1072.95 1072.95 47.51 13.66



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 3317.53 3015.63 0.10 21-JAN-12:10 0.09 0.09 6.87 0.02
February 9185.71 8349.81 0.33 15-FEB-12:20 0.30 0.30 7.41 0.08
March 38114.28 34645.88 3.10 29-MAR-13:20 2.82 2.82 8.22 0.64
April 142501.33 129533.71 23.46 20-APR-14:00 21.32 21.32 8.45 3.08
May 38824569.60 35291533.77 637.10 31-MAY-15:50 579.12 579.12 8.00 19.74
June 0.336423E+09 0.305809E+09 3173.46 21-JUN-15:00 2884.67 2884.67 6.98 40.70
July 0.659056E+09 0.599082E+09 8056.58 23-JUL-15:11 7323.43 7323.43 7.91 59.95
August 0.385540E+09 0.350455E+09 4094.30 11-AUG-15:40 3721.72 3721.72 6.95 45.34
September 1133502.89 1030354.13 82.94 10-SEP-11:22 75.39 75.39 8.51 6.79
October 18702.51 17000.58 0.70 05-OCT-10:00 0.63 0.63 8.47 0.16
November 13338.95 12125.10 0.50 07-NOV-08:00 0.46 0.46 8.42 0.12
December 3515.10 3195.23 0.94 27-DEC-13:00 0.85 0.85 8.42 0.21
                 
Annual Sum or Average 0.142121E+10 0.129188E+10            
Minimum of Months 3317.53 3015.63 0.10   0.09 0.09 6.87 0.02
Maximum of Months 0.659056E+09 0.599082E+09 8056.58   7323.43 7323.43 8.51 59.95



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.398717E+10 0.362434E+10 11212.43 02-JAN-05:01 10192.10 10192.10 8.43 79.37
February 0.525670E+10 0.477834E+10 11212.43 01-FEB-08:40 10192.10 10192.10 8.43 79.37
March 0.696999E+10 0.633572E+10 11212.43 01-MAR-04:01 10192.10 10192.10 8.43 79.37
April 0.335090E+10 0.304597E+10 11212.43 01-APR-06:05 10192.10 10192.10 8.43 79.37
May 0.680652E+10 0.618713E+10 11212.43 01-MAY-14:50 10192.10 10192.10 8.43 79.37
June 0.146212E+11 0.132907E+11 11212.43 01-JUN-10:10 10192.10 10192.10 8.50 79.37
July 0.166176E+11 0.151054E+11 11212.43 01-JUL-04:03 10192.10 10192.10 8.39 79.37
August 0.123304E+11 0.112084E+11 11212.43 01-AUG-00:10 10192.10 10192.10 8.29 79.37
September 0.225078E+10 0.204596E+10 11212.43 01-SEP-13:40 10192.10 10192.10 8.44 79.37
October 0.518743E+10 0.471538E+10 11212.43 02-OCT-12:50 10192.10 10192.10 8.43 79.37
November 0.701943E+10 0.638066E+10 11212.43 01-NOV-06:05 10192.10 10192.10 8.43 79.37
December 0.361490E+10 0.328595E+10 11212.43 03-DEC-09:28 10192.10 10192.10 8.43 79.37
                 
Annual Sum or Average 0.880131E+11 0.800039E+11            
Minimum of Months 0.225078E+10 0.204596E+10 11212.43   10192.10 10192.10 8.29 79.37
Maximum of Months 0.166176E+11 0.151054E+11 11212.43   10192.10 10192.10 8.50 79.37



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.168722E+10 0.153368E+10 702.21 01-JAN-00:02 638.31 638.31 18.44 2.96
February 0.169879E+10 0.154420E+10 702.21 01-FEB-00:03 638.31 638.31 19.27 2.96
March 0.188080E+10 0.170965E+10 702.21 01-MAR-00:10 638.31 638.31 23.22 2.96
April 0.182013E+10 0.165450E+10 702.21 01-APR-00:10 638.31 638.31 27.51 2.96
May 0.188080E+10 0.170965E+10 702.21 01-MAY-00:10 638.31 638.31 21.05 2.96
June 0.182013E+10 0.165450E+10 702.21 01-JUN-00:10 638.31 638.31 23.77 2.96
July 0.188080E+10 0.170965E+10 702.21 01-JUL-00:10 638.31 638.31 26.40 2.96
August 0.188080E+10 0.170965E+10 702.21 01-AUG-00:03 638.31 638.31 29.16 2.96
September 0.182013E+10 0.165450E+10 702.21 01-SEP-00:10 638.31 638.31 20.98 2.96
October 0.188080E+10 0.170965E+10 702.21 01-OCT-00:10 638.31 638.31 22.34 2.96
November 0.182013E+10 0.165450E+10 702.21 01-NOV-00:10 638.31 638.31 24.01 2.96
December 0.188080E+10 0.170965E+10 702.21 01-DEC-00:10 638.31 638.31 25.94 2.96
                 
Annual Sum or Average 0.219513E+11 0.199538E+11            
Minimum of Months 0.168722E+10 0.153368E+10 702.21   638.31 638.31 18.44 2.96
Maximum of Months 0.188080E+10 0.170965E+10 702.21   638.31 638.31 29.16 2.96



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 11967951.72 3590385.52 5.96 01-JAN-06:02 1.79 1.79 55.38 0.44
February 10809762.85 3242928.85 5.96 01-FEB-06:01 1.79 1.79 55.67 0.44
March 11967951.72 3590385.52 5.96 01-MAR-06:01 1.79 1.79 55.99 0.44
April 11581888.76 3474566.63 5.96 01-APR-05:03 1.79 1.79 54.86 0.44
May 11967951.72 3590385.52 5.96 01-MAY-05:03 1.79 1.79 56.02 0.44
June 11581888.76 3474566.63 5.96 01-JUN-05:03 1.79 1.79 55.82 0.44
July 11967951.72 3590385.52 5.96 01-JUL-05:03 1.79 1.79 55.52 0.44
August 11967951.72 3590385.52 5.96 01-AUG-05:02 1.79 1.79 55.17 0.44
September 11581888.76 3474566.63 5.96 01-SEP-05:03 1.79 1.79 55.29 0.44
October 11967951.72 3590385.52 5.96 01-OCT-05:10 1.79 1.79 55.27 0.44
November 11581888.76 3474566.63 5.96 01-NOV-05:03 1.79 1.79 56.02 0.44
December 11967951.72 3590385.52 5.96 01-DEC-06:01 1.79 1.79 55.55 0.44
                 
Annual Sum or Average 0.140913E+09 42273893.99            
Minimum of Months 10809762.85 3242928.85 5.96   1.79 1.79 54.86 0.44
Maximum of Months 11967951.72 3590385.52 5.96   1.79 1.79 56.02 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.504590E+10 0.458673E+10 14192.18 25-JAN-19:10 12900.69 12900.69 21.21 47.75
February 0.665255E+10 0.604717E+10 14192.19 21-FEB-07:40 12900.70 12900.70 21.21 47.75
March 0.882073E+10 0.801805E+10 14192.22 07-MAR-19:30 12900.73 12900.73 21.21 47.75
April 0.424069E+10 0.385478E+10 14193.95 20-APR-13:50 12902.30 12902.30 21.38 47.75
May 0.871218E+10 0.791937E+10 28467.70 31-MAY-15:50 25877.14 25877.14 25.24 95.50
June 0.203044E+11 0.184567E+11 28485.97 30-JUN-13:40 25893.75 25893.75 26.00 95.50
July 0.241594E+11 0.219609E+11 28485.45 21-JUL-14:50 25893.27 25893.27 25.98 95.50
August 0.170551E+11 0.155031E+11 28485.36 11-AUG-15:40 25893.19 25893.19 25.98 95.50
September 0.284879E+10 0.258955E+10 14204.67 07-SEP-16:00 12912.05 12912.05 22.43 47.75
October 0.656486E+10 0.596746E+10 14192.24 26-OCT-17:40 12900.74 12900.74 21.21 47.75
November 0.888333E+10 0.807495E+10 14192.23 18-NOV-12:10 12900.74 12900.74 21.21 47.75
December 0.457480E+10 0.415849E+10 14192.22 26-DEC-13:40 12900.72 12900.72 21.21 47.75
                 
Annual Sum or Average 0.117863E+12 0.107137E+12            
Minimum of Months 0.284879E+10 0.258955E+10 14192.18   12900.69 12900.69 21.21 47.75
Maximum of Months 0.241594E+11 0.219609E+11 28485.97   25893.75 25893.75 26.00 95.50



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 37.67 37.67 314320.42 2180992.49 18-JAN-05:01
February 0.00 0.00 01-FEB-00:03 30.11 30.11 202652.91 2096358.65 27-FEB-07:10
March 0.00 0.00 01-MAR-00:10 41.94 82.20 84340.43 1745918.47 02-MAR-06:01
April 0.00 0.00 01-APR-00:10 41.06 41.06 13918.45 1343009.51 05-APR-05:01
May 0.00 0.00 01-MAY-00:10 28.97 28.97 304.36 193573.76 27-MAY-06:10
June 0.00 0.00 01-JUN-00:10 25.50 25.50 1.47 6069.67 02-JUN-06:10
July 0.00 0.00 01-JUL-00:10 25.45 25.45 0.01 29.17 05-JUL-07:00
August 0.00 0.00 01-AUG-00:03 25.45 25.45 266.85 261480.21 31-AUG-06:10
September 0.00 0.00 01-SEP-00:10 25.96 25.96 5475.37 679198.10 28-SEP-05:03
October 0.00 0.00 01-OCT-00:10 24.06 24.06 50544.76 1639136.04 30-OCT-05:01
November 0.00 0.00 01-NOV-00:10 27.54 27.54 255317.50 1843969.32 18-NOV-06:02
December 0.00 0.00 01-DEC-00:10 40.98 82.20 354272.77 1891166.72 26-DEC-05:11
                 
Annual Sum or Average 0.00         106414.25    
Minimum of Months 0.00 0.00   24.06 24.06 0.01 29.17  
Maximum of Months 0.00 0.00   41.94 82.20 354272.77 2180992.49  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 2683.40 20276.19 23-JAN-07:05 8.43 8.40 0.00 0.00 01-JAN-00:02
February 3935.67 21393.83 15-FEB-12:20 8.43 8.40 0.00 0.00 01-FEB-00:03
March 4836.71 45400.43 29-MAR-13:20 8.51 8.44 0.00 0.00 01-MAR-00:10
April 2812.83 161597.87 20-APR-14:10 8.86 8.61 0.00 0.00 01-APR-00:10
May 68962.46 1024696.01 31-MAY-14:00 10.79 9.12 3.06 81933.37 14-MAY-08:12
June 261387.16 1285174.53 20-JUN-14:40 10.88 7.01 23.85 92814.76 24-JUN-03:02
July 300945.89 1312557.09 21-JUL-13:10 10.95 7.00 14.51 37090.85 10-JUL-22:42
August 184056.17 1318524.80 11-AUG-15:10 10.98 7.02 0.96 10482.03 05-AUG-21:42
September 5485.68 439721.34 07-SEP-16:00 9.45 8.79 0.00 0.00 01-SEP-00:10
October 3596.82 28829.35 05-OCT-10:00 8.46 8.41 0.00 0.00 01-OCT-00:10
November 4968.55 25508.06 07-NOV-08:00 8.45 8.41 0.00 0.00 01-NOV-00:10
December 2457.87 30303.87 27-DEC-13:00 8.46 8.42 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 71078.20         3.53    
Minimum of Months 2457.87 20276.19   8.43 7.00 0.00 0.00  
Maximum of Months 300945.89 1318524.80   10.98 9.12 23.85 92814.76  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.92 105.93 26-JAN-10:00 7.97 8.40 0.00 0.00 01-JAN-00:02
February 11.31 1247.76 15-FEB-12:20 10.53 8.40 0.00 0.00 01-FEB-00:03
March 92.79 20791.56 29-MAR-13:20 14.49 8.43 0.00 0.00 01-MAR-00:10
April 319.36 101663.51 20-APR-14:00 14.58 8.61 0.00 0.00 01-APR-00:10
May 43229.13 969387.84 31-MAY-15:50 18.44 8.75 0.00 0.00 01-MAY-00:10
June 195157.31 1342462.24 20-JUN-14:40 15.28 7.01 0.00 0.00 01-JUN-00:10
July 250375.28 1765309.90 23-JUL-15:11 13.73 7.64 0.00 0.00 01-JUL-00:10
August 140964.22 1387079.14 11-AUG-15:10 14.34 7.02 0.00 0.00 01-AUG-00:03
September 2450.56 270109.34 07-SEP-16:00 16.56 8.79 0.00 0.00 01-SEP-00:10
October 59.89 5671.56 05-OCT-10:00 15.18 8.41 0.00 0.00 01-OCT-00:10
November 45.48 4317.28 07-NOV-08:00 15.52 8.41 0.00 0.00 01-NOV-00:10
December 11.87 8157.07 27-DEC-13:00 15.85 8.41 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 53195.22         0.00    
Minimum of Months 0.92 105.93   7.97 7.01 0.00 0.00  
Maximum of Months 250375.28 1765309.90   18.44 8.79 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 1292.66 4718.65 27-JAN-22:10 18.79 18.33 0.00 0.00 01-JAN-00:02
February 25958.94 40873.33 16-FEB-16:10 22.30 18.33 0.00 0.00 01-FEB-00:03
March 60965.21 95355.99 31-MAR-23:20 27.54 18.33 0.00 0.00 01-MAR-00:10
April 100724.30 122160.17 22-APR-18:50 30.11 18.33 0.00 0.00 01-APR-00:10
May 27993.56 79855.95 31-MAY-16:00 26.06 22.78 0.00 0.00 01-MAY-00:10
June 69849.38 182908.37 30-JUN-15:00 35.87 29.46 0.00 0.00 01-JUN-00:10
July 105718.83 232794.02 29-JUL-17:00 40.55 31.64 0.00 0.00 01-JUL-00:10
August 120528.44 218314.81 11-AUG-18:00 39.20 27.70 0.00 0.00 01-AUG-00:03
September 20785.75 41333.27 30-SEP-24:00 22.34 18.33 0.00 0.00 01-SEP-00:10
October 36322.05 58792.60 31-OCT-23:30 24.03 18.33 0.00 0.00 01-OCT-00:10
November 51955.46 64329.50 08-NOV-15:50 24.56 18.33 0.00 0.00 01-NOV-00:10
December 76825.28 87724.81 29-DEC-22:10 26.81 18.33 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 58480.34         0.00    
Minimum of Months 1292.66 4718.65   18.79 18.33 0.00 0.00  
Maximum of Months 120528.44 232794.02   40.55 31.64 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 56.64 56.64 18931.13 63786.40 03-JAN-12:57
February 0.00 0.00 01-FEB-00:03 56.07 56.07 19037.22 63850.74 28-FEB-12:55
March 0.00 0.00 01-MAR-00:10 56.53 56.53 20139.72 63788.52 29-MAR-11:23
April 0.00 0.00 01-APR-00:10 55.72 55.72 18959.23 63838.72 04-APR-11:45
May 0.00 0.00 01-MAY-00:10 57.15 57.15 19409.32 63741.45 01-MAY-11:20
June 0.00 0.00 01-JUN-00:10 56.56 56.56 19173.96 62175.93 01-JUN-11:20
July 0.00 0.00 01-JUL-00:10 56.23 56.23 17143.28 59651.08 03-JUL-11:50
August 0.00 0.00 01-AUG-00:03 55.78 55.78 18214.92 57892.04 01-AUG-12:00
September 0.00 0.00 01-SEP-00:10 56.04 56.04 17113.67 57537.35 29-SEP-11:30
October 0.00 0.00 01-OCT-00:10 55.74 55.74 17396.59 59183.71 31-OCT-11:50
November 0.00 0.00 01-NOV-00:10 56.64 56.64 18195.23 61483.57 30-NOV-12:20
December 0.00 0.00 01-DEC-00:10 56.13 56.13 18244.08 63739.71 29-DEC-12:20
                 
Annual Sum or Average 0.00         18493.58    
Minimum of Months 0.00 0.00   55.72 55.72 17113.67 57537.35  
Maximum of Months 0.00 0.00   57.15 57.15 20139.72 63850.74  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 128.97 21373.44 25-JAN-19:10 21.21 20.27 3682.18 118236.41 20-JAN-18:00
February 216.85 21687.43 21-FEB-07:40 21.21 20.27 5333.51 118375.21 15-FEB-19:00
March 192.41 22173.34 07-MAR-19:30 21.21 20.27 6545.47 118520.76 30-MAR-07:00
April 191.20 56037.02 20-APR-13:50 21.38 20.68 3211.45 117802.94 03-APR-08:30
May 39176.81 1651931.89 31-MAY-15:50 25.24 21.10 1129.32 110281.76 27-MAY-11:10
June 203337.11 1957581.81 30-JUN-13:40 26.00 21.84 385.31 59675.02 07-JUN-08:30
July 266688.68 1948802.75 21-JUL-14:50 25.98 21.10 505.50 49393.10 11-JUL-23:10
August 145684.71 1947280.32 11-AUG-15:40 25.98 21.10 821.86 93395.07 31-AUG-20:30
September 1614.72 265703.95 07-SEP-16:00 22.43 21.10 1085.06 118018.35 30-SEP-07:40
October 122.86 22550.70 26-OCT-17:40 21.21 20.28 4832.04 118603.90 27-OCT-19:40
November 286.90 22400.84 18-NOV-12:10 21.21 20.28 6771.06 124744.79 27-NOV-04:01
December 117.27 22113.03 26-DEC-13:40 21.21 20.27 3256.44 117980.48 19-DEC-21:00
                 
Annual Sum or Average 55299.82         3114.74    
Minimum of Months 117.27 21373.44   21.21 20.27 385.31 49393.10  
Maximum of Months 266688.68 1957581.81   26.00 21.84 6771.06 124744.79  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.363351E+11 0.00 4198159.85 0.290841E+10 0.00 0.00
February 0.186478E+11 0.00 15114321.99 0.281740E+10 0.00 0.00
March 0.587492E+10 0.00 40584701.93 0.441750E+10 0.00 0.00
April 0.554942E+09 0.00 73221186.88 0.757680E+10 0.00 0.00
May 28572665.10 0.00 0.843258E+10 0.846443E+10 0.00 0.00
June 101.99 0.00 0.389659E+11 0.110868E+11 0.00 0.00
July 0.00 0.00 0.526532E+11 0.117090E+11 0.00 0.00
August 19769940.67 0.00 0.300603E+11 0.117810E+11 0.00 0.00
September 0.216608E+09 0.00 0.499455E+09 0.517346E+10 0.00 0.00
October 0.142676E+10 0.00 30516028.97 0.400988E+10 0.00 0.00
November 0.260310E+11 0.00 29350106.65 0.308510E+10 0.00 0.00
December 0.432775E+11 0.00 5485206.33 0.299294E+10 0.00 0.00
             
Annual Sum or Average 0.132413E+12 0.00 0.130810E+12 0.760227E+11 0.00 0.00
Minimum of Months 0.00 0.00 4198159.85 0.281740E+10 0.00 0.00
Maximum of Months 0.432775E+11 0.00 0.526532E+11 0.117810E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.678480E+12 0.00 15396889.47 0.376272E+11 0.00 0.00
February 0.387244E+12 0.00 37337995.78 0.310700E+11 0.00 0.00
March 0.170405E+12 0.00 0.182132E+09 0.333442E+11 0.00 0.00
April 0.235694E+11 0.00 0.517552E+09 0.422128E+11 0.00 0.00
May 0.499227E+09 0.00 0.750780E+11 0.673669E+11 0.00 0.00
June 2326720.55 0.00 0.331807E+12 0.852011E+11 0.00 0.00
July 0.00 0.00 0.429244E+12 0.807634E+11 0.00 0.00
August 0.509227E+09 0.00 0.231058E+12 0.714200E+11 0.00 0.00
September 0.807395E+10 0.00 0.426428E+10 0.378276E+11 0.00 0.00
October 0.971770E+11 0.00 57149762.41 0.294034E+11 0.00 0.00
November 0.526777E+12 0.00 30054792.72 0.322409E+11 0.00 0.00
December 0.767876E+12 0.00 5115440.41 0.349080E+11 0.00 0.00
             
Annual Sum or Average 0.266061E+13 0.00 0.107230E+13 0.583385E+12 0.00 0.00
Minimum of Months 0.00 0.00 5115440.41 0.294034E+11 0.00 0.00
Maximum of Months 0.767876E+12 0.00 0.429244E+12 0.852011E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.127765E+12 0.00 425207.57 0.481402E+10 0.00 0.00
February 0.853663E+11 0.00 3476096.06 0.411950E+10 0.00 0.00
March 0.506183E+11 0.00 13933196.64 0.415823E+10 0.00 0.00
April 0.122492E+11 0.00 39322996.83 0.369741E+10 0.00 0.00
May 0.323891E+09 0.00 0.719992E+10 0.535243E+10 0.00 0.00
June 1903402.42 0.00 0.347188E+11 0.812215E+10 0.00 0.00
July 35379.67 0.00 0.447259E+11 0.763613E+10 0.00 0.00
August 0.182957E+09 0.00 0.232185E+11 0.607261E+10 0.00 0.00
September 0.598614E+10 0.00 0.304765E+09 0.305320E+10 0.00 0.00
October 0.374304E+11 0.00 7962375.04 0.359286E+10 0.00 0.00
November 0.110257E+12 0.00 103733.72 0.452707E+10 0.00 0.00
December 0.139993E+12 0.00 656271.04 0.494275E+10 0.00 0.00
             
Annual Sum or Average 0.570173E+12 0.00 0.110234E+12 0.600884E+11 0.00 0.00
Minimum of Months 35379.67 0.00 103733.72 0.305320E+10 0.00 0.00
Maximum of Months 0.139993E+12 0.00 0.447259E+11 0.812215E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.379084E+10 0.00 11359025.64 0.115651E+11 0.00 0.00
February 0.146934E+10 0.00 23090215.37 0.106164E+11 0.00 0.00
March 0.180762E+09 0.00 38291662.31 0.129531E+11 0.00 0.00
April 0.00 0.00 17735853.64 0.121984E+11 0.00 0.00
May 0.00 0.00 0.274365E+10 0.128853E+11 0.00 0.00
June 0.00 0.00 0.172795E+11 0.131425E+11 0.00 0.00
July 0.00 0.00 0.262407E+11 0.127648E+11 0.00 0.00
August 0.00 0.00 0.141080E+11 0.140297E+11 0.00 0.00
September 0.00 0.00 46509867.81 0.128560E+11 0.00 0.00
October 0.00 0.00 38196331.69 0.124569E+11 0.00 0.00
November 0.207940E+10 0.00 41158273.76 0.115347E+11 0.00 0.00
December 0.275334E+10 0.00 17896533.94 0.115049E+11 0.00 0.00
             
Annual Sum or Average 0.102737E+11 0.00 0.606060E+11 0.148508E+12 0.00 0.00
Minimum of Months 0.00 0.00 11359025.64 0.106164E+11 0.00 0.00
Maximum of Months 0.379084E+10 0.00 0.262407E+11 0.140297E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.175436E+10 0.187630E+10 0.00 0.00
February 0.00 0.00 0.845531E+10 0.301861E+10 0.00 0.00
March 0.00 0.00 0.169818E+11 0.468150E+10 0.00 0.00
April 0.00 0.00 0.238655E+11 0.569372E+10 0.00 0.00
May 0.00 0.00 0.675692E+10 0.279606E+10 0.00 0.00
June 0.00 0.00 0.129997E+11 0.385491E+10 0.00 0.00
July 0.00 0.00 0.196868E+11 0.508023E+10 0.00 0.00
August 0.00 0.00 0.252812E+11 0.588465E+10 0.00 0.00
September 0.00 0.00 0.589992E+10 0.257184E+10 0.00 0.00
October 0.00 0.00 0.111694E+11 0.361125E+10 0.00 0.00
November 0.00 0.00 0.153124E+11 0.436927E+10 0.00 0.00
December 0.00 0.00 0.215309E+11 0.550161E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.169694E+12 0.489400E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.175436E+10 0.187630E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.252812E+11 0.588465E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.173925E+09 0.142948E+11 0.00 0.00
February 0.00 0.00 0.499402E+11 0.230678E+11 0.00 0.00
March 0.00 0.00 0.133075E+12 0.397478E+11 0.00 0.00
April 0.00 0.00 0.213737E+12 0.521847E+11 0.00 0.00
May 0.00 0.00 0.585923E+11 0.256802E+11 0.00 0.00
June 0.00 0.00 0.121400E+12 0.364120E+11 0.00 0.00
July 0.00 0.00 0.185968E+12 0.482520E+11 0.00 0.00
August 0.00 0.00 0.238420E+12 0.558137E+11 0.00 0.00
September 0.00 0.00 0.437767E+11 0.223353E+11 0.00 0.00
October 0.00 0.00 0.791965E+11 0.296318E+11 0.00 0.00
November 0.00 0.00 0.108832E+12 0.351643E+11 0.00 0.00
December 0.00 0.00 0.166907E+12 0.460866E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.140002E+13 0.428671E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.173925E+09 0.142948E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.238420E+12 0.558137E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.143856E+10 0.00 0.00
February 0.00 0.00 0.270061E+10 0.186453E+10 0.00 0.00
March 0.00 0.00 0.105974E+11 0.350515E+10 0.00 0.00
April 0.00 0.00 0.193560E+11 0.490625E+10 0.00 0.00
May 0.00 0.00 0.500633E+10 0.242570E+10 0.00 0.00
June 0.00 0.00 0.119445E+11 0.362523E+10 0.00 0.00
July 0.00 0.00 0.184224E+11 0.481695E+10 0.00 0.00
August 0.00 0.00 0.233882E+11 0.553208E+10 0.00 0.00
September 0.00 0.00 0.245453E+10 0.188504E+10 0.00 0.00
October 0.00 0.00 0.489965E+10 0.241581E+10 0.00 0.00
November 0.00 0.00 0.820782E+10 0.303808E+10 0.00 0.00
December 0.00 0.00 0.141382E+11 0.417972E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.121116E+12 0.396331E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.143856E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.233882E+11 0.553208E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.290841E+10 4198159.85 0.363351E+11 0.559635E+11 0.00 0.00 0.00 0.00
February 0.281740E+10 15114321.99 0.186478E+11 0.447512E+11 0.00 0.00 0.00 0.00
March 0.441750E+10 40584701.93 0.587492E+10 0.461006E+11 0.00 0.00 0.00 0.00
April 0.757680E+10 73221186.88 0.554942E+09 0.939012E+10 0.00 0.00 0.00 0.00
May 0.846443E+10 0.843258E+10 28572665.10 0.522483E+09 0.00 0.00 0.00 0.00
June 0.110868E+11 0.389659E+11 101.99 0.211125E+09 1094838.71 0.00 0.00 0.00
July 0.117090E+11 0.526532E+11 0.00 0.409989E+09 0.124669E+09 0.00 0.00 0.00
August 0.117810E+11 0.300603E+11 19769940.67 0.142941E+09 234796.25 0.00 0.00 0.00
September 0.517346E+10 0.499455E+09 0.216608E+09 0.406943E+10 0.00 0.00 0.00 0.00
October 0.400988E+10 30516028.97 0.142676E+10 0.287234E+11 0.00 0.00 0.00 0.00
November 0.308510E+10 29350106.65 0.260310E+11 0.532586E+11 0.00 0.00 0.00 0.00
December 0.299294E+10 5485206.33 0.432775E+11 0.493039E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.760227E+11 0.130810E+12 0.132413E+12 0.292847E+12 0.125999E+09 0.00 0.00 0.00
Minimum of Months 0.281740E+10 4198159.85 0.00 0.142941E+09 0.00 0.00 0.00 0.00
Maximum of Months 0.117810E+11 0.526532E+11 0.432775E+11 0.559635E+11 0.124669E+09 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.376272E+11 15396889.47 0.678480E+12 0.554774E+12 0.00 0.00 0.00 0.00
February 0.310700E+11 37337995.78 0.387244E+12 0.470627E+12 0.00 0.00 0.00 0.00
March 0.333442E+11 0.182132E+09 0.170405E+12 0.534151E+12 0.00 0.00 0.00 0.00
April 0.422128E+11 0.517552E+09 0.235694E+11 0.146649E+12 0.00 0.00 0.00 0.00
May 0.673669E+11 0.750780E+11 0.499227E+09 0.714262E+10 0.00 0.00 0.00 0.00
June 0.852011E+11 0.331807E+12 2326720.55 0.254303E+10 13298576.49 0.00 0.00 0.00
July 0.807634E+11 0.429244E+12 0.00 0.436693E+10 0.132798E+10 0.00 0.00 0.00
August 0.714200E+11 0.231058E+12 0.509227E+09 0.324912E+10 0.00 0.00 0.00 0.00
September 0.378276E+11 0.426428E+10 0.807395E+10 0.652878E+11 0.00 0.00 0.00 0.00
October 0.294034E+11 57149762.41 0.971770E+11 0.348325E+12 0.00 0.00 0.00 0.00
November 0.322409E+11 30054792.72 0.526777E+12 0.548262E+12 0.00 0.00 0.00 0.00
December 0.349080E+11 5115440.41 0.767876E+12 0.484112E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.583385E+12 0.107230E+13 0.266061E+13 0.316949E+13 0.134128E+10 0.00 0.00 0.00
Minimum of Months 0.294034E+11 5115440.41 0.00 0.254303E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.852011E+11 0.429244E+12 0.767876E+12 0.554774E+12 0.132798E+10 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.481402E+10 425207.57 0.127765E+12 0.542642E+11 0.00 0.00 0.00 0.00
February 0.411950E+10 3476096.06 0.853663E+11 0.476782E+11 0.00 0.00 0.00 0.00
March 0.415823E+10 13933196.64 0.506183E+11 0.562345E+11 0.00 0.00 0.00 0.00
April 0.369741E+10 39322996.83 0.122492E+11 0.183346E+11 0.00 0.00 0.00 0.00
May 0.535243E+10 0.719992E+10 0.323891E+09 0.120425E+10 0.00 0.00 0.00 0.00
June 0.812215E+10 0.347188E+11 1903402.42 0.144690E+09 5212181.82 0.00 0.00 0.00
July 0.763613E+10 0.447259E+11 35379.67 0.274697E+09 0.100796E+09 0.00 0.00 0.00
August 0.607261E+10 0.232185E+11 0.182957E+09 0.668214E+09 0.00 0.00 0.00 0.00
September 0.305320E+10 0.304765E+09 0.598614E+10 0.102420E+11 0.00 0.00 0.00 0.00
October 0.359286E+10 7962375.04 0.374304E+11 0.391141E+11 0.00 0.00 0.00 0.00
November 0.452707E+10 103733.72 0.110257E+12 0.532569E+11 0.00 0.00 0.00 0.00
December 0.494275E+10 656271.04 0.139993E+12 0.469131E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.600884E+11 0.110234E+12 0.570173E+12 0.328329E+12 0.106009E+09 0.00 0.00 0.00
Minimum of Months 0.305320E+10 103733.72 35379.67 0.144690E+09 0.00 0.00 0.00 0.00
Maximum of Months 0.812215E+10 0.447259E+11 0.139993E+12 0.562345E+11 0.100796E+09 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.115651E+11 11359025.64 0.379084E+10 0.373416E+11 0.00 0.00 0.00 0.00
February 0.106164E+11 23090215.37 0.146934E+10 0.247187E+11 0.00 0.00 0.00 0.00
March 0.129531E+11 38291662.31 0.180762E+09 0.215831E+11 0.00 0.00 0.00 0.00
April 0.121984E+11 17735853.64 0.00 0.345706E+10 0.00 0.00 0.00 0.00
May 0.128853E+11 0.274365E+10 0.00 0.648411E+09 0.00 0.00 0.00 0.00
June 0.131425E+11 0.172795E+11 0.00 0.469512E+09 1869014.90 0.00 0.00 0.00
July 0.127648E+11 0.262407E+11 0.00 0.530006E+09 79709394.52 0.00 0.00 0.00
August 0.140297E+11 0.141080E+11 0.00 0.388887E+09 0.00 0.00 0.00 0.00
September 0.128560E+11 46509867.81 0.00 0.122175E+10 0.00 0.00 0.00 0.00
October 0.124569E+11 38196331.69 0.00 0.850197E+10 0.00 0.00 0.00 0.00
November 0.115347E+11 41158273.76 0.207940E+10 0.240676E+11 0.00 0.00 0.00 0.00
December 0.115049E+11 17896533.94 0.275334E+10 0.309190E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.148508E+12 0.606060E+11 0.102737E+11 0.153848E+12 81578409.42 0.00 0.00 0.00
Minimum of Months 0.106164E+11 11359025.64 0.00 0.388887E+09 0.00 0.00 0.00 0.00
Maximum of Months 0.140297E+11 0.262407E+11 0.379084E+10 0.373416E+11 79709394.52 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.148551E+10 0.136356E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.134175E+10 0.677844E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.148551E+10 0.137858E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.143759E+10 0.196094E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.148551E+10 0.544636E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.143759E+10 0.105824E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.148551E+10 0.160921E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.148551E+10 0.208821E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.143759E+10 0.476566E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.148551E+10 0.904364E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.143759E+10 0.123807E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.148551E+10 0.175148E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.174906E+11 0.138245E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.134175E+10 0.136356E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.148551E+10 0.208821E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.142384E+11 0.117589E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.128605E+11 0.397329E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.142384E+11 0.107566E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.137791E+11 0.175332E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.142384E+11 0.471505E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.137791E+11 0.987670E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.142384E+11 0.151954E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.142384E+11 0.196844E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.137791E+11 0.352204E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.142384E+11 0.638031E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.137791E+11 0.874471E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.142384E+11 0.135059E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.167646E+12 0.113899E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.128605E+11 0.117589E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.142384E+11 0.196844E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.143856E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.129934E+10 0.213543E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.143856E+10 0.853085E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.139215E+10 0.158419E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.143856E+10 0.401918E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139215E+10 0.971143E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.143856E+10 0.150440E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.143856E+10 0.192946E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.139215E+10 0.196165E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.143856E+10 0.392240E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.139215E+10 0.656189E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.143856E+10 0.113970E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.169379E+11 0.984204E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.129934E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.143856E+10 0.192946E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.290841E+10 0.363351E+11 4198159.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.281740E+10 0.186478E+11 15114321.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.441750E+10 0.587492E+10 40584701.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.757680E+10 0.554942E+09 73221186.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.846443E+10 28572665.10 0.843258E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.110868E+11 101.99 0.389659E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.117090E+11 0.00 0.526532E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.117810E+11 19769940.67 0.300603E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.517346E+10 0.216608E+09 0.499455E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.400988E+10 0.142676E+10 30516028.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.308510E+10 0.260310E+11 29350106.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.299294E+10 0.432775E+11 5485206.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.760227E+11 0.132413E+12 0.130810E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.281740E+10 0.00 4198159.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.117810E+11 0.432775E+11 0.526532E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.376272E+11 0.678480E+12 15396889.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.310700E+11 0.387244E+12 37337995.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.333442E+11 0.170405E+12 0.182132E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.422128E+11 0.235694E+11 0.517552E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.673669E+11 0.499227E+09 0.750780E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.852011E+11 2326720.55 0.331807E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.807634E+11 0.00 0.429244E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.714200E+11 0.509227E+09 0.231058E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.378276E+11 0.807395E+10 0.426428E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.294034E+11 0.971770E+11 57149762.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.322409E+11 0.526777E+12 30054792.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.349080E+11 0.767876E+12 5115440.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.583385E+12 0.266061E+13 0.107230E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.294034E+11 0.00 5115440.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.852011E+11 0.767876E+12 0.429244E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.481402E+10 0.127765E+12 425207.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.411950E+10 0.853663E+11 3476096.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.415823E+10 0.506183E+11 13933196.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.369741E+10 0.122492E+11 39322996.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.535243E+10 0.323891E+09 0.719992E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.812215E+10 1903402.42 0.347188E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.763613E+10 35379.67 0.447259E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.607261E+10 0.182957E+09 0.232185E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.305320E+10 0.598614E+10 0.304765E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.359286E+10 0.374304E+11 7962375.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.452707E+10 0.110257E+12 103733.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.494275E+10 0.139993E+12 656271.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.600884E+11 0.570173E+12 0.110234E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.305320E+10 35379.67 103733.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.812215E+10 0.139993E+12 0.447259E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.115651E+11 0.379084E+10 11359025.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.106164E+11 0.146934E+10 23090215.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.129531E+11 0.180762E+09 38291662.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.121984E+11 0.00 17735853.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.128853E+11 0.00 0.274365E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.131425E+11 0.00 0.172795E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.127648E+11 0.00 0.262407E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.140297E+11 0.00 0.141080E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128560E+11 0.00 46509867.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.124569E+11 0.00 38196331.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.115347E+11 0.207940E+10 41158273.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.115049E+11 0.275334E+10 17896533.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.148508E+12 0.102737E+11 0.606060E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.106164E+11 0.00 11359025.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140297E+11 0.379084E+10 0.262407E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.148551E+10 0.00 0.175436E+10 0.00 0.390796E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.134175E+10 0.00 0.845531E+10 0.00 0.167686E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.148551E+10 0.00 0.169818E+11 0.00 0.319600E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.143759E+10 0.00 0.238655E+11 0.00 0.425614E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.148551E+10 0.00 0.675692E+10 0.00 0.131056E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.143759E+10 0.00 0.129997E+11 0.00 0.241732E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.148551E+10 0.00 0.196868E+11 0.00 0.359473E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.148551E+10 0.00 0.252812E+11 0.00 0.439914E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.143759E+10 0.00 0.589992E+10 0.00 0.113426E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.148551E+10 0.00 0.111694E+11 0.00 0.212575E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.143759E+10 0.00 0.153124E+11 0.00 0.293168E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.148551E+10 0.00 0.215309E+11 0.00 0.401611E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.174906E+11 0.00 0.169694E+12 0.00 0.314493E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.134175E+10 0.00 0.175436E+10 0.00 0.390796E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.148551E+10 0.00 0.252812E+11 0.00 0.439914E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.142384E+11 0.00 0.173925E+09 0.00 56336011.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.128605E+11 0.00 0.499402E+11 0.00 0.102073E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.142384E+11 0.00 0.133075E+12 0.00 0.255093E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.137791E+11 0.00 0.213737E+12 0.00 0.384056E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.142384E+11 0.00 0.585923E+11 0.00 0.114418E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.137791E+11 0.00 0.121400E+12 0.00 0.226329E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.142384E+11 0.00 0.185968E+12 0.00 0.340135E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.142384E+11 0.00 0.238420E+12 0.00 0.415753E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.137791E+11 0.00 0.437767E+11 0.00 0.855622E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.142384E+11 0.00 0.791965E+11 0.00 0.153934E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.137791E+11 0.00 0.108832E+12 0.00 0.213852E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.142384E+11 0.00 0.166907E+12 0.00 0.318481E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.167646E+12 0.00 0.140002E+13 0.00 0.261025E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.128605E+11 0.00 0.173925E+09 0.00 56336011.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.142384E+11 0.00 0.238420E+12 0.00 0.415753E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.143856E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.129934E+10 0.00 0.270061E+10 0.00 0.565182E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.143856E+10 0.00 0.105974E+11 0.00 0.206659E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.139215E+10 0.00 0.193560E+11 0.00 0.351410E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.143856E+10 0.00 0.500633E+10 0.00 0.987146E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139215E+10 0.00 0.119445E+11 0.00 0.223307E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.143856E+10 0.00 0.184224E+11 0.00 0.337839E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.143856E+10 0.00 0.233882E+11 0.00 0.409352E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.139215E+10 0.00 0.245453E+10 0.00 0.492884E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.143856E+10 0.00 0.489965E+10 0.00 0.977249E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.139215E+10 0.00 0.820782E+10 0.00 0.164593E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.143856E+10 0.00 0.141382E+11 0.00 0.274116E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.169379E+11 0.00 0.121116E+12 0.00 0.226952E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.129934E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.143856E+10 0.00 0.233882E+11 0.00 0.409352E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.247555E+11 0.00 0.00 30511649.08 0.00 0.00 0.260018E+11 0.00 0.32
February 0.144605E+11 0.00 0.00 43694623.23 0.00 0.00 0.331698E+11 0.00 0.33
March 0.536087E+10 0.00 0.00 82637189.86 0.00 0.00 0.524465E+11 0.00 0.37
April 0.434492E+09 0.00 0.00 95971178.83 0.00 0.00 0.614071E+11 0.00 0.54
May 0.190283E+09 0.00 0.00 97273308.66 0.00 0.00 0.647146E+11 0.00 0.95
June 0.127860E+09 249938.49 0.00 0.103974E+09 0.00 0.00 0.529050E+11 0.00 1.25
July 0.127704E+09 0.121406E+09 0.00 0.107747E+09 26376256.32 0.00 0.450098E+11 0.00 1.16
August 0.158685E+09 0.00 0.00 0.120143E+09 0.00 0.00 0.645624E+11 0.00 1.22
September 0.336582E+09 0.00 0.00 0.101493E+09 0.00 0.00 0.659106E+11 0.00 0.70
October 0.695821E+09 0.00 0.00 99175725.43 0.00 0.00 0.617237E+11 0.00 0.44
November 0.199392E+11 0.00 0.00 63708728.98 0.00 0.00 0.407101E+11 0.00 0.33
December 0.347438E+11 0.00 0.00 31876062.69 0.00 0.00 0.236954E+11 0.00 0.32
                   
Annual Sum or Average 0.101331E+12 0.121656E+09 0.00 0.978205E+09 26376256.32 0.00 0.592257E+12 0.00 0.66
Minimum of Months 0.127704E+09 0.00 0.00 30511649.08 0.00 0.00 0.236954E+11 0.00 0.32
Maximum of Months 0.347438E+11 0.121406E+09 0.00 0.120143E+09 26376256.32 0.00 0.659106E+11 0.00 1.25



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.321041E+11 0.00 0.00 6789503.96 0.00 0.00 0.853665E+10 0.00 0.28
February 0.201113E+11 0.00 0.00 21453282.49 0.00 0.00 0.166116E+11 0.00 0.30
March 0.906423E+10 0.00 0.00 57473583.93 0.00 0.00 0.368629E+11 0.00 0.35
April 0.826643E+10 0.00 0.00 78166131.00 0.00 0.00 0.497413E+11 0.00 0.52
May 0.759312E+10 0.00 0.00 76524461.09 0.00 0.00 0.497332E+11 0.00 0.78
June 0.895681E+10 82302.96 0.00 80997075.07 0.00 0.00 0.402809E+11 0.00 1.01
July 0.142609E+11 0.104489E+09 0.00 78704490.34 28180919.57 0.00 0.329659E+11 0.00 1.03
August 0.139757E+11 0.00 0.00 89475834.41 0.00 0.00 0.496942E+11 0.00 1.06
September 0.470444E+10 0.00 0.00 66529950.47 0.00 0.00 0.455703E+11 0.00 0.52
October 0.538233E+10 0.00 0.00 57220969.98 0.00 0.00 0.375438E+11 0.00 0.36
November 0.177339E+11 0.00 0.00 28176540.16 0.00 0.00 0.265395E+11 0.00 0.30
December 0.228595E+11 0.00 0.00 18874500.82 0.00 0.00 0.261049E+11 0.00 0.29
                   
Annual Sum or Average 0.165013E+12 0.104571E+09 0.00 0.660386E+09 28180919.57 0.00 0.420185E+12 0.00 0.57
Minimum of Months 0.470444E+10 0.00 0.00 6789503.96 0.00 0.00 0.853665E+10 0.00 0.28
Maximum of Months 0.321041E+11 0.104489E+09 0.00 89475834.41 28180919.57 0.00 0.497413E+11 0.00 1.06



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.359096E+12 0.00 0.00 0.00 0.00 0.214069E+11 0.00 0.00 0.28
February 0.307972E+12 0.00 0.00 0.00 0.00 0.771654E+10 0.00 0.00 0.29
March 0.267437E+12 0.00 0.00 37359163.16 0.00 0.296537E+09 0.442920E+11 0.00 0.30
April 0.140464E+12 0.00 0.00 0.266345E+09 0.00 0.00 0.213819E+12 0.00 0.36
May 0.700449E+11 0.00 0.00 0.559855E+09 0.00 0.00 0.396039E+12 0.00 0.65
June 0.541934E+11 1097304.04 0.00 0.624065E+09 0.00 0.00 0.326184E+12 0.00 0.80
July 0.581816E+11 0.898724E+09 0.00 0.600554E+09 0.284499E+09 0.00 0.262191E+12 0.00 0.74
August 0.467263E+11 0.00 0.00 0.637332E+09 0.00 0.00 0.370796E+12 0.00 0.72
September 0.102865E+12 0.00 0.00 0.347779E+09 0.00 0.00 0.274717E+12 0.00 0.42
October 0.200742E+12 0.00 0.00 86061734.06 0.00 0.140391E+09 0.828287E+11 0.00 0.29
November 0.357574E+12 0.00 0.00 0.00 0.00 0.881322E+10 0.00 0.00 0.28
December 0.435735E+12 0.00 0.00 0.00 0.00 0.968395E+10 0.00 0.00 0.28
                   
Annual Sum or Average 0.240103E+13 0.899822E+09 0.00 0.315935E+10 0.284499E+09 0.480575E+11 0.197087E+13 0.00 0.45
Minimum of Months 0.467263E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.435735E+12 0.898724E+09 0.00 0.637332E+09 0.284499E+09 0.214069E+11 0.396039E+12 0.00 0.80



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.134642E+11 0.00 0.00 0.00 0.00 0.177100E+11 0.00 0.00 0.26
February 0.136930E+11 0.00 0.00 0.00 0.00 0.111918E+11 0.00 0.00 0.27
March 0.190075E+11 0.00 0.00 0.00 0.00 0.518066E+10 0.00 0.00 0.29
April 0.198226E+11 0.00 0.00 4763290.04 0.00 0.754574E+09 0.587598E+10 0.00 0.31
May 0.118964E+11 0.00 0.00 34434313.80 0.00 0.00 0.273348E+11 0.00 0.57
June 0.639066E+10 2992389.82 0.00 55022705.63 4352091.79 0.00 0.305142E+11 0.00 0.79
July 0.626497E+10 77891077.56 0.00 52453705.62 27663211.67 0.00 0.237905E+11 0.00 0.73
August 0.744096E+10 0.00 0.00 46805070.28 0.00 0.00 0.281293E+11 0.00 0.66
September 0.197056E+11 0.00 0.00 4983821.97 0.00 0.260460E+09 0.614178E+10 0.00 0.34
October 0.176104E+11 0.00 0.00 0.00 0.00 0.309985E+10 0.00 0.00 0.27
November 0.151298E+11 0.00 0.00 0.00 0.00 0.150354E+11 0.00 0.00 0.26
December 0.178589E+11 0.00 0.00 0.00 0.00 0.192263E+11 0.00 0.00 0.25
                   
Annual Sum or Average 0.168285E+12 80883467.38 0.00 0.198463E+09 32015303.46 0.724592E+11 0.121787E+12 0.00 0.42
Minimum of Months 0.626497E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.25
Maximum of Months 0.198226E+11 77891077.56 0.00 55022705.63 27663211.67 0.192263E+11 0.305142E+11 0.00 0.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.109763E+10 0.00 0.00 0.00 0.00 0.401972E+10 0.00 0.00 0.28
February 0.220865E+10 0.00 0.00 0.00 0.00 0.208618E+10 0.00 0.00 0.27
March 0.354929E+10 0.00 0.00 165410.39 0.00 0.699305E+09 0.244556E+09 0.00 0.28
April 0.264381E+10 0.00 0.00 3400997.58 0.00 0.00 0.287084E+10 0.00 0.40
May 0.115837E+10 0.00 0.00 9000592.39 0.00 0.00 0.611502E+10 0.00 0.81
June 0.907771E+09 15855.25 0.00 15602415.00 0.00 0.00 0.704674E+10 0.00 1.31
July 0.169153E+10 18344493.95 0.00 13574930.11 3060838.65 0.00 0.531082E+10 0.00 1.27
August 0.187866E+10 0.00 0.00 10686749.91 0.00 0.00 0.600764E+10 0.00 1.10
September 0.241152E+10 0.00 0.00 2728947.15 0.00 0.00 0.246377E+10 0.00 0.41
October 0.338819E+10 0.00 0.00 487810.96 0.00 92741539.28 0.521533E+09 0.00 0.27
November 0.250228E+10 0.00 0.00 0.00 0.00 0.252185E+10 0.00 0.00 0.27
December 0.157549E+10 0.00 0.00 0.00 0.00 0.428450E+10 0.00 0.00 0.27
                   
Annual Sum or Average 0.250132E+11 18360349.20 0.00 55647853.49 3060838.65 0.137043E+11 0.305809E+11 0.00 0.58
Minimum of Months 0.907771E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.27
Maximum of Months 0.354929E+10 18344493.95 0.00 15602415.00 3060838.65 0.428450E+10 0.704674E+10 0.00 1.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.784397E+09 0.00 0.00 0.00 0.00 0.403763E+10 0.00 0.00 0.41
February 0.219901E+10 0.00 0.00 0.00 0.00 0.185685E+10 0.00 0.00 0.40
March 0.298561E+10 0.00 0.00 1492071.28 0.00 0.530368E+09 0.104541E+10 0.00 0.43
April 0.233670E+10 0.00 0.00 5148914.09 0.00 12081842.79 0.377187E+10 0.00 0.67
May 0.103001E+10 0.00 0.00 13059181.07 0.00 0.00 0.827041E+10 0.00 1.54
June 0.979456E+09 14840.94 0.00 13299029.88 0.00 0.00 0.692416E+10 0.00 1.94
July 0.162972E+10 12868016.99 0.00 12812809.89 2844626.24 0.00 0.522383E+10 0.00 1.91
August 0.190222E+10 0.00 0.00 9862389.91 0.00 0.00 0.597046E+10 0.00 1.60
September 0.209925E+10 0.00 0.00 3634250.39 0.00 0.00 0.282910E+10 0.00 0.63
October 0.303947E+10 0.00 0.00 660793.63 0.00 0.179380E+09 0.630753E+09 0.00 0.40
November 0.179260E+10 0.00 0.00 0.00 0.00 0.296197E+10 0.00 0.00 0.39
December 0.612436E+09 0.00 0.00 0.00 0.00 0.493308E+10 0.00 0.00 0.39
                   
Annual Sum or Average 0.213909E+11 12882857.93 0.00 59969440.13 2844626.24 0.145114E+11 0.346660E+11 0.00 0.90
Minimum of Months 0.612436E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.39
Maximum of Months 0.303947E+10 12868016.99 0.00 13299029.88 2844626.24 0.493308E+10 0.827041E+10 0.00 1.94



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.131043E+10 0.00 0.00 0.00 0.00 0.605665E+10 0.00 0.00 0.40
February 0.328973E+10 0.00 0.00 811109.85 0.00 0.245307E+10 0.640514E+09 0.00 0.41
March 0.385154E+10 0.00 0.00 6000354.61 0.00 0.772530E+09 0.399848E+10 0.00 0.52
April 0.309290E+10 0.00 0.00 13629800.65 0.00 25974618.74 0.977555E+10 0.00 0.99
May 0.220446E+10 0.00 0.00 16198307.06 0.00 0.00 0.103294E+11 0.00 1.48
June 0.161697E+10 34989.93 0.00 18023425.79 0.00 0.00 0.860897E+10 0.00 1.83
July 0.253048E+10 33580929.78 0.00 18902480.32 3578687.18 0.00 0.638652E+10 0.00 1.81
August 0.290497E+10 0.00 0.00 18653064.32 0.00 0.00 0.956550E+10 0.00 1.86
September 0.319762E+10 0.00 0.00 7632128.58 0.00 0.00 0.595759E+10 0.00 0.81
October 0.436390E+10 0.00 0.00 2452725.41 0.00 0.279271E+09 0.200404E+10 0.00 0.45
November 0.329991E+10 0.00 0.00 125296.36 0.00 0.389140E+10 94413965.22 0.00 0.39
December 0.130194E+10 0.00 0.00 0.00 0.00 0.716374E+10 0.00 0.00 0.39
                   
Annual Sum or Average 0.329648E+11 33615919.71 0.00 0.102429E+09 3578687.18 0.206426E+11 0.573610E+11 0.00 0.95
Minimum of Months 0.130194E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.39
Maximum of Months 0.436390E+10 33580929.78 0.00 18902480.32 3578687.18 0.716374E+10 0.103294E+11 0.00 1.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.318617E+10 0.00 0.00 0.00 0.00 0.258828E+10 0.00 0.00 0.49
February 0.430140E+10 0.00 0.00 39355.37 0.00 0.478119E+09 78673593.91 0.00 0.48
March 0.311569E+10 0.00 0.00 2775547.79 0.00 44520521.54 0.246427E+10 0.00 0.53
April 0.782229E+09 0.00 0.00 15193181.31 0.00 0.00 0.949814E+10 0.00 1.21
May 0.912532E+09 0.00 0.00 12673944.70 0.00 0.00 0.747944E+10 0.00 1.51
June 0.761161E+09 14716.55 0.00 18660692.10 0.00 0.00 0.760436E+10 0.00 2.32
July 0.118588E+10 31872233.97 0.00 19468073.65 879421.57 0.00 0.663024E+10 0.00 2.34
August 0.113961E+10 0.00 0.00 20662927.95 0.00 0.00 0.957902E+10 0.00 2.41
September 0.176268E+10 0.00 0.00 4924987.25 0.00 0.00 0.416049E+10 0.00 0.80
October 0.291243E+10 0.00 0.00 1660152.46 0.00 223879.30 0.178838E+10 0.00 0.50
November 0.558709E+10 0.00 0.00 12395.33 0.00 91232565.17 16481053.15 0.00 0.47
December 0.662813E+10 0.00 0.00 0.00 0.00 8191293.67 0.00 0.00 0.47
                   
Annual Sum or Average 0.322750E+11 31886950.51 0.00 96071257.92 879421.57 0.321057E+10 0.492995E+11 0.00 1.13
Minimum of Months 0.761161E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.47
Maximum of Months 0.662813E+10 31872233.97 0.00 20662927.95 879421.57 0.258828E+10 0.957902E+10 0.00 2.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.671636E+09 0.00 0.00 0.00 0.00 0.545211E+11 0.00 0.00 0.31
February 0.248146E+10 0.00 0.00 0.00 0.00 0.417398E+11 0.00 0.00 0.30
March 0.135835E+11 0.00 0.00 0.00 0.00 0.273934E+11 0.00 0.00 0.30
April 0.308943E+11 0.00 0.00 3153053.89 0.00 0.426940E+10 0.417595E+10 0.00 0.32
May 0.143949E+11 0.00 0.00 58553008.42 0.00 0.00 0.422716E+11 0.00 0.65
June 0.550769E+10 222617.69 0.00 0.129628E+09 0.00 0.00 0.587535E+11 0.00 1.09
July 0.671642E+10 0.158225E+09 0.00 0.108565E+09 33087234.79 0.00 0.426458E+11 0.00 0.96
August 0.128386E+11 0.00 0.00 63806389.76 0.00 0.00 0.367583E+11 0.00 0.72
September 0.320457E+11 0.00 0.00 5224209.79 0.00 0.114876E+10 0.641230E+10 0.00 0.35
October 0.191760E+11 0.00 0.00 0.00 0.00 0.158986E+11 0.00 0.00 0.28
November 0.695316E+09 0.00 0.00 0.00 0.00 0.501647E+11 0.00 0.00 0.30
December 0.804329E+09 0.00 0.00 0.00 0.00 0.620504E+11 0.00 0.00 0.31
                   
Annual Sum or Average 0.139810E+12 0.158447E+09 0.00 0.368930E+09 33087234.79 0.257186E+12 0.191017E+12 0.00 0.49
Minimum of Months 0.671636E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.320457E+11 0.158225E+09 0.00 0.129628E+09 33087234.79 0.620504E+11 0.587535E+11 0.00 1.09



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.836472E+09 0.00 0.00 0.00 0.00 0.490196E+11 0.00 0.00 0.45
February 0.576138E+10 0.00 0.00 0.00 0.00 0.354615E+11 0.00 0.00 0.45
March 0.223856E+11 0.00 0.00 3560159.58 0.00 0.155574E+11 0.252057E+10 0.00 0.47
April 0.206773E+11 0.00 0.00 33780263.35 0.00 0.231733E+10 0.259644E+11 0.00 0.61
May 0.102522E+11 0.00 0.00 0.124267E+09 0.00 0.00 0.785780E+11 0.00 1.50
June 0.655150E+10 239890.90 0.00 0.132399E+09 0.00 0.00 0.685315E+11 0.00 1.88
July 0.694792E+10 0.139916E+09 0.00 0.133646E+09 30533274.61 0.00 0.527656E+11 0.00 1.77
August 0.980925E+10 0.00 0.00 91463610.00 0.00 0.00 0.551375E+11 0.00 1.37
September 0.270614E+11 0.00 0.00 19368368.80 0.00 0.874543E+09 0.163196E+11 0.00 0.60
October 0.217350E+11 0.00 0.00 847437.13 0.00 0.129791E+11 0.878626E+09 0.00 0.45
November 0.758923E+09 0.00 0.00 0.00 0.00 0.469789E+11 0.00 0.00 0.45
December 0.924347E+09 0.00 0.00 0.00 0.00 0.571426E+11 0.00 0.00 0.44
                   
Annual Sum or Average 0.133701E+12 0.140156E+09 0.00 0.539332E+09 30533274.61 0.220331E+12 0.300696E+12 0.00 0.87
Minimum of Months 0.758923E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.44
Maximum of Months 0.270614E+11 0.139916E+09 0.00 0.133646E+09 30533274.61 0.571426E+11 0.785780E+11 0.00 1.88



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.532348E+10 0.00 0.00 0.00 0.00 0.691495E+11 0.00 0.00 0.43
February 0.198363E+11 0.00 0.00 4491211.78 0.00 0.388975E+11 0.321631E+10 0.00 0.44
March 0.292287E+11 0.00 0.00 50586171.16 0.00 0.172231E+11 0.292413E+11 0.00 0.57
April 0.238841E+11 0.00 0.00 0.129090E+09 0.00 0.207279E+10 0.878970E+11 0.00 0.94
May 0.215787E+11 0.00 0.00 0.165482E+09 0.00 0.00 0.100869E+12 0.00 1.48
June 0.143004E+11 539162.63 0.00 0.169752E+09 0.00 0.00 0.782398E+11 0.00 1.71
July 0.133097E+11 0.373753E+09 0.00 0.176642E+09 29083281.56 0.00 0.575964E+11 0.00 1.58
August 0.165947E+11 0.00 0.00 0.172113E+09 0.00 0.00 0.848273E+11 0.00 1.59
September 0.321841E+11 0.00 0.00 73043853.85 0.00 0.567395E+09 0.552379E+11 0.00 0.82
October 0.330735E+11 0.00 0.00 18233267.44 0.00 0.130179E+11 0.131780E+11 0.00 0.48
November 0.966776E+10 0.00 0.00 533507.02 0.00 0.611853E+11 0.393942E+09 0.00 0.43
December 0.139392E+10 0.00 0.00 0.00 0.00 0.854554E+11 0.00 0.00 0.43
                   
Annual Sum or Average 0.220375E+12 0.374292E+09 0.00 0.959967E+09 29083281.56 0.287569E+12 0.510697E+12 0.00 0.91
Minimum of Months 0.139392E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
Maximum of Months 0.330735E+11 0.373753E+09 0.00 0.176642E+09 29083281.56 0.854554E+11 0.100869E+12 0.00 1.71



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.999984E+09 0.00 0.00 0.00 0.00 0.488982E+11 0.00 0.00 0.45
February 0.729607E+10 0.00 0.00 0.00 0.00 0.339276E+11 0.00 0.00 0.46
March 0.218984E+11 0.00 0.00 1156290.46 0.00 0.173574E+11 0.121478E+10 0.00 0.47
April 0.245409E+11 0.00 0.00 36026596.45 0.00 0.114123E+10 0.272897E+11 0.00 0.69
May 0.145621E+11 0.00 0.00 79185950.75 0.00 0.00 0.467123E+11 0.00 1.14
June 0.655131E+10 162859.63 0.00 0.118362E+09 0.00 0.00 0.482539E+11 0.00 1.62
July 0.757021E+10 0.232488E+09 0.00 95934565.42 21911974.37 0.00 0.334611E+11 0.00 1.38
August 0.118961E+11 0.00 0.00 78391471.40 0.00 0.00 0.380569E+11 0.00 1.22
September 0.310343E+11 0.00 0.00 12366864.54 0.00 0.369389E+09 0.119193E+11 0.00 0.60
October 0.238566E+11 0.00 0.00 155737.79 0.00 0.117860E+11 0.212195E+09 0.00 0.45
November 0.328166E+10 0.00 0.00 0.00 0.00 0.444662E+11 0.00 0.00 0.45
December 0.160002E+10 0.00 0.00 0.00 0.00 0.564140E+11 0.00 0.00 0.44
                   
Annual Sum or Average 0.155088E+12 0.232651E+09 0.00 0.421580E+09 21911974.37 0.214360E+12 0.207120E+12 0.00 0.78
Minimum of Months 0.999984E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.44
Maximum of Months 0.310343E+11 0.232488E+09 0.00 0.118362E+09 21911974.37 0.564140E+11 0.482539E+11 0.00 1.62



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 45272445.11 0.00 0.00 0.00 0.00 0.647297E+10 0.00 0.00 0.40
February 50639060.26 0.00 0.00 0.00 0.00 0.482589E+10 0.00 0.00 0.38
March 0.346288E+09 0.00 0.00 0.00 0.00 0.397434E+10 0.00 0.00 0.39
April 0.298048E+10 0.00 0.00 0.00 0.00 0.124011E+10 0.00 0.00 0.40
May 0.323668E+10 0.00 0.00 2540149.88 0.00 43303217.12 0.228068E+10 0.00 0.64
June 0.901944E+09 1049705.48 0.00 11131438.11 411884.22 0.00 0.532659E+10 0.00 1.09
July 0.113362E+10 13863573.36 0.00 9084153.03 4071349.04 0.00 0.367042E+10 0.00 0.97
August 0.235391E+10 0.00 0.00 4080918.33 0.00 35437057.07 0.251640E+10 0.00 0.73
September 0.322583E+10 0.00 0.00 0.00 0.00 0.930237E+09 0.00 0.00 0.43
October 0.640065E+09 0.00 0.00 0.00 0.00 0.279810E+10 0.00 0.00 0.36
November 37913847.84 0.00 0.00 0.00 0.00 0.595980E+10 0.00 0.00 0.38
December 56348740.89 0.00 0.00 0.00 0.00 0.765327E+10 0.00 0.00 0.41
                   
Annual Sum or Average 0.150090E+11 14913278.85 0.00 26836659.35 4483233.26 0.339335E+11 0.137941E+11 0.00 0.55
Minimum of Months 37913847.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.36
Maximum of Months 0.323668E+10 13863573.36 0.00 11131438.11 4071349.04 0.765327E+10 0.532659E+10 0.00 1.09



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 35972925.42 0.00 0.00 0.00 0.00 0.446003E+10 0.00 0.00 0.44
February 98208654.23 0.00 0.00 0.00 0.00 0.329554E+10 0.00 0.00 0.43
March 0.107982E+10 0.00 0.00 9936.33 0.00 0.210507E+10 14242501.65 0.00 0.45
April 0.181539E+10 0.00 0.00 1712880.37 0.00 0.519715E+09 0.130886E+10 0.00 0.53
May 0.104275E+10 0.00 0.00 10576232.76 0.00 2077526.67 0.671630E+10 0.00 1.36
June 0.643600E+09 475903.22 0.00 13028630.13 547600.36 0.00 0.676095E+10 0.00 1.88
July 0.706469E+09 12457001.02 0.00 12857566.64 2871134.74 0.00 0.511910E+10 0.00 1.79
August 0.974844E+09 0.00 0.00 8210043.82 0.00 16054289.74 0.483439E+10 0.00 1.30
September 0.239783E+10 0.00 0.00 788935.94 0.00 0.348421E+09 0.603910E+09 0.00 0.53
October 0.872818E+09 0.00 0.00 1898.29 0.00 0.176539E+10 8887755.76 0.00 0.43
November 30003964.58 0.00 0.00 0.00 0.00 0.416546E+10 0.00 0.00 0.43
December 44264474.17 0.00 0.00 0.00 0.00 0.523723E+10 0.00 0.00 0.44
                   
Annual Sum or Average 0.974198E+10 12932904.24 0.00 47186124.27 3418735.10 0.219150E+11 0.253666E+11 0.00 0.84
Minimum of Months 30003964.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
Maximum of Months 0.239783E+10 12457001.02 0.00 13028630.13 2871134.74 0.523723E+10 0.676095E+10 0.00 1.88



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.151595E+09 0.00 0.00 0.00 0.00 0.655448E+10 0.00 0.00 0.43
February 0.754451E+09 0.00 0.00 85064.91 0.00 0.434798E+10 60675372.44 0.00 0.43
March 0.164568E+10 0.00 0.00 2617381.91 0.00 0.243374E+10 0.138206E+10 0.00 0.50
April 0.188472E+10 0.00 0.00 8752636.40 0.00 0.608564E+09 0.638618E+10 0.00 0.81
May 0.235601E+10 0.00 0.00 13777977.68 0.00 21602618.81 0.887776E+10 0.00 1.36
June 0.164959E+10 1189306.53 0.00 16186632.89 504315.24 0.00 0.768099E+10 0.00 1.71
July 0.179786E+10 31456371.19 0.00 16430421.94 3316988.09 0.00 0.535975E+10 0.00 1.61
August 0.191769E+10 0.00 0.00 15597590.63 0.00 23529368.74 0.761627E+10 0.00 1.54
September 0.288232E+10 0.00 0.00 4317950.65 0.00 0.451569E+09 0.334660E+10 0.00 0.70
October 0.168263E+10 0.00 0.00 813803.84 0.00 0.212350E+10 0.539038E+09 0.00 0.45
November 0.250447E+09 0.00 0.00 0.00 0.00 0.606235E+10 0.00 0.00 0.42
December 69356760.63 0.00 0.00 0.00 0.00 0.786522E+10 0.00 0.00 0.43
                   
Annual Sum or Average 0.170424E+11 32645677.73 0.00 78579460.84 3821303.33 0.304925E+11 0.412493E+11 0.00 0.87
Minimum of Months 69356760.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.42
Maximum of Months 0.288232E+10 31456371.19 0.00 16430421.94 3316988.09 0.786522E+10 0.887776E+10 0.00 1.71



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 38456235.18 0.00 0.00 0.00 0.00 0.445969E+10 0.00 0.00 0.44
February 0.122856E+09 0.00 0.00 0.00 0.00 0.330716E+10 0.00 0.00 0.44
March 0.997927E+09 0.00 0.00 0.00 0.00 0.228985E+10 0.00 0.00 0.47
April 0.202186E+10 0.00 0.00 2394796.09 0.00 0.468714E+09 0.185074E+10 0.00 0.64
May 0.197803E+10 0.00 0.00 5840196.33 0.00 13706588.01 0.362701E+10 0.00 1.06
June 0.820597E+09 2135971.56 0.00 11062706.71 48431.64 0.00 0.462234E+10 0.00 1.61
July 0.926352E+09 20632111.75 0.00 8767209.92 2180501.23 0.00 0.307853E+10 0.00 1.40
August 0.144701E+10 0.00 0.00 6487465.01 0.00 1258104.37 0.317029E+10 0.00 1.17
September 0.270100E+10 0.00 0.00 513360.37 0.00 0.345062E+09 0.497458E+09 0.00 0.57
October 0.102865E+10 0.00 0.00 0.00 0.00 0.173994E+10 0.00 0.00 0.45
November 41715085.98 0.00 0.00 0.00 0.00 0.408076E+10 0.00 0.00 0.43
December 50194635.84 0.00 0.00 0.00 0.00 0.503404E+10 0.00 0.00 0.43
                   
Annual Sum or Average 0.121747E+11 22768083.31 0.00 35065734.43 2228932.87 0.217402E+11 0.168464E+11 0.00 0.76
Minimum of Months 38456235.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43
Maximum of Months 0.270100E+10 20632111.75 0.00 11062706.71 2180501.23 0.503404E+10 0.462234E+10 0.00 1.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 98947152.59 0.00 0.00 1220570.50 0.00 0.00 0.108703E+10 0.00 0.28
February 0.00 0.00 0.00 6230629.78 0.00 0.00 0.973093E+09 0.00 0.29
March 0.00 0.00 0.00 14298195.11 0.00 0.00 0.102436E+10 0.00 0.31
April 0.00 0.00 0.00 17532999.92 0.00 0.00 0.636413E+09 0.00 0.29
May 0.00 0.00 0.00 3884388.35 0.00 0.00 0.454372E+09 0.00 0.30
June 0.00 1745302.99 0.00 8132850.02 0.00 0.00 0.248506E+09 0.00 0.30
July 0.00 2934777.76 0.00 10978905.37 0.00 0.00 0.120017E+09 0.00 0.28
August 0.00 32367.96 0.00 18099016.34 0.00 0.00 0.255000E+09 0.00 0.30
September 0.00 0.00 0.00 3473283.91 0.00 0.00 0.539900E+09 0.00 0.29
October 0.00 0.00 0.00 7566801.25 0.00 0.00 0.804627E+09 0.00 0.28
November 0.00 0.00 0.00 11112631.99 0.00 0.00 0.112695E+10 0.00 0.28
December 0.00 0.00 0.00 16365080.15 0.00 0.00 0.120899E+10 0.00 0.28
                   
Annual Sum or Average 98947152.59 4712448.71 0.00 0.118895E+09 0.00 0.00 0.847925E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 1220570.50 0.00 0.00 0.120017E+09 0.00 0.28
Maximum of Months 98947152.59 2934777.76 0.00 18099016.34 0.00 0.00 0.120899E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.104804E+11 0.00 0.00 282552.15 0.00 0.00 0.996971E+09 0.00 0.28
February 0.00 0.00 0.00 41921161.65 0.00 0.00 0.975011E+10 0.00 0.29
March 0.00 0.00 0.00 0.115942E+09 0.00 0.00 0.102708E+11 0.00 0.31
April 0.00 0.00 0.00 0.158695E+09 0.00 0.00 0.638128E+10 0.00 0.29
May 0.00 0.00 0.00 33842346.49 0.00 0.00 0.454903E+10 0.00 0.30
June 0.00 17087503.64 0.00 76350730.26 0.00 0.00 0.249249E+10 0.00 0.30
July 0.00 29016136.11 0.00 0.104252E+09 0.00 0.00 0.120934E+10 0.00 0.28
August 0.00 315902.56 0.00 0.171202E+09 0.00 0.00 0.256018E+10 0.00 0.30
September 0.00 0.00 0.00 25201027.97 0.00 0.00 0.541605E+10 0.00 0.29
October 0.00 0.00 0.00 55778098.89 0.00 0.00 0.806556E+10 0.00 0.28
November 0.00 0.00 0.00 85242650.61 0.00 0.00 0.112954E+11 0.00 0.28
December 0.00 0.00 0.00 0.134324E+09 0.00 0.00 0.121197E+11 0.00 0.28
                   
Annual Sum or Average 0.104804E+11 46419542.31 0.00 0.100303E+10 0.00 0.00 0.751069E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 282552.15 0.00 0.00 0.996971E+09 0.00 0.28
Maximum of Months 0.104804E+11 29016136.11 0.00 0.171202E+09 0.00 0.00 0.121197E+11 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.111071E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
February 9449337.24 0.00 0.00 3050173.48 0.00 0.00 0.966273E+09 0.00 0.29
March 0.00 0.00 0.00 9965638.35 0.00 0.00 0.102871E+10 0.00 0.31
April 0.00 0.00 0.00 14734215.33 0.00 0.00 0.639251E+09 0.00 0.29
May 0.00 0.00 0.00 2963315.58 0.00 0.00 0.455332E+09 0.00 0.30
June 0.00 1717173.15 0.00 7578279.63 0.00 0.00 0.249442E+09 0.00 0.30
July 0.00 2902401.83 0.00 10357177.69 0.00 0.00 0.121156E+09 0.00 0.28
August 0.00 31396.91 0.00 16834623.70 0.00 0.00 0.256517E+09 0.00 0.30
September 97440490.17 0.00 0.00 1345999.78 0.00 0.00 0.445317E+09 0.00 0.29
October 0.00 0.00 0.00 4085801.07 0.00 0.00 0.808080E+09 0.00 0.28
November 0.00 0.00 0.00 7306784.69 0.00 0.00 0.113076E+10 0.00 0.28
December 0.00 0.00 0.00 12202709.68 0.00 0.00 0.121319E+10 0.00 0.28
                   
Annual Sum or Average 0.121760E+10 4650971.89 0.00 90424718.97 0.00 0.00 0.731402E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.111071E+10 2902401.83 0.00 16834623.70 0.00 0.00 0.121319E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:06:40

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January -0.314112E+11 0.641669E+10 0.00 0.189679E+13 0.254320E+12
February 0.674982E+11 0.523492E+10 0.00 0.176296E+13 0.229701E+12
March 0.368663E+12 0.803406E+10 0.00 0.210487E+13 0.265253E+12
April 0.662170E+12 0.879522E+10 0.00 0.201847E+13 0.291443E+12
May 0.820910E+12 0.521028E+10 0.00 0.216825E+13 0.198826E+12
June 0.848629E+12 0.286314E+10 0.00 0.175228E+13 0.677871E+12
July 0.770404E+12 0.232112E+10 0.00 0.185541E+13 0.913804E+12
August 0.579626E+12 0.272104E+10 0.00 0.196629E+13 0.689786E+12
September 0.272714E+12 0.318809E+10 0.00 0.202125E+13 0.746777E+11
October 0.118253E+12 0.698609E+10 0.00 0.200642E+13 0.170503E+12
November -0.218457E+10 0.247803E+10 0.00 0.200384E+13 0.348023E+12
December -0.512323E+11 0.463923E+10 0.00 0.199347E+13 0.460701E+12
           
Annual Sum or Average 0.442404E+13 0.588879E+11 0.00 0.235503E+14 0.457491E+13
Minimum of Months -0.512323E+11 0.232112E+10 0.00 0.175228E+13 0.746777E+11
Maximum of Months 0.848629E+12 0.879522E+10 0.00 0.216825E+13 0.913804E+12