Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:07
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2023-10-16 09:07:54
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 33412.14 | 721.33 | 721.33 |
Net Site Energy | 33412.14 | 721.33 | 721.33 |
Total Source Energy | 89221.75 | 1926.19 | 1926.19 |
Net Source Energy | 89221.75 | 1926.19 | 1926.19 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 82.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2459.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7190.82 | 0.00 | 0.00 |
Interior Lighting | 2023.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 325.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3333.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 915.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 978.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 770.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10503.98 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 61.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 595.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 25543.31 | 678.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7190.82 | 0.00 | 12784.15 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 82.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2459.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7190.82 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2023.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 325.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ComputerHVAC | 1424.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 915.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 978.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 770.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10503.98 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 61.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 595.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 82.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2459.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7190.82 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2023.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 325.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 3333.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 915.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 978.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 770.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10503.98 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 61.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 595.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 110.62 | 14.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.24 | 0.00 | 0.28 |
Other | 390.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 551.45 | 14.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.24 | 0.00 | 0.28 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 110.62 | 14.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.24 | 0.00 | 0.28 |
Other | 390.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 551.45 | 14.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.24 | 0.00 | 0.28 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 25543.312 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 25543.312 | 100.00 |
Total On-Site and Utility Electric Sources | 25543.312 | 100.00 |
Total Electricity End Uses | 25543.312 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 2682.53 | 99.78 |
Air to Air Heat Recovery for Heating | 5.99 | 0.22 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2688.52 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 12784.15 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 12784.15 | 100.00 |
Total Water End Uses | 12784.15 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.67 |
Time Setpoint Not Met During Occupied Cooling | 175.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionDistrictHeatingCoolingMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:07 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.8895 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.8895 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 5.9168 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 5.9168 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.8895 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8895 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.8895 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8895 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.8895 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.9168 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.9168 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.8190 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
Time of Peak | 30-AUG-15:50 | 06-FEB-06:10 | - | - | - | - | - | - | - | - | 21-AUG-13:00 | 31-MAY-23:40 | 30-AUG-15:50 |
Heating | 0.00 | 423881.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 | 0.00 |
Cooling | 279391.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370154.94 | 0.00 | 0.00 |
Interior Lighting | 171235.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 154937.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 90954.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 67029.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 55581.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 5695.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1603116.60 | 429576.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370154.94 | 13.56 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 | 0.00 |
Boiler | 0.00 | 423881.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 279391.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370154.94 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 171235.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3372.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ComputerHVAC | 72130.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 90954.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 67029.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 55581.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 5695.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 89.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7788.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7591.11 | 0.00 |
Interior Lighting | 6407.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1029.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10555.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2900.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3098.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2439.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 195.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 645.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 80895.67 | 734.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7591.11 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 168.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.88 | 0.00 |
Interior Lighting | 138.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 22.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 62.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 66.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 52.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1746.44 | 15.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.88 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 168.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.88 | 0.00 |
Interior Lighting | 138.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 22.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 227.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 62.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 66.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 52.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1746.44 | 15.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.88 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.04 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.458462 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.36 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.445033 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.28 | 0.360514 | 0.352000 | 1.86 | 0.961371 | 0.500000 | 0.001057 | 0.000163 | 1.86 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 49.21 | 0.386535 | 0.367000 | 18.06 | 1.00 | 0.500000 | 0.000986 | 0.003081 | 18.06 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 4.89 | 0.389051 | 0.379000 | 1.85 | 1.00 | 0.500000 | 0.000979 | 0.000526 | 1.85 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.844600 | 0.282762 | 0.276000 | 0.233110 | 0.754031 | 0.500000 | 0.001347 | 0.000043 | 0.233110 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.883795 | 0.174141 | 0.200000 | 0.176759 | 0.464376 | 0.500000 | 0.002188 | 0.000033 | 0.176759 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.03 | 0.231743 | 0.226000 | 0.232907 | 0.617982 | 0.500000 | 0.001644 | 0.000057 | 0.232907 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.15 | 0.134353 | 0.200000 | 0.229106 | 0.358273 | 0.500000 | 0.002836 | 0.000025 | 0.229106 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 7.69 | 0.310727 | 0.295000 | 2.27 | 0.828607 | 0.500000 | 0.001226 | 0.001146 | 3.91 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 9.04 | 0.170291 | 0.200000 | 1.81 | 0.454108 | 0.500000 | 0.002237 | 0.000765 | 2.61 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 9.59 | 0.248947 | 0.236000 | 2.26 | 0.663858 | 0.500000 | 0.001530 | 0.001140 | 3.88 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 9.53 | 0.161444 | 0.200000 | 1.91 | 0.430518 | 0.500000 | 0.002360 | 0.000665 | 2.27 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.889037 | 0.268628 | 0.261000 | 0.232039 | 0.716342 | 0.500000 | 0.001418 | 0.000159 | 0.541966 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.922741 | 0.166791 | 0.200000 | 0.184548 | 0.444777 | 0.500000 | 0.002284 | 0.000105 | 0.357885 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.07 | 0.222166 | 0.216000 | 0.232198 | 0.592442 | 0.500000 | 0.001715 | 0.000158 | 0.539261 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.04 | 0.148542 | 0.200000 | 0.207220 | 0.396113 | 0.500000 | 0.002565 | 0.000097 | 0.330987 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18683.49 | 0.000163 | 376.64 |
CORE_MID VAV BOX REHEAT COIL | 352123.36 | 0.003081 | 7826.57 |
CORE_TOP VAV BOX REHEAT COIL | 60079.97 | 0.000526 | 1561.78 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 4910.08 | 0.000043 | 111.05 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3759.73 | 0.000033 | 85.23 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6519.25 | 0.000057 | 160.03 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2807.51 | 0.000025 | 57.84 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 131020.14 | 0.001146 | 3457.77 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 87474.62 | 0.000765 | 2308.44 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 130259.72 | 0.001140 | 3437.73 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 76054.83 | 0.000665 | 2007.49 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 18167.21 | 0.000159 | 479.27 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11995.90 | 0.000105 | 316.45 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 18076.76 | 0.000158 | 476.88 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11096.38 | 0.000097 | 292.75 |
VAV_BOT WITH REHEAT HEATING COIL | 25001.60 | 0.000219 | 432.11 |
VAV_MID WITH REHEAT HEATING COIL | 230102.43 | 0.002013 | 3976.96 |
VAV_TOP WITH REHEAT HEATING COIL | 24843.27 | 0.000217 | 429.38 |
CAV_BAS HEATING COIL | 237002.75 | 0.002073 | 5383.16 |
Design Size Maximum Heating Air Flow Rate [m3/s] | Design Size Maximum Cooling Air Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT | 0.338402 | 21.26 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 4.59 | 2.73 | 9.18 | 2.73 | 8.41 | 8.41 | 0.300000 | 0.324641 | 8.41 |
VAV_MID WITH REHEAT | 42.53 | 26.30 | 85.06 | 26.30 | 77.37 | 77.37 | 0.300000 | 0.340000 | 77.37 |
VAV_TOP WITH REHEAT | 4.41 | 2.71 | 8.81 | 3.53 | 8.35 | 8.35 | 0.300000 | 0.422183 | 8.35 |
CAV_BAS | 5.04 | 5.04 | 5.04 | 5.04 | 5.04 | 5.04 | 1.00 | 1.00 | 5.04 |
AIRLOOP DATACENTER BOT | 0.458462 | 0.458462 | 0.458462 | 0.458462 | 0.458462 | 0.458462 | 1.00 | 1.00 | 0.458462 |
AIRLOOP DATACENTER MID | 4.36 | 4.36 | 4.36 | 4.36 | 4.36 | 4.36 | 1.00 | 1.00 | 4.36 |
AIRLOOP DATACENTER TOP | 0.445033 | 0.445033 | 0.445033 | 0.445033 | 0.445033 | 0.445033 | 1.00 | 1.00 | 0.445033 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.41 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 77.37 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.35 | |
CAV_BAS_OA_CONTROLLER | 5.04 | |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.458462 | 0.015633 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.36 | 0.156328 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.445033 | 0.015633 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 27.14 | 6.67 | 11.05 | 0.011324 | 0.008500 | 238952.87 | 0.010166 | 8.41 |
VAV_MID WITH REHEAT COOLING COIL | 27.56 | 6.67 | 11.05 | 0.011699 | 0.008500 | 2328648.57 | 0.099066 | 77.37 |
VAV_TOP WITH REHEAT COOLING COIL | 27.02 | 6.67 | 11.05 | 0.011242 | 0.008500 | 234131.85 | 0.009961 | 8.35 |
CAV_BAS COOLING COIL | 25.09 | 6.67 | 11.42 | 0.010799 | 0.008500 | 120036.58 | 0.005107 | 5.04 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.41 |
VAV_MID WITH REHEAT FAN | 77.37 |
VAV_TOP WITH REHEAT FAN | 8.35 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.010166 | 0.000047 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000219 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.099066 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.002013 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.009961 | 0.000048 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000217 | |
CAV_BAS_COOLC_CONTROLLER | 0.005107 | 0.000093 |
CAV_BAS_HEATC_CONTROLLER | 0.002073 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.04 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.458462 | 9361.61 | 6717.53 | 0.000229 |
AIRLOOP DATACENTER MID COOLING COIL | 4.36 | 89307.37 | 63990.84 | 0.002187 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.445033 | 9105.26 | 6526.80 | 0.000223 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.458462 | 0.458462 | 0.458462 | 0.458462 | 9361.61 | 9361.61 | 669.07 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.36 | 4.36 | 4.36 | 4.36 | 89307.37 | 89307.37 | 6690.69 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.445033 | 0.445033 | 0.445033 | 0.445033 | 9105.26 | 9105.26 | 669.07 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.458462 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.36 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.445033 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT HEATING COIL | 0.458462 | 9361.61 | 0.000229 |
AIRLOOP DATACENTER MID HEATING COIL | 4.36 | 89307.37 | 0.002187 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.445033 | 9105.26 | 0.000223 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 669.07 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6690.69 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 669.07 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.124299 | 25359.79 | |
HEATSYS1 PUMP | 0.012685 | 3782.36 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.124299 | 14.92 |
HEATSYS1 | 0.012685 | 1.52 |
COOLSYS1_SUPPLY | 0.124299 | 14.92 |
SINGLE WATER PLANT LOOP | 0.002639 | 0.316726 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.124299 | 0.124299 | 521744.62 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1449979.01 | 1449979.01 | 0.012685 |
CENTRAL BOILER | 108720.00 | 108720.00 | 0.002639 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.124299 | 17557.44 |
PLANT CIRC PUMP | 0.002639 | 666.51 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.124299 | 0.062640 | 1476033.41 | 1482993.02 | 0.073388 |
COOLSYS1 CHILLER2 | 0.124299 | 0.062640 | 1476033.41 | 1482993.02 | 0.073388 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.002639 | 35644.39 | 21899.84 | 17822.20 | 1996.20 | 5888.66 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.146776 | 17.61 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.146776 | 43767.95 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 56.77 | 1759550.91 | 11.35 | 219943.86 |
TOWERWATERSYS COOLTOWER 2 | 56.77 | 1759550.91 | 11.35 | 219943.86 |
Design Water Flow Rate [m3/s] Equipment # 45 | |
WSHPPLANT OPERATION SCHEME | 0.076228 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.889 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.731 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.889 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.313 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16369.361 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16369.361 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4615.459 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4615.459 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.743 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.656 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 2.135 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4064 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4365 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3009 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.76055735E-15 | 0.55973061E-16 | -0.11090261E-09 | -0.43371185E-17 |
51 | 8 | 0.16390423E-07 | 0.22068143E-12 | 0.31740643E-03 | -0.18636477E-09 |
52 | 7 | -0.10429999E-01 | 0.12271718E-07 | -0.20474149E-01 | 0.11859286E-03 |
53 | 6 | 0.35611320 | 0.43955117E-05 | 0.42991281 | -0.41673803E-02 |
54 | 5 | -4.7098961 | 0.16827687E-03 | -4.1162358 | 0.57223947E-01 |
55 | 4 | 30.875684 | 0.14076848E-02 | 20.167480 | -0.39388153 |
56 | 3 | -106.69740 | 0.31291265E-02 | -53.106522 | 1.4497707 |
57 | 2 | 192.63914 | 0.17911574E-02 | 75.570394 | -2.8293896 |
58 | 1 | -169.50392 | 0.19431750E-03 | -54.592911 | 2.7164834 |
59 | 0 | 57.057407 | 0.11257899E-05 | 15.674734 | |
60 | 9 | 0.11474244E-14 | 0.54197419E-16 | -0.11508650E-09 | -0.49945851E-17 |
61 | 8 | 0.16984416E-07 | 0.21156325E-12 | 0.32425024E-03 | -0.19311866E-09 |
62 | 7 | -0.10636353E-01 | 0.11664670E-07 | -0.20772028E-01 | 0.12093918E-03 |
63 | 6 | 0.36172330 | 0.41637772E-05 | 0.43474562 | -0.42335086E-02 |
64 | 5 | -4.7646824 | 0.15893927E-03 | -4.1535939 | 0.57903236E-01 |
65 | 4 | 31.118254 | 0.13261305E-02 | 20.314042 | -0.39710182 |
66 | 3 | -107.21418 | 0.29411649E-02 | -53.396504 | 1.4572354 |
67 | 2 | 193.15212 | 0.16802168E-02 | 75.835339 | -2.8375342 |
68 | 1 | -169.69371 | 0.18194848E-03 | -54.668081 | 2.7198097 |
69 | 0 | 57.057407 | 0.10520719E-05 | 15.660794 | |
70 | 9 | 0.66246833E-15 | 0.57738042E-16 | -0.92036509E-10 | -0.27018983E-17 |
71 | 8 | 0.13701644E-07 | 0.25726543E-12 | 0.28527343E-03 | -0.15579243E-09 |
72 | 7 | -0.94571194E-02 | 0.14940887E-07 | -0.19068097E-01 | 0.10753086E-03 |
73 | 6 | 0.32965778 | 0.54453531E-05 | 0.40701455 | -0.38555430E-02 |
74 | 5 | -4.4514676 | 0.21157254E-03 | -3.9387765 | 0.54019785E-01 |
75 | 4 | 29.731016 | 0.17930056E-02 | 19.470280 | -0.37868589 |
76 | 3 | -104.25747 | 0.40308508E-02 | -51.726693 | 1.4145289 |
77 | 2 | 190.21562 | 0.23301583E-02 | 74.311741 | -2.7909129 |
78 | 1 | -168.60668 | 0.25508611E-03 | -54.239505 | 2.7007581 |
79 | 0 | 57.057407 | 0.14924561E-05 | 15.743350 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.4547_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.584 | 2.584 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.584 | 2.584 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.4547_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.584 | 2.584 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.584 | 2.584 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.60743E-002 | 0.16139 | 0.61671 | 0.61671 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12075 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.60743E-002 | 0.16139 | 0.61671 | 0.61671 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12075 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.60743E-002 | 0.16139 | 0.61671 | 0.61671 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12075 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.60743E-002 | 0.16139 | 0.61671 | 0.61671 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12075 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2.856E-002 | 9.114E-005 | 1.371E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.384E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2.856E-002 | 9.114E-005 | 1.371E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.384E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 4.231E-002 | 1.187E-005 | 1.424E-004 | 3.506E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 4.231E-002 | 1.187E-005 | 1.424E-004 | 3.506E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 4.231E-002 | 1.187E-005 | 1.096E-005 | 3.506E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6254E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6265E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7661E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7670E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1309E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1315E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2447E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2452E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6512E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7229E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7871E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8468E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1472E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1952E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2574E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2891E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2727E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0291E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.0494E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2035E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.9708E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2098E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6042E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.1095E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6579E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7555E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7943E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8820E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1538E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2204E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2577E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2900E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6253E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6267E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7661E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7672E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1309E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1317E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2447E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2451E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8368E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9662E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7256E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8595E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.5577E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6254E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1302E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1521E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4075E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.6441E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2729E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5117E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4408E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.3988E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6787E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.9865E-003 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8074E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8584E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6892E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7267E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.5378E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5542E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1303E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1525E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2173E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2185E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0474E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0484E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.3115E-004 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.3188E-004 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2447E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2452E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2446E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3113E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0699E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1233E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.4925E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.8862E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2577E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2900E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8942E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0694E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4825E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.1954E-003 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4675E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.8147E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6042E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.1067E-003 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2422E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3084E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0669E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1173E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.4412E-004 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.7295E-004 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2574E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2891E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2172E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2184E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0473E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0482E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.3105E-004 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.3158E-004 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2447E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2451E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3332E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3869E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1155E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1543E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.0937E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1081E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1303E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1525E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.4812E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2955E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1647E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.0967E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.5251E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.0492E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6787E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 9.9865E-003 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3553E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4510E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1434E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2365E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1120E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1695E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1302E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1521E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.3410E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.1344E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.9692E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.3683E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.3222E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.1272E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.0133E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.4574E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9035E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2699E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.7576E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1160E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9026E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9643E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.0820E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4729E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2861E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5883E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8361E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2694E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8134E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 9.9391E-003 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0133E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4571E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.8977E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8133E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.5522E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5701E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.9157E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5175E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.0820E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.4729E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.3413E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.1409E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.9711E-002 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.3759E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.3264E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.1337E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.0168E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.4602E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9027E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2722E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.7578E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1183E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9047E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9678E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.0854E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4757E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2836E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5890E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8344E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2700E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8144E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 9.9535E-003 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0168E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4599E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.8960E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8147E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.5513E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5714E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.9171E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5200E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.0854E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4757E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 69955.87436 | 69955.87436 | 5.03877 | 5.03877 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 2779.42662 | 149.60210 | 1.20019 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20019 | 00:10:00 | 4.60000 | 5.25715E-003 | 2779.42662 | 149.60210 | 1.20019 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 73252.66161 | 73252.66161 | 5.27592 | 5.27592 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 683437.97367 | 683437.97367 | 49.20754 | 49.20754 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 170440.12056 | 170440.12056 | 7.13096 | 10.77825 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 67903.33379 | 67903.33379 | 4.88893 | 4.88893 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 41438.92454 | 41438.92454 | 1.75640 | 1.75640 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 11614.98554 | 11614.98554 | 0.84460 | 0.84460 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 33.90000 | 1.65364E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 2566.48423 | 2566.48423 | 0.10808 | 0.13533 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 12154.06691 | 12154.06691 | 0.88380 | 0.88380 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 30.22650 | 1.65295E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 1982.54847 | 1982.54847 | 8.34813E-002 | 8.72129E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 14172.36861 | 14172.36861 | 1.03056 | 1.03056 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 33.76833 | 1.65361E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 4177.18845 | 4177.18845 | 0.17668 | 0.17668 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 15753.57315 | 15753.57315 | 1.14553 | 1.14553 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 505.54203 | 505.54203 | 2.15499E-002 | 8.72129E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 105694.40981 | 105694.40981 | 7.68585 | 7.68585 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90000 | 1.65364E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 91744.64662 | 91744.64662 | 3.90527 | 3.90527 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 124287.04513 | 124287.04513 | 9.03779 | 9.03779 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 30.67417 | 1.65303E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 61249.47875 | 61249.47875 | 2.60761 | 2.60761 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 131927.68353 | 131927.68353 | 9.59345 | 9.59345 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 91213.06785 | 91213.06785 | 3.88253 | 3.88253 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 131097.42303 | 131097.42303 | 9.53302 | 9.53302 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 32.66233 | 1.65340E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 53266.05295 | 53266.05295 | 2.26616 | 2.26616 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 12225.81809 | 12225.81809 | 0.88904 | 0.88904 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 33.74200 | 1.65361E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 12715.87243 | 12715.87243 | 0.54197 | 0.54197 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 12689.37376 | 12689.37376 | 0.92274 | 0.92274 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 30.89800 | 1.65307E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 8396.11741 | 8396.11741 | 0.35789 | 0.35789 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 14783.01866 | 14783.01866 | 1.07499 | 1.07499 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 33.90000 | 1.65364E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 12652.64398 | 12652.64398 | 0.53926 | 0.53926 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 14248.32292 | 14248.32292 | 1.03610 | 1.03610 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 7767.30619 | 7767.30619 | 0.33099 | 0.33099 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 7993.56845 | 7993.56845 | 0.45846 | 0.45846 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 31.21400 | 1.65313E-002 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56328E-002 | 00:10:00 | 4.60000 | 5.25715E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 76046.43022 | 76046.43022 | 4.36160 | 4.36160 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 31.21400 | 1.65313E-002 | 36.20274 | 1.94861 | 0.15633 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15633 | 00:10:00 | 4.60000 | 5.25715E-003 | 36.20274 | 1.94861 | 0.15633 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7759.38259 | 7759.38259 | 0.44503 | 0.44503 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 31.21400 | 1.65313E-002 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56328E-002 | 00:10:00 | 4.60000 | 5.25715E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370763.86227 | 370763.86227 | 21.26430 | 21.26430 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 26.71100 | 1.65229E-002 | 783.67941 | 42.18139 | 0.33840 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33840 | 00:10:00 | 4.60000 | 5.25715E-003 | 783.67941 | 42.18139 | 0.33840 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 138768.59 | 8.40624 | 8.40624 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 15507.95 | 1.56426 | 1.56426 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1258702.92 | 77.36691 | 77.36691 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 232380.05 | 23.43981 | 23.43981 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 142940.18 | 8.35301 | 8.35301 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 25147.62 | 3.52650 | 3.52650 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 |
7 | CAV_BAS | Cooling | Sensible | 74623.12 | 5.03877 | 5.03877 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 51367.02 | 1.20019 | 1.20019 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 7949.64 | 0.45846 | 0.45846 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BOT | Heating | Sensible | 669.07 | 1.56328E-002 | 1.56328E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER MID | Cooling | Sensible | 75667.29 | 4.36160 | 4.36160 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER MID | Heating | Sensible | 6690.69 | 0.15633 | 0.15633 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7721.92 | 0.44503 | 0.44503 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER TOP | Heating | Sensible | 669.07 | 1.56328E-002 | 1.56328E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.03877 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.27592 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36051 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35200 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.85712 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96137 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05682E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.63451E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.85712 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18683.49429 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.63451E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 376.64458 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 49.20754 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38653 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36700 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.05917 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.85680E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.08053E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.05917 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 352123.36454 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.08053E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7826.57115 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.88893 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38905 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.37900 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.85290 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.79306E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.25606E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.85290 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 60079.96777 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.25606E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1561.78031 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84460 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28276 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27600 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23311 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75403 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34742E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.29555E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23311 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4910.07813 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.29555E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 111.05419 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88380 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17414 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17676 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46438 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18788E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.28918E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17676 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3759.73242 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.28918E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 85.23488 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03056 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23174 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22600 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23291 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61798 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.64406E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.70333E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23291 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6519.25172 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.70333E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 160.02588 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.14553 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13435 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22911 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35827 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.83582E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.45613E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.22911 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2807.50591 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.45613E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 57.83770 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.68585 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31073 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29500 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.26733 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82861 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22615E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.14622E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.90527 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 131020.13908 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14622E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3457.77147 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.03779 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17029 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.80756 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45411 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.23735E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.65266E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.60761 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 87474.61699 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.65266E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2308.44085 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.59345 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24895 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23600 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.26405 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66386 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.53045E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.13957E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.88253 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 130259.72320 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.13957E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3437.73317 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.53302 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16144 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.90660 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43052 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35995E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.65361E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.26616 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 76054.83060 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.65361E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2007.48863 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88904 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26863 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26100 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23204 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71634 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.41832E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.58935E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54197 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18167.21160 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.58935E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 479.26582 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92274 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16679 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18455 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44478 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.28429E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.04945E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35789 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11995.90295 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.04945E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 316.45269 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07499 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22217 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21600 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23220 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59244 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.71494E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.58143E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.53926 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18076.75683 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.58143E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 476.88244 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03610 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14854 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20722 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39611 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56492E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.70759E-005 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33099 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11096.37537 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.70759E-005 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 292.74827 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45846 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.36160 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.44503 |
215 | ZoneHVAC:IdealLoadsAirSystem | AIRLOOP DATACENTER BASEMENT | Design Size Maximum Heating Air Flow Rate [m3/s] | 0.33840 |
216 | ZoneHVAC:IdealLoadsAirSystem | AIRLOOP DATACENTER BASEMENT | Design Size Maximum Cooling Air Flow Rate [m3/s] | 21.26430 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.59021 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.72901 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.18041 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.72901 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.40624 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.40624 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32464 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 42.52883 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 26.30471 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 85.05766 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 26.30471 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 77.36691 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 77.36691 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34000 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.40590 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.70891 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.81180 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.52650 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.35301 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.35301 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.42218 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.03877 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.03877 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.03877 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.03877 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.03877 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.03877 |
247 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45846 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45846 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45846 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45846 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45846 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.45846 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
257 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.36160 |
258 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.36160 |
259 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.36160 |
260 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.36160 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.36160 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.36160 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
265 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.44503 |
266 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.44503 |
267 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.44503 |
268 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.44503 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.44503 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.44503 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
273 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.40624 |
274 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 77.36691 |
275 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.35301 |
276 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.03877 |
277 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.45846 |
278 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.36160 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.44503 |
280 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.40624 |
281 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
282 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.13813 |
283 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
284 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04928 |
285 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.13239E-002 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 238952.86578 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.01656E-002 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.40624 |
290 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 25001.59582 |
291 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.18725E-004 |
292 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 432.11353 |
293 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.40624 |
294 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.01656E-002 |
295 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.68433E-005 |
296 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.18725E-004 |
297 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 77.36691 |
298 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
299 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.56213 |
300 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
301 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.05047 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.16988E-002 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2328648.57305 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.90661E-002 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 77.36691 |
307 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 230102.43263 |
308 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.01304E-003 |
309 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3976.96115 |
310 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 77.36691 |
311 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.90661E-002 |
312 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.80680E-006 |
313 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.01304E-003 |
314 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.35301 |
315 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
316 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.02168 |
317 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04902 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.12416E-002 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 234131.84997 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.96051E-003 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.35301 |
324 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 24843.27469 |
325 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.17340E-004 |
326 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 429.37720 |
327 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.35301 |
328 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.96051E-003 |
329 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.78078E-005 |
330 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.17340E-004 |
331 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.03877 |
332 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.08707 |
333 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
334 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.42493 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.07986E-002 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
337 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 120036.57806 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.10663E-003 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.03877 |
340 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 237002.75266 |
341 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.07340E-003 |
342 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5383.15759 |
343 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.03877 |
344 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.10663E-003 |
345 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.32494E-005 |
346 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.07340E-003 |
347 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45846 |
348 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56328E-002 |
349 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45846 |
350 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9361.60868 |
351 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6717.53076 |
352 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29265E-004 |
353 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45846 |
354 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45846 |
355 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45846 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45846 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9361.60868 |
358 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9361.60868 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 669.06860 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
361 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45846 |
362 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45846 |
363 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9361.60868 |
364 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29265E-004 |
365 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 669.06860 |
366 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.36160 |
367 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15633 |
368 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.36160 |
369 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 89307.36748 |
370 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 63990.84233 |
371 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.18713E-003 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.36160 |
373 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.36160 |
374 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.36160 |
375 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.36160 |
376 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 89307.36748 |
377 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 89307.36748 |
378 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6690.68596 |
379 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
380 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.36160 |
381 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.36160 |
382 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 89307.36748 |
383 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.18713E-003 |
384 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6690.68596 |
385 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.44503 |
386 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56328E-002 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44503 |
388 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9105.25894 |
389 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6526.80272 |
390 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.22987E-004 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.44503 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.44503 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.44503 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.44503 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9105.25894 |
396 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9105.25894 |
397 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 669.06860 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
399 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.44503 |
400 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44503 |
401 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9105.25894 |
402 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.22987E-004 |
403 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 669.06860 |
404 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.12430 |
405 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 25359.78701 |
406 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.12430 |
407 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 14.91586 |
408 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.12430 |
409 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.12430 |
410 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 521744.61908 |
411 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
412 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.26850E-002 |
413 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.52221 |
414 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.26850E-002 |
415 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3782.35610 |
416 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
417 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1449979.00722 |
418 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1449979.01000 |
419 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.26850E-002 |
420 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.12430 |
421 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 14.91586 |
422 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 0.12430 |
423 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 17557.43599 |
424 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12430 |
425 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.26400E-002 |
426 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1476033.40523 |
427 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1482993.02000 |
428 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.33878E-002 |
429 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12430 |
430 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.26400E-002 |
431 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1476033.40523 |
432 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1482993.02000 |
433 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.33878E-002 |
434 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 2.63938E-003 |
435 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 0.31673 |
436 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 2.63938E-003 |
437 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 666.50983 |
438 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 2.63938E-003 |
439 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 35644.39112 |
440 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 21899.83861 |
441 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 17822.19556 |
442 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 1996.19659 |
443 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 5888.66036 |
444 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 108719.99657 |
445 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 108720.00000 |
446 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 2.63938E-003 |
447 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
448 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
449 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
450 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
451 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
452 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.14678 |
453 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 17.61308 |
454 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.14678 |
455 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 43767.95378 |
456 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 56.77130 |
457 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1759550.91278 |
458 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.35426 |
459 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 219943.86410 |
460 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 56.77130 |
461 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1759550.91278 |
462 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.35426 |
463 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 219943.86410 |
464 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 7.62275E-002 |
465 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 7.62275E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17715.59 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 333704.62 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 56891.75 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 4652.89 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3562.77 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6174.79 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2661.79 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 124148.55 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 82886.08 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 123428.21 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 72068.10 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 17213.14 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11365.87 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 17127.46 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10513.75 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 21199.84 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 195112.94 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 21065.59 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 192368.80 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 233673.59 | 157072.86 | 76600.73 | 0.67 | 24382.62 | 247.30 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2195648.10 | 1467005.60 | 728642.50 | 0.67 | 230314.52 | 2335.98 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 231002.78 | 155513.89 | 75488.89 | 0.67 | 24078.61 | 244.22 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 129811.88 | 89228.60 | 40583.28 | 0.69 | 13252.31 | 134.41 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_EAST_0.25 | N/A | 2.584 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_EAST_0.25 | N/A | 2.584 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_EAST_0.25 | N/A | 2.584 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_WEST_0.25 | N/A | 2.584 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_WEST_0.25 | N/A | 2.584 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_WEST_0.25 | N/A | 2.584 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_EAST_0.25 | N/A | 2.584 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_WEST_0.25 | N/A | 2.584 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_EAST_0.25 | N/A | 2.584 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_WEST_0.25 | N/A | 2.584 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2349949155 | 0.2331475396 | Pass | Pass | 0.7497316074 | 0.7586655436 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2368879420 | 0.2520423166 | Pass | Pass | 0.2477897796 | 0.4314528979 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1605356826 | 0.2154150483 | Pass | Pass | 0.2110778569 | 0.4063540308 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1434765342 | 0.2075324207 | Pass | Pass | 0.1961457471 | 0.3958162788 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2080261043 | 0.2266061402 | Pass | Pass | 0.2445994975 | 0.4283722885 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2726168379 | 0.2983185111 | Pass | Pass | 0.2534977471 | 0.4382735364 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3712136743 | 0.4934866528 | Pass | Pass | 0.2634019722 | 0.4406694698 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3524818135 | 0.4232864959 | Pass | Pass | 0.2475428344 | 0.4278959872 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1453112950 | 0.2008856104 | Pass | Pass | 0.2105676437 | 0.4055544364 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2130115300 | 0.2644736090 | Pass | Pass | 0.2117641095 | 0.4071876103 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3137358178 | 0.5131802396 | Pass | Pass | 0.2538783277 | 0.4701281117 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2071192766 | 0.2959107082 | Pass | Pass | 0.2108997832 | 0.4049537493 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1324773747 | 0.1837529775 | Pass | Pass | 0.1958433376 | 0.3948662297 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2001267582 | 0.2405883754 | Pass | Pass | 0.1968264473 | 0.3968667102 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3180218579 | 0.4984168255 | Pass | Pass | 0.2236569429 | 0.4300629485 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1946615784 | 0.2976940411 | Pass | Pass | 0.1964550793 | 0.3940959209 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.4115142113E-002 | 5.0033309304E-002 | Pass | Pass | 0.2596326369 | 0.4184114472 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.2554920493E-002 | 4.1148990982E-002 | Pass | Pass | 0.2609910914 | 0.6852964326 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.5047225047E-002 | 7.5810558740E-002 | Pass | Pass | 0.2120795165 | 0.4190840981 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.7870604279E-006 | 8.4739059997E-006 | Pass | Pass | 3.2381170306E-003 | 3.7839650097E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.8435044289E-006 | 7.2730644227E-006 | Pass | Pass | 5.0552086807E-003 | 5.7294804339E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.8440891050E-006 | 7.4831735446E-006 | Pass | Pass | 7.0572725827E-003 | 6.1159352028E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.0724163126E-015 | 2.6972301664E-015 | Pass | Pass | 4.8004441168E-005 | 1.1006655033E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5952.35 | -19.5 | 0.00 | 1994.56 | 19209.73 | 27137.19 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.4547_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.4547_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.4547_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.4547_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.4547_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.4547_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.584 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.4547_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.584 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.584 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.4547_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.584 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.584 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.4547_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.584 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.584 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.4547_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.584 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.584 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 1043.06 | 2.584 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.584 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.8895 | 2779.43 | 16369.36 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 135.58 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8895 | 2496.12 | 14700.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 121.76 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8895 | 24961.20 | 147008.37 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 1217.57 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8895 | 2496.12 | 14700.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 121.76 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8895 | 313.41 | 1845.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.77 | 0.0000 | Y | 8.93 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.54 | 0.0000 | Y | 5.70 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8895 | 313.42 | 1845.88 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.21 | 0.0000 | Y | 8.74 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.60 | 0.0000 | Y | 5.72 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8895 | 3134.13 | 18458.37 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.78 | 0.0000 | Y | 89.31 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8895 | 2019.75 | 11895.27 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.53 | 0.0000 | Y | 57.00 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8895 | 3134.20 | 18458.77 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.22 | 0.0000 | Y | 87.39 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8895 | 2019.75 | 11895.27 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.59 | 0.0000 | Y | 57.14 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8895 | 313.41 | 1845.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.77 | 0.0000 | Y | 8.93 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.53 | 0.0000 | Y | 5.70 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8895 | 313.42 | 1845.88 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.22 | 0.0000 | Y | 8.74 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.59 | 0.0000 | Y | 5.71 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.8895 | 783.68 | 4615.46 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 38.23 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 8.8011 | 36.20 | 318.62 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.26 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 8.8011 | 362.03 | 3186.24 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 32.64 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 8.8011 | 36.20 | 318.62 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.26 |
Interior Lighting Total | 5.9168 | 46320.38 | 274067.57 | 636.12 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.05 | AstronomicalClock | - | 41.73 | 41.73 | 78.11 | |
EXTERIOR_LIGHTS_B | 991.40 | AstronomicalClock | - | 83.73 | 62.73 | 11.67 | |
EXTERIOR_LIGHTS_C | 26646.63 | AstronomicalClock | - | 83.73 | 47.05 | 235.35 | |
Exterior Lighting Total | 37611.08 | 325.14 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2915050.66 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1449979.01 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1482993.02 | 6.28 | 1419425.64 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1482993.02 | 6.28 | 1419425.64 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 148548.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 108720.00 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1759550.91 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1759550.91 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 238952.87 | 233673.59 | 157072.86 | 76600.73 | 0.67 | - | 24382.62 | 247.30 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2328648.57 | 2195648.10 | 1467005.60 | 728642.50 | 0.67 | - | 230314.52 | 2335.98 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 234131.85 | 231002.78 | 155513.89 | 75488.89 | 0.67 | - | 24078.61 | 244.22 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 120036.58 | 129811.88 | 89228.60 | 40583.28 | 0.69 | - | 13252.31 | 134.41 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9361.61 | 6717.53 | 2644.08 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 89307.37 | 63990.84 | 25316.53 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9105.26 | 6526.80 | 2578.46 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18683.49 | 17715.59 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 352123.36 | 333704.62 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 60079.97 | 56891.75 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 4910.08 | 4652.89 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 3759.73 | 3562.77 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6519.25 | 6174.79 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 2807.51 | 2661.79 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 131020.14 | 124148.55 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 87474.62 | 82886.08 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 130259.72 | 123428.21 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 76054.83 | 72068.10 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 18167.21 | 17213.14 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11995.90 | 11365.87 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 18076.76 | 17127.46 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11096.38 | 10513.75 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 25001.60 | 21199.84 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 230102.43 | 195112.94 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 24843.27 | 21065.59 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 237002.75 | 192368.80 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9361.61 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 89307.37 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9105.26 | 0.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 669.07 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6690.69 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 669.07 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.41 | 18165.44 | 2160.95 | 1.00 | 1.12 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 77.37 | 167185.78 | 2160.95 | 1.00 | 1.08 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.35 | 18050.41 | 2160.95 | 1.00 | 1.12 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.04 | 8544.02 | 1695.65 | 1.00 | 1.16 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 513.53 | 1120.11 | 1.00 | 1.65 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.36 | 4885.47 | 1120.11 | 1.00 | 1.16 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 498.48 | 1120.11 | 1.00 | 1.66 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.124299 | 25359.79 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.012685 | 3782.36 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.124299 | 17557.44 | 141251.81 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.002639 | 666.51 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.146776 | 43767.95 | 298196.27 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 69955.87 | 69955.87 | 25.17 | 5.039 | 5.039 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00900 | 28.05 | 0.01653 | 1.200 | 0.00 |
CORE_BOTTOM | 73252.66 | 73252.66 | 29.35 | 5.276 | 5.276 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 28.05 | 0.01653 | 1.078 | 0.00 |
CORE_MID | 683437.97 | 683437.97 | 273.80 | 49.208 | 49.208 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 28.05 | 0.01653 | 10.778 | 0.00 |
CORE_TOP | 67903.33 | 67903.33 | 27.20 | 4.889 | 4.889 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 28.05 | 0.01653 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11614.99 | 11614.99 | 37.06 | 0.845 | 0.845 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00887 | 33.90 | 0.01654 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 12154.07 | 12154.07 | 60.18 | 0.884 | 0.884 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 24.00 | 24.00 | 0.00873 | 30.23 | 0.01653 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 14172.37 | 14172.37 | 45.22 | 1.031 | 1.031 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00880 | 33.77 | 0.01654 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 15753.57 | 15753.57 | 78.00 | 1.146 | 1.146 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00868 | 32.79 | 0.01653 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 105694.41 | 105694.41 | 337.24 | 7.686 | 7.686 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00896 | 33.90 | 0.01654 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 124287.05 | 124287.05 | 615.36 | 9.038 | 9.038 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 24.00 | 24.00 | 0.00876 | 30.67 | 0.01653 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 131927.68 | 131927.68 | 420.93 | 9.593 | 9.593 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00887 | 33.83 | 0.01654 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 131097.42 | 131097.42 | 649.08 | 9.533 | 9.533 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00874 | 32.66 | 0.01653 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12225.82 | 12225.82 | 39.01 | 0.889 | 0.889 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00892 | 33.74 | 0.01654 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 12689.37 | 12689.37 | 62.83 | 0.923 | 0.923 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 24.00 | 24.00 | 0.00876 | 30.90 | 0.01653 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 14783.02 | 14783.02 | 47.17 | 1.075 | 1.075 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00885 | 33.90 | 0.01654 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 14248.32 | 14248.32 | 70.54 | 1.036 | 1.036 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00873 | 32.79 | 0.01653 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 7993.57 | 7993.57 | 220.80 | 0.458 | 0.458 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 31.21 | 0.01653 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 76046.43 | 76046.43 | 2100.57 | 4.362 | 4.362 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00860 | 31.21 | 0.01653 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7759.38 | 7759.38 | 214.33 | 0.445 | 0.445 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 31.21 | 0.01653 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370763.86 | 370763.86 | 473.11 | 21.264 | 21.264 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 26.71 | 0.01652 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 25.40 | 0.00526 | 4.60 | 0.00526 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 23.03 | 0.00526 | 4.60 | 0.00526 | 1.078 | 0.00 | |
CORE_MID | 170440.12 | 170440.12 | 68.28 | 7.131 | 10.778 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 10.778 | 0.00 |
CORE_TOP | 41438.92 | 41438.92 | 16.60 | 1.756 | 1.756 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 2566.48 | 2566.48 | 8.19 | 0.108 | 0.135 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 1982.55 | 1982.55 | 9.82 | 0.083 | 0.087 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00769 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 4177.19 | 4177.19 | 13.33 | 0.177 | 0.177 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 505.54 | 505.54 | 2.50 | 0.022 | 0.087 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00731 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 91744.65 | 91744.65 | 292.73 | 3.905 | 3.905 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | 4.60 | 0.00526 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 61249.48 | 61249.48 | 303.25 | 2.608 | 2.608 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | 4.60 | 0.00526 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 91213.07 | 91213.07 | 291.03 | 3.883 | 3.883 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | 4.60 | 0.00526 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 53266.05 | 53266.05 | 263.73 | 2.266 | 2.266 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00780 | 4.60 | 0.00526 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12715.87 | 12715.87 | 40.57 | 0.542 | 0.542 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 8396.12 | 8396.12 | 41.57 | 0.358 | 0.358 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 12652.64 | 12652.64 | 40.37 | 0.539 | 0.539 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 7767.31 | 7767.31 | 38.46 | 0.331 | 0.331 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 4.60 | 0.00526 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 4.60 | 0.00526 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 25.09 | 0.00834 | 4.60 | 0.00526 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.14 | 0.00568 | 4.60 | 0.00526 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 4.60 | 0.00526 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 8.41 | 8.41 | 1.56 | 1.56 | 8.4062 | 2.7290 | 8.4062 | 0.3246 | 0.3000 |
VAV_MID WITH REHEAT | 77.37 | 77.37 | 23.44 | 23.44 | 77.3669 | 26.3047 | 77.3669 | 0.3400 | 0.3000 |
VAV_TOP WITH REHEAT | 8.35 | 8.35 | 3.53 | 3.53 | 8.3530 | 3.5265 | 8.3530 | 0.4222 | 0.3000 |
CAV_BAS | 5.04 | 5.04 | 1.20 | 1.20 | 5.0388 | 5.0388 | 5.0388 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.46 | 0.46 | 0.02 | 0.02 | 0.4585 | 0.4585 | 0.4585 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.36 | 4.36 | 0.16 | 0.16 | 4.3616 | 4.3616 | 4.3616 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.45 | 0.45 | 0.02 | 0.02 | 0.4450 | 0.4450 | 0.4450 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18683.494 | 18683.494 | 1.857124 | 0.00016345 | 376.645 | 1/21 00:10:00 | 1/21 00:10:00 | 18683.49 | 18683.49 | 1.857124 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 18752.38 | 18752.38 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 352123.365 | 352123.365 | 18.059169 | 0.00308053 | 7826.571 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 352123.36 | 352123.36 | 18.059169 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 170440.12 | 0.00 | 353333.69 | 353333.69 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 60079.968 | 60079.968 | 1.852905 | 0.00052561 | 1561.780 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 60079.97 | 60079.97 | 1.852905 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 41438.92 | 0.00 | 60263.87 | 60263.87 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 4910.078 | 4910.078 | 0.233110 | 0.00004296 | 111.054 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4910.08 | 4910.08 | 0.233110 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00764670 | 49.4210 | 2566.48 | 0.00 | 4926.83 | 4926.83 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 3759.732 | 3759.732 | 0.176759 | 0.00003289 | 85.235 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3759.73 | 3759.73 | 0.176759 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00768566 | 49.6698 | 1982.55 | 0.00 | 3772.54 | 3772.54 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 6519.252 | 6519.252 | 0.232907 | 0.00005703 | 160.026 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6519.25 | 6519.25 | 0.232907 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00776822 | 50.1967 | 4177.19 | 0.00 | 6539.79 | 6539.79 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 2807.506 | 2807.506 | 0.229106 | 0.00002456 | 57.838 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2807.51 | 2807.51 | 0.229106 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00730975 | 47.2682 | 505.54 | 0.00 | 2817.74 | 2817.74 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 131020.139 | 131020.139 | 3.905268 | 0.00114622 | 3457.771 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 131020.14 | 131020.14 | 3.905268 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00784597 | 50.6933 | 91744.65 | 0.00 | 131467.45 | 131467.45 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 87474.617 | 87474.617 | 2.607605 | 0.00076527 | 2308.441 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 87474.62 | 87474.62 | 2.607605 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00785209 | 50.7324 | 61249.48 | 0.00 | 87772.44 | 87772.44 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 130259.723 | 130259.723 | 3.882529 | 0.00113957 | 3437.733 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 130259.72 | 130259.72 | 3.882529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00784410 | 50.6814 | 91213.07 | 0.00 | 130704.65 | 130704.65 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 76054.831 | 76054.831 | 2.266163 | 0.00066536 | 2007.489 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 76054.83 | 76054.83 | 2.266163 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00780006 | 50.4007 | 53266.05 | 0.00 | 76316.74 | 76316.74 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 18167.212 | 18167.212 | 0.541966 | 0.00015893 | 479.266 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18167.21 | 18167.21 | 0.541966 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00791336 | 51.1229 | 12715.87 | 0.00 | 18227.89 | 18227.89 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 11995.903 | 11995.903 | 0.357885 | 0.00010495 | 316.453 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11995.90 | 11995.90 | 0.357885 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00791539 | 51.1358 | 8396.12 | 0.00 | 12035.90 | 12035.90 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 18076.757 | 18076.757 | 0.539261 | 0.00015814 | 476.882 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18076.76 | 18076.76 | 0.539261 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00791231 | 51.1162 | 12652.64 | 0.00 | 18137.15 | 18137.15 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 11096.375 | 11096.375 | 0.330987 | 0.00009708 | 292.748 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11096.38 | 11096.38 | 0.330987 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00789404 | 50.9998 | 7767.31 | 0.00 | 11133.56 | 11133.56 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 238952.866 | -999.000 | 8.406240 | 0.01016561 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 238952.87 | 164353.90 | 8.406240 | 27.14 | 19.70 | 0.01132385 | 11.05 | 11.05 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 30.1941 | 24.00 | 0.00890377 | 47.8630 | 110086.83 | 0.00 | 239230.99 | 160737.22 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 25001.596 | 25001.596 | 2.521872 | 0.00021872 | 432.114 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25001.60 | 25001.60 | 2.521872 | 4.60 | 4.60 | 0.00525715 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 100.6471 | 22.15 | 0.00627136 | 37.8561 | 9231.76 | 0.00 | 25664.22 | 25664.22 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2328648.573 | -999.000 | 77.366915 | 0.09906609 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 2328648.57 | 1551746.77 | 77.366915 | 27.56 | 20.11 | 0.01169876 | 11.05 | 11.05 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 32.8072 | 24.00 | 0.00897878 | 48.2608 | 969855.67 | 0.00 | 2331523.64 | 1523593.49 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 230102.433 | 230102.433 | 23.210074 | 0.00201304 | 3976.961 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 230102.43 | 230102.43 | 23.210074 | 4.60 | 4.60 | 0.00525715 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 109.3575 | 21.00 | 0.00789665 | 51.0162 | 467913.37 | 0.00 | 236200.91 | 236200.91 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 234131.850 | -999.000 | 8.353008 | 0.00996051 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 234131.85 | 162146.56 | 8.353008 | 27.02 | 19.60 | 0.01124156 | 11.05 | 11.05 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 30.3865 | 24.00 | 0.00891445 | 47.9199 | 114323.60 | 0.00 | 234400.96 | 158429.83 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 24843.275 | 24843.275 | 2.505902 | 0.00021734 | 429.377 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24843.27 | 24843.27 | 2.505902 | 4.60 | 4.60 | 0.00525715 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 101.2885 | 21.00 | 0.00796081 | 51.4248 | 59204.57 | 0.00 | 25501.70 | 25501.70 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 120036.578 | -999.000 | 5.038772 | 0.00510663 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 120036.58 | 84239.10 | 5.038772 | 25.09 | 18.64 | 0.01079856 | 11.42 | 11.42 | 0.00850000 | 28.55 | 0.01652632 | 23.72 | 23.8191 | 24.00 | 0.00900047 | 48.3755 | 69080.78 | 0.00 | 120184.22 | 82186.13 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 237002.753 | 237002.753 | 5.038772 | 0.00207340 | 5383.158 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 237002.75 | 237002.75 | 5.038772 | 1.10 | 1.10 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 23.8191 | 25.40 | 0.00525715 | 26.1354 | 0.00 | 0.00 | 203516.08 | 203516.08 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9361.609 | 6717.531 | 0.458462 | 0.00022927 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 8774.89 | 8319.21 | -999.0 | 28.09 | 18.09 | 0.00886136 | 12.80 | 12.09 | 0.00850000 | 31.21 | 0.01653132 | 24.43 | -999.0000 | 27.00 | 0.00859060 | 38.6629 | 7993.57 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 89307.367 | 63990.842 | 4.361603 | 0.00218713 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 83749.15 | 79193.70 | -999.0 | 28.10 | 18.10 | 0.00887966 | 12.80 | 12.09 | 0.00850000 | 31.21 | 0.01653132 | 24.43 | -999.0000 | 27.00 | 0.00859521 | 38.6837 | 76046.43 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9105.259 | 6526.803 | 0.445033 | 0.00022299 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 8537.48 | 8081.91 | -999.0 | 28.10 | 18.10 | 0.00887213 | 12.80 | 12.09 | 0.00850000 | 31.41 | 0.01653169 | 24.48 | -999.0000 | 27.00 | 0.00859324 | 38.6748 | 7758.48 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9361.609 | 9361.609 | 0.458462 | 0.00022927 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9361.61 | 9361.61 | 0.458462 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.4098 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 89307.367 | 89307.367 | 4.361603 | 0.00218713 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 89307.37 | 89307.37 | 4.361603 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.5842 | 25.09 | 0.00834293 | 42.0626 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9105.259 | 9105.259 | 0.445033 | 0.00022299 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9105.26 | 9105.26 | 0.445033 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.5127 | 24.14 | 0.00568123 | 30.4321 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 669.069 | 669.069 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.07 | 669.07 | 0.458462 | 0.16 | 0.16 | 0.00838942 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.4098 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6690.686 | 6690.686 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6690.69 | 6690.69 | 4.361603 | 0.16 | 0.16 | 0.00823233 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.5842 | 25.09 | 0.00834293 | 42.0626 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 669.069 | 669.069 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.07 | 669.07 | 0.445033 | 0.16 | 0.16 | 0.00566633 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.5127 | 24.14 | 0.00568123 | 30.4321 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18683.494 | 18683.494 | 1.857124 | 0.00016345 | 376.645 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 1.2631 | 1.288536 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 18683.49 | 18683.49 | 1.0000 | 2.23443071 | 1.857124 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.16343468 | 60.00 | 32.22 | 27.78 | 0.000 | 18683.49 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 18752.38 | 18752.38 | 2.23443071 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 352123.365 | 352123.365 | 18.059169 | 0.00308053 | 7826.571 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 23.8056 | 24.284722 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 352123.36 | 352123.36 | 1.0000 | 21.72819430 | 18.059169 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 3.08021456 | 60.00 | 32.22 | 27.78 | 0.000 | 352123.36 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 170440.12 | 0.00 | 353333.69 | 353333.69 | 21.72819430 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.75 | 17.62 | 0.00800000 | 49321.4 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 60079.968 | 60079.968 | 1.852905 | 0.00052561 | 1561.780 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 4.0618 | 4.143506 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 60079.97 | 60079.97 | 1.0000 | 2.22935382 | 1.852905 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.52555215 | 60.00 | 32.22 | 27.78 | 0.000 | 60079.97 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 41438.92 | 0.00 | 60263.87 | 60263.87 | 2.22935382 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.31 | 20.98 | 0.00800000 | 60091.8 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4910.078 | 4910.078 | 0.233110 | 0.00004296 | 111.054 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 0.3320 | 0.338631 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4910.08 | 4910.08 | 1.0000 | 0.28046978 | 0.233110 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.04295112 | 60.00 | 32.22 | 27.78 | 0.000 | 4910.08 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.85 | 0.00764670 | 21.00 | 0.00764670 | 49.4210 | 2566.48 | 0.00 | 4926.83 | 4926.83 | 0.28046978 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.03 | 18.05 | 0.00800000 | 50626.2 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3759.732 | 3759.732 | 0.176759 | 0.00003289 | 85.235 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 0.2542 | 0.259296 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3759.73 | 3759.73 | 1.0000 | 0.21267067 | 0.176759 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.03288842 | 60.00 | 32.22 | 27.78 | 0.000 | 3759.73 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.82 | 0.00768566 | 21.00 | 0.00768566 | 49.6698 | 1982.55 | 0.00 | 3772.54 | 3772.54 | 0.21267067 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.20 | 18.10 | 0.00800000 | 50798.7 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6519.252 | 6519.252 | 0.232907 | 0.00005703 | 160.026 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 0.4407 | 0.449610 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6519.25 | 6519.25 | 1.0000 | 0.28022585 | 0.232907 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.05702744 | 60.00 | 32.22 | 27.78 | 0.000 | 6519.25 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.87 | 0.00776822 | 21.00 | 0.00776822 | 50.1967 | 4177.19 | 0.00 | 6539.79 | 6539.79 | 0.28022585 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.69 | 19.87 | 0.00800000 | 56397.4 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2807.506 | 2807.506 | 0.229106 | 0.00002456 | 57.838 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 0.1898 | 0.193624 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2807.51 | 2807.51 | 1.0000 | 0.27565314 | 0.229106 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.02455878 | 60.00 | 32.22 | 27.78 | 0.000 | 2807.51 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.96 | 0.00730975 | 21.00 | 0.00730975 | 47.2682 | 505.54 | 0.00 | 2817.74 | 2817.74 | 0.27565314 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 22.82 | 15.53 | 0.00800000 | 43281.9 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 131020.139 | 131020.139 | 3.905268 | 0.00114622 | 3457.771 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 8.8577 | 9.036002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 131020.14 | 131020.14 | 1.0000 | 4.69868952 | 3.905268 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 1.14610441 | 60.00 | 32.22 | 27.78 | 0.000 | 131020.14 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00784597 | 21.00 | 0.00784597 | 50.6933 | 91744.65 | 0.00 | 131467.45 | 131467.45 | 4.69868952 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61039.4 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 87474.617 | 87474.617 | 2.607605 | 0.00076527 | 2308.441 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 5.9138 | 6.032820 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 87474.62 | 87474.62 | 1.0000 | 3.13738427 | 2.607605 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.76518804 | 60.00 | 32.22 | 27.78 | 0.000 | 87474.62 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00785209 | 21.00 | 0.00785209 | 50.7324 | 61249.48 | 0.00 | 87772.44 | 87772.44 | 3.13738427 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61036.1 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 130259.723 | 130259.723 | 3.882529 | 0.00113957 | 3437.733 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 8.8063 | 8.983559 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 130259.72 | 130259.72 | 1.0000 | 4.67133042 | 3.882529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 1.13945264 | 60.00 | 32.22 | 27.78 | 0.000 | 130259.72 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00784410 | 21.00 | 0.00784410 | 50.6814 | 91213.07 | 0.00 | 130704.65 | 130704.65 | 4.67133042 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61040.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 76054.831 | 76054.831 | 2.266163 | 0.00066536 | 2007.489 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 5.1418 | 5.245237 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 76054.83 | 76054.83 | 1.0000 | 2.72657250 | 2.266163 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.66529296 | 60.00 | 32.22 | 27.78 | 0.000 | 76054.83 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00780006 | 21.00 | 0.00780006 | 50.4007 | 53266.05 | 0.00 | 76316.74 | 76316.74 | 2.72657250 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.26 | 0.00800000 | 61049.8 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18167.212 | 18167.212 | 0.541966 | 0.00015893 | 479.266 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 1.2282 | 1.252929 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18167.21 | 18167.21 | 1.0000 | 0.65207600 | 0.541966 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.15891848 | 60.00 | 32.22 | 27.78 | 0.000 | 18167.21 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00791336 | 21.00 | 0.00791336 | 51.1229 | 12715.87 | 0.00 | 18227.89 | 18227.89 | 0.65207600 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61013.4 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11995.903 | 11995.903 | 0.357885 | 0.00010495 | 316.453 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 0.8110 | 0.827316 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11995.90 | 11995.90 | 1.0000 | 0.43059583 | 0.357885 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.10493469 | 60.00 | 32.22 | 27.78 | 0.000 | 11995.90 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00791539 | 21.00 | 0.00791539 | 51.1358 | 8396.12 | 0.00 | 12035.90 | 12035.90 | 0.43059583 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61011.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18076.757 | 18076.757 | 0.539261 | 0.00015814 | 476.882 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 1.2221 | 1.246691 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18076.76 | 18076.76 | 1.0000 | 0.64882071 | 0.539261 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.15812722 | 60.00 | 32.22 | 27.78 | 0.000 | 18076.76 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00791231 | 21.00 | 0.00791231 | 51.1162 | 12652.64 | 0.00 | 18137.15 | 18137.15 | 0.64882071 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61013.9 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11096.375 | 11096.375 | 0.330987 | 0.00009708 | 292.748 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 0.7502 | 0.765278 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11096.38 | 11096.38 | 1.0000 | 0.39823226 | 0.330987 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.09706603 | 60.00 | 32.22 | 27.78 | 0.000 | 11096.38 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00789404 | 21.00 | 0.00789404 | 50.9998 | 7767.31 | 0.00 | 11133.56 | 11133.56 | 0.39823226 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61017.3 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 238952.866 | -999.000 | 8.406240 | 0.01016561 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.8905 | 1004.8586 | 1.2032 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.406240 | 10.11411003 | 4197.9300 | 999.8980 | 124.28616463 | 12.27 | 6.67 | 5.60 | 2921769.87 | 8.1784 | 8.178360 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 238952.87 | 164353.90 | 1.0000 | 10.11411003 | 8.406240 | 27.14 | 19.70 | 0.01132385 | 56161.0 | 11.05 | 11.05 | 0.00850000 | 32535.3 | 10.16457030 | 6.67 | 12.27 | 5.60 | 18165.438 | 220787.43 | 33.90 | 0.01653638 | 25.13 | 2.53819000 | 30.1941 | 24.00 | 0.00890377 | 24.00 | 0.00890377 | 47.8630 | 110086.83 | 0.00 | 239230.99 | 160737.22 | 10.11411003 | 27.14 | 19.71 | 0.01132385 | 56161.0 | 11.65 | 11.36 | 0.00824733 | 32507.8 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 25001.596 | 25001.596 | 2.521872 | 0.00021872 | 432.114 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.406240 | 10.11411003 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 1.6903 | 1.724273 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25001.60 | 25001.60 | 1.0000 | 3.03423301 | 2.521872 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.21870255 | 60.00 | 32.22 | 27.78 | 0.000 | 25001.60 | 4.60 | 0.00525715 | 4.60 | 2.53819000 | 100.6471 | 6.49 | 0.00599734 | 22.15 | 0.00627136 | 37.8561 | 9231.76 | 0.00 | 25664.22 | 25664.22 | 3.03423301 | 2.80 | 2.80 | 0.00525715 | 15988.7 | 11.14 | 7.87 | 0.00525715 | 24447.0 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2328648.573 | -999.000 | 77.366915 | 0.09906609 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5874 | 1004.8586 | 1.2032 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 77.366915 | 93.08531092 | 4197.9300 | 999.8980 | 124.28616463 | 12.27 | 6.67 | 5.60 | 2921769.87 | 79.6999 | 79.699931 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 2328648.57 | 1551746.77 | 1.0000 | 93.08531092 | 77.366915 | 27.56 | 20.11 | 0.01169876 | 57552.8 | 11.05 | 11.05 | 0.00850000 | 32536.6 | 99.05598767 | 6.67 | 12.27 | 5.60 | 167185.783 | 2161462.79 | 33.90 | 0.01653638 | 25.13 | 25.38195000 | 32.8072 | 24.00 | 0.00897878 | 24.00 | 0.00897878 | 48.2608 | 969855.67 | 0.00 | 2331523.64 | 1523593.49 | 93.08531092 | 27.56 | 20.13 | 0.01169876 | 57552.8 | 11.62 | 11.36 | 0.00825800 | 32505.7 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 230102.433 | 230102.433 | 23.210074 | 0.00201304 | 3976.961 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 77.366915 | 93.08531092 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 15.5563 | 15.869363 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 230102.43 | 230102.43 | 1.0000 | 27.92559328 | 23.210074 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 2.01283111 | 60.00 | 32.22 | 27.78 | 0.000 | 230102.43 | 4.60 | 0.00525715 | 4.60 | 25.38195000 | 109.3575 | 20.76 | 0.00791273 | 21.00 | 0.00789665 | 51.0162 | 467913.37 | 0.00 | 236200.91 | 236200.91 | 27.92559328 | 2.80 | 2.80 | 0.00525715 | 15988.7 | 11.14 | 7.87 | 0.00525715 | 24447.0 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 234131.850 | -999.000 | 8.353008 | 0.00996051 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.7375 | 1004.8586 | 1.2032 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.353008 | 10.05006302 | 4197.9300 | 999.8980 | 124.28616463 | 12.27 | 6.67 | 5.60 | 2921769.87 | 8.0134 | 8.013357 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | Sensible | 234131.85 | 162146.56 | 1.0000 | 10.05006302 | 8.353008 | 27.02 | 19.60 | 0.01124156 | 55831.6 | 11.05 | 11.05 | 0.00850000 | 32535.1 | 9.95949407 | 6.67 | 12.27 | 5.60 | 18050.406 | 216081.44 | 33.90 | 0.01653638 | 25.13 | 2.53819000 | 30.3865 | 24.00 | 0.00891445 | 24.00 | 0.00891445 | 47.9199 | 114323.60 | 0.00 | 234400.96 | 158429.83 | 10.05006302 | 27.02 | 19.61 | 0.01124156 | 55831.6 | 11.65 | 11.36 | 0.00824495 | 32508.3 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 24843.275 | 24843.275 | 2.505902 | 0.00021734 | 429.377 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.353008 | 10.05006302 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 1.6796 | 1.713354 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24843.27 | 24843.27 | 1.0000 | 3.01501891 | 2.505902 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.21731763 | 60.00 | 32.22 | 27.78 | 0.000 | 24843.27 | 4.60 | 0.00525715 | 4.60 | 2.53819000 | 101.2885 | 21.00 | 0.00796081 | 21.00 | 0.00796081 | 51.4248 | 59204.57 | 0.00 | 25501.70 | 25501.70 | 3.01501891 | 2.80 | 2.80 | 0.00525715 | 15988.7 | 11.14 | 7.87 | 0.00525715 | 24447.0 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 120036.578 | -999.000 | 5.038772 | 0.00510663 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9140 | 1004.8586 | 1.2032 | CAV_BAS FAN | Fan:ConstantVolume | 5.038772 | 6.06248397 | 4197.9300 | 999.8980 | 124.28616463 | 12.27 | 6.67 | 5.60 | 2921769.87 | 4.1084 | 4.108352 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 120036.58 | 84239.10 | 1.0000 | 6.06248397 | 5.038772 | 25.09 | 18.64 | 0.01079856 | 52718.6 | 11.42 | 11.42 | 0.00850000 | 32918.7 | 5.10611259 | 6.67 | 12.27 | 5.60 | 8544.016 | 111492.56 | 28.55 | 0.01652632 | 23.72 | 1.20019084 | 23.8191 | 24.00 | 0.00900047 | 24.00 | 0.00900047 | 48.3755 | 69080.78 | 0.00 | 120184.22 | 82186.13 | 6.06248397 | 25.09 | 18.65 | 0.01079856 | 52718.6 | 11.86 | 11.52 | 0.00831431 | 32894.4 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 237002.753 | 237002.753 | 5.038772 | 0.00207340 | 5383.158 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | CAV_BAS FAN | Fan:ConstantVolume | 5.038772 | 6.06248397 | 4197.9300 | 999.8980 | 12.68375489 | 54.44 | 82.22 | 27.78 | 1479160.41 | 16.0228 | 16.345254 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 237002.75 | 237002.75 | 1.0000 | 6.06248397 | 5.038772 | 1.10 | 1.10 | 0.00525715 | 14259.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 2.07319196 | 60.00 | 32.22 | 27.78 | 0.000 | 237002.75 | 4.60 | 0.00525715 | 4.60 | 1.20019084 | 23.8191 | 0.00 | 0.00525715 | 25.40 | 0.00525715 | 26.1354 | 0.00 | 0.00 | 203516.08 | 203516.08 | 6.06248397 | 12.80 | 8.65 | 0.00525715 | 26134.9 | 45.89 | 20.94 | 0.00525715 | 59704.6 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9361.609 | 6717.531 | 0.458462 | 0.00022927 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3128 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 8774.89 | 8319.21 | 0.9373 | -999.0 | -999.0 | 28.09 | 18.09 | 0.00886136 | 50849.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8774.89 | 31.21 | 0.01653132 | 24.43 | 0.01563279 | -999.0000 | 27.00 | 0.00859060 | 27.00 | 0.00859060 | 38.6629 | 7993.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 89307.367 | 63990.842 | 4.361603 | 0.00218713 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3468 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 83749.15 | 79193.70 | 0.9378 | -999.0 | -999.0 | 28.10 | 18.10 | 0.00887966 | 50903.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 83749.15 | 31.21 | 0.01653132 | 24.43 | 0.15632792 | -999.0000 | 27.00 | 0.00859521 | 27.00 | 0.00859521 | 38.6837 | 76046.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9105.259 | 6526.803 | 0.445033 | 0.00022299 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3328 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 8537.48 | 8081.91 | 0.9376 | -999.0 | -999.0 | 28.10 | 18.10 | 0.00887213 | 50888.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8537.48 | 31.41 | 0.01653169 | 24.48 | 0.01563279 | -999.0000 | 27.00 | 0.00859324 | 27.00 | 0.00859324 | 38.6748 | 7758.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9361.609 | 9361.609 | 0.458462 | 0.00022927 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9361.61 | 9361.61 | 1.0000 | 0.55160676 | 0.458462 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9361.61 | 4.60 | 0.00525715 | 4.60 | 0.01563279 | 3.4098 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 89307.367 | 89307.367 | 4.361603 | 0.00218713 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 89307.37 | 89307.37 | 1.0000 | 5.24773579 | 4.361603 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89307.37 | 4.60 | 0.00525715 | 4.60 | 0.15632792 | 3.5842 | 0.00 | 0.00834293 | 25.09 | 0.00834293 | 42.0626 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9105.259 | 9105.259 | 0.445033 | 0.00022299 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9105.26 | 9105.26 | 1.0000 | 0.53544868 | 0.445033 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9105.26 | 4.60 | 0.00525715 | 4.60 | 0.01563279 | 3.5127 | 0.00 | 0.00568123 | 24.14 | 0.00568123 | 30.4321 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 669.069 | 669.069 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.458462 | 0.55160676 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 669.07 | 669.07 | 1.0000 | 0.55160676 | 0.458462 | 0.16 | 0.16 | 0.00838942 | 21141.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 669.07 | 4.60 | 0.00525715 | 4.60 | 0.01563279 | 3.4098 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6690.686 | 6690.686 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.361603 | 5.24773579 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6690.69 | 6690.69 | 1.0000 | 5.24773579 | 4.361603 | 0.16 | 0.16 | 0.00823233 | 20756.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6690.69 | 4.60 | 0.00525715 | 4.60 | 0.15632792 | 3.5842 | 0.00 | 0.00834293 | 25.09 | 0.00834293 | 42.0626 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 669.069 | 669.069 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.445033 | 0.53544868 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 669.07 | 669.07 | 1.0000 | 0.53544868 | 0.445033 | 0.16 | 0.16 | 0.00566633 | 14335.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 669.07 | 4.60 | 0.00525715 | 4.60 | 0.01563279 | 3.5127 | 0.00 | 0.00568123 | 24.14 | 0.00568123 | 30.4321 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 8.41 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 77.37 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 8.35 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 5.04 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | BASEMENT_DCV | 0.002360 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 4947.50 | 1951.33 | 1865.33 |
CORE_BOTTOM | 4268.67 | 320.50 | 0.00 |
CORE_MID | 2346.67 | 1893.33 | 0.00 |
CORE_TOP | 2579.00 | 2187.50 | 58.50 |
PERIMETER_BOT_ZN_3 | 3946.00 | 1306.67 | 2.83 |
PERIMETER_BOT_ZN_2 | 3867.83 | 1315.83 | 88.17 |
PERIMETER_BOT_ZN_1 | 4589.17 | 815.00 | 139.33 |
PERIMETER_BOT_ZN_4 | 5041.17 | 687.33 | 274.50 |
PERIMETER_MID_ZN_3 | 3277.00 | 2280.83 | 168.67 |
PERIMETER_MID_ZN_2 | 2921.33 | 1789.67 | 224.17 |
PERIMETER_MID_ZN_1 | 4198.50 | 1177.83 | 175.17 |
PERIMETER_MID_ZN_4 | 3848.50 | 1709.83 | 175.50 |
PERIMETER_TOP_ZN_3 | 3569.67 | 2450.33 | 526.17 |
PERIMETER_TOP_ZN_2 | 3714.67 | 2255.00 | 515.50 |
PERIMETER_TOP_ZN_1 | 4117.00 | 1512.00 | 327.33 |
PERIMETER_TOP_ZN_4 | 3796.50 | 2021.00 | 388.33 |
DATACENTER_BOT_ZN_6 | 5943.00 | 848.83 | 848.83 |
DATACENTER_MID_ZN_6 | 5943.00 | 16.67 | 16.67 |
DATACENTER_TOP_ZN_6 | 5865.83 | 124.83 | 110.67 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 76.83 | 0.00 | 2.33 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.33 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 17.83 | 0.00 | 17.83 |
PERIMETER_BOT_ZN_1 | 0.00 | 39.83 | 0.00 | 38.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 154.50 | 0.00 | 57.50 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 23.50 | 0.00 | 23.50 |
PERIMETER_MID_ZN_1 | 0.00 | 39.67 | 0.00 | 39.17 |
PERIMETER_MID_ZN_4 | 0.00 | 29.17 | 0.00 | 18.33 |
PERIMETER_TOP_ZN_3 | 4.67 | 2.17 | 0.67 | 2.00 |
PERIMETER_TOP_ZN_2 | 2.50 | 46.67 | 0.00 | 44.17 |
PERIMETER_TOP_ZN_1 | 1.17 | 39.83 | 0.00 | 37.00 |
PERIMETER_TOP_ZN_4 | 1.17 | 40.00 | 0.00 | 24.67 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.83 | 0.00 | 0.83 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 4.67 | 354.00 | 0.67 | 175.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 0.874 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.572 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.511 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.500 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.617 | 0.008 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.760 | 0.009 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 0.832 | 0.008 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 1.156 | 0.009 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.585 | 0.020 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.722 | 0.022 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 0.810 | 0.020 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.838 | 0.020 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.581 | 0.024 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.775 | 0.025 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 0.765 | 0.025 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.837 | 0.025 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.01 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 0.847 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.011 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.110 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.011 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 783.68 | 0.239 | ||
Total Facility | 1027.73 | 2493.19 | 126016.35 | 46320.38 | 1.3878 | 157.549 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 36453805.27 | 0.00 | 36453805.27 | 0.00 | 36453805.27 | 29876159.83 | 4075.23 | 2841.91 | 1842.86 | 240.62 |
CORE_BOTTOM | 23921062.16 | 0.00 | 23921062.16 | 0.00 | 23921062.16 | 33990283.35 | 6743.03 | 233.65 | 1783.32 | 163.03 |
CORE_MID | 0.20E+09 | 0.00 | 0.20E+09 | 0.00 | 0.20E+09 | 0.34E+09 | 6635.61 | 585.27 | 1539.12 | 11.78 |
CORE_TOP | 20123285.08 | 0.00 | 20123285.08 | 0.00 | 20123285.08 | 33990283.35 | 6720.23 | 652.55 | 1387.21 | 35.92 |
PERIMETER_BOT_ZN_3 | 3223040.42 | 0.00 | 3223040.42 | 82232.77 | 3305273.20 | 4267819.30 | 4586.26 | 271.77 | 3901.98 | 163.03 |
PERIMETER_BOT_ZN_2 | 2555042.92 | 0.00 | 2555042.92 | 54821.81 | 2609864.73 | 2750345.05 | 4157.82 | 26.98 | 4575.20 | 163.03 |
PERIMETER_BOT_ZN_1 | 4301615.29 | 0.00 | 4301615.29 | 82232.77 | 4383848.06 | 4267912.63 | 4250.74 | 199.74 | 4309.52 | 163.03 |
PERIMETER_BOT_ZN_4 | 3867561.70 | 0.00 | 3867561.70 | 54821.81 | 3922383.51 | 2750345.05 | 4037.24 | 0.00 | 4722.76 | 163.03 |
PERIMETER_MID_ZN_3 | 29471419.01 | 0.00 | 29471419.01 | 192855.40 | 29664274.42 | 42678193.03 | 4776.34 | 586.84 | 3396.82 | 11.78 |
PERIMETER_MID_ZN_2 | 25359183.05 | 0.00 | 25359183.05 | 128570.18 | 25487753.23 | 27503450.52 | 4260.22 | 6.85 | 4492.93 | 920.78 |
PERIMETER_MID_ZN_1 | 40671393.72 | 0.00 | 40671393.72 | 192855.40 | 40864249.12 | 42679126.28 | 4330.57 | 505.40 | 3924.03 | 11.78 |
PERIMETER_MID_ZN_4 | 27148966.66 | 0.00 | 27148966.66 | 128570.18 | 27277536.84 | 27503450.52 | 4239.82 | 0.46 | 4519.72 | 11.78 |
PERIMETER_TOP_ZN_3 | 2938843.66 | 0.00 | 2938843.66 | 239446.20 | 3178289.86 | 4267819.30 | 4842.86 | 607.91 | 3309.24 | 35.92 |
PERIMETER_TOP_ZN_2 | 2522628.03 | 0.00 | 2522628.03 | 159630.69 | 2682258.72 | 2750345.05 | 4264.61 | 2.80 | 4492.59 | 35.92 |
PERIMETER_TOP_ZN_1 | 3852779.31 | 0.00 | 3852779.31 | 239446.20 | 4092225.51 | 4267912.63 | 4394.96 | 567.43 | 3797.61 | 35.92 |
PERIMETER_TOP_ZN_4 | 2722711.15 | 0.00 | 2722711.15 | 159630.69 | 2882341.84 | 2750345.05 | 4255.77 | 0.59 | 4503.64 | 35.92 |
DATACENTER_BOT_ZN_6 | 244303.03 | 0.00 | 244303.03 | 0.00 | 244303.03 | 389144.62 | 4419.00 | 504.00 | 3837.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2443030.26 | 0.00 | 2443030.26 | 0.00 | 2443030.26 | 3891446.16 | 4419.00 | 504.00 | 3837.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244303.03 | 0.00 | 244303.03 | 0.00 | 244303.03 | 389144.62 | 4419.00 | 504.00 | 3837.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8423799.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 0.34E+10 | 0.00 | 0.34E+10 | 7500774.64 | 0.34E+10 | 0.50E+10 | 8760.00 | 3265.93 | 4894.04 | 1235.26 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.6109 | 0.0000 | 1.6109 | 0.0000 | 1.6109 | 0.9949 | 1448.44 | 2841.00 | 1653.56 |
CORE_BOTTOM | 1.0678 | 0.0000 | 1.0678 | 0.0000 | 1.0678 | 1.0778 | 4086.27 | 233.62 | 1623.10 |
CORE_MID | 9.5331 | 0.0000 | 9.5331 | 0.0000 | 9.5331 | 10.7782 | 3828.22 | 585.27 | 1529.51 |
CORE_TOP | 0.9341 | 0.0000 | 0.9341 | 0.0000 | 0.9341 | 1.0778 | 3917.44 | 651.60 | 1373.96 |
PERIMETER_BOT_ZN_3 | 0.1446 | 0.0000 | 0.1446 | 0.0020 | 0.1466 | 0.1353 | 1929.31 | 271.69 | 3742.01 |
PERIMETER_BOT_ZN_2 | 0.1148 | 0.0000 | 0.1148 | 0.0013 | 0.1161 | 0.0872 | 1503.85 | 26.57 | 4412.58 |
PERIMETER_BOT_ZN_1 | 0.1950 | 0.0000 | 0.1950 | 0.0020 | 0.1970 | 0.1353 | 1593.79 | 199.66 | 4149.55 |
PERIMETER_BOT_ZN_4 | 0.1744 | 0.0000 | 0.1744 | 0.0013 | 0.1757 | 0.0872 | 1383.27 | 0.00 | 4559.73 |
PERIMETER_MID_ZN_3 | 1.3734 | 0.0000 | 1.3734 | 0.0046 | 1.3780 | 1.3533 | 1969.13 | 586.84 | 3387.03 |
PERIMETER_MID_ZN_2 | 1.0919 | 0.0000 | 1.0919 | 0.0033 | 1.0951 | 0.8721 | 1443.23 | 5.17 | 3585.60 |
PERIMETER_MID_ZN_1 | 1.8968 | 0.0000 | 1.8968 | 0.0046 | 1.9014 | 1.3533 | 1523.18 | 505.40 | 3914.42 |
PERIMETER_MID_ZN_4 | 1.2653 | 0.0000 | 1.2653 | 0.0031 | 1.2684 | 0.8721 | 1434.60 | 0.42 | 4507.99 |
PERIMETER_TOP_ZN_3 | 0.1365 | 0.0000 | 0.1365 | 0.0057 | 0.1422 | 0.1353 | 2044.12 | 606.71 | 3292.17 |
PERIMETER_TOP_ZN_2 | 0.1172 | 0.0000 | 0.1172 | 0.0038 | 0.1211 | 0.0872 | 1473.60 | 2.42 | 4466.98 |
PERIMETER_TOP_ZN_1 | 0.1792 | 0.0000 | 0.1792 | 0.0057 | 0.1850 | 0.1353 | 1593.09 | 566.19 | 3783.72 |
PERIMETER_TOP_ZN_4 | 0.1265 | 0.0000 | 0.1265 | 0.0038 | 0.1303 | 0.0872 | 1465.05 | 0.20 | 4477.75 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0130 | 1602.00 | 504.00 | 3837.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1296 | 1602.00 | 504.00 | 3837.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0130 | 1602.00 | 504.00 | 3837.00 |
DATACENTER_BASEMENT_ZN_6 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.2805 | 5943.00 | 0.00 | 0.00 |
Total Facility | 157.5700 | 0.0000 | 157.5700 | 0.1816 | 157.7516 | 157.9346 | 5943.00 | 3262.13 | 4606.68 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 54817639.58 | 0.00 | 54817639.58 | 48026705.38 | 4037.24 | 0.00 | 4722.76 | 163.03 |
VAV_MID WITH REHEAT | 0.47E+09 | 0.00 | 0.47E+09 | 0.48E+09 | 4239.49 | 0.00 | 4520.51 | 11.78 |
VAV_TOP WITH REHEAT | 46557202.62 | 0.00 | 46557202.62 | 48026705.38 | 4246.17 | 2.15 | 4511.68 | 35.92 |
CAV_BAS | 52770914.23 | 0.00 | 52770914.23 | 29876159.83 | 4058.01 | 0.26 | 4701.73 | 240.62 |
AIRLOOP DATACENTER BOT | 353655.65 | 0.00 | 353655.65 | 389144.62 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3536556.46 | 0.00 | 3536556.46 | 3891446.16 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 353655.65 | 0.00 | 353655.65 | 389144.62 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.4559 | 0.0000 | 2.4559 | 1.5229 | 1383.27 | 0.00 | 4559.73 |
VAV_MID WITH REHEAT | 22.0768 | 0.0000 | 22.0768 | 15.2292 | 1434.26 | 0.00 | 4508.74 |
VAV_TOP WITH REHEAT | 2.1621 | 0.0000 | 2.1621 | 1.5229 | 1459.24 | 1.71 | 4482.05 |
CAV_BAS | 2.3320 | 0.0000 | 2.3320 | 0.9949 | 1446.67 | 0.00 | 4496.33 |
AIRLOOP DATACENTER BOT | 0.0165 | 0.0000 | 0.0165 | 0.0130 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1653 | 0.0000 | 0.1653 | 0.1296 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0165 | 0.0000 | 0.0165 | 0.0130 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 1707.51 | 0.00 | 0.00 | 0.00 | 3015.25 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 1478.85 | 0.00 | 0.00 | 0.00 | 3041.67 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 1416.52 | 0.00 | 0.00 | 0.00 | 3108.75 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 0.00 | 1899.10 | 0.00 | 0.00 | 0.00 | 2840.67 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 4.7536 | 0.0000 | 0.0000 | 0.0000 | 2.4067 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 39.3196 | 0.0000 | 0.0000 | 0.0000 | 24.1764 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 3.9112 | 0.0000 | 0.0000 | 0.0000 | 2.3977 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 0.0000 | 5.7703 | 0.0000 | 0.0000 | 0.0000 | 1.5112 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2264 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 7 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1361 |
Defaulted Fields | 1168 |
Fields with Defaults | 3868 |
Autosized Fields | 316 |
Autosizable Fields | 394 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 25543.31 | 287925.10 | 22-JAN-05:00 | 1603116.60 | 30-AUG-15:50 |
Electricity:Building | 16699.48 | 216770.18 | 28-MAY-17:10 | 971964.54 | 12-DEC-08:10 |
Electricity:Zone:BASEMENT | 559.97 | 14115.26 | 01-JAN-00:10 | 25295.37 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16699.48 | 216770.18 | 28-MAY-17:10 | 971964.54 | 12-DEC-08:10 |
InteriorLights:Electricity | 2023.08 | 9514.02 | 01-JAN-10:00 | 193957.09 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 135.58 | 657.72 | 01-JAN-00:10 | 11837.83 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2023.08 | 9514.02 | 01-JAN-10:00 | 193957.09 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 2023.08 | 9514.02 | 01-JAN-10:00 | 193957.09 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 135.58 | 657.72 | 01-JAN-00:10 | 11837.83 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2023.08 | 9514.02 | 01-JAN-10:00 | 193957.09 | 25-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 411.37 | 5043.91 | 01-JAN-00:10 | 27837.83 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4113.71 | 50438.97 | 01-JAN-00:10 | 278377.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1217.58 | 5906.80 | 01-JAN-00:10 | 106312.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1217.58 | 5906.80 | 01-JAN-00:10 | 106312.04 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 411.37 | 5043.90 | 01-JAN-00:10 | 27837.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 45.30 | 594.46 | 26-MAR-17:10 | 3374.64 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.93 | 35.29 | 01-JAN-10:00 | 1214.09 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.93 | 35.29 | 01-JAN-10:00 | 1214.09 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 29.14 | 383.09 | 28-MAY-17:10 | 2160.02 | 12-DEC-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.70 | 22.74 | 01-JAN-08:00 | 767.68 | 12-DEC-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.70 | 22.74 | 01-JAN-08:00 | 767.68 | 12-DEC-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 45.10 | 594.47 | 12-MAR-17:10 | 3367.21 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.74 | 35.29 | 01-JAN-08:00 | 1206.62 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.74 | 35.29 | 01-JAN-08:00 | 1206.62 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 29.15 | 383.09 | 12-MAR-17:10 | 2180.87 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.72 | 22.74 | 01-JAN-09:50 | 788.54 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.72 | 22.74 | 01-JAN-09:50 | 788.54 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 452.96 | 5944.59 | 26-MAR-17:10 | 33772.17 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 89.31 | 352.88 | 01-JAN-09:50 | 12166.65 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 89.31 | 352.88 | 01-JAN-09:50 | 12166.65 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 291.35 | 3830.92 | 28-MAY-17:10 | 21604.35 | 12-DEC-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 57.00 | 227.41 | 01-JAN-08:00 | 7680.93 | 12-DEC-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 57.00 | 227.41 | 01-JAN-08:00 | 7680.93 | 12-DEC-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 451.05 | 5944.68 | 12-MAR-17:10 | 33700.43 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 87.39 | 352.89 | 01-JAN-08:00 | 12094.58 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 87.39 | 352.89 | 01-JAN-08:00 | 12094.58 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 291.50 | 3830.90 | 12-MAR-17:10 | 21810.15 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 57.14 | 227.41 | 01-JAN-09:50 | 7886.82 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 57.14 | 227.41 | 01-JAN-09:50 | 7886.82 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 45.30 | 594.46 | 26-MAR-17:10 | 3377.09 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.93 | 35.29 | 01-JAN-09:50 | 1216.54 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.93 | 35.29 | 01-JAN-09:50 | 1216.54 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 29.14 | 383.09 | 28-MAY-17:10 | 2160.34 | 12-DEC-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.70 | 22.74 | 01-JAN-08:00 | 768.00 | 12-DEC-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.70 | 22.74 | 01-JAN-08:00 | 768.00 | 12-DEC-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 45.10 | 594.47 | 12-MAR-17:10 | 3369.92 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.74 | 35.29 | 01-JAN-08:00 | 1209.33 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.74 | 35.29 | 01-JAN-08:00 | 1209.33 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 29.15 | 383.09 | 12-MAR-17:10 | 2180.94 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.71 | 22.74 | 01-JAN-09:50 | 788.60 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.71 | 22.74 | 01-JAN-09:50 | 788.60 | 25-OCT-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7533.08 | 95093.58 | 01-JAN-00:10 | 382970.28 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 38.23 | 185.45 | 01-JAN-00:10 | 3337.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 38.23 | 185.45 | 01-JAN-00:10 | 3337.76 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.14 | 1964.44 | 01-JAN-00:10 | 8079.39 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1571.44 | 19644.38 | 01-JAN-00:10 | 80793.90 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 32.64 | 158.32 | 01-JAN-00:10 | 2849.68 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 32.64 | 158.32 | 01-JAN-00:10 | 2849.68 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.14 | 1964.44 | 01-JAN-00:10 | 8079.39 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 3769.76 | 974.35 | 10-JAN-04:40 | 390054.01 | 17-AUG-14:10 |
HeatRejection:Electricity | 770.22 | 153.55 | 10-JAN-07:20 | 55581.51 | 10-SEP-15:00 |
General:HeatRejection:Electricity | 770.22 | 153.55 | 10-JAN-07:20 | 55581.51 | 10-SEP-15:00 |
Electricity:HVAC | 1470.30 | 9387.69 | 10-JAN-04:40 | 131797.85 | 30-AUG-16:00 |
ExteriorEquipment:Electricity | 3333.12 | 46194.44 | 01-JAN-00:10 | 188992.77 | 12-DEC-08:20 |
Transformer:ExteriorEquipment:Electricity | 54.48 | 979.82 | 01-JAN-00:10 | 3384.80 | 25-OCT-07:20 |
ElectricityPurchased:Facility | 25543.31 | 287925.10 | 22-JAN-05:00 | 1603116.60 | 30-AUG-15:50 |
ElectricityPurchased:Plant | 25543.31 | 287925.10 | 22-JAN-05:00 | 1603116.60 | 30-AUG-15:50 |
Cogeneration:ElectricityPurchased | 25543.31 | 287925.10 | 22-JAN-05:00 | 1603116.60 | 30-AUG-15:50 |
General:Cogeneration:ElectricityPurchased | 25543.31 | 287925.10 | 22-JAN-05:00 | 1603116.60 | 30-AUG-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 25543.31 | 287925.10 | 22-JAN-05:00 | 1603116.60 | 30-AUG-15:50 |
ElectricityNet:Plant | 25543.31 | 287925.10 | 22-JAN-05:00 | 1603116.60 | 30-AUG-15:50 |
Cogeneration:ElectricityNet | 25543.31 | 287925.10 | 22-JAN-05:00 | 1603116.60 | 30-AUG-15:50 |
General:Cogeneration:ElectricityNet | 25543.31 | 287925.10 | 22-JAN-05:00 | 1603116.60 | 30-AUG-15:50 |
Fans:Electricity | 915.75 | 5897.48 | 03-JAN-00:20 | 91221.95 | 30-AUG-16:00 |
General:Fans:Electricity | 915.75 | 5897.48 | 03-JAN-00:20 | 91221.95 | 30-AUG-16:00 |
ExteriorLights:Electricity | 325.14 | 0.00 | 01-JAN-07:30 | 37611.08 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 325.14 | 0.00 | 01-JAN-07:30 | 37611.08 | 01-JAN-06:10 |
ComputerHVAC:ExteriorEquipment:Electricity | 1424.02 | 18032.55 | 01-JAN-00:10 | 72130.20 | 31-MAR-23:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 61.82 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-10:10 |
General:HeatRecovery:Electricity | 61.82 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-10:10 |
Cooling:Electricity | 2459.32 | 1038.20 | 10-JAN-07:10 | 296302.86 | 17-AUG-14:10 |
General:Cooling:Electricity | 2459.32 | 1038.20 | 10-JAN-07:10 | 296302.86 | 17-AUG-14:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 978.48 | 666.51 | 01-JAN-00:10 | 68241.86 | 14-SEP-16:00 |
General:Pumps:Electricity | 978.48 | 666.51 | 01-JAN-00:10 | 68241.86 | 14-SEP-16:00 |
WIRED_LTG_ELECTRICITY | 56.85 | 0.00 | 01-JAN-00:10 | 5450.19 | 25-OCT-07:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 678.01 | 5695.87 | 01-JAN-00:10 | 429576.91 | 06-FEB-06:10 |
NaturalGas:Plant | 678.01 | 5695.87 | 01-JAN-00:10 | 429576.91 | 06-FEB-06:10 |
Heating:NaturalGas | 82.69 | 0.00 | 01-JAN-00:10 | 423881.04 | 06-FEB-06:10 |
Boiler:Heating:NaturalGas | 82.69 | 0.00 | 01-JAN-00:10 | 423881.04 | 06-FEB-06:10 |
WaterSystems:NaturalGas | 595.32 | 5695.87 | 01-JAN-00:10 | 73380.93 | 20-JAN-12:20 |
Water Heater:WaterSystems:NaturalGas | 595.32 | 5695.87 | 01-JAN-00:10 | 73380.93 | 20-JAN-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 16267.25 | 4619.88 | 10-JAN-07:10 | 1723418.14 | 07-AUG-14:40 |
PlantLoopCoolingDemand:HVAC | 16267.25 | 4619.88 | 10-JAN-07:10 | 1723418.14 | 07-AUG-14:40 |
CoolingCoils:PlantLoopCoolingDemand | 16267.25 | 4619.88 | 10-JAN-07:10 | 1723418.14 | 07-AUG-14:40 |
DistrictCooling:Facility | 7190.82 | 87779.68 | 22-JAN-06:00 | 370154.94 | 21-AUG-14:00 |
DistrictCooling:HVAC | 7190.82 | 87779.68 | 22-JAN-06:00 | 370154.94 | 21-AUG-14:00 |
Cooling:DistrictCooling | 7190.82 | 87779.68 | 22-JAN-06:00 | 370154.94 | 21-AUG-14:00 |
General:Cooling:DistrictCooling | 7190.82 | 87779.68 | 22-JAN-06:00 | 370154.94 | 21-AUG-14:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 12784.15 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
Water:Plant | 12784.15 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 12784.15 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
MainsWater:Plant | 12784.15 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 10503.98 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
General:HeatRejection:Water | 10503.98 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
HeatRejection:MainsWater | 10503.98 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
General:HeatRejection:MainsWater | 10503.98 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 83030.99 | 102297.59 | 10-JAN-04:40 | 8852558.97 | 02-AUG-14:10 |
EnergyTransfer:Building | 20258.81 | 92646.70 | 22-JAN-07:50 | 1468300.60 | 30-AUG-16:00 |
EnergyTransfer:Zone:BASEMENT | 644.88 | 0.00 | 01-JAN-00:10 | 70466.48 | 13-NOV-06:10 |
Heating:EnergyTransfer | 27.08 | 0.00 | 01-JAN-00:10 | 205165.29 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 5.19 | 0.00 | 01-JAN-00:10 | 17838.49 | 09-SEP-16:30 |
General:Heating:EnergyTransfer | 27.08 | 0.00 | 01-JAN-00:10 | 205165.29 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 5.19 | 0.00 | 01-JAN-00:10 | 17838.49 | 09-SEP-16:30 |
Cooling:EnergyTransfer | 20231.73 | 92138.46 | 22-JAN-07:40 | 1468300.60 | 30-AUG-16:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 639.70 | 0.00 | 01-JAN-00:10 | 70466.48 | 13-NOV-06:10 |
General:Cooling:EnergyTransfer | 20231.73 | 92138.46 | 22-JAN-07:40 | 1468300.60 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 639.70 | 0.00 | 01-JAN-00:10 | 70466.48 | 13-NOV-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 697.20 | 0.00 | 01-JAN-00:10 | 50267.76 | 27-NOV-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 697.20 | 0.00 | 01-JAN-00:10 | 50267.76 | 27-NOV-06:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 697.20 | 0.00 | 01-JAN-00:10 | 50267.76 | 27-NOV-06:10 |
EnergyTransfer:Zone:CORE_MID | 5080.03 | 0.00 | 01-JAN-00:10 | 427276.82 | 10-APR-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5080.03 | 0.00 | 01-JAN-00:10 | 427276.82 | 10-APR-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5080.03 | 0.00 | 01-JAN-00:10 | 427276.82 | 10-APR-05:10 |
EnergyTransfer:Zone:CORE_TOP | 523.78 | 0.00 | 01-JAN-00:10 | 45884.76 | 18-JUL-15:30 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.55 | 0.00 | 01-JAN-00:10 | 39310.16 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.55 | 0.00 | 01-JAN-00:10 | 39310.16 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 523.23 | 0.00 | 01-JAN-00:10 | 45884.76 | 18-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 523.23 | 0.00 | 01-JAN-00:10 | 45884.76 | 18-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 99.76 | 0.00 | 01-JAN-00:10 | 10130.20 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 99.76 | 0.00 | 01-JAN-00:10 | 10130.20 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 99.76 | 0.00 | 01-JAN-00:10 | 10130.20 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 77.78 | 0.00 | 01-JAN-00:10 | 9671.32 | 11-SEP-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 77.78 | 0.00 | 01-JAN-00:10 | 9671.32 | 11-SEP-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 77.78 | 0.00 | 01-JAN-00:10 | 9671.32 | 11-SEP-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 124.94 | 0.00 | 01-JAN-00:10 | 14927.89 | 06-NOV-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 124.94 | 0.00 | 01-JAN-00:10 | 14927.89 | 06-NOV-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 124.94 | 0.00 | 01-JAN-00:10 | 14927.89 | 06-NOV-13:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 117.63 | 0.00 | 01-JAN-00:10 | 14098.04 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 117.63 | 0.00 | 01-JAN-00:10 | 14098.04 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 117.63 | 0.00 | 01-JAN-00:10 | 14098.04 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 746.15 | 0.00 | 01-JAN-00:10 | 88319.76 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.85 | 0.00 | 01-JAN-00:10 | 49772.38 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.85 | 0.00 | 01-JAN-00:10 | 49772.38 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 743.29 | 0.00 | 01-JAN-00:10 | 88319.76 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 743.29 | 0.00 | 01-JAN-00:10 | 88319.76 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 657.97 | 0.00 | 01-JAN-00:10 | 98654.96 | 03-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.08 | 0.00 | 01-JAN-00:10 | 29913.39 | 21-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.08 | 0.00 | 01-JAN-00:10 | 29913.39 | 21-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 656.89 | 0.00 | 01-JAN-00:10 | 98654.96 | 03-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 656.89 | 0.00 | 01-JAN-00:10 | 98654.96 | 03-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1025.21 | 0.00 | 01-JAN-00:10 | 142811.32 | 06-NOV-14:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.28 | 0.00 | 01-JAN-00:10 | 27509.05 | 21-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.28 | 0.00 | 01-JAN-00:10 | 27509.05 | 21-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1024.93 | 0.00 | 01-JAN-00:10 | 142811.32 | 06-NOV-14:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1024.93 | 0.00 | 01-JAN-00:10 | 142811.32 | 06-NOV-14:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 704.69 | 0.00 | 01-JAN-00:10 | 113620.11 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.28 | 0.00 | 01-JAN-00:10 | 22979.40 | 21-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.28 | 0.00 | 01-JAN-00:10 | 22979.40 | 21-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 704.41 | 0.00 | 01-JAN-00:10 | 113620.11 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 704.41 | 0.00 | 01-JAN-00:10 | 113620.11 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 79.43 | 0.00 | 01-JAN-00:10 | 11379.31 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.63 | 0.00 | 01-JAN-00:10 | 11379.31 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.63 | 0.00 | 01-JAN-00:10 | 11379.31 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 76.79 | 0.00 | 01-JAN-00:10 | 10113.06 | 19-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 76.79 | 0.00 | 01-JAN-00:10 | 10113.06 | 19-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 70.05 | 0.00 | 01-JAN-00:10 | 10239.06 | 03-MAY-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.07 | 0.00 | 01-JAN-00:10 | 8253.54 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.07 | 0.00 | 01-JAN-00:10 | 8253.54 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 68.97 | 0.00 | 01-JAN-00:10 | 10239.06 | 03-MAY-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 68.97 | 0.00 | 01-JAN-00:10 | 10239.06 | 03-MAY-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 105.22 | 0.00 | 01-JAN-00:10 | 15627.21 | 06-NOV-14:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.85 | 0.00 | 01-JAN-00:10 | 9152.60 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.85 | 0.00 | 01-JAN-00:10 | 9152.60 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 104.37 | 0.00 | 01-JAN-00:10 | 15627.21 | 06-NOV-14:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 104.37 | 0.00 | 01-JAN-00:10 | 15627.21 | 06-NOV-14:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 74.30 | 0.00 | 01-JAN-00:10 | 12211.97 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.63 | 0.00 | 01-JAN-00:10 | 5815.69 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.63 | 0.00 | 01-JAN-00:10 | 5815.69 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 73.68 | 0.00 | 01-JAN-00:10 | 12211.97 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 73.68 | 0.00 | 01-JAN-00:10 | 12211.97 | 30-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 76.77 | 0.00 | 01-JAN-00:10 | 7405.64 | 10-OCT-15:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.58 | 0.00 | 01-JAN-00:10 | 3680.20 | 12-MAR-14:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.58 | 0.00 | 01-JAN-00:10 | 3680.20 | 12-MAR-14:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 76.19 | 0.00 | 01-JAN-00:10 | 7405.64 | 10-OCT-15:30 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 76.19 | 0.00 | 01-JAN-00:10 | 7405.64 | 10-OCT-15:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 548.48 | 0.00 | 01-JAN-00:10 | 55863.42 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 5.52 | 0.00 | 01-JAN-00:10 | 22754.28 | 29-JAN-11:40 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 5.52 | 0.00 | 01-JAN-00:10 | 22754.28 | 29-JAN-11:40 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 542.96 | 0.00 | 01-JAN-00:10 | 55863.42 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 542.96 | 0.00 | 01-JAN-00:10 | 55863.42 | 30-AUG-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 95.31 | 0.00 | 01-JAN-00:10 | 17371.23 | 07-JUL-14:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.39 | 0.00 | 01-JAN-00:10 | 13565.22 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.39 | 0.00 | 01-JAN-00:10 | 13565.22 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 89.92 | 0.00 | 01-JAN-00:10 | 17371.23 | 07-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 89.92 | 0.00 | 01-JAN-00:10 | 17371.23 | 07-JUL-14:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.33 | 958.38 | 10-JAN-08:00 | 7829.21 | 16-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.33 | 958.38 | 10-JAN-08:00 | 7829.21 | 16-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.33 | 958.38 | 10-JAN-08:00 | 7829.21 | 16-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1278.16 | 1963.86 | 10-JAN-07:00 | 73508.80 | 16-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1278.16 | 1963.86 | 10-JAN-07:00 | 73508.80 | 16-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1278.16 | 1963.86 | 10-JAN-07:00 | 73508.80 | 16-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 124.52 | 3.80 | 13-JAN-07:50 | 7461.95 | 23-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.17 | 0.00 | 01-JAN-00:10 | 519.55 | 10-JAN-04:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.17 | 0.00 | 01-JAN-00:10 | 519.55 | 10-JAN-04:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 124.35 | 0.00 | 04-JAN-03:20 | 7461.95 | 23-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 124.35 | 0.00 | 04-JAN-03:20 | 7461.95 | 23-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7166.23 | 87779.68 | 22-JAN-06:00 | 367527.12 | 21-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7166.23 | 87779.68 | 22-JAN-06:00 | 367527.12 | 21-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7166.23 | 87779.68 | 22-JAN-06:00 | 367527.12 | 21-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 378.25 | 0.00 | 01-JAN-00:10 | 325155.45 | 21-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 321.87 | 0.00 | 01-JAN-00:10 | 40639.71 | 23-JAN-12:20 |
WaterSystems:PlantLoopHeatingDemand | 321.87 | 0.00 | 01-JAN-00:10 | 40639.71 | 23-JAN-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 321.87 | 0.00 | 01-JAN-00:10 | 40639.71 | 23-JAN-12:20 |
EnergyTransfer:HVAC | 18573.90 | 9013.49 | 10-JAN-21:10 | 2210628.47 | 06-OCT-14:00 |
HeatingCoils:EnergyTransfer | 56.38 | 0.00 | 01-JAN-00:10 | 314398.69 | 06-FEB-06:10 |
PlantLoopHeatingDemand:HVAC | 56.38 | 0.00 | 01-JAN-00:10 | 314398.69 | 06-FEB-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 56.38 | 0.00 | 01-JAN-00:10 | 314398.69 | 06-FEB-06:10 |
CoolingCoils:EnergyTransfer | 15828.99 | 3581.68 | 10-JAN-07:10 | 1699646.06 | 07-AUG-14:40 |
DistrictHeating:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 13.56 | 31-MAY-23:40 |
DistrictHeating:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 13.56 | 31-MAY-23:40 |
Heating:DistrictHeating | 0.00 | 0.00 | 01-JAN-00:10 | 13.56 | 31-MAY-23:40 |
General:Heating:DistrictHeating | 0.00 | 0.00 | 01-JAN-00:10 | 13.56 | 31-MAY-23:40 |
HeatRecoveryForHeating:EnergyTransfer | 5.99 | 0.00 | 01-JAN-00:10 | 127001.52 | 20-DEC-08:00 |
HeatRecoveryForCooling:EnergyTransfer | 2682.53 | 0.00 | 01-JAN-00:10 | 644836.39 | 07-OCT-08:00 |
EnergyTransfer:Plant | 44198.28 | 0.00 | 01-JAN-00:10 | 5658202.36 | 14-SEP-16:00 |
LoopToLoop:EnergyTransfer | 15644.87 | 0.00 | 01-JAN-00:10 | 1813394.13 | 14-SEP-16:00 |
WaterSystems:EnergyTransfer | 321.87 | 0.00 | 01-JAN-00:10 | 40639.71 | 23-JAN-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 321.87 | 0.00 | 01-JAN-00:10 | 40639.71 | 23-JAN-12:20 |
Boilers:EnergyTransfer | 55.71 | 0.00 | 01-JAN-00:10 | 342636.33 | 06-FEB-06:10 |
Chillers:EnergyTransfer | 13077.38 | 0.00 | 01-JAN-00:10 | 1784750.67 | 14-SEP-16:00 |
HeatRejection:EnergyTransfer | 15098.45 | 0.00 | 01-JAN-00:10 | 2035067.52 | 14-SEP-16:00 |
General:HeatRejection:EnergyTransfer | 15098.45 | 0.00 | 01-JAN-00:10 | 2035067.52 | 14-SEP-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 5.185 | -639.698 | 0.000 | 0.000 | 92.612 | 135.577 | 424.397 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -18.074 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -697.202 | 0.000 | 0.000 | 83.608 | 121.758 | 289.614 | 0.000 | 0.000 | 0.000 | 202.223 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5080.017 | 0.000 | 0.000 | 845.738 | 1217.578 | 2896.128 | 0.000 | 0.000 | 0.000 | 120.574 | 0.000 | 0.000 | 0.000 | 0.000 | -0.011 |
CORE_TOP | 0.000 | 0.000 | 0.550 | -523.224 | 0.000 | 0.000 | 86.224 | 121.758 | 289.613 | 0.000 | 0.000 | 0.000 | 25.080 | 0.000 | 0.000 | 0.000 | 0.000 | -0.003 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -99.762 | 0.000 | 0.000 | 10.600 | 8.930 | 36.365 | 31.468 | 0.000 | 0.105 | 35.353 | 0.000 | -22.613 | 0.000 | -0.447 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -77.776 | 0.000 | 0.000 | 6.813 | 5.702 | 23.435 | 45.739 | 0.000 | 0.070 | 10.046 | 0.000 | -13.734 | 0.000 | -0.296 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -124.944 | 0.000 | 0.000 | 10.517 | 8.737 | 36.366 | 78.750 | 0.000 | 0.098 | 12.585 | 0.000 | -21.629 | 0.000 | -0.479 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -117.633 | 0.000 | 0.000 | 6.760 | 5.717 | 23.435 | 43.552 | 0.000 | 0.058 | 56.063 | 0.000 | -17.592 | 0.000 | -0.360 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 2.854 | -743.282 | 0.000 | 0.000 | 108.811 | 89.311 | 363.654 | 325.151 | 0.000 | 2.366 | 61.229 | 0.000 | -200.827 | 0.000 | -9.269 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.084 | -656.879 | 0.000 | 0.000 | 50.886 | 57.002 | 234.352 | 457.199 | 0.000 | 1.423 | 0.023 | 0.000 | -130.630 | 0.000 | -6.655 | -7.781 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.283 | -1024.912 | 0.000 | 0.000 | 105.731 | 87.392 | 363.660 | 786.553 | 0.000 | 2.116 | 0.005 | 0.000 | -210.399 | 0.000 | -11.157 | -99.265 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.283 | -704.402 | 0.000 | 0.000 | 69.280 | 57.144 | 234.351 | 446.812 | 0.000 | 1.371 | 50.214 | 0.000 | -147.848 | 0.000 | -7.205 | -0.005 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 2.634 | -76.792 | 0.000 | 0.000 | 11.003 | 8.931 | 36.365 | 32.408 | 0.000 | 0.275 | 5.224 | 0.000 | -18.977 | 0.000 | -1.070 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 1.073 | -68.971 | 0.000 | 0.000 | 6.986 | 5.700 | 23.435 | 45.661 | 0.000 | 0.166 | 0.003 | 0.000 | -12.488 | 0.000 | -0.776 | -0.785 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.850 | -104.372 | 0.000 | 0.000 | 10.667 | 8.739 | 36.366 | 78.475 | 0.000 | 0.246 | 0.000 | 0.000 | -20.207 | 0.000 | -1.313 | -9.451 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.626 | -73.674 | 0.000 | 0.000 | 7.015 | 5.714 | 23.435 | 44.589 | 0.000 | 0.166 | 7.109 | 0.000 | -14.134 | 0.000 | -0.845 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -140.325 | 0.000 | 0.000 | 0.950 | 3.264 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -17.769 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1278.161 | 0.000 | 0.000 | 9.499 | 32.637 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -302.780 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.166 | -124.350 | 0.000 | 0.000 | 0.950 | 3.264 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -33.910 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | -7166.230 | 0.000 | 0.000 | 0.000 | 0.000 | 20.569 | 38.227 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -387.423 |
GROUNDFLOOR_PLENUM | 0.582 | -76.189 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.179 | 76.419 | 0.000 | 0.000 | 0.000 | -0.991 | 0.000 |
MIDFLOOR_PLENUM | 5.521 | -542.951 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.368 | 550.496 | 0.000 | 0.000 | 0.000 | -16.433 | 0.000 |
TOPFLOOR_PLENUM | 5.388 | -89.922 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.292 | 85.942 | 0.000 | 0.000 | 0.000 | -1.699 | -0.001 |
Total Facility | 11.491 | -7875.293 | 15.587 | -12356.376 | 0.000 | 0.000 | 1545.218 | 2023.080 | 14676.396 | 2416.356 | 0.000 | 12.296 | 1298.587 | 0.000 | -831.078 | 0.000 | -58.996 | -877.261 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 09-JAN-04:12 | 0.00 | 0.00 | 0.00 | -100674.72 | 0.00 | 0.00 | 0.00 | 657.72 | 13457.54 | 0.00 | 0.00 | 0.00 | 86559.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 13-NOV-04:02 | 0.00 | 0.00 | 0.00 | -84100.34 | 0.00 | 0.00 | 0.00 | 590.68 | 5937.65 | 0.00 | 0.00 | 0.00 | 77572.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 14-APR-05:04 | 0.00 | 0.00 | 0.00 | -733633.34 | 0.00 | 0.00 | 8371.48 | 11812.12 | 76473.61 | 0.00 | 0.00 | 0.00 | 636976.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 08-SEP-05:04 | 0.00 | 0.00 | 0.00 | -73279.75 | 0.00 | 0.00 | 841.08 | 1181.21 | 7647.36 | 0.00 | 0.00 | 0.00 | 63610.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 03-JUL-05:03 | 0.00 | 0.00 | 0.00 | -12670.63 | 0.00 | 0.00 | 102.77 | 148.31 | 960.25 | 0.00 | 0.00 | 2.91 | 11698.42 | 0.00 | -242.04 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 29-MAY-08:62 | 0.00 | 0.00 | 0.00 | -16208.99 | 0.00 | 0.00 | 23.78 | 22.74 | 464.11 | 11417.16 | 0.00 | 0.00 | 4283.60 | 0.00 | -0.00 | 0.00 | -2.41 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-JAN-13:32 | 0.00 | 0.00 | 0.00 | -20112.08 | 0.00 | 0.00 | 34.41 | 35.29 | 720.19 | 16650.16 | 0.00 | 0.00 | 2682.12 | 0.00 | -0.00 | 0.00 | -10.10 | 0.00 |
PERIMETER_BOT_ZN_4 | 25-JUN-15:52 | 0.00 | 0.00 | 0.00 | -21302.70 | 0.00 | 0.00 | 21.90 | 22.74 | 464.11 | 9397.43 | 0.00 | 5.37 | 11391.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 14-AUG-03:02 | 0.00 | 0.00 | 0.00 | -119318.33 | 0.00 | 0.00 | 0.00 | 741.66 | 7455.61 | 0.00 | 0.00 | 41.29 | 114379.20 | 0.00 | -3299.43 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 29-MAY-09:32 | 0.00 | 0.00 | 0.00 | -167695.22 | 0.00 | 0.00 | 230.66 | 227.41 | 4641.14 | 93557.97 | 0.00 | 18.03 | 69020.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 10-DEC-14:32 | 0.00 | 0.00 | 0.00 | -187602.78 | 0.00 | 0.00 | 345.73 | 352.89 | 7201.95 | 147041.59 | 0.00 | 0.00 | 32792.43 | 0.00 | -0.00 | 0.00 | -131.81 | 0.00 |
PERIMETER_MID_ZN_4 | 03-SEP-15:42 | 0.00 | 0.00 | 0.00 | -176792.98 | 0.00 | 0.00 | 228.77 | 227.41 | 4641.11 | 106973.43 | 0.00 | 489.13 | 64233.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 10-SEP-14:52 | 0.00 | 0.00 | 0.00 | -15397.92 | 0.00 | 0.00 | 41.82 | 35.29 | 720.18 | 3778.41 | 0.00 | 77.68 | 10744.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 29-MAY-10:42 | 0.00 | 0.00 | 0.00 | -17051.46 | 0.00 | 0.00 | 23.07 | 22.74 | 464.11 | 5939.28 | 0.00 | 11.81 | 10590.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-JAN-14:12 | 0.00 | 0.00 | 0.00 | -21144.78 | 0.00 | 0.00 | 33.65 | 35.29 | 720.19 | 15362.81 | 0.00 | 0.00 | 5022.63 | 0.00 | -0.00 | 0.00 | -29.79 | 0.00 |
PERIMETER_TOP_ZN_4 | 03-SEP-15:42 | 0.00 | 0.00 | 0.00 | -19454.82 | 0.00 | 0.00 | 21.57 | 22.74 | 464.11 | 10592.53 | 0.00 | 54.70 | 8299.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 16-APR-18:15 | 0.00 | 0.00 | 0.00 | -7829.13 | 0.00 | 0.00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 18.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 16-APR-18:02 | 0.00 | 0.00 | 0.00 | -73508.53 | 0.00 | 0.00 | 0.00 | 158.32 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4594.02 |
DATACENTER_TOP_ZN_6 | 23-APR-18:10 | 0.00 | 0.00 | 0.00 | -7461.95 | 0.00 | 0.00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -348.30 |
DATACENTER_BASEMENT_ZN_6 | 21-AUG-16:00 | 0.00 | -367527.12 | 0.00 | 0.00 | 0.00 | 0.00 | 2183.10 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17626.26 |
GROUNDFLOOR_PLENUM | 02-JAN-06:15 | 0.00 | -9123.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9136.96 | 0.00 | -0.00 | 0.00 | -13.44 | 0.00 |
MIDFLOOR_PLENUM | 23-JUN-05:02 | 0.00 | -76132.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.98 | 76116.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 07-JUL-14:50 | 0.00 | -17370.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.20 | 17339.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-AUG-05:02 | 0.00 | -394312.10 | 0.00 | -1367551.41 | 0.00 | 0.00 | 15990.51 | 22094.05 | 616289.16 | 0.00 | 0.00 | 0.00 | 1140203.70 | 0.00 | -32281.51 | 0.00 | -432.39 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 09-SEP-16:13 | 0.00 | 0.00 | 18736.84 | 0.00 | 0.00 | 0.00 | 433.87 | 657.72 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33285.98 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 06-FEB-05:01 | 0.00 | 0.00 | 51777.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1181.21 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -58896.04 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 96770.40 | 0.00 | 0.00 | 0.00 | 0.00 | 1483.13 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31587.20 | 0.00 | -1176.23 | -72945.71 |
PERIMETER_MID_ZN_2 | 21-DEC-05:01 | 0.00 | 0.00 | 73407.26 | 0.00 | 0.00 | 0.00 | 0.00 | 955.79 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -26508.02 | 0.00 | -1317.58 | -51342.14 |
PERIMETER_MID_ZN_1 | 21-DEC-06:01 | 0.00 | 0.00 | 98437.01 | 0.00 | 0.00 | 0.00 | 1460.97 | 1483.16 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -39496.61 | 0.00 | -588.35 | -70898.78 |
PERIMETER_MID_ZN_4 | 21-DEC-06:01 | 0.00 | 0.00 | 61678.84 | 0.00 | 0.00 | 0.00 | 941.50 | 955.79 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -26074.13 | 0.00 | -390.36 | -43299.78 |
PERIMETER_TOP_ZN_3 | 06-FEB-04:01 | 0.00 | 0.00 | 13081.53 | 0.00 | 0.00 | 0.00 | 0.00 | 74.17 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2457.57 | 0.00 | -126.34 | -11317.34 |
PERIMETER_TOP_ZN_2 | 06-FEB-04:01 | 0.00 | 0.00 | 11396.99 | 0.00 | 0.00 | 0.00 | 0.00 | 47.80 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1703.53 | 0.00 | -87.61 | -10134.11 |
PERIMETER_TOP_ZN_1 | 06-FEB-04:01 | 0.00 | 0.00 | 14349.58 | 0.00 | 0.00 | 0.00 | 0.00 | 74.17 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2802.58 | 0.00 | -145.88 | -12220.85 |
PERIMETER_TOP_ZN_4 | 06-FEB-04:01 | 0.00 | 0.00 | 10394.28 | 0.00 | 0.00 | 0.00 | 0.00 | 47.80 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1913.05 | 0.00 | -97.67 | -8911.82 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 10-JAN-04:45 | 0.00 | 0.00 | 525.60 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2490.04 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 13-MAR-04:01 | 9507.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -89.20 | -9418.06 |
MIDFLOOR_PLENUM | 22-MAY-03:02 | 67534.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.46 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -67627.84 |
TOPFLOOR_PLENUM | 06-FEB-06:13 | 16751.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -46.84 | -16705.09 |
Total Facility | 21-DEC-06:01 | -854454.01 | 457281.01 | 412532.51 | -457281.01 | 0.00 | 0.00 | 19414.73 | 22094.05 | 616289.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -156948.36 | 0.00 | -3418.70 | -55509.38 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 9.1804 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.4062 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 85.0577 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 77.3669 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 8.8118 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.3530 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.0388 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.0388 | 0.2382 | 1.0000 | Not calculated | 1.2002 | 0.2382 | ||
AIRLOOP DATACENTER BOT | 0.4585 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4585 | 0.0341 | 1.0000 | Not calculated | 0.0156 | 0.0341 | ||
AIRLOOP DATACENTER MID | 4.3616 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.3616 | 0.0358 | 1.0000 | Not calculated | 0.1563 | 0.0358 | ||
AIRLOOP DATACENTER TOP | 0.4450 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4450 | 0.0351 | 1.0000 | Not calculated | 0.0156 | 0.0351 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 4.5902 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.7290 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 42.5288 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 26.3047 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.4059 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.7089 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.0388 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.0388 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2382 | ||
AIRLOOP DATACENTER BOT | 0.4585 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4585 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0341 | ||
AIRLOOP DATACENTER MID | 4.3616 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.3616 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0358 | ||
AIRLOOP DATACENTER TOP | 0.4450 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4450 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0351 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.002360 | 149.6021 | 0.000305 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.002360 | 1.9486 | 0.000305 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.002360 | 19.4861 | 0.000305 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.002360 | 1.9486 | 0.000305 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.002360 | 149.60 | 0.000305 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BOT | 0.002360 | 1.95 | 0.000305 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.002360 | 19.49 | 0.000305 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.002360 | 1.95 | 0.000305 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0388 | 5.0388 | 5.0388 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2759 | 5.2759 | 1.8571 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 49.2075 | 49.2075 | 18.0592 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.8889 | 4.8889 | 1.8529 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8446 | 0.8446 | 0.2331 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8838 | 0.8838 | 0.1768 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0306 | 1.0306 | 0.2329 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1455 | 1.1455 | 0.2291 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.6859 | 7.6859 | 2.2673 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.0378 | 9.0378 | 1.8076 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.5934 | 9.5934 | 2.2641 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.5330 | 9.5330 | 1.9066 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8890 | 0.8890 | 0.2320 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9227 | 0.9227 | 0.1845 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0750 | 1.0750 | 0.2322 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0361 | 1.0361 | 0.2072 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4585 | 0.4585 | 0.4585 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.3616 | 4.3616 | 4.3616 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4450 | 0.4450 | 0.4450 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 9.1804 | 8.4062 | 9.1804 | 2.7290 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 85.0577 | 77.3669 | 85.0577 | 26.3047 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 8.8118 | 8.3530 | 8.8118 | 2.7089 | 0.0000 | 1.0000 |
CAV_BAS | 5.0388 | 5.0388 | 5.0388 | 5.0388 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4585 | 0.4585 | 0.4585 | 0.4585 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.3616 | 4.3616 | 4.3616 | 4.3616 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4450 | 0.4450 | 0.4450 | 0.4450 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0388 | 5.0388 | 5.0388 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6380 | 2.6380 | 1.8571 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 24.6038 | 24.6038 | 18.0592 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4445 | 2.4445 | 1.8529 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4223 | 0.4223 | 0.2331 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4419 | 0.4419 | 0.1768 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5153 | 0.5153 | 0.2329 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5728 | 0.5728 | 0.2291 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.8429 | 3.8429 | 2.2673 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.5189 | 4.5189 | 1.8076 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7967 | 4.7967 | 2.2641 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7665 | 4.7665 | 1.9066 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4445 | 0.4445 | 0.2320 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4614 | 0.4614 | 0.1845 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5375 | 0.5375 | 0.2322 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5181 | 0.5181 | 0.2072 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4585 | 0.4585 | 0.4585 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.3616 | 4.3616 | 4.3616 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4450 | 0.4450 | 0.4450 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 4.5902 | 2.7290 | 2.7290 | 2.7290 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 42.5288 | 26.3047 | 26.3047 | 26.3047 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.4059 | 2.7089 | 2.7089 | 2.7089 | 0.0000 | 1.0000 |
CAV_BAS | 5.0388 | 5.0388 | 5.0388 | 5.0388 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4585 | 0.4585 | 0.4585 | 0.4585 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.3616 | 4.3616 | 4.3616 | 4.3616 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4450 | 0.4450 | 0.4450 | 0.4450 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.67 |
Number of hours cooling loads not met | 175.83 |
Number of hours not met | 176.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 |
Heating -- Boiler | 0.00 | 0.00 | 82.69 | 423881.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2459.32 | 296302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7190.82 | 370154.94 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2023.08 | 193957.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 325.14 | 37611.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.48 | 3384.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ComputerHVAC | 1424.02 | 72130.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 915.75 | 91221.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 978.48 | 68241.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 770.22 | 55581.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 61.82 | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 595.32 | 73380.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 25543.31 |
Natural Gas | 0.00 | 678.01 |
Additional | 0.00 | 7190.82 |
Total | 14676.40 | 33412.14 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 43.68 |
Space Heating | 0.00 |
Space Cooling | 53.09 |
Fans (All) | 19.77 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 551.45 |
Subtotal | 551.45 |
Natural Gas [MJ/m2] | |
Space Heating | 1.79 |
Service Water Heating | 12.85 |
Miscellaneous (All) | 14.64 |
Subtotal | 14.64 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.05 |
Space Heating | 0.25 |
Space Cooling | 28.88 |
Fans (All) | 2.74 |
Service Water Heating | 1.78 |
Receptacle Equipment | 43.93 |
Miscellaneous | 16.37 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2362. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7415.17 | 1344.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8742.00 | 18.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8694.67 | 65.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8663.33 | 96.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7719.17 | 1040.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8745.50 | 14.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8600.33 | 159.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8551.67 | 208.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8065.67 | 694.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8714.17 | 45.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8529.67 | 230.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8493.33 | 266.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8061.17 | 698.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 4785.67 | 3974.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 4863.00 | 3897.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 4810.17 | 3949.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8573.83 | 186.17 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
Average | 7644.51 | 1115.49 | 0.00 | 0.00 | 0.00 |
Sum | 175823.83 | 25656.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 364911.83 | 3704.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330776.00 | 37.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 605.50 | 1662.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 603.33 | 1664.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 587.67 | 1680.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 103395.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 364911.83 | 103395.00 | 0.00 | 0.00 | 0.00 |
Average | 75459.10 | 4875.81 | 0.00 | 0.00 | 0.00 |
Sum | 1735559.33 | 112143.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 4136.17 | 4623.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8672.00 | 88.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8756.67 | 3.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8630.17 | 129.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8542.33 | 217.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8441.00 | 319.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7465.33 | 1294.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8005.83 | 754.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7713.83 | 1046.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7656.67 | 1103.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7357.33 | 1402.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7824.83 | 935.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7603.33 | 1156.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7509.83 | 1250.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7390.83 | 1369.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6127.83 | 2632.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6087.17 | 2672.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6066.33 | 2693.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8714.83 | 45.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8427.83 | 332.17 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 1.17 | 0.00 | 0.00 | 0.00 |
Max | 8758.83 | 8760.00 | 0.00 | 0.00 | 0.00 |
Average | 7332.33 | 1427.67 | 0.00 | 0.00 | 0.00 |
Sum | 168643.67 | 32836.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 293217.17 | 75398.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330609.00 | 204.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330806.00 | 7.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330796.00 | 17.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 831.83 | 1436.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 815.33 | 1452.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 800.83 | 1467.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 103395.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330806.00 | 103395.00 | 0.00 | 0.00 | 0.00 |
Average | 72361.96 | 7972.95 | 0.00 | 0.00 | 0.00 |
Sum | 1664325.17 | 183377.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:54
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.510972E+11 | 100714.27 | 09-JAN-04:12 | 8.67 | 6.99 | 0.567277E+10 | 7499.41 | 12-JAN-10:09 | 18.17 | 17.41 |
February | 0.446855E+11 | 100289.71 | 13-FEB-04:03 | 6.38 | 2.53 | 0.514508E+10 | 7499.09 | 09-FEB-10:00 | 6.38 | 2.53 |
March | 0.514119E+11 | 98286.81 | 20-MAR-03:02 | 12.55 | 8.37 | 0.613867E+10 | 7499.71 | 23-MAR-09:20 | 16.97 | 14.65 |
April | 0.471341E+11 | 96806.33 | 10-APR-03:02 | 13.30 | 9.00 | 0.545470E+10 | 7499.32 | 12-APR-09:20 | 21.23 | 16.81 |
May | 0.512338E+11 | 71226.47 | 30-MAY-03:02 | 25.60 | 23.91 | 0.590827E+10 | 7498.82 | 05-MAY-09:20 | 25.60 | 23.91 |
June | 0.515616E+11 | 74281.70 | 07-JUN-03:02 | 21.10 | 18.25 | 0.588749E+10 | 7498.82 | 29-JUN-09:20 | 29.63 | 25.44 |
July | 0.532924E+11 | 71744.94 | 05-JUL-03:02 | 25.60 | 23.97 | 0.547936E+10 | 7498.80 | 14-JUL-09:20 | 24.27 | 23.35 |
August | 0.620320E+11 | 75370.86 | 28-AUG-03:02 | 26.27 | 23.76 | 0.614566E+10 | 7498.78 | 25-AUG-13:20 | 26.27 | 23.76 |
September | 0.557254E+11 | 78567.97 | 05-SEP-02:13 | 23.20 | 23.20 | 0.546051E+10 | 7498.80 | 14-SEP-13:20 | 28.13 | 24.89 |
October | 0.589485E+11 | 88874.08 | 28-OCT-05:03 | 10.00 | 5.56 | 0.567972E+10 | 7499.09 | 17-OCT-13:20 | 10.00 | 5.56 |
November | 0.572188E+11 | 97038.41 | 24-NOV-04:03 | 10.03 | 8.79 | 0.562317E+10 | 7499.03 | 21-NOV-14:00 | 10.03 | 8.79 |
December | 0.553546E+11 | 99135.99 | 04-DEC-04:03 | 6.00 | 5.06 | 0.548004E+10 | 7499.55 | 08-DEC-10:00 | 24.00 | 18.77 |
Annual Sum or Average | 0.639696E+12 | 0.680754E+11 | ||||||||
Minimum of Months | 0.446855E+11 | 71226.47 | 6.00 | 2.53 | 0.514508E+10 | 7498.78 | 6.38 | 2.53 | ||
Maximum of Months | 0.620320E+11 | 100714.27 | 26.27 | 23.97 | 0.614566E+10 | 7499.71 | 29.63 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.451328E+11 | 83572.81 | 02-JAN-04:02 | 17.00 | 16.27 | 0.504024E+10 | 6734.76 | 05-JAN-14:09 | 14.17 | 9.63 |
February | 0.436681E+11 | 80586.93 | 21-FEB-04:03 | 17.30 | 17.30 | 0.458411E+10 | 6734.65 | 09-FEB-14:00 | 17.30 | 17.30 |
March | 0.553513E+11 | 81033.29 | 20-MAR-03:02 | 12.55 | 8.37 | 0.548105E+10 | 6734.93 | 23-MAR-09:09 | 16.78 | 14.63 |
April | 0.610045E+11 | 79016.52 | 10-APR-03:02 | 13.30 | 9.00 | 0.486751E+10 | 6734.83 | 10-APR-13:00 | 20.50 | 10.92 |
May | 0.578848E+11 | 76261.15 | 09-MAY-03:02 | 23.90 | 21.88 | 0.526910E+10 | 6734.43 | 22-MAY-09:09 | 26.93 | 23.35 |
June | 0.627979E+11 | 74077.96 | 07-JUN-03:02 | 21.10 | 18.25 | 0.525249E+10 | 6734.43 | 27-JUN-09:09 | 28.58 | 25.38 |
July | 0.677113E+11 | 67027.64 | 12-JUL-05:02 | 23.90 | 23.16 | 0.488146E+10 | 6734.43 | 13-JUL-09:30 | 24.45 | 23.19 |
August | 0.740768E+11 | 66853.99 | 01-AUG-05:02 | 23.90 | 22.91 | 0.548604E+10 | 6734.43 | 07-AUG-09:09 | 27.50 | 25.10 |
September | 0.565939E+11 | 78029.09 | 20-SEP-03:02 | 22.38 | 21.02 | 0.486633E+10 | 6734.43 | 26-SEP-09:09 | 22.80 | 22.02 |
October | 0.610594E+11 | 80965.90 | 30-OCT-03:02 | 17.00 | 14.54 | 0.506539E+10 | 6734.76 | 17-OCT-13:09 | 17.00 | 14.54 |
November | 0.559588E+11 | 84093.15 | 13-NOV-04:02 | 9.98 | 8.04 | 0.501983E+10 | 6734.72 | 13-NOV-10:09 | 16.47 | 13.02 |
December | 0.559627E+11 | 83730.07 | 26-DEC-04:02 | 6.82 | 3.27 | 0.488674E+10 | 6734.74 | 26-DEC-14:00 | 13.30 | 6.27 |
Annual Sum or Average | 0.697202E+12 | 0.607003E+11 | ||||||||
Minimum of Months | 0.436681E+11 | 66853.99 | 6.82 | 3.27 | 0.458411E+10 | 6734.43 | 13.30 | 6.27 | ||
Maximum of Months | 0.740768E+11 | 84093.15 | 23.90 | 23.16 | 0.548604E+10 | 6734.93 | 28.58 | 25.38 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342035E+11 | 70706.70 | 20-JAN-06:04 | 17.00 | 17.00 | 0.480661E+10 | 6734.47 | 03-JAN-14:09 | 17.00 | 17.00 |
February | 0.317597E+11 | 68997.04 | 24-FEB-06:03 | 14.50 | 14.50 | 0.442502E+10 | 6734.45 | 23-FEB-10:09 | 14.50 | 14.50 |
March | 0.388599E+11 | 71616.10 | 28-MAR-05:04 | 19.05 | 18.47 | 0.534864E+10 | 6734.58 | 24-MAR-09:00 | 19.05 | 18.47 |
April | 0.401875E+11 | 73372.89 | 14-APR-05:04 | 18.80 | 18.80 | 0.482737E+10 | 6734.74 | 10-APR-13:00 | 18.80 | 18.80 |
May | 0.484283E+11 | 69064.57 | 23-MAY-04:03 | 24.32 | 23.29 | 0.524460E+10 | 6734.45 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.488529E+11 | 70862.51 | 07-JUN-04:03 | 21.10 | 18.53 | 0.522803E+10 | 6734.46 | 01-JUN-13:09 | 21.10 | 18.53 |
July | 0.488963E+11 | 69581.97 | 12-JUL-04:03 | 23.40 | 22.98 | 0.485177E+10 | 6734.44 | 14-JUL-09:09 | 24.08 | 23.26 |
August | 0.505900E+11 | 70282.77 | 17-AUG-04:03 | 21.77 | 21.49 | 0.545764E+10 | 6734.45 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.460511E+11 | 70017.20 | 08-SEP-04:03 | 24.17 | 23.46 | 0.483300E+10 | 6734.44 | 27-SEP-13:09 | 23.30 | 22.57 |
October | 0.458805E+11 | 71165.85 | 17-OCT-04:03 | 17.42 | 12.92 | 0.503069E+10 | 6734.78 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.386151E+11 | 73022.89 | 01-NOV-05:04 | 22.62 | 22.36 | 0.495274E+10 | 6734.74 | 13-NOV-10:09 | 16.47 | 13.02 |
December | 0.356782E+11 | 72726.97 | 12-DEC-06:04 | 20.17 | 20.17 | 0.472857E+10 | 6734.60 | 18-DEC-14:09 | 16.17 | 10.34 |
Annual Sum or Average | 0.508003E+12 | 0.597347E+11 | ||||||||
Minimum of Months | 0.317597E+11 | 68997.04 | 14.50 | 12.92 | 0.442502E+10 | 6734.44 | 14.50 | 10.34 | ||
Maximum of Months | 0.505900E+11 | 73372.89 | 24.32 | 23.46 | 0.545764E+10 | 6734.78 | 27.80 | 24.45 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.299399E+11 | 66898.55 | 20-JAN-06:02 | 17.00 | 17.00 | 0.437629E+10 | 6734.36 | 18-JAN-14:09 | 17.00 | 17.00 |
February | 0.293755E+11 | 66210.95 | 03-FEB-06:03 | 18.90 | 18.50 | 0.414367E+10 | 6734.39 | 28-FEB-10:20 | 21.07 | 19.22 |
March | 0.366940E+11 | 68196.05 | 28-MAR-05:02 | 19.05 | 18.47 | 0.507207E+10 | 6734.46 | 20-MAR-13:00 | 19.05 | 18.47 |
April | 0.408247E+11 | 70472.24 | 06-APR-05:04 | 17.78 | 16.89 | 0.476651E+10 | 6734.71 | 10-APR-13:00 | 20.50 | 10.92 |
May | 0.538600E+11 | 69727.37 | 23-MAY-04:03 | 24.32 | 23.29 | 0.525148E+10 | 6734.42 | 23-MAY-09:09 | 26.47 | 24.28 |
June | 0.552468E+11 | 69990.53 | 30-JUN-03:02 | 23.48 | 22.93 | 0.523790E+10 | 6734.43 | 01-JUN-13:09 | 23.48 | 22.93 |
July | 0.553398E+11 | 70094.66 | 12-JUL-04:03 | 23.40 | 22.98 | 0.486217E+10 | 6734.44 | 14-JUL-09:09 | 24.08 | 23.26 |
August | 0.565705E+11 | 69113.62 | 01-AUG-04:03 | 23.90 | 22.80 | 0.546468E+10 | 6734.42 | 17-AUG-09:09 | 26.28 | 23.28 |
September | 0.495937E+11 | 73289.84 | 08-SEP-05:04 | 24.58 | 23.92 | 0.483640E+10 | 6734.43 | 26-SEP-09:09 | 22.80 | 22.02 |
October | 0.478946E+11 | 71681.92 | 17-OCT-05:04 | 16.83 | 11.73 | 0.500230E+10 | 6734.73 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.360971E+11 | 72393.33 | 04-NOV-05:04 | 20.58 | 20.07 | 0.473274E+10 | 6734.48 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.317895E+11 | 66272.70 | 12-DEC-06:02 | 20.17 | 20.17 | 0.433867E+10 | 6734.44 | 01-DEC-14:00 | 20.17 | 20.17 |
Annual Sum or Average | 0.523226E+12 | 0.580849E+11 | ||||||||
Minimum of Months | 0.293755E+11 | 66210.95 | 16.83 | 11.73 | 0.414367E+10 | 6734.36 | 17.00 | 10.92 | ||
Maximum of Months | 0.565705E+11 | 73289.84 | 24.58 | 23.92 | 0.546468E+10 | 6734.73 | 26.47 | 24.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472573E+10 | 9695.97 | 31-JAN-06:02 | 18.17 | 18.17 | 0.588632E+09 | 845.59 | 02-JAN-14:39 | 18.17 | 18.17 |
February | 0.481991E+10 | 6310.69 | 22-FEB-14:30 | 25.55 | 20.41 | 0.553900E+09 | 845.61 | 09-FEB-14:00 | 25.55 | 20.41 |
March | 0.636125E+10 | 8134.79 | 27-MAR-05:02 | 19.82 | 18.59 | 0.671571E+09 | 845.61 | 24-MAR-09:20 | 19.82 | 18.59 |
April | 0.826950E+10 | 10389.85 | 24-APR-05:02 | 20.08 | 20.03 | 0.609324E+09 | 845.65 | 18-APR-13:00 | 20.08 | 20.03 |
May | 0.984317E+10 | 11405.88 | 31-MAY-03:02 | 23.22 | 21.33 | 0.664426E+09 | 845.60 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.111942E+11 | 11614.97 | 25-JUN-15:52 | 32.80 | 24.12 | 0.662264E+09 | 845.60 | 01-JUN-13:09 | 32.80 | 24.12 |
July | 0.117800E+11 | 12672.33 | 03-JUL-05:03 | 26.10 | 23.49 | 0.615689E+09 | 845.60 | 12-JUL-13:39 | 24.47 | 22.46 |
August | 0.124249E+11 | 12485.70 | 14-AUG-05:03 | 26.10 | 23.77 | 0.690630E+09 | 845.60 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.887390E+10 | 10850.99 | 05-SEP-05:03 | 22.80 | 22.80 | 0.613088E+09 | 845.60 | 27-SEP-13:09 | 23.30 | 22.57 |
October | 0.895911E+10 | 10849.70 | 07-OCT-05:02 | 26.17 | 26.04 | 0.635753E+09 | 845.64 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.654338E+10 | 9719.95 | 02-NOV-05:02 | 23.38 | 22.55 | 0.623005E+09 | 845.63 | 13-NOV-10:09 | 16.47 | 13.02 |
December | 0.596719E+10 | 10690.56 | 11-DEC-06:02 | 20.83 | 20.26 | 0.591454E+09 | 845.62 | 26-DEC-14:00 | 13.30 | 6.27 |
Annual Sum or Average | 0.997622E+11 | 0.751973E+10 | ||||||||
Minimum of Months | 0.472573E+10 | 6310.69 | 18.17 | 18.17 | 0.553900E+09 | 845.59 | 13.30 | 6.27 | ||
Maximum of Months | 0.124249E+11 | 12672.33 | 32.80 | 26.04 | 0.690630E+09 | 845.65 | 32.80 | 24.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.377890E+10 | 9858.53 | 01-JAN-10:13 | 20.67 | 16.62 | 0.393339E+09 | 544.95 | 11-JAN-10:09 | 14.67 | 12.06 |
February | 0.393365E+10 | 7069.83 | 27-FEB-10:10 | 21.37 | 19.24 | 0.362865E+09 | 544.96 | 09-FEB-10:00 | 21.37 | 19.24 |
March | 0.535747E+10 | 10041.24 | 26-MAR-09:02 | 23.67 | 19.70 | 0.433181E+09 | 544.97 | 23-MAR-09:09 | 23.67 | 19.70 |
April | 0.670698E+10 | 12772.77 | 23-APR-11:02 | 26.70 | 20.26 | 0.391841E+09 | 544.97 | 18-APR-13:00 | 26.70 | 20.26 |
May | 0.806037E+10 | 16209.80 | 29-MAY-08:62 | 26.88 | 22.53 | 0.428369E+09 | 544.94 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.865813E+10 | 15406.75 | 11-JUN-08:53 | 27.80 | 20.73 | 0.426643E+09 | 544.94 | 01-JUN-13:09 | 27.80 | 20.73 |
July | 0.885479E+10 | 15552.00 | 23-JUL-09:53 | 31.10 | 26.51 | 0.396576E+09 | 544.93 | 12-JUL-13:39 | 31.10 | 26.51 |
August | 0.902232E+10 | 13743.76 | 06-AUG-10:02 | 30.17 | 26.87 | 0.444486E+09 | 544.94 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.687953E+10 | 15616.42 | 24-SEP-09:23 | 28.85 | 25.01 | 0.395094E+09 | 544.93 | 27-SEP-13:09 | 23.30 | 22.57 |
October | 0.703860E+10 | 15460.95 | 09-OCT-09:02 | 27.42 | 22.34 | 0.409507E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.510722E+10 | 8703.35 | 11-NOV-09:03 | 24.40 | 21.68 | 0.402555E+09 | 544.95 | 09-NOV-10:09 | 24.40 | 21.68 |
December | 0.437804E+10 | 5271.38 | 16-DEC-09:40 | 23.33 | 20.99 | 0.378900E+09 | 544.95 | 04-DEC-10:00 | 23.33 | 20.99 |
Annual Sum or Average | 0.777760E+11 | 0.486336E+10 | ||||||||
Minimum of Months | 0.377890E+10 | 5271.38 | 20.67 | 16.62 | 0.362865E+09 | 544.93 | 14.67 | 12.06 | ||
Maximum of Months | 0.902232E+10 | 16209.80 | 31.10 | 26.87 | 0.444486E+09 | 544.97 | 31.10 | 26.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.813918E+10 | 20113.83 | 01-JAN-13:32 | 25.67 | 18.12 | 0.624505E+09 | 860.90 | 19-JAN-14:20 | 25.00 | 21.54 |
February | 0.799666E+10 | 18596.69 | 26-FEB-13:23 | 26.35 | 19.10 | 0.569903E+09 | 861.22 | 27-FEB-14:20 | 25.70 | 20.08 |
March | 0.846299E+10 | 17722.26 | 26-MAR-14:23 | 26.90 | 20.14 | 0.675420E+09 | 845.65 | 23-MAR-09:30 | 26.90 | 20.14 |
April | 0.952936E+10 | 12887.73 | 28-APR-05:02 | 22.80 | 21.69 | 0.609783E+09 | 845.69 | 18-APR-13:00 | 22.80 | 21.69 |
May | 0.100214E+11 | 13168.16 | 22-MAY-05:03 | 26.10 | 22.55 | 0.664461E+09 | 845.62 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.108397E+11 | 13287.56 | 29-JUN-05:02 | 25.18 | 24.55 | 0.662083E+09 | 845.62 | 01-JUN-13:09 | 25.18 | 24.55 |
July | 0.116543E+11 | 13792.04 | 24-JUL-05:03 | 27.02 | 24.85 | 0.615629E+09 | 845.61 | 12-JUL-13:39 | 27.02 | 24.85 |
August | 0.133815E+11 | 13999.37 | 06-AUG-13:23 | 30.00 | 24.60 | 0.691036E+09 | 845.62 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.106211E+11 | 18412.61 | 10-SEP-13:02 | 35.13 | 27.70 | 0.614239E+09 | 845.62 | 20-SEP-13:39 | 26.60 | 22.72 |
October | 0.130306E+11 | 19006.38 | 15-OCT-13:32 | 29.67 | 22.65 | 0.638861E+09 | 859.07 | 13-OCT-13:39 | 29.67 | 22.65 |
November | 0.110563E+11 | 18597.68 | 11-NOV-11:02 | 26.18 | 21.89 | 0.631360E+09 | 892.47 | 06-NOV-14:09 | 26.18 | 21.89 |
December | 0.102112E+11 | 19287.60 | 17-DEC-13:12 | 19.00 | 12.71 | 0.605976E+09 | 869.92 | 15-DEC-14:39 | 19.00 | 12.71 |
Annual Sum or Average | 0.124944E+12 | 0.760325E+10 | ||||||||
Minimum of Months | 0.799666E+10 | 12887.73 | 19.00 | 12.71 | 0.569903E+09 | 845.61 | 19.00 | 12.71 | ||
Maximum of Months | 0.133815E+11 | 20113.83 | 35.13 | 27.70 | 0.691036E+09 | 892.47 | 29.67 | 24.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.541455E+10 | 19622.35 | 01-JAN-16:12 | 24.67 | 18.84 | 0.392994E+09 | 544.96 | 05-JAN-14:00 | 15.00 | 10.71 |
February | 0.615018E+10 | 20630.06 | 26-FEB-16:42 | 24.58 | 19.86 | 0.368312E+09 | 544.96 | 09-FEB-14:00 | 24.58 | 19.86 |
March | 0.857760E+10 | 18351.83 | 26-MAR-14:23 | 26.90 | 20.14 | 0.444224E+09 | 544.97 | 23-MAR-09:09 | 26.90 | 20.14 |
April | 0.116010E+11 | 20561.43 | 23-APR-18:22 | 24.40 | 20.99 | 0.396672E+09 | 545.00 | 18-APR-13:00 | 24.40 | 20.99 |
May | 0.977846E+10 | 21173.29 | 28-MAY-15:52 | 33.90 | 24.40 | 0.429042E+09 | 544.94 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.117381E+11 | 21304.75 | 25-JUN-15:52 | 32.80 | 24.12 | 0.427915E+09 | 544.94 | 01-JUN-13:09 | 32.80 | 24.12 |
July | 0.129228E+11 | 20414.04 | 02-JUL-15:42 | 28.98 | 25.06 | 0.398183E+09 | 544.93 | 12-JUL-13:39 | 24.47 | 22.46 |
August | 0.148996E+11 | 20487.62 | 20-AUG-17:12 | 30.33 | 24.28 | 0.446578E+09 | 544.94 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.910596E+10 | 20567.05 | 24-SEP-16:02 | 30.32 | 25.93 | 0.396187E+09 | 544.93 | 07-SEP-13:39 | 30.32 | 25.93 |
October | 0.103333E+11 | 20600.01 | 09-OCT-16:22 | 28.00 | 21.50 | 0.412099E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.857115E+10 | 19237.04 | 05-NOV-14:43 | 27.20 | 20.17 | 0.407682E+09 | 544.97 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.854101E+10 | 20531.51 | 10-DEC-16:42 | 25.33 | 19.74 | 0.396448E+09 | 544.97 | 26-DEC-14:00 | 13.30 | 6.27 |
Annual Sum or Average | 0.117634E+12 | 0.491634E+10 | ||||||||
Minimum of Months | 0.541455E+10 | 18351.83 | 24.40 | 18.84 | 0.368312E+09 | 544.93 | 13.30 | 6.27 | ||
Maximum of Months | 0.148996E+11 | 21304.75 | 33.90 | 25.93 | 0.446578E+09 | 545.00 | 32.80 | 25.93 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310626E+10 | 4101.53 | 02-JAN-13:30 | 26.00 | 18.64 | 0.528239E+09 | 845.59 | 02-JAN-14:39 | 26.67 | 18.58 |
February | 0.332163E+10 | 4685.17 | 28-FEB-15:00 | 25.00 | 20.38 | 0.506152E+09 | 845.59 | 28-FEB-14:09 | 25.00 | 20.38 |
March | 0.434099E+10 | 7573.57 | 28-MAR-05:02 | 19.05 | 18.47 | 0.619843E+09 | 845.59 | 28-MAR-13:39 | 27.20 | 21.71 |
April | 0.534566E+10 | 9202.47 | 14-APR-05:02 | 18.80 | 18.80 | 0.596342E+09 | 845.60 | 12-APR-13:20 | 18.80 | 18.80 |
May | 0.853108E+10 | 11756.53 | 26-MAY-03:02 | 25.50 | 23.88 | 0.663872E+09 | 845.60 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.925239E+10 | 11867.13 | 28-JUN-03:02 | 27.20 | 25.10 | 0.662210E+09 | 845.60 | 01-JUN-13:09 | 27.20 | 25.10 |
July | 0.914000E+10 | 11875.67 | 10-JUL-03:02 | 25.60 | 23.91 | 0.615754E+09 | 845.59 | 12-JUL-13:39 | 24.47 | 22.46 |
August | 0.905717E+10 | 11933.78 | 14-AUG-03:02 | 26.52 | 24.51 | 0.690528E+09 | 845.60 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.734527E+10 | 10365.35 | 11-SEP-05:02 | 25.42 | 23.91 | 0.611433E+09 | 845.59 | 07-SEP-13:39 | 25.42 | 23.91 |
October | 0.680515E+10 | 11093.14 | 06-OCT-03:02 | 26.67 | 25.46 | 0.629473E+09 | 845.63 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.448764E+10 | 9281.79 | 01-NOV-05:02 | 22.62 | 22.36 | 0.586863E+09 | 845.60 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.359590E+10 | 8490.26 | 12-DEC-06:02 | 20.17 | 20.17 | 0.527510E+09 | 845.59 | 11-DEC-14:00 | 20.17 | 20.17 |
Annual Sum or Average | 0.743291E+11 | 0.723822E+10 | ||||||||
Minimum of Months | 0.310626E+10 | 4101.53 | 18.80 | 18.47 | 0.506152E+09 | 845.59 | 18.80 | 15.14 | ||
Maximum of Months | 0.925239E+10 | 11933.78 | 27.20 | 25.46 | 0.690528E+09 | 845.63 | 27.80 | 25.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.290915E+10 | 5689.03 | 19-JAN-10:00 | 23.00 | 20.89 | 0.264032E+09 | 521.19 | 02-JAN-15:20 | 23.00 | 20.89 |
February | 0.307931E+10 | 6071.84 | 27-FEB-10:00 | 21.10 | 19.21 | 0.251230E+09 | 521.21 | 09-FEB-11:09 | 21.10 | 19.21 |
March | 0.415217E+10 | 8225.52 | 26-MAR-09:53 | 25.50 | 20.23 | 0.305969E+09 | 521.23 | 23-MAR-08:50 | 25.50 | 20.23 |
April | 0.532253E+10 | 15659.31 | 23-APR-11:02 | 26.70 | 20.26 | 0.286539E+09 | 521.24 | 18-APR-14:20 | 26.70 | 20.26 |
May | 0.758591E+10 | 16771.03 | 29-MAY-09:32 | 28.53 | 23.16 | 0.315215E+09 | 521.20 | 03-MAY-12:09 | 28.53 | 23.16 |
June | 0.792456E+10 | 15931.27 | 11-JUN-08:53 | 27.80 | 20.73 | 0.313898E+09 | 521.20 | 12-JUN-12:09 | 31.70 | 20.35 |
July | 0.782266E+10 | 15960.63 | 16-JUL-08:32 | 28.53 | 23.97 | 0.292962E+09 | 521.20 | 05-JUL-12:09 | 28.53 | 23.97 |
August | 0.764917E+10 | 15688.00 | 27-AUG-10:23 | 30.00 | 24.51 | 0.327084E+09 | 521.20 | 30-AUG-12:09 | 31.18 | 24.70 |
September | 0.622301E+10 | 16589.43 | 03-SEP-09:42 | 29.98 | 24.61 | 0.290219E+09 | 521.20 | 07-SEP-14:20 | 24.20 | 22.95 |
October | 0.604017E+10 | 15872.94 | 09-OCT-09:23 | 28.05 | 22.46 | 0.299526E+09 | 521.23 | 17-OCT-12:20 | 21.33 | 14.79 |
November | 0.395096E+10 | 9410.98 | 01-NOV-05:02 | 22.62 | 22.36 | 0.288341E+09 | 521.20 | 21-NOV-15:39 | 21.47 | 15.14 |
December | 0.302905E+10 | 5466.50 | 12-DEC-06:02 | 20.17 | 20.17 | 0.258097E+09 | 521.20 | 01-DEC-11:20 | 20.17 | 20.17 |
Annual Sum or Average | 0.656887E+11 | 0.349311E+10 | ||||||||
Minimum of Months | 0.290915E+10 | 5466.50 | 20.17 | 19.21 | 0.251230E+09 | 521.19 | 20.17 | 14.79 | ||
Maximum of Months | 0.792456E+10 | 16771.03 | 30.00 | 24.61 | 0.327084E+09 | 521.24 | 31.70 | 24.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.719380E+10 | 17503.37 | 16-JAN-14:32 | 26.67 | 18.75 | 0.615196E+09 | 890.16 | 19-JAN-14:50 | 25.00 | 21.54 |
February | 0.685216E+10 | 17547.73 | 26-FEB-13:32 | 26.43 | 19.30 | 0.561151E+09 | 882.17 | 27-FEB-14:39 | 25.90 | 20.26 |
March | 0.655985E+10 | 15073.98 | 05-MAR-12:53 | 27.70 | 18.32 | 0.658908E+09 | 845.63 | 03-MAR-14:00 | 27.70 | 18.32 |
April | 0.678073E+10 | 11532.35 | 29-APR-05:03 | 23.20 | 21.68 | 0.604096E+09 | 845.67 | 10-APR-13:00 | 23.20 | 21.68 |
May | 0.876873E+10 | 13091.64 | 22-MAY-03:02 | 26.10 | 22.50 | 0.663868E+09 | 845.61 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.890649E+10 | 12925.19 | 14-JUN-05:02 | 25.00 | 22.88 | 0.661867E+09 | 845.62 | 01-JUN-13:09 | 25.00 | 22.88 |
July | 0.906282E+10 | 14365.02 | 20-JUL-03:02 | 26.70 | 24.39 | 0.615595E+09 | 845.61 | 12-JUL-13:39 | 26.70 | 24.39 |
August | 0.101501E+11 | 14830.63 | 14-AUG-03:02 | 26.52 | 24.51 | 0.691111E+09 | 845.62 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.936054E+10 | 17093.21 | 03-SEP-14:22 | 32.45 | 24.62 | 0.613563E+09 | 845.62 | 20-SEP-13:39 | 26.60 | 22.72 |
October | 0.113525E+11 | 18135.31 | 08-OCT-13:42 | 32.83 | 26.23 | 0.638847E+09 | 882.60 | 13-OCT-13:50 | 32.87 | 23.24 |
November | 0.938609E+10 | 17435.09 | 05-NOV-14:43 | 27.20 | 20.17 | 0.629076E+09 | 919.62 | 06-NOV-14:09 | 28.30 | 21.03 |
December | 0.811872E+10 | 18762.01 | 10-DEC-14:32 | 27.67 | 20.09 | 0.593427E+09 | 885.72 | 15-DEC-14:50 | 29.00 | 21.65 |
Annual Sum or Average | 0.102493E+12 | 0.754671E+10 | ||||||||
Minimum of Months | 0.655985E+10 | 11532.35 | 23.20 | 18.32 | 0.561151E+09 | 845.61 | 23.20 | 18.32 | ||
Maximum of Months | 0.113525E+11 | 18762.01 | 32.83 | 26.23 | 0.691111E+09 | 919.62 | 32.87 | 24.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334894E+10 | 7660.06 | 20-JAN-06:02 | 17.00 | 17.00 | 0.359582E+09 | 544.93 | 02-JAN-14:39 | 17.00 | 17.00 |
February | 0.358503E+10 | 8803.27 | 27-FEB-16:30 | 24.95 | 20.41 | 0.340483E+09 | 544.94 | 09-FEB-14:00 | 24.95 | 20.41 |
March | 0.445647E+10 | 12145.99 | 06-MAR-06:02 | 18.80 | 18.03 | 0.411413E+09 | 544.93 | 03-MAR-14:00 | 18.80 | 18.03 |
April | 0.580325E+10 | 16471.49 | 16-APR-16:31 | 19.97 | 13.44 | 0.389897E+09 | 544.96 | 10-APR-13:00 | 19.97 | 13.44 |
May | 0.747515E+10 | 16955.44 | 28-MAY-18:02 | 29.32 | 24.32 | 0.428396E+09 | 544.93 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.805193E+10 | 16685.65 | 11-JUN-16:52 | 33.30 | 21.96 | 0.427391E+09 | 544.94 | 01-JUN-13:09 | 33.30 | 21.96 |
July | 0.782567E+10 | 17308.33 | 16-JUL-16:32 | 30.17 | 24.94 | 0.397511E+09 | 544.93 | 11-JUL-13:09 | 30.17 | 24.94 |
August | 0.826345E+10 | 16274.02 | 20-AUG-17:12 | 30.33 | 24.28 | 0.445893E+09 | 544.93 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.668726E+10 | 17680.34 | 03-SEP-15:42 | 32.28 | 24.61 | 0.394896E+09 | 544.93 | 07-SEP-13:39 | 26.07 | 23.43 |
October | 0.663297E+10 | 17003.90 | 08-OCT-16:22 | 30.00 | 24.93 | 0.408389E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.450085E+10 | 11607.15 | 01-NOV-05:02 | 22.62 | 22.36 | 0.388404E+09 | 544.95 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.381009E+10 | 11459.06 | 13-DEC-06:02 | 20.00 | 20.00 | 0.356546E+09 | 544.94 | 07-DEC-14:50 | 20.00 | 20.00 |
Annual Sum or Average | 0.704411E+11 | 0.474880E+10 | ||||||||
Minimum of Months | 0.334894E+10 | 7660.06 | 17.00 | 13.44 | 0.340483E+09 | 544.93 | 17.00 | 13.44 | ||
Maximum of Months | 0.826345E+10 | 17680.34 | 33.30 | 24.94 | 0.445893E+09 | 544.96 | 33.30 | 24.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228940E+10 | 4399.37 | 31-JAN-16:00 | 25.00 | 21.54 | 0.510238E+09 | 845.59 | 02-JAN-14:09 | 25.00 | 21.54 |
February | 0.285318E+10 | 5061.33 | 28-FEB-15:00 | 25.00 | 20.38 | 0.488621E+09 | 845.58 | 28-FEB-14:09 | 25.00 | 20.38 |
March | 0.399956E+10 | 6376.07 | 30-MAR-13:30 | 28.55 | 22.55 | 0.596624E+09 | 845.59 | 27-MAR-13:09 | 28.55 | 22.55 |
April | 0.550644E+10 | 10663.02 | 27-APR-05:02 | 20.92 | 20.25 | 0.585587E+09 | 845.60 | 12-APR-13:30 | 20.92 | 20.25 |
May | 0.941380E+10 | 12722.48 | 22-MAY-03:02 | 26.10 | 22.50 | 0.664080E+09 | 845.60 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.103521E+11 | 13452.12 | 17-JUN-03:02 | 25.60 | 23.91 | 0.662494E+09 | 845.60 | 01-JUN-13:09 | 25.60 | 23.91 |
July | 0.102424E+11 | 15086.01 | 23-JUL-14:22 | 32.50 | 25.44 | 0.616142E+09 | 845.59 | 11-JUL-13:09 | 32.50 | 25.44 |
August | 0.100495E+11 | 13663.98 | 28-AUG-03:02 | 26.27 | 23.76 | 0.690695E+09 | 845.60 | 25-AUG-13:09 | 26.27 | 23.76 |
September | 0.790544E+10 | 15398.21 | 10-SEP-14:52 | 35.60 | 27.28 | 0.611169E+09 | 845.60 | 07-SEP-13:00 | 35.60 | 27.28 |
October | 0.714091E+10 | 11896.43 | 07-OCT-05:02 | 26.17 | 26.04 | 0.624128E+09 | 845.63 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.416228E+10 | 11002.68 | 02-NOV-05:02 | 23.38 | 22.55 | 0.561760E+09 | 845.59 | 08-NOV-14:00 | 22.70 | 16.46 |
December | 0.287829E+10 | 5692.43 | 15-DEC-15:00 | 29.00 | 21.56 | 0.504551E+09 | 845.59 | 11-DEC-14:39 | 29.00 | 21.56 |
Annual Sum or Average | 0.767932E+11 | 0.711609E+10 | ||||||||
Minimum of Months | 0.228940E+10 | 4399.37 | 20.92 | 20.25 | 0.488621E+09 | 845.58 | 20.92 | 15.50 | ||
Maximum of Months | 0.103521E+11 | 15398.21 | 35.60 | 27.28 | 0.690695E+09 | 845.63 | 35.60 | 27.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248472E+10 | 5351.09 | 19-JAN-10:30 | 23.85 | 21.17 | 0.342820E+09 | 544.93 | 02-JAN-14:39 | 23.85 | 21.17 |
February | 0.281926E+10 | 5816.94 | 27-FEB-10:30 | 21.90 | 19.28 | 0.332449E+09 | 544.93 | 08-FEB-10:00 | 21.90 | 19.28 |
March | 0.394630E+10 | 8838.24 | 27-MAR-05:02 | 19.82 | 18.59 | 0.408941E+09 | 544.95 | 23-MAR-09:50 | 19.82 | 18.59 |
April | 0.552103E+10 | 16072.78 | 23-APR-11:02 | 26.70 | 20.26 | 0.388242E+09 | 544.97 | 10-APR-13:00 | 26.70 | 20.26 |
May | 0.841484E+10 | 17053.15 | 29-MAY-10:42 | 29.82 | 23.25 | 0.428455E+09 | 544.93 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.889359E+10 | 16293.50 | 11-JUN-08:53 | 27.80 | 20.73 | 0.427214E+09 | 544.94 | 01-JUN-13:09 | 27.80 | 20.73 |
July | 0.879319E+10 | 16360.45 | 16-JUL-08:32 | 28.53 | 23.97 | 0.397411E+09 | 544.93 | 12-JUL-13:09 | 28.53 | 23.97 |
August | 0.854008E+10 | 16198.98 | 27-AUG-10:23 | 30.00 | 24.51 | 0.445296E+09 | 544.94 | 25-AUG-13:09 | 30.00 | 24.51 |
September | 0.679547E+10 | 17013.45 | 03-SEP-09:42 | 29.98 | 24.61 | 0.394403E+09 | 544.94 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.641667E+10 | 16224.40 | 09-OCT-09:23 | 28.05 | 22.46 | 0.405556E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.375448E+10 | 8041.49 | 01-NOV-05:02 | 22.62 | 22.36 | 0.382715E+09 | 544.95 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.259267E+10 | 4437.97 | 16-DEC-10:10 | 24.33 | 21.30 | 0.337572E+09 | 544.94 | 01-DEC-10:00 | 24.33 | 21.30 |
Annual Sum or Average | 0.689723E+11 | 0.469108E+10 | ||||||||
Minimum of Months | 0.248472E+10 | 4437.97 | 19.82 | 18.59 | 0.332449E+09 | 544.93 | 19.82 | 15.14 | ||
Maximum of Months | 0.889359E+10 | 17053.15 | 30.00 | 24.61 | 0.445296E+09 | 544.97 | 30.00 | 24.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.606290E+10 | 21147.29 | 01-JAN-14:12 | 25.67 | 18.12 | 0.596749E+09 | 868.19 | 19-JAN-14:50 | 25.00 | 21.54 |
February | 0.623951E+10 | 19418.74 | 26-FEB-14:43 | 26.18 | 20.05 | 0.546739E+09 | 861.56 | 27-FEB-14:39 | 25.90 | 20.26 |
March | 0.615332E+10 | 13941.69 | 27-MAR-05:02 | 19.82 | 18.59 | 0.637999E+09 | 845.63 | 03-MAR-14:00 | 19.82 | 18.59 |
April | 0.698057E+10 | 12994.91 | 27-APR-05:02 | 20.92 | 20.25 | 0.595809E+09 | 845.66 | 10-APR-13:00 | 20.92 | 20.25 |
May | 0.967522E+10 | 15235.59 | 22-MAY-03:02 | 26.10 | 22.50 | 0.664001E+09 | 845.61 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.999379E+10 | 14622.82 | 28-JUN-03:02 | 27.20 | 25.10 | 0.662080E+09 | 845.62 | 01-JUN-13:09 | 27.20 | 25.10 |
July | 0.101597E+11 | 18069.91 | 23-JUL-14:22 | 32.50 | 25.44 | 0.615917E+09 | 845.61 | 11-JUL-13:09 | 32.50 | 25.44 |
August | 0.112163E+11 | 18282.07 | 27-AUG-14:23 | 33.00 | 23.46 | 0.691290E+09 | 845.62 | 25-AUG-13:09 | 33.00 | 23.46 |
September | 0.100975E+11 | 20007.72 | 10-SEP-14:52 | 35.60 | 27.28 | 0.613332E+09 | 845.62 | 07-SEP-13:00 | 35.60 | 27.28 |
October | 0.118522E+11 | 20048.82 | 08-OCT-12:12 | 31.33 | 25.87 | 0.635790E+09 | 869.93 | 13-OCT-13:00 | 33.00 | 23.24 |
November | 0.878670E+10 | 20748.64 | 11-NOV-14:12 | 26.27 | 22.90 | 0.618979E+09 | 896.71 | 06-NOV-14:20 | 26.27 | 22.90 |
December | 0.715582E+10 | 21032.54 | 10-DEC-14:22 | 27.50 | 20.13 | 0.574300E+09 | 865.09 | 15-DEC-14:50 | 29.00 | 21.65 |
Annual Sum or Average | 0.104373E+12 | 0.745299E+10 | ||||||||
Minimum of Months | 0.606290E+10 | 12994.91 | 19.82 | 18.12 | 0.546739E+09 | 845.61 | 19.82 | 18.59 | ||
Maximum of Months | 0.118522E+11 | 21147.29 | 35.60 | 27.28 | 0.691290E+09 | 896.71 | 35.60 | 27.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292575E+10 | 10097.47 | 01-JAN-16:12 | 24.67 | 18.84 | 0.345233E+09 | 544.93 | 02-JAN-14:39 | 26.67 | 18.58 |
February | 0.339202E+10 | 17831.90 | 26-FEB-17:22 | 23.85 | 19.57 | 0.327954E+09 | 544.93 | 28-FEB-14:50 | 25.00 | 20.38 |
March | 0.433041E+10 | 13117.07 | 27-MAR-05:02 | 19.82 | 18.59 | 0.395391E+09 | 544.93 | 27-MAR-13:09 | 26.78 | 20.95 |
April | 0.605566E+10 | 18107.17 | 23-APR-18:22 | 24.40 | 20.99 | 0.382656E+09 | 544.96 | 10-APR-13:00 | 24.40 | 20.99 |
May | 0.821220E+10 | 18614.29 | 28-MAY-18:02 | 29.32 | 24.32 | 0.428026E+09 | 544.93 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.893042E+10 | 18260.81 | 11-JUN-16:52 | 33.30 | 21.96 | 0.427142E+09 | 544.93 | 01-JUN-13:09 | 33.30 | 21.96 |
July | 0.871008E+10 | 18918.36 | 16-JUL-16:32 | 30.17 | 24.94 | 0.397306E+09 | 544.93 | 11-JUL-13:09 | 30.17 | 24.94 |
August | 0.906131E+10 | 17637.21 | 20-AUG-17:12 | 30.33 | 24.28 | 0.445735E+09 | 544.93 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.722704E+10 | 19456.13 | 03-SEP-15:42 | 32.28 | 24.61 | 0.393933E+09 | 544.94 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.700254E+10 | 17846.73 | 08-OCT-15:32 | 31.00 | 25.40 | 0.404729E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.439969E+10 | 14175.15 | 11-NOV-15:32 | 26.27 | 22.90 | 0.373946E+09 | 544.95 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.342800E+10 | 10072.51 | 16-DEC-06:03 | 20.83 | 19.18 | 0.340185E+09 | 544.94 | 01-DEC-14:00 | 20.83 | 19.18 |
Annual Sum or Average | 0.736751E+11 | 0.466224E+10 | ||||||||
Minimum of Months | 0.292575E+10 | 10072.51 | 19.82 | 18.59 | 0.327954E+09 | 544.93 | 20.83 | 15.14 | ||
Maximum of Months | 0.906131E+10 | 19456.13 | 33.30 | 25.40 | 0.445735E+09 | 544.96 | 33.30 | 24.94 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.344402E+10 | 9123.69 | 02-JAN-06:15 | 16.00 | 15.39 | 0.00 | 0.00 | 01-JAN-00:10 | 16.00 | 15.39 |
February | 0.363851E+10 | 5597.63 | 27-FEB-15:40 | 25.70 | 20.50 | 0.00 | 0.00 | 01-FEB-00:10 | 25.70 | 20.50 |
March | 0.469726E+10 | 5665.60 | 20-MAR-05:03 | 12.10 | 7.78 | 0.00 | 0.00 | 01-MAR-00:10 | 12.10 | 7.78 |
April | 0.603519E+10 | 5663.22 | 28-APR-16:00 | 32.20 | 25.55 | 0.00 | 0.00 | 01-APR-00:10 | 32.20 | 25.55 |
May | 0.747339E+10 | 6781.63 | 06-MAY-05:03 | 24.40 | 21.68 | 0.00 | 0.00 | 01-MAY-00:10 | 24.40 | 21.68 |
June | 0.811065E+10 | 6222.78 | 12-JUN-16:00 | 33.30 | 21.04 | 0.00 | 0.00 | 01-JUN-00:10 | 33.30 | 21.04 |
July | 0.864351E+10 | 7782.23 | 18-JUL-05:03 | 24.32 | 22.84 | 0.00 | 0.00 | 01-JUL-00:10 | 24.32 | 22.84 |
August | 0.928530E+10 | 8805.89 | 21-AUG-05:03 | 26.00 | 23.88 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 23.88 |
September | 0.715802E+10 | 9008.33 | 25-SEP-05:03 | 23.38 | 22.59 | 0.00 | 0.00 | 01-SEP-00:10 | 23.38 | 22.59 |
October | 0.753575E+10 | 7868.42 | 10-OCT-05:15 | 21.97 | 20.04 | 0.00 | 0.00 | 01-OCT-00:10 | 21.97 | 20.04 |
November | 0.556380E+10 | 7269.09 | 13-NOV-06:13 | 9.60 | 8.03 | 0.00 | 0.00 | 01-NOV-00:10 | 9.60 | 8.03 |
December | 0.460390E+10 | 6873.35 | 26-DEC-06:13 | 5.90 | 2.19 | 0.00 | 0.00 | 01-DEC-00:10 | 5.90 | 2.19 |
Annual Sum or Average | 0.761893E+11 | 0.00 | ||||||||
Minimum of Months | 0.344402E+10 | 5597.63 | 5.90 | 2.19 | 0.00 | 0.00 | 5.90 | 2.19 | ||
Maximum of Months | 0.928530E+10 | 9123.69 | 33.30 | 25.55 | 0.00 | 0.00 | 33.30 | 25.55 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196162E+10 | 4659.35 | 03-JAN-06:10 | 2.83 | 0.47 | 0.00 | 0.00 | 01-JAN-00:10 | 2.83 | 0.47 |
February | 0.210403E+10 | 4360.03 | 06-FEB-06:02 | 2.88 | 0.92 | 0.00 | 0.00 | 01-FEB-00:10 | 2.88 | 0.92 |
March | 0.284072E+10 | 4209.89 | 28-MAR-05:10 | 19.05 | 18.47 | 0.00 | 0.00 | 01-MAR-00:10 | 19.05 | 18.47 |
April | 0.394358E+10 | 4540.78 | 28-APR-16:00 | 32.20 | 25.55 | 0.00 | 0.00 | 01-APR-00:10 | 32.20 | 25.55 |
May | 0.623108E+10 | 6761.25 | 06-MAY-05:03 | 24.40 | 21.68 | 0.00 | 0.00 | 01-MAY-00:10 | 24.40 | 21.68 |
June | 0.649377E+10 | 7613.32 | 23-JUN-05:02 | 25.60 | 23.86 | 0.00 | 0.00 | 01-JUN-00:10 | 25.60 | 23.86 |
July | 0.660786E+10 | 6675.34 | 25-JUL-05:02 | 24.50 | 23.30 | 0.00 | 0.00 | 01-JUL-00:10 | 24.50 | 23.30 |
August | 0.674030E+10 | 6607.73 | 18-AUG-05:02 | 23.90 | 23.26 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 23.26 |
September | 0.569740E+10 | 5691.80 | 13-SEP-05:03 | 23.22 | 21.59 | 0.00 | 0.00 | 01-SEP-00:10 | 23.22 | 21.59 |
October | 0.565578E+10 | 7132.44 | 13-OCT-05:02 | 23.00 | 21.02 | 0.00 | 0.00 | 01-OCT-00:10 | 23.00 | 21.02 |
November | 0.338485E+10 | 4410.80 | 09-NOV-06:10 | 10.42 | 5.53 | 0.00 | 0.00 | 01-NOV-00:10 | 10.42 | 5.53 |
December | 0.263455E+10 | 4959.70 | 21-DEC-06:01 | 0.83 | 0.01 | 0.00 | 0.00 | 01-DEC-00:10 | 0.83 | 0.01 |
Annual Sum or Average | 0.542955E+11 | 0.00 | ||||||||
Minimum of Months | 0.196162E+10 | 4209.89 | 0.83 | 0.01 | 0.00 | 0.00 | 0.83 | 0.01 | ||
Maximum of Months | 0.674030E+10 | 7613.32 | 32.20 | 25.55 | 0.00 | 0.00 | 32.20 | 25.55 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203303E+10 | 8359.51 | 19-JAN-15:00 | 25.00 | 21.54 | 0.00 | 0.00 | 01-JAN-00:10 | 25.00 | 21.54 |
February | 0.290260E+10 | 10007.26 | 27-FEB-15:20 | 25.90 | 20.46 | 0.00 | 0.00 | 01-FEB-00:10 | 25.90 | 20.46 |
March | 0.405006E+10 | 10189.35 | 06-MAR-14:50 | 26.18 | 21.15 | 0.00 | 0.00 | 01-MAR-00:10 | 26.18 | 21.15 |
April | 0.690720E+10 | 15124.74 | 28-APR-15:00 | 33.30 | 23.06 | 0.00 | 0.00 | 01-APR-00:10 | 33.30 | 23.06 |
May | 0.114829E+11 | 16201.75 | 10-MAY-14:50 | 32.80 | 23.14 | 0.00 | 0.00 | 01-MAY-00:10 | 32.80 | 23.14 |
June | 0.127495E+11 | 17189.81 | 28-JUN-14:30 | 33.60 | 26.19 | 0.00 | 0.00 | 01-JUN-00:10 | 33.60 | 26.19 |
July | 0.123417E+11 | 17371.23 | 07-JUL-14:50 | 34.82 | 23.96 | 0.00 | 0.00 | 01-JUL-00:10 | 34.82 | 23.96 |
August | 0.123022E+11 | 16420.89 | 03-AUG-15:00 | 35.00 | 24.85 | 0.00 | 0.00 | 01-AUG-00:10 | 35.00 | 24.85 |
September | 0.941256E+10 | 15263.81 | 01-SEP-14:00 | 32.20 | 22.62 | 0.00 | 0.00 | 01-SEP-00:10 | 32.20 | 22.62 |
October | 0.892597E+10 | 15121.61 | 05-OCT-15:20 | 33.33 | 23.87 | 0.00 | 0.00 | 01-OCT-00:10 | 33.33 | 23.87 |
November | 0.416102E+10 | 11847.76 | 02-NOV-14:00 | 29.40 | 24.47 | 0.00 | 0.00 | 01-NOV-00:10 | 29.40 | 24.47 |
December | 0.265501E+10 | 9922.92 | 15-DEC-15:00 | 29.00 | 21.56 | 0.00 | 0.00 | 01-DEC-00:10 | 29.00 | 21.56 |
Annual Sum or Average | 0.899237E+11 | 0.00 | ||||||||
Minimum of Months | 0.203303E+10 | 8359.51 | 25.00 | 20.46 | 0.00 | 0.00 | 25.00 | 20.46 | ||
Maximum of Months | 0.127495E+11 | 17371.23 | 35.00 | 26.19 | 0.00 | 0.00 | 35.00 | 26.19 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.379658E+10 | 2009.47 | 01-JAN-17:03 | 23.33 | 19.19 | 95231924.64 | 126.85 | 02-JAN-10:00 | 24.00 | 19.35 |
February | 0.824003E+10 | 4039.02 | 26-FEB-17:50 | 23.48 | 19.39 | 86406197.58 | 126.85 | 24-FEB-14:00 | 23.48 | 19.39 |
March | 0.143005E+11 | 7170.92 | 31-MAR-24:00 | 20.70 | 19.78 | 0.103243E+09 | 126.85 | 07-MAR-14:00 | 20.70 | 19.78 |
April | 0.188361E+11 | 7829.21 | 16-APR-18:20 | 18.07 | 13.19 | 91609734.42 | 126.83 | 14-APR-09:09 | 18.07 | 13.19 |
May | 0.447038E+10 | 3460.71 | 31-MAY-24:00 | 23.00 | 21.40 | 99234996.68 | 126.85 | 08-MAY-13:00 | 23.00 | 21.40 |
June | 0.921271E+10 | 5329.36 | 30-JUN-23:57 | 25.10 | 23.16 | 98983001.64 | 126.87 | 27-JUN-13:09 | 25.10 | 23.16 |
July | 0.145720E+11 | 7187.81 | 31-JUL-23:53 | 25.20 | 23.65 | 91896857.74 | 126.85 | 14-JUL-13:00 | 25.20 | 23.65 |
August | 0.195994E+11 | 7613.92 | 06-AUG-17:50 | 25.17 | 23.64 | 0.103375E+09 | 129.34 | 28-AUG-13:00 | 33.00 | 25.67 |
September | 0.435146E+10 | 3480.98 | 30-SEP-24:00 | 22.30 | 21.22 | 91605633.79 | 126.82 | 05-SEP-13:30 | 22.30 | 21.22 |
October | 0.955041E+10 | 5343.13 | 31-OCT-24:00 | 21.60 | 20.90 | 95250011.87 | 126.87 | 25-OCT-13:20 | 21.60 | 20.90 |
November | 0.140095E+11 | 5854.63 | 06-NOV-17:00 | 26.60 | 19.72 | 94308222.88 | 126.85 | 01-NOV-09:00 | 26.60 | 19.72 |
December | 0.193861E+11 | 7731.29 | 10-DEC-16:55 | 25.00 | 19.63 | 91882872.14 | 126.83 | 28-DEC-10:09 | 18.33 | 18.33 |
Annual Sum or Average | 0.140325E+12 | 0.114303E+10 | ||||||||
Minimum of Months | 0.379658E+10 | 2009.47 | 18.07 | 13.19 | 86406197.58 | 126.82 | 18.07 | 13.19 | ||
Maximum of Months | 0.195994E+11 | 7829.21 | 26.60 | 23.65 | 0.103375E+09 | 129.34 | 33.00 | 25.67 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233830E+10 | 1748.02 | 19-JAN-17:00 | 24.00 | 20.62 | 95231042.33 | 126.84 | 02-JAN-14:09 | 24.00 | 20.62 |
February | 0.687047E+10 | 3619.72 | 26-FEB-17:54 | 23.30 | 19.29 | 86405551.85 | 126.85 | 24-FEB-10:20 | 23.30 | 19.29 |
March | 0.128244E+11 | 6669.80 | 31-MAR-24:00 | 20.70 | 19.78 | 0.103242E+09 | 126.84 | 07-MAR-14:00 | 20.70 | 19.78 |
April | 0.177645E+11 | 7350.88 | 16-APR-18:06 | 18.43 | 13.27 | 91611674.40 | 126.83 | 24-APR-09:09 | 20.45 | 20.45 |
May | 0.405177E+10 | 3218.38 | 31-MAY-24:00 | 23.00 | 21.40 | 99233579.45 | 126.82 | 26-MAY-13:09 | 23.00 | 21.40 |
June | 0.868116E+10 | 5155.39 | 30-JUN-23:57 | 25.10 | 23.16 | 98981455.16 | 126.86 | 19-JUN-09:09 | 25.10 | 23.16 |
July | 0.138258E+11 | 6879.26 | 31-JUL-23:53 | 25.20 | 23.65 | 91895927.46 | 126.85 | 14-JUL-13:00 | 25.20 | 23.65 |
August | 0.186745E+11 | 7194.57 | 29-AUG-16:00 | 31.10 | 23.86 | 0.103461E+09 | 129.89 | 28-AUG-13:00 | 31.10 | 23.86 |
September | 0.384378E+10 | 3191.99 | 30-SEP-24:00 | 22.30 | 21.22 | 91605370.43 | 126.82 | 05-SEP-13:30 | 22.30 | 21.22 |
October | 0.880411E+10 | 4920.07 | 31-OCT-24:00 | 21.60 | 20.90 | 95248755.41 | 126.87 | 24-OCT-09:20 | 21.60 | 20.90 |
November | 0.126828E+11 | 5538.52 | 06-NOV-17:00 | 26.60 | 19.72 | 94307552.42 | 126.85 | 01-NOV-09:00 | 26.60 | 19.72 |
December | 0.174544E+11 | 7274.10 | 15-DEC-17:00 | 28.00 | 21.24 | 91882894.97 | 126.83 | 28-DEC-14:00 | 20.00 | 20.00 |
Annual Sum or Average | 0.127816E+12 | 0.114311E+10 | ||||||||
Minimum of Months | 0.233830E+10 | 1748.02 | 18.43 | 13.27 | 86405551.85 | 126.82 | 20.00 | 19.29 | ||
Maximum of Months | 0.186745E+11 | 7350.88 | 31.10 | 23.86 | 0.103461E+09 | 129.89 | 31.10 | 23.86 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140343E+10 | 1815.75 | 19-JAN-17:00 | 24.00 | 20.62 | 95016880.30 | 127.20 | 09-JAN-10:09 | 24.00 | 20.62 |
February | 0.604062E+10 | 3665.94 | 27-FEB-17:40 | 23.27 | 19.63 | 86405681.63 | 126.85 | 24-FEB-14:00 | 23.27 | 19.63 |
March | 0.121992E+11 | 6560.21 | 31-MAR-24:00 | 20.70 | 19.78 | 0.103243E+09 | 126.85 | 07-MAR-14:00 | 20.70 | 19.78 |
April | 0.176079E+11 | 7461.95 | 23-APR-18:05 | 25.13 | 21.19 | 91609923.40 | 126.83 | 24-APR-09:09 | 20.45 | 20.45 |
May | 0.419472E+10 | 3201.24 | 31-MAY-24:00 | 23.00 | 21.40 | 99234752.10 | 126.85 | 08-MAY-13:00 | 23.00 | 21.40 |
June | 0.883644E+10 | 5207.71 | 30-JUN-23:57 | 25.10 | 23.16 | 98982935.08 | 126.87 | 01-JUN-13:09 | 25.10 | 23.16 |
July | 0.139768E+11 | 6868.87 | 31-JUL-23:53 | 25.20 | 23.65 | 91897032.46 | 126.85 | 12-JUL-13:20 | 25.20 | 23.65 |
August | 0.187997E+11 | 7375.98 | 06-AUG-17:40 | 25.33 | 23.69 | 0.103340E+09 | 128.54 | 28-AUG-13:00 | 33.00 | 25.67 |
September | 0.394963E+10 | 3222.88 | 30-SEP-24:00 | 22.30 | 21.22 | 91605386.02 | 126.82 | 05-SEP-13:30 | 22.30 | 21.22 |
October | 0.874067E+10 | 4845.83 | 31-OCT-24:00 | 21.60 | 20.90 | 95249467.37 | 126.87 | 06-OCT-13:00 | 21.60 | 20.90 |
November | 0.120748E+11 | 5598.98 | 06-NOV-17:00 | 26.60 | 19.72 | 94307871.26 | 126.85 | 07-NOV-14:00 | 27.70 | 24.03 |
December | 0.165262E+11 | 7340.65 | 15-DEC-17:00 | 28.00 | 21.24 | 91883283.37 | 126.83 | 28-DEC-14:00 | 20.00 | 20.00 |
Annual Sum or Average | 0.124350E+12 | 0.114278E+10 | ||||||||
Minimum of Months | 0.140343E+10 | 1815.75 | 20.70 | 19.63 | 86405681.63 | 126.82 | 20.00 | 19.63 | ||
Maximum of Months | 0.187997E+11 | 7461.95 | 28.00 | 23.69 | 0.103340E+09 | 128.54 | 33.00 | 25.67 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239534E+12 | 92474.00 | 02-JAN-15:00 | 27.00 | 18.67 | 0.206144E+10 | 2745.29 | 03-JAN-10:30 | 9.00 | 4.28 |
February | 0.435841E+12 | 182993.35 | 27-FEB-17:00 | 24.40 | 20.28 | 0.187022E+10 | 2745.29 | 02-FEB-14:30 | 24.40 | 20.28 |
March | 0.727453E+12 | 358199.25 | 31-MAR-24:00 | 20.70 | 19.78 | 0.223475E+10 | 2745.29 | 28-MAR-13:00 | 20.70 | 19.78 |
April | 0.940116E+12 | 365498.39 | 28-APR-16:00 | 32.20 | 25.55 | 0.198297E+10 | 2745.29 | 07-APR-09:00 | 32.20 | 25.55 |
May | 0.239669E+12 | 175334.95 | 31-MAY-24:00 | 23.00 | 21.40 | 0.214810E+10 | 2745.29 | 04-MAY-09:20 | 23.00 | 21.40 |
June | 0.468058E+12 | 266978.84 | 30-JUN-23:53 | 25.10 | 23.16 | 0.214213E+10 | 2745.29 | 01-JUN-13:00 | 25.10 | 23.16 |
July | 0.730139E+12 | 359207.51 | 31-JUL-24:00 | 25.20 | 23.65 | 0.198894E+10 | 2745.29 | 07-JUL-09:39 | 25.20 | 23.65 |
August | 0.977148E+12 | 367527.12 | 21-AUG-16:00 | 34.00 | 23.39 | 0.223475E+10 | 2745.29 | 21-AUG-09:30 | 34.00 | 23.39 |
September | 0.235625E+12 | 176337.73 | 30-SEP-24:00 | 22.30 | 21.22 | 0.198297E+10 | 2745.29 | 01-SEP-09:09 | 22.30 | 21.22 |
October | 0.487473E+12 | 268335.65 | 31-OCT-24:00 | 21.60 | 20.90 | 0.206144E+10 | 2745.29 | 06-OCT-09:50 | 21.60 | 20.90 |
November | 0.708489E+12 | 275847.86 | 06-NOV-17:00 | 26.60 | 19.72 | 0.204131E+10 | 2745.29 | 10-NOV-14:00 | 27.70 | 19.95 |
December | 0.976687E+12 | 367387.09 | 26-DEC-17:00 | 12.70 | 5.60 | 0.198894E+10 | 2745.29 | 05-DEC-10:09 | 12.70 | 5.60 |
Annual Sum or Average | 0.716623E+13 | 0.247380E+11 | ||||||||
Minimum of Months | 0.235625E+12 | 92474.00 | 12.70 | 5.60 | 0.187022E+10 | 2745.29 | 9.00 | 4.28 | ||
Maximum of Months | 0.977148E+12 | 367527.12 | 34.00 | 25.55 | 0.223475E+10 | 2745.29 | 34.00 | 25.55 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.361047E+09 | 10330.07 | 03-JAN-04:05 | 5.67 |
February | 0.263236E+09 | 12157.38 | 22-FEB-04:53 | 17.70 |
March | 0.223972E+09 | 11400.19 | 17-MAR-03:53 | 15.80 |
April | 0.279828E+09 | 13504.74 | 22-APR-15:02 | 30.42 |
May | 0.394224E+09 | 15537.42 | 27-MAY-15:02 | 32.30 |
June | 0.442339E+09 | 16573.23 | 10-JUN-15:02 | 33.40 |
July | 0.465126E+09 | 18671.94 | 22-JUL-16:13 | 35.73 |
August | 0.444508E+09 | 16309.95 | 19-AUG-15:02 | 33.30 |
September | 0.547460E+09 | 18735.73 | 09-SEP-16:13 | 35.87 |
October | 0.560617E+09 | 14938.78 | 07-OCT-15:02 | 31.95 |
November | 0.562710E+09 | 12048.50 | 30-NOV-04:53 | 16.10 |
December | 0.640316E+09 | 12184.55 | 25-DEC-12:13 | 15.67 |
Annual Sum or Average | 0.518538E+10 | |||
Minimum of Months | 0.223972E+09 | 10330.07 | 5.67 | |
Maximum of Months | 0.640316E+09 | 18735.73 | 35.87 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164599E+09 | 45630.22 | 05-JAN-06:02 | 0.17 |
February | 0.265033E+09 | 51777.23 | 06-FEB-05:01 | 3.03 |
March | 44420930.65 | 44343.93 | 13-MAR-05:03 | 6.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 76005933.19 | 47180.24 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.550059E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.265033E+09 | 51777.23 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124557E+09 | 9443.92 | 10-JAN-05:01 | 1.33 |
February | 68610330.82 | 9676.93 | 06-FEB-05:01 | 3.03 |
March | 25120174.05 | 8799.97 | 13-MAR-05:03 | 6.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 38141.44 | 317.85 | 16-NOV-06:06 | 9.40 |
December | 67125045.22 | 9527.03 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.285451E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.124557E+09 | 9676.93 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42193610.43 | 7216.15 | 05-JAN-06:02 | 0.17 |
February | 21498264.00 | 7274.35 | 06-FEB-05:01 | 3.03 |
March | 9479659.01 | 6239.99 | 11-MAR-06:02 | 6.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 4338.18 | 36.15 | 16-NOV-06:08 | 9.40 |
December | 35186255.58 | 7340.77 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.108362E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 42193610.43 | 7340.77 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6214716.23 | 9699.56 | 10-JAN-06:02 | 3.00 |
February | 4099173.34 | 9730.65 | 06-FEB-06:02 | 2.88 |
March | 1509163.61 | 3372.12 | 11-MAR-06:02 | 6.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 16491230.27 | 9843.70 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 28314283.45 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 16491230.27 | 9843.70 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11491013.52 | 6082.97 | 10-JAN-06:02 | 3.00 |
February | 6375652.09 | 6074.75 | 06-FEB-06:02 | 2.88 |
March | 7080.38 | 59.00 | 11-MAR-06:02 | 6.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 10403510.00 | 6167.87 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 28277255.99 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 11491013.52 | 6167.87 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104291E+10 | 12059.87 | 23-JAN-05:01 | 7.83 |
February | 0.541141E+09 | 13081.37 | 06-FEB-04:01 | 3.35 |
March | 0.347130E+09 | 11664.98 | 13-MAR-04:01 | 7.05 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 63753953.39 | 10798.59 | 16-NOV-06:02 | 9.40 |
December | 0.638833E+09 | 11794.53 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.263377E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.104291E+10 | 13081.37 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.398745E+09 | 10338.29 | 05-JAN-05:01 | 0.83 |
February | 0.192581E+09 | 11396.80 | 06-FEB-04:01 | 3.35 |
March | 0.166519E+09 | 9730.31 | 10-MAR-05:02 | 5.83 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 33004.48 | 220.03 | 28-OCT-05:08 | 10.00 |
November | 13547633.50 | 8872.01 | 16-NOV-06:02 | 9.40 |
December | 0.301392E+09 | 10306.70 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.107282E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.398745E+09 | 11396.80 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288714E+09 | 13725.13 | 10-JAN-05:01 | 1.33 |
February | 0.161670E+09 | 14349.41 | 06-FEB-04:01 | 3.35 |
March | 0.184284E+09 | 13002.78 | 10-MAR-05:02 | 5.83 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 2789171.13 | 7896.41 | 16-NOV-06:02 | 9.40 |
December | 0.212777E+09 | 14027.04 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.850233E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.288714E+09 | 14349.41 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272288E+09 | 9935.06 | 10-JAN-05:01 | 1.33 |
February | 0.129418E+09 | 10394.10 | 06-FEB-04:01 | 3.35 |
March | 77051113.47 | 8472.13 | 10-MAR-06:03 | 5.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 4097751.01 | 7701.20 | 16-NOV-06:02 | 9.40 |
December | 0.142728E+09 | 10068.08 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.625582E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.272288E+09 | 10394.10 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 54159135.57 | 8113.79 | 09-JAN-05:02 | 7.83 |
February | 51877162.18 | 8772.67 | 06-FEB-05:01 | 3.03 |
March | 61434492.43 | 9507.36 | 13-MAR-04:01 | 7.05 |
April | 64881839.64 | 8516.32 | 10-APR-03:02 | 13.30 |
May | 32420272.19 | 5753.71 | 02-MAY-03:02 | 24.13 |
June | 27644341.06 | 5140.17 | 07-JUN-03:02 | 21.10 |
July | 25555428.78 | 3086.47 | 23-JUL-13:53 | 33.30 |
August | 16605607.09 | 3073.85 | 06-AUG-15:22 | 28.00 |
September | 30884028.59 | 6485.47 | 29-SEP-03:02 | 23.80 |
October | 50108256.32 | 8274.00 | 30-OCT-03:02 | 17.00 |
November | 66525410.22 | 8645.10 | 27-NOV-04:02 | 14.30 |
December | 0.100128E+09 | 9476.30 | 22-DEC-05:02 | 8.33 |
Annual Sum or Average | 0.582224E+09 | |||
Minimum of Months | 16605607.09 | 3073.85 | 3.03 | |
Maximum of Months | 0.100128E+09 | 9507.36 | 33.30 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144783E+09 | 4709.39 | 31-JAN-06:02 | 18.17 |
February | 92375176.96 | 4985.19 | 20-FEB-13:38 | 23.47 |
March | 72929458.47 | 5085.99 | 06-MAR-06:02 | 18.80 |
April | 21013630.67 | 4501.49 | 10-APR-05:02 | 12.20 |
May | 19240210.38 | 6753.66 | 22-MAY-03:02 | 26.10 |
June | 15174729.34 | 4367.45 | 15-JUN-03:02 | 26.52 |
July | 18722494.53 | 5005.50 | 20-JUL-03:02 | 26.70 |
August | 16835741.71 | 4972.39 | 03-AUG-03:02 | 25.95 |
September | 23305544.06 | 4053.18 | 25-SEP-03:02 | 23.80 |
October | 26728163.63 | 5025.70 | 06-OCT-03:02 | 26.67 |
November | 30198493.28 | 5026.45 | 29-NOV-06:02 | 21.60 |
December | 70804652.17 | 4731.97 | 25-DEC-11:08 | 14.17 |
Annual Sum or Average | 0.552111E+09 | |||
Minimum of Months | 15174729.34 | 4053.18 | 12.20 | |
Maximum of Months | 0.144783E+09 | 6753.66 | 26.70 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168845E+10 | 12178.56 | 10-JAN-06:03 | 3.00 |
February | 0.921240E+09 | 16751.91 | 06-FEB-06:13 | 3.07 |
March | 0.858237E+09 | 13056.01 | 20-MAR-05:03 | 12.10 |
April | 0.154964E+09 | 13259.44 | 17-APR-05:02 | 12.70 |
May | 29603992.36 | 5201.01 | 08-MAY-03:02 | 24.40 |
June | 23800259.93 | 6552.16 | 07-JUN-04:03 | 21.10 |
July | 20574917.61 | 5592.27 | 10-JUL-03:02 | 25.60 |
August | 20779384.86 | 5729.34 | 01-AUG-04:03 | 23.90 |
September | 24623140.59 | 7863.53 | 08-SEP-05:02 | 24.58 |
October | 81223497.21 | 10244.10 | 27-OCT-05:03 | 15.00 |
November | 0.328086E+09 | 8597.57 | 30-NOV-06:03 | 15.08 |
December | 0.123589E+10 | 12436.09 | 21-DEC-06:03 | 0.83 |
Annual Sum or Average | 0.538748E+10 | |||
Minimum of Months | 20574917.61 | 5201.01 | 0.83 | |
Maximum of Months | 0.168845E+10 | 16751.91 | 25.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165561E+09 | 525.60 | 10-JAN-04:45 | 1.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.165561E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.17 | |
Maximum of Months | 0.165561E+09 | 525.60 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113123E+11 | 11837.83 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.102611E+11 | 11837.83 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.121930E+11 | 11837.83 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.108909E+11 | 11837.83 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.117527E+11 | 11837.83 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.116958E+11 | 11837.83 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.109477E+11 | 11837.83 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.121930E+11 | 11837.83 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.108909E+11 | 11837.83 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.113123E+11 | 11837.83 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.111797E+11 | 11837.83 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.109477E+11 | 11837.83 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.135577E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.102611E+11 | 11837.83 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.121930E+11 | 11837.83 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.811160E+09 | 1135.02 | 31-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.702011E+09 | 1167.25 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.803448E+09 | 1091.46 | 27-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.694308E+09 | 1115.86 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.723357E+09 | 883.46 | 23-MAY-07:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.709831E+09 | 689.07 | 27-JUN-11:30 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.672503E+09 | 736.83 | 14-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.760486E+09 | 911.01 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.704043E+09 | 1088.83 | 26-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.752426E+09 | 1214.09 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.795053E+09 | 1174.17 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.801756E+09 | 1205.45 | 12-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.893038E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.672503E+09 | 689.07 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.811160E+09 | 1214.09 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.507326E+09 | 704.89 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.444013E+09 | 729.41 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.509095E+09 | 661.70 | 27-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.446198E+09 | 696.02 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.469860E+09 | 560.96 | 30-MAY-15:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.462571E+09 | 445.37 | 27-JUN-13:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.436938E+09 | 451.48 | 14-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.491107E+09 | 472.79 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.451440E+09 | 658.09 | 26-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.479627E+09 | 767.38 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.500294E+09 | 764.09 | 21-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.503926E+09 | 767.68 | 12-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.570240E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.436938E+09 | 445.37 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.509095E+09 | 767.68 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.753915E+09 | 1106.32 | 31-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.670839E+09 | 1149.29 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.786625E+09 | 1081.67 | 27-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.695940E+09 | 1119.68 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.732927E+09 | 914.74 | 23-MAY-07:19 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.720760E+09 | 719.77 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.680495E+09 | 857.85 | 14-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.764630E+09 | 946.49 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.699387E+09 | 1085.88 | 26-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.737534E+09 | 1206.62 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.746421E+09 | 1144.87 | 21-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.747149E+09 | 1194.94 | 12-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.873662E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.670839E+09 | 719.77 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.786625E+09 | 1206.62 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.502986E+09 | 741.01 | 31-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.443326E+09 | 758.17 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.517170E+09 | 726.59 | 27-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.451774E+09 | 734.93 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.473215E+09 | 637.06 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.464361E+09 | 561.45 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.439551E+09 | 603.04 | 14-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.496294E+09 | 681.58 | 23-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.458088E+09 | 727.14 | 26-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.483275E+09 | 788.54 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.492988E+09 | 771.05 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.493842E+09 | 778.02 | 12-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.571687E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.439551E+09 | 561.45 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.517170E+09 | 788.54 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.811064E+09 | 1139.16 | 31-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.702087E+09 | 1170.75 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.803282E+09 | 1096.78 | 27-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.694254E+09 | 1120.56 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.723821E+09 | 892.90 | 23-MAY-07:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.709056E+09 | 684.55 | 27-JUN-11:30 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.672651E+09 | 734.95 | 14-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.760616E+09 | 920.22 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.704010E+09 | 1094.11 | 26-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.752685E+09 | 1216.67 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.795121E+09 | 1177.57 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.802431E+09 | 1208.17 | 12-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.893108E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.672651E+09 | 684.55 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.811064E+09 | 1216.67 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.506884E+09 | 706.33 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.443850E+09 | 730.25 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.508693E+09 | 663.73 | 27-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.446107E+09 | 697.47 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.469576E+09 | 559.82 | 30-MAY-15:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.462451E+09 | 442.08 | 27-JUN-13:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.436780E+09 | 449.98 | 14-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.491009E+09 | 471.62 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.451301E+09 | 660.42 | 26-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.479538E+09 | 768.03 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.500218E+09 | 764.31 | 21-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.503751E+09 | 768.09 | 12-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.570016E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.436780E+09 | 442.08 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.508693E+09 | 768.09 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.753999E+09 | 1111.44 | 31-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.670984E+09 | 1153.40 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.786677E+09 | 1087.32 | 27-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.696156E+09 | 1124.26 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.733034E+09 | 923.25 | 23-MAY-07:19 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.720907E+09 | 717.43 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.680533E+09 | 867.36 | 14-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.764950E+09 | 954.53 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.699434E+09 | 1091.25 | 26-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.737811E+09 | 1209.46 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.746814E+09 | 1149.40 | 21-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.747875E+09 | 1198.05 | 12-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.873917E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.670984E+09 | 717.43 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.786677E+09 | 1209.46 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.502621E+09 | 741.26 | 31-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.443165E+09 | 758.38 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.516871E+09 | 726.84 | 27-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.451713E+09 | 735.16 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.472965E+09 | 637.17 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.464048E+09 | 561.61 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.439228E+09 | 603.49 | 14-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.496028E+09 | 682.14 | 23-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.457899E+09 | 727.39 | 26-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.483209E+09 | 788.68 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.493151E+09 | 771.27 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.493545E+09 | 778.20 | 12-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.571444E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.439228E+09 | 561.61 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.516871E+09 | 788.68 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.811105E+09 | 1138.96 | 31-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.702071E+09 | 1170.56 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.803214E+09 | 1096.55 | 27-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.694237E+09 | 1120.34 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.723803E+09 | 892.46 | 23-MAY-07:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.709042E+09 | 684.39 | 27-JUN-11:30 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.672637E+09 | 734.80 | 14-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.760599E+09 | 919.88 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.703964E+09 | 1093.89 | 26-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.752628E+09 | 1216.54 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.795090E+09 | 1177.44 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.802355E+09 | 1208.02 | 12-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.893074E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.672637E+09 | 684.39 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.811105E+09 | 1216.54 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.506887E+09 | 706.46 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.443850E+09 | 730.15 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.508681E+09 | 663.61 | 27-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.446107E+09 | 697.34 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.469565E+09 | 559.68 | 30-MAY-15:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.462443E+09 | 442.00 | 27-JUN-13:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.436755E+09 | 449.85 | 14-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.491013E+09 | 471.53 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.451464E+09 | 660.31 | 26-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.479533E+09 | 767.96 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.500221E+09 | 764.21 | 21-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.503717E+09 | 768.00 | 12-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.570024E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.436755E+09 | 442.00 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.508681E+09 | 768.00 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.753994E+09 | 1111.23 | 31-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.670979E+09 | 1153.22 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.786661E+09 | 1087.10 | 27-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.696136E+09 | 1124.03 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.733010E+09 | 922.83 | 23-MAY-07:19 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.720905E+09 | 717.27 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.680477E+09 | 866.95 | 14-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.764921E+09 | 954.20 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.699416E+09 | 1091.03 | 26-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.737796E+09 | 1209.33 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.746811E+09 | 1149.24 | 21-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.747866E+09 | 1197.90 | 12-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.873897E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.670979E+09 | 717.27 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.786661E+09 | 1209.33 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.502623E+09 | 741.13 | 31-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.443186E+09 | 758.27 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.516866E+09 | 726.71 | 27-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.451709E+09 | 735.02 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.472943E+09 | 637.02 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.464039E+09 | 561.42 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.439215E+09 | 603.25 | 14-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.496010E+09 | 682.08 | 23-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.457883E+09 | 727.25 | 26-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.483189E+09 | 788.60 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.493150E+09 | 771.19 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.493522E+09 | 778.10 | 12-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.571434E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.439215E+09 | 561.42 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.516866E+09 | 788.60 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.318958E+10 | 3337.76 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.289319E+10 | 3337.76 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.343791E+10 | 3337.76 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.307076E+10 | 3337.76 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.331375E+10 | 3337.76 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.329773E+10 | 3337.76 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.308678E+10 | 3337.76 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.343791E+10 | 3337.76 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.307076E+10 | 3337.76 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.318958E+10 | 3337.76 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.315220E+10 | 3337.76 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.308678E+10 | 3337.76 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.382269E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.289319E+10 | 3337.76 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.343791E+10 | 3337.76 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.113123E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.102611E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.108909E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.117527E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.116958E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.109477E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.108909E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.113123E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.111797E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.109477E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.135577E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.102611E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.811160E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 291468.04 | 92590153.40 |
February | 0.136985E+10 | 0.702011E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 535911.83 | 72354429.86 |
March | 0.163685E+10 | 0.803448E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1683937.54 | 75467746.44 |
April | 0.145243E+10 | 0.694308E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3419318.90 | 30903928.61 |
May | 0.157338E+10 | 0.723357E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14195187.57 | 4329890.29 |
June | 0.156900E+10 | 0.709831E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13283889.66 | 2656122.17 |
July | 0.145680E+10 | 0.672503E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20004724.42 | 438275.87 |
August | 0.163685E+10 | 0.760486E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18998996.53 | 2520104.36 |
September | 0.145243E+10 | 0.704043E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16274761.32 | 7518194.64 |
October | 0.150991E+10 | 0.752426E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13578189.23 | 26142115.95 |
November | 0.149516E+10 | 0.795053E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1451096.21 | 47479902.38 |
December | 0.145680E+10 | 0.801756E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 907390.03 | 84102341.46 |
Annual Sum or Average | 0.181194E+11 | 0.893038E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104625E+09 | 0.446503E+09 |
Minimum of Months | 0.136985E+10 | 0.672503E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 291468.04 | 438275.87 |
Maximum of Months | 0.163685E+10 | 0.811160E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20004724.42 | 92590153.40 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.507326E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 155388.13 | 63369611.91 |
February | 0.882782E+09 | 0.444013E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 326198.96 | 49002418.54 |
March | 0.105485E+10 | 0.509095E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 975083.57 | 49900647.72 |
April | 0.936002E+09 | 0.446198E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2263638.98 | 19958870.12 |
May | 0.101394E+10 | 0.469860E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9185118.24 | 2853091.04 |
June | 0.101113E+10 | 0.462571E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9052601.85 | 1493445.39 |
July | 0.938820E+09 | 0.436938E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13966494.18 | 192700.99 |
August | 0.105485E+10 | 0.491107E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13585499.62 | 1102226.10 |
September | 0.936002E+09 | 0.451440E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10301957.13 | 4841621.02 |
October | 0.973041E+09 | 0.479627E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8647919.35 | 17044970.07 |
November | 0.963541E+09 | 0.500294E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 891661.21 | 31556722.57 |
December | 0.938820E+09 | 0.503926E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 570877.00 | 54430380.15 |
Annual Sum or Average | 0.116768E+11 | 0.570240E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69922438.21 | 0.295747E+09 |
Minimum of Months | 0.882782E+09 | 0.436938E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 155388.13 | 192700.99 |
Maximum of Months | 0.105485E+10 | 0.509095E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13966494.18 | 63369611.91 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.753915E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 160690.30 | 0.100841E+09 |
February | 0.136988E+10 | 0.670839E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 375508.50 | 77186911.64 |
March | 0.163688E+10 | 0.786625E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1181023.31 | 77122629.03 |
April | 0.145246E+10 | 0.695940E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3058392.92 | 31999700.41 |
May | 0.157341E+10 | 0.732927E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14158764.63 | 4307265.62 |
June | 0.156904E+10 | 0.720760E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13485772.32 | 2564457.22 |
July | 0.145684E+10 | 0.680495E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20023896.37 | 438211.32 |
August | 0.163688E+10 | 0.764630E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18291888.17 | 2757775.03 |
September | 0.145246E+10 | 0.699387E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14518029.72 | 8526681.01 |
October | 0.150994E+10 | 0.737534E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10629634.65 | 30734010.89 |
November | 0.149520E+10 | 0.746421E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1008201.92 | 52531315.27 |
December | 0.145684E+10 | 0.747149E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 645617.49 | 90343165.35 |
Annual Sum or Average | 0.181198E+11 | 0.873662E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97537420.31 | 0.479353E+09 |
Minimum of Months | 0.136988E+10 | 0.670839E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 160690.30 | 438211.32 |
Maximum of Months | 0.163688E+10 | 0.786625E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20023896.37 | 0.100841E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.502986E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 139462.05 | 68511402.79 |
February | 0.882782E+09 | 0.443326E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 271736.73 | 55053819.59 |
March | 0.105485E+10 | 0.517170E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 821763.09 | 59233040.25 |
April | 0.936002E+09 | 0.451774E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1727021.76 | 27217614.78 |
May | 0.101394E+10 | 0.473215E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8697208.97 | 4914692.38 |
June | 0.101113E+10 | 0.464361E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7675845.57 | 3345266.20 |
July | 0.938820E+09 | 0.439551E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10639028.80 | 1388536.74 |
August | 0.105485E+10 | 0.496294E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10230524.68 | 4387487.33 |
September | 0.936002E+09 | 0.458088E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9553066.18 | 7489411.94 |
October | 0.973041E+09 | 0.483275E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7363269.16 | 23272507.00 |
November | 0.963541E+09 | 0.492988E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 719151.57 | 38096466.83 |
December | 0.938820E+09 | 0.493842E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 456027.70 | 67419966.93 |
Annual Sum or Average | 0.116768E+11 | 0.571687E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58294106.26 | 0.360330E+09 |
Minimum of Months | 0.882782E+09 | 0.439551E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 139462.05 | 1388536.74 |
Maximum of Months | 0.105485E+10 | 0.517170E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10639028.80 | 68511402.79 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.811064E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1810449.41 | 0.184209E+09 |
February | 0.136985E+10 | 0.702087E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1843754.45 | 0.143831E+09 |
March | 0.163685E+10 | 0.803282E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5212752.88 | 0.155174E+09 |
April | 0.145243E+10 | 0.694254E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7969308.12 | 69931997.58 |
May | 0.157338E+10 | 0.723821E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32109437.64 | 11033819.11 |
June | 0.156900E+10 | 0.709056E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29093778.35 | 8868624.64 |
July | 0.145680E+10 | 0.672651E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41528337.82 | 3377653.75 |
August | 0.163685E+10 | 0.760616E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39473985.29 | 11403822.40 |
September | 0.145243E+10 | 0.704010E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37833158.78 | 17243520.68 |
October | 0.150991E+10 | 0.752685E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32137473.05 | 58343693.30 |
November | 0.149516E+10 | 0.795121E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4525394.12 | 96878627.82 |
December | 0.145680E+10 | 0.802431E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3084933.76 | 0.166574E+09 |
Annual Sum or Average | 0.181194E+11 | 0.893108E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236623E+09 | 0.926870E+09 |
Minimum of Months | 0.136985E+10 | 0.672651E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1810449.41 | 3377653.75 |
Maximum of Months | 0.163685E+10 | 0.811064E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41528337.82 | 0.184209E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.506884E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 626916.46 | 0.131094E+09 |
February | 0.649041E+09 | 0.443850E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 877873.16 | 0.103118E+09 |
March | 0.773965E+09 | 0.508693E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2308514.60 | 0.111057E+09 |
April | 0.688021E+09 | 0.446107E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4650753.60 | 51493768.46 |
May | 0.744847E+09 | 0.469576E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19600286.42 | 8558560.94 |
June | 0.742030E+09 | 0.462451E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18590352.32 | 6467418.51 |
July | 0.690839E+09 | 0.436780E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25867847.31 | 2913702.06 |
August | 0.773965E+09 | 0.491009E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25007104.51 | 8415206.39 |
September | 0.688021E+09 | 0.451301E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22685072.44 | 12762195.59 |
October | 0.715730E+09 | 0.479538E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18477766.86 | 42524677.63 |
November | 0.708685E+09 | 0.500218E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2127777.15 | 70499954.96 |
December | 0.690839E+09 | 0.503751E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1459550.03 | 0.116552E+09 |
Annual Sum or Average | 0.858171E+10 | 0.570016E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142280E+09 | 0.665457E+09 |
Minimum of Months | 0.649041E+09 | 0.436780E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 626916.46 | 2913702.06 |
Maximum of Months | 0.773965E+09 | 0.508693E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25867847.31 | 0.131094E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.753999E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 301546.60 | 0.228952E+09 |
February | 0.136988E+10 | 0.670984E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 806258.18 | 0.174082E+09 |
March | 0.163688E+10 | 0.786677E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2639864.47 | 0.173190E+09 |
April | 0.145246E+10 | 0.696156E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6871300.18 | 77402027.37 |
May | 0.157341E+10 | 0.733034E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31925183.86 | 11310969.00 |
June | 0.156904E+10 | 0.720907E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29749263.42 | 8487779.50 |
July | 0.145684E+10 | 0.680533E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41895463.53 | 3301160.17 |
August | 0.163688E+10 | 0.764950E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37923498.17 | 12520524.28 |
September | 0.145246E+10 | 0.699434E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32481620.52 | 21414090.12 |
October | 0.150994E+10 | 0.737811E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23327562.24 | 77471157.19 |
November | 0.149520E+10 | 0.746814E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2213434.54 | 0.122212E+09 |
December | 0.145684E+10 | 0.747875E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1419938.69 | 0.205397E+09 |
Annual Sum or Average | 0.181198E+11 | 0.873917E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211555E+09 | 0.111574E+10 |
Minimum of Months | 0.136988E+10 | 0.670984E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 301546.60 | 3301160.17 |
Maximum of Months | 0.163688E+10 | 0.786677E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41895463.53 | 0.228952E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.502621E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 538117.88 | 0.138100E+09 |
February | 0.882782E+09 | 0.443165E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 776931.24 | 0.107633E+09 |
March | 0.105485E+10 | 0.516871E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2438926.25 | 0.116002E+09 |
April | 0.936002E+09 | 0.451713E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4113989.02 | 57061032.22 |
May | 0.101394E+10 | 0.472965E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19788924.72 | 10696396.07 |
June | 0.101113E+10 | 0.464048E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17590214.03 | 8709713.89 |
July | 0.938820E+09 | 0.439228E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24462317.67 | 4571507.28 |
August | 0.105485E+10 | 0.496028E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24109086.40 | 11845098.26 |
September | 0.936002E+09 | 0.457899E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21774653.65 | 16076456.97 |
October | 0.973041E+09 | 0.483209E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17845752.05 | 49524013.34 |
November | 0.963541E+09 | 0.493151E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2234654.03 | 74004830.75 |
December | 0.938820E+09 | 0.493545E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1376503.84 | 0.126260E+09 |
Annual Sum or Average | 0.116768E+11 | 0.571444E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137050E+09 | 0.720484E+09 |
Minimum of Months | 0.882782E+09 | 0.439228E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 538117.88 | 4571507.28 |
Maximum of Months | 0.105485E+10 | 0.516871E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24462317.67 | 0.138100E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.811105E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2520881.88 | 0.207396E+09 |
February | 0.136985E+10 | 0.702071E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2568152.28 | 0.159872E+09 |
March | 0.163685E+10 | 0.803214E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6300614.11 | 0.179143E+09 |
April | 0.145243E+10 | 0.694237E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9080788.38 | 83945507.08 |
May | 0.157338E+10 | 0.723803E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37072072.97 | 15623286.12 |
June | 0.156900E+10 | 0.709042E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33646509.64 | 12388812.29 |
July | 0.145680E+10 | 0.672637E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47378283.06 | 5265476.84 |
August | 0.163685E+10 | 0.760599E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45982939.48 | 16094980.37 |
September | 0.145243E+10 | 0.703964E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42959021.31 | 23369639.18 |
October | 0.150991E+10 | 0.752628E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37041267.79 | 69948160.25 |
November | 0.149516E+10 | 0.795090E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5871067.82 | 0.108720E+09 |
December | 0.145680E+10 | 0.802355E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4260916.22 | 0.188640E+09 |
Annual Sum or Average | 0.181194E+11 | 0.893074E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274683E+09 | 0.107041E+10 |
Minimum of Months | 0.136985E+10 | 0.672637E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2520881.88 | 5265476.84 |
Maximum of Months | 0.163685E+10 | 0.811105E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47378283.06 | 0.207396E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.506887E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 838659.46 | 0.148059E+09 |
February | 0.882782E+09 | 0.443850E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1061800.80 | 0.115459E+09 |
March | 0.105485E+10 | 0.508681E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2647091.08 | 0.130217E+09 |
April | 0.936002E+09 | 0.446107E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5245141.64 | 62853130.38 |
May | 0.101394E+10 | 0.469565E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23034265.28 | 11878963.93 |
June | 0.101113E+10 | 0.462443E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21759865.24 | 8958778.05 |
July | 0.938820E+09 | 0.436755E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30008188.22 | 4341352.84 |
August | 0.105485E+10 | 0.491013E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29480041.18 | 11799108.60 |
September | 0.936002E+09 | 0.451464E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26230834.03 | 17262588.68 |
October | 0.973041E+09 | 0.479533E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21370576.96 | 51655762.34 |
November | 0.963541E+09 | 0.500221E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2523503.69 | 80826985.32 |
December | 0.938820E+09 | 0.503717E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1840410.15 | 0.132977E+09 |
Annual Sum or Average | 0.116768E+11 | 0.570024E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166040E+09 | 0.776289E+09 |
Minimum of Months | 0.882782E+09 | 0.436755E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 838659.46 | 4341352.84 |
Maximum of Months | 0.105485E+10 | 0.508681E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30008188.22 | 0.148059E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.753994E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 356308.80 | 0.263253E+09 |
February | 0.136988E+10 | 0.670979E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 939994.12 | 0.197129E+09 |
March | 0.163688E+10 | 0.786661E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3059556.26 | 0.202499E+09 |
April | 0.145246E+10 | 0.696136E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7807784.44 | 93856752.84 |
May | 0.157341E+10 | 0.733010E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36910757.36 | 15994975.49 |
June | 0.156904E+10 | 0.720905E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34385784.48 | 11894914.74 |
July | 0.145684E+10 | 0.680477E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47900868.02 | 5120516.14 |
August | 0.163688E+10 | 0.764921E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44358016.15 | 17619470.10 |
September | 0.145246E+10 | 0.699416E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37926826.05 | 28868622.51 |
October | 0.150994E+10 | 0.737796E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27621976.08 | 95450875.71 |
November | 0.149520E+10 | 0.746811E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2672362.85 | 0.143726E+09 |
December | 0.145684E+10 | 0.747866E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1687188.56 | 0.237541E+09 |
Annual Sum or Average | 0.181198E+11 | 0.873897E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245627E+09 | 0.131295E+10 |
Minimum of Months | 0.136988E+10 | 0.670979E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 356308.80 | 5120516.14 |
Maximum of Months | 0.163688E+10 | 0.786661E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47900868.02 | 0.263253E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.502623E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 715051.75 | 0.158847E+09 |
February | 0.882782E+09 | 0.443186E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 995336.04 | 0.122405E+09 |
March | 0.105485E+10 | 0.516866E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2973359.61 | 0.136040E+09 |
April | 0.936002E+09 | 0.451709E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4917880.54 | 68937953.34 |
May | 0.101394E+10 | 0.472943E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23872590.24 | 14047417.22 |
June | 0.101113E+10 | 0.464039E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21242307.89 | 11380693.19 |
July | 0.938820E+09 | 0.439215E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29647666.15 | 6002175.45 |
August | 0.105485E+10 | 0.496010E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29061226.34 | 15672003.29 |
September | 0.936002E+09 | 0.457883E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26137983.67 | 20771135.10 |
October | 0.973041E+09 | 0.483189E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21482758.41 | 60003714.46 |
November | 0.963541E+09 | 0.493150E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2889501.26 | 85453729.16 |
December | 0.938820E+09 | 0.493522E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1830737.79 | 0.145835E+09 |
Annual Sum or Average | 0.116768E+11 | 0.571434E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165766E+09 | 0.845395E+09 |
Minimum of Months | 0.882782E+09 | 0.439215E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 715051.75 | 6002175.45 |
Maximum of Months | 0.105485E+10 | 0.516866E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29647666.15 | 0.158847E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.318958E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.289319E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.343791E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.307076E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.331375E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.329773E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.308678E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.343791E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.307076E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.318958E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.315220E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.308678E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.382269E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.289319E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.343791E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228981.42 | 0.204851E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576831.85 | 0.159044E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2331892.01 | 0.163916E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5268527.72 | 69874845.23 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25180107.44 | 8048192.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23416036.55 | 6278006.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36071219.14 | 1485015.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32263772.28 | 8175653.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28485085.94 | 16067270.10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22118627.55 | 60464996.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1919733.59 | 0.106362E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1243533.30 | 0.186073E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179104E+09 | 0.990639E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228981.42 | 1485015.57 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36071219.14 | 0.204851E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1078630.74 | 0.336590E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1696941.30 | 0.262738E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5796991.34 | 0.272821E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10228412.39 | 0.119645E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47449256.91 | 13391775.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43013908.22 | 11368550.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65661344.58 | 2919561.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58390722.92 | 15747181.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54382446.17 | 25564666.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41935999.56 | 0.101885E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4241380.48 | 0.177358E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2880022.42 | 0.303290E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336756E+09 | 0.164332E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1078630.74 | 2919561.88 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65661344.58 | 0.336590E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480835.76 | 0.335376E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 690595.47 | 0.261178E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3252810.40 | 0.286153E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6593671.56 | 0.135415E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40507566.19 | 18036153.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38257652.29 | 14442583.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58217561.79 | 5075588.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54015105.52 | 20714562.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49962531.62 | 31035333.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34321661.16 | 0.109687E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3098807.12 | 0.178332E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2384205.27 | 0.303738E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291783E+09 | 0.169918E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480835.76 | 5075588.60 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58217561.79 | 0.335376E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 11837.83 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 11837.83 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 11837.83 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 11837.83 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 11837.83 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 11837.83 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 11837.83 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 11837.83 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 11837.83 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 11837.83 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 11837.83 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 11837.83 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 11837.83 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 11837.83 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1135.02 | 31-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.62 | 16-JAN-15:00 | 179.64 | 09-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 1167.25 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.48 | 02-FEB-13:00 | 250.14 | 05-FEB-08:00 |
March | 2010.79 | 01-MAR-10:09 | 1091.46 | 27-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 05-MAR-13:10 | 215.86 | 20-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1115.86 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.23 | 29-APR-17:02 | 130.49 | 01-APR-21:00 |
May | 2010.79 | 01-MAY-09:09 | 883.46 | 23-MAY-07:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.32 | 21-MAY-13:50 | 25.56 | 09-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 689.07 | 27-JUN-11:30 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.80 | 10-JUN-17:02 | 40.18 | 06-JUN-21:50 |
July | 2010.79 | 03-JUL-09:09 | 736.83 | 14-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.39 | 22-JUL-18:50 | 18.33 | 30-JUL-10:53 |
August | 2010.79 | 01-AUG-09:09 | 911.01 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.98 | 20-AUG-14:00 | 40.11 | 26-AUG-00:10 |
September | 2010.79 | 01-SEP-09:09 | 1088.83 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.82 | 09-SEP-22:57 | 48.41 | 05-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 1214.09 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.52 | 09-OCT-13:50 | 105.97 | 29-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 1174.17 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.10 | 05-NOV-13:00 | 152.51 | 12-NOV-08:00 |
December | 2010.79 | 01-DEC-10:09 | 1205.45 | 12-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.21 | 10-DEC-14:50 | 232.12 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 689.07 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 12.48 | 18.33 | |||||
Maximum of Months | 2010.79 | 1214.09 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 105.52 | 250.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 704.89 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 16-JAN-15:00 | 119.08 | 22-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 729.41 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.32 | 02-FEB-13:00 | 175.13 | 05-FEB-10:00 |
March | 1295.83 | 01-MAR-10:09 | 661.70 | 27-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.08 | 05-MAR-13:10 | 142.02 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 696.02 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.59 | 29-APR-17:50 | 83.83 | 01-APR-21:00 |
May | 1295.83 | 01-MAY-09:09 | 560.96 | 30-MAY-15:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.48 | 21-MAY-13:50 | 17.24 | 14-MAY-12:10 |
June | 1295.83 | 01-JUN-09:09 | 445.37 | 27-JUN-13:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.33 | 10-JUN-17:02 | 25.19 | 06-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 451.48 | 14-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.78 | 22-JUL-18:50 | 17.05 | 30-JUL-10:53 |
August | 1295.83 | 01-AUG-09:09 | 472.79 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.86 | 20-AUG-14:00 | 24.33 | 26-AUG-00:10 |
September | 1295.83 | 01-SEP-09:09 | 658.09 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.37 | 09-SEP-22:53 | 32.22 | 05-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 767.38 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.56 | 09-OCT-13:50 | 69.96 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 764.09 | 21-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.36 | 05-NOV-13:00 | 114.12 | 12-NOV-08:10 |
December | 1295.83 | 01-DEC-10:09 | 767.68 | 12-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 | 10-DEC-14:50 | 149.34 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 445.37 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 17.05 | |||||
Maximum of Months | 1295.83 | 767.68 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 64.56 | 175.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1106.32 | 31-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.58 | 19-JAN-12:10 | 180.89 | 26-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 1149.29 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 02-FEB-13:00 | 249.07 | 05-FEB-08:00 |
March | 2010.83 | 01-MAR-10:09 | 1081.67 | 27-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.47 | 26-MAR-13:55 | 218.25 | 20-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1119.68 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 29-APR-17:02 | 132.00 | 01-APR-21:00 |
May | 2010.83 | 01-MAY-09:09 | 914.74 | 23-MAY-07:19 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.79 | 21-MAY-13:50 | 25.70 | 09-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 719.77 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.65 | 10-JUN-17:02 | 39.67 | 06-JUN-21:50 |
July | 2010.83 | 03-JUL-09:09 | 857.85 | 14-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.37 | 22-JUL-18:50 | 19.72 | 30-JUL-10:53 |
August | 2010.83 | 01-AUG-09:09 | 946.49 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.48 | 20-AUG-14:00 | 41.09 | 26-AUG-00:10 |
September | 2010.83 | 01-SEP-09:09 | 1085.88 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.62 | 09-SEP-22:57 | 51.46 | 05-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 1206.62 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.40 | 09-OCT-13:55 | 110.92 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 1144.87 | 21-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 | 07-NOV-13:00 | 166.39 | 12-NOV-08:10 |
December | 2010.83 | 01-DEC-10:09 | 1194.94 | 12-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 | 13-DEC-14:00 | 226.90 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 719.77 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4.58 | 19.72 | |||||
Maximum of Months | 2010.83 | 1206.62 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 85.40 | 249.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 741.01 | 31-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 16-JAN-14:10 | 126.80 | 26-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 758.17 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.32 | 02-FEB-13:00 | 177.29 | 05-FEB-08:00 |
March | 1295.83 | 01-MAR-10:09 | 726.59 | 27-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 05-MAR-12:50 | 161.55 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 734.93 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.68 | 29-APR-17:07 | 108.48 | 01-APR-21:00 |
May | 1295.83 | 01-MAY-09:09 | 637.06 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.78 | 21-MAY-13:50 | 23.14 | 09-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 561.45 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.72 | 10-JUN-17:08 | 38.24 | 06-JUN-21:50 |
July | 1295.83 | 03-JUL-09:09 | 603.04 | 14-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.74 | 02-JUL-11:50 | 19.11 | 31-JUL-02:20 |
August | 1295.83 | 01-AUG-09:09 | 681.58 | 23-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.24 | 20-AUG-13:58 | 39.38 | 25-AUG-23:35 |
September | 1295.83 | 01-SEP-09:09 | 727.14 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.68 | 09-SEP-23:00 | 37.91 | 13-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 788.54 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.98 | 09-OCT-13:48 | 83.46 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 771.05 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.51 | 11-NOV-12:30 | 112.81 | 12-NOV-08:00 |
December | 1295.83 | 01-DEC-10:09 | 778.02 | 12-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.05 | 13-DEC-14:00 | 178.19 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 561.45 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 19.11 | |||||
Maximum of Months | 1295.83 | 788.54 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 60.98 | 178.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1139.16 | 31-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.07 | 16-JAN-15:00 | 370.99 | 21-JAN-05:55 |
February | 2010.79 | 01-FEB-10:09 | 1170.75 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 69.46 | 20-FEB-15:00 | 517.09 | 05-FEB-07:55 |
March | 2010.79 | 01-MAR-10:09 | 1096.78 | 27-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 92.63 | 05-MAR-13:00 | 457.51 | 20-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1120.56 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.72 | 29-APR-17:02 | 265.24 | 01-APR-21:00 |
May | 2010.79 | 01-MAY-09:09 | 892.90 | 23-MAY-07:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.93 | 07-MAY-14:00 | 53.02 | 09-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 684.55 | 27-JUN-11:30 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.68 | 10-JUN-17:02 | 83.18 | 06-JUN-21:50 |
July | 2010.79 | 03-JUL-09:09 | 734.95 | 14-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.94 | 22-JUL-18:50 | 43.35 | 31-JUL-02:35 |
August | 2010.79 | 01-AUG-09:09 | 920.22 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.88 | 20-AUG-14:00 | 117.29 | 25-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 1094.11 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.41 | 09-SEP-22:53 | 114.00 | 05-SEP-02:53 |
October | 2010.79 | 02-OCT-09:09 | 1216.67 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.51 | 09-OCT-13:52 | 211.79 | 29-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 1177.57 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.52 | 11-NOV-13:10 | 323.53 | 12-NOV-08:00 |
December | 2010.79 | 01-DEC-10:09 | 1208.17 | 12-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.12 | 10-DEC-15:00 | 463.70 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 684.55 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 53.07 | 43.35 | |||||
Maximum of Months | 2010.79 | 1216.67 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 262.51 | 517.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 706.33 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.91 | 16-JAN-15:00 | 246.94 | 21-JAN-05:55 |
February | 1239.33 | 01-FEB-08:09 | 730.25 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.80 | 20-FEB-15:00 | 369.14 | 05-FEB-10:00 |
March | 1239.33 | 01-MAR-08:09 | 663.73 | 27-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.04 | 05-MAR-13:00 | 312.27 | 20-MAR-22:00 |
April | 1239.33 | 03-APR-07:10 | 697.47 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.73 | 29-APR-17:02 | 184.38 | 01-APR-21:00 |
May | 1239.33 | 01-MAY-07:10 | 559.82 | 30-MAY-15:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.08 | 21-MAY-13:37 | 45.90 | 14-MAY-12:10 |
June | 1239.33 | 01-JUN-07:10 | 442.08 | 27-JUN-13:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.55 | 10-JUN-17:02 | 56.25 | 06-JUN-22:00 |
July | 1239.33 | 03-JUL-07:10 | 449.98 | 14-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.52 | 22-JUL-18:50 | 56.99 | 30-JUL-11:00 |
August | 1239.33 | 01-AUG-07:10 | 471.62 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.00 | 20-AUG-14:00 | 80.65 | 25-AUG-23:53 |
September | 1239.33 | 01-SEP-07:10 | 660.42 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.30 | 09-SEP-22:53 | 82.08 | 05-SEP-02:53 |
October | 1239.33 | 02-OCT-07:10 | 768.03 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.20 | 09-OCT-13:50 | 146.86 | 29-OCT-02:00 |
November | 1239.33 | 01-NOV-07:10 | 764.31 | 21-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.96 | 05-NOV-13:00 | 253.44 | 12-NOV-08:40 |
December | 1239.33 | 01-DEC-08:09 | 768.09 | 12-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.79 | 10-DEC-15:00 | 311.03 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 442.08 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 26.91 | 45.90 | |||||
Maximum of Months | 1239.33 | 768.09 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 142.20 | 369.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1111.44 | 31-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | 19-JAN-12:10 | 404.48 | 26-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 1153.40 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.52 | 02-FEB-13:00 | 551.95 | 05-FEB-08:00 |
March | 2010.83 | 01-MAR-10:09 | 1087.32 | 27-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.08 | 26-MAR-13:53 | 481.77 | 20-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1124.26 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.67 | 29-APR-17:02 | 286.01 | 01-APR-21:00 |
May | 2010.83 | 01-MAY-09:09 | 923.25 | 23-MAY-07:19 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.23 | 21-MAY-13:37 | 55.06 | 09-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 717.43 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.22 | 10-JUN-17:02 | 83.48 | 06-JUN-21:50 |
July | 2010.83 | 03-JUL-09:09 | 867.36 | 14-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.04 | 22-JUL-18:50 | 45.11 | 31-JUL-02:35 |
August | 2010.83 | 01-AUG-09:09 | 954.53 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.38 | 20-AUG-14:00 | 121.00 | 25-AUG-23:53 |
September | 2010.83 | 01-SEP-09:09 | 1091.25 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.40 | 09-SEP-22:53 | 126.28 | 05-SEP-02:53 |
October | 2010.83 | 02-OCT-09:09 | 1209.46 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.72 | 09-OCT-13:48 | 249.81 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 1149.40 | 21-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.23 | 07-NOV-13:00 | 376.32 | 12-NOV-11:00 |
December | 2010.83 | 01-DEC-10:09 | 1198.05 | 12-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.82 | 13-DEC-14:00 | 488.28 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 717.43 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | 45.11 | |||||
Maximum of Months | 2010.83 | 1209.46 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 194.38 | 551.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 741.26 | 31-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.69 | 16-JAN-13:40 | 256.23 | 26-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 758.38 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 | 02-FEB-13:00 | 355.52 | 05-FEB-07:55 |
March | 1295.83 | 01-MAR-10:09 | 726.84 | 27-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.73 | 05-MAR-12:40 | 325.99 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 735.16 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.48 | 29-APR-17:07 | 203.75 | 01-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 637.17 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.80 | 21-MAY-13:33 | 51.53 | 06-MAY-19:53 |
June | 1295.83 | 01-JUN-09:09 | 561.61 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.52 | 10-JUN-17:08 | 67.73 | 06-JUN-21:50 |
July | 1295.83 | 03-JUL-09:09 | 603.49 | 14-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.72 | 16-JUL-13:00 | 44.49 | 31-JUL-01:55 |
August | 1295.83 | 01-AUG-09:09 | 682.14 | 23-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.29 | 20-AUG-14:00 | 90.54 | 25-AUG-23:53 |
September | 1295.83 | 01-SEP-09:09 | 727.39 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.16 | 09-SEP-22:43 | 88.25 | 05-SEP-02:53 |
October | 1295.83 | 02-OCT-09:09 | 788.68 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.82 | 09-OCT-12:10 | 161.93 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 771.27 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.71 | 11-NOV-12:30 | 229.64 | 12-NOV-07:05 |
December | 1295.83 | 01-DEC-10:09 | 778.20 | 12-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.68 | 10-DEC-11:20 | 323.58 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 561.61 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 | 44.49 | |||||
Maximum of Months | 1295.83 | 788.68 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 154.82 | 355.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1138.96 | 31-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 68.94 | 15-JAN-14:10 | 447.75 | 21-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 1170.56 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.48 | 20-FEB-15:10 | 572.46 | 05-FEB-08:00 |
March | 2010.79 | 01-MAR-10:09 | 1096.55 | 27-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.66 | 05-MAR-12:50 | 538.88 | 20-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1120.34 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.56 | 29-APR-17:02 | 314.74 | 01-APR-21:00 |
May | 2010.79 | 01-MAY-09:09 | 892.46 | 23-MAY-07:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.00 | 07-MAY-14:00 | 72.00 | 09-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 684.39 | 27-JUN-11:30 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.10 | 10-JUN-17:02 | 108.31 | 06-JUN-21:50 |
July | 2010.79 | 03-JUL-09:09 | 734.80 | 14-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.72 | 22-JUL-18:50 | 65.73 | 30-JUL-11:00 |
August | 2010.79 | 01-AUG-09:09 | 919.88 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.41 | 20-AUG-14:00 | 145.19 | 25-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 1093.89 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.33 | 09-SEP-22:57 | 152.86 | 05-SEP-02:53 |
October | 2010.79 | 02-OCT-09:09 | 1216.54 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.09 | 09-OCT-13:43 | 227.29 | 29-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 1177.44 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.30 | 05-NOV-13:00 | 381.90 | 12-NOV-07:00 |
December | 2010.79 | 01-DEC-10:09 | 1208.02 | 12-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 64.49 | 10-DEC-10:53 | 500.36 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 684.39 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 64.49 | 65.73 | |||||
Maximum of Months | 2010.79 | 1216.54 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 290.09 | 572.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 706.46 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.83 | 16-JAN-15:00 | 298.51 | 21-JAN-05:55 |
February | 1295.83 | 01-FEB-10:09 | 730.15 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.03 | 20-FEB-15:10 | 383.75 | 05-FEB-08:00 |
March | 1295.83 | 01-MAR-10:09 | 663.61 | 27-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.74 | 05-MAR-13:10 | 371.58 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 697.34 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.97 | 29-APR-17:02 | 221.19 | 01-APR-21:00 |
May | 1295.83 | 01-MAY-09:09 | 559.68 | 30-MAY-15:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.41 | 21-MAY-13:33 | 56.02 | 14-MAY-12:00 |
June | 1295.83 | 01-JUN-09:09 | 442.00 | 27-JUN-13:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.69 | 10-JUN-17:02 | 74.92 | 18-JUN-13:55 |
July | 1295.83 | 03-JUL-09:09 | 449.85 | 14-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.03 | 22-JUL-18:50 | 79.72 | 30-JUL-11:00 |
August | 1295.83 | 01-AUG-09:09 | 471.53 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.93 | 20-AUG-14:00 | 100.12 | 25-AUG-23:53 |
September | 1295.83 | 01-SEP-09:09 | 660.31 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.50 | 09-SEP-22:53 | 108.40 | 05-SEP-02:53 |
October | 1295.83 | 02-OCT-09:09 | 767.96 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.43 | 09-OCT-14:10 | 159.15 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 764.21 | 21-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.10 | 05-NOV-13:00 | 297.44 | 12-NOV-08:40 |
December | 1295.83 | 01-DEC-10:09 | 768.00 | 12-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 10-DEC-15:10 | 336.93 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 442.00 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 56.02 | |||||
Maximum of Months | 1295.83 | 768.00 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 173.43 | 383.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1111.23 | 31-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 | 19-JAN-12:00 | 470.74 | 22-JAN-16:55 |
February | 2010.83 | 01-FEB-10:09 | 1153.22 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.48 | 02-FEB-13:00 | 573.99 | 04-FEB-20:00 |
March | 2010.83 | 01-MAR-10:09 | 1087.10 | 27-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.27 | 26-MAR-13:45 | 574.00 | 20-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1124.03 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.19 | 29-APR-17:02 | 346.90 | 01-APR-17:53 |
May | 2010.83 | 01-MAY-09:09 | 922.83 | 23-MAY-07:19 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.61 | 21-MAY-13:33 | 74.63 | 09-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 717.27 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.38 | 10-JUN-17:02 | 109.13 | 06-JUN-21:50 |
July | 2010.83 | 03-JUL-09:09 | 866.95 | 14-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.52 | 22-JUL-18:50 | 68.15 | 30-JUL-11:00 |
August | 2010.83 | 01-AUG-09:09 | 954.20 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.62 | 20-AUG-14:00 | 150.01 | 25-AUG-23:53 |
September | 2010.83 | 01-SEP-09:09 | 1091.03 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.56 | 09-SEP-22:57 | 166.81 | 05-SEP-02:53 |
October | 2010.83 | 02-OCT-09:09 | 1209.33 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.01 | 09-OCT-13:48 | 279.71 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 1149.24 | 21-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.36 | 07-NOV-13:00 | 440.12 | 12-NOV-08:00 |
December | 2010.83 | 01-DEC-10:09 | 1197.90 | 12-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.27 | 13-DEC-14:00 | 523.94 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 717.27 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 | 68.15 | |||||
Maximum of Months | 2010.83 | 1209.33 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 240.62 | 574.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 741.13 | 31-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.35 | 16-JAN-13:20 | 298.51 | 21-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 758.27 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 26-FEB-13:32 | 381.65 | 05-FEB-07:55 |
March | 1295.83 | 01-MAR-10:09 | 726.71 | 27-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 64.37 | 05-MAR-13:10 | 387.93 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 735.02 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.26 | 29-APR-17:07 | 248.59 | 01-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 637.02 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.74 | 21-MAY-13:33 | 62.44 | 06-MAY-20:00 |
June | 1295.83 | 01-JUN-09:09 | 561.42 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.69 | 10-JUN-17:08 | 87.40 | 06-JUN-21:50 |
July | 1295.83 | 03-JUL-09:09 | 603.25 | 14-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.57 | 02-JUL-12:00 | 54.52 | 31-JUL-02:10 |
August | 1295.83 | 01-AUG-09:09 | 682.08 | 23-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.66 | 20-AUG-14:00 | 112.50 | 25-AUG-23:53 |
September | 1295.83 | 01-SEP-09:09 | 727.25 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.09 | 09-SEP-23:00 | 113.80 | 05-SEP-02:53 |
October | 1295.83 | 02-OCT-09:09 | 788.60 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.96 | 09-OCT-12:10 | 181.54 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 771.19 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.21 | 05-NOV-13:00 | 273.37 | 12-NOV-07:00 |
December | 1295.83 | 01-DEC-10:09 | 778.10 | 12-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.50 | 10-DEC-11:10 | 358.98 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 561.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 54.52 | |||||
Maximum of Months | 1295.83 | 788.60 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 187.96 | 387.93 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 3337.76 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 3337.76 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 3337.76 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 3337.76 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 3337.76 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 3337.76 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 3337.76 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 3337.76 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 3337.76 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 3337.76 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 3337.76 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 3337.76 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 3337.76 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.52 | 16-JAN-15:00 | 382.30 | 09-JAN-05:04 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.25 | 02-FEB-13:00 | 549.23 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.65 | 26-MAR-14:00 | 464.93 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.55 | 29-APR-17:02 | 269.41 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.36 | 21-MAY-13:53 | 40.71 | 09-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.88 | 10-JUN-17:02 | 69.58 | 06-JUN-21:50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.05 | 22-JUL-18:53 | 26.41 | 31-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.77 | 20-AUG-14:00 | 97.10 | 25-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.70 | 09-SEP-17:02 | 89.66 | 05-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.38 | 09-OCT-14:00 | 228.08 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.28 | 05-NOV-13:00 | 320.83 | 12-NOV-08:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.25 | 10-DEC-15:00 | 508.61 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.52 | 26.41 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.38 | 549.23 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.96 | 16-JAN-15:00 | 657.51 | 21-JAN-05:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.51 | 20-FEB-15:00 | 948.31 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.98 | 05-MAR-13:00 | 801.51 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.36 | 29-APR-17:02 | 451.65 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.43 | 21-MAY-13:53 | 64.36 | 09-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.84 | 10-JUN-17:02 | 116.94 | 06-JUN-21:50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.50 | 22-JUL-18:53 | 48.92 | 31-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.64 | 20-AUG-14:00 | 184.04 | 25-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.74 | 09-SEP-17:02 | 149.24 | 05-SEP-03:04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.68 | 09-OCT-13:52 | 384.94 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.25 | 05-NOV-13:00 | 554.60 | 12-NOV-08:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.45 | 10-DEC-15:00 | 864.27 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.96 | 48.92 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.68 | 948.31 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.66 | 16-JAN-15:00 | 655.98 | 21-JAN-05:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.29 | 02-FEB-13:00 | 870.52 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.07 | 26-MAR-13:53 | 844.02 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.13 | 29-APR-17:02 | 493.72 | 01-APR-17:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.22 | 07-MAY-14:00 | 128.13 | 14-MAY-11:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.33 | 10-JUN-17:02 | 127.02 | 07-JUN-01:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.92 | 02-JUL-10:53 | 122.84 | 30-JUL-11:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.10 | 20-AUG-14:00 | 204.03 | 25-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.32 | 09-SEP-23:00 | 199.30 | 05-SEP-03:04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.43 | 09-OCT-13:52 | 359.29 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 | 05-NOV-13:00 | 579.82 | 12-NOV-07:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.49 | 10-DEC-14:52 | 802.05 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.29 | 122.84 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.32 | 870.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 100714.27 | 09-JAN-04:12 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 100289.71 | 13-FEB-04:03 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 98286.81 | 20-MAR-03:02 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96806.33 | 10-APR-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71226.47 | 30-MAY-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74281.70 | 07-JUN-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 71744.94 | 05-JUL-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75370.86 | 28-AUG-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 78567.97 | 05-SEP-02:13 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 88874.08 | 28-OCT-05:03 | 7180.90 | 5261.11 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 97038.41 | 24-NOV-04:03 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 99135.99 | 04-DEC-04:03 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 71226.47 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 100714.27 | 7180.90 | 5261.11 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 83572.81 | 02-JAN-04:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 80586.93 | 21-FEB-04:03 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 81033.29 | 20-MAR-03:02 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79016.52 | 10-APR-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76261.15 | 09-MAY-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74077.96 | 07-JUN-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 67027.64 | 12-JUL-05:02 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 66853.99 | 01-AUG-05:02 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 78029.09 | 20-SEP-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 80965.90 | 30-OCT-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84093.15 | 13-NOV-04:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 83730.07 | 26-DEC-04:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 66853.99 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84093.15 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 70706.70 | 20-JAN-06:04 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 68997.04 | 24-FEB-06:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 71616.10 | 28-MAR-05:04 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 73372.89 | 14-APR-05:04 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69064.57 | 23-MAY-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 70862.51 | 07-JUN-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 69581.97 | 12-JUL-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 70282.77 | 17-AUG-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 70017.20 | 08-SEP-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 71165.85 | 17-OCT-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 73022.89 | 01-NOV-05:04 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 72726.97 | 12-DEC-06:04 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 68997.04 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73372.89 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 66898.55 | 20-JAN-06:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 66210.95 | 03-FEB-06:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 68196.05 | 28-MAR-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70472.24 | 06-APR-05:04 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69727.37 | 23-MAY-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 69990.53 | 30-JUN-03:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 70094.66 | 12-JUL-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 69113.62 | 01-AUG-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 73289.84 | 08-SEP-05:04 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 71681.92 | 17-OCT-05:04 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 72393.33 | 04-NOV-05:04 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 66272.70 | 12-DEC-06:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 66210.95 | 0.00 | 2953.40 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73289.84 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9695.97 | 31-JAN-06:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 |
February | 6310.69 | 22-FEB-14:30 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 | 0.00 |
March | 8134.79 | 27-MAR-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 |
April | 10389.85 | 24-APR-05:02 | 1214.60 | 889.88 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
May | 11405.88 | 31-MAY-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11614.97 | 25-JUN-15:52 | 607.30 | 211.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 | 0.00 |
July | 12672.33 | 03-JUL-05:03 | 1214.60 | 889.88 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 2.91 | 0.00 |
August | 12485.70 | 14-AUG-05:03 | 1214.60 | 889.88 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 0.00 |
September | 10850.99 | 05-SEP-05:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.36 |
October | 10849.70 | 07-OCT-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 1.30 | 0.00 |
November | 9719.95 | 02-NOV-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
December | 10690.56 | 11-DEC-06:02 | 1214.60 | 889.88 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6310.69 | 0.00 | 211.73 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12672.33 | 2010.79 | 889.88 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 | 7.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9858.53 | 01-JAN-10:13 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.87 |
February | 7069.83 | 27-FEB-10:10 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 |
March | 10041.24 | 26-MAR-09:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 |
April | 12772.77 | 23-APR-11:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
May | 16209.80 | 29-MAY-08:62 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 |
June | 15406.75 | 11-JUN-08:53 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 4.69 | 0.00 |
July | 15552.00 | 23-JUL-09:53 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13743.76 | 06-AUG-10:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 0.00 |
September | 15616.42 | 24-SEP-09:23 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 4.35 | 0.00 |
October | 15460.95 | 09-OCT-09:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 | 0.00 |
November | 8703.35 | 11-NOV-09:03 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.96 |
December | 5271.38 | 16-DEC-09:40 | 391.37 | 136.43 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5271.38 | 195.68 | 68.22 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16209.80 | 1295.83 | 409.30 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 28.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20113.83 | 01-JAN-13:32 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.10 |
February | 18596.69 | 26-FEB-13:23 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.71 |
March | 17722.26 | 26-MAR-14:23 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
April | 12887.73 | 28-APR-05:02 | 1214.62 | 889.90 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
May | 13168.16 | 22-MAY-05:03 | 809.75 | 593.26 | 3841.04 | 0.00 | 0.00 | 0.00 | 0.00 | 5.62 | 0.00 |
June | 13287.56 | 29-JUN-05:02 | 1012.19 | 741.58 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 | 0.00 |
July | 13792.04 | 24-JUL-05:03 | 809.75 | 593.26 | 3841.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 | 0.00 |
August | 13999.37 | 06-AUG-13:23 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 20.75 | 0.00 |
September | 18412.61 | 10-SEP-13:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 37.14 | 0.00 |
October | 19006.38 | 15-OCT-13:32 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 | 0.00 |
November | 18597.68 | 11-NOV-11:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.60 |
December | 19287.60 | 17-DEC-13:12 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12887.73 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20113.83 | 1214.62 | 889.90 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 37.14 | 91.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19622.35 | 01-JAN-16:12 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 |
February | 20630.06 | 26-FEB-16:42 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 |
March | 18351.83 | 26-MAR-14:23 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 | 0.00 |
April | 20561.43 | 23-APR-18:22 | 0.00 | 156.39 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.93 |
May | 21173.29 | 28-MAY-15:52 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 0.00 |
June | 21304.75 | 25-JUN-15:52 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 5.37 | 0.00 |
July | 20414.04 | 02-JUL-15:42 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 8.15 | 0.00 |
August | 20487.62 | 20-AUG-17:12 | 0.00 | 113.70 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 | 0.00 |
September | 20567.05 | 24-SEP-16:02 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 11.42 | 0.00 |
October | 20600.01 | 09-OCT-16:22 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 | 0.00 |
November | 19237.04 | 05-NOV-14:43 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 | 0.00 |
December | 20531.51 | 10-DEC-16:42 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18351.83 | 0.00 | 90.96 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21304.75 | 391.37 | 156.39 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 15.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4101.53 | 02-JAN-13:30 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 | 0.00 |
February | 4685.17 | 28-FEB-15:00 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 | 0.00 |
March | 7573.57 | 28-MAR-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 |
April | 9202.47 | 14-APR-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.28 |
May | 11756.53 | 26-MAY-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 |
June | 11867.13 | 28-JUN-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 7.38 | 0.00 |
July | 11875.67 | 10-JUL-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.91 |
August | 11933.78 | 14-AUG-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 4.13 | 0.00 |
September | 10365.35 | 11-SEP-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 2.46 | 0.00 |
October | 11093.14 | 06-OCT-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 13.85 | 0.00 |
November | 9281.79 | 01-NOV-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.93 |
December | 8490.26 | 12-DEC-06:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4101.53 | 0.00 | 370.83 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11933.78 | 2010.79 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 13.85 | 15.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5689.03 | 19-JAN-10:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 |
February | 6071.84 | 27-FEB-10:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
March | 8225.52 | 26-MAR-09:53 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.43 |
April | 15659.31 | 23-APR-11:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
May | 16771.03 | 29-MAY-09:32 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 0.00 |
June | 15931.27 | 11-JUN-08:53 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 | 0.00 |
July | 15960.63 | 16-JUL-08:32 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 0.00 |
August | 15688.00 | 27-AUG-10:23 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 25.04 | 0.00 |
September | 16589.43 | 03-SEP-09:42 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 0.00 |
October | 15872.94 | 09-OCT-09:23 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 18.87 | 0.00 |
November | 9410.98 | 01-NOV-05:02 | 652.28 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.73 |
December | 5466.50 | 12-DEC-06:02 | 652.28 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5466.50 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16771.03 | 1239.33 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.04 | 13.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17503.37 | 16-JAN-14:32 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 |
February | 17547.73 | 26-FEB-13:32 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.40 |
March | 15073.98 | 05-MAR-12:53 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 18.40 | 0.00 |
April | 11532.35 | 29-APR-05:03 | 809.75 | 593.26 | 3841.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 |
May | 13091.64 | 22-MAY-03:02 | 0.00 | 370.84 | 3727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
June | 12925.19 | 14-JUN-05:02 | 1012.19 | 741.58 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 | 0.00 |
July | 14365.02 | 20-JUL-03:02 | 0.00 | 370.84 | 3727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 0.00 |
August | 14830.63 | 14-AUG-03:02 | 0.00 | 370.84 | 3727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 4.49 | 0.00 |
September | 17093.21 | 03-SEP-14:22 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 59.85 | 0.00 |
October | 18135.31 | 08-OCT-13:42 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 120.46 | 0.00 |
November | 17435.09 | 05-NOV-14:43 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 |
December | 18762.01 | 10-DEC-14:32 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11532.35 | 0.00 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18762.01 | 1012.19 | 741.58 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 120.46 | 16.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7660.06 | 20-JAN-06:02 | 652.28 | 477.89 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.73 |
February | 8803.27 | 27-FEB-16:30 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 | 0.00 |
March | 12145.99 | 06-MAR-06:02 | 652.28 | 477.89 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 |
April | 16471.49 | 16-APR-16:31 | 456.59 | 159.19 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.87 |
May | 16955.44 | 28-MAY-18:02 | 0.00 | 113.70 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | 0.00 |
June | 16685.65 | 11-JUN-16:52 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 34.76 | 0.00 |
July | 17308.33 | 16-JUL-16:32 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 31.35 | 0.00 |
August | 16274.02 | 20-AUG-17:12 | 0.00 | 113.70 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 38.56 | 0.00 |
September | 17680.34 | 03-SEP-15:42 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 48.91 | 0.00 |
October | 17003.90 | 08-OCT-16:22 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 56.73 | 0.00 |
November | 11607.15 | 01-NOV-05:02 | 652.28 | 477.89 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 |
December | 11459.06 | 13-DEC-06:02 | 652.28 | 477.89 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7660.06 | 0.00 | 113.70 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17680.34 | 1239.33 | 477.89 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 56.73 | 102.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4399.37 | 31-JAN-16:00 | 1923.11 | 664.70 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 6.30 | 0.00 |
February | 5061.33 | 28-FEB-15:00 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 |
March | 6376.07 | 30-MAR-13:30 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 15.24 | 0.00 |
April | 10663.02 | 27-APR-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.23 |
May | 12722.48 | 22-MAY-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.24 |
June | 13452.12 | 17-JUN-03:02 | 0.00 | 370.83 | 2795.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 |
July | 15086.01 | 23-JUL-14:22 | 506.08 | 176.44 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 89.41 | 0.00 |
August | 13663.98 | 28-AUG-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 | 0.00 |
September | 15398.21 | 10-SEP-14:52 | 607.30 | 211.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.68 | 0.00 |
October | 11896.43 | 07-OCT-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 | 0.00 |
November | 11002.68 | 02-NOV-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 |
December | 5692.43 | 15-DEC-15:00 | 2010.79 | 679.27 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4399.37 | 0.00 | 176.44 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15398.21 | 2010.79 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 89.41 | 12.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5351.09 | 19-JAN-10:30 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 |
February | 5816.94 | 27-FEB-10:30 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.16 |
March | 8838.24 | 27-MAR-05:02 | 652.28 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 |
April | 16072.78 | 23-APR-11:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 |
May | 17053.15 | 29-MAY-10:42 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 11.81 | 0.00 |
June | 16293.50 | 11-JUN-08:53 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 6.81 | 0.00 |
July | 16360.45 | 16-JUL-08:32 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 15.89 | 0.00 |
August | 16198.98 | 27-AUG-10:23 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 28.35 | 0.00 |
September | 17013.45 | 03-SEP-09:42 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 | 0.00 |
October | 16224.40 | 09-OCT-09:23 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 0.00 |
November | 8041.49 | 01-NOV-05:02 | 652.28 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.19 |
December | 4437.97 | 16-DEC-10:10 | 409.21 | 136.43 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4437.97 | 260.91 | 90.96 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17053.15 | 1295.83 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.35 | 11.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21147.29 | 01-JAN-14:12 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.79 |
February | 19418.74 | 26-FEB-14:43 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.36 |
March | 13941.69 | 27-MAR-05:02 | 1012.19 | 741.58 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.65 |
April | 12994.91 | 27-APR-05:02 | 1012.19 | 741.58 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.28 |
May | 15235.59 | 22-MAY-03:02 | 0.00 | 370.84 | 3727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 |
June | 14622.82 | 28-JUN-03:02 | 0.00 | 370.84 | 3727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | 0.00 |
July | 18069.91 | 23-JUL-14:22 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 91.62 | 0.00 |
August | 18282.07 | 27-AUG-14:23 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 102.85 | 0.00 |
September | 20007.72 | 10-SEP-14:52 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 67.56 | 0.00 |
October | 20048.82 | 08-OCT-12:12 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 97.94 | 0.00 |
November | 20748.64 | 11-NOV-14:12 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.38 |
December | 21032.54 | 10-DEC-14:22 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12994.91 | 0.00 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21147.29 | 1012.19 | 741.58 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 102.85 | 52.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10097.47 | 01-JAN-16:12 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 |
February | 17831.90 | 26-FEB-17:22 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 |
March | 13117.07 | 27-MAR-05:02 | 652.28 | 477.89 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.79 |
April | 18107.17 | 23-APR-18:22 | 0.00 | 159.35 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.70 |
May | 18614.29 | 28-MAY-18:02 | 0.00 | 113.70 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 6.68 | 0.00 |
June | 18260.81 | 11-JUN-16:52 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 41.34 | 0.00 |
July | 18918.36 | 16-JUL-16:32 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 31.51 | 0.00 |
August | 17637.21 | 20-AUG-17:12 | 0.00 | 113.70 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 43.34 | 0.00 |
September | 19456.13 | 03-SEP-15:42 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 54.70 | 0.00 |
October | 17846.73 | 08-OCT-15:32 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 102.94 | 0.00 |
November | 14175.15 | 11-NOV-15:32 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 |
December | 10072.51 | 16-DEC-06:03 | 521.82 | 382.31 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10072.51 | 0.00 | 113.70 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19456.13 | 652.28 | 477.89 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 102.94 | 43.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9123.69 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 |
February | 5597.63 | 27-FEB-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 0.00 |
March | 5665.60 | 20-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 |
April | 5663.22 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 0.00 |
May | 6781.63 | 06-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.63 |
June | 6222.78 | 12-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.23 | 0.00 |
July | 7782.23 | 18-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
August | 8805.89 | 21-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.90 | 0.00 |
September | 9008.33 | 25-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.28 |
October | 7868.42 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.11 |
November | 7269.09 | 13-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.08 |
December | 6873.35 | 26-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5597.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9123.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 68.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4659.35 | 03-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.55 |
February | 4360.03 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.64 |
March | 4209.89 | 28-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.27 |
April | 4540.78 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.25 | 0.00 |
May | 6761.25 | 06-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.11 |
June | 7613.32 | 23-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 0.00 |
July | 6675.34 | 25-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.39 |
August | 6607.73 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
September | 5691.80 | 13-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.76 |
October | 7132.44 | 13-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.60 |
November | 4410.80 | 09-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.40 |
December | 4959.70 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4209.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7613.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.25 | 122.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8359.51 | 19-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.10 |
February | 10007.26 | 27-FEB-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
March | 10189.35 | 06-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 | 0.00 |
April | 15124.74 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.08 | 0.00 |
May | 16201.75 | 10-MAY-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.01 | 0.00 |
June | 17189.81 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.46 | 0.00 |
July | 17371.23 | 07-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.20 | 0.00 |
August | 16420.89 | 03-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.56 | 0.00 |
September | 15263.81 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.93 | 0.00 |
October | 15121.61 | 05-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.13 | 0.00 |
November | 11847.76 | 02-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 0.00 |
December | 9922.92 | 15-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8359.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17371.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.56 | 9.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2009.47 | 01-JAN-17:03 | 35.07 | 47.50 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4039.02 | 26-FEB-17:50 | 23.38 | 31.66 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7170.92 | 31-MAR-24:00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7829.21 | 16-APR-18:20 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3460.71 | 31-MAY-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5329.36 | 30-JUN-23:57 | 0.00 | 47.50 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7187.81 | 31-JUL-23:53 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7613.92 | 06-AUG-17:50 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3480.98 | 30-SEP-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5343.13 | 31-OCT-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5854.63 | 06-NOV-17:00 | 222.14 | 284.97 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7731.29 | 10-DEC-16:55 | 46.77 | 63.33 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2009.47 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7829.21 | 222.14 | 284.97 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1748.02 | 19-JAN-17:00 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3619.72 | 26-FEB-17:54 | 58.46 | 79.16 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6669.80 | 31-MAR-24:00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7350.88 | 16-APR-18:06 | 0.00 | 79.16 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3218.38 | 31-MAY-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5155.39 | 30-JUN-23:57 | 0.00 | 47.50 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6879.26 | 31-JUL-23:53 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7194.57 | 29-AUG-16:00 | 222.14 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3191.99 | 30-SEP-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4920.07 | 31-OCT-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5538.52 | 06-NOV-17:00 | 222.14 | 284.97 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7274.10 | 15-DEC-17:00 | 222.14 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1748.02 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7350.88 | 222.14 | 284.97 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1815.75 | 19-JAN-17:00 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3665.94 | 27-FEB-17:40 | 70.15 | 158.31 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6560.21 | 31-MAR-24:00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7461.95 | 23-APR-18:05 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3201.24 | 31-MAY-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5207.71 | 30-JUN-23:57 | 0.00 | 47.50 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6868.87 | 31-JUL-23:53 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7375.98 | 06-AUG-17:40 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3222.88 | 30-SEP-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4845.83 | 31-OCT-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5598.98 | 06-NOV-17:00 | 222.14 | 284.97 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7340.65 | 15-DEC-17:00 | 222.14 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1815.75 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7461.95 | 222.14 | 284.97 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92474.00 | 02-JAN-15:00 | 5027.92 | 3337.76 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182993.35 | 27-FEB-17:00 | 4808.68 | 3337.76 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358199.25 | 31-MAR-24:00 | 0.00 | 185.45 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 365498.39 | 28-APR-16:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175334.95 | 31-MAY-24:00 | 0.00 | 185.45 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 266978.84 | 30-JUN-23:53 | 0.00 | 556.35 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359207.51 | 31-JUL-24:00 | 0.00 | 556.35 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 367527.12 | 21-AUG-16:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176337.73 | 30-SEP-24:00 | 0.00 | 185.45 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268335.65 | 31-OCT-24:00 | 0.00 | 185.45 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275847.86 | 06-NOV-17:00 | 4808.68 | 3337.76 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367387.09 | 26-DEC-17:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92474.00 | 0.00 | 185.45 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 367527.12 | 5027.92 | 3337.76 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.137460E+13 | 1115397.53 | 19-JAN-16:40 | 0.862407E+11 | 383758.04 | 10-JAN-06:10 |
February | 0.163000E+13 | 1261970.19 | 24-FEB-16:00 | 0.644211E+11 | 429576.91 | 06-FEB-06:10 |
March | 0.223415E+13 | 1394676.56 | 07-MAR-16:30 | 0.681597E+11 | 279685.74 | 13-MAR-05:10 |
April | 0.259642E+13 | 1596566.80 | 28-APR-15:30 | 0.493187E+11 | 69661.08 | 04-APR-11:20 |
May | 0.170400E+13 | 1165012.66 | 17-MAY-15:30 | 0.493990E+11 | 66332.01 | 04-MAY-11:30 |
June | 0.207798E+13 | 1313862.97 | 21-JUN-15:09 | 0.465477E+11 | 62958.17 | 02-JUN-11:20 |
July | 0.251581E+13 | 1459751.42 | 07-JUL-15:00 | 0.446469E+11 | 60295.68 | 03-JUL-11:20 |
August | 0.295478E+13 | 1603116.60 | 30-AUG-15:50 | 0.476408E+11 | 61258.58 | 28-AUG-11:30 |
September | 0.165039E+13 | 1168797.95 | 12-SEP-15:30 | 0.456915E+11 | 64485.20 | 28-SEP-11:30 |
October | 0.204369E+13 | 1319544.77 | 05-OCT-15:20 | 0.494712E+11 | 67431.00 | 30-OCT-11:09 |
November | 0.220455E+13 | 1448812.47 | 02-NOV-15:20 | 0.518318E+11 | 88982.23 | 16-NOV-06:00 |
December | 0.255695E+13 | 1561732.69 | 12-DEC-16:40 | 0.746432E+11 | 393598.72 | 21-DEC-06:10 |
Annual Sum or Average | 0.255433E+14 | 0.678012E+12 | ||||
Minimum of Months | 0.137460E+13 | 1115397.53 | 0.446469E+11 | 60295.68 | ||
Maximum of Months | 0.295478E+13 | 1603116.60 | 0.862407E+11 | 429576.91 |
Report: EnergyConsumptionDistrictHeatingCoolingMonthly
For: Meter
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportDISTRICTCOOLING:FACILITY [J] | DISTRICTCOOLING:FACILITY {Maximum} [W] | DISTRICTCOOLING:FACILITY {TIMESTAMP} | DISTRICTHEATING:FACILITY [J] | DISTRICTHEATING:FACILITY {Maximum} [W] | DISTRICTHEATING:FACILITY {TIMESTAMP} | |
January | 0.241581E+12 | 95191.06 | 02-JAN-14:00 | 129712.56 | 8.47 | 22-JAN-18:40 |
February | 0.437700E+12 | 185592.44 | 27-FEB-16:00 | 159308.18 | 13.49 | 01-FEB-00:40 |
March | 0.729677E+12 | 358200.20 | 31-MAR-23:00 | 198363.82 | 11.22 | 24-MAR-23:30 |
April | 0.942087E+12 | 368097.36 | 28-APR-15:00 | 65877.68 | 10.68 | 01-APR-18:30 |
May | 0.241802E+12 | 175338.47 | 31-MAY-23:00 | 74777.54 | 13.56 | 31-MAY-23:40 |
June | 0.470191E+12 | 266978.92 | 30-JUN-23:00 | 40336.98 | 6.97 | 01-JUN-23:40 |
July | 0.732116E+12 | 359207.53 | 31-JUL-23:00 | 29556.01 | 4.51 | 03-JUL-23:19 |
August | 0.979368E+12 | 370154.94 | 21-AUG-13:00 | 69524.26 | 7.04 | 22-AUG-23:19 |
September | 0.237593E+12 | 176337.73 | 30-SEP-23:00 | 78127.48 | 4.88 | 11-SEP-23:40 |
October | 0.489519E+12 | 268337.49 | 31-OCT-23:00 | 83110.05 | 10.74 | 31-OCT-23:30 |
November | 0.710519E+12 | 278457.05 | 13-NOV-14:00 | 131452.39 | 11.26 | 11-NOV-00:30 |
December | 0.978665E+12 | 370011.12 | 26-DEC-14:00 | 131389.55 | 11.04 | 01-DEC-00:30 |
Annual Sum or Average | 0.719082E+13 | 1191536.52 | ||||
Minimum of Months | 0.237593E+12 | 95191.06 | 29556.01 | 4.51 | ||
Maximum of Months | 0.979368E+12 | 370154.94 | 198363.82 | 13.56 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.170576E+12 | 0.334121E+11 | 0.766053E+12 | 0.210403E+12 | 0.629730E+11 | 0.433396E+11 | 0.00 | 0.682829E+11 | 0.174793E+11 | 0.00 | 0.207811E+10 | 0.00 | 0.00 |
February | 0.153822E+12 | 0.279329E+11 | 0.978954E+12 | 0.233673E+12 | 0.582159E+11 | 0.498304E+11 | 0.00 | 0.995387E+11 | 0.252674E+11 | 0.00 | 0.276969E+10 | 0.00 | 0.00 |
March | 0.181942E+12 | 0.280724E+11 | 0.141687E+13 | 0.307234E+12 | 0.677570E+11 | 0.635811E+11 | 0.00 | 0.131830E+12 | 0.338939E+11 | 0.00 | 0.296392E+10 | 0.00 | 0.00 |
April | 0.161936E+12 | 0.244742E+11 | 0.165903E+13 | 0.343627E+12 | 0.705975E+11 | 0.847987E+11 | 0.00 | 0.194527E+12 | 0.523990E+11 | 0.00 | 0.503641E+10 | 0.00 | 0.00 |
May | 0.173911E+12 | 0.227784E+11 | 0.774844E+12 | 0.210552E+12 | 0.859212E+11 | 0.935084E+11 | 0.00 | 0.247313E+12 | 0.876133E+11 | 0.00 | 0.755798E+10 | 0.00 | 0.00 |
June | 0.172695E+12 | 0.207734E+11 | 0.106252E+13 | 0.250564E+12 | 0.878366E+11 | 0.101211E+12 | 0.00 | 0.279838E+12 | 0.949869E+11 | 0.00 | 0.755798E+10 | 0.00 | 0.00 |
July | 0.161929E+12 | 0.223257E+11 | 0.139340E+13 | 0.306990E+12 | 0.875252E+11 | 0.111285E+12 | 0.00 | 0.317380E+12 | 0.107794E+12 | 0.00 | 0.717402E+10 | 0.00 | 0.00 |
August | 0.180707E+12 | 0.242541E+11 | 0.173200E+13 | 0.355272E+12 | 0.931706E+11 | 0.115683E+12 | 0.00 | 0.339384E+12 | 0.106447E+12 | 0.00 | 0.786111E+10 | 0.00 | 0.00 |
September | 0.162229E+12 | 0.259141E+11 | 0.740713E+12 | 0.203664E+12 | 0.807260E+11 | 0.929113E+11 | 0.00 | 0.247038E+12 | 0.900191E+11 | 0.00 | 0.717402E+10 | 0.00 | 0.00 |
October | 0.169119E+12 | 0.295852E+11 | 0.108340E+13 | 0.258767E+12 | 0.847125E+11 | 0.935515E+11 | 0.00 | 0.240993E+12 | 0.776810E+11 | 0.00 | 0.587619E+10 | 0.00 | 0.00 |
November | 0.168466E+12 | 0.314578E+11 | 0.135889E+13 | 0.297145E+12 | 0.698724E+11 | 0.712876E+11 | 0.00 | 0.161825E+12 | 0.425619E+11 | 0.00 | 0.304082E+10 | 0.00 | 0.00 |
December | 0.165749E+12 | 0.341568E+11 | 0.170972E+13 | 0.355224E+12 | 0.664469E+11 | 0.574885E+11 | 0.00 | 0.131372E+12 | 0.340729E+11 | 0.00 | 0.272478E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.202308E+13 | 0.325137E+12 | 0.146764E+14 | 0.333312E+13 | 0.915755E+12 | 0.978476E+12 | 0.00 | 0.245932E+13 | 0.770216E+12 | 0.00 | 0.618150E+11 | 0.00 | 0.00 |
Minimum of Months | 0.153822E+12 | 0.207734E+11 | 0.740713E+12 | 0.203664E+12 | 0.582159E+11 | 0.433396E+11 | 0.00 | 0.682829E+11 | 0.174793E+11 | 0.00 | 0.207811E+10 | 0.00 | 0.00 |
Maximum of Months | 0.181942E+12 | 0.341568E+11 | 0.173200E+13 | 0.355272E+12 | 0.931706E+11 | 0.115683E+12 | 0.00 | 0.339384E+12 | 0.107794E+12 | 0.00 | 0.786111E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.315625E+11 | 0.00 | 0.546781E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.151100E+11 | 0.00 | 0.493111E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.127222E+11 | 0.00 | 0.554375E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.220578E+09 | 0.00 | 0.490981E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.493990E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.465477E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.446469E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.476408E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.456915E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 68803006.69 | 0.00 | 0.494024E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.122077E+10 | 0.00 | 0.506110E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.217880E+11 | 0.00 | 0.528552E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.826929E+11 | 0.00 | 0.595320E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.446469E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.315625E+11 | 0.00 | 0.554375E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 190416.39 | 31-JAN-08:09 | 37611.08 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 134893.45 | 31-JAN-08:20 | 72003.84 | 20-JAN-06:10 | 66102.39 | 19-JAN-16:40 | 0.00 | 01-JAN-00:10 |
February | 191913.68 | 01-FEB-08:09 | 37611.08 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 152926.79 | 01-FEB-08:20 | 68618.30 | 27-FEB-16:10 | 66233.55 | 24-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 189051.72 | 27-MAR-07:10 | 37611.08 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 170957.83 | 27-MAR-07:19 | 73800.64 | 28-MAR-05:10 | 66294.31 | 07-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 190287.35 | 14-APR-07:10 | 37611.08 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 188991.03 | 14-APR-07:19 | 86048.92 | 18-APR-14:50 | 66924.19 | 28-APR-15:30 | 0.00 | 01-APR-00:10 |
May | 181078.57 | 23-MAY-07:30 | 37611.08 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 134888.53 | 23-MAY-07:40 | 81094.74 | 17-MAY-05:10 | 66840.81 | 17-MAY-15:30 | 0.00 | 01-MAY-00:10 |
June | 174592.27 | 16-JUN-07:10 | 37611.08 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 152917.67 | 16-JUN-07:19 | 90421.80 | 28-JUN-05:10 | 67030.48 | 05-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 178031.58 | 14-JUL-07:10 | 37611.08 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 170952.03 | 14-JUL-07:19 | 84266.60 | 07-JUL-15:00 | 67901.08 | 12-JUL-15:39 | 0.00 | 01-JUL-00:10 |
August | 182181.15 | 21-AUG-07:10 | 37611.08 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 188986.76 | 21-AUG-07:19 | 91221.95 | 30-AUG-15:00 | 67214.20 | 29-AUG-14:50 | 0.00 | 01-AUG-00:10 |
September | 189033.85 | 26-SEP-07:10 | 37611.08 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 134892.72 | 26-SEP-07:19 | 83327.24 | 21-SEP-05:10 | 68241.86 | 14-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 193957.09 | 25-OCT-07:10 | 37611.08 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 152927.87 | 25-OCT-07:19 | 89940.32 | 05-OCT-15:30 | 67255.32 | 13-OCT-08:00 | 0.00 | 01-OCT-00:10 |
November | 191933.16 | 21-NOV-16:00 | 37611.08 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 170959.23 | 01-NOV-07:19 | 85419.87 | 01-NOV-05:10 | 66831.80 | 07-NOV-15:09 | 0.00 | 01-NOV-00:10 |
December | 193592.86 | 12-DEC-08:09 | 37611.08 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 188992.77 | 12-DEC-08:20 | 80391.49 | 12-DEC-06:10 | 66793.70 | 12-DEC-16:40 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 174592.27 | 37611.08 | 423497.50 | 134888.53 | 68618.30 | 66102.39 | 0.00 | |||||||
Maximum of Months | 193957.09 | 37611.08 | 778371.69 | 188992.77 | 91221.95 | 68241.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 232224.73 | 19-JAN-16:40 | 55581.51 | 19-JAN-10:30 | 0.00 | 5613.48 | 02-JAN-10:09 | 0.00 | 0.00 |
February | 241504.09 | 24-FEB-16:00 | 55581.51 | 24-FEB-10:50 | 0.00 | 5613.48 | 01-FEB-11:39 | 0.00 | 0.00 |
March | 251842.02 | 07-MAR-14:00 | 55581.51 | 06-MAR-12:00 | 0.00 | 5613.48 | 04-MAR-14:30 | 0.00 | 0.00 |
April | 285540.13 | 28-APR-15:30 | 55581.51 | 14-APR-10:20 | 0.00 | 5613.48 | 01-APR-06:10 | 0.00 | 0.00 |
May | 271054.35 | 26-MAY-10:50 | 55581.51 | 01-MAY-08:20 | 0.00 | 5613.48 | 01-MAY-06:10 | 0.00 | 0.00 |
June | 281748.60 | 19-JUN-10:39 | 55581.51 | 01-JUN-09:20 | 0.00 | 5613.48 | 01-JUN-06:10 | 0.00 | 0.00 |
July | 288992.84 | 03-JUL-09:00 | 55581.51 | 01-JUL-06:19 | 0.00 | 5613.48 | 01-JUL-06:10 | 0.00 | 0.00 |
August | 296302.86 | 17-AUG-14:09 | 55581.51 | 01-AUG-06:30 | 0.00 | 5613.48 | 01-AUG-06:10 | 0.00 | 0.00 |
September | 273471.42 | 18-SEP-10:09 | 55581.51 | 10-SEP-14:00 | 0.00 | 5613.48 | 01-SEP-06:10 | 0.00 | 0.00 |
October | 284269.29 | 06-OCT-11:00 | 55581.51 | 08-OCT-12:50 | 0.00 | 5613.48 | 02-OCT-08:50 | 0.00 | 0.00 |
November | 275919.73 | 02-NOV-14:50 | 55581.51 | 01-NOV-08:20 | 0.00 | 5613.48 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 264412.60 | 12-DEC-16:40 | 55581.51 | 11-DEC-14:50 | 0.00 | 5613.48 | 02-DEC-13:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232224.73 | 55581.51 | 0.00 | 5613.48 | 0.00 | 0.00 | |||
Maximum of Months | 296302.86 | 55581.51 | 0.00 | 5613.48 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1115397.53 | 19-JAN-16:40 | 172690.50 | 423497.50 | 0.00 | 100840.57 | 58846.85 | 66102.39 | 0.00 | 232224.73 | 55581.51 |
February | 1261970.19 | 24-FEB-16:00 | 172307.68 | 541788.89 | 0.00 | 118872.94 | 60068.06 | 66233.55 | 0.00 | 241504.09 | 55581.51 |
March | 1394676.56 | 07-MAR-16:30 | 171591.05 | 660080.29 | 0.00 | 136905.25 | 54633.02 | 66254.53 | 0.00 | 244017.43 | 55581.51 |
April | 1596566.80 | 28-APR-15:30 | 171235.93 | 778371.69 | 0.00 | 154937.61 | 78362.27 | 66924.19 | 0.00 | 285540.13 | 55581.51 |
May | 1165012.66 | 17-MAY-15:30 | 171235.93 | 423497.50 | 0.00 | 100839.97 | 77822.48 | 66840.81 | 0.00 | 263581.00 | 55581.51 |
June | 1313862.97 | 21-JUN-15:09 | 171235.93 | 541788.89 | 0.00 | 118872.52 | 73603.58 | 66902.12 | 0.00 | 280264.95 | 55581.51 |
July | 1459751.42 | 07-JUL-15:00 | 171235.93 | 660080.29 | 0.00 | 136905.07 | 84266.60 | 66893.47 | 0.00 | 279175.09 | 55581.51 |
August | 1603116.60 | 30-AUG-15:50 | 171235.93 | 778371.69 | 0.00 | 154937.61 | 90954.55 | 67029.98 | 0.00 | 279391.86 | 55581.51 |
September | 1168797.95 | 12-SEP-15:30 | 171235.93 | 423497.50 | 0.00 | 100839.97 | 77033.87 | 67046.46 | 0.00 | 267949.25 | 55581.51 |
October | 1319544.77 | 05-OCT-15:20 | 171235.93 | 541788.89 | 0.00 | 118872.52 | 89732.40 | 67153.38 | 0.00 | 269566.67 | 55581.51 |
November | 1448812.47 | 02-NOV-15:20 | 171818.25 | 660080.29 | 0.00 | 136905.09 | 76942.79 | 66816.90 | 0.00 | 275054.17 | 55581.51 |
December | 1561732.69 | 12-DEC-16:40 | 178460.80 | 778371.69 | 0.00 | 154940.77 | 57558.15 | 66793.70 | 0.00 | 264412.60 | 55581.51 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1115397.53 | 171235.93 | 423497.50 | 0.00 | 100839.97 | 54633.02 | 66102.39 | 0.00 | 232224.73 | 55581.51 | |
Maximum of Months | 1603116.60 | 178460.80 | 778371.69 | 0.00 | 154940.77 | 90954.55 | 67153.38 | 0.00 | 285540.13 | 55581.51 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 378062.17 | 10-JAN-06:10 | 0.00 | 73380.93 | 20-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 423881.04 | 06-FEB-06:10 | 0.00 | 73307.27 | 03-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 273064.66 | 11-MAR-06:10 | 0.00 | 72210.55 | 03-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 38936.57 | 03-APR-16:49 | 0.00 | 69661.08 | 04-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 66332.01 | 04-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 62958.17 | 02-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 60295.68 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 61258.58 | 28-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 64485.20 | 28-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 7310.77 | 28-OCT-06:49 | 0.00 | 67431.00 | 30-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 77275.55 | 16-NOV-06:10 | 0.00 | 70479.83 | 21-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 387902.85 | 21-DEC-06:10 | 0.00 | 72870.26 | 28-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 60295.68 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 423881.04 | 0.00 | 73380.93 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.75 | 0.00 | 26.75 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 26.69 | 0.00 | 26.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.99 | 0.00 | 25.99 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 26.00 | 0.00 | 26.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 25.79 | 0.17 | 25.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.73 | 0.00 | 25.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 26.10 | 0.00 | 26.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 26.07 | 0.00 | 26.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 26.67 | 1.17 | 26.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.54 | 0.00 | 26.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 26.92 | 0.67 | 26.94 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 26.88 | 0.33 | 26.89 |
Annual Sum or Average | 0.00 | 0.00 | 76.83 | 26.55 | 2.33 | 26.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.73 | 0.00 | 25.73 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 26.92 | 1.17 | 26.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.64 | 0.00 | 25.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 25.60 | 0.00 | 25.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.64 | 0.00 | 25.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.36 | 0.17 | 27.36 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.71 | 0.83 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.78 | 4.33 | 27.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.61 | 1.67 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.61 | 3.50 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.45 | 0.83 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.70 | 4.00 | 27.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.55 | 2.17 | 27.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.83 | 27.66 | 17.83 | 27.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.78 | 4.33 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.83 | 4.50 | 27.83 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.63 | 2.17 | 27.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.45 | 1.17 | 27.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.15 | 0.17 | 26.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.54 | 5.50 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.67 | 8.83 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.35 | 9.50 | 27.35 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.83 | 6.67 | 27.83 |
Annual Sum or Average | 0.00 | 0.00 | 39.83 | 27.58 | 38.50 | 27.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.83 | 9.50 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.55 | 0.83 | 27.55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.74 | 1.50 | 27.77 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.21 | 2.83 | 27.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 27.05 | 5.83 | 27.25 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.55 | 3.67 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 27.00 | 4.83 | 27.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 27.11 | 9.50 | 27.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 27.11 | 7.67 | 27.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.61 | 3.83 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.13 | 6.83 | 27.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.16 | 4.83 | 27.39 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.18 | 5.33 | 27.37 |
Annual Sum or Average | 0.00 | 0.00 | 154.50 | 27.16 | 57.50 | 27.34 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.00 | 0.83 | 27.17 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 27.74 | 9.50 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.86 | 1.00 | 27.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.78 | 5.33 | 27.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.70 | 2.50 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.76 | 5.00 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.54 | 2.83 | 27.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.75 | 4.50 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.59 | 2.33 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 23.50 | 27.72 | 23.50 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.86 | 5.33 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.58 | 4.67 | 27.58 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.76 | 1.67 | 27.76 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.35 | 0.83 | 27.35 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.60 | 5.33 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.81 | 8.00 | 27.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.49 | 13.17 | 26.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.86 | 5.50 | 27.86 |
Annual Sum or Average | 0.00 | 0.00 | 39.67 | 27.31 | 39.17 | 27.31 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.86 | 13.17 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.76 | 0.33 | 27.76 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.36 | 0.33 | 27.36 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.72 | 1.67 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.96 | 1.67 | 27.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.88 | 2.50 | 27.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.46 | 4.17 | 27.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.09 | 1.67 | 27.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.91 | 2.83 | 27.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.65 | 3.00 | 27.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 29.17 | 27.65 | 18.33 | 27.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.96 | 4.17 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
February | 2.00 | 19.08 | 0.67 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
March | 0.33 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.33 | 27.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.38 | 0.83 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.40 | 0.83 | 27.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
December | 0.50 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
Annual Sum or Average | 4.67 | 19.10 | 0.67 | 19.23 | 2.17 | 21.58 | 2.00 | 22.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 19.44 | 0.67 | 19.44 | 0.83 | 27.40 | 0.83 | 27.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
February | 0.83 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
March | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.78 | 1.17 | 27.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.81 | 8.17 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.60 | 7.17 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.67 | 9.17 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.60 | 6.33 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.75 | 8.00 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.52 | 4.17 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
Annual Sum or Average | 2.50 | 18.85 | 0.00 | 18.85 | 46.67 | 27.23 | 44.17 | 27.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.44 | 0.00 | 19.44 | 9.83 | 27.81 | 9.17 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.25 | 0.00 | 19.25 | 3.17 | 27.10 | 3.17 | 27.49 |
February | 0.33 | 18.78 | 0.00 | 18.78 | 1.50 | 26.12 | 1.50 | 26.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.41 | 1.17 | 27.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.36 | 0.83 | 27.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.42 | 3.00 | 27.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.77 | 6.67 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.89 | 8.50 | 27.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.02 | 7.83 | 27.02 |
December | 0.50 | 19.18 | 0.00 | 19.18 | 4.33 | 27.04 | 4.33 | 27.47 |
Annual Sum or Average | 1.17 | 19.08 | 0.00 | 19.08 | 39.83 | 27.38 | 37.00 | 27.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.25 | 0.00 | 19.25 | 9.83 | 27.89 | 8.50 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
February | 0.33 | 18.79 | 0.00 | 18.79 | 0.50 | 24.07 | 0.50 | 25.39 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.59 | 0.33 | 27.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.88 | 1.67 | 27.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.98 | 2.83 | 27.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.89 | 3.17 | 27.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.61 | 5.50 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.56 | 3.17 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.00 | 3.67 | 28.07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.84 | 3.67 | 27.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
December | 0.33 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
Annual Sum or Average | 1.17 | 19.02 | 0.00 | 19.02 | 40.00 | 27.55 | 24.67 | 27.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.02 | 0.00 | 19.02 |
Maximum of Months | 0.50 | 19.17 | 0.00 | 19.17 | 9.33 | 28.00 | 5.50 | 28.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.60 | 0.83 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 27.60 | 0.83 | 27.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.60 | 0.83 | 27.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 67.50 | 24.51 | 242.67 | 25.00 | 38.67 | 24.99 |
February | 84.33 | 24.60 | 309.83 | 24.74 | 62.83 | 24.75 |
March | 111.83 | 24.65 | 312.00 | 24.69 | 83.33 | 24.72 |
April | 177.50 | 24.84 | 431.33 | 24.67 | 176.50 | 24.71 |
May | 295.83 | 24.95 | 508.00 | 24.70 | 295.83 | 24.76 |
June | 264.17 | 24.94 | 496.00 | 24.65 | 264.17 | 24.72 |
July | 248.00 | 25.30 | 497.00 | 24.87 | 248.00 | 24.98 |
August | 188.17 | 25.47 | 514.00 | 24.79 | 188.17 | 24.94 |
September | 214.00 | 25.40 | 485.00 | 24.86 | 214.00 | 24.99 |
October | 162.67 | 25.69 | 454.50 | 24.99 | 162.67 | 25.14 |
November | 74.83 | 25.53 | 381.17 | 24.97 | 74.83 | 25.05 |
December | 62.50 | 25.16 | 316.00 | 25.04 | 56.33 | 25.07 |
Annual Sum or Average | 1951.33 | 25.12 | 4947.50 | 24.81 | 1865.33 | 24.89 |
Minimum of Months | 62.50 | 24.51 | 242.67 | 24.65 | 38.67 | 24.71 |
Maximum of Months | 295.83 | 25.69 | 514.00 | 25.04 | 295.83 | 25.14 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 145.17 | 23.43 | 163.83 | 24.03 | 0.00 | 24.03 |
February | 67.67 | 23.53 | 232.33 | 24.20 | 0.00 | 24.20 |
March | 59.50 | 23.59 | 268.67 | 24.22 | 0.00 | 24.22 |
April | 0.00 | 0.00 | 369.83 | 24.19 | 0.00 | 24.19 |
May | 1.00 | 23.28 | 404.83 | 24.22 | 0.00 | 24.22 |
June | 0.00 | 0.00 | 418.67 | 24.11 | 0.00 | 24.11 |
July | 0.00 | 0.00 | 457.50 | 24.10 | 0.00 | 24.10 |
August | 0.00 | 0.00 | 497.67 | 24.08 | 0.00 | 24.08 |
September | 0.00 | 0.00 | 410.00 | 24.20 | 0.00 | 24.20 |
October | 9.83 | 23.61 | 419.67 | 24.24 | 0.00 | 24.24 |
November | 5.17 | 23.76 | 355.17 | 24.35 | 0.00 | 24.35 |
December | 32.17 | 23.58 | 270.50 | 24.36 | 0.00 | 24.36 |
Annual Sum or Average | 320.50 | 23.51 | 4268.67 | 24.19 | 0.00 | 24.19 |
Minimum of Months | 0.00 | 0.00 | 163.83 | 24.03 | 0.00 | 24.03 |
Maximum of Months | 145.17 | 23.76 | 497.67 | 24.36 | 0.00 | 24.36 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 403.33 | 23.01 | 43.50 | 23.13 | 0.00 | 23.13 |
February | 290.33 | 23.06 | 92.83 | 23.33 | 0.00 | 23.33 |
March | 280.50 | 23.10 | 123.17 | 23.44 | 0.00 | 23.44 |
April | 125.33 | 23.20 | 220.50 | 23.93 | 0.00 | 23.93 |
May | 45.50 | 23.12 | 284.83 | 24.10 | 0.00 | 24.10 |
June | 44.50 | 23.12 | 274.17 | 24.07 | 0.00 | 24.07 |
July | 57.00 | 23.15 | 262.00 | 24.06 | 0.00 | 24.06 |
August | 32.00 | 23.13 | 295.33 | 24.13 | 0.00 | 24.13 |
September | 63.00 | 23.11 | 252.67 | 24.00 | 0.00 | 24.00 |
October | 66.50 | 23.19 | 249.67 | 24.06 | 0.00 | 24.06 |
November | 180.17 | 23.19 | 155.67 | 23.68 | 0.00 | 23.68 |
December | 305.17 | 23.04 | 92.33 | 23.33 | 0.00 | 23.33 |
Annual Sum or Average | 1893.33 | 23.09 | 2346.67 | 23.73 | 0.00 | 23.73 |
Minimum of Months | 32.00 | 23.01 | 43.50 | 23.13 | 0.00 | 23.13 |
Maximum of Months | 403.33 | 23.20 | 295.33 | 24.13 | 0.00 | 24.13 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 430.83 | 21.89 | 47.67 | 22.00 | 15.67 | 21.96 |
February | 347.67 | 22.19 | 83.00 | 22.35 | 20.83 | 22.24 |
March | 342.67 | 22.45 | 106.83 | 22.78 | 9.67 | 22.72 |
April | 160.17 | 23.10 | 201.33 | 23.76 | 0.00 | 23.76 |
May | 21.00 | 23.13 | 350.17 | 24.18 | 0.00 | 24.18 |
June | 7.83 | 23.25 | 349.00 | 24.18 | 0.00 | 24.18 |
July | 13.67 | 23.24 | 343.83 | 24.20 | 0.00 | 24.20 |
August | 15.67 | 23.26 | 363.83 | 24.20 | 0.00 | 24.20 |
September | 51.83 | 23.21 | 303.50 | 24.08 | 0.00 | 24.08 |
October | 86.00 | 22.95 | 268.17 | 23.95 | 0.00 | 23.95 |
November | 305.50 | 22.72 | 92.33 | 23.05 | 0.00 | 23.05 |
December | 404.67 | 22.21 | 69.33 | 22.40 | 12.33 | 22.35 |
Annual Sum or Average | 2187.50 | 22.40 | 2579.00 | 23.34 | 58.50 | 23.30 |
Minimum of Months | 7.83 | 21.89 | 47.67 | 22.00 | 0.00 | 21.96 |
Maximum of Months | 430.83 | 23.26 | 363.83 | 24.20 | 20.83 | 24.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 360.17 | 22.56 | 81.83 | 22.87 | 0.00 | 22.87 |
February | 241.17 | 22.82 | 127.00 | 23.28 | 1.67 | 23.27 |
March | 233.33 | 23.10 | 182.00 | 23.61 | 0.00 | 23.61 |
April | 41.67 | 23.44 | 322.33 | 24.11 | 0.00 | 24.11 |
May | 0.67 | 26.39 | 503.83 | 24.37 | 0.67 | 24.37 |
June | 0.00 | 0.00 | 490.67 | 24.32 | 0.00 | 24.32 |
July | 0.50 | 26.96 | 495.17 | 24.39 | 0.50 | 24.40 |
August | 0.00 | 0.00 | 513.83 | 24.27 | 0.00 | 24.27 |
September | 0.00 | 0.00 | 460.83 | 24.36 | 0.00 | 24.36 |
October | 33.67 | 23.41 | 410.17 | 24.28 | 0.00 | 24.28 |
November | 145.83 | 23.38 | 216.33 | 23.88 | 0.00 | 23.88 |
December | 249.67 | 22.99 | 142.00 | 23.42 | 0.00 | 23.42 |
Annual Sum or Average | 1306.67 | 22.93 | 3946.00 | 23.96 | 2.83 | 23.96 |
Minimum of Months | 0.00 | 0.00 | 81.83 | 22.87 | 0.00 | 22.87 |
Maximum of Months | 360.17 | 26.96 | 513.83 | 24.39 | 1.67 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 311.33 | 22.73 | 104.67 | 23.18 | 0.83 | 23.19 |
February | 212.50 | 22.85 | 142.83 | 23.45 | 1.33 | 23.44 |
March | 198.33 | 22.78 | 203.83 | 23.59 | 1.17 | 23.60 |
April | 72.67 | 23.29 | 309.33 | 24.06 | 3.67 | 24.09 |
May | 22.17 | 26.74 | 484.00 | 24.55 | 21.17 | 24.65 |
June | 8.17 | 26.40 | 478.50 | 24.37 | 7.00 | 24.41 |
July | 15.00 | 26.74 | 477.17 | 24.48 | 14.50 | 24.54 |
August | 6.17 | 26.54 | 480.67 | 24.28 | 5.67 | 24.31 |
September | 21.33 | 26.71 | 430.50 | 24.58 | 20.33 | 24.68 |
October | 48.17 | 24.10 | 392.17 | 24.39 | 11.50 | 24.45 |
November | 140.67 | 23.19 | 234.83 | 23.92 | 1.00 | 23.93 |
December | 259.33 | 22.73 | 129.33 | 23.25 | 0.00 | 23.25 |
Annual Sum or Average | 1315.83 | 23.11 | 3867.83 | 24.05 | 88.17 | 24.10 |
Minimum of Months | 6.17 | 22.73 | 104.67 | 23.18 | 0.00 | 23.19 |
Maximum of Months | 311.33 | 26.74 | 484.00 | 24.58 | 21.17 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 195.17 | 23.23 | 186.83 | 23.97 | 16.00 | 24.09 |
February | 124.33 | 23.15 | 250.00 | 24.03 | 9.33 | 24.06 |
March | 167.33 | 23.00 | 240.50 | 23.83 | 4.00 | 23.86 |
April | 36.17 | 23.35 | 349.83 | 24.20 | 0.00 | 24.20 |
May | 0.67 | 26.25 | 504.83 | 24.37 | 0.67 | 24.37 |
June | 0.00 | 0.00 | 486.17 | 24.31 | 0.00 | 24.31 |
July | 0.50 | 27.02 | 492.17 | 24.39 | 0.50 | 24.39 |
August | 3.83 | 27.00 | 513.00 | 24.34 | 3.83 | 24.36 |
September | 25.67 | 26.86 | 472.33 | 24.60 | 25.67 | 24.71 |
October | 49.33 | 25.98 | 452.17 | 24.72 | 36.00 | 24.86 |
November | 68.00 | 24.69 | 365.67 | 24.62 | 24.67 | 24.75 |
December | 144.00 | 23.48 | 275.67 | 24.25 | 18.67 | 24.38 |
Annual Sum or Average | 815.00 | 23.64 | 4589.17 | 24.32 | 139.33 | 24.39 |
Minimum of Months | 0.00 | 0.00 | 186.83 | 23.83 | 0.00 | 23.86 |
Maximum of Months | 195.17 | 27.02 | 513.00 | 24.72 | 36.00 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 231.50 | 22.94 | 186.83 | 23.65 | 3.33 | 23.67 |
February | 93.83 | 23.39 | 296.00 | 24.27 | 5.67 | 24.31 |
March | 56.67 | 23.96 | 359.00 | 24.50 | 10.50 | 24.56 |
April | 28.33 | 26.93 | 467.50 | 24.75 | 28.33 | 24.86 |
May | 18.17 | 26.90 | 508.00 | 24.59 | 18.17 | 24.67 |
June | 26.00 | 26.94 | 496.00 | 24.63 | 26.00 | 24.74 |
July | 52.83 | 26.83 | 497.00 | 24.85 | 52.83 | 25.02 |
August | 47.83 | 26.82 | 514.00 | 24.73 | 47.83 | 24.89 |
September | 22.83 | 26.93 | 485.00 | 24.63 | 22.83 | 24.73 |
October | 32.17 | 26.37 | 469.00 | 24.74 | 27.00 | 24.85 |
November | 25.17 | 25.55 | 419.83 | 24.68 | 14.67 | 24.75 |
December | 52.00 | 24.64 | 343.00 | 24.78 | 17.33 | 24.87 |
Annual Sum or Average | 687.33 | 24.59 | 5041.17 | 24.59 | 274.50 | 24.69 |
Minimum of Months | 18.17 | 22.94 | 186.83 | 23.65 | 3.33 | 23.67 |
Maximum of Months | 231.50 | 26.94 | 514.00 | 24.85 | 52.83 | 25.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 462.50 | 21.60 | 68.33 | 21.59 | 50.67 | 21.50 |
February | 384.83 | 21.96 | 77.17 | 21.97 | 40.33 | 21.83 |
March | 389.17 | 22.28 | 90.67 | 22.47 | 19.50 | 22.39 |
April | 181.17 | 23.16 | 208.00 | 23.74 | 4.50 | 23.77 |
May | 9.67 | 26.20 | 488.00 | 24.37 | 9.67 | 24.40 |
June | 1.00 | 23.37 | 486.17 | 24.34 | 0.00 | 24.34 |
July | 3.83 | 26.16 | 481.17 | 24.46 | 3.83 | 24.47 |
August | 0.00 | 0.00 | 490.50 | 24.34 | 0.00 | 24.34 |
September | 10.50 | 24.63 | 402.50 | 24.34 | 6.50 | 24.36 |
October | 94.83 | 23.19 | 336.17 | 24.08 | 9.00 | 24.11 |
November | 326.67 | 22.53 | 80.00 | 22.84 | 0.00 | 22.84 |
December | 416.67 | 21.89 | 68.33 | 22.02 | 24.67 | 21.95 |
Annual Sum or Average | 2280.83 | 22.19 | 3277.00 | 23.36 | 168.67 | 23.30 |
Minimum of Months | 0.00 | 0.00 | 68.33 | 21.59 | 0.00 | 21.50 |
Maximum of Months | 462.50 | 26.20 | 490.50 | 24.46 | 50.67 | 24.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 373.67 | 21.97 | 52.67 | 22.12 | 18.33 | 22.06 |
February | 284.17 | 22.23 | 73.83 | 22.51 | 13.00 | 22.43 |
March | 252.00 | 22.35 | 126.50 | 22.98 | 9.17 | 22.92 |
April | 106.83 | 23.31 | 230.67 | 24.16 | 9.50 | 24.23 |
May | 36.50 | 26.71 | 404.33 | 24.75 | 36.17 | 24.90 |
June | 17.50 | 26.58 | 404.67 | 24.60 | 16.17 | 24.68 |
July | 34.17 | 26.77 | 402.00 | 24.83 | 33.83 | 24.97 |
August | 17.00 | 26.73 | 404.83 | 24.60 | 16.50 | 24.68 |
September | 39.33 | 25.88 | 335.00 | 24.74 | 30.00 | 24.88 |
October | 90.33 | 23.87 | 295.33 | 24.43 | 24.17 | 24.56 |
November | 213.33 | 22.73 | 120.00 | 23.36 | 0.50 | 23.37 |
December | 324.83 | 22.07 | 71.50 | 22.33 | 16.83 | 22.26 |
Annual Sum or Average | 1789.67 | 22.72 | 2921.33 | 23.81 | 224.17 | 23.87 |
Minimum of Months | 17.00 | 21.97 | 52.67 | 22.12 | 0.50 | 22.06 |
Maximum of Months | 373.67 | 26.77 | 404.83 | 24.83 | 36.17 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 237.50 | 22.87 | 157.67 | 23.62 | 16.83 | 23.73 |
February | 178.50 | 22.80 | 200.67 | 23.64 | 13.33 | 23.64 |
March | 224.67 | 22.56 | 187.00 | 23.33 | 8.00 | 23.29 |
April | 105.50 | 23.30 | 284.33 | 24.10 | 4.67 | 24.12 |
May | 9.67 | 26.19 | 480.33 | 24.39 | 9.67 | 24.42 |
June | 1.00 | 23.36 | 476.33 | 24.33 | 0.00 | 24.33 |
July | 3.83 | 26.07 | 476.50 | 24.45 | 3.83 | 24.46 |
August | 0.67 | 26.95 | 498.00 | 24.39 | 0.67 | 24.40 |
September | 32.17 | 26.50 | 450.00 | 24.62 | 30.83 | 24.74 |
October | 69.67 | 25.51 | 440.50 | 24.73 | 43.83 | 24.89 |
November | 111.50 | 24.01 | 315.17 | 24.48 | 24.17 | 24.62 |
December | 203.17 | 22.93 | 232.00 | 23.88 | 19.33 | 23.98 |
Annual Sum or Average | 1177.83 | 23.25 | 4198.50 | 24.20 | 175.17 | 24.26 |
Minimum of Months | 0.67 | 22.56 | 157.67 | 23.33 | 0.00 | 23.29 |
Maximum of Months | 237.50 | 26.95 | 498.00 | 24.73 | 43.83 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 383.00 | 22.05 | 73.83 | 22.34 | 10.83 | 22.31 |
February | 279.50 | 22.29 | 127.33 | 22.79 | 16.00 | 22.72 |
March | 266.50 | 22.43 | 164.67 | 23.14 | 7.83 | 23.11 |
April | 89.17 | 23.73 | 330.50 | 24.34 | 14.17 | 24.42 |
May | 19.17 | 26.70 | 497.83 | 24.53 | 19.17 | 24.61 |
June | 15.17 | 26.89 | 491.50 | 24.54 | 15.17 | 24.61 |
July | 27.50 | 26.80 | 488.00 | 24.69 | 27.50 | 24.80 |
August | 12.67 | 26.80 | 509.17 | 24.52 | 12.67 | 24.58 |
September | 24.33 | 26.29 | 441.33 | 24.57 | 21.67 | 24.66 |
October | 64.33 | 24.33 | 411.50 | 24.46 | 23.00 | 24.55 |
November | 218.17 | 22.83 | 181.67 | 23.52 | 1.50 | 23.53 |
December | 310.33 | 22.18 | 131.17 | 22.80 | 6.00 | 22.78 |
Annual Sum or Average | 1709.83 | 22.71 | 3848.50 | 23.90 | 175.50 | 23.95 |
Minimum of Months | 12.67 | 22.05 | 73.83 | 22.34 | 1.50 | 22.31 |
Maximum of Months | 383.00 | 26.89 | 509.17 | 24.69 | 27.50 | 24.80 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.33 | 21.17 | 183.00 | 21.03 | 167.33 | 20.89 |
February | 397.67 | 21.51 | 126.83 | 21.41 | 91.50 | 21.20 |
March | 402.67 | 21.86 | 135.33 | 21.95 | 65.83 | 21.77 |
April | 208.17 | 22.87 | 203.83 | 23.56 | 7.83 | 23.60 |
May | 12.50 | 26.24 | 480.33 | 24.44 | 12.50 | 24.48 |
June | 6.83 | 25.60 | 485.50 | 24.42 | 4.67 | 24.44 |
July | 14.17 | 26.33 | 480.33 | 24.56 | 13.17 | 24.61 |
August | 7.83 | 25.65 | 487.83 | 24.41 | 5.67 | 24.43 |
September | 28.67 | 24.35 | 407.00 | 24.39 | 11.50 | 24.43 |
October | 112.00 | 22.85 | 332.83 | 23.98 | 10.17 | 24.02 |
November | 362.67 | 22.02 | 93.33 | 22.29 | 20.67 | 22.21 |
December | 430.83 | 21.44 | 153.50 | 21.43 | 115.33 | 21.28 |
Annual Sum or Average | 2450.33 | 21.85 | 3569.67 | 23.04 | 526.17 | 22.88 |
Minimum of Months | 6.83 | 21.17 | 93.33 | 21.03 | 4.67 | 20.89 |
Maximum of Months | 466.33 | 26.33 | 487.83 | 24.56 | 167.33 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 444.50 | 21.48 | 133.17 | 21.50 | 94.33 | 21.34 |
February | 346.67 | 21.83 | 121.33 | 21.98 | 48.17 | 21.78 |
March | 297.33 | 21.99 | 190.00 | 22.60 | 39.83 | 22.44 |
April | 126.83 | 23.11 | 292.83 | 24.03 | 14.17 | 24.11 |
May | 48.00 | 26.61 | 480.67 | 24.70 | 46.33 | 24.87 |
June | 33.83 | 26.49 | 484.67 | 24.60 | 31.00 | 24.72 |
July | 55.50 | 26.57 | 478.17 | 24.80 | 52.67 | 24.98 |
August | 37.33 | 26.33 | 487.17 | 24.59 | 33.00 | 24.72 |
September | 63.83 | 25.67 | 416.00 | 24.68 | 45.17 | 24.85 |
October | 115.50 | 23.68 | 362.00 | 24.32 | 32.00 | 24.46 |
November | 291.33 | 22.43 | 135.33 | 22.96 | 8.00 | 22.92 |
December | 394.33 | 21.67 | 133.33 | 21.83 | 70.83 | 21.69 |
Annual Sum or Average | 2255.00 | 22.47 | 3714.67 | 23.54 | 515.50 | 23.54 |
Minimum of Months | 33.83 | 21.48 | 121.33 | 21.50 | 8.00 | 21.34 |
Maximum of Months | 444.50 | 26.61 | 487.17 | 24.80 | 94.33 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 289.00 | 22.32 | 158.00 | 22.88 | 47.00 | 22.82 |
February | 226.67 | 22.27 | 193.67 | 23.02 | 31.33 | 22.90 |
March | 264.33 | 22.15 | 202.00 | 22.79 | 42.00 | 22.64 |
April | 140.83 | 23.03 | 271.67 | 23.93 | 9.00 | 23.98 |
May | 15.50 | 26.34 | 472.50 | 24.47 | 15.50 | 24.53 |
June | 6.17 | 25.05 | 475.17 | 24.39 | 3.17 | 24.41 |
July | 16.33 | 25.90 | 476.83 | 24.54 | 13.17 | 24.59 |
August | 20.67 | 26.43 | 495.00 | 24.52 | 19.33 | 24.59 |
September | 43.00 | 26.27 | 443.17 | 24.67 | 37.67 | 24.82 |
October | 82.67 | 25.03 | 431.33 | 24.67 | 46.33 | 24.85 |
November | 155.67 | 23.24 | 273.17 | 24.12 | 18.67 | 24.23 |
December | 251.17 | 22.39 | 224.50 | 23.25 | 44.17 | 23.22 |
Annual Sum or Average | 1512.00 | 22.86 | 4117.00 | 23.97 | 327.33 | 23.98 |
Minimum of Months | 6.17 | 22.15 | 158.00 | 22.79 | 3.17 | 22.64 |
Maximum of Months | 289.00 | 26.43 | 495.00 | 24.67 | 47.00 | 24.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.67 | 21.63 | 124.17 | 21.75 | 73.50 | 21.62 |
February | 317.17 | 21.83 | 141.17 | 22.14 | 51.50 | 21.95 |
March | 301.00 | 21.98 | 178.33 | 22.57 | 37.83 | 22.43 |
April | 132.50 | 23.32 | 292.50 | 24.14 | 18.17 | 24.25 |
May | 24.67 | 26.61 | 480.00 | 24.58 | 24.33 | 24.67 |
June | 21.50 | 26.39 | 483.17 | 24.56 | 18.67 | 24.65 |
July | 38.50 | 26.50 | 483.50 | 24.72 | 36.00 | 24.85 |
August | 21.33 | 26.62 | 501.17 | 24.58 | 20.17 | 24.66 |
September | 40.50 | 25.53 | 425.50 | 24.59 | 27.33 | 24.71 |
October | 86.50 | 23.81 | 388.83 | 24.36 | 25.67 | 24.47 |
November | 273.17 | 22.32 | 149.17 | 23.02 | 3.50 | 23.02 |
December | 349.50 | 21.73 | 149.00 | 22.16 | 51.67 | 22.04 |
Annual Sum or Average | 2021.00 | 22.36 | 3796.50 | 23.60 | 388.33 | 23.58 |
Minimum of Months | 21.33 | 21.63 | 124.17 | 21.75 | 3.50 | 21.62 |
Maximum of Months | 414.67 | 26.62 | 501.17 | 24.72 | 73.50 | 24.85 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 27.00 | 502.00 | 27.00 | 0.67 | 27.00 |
February | 5.00 | 27.00 | 454.00 | 27.00 | 5.00 | 27.00 |
March | 9.50 | 27.00 | 514.00 | 27.00 | 9.50 | 27.00 |
April | 145.33 | 27.00 | 485.00 | 27.00 | 145.33 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 18.50 | 27.00 | 496.00 | 27.00 | 18.50 | 27.00 |
July | 163.00 | 27.00 | 497.00 | 27.00 | 163.00 | 27.00 |
August | 339.50 | 27.02 | 514.00 | 27.01 | 339.50 | 27.01 |
September | 3.00 | 27.00 | 485.00 | 27.00 | 3.00 | 27.00 |
October | 35.00 | 27.00 | 502.00 | 27.00 | 35.00 | 27.00 |
November | 41.50 | 27.00 | 489.00 | 27.00 | 41.50 | 27.00 |
December | 87.83 | 27.00 | 497.00 | 27.00 | 87.83 | 27.00 |
Annual Sum or Average | 848.83 | 27.01 | 5943.00 | 27.00 | 848.83 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 339.50 | 27.02 | 514.00 | 27.01 | 339.50 | 27.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 0.50 | 27.17 | 485.00 | 27.00 | 0.50 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 0.00 | 0.00 | 496.00 | 27.00 | 0.00 | 27.00 |
July | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
August | 16.00 | 27.31 | 514.00 | 27.03 | 16.00 | 27.03 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
November | 0.17 | 27.00 | 489.00 | 27.00 | 0.17 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 16.67 | 27.30 | 5943.00 | 27.00 | 16.67 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 16.00 | 27.31 | 514.00 | 27.03 | 16.00 | 27.03 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.67 | 26.05 | 464.00 | 26.98 | 0.00 | 26.98 |
February | 5.50 | 27.00 | 430.67 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 506.33 | 27.00 | 0.00 | 27.00 |
April | 11.00 | 27.01 | 485.00 | 27.00 | 11.00 | 27.00 |
May | 1.83 | 27.00 | 508.00 | 27.00 | 1.83 | 27.00 |
June | 6.83 | 27.00 | 496.00 | 27.00 | 6.83 | 27.00 |
July | 22.83 | 27.00 | 497.00 | 27.00 | 22.83 | 27.00 |
August | 58.00 | 27.07 | 514.00 | 27.01 | 58.00 | 27.02 |
September | 3.50 | 27.00 | 485.00 | 27.00 | 3.50 | 27.00 |
October | 3.33 | 27.00 | 502.00 | 27.00 | 3.33 | 27.00 |
November | 1.17 | 27.00 | 489.00 | 27.00 | 1.17 | 27.00 |
December | 2.17 | 27.00 | 488.83 | 27.00 | 2.17 | 27.00 |
Annual Sum or Average | 124.83 | 26.97 | 5865.83 | 27.00 | 110.67 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 430.67 | 26.98 | 0.00 | 26.98 |
Maximum of Months | 58.00 | 27.07 | 514.00 | 27.01 | 58.00 | 27.02 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5943.00 | 27.00 | 5943.00 | 27.00 | 5943.00 | 27.00 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00017 | 32.32239 | 0.86730 | 21.01415 |
February | 454.00000 | 27.00096 | 33.38689 | 0.92292 | 23.10301 |
March | 514.00000 | 27.00060 | 33.57482 | 0.96114 | 24.57889 |
April | 485.00000 | 27.00047 | 35.90929 | 1.02796 | 27.33590 |
May | 508.00000 | 27.00026 | 41.97198 | 0.32225 | 7.19660 |
June | 496.00000 | 27.00238 | 40.13716 | 0.35652 | 7.67574 |
July | 497.00000 | 27.00154 | 39.22439 | 0.39715 | 8.31265 |
August | 514.00000 | 27.01056 | 38.47022 | 0.43922 | 9.05683 |
September | 485.00000 | 27.00017 | 42.38311 | 0.32808 | 7.28046 |
October | 502.00000 | 27.00186 | 38.03631 | 0.99608 | 25.99764 |
November | 489.00000 | 27.00072 | 35.04243 | 0.98968 | 25.73026 |
December | 497.00000 | 27.00020 | 33.14069 | 0.99189 | 25.84788 |
Annual Sum or Average | 5943.00000 | 27.00169 | 36.98665 | 0.71458 | 17.69970 |
Minimum of Months | 454.00000 | 27.00017 | 32.32239 | 0.32225 | 7.19660 |
Maximum of Months | 514.00000 | 27.01056 | 42.38311 | 1.02796 | 27.33590 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00010 | 32.51564 | 0.77674 | 17.90524 |
February | 454.00000 | 27.00091 | 33.44975 | 0.82014 | 19.38889 |
March | 514.00000 | 27.00055 | 33.56145 | 0.85097 | 20.40855 |
April | 485.00000 | 27.00065 | 35.87030 | 0.93081 | 23.34313 |
May | 508.00000 | 27.00014 | 42.25037 | 0.26926 | 6.55327 |
June | 496.00000 | 27.00226 | 40.23254 | 0.28121 | 6.68039 |
July | 497.00000 | 27.00146 | 39.25715 | 0.29560 | 6.84911 |
August | 514.00000 | 27.01686 | 38.45726 | 0.31858 | 7.15989 |
September | 485.00000 | 27.00010 | 42.78995 | 0.26527 | 6.51600 |
October | 502.00000 | 27.00177 | 38.12067 | 0.93132 | 23.38737 |
November | 489.00000 | 27.00067 | 35.02999 | 0.88220 | 21.51322 |
December | 497.00000 | 27.00020 | 33.09665 | 0.84621 | 20.26181 |
Annual Sum or Average | 5943.00000 | 27.00219 | 37.07244 | 0.62026 | 14.94530 |
Minimum of Months | 454.00000 | 27.00010 | 32.51564 | 0.26527 | 6.51600 |
Maximum of Months | 514.00000 | 27.01686 | 42.78995 | 0.93132 | 23.38737 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.96404 | 32.67272 | 0.71816 | 16.27884 |
February | 454.00000 | 27.00092 | 33.52190 | 0.77887 | 18.17017 |
March | 514.00000 | 27.00058 | 33.59604 | 0.82053 | 19.46733 |
April | 485.00000 | 27.00049 | 35.90196 | 0.92661 | 23.23577 |
May | 508.00000 | 27.00023 | 42.13121 | 0.28987 | 6.82890 |
June | 496.00000 | 27.00239 | 40.19954 | 0.30794 | 7.04561 |
July | 497.00000 | 27.00156 | 39.26242 | 0.32203 | 7.22579 |
August | 514.00000 | 27.00837 | 38.48488 | 0.34055 | 7.49377 |
September | 485.00000 | 27.00011 | 42.69665 | 0.28032 | 6.72448 |
October | 502.00000 | 27.00183 | 38.12539 | 0.93303 | 23.51889 |
November | 489.00000 | 27.00070 | 35.07564 | 0.84957 | 20.40563 |
December | 497.00000 | 27.00023 | 33.13825 | 0.79729 | 18.68742 |
Annual Sum or Average | 5943.00000 | 26.99844 | 37.08670 | 0.61188 | 14.54440 |
Minimum of Months | 454.00000 | 26.96404 | 32.67272 | 0.28032 | 6.72448 |
Maximum of Months | 514.00000 | 27.00837 | 42.69665 | 0.93303 | 23.51889 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 41.12180 | 1.15862 | 33.25791 |
February | 454.00000 | 27.00000 | 40.91397 | 1.30096 | 40.32110 |
March | 514.00000 | 27.00000 | 40.81080 | 1.43623 | 47.45321 |
April | 485.00000 | 27.00000 | 40.76072 | 1.56650 | 54.52038 |
May | 508.00000 | 27.00000 | 40.96818 | 0.55859 | 11.56118 |
June | 496.00000 | 27.00000 | 40.77820 | 0.77399 | 17.63039 |
July | 497.00000 | 27.00000 | 40.77875 | 0.98995 | 25.70654 |
August | 514.00000 | 27.00000 | 40.77244 | 1.20102 | 35.30160 |
September | 485.00000 | 27.00000 | 40.92490 | 0.61759 | 13.02938 |
October | 502.00000 | 27.00000 | 40.87611 | 1.34167 | 42.43218 |
November | 489.00000 | 27.00000 | 40.85137 | 1.47590 | 49.59360 |
December | 497.00000 | 27.00000 | 40.88121 | 1.59723 | 56.19421 |
Annual Sum or Average | 5943.00000 | 27.00000 | 40.86965 | 1.16706 | 35.53315 |
Minimum of Months | 454.00000 | 27.00000 | 40.76072 | 0.55859 | 11.56118 |
Maximum of Months | 514.00000 | 27.00000 | 41.12180 | 1.59723 | 56.19421 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.58370 | 37.95974 | 0.48807 | 10.84236 |
February | 454.00000 | 24.55821 | 46.28585 | 0.53778 | 11.83523 |
March | 514.00000 | 24.45640 | 45.29980 | 0.50934 | 11.17078 |
April | 485.00000 | 24.54269 | 57.01624 | 0.61094 | 13.54888 |
May | 508.00000 | 24.55133 | 65.15417 | -0.1775 | 6.96715 |
June | 496.00000 | 24.49839 | 64.61808 | -0.1944 | 6.85436 |
July | 497.00000 | 24.65108 | 64.17743 | -0.1402 | 7.08164 |
August | 514.00000 | 24.54897 | 62.00863 | -0.1715 | 7.03155 |
September | 485.00000 | 24.62185 | 62.70409 | -0.1508 | 7.11354 |
October | 502.00000 | 24.67419 | 57.25529 | 0.66570 | 15.52567 |
November | 489.00000 | 24.67428 | 47.77258 | 0.59434 | 13.33379 |
December | 497.00000 | 24.65947 | 42.86751 | 0.55088 | 12.39234 |
Annual Sum or Average | 5943.00000 | 24.58469 | 54.47478 | 0.25716 | 10.28522 |
Minimum of Months | 454.00000 | 24.45640 | 37.95974 | -0.1944 | 6.85436 |
Maximum of Months | 514.00000 | 24.67428 | 65.15417 | 0.66570 | 15.52567 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.04208 | 38.07606 | 0.37160 | 8.39551 |
February | 454.00000 | 24.13334 | 41.78295 | 0.42451 | 9.20630 |
March | 514.00000 | 24.11954 | 41.02161 | 0.42492 | 9.09546 |
April | 485.00000 | 24.10994 | 46.37808 | 0.47147 | 9.78892 |
May | 508.00000 | 24.10802 | 49.34900 | -0.3917 | 8.51365 |
June | 496.00000 | 24.04402 | 49.26503 | -0.4035 | 8.53812 |
July | 497.00000 | 24.07126 | 48.95633 | -0.3888 | 8.24890 |
August | 514.00000 | 24.07151 | 48.91499 | -0.3786 | 8.04376 |
September | 485.00000 | 24.11494 | 49.23430 | -0.3861 | 8.41014 |
October | 502.00000 | 24.18783 | 46.71460 | 0.49406 | 10.31214 |
November | 489.00000 | 24.24742 | 43.39671 | 0.48145 | 10.14058 |
December | 497.00000 | 24.20608 | 40.03137 | 0.44381 | 9.47068 |
Annual Sum or Average | 5943.00000 | 24.12094 | 45.27787 | 0.09358 | 9.00761 |
Minimum of Months | 454.00000 | 24.04208 | 38.07606 | -0.4035 | 8.04376 |
Maximum of Months | 514.00000 | 24.24742 | 49.34900 | 0.49406 | 10.31214 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.20435 | 40.77675 | 0.15506 | 6.19790 |
February | 454.00000 | 23.40864 | 44.44211 | 0.23289 | 6.88348 |
March | 514.00000 | 23.54443 | 43.55958 | 0.26773 | 7.13791 |
April | 485.00000 | 23.87399 | 48.16664 | 0.39009 | 8.49344 |
May | 508.00000 | 23.91986 | 50.34276 | -0.4735 | 10.11907 |
June | 496.00000 | 23.89417 | 50.30397 | -0.4798 | 10.20158 |
July | 497.00000 | 23.89056 | 50.28507 | -0.4828 | 10.30011 |
August | 514.00000 | 23.93392 | 50.31148 | -0.4663 | 9.92664 |
September | 485.00000 | 23.85410 | 50.56235 | -0.4957 | 10.57392 |
October | 502.00000 | 23.92659 | 48.15257 | 0.41336 | 8.86206 |
November | 489.00000 | 23.74991 | 45.74241 | 0.34023 | 7.80999 |
December | 497.00000 | 23.43596 | 43.07287 | 0.23461 | 6.93632 |
Annual Sum or Average | 5943.00000 | 23.72153 | 47.15537 | -0.0333 | 8.63034 |
Minimum of Months | 454.00000 | 23.20435 | 40.77675 | -0.4957 | 6.19790 |
Maximum of Months | 514.00000 | 23.93392 | 50.56235 | 0.41336 | 10.57392 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.18353 | 42.92954 | -0.0973 | 7.10536 |
February | 454.00000 | 22.59506 | 46.34517 | 0.03682 | 7.46034 |
March | 514.00000 | 22.97872 | 44.82382 | 0.13056 | 7.20214 |
April | 485.00000 | 23.75528 | 48.52810 | 0.36633 | 8.30574 |
May | 508.00000 | 24.02383 | 49.64310 | -0.4219 | 9.12620 |
June | 496.00000 | 24.02276 | 49.44517 | -0.4170 | 8.94613 |
July | 497.00000 | 24.03133 | 49.46354 | -0.4177 | 9.00013 |
August | 514.00000 | 24.03878 | 49.61428 | -0.4141 | 8.96194 |
September | 485.00000 | 23.94852 | 50.07251 | -0.4524 | 9.68942 |
October | 502.00000 | 23.86903 | 48.15614 | 0.40562 | 9.01441 |
November | 489.00000 | 23.18794 | 47.37835 | 0.20401 | 6.88951 |
December | 497.00000 | 22.54426 | 45.11850 | 0.01485 | 6.94274 |
Annual Sum or Average | 5943.00000 | 23.43703 | 47.62695 | -0.0905 | 8.22498 |
Minimum of Months | 454.00000 | 22.18353 | 42.92954 | -0.4524 | 6.88951 |
Maximum of Months | 514.00000 | 24.03878 | 50.07251 | 0.40562 | 9.68942 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.99560 | 39.41091 | 0.09726 | 6.79637 |
February | 454.00000 | 23.39557 | 42.29476 | 0.22245 | 7.44473 |
March | 514.00000 | 23.66227 | 41.23724 | 0.28891 | 7.75442 |
April | 485.00000 | 24.05445 | 45.62760 | 0.44474 | 9.36861 |
May | 508.00000 | 24.36120 | 47.78035 | -0.2831 | 7.24153 |
June | 496.00000 | 24.31801 | 47.29230 | -0.2755 | 7.01797 |
July | 497.00000 | 24.39015 | 47.14560 | -0.2478 | 6.89061 |
August | 514.00000 | 24.27441 | 47.37503 | -0.2824 | 7.05021 |
September | 485.00000 | 24.33055 | 47.98514 | -0.3051 | 7.51783 |
October | 502.00000 | 24.23647 | 45.87965 | 0.50278 | 10.73878 |
November | 489.00000 | 23.88242 | 43.57028 | 0.36681 | 8.31408 |
December | 497.00000 | 23.53332 | 40.98966 | 0.25077 | 7.38783 |
Annual Sum or Average | 5943.00000 | 23.95624 | 44.72573 | 0.06288 | 7.79129 |
Minimum of Months | 454.00000 | 22.99560 | 39.41091 | -0.3051 | 6.79637 |
Maximum of Months | 514.00000 | 24.39015 | 47.98514 | 0.50278 | 10.73878 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.30824 | 38.43314 | 0.18654 | 7.45330 |
February | 454.00000 | 23.54402 | 41.62533 | 0.27775 | 8.04661 |
March | 514.00000 | 23.64746 | 40.75017 | 0.31358 | 8.57133 |
April | 485.00000 | 23.98962 | 45.41204 | 0.45991 | 9.96366 |
May | 508.00000 | 24.41678 | 47.29107 | -0.2176 | 7.20601 |
June | 496.00000 | 24.31218 | 47.06381 | -0.2389 | 6.93141 |
July | 497.00000 | 24.37536 | 46.99856 | -0.2198 | 7.03515 |
August | 514.00000 | 24.21548 | 47.37871 | -0.2766 | 7.23664 |
September | 485.00000 | 24.37996 | 47.56811 | -0.2554 | 7.72587 |
October | 502.00000 | 24.25128 | 45.51445 | 0.53097 | 11.67082 |
November | 489.00000 | 23.91089 | 43.17064 | 0.39487 | 9.04377 |
December | 497.00000 | 23.38425 | 41.06120 | 0.23066 | 7.56160 |
Annual Sum or Average | 5943.00000 | 23.98051 | 44.36764 | 0.09658 | 8.20020 |
Minimum of Months | 454.00000 | 23.30824 | 38.43314 | -0.2766 | 6.93141 |
Maximum of Months | 514.00000 | 24.41678 | 47.56811 | 0.53097 | 11.67082 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.87495 | 36.79597 | 0.34580 | 9.57318 |
February | 454.00000 | 23.98265 | 40.24798 | 0.40402 | 10.10897 |
March | 514.00000 | 23.83924 | 40.26721 | 0.35692 | 9.20739 |
April | 485.00000 | 24.14151 | 45.17482 | 0.48212 | 10.24597 |
May | 508.00000 | 24.36280 | 47.75402 | -0.2795 | 7.23128 |
June | 496.00000 | 24.29841 | 47.39383 | -0.2894 | 7.17842 |
July | 497.00000 | 24.38146 | 47.18623 | -0.2535 | 6.97905 |
August | 514.00000 | 24.31879 | 47.15608 | -0.2508 | 6.88817 |
September | 485.00000 | 24.46345 | 47.38492 | -0.2264 | 7.32220 |
October | 502.00000 | 24.50801 | 44.67322 | 0.61990 | 14.01509 |
November | 489.00000 | 24.39940 | 41.57989 | 0.54919 | 12.39161 |
December | 497.00000 | 24.09961 | 39.00840 | 0.43927 | 10.97874 |
Annual Sum or Average | 5943.00000 | 24.22307 | 43.73798 | 0.15516 | 9.32912 |
Minimum of Months | 454.00000 | 23.83924 | 36.79597 | -0.2894 | 6.88817 |
Maximum of Months | 514.00000 | 24.50801 | 47.75402 | 0.61990 | 14.01509 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.68438 | 37.03273 | 0.30556 | 8.57241 |
February | 454.00000 | 24.18778 | 39.56434 | 0.47279 | 11.01564 |
March | 514.00000 | 24.35438 | 38.63869 | 0.53393 | 12.02570 |
April | 485.00000 | 24.59154 | 43.42336 | 0.68751 | 15.71519 |
May | 508.00000 | 24.51148 | 46.84921 | -0.1429 | 6.61153 |
June | 496.00000 | 24.51314 | 46.31062 | -0.0953 | 6.41706 |
July | 497.00000 | 24.63718 | 45.96985 | -0.0352 | 6.54738 |
August | 514.00000 | 24.53670 | 46.06583 | -0.0313 | 6.26674 |
September | 485.00000 | 24.52099 | 46.86844 | -0.1482 | 6.83795 |
October | 502.00000 | 24.57944 | 44.28197 | 0.66642 | 15.18661 |
November | 489.00000 | 24.53131 | 41.05428 | 0.60346 | 13.44859 |
December | 497.00000 | 24.51200 | 37.73510 | 0.56634 | 12.90727 |
Annual Sum or Average | 5943.00000 | 24.43086 | 42.83328 | 0.27961 | 10.10526 |
Minimum of Months | 454.00000 | 23.68438 | 37.03273 | -0.1482 | 6.26674 |
Maximum of Months | 514.00000 | 24.63718 | 46.86844 | 0.68751 | 15.71519 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.78276 | 42.78347 | -0.2076 | 7.96450 |
February | 454.00000 | 22.25976 | 45.45894 | -0.0611 | 7.74712 |
March | 514.00000 | 22.69927 | 44.18690 | 0.04735 | 7.16457 |
April | 485.00000 | 23.74384 | 47.79522 | 0.34972 | 8.24736 |
May | 508.00000 | 24.31334 | 49.10680 | -0.3122 | 7.58687 |
June | 496.00000 | 24.33402 | 48.15047 | -0.2936 | 7.33423 |
July | 497.00000 | 24.42201 | 48.51504 | -0.2659 | 7.29052 |
August | 514.00000 | 24.31323 | 48.82317 | -0.3079 | 7.54909 |
September | 485.00000 | 24.22789 | 49.78228 | -0.3566 | 8.20735 |
October | 502.00000 | 24.01243 | 48.11422 | 0.43823 | 9.87305 |
November | 489.00000 | 22.99974 | 46.73029 | 0.14533 | 6.78295 |
December | 497.00000 | 22.22550 | 45.02803 | -0.0738 | 7.41877 |
Annual Sum or Average | 5943.00000 | 23.45236 | 47.04226 | -0.0759 | 7.76279 |
Minimum of Months | 454.00000 | 21.78276 | 42.78347 | -0.3566 | 6.78295 |
Maximum of Months | 514.00000 | 24.42201 | 49.78228 | 0.43823 | 9.87305 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.25988 | 41.03720 | -0.0775 | 7.29282 |
February | 385.00000 | 22.73441 | 43.26909 | 0.06578 | 7.45930 |
March | 433.00000 | 23.15607 | 41.97552 | 0.17471 | 8.25940 |
April | 410.00000 | 24.03860 | 46.13100 | 0.44732 | 10.22876 |
May | 430.00000 | 24.51500 | 48.01853 | -0.2038 | 7.56694 |
June | 418.00000 | 24.48295 | 47.25007 | -0.2083 | 7.17545 |
July | 422.00000 | 24.61059 | 47.51842 | -0.1684 | 7.41653 |
August | 433.00000 | 24.44981 | 47.94049 | -0.2306 | 7.41726 |
September | 410.00000 | 24.40751 | 48.62431 | -0.2671 | 8.42214 |
October | 427.00000 | 24.21615 | 46.89734 | 0.50868 | 11.82420 |
November | 417.00000 | 23.45498 | 44.57917 | 0.26825 | 7.90569 |
December | 422.00000 | 22.55606 | 43.46425 | 0.01522 | 7.56746 |
Annual Sum or Average | 5034.00000 | 23.74546 | 45.56469 | 0.02616 | 8.21269 |
Minimum of Months | 385.00000 | 22.25988 | 41.03720 | -0.2671 | 7.17545 |
Maximum of Months | 433.00000 | 24.61059 | 48.62431 | 0.50868 | 11.82420 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.61772 | 37.94770 | 0.27717 | 9.24366 |
February | 454.00000 | 23.70964 | 41.26944 | 0.32824 | 9.62446 |
March | 514.00000 | 23.49754 | 41.71548 | 0.26211 | 8.66888 |
April | 485.00000 | 24.03278 | 46.59482 | 0.43640 | 9.69532 |
May | 508.00000 | 24.32156 | 49.04410 | -0.3052 | 7.55117 |
June | 496.00000 | 24.30557 | 48.29994 | -0.3102 | 7.51293 |
July | 497.00000 | 24.40782 | 48.57501 | -0.2722 | 7.35651 |
August | 514.00000 | 24.37038 | 48.47996 | -0.2686 | 7.26903 |
September | 485.00000 | 24.42635 | 48.77287 | -0.2510 | 7.68496 |
October | 502.00000 | 24.49102 | 45.92640 | 0.60874 | 13.96382 |
November | 489.00000 | 24.26017 | 42.51429 | 0.50449 | 11.78193 |
December | 497.00000 | 23.79765 | 40.56338 | 0.35371 | 10.52191 |
Annual Sum or Average | 5943.00000 | 24.10463 | 44.99703 | 0.11083 | 9.22943 |
Minimum of Months | 454.00000 | 23.49754 | 37.94770 | -0.3102 | 7.26903 |
Maximum of Months | 514.00000 | 24.49102 | 49.04410 | 0.60874 | 13.96382 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.53640 | 40.34722 | 0.00010 | 7.43817 |
February | 454.00000 | 22.99446 | 42.90608 | 0.14506 | 8.25031 |
March | 514.00000 | 23.27771 | 42.04760 | 0.21696 | 8.28995 |
April | 485.00000 | 24.18280 | 45.88851 | 0.50211 | 11.24803 |
May | 508.00000 | 24.43186 | 48.30387 | -0.2190 | 7.13547 |
June | 496.00000 | 24.45824 | 47.44082 | -0.1950 | 6.99949 |
July | 497.00000 | 24.55651 | 47.69076 | -0.1685 | 7.07191 |
August | 514.00000 | 24.45966 | 47.85987 | -0.1929 | 6.88685 |
September | 485.00000 | 24.39311 | 48.65266 | -0.2454 | 7.65799 |
October | 502.00000 | 24.29564 | 46.57517 | 0.54838 | 12.34932 |
November | 489.00000 | 23.56463 | 44.47574 | 0.31118 | 8.34444 |
December | 497.00000 | 22.94490 | 42.53118 | 0.12679 | 7.99057 |
Annual Sum or Average | 5943.00000 | 23.84645 | 45.40422 | 0.06757 | 8.29755 |
Minimum of Months | 454.00000 | 22.53640 | 40.34722 | -0.2454 | 6.88685 |
Maximum of Months | 514.00000 | 24.55651 | 48.65266 | 0.54838 | 12.34932 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.36417 | 43.87438 | -0.3404 | 10.41867 |
February | 454.00000 | 21.80609 | 46.71312 | -0.1856 | 9.78911 |
March | 514.00000 | 22.32558 | 45.01414 | -0.0527 | 8.42626 |
April | 485.00000 | 23.56981 | 48.23760 | 0.31337 | 8.29948 |
May | 508.00000 | 24.35623 | 48.86814 | -0.2787 | 7.42409 |
June | 496.00000 | 24.38270 | 47.76288 | -0.2544 | 7.13961 |
July | 497.00000 | 24.47782 | 48.17898 | -0.2251 | 7.19824 |
August | 514.00000 | 24.35356 | 48.57752 | -0.2745 | 7.40060 |
September | 485.00000 | 24.27013 | 49.72270 | -0.3285 | 8.20465 |
October | 502.00000 | 23.92356 | 48.38870 | 0.42429 | 10.24312 |
November | 489.00000 | 22.52003 | 48.00373 | 0.02568 | 7.30229 |
December | 497.00000 | 21.76925 | 46.34711 | -0.2066 | 9.13065 |
Annual Sum or Average | 5943.00000 | 23.27002 | 47.46919 | -0.1157 | 8.40568 |
Minimum of Months | 454.00000 | 21.36417 | 43.87438 | -0.3404 | 7.13961 |
Maximum of Months | 514.00000 | 24.47782 | 49.72270 | 0.42429 | 10.41867 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.78559 | 42.37495 | -0.2072 | 8.87894 |
February | 454.00000 | 22.34636 | 44.81010 | -0.0295 | 8.76794 |
March | 514.00000 | 22.92706 | 42.93765 | 0.11800 | 9.05389 |
April | 485.00000 | 23.92893 | 46.49660 | 0.43883 | 10.34140 |
May | 508.00000 | 24.46140 | 47.96176 | -0.1792 | 7.33390 |
June | 496.00000 | 24.44333 | 47.12274 | -0.1732 | 6.90720 |
July | 497.00000 | 24.55775 | 47.42482 | -0.1393 | 7.24727 |
August | 514.00000 | 24.41200 | 47.88119 | -0.2001 | 7.17564 |
September | 485.00000 | 24.37311 | 48.71577 | -0.2447 | 8.25726 |
October | 502.00000 | 24.11006 | 47.12587 | 0.50326 | 12.10979 |
November | 489.00000 | 23.11956 | 45.92113 | 0.18994 | 7.76236 |
December | 497.00000 | 22.16529 | 44.86207 | -0.0928 | 8.57149 |
Annual Sum or Average | 5943.00000 | 23.56061 | 46.13689 | -0.0021 | 8.52913 |
Minimum of Months | 454.00000 | 21.78559 | 42.37495 | -0.2447 | 6.90720 |
Maximum of Months | 514.00000 | 24.55775 | 48.71577 | 0.50326 | 12.10979 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.15581 | 39.23874 | 0.14320 | 9.38244 |
February | 454.00000 | 23.26472 | 42.47636 | 0.21072 | 9.96000 |
March | 514.00000 | 23.14824 | 42.56555 | 0.16995 | 9.29363 |
April | 485.00000 | 23.88384 | 47.03124 | 0.40666 | 9.69076 |
May | 508.00000 | 24.36160 | 48.81830 | -0.2723 | 7.43113 |
June | 496.00000 | 24.35379 | 47.90842 | -0.2713 | 7.29859 |
July | 497.00000 | 24.46087 | 48.24638 | -0.2325 | 7.26739 |
August | 514.00000 | 24.40746 | 48.25616 | -0.2352 | 7.19810 |
September | 485.00000 | 24.44160 | 48.77948 | -0.2285 | 7.82333 |
October | 502.00000 | 24.42762 | 46.14761 | 0.60251 | 14.19832 |
November | 489.00000 | 23.98703 | 43.34650 | 0.43028 | 11.09174 |
December | 497.00000 | 23.36888 | 41.80871 | 0.23317 | 10.52332 |
Annual Sum or Average | 5943.00000 | 23.94191 | 45.40045 | 0.07752 | 9.25314 |
Minimum of Months | 454.00000 | 23.14824 | 39.23874 | -0.2723 | 7.19810 |
Maximum of Months | 514.00000 | 24.46087 | 48.81830 | 0.60251 | 14.19832 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.06157 | 41.42674 | -0.1332 | 8.68354 |
February | 454.00000 | 22.51705 | 44.12290 | 0.02446 | 9.24837 |
March | 514.00000 | 22.88473 | 42.88998 | 0.11939 | 8.85026 |
April | 485.00000 | 23.98399 | 46.38557 | 0.46325 | 11.01060 |
May | 508.00000 | 24.42369 | 48.19006 | -0.2000 | 7.19356 |
June | 496.00000 | 24.45864 | 47.19570 | -0.1700 | 6.99219 |
July | 497.00000 | 24.55199 | 47.50533 | -0.1461 | 7.12258 |
August | 514.00000 | 24.46650 | 47.70734 | -0.1693 | 6.91725 |
September | 485.00000 | 24.37116 | 48.71978 | -0.2352 | 7.92312 |
October | 502.00000 | 24.17987 | 46.86867 | 0.53087 | 12.42688 |
November | 489.00000 | 23.12088 | 45.59763 | 0.20488 | 8.08989 |
December | 497.00000 | 22.46114 | 43.78063 | -0.0016 | 8.68521 |
Annual Sum or Average | 5943.00000 | 23.63067 | 45.86996 | 0.02297 | 8.58463 |
Minimum of Months | 454.00000 | 22.06157 | 41.42674 | -0.2352 | 6.91725 |
Maximum of Months | 514.00000 | 24.55199 | 48.71978 | 0.53087 | 12.42688 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.577395E+11 | 112138.29 | 19-JAN-16:40 | 284.67 | 0.355434E+12 | 0.00 | 0.413173E+12 | 2.14 | 7.58 | 20-JAN-06:04 | 0.00 | 0.00 |
February | 0.761419E+11 | 114048.59 | 24-FEB-17:00 | 330.41 | 0.486553E+12 | 0.00 | 0.562695E+12 | 2.91 | 7.43 | 28-FEB-06:03 | 0.00 | 0.00 |
March | 0.926952E+11 | 127721.78 | 28-MAR-05:04 | 423.69 | 0.584096E+12 | 0.00 | 0.676791E+12 | 3.27 | 7.66 | 28-MAR-05:04 | 0.00 | 0.00 |
April | 0.134024E+12 | 127958.77 | 14-APR-05:04 | 557.36 | 0.879633E+12 | 0.00 | 0.101366E+13 | 4.64 | 7.67 | 14-APR-05:04 | 0.00 | 0.00 |
May | 0.180544E+12 | 158928.27 | 22-MAY-05:03 | 553.81 | 0.117934E+13 | 0.00 | 0.135988E+13 | 4.69 | 7.38 | 09-MAY-05:04 | 0.00 | 0.00 |
June | 0.187638E+12 | 132476.30 | 19-JUN-10:40 | 596.32 | 0.121041E+13 | 0.00 | 0.139805E+13 | 5.07 | 7.30 | 07-JUN-05:05 | 0.00 | 0.00 |
July | 0.198187E+12 | 138234.56 | 26-JUL-05:02 | 654.90 | 0.124908E+13 | 0.00 | 0.144727E+13 | 5.18 | 7.26 | 14-JUL-05:04 | 0.00 | 0.00 |
August | 0.200989E+12 | 133935.58 | 17-AUG-14:10 | 676.02 | 0.128604E+13 | 0.00 | 0.148703E+13 | 5.39 | 7.33 | 29-AUG-05:04 | 0.00 | 0.00 |
September | 0.178656E+12 | 131951.42 | 18-SEP-10:10 | 547.86 | 0.115971E+13 | 0.00 | 0.133836E+13 | 4.74 | 7.44 | 22-SEP-05:04 | 0.00 | 0.00 |
October | 0.164071E+12 | 133726.79 | 21-OCT-05:04 | 562.86 | 0.106032E+13 | 0.00 | 0.122439E+13 | 4.59 | 7.37 | 13-OCT-05:02 | 0.00 | 0.00 |
November | 0.110958E+12 | 142922.03 | 01-NOV-05:04 | 461.02 | 0.703896E+12 | 0.00 | 0.814854E+12 | 3.75 | 7.52 | 29-NOV-06:04 | 0.00 | 0.00 |
December | 0.780601E+11 | 131532.17 | 12-DEC-06:04 | 374.89 | 0.491178E+12 | 0.00 | 0.569238E+12 | 2.85 | 7.59 | 12-DEC-06:04 | 0.00 | 0.00 |
Annual Sum or Average | 0.165970E+13 | 6023.81 | 0.106457E+14 | 0.00 | 0.123054E+14 | 4.11 | 0.00 | 0.00 | ||||
Minimum of Months | 0.577395E+11 | 112138.29 | 284.67 | 0.355434E+12 | 0.00 | 0.413173E+12 | 2.14 | 7.26 | 0.00 | 0.00 | ||
Maximum of Months | 0.200989E+12 | 158928.27 | 676.02 | 0.128604E+13 | 0.00 | 0.148703E+13 | 5.39 | 7.67 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.400406E+09 | 112138.29 | 19-JAN-16:40 | 1.03 | 0.283095E+10 | 0.00 | 0.323135E+10 | 0.01 | 7.58 | 20-JAN-06:04 | 0.00 | 0.00 |
February | 0.143241E+10 | 114048.59 | 24-FEB-17:00 | 3.71 | 0.101592E+11 | 0.00 | 0.115916E+11 | 0.04 | 7.41 | 03-FEB-06:05 | 0.00 | 0.00 |
March | 0.123094E+10 | 127721.78 | 28-MAR-05:04 | 3.07 | 0.868939E+10 | 0.00 | 0.992033E+10 | 0.03 | 7.66 | 28-MAR-05:04 | 0.00 | 0.00 |
April | 0.762516E+10 | 127958.77 | 14-APR-05:04 | 18.95 | 0.525638E+11 | 0.00 | 0.601889E+11 | 0.18 | 7.67 | 14-APR-05:04 | 0.00 | 0.00 |
May | 0.461531E+11 | 158928.27 | 22-MAY-05:03 | 111.38 | 0.312422E+12 | 0.00 | 0.358575E+12 | 1.01 | 7.38 | 09-MAY-05:04 | 0.00 | 0.00 |
June | 0.560627E+11 | 132476.30 | 19-JUN-10:40 | 131.31 | 0.375447E+12 | 0.00 | 0.431509E+12 | 1.22 | 7.30 | 07-JUN-05:05 | 0.00 | 0.00 |
July | 0.662900E+11 | 138234.56 | 26-JUL-05:02 | 151.99 | 0.440945E+12 | 0.00 | 0.507235E+12 | 1.36 | 7.26 | 14-JUL-05:04 | 0.00 | 0.00 |
August | 0.718832E+11 | 133935.58 | 17-AUG-14:10 | 165.79 | 0.480756E+12 | 0.00 | 0.552639E+12 | 1.49 | 7.33 | 29-AUG-05:04 | 0.00 | 0.00 |
September | 0.490589E+11 | 131951.42 | 18-SEP-10:10 | 115.75 | 0.332061E+12 | 0.00 | 0.381120E+12 | 1.09 | 7.44 | 22-SEP-05:04 | 0.00 | 0.00 |
October | 0.435979E+11 | 133726.79 | 21-OCT-05:04 | 102.40 | 0.295042E+12 | 0.00 | 0.338640E+12 | 0.93 | 7.37 | 13-OCT-05:02 | 0.00 | 0.00 |
November | 0.124946E+11 | 142922.03 | 01-NOV-05:04 | 29.92 | 0.853350E+11 | 0.00 | 0.978297E+11 | 0.28 | 7.52 | 29-NOV-06:04 | 0.00 | 0.00 |
December | 0.513469E+10 | 131532.17 | 12-DEC-06:04 | 12.90 | 0.354413E+11 | 0.00 | 0.405760E+11 | 0.12 | 7.59 | 12-DEC-06:04 | 0.00 | 0.00 |
Annual Sum or Average | 0.361364E+12 | 848.20 | 0.243169E+13 | 0.00 | 0.279306E+13 | 0.65 | 0.00 | 0.00 | ||||
Minimum of Months | 0.400406E+09 | 112138.29 | 1.03 | 0.283095E+10 | 0.00 | 0.323135E+10 | 0.01 | 7.26 | 0.00 | 0.00 | ||
Maximum of Months | 0.718832E+11 | 158928.27 | 165.79 | 0.480756E+12 | 0.00 | 0.552639E+12 | 1.49 | 7.67 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.122244E+11 | 744.00 | 12476.23 | 01-JAN-08:33 | 39706.57 | 19-JAN-17:00 | 21.21 | 19.16 | 2.81 |
February | 0.183251E+11 | 672.00 | 12476.23 | 01-FEB-00:10 | 67843.00 | 27-FEB-17:00 | 24.72 | 19.63 | 2.81 |
March | 0.243751E+11 | 744.00 | 12476.23 | 01-MAR-00:10 | 107129.07 | 31-MAR-24:00 | 28.57 | 20.54 | 2.81 |
April | 0.310201E+11 | 720.00 | 12476.23 | 01-APR-00:10 | 131046.40 | 28-APR-16:10 | 34.28 | 22.99 | 2.81 |
May | 0.334163E+11 | 744.00 | 12476.23 | 01-MAY-00:03 | 58376.83 | 31-MAY-23:20 | 30.89 | 27.33 | 2.81 |
June | 0.323384E+11 | 720.00 | 12476.23 | 01-JUN-00:10 | 87194.27 | 30-JUN-23:53 | 34.89 | 28.40 | 2.81 |
July | 0.334163E+11 | 744.00 | 12476.23 | 01-JUL-00:10 | 113293.22 | 31-JUL-23:53 | 38.41 | 29.09 | 2.81 |
August | 0.334163E+11 | 744.00 | 12476.23 | 01-AUG-00:03 | 133359.98 | 07-AUG-13:10 | 41.00 | 28.94 | 2.81 |
September | 0.323384E+11 | 720.00 | 12476.23 | 01-SEP-00:05 | 57045.37 | 30-SEP-23:50 | 30.16 | 26.66 | 2.81 |
October | 0.317924E+11 | 744.00 | 12476.23 | 01-OCT-00:10 | 81870.18 | 31-OCT-24:00 | 31.43 | 25.26 | 2.81 |
November | 0.267241E+11 | 720.00 | 12476.23 | 01-NOV-00:10 | 100021.45 | 02-NOV-15:10 | 29.62 | 21.34 | 2.81 |
December | 0.234289E+11 | 744.00 | 12476.23 | 01-DEC-10:30 | 126603.29 | 14-DEC-17:00 | 30.87 | 20.33 | 2.81 |
Annual Sum or Average | 0.332816E+12 | 8760.00 | 31.38 | 24.17 | 2.81 | ||||
Minimum of Months | 0.122244E+11 | 672.00 | 12476.23 | 39706.57 | 21.21 | 19.16 | 2.81 | ||
Maximum of Months | 0.334163E+11 | 744.00 | 12476.23 | 133359.98 | 41.00 | 29.09 | 2.81 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.515143E+10 | 205.56 | 21552.64 | 02-JAN-10:30 | 1102317.68 | 02-JAN-16:20 | 21.80 | 21.26 | 24.61 |
February | 0.665785E+10 | 274.57 | 21552.64 | 01-FEB-13:10 | 1075578.46 | 23-FEB-11:40 | 22.29 | 21.47 | 33.64 |
March | 0.927307E+10 | 343.02 | 21552.64 | 06-MAR-08:50 | 1133166.73 | 28-MAR-05:06 | 22.29 | 21.40 | 37.98 |
April | 0.196500E+11 | 487.17 | 21552.64 | 01-APR-03:02 | 1151631.61 | 18-APR-15:30 | 23.08 | 21.69 | 53.54 |
May | 0.424038E+11 | 553.81 | 21552.64 | 01-MAY-01:03 | 1036663.59 | 22-MAY-05:05 | 26.06 | 24.31 | 53.14 |
June | 0.450818E+11 | 596.32 | 21552.64 | 01-JUN-03:02 | 1032343.01 | 15-JUN-15:10 | 26.40 | 24.54 | 56.43 |
July | 0.508132E+11 | 654.90 | 21552.64 | 01-JUL-00:10 | 1040777.85 | 20-JUL-13:50 | 27.35 | 25.49 | 57.59 |
August | 0.515724E+11 | 675.52 | 21552.64 | 01-AUG-00:03 | 1037533.60 | 21-AUG-14:40 | 26.80 | 24.88 | 61.69 |
September | 0.422869E+11 | 547.86 | 21552.64 | 01-SEP-00:05 | 1046187.85 | 01-SEP-15:50 | 26.62 | 24.84 | 52.07 |
October | 0.328083E+11 | 538.89 | 21552.64 | 02-OCT-09:10 | 1440742.63 | 01-OCT-07:33 | 25.02 | 23.42 | 51.79 |
November | 0.129166E+11 | 395.97 | 21552.64 | 01-NOV-01:53 | 1128275.34 | 08-NOV-11:40 | 22.93 | 21.82 | 44.20 |
December | 0.954483E+10 | 288.87 | 21552.64 | 08-DEC-11:10 | 1092777.82 | 08-DEC-17:00 | 22.14 | 21.40 | 33.49 |
Annual Sum or Average | 0.328160E+12 | 5562.47 | 24.41 | 23.05 | 46.73 | ||||
Minimum of Months | 0.515143E+10 | 205.56 | 21552.64 | 1032343.01 | 21.80 | 21.26 | 24.61 | ||
Maximum of Months | 0.515724E+11 | 675.52 | 21552.64 | 1440742.63 | 27.35 | 25.49 | 61.69 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.103453E+09 | 1.33 | 21552.64 | 19-JAN-10:30 | 957080.88 | 19-JAN-16:40 | 21.80 | 21.80 | 0.13 |
February | 0.284495E+09 | 3.67 | 21552.64 | 24-FEB-10:50 | 962996.12 | 24-FEB-17:00 | 22.29 | 22.27 | 0.40 |
March | 0.245700E+09 | 3.17 | 21552.64 | 06-MAR-13:00 | 972474.57 | 07-MAR-15:10 | 22.29 | 22.28 | 0.31 |
April | 0.172895E+10 | 22.28 | 21552.64 | 14-APR-10:20 | 1017470.61 | 24-APR-11:00 | 23.08 | 22.99 | 2.20 |
May | 0.117932E+11 | 151.99 | 21552.64 | 01-MAY-08:20 | 1036663.59 | 22-MAY-05:05 | 26.06 | 25.46 | 13.67 |
June | 0.175667E+11 | 226.41 | 21552.64 | 01-JUN-05:05 | 1032343.01 | 15-JUN-15:10 | 26.40 | 25.48 | 18.87 |
July | 0.235646E+11 | 303.71 | 21552.64 | 01-JUL-06:20 | 1040777.85 | 20-JUL-13:50 | 27.35 | 26.18 | 23.09 |
August | 0.214587E+11 | 276.57 | 21552.64 | 01-AUG-05:04 | 1037533.60 | 21-AUG-14:40 | 26.80 | 25.71 | 22.45 |
September | 0.153938E+11 | 198.40 | 21552.64 | 01-SEP-05:02 | 1046187.85 | 01-SEP-15:50 | 26.62 | 25.83 | 16.58 |
October | 0.130803E+11 | 168.58 | 21552.64 | 02-OCT-14:10 | 1034276.38 | 23-OCT-13:20 | 25.02 | 24.36 | 13.80 |
November | 0.292124E+10 | 37.65 | 21552.64 | 01-NOV-05:04 | 1032311.05 | 02-NOV-14:40 | 22.93 | 22.77 | 3.48 |
December | 0.109918E+10 | 14.17 | 21552.64 | 11-DEC-14:50 | 1000397.12 | 12-DEC-16:40 | 22.14 | 22.09 | 1.37 |
Annual Sum or Average | 0.109240E+12 | 1407.93 | 24.41 | 23.94 | 9.77 | ||||
Minimum of Months | 0.103453E+09 | 1.33 | 21552.64 | 957080.88 | 21.80 | 21.80 | 0.13 | ||
Maximum of Months | 0.235646E+11 | 303.71 | 21552.64 | 1046187.85 | 27.35 | 26.18 | 23.09 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.212664E+11 | 0.00 | 232.26 | 835402.57 | 10-JAN-06:02 | 0.00 | 25.84 | 42.96 | 0.04 | 0.00 | 0.01 | 0.58 | 10-JAN-06:02 |
February | 0.102685E+11 | 0.00 | 122.18 | 791024.58 | 06-FEB-06:02 | 0.00 | 19.73 | 30.10 | 0.02 | 0.00 | 0.00 | 0.55 | 06-FEB-06:02 |
March | 0.858775E+10 | 0.00 | 100.82 | 674912.12 | 11-MAR-06:02 | 0.00 | 21.26 | 28.96 | 0.01 | 0.00 | 0.00 | 0.47 | 11-MAR-06:02 |
April | 0.141620E+09 | 0.00 | 8.39 | 24618.72 | 03-APR-16:50 | 0.00 | 26.95 | 27.60 | 0.00 | 0.00 | 0.00 | 0.02 | 03-APR-16:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 32.02 | 32.02 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 32.02 | 32.02 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 32.02 | 32.02 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 32.02 | 32.02 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 32.02 | 32.02 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 43502604.04 | 0.00 | 8.29 | 4622.43 | 28-OCT-06:50 | 0.00 | 31.62 | 32.18 | 0.00 | 0.00 | 0.00 | 0.00 | 28-OCT-06:50 |
November | 0.773347E+09 | 0.00 | 48.11 | 98675.35 | 16-NOV-06:02 | 0.00 | 25.44 | 29.14 | 0.00 | 0.00 | 0.00 | 0.07 | 16-NOV-06:02 |
December | 0.146308E+11 | 0.00 | 175.54 | 804124.28 | 21-DEC-06:01 | 0.00 | 21.20 | 34.69 | 0.02 | 0.00 | 0.00 | 0.55 | 21-DEC-06:01 |
Annual Sum or Average | 0.557120E+11 | 0.00 | 695.59 | 0.00 | 27.73 | 32.18 | 0.01 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.73 | 27.60 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.212664E+11 | 0.00 | 232.26 | 835402.57 | 0.00 | 32.02 | 42.96 | 0.04 | 0.00 | 0.01 | 0.58 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 21.21 | 21.21 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 24.72 | 24.72 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 28.57 | 28.57 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 34.28 | 34.28 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 30.89 | 30.89 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 34.89 | 34.89 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 38.41 | 38.41 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 41.00 | 41.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 30.16 | 30.16 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 31.43 | 31.43 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 29.62 | 29.62 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 30.87 | 30.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 31.38 | 31.38 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.21 | 21.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 | 41.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.394737E+11 | 0.00 | 268.00 | 0.299407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 144942.67 | 31-JAN-06:02 | 132349.35 | 30-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.565043E+11 | 0.00 | 321.07 | 0.413368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131220.89 | 28-FEB-06:03 | 119282.02 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.704633E+11 | 0.00 | 413.18 | 0.557049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 136065.61 | 27-MAR-05:02 | 128614.96 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.113887E+12 | 0.00 | 545.30 | 0.910678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145596.59 | 24-APR-05:02 | 135830.13 | 24-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.142552E+12 | 0.00 | 521.85 | 0.111343E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 161503.86 | 22-MAY-05:03 | 141541.02 | 30-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.154763E+12 | 0.00 | 569.12 | 0.123158E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 150436.40 | 26-JUN-05:02 | 139320.04 | 26-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.167088E+12 | 0.00 | 612.81 | 0.131766E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 156235.15 | 05-JUL-05:02 | 141902.28 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.181643E+12 | 0.00 | 647.84 | 0.144148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 155060.86 | 14-AUG-05:02 | 140687.66 | 14-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.142557E+12 | 0.00 | 508.34 | 0.105687E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 164389.46 | 05-SEP-05:03 | 143076.15 | 05-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.134102E+12 | 0.00 | 531.53 | 0.106674E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 161320.54 | 10-OCT-05:02 | 144746.02 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.854992E+11 | 0.00 | 447.99 | 0.691610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 147145.52 | 01-NOV-05:02 | 131775.34 | 02-NOV-05:02 | 0.00 | 0.00 | 0.00 |
December | 0.632382E+11 | 0.00 | 360.79 | 0.501482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 151092.24 | 11-DEC-06:02 | 138280.35 | 11-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135177E+13 | 0.00 | 5747.80 | 0.106014E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.394737E+11 | 0.00 | 268.00 | 0.299407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131220.89 | 119282.02 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.181643E+12 | 0.00 | 647.84 | 0.144148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 164389.46 | 144746.02 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.304851E+12 | 0.00 | 257.92 | 0.224675E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1126680.77 | 20-JAN-06:02 | 912951.06 | 19-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.435918E+12 | 0.00 | 295.39 | 0.306262E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1201178.75 | 03-FEB-06:03 | 1056144.72 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.516071E+12 | 0.00 | 361.53 | 0.389006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1369653.84 | 28-MAR-05:02 | 1185631.54 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.817918E+12 | 0.00 | 412.05 | 0.616538E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1413295.89 | 29-APR-05:03 | 1223953.47 | 29-APR-05:03 | 0.00 | 0.00 | 0.00 |
May | 0.125516E+13 | 0.00 | 480.71 | 0.945060E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1840667.26 | 22-MAY-03:02 | 1280958.13 | 22-MAY-03:02 | 0.00 | 0.00 | 0.00 |
June | 0.129195E+13 | 0.00 | 488.09 | 0.979148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1451170.00 | 07-JUN-05:03 | 1234201.48 | 28-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.132969E+13 | 0.00 | 495.71 | 0.975580E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1468541.56 | 26-JUL-05:02 | 1245996.05 | 06-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.137627E+13 | 0.00 | 500.05 | 0.100783E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1489928.03 | 29-AUG-05:02 | 1258988.86 | 29-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.123468E+13 | 0.00 | 466.67 | 0.869302E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1601484.65 | 14-SEP-05:03 | 1238396.63 | 14-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.108876E+13 | 0.00 | 455.40 | 0.820747E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1544797.82 | 21-OCT-05:02 | 1237695.21 | 21-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.635493E+12 | 0.00 | 390.01 | 0.493183E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1460978.08 | 01-NOV-05:02 | 1223874.17 | 01-NOV-05:02 | 0.00 | 0.00 | 0.00 |
December | 0.440595E+12 | 0.00 | 296.35 | 0.326063E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1386007.70 | 13-DEC-06:02 | 1202293.78 | 12-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107274E+14 | 0.00 | 4899.87 | 0.795339E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.304851E+12 | 0.00 | 257.92 | 0.224675E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1126680.77 | 912951.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.137627E+13 | 0.00 | 500.05 | 0.100783E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1840667.26 | 1280958.13 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.312397E+11 | 0.00 | 253.78 | 0.227633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116874.82 | 19-JAN-15:00 | 77864.18 | 19-JAN-15:50 | 0.00 | 0.00 | 0.00 |
February | 0.450116E+11 | 0.00 | 290.92 | 0.314260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114715.24 | 28-FEB-06:03 | 101963.08 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.541084E+11 | 0.00 | 359.24 | 0.405466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139005.22 | 27-MAR-05:02 | 121128.24 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.871330E+11 | 0.00 | 409.45 | 0.665621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143596.61 | 27-APR-05:02 | 142391.83 | 18-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.140593E+12 | 0.00 | 490.03 | 0.108781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 196911.83 | 22-MAY-03:02 | 144830.60 | 22-MAY-03:02 | 0.00 | 0.00 | 0.00 |
June | 0.146918E+12 | 0.00 | 502.02 | 0.114851E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 155712.11 | 30-JUN-03:02 | 135745.60 | 30-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.150639E+12 | 0.00 | 515.39 | 0.114011E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 166592.74 | 26-JUL-03:02 | 142193.61 | 26-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.154275E+12 | 0.00 | 514.69 | 0.116298E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 161579.08 | 24-AUG-03:02 | 140410.23 | 24-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.134290E+12 | 0.00 | 472.21 | 0.966514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 189813.22 | 05-SEP-03:02 | 139051.28 | 05-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.117050E+12 | 0.00 | 456.72 | 0.899064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 166670.02 | 21-OCT-05:02 | 130118.79 | 21-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.637855E+11 | 0.00 | 385.28 | 0.495261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 151289.45 | 01-NOV-05:02 | 126441.01 | 01-NOV-05:02 | 0.00 | 0.00 | 0.00 |
December | 0.441520E+11 | 0.00 | 292.61 | 0.326099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132746.27 | 15-DEC-06:03 | 111558.08 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116920E+13 | 0.00 | 4942.34 | 0.883932E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.312397E+11 | 0.00 | 253.78 | 0.227633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114715.24 | 77864.18 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.154275E+12 | 0.00 | 515.39 | 0.116298E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 196911.83 | 144830.60 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.204821E+11 | 0.00 | 146.17 | 0.158825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110691.16 | 01-JAN-16:12 | 85566.53 | 01-JAN-16:53 | 0.00 | 0.00 | 0.00 |
February | 0.243698E+11 | 0.00 | 190.24 | 0.196492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100526.35 | 03-FEB-06:03 | 93983.67 | 21-FEB-04:03 | 0.00 | 0.00 | 0.00 |
March | 0.326463E+11 | 0.00 | 233.67 | 0.274596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130456.19 | 07-MAR-05:03 | 83078.22 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 |
April | 0.507797E+11 | 0.00 | 339.56 | 0.439375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135678.51 | 29-APR-05:03 | 76458.03 | 24-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.935505E+11 | 0.00 | 427.83 | 0.720369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 163086.64 | 22-MAY-03:04 | 100954.03 | 29-MAY-12:43 | 0.00 | 0.00 | 0.00 |
June | 0.982552E+11 | 0.00 | 426.85 | 0.737793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 163023.10 | 19-JUN-03:02 | 85036.75 | 12-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.105253E+12 | 0.00 | 410.96 | 0.744623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168727.85 | 03-JUL-03:03 | 83581.38 | 05-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.117337E+12 | 0.00 | 465.42 | 0.852203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 156687.93 | 13-AUG-18:20 | 87596.00 | 28-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.100499E+12 | 0.00 | 431.75 | 0.734065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160862.39 | 17-SEP-17:53 | 91780.84 | 05-SEP-02:13 | 0.00 | 0.00 | 0.00 |
October | 0.866626E+11 | 0.00 | 408.59 | 0.667716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 161033.56 | 08-OCT-16:20 | 85480.16 | 09-OCT-19:40 | 0.00 | 0.00 | 0.00 |
November | 0.486032E+11 | 0.00 | 302.06 | 0.399271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 144127.58 | 02-NOV-03:02 | 79639.58 | 02-NOV-03:02 | 0.00 | 0.00 | 0.00 |
December | 0.315948E+11 | 0.00 | 203.48 | 0.254428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134032.76 | 15-DEC-05:03 | 84992.29 | 11-DEC-04:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.810033E+12 | 0.00 | 3986.59 | 0.617976E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.204821E+11 | 0.00 | 146.17 | 0.158825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100526.35 | 76458.03 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.117337E+12 | 0.00 | 465.42 | 0.852203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168727.85 | 100954.03 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.497309E+10 | 0.117683E+10 | 744.00 | 0.486926E+10 | 0.103829E+09 | 0.00 | 0.33 | 19-JAN-17:00 | 0.14 | 05-JAN-08:00 | 2720.09 | 19-JAN-17:00 | 2523.00 | 01-JAN-17:10 | 392.39 | 31-JAN-17:00 | 715.16 | 02-JAN-15:00 | 0.00 |
February | 0.944723E+10 | 0.211857E+10 | 672.00 | 0.926601E+10 | 0.181221E+09 | 0.00 | 0.55 | 27-FEB-17:00 | 0.39 | 17-FEB-07:50 | 4642.82 | 27-FEB-17:00 | 4552.54 | 26-FEB-17:50 | 391.98 | 24-FEB-17:00 | 1247.28 | 02-FEB-13:10 | 0.00 |
March | 0.156457E+11 | 0.345698E+10 | 744.00 | 0.154473E+11 | 0.198407E+09 | 0.00 | 0.86 | 31-MAR-24:00 | 0.59 | 11-MAR-18:00 | 7684.44 | 31-MAR-24:00 | 7684.44 | 31-MAR-24:00 | 480.60 | 07-MAR-15:00 | 1832.71 | 30-MAR-13:00 | 0.00 |
April | 0.203760E+11 | 0.463499E+10 | 720.00 | 0.200781E+11 | 0.297950E+09 | 0.00 | 1.00 | 28-APR-15:10 | 0.30 | 30-APR-23:55 | 8605.31 | 28-APR-16:10 | 8342.76 | 16-APR-18:20 | 527.88 | 24-APR-11:00 | 2596.23 | 28-APR-15:00 | 0.00 |
May | 0.637587E+10 | 0.184013E+10 | 744.00 | 0.588497E+10 | 0.490903E+09 | 0.00 | 0.49 | 31-MAY-23:20 | 0.25 | 13-MAY-06:10 | 4062.61 | 31-MAY-23:10 | 3974.67 | 31-MAY-24:00 | 548.37 | 23-MAY-16:00 | 1016.11 | 31-MAY-23:20 | 0.00 |
June | 0.111765E+11 | 0.316051E+10 | 720.00 | 0.106080E+11 | 0.568463E+09 | 0.00 | 0.70 | 30-JUN-23:53 | 0.47 | 01-JUN-06:00 | 5855.86 | 30-JUN-23:53 | 5842.92 | 30-JUN-23:57 | 675.78 | 29-JUN-15:00 | 1587.95 | 29-JUN-14:00 | 0.00 |
July | 0.166550E+11 | 0.460955E+10 | 744.00 | 0.160060E+11 | 0.648954E+09 | 0.00 | 0.89 | 31-JUL-23:53 | 0.69 | 15-JUL-06:00 | 7708.72 | 31-JUL-23:53 | 7701.35 | 31-JUL-23:53 | 668.31 | 12-JUL-10:00 | 2274.11 | 21-JUL-16:00 | 0.00 |
August | 0.217027E+11 | 0.578159E+10 | 744.00 | 0.210288E+11 | 0.673925E+09 | 0.00 | 1.00 | 01-AUG-13:40 | 0.32 | 31-AUG-24:00 | 8750.97 | 07-AUG-13:10 | 8190.69 | 30-AUG-18:20 | 727.09 | 07-AUG-13:20 | 2743.80 | 30-AUG-16:00 | 0.00 |
September | 0.621027E+10 | 0.175210E+10 | 720.00 | 0.568213E+10 | 0.528144E+09 | 0.00 | 0.49 | 30-SEP-23:50 | 0.25 | 28-SEP-06:10 | 4018.78 | 30-SEP-24:00 | 3994.62 | 30-SEP-24:00 | 580.21 | 18-SEP-14:30 | 1007.46 | 09-SEP-17:00 | 0.00 |
October | 0.113369E+11 | 0.296179E+10 | 744.00 | 0.108974E+11 | 0.439519E+09 | 0.00 | 0.68 | 31-OCT-24:00 | 0.43 | 28-OCT-07:00 | 5864.34 | 31-OCT-24:00 | 5856.67 | 31-OCT-24:00 | 680.92 | 24-OCT-14:10 | 1561.77 | 05-OCT-15:00 | 0.00 |
November | 0.154412E+11 | 0.347180E+10 | 720.00 | 0.151973E+11 | 0.243854E+09 | 0.00 | 0.79 | 02-NOV-15:00 | 0.62 | 15-NOV-07:10 | 6718.24 | 07-NOV-16:40 | 6362.31 | 06-NOV-17:00 | 562.17 | 01-NOV-11:00 | 1899.20 | 01-NOV-14:00 | 0.00 |
December | 0.207021E+11 | 0.438273E+10 | 744.00 | 0.205201E+11 | 0.181960E+09 | 0.00 | 0.98 | 15-DEC-17:00 | 0.79 | 20-DEC-07:40 | 8642.62 | 14-DEC-17:00 | 8244.82 | 10-DEC-16:55 | 574.84 | 12-DEC-15:00 | 2359.65 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.160043E+12 | 0.393476E+11 | 8760.00 | 0.155485E+12 | 0.455713E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.497309E+10 | 0.117683E+10 | 672.00 | 0.486926E+10 | 0.103829E+09 | 0.00 | 0.33 | 0.14 | 2720.09 | 2523.00 | 391.98 | 715.16 | 0.00 | ||||||
Maximum of Months | 0.217027E+11 | 0.578159E+10 | 744.00 | 0.210288E+11 | 0.673925E+09 | 0.00 | 1.00 | 0.79 | 8750.97 | 8342.76 | 727.09 | 2743.80 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.344389E+11 | 0.837330E+10 | 744.00 | 0.334406E+11 | 0.998270E+09 | 0.00 | 0.33 | 19-JAN-17:00 | 0.05 | 10-JAN-07:10 | 25353.14 | 19-JAN-17:00 | 21815.61 | 19-JAN-17:00 | 3931.81 | 31-JAN-17:00 | 6570.81 | 19-JAN-16:50 | 0.00 |
February | 0.801566E+11 | 0.181915E+11 | 672.00 | 0.783604E+11 | 0.179626E+10 | 0.00 | 0.55 | 27-FEB-17:00 | 0.29 | 06-FEB-07:10 | 43879.35 | 27-FEB-17:00 | 41082.70 | 26-FEB-17:54 | 3893.25 | 24-FEB-17:00 | 11615.53 | 24-FEB-14:00 | 0.00 |
March | 0.141024E+12 | 0.314127E+11 | 744.00 | 0.139044E+12 | 0.197966E+10 | 0.00 | 0.84 | 31-MAR-24:00 | 0.50 | 11-MAR-18:00 | 71583.49 | 31-MAR-24:00 | 71583.49 | 31-MAR-24:00 | 4792.15 | 07-MAR-15:00 | 17456.95 | 30-MAR-13:00 | 0.00 |
April | 0.192398E+12 | 0.438653E+11 | 720.00 | 0.189417E+12 | 0.298091E+10 | 0.00 | 1.00 | 28-APR-15:00 | 0.28 | 30-APR-23:55 | 82278.49 | 28-APR-16:30 | 78394.48 | 16-APR-18:06 | 5284.04 | 24-APR-11:00 | 24810.81 | 28-APR-15:00 | 0.00 |
May | 0.588475E+11 | 0.170226E+11 | 744.00 | 0.539934E+11 | 0.485407E+10 | 0.00 | 0.48 | 31-MAY-23:20 | 0.24 | 02-MAY-06:10 | 38094.17 | 31-MAY-23:10 | 37074.20 | 31-MAY-24:00 | 5410.34 | 23-MAY-16:00 | 9532.28 | 31-MAY-23:20 | 0.00 |
June | 0.105778E+12 | 0.299304E+11 | 720.00 | 0.100117E+12 | 0.566119E+10 | 0.00 | 0.70 | 30-JUN-23:53 | 0.46 | 07-JUN-06:10 | 56578.06 | 30-JUN-23:53 | 56439.74 | 30-JUN-23:57 | 6711.09 | 29-JUN-15:00 | 15188.24 | 29-JUN-14:00 | 0.00 |
July | 0.158407E+12 | 0.438528E+11 | 744.00 | 0.151930E+12 | 0.647700E+10 | 0.00 | 0.89 | 31-JUL-23:53 | 0.67 | 11-JUL-21:20 | 73753.20 | 31-JUL-23:53 | 73678.24 | 31-JUL-23:53 | 6678.05 | 12-JUL-10:00 | 21787.42 | 21-JUL-16:00 | 0.00 |
August | 0.207103E+12 | 0.551616E+11 | 744.00 | 0.200367E+12 | 0.673668E+10 | 0.00 | 1.00 | 01-AUG-13:10 | 0.29 | 31-AUG-24:00 | 83702.75 | 07-AUG-13:10 | 78182.02 | 30-AUG-18:30 | 7240.74 | 07-AUG-13:20 | 26177.16 | 30-AUG-16:00 | 0.00 |
September | 0.563009E+11 | 0.159366E+11 | 720.00 | 0.510959E+11 | 0.520508E+10 | 0.00 | 0.47 | 30-SEP-23:50 | 0.23 | 28-SEP-06:10 | 37081.19 | 30-SEP-24:00 | 36806.79 | 30-SEP-24:00 | 5770.57 | 18-SEP-14:30 | 9292.96 | 09-SEP-17:00 | 0.00 |
October | 0.105214E+12 | 0.275997E+11 | 744.00 | 0.100842E+12 | 0.437230E+10 | 0.00 | 0.66 | 31-OCT-24:00 | 0.38 | 28-OCT-07:00 | 54183.47 | 31-OCT-24:00 | 54086.41 | 31-OCT-24:00 | 6790.87 | 24-OCT-14:10 | 14895.94 | 05-OCT-15:00 | 0.00 |
November | 0.140490E+12 | 0.318227E+11 | 720.00 | 0.138059E+12 | 0.243173E+10 | 0.00 | 0.79 | 02-NOV-15:00 | 0.57 | 15-NOV-08:00 | 64130.56 | 07-NOV-16:40 | 60211.89 | 06-NOV-17:00 | 5619.58 | 01-NOV-11:00 | 18127.21 | 01-NOV-14:00 | 0.00 |
December | 0.187037E+12 | 0.399519E+11 | 744.00 | 0.185215E+12 | 0.182146E+10 | 0.00 | 0.97 | 15-DEC-17:00 | 0.71 | 30-DEC-08:00 | 82202.08 | 14-DEC-17:00 | 77842.38 | 15-DEC-17:00 | 5740.02 | 12-DEC-15:00 | 22493.35 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.146720E+13 | 0.363121E+12 | 8760.00 | 0.142188E+13 | 0.453146E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.344389E+11 | 0.837330E+10 | 672.00 | 0.334406E+11 | 0.998270E+09 | 0.00 | 0.33 | 0.05 | 25353.14 | 21815.61 | 3893.25 | 6570.81 | 0.00 | ||||||
Maximum of Months | 0.207103E+12 | 0.551616E+11 | 744.00 | 0.200367E+12 | 0.673668E+10 | 0.00 | 1.00 | 0.71 | 83702.75 | 78394.48 | 7240.74 | 26177.16 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.236933E+10 | 0.592840E+09 | 682.65 | 0.227141E+10 | 97925473.29 | 0.00 | 0.33 | 19-JAN-17:00 | 0.00 | 04-JAN-02:55 | 2613.96 | 19-JAN-17:00 | 2259.25 | 19-JAN-17:00 | 396.89 | 31-JAN-17:00 | 677.36 | 19-JAN-16:30 | 0.00 |
February | 0.720872E+10 | 0.165428E+10 | 672.00 | 0.703024E+10 | 0.178478E+09 | 0.00 | 0.55 | 27-FEB-17:00 | 0.10 | 05-FEB-09:00 | 4466.71 | 27-FEB-17:00 | 4128.76 | 26-FEB-17:50 | 390.11 | 24-FEB-17:00 | 1180.36 | 24-FEB-14:00 | 0.00 |
March | 0.135032E+11 | 0.303386E+10 | 744.00 | 0.133058E+11 | 0.197389E+09 | 0.00 | 0.82 | 31-MAR-24:00 | 0.38 | 12-MAR-07:50 | 7059.03 | 31-MAR-24:00 | 7058.70 | 31-MAR-24:00 | 479.52 | 07-MAR-15:00 | 1768.20 | 30-MAR-13:00 | 0.00 |
April | 0.191085E+11 | 0.437708E+10 | 720.00 | 0.188109E+11 | 0.297568E+09 | 0.00 | 1.00 | 28-APR-15:20 | 0.28 | 30-APR-23:55 | 8371.64 | 28-APR-16:10 | 7960.44 | 23-APR-18:10 | 527.61 | 24-APR-11:00 | 2521.89 | 28-APR-15:00 | 0.00 |
May | 0.605677E+10 | 0.175342E+10 | 744.00 | 0.556897E+10 | 0.487804E+09 | 0.00 | 0.47 | 31-MAY-23:20 | 0.23 | 15-MAY-06:10 | 3806.14 | 31-MAY-23:10 | 3700.23 | 31-MAY-24:00 | 547.94 | 23-MAY-16:00 | 954.19 | 31-MAY-23:20 | 0.00 |
June | 0.107596E+11 | 0.304736E+10 | 720.00 | 0.101927E+11 | 0.566910E+09 | 0.00 | 0.70 | 30-JUN-23:53 | 0.44 | 07-JUN-06:10 | 5719.90 | 30-JUN-23:53 | 5706.24 | 30-JUN-23:57 | 674.43 | 29-JUN-15:00 | 1557.35 | 29-JUN-14:00 | 0.00 |
July | 0.160183E+11 | 0.444069E+10 | 744.00 | 0.153706E+11 | 0.647697E+09 | 0.00 | 0.87 | 31-JUL-23:53 | 0.66 | 15-JUL-06:00 | 7374.98 | 31-JUL-23:53 | 7367.37 | 31-JUL-23:53 | 669.65 | 12-JUL-10:00 | 2219.97 | 21-JUL-16:00 | 0.00 |
August | 0.208622E+11 | 0.556832E+10 | 744.00 | 0.201888E+11 | 0.673411E+09 | 0.00 | 1.00 | 01-AUG-13:40 | 0.29 | 31-AUG-24:00 | 8445.85 | 10-AUG-16:00 | 7952.66 | 30-AUG-18:20 | 724.44 | 07-AUG-13:20 | 2668.62 | 30-AUG-16:00 | 0.00 |
September | 0.576360E+10 | 0.163406E+10 | 720.00 | 0.524122E+10 | 0.522382E+09 | 0.00 | 0.47 | 30-SEP-23:30 | 0.22 | 28-SEP-07:00 | 3747.99 | 30-SEP-24:00 | 3721.50 | 30-SEP-24:00 | 579.86 | 18-SEP-10:40 | 989.80 | 09-SEP-17:00 | 0.00 |
October | 0.104845E+11 | 0.276271E+10 | 744.00 | 0.100473E+11 | 0.437197E+09 | 0.00 | 0.64 | 31-OCT-24:00 | 0.31 | 28-OCT-08:00 | 5354.86 | 31-OCT-24:00 | 5344.35 | 31-OCT-24:00 | 680.76 | 24-OCT-14:10 | 1523.37 | 05-OCT-15:00 | 0.00 |
November | 0.134660E+11 | 0.307817E+10 | 720.00 | 0.132237E+11 | 0.242294E+09 | 0.00 | 0.78 | 02-NOV-15:00 | 0.48 | 16-NOV-07:10 | 6474.40 | 07-NOV-16:40 | 6091.63 | 06-NOV-17:00 | 562.86 | 01-NOV-11:00 | 1835.32 | 01-NOV-14:00 | 0.00 |
December | 0.178015E+11 | 0.384218E+10 | 744.00 | 0.176200E+11 | 0.181472E+09 | 0.00 | 0.97 | 15-DEC-17:00 | 0.61 | 20-DEC-07:10 | 8282.90 | 14-DEC-17:00 | 7860.74 | 15-DEC-17:00 | 574.30 | 12-DEC-15:00 | 2266.04 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.143402E+12 | 0.357850E+11 | 8698.65 | 0.138872E+12 | 0.453053E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.236933E+10 | 0.592840E+09 | 672.00 | 0.227141E+10 | 97925473.29 | 0.00 | 0.33 | 0.00 | 2613.96 | 2259.25 | 390.11 | 677.36 | 0.00 | ||||||
Maximum of Months | 0.208622E+11 | 0.556832E+10 | 744.00 | 0.201888E+11 | 0.673411E+09 | 0.00 | 1.00 | 0.66 | 8445.85 | 7960.44 | 724.44 | 2668.62 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.36 | 0.00 | 83.36 | 54.98 | 327.15 | 0.00 | 0.00 | 0.00 |
February | 98.34 | 0.00 | 98.34 | 76.80 | 278.24 | 0.00 | 0.00 | 0.00 |
March | 114.09 | 0.00 | 114.09 | 113.39 | 235.80 | 0.00 | 0.00 | 0.00 |
April | 134.65 | 0.55 | 134.10 | 183.91 | 140.03 | 0.00 | 0.00 | 0.00 |
May | 152.52 | 5.58 | 146.94 | 311.55 | 37.54 | 0.00 | 0.00 | 0.00 |
June | 173.44 | 12.01 | 161.43 | 367.95 | 30.39 | 0.00 | 0.00 | 0.00 |
July | 168.32 | 6.41 | 161.90 | 353.99 | 19.08 | 0.00 | 0.00 | 0.00 |
August | 150.73 | 1.19 | 149.54 | 318.30 | 28.23 | 0.00 | 0.00 | 0.00 |
September | 130.20 | 0.01 | 130.19 | 254.60 | 45.06 | 0.00 | 0.00 | 0.00 |
October | 113.14 | 0.00 | 113.14 | 203.54 | 87.83 | 0.00 | 0.00 | 0.00 |
November | 85.89 | 0.00 | 85.89 | 88.53 | 211.76 | 0.00 | 0.00 | 0.00 |
December | 77.49 | 0.00 | 77.49 | 58.56 | 288.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.64 | 2.15 | 121.49 | 199.57 | 143.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.49 | 0.00 | 77.49 | 54.98 | 19.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.44 | 12.01 | 161.90 | 367.95 | 327.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.36 | 0.00 | 83.36 | 54.98 | 327.15 | 0.00 | 0.00 | 0.00 |
February | 98.34 | 0.00 | 98.34 | 76.80 | 278.24 | 0.00 | 0.00 | 0.00 |
March | 114.09 | 0.00 | 114.09 | 113.39 | 235.80 | 0.00 | 0.00 | 0.00 |
April | 134.65 | 0.55 | 134.09 | 183.91 | 140.03 | 0.00 | 0.00 | 0.00 |
May | 152.51 | 5.58 | 146.94 | 311.54 | 37.54 | 0.00 | 0.00 | 0.00 |
June | 173.44 | 12.01 | 161.43 | 367.95 | 30.39 | 0.00 | 0.00 | 0.00 |
July | 168.31 | 6.41 | 161.90 | 353.98 | 19.08 | 0.00 | 0.00 | 0.00 |
August | 150.73 | 1.19 | 149.54 | 318.30 | 28.23 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 0.01 | 130.18 | 254.60 | 45.06 | 0.00 | 0.00 | 0.00 |
October | 113.14 | 0.00 | 113.14 | 203.54 | 87.83 | 0.00 | 0.00 | 0.00 |
November | 85.89 | 0.00 | 85.89 | 88.53 | 211.76 | 0.00 | 0.00 | 0.00 |
December | 77.49 | 0.00 | 77.49 | 58.56 | 288.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.64 | 2.15 | 121.48 | 199.57 | 143.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.49 | 0.00 | 77.49 | 54.98 | 19.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.44 | 12.01 | 161.90 | 367.95 | 327.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.36 | 0.00 | 83.36 | 54.98 | 327.15 | 0.00 | 0.00 | 0.00 |
February | 98.34 | 0.00 | 98.34 | 76.80 | 278.24 | 0.00 | 0.00 | 0.00 |
March | 114.09 | 0.00 | 114.09 | 113.39 | 235.80 | 0.00 | 0.00 | 0.00 |
April | 134.65 | 0.55 | 134.10 | 183.91 | 140.03 | 0.00 | 0.00 | 0.00 |
May | 152.51 | 5.58 | 146.94 | 311.55 | 37.54 | 0.00 | 0.00 | 0.00 |
June | 173.44 | 12.01 | 161.43 | 367.95 | 30.39 | 0.00 | 0.00 | 0.00 |
July | 168.31 | 6.41 | 161.90 | 353.98 | 19.08 | 0.00 | 0.00 | 0.00 |
August | 150.73 | 1.19 | 149.54 | 318.30 | 28.23 | 0.00 | 0.00 | 0.00 |
September | 130.20 | 0.01 | 130.19 | 254.60 | 45.06 | 0.00 | 0.00 | 0.00 |
October | 113.14 | 0.00 | 113.14 | 203.54 | 87.83 | 0.00 | 0.00 | 0.00 |
November | 85.89 | 0.00 | 85.89 | 88.53 | 211.76 | 0.00 | 0.00 | 0.00 |
December | 77.49 | 0.00 | 77.49 | 58.56 | 288.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.64 | 2.15 | 121.48 | 199.57 | 143.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.49 | 0.00 | 77.49 | 54.98 | 19.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.44 | 12.01 | 161.90 | 367.95 | 327.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.36 | 0.00 | 83.36 | 54.98 | 327.15 | 0.00 | 0.00 | 0.00 |
February | 98.34 | 0.00 | 98.34 | 76.80 | 278.24 | 0.00 | 0.00 | 0.00 |
March | 114.09 | 0.00 | 114.09 | 113.39 | 235.80 | 0.00 | 0.00 | 0.00 |
April | 134.65 | 0.55 | 134.09 | 183.91 | 140.03 | 0.00 | 0.00 | 0.00 |
May | 152.51 | 5.58 | 146.94 | 311.54 | 37.54 | 0.00 | 0.00 | 0.00 |
June | 173.44 | 12.01 | 161.43 | 367.95 | 30.39 | 0.00 | 0.00 | 0.00 |
July | 168.31 | 6.41 | 161.90 | 353.98 | 19.08 | 0.00 | 0.00 | 0.00 |
August | 150.73 | 1.19 | 149.54 | 318.30 | 28.23 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 0.01 | 130.18 | 254.60 | 45.06 | 0.00 | 0.00 | 0.00 |
October | 113.14 | 0.00 | 113.14 | 203.54 | 87.83 | 0.00 | 0.00 | 0.00 |
November | 85.89 | 0.00 | 85.89 | 88.53 | 211.76 | 0.00 | 0.00 | 0.00 |
December | 77.49 | 0.00 | 77.49 | 58.56 | 288.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.64 | 2.15 | 121.48 | 199.57 | 143.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.49 | 0.00 | 77.49 | 54.98 | 19.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.44 | 12.01 | 161.90 | 367.95 | 327.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.36 | 0.00 | 83.36 | 54.98 | 327.14 | 0.00 | 0.00 | 0.00 |
February | 98.34 | 0.00 | 98.34 | 76.79 | 278.23 | 0.00 | 0.00 | 0.00 |
March | 114.08 | 0.00 | 114.08 | 113.39 | 235.79 | 0.00 | 0.00 | 0.00 |
April | 134.64 | 0.55 | 134.09 | 183.90 | 140.03 | 0.00 | 0.00 | 0.00 |
May | 152.51 | 5.58 | 146.93 | 311.53 | 37.53 | 0.00 | 0.00 | 0.00 |
June | 173.43 | 12.01 | 161.43 | 367.93 | 30.39 | 0.00 | 0.00 | 0.00 |
July | 168.31 | 6.41 | 161.89 | 353.97 | 19.08 | 0.00 | 0.00 | 0.00 |
August | 150.72 | 1.19 | 149.54 | 318.28 | 28.23 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 0.01 | 130.18 | 254.59 | 45.06 | 0.00 | 0.00 | 0.00 |
October | 113.13 | 0.00 | 113.13 | 203.53 | 87.82 | 0.00 | 0.00 | 0.00 |
November | 85.89 | 0.00 | 85.89 | 88.53 | 211.75 | 0.00 | 0.00 | 0.00 |
December | 77.49 | 0.00 | 77.49 | 58.56 | 288.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.63 | 2.15 | 121.48 | 199.56 | 143.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.49 | 0.00 | 77.49 | 54.98 | 19.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.43 | 12.01 | 161.89 | 367.93 | 327.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 238.37 | 121.38 | 116.99 | 278.47 | 332.88 | 0.00 | 0.00 | 0.00 |
February | 265.44 | 128.15 | 137.29 | 329.65 | 280.71 | 0.00 | 0.00 | 0.00 |
March | 312.24 | 150.59 | 161.66 | 424.24 | 237.63 | 0.00 | 0.00 | 0.00 |
April | 342.65 | 154.97 | 187.68 | 533.59 | 144.04 | 0.00 | 0.00 | 0.00 |
May | 353.18 | 153.15 | 200.03 | 658.34 | 40.98 | 0.00 | 0.00 | 0.00 |
June | 358.18 | 142.05 | 216.14 | 691.54 | 30.91 | 0.00 | 0.00 | 0.00 |
July | 345.34 | 126.38 | 218.96 | 669.30 | 17.21 | 0.00 | 0.00 | 0.00 |
August | 318.22 | 109.41 | 208.81 | 617.45 | 25.99 | 0.00 | 0.00 | 0.00 |
September | 281.88 | 96.91 | 184.97 | 519.89 | 48.23 | 0.00 | 0.00 | 0.00 |
October | 278.56 | 117.55 | 161.01 | 488.12 | 90.79 | 0.00 | 0.00 | 0.00 |
November | 246.62 | 125.81 | 120.81 | 343.19 | 212.06 | 0.00 | 0.00 | 0.00 |
December | 194.18 | 87.96 | 106.22 | 237.78 | 288.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 294.67 | 126.13 | 168.54 | 483.46 | 145.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 194.18 | 87.96 | 106.22 | 237.78 | 17.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 358.18 | 154.97 | 218.96 | 691.54 | 332.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 238.37 | 121.38 | 116.99 | 278.47 | 332.88 | 0.00 | 0.00 | 0.00 |
February | 265.44 | 128.15 | 137.29 | 329.65 | 280.71 | 0.00 | 0.00 | 0.00 |
March | 312.24 | 150.59 | 161.66 | 424.24 | 237.63 | 0.00 | 0.00 | 0.00 |
April | 342.65 | 154.97 | 187.68 | 533.59 | 144.04 | 0.00 | 0.00 | 0.00 |
May | 353.18 | 153.15 | 200.03 | 658.34 | 40.98 | 0.00 | 0.00 | 0.00 |
June | 358.18 | 142.05 | 216.14 | 691.54 | 30.91 | 0.00 | 0.00 | 0.00 |
July | 345.34 | 126.38 | 218.96 | 669.30 | 17.21 | 0.00 | 0.00 | 0.00 |
August | 318.22 | 109.41 | 208.81 | 617.45 | 25.99 | 0.00 | 0.00 | 0.00 |
September | 281.88 | 96.91 | 184.97 | 519.89 | 48.23 | 0.00 | 0.00 | 0.00 |
October | 278.56 | 117.55 | 161.01 | 488.12 | 90.79 | 0.00 | 0.00 | 0.00 |
November | 246.62 | 125.81 | 120.81 | 343.19 | 212.06 | 0.00 | 0.00 | 0.00 |
December | 194.18 | 87.96 | 106.22 | 237.78 | 288.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 294.67 | 126.13 | 168.54 | 483.46 | 145.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 194.18 | 87.96 | 106.22 | 237.78 | 17.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 358.18 | 154.97 | 218.96 | 691.54 | 332.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 238.37 | 121.38 | 116.99 | 278.46 | 332.87 | 0.00 | 0.00 | 0.00 |
February | 265.43 | 128.14 | 137.29 | 329.64 | 280.71 | 0.00 | 0.00 | 0.00 |
March | 312.24 | 150.58 | 161.65 | 424.23 | 237.63 | 0.00 | 0.00 | 0.00 |
April | 342.64 | 154.97 | 187.67 | 533.58 | 144.04 | 0.00 | 0.00 | 0.00 |
May | 353.17 | 153.14 | 200.03 | 658.33 | 40.98 | 0.00 | 0.00 | 0.00 |
June | 358.18 | 142.04 | 216.13 | 691.53 | 30.91 | 0.00 | 0.00 | 0.00 |
July | 345.33 | 126.37 | 218.96 | 669.29 | 17.21 | 0.00 | 0.00 | 0.00 |
August | 318.21 | 109.40 | 208.81 | 617.44 | 25.99 | 0.00 | 0.00 | 0.00 |
September | 281.88 | 96.91 | 184.97 | 519.88 | 48.23 | 0.00 | 0.00 | 0.00 |
October | 278.55 | 117.55 | 161.01 | 488.11 | 90.79 | 0.00 | 0.00 | 0.00 |
November | 246.62 | 125.81 | 120.81 | 343.18 | 212.06 | 0.00 | 0.00 | 0.00 |
December | 194.17 | 87.96 | 106.22 | 237.78 | 288.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 294.67 | 126.13 | 168.54 | 483.45 | 145.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 194.17 | 87.96 | 106.22 | 237.78 | 17.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 358.18 | 154.97 | 218.96 | 691.53 | 332.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 481.83 | 343.63 | 138.20 | 689.30 | 296.89 | 0.00 | 0.00 | 0.00 |
February | 436.99 | 282.86 | 154.13 | 638.09 | 256.42 | 0.00 | 0.00 | 0.00 |
March | 278.98 | 125.91 | 153.08 | 418.42 | 226.01 | 0.00 | 0.00 | 0.00 |
April | 206.78 | 48.45 | 158.33 | 343.34 | 143.95 | 0.00 | 0.00 | 0.00 |
May | 158.00 | 6.71 | 151.28 | 326.54 | 38.78 | 0.00 | 0.00 | 0.00 |
June | 156.07 | 1.45 | 154.62 | 332.24 | 31.32 | 0.00 | 0.00 | 0.00 |
July | 163.38 | 3.00 | 160.38 | 345.58 | 18.84 | 0.00 | 0.00 | 0.00 |
August | 192.21 | 23.07 | 169.14 | 406.85 | 30.59 | 0.00 | 0.00 | 0.00 |
September | 230.62 | 60.78 | 169.84 | 452.31 | 48.91 | 0.00 | 0.00 | 0.00 |
October | 357.81 | 186.38 | 171.43 | 644.07 | 93.31 | 0.00 | 0.00 | 0.00 |
November | 455.33 | 313.50 | 141.83 | 706.29 | 201.34 | 0.00 | 0.00 | 0.00 |
December | 470.80 | 338.11 | 132.70 | 698.31 | 267.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 298.34 | 143.77 | 154.57 | 499.43 | 137.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 156.07 | 1.45 | 132.70 | 326.54 | 18.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 481.83 | 343.63 | 171.43 | 706.29 | 296.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 481.82 | 343.62 | 138.20 | 689.29 | 296.89 | 0.00 | 0.00 | 0.00 |
February | 436.99 | 282.85 | 154.13 | 638.09 | 256.42 | 0.00 | 0.00 | 0.00 |
March | 278.98 | 125.90 | 153.08 | 418.42 | 226.01 | 0.00 | 0.00 | 0.00 |
April | 206.78 | 48.45 | 158.33 | 343.34 | 143.95 | 0.00 | 0.00 | 0.00 |
May | 158.00 | 6.71 | 151.28 | 326.54 | 38.78 | 0.00 | 0.00 | 0.00 |
June | 156.07 | 1.45 | 154.62 | 332.23 | 31.32 | 0.00 | 0.00 | 0.00 |
July | 163.38 | 3.00 | 160.38 | 345.58 | 18.84 | 0.00 | 0.00 | 0.00 |
August | 192.21 | 23.07 | 169.14 | 406.84 | 30.59 | 0.00 | 0.00 | 0.00 |
September | 230.62 | 60.78 | 169.84 | 452.31 | 48.91 | 0.00 | 0.00 | 0.00 |
October | 357.81 | 186.38 | 171.42 | 644.07 | 93.31 | 0.00 | 0.00 | 0.00 |
November | 455.33 | 313.50 | 141.83 | 706.29 | 201.34 | 0.00 | 0.00 | 0.00 |
December | 470.80 | 338.10 | 132.70 | 698.31 | 267.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 298.34 | 143.77 | 154.57 | 499.43 | 137.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 156.07 | 1.45 | 132.70 | 326.54 | 18.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 481.82 | 343.62 | 171.42 | 706.29 | 296.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 481.83 | 343.63 | 138.20 | 689.30 | 296.89 | 0.00 | 0.00 | 0.00 |
February | 436.99 | 282.86 | 154.13 | 638.09 | 256.42 | 0.00 | 0.00 | 0.00 |
March | 278.98 | 125.91 | 153.08 | 418.42 | 226.01 | 0.00 | 0.00 | 0.00 |
April | 206.78 | 48.45 | 158.33 | 343.34 | 143.95 | 0.00 | 0.00 | 0.00 |
May | 158.00 | 6.71 | 151.28 | 326.54 | 38.78 | 0.00 | 0.00 | 0.00 |
June | 156.07 | 1.45 | 154.62 | 332.24 | 31.32 | 0.00 | 0.00 | 0.00 |
July | 163.38 | 3.00 | 160.38 | 345.58 | 18.84 | 0.00 | 0.00 | 0.00 |
August | 192.21 | 23.07 | 169.14 | 406.85 | 30.59 | 0.00 | 0.00 | 0.00 |
September | 230.62 | 60.78 | 169.84 | 452.31 | 48.91 | 0.00 | 0.00 | 0.00 |
October | 357.81 | 186.38 | 171.43 | 644.07 | 93.31 | 0.00 | 0.00 | 0.00 |
November | 455.33 | 313.50 | 141.83 | 706.29 | 201.34 | 0.00 | 0.00 | 0.00 |
December | 470.80 | 338.11 | 132.70 | 698.31 | 267.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 298.34 | 143.77 | 154.57 | 499.43 | 137.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 156.07 | 1.45 | 132.70 | 326.54 | 18.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 481.83 | 343.63 | 171.43 | 706.29 | 296.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 481.82 | 343.62 | 138.20 | 689.29 | 296.89 | 0.00 | 0.00 | 0.00 |
February | 436.99 | 282.85 | 154.13 | 638.09 | 256.42 | 0.00 | 0.00 | 0.00 |
March | 278.98 | 125.90 | 153.08 | 418.42 | 226.01 | 0.00 | 0.00 | 0.00 |
April | 206.78 | 48.45 | 158.33 | 343.34 | 143.95 | 0.00 | 0.00 | 0.00 |
May | 158.00 | 6.71 | 151.28 | 326.54 | 38.78 | 0.00 | 0.00 | 0.00 |
June | 156.07 | 1.45 | 154.62 | 332.23 | 31.32 | 0.00 | 0.00 | 0.00 |
July | 163.38 | 3.00 | 160.38 | 345.58 | 18.84 | 0.00 | 0.00 | 0.00 |
August | 192.21 | 23.07 | 169.14 | 406.84 | 30.59 | 0.00 | 0.00 | 0.00 |
September | 230.62 | 60.78 | 169.84 | 452.31 | 48.91 | 0.00 | 0.00 | 0.00 |
October | 357.81 | 186.38 | 171.42 | 644.07 | 93.31 | 0.00 | 0.00 | 0.00 |
November | 455.33 | 313.50 | 141.83 | 706.29 | 201.34 | 0.00 | 0.00 | 0.00 |
December | 470.80 | 338.10 | 132.70 | 698.31 | 267.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 298.34 | 143.77 | 154.57 | 499.43 | 137.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 156.07 | 1.45 | 132.70 | 326.54 | 18.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 481.82 | 343.62 | 171.42 | 706.29 | 296.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 481.81 | 343.61 | 138.20 | 689.27 | 296.88 | 0.00 | 0.00 | 0.00 |
February | 436.97 | 282.84 | 154.13 | 638.06 | 256.41 | 0.00 | 0.00 | 0.00 |
March | 278.97 | 125.90 | 153.07 | 418.40 | 226.00 | 0.00 | 0.00 | 0.00 |
April | 206.77 | 48.45 | 158.32 | 343.33 | 143.94 | 0.00 | 0.00 | 0.00 |
May | 157.99 | 6.71 | 151.27 | 326.52 | 38.77 | 0.00 | 0.00 | 0.00 |
June | 156.07 | 1.45 | 154.61 | 332.22 | 31.31 | 0.00 | 0.00 | 0.00 |
July | 163.38 | 3.00 | 160.37 | 345.56 | 18.83 | 0.00 | 0.00 | 0.00 |
August | 192.20 | 23.07 | 169.13 | 406.83 | 30.59 | 0.00 | 0.00 | 0.00 |
September | 230.61 | 60.78 | 169.84 | 452.29 | 48.91 | 0.00 | 0.00 | 0.00 |
October | 357.79 | 186.38 | 171.42 | 644.04 | 93.31 | 0.00 | 0.00 | 0.00 |
November | 455.31 | 313.49 | 141.83 | 706.26 | 201.33 | 0.00 | 0.00 | 0.00 |
December | 470.78 | 338.09 | 132.69 | 698.28 | 267.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 298.33 | 143.77 | 154.56 | 499.41 | 137.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 156.07 | 1.45 | 132.69 | 326.52 | 18.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 481.81 | 343.61 | 171.42 | 706.26 | 296.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 253.55 | 137.10 | 116.44 | 314.66 | 376.75 | 0.00 | 0.00 | 0.00 |
February | 287.07 | 145.30 | 141.77 | 367.07 | 335.24 | 0.00 | 0.00 | 0.00 |
March | 282.94 | 125.25 | 157.69 | 374.71 | 297.08 | 0.00 | 0.00 | 0.00 |
April | 351.42 | 161.66 | 189.76 | 533.59 | 195.27 | 0.00 | 0.00 | 0.00 |
May | 292.25 | 95.20 | 197.05 | 550.63 | 58.68 | 0.00 | 0.00 | 0.00 |
June | 324.65 | 113.84 | 210.81 | 620.43 | 54.02 | 0.00 | 0.00 | 0.00 |
July | 296.35 | 82.20 | 214.14 | 562.32 | 41.59 | 0.00 | 0.00 | 0.00 |
August | 299.64 | 91.73 | 207.92 | 566.45 | 58.80 | 0.00 | 0.00 | 0.00 |
September | 275.92 | 94.65 | 181.27 | 504.25 | 67.59 | 0.00 | 0.00 | 0.00 |
October | 282.49 | 122.06 | 160.43 | 490.50 | 123.51 | 0.00 | 0.00 | 0.00 |
November | 242.12 | 121.68 | 120.44 | 339.63 | 270.64 | 0.00 | 0.00 | 0.00 |
December | 232.90 | 123.85 | 109.05 | 295.86 | 361.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 284.95 | 117.60 | 167.35 | 460.34 | 185.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 232.90 | 82.20 | 109.05 | 295.86 | 41.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.42 | 161.66 | 214.14 | 620.43 | 376.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 253.55 | 137.10 | 116.44 | 314.66 | 376.75 | 0.00 | 0.00 | 0.00 |
February | 287.07 | 145.30 | 141.77 | 367.07 | 335.24 | 0.00 | 0.00 | 0.00 |
March | 282.94 | 125.25 | 157.69 | 374.71 | 297.08 | 0.00 | 0.00 | 0.00 |
April | 351.42 | 161.66 | 189.76 | 533.59 | 195.27 | 0.00 | 0.00 | 0.00 |
May | 292.25 | 95.20 | 197.05 | 550.63 | 58.68 | 0.00 | 0.00 | 0.00 |
June | 324.65 | 113.84 | 210.81 | 620.43 | 54.02 | 0.00 | 0.00 | 0.00 |
July | 296.35 | 82.20 | 214.14 | 562.32 | 41.59 | 0.00 | 0.00 | 0.00 |
August | 299.64 | 91.73 | 207.92 | 566.45 | 58.80 | 0.00 | 0.00 | 0.00 |
September | 275.92 | 94.65 | 181.27 | 504.25 | 67.59 | 0.00 | 0.00 | 0.00 |
October | 282.49 | 122.06 | 160.43 | 490.50 | 123.51 | 0.00 | 0.00 | 0.00 |
November | 242.12 | 121.68 | 120.44 | 339.63 | 270.64 | 0.00 | 0.00 | 0.00 |
December | 232.90 | 123.85 | 109.05 | 295.86 | 361.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 284.95 | 117.60 | 167.35 | 460.34 | 185.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 232.90 | 82.20 | 109.05 | 295.86 | 41.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.42 | 161.66 | 214.14 | 620.43 | 376.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 253.54 | 137.10 | 116.44 | 314.65 | 376.75 | 0.00 | 0.00 | 0.00 |
February | 287.07 | 145.30 | 141.77 | 367.06 | 335.23 | 0.00 | 0.00 | 0.00 |
March | 282.93 | 125.25 | 157.69 | 374.70 | 297.08 | 0.00 | 0.00 | 0.00 |
April | 351.41 | 161.66 | 189.76 | 533.58 | 195.27 | 0.00 | 0.00 | 0.00 |
May | 292.24 | 95.20 | 197.04 | 550.62 | 58.68 | 0.00 | 0.00 | 0.00 |
June | 324.65 | 113.84 | 210.81 | 620.42 | 54.02 | 0.00 | 0.00 | 0.00 |
July | 296.34 | 82.20 | 214.14 | 562.31 | 41.59 | 0.00 | 0.00 | 0.00 |
August | 299.64 | 91.72 | 207.92 | 566.44 | 58.80 | 0.00 | 0.00 | 0.00 |
September | 275.92 | 94.65 | 181.26 | 504.24 | 67.59 | 0.00 | 0.00 | 0.00 |
October | 282.48 | 122.06 | 160.42 | 490.49 | 123.50 | 0.00 | 0.00 | 0.00 |
November | 242.12 | 121.68 | 120.44 | 339.62 | 270.63 | 0.00 | 0.00 | 0.00 |
December | 232.90 | 123.85 | 109.05 | 295.85 | 361.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 284.94 | 117.59 | 167.35 | 460.33 | 185.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 232.90 | 82.20 | 109.05 | 295.85 | 41.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.41 | 161.66 | 214.14 | 620.42 | 376.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 416.80 | 0.00 | 416.80 | 332.34 | 1436.20 | 0.00 | 0.00 | 0.00 |
February | 491.72 | 0.00 | 491.72 | 441.01 | 1210.23 | 0.00 | 0.00 | 0.00 |
March | 570.44 | 0.00 | 570.44 | 622.28 | 1041.42 | 0.00 | 0.00 | 0.00 |
April | 673.25 | 2.76 | 670.48 | 949.69 | 654.22 | 0.00 | 0.00 | 0.00 |
May | 762.58 | 27.89 | 734.69 | 1567.97 | 180.07 | 0.00 | 0.00 | 0.00 |
June | 867.22 | 60.05 | 807.17 | 1848.72 | 155.96 | 0.00 | 0.00 | 0.00 |
July | 841.58 | 32.06 | 809.51 | 1782.36 | 100.16 | 0.00 | 0.00 | 0.00 |
August | 753.65 | 5.93 | 747.72 | 1610.03 | 143.96 | 0.00 | 0.00 | 0.00 |
September | 650.98 | 0.05 | 650.93 | 1289.32 | 203.22 | 0.00 | 0.00 | 0.00 |
October | 565.69 | 0.00 | 565.69 | 1041.90 | 401.04 | 0.00 | 0.00 | 0.00 |
November | 429.45 | 0.00 | 429.45 | 493.62 | 921.39 | 0.00 | 0.00 | 0.00 |
December | 387.46 | 0.00 | 387.46 | 350.99 | 1229.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 618.19 | 10.76 | 607.43 | 1031.05 | 636.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 387.46 | 0.00 | 387.46 | 332.34 | 100.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 867.22 | 60.05 | 809.51 | 1848.72 | 1436.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 715.11 | 364.14 | 350.98 | 865.32 | 903.99 | 0.00 | 0.00 | 0.00 |
February | 796.30 | 384.43 | 411.87 | 1012.13 | 769.43 | 0.00 | 0.00 | 0.00 |
March | 936.72 | 451.75 | 484.96 | 1279.22 | 671.05 | 0.00 | 0.00 | 0.00 |
April | 1027.94 | 464.91 | 563.03 | 1587.91 | 441.41 | 0.00 | 0.00 | 0.00 |
May | 1059.53 | 459.43 | 600.10 | 1959.90 | 127.75 | 0.00 | 0.00 | 0.00 |
June | 1074.54 | 426.13 | 648.41 | 2058.56 | 109.35 | 0.00 | 0.00 | 0.00 |
July | 1036.01 | 379.12 | 656.88 | 1987.75 | 70.58 | 0.00 | 0.00 | 0.00 |
August | 954.65 | 328.22 | 626.43 | 1835.05 | 101.63 | 0.00 | 0.00 | 0.00 |
September | 845.64 | 290.73 | 554.91 | 1552.07 | 141.66 | 0.00 | 0.00 | 0.00 |
October | 835.67 | 352.65 | 483.02 | 1456.94 | 269.76 | 0.00 | 0.00 | 0.00 |
November | 739.86 | 377.43 | 362.43 | 1038.80 | 595.33 | 0.00 | 0.00 | 0.00 |
December | 582.53 | 263.87 | 318.66 | 735.35 | 791.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 884.01 | 378.40 | 505.61 | 1449.77 | 414.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.53 | 263.87 | 318.66 | 735.35 | 70.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1074.54 | 464.91 | 656.88 | 2058.56 | 903.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2409.18 | 1718.17 | 691.02 | 3426.32 | 1447.73 | 0.00 | 0.00 | 0.00 |
February | 2184.99 | 1414.31 | 770.68 | 3177.27 | 1240.55 | 0.00 | 0.00 | 0.00 |
March | 1394.95 | 629.54 | 765.41 | 2091.98 | 1078.98 | 0.00 | 0.00 | 0.00 |
April | 1033.92 | 242.27 | 791.64 | 1719.76 | 702.73 | 0.00 | 0.00 | 0.00 |
May | 789.99 | 33.57 | 756.41 | 1639.95 | 187.83 | 0.00 | 0.00 | 0.00 |
June | 780.37 | 7.27 | 773.10 | 1672.22 | 159.00 | 0.00 | 0.00 | 0.00 |
July | 816.92 | 15.01 | 801.91 | 1742.02 | 97.47 | 0.00 | 0.00 | 0.00 |
August | 961.07 | 115.36 | 845.71 | 2043.46 | 158.38 | 0.00 | 0.00 | 0.00 |
September | 1153.12 | 303.90 | 849.22 | 2257.08 | 235.03 | 0.00 | 0.00 | 0.00 |
October | 1789.07 | 931.94 | 857.14 | 3203.31 | 465.77 | 0.00 | 0.00 | 0.00 |
November | 2276.71 | 1567.54 | 709.17 | 3515.06 | 982.56 | 0.00 | 0.00 | 0.00 |
December | 2354.07 | 1690.56 | 663.50 | 3481.19 | 1286.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1491.72 | 718.87 | 772.84 | 2494.14 | 667.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 780.37 | 7.27 | 663.50 | 1639.95 | 97.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2409.18 | 1718.17 | 857.14 | 3515.06 | 1447.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 760.64 | 411.31 | 349.33 | 981.55 | 995.63 | 0.00 | 0.00 | 0.00 |
February | 861.21 | 435.89 | 425.32 | 1147.23 | 857.56 | 0.00 | 0.00 | 0.00 |
March | 848.81 | 375.75 | 473.06 | 1169.97 | 744.20 | 0.00 | 0.00 | 0.00 |
April | 1054.25 | 484.97 | 569.27 | 1639.94 | 501.71 | 0.00 | 0.00 | 0.00 |
May | 876.73 | 285.60 | 591.13 | 1665.74 | 155.85 | 0.00 | 0.00 | 0.00 |
June | 973.95 | 341.51 | 632.43 | 1883.28 | 139.50 | 0.00 | 0.00 | 0.00 |
July | 889.03 | 246.60 | 642.43 | 1724.52 | 94.93 | 0.00 | 0.00 | 0.00 |
August | 898.92 | 275.17 | 623.75 | 1743.34 | 132.50 | 0.00 | 0.00 | 0.00 |
September | 827.76 | 283.96 | 543.80 | 1526.86 | 171.73 | 0.00 | 0.00 | 0.00 |
October | 847.45 | 366.17 | 481.28 | 1497.24 | 318.13 | 0.00 | 0.00 | 0.00 |
November | 726.37 | 365.04 | 361.32 | 1065.59 | 670.90 | 0.00 | 0.00 | 0.00 |
December | 698.70 | 371.56 | 327.14 | 945.10 | 868.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 854.83 | 352.79 | 502.04 | 1416.83 | 468.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 698.70 | 246.60 | 327.14 | 945.10 | 94.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1054.25 | 484.97 | 642.43 | 1883.28 | 995.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 416.80 | 0.00 | 416.80 | 358.25 | 1321.37 | 0.00 | 0.00 | 0.00 |
February | 491.72 | 0.00 | 491.72 | 465.81 | 1110.46 | 0.00 | 0.00 | 0.00 |
March | 570.44 | 0.00 | 570.44 | 640.18 | 974.01 | 0.00 | 0.00 | 0.00 |
April | 673.25 | 2.76 | 670.48 | 949.43 | 636.22 | 0.00 | 0.00 | 0.00 |
May | 762.58 | 27.89 | 734.69 | 1540.87 | 193.95 | 0.00 | 0.00 | 0.00 |
June | 867.22 | 60.05 | 807.17 | 1817.36 | 169.70 | 0.00 | 0.00 | 0.00 |
July | 841.58 | 32.06 | 809.51 | 1747.47 | 111.86 | 0.00 | 0.00 | 0.00 |
August | 753.65 | 5.93 | 747.72 | 1581.81 | 156.00 | 0.00 | 0.00 | 0.00 |
September | 650.98 | 0.05 | 650.93 | 1263.56 | 214.62 | 0.00 | 0.00 | 0.00 |
October | 565.69 | 0.00 | 565.69 | 1032.39 | 394.36 | 0.00 | 0.00 | 0.00 |
November | 429.45 | 0.00 | 429.45 | 518.52 | 843.88 | 0.00 | 0.00 | 0.00 |
December | 387.46 | 0.00 | 387.46 | 375.82 | 1126.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 618.19 | 10.76 | 607.43 | 1027.64 | 601.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 387.46 | 0.00 | 387.46 | 358.25 | 111.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 867.22 | 60.05 | 809.51 | 1817.36 | 1321.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 715.11 | 364.14 | 350.98 | 893.71 | 836.28 | 0.00 | 0.00 | 0.00 |
February | 796.30 | 384.43 | 411.87 | 1034.57 | 713.13 | 0.00 | 0.00 | 0.00 |
March | 936.72 | 451.75 | 484.96 | 1289.19 | 636.45 | 0.00 | 0.00 | 0.00 |
April | 1027.94 | 464.91 | 563.03 | 1582.88 | 435.31 | 0.00 | 0.00 | 0.00 |
May | 1059.53 | 459.43 | 600.10 | 1939.73 | 137.11 | 0.00 | 0.00 | 0.00 |
June | 1074.54 | 426.13 | 648.41 | 2036.64 | 118.95 | 0.00 | 0.00 | 0.00 |
July | 1036.01 | 379.12 | 656.88 | 1963.89 | 78.54 | 0.00 | 0.00 | 0.00 |
August | 954.65 | 328.22 | 626.43 | 1814.69 | 110.04 | 0.00 | 0.00 | 0.00 |
September | 845.64 | 290.73 | 554.91 | 1534.30 | 150.29 | 0.00 | 0.00 | 0.00 |
October | 835.67 | 352.65 | 483.02 | 1447.54 | 267.93 | 0.00 | 0.00 | 0.00 |
November | 739.86 | 377.43 | 362.43 | 1055.20 | 555.82 | 0.00 | 0.00 | 0.00 |
December | 582.53 | 263.87 | 318.66 | 755.77 | 732.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 884.01 | 378.40 | 505.61 | 1447.89 | 396.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.53 | 263.87 | 318.66 | 755.77 | 78.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1074.54 | 464.91 | 656.88 | 2036.64 | 836.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2409.18 | 1718.17 | 691.02 | 3456.51 | 1351.44 | 0.00 | 0.00 | 0.00 |
February | 2184.99 | 1414.31 | 770.68 | 3204.20 | 1159.38 | 0.00 | 0.00 | 0.00 |
March | 1394.95 | 629.54 | 765.41 | 2104.95 | 1020.44 | 0.00 | 0.00 | 0.00 |
April | 1033.92 | 242.27 | 791.64 | 1713.90 | 687.74 | 0.00 | 0.00 | 0.00 |
May | 789.99 | 33.57 | 756.41 | 1612.80 | 202.15 | 0.00 | 0.00 | 0.00 |
June | 780.37 | 7.27 | 773.10 | 1642.19 | 173.39 | 0.00 | 0.00 | 0.00 |
July | 816.92 | 15.01 | 801.91 | 1706.36 | 108.61 | 0.00 | 0.00 | 0.00 |
August | 961.07 | 115.36 | 845.71 | 2014.09 | 171.68 | 0.00 | 0.00 | 0.00 |
September | 1153.12 | 303.90 | 849.22 | 2232.05 | 247.75 | 0.00 | 0.00 | 0.00 |
October | 1789.07 | 931.94 | 857.14 | 3186.71 | 465.14 | 0.00 | 0.00 | 0.00 |
November | 2276.71 | 1567.54 | 709.17 | 3527.21 | 932.92 | 0.00 | 0.00 | 0.00 |
December | 2354.07 | 1690.56 | 663.50 | 3502.53 | 1202.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1491.72 | 718.87 | 772.84 | 2488.44 | 640.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 780.37 | 7.27 | 663.50 | 1612.80 | 108.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2409.18 | 1718.17 | 857.14 | 3527.21 | 1351.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 760.64 | 411.31 | 349.33 | 996.45 | 929.65 | 0.00 | 0.00 | 0.00 |
February | 861.21 | 435.89 | 425.32 | 1160.22 | 800.98 | 0.00 | 0.00 | 0.00 |
March | 848.81 | 375.75 | 473.06 | 1177.42 | 704.97 | 0.00 | 0.00 | 0.00 |
April | 1054.25 | 484.97 | 569.27 | 1635.86 | 489.85 | 0.00 | 0.00 | 0.00 |
May | 876.73 | 285.60 | 591.13 | 1650.31 | 162.38 | 0.00 | 0.00 | 0.00 |
June | 973.95 | 341.51 | 632.43 | 1865.32 | 145.82 | 0.00 | 0.00 | 0.00 |
July | 889.03 | 246.60 | 642.43 | 1705.62 | 99.33 | 0.00 | 0.00 | 0.00 |
August | 898.92 | 275.17 | 623.75 | 1726.33 | 138.82 | 0.00 | 0.00 | 0.00 |
September | 827.76 | 283.96 | 543.80 | 1513.35 | 177.01 | 0.00 | 0.00 | 0.00 |
October | 847.45 | 366.17 | 481.28 | 1490.01 | 314.31 | 0.00 | 0.00 | 0.00 |
November | 726.37 | 365.04 | 361.32 | 1077.10 | 628.61 | 0.00 | 0.00 | 0.00 |
December | 698.70 | 371.56 | 327.14 | 958.33 | 809.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 854.83 | 352.79 | 502.04 | 1413.90 | 448.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 698.70 | 246.60 | 327.14 | 958.33 | 99.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1054.25 | 484.97 | 642.43 | 1865.32 | 929.65 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223271E+09 | 0.00 | 0.223271E+09 | 0.147271E+09 | 0.876244E+09 |
February | 0.237915E+09 | 0.00 | 0.237915E+09 | 0.185789E+09 | 0.673126E+09 |
March | 0.305574E+09 | 0.00 | 0.305574E+09 | 0.303708E+09 | 0.631555E+09 |
April | 0.349011E+09 | 1432452.17 | 0.347579E+09 | 0.476702E+09 | 0.362962E+09 |
May | 0.408498E+09 | 14941839.27 | 0.393557E+09 | 0.834449E+09 | 0.100536E+09 |
June | 0.449564E+09 | 31128636.17 | 0.418436E+09 | 0.953731E+09 | 78777030.49 |
July | 0.450816E+09 | 17175142.31 | 0.433641E+09 | 0.948119E+09 | 51096605.22 |
August | 0.403714E+09 | 3175239.04 | 0.400538E+09 | 0.852530E+09 | 75608134.15 |
September | 0.337469E+09 | 25991.58 | 0.337443E+09 | 0.659922E+09 | 0.116802E+09 |
October | 0.303029E+09 | 0.00 | 0.303029E+09 | 0.545173E+09 | 0.235238E+09 |
November | 0.222627E+09 | 0.00 | 0.222627E+09 | 0.229479E+09 | 0.548877E+09 |
December | 0.207556E+09 | 0.00 | 0.207556E+09 | 0.156847E+09 | 0.771900E+09 |
Annual Sum or Average | 0.389904E+10 | 67879300.53 | 0.383116E+10 | 0.629372E+10 | 0.452272E+10 |
Minimum of Months | 0.207556E+09 | 0.00 | 0.207556E+09 | 0.147271E+09 | 51096605.22 |
Maximum of Months | 0.450816E+09 | 31128636.17 | 0.433641E+09 | 0.953731E+09 | 0.876244E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223268E+09 | 0.00 | 0.223268E+09 | 0.147269E+09 | 0.876242E+09 |
February | 0.237912E+09 | 0.00 | 0.237912E+09 | 0.185787E+09 | 0.673125E+09 |
March | 0.305570E+09 | 0.00 | 0.305570E+09 | 0.303704E+09 | 0.631554E+09 |
April | 0.349007E+09 | 1432420.68 | 0.347574E+09 | 0.476696E+09 | 0.362960E+09 |
May | 0.408493E+09 | 14941510.79 | 0.393551E+09 | 0.834440E+09 | 0.100535E+09 |
June | 0.449558E+09 | 31127951.84 | 0.418430E+09 | 0.953721E+09 | 78775759.13 |
July | 0.450809E+09 | 17174764.73 | 0.433634E+09 | 0.948109E+09 | 51095465.99 |
August | 0.403708E+09 | 3175169.23 | 0.400533E+09 | 0.852522E+09 | 75606900.80 |
September | 0.337464E+09 | 25991.01 | 0.337438E+09 | 0.659915E+09 | 0.116801E+09 |
October | 0.303025E+09 | 0.00 | 0.303025E+09 | 0.545167E+09 | 0.235237E+09 |
November | 0.222624E+09 | 0.00 | 0.222624E+09 | 0.229476E+09 | 0.548875E+09 |
December | 0.207553E+09 | 0.00 | 0.207553E+09 | 0.156845E+09 | 0.771899E+09 |
Annual Sum or Average | 0.389899E+10 | 67877808.28 | 0.383111E+10 | 0.629365E+10 | 0.452271E+10 |
Minimum of Months | 0.207553E+09 | 0.00 | 0.207553E+09 | 0.147269E+09 | 51095465.99 |
Maximum of Months | 0.450809E+09 | 31127951.84 | 0.433634E+09 | 0.953721E+09 | 0.876242E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223269E+09 | 0.00 | 0.223269E+09 | 0.147270E+09 | 0.876243E+09 |
February | 0.237913E+09 | 0.00 | 0.237913E+09 | 0.185787E+09 | 0.673125E+09 |
March | 0.305571E+09 | 0.00 | 0.305571E+09 | 0.303705E+09 | 0.631555E+09 |
April | 0.349008E+09 | 1432431.18 | 0.347576E+09 | 0.476698E+09 | 0.362961E+09 |
May | 0.408494E+09 | 14941620.28 | 0.393553E+09 | 0.834443E+09 | 0.100535E+09 |
June | 0.449560E+09 | 31128179.95 | 0.418432E+09 | 0.953724E+09 | 78776182.92 |
July | 0.450811E+09 | 17174890.59 | 0.433636E+09 | 0.948113E+09 | 51095845.74 |
August | 0.403710E+09 | 3175192.50 | 0.400535E+09 | 0.852524E+09 | 75607311.85 |
September | 0.337466E+09 | 25991.20 | 0.337440E+09 | 0.659917E+09 | 0.116801E+09 |
October | 0.303026E+09 | 0.00 | 0.303026E+09 | 0.545169E+09 | 0.235237E+09 |
November | 0.222625E+09 | 0.00 | 0.222625E+09 | 0.229477E+09 | 0.548876E+09 |
December | 0.207554E+09 | 0.00 | 0.207554E+09 | 0.156845E+09 | 0.771899E+09 |
Annual Sum or Average | 0.389901E+10 | 67878305.70 | 0.383113E+10 | 0.629367E+10 | 0.452271E+10 |
Minimum of Months | 0.207554E+09 | 0.00 | 0.207554E+09 | 0.147270E+09 | 51095845.74 |
Maximum of Months | 0.450811E+09 | 31128179.95 | 0.433636E+09 | 0.953724E+09 | 0.876243E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223268E+09 | 0.00 | 0.223268E+09 | 0.147269E+09 | 0.876242E+09 |
February | 0.237912E+09 | 0.00 | 0.237912E+09 | 0.185787E+09 | 0.673125E+09 |
March | 0.305570E+09 | 0.00 | 0.305570E+09 | 0.303704E+09 | 0.631554E+09 |
April | 0.349007E+09 | 1432420.68 | 0.347574E+09 | 0.476696E+09 | 0.362960E+09 |
May | 0.408493E+09 | 14941510.79 | 0.393551E+09 | 0.834440E+09 | 0.100535E+09 |
June | 0.449558E+09 | 31127951.84 | 0.418430E+09 | 0.953721E+09 | 78775759.13 |
July | 0.450809E+09 | 17174764.73 | 0.433634E+09 | 0.948109E+09 | 51095465.99 |
August | 0.403708E+09 | 3175169.23 | 0.400533E+09 | 0.852522E+09 | 75606900.80 |
September | 0.337464E+09 | 25991.01 | 0.337438E+09 | 0.659915E+09 | 0.116801E+09 |
October | 0.303025E+09 | 0.00 | 0.303025E+09 | 0.545167E+09 | 0.235237E+09 |
November | 0.222624E+09 | 0.00 | 0.222624E+09 | 0.229476E+09 | 0.548875E+09 |
December | 0.207553E+09 | 0.00 | 0.207553E+09 | 0.156845E+09 | 0.771899E+09 |
Annual Sum or Average | 0.389899E+10 | 67877808.28 | 0.383111E+10 | 0.629365E+10 | 0.452271E+10 |
Minimum of Months | 0.207553E+09 | 0.00 | 0.207553E+09 | 0.147269E+09 | 51095465.99 |
Maximum of Months | 0.450809E+09 | 31127951.84 | 0.433634E+09 | 0.953721E+09 | 0.876242E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223260E+09 | 0.00 | 0.223260E+09 | 0.147263E+09 | 0.876207E+09 |
February | 0.237903E+09 | 0.00 | 0.237903E+09 | 0.185779E+09 | 0.673098E+09 |
March | 0.305558E+09 | 0.00 | 0.305558E+09 | 0.303692E+09 | 0.631529E+09 |
April | 0.348993E+09 | 1432368.20 | 0.347561E+09 | 0.476678E+09 | 0.362946E+09 |
May | 0.408477E+09 | 14940963.33 | 0.393536E+09 | 0.834408E+09 | 0.100531E+09 |
June | 0.449541E+09 | 31126811.29 | 0.418414E+09 | 0.953684E+09 | 78772796.01 |
July | 0.450792E+09 | 17174135.44 | 0.433618E+09 | 0.948073E+09 | 51093596.49 |
August | 0.403693E+09 | 3175052.89 | 0.400517E+09 | 0.852489E+09 | 75604059.02 |
September | 0.337451E+09 | 25990.05 | 0.337425E+09 | 0.659890E+09 | 0.116796E+09 |
October | 0.303013E+09 | 0.00 | 0.303013E+09 | 0.545146E+09 | 0.235228E+09 |
November | 0.222615E+09 | 0.00 | 0.222615E+09 | 0.229467E+09 | 0.548853E+09 |
December | 0.207545E+09 | 0.00 | 0.207545E+09 | 0.156839E+09 | 0.771868E+09 |
Annual Sum or Average | 0.389884E+10 | 67875321.21 | 0.383097E+10 | 0.629341E+10 | 0.452253E+10 |
Minimum of Months | 0.207545E+09 | 0.00 | 0.207545E+09 | 0.147263E+09 | 51093596.49 |
Maximum of Months | 0.450792E+09 | 31126811.29 | 0.433618E+09 | 0.953684E+09 | 0.876207E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.638461E+09 | 0.325107E+09 | 0.313354E+09 | 0.745849E+09 | 0.891583E+09 |
February | 0.642146E+09 | 0.310011E+09 | 0.332135E+09 | 0.797483E+09 | 0.679099E+09 |
March | 0.836308E+09 | 0.403329E+09 | 0.432980E+09 | 0.113627E+10 | 0.636472E+09 |
April | 0.888146E+09 | 0.401684E+09 | 0.486462E+09 | 0.138307E+10 | 0.373362E+09 |
May | 0.945954E+09 | 0.410184E+09 | 0.535770E+09 | 0.176331E+10 | 0.109758E+09 |
June | 0.928410E+09 | 0.368182E+09 | 0.560228E+09 | 0.179248E+10 | 80108736.54 |
July | 0.924957E+09 | 0.338484E+09 | 0.586473E+09 | 0.179265E+10 | 46093921.93 |
August | 0.852319E+09 | 0.293034E+09 | 0.559285E+09 | 0.165378E+10 | 69603779.80 |
September | 0.730643E+09 | 0.251193E+09 | 0.479451E+09 | 0.134754E+10 | 0.125022E+09 |
October | 0.746094E+09 | 0.314849E+09 | 0.431244E+09 | 0.130739E+10 | 0.243165E+09 |
November | 0.639250E+09 | 0.326106E+09 | 0.313143E+09 | 0.889552E+09 | 0.549669E+09 |
December | 0.520086E+09 | 0.235587E+09 | 0.284498E+09 | 0.636881E+09 | 0.774030E+09 |
Annual Sum or Average | 0.929277E+10 | 0.397775E+10 | 0.531502E+10 | 0.152463E+11 | 0.457797E+10 |
Minimum of Months | 0.520086E+09 | 0.235587E+09 | 0.284498E+09 | 0.636881E+09 | 46093921.93 |
Maximum of Months | 0.945954E+09 | 0.410184E+09 | 0.586473E+09 | 0.179265E+10 | 0.891583E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.638461E+09 | 0.325107E+09 | 0.313354E+09 | 0.745849E+09 | 0.891583E+09 |
February | 0.642146E+09 | 0.310011E+09 | 0.332135E+09 | 0.797483E+09 | 0.679099E+09 |
March | 0.836308E+09 | 0.403329E+09 | 0.432980E+09 | 0.113627E+10 | 0.636472E+09 |
April | 0.888146E+09 | 0.401684E+09 | 0.486462E+09 | 0.138307E+10 | 0.373362E+09 |
May | 0.945954E+09 | 0.410184E+09 | 0.535770E+09 | 0.176331E+10 | 0.109758E+09 |
June | 0.928410E+09 | 0.368182E+09 | 0.560228E+09 | 0.179248E+10 | 80108736.54 |
July | 0.924957E+09 | 0.338484E+09 | 0.586473E+09 | 0.179265E+10 | 46093921.93 |
August | 0.852319E+09 | 0.293034E+09 | 0.559285E+09 | 0.165378E+10 | 69603779.80 |
September | 0.730643E+09 | 0.251193E+09 | 0.479451E+09 | 0.134754E+10 | 0.125022E+09 |
October | 0.746094E+09 | 0.314849E+09 | 0.431244E+09 | 0.130739E+10 | 0.243165E+09 |
November | 0.639250E+09 | 0.326106E+09 | 0.313143E+09 | 0.889552E+09 | 0.549669E+09 |
December | 0.520086E+09 | 0.235587E+09 | 0.284498E+09 | 0.636881E+09 | 0.774030E+09 |
Annual Sum or Average | 0.929277E+10 | 0.397775E+10 | 0.531502E+10 | 0.152463E+11 | 0.457797E+10 |
Minimum of Months | 0.520086E+09 | 0.235587E+09 | 0.284498E+09 | 0.636881E+09 | 46093921.93 |
Maximum of Months | 0.945954E+09 | 0.410184E+09 | 0.586473E+09 | 0.179265E+10 | 0.891583E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.638450E+09 | 0.325101E+09 | 0.313349E+09 | 0.745835E+09 | 0.891567E+09 |
February | 0.642135E+09 | 0.310006E+09 | 0.332129E+09 | 0.797468E+09 | 0.679087E+09 |
March | 0.836293E+09 | 0.403321E+09 | 0.432972E+09 | 0.113625E+10 | 0.636460E+09 |
April | 0.888130E+09 | 0.401677E+09 | 0.486453E+09 | 0.138305E+10 | 0.373355E+09 |
May | 0.945937E+09 | 0.410176E+09 | 0.535761E+09 | 0.176328E+10 | 0.109756E+09 |
June | 0.928393E+09 | 0.368175E+09 | 0.560218E+09 | 0.179245E+10 | 80107272.78 |
July | 0.924940E+09 | 0.338478E+09 | 0.586462E+09 | 0.179262E+10 | 46093079.69 |
August | 0.852304E+09 | 0.293029E+09 | 0.559275E+09 | 0.165375E+10 | 69602507.98 |
September | 0.730630E+09 | 0.251188E+09 | 0.479442E+09 | 0.134752E+10 | 0.125020E+09 |
October | 0.746080E+09 | 0.314843E+09 | 0.431237E+09 | 0.130736E+10 | 0.243161E+09 |
November | 0.639238E+09 | 0.326100E+09 | 0.313138E+09 | 0.889535E+09 | 0.549659E+09 |
December | 0.520076E+09 | 0.235583E+09 | 0.284493E+09 | 0.636869E+09 | 0.774016E+09 |
Annual Sum or Average | 0.929260E+10 | 0.397768E+10 | 0.531493E+10 | 0.152460E+11 | 0.457788E+10 |
Minimum of Months | 0.520076E+09 | 0.235583E+09 | 0.284493E+09 | 0.636869E+09 | 46093079.69 |
Maximum of Months | 0.945937E+09 | 0.410176E+09 | 0.586462E+09 | 0.179262E+10 | 0.891567E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129053E+10 | 0.920368E+09 | 0.370159E+09 | 0.184622E+10 | 0.795203E+09 |
February | 0.105717E+10 | 0.684285E+09 | 0.372883E+09 | 0.154367E+10 | 0.620341E+09 |
March | 0.747233E+09 | 0.337225E+09 | 0.410008E+09 | 0.112069E+10 | 0.605342E+09 |
April | 0.535976E+09 | 0.125591E+09 | 0.410385E+09 | 0.889939E+09 | 0.373120E+09 |
May | 0.423176E+09 | 17984196.22 | 0.405192E+09 | 0.874597E+09 | 0.103856E+09 |
June | 0.404542E+09 | 3770670.32 | 0.400771E+09 | 0.861154E+09 | 81171389.34 |
July | 0.437605E+09 | 8043046.48 | 0.429562E+09 | 0.925595E+09 | 50449748.58 |
August | 0.514818E+09 | 61793137.02 | 0.453025E+09 | 0.108970E+10 | 81944388.59 |
September | 0.597768E+09 | 0.157536E+09 | 0.440232E+09 | 0.117239E+10 | 0.126772E+09 |
October | 0.958355E+09 | 0.499210E+09 | 0.459145E+09 | 0.172508E+10 | 0.249928E+09 |
November | 0.118023E+10 | 0.812596E+09 | 0.367630E+09 | 0.183072E+10 | 0.521869E+09 |
December | 0.126100E+10 | 0.905582E+09 | 0.355420E+09 | 0.187036E+10 | 0.715781E+09 |
Annual Sum or Average | 0.940840E+10 | 0.453399E+10 | 0.487441E+10 | 0.157501E+11 | 0.432578E+10 |
Minimum of Months | 0.404542E+09 | 3770670.32 | 0.355420E+09 | 0.861154E+09 | 50449748.58 |
Maximum of Months | 0.129053E+10 | 0.920368E+09 | 0.459145E+09 | 0.187036E+10 | 0.795203E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129052E+10 | 0.920361E+09 | 0.370157E+09 | 0.184620E+10 | 0.795202E+09 |
February | 0.105716E+10 | 0.684280E+09 | 0.372881E+09 | 0.154366E+10 | 0.620341E+09 |
March | 0.747229E+09 | 0.337223E+09 | 0.410006E+09 | 0.112069E+10 | 0.605341E+09 |
April | 0.535973E+09 | 0.125590E+09 | 0.410383E+09 | 0.889934E+09 | 0.373119E+09 |
May | 0.423174E+09 | 17984064.43 | 0.405190E+09 | 0.874594E+09 | 0.103856E+09 |
June | 0.404540E+09 | 3770642.69 | 0.400769E+09 | 0.861151E+09 | 81170944.27 |
July | 0.437603E+09 | 8042987.54 | 0.429560E+09 | 0.925592E+09 | 50449380.81 |
August | 0.514816E+09 | 61792684.20 | 0.453023E+09 | 0.108969E+10 | 81943958.69 |
September | 0.597765E+09 | 0.157535E+09 | 0.440230E+09 | 0.117238E+10 | 0.126771E+09 |
October | 0.958349E+09 | 0.499207E+09 | 0.459142E+09 | 0.172506E+10 | 0.249928E+09 |
November | 0.118022E+10 | 0.812590E+09 | 0.367628E+09 | 0.183070E+10 | 0.521869E+09 |
December | 0.126099E+10 | 0.905576E+09 | 0.355418E+09 | 0.187035E+10 | 0.715780E+09 |
Annual Sum or Average | 0.940834E+10 | 0.453395E+10 | 0.487439E+10 | 0.157500E+11 | 0.432577E+10 |
Minimum of Months | 0.404540E+09 | 3770642.69 | 0.355418E+09 | 0.861151E+09 | 50449380.81 |
Maximum of Months | 0.129052E+10 | 0.920361E+09 | 0.459142E+09 | 0.187035E+10 | 0.795202E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129053E+10 | 0.920368E+09 | 0.370159E+09 | 0.184622E+10 | 0.795203E+09 |
February | 0.105717E+10 | 0.684285E+09 | 0.372883E+09 | 0.154367E+10 | 0.620341E+09 |
March | 0.747233E+09 | 0.337225E+09 | 0.410008E+09 | 0.112069E+10 | 0.605342E+09 |
April | 0.535976E+09 | 0.125591E+09 | 0.410385E+09 | 0.889939E+09 | 0.373120E+09 |
May | 0.423176E+09 | 17984196.22 | 0.405192E+09 | 0.874597E+09 | 0.103856E+09 |
June | 0.404542E+09 | 3770670.32 | 0.400771E+09 | 0.861154E+09 | 81171389.34 |
July | 0.437605E+09 | 8043046.48 | 0.429562E+09 | 0.925595E+09 | 50449748.58 |
August | 0.514818E+09 | 61793137.02 | 0.453025E+09 | 0.108970E+10 | 81944388.59 |
September | 0.597768E+09 | 0.157536E+09 | 0.440232E+09 | 0.117239E+10 | 0.126772E+09 |
October | 0.958355E+09 | 0.499210E+09 | 0.459145E+09 | 0.172508E+10 | 0.249928E+09 |
November | 0.118023E+10 | 0.812596E+09 | 0.367630E+09 | 0.183072E+10 | 0.521869E+09 |
December | 0.126100E+10 | 0.905582E+09 | 0.355420E+09 | 0.187036E+10 | 0.715781E+09 |
Annual Sum or Average | 0.940840E+10 | 0.453399E+10 | 0.487441E+10 | 0.157501E+11 | 0.432578E+10 |
Minimum of Months | 0.404542E+09 | 3770670.32 | 0.355420E+09 | 0.861154E+09 | 50449748.58 |
Maximum of Months | 0.129053E+10 | 0.920368E+09 | 0.459145E+09 | 0.187036E+10 | 0.795203E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129052E+10 | 0.920361E+09 | 0.370157E+09 | 0.184620E+10 | 0.795202E+09 |
February | 0.105716E+10 | 0.684280E+09 | 0.372881E+09 | 0.154366E+10 | 0.620341E+09 |
March | 0.747229E+09 | 0.337223E+09 | 0.410006E+09 | 0.112069E+10 | 0.605341E+09 |
April | 0.535973E+09 | 0.125590E+09 | 0.410383E+09 | 0.889934E+09 | 0.373119E+09 |
May | 0.423174E+09 | 17984064.43 | 0.405190E+09 | 0.874594E+09 | 0.103856E+09 |
June | 0.404540E+09 | 3770642.69 | 0.400769E+09 | 0.861151E+09 | 81170944.27 |
July | 0.437603E+09 | 8042987.54 | 0.429560E+09 | 0.925592E+09 | 50449380.81 |
August | 0.514816E+09 | 61792684.20 | 0.453023E+09 | 0.108969E+10 | 81943958.69 |
September | 0.597765E+09 | 0.157535E+09 | 0.440230E+09 | 0.117238E+10 | 0.126771E+09 |
October | 0.958349E+09 | 0.499207E+09 | 0.459142E+09 | 0.172506E+10 | 0.249928E+09 |
November | 0.118022E+10 | 0.812590E+09 | 0.367628E+09 | 0.183070E+10 | 0.521869E+09 |
December | 0.126099E+10 | 0.905576E+09 | 0.355418E+09 | 0.187035E+10 | 0.715780E+09 |
Annual Sum or Average | 0.940834E+10 | 0.453395E+10 | 0.487439E+10 | 0.157500E+11 | 0.432577E+10 |
Minimum of Months | 0.404540E+09 | 3770642.69 | 0.355418E+09 | 0.861151E+09 | 50449380.81 |
Maximum of Months | 0.129052E+10 | 0.920361E+09 | 0.459142E+09 | 0.187035E+10 | 0.795202E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129047E+10 | 0.920327E+09 | 0.370144E+09 | 0.184614E+10 | 0.795171E+09 |
February | 0.105712E+10 | 0.684255E+09 | 0.372867E+09 | 0.154360E+10 | 0.620316E+09 |
March | 0.747201E+09 | 0.337211E+09 | 0.409990E+09 | 0.112065E+10 | 0.605317E+09 |
April | 0.535953E+09 | 0.125586E+09 | 0.410367E+09 | 0.889900E+09 | 0.373104E+09 |
May | 0.423158E+09 | 17983405.49 | 0.405175E+09 | 0.874560E+09 | 0.103852E+09 |
June | 0.404524E+09 | 3770504.53 | 0.400754E+09 | 0.861118E+09 | 81167895.25 |
July | 0.437587E+09 | 8042692.84 | 0.429544E+09 | 0.925556E+09 | 50447531.36 |
August | 0.514796E+09 | 61790420.09 | 0.453006E+09 | 0.108965E+10 | 81940870.93 |
September | 0.597743E+09 | 0.157529E+09 | 0.440213E+09 | 0.117234E+10 | 0.126766E+09 |
October | 0.958314E+09 | 0.499188E+09 | 0.459125E+09 | 0.172500E+10 | 0.249918E+09 |
November | 0.118017E+10 | 0.812560E+09 | 0.367614E+09 | 0.183063E+10 | 0.521848E+09 |
December | 0.126095E+10 | 0.905542E+09 | 0.355404E+09 | 0.187028E+10 | 0.715752E+09 |
Annual Sum or Average | 0.940799E+10 | 0.453379E+10 | 0.487420E+10 | 0.157494E+11 | 0.432560E+10 |
Minimum of Months | 0.404524E+09 | 3770504.53 | 0.355404E+09 | 0.861118E+09 | 50447531.36 |
Maximum of Months | 0.129047E+10 | 0.920327E+09 | 0.459125E+09 | 0.187028E+10 | 0.795171E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.679104E+09 | 0.367222E+09 | 0.311882E+09 | 0.842777E+09 | 0.100910E+10 |
February | 0.694487E+09 | 0.351506E+09 | 0.342981E+09 | 0.888018E+09 | 0.811012E+09 |
March | 0.757826E+09 | 0.335471E+09 | 0.422355E+09 | 0.100361E+10 | 0.795709E+09 |
April | 0.910877E+09 | 0.419021E+09 | 0.491856E+09 | 0.138306E+10 | 0.506144E+09 |
May | 0.782752E+09 | 0.254983E+09 | 0.527769E+09 | 0.147482E+10 | 0.157162E+09 |
June | 0.841498E+09 | 0.295069E+09 | 0.546429E+09 | 0.160815E+10 | 0.140022E+09 |
July | 0.793735E+09 | 0.220170E+09 | 0.573565E+09 | 0.150612E+10 | 0.111392E+09 |
August | 0.802566E+09 | 0.245676E+09 | 0.556890E+09 | 0.151717E+10 | 0.157483E+09 |
September | 0.715188E+09 | 0.245344E+09 | 0.469844E+09 | 0.130702E+10 | 0.175200E+09 |
October | 0.756612E+09 | 0.326924E+09 | 0.429688E+09 | 0.131377E+10 | 0.330798E+09 |
November | 0.627587E+09 | 0.315400E+09 | 0.312187E+09 | 0.880322E+09 | 0.701487E+09 |
December | 0.623808E+09 | 0.331732E+09 | 0.292075E+09 | 0.792430E+09 | 0.968497E+09 |
Annual Sum or Average | 0.898604E+10 | 0.370852E+10 | 0.527752E+10 | 0.145173E+11 | 0.586401E+10 |
Minimum of Months | 0.623808E+09 | 0.220170E+09 | 0.292075E+09 | 0.792430E+09 | 0.111392E+09 |
Maximum of Months | 0.910877E+09 | 0.419021E+09 | 0.573565E+09 | 0.160815E+10 | 0.100910E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.679104E+09 | 0.367222E+09 | 0.311882E+09 | 0.842777E+09 | 0.100910E+10 |
February | 0.694487E+09 | 0.351506E+09 | 0.342981E+09 | 0.888018E+09 | 0.811012E+09 |
March | 0.757826E+09 | 0.335471E+09 | 0.422355E+09 | 0.100361E+10 | 0.795709E+09 |
April | 0.910877E+09 | 0.419021E+09 | 0.491856E+09 | 0.138306E+10 | 0.506144E+09 |
May | 0.782752E+09 | 0.254983E+09 | 0.527769E+09 | 0.147482E+10 | 0.157162E+09 |
June | 0.841498E+09 | 0.295069E+09 | 0.546429E+09 | 0.160815E+10 | 0.140022E+09 |
July | 0.793735E+09 | 0.220170E+09 | 0.573565E+09 | 0.150612E+10 | 0.111392E+09 |
August | 0.802566E+09 | 0.245676E+09 | 0.556890E+09 | 0.151717E+10 | 0.157483E+09 |
September | 0.715188E+09 | 0.245344E+09 | 0.469844E+09 | 0.130702E+10 | 0.175200E+09 |
October | 0.756612E+09 | 0.326924E+09 | 0.429688E+09 | 0.131377E+10 | 0.330798E+09 |
November | 0.627587E+09 | 0.315400E+09 | 0.312187E+09 | 0.880322E+09 | 0.701487E+09 |
December | 0.623808E+09 | 0.331732E+09 | 0.292075E+09 | 0.792430E+09 | 0.968497E+09 |
Annual Sum or Average | 0.898604E+10 | 0.370852E+10 | 0.527752E+10 | 0.145173E+11 | 0.586401E+10 |
Minimum of Months | 0.623808E+09 | 0.220170E+09 | 0.292075E+09 | 0.792430E+09 | 0.111392E+09 |
Maximum of Months | 0.910877E+09 | 0.419021E+09 | 0.573565E+09 | 0.160815E+10 | 0.100910E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.679091E+09 | 0.367215E+09 | 0.311876E+09 | 0.842762E+09 | 0.100908E+10 |
February | 0.694475E+09 | 0.351500E+09 | 0.342975E+09 | 0.888002E+09 | 0.810997E+09 |
March | 0.757812E+09 | 0.335464E+09 | 0.422348E+09 | 0.100359E+10 | 0.795694E+09 |
April | 0.910860E+09 | 0.419013E+09 | 0.491847E+09 | 0.138303E+10 | 0.506135E+09 |
May | 0.782738E+09 | 0.254978E+09 | 0.527759E+09 | 0.147479E+10 | 0.157159E+09 |
June | 0.841483E+09 | 0.295063E+09 | 0.546419E+09 | 0.160812E+10 | 0.140020E+09 |
July | 0.793720E+09 | 0.220166E+09 | 0.573554E+09 | 0.150610E+10 | 0.111390E+09 |
August | 0.802552E+09 | 0.245672E+09 | 0.556880E+09 | 0.151714E+10 | 0.157480E+09 |
September | 0.715175E+09 | 0.245339E+09 | 0.469836E+09 | 0.130700E+10 | 0.175197E+09 |
October | 0.756598E+09 | 0.326918E+09 | 0.429680E+09 | 0.131374E+10 | 0.330792E+09 |
November | 0.627576E+09 | 0.315394E+09 | 0.312181E+09 | 0.880306E+09 | 0.701474E+09 |
December | 0.623796E+09 | 0.331726E+09 | 0.292070E+09 | 0.792416E+09 | 0.968480E+09 |
Annual Sum or Average | 0.898588E+10 | 0.370845E+10 | 0.527743E+10 | 0.145170E+11 | 0.586390E+10 |
Minimum of Months | 0.623796E+09 | 0.220166E+09 | 0.292070E+09 | 0.792416E+09 | 0.111390E+09 |
Maximum of Months | 0.910860E+09 | 0.419013E+09 | 0.573554E+09 | 0.160812E+10 | 0.100908E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111635E+10 | 0.00 | 0.111635E+10 | 0.890146E+09 | 0.384671E+10 |
February | 0.118957E+10 | 0.00 | 0.118957E+10 | 0.106688E+10 | 0.292778E+10 |
March | 0.152787E+10 | 0.00 | 0.152787E+10 | 0.166671E+10 | 0.278933E+10 |
April | 0.174505E+10 | 7162306.50 | 0.173789E+10 | 0.246159E+10 | 0.169575E+10 |
May | 0.204249E+10 | 74709672.45 | 0.196778E+10 | 0.419965E+10 | 0.482310E+09 |
June | 0.224782E+10 | 0.155644E+09 | 0.209218E+10 | 0.479188E+10 | 0.404244E+09 |
July | 0.225408E+10 | 85876258.80 | 0.216820E+10 | 0.477388E+10 | 0.268263E+09 |
August | 0.201857E+10 | 15876296.36 | 0.200269E+10 | 0.431230E+10 | 0.385574E+09 |
September | 0.168734E+10 | 129958.71 | 0.168721E+10 | 0.334191E+10 | 0.526733E+09 |
October | 0.151514E+10 | 0.00 | 0.151514E+10 | 0.279063E+10 | 0.107416E+10 |
November | 0.111313E+10 | 0.00 | 0.111313E+10 | 0.127947E+10 | 0.238825E+10 |
December | 0.103778E+10 | 0.00 | 0.103778E+10 | 0.940096E+09 | 0.329364E+10 |
Annual Sum or Average | 0.194952E+11 | 0.339399E+09 | 0.191558E+11 | 0.325151E+11 | 0.200827E+11 |
Minimum of Months | 0.103778E+10 | 0.00 | 0.103778E+10 | 0.890146E+09 | 0.268263E+09 |
Maximum of Months | 0.225408E+10 | 0.155644E+09 | 0.216820E+10 | 0.479188E+10 | 0.384671E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.191536E+10 | 0.975310E+09 | 0.940054E+09 | 0.231768E+10 | 0.242124E+10 |
February | 0.192642E+10 | 0.930024E+09 | 0.996395E+09 | 0.244856E+10 | 0.186141E+10 |
March | 0.250890E+10 | 0.120997E+10 | 0.129893E+10 | 0.342627E+10 | 0.179734E+10 |
April | 0.266441E+10 | 0.120504E+10 | 0.145937E+10 | 0.411587E+10 | 0.114414E+10 |
May | 0.283783E+10 | 0.123054E+10 | 0.160729E+10 | 0.524940E+10 | 0.342158E+09 |
June | 0.278520E+10 | 0.110453E+10 | 0.168067E+10 | 0.533579E+10 | 0.283436E+09 |
July | 0.277484E+10 | 0.101544E+10 | 0.175940E+10 | 0.532398E+10 | 0.189052E+09 |
August | 0.255693E+10 | 0.879093E+09 | 0.167784E+10 | 0.491499E+10 | 0.272204E+09 |
September | 0.219191E+10 | 0.753571E+09 | 0.143834E+10 | 0.402295E+10 | 0.367184E+09 |
October | 0.223826E+10 | 0.944538E+09 | 0.129372E+10 | 0.390226E+10 | 0.722520E+09 |
November | 0.191773E+10 | 0.978309E+09 | 0.939421E+09 | 0.269257E+10 | 0.154310E+10 |
December | 0.156024E+10 | 0.706755E+09 | 0.853486E+09 | 0.196955E+10 | 0.211920E+10 |
Annual Sum or Average | 0.278780E+11 | 0.119331E+11 | 0.159449E+11 | 0.457199E+11 | 0.130630E+11 |
Minimum of Months | 0.156024E+10 | 0.706755E+09 | 0.853486E+09 | 0.196955E+10 | 0.189052E+09 |
Maximum of Months | 0.283783E+10 | 0.123054E+10 | 0.175940E+10 | 0.533579E+10 | 0.242124E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.645276E+10 | 0.460194E+10 | 0.185082E+10 | 0.917705E+10 | 0.387761E+10 |
February | 0.528594E+10 | 0.342150E+10 | 0.186444E+10 | 0.768646E+10 | 0.300114E+10 |
March | 0.373623E+10 | 0.168616E+10 | 0.205006E+10 | 0.560316E+10 | 0.288994E+10 |
April | 0.267991E+10 | 0.627970E+09 | 0.205194E+10 | 0.445763E+10 | 0.182147E+10 |
May | 0.211590E+10 | 89922872.05 | 0.202598E+10 | 0.439244E+10 | 0.503093E+09 |
June | 0.202273E+10 | 18853748.06 | 0.200387E+10 | 0.433441E+10 | 0.412132E+09 |
July | 0.218805E+10 | 40216078.06 | 0.214783E+10 | 0.466583E+10 | 0.261074E+09 |
August | 0.257412E+10 | 0.308972E+09 | 0.226515E+10 | 0.547319E+10 | 0.424211E+09 |
September | 0.298889E+10 | 0.787698E+09 | 0.220119E+10 | 0.585035E+10 | 0.609196E+09 |
October | 0.479186E+10 | 0.249610E+10 | 0.229575E+10 | 0.857975E+10 | 0.124751E+10 |
November | 0.590124E+10 | 0.406306E+10 | 0.183817E+10 | 0.911103E+10 | 0.254679E+10 |
December | 0.630513E+10 | 0.452801E+10 | 0.177712E+10 | 0.932402E+10 | 0.344579E+10 |
Annual Sum or Average | 0.470427E+11 | 0.226704E+11 | 0.243723E+11 | 0.786553E+11 | 0.210399E+11 |
Minimum of Months | 0.202273E+10 | 18853748.06 | 0.177712E+10 | 0.433441E+10 | 0.261074E+09 |
Maximum of Months | 0.645276E+10 | 0.460194E+10 | 0.229575E+10 | 0.932402E+10 | 0.387761E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.203729E+10 | 0.110165E+10 | 0.935636E+09 | 0.262898E+10 | 0.266670E+10 |
February | 0.208344E+10 | 0.105451E+10 | 0.102893E+10 | 0.277539E+10 | 0.207461E+10 |
March | 0.227345E+10 | 0.100640E+10 | 0.126705E+10 | 0.313364E+10 | 0.199327E+10 |
April | 0.273260E+10 | 0.125705E+10 | 0.147555E+10 | 0.425073E+10 | 0.130042E+10 |
May | 0.234823E+10 | 0.764941E+09 | 0.158329E+10 | 0.446153E+10 | 0.417432E+09 |
June | 0.252447E+10 | 0.885198E+09 | 0.163927E+10 | 0.488146E+10 | 0.361582E+09 |
July | 0.238118E+10 | 0.660502E+09 | 0.172068E+10 | 0.461895E+10 | 0.254273E+09 |
August | 0.240767E+10 | 0.737022E+09 | 0.167065E+10 | 0.466935E+10 | 0.354875E+09 |
September | 0.214554E+10 | 0.736024E+09 | 0.140952E+10 | 0.395761E+10 | 0.445128E+09 |
October | 0.226981E+10 | 0.980761E+09 | 0.128905E+10 | 0.401020E+10 | 0.852091E+09 |
November | 0.188274E+10 | 0.946191E+09 | 0.936552E+09 | 0.276200E+10 | 0.173898E+10 |
December | 0.187140E+10 | 0.995187E+09 | 0.876217E+09 | 0.253135E+10 | 0.232540E+10 |
Annual Sum or Average | 0.269578E+11 | 0.111254E+11 | 0.158324E+11 | 0.446812E+11 | 0.147848E+11 |
Minimum of Months | 0.187140E+10 | 0.660502E+09 | 0.876217E+09 | 0.253135E+10 | 0.254273E+09 |
Maximum of Months | 0.273260E+10 | 0.125705E+10 | 0.172068E+10 | 0.488146E+10 | 0.266670E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111635E+10 | 0.00 | 0.111635E+10 | 0.959547E+09 | 0.353917E+10 |
February | 0.118957E+10 | 0.00 | 0.118957E+10 | 0.112689E+10 | 0.268643E+10 |
March | 0.152787E+10 | 0.00 | 0.152787E+10 | 0.171465E+10 | 0.260879E+10 |
April | 0.174505E+10 | 7162306.50 | 0.173789E+10 | 0.246091E+10 | 0.164909E+10 |
May | 0.204249E+10 | 74709672.45 | 0.196778E+10 | 0.412707E+10 | 0.519488E+09 |
June | 0.224782E+10 | 0.155644E+09 | 0.209218E+10 | 0.471058E+10 | 0.439874E+09 |
July | 0.225408E+10 | 85876258.80 | 0.216820E+10 | 0.468043E+10 | 0.299608E+09 |
August | 0.201857E+10 | 15876296.36 | 0.200269E+10 | 0.423673E+10 | 0.417829E+09 |
September | 0.168734E+10 | 129958.71 | 0.168721E+10 | 0.327515E+10 | 0.556306E+09 |
October | 0.151514E+10 | 0.00 | 0.151514E+10 | 0.276516E+10 | 0.105626E+10 |
November | 0.111313E+10 | 0.00 | 0.111313E+10 | 0.134400E+10 | 0.218733E+10 |
December | 0.103778E+10 | 0.00 | 0.103778E+10 | 0.100660E+10 | 0.301656E+10 |
Annual Sum or Average | 0.194952E+11 | 0.339399E+09 | 0.191558E+11 | 0.324077E+11 | 0.189767E+11 |
Minimum of Months | 0.103778E+10 | 0.00 | 0.103778E+10 | 0.959547E+09 | 0.299608E+09 |
Maximum of Months | 0.225408E+10 | 0.155644E+09 | 0.216820E+10 | 0.471058E+10 | 0.353917E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.191536E+10 | 0.975310E+09 | 0.940054E+09 | 0.239372E+10 | 0.223989E+10 |
February | 0.192642E+10 | 0.930024E+09 | 0.996395E+09 | 0.250284E+10 | 0.172521E+10 |
March | 0.250890E+10 | 0.120997E+10 | 0.129893E+10 | 0.345296E+10 | 0.170466E+10 |
April | 0.266441E+10 | 0.120504E+10 | 0.145937E+10 | 0.410283E+10 | 0.112832E+10 |
May | 0.283783E+10 | 0.123054E+10 | 0.160729E+10 | 0.519537E+10 | 0.367235E+09 |
June | 0.278520E+10 | 0.110453E+10 | 0.168067E+10 | 0.527897E+10 | 0.308307E+09 |
July | 0.277484E+10 | 0.101544E+10 | 0.175940E+10 | 0.526009E+10 | 0.210357E+09 |
August | 0.255693E+10 | 0.879093E+09 | 0.167784E+10 | 0.486047E+10 | 0.294742E+09 |
September | 0.219191E+10 | 0.753571E+09 | 0.143834E+10 | 0.397690E+10 | 0.389540E+09 |
October | 0.223826E+10 | 0.944538E+09 | 0.129372E+10 | 0.387708E+10 | 0.717632E+09 |
November | 0.191773E+10 | 0.978309E+09 | 0.939421E+09 | 0.273508E+10 | 0.144069E+10 |
December | 0.156024E+10 | 0.706755E+09 | 0.853486E+09 | 0.202426E+10 | 0.196169E+10 |
Annual Sum or Average | 0.278780E+11 | 0.119331E+11 | 0.159449E+11 | 0.456606E+11 | 0.124883E+11 |
Minimum of Months | 0.156024E+10 | 0.706755E+09 | 0.853486E+09 | 0.202426E+10 | 0.210357E+09 |
Maximum of Months | 0.283783E+10 | 0.123054E+10 | 0.175940E+10 | 0.527897E+10 | 0.223989E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.645276E+10 | 0.460194E+10 | 0.185082E+10 | 0.925790E+10 | 0.361971E+10 |
February | 0.528594E+10 | 0.342150E+10 | 0.186444E+10 | 0.775161E+10 | 0.280477E+10 |
March | 0.373623E+10 | 0.168616E+10 | 0.205006E+10 | 0.563790E+10 | 0.273314E+10 |
April | 0.267991E+10 | 0.627970E+09 | 0.205194E+10 | 0.444243E+10 | 0.178261E+10 |
May | 0.211590E+10 | 89922872.05 | 0.202598E+10 | 0.431973E+10 | 0.541430E+09 |
June | 0.202273E+10 | 18853748.06 | 0.200387E+10 | 0.425656E+10 | 0.449428E+09 |
July | 0.218805E+10 | 40216078.06 | 0.214783E+10 | 0.457032E+10 | 0.290903E+09 |
August | 0.257412E+10 | 0.308972E+09 | 0.226515E+10 | 0.539454E+10 | 0.459819E+09 |
September | 0.298889E+10 | 0.787698E+09 | 0.220119E+10 | 0.578546E+10 | 0.642167E+09 |
October | 0.479186E+10 | 0.249610E+10 | 0.229575E+10 | 0.853528E+10 | 0.124584E+10 |
November | 0.590124E+10 | 0.406306E+10 | 0.183817E+10 | 0.914252E+10 | 0.241813E+10 |
December | 0.630513E+10 | 0.452801E+10 | 0.177712E+10 | 0.938119E+10 | 0.321947E+10 |
Annual Sum or Average | 0.470427E+11 | 0.226704E+11 | 0.243723E+11 | 0.784754E+11 | 0.202074E+11 |
Minimum of Months | 0.202273E+10 | 18853748.06 | 0.177712E+10 | 0.425656E+10 | 0.290903E+09 |
Maximum of Months | 0.645276E+10 | 0.460194E+10 | 0.229575E+10 | 0.938119E+10 | 0.361971E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.203729E+10 | 0.110165E+10 | 0.935636E+09 | 0.266889E+10 | 0.248998E+10 |
February | 0.208344E+10 | 0.105451E+10 | 0.102893E+10 | 0.280680E+10 | 0.193774E+10 |
March | 0.227345E+10 | 0.100640E+10 | 0.126705E+10 | 0.315361E+10 | 0.188820E+10 |
April | 0.273260E+10 | 0.125705E+10 | 0.147555E+10 | 0.424014E+10 | 0.126970E+10 |
May | 0.234823E+10 | 0.764941E+09 | 0.158329E+10 | 0.442019E+10 | 0.434928E+09 |
June | 0.252447E+10 | 0.885198E+09 | 0.163927E+10 | 0.483491E+10 | 0.377956E+09 |
July | 0.238118E+10 | 0.660502E+09 | 0.172068E+10 | 0.456834E+10 | 0.266035E+09 |
August | 0.240767E+10 | 0.737022E+09 | 0.167065E+10 | 0.462379E+10 | 0.371820E+09 |
September | 0.214554E+10 | 0.736024E+09 | 0.140952E+10 | 0.392260E+10 | 0.458805E+09 |
October | 0.226981E+10 | 0.980761E+09 | 0.128905E+10 | 0.399084E+10 | 0.841855E+09 |
November | 0.188274E+10 | 0.946191E+09 | 0.936552E+09 | 0.279184E+10 | 0.162936E+10 |
December | 0.187140E+10 | 0.995187E+09 | 0.876217E+09 | 0.256678E+10 | 0.216726E+10 |
Annual Sum or Average | 0.269578E+11 | 0.111254E+11 | 0.158324E+11 | 0.445887E+11 | 0.141337E+11 |
Minimum of Months | 0.187140E+10 | 0.660502E+09 | 0.876217E+09 | 0.256678E+10 | 0.266035E+09 |
Maximum of Months | 0.273260E+10 | 0.125705E+10 | 0.172068E+10 | 0.483491E+10 | 0.248998E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 274.92 | 1635.74 | 416.79 | 0.00 | 416.79 | 0.00 | 0.00 |
February | 383.98 | 1391.20 | 491.71 | 0.00 | 491.71 | 0.00 | 0.00 |
March | 566.95 | 1178.97 | 570.43 | 0.00 | 570.43 | 0.00 | 0.00 |
April | 919.55 | 700.15 | 673.24 | 2.76 | 670.47 | 0.00 | 0.00 |
May | 1557.71 | 187.68 | 762.57 | 27.89 | 734.67 | 0.00 | 0.00 |
June | 1839.73 | 151.96 | 867.20 | 60.05 | 807.15 | 0.00 | 0.00 |
July | 1769.91 | 95.38 | 841.56 | 32.06 | 809.50 | 0.00 | 0.00 |
August | 1591.47 | 141.14 | 753.63 | 5.93 | 747.71 | 0.00 | 0.00 |
September | 1272.98 | 225.31 | 650.97 | 0.05 | 650.92 | 0.00 | 0.00 |
October | 1017.71 | 439.13 | 565.68 | 0.00 | 565.68 | 0.00 | 0.00 |
November | 442.66 | 1058.78 | 429.44 | 0.00 | 429.44 | 0.00 | 0.00 |
December | 292.79 | 1440.96 | 387.46 | 0.00 | 387.46 | 0.00 | 0.00 |
Annual Sum or Average | 997.85 | 717.07 | 618.18 | 10.76 | 607.42 | 0.00 | 0.00 |
Minimum of Months | 274.92 | 95.38 | 387.46 | 0.00 | 387.46 | 0.00 | 0.00 |
Maximum of Months | 1839.73 | 1635.74 | 867.20 | 60.05 | 809.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 835.40 | 998.63 | 715.12 | 364.14 | 350.98 | 0.00 | 0.00 |
February | 988.94 | 842.13 | 796.31 | 384.44 | 411.87 | 0.00 | 0.00 |
March | 1272.70 | 712.89 | 936.72 | 451.75 | 484.97 | 0.00 | 0.00 |
April | 1600.77 | 432.13 | 1027.94 | 464.91 | 563.03 | 0.00 | 0.00 |
May | 1975.02 | 122.94 | 1059.53 | 459.43 | 600.10 | 0.00 | 0.00 |
June | 2074.62 | 92.72 | 1074.54 | 426.13 | 648.41 | 0.00 | 0.00 |
July | 2007.89 | 51.63 | 1036.01 | 379.12 | 656.89 | 0.00 | 0.00 |
August | 1852.34 | 77.96 | 954.65 | 328.22 | 626.44 | 0.00 | 0.00 |
September | 1559.65 | 144.70 | 845.65 | 290.73 | 554.92 | 0.00 | 0.00 |
October | 1464.36 | 272.36 | 835.67 | 352.65 | 483.02 | 0.00 | 0.00 |
November | 1029.57 | 636.19 | 739.87 | 377.44 | 362.43 | 0.00 | 0.00 |
December | 713.35 | 866.96 | 582.53 | 263.87 | 318.66 | 0.00 | 0.00 |
Annual Sum or Average | 1450.36 | 435.50 | 884.01 | 378.40 | 505.61 | 0.00 | 0.00 |
Minimum of Months | 713.35 | 51.63 | 582.53 | 263.87 | 318.66 | 0.00 | 0.00 |
Maximum of Months | 2074.62 | 998.63 | 1074.54 | 464.91 | 656.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3446.45 | 1484.46 | 2409.11 | 1718.11 | 691.00 | 0.00 | 0.00 |
February | 3190.42 | 1282.11 | 2184.93 | 1414.26 | 770.67 | 0.00 | 0.00 |
March | 2092.07 | 1130.03 | 1394.91 | 629.52 | 765.39 | 0.00 | 0.00 |
April | 1716.68 | 719.75 | 1033.89 | 242.26 | 791.63 | 0.00 | 0.00 |
May | 1632.67 | 193.88 | 789.97 | 33.57 | 756.40 | 0.00 | 0.00 |
June | 1661.16 | 156.58 | 780.36 | 7.27 | 773.08 | 0.00 | 0.00 |
July | 1727.87 | 94.18 | 816.91 | 15.01 | 801.89 | 0.00 | 0.00 |
August | 2034.21 | 152.97 | 961.05 | 115.35 | 845.69 | 0.00 | 0.00 |
September | 2261.53 | 244.54 | 1153.09 | 303.89 | 849.20 | 0.00 | 0.00 |
October | 3220.31 | 466.56 | 1789.02 | 931.91 | 857.12 | 0.00 | 0.00 |
November | 3531.43 | 1006.68 | 2276.64 | 1567.49 | 709.16 | 0.00 | 0.00 |
December | 3491.52 | 1336.20 | 2353.99 | 1690.51 | 663.49 | 0.00 | 0.00 |
Annual Sum or Average | 2497.13 | 685.84 | 1491.68 | 718.85 | 772.82 | 0.00 | 0.00 |
Minimum of Months | 1632.67 | 94.18 | 780.36 | 7.27 | 663.49 | 0.00 | 0.00 |
Maximum of Months | 3531.43 | 1484.46 | 2409.11 | 1718.11 | 857.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 943.97 | 1130.26 | 760.64 | 411.31 | 349.33 | 0.00 | 0.00 |
February | 1101.21 | 1005.71 | 861.21 | 435.89 | 425.32 | 0.00 | 0.00 |
March | 1124.11 | 891.25 | 848.81 | 375.75 | 473.07 | 0.00 | 0.00 |
April | 1600.75 | 585.81 | 1054.25 | 484.97 | 569.27 | 0.00 | 0.00 |
May | 1651.89 | 176.03 | 876.73 | 285.60 | 591.14 | 0.00 | 0.00 |
June | 1861.28 | 162.06 | 973.95 | 341.51 | 632.44 | 0.00 | 0.00 |
July | 1686.96 | 124.77 | 889.03 | 246.60 | 642.43 | 0.00 | 0.00 |
August | 1699.33 | 176.39 | 898.93 | 275.17 | 623.75 | 0.00 | 0.00 |
September | 1512.75 | 202.78 | 827.76 | 283.96 | 543.80 | 0.00 | 0.00 |
October | 1471.50 | 370.51 | 847.45 | 366.18 | 481.28 | 0.00 | 0.00 |
November | 1018.88 | 811.90 | 726.37 | 365.04 | 361.33 | 0.00 | 0.00 |
December | 887.57 | 1084.78 | 698.71 | 371.56 | 327.14 | 0.00 | 0.00 |
Annual Sum or Average | 1381.01 | 557.84 | 854.83 | 352.79 | 502.04 | 0.00 | 0.00 |
Minimum of Months | 887.57 | 124.77 | 698.71 | 246.60 | 327.14 | 0.00 | 0.00 |
Maximum of Months | 1861.28 | 1130.26 | 1054.25 | 484.97 | 642.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 332.34 | 1436.20 | 416.80 | 0.00 | 416.80 | 0.00 | 0.00 |
February | 441.01 | 1210.23 | 491.72 | 0.00 | 491.72 | 0.00 | 0.00 |
March | 622.28 | 1041.42 | 570.44 | 0.00 | 570.44 | 0.00 | 0.00 |
April | 949.69 | 654.22 | 673.25 | 2.76 | 670.48 | 0.00 | 0.00 |
May | 1567.97 | 180.07 | 762.58 | 27.89 | 734.69 | 0.00 | 0.00 |
June | 1848.72 | 155.96 | 867.22 | 60.05 | 807.17 | 0.00 | 0.00 |
July | 1782.36 | 100.16 | 841.58 | 32.06 | 809.51 | 0.00 | 0.00 |
August | 1610.03 | 143.96 | 753.65 | 5.93 | 747.72 | 0.00 | 0.00 |
September | 1289.32 | 203.22 | 650.98 | 0.05 | 650.93 | 0.00 | 0.00 |
October | 1041.90 | 401.04 | 565.69 | 0.00 | 565.69 | 0.00 | 0.00 |
November | 493.62 | 921.39 | 429.45 | 0.00 | 429.45 | 0.00 | 0.00 |
December | 350.99 | 1229.70 | 387.46 | 0.00 | 387.46 | 0.00 | 0.00 |
Annual Sum or Average | 1031.05 | 636.82 | 618.19 | 10.76 | 607.43 | 0.00 | 0.00 |
Minimum of Months | 332.34 | 100.16 | 387.46 | 0.00 | 387.46 | 0.00 | 0.00 |
Maximum of Months | 1848.72 | 1436.20 | 867.22 | 60.05 | 809.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 865.32 | 903.99 | 715.11 | 364.14 | 350.98 | 0.00 | 0.00 |
February | 1012.13 | 769.43 | 796.30 | 384.43 | 411.87 | 0.00 | 0.00 |
March | 1279.22 | 671.05 | 936.72 | 451.75 | 484.96 | 0.00 | 0.00 |
April | 1587.91 | 441.41 | 1027.94 | 464.91 | 563.03 | 0.00 | 0.00 |
May | 1959.90 | 127.75 | 1059.53 | 459.43 | 600.10 | 0.00 | 0.00 |
June | 2058.56 | 109.35 | 1074.54 | 426.13 | 648.41 | 0.00 | 0.00 |
July | 1987.75 | 70.58 | 1036.01 | 379.12 | 656.88 | 0.00 | 0.00 |
August | 1835.05 | 101.63 | 954.65 | 328.22 | 626.43 | 0.00 | 0.00 |
September | 1552.07 | 141.66 | 845.64 | 290.73 | 554.91 | 0.00 | 0.00 |
October | 1456.94 | 269.76 | 835.67 | 352.65 | 483.02 | 0.00 | 0.00 |
November | 1038.80 | 595.33 | 739.86 | 377.43 | 362.43 | 0.00 | 0.00 |
December | 735.35 | 791.22 | 582.53 | 263.87 | 318.66 | 0.00 | 0.00 |
Annual Sum or Average | 1449.77 | 414.22 | 884.01 | 378.40 | 505.61 | 0.00 | 0.00 |
Minimum of Months | 735.35 | 70.58 | 582.53 | 263.87 | 318.66 | 0.00 | 0.00 |
Maximum of Months | 2058.56 | 903.99 | 1074.54 | 464.91 | 656.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3426.32 | 1447.73 | 2409.18 | 1718.17 | 691.02 | 0.00 | 0.00 |
February | 3177.27 | 1240.55 | 2184.99 | 1414.31 | 770.68 | 0.00 | 0.00 |
March | 2091.98 | 1078.98 | 1394.95 | 629.54 | 765.41 | 0.00 | 0.00 |
April | 1719.76 | 702.73 | 1033.92 | 242.27 | 791.64 | 0.00 | 0.00 |
May | 1639.95 | 187.83 | 789.99 | 33.57 | 756.41 | 0.00 | 0.00 |
June | 1672.22 | 159.00 | 780.37 | 7.27 | 773.10 | 0.00 | 0.00 |
July | 1742.02 | 97.47 | 816.92 | 15.01 | 801.91 | 0.00 | 0.00 |
August | 2043.46 | 158.38 | 961.07 | 115.36 | 845.71 | 0.00 | 0.00 |
September | 2257.08 | 235.03 | 1153.12 | 303.90 | 849.22 | 0.00 | 0.00 |
October | 3203.31 | 465.77 | 1789.07 | 931.94 | 857.14 | 0.00 | 0.00 |
November | 3515.06 | 982.56 | 2276.71 | 1567.54 | 709.17 | 0.00 | 0.00 |
December | 3481.19 | 1286.51 | 2354.07 | 1690.56 | 663.50 | 0.00 | 0.00 |
Annual Sum or Average | 2494.14 | 667.17 | 1491.72 | 718.87 | 772.84 | 0.00 | 0.00 |
Minimum of Months | 1639.95 | 97.47 | 780.37 | 7.27 | 663.50 | 0.00 | 0.00 |
Maximum of Months | 3515.06 | 1447.73 | 2409.18 | 1718.17 | 857.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 981.55 | 995.63 | 760.64 | 411.31 | 349.33 | 0.00 | 0.00 |
February | 1147.23 | 857.56 | 861.21 | 435.89 | 425.32 | 0.00 | 0.00 |
March | 1169.97 | 744.20 | 848.81 | 375.75 | 473.06 | 0.00 | 0.00 |
April | 1639.94 | 501.71 | 1054.25 | 484.97 | 569.27 | 0.00 | 0.00 |
May | 1665.74 | 155.85 | 876.73 | 285.60 | 591.13 | 0.00 | 0.00 |
June | 1883.28 | 139.50 | 973.95 | 341.51 | 632.43 | 0.00 | 0.00 |
July | 1724.52 | 94.93 | 889.03 | 246.60 | 642.43 | 0.00 | 0.00 |
August | 1743.34 | 132.50 | 898.92 | 275.17 | 623.75 | 0.00 | 0.00 |
September | 1526.86 | 171.73 | 827.76 | 283.96 | 543.80 | 0.00 | 0.00 |
October | 1497.24 | 318.13 | 847.45 | 366.17 | 481.28 | 0.00 | 0.00 |
November | 1065.59 | 670.90 | 726.37 | 365.04 | 361.32 | 0.00 | 0.00 |
December | 945.10 | 868.20 | 698.70 | 371.56 | 327.14 | 0.00 | 0.00 |
Annual Sum or Average | 1416.83 | 468.82 | 854.83 | 352.79 | 502.04 | 0.00 | 0.00 |
Minimum of Months | 945.10 | 94.93 | 698.70 | 246.60 | 327.14 | 0.00 | 0.00 |
Maximum of Months | 1883.28 | 995.63 | 1054.25 | 484.97 | 642.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 358.25 | 1321.37 | 416.80 | 0.00 | 416.80 | 0.00 | 0.00 |
February | 465.81 | 1110.46 | 491.72 | 0.00 | 491.72 | 0.00 | 0.00 |
March | 640.18 | 974.01 | 570.44 | 0.00 | 570.44 | 0.00 | 0.00 |
April | 949.43 | 636.22 | 673.25 | 2.76 | 670.48 | 0.00 | 0.00 |
May | 1540.87 | 193.95 | 762.58 | 27.89 | 734.69 | 0.00 | 0.00 |
June | 1817.36 | 169.70 | 867.22 | 60.05 | 807.17 | 0.00 | 0.00 |
July | 1747.47 | 111.86 | 841.58 | 32.06 | 809.51 | 0.00 | 0.00 |
August | 1581.81 | 156.00 | 753.65 | 5.93 | 747.72 | 0.00 | 0.00 |
September | 1263.56 | 214.62 | 650.98 | 0.05 | 650.93 | 0.00 | 0.00 |
October | 1032.39 | 394.36 | 565.69 | 0.00 | 565.69 | 0.00 | 0.00 |
November | 518.52 | 843.88 | 429.45 | 0.00 | 429.45 | 0.00 | 0.00 |
December | 375.82 | 1126.25 | 387.46 | 0.00 | 387.46 | 0.00 | 0.00 |
Annual Sum or Average | 1027.64 | 601.75 | 618.19 | 10.76 | 607.43 | 0.00 | 0.00 |
Minimum of Months | 358.25 | 111.86 | 387.46 | 0.00 | 387.46 | 0.00 | 0.00 |
Maximum of Months | 1817.36 | 1321.37 | 867.22 | 60.05 | 809.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 893.71 | 836.28 | 715.11 | 364.14 | 350.98 | 0.00 | 0.00 |
February | 1034.57 | 713.13 | 796.30 | 384.43 | 411.87 | 0.00 | 0.00 |
March | 1289.19 | 636.45 | 936.72 | 451.75 | 484.96 | 0.00 | 0.00 |
April | 1582.88 | 435.31 | 1027.94 | 464.91 | 563.03 | 0.00 | 0.00 |
May | 1939.73 | 137.11 | 1059.53 | 459.43 | 600.10 | 0.00 | 0.00 |
June | 2036.64 | 118.95 | 1074.54 | 426.13 | 648.41 | 0.00 | 0.00 |
July | 1963.89 | 78.54 | 1036.01 | 379.12 | 656.88 | 0.00 | 0.00 |
August | 1814.69 | 110.04 | 954.65 | 328.22 | 626.43 | 0.00 | 0.00 |
September | 1534.30 | 150.29 | 845.64 | 290.73 | 554.91 | 0.00 | 0.00 |
October | 1447.54 | 267.93 | 835.67 | 352.65 | 483.02 | 0.00 | 0.00 |
November | 1055.20 | 555.82 | 739.86 | 377.43 | 362.43 | 0.00 | 0.00 |
December | 755.77 | 732.41 | 582.53 | 263.87 | 318.66 | 0.00 | 0.00 |
Annual Sum or Average | 1447.89 | 396.00 | 884.01 | 378.40 | 505.61 | 0.00 | 0.00 |
Minimum of Months | 755.77 | 78.54 | 582.53 | 263.87 | 318.66 | 0.00 | 0.00 |
Maximum of Months | 2036.64 | 836.28 | 1074.54 | 464.91 | 656.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3456.51 | 1351.44 | 2409.18 | 1718.17 | 691.02 | 0.00 | 0.00 |
February | 3204.20 | 1159.38 | 2184.99 | 1414.31 | 770.68 | 0.00 | 0.00 |
March | 2104.95 | 1020.44 | 1394.95 | 629.54 | 765.41 | 0.00 | 0.00 |
April | 1713.90 | 687.74 | 1033.92 | 242.27 | 791.64 | 0.00 | 0.00 |
May | 1612.80 | 202.15 | 789.99 | 33.57 | 756.41 | 0.00 | 0.00 |
June | 1642.19 | 173.39 | 780.37 | 7.27 | 773.10 | 0.00 | 0.00 |
July | 1706.36 | 108.61 | 816.92 | 15.01 | 801.91 | 0.00 | 0.00 |
August | 2014.09 | 171.68 | 961.07 | 115.36 | 845.71 | 0.00 | 0.00 |
September | 2232.05 | 247.75 | 1153.12 | 303.90 | 849.22 | 0.00 | 0.00 |
October | 3186.71 | 465.14 | 1789.07 | 931.94 | 857.14 | 0.00 | 0.00 |
November | 3527.21 | 932.92 | 2276.71 | 1567.54 | 709.17 | 0.00 | 0.00 |
December | 3502.53 | 1202.01 | 2354.07 | 1690.56 | 663.50 | 0.00 | 0.00 |
Annual Sum or Average | 2488.44 | 640.77 | 1491.72 | 718.87 | 772.84 | 0.00 | 0.00 |
Minimum of Months | 1612.80 | 108.61 | 780.37 | 7.27 | 663.50 | 0.00 | 0.00 |
Maximum of Months | 3527.21 | 1351.44 | 2409.18 | 1718.17 | 857.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 996.45 | 929.65 | 760.64 | 411.31 | 349.33 | 0.00 | 0.00 |
February | 1160.22 | 800.98 | 861.21 | 435.89 | 425.32 | 0.00 | 0.00 |
March | 1177.42 | 704.97 | 848.81 | 375.75 | 473.06 | 0.00 | 0.00 |
April | 1635.86 | 489.85 | 1054.25 | 484.97 | 569.27 | 0.00 | 0.00 |
May | 1650.31 | 162.38 | 876.73 | 285.60 | 591.13 | 0.00 | 0.00 |
June | 1865.32 | 145.82 | 973.95 | 341.51 | 632.43 | 0.00 | 0.00 |
July | 1705.62 | 99.33 | 889.03 | 246.60 | 642.43 | 0.00 | 0.00 |
August | 1726.33 | 138.82 | 898.92 | 275.17 | 623.75 | 0.00 | 0.00 |
September | 1513.35 | 177.01 | 827.76 | 283.96 | 543.80 | 0.00 | 0.00 |
October | 1490.01 | 314.31 | 847.45 | 366.17 | 481.28 | 0.00 | 0.00 |
November | 1077.10 | 628.61 | 726.37 | 365.04 | 361.32 | 0.00 | 0.00 |
December | 958.33 | 809.16 | 698.70 | 371.56 | 327.14 | 0.00 | 0.00 |
Annual Sum or Average | 1413.90 | 448.18 | 854.83 | 352.79 | 502.04 | 0.00 | 0.00 |
Minimum of Months | 958.33 | 99.33 | 698.70 | 246.60 | 327.14 | 0.00 | 0.00 |
Maximum of Months | 1865.32 | 929.65 | 1054.25 | 484.97 | 642.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.736342E+09 | 0.438118E+10 | 0.111634E+10 | 0.00 | 0.111634E+10 | 0.00 | 0.00 |
February | 0.928929E+09 | 0.336560E+10 | 0.118956E+10 | 0.00 | 0.118956E+10 | 0.00 | 0.00 |
March | 0.151851E+10 | 0.315775E+10 | 0.152784E+10 | 0.00 | 0.152784E+10 | 0.00 | 0.00 |
April | 0.238347E+10 | 0.181479E+10 | 0.174503E+10 | 7162092.90 | 0.173786E+10 | 0.00 | 0.00 |
May | 0.417218E+10 | 0.502671E+09 | 0.204246E+10 | 74707444.46 | 0.196775E+10 | 0.00 | 0.00 |
June | 0.476858E+10 | 0.393878E+09 | 0.224778E+10 | 0.155640E+09 | 0.209214E+10 | 0.00 | 0.00 |
July | 0.474052E+10 | 0.255477E+09 | 0.225404E+10 | 85873697.81 | 0.216816E+10 | 0.00 | 0.00 |
August | 0.426259E+10 | 0.378033E+09 | 0.201853E+10 | 15875822.90 | 0.200266E+10 | 0.00 | 0.00 |
September | 0.329956E+10 | 0.584000E+09 | 0.168731E+10 | 129954.84 | 0.168718E+10 | 0.00 | 0.00 |
October | 0.272582E+10 | 0.117618E+10 | 0.151512E+10 | 0.00 | 0.151512E+10 | 0.00 | 0.00 |
November | 0.114737E+10 | 0.274436E+10 | 0.111311E+10 | 0.00 | 0.111311E+10 | 0.00 | 0.00 |
December | 0.784220E+09 | 0.385946E+10 | 0.103776E+10 | 0.00 | 0.103776E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.314681E+11 | 0.226134E+11 | 0.194949E+11 | 0.339389E+09 | 0.191555E+11 | 0.00 | 0.00 |
Minimum of Months | 0.736342E+09 | 0.255477E+09 | 0.103776E+10 | 0.00 | 0.103776E+10 | 0.00 | 0.00 |
Maximum of Months | 0.476858E+10 | 0.438118E+10 | 0.225404E+10 | 0.155640E+09 | 0.216816E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.223753E+10 | 0.267473E+10 | 0.191537E+10 | 0.975314E+09 | 0.940057E+09 | 0.00 | 0.00 |
February | 0.239243E+10 | 0.203728E+10 | 0.192643E+10 | 0.930028E+09 | 0.996399E+09 | 0.00 | 0.00 |
March | 0.340879E+10 | 0.190940E+10 | 0.250891E+10 | 0.120998E+10 | 0.129893E+10 | 0.00 | 0.00 |
April | 0.414919E+10 | 0.112008E+10 | 0.266442E+10 | 0.120504E+10 | 0.145938E+10 | 0.00 | 0.00 |
May | 0.528989E+10 | 0.329273E+09 | 0.283785E+10 | 0.123054E+10 | 0.160730E+10 | 0.00 | 0.00 |
June | 0.537741E+10 | 0.240325E+09 | 0.278521E+10 | 0.110454E+10 | 0.168067E+10 | 0.00 | 0.00 |
July | 0.537793E+10 | 0.138281E+09 | 0.277485E+10 | 0.101545E+10 | 0.175941E+10 | 0.00 | 0.00 |
August | 0.496132E+10 | 0.208810E+09 | 0.255694E+10 | 0.879096E+09 | 0.167785E+10 | 0.00 | 0.00 |
September | 0.404261E+10 | 0.375065E+09 | 0.219192E+10 | 0.753574E+09 | 0.143834E+10 | 0.00 | 0.00 |
October | 0.392213E+10 | 0.729492E+09 | 0.223827E+10 | 0.944542E+09 | 0.129373E+10 | 0.00 | 0.00 |
November | 0.266864E+10 | 0.164900E+10 | 0.191774E+10 | 0.978313E+09 | 0.939424E+09 | 0.00 | 0.00 |
December | 0.191063E+10 | 0.232208E+10 | 0.156025E+10 | 0.706758E+09 | 0.853490E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.457385E+11 | 0.137338E+11 | 0.278782E+11 | 0.119332E+11 | 0.159450E+11 | 0.00 | 0.00 |
Minimum of Months | 0.191063E+10 | 0.138281E+09 | 0.156025E+10 | 0.706758E+09 | 0.853490E+09 | 0.00 | 0.00 |
Maximum of Months | 0.537793E+10 | 0.267473E+10 | 0.283785E+10 | 0.123054E+10 | 0.175941E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.923098E+10 | 0.397598E+10 | 0.645256E+10 | 0.460178E+10 | 0.185078E+10 | 0.00 | 0.00 |
February | 0.771825E+10 | 0.310168E+10 | 0.528578E+10 | 0.342138E+10 | 0.186440E+10 | 0.00 | 0.00 |
March | 0.560341E+10 | 0.302668E+10 | 0.373613E+10 | 0.168611E+10 | 0.205002E+10 | 0.00 | 0.00 |
April | 0.444965E+10 | 0.186558E+10 | 0.267985E+10 | 0.627949E+09 | 0.205190E+10 | 0.00 | 0.00 |
May | 0.437294E+10 | 0.519275E+09 | 0.211586E+10 | 89919926.79 | 0.202594E+10 | 0.00 | 0.00 |
June | 0.430573E+10 | 0.405853E+09 | 0.202269E+10 | 18853130.54 | 0.200383E+10 | 0.00 | 0.00 |
July | 0.462793E+10 | 0.252246E+09 | 0.218800E+10 | 40214760.86 | 0.214779E+10 | 0.00 | 0.00 |
August | 0.544842E+10 | 0.409718E+09 | 0.257406E+10 | 0.308962E+09 | 0.226510E+10 | 0.00 | 0.00 |
September | 0.586188E+10 | 0.633852E+09 | 0.298881E+10 | 0.787672E+09 | 0.220114E+10 | 0.00 | 0.00 |
October | 0.862528E+10 | 0.124963E+10 | 0.479172E+10 | 0.249602E+10 | 0.229570E+10 | 0.00 | 0.00 |
November | 0.915347E+10 | 0.260932E+10 | 0.590106E+10 | 0.406293E+10 | 0.183813E+10 | 0.00 | 0.00 |
December | 0.935169E+10 | 0.357887E+10 | 0.630494E+10 | 0.452786E+10 | 0.177708E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.787496E+11 | 0.216287E+11 | 0.470415E+11 | 0.226697E+11 | 0.243718E+11 | 0.00 | 0.00 |
Minimum of Months | 0.430573E+10 | 0.252246E+09 | 0.202269E+10 | 18853130.54 | 0.177708E+10 | 0.00 | 0.00 |
Maximum of Months | 0.935169E+10 | 0.397598E+10 | 0.645256E+10 | 0.460178E+10 | 0.229570E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.252832E+10 | 0.302728E+10 | 0.203730E+10 | 0.110166E+10 | 0.935640E+09 | 0.00 | 0.00 |
February | 0.266404E+10 | 0.243302E+10 | 0.208345E+10 | 0.105451E+10 | 0.102894E+10 | 0.00 | 0.00 |
March | 0.301081E+10 | 0.238711E+10 | 0.227346E+10 | 0.100641E+10 | 0.126706E+10 | 0.00 | 0.00 |
April | 0.414915E+10 | 0.151842E+10 | 0.273261E+10 | 0.125705E+10 | 0.147556E+10 | 0.00 | 0.00 |
May | 0.442443E+10 | 0.471484E+09 | 0.234824E+10 | 0.764944E+09 | 0.158330E+10 | 0.00 | 0.00 |
June | 0.482443E+10 | 0.420065E+09 | 0.252448E+10 | 0.885201E+09 | 0.163928E+10 | 0.00 | 0.00 |
July | 0.451834E+10 | 0.334173E+09 | 0.238119E+10 | 0.660505E+09 | 0.172068E+10 | 0.00 | 0.00 |
August | 0.455149E+10 | 0.472445E+09 | 0.240768E+10 | 0.737025E+09 | 0.167066E+10 | 0.00 | 0.00 |
September | 0.392104E+10 | 0.525598E+09 | 0.214555E+10 | 0.736027E+09 | 0.140952E+10 | 0.00 | 0.00 |
October | 0.394127E+10 | 0.992387E+09 | 0.226982E+10 | 0.980765E+09 | 0.128906E+10 | 0.00 | 0.00 |
November | 0.264095E+10 | 0.210445E+10 | 0.188275E+10 | 0.946195E+09 | 0.936555E+09 | 0.00 | 0.00 |
December | 0.237728E+10 | 0.290547E+10 | 0.187141E+10 | 0.995191E+09 | 0.876220E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.435515E+11 | 0.175919E+11 | 0.269580E+11 | 0.111255E+11 | 0.158325E+11 | 0.00 | 0.00 |
Minimum of Months | 0.237728E+10 | 0.334173E+09 | 0.187141E+10 | 0.660505E+09 | 0.876220E+09 | 0.00 | 0.00 |
Maximum of Months | 0.482443E+10 | 0.302728E+10 | 0.273261E+10 | 0.125705E+10 | 0.172068E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.890146E+09 | 0.384671E+10 | 0.111635E+10 | 0.00 | 0.111635E+10 | 0.00 | 0.00 |
February | 0.106688E+10 | 0.292778E+10 | 0.118957E+10 | 0.00 | 0.118957E+10 | 0.00 | 0.00 |
March | 0.166671E+10 | 0.278933E+10 | 0.152787E+10 | 0.00 | 0.152787E+10 | 0.00 | 0.00 |
April | 0.246159E+10 | 0.169575E+10 | 0.174505E+10 | 7162306.50 | 0.173789E+10 | 0.00 | 0.00 |
May | 0.419965E+10 | 0.482310E+09 | 0.204249E+10 | 74709672.45 | 0.196778E+10 | 0.00 | 0.00 |
June | 0.479188E+10 | 0.404244E+09 | 0.224782E+10 | 0.155644E+09 | 0.209218E+10 | 0.00 | 0.00 |
July | 0.477388E+10 | 0.268263E+09 | 0.225408E+10 | 85876258.80 | 0.216820E+10 | 0.00 | 0.00 |
August | 0.431230E+10 | 0.385574E+09 | 0.201857E+10 | 15876296.36 | 0.200269E+10 | 0.00 | 0.00 |
September | 0.334191E+10 | 0.526733E+09 | 0.168734E+10 | 129958.71 | 0.168721E+10 | 0.00 | 0.00 |
October | 0.279063E+10 | 0.107416E+10 | 0.151514E+10 | 0.00 | 0.151514E+10 | 0.00 | 0.00 |
November | 0.127947E+10 | 0.238825E+10 | 0.111313E+10 | 0.00 | 0.111313E+10 | 0.00 | 0.00 |
December | 0.940096E+09 | 0.329364E+10 | 0.103778E+10 | 0.00 | 0.103778E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.325151E+11 | 0.200827E+11 | 0.194952E+11 | 0.339399E+09 | 0.191558E+11 | 0.00 | 0.00 |
Minimum of Months | 0.890146E+09 | 0.268263E+09 | 0.103778E+10 | 0.00 | 0.103778E+10 | 0.00 | 0.00 |
Maximum of Months | 0.479188E+10 | 0.384671E+10 | 0.225408E+10 | 0.155644E+09 | 0.216820E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.231768E+10 | 0.242124E+10 | 0.191536E+10 | 0.975310E+09 | 0.940054E+09 | 0.00 | 0.00 |
February | 0.244856E+10 | 0.186141E+10 | 0.192642E+10 | 0.930024E+09 | 0.996395E+09 | 0.00 | 0.00 |
March | 0.342627E+10 | 0.179734E+10 | 0.250890E+10 | 0.120997E+10 | 0.129893E+10 | 0.00 | 0.00 |
April | 0.411587E+10 | 0.114414E+10 | 0.266441E+10 | 0.120504E+10 | 0.145937E+10 | 0.00 | 0.00 |
May | 0.524940E+10 | 0.342158E+09 | 0.283783E+10 | 0.123054E+10 | 0.160729E+10 | 0.00 | 0.00 |
June | 0.533579E+10 | 0.283436E+09 | 0.278520E+10 | 0.110453E+10 | 0.168067E+10 | 0.00 | 0.00 |
July | 0.532398E+10 | 0.189052E+09 | 0.277484E+10 | 0.101544E+10 | 0.175940E+10 | 0.00 | 0.00 |
August | 0.491499E+10 | 0.272204E+09 | 0.255693E+10 | 0.879093E+09 | 0.167784E+10 | 0.00 | 0.00 |
September | 0.402295E+10 | 0.367184E+09 | 0.219191E+10 | 0.753571E+09 | 0.143834E+10 | 0.00 | 0.00 |
October | 0.390226E+10 | 0.722520E+09 | 0.223826E+10 | 0.944538E+09 | 0.129372E+10 | 0.00 | 0.00 |
November | 0.269257E+10 | 0.154310E+10 | 0.191773E+10 | 0.978309E+09 | 0.939421E+09 | 0.00 | 0.00 |
December | 0.196955E+10 | 0.211920E+10 | 0.156024E+10 | 0.706755E+09 | 0.853486E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.457199E+11 | 0.130630E+11 | 0.278780E+11 | 0.119331E+11 | 0.159449E+11 | 0.00 | 0.00 |
Minimum of Months | 0.196955E+10 | 0.189052E+09 | 0.156024E+10 | 0.706755E+09 | 0.853486E+09 | 0.00 | 0.00 |
Maximum of Months | 0.533579E+10 | 0.242124E+10 | 0.283783E+10 | 0.123054E+10 | 0.175940E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.917705E+10 | 0.387761E+10 | 0.645276E+10 | 0.460194E+10 | 0.185082E+10 | 0.00 | 0.00 |
February | 0.768646E+10 | 0.300114E+10 | 0.528594E+10 | 0.342150E+10 | 0.186444E+10 | 0.00 | 0.00 |
March | 0.560316E+10 | 0.288994E+10 | 0.373623E+10 | 0.168616E+10 | 0.205006E+10 | 0.00 | 0.00 |
April | 0.445763E+10 | 0.182147E+10 | 0.267991E+10 | 0.627970E+09 | 0.205194E+10 | 0.00 | 0.00 |
May | 0.439244E+10 | 0.503093E+09 | 0.211590E+10 | 89922872.05 | 0.202598E+10 | 0.00 | 0.00 |
June | 0.433441E+10 | 0.412132E+09 | 0.202273E+10 | 18853748.06 | 0.200387E+10 | 0.00 | 0.00 |
July | 0.466583E+10 | 0.261074E+09 | 0.218805E+10 | 40216078.06 | 0.214783E+10 | 0.00 | 0.00 |
August | 0.547319E+10 | 0.424211E+09 | 0.257412E+10 | 0.308972E+09 | 0.226515E+10 | 0.00 | 0.00 |
September | 0.585035E+10 | 0.609196E+09 | 0.298889E+10 | 0.787698E+09 | 0.220119E+10 | 0.00 | 0.00 |
October | 0.857975E+10 | 0.124751E+10 | 0.479186E+10 | 0.249610E+10 | 0.229575E+10 | 0.00 | 0.00 |
November | 0.911103E+10 | 0.254679E+10 | 0.590124E+10 | 0.406306E+10 | 0.183817E+10 | 0.00 | 0.00 |
December | 0.932402E+10 | 0.344579E+10 | 0.630513E+10 | 0.452801E+10 | 0.177712E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.786553E+11 | 0.210399E+11 | 0.470427E+11 | 0.226704E+11 | 0.243723E+11 | 0.00 | 0.00 |
Minimum of Months | 0.433441E+10 | 0.261074E+09 | 0.202273E+10 | 18853748.06 | 0.177712E+10 | 0.00 | 0.00 |
Maximum of Months | 0.932402E+10 | 0.387761E+10 | 0.645276E+10 | 0.460194E+10 | 0.229575E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.262898E+10 | 0.266670E+10 | 0.203729E+10 | 0.110165E+10 | 0.935636E+09 | 0.00 | 0.00 |
February | 0.277539E+10 | 0.207461E+10 | 0.208344E+10 | 0.105451E+10 | 0.102893E+10 | 0.00 | 0.00 |
March | 0.313364E+10 | 0.199327E+10 | 0.227345E+10 | 0.100640E+10 | 0.126705E+10 | 0.00 | 0.00 |
April | 0.425073E+10 | 0.130042E+10 | 0.273260E+10 | 0.125705E+10 | 0.147555E+10 | 0.00 | 0.00 |
May | 0.446153E+10 | 0.417432E+09 | 0.234823E+10 | 0.764941E+09 | 0.158329E+10 | 0.00 | 0.00 |
June | 0.488146E+10 | 0.361582E+09 | 0.252447E+10 | 0.885198E+09 | 0.163927E+10 | 0.00 | 0.00 |
July | 0.461895E+10 | 0.254273E+09 | 0.238118E+10 | 0.660502E+09 | 0.172068E+10 | 0.00 | 0.00 |
August | 0.466935E+10 | 0.354875E+09 | 0.240767E+10 | 0.737022E+09 | 0.167065E+10 | 0.00 | 0.00 |
September | 0.395761E+10 | 0.445128E+09 | 0.214554E+10 | 0.736024E+09 | 0.140952E+10 | 0.00 | 0.00 |
October | 0.401020E+10 | 0.852091E+09 | 0.226981E+10 | 0.980761E+09 | 0.128905E+10 | 0.00 | 0.00 |
November | 0.276200E+10 | 0.173898E+10 | 0.188274E+10 | 0.946191E+09 | 0.936552E+09 | 0.00 | 0.00 |
December | 0.253135E+10 | 0.232540E+10 | 0.187140E+10 | 0.995187E+09 | 0.876217E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.446812E+11 | 0.147848E+11 | 0.269578E+11 | 0.111254E+11 | 0.158324E+11 | 0.00 | 0.00 |
Minimum of Months | 0.253135E+10 | 0.254273E+09 | 0.187140E+10 | 0.660502E+09 | 0.876217E+09 | 0.00 | 0.00 |
Maximum of Months | 0.488146E+10 | 0.266670E+10 | 0.273260E+10 | 0.125705E+10 | 0.172068E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.959547E+09 | 0.353917E+10 | 0.111635E+10 | 0.00 | 0.111635E+10 | 0.00 | 0.00 |
February | 0.112689E+10 | 0.268643E+10 | 0.118957E+10 | 0.00 | 0.118957E+10 | 0.00 | 0.00 |
March | 0.171465E+10 | 0.260879E+10 | 0.152787E+10 | 0.00 | 0.152787E+10 | 0.00 | 0.00 |
April | 0.246091E+10 | 0.164909E+10 | 0.174505E+10 | 7162306.50 | 0.173789E+10 | 0.00 | 0.00 |
May | 0.412707E+10 | 0.519488E+09 | 0.204249E+10 | 74709672.45 | 0.196778E+10 | 0.00 | 0.00 |
June | 0.471058E+10 | 0.439874E+09 | 0.224782E+10 | 0.155644E+09 | 0.209218E+10 | 0.00 | 0.00 |
July | 0.468043E+10 | 0.299608E+09 | 0.225408E+10 | 85876258.80 | 0.216820E+10 | 0.00 | 0.00 |
August | 0.423673E+10 | 0.417829E+09 | 0.201857E+10 | 15876296.36 | 0.200269E+10 | 0.00 | 0.00 |
September | 0.327515E+10 | 0.556306E+09 | 0.168734E+10 | 129958.71 | 0.168721E+10 | 0.00 | 0.00 |
October | 0.276516E+10 | 0.105626E+10 | 0.151514E+10 | 0.00 | 0.151514E+10 | 0.00 | 0.00 |
November | 0.134400E+10 | 0.218733E+10 | 0.111313E+10 | 0.00 | 0.111313E+10 | 0.00 | 0.00 |
December | 0.100660E+10 | 0.301656E+10 | 0.103778E+10 | 0.00 | 0.103778E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.324077E+11 | 0.189767E+11 | 0.194952E+11 | 0.339399E+09 | 0.191558E+11 | 0.00 | 0.00 |
Minimum of Months | 0.959547E+09 | 0.299608E+09 | 0.103778E+10 | 0.00 | 0.103778E+10 | 0.00 | 0.00 |
Maximum of Months | 0.471058E+10 | 0.353917E+10 | 0.225408E+10 | 0.155644E+09 | 0.216820E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.239372E+10 | 0.223989E+10 | 0.191536E+10 | 0.975310E+09 | 0.940054E+09 | 0.00 | 0.00 |
February | 0.250284E+10 | 0.172521E+10 | 0.192642E+10 | 0.930024E+09 | 0.996395E+09 | 0.00 | 0.00 |
March | 0.345296E+10 | 0.170466E+10 | 0.250890E+10 | 0.120997E+10 | 0.129893E+10 | 0.00 | 0.00 |
April | 0.410283E+10 | 0.112832E+10 | 0.266441E+10 | 0.120504E+10 | 0.145937E+10 | 0.00 | 0.00 |
May | 0.519537E+10 | 0.367235E+09 | 0.283783E+10 | 0.123054E+10 | 0.160729E+10 | 0.00 | 0.00 |
June | 0.527897E+10 | 0.308307E+09 | 0.278520E+10 | 0.110453E+10 | 0.168067E+10 | 0.00 | 0.00 |
July | 0.526009E+10 | 0.210357E+09 | 0.277484E+10 | 0.101544E+10 | 0.175940E+10 | 0.00 | 0.00 |
August | 0.486047E+10 | 0.294742E+09 | 0.255693E+10 | 0.879093E+09 | 0.167784E+10 | 0.00 | 0.00 |
September | 0.397690E+10 | 0.389540E+09 | 0.219191E+10 | 0.753571E+09 | 0.143834E+10 | 0.00 | 0.00 |
October | 0.387708E+10 | 0.717632E+09 | 0.223826E+10 | 0.944538E+09 | 0.129372E+10 | 0.00 | 0.00 |
November | 0.273508E+10 | 0.144069E+10 | 0.191773E+10 | 0.978309E+09 | 0.939421E+09 | 0.00 | 0.00 |
December | 0.202426E+10 | 0.196169E+10 | 0.156024E+10 | 0.706755E+09 | 0.853486E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.456606E+11 | 0.124883E+11 | 0.278780E+11 | 0.119331E+11 | 0.159449E+11 | 0.00 | 0.00 |
Minimum of Months | 0.202426E+10 | 0.210357E+09 | 0.156024E+10 | 0.706755E+09 | 0.853486E+09 | 0.00 | 0.00 |
Maximum of Months | 0.527897E+10 | 0.223989E+10 | 0.283783E+10 | 0.123054E+10 | 0.175940E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.925790E+10 | 0.361971E+10 | 0.645276E+10 | 0.460194E+10 | 0.185082E+10 | 0.00 | 0.00 |
February | 0.775161E+10 | 0.280477E+10 | 0.528594E+10 | 0.342150E+10 | 0.186444E+10 | 0.00 | 0.00 |
March | 0.563790E+10 | 0.273314E+10 | 0.373623E+10 | 0.168616E+10 | 0.205006E+10 | 0.00 | 0.00 |
April | 0.444243E+10 | 0.178261E+10 | 0.267991E+10 | 0.627970E+09 | 0.205194E+10 | 0.00 | 0.00 |
May | 0.431973E+10 | 0.541430E+09 | 0.211590E+10 | 89922872.05 | 0.202598E+10 | 0.00 | 0.00 |
June | 0.425656E+10 | 0.449428E+09 | 0.202273E+10 | 18853748.06 | 0.200387E+10 | 0.00 | 0.00 |
July | 0.457032E+10 | 0.290903E+09 | 0.218805E+10 | 40216078.06 | 0.214783E+10 | 0.00 | 0.00 |
August | 0.539454E+10 | 0.459819E+09 | 0.257412E+10 | 0.308972E+09 | 0.226515E+10 | 0.00 | 0.00 |
September | 0.578546E+10 | 0.642167E+09 | 0.298889E+10 | 0.787698E+09 | 0.220119E+10 | 0.00 | 0.00 |
October | 0.853528E+10 | 0.124584E+10 | 0.479186E+10 | 0.249610E+10 | 0.229575E+10 | 0.00 | 0.00 |
November | 0.914252E+10 | 0.241813E+10 | 0.590124E+10 | 0.406306E+10 | 0.183817E+10 | 0.00 | 0.00 |
December | 0.938119E+10 | 0.321947E+10 | 0.630513E+10 | 0.452801E+10 | 0.177712E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.784754E+11 | 0.202074E+11 | 0.470427E+11 | 0.226704E+11 | 0.243723E+11 | 0.00 | 0.00 |
Minimum of Months | 0.425656E+10 | 0.290903E+09 | 0.202273E+10 | 18853748.06 | 0.177712E+10 | 0.00 | 0.00 |
Maximum of Months | 0.938119E+10 | 0.361971E+10 | 0.645276E+10 | 0.460194E+10 | 0.229575E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.266889E+10 | 0.248998E+10 | 0.203729E+10 | 0.110165E+10 | 0.935636E+09 | 0.00 | 0.00 |
February | 0.280680E+10 | 0.193774E+10 | 0.208344E+10 | 0.105451E+10 | 0.102893E+10 | 0.00 | 0.00 |
March | 0.315361E+10 | 0.188820E+10 | 0.227345E+10 | 0.100640E+10 | 0.126705E+10 | 0.00 | 0.00 |
April | 0.424014E+10 | 0.126970E+10 | 0.273260E+10 | 0.125705E+10 | 0.147555E+10 | 0.00 | 0.00 |
May | 0.442019E+10 | 0.434928E+09 | 0.234823E+10 | 0.764941E+09 | 0.158329E+10 | 0.00 | 0.00 |
June | 0.483491E+10 | 0.377956E+09 | 0.252447E+10 | 0.885198E+09 | 0.163927E+10 | 0.00 | 0.00 |
July | 0.456834E+10 | 0.266035E+09 | 0.238118E+10 | 0.660502E+09 | 0.172068E+10 | 0.00 | 0.00 |
August | 0.462379E+10 | 0.371820E+09 | 0.240767E+10 | 0.737022E+09 | 0.167065E+10 | 0.00 | 0.00 |
September | 0.392260E+10 | 0.458805E+09 | 0.214554E+10 | 0.736024E+09 | 0.140952E+10 | 0.00 | 0.00 |
October | 0.399084E+10 | 0.841855E+09 | 0.226981E+10 | 0.980761E+09 | 0.128905E+10 | 0.00 | 0.00 |
November | 0.279184E+10 | 0.162936E+10 | 0.188274E+10 | 0.946191E+09 | 0.936552E+09 | 0.00 | 0.00 |
December | 0.256678E+10 | 0.216726E+10 | 0.187140E+10 | 0.995187E+09 | 0.876217E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.445887E+11 | 0.141337E+11 | 0.269578E+11 | 0.111254E+11 | 0.158324E+11 | 0.00 | 0.00 |
Minimum of Months | 0.256678E+10 | 0.266035E+09 | 0.187140E+10 | 0.660502E+09 | 0.876217E+09 | 0.00 | 0.00 |
Maximum of Months | 0.483491E+10 | 0.248998E+10 | 0.273260E+10 | 0.125705E+10 | 0.172068E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.316941E+11 | -0.306723E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102177E+10 | 58.98 | 0.00 | 0.00 |
February | 0.285702E+11 | -0.276466E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -923558399.0 | 58.97 | 0.00 | 0.00 |
March | 0.322988E+11 | -0.312725E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102630E+10 | 58.98 | 0.00 | 0.00 |
April | 0.276055E+11 | -0.266158E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989622625.1 | 58.96 | 0.00 | 0.00 |
May | 0.274489E+11 | -0.264265E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102240E+10 | 58.96 | 0.00 | 0.00 |
June | 0.255529E+11 | -0.245617E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991177991.0 | 58.97 | 0.00 | 0.00 |
July | 0.236220E+11 | -0.226038E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101822E+10 | 58.97 | 0.00 | 0.00 |
August | 0.260413E+11 | -0.250196E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102175E+10 | 58.97 | 0.00 | 0.00 |
September | 0.248595E+11 | -0.238729E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986593713.7 | 58.98 | 0.00 | 0.00 |
October | 0.274541E+11 | -0.264366E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101754E+10 | 58.97 | 0.00 | 0.00 |
November | 0.288182E+11 | -0.278329E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985261849.6 | 58.98 | 0.00 | 0.00 |
December | 0.302284E+11 | -0.292101E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101826E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.334194E+12 | -0.322171E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120224E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.236220E+11 | -0.312725E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102630E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.322988E+11 | -0.226038E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -923558399.0 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:00 | 6725.53 | 34.61 | 279.17 | 288.50 | 1112.85 | 25.01 | 167.17 | 270.67 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 2777.54 | 26.53 | 165.17 | 272.50 | 953.61 | 21.96 | 106.50 | 257.17 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 1216.55 | 16.86 | 0.00 | 306.50 | 703.80 | 19.77 | 50.00 | 258.17 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:09 | 965.20 | 16.00 | 0.00 | 309.50 | 553.46 | 18.85 | 19.83 | 258.83 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-07:49 | 864.11 | 16.13 | 0.00 | 332.17 | 484.50 | 19.05 | 5.50 | 266.67 |
June | 394.00 | 0.53 | 0.48 | 01-JUN-07:19 | 819.52 | 15.75 | 0.00 | 332.50 | 462.56 | 18.67 | 1.67 | 266.83 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-07:10 | 910.33 | 16.19 | 0.00 | 345.00 | 496.97 | 19.09 | 10.17 | 279.50 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1062.71 | 16.59 | 0.00 | 335.00 | 567.17 | 19.44 | 36.50 | 281.67 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:40 | 1257.42 | 16.96 | 3.67 | 305.83 | 658.05 | 19.70 | 93.33 | 261.17 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2251.76 | 21.48 | 80.50 | 307.17 | 887.59 | 20.92 | 144.50 | 271.17 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-08:09 | 6845.52 | 35.40 | 293.83 | 282.17 | 1061.02 | 22.98 | 131.33 | 262.00 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 6828.55 | 35.14 | 260.50 | 275.83 | 1454.25 | 26.98 | 168.17 | 258.83 |
Annual Sum or Average | 4027.67 | 0.52 | 2528.61 | 21.68 | 1082.83 | 3692.67 | 755.76 | 20.82 | 934.67 | 3192.67 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 819.52 | 15.75 | 0.00 | 272.50 | 462.56 | 18.67 | 1.67 | 257.17 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 6845.52 | 35.40 | 293.83 | 345.00 | 1454.25 | 26.98 | 168.17 | 281.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.55 | 0.48 | 01-JAN-07:00 | 1570.43 | 18.98 | 81.33 | 238.00 | 804.55 | 20.43 | 71.50 | 174.67 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:39 | 1735.06 | 19.03 | 71.83 | 237.17 | 943.11 | 22.33 | 72.83 | 191.67 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 1821.33 | 19.76 | 74.33 | 294.50 | 927.00 | 21.33 | 60.50 | 230.50 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:19 | 1850.45 | 18.33 | 76.50 | 305.67 | 993.99 | 21.67 | 80.17 | 259.17 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-06:40 | 2070.86 | 19.07 | 80.83 | 339.67 | 817.13 | 20.95 | 68.50 | 278.17 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-06:19 | 1935.40 | 20.16 | 112.67 | 340.33 | 772.01 | 20.72 | 83.00 | 282.50 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:30 | 1808.71 | 18.98 | 87.17 | 347.50 | 765.15 | 20.95 | 95.00 | 285.00 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-06:00 | 1669.00 | 18.86 | 83.50 | 331.17 | 873.34 | 22.06 | 104.33 | 280.33 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-06:49 | 1599.61 | 19.10 | 80.50 | 296.00 | 815.11 | 21.96 | 101.50 | 246.33 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-06:00 | 1662.53 | 19.58 | 76.50 | 283.50 | 828.56 | 21.28 | 87.33 | 238.17 |
November | 308.00 | 0.54 | 0.48 | 01-NOV-07:00 | 1267.09 | 17.68 | 56.83 | 236.67 | 703.99 | 21.22 | 72.17 | 189.67 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-07:49 | 1486.68 | 19.10 | 75.83 | 225.83 | 804.50 | 21.68 | 71.33 | 166.67 |
Annual Sum or Average | 4027.67 | 0.53 | 1718.08 | 19.07 | 957.83 | 3476.00 | 835.83 | 21.37 | 968.17 | 2822.83 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1267.09 | 17.68 | 56.83 | 225.83 | 703.99 | 20.43 | 60.50 | 166.67 | |
Maximum of Months | 394.00 | 0.55 | 0.48 | 2070.86 | 20.16 | 112.67 | 347.50 | 993.99 | 22.33 | 104.33 | 285.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.58 | 0.48 | 01-JAN-09:00 | 401.73 | 12.34 | 0.00 | 194.67 | 265.47 | 15.69 | 0.00 | 54.00 |
February | 295.50 | 0.55 | 0.48 | 01-FEB-11:00 | 463.81 | 13.51 | 0.00 | 215.83 | 307.40 | 16.79 | 0.00 | 112.33 |
March | 296.00 | 0.53 | 0.48 | 02-MAR-12:00 | 548.39 | 14.67 | 0.00 | 282.00 | 348.93 | 17.70 | 0.00 | 156.67 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:09 | 658.81 | 15.31 | 0.00 | 313.83 | 404.02 | 18.18 | 0.00 | 241.00 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:19 | 816.33 | 16.56 | 0.00 | 353.83 | 473.31 | 20.55 | 29.67 | 294.50 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:49 | 955.82 | 16.63 | 0.00 | 362.67 | 501.73 | 19.60 | 13.17 | 314.50 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:49 | 937.83 | 16.71 | 0.00 | 364.00 | 507.07 | 20.53 | 45.00 | 313.67 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:30 | 818.64 | 16.24 | 0.00 | 342.50 | 459.36 | 19.09 | 0.50 | 286.83 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-07:40 | 682.19 | 15.34 | 0.00 | 301.17 | 392.86 | 18.19 | 0.00 | 215.33 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-08:20 | 578.23 | 14.86 | 0.00 | 278.83 | 357.92 | 17.95 | 0.00 | 188.83 |
November | 308.00 | 0.57 | 0.48 | 01-NOV-10:30 | 412.00 | 12.87 | 0.00 | 199.17 | 274.04 | 16.23 | 0.00 | 60.83 |
December | 282.83 | 0.57 | 0.48 | 01-DEC-10:30 | 400.84 | 12.55 | 0.00 | 190.83 | 266.93 | 15.98 | 0.00 | 41.33 |
Annual Sum or Average | 4027.67 | 0.53 | 660.18 | 14.95 | 0.00 | 3399.33 | 388.87 | 18.19 | 88.33 | 2279.83 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 400.84 | 12.34 | 0.00 | 190.83 | 265.47 | 15.69 | 0.00 | 41.33 | |
Maximum of Months | 394.00 | 0.58 | 0.48 | 955.82 | 16.71 | 0.00 | 364.00 | 507.07 | 20.55 | 45.00 | 314.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-09:50 | 1770.46 | 19.34 | 83.83 | 245.33 | 1037.37 | 22.98 | 95.67 | 183.33 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:50 | 1614.34 | 19.93 | 79.00 | 245.33 | 819.79 | 21.30 | 65.50 | 200.00 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 1730.22 | 18.98 | 68.83 | 289.33 | 868.44 | 20.80 | 51.67 | 222.67 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:50 | 1946.70 | 18.80 | 82.00 | 305.83 | 1034.14 | 20.54 | 63.67 | 263.83 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-08:30 | 1596.40 | 14.73 | 0.00 | 334.50 | 694.13 | 18.58 | 26.00 | 276.17 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-07:00 | 1749.52 | 14.66 | 0.00 | 340.00 | 705.11 | 18.41 | 29.17 | 283.33 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-07:40 | 1604.45 | 15.20 | 3.67 | 347.83 | 681.70 | 18.69 | 41.50 | 286.17 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-08:09 | 1623.29 | 17.50 | 59.00 | 332.00 | 727.02 | 18.96 | 49.33 | 279.67 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-08:20 | 1512.31 | 18.94 | 77.00 | 296.83 | 752.68 | 20.81 | 79.67 | 246.17 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-08:39 | 1919.38 | 20.02 | 84.00 | 287.50 | 788.94 | 21.95 | 91.33 | 241.17 |
November | 308.00 | 0.54 | 0.48 | 01-NOV-10:09 | 1563.10 | 19.32 | 80.00 | 241.33 | 849.15 | 22.06 | 81.00 | 186.50 |
December | 282.83 | 0.53 | 0.48 | 01-DEC-10:20 | 1678.16 | 20.48 | 85.00 | 243.33 | 870.32 | 21.95 | 75.83 | 173.33 |
Annual Sum or Average | 4027.67 | 0.52 | 1691.86 | 17.97 | 702.33 | 3509.17 | 811.62 | 20.45 | 750.33 | 2842.33 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1512.31 | 14.66 | 0.00 | 241.33 | 681.70 | 18.41 | 26.00 | 173.33 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 1946.70 | 20.48 | 85.00 | 347.83 | 1037.37 | 22.98 | 95.67 | 286.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:00 | 6715.41 | 33.93 | 278.83 | 287.50 | 1153.68 | 20.87 | 92.17 | 271.67 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 2765.80 | 23.22 | 165.17 | 272.17 | 991.05 | 17.78 | 36.33 | 259.17 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 1203.26 | 11.02 | 0.00 | 305.33 | 730.22 | 15.94 | 0.00 | 260.33 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:09 | 950.87 | 10.58 | 0.00 | 308.00 | 571.62 | 15.28 | 0.00 | 262.67 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-07:40 | 847.82 | 10.58 | 0.00 | 330.33 | 498.52 | 15.36 | 0.00 | 270.50 |
June | 394.00 | 0.53 | 0.48 | 01-JUN-07:19 | 804.00 | 10.25 | 0.00 | 331.17 | 475.89 | 14.98 | 0.00 | 272.17 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-07:10 | 891.79 | 10.51 | 0.00 | 343.17 | 510.94 | 15.22 | 0.00 | 283.83 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1040.46 | 10.90 | 0.00 | 332.83 | 583.31 | 15.56 | 0.00 | 285.67 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:40 | 1229.60 | 11.18 | 3.67 | 304.67 | 677.24 | 15.65 | 0.00 | 263.00 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2220.90 | 16.37 | 77.17 | 306.00 | 922.87 | 16.97 | 10.33 | 273.50 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-08:09 | 6795.94 | 33.52 | 279.00 | 278.00 | 1130.95 | 20.67 | 90.83 | 269.33 |
December | 282.83 | 0.51 | 0.48 | 01-DEC-07:00 | 6770.31 | 33.17 | 248.83 | 272.33 | 1496.40 | 23.18 | 110.83 | 259.50 |
Annual Sum or Average | 4027.67 | 0.52 | 2505.15 | 17.18 | 1052.67 | 3671.50 | 783.37 | 17.07 | 340.50 | 3231.33 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 804.00 | 10.25 | 0.00 | 272.17 | 475.89 | 14.98 | 0.00 | 259.17 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 6795.94 | 33.93 | 279.00 | 343.17 | 1496.40 | 23.18 | 110.83 | 285.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.55 | 0.48 | 01-JAN-07:00 | 1569.52 | 16.39 | 81.33 | 237.67 | 823.65 | 18.41 | 53.50 | 180.33 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:39 | 1735.37 | 16.13 | 71.83 | 236.67 | 964.76 | 20.33 | 64.33 | 197.17 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 1610.91 | 14.00 | 48.50 | 294.17 | 954.27 | 18.83 | 47.83 | 237.00 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:19 | 1841.50 | 15.20 | 76.50 | 304.17 | 1017.92 | 19.37 | 68.00 | 263.33 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-06:40 | 2053.78 | 15.64 | 79.50 | 339.50 | 842.86 | 18.29 | 49.17 | 284.33 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-06:19 | 1845.87 | 15.22 | 85.00 | 338.83 | 795.42 | 18.09 | 54.00 | 287.83 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:30 | 1793.54 | 15.64 | 87.17 | 346.17 | 788.13 | 18.35 | 53.67 | 288.83 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-06:00 | 1650.87 | 15.61 | 83.50 | 330.33 | 895.03 | 19.76 | 75.50 | 284.83 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-06:49 | 1594.91 | 15.98 | 80.50 | 295.33 | 836.03 | 19.67 | 66.17 | 251.83 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-06:00 | 1663.17 | 16.56 | 76.33 | 282.50 | 850.23 | 18.93 | 48.50 | 242.83 |
November | 308.00 | 0.54 | 0.48 | 01-NOV-07:00 | 1265.60 | 14.51 | 56.83 | 236.17 | 723.64 | 19.13 | 55.50 | 195.83 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-07:49 | 1484.76 | 16.54 | 75.83 | 224.83 | 822.29 | 19.90 | 60.33 | 172.33 |
Annual Sum or Average | 4027.67 | 0.53 | 1687.76 | 15.61 | 902.83 | 3466.33 | 858.08 | 19.05 | 696.50 | 2886.50 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1265.60 | 14.00 | 48.50 | 224.83 | 723.64 | 18.09 | 47.83 | 172.33 | |
Maximum of Months | 394.00 | 0.55 | 0.48 | 2053.78 | 16.56 | 87.17 | 346.17 | 1017.92 | 20.33 | 75.50 | 288.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.58 | 0.48 | 01-JAN-09:50 | 394.77 | 7.24 | 0.00 | 188.67 | 273.00 | 12.22 | 0.00 | 66.67 |
February | 295.50 | 0.55 | 0.48 | 01-FEB-11:00 | 456.51 | 8.44 | 0.00 | 212.50 | 316.41 | 13.48 | 0.00 | 123.50 |
March | 296.00 | 0.53 | 0.48 | 02-MAR-12:00 | 540.47 | 9.76 | 0.00 | 279.00 | 359.63 | 14.68 | 0.00 | 171.67 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:09 | 649.19 | 10.32 | 0.00 | 312.33 | 416.45 | 15.09 | 0.00 | 248.83 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:19 | 802.24 | 11.00 | 0.00 | 353.00 | 482.99 | 16.05 | 2.17 | 294.17 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:30 | 940.17 | 10.95 | 0.00 | 361.83 | 524.98 | 18.96 | 59.17 | 324.83 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:49 | 920.50 | 10.96 | 0.00 | 363.50 | 521.26 | 17.08 | 24.50 | 318.83 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:30 | 803.20 | 10.79 | 0.00 | 340.67 | 472.29 | 15.53 | 0.00 | 290.33 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-07:40 | 669.84 | 10.07 | 0.00 | 299.50 | 404.10 | 14.74 | 0.00 | 222.00 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-08:20 | 568.07 | 9.73 | 0.00 | 277.00 | 368.10 | 14.66 | 0.00 | 196.17 |
November | 308.00 | 0.57 | 0.48 | 01-NOV-10:30 | 405.04 | 7.65 | 0.00 | 196.00 | 281.85 | 12.76 | 0.00 | 76.67 |
December | 282.83 | 0.57 | 0.48 | 01-DEC-10:09 | 393.46 | 7.32 | 0.00 | 185.00 | 274.26 | 12.42 | 0.00 | 52.83 |
Annual Sum or Average | 4027.67 | 0.53 | 648.87 | 9.65 | 0.00 | 3369.00 | 400.59 | 14.99 | 85.83 | 2386.50 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 393.46 | 7.24 | 0.00 | 185.00 | 273.00 | 12.22 | 0.00 | 52.83 | |
Maximum of Months | 394.00 | 0.58 | 0.48 | 940.17 | 11.00 | 0.00 | 363.50 | 524.98 | 18.96 | 59.17 | 324.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-09:50 | 1762.94 | 16.60 | 82.83 | 244.67 | 1057.80 | 21.26 | 81.50 | 189.83 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:50 | 1419.40 | 14.33 | 51.33 | 244.83 | 842.88 | 19.08 | 51.17 | 206.00 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 1739.41 | 15.87 | 68.83 | 288.50 | 892.13 | 18.30 | 44.33 | 230.50 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:50 | 1935.96 | 15.72 | 82.00 | 305.50 | 1058.38 | 17.98 | 53.00 | 267.33 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-08:30 | 1580.02 | 10.33 | 0.00 | 333.33 | 715.56 | 15.45 | 0.00 | 281.33 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-07:49 | 1680.71 | 10.32 | 0.00 | 338.67 | 726.96 | 15.31 | 0.00 | 289.17 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-07:30 | 1553.76 | 10.90 | 3.67 | 345.83 | 702.30 | 15.61 | 0.00 | 290.67 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:00 | 1606.16 | 13.94 | 59.00 | 330.83 | 748.15 | 15.95 | 5.50 | 283.17 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-08:20 | 1507.40 | 15.82 | 76.83 | 295.83 | 773.12 | 18.36 | 51.67 | 249.33 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-08:30 | 1919.71 | 17.05 | 84.00 | 286.83 | 803.01 | 19.38 | 50.33 | 244.00 |
November | 308.00 | 0.54 | 0.48 | 01-NOV-10:09 | 1562.19 | 16.52 | 80.00 | 240.83 | 820.92 | 18.68 | 51.17 | 189.17 |
December | 282.83 | 0.53 | 0.48 | 01-DEC-09:00 | 1678.88 | 17.96 | 85.00 | 242.17 | 880.38 | 19.68 | 56.00 | 178.67 |
Annual Sum or Average | 4027.67 | 0.52 | 1661.62 | 14.40 | 673.50 | 3497.83 | 828.16 | 17.75 | 444.67 | 2899.17 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1419.40 | 10.32 | 0.00 | 240.83 | 702.30 | 15.31 | 0.00 | 178.67 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 1935.96 | 17.96 | 85.00 | 345.83 | 1058.38 | 21.26 | 81.50 | 290.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:00 | 6715.08 | 33.91 | 278.83 | 287.50 | 1154.60 | 20.86 | 92.17 | 271.67 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 2766.12 | 23.19 | 165.17 | 272.17 | 991.94 | 17.76 | 36.33 | 259.17 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 1203.75 | 10.98 | 0.00 | 305.33 | 730.97 | 15.92 | 0.00 | 260.33 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:09 | 951.24 | 10.54 | 0.00 | 308.00 | 572.21 | 15.26 | 0.00 | 262.67 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-07:40 | 848.16 | 10.54 | 0.00 | 330.33 | 499.06 | 15.34 | 0.00 | 270.67 |
June | 394.00 | 0.53 | 0.48 | 01-JUN-07:19 | 804.31 | 10.21 | 0.00 | 331.17 | 476.40 | 14.97 | 0.00 | 272.50 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-07:10 | 892.24 | 10.47 | 0.00 | 343.17 | 511.53 | 15.20 | 0.00 | 284.17 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1041.08 | 10.86 | 0.00 | 332.83 | 584.04 | 15.54 | 0.00 | 286.00 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:40 | 1230.38 | 11.14 | 3.67 | 304.67 | 678.14 | 15.63 | 0.00 | 263.00 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2221.55 | 16.34 | 77.17 | 305.83 | 923.94 | 16.95 | 10.33 | 273.50 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-08:09 | 6795.90 | 33.51 | 279.00 | 278.00 | 1131.88 | 20.66 | 90.83 | 269.33 |
December | 282.83 | 0.51 | 0.48 | 01-DEC-07:00 | 6769.81 | 33.16 | 248.83 | 272.33 | 1497.38 | 23.17 | 110.83 | 259.50 |
Annual Sum or Average | 4027.67 | 0.52 | 2505.46 | 17.15 | 1052.67 | 3671.33 | 784.14 | 17.06 | 340.50 | 3232.50 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 804.31 | 10.21 | 0.00 | 272.17 | 476.40 | 14.97 | 0.00 | 259.17 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 6795.90 | 33.91 | 279.00 | 343.17 | 1497.38 | 23.17 | 110.83 | 286.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.55 | 0.48 | 01-JAN-07:00 | 1569.18 | 16.35 | 81.33 | 237.67 | 824.05 | 18.40 | 53.50 | 180.33 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:39 | 1735.03 | 16.09 | 71.83 | 236.67 | 965.24 | 20.31 | 64.33 | 197.17 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 1610.54 | 13.96 | 48.50 | 294.00 | 954.87 | 18.82 | 47.83 | 237.00 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:19 | 1841.47 | 15.16 | 76.50 | 304.17 | 1018.53 | 19.35 | 68.00 | 263.67 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-06:40 | 2053.78 | 15.60 | 79.50 | 339.50 | 843.58 | 18.27 | 49.17 | 284.83 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-06:19 | 1845.97 | 15.18 | 85.00 | 338.83 | 796.17 | 18.07 | 54.00 | 287.83 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:30 | 1793.78 | 15.60 | 87.17 | 346.17 | 788.96 | 18.33 | 53.67 | 289.00 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-06:00 | 1651.16 | 15.57 | 83.50 | 330.33 | 889.70 | 19.56 | 73.17 | 284.50 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-06:49 | 1595.14 | 15.94 | 80.50 | 295.33 | 811.72 | 18.28 | 51.50 | 249.33 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-06:00 | 1662.88 | 16.52 | 76.33 | 282.67 | 850.90 | 18.91 | 48.50 | 242.83 |
November | 308.00 | 0.54 | 0.48 | 01-NOV-07:00 | 1265.25 | 14.47 | 56.83 | 236.17 | 724.07 | 19.11 | 55.50 | 196.00 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-07:49 | 1484.44 | 16.50 | 75.83 | 224.50 | 822.68 | 19.88 | 60.33 | 172.50 |
Annual Sum or Average | 4027.67 | 0.53 | 1687.69 | 15.57 | 902.83 | 3466.00 | 856.00 | 18.90 | 679.50 | 2885.00 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1265.25 | 13.96 | 48.50 | 224.50 | 724.07 | 18.07 | 47.83 | 172.50 | |
Maximum of Months | 394.00 | 0.55 | 0.48 | 2053.78 | 16.52 | 87.17 | 346.17 | 1018.53 | 20.31 | 73.17 | 289.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.58 | 0.48 | 01-JAN-09:50 | 394.60 | 7.20 | 0.00 | 188.83 | 273.17 | 12.20 | 0.00 | 66.83 |
February | 295.50 | 0.55 | 0.48 | 01-FEB-11:00 | 456.32 | 8.39 | 0.00 | 212.50 | 316.60 | 13.46 | 0.00 | 123.67 |
March | 296.00 | 0.53 | 0.48 | 02-MAR-12:00 | 540.36 | 9.72 | 0.00 | 279.00 | 359.89 | 14.66 | 0.00 | 172.00 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:09 | 649.16 | 10.28 | 0.00 | 312.33 | 416.80 | 15.07 | 0.00 | 249.33 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:19 | 802.39 | 10.96 | 0.00 | 353.00 | 483.49 | 16.03 | 2.17 | 294.33 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:30 | 940.41 | 10.91 | 0.00 | 361.83 | 525.54 | 18.94 | 59.17 | 325.17 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:49 | 920.81 | 10.92 | 0.00 | 363.33 | 521.86 | 17.06 | 24.50 | 319.17 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:30 | 803.43 | 10.75 | 0.00 | 340.67 | 472.82 | 15.52 | 0.00 | 290.83 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-07:40 | 669.95 | 10.03 | 0.00 | 299.50 | 404.52 | 14.73 | 0.00 | 222.67 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-08:20 | 567.98 | 9.69 | 0.00 | 277.00 | 368.40 | 14.64 | 0.00 | 196.50 |
November | 308.00 | 0.57 | 0.48 | 01-NOV-10:30 | 404.85 | 7.61 | 0.00 | 196.00 | 282.02 | 12.74 | 0.00 | 76.67 |
December | 282.83 | 0.57 | 0.48 | 01-DEC-10:09 | 393.27 | 7.28 | 0.00 | 184.83 | 274.42 | 12.40 | 0.00 | 53.00 |
Annual Sum or Average | 4027.67 | 0.53 | 648.89 | 9.61 | 0.00 | 3368.83 | 400.95 | 14.97 | 85.83 | 2390.17 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 393.27 | 7.20 | 0.00 | 184.83 | 273.17 | 12.20 | 0.00 | 53.00 | |
Maximum of Months | 394.00 | 0.58 | 0.48 | 940.41 | 10.96 | 0.00 | 363.33 | 525.54 | 18.94 | 59.17 | 325.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-09:50 | 1762.61 | 16.57 | 82.83 | 244.67 | 1058.19 | 21.24 | 81.50 | 189.83 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:50 | 1418.97 | 14.29 | 51.33 | 244.67 | 843.36 | 19.06 | 51.17 | 206.17 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 1739.17 | 15.83 | 68.83 | 288.00 | 892.68 | 18.28 | 44.33 | 230.50 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:50 | 1935.91 | 15.68 | 82.00 | 305.50 | 1059.02 | 17.96 | 53.00 | 267.50 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-08:30 | 1580.16 | 10.28 | 0.00 | 333.33 | 881.93 | 15.43 | 0.00 | 281.50 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-07:49 | 1680.88 | 10.27 | 0.00 | 338.50 | 727.67 | 15.29 | 0.00 | 289.33 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-07:30 | 1554.11 | 10.85 | 3.67 | 345.83 | 710.05 | 15.59 | 0.00 | 290.67 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:00 | 1606.49 | 13.90 | 59.00 | 330.83 | 864.27 | 15.93 | 5.50 | 283.50 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-08:20 | 1507.59 | 15.78 | 76.83 | 295.50 | 773.87 | 18.34 | 51.67 | 249.67 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-08:30 | 1919.49 | 17.01 | 84.00 | 286.83 | 803.67 | 19.36 | 50.33 | 244.17 |
November | 308.00 | 0.54 | 0.48 | 01-NOV-10:09 | 1561.84 | 16.48 | 80.00 | 240.83 | 821.33 | 18.66 | 51.17 | 189.33 |
December | 282.83 | 0.53 | 0.48 | 01-DEC-09:00 | 1678.52 | 17.92 | 85.00 | 242.17 | 880.77 | 19.67 | 56.00 | 178.83 |
Annual Sum or Average | 4027.67 | 0.52 | 1661.58 | 14.35 | 673.50 | 3496.67 | 854.90 | 17.73 | 444.67 | 2901.00 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1418.97 | 10.27 | 0.00 | 240.83 | 710.05 | 15.29 | 0.00 | 178.83 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 1935.91 | 17.92 | 85.00 | 345.83 | 1059.02 | 21.24 | 81.50 | 290.67 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 13563039.37 | 6013.01 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3850755.45 | 5294.62 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7386279.96 | 5182.52 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6642125.06 | 1953.82 | 03-APR-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22446.27 | 21.40 | 18-NOV-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8204267.24 | 7029.34 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39668913.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13563039.37 | 7029.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 8586581.68 | 1451.69 | 05-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 554483.37 | 335.13 | 06-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1646591.30 | 506.87 | 21-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10787656.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8586581.68 | 1451.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 8522065.11 | 1049.86 | 10-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2649511.03 | 849.76 | 06-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2458959.56 | 364.98 | 11-MAR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13151605.69 | 1444.94 | 21-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26782141.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13151605.69 | 1444.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 6444072.29 | 871.99 | 21-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3192970.65 | 1465.51 | 06-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 997283.71 | 264.66 | 11-MAR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7091813.28 | 1102.55 | 20-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17726139.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7091813.28 | 1465.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.305534E+09 | 81210.79 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144407E+09 | 76483.98 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132036E+09 | 72547.07 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 60413785.72 | 13505.49 | 03-APR-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 31368705.41 | 10786.05 | 18-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.217610E+09 | 98192.14 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.891370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.305534E+09 | 98192.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.745712E+10 | 128504.26 | 05-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.348135E+10 | 127096.56 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.221442E+10 | 125213.26 | 13-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193606E+09 | 25871.10 | 16-NOV-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.451325E+10 | 127546.73 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.745712E+10 | 128504.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.288999E+10 | 111607.85 | 10-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120790E+10 | 111601.21 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138293E+10 | 94913.75 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 31459429.29 | 18450.08 | 16-NOV-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.256433E+10 | 112201.67 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.807661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.288999E+10 | 112201.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.921549E+09 | 142123.97 | 10-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.447720E+09 | 142115.70 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101710E+10 | 56290.15 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.900289E+09 | 142875.87 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.328665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.101710E+10 | 142875.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.238776E+10 | 104737.82 | 10-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102603E+10 | 104731.52 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.804196E+09 | 19628.78 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12684789.81 | 3523.87 | 16-NOV-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133224E+10 | 105296.72 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.556291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.238776E+10 | 105296.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 41781220.01 | 12406.06 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16689849.76 | 11461.53 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9271455.46 | 11595.83 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9418507.82 | 14662.89 | 18-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3455653.82 | 1449.06 | 18-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24431851.18 | 13522.46 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41781220.01 | 14662.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.226789E+10 | 67830.71 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131212E+10 | 67777.29 | 06-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.816158E+09 | 67082.93 | 10-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28465788.77 | 5818.77 | 16-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133898E+10 | 68089.72 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.576361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.226789E+10 | 68089.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.253996E+10 | 14847.89 | 06-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129142E+10 | 14826.05 | 09-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.886266E+09 | 14803.40 | 03-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21681299.39 | 1936.62 | 11-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29285099.08 | 2122.78 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.289503E+09 | 14767.17 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169486E+10 | 14863.97 | 20-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.675298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.253996E+10 | 14863.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104846E+10 | 13408.21 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.525997E+09 | 13397.59 | 06-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.475233E+09 | 13284.97 | 10-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4621931.32 | 940.59 | 11-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11389120.65 | 2062.95 | 28-OCT-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102778E+09 | 13161.36 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.912982E+09 | 13459.34 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.308146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104846E+10 | 13459.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.699118E+09 | 17652.06 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.399256E+09 | 17622.09 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.520736E+09 | 17491.94 | 10-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3890434.30 | 719.80 | 11-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4251296.57 | 1044.72 | 28-OCT-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 26595385.13 | 11285.30 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.561440E+09 | 17718.82 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.699118E+09 | 17718.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104879E+10 | 13586.87 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.496470E+09 | 13563.35 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.381890E+09 | 13436.47 | 10-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 181898.38 | 111.88 | 11-APR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10034425.70 | 1003.12 | 28-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 78911322.75 | 11469.98 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.674080E+09 | 13639.21 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104879E+10 | 13639.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.394737E+11 | 0.299407E+11 | 144942.67 | 31-JAN-06:02 | 127103.56 | 0.24 |
February | 0.00 | 0.00 | 0.565043E+11 | 0.413368E+11 | 131220.89 | 28-FEB-06:03 | 118105.94 | 0.40 |
March | 0.00 | 0.00 | 0.704633E+11 | 0.557049E+11 | 136065.61 | 27-MAR-05:02 | 128614.96 | 0.40 |
April | 0.00 | 0.00 | 0.113887E+12 | 0.910678E+11 | 145596.59 | 24-APR-05:02 | 135830.13 | 0.68 |
May | 0.00 | 0.00 | 0.142552E+12 | 0.111343E+12 | 161503.86 | 22-MAY-05:03 | 140652.07 | 0.70 |
June | 0.00 | 0.00 | 0.154763E+12 | 0.123158E+12 | 150436.40 | 26-JUN-05:02 | 139320.04 | 0.79 |
July | 0.00 | 0.00 | 0.167088E+12 | 0.131766E+12 | 156235.15 | 05-JUL-05:02 | 141902.28 | 0.82 |
August | 0.00 | 0.00 | 0.181643E+12 | 0.144148E+12 | 155060.86 | 14-AUG-05:02 | 140687.66 | 0.87 |
September | 0.00 | 0.00 | 0.142557E+12 | 0.105687E+12 | 164389.46 | 05-SEP-05:03 | 143076.15 | 0.71 |
October | 0.00 | 0.00 | 0.134102E+12 | 0.106674E+12 | 161320.54 | 10-OCT-05:02 | 144746.02 | 0.65 |
November | 0.00 | 0.00 | 0.854992E+11 | 0.691610E+11 | 147145.52 | 01-NOV-05:02 | 131564.72 | 0.52 |
December | 0.00 | 0.00 | 0.632382E+11 | 0.501482E+11 | 151092.24 | 11-DEC-06:02 | 138280.35 | 0.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.135177E+13 | 0.106014E+13 | 0.60 | |||
Minimum of Months | 0.00 | 0.00 | 0.394737E+11 | 0.299407E+11 | 131220.89 | 118105.94 | 0.24 | |
Maximum of Months | 0.00 | 0.00 | 0.181643E+12 | 0.144148E+12 | 164389.46 | 144746.02 | 0.87 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.304851E+12 | 0.224675E+12 | 1126680.77 | 20-JAN-06:02 | 424536.24 | 0.23 |
February | 0.00 | 0.00 | 0.435918E+12 | 0.306262E+12 | 1201178.75 | 03-FEB-06:03 | 975435.33 | 0.37 |
March | 0.00 | 0.00 | 0.516071E+12 | 0.389006E+12 | 1369653.84 | 28-MAR-05:02 | 1120237.91 | 0.35 |
April | 0.00 | 0.00 | 0.817918E+12 | 0.616538E+12 | 1413295.89 | 29-APR-05:03 | 1223953.47 | 0.51 |
May | 0.00 | 0.00 | 0.125516E+13 | 0.945060E+12 | 1840667.26 | 22-MAY-03:02 | 1280958.13 | 0.65 |
June | 0.00 | 0.00 | 0.129195E+13 | 0.979148E+12 | 1451170.00 | 07-JUN-05:03 | 1232732.04 | 0.68 |
July | 0.00 | 0.00 | 0.132969E+13 | 0.975580E+12 | 1468541.56 | 26-JUL-05:02 | 1241194.99 | 0.67 |
August | 0.00 | 0.00 | 0.137627E+13 | 0.100783E+13 | 1489928.03 | 29-AUG-05:02 | 1258988.86 | 0.67 |
September | 0.00 | 0.00 | 0.123468E+13 | 0.869302E+12 | 1601484.65 | 14-SEP-05:03 | 1238396.63 | 0.65 |
October | 0.00 | 0.00 | 0.108876E+13 | 0.820747E+12 | 1544797.82 | 21-OCT-05:02 | 1237695.21 | 0.55 |
November | 0.00 | 0.00 | 0.635493E+12 | 0.493183E+12 | 1460978.08 | 01-NOV-05:02 | 1223874.17 | 0.44 |
December | 0.00 | 0.00 | 0.440595E+12 | 0.326063E+12 | 1386007.70 | 13-DEC-06:02 | 1169993.86 | 0.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.107274E+14 | 0.795339E+13 | 0.50 | |||
Minimum of Months | 0.00 | 0.00 | 0.304851E+12 | 0.224675E+12 | 1126680.77 | 424536.24 | 0.23 | |
Maximum of Months | 0.00 | 0.00 | 0.137627E+13 | 0.100783E+13 | 1840667.26 | 1280958.13 | 0.68 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.312397E+11 | 0.227633E+11 | 116874.82 | 19-JAN-15:00 | 76293.80 | 0.22 |
February | 0.00 | 0.00 | 0.450116E+11 | 0.314260E+11 | 114715.24 | 28-FEB-06:03 | 101963.08 | 0.37 |
March | 0.00 | 0.00 | 0.541084E+11 | 0.405466E+11 | 139005.22 | 27-MAR-05:02 | 121128.24 | 0.34 |
April | 0.00 | 0.00 | 0.871330E+11 | 0.665621E+11 | 143596.61 | 27-APR-05:02 | 125166.38 | 0.50 |
May | 0.00 | 0.00 | 0.140593E+12 | 0.108781E+12 | 196911.83 | 22-MAY-03:02 | 144830.60 | 0.66 |
June | 0.00 | 0.00 | 0.146918E+12 | 0.114851E+12 | 155712.11 | 30-JUN-03:02 | 135745.60 | 0.70 |
July | 0.00 | 0.00 | 0.150639E+12 | 0.114011E+12 | 166592.74 | 26-JUL-03:02 | 142193.61 | 0.69 |
August | 0.00 | 0.00 | 0.154275E+12 | 0.116298E+12 | 161579.08 | 24-AUG-03:02 | 140410.23 | 0.69 |
September | 0.00 | 0.00 | 0.134290E+12 | 0.966514E+11 | 189813.22 | 05-SEP-03:02 | 139051.28 | 0.66 |
October | 0.00 | 0.00 | 0.117050E+12 | 0.899064E+11 | 166670.02 | 21-OCT-05:02 | 130118.79 | 0.56 |
November | 0.00 | 0.00 | 0.637855E+11 | 0.495261E+11 | 151289.45 | 01-NOV-05:02 | 126441.01 | 0.43 |
December | 0.00 | 0.00 | 0.441520E+11 | 0.326099E+11 | 132746.27 | 15-DEC-06:03 | 111558.08 | 0.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.116920E+13 | 0.883932E+12 | 0.51 | |||
Minimum of Months | 0.00 | 0.00 | 0.312397E+11 | 0.227633E+11 | 114715.24 | 76293.80 | 0.22 | |
Maximum of Months | 0.00 | 0.00 | 0.154275E+12 | 0.116298E+12 | 196911.83 | 144830.60 | 0.70 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.204821E+11 | 0.158825E+11 | 110691.16 | 01-JAN-16:12 | 74916.62 | 0.16 |
February | 0.00 | 0.00 | 0.243698E+11 | 0.196492E+11 | 100526.35 | 03-FEB-06:03 | 38555.02 | 0.26 |
March | 0.00 | 0.00 | 0.326463E+11 | 0.274596E+11 | 130456.19 | 07-MAR-05:03 | 48949.98 | 0.25 |
April | 0.00 | 0.00 | 0.507797E+11 | 0.439375E+11 | 135678.51 | 29-APR-05:03 | 73822.40 | 0.42 |
May | 0.00 | 0.00 | 0.935505E+11 | 0.720369E+11 | 163086.64 | 22-MAY-03:04 | 74812.94 | 0.58 |
June | 0.00 | 0.00 | 0.982552E+11 | 0.737793E+11 | 163023.10 | 19-JUN-03:02 | 78834.21 | 0.59 |
July | 0.00 | 0.00 | 0.105253E+12 | 0.744623E+11 | 168727.85 | 03-JUL-03:03 | 76118.69 | 0.55 |
August | 0.00 | 0.00 | 0.117337E+12 | 0.852203E+11 | 156687.93 | 13-AUG-18:20 | 76956.58 | 0.63 |
September | 0.00 | 0.00 | 0.100499E+12 | 0.734065E+11 | 160862.39 | 17-SEP-17:53 | 76898.56 | 0.60 |
October | 0.00 | 0.00 | 0.866626E+11 | 0.667716E+11 | 161033.56 | 08-OCT-16:20 | 78257.02 | 0.51 |
November | 0.00 | 0.00 | 0.486032E+11 | 0.399271E+11 | 144127.58 | 02-NOV-03:02 | 79639.58 | 0.36 |
December | 0.00 | 0.00 | 0.315948E+11 | 0.254428E+11 | 134032.76 | 15-DEC-05:03 | 73687.54 | 0.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.810033E+12 | 0.617976E+12 | 0.43 | |||
Minimum of Months | 0.00 | 0.00 | 0.204821E+11 | 0.158825E+11 | 100526.35 | 38555.02 | 0.16 | |
Maximum of Months | 0.00 | 0.00 | 0.117337E+12 | 0.852203E+11 | 168727.85 | 79639.58 | 0.63 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.497309E+10 | 0.486926E+10 | 2720.09 | 19-JAN-17:00 | 2365.24 | 0.00 |
February | 0.00 | 0.00 | 0.944723E+10 | 0.926601E+10 | 4642.82 | 27-FEB-17:00 | 4289.49 | 0.00 |
March | 0.00 | 0.00 | 0.156457E+11 | 0.154473E+11 | 7684.44 | 31-MAR-24:00 | 7684.44 | 0.00 |
April | 0.00 | 0.00 | 0.203760E+11 | 0.200781E+11 | 8605.31 | 28-APR-16:10 | 8086.10 | 0.00 |
May | 0.00 | 0.00 | 0.637587E+10 | 0.588497E+10 | 4062.61 | 31-MAY-23:10 | 3916.42 | 0.00 |
June | 0.00 | 0.00 | 0.111765E+11 | 0.106080E+11 | 5855.86 | 30-JUN-23:53 | 5842.87 | 0.00 |
July | 0.00 | 0.00 | 0.166550E+11 | 0.160060E+11 | 7708.72 | 31-JUL-23:53 | 7701.35 | 0.00 |
August | 0.00 | 0.00 | 0.217027E+11 | 0.210288E+11 | 8750.97 | 07-AUG-13:10 | 8046.11 | 0.00 |
September | 0.00 | 0.00 | 0.621027E+10 | 0.568213E+10 | 4018.78 | 30-SEP-24:00 | 3994.62 | 0.00 |
October | 0.00 | 0.00 | 0.113369E+11 | 0.108974E+11 | 5864.34 | 31-OCT-24:00 | 5856.67 | 0.00 |
November | 0.00 | 0.00 | 0.154412E+11 | 0.151973E+11 | 6718.24 | 07-NOV-16:40 | 6183.41 | 0.00 |
December | 0.00 | 0.00 | 0.207021E+11 | 0.205201E+11 | 8642.62 | 14-DEC-17:00 | 8165.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160043E+12 | 0.155485E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.497309E+10 | 0.486926E+10 | 2720.09 | 2365.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.217027E+11 | 0.210288E+11 | 8750.97 | 8165.84 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.344389E+11 | 0.334406E+11 | 25353.14 | 19-JAN-17:00 | 21815.61 | 0.00 |
February | 0.00 | 0.00 | 0.801566E+11 | 0.783604E+11 | 43879.35 | 27-FEB-17:00 | 40366.83 | 0.00 |
March | 0.00 | 0.00 | 0.141024E+12 | 0.139044E+12 | 71583.49 | 31-MAR-24:00 | 71583.49 | 0.00 |
April | 0.00 | 0.00 | 0.192398E+12 | 0.189417E+12 | 82278.49 | 28-APR-16:30 | 77239.41 | 0.00 |
May | 0.00 | 0.00 | 0.588475E+11 | 0.539934E+11 | 38094.17 | 31-MAY-23:10 | 36453.29 | 0.00 |
June | 0.00 | 0.00 | 0.105778E+12 | 0.100117E+12 | 56578.06 | 30-JUN-23:53 | 56439.18 | 0.00 |
July | 0.00 | 0.00 | 0.158407E+12 | 0.151930E+12 | 73753.20 | 31-JUL-23:53 | 73678.24 | 0.00 |
August | 0.00 | 0.00 | 0.207103E+12 | 0.200367E+12 | 83702.75 | 07-AUG-13:10 | 76699.80 | 0.00 |
September | 0.00 | 0.00 | 0.563009E+11 | 0.510959E+11 | 37081.19 | 30-SEP-24:00 | 36806.79 | 0.00 |
October | 0.00 | 0.00 | 0.105214E+12 | 0.100842E+12 | 54183.47 | 31-OCT-24:00 | 54086.41 | 0.00 |
November | 0.00 | 0.00 | 0.140490E+12 | 0.138059E+12 | 64130.56 | 07-NOV-16:40 | 58796.71 | 0.00 |
December | 0.00 | 0.00 | 0.187037E+12 | 0.185215E+12 | 82202.08 | 14-DEC-17:00 | 77446.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.146720E+13 | 0.142188E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.344389E+11 | 0.334406E+11 | 25353.14 | 21815.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.207103E+12 | 0.200367E+12 | 83702.75 | 77446.16 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.236933E+10 | 0.227141E+10 | 2613.96 | 19-JAN-17:00 | 2259.25 | 0.00 |
February | 0.00 | 0.00 | 0.720872E+10 | 0.703024E+10 | 4466.71 | 27-FEB-17:00 | 4114.71 | 0.00 |
March | 0.00 | 0.00 | 0.135032E+11 | 0.133058E+11 | 7059.03 | 31-MAR-24:00 | 7058.70 | 0.00 |
April | 0.00 | 0.00 | 0.191085E+11 | 0.188109E+11 | 8371.64 | 28-APR-16:10 | 7853.76 | 0.00 |
May | 0.00 | 0.00 | 0.605677E+10 | 0.556897E+10 | 3806.14 | 31-MAY-23:10 | 3644.31 | 0.00 |
June | 0.00 | 0.00 | 0.107596E+11 | 0.101927E+11 | 5719.90 | 30-JUN-23:53 | 5706.18 | 0.00 |
July | 0.00 | 0.00 | 0.160183E+11 | 0.153706E+11 | 7374.98 | 31-JUL-23:53 | 7367.37 | 0.00 |
August | 0.00 | 0.00 | 0.208622E+11 | 0.201888E+11 | 8445.85 | 10-AUG-16:00 | 7832.24 | 0.00 |
September | 0.00 | 0.00 | 0.576360E+10 | 0.524122E+10 | 3747.99 | 30-SEP-24:00 | 3721.50 | 0.00 |
October | 0.00 | 0.00 | 0.104845E+11 | 0.100473E+11 | 5354.86 | 31-OCT-24:00 | 5344.35 | 0.00 |
November | 0.00 | 0.00 | 0.134660E+11 | 0.132237E+11 | 6474.40 | 07-NOV-16:40 | 5941.15 | 0.00 |
December | 0.00 | 0.00 | 0.178015E+11 | 0.176200E+11 | 8282.90 | 14-DEC-17:00 | 7807.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143402E+12 | 0.138872E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.236933E+10 | 0.227141E+10 | 2613.96 | 2259.25 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208622E+11 | 0.201888E+11 | 8445.85 | 7853.76 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7939.98 | 835402.57 | 10-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 4244.57 | 791024.58 | 06-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3206.30 | 674912.12 | 11-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 54.64 | 24618.72 | 03-APR-16:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.24 | 4622.43 | 28-OCT-06:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 298.36 | 98675.35 | 16-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5462.52 | 804124.28 | 21-DEC-06:01 |
Annual Sum or Average | 0.00 | 1766.61 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 7939.98 | 835402.57 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 263439.47 | 1655840.59 | 20-JAN-06:04 | 16.53 | 87635.05 | 30-JAN-04:12 |
February | 399189.82 | 1631031.01 | 24-FEB-17:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 432880.04 | 1956350.23 | 28-MAR-05:04 | 19.12 | 122747.56 | 19-MAR-08:00 |
April | 673911.62 | 1961768.07 | 14-APR-05:04 | 0.00 | 0.00 | 01-APR-00:10 |
May | 875812.19 | 2278459.56 | 22-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 929170.74 | 1750778.01 | 21-JUN-15:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 928214.29 | 1930802.71 | 12-JUL-05:04 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 955831.04 | 1915951.72 | 29-AUG-05:04 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 890065.29 | 1931434.11 | 20-SEP-05:04 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 787505.05 | 1932204.51 | 21-OCT-05:04 | 0.52 | 5539.56 | 29-OCT-23:43 |
November | 539481.18 | 2105999.99 | 01-NOV-05:04 | 4.80 | 48944.20 | 19-NOV-18:33 |
December | 364215.72 | 1997655.87 | 12-DEC-06:04 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 671235.65 | 3.47 | ||||
Minimum of Months | 263439.47 | 1631031.01 | 0.00 | 0.00 | ||
Maximum of Months | 955831.04 | 2278459.56 | 19.12 | 122747.56 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 200185.64 | 2254720.03 | 20-JAN-06:02 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 316156.60 | 2305323.54 | 27-FEB-06:03 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 329558.44 | 2665191.33 | 27-MAR-05:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 527382.16 | 2617700.69 | 14-APR-05:02 | 0.00 | 0.00 | 01-APR-00:10 |
May | 735866.62 | 2817411.06 | 22-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 781067.23 | 2478397.72 | 01-JUN-05:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 775994.28 | 2554904.14 | 06-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 815739.99 | 2602225.76 | 29-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 758657.90 | 2652133.04 | 22-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 650317.84 | 2701712.98 | 21-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 418962.91 | 2812633.85 | 01-NOV-05:02 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 285747.10 | 2578014.50 | 12-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 550767.67 | 0.00 | ||||
Minimum of Months | 200185.64 | 2254720.03 | 0.00 | 0.00 | ||
Maximum of Months | 815739.99 | 2817411.06 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 28186.40 | 124914.52 | 02-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 62710.05 | 169532.14 | 02-FEB-13:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 100764.25 | 218135.30 | 30-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 157845.94 | 295556.73 | 28-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 123824.96 | 198429.86 | 18-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 163937.93 | 248335.60 | 14-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 199385.08 | 297508.14 | 21-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 225637.60 | 324834.72 | 30-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 116610.07 | 228484.77 | 09-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 129378.00 | 238861.24 | 05-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 111214.39 | 227700.58 | 01-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 123681.25 | 256776.21 | 13-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 129043.05 | 0.00 | ||||
Minimum of Months | 28186.40 | 124914.52 | 0.00 | 0.00 | ||
Maximum of Months | 225637.60 | 324834.72 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 12871.72 | 42424.03 | 25-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 12847.91 | 42353.45 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 13091.92 | 41416.62 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11687.25 | 39165.77 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 11287.00 | 36780.07 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 10898.71 | 34306.95 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 9868.03 | 32662.19 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 10767.39 | 33353.66 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 10639.74 | 35277.13 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11292.29 | 38034.64 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12157.85 | 40415.14 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12325.76 | 41969.98 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 11638.01 | ||||
Minimum of Months | 0.00 | 0.00 | 9868.03 | 32662.19 | ||
Maximum of Months | 0.00 | 0.00 | 13091.92 | 42424.03 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 190324.23 | 3238903.48 | 19-JAN-15:00 | 1590.16 | 180023.89 | 04-JAN-08:00 |
February | 286550.13 | 3161890.11 | 24-FEB-17:00 | 1030.34 | 178463.04 | 17-FEB-09:10 |
March | 340404.40 | 3759327.63 | 07-MAR-15:00 | 1975.15 | 185950.92 | 09-MAR-08:40 |
April | 641518.44 | 5612529.32 | 28-APR-16:00 | 901.08 | 103408.11 | 03-APR-04:50 |
May | 1621087.00 | 5939734.76 | 26-MAY-10:40 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1953814.54 | 6215091.75 | 27-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 2356150.28 | 6412201.90 | 12-JUL-10:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 2267477.33 | 6371226.05 | 17-AUG-14:10 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1813838.09 | 6228143.37 | 18-SEP-10:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1400221.36 | 6380596.67 | 24-OCT-10:40 | 268.44 | 93121.98 | 27-OCT-20:40 |
November | 577949.41 | 5189123.04 | 02-NOV-14:00 | 728.55 | 111131.73 | 09-NOV-09:00 |
December | 341856.29 | 4651384.81 | 12-DEC-14:00 | 1603.71 | 165691.92 | 20-DEC-20:10 |
Annual Sum or Average | 1155288.12 | 674.79 | ||||
Minimum of Months | 190324.23 | 3161890.11 | 0.00 | 0.00 | ||
Maximum of Months | 2356150.28 | 6412201.90 | 1975.15 | 185950.92 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135521E+11 | 0.82 | 8544.02 | 01-JAN-00:15 | 1.37 |
February | 0.118198E+11 | 0.79 | 8544.02 | 01-FEB-04:03 | 1.38 |
March | 0.137337E+11 | 0.83 | 8544.02 | 01-MAR-04:03 | 1.38 |
April | 0.125905E+11 | 0.78 | 8544.02 | 01-APR-03:02 | 1.38 |
May | 0.135020E+11 | 0.81 | 8544.02 | 01-MAY-03:02 | 1.38 |
June | 0.134637E+11 | 0.83 | 8544.02 | 01-JUN-03:02 | 1.38 |
July | 0.129438E+11 | 0.78 | 8544.02 | 01-JUL-03:02 | 1.38 |
August | 0.146198E+11 | 0.88 | 8544.02 | 01-AUG-03:02 | 1.38 |
September | 0.137738E+11 | 0.85 | 8544.02 | 01-SEP-03:02 | 1.38 |
October | 0.142453E+11 | 0.86 | 8544.02 | 01-OCT-15:53 | 1.38 |
November | 0.137663E+11 | 0.86 | 8544.02 | 01-NOV-03:02 | 1.38 |
December | 0.138456E+11 | 0.84 | 8544.02 | 01-DEC-04:03 | 1.39 |
Annual Sum or Average | 0.161856E+12 | 0.83 | |||
Minimum of Months | 0.118198E+11 | 0.78 | 8544.02 | 1.37 | |
Maximum of Months | 0.146198E+11 | 0.88 | 8544.02 | 1.39 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.355840E+10 | 0.32 | 18158.17 | 30-JAN-06:02 | 1.76 |
February | 0.364915E+10 | 0.34 | 12575.64 | 27-FEB-06:03 | 1.39 |
March | 0.459576E+10 | 0.39 | 16154.62 | 27-MAR-05:02 | 1.63 |
April | 0.541804E+10 | 0.46 | 18158.17 | 28-APR-05:02 | 1.76 |
May | 0.545659E+10 | 0.43 | 18158.17 | 02-MAY-05:03 | 1.76 |
June | 0.608899E+10 | 0.49 | 18158.17 | 06-JUN-05:02 | 1.76 |
July | 0.659325E+10 | 0.51 | 18158.17 | 03-JUL-05:02 | 1.76 |
August | 0.754641E+10 | 0.56 | 18158.17 | 07-AUG-05:03 | 1.76 |
September | 0.523618E+10 | 0.43 | 18158.17 | 01-SEP-05:02 | 1.76 |
October | 0.596378E+10 | 0.45 | 18158.17 | 03-OCT-05:03 | 1.76 |
November | 0.506506E+10 | 0.41 | 17581.78 | 02-NOV-05:02 | 1.72 |
December | 0.474974E+10 | 0.39 | 18158.17 | 11-DEC-06:02 | 1.76 |
Annual Sum or Average | 0.639213E+11 | 0.43 | |||
Minimum of Months | 0.355840E+10 | 0.32 | 12575.64 | 1.39 | |
Maximum of Months | 0.754641E+10 | 0.56 | 18158.17 | 1.76 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.273363E+11 | 0.29 | 126729.94 | 20-JAN-06:02 | 1.47 |
February | 0.258848E+11 | 0.30 | 124986.14 | 27-FEB-06:03 | 1.46 |
March | 0.305833E+11 | 0.32 | 167118.91 | 27-MAR-05:02 | 1.76 |
April | 0.338173E+11 | 0.33 | 167118.91 | 14-APR-05:02 | 1.76 |
May | 0.459155E+11 | 0.39 | 167118.91 | 05-MAY-05:03 | 1.76 |
June | 0.474574E+11 | 0.42 | 167118.91 | 01-JUN-05:03 | 1.76 |
July | 0.467889E+11 | 0.40 | 167118.91 | 06-JUL-05:02 | 1.76 |
August | 0.495398E+11 | 0.42 | 167118.91 | 01-AUG-05:02 | 1.76 |
September | 0.418904E+11 | 0.38 | 167118.91 | 08-SEP-05:02 | 1.76 |
October | 0.440613E+11 | 0.38 | 167118.91 | 03-OCT-05:03 | 1.76 |
November | 0.326715E+11 | 0.32 | 167118.91 | 29-NOV-06:02 | 1.76 |
December | 0.292168E+11 | 0.30 | 167118.91 | 12-DEC-06:02 | 1.76 |
Annual Sum or Average | 0.455163E+12 | 0.35 | |||
Minimum of Months | 0.258848E+11 | 0.29 | 124986.14 | 1.46 | |
Maximum of Months | 0.495398E+11 | 0.42 | 167118.91 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.273040E+10 | 0.29 | 9701.84 | 20-JAN-06:02 | 1.19 |
February | 0.259489E+10 | 0.29 | 11224.28 | 28-FEB-06:03 | 1.30 |
March | 0.304852E+10 | 0.31 | 16785.05 | 27-MAR-05:02 | 1.68 |
April | 0.348541E+10 | 0.32 | 18043.19 | 27-APR-05:02 | 1.76 |
May | 0.525128E+10 | 0.41 | 18043.19 | 05-MAY-05:03 | 1.76 |
June | 0.554028E+10 | 0.44 | 18043.19 | 21-JUN-05:03 | 1.76 |
July | 0.540352E+10 | 0.43 | 18043.19 | 10-JUL-05:03 | 1.76 |
August | 0.566881E+10 | 0.43 | 18043.19 | 01-AUG-05:02 | 1.76 |
September | 0.453935E+10 | 0.39 | 18043.19 | 05-SEP-03:02 | 1.76 |
October | 0.464639E+10 | 0.37 | 18043.19 | 21-OCT-05:02 | 1.76 |
November | 0.308329E+10 | 0.31 | 18043.19 | 01-NOV-05:02 | 1.76 |
December | 0.283898E+10 | 0.29 | 13353.42 | 15-DEC-06:03 | 1.45 |
Annual Sum or Average | 0.488311E+11 | 0.36 | |||
Minimum of Months | 0.259489E+10 | 0.29 | 9701.84 | 1.19 | |
Maximum of Months | 0.566881E+10 | 0.44 | 18043.19 | 1.76 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137543E+10 | 0.91 | 513.53 | 01-JAN-00:05 | 0.91 |
February | 0.124233E+10 | 0.91 | 513.53 | 01-FEB-00:10 | 0.91 |
March | 0.137543E+10 | 0.91 | 513.53 | 01-MAR-00:10 | 0.91 |
April | 0.133106E+10 | 0.91 | 513.53 | 01-APR-00:10 | 0.91 |
May | 0.137543E+10 | 0.91 | 513.53 | 01-MAY-00:03 | 0.91 |
June | 0.133106E+10 | 0.91 | 513.53 | 01-JUN-00:10 | 0.91 |
July | 0.137543E+10 | 0.91 | 513.53 | 01-JUL-00:10 | 0.91 |
August | 0.137543E+10 | 0.91 | 513.53 | 01-AUG-00:03 | 0.91 |
September | 0.133106E+10 | 0.91 | 513.53 | 01-SEP-00:05 | 0.91 |
October | 0.137543E+10 | 0.91 | 513.53 | 01-OCT-00:10 | 0.91 |
November | 0.133106E+10 | 0.91 | 513.53 | 01-NOV-00:10 | 0.91 |
December | 0.137543E+10 | 0.91 | 513.53 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.161946E+11 | 0.91 | |||
Minimum of Months | 0.124233E+10 | 0.91 | 513.53 | 0.91 | |
Maximum of Months | 0.137543E+10 | 0.91 | 513.53 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.130852E+11 | 0.91 | 4885.47 | 01-JAN-00:05 | 0.91 |
February | 0.118189E+11 | 0.91 | 4885.47 | 01-FEB-00:10 | 0.91 |
March | 0.130852E+11 | 0.91 | 4885.47 | 01-MAR-00:10 | 0.91 |
April | 0.126631E+11 | 0.91 | 4885.47 | 01-APR-00:10 | 0.91 |
May | 0.130852E+11 | 0.91 | 4885.47 | 01-MAY-00:03 | 0.91 |
June | 0.126631E+11 | 0.91 | 4885.47 | 01-JUN-00:10 | 0.91 |
July | 0.130852E+11 | 0.91 | 4885.47 | 01-JUL-00:10 | 0.91 |
August | 0.130852E+11 | 0.91 | 4885.47 | 01-AUG-00:03 | 0.91 |
September | 0.126631E+11 | 0.91 | 4885.47 | 01-SEP-00:05 | 0.91 |
October | 0.130852E+11 | 0.91 | 4885.47 | 01-OCT-00:10 | 0.91 |
November | 0.126631E+11 | 0.91 | 4885.47 | 01-NOV-00:10 | 0.91 |
December | 0.130852E+11 | 0.91 | 4885.47 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.154068E+12 | 0.91 | |||
Minimum of Months | 0.118189E+11 | 0.91 | 4885.47 | 0.91 | |
Maximum of Months | 0.130852E+11 | 0.91 | 4885.47 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.133514E+10 | 0.91 | 498.48 | 01-JAN-00:05 | 0.91 |
February | 0.120593E+10 | 0.91 | 498.48 | 01-FEB-00:10 | 0.91 |
March | 0.133514E+10 | 0.91 | 498.48 | 01-MAR-00:10 | 0.91 |
April | 0.129207E+10 | 0.91 | 498.48 | 01-APR-00:10 | 0.91 |
May | 0.133514E+10 | 0.91 | 498.48 | 01-MAY-00:03 | 0.91 |
June | 0.129207E+10 | 0.91 | 498.48 | 01-JUN-00:10 | 0.91 |
July | 0.133514E+10 | 0.91 | 498.48 | 01-JUL-00:10 | 0.91 |
August | 0.133514E+10 | 0.91 | 498.48 | 01-AUG-00:03 | 0.91 |
September | 0.129207E+10 | 0.91 | 498.48 | 01-SEP-00:05 | 0.91 |
October | 0.133514E+10 | 0.91 | 498.48 | 01-OCT-00:10 | 0.91 |
November | 0.129207E+10 | 0.91 | 498.48 | 01-NOV-00:10 | 0.91 |
December | 0.133514E+10 | 0.91 | 498.48 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.157202E+11 | 0.91 | |||
Minimum of Months | 0.120593E+10 | 0.91 | 498.48 | 0.91 | |
Maximum of Months | 0.133514E+10 | 0.91 | 498.48 | 0.91 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 89682562.95 | 81521449.72 | 2589.69 | 10-JAN-06:02 | 2354.03 | 2354.03 | 38.30 | 4.73 |
February | 43768120.38 | 39785221.43 | 2590.88 | 06-FEB-06:02 | 2355.11 | 2355.11 | 40.57 | 4.73 |
March | 34956199.45 | 31775185.30 | 2172.47 | 11-MAR-06:02 | 1974.77 | 1974.77 | 31.65 | 3.34 |
April | 607970.87 | 552645.52 | 98.92 | 03-APR-16:50 | 89.92 | 89.92 | 22.28 | 0.10 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 32.02 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 32.02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 32.02 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 32.02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 32.02 | 0.00 |
October | 205951.16 | 187209.60 | 21.88 | 28-OCT-06:50 | 19.88 | 19.88 | 30.34 | 0.02 |
November | 3250410.43 | 2954623.09 | 397.33 | 16-NOV-06:02 | 361.17 | 361.17 | 24.59 | 0.43 |
December | 60560773.63 | 55049743.23 | 2586.03 | 21-DEC-06:01 | 2350.70 | 2350.70 | 40.08 | 4.71 |
Annual Sum or Average | 0.233032E+09 | 0.211826E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.28 | 0.00 | |
Maximum of Months | 89682562.95 | 81521449.72 | 2590.88 | 2355.11 | 2355.11 | 40.57 | 4.73 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.611764E+09 | 0.556093E+09 | 10742.64 | 20-JAN-06:04 | 9765.06 | 9765.06 | 8.67 | 87.93 |
February | 0.975467E+09 | 0.886700E+09 | 9306.32 | 27-FEB-06:03 | 8459.45 | 8459.45 | 8.83 | 82.90 |
March | 0.108078E+10 | 0.982430E+09 | 13022.34 | 27-MAR-05:02 | 11837.31 | 11837.31 | 8.54 | 95.09 |
April | 0.180977E+10 | 0.164508E+10 | 14455.07 | 14-APR-05:04 | 13139.66 | 13139.66 | 8.47 | 99.18 |
May | 0.319827E+10 | 0.290723E+10 | 15835.68 | 22-MAY-05:03 | 14394.63 | 14394.63 | 7.60 | 102.88 |
June | 0.338376E+10 | 0.307584E+10 | 10781.37 | 07-JUN-05:03 | 9800.27 | 9800.27 | 8.42 | 88.06 |
July | 0.354243E+10 | 0.322007E+10 | 10951.39 | 06-JUL-05:02 | 9954.81 | 9954.81 | 7.80 | 88.62 |
August | 0.384932E+10 | 0.349903E+10 | 11140.97 | 29-AUG-05:02 | 10127.14 | 10127.14 | 8.10 | 89.25 |
September | 0.329639E+10 | 0.299642E+10 | 12769.68 | 22-SEP-05:02 | 11607.64 | 11607.64 | 8.31 | 94.33 |
October | 0.286841E+10 | 0.260739E+10 | 11826.24 | 21-OCT-05:02 | 10750.05 | 10750.05 | 7.72 | 91.44 |
November | 0.149411E+10 | 0.135814E+10 | 12870.71 | 08-NOV-06:03 | 11699.48 | 11699.48 | 8.62 | 94.64 |
December | 0.100719E+10 | 0.915534E+09 | 11732.69 | 12-DEC-06:04 | 10665.02 | 10665.02 | 8.28 | 91.15 |
Annual Sum or Average | 0.271177E+11 | 0.246500E+11 | ||||||
Minimum of Months | 0.611764E+09 | 0.556093E+09 | 9306.32 | 8459.45 | 8459.45 | 7.60 | 82.90 | |
Maximum of Months | 0.384932E+10 | 0.349903E+10 | 15835.68 | 14394.63 | 14394.63 | 8.83 | 102.88 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.180057E+11 | 0.163672E+11 | 17557.44 | 01-JAN-01:03 | 15959.71 | 15959.71 | 8.23 | 124.29 |
February | 0.208840E+11 | 0.189836E+11 | 17557.44 | 01-FEB-04:03 | 15959.71 | 15959.71 | 9.54 | 124.29 |
March | 0.267925E+11 | 0.243544E+11 | 17557.44 | 01-MAR-04:03 | 15959.71 | 15959.71 | 9.49 | 124.29 |
April | 0.352292E+11 | 0.320233E+11 | 17557.44 | 01-APR-03:02 | 15959.71 | 15959.71 | 9.46 | 124.29 |
May | 0.350043E+11 | 0.318189E+11 | 17557.44 | 01-MAY-00:03 | 15959.71 | 15959.71 | 7.64 | 124.29 |
June | 0.376918E+11 | 0.342618E+11 | 17557.44 | 01-JUN-03:02 | 15959.71 | 15959.71 | 9.29 | 124.29 |
July | 0.413939E+11 | 0.376271E+11 | 17557.44 | 01-JUL-00:10 | 15959.71 | 15959.71 | 7.19 | 124.29 |
August | 0.427290E+11 | 0.388407E+11 | 17557.44 | 01-AUG-00:03 | 15959.71 | 15959.71 | 7.18 | 124.29 |
September | 0.346287E+11 | 0.314775E+11 | 17557.44 | 01-SEP-00:05 | 15959.71 | 15959.71 | 7.21 | 124.29 |
October | 0.355828E+11 | 0.323447E+11 | 17557.44 | 01-OCT-07:33 | 15959.71 | 15959.71 | 8.75 | 124.29 |
November | 0.291504E+11 | 0.264977E+11 | 17557.44 | 01-NOV-01:53 | 15959.71 | 15959.71 | 9.09 | 124.29 |
December | 0.236959E+11 | 0.215395E+11 | 17557.44 | 01-DEC-04:03 | 15959.71 | 15959.71 | 8.72 | 124.29 |
Annual Sum or Average | 0.380788E+12 | 0.346136E+12 | ||||||
Minimum of Months | 0.180057E+11 | 0.163672E+11 | 17557.44 | 15959.71 | 15959.71 | 7.18 | 124.29 | |
Maximum of Months | 0.427290E+11 | 0.388407E+11 | 17557.44 | 15959.71 | 15959.71 | 9.54 | 124.29 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.178518E+10 | 0.162273E+10 | 666.51 | 01-JAN-00:05 | 605.86 | 605.86 | 21.21 | 2.81 |
February | 0.161242E+10 | 0.146569E+10 | 666.51 | 01-FEB-00:10 | 605.86 | 605.86 | 24.00 | 2.81 |
March | 0.178518E+10 | 0.162273E+10 | 666.51 | 01-MAR-00:10 | 605.86 | 605.86 | 26.42 | 2.81 |
April | 0.172759E+10 | 0.157038E+10 | 666.51 | 01-APR-00:10 | 605.86 | 605.86 | 32.90 | 2.81 |
May | 0.178518E+10 | 0.162273E+10 | 666.51 | 01-MAY-00:03 | 605.86 | 605.86 | 26.11 | 2.81 |
June | 0.172759E+10 | 0.157038E+10 | 666.51 | 01-JUN-00:10 | 605.86 | 605.86 | 29.54 | 2.81 |
July | 0.178518E+10 | 0.162273E+10 | 666.51 | 01-JUL-00:10 | 605.86 | 605.86 | 34.96 | 2.81 |
August | 0.178518E+10 | 0.162273E+10 | 666.51 | 01-AUG-00:03 | 605.86 | 605.86 | 37.99 | 2.81 |
September | 0.172759E+10 | 0.157038E+10 | 666.51 | 01-SEP-00:05 | 605.86 | 605.86 | 28.70 | 2.81 |
October | 0.178518E+10 | 0.162273E+10 | 666.51 | 01-OCT-00:10 | 605.86 | 605.86 | 28.67 | 2.81 |
November | 0.172759E+10 | 0.157038E+10 | 666.51 | 01-NOV-00:10 | 605.86 | 605.86 | 30.96 | 2.81 |
December | 0.178518E+10 | 0.162273E+10 | 666.51 | 01-DEC-00:10 | 605.86 | 605.86 | 28.61 | 2.81 |
Annual Sum or Average | 0.210191E+11 | 0.191063E+11 | ||||||
Minimum of Months | 0.161242E+10 | 0.146569E+10 | 666.51 | 605.86 | 605.86 | 21.21 | 2.81 | |
Maximum of Months | 0.178518E+10 | 0.162273E+10 | 666.51 | 605.86 | 605.86 | 37.99 | 2.81 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:05 | 1.79 | 1.79 | 56.28 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:03 | 1.79 | 1.79 | 56.92 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:03 | 1.79 | 1.79 | 56.31 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:03 | 1.79 | 1.79 | 57.10 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:03 | 1.79 | 1.79 | 57.17 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:03 | 1.79 | 1.79 | 57.19 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:02 | 1.79 | 1.79 | 57.06 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:02 | 1.79 | 1.79 | 56.42 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:02 | 1.79 | 1.79 | 57.02 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 57.36 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:02 | 1.79 | 1.79 | 57.01 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:03 | 1.79 | 1.79 | 56.64 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 56.28 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 57.36 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.228353E+11 | 0.207573E+11 | 43618.49 | 19-JAN-15:00 | 39649.21 | 39649.21 | 26.40 | 146.18 |
February | 0.263039E+11 | 0.239103E+11 | 43613.88 | 24-FEB-17:00 | 39645.02 | 39645.02 | 26.28 | 146.18 |
March | 0.338757E+11 | 0.307930E+11 | 43649.67 | 07-MAR-15:00 | 39677.55 | 39677.55 | 27.25 | 146.18 |
April | 0.460200E+11 | 0.418322E+11 | 43706.68 | 28-APR-15:20 | 39729.37 | 39729.37 | 28.99 | 146.18 |
May | 0.535088E+11 | 0.486395E+11 | 43706.68 | 01-MAY-14:20 | 39729.37 | 39729.37 | 28.96 | 146.18 |
June | 0.583960E+11 | 0.530819E+11 | 43706.68 | 01-JUN-11:50 | 39729.37 | 39729.37 | 29.08 | 146.18 |
July | 0.645516E+11 | 0.586774E+11 | 43706.68 | 03-JUL-08:70 | 39729.37 | 39729.37 | 29.30 | 146.18 |
August | 0.673073E+11 | 0.611823E+11 | 43706.68 | 01-AUG-08:50 | 39729.37 | 39729.37 | 29.54 | 146.18 |
September | 0.532470E+11 | 0.484015E+11 | 43706.68 | 01-SEP-08:00 | 39729.37 | 39729.37 | 29.38 | 146.18 |
October | 0.533029E+11 | 0.484524E+11 | 43706.68 | 05-OCT-09:10 | 39729.37 | 39729.37 | 28.82 | 146.18 |
November | 0.389006E+11 | 0.353607E+11 | 43706.68 | 01-NOV-12:20 | 39729.37 | 39729.37 | 29.11 | 146.18 |
December | 0.309278E+11 | 0.281133E+11 | 43703.21 | 12-DEC-14:00 | 39726.21 | 39726.21 | 28.71 | 146.18 |
Annual Sum or Average | 0.549177E+12 | 0.499202E+12 | ||||||
Minimum of Months | 0.228353E+11 | 0.207573E+11 | 43613.88 | 39645.02 | 39645.02 | 26.28 | 146.18 | |
Maximum of Months | 0.673073E+11 | 0.611823E+11 | 43706.68 | 39729.37 | 39729.37 | 29.54 | 146.18 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 79.40 | 79.40 | 7939.98 | 835402.57 | 10-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.45 | 18.45 | 4244.57 | 791024.58 | 06-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.76 | 17.76 | 3206.30 | 674912.12 | 11-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.62 | 20.62 | 54.64 | 24618.72 | 03-APR-16:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 32.02 | 32.02 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.02 | 32.02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.02 | 32.02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 32.02 | 32.02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 32.02 | 32.02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 32.02 | 32.02 | 16.24 | 4622.43 | 28-OCT-06:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 28.59 | 28.59 | 298.36 | 98675.35 | 16-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 22.78 | 22.78 | 5462.52 | 804124.28 | 21-DEC-06:01 |
Annual Sum or Average | 0.00 | 1766.61 | ||||||
Minimum of Months | 0.00 | 0.00 | 17.76 | 17.76 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 79.40 | 79.40 | 7939.98 | 835402.57 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 263439.47 | 1655840.59 | 20-JAN-06:04 | 11.34 | 8.16 | 16.53 | 87635.05 | 30-JAN-04:12 |
February | 399189.82 | 1631031.01 | 24-FEB-17:00 | 10.18 | 7.05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 432880.04 | 1956350.23 | 28-MAR-05:04 | 11.61 | 7.85 | 19.12 | 122747.56 | 19-MAR-08:00 |
April | 673911.62 | 1961768.07 | 14-APR-05:04 | 11.66 | 7.89 | 0.00 | 0.00 | 01-APR-00:10 |
May | 875812.19 | 2278459.56 | 22-MAY-05:03 | 11.17 | 6.79 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 929170.74 | 1750778.01 | 21-JUN-15:10 | 10.06 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 928214.29 | 1930802.71 | 12-JUL-05:04 | 10.83 | 7.12 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 955831.04 | 1915951.72 | 29-AUG-05:04 | 10.98 | 7.30 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 890065.29 | 1931434.11 | 20-SEP-05:04 | 10.94 | 7.23 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 787505.05 | 1932204.51 | 21-OCT-05:04 | 10.94 | 7.23 | 0.52 | 5539.56 | 29-OCT-23:43 |
November | 539481.18 | 2105999.99 | 01-NOV-05:04 | 11.36 | 7.31 | 4.80 | 48944.20 | 19-NOV-18:33 |
December | 364215.72 | 1997655.87 | 12-DEC-06:04 | 11.52 | 7.68 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 671235.65 | 3.47 | ||||||
Minimum of Months | 263439.47 | 1631031.01 | 10.06 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 955831.04 | 2278459.56 | 11.66 | 8.16 | 19.12 | 122747.56 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 200185.64 | 2254720.03 | 20-JAN-06:02 | 13.12 | 8.82 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 316156.60 | 2305323.54 | 27-FEB-06:03 | 13.34 | 8.90 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 329558.44 | 2665191.33 | 27-MAR-05:02 | 13.39 | 8.54 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 527382.16 | 2617700.69 | 14-APR-05:02 | 13.36 | 8.66 | 0.00 | 0.00 | 01-APR-00:10 |
May | 735866.62 | 2817411.06 | 22-MAY-05:03 | 13.24 | 7.25 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 781067.23 | 2478397.72 | 01-JUN-05:03 | 13.50 | 8.47 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 775994.28 | 2554904.14 | 06-JUL-05:02 | 13.59 | 7.48 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 815739.99 | 2602225.76 | 29-AUG-05:02 | 13.66 | 8.15 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 758657.90 | 2652133.04 | 22-SEP-05:02 | 13.41 | 8.31 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 650317.84 | 2701712.98 | 21-OCT-05:02 | 13.76 | 7.47 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 418962.91 | 2812633.85 | 01-NOV-05:02 | 13.99 | 8.11 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 285747.10 | 2578014.50 | 12-DEC-06:02 | 13.58 | 8.46 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 550767.67 | 0.00 | ||||||
Minimum of Months | 200185.64 | 2254720.03 | 13.12 | 7.25 | 0.00 | 0.00 | ||
Maximum of Months | 815739.99 | 2817411.06 | 13.99 | 8.90 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 28186.40 | 124914.52 | 02-JAN-15:00 | 31.01 | 27.43 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 62710.05 | 169532.14 | 02-FEB-13:10 | 35.46 | 28.99 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 100764.25 | 218135.30 | 30-MAR-13:00 | 40.27 | 30.60 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 157845.94 | 295556.73 | 28-APR-15:00 | 47.85 | 34.93 | 0.00 | 0.00 | 01-APR-00:10 |
May | 123824.96 | 198429.86 | 18-MAY-16:00 | 38.33 | 33.85 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 163937.93 | 248335.60 | 14-JUN-14:00 | 43.24 | 35.92 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 199385.08 | 297508.14 | 21-JUL-16:00 | 48.04 | 37.44 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 225637.60 | 324834.72 | 30-AUG-16:00 | 50.68 | 37.92 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 116610.07 | 228484.77 | 09-SEP-17:00 | 41.29 | 36.94 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 129378.00 | 238861.24 | 05-OCT-15:00 | 42.31 | 34.92 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 111214.39 | 227700.58 | 01-NOV-14:00 | 41.21 | 31.24 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 123681.25 | 256776.21 | 13-DEC-15:00 | 44.07 | 31.57 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 129043.05 | 0.00 | ||||||
Minimum of Months | 28186.40 | 124914.52 | 31.01 | 27.43 | 0.00 | 0.00 | ||
Maximum of Months | 225637.60 | 324834.72 | 50.68 | 37.92 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.09 | 58.09 | 12871.72 | 42424.03 | 25-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.07 | 57.07 | 12847.91 | 42353.45 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.89 | 56.89 | 13091.92 | 41416.62 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.19 | 57.19 | 11687.25 | 39165.77 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 57.76 | 57.76 | 11287.00 | 36780.07 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.60 | 57.60 | 10898.71 | 34306.95 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.36 | 57.36 | 9868.03 | 32662.19 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 56.70 | 56.70 | 10767.39 | 33353.66 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 57.31 | 57.31 | 10639.74 | 35277.13 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.98 | 57.98 | 11292.29 | 38034.64 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.42 | 57.42 | 12157.85 | 40415.14 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.13 | 57.13 | 12325.76 | 41969.98 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 11638.01 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.70 | 56.70 | 9868.03 | 32662.19 | ||
Maximum of Months | 0.00 | 0.00 | 58.09 | 58.09 | 13091.92 | 42424.03 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 190324.23 | 3238903.48 | 19-JAN-15:00 | 26.40 | 23.45 | 1590.16 | 180023.89 | 04-JAN-08:00 |
February | 286550.13 | 3161890.11 | 24-FEB-17:00 | 26.28 | 23.12 | 1030.34 | 178463.04 | 17-FEB-09:10 |
March | 340404.40 | 3759327.63 | 07-MAR-15:00 | 27.25 | 24.08 | 1975.15 | 185950.92 | 09-MAR-08:40 |
April | 641518.44 | 5612529.32 | 28-APR-16:00 | 30.29 | 27.13 | 901.08 | 103408.11 | 03-APR-04:50 |
May | 1621087.00 | 5939734.76 | 26-MAY-10:40 | 30.82 | 27.48 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1953814.54 | 6215091.75 | 27-JUN-15:00 | 31.27 | 28.03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 2356150.28 | 6412201.90 | 12-JUL-10:10 | 31.59 | 28.24 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 2267477.33 | 6371226.05 | 17-AUG-14:10 | 31.53 | 28.21 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1813838.09 | 6228143.37 | 18-SEP-10:00 | 31.29 | 28.05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1400221.36 | 6380596.67 | 24-OCT-10:40 | 31.54 | 28.22 | 268.44 | 93121.98 | 27-OCT-20:40 |
November | 577949.41 | 5189123.04 | 02-NOV-14:00 | 29.59 | 26.27 | 728.55 | 111131.73 | 09-NOV-09:00 |
December | 341856.29 | 4651384.81 | 12-DEC-14:00 | 28.71 | 25.74 | 1603.71 | 165691.92 | 20-DEC-20:10 |
Annual Sum or Average | 1155288.12 | 674.79 | ||||||
Minimum of Months | 190324.23 | 3161890.11 | 26.28 | 23.12 | 0.00 | 0.00 | ||
Maximum of Months | 2356150.28 | 6412201.90 | 31.59 | 28.24 | 1975.15 | 185950.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 37115758.46 | 0.00 | 0.394737E+11 | 0.355840E+10 | 0.00 | 0.00 |
February | 10247720.49 | 0.00 | 0.565043E+11 | 0.364915E+10 | 0.00 | 0.00 |
March | 10842523.22 | 0.00 | 0.704633E+11 | 0.459576E+10 | 0.00 | 0.00 |
April | 6642125.06 | 0.00 | 0.113887E+12 | 0.541804E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.142552E+12 | 0.545659E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.154763E+12 | 0.608899E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.167088E+12 | 0.659325E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.181643E+12 | 0.754641E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.142557E+12 | 0.523618E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.134102E+12 | 0.596378E+10 | 0.00 | 0.00 |
November | 22446.27 | 0.00 | 0.854992E+11 | 0.506506E+10 | 0.00 | 0.00 |
December | 30094277.51 | 0.00 | 0.632382E+11 | 0.474974E+10 | 0.00 | 0.00 |
Annual Sum or Average | 94964851.02 | 0.00 | 0.135177E+13 | 0.639213E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.394737E+11 | 0.355840E+10 | 0.00 | 0.00 |
Maximum of Months | 37115758.46 | 0.00 | 0.181643E+12 | 0.754641E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.139620E+11 | 0.00 | 0.304851E+12 | 0.273363E+11 | 0.00 | 0.00 |
February | 0.630740E+10 | 0.00 | 0.435918E+12 | 0.258848E+11 | 0.00 | 0.00 |
March | 0.555067E+10 | 0.00 | 0.516071E+12 | 0.305833E+11 | 0.00 | 0.00 |
April | 60413785.72 | 0.00 | 0.817918E+12 | 0.338173E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.125516E+13 | 0.459155E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.129195E+13 | 0.474574E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.132969E+13 | 0.467889E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.137627E+13 | 0.495398E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.123468E+13 | 0.418904E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.108876E+13 | 0.440613E+11 | 0.00 | 0.00 |
November | 0.269119E+09 | 0.00 | 0.635493E+12 | 0.326715E+11 | 0.00 | 0.00 |
December | 0.952772E+10 | 0.00 | 0.440595E+12 | 0.292168E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.356773E+11 | 0.00 | 0.107274E+14 | 0.455163E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.304851E+12 | 0.258848E+11 | 0.00 | 0.00 |
Maximum of Months | 0.139620E+11 | 0.00 | 0.137627E+13 | 0.495398E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.764601E+10 | 0.00 | 0.312397E+11 | 0.273040E+10 | 0.00 | 0.00 |
February | 0.404196E+10 | 0.00 | 0.450116E+11 | 0.259489E+10 | 0.00 | 0.00 |
March | 0.308955E+10 | 0.00 | 0.541084E+11 | 0.304852E+10 | 0.00 | 0.00 |
April | 39794071.22 | 0.00 | 0.871330E+11 | 0.348541E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.140593E+12 | 0.525128E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.146918E+12 | 0.554028E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.150639E+12 | 0.540352E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.154275E+12 | 0.566881E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.134290E+12 | 0.453935E+10 | 0.00 | 0.00 |
October | 54959942.00 | 0.00 | 0.117050E+12 | 0.464639E+10 | 0.00 | 0.00 |
November | 0.529709E+09 | 0.00 | 0.637855E+11 | 0.308329E+10 | 0.00 | 0.00 |
December | 0.520677E+10 | 0.00 | 0.441520E+11 | 0.283898E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.206087E+11 | 0.00 | 0.116920E+13 | 0.488311E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.312397E+11 | 0.259489E+10 | 0.00 | 0.00 |
Maximum of Months | 0.764601E+10 | 0.00 | 0.154275E+12 | 0.566881E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.204821E+11 | 0.135521E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.243698E+11 | 0.118198E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.326463E+11 | 0.137337E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.507797E+11 | 0.125905E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.935505E+11 | 0.135020E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.982552E+11 | 0.134637E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.105253E+12 | 0.129438E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.117337E+12 | 0.146198E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.100499E+12 | 0.137738E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.866626E+11 | 0.142453E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.486032E+11 | 0.137663E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.315948E+11 | 0.138456E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.810033E+12 | 0.161856E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.204821E+11 | 0.118198E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.117337E+12 | 0.146198E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.614992E+10 | 0.255226E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.115658E+11 | 0.336090E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.191027E+11 | 0.483241E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.250110E+11 | 0.596605E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.821600E+10 | 0.321556E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.143370E+11 | 0.449157E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.212645E+11 | 0.598498E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.274843E+11 | 0.715703E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.796237E+10 | 0.308316E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.142987E+11 | 0.433722E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.189130E+11 | 0.480286E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.250848E+11 | 0.575816E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.199390E+12 | 0.555422E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.614992E+10 | 0.255226E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.274843E+11 | 0.715703E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.428122E+11 | 0.214585E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.983481E+11 | 0.300104E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.172436E+12 | 0.444979E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.236264E+12 | 0.565284E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.758700E+11 | 0.301078E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.135708E+12 | 0.425935E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.202259E+12 | 0.569380E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.262265E+12 | 0.682469E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.722375E+11 | 0.285997E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.132814E+12 | 0.406849E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.172313E+12 | 0.444858E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.226989E+12 | 0.530371E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.183032E+13 | 0.517189E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.428122E+11 | 0.214585E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.262265E+12 | 0.682469E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.296217E+10 | 0.192798E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.886300E+10 | 0.286021E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.165371E+11 | 0.436900E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.234856E+11 | 0.566916E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.781019E+10 | 0.308856E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.138070E+11 | 0.433943E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.204590E+11 | 0.577583E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.264305E+11 | 0.690346E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.739767E+10 | 0.292614E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.132472E+11 | 0.409785E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.165441E+11 | 0.437025E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.216436E+11 | 0.517732E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.179187E+12 | 0.515052E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.296217E+10 | 0.192798E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.264305E+11 | 0.690346E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.355840E+10 | 0.394737E+11 | 37115758.46 | 80450849.58 | 0.831438E+09 | 0.00 | 0.00 | 0.00 |
February | 0.364915E+10 | 0.565043E+11 | 10247720.49 | 17286937.09 | 0.137199E+10 | 0.00 | 0.00 | 0.00 |
March | 0.459576E+10 | 0.704633E+11 | 10842523.22 | 16986265.25 | 0.264568E+10 | 0.00 | 0.00 | 0.00 |
April | 0.541804E+10 | 0.113887E+12 | 6642125.06 | 0.00 | 0.730908E+10 | 0.00 | 0.00 | 0.00 |
May | 0.545659E+10 | 0.142552E+12 | 0.00 | 0.00 | 0.309336E+11 | 0.00 | 0.00 | 0.00 |
June | 0.608899E+10 | 0.154763E+12 | 0.00 | 0.00 | 0.376469E+11 | 0.00 | 0.00 | 0.00 |
July | 0.659325E+10 | 0.167088E+12 | 0.00 | 0.00 | 0.411811E+11 | 0.00 | 0.00 | 0.00 |
August | 0.754641E+10 | 0.181643E+12 | 0.00 | 0.00 | 0.405055E+11 | 0.00 | 0.00 | 0.00 |
September | 0.523618E+10 | 0.142557E+12 | 0.00 | 0.00 | 0.269111E+11 | 0.00 | 0.00 | 0.00 |
October | 0.596378E+10 | 0.134102E+12 | 0.00 | 0.00 | 0.228873E+11 | 0.00 | 0.00 | 0.00 |
November | 0.506506E+10 | 0.854992E+11 | 22446.27 | 0.00 | 0.555876E+10 | 0.00 | 0.00 | 0.00 |
December | 0.474974E+10 | 0.632382E+11 | 30094277.51 | 45944351.37 | 0.302636E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.639213E+11 | 0.135177E+13 | 94964851.02 | 0.160668E+09 | 0.220809E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.355840E+10 | 0.394737E+11 | 0.00 | 0.00 | 0.831438E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.754641E+10 | 0.181643E+12 | 37115758.46 | 80450849.58 | 0.411811E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.273363E+11 | 0.304851E+12 | 0.139620E+11 | 0.189292E+10 | 0.103471E+11 | 0.00 | 0.00 | 0.00 |
February | 0.258848E+11 | 0.435918E+12 | 0.630740E+10 | 0.591885E+09 | 0.169256E+11 | 0.00 | 0.00 | 0.00 |
March | 0.305833E+11 | 0.516071E+12 | 0.555067E+10 | 0.398038E+09 | 0.316368E+11 | 0.00 | 0.00 | 0.00 |
April | 0.338173E+11 | 0.817918E+12 | 60413785.72 | 0.00 | 0.728319E+11 | 0.00 | 0.00 | 0.00 |
May | 0.459155E+11 | 0.125516E+13 | 0.00 | 0.00 | 0.313848E+12 | 0.00 | 0.00 | 0.00 |
June | 0.474574E+11 | 0.129195E+13 | 0.00 | 0.00 | 0.379056E+12 | 0.00 | 0.00 | 0.00 |
July | 0.467889E+11 | 0.132969E+13 | 0.00 | 0.00 | 0.413724E+12 | 0.00 | 0.00 | 0.00 |
August | 0.495398E+11 | 0.137627E+13 | 0.00 | 0.00 | 0.409396E+12 | 0.00 | 0.00 | 0.00 |
September | 0.418904E+11 | 0.123468E+13 | 0.00 | 0.00 | 0.276344E+12 | 0.00 | 0.00 | 0.00 |
October | 0.440613E+11 | 0.108876E+13 | 0.00 | 0.00 | 0.231756E+12 | 0.00 | 0.00 | 0.00 |
November | 0.326715E+11 | 0.635493E+12 | 0.269119E+09 | 0.00 | 0.609508E+11 | 0.00 | 0.00 | 0.00 |
December | 0.292168E+11 | 0.440595E+12 | 0.952772E+10 | 0.179260E+10 | 0.322887E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.455163E+12 | 0.107274E+14 | 0.356773E+11 | 0.467545E+10 | 0.224910E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.258848E+11 | 0.304851E+12 | 0.00 | 0.00 | 0.103471E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.495398E+11 | 0.137627E+13 | 0.139620E+11 | 0.189292E+10 | 0.413724E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.273040E+10 | 0.312397E+11 | 0.764601E+10 | 0.486603E+09 | 0.399236E+09 | 0.00 | 0.00 | 0.00 |
February | 0.259489E+10 | 0.450116E+11 | 0.404196E+10 | 0.167009E+09 | 0.806276E+09 | 0.00 | 0.00 | 0.00 |
March | 0.304852E+10 | 0.541084E+11 | 0.308955E+10 | 0.114424E+09 | 0.208107E+10 | 0.00 | 0.00 | 0.00 |
April | 0.348541E+10 | 0.871330E+11 | 39794071.22 | 0.00 | 0.620302E+10 | 0.00 | 0.00 | 0.00 |
May | 0.525128E+10 | 0.140593E+12 | 0.00 | 0.00 | 0.302608E+11 | 0.00 | 0.00 | 0.00 |
June | 0.554028E+10 | 0.146918E+12 | 0.00 | 0.00 | 0.363825E+11 | 0.00 | 0.00 | 0.00 |
July | 0.540352E+10 | 0.150639E+12 | 0.00 | 0.00 | 0.396700E+11 | 0.00 | 0.00 | 0.00 |
August | 0.566881E+10 | 0.154275E+12 | 0.00 | 0.00 | 0.393116E+11 | 0.00 | 0.00 | 0.00 |
September | 0.453935E+10 | 0.134290E+12 | 0.00 | 0.00 | 0.264412E+11 | 0.00 | 0.00 | 0.00 |
October | 0.464639E+10 | 0.117050E+12 | 54959942.00 | 0.00 | 0.224946E+11 | 0.00 | 0.00 | 0.00 |
November | 0.308329E+10 | 0.637855E+11 | 0.529709E+09 | 0.00 | 0.570945E+10 | 0.00 | 0.00 | 0.00 |
December | 0.283898E+10 | 0.441520E+11 | 0.520677E+10 | 0.388557E+09 | 0.285818E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.488311E+11 | 0.116920E+13 | 0.206087E+11 | 0.115659E+10 | 0.212618E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.259489E+10 | 0.312397E+11 | 0.00 | 0.00 | 0.399236E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.566881E+10 | 0.154275E+12 | 0.764601E+10 | 0.486603E+09 | 0.396700E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135521E+11 | 0.204821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118198E+11 | 0.243698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137337E+11 | 0.326463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125905E+11 | 0.507797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135020E+11 | 0.935505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134637E+11 | 0.982552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129438E+11 | 0.105253E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146198E+11 | 0.117337E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137738E+11 | 0.100499E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142453E+11 | 0.866626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137663E+11 | 0.486032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138456E+11 | 0.315948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161856E+12 | 0.810033E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118198E+11 | 0.204821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146198E+11 | 0.117337E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137543E+10 | 0.497309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124233E+10 | 0.944723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137543E+10 | 0.156457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133106E+10 | 0.203760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137543E+10 | 0.637587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133106E+10 | 0.111765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137543E+10 | 0.166550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137543E+10 | 0.217027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133106E+10 | 0.621027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137543E+10 | 0.113369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133106E+10 | 0.154412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137543E+10 | 0.207021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161946E+11 | 0.160043E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124233E+10 | 0.497309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137543E+10 | 0.217027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.130852E+11 | 0.344389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118189E+11 | 0.801566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130852E+11 | 0.141024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126631E+11 | 0.192398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130852E+11 | 0.588475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126631E+11 | 0.105778E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.130852E+11 | 0.158407E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130852E+11 | 0.207103E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126631E+11 | 0.563009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130852E+11 | 0.105214E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126631E+11 | 0.140490E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130852E+11 | 0.187037E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154068E+12 | 0.146720E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118189E+11 | 0.344389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130852E+11 | 0.207103E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.133514E+10 | 0.236933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120593E+10 | 0.720872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133514E+10 | 0.135032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129207E+10 | 0.191085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133514E+10 | 0.605677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129207E+10 | 0.107596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133514E+10 | 0.160183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133514E+10 | 0.208622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129207E+10 | 0.576360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133514E+10 | 0.104845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129207E+10 | 0.134660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133514E+10 | 0.178015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157202E+11 | 0.143402E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120593E+10 | 0.236933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133514E+10 | 0.208622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.355840E+10 | 37115758.46 | 0.394737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.364915E+10 | 10247720.49 | 0.565043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.459576E+10 | 10842523.22 | 0.704633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.541804E+10 | 6642125.06 | 0.113887E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.545659E+10 | 0.00 | 0.142552E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.608899E+10 | 0.00 | 0.154763E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.659325E+10 | 0.00 | 0.167088E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.754641E+10 | 0.00 | 0.181643E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.523618E+10 | 0.00 | 0.142557E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.596378E+10 | 0.00 | 0.134102E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.506506E+10 | 22446.27 | 0.854992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.474974E+10 | 30094277.51 | 0.632382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.639213E+11 | 94964851.02 | 0.135177E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.355840E+10 | 0.00 | 0.394737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.754641E+10 | 37115758.46 | 0.181643E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.273363E+11 | 0.139620E+11 | 0.304851E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.258848E+11 | 0.630740E+10 | 0.435918E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.305833E+11 | 0.555067E+10 | 0.516071E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.338173E+11 | 60413785.72 | 0.817918E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.459155E+11 | 0.00 | 0.125516E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.474574E+11 | 0.00 | 0.129195E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.467889E+11 | 0.00 | 0.132969E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.495398E+11 | 0.00 | 0.137627E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.418904E+11 | 0.00 | 0.123468E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.440613E+11 | 0.00 | 0.108876E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.326715E+11 | 0.269119E+09 | 0.635493E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.292168E+11 | 0.952772E+10 | 0.440595E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.455163E+12 | 0.356773E+11 | 0.107274E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.258848E+11 | 0.00 | 0.304851E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.495398E+11 | 0.139620E+11 | 0.137627E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.273040E+10 | 0.764601E+10 | 0.312397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.259489E+10 | 0.404196E+10 | 0.450116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.304852E+10 | 0.308955E+10 | 0.541084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.348541E+10 | 39794071.22 | 0.871330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.525128E+10 | 0.00 | 0.140593E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.554028E+10 | 0.00 | 0.146918E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.540352E+10 | 0.00 | 0.150639E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.566881E+10 | 0.00 | 0.154275E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453935E+10 | 0.00 | 0.134290E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.464639E+10 | 54959942.00 | 0.117050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.308329E+10 | 0.529709E+09 | 0.637855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.283898E+10 | 0.520677E+10 | 0.441520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.488311E+11 | 0.206087E+11 | 0.116920E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.259489E+10 | 0.00 | 0.312397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.566881E+10 | 0.764601E+10 | 0.154275E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135521E+11 | 0.00 | 0.204821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118198E+11 | 0.00 | 0.243698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137337E+11 | 0.00 | 0.326463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125905E+11 | 0.00 | 0.507797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135020E+11 | 0.00 | 0.935505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134637E+11 | 0.00 | 0.982552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129438E+11 | 0.00 | 0.105253E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146198E+11 | 0.00 | 0.117337E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137738E+11 | 0.00 | 0.100499E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142453E+11 | 0.00 | 0.866626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137663E+11 | 0.00 | 0.486032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138456E+11 | 0.00 | 0.315948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161856E+12 | 0.00 | 0.810033E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118198E+11 | 0.00 | 0.204821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146198E+11 | 0.00 | 0.117337E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137543E+10 | 0.00 | 0.614992E+10 | 0.00 | 0.117683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124233E+10 | 0.00 | 0.115658E+11 | 0.00 | 0.211857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137543E+10 | 0.00 | 0.191027E+11 | 0.00 | 0.345698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133106E+10 | 0.00 | 0.250110E+11 | 0.00 | 0.463499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137543E+10 | 0.00 | 0.821600E+10 | 0.00 | 0.184013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133106E+10 | 0.00 | 0.143370E+11 | 0.00 | 0.316051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137543E+10 | 0.00 | 0.212645E+11 | 0.00 | 0.460955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137543E+10 | 0.00 | 0.274843E+11 | 0.00 | 0.578159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133106E+10 | 0.00 | 0.796237E+10 | 0.00 | 0.175210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137543E+10 | 0.00 | 0.142987E+11 | 0.00 | 0.296179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133106E+10 | 0.00 | 0.189130E+11 | 0.00 | 0.347180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137543E+10 | 0.00 | 0.250848E+11 | 0.00 | 0.438273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161946E+11 | 0.00 | 0.199390E+12 | 0.00 | 0.393476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124233E+10 | 0.00 | 0.614992E+10 | 0.00 | 0.117683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137543E+10 | 0.00 | 0.274843E+11 | 0.00 | 0.578159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.130852E+11 | 0.00 | 0.428122E+11 | 0.00 | 0.837330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118189E+11 | 0.00 | 0.983481E+11 | 0.00 | 0.181915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130852E+11 | 0.00 | 0.172436E+12 | 0.00 | 0.314127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126631E+11 | 0.00 | 0.236264E+12 | 0.00 | 0.438653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130852E+11 | 0.00 | 0.758700E+11 | 0.00 | 0.170226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126631E+11 | 0.00 | 0.135708E+12 | 0.00 | 0.299304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.130852E+11 | 0.00 | 0.202259E+12 | 0.00 | 0.438528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130852E+11 | 0.00 | 0.262265E+12 | 0.00 | 0.551616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126631E+11 | 0.00 | 0.722375E+11 | 0.00 | 0.159366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130852E+11 | 0.00 | 0.132814E+12 | 0.00 | 0.275997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126631E+11 | 0.00 | 0.172313E+12 | 0.00 | 0.318227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130852E+11 | 0.00 | 0.226989E+12 | 0.00 | 0.399519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154068E+12 | 0.00 | 0.183032E+13 | 0.00 | 0.363121E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118189E+11 | 0.00 | 0.428122E+11 | 0.00 | 0.837330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130852E+11 | 0.00 | 0.262265E+12 | 0.00 | 0.551616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.133514E+10 | 0.00 | 0.296217E+10 | 0.00 | 0.592840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120593E+10 | 0.00 | 0.886300E+10 | 0.00 | 0.165428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133514E+10 | 0.00 | 0.165371E+11 | 0.00 | 0.303386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129207E+10 | 0.00 | 0.234856E+11 | 0.00 | 0.437708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133514E+10 | 0.00 | 0.781019E+10 | 0.00 | 0.175342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129207E+10 | 0.00 | 0.138070E+11 | 0.00 | 0.304736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133514E+10 | 0.00 | 0.204590E+11 | 0.00 | 0.444069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133514E+10 | 0.00 | 0.264305E+11 | 0.00 | 0.556832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129207E+10 | 0.00 | 0.739767E+10 | 0.00 | 0.163406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133514E+10 | 0.00 | 0.132472E+11 | 0.00 | 0.276271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129207E+10 | 0.00 | 0.165441E+11 | 0.00 | 0.307817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133514E+10 | 0.00 | 0.216436E+11 | 0.00 | 0.384218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157202E+11 | 0.00 | 0.179187E+12 | 0.00 | 0.357850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120593E+10 | 0.00 | 0.296217E+10 | 0.00 | 0.592840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133514E+10 | 0.00 | 0.264305E+11 | 0.00 | 0.556832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.608432E+09 | 0.149314E+10 | 0.00 | 91494134.00 | 2772671.67 | 0.00 | 0.502336E+11 | 0.00 | 0.86 |
February | 0.424394E+09 | 0.152851E+10 | 0.00 | 72201781.17 | 5484318.69 | 0.00 | 0.381802E+11 | 0.00 | 0.95 |
March | 0.319142E+09 | 0.294973E+10 | 0.00 | 79338588.07 | 6012859.30 | 0.00 | 0.409997E+11 | 0.00 | 0.97 |
April | 0.186705E+09 | 0.491499E+10 | 0.00 | 53995130.34 | 70835364.00 | 0.00 | 0.187823E+11 | 0.00 | 0.83 |
May | 795109.23 | 0.231541E+11 | 0.00 | 1269361.76 | 0.219339E+09 | 0.00 | 56051099.46 | 0.00 | 0.29 |
June | 2062510.87 | 0.278402E+11 | 0.00 | 1602813.74 | 0.333361E+09 | 0.00 | 0.166840E+09 | 0.00 | 0.31 |
July | 0.00 | 0.336820E+11 | 0.00 | 55969.02 | 0.529319E+09 | 0.00 | 664647.51 | 0.00 | 0.27 |
August | 92750.20 | 0.347703E+11 | 0.00 | 139190.17 | 0.348532E+09 | 0.00 | 16867863.66 | 0.00 | 0.30 |
September | 3019722.80 | 0.259880E+11 | 0.00 | 1888632.17 | 0.318544E+09 | 0.00 | 0.118098E+09 | 0.00 | 0.29 |
October | 0.112524E+09 | 0.196005E+11 | 0.00 | 35518168.28 | 0.268860E+09 | 0.00 | 0.114968E+11 | 0.00 | 0.59 |
November | 0.328784E+09 | 0.605055E+10 | 0.00 | 88028946.85 | 40729324.07 | 0.00 | 0.333832E+11 | 0.00 | 1.02 |
December | 0.477340E+09 | 0.387097E+10 | 0.00 | 91049397.88 | 21283774.55 | 0.00 | 0.458471E+11 | 0.00 | 0.86 |
Annual Sum or Average | 0.246329E+10 | 0.185843E+12 | 0.00 | 0.516582E+09 | 0.216507E+10 | 0.00 | 0.239281E+12 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.149314E+10 | 0.00 | 55969.02 | 2772671.67 | 0.00 | 664647.51 | 0.00 | 0.27 |
Maximum of Months | 0.608432E+09 | 0.347703E+11 | 0.00 | 91494134.00 | 0.529319E+09 | 0.00 | 0.502336E+11 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.720455E+10 | 0.215935E+10 | 0.00 | 41292532.62 | 0.166386E+09 | 0.00 | 0.248780E+11 | 0.00 | 0.49 |
February | 0.372380E+10 | 0.254712E+10 | 0.00 | 34668760.31 | 0.212353E+09 | 0.00 | 0.168291E+11 | 0.00 | 0.50 |
March | 0.410885E+10 | 0.388542E+10 | 0.00 | 49132899.72 | 0.336893E+09 | 0.00 | 0.232255E+11 | 0.00 | 0.58 |
April | 0.425467E+10 | 0.594112E+10 | 0.00 | 24240964.58 | 0.733417E+09 | 0.00 | 0.583099E+10 | 0.00 | 0.50 |
May | 0.00 | 0.127075E+11 | 0.00 | 0.00 | 0.133361E+10 | 0.00 | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.131124E+11 | 0.00 | 0.00 | 0.136951E+10 | 0.00 | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.151395E+11 | 0.00 | 0.00 | 0.149588E+10 | 0.00 | 0.00 | 0.00 | 0.25 |
August | 2301105.05 | 0.157639E+11 | 0.00 | 0.00 | 0.149578E+10 | 0.00 | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.153909E+11 | 0.00 | 0.00 | 0.171090E+10 | 0.00 | 0.00 | 0.00 | 0.27 |
October | 0.110410E+10 | 0.100958E+11 | 0.00 | 16135029.89 | 0.110635E+10 | 0.00 | 0.505352E+10 | 0.00 | 0.36 |
November | 0.456266E+10 | 0.474144E+10 | 0.00 | 46746691.36 | 0.482403E+09 | 0.00 | 0.156376E+11 | 0.00 | 0.57 |
December | 0.583948E+10 | 0.410925E+10 | 0.00 | 52196684.39 | 0.366279E+09 | 0.00 | 0.267180E+11 | 0.00 | 0.56 |
Annual Sum or Average | 0.308004E+11 | 0.105594E+12 | 0.00 | 0.264414E+09 | 0.108098E+11 | 0.00 | 0.118173E+12 | 0.00 | 0.41 |
Minimum of Months | 0.00 | 0.215935E+10 | 0.00 | 0.00 | 0.166386E+09 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.720455E+10 | 0.157639E+11 | 0.00 | 52196684.39 | 0.171090E+10 | 0.00 | 0.267180E+11 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163143E+12 | 0.136523E+11 | 0.00 | 94929927.19 | 0.900987E+10 | 0.00 | 0.890719E+11 | 0.00 | 0.41 |
February | 0.905272E+11 | 0.184971E+11 | 0.00 | 94238730.76 | 0.825828E+10 | 0.00 | 0.583380E+11 | 0.00 | 0.40 |
March | 0.930387E+11 | 0.260165E+11 | 0.00 | 0.183139E+09 | 0.137529E+11 | 0.00 | 0.102393E+12 | 0.00 | 0.45 |
April | 0.221399E+11 | 0.421445E+11 | 0.00 | 0.150345E+09 | 0.246789E+11 | 0.00 | 0.350250E+11 | 0.00 | 0.38 |
May | 0.00 | 0.115915E+12 | 0.00 | 0.00 | 0.224460E+11 | 0.00 | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.121868E+12 | 0.00 | 0.00 | 0.221775E+11 | 0.00 | 0.00 | 0.00 | 0.28 |
July | 0.00 | 0.136324E+12 | 0.00 | 0.00 | 0.296768E+11 | 0.00 | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.145563E+12 | 0.00 | 0.00 | 0.242085E+11 | 0.00 | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.132571E+12 | 0.00 | 0.00 | 0.345946E+11 | 0.00 | 0.00 | 0.00 | 0.27 |
October | 0.154367E+11 | 0.906326E+11 | 0.00 | 93584549.60 | 0.197330E+11 | 0.00 | 0.324141E+11 | 0.00 | 0.33 |
November | 0.642253E+11 | 0.374342E+11 | 0.00 | 0.208071E+09 | 0.118506E+11 | 0.00 | 0.734733E+11 | 0.00 | 0.45 |
December | 0.118658E+12 | 0.283945E+11 | 0.00 | 0.138080E+09 | 0.151022E+11 | 0.00 | 0.927105E+11 | 0.00 | 0.41 |
Annual Sum or Average | 0.567169E+12 | 0.909013E+12 | 0.00 | 0.962388E+09 | 0.235489E+12 | 0.00 | 0.483426E+12 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.136523E+11 | 0.00 | 0.00 | 0.825828E+10 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.163143E+12 | 0.145563E+12 | 0.00 | 0.208071E+09 | 0.345946E+11 | 0.00 | 0.102393E+12 | 0.00 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.203186E+11 | 0.133018E+10 | 0.00 | 1975398.07 | 0.124264E+10 | 0.324626E+09 | 0.163914E+10 | 0.00 | 0.41 |
February | 0.113607E+11 | 0.196192E+10 | 0.00 | 2250662.72 | 0.112804E+10 | 0.170088E+09 | 0.165198E+10 | 0.00 | 0.40 |
March | 0.130837E+11 | 0.304763E+10 | 0.00 | 6162947.34 | 0.135011E+10 | 99306880.11 | 0.416630E+10 | 0.00 | 0.44 |
April | 0.286712E+10 | 0.449124E+10 | 0.00 | 9127958.78 | 0.233715E+10 | 0.00 | 0.252817E+10 | 0.00 | 0.37 |
May | 0.00 | 0.114098E+11 | 0.00 | 0.00 | 0.214973E+10 | 0.00 | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.122242E+11 | 0.00 | 0.00 | 0.193285E+10 | 0.00 | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.141298E+11 | 0.00 | 0.00 | 0.241007E+10 | 0.00 | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.143106E+11 | 0.00 | 0.00 | 0.253449E+10 | 0.00 | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.127371E+11 | 0.00 | 0.00 | 0.393107E+10 | 0.00 | 0.00 | 0.00 | 0.27 |
October | 0.175689E+10 | 0.856456E+10 | 0.00 | 6786260.10 | 0.222181E+10 | 0.00 | 0.236801E+10 | 0.00 | 0.32 |
November | 0.843846E+10 | 0.324446E+10 | 0.00 | 6841114.80 | 0.183501E+10 | 0.00 | 0.331855E+10 | 0.00 | 0.43 |
December | 0.171826E+11 | 0.253078E+10 | 0.00 | 1105777.90 | 0.196419E+10 | 0.164015E+09 | 0.794413E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.750080E+11 | 0.899822E+11 | 0.00 | 34250119.71 | 0.250372E+11 | 0.758036E+09 | 0.164666E+11 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.133018E+10 | 0.00 | 0.00 | 0.112804E+10 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.203186E+11 | 0.143106E+11 | 0.00 | 9127958.78 | 0.393107E+10 | 0.324626E+09 | 0.416630E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.305011E+10 | 0.256389E+09 | 0.00 | 552891.31 | 34187922.55 | 0.00 | 0.453187E+09 | 0.00 | 0.44 |
February | 0.168036E+10 | 0.323871E+09 | 0.00 | 1092857.74 | 28543003.61 | 0.00 | 0.543135E+09 | 0.00 | 0.45 |
March | 0.175504E+10 | 0.526966E+09 | 0.00 | 2268509.48 | 50434693.24 | 0.00 | 0.113144E+10 | 0.00 | 0.52 |
April | 0.717182E+09 | 0.899398E+09 | 0.00 | 2041060.49 | 88202299.52 | 0.00 | 0.455839E+09 | 0.00 | 0.52 |
May | 0.00 | 0.228395E+10 | 0.00 | 0.00 | 0.152981E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.267177E+10 | 0.00 | 0.00 | 0.104146E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.306129E+10 | 0.00 | 0.00 | 0.106427E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 288838.86 | 0.300403E+10 | 0.00 | 0.00 | 99487369.33 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.250898E+10 | 0.00 | 0.00 | 0.195125E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
October | 0.317760E+09 | 0.167087E+10 | 0.00 | 1342398.52 | 0.124992E+09 | 0.00 | 0.404471E+09 | 0.00 | 0.41 |
November | 0.124128E+10 | 0.649133E+09 | 0.00 | 2568466.87 | 60552138.87 | 0.00 | 0.937858E+09 | 0.00 | 0.52 |
December | 0.240700E+10 | 0.526764E+09 | 0.00 | 1451162.51 | 48529497.38 | 0.00 | 0.886056E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.111690E+11 | 0.183834E+11 | 0.00 | 11317346.93 | 0.109361E+10 | 0.00 | 0.481198E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.256389E+09 | 0.00 | 0.00 | 28543003.61 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.305011E+10 | 0.306129E+10 | 0.00 | 2568466.87 | 0.195125E+09 | 0.00 | 0.113144E+10 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.165702E+10 | 0.184143E+09 | 0.00 | 1492822.94 | 40510893.94 | 0.00 | 0.111146E+10 | 0.00 | 0.53 |
February | 0.987578E+09 | 0.260146E+09 | 0.00 | 1578491.79 | 24680015.38 | 0.00 | 0.814230E+09 | 0.00 | 0.56 |
March | 0.126463E+10 | 0.419044E+09 | 0.00 | 2611146.66 | 49690063.36 | 0.00 | 0.118539E+10 | 0.00 | 0.69 |
April | 0.545647E+09 | 0.712108E+09 | 0.00 | 2008548.75 | 90512922.52 | 0.00 | 0.523039E+09 | 0.00 | 0.68 |
May | 0.00 | 0.187103E+10 | 0.00 | 0.00 | 0.115068E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
June | 0.00 | 0.202976E+10 | 0.00 | 0.00 | 0.114910E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
July | 0.00 | 0.228985E+10 | 0.00 | 0.00 | 0.102328E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 219016.66 | 0.211551E+10 | 0.00 | 0.00 | 0.118764E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.192671E+10 | 0.00 | 0.00 | 0.153572E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.233807E+09 | 0.130699E+10 | 0.00 | 1094915.68 | 0.103192E+09 | 0.00 | 0.334432E+09 | 0.00 | 0.50 |
November | 0.911646E+09 | 0.465854E+09 | 0.00 | 2534838.15 | 65468097.69 | 0.00 | 0.891668E+09 | 0.00 | 0.64 |
December | 0.184093E+10 | 0.316873E+09 | 0.00 | 1499540.77 | 72848786.88 | 0.00 | 0.762440E+09 | 0.00 | 0.56 |
Annual Sum or Average | 0.744148E+10 | 0.138980E+11 | 0.00 | 12820304.75 | 0.105155E+10 | 0.00 | 0.562266E+10 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.184143E+09 | 0.00 | 0.00 | 24680015.38 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.184093E+10 | 0.228985E+10 | 0.00 | 2611146.66 | 0.153572E+09 | 0.00 | 0.118539E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150833E+10 | 0.410756E+09 | 0.00 | 7454656.74 | 26203804.60 | 0.00 | 0.395925E+10 | 0.00 | 0.72 |
February | 0.998519E+09 | 0.616818E+09 | 0.00 | 4908585.64 | 23093128.75 | 0.00 | 0.221082E+10 | 0.00 | 0.70 |
March | 0.151872E+10 | 0.727394E+09 | 0.00 | 4920530.63 | 34406973.63 | 0.00 | 0.202414E+10 | 0.00 | 0.69 |
April | 0.709345E+09 | 0.107272E+10 | 0.00 | 2522941.25 | 73166378.55 | 0.00 | 0.553130E+09 | 0.00 | 0.60 |
May | 0.00 | 0.230903E+10 | 0.00 | 0.00 | 0.148329E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.253956E+10 | 0.00 | 0.00 | 0.117487E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
July | 0.00 | 0.300485E+10 | 0.00 | 0.00 | 0.107741E+09 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 288587.65 | 0.327275E+10 | 0.00 | 0.00 | 80470355.13 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.308322E+10 | 0.00 | 0.00 | 0.148727E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.226542E+09 | 0.252673E+10 | 0.00 | 2640179.41 | 49991062.38 | 0.00 | 0.704382E+09 | 0.00 | 0.60 |
November | 0.759911E+09 | 0.107279E+10 | 0.00 | 9045141.38 | 32080331.29 | 0.00 | 0.269276E+10 | 0.00 | 0.88 |
December | 0.152437E+10 | 0.856556E+09 | 0.00 | 8922187.86 | 34202952.68 | 0.00 | 0.351596E+10 | 0.00 | 0.81 |
Annual Sum or Average | 0.724602E+10 | 0.214932E+11 | 0.00 | 40414222.90 | 0.875899E+09 | 0.00 | 0.156604E+11 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.410756E+09 | 0.00 | 0.00 | 23093128.75 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.152437E+10 | 0.327275E+10 | 0.00 | 9045141.38 | 0.148727E+09 | 0.00 | 0.395925E+10 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.204205E+10 | 0.305935E+09 | 0.00 | 2743513.53 | 20526419.55 | 0.00 | 0.172678E+10 | 0.00 | 0.74 |
February | 0.821037E+09 | 0.448559E+09 | 0.00 | 3997483.47 | 11915943.75 | 0.00 | 0.172668E+10 | 0.00 | 0.84 |
March | 0.611419E+09 | 0.727267E+09 | 0.00 | 7433006.95 | 8908413.41 | 0.00 | 0.305493E+10 | 0.00 | 1.08 |
April | 0.314916E+09 | 0.141552E+10 | 0.00 | 6394783.06 | 8047185.10 | 0.00 | 0.120407E+10 | 0.00 | 1.12 |
May | 0.00 | 0.233965E+10 | 0.00 | 0.00 | 45888532.87 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.282997E+10 | 0.00 | 0.00 | 18768980.29 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.343157E+10 | 0.00 | 0.00 | 15023596.21 | 0.00 | 0.00 | 0.00 | 0.64 |
August | 263304.14 | 0.375552E+10 | 0.00 | 3687.35 | 12855103.25 | 0.00 | 16887.02 | 0.00 | 0.74 |
September | 0.00 | 0.266572E+10 | 0.00 | 0.00 | 82472083.13 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.125134E+09 | 0.200262E+10 | 0.00 | 2472073.19 | 29884724.12 | 0.00 | 0.700675E+09 | 0.00 | 0.74 |
November | 0.479915E+09 | 0.891947E+09 | 0.00 | 7062891.68 | 7214115.34 | 0.00 | 0.221680E+10 | 0.00 | 1.05 |
December | 0.680789E+09 | 0.792793E+09 | 0.00 | 7771953.42 | 10980109.92 | 0.00 | 0.351093E+10 | 0.00 | 1.01 |
Annual Sum or Average | 0.507553E+10 | 0.216071E+11 | 0.00 | 37879392.65 | 0.272485E+09 | 0.00 | 0.141409E+11 | 0.00 | 0.81 |
Minimum of Months | 0.00 | 0.305935E+09 | 0.00 | 0.00 | 7214115.34 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.204205E+10 | 0.375552E+10 | 0.00 | 7771953.42 | 82472083.13 | 0.00 | 0.351093E+10 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.273197E+11 | 0.117813E+10 | 0.00 | 85384.96 | 0.166480E+10 | 0.381176E+10 | 24080388.37 | 0.00 | 0.41 |
February | 0.160262E+11 | 0.189608E+10 | 0.00 | 425292.18 | 0.141867E+10 | 0.154751E+10 | 0.870391E+09 | 0.00 | 0.40 |
March | 0.211474E+11 | 0.348904E+10 | 0.00 | 1737341.60 | 0.170850E+10 | 0.142268E+10 | 0.978940E+09 | 0.00 | 0.44 |
April | 0.508898E+10 | 0.714165E+10 | 0.00 | 8283183.85 | 0.205478E+10 | 0.00 | 0.161825E+10 | 0.00 | 0.40 |
May | 0.00 | 0.223696E+11 | 0.00 | 0.00 | 0.157743E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.262058E+11 | 0.00 | 0.00 | 0.157570E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.302318E+11 | 0.00 | 0.00 | 0.163778E+10 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.289057E+11 | 0.00 | 0.00 | 0.163817E+10 | 0.00 | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.236539E+11 | 0.00 | 0.00 | 0.235413E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
October | 0.328760E+10 | 0.154884E+11 | 0.00 | 7267756.64 | 0.168243E+10 | 0.00 | 0.237137E+10 | 0.00 | 0.37 |
November | 0.145903E+11 | 0.470832E+10 | 0.00 | 4126245.48 | 0.174858E+10 | 3297880.43 | 0.179780E+10 | 0.00 | 0.43 |
December | 0.238511E+11 | 0.319653E+10 | 0.00 | 243029.47 | 0.226429E+10 | 0.200852E+10 | 0.131221E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.111311E+12 | 0.168465E+12 | 0.00 | 22168234.18 | 0.213253E+11 | 0.879377E+10 | 0.779205E+10 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.117813E+10 | 0.00 | 0.00 | 0.141867E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.273197E+11 | 0.302318E+11 | 0.00 | 8283183.85 | 0.235413E+10 | 0.381176E+10 | 0.237137E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.216344E+11 | 0.120239E+10 | 0.00 | 1168442.52 | 0.120281E+10 | 0.168914E+10 | 0.152227E+10 | 0.00 | 0.51 |
February | 0.117570E+11 | 0.219157E+10 | 0.00 | 4312903.02 | 0.838007E+09 | 0.564561E+09 | 0.249418E+10 | 0.00 | 0.52 |
March | 0.128279E+11 | 0.417209E+10 | 0.00 | 14221846.29 | 0.867429E+09 | 0.831111E+09 | 0.613349E+10 | 0.00 | 0.61 |
April | 0.272067E+10 | 0.770061E+10 | 0.00 | 17137020.32 | 0.124205E+10 | 0.00 | 0.446805E+10 | 0.00 | 0.61 |
May | 0.00 | 0.199739E+11 | 0.00 | 0.00 | 0.125385E+10 | 0.00 | 0.00 | 0.00 | 0.53 |
June | 0.00 | 0.225629E+11 | 0.00 | 0.00 | 0.123241E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.262671E+11 | 0.00 | 0.00 | 0.120138E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
August | 0.00 | 0.244587E+11 | 0.00 | 0.00 | 0.135145E+10 | 0.00 | 0.00 | 0.00 | 0.53 |
September | 0.00 | 0.197655E+11 | 0.00 | 0.00 | 0.205187E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.230267E+10 | 0.139058E+11 | 0.00 | 8079568.05 | 0.132145E+10 | 0.00 | 0.245130E+10 | 0.00 | 0.51 |
November | 0.861289E+10 | 0.441828E+10 | 0.00 | 12754426.96 | 0.119365E+10 | 2629589.52 | 0.499068E+10 | 0.00 | 0.56 |
December | 0.178177E+11 | 0.253161E+10 | 0.00 | 3071296.65 | 0.172794E+10 | 0.122978E+10 | 0.176087E+10 | 0.00 | 0.50 |
Annual Sum or Average | 0.776732E+11 | 0.149151E+12 | 0.00 | 60745503.81 | 0.154843E+11 | 0.431722E+10 | 0.238208E+11 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.120239E+10 | 0.00 | 0.00 | 0.838007E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.216344E+11 | 0.262671E+11 | 0.00 | 17137020.32 | 0.205187E+10 | 0.168914E+10 | 0.613349E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.142119E+11 | 0.413624E+10 | 0.00 | 63299212.41 | 0.533787E+09 | 0.515310E+09 | 0.327006E+11 | 0.00 | 0.67 |
February | 0.922416E+10 | 0.658872E+10 | 0.00 | 39106594.99 | 0.340215E+09 | 0.162414E+09 | 0.164314E+11 | 0.00 | 0.65 |
March | 0.147140E+11 | 0.660272E+10 | 0.00 | 33383341.56 | 0.741003E+09 | 0.286597E+09 | 0.132375E+11 | 0.00 | 0.60 |
April | 0.394757E+10 | 0.969995E+10 | 0.00 | 18372799.15 | 0.142729E+10 | 0.00 | 0.374516E+10 | 0.00 | 0.49 |
May | 0.00 | 0.228910E+11 | 0.00 | 0.00 | 0.156529E+10 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.249353E+11 | 0.00 | 0.00 | 0.161225E+10 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.298576E+11 | 0.00 | 0.00 | 0.162916E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.326281E+11 | 0.00 | 0.00 | 0.146677E+10 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.308230E+11 | 0.00 | 0.00 | 0.196112E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 0.214283E+10 | 0.261562E+11 | 0.00 | 22247080.46 | 0.810275E+09 | 0.00 | 0.557200E+10 | 0.00 | 0.61 |
November | 0.544562E+10 | 0.108347E+11 | 0.00 | 78778565.83 | 0.558205E+09 | 0.00 | 0.226075E+11 | 0.00 | 0.82 |
December | 0.131866E+11 | 0.854337E+10 | 0.00 | 70406082.69 | 0.722859E+09 | 0.712804E+09 | 0.250054E+11 | 0.00 | 0.71 |
Annual Sum or Average | 0.628727E+11 | 0.213697E+12 | 0.00 | 0.325594E+09 | 0.133682E+11 | 0.167712E+10 | 0.119300E+12 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.413624E+10 | 0.00 | 0.00 | 0.340215E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.147140E+11 | 0.326281E+11 | 0.00 | 78778565.83 | 0.196112E+10 | 0.712804E+09 | 0.327006E+11 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.214391E+11 | 0.212982E+10 | 0.00 | 6539490.18 | 0.689053E+09 | 0.643917E+09 | 0.457913E+10 | 0.00 | 0.56 |
February | 0.119990E+11 | 0.300697E+10 | 0.00 | 7495234.17 | 0.612124E+09 | 0.334204E+09 | 0.367915E+10 | 0.00 | 0.58 |
March | 0.151332E+11 | 0.415719E+10 | 0.00 | 16167001.05 | 0.663307E+09 | 3514174.90 | 0.644152E+10 | 0.00 | 0.66 |
April | 0.285299E+10 | 0.887854E+10 | 0.00 | 19487455.90 | 0.851494E+09 | 0.00 | 0.365877E+10 | 0.00 | 0.65 |
May | 0.00 | 0.198234E+11 | 0.00 | 0.00 | 0.869130E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 0.00 | 0.227928E+11 | 0.00 | 0.00 | 0.798535E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.262800E+11 | 0.00 | 0.00 | 0.732143E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
August | 0.00 | 0.270945E+11 | 0.00 | 0.00 | 0.711414E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.218245E+11 | 0.00 | 0.00 | 0.139611E+10 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.214256E+10 | 0.152342E+11 | 0.00 | 9938190.91 | 0.865676E+09 | 0.00 | 0.298250E+10 | 0.00 | 0.56 |
November | 0.101277E+11 | 0.537926E+10 | 0.00 | 14351815.19 | 0.749007E+09 | 0.00 | 0.475074E+10 | 0.00 | 0.63 |
December | 0.187818E+11 | 0.422177E+10 | 0.00 | 7240430.00 | 0.963979E+09 | 0.518225E+09 | 0.318432E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.824764E+11 | 0.160823E+12 | 0.00 | 81219617.41 | 0.990197E+10 | 0.149986E+10 | 0.292761E+11 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.212982E+10 | 0.00 | 0.00 | 0.612124E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.214391E+11 | 0.270945E+11 | 0.00 | 19487455.90 | 0.139611E+10 | 0.643917E+09 | 0.644152E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.173248E+10 | 0.126092E+09 | 44218.63 | 5115.83 | 0.197271E+09 | 0.108314E+10 | 2402251.46 | 805.46 | 0.41 |
February | 0.110905E+10 | 0.197348E+09 | 0.00 | 1966.15 | 0.189102E+09 | 0.525241E+09 | 29759229.45 | 0.00 | 0.40 |
March | 0.172070E+10 | 0.375622E+09 | 0.00 | 136212.13 | 0.202497E+09 | 0.380318E+09 | 55729567.55 | 0.00 | 0.44 |
April | 0.507250E+09 | 0.705860E+09 | 0.00 | 728922.21 | 0.243523E+09 | 0.00 | 0.156685E+09 | 0.00 | 0.39 |
May | 0.00 | 0.221722E+10 | 0.00 | 0.00 | 0.143108E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.260664E+10 | 0.00 | 0.00 | 0.132856E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.303335E+10 | 0.00 | 0.00 | 0.142147E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.286650E+10 | 0.00 | 0.00 | 0.172879E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.231931E+10 | 0.00 | 0.00 | 0.290631E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
October | 0.323443E+09 | 0.149313E+10 | 0.00 | 619510.19 | 0.191110E+09 | 0.00 | 0.185909E+09 | 0.00 | 0.37 |
November | 0.129336E+10 | 0.435089E+09 | 2202486.45 | 252348.31 | 0.232182E+09 | 77619294.43 | 89911648.44 | 7348.84 | 0.43 |
December | 0.152943E+10 | 0.290024E+09 | 1644674.45 | 168.57 | 0.279565E+09 | 0.755893E+09 | 4048418.54 | 18289.18 | 0.40 |
Annual Sum or Average | 0.821570E+10 | 0.166662E+11 | 3891379.54 | 1744243.38 | 0.241687E+10 | 0.282221E+10 | 0.524444E+09 | 26443.47 | 0.40 |
Minimum of Months | 0.00 | 0.126092E+09 | 0.00 | 0.00 | 0.132856E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.173248E+10 | 0.303335E+10 | 2202486.45 | 728922.21 | 0.290631E+09 | 0.108314E+10 | 0.185909E+09 | 18289.18 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.180809E+10 | 0.142997E+09 | 0.00 | 12244.35 | 0.130339E+09 | 0.418263E+09 | 3043982.86 | 0.00 | 0.51 |
February | 0.103706E+10 | 0.252980E+09 | 0.00 | 221737.36 | 98697542.03 | 0.168393E+09 | 0.110958E+09 | 0.00 | 0.51 |
March | 0.106576E+10 | 0.466136E+09 | 0.00 | 1003792.18 | 98403245.98 | 0.218547E+09 | 0.473024E+09 | 0.00 | 0.60 |
April | 0.247681E+09 | 0.790090E+09 | 0.00 | 1622821.47 | 0.141922E+09 | 0.00 | 0.430717E+09 | 0.00 | 0.60 |
May | 0.00 | 0.198498E+10 | 0.00 | 0.00 | 0.104238E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
June | 0.00 | 0.226788E+10 | 0.00 | 0.00 | 86609654.69 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.264361E+10 | 0.00 | 0.00 | 0.106103E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
August | 0.00 | 0.245565E+10 | 0.00 | 0.00 | 0.128888E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
September | 0.00 | 0.198984E+10 | 0.00 | 0.00 | 0.223884E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.203716E+09 | 0.137435E+10 | 0.00 | 742118.80 | 0.139289E+09 | 397305.23 | 0.218223E+09 | 0.00 | 0.51 |
November | 0.824461E+09 | 0.443899E+09 | 206966.27 | 688563.67 | 0.141444E+09 | 23051105.76 | 0.323237E+09 | 35.35 | 0.54 |
December | 0.138333E+10 | 0.249148E+09 | 482205.77 | 94768.14 | 0.201887E+09 | 0.393702E+09 | 37553115.77 | 3453.83 | 0.49 |
Annual Sum or Average | 0.657010E+10 | 0.150616E+11 | 689172.05 | 4386045.97 | 0.160170E+10 | 0.122235E+10 | 0.159676E+10 | 3489.18 | 0.53 |
Minimum of Months | 0.00 | 0.142997E+09 | 0.00 | 0.00 | 86609654.69 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.180809E+10 | 0.264361E+10 | 482205.77 | 1622821.47 | 0.223884E+09 | 0.418263E+09 | 0.473024E+09 | 3453.83 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.123100E+10 | 0.476727E+09 | 0.00 | 4237224.65 | 72707902.70 | 0.330721E+09 | 0.212106E+10 | 0.00 | 0.58 |
February | 0.802037E+09 | 0.726634E+09 | 0.00 | 2793453.53 | 63536529.41 | 0.152266E+09 | 0.115747E+10 | 0.00 | 0.59 |
March | 0.128739E+10 | 0.720288E+09 | 0.00 | 2668856.68 | 99051704.90 | 0.248279E+09 | 0.101701E+10 | 0.00 | 0.58 |
April | 0.383714E+09 | 0.951338E+09 | 0.00 | 1757309.96 | 0.192101E+09 | 0.00 | 0.386338E+09 | 0.00 | 0.48 |
May | 0.00 | 0.227037E+10 | 0.00 | 0.00 | 0.137526E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.246503E+10 | 0.00 | 0.00 | 0.157326E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.297866E+10 | 0.00 | 0.00 | 0.156411E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.324313E+10 | 0.00 | 0.00 | 0.123962E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.308236E+10 | 0.00 | 0.00 | 0.184539E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 0.203597E+09 | 0.253889E+10 | 0.00 | 1929110.35 | 74193255.67 | 0.00 | 0.492810E+09 | 0.00 | 0.59 |
November | 0.570462E+09 | 0.107023E+10 | 0.00 | 6016819.66 | 85134489.07 | 6102495.96 | 0.177998E+10 | 0.00 | 0.75 |
December | 0.118238E+10 | 0.822027E+09 | 0.00 | 5395525.80 | 0.117235E+09 | 0.245163E+09 | 0.164902E+10 | 0.00 | 0.64 |
Annual Sum or Average | 0.566059E+10 | 0.213457E+11 | 0.00 | 24798300.62 | 0.146373E+10 | 0.982531E+09 | 0.860368E+10 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 0.476727E+09 | 0.00 | 0.00 | 63536529.41 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.128739E+10 | 0.324313E+10 | 0.00 | 6016819.66 | 0.192101E+09 | 0.330721E+09 | 0.212106E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.183800E+10 | 0.210082E+09 | 0.00 | 323284.03 | 0.124967E+09 | 0.445075E+09 | 0.222726E+09 | 0.00 | 0.58 |
February | 0.109205E+10 | 0.319732E+09 | 0.00 | 486122.51 | 0.109350E+09 | 0.178818E+09 | 0.227510E+09 | 0.00 | 0.59 |
March | 0.138000E+10 | 0.427968E+09 | 0.00 | 1383965.05 | 0.118857E+09 | 0.162578E+09 | 0.531856E+09 | 0.00 | 0.68 |
April | 0.334374E+09 | 0.885134E+09 | 0.00 | 1700616.25 | 0.124714E+09 | 0.00 | 0.354814E+09 | 0.00 | 0.65 |
May | 0.00 | 0.193660E+10 | 0.00 | 0.00 | 78291903.79 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 0.00 | 0.221779E+10 | 0.00 | 0.00 | 66385371.17 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.256682E+10 | 0.00 | 0.00 | 81421222.38 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 0.00 | 0.265381E+10 | 0.00 | 0.00 | 73212741.46 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.215201E+10 | 0.00 | 0.00 | 0.178037E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.247039E+09 | 0.147477E+10 | 0.00 | 799060.23 | 99125149.14 | 0.00 | 0.240418E+09 | 0.00 | 0.56 |
November | 0.993879E+09 | 0.489716E+09 | 0.00 | 1068149.49 | 0.158707E+09 | 12866286.42 | 0.370034E+09 | 0.00 | 0.64 |
December | 0.158860E+10 | 0.391388E+09 | 775783.56 | 453780.89 | 0.166073E+09 | 0.272688E+09 | 0.197817E+09 | 637.27 | 0.58 |
Annual Sum or Average | 0.747395E+10 | 0.157258E+11 | 775783.56 | 6214978.44 | 0.137914E+10 | 0.107202E+10 | 0.214517E+10 | 637.27 | 0.57 |
Minimum of Months | 0.00 | 0.210082E+09 | 0.00 | 0.00 | 66385371.17 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.183800E+10 | 0.265381E+10 | 775783.56 | 1700616.25 | 0.178037E+09 | 0.445075E+09 | 0.531856E+09 | 637.27 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 31761234.67 | 0.00 | 2499321.68 | 0.00 | 0.00 | 0.325698E+09 | 0.00 | 0.28 |
February | 0.00 | 50573442.05 | 0.00 | 4289320.22 | 0.00 | 0.00 | 0.174383E+09 | 0.00 | 0.29 |
March | 0.00 | 86698685.99 | 0.00 | 8563519.47 | 0.00 | 0.00 | 0.218022E+09 | 0.00 | 0.31 |
April | 0.00 | 0.167192E+09 | 0.00 | 4765828.86 | 0.00 | 0.00 | 48903953.93 | 0.00 | 0.29 |
May | 0.00 | 0.425218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.526346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.610408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.625334E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.430119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.353820E+09 | 0.00 | 1511633.75 | 0.00 | 0.00 | 44334330.17 | 0.00 | 0.28 |
November | 0.00 | 0.127563E+09 | 0.00 | 6718114.40 | 0.00 | 0.00 | 0.122729E+09 | 0.00 | 0.28 |
December | 0.00 | 94096557.67 | 0.00 | 10973848.77 | 0.00 | 0.00 | 0.239241E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.352913E+10 | 0.00 | 39321587.15 | 0.00 | 0.00 | 0.117331E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 31761234.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.625334E+09 | 0.00 | 10973848.77 | 0.00 | 0.00 | 0.325698E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.293209E+09 | 0.00 | 16089098.09 | 0.00 | 0.00 | 0.327550E+10 | 0.00 | 0.28 |
February | 0.00 | 0.496334E+09 | 0.00 | 36178164.97 | 0.00 | 0.00 | 0.175300E+10 | 0.00 | 0.29 |
March | 0.00 | 0.863791E+09 | 0.00 | 76536556.06 | 0.00 | 0.00 | 0.218594E+10 | 0.00 | 0.31 |
April | 0.00 | 0.167345E+10 | 0.00 | 44782932.01 | 0.00 | 0.00 | 0.489800E+09 | 0.00 | 0.29 |
May | 0.00 | 0.420335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.524472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.609517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.624778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.423333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.352067E+10 | 0.00 | 13667499.47 | 0.00 | 0.00 | 0.443812E+09 | 0.00 | 0.28 |
November | 0.00 | 0.127208E+10 | 0.00 | 60799187.63 | 0.00 | 0.00 | 0.123103E+10 | 0.00 | 0.28 |
December | 0.00 | 0.940344E+09 | 0.00 | 98430274.05 | 0.00 | 0.00 | 0.239833E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.350842E+11 | 0.00 | 0.346484E+09 | 0.00 | 0.00 | 0.117774E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.293209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.624778E+10 | 0.00 | 98430274.05 | 0.00 | 0.00 | 0.327550E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 70776027.57 | 28866282.46 | 0.00 | 925577.93 | 0.00 | 0.00 | 0.257849E+09 | 0.00 | 0.28 |
February | 0.00 | 49275002.47 | 0.00 | 3203744.79 | 0.00 | 0.00 | 0.176424E+09 | 0.00 | 0.29 |
March | 0.00 | 86183203.25 | 0.00 | 7197961.25 | 0.00 | 0.00 | 0.219424E+09 | 0.00 | 0.31 |
April | 0.00 | 0.167024E+09 | 0.00 | 4400143.59 | 0.00 | 0.00 | 49197104.84 | 0.00 | 0.29 |
May | 0.00 | 0.422449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.525103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.609499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.625028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.424987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.352139E+09 | 0.00 | 1299728.08 | 0.00 | 0.00 | 44543205.65 | 0.00 | 0.28 |
November | 0.00 | 0.126891E+09 | 0.00 | 5742708.57 | 0.00 | 0.00 | 0.123814E+09 | 0.00 | 0.28 |
December | 0.00 | 93759013.06 | 0.00 | 9218107.06 | 0.00 | 0.00 | 0.240830E+09 | 0.00 | 0.28 |
Annual Sum or Average | 70776027.57 | 0.351120E+10 | 0.00 | 31987971.27 | 0.00 | 0.00 | 0.111208E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 28866282.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 70776027.57 | 0.625028E+09 | 0.00 | 9218107.06 | 0.00 | 0.00 | 0.257849E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:07:54
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.425768E+12 | 0.217507E+10 | 0.00 | 0.140861E+13 | 0.530332E+12 |
February | 0.454591E+12 | 0.181921E+10 | 0.00 | 0.102811E+13 | 0.769774E+12 |
March | 0.519601E+12 | 0.153588E+10 | 0.00 | 0.110399E+13 | 0.984890E+12 |
April | 0.576130E+12 | -312818542.7 | 0.00 | 0.367431E+12 | 0.151169E+13 |
May | 0.573463E+12 | -0.424138E+10 | 0.00 | -0.677801E+12 | 0.202148E+13 |
June | 0.569999E+12 | -0.318563E+10 | 0.00 | -0.782208E+12 | 0.221727E+13 |
July | 0.589439E+12 | -0.535040E+10 | 0.00 | -0.876941E+12 | 0.243811E+13 |
August | 0.543727E+12 | -0.525789E+10 | 0.00 | -0.877357E+12 | 0.260180E+13 |
September | 0.471943E+12 | -0.534730E+10 | 0.00 | -0.686919E+12 | 0.201377E+13 |
October | 0.475717E+12 | -0.366496E+10 | 0.00 | -0.191888E+12 | 0.191713E+13 |
November | 0.369766E+12 | 0.665741E+09 | 0.00 | 0.896860E+12 | 0.123178E+13 |
December | 0.382204E+12 | 0.171248E+10 | 0.00 | 0.128262E+13 | 0.971709E+12 |
Annual Sum or Average | 0.595235E+13 | -0.194520E+11 | 0.00 | 0.199451E+13 | 0.192097E+14 |
Minimum of Months | 0.369766E+12 | -0.535040E+10 | 0.00 | -0.877357E+12 | 0.530332E+12 |
Maximum of Months | 0.589439E+12 | 0.217507E+10 | 0.00 | 0.140861E+13 | 0.260180E+13 |