Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:07
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 09:07:53
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 32816.90 | 708.48 | 708.48 |
Net Site Energy | 32816.90 | 708.48 | 708.48 |
Total Source Energy | 87375.17 | 1886.32 | 1886.32 |
Net Source Energy | 87375.17 | 1886.32 | 1886.32 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 56.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2074.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7196.12 | 0.00 | 0.00 |
Interior Lighting | 2025.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 325.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3258.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1390.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 755.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 461.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12276.29 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 597.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 24966.65 | 654.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7196.12 | 0.00 | 14556.46 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 56.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2074.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7196.12 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2025.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 325.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ComputerHVAC | 1349.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 1390.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 755.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 461.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12276.29 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 597.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 56.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2074.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7196.12 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2025.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 325.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 3258.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 1390.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 755.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 461.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12276.29 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 597.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 101.06 | 14.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.36 | 0.00 | 0.31 |
Other | 387.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 539.00 | 14.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.36 | 0.00 | 0.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 101.06 | 14.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.36 | 0.00 | 0.31 |
Other | 387.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 539.00 | 14.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.36 | 0.00 | 0.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 24966.649 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 24966.649 | 100.00 |
Total On-Site and Utility Electric Sources | 24966.649 | 100.00 |
Total Electricity End Uses | 24966.649 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 14556.46 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 14556.46 | 100.00 |
Total Water End Uses | 14556.46 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 560.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionDistrictHeatingCoolingMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:07 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.8895 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.8895 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 5.9168 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 5.9168 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.8895 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8895 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.8895 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8895 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.8895 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.9168 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.9168 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.8190 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
Time of Peak | 11-AUG-15:20 | 06-DEC-07:10 | - | - | - | - | - | - | - | - | 28-AUG-13:00 | 01-FEB-00:40 | 27-JUN-11:00 |
Heating | 0.00 | 408251.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 | 0.00 |
Cooling | 263987.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370732.56 | 0.00 | 0.00 |
Interior Lighting | 171235.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 151141.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 171564.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 51545.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 46841.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 28487.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1634688.54 | 436739.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370732.56 | 12.65 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 | 0.00 |
Boiler | 0.00 | 408251.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 263987.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370732.56 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 171235.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3372.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ComputerHVAC | 68333.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 171564.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 51545.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 46841.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 28487.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 61.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6568.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7596.71 | 0.00 |
Interior Lighting | 6414.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1030.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10318.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4402.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2392.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1461.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 647.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 79069.38 | 709.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7596.71 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 141.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.00 | 0.00 |
Interior Lighting | 138.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 22.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 222.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 95.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 51.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 31.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1707.01 | 15.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 141.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.00 | 0.00 |
Interior Lighting | 138.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 22.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 222.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 95.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 51.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 31.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1707.01 | 15.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.48 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.506689 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.82 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.491290 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.90 | 0.322447 | 0.328000 | 1.93 | 0.859858 | 0.500000 | 0.001182 | 0.000155 | 1.93 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 55.45 | 0.343018 | 0.341000 | 18.91 | 0.914716 | 0.500000 | 0.001111 | 0.003219 | 18.91 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.57 | 0.341488 | 0.350000 | 1.95 | 0.910635 | 0.500000 | 0.001116 | 0.000614 | 2.30 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.07 | 0.223703 | 0.227000 | 0.242341 | 0.596540 | 0.500000 | 0.001703 | 0.000054 | 0.242341 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.00 | 0.153158 | 0.200000 | 0.200975 | 0.408423 | 0.500000 | 0.002488 | 0.000043 | 0.200975 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.18 | 0.201887 | 0.205000 | 0.242509 | 0.538364 | 0.500000 | 0.001887 | 0.000075 | 0.279198 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.32 | 0.116732 | 0.200000 | 0.263689 | 0.311287 | 0.500000 | 0.003264 | 0.000035 | 0.263689 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 10.04 | 0.237940 | 0.237000 | 2.38 | 0.634506 | 0.500000 | 0.001601 | 0.001379 | 5.18 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 10.39 | 0.148087 | 0.200000 | 2.08 | 0.394898 | 0.500000 | 0.002573 | 0.000926 | 3.48 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 11.15 | 0.214180 | 0.213000 | 2.38 | 0.571147 | 0.500000 | 0.001779 | 0.001391 | 5.22 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 11.18 | 0.137624 | 0.200000 | 2.24 | 0.366997 | 0.500000 | 0.002768 | 0.000831 | 3.12 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.17 | 0.204387 | 0.210000 | 0.245380 | 0.545031 | 0.500000 | 0.001864 | 0.000184 | 0.691510 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.08 | 0.143126 | 0.200000 | 0.215063 | 0.381669 | 0.500000 | 0.002662 | 0.000122 | 0.459451 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.27 | 0.188072 | 0.200000 | 0.253973 | 0.501525 | 0.500000 | 0.002026 | 0.000185 | 0.696486 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.23 | 0.125044 | 0.200000 | 0.246162 | 0.333450 | 0.500000 | 0.003047 | 0.000115 | 0.433173 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 17685.80 | 0.000155 | 356.53 |
CORE_MID VAV BOX REHEAT COIL | 367939.72 | 0.003219 | 8355.15 |
CORE_TOP VAV BOX REHEAT COIL | 70137.10 | 0.000614 | 1852.23 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6193.01 | 0.000054 | 152.27 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4873.79 | 0.000043 | 117.74 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8523.97 | 0.000075 | 225.12 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3987.72 | 0.000035 | 85.94 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 157657.36 | 0.001379 | 4159.32 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 105871.06 | 0.000926 | 2792.96 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 159023.61 | 0.001391 | 4195.32 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 94987.90 | 0.000831 | 2506.17 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21049.62 | 0.000184 | 555.16 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13984.86 | 0.000122 | 368.83 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21200.76 | 0.000185 | 559.15 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13186.45 | 0.000115 | 347.79 |
VAV_BOT WITH REHEAT HEATING COIL | 36113.35 | 0.000316 | 611.42 |
VAV_MID WITH REHEAT HEATING COIL | 329724.29 | 0.002885 | 5590.72 |
VAV_TOP WITH REHEAT HEATING COIL | 30222.77 | 0.000264 | 518.87 |
CAV_BAS HEATING COIL | 240018.69 | 0.002100 | 5397.42 |
Design Size Maximum Heating Air Flow Rate [m3/s] | Design Size Maximum Cooling Air Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT | 0.338402 | 23.38 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.24 | 2.88 | 10.47 | 2.88 | 9.65 | 9.65 | 0.300000 | 0.298751 | 9.65 |
VAV_MID WITH REHEAT | 49.11 | 27.98 | 98.21 | 27.98 | 90.01 | 90.01 | 0.300000 | 0.310836 | 90.01 |
VAV_TOP WITH REHEAT | 5.16 | 2.91 | 10.31 | 4.58 | 9.97 | 9.97 | 0.300000 | 0.459301 | 9.97 |
CAV_BAS | 5.48 | 5.48 | 5.48 | 5.48 | 5.48 | 5.48 | 1.00 | 1.00 | 5.48 |
AIRLOOP DATACENTER BOT | 0.506689 | 0.506689 | 0.506689 | 0.506689 | 0.506689 | 0.506689 | 1.00 | 1.00 | 0.506689 |
AIRLOOP DATACENTER MID | 4.82 | 4.82 | 4.82 | 4.82 | 4.82 | 4.82 | 1.00 | 1.00 | 4.82 |
AIRLOOP DATACENTER TOP | 0.491290 | 0.491290 | 0.491290 | 0.491290 | 0.491290 | 0.491290 | 1.00 | 1.00 | 0.491290 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.65 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 90.01 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.97 | |
CAV_BAS_OA_CONTROLLER | 5.48 | |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.506689 | 0.015633 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.82 | 0.156328 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.491290 | 0.015633 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 28.61 | 6.67 | 10.86 | 0.007977 | 0.007977 | 190969.86 | 0.008124 | 9.65 |
VAV_MID WITH REHEAT COOLING COIL | 29.14 | 6.67 | 10.86 | 0.007896 | 0.007896 | 1834111.50 | 0.078027 | 90.01 |
VAV_TOP WITH REHEAT COOLING COIL | 28.30 | 6.67 | 10.86 | 0.008008 | 0.008008 | 193820.60 | 0.008246 | 9.97 |
CAV_BAS COOLING COIL | 28.01 | 6.67 | 11.28 | 0.008207 | 0.008207 | 102213.95 | 0.004348 | 5.48 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.65 |
VAV_MID WITH REHEAT FAN | 90.01 |
VAV_TOP WITH REHEAT FAN | 9.97 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.008124 | 0.000059 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000316 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.078027 | 0.000006 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.002885 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.008246 | 0.000058 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000264 | |
CAV_BAS_COOLC_CONTROLLER | 0.004348 | 0.000110 |
CAV_BAS_HEATC_CONTROLLER | 0.002100 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.48 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.506689 | 9327.57 | 6168.56 | 0.000228 |
AIRLOOP DATACENTER MID COOLING COIL | 4.82 | 88800.76 | 58702.82 | 0.002175 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.491290 | 9047.39 | 5982.13 | 0.000222 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.506689 | 0.506689 | 0.506689 | 0.506689 | 9327.57 | 9327.57 | 678.32 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.82 | 4.82 | 4.82 | 4.82 | 88800.76 | 88800.76 | 6783.22 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.491290 | 0.491290 | 0.491290 | 0.491290 | 9047.39 | 9047.39 | 678.32 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.506689 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.82 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.491290 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT HEATING COIL | 0.506689 | 9327.57 | 0.000228 |
AIRLOOP DATACENTER MID HEATING COIL | 4.82 | 88800.76 | 0.002175 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.491290 | 9047.39 | 0.000222 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 678.32 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6783.22 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 678.32 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.098746 | 20146.35 | |
HEATSYS1 PUMP | 0.014893 | 4440.76 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.098746 | 11.85 |
HEATSYS1 | 0.014893 | 1.79 |
COOLSYS1_SUPPLY | 0.098746 | 11.85 |
SINGLE WATER PLANT LOOP | 0.002625 | 0.314967 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.098746 | 0.098746 | 414484.98 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1702381.83 | 1702381.83 | 0.014893 |
CENTRAL BOILER | 108116.23 | 108116.23 | 0.002625 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.098746 | 13948.00 |
PLANT CIRC PUMP | 0.002625 | 662.81 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.098746 | 0.049940 | 1176765.51 | 1182347.27 | 0.058510 |
COOLSYS1 CHILLER2 | 0.098746 | 0.049940 | 1176765.51 | 1182347.27 | 0.058510 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.002625 | 35644.39 | 22226.57 | 17822.20 | 1996.20 | 5900.63 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.117020 | 14.04 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.117020 | 34894.92 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 49.81 | 1403341.78 | 9.96 | 175417.72 |
TOWERWATERSYS COOLTOWER 2 | 49.81 | 1403341.78 | 9.96 | 175417.72 |
Design Water Flow Rate [m3/s] Equipment # 45 | |
WSHPPLANT OPERATION SCHEME | 0.060773 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.889 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.731 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.889 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.313 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16369.361 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16369.361 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4615.459 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4615.459 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.743 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.656 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 2.135 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4064 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4365 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3009 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.76055735E-15 | 0.55973061E-16 | -0.11090261E-09 | -0.43371185E-17 |
51 | 8 | 0.16390423E-07 | 0.22068143E-12 | 0.31740643E-03 | -0.18636477E-09 |
52 | 7 | -0.10429999E-01 | 0.12271718E-07 | -0.20474149E-01 | 0.11859286E-03 |
53 | 6 | 0.35611320 | 0.43955117E-05 | 0.42991281 | -0.41673803E-02 |
54 | 5 | -4.7098961 | 0.16827687E-03 | -4.1162358 | 0.57223947E-01 |
55 | 4 | 30.875684 | 0.14076848E-02 | 20.167480 | -0.39388153 |
56 | 3 | -106.69740 | 0.31291265E-02 | -53.106522 | 1.4497707 |
57 | 2 | 192.63914 | 0.17911574E-02 | 75.570394 | -2.8293896 |
58 | 1 | -169.50392 | 0.19431750E-03 | -54.592911 | 2.7164834 |
59 | 0 | 57.057407 | 0.11257899E-05 | 15.674734 | |
60 | 9 | 0.11474244E-14 | 0.54197419E-16 | -0.11508650E-09 | -0.49945851E-17 |
61 | 8 | 0.16984416E-07 | 0.21156325E-12 | 0.32425024E-03 | -0.19311866E-09 |
62 | 7 | -0.10636353E-01 | 0.11664670E-07 | -0.20772028E-01 | 0.12093918E-03 |
63 | 6 | 0.36172330 | 0.41637772E-05 | 0.43474562 | -0.42335086E-02 |
64 | 5 | -4.7646824 | 0.15893927E-03 | -4.1535939 | 0.57903236E-01 |
65 | 4 | 31.118254 | 0.13261305E-02 | 20.314042 | -0.39710182 |
66 | 3 | -107.21418 | 0.29411649E-02 | -53.396504 | 1.4572354 |
67 | 2 | 193.15212 | 0.16802168E-02 | 75.835339 | -2.8375342 |
68 | 1 | -169.69371 | 0.18194848E-03 | -54.668081 | 2.7198097 |
69 | 0 | 57.057407 | 0.10520719E-05 | 15.660794 | |
70 | 9 | 0.66246833E-15 | 0.57738042E-16 | -0.92036509E-10 | -0.27018983E-17 |
71 | 8 | 0.13701644E-07 | 0.25726543E-12 | 0.28527343E-03 | -0.15579243E-09 |
72 | 7 | -0.94571194E-02 | 0.14940887E-07 | -0.19068097E-01 | 0.10753086E-03 |
73 | 6 | 0.32965778 | 0.54453531E-05 | 0.40701455 | -0.38555430E-02 |
74 | 5 | -4.4514676 | 0.21157254E-03 | -3.9387765 | 0.54019785E-01 |
75 | 4 | 29.731016 | 0.17930056E-02 | 19.470280 | -0.37868589 |
76 | 3 | -104.25747 | 0.40308508E-02 | -51.726693 | 1.4145289 |
77 | 2 | 190.21562 | 0.23301583E-02 | 74.311741 | -2.7909129 |
78 | 1 | -168.60668 | 0.25508611E-03 | -54.239505 | 2.7007581 |
79 | 0 | 57.057407 | 0.14924561E-05 | 15.743350 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.4547_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.584 | 2.584 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.584 | 2.584 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.4547_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.584 | 2.584 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.584 | 2.584 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.60743E-002 | 0.16139 | 0.61671 | 0.61671 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12075 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.60743E-002 | 0.16139 | 0.61671 | 0.61671 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12075 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.60743E-002 | 0.16139 | 0.61671 | 0.61671 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12075 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.60743E-002 | 0.16139 | 0.61671 | 0.61671 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12075 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2.857E-002 | 9.114E-005 | 1.371E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.384E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2.857E-002 | 9.114E-005 | 1.371E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.384E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2.857E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2.857E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2.857E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2.857E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 4.231E-002 | 1.187E-005 | 1.424E-004 | 3.506E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 4.231E-002 | 1.187E-005 | 1.424E-004 | 3.506E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 4.231E-002 | 1.187E-005 | 1.096E-005 | 3.506E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9488E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9501E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1771E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1781E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2307E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2315E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2447E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2452E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9766E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0562E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2001E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2684E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2501E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3069E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2574E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2891E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1365E-002 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7865E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.1759E-002 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1680E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2903E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4638E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6042E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.1095E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9803E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0747E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2041E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2882E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2536E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3204E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2577E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2900E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9488E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9501E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1770E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1781E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2307E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2316E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2447E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2451E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7771E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9341E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6480E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8165E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.5118E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5858E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1302E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1521E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2325E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.6117E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0587E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4677E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3390E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.3872E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6787E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.9865E-003 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7343E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7902E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.5934E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6342E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.4886E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5052E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1303E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1525E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2584E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2597E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0739E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0748E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.5102E-004 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.5174E-004 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2447E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2452E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2856E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3540E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0960E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1503E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.6907E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0084E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2577E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2900E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9879E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1415E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5426E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.6788E-003 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5419E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.1125E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6042E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.1067E-003 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2843E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3524E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0944E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1472E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.6633E-004 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0001E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2574E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2891E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2584E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2595E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0738E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0747E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.5095E-004 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.5157E-004 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2447E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2451E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.4901E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5478E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.2925E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3342E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.2780E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2935E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1303E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1525E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7582E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4263E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.4801E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2418E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9038E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2152E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6787E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 9.9865E-003 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.5263E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6552E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3390E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4724E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3000E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3678E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1302E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1521E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.6411E-002 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.9695E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.3533E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.4310E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.5374E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.4130E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.0133E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.4574E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.7146E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2272E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.5255E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.0581E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.7894E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9427E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.0820E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4729E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3850E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6755E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8993E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3274E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8936E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.0330E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0133E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4571E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2000E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9843E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.8969E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7611E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3213E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7245E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.0820E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.4729E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.6364E-002 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.9771E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.3489E-002 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.4402E-002 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.5396E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.4201E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.0168E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.4602E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.7130E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2292E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.5248E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.0602E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.7908E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9461E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.0854E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4757E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3821E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6761E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8973E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3280E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8946E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.0345E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0168E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4599E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.1981E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9859E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.8958E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7626E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3226E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7273E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.0854E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4757E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 69069.56672 | 69069.56672 | 5.47739 | 5.47739 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2779.42662 | 149.60210 | 1.20019 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20019 | 00:10:00 | 0.50000 | 4.31558E-003 | 2779.42662 | 149.60210 | 1.20019 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 74382.11190 | 74382.11190 | 5.89878 | 5.89878 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 0.50000 | 4.31558E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 699396.69482 | 699396.69482 | 55.45019 | 55.45019 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 195098.93895 | 195098.93895 | 9.04195 | 10.77825 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 70250.60347 | 70250.60347 | 5.56987 | 5.56987 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 49135.71693 | 49135.71693 | 2.29752 | 2.29752 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 13339.71397 | 13339.71397 | 1.06758 | 1.06758 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80000 | 5.63111E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 3978.80248 | 3978.80248 | 0.18534 | 0.18534 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 12556.25733 | 12556.25733 | 1.00487 | 1.00487 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 34.99233 | 5.62211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 3037.39723 | 3037.39723 | 0.14174 | 0.14174 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 14781.56276 | 14781.56276 | 1.18297 | 1.18297 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 40.68917 | 5.63093E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 5972.51095 | 5972.51095 | 0.27920 | 0.27920 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 16474.46177 | 16474.46177 | 1.31844 | 1.31844 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 1579.17040 | 1579.17040 | 7.34517E-002 | 8.72129E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 125416.50340 | 125416.50340 | 10.03703 | 10.03703 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 110353.30860 | 110353.30860 | 5.17586 | 5.17586 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 129864.28875 | 129864.28875 | 10.39291 | 10.39291 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 35.36917 | 5.62269E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 74101.47431 | 74101.47431 | 3.47610 | 3.47610 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 139332.36279 | 139332.36279 | 11.15069 | 11.15069 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 40.80000 | 5.63111E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 111308.38606 | 111308.38606 | 5.22084 | 5.22084 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 139737.18262 | 139737.18262 | 11.18303 | 11.18303 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 38.71633 | 5.62786E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 66493.19401 | 66493.19401 | 3.11790 | 3.11790 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 14600.63449 | 14600.63449 | 1.16848 | 1.16848 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 40.40100 | 5.63048E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 14729.39585 | 14729.39585 | 0.69151 | 0.69151 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 13436.60614 | 13436.60614 | 1.07531 | 1.07531 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 36.07850 | 5.62379E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 9785.59137 | 9785.59137 | 0.45945 | 0.45945 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 15867.56535 | 15867.56535 | 1.26987 | 1.26987 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 40.80000 | 5.63111E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 14835.04841 | 14835.04841 | 0.69649 | 0.69649 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 15379.63789 | 15379.63789 | 1.23081 | 1.23081 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 9227.39899 | 9227.39899 | 0.43317 | 0.43317 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8027.87489 | 8027.87489 | 0.50669 | 0.50669 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 27.58867 | 5.61093E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56328E-002 | 00:10:00 | 0.50000 | 4.31558E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 76370.30951 | 76370.30951 | 4.82021 | 4.82021 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 27.58867 | 5.61093E-003 | 36.20274 | 1.94861 | 0.15633 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15633 | 00:10:00 | 0.50000 | 4.31558E-003 | 36.20274 | 1.94861 | 0.15633 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7782.91687 | 7782.91687 | 0.49129 | 0.49129 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 36.27800 | 5.62409E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56328E-002 | 00:10:00 | 0.50000 | 4.31558E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370382.35721 | 370382.35721 | 23.37946 | 23.37946 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 28.69700 | 5.61258E-003 | 783.67941 | 42.18139 | 0.33840 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33840 | 00:10:00 | 0.50000 | 4.31558E-003 | 783.67941 | 42.18139 | 0.33840 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 160702.96 | 9.65456 | 9.65456 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 23933.36 | 1.77132 | 1.77132 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1487988.82 | 90.00760 | 90.00760 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 342240.19 | 27.76895 | 27.76895 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 168680.27 | 9.96762 | 9.96762 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 34184.00 | 4.57814 | 4.57814 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 |
7 | CAV_BAS | Cooling | Sensible | 80616.46 | 5.47739 | 5.47739 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 52077.45 | 1.20019 | 1.20019 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8009.61 | 0.50669 | 0.50669 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BOT | Heating | Sensible | 678.32 | 1.56328E-002 | 1.56328E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER MID | Cooling | Sensible | 76365.12 | 4.82021 | 4.82021 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER MID | Heating | Sensible | 6783.22 | 0.15633 | 0.15633 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7821.93 | 0.49129 | 0.49129 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER TOP | Heating | Sensible | 678.32 | 1.56328E-002 | 1.56328E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.47739 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.89878 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32245 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32800 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.93480 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85986 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18159E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54723E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.93480 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17685.80269 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54723E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 356.53190 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 55.45019 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34302 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34100 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.90852 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91472 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11073E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.21890E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.90852 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 367939.72409 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.21890E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8355.15446 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.56987 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34149 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35000 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.94945 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91063 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11571E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.13590E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.29752 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 70137.10126 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.13590E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1852.23057 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06758 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22370 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22700 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24234 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59654 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.70315E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.41792E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24234 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6193.01226 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.41792E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 152.27402 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.00487 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15316 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20097 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40842 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.48762E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.26381E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20097 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4873.79387 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.26381E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 117.74047 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18297 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20189 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20500 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24251 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53836 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.88720E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.45714E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.27920 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8523.96719 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.45714E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 225.11691 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.31844 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11673 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26369 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31129 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.26387E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.48863E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26369 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3987.71727 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.48863E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 85.94349 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.03703 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23794 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23700 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.37877 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63451 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.60125E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.37926E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.17586 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 157657.35883 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37926E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4159.32254 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.39291 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14809 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.07858 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39490 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.57282E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.26206E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.47610 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 105871.05673 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.26206E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2792.95616 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.15069 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21418 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21300 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.37510 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57115 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.77888E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.39121E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.22084 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 159023.60539 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.39121E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4195.32222 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.18303 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13762 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.23661 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36700 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.76842E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.30996E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.11790 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 94987.90469 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.30996E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2506.17184 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.16848 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20439 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24538 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54503 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.86412E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.84151E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.69151 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21049.62372 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.84151E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 555.16479 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07531 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14313 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21506 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38167 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.66200E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.22346E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.45945 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13984.85660 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22346E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 368.82754 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.26987 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18807 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25397 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50152 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.02582E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.85473E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.69649 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21200.75540 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.85473E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 559.14695 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23081 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12504 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24616 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33345 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.04694E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.15361E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.43317 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13186.44571 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15361E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 347.78830 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.50669 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.82021 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49129 |
215 | ZoneHVAC:IdealLoadsAirSystem | AIRLOOP DATACENTER BASEMENT | Design Size Maximum Heating Air Flow Rate [m3/s] | 0.33840 |
216 | ZoneHVAC:IdealLoadsAirSystem | AIRLOOP DATACENTER BASEMENT | Design Size Maximum Cooling Air Flow Rate [m3/s] | 23.37946 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.23633 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.88431 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.47265 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.88431 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.65456 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.65456 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.29875 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 49.10692 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 27.97758 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 98.21385 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 27.97758 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 90.00760 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 90.00760 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31084 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.15717 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.91003 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.31433 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.57814 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.96762 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.96762 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.45930 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.47739 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.47739 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.47739 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.47739 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.47739 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.47739 |
247 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.50669 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.50669 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.50669 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.50669 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.50669 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.50669 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
257 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.82021 |
258 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.82021 |
259 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.82021 |
260 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.82021 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.82021 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.82021 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
265 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49129 |
266 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49129 |
267 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49129 |
268 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49129 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49129 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.49129 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
273 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.65456 |
274 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 90.00760 |
275 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.96762 |
276 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.47739 |
277 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.50669 |
278 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.82021 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.49129 |
280 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.65456 |
281 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.60638 |
282 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
283 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.86140 |
284 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.97740E-003 |
285 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.97740E-003 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 190969.86132 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.12430E-003 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.65456 |
289 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 36113.35193 |
290 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.15935E-004 |
291 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 611.41892 |
292 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.65456 |
293 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.12430E-003 |
294 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.86131E-005 |
295 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.15935E-004 |
296 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 90.00760 |
297 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.14441 |
298 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
299 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.86111 |
300 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.89556E-003 |
301 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.89556E-003 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1834111.49563 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.80273E-002 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 90.00760 |
305 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 329724.29146 |
306 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.88457E-003 |
307 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5590.71751 |
308 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 90.00760 |
309 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.80273E-002 |
310 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.10287E-006 |
311 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.88457E-003 |
312 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.96762 |
313 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.30476 |
314 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
315 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.86151 |
316 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00835E-003 |
317 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00835E-003 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 193820.60254 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.24558E-003 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.96762 |
321 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 30222.76658 |
322 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.64402E-004 |
323 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 518.87108 |
324 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.96762 |
325 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.24558E-003 |
326 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.77510E-005 |
327 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.64402E-004 |
328 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.47739 |
329 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.01337 |
330 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
331 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.27946 |
332 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.20732E-003 |
333 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.20732E-003 |
334 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 102213.95400 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.34842E-003 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.47739 |
337 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 240018.68983 |
338 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.09979E-003 |
339 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5397.41837 |
340 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.47739 |
341 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.34842E-003 |
342 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.09509E-004 |
343 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.09979E-003 |
344 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.50669 |
345 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56328E-002 |
346 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50669 |
347 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9327.56918 |
348 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6168.56054 |
349 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.28432E-004 |
350 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.50669 |
351 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.50669 |
352 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.50669 |
353 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.50669 |
354 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9327.56918 |
355 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9327.56918 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 678.32204 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
358 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.50669 |
359 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50669 |
360 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9327.56918 |
361 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.28432E-004 |
362 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 678.32204 |
363 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.82021 |
364 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15633 |
365 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.82021 |
366 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 88800.75831 |
367 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 58702.81707 |
368 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.17472E-003 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.82021 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.82021 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.82021 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.82021 |
373 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 88800.75831 |
374 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 88800.75831 |
375 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6783.22044 |
376 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
377 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.82021 |
378 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.82021 |
379 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 88800.75831 |
380 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.17472E-003 |
381 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6783.22044 |
382 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49129 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56328E-002 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49129 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9047.39399 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5982.12539 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.21570E-004 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49129 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49129 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49129 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49129 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9047.39399 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9047.39399 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 678.32204 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
396 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49129 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49129 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9047.39399 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.21570E-004 |
400 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 678.32204 |
401 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 9.87456E-002 |
402 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 20146.35234 |
403 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 9.87456E-002 |
404 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 11.84948 |
405 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 9.87456E-002 |
406 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 9.87456E-002 |
407 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 414484.98455 |
408 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
409 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.48932E-002 |
410 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.78718 |
411 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.48932E-002 |
412 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 4440.76380 |
413 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
414 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1702381.82550 |
415 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1702381.83000 |
416 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.48932E-002 |
417 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 9.87456E-002 |
418 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 11.84948 |
419 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 9.87456E-002 |
420 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 13947.99931 |
421 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.87456E-002 |
422 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.99397E-002 |
423 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1176765.51158 |
424 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1182347.27000 |
425 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.85100E-002 |
426 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.87456E-002 |
427 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.99397E-002 |
428 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1176765.51158 |
429 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1182347.27000 |
430 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.85100E-002 |
431 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 2.62473E-003 |
432 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 0.31497 |
433 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 2.62473E-003 |
434 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 662.80843 |
435 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 2.62473E-003 |
436 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 35644.39112 |
437 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 22226.56760 |
438 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 17822.19556 |
439 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 1996.19659 |
440 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 5900.63371 |
441 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 108116.23075 |
442 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 108116.23000 |
443 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 2.62473E-003 |
444 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
445 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
446 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
447 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
448 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
449 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.11702 |
450 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 14.04240 |
451 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.11702 |
452 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 34894.91857 |
453 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 49.81416 |
454 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1403341.77578 |
455 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 9.96283 |
456 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 175417.72197 |
457 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 49.81416 |
458 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1403341.77578 |
459 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 9.96283 |
460 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 175417.72197 |
461 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 6.07725E-002 |
462 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 6.07725E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 16770.88 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 348721.71 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 66479.52 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5867.11 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4617.87 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8079.52 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3780.17 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 149407.45 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 100330.10 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 150701.90 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 90018.70 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19947.01 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13252.24 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20090.20 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12495.77 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 29427.95 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 269467.64 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 25302.47 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 192601.99 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 251214.11 | 162114.20 | 89099.91 | 0.65 | 30384.10 | 308.17 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2382201.82 | 1528827.04 | 853374.78 | 0.64 | 290866.92 | 2950.13 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 257248.47 | 166471.11 | 90777.36 | 0.65 | 31070.86 | 315.14 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 134568.36 | 88335.90 | 46232.46 | 0.66 | 15260.04 | 154.78 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_EAST_0.25 | N/A | 2.584 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_EAST_0.25 | N/A | 2.584 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_EAST_0.25 | N/A | 2.584 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_WEST_0.25 | N/A | 2.584 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_WEST_0.25 | N/A | 2.584 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_WEST_0.25 | N/A | 2.584 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_EAST_0.25 | N/A | 2.584 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_WEST_0.25 | N/A | 2.584 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_EAST_0.25 | N/A | 2.584 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_WEST_0.25 | N/A | 2.584 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.3533962836 | 0.2635949774 | Pass | Pass | 1.3197930009 | 3.7372871102 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 7.5304239581E-002 | 0.1641768332 | Pass | Pass | 0.1054996719 | 0.3066518836 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.9455699289E-002 | 8.7812243245E-002 | Pass | Pass | 7.7514143779E-002 | 0.2668598433 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.6275497575E-002 | 4.2427805941E-002 | Pass | Pass | 9.0381403913E-002 | 0.2813698922 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.6205331938E-002 | 0.1094426839 | Pass | Pass | 0.1047377602 | 0.3059034183 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1108107886 | 0.1680759375 | Pass | Pass | 0.1053540121 | 0.3070923356 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1463091763 | 0.2060356074 | Pass | Pass | 0.1111184853 | 0.3099571757 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1199195859 | 0.2192597636 | Pass | Pass | 0.1037013273 | 0.3016329590 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.0051974387E-002 | 4.4459543366E-002 | Pass | Pass | 7.6634339364E-002 | 0.2652947203 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.8338133110E-002 | 0.1014311330 | Pass | Pass | 7.7365993838E-002 | 0.2670107233 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1497548144 | 0.1803628594 | Pass | Pass | 8.0664456563E-002 | 0.2654693221 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.5661876401E-002 | 0.1314461291 | Pass | Pass | 7.4535538283E-002 | 0.2570042635 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.7404597420E-002 | 8.7187545146E-002 | Pass | Pass | 0.3942144375 | 1.3107186494 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.8342731512E-002 | 6.9625340324E-002 | Pass | Pass | 0.5848390597 | 3.1749217579 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1254287472 | 9.0844438778E-002 | Pass | Pass | 9.8634122442E-002 | 0.3084095534 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1026864559 | 8.8227521031E-002 | Pass | Pass | 0.1142894984 | 0.3782284166 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.4250934727E-002 | 2.2765816374E-002 | Pass | Pass | 0.2046180518 | 0.8078278894 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.3485414148E-002 | 2.4804192702E-002 | Pass | Pass | 0.2349758890 | 1.1169361185 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.8919849208E-002 | 6.2197835495E-002 | Pass | Pass | 9.3051962480E-002 | 0.2849992942 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.0951971622E-006 | 1.8163091761E-006 | Pass | Pass | 5.5200140606E-003 | 6.6261459332E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.1256787198E-006 | 2.0153284279E-006 | Pass | Pass | 4.8333456593E-002 | 2.4935400841E-002 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.2625959189E-002 | 3.8344014781E-002 | Pass | Pass | 6.8225491555E-002 | 0.2192295701 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.2451176720E-015 | 2.7374385675E-015 | Pass | Pass | 5.4078702238E-005 | 1.0282799357E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5446.53 | 10.28 | 0.00 | 9888.19 | 16021.44 | 31366.46 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.4547_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.4547_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.4547_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.4547_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.4547_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.4547_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.584 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.4547_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.584 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.584 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.4547_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.584 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.584 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.4547_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.584 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.584 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.4547_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.584 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.584 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 1043.06 | 2.584 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.584 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.8895 | 2779.43 | 16369.36 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 135.58 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8895 | 2496.12 | 14700.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 121.76 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8895 | 24961.20 | 147008.37 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 1217.57 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8895 | 2496.12 | 14700.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 121.76 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8895 | 313.41 | 1845.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.15 | 0.0000 | Y | 9.06 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.54 | 0.0000 | Y | 5.70 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8895 | 313.42 | 1845.88 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.25 | 0.0000 | Y | 8.75 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.92 | 0.0000 | Y | 5.79 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8895 | 3134.13 | 18458.37 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.14 | 0.0000 | Y | 90.56 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8895 | 2019.75 | 11895.27 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.52 | 0.0000 | Y | 56.99 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8895 | 3134.20 | 18458.77 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.24 | 0.0000 | Y | 87.47 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8895 | 2019.75 | 11895.27 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.89 | 0.0000 | Y | 57.81 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8895 | 313.41 | 1845.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.14 | 0.0000 | Y | 9.06 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.52 | 0.0000 | Y | 5.70 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8895 | 313.42 | 1845.88 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.24 | 0.0000 | Y | 8.75 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.89 | 0.0000 | Y | 5.78 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.8895 | 783.68 | 4615.46 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 38.23 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 8.8011 | 36.20 | 318.62 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.26 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 8.8011 | 362.03 | 3186.24 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 32.64 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 8.8011 | 36.20 | 318.62 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.26 |
Interior Lighting Total | 5.9168 | 46320.38 | 274067.57 | 636.73 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.05 | AstronomicalClock | - | 41.79 | 41.79 | 78.23 | |
EXTERIOR_LIGHTS_B | 991.40 | AstronomicalClock | - | 83.79 | 62.79 | 11.68 | |
EXTERIOR_LIGHTS_C | 26646.63 | AstronomicalClock | - | 83.79 | 47.06 | 235.40 | |
Exterior Lighting Total | 37611.08 | 325.31 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2315778.03 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1702381.83 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1182347.27 | 6.28 | 1131661.23 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1182347.27 | 6.28 | 1131661.23 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 148548.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 108116.23 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1403341.78 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1403341.78 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 190969.86 | 251214.11 | 162114.20 | 89099.91 | 0.65 | - | 30384.10 | 308.17 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1834111.50 | 2382201.82 | 1528827.04 | 853374.78 | 0.64 | - | 290866.92 | 2950.13 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 193820.60 | 257248.47 | 166471.11 | 90777.36 | 0.65 | - | 31070.86 | 315.14 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 102213.95 | 134568.36 | 88335.90 | 46232.46 | 0.66 | - | 15260.04 | 154.78 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9327.57 | 6168.56 | 3159.01 | 0.66 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 88800.76 | 58702.82 | 30097.94 | 0.66 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9047.39 | 5982.13 | 3065.27 | 0.66 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 17685.80 | 16770.88 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 367939.72 | 348721.71 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 70137.10 | 66479.52 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 6193.01 | 5867.11 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 4873.79 | 4617.87 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8523.97 | 8079.52 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3987.72 | 3780.17 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 157657.36 | 149407.45 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 105871.06 | 100330.10 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 159023.61 | 150701.90 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 94987.90 | 90018.70 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 21049.62 | 19947.01 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13984.86 | 13252.24 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 21200.76 | 20090.20 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 13186.45 | 12495.77 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 36113.35 | 29427.95 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 329724.29 | 269467.64 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 30222.77 | 25302.47 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 240018.69 | 192601.99 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9327.57 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 88800.76 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9047.39 | 0.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 678.32 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6783.22 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 678.32 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.65 | 20862.99 | 2160.95 | 1.00 | 1.12 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 90.01 | 194501.63 | 2160.95 | 1.00 | 1.08 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.97 | 21539.49 | 2160.95 | 1.00 | 1.12 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.48 | 9287.77 | 1695.65 | 1.00 | 1.16 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.51 | 567.55 | 1120.11 | 1.00 | 1.60 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.82 | 5399.15 | 1120.11 | 1.00 | 1.16 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 550.30 | 1120.11 | 1.00 | 1.61 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.098746 | 20146.35 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.014893 | 4440.76 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.098746 | 13948.00 | 141251.81 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.002625 | 662.81 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.117020 | 34894.92 | 298196.27 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 69069.57 | 69069.57 | 24.85 | 5.477 | 5.477 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00901 | 30.96 | 0.00562 | 1.200 | 0.00 |
CORE_BOTTOM | 74382.11 | 74382.11 | 29.80 | 5.899 | 5.899 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 30.96 | 0.00562 | 1.078 | 0.00 |
CORE_MID | 699396.69 | 699396.69 | 280.19 | 55.450 | 55.450 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 30.96 | 0.00562 | 10.778 | 0.00 |
CORE_TOP | 70250.60 | 70250.60 | 28.14 | 5.570 | 5.570 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 30.96 | 0.00562 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13339.71 | 13339.71 | 42.56 | 1.068 | 1.068 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00877 | 40.80 | 0.00563 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 12556.26 | 12556.26 | 62.17 | 1.005 | 1.005 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00868 | 34.99 | 0.00562 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 14781.56 | 14781.56 | 47.16 | 1.183 | 1.183 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00874 | 40.69 | 0.00563 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 16474.46 | 16474.46 | 81.57 | 1.318 | 1.318 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00864 | 38.94 | 0.00563 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 125416.50 | 125416.50 | 400.16 | 10.037 | 10.037 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00876 | 40.67 | 0.00563 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 129864.29 | 129864.29 | 642.97 | 10.393 | 10.393 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00866 | 35.37 | 0.00562 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 139332.36 | 139332.36 | 444.56 | 11.151 | 11.151 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00873 | 40.80 | 0.00563 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 139737.18 | 139737.18 | 691.85 | 11.183 | 11.183 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00865 | 38.72 | 0.00563 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14600.63 | 14600.63 | 46.59 | 1.168 | 1.168 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00871 | 40.40 | 0.00563 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 13436.61 | 13436.61 | 66.53 | 1.075 | 1.075 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00865 | 36.08 | 0.00562 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15867.57 | 15867.57 | 50.63 | 1.270 | 1.270 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00869 | 40.80 | 0.00563 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 15379.64 | 15379.64 | 76.15 | 1.231 | 1.231 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00863 | 38.94 | 0.00563 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8027.87 | 8027.87 | 221.75 | 0.507 | 0.507 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 27.59 | 0.00561 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 76370.31 | 76370.31 | 2109.52 | 4.820 | 4.820 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 27.59 | 0.00561 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7782.92 | 7782.92 | 214.98 | 0.491 | 0.491 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 36.28 | 0.00562 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370382.36 | 370382.36 | 472.62 | 23.379 | 23.379 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 28.70 | 0.00561 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 25.35 | 0.00432 | 0.50 | 0.00432 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 22.75 | 0.00432 | 0.50 | 0.00432 | 1.078 | 0.00 | |
CORE_MID | 195098.94 | 195098.94 | 78.16 | 9.042 | 10.778 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 10.778 | 0.00 |
CORE_TOP | 49135.72 | 49135.72 | 19.68 | 2.298 | 2.298 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 3978.80 | 3978.80 | 12.70 | 0.185 | 0.185 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 3037.40 | 3037.40 | 15.04 | 0.142 | 0.142 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | 0.50 | 0.00432 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 5972.51 | 5972.51 | 19.06 | 0.279 | 0.279 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 1579.17 | 1579.17 | 7.82 | 0.073 | 0.087 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00761 | 0.50 | 0.00432 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 110353.31 | 110353.31 | 352.10 | 5.176 | 5.176 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 0.50 | 0.00432 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 74101.47 | 74101.47 | 366.88 | 3.476 | 3.476 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 0.50 | 0.00432 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 111308.39 | 111308.39 | 355.14 | 5.221 | 5.221 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 0.50 | 0.00432 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 66493.19 | 66493.19 | 329.21 | 3.118 | 3.118 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | 0.50 | 0.00432 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14729.40 | 14729.40 | 47.00 | 0.692 | 0.692 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00795 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 9785.59 | 9785.59 | 48.45 | 0.459 | 0.459 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00795 | 0.50 | 0.00432 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 14835.05 | 14835.05 | 47.33 | 0.696 | 0.696 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00795 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 9227.40 | 9227.40 | 45.69 | 0.433 | 0.433 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00794 | 0.50 | 0.00432 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 0.50 | 0.00432 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 24.75 | 0.00737 | 0.50 | 0.00432 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 23.68 | 0.00459 | 0.50 | 0.00432 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 0.50 | 0.00432 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.65 | 9.65 | 1.77 | 1.77 | 9.6546 | 2.8843 | 9.6546 | 0.2988 | 0.3000 |
VAV_MID WITH REHEAT | 90.01 | 90.01 | 27.77 | 27.77 | 90.0076 | 27.9776 | 90.0076 | 0.3108 | 0.3000 |
VAV_TOP WITH REHEAT | 9.97 | 9.97 | 4.58 | 4.58 | 9.9676 | 4.5781 | 9.9676 | 0.4593 | 0.3000 |
CAV_BAS | 5.48 | 5.48 | 1.20 | 1.20 | 5.4774 | 5.4774 | 5.4774 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.51 | 0.51 | 0.02 | 0.02 | 0.5067 | 0.5067 | 0.5067 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.82 | 4.82 | 0.16 | 0.16 | 4.8202 | 4.8202 | 4.8202 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.49 | 0.49 | 0.02 | 0.02 | 0.4913 | 0.4913 | 0.4913 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 17685.803 | 17685.803 | 1.934801 | 0.00015472 | 356.532 | 12/21 00:10:00 | 12/21 00:10:00 | 17685.80 | 17685.80 | 1.934801 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | 17751.01 | 17751.01 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 367939.724 | 367939.724 | 18.908516 | 0.00321890 | 8355.154 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 367939.72 | 367939.72 | 18.908516 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 195098.94 | 0.00 | 369192.74 | 369192.74 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 70137.101 | 70137.101 | 2.297520 | 0.00061359 | 1852.231 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 70137.10 | 70137.10 | 2.297520 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 49135.72 | 0.00 | 70385.39 | 70385.39 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 6193.012 | 6193.012 | 0.242341 | 0.00005418 | 152.274 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6193.01 | 6193.01 | 0.242341 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00777436 | 45.6443 | 3978.80 | 0.00 | 6212.51 | 6212.51 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4873.794 | 4873.794 | 0.200975 | 0.00004264 | 117.740 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4873.79 | 4873.79 | 0.200975 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00781474 | 45.8784 | 3037.40 | 0.00 | 4889.56 | 4889.56 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 8523.967 | 8523.967 | 0.279198 | 0.00007457 | 225.117 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8523.97 | 8523.97 | 0.279198 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00787644 | 46.2359 | 5972.51 | 0.00 | 8554.21 | 8554.21 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3987.717 | 3987.717 | 0.263689 | 0.00003489 | 85.943 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3987.72 | 3987.72 | 0.263689 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00761120 | 44.6979 | 1579.17 | 0.00 | 4001.65 | 4001.65 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 157657.359 | 157657.359 | 5.175863 | 0.00137926 | 4159.323 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 157657.36 | 157657.36 | 5.175863 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00792578 | 46.5219 | 110353.31 | 0.00 | 158185.28 | 158185.28 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 105871.057 | 105871.057 | 3.476104 | 0.00092621 | 2792.956 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 105871.06 | 105871.06 | 3.476104 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00792939 | 46.5428 | 74101.47 | 0.00 | 106224.58 | 106224.58 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 159023.605 | 159023.605 | 5.220838 | 0.00139121 | 4195.322 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 159023.61 | 159023.61 | 5.220838 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00792704 | 46.5292 | 111308.39 | 0.00 | 159555.78 | 159555.78 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 94987.905 | 94987.905 | 3.117900 | 0.00083100 | 2506.172 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 94987.90 | 94987.90 | 3.117900 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00791135 | 46.4384 | 66493.19 | 0.00 | 95307.40 | 95307.40 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 21049.624 | 21049.624 | 0.691510 | 0.00018415 | 555.165 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21049.62 | 21049.62 | 0.691510 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00794627 | 46.6405 | 14729.40 | 0.00 | 21118.91 | 21118.91 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 13984.857 | 13984.857 | 0.459451 | 0.00012235 | 368.828 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13984.86 | 13984.86 | 0.459451 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00794656 | 46.6422 | 9785.59 | 0.00 | 14030.81 | 14030.81 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 21200.755 | 21200.755 | 0.696486 | 0.00018547 | 559.147 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21200.76 | 21200.76 | 0.696486 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00794677 | 46.6434 | 14835.05 | 0.00 | 21270.51 | 21270.51 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 13186.446 | 13186.446 | 0.433173 | 0.00011536 | 347.788 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13186.45 | 13186.45 | 0.433173 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00794174 | 46.6143 | 9227.40 | 0.00 | 13229.90 | 13229.90 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 190969.861 | -999.000 | 9.654561 | 0.00812430 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 190969.86 | 190969.86 | 9.654561 | 28.61 | 16.53 | 0.00797740 | 10.86 | 9.91 | 0.00797740 | 40.80 | 0.00563111 | 18.58 | 26.2901 | 24.00 | 0.00886400 | 43.2965 | 115645.76 | 0.00 | 205074.98 | 195502.69 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 36113.352 | 36113.352 | 2.896368 | 0.00031594 | 611.419 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 36113.35 | 36113.35 | 2.896368 | 1.45 | 1.26 | 0.00448444 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 87.6335 | 21.78 | 0.00620424 | 34.8204 | 14567.88 | 0.00 | 35616.30 | 35616.30 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1834111.496 | -999.000 | 90.007601 | 0.07802734 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1834111.50 | 1834111.49 | 90.007601 | 29.14 | 16.64 | 0.00789556 | 10.86 | 9.83 | 0.00789556 | 40.80 | 0.00563111 | 18.58 | 28.1998 | 24.00 | 0.00889525 | 43.4470 | 1035547.13 | 0.00 | 1967661.67 | 1887692.84 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 329724.291 | 329724.291 | 27.002280 | 0.00288457 | 5590.718 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 329724.29 | 329724.29 | 27.002280 | 1.68 | 1.46 | 0.00453268 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 93.9993 | 21.06 | 0.00791514 | 46.3020 | 437307.51 | 0.00 | 326138.02 | 326138.02 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 193820.603 | -999.000 | 9.967616 | 0.00824558 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 193820.60 | 193820.60 | 9.967616 | 28.30 | 16.45 | 0.00800835 | 10.86 | 9.95 | 0.00800835 | 40.80 | 0.00563111 | 18.58 | 25.4644 | 24.00 | 0.00882756 | 43.1209 | 123748.55 | 0.00 | 208339.61 | 198066.62 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 30222.767 | 30222.767 | 2.990285 | 0.00026440 | 518.871 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 30222.77 | 30222.77 | 2.990285 | 3.60 | 2.92 | 0.00486574 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 84.8812 | 21.00 | 0.00795445 | 46.6877 | 54020.66 | 0.00 | 30626.58 | 30626.58 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 102213.954 | -999.000 | 5.477394 | 0.00434842 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 102213.95 | 102213.95 | 5.477394 | 28.01 | 16.52 | 0.00820732 | 11.28 | 10.32 | 0.00820732 | 40.13 | 0.00563007 | 18.37 | 21.9117 | 24.00 | 0.00906093 | 44.2451 | 60274.00 | 0.00 | 109866.97 | 103870.71 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 240018.690 | 240018.690 | 5.477394 | 0.00209979 | 5397.418 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 240018.69 | 240018.69 | 5.477394 | 0.11 | 0.11 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 21.9117 | 25.35 | 0.00431558 | 19.5852 | 0.00 | 0.00 | 203618.05 | 203618.05 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9327.569 | 6168.561 | 0.506689 | 0.00022843 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 8451.15 | 8451.15 | -999.0 | 28.33 | 16.85 | 0.00849859 | 12.80 | 11.23 | 0.00849859 | 36.28 | 0.00562409 | 17.15 | -999.0000 | 27.00 | 0.00859074 | 35.1297 | 7973.55 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 88800.758 | 58702.817 | 4.820209 | 0.00217472 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 80467.16 | 80467.16 | -999.0 | 28.34 | 16.86 | 0.00849836 | 12.80 | 11.23 | 0.00849836 | 36.28 | 0.00562409 | 17.15 | -999.0000 | 27.00 | 0.00859524 | 35.1482 | 75945.89 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9047.394 | 5982.125 | 0.491290 | 0.00022157 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8197.82 | 8197.82 | -999.0 | 28.34 | 16.86 | 0.00849854 | 12.80 | 11.23 | 0.00849854 | 36.28 | 0.00562409 | 17.15 | -999.0000 | 27.00 | 0.00859301 | 35.1390 | 7782.92 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9327.569 | 9327.569 | 0.506689 | 0.00022843 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9327.57 | 9327.57 | 0.506689 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.0853 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 88800.758 | 88800.758 | 4.820209 | 0.00217472 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 88800.76 | 88800.76 | 4.820209 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.2432 | 24.75 | 0.00736986 | 34.4972 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9047.394 | 9047.394 | 0.491290 | 0.00022157 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9047.39 | 9047.39 | 0.491290 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.1820 | 23.68 | 0.00458893 | 23.0063 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 678.322 | 678.322 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 678.32 | 678.32 | 0.506689 | 0.02 | 0.02 | 0.00837090 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.0853 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6783.220 | 6783.220 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6783.22 | 6783.22 | 4.820209 | 0.02 | 0.02 | 0.00727081 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.2432 | 24.75 | 0.00736986 | 34.4972 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 678.322 | 678.322 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 678.32 | 678.32 | 0.491290 | 0.02 | 0.02 | 0.00458023 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.1820 | 23.68 | 0.00458893 | 23.0063 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 17685.803 | 17685.803 | 1.934801 | 0.00015472 | 356.532 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 1.0184 | 1.038886 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 17685.80 | 17685.80 | 1.0000 | 2.11511295 | 1.934801 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.15470733 | 60.00 | 32.22 | 27.78 | 0.000 | 17685.80 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | 17751.01 | 17751.01 | 2.11511295 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 367939.724 | 367939.724 | 18.908516 | 0.00321890 | 8355.154 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 21.1868 | 21.613231 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 367939.72 | 367939.72 | 1.0000 | 20.67068000 | 18.908516 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 3.21856885 | 60.00 | 32.22 | 27.78 | 0.000 | 367939.72 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 195098.94 | 0.00 | 369192.74 | 369192.74 | 20.67068000 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.32 | 18.14 | 0.00800000 | 50920.5 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 70137.101 | 70137.101 | 2.297520 | 0.00061359 | 1852.231 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 4.0387 | 4.119939 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 70137.10 | 70137.10 | 1.0000 | 2.51163606 | 2.297520 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.61352737 | 60.00 | 32.22 | 27.78 | 0.000 | 70137.10 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 49135.72 | 0.00 | 70385.39 | 70385.39 | 2.51163606 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.28 | 21.27 | 0.00800000 | 61083.6 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6193.012 | 6193.012 | 0.242341 | 0.00005418 | 152.274 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 0.3566 | 0.363785 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6193.01 | 6193.01 | 1.0000 | 0.26492550 | 0.242341 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.05417365 | 60.00 | 32.22 | 27.78 | 0.000 | 6193.01 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.87 | 0.00777436 | 21.00 | 0.00777436 | 45.6443 | 3978.80 | 0.00 | 6212.51 | 6212.51 | 0.26492550 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.80 | 19.91 | 0.00800000 | 56509.8 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4873.794 | 4873.794 | 0.200975 | 0.00004264 | 117.740 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 0.2806 | 0.286293 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4873.79 | 4873.79 | 1.0000 | 0.21970468 | 0.200975 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04263373 | 60.00 | 32.22 | 27.78 | 0.000 | 4873.79 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.86 | 0.00781474 | 21.00 | 0.00781474 | 45.8784 | 3037.40 | 0.00 | 4889.56 | 4889.56 | 0.21970468 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.62 | 19.54 | 0.00800000 | 55315.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8523.967 | 8523.967 | 0.279198 | 0.00007457 | 225.117 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 0.4908 | 0.500708 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8523.97 | 8523.97 | 1.0000 | 0.30521723 | 0.279198 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.07456378 | 60.00 | 32.22 | 27.78 | 0.000 | 8523.97 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.92 | 0.00787644 | 21.00 | 0.00787644 | 46.2359 | 5972.51 | 0.00 | 8554.21 | 8554.21 | 0.30521723 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.28 | 21.27 | 0.00800000 | 61086.5 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3987.717 | 3987.717 | 0.263689 | 0.00003489 | 85.943 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 0.2296 | 0.234243 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 3987.72 | 3987.72 | 1.0000 | 0.28826282 | 0.263689 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.03488273 | 60.00 | 32.22 | 27.78 | 0.000 | 3987.72 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.90 | 0.00761120 | 21.00 | 0.00761120 | 44.6979 | 1579.17 | 0.00 | 4001.65 | 4001.65 | 0.28826282 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 26.41 | 16.81 | 0.00800000 | 46941.8 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 157657.359 | 157657.359 | 5.175863 | 0.00137926 | 4159.323 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 9.0783 | 9.260987 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 157657.36 | 157657.36 | 1.0000 | 5.65822379 | 5.175863 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 1.37911465 | 60.00 | 32.22 | 27.78 | 0.000 | 157657.36 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00792578 | 21.00 | 0.00792578 | 46.5219 | 110353.31 | 0.00 | 158185.28 | 158185.28 | 5.65822379 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61016.5 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 105871.057 | 105871.057 | 3.476104 | 0.00092621 | 2792.956 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 6.0963 | 6.218996 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 105871.06 | 105871.06 | 1.0000 | 3.80005647 | 3.476104 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.92611171 | 60.00 | 32.22 | 27.78 | 0.000 | 105871.06 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00792939 | 21.00 | 0.00792939 | 46.5428 | 74101.47 | 0.00 | 106224.58 | 106224.58 | 3.80005647 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61013.2 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 159023.605 | 159023.605 | 5.220838 | 0.00139121 | 4195.322 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 9.1570 | 9.341242 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 159023.61 | 159023.61 | 1.0000 | 5.70739033 | 5.220838 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 1.39106595 | 60.00 | 32.22 | 27.78 | 0.000 | 159023.61 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00792704 | 21.00 | 0.00792704 | 46.5292 | 111308.39 | 0.00 | 159555.78 | 159555.78 | 5.70739033 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61015.8 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 94987.905 | 94987.905 | 3.117900 | 0.00083100 | 2506.172 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 5.4696 | 5.579706 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 94987.90 | 94987.90 | 1.0000 | 3.40847036 | 3.117900 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.83091086 | 60.00 | 32.22 | 27.78 | 0.000 | 94987.90 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00791135 | 21.00 | 0.00791135 | 46.4384 | 66493.19 | 0.00 | 95307.40 | 95307.40 | 3.40847036 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61021.8 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21049.624 | 21049.624 | 0.691510 | 0.00018415 | 555.165 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 1.2121 | 1.236481 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21049.62 | 21049.62 | 1.0000 | 0.75595512 | 0.691510 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.18413251 | 60.00 | 32.22 | 27.78 | 0.000 | 21049.62 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00794627 | 21.00 | 0.00794627 | 46.6405 | 14729.40 | 0.00 | 21118.91 | 21118.91 | 0.75595512 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60996.5 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13984.857 | 13984.857 | 0.459451 | 0.00012235 | 368.828 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 0.8053 | 0.821488 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13984.86 | 13984.86 | 1.0000 | 0.50226912 | 0.459451 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.12233315 | 60.00 | 32.22 | 27.78 | 0.000 | 13984.86 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00794656 | 21.00 | 0.00794656 | 46.6422 | 9785.59 | 0.00 | 14030.81 | 14030.81 | 0.50226912 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60994.7 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21200.755 | 21200.755 | 0.696486 | 0.00018547 | 559.147 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 1.2208 | 1.245358 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21200.76 | 21200.76 | 1.0000 | 0.76139404 | 0.696486 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.18545454 | 60.00 | 32.22 | 27.78 | 0.000 | 21200.76 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00794677 | 21.00 | 0.00794677 | 46.6434 | 14835.05 | 0.00 | 21270.51 | 21270.51 | 0.76139404 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60996.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13186.446 | 13186.446 | 0.433173 | 0.00011536 | 347.788 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 0.7593 | 0.774588 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13186.45 | 13186.45 | 1.0000 | 0.47354183 | 0.433173 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.11534901 | 60.00 | 32.22 | 27.78 | 0.000 | 13186.45 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00794174 | 21.00 | 0.00794174 | 46.6143 | 9227.40 | 0.00 | 13229.90 | 13229.90 | 0.47354183 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60998.0 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 190969.861 | -999.000 | 9.654561 | 0.00812430 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6696 | 1004.8586 | 1.0932 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.654561 | 10.55431026 | 4197.9300 | 999.8980 | 98.73556361 | 12.27 | 6.67 | 5.60 | 2321115.91 | 8.2275 | 8.227502 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 190969.86 | 190969.86 | 1.0000 | 10.55431026 | 9.654561 | 28.61 | 16.53 | 0.00797740 | 49120.1 | 10.86 | 9.91 | 0.00797740 | 31026.0 | 8.12347060 | 6.67 | 12.27 | 5.60 | 20862.992 | 170106.87 | 40.80 | 0.00563111 | 18.58 | 2.53819000 | 26.2901 | 24.00 | 0.00886400 | 24.00 | 0.00886400 | 43.2965 | 115645.76 | 0.00 | 205074.98 | 195502.69 | 10.55431026 | 28.61 | 17.55 | 0.00797740 | 49120.1 | 10.44 | 10.18 | 0.00761755 | 29689.6 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 36113.352 | 36113.352 | 2.896368 | 0.00031594 | 611.419 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.654561 | 10.55431026 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 2.0795 | 2.121343 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 36113.35 | 36113.35 | 1.0000 | 3.16629308 | 2.896368 | 1.45 | 1.26 | 0.00448444 | 12684.0 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 0.31590313 | 60.00 | 32.22 | 27.78 | 0.000 | 36113.35 | 0.50 | 0.00431558 | 0.50 | 2.53819000 | 87.6335 | 8.18 | 0.00568102 | 21.78 | 0.00620424 | 34.8204 | 14567.88 | 0.00 | 35616.30 | 35616.30 | 3.16629308 | 2.80 | 2.61 | 0.00448444 | 14052.2 | 13.90 | 8.28 | 0.00448444 | 25300.8 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1834111.496 | -999.000 | 90.007601 | 0.07802734 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5175 | 1004.8586 | 1.0932 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 90.007601 | 98.39578839 | 4197.9300 | 999.8980 | 98.73556361 | 12.27 | 6.67 | 5.60 | 2321115.91 | 79.0185 | 79.018522 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1834111.50 | 1834111.49 | 1.0000 | 98.39578839 | 90.007601 | 29.14 | 16.64 | 0.00789556 | 49459.6 | 10.86 | 9.83 | 0.00789556 | 30819.4 | 78.01938335 | 6.67 | 12.27 | 5.60 | 194501.632 | 1639609.86 | 40.80 | 0.00563111 | 18.58 | 25.38195000 | 28.1998 | 24.00 | 0.00889525 | 24.00 | 0.00889525 | 43.4470 | 1035547.13 | 0.00 | 1967661.67 | 1887692.84 | 98.39578839 | 29.14 | 17.66 | 0.00789556 | 49459.6 | 10.33 | 10.08 | 0.00757307 | 29462.1 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 329724.291 | 329724.291 | 27.002280 | 0.00288457 | 5590.718 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 90.007601 | 98.39578839 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 18.9863 | 19.368410 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 329724.29 | 329724.29 | 1.0000 | 29.51873652 | 27.002280 | 1.68 | 1.46 | 0.00453268 | 13042.3 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 2.88427768 | 60.00 | 32.22 | 27.78 | 0.000 | 329724.29 | 0.50 | 0.00431558 | 0.50 | 25.38195000 | 93.9993 | 20.23 | 0.00793338 | 21.06 | 0.00791514 | 46.3020 | 437307.51 | 0.00 | 326138.02 | 326138.02 | 29.51873652 | 2.80 | 2.68 | 0.00453268 | 14173.1 | 13.70 | 8.24 | 0.00453268 | 25221.6 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 193820.603 | -999.000 | 9.967616 | 0.00824558 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7271 | 1004.8586 | 1.0932 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.967616 | 10.89654024 | 4197.9300 | 999.8980 | 98.73556361 | 12.27 | 6.67 | 5.60 | 2321115.91 | 8.3503 | 8.350320 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 193820.60 | 193820.60 | 1.0000 | 10.89654024 | 9.967616 | 28.30 | 16.45 | 0.00800835 | 48891.5 | 10.86 | 9.95 | 0.00800835 | 31104.2 | 8.24473535 | 6.67 | 12.27 | 5.60 | 21539.488 | 172281.12 | 40.80 | 0.00563111 | 18.58 | 2.53819000 | 25.4644 | 24.00 | 0.00882756 | 24.00 | 0.00882756 | 43.1209 | 123748.55 | 0.00 | 208339.61 | 198066.62 | 10.89654024 | 28.30 | 17.47 | 0.00800835 | 48891.5 | 10.48 | 10.22 | 0.00763429 | 29771.7 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 30222.767 | 30222.767 | 2.990285 | 0.00026440 | 518.871 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.967616 | 10.89654024 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 1.7403 | 1.775322 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 30222.77 | 30222.77 | 1.0000 | 3.26896207 | 2.990285 | 3.60 | 2.92 | 0.00486574 | 15818.2 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 0.26437497 | 60.00 | 32.22 | 27.78 | 0.000 | 30222.77 | 0.50 | 0.00431558 | 0.50 | 2.53819000 | 84.8812 | 21.00 | 0.00795445 | 21.00 | 0.00795445 | 46.6877 | 54020.66 | 0.00 | 30626.58 | 30626.58 | 3.26896207 | 2.80 | 2.80 | 0.00486574 | 15007.8 | 12.04 | 7.84 | 0.00486574 | 24376.7 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 102213.954 | -999.000 | 5.477394 | 0.00434842 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0970 | 1004.8586 | 1.0932 | CAV_BAS FAN | Fan:ConstantVolume | 5.477394 | 5.98785492 | 4197.9300 | 999.8980 | 98.73556361 | 12.27 | 6.67 | 5.60 | 2321115.91 | 4.4037 | 4.403656 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 102213.95 | 102213.95 | 1.0000 | 5.98785492 | 5.477394 | 28.01 | 16.52 | 0.00820732 | 49102.4 | 11.28 | 10.32 | 0.00820732 | 32032.2 | 4.34797431 | 6.67 | 12.27 | 5.60 | 9287.766 | 92926.19 | 40.13 | 0.00563007 | 18.37 | 1.20019084 | 21.9117 | 24.00 | 0.00906093 | 24.00 | 0.00906093 | 44.2451 | 60274.00 | 0.00 | 109866.97 | 103870.71 | 5.98785492 | 28.01 | 17.54 | 0.00820732 | 49102.4 | 11.01 | 10.63 | 0.00781016 | 30754.1 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 240018.690 | 240018.690 | 5.477394 | 0.00209979 | 5397.418 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | CAV_BAS FAN | Fan:ConstantVolume | 5.477394 | 5.98785492 | 4197.9300 | 999.8980 | 14.89165960 | 54.44 | 82.22 | 27.78 | 1736642.94 | 13.8208 | 14.098993 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 240018.69 | 240018.69 | 1.0000 | 5.98785492 | 5.477394 | 0.11 | 0.11 | 0.00431558 | 10904.0 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 2.09957400 | 60.00 | 32.22 | 27.78 | 0.000 | 240018.69 | 0.50 | 0.00431558 | 0.50 | 1.20019084 | 21.9117 | 0.00 | 0.00431558 | 25.35 | 0.00431558 | 19.5852 | 0.00 | 0.00 | 203618.05 | 203618.05 | 5.98785492 | 12.80 | 7.56 | 0.00431558 | 23757.7 | 46.37 | 20.38 | 0.00431558 | 57762.8 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9327.569 | 6168.561 | 0.506689 | 0.00022843 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6385 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | Sensible | 8451.15 | 8451.15 | 0.9060 | -999.0 | -999.0 | 28.33 | 16.85 | 0.00849859 | 50168.5 | 12.80 | 11.23 | 0.00849859 | 34318.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8451.15 | 36.28 | 0.00562409 | 17.15 | 0.01563279 | -999.0000 | 27.00 | 0.00859074 | 27.00 | 0.00859074 | 35.1297 | 7973.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 88800.758 | 58702.817 | 4.820209 | 0.00217472 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6380 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | Sensible | 80467.16 | 80467.16 | 0.9062 | -999.0 | -999.0 | 28.34 | 16.86 | 0.00849836 | 50182.5 | 12.80 | 11.23 | 0.00849836 | 34318.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 80467.16 | 36.28 | 0.00562409 | 17.15 | 0.15632792 | -999.0000 | 27.00 | 0.00859524 | 27.00 | 0.00859524 | 35.1482 | 75945.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9047.394 | 5982.125 | 0.491290 | 0.00022157 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6384 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8197.82 | 8197.82 | 0.9061 | -999.0 | -999.0 | 28.34 | 16.86 | 0.00849854 | 50175.6 | 12.80 | 11.23 | 0.00849854 | 34318.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8197.82 | 36.28 | 0.00562409 | 17.15 | 0.01563279 | -999.0000 | 27.00 | 0.00859301 | 27.00 | 0.00859301 | 35.1390 | 7782.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9327.569 | 9327.569 | 0.506689 | 0.00022843 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9327.57 | 9327.57 | 1.0000 | 0.55391000 | 0.506689 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9327.57 | 0.50 | 0.00431558 | 0.50 | 0.01563279 | 3.0853 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 88800.758 | 88800.758 | 4.820209 | 0.00217472 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 88800.76 | 88800.76 | 1.0000 | 5.26942423 | 4.820209 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 88800.76 | 0.50 | 0.00431558 | 0.50 | 0.15632792 | 3.2432 | 0.00 | 0.00736986 | 24.75 | 0.00736986 | 34.4972 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9047.394 | 9047.394 | 0.491290 | 0.00022157 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9047.39 | 9047.39 | 1.0000 | 0.53707512 | 0.491290 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9047.39 | 0.50 | 0.00431558 | 0.50 | 0.01563279 | 3.1820 | 0.00 | 0.00458893 | 23.68 | 0.00458893 | 23.0063 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 678.322 | 678.322 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.506689 | 0.55391000 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 678.32 | 678.32 | 1.0000 | 0.55391000 | 0.506689 | 0.02 | 0.02 | 0.00837090 | 20950.9 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 678.32 | 0.50 | 0.00431558 | 0.50 | 0.01563279 | 3.0853 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6783.220 | 6783.220 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.820209 | 5.26942423 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 6783.22 | 6783.22 | 1.0000 | 5.26942423 | 4.820209 | 0.02 | 0.02 | 0.00727081 | 18200.4 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6783.22 | 0.50 | 0.00431558 | 0.50 | 0.15632792 | 3.2432 | 0.00 | 0.00736986 | 24.75 | 0.00736986 | 34.4972 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 678.322 | 678.322 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.491290 | 0.53707512 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 678.32 | 678.32 | 1.0000 | 0.53707512 | 0.491290 | 0.02 | 0.02 | 0.00458023 | 11471.0 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 678.32 | 0.50 | 0.00431558 | 0.50 | 0.01563279 | 3.1820 | 0.00 | 0.00458893 | 23.68 | 0.00458893 | 23.0063 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.65 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 90.01 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.97 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.48 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | BASEMENT_DCV | 0.002360 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2521.33 | 1090.00 | 375.50 |
CORE_BOTTOM | 2135.17 | 784.67 | 14.50 |
CORE_MID | 1531.00 | 2360.17 | 92.67 |
CORE_TOP | 1595.50 | 2914.83 | 212.00 |
PERIMETER_BOT_ZN_3 | 2011.17 | 2304.83 | 57.83 |
PERIMETER_BOT_ZN_2 | 2578.50 | 1852.50 | 153.83 |
PERIMETER_BOT_ZN_1 | 2892.50 | 1177.33 | 148.00 |
PERIMETER_BOT_ZN_4 | 3669.50 | 828.33 | 320.50 |
PERIMETER_MID_ZN_3 | 1909.50 | 3000.00 | 239.83 |
PERIMETER_MID_ZN_2 | 2079.50 | 2138.00 | 246.00 |
PERIMETER_MID_ZN_1 | 2655.83 | 1575.17 | 171.33 |
PERIMETER_MID_ZN_4 | 2536.33 | 2334.17 | 221.83 |
PERIMETER_TOP_ZN_3 | 2523.50 | 3165.50 | 791.67 |
PERIMETER_TOP_ZN_2 | 2831.83 | 2693.50 | 571.17 |
PERIMETER_TOP_ZN_1 | 2710.67 | 1994.00 | 327.33 |
PERIMETER_TOP_ZN_4 | 2777.00 | 2653.33 | 511.83 |
DATACENTER_BOT_ZN_6 | 5943.00 | 919.83 | 919.83 |
DATACENTER_MID_ZN_6 | 5943.00 | 287.17 | 287.17 |
DATACENTER_TOP_ZN_6 | 5767.00 | 393.83 | 382.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 94.83 | 0.00 | 6.17 |
CORE_BOTTOM | 0.00 | 2.17 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 23.33 | 0.00 | 8.67 |
PERIMETER_BOT_ZN_2 | 0.00 | 60.33 | 0.00 | 51.50 |
PERIMETER_BOT_ZN_1 | 0.00 | 82.67 | 0.00 | 61.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 247.00 | 0.00 | 82.00 |
PERIMETER_MID_ZN_3 | 0.00 | 10.50 | 0.00 | 3.83 |
PERIMETER_MID_ZN_2 | 0.00 | 65.33 | 0.00 | 55.67 |
PERIMETER_MID_ZN_1 | 0.00 | 78.33 | 0.00 | 67.17 |
PERIMETER_MID_ZN_4 | 0.00 | 84.67 | 0.00 | 29.67 |
PERIMETER_TOP_ZN_3 | 3.33 | 39.67 | 0.17 | 18.83 |
PERIMETER_TOP_ZN_2 | 2.50 | 90.50 | 0.00 | 63.50 |
PERIMETER_TOP_ZN_1 | 1.33 | 82.17 | 0.00 | 53.00 |
PERIMETER_TOP_ZN_4 | 1.33 | 101.50 | 0.00 | 35.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 400.33 | 0.00 | 323.83 |
DATACENTER_MID_ZN_6 | 0.00 | 402.00 | 0.00 | 325.67 |
DATACENTER_TOP_ZN_6 | 0.00 | 353.00 | 0.00 | 285.17 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 3.33 | 910.17 | 0.17 | 560.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 1.171 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 0.874 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.679 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.616 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.825 | 0.009 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 1.197 | 0.009 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 1.343 | 0.009 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 1.746 | 0.009 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.723 | 0.020 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 1.094 | 0.023 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 1.244 | 0.020 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 1.177 | 0.021 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.701 | 0.025 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 1.102 | 0.026 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 1.159 | 0.025 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 1.151 | 0.026 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.22 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 0.847 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.95 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.011 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.110 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.011 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 783.68 | 0.239 | ||
Total Facility | 1031.21 | 2493.19 | 126016.35 | 46320.38 | 1.3878 | 157.549 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 51067799.35 | 0.00 | 51067799.35 | 0.00 | 51067799.35 | 29876159.83 | 3724.03 | 2353.28 | 2682.69 | 463.61 |
CORE_BOTTOM | 39332309.65 | 0.00 | 39332309.65 | 0.00 | 39332309.65 | 33990283.35 | 5462.48 | 8.64 | 3288.88 | 672.25 |
CORE_MID | 0.29E+09 | 0.00 | 0.29E+09 | 0.00 | 0.29E+09 | 0.34E+09 | 6097.00 | 30.78 | 2632.22 | 213.21 |
CORE_TOP | 26088082.10 | 0.00 | 26088082.10 | 0.00 | 26088082.10 | 33990283.35 | 6296.02 | 21.43 | 2442.54 | 233.16 |
PERIMETER_BOT_ZN_3 | 4680074.81 | 0.00 | 4680074.81 | 86999.60 | 4767074.41 | 4267819.30 | 3692.54 | 51.33 | 5016.13 | 672.25 |
PERIMETER_BOT_ZN_2 | 4318212.91 | 0.00 | 4318212.91 | 57999.70 | 4376212.60 | 2750345.05 | 3298.93 | 15.49 | 5445.58 | 672.25 |
PERIMETER_BOT_ZN_1 | 7286757.69 | 0.00 | 7286757.69 | 86999.60 | 7373757.29 | 4267912.63 | 3482.91 | 25.07 | 5252.02 | 672.25 |
PERIMETER_BOT_ZN_4 | 6300625.30 | 0.00 | 6300625.30 | 57999.70 | 6358625.00 | 2750345.05 | 3244.54 | 0.00 | 5515.46 | 672.25 |
PERIMETER_MID_ZN_3 | 38111651.81 | 0.00 | 38111651.81 | 204034.67 | 38315686.48 | 42678193.03 | 4352.25 | 64.31 | 4343.44 | 213.21 |
PERIMETER_MID_ZN_2 | 38941659.88 | 0.00 | 38941659.88 | 136023.02 | 39077682.90 | 27503450.52 | 3834.62 | 1.57 | 4923.82 | 1122.21 |
PERIMETER_MID_ZN_1 | 64248456.86 | 0.00 | 64248456.86 | 204034.67 | 64452491.53 | 42679126.28 | 4099.59 | 30.39 | 4630.02 | 213.21 |
PERIMETER_MID_ZN_4 | 39875232.41 | 0.00 | 39875232.41 | 136023.02 | 40011255.43 | 27503450.52 | 3830.13 | 1.73 | 4928.14 | 213.21 |
PERIMETER_TOP_ZN_3 | 3711169.27 | 0.00 | 3711169.27 | 253326.10 | 3964495.36 | 4267819.30 | 4509.77 | 34.15 | 4216.08 | 233.16 |
PERIMETER_TOP_ZN_2 | 3730480.99 | 0.00 | 3730480.99 | 168883.95 | 3899364.93 | 2750345.05 | 3906.82 | 3.87 | 4849.31 | 233.16 |
PERIMETER_TOP_ZN_1 | 6019186.27 | 0.00 | 6019186.27 | 253326.10 | 6272512.36 | 4267912.63 | 3992.99 | 34.97 | 4732.04 | 233.16 |
PERIMETER_TOP_ZN_4 | 3925725.11 | 0.00 | 3925725.11 | 168883.95 | 4094609.06 | 2750345.05 | 3883.51 | 3.70 | 4872.79 | 233.16 |
DATACENTER_BOT_ZN_6 | 244303.03 | 0.00 | 244303.03 | 0.00 | 244303.03 | 389144.62 | 4419.00 | 504.00 | 3837.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2443030.26 | 0.00 | 2443030.26 | 0.00 | 2443030.26 | 3891446.16 | 4419.00 | 504.00 | 3837.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244303.03 | 0.00 | 244303.03 | 0.00 | 244303.03 | 389144.62 | 4419.00 | 504.00 | 3837.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8423799.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 0.48E+10 | 0.00 | 0.48E+10 | 7935572.39 | 0.49E+10 | 0.50E+10 | 8760.00 | 2651.43 | 5763.23 | 1823.93 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.1606 | 0.0000 | 2.1606 | 0.0000 | 2.1606 | 0.9949 | 1303.95 | 2351.69 | 2287.36 |
CORE_BOTTOM | 1.6280 | 0.0000 | 1.6280 | 0.0000 | 1.6280 | 1.0778 | 3290.36 | 4.34 | 2648.30 |
CORE_MID | 12.6512 | 0.0000 | 12.6512 | 0.0000 | 12.6512 | 10.7782 | 3490.63 | 30.54 | 2421.83 |
CORE_TOP | 1.1482 | 0.0000 | 1.1482 | 0.0000 | 1.1482 | 1.0778 | 3683.62 | 21.43 | 2237.94 |
PERIMETER_BOT_ZN_3 | 0.1929 | 0.0000 | 0.1929 | 0.0020 | 0.1949 | 0.1353 | 1515.37 | 47.03 | 4380.60 |
PERIMETER_BOT_ZN_2 | 0.1806 | 0.0000 | 0.1806 | 0.0014 | 0.1820 | 0.0872 | 1150.00 | 14.33 | 4778.67 |
PERIMETER_BOT_ZN_1 | 0.3145 | 0.0000 | 0.3145 | 0.0020 | 0.3165 | 0.1353 | 1305.98 | 20.59 | 4616.43 |
PERIMETER_BOT_ZN_4 | 0.2633 | 0.0000 | 0.2633 | 0.0014 | 0.2647 | 0.0872 | 1099.79 | 0.00 | 4843.21 |
PERIMETER_MID_ZN_3 | 1.6947 | 0.0000 | 1.6947 | 0.0048 | 1.6995 | 1.3533 | 1745.98 | 64.03 | 4132.98 |
PERIMETER_MID_ZN_2 | 1.6509 | 0.0000 | 1.6509 | 0.0034 | 1.6543 | 0.8721 | 1228.62 | 1.04 | 3804.34 |
PERIMETER_MID_ZN_1 | 2.9131 | 0.0000 | 2.9131 | 0.0048 | 2.9179 | 1.3533 | 1493.18 | 30.15 | 4419.67 |
PERIMETER_MID_ZN_4 | 1.7763 | 0.0000 | 1.7763 | 0.0032 | 1.7794 | 0.8721 | 1224.76 | 1.73 | 4716.51 |
PERIMETER_TOP_ZN_3 | 0.1643 | 0.0000 | 0.1643 | 0.0059 | 0.1702 | 0.1353 | 1898.25 | 34.05 | 4010.70 |
PERIMETER_TOP_ZN_2 | 0.1664 | 0.0000 | 0.1664 | 0.0039 | 0.1703 | 0.0872 | 1298.54 | 2.32 | 4642.14 |
PERIMETER_TOP_ZN_1 | 0.2716 | 0.0000 | 0.2716 | 0.0059 | 0.2775 | 0.1353 | 1380.81 | 34.97 | 4527.22 |
PERIMETER_TOP_ZN_4 | 0.1739 | 0.0000 | 0.1739 | 0.0039 | 0.1778 | 0.0872 | 1280.59 | 2.55 | 4659.86 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0130 | 1602.00 | 504.00 | 3837.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1296 | 1602.00 | 504.00 | 3837.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0130 | 1602.00 | 504.00 | 3837.00 |
DATACENTER_BASEMENT_ZN_6 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.2805 | 5943.00 | 0.00 | 0.00 |
Total Facility | 214.6903 | 0.0000 | 214.6903 | 0.1878 | 214.8781 | 157.9346 | 5943.00 | 2640.69 | 4901.12 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 73996549.04 | 0.00 | 73996549.04 | 48026705.38 | 3250.66 | 1.37 | 5507.97 | 672.25 |
VAV_MID WITH REHEAT | 0.56E+09 | 0.00 | 0.56E+09 | 0.48E+09 | 3839.35 | 0.87 | 4919.78 | 213.21 |
VAV_TOP WITH REHEAT | 51955400.72 | 0.00 | 51955400.72 | 48026705.38 | 3922.87 | 3.65 | 4833.49 | 233.16 |
CAV_BAS | 61029778.58 | 0.00 | 61029778.58 | 29876159.83 | 3707.08 | 1.89 | 5051.03 | 463.61 |
AIRLOOP DATACENTER BOT | 291960.10 | 0.00 | 291960.10 | 389144.62 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 2919600.96 | 0.00 | 2919600.96 | 3891446.16 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 291960.10 | 0.00 | 291960.10 | 389144.62 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.0824 | 0.0000 | 3.0824 | 1.5229 | 1101.52 | 0.33 | 4841.15 |
VAV_MID WITH REHEAT | 24.8332 | 0.0000 | 24.8332 | 15.2292 | 1233.47 | 0.87 | 4708.65 |
VAV_TOP WITH REHEAT | 2.2998 | 0.0000 | 2.2998 | 1.5229 | 1311.39 | 3.59 | 4628.02 |
CAV_BAS | 2.5821 | 0.0000 | 2.5821 | 0.9949 | 1302.46 | 0.12 | 4640.41 |
AIRLOOP DATACENTER BOT | 0.0136 | 0.0000 | 0.0136 | 0.0130 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1365 | 0.0000 | 0.1365 | 0.1296 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0136 | 0.0000 | 0.0136 | 0.0130 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.22 | 3320.24 | 0.00 | 0.00 | 0.00 | 2195.00 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.43 | 2659.18 | 0.00 | 0.00 | 0.00 | 2278.25 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.35 | 2561.88 | 0.00 | 0.00 | 0.00 | 2357.75 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 0.00 | 2759.19 | 0.00 | 0.00 | 0.00 | 2351.43 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 5.2793 | 0.0000 | 0.0000 | 0.0000 | 1.9760 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 41.3116 | 0.0000 | 0.0000 | 0.0000 | 20.4111 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 3.8512 | 0.0000 | 0.0000 | 0.0000 | 1.9932 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 0.0000 | 5.4048 | 0.0000 | 0.0000 | 0.0000 | 1.2510 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0187 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1869 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0187 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 7 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1352 |
Defaulted Fields | 1168 |
Fields with Defaults | 3820 |
Autosized Fields | 313 |
Autosizable Fields | 391 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 24966.65 | 287053.15 | 01-JAN-04:40 | 1634688.54 | 11-AUG-15:20 |
Electricity:Building | 16701.88 | 216771.18 | 29-MAY-17:10 | 977223.71 | 01-DEC-16:30 |
Electricity:Zone:BASEMENT | 559.97 | 14115.26 | 01-JAN-00:10 | 25295.37 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16701.88 | 216771.18 | 29-MAY-17:10 | 977223.71 | 01-DEC-16:30 |
InteriorLights:Electricity | 2025.48 | 9514.02 | 01-JAN-10:40 | 198852.03 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:BASEMENT | 135.58 | 657.72 | 01-JAN-00:10 | 11837.83 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2025.48 | 9514.02 | 01-JAN-10:40 | 198852.03 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity | 2025.48 | 9514.02 | 01-JAN-10:40 | 198852.03 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 135.58 | 657.72 | 01-JAN-00:10 | 11837.83 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2025.48 | 9514.02 | 01-JAN-10:40 | 198852.03 | 28-NOV-16:30 |
Electricity:Zone:CORE_BOTTOM | 411.37 | 5043.91 | 01-JAN-00:10 | 27837.83 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4113.71 | 50438.97 | 01-JAN-00:10 | 278377.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1217.58 | 5906.80 | 01-JAN-00:10 | 106312.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1217.58 | 5906.80 | 01-JAN-00:10 | 106312.04 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 411.37 | 5043.90 | 01-JAN-00:10 | 27837.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 45.43 | 594.46 | 02-APR-17:10 | 3495.41 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.06 | 35.29 | 01-JAN-10:40 | 1334.85 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.06 | 35.29 | 01-JAN-10:40 | 1334.85 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 29.14 | 384.09 | 29-MAY-17:10 | 2252.57 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.70 | 22.74 | 01-JAN-08:00 | 860.23 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.70 | 22.74 | 01-JAN-08:00 | 860.23 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 45.12 | 594.47 | 02-APR-17:10 | 3495.47 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.75 | 35.29 | 01-JAN-08:10 | 1334.88 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.75 | 35.29 | 01-JAN-08:10 | 1334.88 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 29.22 | 383.09 | 12-MAR-17:10 | 2252.56 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.79 | 22.74 | 01-JAN-10:30 | 860.23 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.79 | 22.74 | 01-JAN-10:30 | 860.23 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 454.22 | 5944.59 | 02-APR-17:10 | 34954.06 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 90.56 | 352.88 | 01-JAN-10:30 | 13348.54 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 90.56 | 352.88 | 01-JAN-10:30 | 13348.54 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 291.34 | 3830.92 | 16-APR-17:10 | 22525.72 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 56.99 | 227.41 | 01-JAN-08:00 | 8602.31 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 56.99 | 227.41 | 01-JAN-08:00 | 8602.31 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 451.13 | 5944.68 | 02-APR-17:10 | 34954.68 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 87.47 | 352.89 | 01-JAN-08:10 | 13348.83 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 87.47 | 352.89 | 01-JAN-08:10 | 13348.83 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 292.17 | 3830.90 | 12-MAR-17:10 | 22525.63 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 57.82 | 227.41 | 01-JAN-10:20 | 8602.31 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 57.82 | 227.41 | 01-JAN-10:20 | 8602.31 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 45.42 | 594.46 | 02-APR-17:10 | 3495.41 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.06 | 35.29 | 01-JAN-10:30 | 1334.85 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.06 | 35.29 | 01-JAN-10:30 | 1334.85 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 29.13 | 383.09 | 16-APR-17:10 | 2252.57 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.70 | 22.74 | 01-JAN-08:00 | 860.23 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.70 | 22.74 | 01-JAN-08:00 | 860.23 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 45.11 | 594.47 | 02-APR-17:10 | 3495.47 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.75 | 35.29 | 01-JAN-08:10 | 1334.88 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.75 | 35.29 | 01-JAN-08:10 | 1334.88 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 29.22 | 383.09 | 12-MAR-17:10 | 2252.56 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.78 | 22.74 | 01-JAN-10:20 | 860.23 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.78 | 22.74 | 01-JAN-10:20 | 860.23 | 28-NOV-16:30 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7533.08 | 95093.58 | 01-JAN-00:10 | 382970.28 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 38.23 | 185.45 | 01-JAN-00:10 | 3337.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 38.23 | 185.45 | 01-JAN-00:10 | 3337.76 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.14 | 1964.44 | 01-JAN-00:10 | 8079.39 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1571.44 | 19644.38 | 01-JAN-00:10 | 80793.90 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 32.64 | 158.32 | 01-JAN-00:10 | 2849.68 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 32.64 | 158.32 | 01-JAN-00:10 | 2849.68 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.14 | 1964.44 | 01-JAN-00:10 | 8079.39 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2818.91 | 913.78 | 01-JAN-08:00 | 358624.35 | 05-SEP-07:50 |
HeatRejection:Electricity | 461.63 | 220.54 | 02-JAN-07:20 | 46841.99 | 11-APR-14:20 |
General:HeatRejection:Electricity | 461.63 | 220.54 | 02-JAN-07:20 | 46841.99 | 11-APR-14:20 |
Electricity:HVAC | 1916.86 | 9521.72 | 01-JAN-08:40 | 217367.10 | 21-JUL-15:40 |
ExteriorEquipment:Electricity | 3258.17 | 45245.36 | 01-JAN-00:10 | 185195.11 | 12-DEC-08:20 |
Transformer:ExteriorEquipment:Electricity | 54.48 | 979.82 | 01-JAN-00:10 | 3387.38 | 01-DEC-16:40 |
ElectricityPurchased:Facility | 24966.65 | 287053.15 | 01-JAN-04:40 | 1634688.54 | 11-AUG-15:20 |
ElectricityPurchased:Plant | 24966.65 | 287053.15 | 01-JAN-04:40 | 1634688.54 | 11-AUG-15:20 |
Cogeneration:ElectricityPurchased | 24966.65 | 287053.15 | 01-JAN-04:40 | 1634688.54 | 11-AUG-15:20 |
General:Cogeneration:ElectricityPurchased | 24966.65 | 287053.15 | 01-JAN-04:40 | 1634688.54 | 11-AUG-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 24966.65 | 287053.15 | 01-JAN-04:40 | 1634688.54 | 11-AUG-15:20 |
ElectricityNet:Plant | 24966.65 | 287053.15 | 01-JAN-04:40 | 1634688.54 | 11-AUG-15:20 |
Cogeneration:ElectricityNet | 24966.65 | 287053.15 | 01-JAN-04:40 | 1634688.54 | 11-AUG-15:20 |
General:Cogeneration:ElectricityNet | 24966.65 | 287053.15 | 01-JAN-04:40 | 1634688.54 | 11-AUG-15:20 |
Fans:Electricity | 1390.20 | 6517.00 | 01-JAN-20:20 | 186114.34 | 21-JUL-15:40 |
General:Fans:Electricity | 1390.20 | 6517.00 | 01-JAN-20:20 | 186114.34 | 21-JUL-15:40 |
ExteriorLights:Electricity | 325.31 | 0.00 | 01-JAN-07:30 | 37611.08 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 325.31 | 0.00 | 01-JAN-07:30 | 37611.08 | 01-JAN-06:10 |
ComputerHVAC:ExteriorEquipment:Electricity | 1349.07 | 17083.47 | 01-JAN-00:10 | 68333.87 | 31-MAR-23:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 2074.12 | 1212.23 | 02-JAN-07:10 | 275757.35 | 19-JUL-13:40 |
General:Cooling:Electricity | 2074.12 | 1212.23 | 02-JAN-07:10 | 275757.35 | 19-JUL-13:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 755.34 | 662.81 | 01-JAN-00:10 | 57021.32 | 05-OCT-15:50 |
General:Pumps:Electricity | 755.34 | 662.81 | 01-JAN-00:10 | 57021.32 | 05-OCT-15:50 |
WIRED_LTG_ELECTRICITY | 56.92 | 0.00 | 01-JAN-00:10 | 5587.74 | 28-NOV-16:40 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 654.13 | 5695.87 | 02-APR-16:10 | 436739.18 | 06-DEC-07:10 |
NaturalGas:Plant | 654.13 | 5695.87 | 02-APR-16:10 | 436739.18 | 06-DEC-07:10 |
Heating:NaturalGas | 56.64 | 0.00 | 01-JAN-00:10 | 408251.94 | 06-DEC-07:10 |
Boiler:Heating:NaturalGas | 56.64 | 0.00 | 01-JAN-00:10 | 408251.94 | 06-DEC-07:10 |
WaterSystems:NaturalGas | 597.49 | 5695.87 | 02-APR-16:10 | 75259.97 | 19-JAN-12:30 |
Water Heater:WaterSystems:NaturalGas | 597.49 | 5695.87 | 02-APR-16:10 | 75259.97 | 19-JAN-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 13686.00 | 5692.69 | 02-JAN-07:10 | 1867517.68 | 05-SEP-07:40 |
PlantLoopCoolingDemand:HVAC | 13686.00 | 5692.69 | 02-JAN-07:10 | 1867517.68 | 05-SEP-07:40 |
CoolingCoils:PlantLoopCoolingDemand | 13686.00 | 5692.69 | 02-JAN-07:10 | 1867517.68 | 05-SEP-07:40 |
DistrictCooling:Facility | 7196.12 | 87875.08 | 13-MAY-23:00 | 370732.56 | 28-AUG-14:00 |
DistrictCooling:HVAC | 7196.12 | 87875.08 | 13-MAY-23:00 | 370732.56 | 28-AUG-14:00 |
Cooling:DistrictCooling | 7196.12 | 87875.08 | 13-MAY-23:00 | 370732.56 | 28-AUG-14:00 |
General:Cooling:DistrictCooling | 7196.12 | 87875.08 | 13-MAY-23:00 | 370732.56 | 28-AUG-14:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 14556.46 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-12:00 |
Water:Plant | 14556.46 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-12:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 14556.46 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-12:00 |
MainsWater:Plant | 14556.46 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-12:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 12276.29 | 0.00 | 01-JAN-00:10 | 0.00 | 31-MAY-16:00 |
General:HeatRejection:Water | 12276.29 | 0.00 | 01-JAN-00:10 | 0.00 | 31-MAY-16:00 |
HeatRejection:MainsWater | 12276.29 | 0.00 | 01-JAN-00:10 | 0.00 | 31-MAY-16:00 |
General:HeatRejection:MainsWater | 12276.29 | 0.00 | 01-JAN-00:10 | 0.00 | 31-MAY-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 68841.54 | 99592.49 | 01-JAN-06:00 | 8682247.96 | 05-SEP-07:50 |
EnergyTransfer:Building | 20388.57 | 90886.69 | 01-JAN-08:40 | 1542446.39 | 14-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 662.70 | 0.00 | 01-JAN-00:40 | 70627.64 | 10-OCT-05:30 |
Heating:EnergyTransfer | 33.39 | 0.00 | 01-JAN-17:20 | 172196.40 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 5.77 | 0.00 | 01-JAN-00:40 | 21176.28 | 26-AUG-16:10 |
General:Heating:EnergyTransfer | 33.39 | 0.00 | 01-JAN-17:20 | 172196.40 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 5.77 | 0.00 | 01-JAN-00:40 | 21176.28 | 26-AUG-16:10 |
Cooling:EnergyTransfer | 20355.18 | 90328.70 | 01-JAN-08:40 | 1542446.39 | 14-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 656.94 | 0.00 | 01-JAN-00:10 | 70627.64 | 10-OCT-05:30 |
General:Cooling:EnergyTransfer | 20355.18 | 90328.70 | 01-JAN-08:40 | 1542446.39 | 14-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 656.94 | 0.00 | 01-JAN-00:10 | 70627.64 | 10-OCT-05:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 664.38 | 0.00 | 01-JAN-00:10 | 52250.16 | 28-AUG-07:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 664.38 | 0.00 | 01-JAN-00:10 | 52250.16 | 28-AUG-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 664.38 | 0.00 | 01-JAN-00:10 | 52250.16 | 28-AUG-07:20 |
EnergyTransfer:Zone:CORE_MID | 4851.56 | 0.00 | 01-JAN-00:10 | 389101.58 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4851.56 | 0.00 | 01-JAN-00:10 | 389101.58 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4851.56 | 0.00 | 01-JAN-00:10 | 389101.58 | 05-SEP-13:10 |
EnergyTransfer:Zone:CORE_TOP | 481.61 | 0.00 | 01-JAN-00:10 | 47164.05 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.40 | 0.00 | 01-JAN-00:10 | 34749.57 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.40 | 0.00 | 01-JAN-00:10 | 34749.57 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 481.20 | 0.00 | 01-JAN-00:10 | 47164.05 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 481.20 | 0.00 | 01-JAN-00:10 | 47164.05 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 92.98 | 0.00 | 01-JAN-00:10 | 10499.51 | 28-AUG-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 92.98 | 0.00 | 01-JAN-00:10 | 10499.51 | 28-AUG-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 92.98 | 0.00 | 01-JAN-00:10 | 10499.51 | 28-AUG-12:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 83.13 | 0.00 | 01-JAN-00:10 | 11466.06 | 19-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 83.13 | 0.00 | 01-JAN-00:10 | 11466.06 | 19-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 83.13 | 0.00 | 01-JAN-00:10 | 11466.06 | 19-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 131.01 | 0.00 | 01-JAN-00:10 | 15412.38 | 02-OCT-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 131.01 | 0.00 | 01-JAN-00:10 | 15412.38 | 02-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 131.01 | 0.00 | 01-JAN-00:10 | 15412.38 | 02-OCT-12:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 121.93 | 0.00 | 01-JAN-00:10 | 14802.52 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 121.93 | 0.00 | 01-JAN-00:10 | 14802.52 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 121.93 | 0.00 | 01-JAN-00:10 | 14802.52 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 730.55 | 0.00 | 01-JAN-00:10 | 100727.48 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1.74 | 0.00 | 01-JAN-00:10 | 48463.40 | 06-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1.74 | 0.00 | 01-JAN-00:10 | 48463.40 | 06-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 728.81 | 0.00 | 01-JAN-00:10 | 100727.48 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 728.81 | 0.00 | 01-JAN-00:10 | 100727.48 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 748.09 | 0.00 | 01-JAN-00:10 | 115542.89 | 19-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.59 | 0.00 | 01-JAN-00:10 | 26713.12 | 06-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.59 | 0.00 | 01-JAN-00:10 | 26713.12 | 06-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 747.50 | 0.00 | 01-JAN-00:10 | 115542.89 | 19-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 747.50 | 0.00 | 01-JAN-00:10 | 115542.89 | 19-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1139.13 | 0.00 | 01-JAN-00:10 | 148684.96 | 28-SEP-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.05 | 0.00 | 01-JAN-00:10 | 20106.76 | 07-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.05 | 0.00 | 01-JAN-00:10 | 20106.76 | 07-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1139.08 | 0.00 | 01-JAN-00:10 | 148684.96 | 28-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1139.08 | 0.00 | 01-JAN-00:10 | 148684.96 | 28-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 779.55 | 0.00 | 01-JAN-00:10 | 126472.15 | 29-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.21 | 0.00 | 01-JAN-00:10 | 20012.92 | 07-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.21 | 0.00 | 01-JAN-00:10 | 20012.92 | 07-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 779.33 | 0.00 | 01-JAN-00:10 | 126472.15 | 29-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 779.33 | 0.00 | 01-JAN-00:10 | 126472.15 | 29-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 77.46 | 0.00 | 01-JAN-00:10 | 12031.46 | 02-JAN-06:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.41 | 0.00 | 01-JAN-00:10 | 12031.46 | 02-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.41 | 0.00 | 01-JAN-00:10 | 12031.46 | 02-JAN-06:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 75.05 | 0.00 | 01-JAN-00:10 | 11675.19 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 75.05 | 0.00 | 01-JAN-00:10 | 11675.19 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 78.15 | 0.00 | 01-JAN-00:10 | 12080.17 | 29-JUN-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.88 | 0.00 | 01-JAN-00:10 | 6967.27 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.88 | 0.00 | 01-JAN-00:10 | 6967.27 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 77.27 | 0.00 | 01-JAN-00:10 | 12080.17 | 29-JUN-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 77.27 | 0.00 | 01-JAN-00:10 | 12080.17 | 29-JUN-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 114.32 | 0.00 | 01-JAN-00:10 | 16557.53 | 28-SEP-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.55 | 0.00 | 01-JAN-00:10 | 7044.98 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.55 | 0.00 | 01-JAN-00:10 | 7044.98 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 113.77 | 0.00 | 01-JAN-00:10 | 16557.53 | 28-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 113.77 | 0.00 | 01-JAN-00:10 | 16557.53 | 28-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 80.90 | 0.00 | 01-JAN-00:10 | 13719.89 | 29-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.48 | 0.00 | 01-JAN-00:10 | 5084.56 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.48 | 0.00 | 01-JAN-00:10 | 5084.56 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 80.43 | 0.00 | 01-JAN-00:10 | 13719.89 | 29-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 80.43 | 0.00 | 01-JAN-00:10 | 13719.89 | 29-JUN-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 88.04 | 0.00 | 01-JAN-00:10 | 12015.43 | 28-AUG-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.82 | 0.00 | 01-JAN-00:10 | 3528.05 | 10-DEC-11:00 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.82 | 0.00 | 01-JAN-00:10 | 3528.05 | 10-DEC-11:00 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 87.22 | 0.00 | 01-JAN-00:10 | 12015.43 | 28-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 87.22 | 0.00 | 01-JAN-00:10 | 12015.43 | 28-AUG-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 622.01 | 0.00 | 01-JAN-00:10 | 77119.55 | 19-JUN-15:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.05 | 0.00 | 01-JAN-00:10 | 30808.37 | 02-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.05 | 0.00 | 01-JAN-00:10 | 30808.37 | 02-JAN-16:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 611.95 | 0.00 | 01-JAN-00:10 | 77119.55 | 19-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 611.95 | 0.00 | 01-JAN-00:10 | 77119.55 | 19-JUN-15:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 115.50 | 0.00 | 01-JAN-00:10 | 22695.43 | 28-JUN-14:40 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 9.37 | 0.00 | 01-JAN-00:10 | 12424.06 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 9.37 | 0.00 | 01-JAN-00:10 | 12424.06 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 106.13 | 0.00 | 01-JAN-00:10 | 22695.43 | 28-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 106.13 | 0.00 | 01-JAN-00:10 | 22695.43 | 28-JUN-14:40 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.94 | 1173.22 | 21-JAN-08:00 | 7781.17 | 26-DEC-16:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.94 | 1173.22 | 21-JAN-08:00 | 7781.17 | 26-DEC-16:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.94 | 1173.22 | 21-JAN-08:00 | 7781.17 | 26-DEC-16:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1289.20 | 309.02 | 01-JAN-08:30 | 73691.94 | 06-AUG-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1289.20 | 309.02 | 01-JAN-08:30 | 73691.94 | 06-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1289.20 | 309.02 | 01-JAN-08:30 | 73691.94 | 06-AUG-18:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 123.90 | 5.66 | 16-JAN-09:40 | 7519.00 | 06-AUG-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.07 | 0.00 | 01-JAN-16:50 | 565.58 | 01-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.07 | 0.00 | 01-JAN-16:50 | 565.58 | 01-JAN-05:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 123.83 | 0.00 | 01-JAN-00:10 | 7519.00 | 06-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 123.83 | 0.00 | 01-JAN-00:10 | 7519.00 | 06-AUG-18:20 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7171.56 | 87875.08 | 13-MAY-23:00 | 368033.17 | 14-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7171.56 | 87875.08 | 13-MAY-23:00 | 368033.17 | 14-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7171.56 | 87875.08 | 13-MAY-23:00 | 368033.17 | 14-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 362.75 | 0.00 | 01-JAN-00:10 | 334380.89 | 06-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 323.62 | 0.00 | 01-JAN-00:10 | 42566.01 | 25-JAN-12:30 |
WaterSystems:PlantLoopHeatingDemand | 323.62 | 0.00 | 01-JAN-00:10 | 42566.01 | 25-JAN-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 323.62 | 0.00 | 01-JAN-00:10 | 42566.01 | 25-JAN-12:30 |
EnergyTransfer:HVAC | 13252.94 | 7636.82 | 01-JAN-08:40 | 1860196.41 | 05-SEP-07:40 |
HeatingCoils:EnergyTransfer | 39.13 | 0.00 | 01-JAN-00:10 | 321032.58 | 06-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 39.13 | 0.00 | 01-JAN-00:10 | 321032.58 | 06-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 39.13 | 0.00 | 01-JAN-00:10 | 321032.58 | 06-DEC-07:10 |
CoolingCoils:EnergyTransfer | 13213.81 | 4480.46 | 02-JAN-07:10 | 1860196.41 | 05-SEP-07:40 |
DistrictHeating:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 12.65 | 01-FEB-00:40 |
DistrictHeating:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 12.65 | 01-FEB-00:40 |
Heating:DistrictHeating | 0.00 | 0.00 | 01-JAN-00:10 | 12.65 | 01-FEB-00:40 |
General:Heating:DistrictHeating | 0.00 | 0.00 | 01-JAN-00:10 | 12.65 | 01-FEB-00:40 |
EnergyTransfer:Plant | 35200.02 | 0.00 | 01-JAN-00:10 | 5806619.81 | 05-SEP-07:40 |
LoopToLoop:EnergyTransfer | 11831.90 | -30.75 | 01-JAN-15:10 | 1833964.29 | 05-SEP-07:40 |
WaterSystems:EnergyTransfer | 323.62 | 0.00 | 01-JAN-00:10 | 42566.01 | 25-JAN-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 323.62 | 0.00 | 01-JAN-00:10 | 42566.01 | 25-JAN-12:30 |
Boilers:EnergyTransfer | 38.66 | 0.00 | 01-JAN-00:10 | 332147.51 | 06-DEC-07:10 |
Chillers:EnergyTransfer | 10701.95 | 0.00 | 01-JAN-00:10 | 1847343.12 | 05-SEP-07:40 |
HeatRejection:EnergyTransfer | 12303.90 | 0.00 | 01-JAN-00:10 | 2106526.32 | 05-SEP-07:40 |
General:HeatRejection:EnergyTransfer | 12303.90 | 0.00 | 01-JAN-00:10 | 2106526.32 | 05-SEP-07:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 5.768 | -656.935 | 0.000 | 0.000 | 92.598 | 135.577 | 424.397 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -1.405 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -664.381 | 0.000 | 0.000 | 83.412 | 121.758 | 289.614 | 0.000 | 0.000 | 0.000 | 169.598 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 0.000 | -4851.550 | 0.000 | 0.000 | 836.955 | 1217.578 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.010 | 0.000 | 0.000 | 0.000 | 0.000 | -99.110 |
CORE_TOP | 0.000 | 0.000 | 0.404 | -481.199 | 0.000 | 0.000 | 85.056 | 121.758 | 289.613 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -15.632 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -92.977 | 0.000 | 0.000 | 10.541 | 9.062 | 36.365 | 32.755 | 0.000 | 0.201 | 35.142 | 0.000 | -30.581 | 0.000 | -0.508 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -83.130 | 0.000 | 0.000 | 6.777 | 5.703 | 23.435 | 58.039 | 0.000 | 0.135 | 7.981 | 0.000 | -18.602 | 0.000 | -0.338 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -131.012 | 0.000 | 0.000 | 10.483 | 8.750 | 36.366 | 95.256 | 0.000 | 0.195 | 10.151 | 0.000 | -29.650 | 0.000 | -0.538 | -0.002 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -121.932 | 0.000 | 0.000 | 6.741 | 5.787 | 23.435 | 54.461 | 0.000 | 0.123 | 55.112 | 0.000 | -23.334 | 0.000 | -0.393 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 1.741 | -728.805 | 0.000 | 0.000 | 108.369 | 90.563 | 363.654 | 340.707 | 0.000 | 4.679 | 107.173 | 0.000 | -277.341 | 0.000 | -10.740 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.586 | -747.502 | 0.000 | 0.000 | 50.425 | 56.985 | 234.352 | 580.436 | 0.000 | 2.993 | 7.766 | 0.000 | -178.403 | 0.000 | -7.639 | -0.005 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.048 | -1139.060 | 0.000 | 0.000 | 105.167 | 87.471 | 363.660 | 952.410 | 0.000 | 4.448 | 0.012 | 0.000 | -290.890 | 0.000 | -12.487 | -70.768 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.213 | -779.318 | 0.000 | 0.000 | 69.124 | 57.815 | 234.351 | 556.261 | 0.000 | 2.881 | 69.684 | 0.000 | -202.968 | 0.000 | -8.043 | -0.002 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 2.410 | -75.048 | 0.000 | 0.000 | 11.031 | 9.056 | 36.365 | 34.235 | 0.000 | 0.561 | 8.459 | 0.000 | -25.848 | 0.000 | -1.222 | -0.002 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.884 | -77.265 | 0.000 | 0.000 | 6.940 | 5.699 | 23.435 | 58.150 | 0.000 | 0.359 | 0.000 | 0.000 | -16.871 | 0.000 | -0.882 | -0.449 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.548 | -113.768 | 0.000 | 0.000 | 10.631 | 8.747 | 36.366 | 95.288 | 0.000 | 0.534 | 0.001 | 0.000 | -27.682 | 0.000 | -1.459 | -9.204 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.475 | -80.424 | 0.000 | 0.000 | 7.025 | 5.782 | 23.435 | 55.619 | 0.000 | 0.352 | 7.912 | 0.000 | -19.239 | 0.000 | -0.937 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -140.941 | 0.000 | 0.000 | 0.943 | 3.264 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -17.146 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1289.196 | 0.000 | 0.000 | 9.427 | 32.637 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -291.674 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.071 | -123.826 | 0.000 | 0.000 | 0.944 | 3.264 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -34.333 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | -7171.555 | 0.000 | 0.000 | 0.000 | 0.000 | 20.569 | 38.227 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -382.098 |
GROUNDFLOOR_PLENUM | 0.818 | -87.222 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.377 | 87.140 | 0.000 | 0.000 | 0.000 | -1.114 | 0.000 |
MIDFLOOR_PLENUM | 10.054 | -611.952 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.925 | 614.019 | 0.000 | 0.000 | 0.000 | -19.045 | -0.006 |
TOPFLOOR_PLENUM | 9.369 | -106.125 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.701 | 97.980 | 0.000 | 0.000 | 0.000 | -1.926 | -0.000 |
Total Facility | 20.242 | -7976.854 | 13.147 | -12378.269 | 0.000 | 0.000 | 1533.157 | 2025.481 | 14676.396 | 2913.618 | 0.000 | 25.464 | 1278.144 | 0.000 | -1141.410 | 0.000 | -67.270 | -921.839 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 23-OCT-03:02 | 0.00 | 0.00 | 0.00 | -100145.38 | 0.00 | 0.00 | 0.00 | 657.72 | 13457.54 | 0.00 | 0.00 | 0.00 | 86030.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 23-OCT-03:02 | 0.00 | 0.00 | 0.00 | -86715.07 | 0.00 | 0.00 | 0.00 | 590.68 | 5937.65 | 0.00 | 0.00 | 0.00 | 80186.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 13-NOV-05:03 | 0.00 | 0.00 | 0.00 | -747468.81 | 0.00 | 0.00 | 0.00 | 11812.12 | 59376.23 | 0.00 | 0.00 | 0.00 | 676280.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 11-SEP-03:02 | 0.00 | 0.00 | 0.00 | -75387.20 | 0.00 | 0.00 | 0.00 | 590.68 | 5937.62 | 0.00 | 0.00 | 0.00 | 68858.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-JUL-17:41 | 0.00 | 0.00 | 0.00 | -17170.65 | 0.00 | 0.00 | 0.00 | 35.29 | 559.17 | 4925.67 | 0.00 | 121.40 | 11529.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 27-AUG-09:02 | 0.00 | 0.00 | 0.00 | -16795.03 | 0.00 | 0.00 | 22.88 | 22.74 | 464.11 | 11090.25 | 0.00 | 16.71 | 5178.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 03-DEC-13:22 | 0.00 | 0.00 | 0.00 | -19647.96 | 0.00 | 0.00 | 37.36 | 35.29 | 720.19 | 17478.56 | 0.00 | 0.00 | 1416.70 | 0.00 | -0.00 | 0.00 | -40.15 | 0.00 |
PERIMETER_BOT_ZN_4 | 27-AUG-16:21 | 0.00 | 0.00 | 0.00 | -24925.23 | 0.00 | 0.00 | 16.20 | 22.74 | 464.11 | 12574.89 | 0.00 | 46.63 | 11800.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JUL-17:41 | 0.00 | 0.00 | 0.00 | -156553.60 | 0.00 | 0.00 | 0.00 | 352.88 | 5591.71 | 52236.47 | 0.00 | 2371.98 | 96000.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUN-08:32 | 0.00 | 0.00 | 0.00 | -177569.86 | 0.00 | 0.00 | 221.88 | 227.41 | 4641.14 | 113761.61 | 0.00 | 109.75 | 58608.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-13:22 | 0.00 | 0.00 | 0.00 | -195316.78 | 0.00 | 0.00 | 347.62 | 352.89 | 7201.95 | 148638.78 | 0.00 | 189.06 | 38586.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 30-JUL-16:51 | 0.00 | 0.00 | 0.00 | -203264.28 | 0.00 | 0.00 | 190.91 | 227.41 | 4641.11 | 124626.61 | 0.00 | 1266.11 | 72312.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 04-JUN-16:01 | 0.00 | 0.00 | 0.00 | -19087.56 | 0.00 | 0.00 | 39.27 | 35.29 | 720.18 | 3987.51 | 0.00 | 223.80 | 14081.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUN-08:42 | 0.00 | 0.00 | 0.00 | -18539.86 | 0.00 | 0.00 | 21.63 | 22.74 | 464.11 | 11209.92 | 0.00 | 12.02 | 6809.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-14:02 | 0.00 | 0.00 | 0.00 | -22042.62 | 0.00 | 0.00 | 34.62 | 35.29 | 720.19 | 13415.55 | 0.00 | 18.09 | 7818.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 30-JUL-16:51 | 0.00 | 0.00 | 0.00 | -23004.82 | 0.00 | 0.00 | 17.32 | 22.74 | 464.11 | 12343.23 | 0.00 | 147.70 | 10009.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 26-DEC-16:50 | 0.00 | 0.00 | 0.00 | -7781.55 | 0.00 | 0.00 | 99.62 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -397.46 |
DATACENTER_MID_ZN_6 | 06-AUG-18:20 | 0.00 | 0.00 | 0.00 | -73707.43 | 0.00 | 0.00 | 0.00 | 158.32 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4395.12 |
DATACENTER_TOP_ZN_6 | 06-AUG-18:20 | 0.00 | 0.00 | 0.00 | -7520.73 | 0.00 | 0.00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -289.52 |
DATACENTER_BASEMENT_ZN_6 | 14-AUG-16:00 | 0.00 | -368033.17 | 0.00 | 0.00 | 0.00 | 0.00 | 2183.10 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17120.21 |
GROUNDFLOOR_PLENUM | 14-AUG-05:15 | 0.00 | -15238.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 15238.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-SEP-05:02 | 0.00 | -96358.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96399.75 | 0.00 | -0.00 | 0.00 | -41.51 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-14:40 | 0.00 | -22696.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.15 | 22542.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-AUG-05:03 | 0.00 | -408471.67 | 0.00 | -1504085.09 | 0.00 | 0.00 | 15735.38 | 22094.05 | 616289.16 | 0.00 | 0.00 | 0.00 | 1292766.11 | 0.00 | -34111.41 | 0.00 | -216.53 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 26-AUG-16:02 | 0.00 | 0.00 | 22921.64 | 0.00 | 0.00 | 0.00 | 484.19 | 657.72 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -37521.10 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-05:01 | 0.00 | 0.00 | 64086.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1181.21 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -71204.88 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-05:01 | 0.00 | 0.00 | 114391.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1483.13 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31096.96 | 0.00 | -686.39 | -91546.62 |
PERIMETER_MID_ZN_2 | 07-DEC-06:01 | 0.00 | 0.00 | 94559.71 | 0.00 | 0.00 | 0.00 | 941.47 | 955.79 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -28579.25 | 0.00 | -442.68 | -73623.22 |
PERIMETER_MID_ZN_1 | 07-DEC-06:01 | 0.00 | 0.00 | 117059.54 | 0.00 | 0.00 | 0.00 | 1445.84 | 1483.16 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44381.05 | 0.00 | -674.16 | -84535.92 |
PERIMETER_MID_ZN_4 | 07-DEC-06:01 | 0.00 | 0.00 | 88705.04 | 0.00 | 0.00 | 0.00 | 941.48 | 955.79 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -28306.60 | 0.00 | -443.01 | -68040.84 |
PERIMETER_TOP_ZN_3 | 02-JAN-04:01 | 0.00 | 0.00 | 15379.13 | 0.00 | 0.00 | 0.00 | 0.00 | 74.17 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2393.81 | 0.00 | -161.28 | -13643.77 |
PERIMETER_TOP_ZN_2 | 02-JAN-04:01 | 0.00 | 0.00 | 13401.66 | 0.00 | 0.00 | 0.00 | 0.00 | 47.80 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1699.64 | 0.00 | -116.17 | -12114.12 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:01 | 0.00 | 0.00 | 15070.44 | 0.00 | 0.00 | 0.00 | 0.00 | 148.32 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3000.00 | 0.00 | -81.29 | -12883.05 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 12794.65 | 0.00 | 0.00 | 0.00 | 0.00 | 95.58 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1940.63 | 0.00 | -54.62 | -11375.45 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 01-JAN-05:25 | 0.00 | 0.00 | 570.16 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2534.60 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 18-DEC-04:02 | 9825.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -211.38 | -9614.40 |
MIDFLOOR_PLENUM | 04-JUN-16:31 | 65489.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3154.51 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -68643.64 |
TOPFLOOR_PLENUM | 01-MAY-05:02 | 14837.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -62.46 | -14775.38 |
Total Facility | 07-DEC-06:01 | -805739.83 | 401878.10 | 518277.15 | -401878.10 | 0.00 | 0.00 | 18938.70 | 22094.05 | 616289.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -171428.23 | 0.00 | -3877.55 | -194553.45 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.4727 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.6546 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 98.2138 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 90.0076 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.3143 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.9676 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.4774 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.4774 | 0.2191 | 1.0000 | Not calculated | 1.2002 | 0.2191 | ||
AIRLOOP DATACENTER BOT | 0.5067 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5067 | 0.0309 | 1.0000 | Not calculated | 0.0156 | 0.0309 | ||
AIRLOOP DATACENTER MID | 4.8202 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.8202 | 0.0324 | 1.0000 | Not calculated | 0.1563 | 0.0324 | ||
AIRLOOP DATACENTER TOP | 0.4913 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4913 | 0.0318 | 1.0000 | Not calculated | 0.0156 | 0.0318 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.2363 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.8843 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 49.1069 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 27.9776 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.1572 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.9100 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.4774 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.4774 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2191 | ||
AIRLOOP DATACENTER BOT | 0.5067 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5067 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0309 | ||
AIRLOOP DATACENTER MID | 4.8202 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.8202 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0324 | ||
AIRLOOP DATACENTER TOP | 0.4913 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4913 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0318 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.002360 | 149.6021 | 0.000305 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.002360 | 1.9486 | 0.000305 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.002360 | 19.4861 | 0.000305 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.002360 | 1.9486 | 0.000305 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.002360 | 149.60 | 0.000305 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BOT | 0.002360 | 1.95 | 0.000305 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.002360 | 19.49 | 0.000305 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.002360 | 1.95 | 0.000305 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.4774 | 5.4774 | 5.4774 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8988 | 5.8988 | 1.9348 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 55.4502 | 55.4502 | 18.9085 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5699 | 5.5699 | 1.9495 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0676 | 1.0676 | 0.2423 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0049 | 1.0049 | 0.2010 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1830 | 1.1830 | 0.2425 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3184 | 1.3184 | 0.2637 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.0370 | 10.0370 | 2.3788 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.3929 | 10.3929 | 2.0786 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.1507 | 11.1507 | 2.3751 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.1830 | 11.1830 | 2.2366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1685 | 1.1685 | 0.2454 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0753 | 1.0753 | 0.2151 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2699 | 1.2699 | 0.2540 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2308 | 1.2308 | 0.2462 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5067 | 0.5067 | 0.5067 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8202 | 4.8202 | 4.8202 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4913 | 0.4913 | 0.4913 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.4727 | 9.6546 | 10.4727 | 2.8843 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 98.2138 | 90.0076 | 98.2138 | 27.9776 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.3143 | 9.9676 | 10.3143 | 2.9100 | 0.0000 | 1.0000 |
CAV_BAS | 5.4774 | 5.4774 | 5.4774 | 5.4774 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5067 | 0.5067 | 0.5067 | 0.5067 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.8202 | 4.8202 | 4.8202 | 4.8202 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4913 | 0.4913 | 0.4913 | 0.4913 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.4774 | 5.4774 | 5.4774 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9494 | 2.9494 | 1.9348 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 27.7251 | 27.7251 | 18.9085 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7849 | 2.7849 | 1.9495 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5338 | 0.5338 | 0.2423 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5024 | 0.5024 | 0.2010 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5915 | 0.5915 | 0.2425 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6592 | 0.6592 | 0.2637 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0185 | 5.0185 | 2.3788 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1965 | 5.1965 | 2.0786 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5753 | 5.5753 | 2.3751 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5915 | 5.5915 | 2.2366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5842 | 0.5842 | 0.2454 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5377 | 0.5377 | 0.2151 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6349 | 0.6349 | 0.2540 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6154 | 0.6154 | 0.2462 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5067 | 0.5067 | 0.5067 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8202 | 4.8202 | 4.8202 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4913 | 0.4913 | 0.4913 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.2363 | 2.8843 | 2.8843 | 2.8843 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 49.1069 | 27.9776 | 27.9776 | 27.9776 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.1572 | 2.9100 | 2.9100 | 2.9100 | 0.0000 | 1.0000 |
CAV_BAS | 5.4774 | 5.4774 | 5.4774 | 5.4774 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5067 | 0.5067 | 0.5067 | 0.5067 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.8202 | 4.8202 | 4.8202 | 4.8202 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4913 | 0.4913 | 0.4913 | 0.4913 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 560.00 |
Number of hours not met | 560.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 |
Heating -- Boiler | 0.00 | 0.00 | 56.64 | 408251.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2074.12 | 275757.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7196.12 | 370732.56 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2025.48 | 198852.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 325.31 | 37611.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.48 | 3387.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ComputerHVAC | 1349.07 | 68333.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 1390.20 | 186114.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 755.34 | 57021.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 461.63 | 46841.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 597.49 | 75259.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 24966.65 |
Natural Gas | 0.00 | 654.13 |
Additional | 0.00 | 7196.12 |
Total | 14676.40 | 32816.90 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 43.73 |
Space Heating | 0.00 |
Space Cooling | 44.78 |
Fans (All) | 30.01 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 539.00 |
Subtotal | 539.00 |
Natural Gas [MJ/m2] | |
Space Heating | 1.22 |
Service Water Heating | 12.90 |
Miscellaneous (All) | 14.12 |
Subtotal | 14.12 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.17 |
Space Heating | 0.17 |
Space Cooling | 28.25 |
Fans (All) | 4.24 |
Service Water Heating | 1.82 |
Receptacle Equipment | 44.72 |
Miscellaneous | 14.63 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2362. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8418.50 | 341.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8737.17 | 22.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8746.83 | 13.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8725.83 | 34.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8693.33 | 66.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8667.17 | 92.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8396.50 | 363.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8721.67 | 38.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8622.67 | 137.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8614.17 | 145.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8481.50 | 278.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8689.67 | 70.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8582.50 | 177.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8583.67 | 176.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8496.17 | 263.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7922.50 | 837.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7921.33 | 838.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7943.33 | 816.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 250.83 | 8509.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8576.50 | 183.50 | 0.00 | 0.00 | 0.00 |
Min | 250.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 8509.17 | 0.00 | 0.00 | 0.00 |
Average | 8176.93 | 583.07 | 0.00 | 0.00 | 0.00 |
Sum | 188069.33 | 13410.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367483.17 | 1132.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330779.00 | 34.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330800.00 | 13.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330791.00 | 22.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1821.33 | 446.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1812.17 | 455.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1821.17 | 446.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 267.33 | 103127.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367483.17 | 103127.67 | 0.00 | 0.00 | 0.00 |
Average | 75740.18 | 4594.73 | 0.00 | 0.00 | 0.00 |
Sum | 1742024.17 | 105678.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8036.33 | 723.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8460.67 | 299.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8482.67 | 277.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8496.50 | 263.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8328.17 | 431.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8413.67 | 346.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8283.67 | 476.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8113.67 | 646.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8340.67 | 419.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8279.50 | 480.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8259.17 | 500.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8226.00 | 534.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8288.33 | 471.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8253.67 | 506.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8240.33 | 519.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8236.33 | 523.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8479.33 | 280.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8456.00 | 304.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8471.67 | 288.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8223.00 | 537.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8342.50 | 417.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7844.17 | 915.83 | 0.00 | 0.00 | 0.00 |
Min | 7844.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 915.83 | 0.00 | 0.00 | 0.00 |
Average | 8318.09 | 441.91 | 0.00 | 0.00 | 0.00 |
Sum | 191316.00 | 10164.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 365976.33 | 2639.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330184.00 | 629.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330324.00 | 489.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 329817.17 | 995.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38924.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2076.17 | 191.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2058.00 | 210.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2074.17 | 193.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 103395.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 365976.33 | 2639.67 | 0.00 | 0.00 | 0.00 |
Average | 80102.32 | 232.59 | 0.00 | 0.00 | 0.00 |
Sum | 1842353.33 | 5349.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:53
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.517444E+11 | 98398.74 | 02-JAN-04:01 | 4.83 | 1.48 | 0.567558E+10 | 7499.15 | 06-JAN-14:20 | 23.67 | 10.50 |
February | 0.428440E+11 | 96511.18 | 21-FEB-04:03 | 9.83 | 8.78 | 0.514408E+10 | 7499.32 | 15-FEB-14:00 | 9.83 | 8.78 |
March | 0.502769E+11 | 97543.52 | 20-MAR-03:02 | 12.62 | 8.05 | 0.613882E+10 | 7499.13 | 09-MAR-14:30 | 12.62 | 8.05 |
April | 0.498195E+11 | 92654.98 | 03-APR-03:02 | 16.67 | 5.66 | 0.545706E+10 | 7499.04 | 06-APR-09:20 | 24.67 | 12.12 |
May | 0.507571E+11 | 93785.47 | 01-MAY-03:03 | 13.58 | 4.86 | 0.590776E+10 | 7498.99 | 11-MAY-09:20 | 26.33 | 13.51 |
June | 0.525116E+11 | 89787.91 | 12-JUN-03:02 | 20.83 | 10.48 | 0.588836E+10 | 7499.07 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.575763E+11 | 88160.68 | 05-JUL-03:02 | 23.00 | 11.69 | 0.548201E+10 | 7499.23 | 21-JUL-09:09 | 31.17 | 20.71 |
August | 0.644806E+11 | 87571.94 | 27-AUG-16:40 | 40.00 | 18.00 | 0.614652E+10 | 7498.96 | 15-AUG-09:09 | 40.00 | 18.00 |
September | 0.600016E+11 | 88002.73 | 18-SEP-03:02 | 26.00 | 12.63 | 0.546274E+10 | 7499.02 | 22-SEP-09:30 | 24.40 | 17.34 |
October | 0.615587E+11 | 100151.09 | 23-OCT-03:02 | 11.83 | 9.72 | 0.568074E+10 | 7551.17 | 10-OCT-09:09 | 11.83 | 9.72 |
November | 0.588062E+11 | 98254.71 | 27-NOV-04:03 | 8.78 | 4.41 | 0.562468E+10 | 7542.77 | 13-NOV-10:30 | 8.78 | 4.41 |
December | 0.565589E+11 | 99347.34 | 18-DEC-04:02 | 4.00 | 0.69 | 0.548100E+10 | 7498.93 | 13-DEC-10:20 | 4.00 | 0.69 |
Annual Sum or Average | 0.656936E+12 | 0.680894E+11 | ||||||||
Minimum of Months | 0.428440E+11 | 87571.94 | 4.00 | 0.69 | 0.514408E+10 | 7498.93 | 4.00 | 0.69 | ||
Maximum of Months | 0.644806E+11 | 100151.09 | 40.00 | 18.00 | 0.614652E+10 | 7551.17 | 40.00 | 20.71 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.437352E+11 | 81835.26 | 02-JAN-04:01 | 4.83 | 1.48 | 0.507567E+10 | 6734.79 | 23-JAN-14:09 | 21.83 | 11.36 |
February | 0.385296E+11 | 81851.39 | 21-FEB-04:03 | 9.83 | 8.78 | 0.460592E+10 | 6735.05 | 15-FEB-14:00 | 9.83 | 8.78 |
March | 0.510787E+11 | 81975.55 | 06-MAR-04:03 | 13.20 | 12.40 | 0.550082E+10 | 6734.83 | 17-MAR-09:00 | 21.60 | 14.25 |
April | 0.622552E+11 | 76221.92 | 21-APR-03:02 | 9.67 | 1.37 | 0.487759E+10 | 6734.78 | 03-APR-09:30 | 9.67 | 1.37 |
May | 0.562682E+11 | 76897.79 | 02-MAY-03:02 | 20.00 | 8.81 | 0.528372E+10 | 6734.75 | 22-MAY-09:00 | 25.00 | 9.85 |
June | 0.634804E+11 | 71575.09 | 26-JUN-05:02 | 22.17 | 10.13 | 0.526484E+10 | 6734.75 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.665146E+11 | 74158.74 | 24-JUL-05:03 | 24.83 | 18.79 | 0.489379E+10 | 6734.85 | 05-JUL-09:09 | 24.83 | 18.79 |
August | 0.714528E+11 | 79646.87 | 14-AUG-05:05 | 26.00 | 16.58 | 0.549667E+10 | 6734.92 | 28-AUG-09:20 | 32.00 | 20.57 |
September | 0.561668E+11 | 79762.42 | 11-SEP-05:04 | 22.52 | 18.19 | 0.488249E+10 | 6734.74 | 15-SEP-09:09 | 25.45 | 16.44 |
October | 0.549093E+11 | 86729.65 | 23-OCT-03:02 | 11.83 | 9.72 | 0.508023E+10 | 6734.79 | 03-OCT-13:39 | 11.83 | 9.72 |
November | 0.508228E+11 | 86310.74 | 13-NOV-04:02 | 17.00 | 17.00 | 0.503152E+10 | 6734.97 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.491676E+11 | 84391.36 | 26-DEC-04:02 | 8.00 | 2.80 | 0.490364E+10 | 6734.71 | 13-DEC-10:09 | 8.00 | 2.80 |
Annual Sum or Average | 0.664381E+12 | 0.608969E+11 | ||||||||
Minimum of Months | 0.385296E+11 | 71575.09 | 4.83 | 1.37 | 0.460592E+10 | 6734.71 | 8.00 | 1.37 | ||
Maximum of Months | 0.714528E+11 | 86729.65 | 26.00 | 18.79 | 0.550082E+10 | 6735.05 | 33.17 | 20.57 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323316E+11 | 71765.20 | 09-JAN-06:03 | 9.83 | 9.83 | 0.502102E+10 | 6734.74 | 11-JAN-10:09 | 13.33 | 9.76 |
February | 0.272272E+11 | 71857.90 | 01-FEB-06:02 | 5.00 | 3.59 | 0.455772E+10 | 6734.92 | 15-FEB-14:00 | 20.00 | 13.98 |
March | 0.355288E+11 | 73449.76 | 16-MAR-05:02 | 14.90 | 8.03 | 0.547168E+10 | 6734.80 | 17-MAR-09:00 | 21.60 | 14.25 |
April | 0.423461E+11 | 73014.26 | 27-APR-04:03 | 12.83 | 8.17 | 0.487015E+10 | 6734.75 | 04-APR-09:09 | 12.83 | 8.17 |
May | 0.471973E+11 | 73938.87 | 03-MAY-05:04 | 17.17 | 7.05 | 0.527858E+10 | 6734.72 | 22-MAY-09:00 | 25.00 | 9.85 |
June | 0.515929E+11 | 60838.24 | 01-JUN-05:02 | 22.83 | 13.08 | 0.525887E+10 | 6734.75 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.494084E+11 | 72808.50 | 29-JUL-04:03 | 21.00 | 17.54 | 0.488720E+10 | 6734.84 | 05-JUL-09:09 | 21.00 | 17.54 |
August | 0.510594E+11 | 72348.19 | 29-AUG-04:03 | 25.17 | 17.65 | 0.549035E+10 | 6734.86 | 28-AUG-09:09 | 25.17 | 17.65 |
September | 0.451145E+11 | 74144.51 | 22-SEP-04:03 | 17.70 | 14.85 | 0.487833E+10 | 6734.73 | 15-SEP-09:09 | 17.70 | 14.85 |
October | 0.406247E+11 | 73206.31 | 25-OCT-05:02 | 6.67 | 1.21 | 0.506485E+10 | 6734.74 | 17-OCT-09:30 | 6.67 | 1.21 |
November | 0.336121E+11 | 74765.92 | 13-NOV-05:03 | 17.00 | 17.00 | 0.500134E+10 | 6734.92 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.291126E+11 | 69826.60 | 29-DEC-06:02 | 6.00 | 1.72 | 0.483287E+10 | 6734.75 | 13-DEC-10:09 | 6.00 | 1.72 |
Annual Sum or Average | 0.485156E+12 | 0.606130E+11 | ||||||||
Minimum of Months | 0.272272E+11 | 60838.24 | 5.00 | 1.21 | 0.455772E+10 | 6734.72 | 6.00 | 1.21 | ||
Maximum of Months | 0.515929E+11 | 74765.92 | 25.17 | 17.65 | 0.549035E+10 | 6734.92 | 33.17 | 18.03 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.254611E+11 | 32467.50 | 27-JAN-17:00 | 26.00 | 9.22 | 0.477508E+10 | 6734.54 | 26-JAN-14:09 | 26.00 | 9.22 |
February | 0.214697E+11 | 29882.84 | 22-FEB-17:00 | 20.00 | 11.26 | 0.428924E+10 | 6734.72 | 15-FEB-14:00 | 20.00 | 11.26 |
March | 0.298608E+11 | 70422.91 | 17-MAR-05:03 | 13.48 | 9.60 | 0.530702E+10 | 6734.77 | 17-MAR-09:00 | 21.60 | 14.25 |
April | 0.434146E+11 | 70690.37 | 18-APR-05:03 | 15.67 | 9.39 | 0.485462E+10 | 6734.74 | 27-APR-13:00 | 26.00 | 12.23 |
May | 0.507840E+11 | 71765.45 | 26-MAY-04:03 | 21.00 | 12.54 | 0.527643E+10 | 6734.70 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.597235E+11 | 64250.45 | 26-JUN-05:02 | 22.17 | 10.13 | 0.526314E+10 | 6734.74 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.573046E+11 | 68364.75 | 29-JUL-05:02 | 21.00 | 17.09 | 0.489359E+10 | 6734.84 | 05-JUL-09:09 | 21.00 | 17.09 |
August | 0.577087E+11 | 73234.04 | 29-AUG-04:03 | 25.17 | 17.65 | 0.549366E+10 | 6734.89 | 28-AUG-09:30 | 25.17 | 17.65 |
September | 0.490555E+11 | 75405.02 | 11-SEP-03:02 | 23.12 | 19.33 | 0.488074E+10 | 6734.69 | 15-SEP-09:09 | 25.45 | 16.44 |
October | 0.374175E+11 | 69926.00 | 17-OCT-05:03 | 18.00 | 6.91 | 0.500254E+10 | 6734.79 | 03-OCT-13:39 | 18.00 | 6.91 |
November | 0.272364E+11 | 70274.63 | 03-NOV-05:03 | 16.00 | 12.46 | 0.482897E+10 | 6734.83 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.217647E+11 | 28855.40 | 22-DEC-17:00 | 24.00 | 9.52 | 0.438772E+10 | 6734.48 | 22-DEC-14:09 | 24.00 | 9.52 |
Annual Sum or Average | 0.481201E+12 | 0.592527E+11 | ||||||||
Minimum of Months | 0.214697E+11 | 28855.40 | 13.48 | 6.91 | 0.428924E+10 | 6734.48 | 18.00 | 6.91 | ||
Maximum of Months | 0.597235E+11 | 75405.02 | 26.00 | 19.33 | 0.549366E+10 | 6734.89 | 33.17 | 18.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382335E+10 | 4587.17 | 31-JAN-16:30 | 29.00 | 10.73 | 0.620293E+09 | 845.63 | 23-JAN-14:09 | 29.00 | 10.73 |
February | 0.325159E+10 | 4553.18 | 22-FEB-14:00 | 21.00 | 12.01 | 0.562461E+09 | 845.65 | 15-FEB-14:00 | 21.00 | 12.01 |
March | 0.508026E+10 | 6402.49 | 20-MAR-14:00 | 27.70 | 14.42 | 0.680967E+09 | 845.63 | 17-MAR-09:00 | 27.70 | 14.42 |
April | 0.867133E+10 | 9438.28 | 24-APR-05:03 | 15.17 | 4.62 | 0.612313E+09 | 845.63 | 27-APR-13:30 | 25.00 | 11.82 |
May | 0.938620E+10 | 13668.00 | 29-MAY-18:11 | 30.67 | 13.66 | 0.664622E+09 | 845.63 | 22-MAY-09:00 | 30.67 | 13.66 |
June | 0.129608E+11 | 16440.61 | 18-JUN-15:32 | 38.67 | 19.54 | 0.663548E+09 | 845.88 | 28-JUN-13:39 | 40.67 | 19.28 |
July | 0.125848E+11 | 17173.94 | 16-JUL-17:41 | 36.17 | 21.47 | 0.616983E+09 | 845.64 | 05-JUL-09:09 | 36.17 | 21.47 |
August | 0.126111E+11 | 16988.04 | 27-AUG-16:21 | 40.00 | 18.07 | 0.691820E+09 | 845.65 | 28-AUG-09:20 | 32.00 | 20.57 |
September | 0.938136E+10 | 14674.98 | 17-SEP-15:42 | 33.93 | 17.61 | 0.614363E+09 | 845.63 | 22-SEP-09:00 | 25.00 | 17.32 |
October | 0.663055E+10 | 13346.11 | 02-OCT-05:02 | 25.83 | 16.98 | 0.633858E+09 | 845.65 | 03-OCT-13:39 | 33.00 | 20.21 |
November | 0.478350E+10 | 10618.42 | 13-NOV-06:02 | 16.83 | 16.83 | 0.623316E+09 | 845.65 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.381262E+10 | 4876.37 | 26-DEC-15:30 | 23.00 | 10.56 | 0.594275E+09 | 845.62 | 13-DEC-10:09 | 23.00 | 10.56 |
Annual Sum or Average | 0.929774E+11 | 0.757882E+10 | ||||||||
Minimum of Months | 0.325159E+10 | 4553.18 | 15.17 | 4.62 | 0.562461E+09 | 845.62 | 18.00 | 10.56 | ||
Maximum of Months | 0.129608E+11 | 17173.94 | 40.00 | 21.47 | 0.691820E+09 | 845.88 | 40.67 | 21.47 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.380217E+10 | 6181.73 | 17-JAN-09:30 | 16.50 | 6.15 | 0.404992E+09 | 544.96 | 23-JAN-14:09 | 21.83 | 11.36 |
February | 0.310138E+10 | 5997.86 | 23-FEB-09:20 | 13.33 | 10.50 | 0.365156E+09 | 544.97 | 15-FEB-14:00 | 13.33 | 10.50 |
March | 0.460654E+10 | 7971.67 | 19-MAR-09:03 | 20.45 | 11.62 | 0.440274E+09 | 544.97 | 14-MAR-09:00 | 20.45 | 11.62 |
April | 0.821531E+10 | 15625.59 | 23-APR-10:02 | 27.33 | 10.17 | 0.395010E+09 | 545.44 | 24-APR-09:09 | 26.17 | 10.69 |
May | 0.920363E+10 | 16724.34 | 21-MAY-08:52 | 27.00 | 11.45 | 0.428980E+09 | 545.42 | 11-MAY-09:50 | 27.00 | 11.45 |
June | 0.113375E+11 | 16016.79 | 18-JUN-08:52 | 32.00 | 17.50 | 0.427796E+09 | 545.45 | 09-JUN-09:00 | 32.00 | 17.50 |
July | 0.104899E+11 | 16094.42 | 23-JUL-09:01 | 32.17 | 22.04 | 0.397658E+09 | 545.41 | 03-JUL-09:00 | 32.17 | 22.04 |
August | 0.105233E+11 | 16794.96 | 27-AUG-09:02 | 33.33 | 15.93 | 0.445810E+09 | 545.50 | 01-AUG-09:00 | 33.33 | 15.93 |
September | 0.811458E+10 | 15762.01 | 10-SEP-11:02 | 33.30 | 19.22 | 0.396015E+09 | 545.94 | 08-SEP-09:00 | 33.30 | 19.22 |
October | 0.628187E+10 | 11367.33 | 09-OCT-10:53 | 27.00 | 15.46 | 0.409412E+09 | 544.98 | 17-OCT-09:39 | 25.33 | 10.15 |
November | 0.419357E+10 | 6638.63 | 20-NOV-09:30 | 20.00 | 10.40 | 0.402635E+09 | 544.98 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.326055E+10 | 5361.69 | 26-DEC-09:40 | 16.33 | 7.28 | 0.385928E+09 | 544.95 | 13-DEC-10:09 | 16.33 | 7.28 |
Annual Sum or Average | 0.831303E+11 | 0.489966E+10 | ||||||||
Minimum of Months | 0.310138E+10 | 5361.69 | 13.33 | 6.15 | 0.365156E+09 | 544.95 | 13.33 | 7.28 | ||
Maximum of Months | 0.113375E+11 | 16794.96 | 33.33 | 22.04 | 0.445810E+09 | 545.94 | 33.33 | 22.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105532E+11 | 19611.15 | 15-JAN-13:52 | 23.00 | 10.38 | 0.634830E+09 | 869.23 | 17-JAN-14:30 | 24.50 | 9.15 |
February | 0.638902E+10 | 14044.17 | 26-FEB-14:03 | 17.00 | 10.27 | 0.570454E+09 | 847.13 | 23-FEB-14:00 | 17.00 | 10.27 |
March | 0.787660E+10 | 12034.54 | 23-MAR-13:40 | 25.33 | 11.79 | 0.683847E+09 | 845.97 | 22-MAR-13:09 | 25.33 | 11.79 |
April | 0.114889E+11 | 18536.82 | 30-APR-13:02 | 34.00 | 12.41 | 0.613705E+09 | 846.89 | 25-APR-13:20 | 34.00 | 12.41 |
May | 0.101214E+11 | 17886.00 | 07-MAY-15:02 | 35.17 | 13.95 | 0.664969E+09 | 845.65 | 22-MAY-09:00 | 25.00 | 9.85 |
June | 0.124666E+11 | 18064.25 | 18-JUN-15:32 | 38.67 | 19.54 | 0.663373E+09 | 845.66 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.127511E+11 | 18871.60 | 16-JUL-17:01 | 36.83 | 20.98 | 0.617075E+09 | 845.91 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.144071E+11 | 19314.33 | 27-AUG-15:41 | 40.00 | 18.27 | 0.692282E+09 | 847.42 | 28-AUG-13:30 | 37.50 | 20.42 |
September | 0.127092E+11 | 19263.47 | 10-SEP-11:43 | 33.30 | 19.39 | 0.615682E+09 | 877.47 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.123216E+11 | 19108.70 | 09-OCT-10:53 | 27.00 | 15.46 | 0.639217E+09 | 881.72 | 02-OCT-13:09 | 27.00 | 15.46 |
November | 0.105419E+11 | 19017.00 | 05-NOV-12:02 | 20.33 | 8.59 | 0.631066E+09 | 881.90 | 20-NOV-14:30 | 27.00 | 11.68 |
December | 0.938699E+10 | 19648.78 | 03-DEC-13:22 | 20.50 | 10.49 | 0.610053E+09 | 862.49 | 26-DEC-14:09 | 23.00 | 10.20 |
Annual Sum or Average | 0.131014E+12 | 0.763655E+10 | ||||||||
Minimum of Months | 0.638902E+10 | 12034.54 | 17.00 | 8.59 | 0.570454E+09 | 845.65 | 17.00 | 9.15 | ||
Maximum of Months | 0.144071E+11 | 19648.78 | 40.00 | 20.98 | 0.692282E+09 | 881.90 | 38.17 | 20.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.547133E+10 | 14110.55 | 16-JAN-16:03 | 24.00 | 8.95 | 0.406250E+09 | 544.97 | 30-JAN-14:50 | 24.83 | 9.61 |
February | 0.476520E+10 | 17531.15 | 20-FEB-16:03 | 17.83 | 9.64 | 0.370438E+09 | 544.99 | 15-FEB-14:00 | 17.83 | 9.64 |
March | 0.788523E+10 | 15691.70 | 18-MAR-17:06 | 26.92 | 12.85 | 0.445645E+09 | 544.97 | 09-MAR-14:09 | 26.92 | 12.85 |
April | 0.136621E+11 | 21940.28 | 02-APR-16:51 | 31.00 | 12.54 | 0.396935E+09 | 544.97 | 27-APR-13:30 | 25.00 | 11.82 |
May | 0.111373E+11 | 23006.56 | 21-MAY-16:51 | 32.00 | 13.36 | 0.429450E+09 | 544.96 | 22-MAY-09:00 | 25.00 | 9.85 |
June | 0.148735E+11 | 21737.06 | 25-JUN-17:02 | 38.00 | 15.28 | 0.428243E+09 | 544.96 | 19-JUN-13:09 | 38.00 | 15.28 |
July | 0.145151E+11 | 24359.48 | 16-JUL-17:01 | 36.83 | 20.98 | 0.398559E+09 | 544.97 | 05-JUL-09:09 | 36.83 | 20.98 |
August | 0.160982E+11 | 24925.07 | 27-AUG-16:21 | 40.00 | 18.07 | 0.446991E+09 | 544.97 | 28-AUG-09:20 | 32.00 | 20.57 |
September | 0.100602E+11 | 20419.56 | 17-SEP-16:22 | 34.40 | 17.42 | 0.396674E+09 | 544.96 | 15-SEP-09:09 | 34.40 | 17.42 |
October | 0.888495E+10 | 20305.43 | 15-OCT-16:02 | 30.83 | 12.50 | 0.411982E+09 | 544.98 | 03-OCT-13:30 | 30.83 | 12.50 |
November | 0.766016E+10 | 17496.23 | 26-NOV-16:22 | 18.50 | 8.85 | 0.407764E+09 | 544.99 | 27-NOV-14:39 | 24.97 | 9.27 |
December | 0.692014E+10 | 20099.67 | 03-DEC-14:42 | 21.00 | 10.55 | 0.396800E+09 | 544.95 | 13-DEC-10:09 | 11.33 | 10.45 |
Annual Sum or Average | 0.121933E+12 | 0.493573E+10 | ||||||||
Minimum of Months | 0.476520E+10 | 14110.55 | 17.83 | 8.85 | 0.370438E+09 | 544.95 | 11.33 | 9.27 | ||
Maximum of Months | 0.160982E+11 | 24925.07 | 40.00 | 20.98 | 0.446991E+09 | 544.99 | 38.00 | 20.98 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.284902E+10 | 3195.33 | 27-JAN-16:30 | 26.50 | 9.48 | 0.563609E+09 | 845.60 | 06-JAN-14:30 | 26.50 | 9.48 |
February | 0.226327E+10 | 2648.09 | 23-FEB-14:00 | 18.00 | 10.78 | 0.507530E+09 | 845.56 | 22-FEB-14:00 | 18.00 | 10.78 |
March | 0.332025E+10 | 4930.24 | 17-MAR-15:40 | 26.80 | 14.12 | 0.642384E+09 | 845.63 | 17-MAR-09:00 | 26.80 | 14.12 |
April | 0.596638E+10 | 9068.40 | 13-APR-05:02 | 16.00 | 7.32 | 0.608508E+09 | 845.63 | 27-APR-13:30 | 25.00 | 11.82 |
May | 0.822697E+10 | 11771.98 | 26-MAY-05:03 | 21.33 | 12.61 | 0.664176E+09 | 845.63 | 22-MAY-09:00 | 21.33 | 12.61 |
June | 0.116753E+11 | 15520.74 | 18-JUN-15:32 | 38.67 | 19.54 | 0.663588E+09 | 845.72 | 29-JUN-13:39 | 39.67 | 18.36 |
July | 0.104682E+11 | 15655.38 | 02-JUL-17:41 | 38.00 | 14.95 | 0.617029E+09 | 845.64 | 05-JUL-09:09 | 31.33 | 16.71 |
August | 0.994906E+10 | 13527.69 | 28-AUG-04:03 | 29.00 | 19.59 | 0.691565E+09 | 845.64 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.797884E+10 | 12572.35 | 19-SEP-03:02 | 25.60 | 12.58 | 0.614077E+09 | 845.62 | 15-SEP-09:09 | 25.60 | 12.58 |
October | 0.488842E+10 | 11771.72 | 02-OCT-05:02 | 25.83 | 16.98 | 0.616566E+09 | 845.64 | 03-OCT-13:39 | 33.00 | 20.21 |
November | 0.303057E+10 | 4800.90 | 02-NOV-14:00 | 27.00 | 15.44 | 0.582726E+09 | 845.62 | 16-NOV-14:50 | 18.00 | 12.11 |
December | 0.226474E+10 | 2810.02 | 22-DEC-16:00 | 25.00 | 10.09 | 0.510691E+09 | 796.50 | 22-DEC-14:00 | 25.00 | 10.09 |
Annual Sum or Average | 0.728810E+11 | 0.728245E+10 | ||||||||
Minimum of Months | 0.226327E+10 | 2648.09 | 16.00 | 7.32 | 0.507530E+09 | 796.50 | 18.00 | 9.48 | ||
Maximum of Months | 0.116753E+11 | 15655.38 | 38.67 | 19.59 | 0.691565E+09 | 845.72 | 39.67 | 20.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296527E+10 | 4630.73 | 27-JAN-10:00 | 20.00 | 7.78 | 0.285369E+09 | 521.20 | 09-JAN-09:20 | 20.00 | 7.78 |
February | 0.234496E+10 | 4950.21 | 23-FEB-10:00 | 14.00 | 11.11 | 0.256613E+09 | 521.21 | 16-FEB-16:10 | 14.00 | 11.11 |
March | 0.363129E+10 | 6337.56 | 23-MAR-10:10 | 21.97 | 10.49 | 0.314751E+09 | 521.22 | 16-MAR-10:09 | 21.97 | 10.49 |
April | 0.724050E+10 | 17001.66 | 30-APR-10:02 | 28.50 | 10.63 | 0.291011E+09 | 521.23 | 28-APR-10:09 | 28.50 | 10.63 |
May | 0.898083E+10 | 17556.12 | 21-MAY-08:52 | 27.00 | 11.45 | 0.315945E+09 | 521.33 | 18-MAY-10:30 | 27.00 | 11.45 |
June | 0.113097E+11 | 17756.47 | 04-JUN-08:32 | 30.33 | 15.98 | 0.314833E+09 | 524.71 | 19-JUN-07:19 | 29.00 | 12.63 |
July | 0.999517E+10 | 17163.23 | 30-JUL-08:12 | 27.00 | 19.19 | 0.293868E+09 | 521.92 | 13-JUL-10:30 | 27.00 | 19.19 |
August | 0.982847E+10 | 16641.87 | 13-AUG-09:22 | 32.50 | 21.03 | 0.328112E+09 | 521.92 | 16-AUG-10:30 | 33.50 | 22.15 |
September | 0.758002E+10 | 13155.23 | 10-SEP-10:02 | 31.88 | 19.21 | 0.291909E+09 | 521.38 | 08-SEP-08:30 | 31.88 | 19.21 |
October | 0.542438E+10 | 14410.99 | 15-OCT-09:53 | 26.00 | 10.46 | 0.298863E+09 | 521.22 | 02-OCT-07:10 | 26.00 | 10.46 |
November | 0.314799E+10 | 5643.86 | 10-NOV-09:30 | 22.00 | 9.55 | 0.288530E+09 | 521.23 | 02-NOV-08:09 | 22.00 | 9.55 |
December | 0.230167E+10 | 3254.21 | 27-DEC-10:00 | 14.00 | 6.80 | 0.259427E+09 | 521.20 | 29-DEC-11:30 | 17.50 | 8.08 |
Annual Sum or Average | 0.747503E+11 | 0.353923E+10 | ||||||||
Minimum of Months | 0.230167E+10 | 3254.21 | 14.00 | 6.80 | 0.256613E+09 | 521.20 | 14.00 | 7.78 | ||
Maximum of Months | 0.113097E+11 | 17756.47 | 32.50 | 21.03 | 0.328112E+09 | 524.71 | 33.50 | 22.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100817E+11 | 18799.85 | 16-JAN-14:32 | 24.00 | 8.99 | 0.633355E+09 | 897.79 | 30-JAN-14:39 | 24.67 | 9.55 |
February | 0.562741E+10 | 16905.28 | 26-FEB-14:23 | 17.00 | 10.00 | 0.561671E+09 | 846.29 | 23-FEB-14:00 | 17.00 | 10.00 |
March | 0.635945E+10 | 11622.55 | 23-MAR-14:00 | 25.50 | 11.67 | 0.673558E+09 | 845.78 | 16-MAR-13:00 | 25.50 | 11.67 |
April | 0.906527E+10 | 17531.43 | 30-APR-13:23 | 34.00 | 12.40 | 0.612416E+09 | 846.28 | 25-APR-13:30 | 34.00 | 12.40 |
May | 0.907581E+10 | 16911.73 | 07-MAY-15:02 | 35.17 | 13.95 | 0.664668E+09 | 845.65 | 22-MAY-09:00 | 25.00 | 9.85 |
June | 0.111340E+11 | 17054.35 | 18-JUN-15:32 | 38.67 | 19.54 | 0.663331E+09 | 845.66 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.106699E+11 | 17740.38 | 30-JUL-14:51 | 38.00 | 18.95 | 0.617152E+09 | 845.82 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.119181E+11 | 17288.42 | 27-AUG-12:02 | 38.00 | 17.92 | 0.692295E+09 | 846.60 | 18-AUG-13:09 | 38.00 | 17.92 |
September | 0.116331E+11 | 17996.21 | 10-SEP-13:22 | 34.70 | 19.32 | 0.616298E+09 | 909.18 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.111647E+11 | 19531.60 | 09-OCT-13:22 | 31.50 | 17.30 | 0.639306E+09 | 900.36 | 06-OCT-13:00 | 31.50 | 17.30 |
November | 0.926263E+10 | 18801.82 | 19-NOV-13:52 | 26.00 | 11.13 | 0.628680E+09 | 897.51 | 20-NOV-14:39 | 27.00 | 11.68 |
December | 0.791574E+10 | 18749.23 | 24-DEC-13:42 | 23.83 | 10.31 | 0.600288E+09 | 873.60 | 27-DEC-14:09 | 19.17 | 9.79 |
Annual Sum or Average | 0.113908E+12 | 0.760302E+10 | ||||||||
Minimum of Months | 0.562741E+10 | 11622.55 | 17.00 | 8.99 | 0.561671E+09 | 845.65 | 17.00 | 9.55 | ||
Maximum of Months | 0.119181E+11 | 19531.60 | 38.67 | 19.54 | 0.692295E+09 | 909.18 | 38.17 | 19.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362189E+10 | 7798.38 | 24-JAN-16:30 | 24.50 | 10.78 | 0.377871E+09 | 544.95 | 17-JAN-14:30 | 24.50 | 10.78 |
February | 0.266583E+10 | 8152.12 | 22-FEB-16:30 | 20.50 | 11.47 | 0.336435E+09 | 544.97 | 15-FEB-14:00 | 20.50 | 11.47 |
March | 0.398188E+10 | 10830.28 | 18-MAR-17:06 | 26.92 | 12.85 | 0.420450E+09 | 544.96 | 17-MAR-09:00 | 26.92 | 12.85 |
April | 0.769434E+10 | 19141.56 | 23-APR-17:41 | 32.17 | 12.25 | 0.394955E+09 | 544.96 | 03-APR-09:20 | 32.17 | 12.25 |
May | 0.900865E+10 | 19926.58 | 28-MAY-17:21 | 32.50 | 12.51 | 0.429131E+09 | 544.96 | 22-MAY-09:00 | 32.50 | 12.51 |
June | 0.116183E+11 | 19540.77 | 11-JUN-16:11 | 34.00 | 15.03 | 0.428018E+09 | 544.96 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.966853E+10 | 20327.36 | 30-JUL-16:51 | 38.00 | 19.28 | 0.398133E+09 | 544.97 | 05-JUL-09:09 | 38.00 | 19.28 |
August | 0.986218E+10 | 18933.91 | 06-AUG-16:22 | 31.00 | 18.77 | 0.446314E+09 | 544.97 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.758639E+10 | 17542.24 | 04-SEP-15:42 | 31.60 | 21.45 | 0.396318E+09 | 544.96 | 15-SEP-09:09 | 25.45 | 16.44 |
October | 0.557209E+10 | 17589.85 | 15-OCT-15:51 | 31.00 | 12.59 | 0.400923E+09 | 544.97 | 03-OCT-13:39 | 31.00 | 12.59 |
November | 0.384880E+10 | 9588.47 | 01-NOV-16:00 | 28.00 | 15.72 | 0.386422E+09 | 544.97 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.280437E+10 | 7986.63 | 22-DEC-16:30 | 24.50 | 9.81 | 0.349425E+09 | 544.93 | 22-DEC-14:20 | 24.50 | 9.81 |
Annual Sum or Average | 0.779332E+11 | 0.476439E+10 | ||||||||
Minimum of Months | 0.266583E+10 | 7798.38 | 20.50 | 9.81 | 0.336435E+09 | 544.93 | 18.00 | 9.81 | ||
Maximum of Months | 0.116183E+11 | 20327.36 | 38.00 | 21.45 | 0.446314E+09 | 544.97 | 38.17 | 20.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.219915E+10 | 2835.62 | 27-JAN-16:30 | 26.50 | 9.48 | 0.528540E+09 | 826.68 | 27-JAN-14:00 | 26.50 | 9.48 |
February | 0.170381E+10 | 2287.54 | 23-FEB-14:20 | 18.00 | 10.64 | 0.470852E+09 | 824.77 | 22-FEB-14:00 | 18.00 | 10.64 |
March | 0.287290E+10 | 5330.67 | 17-MAR-15:50 | 26.70 | 14.13 | 0.608136E+09 | 845.62 | 23-MAR-13:09 | 25.08 | 11.95 |
April | 0.617680E+10 | 10678.67 | 30-APR-17:31 | 30.67 | 11.39 | 0.603440E+09 | 845.63 | 27-APR-13:00 | 30.67 | 11.39 |
May | 0.879511E+10 | 13346.68 | 26-MAY-05:03 | 21.33 | 12.61 | 0.663940E+09 | 845.63 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.131841E+11 | 19087.95 | 04-JUN-16:01 | 38.00 | 16.06 | 0.663893E+09 | 845.73 | 29-JUN-13:50 | 39.83 | 18.32 |
July | 0.118600E+11 | 19016.22 | 30-JUL-17:31 | 38.00 | 19.05 | 0.617408E+09 | 845.64 | 05-JUL-09:09 | 38.00 | 19.05 |
August | 0.110692E+11 | 18107.96 | 27-AUG-16:31 | 40.00 | 18.00 | 0.691796E+09 | 845.65 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.862398E+10 | 14291.88 | 10-SEP-17:23 | 33.00 | 18.83 | 0.613993E+09 | 845.62 | 19-SEP-09:09 | 28.77 | 14.28 |
October | 0.470168E+10 | 15180.53 | 02-OCT-03:02 | 25.17 | 16.69 | 0.597661E+09 | 845.66 | 03-OCT-13:39 | 33.00 | 20.21 |
November | 0.244878E+10 | 4991.89 | 01-NOV-15:40 | 28.33 | 15.88 | 0.551938E+09 | 845.61 | 02-NOV-13:09 | 26.17 | 15.52 |
December | 0.141324E+10 | 2563.81 | 22-DEC-15:30 | 25.50 | 10.26 | 0.476653E+09 | 781.00 | 22-DEC-14:00 | 25.50 | 10.26 |
Annual Sum or Average | 0.750488E+11 | 0.708825E+10 | ||||||||
Minimum of Months | 0.141324E+10 | 2287.54 | 18.00 | 9.48 | 0.470852E+09 | 781.00 | 18.00 | 9.48 | ||
Maximum of Months | 0.131841E+11 | 19087.95 | 40.00 | 19.05 | 0.691796E+09 | 845.73 | 39.83 | 20.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240365E+10 | 3463.83 | 27-JAN-10:30 | 21.00 | 7.83 | 0.376138E+09 | 544.94 | 09-JAN-10:09 | 21.00 | 7.83 |
February | 0.187313E+10 | 3817.65 | 23-FEB-10:30 | 15.00 | 11.05 | 0.333669E+09 | 544.94 | 23-FEB-10:09 | 15.00 | 11.05 |
March | 0.321940E+10 | 5626.50 | 23-MAR-10:30 | 22.70 | 10.73 | 0.419229E+09 | 544.96 | 14-MAR-13:50 | 22.70 | 10.73 |
April | 0.752580E+10 | 17506.72 | 30-APR-09:32 | 27.00 | 10.05 | 0.394802E+09 | 544.99 | 03-APR-09:20 | 27.00 | 10.05 |
May | 0.959870E+10 | 17369.87 | 28-MAY-09:32 | 28.33 | 12.03 | 0.429113E+09 | 545.43 | 11-MAY-09:00 | 28.33 | 12.03 |
June | 0.126133E+11 | 18539.73 | 04-JUN-08:42 | 30.67 | 16.03 | 0.428167E+09 | 545.35 | 08-JUN-09:00 | 34.00 | 15.03 |
July | 0.112136E+11 | 17867.99 | 30-JUL-16:11 | 38.00 | 19.05 | 0.398309E+09 | 545.32 | 28-JUL-09:00 | 38.00 | 19.05 |
August | 0.108965E+11 | 18370.90 | 27-AUG-09:12 | 33.67 | 16.18 | 0.446344E+09 | 545.33 | 22-AUG-09:00 | 33.67 | 16.18 |
September | 0.824979E+10 | 13693.64 | 10-SEP-10:02 | 31.88 | 19.21 | 0.396195E+09 | 545.76 | 08-SEP-09:00 | 31.88 | 19.21 |
October | 0.527182E+10 | 12815.09 | 01-OCT-11:02 | 34.17 | 19.37 | 0.402788E+09 | 544.98 | 17-OCT-09:30 | 25.00 | 10.00 |
November | 0.266418E+10 | 4911.29 | 01-NOV-10:00 | 23.00 | 16.02 | 0.382422E+09 | 544.97 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.173526E+10 | 2351.73 | 22-DEC-15:30 | 25.50 | 10.26 | 0.329763E+09 | 536.04 | 22-DEC-10:00 | 25.50 | 10.26 |
Annual Sum or Average | 0.772651E+11 | 0.473694E+10 | ||||||||
Minimum of Months | 0.173526E+10 | 2351.73 | 15.00 | 7.83 | 0.329763E+09 | 536.04 | 15.00 | 7.83 | ||
Maximum of Months | 0.126133E+11 | 18539.73 | 38.00 | 19.37 | 0.446344E+09 | 545.76 | 38.00 | 19.21 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.875555E+10 | 20924.38 | 29-JAN-15:22 | 24.50 | 9.40 | 0.615973E+09 | 845.80 | 27-JAN-14:20 | 24.50 | 9.40 |
February | 0.459445E+10 | 12896.67 | 23-FEB-14:00 | 18.00 | 10.78 | 0.539304E+09 | 846.19 | 23-FEB-14:50 | 18.00 | 10.42 |
March | 0.558771E+10 | 11726.69 | 23-MAR-14:00 | 25.50 | 11.67 | 0.651359E+09 | 845.67 | 10-MAR-14:00 | 25.50 | 11.67 |
April | 0.939253E+10 | 19969.51 | 30-APR-12:53 | 34.00 | 12.41 | 0.608742E+09 | 846.25 | 25-APR-13:09 | 34.00 | 12.41 |
May | 0.973275E+10 | 19130.50 | 28-MAY-16:51 | 33.00 | 12.91 | 0.663930E+09 | 845.64 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.126164E+11 | 20642.83 | 04-JUN-16:01 | 38.00 | 16.06 | 0.663581E+09 | 845.66 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.121299E+11 | 21020.50 | 30-JUL-16:11 | 38.00 | 19.05 | 0.617324E+09 | 845.91 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.132249E+11 | 20047.48 | 27-AUG-16:31 | 40.00 | 18.00 | 0.692380E+09 | 847.01 | 28-AUG-13:20 | 37.67 | 20.48 |
September | 0.125237E+11 | 20526.18 | 10-SEP-13:22 | 34.70 | 19.32 | 0.615874E+09 | 887.58 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.108792E+11 | 22042.56 | 09-OCT-14:02 | 32.00 | 17.25 | 0.628791E+09 | 878.18 | 02-OCT-13:20 | 32.00 | 17.25 |
November | 0.813154E+10 | 20789.69 | 19-NOV-14:32 | 26.67 | 11.36 | 0.614750E+09 | 863.74 | 01-NOV-13:00 | 26.67 | 11.36 |
December | 0.620132E+10 | 20418.97 | 24-DEC-15:02 | 23.83 | 10.51 | 0.577173E+09 | 845.84 | 22-DEC-14:20 | 23.83 | 10.51 |
Annual Sum or Average | 0.113770E+12 | 0.748918E+10 | ||||||||
Minimum of Months | 0.459445E+10 | 11726.69 | 18.00 | 9.40 | 0.539304E+09 | 845.64 | 18.00 | 9.40 | ||
Maximum of Months | 0.132249E+11 | 22042.56 | 40.00 | 19.32 | 0.692380E+09 | 887.58 | 38.17 | 20.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.317992E+10 | 7534.55 | 24-JAN-16:30 | 24.50 | 10.78 | 0.358142E+09 | 544.95 | 17-JAN-14:00 | 24.50 | 10.78 |
February | 0.228226E+10 | 7924.24 | 22-FEB-16:30 | 20.50 | 11.47 | 0.315779E+09 | 544.92 | 23-FEB-14:00 | 18.00 | 10.35 |
March | 0.369446E+10 | 11351.06 | 18-MAR-17:06 | 26.92 | 12.85 | 0.399736E+09 | 544.96 | 10-MAR-14:00 | 26.92 | 12.85 |
April | 0.796343E+10 | 21611.00 | 30-APR-17:31 | 30.67 | 11.39 | 0.392156E+09 | 544.96 | 27-APR-13:00 | 30.67 | 11.39 |
May | 0.955474E+10 | 21901.98 | 28-MAY-16:51 | 33.00 | 12.91 | 0.428639E+09 | 544.95 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.128017E+11 | 22627.96 | 04-JUN-16:01 | 38.00 | 16.06 | 0.428047E+09 | 544.96 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.107792E+11 | 23005.96 | 30-JUL-16:51 | 38.00 | 19.28 | 0.398074E+09 | 544.97 | 05-JUL-09:09 | 38.00 | 19.28 |
August | 0.108078E+11 | 21144.70 | 27-AUG-16:31 | 40.00 | 18.00 | 0.446198E+09 | 544.97 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.817332E+10 | 19328.70 | 04-SEP-15:42 | 31.60 | 21.45 | 0.395936E+09 | 544.95 | 15-SEP-09:09 | 25.45 | 16.44 |
October | 0.550305E+10 | 20357.68 | 15-OCT-16:22 | 30.50 | 12.33 | 0.390298E+09 | 544.98 | 03-OCT-13:39 | 30.50 | 12.33 |
November | 0.345671E+10 | 9934.13 | 01-NOV-16:00 | 28.00 | 15.72 | 0.369512E+09 | 544.96 | 16-NOV-14:30 | 18.00 | 11.97 |
December | 0.222856E+10 | 7771.40 | 22-DEC-16:30 | 24.50 | 9.81 | 0.328847E+09 | 544.94 | 22-DEC-14:39 | 24.50 | 9.81 |
Annual Sum or Average | 0.804252E+11 | 0.465136E+10 | ||||||||
Minimum of Months | 0.222856E+10 | 7534.55 | 20.50 | 9.81 | 0.315779E+09 | 544.92 | 18.00 | 9.81 | ||
Maximum of Months | 0.128017E+11 | 23005.96 | 40.00 | 21.45 | 0.446198E+09 | 544.98 | 38.17 | 20.80 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.381663E+10 | 5451.36 | 17-JAN-06:15 | 12.33 | 4.18 | 0.00 | 0.00 | 01-JAN-00:10 | 12.33 | 4.18 |
February | 0.280966E+10 | 4808.21 | 23-FEB-06:15 | 8.00 | 8.00 | 0.00 | 0.00 | 01-FEB-00:10 | 8.00 | 8.00 |
March | 0.450025E+10 | 6992.73 | 20-MAR-05:15 | 11.27 | 7.51 | 0.00 | 0.00 | 01-MAR-00:10 | 11.27 | 7.51 |
April | 0.805676E+10 | 7830.05 | 03-APR-05:15 | 15.33 | 5.33 | 0.00 | 0.00 | 01-APR-00:10 | 15.33 | 5.33 |
May | 0.864938E+10 | 8977.15 | 01-MAY-05:15 | 13.00 | 4.63 | 0.00 | 0.00 | 01-MAY-00:10 | 13.00 | 4.63 |
June | 0.114568E+11 | 11718.32 | 05-JUN-05:03 | 23.33 | 12.92 | 0.00 | 0.00 | 01-JUN-00:10 | 23.33 | 12.92 |
July | 0.113199E+11 | 14492.14 | 24-JUL-05:15 | 24.67 | 18.75 | 0.00 | 0.00 | 01-JUL-00:10 | 24.67 | 18.75 |
August | 0.119234E+11 | 15241.21 | 14-AUG-05:15 | 26.00 | 16.67 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 16.67 |
September | 0.905800E+10 | 12772.99 | 11-SEP-05:15 | 22.33 | 18.20 | 0.00 | 0.00 | 01-SEP-00:10 | 22.33 | 18.20 |
October | 0.698513E+10 | 12093.57 | 10-OCT-05:15 | 17.33 | 11.48 | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 | 11.48 |
November | 0.502380E+10 | 8199.30 | 13-NOV-06:15 | 16.67 | 16.67 | 0.00 | 0.00 | 01-NOV-00:10 | 16.67 | 16.67 |
December | 0.362191E+10 | 8084.35 | 26-DEC-06:15 | 8.67 | 3.13 | 0.00 | 0.00 | 01-DEC-00:10 | 8.67 | 3.13 |
Annual Sum or Average | 0.872216E+11 | 0.00 | ||||||||
Minimum of Months | 0.280966E+10 | 4808.21 | 8.00 | 3.13 | 0.00 | 0.00 | 8.00 | 3.13 | ||
Maximum of Months | 0.119234E+11 | 15241.21 | 26.00 | 18.75 | 0.00 | 0.00 | 26.00 | 18.75 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190825E+10 | 3274.55 | 28-JAN-06:10 | 8.00 | 1.64 | 0.00 | 0.00 | 01-JAN-00:10 | 8.00 | 1.64 |
February | 0.130368E+10 | 3705.29 | 01-FEB-06:10 | 5.00 | 3.59 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | 3.59 |
March | 0.225134E+10 | 4373.37 | 20-MAR-05:15 | 11.27 | 7.51 | 0.00 | 0.00 | 01-MAR-00:10 | 11.27 | 7.51 |
April | 0.561949E+10 | 6094.93 | 25-APR-15:20 | 33.00 | 15.00 | 0.00 | 0.00 | 01-APR-00:10 | 33.00 | 15.00 |
May | 0.719910E+10 | 7746.35 | 11-MAY-05:03 | 21.83 | 11.99 | 0.00 | 0.00 | 01-MAY-00:10 | 21.83 | 11.99 |
June | 0.939542E+10 | 8453.56 | 29-JUN-05:02 | 28.00 | 14.69 | 0.00 | 0.00 | 01-JUN-00:10 | 28.00 | 14.69 |
July | 0.874753E+10 | 7659.17 | 14-JUL-05:03 | 24.00 | 21.67 | 0.00 | 0.00 | 01-JUL-00:10 | 24.00 | 21.67 |
August | 0.881652E+10 | 7631.57 | 14-AUG-15:20 | 38.00 | 19.72 | 0.00 | 0.00 | 01-AUG-00:10 | 38.00 | 19.72 |
September | 0.740067E+10 | 9635.90 | 05-SEP-05:02 | 21.92 | 18.79 | 0.00 | 0.00 | 01-SEP-00:10 | 21.92 | 18.79 |
October | 0.482166E+10 | 7292.90 | 03-OCT-05:03 | 22.00 | 18.54 | 0.00 | 0.00 | 01-OCT-00:10 | 22.00 | 18.54 |
November | 0.245305E+10 | 4289.62 | 13-NOV-06:15 | 16.67 | 16.67 | 0.00 | 0.00 | 01-NOV-00:10 | 16.67 | 16.67 |
December | 0.127860E+10 | 5202.27 | 07-DEC-06:01 | -0.7 | -5.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -5.3 |
Annual Sum or Average | 0.611953E+11 | 0.00 | ||||||||
Minimum of Months | 0.127860E+10 | 3274.55 | -0.7 | -5.3 | 0.00 | 0.00 | -0.7 | -5.3 | ||
Maximum of Months | 0.939542E+10 | 9635.90 | 38.00 | 21.67 | 0.00 | 0.00 | 38.00 | 21.67 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222046E+10 | 7126.29 | 31-JAN-16:20 | 29.00 | 10.73 | 0.00 | 0.00 | 01-JAN-00:10 | 29.00 | 10.73 |
February | 0.118843E+10 | 6348.71 | 23-FEB-14:40 | 18.00 | 10.49 | 0.00 | 0.00 | 01-FEB-00:10 | 18.00 | 10.49 |
March | 0.322288E+10 | 10834.16 | 16-MAR-15:30 | 28.80 | 13.83 | 0.00 | 0.00 | 01-MAR-00:10 | 28.80 | 13.83 |
April | 0.103848E+11 | 18107.20 | 14-APR-15:20 | 35.00 | 14.57 | 0.00 | 0.00 | 01-APR-00:10 | 35.00 | 14.57 |
May | 0.135047E+11 | 18472.96 | 19-MAY-14:00 | 36.00 | 14.39 | 0.00 | 0.00 | 01-MAY-00:10 | 36.00 | 14.39 |
June | 0.192985E+11 | 22695.43 | 28-JUN-14:40 | 41.67 | 19.29 | 0.00 | 0.00 | 01-JUN-00:10 | 41.67 | 19.29 |
July | 0.171029E+11 | 21565.69 | 20-JUL-14:00 | 39.00 | 20.25 | 0.00 | 0.00 | 01-JUL-00:10 | 39.00 | 20.25 |
August | 0.166418E+11 | 20854.17 | 15-AUG-15:20 | 39.00 | 18.95 | 0.00 | 0.00 | 01-AUG-00:10 | 39.00 | 18.95 |
September | 0.123661E+11 | 18458.35 | 07-SEP-15:00 | 37.20 | 19.77 | 0.00 | 0.00 | 01-SEP-00:10 | 37.20 | 19.77 |
October | 0.663191E+10 | 16090.62 | 02-OCT-14:20 | 35.00 | 19.60 | 0.00 | 0.00 | 01-OCT-00:10 | 35.00 | 19.60 |
November | 0.258767E+10 | 9980.26 | 01-NOV-15:20 | 28.67 | 16.04 | 0.00 | 0.00 | 01-NOV-00:10 | 28.67 | 16.04 |
December | 0.976794E+09 | 5178.14 | 22-DEC-16:00 | 25.00 | 10.09 | 0.00 | 0.00 | 01-DEC-00:10 | 25.00 | 10.09 |
Annual Sum or Average | 0.106127E+12 | 0.00 | ||||||||
Minimum of Months | 0.976794E+09 | 5178.14 | 18.00 | 10.09 | 0.00 | 0.00 | 18.00 | 10.09 | ||
Maximum of Months | 0.192985E+11 | 22695.43 | 41.67 | 20.25 | 0.00 | 0.00 | 41.67 | 20.25 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.406946E+10 | 2069.52 | 24-JAN-17:00 | 24.00 | 10.79 | 95230236.07 | 126.83 | 09-JAN-10:00 | 24.00 | 10.79 |
February | 0.817254E+10 | 3904.27 | 27-FEB-17:40 | 15.67 | 8.53 | 86398847.81 | 126.84 | 16-FEB-10:50 | 15.67 | 8.53 |
March | 0.143640E+11 | 7167.82 | 31-MAR-24:00 | 15.30 | 7.49 | 0.103237E+09 | 126.84 | 06-MAR-10:00 | 15.30 | 7.49 |
April | 0.186261E+11 | 7683.11 | 26-APR-18:10 | 20.67 | 10.17 | 95480697.45 | 150.57 | 24-APR-13:00 | 20.67 | 10.17 |
May | 0.458487E+10 | 3470.26 | 31-MAY-23:57 | 26.00 | 10.61 | 99233118.02 | 126.82 | 09-MAY-13:39 | 26.00 | 10.61 |
June | 0.943052E+10 | 5411.67 | 30-JUN-23:37 | 28.87 | 14.96 | 98957400.04 | 126.83 | 30-JUN-09:00 | 28.87 | 14.96 |
July | 0.147792E+11 | 7313.43 | 31-JUL-23:57 | 29.60 | 17.96 | 91884793.29 | 126.84 | 18-JUL-09:09 | 29.60 | 17.96 |
August | 0.195110E+11 | 7766.54 | 06-AUG-18:50 | 29.17 | 19.47 | 0.106634E+09 | 158.30 | 25-AUG-13:00 | 41.00 | 17.20 |
September | 0.449085E+10 | 3491.40 | 30-SEP-24:00 | 25.20 | 15.49 | 91612862.36 | 126.85 | 01-SEP-09:00 | 25.20 | 15.49 |
October | 0.955750E+10 | 5329.96 | 31-OCT-24:00 | 17.10 | 9.96 | 95231442.78 | 126.85 | 03-OCT-09:00 | 17.10 | 9.96 |
November | 0.140159E+11 | 6041.47 | 26-NOV-16:56 | 18.00 | 8.58 | 94302271.18 | 126.85 | 13-NOV-10:50 | 18.00 | 8.58 |
December | 0.193389E+11 | 7781.17 | 26-DEC-16:50 | 23.00 | 10.75 | 91929414.32 | 127.75 | 22-DEC-14:00 | 23.00 | 10.75 |
Annual Sum or Average | 0.140941E+12 | 0.115013E+10 | ||||||||
Minimum of Months | 0.406946E+10 | 2069.52 | 15.30 | 7.49 | 86398847.81 | 126.82 | 15.30 | 7.49 | ||
Maximum of Months | 0.195110E+11 | 7781.17 | 29.60 | 19.47 | 0.106634E+09 | 158.30 | 41.00 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.293013E+10 | 1890.43 | 24-JAN-17:00 | 24.00 | 10.79 | 95230228.10 | 126.83 | 09-JAN-10:00 | 24.00 | 10.79 |
February | 0.681548E+10 | 3627.70 | 27-FEB-17:40 | 15.67 | 8.53 | 86398721.91 | 126.84 | 16-FEB-10:50 | 15.67 | 8.53 |
March | 0.130409E+11 | 6684.34 | 31-MAR-24:00 | 15.30 | 7.49 | 0.103237E+09 | 126.83 | 06-MAR-10:00 | 15.30 | 7.49 |
April | 0.177232E+11 | 7347.55 | 26-APR-18:10 | 20.67 | 10.17 | 95434586.28 | 149.29 | 24-APR-13:00 | 20.67 | 10.17 |
May | 0.424666E+10 | 3365.46 | 31-MAY-23:27 | 26.50 | 10.77 | 99233118.03 | 126.82 | 08-MAY-09:00 | 26.50 | 10.77 |
June | 0.893458E+10 | 5209.31 | 30-JUN-23:57 | 28.10 | 15.37 | 98957399.91 | 126.83 | 30-JUN-09:00 | 28.10 | 15.37 |
July | 0.140305E+11 | 6991.80 | 31-JUL-23:57 | 29.60 | 17.96 | 91884641.37 | 126.84 | 14-JUL-09:09 | 29.60 | 17.96 |
August | 0.185573E+11 | 7370.74 | 06-AUG-18:20 | 29.67 | 19.02 | 0.106907E+09 | 157.80 | 25-AUG-13:00 | 41.00 | 17.20 |
September | 0.411062E+10 | 3407.59 | 30-SEP-24:00 | 25.20 | 15.49 | 91611667.53 | 126.85 | 11-SEP-13:00 | 25.20 | 15.49 |
October | 0.869568E+10 | 4921.07 | 31-OCT-24:00 | 17.10 | 9.96 | 95231364.12 | 126.85 | 03-OCT-09:50 | 17.10 | 9.96 |
November | 0.126234E+11 | 5631.32 | 14-NOV-17:00 | 19.00 | 14.11 | 94302069.13 | 126.84 | 13-NOV-14:00 | 19.00 | 14.11 |
December | 0.172111E+11 | 7357.25 | 26-DEC-17:00 | 23.00 | 10.75 | 91892169.58 | 126.82 | 13-DEC-10:00 | 23.00 | 10.75 |
Annual Sum or Average | 0.128920E+12 | 0.115032E+10 | ||||||||
Minimum of Months | 0.293013E+10 | 1890.43 | 15.30 | 7.49 | 86398721.91 | 126.82 | 15.30 | 7.49 | ||
Maximum of Months | 0.185573E+11 | 7370.74 | 29.67 | 19.02 | 0.106907E+09 | 157.80 | 41.00 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194062E+10 | 1895.41 | 24-JAN-17:00 | 24.00 | 10.79 | 95119077.44 | 126.83 | 09-JAN-10:00 | 24.00 | 10.79 |
February | 0.567409E+10 | 3621.87 | 22-FEB-17:00 | 20.00 | 11.26 | 86398694.87 | 126.84 | 16-FEB-10:00 | 20.00 | 11.26 |
March | 0.122952E+11 | 6490.49 | 31-MAR-23:30 | 15.35 | 6.98 | 0.103237E+09 | 126.83 | 06-MAR-10:00 | 15.35 | 6.98 |
April | 0.177153E+11 | 7396.17 | 26-APR-18:10 | 20.67 | 10.17 | 94931171.56 | 149.65 | 24-APR-13:00 | 20.67 | 10.17 |
May | 0.429057E+10 | 3367.30 | 31-MAY-23:37 | 26.33 | 10.72 | 99233118.03 | 126.82 | 02-MAY-09:39 | 26.33 | 10.72 |
June | 0.910711E+10 | 5265.08 | 30-JUN-23:30 | 29.25 | 14.73 | 98957403.36 | 126.83 | 30-JUN-09:00 | 29.25 | 14.73 |
July | 0.142133E+11 | 7056.67 | 31-JUL-23:57 | 29.60 | 17.96 | 91884927.93 | 126.84 | 14-JUL-09:00 | 29.60 | 17.96 |
August | 0.187017E+11 | 7520.73 | 06-AUG-18:20 | 29.67 | 19.02 | 0.106446E+09 | 158.64 | 25-AUG-13:00 | 41.00 | 17.20 |
September | 0.419242E+10 | 3443.61 | 30-SEP-24:00 | 25.20 | 15.49 | 91612311.16 | 126.85 | 05-SEP-13:20 | 25.20 | 15.49 |
October | 0.829494E+10 | 4718.53 | 31-OCT-24:00 | 17.10 | 9.96 | 95231402.80 | 126.85 | 03-OCT-09:00 | 17.10 | 9.96 |
November | 0.117011E+11 | 5649.22 | 21-NOV-17:00 | 24.00 | 10.76 | 94302122.47 | 126.84 | 13-NOV-14:00 | 24.00 | 10.76 |
December | 0.156996E+11 | 7306.72 | 22-DEC-17:00 | 24.00 | 9.52 | 91882840.72 | 126.82 | 13-DEC-10:00 | 24.00 | 9.52 |
Annual Sum or Average | 0.123826E+12 | 0.114924E+10 | ||||||||
Minimum of Months | 0.194062E+10 | 1895.41 | 15.35 | 6.98 | 86398694.87 | 126.82 | 15.35 | 6.98 | ||
Maximum of Months | 0.187017E+11 | 7520.73 | 29.67 | 19.02 | 0.106446E+09 | 158.64 | 41.00 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239377E+12 | 91771.60 | 17-JAN-17:00 | 24.00 | 9.10 | 0.206144E+10 | 2745.29 | 03-JAN-14:09 | 24.00 | 9.10 |
February | 0.434582E+12 | 182351.00 | 21-FEB-17:00 | 19.00 | 10.37 | 0.187022E+10 | 2745.29 | 01-FEB-10:50 | 19.00 | 10.37 |
March | 0.726460E+12 | 357750.41 | 31-MAR-24:00 | 15.30 | 7.49 | 0.223475E+10 | 2745.29 | 07-MAR-10:20 | 15.30 | 7.49 |
April | 0.941343E+12 | 366071.03 | 24-APR-16:00 | 34.00 | 13.45 | 0.198297E+10 | 2745.29 | 12-APR-13:09 | 34.00 | 13.45 |
May | 0.239321E+12 | 175243.44 | 31-MAY-23:53 | 26.00 | 10.61 | 0.214810E+10 | 2745.29 | 26-MAY-13:20 | 26.00 | 10.61 |
June | 0.468357E+12 | 267170.52 | 30-JUN-23:53 | 28.10 | 15.37 | 0.214213E+10 | 2745.29 | 05-JUN-13:30 | 28.10 | 15.37 |
July | 0.731818E+12 | 360017.65 | 31-JUL-23:57 | 29.60 | 17.96 | 0.198894E+10 | 2745.29 | 27-JUL-09:00 | 29.60 | 17.96 |
August | 0.977890E+12 | 368033.17 | 14-AUG-16:00 | 38.00 | 19.28 | 0.223475E+10 | 2745.29 | 02-AUG-13:50 | 38.00 | 19.28 |
September | 0.237316E+12 | 176992.97 | 30-SEP-24:00 | 25.20 | 15.49 | 0.198297E+10 | 2745.29 | 08-SEP-09:50 | 25.20 | 15.49 |
October | 0.488519E+12 | 268741.10 | 31-OCT-24:00 | 17.10 | 9.96 | 0.206144E+10 | 2745.29 | 02-OCT-13:00 | 17.10 | 9.96 |
November | 0.709356E+12 | 276223.42 | 20-NOV-17:00 | 26.00 | 12.00 | 0.204131E+10 | 2745.29 | 01-NOV-09:20 | 26.00 | 12.00 |
December | 0.977218E+12 | 367820.63 | 26-DEC-17:00 | 23.00 | 10.75 | 0.198894E+10 | 2745.29 | 06-DEC-14:39 | 23.00 | 10.75 |
Annual Sum or Average | 0.717156E+13 | 0.247380E+11 | ||||||||
Minimum of Months | 0.237316E+12 | 91771.60 | 15.30 | 7.49 | 0.187022E+10 | 2745.29 | 15.30 | 7.49 | ||
Maximum of Months | 0.977890E+12 | 368033.17 | 38.00 | 19.28 | 0.223475E+10 | 2745.29 | 38.00 | 19.28 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.603546E+09 | 12883.29 | 01-JAN-14:33 | 14.73 |
February | 0.252763E+09 | 11178.56 | 13-FEB-04:15 | 8.67 |
March | 0.193356E+09 | 10963.45 | 02-MAR-05:05 | 7.52 |
April | 0.465923E+09 | 15682.59 | 29-APR-15:02 | 32.97 |
May | 0.489878E+09 | 18411.37 | 20-MAY-15:02 | 35.83 |
June | 0.518210E+09 | 22514.28 | 17-JUN-15:02 | 40.17 |
July | 0.663199E+09 | 20440.56 | 22-JUL-16:02 | 38.00 |
August | 0.493199E+09 | 22921.72 | 26-AUG-16:02 | 40.83 |
September | 0.630521E+09 | 17660.12 | 30-SEP-15:02 | 35.32 |
October | 0.572967E+09 | 13719.98 | 14-OCT-16:02 | 31.00 |
November | 0.401859E+09 | 12116.09 | 19-NOV-19:33 | 18.00 |
December | 0.482518E+09 | 12249.43 | 24-DEC-19:23 | 14.00 |
Annual Sum or Average | 0.576794E+10 | |||
Minimum of Months | 0.193356E+09 | 10963.45 | 7.52 | |
Maximum of Months | 0.663199E+09 | 22921.72 | 40.83 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210835E+09 | 64086.32 | 02-JAN-05:01 | 4.00 |
February | 33229947.28 | 57005.08 | 13-FEB-06:03 | 8.00 |
March | 5781226.23 | 38541.51 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 6192486.10 | 38105.23 | 24-NOV-06:03 | 3.17 |
December | 0.148458E+09 | 60574.03 | 18-DEC-05:01 | 4.00 |
Annual Sum or Average | 0.404496E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.52 | |
Maximum of Months | 0.210835E+09 | 64086.32 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35446508.88 | 11439.14 | 02-JAN-05:01 | 4.00 |
February | 1735593.73 | 4167.66 | 13-FEB-06:03 | 8.00 |
March | 8675047.97 | 10365.16 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 7317580.71 | 10026.59 | 24-NOV-06:03 | 3.17 |
December | 0.120932E+09 | 11147.08 | 07-DEC-05:01 | -1.1 |
Annual Sum or Average | 0.174107E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 0.120932E+09 | 11439.14 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12369255.86 | 9303.58 | 02-JAN-06:01 | 4.33 |
February | 1445388.78 | 3262.71 | 13-FEB-06:03 | 8.00 |
March | 421966.60 | 516.59 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 1491553.09 | 2877.21 | 24-NOV-06:03 | 3.17 |
December | 42842165.35 | 9455.94 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 58570329.68 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 42842165.35 | 9455.94 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 530093.47 | 5741.92 | 02-JAN-06:01 | 4.33 |
February | 1363215.81 | 3640.66 | 13-FEB-06:03 | 8.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 2884095.57 | 11705.94 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 4777404.85 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 2884095.57 | 11705.94 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3734888.71 | 8710.78 | 02-JAN-06:01 | 4.33 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 17572176.94 | 8870.48 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 21307065.65 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 17572176.94 | 8870.48 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.385988E+09 | 15378.80 | 02-JAN-04:01 | 4.83 |
February | 0.366767E+09 | 13943.74 | 13-FEB-05:01 | 8.00 |
March | 0.195994E+09 | 13925.35 | 27-MAR-04:01 | 2.28 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 20265759.56 | 12268.64 | 26-OCT-05:03 | 7.17 |
November | 0.249773E+09 | 14169.35 | 24-NOV-05:01 | 3.83 |
December | 0.119156E+10 | 14759.43 | 18-DEC-04:02 | 4.00 |
Annual Sum or Average | 0.241034E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.28 | |
Maximum of Months | 0.119156E+10 | 15378.80 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133349E+09 | 13401.30 | 02-JAN-04:01 | 4.83 |
February | 0.134786E+09 | 12212.53 | 13-FEB-05:01 | 8.00 |
March | 65309959.24 | 11859.51 | 27-MAR-04:01 | 2.28 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 4316645.14 | 3392.31 | 26-OCT-05:03 | 7.17 |
November | 79491501.78 | 12244.58 | 24-NOV-05:01 | 3.83 |
December | 0.466683E+09 | 12776.19 | 06-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.883935E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.466683E+09 | 13401.30 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52284648.18 | 15070.28 | 02-JAN-05:01 | 4.00 |
February | 94716314.49 | 15054.51 | 13-FEB-05:01 | 8.00 |
March | 64070936.10 | 13658.69 | 07-MAR-06:02 | 7.28 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 27368.51 | 182.46 | 26-OCT-05:08 | 7.17 |
November | 23573804.04 | 13337.79 | 24-NOV-06:03 | 3.17 |
December | 0.312848E+09 | 14945.51 | 18-DEC-05:01 | 4.00 |
Annual Sum or Average | 0.547521E+09 | |||
Minimum of Months | 0.00 | 0.00 | 3.17 | |
Maximum of Months | 0.312848E+09 | 15070.28 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55163052.35 | 12794.47 | 02-JAN-05:01 | 4.00 |
February | 63159542.81 | 11823.99 | 13-FEB-05:01 | 8.00 |
March | 23824492.19 | 8609.87 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 9533.77 | 46.28 | 28-OCT-05:08 | 10.00 |
November | 28101217.53 | 10950.77 | 24-NOV-05:01 | 3.83 |
December | 0.304770E+09 | 12737.92 | 07-DEC-05:01 | -1.1 |
Annual Sum or Average | 0.475028E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 0.304770E+09 | 12794.47 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73549354.88 | 7334.46 | 02-JAN-04:01 | 4.83 |
February | 64305459.09 | 8954.90 | 13-FEB-05:01 | 8.00 |
March | 81644075.31 | 8254.44 | 06-MAR-04:03 | 13.20 |
April | 70920311.58 | 6643.39 | 08-APR-03:02 | 13.82 |
May | 48989176.95 | 5160.85 | 07-MAY-15:02 | 35.17 |
June | 29240763.22 | 5587.75 | 25-JUN-17:02 | 38.00 |
July | 49418353.60 | 6571.51 | 16-JUL-16:21 | 36.50 |
August | 50121744.40 | 6829.09 | 27-AUG-15:01 | 40.00 |
September | 50422169.15 | 5317.67 | 21-SEP-03:02 | 22.10 |
October | 75046418.63 | 7917.18 | 23-OCT-03:02 | 11.83 |
November | 0.102625E+09 | 8700.19 | 13-NOV-04:02 | 17.00 |
December | 0.121601E+09 | 9825.10 | 18-DEC-04:02 | 4.00 |
Annual Sum or Average | 0.817884E+09 | |||
Minimum of Months | 29240763.22 | 5160.85 | 4.00 | |
Maximum of Months | 0.121601E+09 | 9825.10 | 40.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217472E+09 | 5540.52 | 01-JAN-14:33 | 14.73 |
February | 0.143918E+09 | 5287.17 | 07-FEB-06:02 | 9.00 |
March | 45739875.25 | 5378.65 | 26-MAR-16:07 | 18.30 |
April | 39900540.43 | 5158.65 | 23-APR-15:41 | 33.25 |
May | 34616588.65 | 4836.29 | 07-MAY-15:02 | 35.17 |
June | 28762079.07 | 6548.92 | 04-JUN-16:31 | 38.00 |
July | 38272292.23 | 6495.02 | 30-JUL-16:51 | 38.00 |
August | 33220393.94 | 5563.10 | 27-AUG-16:02 | 40.00 |
September | 33922850.78 | 4844.66 | 19-SEP-03:02 | 25.60 |
October | 44091042.73 | 5230.20 | 15-OCT-15:11 | 31.00 |
November | 46787415.60 | 5360.69 | 13-NOV-05:03 | 17.00 |
December | 0.298732E+09 | 5000.14 | 21-DEC-06:03 | 8.50 |
Annual Sum or Average | 0.100543E+10 | |||
Minimum of Months | 28762079.07 | 4836.29 | 8.50 | |
Maximum of Months | 0.298732E+09 | 6548.92 | 40.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160085E+10 | 13960.88 | 02-JAN-06:03 | 4.33 |
February | 0.141028E+10 | 7546.78 | 13-FEB-06:03 | 8.00 |
March | 0.125796E+10 | 13566.58 | 20-MAR-05:03 | 11.18 |
April | 0.370899E+09 | 13591.17 | 22-APR-05:03 | 11.00 |
May | 0.176581E+09 | 14837.69 | 01-MAY-05:02 | 13.00 |
June | 30411653.99 | 6063.70 | 22-JUN-03:02 | 23.50 |
July | 25664834.13 | 6393.69 | 07-JUL-03:02 | 24.67 |
August | 29166077.58 | 6587.41 | 30-AUG-05:02 | 21.83 |
September | 49265638.91 | 10765.03 | 22-SEP-05:02 | 17.10 |
October | 0.668834E+09 | 14366.53 | 12-OCT-05:02 | 7.00 |
November | 0.110406E+10 | 11040.02 | 02-NOV-05:02 | 16.00 |
December | 0.264515E+10 | 13049.72 | 18-DEC-06:03 | 3.83 |
Annual Sum or Average | 0.936912E+10 | |||
Minimum of Months | 25664834.13 | 6063.70 | 3.83 | |
Maximum of Months | 0.264515E+10 | 14837.69 | 24.67 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70561298.81 | 570.16 | 01-JAN-05:25 | 1.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 70561298.81 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 70561298.81 | 570.16 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113123E+11 | 11837.83 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.102611E+11 | 11837.83 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.121930E+11 | 11837.83 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.108909E+11 | 11837.83 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.117527E+11 | 11837.83 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.116958E+11 | 11837.83 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.109477E+11 | 11837.83 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.121930E+11 | 11837.83 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.108909E+11 | 11837.83 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.113123E+11 | 11837.83 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.111797E+11 | 11837.83 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.109477E+11 | 11837.83 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.135577E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.102611E+11 | 11837.83 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.121930E+11 | 11837.83 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.842154E+09 | 1224.17 | 20-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.732023E+09 | 1171.87 | 03-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.803708E+09 | 1100.61 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.685142E+09 | 898.31 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.717130E+09 | 713.37 | 26-MAY-08:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.697659E+09 | 635.12 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.666871E+09 | 727.68 | 13-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.767109E+09 | 1105.58 | 04-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.703589E+09 | 1002.41 | 29-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.796108E+09 | 1194.44 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.816393E+09 | 1334.85 | 28-NOV-16:30 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.833994E+09 | 1334.85 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.906188E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.666871E+09 | 635.12 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.842154E+09 | 1334.85 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.508629E+09 | 780.95 | 20-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.454228E+09 | 724.20 | 10-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.508509E+09 | 618.66 | 09-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.437459E+09 | 409.30 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.465505E+09 | 450.50 | 25-MAY-15:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.455210E+09 | 409.30 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.434534E+09 | 474.53 | 13-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.492319E+09 | 697.77 | 04-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.449185E+09 | 473.43 | 29-SEP-14:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.487655E+09 | 639.56 | 31-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.503161E+09 | 860.23 | 28-NOV-16:30 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.506165E+09 | 860.23 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.570256E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.434534E+09 | 409.30 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.508629E+09 | 860.23 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.761302E+09 | 1197.01 | 20-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.687188E+09 | 1138.07 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.780119E+09 | 1065.16 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.687093E+09 | 924.76 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.730549E+09 | 713.37 | 26-MAY-08:30 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.715565E+09 | 709.94 | 27-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.682614E+09 | 904.87 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.771672E+09 | 1110.17 | 04-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.695852E+09 | 904.69 | 29-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.733616E+09 | 1070.41 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.751873E+09 | 1334.88 | 28-NOV-16:30 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.752610E+09 | 1334.88 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.875005E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.682614E+09 | 709.94 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.780119E+09 | 1334.88 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522445E+09 | 797.30 | 20-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.462086E+09 | 757.70 | 03-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.514947E+09 | 755.88 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.445648E+09 | 649.13 | 04-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.470905E+09 | 551.00 | 05-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.459575E+09 | 536.43 | 27-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.439468E+09 | 607.94 | 27-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.500164E+09 | 723.16 | 04-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.455105E+09 | 692.80 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.498692E+09 | 776.61 | 27-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.505308E+09 | 860.23 | 28-NOV-16:30 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.512771E+09 | 860.23 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.578711E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.439468E+09 | 536.43 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.522445E+09 | 860.23 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.841191E+09 | 1226.43 | 20-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.731534E+09 | 1172.77 | 03-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.803199E+09 | 1105.67 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.684804E+09 | 903.22 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.718051E+09 | 710.58 | 26-MAY-08:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.697382E+09 | 635.12 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.666585E+09 | 725.21 | 13-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.766692E+09 | 1110.47 | 04-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.703225E+09 | 1009.25 | 29-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.794746E+09 | 1198.25 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.814966E+09 | 1334.85 | 28-NOV-16:30 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.833884E+09 | 1334.85 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.905626E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.666585E+09 | 635.12 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.841191E+09 | 1334.85 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.507954E+09 | 781.12 | 20-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.453706E+09 | 724.99 | 10-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.508154E+09 | 617.41 | 09-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.437499E+09 | 409.30 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.465395E+09 | 448.05 | 25-MAY-15:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.455063E+09 | 409.30 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.434264E+09 | 472.85 | 13-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.492099E+09 | 698.79 | 04-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.449013E+09 | 471.65 | 29-SEP-14:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.486957E+09 | 637.09 | 31-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.502700E+09 | 860.23 | 28-NOV-16:30 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.505735E+09 | 860.23 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.569854E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.434264E+09 | 409.30 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.508154E+09 | 860.23 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.761373E+09 | 1200.16 | 20-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.687196E+09 | 1142.42 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.780035E+09 | 1071.01 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.687065E+09 | 929.62 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.730343E+09 | 710.59 | 26-MAY-08:30 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.715316E+09 | 706.60 | 27-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.682395E+09 | 906.41 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.771512E+09 | 1114.92 | 04-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.695862E+09 | 900.32 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.732005E+09 | 1041.89 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.751342E+09 | 1334.88 | 28-NOV-16:30 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.752669E+09 | 1334.88 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.874711E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.682395E+09 | 706.60 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.780035E+09 | 1334.88 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.521537E+09 | 797.67 | 20-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.461461E+09 | 757.42 | 03-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.514693E+09 | 756.02 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.445529E+09 | 650.34 | 04-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.470628E+09 | 550.79 | 05-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.459200E+09 | 535.34 | 27-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.439088E+09 | 606.97 | 27-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.499725E+09 | 723.42 | 04-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.454971E+09 | 693.07 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.497997E+09 | 777.30 | 27-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.504662E+09 | 860.23 | 28-NOV-16:30 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.512034E+09 | 860.23 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.578153E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.439088E+09 | 535.34 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.521537E+09 | 860.23 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.841225E+09 | 1226.41 | 20-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.731498E+09 | 1172.86 | 03-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.803150E+09 | 1105.54 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.684788E+09 | 903.44 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.718067E+09 | 710.38 | 26-MAY-08:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.697378E+09 | 635.12 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.666573E+09 | 725.03 | 13-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.766673E+09 | 1110.22 | 04-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.703186E+09 | 1009.03 | 29-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.794766E+09 | 1198.36 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.815026E+09 | 1334.85 | 28-NOV-16:30 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.833893E+09 | 1334.85 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.905622E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.666573E+09 | 635.12 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.841225E+09 | 1334.85 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.507970E+09 | 781.03 | 20-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.453688E+09 | 724.88 | 10-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.508142E+09 | 617.60 | 09-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.437503E+09 | 409.30 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.465426E+09 | 447.90 | 25-MAY-15:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.455069E+09 | 409.30 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.434248E+09 | 472.75 | 13-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.492073E+09 | 698.64 | 04-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.449011E+09 | 471.57 | 29-SEP-14:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.487000E+09 | 637.24 | 31-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.502712E+09 | 860.23 | 28-NOV-16:30 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.505762E+09 | 860.23 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.569860E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.434248E+09 | 409.30 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.508142E+09 | 860.23 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.761394E+09 | 1200.02 | 20-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.687162E+09 | 1142.22 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.780008E+09 | 1070.88 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.687065E+09 | 929.82 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.730340E+09 | 710.38 | 26-MAY-08:30 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.715316E+09 | 706.54 | 27-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.682382E+09 | 906.61 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.771494E+09 | 1114.66 | 04-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.695855E+09 | 900.55 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.732005E+09 | 1041.94 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.751296E+09 | 1334.88 | 28-NOV-16:30 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.752670E+09 | 1334.88 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.874699E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.682382E+09 | 706.54 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.780008E+09 | 1334.88 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.521558E+09 | 797.65 | 20-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.461462E+09 | 757.50 | 03-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.514697E+09 | 755.94 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.445540E+09 | 650.53 | 04-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.470644E+09 | 551.03 | 05-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.459210E+09 | 535.59 | 27-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.439087E+09 | 607.17 | 27-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.499727E+09 | 723.26 | 04-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.454973E+09 | 692.93 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.498020E+09 | 777.31 | 27-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.504671E+09 | 860.23 | 28-NOV-16:30 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.512078E+09 | 860.23 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.578167E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.439087E+09 | 535.59 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.521558E+09 | 860.23 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.318958E+10 | 3337.76 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.289319E+10 | 3337.76 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.343791E+10 | 3337.76 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.307076E+10 | 3337.76 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.331375E+10 | 3337.76 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.329773E+10 | 3337.76 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.308678E+10 | 3337.76 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.343791E+10 | 3337.76 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.307076E+10 | 3337.76 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.318958E+10 | 3337.76 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.315220E+10 | 3337.76 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.308678E+10 | 3337.76 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.382269E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.289319E+10 | 3337.76 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.343791E+10 | 3337.76 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.113123E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.102611E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.108909E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.117527E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.116958E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.109477E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.108909E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.113123E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.111797E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.109477E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.135577E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.102611E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.842154E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 310028.19 | 84935019.66 |
February | 0.136985E+10 | 0.732023E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67575094.92 |
March | 0.163685E+10 | 0.803708E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 751367.02 | 86642133.63 |
April | 0.145243E+10 | 0.685142E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13610676.07 | 26102719.52 |
May | 0.157338E+10 | 0.717130E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25899024.17 | 16713756.48 |
June | 0.156900E+10 | 0.697659E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46675826.01 | 3798948.03 |
July | 0.145680E+10 | 0.666871E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46700076.36 | 3165198.06 |
August | 0.163685E+10 | 0.767109E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32853912.19 | 4855025.89 |
September | 0.145243E+10 | 0.703589E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24530861.38 | 10797163.96 |
October | 0.150991E+10 | 0.796108E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8940056.31 | 43418268.49 |
November | 0.149516E+10 | 0.816393E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 805946.89 | 77171711.64 |
December | 0.145680E+10 | 0.833994E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75583.31 | 82936026.63 |
Annual Sum or Average | 0.181194E+11 | 0.906188E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201153E+09 | 0.508111E+09 |
Minimum of Months | 0.136985E+10 | 0.666871E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3165198.06 |
Maximum of Months | 0.163685E+10 | 0.842154E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46700076.36 | 86642133.63 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.508629E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 175502.69 | 57928410.59 |
February | 0.882782E+09 | 0.454228E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45087810.31 |
March | 0.105485E+10 | 0.508509E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 495871.61 | 57546277.35 |
April | 0.936002E+09 | 0.437459E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8869617.80 | 17246708.54 |
May | 0.101394E+10 | 0.465505E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16635624.80 | 11462953.69 |
June | 0.101113E+10 | 0.455210E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31520538.59 | 2334679.53 |
July | 0.938820E+09 | 0.434534E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32031080.26 | 1844862.27 |
August | 0.105485E+10 | 0.492319E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22524611.20 | 2787736.25 |
September | 0.936002E+09 | 0.449185E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16314987.23 | 7127096.56 |
October | 0.973041E+09 | 0.487655E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5785646.98 | 29121523.27 |
November | 0.963541E+09 | 0.503161E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 487548.12 | 51152458.36 |
December | 0.938820E+09 | 0.506165E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49810.40 | 54678139.72 |
Annual Sum or Average | 0.116768E+11 | 0.570256E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134891E+09 | 0.338319E+09 |
Minimum of Months | 0.882782E+09 | 0.434534E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1844862.27 |
Maximum of Months | 0.105485E+10 | 0.508629E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32031080.26 | 57928410.59 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.761302E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 234571.21 | 93158246.97 |
February | 0.136988E+10 | 0.687188E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69532191.95 |
March | 0.163688E+10 | 0.780119E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 663367.75 | 89150190.07 |
April | 0.145246E+10 | 0.687093E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12302600.93 | 27650619.67 |
May | 0.157341E+10 | 0.730549E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25276182.39 | 16943454.14 |
June | 0.156904E+10 | 0.715565E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47100134.12 | 3663042.75 |
July | 0.145684E+10 | 0.682614E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46560236.70 | 3122484.24 |
August | 0.163688E+10 | 0.771672E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32008694.16 | 5106600.53 |
September | 0.145246E+10 | 0.695852E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22851442.03 | 12158222.68 |
October | 0.150994E+10 | 0.733616E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7722022.26 | 47423606.81 |
November | 0.149520E+10 | 0.751873E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 423065.47 | 82634155.27 |
December | 0.145684E+10 | 0.752610E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21632.38 | 87697849.62 |
Annual Sum or Average | 0.181198E+11 | 0.875005E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195164E+09 | 0.538241E+09 |
Minimum of Months | 0.136988E+10 | 0.682614E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3122484.24 |
Maximum of Months | 0.163688E+10 | 0.780119E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47100134.12 | 93158246.97 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.522445E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 160784.70 | 62852962.82 |
February | 0.882782E+09 | 0.462086E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50239775.93 |
March | 0.105485E+10 | 0.514947E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 430766.77 | 66358984.25 |
April | 0.936002E+09 | 0.445648E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7553261.24 | 22204020.27 |
May | 0.101394E+10 | 0.470905E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15758006.00 | 13477184.61 |
June | 0.101113E+10 | 0.459575E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29555674.64 | 3250039.33 |
July | 0.938820E+09 | 0.439468E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28752751.09 | 3168101.92 |
August | 0.105485E+10 | 0.500164E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19642105.95 | 5159373.92 |
September | 0.936002E+09 | 0.455105E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15224536.62 | 9026813.07 |
October | 0.973041E+09 | 0.498692E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5284639.19 | 33899273.52 |
November | 0.963541E+09 | 0.505308E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 297781.66 | 59736090.01 |
December | 0.938820E+09 | 0.512771E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14666.06 | 63742083.38 |
Annual Sum or Average | 0.116768E+11 | 0.578711E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122675E+09 | 0.393115E+09 |
Minimum of Months | 0.882782E+09 | 0.439468E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3168101.92 |
Maximum of Months | 0.105485E+10 | 0.522445E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29555674.64 | 66358984.25 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.841191E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1825469.95 | 0.172660E+09 |
February | 0.136985E+10 | 0.731534E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137985E+09 |
March | 0.163685E+10 | 0.803199E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1778657.36 | 0.182919E+09 |
April | 0.145243E+10 | 0.684804E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33439643.73 | 62373955.69 |
May | 0.157338E+10 | 0.718051E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60453580.01 | 40261610.33 |
June | 0.156900E+10 | 0.697382E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106819E+09 | 10245709.74 |
July | 0.145680E+10 | 0.666585E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106535E+09 | 9697417.09 |
August | 0.163685E+10 | 0.766692E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75409314.01 | 13754052.45 |
September | 0.145243E+10 | 0.703225E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55780909.81 | 27017760.32 |
October | 0.150991E+10 | 0.794746E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21936805.14 | 93740931.61 |
November | 0.149516E+10 | 0.814966E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3076638.75 | 0.158206E+09 |
December | 0.145680E+10 | 0.833884E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 846419.33 | 0.165125E+09 |
Annual Sum or Average | 0.181194E+11 | 0.905626E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467902E+09 | 0.107399E+10 |
Minimum of Months | 0.136985E+10 | 0.666585E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9697417.09 |
Maximum of Months | 0.163685E+10 | 0.841191E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106819E+09 | 0.182919E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.507954E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 586666.42 | 0.123258E+09 |
February | 0.649041E+09 | 0.453706E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97162402.42 |
March | 0.773965E+09 | 0.508154E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1050045.39 | 0.129398E+09 |
April | 0.688021E+09 | 0.437499E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19728989.62 | 46006229.20 |
May | 0.744847E+09 | 0.465395E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37678416.99 | 29109801.85 |
June | 0.742030E+09 | 0.455063E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70998894.14 | 6987336.42 |
July | 0.690839E+09 | 0.434264E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70241068.87 | 6957228.28 |
August | 0.773965E+09 | 0.492099E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48660586.70 | 10174699.58 |
September | 0.688021E+09 | 0.449013E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35847536.84 | 19553982.95 |
October | 0.715730E+09 | 0.486957E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12970352.58 | 67456232.55 |
November | 0.708685E+09 | 0.502700E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1264282.66 | 0.111972E+09 |
December | 0.690839E+09 | 0.505735E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 295045.99 | 0.115848E+09 |
Annual Sum or Average | 0.858171E+10 | 0.569854E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299322E+09 | 0.763884E+09 |
Minimum of Months | 0.649041E+09 | 0.434264E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6957228.28 |
Maximum of Months | 0.773965E+09 | 0.508154E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70998894.14 | 0.129398E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.761373E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 457856.12 | 0.214481E+09 |
February | 0.136988E+10 | 0.687196E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157165E+09 |
March | 0.163688E+10 | 0.780035E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1456533.11 | 0.202618E+09 |
April | 0.145246E+10 | 0.687065E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28358862.15 | 68658485.14 |
May | 0.157341E+10 | 0.730343E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58410476.38 | 41360196.53 |
June | 0.156904E+10 | 0.715316E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108256E+09 | 9797824.44 |
July | 0.145684E+10 | 0.682395E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106113E+09 | 9566616.47 |
August | 0.163688E+10 | 0.771512E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72544695.83 | 14989212.64 |
September | 0.145246E+10 | 0.695862E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51079575.16 | 31551599.32 |
October | 0.150994E+10 | 0.732005E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17239142.28 | 0.111556E+09 |
November | 0.149520E+10 | 0.751342E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 877307.15 | 0.188842E+09 |
December | 0.145684E+10 | 0.752669E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42564.81 | 0.198127E+09 |
Annual Sum or Average | 0.181198E+11 | 0.874711E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444836E+09 | 0.124871E+10 |
Minimum of Months | 0.136988E+10 | 0.682395E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9566616.47 |
Maximum of Months | 0.163688E+10 | 0.780035E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108256E+09 | 0.214481E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.521537E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 531899.90 | 0.129380E+09 |
February | 0.882782E+09 | 0.461461E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99827715.16 |
March | 0.105485E+10 | 0.514693E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 976991.85 | 0.134138E+09 |
April | 0.936002E+09 | 0.445529E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18109474.37 | 50364560.21 |
May | 0.101394E+10 | 0.470628E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36427393.18 | 31868843.14 |
June | 0.101113E+10 | 0.459200E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68861069.32 | 8160289.26 |
July | 0.938820E+09 | 0.439088E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67644497.95 | 8124163.43 |
August | 0.105485E+10 | 0.499725E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46865585.85 | 11450279.42 |
September | 0.936002E+09 | 0.454971E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34683052.14 | 21344162.60 |
October | 0.973041E+09 | 0.497997E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12612196.37 | 70898404.92 |
November | 0.963541E+09 | 0.504662E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1193535.23 | 0.117788E+09 |
December | 0.938820E+09 | 0.512034E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 148094.69 | 0.120970E+09 |
Annual Sum or Average | 0.116768E+11 | 0.578153E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288054E+09 | 0.804315E+09 |
Minimum of Months | 0.882782E+09 | 0.439088E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8124163.43 |
Maximum of Months | 0.105485E+10 | 0.521537E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68861069.32 | 0.134138E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.841225E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3345790.85 | 0.189129E+09 |
February | 0.136985E+10 | 0.731498E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.51 | 0.151041E+09 |
March | 0.163685E+10 | 0.803150E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2119032.29 | 0.209139E+09 |
April | 0.145243E+10 | 0.684788E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39087382.41 | 76340733.51 |
May | 0.157338E+10 | 0.718067E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71253787.08 | 50380597.78 |
June | 0.156900E+10 | 0.697378E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128420E+09 | 13451605.86 |
July | 0.145680E+10 | 0.666573E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126735E+09 | 12891378.59 |
August | 0.163685E+10 | 0.766673E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89804095.11 | 17672929.64 |
September | 0.145243E+10 | 0.703186E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66199127.79 | 35088132.54 |
October | 0.150991E+10 | 0.794766E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26955364.62 | 0.108822E+09 |
November | 0.149516E+10 | 0.815026E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4834293.94 | 0.175668E+09 |
December | 0.145680E+10 | 0.833893E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1851404.39 | 0.181919E+09 |
Annual Sum or Average | 0.181194E+11 | 0.905622E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560606E+09 | 0.122154E+10 |
Minimum of Months | 0.136985E+10 | 0.666573E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.51 | 12891378.59 |
Maximum of Months | 0.163685E+10 | 0.841225E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128420E+09 | 0.209139E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.507970E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1089963.12 | 0.137565E+09 |
February | 0.882782E+09 | 0.453688E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108303E+09 |
March | 0.105485E+10 | 0.508142E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1212287.40 | 0.150767E+09 |
April | 0.936002E+09 | 0.437503E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23162761.97 | 57112031.20 |
May | 0.101394E+10 | 0.465426E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44909987.60 | 36629546.45 |
June | 0.101113E+10 | 0.455069E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85497539.16 | 9118123.51 |
July | 0.938820E+09 | 0.434248E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84030866.05 | 9140940.12 |
August | 0.105485E+10 | 0.492073E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58358379.33 | 13075524.41 |
September | 0.936002E+09 | 0.449011E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43040283.89 | 25280017.09 |
October | 0.973041E+09 | 0.487000E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15690278.71 | 80156193.26 |
November | 0.963541E+09 | 0.502712E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1847156.36 | 0.126413E+09 |
December | 0.938820E+09 | 0.505762E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 624484.70 | 0.128483E+09 |
Annual Sum or Average | 0.116768E+11 | 0.569860E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359464E+09 | 0.882043E+09 |
Minimum of Months | 0.882782E+09 | 0.434248E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9118123.51 |
Maximum of Months | 0.105485E+10 | 0.508142E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85497539.16 | 0.150767E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.761394E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 589486.72 | 0.246082E+09 |
February | 0.136988E+10 | 0.687162E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177269E+09 |
March | 0.163688E+10 | 0.780008E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1693165.31 | 0.236690E+09 |
April | 0.145246E+10 | 0.687065E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33749184.23 | 84613751.81 |
May | 0.157341E+10 | 0.730340E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69653765.26 | 51604908.23 |
June | 0.156904E+10 | 0.715316E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130136E+09 | 12718000.37 |
July | 0.145684E+10 | 0.682382E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126921E+09 | 12614021.52 |
August | 0.163688E+10 | 0.771494E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87221732.55 | 19202554.54 |
September | 0.145246E+10 | 0.695855E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61744226.55 | 40812313.34 |
October | 0.150994E+10 | 0.732005E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20920917.44 | 0.133453E+09 |
November | 0.149520E+10 | 0.751296E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1083124.32 | 0.218106E+09 |
December | 0.145684E+10 | 0.752670E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48764.98 | 0.225394E+09 |
Annual Sum or Average | 0.181198E+11 | 0.874699E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533762E+09 | 0.145856E+10 |
Minimum of Months | 0.136988E+10 | 0.682382E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12614021.52 |
Maximum of Months | 0.163688E+10 | 0.780008E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130136E+09 | 0.246082E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.521558E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 881207.43 | 0.146924E+09 |
February | 0.882782E+09 | 0.461462E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113020E+09 |
March | 0.105485E+10 | 0.514697E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1184236.57 | 0.156883E+09 |
April | 0.936002E+09 | 0.445540E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21935178.66 | 61864076.74 |
May | 0.101394E+10 | 0.470644E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44377541.44 | 39755898.25 |
June | 0.101113E+10 | 0.459210E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84096308.12 | 10291498.91 |
July | 0.938820E+09 | 0.439087E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82391917.14 | 10288053.93 |
August | 0.105485E+10 | 0.499727E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57026188.05 | 14326634.68 |
September | 0.936002E+09 | 0.454973E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42392719.87 | 27107357.47 |
October | 0.973041E+09 | 0.498020E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15586873.47 | 84111581.99 |
November | 0.963541E+09 | 0.504671E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1703173.15 | 0.134914E+09 |
December | 0.938820E+09 | 0.512078E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 336336.93 | 0.137041E+09 |
Annual Sum or Average | 0.116768E+11 | 0.578167E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351912E+09 | 0.936527E+09 |
Minimum of Months | 0.882782E+09 | 0.439087E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10288053.93 |
Maximum of Months | 0.105485E+10 | 0.521558E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84096308.12 | 0.156883E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.318958E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.289319E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.343791E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.307076E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.331375E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.329773E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.308678E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.343791E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.307076E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.318958E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.315220E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.308678E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.382269E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.289319E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.343791E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313158.57 | 0.187761E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145760E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1044910.03 | 0.186500E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24377292.74 | 59595985.07 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48336648.19 | 36458075.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90012751.13 | 9099712.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90130538.58 | 7845161.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61141106.36 | 12343864.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45258600.93 | 23363308.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15443745.24 | 95609010.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 886368.87 | 0.168503E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33506.73 | 0.180729E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376979E+09 | 0.111357E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7845161.61 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90130538.58 | 0.187761E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 687618.34 | 0.315828E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247439E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2062945.21 | 0.320695E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46110615.81 | 0.106418E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88490763.83 | 65373619.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163267E+09 | 16524143.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165148E+09 | 14254573.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112845E+09 | 22387953.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82151553.22 | 41788815.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28945689.03 | 0.165811E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2429065.53 | 0.286105E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316465.09 | 0.301888E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692454E+09 | 0.190451E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14254573.30 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165148E+09 | 0.320695E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 702186.86 | 0.308250E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246373E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1289580.80 | 0.333063E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41004655.57 | 0.115735E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85805932.23 | 69002106.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172417E+09 | 18002780.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167408E+09 | 16663424.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117040E+09 | 24733333.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83633577.46 | 48980535.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29029050.75 | 0.171773E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2584030.53 | 0.283485E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453150.85 | 0.289889E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701367E+09 | 0.192595E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16663424.76 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172417E+09 | 0.333063E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 11837.83 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 11837.83 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 11837.83 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 11837.83 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 11837.83 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 11837.83 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 11837.83 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 11837.83 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 11837.83 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 11837.83 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 11837.83 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 11837.83 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 11837.83 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 11837.83 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1224.17 | 20-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.88 | 29-JAN-15:52 | 186.57 | 01-JAN-00:53 |
February | 2010.79 | 01-FEB-10:09 | 1171.87 | 03-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 195.71 | 02-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 1100.61 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 | 18-MAR-17:02 | 170.32 | 28-MAR-04:00 |
April | 2010.79 | 03-APR-09:09 | 898.31 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.47 | 30-APR-15:10 | 82.77 | 21-APR-05:00 |
May | 2010.79 | 01-MAY-09:09 | 713.37 | 26-MAY-08:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.96 | 20-MAY-17:30 | 65.47 | 23-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 635.12 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.34 | 17-JUN-17:03 | 31.68 | 13-JUN-04:00 |
July | 2010.79 | 03-JUL-09:09 | 727.68 | 13-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.82 | 22-JUL-17:45 | 46.23 | 27-JUL-00:30 |
August | 2010.79 | 01-AUG-09:09 | 1105.58 | 04-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.88 | 13-AUG-15:51 | 80.50 | 05-AUG-17:57 |
September | 2010.79 | 01-SEP-09:09 | 1002.41 | 29-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.46 | 17-SEP-12:10 | 62.43 | 03-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1194.44 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.87 | 01-OCT-14:50 | 169.49 | 22-OCT-14:00 |
November | 2010.79 | 01-NOV-09:09 | 1334.85 | 28-NOV-16:30 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 | 19-NOV-15:00 | 170.60 | 29-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1334.85 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 | 25-DEC-15:53 | 140.61 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.68 | |||||
Maximum of Months | 2010.79 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 180.82 | 195.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 780.95 | 20-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 | 29-JAN-15:52 | 126.39 | 01-JAN-00:53 |
February | 1295.83 | 01-FEB-10:09 | 724.20 | 10-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 130.71 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 618.66 | 09-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.93 | 18-MAR-17:02 | 112.69 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 409.30 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.71 | 30-APR-15:50 | 71.24 | 16-APR-08:40 |
May | 1295.83 | 01-MAY-09:09 | 450.50 | 25-MAY-15:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.39 | 20-MAY-17:30 | 43.30 | 23-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 409.30 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.37 | 17-JUN-17:03 | 22.21 | 11-JUN-06:20 |
July | 1295.83 | 03-JUL-09:09 | 474.53 | 13-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.34 | 22-JUL-18:00 | 28.89 | 27-JUL-00:30 |
August | 1295.83 | 01-AUG-09:09 | 697.77 | 04-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.03 | 13-AUG-15:51 | 52.51 | 05-AUG-17:57 |
September | 1295.83 | 01-SEP-09:09 | 473.43 | 29-SEP-14:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.91 | 17-SEP-11:53 | 40.48 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 639.56 | 31-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.20 | 01-OCT-14:40 | 118.05 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 28-NOV-16:30 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.90 | 19-NOV-15:00 | 112.13 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.20 | 25-DEC-15:53 | 92.39 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.21 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 125.34 | 130.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1197.01 | 20-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 | 31-JAN-14:00 | 190.74 | 01-JAN-00:53 |
February | 2010.83 | 01-FEB-10:09 | 1138.07 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 210.77 | 02-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 1065.16 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.53 | 15-MAR-13:00 | 171.02 | 28-MAR-04:00 |
April | 2010.83 | 03-APR-09:09 | 924.76 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.50 | 30-APR-15:45 | 83.04 | 21-APR-05:00 |
May | 2010.83 | 01-MAY-09:09 | 713.37 | 26-MAY-08:30 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.87 | 20-MAY-17:30 | 65.30 | 23-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 709.94 | 27-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.07 | 17-JUN-17:03 | 31.11 | 13-JUN-04:00 |
July | 2010.83 | 03-JUL-09:09 | 904.87 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.38 | 22-JUL-18:00 | 46.32 | 27-JUL-00:30 |
August | 2010.83 | 01-AUG-09:09 | 1110.17 | 04-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.45 | 13-AUG-15:51 | 83.40 | 05-AUG-17:57 |
September | 2010.83 | 01-SEP-09:09 | 904.69 | 29-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.37 | 17-SEP-12:28 | 64.56 | 03-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 1070.41 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.35 | 01-OCT-14:38 | 186.33 | 22-OCT-14:00 |
November | 2010.83 | 01-NOV-09:09 | 1334.88 | 28-NOV-16:30 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.10 | 01-NOV-16:00 | 177.55 | 29-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1334.88 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.10 | 21-DEC-15:00 | 143.91 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 709.94 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.11 | |||||
Maximum of Months | 2010.83 | 1334.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 183.38 | 210.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 797.30 | 20-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 | 31-JAN-14:00 | 133.77 | 01-JAN-00:53 |
February | 1295.83 | 01-FEB-10:09 | 757.70 | 03-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 149.36 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 755.88 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.02 | 15-MAR-13:00 | 127.12 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 649.13 | 04-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.18 | 30-APR-15:04 | 66.37 | 26-APR-21:17 |
May | 1295.83 | 01-MAY-09:09 | 551.00 | 05-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.17 | 20-MAY-17:47 | 47.90 | 23-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 536.43 | 27-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.52 | 17-JUN-17:10 | 25.79 | 13-JUN-04:00 |
July | 1295.83 | 03-JUL-09:09 | 607.94 | 27-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.72 | 22-JUL-18:00 | 43.20 | 26-JUL-23:50 |
August | 1295.83 | 01-AUG-09:09 | 723.16 | 04-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.30 | 13-AUG-16:00 | 64.80 | 05-AUG-17:57 |
September | 1295.83 | 01-SEP-09:09 | 692.80 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.76 | 17-SEP-11:53 | 48.67 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 776.61 | 27-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.80 | 01-OCT-14:38 | 128.74 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 28-NOV-16:30 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.42 | 01-NOV-16:00 | 129.68 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 | 21-DEC-15:00 | 104.40 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 536.43 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.79 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 119.72 | 149.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1226.43 | 20-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.53 | 16-JAN-12:00 | 338.81 | 01-JAN-00:53 |
February | 2010.79 | 01-FEB-10:09 | 1172.77 | 03-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 409.00 | 02-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 1105.67 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.93 | 18-MAR-17:02 | 358.56 | 28-MAR-04:00 |
April | 2010.79 | 03-APR-09:09 | 903.22 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.30 | 30-APR-15:10 | 186.46 | 21-APR-05:00 |
May | 2010.79 | 01-MAY-09:09 | 710.58 | 26-MAY-08:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.74 | 20-MAY-17:30 | 153.28 | 23-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 635.12 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.70 | 17-JUN-17:03 | 78.41 | 25-JUN-06:00 |
July | 2010.79 | 03-JUL-09:09 | 725.21 | 13-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.17 | 22-JUL-18:00 | 131.27 | 26-JUL-24:00 |
August | 2010.79 | 01-AUG-09:09 | 1110.47 | 04-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.43 | 13-AUG-16:05 | 184.73 | 05-AUG-17:43 |
September | 2010.79 | 01-SEP-09:09 | 1009.25 | 29-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.82 | 17-SEP-12:00 | 140.13 | 03-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1198.25 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.36 | 01-OCT-14:32 | 351.66 | 22-OCT-14:00 |
November | 2010.79 | 01-NOV-09:09 | 1334.85 | 28-NOV-16:30 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.90 | 19-NOV-15:00 | 350.59 | 29-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1334.85 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.69 | 25-DEC-15:53 | 294.13 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.41 | |||||
Maximum of Months | 2010.79 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 421.17 | 409.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 781.12 | 20-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.18 | 29-JAN-15:52 | 238.76 | 01-JAN-00:53 |
February | 1239.33 | 01-FEB-08:09 | 724.99 | 10-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 284.72 | 02-FEB-23:00 |
March | 1239.33 | 01-MAR-08:09 | 617.41 | 09-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 18-MAR-17:02 | 246.38 | 28-MAR-04:00 |
April | 1239.33 | 03-APR-07:10 | 409.30 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.74 | 30-APR-15:30 | 176.42 | 16-APR-09:00 |
May | 1239.33 | 01-MAY-07:10 | 448.05 | 25-MAY-15:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.23 | 20-MAY-17:30 | 103.89 | 23-MAY-05:00 |
June | 1239.33 | 01-JUN-07:10 | 409.30 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.52 | 17-JUN-17:03 | 58.47 | 25-JUN-06:00 |
July | 1239.33 | 03-JUL-07:10 | 472.85 | 13-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.54 | 22-JUL-18:00 | 90.82 | 26-JUL-24:00 |
August | 1239.33 | 01-AUG-07:10 | 698.79 | 04-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.81 | 13-AUG-16:05 | 128.25 | 05-AUG-17:43 |
September | 1239.33 | 01-SEP-07:10 | 471.65 | 29-SEP-14:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.62 | 17-SEP-12:00 | 95.62 | 03-SEP-05:00 |
October | 1239.33 | 02-OCT-07:10 | 637.09 | 31-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.29 | 01-OCT-14:30 | 266.93 | 22-OCT-14:00 |
November | 1239.33 | 01-NOV-07:10 | 860.23 | 28-NOV-16:30 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.16 | 19-NOV-15:00 | 241.43 | 29-NOV-02:00 |
December | 1239.33 | 01-DEC-08:09 | 860.23 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.85 | 25-DEC-15:53 | 199.65 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.47 | |||||
Maximum of Months | 1239.33 | 860.23 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 288.54 | 284.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1200.16 | 20-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 31-JAN-15:00 | 422.75 | 01-JAN-00:53 |
February | 2010.83 | 01-FEB-10:09 | 1142.42 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 475.32 | 02-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 1071.01 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 | 15-MAR-13:00 | 382.27 | 28-MAR-04:00 |
April | 2010.83 | 03-APR-09:09 | 929.62 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.52 | 30-APR-15:24 | 191.76 | 21-APR-05:00 |
May | 2010.83 | 01-MAY-09:09 | 710.59 | 26-MAY-08:30 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.20 | 20-MAY-17:30 | 154.00 | 23-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 706.60 | 27-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.17 | 17-JUN-17:03 | 70.70 | 13-JUN-03:53 |
July | 2010.83 | 03-JUL-09:09 | 906.41 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 428.23 | 22-JUL-18:00 | 131.05 | 26-JUL-24:00 |
August | 2010.83 | 01-AUG-09:09 | 1114.92 | 04-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 376.15 | 13-AUG-16:05 | 194.99 | 05-AUG-17:43 |
September | 2010.83 | 01-SEP-09:09 | 900.32 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.73 | 17-SEP-12:00 | 147.17 | 03-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 1041.89 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.02 | 01-OCT-14:28 | 427.15 | 22-OCT-14:00 |
November | 2010.83 | 01-NOV-09:09 | 1334.88 | 28-NOV-16:30 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 01-NOV-16:10 | 393.11 | 29-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1334.88 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 | 21-DEC-15:00 | 323.05 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 706.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.70 | |||||
Maximum of Months | 2010.83 | 1334.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 428.23 | 475.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 797.67 | 20-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 | 16-JAN-12:00 | 259.67 | 01-JAN-00:53 |
February | 1295.83 | 01-FEB-10:09 | 757.42 | 03-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 302.44 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 756.02 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.90 | 15-MAR-13:00 | 257.88 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 650.34 | 04-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.28 | 30-APR-14:43 | 136.60 | 26-APR-21:20 |
May | 1295.83 | 01-MAY-09:09 | 550.79 | 05-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.64 | 20-MAY-17:47 | 110.37 | 23-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 535.34 | 27-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.52 | 17-JUN-17:03 | 56.69 | 25-JUN-06:00 |
July | 1295.83 | 03-JUL-09:09 | 606.97 | 27-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.08 | 22-JUL-18:00 | 104.26 | 26-JUL-24:00 |
August | 1295.83 | 01-AUG-09:09 | 723.42 | 04-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.30 | 13-AUG-16:10 | 133.61 | 05-AUG-17:43 |
September | 1295.83 | 01-SEP-09:09 | 693.07 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.32 | 17-SEP-12:00 | 98.70 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 777.30 | 27-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.41 | 01-OCT-14:28 | 250.15 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 28-NOV-16:30 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.33 | 19-NOV-12:40 | 247.89 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | 25-DEC-13:52 | 205.57 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 535.34 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.69 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 278.08 | 302.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1226.41 | 20-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 78.68 | 16-JAN-12:00 | 327.00 | 01-JAN-00:53 |
February | 2010.79 | 01-FEB-10:09 | 1172.86 | 03-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 | 18-FEB-14:00 | 460.72 | 02-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 1105.54 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.94 | 18-MAR-17:02 | 403.85 | 28-MAR-04:00 |
April | 2010.79 | 03-APR-09:09 | 903.44 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 283.55 | 30-APR-15:00 | 219.49 | 26-APR-21:10 |
May | 2010.79 | 01-MAY-09:09 | 710.38 | 26-MAY-08:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 257.84 | 20-MAY-17:30 | 186.66 | 23-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 635.12 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 409.31 | 17-JUN-17:10 | 99.74 | 25-JUN-06:00 |
July | 2010.79 | 03-JUL-09:09 | 725.03 | 13-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 519.96 | 22-JUL-17:45 | 165.20 | 26-JUL-24:00 |
August | 2010.79 | 01-AUG-09:09 | 1110.22 | 04-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 463.30 | 13-AUG-16:05 | 240.30 | 05-AUG-17:43 |
September | 2010.79 | 01-SEP-09:09 | 1009.03 | 29-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.02 | 17-SEP-12:00 | 180.54 | 03-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1198.36 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.31 | 01-OCT-14:28 | 420.23 | 22-OCT-14:00 |
November | 2010.79 | 01-NOV-09:09 | 1334.85 | 28-NOV-16:30 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.29 | 19-NOV-13:00 | 398.22 | 29-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1334.85 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 64.06 | 25-DEC-15:53 | 337.74 | 07-DEC-05:09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 | 99.74 | |||||
Maximum of Months | 2010.79 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 519.96 | 460.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 781.03 | 20-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.12 | 16-JAN-13:52 | 236.04 | 01-JAN-00:53 |
February | 1295.83 | 01-FEB-10:09 | 724.88 | 10-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 324.67 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 617.60 | 09-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.28 | 18-MAR-17:02 | 279.99 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 409.30 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.71 | 30-APR-15:35 | 203.63 | 16-APR-08:30 |
May | 1295.83 | 01-MAY-09:09 | 447.90 | 25-MAY-15:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.73 | 20-MAY-17:50 | 127.20 | 23-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 409.30 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.56 | 17-JUN-17:10 | 74.11 | 25-JUN-06:00 |
July | 1295.83 | 03-JUL-09:09 | 472.75 | 13-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.00 | 22-JUL-17:45 | 113.80 | 26-JUL-24:00 |
August | 1295.83 | 01-AUG-09:09 | 698.64 | 04-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.18 | 13-AUG-16:05 | 167.18 | 05-AUG-17:43 |
September | 1295.83 | 01-SEP-09:09 | 471.57 | 29-SEP-14:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.41 | 17-SEP-12:00 | 122.95 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 637.24 | 31-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.22 | 01-OCT-14:28 | 323.33 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 28-NOV-16:30 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.84 | 19-NOV-15:00 | 277.83 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.20 | 25-DEC-16:10 | 226.21 | 07-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.11 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 351.00 | 324.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1200.02 | 20-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.70 | 31-JAN-14:00 | 439.87 | 01-JAN-00:53 |
February | 2010.83 | 01-FEB-10:09 | 1142.22 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 553.91 | 02-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 1070.88 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.57 | 15-MAR-13:00 | 437.90 | 28-MAR-04:00 |
April | 2010.83 | 03-APR-09:09 | 929.82 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.01 | 30-APR-14:54 | 231.19 | 26-APR-21:10 |
May | 2010.83 | 01-MAY-09:09 | 710.38 | 26-MAY-08:30 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.83 | 20-MAY-17:50 | 187.28 | 23-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 706.54 | 27-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 409.32 | 17-JUN-17:10 | 89.95 | 25-JUN-06:00 |
July | 2010.83 | 03-JUL-09:09 | 906.61 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 522.57 | 22-JUL-17:45 | 164.64 | 26-JUL-24:00 |
August | 2010.83 | 01-AUG-09:09 | 1114.66 | 04-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 453.51 | 13-AUG-16:05 | 253.68 | 05-AUG-17:43 |
September | 2010.83 | 01-SEP-09:09 | 900.55 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 349.32 | 17-SEP-12:00 | 189.33 | 03-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 1041.94 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.52 | 01-OCT-14:28 | 518.25 | 22-OCT-14:00 |
November | 2010.83 | 01-NOV-09:09 | 1334.88 | 28-NOV-16:30 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.31 | 01-NOV-16:00 | 459.18 | 29-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1334.88 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 21-DEC-15:00 | 366.81 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 706.54 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.95 | |||||
Maximum of Months | 2010.83 | 1334.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 522.57 | 553.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 797.65 | 20-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.41 | 16-JAN-12:00 | 273.97 | 01-JAN-00:53 |
February | 1295.83 | 01-FEB-10:09 | 757.50 | 03-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 350.29 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 755.94 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.04 | 15-MAR-13:00 | 298.78 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 650.53 | 04-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.04 | 30-APR-15:34 | 169.62 | 26-APR-21:20 |
May | 1295.83 | 01-MAY-09:09 | 551.03 | 05-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.09 | 20-MAY-17:47 | 135.61 | 23-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 535.59 | 27-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 274.53 | 17-JUN-17:10 | 70.74 | 25-JUN-06:00 |
July | 1295.83 | 03-JUL-09:09 | 607.17 | 27-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.86 | 22-JUL-18:00 | 130.38 | 26-JUL-24:00 |
August | 1295.83 | 01-AUG-09:09 | 723.26 | 04-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.36 | 13-AUG-16:10 | 172.45 | 05-AUG-17:43 |
September | 1295.83 | 01-SEP-09:09 | 692.93 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.95 | 17-SEP-12:00 | 125.78 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 777.31 | 27-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.51 | 01-OCT-14:28 | 302.91 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 28-NOV-16:30 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.89 | 19-NOV-12:40 | 287.69 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.14 | 25-DEC-13:52 | 234.76 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 535.59 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.74 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 341.86 | 350.29 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 3337.76 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 3337.76 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 3337.76 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 3337.76 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 3337.76 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 3337.76 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 3337.76 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 3337.76 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 3337.76 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 3337.76 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 3337.76 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 3337.76 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 3337.76 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 | 31-JAN-14:00 | 411.96 | 01-JAN-00:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 428.47 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.72 | 18-MAR-17:02 | 365.58 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.29 | 30-APR-14:51 | 178.84 | 21-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.93 | 20-MAY-17:02 | 140.90 | 23-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.81 | 17-JUN-17:03 | 66.56 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.64 | 22-JUL-18:00 | 101.22 | 26-JUL-23:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.91 | 13-AUG-16:00 | 160.81 | 05-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.65 | 17-SEP-12:00 | 119.77 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.86 | 01-OCT-14:23 | 327.31 | 22-OCT-14:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.75 | 19-NOV-15:00 | 365.63 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 | 21-DEC-15:00 | 305.24 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.56 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.64 | 428.47 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.03 | 31-JAN-14:00 | 632.60 | 01-JAN-00:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 748.85 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.39 | 18-MAR-17:02 | 630.33 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.51 | 30-APR-15:10 | 321.78 | 21-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.84 | 20-MAY-17:30 | 253.74 | 23-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.32 | 17-JUN-17:03 | 119.50 | 13-JUN-03:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 693.42 | 22-JUL-18:00 | 191.13 | 26-JUL-23:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.58 | 13-AUG-15:51 | 286.42 | 05-AUG-17:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.76 | 17-SEP-11:53 | 212.72 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.02 | 01-OCT-14:50 | 558.73 | 22-OCT-14:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.20 | 19-NOV-15:00 | 620.68 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.58 | 25-DEC-16:00 | 527.82 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.50 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 693.42 | 748.85 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.97 | 16-JAN-11:53 | 539.81 | 01-JAN-00:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 737.39 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.45 | 18-MAR-17:02 | 623.82 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.86 | 30-APR-16:00 | 325.58 | 26-APR-21:03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.69 | 20-MAY-17:30 | 269.17 | 23-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 589.34 | 17-JUN-17:03 | 131.61 | 13-JUN-03:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 708.02 | 22-JUL-18:00 | 233.59 | 26-JUL-23:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.89 | 13-AUG-15:51 | 366.39 | 05-AUG-17:43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.12 | 17-SEP-12:20 | 260.89 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.65 | 01-OCT-14:40 | 721.19 | 22-OCT-14:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.56 | 19-NOV-15:00 | 623.07 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.10 | 25-DEC-15:53 | 508.31 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.61 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 708.02 | 737.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 98398.74 | 02-JAN-04:01 | 0.00 | 4604.05 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 96511.18 | 21-FEB-04:03 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 97543.52 | 20-MAR-03:02 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 92654.98 | 03-APR-03:02 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 93785.47 | 01-MAY-03:03 | 0.00 | 1973.16 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 89787.91 | 12-JUN-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88160.68 | 05-JUL-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87571.94 | 27-AUG-16:40 | 8078.51 | 5919.49 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 88002.73 | 18-SEP-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 100151.09 | 23-OCT-03:02 | 0.00 | 3946.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98254.71 | 27-NOV-04:03 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 99347.34 | 18-DEC-04:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 87571.94 | 0.00 | 1973.16 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 100151.09 | 8078.51 | 5919.49 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 81835.26 | 02-JAN-04:01 | 0.00 | 4134.76 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 81851.39 | 21-FEB-04:03 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 81975.55 | 06-MAR-04:03 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 76221.92 | 21-APR-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76897.79 | 02-MAY-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 71575.09 | 26-JUN-05:02 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 74158.74 | 24-JUL-05:03 | 9673.43 | 7087.27 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 79646.87 | 14-AUG-05:05 | 9673.43 | 7087.27 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79762.42 | 11-SEP-05:04 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86729.65 | 23-OCT-03:02 | 0.00 | 3544.08 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86310.74 | 13-NOV-04:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 84391.36 | 26-DEC-04:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 71575.09 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86729.65 | 9673.43 | 7087.27 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 71765.20 | 09-JAN-06:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 71857.90 | 01-FEB-06:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 73449.76 | 16-MAR-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 73014.26 | 27-APR-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73938.87 | 03-MAY-05:04 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 60838.24 | 01-JUN-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 72808.50 | 29-JUL-04:03 | 0.00 | 2362.72 | 17812.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 72348.19 | 29-AUG-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74144.51 | 22-SEP-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 73206.31 | 25-OCT-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 74765.92 | 13-NOV-05:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 69826.60 | 29-DEC-06:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 60838.24 | 0.00 | 2362.72 | 17812.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74765.92 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 32467.50 | 27-JAN-17:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29882.84 | 22-FEB-17:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 70422.91 | 17-MAR-05:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70690.37 | 18-APR-05:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71765.45 | 26-MAY-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 64250.45 | 26-JUN-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 68364.75 | 29-JUL-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 73234.04 | 29-AUG-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 75405.02 | 11-SEP-03:02 | 0.00 | 2362.72 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 69926.00 | 17-OCT-05:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 70274.63 | 03-NOV-05:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28855.40 | 22-DEC-17:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 28855.40 | 0.00 | 2362.72 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75405.02 | 15316.26 | 10631.20 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4587.17 | 31-JAN-16:30 | 1923.11 | 687.48 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 | 0.00 |
February | 4553.18 | 22-FEB-14:00 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.80 |
March | 6402.49 | 20-MAR-14:00 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 0.00 |
April | 9438.28 | 24-APR-05:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 |
May | 13668.00 | 29-MAY-18:11 | 0.00 | 247.02 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 48.00 | 0.00 |
June | 16440.61 | 18-JUN-15:32 | 404.87 | 141.15 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 96.29 | 0.00 |
July | 17173.94 | 16-JUL-17:41 | 0.00 | 317.59 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 121.40 | 0.00 |
August | 16988.04 | 27-AUG-16:21 | 1012.16 | 352.88 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 89.21 | 0.00 |
September | 14674.98 | 17-SEP-15:42 | 506.08 | 176.44 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 42.84 | 0.00 |
October | 13346.11 | 02-OCT-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 | 0.00 |
November | 10618.42 | 13-NOV-06:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
December | 4876.37 | 26-DEC-15:30 | 1923.11 | 680.74 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4553.18 | 0.00 | 141.15 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17173.94 | 2010.79 | 741.56 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 121.40 | 8.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6181.73 | 17-JAN-09:30 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 |
February | 5997.86 | 23-FEB-09:20 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 |
March | 7971.67 | 19-MAR-09:03 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.15 |
April | 15625.59 | 23-APR-10:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 | 0.00 |
May | 16724.34 | 21-MAY-08:52 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.44 |
June | 16016.79 | 18-JUN-08:52 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 23.86 | 0.00 |
July | 16094.42 | 23-JUL-09:01 | 456.59 | 159.19 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 0.00 |
August | 16794.96 | 27-AUG-09:02 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 0.00 |
September | 15762.01 | 10-SEP-11:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 22.95 | 0.00 |
October | 11367.33 | 09-OCT-10:53 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 | 0.00 |
November | 6638.63 | 20-NOV-09:30 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.94 |
December | 5361.69 | 26-DEC-09:40 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5361.69 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16794.96 | 1239.33 | 409.30 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 23.86 | 24.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19611.15 | 15-JAN-13:52 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.79 |
February | 14044.17 | 26-FEB-14:03 | 303.66 | 105.87 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.49 |
March | 12034.54 | 23-MAR-13:40 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4.92 | 0.00 |
April | 18536.82 | 30-APR-13:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 65.39 | 0.00 |
May | 17886.00 | 07-MAY-15:02 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 38.55 | 0.00 |
June | 18064.25 | 18-JUN-15:32 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | 0.00 |
July | 18871.60 | 16-JUL-17:01 | 0.00 | 317.60 | 5032.61 | 0.00 | 0.00 | 0.00 | 0.00 | 116.68 | 0.00 |
August | 19314.33 | 27-AUG-15:41 | 910.97 | 317.60 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 102.72 | 0.00 |
September | 19263.47 | 10-SEP-11:43 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 24.81 | 0.00 |
October | 19108.70 | 09-OCT-10:53 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.68 |
November | 19017.00 | 05-NOV-12:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.51 |
December | 19648.78 | 03-DEC-13:22 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12034.54 | 0.00 | 105.87 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19648.78 | 2010.83 | 635.14 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 116.68 | 59.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14110.55 | 16-JAN-16:03 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.70 |
February | 17531.15 | 20-FEB-16:03 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.80 |
March | 15691.70 | 18-MAR-17:06 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 | 0.00 |
April | 21940.28 | 02-APR-16:51 | 456.59 | 159.19 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 | 0.00 |
May | 23006.56 | 21-MAY-16:51 | 521.82 | 181.93 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 30.69 | 0.00 |
June | 21737.06 | 25-JUN-17:02 | 0.00 | 136.45 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.23 | 0.00 |
July | 24359.48 | 16-JUL-17:01 | 0.00 | 204.67 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 59.26 | 0.00 |
August | 24925.07 | 27-AUG-16:21 | 652.28 | 227.41 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 46.63 | 0.00 |
September | 20419.56 | 17-SEP-16:22 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 21.14 | 0.00 |
October | 20305.43 | 15-OCT-16:02 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 0.00 |
November | 17496.23 | 26-NOV-16:22 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.26 |
December | 20099.67 | 03-DEC-14:42 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14110.55 | 0.00 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24925.07 | 652.28 | 227.41 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 59.26 | 40.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3195.33 | 27-JAN-16:30 | 1923.11 | 680.55 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5.30 | 0.00 |
February | 2648.09 | 23-FEB-14:00 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 |
March | 4930.24 | 17-MAR-15:40 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 | 0.00 |
April | 9068.40 | 13-APR-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.99 |
May | 11771.98 | 26-MAY-05:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 |
June | 15520.74 | 18-JUN-15:32 | 404.87 | 141.15 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 222.39 | 0.00 |
July | 15655.38 | 02-JUL-17:41 | 0.00 | 317.59 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 237.20 | 0.00 |
August | 13527.69 | 28-AUG-04:03 | 0.00 | 593.25 | 2982.24 | 0.00 | 0.00 | 0.00 | 0.00 | 42.28 | 0.00 |
September | 12572.35 | 19-SEP-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 |
October | 11771.72 | 02-OCT-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 | 0.00 |
November | 4800.90 | 02-NOV-14:00 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 16.82 | 0.00 |
December | 2810.02 | 22-DEC-16:00 | 1923.11 | 703.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2648.09 | 0.00 | 141.15 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15655.38 | 2010.79 | 741.56 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 237.20 | 19.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4630.73 | 27-JAN-10:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.75 |
February | 4950.21 | 23-FEB-10:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.61 |
March | 6337.56 | 23-MAR-10:10 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.09 |
April | 17001.66 | 30-APR-10:02 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 | 0.00 |
May | 17556.12 | 21-MAY-08:52 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 |
June | 17756.47 | 04-JUN-08:32 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 10.98 | 0.00 |
July | 17163.23 | 30-JUL-08:12 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 |
August | 16641.87 | 13-AUG-09:22 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 | 0.00 |
September | 13155.23 | 10-SEP-10:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 37.39 | 0.00 |
October | 14410.99 | 15-OCT-09:53 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.21 |
November | 5643.86 | 10-NOV-09:30 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 |
December | 3254.21 | 27-DEC-10:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3254.21 | 260.91 | 90.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17756.47 | 1239.33 | 409.30 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 37.39 | 17.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18799.85 | 16-JAN-14:32 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.48 |
February | 16905.28 | 26-FEB-14:23 | 303.66 | 105.87 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.67 |
March | 11622.55 | 23-MAR-14:00 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 0.00 |
April | 17531.43 | 30-APR-13:23 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 146.58 | 0.00 |
May | 16911.73 | 07-MAY-15:02 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 88.87 | 0.00 |
June | 17054.35 | 18-JUN-15:32 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 225.29 | 0.00 |
July | 17740.38 | 30-JUL-14:51 | 708.53 | 247.02 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 174.73 | 0.00 |
August | 17288.42 | 27-AUG-12:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 135.61 | 0.00 |
September | 17996.21 | 10-SEP-13:22 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 151.22 | 0.00 |
October | 19531.60 | 09-OCT-13:22 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 18.91 | 0.00 |
November | 18801.82 | 19-NOV-13:52 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.32 |
December | 18749.23 | 24-DEC-13:42 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11622.55 | 303.66 | 105.87 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19531.60 | 2010.83 | 635.14 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 225.29 | 147.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7798.38 | 24-JAN-16:30 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 0.00 |
February | 8152.12 | 22-FEB-16:30 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 |
March | 10830.28 | 18-MAR-17:06 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
April | 19141.56 | 23-APR-17:41 | 0.00 | 159.19 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 58.64 | 0.00 |
May | 19926.58 | 28-MAY-17:21 | 0.00 | 181.93 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 53.25 | 0.00 |
June | 19540.77 | 11-JUN-16:11 | 521.82 | 181.93 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 54.02 | 0.00 |
July | 20327.36 | 30-JUL-16:51 | 587.05 | 204.67 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.61 | 0.00 |
August | 18933.91 | 06-AUG-16:22 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 22.81 | 0.00 |
September | 17542.24 | 04-SEP-15:42 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 35.27 | 0.00 |
October | 17589.85 | 15-OCT-15:51 | 456.59 | 159.19 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 28.89 | 0.00 |
November | 9588.47 | 01-NOV-16:00 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 12.37 | 0.00 |
December | 7986.63 | 22-DEC-16:30 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7798.38 | 0.00 | 113.70 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20327.36 | 1239.33 | 409.30 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.61 | 11.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2835.62 | 27-JAN-16:30 | 1923.11 | 680.48 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 | 0.00 |
February | 2287.54 | 23-FEB-14:20 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.41 |
March | 5330.67 | 17-MAR-15:50 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 10.64 | 0.00 |
April | 10678.67 | 30-APR-17:31 | 0.00 | 282.30 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 135.47 | 0.00 |
May | 13346.68 | 26-MAY-05:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.02 |
June | 19087.95 | 04-JUN-16:01 | 910.95 | 317.59 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 223.80 | 0.00 |
July | 19016.22 | 30-JUL-17:31 | 0.00 | 317.59 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 341.54 | 0.00 |
August | 18107.96 | 27-AUG-16:31 | 910.95 | 317.59 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 243.39 | 0.00 |
September | 14291.88 | 10-SEP-17:23 | 0.00 | 220.46 | 2236.68 | 0.00 | 0.00 | 0.00 | 0.00 | 226.50 | 0.00 |
October | 15180.53 | 02-OCT-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.94 |
November | 4991.89 | 01-NOV-15:40 | 1923.11 | 685.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 20.37 | 0.00 |
December | 2563.81 | 22-DEC-15:30 | 1923.11 | 678.89 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2287.54 | 0.00 | 220.46 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19087.95 | 2010.79 | 685.05 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 341.54 | 13.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3463.83 | 27-JAN-10:30 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.48 |
February | 3817.65 | 23-FEB-10:30 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.28 |
March | 5626.50 | 23-MAR-10:30 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 |
April | 17506.72 | 30-APR-09:32 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.09 |
May | 17369.87 | 28-MAY-09:32 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.13 | 0.00 |
June | 18539.73 | 04-JUN-08:42 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 12.02 | 0.00 |
July | 17867.99 | 30-JUL-16:11 | 587.05 | 204.67 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 150.71 | 0.00 |
August | 18370.90 | 27-AUG-09:12 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 54.08 | 0.00 |
September | 13693.64 | 10-SEP-10:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 45.25 | 0.00 |
October | 12815.09 | 01-OCT-11:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 21.80 | 0.00 |
November | 4911.29 | 01-NOV-10:00 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 |
December | 2351.73 | 22-DEC-15:30 | 1239.33 | 436.58 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2351.73 | 260.91 | 90.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18539.73 | 1295.83 | 436.58 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 150.71 | 18.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20924.38 | 29-JAN-15:22 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 |
February | 12896.67 | 23-FEB-14:00 | 1923.15 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 |
March | 11726.69 | 23-MAR-14:00 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 | 0.00 |
April | 19969.51 | 30-APR-12:53 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 186.97 | 0.00 |
May | 19130.50 | 28-MAY-16:51 | 809.75 | 282.31 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 182.17 | 0.00 |
June | 20642.83 | 04-JUN-16:01 | 910.97 | 317.60 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 225.42 | 0.00 |
July | 21020.50 | 30-JUL-16:11 | 910.97 | 317.60 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 227.37 | 0.00 |
August | 20047.48 | 27-AUG-16:31 | 910.97 | 317.60 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 238.35 | 0.00 |
September | 20526.18 | 10-SEP-13:22 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 182.76 | 0.00 |
October | 22042.56 | 09-OCT-14:02 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 | 0.00 |
November | 20789.69 | 19-NOV-14:32 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.47 |
December | 20418.97 | 24-DEC-15:02 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11726.69 | 404.87 | 141.16 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22042.56 | 2010.83 | 635.14 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 238.35 | 78.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7534.55 | 24-JAN-16:30 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1.44 | 0.00 |
February | 7924.24 | 22-FEB-16:30 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.02 |
March | 11351.06 | 18-MAR-17:06 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 |
April | 21611.00 | 30-APR-17:31 | 0.00 | 181.93 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 33.58 | 0.00 |
May | 21901.98 | 28-MAY-16:51 | 521.82 | 181.93 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 71.20 | 0.00 |
June | 22627.96 | 04-JUN-16:01 | 587.05 | 204.67 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.61 | 0.00 |
July | 23005.96 | 30-JUL-16:51 | 587.05 | 204.67 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.70 | 0.00 |
August | 21144.70 | 27-AUG-16:31 | 587.05 | 204.67 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.79 | 0.00 |
September | 19328.70 | 04-SEP-15:42 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 42.16 | 0.00 |
October | 20357.68 | 15-OCT-16:22 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 26.57 | 0.00 |
November | 9934.13 | 01-NOV-16:00 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 | 0.00 |
December | 7771.40 | 22-DEC-16:30 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7534.55 | 0.00 | 113.70 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23005.96 | 1239.33 | 409.30 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.70 | 15.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5451.36 | 17-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.40 |
February | 4808.21 | 23-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.79 |
March | 6992.73 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.03 |
April | 7830.05 | 03-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.74 |
May | 8977.15 | 01-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.72 |
June | 11718.32 | 05-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.47 |
July | 14492.14 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 |
August | 15241.21 | 14-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
September | 12772.99 | 11-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 |
October | 12093.57 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 |
November | 8199.30 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.45 |
December | 8084.35 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4808.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15241.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 45.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3274.55 | 28-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.25 |
February | 3705.29 | 01-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.00 |
March | 4373.37 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.56 |
April | 6094.93 | 25-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.16 | 0.00 |
May | 7746.35 | 11-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.45 |
June | 8453.56 | 29-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.99 | 0.00 |
July | 7659.17 | 14-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 |
August | 7631.57 | 14-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.59 | 0.00 |
September | 9635.90 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.15 |
October | 7292.90 | 03-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 |
November | 4289.62 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.56 |
December | 5202.27 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3274.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9635.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.59 | 112.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7126.29 | 31-JAN-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.41 | 0.00 |
February | 6348.71 | 23-FEB-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.86 |
March | 10834.16 | 16-MAR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.53 | 0.00 |
April | 18107.20 | 14-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | 0.00 |
May | 18472.96 | 19-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.05 | 0.00 |
June | 22695.43 | 28-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.15 | 0.00 |
July | 21565.69 | 20-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.60 | 0.00 |
August | 20854.17 | 15-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.82 | 0.00 |
September | 18458.35 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.07 | 0.00 |
October | 16090.62 | 02-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.46 | 0.00 |
November | 9980.26 | 01-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.05 | 0.00 |
December | 5178.14 | 22-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5178.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22695.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.15 | 46.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2069.52 | 24-JAN-17:00 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3904.27 | 27-FEB-17:40 | 70.15 | 158.31 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7167.82 | 31-MAR-24:00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7683.11 | 26-APR-18:10 | 23.38 | 94.99 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3470.26 | 31-MAY-23:57 | 0.00 | 47.50 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5411.67 | 30-JUN-23:37 | 0.00 | 47.50 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7313.43 | 31-JUL-23:57 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7766.54 | 06-AUG-18:50 | 0.00 | 63.33 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3491.40 | 30-SEP-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5329.96 | 31-OCT-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6041.47 | 26-NOV-16:56 | 58.46 | 79.16 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7781.17 | 26-DEC-16:50 | 222.14 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2069.52 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7781.17 | 222.14 | 284.97 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1890.43 | 24-JAN-17:00 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3627.70 | 27-FEB-17:40 | 70.15 | 158.31 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6684.34 | 31-MAR-24:00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7347.55 | 26-APR-18:10 | 23.38 | 94.99 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3365.46 | 31-MAY-23:27 | 0.00 | 47.50 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5209.31 | 30-JUN-23:57 | 0.00 | 47.50 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6991.80 | 31-JUL-23:57 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7370.74 | 06-AUG-18:20 | 0.00 | 79.16 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3407.59 | 30-SEP-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4921.07 | 31-OCT-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5631.32 | 14-NOV-17:00 | 222.14 | 284.97 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7357.25 | 26-DEC-17:00 | 222.14 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1890.43 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7370.74 | 222.14 | 284.97 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1895.41 | 24-JAN-17:00 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3621.87 | 22-FEB-17:00 | 222.14 | 284.97 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6490.49 | 31-MAR-23:30 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7396.17 | 26-APR-18:10 | 23.38 | 94.99 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3367.30 | 31-MAY-23:37 | 0.00 | 47.50 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5265.08 | 30-JUN-23:30 | 0.00 | 31.66 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7056.67 | 31-JUL-23:57 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7520.73 | 06-AUG-18:20 | 0.00 | 79.16 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3443.61 | 30-SEP-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4718.53 | 31-OCT-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5649.22 | 21-NOV-17:00 | 222.14 | 284.97 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7306.72 | 22-DEC-17:00 | 222.14 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1895.41 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7520.73 | 222.14 | 284.97 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91771.60 | 17-JAN-17:00 | 4808.68 | 3337.76 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182351.00 | 21-FEB-17:00 | 4808.68 | 3337.76 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357750.41 | 31-MAR-24:00 | 0.00 | 185.45 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366071.03 | 24-APR-16:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175243.44 | 31-MAY-23:53 | 0.00 | 556.35 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267170.52 | 30-JUN-23:53 | 0.00 | 556.35 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360017.65 | 31-JUL-23:57 | 0.00 | 556.35 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 368033.17 | 14-AUG-16:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176992.97 | 30-SEP-24:00 | 0.00 | 185.45 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268741.10 | 31-OCT-24:00 | 0.00 | 185.45 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276223.42 | 20-NOV-17:00 | 4808.68 | 3337.76 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367820.63 | 26-DEC-17:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91771.60 | 0.00 | 185.45 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 368033.17 | 4808.68 | 3337.76 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.137850E+13 | 944334.56 | 18-JAN-16:00 | 0.630091E+11 | 339472.26 | 02-JAN-06:10 |
February | 0.153130E+13 | 1051186.44 | 22-FEB-16:30 | 0.584630E+11 | 217223.96 | 13-FEB-06:10 |
March | 0.217322E+13 | 1340098.02 | 16-MAR-15:39 | 0.632324E+11 | 294449.68 | 27-MAR-06:19 |
April | 0.261091E+13 | 1576761.72 | 13-APR-15:30 | 0.495489E+11 | 70607.50 | 03-APR-11:20 |
May | 0.163466E+13 | 1159861.62 | 18-MAY-15:09 | 0.490315E+11 | 66169.94 | 01-MAY-11:39 |
June | 0.211219E+13 | 1356417.55 | 30-JUN-15:09 | 0.454573E+11 | 61202.77 | 02-JUN-11:30 |
July | 0.251054E+13 | 1500241.46 | 21-JUL-15:20 | 0.432592E+11 | 57184.96 | 12-JUL-11:50 |
August | 0.294391E+13 | 1634688.54 | 11-AUG-15:20 | 0.462324E+11 | 59396.87 | 31-AUG-11:30 |
September | 0.162888E+13 | 1218243.41 | 05-SEP-07:49 | 0.449009E+11 | 63291.13 | 26-SEP-11:39 |
October | 0.189051E+13 | 1287367.10 | 03-OCT-08:00 | 0.501071E+11 | 128936.45 | 25-OCT-06:49 |
November | 0.209128E+13 | 1363611.63 | 02-NOV-15:00 | 0.548175E+11 | 208355.14 | 24-NOV-06:10 |
December | 0.246075E+13 | 1366471.74 | 26-DEC-16:00 | 0.860714E+11 | 436739.18 | 06-DEC-07:10 |
Annual Sum or Average | 0.249666E+14 | 0.654131E+12 | ||||
Minimum of Months | 0.137850E+13 | 944334.56 | 0.432592E+11 | 57184.96 | ||
Maximum of Months | 0.294391E+13 | 1634688.54 | 0.860714E+11 | 436739.18 |
Report: EnergyConsumptionDistrictHeatingCoolingMonthly
For: Meter
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportDISTRICTCOOLING:FACILITY [J] | DISTRICTCOOLING:FACILITY {Maximum} [W] | DISTRICTCOOLING:FACILITY {TIMESTAMP} | DISTRICTHEATING:FACILITY [J] | DISTRICTHEATING:FACILITY {Maximum} [W] | DISTRICTHEATING:FACILITY {TIMESTAMP} | |
January | 0.241427E+12 | 94381.29 | 17-JAN-14:00 | 146775.50 | 9.10 | 15-JAN-18:40 |
February | 0.436442E+12 | 184949.99 | 21-FEB-16:00 | 187613.45 | 12.65 | 01-FEB-00:40 |
March | 0.728686E+12 | 357751.17 | 31-MAR-23:00 | 200424.59 | 11.57 | 01-MAR-00:30 |
April | 0.943317E+12 | 368669.98 | 24-APR-15:00 | 24698.17 | 7.28 | 04-APR-23:19 |
May | 0.241449E+12 | 175243.44 | 31-MAY-23:00 | 29223.19 | 5.44 | 12-MAY-23:40 |
June | 0.470478E+12 | 267170.53 | 30-JUN-23:00 | 14272.66 | 2.86 | 11-JUN-17:30 |
July | 0.733787E+12 | 360017.65 | 31-JUL-23:00 | 15215.72 | 3.74 | 09-JUL-17:30 |
August | 0.980103E+12 | 370732.56 | 28-AUG-13:00 | 27370.98 | 7.29 | 29-AUG-23:19 |
September | 0.239279E+12 | 176992.97 | 30-SEP-23:00 | 43796.51 | 6.74 | 29-SEP-23:40 |
October | 0.490570E+12 | 268742.65 | 31-OCT-23:00 | 121673.40 | 11.56 | 31-OCT-23:30 |
November | 0.711389E+12 | 278822.34 | 20-NOV-16:00 | 178390.50 | 7.94 | 22-NOV-00:30 |
December | 0.979195E+12 | 370434.35 | 26-DEC-14:00 | 193079.60 | 11.14 | 01-DEC-00:30 |
Annual Sum or Average | 0.719612E+13 | 1182534.26 | ||||
Minimum of Months | 0.239279E+12 | 94381.29 | 14272.66 | 2.86 | ||
Maximum of Months | 0.980103E+12 | 370732.56 | 200424.59 | 12.65 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.171268E+12 | 0.345630E+11 | 0.766053E+12 | 0.207862E+12 | 0.801236E+11 | 0.368771E+11 | 0.00 | 0.669824E+11 | 0.147732E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154709E+12 | 0.285874E+11 | 0.978954E+12 | 0.229081E+12 | 0.680647E+11 | 0.222841E+11 | 0.00 | 0.391393E+11 | 0.104829E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181830E+12 | 0.281410E+11 | 0.141687E+13 | 0.299605E+12 | 0.881564E+11 | 0.419380E+11 | 0.00 | 0.946713E+11 | 0.220116E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161536E+12 | 0.238540E+11 | 0.165903E+13 | 0.333797E+12 | 0.125051E+12 | 0.753201E+11 | 0.00 | 0.198949E+12 | 0.333765E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173731E+12 | 0.217112E+11 | 0.774844E+12 | 0.208007E+12 | 0.143001E+12 | 0.780624E+11 | 0.00 | 0.199683E+12 | 0.356172E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172341E+12 | 0.199412E+11 | 0.106252E+13 | 0.245640E+12 | 0.165664E+12 | 0.968396E+11 | 0.00 | 0.295363E+12 | 0.538844E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161848E+12 | 0.211311E+11 | 0.139340E+13 | 0.299361E+12 | 0.156373E+12 | 0.972603E+11 | 0.00 | 0.306644E+12 | 0.745152E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180917E+12 | 0.234549E+11 | 0.173200E+13 | 0.345115E+12 | 0.163191E+12 | 0.976510E+11 | 0.00 | 0.325551E+12 | 0.760344E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162114E+12 | 0.255765E+11 | 0.740713E+12 | 0.201201E+12 | 0.132879E+12 | 0.795271E+11 | 0.00 | 0.221746E+12 | 0.651218E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169825E+12 | 0.300722E+11 | 0.108340E+13 | 0.253679E+12 | 0.106116E+12 | 0.605773E+11 | 0.00 | 0.151046E+12 | 0.357892E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168931E+12 | 0.326087E+11 | 0.135889E+13 | 0.289765E+12 | 0.847823E+11 | 0.405422E+11 | 0.00 | 0.934840E+11 | 0.222766E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166432E+12 | 0.356688E+11 | 0.170972E+13 | 0.345057E+12 | 0.767984E+11 | 0.284648E+11 | 0.00 | 0.808637E+11 | 0.177420E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202548E+13 | 0.325310E+12 | 0.146764E+14 | 0.325817E+13 | 0.139020E+13 | 0.755344E+12 | 0.00 | 0.207412E+13 | 0.461625E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154709E+12 | 0.199412E+11 | 0.740713E+12 | 0.201201E+12 | 0.680647E+11 | 0.222841E+11 | 0.00 | 0.391393E+11 | 0.104829E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181830E+12 | 0.356688E+11 | 0.173200E+13 | 0.345115E+12 | 0.165664E+12 | 0.976510E+11 | 0.00 | 0.325551E+12 | 0.760344E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.654470E+10 | 0.00 | 0.564644E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.759649E+10 | 0.00 | 0.508665E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.649364E+10 | 0.00 | 0.567387E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 921172.02 | 0.00 | 0.495480E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.490315E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.454573E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.432592E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.462324E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.449009E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.748769E+09 | 0.00 | 0.493584E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.344878E+10 | 0.00 | 0.513688E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.318050E+11 | 0.00 | 0.542664E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.566383E+11 | 0.00 | 0.597492E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.432592E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.318050E+11 | 0.00 | 0.567387E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 193694.38 | 20-JAN-16:00 | 37611.08 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 133945.62 | 20-JAN-08:39 | 96057.05 | 31-JAN-16:00 | 49933.36 | 17-JAN-14:09 | 0.00 | 01-JAN-00:10 |
February | 191472.14 | 10-FEB-08:09 | 37611.08 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 151028.39 | 10-FEB-08:20 | 92656.56 | 22-FEB-16:30 | 32617.83 | 13-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 188298.56 | 21-MAR-07:10 | 37611.08 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 168110.19 | 21-MAR-07:19 | 120384.68 | 16-MAR-15:50 | 52322.44 | 17-MAR-14:39 | 0.00 | 01-MAR-00:10 |
April | 180869.02 | 04-APR-07:10 | 37611.08 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 185189.74 | 04-APR-07:19 | 162662.01 | 12-APR-15:39 | 50366.77 | 14-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 174163.98 | 05-MAY-07:10 | 37611.08 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 133935.81 | 05-MAY-07:19 | 166681.44 | 18-MAY-15:20 | 50331.91 | 17-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 173610.58 | 27-JUN-07:10 | 37611.08 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 151018.99 | 27-JUN-07:19 | 185285.79 | 27-JUN-14:50 | 56423.73 | 19-JUN-14:09 | 0.00 | 01-JUN-00:10 |
July | 177365.03 | 27-JUL-07:10 | 37611.08 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 168104.43 | 27-JUL-07:19 | 186114.34 | 21-JUL-15:39 | 52772.82 | 11-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 189929.12 | 04-AUG-07:10 | 37611.08 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 185194.51 | 04-AUG-07:19 | 180633.14 | 08-AUG-15:39 | 55181.64 | 23-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 182630.94 | 29-SEP-07:10 | 37611.08 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 133940.27 | 29-SEP-07:19 | 162025.17 | 19-SEP-15:30 | 56756.33 | 28-SEP-13:20 | 0.00 | 01-SEP-00:10 |
October | 188691.46 | 27-OCT-07:10 | 37611.08 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 151026.93 | 27-OCT-07:19 | 143870.28 | 02-OCT-09:09 | 57021.32 | 05-OCT-15:50 | 0.00 | 01-OCT-00:10 |
November | 198852.03 | 28-NOV-16:30 | 37611.08 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 168110.54 | 02-NOV-07:19 | 113507.78 | 02-NOV-15:00 | 51793.71 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 198852.03 | 01-DEC-16:30 | 37611.08 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 185195.11 | 12-DEC-08:20 | 86371.07 | 26-DEC-16:00 | 49879.69 | 26-DEC-13:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 173610.58 | 37611.08 | 423497.50 | 133935.81 | 86371.07 | 32617.83 | 0.00 | |||||||
Maximum of Months | 198852.03 | 37611.08 | 778371.69 | 185195.11 | 186114.34 | 57021.32 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 95954.04 | 31-JAN-17:10 | 14155.78 | 26-JAN-14:09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 85810.62 | 22-FEB-15:00 | 13533.48 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 205914.54 | 20-MAR-14:09 | 18683.06 | 20-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 222256.99 | 14-APR-15:30 | 46841.99 | 11-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 208634.84 | 18-MAY-15:20 | 46841.99 | 09-MAY-13:39 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 266176.00 | 19-JUN-14:09 | 46841.99 | 01-JUN-09:20 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 275757.35 | 19-JUL-13:39 | 46841.99 | 03-JUL-11:50 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 273908.49 | 11-AUG-15:00 | 46841.99 | 01-AUG-05:19 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 266782.34 | 05-SEP-07:49 | 46841.99 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232791.07 | 03-OCT-10:00 | 46841.99 | 02-OCT-07:49 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 199689.15 | 01-NOV-15:30 | 46841.99 | 01-NOV-13:20 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 112188.28 | 21-DEC-15:09 | 13872.58 | 21-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 85810.62 | 13533.48 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 275757.35 | 46841.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 944334.56 | 18-JAN-16:00 | 178778.73 | 423497.50 | 0.00 | 99894.00 | 84041.57 | 49698.61 | 0.00 | 94938.47 | 13485.68 |
February | 1051186.44 | 22-FEB-16:30 | 172389.88 | 541788.89 | 0.00 | 116974.94 | 92656.56 | 32181.52 | 0.00 | 81949.55 | 13245.10 |
March | 1340098.02 | 16-MAR-15:39 | 171235.93 | 660080.29 | 0.00 | 134057.82 | 117761.02 | 50026.82 | 0.00 | 190840.30 | 16095.84 |
April | 1576761.72 | 13-APR-15:30 | 171235.93 | 778371.69 | 0.00 | 151141.29 | 160928.51 | 50285.16 | 0.00 | 217957.17 | 46841.99 |
May | 1159861.62 | 18-MAY-15:09 | 171235.93 | 423497.50 | 0.00 | 99890.88 | 164187.53 | 50286.70 | 0.00 | 203921.10 | 46841.99 |
June | 1356417.55 | 30-JUN-15:09 | 171235.93 | 541788.89 | 0.00 | 116974.35 | 176851.12 | 53038.63 | 0.00 | 249686.65 | 46841.99 |
July | 1500241.46 | 21-JUL-15:20 | 171235.93 | 660080.29 | 0.00 | 134057.82 | 185465.38 | 51424.50 | 0.00 | 251135.57 | 46841.99 |
August | 1634688.54 | 11-AUG-15:20 | 171235.93 | 778371.69 | 0.00 | 151141.29 | 171564.96 | 51545.43 | 0.00 | 263987.26 | 46841.99 |
September | 1218243.41 | 05-SEP-07:49 | 172958.01 | 423497.50 | 0.00 | 133935.73 | 121750.91 | 52476.95 | 0.00 | 266782.34 | 46841.99 |
October | 1287367.10 | 03-OCT-08:00 | 171235.93 | 541788.89 | 0.00 | 116974.35 | 135918.50 | 50987.41 | 0.00 | 223620.03 | 46841.99 |
November | 1363611.63 | 02-NOV-15:00 | 172727.18 | 660080.29 | 0.00 | 134058.31 | 113507.78 | 50949.91 | 0.00 | 185446.17 | 46841.99 |
December | 1366471.74 | 26-DEC-16:00 | 181603.94 | 778371.69 | 0.00 | 151145.73 | 86371.07 | 49659.90 | 0.00 | 105910.67 | 13408.74 |
Annual Sum or Average | |||||||||||
Minimum of Months | 944334.56 | 171235.93 | 423497.50 | 0.00 | 99890.88 | 84041.57 | 32181.52 | 0.00 | 81949.55 | 13245.10 | |
Maximum of Months | 1634688.54 | 181603.94 | 778371.69 | 0.00 | 151145.73 | 185465.38 | 53038.63 | 0.00 | 266782.34 | 46841.99 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 312807.85 | 02-JAN-06:10 | 0.00 | 75259.97 | 19-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 211528.09 | 13-FEB-06:10 | 0.00 | 75209.70 | 01-FEB-12:50 | 0.00 |
March | 0.00 | 0.00 | 279726.80 | 27-MAR-06:10 | 0.00 | 73853.93 | 03-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 252.28 | 01-APR-06:10 | 0.00 | 70607.50 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 66169.94 | 01-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 61202.77 | 02-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 57184.96 | 12-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 59396.87 | 31-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 63291.13 | 26-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 101299.07 | 25-OCT-06:30 | 0.00 | 67911.53 | 30-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 202659.27 | 24-NOV-06:10 | 0.00 | 72167.12 | 30-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 408251.94 | 06-DEC-07:10 | 0.00 | 74630.17 | 28-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 57184.96 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 408251.94 | 0.00 | 75259.97 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 26.79 | 1.83 | 26.88 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 26.52 | 0.00 | 26.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 25.95 | 0.00 | 25.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 25.99 | 0.00 | 25.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.01 | 0.00 | 26.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.08 | 0.00 | 26.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.06 | 0.00 | 26.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.00 | 0.17 | 26.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 26.25 | 0.67 | 26.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 26.41 | 1.17 | 26.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 26.50 | 1.33 | 26.59 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 26.57 | 1.00 | 26.63 |
Annual Sum or Average | 0.00 | 0.00 | 94.83 | 26.37 | 6.17 | 26.44 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.95 | 0.00 | 25.95 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 26.79 | 1.83 | 26.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.64 | 0.00 | 25.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.66 | 0.00 | 25.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 25.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.60 | 0.00 | 25.60 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.60 | 0.00 | 25.60 |
Annual Sum or Average | 0.00 | 0.00 | 2.17 | 25.62 | 0.00 | 25.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.66 | 0.00 | 25.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 26.84 | 2.67 | 27.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.81 | 3.50 | 26.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 26.72 | 2.50 | 26.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.70 | 0.00 | 25.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.68 | 0.00 | 25.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 23.33 | 26.75 | 8.67 | 26.93 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.84 | 3.50 | 27.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.33 | 0.33 | 27.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.50 | 27.36 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.71 | 5.00 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.70 | 9.83 | 27.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.59 | 10.33 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.49 | 12.33 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.55 | 6.33 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.45 | 4.17 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.40 | 2.50 | 27.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 60.33 | 27.56 | 51.50 | 27.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.71 | 12.33 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.75 | 7.50 | 27.75 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.38 | 1.33 | 27.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.51 | 6.33 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.29 | 0.67 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.90 | 3.83 | 27.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 26.99 | 6.83 | 27.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 26.99 | 5.33 | 27.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.27 | 7.17 | 27.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.60 | 8.50 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.72 | 6.17 | 27.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.84 | 7.17 | 27.84 |
Annual Sum or Average | 0.00 | 0.00 | 82.67 | 27.34 | 61.00 | 27.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.90 | 0.17 | 27.08 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.84 | 8.50 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.64 | 1.33 | 27.64 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.73 | 0.50 | 27.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.33 | 2.00 | 27.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 34.50 | 27.43 | 9.33 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.53 | 6.83 | 27.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 37.00 | 27.35 | 10.00 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 27.58 | 16.33 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 59.50 | 27.57 | 16.83 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 26.96 | 6.33 | 27.19 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.21 | 5.33 | 27.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.20 | 3.67 | 27.46 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.78 | 3.50 | 27.85 |
Annual Sum or Average | 0.00 | 0.00 | 247.00 | 27.45 | 82.00 | 27.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.96 | 0.50 | 27.19 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 59.50 | 27.78 | 16.83 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.24 | 2.17 | 27.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 26.95 | 1.00 | 27.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.13 | 0.67 | 27.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.50 | 27.11 | 3.83 | 27.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.24 | 2.17 | 27.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.75 | 6.33 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.76 | 11.17 | 27.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.82 | 10.67 | 27.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.55 | 12.33 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.68 | 7.83 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.71 | 4.83 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.49 | 2.50 | 27.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 65.33 | 27.70 | 55.67 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.82 | 12.33 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.22 | 9.17 | 27.22 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.44 | 1.00 | 27.44 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.49 | 4.50 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.27 | 0.67 | 27.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.15 | 2.67 | 27.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.96 | 4.00 | 27.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.20 | 4.50 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.77 | 9.50 | 26.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 26.38 | 15.17 | 26.36 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 26.48 | 9.83 | 26.48 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.86 | 6.17 | 27.86 |
Annual Sum or Average | 0.00 | 0.00 | 78.33 | 26.92 | 67.17 | 26.96 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.86 | 15.17 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.47 | 0.17 | 27.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.05 | 4.00 | 28.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.15 | 4.50 | 28.22 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.39 | 4.17 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.42 | 6.17 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 27.31 | 4.17 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.34 | 3.67 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.58 | 2.83 | 27.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 84.67 | 27.54 | 29.67 | 27.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 28.15 | 6.17 | 28.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.38 | 0.17 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 |
February | 0.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
March | 0.17 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.31 | 0.00 | 27.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.38 | 5.67 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.25 | 7.33 | 27.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.27 | 3.33 | 27.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.30 | 1.83 | 27.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.00 | 0.67 | 27.16 |
November | 0.17 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
December | 2.17 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
Annual Sum or Average | 3.33 | 18.77 | 0.17 | 18.85 | 39.67 | 26.61 | 18.83 | 26.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.25 | 0.17 | 19.25 | 15.33 | 27.38 | 7.33 | 27.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 17.95 | 0.00 | 17.95 | 0.00 | 17.95 | 0.00 | 17.95 |
February | 0.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
March | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.69 | 8.00 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.82 | 12.17 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.84 | 11.17 | 27.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 27.64 | 14.00 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.72 | 8.17 | 27.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.73 | 7.67 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.41 | 2.33 | 27.47 |
November | 0.17 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
December | 1.50 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
Annual Sum or Average | 2.50 | 18.80 | 0.00 | 18.80 | 90.50 | 27.49 | 63.50 | 27.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.95 | 0.00 | 17.95 |
Maximum of Months | 1.50 | 19.40 | 0.00 | 19.40 | 23.00 | 27.84 | 14.00 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.09 | 0.00 | 19.09 | 5.17 | 27.20 | 5.17 | 27.46 |
February | 0.17 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.59 | 5.17 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.40 | 2.83 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.38 | 5.17 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.30 | 8.67 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.36 | 5.17 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.49 | 7.00 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.78 | 7.50 | 27.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.61 | 3.17 | 27.61 |
December | 0.83 | 19.20 | 0.00 | 19.20 | 3.17 | 25.97 | 3.17 | 26.76 |
Annual Sum or Average | 1.33 | 19.18 | 0.00 | 19.18 | 82.17 | 27.35 | 53.00 | 27.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 19.26 | 0.00 | 19.26 | 16.67 | 27.78 | 8.67 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.65 | 0.17 | 27.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.16 | 4.00 | 28.21 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 28.20 | 5.00 | 28.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 27.64 | 5.67 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 27.61 | 8.17 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 27.58 | 4.50 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.54 | 4.33 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.64 | 3.17 | 27.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
Annual Sum or Average | 1.33 | 19.05 | 0.00 | 19.05 | 101.50 | 27.61 | 35.00 | 27.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.09 | 0.00 | 19.09 | 27.50 | 28.20 | 8.17 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 238.50 | 28.50 | 189.17 | 28.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 155.17 | 28.52 | 128.00 | 28.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.00 | 6.67 | 28.00 |
Annual Sum or Average | 0.00 | 0.00 | 400.33 | 28.50 | 323.83 | 28.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 238.50 | 28.52 | 189.17 | 28.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 236.50 | 28.43 | 186.33 | 28.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 165.50 | 28.44 | 139.33 | 28.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 402.00 | 28.43 | 325.67 | 28.41 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 236.50 | 28.44 | 186.33 | 28.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 204.67 | 28.49 | 163.67 | 28.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 148.33 | 28.59 | 121.50 | 28.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 353.00 | 28.54 | 285.17 | 28.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 204.67 | 28.59 | 163.67 | 28.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 95.83 | 24.00 | 121.33 | 25.25 | 0.00 | 25.25 |
February | 34.50 | 24.00 | 195.50 | 25.00 | 0.00 | 25.00 |
March | 89.00 | 24.01 | 111.17 | 24.94 | 0.00 | 24.94 |
April | 97.33 | 24.00 | 92.83 | 25.17 | 0.00 | 25.17 |
May | 119.17 | 24.00 | 83.17 | 24.99 | 0.00 | 24.99 |
June | 26.50 | 24.00 | 124.33 | 25.49 | 0.00 | 25.49 |
July | 148.17 | 24.48 | 414.83 | 24.72 | 138.33 | 24.68 |
August | 125.67 | 24.71 | 453.50 | 24.64 | 123.17 | 24.65 |
September | 92.17 | 25.12 | 395.17 | 24.85 | 92.17 | 24.89 |
October | 50.33 | 24.02 | 216.00 | 25.18 | 2.67 | 25.17 |
November | 66.33 | 24.60 | 205.83 | 25.30 | 19.17 | 25.35 |
December | 145.00 | 24.00 | 107.67 | 25.09 | 0.00 | 25.09 |
Annual Sum or Average | 1090.00 | 24.28 | 2521.33 | 24.96 | 375.50 | 24.95 |
Minimum of Months | 26.50 | 24.00 | 83.17 | 24.64 | 0.00 | 24.65 |
Maximum of Months | 148.17 | 25.12 | 453.50 | 25.49 | 138.33 | 25.49 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 138.33 | 23.99 | 69.50 | 24.54 | 0.00 | 24.54 |
February | 33.50 | 23.94 | 180.33 | 24.68 | 0.00 | 24.68 |
March | 72.17 | 24.01 | 100.00 | 24.69 | 0.00 | 24.69 |
April | 80.17 | 24.03 | 21.00 | 24.24 | 0.00 | 24.24 |
May | 99.00 | 24.01 | 18.50 | 24.30 | 0.00 | 24.30 |
June | 11.67 | 24.01 | 79.83 | 24.41 | 0.00 | 24.41 |
July | 12.67 | 24.04 | 387.00 | 24.21 | 0.00 | 24.21 |
August | 0.33 | 23.80 | 449.67 | 24.22 | 0.00 | 24.22 |
September | 11.00 | 26.01 | 387.33 | 24.41 | 11.00 | 24.45 |
October | 66.33 | 24.02 | 191.67 | 24.62 | 0.00 | 24.62 |
November | 77.00 | 24.06 | 175.67 | 24.64 | 3.50 | 24.65 |
December | 182.50 | 24.01 | 74.67 | 24.56 | 0.00 | 24.56 |
Annual Sum or Average | 784.67 | 24.04 | 2135.17 | 24.44 | 14.50 | 24.45 |
Minimum of Months | 0.33 | 23.80 | 18.50 | 24.21 | 0.00 | 24.21 |
Maximum of Months | 182.50 | 26.01 | 449.67 | 24.69 | 11.00 | 24.69 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 358.00 | 23.68 | 13.67 | 23.72 | 0.00 | 23.72 |
February | 215.83 | 23.58 | 47.67 | 23.74 | 0.67 | 23.74 |
March | 234.00 | 23.79 | 48.00 | 23.96 | 0.00 | 23.96 |
April | 218.00 | 23.94 | 9.67 | 24.01 | 0.00 | 24.01 |
May | 207.50 | 23.99 | 7.83 | 24.05 | 0.00 | 24.05 |
June | 89.67 | 23.95 | 38.83 | 24.03 | 0.00 | 24.03 |
July | 37.83 | 24.08 | 358.50 | 24.15 | 6.67 | 24.16 |
August | 53.67 | 24.27 | 412.83 | 24.16 | 27.83 | 24.18 |
September | 36.67 | 24.99 | 370.00 | 24.38 | 32.83 | 24.43 |
October | 177.00 | 23.89 | 124.33 | 24.18 | 2.33 | 24.18 |
November | 272.67 | 23.84 | 99.67 | 24.05 | 22.33 | 24.07 |
December | 459.33 | 23.72 | 0.00 | 23.72 | 0.00 | 23.72 |
Annual Sum or Average | 2360.17 | 23.82 | 1531.00 | 24.02 | 92.67 | 24.03 |
Minimum of Months | 36.67 | 23.58 | 0.00 | 23.72 | 0.00 | 23.72 |
Maximum of Months | 459.33 | 24.99 | 412.83 | 24.38 | 32.83 | 24.43 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 477.50 | 22.99 | 18.67 | 22.86 | 18.67 | 22.74 |
February | 400.50 | 22.74 | 4.67 | 22.72 | 4.50 | 22.70 |
March | 362.17 | 23.26 | 19.67 | 23.27 | 5.83 | 23.24 |
April | 213.83 | 23.84 | 9.67 | 23.89 | 0.00 | 23.89 |
May | 171.17 | 23.98 | 7.00 | 24.04 | 0.00 | 24.04 |
June | 51.83 | 23.90 | 90.67 | 24.26 | 0.00 | 24.26 |
July | 33.67 | 24.06 | 387.17 | 24.25 | 12.83 | 24.25 |
August | 48.83 | 24.23 | 432.67 | 24.21 | 37.17 | 24.22 |
September | 51.33 | 24.74 | 384.50 | 24.41 | 50.67 | 24.44 |
October | 250.83 | 23.56 | 113.00 | 23.83 | 5.67 | 23.83 |
November | 356.17 | 23.07 | 79.83 | 23.28 | 28.67 | 23.31 |
December | 497.00 | 22.46 | 48.00 | 22.32 | 48.00 | 22.20 |
Annual Sum or Average | 2914.83 | 23.16 | 1595.50 | 23.50 | 212.00 | 23.48 |
Minimum of Months | 33.67 | 22.46 | 4.67 | 22.32 | 0.00 | 22.20 |
Maximum of Months | 497.00 | 24.74 | 432.67 | 24.41 | 50.67 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 476.67 | 23.52 | 8.00 | 23.54 | 0.00 | 23.54 |
February | 321.17 | 23.32 | 10.50 | 23.35 | 0.00 | 23.35 |
March | 286.00 | 23.59 | 36.50 | 23.70 | 0.00 | 23.70 |
April | 128.83 | 23.96 | 49.17 | 24.31 | 0.00 | 24.31 |
May | 63.00 | 23.99 | 65.00 | 24.91 | 0.00 | 24.91 |
June | 10.50 | 26.26 | 265.33 | 24.87 | 8.33 | 24.93 |
July | 17.00 | 26.66 | 453.67 | 24.65 | 16.17 | 24.72 |
August | 12.50 | 26.53 | 469.17 | 24.48 | 11.50 | 24.54 |
September | 19.83 | 26.22 | 424.00 | 24.60 | 19.83 | 24.67 |
October | 195.67 | 23.79 | 145.83 | 24.14 | 0.00 | 24.14 |
November | 304.67 | 23.63 | 84.00 | 23.80 | 2.00 | 23.80 |
December | 469.00 | 23.44 | 0.00 | 23.44 | 0.00 | 23.44 |
Annual Sum or Average | 2304.83 | 23.63 | 2011.17 | 24.09 | 57.83 | 24.12 |
Minimum of Months | 10.50 | 23.32 | 0.00 | 23.35 | 0.00 | 23.35 |
Maximum of Months | 476.67 | 26.66 | 469.17 | 24.91 | 19.83 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 329.50 | 23.47 | 29.50 | 23.64 | 0.00 | 23.64 |
February | 258.17 | 23.12 | 55.83 | 23.39 | 0.33 | 23.40 |
March | 230.50 | 23.42 | 77.00 | 23.76 | 0.00 | 23.76 |
April | 71.83 | 23.98 | 146.67 | 24.62 | 4.50 | 24.68 |
May | 28.50 | 25.05 | 194.17 | 25.07 | 9.50 | 25.17 |
June | 34.00 | 26.82 | 373.50 | 24.79 | 31.83 | 24.95 |
July | 34.50 | 26.80 | 462.33 | 24.72 | 33.17 | 24.86 |
August | 29.67 | 26.66 | 487.00 | 24.54 | 27.17 | 24.66 |
September | 36.67 | 26.51 | 445.50 | 24.68 | 36.50 | 24.80 |
October | 140.50 | 23.74 | 194.00 | 24.33 | 3.83 | 24.36 |
November | 247.83 | 23.48 | 97.17 | 23.76 | 4.00 | 23.76 |
December | 410.83 | 23.27 | 15.83 | 23.33 | 3.00 | 23.32 |
Annual Sum or Average | 1852.50 | 23.67 | 2578.50 | 24.23 | 153.83 | 24.31 |
Minimum of Months | 28.50 | 23.12 | 15.83 | 23.33 | 0.00 | 23.32 |
Maximum of Months | 410.83 | 26.82 | 487.00 | 25.07 | 36.50 | 25.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 143.00 | 23.75 | 161.00 | 24.41 | 8.17 | 24.49 |
February | 177.33 | 23.24 | 118.67 | 23.76 | 1.00 | 23.77 |
March | 165.83 | 23.51 | 114.17 | 24.00 | 0.00 | 24.00 |
April | 74.50 | 23.97 | 152.50 | 24.64 | 1.00 | 24.66 |
May | 66.33 | 24.00 | 91.83 | 24.90 | 0.00 | 24.90 |
June | 16.67 | 25.41 | 256.17 | 24.83 | 8.17 | 24.89 |
July | 29.50 | 26.36 | 446.00 | 24.69 | 24.67 | 24.79 |
August | 21.83 | 26.81 | 481.50 | 24.57 | 21.00 | 24.66 |
September | 41.67 | 26.70 | 451.83 | 24.79 | 41.67 | 24.94 |
October | 98.33 | 24.55 | 280.50 | 24.79 | 23.67 | 24.93 |
November | 111.00 | 23.89 | 236.17 | 24.44 | 8.33 | 24.48 |
December | 231.33 | 23.72 | 102.17 | 24.22 | 10.33 | 24.31 |
Annual Sum or Average | 1177.33 | 23.99 | 2892.50 | 24.52 | 148.00 | 24.60 |
Minimum of Months | 16.67 | 23.24 | 91.83 | 23.76 | 0.00 | 23.77 |
Maximum of Months | 231.33 | 26.81 | 481.50 | 24.90 | 41.67 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 202.17 | 23.64 | 76.83 | 24.06 | 0.83 | 24.07 |
February | 77.17 | 23.57 | 181.67 | 24.36 | 1.33 | 24.37 |
March | 38.17 | 24.21 | 252.50 | 24.80 | 4.17 | 24.84 |
April | 30.00 | 26.85 | 333.17 | 25.08 | 27.00 | 25.22 |
May | 19.00 | 26.85 | 265.67 | 25.17 | 16.83 | 25.29 |
June | 31.33 | 27.01 | 424.50 | 24.82 | 31.33 | 24.96 |
July | 81.17 | 26.84 | 480.33 | 25.03 | 81.17 | 25.26 |
August | 76.33 | 26.87 | 505.33 | 24.90 | 76.33 | 25.13 |
September | 42.50 | 26.85 | 466.50 | 24.80 | 42.50 | 24.96 |
October | 58.00 | 24.78 | 300.67 | 24.93 | 16.67 | 25.03 |
November | 54.00 | 24.81 | 252.17 | 24.96 | 15.50 | 25.06 |
December | 118.50 | 24.07 | 130.17 | 24.91 | 6.83 | 24.97 |
Annual Sum or Average | 828.33 | 24.97 | 3669.50 | 24.85 | 320.50 | 24.99 |
Minimum of Months | 19.00 | 23.57 | 76.83 | 24.06 | 0.83 | 24.07 |
Maximum of Months | 202.17 | 27.01 | 505.33 | 25.17 | 81.17 | 25.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.40 | 26.83 | 22.29 | 26.83 | 22.19 |
February | 448.67 | 22.25 | 3.83 | 22.24 | 3.83 | 22.22 |
March | 445.33 | 22.86 | 13.00 | 22.81 | 12.00 | 22.76 |
April | 224.00 | 23.78 | 19.50 | 23.89 | 0.00 | 23.89 |
May | 103.50 | 23.99 | 52.00 | 24.60 | 0.00 | 24.60 |
June | 11.67 | 25.62 | 217.83 | 25.03 | 6.83 | 25.08 |
July | 11.83 | 25.63 | 430.83 | 24.64 | 7.50 | 24.67 |
August | 18.33 | 24.98 | 457.00 | 24.44 | 12.17 | 24.46 |
September | 25.00 | 25.87 | 401.33 | 24.61 | 23.50 | 24.68 |
October | 289.83 | 23.27 | 106.17 | 23.60 | 0.00 | 23.60 |
November | 422.83 | 22.64 | 58.67 | 22.78 | 24.67 | 22.80 |
December | 497.00 | 21.77 | 122.50 | 21.58 | 122.50 | 21.46 |
Annual Sum or Average | 3000.00 | 22.69 | 1909.50 | 23.30 | 239.83 | 23.24 |
Minimum of Months | 11.67 | 21.77 | 3.83 | 21.58 | 0.00 | 21.46 |
Maximum of Months | 502.00 | 25.87 | 457.00 | 25.03 | 122.50 | 25.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 381.50 | 22.86 | 14.67 | 22.85 | 7.17 | 22.81 |
February | 319.67 | 22.52 | 16.67 | 22.62 | 1.33 | 22.61 |
March | 282.83 | 22.99 | 43.00 | 23.26 | 3.83 | 23.23 |
April | 75.83 | 24.06 | 129.00 | 24.88 | 7.00 | 24.96 |
May | 36.50 | 25.14 | 163.50 | 25.38 | 13.00 | 25.50 |
June | 36.67 | 26.80 | 302.33 | 25.04 | 33.50 | 25.22 |
July | 44.00 | 26.83 | 389.67 | 25.01 | 42.50 | 25.18 |
August | 37.33 | 26.60 | 407.83 | 24.77 | 34.83 | 24.92 |
September | 41.83 | 26.55 | 365.33 | 24.89 | 40.83 | 25.05 |
October | 167.00 | 23.39 | 147.50 | 24.13 | 2.00 | 24.15 |
November | 298.00 | 22.95 | 54.00 | 23.14 | 14.00 | 23.16 |
December | 416.83 | 22.33 | 46.00 | 22.18 | 46.00 | 22.06 |
Annual Sum or Average | 2138.00 | 23.15 | 2079.50 | 23.93 | 246.00 | 24.00 |
Minimum of Months | 36.50 | 22.33 | 14.67 | 22.18 | 1.33 | 22.06 |
Maximum of Months | 416.83 | 26.83 | 407.83 | 25.38 | 46.00 | 25.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 188.67 | 23.61 | 161.33 | 24.22 | 14.50 | 24.30 |
February | 242.17 | 22.87 | 96.33 | 23.36 | 0.83 | 23.37 |
March | 244.83 | 23.23 | 82.17 | 23.60 | 2.83 | 23.58 |
April | 113.67 | 23.85 | 119.00 | 24.53 | 0.17 | 24.53 |
May | 95.83 | 23.99 | 78.83 | 24.78 | 0.00 | 24.78 |
June | 22.50 | 24.81 | 208.83 | 24.93 | 6.67 | 24.99 |
July | 26.17 | 25.91 | 434.50 | 24.69 | 18.83 | 24.76 |
August | 27.83 | 25.81 | 476.00 | 24.56 | 22.33 | 24.63 |
September | 42.33 | 26.71 | 443.33 | 24.83 | 42.33 | 24.99 |
October | 118.17 | 24.25 | 254.00 | 24.72 | 22.83 | 24.86 |
November | 172.33 | 23.66 | 208.33 | 24.23 | 20.33 | 24.28 |
December | 280.67 | 23.24 | 93.17 | 23.67 | 19.67 | 23.67 |
Annual Sum or Average | 1575.17 | 23.64 | 2655.83 | 24.34 | 171.33 | 24.41 |
Minimum of Months | 22.50 | 22.87 | 78.83 | 23.36 | 0.00 | 23.37 |
Maximum of Months | 280.67 | 26.71 | 476.00 | 24.93 | 42.33 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 398.33 | 22.81 | 27.67 | 22.87 | 9.17 | 22.82 |
February | 385.50 | 22.53 | 15.67 | 22.60 | 0.00 | 22.60 |
March | 324.33 | 23.00 | 55.33 | 23.25 | 0.83 | 23.25 |
April | 95.67 | 24.07 | 182.33 | 24.73 | 9.50 | 24.81 |
May | 57.33 | 24.75 | 203.67 | 25.08 | 13.67 | 25.19 |
June | 22.50 | 26.74 | 333.67 | 24.91 | 20.67 | 25.02 |
July | 38.83 | 26.83 | 463.83 | 24.85 | 37.33 | 24.99 |
August | 29.00 | 26.71 | 484.33 | 24.64 | 29.00 | 24.76 |
September | 36.50 | 26.52 | 437.00 | 24.76 | 36.50 | 24.89 |
October | 181.83 | 23.44 | 181.83 | 24.08 | 7.50 | 24.14 |
November | 311.50 | 23.00 | 104.50 | 23.35 | 17.50 | 23.37 |
December | 452.83 | 22.38 | 46.50 | 22.31 | 40.17 | 22.21 |
Annual Sum or Average | 2334.17 | 23.09 | 2536.33 | 23.90 | 221.83 | 23.96 |
Minimum of Months | 22.50 | 22.38 | 15.67 | 22.31 | 0.00 | 22.21 |
Maximum of Months | 452.83 | 26.83 | 484.33 | 25.08 | 40.17 | 25.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.66 | 111.00 | 21.40 | 111.00 | 21.21 |
February | 454.00 | 21.43 | 83.67 | 21.25 | 83.67 | 21.11 |
March | 468.17 | 22.29 | 56.67 | 22.12 | 54.33 | 21.97 |
April | 226.83 | 23.55 | 34.50 | 23.76 | 0.00 | 23.76 |
May | 109.17 | 23.91 | 68.83 | 24.57 | 0.00 | 24.57 |
June | 23.67 | 26.00 | 292.50 | 24.92 | 16.17 | 25.02 |
July | 35.83 | 26.20 | 451.00 | 24.75 | 29.83 | 24.86 |
August | 34.00 | 25.27 | 466.83 | 24.50 | 26.00 | 24.56 |
September | 48.83 | 25.54 | 411.00 | 24.66 | 40.17 | 24.76 |
October | 316.00 | 22.79 | 121.33 | 23.12 | 20.00 | 23.06 |
November | 450.00 | 22.01 | 131.83 | 21.86 | 116.17 | 21.71 |
December | 497.00 | 20.99 | 294.33 | 20.80 | 294.33 | 20.71 |
Annual Sum or Average | 3165.50 | 22.17 | 2523.50 | 22.77 | 791.67 | 22.60 |
Minimum of Months | 23.67 | 20.99 | 34.50 | 20.80 | 0.00 | 20.71 |
Maximum of Months | 502.00 | 26.20 | 466.83 | 24.92 | 294.33 | 25.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.83 | 22.50 | 52.50 | 22.28 | 51.17 | 22.09 |
February | 424.17 | 22.07 | 46.17 | 21.91 | 45.33 | 21.76 |
March | 358.00 | 22.69 | 41.50 | 22.74 | 17.33 | 22.65 |
April | 77.17 | 23.79 | 180.00 | 24.64 | 6.33 | 24.71 |
May | 44.17 | 25.12 | 245.50 | 25.01 | 16.17 | 25.14 |
June | 45.83 | 26.76 | 418.33 | 24.85 | 41.50 | 25.03 |
July | 57.33 | 26.90 | 471.17 | 24.94 | 55.83 | 25.13 |
August | 48.67 | 26.55 | 492.00 | 24.71 | 45.83 | 24.86 |
September | 50.67 | 26.39 | 444.17 | 24.78 | 45.83 | 24.94 |
October | 210.17 | 23.13 | 177.17 | 23.82 | 9.83 | 23.81 |
November | 386.50 | 22.52 | 87.00 | 22.49 | 59.67 | 22.38 |
December | 497.00 | 21.61 | 176.33 | 21.34 | 176.33 | 21.19 |
Annual Sum or Average | 2693.50 | 22.74 | 2831.83 | 23.48 | 571.17 | 23.43 |
Minimum of Months | 44.17 | 21.61 | 41.50 | 21.34 | 6.33 | 21.19 |
Maximum of Months | 497.00 | 26.90 | 492.00 | 25.01 | 176.33 | 25.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 251.33 | 22.94 | 128.17 | 23.45 | 15.83 | 23.39 |
February | 305.33 | 22.20 | 78.33 | 22.41 | 20.83 | 22.27 |
March | 310.33 | 22.77 | 76.50 | 22.93 | 21.67 | 22.81 |
April | 128.83 | 23.63 | 142.17 | 24.36 | 2.33 | 24.39 |
May | 100.83 | 23.85 | 108.00 | 24.62 | 0.33 | 24.63 |
June | 36.17 | 25.17 | 277.50 | 24.83 | 14.67 | 24.93 |
July | 40.17 | 26.16 | 444.50 | 24.76 | 32.50 | 24.88 |
August | 41.50 | 25.76 | 480.17 | 24.60 | 34.33 | 24.69 |
September | 50.50 | 26.49 | 445.50 | 24.85 | 49.00 | 25.00 |
October | 159.17 | 23.77 | 235.00 | 24.40 | 26.50 | 24.53 |
November | 229.33 | 22.97 | 175.00 | 23.47 | 41.67 | 23.37 |
December | 340.50 | 22.58 | 119.83 | 22.65 | 67.67 | 22.45 |
Annual Sum or Average | 1994.00 | 23.15 | 2710.67 | 23.93 | 327.33 | 23.93 |
Minimum of Months | 36.17 | 22.20 | 76.50 | 22.41 | 0.33 | 22.27 |
Maximum of Months | 340.50 | 26.49 | 480.17 | 24.85 | 67.67 | 25.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 420.50 | 22.16 | 47.50 | 22.06 | 37.50 | 21.91 |
February | 412.17 | 21.83 | 31.67 | 21.81 | 22.17 | 21.74 |
March | 377.33 | 22.48 | 73.00 | 22.60 | 27.33 | 22.49 |
April | 123.67 | 23.83 | 188.50 | 24.52 | 12.50 | 24.63 |
May | 87.67 | 24.52 | 224.17 | 24.89 | 17.67 | 25.01 |
June | 29.67 | 26.61 | 359.83 | 24.88 | 25.67 | 25.01 |
July | 54.17 | 26.66 | 464.67 | 24.88 | 50.50 | 25.06 |
August | 36.83 | 26.50 | 489.33 | 24.65 | 36.83 | 24.77 |
September | 47.50 | 26.10 | 438.17 | 24.75 | 43.83 | 24.88 |
October | 233.00 | 23.04 | 177.17 | 23.71 | 13.17 | 23.75 |
November | 362.50 | 22.44 | 117.67 | 22.57 | 61.67 | 22.47 |
December | 468.33 | 21.68 | 165.33 | 21.45 | 163.00 | 21.30 |
Annual Sum or Average | 2653.33 | 22.61 | 2777.00 | 23.45 | 511.83 | 23.42 |
Minimum of Months | 29.67 | 21.68 | 31.67 | 21.45 | 12.50 | 21.30 |
Maximum of Months | 468.33 | 26.66 | 489.33 | 24.89 | 163.00 | 25.06 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 2.67 | 27.00 | 454.00 | 27.00 | 2.67 | 27.00 |
March | 2.50 | 27.00 | 514.00 | 27.00 | 2.50 | 27.00 |
April | 180.67 | 28.45 | 485.00 | 27.84 | 180.67 | 27.97 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 12.00 | 27.00 | 496.00 | 27.00 | 12.00 | 27.00 |
July | 215.33 | 27.00 | 497.00 | 27.00 | 215.33 | 27.00 |
August | 431.33 | 27.48 | 514.00 | 27.44 | 431.33 | 27.45 |
September | 9.17 | 27.00 | 485.00 | 27.00 | 9.17 | 27.00 |
October | 18.33 | 27.00 | 502.00 | 27.00 | 18.33 | 27.00 |
November | 32.67 | 27.00 | 489.00 | 27.00 | 32.67 | 27.00 |
December | 15.17 | 27.50 | 497.00 | 27.03 | 15.17 | 27.05 |
Annual Sum or Average | 919.83 | 27.52 | 5943.00 | 27.14 | 919.83 | 27.19 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 431.33 | 28.45 | 514.00 | 27.84 | 431.33 | 27.97 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 109.33 | 28.69 | 485.00 | 27.78 | 109.33 | 27.92 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 0.00 | 0.00 | 496.00 | 27.00 | 0.00 | 27.00 |
July | 3.50 | 27.00 | 497.00 | 27.00 | 3.50 | 27.00 |
August | 172.50 | 28.15 | 514.00 | 27.61 | 172.50 | 27.72 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
November | 1.83 | 27.00 | 489.00 | 27.00 | 1.83 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 287.17 | 28.34 | 5943.00 | 27.14 | 287.17 | 27.19 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 172.50 | 28.69 | 514.00 | 27.78 | 172.50 | 27.92 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.50 | 24.97 | 461.83 | 26.95 | 0.00 | 26.95 |
February | 0.00 | 0.00 | 447.17 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 501.17 | 27.00 | 0.00 | 27.00 |
April | 114.00 | 28.65 | 485.00 | 27.73 | 114.00 | 27.88 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 10.67 | 27.00 | 496.00 | 27.00 | 10.67 | 27.00 |
July | 61.33 | 27.00 | 497.00 | 27.00 | 61.33 | 27.00 |
August | 181.33 | 28.07 | 514.00 | 27.57 | 181.33 | 27.67 |
September | 11.17 | 27.00 | 485.00 | 27.00 | 11.17 | 27.00 |
October | 1.33 | 27.00 | 502.00 | 27.00 | 1.33 | 27.00 |
November | 2.50 | 27.00 | 477.00 | 27.00 | 2.50 | 27.00 |
December | 0.00 | 0.00 | 392.83 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 393.83 | 27.91 | 5767.00 | 27.13 | 382.33 | 27.18 |
Minimum of Months | 0.00 | 0.00 | 392.83 | 26.95 | 0.00 | 26.95 |
Maximum of Months | 181.33 | 28.65 | 514.00 | 27.73 | 181.33 | 27.88 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5943.00 | 27.00 | 5943.00 | 27.00 | 5943.00 | 27.00 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00001 | 22.70672 | 0.80755 | 18.82579 |
February | 454.00000 | 27.00023 | 29.25624 | 0.88210 | 21.48085 |
March | 514.00000 | 27.00004 | 26.44759 | 0.90640 | 22.42252 |
April | 485.00000 | 27.60904 | 18.37326 | 1.00126 | 26.52951 |
May | 508.00000 | 27.00000 | 17.49348 | 0.13479 | 5.42603 |
June | 496.00000 | 27.00000 | 23.60012 | 0.25079 | 6.38662 |
July | 497.00000 | 27.00035 | 32.64003 | 0.36616 | 7.87646 |
August | 514.00000 | 27.40785 | 33.45429 | 0.51106 | 11.08441 |
September | 485.00000 | 27.00069 | 34.33826 | 0.28203 | 6.71385 |
October | 502.00000 | 27.00012 | 25.07285 | 0.88836 | 21.78993 |
November | 489.00000 | 27.00015 | 24.54296 | 0.90343 | 22.34398 |
December | 497.00000 | 27.02074 | 17.27658 | 0.85971 | 20.69496 |
Annual Sum or Average | 5943.00000 | 27.08684 | 25.41221 | 0.64726 | 15.90735 |
Minimum of Months | 454.00000 | 27.00000 | 17.27658 | 0.13479 | 5.42603 |
Maximum of Months | 514.00000 | 27.60904 | 34.33826 | 1.00126 | 26.52951 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00001 | 22.69735 | 0.73242 | 16.39234 |
February | 454.00000 | 27.00022 | 29.28217 | 0.78249 | 17.98227 |
March | 514.00000 | 27.00003 | 26.41743 | 0.80642 | 18.82374 |
April | 485.00000 | 27.58064 | 18.35394 | 0.91341 | 23.01909 |
May | 508.00000 | 27.00000 | 17.47138 | 0.08677 | 5.21542 |
June | 496.00000 | 27.00000 | 23.58350 | 0.18032 | 5.76080 |
July | 497.00000 | 27.00033 | 32.65039 | 0.26671 | 6.56498 |
August | 514.00000 | 27.42280 | 33.44196 | 0.39510 | 8.90474 |
September | 485.00000 | 27.00059 | 34.41203 | 0.22730 | 6.13486 |
October | 502.00000 | 27.00011 | 25.05400 | 0.81685 | 19.23217 |
November | 489.00000 | 27.00014 | 24.52318 | 0.79485 | 18.48295 |
December | 497.00000 | 27.00186 | 17.27041 | 0.70259 | 15.52152 |
Annual Sum or Average | 5943.00000 | 27.08423 | 25.40802 | 0.55658 | 13.45474 |
Minimum of Months | 454.00000 | 27.00000 | 17.27041 | 0.08677 | 5.21542 |
Maximum of Months | 514.00000 | 27.58064 | 34.41203 | 0.91341 | 23.01909 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.95116 | 22.73337 | 0.66923 | 14.76022 |
February | 454.00000 | 27.00022 | 29.33332 | 0.72186 | 16.13379 |
March | 514.00000 | 27.00003 | 26.43666 | 0.76803 | 17.64043 |
April | 485.00000 | 27.51273 | 18.40041 | 0.90123 | 22.68704 |
May | 508.00000 | 27.00000 | 17.47930 | 0.10007 | 5.32677 |
June | 496.00000 | 27.00000 | 23.59005 | 0.21149 | 6.07533 |
July | 497.00000 | 27.00036 | 32.65394 | 0.29663 | 6.96544 |
August | 514.00000 | 27.39549 | 33.46630 | 0.41104 | 9.37442 |
September | 485.00000 | 27.00065 | 34.40196 | 0.24223 | 6.32348 |
October | 502.00000 | 27.00011 | 25.06623 | 0.79713 | 18.65317 |
November | 489.00000 | 27.00015 | 24.54674 | 0.74637 | 17.02257 |
December | 497.00000 | 27.00018 | 17.27904 | 0.62560 | 13.46873 |
Annual Sum or Average | 5943.00000 | 27.07206 | 25.42692 | 0.53904 | 12.83075 |
Minimum of Months | 454.00000 | 26.95116 | 17.27904 | 0.10007 | 5.32677 |
Maximum of Months | 514.00000 | 27.51273 | 34.40196 | 0.90123 | 22.68704 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 37.28359 | 1.12655 | 31.74259 |
February | 454.00000 | 27.00000 | 36.90181 | 1.25502 | 37.98127 |
March | 514.00000 | 27.00000 | 36.90498 | 1.39574 | 45.28615 |
April | 485.00000 | 27.00000 | 36.89943 | 1.54405 | 53.29774 |
May | 508.00000 | 27.00000 | 37.10225 | 0.51835 | 10.65379 |
June | 496.00000 | 27.00000 | 36.89982 | 0.74615 | 16.73174 |
July | 497.00000 | 27.00000 | 36.97649 | 0.97709 | 25.17382 |
August | 514.00000 | 27.00000 | 36.94691 | 1.17731 | 34.15031 |
September | 485.00000 | 27.00000 | 37.13500 | 0.61135 | 12.86255 |
October | 502.00000 | 27.00000 | 36.96411 | 1.31736 | 41.16711 |
November | 489.00000 | 27.00000 | 36.95589 | 1.45016 | 48.20254 |
December | 497.00000 | 27.00000 | 36.91434 | 1.56767 | 54.58423 |
Annual Sum or Average | 5943.00000 | 27.00000 | 36.99104 | 1.13946 | 34.27295 |
Minimum of Months | 454.00000 | 27.00000 | 36.89943 | 0.51835 | 10.65379 |
Maximum of Months | 514.00000 | 27.00000 | 37.28359 | 1.56767 | 54.58423 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.62063 | 20.49207 | 0.37259 | 8.53873 |
February | 454.00000 | 24.54406 | 32.61663 | 0.43298 | 9.55150 |
March | 514.00000 | 24.45795 | 26.13935 | 0.37021 | 8.31417 |
April | 485.00000 | 24.57522 | 19.08462 | 0.35089 | 8.00064 |
May | 508.00000 | 24.54541 | 18.58991 | -0.5170 | 11.42127 |
June | 496.00000 | 24.51271 | 26.10319 | -0.4627 | 10.40540 |
July | 497.00000 | 24.68762 | 45.28144 | -0.2579 | 7.70983 |
August | 514.00000 | 24.55430 | 48.01288 | -0.2648 | 7.63608 |
September | 485.00000 | 24.63990 | 46.96938 | -0.2461 | 7.86787 |
October | 502.00000 | 24.68330 | 26.77259 | 0.45087 | 10.16117 |
November | 489.00000 | 24.68330 | 26.42335 | 0.44671 | 10.18768 |
December | 497.00000 | 24.66971 | 14.65613 | 0.35192 | 8.29646 |
Annual Sum or Average | 5943.00000 | 24.59756 | 29.24215 | 0.08211 | 9.00528 |
Minimum of Months | 454.00000 | 24.45795 | 14.65613 | -0.5170 | 7.63608 |
Maximum of Months | 514.00000 | 24.68762 | 48.01288 | 0.45087 | 11.42127 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.31438 | 21.91957 | 0.32057 | 7.44462 |
February | 454.00000 | 24.33698 | 34.23689 | 0.40759 | 8.87346 |
March | 514.00000 | 24.29948 | 27.01776 | 0.36356 | 8.06892 |
April | 485.00000 | 24.20672 | 20.03421 | 0.31555 | 7.18615 |
May | 508.00000 | 24.22087 | 19.59049 | -0.5658 | 11.92518 |
June | 496.00000 | 24.15249 | 27.69513 | -0.5121 | 10.67115 |
July | 497.00000 | 24.22664 | 45.42160 | -0.3564 | 7.96345 |
August | 514.00000 | 24.20941 | 47.91968 | -0.3346 | 7.62173 |
September | 485.00000 | 24.29792 | 47.15829 | -0.3383 | 7.94667 |
October | 502.00000 | 24.37729 | 27.88027 | 0.39866 | 8.80363 |
November | 489.00000 | 24.40159 | 27.14247 | 0.39550 | 8.84775 |
December | 497.00000 | 24.40615 | 15.85669 | 0.30922 | 7.34801 |
Annual Sum or Average | 5943.00000 | 24.28693 | 30.13058 | 0.03002 | 8.56080 |
Minimum of Months | 454.00000 | 24.15249 | 15.85669 | -0.5658 | 7.18615 |
Maximum of Months | 514.00000 | 24.40615 | 47.91968 | 0.40759 | 11.92518 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.88304 | 23.24733 | 0.19616 | 6.16493 |
February | 454.00000 | 23.87776 | 36.19296 | 0.27506 | 6.81019 |
March | 514.00000 | 24.03896 | 28.28550 | 0.27316 | 6.81482 |
April | 485.00000 | 24.12472 | 20.27829 | 0.26297 | 6.61751 |
May | 508.00000 | 24.15372 | 19.70128 | -0.6133 | 13.10095 |
June | 496.00000 | 24.07042 | 27.55193 | -0.5754 | 12.07138 |
July | 497.00000 | 24.14099 | 45.88406 | -0.4304 | 9.24438 |
August | 514.00000 | 24.13403 | 48.80483 | -0.4094 | 8.81521 |
September | 485.00000 | 24.24076 | 47.40707 | -0.3880 | 8.67343 |
October | 502.00000 | 24.19465 | 28.40641 | 0.32861 | 7.68419 |
November | 489.00000 | 24.07741 | 28.65235 | 0.28672 | 7.35049 |
December | 497.00000 | 23.77257 | 17.71459 | 0.12270 | 5.60073 |
Annual Sum or Average | 5943.00000 | 24.06017 | 30.97882 | -0.0592 | 8.26336 |
Minimum of Months | 454.00000 | 23.77257 | 17.71459 | -0.6133 | 5.60073 |
Maximum of Months | 514.00000 | 24.24076 | 48.80483 | 0.32861 | 13.10095 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.04369 | 25.11723 | -0.0174 | 6.41002 |
February | 454.00000 | 22.88436 | 39.19482 | 0.02660 | 5.97449 |
March | 514.00000 | 23.51815 | 29.57067 | 0.13787 | 6.23976 |
April | 485.00000 | 24.06220 | 20.44270 | 0.25452 | 6.60846 |
May | 508.00000 | 24.16085 | 19.82048 | -0.5927 | 12.60029 |
June | 496.00000 | 24.15526 | 27.58454 | -0.5141 | 10.83032 |
July | 497.00000 | 24.24511 | 45.74837 | -0.3657 | 8.25039 |
August | 514.00000 | 24.19441 | 48.64227 | -0.3650 | 8.13978 |
September | 485.00000 | 24.29131 | 47.50523 | -0.3544 | 8.24086 |
October | 502.00000 | 23.92529 | 29.05630 | 0.25938 | 7.22271 |
November | 489.00000 | 23.36797 | 30.21674 | 0.10488 | 6.79509 |
December | 497.00000 | 22.46064 | 19.44510 | -0.2069 | 7.16390 |
Annual Sum or Average | 5943.00000 | 23.69814 | 31.81451 | -0.1382 | 7.89257 |
Minimum of Months | 454.00000 | 22.46064 | 19.44510 | -0.5927 | 5.97449 |
Maximum of Months | 514.00000 | 24.29131 | 48.64227 | 0.25938 | 12.60029 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.56181 | 22.76537 | 0.10394 | 5.58752 |
February | 454.00000 | 23.53059 | 35.55702 | 0.17661 | 6.13091 |
March | 514.00000 | 23.84685 | 27.29588 | 0.21921 | 6.50054 |
April | 485.00000 | 24.24137 | 19.28883 | 0.31316 | 7.33111 |
May | 508.00000 | 24.36778 | 18.42293 | -0.4962 | 10.66603 |
June | 496.00000 | 24.45061 | 26.04762 | -0.3423 | 8.44475 |
July | 497.00000 | 24.53017 | 43.83893 | -0.2022 | 6.84603 |
August | 514.00000 | 24.39573 | 46.54511 | -0.2341 | 6.91492 |
September | 485.00000 | 24.45761 | 45.86420 | -0.2637 | 7.41162 |
October | 502.00000 | 24.16714 | 27.53778 | 0.32430 | 7.99455 |
November | 489.00000 | 23.84445 | 27.61797 | 0.22104 | 6.75026 |
December | 497.00000 | 23.48644 | 16.61126 | 0.04178 | 5.64973 |
Annual Sum or Average | 5943.00000 | 24.07690 | 29.74524 | -0.0138 | 7.19596 |
Minimum of Months | 454.00000 | 23.48644 | 16.61126 | -0.4962 | 5.58752 |
Maximum of Months | 514.00000 | 24.53017 | 46.54511 | 0.32430 | 10.66603 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.76688 | 21.75003 | 0.18394 | 6.36130 |
February | 454.00000 | 23.58749 | 34.88819 | 0.21836 | 6.88549 |
March | 514.00000 | 23.88355 | 26.76268 | 0.26038 | 7.19029 |
April | 485.00000 | 24.32627 | 18.85935 | 0.39063 | 8.90991 |
May | 508.00000 | 24.49060 | 18.02712 | -0.3643 | 9.10493 |
June | 496.00000 | 24.46965 | 25.83580 | -0.2528 | 7.79033 |
July | 497.00000 | 24.53237 | 43.71350 | -0.1350 | 6.65739 |
August | 514.00000 | 24.39080 | 46.37820 | -0.1704 | 6.74588 |
September | 485.00000 | 24.48234 | 45.53846 | -0.1939 | 7.07749 |
October | 502.00000 | 24.25082 | 26.91903 | 0.38852 | 9.30729 |
November | 489.00000 | 23.84527 | 27.25167 | 0.25048 | 7.12997 |
December | 497.00000 | 23.47949 | 16.12892 | 0.06229 | 6.07193 |
Annual Sum or Average | 5943.00000 | 24.12909 | 29.30145 | 0.05115 | 7.43918 |
Minimum of Months | 454.00000 | 23.47949 | 16.12892 | -0.3643 | 6.07193 |
Maximum of Months | 514.00000 | 24.53237 | 46.37820 | 0.39063 | 9.30729 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.27238 | 20.50724 | 0.36292 | 8.93717 |
February | 454.00000 | 23.85324 | 34.02594 | 0.29997 | 7.80151 |
March | 514.00000 | 24.04922 | 26.43404 | 0.30549 | 7.70357 |
April | 485.00000 | 24.39738 | 18.87889 | 0.38976 | 8.78892 |
May | 508.00000 | 24.40383 | 18.32427 | -0.4711 | 10.39797 |
June | 496.00000 | 24.42607 | 26.10989 | -0.3609 | 8.73412 |
July | 497.00000 | 24.53622 | 43.79592 | -0.1974 | 6.99357 |
August | 514.00000 | 24.43866 | 46.32096 | -0.1876 | 6.74681 |
September | 485.00000 | 24.57572 | 45.30552 | -0.1577 | 6.99607 |
October | 502.00000 | 24.50040 | 26.36516 | 0.48101 | 11.11848 |
November | 489.00000 | 24.31751 | 26.08914 | 0.41399 | 9.59765 |
December | 497.00000 | 24.13809 | 14.89748 | 0.27190 | 8.11541 |
Annual Sum or Average | 5943.00000 | 24.32827 | 28.88956 | 0.09324 | 8.49903 |
Minimum of Months | 454.00000 | 23.85324 | 14.89748 | -0.4711 | 6.74681 |
Maximum of Months | 514.00000 | 24.57572 | 46.32096 | 0.48101 | 11.11848 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.12239 | 21.01679 | 0.29971 | 7.52900 |
February | 454.00000 | 24.20437 | 33.24135 | 0.39599 | 8.81014 |
March | 514.00000 | 24.44597 | 25.46869 | 0.45186 | 9.97351 |
April | 485.00000 | 24.63713 | 18.33640 | 0.55537 | 12.41900 |
May | 508.00000 | 24.56074 | 17.89424 | -0.2978 | 8.38612 |
June | 496.00000 | 24.56531 | 25.62296 | -0.1446 | 7.17238 |
July | 497.00000 | 24.70300 | 43.20088 | 0.00677 | 6.91421 |
August | 514.00000 | 24.59618 | 45.68885 | 0.01895 | 6.77158 |
September | 485.00000 | 24.59453 | 45.21211 | -0.1065 | 6.78772 |
October | 502.00000 | 24.58436 | 26.24640 | 0.51289 | 11.61157 |
November | 489.00000 | 24.54208 | 25.63632 | 0.47954 | 10.82086 |
December | 497.00000 | 24.49454 | 14.48628 | 0.36589 | 8.61491 |
Annual Sum or Average | 5943.00000 | 24.50582 | 28.47377 | 0.20933 | 8.80997 |
Minimum of Months | 454.00000 | 24.12239 | 14.48628 | -0.2978 | 6.77158 |
Maximum of Months | 514.00000 | 24.70300 | 45.68885 | 0.55537 | 12.41900 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.40026 | 24.62700 | -0.1775 | 6.71096 |
February | 454.00000 | 22.26960 | 38.73181 | -0.1281 | 6.12739 |
March | 514.00000 | 23.02995 | 29.23332 | 0.00917 | 6.22498 |
April | 485.00000 | 24.06584 | 19.40493 | 0.24119 | 6.61416 |
May | 508.00000 | 24.32883 | 18.27983 | -0.5315 | 11.38233 |
June | 496.00000 | 24.45794 | 25.44214 | -0.3673 | 8.81421 |
July | 497.00000 | 24.54531 | 43.91451 | -0.2334 | 7.13559 |
August | 514.00000 | 24.38023 | 47.05884 | -0.2816 | 7.35538 |
September | 485.00000 | 24.43812 | 45.99144 | -0.2955 | 7.76481 |
October | 502.00000 | 23.70459 | 28.29889 | 0.19526 | 7.22035 |
November | 489.00000 | 22.83677 | 29.82653 | -0.0323 | 6.77418 |
December | 497.00000 | 21.77018 | 18.51125 | -0.3759 | 8.89436 |
Annual Sum or Average | 5943.00000 | 23.52759 | 30.72534 | -0.1660 | 7.59936 |
Minimum of Months | 454.00000 | 21.77018 | 18.27983 | -0.5315 | 6.12739 |
Maximum of Months | 514.00000 | 24.54531 | 47.05884 | 0.24119 | 11.38233 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.02243 | 22.74904 | -0.0106 | 6.24742 |
February | 385.00000 | 22.81603 | 36.81683 | 0.01975 | 6.35005 |
March | 433.00000 | 23.49240 | 27.33200 | 0.14356 | 6.82102 |
April | 410.00000 | 24.48087 | 18.01015 | 0.39709 | 9.26634 |
May | 430.00000 | 24.62115 | 17.23448 | -0.3489 | 9.27436 |
June | 418.00000 | 24.60905 | 24.64575 | -0.2321 | 8.01982 |
July | 422.00000 | 24.74901 | 42.87818 | -0.0967 | 6.97266 |
August | 433.00000 | 24.57065 | 45.77664 | -0.1471 | 7.01835 |
September | 410.00000 | 24.62273 | 44.97930 | -0.1806 | 7.41730 |
October | 427.00000 | 24.12034 | 26.48027 | 0.32897 | 9.01209 |
November | 417.00000 | 23.30679 | 28.28453 | 0.10093 | 6.64138 |
December | 422.00000 | 22.36002 | 16.79921 | -0.2222 | 7.39848 |
Annual Sum or Average | 5034.00000 | 23.90356 | 29.27461 | -0.0216 | 7.54224 |
Minimum of Months | 385.00000 | 22.36002 | 16.79921 | -0.3489 | 6.24742 |
Maximum of Months | 433.00000 | 24.74901 | 45.77664 | 0.39709 | 9.27436 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.14190 | 20.83321 | 0.32792 | 8.90053 |
February | 454.00000 | 23.52180 | 35.05959 | 0.21485 | 7.47170 |
March | 514.00000 | 23.79211 | 27.17012 | 0.22931 | 7.29783 |
April | 485.00000 | 24.36348 | 18.69153 | 0.35566 | 8.33250 |
May | 508.00000 | 24.38677 | 18.13986 | -0.4965 | 10.92329 |
June | 496.00000 | 24.42431 | 25.52381 | -0.3900 | 9.14830 |
July | 497.00000 | 24.55567 | 43.86067 | -0.2264 | 7.26772 |
August | 514.00000 | 24.45210 | 46.71827 | -0.2204 | 7.04551 |
September | 485.00000 | 24.59874 | 45.24084 | -0.1677 | 7.18634 |
October | 502.00000 | 24.44125 | 26.26512 | 0.45374 | 10.87821 |
November | 489.00000 | 24.14089 | 26.66697 | 0.35945 | 9.12815 |
December | 497.00000 | 23.80612 | 15.47813 | 0.17966 | 8.05662 |
Annual Sum or Average | 5943.00000 | 24.22270 | 29.10191 | 0.04922 | 8.47832 |
Minimum of Months | 454.00000 | 23.52180 | 15.47813 | -0.4965 | 7.04551 |
Maximum of Months | 514.00000 | 24.59874 | 46.71827 | 0.45374 | 10.92329 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.13003 | 22.71969 | 0.03301 | 6.38944 |
February | 454.00000 | 22.76966 | 36.96738 | 0.01962 | 6.01696 |
March | 514.00000 | 23.47916 | 27.69383 | 0.15511 | 6.82032 |
April | 485.00000 | 24.43163 | 18.54022 | 0.40811 | 9.40650 |
May | 508.00000 | 24.52057 | 17.81864 | -0.3674 | 9.39179 |
June | 496.00000 | 24.52687 | 25.17126 | -0.2404 | 7.82726 |
July | 497.00000 | 24.63643 | 43.54462 | -0.1296 | 7.05535 |
August | 514.00000 | 24.49097 | 46.53406 | -0.1548 | 6.91307 |
September | 485.00000 | 24.54936 | 45.46131 | -0.1857 | 7.21500 |
October | 502.00000 | 24.06963 | 27.05423 | 0.33204 | 8.86643 |
November | 489.00000 | 23.46549 | 27.95249 | 0.15742 | 7.22469 |
December | 497.00000 | 22.55731 | 16.92207 | -0.1598 | 7.15589 |
Annual Sum or Average | 5943.00000 | 23.89294 | 29.65188 | -0.0122 | 7.53151 |
Minimum of Months | 454.00000 | 22.55731 | 16.92207 | -0.3674 | 6.01696 |
Maximum of Months | 514.00000 | 24.63643 | 46.53406 | 0.40811 | 9.40650 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.66444 | 25.84639 | -0.3696 | 9.74786 |
February | 454.00000 | 21.43413 | 40.77322 | -0.3448 | 8.77955 |
March | 514.00000 | 22.45548 | 30.11746 | -0.1377 | 7.51807 |
April | 485.00000 | 23.96284 | 19.71092 | 0.22345 | 6.84833 |
May | 508.00000 | 24.32985 | 18.56249 | -0.5140 | 11.29641 |
June | 496.00000 | 24.49514 | 25.82588 | -0.3192 | 8.43766 |
July | 497.00000 | 24.59112 | 44.03499 | -0.1868 | 7.08979 |
August | 514.00000 | 24.41009 | 47.10881 | -0.2469 | 7.22296 |
September | 485.00000 | 24.45957 | 46.29750 | -0.2706 | 7.75152 |
October | 502.00000 | 23.34959 | 28.83042 | 0.10883 | 7.75269 |
November | 489.00000 | 22.16600 | 30.92885 | -0.2064 | 8.66671 |
December | 497.00000 | 20.98702 | 19.22003 | -0.5984 | 14.01327 |
Annual Sum or Average | 5943.00000 | 23.20420 | 31.37616 | -0.2387 | 8.76307 |
Minimum of Months | 454.00000 | 20.98702 | 18.56249 | -0.5984 | 6.84833 |
Maximum of Months | 514.00000 | 24.59112 | 47.10881 | 0.22345 | 14.01327 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.52716 | 24.07412 | -0.1405 | 7.41541 |
February | 454.00000 | 22.19922 | 38.67145 | -0.1413 | 7.19668 |
March | 514.00000 | 23.15189 | 28.29806 | 0.05834 | 6.93445 |
April | 485.00000 | 24.37453 | 18.66631 | 0.39924 | 9.37791 |
May | 508.00000 | 24.52714 | 18.00360 | -0.3325 | 8.91934 |
June | 496.00000 | 24.53928 | 25.54766 | -0.1907 | 7.57136 |
July | 497.00000 | 24.66230 | 43.66385 | -0.0639 | 6.90183 |
August | 514.00000 | 24.50118 | 46.55071 | -0.1138 | 6.78867 |
September | 485.00000 | 24.53766 | 45.72225 | -0.1628 | 7.24612 |
October | 502.00000 | 23.89997 | 27.32623 | 0.28717 | 8.97626 |
November | 489.00000 | 22.83507 | 29.39813 | -0.0204 | 7.14517 |
December | 497.00000 | 21.61160 | 18.04451 | -0.4219 | 10.52159 |
Annual Sum or Average | 5943.00000 | 23.62388 | 30.27473 | -0.0705 | 7.91723 |
Minimum of Months | 454.00000 | 21.61160 | 18.00360 | -0.4219 | 6.78867 |
Maximum of Months | 514.00000 | 24.66230 | 46.55071 | 0.39924 | 10.52159 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.67773 | 21.77978 | 0.19664 | 8.63196 |
February | 454.00000 | 22.85365 | 36.95808 | 0.03737 | 7.73563 |
March | 514.00000 | 23.36128 | 28.02305 | 0.11424 | 7.44181 |
April | 485.00000 | 24.27084 | 19.01320 | 0.34227 | 8.51998 |
May | 508.00000 | 24.36061 | 18.46014 | -0.4858 | 11.05048 |
June | 496.00000 | 24.45568 | 25.92105 | -0.3443 | 8.76240 |
July | 497.00000 | 24.58308 | 44.03255 | -0.1849 | 7.25476 |
August | 514.00000 | 24.46579 | 46.82568 | -0.1893 | 7.01084 |
September | 485.00000 | 24.60180 | 45.63356 | -0.1455 | 7.25403 |
October | 502.00000 | 24.22384 | 26.71250 | 0.39846 | 10.64852 |
November | 489.00000 | 23.70983 | 27.55032 | 0.23863 | 8.60639 |
December | 497.00000 | 23.18334 | 16.23956 | -0.0038 | 8.69368 |
Annual Sum or Average | 5943.00000 | 23.98582 | 29.71731 | -0.0037 | 8.47459 |
Minimum of Months | 454.00000 | 22.85365 | 16.23956 | -0.4858 | 7.01084 |
Maximum of Months | 514.00000 | 24.60180 | 46.82568 | 0.39846 | 11.05048 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.49667 | 23.77021 | -0.1282 | 7.77840 |
February | 454.00000 | 22.04692 | 38.72683 | -0.1638 | 7.24589 |
March | 514.00000 | 22.96328 | 28.46488 | 0.02645 | 7.29825 |
April | 485.00000 | 24.31836 | 18.86363 | 0.39069 | 9.49996 |
May | 508.00000 | 24.47810 | 18.15783 | -0.3602 | 9.58162 |
June | 496.00000 | 24.53242 | 25.63399 | -0.2022 | 7.74213 |
July | 497.00000 | 24.63632 | 43.80935 | -0.0973 | 7.17390 |
August | 514.00000 | 24.48663 | 46.70314 | -0.1302 | 6.99113 |
September | 485.00000 | 24.53453 | 45.88336 | -0.1703 | 7.30942 |
October | 502.00000 | 23.76397 | 27.52218 | 0.25984 | 8.97307 |
November | 489.00000 | 22.89054 | 28.88344 | 0.01118 | 7.69000 |
December | 497.00000 | 21.82875 | 17.55350 | -0.3578 | 10.02047 |
Annual Sum or Average | 5943.00000 | 23.59156 | 30.27585 | -0.0772 | 8.11202 |
Minimum of Months | 454.00000 | 21.82875 | 17.55350 | -0.3602 | 6.99113 |
Maximum of Months | 514.00000 | 24.63632 | 46.70314 | 0.39069 | 10.02047 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.540484E+11 | 87414.06 | 26-JAN-15:10 | 304.38 | 0.337295E+12 | 0.00 | 0.391344E+12 | 2.36 | 7.31 | 30-JAN-17:00 | 0.00 | 0.00 |
February | 0.178696E+11 | 74579.20 | 22-FEB-16:00 | 183.07 | 0.933165E+11 | 0.00 | 0.111186E+12 | 1.32 | 7.14 | 22-FEB-16:00 | 0.00 | 0.00 |
March | 0.547854E+11 | 105513.66 | 20-MAR-16:00 | 347.34 | 0.335092E+12 | 0.00 | 0.389878E+12 | 2.59 | 7.36 | 22-MAR-15:50 | 0.00 | 0.00 |
April | 0.112131E+12 | 95879.18 | 14-APR-15:30 | 592.09 | 0.737505E+12 | 0.00 | 0.849637E+12 | 4.88 | 7.35 | 17-APR-09:10 | 0.00 | 0.00 |
May | 0.134122E+12 | 98158.54 | 18-MAY-15:20 | 583.62 | 0.893699E+12 | 0.00 | 0.102782E+13 | 4.92 | 7.45 | 08-MAY-05:02 | 0.00 | 0.00 |
June | 0.171137E+12 | 122765.71 | 19-JUN-14:10 | 690.14 | 0.115045E+13 | 0.00 | 0.132159E+13 | 6.11 | 7.55 | 28-JUN-05:02 | 0.00 | 0.00 |
July | 0.172124E+12 | 165133.94 | 18-JUL-05:03 | 703.64 | 0.114087E+13 | 0.00 | 0.131300E+13 | 5.89 | 7.54 | 28-JUL-05:03 | 0.00 | 0.00 |
August | 0.171652E+12 | 157035.33 | 01-AUG-05:02 | 694.96 | 0.114728E+13 | 0.00 | 0.131894E+13 | 5.86 | 7.66 | 19-AUG-05:03 | 0.00 | 0.00 |
September | 0.142633E+12 | 159667.73 | 12-SEP-05:04 | 574.69 | 0.955573E+12 | 0.00 | 0.109821E+13 | 5.05 | 7.69 | 13-SEP-05:02 | 0.00 | 0.00 |
October | 0.952984E+11 | 136482.05 | 03-OCT-05:03 | 467.51 | 0.620701E+12 | 0.00 | 0.716000E+12 | 3.77 | 7.63 | 03-OCT-05:03 | 0.00 | 0.00 |
November | 0.540649E+11 | 89542.93 | 01-NOV-15:30 | 333.99 | 0.336460E+12 | 0.00 | 0.390525E+12 | 2.60 | 7.56 | 13-NOV-06:04 | 0.00 | 0.00 |
December | 0.316089E+11 | 87534.78 | 22-DEC-16:50 | 232.57 | 0.181981E+12 | 0.00 | 0.213589E+12 | 1.64 | 7.31 | 22-DEC-16:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.121147E+13 | 5707.98 | 0.793023E+13 | 0.00 | 0.914171E+13 | 3.93 | 0.00 | 0.00 | ||||
Minimum of Months | 0.178696E+11 | 74579.20 | 183.07 | 0.933165E+11 | 0.00 | 0.111186E+12 | 1.32 | 7.14 | 0.00 | 0.00 | ||
Maximum of Months | 0.172124E+12 | 165133.94 | 703.64 | 0.115045E+13 | 0.00 | 0.132159E+13 | 6.11 | 7.69 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.871887E+09 | 92993.05 | 20-MAR-14:10 | 2.83 | 0.624076E+10 | 0.00 | 0.711264E+10 | 0.03 | 7.30 | 20-MAR-14:10 | 0.00 | 0.00 |
April | 0.257217E+11 | 95879.18 | 14-APR-15:30 | 82.50 | 0.183800E+12 | 0.00 | 0.209521E+12 | 0.82 | 7.31 | 14-APR-15:10 | 0.00 | 0.00 |
May | 0.427604E+11 | 98158.54 | 18-MAY-15:20 | 136.03 | 0.306139E+12 | 0.00 | 0.348899E+12 | 1.31 | 7.45 | 08-MAY-05:02 | 0.00 | 0.00 |
June | 0.805055E+11 | 122765.71 | 19-JUN-14:10 | 242.98 | 0.578369E+12 | 0.00 | 0.658875E+12 | 2.42 | 7.55 | 28-JUN-05:02 | 0.00 | 0.00 |
July | 0.755884E+11 | 165133.94 | 18-JUL-05:03 | 219.13 | 0.531822E+12 | 0.00 | 0.607410E+12 | 2.07 | 7.54 | 28-JUL-05:03 | 0.00 | 0.00 |
August | 0.822021E+11 | 157035.33 | 01-AUG-05:02 | 238.08 | 0.578290E+12 | 0.00 | 0.660492E+12 | 2.25 | 7.66 | 19-AUG-05:03 | 0.00 | 0.00 |
September | 0.577000E+11 | 159667.73 | 12-SEP-05:04 | 169.18 | 0.407923E+12 | 0.00 | 0.465623E+12 | 1.66 | 7.69 | 13-SEP-05:02 | 0.00 | 0.00 |
October | 0.236134E+11 | 136482.05 | 03-OCT-05:03 | 71.90 | 0.168391E+12 | 0.00 | 0.192004E+12 | 0.69 | 7.63 | 03-OCT-05:03 | 0.00 | 0.00 |
November | 0.150386E+10 | 89542.93 | 01-NOV-15:30 | 4.87 | 0.107464E+11 | 0.00 | 0.122503E+11 | 0.05 | 7.56 | 13-NOV-06:04 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.390467E+12 | 1167.51 | 0.277172E+13 | 0.00 | 0.316219E+13 | 0.95 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.822021E+11 | 165133.94 | 242.98 | 0.578369E+12 | 0.00 | 0.660492E+12 | 2.42 | 7.69 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.144110E+11 | 744.00 | 12476.23 | 02-JAN-12:10 | 39198.30 | 31-JAN-17:10 | 22.03 | 19.53 | 2.80 |
February | 0.103759E+11 | 672.00 | 12476.23 | 06-FEB-14:00 | 61605.80 | 22-FEB-17:00 | 23.50 | 18.46 | 2.80 |
March | 0.213916E+11 | 744.00 | 12476.23 | 01-MAR-10:20 | 107690.98 | 31-MAR-24:00 | 28.11 | 19.91 | 2.80 |
April | 0.307161E+11 | 720.00 | 12476.23 | 01-APR-07:15 | 122228.50 | 25-APR-18:40 | 36.73 | 25.15 | 2.80 |
May | 0.321333E+11 | 744.00 | 12476.23 | 01-MAY-00:10 | 63479.82 | 31-MAY-23:23 | 30.46 | 26.87 | 2.80 |
June | 0.323384E+11 | 720.00 | 12476.23 | 01-JUN-00:03 | 93406.58 | 30-JUN-23:13 | 38.76 | 31.99 | 2.80 |
July | 0.334163E+11 | 744.00 | 12476.23 | 01-JUL-00:03 | 120380.56 | 31-JUL-23:23 | 41.10 | 31.55 | 2.80 |
August | 0.334163E+11 | 744.00 | 12476.23 | 01-AUG-00:03 | 133774.91 | 05-AUG-16:03 | 43.37 | 31.26 | 2.80 |
September | 0.322880E+11 | 720.00 | 12476.23 | 01-SEP-00:05 | 62176.11 | 30-SEP-23:33 | 31.81 | 28.18 | 2.80 |
October | 0.268113E+11 | 744.00 | 12476.23 | 01-OCT-00:03 | 81391.60 | 31-OCT-24:00 | 28.94 | 22.98 | 2.80 |
November | 0.209289E+11 | 720.00 | 12476.23 | 01-NOV-00:30 | 97920.30 | 09-NOV-16:50 | 27.95 | 19.73 | 2.80 |
December | 0.175973E+11 | 744.00 | 12476.23 | 01-DEC-10:10 | 120702.81 | 25-DEC-17:23 | 29.55 | 19.06 | 2.80 |
Annual Sum or Average | 0.305825E+12 | 8760.00 | 31.91 | 24.59 | 2.80 | ||||
Minimum of Months | 0.103759E+11 | 672.00 | 12476.23 | 39198.30 | 22.03 | 18.46 | 2.80 | ||
Maximum of Months | 0.334163E+11 | 744.00 | 12476.23 | 133774.91 | 43.37 | 31.99 | 2.80 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.362217E+09 | 243.80 | 1679.55 | 26-JAN-14:10 | 1061170.50 | 31-JAN-16:30 | 21.88 | 21.20 | 22.12 |
February | 0.106996E+09 | 98.00 | 1057.25 | 18-FEB-14:00 | 622132.90 | 22-FEB-16:00 | 21.27 | 21.06 | 13.01 |
March | 0.600534E+09 | 251.51 | 3248.66 | 17-MAR-11:00 | 1083802.00 | 17-MAR-14:40 | 21.76 | 21.09 | 24.07 |
April | 0.198217E+10 | 432.65 | 17182.88 | 11-APR-14:20 | 1131992.55 | 24-APR-16:00 | 22.69 | 21.07 | 41.74 |
May | 0.254448E+10 | 518.83 | 17182.88 | 09-MAY-13:40 | 1175598.92 | 31-MAY-16:00 | 23.12 | 21.20 | 44.44 |
June | 0.132175E+11 | 654.98 | 17182.88 | 01-JUN-09:20 | 1163890.48 | 05-JUN-13:10 | 23.75 | 21.34 | 55.64 |
July | 0.288453E+11 | 687.54 | 17182.88 | 03-JUL-11:50 | 1105842.47 | 06-JUL-12:50 | 24.51 | 22.35 | 54.71 |
August | 0.285381E+11 | 679.65 | 17182.88 | 01-AUG-00:57 | 1088674.95 | 24-AUG-12:10 | 24.42 | 22.27 | 54.14 |
September | 0.233693E+11 | 558.42 | 17182.88 | 01-SEP-03:02 | 1107613.89 | 28-SEP-16:00 | 23.99 | 22.06 | 46.39 |
October | 0.607701E+10 | 392.77 | 17182.88 | 01-OCT-10:00 | 1100040.99 | 06-OCT-15:40 | 22.53 | 21.29 | 34.36 |
November | 0.129617E+10 | 250.10 | 17182.88 | 01-NOV-10:30 | 1084469.51 | 09-NOV-15:30 | 21.81 | 21.09 | 24.52 |
December | 0.144668E+09 | 148.85 | 1396.35 | 21-DEC-15:00 | 920281.22 | 22-DEC-16:00 | 21.39 | 21.03 | 15.05 |
Annual Sum or Average | 0.107084E+12 | 4917.11 | 22.77 | 21.42 | 35.97 | ||||
Minimum of Months | 0.106996E+09 | 98.00 | 1057.25 | 622132.90 | 21.27 | 21.03 | 13.01 | ||
Maximum of Months | 0.288453E+11 | 687.54 | 17182.88 | 1175598.92 | 24.51 | 22.35 | 55.64 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.88 | 21.88 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.27 | 21.27 | 0.00 |
March | 19471554.77 | 2.50 | 3103.42 | 20-MAR-14:30 | 1083802.00 | 17-MAR-14:40 | 21.76 | 21.75 | 0.20 |
April | 0.678277E+09 | 35.50 | 17182.88 | 11-APR-14:20 | 1131992.55 | 24-APR-16:00 | 22.69 | 22.48 | 2.87 |
May | 0.939364E+09 | 64.50 | 17182.88 | 09-MAY-13:40 | 1175598.92 | 31-MAY-16:00 | 23.12 | 22.75 | 5.05 |
June | 0.832855E+10 | 177.23 | 17182.88 | 01-JUN-09:20 | 1163890.48 | 05-JUN-13:10 | 23.75 | 22.82 | 14.32 |
July | 0.122535E+11 | 209.19 | 17182.88 | 03-JUL-11:50 | 1105842.47 | 06-JUL-12:50 | 24.51 | 23.56 | 16.35 |
August | 0.140799E+11 | 230.86 | 17182.88 | 01-AUG-03:57 | 1088674.95 | 24-AUG-12:10 | 24.42 | 23.40 | 18.07 |
September | 0.946449E+10 | 156.09 | 17182.88 | 01-SEP-05:03 | 1107613.89 | 28-SEP-16:00 | 23.99 | 23.25 | 12.63 |
October | 0.290091E+10 | 51.16 | 17182.88 | 02-OCT-05:04 | 1100040.99 | 06-OCT-15:40 | 22.53 | 22.29 | 4.01 |
November | 51548635.20 | 0.83 | 17182.88 | 01-NOV-13:20 | 1036001.35 | 02-NOV-16:00 | 21.81 | 21.81 | 0.07 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.39 | 21.39 | 0.00 |
Annual Sum or Average | 0.487161E+11 | 927.86 | 22.77 | 22.39 | 6.17 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.27 | 21.27 | 0.00 | ||
Maximum of Months | 0.140799E+11 | 230.86 | 17182.88 | 1175598.92 | 24.51 | 23.56 | 18.07 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.445203E+10 | 0.00 | 94.32 | 729786.03 | 02-JAN-06:01 | 0.00 | 25.54 | 32.28 | 0.01 | 0.00 | 0.00 | 0.43 | 02-JAN-06:01 |
February | 0.490321E+10 | 0.00 | 114.47 | 418845.05 | 13-FEB-06:03 | 0.00 | 24.04 | 33.39 | 0.01 | 0.00 | 0.00 | 0.25 | 13-FEB-06:03 |
March | 0.435401E+10 | 0.00 | 59.63 | 403231.37 | 27-MAR-05:03 | 0.00 | 25.28 | 29.56 | 0.01 | 0.00 | 0.00 | 0.24 | 27-MAR-05:03 |
April | 590197.04 | 0.00 | 1.50 | 161.63 | 01-APR-06:10 | 0.00 | 27.24 | 27.35 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-06:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 27.24 | 27.24 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 27.24 | 27.24 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 27.24 | 27.24 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 27.24 | 27.24 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 27.24 | 27.24 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.479738E+09 | 0.00 | 23.07 | 64902.55 | 25-OCT-06:30 | 0.00 | 26.47 | 28.13 | 0.00 | 0.00 | 0.00 | 0.04 | 25-OCT-06:30 |
November | 0.224641E+10 | 0.00 | 70.27 | 474806.41 | 24-NOV-06:03 | 0.00 | 25.27 | 30.50 | 0.00 | 0.00 | 0.00 | 0.28 | 24-NOV-06:03 |
December | 0.222212E+11 | 0.00 | 213.61 | 925675.53 | 07-DEC-06:01 | 0.00 | 25.83 | 40.87 | 0.04 | 0.00 | 0.00 | 0.54 | 07-DEC-06:01 |
Annual Sum or Average | 0.386571E+11 | 0.00 | 576.86 | 0.00 | 26.34 | 29.85 | 0.01 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | 27.24 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.222212E+11 | 0.00 | 213.61 | 925675.53 | 0.00 | 27.24 | 40.87 | 0.04 | 0.00 | 0.00 | 0.54 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 22.03 | 22.03 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 23.50 | 23.50 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 28.11 | 28.11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 36.73 | 36.73 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 30.46 | 30.46 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 38.76 | 38.76 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 41.10 | 41.10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 43.37 | 43.37 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 31.81 | 31.81 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 28.94 | 28.94 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 27.95 | 27.95 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 29.55 | 29.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 31.91 | 31.91 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 | 22.03 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.37 | 43.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.357209E+11 | 0.00 | 285.98 | 0.357077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88211.47 | 31-JAN-16:40 | 88211.47 | 31-JAN-16:40 | 0.00 | 0.00 | 0.00 |
February | 0.906358E+10 | 0.00 | 168.25 | 0.906358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56854.57 | 21-FEB-15:00 | 56854.57 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.395181E+11 | 0.00 | 332.31 | 0.395181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97853.95 | 20-MAR-14:40 | 97853.95 | 20-MAR-14:40 | 0.00 | 0.00 | 0.00 |
April | 0.103555E+12 | 0.00 | 565.34 | 0.103555E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 122665.92 | 24-APR-16:00 | 122665.92 | 24-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.116999E+12 | 0.00 | 549.39 | 0.116999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 116871.54 | 15-MAY-15:50 | 116871.54 | 15-MAY-15:50 | 0.00 | 0.00 | 0.00 |
June | 0.160237E+12 | 0.00 | 630.68 | 0.160218E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 156331.95 | 30-JUN-05:02 | 156331.95 | 30-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.169526E+12 | 0.00 | 645.43 | 0.158495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 267120.40 | 18-JUL-05:03 | 157414.12 | 21-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.178193E+12 | 0.00 | 652.22 | 0.167674E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 251415.43 | 01-AUG-05:02 | 165923.97 | 28-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.132989E+12 | 0.00 | 535.08 | 0.123728E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 240739.06 | 05-SEP-03:02 | 154859.64 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.803420E+11 | 0.00 | 443.84 | 0.788504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 200951.96 | 03-OCT-05:03 | 160487.02 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.422354E+11 | 0.00 | 314.20 | 0.397989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142684.11 | 13-NOV-06:02 | 98372.12 | 01-NOV-15:20 | 0.00 | 0.00 | 0.00 |
December | 0.206936E+11 | 0.00 | 215.61 | 0.206936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86375.87 | 22-DEC-16:20 | 86375.87 | 22-DEC-16:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108907E+13 | 0.00 | 5338.32 | 0.105430E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.906358E+10 | 0.00 | 168.25 | 0.906358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56854.57 | 56854.57 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.178193E+12 | 0.00 | 652.22 | 0.167674E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 267120.40 | 165923.97 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.292150E+12 | 0.00 | 290.57 | 0.292080E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 751867.45 | 31-JAN-16:30 | 751867.45 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 |
February | 0.662999E+11 | 0.00 | 173.17 | 0.662999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 407219.50 | 22-FEB-16:00 | 407219.50 | 22-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.285485E+12 | 0.00 | 317.23 | 0.285485E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 805952.85 | 16-MAR-15:50 | 805952.85 | 16-MAR-15:50 | 0.00 | 0.00 | 0.00 |
April | 0.789775E+12 | 0.00 | 443.97 | 0.789775E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1078232.24 | 14-APR-15:20 | 1078232.24 | 14-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.103728E+13 | 0.00 | 506.83 | 0.103728E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1096376.96 | 18-MAY-15:20 | 1096376.96 | 18-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.139844E+13 | 0.00 | 584.27 | 0.139829E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1339061.75 | 29-JUN-05:02 | 1339061.75 | 29-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.134847E+13 | 0.00 | 559.32 | 0.127246E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2444120.97 | 15-JUL-05:03 | 1424895.42 | 19-JUL-05:03 | 0.00 | 0.00 | 0.00 |
August | 0.136716E+13 | 0.00 | 554.64 | 0.129777E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2384952.06 | 01-AUG-05:02 | 1389035.74 | 16-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.113021E+13 | 0.00 | 478.34 | 0.105522E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2146418.24 | 08-SEP-05:02 | 1412027.45 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.643972E+12 | 0.00 | 396.41 | 0.631554E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1724860.08 | 03-OCT-03:02 | 1431874.99 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.295257E+12 | 0.00 | 296.88 | 0.282908E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1011775.92 | 13-NOV-06:02 | 819858.78 | 01-NOV-15:20 | 0.00 | 0.00 | 0.00 |
December | 0.141608E+12 | 0.00 | 207.72 | 0.141608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 629198.37 | 22-DEC-16:00 | 629198.37 | 22-DEC-16:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.879610E+13 | 0.00 | 4809.35 | 0.855073E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.662999E+11 | 0.00 | 173.17 | 0.662999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 407219.50 | 407219.50 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.139844E+13 | 0.00 | 584.27 | 0.139829E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2444120.97 | 1431874.99 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.253626E+11 | 0.00 | 275.37 | 0.253535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77255.44 | 31-JAN-16:30 | 77255.44 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 |
February | 0.523036E+10 | 0.00 | 153.14 | 0.523036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38106.33 | 22-FEB-16:00 | 38106.33 | 22-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.271201E+11 | 0.00 | 299.36 | 0.271201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92444.09 | 16-MAR-15:40 | 92444.09 | 16-MAR-15:40 | 0.00 | 0.00 | 0.00 |
April | 0.873096E+11 | 0.00 | 442.77 | 0.873096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131760.29 | 14-APR-15:20 | 131760.29 | 14-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.116807E+12 | 0.00 | 508.79 | 0.116807E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 133655.08 | 18-MAY-15:30 | 133655.08 | 18-MAY-15:30 | 0.00 | 0.00 | 0.00 |
June | 0.162904E+12 | 0.00 | 596.61 | 0.162898E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 159403.64 | 28-JUN-15:00 | 159403.64 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.156683E+12 | 0.00 | 576.88 | 0.148477E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 255844.53 | 15-JUL-05:03 | 155576.19 | 10-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.156187E+12 | 0.00 | 567.22 | 0.148488E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 257409.69 | 01-AUG-05:02 | 159501.44 | 28-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.124985E+12 | 0.00 | 489.31 | 0.117269E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 275524.15 | 02-SEP-03:02 | 151789.54 | 02-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.659681E+11 | 0.00 | 385.57 | 0.647972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168266.81 | 03-OCT-03:02 | 155731.29 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.257992E+11 | 0.00 | 278.12 | 0.249986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93871.10 | 01-NOV-15:20 | 93871.10 | 01-NOV-15:20 | 0.00 | 0.00 | 0.00 |
December | 0.114095E+11 | 0.00 | 184.23 | 0.114095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62235.82 | 22-DEC-16:00 | 62235.82 | 22-DEC-16:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.965766E+12 | 0.00 | 4757.39 | 0.940158E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.523036E+10 | 0.00 | 153.14 | 0.523036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38106.33 | 38106.33 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.162904E+12 | 0.00 | 596.61 | 0.162898E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 275524.15 | 159501.44 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.231573E+11 | 0.00 | 221.51 | 0.231544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71974.54 | 16-JAN-15:20 | 71974.54 | 16-JAN-15:20 | 0.00 | 0.00 | 0.00 |
February | 0.393719E+10 | 0.00 | 90.63 | 0.392461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39232.96 | 21-FEB-15:00 | 39232.96 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.222638E+11 | 0.00 | 235.34 | 0.222584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59632.78 | 20-MAR-13:10 | 59632.78 | 20-MAR-13:10 | 0.00 | 0.00 | 0.00 |
April | 0.522457E+11 | 0.00 | 338.26 | 0.522457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78684.72 | 25-APR-03:02 | 78684.72 | 25-APR-03:02 | 0.00 | 0.00 | 0.00 |
May | 0.648167E+11 | 0.00 | 395.60 | 0.648167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99713.80 | 29-MAY-17:40 | 99713.80 | 29-MAY-17:40 | 0.00 | 0.00 | 0.00 |
June | 0.797126E+11 | 0.00 | 422.05 | 0.797126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94858.42 | 30-JUN-04:03 | 94858.42 | 30-JUN-04:03 | 0.00 | 0.00 | 0.00 |
July | 0.871693E+11 | 0.00 | 435.73 | 0.835126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153813.29 | 14-JUL-03:02 | 96960.53 | 04-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.957187E+11 | 0.00 | 476.94 | 0.915961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145034.14 | 01-AUG-03:02 | 99550.97 | 27-AUG-13:40 | 0.00 | 0.00 | 0.00 |
September | 0.834084E+11 | 0.00 | 440.69 | 0.787538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145969.02 | 03-SEP-22:53 | 94083.11 | 18-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.521004E+11 | 0.00 | 344.13 | 0.514751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133315.29 | 03-OCT-03:02 | 99563.96 | 15-OCT-14:38 | 0.00 | 0.00 | 0.00 |
November | 0.281018E+11 | 0.00 | 231.82 | 0.260059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105006.78 | 12-NOV-14:20 | 94862.69 | 19-NOV-15:20 | 0.00 | 0.00 | 0.00 |
December | 0.122277E+11 | 0.00 | 156.88 | 0.122274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59720.13 | 26-DEC-13:10 | 59720.13 | 26-DEC-13:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.604860E+12 | 0.00 | 3789.57 | 0.589683E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.393719E+10 | 0.00 | 90.63 | 0.392461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39232.96 | 39232.96 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.957187E+11 | 0.00 | 476.94 | 0.915961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153813.29 | 99713.80 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.539377E+10 | 0.135739E+10 | 744.00 | 0.539159E+10 | 2184798.24 | 0.00 | 0.39 | 29-JAN-17:05 | 0.19 | 21-JAN-08:00 | 2628.27 | 29-JAN-17:17 | 2628.27 | 29-JAN-17:17 | 88.62 | 09-JAN-11:30 | 868.03 | 31-JAN-17:00 | 0.00 |
February | 0.933101E+10 | 0.206166E+10 | 672.00 | 0.929022E+10 | 40787290.84 | 0.00 | 0.54 | 25-FEB-18:05 | 0.42 | 08-FEB-07:50 | 4438.22 | 20-FEB-17:05 | 4428.63 | 20-FEB-17:10 | 169.91 | 16-FEB-10:30 | 1003.75 | 22-FEB-17:00 | 0.00 |
March | 0.156862E+11 | 0.353059E+10 | 744.00 | 0.156750E+11 | 11245104.57 | 0.00 | 0.95 | 31-MAR-24:00 | 0.63 | 07-MAR-08:00 | 7735.37 | 31-MAR-24:00 | 7735.37 | 31-MAR-24:00 | 212.10 | 06-MAR-11:10 | 1849.55 | 16-MAR-16:00 | 0.00 |
April | 0.200632E+11 | 0.532268E+10 | 720.00 | 0.200632E+11 | 0.00 | 0.00 | 1.00 | 01-APR-09:50 | 0.37 | 30-APR-24:00 | 8167.94 | 16-APR-20:25 | 8167.94 | 16-APR-20:25 | 0.00 | 02-APR-01:07 | 2654.63 | 14-APR-16:10 | 0.00 |
May | 0.616173E+10 | 0.201601E+10 | 744.00 | 0.616173E+10 | 0.00 | 0.00 | 0.58 | 31-MAY-23:13 | 0.26 | 13-MAY-06:10 | 4037.81 | 31-MAY-23:57 | 4037.81 | 31-MAY-23:57 | 0.00 | 10-MAY-09:50 | 1273.88 | 31-MAY-23:10 | 0.00 |
June | 0.110740E+11 | 0.381380E+10 | 720.00 | 0.110722E+11 | 1759223.50 | 0.00 | 0.77 | 30-JUN-23:10 | 0.49 | 21-JUN-06:10 | 5979.22 | 30-JUN-23:37 | 5979.22 | 30-JUN-23:37 | 104.96 | 30-JUN-10:00 | 2111.40 | 16-JUN-16:00 | 0.00 |
July | 0.165840E+11 | 0.513785E+10 | 744.00 | 0.164291E+11 | 0.154891E+09 | 0.00 | 0.99 | 02-JUL-18:11 | 0.68 | 01-JUL-06:10 | 7896.12 | 31-JUL-23:53 | 7881.02 | 31-JUL-23:57 | 439.31 | 13-JUL-18:00 | 2720.58 | 02-JUL-18:05 | 0.00 |
August | 0.213172E+11 | 0.624578E+10 | 744.00 | 0.211478E+11 | 0.169340E+09 | 0.00 | 1.00 | 01-AUG-11:50 | 0.34 | 31-AUG-24:00 | 8727.32 | 28-AUG-16:00 | 8357.21 | 06-AUG-18:45 | 591.06 | 28-AUG-16:10 | 2948.71 | 25-AUG-16:10 | 0.00 |
September | 0.616631E+10 | 0.190510E+10 | 720.00 | 0.603672E+10 | 0.129591E+09 | 0.00 | 0.54 | 30-SEP-23:43 | 0.25 | 22-SEP-06:10 | 4058.95 | 30-SEP-24:00 | 4058.95 | 30-SEP-24:00 | 294.86 | 11-SEP-15:20 | 1156.24 | 30-SEP-23:33 | 0.00 |
October | 0.110254E+11 | 0.289232E+10 | 744.00 | 0.109965E+11 | 28876063.65 | 0.00 | 0.72 | 31-OCT-24:00 | 0.44 | 25-OCT-06:55 | 5897.51 | 31-OCT-24:00 | 5897.51 | 31-OCT-24:00 | 304.89 | 03-OCT-09:30 | 1669.77 | 01-OCT-13:53 | 0.00 |
November | 0.153388E+11 | 0.345592E+10 | 720.00 | 0.152942E+11 | 44573170.80 | 0.00 | 0.86 | 09-NOV-16:50 | 0.64 | 18-NOV-07:50 | 6616.84 | 14-NOV-16:50 | 6609.02 | 26-NOV-16:56 | 380.10 | 13-NOV-16:00 | 1937.54 | 09-NOV-16:40 | 0.00 |
December | 0.205844E+11 | 0.453614E+10 | 744.00 | 0.205840E+11 | 401347.95 | 0.00 | 1.00 | 03-DEC-14:53 | 0.85 | 14-DEC-07:10 | 8293.61 | 26-DEC-17:10 | 8293.61 | 26-DEC-17:10 | 69.73 | 13-DEC-11:20 | 2209.68 | 25-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.158726E+12 | 0.422752E+11 | 8760.00 | 0.158142E+12 | 0.583649E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.539377E+10 | 0.135739E+10 | 672.00 | 0.539159E+10 | 0.00 | 0.00 | 0.39 | 0.19 | 2628.27 | 2628.27 | 0.00 | 868.03 | 0.00 | ||||||
Maximum of Months | 0.213172E+11 | 0.624578E+10 | 744.00 | 0.211478E+11 | 0.169340E+09 | 0.00 | 1.00 | 0.85 | 8727.32 | 8357.21 | 591.06 | 2948.71 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.418049E+11 | 0.107429E+11 | 744.00 | 0.417828E+11 | 22102669.99 | 0.00 | 0.37 | 31-JAN-17:00 | 0.05 | 02-JAN-07:10 | 23782.17 | 24-JAN-17:00 | 23782.17 | 24-JAN-17:00 | 827.01 | 09-JAN-11:40 | 8051.07 | 31-JAN-17:00 | 0.00 |
February | 0.790656E+11 | 0.176687E+11 | 672.00 | 0.786635E+11 | 0.402158E+09 | 0.00 | 0.52 | 28-FEB-17:00 | 0.33 | 13-FEB-07:10 | 40577.25 | 22-FEB-17:00 | 40257.16 | 22-FEB-17:00 | 1671.64 | 16-FEB-10:30 | 9400.38 | 22-FEB-17:00 | 0.00 |
March | 0.142892E+12 | 0.323786E+11 | 744.00 | 0.142779E+12 | 0.113373E+09 | 0.00 | 0.93 | 31-MAR-24:00 | 0.57 | 07-MAR-08:00 | 72242.55 | 31-MAR-24:00 | 72242.55 | 31-MAR-24:00 | 2104.60 | 06-MAR-11:20 | 17590.18 | 16-MAR-16:00 | 0.00 |
April | 0.190886E+12 | 0.506752E+11 | 720.00 | 0.190886E+12 | 0.00 | 0.00 | 1.00 | 01-APR-10:30 | 0.33 | 30-APR-24:00 | 77847.90 | 26-APR-17:50 | 77847.90 | 26-APR-17:50 | 0.00 | 01-APR-04:23 | 25274.89 | 14-APR-16:10 | 0.00 |
May | 0.574951E+11 | 0.188646E+11 | 744.00 | 0.574951E+11 | -0.0 | 0.00 | 0.59 | 31-MAY-23:23 | 0.25 | 13-MAY-06:30 | 39053.77 | 31-MAY-23:27 | 39053.77 | 31-MAY-23:27 | 0.00 | 09-MAY-04:17 | 12299.52 | 31-MAY-23:13 | 0.00 |
June | 0.105065E+12 | 0.362118E+11 | 720.00 | 0.105047E+12 | 18550712.85 | 0.00 | 0.77 | 30-JUN-23:10 | 0.49 | 21-JUN-06:10 | 57492.24 | 30-JUN-23:57 | 57492.24 | 30-JUN-23:57 | 1060.98 | 30-JUN-10:00 | 20178.83 | 16-JUN-16:00 | 0.00 |
July | 0.157608E+12 | 0.488374E+11 | 744.00 | 0.156064E+12 | 0.154461E+10 | 0.00 | 0.98 | 02-JUL-18:11 | 0.69 | 01-JUL-06:10 | 75464.69 | 31-JUL-23:53 | 75317.51 | 31-JUL-23:57 | 4349.67 | 13-JUL-18:00 | 25761.67 | 02-JUL-18:00 | 0.00 |
August | 0.202880E+12 | 0.594417E+11 | 744.00 | 0.201191E+12 | 0.168927E+10 | 0.00 | 1.00 | 01-AUG-10:30 | 0.31 | 31-AUG-24:00 | 83234.28 | 28-AUG-16:00 | 79243.91 | 06-AUG-18:25 | 5852.79 | 28-AUG-16:10 | 28073.92 | 25-AUG-16:10 | 0.00 |
September | 0.571254E+11 | 0.176998E+11 | 720.00 | 0.558485E+11 | 0.127683E+10 | 0.00 | 0.55 | 30-SEP-24:00 | 0.23 | 22-SEP-06:20 | 39475.08 | 30-SEP-24:00 | 39475.08 | 30-SEP-24:00 | 2908.43 | 11-SEP-15:20 | 11220.94 | 30-SEP-23:33 | 0.00 |
October | 0.100895E+12 | 0.266493E+11 | 744.00 | 0.100607E+12 | 0.288248E+09 | 0.00 | 0.71 | 31-OCT-24:00 | 0.39 | 25-OCT-06:55 | 54609.90 | 31-OCT-24:00 | 54609.90 | 31-OCT-24:00 | 3038.36 | 03-OCT-09:30 | 15821.75 | 01-OCT-13:53 | 0.00 |
November | 0.138747E+12 | 0.314821E+11 | 720.00 | 0.138301E+12 | 0.445429E+09 | 0.00 | 0.85 | 09-NOV-16:50 | 0.58 | 18-NOV-08:00 | 62299.06 | 14-NOV-16:50 | 61435.96 | 09-NOV-17:00 | 3786.76 | 13-NOV-16:00 | 18278.01 | 09-NOV-16:40 | 0.00 |
December | 0.183825E+12 | 0.409050E+11 | 744.00 | 0.183820E+12 | 4771054.93 | 0.00 | 1.00 | 22-DEC-15:40 | 0.79 | 14-DEC-07:10 | 78272.34 | 26-DEC-17:00 | 78272.34 | 26-DEC-17:00 | 767.80 | 13-DEC-11:20 | 21007.93 | 25-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.145829E+13 | 0.391557E+12 | 8760.00 | 0.145248E+13 | 0.580534E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.418049E+11 | 0.107429E+11 | 672.00 | 0.417828E+11 | -0.0 | 0.00 | 0.37 | 0.05 | 23782.17 | 23782.17 | 0.00 | 8051.07 | 0.00 | ||||||
Maximum of Months | 0.202880E+12 | 0.594417E+11 | 744.00 | 0.201191E+12 | 0.168927E+10 | 0.00 | 1.00 | 0.79 | 83234.28 | 79243.91 | 5852.79 | 28073.92 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.314806E+10 | 0.833709E+09 | 712.65 | 0.314610E+10 | 1958542.34 | 0.00 | 0.36 | 31-JAN-17:00 | 0.00 | 01-JAN-00:05 | 2393.58 | 24-JAN-17:00 | 2393.58 | 24-JAN-17:00 | 72.79 | 09-JAN-11:50 | 814.65 | 31-JAN-17:00 | 0.00 |
February | 0.678956E+10 | 0.153925E+10 | 672.00 | 0.675011E+10 | 39453326.55 | 0.00 | 0.51 | 22-FEB-17:00 | 0.21 | 13-FEB-07:10 | 4082.53 | 22-FEB-17:00 | 4050.33 | 22-FEB-17:00 | 165.72 | 16-FEB-10:40 | 946.91 | 22-FEB-17:00 | 0.00 |
March | 0.135712E+11 | 0.310484E+10 | 744.00 | 0.135600E+11 | 11139031.67 | 0.00 | 0.90 | 31-MAR-23:30 | 0.48 | 27-MAR-06:10 | 7040.79 | 31-MAR-23:30 | 7040.79 | 31-MAR-23:30 | 208.41 | 06-MAR-11:20 | 1781.53 | 16-MAR-16:00 | 0.00 |
April | 0.191097E+11 | 0.509875E+10 | 720.00 | 0.191097E+11 | 0.00 | 0.00 | 1.00 | 01-APR-12:10 | 0.33 | 30-APR-24:00 | 7868.38 | 16-APR-19:53 | 7868.38 | 16-APR-19:53 | 0.00 | 02-APR-17:06 | 2575.13 | 14-APR-16:10 | 0.00 |
May | 0.582123E+10 | 0.191969E+10 | 744.00 | 0.582123E+10 | -0.0 | 0.00 | 0.58 | 31-MAY-23:23 | 0.22 | 13-MAY-07:00 | 3917.59 | 31-MAY-23:33 | 3917.59 | 31-MAY-23:33 | 0.00 | 09-MAY-08:40 | 1234.08 | 31-MAY-23:10 | 0.00 |
June | 0.107059E+11 | 0.369520E+10 | 720.00 | 0.107041E+11 | 1817721.89 | 0.00 | 0.77 | 30-JUN-23:10 | 0.47 | 21-JUN-06:10 | 5815.38 | 30-JUN-23:30 | 5815.38 | 30-JUN-23:30 | 105.71 | 30-JUN-10:00 | 2073.48 | 16-JUN-16:00 | 0.00 |
July | 0.159714E+11 | 0.495644E+10 | 744.00 | 0.158170E+11 | 0.154432E+09 | 0.00 | 1.00 | 02-JUL-17:52 | 0.67 | 29-JUL-06:05 | 7621.87 | 31-JUL-23:53 | 7607.01 | 31-JUL-23:57 | 435.44 | 13-JUL-18:00 | 2694.47 | 02-JUL-18:00 | 0.00 |
August | 0.204619E+11 | 0.601015E+10 | 744.00 | 0.202927E+11 | 0.169204E+09 | 0.00 | 1.00 | 01-AUG-12:10 | 0.31 | 31-AUG-24:00 | 8379.16 | 28-AUG-15:50 | 8089.91 | 06-AUG-18:37 | 576.72 | 28-AUG-16:00 | 2860.47 | 25-AUG-16:10 | 0.00 |
September | 0.582160E+10 | 0.180823E+10 | 720.00 | 0.569358E+10 | 0.128018E+09 | 0.00 | 0.55 | 30-SEP-24:00 | 0.21 | 22-SEP-07:00 | 3993.91 | 30-SEP-24:00 | 3993.91 | 30-SEP-24:00 | 293.26 | 11-SEP-15:20 | 1135.90 | 30-SEP-23:33 | 0.00 |
October | 0.971649E+10 | 0.259285E+10 | 744.00 | 0.968778E+10 | 28708379.23 | 0.00 | 0.69 | 15-OCT-17:12 | 0.32 | 28-OCT-07:00 | 5268.83 | 31-OCT-24:00 | 5268.83 | 31-OCT-24:00 | 304.46 | 03-OCT-09:40 | 1642.17 | 01-OCT-13:53 | 0.00 |
November | 0.129790E+11 | 0.297717E+10 | 720.00 | 0.129347E+11 | 44269923.06 | 0.00 | 0.84 | 09-NOV-16:50 | 0.47 | 24-NOV-07:05 | 6235.06 | 14-NOV-16:50 | 6176.51 | 09-NOV-17:00 | 380.24 | 13-NOV-16:00 | 1840.40 | 09-NOV-16:40 | 0.00 |
December | 0.168988E+11 | 0.381369E+10 | 744.00 | 0.168984E+11 | 443148.93 | 0.00 | 1.00 | 22-DEC-16:30 | 0.66 | 18-DEC-07:10 | 7804.69 | 22-DEC-17:10 | 7804.69 | 22-DEC-17:10 | 71.07 | 13-DEC-11:20 | 2103.65 | 22-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.140995E+12 | 0.383500E+11 | 8728.65 | 0.140415E+12 | 0.579444E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.314806E+10 | 0.833709E+09 | 672.00 | 0.314610E+10 | -0.0 | 0.00 | 0.36 | 0.00 | 2393.58 | 2393.58 | 0.00 | 814.65 | 0.00 | ||||||
Maximum of Months | 0.204619E+11 | 0.601015E+10 | 744.00 | 0.202927E+11 | 0.169204E+09 | 0.00 | 1.00 | 0.67 | 8379.16 | 8089.91 | 576.72 | 2860.47 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.75 | 0.00 | 75.75 | 53.08 | 336.92 | 0.00 | 0.00 | 0.00 |
February | 86.32 | 0.00 | 86.32 | 36.33 | 338.93 | 0.00 | 0.00 | 0.00 |
March | 114.72 | 0.00 | 114.72 | 101.24 | 292.71 | 0.00 | 0.00 | 0.00 |
April | 139.76 | 1.45 | 138.31 | 227.35 | 151.38 | 0.00 | 0.00 | 0.00 |
May | 163.61 | 13.10 | 150.51 | 315.47 | 99.85 | 0.00 | 0.00 | 0.00 |
June | 190.12 | 34.54 | 155.58 | 488.11 | 39.82 | 0.00 | 0.00 | 0.00 |
July | 162.14 | 16.89 | 145.25 | 415.69 | 30.96 | 0.00 | 0.00 | 0.00 |
August | 130.88 | 3.25 | 127.62 | 341.48 | 40.67 | 0.00 | 0.00 | 0.00 |
September | 123.48 | 0.03 | 123.45 | 287.37 | 62.02 | 0.00 | 0.00 | 0.00 |
October | 95.53 | 0.00 | 95.53 | 135.90 | 207.27 | 0.00 | 0.00 | 0.00 |
November | 79.60 | 0.00 | 79.60 | 54.41 | 313.90 | 0.00 | 0.00 | 0.00 |
December | 70.76 | 0.00 | 70.76 | 27.08 | 420.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.51 | 5.78 | 113.72 | 207.73 | 193.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 70.76 | 0.00 | 70.76 | 27.08 | 30.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 190.12 | 34.54 | 155.58 | 488.11 | 420.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.75 | 0.00 | 75.75 | 53.08 | 336.92 | 0.00 | 0.00 | 0.00 |
February | 86.32 | 0.00 | 86.32 | 36.33 | 338.93 | 0.00 | 0.00 | 0.00 |
March | 114.71 | 0.00 | 114.71 | 101.24 | 292.71 | 0.00 | 0.00 | 0.00 |
April | 139.76 | 1.45 | 138.31 | 227.35 | 151.38 | 0.00 | 0.00 | 0.00 |
May | 163.61 | 13.10 | 150.51 | 315.47 | 99.85 | 0.00 | 0.00 | 0.00 |
June | 190.12 | 34.54 | 155.58 | 488.11 | 39.82 | 0.00 | 0.00 | 0.00 |
July | 162.14 | 16.89 | 145.25 | 415.68 | 30.95 | 0.00 | 0.00 | 0.00 |
August | 130.87 | 3.25 | 127.62 | 341.48 | 40.67 | 0.00 | 0.00 | 0.00 |
September | 123.48 | 0.03 | 123.44 | 287.37 | 62.02 | 0.00 | 0.00 | 0.00 |
October | 95.53 | 0.00 | 95.53 | 135.90 | 207.27 | 0.00 | 0.00 | 0.00 |
November | 79.60 | 0.00 | 79.60 | 54.41 | 313.90 | 0.00 | 0.00 | 0.00 |
December | 70.76 | 0.00 | 70.76 | 27.07 | 420.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.51 | 5.78 | 113.72 | 207.73 | 193.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 70.76 | 0.00 | 70.76 | 27.07 | 30.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 190.12 | 34.54 | 155.58 | 488.11 | 420.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.75 | 0.00 | 75.75 | 53.08 | 336.92 | 0.00 | 0.00 | 0.00 |
February | 86.32 | 0.00 | 86.32 | 36.33 | 338.93 | 0.00 | 0.00 | 0.00 |
March | 114.71 | 0.00 | 114.71 | 101.24 | 292.71 | 0.00 | 0.00 | 0.00 |
April | 139.76 | 1.45 | 138.31 | 227.35 | 151.38 | 0.00 | 0.00 | 0.00 |
May | 163.61 | 13.10 | 150.51 | 315.47 | 99.85 | 0.00 | 0.00 | 0.00 |
June | 190.12 | 34.54 | 155.58 | 488.11 | 39.82 | 0.00 | 0.00 | 0.00 |
July | 162.14 | 16.89 | 145.25 | 415.69 | 30.95 | 0.00 | 0.00 | 0.00 |
August | 130.87 | 3.25 | 127.62 | 341.48 | 40.67 | 0.00 | 0.00 | 0.00 |
September | 123.48 | 0.03 | 123.45 | 287.37 | 62.02 | 0.00 | 0.00 | 0.00 |
October | 95.53 | 0.00 | 95.53 | 135.90 | 207.27 | 0.00 | 0.00 | 0.00 |
November | 79.60 | 0.00 | 79.60 | 54.41 | 313.90 | 0.00 | 0.00 | 0.00 |
December | 70.76 | 0.00 | 70.76 | 27.08 | 420.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.51 | 5.78 | 113.72 | 207.73 | 193.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 70.76 | 0.00 | 70.76 | 27.08 | 30.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 190.12 | 34.54 | 155.58 | 488.11 | 420.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.75 | 0.00 | 75.75 | 53.08 | 336.92 | 0.00 | 0.00 | 0.00 |
February | 86.32 | 0.00 | 86.32 | 36.33 | 338.93 | 0.00 | 0.00 | 0.00 |
March | 114.71 | 0.00 | 114.71 | 101.24 | 292.71 | 0.00 | 0.00 | 0.00 |
April | 139.76 | 1.45 | 138.31 | 227.35 | 151.38 | 0.00 | 0.00 | 0.00 |
May | 163.61 | 13.10 | 150.51 | 315.47 | 99.85 | 0.00 | 0.00 | 0.00 |
June | 190.12 | 34.54 | 155.58 | 488.11 | 39.82 | 0.00 | 0.00 | 0.00 |
July | 162.14 | 16.89 | 145.25 | 415.68 | 30.95 | 0.00 | 0.00 | 0.00 |
August | 130.87 | 3.25 | 127.62 | 341.48 | 40.67 | 0.00 | 0.00 | 0.00 |
September | 123.48 | 0.03 | 123.44 | 287.37 | 62.02 | 0.00 | 0.00 | 0.00 |
October | 95.53 | 0.00 | 95.53 | 135.90 | 207.27 | 0.00 | 0.00 | 0.00 |
November | 79.60 | 0.00 | 79.60 | 54.41 | 313.90 | 0.00 | 0.00 | 0.00 |
December | 70.76 | 0.00 | 70.76 | 27.07 | 420.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.51 | 5.78 | 113.72 | 207.73 | 193.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 70.76 | 0.00 | 70.76 | 27.07 | 30.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 190.12 | 34.54 | 155.58 | 488.11 | 420.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.75 | 0.00 | 75.75 | 53.08 | 336.90 | 0.00 | 0.00 | 0.00 |
February | 86.31 | 0.00 | 86.31 | 36.32 | 338.92 | 0.00 | 0.00 | 0.00 |
March | 114.71 | 0.00 | 114.71 | 101.24 | 292.70 | 0.00 | 0.00 | 0.00 |
April | 139.76 | 1.45 | 138.31 | 227.34 | 151.37 | 0.00 | 0.00 | 0.00 |
May | 163.60 | 13.10 | 150.50 | 315.45 | 99.84 | 0.00 | 0.00 | 0.00 |
June | 190.11 | 34.54 | 155.57 | 488.09 | 39.82 | 0.00 | 0.00 | 0.00 |
July | 162.13 | 16.89 | 145.24 | 415.67 | 30.95 | 0.00 | 0.00 | 0.00 |
August | 130.87 | 3.25 | 127.62 | 341.47 | 40.66 | 0.00 | 0.00 | 0.00 |
September | 123.47 | 0.03 | 123.44 | 287.35 | 62.02 | 0.00 | 0.00 | 0.00 |
October | 95.53 | 0.00 | 95.53 | 135.90 | 207.26 | 0.00 | 0.00 | 0.00 |
November | 79.59 | 0.00 | 79.59 | 54.41 | 313.89 | 0.00 | 0.00 | 0.00 |
December | 70.76 | 0.00 | 70.76 | 27.07 | 420.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.50 | 5.78 | 113.72 | 207.72 | 193.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 70.76 | 0.00 | 70.76 | 27.07 | 30.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 190.11 | 34.54 | 155.57 | 488.09 | 420.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.91 | 170.57 | 101.33 | 344.64 | 342.73 | 0.00 | 0.00 | 0.00 |
February | 268.02 | 153.32 | 114.70 | 301.94 | 345.37 | 0.00 | 0.00 | 0.00 |
March | 335.41 | 172.54 | 162.87 | 436.63 | 295.58 | 0.00 | 0.00 | 0.00 |
April | 478.78 | 285.36 | 193.42 | 793.58 | 154.12 | 0.00 | 0.00 | 0.00 |
May | 496.19 | 294.14 | 202.05 | 877.33 | 111.19 | 0.00 | 0.00 | 0.00 |
June | 517.19 | 321.38 | 195.82 | 1049.40 | 41.07 | 0.00 | 0.00 | 0.00 |
July | 436.80 | 246.29 | 190.51 | 897.33 | 30.51 | 0.00 | 0.00 | 0.00 |
August | 414.56 | 236.59 | 177.97 | 844.27 | 39.55 | 0.00 | 0.00 | 0.00 |
September | 340.18 | 163.97 | 176.21 | 666.86 | 63.98 | 0.00 | 0.00 | 0.00 |
October | 341.69 | 207.95 | 133.74 | 536.35 | 210.34 | 0.00 | 0.00 | 0.00 |
November | 262.74 | 157.73 | 105.01 | 332.05 | 316.77 | 0.00 | 0.00 | 0.00 |
December | 239.55 | 144.65 | 94.90 | 263.72 | 415.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 367.37 | 213.15 | 154.22 | 613.48 | 196.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 239.55 | 144.65 | 94.90 | 263.72 | 30.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 517.19 | 321.38 | 202.05 | 1049.40 | 415.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.91 | 170.57 | 101.33 | 344.64 | 342.73 | 0.00 | 0.00 | 0.00 |
February | 268.02 | 153.32 | 114.70 | 301.94 | 345.37 | 0.00 | 0.00 | 0.00 |
March | 335.41 | 172.54 | 162.87 | 436.63 | 295.58 | 0.00 | 0.00 | 0.00 |
April | 478.78 | 285.36 | 193.42 | 793.58 | 154.12 | 0.00 | 0.00 | 0.00 |
May | 496.19 | 294.14 | 202.05 | 877.33 | 111.19 | 0.00 | 0.00 | 0.00 |
June | 517.19 | 321.38 | 195.82 | 1049.40 | 41.07 | 0.00 | 0.00 | 0.00 |
July | 436.80 | 246.29 | 190.51 | 897.33 | 30.51 | 0.00 | 0.00 | 0.00 |
August | 414.56 | 236.59 | 177.97 | 844.27 | 39.55 | 0.00 | 0.00 | 0.00 |
September | 340.18 | 163.97 | 176.21 | 666.86 | 63.98 | 0.00 | 0.00 | 0.00 |
October | 341.69 | 207.95 | 133.74 | 536.35 | 210.34 | 0.00 | 0.00 | 0.00 |
November | 262.74 | 157.73 | 105.01 | 332.05 | 316.77 | 0.00 | 0.00 | 0.00 |
December | 239.55 | 144.65 | 94.90 | 263.72 | 415.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 367.37 | 213.15 | 154.22 | 613.48 | 196.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 239.55 | 144.65 | 94.90 | 263.72 | 30.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 517.19 | 321.38 | 202.05 | 1049.40 | 415.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.90 | 170.57 | 101.33 | 344.63 | 342.73 | 0.00 | 0.00 | 0.00 |
February | 268.01 | 153.32 | 114.70 | 301.93 | 345.37 | 0.00 | 0.00 | 0.00 |
March | 335.41 | 172.54 | 162.87 | 436.63 | 295.57 | 0.00 | 0.00 | 0.00 |
April | 478.77 | 285.35 | 193.42 | 793.56 | 154.12 | 0.00 | 0.00 | 0.00 |
May | 496.18 | 294.13 | 202.05 | 877.31 | 111.18 | 0.00 | 0.00 | 0.00 |
June | 517.18 | 321.37 | 195.81 | 1049.38 | 41.07 | 0.00 | 0.00 | 0.00 |
July | 436.79 | 246.29 | 190.50 | 897.31 | 30.51 | 0.00 | 0.00 | 0.00 |
August | 414.55 | 236.59 | 177.97 | 844.26 | 39.55 | 0.00 | 0.00 | 0.00 |
September | 340.17 | 163.97 | 176.20 | 666.84 | 63.98 | 0.00 | 0.00 | 0.00 |
October | 341.68 | 207.94 | 133.74 | 536.34 | 210.34 | 0.00 | 0.00 | 0.00 |
November | 262.73 | 157.72 | 105.01 | 332.04 | 316.76 | 0.00 | 0.00 | 0.00 |
December | 239.54 | 144.64 | 94.90 | 263.71 | 415.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 367.36 | 213.15 | 154.22 | 613.47 | 196.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 239.54 | 144.64 | 94.90 | 263.71 | 30.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 517.18 | 321.37 | 202.05 | 1049.38 | 415.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 623.73 | 498.16 | 125.58 | 947.52 | 322.86 | 0.00 | 0.00 | 0.00 |
February | 394.38 | 265.98 | 128.40 | 537.54 | 313.79 | 0.00 | 0.00 | 0.00 |
March | 328.15 | 169.01 | 159.14 | 480.26 | 285.48 | 0.00 | 0.00 | 0.00 |
April | 279.34 | 112.88 | 166.46 | 524.56 | 160.92 | 0.00 | 0.00 | 0.00 |
May | 187.19 | 30.93 | 156.27 | 387.69 | 110.64 | 0.00 | 0.00 | 0.00 |
June | 160.29 | 12.36 | 147.93 | 438.42 | 41.75 | 0.00 | 0.00 | 0.00 |
July | 163.79 | 16.95 | 146.84 | 428.00 | 31.78 | 0.00 | 0.00 | 0.00 |
August | 199.16 | 55.04 | 144.12 | 494.52 | 42.27 | 0.00 | 0.00 | 0.00 |
September | 286.97 | 122.43 | 164.54 | 602.46 | 65.35 | 0.00 | 0.00 | 0.00 |
October | 457.25 | 316.48 | 140.77 | 764.49 | 203.20 | 0.00 | 0.00 | 0.00 |
November | 532.87 | 408.15 | 124.72 | 798.33 | 297.47 | 0.00 | 0.00 | 0.00 |
December | 579.89 | 459.06 | 120.83 | 837.44 | 387.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 349.43 | 205.58 | 143.85 | 604.11 | 188.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.29 | 12.36 | 120.83 | 387.69 | 31.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 623.73 | 498.16 | 166.46 | 947.52 | 387.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 623.73 | 498.15 | 125.58 | 947.51 | 322.86 | 0.00 | 0.00 | 0.00 |
February | 394.38 | 265.98 | 128.40 | 537.54 | 313.79 | 0.00 | 0.00 | 0.00 |
March | 328.15 | 169.01 | 159.14 | 480.26 | 285.48 | 0.00 | 0.00 | 0.00 |
April | 279.34 | 112.88 | 166.46 | 524.56 | 160.92 | 0.00 | 0.00 | 0.00 |
May | 187.19 | 30.93 | 156.26 | 387.69 | 110.64 | 0.00 | 0.00 | 0.00 |
June | 160.29 | 12.36 | 147.93 | 438.42 | 41.75 | 0.00 | 0.00 | 0.00 |
July | 163.79 | 16.94 | 146.84 | 428.00 | 31.78 | 0.00 | 0.00 | 0.00 |
August | 199.16 | 55.04 | 144.12 | 494.52 | 42.27 | 0.00 | 0.00 | 0.00 |
September | 286.96 | 122.43 | 164.54 | 602.46 | 65.35 | 0.00 | 0.00 | 0.00 |
October | 457.25 | 316.48 | 140.76 | 764.49 | 203.20 | 0.00 | 0.00 | 0.00 |
November | 532.86 | 408.15 | 124.72 | 798.32 | 297.47 | 0.00 | 0.00 | 0.00 |
December | 579.88 | 459.05 | 120.83 | 837.43 | 387.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 349.42 | 205.58 | 143.85 | 604.11 | 188.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.29 | 12.36 | 120.83 | 387.69 | 31.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 623.73 | 498.15 | 166.46 | 947.51 | 387.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 623.73 | 498.16 | 125.58 | 947.52 | 322.86 | 0.00 | 0.00 | 0.00 |
February | 394.38 | 265.98 | 128.40 | 537.54 | 313.79 | 0.00 | 0.00 | 0.00 |
March | 328.15 | 169.01 | 159.14 | 480.26 | 285.48 | 0.00 | 0.00 | 0.00 |
April | 279.34 | 112.88 | 166.46 | 524.56 | 160.92 | 0.00 | 0.00 | 0.00 |
May | 187.19 | 30.93 | 156.27 | 387.69 | 110.64 | 0.00 | 0.00 | 0.00 |
June | 160.29 | 12.36 | 147.93 | 438.42 | 41.75 | 0.00 | 0.00 | 0.00 |
July | 163.79 | 16.95 | 146.84 | 428.00 | 31.78 | 0.00 | 0.00 | 0.00 |
August | 199.16 | 55.04 | 144.12 | 494.52 | 42.27 | 0.00 | 0.00 | 0.00 |
September | 286.97 | 122.43 | 164.54 | 602.46 | 65.35 | 0.00 | 0.00 | 0.00 |
October | 457.25 | 316.48 | 140.77 | 764.49 | 203.20 | 0.00 | 0.00 | 0.00 |
November | 532.87 | 408.15 | 124.72 | 798.33 | 297.47 | 0.00 | 0.00 | 0.00 |
December | 579.89 | 459.06 | 120.83 | 837.44 | 387.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 349.43 | 205.58 | 143.85 | 604.11 | 188.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.29 | 12.36 | 120.83 | 387.69 | 31.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 623.73 | 498.16 | 166.46 | 947.52 | 387.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 623.73 | 498.15 | 125.58 | 947.51 | 322.86 | 0.00 | 0.00 | 0.00 |
February | 394.38 | 265.98 | 128.40 | 537.54 | 313.79 | 0.00 | 0.00 | 0.00 |
March | 328.15 | 169.01 | 159.14 | 480.26 | 285.48 | 0.00 | 0.00 | 0.00 |
April | 279.34 | 112.88 | 166.46 | 524.56 | 160.92 | 0.00 | 0.00 | 0.00 |
May | 187.19 | 30.93 | 156.26 | 387.69 | 110.64 | 0.00 | 0.00 | 0.00 |
June | 160.29 | 12.36 | 147.93 | 438.42 | 41.75 | 0.00 | 0.00 | 0.00 |
July | 163.79 | 16.94 | 146.84 | 428.00 | 31.78 | 0.00 | 0.00 | 0.00 |
August | 199.16 | 55.04 | 144.12 | 494.52 | 42.27 | 0.00 | 0.00 | 0.00 |
September | 286.96 | 122.43 | 164.54 | 602.46 | 65.35 | 0.00 | 0.00 | 0.00 |
October | 457.25 | 316.48 | 140.76 | 764.49 | 203.20 | 0.00 | 0.00 | 0.00 |
November | 532.86 | 408.15 | 124.72 | 798.32 | 297.47 | 0.00 | 0.00 | 0.00 |
December | 579.88 | 459.05 | 120.83 | 837.43 | 387.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 349.42 | 205.58 | 143.85 | 604.11 | 188.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.29 | 12.36 | 120.83 | 387.69 | 31.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 623.73 | 498.15 | 166.46 | 947.51 | 387.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 623.71 | 498.14 | 125.57 | 947.48 | 322.85 | 0.00 | 0.00 | 0.00 |
February | 394.36 | 265.97 | 128.39 | 537.52 | 313.77 | 0.00 | 0.00 | 0.00 |
March | 328.14 | 169.01 | 159.13 | 480.24 | 285.47 | 0.00 | 0.00 | 0.00 |
April | 279.33 | 112.88 | 166.46 | 524.54 | 160.91 | 0.00 | 0.00 | 0.00 |
May | 187.18 | 30.92 | 156.26 | 387.67 | 110.64 | 0.00 | 0.00 | 0.00 |
June | 160.28 | 12.36 | 147.93 | 438.40 | 41.75 | 0.00 | 0.00 | 0.00 |
July | 163.78 | 16.94 | 146.84 | 427.98 | 31.78 | 0.00 | 0.00 | 0.00 |
August | 199.15 | 55.03 | 144.11 | 494.50 | 42.27 | 0.00 | 0.00 | 0.00 |
September | 286.95 | 122.42 | 164.53 | 602.43 | 65.35 | 0.00 | 0.00 | 0.00 |
October | 457.23 | 316.47 | 140.76 | 764.46 | 203.19 | 0.00 | 0.00 | 0.00 |
November | 532.84 | 408.13 | 124.71 | 798.29 | 297.45 | 0.00 | 0.00 | 0.00 |
December | 579.86 | 459.04 | 120.82 | 837.40 | 387.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 349.41 | 205.57 | 143.84 | 604.09 | 188.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.28 | 12.36 | 120.82 | 387.67 | 31.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 623.71 | 498.14 | 166.46 | 947.48 | 387.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 284.33 | 176.71 | 107.61 | 400.49 | 403.18 | 0.00 | 0.00 | 0.00 |
February | 230.33 | 111.35 | 118.98 | 256.38 | 409.85 | 0.00 | 0.00 | 0.00 |
March | 305.08 | 145.44 | 159.65 | 393.79 | 360.85 | 0.00 | 0.00 | 0.00 |
April | 468.47 | 267.23 | 201.24 | 777.67 | 211.10 | 0.00 | 0.00 | 0.00 |
May | 469.67 | 263.34 | 206.32 | 842.36 | 142.22 | 0.00 | 0.00 | 0.00 |
June | 499.30 | 293.67 | 205.63 | 1010.05 | 63.30 | 0.00 | 0.00 | 0.00 |
July | 363.41 | 169.64 | 193.77 | 750.37 | 51.65 | 0.00 | 0.00 | 0.00 |
August | 346.54 | 174.04 | 172.50 | 708.39 | 69.94 | 0.00 | 0.00 | 0.00 |
September | 302.07 | 126.92 | 175.15 | 598.15 | 83.78 | 0.00 | 0.00 | 0.00 |
October | 309.08 | 176.73 | 132.35 | 491.25 | 259.32 | 0.00 | 0.00 | 0.00 |
November | 284.67 | 171.87 | 112.79 | 386.05 | 392.50 | 0.00 | 0.00 | 0.00 |
December | 229.43 | 130.63 | 98.80 | 277.07 | 520.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 341.42 | 184.22 | 157.20 | 575.65 | 246.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 229.43 | 111.35 | 98.80 | 256.38 | 51.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 499.30 | 293.67 | 206.32 | 1010.05 | 520.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 284.33 | 176.71 | 107.61 | 400.49 | 403.18 | 0.00 | 0.00 | 0.00 |
February | 230.33 | 111.35 | 118.98 | 256.38 | 409.85 | 0.00 | 0.00 | 0.00 |
March | 305.08 | 145.44 | 159.65 | 393.79 | 360.85 | 0.00 | 0.00 | 0.00 |
April | 468.47 | 267.23 | 201.24 | 777.67 | 211.10 | 0.00 | 0.00 | 0.00 |
May | 469.67 | 263.34 | 206.32 | 842.36 | 142.22 | 0.00 | 0.00 | 0.00 |
June | 499.30 | 293.67 | 205.63 | 1010.05 | 63.30 | 0.00 | 0.00 | 0.00 |
July | 363.41 | 169.64 | 193.77 | 750.37 | 51.65 | 0.00 | 0.00 | 0.00 |
August | 346.54 | 174.04 | 172.50 | 708.39 | 69.94 | 0.00 | 0.00 | 0.00 |
September | 302.07 | 126.92 | 175.15 | 598.15 | 83.78 | 0.00 | 0.00 | 0.00 |
October | 309.08 | 176.73 | 132.35 | 491.25 | 259.32 | 0.00 | 0.00 | 0.00 |
November | 284.67 | 171.87 | 112.79 | 386.05 | 392.50 | 0.00 | 0.00 | 0.00 |
December | 229.43 | 130.63 | 98.80 | 277.07 | 520.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 341.42 | 184.22 | 157.20 | 575.65 | 246.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 229.43 | 111.35 | 98.80 | 256.38 | 51.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 499.30 | 293.67 | 206.32 | 1010.05 | 520.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 284.32 | 176.71 | 107.61 | 400.48 | 403.17 | 0.00 | 0.00 | 0.00 |
February | 230.33 | 111.35 | 118.98 | 256.38 | 409.84 | 0.00 | 0.00 | 0.00 |
March | 305.08 | 145.44 | 159.64 | 393.78 | 360.84 | 0.00 | 0.00 | 0.00 |
April | 468.46 | 267.22 | 201.23 | 777.66 | 211.10 | 0.00 | 0.00 | 0.00 |
May | 469.66 | 263.34 | 206.32 | 842.34 | 142.22 | 0.00 | 0.00 | 0.00 |
June | 499.29 | 293.67 | 205.63 | 1010.03 | 63.29 | 0.00 | 0.00 | 0.00 |
July | 363.40 | 169.63 | 193.77 | 750.36 | 51.65 | 0.00 | 0.00 | 0.00 |
August | 346.53 | 174.04 | 172.50 | 708.38 | 69.94 | 0.00 | 0.00 | 0.00 |
September | 302.06 | 126.91 | 175.15 | 598.14 | 83.78 | 0.00 | 0.00 | 0.00 |
October | 309.07 | 176.73 | 132.34 | 491.24 | 259.31 | 0.00 | 0.00 | 0.00 |
November | 284.66 | 171.87 | 112.79 | 386.05 | 392.50 | 0.00 | 0.00 | 0.00 |
December | 229.43 | 130.63 | 98.80 | 277.07 | 520.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 341.41 | 184.22 | 157.19 | 575.64 | 246.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 229.43 | 111.35 | 98.80 | 256.38 | 51.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 499.29 | 293.67 | 206.32 | 1010.03 | 520.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 378.76 | 0.00 | 378.76 | 326.49 | 1508.47 | 0.00 | 0.00 | 0.00 |
February | 431.59 | 0.00 | 431.59 | 226.59 | 1493.95 | 0.00 | 0.00 | 0.00 |
March | 573.58 | 0.00 | 573.58 | 554.32 | 1334.46 | 0.00 | 0.00 | 0.00 |
April | 698.82 | 7.25 | 691.57 | 1176.11 | 727.95 | 0.00 | 0.00 | 0.00 |
May | 818.04 | 65.50 | 752.54 | 1600.96 | 491.04 | 0.00 | 0.00 | 0.00 |
June | 950.62 | 172.72 | 777.90 | 2469.59 | 198.80 | 0.00 | 0.00 | 0.00 |
July | 810.70 | 84.46 | 726.24 | 2111.46 | 153.27 | 0.00 | 0.00 | 0.00 |
August | 654.38 | 16.26 | 638.12 | 1749.00 | 193.45 | 0.00 | 0.00 | 0.00 |
September | 617.40 | 0.16 | 617.23 | 1457.88 | 303.88 | 0.00 | 0.00 | 0.00 |
October | 477.66 | 0.00 | 477.66 | 717.98 | 958.06 | 0.00 | 0.00 | 0.00 |
November | 397.98 | 0.00 | 397.98 | 322.87 | 1397.21 | 0.00 | 0.00 | 0.00 |
December | 353.80 | 0.00 | 353.80 | 204.29 | 1823.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 597.54 | 28.92 | 568.62 | 1080.38 | 879.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.80 | 0.00 | 353.80 | 204.29 | 153.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 950.62 | 172.72 | 777.90 | 2469.59 | 1823.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 815.71 | 511.72 | 303.99 | 1054.21 | 959.09 | 0.00 | 0.00 | 0.00 |
February | 804.04 | 459.95 | 344.09 | 917.06 | 960.31 | 0.00 | 0.00 | 0.00 |
March | 1006.22 | 517.61 | 488.61 | 1312.03 | 853.37 | 0.00 | 0.00 | 0.00 |
April | 1436.33 | 856.07 | 580.26 | 2364.89 | 479.73 | 0.00 | 0.00 | 0.00 |
May | 1488.56 | 882.40 | 606.15 | 2618.33 | 339.46 | 0.00 | 0.00 | 0.00 |
June | 1551.56 | 964.12 | 587.44 | 3135.92 | 129.90 | 0.00 | 0.00 | 0.00 |
July | 1310.39 | 738.87 | 571.51 | 2678.32 | 101.24 | 0.00 | 0.00 | 0.00 |
August | 1243.67 | 709.76 | 533.91 | 2522.85 | 129.74 | 0.00 | 0.00 | 0.00 |
September | 1020.52 | 491.91 | 528.61 | 1991.11 | 198.17 | 0.00 | 0.00 | 0.00 |
October | 1025.05 | 623.84 | 401.21 | 1606.32 | 614.12 | 0.00 | 0.00 | 0.00 |
November | 788.21 | 473.17 | 315.04 | 1007.94 | 894.81 | 0.00 | 0.00 | 0.00 |
December | 718.64 | 433.93 | 284.70 | 824.95 | 1148.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1102.10 | 639.45 | 462.65 | 1840.55 | 565.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 718.64 | 433.93 | 284.70 | 824.95 | 101.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1551.56 | 964.12 | 606.15 | 3135.92 | 1148.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3118.73 | 2490.84 | 627.89 | 4704.65 | 1602.64 | 0.00 | 0.00 | 0.00 |
February | 1971.93 | 1329.94 | 641.99 | 2672.34 | 1522.24 | 0.00 | 0.00 | 0.00 |
March | 1640.79 | 845.09 | 795.70 | 2393.42 | 1390.28 | 0.00 | 0.00 | 0.00 |
April | 1396.74 | 564.42 | 832.32 | 2625.89 | 798.35 | 0.00 | 0.00 | 0.00 |
May | 935.96 | 154.63 | 781.33 | 1954.07 | 546.98 | 0.00 | 0.00 | 0.00 |
June | 801.45 | 61.78 | 739.67 | 2227.62 | 203.52 | 0.00 | 0.00 | 0.00 |
July | 818.95 | 84.73 | 734.22 | 2171.64 | 155.30 | 0.00 | 0.00 | 0.00 |
August | 995.80 | 275.19 | 720.61 | 2498.68 | 203.59 | 0.00 | 0.00 | 0.00 |
September | 1434.85 | 612.14 | 822.71 | 3007.12 | 327.69 | 0.00 | 0.00 | 0.00 |
October | 2286.29 | 1582.45 | 703.84 | 3798.57 | 1004.78 | 0.00 | 0.00 | 0.00 |
November | 2664.39 | 2040.78 | 623.60 | 3968.01 | 1457.25 | 0.00 | 0.00 | 0.00 |
December | 2899.49 | 2295.34 | 604.15 | 4177.11 | 1885.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1747.16 | 1027.91 | 719.25 | 3020.07 | 922.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 801.45 | 61.78 | 604.15 | 1954.07 | 155.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3118.73 | 2490.84 | 832.32 | 4704.65 | 1885.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 852.98 | 530.14 | 322.84 | 1234.26 | 1091.23 | 0.00 | 0.00 | 0.00 |
February | 690.99 | 334.05 | 356.94 | 804.90 | 1044.79 | 0.00 | 0.00 | 0.00 |
March | 915.24 | 436.31 | 478.93 | 1227.77 | 939.23 | 0.00 | 0.00 | 0.00 |
April | 1405.38 | 801.67 | 603.71 | 2367.75 | 572.98 | 0.00 | 0.00 | 0.00 |
May | 1408.99 | 790.02 | 618.97 | 2536.50 | 409.35 | 0.00 | 0.00 | 0.00 |
June | 1497.90 | 881.00 | 616.89 | 3060.47 | 170.56 | 0.00 | 0.00 | 0.00 |
July | 1090.20 | 508.90 | 581.30 | 2301.86 | 128.44 | 0.00 | 0.00 | 0.00 |
August | 1039.61 | 522.11 | 517.50 | 2180.99 | 161.60 | 0.00 | 0.00 | 0.00 |
September | 906.19 | 380.74 | 525.45 | 1811.62 | 230.97 | 0.00 | 0.00 | 0.00 |
October | 927.22 | 530.18 | 397.04 | 1503.09 | 694.20 | 0.00 | 0.00 | 0.00 |
November | 853.99 | 515.62 | 338.38 | 1197.98 | 1007.49 | 0.00 | 0.00 | 0.00 |
December | 688.28 | 391.89 | 296.40 | 891.30 | 1292.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1024.25 | 552.66 | 471.59 | 1763.89 | 643.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 688.28 | 334.05 | 296.40 | 804.90 | 128.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1497.90 | 881.00 | 618.97 | 3060.47 | 1292.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 378.76 | 0.00 | 378.76 | 371.02 | 1370.47 | 0.00 | 0.00 | 0.00 |
February | 431.59 | 0.00 | 431.59 | 265.91 | 1330.25 | 0.00 | 0.00 | 0.00 |
March | 573.58 | 0.00 | 573.58 | 589.12 | 1242.66 | 0.00 | 0.00 | 0.00 |
April | 698.82 | 7.25 | 691.57 | 1168.48 | 715.95 | 0.00 | 0.00 | 0.00 |
May | 818.04 | 65.50 | 752.54 | 1583.58 | 494.82 | 0.00 | 0.00 | 0.00 |
June | 950.62 | 172.72 | 777.90 | 2435.00 | 208.83 | 0.00 | 0.00 | 0.00 |
July | 810.70 | 84.46 | 726.24 | 2072.06 | 163.20 | 0.00 | 0.00 | 0.00 |
August | 654.38 | 16.26 | 638.12 | 1719.57 | 201.45 | 0.00 | 0.00 | 0.00 |
September | 617.40 | 0.16 | 617.23 | 1436.00 | 311.18 | 0.00 | 0.00 | 0.00 |
October | 477.66 | 0.00 | 477.66 | 731.70 | 903.08 | 0.00 | 0.00 | 0.00 |
November | 397.98 | 0.00 | 397.98 | 359.90 | 1271.35 | 0.00 | 0.00 | 0.00 |
December | 353.80 | 0.00 | 353.80 | 249.47 | 1646.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 597.54 | 28.92 | 568.62 | 1085.59 | 819.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.80 | 0.00 | 353.80 | 249.47 | 163.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 950.62 | 172.72 | 777.90 | 2435.00 | 1646.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 815.71 | 511.72 | 303.99 | 1088.69 | 887.26 | 0.00 | 0.00 | 0.00 |
February | 804.04 | 459.95 | 344.09 | 948.52 | 870.14 | 0.00 | 0.00 | 0.00 |
March | 1006.22 | 517.61 | 488.61 | 1332.99 | 808.52 | 0.00 | 0.00 | 0.00 |
April | 1436.33 | 856.07 | 580.26 | 2353.72 | 478.48 | 0.00 | 0.00 | 0.00 |
May | 1488.56 | 882.40 | 606.15 | 2601.91 | 342.84 | 0.00 | 0.00 | 0.00 |
June | 1551.56 | 964.12 | 587.44 | 3108.64 | 136.35 | 0.00 | 0.00 | 0.00 |
July | 1310.39 | 738.87 | 571.51 | 2649.78 | 107.55 | 0.00 | 0.00 | 0.00 |
August | 1243.67 | 709.76 | 533.91 | 2500.01 | 135.04 | 0.00 | 0.00 | 0.00 |
September | 1020.52 | 491.91 | 528.61 | 1973.99 | 203.41 | 0.00 | 0.00 | 0.00 |
October | 1025.05 | 623.84 | 401.21 | 1610.66 | 590.05 | 0.00 | 0.00 | 0.00 |
November | 788.21 | 473.17 | 315.04 | 1035.17 | 828.64 | 0.00 | 0.00 | 0.00 |
December | 718.64 | 433.93 | 284.70 | 871.70 | 1048.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1102.10 | 639.45 | 462.65 | 1843.92 | 534.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 718.64 | 433.93 | 284.70 | 871.70 | 107.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1551.56 | 964.12 | 606.15 | 3108.64 | 1048.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3118.73 | 2490.84 | 627.89 | 4737.71 | 1507.20 | 0.00 | 0.00 | 0.00 |
February | 1971.93 | 1329.94 | 641.99 | 2710.93 | 1389.27 | 0.00 | 0.00 | 0.00 |
March | 1640.79 | 845.09 | 795.70 | 2417.98 | 1315.26 | 0.00 | 0.00 | 0.00 |
April | 1396.74 | 564.42 | 832.32 | 2612.26 | 789.13 | 0.00 | 0.00 | 0.00 |
May | 935.96 | 154.63 | 781.33 | 1936.49 | 547.66 | 0.00 | 0.00 | 0.00 |
June | 801.45 | 61.78 | 739.67 | 2193.64 | 211.26 | 0.00 | 0.00 | 0.00 |
July | 818.95 | 84.73 | 734.22 | 2134.13 | 163.75 | 0.00 | 0.00 | 0.00 |
August | 995.80 | 275.19 | 720.61 | 2469.27 | 210.58 | 0.00 | 0.00 | 0.00 |
September | 1434.85 | 612.14 | 822.71 | 2983.36 | 336.13 | 0.00 | 0.00 | 0.00 |
October | 2286.29 | 1582.45 | 703.84 | 3800.28 | 969.11 | 0.00 | 0.00 | 0.00 |
November | 2664.39 | 2040.78 | 623.60 | 3996.43 | 1369.14 | 0.00 | 0.00 | 0.00 |
December | 2899.49 | 2295.34 | 604.15 | 4226.68 | 1748.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1747.16 | 1027.91 | 719.25 | 3021.58 | 877.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 801.45 | 61.78 | 604.15 | 1936.49 | 163.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3118.73 | 2490.84 | 832.32 | 4737.71 | 1748.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 852.98 | 530.14 | 322.84 | 1253.93 | 1015.90 | 0.00 | 0.00 | 0.00 |
February | 690.99 | 334.05 | 356.94 | 823.99 | 955.24 | 0.00 | 0.00 | 0.00 |
March | 915.24 | 436.31 | 478.93 | 1243.95 | 888.69 | 0.00 | 0.00 | 0.00 |
April | 1405.38 | 801.67 | 603.71 | 2357.93 | 565.97 | 0.00 | 0.00 | 0.00 |
May | 1408.99 | 790.02 | 618.97 | 2522.43 | 409.31 | 0.00 | 0.00 | 0.00 |
June | 1497.90 | 881.00 | 616.89 | 3037.50 | 174.36 | 0.00 | 0.00 | 0.00 |
July | 1090.20 | 508.90 | 581.30 | 2279.84 | 132.59 | 0.00 | 0.00 | 0.00 |
August | 1039.61 | 522.11 | 517.50 | 2163.09 | 164.74 | 0.00 | 0.00 | 0.00 |
September | 906.19 | 380.74 | 525.45 | 1797.91 | 234.13 | 0.00 | 0.00 | 0.00 |
October | 927.22 | 530.18 | 397.04 | 1506.17 | 664.63 | 0.00 | 0.00 | 0.00 |
November | 853.99 | 515.62 | 338.38 | 1214.36 | 938.95 | 0.00 | 0.00 | 0.00 |
December | 688.28 | 391.89 | 296.40 | 915.44 | 1192.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1024.25 | 552.66 | 471.59 | 1763.65 | 610.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 688.28 | 334.05 | 296.40 | 823.99 | 132.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1497.90 | 881.00 | 618.97 | 3037.50 | 1192.71 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202894E+09 | 0.00 | 0.202894E+09 | 0.142174E+09 | 0.902398E+09 |
February | 0.208819E+09 | 0.00 | 0.208819E+09 | 87882098.94 | 0.819944E+09 |
March | 0.307254E+09 | 0.00 | 0.307254E+09 | 0.271168E+09 | 0.784004E+09 |
April | 0.362269E+09 | 3759385.01 | 0.358509E+09 | 0.589291E+09 | 0.392378E+09 |
May | 0.438210E+09 | 35087473.41 | 0.403122E+09 | 0.844950E+09 | 0.267429E+09 |
June | 0.492800E+09 | 89536035.68 | 0.403264E+09 | 0.126519E+10 | 0.103217E+09 |
July | 0.434274E+09 | 45242389.50 | 0.389031E+09 | 0.111338E+10 | 82910149.94 |
August | 0.350538E+09 | 8708099.40 | 0.341830E+09 | 0.914624E+09 | 0.108922E+09 |
September | 0.320058E+09 | 85439.34 | 0.319973E+09 | 0.744855E+09 | 0.160762E+09 |
October | 0.255876E+09 | 0.00 | 0.255876E+09 | 0.363999E+09 | 0.555157E+09 |
November | 0.206315E+09 | 0.00 | 0.206315E+09 | 0.141032E+09 | 0.813639E+09 |
December | 0.189521E+09 | 0.00 | 0.189521E+09 | 72518711.27 | 0.112553E+10 |
Annual Sum or Average | 0.376883E+10 | 0.182419E+09 | 0.358641E+10 | 0.655106E+10 | 0.611629E+10 |
Minimum of Months | 0.189521E+09 | 0.00 | 0.189521E+09 | 72518711.27 | 82910149.94 |
Maximum of Months | 0.492800E+09 | 89536035.68 | 0.403264E+09 | 0.126519E+10 | 0.112553E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202891E+09 | 0.00 | 0.202891E+09 | 0.142172E+09 | 0.902395E+09 |
February | 0.208816E+09 | 0.00 | 0.208816E+09 | 87879723.70 | 0.819943E+09 |
March | 0.307250E+09 | 0.00 | 0.307250E+09 | 0.271163E+09 | 0.784001E+09 |
April | 0.362265E+09 | 3759302.37 | 0.358506E+09 | 0.589287E+09 | 0.392375E+09 |
May | 0.438204E+09 | 35086702.06 | 0.403118E+09 | 0.844945E+09 | 0.267426E+09 |
June | 0.492794E+09 | 89534067.33 | 0.403260E+09 | 0.126518E+10 | 0.103215E+09 |
July | 0.434268E+09 | 45241394.90 | 0.389027E+09 | 0.111337E+10 | 82908993.21 |
August | 0.350534E+09 | 8707907.96 | 0.341826E+09 | 0.914620E+09 | 0.108920E+09 |
September | 0.320054E+09 | 85437.46 | 0.319968E+09 | 0.744850E+09 | 0.160760E+09 |
October | 0.255873E+09 | 0.00 | 0.255873E+09 | 0.363997E+09 | 0.555154E+09 |
November | 0.206312E+09 | 0.00 | 0.206312E+09 | 0.141030E+09 | 0.813636E+09 |
December | 0.189519E+09 | 0.00 | 0.189519E+09 | 72517502.00 | 0.112553E+10 |
Annual Sum or Average | 0.376878E+10 | 0.182415E+09 | 0.358637E+10 | 0.655101E+10 | 0.611627E+10 |
Minimum of Months | 0.189519E+09 | 0.00 | 0.189519E+09 | 72517502.00 | 82908993.21 |
Maximum of Months | 0.492794E+09 | 89534067.33 | 0.403260E+09 | 0.126518E+10 | 0.112553E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202892E+09 | 0.00 | 0.202892E+09 | 0.142173E+09 | 0.902396E+09 |
February | 0.208817E+09 | 0.00 | 0.208817E+09 | 87880515.44 | 0.819944E+09 |
March | 0.307251E+09 | 0.00 | 0.307251E+09 | 0.271165E+09 | 0.784002E+09 |
April | 0.362266E+09 | 3759329.92 | 0.358507E+09 | 0.589288E+09 | 0.392376E+09 |
May | 0.438206E+09 | 35086959.18 | 0.403119E+09 | 0.844947E+09 | 0.267427E+09 |
June | 0.492796E+09 | 89534723.45 | 0.403261E+09 | 0.126518E+10 | 0.103216E+09 |
July | 0.434270E+09 | 45241726.43 | 0.389028E+09 | 0.111337E+10 | 82909378.79 |
August | 0.350535E+09 | 8707971.77 | 0.341827E+09 | 0.914621E+09 | 0.108921E+09 |
September | 0.320055E+09 | 85438.09 | 0.319970E+09 | 0.744852E+09 | 0.160760E+09 |
October | 0.255874E+09 | 0.00 | 0.255874E+09 | 0.363998E+09 | 0.555155E+09 |
November | 0.206313E+09 | 0.00 | 0.206313E+09 | 0.141031E+09 | 0.813637E+09 |
December | 0.189520E+09 | 0.00 | 0.189520E+09 | 72517905.09 | 0.112553E+10 |
Annual Sum or Average | 0.376880E+10 | 0.182416E+09 | 0.358638E+10 | 0.655103E+10 | 0.611628E+10 |
Minimum of Months | 0.189520E+09 | 0.00 | 0.189520E+09 | 72517905.09 | 82909378.79 |
Maximum of Months | 0.492796E+09 | 89534723.45 | 0.403261E+09 | 0.126518E+10 | 0.112553E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202891E+09 | 0.00 | 0.202891E+09 | 0.142172E+09 | 0.902395E+09 |
February | 0.208816E+09 | 0.00 | 0.208816E+09 | 87879723.70 | 0.819943E+09 |
March | 0.307250E+09 | 0.00 | 0.307250E+09 | 0.271163E+09 | 0.784001E+09 |
April | 0.362265E+09 | 3759302.37 | 0.358506E+09 | 0.589287E+09 | 0.392375E+09 |
May | 0.438204E+09 | 35086702.06 | 0.403118E+09 | 0.844945E+09 | 0.267426E+09 |
June | 0.492794E+09 | 89534067.33 | 0.403260E+09 | 0.126518E+10 | 0.103215E+09 |
July | 0.434268E+09 | 45241394.90 | 0.389027E+09 | 0.111337E+10 | 82908993.21 |
August | 0.350534E+09 | 8707907.96 | 0.341826E+09 | 0.914620E+09 | 0.108920E+09 |
September | 0.320054E+09 | 85437.46 | 0.319968E+09 | 0.744850E+09 | 0.160760E+09 |
October | 0.255873E+09 | 0.00 | 0.255873E+09 | 0.363997E+09 | 0.555154E+09 |
November | 0.206312E+09 | 0.00 | 0.206312E+09 | 0.141030E+09 | 0.813636E+09 |
December | 0.189519E+09 | 0.00 | 0.189519E+09 | 72517502.00 | 0.112553E+10 |
Annual Sum or Average | 0.376878E+10 | 0.182415E+09 | 0.358637E+10 | 0.655101E+10 | 0.611627E+10 |
Minimum of Months | 0.189519E+09 | 0.00 | 0.189519E+09 | 72517502.00 | 82908993.21 |
Maximum of Months | 0.492794E+09 | 89534067.33 | 0.403260E+09 | 0.126518E+10 | 0.112553E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202884E+09 | 0.00 | 0.202884E+09 | 0.142167E+09 | 0.902359E+09 |
February | 0.208808E+09 | 0.00 | 0.208808E+09 | 87876577.61 | 0.819910E+09 |
March | 0.307238E+09 | 0.00 | 0.307238E+09 | 0.271153E+09 | 0.783970E+09 |
April | 0.362251E+09 | 3759164.62 | 0.358492E+09 | 0.589264E+09 | 0.392359E+09 |
May | 0.438188E+09 | 35085416.46 | 0.403102E+09 | 0.844912E+09 | 0.267416E+09 |
June | 0.492775E+09 | 89530786.76 | 0.403244E+09 | 0.126513E+10 | 0.103211E+09 |
July | 0.434252E+09 | 45239737.23 | 0.389012E+09 | 0.111333E+10 | 82905844.39 |
August | 0.350520E+09 | 8707588.90 | 0.341813E+09 | 0.914584E+09 | 0.108916E+09 |
September | 0.320042E+09 | 85434.33 | 0.319956E+09 | 0.744821E+09 | 0.160754E+09 |
October | 0.255863E+09 | 0.00 | 0.255863E+09 | 0.363983E+09 | 0.555132E+09 |
November | 0.206304E+09 | 0.00 | 0.206304E+09 | 0.141025E+09 | 0.813604E+09 |
December | 0.189512E+09 | 0.00 | 0.189512E+09 | 72514780.76 | 0.112549E+10 |
Annual Sum or Average | 0.376864E+10 | 0.182408E+09 | 0.358623E+10 | 0.655075E+10 | 0.611602E+10 |
Minimum of Months | 0.189512E+09 | 0.00 | 0.189512E+09 | 72514780.76 | 82905844.39 |
Maximum of Months | 0.492775E+09 | 89530786.76 | 0.403244E+09 | 0.126513E+10 | 0.112549E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.728276E+09 | 0.456868E+09 | 0.271408E+09 | 0.923082E+09 | 0.917977E+09 |
February | 0.648388E+09 | 0.370907E+09 | 0.277480E+09 | 0.730446E+09 | 0.835530E+09 |
March | 0.898366E+09 | 0.462126E+09 | 0.436240E+09 | 0.116948E+10 | 0.791677E+09 |
April | 0.124100E+10 | 0.739653E+09 | 0.501349E+09 | 0.205696E+10 | 0.399491E+09 |
May | 0.132900E+10 | 0.787817E+09 | 0.541179E+09 | 0.234984E+10 | 0.297798E+09 |
June | 0.134056E+10 | 0.833005E+09 | 0.507554E+09 | 0.272005E+10 | 0.106458E+09 |
July | 0.116993E+10 | 0.659674E+09 | 0.510253E+09 | 0.240340E+10 | 81728513.93 |
August | 0.111036E+10 | 0.633683E+09 | 0.476679E+09 | 0.226130E+10 | 0.105931E+09 |
September | 0.881737E+09 | 0.425013E+09 | 0.456724E+09 | 0.172849E+10 | 0.165829E+09 |
October | 0.915174E+09 | 0.556969E+09 | 0.358206E+09 | 0.143655E+10 | 0.563386E+09 |
November | 0.681017E+09 | 0.408823E+09 | 0.272193E+09 | 0.860663E+09 | 0.821064E+09 |
December | 0.641607E+09 | 0.387421E+09 | 0.254186E+09 | 0.706340E+09 | 0.111382E+10 |
Annual Sum or Average | 0.115854E+11 | 0.672196E+10 | 0.486345E+10 | 0.193466E+11 | 0.620069E+10 |
Minimum of Months | 0.641607E+09 | 0.370907E+09 | 0.254186E+09 | 0.706340E+09 | 81728513.93 |
Maximum of Months | 0.134056E+10 | 0.833005E+09 | 0.541179E+09 | 0.272005E+10 | 0.111382E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.728276E+09 | 0.456868E+09 | 0.271408E+09 | 0.923082E+09 | 0.917977E+09 |
February | 0.648388E+09 | 0.370907E+09 | 0.277480E+09 | 0.730446E+09 | 0.835530E+09 |
March | 0.898366E+09 | 0.462126E+09 | 0.436240E+09 | 0.116948E+10 | 0.791677E+09 |
April | 0.124100E+10 | 0.739653E+09 | 0.501349E+09 | 0.205696E+10 | 0.399491E+09 |
May | 0.132900E+10 | 0.787817E+09 | 0.541179E+09 | 0.234984E+10 | 0.297798E+09 |
June | 0.134056E+10 | 0.833005E+09 | 0.507554E+09 | 0.272005E+10 | 0.106458E+09 |
July | 0.116993E+10 | 0.659674E+09 | 0.510253E+09 | 0.240340E+10 | 81728513.93 |
August | 0.111036E+10 | 0.633683E+09 | 0.476679E+09 | 0.226130E+10 | 0.105931E+09 |
September | 0.881737E+09 | 0.425013E+09 | 0.456724E+09 | 0.172849E+10 | 0.165829E+09 |
October | 0.915174E+09 | 0.556969E+09 | 0.358206E+09 | 0.143655E+10 | 0.563386E+09 |
November | 0.681017E+09 | 0.408823E+09 | 0.272193E+09 | 0.860663E+09 | 0.821064E+09 |
December | 0.641607E+09 | 0.387421E+09 | 0.254186E+09 | 0.706340E+09 | 0.111382E+10 |
Annual Sum or Average | 0.115854E+11 | 0.672196E+10 | 0.486345E+10 | 0.193466E+11 | 0.620069E+10 |
Minimum of Months | 0.641607E+09 | 0.370907E+09 | 0.254186E+09 | 0.706340E+09 | 81728513.93 |
Maximum of Months | 0.134056E+10 | 0.833005E+09 | 0.541179E+09 | 0.272005E+10 | 0.111382E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.728263E+09 | 0.456860E+09 | 0.271403E+09 | 0.923065E+09 | 0.917960E+09 |
February | 0.648376E+09 | 0.370901E+09 | 0.277475E+09 | 0.730432E+09 | 0.835515E+09 |
March | 0.898350E+09 | 0.462118E+09 | 0.436232E+09 | 0.116946E+10 | 0.791662E+09 |
April | 0.124098E+10 | 0.739640E+09 | 0.501339E+09 | 0.205692E+10 | 0.399483E+09 |
May | 0.132897E+10 | 0.787803E+09 | 0.541169E+09 | 0.234980E+10 | 0.297793E+09 |
June | 0.134053E+10 | 0.832989E+09 | 0.507545E+09 | 0.272000E+10 | 0.106456E+09 |
July | 0.116991E+10 | 0.659662E+09 | 0.510243E+09 | 0.240336E+10 | 81727020.57 |
August | 0.111034E+10 | 0.633671E+09 | 0.476671E+09 | 0.226126E+10 | 0.105929E+09 |
September | 0.881721E+09 | 0.425005E+09 | 0.456716E+09 | 0.172846E+10 | 0.165826E+09 |
October | 0.915157E+09 | 0.556958E+09 | 0.358199E+09 | 0.143652E+10 | 0.563376E+09 |
November | 0.681004E+09 | 0.408816E+09 | 0.272188E+09 | 0.860648E+09 | 0.821049E+09 |
December | 0.641595E+09 | 0.387414E+09 | 0.254181E+09 | 0.706328E+09 | 0.111380E+10 |
Annual Sum or Average | 0.115852E+11 | 0.672184E+10 | 0.486336E+10 | 0.193462E+11 | 0.620057E+10 |
Minimum of Months | 0.641595E+09 | 0.370901E+09 | 0.254181E+09 | 0.706328E+09 | 81727020.57 |
Maximum of Months | 0.134053E+10 | 0.832989E+09 | 0.541169E+09 | 0.272000E+10 | 0.111380E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167061E+10 | 0.133427E+10 | 0.336343E+09 | 0.253784E+10 | 0.864754E+09 |
February | 0.954080E+09 | 0.643463E+09 | 0.310617E+09 | 0.130042E+10 | 0.759115E+09 |
March | 0.878924E+09 | 0.452690E+09 | 0.426234E+09 | 0.128634E+10 | 0.764626E+09 |
April | 0.724062E+09 | 0.292589E+09 | 0.431472E+09 | 0.135967E+10 | 0.417104E+09 |
May | 0.501372E+09 | 82831415.39 | 0.418541E+09 | 0.103838E+10 | 0.296347E+09 |
June | 0.415472E+09 | 32027021.88 | 0.383445E+09 | 0.113638E+10 | 0.108228E+09 |
July | 0.438690E+09 | 45385518.83 | 0.393305E+09 | 0.114634E+10 | 85132508.49 |
August | 0.533424E+09 | 0.147411E+09 | 0.386013E+09 | 0.132453E+10 | 0.113225E+09 |
September | 0.743816E+09 | 0.317329E+09 | 0.426488E+09 | 0.156158E+10 | 0.169392E+09 |
October | 0.122470E+10 | 0.847670E+09 | 0.377026E+09 | 0.204762E+10 | 0.544254E+09 |
November | 0.138119E+10 | 0.105792E+10 | 0.323272E+09 | 0.206927E+10 | 0.771033E+09 |
December | 0.155317E+10 | 0.122954E+10 | 0.323629E+09 | 0.224300E+10 | 0.103694E+10 |
Annual Sum or Average | 0.110195E+11 | 0.648312E+10 | 0.453639E+10 | 0.190514E+11 | 0.593015E+10 |
Minimum of Months | 0.415472E+09 | 32027021.88 | 0.310617E+09 | 0.103838E+10 | 85132508.49 |
Maximum of Months | 0.167061E+10 | 0.133427E+10 | 0.431472E+09 | 0.253784E+10 | 0.103694E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167060E+10 | 0.133426E+10 | 0.336341E+09 | 0.253782E+10 | 0.864753E+09 |
February | 0.954074E+09 | 0.643458E+09 | 0.310616E+09 | 0.130041E+10 | 0.759115E+09 |
March | 0.878918E+09 | 0.452686E+09 | 0.426232E+09 | 0.128633E+10 | 0.764625E+09 |
April | 0.724058E+09 | 0.292587E+09 | 0.431471E+09 | 0.135966E+10 | 0.417103E+09 |
May | 0.501370E+09 | 82830808.40 | 0.418539E+09 | 0.103838E+10 | 0.296346E+09 |
June | 0.415471E+09 | 32026787.19 | 0.383444E+09 | 0.113638E+10 | 0.108228E+09 |
July | 0.438688E+09 | 45385186.24 | 0.393303E+09 | 0.114634E+10 | 85132138.76 |
August | 0.533421E+09 | 0.147410E+09 | 0.386012E+09 | 0.132452E+10 | 0.113225E+09 |
September | 0.743812E+09 | 0.317326E+09 | 0.426485E+09 | 0.156157E+10 | 0.169392E+09 |
October | 0.122469E+10 | 0.847664E+09 | 0.377025E+09 | 0.204761E+10 | 0.544253E+09 |
November | 0.138118E+10 | 0.105791E+10 | 0.323271E+09 | 0.206925E+10 | 0.771033E+09 |
December | 0.155316E+10 | 0.122953E+10 | 0.323627E+09 | 0.224298E+10 | 0.103694E+10 |
Annual Sum or Average | 0.110194E+11 | 0.648307E+10 | 0.453636E+10 | 0.190513E+11 | 0.593014E+10 |
Minimum of Months | 0.415471E+09 | 32026787.19 | 0.310616E+09 | 0.103838E+10 | 85132138.76 |
Maximum of Months | 0.167060E+10 | 0.133426E+10 | 0.431471E+09 | 0.253782E+10 | 0.103694E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167061E+10 | 0.133427E+10 | 0.336343E+09 | 0.253784E+10 | 0.864754E+09 |
February | 0.954080E+09 | 0.643463E+09 | 0.310617E+09 | 0.130042E+10 | 0.759115E+09 |
March | 0.878924E+09 | 0.452690E+09 | 0.426234E+09 | 0.128634E+10 | 0.764626E+09 |
April | 0.724062E+09 | 0.292589E+09 | 0.431472E+09 | 0.135967E+10 | 0.417104E+09 |
May | 0.501372E+09 | 82831415.39 | 0.418541E+09 | 0.103838E+10 | 0.296347E+09 |
June | 0.415472E+09 | 32027021.88 | 0.383445E+09 | 0.113638E+10 | 0.108228E+09 |
July | 0.438690E+09 | 45385518.83 | 0.393305E+09 | 0.114634E+10 | 85132508.49 |
August | 0.533424E+09 | 0.147411E+09 | 0.386013E+09 | 0.132453E+10 | 0.113225E+09 |
September | 0.743816E+09 | 0.317329E+09 | 0.426488E+09 | 0.156158E+10 | 0.169392E+09 |
October | 0.122470E+10 | 0.847670E+09 | 0.377026E+09 | 0.204762E+10 | 0.544254E+09 |
November | 0.138119E+10 | 0.105792E+10 | 0.323272E+09 | 0.206927E+10 | 0.771033E+09 |
December | 0.155317E+10 | 0.122954E+10 | 0.323629E+09 | 0.224300E+10 | 0.103694E+10 |
Annual Sum or Average | 0.110195E+11 | 0.648312E+10 | 0.453639E+10 | 0.190514E+11 | 0.593015E+10 |
Minimum of Months | 0.415472E+09 | 32027021.88 | 0.310617E+09 | 0.103838E+10 | 85132508.49 |
Maximum of Months | 0.167061E+10 | 0.133427E+10 | 0.431472E+09 | 0.253784E+10 | 0.103694E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167060E+10 | 0.133426E+10 | 0.336341E+09 | 0.253782E+10 | 0.864753E+09 |
February | 0.954074E+09 | 0.643458E+09 | 0.310616E+09 | 0.130041E+10 | 0.759115E+09 |
March | 0.878918E+09 | 0.452686E+09 | 0.426232E+09 | 0.128633E+10 | 0.764625E+09 |
April | 0.724058E+09 | 0.292587E+09 | 0.431471E+09 | 0.135966E+10 | 0.417103E+09 |
May | 0.501370E+09 | 82830808.40 | 0.418539E+09 | 0.103838E+10 | 0.296346E+09 |
June | 0.415471E+09 | 32026787.19 | 0.383444E+09 | 0.113638E+10 | 0.108228E+09 |
July | 0.438688E+09 | 45385186.24 | 0.393303E+09 | 0.114634E+10 | 85132138.76 |
August | 0.533421E+09 | 0.147410E+09 | 0.386012E+09 | 0.132452E+10 | 0.113225E+09 |
September | 0.743812E+09 | 0.317326E+09 | 0.426485E+09 | 0.156157E+10 | 0.169392E+09 |
October | 0.122469E+10 | 0.847664E+09 | 0.377025E+09 | 0.204761E+10 | 0.544253E+09 |
November | 0.138118E+10 | 0.105791E+10 | 0.323271E+09 | 0.206925E+10 | 0.771033E+09 |
December | 0.155316E+10 | 0.122953E+10 | 0.323627E+09 | 0.224298E+10 | 0.103694E+10 |
Annual Sum or Average | 0.110194E+11 | 0.648307E+10 | 0.453636E+10 | 0.190513E+11 | 0.593014E+10 |
Minimum of Months | 0.415471E+09 | 32026787.19 | 0.310616E+09 | 0.103838E+10 | 85132138.76 |
Maximum of Months | 0.167060E+10 | 0.133426E+10 | 0.431471E+09 | 0.253782E+10 | 0.103694E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167054E+10 | 0.133421E+10 | 0.336328E+09 | 0.253773E+10 | 0.864719E+09 |
February | 0.954039E+09 | 0.643435E+09 | 0.310604E+09 | 0.130036E+10 | 0.759084E+09 |
March | 0.878886E+09 | 0.452670E+09 | 0.426216E+09 | 0.128628E+10 | 0.764595E+09 |
April | 0.724030E+09 | 0.292576E+09 | 0.431454E+09 | 0.135961E+10 | 0.417087E+09 |
May | 0.501351E+09 | 82827773.44 | 0.418523E+09 | 0.103834E+10 | 0.296335E+09 |
June | 0.415455E+09 | 32025613.71 | 0.383429E+09 | 0.113633E+10 | 0.108224E+09 |
July | 0.438671E+09 | 45383523.31 | 0.393288E+09 | 0.114630E+10 | 85128892.41 |
August | 0.533401E+09 | 0.147404E+09 | 0.385997E+09 | 0.132447E+10 | 0.113220E+09 |
September | 0.743784E+09 | 0.317315E+09 | 0.426469E+09 | 0.156151E+10 | 0.169385E+09 |
October | 0.122464E+10 | 0.847633E+09 | 0.377010E+09 | 0.204753E+10 | 0.544231E+09 |
November | 0.138113E+10 | 0.105787E+10 | 0.323259E+09 | 0.206918E+10 | 0.771002E+09 |
December | 0.155310E+10 | 0.122949E+10 | 0.323615E+09 | 0.224290E+10 | 0.103690E+10 |
Annual Sum or Average | 0.110190E+11 | 0.648284E+10 | 0.453619E+10 | 0.190505E+11 | 0.592991E+10 |
Minimum of Months | 0.415455E+09 | 32025613.71 | 0.310604E+09 | 0.103834E+10 | 85128892.41 |
Maximum of Months | 0.167054E+10 | 0.133421E+10 | 0.431454E+09 | 0.253773E+10 | 0.103690E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.761544E+09 | 0.473312E+09 | 0.288232E+09 | 0.107266E+10 | 0.107987E+10 |
February | 0.557222E+09 | 0.269383E+09 | 0.287839E+09 | 0.620234E+09 | 0.991510E+09 |
March | 0.817136E+09 | 0.389542E+09 | 0.427594E+09 | 0.105473E+10 | 0.966502E+09 |
April | 0.121426E+10 | 0.692653E+09 | 0.521611E+09 | 0.201573E+10 | 0.547182E+09 |
May | 0.125796E+10 | 0.705339E+09 | 0.552620E+09 | 0.225618E+10 | 0.380925E+09 |
June | 0.129420E+10 | 0.761196E+09 | 0.533000E+09 | 0.261805E+10 | 0.164061E+09 |
July | 0.973344E+09 | 0.454354E+09 | 0.518991E+09 | 0.200979E+10 | 0.138339E+09 |
August | 0.928171E+09 | 0.466146E+09 | 0.462025E+09 | 0.189736E+10 | 0.187340E+09 |
September | 0.782955E+09 | 0.328966E+09 | 0.453989E+09 | 0.155040E+10 | 0.217166E+09 |
October | 0.827831E+09 | 0.473352E+09 | 0.354479E+09 | 0.131575E+10 | 0.694560E+09 |
November | 0.737858E+09 | 0.445497E+09 | 0.292361E+09 | 0.100065E+10 | 0.101737E+10 |
December | 0.614505E+09 | 0.349880E+09 | 0.264625E+09 | 0.742105E+09 | 0.139313E+10 |
Annual Sum or Average | 0.107670E+11 | 0.580962E+10 | 0.495737E+10 | 0.181536E+11 | 0.777796E+10 |
Minimum of Months | 0.557222E+09 | 0.269383E+09 | 0.264625E+09 | 0.620234E+09 | 0.138339E+09 |
Maximum of Months | 0.129420E+10 | 0.761196E+09 | 0.552620E+09 | 0.261805E+10 | 0.139313E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.761544E+09 | 0.473312E+09 | 0.288232E+09 | 0.107266E+10 | 0.107987E+10 |
February | 0.557222E+09 | 0.269383E+09 | 0.287839E+09 | 0.620234E+09 | 0.991510E+09 |
March | 0.817136E+09 | 0.389542E+09 | 0.427594E+09 | 0.105473E+10 | 0.966502E+09 |
April | 0.121426E+10 | 0.692653E+09 | 0.521611E+09 | 0.201573E+10 | 0.547182E+09 |
May | 0.125796E+10 | 0.705339E+09 | 0.552620E+09 | 0.225618E+10 | 0.380925E+09 |
June | 0.129420E+10 | 0.761196E+09 | 0.533000E+09 | 0.261805E+10 | 0.164061E+09 |
July | 0.973344E+09 | 0.454354E+09 | 0.518991E+09 | 0.200979E+10 | 0.138339E+09 |
August | 0.928171E+09 | 0.466146E+09 | 0.462025E+09 | 0.189736E+10 | 0.187340E+09 |
September | 0.782955E+09 | 0.328966E+09 | 0.453989E+09 | 0.155040E+10 | 0.217166E+09 |
October | 0.827831E+09 | 0.473352E+09 | 0.354479E+09 | 0.131575E+10 | 0.694560E+09 |
November | 0.737858E+09 | 0.445497E+09 | 0.292361E+09 | 0.100065E+10 | 0.101737E+10 |
December | 0.614505E+09 | 0.349880E+09 | 0.264625E+09 | 0.742105E+09 | 0.139313E+10 |
Annual Sum or Average | 0.107670E+11 | 0.580962E+10 | 0.495737E+10 | 0.181536E+11 | 0.777796E+10 |
Minimum of Months | 0.557222E+09 | 0.269383E+09 | 0.264625E+09 | 0.620234E+09 | 0.138339E+09 |
Maximum of Months | 0.129420E+10 | 0.761196E+09 | 0.552620E+09 | 0.261805E+10 | 0.139313E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.761530E+09 | 0.473303E+09 | 0.288227E+09 | 0.107264E+10 | 0.107985E+10 |
February | 0.557212E+09 | 0.269378E+09 | 0.287834E+09 | 0.620223E+09 | 0.991492E+09 |
March | 0.817121E+09 | 0.389535E+09 | 0.427587E+09 | 0.105471E+10 | 0.966484E+09 |
April | 0.121424E+10 | 0.692640E+09 | 0.521601E+09 | 0.201569E+10 | 0.547172E+09 |
May | 0.125794E+10 | 0.705327E+09 | 0.552610E+09 | 0.225614E+10 | 0.380918E+09 |
June | 0.129417E+10 | 0.761182E+09 | 0.532990E+09 | 0.261800E+10 | 0.164058E+09 |
July | 0.973326E+09 | 0.454345E+09 | 0.518981E+09 | 0.200976E+10 | 0.138337E+09 |
August | 0.928154E+09 | 0.466138E+09 | 0.462016E+09 | 0.189733E+10 | 0.187337E+09 |
September | 0.782941E+09 | 0.328960E+09 | 0.453981E+09 | 0.155037E+10 | 0.217162E+09 |
October | 0.827815E+09 | 0.473343E+09 | 0.354472E+09 | 0.131573E+10 | 0.694547E+09 |
November | 0.737844E+09 | 0.445489E+09 | 0.292355E+09 | 0.100063E+10 | 0.101735E+10 |
December | 0.614494E+09 | 0.349874E+09 | 0.264620E+09 | 0.742092E+09 | 0.139311E+10 |
Annual Sum or Average | 0.107668E+11 | 0.580951E+10 | 0.495728E+10 | 0.181533E+11 | 0.777782E+10 |
Minimum of Months | 0.557212E+09 | 0.269378E+09 | 0.264620E+09 | 0.620223E+09 | 0.138337E+09 |
Maximum of Months | 0.129417E+10 | 0.761182E+09 | 0.552610E+09 | 0.261800E+10 | 0.139311E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101447E+10 | 0.00 | 0.101447E+10 | 0.874467E+09 | 0.404030E+10 |
February | 0.104409E+10 | 0.00 | 0.104409E+10 | 0.548158E+09 | 0.361416E+10 |
March | 0.153627E+10 | 0.00 | 0.153627E+10 | 0.148469E+10 | 0.357422E+10 |
April | 0.181134E+10 | 18797044.85 | 0.179254E+10 | 0.304847E+10 | 0.188684E+10 |
May | 0.219104E+10 | 0.175438E+09 | 0.201560E+10 | 0.428801E+10 | 0.131521E+10 |
June | 0.246400E+10 | 0.447683E+09 | 0.201631E+10 | 0.640118E+10 | 0.515300E+09 |
July | 0.217137E+10 | 0.226213E+09 | 0.194515E+10 | 0.565532E+10 | 0.410516E+09 |
August | 0.175268E+10 | 43540774.45 | 0.170914E+10 | 0.468451E+10 | 0.518137E+09 |
September | 0.160029E+10 | 427199.43 | 0.159986E+10 | 0.377884E+10 | 0.787653E+09 |
October | 0.127938E+10 | 0.00 | 0.127938E+10 | 0.192304E+10 | 0.256608E+10 |
November | 0.103157E+10 | 0.00 | 0.103157E+10 | 0.836877E+09 | 0.362157E+10 |
December | 0.947605E+09 | 0.00 | 0.947605E+09 | 0.547179E+09 | 0.488415E+10 |
Annual Sum or Average | 0.188441E+11 | 0.912100E+09 | 0.179320E+11 | 0.340707E+11 | 0.277341E+11 |
Minimum of Months | 0.947605E+09 | 0.00 | 0.947605E+09 | 0.547179E+09 | 0.410516E+09 |
Maximum of Months | 0.246400E+10 | 0.447683E+09 | 0.201631E+10 | 0.640118E+10 | 0.488415E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.218481E+10 | 0.137059E+10 | 0.814217E+09 | 0.282358E+10 | 0.256882E+10 |
February | 0.194514E+10 | 0.111271E+10 | 0.832432E+09 | 0.221855E+10 | 0.232318E+10 |
March | 0.269507E+10 | 0.138636E+10 | 0.130871E+10 | 0.351413E+10 | 0.228567E+10 |
April | 0.372297E+10 | 0.221894E+10 | 0.150403E+10 | 0.612981E+10 | 0.124345E+10 |
May | 0.398695E+10 | 0.236343E+10 | 0.162352E+10 | 0.701293E+10 | 0.909208E+09 |
June | 0.402164E+10 | 0.249899E+10 | 0.152265E+10 | 0.812832E+10 | 0.336703E+09 |
July | 0.350974E+10 | 0.197900E+10 | 0.153074E+10 | 0.717362E+10 | 0.271168E+09 |
August | 0.333105E+10 | 0.190103E+10 | 0.143002E+10 | 0.675720E+10 | 0.347491E+09 |
September | 0.264518E+10 | 0.127503E+10 | 0.137016E+10 | 0.516095E+10 | 0.513667E+09 |
October | 0.274549E+10 | 0.167089E+10 | 0.107461E+10 | 0.430237E+10 | 0.164485E+10 |
November | 0.204303E+10 | 0.122646E+10 | 0.816572E+09 | 0.261258E+10 | 0.231934E+10 |
December | 0.192480E+10 | 0.116225E+10 | 0.762549E+09 | 0.220955E+10 | 0.307677E+10 |
Annual Sum or Average | 0.347559E+11 | 0.201657E+11 | 0.145902E+11 | 0.580436E+11 | 0.178403E+11 |
Minimum of Months | 0.192480E+10 | 0.111271E+10 | 0.762549E+09 | 0.220955E+10 | 0.271168E+09 |
Maximum of Months | 0.402164E+10 | 0.249899E+10 | 0.162352E+10 | 0.812832E+10 | 0.307677E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.835320E+10 | 0.667147E+10 | 0.168173E+10 | 0.126009E+11 | 0.429250E+10 |
February | 0.477049E+10 | 0.321738E+10 | 0.155310E+10 | 0.646492E+10 | 0.368260E+10 |
March | 0.439469E+10 | 0.226350E+10 | 0.213119E+10 | 0.641052E+10 | 0.372372E+10 |
April | 0.362035E+10 | 0.146298E+10 | 0.215738E+10 | 0.680630E+10 | 0.206931E+10 |
May | 0.250688E+10 | 0.414166E+09 | 0.209271E+10 | 0.523377E+10 | 0.146503E+10 |
June | 0.207737E+10 | 0.160138E+09 | 0.191723E+10 | 0.577399E+10 | 0.527525E+09 |
July | 0.219347E+10 | 0.226932E+09 | 0.196653E+10 | 0.581653E+10 | 0.415967E+09 |
August | 0.266715E+10 | 0.737069E+09 | 0.193008E+10 | 0.669247E+10 | 0.545284E+09 |
September | 0.371914E+10 | 0.158668E+10 | 0.213246E+10 | 0.779445E+10 | 0.849375E+09 |
October | 0.612359E+10 | 0.423844E+10 | 0.188515E+10 | 0.101741E+11 | 0.269119E+10 |
November | 0.690609E+10 | 0.528971E+10 | 0.161638E+10 | 0.102851E+11 | 0.377719E+10 |
December | 0.776599E+10 | 0.614783E+10 | 0.161816E+10 | 0.111880E+11 | 0.504930E+10 |
Annual Sum or Average | 0.550984E+11 | 0.324163E+11 | 0.226821E+11 | 0.952410E+11 | 0.290890E+11 |
Minimum of Months | 0.207737E+10 | 0.160138E+09 | 0.155310E+10 | 0.523377E+10 | 0.415967E+09 |
Maximum of Months | 0.835320E+10 | 0.667147E+10 | 0.215738E+10 | 0.126009E+11 | 0.504930E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228461E+10 | 0.141992E+10 | 0.864688E+09 | 0.330585E+10 | 0.292276E+10 |
February | 0.167165E+10 | 0.808141E+09 | 0.863510E+09 | 0.194721E+10 | 0.252755E+10 |
March | 0.245138E+10 | 0.116861E+10 | 0.128277E+10 | 0.328846E+10 | 0.251563E+10 |
April | 0.364275E+10 | 0.207794E+10 | 0.156482E+10 | 0.613722E+10 | 0.148516E+10 |
May | 0.377384E+10 | 0.211600E+10 | 0.165784E+10 | 0.679376E+10 | 0.109641E+10 |
June | 0.388255E+10 | 0.228356E+10 | 0.159898E+10 | 0.793275E+10 | 0.442079E+09 |
July | 0.292000E+10 | 0.136305E+10 | 0.155696E+10 | 0.616530E+10 | 0.344018E+09 |
August | 0.278448E+10 | 0.139843E+10 | 0.138606E+10 | 0.584156E+10 | 0.432830E+09 |
September | 0.234884E+10 | 0.986888E+09 | 0.136195E+10 | 0.469572E+10 | 0.598665E+09 |
October | 0.248347E+10 | 0.142004E+10 | 0.106343E+10 | 0.402587E+10 | 0.185933E+10 |
November | 0.221355E+10 | 0.133648E+10 | 0.877073E+09 | 0.310515E+10 | 0.261142E+10 |
December | 0.184350E+10 | 0.104963E+10 | 0.793866E+09 | 0.238726E+10 | 0.346092E+10 |
Annual Sum or Average | 0.323006E+11 | 0.174287E+11 | 0.148719E+11 | 0.556261E+11 | 0.202968E+11 |
Minimum of Months | 0.167165E+10 | 0.808141E+09 | 0.793866E+09 | 0.194721E+10 | 0.344018E+09 |
Maximum of Months | 0.388255E+10 | 0.228356E+10 | 0.165784E+10 | 0.793275E+10 | 0.346092E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101447E+10 | 0.00 | 0.101447E+10 | 0.993735E+09 | 0.367067E+10 |
February | 0.104409E+10 | 0.00 | 0.104409E+10 | 0.643296E+09 | 0.321815E+10 |
March | 0.153627E+10 | 0.00 | 0.153627E+10 | 0.157790E+10 | 0.332834E+10 |
April | 0.181134E+10 | 18797044.85 | 0.179254E+10 | 0.302869E+10 | 0.185574E+10 |
May | 0.219104E+10 | 0.175438E+09 | 0.201560E+10 | 0.424147E+10 | 0.132533E+10 |
June | 0.246400E+10 | 0.447683E+09 | 0.201631E+10 | 0.631151E+10 | 0.541279E+09 |
July | 0.217137E+10 | 0.226213E+09 | 0.194515E+10 | 0.554980E+10 | 0.437126E+09 |
August | 0.175268E+10 | 43540774.45 | 0.170914E+10 | 0.460570E+10 | 0.539563E+09 |
September | 0.160029E+10 | 427199.43 | 0.159986E+10 | 0.372210E+10 | 0.806584E+09 |
October | 0.127938E+10 | 0.00 | 0.127938E+10 | 0.195977E+10 | 0.241882E+10 |
November | 0.103157E+10 | 0.00 | 0.103157E+10 | 0.932870E+09 | 0.329535E+10 |
December | 0.947605E+09 | 0.00 | 0.947605E+09 | 0.668176E+09 | 0.441105E+10 |
Annual Sum or Average | 0.188441E+11 | 0.912100E+09 | 0.179320E+11 | 0.342350E+11 | 0.258480E+11 |
Minimum of Months | 0.947605E+09 | 0.00 | 0.947605E+09 | 0.643296E+09 | 0.437126E+09 |
Maximum of Months | 0.246400E+10 | 0.447683E+09 | 0.201631E+10 | 0.631151E+10 | 0.441105E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.218481E+10 | 0.137059E+10 | 0.814217E+09 | 0.291596E+10 | 0.237643E+10 |
February | 0.194514E+10 | 0.111271E+10 | 0.832432E+09 | 0.229466E+10 | 0.210503E+10 |
March | 0.269507E+10 | 0.138636E+10 | 0.130871E+10 | 0.357027E+10 | 0.216553E+10 |
April | 0.372297E+10 | 0.221894E+10 | 0.150403E+10 | 0.610085E+10 | 0.124022E+10 |
May | 0.398695E+10 | 0.236343E+10 | 0.162352E+10 | 0.696896E+10 | 0.918269E+09 |
June | 0.402164E+10 | 0.249899E+10 | 0.152265E+10 | 0.805761E+10 | 0.353409E+09 |
July | 0.350974E+10 | 0.197900E+10 | 0.153074E+10 | 0.709717E+10 | 0.288055E+09 |
August | 0.333105E+10 | 0.190103E+10 | 0.143002E+10 | 0.669604E+10 | 0.361693E+09 |
September | 0.264518E+10 | 0.127503E+10 | 0.137016E+10 | 0.511659E+10 | 0.527236E+09 |
October | 0.274549E+10 | 0.167089E+10 | 0.107461E+10 | 0.431398E+10 | 0.158039E+10 |
November | 0.204303E+10 | 0.122646E+10 | 0.816572E+09 | 0.268316E+10 | 0.214784E+10 |
December | 0.192480E+10 | 0.116225E+10 | 0.762549E+09 | 0.233476E+10 | 0.280697E+10 |
Annual Sum or Average | 0.347559E+11 | 0.201657E+11 | 0.145902E+11 | 0.581500E+11 | 0.168711E+11 |
Minimum of Months | 0.192480E+10 | 0.111271E+10 | 0.762549E+09 | 0.229466E+10 | 0.288055E+09 |
Maximum of Months | 0.402164E+10 | 0.249899E+10 | 0.162352E+10 | 0.805761E+10 | 0.280697E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.835320E+10 | 0.667147E+10 | 0.168173E+10 | 0.126895E+11 | 0.403690E+10 |
February | 0.477049E+10 | 0.321738E+10 | 0.155310E+10 | 0.655828E+10 | 0.336091E+10 |
March | 0.439469E+10 | 0.226350E+10 | 0.213119E+10 | 0.647633E+10 | 0.352279E+10 |
April | 0.362035E+10 | 0.146298E+10 | 0.215738E+10 | 0.677098E+10 | 0.204542E+10 |
May | 0.250688E+10 | 0.414166E+09 | 0.209271E+10 | 0.518669E+10 | 0.146685E+10 |
June | 0.207737E+10 | 0.160138E+09 | 0.191723E+10 | 0.568590E+10 | 0.547585E+09 |
July | 0.219347E+10 | 0.226932E+09 | 0.196653E+10 | 0.571606E+10 | 0.438599E+09 |
August | 0.266715E+10 | 0.737069E+09 | 0.193008E+10 | 0.661368E+10 | 0.564016E+09 |
September | 0.371914E+10 | 0.158668E+10 | 0.213246E+10 | 0.773287E+10 | 0.871244E+09 |
October | 0.612359E+10 | 0.423844E+10 | 0.188515E+10 | 0.101787E+11 | 0.259566E+10 |
November | 0.690609E+10 | 0.528971E+10 | 0.161638E+10 | 0.103588E+11 | 0.354882E+10 |
December | 0.776599E+10 | 0.614783E+10 | 0.161816E+10 | 0.113207E+11 | 0.468361E+10 |
Annual Sum or Average | 0.550984E+11 | 0.324163E+11 | 0.226821E+11 | 0.952884E+11 | 0.276824E+11 |
Minimum of Months | 0.207737E+10 | 0.160138E+09 | 0.155310E+10 | 0.518669E+10 | 0.438599E+09 |
Maximum of Months | 0.835320E+10 | 0.667147E+10 | 0.215738E+10 | 0.126895E+11 | 0.468361E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.228461E+10 | 0.141992E+10 | 0.864688E+09 | 0.335853E+10 | 0.272098E+10 |
February | 0.167165E+10 | 0.808141E+09 | 0.863510E+09 | 0.199340E+10 | 0.231091E+10 |
March | 0.245138E+10 | 0.116861E+10 | 0.128277E+10 | 0.333179E+10 | 0.238027E+10 |
April | 0.364275E+10 | 0.207794E+10 | 0.156482E+10 | 0.611176E+10 | 0.146698E+10 |
May | 0.377384E+10 | 0.211600E+10 | 0.165784E+10 | 0.675608E+10 | 0.109629E+10 |
June | 0.388255E+10 | 0.228356E+10 | 0.159898E+10 | 0.787320E+10 | 0.451935E+09 |
July | 0.292000E+10 | 0.136305E+10 | 0.155696E+10 | 0.610632E+10 | 0.355142E+09 |
August | 0.278448E+10 | 0.139843E+10 | 0.138606E+10 | 0.579362E+10 | 0.441238E+09 |
September | 0.234884E+10 | 0.986888E+09 | 0.136195E+10 | 0.466018E+10 | 0.606875E+09 |
October | 0.248347E+10 | 0.142004E+10 | 0.106343E+10 | 0.403412E+10 | 0.178015E+10 |
November | 0.221355E+10 | 0.133648E+10 | 0.877073E+09 | 0.314762E+10 | 0.243375E+10 |
December | 0.184350E+10 | 0.104963E+10 | 0.793866E+09 | 0.245191E+10 | 0.319457E+10 |
Annual Sum or Average | 0.323006E+11 | 0.174287E+11 | 0.148719E+11 | 0.556185E+11 | 0.192391E+11 |
Minimum of Months | 0.167165E+10 | 0.808141E+09 | 0.793866E+09 | 0.199340E+10 | 0.355142E+09 |
Maximum of Months | 0.388255E+10 | 0.228356E+10 | 0.165784E+10 | 0.787320E+10 | 0.319457E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 265.40 | 1684.57 | 378.75 | 0.00 | 378.75 | 0.00 | 0.00 |
February | 181.63 | 1694.64 | 431.58 | 0.00 | 431.58 | 0.00 | 0.00 |
March | 506.20 | 1463.55 | 573.57 | 0.00 | 573.57 | 0.00 | 0.00 |
April | 1136.74 | 756.89 | 698.81 | 7.25 | 691.56 | 0.00 | 0.00 |
May | 1577.32 | 499.23 | 818.03 | 65.50 | 752.53 | 0.00 | 0.00 |
June | 2440.53 | 199.10 | 950.60 | 172.71 | 777.89 | 0.00 | 0.00 |
July | 2078.41 | 154.77 | 810.68 | 84.46 | 726.23 | 0.00 | 0.00 |
August | 1707.39 | 203.33 | 654.37 | 16.26 | 638.11 | 0.00 | 0.00 |
September | 1436.82 | 310.11 | 617.39 | 0.16 | 617.22 | 0.00 | 0.00 |
October | 679.50 | 1036.35 | 477.66 | 0.00 | 477.66 | 0.00 | 0.00 |
November | 272.05 | 1569.50 | 397.98 | 0.00 | 397.98 | 0.00 | 0.00 |
December | 135.37 | 2101.11 | 353.79 | 0.00 | 353.79 | 0.00 | 0.00 |
Annual Sum or Average | 1038.65 | 969.72 | 597.53 | 28.92 | 568.61 | 0.00 | 0.00 |
Minimum of Months | 135.37 | 154.77 | 353.79 | 0.00 | 353.79 | 0.00 | 0.00 |
Maximum of Months | 2440.53 | 2101.11 | 950.60 | 172.71 | 777.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1033.91 | 1028.19 | 815.72 | 511.72 | 303.99 | 0.00 | 0.00 |
February | 905.81 | 1036.12 | 804.05 | 459.95 | 344.10 | 0.00 | 0.00 |
March | 1309.89 | 886.73 | 1006.23 | 517.61 | 488.62 | 0.00 | 0.00 |
April | 2380.72 | 462.37 | 1436.34 | 856.07 | 580.26 | 0.00 | 0.00 |
May | 2631.97 | 333.55 | 1488.56 | 882.41 | 606.16 | 0.00 | 0.00 |
June | 3148.18 | 123.21 | 1551.56 | 964.12 | 587.44 | 0.00 | 0.00 |
July | 2691.96 | 91.54 | 1310.39 | 738.88 | 571.52 | 0.00 | 0.00 |
August | 2532.80 | 118.65 | 1243.68 | 709.77 | 533.91 | 0.00 | 0.00 |
September | 2000.56 | 191.93 | 1020.52 | 491.91 | 528.61 | 0.00 | 0.00 |
October | 1609.03 | 631.03 | 1025.05 | 623.84 | 401.21 | 0.00 | 0.00 |
November | 996.13 | 950.30 | 788.21 | 473.17 | 315.04 | 0.00 | 0.00 |
December | 791.15 | 1247.55 | 718.64 | 433.94 | 284.70 | 0.00 | 0.00 |
Annual Sum or Average | 1840.42 | 589.86 | 1102.11 | 639.45 | 462.65 | 0.00 | 0.00 |
Minimum of Months | 791.15 | 91.54 | 718.64 | 433.94 | 284.70 | 0.00 | 0.00 |
Maximum of Months | 3148.18 | 1247.55 | 1551.56 | 964.12 | 606.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4737.55 | 1614.30 | 3118.63 | 2490.76 | 627.87 | 0.00 | 0.00 |
February | 2687.68 | 1568.92 | 1971.87 | 1329.89 | 641.98 | 0.00 | 0.00 |
March | 2401.29 | 1427.38 | 1640.74 | 845.06 | 795.68 | 0.00 | 0.00 |
April | 2622.78 | 804.59 | 1396.71 | 564.40 | 832.31 | 0.00 | 0.00 |
May | 1938.42 | 553.21 | 935.95 | 154.63 | 781.32 | 0.00 | 0.00 |
June | 2192.07 | 208.77 | 801.44 | 61.78 | 739.66 | 0.00 | 0.00 |
July | 2139.96 | 158.92 | 818.93 | 84.72 | 734.21 | 0.00 | 0.00 |
August | 2472.58 | 211.36 | 995.78 | 275.18 | 720.60 | 0.00 | 0.00 |
September | 3012.27 | 326.76 | 1434.82 | 612.12 | 822.69 | 0.00 | 0.00 |
October | 3822.43 | 1016.00 | 2286.22 | 1582.40 | 703.82 | 0.00 | 0.00 |
November | 3991.60 | 1487.32 | 2664.31 | 2040.72 | 623.59 | 0.00 | 0.00 |
December | 4187.15 | 1935.73 | 2899.40 | 2295.26 | 604.14 | 0.00 | 0.00 |
Annual Sum or Average | 3020.54 | 940.21 | 1747.11 | 1027.88 | 719.23 | 0.00 | 0.00 |
Minimum of Months | 1938.42 | 158.92 | 801.44 | 61.78 | 604.14 | 0.00 | 0.00 |
Maximum of Months | 4737.55 | 1935.73 | 3118.63 | 2490.76 | 832.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1201.45 | 1209.53 | 852.98 | 530.14 | 322.84 | 0.00 | 0.00 |
February | 769.13 | 1229.54 | 691.00 | 334.05 | 356.94 | 0.00 | 0.00 |
March | 1181.36 | 1082.55 | 915.25 | 436.31 | 478.93 | 0.00 | 0.00 |
April | 2333.01 | 633.31 | 1405.39 | 801.68 | 603.71 | 0.00 | 0.00 |
May | 2527.06 | 426.66 | 1409.00 | 790.03 | 618.97 | 0.00 | 0.00 |
June | 3030.13 | 189.88 | 1497.90 | 881.01 | 616.89 | 0.00 | 0.00 |
July | 2251.10 | 154.95 | 1090.21 | 508.91 | 581.30 | 0.00 | 0.00 |
August | 2125.17 | 209.83 | 1039.61 | 522.11 | 517.50 | 0.00 | 0.00 |
September | 1794.43 | 251.35 | 906.19 | 380.75 | 525.45 | 0.00 | 0.00 |
October | 1473.73 | 777.95 | 927.22 | 530.18 | 397.04 | 0.00 | 0.00 |
November | 1158.15 | 1177.50 | 854.00 | 515.62 | 338.38 | 0.00 | 0.00 |
December | 831.21 | 1560.40 | 688.29 | 391.89 | 296.40 | 0.00 | 0.00 |
Annual Sum or Average | 1726.93 | 739.91 | 1024.25 | 552.66 | 471.59 | 0.00 | 0.00 |
Minimum of Months | 769.13 | 154.95 | 688.29 | 334.05 | 296.40 | 0.00 | 0.00 |
Maximum of Months | 3030.13 | 1560.40 | 1497.90 | 881.01 | 618.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 326.49 | 1508.47 | 378.76 | 0.00 | 378.76 | 0.00 | 0.00 |
February | 226.59 | 1493.95 | 431.59 | 0.00 | 431.59 | 0.00 | 0.00 |
March | 554.32 | 1334.46 | 573.58 | 0.00 | 573.58 | 0.00 | 0.00 |
April | 1176.11 | 727.95 | 698.82 | 7.25 | 691.57 | 0.00 | 0.00 |
May | 1600.96 | 491.04 | 818.04 | 65.50 | 752.54 | 0.00 | 0.00 |
June | 2469.59 | 198.80 | 950.62 | 172.72 | 777.90 | 0.00 | 0.00 |
July | 2111.46 | 153.27 | 810.70 | 84.46 | 726.24 | 0.00 | 0.00 |
August | 1749.00 | 193.45 | 654.38 | 16.26 | 638.12 | 0.00 | 0.00 |
September | 1457.88 | 303.88 | 617.40 | 0.16 | 617.23 | 0.00 | 0.00 |
October | 717.98 | 958.06 | 477.66 | 0.00 | 477.66 | 0.00 | 0.00 |
November | 322.87 | 1397.21 | 397.98 | 0.00 | 397.98 | 0.00 | 0.00 |
December | 204.29 | 1823.53 | 353.80 | 0.00 | 353.80 | 0.00 | 0.00 |
Annual Sum or Average | 1080.38 | 879.44 | 597.54 | 28.92 | 568.62 | 0.00 | 0.00 |
Minimum of Months | 204.29 | 153.27 | 353.80 | 0.00 | 353.80 | 0.00 | 0.00 |
Maximum of Months | 2469.59 | 1823.53 | 950.62 | 172.72 | 777.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1054.21 | 959.09 | 815.71 | 511.72 | 303.99 | 0.00 | 0.00 |
February | 917.06 | 960.31 | 804.04 | 459.95 | 344.09 | 0.00 | 0.00 |
March | 1312.03 | 853.37 | 1006.22 | 517.61 | 488.61 | 0.00 | 0.00 |
April | 2364.89 | 479.73 | 1436.33 | 856.07 | 580.26 | 0.00 | 0.00 |
May | 2618.33 | 339.46 | 1488.56 | 882.40 | 606.15 | 0.00 | 0.00 |
June | 3135.92 | 129.90 | 1551.56 | 964.12 | 587.44 | 0.00 | 0.00 |
July | 2678.32 | 101.24 | 1310.39 | 738.87 | 571.51 | 0.00 | 0.00 |
August | 2522.85 | 129.74 | 1243.67 | 709.76 | 533.91 | 0.00 | 0.00 |
September | 1991.11 | 198.17 | 1020.52 | 491.91 | 528.61 | 0.00 | 0.00 |
October | 1606.32 | 614.12 | 1025.05 | 623.84 | 401.21 | 0.00 | 0.00 |
November | 1007.94 | 894.81 | 788.21 | 473.17 | 315.04 | 0.00 | 0.00 |
December | 824.95 | 1148.74 | 718.64 | 433.93 | 284.70 | 0.00 | 0.00 |
Annual Sum or Average | 1840.55 | 565.71 | 1102.10 | 639.45 | 462.65 | 0.00 | 0.00 |
Minimum of Months | 824.95 | 101.24 | 718.64 | 433.93 | 284.70 | 0.00 | 0.00 |
Maximum of Months | 3135.92 | 1148.74 | 1551.56 | 964.12 | 606.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4704.65 | 1602.64 | 3118.73 | 2490.84 | 627.89 | 0.00 | 0.00 |
February | 2672.34 | 1522.24 | 1971.93 | 1329.94 | 641.99 | 0.00 | 0.00 |
March | 2393.42 | 1390.28 | 1640.79 | 845.09 | 795.70 | 0.00 | 0.00 |
April | 2625.89 | 798.35 | 1396.74 | 564.42 | 832.32 | 0.00 | 0.00 |
May | 1954.07 | 546.98 | 935.96 | 154.63 | 781.33 | 0.00 | 0.00 |
June | 2227.62 | 203.52 | 801.45 | 61.78 | 739.67 | 0.00 | 0.00 |
July | 2171.64 | 155.30 | 818.95 | 84.73 | 734.22 | 0.00 | 0.00 |
August | 2498.68 | 203.59 | 995.80 | 275.19 | 720.61 | 0.00 | 0.00 |
September | 3007.12 | 327.69 | 1434.85 | 612.14 | 822.71 | 0.00 | 0.00 |
October | 3798.57 | 1004.78 | 2286.29 | 1582.45 | 703.84 | 0.00 | 0.00 |
November | 3968.01 | 1457.25 | 2664.39 | 2040.78 | 623.60 | 0.00 | 0.00 |
December | 4177.11 | 1885.19 | 2899.49 | 2295.34 | 604.15 | 0.00 | 0.00 |
Annual Sum or Average | 3020.07 | 922.41 | 1747.16 | 1027.91 | 719.25 | 0.00 | 0.00 |
Minimum of Months | 1954.07 | 155.30 | 801.45 | 61.78 | 604.15 | 0.00 | 0.00 |
Maximum of Months | 4704.65 | 1885.19 | 3118.73 | 2490.84 | 832.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1234.26 | 1091.23 | 852.98 | 530.14 | 322.84 | 0.00 | 0.00 |
February | 804.90 | 1044.79 | 690.99 | 334.05 | 356.94 | 0.00 | 0.00 |
March | 1227.77 | 939.23 | 915.24 | 436.31 | 478.93 | 0.00 | 0.00 |
April | 2367.75 | 572.98 | 1405.38 | 801.67 | 603.71 | 0.00 | 0.00 |
May | 2536.50 | 409.35 | 1408.99 | 790.02 | 618.97 | 0.00 | 0.00 |
June | 3060.47 | 170.56 | 1497.90 | 881.00 | 616.89 | 0.00 | 0.00 |
July | 2301.86 | 128.44 | 1090.20 | 508.90 | 581.30 | 0.00 | 0.00 |
August | 2180.99 | 161.60 | 1039.61 | 522.11 | 517.50 | 0.00 | 0.00 |
September | 1811.62 | 230.97 | 906.19 | 380.74 | 525.45 | 0.00 | 0.00 |
October | 1503.09 | 694.20 | 927.22 | 530.18 | 397.04 | 0.00 | 0.00 |
November | 1197.98 | 1007.49 | 853.99 | 515.62 | 338.38 | 0.00 | 0.00 |
December | 891.30 | 1292.16 | 688.28 | 391.89 | 296.40 | 0.00 | 0.00 |
Annual Sum or Average | 1763.89 | 643.61 | 1024.25 | 552.66 | 471.59 | 0.00 | 0.00 |
Minimum of Months | 804.90 | 128.44 | 688.28 | 334.05 | 296.40 | 0.00 | 0.00 |
Maximum of Months | 3060.47 | 1292.16 | 1497.90 | 881.00 | 618.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 371.02 | 1370.47 | 378.76 | 0.00 | 378.76 | 0.00 | 0.00 |
February | 265.91 | 1330.25 | 431.59 | 0.00 | 431.59 | 0.00 | 0.00 |
March | 589.12 | 1242.66 | 573.58 | 0.00 | 573.58 | 0.00 | 0.00 |
April | 1168.48 | 715.95 | 698.82 | 7.25 | 691.57 | 0.00 | 0.00 |
May | 1583.58 | 494.82 | 818.04 | 65.50 | 752.54 | 0.00 | 0.00 |
June | 2435.00 | 208.83 | 950.62 | 172.72 | 777.90 | 0.00 | 0.00 |
July | 2072.06 | 163.20 | 810.70 | 84.46 | 726.24 | 0.00 | 0.00 |
August | 1719.57 | 201.45 | 654.38 | 16.26 | 638.12 | 0.00 | 0.00 |
September | 1436.00 | 311.18 | 617.40 | 0.16 | 617.23 | 0.00 | 0.00 |
October | 731.70 | 903.08 | 477.66 | 0.00 | 477.66 | 0.00 | 0.00 |
November | 359.90 | 1271.35 | 397.98 | 0.00 | 397.98 | 0.00 | 0.00 |
December | 249.47 | 1646.90 | 353.80 | 0.00 | 353.80 | 0.00 | 0.00 |
Annual Sum or Average | 1085.59 | 819.63 | 597.54 | 28.92 | 568.62 | 0.00 | 0.00 |
Minimum of Months | 249.47 | 163.20 | 353.80 | 0.00 | 353.80 | 0.00 | 0.00 |
Maximum of Months | 2435.00 | 1646.90 | 950.62 | 172.72 | 777.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1088.69 | 887.26 | 815.71 | 511.72 | 303.99 | 0.00 | 0.00 |
February | 948.52 | 870.14 | 804.04 | 459.95 | 344.09 | 0.00 | 0.00 |
March | 1332.99 | 808.52 | 1006.22 | 517.61 | 488.61 | 0.00 | 0.00 |
April | 2353.72 | 478.48 | 1436.33 | 856.07 | 580.26 | 0.00 | 0.00 |
May | 2601.91 | 342.84 | 1488.56 | 882.40 | 606.15 | 0.00 | 0.00 |
June | 3108.64 | 136.35 | 1551.56 | 964.12 | 587.44 | 0.00 | 0.00 |
July | 2649.78 | 107.55 | 1310.39 | 738.87 | 571.51 | 0.00 | 0.00 |
August | 2500.01 | 135.04 | 1243.67 | 709.76 | 533.91 | 0.00 | 0.00 |
September | 1973.99 | 203.41 | 1020.52 | 491.91 | 528.61 | 0.00 | 0.00 |
October | 1610.66 | 590.05 | 1025.05 | 623.84 | 401.21 | 0.00 | 0.00 |
November | 1035.17 | 828.64 | 788.21 | 473.17 | 315.04 | 0.00 | 0.00 |
December | 871.70 | 1048.00 | 718.64 | 433.93 | 284.70 | 0.00 | 0.00 |
Annual Sum or Average | 1843.92 | 534.98 | 1102.10 | 639.45 | 462.65 | 0.00 | 0.00 |
Minimum of Months | 871.70 | 107.55 | 718.64 | 433.93 | 284.70 | 0.00 | 0.00 |
Maximum of Months | 3108.64 | 1048.00 | 1551.56 | 964.12 | 606.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4737.71 | 1507.20 | 3118.73 | 2490.84 | 627.89 | 0.00 | 0.00 |
February | 2710.93 | 1389.27 | 1971.93 | 1329.94 | 641.99 | 0.00 | 0.00 |
March | 2417.98 | 1315.26 | 1640.79 | 845.09 | 795.70 | 0.00 | 0.00 |
April | 2612.26 | 789.13 | 1396.74 | 564.42 | 832.32 | 0.00 | 0.00 |
May | 1936.49 | 547.66 | 935.96 | 154.63 | 781.33 | 0.00 | 0.00 |
June | 2193.64 | 211.26 | 801.45 | 61.78 | 739.67 | 0.00 | 0.00 |
July | 2134.13 | 163.75 | 818.95 | 84.73 | 734.22 | 0.00 | 0.00 |
August | 2469.27 | 210.58 | 995.80 | 275.19 | 720.61 | 0.00 | 0.00 |
September | 2983.36 | 336.13 | 1434.85 | 612.14 | 822.71 | 0.00 | 0.00 |
October | 3800.28 | 969.11 | 2286.29 | 1582.45 | 703.84 | 0.00 | 0.00 |
November | 3996.43 | 1369.14 | 2664.39 | 2040.78 | 623.60 | 0.00 | 0.00 |
December | 4226.68 | 1748.66 | 2899.49 | 2295.34 | 604.15 | 0.00 | 0.00 |
Annual Sum or Average | 3021.58 | 877.80 | 1747.16 | 1027.91 | 719.25 | 0.00 | 0.00 |
Minimum of Months | 1936.49 | 163.75 | 801.45 | 61.78 | 604.15 | 0.00 | 0.00 |
Maximum of Months | 4737.71 | 1748.66 | 3118.73 | 2490.84 | 832.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1253.93 | 1015.90 | 852.98 | 530.14 | 322.84 | 0.00 | 0.00 |
February | 823.99 | 955.24 | 690.99 | 334.05 | 356.94 | 0.00 | 0.00 |
March | 1243.95 | 888.69 | 915.24 | 436.31 | 478.93 | 0.00 | 0.00 |
April | 2357.93 | 565.97 | 1405.38 | 801.67 | 603.71 | 0.00 | 0.00 |
May | 2522.43 | 409.31 | 1408.99 | 790.02 | 618.97 | 0.00 | 0.00 |
June | 3037.50 | 174.36 | 1497.90 | 881.00 | 616.89 | 0.00 | 0.00 |
July | 2279.84 | 132.59 | 1090.20 | 508.90 | 581.30 | 0.00 | 0.00 |
August | 2163.09 | 164.74 | 1039.61 | 522.11 | 517.50 | 0.00 | 0.00 |
September | 1797.91 | 234.13 | 906.19 | 380.74 | 525.45 | 0.00 | 0.00 |
October | 1506.17 | 664.63 | 927.22 | 530.18 | 397.04 | 0.00 | 0.00 |
November | 1214.36 | 938.95 | 853.99 | 515.62 | 338.38 | 0.00 | 0.00 |
December | 915.44 | 1192.71 | 688.28 | 391.89 | 296.40 | 0.00 | 0.00 |
Annual Sum or Average | 1763.65 | 610.07 | 1024.25 | 552.66 | 471.59 | 0.00 | 0.00 |
Minimum of Months | 823.99 | 132.59 | 688.28 | 334.05 | 296.40 | 0.00 | 0.00 |
Maximum of Months | 3037.50 | 1192.71 | 1497.90 | 881.00 | 618.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.710857E+09 | 0.451194E+10 | 0.101445E+10 | 0.00 | 0.101445E+10 | 0.00 | 0.00 |
February | 0.439399E+09 | 0.409968E+10 | 0.104408E+10 | 0.00 | 0.104408E+10 | 0.00 | 0.00 |
March | 0.135581E+10 | 0.391998E+10 | 0.153624E+10 | 0.00 | 0.153624E+10 | 0.00 | 0.00 |
April | 0.294642E+10 | 0.196186E+10 | 0.181132E+10 | 18796484.29 | 0.179252E+10 | 0.00 | 0.00 |
May | 0.422470E+10 | 0.133713E+10 | 0.219101E+10 | 0.175433E+09 | 0.201558E+10 | 0.00 | 0.00 |
June | 0.632585E+10 | 0.516074E+09 | 0.246396E+10 | 0.447670E+09 | 0.201629E+10 | 0.00 | 0.00 |
July | 0.556682E+10 | 0.414543E+09 | 0.217133E+10 | 0.226207E+09 | 0.194513E+10 | 0.00 | 0.00 |
August | 0.457307E+10 | 0.544600E+09 | 0.175266E+10 | 43539475.99 | 0.170912E+10 | 0.00 | 0.00 |
September | 0.372423E+10 | 0.803795E+09 | 0.160026E+10 | 427186.69 | 0.159984E+10 | 0.00 | 0.00 |
October | 0.181997E+10 | 0.277575E+10 | 0.127936E+10 | 0.00 | 0.127936E+10 | 0.00 | 0.00 |
November | 0.705148E+09 | 0.406815E+10 | 0.103156E+10 | 0.00 | 0.103156E+10 | 0.00 | 0.00 |
December | 0.362586E+09 | 0.562762E+10 | 0.947591E+09 | 0.00 | 0.947591E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.327549E+11 | 0.305811E+11 | 0.188438E+11 | 0.912073E+09 | 0.179317E+11 | 0.00 | 0.00 |
Minimum of Months | 0.362586E+09 | 0.414543E+09 | 0.947591E+09 | 0.00 | 0.947591E+09 | 0.00 | 0.00 |
Maximum of Months | 0.632585E+10 | 0.562762E+10 | 0.246396E+10 | 0.447670E+09 | 0.201629E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.276923E+10 | 0.275391E+10 | 0.218482E+10 | 0.137060E+10 | 0.814220E+09 | 0.00 | 0.00 |
February | 0.219132E+10 | 0.250658E+10 | 0.194515E+10 | 0.111272E+10 | 0.832436E+09 | 0.00 | 0.00 |
March | 0.350842E+10 | 0.237502E+10 | 0.269508E+10 | 0.138637E+10 | 0.130871E+10 | 0.00 | 0.00 |
April | 0.617083E+10 | 0.119846E+10 | 0.372298E+10 | 0.221895E+10 | 0.150404E+10 | 0.00 | 0.00 |
May | 0.704948E+10 | 0.893389E+09 | 0.398696E+10 | 0.236344E+10 | 0.162353E+10 | 0.00 | 0.00 |
June | 0.816010E+10 | 0.319372E+09 | 0.402165E+10 | 0.249900E+10 | 0.152265E+10 | 0.00 | 0.00 |
July | 0.721016E+10 | 0.245184E+09 | 0.350976E+10 | 0.197901E+10 | 0.153075E+10 | 0.00 | 0.00 |
August | 0.678386E+10 | 0.317792E+09 | 0.333107E+10 | 0.190104E+10 | 0.143003E+10 | 0.00 | 0.00 |
September | 0.518544E+10 | 0.497483E+09 | 0.264519E+10 | 0.127503E+10 | 0.137016E+10 | 0.00 | 0.00 |
October | 0.430961E+10 | 0.169015E+10 | 0.274551E+10 | 0.167090E+10 | 0.107461E+10 | 0.00 | 0.00 |
November | 0.258197E+10 | 0.246318E+10 | 0.204304E+10 | 0.122646E+10 | 0.816575E+09 | 0.00 | 0.00 |
December | 0.211901E+10 | 0.334144E+10 | 0.192481E+10 | 0.116226E+10 | 0.762553E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.580394E+11 | 0.186020E+11 | 0.347560E+11 | 0.201658E+11 | 0.145903E+11 | 0.00 | 0.00 |
Minimum of Months | 0.211901E+10 | 0.245184E+09 | 0.192481E+10 | 0.111272E+10 | 0.762553E+09 | 0.00 | 0.00 |
Maximum of Months | 0.816010E+10 | 0.334144E+10 | 0.402165E+10 | 0.249900E+10 | 0.162353E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126890E+11 | 0.432373E+10 | 0.835295E+10 | 0.667125E+10 | 0.168170E+10 | 0.00 | 0.00 |
February | 0.650203E+10 | 0.379554E+10 | 0.477035E+10 | 0.321728E+10 | 0.155307E+10 | 0.00 | 0.00 |
March | 0.643162E+10 | 0.382310E+10 | 0.439457E+10 | 0.226342E+10 | 0.213115E+10 | 0.00 | 0.00 |
April | 0.679825E+10 | 0.208550E+10 | 0.362027E+10 | 0.146293E+10 | 0.215734E+10 | 0.00 | 0.00 |
May | 0.519185E+10 | 0.148172E+10 | 0.250684E+10 | 0.414152E+09 | 0.209268E+10 | 0.00 | 0.00 |
June | 0.568184E+10 | 0.541137E+09 | 0.207734E+10 | 0.160133E+09 | 0.191721E+10 | 0.00 | 0.00 |
July | 0.573167E+10 | 0.425658E+09 | 0.219343E+10 | 0.226925E+09 | 0.196650E+10 | 0.00 | 0.00 |
August | 0.662257E+10 | 0.566120E+09 | 0.266709E+10 | 0.737045E+09 | 0.193005E+10 | 0.00 | 0.00 |
September | 0.780780E+10 | 0.846953E+09 | 0.371904E+10 | 0.158663E+10 | 0.213242E+10 | 0.00 | 0.00 |
October | 0.102380E+11 | 0.272124E+10 | 0.612341E+10 | 0.423830E+10 | 0.188511E+10 | 0.00 | 0.00 |
November | 0.103462E+11 | 0.385513E+10 | 0.690588E+10 | 0.528954E+10 | 0.161635E+10 | 0.00 | 0.00 |
December | 0.112149E+11 | 0.518465E+10 | 0.776575E+10 | 0.614763E+10 | 0.161813E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.952558E+11 | 0.296505E+11 | 0.550969E+11 | 0.324152E+11 | 0.226817E+11 | 0.00 | 0.00 |
Minimum of Months | 0.519185E+10 | 0.425658E+09 | 0.207734E+10 | 0.160133E+09 | 0.155307E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126890E+11 | 0.518465E+10 | 0.835295E+10 | 0.667125E+10 | 0.215734E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.321796E+10 | 0.323960E+10 | 0.228462E+10 | 0.141993E+10 | 0.864692E+09 | 0.00 | 0.00 |
February | 0.186069E+10 | 0.297451E+10 | 0.167166E+10 | 0.808144E+09 | 0.863513E+09 | 0.00 | 0.00 |
March | 0.316416E+10 | 0.289949E+10 | 0.245139E+10 | 0.116862E+10 | 0.128278E+10 | 0.00 | 0.00 |
April | 0.604715E+10 | 0.164154E+10 | 0.364277E+10 | 0.207795E+10 | 0.156482E+10 | 0.00 | 0.00 |
May | 0.676849E+10 | 0.114277E+10 | 0.377386E+10 | 0.211601E+10 | 0.165785E+10 | 0.00 | 0.00 |
June | 0.785410E+10 | 0.492181E+09 | 0.388256E+10 | 0.228357E+10 | 0.159899E+10 | 0.00 | 0.00 |
July | 0.602934E+10 | 0.415015E+09 | 0.292002E+10 | 0.136305E+10 | 0.155696E+10 | 0.00 | 0.00 |
August | 0.569205E+10 | 0.562017E+09 | 0.278450E+10 | 0.139843E+10 | 0.138607E+10 | 0.00 | 0.00 |
September | 0.465116E+10 | 0.651495E+09 | 0.234885E+10 | 0.986892E+09 | 0.136196E+10 | 0.00 | 0.00 |
October | 0.394724E+10 | 0.208367E+10 | 0.248348E+10 | 0.142005E+10 | 0.106343E+10 | 0.00 | 0.00 |
November | 0.300193E+10 | 0.305208E+10 | 0.221356E+10 | 0.133648E+10 | 0.877077E+09 | 0.00 | 0.00 |
December | 0.222630E+10 | 0.417938E+10 | 0.184350E+10 | 0.104963E+10 | 0.793870E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.544606E+11 | 0.233337E+11 | 0.323008E+11 | 0.174288E+11 | 0.148720E+11 | 0.00 | 0.00 |
Minimum of Months | 0.186069E+10 | 0.415015E+09 | 0.167166E+10 | 0.808144E+09 | 0.793870E+09 | 0.00 | 0.00 |
Maximum of Months | 0.785410E+10 | 0.417938E+10 | 0.388256E+10 | 0.228357E+10 | 0.165785E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.874467E+09 | 0.404030E+10 | 0.101447E+10 | 0.00 | 0.101447E+10 | 0.00 | 0.00 |
February | 0.548158E+09 | 0.361416E+10 | 0.104409E+10 | 0.00 | 0.104409E+10 | 0.00 | 0.00 |
March | 0.148469E+10 | 0.357422E+10 | 0.153627E+10 | 0.00 | 0.153627E+10 | 0.00 | 0.00 |
April | 0.304847E+10 | 0.188684E+10 | 0.181134E+10 | 18797044.85 | 0.179254E+10 | 0.00 | 0.00 |
May | 0.428801E+10 | 0.131521E+10 | 0.219104E+10 | 0.175438E+09 | 0.201560E+10 | 0.00 | 0.00 |
June | 0.640118E+10 | 0.515300E+09 | 0.246400E+10 | 0.447683E+09 | 0.201631E+10 | 0.00 | 0.00 |
July | 0.565532E+10 | 0.410516E+09 | 0.217137E+10 | 0.226213E+09 | 0.194515E+10 | 0.00 | 0.00 |
August | 0.468451E+10 | 0.518137E+09 | 0.175268E+10 | 43540774.45 | 0.170914E+10 | 0.00 | 0.00 |
September | 0.377884E+10 | 0.787653E+09 | 0.160029E+10 | 427199.43 | 0.159986E+10 | 0.00 | 0.00 |
October | 0.192304E+10 | 0.256608E+10 | 0.127938E+10 | 0.00 | 0.127938E+10 | 0.00 | 0.00 |
November | 0.836877E+09 | 0.362157E+10 | 0.103157E+10 | 0.00 | 0.103157E+10 | 0.00 | 0.00 |
December | 0.547179E+09 | 0.488415E+10 | 0.947605E+09 | 0.00 | 0.947605E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.340707E+11 | 0.277341E+11 | 0.188441E+11 | 0.912100E+09 | 0.179320E+11 | 0.00 | 0.00 |
Minimum of Months | 0.547179E+09 | 0.410516E+09 | 0.947605E+09 | 0.00 | 0.947605E+09 | 0.00 | 0.00 |
Maximum of Months | 0.640118E+10 | 0.488415E+10 | 0.246400E+10 | 0.447683E+09 | 0.201631E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.282358E+10 | 0.256882E+10 | 0.218481E+10 | 0.137059E+10 | 0.814217E+09 | 0.00 | 0.00 |
February | 0.221855E+10 | 0.232318E+10 | 0.194514E+10 | 0.111271E+10 | 0.832432E+09 | 0.00 | 0.00 |
March | 0.351413E+10 | 0.228567E+10 | 0.269507E+10 | 0.138636E+10 | 0.130871E+10 | 0.00 | 0.00 |
April | 0.612981E+10 | 0.124345E+10 | 0.372297E+10 | 0.221894E+10 | 0.150403E+10 | 0.00 | 0.00 |
May | 0.701293E+10 | 0.909208E+09 | 0.398695E+10 | 0.236343E+10 | 0.162352E+10 | 0.00 | 0.00 |
June | 0.812832E+10 | 0.336703E+09 | 0.402164E+10 | 0.249899E+10 | 0.152265E+10 | 0.00 | 0.00 |
July | 0.717362E+10 | 0.271168E+09 | 0.350974E+10 | 0.197900E+10 | 0.153074E+10 | 0.00 | 0.00 |
August | 0.675720E+10 | 0.347491E+09 | 0.333105E+10 | 0.190103E+10 | 0.143002E+10 | 0.00 | 0.00 |
September | 0.516095E+10 | 0.513667E+09 | 0.264518E+10 | 0.127503E+10 | 0.137016E+10 | 0.00 | 0.00 |
October | 0.430237E+10 | 0.164485E+10 | 0.274549E+10 | 0.167089E+10 | 0.107461E+10 | 0.00 | 0.00 |
November | 0.261258E+10 | 0.231934E+10 | 0.204303E+10 | 0.122646E+10 | 0.816572E+09 | 0.00 | 0.00 |
December | 0.220955E+10 | 0.307677E+10 | 0.192480E+10 | 0.116225E+10 | 0.762549E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.580436E+11 | 0.178403E+11 | 0.347559E+11 | 0.201657E+11 | 0.145902E+11 | 0.00 | 0.00 |
Minimum of Months | 0.220955E+10 | 0.271168E+09 | 0.192480E+10 | 0.111271E+10 | 0.762549E+09 | 0.00 | 0.00 |
Maximum of Months | 0.812832E+10 | 0.307677E+10 | 0.402164E+10 | 0.249899E+10 | 0.162352E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126009E+11 | 0.429250E+10 | 0.835320E+10 | 0.667147E+10 | 0.168173E+10 | 0.00 | 0.00 |
February | 0.646492E+10 | 0.368260E+10 | 0.477049E+10 | 0.321738E+10 | 0.155310E+10 | 0.00 | 0.00 |
March | 0.641052E+10 | 0.372372E+10 | 0.439469E+10 | 0.226350E+10 | 0.213119E+10 | 0.00 | 0.00 |
April | 0.680630E+10 | 0.206931E+10 | 0.362035E+10 | 0.146298E+10 | 0.215738E+10 | 0.00 | 0.00 |
May | 0.523377E+10 | 0.146503E+10 | 0.250688E+10 | 0.414166E+09 | 0.209271E+10 | 0.00 | 0.00 |
June | 0.577399E+10 | 0.527525E+09 | 0.207737E+10 | 0.160138E+09 | 0.191723E+10 | 0.00 | 0.00 |
July | 0.581653E+10 | 0.415967E+09 | 0.219347E+10 | 0.226932E+09 | 0.196653E+10 | 0.00 | 0.00 |
August | 0.669247E+10 | 0.545284E+09 | 0.266715E+10 | 0.737069E+09 | 0.193008E+10 | 0.00 | 0.00 |
September | 0.779445E+10 | 0.849375E+09 | 0.371914E+10 | 0.158668E+10 | 0.213246E+10 | 0.00 | 0.00 |
October | 0.101741E+11 | 0.269119E+10 | 0.612359E+10 | 0.423844E+10 | 0.188515E+10 | 0.00 | 0.00 |
November | 0.102851E+11 | 0.377719E+10 | 0.690609E+10 | 0.528971E+10 | 0.161638E+10 | 0.00 | 0.00 |
December | 0.111880E+11 | 0.504930E+10 | 0.776599E+10 | 0.614783E+10 | 0.161816E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.952410E+11 | 0.290890E+11 | 0.550984E+11 | 0.324163E+11 | 0.226821E+11 | 0.00 | 0.00 |
Minimum of Months | 0.523377E+10 | 0.415967E+09 | 0.207737E+10 | 0.160138E+09 | 0.155310E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126009E+11 | 0.504930E+10 | 0.835320E+10 | 0.667147E+10 | 0.215738E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.330585E+10 | 0.292276E+10 | 0.228461E+10 | 0.141992E+10 | 0.864688E+09 | 0.00 | 0.00 |
February | 0.194721E+10 | 0.252755E+10 | 0.167165E+10 | 0.808141E+09 | 0.863510E+09 | 0.00 | 0.00 |
March | 0.328846E+10 | 0.251563E+10 | 0.245138E+10 | 0.116861E+10 | 0.128277E+10 | 0.00 | 0.00 |
April | 0.613722E+10 | 0.148516E+10 | 0.364275E+10 | 0.207794E+10 | 0.156482E+10 | 0.00 | 0.00 |
May | 0.679376E+10 | 0.109641E+10 | 0.377384E+10 | 0.211600E+10 | 0.165784E+10 | 0.00 | 0.00 |
June | 0.793275E+10 | 0.442079E+09 | 0.388255E+10 | 0.228356E+10 | 0.159898E+10 | 0.00 | 0.00 |
July | 0.616530E+10 | 0.344018E+09 | 0.292000E+10 | 0.136305E+10 | 0.155696E+10 | 0.00 | 0.00 |
August | 0.584156E+10 | 0.432830E+09 | 0.278448E+10 | 0.139843E+10 | 0.138606E+10 | 0.00 | 0.00 |
September | 0.469572E+10 | 0.598665E+09 | 0.234884E+10 | 0.986888E+09 | 0.136195E+10 | 0.00 | 0.00 |
October | 0.402587E+10 | 0.185933E+10 | 0.248347E+10 | 0.142004E+10 | 0.106343E+10 | 0.00 | 0.00 |
November | 0.310515E+10 | 0.261142E+10 | 0.221355E+10 | 0.133648E+10 | 0.877073E+09 | 0.00 | 0.00 |
December | 0.238726E+10 | 0.346092E+10 | 0.184350E+10 | 0.104963E+10 | 0.793866E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.556261E+11 | 0.202968E+11 | 0.323006E+11 | 0.174287E+11 | 0.148719E+11 | 0.00 | 0.00 |
Minimum of Months | 0.194721E+10 | 0.344018E+09 | 0.167165E+10 | 0.808141E+09 | 0.793866E+09 | 0.00 | 0.00 |
Maximum of Months | 0.793275E+10 | 0.346092E+10 | 0.388255E+10 | 0.228356E+10 | 0.165784E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.993735E+09 | 0.367067E+10 | 0.101447E+10 | 0.00 | 0.101447E+10 | 0.00 | 0.00 |
February | 0.643296E+09 | 0.321815E+10 | 0.104409E+10 | 0.00 | 0.104409E+10 | 0.00 | 0.00 |
March | 0.157790E+10 | 0.332834E+10 | 0.153627E+10 | 0.00 | 0.153627E+10 | 0.00 | 0.00 |
April | 0.302869E+10 | 0.185574E+10 | 0.181134E+10 | 18797044.85 | 0.179254E+10 | 0.00 | 0.00 |
May | 0.424147E+10 | 0.132533E+10 | 0.219104E+10 | 0.175438E+09 | 0.201560E+10 | 0.00 | 0.00 |
June | 0.631151E+10 | 0.541279E+09 | 0.246400E+10 | 0.447683E+09 | 0.201631E+10 | 0.00 | 0.00 |
July | 0.554980E+10 | 0.437126E+09 | 0.217137E+10 | 0.226213E+09 | 0.194515E+10 | 0.00 | 0.00 |
August | 0.460570E+10 | 0.539563E+09 | 0.175268E+10 | 43540774.45 | 0.170914E+10 | 0.00 | 0.00 |
September | 0.372210E+10 | 0.806584E+09 | 0.160029E+10 | 427199.43 | 0.159986E+10 | 0.00 | 0.00 |
October | 0.195977E+10 | 0.241882E+10 | 0.127938E+10 | 0.00 | 0.127938E+10 | 0.00 | 0.00 |
November | 0.932870E+09 | 0.329535E+10 | 0.103157E+10 | 0.00 | 0.103157E+10 | 0.00 | 0.00 |
December | 0.668176E+09 | 0.441105E+10 | 0.947605E+09 | 0.00 | 0.947605E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.342350E+11 | 0.258480E+11 | 0.188441E+11 | 0.912100E+09 | 0.179320E+11 | 0.00 | 0.00 |
Minimum of Months | 0.643296E+09 | 0.437126E+09 | 0.947605E+09 | 0.00 | 0.947605E+09 | 0.00 | 0.00 |
Maximum of Months | 0.631151E+10 | 0.441105E+10 | 0.246400E+10 | 0.447683E+09 | 0.201631E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.291596E+10 | 0.237643E+10 | 0.218481E+10 | 0.137059E+10 | 0.814217E+09 | 0.00 | 0.00 |
February | 0.229466E+10 | 0.210503E+10 | 0.194514E+10 | 0.111271E+10 | 0.832432E+09 | 0.00 | 0.00 |
March | 0.357027E+10 | 0.216553E+10 | 0.269507E+10 | 0.138636E+10 | 0.130871E+10 | 0.00 | 0.00 |
April | 0.610085E+10 | 0.124022E+10 | 0.372297E+10 | 0.221894E+10 | 0.150403E+10 | 0.00 | 0.00 |
May | 0.696896E+10 | 0.918269E+09 | 0.398695E+10 | 0.236343E+10 | 0.162352E+10 | 0.00 | 0.00 |
June | 0.805761E+10 | 0.353409E+09 | 0.402164E+10 | 0.249899E+10 | 0.152265E+10 | 0.00 | 0.00 |
July | 0.709717E+10 | 0.288055E+09 | 0.350974E+10 | 0.197900E+10 | 0.153074E+10 | 0.00 | 0.00 |
August | 0.669604E+10 | 0.361693E+09 | 0.333105E+10 | 0.190103E+10 | 0.143002E+10 | 0.00 | 0.00 |
September | 0.511659E+10 | 0.527236E+09 | 0.264518E+10 | 0.127503E+10 | 0.137016E+10 | 0.00 | 0.00 |
October | 0.431398E+10 | 0.158039E+10 | 0.274549E+10 | 0.167089E+10 | 0.107461E+10 | 0.00 | 0.00 |
November | 0.268316E+10 | 0.214784E+10 | 0.204303E+10 | 0.122646E+10 | 0.816572E+09 | 0.00 | 0.00 |
December | 0.233476E+10 | 0.280697E+10 | 0.192480E+10 | 0.116225E+10 | 0.762549E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.581500E+11 | 0.168711E+11 | 0.347559E+11 | 0.201657E+11 | 0.145902E+11 | 0.00 | 0.00 |
Minimum of Months | 0.229466E+10 | 0.288055E+09 | 0.192480E+10 | 0.111271E+10 | 0.762549E+09 | 0.00 | 0.00 |
Maximum of Months | 0.805761E+10 | 0.280697E+10 | 0.402164E+10 | 0.249899E+10 | 0.162352E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126895E+11 | 0.403690E+10 | 0.835320E+10 | 0.667147E+10 | 0.168173E+10 | 0.00 | 0.00 |
February | 0.655828E+10 | 0.336091E+10 | 0.477049E+10 | 0.321738E+10 | 0.155310E+10 | 0.00 | 0.00 |
March | 0.647633E+10 | 0.352279E+10 | 0.439469E+10 | 0.226350E+10 | 0.213119E+10 | 0.00 | 0.00 |
April | 0.677098E+10 | 0.204542E+10 | 0.362035E+10 | 0.146298E+10 | 0.215738E+10 | 0.00 | 0.00 |
May | 0.518669E+10 | 0.146685E+10 | 0.250688E+10 | 0.414166E+09 | 0.209271E+10 | 0.00 | 0.00 |
June | 0.568590E+10 | 0.547585E+09 | 0.207737E+10 | 0.160138E+09 | 0.191723E+10 | 0.00 | 0.00 |
July | 0.571606E+10 | 0.438599E+09 | 0.219347E+10 | 0.226932E+09 | 0.196653E+10 | 0.00 | 0.00 |
August | 0.661368E+10 | 0.564016E+09 | 0.266715E+10 | 0.737069E+09 | 0.193008E+10 | 0.00 | 0.00 |
September | 0.773287E+10 | 0.871244E+09 | 0.371914E+10 | 0.158668E+10 | 0.213246E+10 | 0.00 | 0.00 |
October | 0.101787E+11 | 0.259566E+10 | 0.612359E+10 | 0.423844E+10 | 0.188515E+10 | 0.00 | 0.00 |
November | 0.103588E+11 | 0.354882E+10 | 0.690609E+10 | 0.528971E+10 | 0.161638E+10 | 0.00 | 0.00 |
December | 0.113207E+11 | 0.468361E+10 | 0.776599E+10 | 0.614783E+10 | 0.161816E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.952884E+11 | 0.276824E+11 | 0.550984E+11 | 0.324163E+11 | 0.226821E+11 | 0.00 | 0.00 |
Minimum of Months | 0.518669E+10 | 0.438599E+09 | 0.207737E+10 | 0.160138E+09 | 0.155310E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126895E+11 | 0.468361E+10 | 0.835320E+10 | 0.667147E+10 | 0.215738E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.335853E+10 | 0.272098E+10 | 0.228461E+10 | 0.141992E+10 | 0.864688E+09 | 0.00 | 0.00 |
February | 0.199340E+10 | 0.231091E+10 | 0.167165E+10 | 0.808141E+09 | 0.863510E+09 | 0.00 | 0.00 |
March | 0.333179E+10 | 0.238027E+10 | 0.245138E+10 | 0.116861E+10 | 0.128277E+10 | 0.00 | 0.00 |
April | 0.611176E+10 | 0.146698E+10 | 0.364275E+10 | 0.207794E+10 | 0.156482E+10 | 0.00 | 0.00 |
May | 0.675608E+10 | 0.109629E+10 | 0.377384E+10 | 0.211600E+10 | 0.165784E+10 | 0.00 | 0.00 |
June | 0.787320E+10 | 0.451935E+09 | 0.388255E+10 | 0.228356E+10 | 0.159898E+10 | 0.00 | 0.00 |
July | 0.610632E+10 | 0.355142E+09 | 0.292000E+10 | 0.136305E+10 | 0.155696E+10 | 0.00 | 0.00 |
August | 0.579362E+10 | 0.441238E+09 | 0.278448E+10 | 0.139843E+10 | 0.138606E+10 | 0.00 | 0.00 |
September | 0.466018E+10 | 0.606875E+09 | 0.234884E+10 | 0.986888E+09 | 0.136195E+10 | 0.00 | 0.00 |
October | 0.403412E+10 | 0.178015E+10 | 0.248347E+10 | 0.142004E+10 | 0.106343E+10 | 0.00 | 0.00 |
November | 0.314762E+10 | 0.243375E+10 | 0.221355E+10 | 0.133648E+10 | 0.877073E+09 | 0.00 | 0.00 |
December | 0.245191E+10 | 0.319457E+10 | 0.184350E+10 | 0.104963E+10 | 0.793866E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.556185E+11 | 0.192391E+11 | 0.323006E+11 | 0.174287E+11 | 0.148719E+11 | 0.00 | 0.00 |
Minimum of Months | 0.199340E+10 | 0.355142E+09 | 0.167165E+10 | 0.808141E+09 | 0.793866E+09 | 0.00 | 0.00 |
Maximum of Months | 0.787320E+10 | 0.319457E+10 | 0.388255E+10 | 0.228356E+10 | 0.165784E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.331329E+11 | -0.321131E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101984E+10 | 58.97 | 0.00 | 0.00 |
February | 0.298157E+11 | -0.288915E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -924203232.9 | 58.97 | 0.00 | 0.00 |
March | 0.333458E+11 | -0.323194E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102638E+10 | 58.98 | 0.00 | 0.00 |
April | 0.279652E+11 | -0.269768E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988478654.5 | 58.98 | 0.00 | 0.00 |
May | 0.271537E+11 | -0.261310E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102266E+10 | 58.96 | 0.00 | 0.00 |
June | 0.246740E+11 | -0.236840E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990076282.7 | 58.96 | 0.00 | 0.00 |
July | 0.225117E+11 | -0.214944E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101726E+10 | 58.97 | 0.00 | 0.00 |
August | 0.249106E+11 | -0.238894E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102124E+10 | 58.97 | 0.00 | 0.00 |
September | 0.242261E+11 | -0.232407E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985433861.7 | 58.97 | 0.00 | 0.00 |
October | 0.274146E+11 | -0.263974E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101722E+10 | 58.97 | 0.00 | 0.00 |
November | 0.294292E+11 | -0.284443E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -984853879.8 | 58.97 | 0.00 | 0.00 |
December | 0.313631E+11 | -0.303449E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101819E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.335943E+12 | -0.323927E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120158E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.225117E+11 | -0.323194E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102638E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.333458E+11 | -0.214944E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -924203232.9 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.51 | 0.48 | 01-JAN-08:09 | 7877.34 | 34.91 | 270.50 | 277.50 | 1943.54 | 28.36 | 167.50 | 283.33 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:49 | 7250.14 | 35.69 | 233.83 | 258.67 | 1009.02 | 22.21 | 108.17 | 211.17 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:30 | 1227.61 | 16.43 | 2.33 | 318.17 | 706.45 | 19.33 | 67.17 | 267.00 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:30 | 935.78 | 15.89 | 0.00 | 317.50 | 586.32 | 18.81 | 10.00 | 276.33 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:49 | 742.79 | 15.49 | 0.00 | 339.00 | 469.33 | 18.50 | 0.00 | 274.33 |
June | 418.17 | 0.53 | 0.48 | 01-JUN-07:40 | 614.55 | 14.62 | 0.00 | 336.83 | 401.32 | 17.69 | 0.00 | 246.00 |
July | 399.50 | 0.53 | 0.48 | 01-JUL-08:09 | 720.11 | 15.16 | 0.00 | 339.17 | 435.41 | 18.15 | 0.00 | 243.00 |
August | 361.83 | 0.53 | 0.48 | 01-AUG-08:09 | 825.37 | 15.60 | 0.00 | 318.50 | 501.37 | 18.56 | 3.50 | 250.17 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-07:19 | 1196.23 | 16.85 | 10.83 | 306.67 | 660.81 | 19.28 | 49.50 | 265.33 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-07:19 | 2615.18 | 22.85 | 137.33 | 307.33 | 855.34 | 19.06 | 56.83 | 287.00 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:40 | 7556.28 | 35.63 | 268.50 | 277.67 | 1239.98 | 23.11 | 104.83 | 255.50 |
December | 290.67 | 0.50 | 0.48 | 01-DEC-07:00 | 7295.36 | 35.55 | 262.50 | 268.83 | 1767.17 | 27.38 | 158.33 | 268.00 |
Annual Sum or Average | 4135.50 | 0.52 | 2838.55 | 21.68 | 1185.83 | 3665.83 | 828.06 | 20.50 | 725.83 | 3127.17 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 614.55 | 14.62 | 0.00 | 258.67 | 401.32 | 17.69 | 0.00 | 211.17 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 7877.34 | 35.69 | 270.50 | 339.17 | 1943.54 | 28.36 | 167.50 | 287.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.54 | 0.48 | 01-JAN-07:00 | 1729.45 | 19.56 | 86.50 | 234.67 | 887.97 | 20.75 | 60.67 | 168.33 |
February | 241.00 | 0.53 | 0.48 | 01-FEB-07:00 | 2044.72 | 19.59 | 65.00 | 225.33 | 1202.23 | 23.36 | 73.83 | 149.17 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-07:30 | 1752.03 | 19.22 | 85.17 | 290.83 | 878.65 | 20.84 | 67.67 | 240.83 |
April | 380.33 | 0.51 | 0.48 | 01-APR-06:49 | 2385.54 | 18.71 | 84.50 | 329.33 | 1406.65 | 22.39 | 84.17 | 283.83 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-06:10 | 2881.49 | 20.53 | 117.83 | 361.17 | 1045.59 | 20.79 | 56.50 | 311.50 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-05:00 | 2897.91 | 19.70 | 115.00 | 358.83 | 1023.63 | 20.04 | 55.00 | 300.17 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-05:00 | 2514.06 | 20.11 | 113.33 | 350.00 | 945.72 | 20.49 | 61.33 | 281.83 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2328.24 | 18.98 | 86.83 | 327.17 | 1352.82 | 22.61 | 88.50 | 266.17 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-06:40 | 1869.17 | 18.88 | 81.17 | 296.00 | 1013.43 | 22.13 | 87.17 | 247.50 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-07:10 | 1794.99 | 18.53 | 83.83 | 258.17 | 928.73 | 20.26 | 65.83 | 205.83 |
November | 288.50 | 0.53 | 0.48 | 01-NOV-07:40 | 1318.78 | 17.50 | 53.67 | 224.50 | 780.29 | 21.36 | 61.83 | 151.33 |
December | 290.67 | 0.53 | 0.48 | 01-DEC-07:49 | 1711.39 | 20.02 | 85.33 | 217.00 | 962.52 | 22.78 | 77.17 | 157.00 |
Annual Sum or Average | 4135.50 | 0.52 | 2156.12 | 19.31 | 1058.17 | 3473.00 | 1040.33 | 21.39 | 839.67 | 2763.50 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1318.78 | 17.50 | 53.67 | 217.00 | 780.29 | 20.04 | 55.00 | 149.17 | |
Maximum of Months | 418.17 | 0.54 | 0.48 | 2897.91 | 20.53 | 117.83 | 361.17 | 1406.65 | 23.36 | 88.50 | 311.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.59 | 0.48 | 01-JAN-10:39 | 346.89 | 11.50 | 0.00 | 149.00 | 245.93 | 15.12 | 0.00 | 20.83 |
February | 241.00 | 0.57 | 0.48 | 01-FEB-13:09 | 434.73 | 12.66 | 0.00 | 178.50 | 283.49 | 15.90 | 0.00 | 59.00 |
March | 344.33 | 0.55 | 0.48 | 01-MAR-08:30 | 501.41 | 13.96 | 0.00 | 270.50 | 315.66 | 16.99 | 0.00 | 147.83 |
April | 380.33 | 0.52 | 0.48 | 01-APR-08:50 | 585.45 | 15.19 | 0.00 | 321.17 | 390.29 | 18.18 | 0.00 | 251.83 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 697.58 | 16.08 | 1.50 | 382.33 | 463.47 | 19.02 | 1.50 | 343.67 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:00 | 806.05 | 17.88 | 43.33 | 394.17 | 483.71 | 20.81 | 46.33 | 378.17 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-06:19 | 690.06 | 15.88 | 0.00 | 376.00 | 462.73 | 21.40 | 63.00 | 314.33 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-08:09 | 597.41 | 15.31 | 0.00 | 330.50 | 382.57 | 18.27 | 0.00 | 224.17 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:19 | 571.15 | 14.65 | 0.00 | 296.00 | 351.87 | 17.59 | 0.00 | 190.83 |
October | 348.00 | 0.58 | 0.48 | 01-OCT-07:00 | 405.51 | 12.45 | 0.00 | 198.50 | 275.32 | 15.74 | 0.00 | 79.67 |
November | 288.50 | 0.58 | 0.48 | 01-NOV-08:00 | 380.46 | 12.20 | 0.00 | 161.83 | 257.87 | 15.74 | 0.00 | 30.33 |
December | 290.67 | 0.59 | 0.48 | 01-DEC-11:09 | 351.13 | 11.68 | 0.00 | 136.33 | 242.07 | 15.31 | 0.00 | 9.67 |
Annual Sum or Average | 4135.50 | 0.54 | 549.06 | 14.37 | 44.83 | 3194.83 | 357.36 | 17.76 | 110.83 | 2050.33 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 346.89 | 11.50 | 0.00 | 136.33 | 242.07 | 15.12 | 0.00 | 9.67 | |
Maximum of Months | 418.17 | 0.59 | 0.48 | 806.05 | 17.88 | 43.33 | 394.17 | 483.71 | 21.40 | 63.00 | 378.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.56 | 0.48 | 01-JAN-10:30 | 1833.95 | 19.08 | 85.67 | 215.33 | 957.11 | 20.36 | 64.33 | 158.67 |
February | 241.00 | 0.55 | 0.48 | 01-FEB-12:39 | 1812.98 | 18.65 | 64.33 | 209.67 | 724.84 | 20.16 | 58.17 | 143.83 |
March | 344.33 | 0.53 | 0.48 | 02-MAR-09:39 | 1589.44 | 18.64 | 79.00 | 287.50 | 820.78 | 20.43 | 65.00 | 233.50 |
April | 380.33 | 0.52 | 0.48 | 01-APR-08:00 | 2250.03 | 18.51 | 85.00 | 308.83 | 1282.67 | 20.57 | 58.17 | 275.50 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-08:09 | 2415.38 | 16.40 | 54.50 | 338.83 | 1379.89 | 17.83 | 3.17 | 300.17 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:00 | 2581.88 | 12.98 | 0.00 | 342.50 | 953.15 | 17.41 | 0.67 | 298.50 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-08:39 | 1895.61 | 13.78 | 3.67 | 342.17 | 801.42 | 17.74 | 8.00 | 275.17 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-08:39 | 1887.38 | 16.14 | 49.17 | 313.00 | 1052.29 | 17.82 | 7.17 | 252.00 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-08:20 | 1513.14 | 18.54 | 78.83 | 294.83 | 791.81 | 20.63 | 69.67 | 245.33 |
October | 348.00 | 0.55 | 0.48 | 01-OCT-08:20 | 1833.45 | 18.42 | 87.67 | 251.00 | 1023.02 | 21.75 | 85.33 | 207.83 |
November | 288.50 | 0.54 | 0.48 | 01-NOV-09:09 | 1734.31 | 19.59 | 80.83 | 223.00 | 888.13 | 20.86 | 61.83 | 161.67 |
December | 290.67 | 0.55 | 0.48 | 01-DEC-10:00 | 1458.10 | 19.41 | 80.67 | 209.00 | 739.18 | 20.43 | 63.00 | 155.33 |
Annual Sum or Average | 4135.50 | 0.53 | 1933.00 | 17.28 | 749.33 | 3335.67 | 967.69 | 19.53 | 544.50 | 2707.50 | ||
Minimum of Months | 241.00 | 0.52 | 0.48 | 1458.10 | 12.98 | 0.00 | 209.00 | 724.84 | 17.41 | 0.67 | 143.83 | |
Maximum of Months | 418.17 | 0.56 | 0.48 | 2581.88 | 19.59 | 87.67 | 342.50 | 1379.89 | 21.75 | 85.33 | 300.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.51 | 0.48 | 01-JAN-08:09 | 7886.21 | 34.04 | 270.50 | 277.50 | 1996.56 | 24.79 | 145.33 | 283.67 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:49 | 7243.34 | 35.36 | 233.33 | 257.33 | 1049.37 | 17.92 | 37.50 | 212.17 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:30 | 1214.72 | 10.38 | 2.33 | 317.00 | 734.06 | 15.29 | 1.83 | 269.33 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:20 | 930.18 | 10.55 | 0.00 | 315.50 | 609.52 | 15.45 | 0.00 | 279.00 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:40 | 735.71 | 10.29 | 0.00 | 336.83 | 486.04 | 15.23 | 0.00 | 280.33 |
June | 418.17 | 0.53 | 0.48 | 01-JUN-07:40 | 609.36 | 9.49 | 0.00 | 334.33 | 415.64 | 14.47 | 0.00 | 254.67 |
July | 399.50 | 0.53 | 0.48 | 01-JUL-08:09 | 710.20 | 9.79 | 0.00 | 335.00 | 449.78 | 14.68 | 0.00 | 249.67 |
August | 361.83 | 0.53 | 0.48 | 01-AUG-07:00 | 816.68 | 10.11 | 0.00 | 317.17 | 519.65 | 15.05 | 0.00 | 253.67 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-07:19 | 1182.00 | 11.17 | 10.83 | 306.17 | 684.46 | 15.34 | 0.00 | 268.00 |
October | 348.00 | 0.51 | 0.48 | 01-OCT-07:19 | 2635.48 | 18.56 | 137.17 | 312.33 | 900.73 | 15.00 | 13.17 | 289.50 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:40 | 7557.58 | 35.00 | 268.00 | 277.00 | 1323.42 | 20.61 | 88.67 | 261.67 |
December | 290.67 | 0.50 | 0.48 | 01-DEC-07:00 | 7295.18 | 34.79 | 262.50 | 267.67 | 1818.52 | 23.50 | 123.33 | 268.50 |
Annual Sum or Average | 4135.50 | 0.52 | 2834.88 | 17.63 | 1184.67 | 3653.83 | 860.13 | 16.93 | 409.83 | 3170.17 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 609.36 | 9.49 | 0.00 | 257.33 | 415.64 | 14.47 | 0.00 | 212.17 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 7886.21 | 35.36 | 270.50 | 336.83 | 1996.56 | 24.79 | 145.33 | 289.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.54 | 0.48 | 01-JAN-07:00 | 1737.76 | 17.10 | 86.50 | 234.33 | 911.08 | 18.83 | 56.33 | 176.17 |
February | 241.00 | 0.53 | 0.48 | 01-FEB-07:00 | 2050.70 | 16.81 | 65.00 | 225.17 | 1227.46 | 21.45 | 62.83 | 154.00 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-07:30 | 1525.29 | 13.49 | 55.83 | 290.00 | 904.41 | 18.35 | 56.83 | 247.00 |
April | 380.33 | 0.51 | 0.48 | 01-APR-06:49 | 2389.87 | 15.51 | 84.50 | 328.00 | 1437.86 | 20.11 | 82.33 | 290.33 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-06:10 | 2880.97 | 17.58 | 117.83 | 360.17 | 1080.18 | 18.06 | 56.00 | 317.33 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-05:00 | 2900.53 | 16.63 | 114.00 | 356.83 | 1057.11 | 17.25 | 55.00 | 306.33 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-05:00 | 2309.72 | 14.96 | 87.00 | 349.33 | 976.02 | 17.75 | 55.33 | 288.17 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2325.00 | 15.68 | 86.83 | 326.00 | 1382.99 | 20.24 | 83.50 | 272.50 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-06:40 | 1874.91 | 15.78 | 81.17 | 295.00 | 1038.71 | 19.88 | 73.17 | 252.50 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-07:10 | 1805.50 | 15.60 | 83.83 | 258.83 | 954.44 | 17.90 | 56.83 | 213.83 |
November | 288.50 | 0.53 | 0.48 | 01-NOV-07:40 | 1324.02 | 14.35 | 53.67 | 224.50 | 775.04 | 18.80 | 49.00 | 156.67 |
December | 290.67 | 0.53 | 0.48 | 01-DEC-07:49 | 1716.83 | 17.52 | 85.33 | 216.50 | 897.93 | 19.13 | 54.33 | 159.17 |
Annual Sum or Average | 4135.50 | 0.52 | 2120.92 | 15.90 | 1001.50 | 3464.67 | 1060.26 | 18.87 | 741.50 | 2834.00 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1324.02 | 13.49 | 53.67 | 216.50 | 775.04 | 17.25 | 49.00 | 154.00 | |
Maximum of Months | 418.17 | 0.54 | 0.48 | 2900.53 | 17.58 | 117.83 | 360.17 | 1437.86 | 21.45 | 83.50 | 317.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.59 | 0.48 | 01-JAN-10:30 | 341.68 | 6.39 | 0.00 | 145.67 | 253.17 | 11.59 | 0.00 | 30.17 |
February | 241.00 | 0.57 | 0.48 | 01-FEB-12:00 | 428.39 | 7.51 | 0.00 | 174.83 | 292.19 | 12.49 | 0.00 | 66.67 |
March | 344.33 | 0.55 | 0.48 | 01-MAR-08:30 | 494.40 | 8.86 | 0.00 | 267.17 | 325.54 | 13.79 | 0.00 | 166.50 |
April | 380.33 | 0.52 | 0.48 | 01-APR-08:50 | 579.50 | 10.51 | 0.00 | 320.17 | 403.32 | 15.51 | 0.00 | 261.83 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-06:30 | 665.33 | 10.94 | 1.50 | 372.00 | 479.29 | 16.08 | 2.67 | 349.50 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:00 | 801.84 | 12.99 | 43.33 | 393.33 | 521.89 | 19.51 | 81.50 | 389.50 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-06:19 | 681.77 | 10.41 | 0.00 | 374.83 | 477.20 | 18.64 | 62.67 | 326.50 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:00 | 590.70 | 10.16 | 0.00 | 328.50 | 395.32 | 15.23 | 0.00 | 239.67 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:19 | 562.37 | 9.59 | 0.00 | 293.83 | 362.56 | 14.41 | 0.00 | 201.83 |
October | 348.00 | 0.58 | 0.48 | 01-OCT-07:00 | 400.83 | 7.43 | 0.00 | 196.83 | 284.22 | 12.51 | 0.00 | 93.00 |
November | 288.50 | 0.58 | 0.48 | 01-NOV-08:50 | 374.74 | 6.86 | 0.00 | 156.67 | 265.62 | 12.14 | 0.00 | 38.83 |
December | 290.67 | 0.59 | 0.48 | 01-DEC-10:00 | 345.21 | 6.32 | 0.00 | 131.50 | 248.98 | 11.61 | 0.00 | 18.67 |
Annual Sum or Average | 4135.50 | 0.54 | 540.26 | 9.26 | 44.83 | 3155.33 | 371.02 | 14.78 | 146.83 | 2182.67 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 341.68 | 6.32 | 0.00 | 131.50 | 248.98 | 11.59 | 0.00 | 18.67 | |
Maximum of Months | 418.17 | 0.59 | 0.48 | 801.84 | 12.99 | 43.33 | 393.33 | 521.89 | 19.51 | 81.50 | 389.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.56 | 0.48 | 01-JAN-10:20 | 1838.52 | 16.56 | 85.67 | 216.33 | 980.20 | 18.39 | 55.50 | 164.67 |
February | 241.00 | 0.55 | 0.48 | 01-FEB-12:30 | 1813.78 | 15.91 | 64.33 | 209.33 | 745.57 | 17.95 | 36.33 | 149.83 |
March | 344.33 | 0.53 | 0.48 | 02-MAR-09:30 | 1596.35 | 15.52 | 79.00 | 287.50 | 844.21 | 17.92 | 50.67 | 241.83 |
April | 380.33 | 0.52 | 0.48 | 01-APR-08:50 | 2247.73 | 15.33 | 85.00 | 308.33 | 1312.76 | 17.89 | 55.00 | 282.33 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-08:09 | 2402.50 | 12.66 | 54.50 | 338.83 | 1412.01 | 14.53 | 0.00 | 305.33 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:49 | 2361.82 | 8.46 | 0.00 | 342.33 | 984.96 | 14.06 | 0.00 | 305.50 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-08:30 | 1762.10 | 9.42 | 3.67 | 341.83 | 826.31 | 14.53 | 0.00 | 283.00 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-08:30 | 1882.18 | 12.44 | 49.17 | 311.83 | 1078.31 | 14.65 | 5.00 | 258.50 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-08:20 | 1515.25 | 15.47 | 78.67 | 293.50 | 814.03 | 18.18 | 53.83 | 251.17 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-08:20 | 1841.64 | 15.55 | 87.67 | 252.33 | 1046.34 | 19.67 | 78.50 | 214.67 |
November | 288.50 | 0.54 | 0.48 | 01-NOV-08:00 | 1712.55 | 16.59 | 78.17 | 222.33 | 912.18 | 18.71 | 52.33 | 167.83 |
December | 290.67 | 0.55 | 0.48 | 01-DEC-09:00 | 1272.48 | 14.75 | 60.33 | 208.17 | 759.99 | 18.52 | 49.67 | 161.33 |
Annual Sum or Average | 4135.50 | 0.53 | 1883.20 | 13.77 | 726.17 | 3332.67 | 993.36 | 16.88 | 436.83 | 2786.00 | ||
Minimum of Months | 241.00 | 0.52 | 0.48 | 1272.48 | 8.46 | 0.00 | 208.17 | 745.57 | 14.06 | 0.00 | 149.83 | |
Maximum of Months | 418.17 | 0.56 | 0.48 | 2402.50 | 16.59 | 87.67 | 342.33 | 1412.01 | 19.67 | 78.50 | 305.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.51 | 0.48 | 01-JAN-08:09 | 7885.52 | 34.02 | 270.50 | 277.50 | 1997.31 | 24.78 | 145.33 | 283.67 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:49 | 7243.51 | 35.35 | 233.33 | 257.33 | 1050.26 | 17.90 | 37.50 | 212.17 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:30 | 1215.23 | 10.34 | 2.33 | 317.00 | 734.83 | 15.27 | 1.83 | 269.33 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:20 | 930.35 | 10.51 | 0.00 | 315.50 | 610.00 | 15.43 | 0.00 | 279.00 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:40 | 735.76 | 10.24 | 0.00 | 336.83 | 486.40 | 15.21 | 0.00 | 280.67 |
June | 418.17 | 0.53 | 0.48 | 01-JUN-07:40 | 609.32 | 9.45 | 0.00 | 334.17 | 415.92 | 14.45 | 0.00 | 254.83 |
July | 399.50 | 0.53 | 0.48 | 01-JUL-08:09 | 710.34 | 9.75 | 0.00 | 335.00 | 450.17 | 14.66 | 0.00 | 250.00 |
August | 361.83 | 0.53 | 0.48 | 01-AUG-07:00 | 816.89 | 10.06 | 0.00 | 317.17 | 520.09 | 15.03 | 0.00 | 253.83 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-07:19 | 1182.51 | 11.13 | 10.83 | 306.17 | 685.21 | 15.32 | 0.00 | 268.17 |
October | 348.00 | 0.51 | 0.48 | 01-OCT-07:19 | 2635.71 | 18.53 | 137.17 | 312.33 | 901.41 | 14.98 | 13.17 | 289.50 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:40 | 7557.18 | 34.99 | 268.00 | 277.00 | 1324.20 | 20.59 | 88.67 | 261.67 |
December | 290.67 | 0.50 | 0.48 | 01-DEC-07:00 | 7294.26 | 34.77 | 262.50 | 267.67 | 1819.34 | 23.48 | 123.33 | 268.50 |
Annual Sum or Average | 4135.50 | 0.52 | 2834.89 | 17.60 | 1184.67 | 3653.67 | 860.72 | 16.91 | 409.83 | 3171.33 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 609.32 | 9.45 | 0.00 | 257.33 | 415.92 | 14.45 | 0.00 | 212.17 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 7885.52 | 35.35 | 270.50 | 336.83 | 1997.31 | 24.78 | 145.33 | 289.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.54 | 0.48 | 01-JAN-07:00 | 1737.40 | 17.06 | 86.50 | 234.33 | 911.34 | 18.81 | 56.33 | 176.33 |
February | 241.00 | 0.53 | 0.48 | 01-FEB-07:00 | 2050.42 | 16.78 | 65.00 | 225.00 | 1227.88 | 21.43 | 62.83 | 154.17 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-07:30 | 1525.02 | 13.45 | 55.83 | 290.00 | 904.95 | 18.33 | 56.83 | 247.00 |
April | 380.33 | 0.51 | 0.48 | 01-APR-06:49 | 2389.53 | 15.47 | 84.50 | 328.00 | 1438.31 | 20.09 | 82.33 | 290.33 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-06:10 | 2603.74 | 15.09 | 88.67 | 360.17 | 1080.64 | 18.04 | 56.00 | 317.50 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-05:00 | 2900.10 | 16.59 | 114.00 | 356.50 | 1057.49 | 17.23 | 55.00 | 306.50 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-05:00 | 2309.51 | 14.92 | 87.00 | 349.17 | 976.53 | 17.73 | 55.33 | 288.17 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2324.79 | 15.64 | 86.83 | 326.00 | 1383.51 | 20.22 | 83.50 | 272.67 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-06:40 | 1874.82 | 15.74 | 81.17 | 295.00 | 1039.33 | 19.87 | 73.17 | 252.50 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-07:10 | 1805.09 | 15.56 | 83.83 | 258.83 | 954.81 | 17.88 | 56.83 | 214.00 |
November | 288.50 | 0.53 | 0.48 | 01-NOV-07:40 | 1323.72 | 14.30 | 53.67 | 224.67 | 775.36 | 18.78 | 49.00 | 156.83 |
December | 290.67 | 0.53 | 0.48 | 01-DEC-07:49 | 1716.50 | 17.49 | 85.33 | 216.50 | 898.21 | 19.11 | 54.33 | 159.50 |
Annual Sum or Average | 4135.50 | 0.52 | 2093.62 | 15.62 | 972.33 | 3464.17 | 1060.70 | 18.86 | 741.50 | 2835.50 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1323.72 | 13.45 | 53.67 | 216.50 | 775.36 | 17.23 | 49.00 | 154.17 | |
Maximum of Months | 418.17 | 0.54 | 0.48 | 2900.10 | 17.49 | 114.00 | 360.17 | 1438.31 | 21.43 | 83.50 | 317.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.59 | 0.48 | 01-JAN-10:30 | 341.44 | 6.34 | 0.00 | 145.33 | 253.28 | 11.57 | 0.00 | 30.17 |
February | 241.00 | 0.57 | 0.48 | 01-FEB-12:00 | 428.26 | 7.47 | 0.00 | 174.83 | 292.38 | 12.47 | 0.00 | 66.67 |
March | 344.33 | 0.55 | 0.48 | 01-MAR-08:30 | 494.34 | 8.82 | 0.00 | 267.17 | 325.79 | 13.77 | 0.00 | 166.83 |
April | 380.33 | 0.52 | 0.48 | 01-APR-08:50 | 579.30 | 10.46 | 0.00 | 320.17 | 403.56 | 15.49 | 0.00 | 261.83 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-06:30 | 665.18 | 10.89 | 1.50 | 372.00 | 479.59 | 16.06 | 2.67 | 349.50 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:00 | 801.67 | 12.95 | 43.33 | 393.33 | 522.18 | 19.50 | 81.50 | 389.50 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-06:19 | 681.73 | 10.37 | 0.00 | 374.83 | 477.55 | 18.62 | 62.67 | 326.67 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:00 | 590.61 | 10.12 | 0.00 | 328.50 | 395.61 | 15.21 | 0.00 | 240.00 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:19 | 562.32 | 9.55 | 0.00 | 293.83 | 362.86 | 14.39 | 0.00 | 202.17 |
October | 348.00 | 0.58 | 0.48 | 01-OCT-07:00 | 400.67 | 7.38 | 0.00 | 196.83 | 284.38 | 12.49 | 0.00 | 93.33 |
November | 288.50 | 0.58 | 0.48 | 01-NOV-08:50 | 374.56 | 6.81 | 0.00 | 156.83 | 265.77 | 12.12 | 0.00 | 38.83 |
December | 290.67 | 0.59 | 0.48 | 01-DEC-10:00 | 345.00 | 6.28 | 0.00 | 131.00 | 249.10 | 11.58 | 0.00 | 18.83 |
Annual Sum or Average | 4135.50 | 0.54 | 540.13 | 9.21 | 44.83 | 3154.67 | 371.26 | 14.76 | 146.83 | 2184.33 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 341.44 | 6.28 | 0.00 | 131.00 | 249.10 | 11.57 | 0.00 | 18.83 | |
Maximum of Months | 418.17 | 0.59 | 0.48 | 801.67 | 12.95 | 43.33 | 393.33 | 522.18 | 19.50 | 81.50 | 389.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.56 | 0.48 | 01-JAN-10:20 | 1838.02 | 16.52 | 85.67 | 216.33 | 980.49 | 18.37 | 55.50 | 164.67 |
February | 241.00 | 0.55 | 0.48 | 01-FEB-12:30 | 1813.47 | 15.87 | 64.33 | 209.33 | 746.04 | 17.93 | 36.33 | 150.00 |
March | 344.33 | 0.53 | 0.48 | 02-MAR-09:30 | 1596.15 | 15.48 | 79.00 | 287.50 | 844.74 | 17.90 | 50.67 | 242.17 |
April | 380.33 | 0.52 | 0.48 | 01-APR-08:50 | 2247.35 | 15.29 | 85.00 | 308.33 | 1313.26 | 17.87 | 55.00 | 282.50 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-08:09 | 2402.08 | 12.61 | 54.50 | 338.83 | 1412.52 | 14.51 | 0.00 | 305.33 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:49 | 2361.27 | 8.41 | 0.00 | 342.33 | 985.40 | 14.04 | 0.00 | 305.50 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-08:30 | 1761.88 | 9.37 | 3.67 | 341.67 | 826.83 | 14.51 | 0.00 | 283.33 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-08:30 | 1881.97 | 12.40 | 49.17 | 311.83 | 1078.78 | 14.63 | 5.00 | 258.50 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-08:20 | 1515.15 | 15.43 | 78.67 | 293.50 | 814.63 | 18.16 | 53.83 | 251.17 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-08:20 | 1841.31 | 15.51 | 87.67 | 252.33 | 1046.72 | 19.65 | 78.50 | 214.83 |
November | 288.50 | 0.54 | 0.48 | 01-NOV-08:00 | 1712.10 | 16.55 | 78.17 | 222.33 | 912.53 | 18.69 | 52.33 | 167.83 |
December | 290.67 | 0.55 | 0.48 | 01-DEC-09:00 | 1272.06 | 14.71 | 60.33 | 208.00 | 760.30 | 18.50 | 49.67 | 161.67 |
Annual Sum or Average | 4135.50 | 0.53 | 1882.86 | 13.73 | 726.17 | 3332.33 | 993.81 | 16.87 | 436.83 | 2787.50 | ||
Minimum of Months | 241.00 | 0.52 | 0.48 | 1272.06 | 8.41 | 0.00 | 208.00 | 746.04 | 14.04 | 0.00 | 150.00 | |
Maximum of Months | 418.17 | 0.56 | 0.48 | 2402.08 | 16.55 | 87.67 | 342.33 | 1412.52 | 19.65 | 78.50 | 305.50 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 19025708.51 | 3628.05 | 12-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22723018.61 | 2216.02 | 01-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 76255243.69 | 7332.69 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2467236.08 | 893.71 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2454501.85 | 1690.02 | 04-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.322806E+09 | 12776.05 | 06-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.445732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.322806E+09 | 12776.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1697393.12 | 566.19 | 07-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1697393.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1697393.12 | 566.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.902959E+09 | 68342.15 | 02-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122363E+10 | 54430.60 | 01-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.226763E+10 | 118250.67 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197772E+09 | 52186.25 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.504764E+09 | 70727.91 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.868497E+10 | 162650.96 | 06-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.868497E+10 | 162650.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.913841E+09 | 135276.79 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.684296E+09 | 55926.83 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.344005E+09 | 132155.97 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316141E+09 | 140673.94 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.355556E+10 | 142474.25 | 05-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.581385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.355556E+10 | 142474.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.384051E+09 | 121572.60 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.325950E+09 | 45077.15 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135884E+09 | 17195.73 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104891E+09 | 46349.25 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158558E+10 | 123815.34 | 06-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.253635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.158558E+10 | 123815.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 64552272.87 | 73525.85 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 98406255.84 | 50644.79 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18276814.00 | 3986.95 | 27-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.338058E+09 | 149352.50 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.519293E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.338058E+09 | 149352.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.180032E+09 | 117977.96 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134868E+09 | 12756.98 | 13-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27493388.35 | 5674.44 | 27-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 39096089.21 | 12590.30 | 24-NOV-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116075E+10 | 119183.74 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116075E+10 | 119183.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.284053E+09 | 10501.44 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.432363E+09 | 9447.13 | 28-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.485200E+09 | 16839.33 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 74420.13 | 133.24 | 21-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 96998702.74 | 8682.38 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191277E+09 | 12513.66 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168950E+10 | 21803.04 | 06-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168950E+10 | 21803.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.397443E+09 | 73118.98 | 02-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179558E+09 | 71982.64 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 55218381.21 | 50010.80 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 79158429.95 | 49563.21 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.715262E+09 | 73447.23 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.715262E+09 | 73447.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.772567E+09 | 15914.01 | 02-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.811838E+09 | 15962.47 | 13-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.433844E+09 | 15850.80 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 653485.77 | 199.12 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.103122E+09 | 15711.04 | 26-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.538315E+09 | 15836.57 | 18-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209186E+10 | 15857.05 | 18-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.475220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.209186E+10 | 15962.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.327764E+09 | 14310.66 | 02-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385905E+09 | 14145.16 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186318E+09 | 14166.86 | 27-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 47011273.35 | 4670.44 | 26-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215675E+09 | 14116.95 | 24-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.903127E+09 | 14443.25 | 07-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.903127E+09 | 14443.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.124281E+09 | 17171.79 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.305743E+09 | 17315.70 | 13-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195880E+09 | 17209.19 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16164832.26 | 1696.48 | 26-OCT-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 95179135.35 | 17046.95 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.563907E+09 | 17166.90 | 07-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.563907E+09 | 17315.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.250716E+09 | 14831.82 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.336002E+09 | 14621.45 | 13-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158159E+09 | 11007.34 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32555730.20 | 1519.29 | 28-OCT-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.175992E+09 | 13438.56 | 24-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.808493E+09 | 14924.84 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.808493E+09 | 14924.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.357209E+11 | 0.357077E+11 | 88211.47 | 31-JAN-16:40 | 88211.47 | 0.00 |
February | 0.00 | 0.00 | 0.906358E+10 | 0.906358E+10 | 56854.57 | 21-FEB-15:00 | 56854.57 | 0.07 |
March | 0.00 | 0.00 | 0.395181E+11 | 0.395181E+11 | 97853.95 | 20-MAR-14:40 | 97853.95 | 0.03 |
April | 0.00 | 0.00 | 0.103555E+12 | 0.103555E+12 | 122665.92 | 24-APR-16:00 | 122665.92 | 0.00 |
May | 0.00 | 0.00 | 0.116999E+12 | 0.116999E+12 | 116871.54 | 15-MAY-15:50 | 116871.54 | 0.00 |
June | 0.00 | 0.00 | 0.160237E+12 | 0.160218E+12 | 156331.95 | 30-JUN-05:02 | 156331.95 | 0.10 |
July | 0.00 | 0.00 | 0.169526E+12 | 0.158495E+12 | 267120.40 | 18-JUL-05:03 | 121208.54 | 0.66 |
August | 0.00 | 0.00 | 0.178193E+12 | 0.167674E+12 | 251415.43 | 01-AUG-05:02 | 120264.56 | 0.74 |
September | 0.00 | 0.00 | 0.132989E+12 | 0.123728E+12 | 240739.06 | 05-SEP-03:02 | 120460.52 | 0.58 |
October | 0.00 | 0.00 | 0.803420E+11 | 0.788504E+11 | 200951.96 | 03-OCT-05:03 | 104698.93 | 0.17 |
November | 0.00 | 0.00 | 0.422354E+11 | 0.397989E+11 | 142684.11 | 13-NOV-06:02 | 51102.67 | 0.13 |
December | 0.00 | 0.00 | 0.206936E+11 | 0.206936E+11 | 86375.87 | 22-DEC-16:20 | 86375.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.108907E+13 | 0.105430E+13 | 0.21 | |||
Minimum of Months | 0.00 | 0.00 | 0.906358E+10 | 0.906358E+10 | 56854.57 | 51102.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.178193E+12 | 0.167674E+12 | 267120.40 | 156331.95 | 0.74 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.292150E+12 | 0.292080E+12 | 751867.45 | 31-JAN-16:30 | 751867.45 | 0.00 |
February | 0.00 | 0.00 | 0.662999E+11 | 0.662999E+11 | 407219.50 | 22-FEB-16:00 | 407219.50 | 0.08 |
March | 0.00 | 0.00 | 0.285485E+12 | 0.285485E+12 | 805952.85 | 16-MAR-15:50 | 805952.85 | 0.03 |
April | 0.00 | 0.00 | 0.789775E+12 | 0.789775E+12 | 1078232.24 | 14-APR-15:20 | 1078232.24 | 0.00 |
May | 0.00 | 0.00 | 0.103728E+13 | 0.103728E+13 | 1096376.96 | 18-MAY-15:20 | 1096376.96 | 0.00 |
June | 0.00 | 0.00 | 0.139844E+13 | 0.139829E+13 | 1339061.75 | 29-JUN-05:02 | 1339061.75 | 0.09 |
July | 0.00 | 0.00 | 0.134847E+13 | 0.127246E+13 | 2444120.97 | 15-JUL-05:03 | 1014940.73 | 0.57 |
August | 0.00 | 0.00 | 0.136716E+13 | 0.129777E+13 | 2384952.06 | 01-AUG-05:02 | 1137422.75 | 0.63 |
September | 0.00 | 0.00 | 0.113021E+13 | 0.105522E+13 | 2146418.24 | 08-SEP-05:02 | 1251740.09 | 0.51 |
October | 0.00 | 0.00 | 0.643972E+12 | 0.631554E+12 | 1724860.08 | 03-OCT-03:02 | 817472.33 | 0.13 |
November | 0.00 | 0.00 | 0.295257E+12 | 0.282908E+12 | 1011775.92 | 13-NOV-06:02 | 359752.67 | 0.11 |
December | 0.00 | 0.00 | 0.141608E+12 | 0.141608E+12 | 629198.37 | 22-DEC-16:00 | 629198.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.879610E+13 | 0.855073E+13 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 0.662999E+11 | 0.662999E+11 | 407219.50 | 359752.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.139844E+13 | 0.139829E+13 | 2444120.97 | 1339061.75 | 0.63 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.253626E+11 | 0.253535E+11 | 77255.44 | 31-JAN-16:30 | 77255.44 | 0.00 |
February | 0.00 | 0.00 | 0.523036E+10 | 0.523036E+10 | 38106.33 | 22-FEB-16:00 | 38106.33 | 0.07 |
March | 0.00 | 0.00 | 0.271201E+11 | 0.271201E+11 | 92444.09 | 16-MAR-15:40 | 92444.09 | 0.03 |
April | 0.00 | 0.00 | 0.873096E+11 | 0.873096E+11 | 131760.29 | 14-APR-15:20 | 131760.29 | 0.00 |
May | 0.00 | 0.00 | 0.116807E+12 | 0.116807E+12 | 133655.08 | 18-MAY-15:30 | 133655.08 | 0.00 |
June | 0.00 | 0.00 | 0.162904E+12 | 0.162898E+12 | 159403.64 | 28-JUN-15:00 | 159403.64 | 0.09 |
July | 0.00 | 0.00 | 0.156683E+12 | 0.148477E+12 | 255844.53 | 15-JUL-05:03 | 106376.53 | 0.59 |
August | 0.00 | 0.00 | 0.156187E+12 | 0.148488E+12 | 257409.69 | 01-AUG-05:02 | 123321.89 | 0.64 |
September | 0.00 | 0.00 | 0.124985E+12 | 0.117269E+12 | 275524.15 | 02-SEP-03:02 | 144081.25 | 0.53 |
October | 0.00 | 0.00 | 0.659681E+11 | 0.647972E+11 | 168266.81 | 03-OCT-03:02 | 82647.02 | 0.13 |
November | 0.00 | 0.00 | 0.257992E+11 | 0.249986E+11 | 93871.10 | 01-NOV-15:20 | 93871.10 | 0.10 |
December | 0.00 | 0.00 | 0.114095E+11 | 0.114095E+11 | 62235.82 | 22-DEC-16:00 | 62235.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.965766E+12 | 0.940158E+12 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 0.523036E+10 | 0.523036E+10 | 38106.33 | 38106.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.162904E+12 | 0.162898E+12 | 275524.15 | 159403.64 | 0.64 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.231573E+11 | 0.231544E+11 | 71974.54 | 16-JAN-15:20 | 71974.54 | 0.00 |
February | 0.00 | 0.00 | 0.393719E+10 | 0.392461E+10 | 39232.96 | 21-FEB-15:00 | 39232.96 | 0.04 |
March | 0.00 | 0.00 | 0.222638E+11 | 0.222584E+11 | 59632.78 | 20-MAR-13:10 | 59632.78 | 0.03 |
April | 0.00 | 0.00 | 0.522457E+11 | 0.522457E+11 | 78684.72 | 25-APR-03:02 | 78684.72 | 0.00 |
May | 0.00 | 0.00 | 0.648167E+11 | 0.648167E+11 | 99713.80 | 29-MAY-17:40 | 99713.80 | 0.00 |
June | 0.00 | 0.00 | 0.797126E+11 | 0.797126E+11 | 94858.42 | 30-JUN-04:03 | 94858.42 | 0.07 |
July | 0.00 | 0.00 | 0.871693E+11 | 0.835126E+11 | 153813.29 | 14-JUL-03:02 | 61165.89 | 0.46 |
August | 0.00 | 0.00 | 0.957187E+11 | 0.915961E+11 | 145034.14 | 01-AUG-03:02 | 75510.50 | 0.55 |
September | 0.00 | 0.00 | 0.834084E+11 | 0.787538E+11 | 145969.02 | 03-SEP-22:53 | 62992.77 | 0.47 |
October | 0.00 | 0.00 | 0.521004E+11 | 0.514751E+11 | 133315.29 | 03-OCT-03:02 | 61370.04 | 0.13 |
November | 0.00 | 0.00 | 0.281018E+11 | 0.260059E+11 | 105006.78 | 12-NOV-14:20 | 54375.87 | 0.09 |
December | 0.00 | 0.00 | 0.122277E+11 | 0.122274E+11 | 59720.13 | 26-DEC-13:10 | 59720.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.604860E+12 | 0.589683E+12 | 0.15 | |||
Minimum of Months | 0.00 | 0.00 | 0.393719E+10 | 0.392461E+10 | 39232.96 | 39232.96 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.957187E+11 | 0.915961E+11 | 153813.29 | 99713.80 | 0.55 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.539377E+10 | 0.539159E+10 | 2628.27 | 29-JAN-17:17 | 2628.27 | 0.00 |
February | 0.00 | 0.00 | 0.933101E+10 | 0.929022E+10 | 4438.22 | 20-FEB-17:05 | 4428.62 | 0.00 |
March | 0.00 | 0.00 | 0.156862E+11 | 0.156750E+11 | 7735.37 | 31-MAR-24:00 | 7735.37 | 0.00 |
April | 0.00 | 0.00 | 0.200632E+11 | 0.200632E+11 | 8167.94 | 16-APR-20:25 | 8167.94 | 0.00 |
May | 0.00 | 0.00 | 0.616173E+10 | 0.616173E+10 | 4037.81 | 31-MAY-23:57 | 4037.81 | 0.00 |
June | 0.00 | 0.00 | 0.110740E+11 | 0.110722E+11 | 5979.22 | 30-JUN-23:37 | 5979.22 | 0.00 |
July | 0.00 | 0.00 | 0.165840E+11 | 0.164291E+11 | 7896.12 | 31-JUL-23:53 | 7880.90 | 0.00 |
August | 0.00 | 0.00 | 0.213172E+11 | 0.211478E+11 | 8727.32 | 28-AUG-16:00 | 8147.22 | 0.00 |
September | 0.00 | 0.00 | 0.616631E+10 | 0.603672E+10 | 4058.95 | 30-SEP-24:00 | 4058.95 | 0.00 |
October | 0.00 | 0.00 | 0.110254E+11 | 0.109965E+11 | 5897.51 | 31-OCT-24:00 | 5897.51 | 0.00 |
November | 0.00 | 0.00 | 0.153388E+11 | 0.152942E+11 | 6616.84 | 14-NOV-16:50 | 6411.88 | 0.00 |
December | 0.00 | 0.00 | 0.205844E+11 | 0.205840E+11 | 8293.61 | 26-DEC-17:10 | 8293.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.158726E+12 | 0.158142E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.539377E+10 | 0.539159E+10 | 2628.27 | 2628.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.213172E+11 | 0.211478E+11 | 8727.32 | 8293.61 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.418049E+11 | 0.417828E+11 | 23782.17 | 24-JAN-17:00 | 23782.17 | 0.00 |
February | 0.00 | 0.00 | 0.790656E+11 | 0.786635E+11 | 40577.25 | 22-FEB-17:00 | 40257.16 | 0.00 |
March | 0.00 | 0.00 | 0.142892E+12 | 0.142779E+12 | 72242.55 | 31-MAR-24:00 | 72242.55 | 0.00 |
April | 0.00 | 0.00 | 0.190886E+12 | 0.190886E+12 | 77847.90 | 26-APR-17:50 | 77847.90 | 0.00 |
May | 0.00 | 0.00 | 0.574951E+11 | 0.574951E+11 | 39053.77 | 31-MAY-23:27 | 39053.77 | 0.00 |
June | 0.00 | 0.00 | 0.105065E+12 | 0.105047E+12 | 57492.24 | 30-JUN-23:57 | 57492.24 | 0.00 |
July | 0.00 | 0.00 | 0.157608E+12 | 0.156064E+12 | 75464.69 | 31-JUL-23:53 | 75316.20 | 0.00 |
August | 0.00 | 0.00 | 0.202880E+12 | 0.201191E+12 | 83234.28 | 28-AUG-16:00 | 77531.14 | 0.00 |
September | 0.00 | 0.00 | 0.571254E+11 | 0.558485E+11 | 39475.08 | 30-SEP-24:00 | 39475.08 | 0.00 |
October | 0.00 | 0.00 | 0.100895E+12 | 0.100607E+12 | 54609.90 | 31-OCT-24:00 | 54609.90 | 0.00 |
November | 0.00 | 0.00 | 0.138747E+12 | 0.138301E+12 | 62299.06 | 14-NOV-16:50 | 60264.35 | 0.00 |
December | 0.00 | 0.00 | 0.183825E+12 | 0.183820E+12 | 78272.34 | 26-DEC-17:00 | 78272.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.145829E+13 | 0.145248E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.418049E+11 | 0.417828E+11 | 23782.17 | 23782.17 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202880E+12 | 0.201191E+12 | 83234.28 | 78272.34 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.314806E+10 | 0.314610E+10 | 2393.58 | 24-JAN-17:00 | 2393.58 | 0.00 |
February | 0.00 | 0.00 | 0.678956E+10 | 0.675011E+10 | 4082.53 | 22-FEB-17:00 | 4050.33 | 0.00 |
March | 0.00 | 0.00 | 0.135712E+11 | 0.135600E+11 | 7040.79 | 31-MAR-23:30 | 7040.79 | 0.00 |
April | 0.00 | 0.00 | 0.191097E+11 | 0.191097E+11 | 7868.38 | 16-APR-19:53 | 7868.38 | 0.00 |
May | 0.00 | 0.00 | 0.582123E+10 | 0.582123E+10 | 3917.59 | 31-MAY-23:33 | 3917.59 | 0.00 |
June | 0.00 | 0.00 | 0.107059E+11 | 0.107041E+11 | 5815.38 | 30-JUN-23:30 | 5815.38 | 0.00 |
July | 0.00 | 0.00 | 0.159714E+11 | 0.158170E+11 | 7621.87 | 31-JUL-23:53 | 7606.88 | 0.00 |
August | 0.00 | 0.00 | 0.204619E+11 | 0.202927E+11 | 8379.16 | 28-AUG-15:50 | 7834.41 | 0.00 |
September | 0.00 | 0.00 | 0.582160E+10 | 0.569358E+10 | 3993.91 | 30-SEP-24:00 | 3993.91 | 0.00 |
October | 0.00 | 0.00 | 0.971649E+10 | 0.968778E+10 | 5268.83 | 31-OCT-24:00 | 5268.83 | 0.00 |
November | 0.00 | 0.00 | 0.129790E+11 | 0.129347E+11 | 6235.06 | 14-NOV-16:50 | 6031.49 | 0.00 |
December | 0.00 | 0.00 | 0.168988E+11 | 0.168984E+11 | 7804.69 | 22-DEC-17:10 | 7804.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.140995E+12 | 0.140415E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.314806E+10 | 0.314610E+10 | 2393.58 | 2393.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.204619E+11 | 0.202927E+11 | 8379.16 | 7868.38 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1662.20 | 729786.03 | 02-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2026.79 | 418845.05 | 13-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1625.60 | 403231.37 | 27-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.23 | 161.63 | 01-APR-06:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 179.11 | 64902.55 | 25-OCT-06:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 866.67 | 474806.41 | 24-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8296.43 | 925675.53 | 07-DEC-06:01 |
Annual Sum or Average | 0.00 | 1225.81 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 8296.43 | 925675.53 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 249179.53 | 1277835.50 | 26-JAN-15:10 | 53.51 | 257582.58 | 17-JAN-04:03 |
February | 76270.92 | 1052454.82 | 22-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 247624.64 | 1536895.05 | 20-MAR-16:00 | 22.46 | 148519.47 | 18-MAR-04:03 |
April | 564596.37 | 1399991.79 | 14-APR-15:30 | 11.66 | 55381.00 | 02-APR-04:33 |
May | 662757.65 | 1412738.29 | 18-MAY-15:20 | 162.27 | 275087.73 | 13-MAY-03:02 |
June | 882950.65 | 1797228.17 | 29-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 847080.91 | 2753612.91 | 14-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 852149.53 | 2317419.13 | 01-AUG-05:02 | 2.25 | 30114.50 | 05-AUG-18:00 |
September | 732838.19 | 2580820.76 | 08-SEP-05:02 | 10.66 | 87935.70 | 16-SEP-03:02 |
October | 459898.84 | 2083095.96 | 03-OCT-05:03 | 64.45 | 159728.30 | 08-OCT-08:13 |
November | 256940.13 | 1298636.46 | 13-NOV-06:04 | 17.78 | 56745.83 | 19-NOV-23:42 |
December | 134420.68 | 1280037.32 | 22-DEC-16:50 | 30.88 | 208660.60 | 11-DEC-05:23 |
Annual Sum or Average | 499457.02 | 31.82 | ||||
Minimum of Months | 76270.92 | 1052454.82 | 0.00 | 0.00 | ||
Maximum of Months | 882950.65 | 2753612.91 | 162.27 | 275087.73 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 165352.00 | 1083680.08 | 31-JAN-16:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 44473.93 | 646934.04 | 22-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 161522.92 | 1334869.66 | 20-MAR-14:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 434320.58 | 1405191.46 | 29-APR-05:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 536696.32 | 2126590.39 | 08-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 727259.93 | 2621063.59 | 29-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 696197.01 | 3926457.48 | 15-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 711102.50 | 3999304.95 | 01-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 610562.61 | 3840880.93 | 08-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 349590.02 | 3000323.47 | 03-OCT-05:03 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 182245.20 | 2210469.28 | 13-NOV-06:02 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 82890.09 | 957090.43 | 22-DEC-16:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 393646.02 | 0.00 | ||||
Minimum of Months | 44473.93 | 646934.04 | 0.00 | 0.00 | ||
Maximum of Months | 727259.93 | 3999304.95 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 35979.96 | 148118.57 | 31-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 50284.63 | 91841.52 | 22-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 95620.07 | 208008.18 | 16-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 181635.66 | 300643.16 | 14-APR-16:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 119097.19 | 233414.86 | 31-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 202057.71 | 324069.06 | 16-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 225537.09 | 335881.72 | 19-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 248540.51 | 362547.96 | 25-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 132479.40 | 248017.07 | 08-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 104106.20 | 262385.26 | 01-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 94109.07 | 209964.65 | 01-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 109880.47 | 206517.63 | 22-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 133748.03 | 0.00 | ||||
Minimum of Months | 35979.96 | 91841.52 | 0.00 | 0.00 | ||
Maximum of Months | 248540.51 | 362547.96 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 13406.70 | 44356.07 | 24-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13362.76 | 44275.61 | 01-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 13484.34 | 43031.02 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11826.85 | 40011.87 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 11176.54 | 36788.88 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 10560.53 | 33497.26 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 9456.34 | 31278.98 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 10345.36 | 32173.50 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 10393.15 | 34743.95 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 11279.46 | 38418.01 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12394.74 | 41621.65 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12750.92 | 43723.64 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 11693.98 | ||||
Minimum of Months | 0.00 | 0.00 | 9456.34 | 31278.98 | ||
Maximum of Months | 0.00 | 0.00 | 13484.34 | 44356.07 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 166479.44 | 1061170.50 | 31-JAN-16:30 | 841.70 | 98945.83 | 02-JAN-10:10 |
February | 43877.01 | 622132.90 | 22-FEB-16:00 | 1122.47 | 97106.76 | 02-FEB-13:50 |
March | 168141.92 | 2167604.01 | 17-MAR-14:40 | 1326.54 | 102283.28 | 29-MAR-19:10 |
April | 497287.54 | 2351770.75 | 13-APR-15:40 | 2539.59 | 109311.29 | 22-APR-07:00 |
May | 641309.38 | 2369499.59 | 19-MAY-14:50 | 456.56 | 74994.10 | 01-MAY-02:70 |
June | 979679.82 | 3707033.69 | 17-JUN-15:00 | 78.26 | 41488.38 | 21-JUN-01:10 |
July | 1231169.73 | 4768760.27 | 14-JUL-05:07 | 149.29 | 58021.17 | 04-JUL-03:20 |
August | 1245231.68 | 4400321.29 | 16-AUG-11:00 | 98.99 | 48450.54 | 24-AUG-01:30 |
September | 973026.42 | 4527743.54 | 01-SEP-12:20 | 24.83 | 23791.65 | 29-SEP-01:00 |
October | 440365.06 | 3583651.60 | 03-OCT-09:30 | 918.74 | 108627.13 | 25-OCT-05:40 |
November | 180856.42 | 2176001.73 | 01-NOV-13:40 | 1067.88 | 104175.57 | 28-NOV-19:50 |
December | 83460.26 | 920281.22 | 22-DEC-16:00 | 1779.78 | 124395.79 | 04-DEC-06:50 |
Annual Sum or Average | 557301.22 | 864.29 | ||||
Minimum of Months | 43877.01 | 622132.90 | 24.83 | 23791.65 | ||
Maximum of Months | 1245231.68 | 4768760.27 | 2539.59 | 124395.79 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149649E+11 | 0.92 | 9287.77 | 01-JAN-00:10 | 1.53 |
February | 0.128310E+11 | 0.87 | 9287.77 | 01-FEB-04:10 | 1.54 |
March | 0.148484E+11 | 0.91 | 9287.77 | 01-MAR-05:00 | 1.53 |
April | 0.138717E+11 | 0.88 | 9287.77 | 01-APR-04:05 | 1.53 |
May | 0.146015E+11 | 0.90 | 9287.77 | 01-MAY-03:03 | 1.54 |
June | 0.146473E+11 | 0.93 | 9287.77 | 01-JUN-03:02 | 1.52 |
July | 0.150916E+11 | 0.92 | 9287.77 | 01-JUL-03:02 | 1.54 |
August | 0.164160E+11 | 1.00 | 9287.77 | 01-AUG-03:02 | 1.51 |
September | 0.157519E+11 | 0.99 | 9287.77 | 01-SEP-03:02 | 1.52 |
October | 0.160869E+11 | 0.99 | 9287.77 | 01-OCT-11:48 | 1.53 |
November | 0.152504E+11 | 0.97 | 9287.77 | 01-NOV-03:02 | 1.52 |
December | 0.154525E+11 | 0.95 | 9287.77 | 01-DEC-04:03 | 1.53 |
Annual Sum or Average | 0.179814E+12 | 0.94 | |||
Minimum of Months | 0.128310E+11 | 0.87 | 9287.77 | 1.51 | |
Maximum of Months | 0.164160E+11 | 1.00 | 9287.77 | 1.54 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.577217E+10 | 0.41 | 10249.46 | 17-JAN-17:00 | 1.26 |
February | 0.509209E+10 | 0.40 | 10534.62 | 21-FEB-15:50 | 1.27 |
March | 0.761577E+10 | 0.49 | 12264.14 | 20-MAR-14:40 | 1.39 |
April | 0.116801E+11 | 0.71 | 20051.77 | 15-APR-05:03 | 1.90 |
May | 0.107427E+11 | 0.63 | 20854.65 | 08-MAY-05:02 | 1.95 |
June | 0.136318E+11 | 0.78 | 20854.65 | 01-JUN-05:02 | 1.94 |
July | 0.140302E+11 | 0.77 | 20854.65 | 01-JUL-05:03 | 1.96 |
August | 0.154264E+11 | 0.81 | 20854.65 | 01-AUG-05:02 | 1.93 |
September | 0.103475E+11 | 0.62 | 20854.65 | 05-SEP-04:12 | 1.93 |
October | 0.872913E+10 | 0.54 | 20854.65 | 02-OCT-04:42 | 1.93 |
November | 0.749009E+10 | 0.49 | 15224.96 | 02-NOV-05:02 | 1.59 |
December | 0.674851E+10 | 0.45 | 12864.38 | 26-DEC-17:00 | 1.44 |
Annual Sum or Average | 0.117306E+12 | 0.60 | |||
Minimum of Months | 0.509209E+10 | 0.40 | 10249.46 | 1.26 | |
Maximum of Months | 0.154264E+11 | 0.81 | 20854.65 | 1.96 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.386142E+11 | 0.35 | 80525.54 | 04-JAN-06:02 | 1.13 |
February | 0.317189E+11 | 0.33 | 80525.54 | 01-FEB-06:02 | 1.13 |
March | 0.445438E+11 | 0.38 | 88818.11 | 27-MAR-05:03 | 1.20 |
April | 0.749682E+11 | 0.52 | 194423.83 | 12-APR-05:02 | 1.95 |
May | 0.905043E+11 | 0.58 | 194423.83 | 04-MAY-05:02 | 1.96 |
June | 0.107676E+12 | 0.69 | 194423.83 | 01-JUN-05:02 | 1.94 |
July | 0.983038E+11 | 0.62 | 194423.83 | 03-JUL-05:02 | 1.96 |
August | 0.102199E+12 | 0.63 | 194423.83 | 01-AUG-05:02 | 1.93 |
September | 0.811342E+11 | 0.54 | 194423.83 | 02-SEP-05:02 | 1.93 |
October | 0.584378E+11 | 0.43 | 194423.83 | 02-OCT-05:02 | 1.94 |
November | 0.416690E+11 | 0.36 | 117832.94 | 01-NOV-05:03 | 1.41 |
December | 0.341601E+11 | 0.33 | 102033.67 | 06-DEC-06:02 | 1.31 |
Annual Sum or Average | 0.803930E+12 | 0.48 | |||
Minimum of Months | 0.317189E+11 | 0.33 | 80525.54 | 1.13 | |
Maximum of Months | 0.107676E+12 | 0.69 | 194423.83 | 1.96 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.331723E+10 | 0.32 | 6091.91 | 27-JAN-17:00 | 0.91 |
February | 0.265666E+10 | 0.31 | 5099.01 | 22-FEB-16:30 | 0.82 |
March | 0.369337E+10 | 0.34 | 8890.78 | 16-MAR-15:50 | 1.12 |
April | 0.763909E+10 | 0.50 | 16729.92 | 12-APR-05:02 | 1.66 |
May | 0.969739E+10 | 0.57 | 21530.87 | 08-MAY-05:02 | 1.95 |
June | 0.128176E+11 | 0.73 | 21530.87 | 01-JUN-05:02 | 1.94 |
July | 0.114923E+11 | 0.65 | 21530.87 | 05-JUL-05:02 | 1.95 |
August | 0.116936E+11 | 0.65 | 21530.87 | 01-AUG-05:02 | 1.93 |
September | 0.875375E+10 | 0.54 | 21530.87 | 02-SEP-05:02 | 1.93 |
October | 0.540683E+10 | 0.40 | 21530.87 | 02-OCT-05:02 | 1.94 |
November | 0.348079E+10 | 0.33 | 8632.35 | 01-NOV-05:03 | 1.09 |
December | 0.298210E+10 | 0.31 | 5033.98 | 22-DEC-16:50 | 0.82 |
Annual Sum or Average | 0.836306E+11 | 0.47 | |||
Minimum of Months | 0.265666E+10 | 0.31 | 5033.98 | 0.82 | |
Maximum of Months | 0.128176E+11 | 0.73 | 21530.87 | 1.95 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.152012E+10 | 1.01 | 567.55 | 01-JAN-00:05 | 1.01 |
February | 0.137301E+10 | 1.01 | 567.55 | 01-FEB-00:10 | 1.01 |
March | 0.152012E+10 | 1.01 | 567.55 | 01-MAR-00:10 | 1.01 |
April | 0.147108E+10 | 1.01 | 567.55 | 01-APR-00:10 | 1.01 |
May | 0.152012E+10 | 1.01 | 567.55 | 01-MAY-00:10 | 1.01 |
June | 0.147108E+10 | 1.01 | 567.55 | 01-JUN-00:03 | 1.01 |
July | 0.152012E+10 | 1.01 | 567.55 | 01-JUL-00:03 | 1.01 |
August | 0.152012E+10 | 1.00 | 567.55 | 01-AUG-00:03 | 1.00 |
September | 0.147108E+10 | 1.00 | 567.55 | 01-SEP-00:05 | 1.00 |
October | 0.152012E+10 | 1.01 | 567.55 | 01-OCT-00:03 | 1.01 |
November | 0.147108E+10 | 1.01 | 567.55 | 01-NOV-00:10 | 1.01 |
December | 0.152012E+10 | 1.01 | 567.55 | 01-DEC-00:10 | 1.01 |
Annual Sum or Average | 0.178982E+11 | 1.01 | |||
Minimum of Months | 0.137301E+10 | 1.00 | 567.55 | 1.00 | |
Maximum of Months | 0.152012E+10 | 1.01 | 567.55 | 1.01 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144611E+11 | 1.01 | 5399.15 | 01-JAN-00:10 | 1.01 |
February | 0.130616E+11 | 1.01 | 5399.15 | 01-FEB-00:10 | 1.01 |
March | 0.144611E+11 | 1.01 | 5399.15 | 01-MAR-00:10 | 1.01 |
April | 0.139946E+11 | 1.01 | 5399.15 | 01-APR-00:10 | 1.01 |
May | 0.144611E+11 | 1.01 | 5399.15 | 01-MAY-00:10 | 1.01 |
June | 0.139946E+11 | 1.01 | 5399.15 | 01-JUN-00:03 | 1.01 |
July | 0.144611E+11 | 1.01 | 5399.15 | 01-JUL-00:03 | 1.01 |
August | 0.144611E+11 | 1.00 | 5399.15 | 01-AUG-00:03 | 1.00 |
September | 0.139946E+11 | 1.00 | 5399.15 | 01-SEP-00:05 | 1.00 |
October | 0.144611E+11 | 1.01 | 5399.15 | 01-OCT-00:03 | 1.01 |
November | 0.139946E+11 | 1.01 | 5399.15 | 01-NOV-00:10 | 1.01 |
December | 0.144611E+11 | 1.01 | 5399.15 | 01-DEC-00:10 | 1.01 |
Annual Sum or Average | 0.170268E+12 | 1.01 | |||
Minimum of Months | 0.130616E+11 | 1.00 | 5399.15 | 1.00 | |
Maximum of Months | 0.144611E+11 | 1.01 | 5399.15 | 1.01 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147392E+10 | 1.01 | 550.30 | 01-JAN-00:05 | 1.01 |
February | 0.133128E+10 | 1.01 | 550.30 | 01-FEB-00:10 | 1.01 |
March | 0.147392E+10 | 1.01 | 550.30 | 01-MAR-00:10 | 1.01 |
April | 0.142637E+10 | 1.01 | 550.30 | 01-APR-00:10 | 1.01 |
May | 0.147392E+10 | 1.01 | 550.30 | 01-MAY-00:10 | 1.01 |
June | 0.142637E+10 | 1.01 | 550.30 | 01-JUN-00:03 | 1.01 |
July | 0.147392E+10 | 1.01 | 550.30 | 01-JUL-00:03 | 1.01 |
August | 0.147392E+10 | 1.00 | 550.30 | 01-AUG-00:03 | 1.00 |
September | 0.142637E+10 | 1.00 | 550.30 | 01-SEP-00:05 | 1.00 |
October | 0.147392E+10 | 1.01 | 550.30 | 01-OCT-00:03 | 1.01 |
November | 0.142637E+10 | 1.01 | 550.30 | 01-NOV-00:10 | 1.01 |
December | 0.147392E+10 | 1.01 | 550.30 | 01-DEC-00:10 | 1.01 |
Annual Sum or Average | 0.173542E+11 | 1.01 | |||
Minimum of Months | 0.133128E+10 | 1.00 | 550.30 | 1.00 | |
Maximum of Months | 0.147392E+10 | 1.01 | 550.30 | 1.01 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 20357659.56 | 18505112.54 | 2770.00 | 02-JAN-06:01 | 2517.93 | 2517.93 | 41.89 | 4.54 |
February | 20732725.10 | 18846047.12 | 1639.82 | 13-FEB-06:03 | 1490.59 | 1490.59 | 31.53 | 2.08 |
March | 18779333.48 | 17070414.13 | 1602.08 | 27-MAR-05:03 | 1456.29 | 1456.29 | 32.84 | 2.02 |
April | 2631.93 | 2392.43 | 0.72 | 01-APR-06:10 | 0.66 | 0.66 | 27.26 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 27.24 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 27.24 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 27.24 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 27.24 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 27.24 | 0.00 |
October | 2049633.94 | 1863117.25 | 273.09 | 25-OCT-07:00 | 248.23 | 248.23 | 26.78 | 0.29 |
November | 9770185.91 | 8881098.99 | 1828.86 | 24-NOV-06:03 | 1662.43 | 1662.43 | 33.11 | 2.39 |
December | 97644817.94 | 88759139.50 | 2953.88 | 07-DEC-06:01 | 2685.08 | 2685.08 | 38.53 | 5.19 |
Annual Sum or Average | 0.169337E+09 | 0.153927E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.78 | 0.00 | |
Maximum of Months | 97644817.94 | 88759139.50 | 2953.88 | 2685.08 | 2685.08 | 41.89 | 5.19 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.189323E+09 | 0.172095E+09 | 749.55 | 27-JAN-15:50 | 681.34 | 681.34 | 7.24 | 23.91 |
February | 37165445.65 | 33783390.10 | 395.89 | 10-FEB-06:03 | 359.86 | 359.86 | 8.46 | 17.47 |
March | 0.181358E+09 | 0.164854E+09 | 2954.73 | 17-MAR-14:40 | 2685.85 | 2685.85 | 7.12 | 44.69 |
April | 0.481665E+09 | 0.437834E+09 | 1652.61 | 29-APR-05:03 | 1502.22 | 1502.22 | 8.33 | 34.54 |
May | 0.635566E+09 | 0.577730E+09 | 3217.38 | 08-MAY-05:02 | 2924.60 | 2924.60 | 7.98 | 46.37 |
June | 0.130407E+10 | 0.118540E+10 | 6996.52 | 19-JUN-14:10 | 6359.84 | 6359.84 | 6.72 | 64.38 |
July | 0.144589E+10 | 0.131432E+10 | 20265.22 | 13-JUL-05:03 | 18421.08 | 18421.08 | 7.68 | 98.74 |
August | 0.169205E+10 | 0.153808E+10 | 20265.22 | 01-AUG-05:02 | 18421.08 | 18421.08 | 7.67 | 98.74 |
September | 0.145904E+10 | 0.132627E+10 | 20265.22 | 02-SEP-05:02 | 18421.08 | 18421.08 | 7.35 | 98.74 |
October | 0.760456E+09 | 0.691255E+09 | 18176.11 | 02-OCT-05:02 | 16522.08 | 16522.08 | 7.33 | 94.60 |
November | 0.289494E+09 | 0.263150E+09 | 7444.54 | 13-NOV-06:02 | 6767.08 | 6767.08 | 8.77 | 66.04 |
December | 80707999.61 | 73363571.65 | 681.24 | 22-DEC-16:00 | 619.25 | 619.25 | 7.45 | 22.84 |
Annual Sum or Average | 0.855679E+10 | 0.777812E+10 | ||||||
Minimum of Months | 37165445.65 | 33783390.10 | 395.89 | 359.86 | 359.86 | 6.72 | 17.47 | |
Maximum of Months | 0.169205E+10 | 0.153808E+10 | 20265.22 | 18421.08 | 18421.08 | 8.77 | 98.74 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.152983E+11 | 0.139062E+11 | 13948.00 | 01-JAN-14:30 | 12678.73 | 12678.73 | 8.43 | 98.74 |
February | 0.919257E+10 | 0.835604E+10 | 13948.00 | 01-FEB-12:30 | 12678.73 | 12678.73 | 8.47 | 98.74 |
March | 0.174616E+11 | 0.158726E+11 | 13948.00 | 01-MAR-05:03 | 12678.73 | 12678.73 | 8.74 | 98.74 |
April | 0.297577E+11 | 0.270497E+11 | 13948.00 | 01-APR-03:02 | 12678.73 | 12678.73 | 8.49 | 98.74 |
May | 0.293679E+11 | 0.266954E+11 | 13948.00 | 01-MAY-00:10 | 12678.73 | 12678.73 | 7.96 | 98.74 |
June | 0.346537E+11 | 0.315002E+11 | 13948.00 | 01-JUN-00:23 | 12678.73 | 12678.73 | 7.06 | 98.74 |
July | 0.353317E+11 | 0.321165E+11 | 13948.00 | 01-JUL-00:03 | 12678.73 | 12678.73 | 7.88 | 98.74 |
August | 0.348988E+11 | 0.317230E+11 | 13948.00 | 01-AUG-00:03 | 12678.73 | 12678.73 | 8.57 | 98.74 |
September | 0.288712E+11 | 0.262440E+11 | 13948.00 | 01-SEP-00:05 | 12678.73 | 12678.73 | 6.99 | 98.74 |
October | 0.235236E+11 | 0.213829E+11 | 13948.00 | 01-OCT-01:12 | 12678.73 | 12678.73 | 7.24 | 98.74 |
November | 0.167913E+11 | 0.152633E+11 | 13948.00 | 01-NOV-03:02 | 12678.73 | 12678.73 | 8.80 | 98.74 |
December | 0.117177E+11 | 0.106514E+11 | 13948.00 | 01-DEC-06:03 | 12678.73 | 12678.73 | 8.72 | 98.74 |
Annual Sum or Average | 0.286866E+12 | 0.260761E+12 | ||||||
Minimum of Months | 0.919257E+10 | 0.835604E+10 | 13948.00 | 12678.73 | 12678.73 | 6.99 | 98.74 | |
Maximum of Months | 0.353317E+11 | 0.321165E+11 | 13948.00 | 12678.73 | 12678.73 | 8.80 | 98.74 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.177527E+10 | 0.161372E+10 | 662.81 | 01-JAN-00:05 | 602.49 | 602.49 | 19.76 | 2.80 |
February | 0.160347E+10 | 0.145755E+10 | 662.81 | 01-FEB-00:10 | 602.49 | 602.49 | 23.51 | 2.80 |
March | 0.177527E+10 | 0.161372E+10 | 662.81 | 01-MAR-00:10 | 602.49 | 602.49 | 26.02 | 2.80 |
April | 0.171800E+10 | 0.156166E+10 | 662.81 | 01-APR-00:10 | 602.49 | 602.49 | 29.34 | 2.80 |
May | 0.177527E+10 | 0.161372E+10 | 662.81 | 01-MAY-00:10 | 602.49 | 602.49 | 23.13 | 2.80 |
June | 0.171800E+10 | 0.156166E+10 | 662.81 | 01-JUN-00:03 | 602.49 | 602.49 | 33.01 | 2.80 |
July | 0.177527E+10 | 0.161372E+10 | 662.81 | 01-JUL-00:03 | 602.49 | 602.49 | 38.21 | 2.80 |
August | 0.177527E+10 | 0.161372E+10 | 662.81 | 01-AUG-00:03 | 602.49 | 602.49 | 42.96 | 2.80 |
September | 0.171800E+10 | 0.156166E+10 | 662.81 | 01-SEP-00:05 | 602.49 | 602.49 | 30.26 | 2.80 |
October | 0.177527E+10 | 0.161372E+10 | 662.81 | 01-OCT-00:03 | 602.49 | 602.49 | 32.23 | 2.80 |
November | 0.171800E+10 | 0.156166E+10 | 662.81 | 01-NOV-00:10 | 602.49 | 602.49 | 26.68 | 2.80 |
December | 0.177527E+10 | 0.161372E+10 | 662.81 | 01-DEC-00:10 | 602.49 | 602.49 | 28.66 | 2.80 |
Annual Sum or Average | 0.209023E+11 | 0.190002E+11 | ||||||
Minimum of Months | 0.160347E+10 | 0.145755E+10 | 662.81 | 602.49 | 602.49 | 19.76 | 2.80 | |
Maximum of Months | 0.177527E+10 | 0.161372E+10 | 662.81 | 602.49 | 602.49 | 42.96 | 2.80 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:05 | 1.79 | 1.79 | 55.90 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:02 | 1.79 | 1.79 | 56.83 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:02 | 1.79 | 1.79 | 56.81 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:03 | 1.79 | 1.79 | 56.03 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:02 | 1.79 | 1.79 | 57.40 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:02 | 1.79 | 1.79 | 57.83 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:03 | 1.79 | 1.79 | 56.67 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:02 | 1.79 | 1.79 | 56.52 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 56.74 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 56.68 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:03 | 1.79 | 1.79 | 57.03 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:03 | 1.79 | 1.79 | 56.26 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.90 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 57.83 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.195818E+11 | 0.177999E+11 | 34681.80 | 31-JAN-17:10 | 31525.75 | 31525.75 | 22.87 | 116.54 |
February | 0.114194E+11 | 0.103802E+11 | 17350.60 | 22-FEB-16:00 | 15771.69 | 15771.69 | 23.65 | 58.27 |
March | 0.224890E+11 | 0.204425E+11 | 34750.95 | 17-MAR-14:40 | 31588.61 | 31588.61 | 25.55 | 116.54 |
April | 0.433512E+11 | 0.394062E+11 | 34761.96 | 13-APR-15:40 | 31598.62 | 31598.62 | 25.93 | 116.54 |
May | 0.462716E+11 | 0.420609E+11 | 34763.02 | 19-MAY-14:50 | 31599.59 | 31599.59 | 25.96 | 116.54 |
June | 0.591522E+11 | 0.537694E+11 | 34843.21 | 17-JUN-15:00 | 31672.48 | 31672.48 | 28.71 | 116.54 |
July | 0.586955E+11 | 0.533542E+11 | 34846.07 | 13-JUL-12:40 | 31675.07 | 31675.07 | 28.94 | 116.54 |
August | 0.592729E+11 | 0.538791E+11 | 34846.07 | 01-AUG-13:20 | 31675.07 | 31675.07 | 28.97 | 116.54 |
September | 0.474672E+11 | 0.431477E+11 | 34846.07 | 01-SEP-09:40 | 31675.07 | 31675.07 | 28.95 | 116.54 |
October | 0.345040E+11 | 0.313641E+11 | 34835.80 | 03-OCT-09:30 | 31665.74 | 31665.74 | 28.46 | 116.54 |
November | 0.217221E+11 | 0.197453E+11 | 34751.45 | 01-NOV-13:40 | 31589.07 | 31589.07 | 25.57 | 116.54 |
December | 0.147815E+11 | 0.134364E+11 | 34681.04 | 22-DEC-16:50 | 31525.06 | 31525.06 | 22.84 | 116.54 |
Annual Sum or Average | 0.438708E+12 | 0.398786E+12 | ||||||
Minimum of Months | 0.114194E+11 | 0.103802E+11 | 17350.60 | 15771.69 | 15771.69 | 22.84 | 58.27 | |
Maximum of Months | 0.592729E+11 | 0.538791E+11 | 34846.07 | 31675.07 | 31675.07 | 28.97 | 116.54 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.73 | 57.73 | 1662.20 | 729786.03 | 02-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 24.27 | 24.27 | 2026.79 | 418845.05 | 13-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.23 | 25.23 | 1625.60 | 403231.37 | 27-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.27 | 27.27 | 0.23 | 161.63 | 01-APR-06:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 27.24 | 27.24 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 27.24 | 27.24 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.24 | 27.24 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 27.24 | 27.24 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.24 | 27.24 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.24 | 27.24 | 179.11 | 64902.55 | 25-OCT-06:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 24.38 | 24.38 | 866.67 | 474806.41 | 24-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 25.53 | 25.53 | 8296.43 | 925675.53 | 07-DEC-06:01 |
Annual Sum or Average | 0.00 | 1225.81 | ||||||
Minimum of Months | 0.00 | 0.00 | 24.27 | 24.27 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 57.73 | 57.73 | 8296.43 | 925675.53 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 249179.53 | 1277835.50 | 26-JAN-15:10 | 10.17 | 8.50 | 53.51 | 257582.58 | 17-JAN-04:03 |
February | 76270.92 | 1052454.82 | 22-FEB-16:00 | 10.10 | 8.81 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 247624.64 | 1536895.05 | 20-MAR-16:00 | 10.41 | 8.11 | 22.46 | 148519.47 | 18-MAR-04:03 |
April | 564596.37 | 1399991.79 | 14-APR-15:30 | 10.08 | 6.70 | 11.66 | 55381.00 | 02-APR-04:33 |
May | 662757.65 | 1412738.29 | 18-MAY-15:20 | 10.11 | 6.70 | 162.27 | 275087.73 | 13-MAY-03:02 |
June | 882950.65 | 1797228.17 | 29-JUN-05:02 | 11.04 | 6.70 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 847080.91 | 2753612.91 | 14-JUL-05:03 | 13.77 | 8.05 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 852149.53 | 2317419.13 | 01-AUG-05:02 | 12.71 | 7.11 | 2.25 | 30114.50 | 05-AUG-18:00 |
September | 732838.19 | 2580820.76 | 08-SEP-05:02 | 13.23 | 7.51 | 10.66 | 87935.70 | 16-SEP-03:02 |
October | 459898.84 | 2083095.96 | 03-OCT-05:03 | 12.44 | 7.41 | 64.45 | 159728.30 | 08-OCT-08:13 |
November | 256940.13 | 1298636.46 | 13-NOV-06:04 | 11.32 | 8.18 | 17.78 | 56745.83 | 19-NOV-23:42 |
December | 134420.68 | 1280037.32 | 22-DEC-16:50 | 10.17 | 8.50 | 30.88 | 208660.60 | 11-DEC-05:23 |
Annual Sum or Average | 499457.02 | 31.82 | ||||||
Minimum of Months | 76270.92 | 1052454.82 | 10.08 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 882950.65 | 2753612.91 | 13.77 | 8.81 | 162.27 | 275087.73 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 165352.00 | 1083680.08 | 31-JAN-16:30 | 18.34 | 7.99 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 44473.93 | 646934.04 | 22-FEB-16:00 | 17.79 | 8.78 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 161522.92 | 1334869.66 | 20-MAR-14:10 | 14.08 | 6.84 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 434320.58 | 1405191.46 | 29-APR-05:03 | 16.42 | 8.59 | 0.00 | 0.00 | 01-APR-00:10 |
May | 536696.32 | 2126590.39 | 08-MAY-05:02 | 17.66 | 7.73 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 727259.93 | 2621063.59 | 29-JUN-05:02 | 19.00 | 7.18 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 696197.01 | 3926457.48 | 15-JUL-05:03 | 16.43 | 7.45 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 711102.50 | 3999304.95 | 01-AUG-05:02 | 16.38 | 7.28 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 610562.61 | 3840880.93 | 08-SEP-05:02 | 16.00 | 7.82 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 349590.02 | 3000323.47 | 03-OCT-05:03 | 15.69 | 7.78 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 182245.20 | 2210469.28 | 13-NOV-06:02 | 14.70 | 8.92 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 82890.09 | 957090.43 | 22-DEC-16:00 | 16.72 | 8.06 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 393646.02 | 0.00 | ||||||
Minimum of Months | 44473.93 | 646934.04 | 14.08 | 6.84 | 0.00 | 0.00 | ||
Maximum of Months | 727259.93 | 3999304.95 | 19.00 | 8.92 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 35979.96 | 148118.57 | 31-JAN-17:00 | 33.41 | 29.46 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 50284.63 | 91841.52 | 22-FEB-16:00 | 27.73 | 21.69 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 95620.07 | 208008.18 | 16-MAR-16:00 | 39.39 | 29.92 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 181635.66 | 300643.16 | 14-APR-16:10 | 48.50 | 36.45 | 0.00 | 0.00 | 01-APR-00:10 |
May | 119097.19 | 233414.86 | 31-MAY-16:00 | 41.90 | 37.52 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 202057.71 | 324069.06 | 16-JUN-16:00 | 50.78 | 42.95 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 225537.09 | 335881.72 | 19-JUL-14:00 | 51.93 | 41.29 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 248540.51 | 362547.96 | 25-AUG-16:10 | 54.52 | 42.47 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 132479.40 | 248017.07 | 08-SEP-16:00 | 43.34 | 38.84 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 104106.20 | 262385.26 | 01-OCT-14:00 | 44.76 | 37.83 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 94109.07 | 209964.65 | 01-NOV-15:00 | 39.58 | 30.12 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 109880.47 | 206517.63 | 22-DEC-15:00 | 39.24 | 27.40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 133748.03 | 0.00 | ||||||
Minimum of Months | 35979.96 | 91841.52 | 27.73 | 21.69 | 0.00 | 0.00 | ||
Maximum of Months | 248540.51 | 362547.96 | 54.52 | 42.95 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.27 | 57.27 | 13406.70 | 44356.07 | 24-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.29 | 57.29 | 13362.76 | 44275.61 | 01-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.29 | 57.29 | 13484.34 | 43031.02 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.54 | 56.54 | 11826.85 | 40011.87 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.41 | 58.41 | 11176.54 | 36788.88 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 58.15 | 58.15 | 10560.53 | 33497.26 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 57.21 | 57.21 | 9456.34 | 31278.98 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 56.78 | 56.78 | 10345.36 | 32173.50 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 57.15 | 57.15 | 10393.15 | 34743.95 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 57.33 | 57.33 | 11279.46 | 38418.01 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.50 | 57.50 | 12394.74 | 41621.65 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.77 | 56.77 | 12750.92 | 43723.64 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 11693.98 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.54 | 56.54 | 9456.34 | 31278.98 | ||
Maximum of Months | 0.00 | 0.00 | 58.41 | 58.41 | 13484.34 | 44356.07 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 166479.44 | 1061170.50 | 31-JAN-16:30 | 25.46 | 21.10 | 841.70 | 98945.83 | 02-JAN-10:10 |
February | 43877.01 | 622132.90 | 22-FEB-16:00 | 23.65 | 21.10 | 1122.47 | 97106.76 | 02-FEB-13:50 |
March | 168141.92 | 2167604.01 | 17-MAR-14:40 | 25.55 | 21.10 | 1326.54 | 102283.28 | 29-MAR-19:10 |
April | 497287.54 | 2351770.75 | 13-APR-15:40 | 25.93 | 21.31 | 2539.59 | 109311.29 | 22-APR-07:00 |
May | 641309.38 | 2369499.59 | 19-MAY-14:50 | 25.96 | 21.25 | 456.56 | 74994.10 | 01-MAY-02:70 |
June | 979679.82 | 3707033.69 | 17-JUN-15:00 | 28.71 | 25.55 | 78.26 | 41488.38 | 21-JUN-01:10 |
July | 1231169.73 | 4768760.27 | 14-JUL-05:07 | 30.89 | 26.39 | 149.29 | 58021.17 | 04-JUL-03:20 |
August | 1245231.68 | 4400321.29 | 16-AUG-11:00 | 30.13 | 26.24 | 98.99 | 48450.54 | 24-AUG-01:30 |
September | 973026.42 | 4527743.54 | 01-SEP-12:20 | 30.39 | 26.34 | 24.83 | 23791.65 | 29-SEP-01:00 |
October | 440365.06 | 3583651.60 | 03-OCT-09:30 | 28.46 | 24.87 | 918.74 | 108627.13 | 25-OCT-05:40 |
November | 180856.42 | 2176001.73 | 01-NOV-13:40 | 25.57 | 21.79 | 1067.88 | 104175.57 | 28-NOV-19:50 |
December | 83460.26 | 920281.22 | 22-DEC-16:00 | 24.88 | 21.10 | 1779.78 | 124395.79 | 04-DEC-06:50 |
Annual Sum or Average | 557301.22 | 864.29 | ||||||
Minimum of Months | 43877.01 | 622132.90 | 23.65 | 21.10 | 24.83 | 23791.65 | ||
Maximum of Months | 1245231.68 | 4768760.27 | 30.89 | 26.39 | 2539.59 | 124395.79 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 19025708.51 | 0.00 | 0.357209E+11 | 0.577217E+10 | 0.00 | 0.00 |
February | 22723018.61 | 0.00 | 0.906358E+10 | 0.509209E+10 | 0.00 | 0.00 |
March | 76255243.69 | 0.00 | 0.395181E+11 | 0.761577E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.103555E+12 | 0.116801E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.116999E+12 | 0.107427E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.160237E+12 | 0.136318E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.169526E+12 | 0.140302E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.178193E+12 | 0.154264E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.132989E+12 | 0.103475E+11 | 0.00 | 0.00 |
October | 2467236.08 | 0.00 | 0.803420E+11 | 0.872913E+10 | 0.00 | 0.00 |
November | 2454501.85 | 0.00 | 0.422354E+11 | 0.749009E+10 | 0.00 | 0.00 |
December | 0.324504E+09 | 0.00 | 0.206936E+11 | 0.674851E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.447429E+09 | 0.00 | 0.108907E+13 | 0.117306E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.906358E+10 | 0.509209E+10 | 0.00 | 0.00 |
Maximum of Months | 0.324504E+09 | 0.00 | 0.178193E+12 | 0.154264E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.244544E+10 | 0.00 | 0.292150E+12 | 0.386142E+11 | 0.00 | 0.00 |
February | 0.246715E+10 | 0.00 | 0.662999E+11 | 0.317189E+11 | 0.00 | 0.00 |
March | 0.279329E+10 | 0.00 | 0.285485E+12 | 0.445438E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.789775E+12 | 0.749682E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.103728E+13 | 0.905043E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.139844E+13 | 0.107676E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.134847E+13 | 0.983038E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.136716E+13 | 0.102199E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.113021E+13 | 0.811342E+11 | 0.00 | 0.00 |
October | 0.197772E+09 | 0.00 | 0.643972E+12 | 0.584378E+11 | 0.00 | 0.00 |
November | 0.964891E+09 | 0.00 | 0.295257E+12 | 0.416690E+11 | 0.00 | 0.00 |
December | 0.153249E+11 | 0.00 | 0.141608E+12 | 0.341601E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.241935E+11 | 0.00 | 0.879610E+13 | 0.803930E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.662999E+11 | 0.317189E+11 | 0.00 | 0.00 |
Maximum of Months | 0.153249E+11 | 0.00 | 0.139844E+13 | 0.107676E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.215683E+10 | 0.00 | 0.253626E+11 | 0.331723E+10 | 0.00 | 0.00 |
February | 0.245141E+10 | 0.00 | 0.523036E+10 | 0.265666E+10 | 0.00 | 0.00 |
March | 0.151462E+10 | 0.00 | 0.271201E+11 | 0.369337E+10 | 0.00 | 0.00 |
April | 727905.89 | 0.00 | 0.873096E+11 | 0.763909E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.116807E+12 | 0.969739E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.162904E+12 | 0.128176E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.156683E+12 | 0.114923E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.156187E+12 | 0.116936E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.124985E+12 | 0.875375E+10 | 0.00 | 0.00 |
October | 0.295852E+09 | 0.00 | 0.659681E+11 | 0.540683E+10 | 0.00 | 0.00 |
November | 0.129560E+10 | 0.00 | 0.257992E+11 | 0.348079E+10 | 0.00 | 0.00 |
December | 0.677215E+10 | 0.00 | 0.114095E+11 | 0.298210E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.144872E+11 | 0.00 | 0.965766E+12 | 0.836306E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.523036E+10 | 0.265666E+10 | 0.00 | 0.00 |
Maximum of Months | 0.677215E+10 | 0.00 | 0.162904E+12 | 0.128176E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.231573E+11 | 0.149649E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.393719E+10 | 0.128310E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.222638E+11 | 0.148484E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.522457E+11 | 0.138717E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.648167E+11 | 0.146015E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.797126E+11 | 0.146473E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.871693E+11 | 0.150916E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.957187E+11 | 0.164160E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.834084E+11 | 0.157519E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.521004E+11 | 0.160869E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.281018E+11 | 0.152504E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.122277E+11 | 0.154525E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.604860E+12 | 0.179814E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.393719E+10 | 0.128310E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.957187E+11 | 0.164160E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.675116E+10 | 0.287751E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.113927E+11 | 0.343467E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.192168E+11 | 0.505071E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.253858E+11 | 0.679376E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.817774E+10 | 0.353613E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.148878E+11 | 0.528488E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.217219E+11 | 0.665797E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.275629E+11 | 0.776590E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.807141E+10 | 0.337618E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.139177E+11 | 0.441244E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.187947E+11 | 0.492701E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.251205E+11 | 0.605626E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.201001E+12 | 0.601734E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.675116E+10 | 0.287751E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.275629E+11 | 0.776590E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.525478E+11 | 0.252040E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.967344E+11 | 0.307304E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.175271E+12 | 0.468397E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.241561E+12 | 0.646698E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.763597E+11 | 0.333257E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.141277E+12 | 0.502064E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.206446E+12 | 0.632985E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.262322E+12 | 0.739028E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.748251E+11 | 0.316944E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.127545E+12 | 0.411104E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.170229E+12 | 0.454767E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.224730E+12 | 0.553661E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.184985E+13 | 0.561825E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.525478E+11 | 0.252040E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.262322E+12 | 0.739028E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.398177E+10 | 0.230763E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.832881E+10 | 0.287053E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.166760E+11 | 0.457876E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.242084E+11 | 0.652512E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.774092E+10 | 0.339361E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.144011E+11 | 0.512157E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.209278E+11 | 0.643035E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.264721E+11 | 0.748407E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.762982E+10 | 0.323460E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.123093E+11 | 0.406676E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.159562E+11 | 0.440354E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.207125E+11 | 0.528760E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.179345E+12 | 0.557042E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.398177E+10 | 0.230763E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.264721E+11 | 0.748407E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.577217E+10 | 0.357209E+11 | 19025708.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.509209E+10 | 0.906358E+10 | 22723018.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.761577E+10 | 0.395181E+11 | 76255243.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116801E+11 | 0.103555E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107427E+11 | 0.116999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136318E+11 | 0.160237E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140302E+11 | 0.169526E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154264E+11 | 0.178193E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103475E+11 | 0.132989E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.872913E+10 | 0.803420E+11 | 2467236.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.749009E+10 | 0.422354E+11 | 2454501.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.674851E+10 | 0.206936E+11 | 0.324504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117306E+12 | 0.108907E+13 | 0.447429E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.509209E+10 | 0.906358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154264E+11 | 0.178193E+12 | 0.324504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.386142E+11 | 0.292150E+12 | 0.244544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317189E+11 | 0.662999E+11 | 0.246715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.445438E+11 | 0.285485E+12 | 0.279329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.749682E+11 | 0.789775E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.905043E+11 | 0.103728E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107676E+12 | 0.139844E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.983038E+11 | 0.134847E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.102199E+12 | 0.136716E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.811342E+11 | 0.113021E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.584378E+11 | 0.643972E+12 | 0.197772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.416690E+11 | 0.295257E+12 | 0.964891E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.341601E+11 | 0.141608E+12 | 0.153249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.803930E+12 | 0.879610E+13 | 0.241935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.317189E+11 | 0.662999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107676E+12 | 0.139844E+13 | 0.153249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.331723E+10 | 0.253626E+11 | 0.215683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.265666E+10 | 0.523036E+10 | 0.245141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.369337E+10 | 0.271201E+11 | 0.151462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.763909E+10 | 0.873096E+11 | 727905.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.969739E+10 | 0.116807E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128176E+11 | 0.162904E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114923E+11 | 0.156683E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116936E+11 | 0.156187E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.875375E+10 | 0.124985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.540683E+10 | 0.659681E+11 | 0.295852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.348079E+10 | 0.257992E+11 | 0.129560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.298210E+10 | 0.114095E+11 | 0.677215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.836306E+11 | 0.965766E+12 | 0.144872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.265666E+10 | 0.523036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.128176E+11 | 0.162904E+12 | 0.677215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149649E+11 | 0.231573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128310E+11 | 0.393719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148484E+11 | 0.222638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138717E+11 | 0.522457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146015E+11 | 0.648167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146473E+11 | 0.797126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150916E+11 | 0.871693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164160E+11 | 0.957187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157519E+11 | 0.834084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160869E+11 | 0.521004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152504E+11 | 0.281018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154525E+11 | 0.122277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179814E+12 | 0.604860E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128310E+11 | 0.393719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164160E+11 | 0.957187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.152012E+10 | 0.539377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137301E+10 | 0.933101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152012E+10 | 0.156862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147108E+10 | 0.200632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152012E+10 | 0.616173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147108E+10 | 0.110740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152012E+10 | 0.165840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152012E+10 | 0.213172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147108E+10 | 0.616631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152012E+10 | 0.110254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147108E+10 | 0.153388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152012E+10 | 0.205844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178982E+11 | 0.158726E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137301E+10 | 0.539377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152012E+10 | 0.213172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144611E+11 | 0.418049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130616E+11 | 0.790656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144611E+11 | 0.142892E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139946E+11 | 0.190886E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144611E+11 | 0.574951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139946E+11 | 0.105065E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144611E+11 | 0.157608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144611E+11 | 0.202880E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139946E+11 | 0.571254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144611E+11 | 0.100895E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139946E+11 | 0.138747E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144611E+11 | 0.183825E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170268E+12 | 0.145829E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130616E+11 | 0.418049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144611E+11 | 0.202880E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147392E+10 | 0.314806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133128E+10 | 0.678956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147392E+10 | 0.135712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142637E+10 | 0.191097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147392E+10 | 0.582123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142637E+10 | 0.107059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147392E+10 | 0.159714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147392E+10 | 0.204619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142637E+10 | 0.582160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147392E+10 | 0.971649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142637E+10 | 0.129790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147392E+10 | 0.168988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173542E+11 | 0.140995E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133128E+10 | 0.314806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147392E+10 | 0.204619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.577217E+10 | 19025708.51 | 0.357209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.509209E+10 | 22723018.61 | 0.906358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.761577E+10 | 76255243.69 | 0.395181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116801E+11 | 0.00 | 0.103555E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107427E+11 | 0.00 | 0.116999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136318E+11 | 0.00 | 0.160237E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140302E+11 | 0.00 | 0.169526E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154264E+11 | 0.00 | 0.178193E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103475E+11 | 0.00 | 0.132989E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.872913E+10 | 2467236.08 | 0.803420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.749009E+10 | 2454501.85 | 0.422354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.674851E+10 | 0.324504E+09 | 0.206936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117306E+12 | 0.447429E+09 | 0.108907E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.509209E+10 | 0.00 | 0.906358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154264E+11 | 0.324504E+09 | 0.178193E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.386142E+11 | 0.244544E+10 | 0.292150E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317189E+11 | 0.246715E+10 | 0.662999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.445438E+11 | 0.279329E+10 | 0.285485E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.749682E+11 | 0.00 | 0.789775E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.905043E+11 | 0.00 | 0.103728E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107676E+12 | 0.00 | 0.139844E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.983038E+11 | 0.00 | 0.134847E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.102199E+12 | 0.00 | 0.136716E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.811342E+11 | 0.00 | 0.113021E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.584378E+11 | 0.197772E+09 | 0.643972E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.416690E+11 | 0.964891E+09 | 0.295257E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.341601E+11 | 0.153249E+11 | 0.141608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.803930E+12 | 0.241935E+11 | 0.879610E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.317189E+11 | 0.00 | 0.662999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107676E+12 | 0.153249E+11 | 0.139844E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.331723E+10 | 0.215683E+10 | 0.253626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.265666E+10 | 0.245141E+10 | 0.523036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.369337E+10 | 0.151462E+10 | 0.271201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.763909E+10 | 727905.89 | 0.873096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.969739E+10 | 0.00 | 0.116807E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128176E+11 | 0.00 | 0.162904E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114923E+11 | 0.00 | 0.156683E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116936E+11 | 0.00 | 0.156187E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.875375E+10 | 0.00 | 0.124985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.540683E+10 | 0.295852E+09 | 0.659681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.348079E+10 | 0.129560E+10 | 0.257992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.298210E+10 | 0.677215E+10 | 0.114095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.836306E+11 | 0.144872E+11 | 0.965766E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.265666E+10 | 0.00 | 0.523036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.128176E+11 | 0.677215E+10 | 0.162904E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149649E+11 | 0.00 | 0.231573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128310E+11 | 0.00 | 0.393719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148484E+11 | 0.00 | 0.222638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138717E+11 | 0.00 | 0.522457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146015E+11 | 0.00 | 0.648167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146473E+11 | 0.00 | 0.797126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150916E+11 | 0.00 | 0.871693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164160E+11 | 0.00 | 0.957187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157519E+11 | 0.00 | 0.834084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160869E+11 | 0.00 | 0.521004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152504E+11 | 0.00 | 0.281018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154525E+11 | 0.00 | 0.122277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179814E+12 | 0.00 | 0.604860E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128310E+11 | 0.00 | 0.393719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164160E+11 | 0.00 | 0.957187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.152012E+10 | 0.00 | 0.675116E+10 | 0.00 | 0.135739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137301E+10 | 0.00 | 0.113927E+11 | 0.00 | 0.206166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152012E+10 | 0.00 | 0.192168E+11 | 0.00 | 0.353059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147108E+10 | 0.00 | 0.253858E+11 | 0.00 | 0.532268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152012E+10 | 0.00 | 0.817774E+10 | 0.00 | 0.201601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147108E+10 | 0.00 | 0.148878E+11 | 0.00 | 0.381380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152012E+10 | 0.00 | 0.217219E+11 | 0.00 | 0.513785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152012E+10 | 0.00 | 0.275629E+11 | 0.00 | 0.624578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147108E+10 | 0.00 | 0.807141E+10 | 0.00 | 0.190510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152012E+10 | 0.00 | 0.139177E+11 | 0.00 | 0.289232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147108E+10 | 0.00 | 0.187947E+11 | 0.00 | 0.345592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152012E+10 | 0.00 | 0.251205E+11 | 0.00 | 0.453614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178982E+11 | 0.00 | 0.201001E+12 | 0.00 | 0.422752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137301E+10 | 0.00 | 0.675116E+10 | 0.00 | 0.135739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152012E+10 | 0.00 | 0.275629E+11 | 0.00 | 0.624578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.144611E+11 | 0.00 | 0.525478E+11 | 0.00 | 0.107429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130616E+11 | 0.00 | 0.967344E+11 | 0.00 | 0.176687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144611E+11 | 0.00 | 0.175271E+12 | 0.00 | 0.323786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139946E+11 | 0.00 | 0.241561E+12 | 0.00 | 0.506752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144611E+11 | 0.00 | 0.763597E+11 | 0.00 | 0.188646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139946E+11 | 0.00 | 0.141277E+12 | 0.00 | 0.362118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144611E+11 | 0.00 | 0.206446E+12 | 0.00 | 0.488374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144611E+11 | 0.00 | 0.262322E+12 | 0.00 | 0.594417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139946E+11 | 0.00 | 0.748251E+11 | 0.00 | 0.176998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144611E+11 | 0.00 | 0.127545E+12 | 0.00 | 0.266493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139946E+11 | 0.00 | 0.170229E+12 | 0.00 | 0.314821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144611E+11 | 0.00 | 0.224730E+12 | 0.00 | 0.409050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170268E+12 | 0.00 | 0.184985E+13 | 0.00 | 0.391557E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130616E+11 | 0.00 | 0.525478E+11 | 0.00 | 0.107429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144611E+11 | 0.00 | 0.262322E+12 | 0.00 | 0.594417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147392E+10 | 0.00 | 0.398177E+10 | 0.00 | 0.833709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133128E+10 | 0.00 | 0.832881E+10 | 0.00 | 0.153925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147392E+10 | 0.00 | 0.166760E+11 | 0.00 | 0.310484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142637E+10 | 0.00 | 0.242084E+11 | 0.00 | 0.509875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147392E+10 | 0.00 | 0.774092E+10 | 0.00 | 0.191969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142637E+10 | 0.00 | 0.144011E+11 | 0.00 | 0.369520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147392E+10 | 0.00 | 0.209278E+11 | 0.00 | 0.495644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147392E+10 | 0.00 | 0.264721E+11 | 0.00 | 0.601015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142637E+10 | 0.00 | 0.762982E+10 | 0.00 | 0.180823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147392E+10 | 0.00 | 0.123093E+11 | 0.00 | 0.259285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142637E+10 | 0.00 | 0.159562E+11 | 0.00 | 0.297717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147392E+10 | 0.00 | 0.207125E+11 | 0.00 | 0.381369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173542E+11 | 0.00 | 0.179345E+12 | 0.00 | 0.383500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133128E+10 | 0.00 | 0.398177E+10 | 0.00 | 0.833709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147392E+10 | 0.00 | 0.264721E+11 | 0.00 | 0.601015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.458255E+09 | 8361250.43 | 0.00 | 0.107253E+09 | 294104.06 | 0.00 | 0.482206E+11 | 0.00 | 1.18 |
February | 0.349650E+09 | 0.00 | 0.00 | 86508645.57 | 0.00 | 0.00 | 0.561576E+11 | 0.00 | 1.14 |
March | 0.273275E+09 | 17136242.75 | 0.00 | 98100641.23 | 0.00 | 0.00 | 0.486338E+11 | 0.00 | 1.22 |
April | 62033197.22 | 0.171112E+10 | 0.00 | 66610650.04 | 0.102259E+09 | 0.00 | 0.181307E+11 | 0.00 | 0.76 |
May | 40760996.74 | 0.381111E+10 | 0.00 | 46420762.30 | 0.137050E+09 | 0.00 | 0.988010E+10 | 0.00 | 0.62 |
June | 41948018.53 | 0.104787E+11 | 0.00 | 22809421.09 | 0.233178E+09 | 0.00 | 0.349536E+10 | 0.00 | 0.51 |
July | 24720122.94 | 0.111862E+11 | 0.00 | 13789936.90 | 0.261492E+09 | 0.00 | 0.156021E+10 | 0.00 | 0.41 |
August | 29288625.33 | 0.112336E+11 | 0.00 | 22653570.00 | 0.187997E+09 | 0.00 | 0.220894E+10 | 0.00 | 0.54 |
September | 28305219.97 | 0.816373E+10 | 0.00 | 39287357.11 | 0.170944E+09 | 0.00 | 0.540896E+10 | 0.00 | 0.67 |
October | 0.263589E+09 | 0.174630E+10 | 0.00 | 96495810.18 | 22723134.22 | 0.00 | 0.322543E+11 | 0.00 | 1.05 |
November | 0.416284E+09 | 0.146680E+09 | 0.00 | 0.122525E+09 | 68509.40 | 0.00 | 0.510007E+11 | 0.00 | 1.28 |
December | 0.544229E+09 | 664488.26 | 0.00 | 0.121663E+09 | 0.00 | 0.00 | 0.642720E+11 | 0.00 | 1.19 |
Annual Sum or Average | 0.253234E+10 | 0.485036E+11 | 0.00 | 0.844118E+09 | 0.111601E+10 | 0.00 | 0.341223E+12 | 0.00 | 0.88 |
Minimum of Months | 24720122.94 | 0.00 | 0.00 | 13789936.90 | 0.00 | 0.00 | 0.156021E+10 | 0.00 | 0.41 |
Maximum of Months | 0.544229E+09 | 0.112336E+11 | 0.00 | 0.122525E+09 | 0.261492E+09 | 0.00 | 0.642720E+11 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.405456E+10 | 1622185.23 | 0.00 | 73049837.38 | 31231018.11 | 0.00 | 0.298389E+11 | 0.00 | 0.77 |
February | 0.370082E+10 | 0.00 | 0.00 | 67097001.98 | 0.00 | 0.00 | 0.393763E+11 | 0.00 | 0.80 |
March | 0.488125E+10 | 9311130.07 | 0.00 | 84869684.64 | 961543.87 | 0.00 | 0.358927E+11 | 0.00 | 0.91 |
April | 0.841613E+10 | 0.103332E+10 | 0.00 | 51571866.03 | 0.381829E+09 | 0.00 | 0.125001E+11 | 0.00 | 0.79 |
May | 0.307292E+10 | 0.228803E+10 | 0.00 | 33565341.82 | 0.454651E+09 | 0.00 | 0.542339E+10 | 0.00 | 0.52 |
June | 0.211188E+10 | 0.718963E+10 | 0.00 | 9217320.82 | 0.100202E+10 | 0.00 | 0.116908E+10 | 0.00 | 0.42 |
July | 0.107267E+10 | 0.915222E+10 | 0.00 | 4713462.14 | 0.250749E+10 | 0.00 | 0.441117E+09 | 0.00 | 0.38 |
August | 0.121723E+10 | 0.927168E+10 | 0.00 | 10209299.80 | 0.118292E+10 | 0.00 | 0.755914E+09 | 0.00 | 0.47 |
September | 0.915135E+09 | 0.569059E+10 | 0.00 | 22184111.23 | 0.173918E+10 | 0.00 | 0.250559E+10 | 0.00 | 0.49 |
October | 0.408130E+10 | 0.124042E+10 | 0.00 | 62046362.48 | 0.311488E+09 | 0.00 | 0.204794E+11 | 0.00 | 0.75 |
November | 0.530313E+10 | 22893577.21 | 0.00 | 85300362.54 | 80427908.51 | 0.00 | 0.332217E+11 | 0.00 | 0.90 |
December | 0.527521E+10 | 135576.87 | 0.00 | 84325694.80 | 1688548.64 | 0.00 | 0.437002E+11 | 0.00 | 0.84 |
Annual Sum or Average | 0.441022E+11 | 0.358998E+11 | 0.00 | 0.588150E+09 | 0.769389E+10 | 0.00 | 0.225304E+12 | 0.00 | 0.67 |
Minimum of Months | 0.915135E+09 | 0.00 | 0.00 | 4713462.14 | 0.00 | 0.00 | 0.441117E+09 | 0.00 | 0.38 |
Maximum of Months | 0.841613E+10 | 0.927168E+10 | 0.00 | 85300362.54 | 0.250749E+10 | 0.00 | 0.437002E+11 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.520302E+11 | 237917.62 | 0.00 | 0.409867E+09 | 0.347486E+09 | 0.00 | 0.186485E+12 | 0.00 | 0.57 |
February | 0.727533E+11 | 0.00 | 0.00 | 0.334531E+09 | 0.00 | 0.00 | 0.229509E+12 | 0.00 | 0.58 |
March | 0.443910E+11 | 82744267.07 | 0.00 | 0.503661E+09 | 17113424.34 | 0.00 | 0.235004E+12 | 0.00 | 0.64 |
April | 0.202210E+11 | 0.103178E+11 | 0.00 | 0.411396E+09 | 0.437420E+10 | 0.00 | 0.962790E+11 | 0.00 | 0.51 |
May | 0.172665E+11 | 0.239787E+11 | 0.00 | 0.290426E+09 | 0.451135E+10 | 0.00 | 0.452839E+11 | 0.00 | 0.44 |
June | 0.146222E+11 | 0.730803E+11 | 0.00 | 53929738.02 | 0.104043E+11 | 0.00 | 0.834691E+10 | 0.00 | 0.36 |
July | 0.574167E+10 | 0.864610E+11 | 0.00 | 22011596.81 | 0.135124E+11 | 0.00 | 0.272296E+10 | 0.00 | 0.30 |
August | 0.551531E+10 | 0.819659E+11 | 0.00 | 70336736.69 | 0.964269E+10 | 0.00 | 0.626029E+10 | 0.00 | 0.36 |
September | 0.392776E+10 | 0.551871E+11 | 0.00 | 0.181676E+09 | 0.126623E+11 | 0.00 | 0.209415E+11 | 0.00 | 0.40 |
October | 0.223623E+11 | 0.124643E+11 | 0.00 | 0.430956E+09 | 0.230160E+10 | 0.00 | 0.147252E+12 | 0.00 | 0.55 |
November | 0.456447E+11 | 0.454906E+09 | 0.00 | 0.485131E+09 | 0.275310E+09 | 0.00 | 0.206382E+12 | 0.00 | 0.61 |
December | 0.892806E+11 | 5756276.30 | 0.00 | 0.322233E+09 | 6146136.39 | 0.00 | 0.195745E+12 | 0.00 | 0.52 |
Annual Sum or Average | 0.393756E+12 | 0.343999E+12 | 0.00 | 0.351616E+10 | 0.580549E+11 | 0.00 | 0.138021E+13 | 0.00 | 0.49 |
Minimum of Months | 0.392776E+10 | 0.00 | 0.00 | 22011596.81 | 0.00 | 0.00 | 0.272296E+10 | 0.00 | 0.30 |
Maximum of Months | 0.892806E+11 | 0.864610E+11 | 0.00 | 0.503661E+09 | 0.135124E+11 | 0.00 | 0.235004E+12 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110968E+11 | 0.00 | 0.00 | 16536762.70 | 39153750.08 | 0.110240E+09 | 0.737298E+10 | 0.00 | 0.50 |
February | 0.138623E+11 | 0.00 | 0.00 | 11385547.34 | 670849.74 | 84698476.11 | 0.102003E+11 | 0.00 | 0.49 |
March | 0.100956E+11 | 3475408.48 | 0.00 | 28264126.91 | 478013.26 | 1152839.59 | 0.123262E+11 | 0.00 | 0.56 |
April | 0.270193E+10 | 0.618925E+09 | 0.00 | 39006845.02 | 0.379574E+09 | 0.00 | 0.697211E+10 | 0.00 | 0.49 |
May | 0.141178E+10 | 0.165651E+10 | 0.00 | 33632680.77 | 0.377076E+09 | 0.00 | 0.352447E+10 | 0.00 | 0.41 |
June | 0.146816E+10 | 0.623286E+10 | 0.00 | 4895140.39 | 0.925050E+09 | 0.00 | 0.662158E+09 | 0.00 | 0.36 |
July | 0.552939E+09 | 0.789193E+10 | 0.00 | 2127523.49 | 0.141520E+10 | 0.00 | 0.217559E+09 | 0.00 | 0.30 |
August | 0.527874E+09 | 0.749940E+10 | 0.00 | 5686292.53 | 0.971035E+09 | 0.00 | 0.468003E+09 | 0.00 | 0.36 |
September | 0.357550E+09 | 0.481840E+10 | 0.00 | 18767891.71 | 0.137247E+10 | 0.00 | 0.171540E+10 | 0.00 | 0.39 |
October | 0.444889E+10 | 0.972232E+09 | 0.00 | 31319348.70 | 0.269101E+09 | 0.00 | 0.854978E+10 | 0.00 | 0.49 |
November | 0.963519E+10 | 29309073.70 | 0.00 | 25170750.84 | 43796122.98 | 2855304.98 | 0.107186E+11 | 0.00 | 0.54 |
December | 0.171168E+11 | 0.00 | 0.00 | 6245615.46 | 12641758.43 | 0.136819E+09 | 0.472523E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.732759E+11 | 0.297230E+11 | 0.00 | 0.223039E+09 | 0.580625E+10 | 0.335766E+09 | 0.674528E+11 | 0.00 | 0.44 |
Minimum of Months | 0.357550E+09 | 0.00 | 0.00 | 2127523.49 | 478013.26 | 0.00 | 0.217559E+09 | 0.00 | 0.30 |
Maximum of Months | 0.171168E+11 | 0.789193E+10 | 0.00 | 39006845.02 | 0.141520E+10 | 0.136819E+09 | 0.123262E+11 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179176E+10 | 7321.81 | 0.00 | 3162324.52 | 4106785.30 | 0.00 | 0.123332E+10 | 0.00 | 0.56 |
February | 0.182129E+10 | 0.00 | 0.00 | 2676701.91 | 0.00 | 0.00 | 0.198938E+10 | 0.00 | 0.57 |
March | 0.152669E+10 | 1289203.25 | 0.00 | 5696762.31 | 120436.83 | 0.00 | 0.229834E+10 | 0.00 | 0.72 |
April | 0.120478E+10 | 0.197131E+09 | 0.00 | 5862960.64 | 36993110.92 | 0.00 | 0.117018E+10 | 0.00 | 0.79 |
May | 0.418125E+09 | 0.507744E+09 | 0.00 | 4599141.35 | 36442919.65 | 0.00 | 0.671114E+09 | 0.00 | 0.64 |
June | 0.226333E+09 | 0.189121E+10 | 0.00 | 2078915.67 | 56111944.05 | 0.00 | 0.254375E+09 | 0.00 | 0.66 |
July | 0.121964E+09 | 0.206700E+10 | 0.00 | 943224.05 | 0.225569E+09 | 0.00 | 89281446.74 | 0.00 | 0.56 |
August | 0.147367E+09 | 0.187466E+10 | 0.00 | 1579049.50 | 0.102320E+09 | 0.00 | 0.113335E+09 | 0.00 | 0.62 |
September | 0.117927E+09 | 0.115115E+10 | 0.00 | 3057517.62 | 0.165602E+09 | 0.00 | 0.306907E+09 | 0.00 | 0.60 |
October | 0.944550E+09 | 0.216394E+09 | 0.00 | 4745388.49 | 34870075.17 | 0.00 | 0.138601E+10 | 0.00 | 0.66 |
November | 0.159835E+10 | 1519206.42 | 0.00 | 5313480.28 | 10619766.75 | 0.00 | 0.193463E+10 | 0.00 | 0.69 |
December | 0.232777E+10 | 14825.92 | 0.00 | 2791404.43 | 211496.79 | 0.00 | 0.163994E+10 | 0.00 | 0.56 |
Annual Sum or Average | 0.122469E+11 | 0.790812E+10 | 0.00 | 42506870.78 | 0.672968E+09 | 0.00 | 0.130868E+11 | 0.00 | 0.63 |
Minimum of Months | 0.117927E+09 | 0.00 | 0.00 | 943224.05 | 0.00 | 0.00 | 89281446.74 | 0.00 | 0.56 |
Maximum of Months | 0.232777E+10 | 0.206700E+10 | 0.00 | 5862960.64 | 0.225569E+09 | 0.00 | 0.229834E+10 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117128E+10 | 167843.75 | 0.00 | 4408403.48 | 3244082.41 | 0.00 | 0.198284E+10 | 0.00 | 0.87 |
February | 0.128519E+10 | 0.00 | 0.00 | 3434838.70 | 0.00 | 0.00 | 0.242905E+10 | 0.00 | 0.83 |
March | 0.117717E+10 | 917424.45 | 0.00 | 5807624.68 | 99879.15 | 0.00 | 0.255096E+10 | 0.00 | 1.04 |
April | 0.100134E+10 | 0.161156E+09 | 0.00 | 6812110.94 | 30702599.44 | 0.00 | 0.148893E+10 | 0.00 | 1.25 |
May | 0.338131E+09 | 0.420334E+09 | 0.00 | 5730809.47 | 28589214.17 | 0.00 | 0.829831E+09 | 0.00 | 1.02 |
June | 0.209414E+09 | 0.152311E+10 | 0.00 | 1586724.65 | 42014133.52 | 0.00 | 0.180479E+09 | 0.00 | 0.87 |
July | 0.107993E+09 | 0.164358E+10 | 0.00 | 699247.61 | 0.207770E+09 | 0.00 | 62666295.08 | 0.00 | 0.71 |
August | 0.129716E+09 | 0.152479E+10 | 0.00 | 996988.87 | 94268902.49 | 0.00 | 80431599.17 | 0.00 | 0.78 |
September | 0.102129E+09 | 0.100070E+10 | 0.00 | 2515288.23 | 0.132792E+09 | 0.00 | 0.271309E+09 | 0.00 | 0.81 |
October | 0.759428E+09 | 0.182189E+09 | 0.00 | 5392941.83 | 27504080.16 | 0.00 | 0.170516E+10 | 0.00 | 1.02 |
November | 0.126143E+10 | 854149.20 | 0.00 | 5063084.06 | 9057270.90 | 0.00 | 0.205594E+10 | 0.00 | 0.96 |
December | 0.172923E+10 | 12295.24 | 0.00 | 2927454.81 | 175395.85 | 0.00 | 0.178071E+10 | 0.00 | 0.74 |
Annual Sum or Average | 0.927245E+10 | 0.645782E+10 | 0.00 | 45375517.33 | 0.576217E+09 | 0.00 | 0.154183E+11 | 0.00 | 0.91 |
Minimum of Months | 0.102129E+09 | 0.00 | 0.00 | 699247.61 | 0.00 | 0.00 | 62666295.08 | 0.00 | 0.71 |
Maximum of Months | 0.172923E+10 | 0.164358E+10 | 0.00 | 6812110.94 | 0.207770E+09 | 0.00 | 0.255096E+10 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.922540E+09 | 4088753.93 | 0.00 | 18118285.98 | 1223310.29 | 0.00 | 0.582756E+10 | 0.00 | 1.46 |
February | 0.116741E+10 | 0.00 | 0.00 | 9270546.39 | 0.00 | 0.00 | 0.609994E+10 | 0.00 | 1.11 |
March | 0.126228E+10 | 1920750.22 | 0.00 | 10858502.45 | 120520.42 | 0.00 | 0.415056E+10 | 0.00 | 1.10 |
April | 0.115854E+10 | 0.305277E+09 | 0.00 | 8127665.26 | 33661881.22 | 0.00 | 0.149217E+10 | 0.00 | 0.97 |
May | 0.412465E+09 | 0.573338E+09 | 0.00 | 4685460.65 | 34146052.32 | 0.00 | 0.624151E+09 | 0.00 | 0.65 |
June | 0.237142E+09 | 0.183888E+10 | 0.00 | 1699501.27 | 54206015.91 | 0.00 | 0.204516E+09 | 0.00 | 0.61 |
July | 0.122926E+09 | 0.209761E+10 | 0.00 | 847186.87 | 0.225259E+09 | 0.00 | 78316021.88 | 0.00 | 0.55 |
August | 0.140222E+09 | 0.219814E+10 | 0.00 | 1714919.16 | 90173801.77 | 0.00 | 0.122345E+09 | 0.00 | 0.68 |
September | 0.105852E+09 | 0.165671E+10 | 0.00 | 4180661.83 | 0.138254E+09 | 0.00 | 0.374792E+09 | 0.00 | 0.76 |
October | 0.695984E+09 | 0.385944E+09 | 0.00 | 12069471.47 | 25643078.41 | 0.00 | 0.324027E+10 | 0.00 | 1.18 |
November | 0.939547E+09 | 2919303.34 | 0.00 | 17414856.50 | 10508838.96 | 0.00 | 0.600710E+10 | 0.00 | 1.43 |
December | 0.128975E+10 | 677696.11 | 0.00 | 15510640.30 | 0.00 | 0.00 | 0.719190E+10 | 0.00 | 1.34 |
Annual Sum or Average | 0.845466E+10 | 0.906550E+10 | 0.00 | 0.104498E+09 | 0.613196E+09 | 0.00 | 0.354136E+11 | 0.00 | 0.99 |
Minimum of Months | 0.105852E+09 | 0.00 | 0.00 | 847186.87 | 0.00 | 0.00 | 78316021.88 | 0.00 | 0.55 |
Maximum of Months | 0.128975E+10 | 0.219814E+10 | 0.00 | 18118285.98 | 0.225259E+09 | 0.00 | 0.719190E+10 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114076E+10 | 2599011.59 | 0.00 | 7157995.06 | 2291783.65 | 0.00 | 0.260981E+10 | 0.00 | 1.18 |
February | 0.754897E+09 | 0.00 | 0.00 | 6712781.91 | 0.00 | 0.00 | 0.449238E+10 | 0.00 | 1.26 |
March | 0.437193E+09 | 1820608.45 | 0.00 | 12912059.62 | 0.00 | 0.00 | 0.510158E+10 | 0.00 | 1.70 |
April | 0.445177E+09 | 0.390594E+09 | 0.00 | 14099738.18 | 4286410.01 | 0.00 | 0.300689E+10 | 0.00 | 1.83 |
May | 0.276881E+09 | 0.707712E+09 | 0.00 | 5885576.67 | 14327711.89 | 0.00 | 0.914921E+09 | 0.00 | 1.11 |
June | 0.132995E+09 | 0.226485E+10 | 0.00 | 3558244.57 | 28487625.69 | 0.00 | 0.421183E+09 | 0.00 | 1.15 |
July | 66623001.34 | 0.249161E+10 | 0.00 | 1691938.74 | 0.120428E+09 | 0.00 | 0.184709E+09 | 0.00 | 0.98 |
August | 51638568.56 | 0.241064E+10 | 0.00 | 3851243.62 | 32957891.44 | 0.00 | 0.293123E+09 | 0.00 | 1.22 |
September | 85192729.49 | 0.129030E+10 | 0.00 | 3621154.65 | 0.126131E+09 | 0.00 | 0.378248E+09 | 0.00 | 0.99 |
October | 0.445892E+09 | 0.267847E+09 | 0.00 | 9330576.51 | 24110074.81 | 0.00 | 0.265187E+10 | 0.00 | 1.36 |
November | 0.546890E+09 | 11093149.44 | 0.00 | 12793157.54 | 4639542.61 | 0.00 | 0.471777E+10 | 0.00 | 1.64 |
December | 0.692390E+09 | 176324.37 | 0.00 | 11366038.21 | 98174.04 | 0.00 | 0.575060E+10 | 0.00 | 1.49 |
Annual Sum or Average | 0.507653E+10 | 0.983924E+10 | 0.00 | 92980505.30 | 0.357758E+09 | 0.00 | 0.305231E+11 | 0.00 | 1.33 |
Minimum of Months | 51638568.56 | 0.00 | 0.00 | 1691938.74 | 0.00 | 0.00 | 0.184709E+09 | 0.00 | 0.98 |
Maximum of Months | 0.114076E+10 | 0.249161E+10 | 0.00 | 14099738.18 | 0.126131E+09 | 0.00 | 0.575060E+10 | 0.00 | 1.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.238254E+11 | 22451.50 | 0.00 | 3710421.02 | 43715279.60 | 0.394775E+09 | 0.113080E+10 | 0.00 | 0.48 |
February | 0.291494E+11 | 0.00 | 0.00 | 1765540.48 | 0.00 | 0.120230E+09 | 0.180442E+10 | 0.00 | 0.47 |
March | 0.216638E+11 | 9420747.14 | 0.00 | 19557351.21 | 2152944.53 | 0.175661E+09 | 0.615160E+10 | 0.00 | 0.52 |
April | 0.600483E+10 | 0.198815E+10 | 0.00 | 38553229.10 | 0.474982E+09 | 0.00 | 0.656435E+10 | 0.00 | 0.52 |
May | 0.246834E+10 | 0.561196E+10 | 0.00 | 38073956.96 | 0.381181E+09 | 0.00 | 0.548709E+10 | 0.00 | 0.56 |
June | 0.149952E+10 | 0.215645E+11 | 0.00 | 16499808.47 | 0.553739E+09 | 0.00 | 0.217030E+10 | 0.00 | 0.64 |
July | 0.625181E+09 | 0.221537E+11 | 0.00 | 5300816.94 | 0.784673E+09 | 0.00 | 0.657668E+09 | 0.00 | 0.51 |
August | 0.650684E+09 | 0.188098E+11 | 0.00 | 11489925.06 | 0.688124E+09 | 0.00 | 0.970160E+09 | 0.00 | 0.54 |
September | 0.539496E+09 | 0.119112E+11 | 0.00 | 24187657.30 | 0.116921E+10 | 0.00 | 0.253092E+10 | 0.00 | 0.53 |
October | 0.115284E+11 | 0.223826E+10 | 0.00 | 22369197.48 | 0.283298E+09 | 0.00 | 0.507981E+10 | 0.00 | 0.49 |
November | 0.207439E+11 | 10292181.99 | 0.00 | 13989656.27 | 68424362.73 | 0.180903E+09 | 0.504812E+10 | 0.00 | 0.49 |
December | 0.287073E+11 | 0.00 | 0.00 | 100205.65 | 1443137.42 | 0.250643E+10 | 0.124762E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.147406E+12 | 0.842973E+11 | 0.00 | 0.195598E+09 | 0.445094E+10 | 0.337800E+10 | 0.377200E+11 | 0.00 | 0.52 |
Minimum of Months | 0.539496E+09 | 0.00 | 0.00 | 100205.65 | 0.00 | 0.00 | 0.124762E+09 | 0.00 | 0.45 |
Maximum of Months | 0.291494E+11 | 0.221537E+11 | 0.00 | 38553229.10 | 0.116921E+10 | 0.250643E+10 | 0.656435E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133359E+11 | 23824.50 | 0.00 | 21569243.42 | 38198573.61 | 0.215405E+09 | 0.107916E+11 | 0.00 | 0.71 |
February | 0.156215E+11 | 0.00 | 0.00 | 15557392.29 | 0.00 | 0.100756E+09 | 0.137101E+11 | 0.00 | 0.68 |
March | 0.124916E+11 | 8519469.95 | 0.00 | 39389874.37 | 1881250.92 | 98889706.89 | 0.169461E+11 | 0.00 | 0.85 |
April | 0.320356E+10 | 0.215417E+10 | 0.00 | 68696931.65 | 0.300197E+09 | 0.00 | 0.145619E+11 | 0.00 | 1.06 |
May | 0.194101E+10 | 0.505639E+10 | 0.00 | 56206737.26 | 0.281246E+09 | 0.00 | 0.815681E+10 | 0.00 | 1.00 |
June | 0.136278E+10 | 0.189668E+11 | 0.00 | 15068813.88 | 0.401409E+09 | 0.00 | 0.192059E+10 | 0.00 | 0.94 |
July | 0.531628E+09 | 0.202585E+11 | 0.00 | 5706973.82 | 0.682832E+09 | 0.00 | 0.655301E+09 | 0.00 | 0.75 |
August | 0.552006E+09 | 0.182304E+11 | 0.00 | 11259267.56 | 0.521188E+09 | 0.00 | 0.102538E+10 | 0.00 | 0.81 |
September | 0.500857E+09 | 0.113810E+11 | 0.00 | 23792495.68 | 0.829681E+09 | 0.00 | 0.258290E+10 | 0.00 | 0.79 |
October | 0.626977E+10 | 0.218812E+10 | 0.00 | 42597446.64 | 0.154865E+09 | 0.00 | 0.131582E+11 | 0.00 | 0.86 |
November | 0.125655E+11 | 11668356.75 | 0.00 | 29896054.54 | 57352924.47 | 67719831.99 | 0.127612E+11 | 0.00 | 0.75 |
December | 0.219676E+11 | 0.00 | 0.00 | 5909027.39 | 1261018.83 | 0.114755E+10 | 0.464533E+10 | 0.00 | 0.61 |
Annual Sum or Average | 0.903438E+11 | 0.782556E+11 | 0.00 | 0.335650E+09 | 0.327011E+10 | 0.163032E+10 | 0.100915E+12 | 0.00 | 0.82 |
Minimum of Months | 0.500857E+09 | 0.00 | 0.00 | 5706973.82 | 0.00 | 0.00 | 0.655301E+09 | 0.00 | 0.61 |
Maximum of Months | 0.219676E+11 | 0.202585E+11 | 0.00 | 68696931.65 | 0.829681E+09 | 0.114755E+10 | 0.169461E+11 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.772928E+10 | 58669752.16 | 0.00 | 0.177397E+09 | 25596706.84 | 3455111.07 | 0.514075E+11 | 0.00 | 1.35 |
February | 0.112669E+11 | 0.00 | 0.00 | 78557280.46 | 0.00 | 0.111489E+09 | 0.522465E+11 | 0.00 | 0.99 |
March | 0.121319E+11 | 18586237.25 | 0.00 | 85712559.43 | 2149616.22 | 0.00 | 0.306704E+11 | 0.00 | 0.90 |
April | 0.456380E+10 | 0.368453E+10 | 0.00 | 66944532.88 | 0.296236E+09 | 0.00 | 0.112039E+11 | 0.00 | 0.74 |
May | 0.233204E+10 | 0.642030E+10 | 0.00 | 40666583.74 | 0.341092E+09 | 0.00 | 0.550154E+10 | 0.00 | 0.59 |
June | 0.158526E+10 | 0.206694E+11 | 0.00 | 13041062.26 | 0.581052E+09 | 0.00 | 0.171450E+10 | 0.00 | 0.59 |
July | 0.642728E+09 | 0.225967E+11 | 0.00 | 4527647.77 | 0.763513E+09 | 0.00 | 0.559330E+09 | 0.00 | 0.51 |
August | 0.554787E+09 | 0.231946E+11 | 0.00 | 14142910.67 | 0.470967E+09 | 0.00 | 0.116134E+10 | 0.00 | 0.63 |
September | 0.409238E+09 | 0.184339E+11 | 0.00 | 36889208.27 | 0.831947E+09 | 0.00 | 0.333525E+10 | 0.00 | 0.72 |
October | 0.505814E+10 | 0.458872E+10 | 0.00 | 0.106043E+09 | 86375916.24 | 0.00 | 0.275478E+11 | 0.00 | 1.06 |
November | 0.724829E+10 | 70257915.37 | 0.00 | 0.157302E+09 | 37213710.72 | 0.00 | 0.512641E+11 | 0.00 | 1.24 |
December | 0.115016E+11 | 1254394.93 | 0.00 | 0.131023E+09 | 668890.59 | 0.136051E+09 | 0.568360E+11 | 0.00 | 1.13 |
Annual Sum or Average | 0.650239E+11 | 0.997369E+11 | 0.00 | 0.912247E+09 | 0.343681E+10 | 0.250995E+09 | 0.293448E+12 | 0.00 | 0.87 |
Minimum of Months | 0.409238E+09 | 0.00 | 0.00 | 4527647.77 | 0.00 | 0.00 | 0.559330E+09 | 0.00 | 0.51 |
Maximum of Months | 0.121319E+11 | 0.231946E+11 | 0.00 | 0.177397E+09 | 0.831947E+09 | 0.136051E+09 | 0.568360E+11 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.182073E+11 | 14040829.54 | 0.00 | 27219536.96 | 30998503.77 | 0.145023E+09 | 0.779942E+10 | 0.00 | 0.83 |
February | 0.223449E+11 | 0.00 | 0.00 | 15213326.16 | 0.00 | 0.00 | 0.104773E+11 | 0.00 | 0.79 |
March | 0.165593E+11 | 12829117.08 | 0.00 | 38947423.12 | 0.00 | 0.00 | 0.125984E+11 | 0.00 | 0.91 |
April | 0.341710E+10 | 0.341781E+10 | 0.00 | 57246309.36 | 0.104516E+09 | 0.00 | 0.103532E+11 | 0.00 | 0.98 |
May | 0.174597E+10 | 0.743780E+10 | 0.00 | 39998831.72 | 0.109436E+09 | 0.00 | 0.572437E+10 | 0.00 | 0.90 |
June | 0.929399E+09 | 0.229657E+11 | 0.00 | 18914299.88 | 0.282734E+09 | 0.00 | 0.237325E+10 | 0.00 | 0.96 |
July | 0.424160E+09 | 0.205150E+11 | 0.00 | 6192522.26 | 0.405574E+09 | 0.00 | 0.765506E+09 | 0.00 | 0.71 |
August | 0.410933E+09 | 0.188859E+11 | 0.00 | 13387268.02 | 0.307403E+09 | 0.00 | 0.117905E+10 | 0.00 | 0.81 |
September | 0.516938E+09 | 0.117638E+11 | 0.00 | 22392651.12 | 0.833067E+09 | 0.00 | 0.222163E+10 | 0.00 | 0.76 |
October | 0.825061E+10 | 0.237082E+10 | 0.00 | 38936120.35 | 0.123043E+09 | 0.00 | 0.944430E+10 | 0.00 | 0.84 |
November | 0.148061E+11 | 37076082.09 | 0.00 | 37864585.82 | 46558836.45 | 0.00 | 0.130238E+11 | 0.00 | 0.86 |
December | 0.233027E+11 | 0.00 | 0.00 | 14354390.86 | 1356886.86 | 0.914008E+09 | 0.729280E+10 | 0.00 | 0.72 |
Annual Sum or Average | 0.110915E+12 | 0.874207E+11 | 0.00 | 0.330667E+09 | 0.224469E+10 | 0.105903E+10 | 0.832531E+11 | 0.00 | 0.84 |
Minimum of Months | 0.410933E+09 | 0.00 | 0.00 | 6192522.26 | 0.00 | 0.00 | 0.765506E+09 | 0.00 | 0.71 |
Maximum of Months | 0.233027E+11 | 0.229657E+11 | 0.00 | 57246309.36 | 0.833067E+09 | 0.914008E+09 | 0.130238E+11 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186544E+10 | 0.00 | 0.00 | 125729.85 | 4928323.33 | 0.361915E+09 | 46609967.63 | 0.00 | 0.48 |
February | 0.251078E+10 | 0.00 | 0.00 | 43054.82 | 84440.56 | 0.334512E+09 | 53640426.46 | 0.00 | 0.47 |
March | 0.206158E+10 | 317301.54 | 0.00 | 1413713.86 | 60168.03 | 0.231029E+09 | 0.336548E+09 | 0.00 | 0.51 |
April | 0.607436E+09 | 0.118926E+09 | 0.00 | 4446397.65 | 40783258.42 | 0.00 | 0.519731E+09 | 0.00 | 0.51 |
May | 0.240283E+09 | 0.381482E+09 | 0.00 | 4903575.00 | 29534968.94 | 0.00 | 0.406524E+09 | 0.00 | 0.52 |
June | 0.147596E+09 | 0.173809E+10 | 0.00 | 1698403.02 | 40086621.02 | 0.00 | 0.182010E+09 | 0.00 | 0.61 |
July | 60809168.55 | 0.193420E+10 | 0.00 | 567731.63 | 82669091.40 | 0.00 | 52819454.80 | 0.00 | 0.50 |
August | 62509828.31 | 0.165995E+10 | 0.00 | 1011629.98 | 60439134.04 | 0.00 | 75582972.60 | 0.00 | 0.52 |
September | 83349783.66 | 0.102347E+10 | 0.00 | 2620983.55 | 0.124468E+09 | 0.00 | 0.191233E+09 | 0.00 | 0.51 |
October | 0.110802E+10 | 0.174822E+09 | 0.00 | 2313611.97 | 32147177.75 | 57147505.46 | 0.322106E+09 | 0.00 | 0.47 |
November | 0.180051E+10 | 572455.27 | 0.00 | 846066.17 | 7777159.63 | 0.242206E+09 | 0.307541E+09 | 0.00 | 0.49 |
December | 0.186131E+10 | 0.00 | 0.00 | 1771.12 | 1591231.31 | 0.906508E+09 | 3558984.01 | 0.00 | 0.44 |
Annual Sum or Average | 0.124096E+11 | 0.703183E+10 | 0.00 | 19992668.61 | 0.424569E+09 | 0.213332E+10 | 0.249790E+10 | 0.00 | 0.50 |
Minimum of Months | 60809168.55 | 0.00 | 0.00 | 1771.12 | 60168.03 | 0.00 | 3558984.01 | 0.00 | 0.44 |
Maximum of Months | 0.251078E+10 | 0.193420E+10 | 0.00 | 4903575.00 | 0.124468E+09 | 0.906508E+09 | 0.519731E+09 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127184E+10 | 0.00 | 0.00 | 1210805.23 | 4319421.04 | 0.142585E+09 | 0.608821E+09 | 0.00 | 0.66 |
February | 0.165470E+10 | 0.00 | 0.00 | 643008.58 | 74007.79 | 0.204423E+09 | 0.722277E+09 | 0.00 | 0.65 |
March | 0.124670E+10 | 410227.74 | 0.00 | 3162022.71 | 52734.17 | 0.100654E+09 | 0.123573E+10 | 0.00 | 0.80 |
April | 0.322158E+09 | 0.139355E+09 | 0.00 | 7415638.68 | 25450495.19 | 0.00 | 0.124584E+10 | 0.00 | 1.04 |
May | 0.169382E+09 | 0.348757E+09 | 0.00 | 6898809.31 | 20330100.54 | 0.00 | 0.669188E+09 | 0.00 | 0.96 |
June | 0.132282E+09 | 0.155377E+10 | 0.00 | 1552715.98 | 31156248.76 | 0.00 | 0.159123E+09 | 0.00 | 0.90 |
July | 53923991.12 | 0.178447E+10 | 0.00 | 596438.27 | 69628619.57 | 0.00 | 49000902.12 | 0.00 | 0.73 |
August | 52878859.46 | 0.163018E+10 | 0.00 | 1044332.82 | 45941308.62 | 0.00 | 80235946.91 | 0.00 | 0.79 |
September | 52652063.24 | 0.100683E+10 | 0.00 | 2668307.21 | 85685954.45 | 0.00 | 0.221368E+09 | 0.00 | 0.77 |
October | 0.571714E+09 | 0.182763E+09 | 0.00 | 4238990.81 | 15149612.42 | 16202175.48 | 0.102066E+10 | 0.00 | 0.80 |
November | 0.114901E+10 | 553235.83 | 0.00 | 2142174.92 | 6816279.01 | 0.104620E+09 | 0.905511E+09 | 0.00 | 0.71 |
December | 0.189855E+10 | 0.00 | 0.00 | 127389.52 | 1394632.12 | 0.369356E+09 | 0.138029E+09 | 0.00 | 0.59 |
Annual Sum or Average | 0.857579E+10 | 0.664709E+10 | 0.00 | 31700634.05 | 0.305999E+09 | 0.937840E+09 | 0.705578E+10 | 0.00 | 0.78 |
Minimum of Months | 52652063.24 | 0.00 | 0.00 | 127389.52 | 52734.17 | 0.00 | 49000902.12 | 0.00 | 0.59 |
Maximum of Months | 0.189855E+10 | 0.178447E+10 | 0.00 | 7415638.68 | 85685954.45 | 0.369356E+09 | 0.124584E+10 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.799116E+09 | 3815145.44 | 0.00 | 13496176.00 | 3851441.23 | 27703657.78 | 0.436800E+10 | 0.00 | 1.27 |
February | 0.128965E+10 | 0.00 | 0.00 | 5740602.30 | 87397.71 | 0.102923E+09 | 0.417573E+10 | 0.00 | 0.88 |
March | 0.129033E+10 | 825886.07 | 0.00 | 7149002.76 | 62275.14 | 95441586.10 | 0.248628E+10 | 0.00 | 0.83 |
April | 0.488851E+09 | 0.223421E+09 | 0.00 | 7754938.32 | 27412020.19 | 0.00 | 0.991882E+09 | 0.00 | 0.72 |
May | 0.269228E+09 | 0.429170E+09 | 0.00 | 5307686.77 | 28006109.81 | 0.00 | 0.401863E+09 | 0.00 | 0.56 |
June | 0.164887E+09 | 0.166016E+10 | 0.00 | 1325957.59 | 44081258.28 | 0.00 | 0.141596E+09 | 0.00 | 0.57 |
July | 68268441.78 | 0.195436E+10 | 0.00 | 481414.79 | 86007390.76 | 0.00 | 41991284.71 | 0.00 | 0.50 |
August | 58366237.36 | 0.199807E+10 | 0.00 | 1256712.82 | 48316014.33 | 0.00 | 89699003.33 | 0.00 | 0.61 |
September | 50711647.69 | 0.155297E+10 | 0.00 | 4150581.60 | 86777031.30 | 0.00 | 0.288577E+09 | 0.00 | 0.70 |
October | 0.534803E+09 | 0.364020E+09 | 0.00 | 10994310.81 | 8896050.76 | 204292.13 | 0.241130E+10 | 0.00 | 0.99 |
November | 0.797405E+09 | 4894540.90 | 0.00 | 12448251.60 | 5336970.79 | 32195111.95 | 0.440880E+10 | 0.00 | 1.18 |
December | 0.107910E+10 | 1116097.82 | 0.00 | 8775477.09 | 745422.89 | 0.233430E+09 | 0.405464E+10 | 0.00 | 0.96 |
Annual Sum or Average | 0.689072E+10 | 0.819282E+10 | 0.00 | 78881112.46 | 0.339579E+09 | 0.491898E+09 | 0.238603E+11 | 0.00 | 0.81 |
Minimum of Months | 50711647.69 | 0.00 | 0.00 | 481414.79 | 62275.14 | 0.00 | 41991284.71 | 0.00 | 0.50 |
Maximum of Months | 0.129033E+10 | 0.199807E+10 | 0.00 | 13496176.00 | 86777031.30 | 0.233430E+09 | 0.440880E+10 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.172367E+10 | 834265.95 | 0.00 | 2178667.03 | 4241346.76 | 0.100770E+09 | 0.660671E+09 | 0.00 | 0.85 |
February | 0.219356E+10 | 0.00 | 0.00 | 1086916.00 | 84709.80 | 0.125695E+09 | 0.860209E+09 | 0.00 | 0.80 |
March | 0.182293E+10 | 438313.05 | 0.00 | 3230354.42 | 0.00 | 65244143.12 | 0.999339E+09 | 0.00 | 0.93 |
April | 0.383038E+09 | 0.208065E+09 | 0.00 | 6830744.33 | 11584246.68 | 0.00 | 0.907302E+09 | 0.00 | 0.97 |
May | 0.176748E+09 | 0.487406E+09 | 0.00 | 5063637.00 | 9650127.25 | 0.00 | 0.461501E+09 | 0.00 | 0.84 |
June | 0.108828E+09 | 0.173371E+10 | 0.00 | 1812334.76 | 25801320.71 | 0.00 | 0.201885E+09 | 0.00 | 0.89 |
July | 45332826.56 | 0.171689E+10 | 0.00 | 627477.89 | 63402216.54 | 0.00 | 64987307.64 | 0.00 | 0.67 |
August | 48686652.08 | 0.157644E+10 | 0.00 | 1190239.35 | 38903180.98 | 0.00 | 92322765.21 | 0.00 | 0.77 |
September | 63561138.85 | 0.976422E+09 | 0.00 | 2475927.27 | 0.103073E+09 | 0.00 | 0.192758E+09 | 0.00 | 0.74 |
October | 0.913738E+09 | 0.178789E+09 | 0.00 | 4120687.49 | 20840874.93 | 452587.41 | 0.752914E+09 | 0.00 | 0.82 |
November | 0.156420E+10 | 1429562.97 | 0.00 | 2989063.44 | 7404040.98 | 56561756.09 | 0.104909E+10 | 0.00 | 0.89 |
December | 0.200484E+10 | 0.00 | 0.00 | 952556.06 | 1596305.02 | 0.364071E+09 | 0.510525E+09 | 0.00 | 0.72 |
Annual Sum or Average | 0.110491E+11 | 0.688042E+10 | 0.00 | 32558605.05 | 0.286581E+09 | 0.712795E+09 | 0.675350E+10 | 0.00 | 0.82 |
Minimum of Months | 45332826.56 | 0.00 | 0.00 | 627477.89 | 0.00 | 0.00 | 64987307.64 | 0.00 | 0.67 |
Maximum of Months | 0.219356E+10 | 0.173371E+10 | 0.00 | 6830744.33 | 0.103073E+09 | 0.364071E+09 | 0.104909E+10 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3603438.87 | 0.00 | 0.00 | 0.293477E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7310531.96 | 0.00 | 0.00 | 0.292529E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 13587549.16 | 0.00 | 0.00 | 0.292161E+09 | 0.00 | 0.31 |
April | 0.00 | 1197422.52 | 0.00 | 15258070.30 | 0.00 | 0.00 | 0.113576E+09 | 0.00 | 0.29 |
May | 0.00 | 14016568.33 | 0.00 | 2806969.76 | 0.00 | 0.00 | 54374555.58 | 0.00 | 0.29 |
June | 0.00 | 92841445.74 | 0.00 | 1540818.82 | 0.00 | 0.00 | 14458380.60 | 0.00 | 0.30 |
July | 0.00 | 0.194973E+09 | 0.00 | 478247.18 | 0.00 | 0.00 | 4058793.70 | 0.00 | 0.28 |
August | 0.00 | 0.188135E+09 | 0.00 | 1445400.06 | 0.00 | 0.00 | 4426706.15 | 0.00 | 0.31 |
September | 0.00 | 0.116011E+09 | 0.00 | 671336.90 | 0.00 | 0.00 | 10505179.22 | 0.00 | 0.29 |
October | 0.00 | 23581421.41 | 0.00 | 6707963.81 | 0.00 | 0.00 | 0.168497E+09 | 0.00 | 0.28 |
November | 0.00 | 2229138.77 | 0.00 | 11643233.21 | 0.00 | 0.00 | 0.236172E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16918663.62 | 0.00 | 0.00 | 0.349743E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.632985E+09 | 0.00 | 81972223.65 | 0.00 | 0.00 | 0.183398E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 478247.18 | 0.00 | 0.00 | 4058793.70 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.194973E+09 | 0.00 | 16918663.62 | 0.00 | 0.00 | 0.349743E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 28119534.62 | 0.00 | 0.00 | 0.294156E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 63039560.94 | 0.00 | 0.00 | 0.294083E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.124759E+09 | 0.00 | 0.00 | 0.293068E+10 | 0.00 | 0.31 |
April | 0.00 | 13377761.51 | 0.00 | 0.146328E+09 | 0.00 | 0.00 | 0.114401E+10 | 0.00 | 0.29 |
May | 0.00 | 0.139559E+09 | 0.00 | 26074929.66 | 0.00 | 0.00 | 0.545183E+09 | 0.00 | 0.29 |
June | 0.00 | 0.926610E+09 | 0.00 | 14494985.01 | 0.00 | 0.00 | 0.144010E+09 | 0.00 | 0.30 |
July | 0.00 | 0.194596E+10 | 0.00 | 4512387.97 | 0.00 | 0.00 | 40008513.62 | 0.00 | 0.28 |
August | 0.00 | 0.186506E+10 | 0.00 | 14263467.84 | 0.00 | 0.00 | 44500702.52 | 0.00 | 0.31 |
September | 0.00 | 0.114588E+10 | 0.00 | 6133398.79 | 0.00 | 0.00 | 0.104992E+09 | 0.00 | 0.29 |
October | 0.00 | 0.234515E+09 | 0.00 | 61198641.07 | 0.00 | 0.00 | 0.168841E+10 | 0.00 | 0.28 |
November | 0.00 | 21532525.28 | 0.00 | 0.106580E+09 | 0.00 | 0.00 | 0.236991E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.153131E+09 | 0.00 | 0.00 | 0.351195E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.629250E+10 | 0.00 | 0.748635E+09 | 0.00 | 0.00 | 0.184060E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 4512387.97 | 0.00 | 0.00 | 40008513.62 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.194596E+10 | 0.00 | 0.153131E+09 | 0.00 | 0.00 | 0.351195E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 9990627.64 | 0.00 | 0.00 | 2154016.62 | 0.00 | 0.00 | 0.284362E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 5578089.22 | 0.00 | 0.00 | 0.295524E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 11945659.57 | 0.00 | 0.00 | 0.293823E+09 | 0.00 | 0.31 |
April | 0.00 | 1561879.66 | 0.00 | 14325487.80 | 0.00 | 0.00 | 0.112817E+09 | 0.00 | 0.29 |
May | 0.00 | 13977805.03 | 0.00 | 2625653.53 | 0.00 | 0.00 | 54512075.62 | 0.00 | 0.29 |
June | 0.00 | 92728595.76 | 0.00 | 1448449.49 | 0.00 | 0.00 | 14459360.04 | 0.00 | 0.30 |
July | 0.00 | 0.194611E+09 | 0.00 | 452256.10 | 0.00 | 0.00 | 4031814.33 | 0.00 | 0.28 |
August | 0.00 | 0.188310E+09 | 0.00 | 1362742.80 | 0.00 | 0.00 | 4378583.70 | 0.00 | 0.31 |
September | 0.00 | 0.114875E+09 | 0.00 | 609054.71 | 0.00 | 0.00 | 10561314.74 | 0.00 | 0.29 |
October | 0.00 | 23460969.47 | 0.00 | 5837438.09 | 0.00 | 0.00 | 0.169254E+09 | 0.00 | 0.28 |
November | 0.00 | 2082143.34 | 0.00 | 10105055.07 | 0.00 | 0.00 | 0.237762E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 14312875.41 | 0.00 | 0.00 | 0.352196E+09 | 0.00 | 0.28 |
Annual Sum or Average | 9990627.64 | 0.631607E+09 | 0.00 | 70756778.40 | 0.00 | 0.00 | 0.183368E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 452256.10 | 0.00 | 0.00 | 4031814.33 | 0.00 | 0.28 |
Maximum of Months | 9990627.64 | 0.194611E+09 | 0.00 | 14325487.80 | 0.00 | 0.00 | 0.352196E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:07:53
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.345417E+12 | 0.255718E+10 | 0.00 | 0.156481E+13 | 0.526309E+12 |
February | 0.379760E+12 | 0.200518E+10 | 0.00 | 0.167392E+13 | 0.253417E+12 |
March | 0.490833E+12 | 0.266195E+10 | 0.00 | 0.163281E+13 | 0.692192E+12 |
April | 0.577554E+12 | 0.681176E+09 | 0.00 | 0.762924E+12 | 0.149567E+13 |
May | 0.569199E+12 | 0.138458E+09 | 0.00 | 0.459404E+12 | 0.164464E+13 |
June | 0.579554E+12 | -639633160.4 | 0.00 | -0.102707E+12 | 0.234989E+13 |
July | 0.550482E+12 | -0.149871E+10 | 0.00 | -0.283720E+12 | 0.235639E+13 |
August | 0.494033E+12 | -917621962.0 | 0.00 | -0.161883E+12 | 0.246932E+13 |
September | 0.415276E+12 | -631247252.5 | 0.00 | -0.114412E+12 | 0.184193E+13 |
October | 0.396393E+12 | 0.110095E+10 | 0.00 | 0.114078E+13 | 0.116595E+13 |
November | 0.359071E+12 | 0.234650E+10 | 0.00 | 0.154799E+13 | 0.689316E+12 |
December | 0.288954E+12 | 0.247453E+10 | 0.00 | 0.176805E+13 | 0.536422E+12 |
Annual Sum or Average | 0.544653E+13 | 0.102787E+11 | 0.00 | 0.988797E+13 | 0.160214E+14 |
Minimum of Months | 0.288954E+12 | -0.149871E+10 | 0.00 | -0.283720E+12 | 0.253417E+12 |