Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:05
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 09:05:50
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 35868.21 | 774.35 | 774.35 |
Net Site Energy | 35868.21 | 774.35 | 774.35 |
Total Source Energy | 97235.86 | 2099.20 | 2099.20 |
Net Source Energy | 97235.86 | 2099.20 | 2099.20 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3682.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7230.09 | 0.00 | 0.00 |
Interior Lighting | 2245.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 323.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3408.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1499.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1318.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 958.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21008.42 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 525.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28113.09 | 525.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7230.09 | 0.00 | 23288.59 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3682.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7230.09 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2245.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 323.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ComputerHVAC | 1498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 1499.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 1318.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 958.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21008.42 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 525.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3682.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7230.09 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2245.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 323.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 3408.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 1499.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1318.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 958.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21008.42 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 525.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 55.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 161.03 | 11.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.09 | 0.00 | 0.50 |
Other | 390.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 606.93 | 11.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.09 | 0.00 | 0.50 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 55.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 161.03 | 11.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.09 | 0.00 | 0.50 |
Other | 390.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 606.93 | 11.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.09 | 0.00 | 0.50 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 28113.094 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 28113.094 | 100.00 |
Total On-Site and Utility Electric Sources | 28113.094 | 100.00 |
Total Electricity End Uses | 28113.094 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 23288.59 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 23288.59 | 100.00 |
Total Water End Uses | 23288.59 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 619.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionDistrictHeatingCoolingMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:05 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 6.5439 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5439 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5439 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5439 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 6.5439 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 6.5439 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 6.5439 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 6.5439 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 6.5439 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 6.5439 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 6.5439 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 6.5439 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 6.5439 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 6.5439 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 6.5439 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 6.5439 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 6.5439 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 6.5742 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 6.5742 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.5439 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.5439 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 6.5439 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.5439 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.5439 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.5439 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.5439 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.5439 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.5439 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.5439 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.5439 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.5439 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.5439 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.5439 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.5439 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.5439 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 6.5439 | 18.58 | 484.4232 | |
Total | 46320.38 | 6.5742 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 6.5742 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.0211 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:00 | 12-JAN-12:30 | - | - | - | - | - | - | - | - | 07-AUG-13:00 | 01-DEC-00:30 | 28-APR-11:00 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 0.00 |
Cooling | 427273.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371732.63 | 0.00 | 0.00 |
Interior Lighting | 190262.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 158743.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 176082.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 68975.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 53621.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 68021.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1853330.76 | 68021.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371732.63 | 14.06 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 427273.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371732.63 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 190262.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3382.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ComputerHVAC | 75926.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 176082.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 68975.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 53621.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 68021.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 11662.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7632.56 | 0.00 |
Interior Lighting | 7112.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1024.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10793.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4750.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4175.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3035.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 569.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 89034.17 | 569.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7632.56 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 251.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.78 | 0.00 |
Interior Lighting | 153.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 22.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 102.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 90.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 65.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 12.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1922.14 | 12.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.78 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 251.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.78 | 0.00 |
Interior Lighting | 153.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 22.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 102.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 90.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 65.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 12.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1922.14 | 12.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.78 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.42 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.467581 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.45 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.449400 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.65 | 0.336725 | 0.339000 | 1.91 | 0.897932 | 0.500000 | 0.001131 | 0.000169 | 1.91 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 53.29 | 0.356937 | 0.354000 | 18.86 | 0.951833 | 0.500000 | 0.001067 | 0.002555 | 18.86 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.62 | 0.338676 | 0.352000 | 1.98 | 0.903137 | 0.500000 | 0.001125 | 0.000422 | 1.98 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.13 | 0.211347 | 0.213000 | 0.240688 | 0.563593 | 0.500000 | 0.001803 | 0.000021 | 0.240688 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.924634 | 0.166450 | 0.200000 | 0.184927 | 0.443866 | 0.500000 | 0.002289 | 0.000016 | 0.184927 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.26 | 0.189869 | 0.200000 | 0.251569 | 0.506317 | 0.500000 | 0.002007 | 0.000024 | 0.251569 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.22 | 0.126405 | 0.200000 | 0.243512 | 0.337079 | 0.500000 | 0.003014 | 0.000021 | 0.243512 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 11.26 | 0.212172 | 0.211000 | 2.38 | 0.565791 | 0.500000 | 0.001796 | 0.000699 | 2.38 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 9.72 | 0.158285 | 0.200000 | 1.94 | 0.422093 | 0.500000 | 0.002407 | 0.000498 | 1.94 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 12.46 | 0.191607 | 0.200000 | 2.49 | 0.510952 | 0.500000 | 0.001988 | 0.000706 | 2.49 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 10.56 | 0.145721 | 0.200000 | 2.11 | 0.388588 | 0.500000 | 0.002615 | 0.000440 | 2.11 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.34 | 0.178602 | 0.200000 | 0.267433 | 0.476273 | 0.500000 | 0.002133 | 0.000106 | 0.360461 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.04 | 0.147664 | 0.200000 | 0.208453 | 0.393771 | 0.500000 | 0.002580 | 0.000070 | 0.237639 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.45 | 0.164318 | 0.200000 | 0.290688 | 0.438180 | 0.500000 | 0.002319 | 0.000105 | 0.358739 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.20 | 0.128355 | 0.200000 | 0.239811 | 0.342280 | 0.500000 | 0.002968 | 0.000063 | 0.239811 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19271.56 | 0.000169 | 388.50 |
CORE_MID VAV BOX REHEAT COIL | 292080.01 | 0.002555 | 6218.23 |
CORE_TOP VAV BOX REHEAT COIL | 48241.08 | 0.000422 | 1133.68 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 2422.29 | 0.000021 | 48.83 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 1861.11 | 0.000016 | 37.52 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 2761.53 | 0.000024 | 56.17 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2450.71 | 0.000021 | 49.40 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 79921.31 | 0.000699 | 2111.79 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 56976.37 | 0.000498 | 1421.63 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 80751.95 | 0.000706 | 2097.93 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 50258.73 | 0.000440 | 1172.67 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 12103.70 | 0.000106 | 319.50 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 7978.83 | 0.000070 | 210.61 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 12046.11 | 0.000105 | 317.99 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7235.50 | 0.000063 | 182.57 |
VAV_BOT WITH REHEAT HEATING COIL | 2938.71 | 0.000026 | 53.63 |
VAV_MID WITH REHEAT HEATING COIL | 0.000000 | 0.000000 | 1.00 |
VAV_TOP WITH REHEAT HEATING COIL | 0.000000 | 0.000000 | 1.00 |
CAV_BAS HEATING COIL | 243579.71 | 0.002131 | 5631.26 |
Design Size Maximum Heating Air Flow Rate [m3/s] | Design Size Maximum Cooling Air Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT | 0.338402 | 21.39 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.09 | 2.84 | 10.18 | 2.84 | 9.38 | 9.38 | 0.300000 | 0.302210 | 9.38 |
VAV_MID WITH REHEAT | 48.65 | 27.79 | 97.29 | 27.79 | 89.10 | 89.10 | 0.300000 | 0.311873 | 89.10 |
VAV_TOP WITH REHEAT | 5.32 | 2.98 | 10.65 | 2.98 | 10.48 | 10.48 | 0.300000 | 0.284707 | 10.48 |
CAV_BAS | 5.42 | 5.42 | 5.42 | 5.42 | 5.42 | 5.42 | 1.00 | 1.00 | 5.42 |
AIRLOOP DATACENTER BOT | 0.467581 | 0.467581 | 0.467581 | 0.467581 | 0.467581 | 0.467581 | 1.00 | 1.00 | 0.467581 |
AIRLOOP DATACENTER MID | 4.45 | 4.45 | 4.45 | 4.45 | 4.45 | 4.45 | 1.00 | 1.00 | 4.45 |
AIRLOOP DATACENTER TOP | 0.449400 | 0.449400 | 0.449400 | 0.449400 | 0.449400 | 0.449400 | 1.00 | 1.00 | 0.449400 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.38 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 89.10 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.48 | |
CAV_BAS_OA_CONTROLLER | 5.42 | 1.20 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.467581 | 0.015633 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.45 | 0.156328 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.449400 | 0.015633 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 29.18 | 6.67 | 11.04 | 0.008313 | 0.007000 | 246412.43 | 0.010483 | 9.38 |
VAV_MID WITH REHEAT COOLING COIL | 29.61 | 6.67 | 11.04 | 0.008446 | 0.007000 | 2423888.11 | 0.103118 | 89.10 |
VAV_TOP WITH REHEAT COOLING COIL | 28.56 | 6.67 | 11.05 | 0.008208 | 0.007000 | 263669.41 | 0.011217 | 10.48 |
CAV_BAS COOLING COIL | 28.00 | 6.67 | 11.42 | 0.008288 | 0.007000 | 131447.31 | 0.005592 | 5.42 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.38 |
VAV_MID WITH REHEAT FAN | 89.10 |
VAV_TOP WITH REHEAT FAN | 10.48 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.010483 | 0.000045 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000026 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.103118 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.000000 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.011217 | 0.000042 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000000 | |
CAV_BAS_COOLC_CONTROLLER | 0.005592 | 0.000085 |
CAV_BAS_HEATC_CONTROLLER | 0.002131 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.42 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.467581 | 9608.95 | 6180.90 | 0.000235 |
AIRLOOP DATACENTER MID COOLING COIL | 4.45 | 91593.94 | 58875.09 | 0.002243 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.449400 | 9498.28 | 6024.95 | 0.000233 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.467581 | 0.467581 | 0.467581 | 0.467581 | 9608.95 | 9608.95 | 516.16 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.45 | 4.45 | 4.45 | 4.45 | 91593.94 | 91593.94 | 5161.60 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.449400 | 0.449400 | 0.449400 | 0.449400 | 9498.28 | 9498.28 | 516.16 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.467581 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.45 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.449400 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT HEATING COIL | 0.467581 | 9608.95 | 0.000235 |
AIRLOOP DATACENTER MID HEATING COIL | 4.45 | 91593.94 | 0.002243 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.449400 | 9498.28 | 0.000233 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 516.16 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 5161.60 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 516.16 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.130410 | 26606.59 | |
HEATSYS1 PUMP | 0.008074 | 2407.39 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.130410 | 15.65 |
HEATSYS1 | 0.008074 | 0.968850 |
COOLSYS1_SUPPLY | 0.130410 | 15.65 |
SINGLE WATER PLANT LOOP | 0.002711 | 0.325328 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.130410 | 0.130410 | 547395.94 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 922879.21 | 922879.21 | 0.008074 |
CENTRAL BOILER | 111672.61 | 111672.61 | 0.002711 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.130410 | 18420.64 |
PLANT CIRC PUMP | 0.002711 | 684.61 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.130410 | 0.065770 | 1549787.95 | 1557117.22 | 0.076094 |
COOLSYS1 CHILLER2 | 0.130410 | 0.065770 | 1549787.95 | 1557117.22 | 0.076094 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.002711 | 35644.39 | 20550.62 | 17822.20 | 1996.20 | 5833.87 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.152187 | 18.26 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.152187 | 45381.73 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 54.17 | 1847496.72 | 10.83 | 230937.09 |
TOWERWATERSYS COOLTOWER 2 | 54.17 | 1847496.72 | 10.83 | 230937.09 |
Design Water Flow Rate [m3/s] Equipment # 43 | |
WSHPPLANT OPERATION SCHEME | 0.080037 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 6.544 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 11.386 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.544 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.614 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.544 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.614 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.544 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.614 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.544 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.614 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.544 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.614 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.544 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.614 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.544 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.614 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.544 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.614 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.544 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.614 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.544 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.614 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.544 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.614 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.544 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.614 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.544 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.614 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.544 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.614 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.544 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.614 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 6.544 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.967 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 18188.179 | 6.544 | 121.577 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18188.179 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 16334.263 | 6.544 | 121.577 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16334.263 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 16334.263 | 6.544 | 121.577 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16334.263 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 16334.263 | 6.544 | 121.577 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16334.263 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2050.930 | 6.544 | 121.577 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2050.930 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1321.697 | 6.544 | 121.577 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1321.697 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2050.975 | 6.544 | 121.577 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2050.975 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1321.697 | 6.544 | 121.577 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1321.697 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2050.930 | 6.544 | 121.577 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2050.930 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1321.697 | 6.544 | 121.577 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1321.697 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2050.975 | 6.544 | 121.577 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2050.975 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1321.697 | 6.544 | 121.577 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1321.697 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2050.930 | 6.544 | 121.577 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2050.930 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1321.697 | 6.544 | 121.577 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1321.697 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2050.975 | 6.544 | 121.577 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2050.975 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1321.697 | 6.544 | 121.577 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1321.697 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5128.288 | 6.544 | 121.577 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5128.288 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.743 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.656 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 2.135 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4064 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4365 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3009 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
47 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
48 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
49 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
50 | 9 | 0.76055735E-15 | 0.55973061E-16 | -0.11090261E-09 | -0.43371185E-17 |
51 | 8 | 0.16390423E-07 | 0.22068143E-12 | 0.31740643E-03 | -0.18636477E-09 |
52 | 7 | -0.10429999E-01 | 0.12271718E-07 | -0.20474149E-01 | 0.11859286E-03 |
53 | 6 | 0.35611320 | 0.43955117E-05 | 0.42991281 | -0.41673803E-02 |
54 | 5 | -4.7098961 | 0.16827687E-03 | -4.1162358 | 0.57223947E-01 |
55 | 4 | 30.875684 | 0.14076848E-02 | 20.167480 | -0.39388153 |
56 | 3 | -106.69740 | 0.31291265E-02 | -53.106522 | 1.4497707 |
57 | 2 | 192.63914 | 0.17911574E-02 | 75.570394 | -2.8293896 |
58 | 1 | -169.50392 | 0.19431750E-03 | -54.592911 | 2.7164834 |
59 | 0 | 57.057407 | 0.11257899E-05 | 15.674734 | |
60 | 9 | 0.11474244E-14 | 0.54197419E-16 | -0.11508650E-09 | -0.49945851E-17 |
61 | 8 | 0.16984416E-07 | 0.21156325E-12 | 0.32425024E-03 | -0.19311866E-09 |
62 | 7 | -0.10636353E-01 | 0.11664670E-07 | -0.20772028E-01 | 0.12093918E-03 |
63 | 6 | 0.36172330 | 0.41637772E-05 | 0.43474562 | -0.42335086E-02 |
64 | 5 | -4.7646824 | 0.15893927E-03 | -4.1535939 | 0.57903236E-01 |
65 | 4 | 31.118254 | 0.13261305E-02 | 20.314042 | -0.39710182 |
66 | 3 | -107.21418 | 0.29411649E-02 | -53.396504 | 1.4572354 |
67 | 2 | 193.15212 | 0.16802168E-02 | 75.835339 | -2.8375342 |
68 | 1 | -169.69371 | 0.18194848E-03 | -54.668081 | 2.7198097 |
69 | 0 | 57.057407 | 0.10520719E-05 | 15.660794 | |
70 | 9 | 0.66246833E-15 | 0.57738042E-16 | -0.92036509E-10 | -0.27018983E-17 |
71 | 8 | 0.13701644E-07 | 0.25726543E-12 | 0.28527343E-03 | -0.15579243E-09 |
72 | 7 | -0.94571194E-02 | 0.14940887E-07 | -0.19068097E-01 | 0.10753086E-03 |
73 | 6 | 0.32965778 | 0.54453531E-05 | 0.40701455 | -0.38555430E-02 |
74 | 5 | -4.4514676 | 0.21157254E-03 | -3.9387765 | 0.54019785E-01 |
75 | 4 | 29.731016 | 0.17930056E-02 | 19.470280 | -0.37868589 |
76 | 3 | -104.25747 | 0.40308508E-02 | -51.726693 | 1.4145289 |
77 | 2 | 190.21562 | 0.23301583E-02 | 74.311741 | -2.7909129 |
78 | 1 | -168.60668 | 0.25508611E-03 | -54.239505 | 2.7007581 |
79 | 0 | 57.057407 | 0.14924561E-05 | 15.743350 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.5037_SHGC_EAST_0.23 | 35 | 1 | VerySmooth | 2.864 | 2.864 | 1.000 | 0.231 | ||
2 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 36 | 1 | VerySmooth | 2.864 | 2.864 | 1.000 | 0.231 | ||
3 | WINDOW_U_0.5037_SHGC_WEST_0.23 | 37 | 1 | VerySmooth | 2.864 | 2.864 | 1.000 | 0.231 | ||
4 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 38 | 1 | VerySmooth | 2.864 | 2.864 | 1.000 | 0.231 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.92411E-002 | 0.14129 | 0.63052 | 0.63052 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10752 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.92411E-002 | 0.14129 | 0.63052 | 0.63052 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10752 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.92411E-002 | 0.14129 | 0.63052 | 0.63052 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10752 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.92411E-002 | 0.14129 | 0.63052 | 0.63052 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10752 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.3317E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3327E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4397E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4405E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9276E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9281E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1459E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1463E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.3555E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4221E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4591E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5149E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9426E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9865E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1575E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1867E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.3263E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5859E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9349E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6949E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3396E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9434E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.3959E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.3815E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.3600E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4434E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4639E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5376E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9471E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.0035E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1578E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1876E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.3316E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3328E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4396E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4406E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9275E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9283E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1458E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1463E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.4984E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6036E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.3748E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4811E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.2558E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3138E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 1.9611E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9812E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9269E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4207E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7605E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2837E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9562E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.1971E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.4646E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.1889E-003 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.4754E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5214E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.3464E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3803E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.2387E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2530E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 1.9612E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9816E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1081E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1092E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.5626E-004 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.5713E-004 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 8.4544E-004 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.4606E-004 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1459E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1463E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1325E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1928E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.7616E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0241E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 8.6085E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.9446E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1578E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1876E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7138E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.6181E-003 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3456E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.3923E-003 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3071E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.1729E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3959E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.3789E-003 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1307E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1901E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.7403E-004 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0196E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 8.5737E-004 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.8387E-004 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1576E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1867E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1080E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1091E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.5619E-004 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.5699E-004 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 8.4536E-004 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.4585E-004 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1459E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1463E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1656E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2133E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 1.9745E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0092E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 1.9380E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9510E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 1.9612E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9816E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3264E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.1977E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.0486E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.0211E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3403E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 9.6514E-003 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.4646E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 9.1889E-003 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1844E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2703E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 1.9981E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0812E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 1.9541E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0056E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 1.9611E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9812E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.3117E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.5653E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.7637E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.7190E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.6212E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.7730E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 2.7727E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.3412E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.3666E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9712E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.1865E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.8094E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.3674E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.6963E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 2.8359E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.3555E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0725E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4346E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.6698E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.1502E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.6219E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 8.9157E-003 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7727E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3410E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.7137E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.6780E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.4107E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.4623E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.7027E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.3985E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.8359E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.3555E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.3128E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.5708E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.7664E-002 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.7254E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.6255E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.7788E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 2.7759E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.3438E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.3660E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9731E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.1867E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.8114E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.3693E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.6993E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 2.8390E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.3581E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0703E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4352E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.6683E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.1508E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.6229E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 8.9284E-003 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7759E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3436E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.7124E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.6793E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.4101E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4636E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.7042E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4008E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.8390E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.3581E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 74994.45596 | 74994.45596 | 5.41602 | 5.41602 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2779.42662 | 149.60210 | 1.20019 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20019 | 00:10:00 | 12.70000 | 9.15345E-003 | 2779.42662 | 149.60210 | 1.20019 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 78222.13131 | 78222.13131 | 5.64866 | 5.64866 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 738119.04356 | 738119.04356 | 53.28789 | 53.28789 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 102233.17591 | 102233.17591 | 4.30237 | 10.77825 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 77049.50887 | 77049.50887 | 5.61611 | 5.61611 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 28345.80267 | 28345.80267 | 1.19562 | 1.19562 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 15502.48581 | 15502.48581 | 1.12999 | 1.12999 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 42.80000 | 1.07818E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.13533 | 00:10:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 | |
11 | PERIMETER_BOT_ZN_2 | Cooling | 12685.19326 | 12685.19326 | 0.92463 | 0.92463 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 39.11400 | 1.07755E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 0.00000 | 0.00000 | 0.00000 | 8.72129E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 | |
13 | PERIMETER_BOT_ZN_1 | Cooling | 17256.56000 | 17256.56000 | 1.25785 | 1.25785 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 42.63833 | 1.07815E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 224.65746 | 224.65746 | 9.60430E-003 | 0.13533 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 16703.96742 | 16703.96742 | 1.21756 | 1.21756 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 42.08867 | 1.07806E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 0.00000 | 0.00000 | 0.00000 | 8.72129E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 | |
17 | PERIMETER_MID_ZN_3 | Cooling | 154416.04028 | 154416.04028 | 11.25601 | 11.25601 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 56002.36559 | 56002.36559 | 2.37475 | 2.37475 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 133389.62616 | 133389.62616 | 9.72329 | 9.72329 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 39.35650 | 1.07759E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 37391.74300 | 37391.74300 | 1.58593 | 1.58593 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 170993.15692 | 170993.15692 | 12.46437 | 12.46437 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 55645.96023 | 55645.96023 | 2.35955 | 2.35955 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 144891.08763 | 144891.08763 | 10.56166 | 10.56166 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 28981.84929 | 28981.84929 | 1.22656 | 1.22656 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 18343.68901 | 18343.68901 | 1.33716 | 1.33716 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 8474.30357 | 8474.30357 | 0.36046 | 0.36046 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 14298.16320 | 14298.16320 | 1.04227 | 1.04227 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 39.84150 | 1.07767E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 5586.10969 | 5586.10969 | 0.23764 | 0.23764 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 19938.83099 | 19938.83099 | 1.45344 | 1.45344 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 42.80000 | 1.07818E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 8434.03353 | 8434.03353 | 0.35874 | 0.35874 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 16449.12742 | 16449.12742 | 1.19906 | 1.19906 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 4820.60385 | 4820.60385 | 0.20489 | 0.20489 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8134.11529 | 8134.11529 | 0.46758 | 0.46758 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 33.16467 | 1.07653E-002 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56328E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 77428.44172 | 77428.44172 | 4.45089 | 4.45089 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 33.16467 | 1.07653E-002 | 36.20274 | 1.94861 | 0.15633 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15633 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 0.15633 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7816.91879 | 7816.91879 | 0.44940 | 0.44940 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 41.70067 | 1.07799E-002 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56328E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372061.43988 | 372061.43988 | 21.38956 | 21.38956 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 33.97300 | 1.07667E-002 | 783.67941 | 42.18139 | 0.33840 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33840 | 00:10:00 | 12.70000 | 9.15345E-003 | 783.67941 | 42.18139 | 0.33840 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 182428.68 | 9.38285 | 9.38285 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 184.19 | 1.52292 | 1.52292 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1728140.30 | 89.10300 | 89.10300 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 2216.31 | 18.32505 | 18.32505 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 199471.65 | 10.47833 | 10.47833 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 285.11 | 2.35735 | 2.35735 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | CAV_BAS | Cooling | Sensible | 91358.47 | 5.41602 | 5.41602 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 39627.65 | 1.20019 | 1.20019 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8146.83 | 0.46758 | 0.46758 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BOT | Heating | Sensible | 516.16 | 1.56328E-002 | 1.56328E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER MID | Cooling | Sensible | 77605.53 | 4.45089 | 4.45089 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER MID | Heating | Sensible | 5161.60 | 0.15633 | 0.15633 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7998.17 | 0.44940 | 0.44940 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER TOP | Heating | Sensible | 516.16 | 1.56328E-002 | 1.56328E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.41602 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.64866 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33672 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33900 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.91490 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89793 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13149E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.68596E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.91490 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19271.55881 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.68596E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 388.49950 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 53.28789 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35694 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35400 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.86391 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.95183 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.06741E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.55524E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.86391 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 292080.00974 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.55524E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6218.23228 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.61611 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33868 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35200 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.97687 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90314 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12497E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.22034E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.97687 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 48241.07542 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.22034E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1133.68461 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.12999 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21135 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21300 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24069 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56359 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.80272E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.11912E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24069 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2422.28988 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.11912E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 48.83146 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92463 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16645 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18493 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44387 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.28898E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.62818E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.18493 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1861.10790 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.62818E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 37.51847 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.25785 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18987 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25157 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50632 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.00665E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.41591E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25157 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2761.52894 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.41591E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 56.17081 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.21756 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12640 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24351 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33708 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.01413E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.14399E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24351 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2450.70931 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.14399E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 49.40438 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.25601 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21217 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21100 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.37502 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56579 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.79572E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.99186E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.37502 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 79921.31217 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.99186E-004 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2111.79093 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.72329 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15828 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.94466 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42209 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.40705E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.98454E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.94466 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 56976.37027 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.98454E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1421.63129 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.46437 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19161 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.49287 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51095 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.98845E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.06453E-004 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.49287 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 80751.94577 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.06453E-004 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2097.93458 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.56166 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14572 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.11233 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38859 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.61459E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.39685E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.11233 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 50258.73424 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.39685E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1172.66917 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.33716 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17860 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26743 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47627 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.13323E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.05888E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36046 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12103.70161 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05888E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 319.50407 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.04227 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14766 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20845 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39377 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.58018E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.98023E-005 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23764 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7978.82849 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.98023E-005 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 210.61036 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.45344 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16432 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29069 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43818 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.31868E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.05385E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35874 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12046.10868 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05385E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 317.98656 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.19906 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12836 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23981 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34228 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96833E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.32993E-005 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23981 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7235.49740 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.32993E-005 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 182.56533 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46758 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.45089 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.44940 |
215 | ZoneHVAC:IdealLoadsAirSystem | AIRLOOP DATACENTER BASEMENT | Design Size Maximum Heating Air Flow Rate [m3/s] | 0.33840 |
216 | ZoneHVAC:IdealLoadsAirSystem | AIRLOOP DATACENTER BASEMENT | Design Size Maximum Cooling Air Flow Rate [m3/s] | 21.38956 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.08935 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.83559 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.17869 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.83559 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.38285 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.38285 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.30221 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 48.64661 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 27.78879 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 97.29321 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 27.78879 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 89.10300 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 89.10300 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31187 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.32402 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.98326 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.64804 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.98326 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.47833 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.47833 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.28471 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.41602 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.41602 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.41602 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.41602 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.41602 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.41602 |
247 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46758 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46758 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46758 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46758 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46758 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.46758 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
257 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.45089 |
258 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.45089 |
259 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.45089 |
260 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.45089 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.45089 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.45089 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
265 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.44940 |
266 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.44940 |
267 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.44940 |
268 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.44940 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.44940 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.44940 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
273 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.38285 |
274 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 89.10300 |
275 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.47833 |
276 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.41602 |
277 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.46758 |
278 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.45089 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.44940 |
280 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.38285 |
281 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.18133 |
282 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
283 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04030 |
284 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.31292E-003 |
285 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 246412.43045 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.04830E-002 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.38285 |
289 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 2938.71377 |
290 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.57091E-005 |
291 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 53.62651 |
292 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.38285 |
293 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.04830E-002 |
294 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.54252E-005 |
295 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.57091E-005 |
296 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 89.10300 |
297 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.61401 |
298 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
299 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04073 |
300 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.44632E-003 |
301 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2423888.11158 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 0.10312 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 89.10300 |
305 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 0.00000 |
306 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 0.00000 |
307 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1.00000 |
308 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 89.10300 |
309 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.10312 |
310 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.61793E-006 |
311 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.00000 |
312 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.47833 |
313 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.55791 |
314 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
315 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04932 |
316 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.20814E-003 |
317 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 263669.40756 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.12171E-002 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.47833 |
321 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 0.00000 |
322 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 0.00000 |
323 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1.00000 |
324 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.47833 |
325 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.12171E-002 |
326 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.24522E-005 |
327 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.00000 |
328 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.41602 |
329 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20019 |
330 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.00074 |
331 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
332 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.41913 |
333 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.28753E-003 |
334 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 131447.31422 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.59207E-003 |
337 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.41602 |
338 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 243579.71275 |
339 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.13094E-003 |
340 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5631.25707 |
341 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.41602 |
342 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.59207E-003 |
343 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.51546E-005 |
344 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.13094E-003 |
345 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46758 |
346 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56328E-002 |
347 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46758 |
348 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9608.95324 |
349 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6180.90007 |
350 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.35323E-004 |
351 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46758 |
352 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46758 |
353 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46758 |
354 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46758 |
355 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9608.95324 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9608.95324 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 516.16021 |
358 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
359 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46758 |
360 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46758 |
361 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9608.95324 |
362 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.35323E-004 |
363 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 516.16021 |
364 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.45089 |
365 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15633 |
366 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.45089 |
367 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 91593.93500 |
368 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 58875.08936 |
369 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.24313E-003 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.45089 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.45089 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.45089 |
373 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.45089 |
374 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 91593.93500 |
375 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 91593.93500 |
376 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 5161.60213 |
377 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
378 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.45089 |
379 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.45089 |
380 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 91593.93500 |
381 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.24313E-003 |
382 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 5161.60213 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.44940 |
384 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56328E-002 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44940 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9498.27782 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6024.95383 |
388 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32612E-004 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.44940 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.44940 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.44940 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.44940 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9498.27782 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9498.27782 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 516.16021 |
396 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
397 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.44940 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44940 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9498.27782 |
400 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32612E-004 |
401 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 516.16021 |
402 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.13041 |
403 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 26606.58862 |
404 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.13041 |
405 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 15.64919 |
406 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.13041 |
407 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.13041 |
408 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 547395.93997 |
409 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
410 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 8.07375E-003 |
411 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.96885 |
412 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 8.07375E-003 |
413 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 2407.38506 |
414 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
415 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 922879.20515 |
416 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 922879.21000 |
417 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 8.07375E-003 |
418 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.13041 |
419 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 15.64919 |
420 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 0.13041 |
421 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 18420.63881 |
422 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.13041 |
423 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.57700E-002 |
424 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1549787.94799 |
425 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1557117.21500 |
426 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.60937E-002 |
427 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.13041 |
428 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.57700E-002 |
429 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1549787.94799 |
430 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1557117.21500 |
431 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.60937E-002 |
432 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 2.71106E-003 |
433 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 0.32533 |
434 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 2.71106E-003 |
435 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 684.61089 |
436 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 2.71106E-003 |
437 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 35644.39112 |
438 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 20550.61568 |
439 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 17822.19556 |
440 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 1996.19659 |
441 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 5833.86829 |
442 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 111672.61251 |
443 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 111672.61000 |
444 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 2.71106E-003 |
445 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
446 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
447 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
448 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
449 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
450 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.15219 |
451 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 18.26249 |
452 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.15219 |
453 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 45381.72905 |
454 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 54.17058 |
455 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1847496.71944 |
456 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.83412 |
457 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 230937.08993 |
458 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 54.17058 |
459 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1847496.71944 |
460 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.83412 |
461 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 230937.08993 |
462 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 43 | 8.00375E-002 |
463 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 43 | 8.00375E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18273.18 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 276858.81 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 45703.30 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 2296.80 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 1764.69 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 2618.35 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2323.75 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 75746.82 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 53961.85 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 76466.83 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 47616.37 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 11469.38 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 7560.63 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 11414.83 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 6852.35 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 2753.39 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 0.00 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 0.00 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 201825.53 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 279710.03 | 185439.67 | 94270.36 | 0.66 | 35509.82 | 360.16 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2684011.77 | 1773524.31 | 910487.46 | 0.66 | 340090.32 | 3449.38 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 308397.69 | 205312.24 | 103085.45 | 0.67 | 39288.92 | 398.49 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 155767.13 | 104401.29 | 51365.84 | 0.67 | 19363.64 | 196.40 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 7.53 | 25.69 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 7.53 | 25.69 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2817887854 | 0.2259592964 | Pass | Pass | 1.4300966749 | 4.1496601595 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2015724239 | 0.2631267988 | Pass | Pass | 0.1144264552 | 0.3160393019 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.0929352972E-002 | 0.1333558430 | Pass | Pass | 1.4935805793E-002 | 0.1215045644 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.9210598457E-002 | 1.3210446075E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1529150178 | 0.1933734495 | Pass | Pass | 0.1132159732 | 0.3149935463 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1755660887 | 0.2232893906 | Pass | Pass | 0.1136111785 | 0.3151330823 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1688663231 | 0.2082161868 | Pass | Pass | 0.1295474203 | 0.3523295822 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2312882042 | 0.3121345912 | Pass | Pass | 0.1245339563 | 0.3389653968 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.9383894930E-002 | 9.8261619673E-002 | Pass | Pass | 1.4243597713E-002 | 0.1185178240 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.7990843989E-002 | 0.1224469918 | Pass | Pass | 1.4246027424E-002 | 0.1185280441 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.8434694274E-002 | 0.1355071673 | Pass | Pass | 1.3989028799E-002 | 0.1173303475 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.1082794381E-002 | 0.1377628450 | Pass | Pass | 1.4005675275E-002 | 0.1174788428 | Pass | Fail |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.6850419616E-002 | 2.7793297022E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.7989727734E-002 | 2.6556106224E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 5.9398793030E-002 | 5.1413037891E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.1757854310E-002 | 3.8017618976E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.7586146421E-002 | 3.9454430164E-002 | Pass | Pass | 0.2526548249 | 0.8566333408 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.7482797749E-003 | 1.6034529807E-002 | Pass | Pass | 1.5658471542E-002 | 0.1307614307 | Pass | Fail |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.6677300053E-002 | 4.3306930939E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 9.6680965714E-005 | 1.1938303367E-004 | Pass | Pass | 1.8982413113E-003 | 2.2503806399E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.9587776694E-005 | 9.7887839937E-005 | Pass | Pass | 3.3262587967E-003 | 2.1218040428E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.9906092585E-005 | 1.0557354851E-004 | Pass | Pass | 1.7862990630E-002 | 7.9998416380E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.2204460493E-015 | 2.4725840765E-015 | Pass | Pass | 4.1793466039E-005 | 1.0626517976E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4022.64 | -134.0 | 0.00 | -8563.8 | 30678.65 | 26003.54 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.5037_SHGC_EAST_0.23 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.5037_SHGC_EAST_0.23 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.5037_SHGC_EAST_0.23 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.5037_SHGC_WEST_0.23 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.5037_SHGC_WEST_0.23 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.5037_SHGC_WEST_0.23 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.864 | 0.231 | 0.231 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5037_SHGC_EAST_0.23 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.864 | 0.231 | 0.231 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.864 | 0.231 | 0.231 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5037_SHGC_WEST_0.23 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.864 | 0.231 | 0.231 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.864 | 0.231 | 0.231 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5037_SHGC_EAST_0.23 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.864 | 0.231 | 0.231 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.864 | 0.231 | 0.231 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5037_SHGC_WEST_0.23 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.864 | 0.231 | 0.231 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.864 | 0.231 | 0.231 | |||||||||||||||||
North Total or Average | 1043.06 | 2.864 | 0.231 | 0.231 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.864 | 0.231 | 0.231 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.5439 | 2779.43 | 18188.18 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 150.64 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.5439 | 2496.12 | 16334.26 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 135.29 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.5439 | 24961.20 | 163342.63 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 1352.86 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.5439 | 2496.12 | 16334.26 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 135.29 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.5439 | 313.41 | 2050.93 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.54 | 0.0000 | Y | 9.83 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.5439 | 201.98 | 1321.70 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.45 | 0.0000 | Y | 6.31 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.5439 | 313.42 | 2050.97 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.17 | 0.0000 | Y | 9.69 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.5439 | 201.98 | 1321.70 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.47 | 0.0000 | Y | 6.32 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.5439 | 3134.13 | 20509.30 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.54 | 0.0000 | Y | 98.31 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.5439 | 2019.75 | 13216.97 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.44 | 0.0000 | Y | 63.12 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.5439 | 3134.20 | 20509.75 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.18 | 0.0000 | Y | 96.94 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.5439 | 2019.75 | 13216.97 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.46 | 0.0000 | Y | 63.17 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.5439 | 313.41 | 2050.93 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.53 | 0.0000 | Y | 9.83 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.5439 | 201.98 | 1321.70 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.44 | 0.0000 | Y | 6.31 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.5439 | 313.42 | 2050.97 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.18 | 0.0000 | Y | 9.69 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.5439 | 201.98 | 1321.70 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.46 | 0.0000 | Y | 6.32 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 6.5439 | 783.68 | 5128.29 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 42.47 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 9.7790 | 362.03 | 3540.27 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 36.26 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
Interior Lighting Total | 6.5742 | 46320.38 | 304519.52 | 706.31 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2050.97 | 791.06 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2050.97 | 284.06 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1321.70 | 509.78 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1321.70 | 183.06 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2050.93 | 791.04 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2050.93 | 284.05 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1321.70 | 509.78 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1321.70 | 183.06 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2050.97 | 791.06 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2050.97 | 284.06 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1321.70 | 509.78 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1321.70 | 183.06 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2050.93 | 791.04 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2050.93 | 284.05 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1321.70 | 509.78 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1321.70 | 183.06 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2050.97 | 791.06 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2050.97 | 284.06 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1321.70 | 509.78 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1321.70 | 183.06 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2050.93 | 791.04 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2050.93 | 284.05 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1321.70 | 509.78 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1321.70 | 183.06 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.05 | AstronomicalClock | - | 41.85 | 41.85 | 78.35 | |
EXTERIOR_LIGHTS_B | 991.40 | AstronomicalClock | - | 83.85 | 62.85 | 11.70 | |
EXTERIOR_LIGHTS_C | 26646.63 | AstronomicalClock | - | 83.85 | 46.68 | 233.50 | |
Exterior Lighting Total | 37611.08 | 323.55 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3058367.71 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 922879.21 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1557117.22 | 6.91 | 1493786.98 | 6.60 | 7.53 | 25.69 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1557117.22 | 6.91 | 1493786.98 | 6.60 | 7.53 | 25.69 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 148548.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 111672.61 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1847496.72 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1847496.72 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 246412.43 | 279710.03 | 185439.67 | 94270.36 | 0.66 | - | 35509.82 | 360.16 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2423888.11 | 2684011.77 | 1773524.31 | 910487.46 | 0.66 | - | 340090.32 | 3449.38 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 263669.41 | 308397.69 | 205312.24 | 103085.45 | 0.67 | - | 39288.92 | 398.49 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 131447.31 | 155767.13 | 104401.29 | 51365.84 | 0.67 | - | 19363.64 | 196.40 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9608.95 | 6180.90 | 3428.05 | 0.64 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 91593.94 | 58875.09 | 32718.85 | 0.64 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9498.28 | 6024.95 | 3473.32 | 0.63 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19271.56 | 18273.18 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 292080.01 | 276858.81 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 48241.08 | 45703.30 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 2422.29 | 2296.80 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 1861.11 | 1764.69 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2761.53 | 2618.35 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 2450.71 | 2323.75 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 79921.31 | 75746.82 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 56976.37 | 53961.85 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 80751.95 | 76466.83 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 50258.73 | 47616.37 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12103.70 | 11469.38 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 7978.83 | 7560.63 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12046.11 | 11414.83 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 7235.50 | 6852.35 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 2938.71 | 2753.39 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 0.00 | 0.00 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 0.00 | 0.00 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 243579.71 | 201825.53 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9608.95 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 91593.94 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9498.28 | 0.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 516.16 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 5161.60 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 516.16 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.38 | 20275.83 | 2160.95 | 1.00 | 1.12 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 89.10 | 192546.83 | 2160.95 | 1.00 | 1.08 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.48 | 22522.79 | 2149.46 | 1.00 | 1.12 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.42 | 9183.69 | 1695.65 | 1.00 | 1.16 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 523.74 | 1120.11 | 1.00 | 1.64 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.45 | 4985.48 | 1120.11 | 1.00 | 1.16 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 503.38 | 1120.11 | 1.00 | 1.66 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.130410 | 26606.59 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.008074 | 2407.39 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.130410 | 18420.64 | 141251.81 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.002711 | 684.61 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.152187 | 45381.73 | 298196.27 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 74994.46 | 74994.46 | 26.98 | 5.416 | 5.416 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00747 | 35.62 | 0.01077 | 1.200 | 0.00 |
CORE_BOTTOM | 78222.13 | 78222.13 | 31.34 | 5.649 | 5.649 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 35.62 | 0.01077 | 1.078 | 0.00 |
CORE_MID | 738119.04 | 738119.04 | 295.71 | 53.288 | 53.288 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00742 | 35.62 | 0.01077 | 10.778 | 0.00 |
CORE_TOP | 77049.51 | 77049.51 | 30.87 | 5.616 | 5.616 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00739 | 42.80 | 0.01078 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 15502.49 | 15502.49 | 49.46 | 1.130 | 1.130 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00733 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 12685.19 | 12685.19 | 62.81 | 0.925 | 0.925 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 24.00 | 24.00 | 0.00726 | 39.11 | 0.01078 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 17256.56 | 17256.56 | 55.06 | 1.258 | 1.258 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00730 | 42.64 | 0.01078 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 16703.97 | 16703.97 | 82.70 | 1.218 | 1.218 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 24.00 | 24.00 | 0.00720 | 42.09 | 0.01078 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 154416.04 | 154416.04 | 492.69 | 11.256 | 11.256 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00744 | 42.80 | 0.01078 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 133389.63 | 133389.63 | 660.43 | 9.723 | 9.723 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 24.00 | 24.00 | 0.00734 | 39.36 | 0.01078 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 170993.16 | 170993.16 | 545.57 | 12.464 | 12.464 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00740 | 42.72 | 0.01078 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 144891.09 | 144891.09 | 717.37 | 10.562 | 10.562 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00731 | 41.96 | 0.01078 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 18343.69 | 18343.69 | 58.53 | 1.337 | 1.337 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00741 | 42.70 | 0.01078 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14298.16 | 14298.16 | 70.79 | 1.042 | 1.042 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 24.00 | 24.00 | 0.00735 | 39.84 | 0.01078 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 19938.83 | 19938.83 | 63.62 | 1.453 | 1.453 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00738 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16449.13 | 16449.13 | 81.44 | 1.199 | 1.199 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00730 | 41.96 | 0.01078 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8134.12 | 8134.12 | 224.68 | 0.468 | 0.468 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 33.16 | 0.01077 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 77428.44 | 77428.44 | 2138.75 | 4.451 | 4.451 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 33.16 | 0.01077 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7816.92 | 7816.92 | 215.92 | 0.449 | 0.449 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 27.00 | 27.00 | 0.00709 | 41.70 | 0.01078 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372061.44 | 372061.44 | 474.76 | 21.390 | 21.390 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 33.97 | 0.01077 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 26.70 | 0.00700 | 12.70 | 0.00915 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 24.62 | 0.00915 | 12.70 | 0.00915 | 1.078 | 0.00 | |
CORE_MID | 102233.18 | 102233.18 | 40.96 | 4.302 | 10.778 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 10.778 | 0.00 |
CORE_TOP | 28345.80 | 28345.80 | 11.36 | 1.196 | 1.196 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.000 | 0.135 | 00:10:00 | 15.60 | 22.13 | 0.00915 | 12.70 | 0.00915 | 0.135 | 0.00 | |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 0.00 | 0.000 | 0.087 | 00:10:00 | 15.60 | 21.86 | 0.00915 | 12.70 | 0.00915 | 0.087 | 0.00 | |
PERIMETER_BOT_ZN_1 | 224.66 | 224.66 | 0.72 | 0.010 | 0.135 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00910 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 0.00 | 0.000 | 0.087 | 00:10:00 | 15.60 | 22.72 | 0.00915 | 12.70 | 0.00915 | 0.087 | 0.00 | |
PERIMETER_MID_ZN_3 | 56002.37 | 56002.37 | 178.69 | 2.375 | 2.375 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00834 | 12.70 | 0.00915 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 37391.74 | 37391.74 | 185.13 | 1.586 | 1.586 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00834 | 12.70 | 0.00915 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 55645.96 | 55645.96 | 177.54 | 2.360 | 2.360 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00834 | 12.70 | 0.00915 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 28981.85 | 28981.85 | 143.49 | 1.227 | 1.227 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00843 | 12.70 | 0.00915 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 8474.30 | 8474.30 | 27.04 | 0.360 | 0.360 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00822 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 5586.11 | 5586.11 | 27.66 | 0.238 | 0.238 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00822 | 12.70 | 0.00915 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 8434.03 | 8434.03 | 26.91 | 0.359 | 0.359 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00822 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 4820.60 | 4820.60 | 23.87 | 0.205 | 0.205 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00828 | 12.70 | 0.00915 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 12.70 | 0.00915 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 25.69 | 0.00700 | 12.70 | 0.00915 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.92 | 0.00799 | 12.70 | 0.00915 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 12.70 | 0.00915 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.38 | 9.38 | 1.52 | 1.52 | 9.3828 | 2.8356 | 9.3828 | 0.3022 | 0.3000 |
VAV_MID WITH REHEAT | 89.10 | 89.10 | 18.33 | 18.33 | 89.1030 | 27.7888 | 89.1030 | 0.3119 | 0.3000 |
VAV_TOP WITH REHEAT | 10.48 | 10.48 | 2.36 | 2.36 | 10.4783 | 2.9833 | 10.4783 | 0.2847 | 0.3000 |
CAV_BAS | 5.42 | 5.42 | 1.20 | 1.20 | 5.4160 | 5.4160 | 5.4160 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.47 | 0.47 | 0.02 | 0.02 | 0.4676 | 0.4676 | 0.4676 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.45 | 4.45 | 0.16 | 0.16 | 4.4509 | 4.4509 | 4.4509 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.45 | 0.45 | 0.02 | 0.02 | 0.4494 | 0.4494 | 0.4494 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19271.559 | 19271.559 | 1.914896 | 0.00016860 | 388.499 | 1/21 00:10:00 | 1/21 00:10:00 | 19271.56 | 19271.56 | 1.914896 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 19342.62 | 19342.62 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 292080.010 | 292080.010 | 18.863912 | 0.00255524 | 6218.232 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 292080.01 | 292080.01 | 18.863912 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 102233.18 | 0.00 | 293108.34 | 293108.34 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 48241.075 | 48241.075 | 1.976871 | 0.00042203 | 1133.685 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 48241.08 | 48241.08 | 1.976871 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 28345.80 | 0.00 | 48399.18 | 48399.18 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 2422.290 | 2422.290 | 0.240688 | 0.00002119 | 48.831 | 1/21 00:10:00 | 1/21 00:10:00 | 2422.29 | 2422.29 | 0.240688 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 2431.22 | 2431.22 | ||
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 1861.108 | 1861.108 | 0.184927 | 0.00001628 | 37.518 | 1/21 00:10:00 | 1/21 00:10:00 | 1861.11 | 1861.11 | 0.184927 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 1867.97 | 1867.97 | ||
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 2761.529 | 2761.529 | 0.251569 | 0.00002416 | 56.171 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2761.53 | 2761.53 | 0.251569 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00909601 | 58.6725 | 224.66 | 0.00 | 2771.66 | 2771.66 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 2450.709 | 2450.709 | 0.243512 | 0.00002144 | 49.404 | 1/21 00:10:00 | 1/21 00:10:00 | 2450.71 | 2450.71 | 0.243512 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 2459.75 | 2459.75 | ||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 79921.312 | 79921.312 | 2.375018 | 0.00069919 | 2111.791 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 79921.31 | 79921.31 | 2.375018 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00834097 | 53.8648 | 56002.37 | 0.00 | 80212.62 | 80212.62 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 56976.370 | 56976.370 | 1.944658 | 0.00049845 | 1421.631 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 56976.37 | 56976.37 | 1.944658 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00833634 | 53.8352 | 37391.74 | 0.00 | 57154.18 | 57154.18 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 80751.946 | 80751.946 | 2.492873 | 0.00070645 | 2097.935 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 80751.95 | 80751.95 | 2.492873 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00834336 | 53.8800 | 55645.96 | 0.00 | 80999.18 | 80999.18 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 50258.734 | 50258.734 | 2.112332 | 0.00043969 | 1172.669 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 50258.73 | 50258.73 | 2.112332 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00842877 | 54.4241 | 28981.85 | 0.00 | 50424.11 | 50424.11 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 12103.702 | 12103.702 | 0.360461 | 0.00010589 | 319.504 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12103.70 | 12103.70 | 0.360461 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00821872 | 53.0857 | 8474.30 | 0.00 | 12145.55 | 12145.55 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 7978.828 | 7978.828 | 0.237639 | 0.00006980 | 210.610 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7978.83 | 7978.83 | 0.237639 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00821587 | 53.0676 | 5586.11 | 0.00 | 8006.36 | 8006.36 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 12046.109 | 12046.109 | 0.358739 | 0.00010538 | 317.987 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12046.11 | 12046.11 | 0.358739 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00822086 | 53.0994 | 8434.03 | 0.00 | 12087.78 | 12087.78 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 7235.497 | 7235.497 | 0.239811 | 0.00006330 | 182.565 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7235.50 | 7235.50 | 0.239811 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00827916 | 53.4707 | 4820.60 | 0.00 | 7257.94 | 7257.94 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 246412.430 | -999.000 | 9.382848 | 0.01048295 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 246412.43 | 212219.16 | 9.382848 | 29.18 | 18.01 | 0.00831292 | 11.04 | 9.78 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 27.0514 | 24.00 | 0.00737336 | 39.7468 | 126325.05 | 0.00 | 246703.67 | 221641.37 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 2938.714 | 2938.714 | 2.814854 | 0.00002571 | 53.627 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 2938.71 | 2938.71 | 2.814854 | 11.94 | 11.94 | 0.00915315 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 90.1713 | 22.48 | 0.00914653 | 53.8923 | 0.00 | 0.00 | 3333.59 | 3333.59 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2423888.112 | -999.000 | 89.102996 | 0.10311780 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 2423888.11 | 2064866.66 | 89.102996 | 29.61 | 18.26 | 0.00844632 | 11.04 | 9.78 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 28.4861 | 24.00 | 0.00745168 | 40.1646 | 1165851.66 | 0.00 | 2426866.16 | 2153193.60 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 0.000 | 0.000 | 26.730899 | 0.00000000 | 1.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 26.730899 | 13.11 | 12.82 | 0.00910262 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 94.9536 | 21.00 | 0.00822611 | 53.1334 | 280255.09 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 263669.408 | -999.000 | 10.478327 | 0.01121711 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 263669.41 | 228709.87 | 10.478327 | 28.56 | 17.72 | 0.00820814 | 11.05 | 9.78 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 24.2232 | 24.00 | 0.00738419 | 39.8052 | 143587.49 | 0.00 | 263968.92 | 239358.27 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 0.000 | 0.000 | 3.143498 | 0.00000000 | 1.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 3.143498 | 14.28 | 13.14 | 0.00895312 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 80.7441 | 21.00 | 0.00811308 | 52.4131 | 55660.85 | 0.00 | 0.00 | 0.00 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 131447.314 | -999.000 | 5.416018 | 0.00559207 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 131447.31 | 112584.83 | 5.416018 | 28.00 | 17.59 | 0.00828753 | 11.42 | 9.94 | 0.00700000 | 40.57 | 0.01077797 | 23.25 | 22.1600 | 24.00 | 0.00749451 | 40.3920 | 68175.98 | 0.00 | 131604.39 | 118755.93 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 243579.713 | 243579.713 | 5.416018 | 0.00213094 | 5631.257 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 243579.71 | 243579.71 | 5.416018 | 2.81 | 2.81 | 0.00747725 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 22.1600 | 26.70 | 0.00700005 | 32.1545 | 0.00 | 0.00 | 213726.10 | 213726.10 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9608.953 | 6180.900 | 0.467581 | 0.00023532 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 8661.27 | 8522.73 | -999.0 | 28.15 | 16.67 | 0.00712589 | 12.80 | 10.55 | 0.00700000 | 33.16 | 0.01076533 | 21.14 | -999.0000 | 27.00 | 0.00700000 | 31.5922 | 8085.88 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 91593.935 | 58875.089 | 4.450890 | 0.00224313 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 82581.62 | 81195.88 | -999.0 | 28.16 | 16.68 | 0.00713225 | 12.80 | 10.55 | 0.00700000 | 33.16 | 0.01076533 | 21.14 | -999.0000 | 27.00 | 0.00700000 | 31.5922 | 77075.91 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9498.278 | 6024.954 | 0.449400 | 0.00023261 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 8607.47 | 8372.51 | -999.0 | 28.47 | 16.86 | 0.00722080 | 12.80 | 10.55 | 0.00700000 | 41.96 | 0.01078037 | 23.63 | -999.0000 | 27.00 | 0.00709249 | 32.0080 | 7815.08 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9608.953 | 9608.953 | 0.467581 | 0.00023532 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9608.95 | 9608.95 | 0.467581 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.3433 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 91593.935 | 91593.935 | 4.450890 | 0.00224313 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 91593.94 | 91593.94 | 4.450890 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.5123 | 25.69 | 0.00700011 | 34.1287 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9498.278 | 9498.278 | 0.449400 | 0.00023261 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9498.28 | 9498.28 | 0.449400 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.4786 | 24.92 | 0.00798500 | 40.6972 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 516.160 | 516.160 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 516.16 | 516.16 | 0.467581 | 0.42 | 0.42 | 0.00707200 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.3433 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 5161.602 | 5161.602 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 5161.60 | 5161.60 | 4.450890 | 0.45 | 0.45 | 0.00707574 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.5123 | 25.69 | 0.00700011 | 34.1287 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 516.160 | 516.160 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 516.16 | 516.16 | 0.449400 | 0.44 | 0.44 | 0.00802565 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.4786 | 24.92 | 0.00798500 | 40.6972 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19271.559 | 19271.559 | 1.914896 | 0.00016860 | 388.499 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 2.0470 | 2.088199 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 19271.56 | 19271.56 | 1.0000 | 2.30475960 | 1.914896 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.16857880 | 60.00 | 32.22 | 27.78 | 0.000 | 19271.56 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 19342.62 | 19342.62 | 2.30475960 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 292080.010 | 292080.010 | 18.863912 | 0.00255524 | 6218.232 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 31.0244 | 31.648780 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 292080.01 | 292080.01 | 1.0000 | 22.70450998 | 18.863912 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 2.55498268 | 60.00 | 32.22 | 27.78 | 0.000 | 292080.01 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.73 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 102233.18 | 0.00 | 293108.34 | 293108.34 | 22.70450998 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 25.46 | 16.48 | 0.00800000 | 45969.5 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 48241.075 | 48241.075 | 1.976871 | 0.00042203 | 1133.685 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 5.1241 | 5.227236 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 48241.08 | 48241.08 | 1.0000 | 2.37935194 | 1.976871 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.42199092 | 60.00 | 32.22 | 27.78 | 0.000 | 48241.08 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 28345.80 | 0.00 | 48399.18 | 48399.18 | 2.37935194 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.75 | 18.94 | 0.00800000 | 53401.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2422.290 | 2422.290 | 0.240688 | 0.00002119 | 48.831 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 0.2573 | 0.262471 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 2422.29 | 2422.29 | 1.0000 | 0.28969093 | 0.240688 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.02118909 | 60.00 | 32.22 | 27.78 | 0.000 | 2422.29 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 2431.22 | 2431.22 | 0.28969093 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1861.108 | 1861.108 | 0.184927 | 0.00001628 | 37.518 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 0.1977 | 0.201663 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 1861.11 | 1861.11 | 1.0000 | 0.22257703 | 0.184927 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01628012 | 60.00 | 32.22 | 27.78 | 0.000 | 1861.11 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 1867.97 | 1867.97 | 0.22257703 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2761.529 | 2761.529 | 0.251569 | 0.00002416 | 56.171 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 0.2933 | 0.299230 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2761.53 | 2761.53 | 1.0000 | 0.30278726 | 0.251569 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.02415660 | 60.00 | 32.22 | 27.78 | 0.000 | 2761.53 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.99 | 0.00909601 | 21.00 | 0.00909601 | 58.6725 | 224.66 | 0.00 | 2771.66 | 2771.66 | 0.30278726 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.78 | 15.14 | 0.00800000 | 42213.7 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2450.709 | 2450.709 | 0.243512 | 0.00002144 | 49.404 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 0.2603 | 0.265550 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 2450.71 | 2450.71 | 1.0000 | 0.29308972 | 0.243512 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.02143769 | 60.00 | 32.22 | 27.78 | 0.000 | 2450.71 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 2459.75 | 2459.75 | 0.29308972 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 79921.312 | 79921.312 | 2.375018 | 0.00069919 | 2111.791 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 8.4891 | 8.659997 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 79921.31 | 79921.31 | 1.0000 | 2.85855962 | 2.375018 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.69911518 | 60.00 | 32.22 | 27.78 | 0.000 | 79921.31 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00834097 | 21.00 | 0.00834097 | 53.8648 | 56002.37 | 0.00 | 80212.62 | 80212.62 | 2.85855962 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.32 | 21.28 | 0.00800000 | 61120.3 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 56976.370 | 56976.370 | 1.944658 | 0.00049845 | 1421.631 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 6.0520 | 6.173762 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 56976.37 | 56976.37 | 1.0000 | 2.34058104 | 1.944658 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.49840329 | 60.00 | 32.22 | 27.78 | 0.000 | 56976.37 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00833634 | 21.00 | 0.00833634 | 53.8352 | 37391.74 | 0.00 | 57154.18 | 57154.18 | 2.34058104 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 36.75 | 20.20 | 0.00800000 | 57478.6 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 80751.946 | 80751.946 | 2.492873 | 0.00070645 | 2097.935 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 8.5774 | 8.750002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 80751.95 | 80751.95 | 1.0000 | 3.00040958 | 2.492873 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.70638118 | 60.00 | 32.22 | 27.78 | 0.000 | 80751.95 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00834336 | 21.00 | 0.00834336 | 53.8800 | 55645.96 | 0.00 | 80999.18 | 80999.18 | 3.00040958 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.27 | 20.97 | 0.00800000 | 60055.9 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 50258.734 | 50258.734 | 2.112332 | 0.00043969 | 1172.669 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 5.3384 | 5.445863 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 50258.73 | 50258.73 | 1.0000 | 2.54239245 | 2.112332 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.43964048 | 60.00 | 32.22 | 27.78 | 0.000 | 50258.73 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00842877 | 21.00 | 0.00842877 | 54.4241 | 28981.85 | 0.00 | 50424.11 | 50424.11 | 2.54239245 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.25 | 18.78 | 0.00800000 | 52893.2 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12103.702 | 12103.702 | 0.360461 | 0.00010589 | 319.504 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 1.2856 | 1.311515 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12103.70 | 12103.70 | 1.0000 | 0.43384931 | 0.360461 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.10587766 | 60.00 | 32.22 | 27.78 | 0.000 | 12103.70 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00821872 | 21.00 | 0.00821872 | 53.0857 | 8474.30 | 0.00 | 12145.55 | 12145.55 | 0.43384931 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.26 | 0.00800000 | 61054.7 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7978.828 | 7978.828 | 0.237639 | 0.00006980 | 210.610 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 0.8475 | 0.864558 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7978.83 | 7978.83 | 1.0000 | 0.28602116 | 0.237639 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.06979515 | 60.00 | 32.22 | 27.78 | 0.000 | 7978.83 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00821587 | 21.00 | 0.00821587 | 53.0676 | 5586.11 | 0.00 | 8006.36 | 8006.36 | 0.28602116 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.26 | 0.00800000 | 61052.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12046.109 | 12046.109 | 0.358739 | 0.00010538 | 317.987 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 1.2795 | 1.305275 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12046.11 | 12046.11 | 1.0000 | 0.43177671 | 0.358739 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.10537386 | 60.00 | 32.22 | 27.78 | 0.000 | 12046.11 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00822086 | 21.00 | 0.00822086 | 53.0994 | 8434.03 | 0.00 | 12087.78 | 12087.78 | 0.43177671 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.26 | 0.00800000 | 61055.3 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7235.497 | 7235.497 | 0.239811 | 0.00006330 | 182.565 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 0.7685 | 0.784013 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7235.50 | 7235.50 | 1.0000 | 0.28863561 | 0.239811 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.06329283 | 60.00 | 32.22 | 27.78 | 0.000 | 7235.50 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00827916 | 21.00 | 0.00827916 | 53.4707 | 4820.60 | 0.00 | 7257.94 | 7257.94 | 0.28863561 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.46 | 20.42 | 0.00800000 | 58205.5 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 246412.430 | -999.000 | 9.382848 | 0.01048295 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2933 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.382848 | 11.29314864 | 4197.9300 | 999.8980 | 130.39663357 | 12.27 | 6.67 | 5.60 | 3065417.26 | 8.0385 | 8.038463 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 246412.43 | 212219.16 | 1.0000 | 11.29314864 | 9.382848 | 29.18 | 18.01 | 0.00831292 | 50563.6 | 11.04 | 9.78 | 0.00700000 | 28744.0 | 10.48188505 | 6.67 | 12.27 | 5.60 | 20275.835 | 226136.60 | 42.80 | 0.01078182 | 23.86 | 2.53819000 | 27.0514 | 24.00 | 0.00737336 | 24.00 | 0.00737336 | 39.7468 | 126325.05 | 0.00 | 246703.67 | 221641.37 | 11.29314864 | 29.18 | 18.02 | 0.00831292 | 50563.6 | 9.95 | 9.76 | 0.00743206 | 28718.2 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 2938.714 | 2938.714 | 2.814854 | 0.00002571 | 53.627 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.382848 | 11.29314864 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 0.3121 | 0.318429 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 2938.71 | 2938.71 | 1.0000 | 3.38794459 | 2.814854 | 11.94 | 11.94 | 0.00915315 | 35089.1 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.02570653 | 60.00 | 32.22 | 27.78 | 0.000 | 2938.71 | 12.70 | 0.00915345 | 12.70 | 2.53819000 | 90.1713 | 4.93 | 0.00915037 | 22.48 | 0.00914653 | 53.8923 | 0.00 | 0.00 | 3333.59 | 3333.59 | 3.38794459 | 2.80 | 2.80 | 0.00915315 | 25752.7 | 3.76 | 3.76 | 0.00915315 | 26736.6 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2423888.112 | -999.000 | 89.102996 | 0.10311780 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5413 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 89.102996 | 107.24391913 | 4197.9300 | 999.8980 | 130.39663357 | 12.27 | 6.67 | 5.60 | 3065417.26 | 79.0720 | 79.072045 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 2423888.11 | 2064866.66 | 1.0000 | 107.24391913 | 89.102996 | 29.61 | 18.26 | 0.00844632 | 51346.1 | 11.04 | 9.78 | 0.00700000 | 28744.4 | 103.10728449 | 6.67 | 12.27 | 5.60 | 192546.830 | 2231341.28 | 42.80 | 0.01078182 | 23.86 | 25.38195000 | 28.4861 | 24.00 | 0.00745168 | 24.00 | 0.00745168 | 40.1646 | 1165851.66 | 0.00 | 2426866.16 | 2153193.60 | 107.24391913 | 29.61 | 18.27 | 0.00844632 | 51346.1 | 9.94 | 9.76 | 0.00743344 | 28716.6 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 0.000 | 0.000 | 26.730899 | 0.00000000 | 1.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 89.102996 | 107.24391913 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 0.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 32.17317574 | 26.730899 | 13.11 | 12.82 | 0.00910262 | 36158.5 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.00000000 | 60.00 | 32.22 | 27.78 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 25.38195000 | 94.9536 | 20.79 | 0.00814621 | 21.00 | 0.00822611 | 53.1334 | 280255.09 | 0.00 | 0.00 | 0.00 | 32.17317574 | 2.80 | 2.80 | 0.00910262 | 25626.0 | 2.80 | 2.80 | 0.00910262 | 25626.0 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 263669.408 | -999.000 | 10.478327 | 0.01121711 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0985 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.478327 | 12.61166216 | 4197.9300 | 999.8980 | 130.39663357 | 12.27 | 6.67 | 5.60 | 3065417.26 | 8.6014 | 8.601420 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 263669.41 | 228709.87 | 1.0000 | 12.61166216 | 10.478327 | 28.56 | 17.72 | 0.00820814 | 49659.9 | 11.05 | 9.78 | 0.00700000 | 28753.2 | 11.21596186 | 6.67 | 12.27 | 5.60 | 22522.793 | 241146.61 | 42.80 | 0.01078182 | 23.86 | 2.53819000 | 24.2232 | 24.00 | 0.00738419 | 24.00 | 0.00738419 | 39.8052 | 143587.49 | 0.00 | 263968.92 | 239358.27 | 12.61166216 | 28.56 | 17.72 | 0.00820814 | 49659.9 | 9.95 | 9.77 | 0.00743360 | 28729.4 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 0.000 | 0.000 | 3.143498 | 0.00000000 | 1.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.478327 | 12.61166216 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 0.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 3.78349865 | 3.143498 | 14.28 | 13.14 | 0.00895312 | 36975.3 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.00000000 | 60.00 | 32.22 | 27.78 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 2.53819000 | 80.7441 | 20.89 | 0.00811308 | 21.00 | 0.00811308 | 52.4131 | 55660.85 | 0.00 | 0.00 | 0.00 | 3.78349865 | 2.80 | 2.80 | 0.00895312 | 25251.4 | 2.80 | 2.80 | 0.00895312 | 25251.4 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 131447.314 | -999.000 | 5.416018 | 0.00559207 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2461 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 5.416018 | 6.51869214 | 4197.9300 | 999.8980 | 130.39663357 | 12.27 | 6.67 | 5.60 | 3065417.26 | 4.2881 | 4.288072 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 131447.31 | 112584.83 | 1.0000 | 6.51869214 | 5.416018 | 28.00 | 17.59 | 0.00828753 | 49294.3 | 11.42 | 9.94 | 0.00700000 | 29129.6 | 5.59150216 | 6.67 | 12.27 | 5.60 | 9183.695 | 122263.62 | 40.57 | 0.01077797 | 23.25 | 1.20019084 | 22.1600 | 24.00 | 0.00749451 | 24.00 | 0.00749451 | 40.3920 | 68175.98 | 0.00 | 131604.39 | 118755.93 | 6.51869214 | 28.00 | 17.60 | 0.00828753 | 49294.3 | 10.14 | 9.93 | 0.00750531 | 29105.5 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 243579.713 | 243579.713 | 5.416018 | 0.00213094 | 5631.257 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 5.416018 | 6.51869214 | 4197.9300 | 999.8980 | 8.07292628 | 54.44 | 82.22 | 27.78 | 941452.52 | 25.8728 | 26.393456 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 243579.71 | 243579.71 | 1.0000 | 6.51869214 | 5.416018 | 2.81 | 2.81 | 0.00747725 | 21567.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 2.13072421 | 60.00 | 32.22 | 27.78 | 0.000 | 243579.71 | 12.70 | 0.00915345 | 12.70 | 1.20019084 | 22.1600 | 0.00 | 0.00700005 | 26.70 | 0.00700005 | 32.1545 | 0.00 | 0.00 | 213726.10 | 213726.10 | 6.51869214 | 12.80 | 11.06 | 0.00747725 | 31740.0 | 44.98 | 22.26 | 0.00747725 | 64526.7 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9608.953 | 6180.900 | 0.467581 | 0.00023532 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0867 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 06:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | Sensible | 8661.27 | 8522.73 | 0.9014 | -999.0 | -999.0 | 28.15 | 16.67 | 0.00712589 | 46484.0 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8661.27 | 33.16 | 0.01076533 | 21.14 | 0.01563279 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 8085.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 91593.935 | 58875.089 | 4.450890 | 0.00224313 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0985 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 06:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | Sensible | 82581.62 | 81195.88 | 0.9016 | -999.0 | -999.0 | 28.16 | 16.68 | 0.00713225 | 46510.9 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 82581.62 | 33.16 | 0.01076533 | 21.14 | 0.15632792 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 77075.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9498.278 | 6024.954 | 0.449400 | 0.00023261 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.2631 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | Sensible | 8607.47 | 8372.51 | 0.9062 | -999.0 | -999.0 | 28.47 | 16.86 | 0.00722080 | 47045.8 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8607.47 | 41.96 | 0.01078037 | 23.63 | 0.01563279 | -999.0000 | 27.00 | 0.00709249 | 27.00 | 0.00709249 | 32.0080 | 7815.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9608.953 | 9608.953 | 0.467581 | 0.00023532 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9608.95 | 9608.95 | 1.0000 | 0.56277794 | 0.467581 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9608.95 | 12.70 | 0.00915345 | 12.70 | 0.01563279 | 3.3433 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 91593.935 | 91593.935 | 4.450890 | 0.00224313 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 91593.94 | 91593.94 | 1.0000 | 5.35706928 | 4.450890 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 91593.94 | 12.70 | 0.00915345 | 12.70 | 0.15632792 | 3.5123 | 0.00 | 0.00700011 | 25.69 | 0.00700011 | 34.1287 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9498.278 | 9498.278 | 0.449400 | 0.00023261 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9498.28 | 9498.28 | 1.0000 | 0.54089566 | 0.449400 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9498.28 | 12.70 | 0.00915345 | 12.70 | 0.01563279 | 3.4786 | 0.00 | 0.00798500 | 24.92 | 0.00798500 | 40.6972 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 516.160 | 516.160 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.467581 | 0.56277794 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 516.16 | 516.16 | 1.0000 | 0.56277794 | 0.467581 | 0.42 | 0.42 | 0.00707200 | 18118.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 516.16 | 12.70 | 0.00915345 | 12.70 | 0.01563279 | 3.3433 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5161.602 | 5161.602 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.450890 | 5.35706928 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 5161.60 | 5161.60 | 1.0000 | 5.35706928 | 4.450890 | 0.45 | 0.45 | 0.00707574 | 18150.1 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5161.60 | 12.70 | 0.00915345 | 12.70 | 0.15632792 | 3.5123 | 0.00 | 0.00700011 | 25.69 | 0.00700011 | 34.1287 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 516.160 | 516.160 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.449400 | 0.54089566 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 516.16 | 516.16 | 1.0000 | 0.54089566 | 0.449400 | 0.44 | 0.44 | 0.00802565 | 20522.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 516.16 | 12.70 | 0.00915345 | 12.70 | 0.01563279 | 3.4786 | 0.00 | 0.00798500 | 24.92 | 0.00798500 | 40.6972 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5730.17 | 1750.67 | 1750.67 |
CORE_BOTTOM | 5730.83 | 1.00 | 0.00 |
CORE_MID | 5278.33 | 89.50 | 0.00 |
CORE_TOP | 4942.83 | 481.17 | 13.33 |
PERIMETER_BOT_ZN_3 | 5488.00 | 317.33 | 226.33 |
PERIMETER_BOT_ZN_2 | 5441.50 | 431.83 | 286.50 |
PERIMETER_BOT_ZN_1 | 5671.00 | 416.17 | 356.33 |
PERIMETER_BOT_ZN_4 | 5841.00 | 755.00 | 744.33 |
PERIMETER_MID_ZN_3 | 4870.33 | 929.00 | 370.83 |
PERIMETER_MID_ZN_2 | 4253.17 | 830.83 | 438.00 |
PERIMETER_MID_ZN_1 | 5483.17 | 671.00 | 487.67 |
PERIMETER_MID_ZN_4 | 5234.00 | 830.00 | 478.33 |
PERIMETER_TOP_ZN_3 | 4588.17 | 1391.67 | 435.67 |
PERIMETER_TOP_ZN_2 | 4856.83 | 1225.50 | 505.50 |
PERIMETER_TOP_ZN_1 | 5201.50 | 968.33 | 535.17 |
PERIMETER_TOP_ZN_4 | 4908.00 | 1215.83 | 528.00 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1038.17 | 1038.17 |
DATACENTER_MID_ZN_6 | 5943.00 | 393.83 | 393.83 |
DATACENTER_TOP_ZN_6 | 5943.00 | 493.83 | 493.83 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 120.67 | 0.00 | 7.00 |
CORE_BOTTOM | 0.00 | 2.33 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 92.00 | 0.00 | 39.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 95.83 | 0.00 | 62.83 |
PERIMETER_BOT_ZN_1 | 0.00 | 131.33 | 0.00 | 73.33 |
PERIMETER_BOT_ZN_4 | 0.00 | 386.33 | 0.00 | 125.33 |
PERIMETER_MID_ZN_3 | 0.00 | 77.17 | 0.00 | 38.00 |
PERIMETER_MID_ZN_2 | 0.00 | 109.67 | 0.00 | 70.00 |
PERIMETER_MID_ZN_1 | 0.00 | 112.83 | 0.00 | 67.50 |
PERIMETER_MID_ZN_4 | 0.00 | 145.67 | 0.00 | 56.17 |
PERIMETER_TOP_ZN_3 | 0.00 | 128.50 | 0.00 | 54.50 |
PERIMETER_TOP_ZN_2 | 0.00 | 156.83 | 0.00 | 79.17 |
PERIMETER_TOP_ZN_1 | 0.00 | 152.33 | 0.00 | 76.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 178.17 | 0.00 | 67.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 484.83 | 0.00 | 381.83 |
DATACENTER_MID_ZN_6 | 0.00 | 467.17 | 0.00 | 387.17 |
DATACENTER_TOP_ZN_6 | 0.00 | 322.67 | 0.00 | 283.50 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 1134.83 | 0.00 | 619.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.535 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.480 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.458 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.451 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.644 | 0.037 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.726 | 0.038 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.759 | 0.037 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 1.104 | 0.038 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.668 | 0.087 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.801 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.823 | 0.087 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.907 | 0.090 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.663 | 0.108 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.828 | 0.112 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.809 | 0.108 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.889 | 0.112 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.576 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.576 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.576 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 60.99 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 0.847 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.86 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.011 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.79 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.110 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.011 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 783.68 | 0.239 | ||
Total Facility | 1010.73 | 2493.19 | 126016.35 | 46320.38 | 1.3878 | 157.549 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 24189427.79 | 0.00 | 24189427.79 | 0.00 | 24189427.79 | 29876159.83 | 3161.49 | 504.00 | 5094.51 | 788.26 |
CORE_BOTTOM | 24591852.61 | 0.00 | 24591852.61 | 0.00 | 24591852.61 | 33990283.35 | 8110.77 | 81.98 | 567.26 | 1520.75 |
CORE_MID | 0.21E+09 | 0.00 | 0.21E+09 | 0.00 | 0.21E+09 | 0.34E+09 | 8250.50 | 70.16 | 439.34 | 880.58 |
CORE_TOP | 21077538.98 | 0.00 | 21077538.98 | 0.00 | 21077538.98 | 33990283.35 | 8453.38 | 59.47 | 247.15 | 905.47 |
PERIMETER_BOT_ZN_3 | 3927236.20 | 0.00 | 3927236.20 | 322129.40 | 4249365.60 | 4267819.30 | 5250.92 | 109.91 | 3399.18 | 1520.75 |
PERIMETER_BOT_ZN_2 | 2868439.60 | 0.00 | 2868439.60 | 214752.79 | 3083192.39 | 2750345.05 | 2461.23 | 92.98 | 6205.78 | 1520.75 |
PERIMETER_BOT_ZN_1 | 4529240.02 | 0.00 | 4529240.02 | 322129.40 | 4851369.42 | 4267912.63 | 2223.24 | 266.73 | 6270.03 | 1520.75 |
PERIMETER_BOT_ZN_4 | 4356716.25 | 0.00 | 4356716.25 | 214752.79 | 4571469.04 | 2750345.05 | 1870.85 | 0.25 | 6888.90 | 1520.75 |
PERIMETER_MID_ZN_3 | 37344760.80 | 0.00 | 37344760.80 | 755463.31 | 38100224.11 | 42678193.03 | 5464.35 | 125.25 | 3170.40 | 880.58 |
PERIMETER_MID_ZN_2 | 29991139.54 | 0.00 | 29991139.54 | 503641.86 | 30494781.41 | 27503450.52 | 2863.53 | 29.23 | 5867.23 | 1789.58 |
PERIMETER_MID_ZN_1 | 45303309.62 | 0.00 | 45303309.62 | 755463.31 | 46058772.93 | 42679126.28 | 2829.22 | 78.30 | 5852.49 | 880.58 |
PERIMETER_MID_ZN_4 | 32926104.16 | 0.00 | 32926104.16 | 503641.86 | 33429746.02 | 27503450.52 | 2773.78 | 18.08 | 5968.14 | 880.58 |
PERIMETER_TOP_ZN_3 | 3769182.29 | 0.00 | 3769182.29 | 937962.89 | 4707145.18 | 4267819.30 | 3339.13 | 107.00 | 5313.88 | 905.47 |
PERIMETER_TOP_ZN_2 | 3011466.95 | 0.00 | 3011466.95 | 625308.16 | 3636775.12 | 2750345.05 | 2731.06 | 14.06 | 6014.89 | 905.47 |
PERIMETER_TOP_ZN_1 | 4531966.41 | 0.00 | 4531966.41 | 937962.89 | 5469929.30 | 4267912.63 | 2734.78 | 11.08 | 6014.14 | 905.47 |
PERIMETER_TOP_ZN_4 | 3279461.16 | 0.00 | 3279461.16 | 625308.16 | 3904769.32 | 2750345.05 | 2713.94 | 1.08 | 6044.99 | 905.47 |
DATACENTER_BOT_ZN_6 | 492995.74 | 0.00 | 492995.74 | 0.00 | 492995.74 | 389144.62 | 0.00 | 504.00 | 8256.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929957.41 | 0.00 | 4929957.41 | 0.00 | 4929957.41 | 3891446.16 | 0.00 | 504.00 | 8256.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492995.74 | 0.00 | 492995.74 | 0.00 | 492995.74 | 389144.62 | 0.00 | 504.00 | 8256.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8423799.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 0.37E+10 | 0.00 | 0.37E+10 | 29382409.93 | 0.38E+10 | 0.50E+10 | 8760.00 | 1343.27 | 8760.00 | 3726.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9714 | 0.0000 | 0.9714 | 0.0000 | 0.9714 | 0.9949 | 1132.75 | 504.00 | 4306.25 |
CORE_BOTTOM | 0.8826 | 0.0000 | 0.8826 | 0.0000 | 0.8826 | 1.0778 | 5304.97 | 81.60 | 556.43 |
CORE_MID | 8.4187 | 0.0000 | 8.4187 | 0.0000 | 8.4187 | 10.7782 | 5440.83 | 70.16 | 432.01 |
CORE_TOP | 0.8295 | 0.0000 | 0.8295 | 0.0000 | 0.8295 | 1.0778 | 5638.26 | 59.42 | 245.32 |
PERIMETER_BOT_ZN_3 | 0.1486 | 0.0000 | 0.1486 | 0.0086 | 0.1571 | 0.1353 | 2536.68 | 107.70 | 3298.63 |
PERIMETER_BOT_ZN_2 | 0.1079 | 0.0000 | 0.1079 | 0.0057 | 0.1136 | 0.0872 | 1151.52 | 91.08 | 4700.40 |
PERIMETER_BOT_ZN_1 | 0.1751 | 0.0000 | 0.1751 | 0.0086 | 0.1836 | 0.1353 | 862.40 | 124.75 | 4955.85 |
PERIMETER_BOT_ZN_4 | 0.1640 | 0.0000 | 0.1640 | 0.0057 | 0.1697 | 0.0872 | 573.96 | 0.21 | 5368.83 |
PERIMETER_MID_ZN_3 | 1.5389 | 0.0000 | 1.5389 | 0.0201 | 1.5590 | 1.3533 | 2731.11 | 121.25 | 3090.64 |
PERIMETER_MID_ZN_2 | 1.1897 | 0.0000 | 1.1897 | 0.0141 | 1.2038 | 0.8721 | 848.54 | 20.18 | 4165.28 |
PERIMETER_MID_ZN_1 | 1.8983 | 0.0000 | 1.8983 | 0.0201 | 1.9183 | 1.3533 | 883.44 | 56.33 | 5003.22 |
PERIMETER_MID_ZN_4 | 1.3473 | 0.0000 | 1.3473 | 0.0134 | 1.3607 | 0.8721 | 834.79 | 17.82 | 5090.40 |
PERIMETER_TOP_ZN_3 | 0.1529 | 0.0000 | 0.1529 | 0.0249 | 0.1778 | 0.1353 | 1421.17 | 101.53 | 4420.31 |
PERIMETER_TOP_ZN_2 | 0.1230 | 0.0000 | 0.1230 | 0.0166 | 0.1396 | 0.0872 | 817.99 | 14.06 | 5110.96 |
PERIMETER_TOP_ZN_1 | 0.1867 | 0.0000 | 0.1867 | 0.0249 | 0.2116 | 0.1353 | 822.28 | 10.92 | 5109.79 |
PERIMETER_TOP_ZN_4 | 0.1321 | 0.0000 | 0.1321 | 0.0166 | 0.1487 | 0.0872 | 802.33 | 1.08 | 5139.60 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0130 | 0.00 | 504.00 | 5439.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1296 | 0.00 | 504.00 | 5439.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0130 | 0.00 | 504.00 | 5439.00 |
DATACENTER_BASEMENT_ZN_6 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.2805 | 5943.00 | 0.00 | 0.00 |
Total Facility | 149.3972 | 0.0000 | 149.3972 | 0.7874 | 150.1847 | 157.9346 | 5943.00 | 1168.28 | 5943.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 58341827.94 | 0.00 | 58341827.94 | 48026705.38 | 1869.07 | 0.00 | 6890.93 | 1520.75 |
VAV_MID WITH REHEAT | 0.52E+09 | 0.00 | 0.52E+09 | 0.48E+09 | 2742.32 | 0.00 | 6017.68 | 880.58 |
VAV_TOP WITH REHEAT | 51672467.24 | 0.00 | 51672467.24 | 48026705.38 | 2711.59 | 0.00 | 6048.41 | 905.47 |
CAV_BAS | 35041793.95 | 0.00 | 35041793.95 | 29876159.83 | 3161.49 | 0.00 | 5598.51 | 788.26 |
AIRLOOP DATACENTER BOT | 714173.78 | 0.00 | 714173.78 | 389144.62 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 7141737.84 | 0.00 | 7141737.84 | 3891446.16 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 714173.78 | 0.00 | 714173.78 | 389144.62 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.1413 | 0.0000 | 2.1413 | 1.5229 | 572.82 | 0.00 | 5370.18 |
VAV_MID WITH REHEAT | 20.9179 | 0.0000 | 20.9179 | 15.2292 | 805.90 | 0.00 | 5137.10 |
VAV_TOP WITH REHEAT | 2.0630 | 0.0000 | 2.0630 | 1.5229 | 800.06 | 0.00 | 5142.94 |
CAV_BAS | 1.4073 | 0.0000 | 1.4073 | 0.9949 | 1132.75 | 0.00 | 4810.25 |
AIRLOOP DATACENTER BOT | 0.0226 | 0.0000 | 0.0226 | 0.0130 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2265 | 0.0000 | 0.2265 | 0.1296 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0226 | 0.0000 | 0.0226 | 0.0130 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6890.93 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6017.68 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6048.41 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 5598.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.3698 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 24.2000 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.3844 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7387 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2265 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 7 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1352 |
Defaulted Fields | 1168 |
Fields with Defaults | 3820 |
Autosized Fields | 314 |
Autosizable Fields | 391 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 28113.09 | 291814.38 | 21-JAN-04:00 | 1853330.76 | 10-AUG-16:00 |
Electricity:Building | 16922.31 | 217854.47 | 29-MAY-17:10 | 991311.80 | 15-DEC-17:00 |
Electricity:Zone:BASEMENT | 575.04 | 14188.35 | 01-JAN-00:10 | 26610.69 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16922.31 | 217854.47 | 29-MAY-17:10 | 991311.80 | 15-DEC-17:00 |
InteriorLights:Electricity | 2245.92 | 10571.13 | 01-JAN-11:00 | 215979.07 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 150.64 | 730.80 | 01-JAN-00:10 | 13153.15 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2245.92 | 10571.13 | 01-JAN-11:00 | 215979.07 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity | 2245.92 | 10571.13 | 01-JAN-11:00 | 215979.07 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 150.64 | 730.80 | 01-JAN-00:10 | 13153.15 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2245.92 | 10571.13 | 01-JAN-11:00 | 215979.07 | 15-MAR-07:10 |
Electricity:Zone:CORE_BOTTOM | 424.90 | 5109.54 | 01-JAN-00:10 | 29019.08 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 135.29 | 656.31 | 01-JAN-00:10 | 11812.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 135.29 | 656.31 | 01-JAN-00:10 | 11812.45 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4248.99 | 51095.28 | 01-JAN-00:10 | 290190.11 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1352.86 | 6563.11 | 01-JAN-00:10 | 118124.49 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1352.86 | 6563.11 | 01-JAN-00:10 | 118124.49 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 424.90 | 5109.53 | 01-JAN-00:10 | 29019.01 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 135.29 | 656.31 | 01-JAN-00:10 | 11812.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 135.29 | 656.31 | 01-JAN-00:10 | 11812.45 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 46.20 | 598.38 | 23-APR-17:10 | 3518.35 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.83 | 39.21 | 01-JAN-11:00 | 1357.79 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.83 | 39.21 | 01-JAN-11:00 | 1357.79 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 29.75 | 388.00 | 25-JUN-17:10 | 2257.85 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.31 | 25.27 | 01-JAN-08:00 | 865.51 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.31 | 25.27 | 01-JAN-08:00 | 865.51 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 46.06 | 598.39 | 30-APR-17:10 | 3515.91 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.69 | 39.21 | 01-JAN-08:10 | 1355.33 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.69 | 39.21 | 01-JAN-08:10 | 1355.33 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 29.75 | 385.62 | 12-MAR-17:10 | 2272.35 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.32 | 25.27 | 01-JAN-10:20 | 880.02 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.32 | 25.27 | 01-JAN-10:20 | 880.02 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 461.96 | 5983.80 | 23-APR-17:10 | 35210.28 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 98.31 | 392.09 | 01-JAN-10:40 | 13604.77 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 98.31 | 392.09 | 01-JAN-10:40 | 13604.77 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 297.48 | 3878.51 | 25-JUN-17:10 | 22583.90 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 63.12 | 252.68 | 01-JAN-08:00 | 8660.48 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 63.12 | 252.68 | 01-JAN-08:00 | 8660.48 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 460.60 | 5983.89 | 26-MAR-17:10 | 35186.79 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 96.94 | 392.10 | 01-JAN-08:10 | 13580.95 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 96.94 | 392.10 | 01-JAN-08:10 | 13580.95 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 297.52 | 3856.16 | 12-MAR-17:10 | 22724.97 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 63.17 | 252.68 | 01-JAN-10:20 | 8801.64 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 63.17 | 252.68 | 01-JAN-10:20 | 8801.64 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 46.20 | 598.38 | 23-APR-17:10 | 3520.89 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.83 | 39.21 | 01-JAN-10:40 | 1360.34 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.83 | 39.21 | 01-JAN-10:40 | 1360.34 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 29.75 | 387.85 | 25-JUN-17:10 | 2258.31 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.31 | 25.27 | 01-JAN-08:00 | 865.97 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.31 | 25.27 | 01-JAN-08:00 | 865.97 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 46.06 | 598.39 | 26-MAR-17:10 | 3518.54 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.69 | 39.21 | 01-JAN-08:10 | 1357.95 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.69 | 39.21 | 01-JAN-08:10 | 1357.95 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 29.75 | 385.62 | 12-MAR-17:10 | 2272.41 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.32 | 25.27 | 01-JAN-10:20 | 880.08 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.32 | 25.27 | 01-JAN-10:20 | 880.08 | 14-MAR-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7537.33 | 95114.19 | 01-JAN-00:10 | 383341.15 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 42.47 | 206.05 | 01-JAN-00:10 | 3708.62 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 42.47 | 206.05 | 01-JAN-00:10 | 3708.62 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1575.07 | 19661.97 | 01-JAN-00:10 | 81110.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 5451.96 | 1742.82 | 20-JAN-05:00 | 517357.89 | 03-AUG-14:00 |
HeatRejection:Electricity | 958.40 | 1006.34 | 20-JAN-07:00 | 53621.47 | 06-FEB-18:10 |
General:HeatRejection:Electricity | 958.40 | 1006.34 | 20-JAN-07:00 | 53621.47 | 06-FEB-18:10 |
Electricity:HVAC | 2061.69 | 10385.13 | 21-JAN-04:50 | 215377.54 | 16-AUG-12:10 |
ExteriorEquipment:Electricity | 3408.16 | 47143.53 | 01-JAN-00:10 | 192798.69 | 15-DEC-08:20 |
Transformer:ExteriorEquipment:Electricity | 54.57 | 979.82 | 01-JAN-00:10 | 3396.43 | 15-MAR-07:20 |
ElectricityPurchased:Facility | 28113.09 | 291814.38 | 21-JAN-04:00 | 1853330.76 | 10-AUG-16:00 |
ElectricityPurchased:Plant | 28113.09 | 291814.38 | 21-JAN-04:00 | 1853330.76 | 10-AUG-16:00 |
Cogeneration:ElectricityPurchased | 28113.09 | 291814.38 | 21-JAN-04:00 | 1853330.76 | 10-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 28113.09 | 291814.38 | 21-JAN-04:00 | 1853330.76 | 10-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 28113.09 | 291814.38 | 21-JAN-04:00 | 1853330.76 | 10-AUG-16:00 |
ElectricityNet:Plant | 28113.09 | 291814.38 | 21-JAN-04:00 | 1853330.76 | 10-AUG-16:00 |
Cogeneration:ElectricityNet | 28113.09 | 291814.38 | 21-JAN-04:00 | 1853330.76 | 10-AUG-16:00 |
General:Cogeneration:ElectricityNet | 28113.09 | 291814.38 | 21-JAN-04:00 | 1853330.76 | 10-AUG-16:00 |
Fans:Electricity | 1499.94 | 6012.60 | 01-JAN-00:10 | 178011.96 | 16-AUG-14:00 |
General:Fans:Electricity | 1499.94 | 6012.60 | 01-JAN-00:10 | 178011.96 | 16-AUG-14:00 |
ExteriorLights:Electricity | 323.55 | 0.00 | 01-JAN-07:10 | 37611.08 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 323.55 | 0.00 | 01-JAN-07:10 | 37611.08 | 01-JAN-06:10 |
ComputerHVAC:ExteriorEquipment:Electricity | 1498.97 | 18981.63 | 01-JAN-00:10 | 75926.52 | 31-MAR-23:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 3682.44 | 3351.79 | 20-JAN-05:00 | 427273.83 | 10-AUG-16:00 |
General:Cooling:Electricity | 3682.44 | 3351.79 | 20-JAN-05:00 | 427273.83 | 10-AUG-16:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 1318.30 | 684.61 | 01-JAN-04:50 | 69964.47 | 30-AUG-05:10 |
General:Pumps:Electricity | 1318.30 | 684.61 | 01-JAN-04:50 | 69964.47 | 30-AUG-05:10 |
WIRED_LTG_ELECTRICITY | 63.11 | 0.00 | 01-JAN-00:10 | 6069.01 | 15-MAR-07:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 525.03 | 5695.87 | 06-AUG-15:40 | 68021.15 | 12-JAN-12:30 |
NaturalGas:Plant | 525.03 | 5695.87 | 06-AUG-15:40 | 68021.15 | 12-JAN-12:30 |
Heating:NaturalGas | 0.01 | 0.00 | 01-JAN-00:10 | 1006.91 | 20-JAN-07:00 |
Boiler:Heating:NaturalGas | 0.01 | 0.00 | 01-JAN-00:10 | 1006.91 | 20-JAN-07:00 |
WaterSystems:NaturalGas | 525.01 | 5695.87 | 06-AUG-15:40 | 68021.15 | 12-JAN-12:30 |
Water Heater:WaterSystems:NaturalGas | 525.01 | 5695.87 | 06-AUG-15:40 | 68021.15 | 12-JAN-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 27052.60 | 18705.88 | 20-JAN-05:00 | 2891839.02 | 03-AUG-14:00 |
PlantLoopCoolingDemand:HVAC | 27052.60 | 18705.88 | 20-JAN-05:00 | 2891839.02 | 03-AUG-14:00 |
CoolingCoils:PlantLoopCoolingDemand | 27052.60 | 18705.88 | 20-JAN-05:00 | 2891839.02 | 03-AUG-14:00 |
DistrictCooling:Facility | 7230.09 | 88847.75 | 06-MAY-23:40 | 371732.63 | 07-AUG-14:00 |
DistrictCooling:HVAC | 7230.09 | 88847.75 | 06-MAY-23:40 | 371732.63 | 07-AUG-14:00 |
Cooling:DistrictCooling | 7230.09 | 88847.75 | 06-MAY-23:40 | 371732.63 | 07-AUG-14:00 |
General:Cooling:DistrictCooling | 7230.09 | 88847.75 | 06-MAY-23:40 | 371732.63 | 07-AUG-14:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 23288.59 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-12:00 |
Water:Plant | 23288.59 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-12:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 23288.59 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-12:00 |
MainsWater:Plant | 23288.59 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-12:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 21008.42 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-10:50 |
General:HeatRejection:Water | 21008.42 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-10:50 |
HeatRejection:MainsWater | 21008.42 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-10:50 |
General:HeatRejection:MainsWater | 21008.42 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-10:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 123717.95 | 117789.43 | 20-JAN-04:50 | 13167980.85 | 10-AUG-16:00 |
EnergyTransfer:Building | 22974.86 | 100232.10 | 21-JAN-18:20 | 1609548.66 | 16-AUG-14:00 |
EnergyTransfer:Zone:BASEMENT | 738.87 | 0.00 | 01-JAN-00:10 | 76364.40 | 13-NOV-06:20 |
Heating:EnergyTransfer | 13.09 | 0.00 | 01-JAN-00:10 | 23660.66 | 01-JUL-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 6.34 | 0.00 | 01-JAN-00:10 | 23660.66 | 01-JUL-16:10 |
General:Heating:EnergyTransfer | 13.09 | 0.00 | 01-JAN-00:10 | 23660.66 | 01-JUL-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 6.34 | 0.00 | 01-JAN-00:10 | 23660.66 | 01-JUL-16:10 |
Cooling:EnergyTransfer | 22961.77 | 100232.10 | 21-JAN-18:20 | 1609548.66 | 16-AUG-14:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 732.54 | 0.00 | 01-JAN-00:10 | 76364.40 | 13-NOV-06:20 |
General:Cooling:EnergyTransfer | 22961.77 | 100232.10 | 21-JAN-18:20 | 1609548.66 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 732.54 | 0.00 | 01-JAN-00:10 | 76364.40 | 13-NOV-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 755.93 | 0.00 | 01-JAN-00:10 | 53904.42 | 07-AUG-05:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 755.93 | 0.00 | 01-JAN-00:10 | 53904.42 | 07-AUG-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 755.93 | 0.00 | 01-JAN-00:10 | 53904.42 | 07-AUG-05:10 |
EnergyTransfer:Zone:CORE_MID | 5655.70 | 0.00 | 01-JAN-00:10 | 424643.03 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5655.70 | 0.00 | 01-JAN-00:10 | 424643.03 | 02-JAN-06:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5655.70 | 0.00 | 01-JAN-00:10 | 424643.03 | 02-JAN-06:10 |
EnergyTransfer:Zone:CORE_TOP | 610.05 | 0.00 | 01-JAN-00:10 | 49665.74 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 610.05 | 0.00 | 01-JAN-00:10 | 49665.74 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 610.05 | 0.00 | 01-JAN-00:10 | 49665.74 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 130.24 | 0.00 | 01-JAN-00:10 | 12193.60 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 130.24 | 0.00 | 01-JAN-00:10 | 12193.60 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 130.24 | 0.00 | 01-JAN-00:10 | 12193.60 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 94.37 | 0.00 | 01-JAN-00:10 | 10271.54 | 31-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 94.37 | 0.00 | 01-JAN-00:10 | 10271.54 | 31-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 94.37 | 0.00 | 01-JAN-00:10 | 10271.54 | 31-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 152.15 | 0.00 | 01-JAN-00:10 | 14167.52 | 10-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 152.15 | 0.00 | 01-JAN-00:10 | 14167.52 | 10-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 152.15 | 0.00 | 01-JAN-00:10 | 14167.52 | 10-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 142.98 | 0.00 | 01-JAN-00:10 | 13489.39 | 10-AUG-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 142.98 | 0.00 | 01-JAN-00:10 | 13489.39 | 10-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 142.98 | 0.00 | 01-JAN-00:10 | 13489.39 | 10-AUG-15:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1074.82 | 0.00 | 01-JAN-00:10 | 116406.66 | 21-JUL-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1074.82 | 0.00 | 01-JAN-00:10 | 116406.66 | 21-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1074.82 | 0.00 | 01-JAN-00:10 | 116406.66 | 21-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 861.40 | 0.00 | 01-JAN-00:10 | 103021.78 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 861.40 | 0.00 | 01-JAN-00:10 | 103021.78 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 861.40 | 0.00 | 01-JAN-00:10 | 103021.78 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1317.97 | 0.00 | 01-JAN-00:10 | 139005.71 | 19-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1317.97 | 0.00 | 01-JAN-00:10 | 139005.71 | 19-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1317.97 | 0.00 | 01-JAN-00:10 | 139005.71 | 19-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 939.27 | 0.00 | 01-JAN-00:10 | 108641.70 | 10-AUG-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 939.27 | 0.00 | 01-JAN-00:10 | 108641.70 | 10-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 939.27 | 0.00 | 01-JAN-00:10 | 108641.70 | 10-AUG-15:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 118.96 | 0.00 | 01-JAN-00:10 | 13565.78 | 21-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 10.07 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 10.07 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 118.96 | 0.00 | 01-JAN-00:10 | 13565.78 | 21-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 118.96 | 0.00 | 01-JAN-00:10 | 13565.78 | 21-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 95.27 | 0.00 | 01-JAN-00:10 | 11187.40 | 04-AUG-10:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 95.27 | 0.00 | 01-JAN-00:10 | 11187.40 | 04-AUG-10:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 95.27 | 0.00 | 01-JAN-00:10 | 11187.40 | 04-AUG-10:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 143.40 | 0.00 | 01-JAN-00:10 | 15207.82 | 05-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 143.40 | 0.00 | 01-JAN-00:10 | 15207.82 | 05-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 143.40 | 0.00 | 01-JAN-00:10 | 15207.82 | 05-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 102.29 | 0.00 | 01-JAN-00:10 | 12049.36 | 10-AUG-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 102.29 | 0.00 | 01-JAN-00:10 | 12049.36 | 10-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 102.29 | 0.00 | 01-JAN-00:10 | 12049.36 | 10-AUG-15:50 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 120.73 | 0.00 | 01-JAN-00:10 | 14048.81 | 07-AUG-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.70 | 0.00 | 01-JAN-00:10 | 2549.82 | 16-JAN-10:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.70 | 0.00 | 01-JAN-00:10 | 2549.82 | 16-JAN-10:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 120.03 | 0.00 | 01-JAN-00:10 | 14048.81 | 07-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 120.03 | 0.00 | 01-JAN-00:10 | 14048.81 | 07-AUG-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 933.10 | 0.00 | 01-JAN-00:10 | 91537.67 | 05-SEP-15:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.19 | 0.00 | 01-JAN-00:10 | 20304.20 | 19-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.19 | 0.00 | 01-JAN-00:10 | 20304.20 | 19-FEB-11:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 928.91 | 0.00 | 01-JAN-00:10 | 91537.67 | 05-SEP-15:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 928.91 | 0.00 | 01-JAN-00:10 | 91537.67 | 05-SEP-15:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 170.38 | 0.00 | 01-JAN-00:10 | 27746.18 | 21-JUL-12:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.86 | 0.00 | 01-JAN-00:10 | 5905.68 | 21-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.86 | 0.00 | 01-JAN-00:10 | 5905.68 | 21-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 168.52 | 0.00 | 01-JAN-00:10 | 27746.18 | 21-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 168.52 | 0.00 | 01-JAN-00:10 | 27746.18 | 21-JUL-12:10 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.68 | 1301.22 | 21-JAN-08:00 | 7669.20 | 23-APR-17:30 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.68 | 1301.22 | 21-JAN-08:00 | 7669.20 | 23-APR-17:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.68 | 1301.22 | 21-JAN-08:00 | 7669.20 | 23-APR-17:30 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1335.59 | 8907.10 | 21-JAN-08:00 | 72382.20 | 23-APR-17:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1335.59 | 8907.10 | 21-JAN-08:00 | 72382.20 | 23-APR-17:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1335.59 | 8907.10 | 21-JAN-08:00 | 72382.20 | 23-APR-17:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 133.15 | 327.68 | 21-JAN-08:00 | 7489.01 | 23-APR-17:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 133.15 | 327.68 | 21-JAN-08:00 | 7489.01 | 23-APR-17:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 133.15 | 327.68 | 21-JAN-08:00 | 7489.01 | 23-APR-17:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7205.54 | 88847.75 | 06-MAY-23:40 | 369063.54 | 07-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7205.54 | 88847.75 | 06-MAY-23:40 | 369063.54 | 07-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7205.54 | 88847.75 | 06-MAY-23:40 | 369063.54 | 07-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 265.50 | 0.00 | 01-JAN-00:10 | 35984.71 | 11-JAN-12:30 |
PlantLoopHeatingDemand:Plant | 265.45 | 0.00 | 01-JAN-00:10 | 35984.71 | 11-JAN-12:30 |
WaterSystems:PlantLoopHeatingDemand | 265.45 | 0.00 | 01-JAN-00:10 | 35984.71 | 11-JAN-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 265.45 | 0.00 | 01-JAN-00:10 | 35984.71 | 11-JAN-12:30 |
EnergyTransfer:HVAC | 26545.47 | 15354.09 | 20-JAN-05:00 | 2861166.44 | 03-AUG-14:00 |
HeatingCoils:EnergyTransfer | 0.05 | 0.00 | 01-JAN-00:10 | 2750.05 | 20-JAN-07:00 |
PlantLoopHeatingDemand:HVAC | 0.05 | 0.00 | 01-JAN-00:10 | 2750.05 | 20-JAN-07:00 |
HeatingCoils:PlantLoopHeatingDemand | 0.05 | 0.00 | 01-JAN-00:10 | 2750.05 | 20-JAN-07:00 |
CoolingCoils:EnergyTransfer | 26545.42 | 15354.09 | 20-JAN-05:00 | 2861166.44 | 03-AUG-14:00 |
DistrictHeating:Facility | 0.00 | 0.00 | 01-JAN-00:40 | 14.06 | 01-DEC-00:30 |
DistrictHeating:HVAC | 0.00 | 0.00 | 01-JAN-00:40 | 14.06 | 01-DEC-00:30 |
Heating:DistrictHeating | 0.00 | 0.00 | 01-JAN-00:40 | 14.06 | 01-DEC-00:30 |
General:Heating:DistrictHeating | 0.00 | 0.00 | 01-JAN-00:40 | 14.06 | 01-DEC-00:30 |
EnergyTransfer:Plant | 74197.62 | 0.00 | 01-JAN-00:10 | 8705257.03 | 10-AUG-16:00 |
LoopToLoop:EnergyTransfer | 25441.74 | 0.00 | 01-JAN-00:10 | 2758952.17 | 03-AUG-14:00 |
WaterSystems:EnergyTransfer | 265.45 | 0.00 | 01-JAN-00:10 | 35984.71 | 11-JAN-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 265.45 | 0.00 | 01-JAN-00:10 | 35984.71 | 11-JAN-12:30 |
Boilers:EnergyTransfer | 0.01 | 0.00 | 01-JAN-00:10 | 636.64 | 20-JAN-07:00 |
Chillers:EnergyTransfer | 22657.58 | 0.00 | 01-JAN-00:10 | 2768215.10 | 03-AUG-14:00 |
HeatRejection:EnergyTransfer | 25832.84 | 0.00 | 01-JAN-00:10 | 3163066.60 | 03-AUG-14:00 |
General:HeatRejection:EnergyTransfer | 25832.84 | 0.00 | 01-JAN-00:10 | 3163066.60 | 03-AUG-14:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 6.336 | -732.537 | 0.000 | 0.000 | 92.569 | 150.641 | 424.397 | 0.000 | 0.000 | 0.000 | 58.594 | 0.000 | 0.000 | 0.000 | 0.000 | -0.021 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -755.935 | 0.000 | 0.000 | 83.433 | 135.286 | 289.614 | 0.000 | 0.000 | 0.000 | 247.602 | 0.000 | 0.000 | 0.000 | 0.000 | -0.003 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5655.711 | 0.000 | 0.000 | 835.736 | 1352.864 | 2896.128 | 0.000 | 0.000 | 0.000 | 570.983 | 0.000 | 0.000 | 0.000 | 0.000 | -0.007 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -610.052 | 0.000 | 0.000 | 83.787 | 135.286 | 289.613 | 0.000 | 0.000 | 0.000 | 101.366 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -130.237 | 0.000 | 0.000 | 10.465 | 9.831 | 36.365 | 50.000 | 0.000 | 1.781 | 34.459 | 0.000 | -12.111 | 0.000 | -0.554 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -94.373 | 0.000 | 0.000 | 6.747 | 6.314 | 23.435 | 51.459 | 0.000 | 1.204 | 12.821 | 0.000 | -7.256 | 0.000 | -0.352 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -152.147 | 0.000 | 0.000 | 10.456 | 9.692 | 36.366 | 79.935 | 0.000 | 1.756 | 26.467 | 0.000 | -11.931 | 0.000 | -0.594 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -142.983 | 0.000 | 0.000 | 6.729 | 6.319 | 23.435 | 50.193 | 0.000 | 1.131 | 65.436 | 0.000 | -9.792 | 0.000 | -0.467 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -1074.815 | 0.000 | 0.000 | 105.017 | 98.308 | 363.654 | 511.412 | 0.000 | 40.824 | 79.463 | 0.000 | -111.869 | 0.000 | -11.995 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -861.396 | 0.000 | 0.000 | 49.626 | 63.124 | 234.352 | 514.532 | 0.000 | 26.992 | 52.920 | 0.000 | -71.721 | 0.000 | -8.429 | 0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -1317.963 | 0.000 | 0.000 | 104.642 | 96.939 | 363.660 | 803.547 | 0.000 | 39.989 | 40.795 | 0.000 | -117.338 | 0.000 | -14.269 | -0.007 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -939.264 | 0.000 | 0.000 | 67.613 | 63.169 | 234.351 | 518.012 | 0.000 | 26.484 | 120.770 | 0.000 | -81.965 | 0.000 | -9.170 | -0.003 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -118.959 | 0.000 | 0.000 | 10.575 | 9.830 | 36.365 | 50.585 | 0.000 | 4.953 | 18.519 | 0.000 | -10.514 | 0.000 | -1.355 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -95.264 | 0.000 | 0.000 | 6.784 | 6.312 | 23.435 | 51.020 | 0.000 | 3.266 | 12.279 | 0.000 | -6.857 | 0.000 | -0.975 | -0.001 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -143.396 | 0.000 | 0.000 | 10.502 | 9.694 | 36.366 | 79.674 | 0.000 | 4.863 | 15.210 | 0.000 | -11.243 | 0.000 | -1.670 | -0.000 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -102.292 | 0.000 | 0.000 | 6.806 | 6.317 | 23.435 | 51.400 | 0.000 | 3.240 | 19.982 | 0.000 | -7.819 | 0.000 | -1.069 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -142.679 | 0.000 | 0.000 | 0.940 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -15.768 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1335.595 | 0.000 | 0.000 | 9.395 | 36.263 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -248.870 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.000 | -133.150 | 0.000 | 0.000 | 0.942 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -25.299 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | -7205.544 | 0.000 | 0.000 | 0.000 | 0.000 | 20.569 | 42.474 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -352.356 |
GROUNDFLOOR_PLENUM | 0.703 | -120.027 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.402 | 117.169 | 0.000 | 0.000 | 0.000 | -1.247 | 0.000 |
MIDFLOOR_PLENUM | 4.192 | -928.906 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 62.226 | 883.582 | 0.000 | 0.000 | 0.000 | -21.094 | 0.000 |
TOPFLOOR_PLENUM | 1.864 | -168.516 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.537 | 162.208 | 0.000 | 0.000 | 0.000 | -2.093 | 0.000 |
Total Facility | 6.759 | -8422.993 | 6.336 | -14538.747 | 0.000 | 0.000 | 1523.334 | 2245.917 | 14676.396 | 2811.768 | 0.000 | 228.648 | 2640.624 | 0.000 | -460.415 | 0.000 | -75.332 | -642.335 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 29-OCT-16:02 | 0.00 | 0.00 | 0.00 | -95981.21 | 0.00 | 0.00 | 392.10 | 730.80 | 13457.54 | 0.00 | 0.00 | 0.00 | 81400.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 02-JAN-04:02 | 0.00 | 0.00 | 0.00 | -91215.09 | 0.00 | 0.00 | 0.00 | 656.31 | 5937.65 | 0.00 | 0.00 | 0.00 | 84621.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:02 | 0.00 | 0.00 | 0.00 | -832760.85 | 0.00 | 0.00 | 0.00 | 6563.11 | 59376.23 | 0.00 | 0.00 | 0.00 | 766821.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 13-NOV-05:03 | 0.00 | 0.00 | 0.00 | -82566.19 | 0.00 | 0.00 | 0.00 | 1312.46 | 5937.62 | 0.00 | 0.00 | 0.00 | 75316.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 13-AUG-15:01 | 0.00 | 0.00 | 0.00 | -20619.86 | 0.00 | 0.00 | 38.81 | 39.21 | 720.18 | 4920.20 | 0.00 | 606.33 | 14295.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 30-JUL-13:41 | 0.00 | 0.00 | 0.00 | -16753.12 | 0.00 | 0.00 | 24.33 | 25.27 | 464.11 | 4111.91 | 0.00 | 451.89 | 11675.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 13-AUG-14:21 | 0.00 | 0.00 | 0.00 | -23150.37 | 0.00 | 0.00 | 37.80 | 39.21 | 720.19 | 6036.86 | 0.00 | 636.18 | 15680.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 13-AUG-15:41 | 0.00 | 0.00 | 0.00 | -24236.96 | 0.00 | 0.00 | 18.94 | 25.27 | 464.11 | 7411.32 | 0.00 | 317.39 | 15999.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JUL-15:31 | 0.00 | 0.00 | 0.00 | -200896.40 | 0.00 | 0.00 | 396.55 | 392.09 | 7201.84 | 49502.48 | 0.00 | 9706.04 | 133697.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 21-MAY-09:22 | 0.00 | 0.00 | 0.00 | -174969.54 | 0.00 | 0.00 | 235.65 | 252.68 | 4641.14 | 83322.31 | 0.00 | 5408.61 | 81109.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-14:32 | 0.00 | 0.00 | 0.00 | -230296.55 | 0.00 | 0.00 | 359.95 | 392.10 | 7201.95 | 80978.50 | 0.00 | 8833.54 | 132530.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JUL-15:31 | 0.00 | 0.00 | 0.00 | -198457.18 | 0.00 | 0.00 | 219.38 | 252.68 | 4641.11 | 76041.85 | 0.00 | 6000.23 | 111301.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 21-MAY-12:32 | 0.00 | 0.00 | 0.00 | -25022.42 | 0.00 | 0.00 | 35.86 | 39.21 | 720.18 | 4394.12 | 0.00 | 3818.00 | 16015.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 21-MAY-12:32 | 0.00 | 0.00 | 0.00 | -19824.36 | 0.00 | 0.00 | 21.54 | 25.27 | 464.11 | 2849.72 | 0.00 | 2479.65 | 13984.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-14:32 | 0.00 | 0.00 | 0.00 | -27470.87 | 0.00 | 0.00 | 33.56 | 39.21 | 720.19 | 7960.95 | 0.00 | 1045.55 | 17671.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-15:31 | 0.00 | 0.00 | 0.00 | -23208.67 | 0.00 | 0.00 | 20.02 | 25.27 | 464.11 | 7481.64 | 0.00 | 706.58 | 14511.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 23-APR-17:30 | 0.00 | 0.00 | 0.00 | -7669.18 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -142.83 |
DATACENTER_MID_ZN_6 | 23-APR-17:32 | 0.00 | 0.00 | 0.00 | -72382.03 | 0.00 | 0.00 | 0.00 | 175.92 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5738.11 |
DATACENTER_TOP_ZN_6 | 23-APR-17:32 | 0.00 | 0.00 | 0.00 | -7488.99 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -323.02 |
DATACENTER_BASEMENT_ZN_6 | 07-AUG-16:00 | 0.00 | -369063.54 | 0.00 | 0.00 | 0.00 | 0.00 | 2183.10 | 3708.62 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16460.71 |
GROUNDFLOOR_PLENUM | 07-AUG-05:15 | 0.00 | -17361.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.64 | 17318.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 18-SEP-05:02 | 0.00 | -99256.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 899.84 | 98356.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-12:10 | 0.00 | -27743.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.72 | 27214.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:02 | 0.00 | -465181.06 | 0.00 | -1704882.52 | 0.00 | 0.00 | 15760.19 | 24548.95 | 616289.16 | 27409.97 | 0.00 | 3169.61 | 1482885.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 30-JUL-13:40 | 0.00 | 0.00 | 33033.53 | 0.00 | 0.00 | 0.00 | 402.42 | 730.80 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -47624.30 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JAN-06:08 | 0.00 | 0.00 | 50.34 | 0.00 | 0.00 | 0.00 | 137.09 | 164.79 | 960.25 | 0.00 | 0.00 | 0.00 | 850.06 | 0.00 | -2118.01 | 0.00 | -44.52 | 0.00 |
PERIMETER_TOP_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 06-MAR-04:02 | 8970.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -254.01 | -8716.30 |
MIDFLOOR_PLENUM | 17-APR-03:02 | 66201.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -147.37 | -66053.81 |
TOPFLOOR_PLENUM | 21-FEB-06:03 | 16351.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -196.18 | -16155.74 |
Total Facility | 17-APR-03:02 | -1696540.76 | 1406634.02 | 0.00 | -1406634.02 | 0.00 | 0.00 | 0.00 | 12276.00 | 587299.42 | 0.00 | 0.00 | 0.18 | 1125615.15 | 0.00 | -28102.93 | 0.00 | -547.06 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.1787 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.3828 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 97.2932 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 89.1030 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.6480 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.4783 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.4160 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.4160 | 0.2216 | 1.0000 | Not calculated | 1.2002 | 0.2216 | ||
AIRLOOP DATACENTER BOT | 0.4676 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4676 | 0.0334 | 1.0000 | Not calculated | 0.0156 | 0.0334 | ||
AIRLOOP DATACENTER MID | 4.4509 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4509 | 0.0351 | 1.0000 | Not calculated | 0.1563 | 0.0351 | ||
AIRLOOP DATACENTER TOP | 0.4494 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4494 | 0.0348 | 1.0000 | Not calculated | 0.0156 | 0.0348 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.0893 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.8356 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 48.6466 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 27.7888 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.3240 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.9833 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.4160 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.4160 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2216 | ||
AIRLOOP DATACENTER BOT | 0.4676 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4676 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0334 | ||
AIRLOOP DATACENTER MID | 4.4509 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4509 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0351 | ||
AIRLOOP DATACENTER TOP | 0.4494 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4494 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0348 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.002360 | 149.6021 | 0.000305 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.002360 | 1.9486 | 0.000305 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.002360 | 19.4861 | 0.000305 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.002360 | 1.9486 | 0.000305 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.002360 | 149.60 | 0.000305 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BOT | 0.002360 | 1.95 | 0.000305 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.002360 | 19.49 | 0.000305 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.002360 | 1.95 | 0.000305 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.4160 | 5.4160 | 5.4160 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6487 | 5.6487 | 1.9149 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 53.2879 | 53.2879 | 18.8639 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6161 | 5.6161 | 1.9769 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1300 | 1.1300 | 0.2407 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9246 | 0.9246 | 0.1849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2578 | 1.2578 | 0.2516 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2176 | 1.2176 | 0.2435 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.2560 | 11.2560 | 2.3750 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.7233 | 9.7233 | 1.9447 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.4644 | 12.4644 | 2.4929 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.5617 | 10.5617 | 2.1123 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3372 | 1.3372 | 0.2674 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0423 | 1.0423 | 0.2085 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4534 | 1.4534 | 0.2907 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1991 | 1.1991 | 0.2398 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4676 | 0.4676 | 0.4676 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4509 | 4.4509 | 4.4509 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4494 | 0.4494 | 0.4494 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.1787 | 9.3828 | 10.1787 | 2.8356 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 97.2932 | 89.1030 | 97.2932 | 27.7888 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.6480 | 10.4783 | 10.6480 | 2.9833 | 0.0000 | 1.0000 |
CAV_BAS | 5.4160 | 5.4160 | 5.4160 | 5.4160 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4676 | 0.4676 | 0.4676 | 0.4676 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4509 | 4.4509 | 4.4509 | 4.4509 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4494 | 0.4494 | 0.4494 | 0.4494 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.4160 | 5.4160 | 5.4160 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8243 | 2.8243 | 1.9149 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 26.6439 | 26.6439 | 18.8639 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8081 | 2.8081 | 1.9769 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5650 | 0.5650 | 0.2407 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4623 | 0.4623 | 0.1849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6289 | 0.6289 | 0.2516 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6088 | 0.6088 | 0.2435 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6280 | 5.6280 | 2.3750 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.8616 | 4.8616 | 1.9447 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.2322 | 6.2322 | 2.4929 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2808 | 5.2808 | 2.1123 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6686 | 0.6686 | 0.2674 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5211 | 0.5211 | 0.2085 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7267 | 0.7267 | 0.2907 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5995 | 0.5995 | 0.2398 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4676 | 0.4676 | 0.4676 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4509 | 4.4509 | 4.4509 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4494 | 0.4494 | 0.4494 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.0893 | 2.8356 | 2.8356 | 2.8356 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 48.6466 | 27.7888 | 27.7888 | 27.7888 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.3240 | 2.9833 | 2.9833 | 2.9833 | 0.0000 | 1.0000 |
CAV_BAS | 5.4160 | 5.4160 | 5.4160 | 5.4160 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4676 | 0.4676 | 0.4676 | 0.4676 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4509 | 4.4509 | 4.4509 | 4.4509 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4494 | 0.4494 | 0.4494 | 0.4494 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 619.33 |
Number of hours not met | 619.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 |
Heating -- Boiler | 0.00 | 0.00 | 0.01 | 1006.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3682.44 | 427273.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7230.09 | 371732.63 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2245.92 | 215979.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 323.55 | 37611.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.57 | 3396.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ComputerHVAC | 1498.97 | 75926.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 1499.94 | 178011.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1318.30 | 69964.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 958.40 | 53621.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 525.01 | 68021.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 28113.09 |
Natural Gas | 0.00 | 525.03 |
Additional | 0.00 | 7230.09 |
Total | 14676.40 | 35868.21 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 48.49 |
Space Heating | 0.00 |
Space Cooling | 79.50 |
Fans (All) | 32.38 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 606.93 |
Subtotal | 606.93 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 11.33 |
Miscellaneous (All) | 11.33 |
Subtotal | 11.33 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.26 |
Space Heating | 0.00 |
Space Cooling | 30.42 |
Fans (All) | 4.18 |
Service Water Heating | 1.46 |
Receptacle Equipment | 40.92 |
Miscellaneous | 16.75 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2362. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 6720.00 | 2040.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8717.50 | 42.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8529.50 | 230.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8525.67 | 234.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8417.50 | 342.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7392.67 | 1367.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8292.00 | 468.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8131.67 | 628.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7942.67 | 817.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7708.67 | 1051.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8163.33 | 596.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8010.17 | 749.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7912.00 | 848.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7772.67 | 987.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 5916.67 | 2843.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 5814.00 | 2946.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6545.17 | 2214.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8700.00 | 60.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8167.50 | 592.50 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
Average | 7550.41 | 1209.59 | 0.00 | 0.00 | 0.00 |
Sum | 173659.33 | 27820.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 363340.33 | 5275.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330774.00 | 39.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1373.83 | 894.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1342.33 | 925.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1508.00 | 760.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 103395.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 363340.33 | 103395.00 | 0.00 | 0.00 | 0.00 |
Average | 75496.24 | 4838.67 | 0.00 | 0.00 | 0.00 |
Sum | 1736413.50 | 111289.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 3994.17 | 4765.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 7270.33 | 1489.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7268.33 | 1491.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7321.50 | 1438.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6076.33 | 2683.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6398.50 | 2361.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5821.00 | 2939.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 5339.17 | 3420.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 5972.83 | 2787.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 5902.83 | 2857.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 5679.33 | 3080.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 5742.67 | 3017.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6045.83 | 2714.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 5940.00 | 2820.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 5752.67 | 3007.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 5830.00 | 2930.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7030.33 | 1729.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6921.33 | 1838.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7433.83 | 1326.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 4977.00 | 3783.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 4543.00 | 4217.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3555.50 | 5204.50 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 1326.17 | 0.00 | 0.00 | 0.00 |
Max | 7433.83 | 8760.00 | 0.00 | 0.00 | 0.00 |
Average | 5687.67 | 3072.33 | 0.00 | 0.00 | 0.00 |
Sum | 130816.50 | 70663.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 312067.83 | 56548.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 327908.00 | 2905.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 328391.00 | 2422.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 326189.33 | 4623.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38865.83 | 59.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24862.33 | 46.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38857.17 | 67.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24821.67 | 87.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38843.83 | 81.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18288.83 | 65.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38835.67 | 89.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24828.00 | 81.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38835.33 | 89.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24828.00 | 81.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38833.83 | 91.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24825.33 | 83.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1693.17 | 574.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1653.50 | 614.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1813.33 | 454.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 103395.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 328391.00 | 103395.00 | 0.00 | 0.00 | 0.00 |
Average | 72836.61 | 7498.30 | 0.00 | 0.00 | 0.00 |
Sum | 1675242.00 | 172461.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:05:50
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.600624E+11 | 95151.77 | 17-JAN-05:03 | 16.83 | 11.99 | 0.567939E+10 | 7499.12 | 10-JAN-10:09 | 16.83 | 11.99 |
February | 0.530361E+11 | 94903.83 | 13-FEB-04:03 | 13.50 | 11.03 | 0.515084E+10 | 7499.45 | 15-FEB-14:20 | 25.33 | 18.17 |
March | 0.591962E+11 | 95020.54 | 27-MAR-03:02 | 22.95 | 13.60 | 0.614385E+10 | 7499.52 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.538384E+11 | 94699.17 | 03-APR-03:02 | 24.90 | 17.54 | 0.545929E+10 | 7499.85 | 28-APR-13:20 | 36.13 | 23.08 |
May | 0.576990E+11 | 88077.09 | 08-MAY-03:13 | 28.93 | 17.95 | 0.591111E+10 | 7499.63 | 08-MAY-13:39 | 35.50 | 23.99 |
June | 0.587144E+11 | 79839.88 | 06-JUN-03:02 | 26.73 | 22.01 | 0.589152E+10 | 7499.72 | 02-JUN-13:20 | 26.73 | 22.01 |
July | 0.620711E+11 | 90572.94 | 03-JUL-03:02 | 29.83 | 17.19 | 0.548307E+10 | 7500.09 | 21-JUL-13:09 | 42.25 | 27.34 |
August | 0.710541E+11 | 84556.92 | 13-AUG-14:59 | 40.00 | 25.61 | 0.614698E+10 | 7498.77 | 11-AUG-13:20 | 40.00 | 25.61 |
September | 0.621392E+11 | 86777.22 | 04-SEP-11:18 | 39.00 | 23.19 | 0.546210E+10 | 7499.28 | 26-SEP-13:00 | 39.00 | 23.79 |
October | 0.665967E+11 | 95994.63 | 29-OCT-16:02 | 31.83 | 20.03 | 0.568170E+10 | 7499.38 | 27-OCT-13:09 | 31.83 | 20.03 |
November | 0.653973E+11 | 95080.20 | 05-NOV-12:08 | 33.90 | 17.83 | 0.562548E+10 | 7499.01 | 17-NOV-14:50 | 29.00 | 19.77 |
December | 0.627344E+11 | 94718.88 | 18-DEC-04:02 | 13.92 | 11.67 | 0.548298E+10 | 7499.07 | 01-DEC-14:20 | 13.92 | 11.67 |
Annual Sum or Average | 0.732539E+12 | 0.681183E+11 | ||||||||
Minimum of Months | 0.530361E+11 | 79839.88 | 13.50 | 11.03 | 0.515084E+10 | 7498.77 | 13.92 | 11.67 | ||
Maximum of Months | 0.710541E+11 | 95994.63 | 40.00 | 25.61 | 0.614698E+10 | 7500.09 | 42.25 | 27.34 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.485378E+11 | 91217.08 | 02-JAN-04:02 | 14.08 | 11.74 | 0.507974E+10 | 6734.81 | 09-JAN-10:09 | 15.75 | 15.22 |
February | 0.476316E+11 | 89377.87 | 13-FEB-04:03 | 13.50 | 11.03 | 0.460918E+10 | 6734.93 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.619408E+11 | 89776.96 | 06-MAR-04:02 | 16.33 | 13.08 | 0.549879E+10 | 6735.13 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.657333E+11 | 82859.45 | 24-APR-05:03 | 21.83 | 13.96 | 0.487680E+10 | 6735.19 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.631366E+11 | 80043.73 | 01-MAY-05:04 | 20.98 | 20.98 | 0.528143E+10 | 6735.04 | 04-MAY-13:00 | 36.00 | 22.99 |
June | 0.668500E+11 | 80043.38 | 12-JUN-05:03 | 29.02 | 24.10 | 0.526431E+10 | 6734.79 | 02-JUN-13:09 | 29.02 | 24.10 |
July | 0.711160E+11 | 83413.18 | 17-JUL-05:05 | 31.00 | 26.53 | 0.489327E+10 | 6735.19 | 03-JUL-09:09 | 31.00 | 26.53 |
August | 0.771751E+11 | 84118.81 | 21-AUG-05:05 | 30.00 | 28.44 | 0.549692E+10 | 6734.57 | 24-AUG-09:00 | 34.90 | 25.82 |
September | 0.626955E+11 | 75698.89 | 05-SEP-05:03 | 30.17 | 24.66 | 0.487659E+10 | 6734.67 | 26-SEP-09:39 | 35.93 | 21.30 |
October | 0.662170E+11 | 83493.90 | 30-OCT-05:04 | 22.82 | 18.34 | 0.507249E+10 | 6734.67 | 10-OCT-13:00 | 22.82 | 18.34 |
November | 0.635838E+11 | 86602.68 | 22-NOV-04:02 | 17.75 | 15.04 | 0.502601E+10 | 6734.67 | 22-NOV-10:09 | 23.42 | 16.99 |
December | 0.613151E+11 | 88132.29 | 18-DEC-04:02 | 13.92 | 11.67 | 0.489946E+10 | 6734.76 | 20-DEC-10:09 | 21.25 | 16.42 |
Annual Sum or Average | 0.755933E+12 | 0.608750E+11 | ||||||||
Minimum of Months | 0.476316E+11 | 75698.89 | 13.50 | 11.03 | 0.460918E+10 | 6734.57 | 15.75 | 15.22 | ||
Maximum of Months | 0.771751E+11 | 91217.08 | 31.00 | 28.44 | 0.549879E+10 | 6735.19 | 36.00 | 26.53 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.376551E+11 | 83287.58 | 02-JAN-04:02 | 14.08 | 11.74 | 0.505478E+10 | 6734.80 | 09-JAN-10:09 | 15.75 | 15.22 |
February | 0.353553E+11 | 78359.67 | 25-FEB-06:02 | 18.98 | 14.29 | 0.459036E+10 | 6734.98 | 15-FEB-14:09 | 18.98 | 14.29 |
March | 0.442715E+11 | 79438.42 | 29-MAR-05:04 | 20.42 | 18.83 | 0.548898E+10 | 6735.14 | 28-MAR-09:00 | 20.42 | 18.83 |
April | 0.446733E+11 | 79322.97 | 04-APR-05:04 | 19.00 | 17.09 | 0.487334E+10 | 6735.21 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.527451E+11 | 67804.25 | 17-MAY-05:03 | 25.02 | 18.40 | 0.527520E+10 | 6735.06 | 08-MAY-13:30 | 25.02 | 18.40 |
June | 0.534760E+11 | 63036.27 | 08-JUN-05:02 | 25.78 | 25.14 | 0.525555E+10 | 6734.89 | 02-JUN-13:09 | 25.78 | 25.14 |
July | 0.550979E+11 | 63282.12 | 12-JUL-05:02 | 30.17 | 28.47 | 0.487749E+10 | 6735.22 | 03-JUL-09:09 | 30.17 | 28.47 |
August | 0.581879E+11 | 64978.46 | 03-AUG-05:02 | 30.83 | 27.31 | 0.548173E+10 | 6734.58 | 15-AUG-09:00 | 38.30 | 20.88 |
September | 0.512576E+11 | 67177.66 | 29-SEP-03:02 | 26.83 | 25.39 | 0.486833E+10 | 6734.68 | 26-SEP-09:50 | 26.83 | 25.39 |
October | 0.497676E+11 | 72882.93 | 17-OCT-03:02 | 25.05 | 23.73 | 0.506834E+10 | 6734.63 | 20-OCT-09:00 | 30.40 | 18.49 |
November | 0.442112E+11 | 79580.07 | 09-NOV-06:04 | 21.90 | 18.65 | 0.502028E+10 | 6734.66 | 22-NOV-10:09 | 23.42 | 16.99 |
December | 0.388713E+11 | 78885.45 | 11-DEC-05:03 | 22.00 | 18.76 | 0.488049E+10 | 6734.75 | 01-DEC-14:09 | 22.00 | 18.76 |
Annual Sum or Average | 0.565570E+12 | 0.607349E+11 | ||||||||
Minimum of Months | 0.353553E+11 | 63036.27 | 14.08 | 11.74 | 0.459036E+10 | 6734.58 | 15.75 | 14.29 | ||
Maximum of Months | 0.581879E+11 | 83287.58 | 30.83 | 28.47 | 0.548898E+10 | 6735.22 | 38.30 | 28.47 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.317025E+11 | 77857.93 | 30-JAN-06:03 | 20.03 | 17.43 | 0.495572E+10 | 6734.75 | 24-JAN-10:00 | 20.03 | 17.43 |
February | 0.325362E+11 | 78754.17 | 27-FEB-06:02 | 17.77 | 15.99 | 0.453822E+10 | 6734.95 | 15-FEB-14:09 | 17.77 | 15.99 |
March | 0.437599E+11 | 82285.41 | 29-MAR-04:03 | 21.08 | 19.43 | 0.546291E+10 | 6735.14 | 28-MAR-09:00 | 21.08 | 19.43 |
April | 0.477913E+11 | 82381.77 | 20-APR-04:03 | 22.08 | 20.02 | 0.486715E+10 | 6735.19 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.611659E+11 | 74518.41 | 02-MAY-05:02 | 21.83 | 20.40 | 0.527958E+10 | 6735.03 | 04-MAY-13:00 | 36.00 | 22.99 |
June | 0.634039E+11 | 72437.05 | 26-JUN-05:02 | 29.00 | 25.21 | 0.526162E+10 | 6734.84 | 02-JUN-13:09 | 29.00 | 25.21 |
July | 0.668379E+11 | 75714.77 | 17-JUL-05:02 | 31.00 | 26.53 | 0.489031E+10 | 6735.20 | 03-JUL-09:09 | 31.00 | 26.53 |
August | 0.701161E+11 | 80805.49 | 07-AUG-05:02 | 32.82 | 23.16 | 0.549186E+10 | 6734.55 | 04-AUG-13:00 | 32.82 | 23.16 |
September | 0.595288E+11 | 71173.16 | 18-SEP-05:02 | 29.00 | 24.48 | 0.487311E+10 | 6734.66 | 26-SEP-09:50 | 36.42 | 21.54 |
October | 0.543476E+11 | 74973.27 | 18-OCT-03:02 | 25.97 | 24.53 | 0.506906E+10 | 6734.65 | 10-OCT-13:39 | 25.97 | 24.53 |
November | 0.439140E+11 | 82575.10 | 13-NOV-05:03 | 21.00 | 17.30 | 0.500793E+10 | 6734.61 | 22-NOV-10:09 | 23.42 | 16.99 |
December | 0.349484E+11 | 80564.97 | 11-DEC-05:03 | 22.00 | 18.76 | 0.482401E+10 | 6734.71 | 01-DEC-14:09 | 22.00 | 18.76 |
Annual Sum or Average | 0.610052E+12 | 0.605215E+11 | ||||||||
Minimum of Months | 0.317025E+11 | 71173.16 | 17.77 | 15.99 | 0.453822E+10 | 6734.55 | 17.77 | 15.99 | ||
Maximum of Months | 0.701161E+11 | 82575.10 | 32.82 | 26.53 | 0.549186E+10 | 6735.20 | 36.42 | 26.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.532970E+10 | 11544.81 | 30-JAN-06:03 | 20.03 | 17.43 | 0.633479E+09 | 845.63 | 17-JAN-14:09 | 20.03 | 17.43 |
February | 0.585332E+10 | 14621.66 | 06-FEB-06:02 | 21.88 | 19.06 | 0.576847E+09 | 845.66 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.873774E+10 | 13982.57 | 29-MAR-05:02 | 20.42 | 18.83 | 0.690051E+09 | 845.68 | 28-MAR-09:00 | 20.42 | 18.83 |
April | 0.105803E+11 | 15032.11 | 03-APR-05:02 | 24.95 | 19.90 | 0.613699E+09 | 845.70 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.126847E+11 | 19175.27 | 29-MAY-14:02 | 34.00 | 27.38 | 0.666014E+09 | 845.68 | 04-MAY-13:00 | 34.00 | 27.38 |
June | 0.142460E+11 | 19446.47 | 25-JUN-16:42 | 34.93 | 28.12 | 0.663828E+09 | 845.63 | 02-JUN-13:09 | 34.93 | 28.12 |
July | 0.156519E+11 | 20495.74 | 30-JUL-13:41 | 44.08 | 24.34 | 0.617973E+09 | 845.97 | 21-JUL-13:20 | 44.08 | 24.34 |
August | 0.167275E+11 | 20625.97 | 13-AUG-15:01 | 39.80 | 25.70 | 0.693021E+09 | 846.70 | 04-AUG-13:20 | 39.80 | 25.70 |
September | 0.124055E+11 | 19300.04 | 04-SEP-15:21 | 40.85 | 24.13 | 0.615068E+09 | 845.62 | 26-SEP-09:39 | 35.93 | 21.30 |
October | 0.113449E+11 | 15722.00 | 10-OCT-04:02 | 27.00 | 23.50 | 0.638965E+09 | 845.63 | 10-OCT-13:00 | 34.50 | 20.13 |
November | 0.925361E+10 | 15221.72 | 20-NOV-06:03 | 25.85 | 18.49 | 0.631563E+09 | 845.62 | 16-NOV-14:00 | 25.85 | 18.49 |
December | 0.742144E+10 | 12590.79 | 11-DEC-06:03 | 21.90 | 19.23 | 0.613821E+09 | 845.63 | 01-DEC-14:09 | 21.90 | 19.23 |
Annual Sum or Average | 0.130237E+12 | 0.765433E+10 | ||||||||
Minimum of Months | 0.532970E+10 | 11544.81 | 20.03 | 17.43 | 0.576847E+09 | 845.62 | 20.03 | 17.43 | ||
Maximum of Months | 0.167275E+11 | 20625.97 | 44.08 | 28.12 | 0.693021E+09 | 846.70 | 44.08 | 28.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.407458E+10 | 6654.96 | 30-JAN-06:03 | 20.03 | 17.43 | 0.408487E+09 | 544.96 | 24-JAN-10:00 | 20.03 | 17.43 |
February | 0.429934E+10 | 9054.30 | 06-FEB-06:02 | 21.88 | 19.06 | 0.371322E+09 | 544.97 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.618308E+10 | 7965.28 | 27-MAR-10:20 | 36.00 | 18.30 | 0.443878E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.760834E+10 | 13758.68 | 23-APR-10:23 | 32.85 | 16.69 | 0.395088E+09 | 545.00 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.972802E+10 | 15985.00 | 21-MAY-10:53 | 38.60 | 21.42 | 0.429267E+09 | 544.99 | 04-MAY-13:00 | 38.60 | 21.42 |
June | 0.102883E+11 | 16146.70 | 11-JUN-09:02 | 36.33 | 26.36 | 0.427666E+09 | 544.95 | 02-JUN-13:09 | 36.33 | 26.36 |
July | 0.110047E+11 | 16758.89 | 30-JUL-13:41 | 44.08 | 24.34 | 0.398117E+09 | 545.08 | 31-JUL-09:00 | 39.90 | 23.78 |
August | 0.117471E+11 | 16727.31 | 13-AUG-10:22 | 38.80 | 25.02 | 0.446414E+09 | 545.11 | 04-AUG-09:00 | 38.80 | 25.02 |
September | 0.943342E+10 | 16381.77 | 04-SEP-08:42 | 35.38 | 21.67 | 0.396435E+09 | 544.95 | 26-SEP-09:39 | 35.93 | 21.30 |
October | 0.843237E+10 | 11847.89 | 02-OCT-05:02 | 26.83 | 24.79 | 0.411797E+09 | 544.96 | 10-OCT-13:00 | 34.50 | 20.13 |
November | 0.657701E+10 | 7528.36 | 01-NOV-05:02 | 23.83 | 21.92 | 0.406742E+09 | 544.95 | 16-NOV-14:00 | 30.00 | 19.03 |
December | 0.499654E+10 | 5220.29 | 04-DEC-10:10 | 24.67 | 20.70 | 0.394280E+09 | 544.96 | 01-DEC-14:09 | 24.67 | 20.70 |
Annual Sum or Average | 0.943728E+11 | 0.492949E+10 | ||||||||
Minimum of Months | 0.407458E+10 | 5220.29 | 20.03 | 16.69 | 0.371322E+09 | 544.95 | 20.03 | 17.43 | ||
Maximum of Months | 0.117471E+11 | 16758.89 | 44.08 | 26.36 | 0.446414E+09 | 545.11 | 39.90 | 26.36 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.803561E+10 | 13981.59 | 30-JAN-06:03 | 20.03 | 17.43 | 0.636088E+09 | 845.65 | 24-JAN-10:00 | 20.03 | 17.43 |
February | 0.830231E+10 | 21997.54 | 05-FEB-13:43 | 31.52 | 19.39 | 0.578019E+09 | 845.69 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.108650E+11 | 16011.00 | 26-MAR-11:53 | 34.00 | 17.12 | 0.690714E+09 | 845.96 | 27-MAR-13:00 | 35.00 | 19.40 |
April | 0.116292E+11 | 20479.80 | 30-APR-12:23 | 37.05 | 20.86 | 0.614072E+09 | 845.72 | 28-APR-13:09 | 37.05 | 20.86 |
May | 0.128151E+11 | 21225.39 | 29-MAY-14:02 | 34.00 | 27.38 | 0.665940E+09 | 845.70 | 04-MAY-13:00 | 34.00 | 27.38 |
June | 0.137778E+11 | 21355.53 | 11-JUN-13:02 | 36.97 | 28.58 | 0.663605E+09 | 845.65 | 02-JUN-13:09 | 36.97 | 28.58 |
July | 0.155235E+11 | 22965.00 | 30-JUL-13:41 | 44.08 | 24.34 | 0.617834E+09 | 845.71 | 03-JUL-09:09 | 44.08 | 24.34 |
August | 0.175530E+11 | 23157.89 | 13-AUG-14:21 | 40.00 | 25.61 | 0.693067E+09 | 846.18 | 29-AUG-13:20 | 37.40 | 29.98 |
September | 0.147340E+11 | 22065.46 | 03-SEP-12:23 | 39.95 | 25.59 | 0.615550E+09 | 845.99 | 28-SEP-13:50 | 35.10 | 25.53 |
October | 0.151251E+11 | 22682.91 | 29-OCT-12:02 | 34.77 | 15.66 | 0.640136E+09 | 846.11 | 11-OCT-13:39 | 34.77 | 15.66 |
November | 0.132017E+11 | 22817.29 | 05-NOV-12:32 | 33.60 | 19.72 | 0.633201E+09 | 846.21 | 13-NOV-14:09 | 33.00 | 16.45 |
December | 0.105853E+11 | 22175.60 | 03-DEC-12:32 | 29.20 | 17.98 | 0.615564E+09 | 845.65 | 01-DEC-14:09 | 29.20 | 17.98 |
Annual Sum or Average | 0.152148E+12 | 0.766379E+10 | ||||||||
Minimum of Months | 0.803561E+10 | 13981.59 | 20.03 | 15.66 | 0.578019E+09 | 845.65 | 20.03 | 15.66 | ||
Maximum of Months | 0.175530E+11 | 23157.89 | 44.08 | 28.58 | 0.693067E+09 | 846.21 | 44.08 | 29.98 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.572150E+10 | 14281.78 | 25-JAN-06:02 | 17.88 | 14.29 | 0.410399E+09 | 544.96 | 24-JAN-10:00 | 17.88 | 14.29 |
February | 0.688240E+10 | 18271.78 | 05-FEB-15:43 | 32.00 | 19.00 | 0.373861E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.107423E+11 | 18727.10 | 19-MAR-15:53 | 25.00 | 17.88 | 0.446599E+09 | 545.00 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.131177E+11 | 20209.96 | 23-APR-15:42 | 32.42 | 18.29 | 0.396930E+09 | 545.01 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.121565E+11 | 21022.78 | 29-MAY-16:01 | 35.25 | 24.36 | 0.429696E+09 | 545.00 | 04-MAY-13:00 | 35.25 | 24.36 |
June | 0.142160E+11 | 22181.81 | 25-JUN-16:02 | 34.67 | 28.02 | 0.428223E+09 | 544.95 | 02-JUN-13:09 | 34.67 | 28.02 |
July | 0.163054E+11 | 23292.92 | 04-JUL-15:51 | 38.40 | 27.76 | 0.398848E+09 | 545.00 | 03-JUL-09:09 | 38.40 | 27.76 |
August | 0.186843E+11 | 24248.98 | 13-AUG-15:41 | 39.00 | 26.01 | 0.447312E+09 | 544.95 | 04-AUG-13:39 | 39.00 | 26.01 |
September | 0.121136E+11 | 21373.60 | 04-SEP-16:01 | 40.58 | 23.84 | 0.396837E+09 | 544.95 | 26-SEP-09:39 | 35.93 | 21.30 |
October | 0.121367E+11 | 21456.08 | 15-OCT-15:52 | 33.50 | 21.41 | 0.412710E+09 | 544.96 | 10-OCT-13:00 | 33.50 | 21.41 |
November | 0.109386E+11 | 21560.84 | 05-NOV-15:12 | 31.80 | 21.10 | 0.408614E+09 | 544.96 | 16-NOV-14:00 | 30.00 | 19.03 |
December | 0.996771E+10 | 18929.70 | 25-DEC-14:32 | 27.00 | 17.07 | 0.398261E+09 | 544.96 | 01-DEC-14:09 | 27.00 | 17.07 |
Annual Sum or Average | 0.142983E+12 | 0.494829E+10 | ||||||||
Minimum of Months | 0.572150E+10 | 14281.78 | 17.88 | 14.29 | 0.373861E+09 | 544.95 | 17.88 | 14.29 | ||
Maximum of Months | 0.186843E+11 | 24248.98 | 40.58 | 28.02 | 0.447312E+09 | 545.01 | 39.00 | 28.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388784E+10 | 5219.80 | 30-JAN-06:03 | 20.03 | 17.43 | 0.619149E+09 | 845.63 | 17-JAN-14:09 | 20.03 | 17.43 |
February | 0.417581E+10 | 11995.68 | 09-FEB-06:02 | 22.92 | 19.06 | 0.568150E+09 | 845.66 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.628486E+10 | 14829.94 | 02-MAR-06:03 | 28.80 | 15.43 | 0.686252E+09 | 845.68 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.776462E+10 | 14217.02 | 29-APR-03:02 | 26.83 | 16.73 | 0.613147E+09 | 845.70 | 28-APR-13:09 | 26.83 | 16.73 |
May | 0.117889E+11 | 19872.70 | 21-MAY-16:02 | 37.42 | 23.26 | 0.666246E+09 | 845.68 | 04-MAY-13:00 | 37.42 | 23.26 |
June | 0.129999E+11 | 19644.70 | 18-JUN-14:42 | 36.00 | 26.94 | 0.664160E+09 | 845.63 | 02-JUN-13:09 | 36.00 | 26.94 |
July | 0.140380E+11 | 20096.11 | 02-JUL-15:31 | 38.27 | 22.94 | 0.618065E+09 | 845.70 | 03-JUL-09:09 | 34.37 | 23.66 |
August | 0.146734E+11 | 19319.62 | 13-AUG-15:12 | 39.60 | 25.78 | 0.692919E+09 | 845.61 | 15-AUG-09:00 | 38.30 | 20.88 |
September | 0.113877E+11 | 19067.26 | 03-SEP-15:32 | 37.60 | 26.81 | 0.615265E+09 | 845.62 | 26-SEP-13:09 | 40.83 | 22.70 |
October | 0.937249E+10 | 19397.10 | 09-OCT-15:12 | 36.93 | 20.06 | 0.639137E+09 | 845.63 | 11-OCT-13:39 | 35.37 | 21.08 |
November | 0.664230E+10 | 14019.02 | 09-NOV-06:02 | 21.90 | 18.65 | 0.630358E+09 | 845.61 | 16-NOV-14:09 | 30.83 | 19.30 |
December | 0.446671E+10 | 11680.89 | 11-DEC-06:03 | 21.90 | 19.23 | 0.604821E+09 | 845.63 | 01-DEC-14:09 | 21.90 | 19.23 |
Annual Sum or Average | 0.107482E+12 | 0.761767E+10 | ||||||||
Minimum of Months | 0.388784E+10 | 5219.80 | 20.03 | 15.43 | 0.568150E+09 | 845.61 | 20.03 | 16.73 | ||
Maximum of Months | 0.146734E+11 | 20096.11 | 39.60 | 26.94 | 0.692919E+09 | 845.70 | 40.83 | 26.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323734E+10 | 5316.38 | 30-JAN-06:03 | 20.03 | 17.43 | 0.295399E+09 | 521.24 | 06-JAN-11:50 | 20.03 | 17.43 |
February | 0.345980E+10 | 8866.65 | 06-FEB-06:02 | 21.88 | 19.06 | 0.270346E+09 | 521.23 | 06-FEB-16:00 | 26.00 | 21.11 |
March | 0.511214E+10 | 10807.30 | 29-MAR-05:02 | 20.42 | 18.83 | 0.324785E+09 | 521.25 | 28-MAR-10:20 | 20.42 | 18.83 |
April | 0.651326E+10 | 16641.67 | 23-APR-10:32 | 32.90 | 16.63 | 0.291316E+09 | 521.24 | 27-APR-10:00 | 35.00 | 22.50 |
May | 0.957317E+10 | 17497.18 | 21-MAY-10:02 | 37.85 | 20.18 | 0.316383E+09 | 521.26 | 11-MAY-12:09 | 37.85 | 20.18 |
June | 0.100868E+11 | 16922.52 | 18-JUN-14:02 | 36.00 | 26.94 | 0.314876E+09 | 521.23 | 02-JUN-12:20 | 36.00 | 26.94 |
July | 0.108093E+11 | 17339.03 | 02-JUL-14:51 | 38.00 | 22.76 | 0.294113E+09 | 521.25 | 21-JUL-12:39 | 43.53 | 25.92 |
August | 0.115253E+11 | 16684.77 | 20-AUG-08:32 | 34.67 | 25.20 | 0.328505E+09 | 521.58 | 04-AUG-10:50 | 34.67 | 25.20 |
September | 0.918729E+10 | 16746.08 | 17-SEP-09:43 | 33.75 | 23.36 | 0.292403E+09 | 521.22 | 13-SEP-12:09 | 33.75 | 23.36 |
October | 0.765534E+10 | 16798.93 | 09-OCT-14:32 | 37.00 | 20.60 | 0.304073E+09 | 521.21 | 27-OCT-12:50 | 32.33 | 21.68 |
November | 0.540143E+10 | 11205.58 | 20-NOV-06:03 | 25.85 | 18.49 | 0.299623E+09 | 521.22 | 13-NOV-15:30 | 25.85 | 18.49 |
December | 0.357907E+10 | 7996.82 | 11-DEC-06:03 | 21.90 | 19.23 | 0.287319E+09 | 521.21 | 01-DEC-13:20 | 21.90 | 19.23 |
Annual Sum or Average | 0.861403E+11 | 0.361914E+10 | ||||||||
Minimum of Months | 0.323734E+10 | 5316.38 | 20.03 | 16.63 | 0.270346E+09 | 521.21 | 20.03 | 17.43 | ||
Maximum of Months | 0.115253E+11 | 17497.18 | 38.00 | 26.94 | 0.328505E+09 | 521.58 | 43.53 | 26.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.700545E+10 | 15471.95 | 30-JAN-06:03 | 20.03 | 17.43 | 0.633021E+09 | 845.66 | 24-JAN-10:00 | 20.03 | 17.43 |
February | 0.695048E+10 | 17591.40 | 05-FEB-12:33 | 31.07 | 19.40 | 0.575378E+09 | 845.70 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.870586E+10 | 16610.28 | 02-MAR-04:02 | 29.10 | 16.33 | 0.689125E+09 | 845.70 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.891701E+10 | 19379.90 | 23-APR-15:12 | 32.17 | 18.37 | 0.613869E+09 | 845.73 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.118829E+11 | 21863.33 | 21-MAY-15:22 | 37.25 | 23.50 | 0.666146E+09 | 845.70 | 04-MAY-13:00 | 37.25 | 23.50 |
June | 0.124953E+11 | 21501.02 | 18-JUN-14:42 | 36.00 | 26.94 | 0.663893E+09 | 845.65 | 02-JUN-13:09 | 36.00 | 26.94 |
July | 0.139177E+11 | 21982.06 | 02-JUL-15:31 | 38.27 | 22.94 | 0.617920E+09 | 845.72 | 03-JUL-09:09 | 34.37 | 23.66 |
August | 0.156111E+11 | 21433.29 | 13-AUG-15:12 | 39.60 | 25.78 | 0.693019E+09 | 845.63 | 15-AUG-09:00 | 38.30 | 20.88 |
September | 0.138719E+11 | 21570.22 | 03-SEP-14:12 | 39.33 | 26.31 | 0.615832E+09 | 845.90 | 28-SEP-13:50 | 35.10 | 25.53 |
October | 0.134823E+11 | 23032.36 | 09-OCT-14:32 | 37.00 | 20.60 | 0.640632E+09 | 845.99 | 10-OCT-13:00 | 34.50 | 20.13 |
November | 0.110183E+11 | 22154.53 | 05-NOV-11:32 | 33.43 | 17.72 | 0.633211E+09 | 846.04 | 13-NOV-14:09 | 33.00 | 16.45 |
December | 0.793914E+10 | 18268.92 | 03-DEC-12:03 | 28.30 | 18.41 | 0.613553E+09 | 845.66 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.131797E+12 | 0.765560E+10 | ||||||||
Minimum of Months | 0.695048E+10 | 15471.95 | 20.03 | 16.33 | 0.575378E+09 | 845.63 | 20.03 | 16.45 | ||
Maximum of Months | 0.156111E+11 | 23032.36 | 39.60 | 26.94 | 0.693019E+09 | 846.04 | 38.30 | 26.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362659E+10 | 8120.44 | 30-JAN-06:03 | 20.03 | 17.43 | 0.398727E+09 | 544.96 | 24-JAN-10:00 | 20.03 | 17.43 |
February | 0.393731E+10 | 12038.52 | 06-FEB-06:02 | 21.88 | 19.06 | 0.366770E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.589388E+10 | 13068.86 | 02-MAR-04:02 | 29.10 | 16.33 | 0.443350E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.706140E+10 | 18321.13 | 23-APR-15:12 | 32.17 | 18.37 | 0.395946E+09 | 545.01 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.995916E+10 | 19703.44 | 21-MAY-16:02 | 37.42 | 23.26 | 0.429660E+09 | 545.00 | 04-MAY-13:00 | 37.42 | 23.26 |
June | 0.108158E+11 | 19049.95 | 18-JUN-14:42 | 36.00 | 26.94 | 0.428220E+09 | 544.96 | 02-JUN-13:09 | 36.00 | 26.94 |
July | 0.116833E+11 | 19854.76 | 02-JUL-15:31 | 38.27 | 22.94 | 0.398486E+09 | 545.01 | 03-JUL-09:09 | 34.37 | 23.66 |
August | 0.126672E+11 | 18739.10 | 06-AUG-15:42 | 40.25 | 25.55 | 0.446793E+09 | 544.95 | 15-AUG-09:00 | 38.30 | 20.88 |
September | 0.980089E+10 | 18427.72 | 03-SEP-15:32 | 37.60 | 26.81 | 0.396843E+09 | 544.95 | 26-SEP-13:09 | 40.83 | 22.70 |
October | 0.823685E+10 | 19155.26 | 09-OCT-15:12 | 36.93 | 20.06 | 0.412439E+09 | 544.96 | 11-OCT-13:39 | 35.37 | 21.08 |
November | 0.601558E+10 | 16237.16 | 05-NOV-15:32 | 31.60 | 21.44 | 0.407016E+09 | 544.95 | 16-NOV-14:09 | 30.83 | 19.30 |
December | 0.422905E+10 | 10668.64 | 11-DEC-06:03 | 21.90 | 19.23 | 0.391232E+09 | 544.96 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.939271E+11 | 0.491548E+10 | ||||||||
Minimum of Months | 0.362659E+10 | 8120.44 | 20.03 | 16.33 | 0.366770E+09 | 544.95 | 20.03 | 17.31 | ||
Maximum of Months | 0.126672E+11 | 19854.76 | 40.25 | 26.94 | 0.446793E+09 | 545.01 | 40.83 | 26.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.354915E+10 | 5044.48 | 23-JAN-14:10 | 27.50 | 16.66 | 0.589343E+09 | 845.63 | 17-JAN-14:09 | 27.50 | 16.66 |
February | 0.405204E+10 | 9062.71 | 06-FEB-06:02 | 21.88 | 19.06 | 0.552333E+09 | 845.66 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.639473E+10 | 15714.23 | 14-MAR-05:02 | 24.00 | 17.16 | 0.678331E+09 | 845.68 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.837567E+10 | 16804.85 | 03-APR-05:02 | 24.95 | 19.90 | 0.611560E+09 | 845.70 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.134716E+11 | 25028.99 | 21-MAY-12:32 | 38.00 | 22.80 | 0.666339E+09 | 845.68 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.150733E+11 | 24111.16 | 18-JUN-14:42 | 36.00 | 26.94 | 0.664276E+09 | 845.63 | 02-JUN-13:09 | 36.00 | 26.94 |
July | 0.165694E+11 | 24783.81 | 02-JUL-15:31 | 38.27 | 22.94 | 0.618294E+09 | 845.70 | 03-JUL-09:09 | 34.37 | 23.66 |
August | 0.171294E+11 | 23497.48 | 06-AUG-15:02 | 40.85 | 24.99 | 0.693094E+09 | 845.60 | 04-AUG-13:39 | 40.85 | 24.99 |
September | 0.130708E+11 | 23512.02 | 04-SEP-15:21 | 40.85 | 24.13 | 0.615387E+09 | 845.62 | 26-SEP-09:50 | 36.42 | 21.54 |
October | 0.102888E+11 | 23635.86 | 09-OCT-15:12 | 36.93 | 20.06 | 0.639068E+09 | 845.63 | 10-OCT-13:39 | 34.40 | 20.40 |
November | 0.675415E+10 | 16545.53 | 01-NOV-05:02 | 23.83 | 21.92 | 0.627590E+09 | 845.62 | 16-NOV-14:20 | 30.67 | 19.24 |
December | 0.423125E+10 | 7954.64 | 11-DEC-06:03 | 21.90 | 19.23 | 0.588285E+09 | 845.63 | 01-DEC-14:09 | 21.90 | 19.23 |
Annual Sum or Average | 0.118960E+12 | 0.754390E+10 | ||||||||
Minimum of Months | 0.354915E+10 | 5044.48 | 21.88 | 16.66 | 0.552333E+09 | 845.60 | 21.90 | 16.66 | ||
Maximum of Months | 0.171294E+11 | 25028.99 | 40.85 | 26.94 | 0.693094E+09 | 845.70 | 40.85 | 26.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296279E+10 | 4367.23 | 30-JAN-06:03 | 20.03 | 17.43 | 0.391675E+09 | 544.96 | 24-JAN-10:00 | 20.03 | 17.43 |
February | 0.337363E+10 | 8235.40 | 06-FEB-06:02 | 21.88 | 19.06 | 0.363290E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.527891E+10 | 12744.73 | 26-MAR-14:13 | 32.87 | 18.44 | 0.440012E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.707116E+10 | 17684.31 | 23-APR-10:43 | 32.95 | 16.56 | 0.395005E+09 | 545.01 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.109091E+11 | 19829.38 | 21-MAY-12:32 | 38.00 | 22.80 | 0.429637E+09 | 544.99 | 08-MAY-13:30 | 38.00 | 22.80 |
June | 0.116583E+11 | 18862.53 | 18-JUN-14:42 | 36.00 | 26.94 | 0.428145E+09 | 544.96 | 02-JUN-13:09 | 36.00 | 26.94 |
July | 0.126609E+11 | 19396.32 | 02-JUL-14:51 | 38.00 | 22.76 | 0.398566E+09 | 545.01 | 03-JUL-09:09 | 34.37 | 23.66 |
August | 0.133687E+11 | 18285.33 | 06-AUG-15:02 | 40.85 | 24.99 | 0.446758E+09 | 545.26 | 04-AUG-09:20 | 40.85 | 24.99 |
September | 0.105068E+11 | 18562.23 | 04-SEP-08:42 | 35.38 | 21.67 | 0.396790E+09 | 544.96 | 26-SEP-09:50 | 36.42 | 21.54 |
October | 0.844474E+10 | 18584.24 | 09-OCT-15:12 | 36.93 | 20.06 | 0.412309E+09 | 544.96 | 10-OCT-13:39 | 34.40 | 20.40 |
November | 0.559665E+10 | 13445.56 | 05-NOV-14:42 | 32.17 | 20.87 | 0.406003E+09 | 544.95 | 16-NOV-14:20 | 30.67 | 19.24 |
December | 0.343359E+10 | 5791.48 | 11-DEC-06:03 | 21.90 | 19.23 | 0.384877E+09 | 544.96 | 01-DEC-14:09 | 21.90 | 19.23 |
Annual Sum or Average | 0.952653E+11 | 0.489307E+10 | ||||||||
Minimum of Months | 0.296279E+10 | 4367.23 | 20.03 | 16.56 | 0.363290E+09 | 544.95 | 20.03 | 17.43 | ||
Maximum of Months | 0.133687E+11 | 19829.38 | 40.85 | 26.94 | 0.446758E+09 | 545.26 | 40.85 | 26.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.629311E+10 | 14382.03 | 30-JAN-06:03 | 20.03 | 17.43 | 0.618859E+09 | 845.66 | 24-JAN-10:00 | 20.03 | 17.43 |
February | 0.669078E+10 | 18965.63 | 06-FEB-06:02 | 21.88 | 19.06 | 0.566648E+09 | 845.70 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.884112E+10 | 25086.98 | 26-MAR-14:13 | 32.87 | 18.44 | 0.683498E+09 | 845.70 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.962764E+10 | 23449.26 | 30-APR-12:23 | 37.05 | 20.86 | 0.612098E+09 | 845.72 | 28-APR-13:09 | 37.05 | 20.86 |
May | 0.136125E+11 | 27193.87 | 21-MAY-12:32 | 38.00 | 22.80 | 0.666143E+09 | 845.70 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.145495E+11 | 25899.33 | 18-JUN-14:42 | 36.00 | 26.94 | 0.663971E+09 | 845.65 | 02-JUN-13:09 | 36.00 | 26.94 |
July | 0.164644E+11 | 26617.94 | 02-JUL-15:31 | 38.27 | 22.94 | 0.618115E+09 | 845.71 | 03-JUL-09:09 | 34.37 | 23.66 |
August | 0.181898E+11 | 25561.76 | 13-AUG-15:12 | 39.60 | 25.78 | 0.693138E+09 | 845.62 | 04-AUG-13:39 | 39.60 | 25.78 |
September | 0.157891E+11 | 26010.65 | 04-SEP-15:21 | 40.85 | 24.13 | 0.615862E+09 | 845.89 | 05-SEP-13:00 | 40.00 | 25.05 |
October | 0.146367E+11 | 27474.03 | 09-OCT-14:32 | 37.00 | 20.60 | 0.640573E+09 | 845.84 | 19-OCT-13:00 | 37.00 | 17.97 |
November | 0.112421E+11 | 26665.33 | 05-NOV-12:42 | 33.50 | 20.30 | 0.632188E+09 | 845.65 | 16-NOV-14:20 | 30.67 | 19.24 |
December | 0.746024E+10 | 17409.18 | 03-DEC-14:43 | 27.00 | 20.88 | 0.606177E+09 | 845.66 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.143397E+12 | 0.761727E+10 | ||||||||
Minimum of Months | 0.629311E+10 | 14382.03 | 20.03 | 17.43 | 0.566648E+09 | 845.62 | 20.03 | 17.31 | ||
Maximum of Months | 0.181898E+11 | 27474.03 | 40.85 | 26.94 | 0.693138E+09 | 845.89 | 40.00 | 26.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342107E+10 | 7696.90 | 30-JAN-06:03 | 20.03 | 17.43 | 0.381713E+09 | 544.96 | 17-JAN-14:09 | 20.03 | 17.43 |
February | 0.388458E+10 | 11267.95 | 06-FEB-06:02 | 21.88 | 19.06 | 0.357058E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.600482E+10 | 17843.52 | 26-MAR-14:53 | 32.60 | 18.60 | 0.438474E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.754113E+10 | 17843.47 | 09-APR-15:53 | 29.60 | 23.46 | 0.394844E+09 | 545.00 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.111759E+11 | 22193.77 | 14-MAY-16:22 | 34.00 | 20.91 | 0.429613E+09 | 544.99 | 04-MAY-13:00 | 34.00 | 20.91 |
June | 0.122892E+11 | 22183.44 | 18-JUN-14:42 | 36.00 | 26.94 | 0.428184E+09 | 544.96 | 02-JUN-13:09 | 36.00 | 26.94 |
July | 0.134222E+11 | 23219.09 | 02-JUL-15:31 | 38.27 | 22.94 | 0.398536E+09 | 545.00 | 03-JUL-09:09 | 34.37 | 23.66 |
August | 0.143403E+11 | 21713.09 | 06-AUG-15:42 | 40.25 | 25.55 | 0.446802E+09 | 544.94 | 04-AUG-13:39 | 40.25 | 25.55 |
September | 0.110445E+11 | 21784.12 | 04-SEP-16:01 | 40.58 | 23.84 | 0.396815E+09 | 544.95 | 26-SEP-09:50 | 36.42 | 21.54 |
October | 0.894715E+10 | 22184.08 | 09-OCT-15:12 | 36.93 | 20.06 | 0.412278E+09 | 544.96 | 10-OCT-13:39 | 34.40 | 20.40 |
November | 0.614263E+10 | 20346.39 | 05-NOV-14:42 | 32.17 | 20.87 | 0.405239E+09 | 544.95 | 16-NOV-14:20 | 30.67 | 19.24 |
December | 0.407907E+10 | 8704.29 | 11-DEC-06:03 | 21.90 | 19.23 | 0.381366E+09 | 544.96 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.102293E+12 | 0.487092E+10 | ||||||||
Minimum of Months | 0.342107E+10 | 7696.90 | 20.03 | 17.43 | 0.357058E+09 | 544.94 | 20.03 | 17.31 | ||
Maximum of Months | 0.143403E+11 | 23219.09 | 40.58 | 26.94 | 0.446802E+09 | 545.00 | 40.25 | 26.94 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.535594E+10 | 10122.47 | 30-JAN-06:13 | 20.07 | 17.42 | 0.00 | 0.00 | 01-JAN-00:10 | 20.07 | 17.42 |
February | 0.569452E+10 | 10078.38 | 06-FEB-06:15 | 21.77 | 18.83 | 0.00 | 0.00 | 01-FEB-00:10 | 21.77 | 18.83 |
March | 0.788879E+10 | 9033.58 | 27-MAR-05:13 | 21.93 | 13.41 | 0.00 | 0.00 | 01-MAR-00:10 | 21.93 | 13.41 |
April | 0.906184E+10 | 11449.23 | 24-APR-05:15 | 21.67 | 13.88 | 0.00 | 0.00 | 01-APR-00:10 | 21.67 | 13.88 |
May | 0.111953E+11 | 12325.09 | 22-MAY-05:15 | 27.80 | 20.99 | 0.00 | 0.00 | 01-MAY-00:10 | 27.80 | 20.99 |
June | 0.124687E+11 | 15899.93 | 12-JUN-05:15 | 29.13 | 24.04 | 0.00 | 0.00 | 01-JUN-00:10 | 29.13 | 24.04 |
July | 0.141966E+11 | 16965.41 | 31-JUL-05:15 | 30.67 | 26.91 | 0.00 | 0.00 | 01-JUL-00:10 | 30.67 | 26.91 |
August | 0.158861E+11 | 17364.93 | 07-AUG-05:15 | 32.63 | 23.12 | 0.00 | 0.00 | 01-AUG-00:10 | 32.63 | 23.12 |
September | 0.116790E+11 | 17279.96 | 05-SEP-05:15 | 30.33 | 24.49 | 0.00 | 0.00 | 01-SEP-00:10 | 30.33 | 24.49 |
October | 0.108863E+11 | 15401.80 | 10-OCT-05:15 | 26.67 | 24.04 | 0.00 | 0.00 | 01-OCT-00:10 | 26.67 | 24.04 |
November | 0.886175E+10 | 12812.35 | 13-NOV-06:13 | 20.83 | 17.71 | 0.00 | 0.00 | 01-NOV-00:10 | 20.83 | 17.71 |
December | 0.685228E+10 | 9878.75 | 26-DEC-06:15 | 14.60 | 14.60 | 0.00 | 0.00 | 01-DEC-00:10 | 14.60 | 14.60 |
Annual Sum or Average | 0.120027E+12 | 0.00 | ||||||||
Minimum of Months | 0.535594E+10 | 9033.58 | 14.60 | 13.41 | 0.00 | 0.00 | 14.60 | 13.41 | ||
Maximum of Months | 0.158861E+11 | 17364.93 | 32.63 | 26.91 | 0.00 | 0.00 | 32.63 | 26.91 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.343398E+10 | 7082.61 | 02-JAN-06:15 | 13.00 | 10.85 | 0.00 | 0.00 | 01-JAN-00:10 | 13.00 | 10.85 |
February | 0.366718E+10 | 5565.88 | 21-FEB-06:13 | 13.90 | 13.23 | 0.00 | 0.00 | 01-FEB-00:10 | 13.90 | 13.23 |
March | 0.553797E+10 | 7057.59 | 29-MAR-05:15 | 20.33 | 18.79 | 0.00 | 0.00 | 01-MAR-00:10 | 20.33 | 18.79 |
April | 0.669611E+10 | 7597.61 | 28-APR-15:20 | 34.77 | 22.64 | 0.00 | 0.00 | 01-APR-00:10 | 34.77 | 22.64 |
May | 0.975379E+10 | 8859.80 | 16-MAY-05:03 | 24.67 | 21.67 | 0.00 | 0.00 | 01-MAY-00:10 | 24.67 | 21.67 |
June | 0.103845E+11 | 8416.42 | 29-JUN-05:02 | 32.17 | 25.17 | 0.00 | 0.00 | 01-JUN-00:10 | 32.17 | 25.17 |
July | 0.114719E+11 | 8812.78 | 21-JUL-16:00 | 42.10 | 24.94 | 0.00 | 0.00 | 01-JUL-00:10 | 42.10 | 24.94 |
August | 0.124361E+11 | 9295.50 | 30-AUG-05:02 | 30.17 | 27.62 | 0.00 | 0.00 | 01-AUG-00:10 | 30.17 | 27.62 |
September | 0.997066E+10 | 9926.28 | 18-SEP-05:02 | 29.00 | 24.48 | 0.00 | 0.00 | 01-SEP-00:10 | 29.00 | 24.48 |
October | 0.883191E+10 | 8459.97 | 31-OCT-05:02 | 23.92 | 22.61 | 0.00 | 0.00 | 01-OCT-00:10 | 23.92 | 22.61 |
November | 0.653662E+10 | 7793.41 | 13-NOV-06:13 | 20.83 | 17.71 | 0.00 | 0.00 | 01-NOV-00:10 | 20.83 | 17.71 |
December | 0.417025E+10 | 5966.88 | 11-DEC-06:15 | 21.80 | 19.16 | 0.00 | 0.00 | 01-DEC-00:10 | 21.80 | 19.16 |
Annual Sum or Average | 0.928910E+11 | 0.00 | ||||||||
Minimum of Months | 0.343398E+10 | 5565.88 | 13.00 | 10.85 | 0.00 | 0.00 | 13.00 | 10.85 | ||
Maximum of Months | 0.124361E+11 | 9926.28 | 42.10 | 27.62 | 0.00 | 0.00 | 42.10 | 27.62 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.336724E+10 | 9065.90 | 23-JAN-14:10 | 27.50 | 16.66 | 0.00 | 0.00 | 01-JAN-00:10 | 27.50 | 16.66 |
February | 0.489901E+10 | 13906.68 | 07-FEB-14:10 | 30.50 | 20.52 | 0.00 | 0.00 | 01-FEB-00:10 | 30.50 | 20.52 |
March | 0.865939E+10 | 19289.01 | 27-MAR-13:40 | 35.33 | 19.53 | 0.00 | 0.00 | 01-MAR-00:10 | 35.33 | 19.53 |
April | 0.120731E+11 | 22223.35 | 28-APR-12:10 | 41.12 | 20.13 | 0.00 | 0.00 | 01-APR-00:10 | 41.12 | 20.13 |
May | 0.196174E+11 | 24392.24 | 10-MAY-14:30 | 40.00 | 20.13 | 0.00 | 0.00 | 01-MAY-00:10 | 40.00 | 20.13 |
June | 0.217348E+11 | 24709.09 | 12-JUN-13:10 | 40.25 | 27.32 | 0.00 | 0.00 | 01-JUN-00:10 | 40.25 | 27.32 |
July | 0.247115E+11 | 27746.18 | 21-JUL-12:10 | 45.38 | 23.17 | 0.00 | 0.00 | 01-JUL-00:10 | 45.38 | 23.17 |
August | 0.260005E+11 | 27506.96 | 16-AUG-13:10 | 44.17 | 25.68 | 0.00 | 0.00 | 01-AUG-00:10 | 44.17 | 25.68 |
September | 0.192046E+11 | 24762.94 | 05-SEP-13:50 | 40.15 | 24.82 | 0.00 | 0.00 | 01-SEP-00:10 | 40.15 | 24.82 |
October | 0.146260E+11 | 20100.86 | 04-OCT-13:10 | 36.50 | 20.99 | 0.00 | 0.00 | 01-OCT-00:10 | 36.50 | 20.99 |
November | 0.900768E+10 | 15782.53 | 01-NOV-13:50 | 32.90 | 26.21 | 0.00 | 0.00 | 01-NOV-00:10 | 32.90 | 26.21 |
December | 0.461621E+10 | 11068.14 | 04-DEC-13:10 | 27.83 | 21.18 | 0.00 | 0.00 | 01-DEC-00:10 | 27.83 | 21.18 |
Annual Sum or Average | 0.168517E+12 | 0.00 | ||||||||
Minimum of Months | 0.336724E+10 | 9065.90 | 27.50 | 16.66 | 0.00 | 0.00 | 27.50 | 16.66 | ||
Maximum of Months | 0.260005E+11 | 27746.18 | 45.38 | 27.32 | 0.00 | 0.00 | 45.38 | 27.32 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.430675E+10 | 1869.69 | 01-JAN-17:23 | 21.95 | 15.54 | 95238999.11 | 126.85 | 12-JAN-14:00 | 23.00 | 16.72 |
February | 0.856863E+10 | 3769.00 | 05-FEB-17:20 | 31.00 | 18.60 | 86409418.62 | 126.85 | 09-FEB-10:20 | 24.13 | 19.37 |
March | 0.145649E+11 | 7202.03 | 31-MAR-23:35 | 22.43 | 20.39 | 0.103245E+09 | 126.85 | 02-MAR-14:20 | 22.43 | 20.39 |
April | 0.189797E+11 | 7669.21 | 23-APR-17:25 | 30.50 | 19.17 | 92051296.58 | 139.60 | 26-APR-13:09 | 37.33 | 19.85 |
May | 0.464762E+10 | 3503.89 | 31-MAY-23:53 | 32.70 | 23.39 | 99239106.82 | 126.85 | 08-MAY-13:00 | 32.70 | 23.39 |
June | 0.940764E+10 | 5364.15 | 30-JUN-23:55 | 31.70 | 26.86 | 98980149.68 | 126.88 | 20-JUN-09:09 | 31.70 | 26.86 |
July | 0.148797E+11 | 7229.09 | 31-JUL-24:00 | 33.30 | 28.31 | 91891813.41 | 126.85 | 26-JUL-09:09 | 33.30 | 28.31 |
August | 0.193260E+11 | 7566.53 | 14-AUG-03:20 | 31.00 | 24.35 | 0.113239E+09 | 150.59 | 10-AUG-13:00 | 31.00 | 24.35 |
September | 0.455624E+10 | 3478.95 | 30-SEP-23:37 | 29.00 | 26.39 | 91606747.39 | 126.85 | 25-SEP-13:39 | 29.00 | 26.39 |
October | 0.969770E+10 | 5366.23 | 31-OCT-23:50 | 27.43 | 21.16 | 95252303.93 | 126.88 | 06-OCT-09:20 | 27.43 | 21.16 |
November | 0.141783E+11 | 5806.72 | 12-NOV-16:43 | 29.02 | 17.82 | 94311764.58 | 126.85 | 01-NOV-09:09 | 29.02 | 17.82 |
December | 0.195655E+11 | 7604.12 | 25-DEC-16:50 | 24.27 | 18.99 | 91883971.27 | 126.83 | 15-DEC-10:09 | 24.27 | 18.99 |
Annual Sum or Average | 0.142679E+12 | 0.115335E+10 | ||||||||
Minimum of Months | 0.430675E+10 | 1869.69 | 21.95 | 15.54 | 86409418.62 | 126.83 | 22.43 | 16.72 | ||
Maximum of Months | 0.195655E+11 | 7669.21 | 33.30 | 28.31 | 0.113239E+09 | 150.59 | 37.33 | 28.31 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345719E+10 | 1697.69 | 01-JAN-17:27 | 21.95 | 15.54 | 95235212.53 | 126.84 | 17-JAN-14:30 | 24.50 | 17.80 |
February | 0.771666E+10 | 3535.79 | 07-FEB-17:00 | 28.00 | 21.23 | 86408481.59 | 126.85 | 09-FEB-10:09 | 23.92 | 19.44 |
March | 0.136924E+11 | 6896.65 | 31-MAR-23:57 | 22.30 | 20.22 | 0.103244E+09 | 126.84 | 02-MAR-14:30 | 22.30 | 20.22 |
April | 0.181005E+11 | 7238.22 | 23-APR-17:32 | 30.33 | 19.12 | 92129627.45 | 139.92 | 26-APR-13:09 | 37.33 | 19.85 |
May | 0.431014E+10 | 3399.89 | 31-MAY-23:53 | 32.70 | 23.39 | 99237719.59 | 126.85 | 08-MAY-13:50 | 32.70 | 23.39 |
June | 0.887314E+10 | 5182.29 | 30-JUN-23:55 | 31.70 | 26.86 | 98978924.93 | 126.87 | 20-JUN-09:09 | 31.70 | 26.86 |
July | 0.140509E+11 | 6877.05 | 31-JUL-24:00 | 33.30 | 28.31 | 91892393.93 | 126.85 | 18-JUL-09:09 | 33.30 | 28.31 |
August | 0.183311E+11 | 7090.37 | 15-AUG-08:20 | 33.33 | 22.07 | 0.113276E+09 | 150.65 | 10-AUG-13:00 | 33.33 | 22.07 |
September | 0.416944E+10 | 3352.14 | 30-SEP-23:27 | 29.00 | 26.37 | 91606102.68 | 126.85 | 05-SEP-13:50 | 29.00 | 26.37 |
October | 0.914734E+10 | 5181.09 | 31-OCT-23:53 | 27.40 | 21.22 | 95250843.02 | 126.87 | 06-OCT-09:20 | 27.40 | 21.22 |
November | 0.133975E+11 | 5407.08 | 06-NOV-17:00 | 30.00 | 22.38 | 94311384.85 | 126.84 | 01-NOV-09:09 | 30.00 | 22.38 |
December | 0.183131E+11 | 7160.27 | 06-DEC-17:00 | 26.00 | 20.50 | 91884033.56 | 126.83 | 15-DEC-10:09 | 19.67 | 18.50 |
Annual Sum or Average | 0.133559E+12 | 0.115345E+10 | ||||||||
Minimum of Months | 0.345719E+10 | 1697.69 | 21.95 | 15.54 | 86408481.59 | 126.83 | 19.67 | 17.80 | ||
Maximum of Months | 0.183311E+11 | 7238.22 | 33.33 | 28.31 | 0.113276E+09 | 150.65 | 37.33 | 28.31 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274546E+10 | 1701.40 | 31-JAN-17:00 | 23.00 | 17.31 | 95233828.56 | 126.84 | 31-JAN-14:00 | 23.00 | 17.31 |
February | 0.733196E+10 | 3599.31 | 06-FEB-16:00 | 31.40 | 17.56 | 86409556.55 | 126.85 | 07-FEB-14:00 | 28.00 | 22.41 |
March | 0.135115E+11 | 6821.48 | 31-MAR-23:57 | 22.30 | 20.22 | 0.103245E+09 | 126.85 | 02-MAR-14:30 | 22.30 | 20.22 |
April | 0.181359E+11 | 7489.02 | 23-APR-17:32 | 30.33 | 19.12 | 91838574.81 | 135.89 | 26-APR-13:09 | 37.33 | 19.85 |
May | 0.448707E+10 | 3450.91 | 31-MAY-23:53 | 32.70 | 23.39 | 99238347.14 | 126.85 | 08-MAY-13:50 | 32.70 | 23.39 |
June | 0.907741E+10 | 5207.78 | 30-JUN-23:37 | 31.57 | 26.68 | 98981258.99 | 126.88 | 08-JUN-13:09 | 31.57 | 26.68 |
July | 0.143422E+11 | 7061.20 | 31-JUL-24:00 | 33.30 | 28.31 | 91893924.84 | 126.85 | 05-JUL-09:09 | 33.30 | 28.31 |
August | 0.187826E+11 | 7302.94 | 07-AUG-02:52 | 33.00 | 23.62 | 0.111083E+09 | 149.34 | 10-AUG-13:00 | 43.00 | 27.50 |
September | 0.434834E+10 | 3395.65 | 30-SEP-23:27 | 29.00 | 26.37 | 91606280.56 | 126.85 | 05-SEP-13:00 | 29.00 | 26.37 |
October | 0.922879E+10 | 5182.89 | 31-OCT-23:53 | 27.40 | 21.22 | 95252800.15 | 126.87 | 06-OCT-09:30 | 27.40 | 21.22 |
November | 0.132892E+11 | 5548.09 | 05-NOV-16:57 | 31.00 | 21.45 | 94313012.00 | 126.85 | 01-NOV-13:30 | 31.00 | 21.45 |
December | 0.178689E+11 | 7187.18 | 06-DEC-17:00 | 26.00 | 20.50 | 91885276.05 | 126.83 | 15-DEC-10:09 | 19.67 | 18.50 |
Annual Sum or Average | 0.133149E+12 | 0.115098E+10 | ||||||||
Minimum of Months | 0.274546E+10 | 1701.40 | 22.30 | 17.31 | 86409556.55 | 126.83 | 19.67 | 17.31 | ||
Maximum of Months | 0.187826E+11 | 7489.02 | 33.30 | 28.31 | 0.111083E+09 | 149.34 | 43.00 | 28.31 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243074E+12 | 93233.27 | 02-JAN-17:00 | 21.00 | 13.15 | 0.206144E+10 | 2745.29 | 04-JAN-10:30 | 18.05 | 13.90 |
February | 0.439409E+12 | 184156.66 | 21-FEB-17:00 | 22.00 | 15.87 | 0.187022E+10 | 2745.29 | 08-FEB-14:39 | 22.00 | 15.87 |
March | 0.730864E+12 | 359272.27 | 31-MAR-24:00 | 22.30 | 20.22 | 0.223475E+10 | 2745.29 | 02-MAR-10:50 | 22.30 | 20.22 |
April | 0.943124E+12 | 366831.34 | 24-APR-16:00 | 33.50 | 21.38 | 0.198297E+10 | 2745.29 | 03-APR-13:00 | 33.50 | 21.38 |
May | 0.242121E+12 | 176390.35 | 31-MAY-23:57 | 32.70 | 23.39 | 0.214810E+10 | 2745.29 | 02-MAY-13:09 | 32.70 | 23.39 |
June | 0.471144E+12 | 268027.29 | 30-JUN-23:53 | 31.70 | 26.86 | 0.214213E+10 | 2745.29 | 08-JUN-13:20 | 31.70 | 26.86 |
July | 0.733696E+12 | 360683.80 | 31-JUL-23:53 | 33.30 | 28.31 | 0.198894E+10 | 2745.29 | 27-JUL-09:30 | 33.30 | 28.31 |
August | 0.980727E+12 | 369063.54 | 07-AUG-16:00 | 39.90 | 26.09 | 0.223475E+10 | 2745.29 | 30-AUG-09:30 | 38.65 | 25.03 |
September | 0.238259E+12 | 177328.55 | 30-SEP-23:53 | 29.00 | 26.44 | 0.198297E+10 | 2745.29 | 15-SEP-13:20 | 29.00 | 26.44 |
October | 0.490818E+12 | 269639.31 | 31-OCT-23:53 | 27.40 | 21.22 | 0.206144E+10 | 2745.29 | 03-OCT-13:39 | 27.40 | 21.22 |
November | 0.712185E+12 | 277320.48 | 13-NOV-17:00 | 29.00 | 22.60 | 0.204131E+10 | 2745.29 | 03-NOV-13:09 | 29.00 | 22.60 |
December | 0.980124E+12 | 368572.85 | 26-DEC-17:00 | 24.00 | 20.62 | 0.198894E+10 | 2745.29 | 05-DEC-14:30 | 24.00 | 20.62 |
Annual Sum or Average | 0.720554E+13 | 0.247380E+11 | ||||||||
Minimum of Months | 0.238259E+12 | 93233.27 | 21.00 | 13.15 | 0.187022E+10 | 2745.29 | 18.05 | 13.90 | ||
Maximum of Months | 0.980727E+12 | 369063.54 | 39.90 | 28.31 | 0.223475E+10 | 2745.29 | 38.65 | 28.31 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144100E+09 | 8505.94 | 16-JAN-12:37 | 25.50 |
February | 0.153086E+09 | 14854.09 | 05-FEB-16:20 | 31.67 |
March | 0.262266E+09 | 15459.30 | 02-MAR-04:04 | 29.10 |
April | 0.491624E+09 | 22788.80 | 29-APR-16:02 | 35.33 |
May | 0.717359E+09 | 29179.77 | 31-MAY-20:03 | 39.87 |
June | 0.726067E+09 | 26568.47 | 17-JUN-15:02 | 37.83 |
July | 0.872228E+09 | 33033.53 | 30-JUL-13:40 | 44.17 |
August | 0.726594E+09 | 29873.08 | 05-AUG-16:02 | 40.08 |
September | 0.768183E+09 | 27664.23 | 04-SEP-16:32 | 40.23 |
October | 0.695191E+09 | 23290.56 | 09-OCT-15:43 | 36.83 |
November | 0.511353E+09 | 20860.19 | 05-NOV-12:10 | 33.90 |
December | 0.267361E+09 | 13085.58 | 10-DEC-13:45 | 29.13 |
Annual Sum or Average | 0.633541E+10 | |||
Minimum of Months | 0.144100E+09 | 8505.94 | 25.50 | |
Maximum of Months | 0.872228E+09 | 33033.53 | 44.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10833.16 | 50.34 | 02-JAN-06:08 | 13.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 10833.16 | |||
Minimum of Months | 0.00 | 0.00 | 13.00 | |
Maximum of Months | 10833.16 | 50.34 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 69107579.16 | 7641.24 | 23-JAN-04:03 | 19.83 |
February | 71639923.88 | 8026.35 | 27-FEB-04:02 | 18.75 |
March | 79269866.87 | 8969.87 | 06-MAR-04:02 | 16.33 |
April | 52761783.20 | 4772.88 | 02-APR-13:02 | 32.67 |
May | 30409516.03 | 5078.07 | 03-MAY-03:02 | 24.75 |
June | 24163305.92 | 4974.98 | 25-JUN-15:22 | 34.80 |
July | 48598378.51 | 6340.84 | 30-JUL-10:21 | 43.70 |
August | 41183173.70 | 5518.20 | 27-AUG-15:41 | 36.58 |
September | 30726305.80 | 4754.14 | 24-SEP-15:12 | 33.97 |
October | 46484098.65 | 4690.57 | 15-OCT-14:32 | 34.33 |
November | 79644142.75 | 7227.46 | 22-NOV-04:02 | 17.75 |
December | 0.128761E+09 | 8802.09 | 22-DEC-04:02 | 15.92 |
Annual Sum or Average | 0.702749E+09 | |||
Minimum of Months | 24163305.92 | 4690.57 | 15.92 | |
Maximum of Months | 0.128761E+09 | 8969.87 | 43.70 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38562281.29 | 5081.49 | 02-JAN-04:02 | 14.08 |
February | 32263018.78 | 5318.96 | 13-FEB-05:03 | 13.00 |
March | 28617328.38 | 6135.48 | 02-MAR-04:02 | 29.10 |
April | 27972183.65 | 6620.22 | 17-APR-03:02 | 24.90 |
May | 39641103.75 | 5698.30 | 19-MAY-03:02 | 25.77 |
June | 29927105.94 | 4968.11 | 18-JUN-16:02 | 35.98 |
July | 41158143.40 | 6127.04 | 30-JUL-13:52 | 44.00 |
August | 29587771.73 | 5511.93 | 13-AUG-15:12 | 39.60 |
September | 42220094.21 | 6008.86 | 03-SEP-14:12 | 39.33 |
October | 41563317.18 | 5773.25 | 13-OCT-03:02 | 26.78 |
November | 31086114.23 | 5661.07 | 20-NOV-04:02 | 26.00 |
December | 36580897.84 | 5147.02 | 11-DEC-05:03 | 22.00 |
Annual Sum or Average | 0.419179E+09 | |||
Minimum of Months | 27972183.65 | 4968.11 | 13.00 | |
Maximum of Months | 42220094.21 | 6620.22 | 44.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.612244E+09 | 12831.99 | 24-JAN-06:03 | 18.03 |
February | 0.350072E+09 | 16352.24 | 21-FEB-06:03 | 13.95 |
March | 0.249944E+09 | 14599.85 | 20-MAR-05:02 | 16.00 |
April | 92817243.76 | 13344.12 | 05-APR-05:02 | 17.00 |
May | 30518277.60 | 9205.90 | 15-MAY-03:02 | 24.18 |
June | 9229537.68 | 6401.20 | 07-JUN-03:02 | 25.83 |
July | 902958.55 | 2223.45 | 27-JUL-03:02 | 30.90 |
August | 322146.51 | 1602.69 | 25-AUG-03:02 | 31.88 |
September | 15983198.27 | 5768.29 | 29-SEP-03:02 | 26.83 |
October | 45816128.96 | 8956.37 | 30-OCT-03:02 | 22.85 |
November | 92233605.27 | 13743.59 | 27-NOV-06:03 | 17.90 |
December | 0.364207E+09 | 13862.86 | 26-DEC-06:02 | 14.80 |
Annual Sum or Average | 0.186429E+10 | |||
Minimum of Months | 322146.51 | 1602.69 | 13.95 | |
Maximum of Months | 0.612244E+09 | 16352.24 | 31.88 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125692E+11 | 13153.15 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.114012E+11 | 13153.15 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.135478E+11 | 13153.15 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.121010E+11 | 13153.15 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.130585E+11 | 13153.15 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.129954E+11 | 13153.15 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.121641E+11 | 13153.15 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.135478E+11 | 13153.15 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.121010E+11 | 13153.15 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.125692E+11 | 13153.15 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.124219E+11 | 13153.15 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.121641E+11 | 13153.15 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.150641E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.114012E+11 | 13153.15 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.135478E+11 | 13153.15 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.112880E+11 | 11812.45 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.102391E+11 | 11812.45 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.121669E+11 | 11812.45 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.108675E+11 | 11812.45 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.117275E+11 | 11812.45 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.116708E+11 | 11812.45 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.109242E+11 | 11812.45 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.121669E+11 | 11812.45 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.108675E+11 | 11812.45 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.112880E+11 | 11812.45 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.111557E+11 | 11812.45 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.109242E+11 | 11812.45 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.135286E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.102391E+11 | 11812.45 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.121669E+11 | 11812.45 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.112880E+11 | 11812.45 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.102391E+11 | 11812.45 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.121669E+11 | 11812.45 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.108675E+11 | 11812.45 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.117275E+11 | 11812.45 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.116708E+11 | 11812.45 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.109242E+11 | 11812.45 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.121669E+11 | 11812.45 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.108675E+11 | 11812.45 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.112880E+11 | 11812.45 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.111557E+11 | 11812.45 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.109242E+11 | 11812.45 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.135286E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.102391E+11 | 11812.45 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.121669E+11 | 11812.45 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.112880E+11 | 11812.45 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.102391E+11 | 11812.45 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.121669E+11 | 11812.45 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.108675E+11 | 11812.45 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.117275E+11 | 11812.45 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.116708E+11 | 11812.45 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.109242E+11 | 11812.45 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.121669E+11 | 11812.45 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.108675E+11 | 11812.45 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.112880E+11 | 11812.45 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.111557E+11 | 11812.45 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.109242E+11 | 11812.45 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.135286E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.102391E+11 | 11812.45 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.121669E+11 | 11812.45 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.880437E+09 | 1174.48 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.767718E+09 | 1195.65 | 09-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.885222E+09 | 1357.79 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.769254E+09 | 1160.97 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.805506E+09 | 752.77 | 23-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.793030E+09 | 756.50 | 08-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.756647E+09 | 992.18 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.845190E+09 | 800.25 | 29-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.774698E+09 | 816.86 | 06-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.829803E+09 | 1079.77 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.856605E+09 | 1281.08 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.867016E+09 | 1307.23 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.983113E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.756647E+09 | 752.77 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.885222E+09 | 1357.79 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.557284E+09 | 788.81 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.491332E+09 | 785.72 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.567860E+09 | 865.51 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.496559E+09 | 699.67 | 18-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.523204E+09 | 484.17 | 25-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.515826E+09 | 454.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.490574E+09 | 524.89 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.546692E+09 | 454.78 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.499275E+09 | 484.15 | 26-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.529767E+09 | 512.17 | 27-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.547777E+09 | 844.98 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.547697E+09 | 852.39 | 14-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.631385E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.490574E+09 | 454.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.567860E+09 | 865.51 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.837353E+09 | 1061.14 | 23-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.747057E+09 | 1144.68 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.876879E+09 | 1355.33 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.770979E+09 | 1167.32 | 18-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.815116E+09 | 781.75 | 23-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.803610E+09 | 793.28 | 08-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.764703E+09 | 1055.83 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.849553E+09 | 795.82 | 29-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.772696E+09 | 813.63 | 06-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.814324E+09 | 809.57 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.820483E+09 | 1171.27 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.818907E+09 | 1252.33 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.969166E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.747057E+09 | 781.75 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.876879E+09 | 1355.33 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.553063E+09 | 751.57 | 09-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.488390E+09 | 721.12 | 09-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.572866E+09 | 880.02 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.501027E+09 | 778.02 | 18-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.526456E+09 | 576.44 | 10-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.517801E+09 | 529.11 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.494366E+09 | 717.77 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.550836E+09 | 668.79 | 29-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.502853E+09 | 687.35 | 06-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.535145E+09 | 742.02 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.537077E+09 | 744.54 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.539328E+09 | 819.70 | 15-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.631921E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.488390E+09 | 529.11 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.572866E+09 | 880.02 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.880366E+09 | 1180.72 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.767591E+09 | 1201.64 | 09-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.885478E+09 | 1360.48 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.769319E+09 | 1167.82 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.805610E+09 | 749.30 | 23-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.792478E+09 | 753.07 | 08-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.756878E+09 | 1002.67 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.845262E+09 | 797.91 | 29-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.774728E+09 | 814.79 | 06-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.829874E+09 | 1088.23 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.856676E+09 | 1285.29 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.866583E+09 | 1310.94 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.983084E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.756878E+09 | 749.30 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.885478E+09 | 1360.48 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.557003E+09 | 789.47 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.491236E+09 | 786.07 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.567594E+09 | 866.05 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.496386E+09 | 702.34 | 18-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.523038E+09 | 480.54 | 25-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.515712E+09 | 454.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.490654E+09 | 523.58 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.546631E+09 | 454.78 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.499180E+09 | 481.00 | 26-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.529783E+09 | 509.97 | 27-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.547578E+09 | 845.31 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.547571E+09 | 852.65 | 14-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.631236E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.490654E+09 | 454.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.567594E+09 | 866.05 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.837556E+09 | 1071.18 | 23-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.747254E+09 | 1152.27 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.877102E+09 | 1358.09 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.771030E+09 | 1173.97 | 18-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.815173E+09 | 778.72 | 23-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.803819E+09 | 790.43 | 08-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.764722E+09 | 1064.40 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.849584E+09 | 793.43 | 29-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.772705E+09 | 811.53 | 06-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.813936E+09 | 807.26 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.821605E+09 | 1178.26 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.819418E+09 | 1257.42 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.969390E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.747254E+09 | 778.72 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.877102E+09 | 1358.09 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.552833E+09 | 752.07 | 09-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.488298E+09 | 721.59 | 09-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.572630E+09 | 880.16 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.500943E+09 | 778.34 | 18-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.526149E+09 | 577.48 | 10-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.517486E+09 | 527.27 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.494136E+09 | 718.18 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.550615E+09 | 669.00 | 29-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.502701E+09 | 687.81 | 26-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.534984E+09 | 743.26 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.536933E+09 | 745.89 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.539168E+09 | 819.99 | 15-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.631688E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.488298E+09 | 527.27 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.572630E+09 | 880.16 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.880278E+09 | 1180.58 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.767545E+09 | 1201.34 | 09-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.885420E+09 | 1360.34 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.769263E+09 | 1167.50 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.805601E+09 | 749.03 | 23-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.792463E+09 | 752.80 | 08-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.756864E+09 | 1002.25 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.845248E+09 | 797.73 | 29-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.774710E+09 | 814.63 | 06-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.829851E+09 | 1088.12 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.856607E+09 | 1285.16 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.866439E+09 | 1310.78 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.983029E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.756864E+09 | 749.03 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.885420E+09 | 1360.34 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.556992E+09 | 789.39 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.491224E+09 | 785.89 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.567580E+09 | 865.97 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.496359E+09 | 702.17 | 18-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.523031E+09 | 480.40 | 25-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.515705E+09 | 454.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.490631E+09 | 523.47 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.546610E+09 | 454.78 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.499168E+09 | 480.90 | 26-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.529778E+09 | 509.89 | 27-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.547562E+09 | 845.22 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.547547E+09 | 852.55 | 14-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.631219E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.490631E+09 | 454.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.567580E+09 | 865.97 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.837553E+09 | 1070.89 | 23-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.747242E+09 | 1151.97 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.877072E+09 | 1357.95 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.771005E+09 | 1173.65 | 18-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.815157E+09 | 778.50 | 23-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.803793E+09 | 790.23 | 08-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.764699E+09 | 1064.00 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.849566E+09 | 793.23 | 29-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.772691E+09 | 811.36 | 06-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.813898E+09 | 807.12 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.821608E+09 | 1178.14 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.819398E+09 | 1257.26 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.969368E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.747242E+09 | 778.50 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.877072E+09 | 1357.95 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.552823E+09 | 751.87 | 09-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.488286E+09 | 721.36 | 09-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.572600E+09 | 880.08 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.500916E+09 | 778.15 | 18-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.526138E+09 | 577.55 | 10-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.517463E+09 | 527.17 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.494119E+09 | 717.95 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.550587E+09 | 668.82 | 29-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.502691E+09 | 687.74 | 26-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.534988E+09 | 743.21 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.536929E+09 | 745.86 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.539123E+09 | 819.85 | 15-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.631666E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.488286E+09 | 527.17 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.572600E+09 | 880.08 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.354398E+10 | 3708.62 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.321465E+10 | 3708.62 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.381990E+10 | 3708.62 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.341196E+10 | 3708.62 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.368194E+10 | 3708.62 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.366414E+10 | 3708.62 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.342976E+10 | 3708.62 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.381990E+10 | 3708.62 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.341196E+10 | 3708.62 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.354398E+10 | 3708.62 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.350245E+10 | 3708.62 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.342976E+10 | 3708.62 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.424744E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.321465E+10 | 3708.62 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.381990E+10 | 3708.62 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.125692E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.114012E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.135478E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.121010E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.130585E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.129954E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.121641E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.135478E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.121010E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.125692E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.124219E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.121641E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.150641E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.114012E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.135478E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.112880E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.102391E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.121669E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.108675E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.117275E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.116708E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.109242E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.121669E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.108675E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.112880E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.111557E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.109242E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.135286E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.102391E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.121669E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.112880E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.102391E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.121669E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.108675E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.117275E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.116708E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.109242E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.121669E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.108675E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.112880E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.111557E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.109242E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.135286E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.102391E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.121669E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.112880E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.102391E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.121669E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.108675E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.117275E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.116708E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.109242E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.121669E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.108675E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.112880E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.111557E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.109242E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.135286E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.102391E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.121669E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.880437E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1418099.55 | 0.153405E+09 |
February | 0.136985E+10 | 0.767718E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13374651.49 | 0.149995E+09 |
March | 0.163685E+10 | 0.885222E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35112582.70 | 76679234.16 |
April | 0.145243E+10 | 0.769254E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84925004.60 | 28605713.58 |
May | 0.157338E+10 | 0.805506E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207586E+09 | 2206262.95 |
June | 0.156900E+10 | 0.793030E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262362E+09 | 76121.07 |
July | 0.145680E+10 | 0.756647E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364213E+09 | 0.00 |
August | 0.163685E+10 | 0.845190E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346336E+09 | 0.00 |
September | 0.145243E+10 | 0.774698E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251268E+09 | 272179.01 |
October | 0.150991E+10 | 0.829803E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145626E+09 | 3181032.06 |
November | 0.149516E+10 | 0.856605E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60151753.07 | 33040739.10 |
December | 0.145680E+10 | 0.867016E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9012418.44 | 0.106589E+09 |
Annual Sum or Average | 0.181194E+11 | 0.983113E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178139E+10 | 0.554051E+09 |
Minimum of Months | 0.136985E+10 | 0.756647E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1418099.55 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.885222E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364213E+09 | 0.153405E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.557284E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 783078.13 | 0.102584E+09 |
February | 0.882782E+09 | 0.491332E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8602155.42 | 97328314.73 |
March | 0.105485E+10 | 0.567860E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23984644.01 | 47347292.69 |
April | 0.936002E+09 | 0.496559E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57646113.35 | 16472871.40 |
May | 0.101394E+10 | 0.523204E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138729E+09 | 1326673.41 |
June | 0.101113E+10 | 0.515826E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178115E+09 | 39073.23 |
July | 0.938820E+09 | 0.490574E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246889E+09 | 0.00 |
August | 0.105485E+10 | 0.546692E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234671E+09 | 0.00 |
September | 0.936002E+09 | 0.499275E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168162E+09 | 166045.26 |
October | 0.973041E+09 | 0.529767E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98284081.31 | 1804098.63 |
November | 0.963541E+09 | 0.547777E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41223344.85 | 20016303.61 |
December | 0.938820E+09 | 0.547697E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6588042.88 | 64763495.72 |
Annual Sum or Average | 0.116768E+11 | 0.631385E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120368E+10 | 0.351848E+09 |
Minimum of Months | 0.882782E+09 | 0.490574E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 783078.13 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.567860E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246889E+09 | 0.102584E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.837353E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 756802.83 | 0.164434E+09 |
February | 0.136988E+10 | 0.747057E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11689084.55 | 0.158391E+09 |
March | 0.163688E+10 | 0.876879E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33443903.85 | 80983334.60 |
April | 0.145246E+10 | 0.770979E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82231810.25 | 29437363.16 |
May | 0.157341E+10 | 0.815116E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208069E+09 | 2206459.29 |
June | 0.156904E+10 | 0.803610E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264928E+09 | 61474.49 |
July | 0.145684E+10 | 0.764703E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366131E+09 | 0.00 |
August | 0.163688E+10 | 0.849553E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346174E+09 | 0.00 |
September | 0.145246E+10 | 0.772696E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246424E+09 | 343930.33 |
October | 0.150994E+10 | 0.814324E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137316E+09 | 4412531.95 |
November | 0.149520E+10 | 0.820483E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51725105.45 | 38088979.38 |
December | 0.145684E+10 | 0.818907E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7144204.14 | 0.115156E+09 |
Annual Sum or Average | 0.181198E+11 | 0.969166E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175603E+10 | 0.593515E+09 |
Minimum of Months | 0.136988E+10 | 0.747057E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 756802.83 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.876879E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366131E+09 | 0.164434E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.553063E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 686988.64 | 0.116341E+09 |
February | 0.882782E+09 | 0.488390E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8029381.72 | 0.120670E+09 |
March | 0.105485E+10 | 0.572866E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21381465.09 | 68559551.34 |
April | 0.936002E+09 | 0.501027E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50367752.41 | 28951586.85 |
May | 0.101394E+10 | 0.526456E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134274E+09 | 2306517.72 |
June | 0.101113E+10 | 0.517801E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168570E+09 | 143304.78 |
July | 0.938820E+09 | 0.494366E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234882E+09 | 0.00 |
August | 0.105485E+10 | 0.550836E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222668E+09 | 0.00 |
September | 0.936002E+09 | 0.502853E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161752E+09 | 304208.00 |
October | 0.973041E+09 | 0.535145E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89633556.08 | 4146081.09 |
November | 0.963541E+09 | 0.537077E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33764013.52 | 32132367.18 |
December | 0.938820E+09 | 0.539328E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4501639.39 | 93357298.35 |
Annual Sum or Average | 0.116768E+11 | 0.631921E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113051E+10 | 0.466912E+09 |
Minimum of Months | 0.882782E+09 | 0.488390E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 686988.64 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.572866E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234882E+09 | 0.120670E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.880366E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5412634.03 | 0.308402E+09 |
February | 0.136985E+10 | 0.767591E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33645847.26 | 0.307734E+09 |
March | 0.163685E+10 | 0.885478E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79795648.23 | 0.172847E+09 |
April | 0.145243E+10 | 0.769319E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194032E+09 | 80940197.18 |
May | 0.157338E+10 | 0.805610E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471631E+09 | 7315554.18 |
June | 0.156900E+10 | 0.792478E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595627E+09 | 386491.62 |
July | 0.145680E+10 | 0.756878E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839769E+09 | 0.00 |
August | 0.163685E+10 | 0.845262E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803828E+09 | 0.00 |
September | 0.145243E+10 | 0.774728E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571408E+09 | 985456.56 |
October | 0.150991E+10 | 0.829874E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324711E+09 | 11555374.55 |
November | 0.149516E+10 | 0.856676E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139206E+09 | 84457599.94 |
December | 0.145680E+10 | 0.866583E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23377006.01 | 0.224861E+09 |
Annual Sum or Average | 0.181194E+11 | 0.983084E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408244E+10 | 0.119948E+10 |
Minimum of Months | 0.136985E+10 | 0.756878E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5412634.03 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.885478E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839769E+09 | 0.308402E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.557003E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2326514.19 | 0.217322E+09 |
February | 0.649041E+09 | 0.491236E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19955930.32 | 0.215301E+09 |
March | 0.773965E+09 | 0.567594E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51283226.80 | 0.121064E+09 |
April | 0.688021E+09 | 0.496386E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123836E+09 | 57564376.78 |
May | 0.744847E+09 | 0.523038E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312655E+09 | 5320236.94 |
June | 0.742030E+09 | 0.515712E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398851E+09 | 291923.02 |
July | 0.690839E+09 | 0.490654E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561848E+09 | 0.00 |
August | 0.773965E+09 | 0.546631E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536750E+09 | 0.00 |
September | 0.688021E+09 | 0.499180E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378469E+09 | 734934.61 |
October | 0.715730E+09 | 0.529783E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211709E+09 | 8980555.95 |
November | 0.708685E+09 | 0.547578E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87126614.34 | 61082058.56 |
December | 0.690839E+09 | 0.547571E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14376958.16 | 0.155283E+09 |
Annual Sum or Average | 0.858171E+10 | 0.631236E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269919E+10 | 0.842944E+09 |
Minimum of Months | 0.649041E+09 | 0.490654E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2326514.19 | 0.00 |
Maximum of Months | 0.773965E+09 | 0.567594E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561848E+09 | 0.217322E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.837556E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1623685.76 | 0.374788E+09 |
February | 0.136988E+10 | 0.747254E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26291128.91 | 0.358859E+09 |
March | 0.163688E+10 | 0.877102E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73684237.19 | 0.197462E+09 |
April | 0.145246E+10 | 0.771030E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185644E+09 | 86530952.34 |
May | 0.157341E+10 | 0.815173E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473748E+09 | 7378124.72 |
June | 0.156904E+10 | 0.803819E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602626E+09 | 318431.70 |
July | 0.145684E+10 | 0.764722E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844756E+09 | 0.00 |
August | 0.163688E+10 | 0.849584E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802132E+09 | 0.00 |
September | 0.145246E+10 | 0.772705E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558932E+09 | 1276886.75 |
October | 0.150994E+10 | 0.813936E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302021E+09 | 17319640.99 |
November | 0.149520E+10 | 0.821605E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112360E+09 | 0.107442E+09 |
December | 0.145684E+10 | 0.819418E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15055221.69 | 0.275530E+09 |
Annual Sum or Average | 0.181198E+11 | 0.969390E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399887E+10 | 0.142690E+10 |
Minimum of Months | 0.136988E+10 | 0.747254E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1623685.76 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.877102E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844756E+09 | 0.374788E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.552833E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2529604.04 | 0.226706E+09 |
February | 0.882782E+09 | 0.488298E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20272091.25 | 0.229563E+09 |
March | 0.105485E+10 | 0.572630E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49743152.92 | 0.136167E+09 |
April | 0.936002E+09 | 0.500943E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120650E+09 | 66104935.69 |
May | 0.101394E+10 | 0.526149E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308021E+09 | 6480859.47 |
June | 0.101113E+10 | 0.517486E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390938E+09 | 439416.22 |
July | 0.938820E+09 | 0.494136E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554706E+09 | 0.00 |
August | 0.105485E+10 | 0.550615E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529041E+09 | 0.00 |
September | 0.936002E+09 | 0.502701E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371350E+09 | 989603.36 |
October | 0.973041E+09 | 0.534984E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205416E+09 | 11334052.49 |
November | 0.963541E+09 | 0.536933E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82927957.37 | 67969227.02 |
December | 0.938820E+09 | 0.539168E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12840168.27 | 0.171218E+09 |
Annual Sum or Average | 0.116768E+11 | 0.631688E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264844E+10 | 0.916973E+09 |
Minimum of Months | 0.882782E+09 | 0.488298E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2529604.04 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.572630E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554706E+09 | 0.229563E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.880278E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7559365.82 | 0.328199E+09 |
February | 0.136985E+10 | 0.767545E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41467353.52 | 0.348112E+09 |
March | 0.163685E+10 | 0.885420E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95655964.57 | 0.202052E+09 |
April | 0.145243E+10 | 0.769263E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230667E+09 | 0.100779E+09 |
May | 0.157338E+10 | 0.805601E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571803E+09 | 10091653.03 |
June | 0.156900E+10 | 0.792463E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722906E+09 | 642725.42 |
July | 0.145680E+10 | 0.756864E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102068E+10 | 0.00 |
August | 0.163685E+10 | 0.845248E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.978347E+09 | 0.00 |
September | 0.145243E+10 | 0.774710E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693706E+09 | 1349799.62 |
October | 0.150991E+10 | 0.829851E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391433E+09 | 15451338.27 |
November | 0.149516E+10 | 0.856607E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168307E+09 | 98855397.08 |
December | 0.145680E+10 | 0.866439E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30431842.91 | 0.249038E+09 |
Annual Sum or Average | 0.181194E+11 | 0.983029E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495296E+10 | 0.135457E+10 |
Minimum of Months | 0.136985E+10 | 0.756864E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7559365.82 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.885420E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102068E+10 | 0.348112E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.556992E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2767749.40 | 0.238566E+09 |
February | 0.882782E+09 | 0.491224E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23918384.94 | 0.248739E+09 |
March | 0.105485E+10 | 0.567580E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61253261.39 | 0.144767E+09 |
April | 0.936002E+09 | 0.496359E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147298E+09 | 72689255.58 |
May | 0.101394E+10 | 0.523031E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378578E+09 | 7374179.65 |
June | 0.101113E+10 | 0.515705E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482846E+09 | 491592.69 |
July | 0.938820E+09 | 0.490631E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681061E+09 | 0.00 |
August | 0.105485E+10 | 0.546610E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651864E+09 | 0.00 |
September | 0.936002E+09 | 0.499168E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458743E+09 | 1009756.86 |
October | 0.973041E+09 | 0.529778E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254735E+09 | 12246493.49 |
November | 0.963541E+09 | 0.547562E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104716E+09 | 73141645.94 |
December | 0.938820E+09 | 0.547547E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18020746.26 | 0.176050E+09 |
Annual Sum or Average | 0.116768E+11 | 0.631219E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326580E+10 | 0.975075E+09 |
Minimum of Months | 0.882782E+09 | 0.490631E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2767749.40 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.567580E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681061E+09 | 0.248739E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.837553E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1910824.38 | 0.422517E+09 |
February | 0.136988E+10 | 0.747242E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31559771.48 | 0.418459E+09 |
March | 0.163688E+10 | 0.877072E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88689532.53 | 0.235351E+09 |
April | 0.145246E+10 | 0.771005E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223176E+09 | 0.108036E+09 |
May | 0.157341E+10 | 0.815157E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575696E+09 | 10020114.32 |
June | 0.156904E+10 | 0.803793E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732569E+09 | 511563.81 |
July | 0.145684E+10 | 0.764699E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102795E+10 | 0.00 |
August | 0.163688E+10 | 0.849566E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.978651E+09 | 0.00 |
September | 0.145246E+10 | 0.772691E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682047E+09 | 1740457.20 |
October | 0.150994E+10 | 0.813898E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366900E+09 | 23466714.25 |
November | 0.149520E+10 | 0.821608E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136283E+09 | 0.129856E+09 |
December | 0.145684E+10 | 0.819398E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17881570.98 | 0.320062E+09 |
Annual Sum or Average | 0.181198E+11 | 0.969368E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486331E+10 | 0.167002E+10 |
Minimum of Months | 0.136988E+10 | 0.747242E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1910824.38 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.877072E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102795E+10 | 0.422517E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.552823E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2868133.59 | 0.253415E+09 |
February | 0.882782E+09 | 0.488286E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24669951.16 | 0.266921E+09 |
March | 0.105485E+10 | 0.572600E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60103800.45 | 0.162863E+09 |
April | 0.936002E+09 | 0.500916E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146344E+09 | 82379488.67 |
May | 0.101394E+10 | 0.526138E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376758E+09 | 8494594.28 |
June | 0.101113E+10 | 0.517463E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478622E+09 | 684507.52 |
July | 0.938820E+09 | 0.494119E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678676E+09 | 0.00 |
August | 0.105485E+10 | 0.550587E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648017E+09 | 0.00 |
September | 0.936002E+09 | 0.502691E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455343E+09 | 1296994.69 |
October | 0.973041E+09 | 0.534988E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250907E+09 | 15018524.08 |
November | 0.963541E+09 | 0.536929E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101230E+09 | 81346734.28 |
December | 0.938820E+09 | 0.539123E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16195559.15 | 0.196809E+09 |
Annual Sum or Average | 0.116768E+11 | 0.631666E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323973E+10 | 0.106923E+10 |
Minimum of Months | 0.882782E+09 | 0.488286E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2868133.59 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.572600E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678676E+09 | 0.266921E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.354398E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.321465E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.381990E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.341196E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.368194E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.366414E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.342976E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.381990E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.341196E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.354398E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.350245E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.342976E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.424744E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.321465E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.381990E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1769773.49 | 0.336777E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23517874.73 | 0.325565E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59613247.13 | 0.174070E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157012E+09 | 70417459.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404211E+09 | 5699401.21 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505526E+09 | 391111.12 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712861E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668791E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482794E+09 | 755094.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269931E+09 | 9747191.43 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102544E+09 | 79905107.23 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13465560.37 | 0.243446E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340204E+10 | 0.124677E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1769773.49 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712861E+09 | 0.336777E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5252688.02 | 0.560366E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46797857.40 | 0.542701E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109682E+09 | 0.297551E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285724E+09 | 0.129015E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730299E+09 | 10486163.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917004E+09 | 727820.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131070E+10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123328E+10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.878450E+09 | 1339559.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487962E+09 | 19184916.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189709E+09 | 0.142768E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27759421.18 | 0.405288E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622263E+10 | 0.210943E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5252688.02 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131070E+10 | 0.560366E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2855231.12 | 0.541344E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42934807.79 | 0.554931E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105538E+09 | 0.315501E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258838E+09 | 0.130958E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753561E+09 | 10573750.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.977575E+09 | 772242.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139685E+10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133583E+10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936066E+09 | 1384571.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513862E+09 | 17931800.16 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190187E+09 | 0.127169E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22593331.86 | 0.392274E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653669E+10 | 0.209284E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2855231.12 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139685E+10 | 0.554931E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 13153.15 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 13153.15 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 13153.15 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 13153.15 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 13153.15 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 13153.15 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 13153.15 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 13153.15 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 13153.15 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 13153.15 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 13153.15 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 13153.15 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 13153.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 13153.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 11812.45 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 11812.45 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 11812.45 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 11812.45 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 11812.45 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 11812.45 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 11812.45 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 11812.45 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 11812.45 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 11812.45 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 11812.45 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 11812.45 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 11812.45 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 11812.45 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 11812.45 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 11812.45 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 11812.45 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 11812.45 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 11812.45 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 11812.45 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 11812.45 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 11812.45 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 11812.45 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 11812.45 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 11812.45 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 11812.45 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 11812.45 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 11812.45 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 11812.45 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 11812.45 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 11812.45 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 11812.45 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 11812.45 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 11812.45 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 11812.45 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 11812.45 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 11812.45 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 11812.45 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 11812.45 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 11812.45 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 11812.45 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 11812.45 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1174.48 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.80 | 29-JAN-11:50 | 411.46 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 1195.65 | 09-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 303.48 | 05-FEB-14:50 | 342.62 | 13-FEB-03:55 |
March | 2010.79 | 01-MAR-10:09 | 1357.79 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 270.84 | 26-MAR-14:00 | 288.84 | 06-MAR-06:00 |
April | 2010.79 | 03-APR-09:09 | 1160.97 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.68 | 30-APR-12:52 | 202.61 | 05-APR-00:53 |
May | 2010.79 | 01-MAY-09:09 | 752.77 | 23-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2114.30 | 21-MAY-12:55 | 60.01 | 01-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 756.50 | 08-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 515.50 | 11-JUN-13:06 | 32.39 | 07-JUN-04:40 |
July | 2010.79 | 03-JUL-09:09 | 992.18 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 780.69 | 30-JUL-14:24 | 0.00 | 01-JUL-00:03 |
August | 2010.79 | 01-AUG-09:09 | 800.25 | 29-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 727.75 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.79 | 01-SEP-09:09 | 816.86 | 06-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 566.56 | 03-SEP-15:46 | 29.42 | 25-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1079.77 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 481.63 | 09-OCT-15:26 | 83.80 | 20-OCT-04:30 |
November | 2010.79 | 01-NOV-09:09 | 1281.08 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.73 | 19-NOV-14:00 | 170.62 | 22-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 1307.23 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 133.05 | 10-DEC-13:00 | 265.18 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 752.77 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 98.80 | 0.00 | |||||
Maximum of Months | 2010.79 | 1357.79 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2114.30 | 411.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 788.81 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.69 | 29-JAN-11:50 | 271.45 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 785.72 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 201.84 | 05-FEB-15:10 | 225.43 | 13-FEB-03:55 |
March | 1295.83 | 01-MAR-10:09 | 865.51 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 199.77 | 02-MAR-04:00 | 181.36 | 06-MAR-06:00 |
April | 1295.83 | 03-APR-09:09 | 699.67 | 18-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.09 | 30-APR-12:52 | 126.47 | 05-APR-00:53 |
May | 1295.83 | 01-MAY-09:09 | 484.17 | 25-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1410.98 | 21-MAY-12:55 | 37.79 | 01-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 454.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 353.67 | 11-JUN-13:06 | 17.32 | 07-JUN-04:40 |
July | 1295.83 | 03-JUL-09:09 | 524.89 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 518.97 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 1295.83 | 01-AUG-09:09 | 454.78 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 485.16 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 484.15 | 26-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 380.06 | 03-SEP-15:46 | 18.91 | 25-SEP-04:40 |
October | 1295.83 | 02-OCT-09:09 | 512.17 | 27-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.90 | 09-OCT-15:26 | 50.42 | 20-OCT-04:30 |
November | 1295.83 | 01-NOV-09:09 | 844.98 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.57 | 19-NOV-14:00 | 107.23 | 22-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 852.39 | 14-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.82 | 10-DEC-12:40 | 164.60 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 454.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 48.69 | 0.00 | |||||
Maximum of Months | 1295.83 | 865.51 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1410.98 | 271.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1061.14 | 23-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.14 | 23-JAN-13:00 | 420.92 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 1144.68 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 291.69 | 05-FEB-15:08 | 347.53 | 10-FEB-24:00 |
March | 2010.83 | 01-MAR-10:09 | 1355.33 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 257.66 | 26-MAR-13:55 | 286.38 | 17-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1167.32 | 18-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 356.54 | 30-APR-13:05 | 204.55 | 05-APR-00:53 |
May | 2010.83 | 01-MAY-09:09 | 781.75 | 23-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2113.64 | 21-MAY-12:55 | 60.48 | 01-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 793.28 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 525.05 | 11-JUN-13:06 | 30.71 | 07-JUN-04:40 |
July | 2010.83 | 03-JUL-09:09 | 1055.83 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 780.14 | 30-JUL-14:24 | 0.00 | 01-JUL-00:03 |
August | 2010.83 | 01-AUG-09:09 | 795.82 | 29-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 727.75 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.83 | 01-SEP-09:09 | 813.63 | 06-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 564.51 | 03-SEP-15:44 | 30.69 | 25-SEP-04:40 |
October | 2010.83 | 02-OCT-09:09 | 809.57 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 476.09 | 09-OCT-15:24 | 94.77 | 20-OCT-04:30 |
November | 2010.83 | 01-NOV-09:09 | 1171.27 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.77 | 19-NOV-13:48 | 171.79 | 22-NOV-06:00 |
December | 2010.83 | 01-DEC-10:09 | 1252.33 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 103.42 | 10-DEC-12:40 | 256.77 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 781.75 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 37.14 | 0.00 | |||||
Maximum of Months | 2010.83 | 1355.33 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2113.64 | 420.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 751.57 | 09-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.79 | 29-JAN-11:50 | 312.71 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 721.12 | 09-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 203.12 | 05-FEB-15:08 | 272.72 | 10-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 880.02 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 173.17 | 26-MAR-13:55 | 247.84 | 17-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 778.02 | 18-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.99 | 30-APR-13:05 | 178.23 | 05-APR-00:50 |
May | 1295.83 | 01-MAY-09:09 | 576.44 | 10-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1418.36 | 21-MAY-12:55 | 49.18 | 02-MAY-02:20 |
June | 1295.83 | 01-JUN-09:09 | 529.11 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.77 | 11-JUN-13:06 | 35.48 | 07-JUN-04:40 |
July | 1295.83 | 03-JUL-09:09 | 717.77 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 521.95 | 30-JUL-14:24 | 0.00 | 01-JUL-00:03 |
August | 1295.83 | 01-AUG-09:09 | 668.79 | 29-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 485.16 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 687.35 | 06-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.34 | 03-SEP-15:44 | 23.14 | 25-SEP-04:40 |
October | 1295.83 | 02-OCT-09:09 | 742.02 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.63 | 09-OCT-15:24 | 77.50 | 20-OCT-04:30 |
November | 1295.83 | 01-NOV-09:09 | 744.54 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.06 | 19-NOV-13:48 | 139.71 | 22-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 819.70 | 15-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.03 | 10-DEC-12:40 | 216.56 | 16-DEC-23:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 529.11 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 58.79 | 0.00 | |||||
Maximum of Months | 1295.83 | 880.02 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1418.36 | 312.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1180.72 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 307.09 | 29-JAN-11:50 | 784.05 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 1201.64 | 09-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 790.23 | 05-FEB-15:00 | 686.29 | 13-FEB-03:55 |
March | 2010.79 | 01-MAR-10:09 | 1360.48 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 648.40 | 26-MAR-14:00 | 605.09 | 06-MAR-06:00 |
April | 2010.79 | 03-APR-09:09 | 1167.82 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 851.73 | 30-APR-13:00 | 464.72 | 05-APR-00:53 |
May | 2010.79 | 01-MAY-09:09 | 749.30 | 23-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4833.14 | 21-MAY-13:00 | 131.50 | 02-MAY-02:55 |
June | 2010.79 | 01-JUN-09:09 | 753.07 | 08-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1177.82 | 11-JUN-14:35 | 91.81 | 07-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 1002.67 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1812.18 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 2010.79 | 01-AUG-09:09 | 797.91 | 29-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1723.38 | 13-AUG-13:54 | 0.00 | 01-AUG-00:03 |
September | 2010.79 | 01-SEP-09:09 | 814.79 | 06-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1312.62 | 04-SEP-16:54 | 91.22 | 25-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1088.23 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1105.14 | 09-OCT-15:55 | 206.87 | 20-OCT-04:00 |
November | 2010.79 | 01-NOV-09:09 | 1285.29 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 764.01 | 19-NOV-14:00 | 376.89 | 22-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 1310.94 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 352.57 | 10-DEC-13:00 | 524.66 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 749.30 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 307.09 | 0.00 | |||||
Maximum of Months | 2010.79 | 1360.48 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4833.14 | 784.05 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 789.47 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 132.62 | 29-JAN-11:50 | 536.38 | 18-JAN-04:00 |
February | 1239.33 | 01-FEB-08:09 | 786.07 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 487.65 | 05-FEB-15:00 | 470.24 | 13-FEB-03:55 |
March | 1239.33 | 01-MAR-08:09 | 866.05 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 415.70 | 02-MAR-04:10 | 410.17 | 05-MAR-14:55 |
April | 1239.33 | 03-APR-07:10 | 702.34 | 18-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 580.46 | 30-APR-12:55 | 318.30 | 05-APR-00:53 |
May | 1239.33 | 01-MAY-07:10 | 480.54 | 25-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3222.09 | 21-MAY-13:00 | 92.99 | 02-MAY-02:55 |
June | 1239.33 | 01-JUN-07:10 | 454.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 788.96 | 11-JUN-14:35 | 59.90 | 07-JUN-05:00 |
July | 1239.33 | 03-JUL-07:10 | 523.58 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1210.24 | 30-JUL-14:33 | 0.00 | 01-JUL-00:03 |
August | 1239.33 | 01-AUG-07:10 | 454.78 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.83 | 13-AUG-13:54 | 0.00 | 01-AUG-00:03 |
September | 1239.33 | 01-SEP-07:10 | 481.00 | 26-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 878.82 | 04-SEP-16:54 | 61.98 | 25-SEP-05:00 |
October | 1239.33 | 02-OCT-07:10 | 509.97 | 27-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 747.44 | 09-OCT-15:15 | 141.24 | 20-OCT-04:00 |
November | 1239.33 | 01-NOV-07:10 | 845.31 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 472.84 | 19-NOV-14:00 | 250.84 | 22-NOV-06:00 |
December | 1239.33 | 01-DEC-08:09 | 852.65 | 14-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 230.86 | 10-DEC-12:55 | 344.13 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 454.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 132.62 | 0.00 | |||||
Maximum of Months | 1239.33 | 866.05 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 3222.09 | 536.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1071.18 | 23-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 84.30 | 23-JAN-13:00 | 872.95 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 1152.27 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 613.30 | 05-FEB-15:17 | 745.41 | 13-FEB-03:55 |
March | 2010.83 | 01-MAR-10:09 | 1358.09 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 597.99 | 02-MAR-04:06 | 692.81 | 05-MAR-14:55 |
April | 2010.83 | 03-APR-09:09 | 1173.97 | 18-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 861.05 | 30-APR-12:55 | 478.52 | 05-APR-00:53 |
May | 2010.83 | 01-MAY-09:09 | 778.72 | 23-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4833.14 | 21-MAY-13:00 | 134.41 | 02-MAY-02:55 |
June | 2010.83 | 01-JUN-09:09 | 790.43 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.27 | 11-JUN-14:50 | 87.39 | 07-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 1064.40 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1812.17 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 2010.83 | 01-AUG-09:09 | 793.43 | 29-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1716.52 | 13-AUG-13:54 | 0.00 | 01-AUG-00:03 |
September | 2010.83 | 01-SEP-09:09 | 811.53 | 06-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1311.65 | 04-SEP-16:54 | 100.24 | 25-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 807.26 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1118.33 | 09-OCT-15:15 | 232.20 | 20-OCT-04:00 |
November | 2010.83 | 01-NOV-09:09 | 1178.26 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 596.99 | 19-NOV-14:00 | 396.34 | 22-NOV-06:00 |
December | 2010.83 | 01-DEC-10:09 | 1257.42 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 233.29 | 10-DEC-11:45 | 530.34 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 778.72 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 84.30 | 0.00 | |||||
Maximum of Months | 2010.83 | 1358.09 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4833.14 | 872.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 752.07 | 09-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 199.36 | 29-JAN-11:50 | 559.17 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 721.59 | 09-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 451.06 | 05-FEB-14:13 | 485.47 | 13-FEB-03:55 |
March | 1295.83 | 01-MAR-10:09 | 880.16 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 422.25 | 02-MAR-04:08 | 468.78 | 05-MAR-14:55 |
April | 1295.83 | 03-APR-09:09 | 778.34 | 18-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 574.32 | 30-APR-12:55 | 343.73 | 05-APR-00:53 |
May | 1295.83 | 01-MAY-09:09 | 577.48 | 10-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3222.45 | 21-MAY-12:53 | 102.37 | 02-MAY-02:55 |
June | 1295.83 | 01-JUN-09:09 | 527.27 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 785.47 | 11-JUN-14:35 | 70.55 | 07-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 718.18 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.11 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 1295.83 | 01-AUG-09:09 | 669.00 | 29-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.33 | 13-AUG-13:54 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 687.81 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 865.33 | 04-SEP-16:54 | 68.64 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 743.26 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 739.23 | 09-OCT-15:15 | 156.47 | 20-OCT-04:00 |
November | 1295.83 | 01-NOV-09:09 | 745.89 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 450.28 | 19-NOV-13:50 | 265.37 | 22-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 819.99 | 15-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 233.12 | 10-DEC-12:15 | 362.13 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 527.27 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 199.36 | 0.00 | |||||
Maximum of Months | 1295.83 | 880.16 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 3222.45 | 559.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1180.58 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 421.89 | 29-JAN-11:50 | 847.72 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 1201.34 | 09-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 952.97 | 05-FEB-15:00 | 754.81 | 13-FEB-03:55 |
March | 2010.79 | 01-MAR-10:09 | 1360.34 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 767.14 | 26-MAR-14:00 | 707.51 | 05-MAR-15:13 |
April | 2010.79 | 03-APR-09:09 | 1167.50 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1028.09 | 30-APR-12:52 | 553.49 | 05-APR-00:53 |
May | 2010.79 | 01-MAY-09:09 | 749.03 | 23-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5942.21 | 21-MAY-13:00 | 164.48 | 15-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 752.80 | 08-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1459.16 | 11-JUN-14:24 | 118.22 | 07-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 1002.25 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2236.69 | 30-JUL-14:35 | 0.00 | 01-JUL-00:03 |
August | 2010.79 | 01-AUG-09:09 | 797.73 | 29-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2099.83 | 13-AUG-13:54 | 0.00 | 01-AUG-00:03 |
September | 2010.79 | 01-SEP-09:09 | 814.63 | 06-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1585.53 | 03-SEP-16:00 | 86.78 | 24-SEP-03:55 |
October | 2010.79 | 02-OCT-09:09 | 1088.12 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1370.10 | 09-OCT-15:55 | 260.98 | 20-OCT-04:00 |
November | 2010.79 | 01-NOV-09:09 | 1285.16 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 932.17 | 19-NOV-14:00 | 436.16 | 22-NOV-05:53 |
December | 2010.79 | 01-DEC-10:09 | 1310.78 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 443.52 | 10-DEC-12:55 | 582.52 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 749.03 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 421.89 | 0.00 | |||||
Maximum of Months | 2010.79 | 1360.34 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5942.21 | 847.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 789.39 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.11 | 29-JAN-11:50 | 588.03 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 785.89 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 578.58 | 05-FEB-15:00 | 521.12 | 13-FEB-03:55 |
March | 1295.83 | 01-MAR-10:09 | 865.97 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 514.59 | 26-MAR-14:18 | 486.07 | 05-MAR-15:13 |
April | 1295.83 | 03-APR-09:09 | 702.17 | 18-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 686.46 | 30-APR-13:08 | 381.20 | 05-APR-00:53 |
May | 1295.83 | 01-MAY-09:09 | 480.40 | 25-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3961.48 | 21-MAY-13:00 | 117.55 | 01-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 454.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 980.91 | 11-JUN-14:24 | 78.81 | 07-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 523.47 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.82 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 1295.83 | 01-AUG-09:09 | 454.78 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1416.00 | 13-AUG-13:54 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 480.90 | 26-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1057.13 | 03-SEP-15:35 | 64.15 | 24-SEP-03:55 |
October | 1295.83 | 02-OCT-09:09 | 509.89 | 27-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 923.39 | 09-OCT-15:55 | 179.55 | 20-OCT-04:00 |
November | 1295.83 | 01-NOV-09:09 | 845.22 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 567.57 | 19-NOV-14:00 | 292.95 | 22-NOV-05:53 |
December | 1295.83 | 01-DEC-10:09 | 852.55 | 14-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 285.20 | 10-DEC-12:40 | 381.99 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 454.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 183.11 | 0.00 | |||||
Maximum of Months | 1295.83 | 865.97 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 3961.48 | 588.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1070.89 | 23-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 108.30 | 29-JAN-11:50 | 970.89 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 1151.97 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 749.78 | 05-FEB-15:17 | 842.32 | 10-FEB-23:10 |
March | 2010.83 | 01-MAR-10:09 | 1357.95 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 735.76 | 26-MAR-14:18 | 822.33 | 05-MAR-14:55 |
April | 2010.83 | 03-APR-09:09 | 1173.65 | 18-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1022.64 | 30-APR-13:05 | 571.01 | 05-APR-00:53 |
May | 2010.83 | 01-MAY-09:09 | 778.50 | 23-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5942.21 | 21-MAY-13:00 | 173.47 | 01-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 790.23 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1466.06 | 11-JUN-14:24 | 110.36 | 07-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 1064.00 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2233.23 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 2010.83 | 01-AUG-09:09 | 793.23 | 29-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2096.50 | 13-AUG-13:54 | 0.00 | 01-AUG-00:03 |
September | 2010.83 | 01-SEP-09:09 | 811.36 | 06-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1585.53 | 03-SEP-16:00 | 101.66 | 24-SEP-03:55 |
October | 2010.83 | 02-OCT-09:09 | 807.12 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1382.37 | 09-OCT-15:15 | 293.79 | 20-OCT-04:00 |
November | 2010.83 | 01-NOV-09:09 | 1178.14 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 722.00 | 19-NOV-13:55 | 464.18 | 22-NOV-05:53 |
December | 2010.83 | 01-DEC-10:09 | 1257.26 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 305.54 | 10-DEC-12:20 | 590.29 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 778.50 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 108.30 | 0.00 | |||||
Maximum of Months | 2010.83 | 1357.95 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5942.21 | 970.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 751.87 | 09-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 263.88 | 29-JAN-11:50 | 621.04 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 721.36 | 09-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 555.64 | 05-FEB-13:32 | 548.54 | 13-FEB-03:55 |
March | 1295.83 | 01-MAR-10:09 | 880.08 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 519.14 | 02-MAR-04:06 | 561.95 | 05-MAR-14:55 |
April | 1295.83 | 03-APR-09:09 | 778.15 | 18-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 687.15 | 30-APR-13:08 | 412.13 | 05-APR-00:53 |
May | 1295.83 | 01-MAY-09:09 | 577.55 | 10-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3961.48 | 21-MAY-13:00 | 129.23 | 01-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 527.17 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 990.92 | 11-JUN-13:06 | 89.15 | 07-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 717.95 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.82 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 1295.83 | 01-AUG-09:09 | 668.82 | 29-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1408.83 | 13-AUG-13:54 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 687.74 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1057.03 | 03-SEP-16:00 | 74.02 | 24-SEP-03:55 |
October | 1295.83 | 02-OCT-09:09 | 743.21 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 912.90 | 09-OCT-15:15 | 197.86 | 20-OCT-04:00 |
November | 1295.83 | 01-NOV-09:09 | 745.86 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 560.57 | 05-NOV-14:46 | 314.14 | 22-NOV-05:53 |
December | 1295.83 | 01-DEC-10:09 | 819.85 | 15-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.98 | 10-DEC-12:40 | 406.94 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 527.17 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 263.88 | 0.00 | |||||
Maximum of Months | 1295.83 | 880.08 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 3961.48 | 621.04 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 3708.62 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 3708.62 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 3708.62 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 3708.62 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 3708.62 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 3708.62 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 3708.62 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 3708.62 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 3708.62 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 3708.62 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 3708.62 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 3708.62 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 3708.62 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 3708.62 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.09 | 29-JAN-11:53 | 880.91 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 612.00 | 05-FEB-14:53 | 724.72 | 13-FEB-03:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 559.69 | 26-MAR-14:00 | 621.93 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 762.48 | 30-APR-12:52 | 438.94 | 05-APR-00:57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4255.37 | 21-MAY-13:00 | 122.05 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1043.15 | 11-JUN-12:52 | 75.88 | 07-JUN-04:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1571.04 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1451.16 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1140.30 | 03-SEP-16:00 | 80.64 | 25-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 949.80 | 09-OCT-15:10 | 178.94 | 20-OCT-04:30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613.25 | 19-NOV-14:00 | 373.52 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.02 | 10-DEC-13:00 | 547.37 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.09 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4255.37 | 880.91 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.26 | 29-JAN-11:53 | 1433.88 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1218.46 | 05-FEB-15:00 | 1218.54 | 13-FEB-03:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1038.22 | 26-MAR-14:00 | 1078.41 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1392.35 | 30-APR-13:00 | 772.85 | 05-APR-03:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7623.87 | 21-MAY-13:00 | 199.05 | 01-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1933.31 | 11-JUN-13:00 | 137.29 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2898.95 | 30-JUL-15:00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2713.61 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2096.41 | 03-SEP-16:00 | 140.92 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1755.66 | 09-OCT-15:00 | 339.51 | 20-OCT-04:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1148.81 | 19-NOV-14:00 | 663.10 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.52 | 10-DEC-13:00 | 930.54 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.26 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7623.87 | 1433.88 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.69 | 29-JAN-11:53 | 1345.77 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1110.36 | 05-FEB-15:00 | 1139.59 | 13-FEB-03:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 892.90 | 02-MAR-03:55 | 1263.41 | 05-MAR-15:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1277.30 | 30-APR-12:52 | 771.34 | 05-APR-00:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7182.08 | 21-MAY-13:00 | 224.32 | 01-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1729.46 | 11-JUN-14:50 | 127.94 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2855.60 | 30-JUL-14:20 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2588.82 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2038.54 | 04-SEP-17:00 | 139.51 | 25-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1675.91 | 09-OCT-15:00 | 377.36 | 20-OCT-04:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1041.34 | 19-NOV-14:00 | 613.20 | 22-NOV-05:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.62 | 10-DEC-12:20 | 889.14 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.69 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7182.08 | 1345.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 95151.77 | 17-JAN-05:03 | 0.00 | 4384.26 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 94903.83 | 13-FEB-04:03 | 0.00 | 2923.20 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 95020.54 | 27-MAR-03:02 | 0.00 | 2923.20 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 94699.17 | 03-APR-03:02 | 0.00 | 3654.01 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 88077.09 | 08-MAY-03:13 | 0.00 | 2192.40 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 79839.88 | 06-JUN-03:02 | 0.00 | 3654.01 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 90572.94 | 03-JUL-03:02 | 0.00 | 4384.81 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84556.92 | 13-AUG-14:59 | 7180.90 | 5846.41 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86777.22 | 04-SEP-11:18 | 5385.68 | 4384.81 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95994.63 | 29-OCT-16:02 | 4488.06 | 3654.01 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 95080.20 | 05-NOV-12:08 | 4488.06 | 3654.01 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 94718.88 | 18-DEC-04:02 | 0.00 | 3654.01 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 79839.88 | 0.00 | 2192.40 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 95994.63 | 7180.90 | 5846.41 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91217.08 | 02-JAN-04:02 | 0.00 | 3281.55 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 89377.87 | 13-FEB-04:03 | 0.00 | 2625.24 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 89776.96 | 06-MAR-04:02 | 0.00 | 3281.55 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82859.45 | 24-APR-05:03 | 9673.43 | 7874.75 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80043.73 | 01-MAY-05:04 | 8061.19 | 6562.29 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80043.38 | 12-JUN-05:03 | 9673.43 | 7874.75 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83413.18 | 17-JUL-05:05 | 9673.43 | 7874.75 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84118.81 | 21-AUG-05:05 | 9673.43 | 7874.75 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 75698.89 | 05-SEP-05:03 | 4836.72 | 3937.37 | 22942.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 83493.90 | 30-OCT-05:04 | 8061.19 | 6562.29 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86602.68 | 22-NOV-04:02 | 0.00 | 3281.55 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 88132.29 | 18-DEC-04:02 | 0.00 | 3281.55 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 75698.89 | 0.00 | 2625.24 | 22942.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91217.08 | 9673.43 | 7874.75 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 83287.58 | 02-JAN-04:02 | 0.00 | 3281.55 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 78359.67 | 25-FEB-06:02 | 8061.19 | 6562.29 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 79438.42 | 29-MAR-05:04 | 8061.19 | 6562.29 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79322.97 | 04-APR-05:04 | 8061.19 | 6562.29 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67804.25 | 17-MAY-05:03 | 6448.95 | 5249.83 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 63036.27 | 08-JUN-05:02 | 8061.19 | 6562.29 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 63282.12 | 12-JUL-05:02 | 8061.19 | 6562.29 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 64978.46 | 03-AUG-05:02 | 9673.43 | 7874.75 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 67177.66 | 29-SEP-03:02 | 0.00 | 3281.55 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72882.93 | 17-OCT-03:02 | 0.00 | 3281.55 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 79580.07 | 09-NOV-06:04 | 8061.19 | 6562.29 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 78885.45 | 11-DEC-05:03 | 0.00 | 5249.83 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 63036.27 | 0.00 | 3281.55 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83287.58 | 9673.43 | 7874.75 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 77857.93 | 30-JAN-06:03 | 6448.95 | 5249.83 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 78754.17 | 27-FEB-06:02 | 8061.19 | 6562.29 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 82285.41 | 29-MAR-04:03 | 0.00 | 5249.83 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82381.77 | 20-APR-04:03 | 0.00 | 5249.83 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74518.41 | 02-MAY-05:02 | 8061.19 | 6562.29 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 72437.05 | 26-JUN-05:02 | 8061.19 | 6562.29 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 75714.77 | 17-JUL-05:02 | 9673.43 | 7874.75 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80805.49 | 07-AUG-05:02 | 9673.43 | 7874.75 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 71173.16 | 18-SEP-05:02 | 8061.19 | 6562.29 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 74973.27 | 18-OCT-03:02 | 0.00 | 3281.55 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 82575.10 | 13-NOV-05:03 | 0.00 | 5249.83 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 80564.97 | 11-DEC-05:03 | 0.00 | 5249.83 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 71173.16 | 0.00 | 3281.55 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82575.10 | 9673.43 | 7874.75 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11544.81 | 30-JAN-06:03 | 809.73 | 659.17 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.92 |
February | 14621.66 | 06-FEB-06:02 | 1012.16 | 823.96 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.20 |
March | 13982.57 | 29-MAR-05:02 | 1012.16 | 823.96 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 |
April | 15032.11 | 03-APR-05:02 | 1214.60 | 988.75 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 0.00 |
May | 19175.27 | 29-MAY-14:02 | 506.08 | 196.04 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 330.55 | 0.00 |
June | 19446.47 | 25-JUN-16:42 | 607.30 | 235.25 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.96 | 0.00 |
July | 20495.74 | 30-JUL-13:41 | 708.51 | 274.46 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 677.38 | 0.00 |
August | 20625.97 | 13-AUG-15:01 | 809.73 | 313.67 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 606.33 | 0.00 |
September | 19300.04 | 04-SEP-15:21 | 708.51 | 274.46 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 472.16 | 0.00 |
October | 15722.00 | 10-OCT-04:02 | 0.00 | 823.96 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 37.23 | 0.00 |
November | 15221.72 | 20-NOV-06:03 | 809.73 | 659.17 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 0.00 |
December | 12590.79 | 11-DEC-06:03 | 809.73 | 659.17 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11544.81 | 0.00 | 196.04 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20625.97 | 1214.60 | 988.75 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 677.38 | 23.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6654.96 | 30-JAN-06:03 | 521.82 | 424.79 | 2475.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 |
February | 9054.30 | 06-FEB-06:02 | 652.28 | 530.99 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.06 |
March | 7965.28 | 27-MAR-10:20 | 1239.33 | 454.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 91.38 | 0.00 |
April | 13758.68 | 23-APR-10:23 | 260.91 | 101.07 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 85.91 | 0.00 |
May | 15985.00 | 21-MAY-10:53 | 260.91 | 101.07 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 320.34 | 0.00 |
June | 16146.70 | 11-JUN-09:02 | 326.14 | 126.34 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 229.41 | 0.00 |
July | 16758.89 | 30-JUL-13:41 | 456.59 | 176.87 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 451.89 | 0.00 |
August | 16727.31 | 13-AUG-10:22 | 391.37 | 151.61 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 354.52 | 0.00 |
September | 16381.77 | 04-SEP-08:42 | 326.14 | 126.34 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 158.04 | 0.00 |
October | 11847.89 | 02-OCT-05:02 | 652.28 | 530.99 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.19 | 0.00 |
November | 7528.36 | 01-NOV-05:02 | 652.28 | 530.99 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 |
December | 5220.29 | 04-DEC-10:10 | 1295.83 | 454.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5220.29 | 260.91 | 101.07 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16758.89 | 1295.83 | 530.99 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 451.89 | 13.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13981.59 | 30-JAN-06:03 | 809.75 | 659.18 | 3841.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 |
February | 21997.54 | 05-FEB-13:43 | 404.87 | 156.84 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 213.23 | 0.00 |
March | 16011.00 | 26-MAR-11:53 | 303.66 | 117.63 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 74.27 | 0.00 |
April | 20479.80 | 30-APR-12:23 | 404.87 | 156.84 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 249.79 | 0.00 |
May | 21225.39 | 29-MAY-14:02 | 506.09 | 196.05 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 334.11 | 0.00 |
June | 21355.53 | 11-JUN-13:02 | 506.09 | 196.05 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 487.43 | 0.00 |
July | 22965.00 | 30-JUL-13:41 | 708.53 | 274.47 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 673.37 | 0.00 |
August | 23157.89 | 13-AUG-14:21 | 809.75 | 313.68 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 636.18 | 0.00 |
September | 22065.46 | 03-SEP-12:23 | 404.87 | 156.84 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 346.90 | 0.00 |
October | 22682.91 | 29-OCT-12:02 | 506.09 | 196.05 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 158.76 | 0.00 |
November | 22817.29 | 05-NOV-12:32 | 506.09 | 196.05 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 153.72 | 0.00 |
December | 22175.60 | 03-DEC-12:32 | 404.87 | 156.84 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13981.59 | 303.66 | 117.63 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23157.89 | 809.75 | 659.18 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 673.37 | 11.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14281.78 | 25-JAN-06:02 | 652.28 | 530.99 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.93 |
February | 18271.78 | 05-FEB-15:43 | 260.91 | 101.07 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 161.42 | 0.00 |
March | 18727.10 | 19-MAR-15:53 | 260.91 | 101.07 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.52 |
April | 20209.96 | 23-APR-15:42 | 326.14 | 126.34 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 164.47 | 0.00 |
May | 21022.78 | 29-MAY-16:01 | 456.59 | 176.87 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 163.37 | 0.00 |
June | 22181.81 | 25-JUN-16:02 | 391.37 | 151.61 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 154.82 | 0.00 |
July | 23292.92 | 04-JUL-15:51 | 456.59 | 176.87 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 248.62 | 0.00 |
August | 24248.98 | 13-AUG-15:41 | 521.82 | 202.14 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 317.39 | 0.00 |
September | 21373.60 | 04-SEP-16:01 | 456.59 | 176.87 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 310.78 | 0.00 |
October | 21456.08 | 15-OCT-15:52 | 326.14 | 126.34 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 129.21 | 0.00 |
November | 21560.84 | 05-NOV-15:12 | 326.14 | 126.34 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 138.17 | 0.00 |
December | 18929.70 | 25-DEC-14:32 | 260.91 | 101.07 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14281.78 | 260.91 | 101.07 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24248.98 | 652.28 | 530.99 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 317.39 | 45.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5219.80 | 30-JAN-06:03 | 809.73 | 659.17 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.02 |
February | 11995.68 | 09-FEB-06:02 | 1012.16 | 823.96 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.84 |
March | 14829.94 | 02-MAR-06:03 | 809.73 | 659.17 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 133.45 | 0.00 |
April | 14217.02 | 29-APR-03:02 | 0.00 | 412.03 | 2795.85 | 0.00 | 0.00 | 0.00 | 0.00 | 16.04 | 0.00 |
May | 19872.70 | 21-MAY-16:02 | 607.30 | 235.25 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1086.34 | 0.00 |
June | 19644.70 | 18-JUN-14:42 | 607.30 | 235.25 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 799.81 | 0.00 |
July | 20096.11 | 02-JUL-15:31 | 708.51 | 274.46 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 970.60 | 0.00 |
August | 19319.62 | 13-AUG-15:12 | 607.30 | 235.25 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1475.80 | 0.00 |
September | 19067.26 | 03-SEP-15:32 | 607.30 | 235.25 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1243.30 | 0.00 |
October | 19397.10 | 09-OCT-15:12 | 607.30 | 235.25 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1030.46 | 0.00 |
November | 14019.02 | 09-NOV-06:02 | 1012.16 | 823.96 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 |
December | 11680.89 | 11-DEC-06:03 | 809.73 | 659.17 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5219.80 | 0.00 | 235.25 | 2795.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20096.11 | 1012.16 | 823.96 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1475.80 | 57.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5316.38 | 30-JAN-06:03 | 521.82 | 424.79 | 2475.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.43 |
February | 8866.65 | 06-FEB-06:02 | 652.28 | 530.99 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.90 |
March | 10807.30 | 29-MAR-05:02 | 652.28 | 530.99 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.31 |
April | 16641.67 | 23-APR-10:32 | 260.91 | 101.07 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 220.08 | 0.00 |
May | 17497.18 | 21-MAY-10:02 | 326.14 | 126.34 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 650.84 | 0.00 |
June | 16922.52 | 18-JUN-14:02 | 391.37 | 151.61 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 595.66 | 0.00 |
July | 17339.03 | 02-JUL-14:51 | 456.59 | 176.87 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 667.77 | 0.00 |
August | 16684.77 | 20-AUG-08:32 | 260.91 | 101.07 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 451.94 | 0.00 |
September | 16746.08 | 17-SEP-09:43 | 260.91 | 101.07 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 378.29 | 0.00 |
October | 16798.93 | 09-OCT-14:32 | 391.37 | 151.61 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 655.04 | 0.00 |
November | 11205.58 | 20-NOV-06:03 | 521.82 | 424.79 | 2475.27 | 0.00 | 0.00 | 0.00 | 0.00 | 23.68 | 0.00 |
December | 7996.82 | 11-DEC-06:03 | 521.82 | 424.79 | 2475.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5316.38 | 260.91 | 101.07 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17497.18 | 652.28 | 530.99 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 667.77 | 38.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15471.95 | 30-JAN-06:03 | 809.75 | 659.18 | 3841.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.66 |
February | 17591.40 | 05-FEB-12:33 | 303.66 | 117.63 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 443.14 | 0.00 |
March | 16610.28 | 02-MAR-04:02 | 0.00 | 412.04 | 3727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 478.67 | 0.00 |
April | 19379.90 | 23-APR-15:12 | 506.09 | 196.05 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 517.12 | 0.00 |
May | 21863.33 | 21-MAY-15:22 | 607.31 | 235.26 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1157.06 | 0.00 |
June | 21501.02 | 18-JUN-14:42 | 607.31 | 235.26 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 815.11 | 0.00 |
July | 21982.06 | 02-JUL-15:31 | 708.53 | 274.47 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 986.84 | 0.00 |
August | 21433.29 | 13-AUG-15:12 | 607.31 | 235.26 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1472.54 | 0.00 |
September | 21570.22 | 03-SEP-14:12 | 607.31 | 235.26 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1071.16 | 0.00 |
October | 23032.36 | 09-OCT-14:32 | 607.31 | 235.26 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 883.35 | 0.00 |
November | 22154.53 | 05-NOV-11:32 | 404.87 | 156.84 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 214.21 | 0.00 |
December | 18268.92 | 03-DEC-12:03 | 303.66 | 117.63 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 34.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15471.95 | 0.00 | 117.63 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23032.36 | 809.75 | 659.18 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1472.54 | 26.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8120.44 | 30-JAN-06:03 | 521.82 | 424.79 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 |
February | 12038.52 | 06-FEB-06:02 | 652.28 | 530.99 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.68 |
March | 13068.86 | 02-MAR-04:02 | 0.00 | 265.53 | 2402.32 | 0.00 | 0.00 | 0.00 | 0.00 | 319.74 | 0.00 |
April | 18321.13 | 23-APR-15:12 | 326.14 | 126.34 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 313.70 | 0.00 |
May | 19703.44 | 21-MAY-16:02 | 391.37 | 151.61 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 664.54 | 0.00 |
June | 19049.95 | 18-JUN-14:42 | 391.37 | 151.61 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 503.21 | 0.00 |
July | 19854.76 | 02-JUL-15:31 | 456.59 | 176.87 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 600.02 | 0.00 |
August | 18739.10 | 06-AUG-15:42 | 391.37 | 151.61 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 616.92 | 0.00 |
September | 18427.72 | 03-SEP-15:32 | 391.37 | 151.61 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 796.30 | 0.00 |
October | 19155.26 | 09-OCT-15:12 | 391.37 | 151.61 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 634.36 | 0.00 |
November | 16237.16 | 05-NOV-15:32 | 260.91 | 101.07 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 340.81 | 0.00 |
December | 10668.64 | 11-DEC-06:03 | 521.82 | 424.79 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8120.44 | 0.00 | 101.07 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19854.76 | 652.28 | 530.99 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 796.30 | 39.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5044.48 | 23-JAN-14:10 | 2010.79 | 705.69 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 78.82 | 0.00 |
February | 9062.71 | 06-FEB-06:02 | 1012.16 | 823.96 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.88 |
March | 15714.23 | 14-MAR-05:02 | 1012.16 | 823.96 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.89 |
April | 16804.85 | 03-APR-05:02 | 1214.60 | 988.75 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 7.78 | 0.00 |
May | 25028.99 | 21-MAY-12:32 | 607.30 | 235.25 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 3818.00 | 0.00 |
June | 24111.16 | 18-JUN-14:42 | 607.30 | 235.25 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 933.74 | 0.00 |
July | 24783.81 | 02-JUL-15:31 | 708.51 | 274.46 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1136.77 | 0.00 |
August | 23497.48 | 06-AUG-15:02 | 607.30 | 235.25 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1296.83 | 0.00 |
September | 23512.02 | 04-SEP-15:21 | 708.51 | 274.46 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1320.25 | 0.00 |
October | 23635.86 | 09-OCT-15:12 | 607.30 | 235.25 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1223.69 | 0.00 |
November | 16545.53 | 01-NOV-05:02 | 1012.16 | 823.96 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.62 |
December | 7954.64 | 11-DEC-06:03 | 809.73 | 659.17 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5044.48 | 607.30 | 235.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25028.99 | 2010.79 | 988.75 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 3818.00 | 73.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4367.23 | 30-JAN-06:03 | 521.82 | 424.79 | 2475.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 |
February | 8235.40 | 06-FEB-06:02 | 652.28 | 530.99 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.01 |
March | 12744.73 | 26-MAR-14:13 | 260.91 | 101.07 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 437.67 | 0.00 |
April | 17684.31 | 23-APR-10:43 | 260.91 | 101.07 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 295.61 | 0.00 |
May | 19829.38 | 21-MAY-12:32 | 391.37 | 151.61 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 2479.65 | 0.00 |
June | 18862.53 | 18-JUN-14:42 | 391.37 | 151.61 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 618.09 | 0.00 |
July | 19396.32 | 02-JUL-14:51 | 456.59 | 176.87 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 774.75 | 0.00 |
August | 18285.33 | 06-AUG-15:02 | 391.37 | 151.61 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 865.94 | 0.00 |
September | 18562.23 | 04-SEP-08:42 | 326.14 | 126.34 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 445.53 | 0.00 |
October | 18584.24 | 09-OCT-15:12 | 391.37 | 151.61 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 804.52 | 0.00 |
November | 13445.56 | 05-NOV-14:42 | 326.14 | 126.34 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 450.93 | 0.00 |
December | 5791.48 | 11-DEC-06:03 | 521.82 | 424.79 | 2475.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4367.23 | 260.91 | 101.07 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19829.38 | 652.28 | 530.99 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 2479.65 | 49.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14382.03 | 30-JAN-06:03 | 809.75 | 659.18 | 3841.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.81 |
February | 18965.63 | 06-FEB-06:02 | 1012.19 | 823.98 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.97 |
March | 25086.98 | 26-MAR-14:13 | 404.87 | 156.84 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 626.07 | 0.00 |
April | 23449.26 | 30-APR-12:23 | 404.87 | 156.84 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 709.52 | 0.00 |
May | 27193.87 | 21-MAY-12:32 | 607.31 | 235.26 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 3820.65 | 0.00 |
June | 25899.33 | 18-JUN-14:42 | 607.31 | 235.26 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 953.65 | 0.00 |
July | 26617.94 | 02-JUL-15:31 | 708.53 | 274.47 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1157.23 | 0.00 |
August | 25561.76 | 13-AUG-15:12 | 607.31 | 235.26 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1773.93 | 0.00 |
September | 26010.65 | 04-SEP-15:21 | 708.53 | 274.47 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1295.09 | 0.00 |
October | 27474.03 | 09-OCT-14:32 | 607.31 | 235.26 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1045.55 | 0.00 |
November | 26665.33 | 05-NOV-12:42 | 506.09 | 196.05 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 460.36 | 0.00 |
December | 17409.18 | 03-DEC-14:43 | 303.66 | 117.63 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14382.03 | 303.66 | 117.63 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27474.03 | 1012.19 | 823.98 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 3820.65 | 63.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7696.90 | 30-JAN-06:03 | 521.82 | 424.79 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.39 |
February | 11267.95 | 06-FEB-06:02 | 652.28 | 530.99 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.72 |
March | 17843.52 | 26-MAR-14:53 | 260.91 | 101.07 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 392.60 | 0.00 |
April | 17843.47 | 09-APR-15:53 | 260.91 | 101.07 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 191.68 | 0.00 |
May | 22193.77 | 14-MAY-16:22 | 391.37 | 151.61 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 461.97 | 0.00 |
June | 22183.44 | 18-JUN-14:42 | 391.37 | 151.61 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 592.68 | 0.00 |
July | 23219.09 | 02-JUL-15:31 | 456.59 | 176.87 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 706.58 | 0.00 |
August | 21713.09 | 06-AUG-15:42 | 391.37 | 151.61 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 744.99 | 0.00 |
September | 21784.12 | 04-SEP-16:01 | 456.59 | 176.87 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 861.23 | 0.00 |
October | 22184.08 | 09-OCT-15:12 | 391.37 | 151.61 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 756.35 | 0.00 |
November | 20346.39 | 05-NOV-14:42 | 326.14 | 126.34 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 443.54 | 0.00 |
December | 8704.29 | 11-DEC-06:03 | 521.82 | 424.79 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7696.90 | 260.91 | 101.07 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23219.09 | 652.28 | 530.99 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 861.23 | 50.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10122.47 | 30-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.75 |
February | 10078.38 | 06-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.45 |
March | 9033.58 | 27-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.52 |
April | 11449.23 | 24-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.22 |
May | 12325.09 | 22-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.49 | 0.00 |
June | 15899.93 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.66 | 0.00 |
July | 16965.41 | 31-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 0.00 |
August | 17364.93 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.64 | 0.00 |
September | 17279.96 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.89 | 0.00 |
October | 15401.80 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.23 | 0.00 |
November | 12812.35 | 13-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.41 |
December | 9878.75 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9033.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17364.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.64 | 59.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7082.61 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.02 |
February | 5565.88 | 21-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.15 |
March | 7057.59 | 29-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.52 |
April | 7597.61 | 28-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.53 | 0.00 |
May | 8859.80 | 16-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 |
June | 8416.42 | 29-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.55 | 0.00 |
July | 8812.78 | 21-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.16 | 0.00 |
August | 9295.50 | 30-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.12 | 0.00 |
September | 9926.28 | 18-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.98 | 0.00 |
October | 8459.97 | 31-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.76 |
November | 7793.41 | 13-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.66 |
December | 5966.88 | 11-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5565.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9926.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.16 | 186.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9065.90 | 23-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.02 | 0.00 |
February | 13906.68 | 07-FEB-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.28 | 0.00 |
March | 19289.01 | 27-MAR-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.62 | 0.00 |
April | 22223.35 | 28-APR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.18 | 0.00 |
May | 24392.24 | 10-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.23 | 0.00 |
June | 24709.09 | 12-JUN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.67 | 0.00 |
July | 27746.18 | 21-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.72 | 0.00 |
August | 27506.96 | 16-AUG-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540.57 | 0.00 |
September | 24762.94 | 05-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 607.86 | 0.00 |
October | 20100.86 | 04-OCT-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.22 | 0.00 |
November | 15782.53 | 01-NOV-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.38 | 0.00 |
December | 11068.14 | 04-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9065.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.80 | 0.00 | |
Maximum of Months | 27746.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.67 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1869.69 | 01-JAN-17:23 | 35.07 | 52.77 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3769.00 | 05-FEB-17:20 | 23.38 | 35.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7202.03 | 31-MAR-23:35 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7669.21 | 23-APR-17:25 | 0.00 | 70.37 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3503.89 | 31-MAY-23:53 | 0.00 | 70.37 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5364.15 | 30-JUN-23:55 | 0.00 | 70.37 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7229.09 | 31-JUL-24:00 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7566.53 | 14-AUG-03:20 | 0.00 | 87.96 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3478.95 | 30-SEP-23:37 | 0.00 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5366.23 | 31-OCT-23:50 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5806.72 | 12-NOV-16:43 | 35.07 | 52.77 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7604.12 | 25-DEC-16:50 | 23.38 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1869.69 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7669.21 | 35.07 | 87.96 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1697.69 | 01-JAN-17:27 | 35.07 | 52.77 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3535.79 | 07-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6896.65 | 31-MAR-23:57 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7238.22 | 23-APR-17:32 | 0.00 | 87.96 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3399.89 | 31-MAY-23:53 | 0.00 | 70.37 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5182.29 | 30-JUN-23:55 | 0.00 | 70.37 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6877.05 | 31-JUL-24:00 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7090.37 | 15-AUG-08:20 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3352.14 | 30-SEP-23:27 | 0.00 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5181.09 | 31-OCT-23:53 | 0.00 | 52.77 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5407.08 | 06-NOV-17:00 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7160.27 | 06-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1697.69 | 0.00 | 52.77 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7238.22 | 222.14 | 316.63 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1701.40 | 31-JAN-17:00 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3599.31 | 06-FEB-16:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6821.48 | 31-MAR-23:57 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7489.02 | 23-APR-17:32 | 0.00 | 87.96 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3450.91 | 31-MAY-23:53 | 0.00 | 70.37 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5207.78 | 30-JUN-23:37 | 0.00 | 52.77 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7061.20 | 31-JUL-24:00 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7302.94 | 07-AUG-02:52 | 0.00 | 87.96 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3395.65 | 30-SEP-23:27 | 0.00 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5182.89 | 31-OCT-23:53 | 0.00 | 52.77 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5548.09 | 05-NOV-16:57 | 35.07 | 52.77 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7187.18 | 06-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1701.40 | 0.00 | 52.77 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7489.02 | 222.14 | 316.63 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 93233.27 | 02-JAN-17:00 | 4808.68 | 3708.62 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 184156.66 | 21-FEB-17:00 | 4808.68 | 3708.62 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 359272.27 | 31-MAR-24:00 | 0.00 | 618.16 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366831.34 | 24-APR-16:00 | 4808.68 | 3708.62 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176390.35 | 31-MAY-23:57 | 0.00 | 824.22 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268027.29 | 30-JUN-23:53 | 0.00 | 824.22 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360683.80 | 31-JUL-23:53 | 0.00 | 618.16 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369063.54 | 07-AUG-16:00 | 4808.68 | 3708.62 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 177328.55 | 30-SEP-23:53 | 0.00 | 618.16 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 269639.31 | 31-OCT-23:53 | 0.00 | 618.16 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277320.48 | 13-NOV-17:00 | 4808.68 | 3708.62 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 368572.85 | 26-DEC-17:00 | 4808.68 | 3708.62 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 93233.27 | 0.00 | 618.16 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369063.54 | 4808.68 | 3708.62 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.149943E+13 | 999923.30 | 30-JAN-16:30 | 0.502843E+11 | 68021.15 | 12-JAN-12:30 |
February | 0.172789E+13 | 1303075.74 | 07-FEB-16:19 | 0.447315E+11 | 67547.66 | 01-FEB-12:30 |
March | 0.238753E+13 | 1493145.01 | 27-MAR-15:20 | 0.491175E+11 | 65019.03 | 02-MAR-12:20 |
April | 0.273535E+13 | 1652229.59 | 28-APR-15:09 | 0.425320E+11 | 59787.95 | 03-APR-11:00 |
May | 0.186899E+13 | 1311235.54 | 31-MAY-15:00 | 0.417753E+11 | 53514.11 | 01-MAY-11:00 |
June | 0.235284E+13 | 1468490.93 | 12-JUN-15:09 | 0.387464E+11 | 46173.52 | 01-JUN-11:00 |
July | 0.288363E+13 | 1685218.75 | 19-JUL-15:09 | 0.374775E+11 | 42189.97 | 31-JUL-11:39 |
August | 0.338292E+13 | 1853330.76 | 10-AUG-15:00 | 0.405426E+11 | 47457.12 | 31-AUG-11:00 |
September | 0.196220E+13 | 1362109.33 | 08-SEP-15:09 | 0.400974E+11 | 53899.80 | 27-SEP-11:30 |
October | 0.223956E+13 | 1427467.55 | 06-OCT-15:39 | 0.445054E+11 | 61126.70 | 31-OCT-11:00 |
November | 0.238416E+13 | 1534985.44 | 01-NOV-15:09 | 0.463800E+11 | 64490.06 | 28-NOV-12:30 |
December | 0.268860E+13 | 1587815.26 | 05-DEC-16:00 | 0.488351E+11 | 67779.11 | 29-DEC-12:39 |
Annual Sum or Average | 0.281131E+14 | 0.525025E+12 | ||||
Minimum of Months | 0.149943E+13 | 999923.30 | 0.374775E+11 | 42189.97 | ||
Maximum of Months | 0.338292E+13 | 1853330.76 | 0.502843E+11 | 68021.15 |
Report: EnergyConsumptionDistrictHeatingCoolingMonthly
For: Meter
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportDISTRICTCOOLING:FACILITY [J] | DISTRICTCOOLING:FACILITY {Maximum} [W] | DISTRICTCOOLING:FACILITY {TIMESTAMP} | DISTRICTHEATING:FACILITY [J] | DISTRICTHEATING:FACILITY {Maximum} [W] | DISTRICTHEATING:FACILITY {TIMESTAMP} | |
January | 0.245127E+12 | 95916.01 | 02-JAN-14:00 | 134844.67 | 8.74 | 01-JAN-18:40 |
February | 0.441271E+12 | 186819.77 | 21-FEB-14:00 | 150237.85 | 13.41 | 01-FEB-00:40 |
March | 0.733085E+12 | 359272.31 | 31-MAR-23:00 | 99919.16 | 10.82 | 01-MAR-00:30 |
April | 0.945092E+12 | 369448.51 | 24-APR-13:00 | 51624.89 | 7.06 | 25-APR-23:19 |
May | 0.244247E+12 | 176391.16 | 31-MAY-23:00 | 12966.41 | 4.16 | 15-MAY-23:40 |
June | 0.473265E+12 | 268027.30 | 30-JUN-23:00 | 11454.16 | 1.70 | 30-JUN-23:19 |
July | 0.735665E+12 | 360683.80 | 31-JUL-23:00 | 15548.80 | 3.36 | 02-JUL-17:30 |
August | 0.982940E+12 | 371732.63 | 07-AUG-13:00 | 12911.32 | 1.22 | 30-AUG-23:10 |
September | 0.240222E+12 | 177328.55 | 30-SEP-23:00 | 2108.39 | 2.32 | 16-SEP-18:00 |
October | 0.492858E+12 | 269639.31 | 31-OCT-23:00 | 9295.74 | 1.70 | 31-OCT-23:19 |
November | 0.714212E+12 | 279990.26 | 13-NOV-14:00 | 52412.76 | 10.10 | 22-NOV-00:30 |
December | 0.982103E+12 | 371224.28 | 26-DEC-14:00 | 109353.26 | 14.06 | 01-DEC-00:30 |
Annual Sum or Average | 0.723009E+13 | 662677.41 | ||||
Minimum of Months | 0.240222E+12 | 95916.01 | 2108.39 | 1.22 | ||
Maximum of Months | 0.982940E+12 | 371732.63 | 150237.85 | 14.06 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.189134E+12 | 0.327125E+11 | 0.766053E+12 | 0.212953E+12 | 0.825013E+11 | 0.718745E+11 | 0.00 | 0.116365E+12 | 0.278328E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170711E+12 | 0.275493E+11 | 0.978954E+12 | 0.238272E+12 | 0.810923E+11 | 0.690630E+11 | 0.00 | 0.129213E+12 | 0.330343E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202117E+12 | 0.279257E+11 | 0.141687E+13 | 0.314872E+12 | 0.106243E+12 | 0.905586E+11 | 0.00 | 0.184615E+12 | 0.443279E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179871E+12 | 0.243961E+11 | 0.165903E+13 | 0.353464E+12 | 0.113606E+12 | 0.104830E+12 | 0.00 | 0.239271E+12 | 0.608852E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.193282E+12 | 0.230543E+11 | 0.774844E+12 | 0.213106E+12 | 0.143969E+12 | 0.119209E+12 | 0.00 | 0.309445E+12 | 0.920802E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.192017E+12 | 0.214780E+11 | 0.106252E+13 | 0.255495E+12 | 0.150250E+12 | 0.131899E+12 | 0.00 | 0.421446E+12 | 0.117733E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.180275E+12 | 0.226227E+11 | 0.139340E+13 | 0.314627E+12 | 0.158407E+12 | 0.144474E+12 | 0.00 | 0.540613E+12 | 0.129210E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.200789E+12 | 0.243829E+11 | 0.173200E+13 | 0.365439E+12 | 0.177440E+12 | 0.149114E+12 | 0.00 | 0.599619E+12 | 0.134136E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.180011E+12 | 0.257020E+11 | 0.740713E+12 | 0.206135E+12 | 0.144719E+12 | 0.129621E+12 | 0.00 | 0.417767E+12 | 0.117527E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187704E+12 | 0.292598E+11 | 0.108340E+13 | 0.263862E+12 | 0.136698E+12 | 0.119443E+12 | 0.00 | 0.322838E+12 | 0.963562E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.186534E+12 | 0.309614E+11 | 0.135889E+13 | 0.304533E+12 | 0.114366E+12 | 0.991247E+11 | 0.00 | 0.226585E+12 | 0.631681E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183471E+12 | 0.335024E+11 | 0.170972E+13 | 0.365400E+12 | 0.906487E+11 | 0.890836E+11 | 0.00 | 0.174664E+12 | 0.421080E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224592E+13 | 0.323547E+12 | 0.146764E+14 | 0.340816E+13 | 0.149994E+13 | 0.131830E+13 | 0.00 | 0.368244E+13 | 0.958399E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.170711E+12 | 0.214780E+11 | 0.740713E+12 | 0.206135E+12 | 0.810923E+11 | 0.690630E+11 | 0.00 | 0.116365E+12 | 0.278328E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.202117E+12 | 0.335024E+11 | 0.173200E+13 | 0.365439E+12 | 0.177440E+12 | 0.149114E+12 | 0.00 | 0.599619E+12 | 0.134136E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 13406096.78 | 0.00 | 0.502709E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 510835.62 | 0.00 | 0.447310E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.491175E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.425320E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.417753E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.387464E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.374775E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.405426E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.400974E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.445054E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.463800E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 8186.34 | 0.00 | 0.488351E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13925118.74 | 0.00 | 0.525011E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.374775E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 13406096.78 | 0.00 | 0.502709E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 206354.08 | 23-JAN-16:00 | 37611.08 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 135850.21 | 09-JAN-08:20 | 86185.49 | 02-JAN-14:30 | 65141.33 | 02-JAN-13:50 | 0.00 | 01-JAN-00:10 |
February | 208588.65 | 09-FEB-16:00 | 37611.08 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 154830.07 | 09-FEB-08:20 | 114355.21 | 06-FEB-14:00 | 65815.93 | 07-FEB-15:20 | 0.00 | 01-FEB-00:10 |
March | 215979.07 | 15-MAR-07:10 | 37611.08 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 173819.28 | 15-MAR-07:19 | 143972.84 | 27-MAR-15:20 | 68761.15 | 27-MAR-10:00 | 0.00 | 01-MAR-00:10 |
April | 208262.75 | 18-APR-07:10 | 37611.08 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 192796.84 | 18-APR-07:19 | 149720.94 | 28-APR-12:09 | 68545.08 | 28-APR-09:50 | 0.00 | 01-APR-00:10 |
May | 192517.36 | 23-MAY-07:10 | 37611.08 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 135843.64 | 23-MAY-07:19 | 153723.51 | 10-MAY-15:20 | 67639.50 | 08-MAY-10:09 | 0.00 | 01-MAY-00:10 |
June | 192724.77 | 08-JUN-07:10 | 37611.08 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 154825.38 | 08-JUN-07:19 | 168184.11 | 09-JUN-15:30 | 67552.60 | 16-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 202097.36 | 20-JUL-07:10 | 37611.08 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 173811.95 | 20-JUL-07:19 | 177806.59 | 21-JUL-15:20 | 69388.16 | 20-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 194996.03 | 29-AUG-07:10 | 37611.08 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 192789.84 | 29-AUG-07:19 | 178011.96 | 16-AUG-13:00 | 69964.47 | 30-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 195638.29 | 06-SEP-07:10 | 37611.08 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 135845.28 | 06-SEP-07:19 | 173231.86 | 05-SEP-15:20 | 68139.67 | 07-SEP-14:09 | 0.00 | 01-SEP-00:10 |
October | 198846.07 | 27-OCT-07:10 | 37611.08 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 154828.61 | 27-OCT-07:19 | 151056.30 | 04-OCT-14:50 | 67962.41 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 210774.81 | 29-NOV-16:00 | 37611.08 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 173810.43 | 29-NOV-08:20 | 135205.86 | 13-NOV-14:39 | 66535.00 | 01-NOV-13:50 | 0.00 | 01-NOV-00:10 |
December | 212940.11 | 15-DEC-16:00 | 37611.08 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 192798.69 | 15-DEC-08:20 | 107835.54 | 04-DEC-13:09 | 65864.10 | 05-DEC-14:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 192517.36 | 37611.08 | 423497.50 | 135843.64 | 86185.49 | 65141.33 | 0.00 | |||||||
Maximum of Months | 215979.07 | 37611.08 | 778371.69 | 192798.69 | 178011.96 | 69964.47 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 114331.09 | 30-JAN-06:10 | 33048.85 | 09-JAN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 237000.05 | 07-FEB-15:20 | 53621.47 | 06-FEB-18:10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254880.86 | 27-MAR-10:00 | 53621.47 | 01-MAR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 262870.52 | 26-APR-12:39 | 53621.47 | 03-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 327948.54 | 31-MAY-15:00 | 53621.47 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 344767.14 | 12-JUN-14:39 | 53621.47 | 01-JUN-07:49 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 416836.04 | 19-JUL-14:00 | 53621.47 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 427273.83 | 10-AUG-15:00 | 53621.47 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 378255.07 | 07-SEP-13:00 | 53621.47 | 01-SEP-03:39 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 315462.69 | 06-OCT-15:00 | 53621.47 | 01-OCT-00:40 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 302565.87 | 01-NOV-13:00 | 53621.47 | 01-NOV-05:30 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 247245.65 | 05-DEC-15:09 | 53621.47 | 04-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 114331.09 | 33048.85 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 427273.83 | 53621.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 999923.30 | 30-JAN-16:30 | 197438.39 | 423497.50 | 0.00 | 101802.39 | 69314.36 | 64919.22 | 0.00 | 109902.59 | 33048.85 |
February | 1303075.74 | 07-FEB-16:19 | 191516.36 | 541788.89 | 0.00 | 120781.24 | 98741.81 | 65697.02 | 0.00 | 230928.94 | 53621.47 |
March | 1493145.01 | 27-MAR-15:20 | 190262.14 | 660080.29 | 0.00 | 139762.32 | 143972.84 | 66703.23 | 0.00 | 238742.72 | 53621.47 |
April | 1652229.59 | 28-APR-15:09 | 190262.14 | 778371.69 | 0.00 | 158743.95 | 147826.63 | 65917.58 | 0.00 | 257486.13 | 53621.47 |
May | 1311235.54 | 31-MAY-15:00 | 190262.14 | 423497.50 | 0.00 | 101799.06 | 146987.06 | 67119.77 | 0.00 | 327948.54 | 53621.47 |
June | 1468490.93 | 12-JUN-15:09 | 190262.14 | 541788.89 | 0.00 | 120780.69 | 151626.40 | 67325.29 | 0.00 | 343086.04 | 53621.47 |
July | 1685218.75 | 19-JUL-15:09 | 190262.14 | 660080.29 | 0.00 | 139762.32 | 157650.05 | 68707.09 | 0.00 | 415135.39 | 53621.47 |
August | 1853330.76 | 10-AUG-15:00 | 190262.14 | 778371.69 | 0.00 | 158743.95 | 176082.30 | 68975.38 | 0.00 | 427273.83 | 53621.47 |
September | 1362109.33 | 08-SEP-15:09 | 190262.14 | 423497.50 | 0.00 | 101799.06 | 149108.77 | 68099.40 | 0.00 | 375721.00 | 53621.47 |
October | 1427467.55 | 06-OCT-15:39 | 190262.14 | 541788.89 | 0.00 | 120780.69 | 140475.72 | 66789.92 | 0.00 | 313748.72 | 53621.47 |
November | 1534985.44 | 01-NOV-15:09 | 190262.14 | 660080.29 | 0.00 | 139762.32 | 128493.53 | 66441.07 | 0.00 | 296324.61 | 53621.47 |
December | 1587815.26 | 05-DEC-16:00 | 202792.47 | 778371.69 | 0.00 | 158748.44 | 88573.56 | 65711.04 | 0.00 | 239996.59 | 53621.47 |
Annual Sum or Average | |||||||||||
Minimum of Months | 999923.30 | 190262.14 | 423497.50 | 0.00 | 101799.06 | 69314.36 | 64919.22 | 0.00 | 109902.59 | 33048.85 | |
Maximum of Months | 1853330.76 | 202792.47 | 778371.69 | 0.00 | 158748.44 | 176082.30 | 68975.38 | 0.00 | 427273.83 | 53621.47 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1006.91 | 20-JAN-06:00 | 0.00 | 68021.15 | 12-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 199.17 | 13-FEB-06:49 | 0.00 | 67547.66 | 01-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 65019.03 | 02-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 59787.95 | 03-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 53514.11 | 01-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 46173.52 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 42189.97 | 31-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 47457.12 | 31-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 53899.80 | 27-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 61126.70 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 64490.06 | 28-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 13.64 | 18-DEC-06:00 | 0.00 | 67779.11 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 42189.97 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1006.91 | 0.00 | 68021.15 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 26.88 | 1.50 | 26.90 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 26.66 | 1.50 | 26.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.19 | 0.17 | 26.14 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.26 | 0.00 | 26.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.26 | 0.33 | 26.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 26.66 | 0.00 | 26.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.23 | 0.00 | 26.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 25.89 | 0.33 | 25.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 26.35 | 0.33 | 26.38 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.11 | 0.50 | 26.17 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 26.27 | 0.83 | 26.27 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 26.60 | 1.50 | 26.67 |
Annual Sum or Average | 0.00 | 0.00 | 120.67 | 26.42 | 7.00 | 26.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 25.89 | 0.00 | 25.93 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 26.88 | 1.50 | 26.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 25.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.59 | 0.00 | 25.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.65 | 0.00 | 25.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 25.62 | 0.00 | 25.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.65 | 0.00 | 25.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 26.91 | 4.67 | 27.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 26.80 | 6.00 | 27.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 27.06 | 12.67 | 27.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 26.92 | 9.00 | 27.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 26.92 | 5.33 | 27.12 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.66 | 1.33 | 26.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 92.00 | 26.94 | 39.00 | 27.13 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 27.06 | 12.67 | 27.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.17 | 27.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.44 | 1.50 | 27.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.40 | 11.00 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.27 | 9.17 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 27.28 | 13.83 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 26.94 | 9.67 | 27.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.33 | 11.17 | 27.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.29 | 6.33 | 27.37 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 95.83 | 27.23 | 62.83 | 27.40 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 27.44 | 13.83 | 27.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.52 | 2.17 | 27.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.56 | 1.50 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.25 | 3.33 | 27.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.02 | 5.67 | 27.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 26.86 | 5.67 | 27.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 27.05 | 11.50 | 27.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 26.97 | 9.00 | 27.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.13 | 9.50 | 27.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.34 | 11.33 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.58 | 9.67 | 27.62 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.55 | 3.83 | 27.55 |
Annual Sum or Average | 0.00 | 0.00 | 131.33 | 27.14 | 73.33 | 27.32 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.86 | 0.17 | 27.07 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 27.58 | 11.50 | 27.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 26.95 | 2.67 | 27.16 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 26.86 | 5.00 | 27.04 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 27.28 | 10.83 | 27.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 27.09 | 9.50 | 27.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 33.33 | 27.27 | 9.33 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 81.67 | 27.64 | 24.17 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 81.50 | 27.76 | 23.67 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 | 27.15 | 10.00 | 27.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 27.10 | 11.17 | 27.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 26.99 | 10.50 | 27.21 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 26.86 | 8.33 | 27.05 |
Annual Sum or Average | 0.00 | 0.00 | 386.33 | 27.35 | 125.33 | 27.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.86 | 0.17 | 27.04 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 81.67 | 27.76 | 24.17 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.22 | 6.33 | 27.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 26.95 | 6.67 | 27.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 27.06 | 10.67 | 27.25 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 26.82 | 7.50 | 27.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.01 | 5.67 | 27.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.22 | 1.17 | 27.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 77.17 | 26.99 | 38.00 | 27.19 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 27.22 | 10.67 | 27.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.36 | 0.33 | 27.36 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.49 | 5.33 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.56 | 11.33 | 27.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.30 | 9.17 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 27.34 | 14.00 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 27.03 | 9.33 | 27.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.38 | 11.33 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.44 | 9.17 | 27.47 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 109.67 | 27.32 | 70.00 | 27.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 27.56 | 14.00 | 27.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.66 | 1.33 | 27.66 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.56 | 1.33 | 27.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.41 | 3.00 | 27.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.21 | 6.33 | 27.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 26.98 | 5.67 | 27.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 27.06 | 10.50 | 27.25 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 26.88 | 7.67 | 27.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.11 | 9.50 | 27.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.42 | 11.00 | 27.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.63 | 9.00 | 27.66 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.62 | 2.17 | 27.62 |
Annual Sum or Average | 0.00 | 0.00 | 112.83 | 27.17 | 67.50 | 27.36 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 27.66 | 11.00 | 27.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.18 | 0.67 | 27.38 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.41 | 3.83 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.34 | 7.17 | 27.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 27.01 | 7.17 | 27.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 27.30 | 12.17 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 27.20 | 9.00 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 27.18 | 8.17 | 27.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.27 | 5.83 | 27.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.50 | 2.17 | 27.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 145.67 | 27.23 | 56.17 | 27.42 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 27.50 | 12.17 | 27.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.41 | 1.83 | 27.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.46 | 8.67 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 27.18 | 8.33 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 | 27.34 | 13.00 | 27.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 27.15 | 9.17 | 27.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.29 | 8.67 | 27.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.41 | 4.83 | 27.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 128.50 | 27.28 | 54.50 | 27.44 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 | 27.46 | 13.00 | 27.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.41 | 1.33 | 27.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.60 | 7.67 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.71 | 11.67 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.43 | 9.83 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 | 27.50 | 14.83 | 27.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 27.31 | 10.17 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.55 | 11.50 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.58 | 11.67 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.50 | 27.32 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 156.83 | 27.50 | 79.17 | 27.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 | 27.71 | 14.83 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.68 | 1.50 | 27.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.52 | 1.33 | 27.64 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.55 | 4.83 | 27.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.53 | 8.50 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.21 | 7.17 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 27.35 | 12.17 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 27.19 | 9.00 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 27.38 | 10.17 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.62 | 11.17 | 27.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.76 | 8.33 | 27.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.57 | 1.83 | 27.57 |
Annual Sum or Average | 0.00 | 0.00 | 152.33 | 27.39 | 76.00 | 27.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 27.76 | 12.17 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.34 | 0.33 | 27.34 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.60 | 0.83 | 27.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.75 | 5.17 | 27.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 27.68 | 8.83 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 27.29 | 8.17 | 27.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 27.55 | 13.17 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 | 27.42 | 10.83 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 27.45 | 9.67 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.63 | 7.33 | 27.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.61 | 2.67 | 27.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 178.17 | 27.50 | 67.00 | 27.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 27.75 | 13.17 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.06 | 8.50 | 28.06 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 476.33 | 28.19 | 373.33 | 28.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 484.83 | 28.18 | 381.83 | 28.22 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 476.33 | 28.19 | 373.33 | 28.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.96 | 12.83 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 454.33 | 28.19 | 374.33 | 28.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 467.17 | 28.19 | 387.17 | 28.22 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 454.33 | 28.19 | 374.33 | 28.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.85 | 5.50 | 27.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 317.17 | 28.22 | 278.00 | 28.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 322.67 | 28.21 | 283.50 | 28.22 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 317.17 | 28.22 | 278.00 | 28.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 25.06 | 448.67 | 24.75 | 1.50 | 24.75 |
February | 50.83 | 25.17 | 433.33 | 24.72 | 50.83 | 24.77 |
March | 60.17 | 24.64 | 474.33 | 24.58 | 60.17 | 24.58 |
April | 141.17 | 25.15 | 442.00 | 24.78 | 141.17 | 24.85 |
May | 174.83 | 24.84 | 482.50 | 24.68 | 174.83 | 24.71 |
June | 301.67 | 24.91 | 494.17 | 24.69 | 301.67 | 24.75 |
July | 246.33 | 25.12 | 497.00 | 24.84 | 246.33 | 24.91 |
August | 225.67 | 25.27 | 514.00 | 24.78 | 225.67 | 24.89 |
September | 248.67 | 25.26 | 485.00 | 24.85 | 248.67 | 24.96 |
October | 135.33 | 25.51 | 490.17 | 24.89 | 135.33 | 25.00 |
November | 86.00 | 25.35 | 484.50 | 24.80 | 86.00 | 24.87 |
December | 78.50 | 25.95 | 484.50 | 24.89 | 78.50 | 25.02 |
Annual Sum or Average | 1750.67 | 25.16 | 5730.17 | 24.77 | 1750.67 | 24.85 |
Minimum of Months | 1.50 | 24.64 | 433.33 | 24.58 | 1.50 | 24.58 |
Maximum of Months | 301.67 | 25.95 | 514.00 | 24.89 | 301.67 | 25.02 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 23.67 | 434.33 | 24.44 | 0.00 | 24.44 |
February | 0.00 | 0.00 | 427.83 | 24.41 | 0.00 | 24.41 |
March | 0.00 | 0.00 | 476.50 | 24.28 | 0.00 | 24.28 |
April | 0.00 | 0.00 | 462.83 | 24.21 | 0.00 | 24.21 |
May | 0.00 | 0.00 | 486.50 | 24.19 | 0.00 | 24.19 |
June | 0.00 | 0.00 | 496.00 | 24.15 | 0.00 | 24.15 |
July | 0.00 | 0.00 | 497.00 | 24.22 | 0.00 | 24.22 |
August | 0.00 | 0.00 | 514.00 | 24.21 | 0.00 | 24.21 |
September | 0.00 | 0.00 | 485.00 | 24.20 | 0.00 | 24.20 |
October | 0.00 | 0.00 | 489.33 | 24.25 | 0.00 | 24.25 |
November | 0.00 | 0.00 | 483.00 | 24.31 | 0.00 | 24.31 |
December | 0.00 | 0.00 | 478.50 | 24.34 | 0.00 | 24.34 |
Annual Sum or Average | 1.00 | 23.67 | 5730.83 | 24.26 | 0.00 | 24.26 |
Minimum of Months | 0.00 | 0.00 | 427.83 | 24.15 | 0.00 | 24.15 |
Maximum of Months | 1.00 | 23.67 | 514.00 | 24.44 | 0.00 | 24.44 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 36.33 | 23.40 | 316.50 | 24.24 | 0.00 | 24.24 |
February | 16.33 | 23.37 | 364.83 | 24.23 | 0.00 | 24.23 |
March | 6.33 | 23.39 | 388.33 | 24.26 | 0.00 | 24.26 |
April | 5.33 | 23.61 | 412.33 | 24.21 | 0.00 | 24.21 |
May | 1.00 | 23.79 | 467.83 | 24.13 | 0.00 | 24.13 |
June | 0.00 | 0.00 | 491.17 | 24.05 | 0.00 | 24.05 |
July | 0.00 | 0.00 | 488.67 | 24.02 | 0.00 | 24.02 |
August | 0.00 | 0.00 | 514.00 | 24.02 | 0.00 | 24.02 |
September | 0.00 | 0.00 | 485.00 | 24.09 | 0.00 | 24.09 |
October | 5.17 | 23.74 | 474.33 | 24.21 | 0.00 | 24.21 |
November | 4.00 | 23.63 | 471.67 | 24.23 | 0.00 | 24.23 |
December | 15.00 | 23.36 | 403.67 | 24.20 | 0.00 | 24.20 |
Annual Sum or Average | 89.50 | 23.43 | 5278.33 | 24.15 | 0.00 | 24.15 |
Minimum of Months | 0.00 | 0.00 | 316.50 | 24.02 | 0.00 | 24.02 |
Maximum of Months | 36.33 | 23.79 | 514.00 | 24.26 | 0.00 | 24.26 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 204.83 | 23.12 | 196.00 | 23.58 | 13.33 | 23.58 |
February | 103.00 | 23.12 | 266.33 | 23.88 | 0.00 | 23.88 |
March | 52.17 | 23.25 | 359.33 | 24.09 | 0.00 | 24.09 |
April | 0.67 | 23.65 | 415.67 | 24.24 | 0.00 | 24.24 |
May | 0.00 | 0.00 | 484.50 | 24.21 | 0.00 | 24.21 |
June | 0.00 | 0.00 | 494.67 | 24.15 | 0.00 | 24.15 |
July | 0.00 | 0.00 | 496.67 | 24.19 | 0.00 | 24.19 |
August | 0.00 | 0.00 | 514.00 | 24.16 | 0.00 | 24.16 |
September | 0.00 | 0.00 | 485.00 | 24.18 | 0.00 | 24.18 |
October | 0.00 | 0.00 | 483.83 | 24.26 | 0.00 | 24.26 |
November | 4.17 | 23.52 | 455.17 | 24.18 | 0.00 | 24.18 |
December | 116.33 | 23.09 | 291.67 | 23.82 | 0.00 | 23.82 |
Annual Sum or Average | 481.17 | 23.13 | 4942.83 | 24.09 | 13.33 | 24.09 |
Minimum of Months | 0.00 | 0.00 | 196.00 | 23.58 | 0.00 | 23.58 |
Maximum of Months | 204.83 | 23.65 | 514.00 | 24.26 | 13.33 | 24.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 63.67 | 23.41 | 294.00 | 24.15 | 0.00 | 24.15 |
February | 16.67 | 23.47 | 372.17 | 24.29 | 0.00 | 24.29 |
March | 4.17 | 23.60 | 446.83 | 24.28 | 0.00 | 24.28 |
April | 3.67 | 26.64 | 469.67 | 24.40 | 3.67 | 24.42 |
May | 26.33 | 26.78 | 505.17 | 24.63 | 26.33 | 24.73 |
June | 34.17 | 26.76 | 496.00 | 24.63 | 34.17 | 24.76 |
July | 59.83 | 26.85 | 497.00 | 24.88 | 59.83 | 25.07 |
August | 44.50 | 26.86 | 514.00 | 24.71 | 44.50 | 24.87 |
September | 37.17 | 26.72 | 485.00 | 24.69 | 37.17 | 24.82 |
October | 20.67 | 26.60 | 496.00 | 24.58 | 20.67 | 24.66 |
November | 0.00 | 0.00 | 483.83 | 24.37 | 0.00 | 24.37 |
December | 6.50 | 23.57 | 428.33 | 24.25 | 0.00 | 24.25 |
Annual Sum or Average | 317.33 | 25.82 | 5488.00 | 24.52 | 226.33 | 24.60 |
Minimum of Months | 0.00 | 0.00 | 294.00 | 24.15 | 0.00 | 24.15 |
Maximum of Months | 63.67 | 26.86 | 514.00 | 24.88 | 59.83 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 66.83 | 23.31 | 312.50 | 24.17 | 0.50 | 24.18 |
February | 27.00 | 23.34 | 367.83 | 24.26 | 0.67 | 24.26 |
March | 20.00 | 23.48 | 432.17 | 24.22 | 0.67 | 24.23 |
April | 11.67 | 26.51 | 459.50 | 24.42 | 10.83 | 24.47 |
May | 47.33 | 26.83 | 507.17 | 24.73 | 47.33 | 24.89 |
June | 37.67 | 26.80 | 496.00 | 24.62 | 37.67 | 24.77 |
July | 59.00 | 26.92 | 497.00 | 24.86 | 59.00 | 25.06 |
August | 42.33 | 26.89 | 514.00 | 24.67 | 42.33 | 24.83 |
September | 48.83 | 26.82 | 485.00 | 24.75 | 48.83 | 24.93 |
October | 38.17 | 26.74 | 497.50 | 24.67 | 38.17 | 24.81 |
November | 1.00 | 25.11 | 480.33 | 24.35 | 0.50 | 24.35 |
December | 32.00 | 23.24 | 392.50 | 24.11 | 0.00 | 24.11 |
Annual Sum or Average | 431.83 | 25.64 | 5441.50 | 24.52 | 286.50 | 24.62 |
Minimum of Months | 1.00 | 23.24 | 312.50 | 24.11 | 0.00 | 24.11 |
Maximum of Months | 66.83 | 26.92 | 514.00 | 24.86 | 59.00 | 25.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.17 | 23.81 | 382.00 | 24.42 | 6.00 | 24.45 |
February | 23.67 | 24.95 | 404.33 | 24.48 | 10.50 | 24.54 |
March | 13.83 | 25.40 | 464.00 | 24.40 | 7.67 | 24.44 |
April | 17.83 | 26.79 | 470.83 | 24.52 | 17.83 | 24.60 |
May | 29.00 | 26.77 | 505.50 | 24.63 | 29.00 | 24.74 |
June | 28.50 | 26.73 | 496.00 | 24.58 | 28.50 | 24.69 |
July | 53.50 | 26.86 | 497.00 | 24.84 | 53.50 | 25.02 |
August | 44.67 | 26.88 | 514.00 | 24.72 | 44.67 | 24.88 |
September | 43.17 | 26.87 | 485.00 | 24.77 | 43.17 | 24.93 |
October | 51.50 | 26.89 | 502.00 | 24.83 | 51.50 | 25.01 |
November | 43.83 | 26.87 | 488.00 | 24.75 | 43.83 | 24.91 |
December | 25.50 | 26.14 | 462.33 | 24.54 | 20.17 | 24.63 |
Annual Sum or Average | 416.17 | 26.35 | 5671.00 | 24.63 | 356.33 | 24.76 |
Minimum of Months | 13.83 | 23.81 | 382.00 | 24.40 | 6.00 | 24.44 |
Maximum of Months | 53.50 | 26.89 | 514.00 | 24.84 | 53.50 | 25.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.67 | 23.93 | 412.67 | 24.49 | 2.00 | 24.50 |
February | 23.50 | 26.92 | 446.50 | 24.70 | 23.50 | 24.81 |
March | 32.67 | 26.96 | 508.83 | 24.70 | 32.67 | 24.83 |
April | 72.00 | 26.84 | 485.00 | 24.92 | 72.00 | 25.14 |
May | 61.67 | 26.88 | 508.00 | 24.85 | 61.67 | 25.05 |
June | 71.67 | 26.76 | 496.00 | 24.84 | 71.67 | 25.06 |
July | 119.00 | 26.85 | 497.00 | 25.15 | 119.00 | 25.43 |
August | 103.67 | 26.92 | 514.00 | 25.02 | 103.67 | 25.30 |
September | 71.33 | 26.81 | 485.00 | 24.90 | 71.33 | 25.12 |
October | 74.00 | 26.85 | 502.00 | 24.94 | 74.00 | 25.16 |
November | 62.33 | 26.88 | 489.00 | 24.91 | 62.33 | 25.11 |
December | 50.50 | 26.86 | 497.00 | 24.86 | 50.50 | 25.03 |
Annual Sum or Average | 755.00 | 26.81 | 5841.00 | 24.87 | 744.33 | 25.07 |
Minimum of Months | 12.67 | 23.93 | 412.67 | 24.49 | 2.00 | 24.50 |
Maximum of Months | 119.00 | 26.96 | 514.00 | 25.15 | 119.00 | 25.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 247.33 | 23.12 | 133.17 | 23.45 | 0.00 | 23.45 |
February | 122.83 | 23.17 | 227.33 | 23.81 | 1.00 | 23.82 |
March | 54.00 | 23.28 | 351.50 | 24.11 | 0.00 | 24.11 |
April | 23.00 | 25.41 | 442.50 | 24.46 | 20.17 | 24.52 |
May | 34.83 | 26.71 | 503.17 | 24.70 | 34.83 | 24.82 |
June | 52.67 | 26.52 | 496.00 | 24.71 | 52.67 | 24.87 |
July | 82.33 | 26.63 | 497.00 | 24.94 | 82.33 | 25.15 |
August | 63.50 | 26.55 | 514.00 | 24.75 | 63.50 | 24.93 |
September | 64.50 | 26.46 | 485.00 | 24.78 | 64.50 | 24.96 |
October | 42.00 | 26.19 | 491.00 | 24.67 | 42.00 | 24.78 |
November | 4.33 | 24.48 | 461.00 | 24.31 | 1.83 | 24.32 |
December | 137.67 | 23.21 | 268.67 | 23.81 | 8.00 | 23.82 |
Annual Sum or Average | 929.00 | 24.45 | 4870.33 | 24.45 | 370.83 | 24.56 |
Minimum of Months | 4.33 | 23.12 | 133.17 | 23.45 | 0.00 | 23.45 |
Maximum of Months | 247.33 | 26.71 | 514.00 | 24.94 | 82.33 | 25.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 168.67 | 23.04 | 147.67 | 23.63 | 0.00 | 23.63 |
February | 81.00 | 23.02 | 225.00 | 24.00 | 1.00 | 24.01 |
March | 46.33 | 23.33 | 313.00 | 24.25 | 2.33 | 24.27 |
April | 39.50 | 26.25 | 386.00 | 24.75 | 35.83 | 24.89 |
May | 55.33 | 26.85 | 429.50 | 24.94 | 55.33 | 25.13 |
June | 55.50 | 26.65 | 418.00 | 24.86 | 55.50 | 25.05 |
July | 86.00 | 26.73 | 422.00 | 25.12 | 86.00 | 25.35 |
August | 62.50 | 26.67 | 433.00 | 24.90 | 62.50 | 25.09 |
September | 66.83 | 26.70 | 410.00 | 24.98 | 66.83 | 25.19 |
October | 59.83 | 26.66 | 424.00 | 24.95 | 59.83 | 25.14 |
November | 6.83 | 26.01 | 399.50 | 24.51 | 5.50 | 24.54 |
December | 102.50 | 23.18 | 245.50 | 23.93 | 7.33 | 23.94 |
Annual Sum or Average | 830.83 | 24.95 | 4253.17 | 24.65 | 438.00 | 24.81 |
Minimum of Months | 6.83 | 23.02 | 147.67 | 23.63 | 0.00 | 23.63 |
Maximum of Months | 168.67 | 26.85 | 433.00 | 25.12 | 86.00 | 25.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 85.17 | 23.50 | 337.00 | 24.27 | 6.50 | 24.31 |
February | 52.50 | 23.74 | 372.67 | 24.31 | 8.67 | 24.36 |
March | 30.50 | 23.97 | 423.67 | 24.35 | 5.83 | 24.38 |
April | 29.67 | 26.05 | 454.50 | 24.58 | 28.33 | 24.67 |
May | 36.17 | 26.69 | 503.17 | 24.69 | 36.17 | 24.81 |
June | 48.33 | 26.40 | 496.00 | 24.66 | 48.33 | 24.80 |
July | 80.50 | 26.56 | 497.00 | 24.91 | 80.50 | 25.11 |
August | 62.67 | 26.60 | 514.00 | 24.76 | 62.67 | 24.94 |
September | 68.00 | 26.69 | 485.00 | 24.88 | 68.00 | 25.07 |
October | 70.17 | 26.82 | 502.00 | 24.94 | 70.17 | 25.15 |
November | 44.67 | 26.88 | 486.17 | 24.78 | 44.67 | 24.94 |
December | 62.67 | 24.68 | 412.00 | 24.50 | 27.83 | 24.61 |
Annual Sum or Average | 671.00 | 25.70 | 5483.17 | 24.66 | 487.67 | 24.80 |
Minimum of Months | 29.67 | 23.50 | 337.00 | 24.27 | 5.83 | 24.31 |
Maximum of Months | 85.17 | 26.88 | 514.00 | 24.94 | 80.50 | 25.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 175.33 | 23.04 | 217.17 | 23.71 | 0.00 | 23.71 |
February | 72.50 | 23.08 | 312.83 | 24.07 | 1.33 | 24.07 |
March | 31.67 | 23.64 | 418.67 | 24.33 | 3.83 | 24.35 |
April | 35.00 | 26.53 | 463.33 | 24.68 | 35.00 | 24.80 |
May | 51.50 | 26.90 | 506.83 | 24.82 | 51.50 | 24.99 |
June | 64.33 | 26.77 | 496.00 | 24.81 | 64.33 | 25.01 |
July | 93.83 | 26.75 | 497.00 | 25.02 | 93.83 | 25.26 |
August | 76.83 | 26.78 | 514.00 | 24.86 | 76.83 | 25.08 |
September | 77.67 | 26.72 | 485.00 | 24.91 | 77.67 | 25.13 |
October | 54.67 | 26.67 | 496.83 | 24.83 | 54.67 | 25.00 |
November | 13.83 | 26.38 | 479.67 | 24.50 | 12.33 | 24.55 |
December | 82.83 | 23.25 | 346.67 | 24.08 | 7.00 | 24.09 |
Annual Sum or Average | 830.00 | 25.17 | 5234.00 | 24.61 | 478.33 | 24.76 |
Minimum of Months | 13.83 | 23.04 | 217.17 | 23.71 | 0.00 | 23.71 |
Maximum of Months | 175.33 | 26.90 | 514.00 | 25.02 | 93.83 | 25.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 361.17 | 22.55 | 83.00 | 22.82 | 0.00 | 22.82 |
February | 213.00 | 22.73 | 171.50 | 23.35 | 1.50 | 23.35 |
March | 118.50 | 23.01 | 312.83 | 23.89 | 0.00 | 23.89 |
April | 41.17 | 24.64 | 423.17 | 24.46 | 24.33 | 24.52 |
May | 44.50 | 26.76 | 503.67 | 24.75 | 44.50 | 24.90 |
June | 61.00 | 26.58 | 496.00 | 24.76 | 61.00 | 24.94 |
July | 90.83 | 26.71 | 497.00 | 25.00 | 90.83 | 25.23 |
August | 72.00 | 26.64 | 514.00 | 24.81 | 72.00 | 25.01 |
September | 69.17 | 26.51 | 485.00 | 24.81 | 69.17 | 25.00 |
October | 54.00 | 26.29 | 491.00 | 24.71 | 54.00 | 24.86 |
November | 30.50 | 23.47 | 419.17 | 24.24 | 4.17 | 24.25 |
December | 235.83 | 22.73 | 191.83 | 23.31 | 14.17 | 23.32 |
Annual Sum or Average | 1391.67 | 23.86 | 4588.17 | 24.32 | 435.67 | 24.47 |
Minimum of Months | 30.50 | 22.55 | 83.00 | 22.82 | 0.00 | 22.82 |
Maximum of Months | 361.17 | 26.76 | 514.00 | 25.00 | 90.83 | 25.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 287.33 | 22.67 | 134.83 | 23.14 | 0.00 | 23.14 |
February | 149.83 | 22.74 | 231.33 | 23.65 | 1.33 | 23.65 |
March | 88.50 | 23.15 | 360.33 | 24.07 | 3.83 | 24.09 |
April | 62.00 | 25.82 | 447.67 | 24.68 | 49.17 | 24.85 |
May | 57.50 | 26.91 | 507.17 | 24.84 | 57.50 | 25.03 |
June | 63.83 | 26.71 | 496.00 | 24.79 | 63.83 | 24.99 |
July | 95.33 | 26.79 | 497.00 | 25.04 | 95.33 | 25.28 |
August | 73.00 | 26.75 | 514.00 | 24.84 | 73.00 | 25.05 |
September | 72.17 | 26.74 | 485.00 | 24.88 | 72.17 | 25.10 |
October | 66.67 | 26.68 | 496.83 | 24.86 | 66.67 | 25.05 |
November | 22.17 | 24.48 | 448.50 | 24.40 | 9.50 | 24.44 |
December | 187.17 | 22.83 | 238.17 | 23.55 | 13.17 | 23.56 |
Annual Sum or Average | 1225.50 | 24.36 | 4856.83 | 24.47 | 505.50 | 24.64 |
Minimum of Months | 22.17 | 22.67 | 134.83 | 23.14 | 0.00 | 23.14 |
Maximum of Months | 287.33 | 26.91 | 514.00 | 25.04 | 95.33 | 25.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 170.83 | 22.85 | 257.67 | 23.79 | 5.17 | 23.83 |
February | 101.00 | 23.07 | 311.00 | 24.04 | 8.83 | 24.09 |
March | 75.33 | 23.39 | 380.50 | 24.19 | 7.33 | 24.23 |
April | 52.50 | 25.33 | 433.33 | 24.58 | 37.67 | 24.70 |
May | 41.33 | 26.77 | 502.83 | 24.72 | 41.33 | 24.86 |
June | 55.00 | 26.47 | 496.00 | 24.70 | 55.00 | 24.86 |
July | 88.67 | 26.63 | 497.00 | 24.96 | 88.67 | 25.18 |
August | 70.67 | 26.65 | 514.00 | 24.81 | 70.67 | 25.01 |
September | 74.17 | 26.71 | 485.00 | 24.90 | 74.17 | 25.11 |
October | 74.67 | 26.81 | 500.67 | 24.96 | 74.67 | 25.17 |
November | 49.00 | 26.46 | 472.67 | 24.73 | 44.17 | 24.89 |
December | 115.17 | 23.60 | 350.83 | 24.21 | 27.50 | 24.32 |
Annual Sum or Average | 968.33 | 24.92 | 5201.50 | 24.59 | 535.17 | 24.75 |
Minimum of Months | 41.33 | 22.85 | 257.67 | 23.79 | 5.17 | 23.83 |
Maximum of Months | 170.83 | 26.81 | 514.00 | 24.96 | 88.67 | 25.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 288.00 | 22.56 | 136.50 | 23.11 | 0.00 | 23.11 |
February | 146.50 | 22.71 | 243.17 | 23.67 | 2.33 | 23.69 |
March | 79.67 | 23.21 | 369.00 | 24.15 | 5.50 | 24.18 |
April | 51.83 | 25.65 | 444.50 | 24.66 | 40.00 | 24.79 |
May | 57.67 | 26.91 | 506.50 | 24.84 | 57.67 | 25.03 |
June | 68.17 | 26.77 | 496.00 | 24.82 | 68.17 | 25.03 |
July | 99.83 | 26.77 | 497.00 | 25.04 | 99.83 | 25.29 |
August | 85.00 | 26.74 | 514.00 | 24.88 | 85.00 | 25.11 |
September | 80.00 | 26.72 | 485.00 | 24.91 | 80.00 | 25.14 |
October | 62.67 | 26.64 | 494.17 | 24.85 | 62.67 | 25.03 |
November | 25.67 | 25.13 | 452.83 | 24.45 | 14.83 | 24.51 |
December | 170.83 | 22.84 | 269.33 | 23.69 | 12.00 | 23.71 |
Annual Sum or Average | 1215.83 | 24.41 | 4908.00 | 24.50 | 528.00 | 24.67 |
Minimum of Months | 25.67 | 22.56 | 136.50 | 23.11 | 0.00 | 23.11 |
Maximum of Months | 288.00 | 26.91 | 514.00 | 25.04 | 99.83 | 25.29 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 3.83 | 27.00 | 514.00 | 27.00 | 3.83 | 27.00 |
April | 122.83 | 27.12 | 485.00 | 27.05 | 122.83 | 27.06 |
May | 3.67 | 27.00 | 508.00 | 27.00 | 3.67 | 27.00 |
June | 38.00 | 27.00 | 496.00 | 27.00 | 38.00 | 27.00 |
July | 272.50 | 27.00 | 497.00 | 27.00 | 272.50 | 27.00 |
August | 490.50 | 28.02 | 514.00 | 28.00 | 490.50 | 28.01 |
September | 21.50 | 27.00 | 485.00 | 27.00 | 21.50 | 27.00 |
October | 16.17 | 27.00 | 502.00 | 27.00 | 16.17 | 27.00 |
November | 27.33 | 27.00 | 489.00 | 27.00 | 27.33 | 27.00 |
December | 41.83 | 27.00 | 497.00 | 27.00 | 41.83 | 27.00 |
Annual Sum or Average | 1038.17 | 27.50 | 5943.00 | 27.15 | 1038.17 | 27.19 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 490.50 | 28.02 | 514.00 | 28.00 | 490.50 | 28.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 16.33 | 27.80 | 485.00 | 27.06 | 16.33 | 27.08 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 0.00 | 0.00 | 496.00 | 27.00 | 0.00 | 27.00 |
July | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
August | 377.50 | 28.26 | 514.00 | 28.09 | 377.50 | 28.14 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 393.83 | 28.24 | 5943.00 | 27.16 | 393.83 | 27.22 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 377.50 | 28.26 | 514.00 | 28.09 | 377.50 | 28.14 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 20.67 | 27.32 | 485.00 | 27.03 | 20.67 | 27.04 |
May | 16.17 | 27.00 | 508.00 | 27.00 | 16.17 | 27.00 |
June | 20.17 | 27.00 | 496.00 | 27.00 | 20.17 | 27.00 |
July | 80.17 | 27.00 | 497.00 | 27.00 | 80.17 | 27.00 |
August | 319.33 | 28.14 | 514.00 | 27.89 | 319.33 | 27.96 |
September | 25.83 | 27.00 | 485.00 | 27.00 | 25.83 | 27.00 |
October | 11.50 | 27.00 | 502.00 | 27.00 | 11.50 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 493.83 | 27.75 | 5943.00 | 27.12 | 493.83 | 27.16 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 319.33 | 28.14 | 514.00 | 27.89 | 319.33 | 27.96 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5943.00 | 27.00 | 5943.00 | 27.00 | 5943.00 | 27.00 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00099 | 31.95929 | 0.89723 | 22.02232 |
February | 454.00000 | 27.00156 | 31.48192 | 0.93415 | 23.45086 |
March | 514.00000 | 27.00088 | 31.16400 | 0.96700 | 24.76865 |
April | 485.00000 | 27.03209 | 31.86544 | 1.01596 | 26.83036 |
May | 508.00000 | 27.00058 | 36.99394 | 0.30730 | 7.00370 |
June | 496.00000 | 27.00256 | 37.05067 | 0.36003 | 7.72828 |
July | 497.00000 | 27.00129 | 36.64696 | 0.41523 | 8.62618 |
August | 514.00000 | 27.97813 | 35.42990 | 0.68798 | 15.57546 |
September | 485.00000 | 27.00016 | 40.79963 | 0.34700 | 7.53793 |
October | 502.00000 | 27.00235 | 35.13923 | 0.98805 | 25.63929 |
November | 489.00000 | 27.00124 | 32.54662 | 0.98970 | 25.70625 |
December | 497.00000 | 27.00038 | 30.57953 | 0.98974 | 25.70731 |
Annual Sum or Average | 5943.00000 | 27.08821 | 34.31684 | 0.74022 | 18.34150 |
Minimum of Months | 454.00000 | 27.00016 | 30.57953 | 0.30730 | 7.00370 |
Maximum of Months | 514.00000 | 27.97813 | 40.79963 | 1.01596 | 26.83036 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00054 | 32.34409 | 0.83888 | 19.88540 |
February | 454.00000 | 27.00146 | 31.61715 | 0.86050 | 20.65658 |
March | 514.00000 | 27.00083 | 31.19118 | 0.88980 | 21.74319 |
April | 485.00000 | 27.03684 | 31.86931 | 0.93452 | 23.48906 |
May | 508.00000 | 27.00046 | 37.23799 | 0.25989 | 6.44146 |
June | 496.00000 | 27.00245 | 37.22419 | 0.28551 | 6.72318 |
July | 497.00000 | 27.00132 | 36.76446 | 0.31077 | 7.03724 |
August | 514.00000 | 27.97334 | 35.51559 | 0.56623 | 12.42052 |
September | 485.00000 | 27.00009 | 41.27644 | 0.29420 | 6.82884 |
October | 502.00000 | 27.00222 | 35.28852 | 0.93450 | 23.46584 |
November | 489.00000 | 27.00119 | 32.60342 | 0.91407 | 22.66661 |
December | 497.00000 | 27.00038 | 30.59586 | 0.88217 | 21.45779 |
Annual Sum or Average | 5943.00000 | 27.08810 | 34.47248 | 0.66275 | 16.02855 |
Minimum of Months | 454.00000 | 27.00009 | 30.59586 | 0.25989 | 6.44146 |
Maximum of Months | 514.00000 | 27.97334 | 41.27644 | 0.93452 | 23.48906 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00036 | 32.21886 | 0.80093 | 18.61664 |
February | 454.00000 | 27.00158 | 31.05368 | 0.83451 | 19.76939 |
March | 514.00000 | 27.00095 | 30.56625 | 0.87829 | 21.35190 |
April | 485.00000 | 27.01679 | 31.24887 | 0.93393 | 23.48628 |
May | 508.00000 | 27.00052 | 36.55895 | 0.28424 | 6.76888 |
June | 496.00000 | 27.00269 | 36.51247 | 0.31546 | 7.15034 |
July | 497.00000 | 27.00149 | 36.06420 | 0.35086 | 7.64193 |
August | 514.00000 | 27.73919 | 34.94760 | 0.54306 | 12.04043 |
September | 485.00000 | 27.00011 | 40.48705 | 0.31736 | 7.17157 |
October | 502.00000 | 27.00241 | 34.63780 | 0.94095 | 23.74144 |
November | 489.00000 | 27.00135 | 31.94970 | 0.90551 | 22.36235 |
December | 497.00000 | 27.00052 | 29.92669 | 0.85135 | 20.36949 |
Annual Sum or Average | 5943.00000 | 27.06630 | 33.85991 | 0.66160 | 15.83608 |
Minimum of Months | 454.00000 | 27.00011 | 29.92669 | 0.28424 | 6.76888 |
Maximum of Months | 514.00000 | 27.73919 | 40.48705 | 0.94095 | 23.74144 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 41.02448 | 1.19681 | 35.09455 |
February | 454.00000 | 27.00000 | 40.76562 | 1.33469 | 42.06772 |
March | 514.00000 | 27.00000 | 40.49303 | 1.46138 | 48.80777 |
April | 485.00000 | 27.00000 | 40.45645 | 1.58697 | 55.63593 |
May | 508.00000 | 27.00000 | 40.55610 | 0.59510 | 12.45455 |
June | 496.00000 | 27.00000 | 40.04512 | 0.80828 | 18.78418 |
July | 497.00000 | 27.00000 | 39.93037 | 1.02290 | 27.10220 |
August | 514.00000 | 27.00000 | 40.00177 | 1.23210 | 36.83461 |
September | 485.00000 | 27.00000 | 40.48391 | 0.65197 | 13.95331 |
October | 502.00000 | 27.00000 | 40.59562 | 1.36684 | 43.75505 |
November | 489.00000 | 27.00000 | 40.70022 | 1.50364 | 51.09832 |
December | 497.00000 | 27.00000 | 40.74501 | 1.62120 | 57.49743 |
Annual Sum or Average | 5943.00000 | 27.00000 | 40.48027 | 1.19735 | 36.87181 |
Minimum of Months | 454.00000 | 27.00000 | 39.93037 | 0.59510 | 12.45455 |
Maximum of Months | 514.00000 | 27.00000 | 41.02448 | 1.62120 | 57.49743 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.66838 | 48.65352 | 0.60177 | 13.25278 |
February | 454.00000 | 24.64244 | 53.61312 | 0.62860 | 13.96633 |
March | 514.00000 | 24.52537 | 52.21001 | 0.58984 | 12.85509 |
April | 485.00000 | 24.60969 | 55.78531 | 0.63141 | 14.12379 |
May | 508.00000 | 24.59011 | 57.79528 | -0.2003 | 7.12619 |
June | 496.00000 | 24.55415 | 63.43743 | -0.1626 | 7.06727 |
July | 497.00000 | 24.70038 | 62.90335 | -0.1097 | 7.16962 |
August | 514.00000 | 24.56357 | 63.02975 | -0.1331 | 7.04240 |
September | 485.00000 | 24.64510 | 64.22297 | -0.1115 | 7.23522 |
October | 502.00000 | 24.69741 | 58.49152 | 0.69453 | 16.19854 |
November | 489.00000 | 24.70075 | 56.56226 | 0.67967 | 15.39817 |
December | 497.00000 | 24.69556 | 54.14891 | 0.65545 | 14.82844 |
Annual Sum or Average | 5943.00000 | 24.63212 | 57.58427 | 0.31032 | 11.32423 |
Minimum of Months | 454.00000 | 24.52537 | 48.65352 | -0.2003 | 7.04240 |
Maximum of Months | 514.00000 | 24.70075 | 64.22297 | 0.69453 | 16.19854 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.38171 | 49.93206 | 0.54551 | 11.57828 |
February | 454.00000 | 24.38670 | 53.23258 | 0.57738 | 12.34228 |
March | 514.00000 | 24.26080 | 51.23715 | 0.54382 | 11.38639 |
April | 485.00000 | 24.19777 | 52.94734 | 0.54995 | 11.44904 |
May | 508.00000 | 24.18404 | 54.48817 | -0.3186 | 7.30337 |
June | 496.00000 | 24.14823 | 56.44747 | -0.3049 | 7.03472 |
July | 497.00000 | 24.21893 | 55.75900 | -0.2740 | 6.72012 |
August | 514.00000 | 24.21198 | 55.96937 | -0.2615 | 6.61046 |
September | 485.00000 | 24.19794 | 56.79893 | -0.2915 | 6.93770 |
October | 502.00000 | 24.24735 | 55.10460 | 0.57681 | 12.10811 |
November | 489.00000 | 24.30257 | 55.69107 | 0.59313 | 12.53337 |
December | 497.00000 | 24.32706 | 53.62450 | 0.57895 | 12.23720 |
Annual Sum or Average | 5943.00000 | 24.25452 | 54.26578 | 0.20605 | 9.82868 |
Minimum of Months | 454.00000 | 24.14823 | 49.93206 | -0.3186 | 6.61046 |
Maximum of Months | 514.00000 | 24.38670 | 56.79893 | 0.59313 | 12.53337 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.13161 | 51.06548 | 0.46445 | 9.81552 |
February | 454.00000 | 24.16332 | 54.31907 | 0.49878 | 10.44872 |
March | 514.00000 | 24.16803 | 51.97909 | 0.49402 | 10.30549 |
April | 485.00000 | 24.17110 | 53.62030 | 0.51345 | 10.71806 |
May | 508.00000 | 24.11248 | 54.92962 | -0.3694 | 8.04590 |
June | 496.00000 | 24.04507 | 57.32984 | -0.3736 | 8.01348 |
July | 497.00000 | 24.01329 | 57.41051 | -0.3832 | 8.14683 |
August | 514.00000 | 24.02395 | 57.91625 | -0.3710 | 7.93560 |
September | 485.00000 | 24.08585 | 57.65659 | -0.3585 | 7.81850 |
October | 502.00000 | 24.19881 | 55.70794 | 0.53990 | 11.27247 |
November | 489.00000 | 24.22825 | 56.53291 | 0.54800 | 11.46418 |
December | 497.00000 | 24.13522 | 54.98598 | 0.49901 | 10.43340 |
Annual Sum or Average | 5943.00000 | 24.12254 | 55.28556 | 0.13825 | 9.52354 |
Minimum of Months | 454.00000 | 24.01329 | 51.06548 | -0.3832 | 7.81850 |
Maximum of Months | 514.00000 | 24.22825 | 57.91625 | 0.54800 | 11.46418 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.64506 | 54.77690 | 0.35057 | 8.12768 |
February | 454.00000 | 23.86474 | 55.78196 | 0.42609 | 9.20295 |
March | 514.00000 | 24.03599 | 52.79986 | 0.46699 | 9.82327 |
April | 485.00000 | 24.18154 | 53.73544 | 0.52674 | 11.01832 |
May | 508.00000 | 24.19849 | 54.67481 | -0.3100 | 7.28477 |
June | 496.00000 | 24.14970 | 56.85136 | -0.3036 | 7.11818 |
July | 497.00000 | 24.19022 | 56.52184 | -0.2836 | 6.88620 |
August | 514.00000 | 24.15703 | 57.16756 | -0.2870 | 6.87160 |
September | 485.00000 | 24.17888 | 57.27112 | -0.2981 | 7.08513 |
October | 502.00000 | 24.24358 | 55.78592 | 0.56374 | 11.84248 |
November | 489.00000 | 24.14978 | 57.23499 | 0.53343 | 11.10359 |
December | 497.00000 | 23.80086 | 56.58459 | 0.41567 | 9.03350 |
Annual Sum or Average | 5943.00000 | 24.06741 | 55.75700 | 0.14711 | 8.77293 |
Minimum of Months | 454.00000 | 23.64506 | 52.79986 | -0.3100 | 6.87160 |
Maximum of Months | 514.00000 | 24.24358 | 57.27112 | 0.56374 | 11.84248 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.09415 | 50.09176 | 0.44852 | 9.50652 |
February | 454.00000 | 24.23218 | 52.95725 | 0.51945 | 10.93512 |
March | 514.00000 | 24.24224 | 50.52551 | 0.53105 | 11.11434 |
April | 485.00000 | 24.37280 | 51.82821 | 0.60146 | 12.94879 |
May | 508.00000 | 24.51866 | 52.63870 | -0.1458 | 6.55143 |
June | 496.00000 | 24.48459 | 54.90277 | -0.1081 | 6.30867 |
July | 497.00000 | 24.64334 | 54.08880 | -0.0398 | 6.54358 |
August | 514.00000 | 24.52667 | 54.63265 | -0.0630 | 6.33987 |
September | 485.00000 | 24.53324 | 55.50941 | -0.1169 | 6.47661 |
October | 502.00000 | 24.49345 | 53.93443 | 0.65443 | 14.49731 |
November | 489.00000 | 24.36683 | 54.85923 | 0.60372 | 12.88860 |
December | 497.00000 | 24.21117 | 53.51682 | 0.52630 | 11.00575 |
Annual Sum or Average | 5943.00000 | 24.39423 | 53.28154 | 0.28175 | 9.57244 |
Minimum of Months | 454.00000 | 24.09415 | 50.09176 | -0.1458 | 6.30867 |
Maximum of Months | 514.00000 | 24.64334 | 55.50941 | 0.65443 | 14.49731 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.10106 | 49.83867 | 0.46615 | 10.00604 |
February | 454.00000 | 24.18904 | 52.93487 | 0.52367 | 11.15595 |
March | 514.00000 | 24.17143 | 50.61339 | 0.52615 | 11.11259 |
April | 485.00000 | 24.33389 | 51.82863 | 0.60761 | 13.22018 |
May | 508.00000 | 24.53077 | 52.41450 | -0.1012 | 6.52847 |
June | 496.00000 | 24.45970 | 54.83367 | -0.0887 | 6.25541 |
July | 497.00000 | 24.61235 | 54.08309 | -0.0272 | 6.57923 |
August | 514.00000 | 24.48861 | 54.64557 | -0.0511 | 6.25528 |
September | 485.00000 | 24.54462 | 55.23351 | -0.0747 | 6.50732 |
October | 502.00000 | 24.50323 | 53.69248 | 0.67715 | 15.24731 |
November | 489.00000 | 24.33769 | 54.85800 | 0.60951 | 13.10657 |
December | 497.00000 | 24.05755 | 53.95826 | 0.49758 | 10.44088 |
Annual Sum or Average | 5943.00000 | 24.36181 | 53.23565 | 0.29459 | 9.67931 |
Minimum of Months | 454.00000 | 24.05755 | 49.83867 | -0.1012 | 6.25528 |
Maximum of Months | 514.00000 | 24.61235 | 55.23351 | 0.67715 | 15.24731 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.31889 | 48.99010 | 0.53977 | 11.77348 |
February | 454.00000 | 24.37436 | 52.19124 | 0.59107 | 12.87664 |
March | 514.00000 | 24.32066 | 50.08598 | 0.57774 | 12.38828 |
April | 485.00000 | 24.41714 | 51.61530 | 0.62580 | 13.70516 |
May | 508.00000 | 24.50802 | 52.66254 | -0.1477 | 6.55979 |
June | 496.00000 | 24.45574 | 55.02700 | -0.1274 | 6.32082 |
July | 497.00000 | 24.62415 | 54.14481 | -0.0494 | 6.50642 |
August | 514.00000 | 24.52946 | 54.56275 | -0.0486 | 6.33738 |
September | 485.00000 | 24.58564 | 55.12008 | -0.0558 | 6.53132 |
October | 502.00000 | 24.61792 | 53.22866 | 0.73306 | 17.08055 |
November | 489.00000 | 24.55774 | 53.93198 | 0.70321 | 16.04632 |
December | 497.00000 | 24.40545 | 52.56403 | 0.61607 | 13.57254 |
Annual Sum or Average | 5943.00000 | 24.47655 | 52.83825 | 0.32695 | 10.77971 |
Minimum of Months | 454.00000 | 24.31889 | 48.99010 | -0.1477 | 6.32082 |
Maximum of Months | 514.00000 | 24.62415 | 55.12008 | 0.73306 | 17.08055 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.38009 | 48.67594 | 0.56428 | 12.17996 |
February | 454.00000 | 24.57423 | 51.37559 | 0.66987 | 15.08422 |
March | 514.00000 | 24.54715 | 49.10486 | 0.69752 | 15.88350 |
April | 485.00000 | 24.63909 | 50.52893 | 0.77770 | 18.57418 |
May | 508.00000 | 24.59923 | 52.09731 | -0.0201 | 6.55128 |
June | 496.00000 | 24.56507 | 54.23302 | 0.03998 | 6.54803 |
July | 497.00000 | 24.74598 | 53.35628 | 0.13706 | 7.51475 |
August | 514.00000 | 24.64122 | 53.80502 | 0.14973 | 7.40465 |
September | 485.00000 | 24.61835 | 54.74629 | 0.01535 | 6.62987 |
October | 502.00000 | 24.65841 | 52.93747 | 0.77768 | 18.53521 |
November | 489.00000 | 24.65882 | 53.48252 | 0.76586 | 18.05980 |
December | 497.00000 | 24.65581 | 51.55169 | 0.72881 | 16.93559 |
Annual Sum or Average | 5943.00000 | 24.60681 | 52.15309 | 0.43957 | 12.45503 |
Minimum of Months | 454.00000 | 24.38009 | 48.67594 | -0.0201 | 6.54803 |
Maximum of Months | 514.00000 | 24.74598 | 54.74629 | 0.77770 | 18.57418 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.55924 | 51.79429 | 0.30432 | 7.45533 |
February | 454.00000 | 23.81363 | 54.63698 | 0.39973 | 8.76182 |
March | 514.00000 | 24.06963 | 51.37728 | 0.46487 | 9.82862 |
April | 485.00000 | 24.36617 | 52.93901 | 0.57670 | 12.40544 |
May | 508.00000 | 24.55139 | 53.02295 | -0.1509 | 6.75525 |
June | 496.00000 | 24.51994 | 56.01618 | -0.1141 | 6.54106 |
July | 497.00000 | 24.66088 | 55.67459 | -0.0580 | 6.68785 |
August | 514.00000 | 24.52869 | 56.64920 | -0.0912 | 6.46194 |
September | 485.00000 | 24.55932 | 56.99643 | -0.1206 | 6.68049 |
October | 502.00000 | 24.52330 | 55.23295 | 0.64783 | 14.43034 |
November | 489.00000 | 24.27902 | 55.97908 | 0.55977 | 11.78010 |
December | 497.00000 | 23.79752 | 55.74919 | 0.40230 | 8.82503 |
Annual Sum or Average | 5943.00000 | 24.27183 | 54.66065 | 0.23294 | 8.87446 |
Minimum of Months | 454.00000 | 23.55924 | 51.37728 | -0.1509 | 6.46194 |
Maximum of Months | 514.00000 | 24.66088 | 56.99643 | 0.64783 | 14.43034 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.70098 | 50.55156 | 0.34977 | 8.20630 |
February | 385.00000 | 23.94186 | 53.71787 | 0.44325 | 9.72348 |
March | 433.00000 | 24.16557 | 50.57676 | 0.50028 | 10.81124 |
April | 410.00000 | 24.54477 | 52.34262 | 0.64025 | 14.43785 |
May | 430.00000 | 24.69205 | 52.58559 | -0.0677 | 6.90639 |
June | 418.00000 | 24.62295 | 55.69075 | -0.0521 | 6.68386 |
July | 422.00000 | 24.79218 | 55.07286 | 0.01206 | 7.10123 |
August | 433.00000 | 24.63959 | 56.18844 | -0.0214 | 6.63675 |
September | 410.00000 | 24.70187 | 56.34632 | -0.0399 | 6.95650 |
October | 427.00000 | 24.70362 | 54.49566 | 0.71061 | 16.55813 |
November | 417.00000 | 24.44700 | 55.07149 | 0.61387 | 13.39607 |
December | 422.00000 | 23.87378 | 54.93812 | 0.43172 | 9.45601 |
Annual Sum or Average | 5034.00000 | 24.40436 | 53.95477 | 0.29188 | 9.73014 |
Minimum of Months | 385.00000 | 23.70098 | 50.55156 | -0.0677 | 6.63675 |
Maximum of Months | 433.00000 | 24.79218 | 56.34632 | 0.71061 | 16.55813 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.18531 | 49.29517 | 0.49582 | 11.01931 |
February | 454.00000 | 24.23258 | 52.76895 | 0.54203 | 11.85448 |
March | 514.00000 | 24.26316 | 50.45581 | 0.54380 | 11.69554 |
April | 485.00000 | 24.44230 | 52.53949 | 0.61093 | 13.41731 |
May | 508.00000 | 24.53830 | 53.04749 | -0.1542 | 6.74174 |
June | 496.00000 | 24.48811 | 56.18096 | -0.1353 | 6.53826 |
July | 497.00000 | 24.64132 | 55.73966 | -0.0677 | 6.63697 |
August | 514.00000 | 24.53746 | 56.48628 | -0.0726 | 6.45278 |
September | 485.00000 | 24.62052 | 56.39793 | -0.0534 | 6.74593 |
October | 502.00000 | 24.68344 | 54.17204 | 0.73963 | 17.47033 |
November | 489.00000 | 24.57849 | 54.49430 | 0.69229 | 15.80683 |
December | 497.00000 | 24.31677 | 53.45585 | 0.57376 | 12.74627 |
Annual Sum or Average | 5943.00000 | 24.46160 | 53.74933 | 0.30683 | 10.57074 |
Minimum of Months | 454.00000 | 24.18531 | 49.29517 | -0.1542 | 6.45278 |
Maximum of Months | 514.00000 | 24.68344 | 56.48628 | 0.73963 | 17.47033 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.73761 | 50.72555 | 0.37251 | 8.59717 |
February | 454.00000 | 24.00889 | 53.54268 | 0.47701 | 10.34629 |
March | 514.00000 | 24.23828 | 50.45095 | 0.54371 | 11.69434 |
April | 485.00000 | 24.50742 | 52.08840 | 0.65331 | 14.70668 |
May | 508.00000 | 24.60429 | 52.57781 | -0.0734 | 6.78790 |
June | 496.00000 | 24.55496 | 55.47744 | -0.0422 | 6.60783 |
July | 497.00000 | 24.69157 | 55.12991 | 0.01520 | 6.92658 |
August | 514.00000 | 24.57227 | 56.00109 | -0.0005 | 6.62365 |
September | 485.00000 | 24.62292 | 56.17624 | -0.0362 | 6.82893 |
October | 502.00000 | 24.62246 | 54.40379 | 0.71261 | 16.52695 |
November | 489.00000 | 24.42735 | 55.10438 | 0.63260 | 13.85674 |
December | 497.00000 | 24.02179 | 54.48259 | 0.48576 | 10.50445 |
Annual Sum or Average | 5943.00000 | 24.38623 | 53.83776 | 0.30959 | 9.98395 |
Minimum of Months | 454.00000 | 23.73761 | 50.45095 | -0.0734 | 6.60783 |
Maximum of Months | 514.00000 | 24.69157 | 56.17624 | 0.71261 | 16.52695 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.92661 | 53.86079 | 0.15257 | 6.74233 |
February | 454.00000 | 23.41129 | 56.08727 | 0.30633 | 7.95890 |
March | 514.00000 | 23.88064 | 52.21183 | 0.42580 | 9.43589 |
April | 485.00000 | 24.33070 | 53.29163 | 0.58074 | 12.67390 |
May | 508.00000 | 24.56308 | 53.13820 | -0.1129 | 6.78776 |
June | 496.00000 | 24.53689 | 56.03293 | -0.0692 | 6.60880 |
July | 497.00000 | 24.68682 | 55.53589 | -0.0024 | 6.95681 |
August | 514.00000 | 24.55102 | 56.54822 | -0.0394 | 6.58442 |
September | 485.00000 | 24.57203 | 57.05949 | -0.0826 | 6.77294 |
October | 502.00000 | 24.52729 | 55.53499 | 0.66417 | 14.97623 |
November | 489.00000 | 24.17896 | 56.73302 | 0.54155 | 11.49274 |
December | 497.00000 | 23.37273 | 57.44203 | 0.30243 | 7.90021 |
Annual Sum or Average | 5943.00000 | 24.13255 | 55.27213 | 0.22068 | 8.73502 |
Minimum of Months | 454.00000 | 22.92661 | 52.21183 | -0.1129 | 6.58442 |
Maximum of Months | 514.00000 | 24.68682 | 57.44203 | 0.66417 | 14.97623 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.25950 | 52.52599 | 0.24710 | 7.49133 |
February | 454.00000 | 23.66219 | 54.95573 | 0.38483 | 9.06341 |
March | 514.00000 | 24.01122 | 51.48426 | 0.48123 | 10.61457 |
April | 485.00000 | 24.44366 | 52.55340 | 0.64242 | 14.54082 |
May | 508.00000 | 24.60042 | 52.73569 | -0.0422 | 6.82602 |
June | 496.00000 | 24.54610 | 55.68085 | -0.0174 | 6.63583 |
July | 497.00000 | 24.70162 | 55.20780 | 0.05130 | 7.22914 |
August | 514.00000 | 24.56495 | 56.16291 | 0.02068 | 6.67414 |
September | 485.00000 | 24.60945 | 56.46484 | -0.0151 | 6.91413 |
October | 502.00000 | 24.61001 | 54.78174 | 0.71796 | 16.74978 |
November | 489.00000 | 24.31578 | 55.94422 | 0.60079 | 13.07638 |
December | 497.00000 | 23.56233 | 56.48306 | 0.36378 | 8.67193 |
Annual Sum or Average | 5943.00000 | 24.24390 | 54.56796 | 0.28461 | 9.52920 |
Minimum of Months | 454.00000 | 23.25950 | 51.48426 | -0.0422 | 6.63583 |
Maximum of Months | 514.00000 | 24.70162 | 56.48306 | 0.71796 | 16.74978 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.77051 | 50.75300 | 0.38970 | 9.78167 |
February | 454.00000 | 23.95018 | 53.86626 | 0.47441 | 10.92937 |
March | 514.00000 | 24.11077 | 51.19255 | 0.51374 | 11.33238 |
April | 485.00000 | 24.39346 | 52.91757 | 0.61323 | 13.63991 |
May | 508.00000 | 24.54303 | 53.18263 | -0.1184 | 6.76997 |
June | 496.00000 | 24.50150 | 56.20063 | -0.0922 | 6.56969 |
July | 497.00000 | 24.66281 | 55.60532 | -0.0135 | 6.86841 |
August | 514.00000 | 24.55324 | 56.41379 | -0.0223 | 6.59797 |
September | 485.00000 | 24.62276 | 56.51039 | -0.0173 | 6.93228 |
October | 502.00000 | 24.68198 | 54.50730 | 0.75648 | 18.07568 |
November | 489.00000 | 24.51557 | 55.09788 | 0.68394 | 15.64111 |
December | 497.00000 | 24.05947 | 54.63056 | 0.50918 | 11.71798 |
Annual Sum or Average | 5943.00000 | 24.36587 | 54.23196 | 0.30411 | 10.38595 |
Minimum of Months | 454.00000 | 23.77051 | 50.75300 | -0.1184 | 6.56969 |
Maximum of Months | 514.00000 | 24.68198 | 56.51039 | 0.75648 | 18.07568 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.20591 | 52.47704 | 0.24563 | 7.67567 |
February | 454.00000 | 23.65616 | 54.81057 | 0.39651 | 9.42277 |
March | 514.00000 | 24.06970 | 51.22887 | 0.51075 | 11.27445 |
April | 485.00000 | 24.45656 | 52.47794 | 0.65473 | 14.88662 |
May | 508.00000 | 24.59918 | 52.77367 | -0.0414 | 6.90731 |
June | 496.00000 | 24.55445 | 55.60762 | -0.0037 | 6.76282 |
July | 497.00000 | 24.69893 | 55.11165 | 0.06334 | 7.28345 |
August | 514.00000 | 24.57567 | 56.02440 | 0.04299 | 6.86564 |
September | 485.00000 | 24.61529 | 56.35218 | -0.0049 | 7.00359 |
October | 502.00000 | 24.60895 | 54.76774 | 0.72553 | 16.98115 |
November | 489.00000 | 24.33072 | 55.82198 | 0.61664 | 13.55541 |
December | 497.00000 | 23.66066 | 55.93449 | 0.40156 | 9.42993 |
Annual Sum or Average | 5943.00000 | 24.25616 | 54.43530 | 0.29902 | 9.82582 |
Minimum of Months | 454.00000 | 23.20591 | 51.22887 | -0.0414 | 6.76282 |
Maximum of Months | 514.00000 | 24.69893 | 56.35218 | 0.72553 | 16.98115 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.103478E+12 | 115565.24 | 30-JAN-06:03 | 466.44 | 0.706193E+12 | 0.00 | 0.809671E+12 | 4.03 | 8.32 | 30-JAN-06:03 | 0.00 | 0.00 |
February | 0.103767E+12 | 135054.02 | 09-FEB-06:02 | 439.39 | 0.729674E+12 | 0.00 | 0.833441E+12 | 4.32 | 8.47 | 27-FEB-06:04 | 0.00 | 0.00 |
March | 0.135534E+12 | 162105.62 | 29-MAR-05:04 | 571.87 | 0.966027E+12 | 0.00 | 0.110156E+13 | 5.09 | 8.61 | 30-MAR-05:04 | 0.00 | 0.00 |
April | 0.158088E+12 | 151300.37 | 20-APR-05:03 | 645.77 | 0.113557E+13 | 0.00 | 0.129366E+13 | 5.92 | 8.62 | 04-APR-05:04 | 0.00 | 0.00 |
May | 0.212297E+12 | 191515.23 | 31-MAY-05:02 | 670.99 | 0.153023E+13 | 0.00 | 0.174253E+13 | 6.25 | 8.48 | 15-MAY-05:02 | 0.00 | 0.00 |
June | 0.249183E+12 | 219509.38 | 09-JUN-05:03 | 692.47 | 0.176212E+13 | 0.00 | 0.201130E+13 | 6.59 | 8.30 | 07-JUN-05:03 | 0.00 | 0.00 |
July | 0.290631E+12 | 220537.13 | 14-JUL-05:03 | 724.11 | 0.204020E+13 | 0.00 | 0.233083E+13 | 6.67 | 8.17 | 13-JUL-05:03 | 0.00 | 0.00 |
August | 0.307313E+12 | 221697.89 | 17-AUG-05:03 | 728.15 | 0.215626E+13 | 0.00 | 0.246357E+13 | 6.71 | 7.97 | 15-AUG-05:02 | 0.00 | 0.00 |
September | 0.247944E+12 | 217396.01 | 08-SEP-05:02 | 665.29 | 0.174444E+13 | 0.00 | 0.199239E+13 | 6.28 | 8.21 | 26-SEP-05:02 | 0.00 | 0.00 |
October | 0.202941E+12 | 202486.20 | 18-OCT-05:02 | 660.27 | 0.145027E+13 | 0.00 | 0.165321E+13 | 5.99 | 8.30 | 30-OCT-05:02 | 0.00 | 0.00 |
November | 0.151731E+12 | 187852.77 | 10-NOV-06:04 | 601.12 | 0.109344E+13 | 0.00 | 0.124517E+13 | 5.54 | 8.55 | 16-NOV-06:04 | 0.00 | 0.00 |
December | 0.121413E+12 | 138892.52 | 11-DEC-06:03 | 573.93 | 0.851306E+12 | 0.00 | 0.972719E+12 | 4.94 | 8.34 | 11-DEC-06:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.228432E+13 | 7439.82 | 0.161657E+14 | 0.00 | 0.184501E+14 | 5.70 | 0.00 | 0.00 | ||||
Minimum of Months | 0.103478E+12 | 115565.24 | 439.39 | 0.706193E+12 | 0.00 | 0.809671E+12 | 4.03 | 7.97 | 0.00 | 0.00 | ||
Maximum of Months | 0.307313E+12 | 221697.89 | 728.15 | 0.215626E+13 | 0.00 | 0.246357E+13 | 6.71 | 8.62 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 28953280.23 | 115565.24 | 30-JAN-06:03 | 0.07 | 0.240647E+09 | 0.00 | 0.269600E+09 | 0.00 | 8.32 | 30-JAN-06:03 | 0.00 | 0.00 |
February | 0.109835E+10 | 135054.02 | 09-FEB-06:02 | 2.82 | 0.839885E+10 | 0.00 | 0.949720E+10 | 0.03 | 8.47 | 27-FEB-06:04 | 0.00 | 0.00 |
March | 0.664680E+10 | 162105.62 | 29-MAR-05:04 | 17.54 | 0.519458E+11 | 0.00 | 0.585926E+11 | 0.18 | 8.61 | 30-MAR-05:04 | 0.00 | 0.00 |
April | 0.220962E+11 | 151300.37 | 20-APR-05:03 | 57.88 | 0.170282E+12 | 0.00 | 0.192378E+12 | 0.62 | 8.62 | 04-APR-05:04 | 0.00 | 0.00 |
May | 0.731306E+11 | 191515.23 | 31-MAY-05:02 | 179.19 | 0.548323E+12 | 0.00 | 0.621454E+12 | 1.81 | 8.48 | 15-MAY-05:02 | 0.00 | 0.00 |
June | 0.130072E+12 | 219509.38 | 09-JUN-05:03 | 296.19 | 0.950046E+12 | 0.00 | 0.108012E+13 | 3.01 | 8.30 | 07-JUN-05:03 | 0.00 | 0.00 |
July | 0.185899E+12 | 220537.13 | 14-JUL-05:03 | 386.44 | 0.133442E+13 | 0.00 | 0.152032E+13 | 3.73 | 8.17 | 13-JUL-05:03 | 0.00 | 0.00 |
August | 0.214291E+12 | 221697.89 | 17-AUG-05:03 | 432.09 | 0.153536E+13 | 0.00 | 0.174965E+13 | 4.16 | 7.97 | 15-AUG-05:02 | 0.00 | 0.00 |
September | 0.144284E+12 | 217396.01 | 08-SEP-05:02 | 316.80 | 0.104498E+13 | 0.00 | 0.118926E+13 | 3.19 | 8.21 | 26-SEP-05:02 | 0.00 | 0.00 |
October | 0.811645E+11 | 202486.20 | 18-OCT-05:02 | 196.31 | 0.604772E+12 | 0.00 | 0.685936E+12 | 1.97 | 8.30 | 30-OCT-05:02 | 0.00 | 0.00 |
November | 0.298107E+11 | 187852.77 | 10-NOV-06:04 | 74.92 | 0.224670E+12 | 0.00 | 0.254481E+12 | 0.78 | 8.55 | 16-NOV-06:04 | 0.00 | 0.00 |
December | 0.241814E+10 | 138892.52 | 11-DEC-06:03 | 6.25 | 0.184117E+11 | 0.00 | 0.208299E+11 | 0.06 | 8.34 | 11-DEC-06:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.890941E+12 | 1966.51 | 0.649184E+13 | 0.00 | 0.738278E+13 | 1.64 | 0.00 | 0.00 | ||||
Minimum of Months | 28953280.23 | 115565.24 | 0.07 | 0.240647E+09 | 0.00 | 0.269600E+09 | 0.00 | 7.97 | 0.00 | 0.00 | ||
Maximum of Months | 0.214291E+12 | 221697.89 | 432.09 | 0.153536E+13 | 0.00 | 0.174965E+13 | 4.16 | 8.62 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.254488E+11 | 744.00 | 12476.23 | 01-JAN-10:03 | 42857.46 | 06-JAN-17:00 | 23.22 | 20.57 | 2.89 |
February | 0.276665E+11 | 672.00 | 12476.23 | 01-FEB-09:20 | 69860.98 | 07-FEB-16:10 | 27.57 | 22.00 | 2.89 |
March | 0.328441E+11 | 744.00 | 12476.23 | 01-MAR-00:10 | 115213.73 | 31-MAR-23:13 | 32.99 | 24.51 | 2.89 |
April | 0.323384E+11 | 720.00 | 12476.23 | 01-APR-00:05 | 132019.43 | 30-APR-14:52 | 39.77 | 28.26 | 2.89 |
May | 0.334163E+11 | 744.00 | 12476.23 | 01-MAY-00:03 | 70314.47 | 31-MAY-23:13 | 35.84 | 31.96 | 2.89 |
June | 0.323384E+11 | 720.00 | 12476.23 | 01-JUN-00:03 | 100692.39 | 30-JUN-23:10 | 41.06 | 34.05 | 2.89 |
July | 0.334163E+11 | 744.00 | 12476.23 | 01-JUL-00:03 | 129617.07 | 31-JUL-23:42 | 46.73 | 36.66 | 2.89 |
August | 0.334163E+11 | 744.00 | 12476.23 | 01-AUG-00:03 | 134420.77 | 04-AUG-14:00 | 49.78 | 37.28 | 2.89 |
September | 0.323384E+11 | 720.00 | 12476.23 | 01-SEP-00:03 | 74023.07 | 30-SEP-23:13 | 37.38 | 33.14 | 2.89 |
October | 0.334163E+11 | 744.00 | 12476.23 | 01-OCT-00:03 | 92243.86 | 31-OCT-23:13 | 37.22 | 30.55 | 2.89 |
November | 0.323335E+11 | 720.00 | 12476.23 | 01-NOV-00:03 | 104408.49 | 01-NOV-14:20 | 35.74 | 26.89 | 2.89 |
December | 0.327605E+11 | 744.00 | 12476.23 | 01-DEC-00:05 | 124602.28 | 05-DEC-17:00 | 33.81 | 22.94 | 2.89 |
Annual Sum or Average | 0.381734E+12 | 8760.00 | 36.82 | 29.11 | 2.89 | ||||
Minimum of Months | 0.254488E+11 | 672.00 | 12476.23 | 42857.46 | 23.22 | 20.57 | 2.89 | ||
Maximum of Months | 0.334163E+11 | 744.00 | 12476.23 | 134420.77 | 49.78 | 37.28 | 2.89 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.238395E+10 | 413.76 | 20572.62 | 09-JAN-13:50 | 1143149.92 | 23-JAN-13:20 | 22.43 | 21.42 | 45.72 |
February | 0.516294E+10 | 400.11 | 20572.62 | 02-FEB-11:50 | 1370370.56 | 06-FEB-15:00 | 22.70 | 21.53 | 48.36 |
March | 0.105978E+11 | 502.55 | 20572.62 | 01-MAR-03:42 | 1417881.54 | 23-MAR-14:50 | 22.81 | 21.36 | 56.29 |
April | 0.242955E+11 | 600.00 | 20572.62 | 03-APR-05:02 | 1406712.62 | 28-APR-09:10 | 23.57 | 21.82 | 66.98 |
May | 0.416750E+11 | 669.99 | 20572.62 | 01-MAY-00:03 | 1385087.62 | 04-MAY-09:00 | 25.84 | 23.65 | 66.20 |
June | 0.500150E+11 | 692.47 | 20572.62 | 01-JUN-00:13 | 1474087.54 | 08-JUN-05:04 | 28.52 | 25.95 | 63.94 |
July | 0.523664E+11 | 724.07 | 20572.62 | 01-JUL-00:03 | 1583456.28 | 19-JUL-15:00 | 29.88 | 27.02 | 64.19 |
August | 0.539282E+11 | 728.15 | 20572.62 | 01-AUG-00:03 | 1600009.58 | 10-AUG-16:00 | 30.49 | 27.48 | 64.53 |
September | 0.490467E+11 | 665.29 | 20572.62 | 01-SEP-00:03 | 1495877.22 | 07-SEP-14:10 | 29.17 | 26.64 | 61.79 |
October | 0.430367E+11 | 657.13 | 20572.62 | 01-OCT-00:03 | 1412802.65 | 18-OCT-05:04 | 26.13 | 24.08 | 64.19 |
November | 0.245364E+11 | 566.85 | 20572.62 | 01-NOV-02:30 | 1403846.65 | 13-NOV-14:00 | 23.72 | 22.07 | 62.50 |
December | 0.882339E+10 | 489.17 | 20572.62 | 01-DEC-13:30 | 1250236.85 | 06-DEC-06:04 | 22.54 | 21.31 | 56.00 |
Annual Sum or Average | 0.365868E+12 | 7109.55 | 25.67 | 23.71 | 60.11 | ||||
Minimum of Months | 0.238395E+10 | 400.11 | 20572.62 | 1143149.92 | 22.43 | 21.31 | 45.72 | ||
Maximum of Months | 0.539282E+11 | 728.15 | 20572.62 | 1600009.58 | 30.49 | 27.48 | 66.98 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 22.43 | 22.43 | 0.00 |
February | 0.204903E+09 | 2.77 | 20572.62 | 06-FEB-06:04 | 1180523.45 | 09-FEB-06:04 | 22.70 | 22.68 | 0.31 |
March | 0.886029E+09 | 13.55 | 20572.62 | 01-MAR-13:30 | 1417881.54 | 23-MAR-14:50 | 22.81 | 22.75 | 1.38 |
April | 0.425135E+10 | 58.52 | 20572.62 | 03-APR-05:03 | 1406712.62 | 28-APR-09:10 | 23.57 | 23.33 | 6.00 |
May | 0.169889E+11 | 229.51 | 20572.62 | 01-MAY-00:23 | 1361211.90 | 04-MAY-09:20 | 25.84 | 24.91 | 21.14 |
June | 0.353799E+11 | 477.71 | 20572.62 | 01-JUN-05:02 | 1474087.54 | 08-JUN-05:04 | 28.52 | 26.52 | 41.30 |
July | 0.434271E+11 | 586.37 | 20572.62 | 01-JUL-00:03 | 1583456.28 | 19-JUL-15:00 | 29.88 | 27.37 | 50.15 |
August | 0.467914E+11 | 631.79 | 20572.62 | 01-AUG-00:03 | 1600009.58 | 10-AUG-16:00 | 30.49 | 27.71 | 54.71 |
September | 0.361422E+11 | 488.00 | 20572.62 | 01-SEP-00:30 | 1495877.22 | 07-SEP-14:10 | 29.17 | 27.07 | 43.12 |
October | 0.199031E+11 | 268.88 | 20572.62 | 01-OCT-00:33 | 1412802.65 | 18-OCT-05:04 | 26.13 | 25.06 | 24.24 |
November | 0.629824E+10 | 86.15 | 20572.62 | 01-NOV-04:23 | 1403846.65 | 13-NOV-14:00 | 23.72 | 23.36 | 8.80 |
December | 0.524133E+09 | 7.11 | 20572.62 | 04-DEC-11:50 | 1250236.85 | 06-DEC-06:04 | 22.54 | 22.52 | 0.72 |
Annual Sum or Average | 0.210797E+12 | 2850.36 | 25.67 | 24.65 | 21.12 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.43 | 22.43 | 0.00 | ||
Maximum of Months | 0.467914E+11 | 631.79 | 20572.62 | 1600009.58 | 30.49 | 27.71 | 54.71 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 8476375.49 | 0.00 | 13.89 | 636.64 | 20-JAN-07:00 | 0.00 | 66.28 | 66.50 | 0.00 | 0.00 | 0.00 | 0.00 | 20-JAN-07:00 |
February | 322989.95 | 0.00 | 1.67 | 125.93 | 13-FEB-06:50 | 0.00 | 59.38 | 59.43 | 0.00 | 0.00 | 0.00 | 0.00 | 13-FEB-06:50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 59.24 | 59.24 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 59.24 | 59.24 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 59.24 | 59.24 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 59.24 | 59.24 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 59.24 | 59.24 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 59.24 | 59.24 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 59.24 | 59.24 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 59.24 | 59.24 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 59.24 | 59.24 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 5176.04 | 0.00 | 0.17 | 8.63 | 18-DEC-07:00 | 0.00 | 59.24 | 59.24 | 0.00 | 0.00 | 0.00 | 0.00 | 18-DEC-07:00 |
Annual Sum or Average | 8804541.49 | 0.00 | 15.72 | 0.00 | 59.85 | 59.87 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.24 | 59.24 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 8476375.49 | 0.00 | 13.89 | 636.64 | 0.00 | 66.28 | 66.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 23.22 | 23.22 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 27.57 | 27.57 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 32.99 | 32.99 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 39.77 | 39.77 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 35.84 | 35.84 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 41.06 | 41.06 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 46.73 | 46.73 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 49.78 | 49.78 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 37.38 | 37.38 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 37.22 | 37.22 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 35.74 | 35.74 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 33.81 | 33.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 36.82 | 36.82 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.22 | 23.22 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.78 | 49.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.715098E+11 | 0.00 | 434.64 | 0.685013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 210057.45 | 30-JAN-06:03 | 141506.31 | 30-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.823144E+11 | 0.00 | 418.06 | 0.761813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 238223.07 | 06-FEB-06:02 | 157178.42 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.120093E+12 | 0.00 | 554.04 | 0.111849E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 227566.78 | 29-MAR-05:02 | 148093.82 | 29-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.156554E+12 | 0.00 | 615.91 | 0.136595E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 239846.38 | 10-APR-05:02 | 165313.11 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.198856E+12 | 0.00 | 604.84 | 0.162778E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 277216.22 | 30-MAY-05:03 | 168433.77 | 31-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.259662E+12 | 0.00 | 630.39 | 0.182053E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 289590.98 | 09-JUN-05:03 | 172947.59 | 12-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.313375E+12 | 0.00 | 652.01 | 0.206525E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 315478.37 | 05-JUL-05:02 | 184174.78 | 24-JUL-05:03 | 0.00 | 0.00 | 0.00 |
August | 0.343167E+12 | 0.00 | 659.36 | 0.225439E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 315396.11 | 21-AUG-05:03 | 191894.94 | 07-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.258940E+12 | 0.00 | 597.75 | 0.168713E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 290828.97 | 08-SEP-05:02 | 177907.43 | 05-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.212697E+12 | 0.00 | 611.81 | 0.157164E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 283739.98 | 02-OCT-05:02 | 171513.89 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.153081E+12 | 0.00 | 566.87 | 0.127375E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 250948.06 | 01-NOV-05:02 | 166052.45 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 0.109326E+12 | 0.00 | 545.25 | 0.976566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 211393.85 | 11-DEC-06:03 | 141476.72 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227958E+13 | 0.00 | 6890.93 | 0.172083E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.715098E+11 | 0.00 | 418.06 | 0.685013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 210057.45 | 141476.72 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.343167E+12 | 0.00 | 659.36 | 0.225439E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 315478.37 | 191894.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.530990E+12 | 0.00 | 408.86 | 0.507351E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1742980.36 | 30-JAN-06:03 | 1147878.04 | 30-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.601720E+12 | 0.00 | 376.22 | 0.552241E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2276203.65 | 09-FEB-06:02 | 1396689.22 | 09-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.876185E+12 | 0.00 | 451.94 | 0.809967E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2240589.37 | 29-MAR-05:02 | 1506296.34 | 28-MAR-05:03 | 0.00 | 0.00 | 0.00 |
April | 0.113308E+13 | 0.00 | 462.48 | 0.986900E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2395291.47 | 20-APR-05:03 | 1513841.15 | 28-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.178619E+13 | 0.00 | 558.54 | 0.145099E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2533727.43 | 24-MAY-05:03 | 1618815.02 | 23-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.230525E+13 | 0.00 | 581.70 | 0.157468E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2858237.39 | 27-JUN-05:02 | 1575637.75 | 28-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.280418E+13 | 0.00 | 622.29 | 0.176171E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3094915.38 | 12-JUL-05:02 | 1618005.56 | 12-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.303128E+13 | 0.00 | 634.48 | 0.187853E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3016435.50 | 26-AUG-05:02 | 1704172.09 | 05-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.235278E+13 | 0.00 | 555.86 | 0.148957E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2857715.88 | 28-SEP-05:02 | 1618256.73 | 07-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.174057E+13 | 0.00 | 511.82 | 0.126820E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2736818.30 | 07-OCT-05:03 | 1567063.94 | 11-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.114710E+13 | 0.00 | 438.79 | 0.932229E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2426652.64 | 10-NOV-06:02 | 1502190.59 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 0.696966E+12 | 0.00 | 414.69 | 0.614842E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2211389.18 | 11-DEC-06:03 | 1393337.90 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190063E+14 | 0.00 | 6017.68 | 0.138272E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.530990E+12 | 0.00 | 376.22 | 0.507351E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1742980.36 | 1147878.04 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.303128E+13 | 0.00 | 634.48 | 0.187853E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3094915.38 | 1704172.09 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.465427E+11 | 0.00 | 391.69 | 0.442504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 161812.33 | 30-JAN-06:03 | 101746.43 | 30-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.582734E+11 | 0.00 | 365.31 | 0.534156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 203629.73 | 06-FEB-06:02 | 134982.34 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.902165E+11 | 0.00 | 441.94 | 0.835813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 230405.10 | 29-MAR-05:02 | 158892.61 | 14-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.123160E+12 | 0.00 | 465.77 | 0.108122E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 235207.90 | 19-APR-05:02 | 164565.05 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.202818E+12 | 0.00 | 575.99 | 0.167612E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 292142.29 | 31-MAY-05:02 | 176809.05 | 31-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.260755E+12 | 0.00 | 597.45 | 0.184231E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 323496.95 | 27-JUN-05:02 | 192130.09 | 29-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.315049E+12 | 0.00 | 634.84 | 0.207566E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 349531.01 | 12-JUL-05:02 | 195247.53 | 24-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.338295E+12 | 0.00 | 647.93 | 0.219872E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 353462.43 | 08-AUG-05:02 | 205728.49 | 07-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.261473E+12 | 0.00 | 575.36 | 0.171210E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 325650.02 | 08-SEP-05:02 | 186014.64 | 13-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.188397E+12 | 0.00 | 521.89 | 0.139396E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 309527.36 | 02-OCT-05:02 | 177157.44 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.116495E+12 | 0.00 | 432.01 | 0.951350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 268405.01 | 01-NOV-05:02 | 159036.31 | 01-NOV-05:02 | 0.00 | 0.00 | 0.00 |
December | 0.653964E+11 | 0.00 | 398.22 | 0.574778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 194354.91 | 11-DEC-06:03 | 120919.46 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206687E+13 | 0.00 | 6048.41 | 0.153187E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.465427E+11 | 0.00 | 365.31 | 0.442504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 161812.33 | 101746.43 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.338295E+12 | 0.00 | 647.93 | 0.219872E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 353462.43 | 205728.49 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.651652E+11 | 0.00 | 421.76 | 0.636699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 148561.69 | 30-JAN-04:03 | 93620.56 | 17-JAN-05:03 | 0.00 | 0.00 | 0.00 |
February | 0.623564E+11 | 0.00 | 384.67 | 0.602227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 157275.66 | 09-FEB-04:02 | 93572.12 | 06-FEB-04:03 | 0.00 | 0.00 | 0.00 |
March | 0.760848E+11 | 0.00 | 447.32 | 0.734980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 165747.36 | 29-MAR-03:02 | 104201.21 | 02-MAR-04:02 | 0.00 | 0.00 | 0.00 |
April | 0.794076E+11 | 0.00 | 415.50 | 0.745458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167101.01 | 12-APR-03:02 | 106744.83 | 29-APR-03:02 | 0.00 | 0.00 | 0.00 |
May | 0.104581E+12 | 0.00 | 452.48 | 0.918537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 223211.15 | 30-MAY-01:30 | 109800.54 | 29-MAY-18:27 | 0.00 | 0.00 | 0.00 |
June | 0.123841E+12 | 0.00 | 450.01 | 0.967158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 230579.38 | 25-JUN-19:00 | 101056.26 | 11-JUN-16:51 | 0.00 | 0.00 | 0.00 |
July | 0.148819E+12 | 0.00 | 460.80 | 0.105362E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 241841.04 | 16-JUL-16:51 | 126873.94 | 30-JUL-12:40 | 0.00 | 0.00 | 0.00 |
August | 0.170581E+12 | 0.00 | 497.54 | 0.118822E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 236751.32 | 21-AUG-01:40 | 114740.84 | 13-AUG-14:59 | 0.00 | 0.00 | 0.00 |
September | 0.136720E+12 | 0.00 | 463.35 | 0.994039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 246570.98 | 10-SEP-15:22 | 115760.19 | 04-SEP-11:18 | 0.00 | 0.00 | 0.00 |
October | 0.120886E+12 | 0.00 | 478.57 | 0.974259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 224614.08 | 01-OCT-22:10 | 118058.53 | 15-OCT-13:08 | 0.00 | 0.00 | 0.00 |
November | 0.982572E+11 | 0.00 | 457.41 | 0.854695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 179864.54 | 03-NOV-03:02 | 117852.12 | 05-NOV-12:08 | 0.00 | 0.00 | 0.00 |
December | 0.761037E+11 | 0.00 | 448.01 | 0.715972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155756.59 | 06-DEC-04:02 | 95466.43 | 12-DEC-04:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126280E+13 | 0.00 | 5377.41 | 0.103859E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.623564E+11 | 0.00 | 384.67 | 0.602227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 148561.69 | 93572.12 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.170581E+12 | 0.00 | 497.54 | 0.118822E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 246570.98 | 126873.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.563873E+10 | 0.126335E+10 | 744.00 | 0.531344E+10 | 0.325293E+09 | 0.00 | 0.32 | 30-JAN-12:00 | 0.20 | 21-JAN-08:00 | 2633.43 | 30-JAN-15:00 | 2338.21 | 23-JAN-14:00 | 409.22 | 30-JAN-15:10 | 680.43 | 23-JAN-14:00 | 0.00 |
February | 0.998705E+10 | 0.220931E+10 | 672.00 | 0.954866E+10 | 0.438398E+09 | 0.00 | 0.58 | 07-FEB-16:10 | 0.43 | 01-FEB-07:00 | 4744.57 | 07-FEB-16:10 | 4370.08 | 05-FEB-17:20 | 476.72 | 07-FEB-16:10 | 1340.65 | 06-FEB-15:00 | 0.00 |
March | 0.162229E+11 | 0.372779E+10 | 744.00 | 0.157715E+11 | 0.451369E+09 | 0.00 | 0.90 | 31-MAR-23:10 | 0.64 | 08-MAR-07:00 | 8095.91 | 31-MAR-23:10 | 7640.85 | 31-MAR-23:35 | 480.30 | 28-MAR-16:10 | 2152.48 | 27-MAR-11:00 | 0.00 |
April | 0.209086E+11 | 0.513386E+10 | 720.00 | 0.203153E+11 | 0.593233E+09 | 0.00 | 1.00 | 02-APR-14:00 | 0.36 | 30-APR-23:13 | 8715.48 | 30-APR-18:00 | 8261.24 | 23-APR-17:30 | 592.19 | 30-APR-15:00 | 2825.24 | 28-APR-12:00 | 0.00 |
May | 0.698876E+10 | 0.210903E+10 | 744.00 | 0.628252E+10 | 0.706240E+09 | 0.00 | 0.57 | 31-MAY-23:05 | 0.27 | 03-MAY-06:00 | 4561.08 | 31-MAY-23:05 | 4141.85 | 31-MAY-23:50 | 639.57 | 30-MAY-02:00 | 1365.27 | 31-MAY-23:10 | 0.00 |
June | 0.122459E+11 | 0.367694E+10 | 720.00 | 0.110763E+11 | 0.116964E+10 | 0.00 | 0.80 | 30-JUN-23:03 | 0.51 | 03-JUN-06:40 | 6746.12 | 30-JUN-23:03 | 5985.77 | 30-JUN-23:55 | 791.00 | 30-JUN-23:03 | 1858.29 | 30-JUN-23:13 | 0.00 |
July | 0.181902E+11 | 0.558535E+10 | 744.00 | 0.167180E+11 | 0.147216E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.73 | 03-JUL-06:00 | 8578.70 | 31-JUL-23:57 | 7874.98 | 31-JUL-24:00 | 952.65 | 20-JUL-14:00 | 2624.62 | 21-JUL-12:00 | 0.00 |
August | 0.226836E+11 | 0.677624E+10 | 744.00 | 0.211301E+11 | 0.155356E+10 | 0.00 | 1.00 | 01-AUG-00:03 | 0.38 | 31-AUG-23:05 | 8813.69 | 21-AUG-04:53 | 8170.85 | 14-AUG-04:12 | 961.58 | 22-AUG-17:00 | 3017.43 | 16-AUG-12:00 | 0.00 |
September | 0.744417E+10 | 0.225297E+10 | 720.00 | 0.620203E+10 | 0.124214E+10 | 0.00 | 0.59 | 30-SEP-23:03 | 0.29 | 26-SEP-07:00 | 5020.16 | 30-SEP-23:03 | 4047.80 | 30-SEP-23:37 | 996.62 | 30-SEP-23:03 | 1302.26 | 30-SEP-23:03 | 0.00 |
October | 0.122428E+11 | 0.338263E+10 | 744.00 | 0.112406E+11 | 0.100217E+10 | 0.00 | 0.74 | 31-OCT-23:03 | 0.48 | 21-OCT-07:00 | 6257.31 | 31-OCT-23:03 | 5900.97 | 31-OCT-23:50 | 834.44 | 07-OCT-10:10 | 1593.27 | 31-OCT-23:13 | 0.00 |
November | 0.161808E+11 | 0.393946E+10 | 720.00 | 0.154688E+11 | 0.712007E+09 | 0.00 | 0.82 | 01-NOV-14:00 | 0.66 | 22-NOV-07:00 | 6883.91 | 01-NOV-15:00 | 6371.07 | 05-NOV-16:47 | 661.99 | 01-NOV-15:00 | 1986.09 | 01-NOV-14:00 | 0.00 |
December | 0.212353E+11 | 0.448432E+10 | 744.00 | 0.206706E+11 | 0.564721E+09 | 0.00 | 0.97 | 05-DEC-17:00 | 0.83 | 30-DEC-08:00 | 8604.67 | 05-DEC-17:00 | 8078.33 | 25-DEC-16:17 | 571.06 | 05-DEC-17:00 | 2170.84 | 10-DEC-12:05 | 0.00 |
Annual Sum or Average | 0.169969E+12 | 0.445412E+11 | 8760.00 | 0.159738E+12 | 0.102309E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.563873E+10 | 0.126335E+10 | 672.00 | 0.531344E+10 | 0.325293E+09 | 0.00 | 0.32 | 0.20 | 2633.43 | 2338.21 | 409.22 | 680.43 | 0.00 | ||||||
Maximum of Months | 0.226836E+11 | 0.677624E+10 | 744.00 | 0.211301E+11 | 0.155356E+10 | 0.00 | 1.00 | 0.83 | 8813.69 | 8261.24 | 996.62 | 3017.43 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.470828E+11 | 0.106663E+11 | 744.00 | 0.439619E+11 | 0.312090E+10 | 0.00 | 0.31 | 30-JAN-14:20 | 0.16 | 21-JAN-08:00 | 24088.55 | 30-JAN-15:00 | 21049.45 | 23-JAN-14:00 | 4005.77 | 30-JAN-15:10 | 6178.44 | 23-JAN-14:00 | 0.00 |
February | 0.906893E+11 | 0.201766E+11 | 672.00 | 0.863572E+11 | 0.433211E+10 | 0.00 | 0.57 | 07-FEB-16:10 | 0.40 | 15-FEB-07:00 | 45167.07 | 07-FEB-16:10 | 41171.30 | 06-FEB-15:00 | 4741.07 | 07-FEB-16:10 | 12689.92 | 06-FEB-15:00 | 0.00 |
March | 0.152815E+12 | 0.351891E+11 | 744.00 | 0.148316E+12 | 0.449894E+10 | 0.00 | 0.91 | 31-MAR-23:10 | 0.62 | 08-MAR-07:00 | 77543.06 | 31-MAR-23:10 | 73076.93 | 31-MAR-23:57 | 4847.15 | 31-MAR-23:10 | 20545.58 | 27-MAR-11:00 | 0.00 |
April | 0.199635E+12 | 0.489943E+11 | 720.00 | 0.193706E+12 | 0.592945E+10 | 0.00 | 1.00 | 06-APR-16:00 | 0.32 | 30-APR-23:13 | 83072.51 | 30-APR-18:00 | 78967.22 | 26-APR-14:20 | 5895.51 | 30-APR-15:00 | 26931.42 | 28-APR-12:00 | 0.00 |
May | 0.657560E+11 | 0.198482E+11 | 744.00 | 0.587742E+11 | 0.698176E+10 | 0.00 | 0.58 | 31-MAY-23:05 | 0.26 | 03-MAY-06:00 | 44265.66 | 31-MAY-23:05 | 40122.97 | 31-MAY-23:53 | 6273.23 | 30-MAY-02:00 | 13215.43 | 31-MAY-23:13 | 0.00 |
June | 0.116401E+12 | 0.349287E+11 | 720.00 | 0.104764E+12 | 0.116370E+11 | 0.00 | 0.81 | 30-JUN-23:03 | 0.51 | 03-JUN-06:40 | 65277.01 | 30-JUN-23:03 | 57787.08 | 30-JUN-23:55 | 8008.60 | 30-JUN-23:03 | 17935.27 | 30-JUN-23:57 | 0.00 |
July | 0.172895E+12 | 0.530607E+11 | 744.00 | 0.158216E+12 | 0.146792E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.72 | 03-JUL-06:00 | 81960.32 | 31-JUL-24:00 | 74954.76 | 31-JUL-24:00 | 9497.68 | 20-JUL-14:00 | 25059.05 | 21-JUL-12:00 | 0.00 |
August | 0.216219E+12 | 0.645722E+11 | 744.00 | 0.200693E+12 | 0.155266E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.35 | 31-AUG-23:05 | 83985.48 | 08-AUG-04:05 | 77376.58 | 06-AUG-04:53 | 9581.86 | 30-AUG-20:00 | 28762.71 | 16-AUG-12:00 | 0.00 |
September | 0.697702E+11 | 0.210993E+11 | 720.00 | 0.574969E+11 | 0.122733E+11 | 0.00 | 0.60 | 30-SEP-23:03 | 0.28 | 26-SEP-07:00 | 48984.72 | 30-SEP-23:03 | 38961.95 | 30-SEP-23:27 | 10227.87 | 30-SEP-23:03 | 12641.33 | 30-SEP-23:03 | 0.00 |
October | 0.116197E+12 | 0.320882E+11 | 744.00 | 0.106227E+12 | 0.996972E+10 | 0.00 | 0.75 | 31-OCT-23:13 | 0.47 | 21-OCT-07:00 | 60265.05 | 31-OCT-23:03 | 56904.28 | 31-OCT-23:53 | 8308.17 | 07-OCT-10:10 | 15335.76 | 31-OCT-23:13 | 0.00 |
November | 0.153323E+12 | 0.373541E+11 | 720.00 | 0.146226E+12 | 0.709756E+10 | 0.00 | 0.83 | 01-NOV-14:00 | 0.64 | 22-NOV-07:00 | 66143.38 | 01-NOV-15:00 | 59799.62 | 05-NOV-16:57 | 6597.67 | 01-NOV-15:00 | 19064.76 | 01-NOV-14:00 | 0.00 |
December | 0.199144E+12 | 0.421706E+11 | 744.00 | 0.193506E+12 | 0.563808E+10 | 0.00 | 0.97 | 05-DEC-17:00 | 0.80 | 30-DEC-08:00 | 82120.75 | 05-DEC-17:00 | 76424.33 | 06-DEC-16:50 | 5700.35 | 05-DEC-17:00 | 20431.78 | 10-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.159993E+13 | 0.420148E+12 | 8760.00 | 0.149824E+13 | 0.101685E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.470828E+11 | 0.106663E+11 | 672.00 | 0.439619E+11 | 0.312090E+10 | 0.00 | 0.31 | 0.16 | 24088.55 | 21049.45 | 4005.77 | 6178.44 | 0.00 | ||||||
Maximum of Months | 0.216219E+12 | 0.645722E+11 | 744.00 | 0.200693E+12 | 0.155266E+11 | 0.00 | 1.00 | 0.80 | 83985.48 | 78967.22 | 10227.87 | 28762.71 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.401152E+10 | 0.928499E+09 | 744.00 | 0.369756E+10 | 0.313959E+09 | 0.00 | 0.30 | 30-JAN-14:30 | 0.08 | 21-JAN-08:00 | 2455.21 | 30-JAN-15:00 | 2158.11 | 23-JAN-14:10 | 410.72 | 30-JAN-15:00 | 636.86 | 23-JAN-14:00 | 0.00 |
February | 0.871008E+10 | 0.196173E+10 | 672.00 | 0.826295E+10 | 0.447126E+09 | 0.00 | 0.57 | 07-FEB-16:10 | 0.33 | 12-FEB-08:00 | 4595.34 | 07-FEB-16:10 | 4194.48 | 06-FEB-15:00 | 482.40 | 07-FEB-16:10 | 1300.72 | 06-FEB-15:00 | 0.00 |
March | 0.151319E+11 | 0.351825E+10 | 744.00 | 0.146640E+11 | 0.467919E+09 | 0.00 | 0.88 | 31-MAR-23:10 | 0.56 | 08-MAR-08:00 | 7700.48 | 31-MAR-23:10 | 7237.51 | 31-MAR-23:57 | 494.61 | 31-MAR-23:10 | 2078.29 | 27-MAR-11:00 | 0.00 |
April | 0.200307E+11 | 0.495796E+10 | 720.00 | 0.194196E+11 | 0.611078E+09 | 0.00 | 1.00 | 24-APR-12:50 | 0.32 | 30-APR-23:13 | 8566.49 | 30-APR-18:00 | 8058.01 | 23-APR-17:10 | 600.10 | 30-APR-15:00 | 2791.78 | 28-APR-12:00 | 0.00 |
May | 0.678702E+10 | 0.205944E+10 | 744.00 | 0.606770E+10 | 0.719321E+09 | 0.00 | 0.57 | 31-MAY-23:05 | 0.25 | 03-MAY-07:00 | 4505.49 | 31-MAY-23:05 | 4068.41 | 31-MAY-23:50 | 638.82 | 30-MAY-02:00 | 1351.40 | 31-MAY-23:10 | 0.00 |
June | 0.118782E+11 | 0.358424E+10 | 720.00 | 0.106937E+11 | 0.118456E+10 | 0.00 | 0.79 | 30-JUN-23:03 | 0.49 | 03-JUN-06:50 | 6577.57 | 30-JUN-23:03 | 5807.51 | 30-JUN-23:42 | 808.25 | 30-JUN-23:03 | 1835.30 | 09-JUN-15:00 | 0.00 |
July | 0.176153E+11 | 0.543774E+10 | 744.00 | 0.161264E+11 | 0.148887E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.71 | 03-JUL-06:00 | 8438.08 | 31-JUL-23:03 | 7694.88 | 31-JUL-24:00 | 959.96 | 20-JUL-14:00 | 2580.85 | 30-JUL-13:52 | 0.00 |
August | 0.221301E+11 | 0.666623E+10 | 744.00 | 0.205476E+11 | 0.158244E+10 | 0.00 | 1.00 | 01-AUG-00:03 | 0.34 | 31-AUG-23:13 | 8606.77 | 08-AUG-07:40 | 7932.11 | 07-AUG-02:52 | 977.92 | 30-AUG-20:00 | 2981.58 | 16-AUG-12:00 | 0.00 |
September | 0.719276E+10 | 0.218691E+10 | 720.00 | 0.594162E+10 | 0.125114E+10 | 0.00 | 0.59 | 30-SEP-23:03 | 0.27 | 26-SEP-07:00 | 4948.20 | 30-SEP-23:03 | 3944.76 | 30-SEP-23:27 | 1020.75 | 30-SEP-23:03 | 1285.09 | 30-SEP-23:03 | 0.00 |
October | 0.117339E+11 | 0.326167E+10 | 744.00 | 0.107176E+11 | 0.101631E+10 | 0.00 | 0.73 | 31-OCT-23:13 | 0.44 | 21-OCT-07:00 | 6040.10 | 31-OCT-23:03 | 5697.22 | 31-OCT-23:53 | 841.69 | 07-OCT-10:10 | 1562.05 | 09-OCT-15:00 | 0.00 |
November | 0.152549E+11 | 0.374961E+10 | 720.00 | 0.145272E+11 | 0.727758E+09 | 0.00 | 0.81 | 01-NOV-14:00 | 0.60 | 22-NOV-07:40 | 6692.71 | 01-NOV-15:00 | 6131.13 | 05-NOV-16:57 | 667.91 | 01-NOV-15:00 | 1939.86 | 01-NOV-14:00 | 0.00 |
December | 0.195023E+11 | 0.417810E+10 | 744.00 | 0.189197E+11 | 0.582543E+09 | 0.00 | 0.95 | 05-DEC-16:50 | 0.72 | 31-DEC-07:50 | 8248.03 | 05-DEC-17:00 | 7676.55 | 06-DEC-16:40 | 577.14 | 05-DEC-17:00 | 2055.08 | 10-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.159979E+12 | 0.424904E+11 | 8760.00 | 0.149586E+12 | 0.103930E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.401152E+10 | 0.928499E+09 | 672.00 | 0.369756E+10 | 0.313959E+09 | 0.00 | 0.30 | 0.08 | 2455.21 | 2158.11 | 410.72 | 636.86 | 0.00 | ||||||
Maximum of Months | 0.221301E+11 | 0.666623E+10 | 744.00 | 0.205476E+11 | 0.158244E+10 | 0.00 | 1.00 | 0.72 | 8606.77 | 8058.01 | 1020.75 | 2981.58 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.17 | 0.00 | 91.17 | 96.08 | 214.21 | 0.00 | 0.00 | 0.00 |
February | 104.51 | 0.00 | 104.51 | 135.48 | 178.60 | 0.00 | 0.00 | 0.00 |
March | 120.04 | 0.00 | 120.04 | 198.22 | 131.65 | 0.00 | 0.00 | 0.00 |
April | 135.25 | 0.28 | 134.97 | 287.98 | 77.95 | 0.00 | 0.00 | 0.00 |
May | 152.23 | 4.46 | 147.77 | 440.24 | 17.58 | 0.00 | 0.00 | 0.00 |
June | 162.99 | 9.05 | 153.94 | 507.77 | 3.65 | 0.00 | 0.00 | 0.00 |
July | 149.56 | 4.31 | 145.25 | 561.63 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 139.23 | 1.15 | 138.08 | 549.42 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 126.83 | 0.01 | 126.81 | 420.00 | 6.05 | 0.00 | 0.00 | 0.00 |
October | 112.43 | 0.00 | 112.43 | 298.88 | 30.26 | 0.00 | 0.00 | 0.00 |
November | 96.52 | 0.00 | 96.52 | 188.13 | 92.57 | 0.00 | 0.00 | 0.00 |
December | 85.10 | 0.00 | 85.10 | 108.17 | 174.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.06 | 1.61 | 121.45 | 317.10 | 76.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.10 | 0.00 | 85.10 | 96.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.99 | 9.05 | 153.94 | 561.63 | 214.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.17 | 0.00 | 91.17 | 96.08 | 214.20 | 0.00 | 0.00 | 0.00 |
February | 104.51 | 0.00 | 104.51 | 135.48 | 178.60 | 0.00 | 0.00 | 0.00 |
March | 120.04 | 0.00 | 120.04 | 198.22 | 131.65 | 0.00 | 0.00 | 0.00 |
April | 135.24 | 0.28 | 134.97 | 287.98 | 77.95 | 0.00 | 0.00 | 0.00 |
May | 152.23 | 4.46 | 147.76 | 440.24 | 17.58 | 0.00 | 0.00 | 0.00 |
June | 162.99 | 9.05 | 153.94 | 507.77 | 3.65 | 0.00 | 0.00 | 0.00 |
July | 149.56 | 4.31 | 145.25 | 561.62 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 139.23 | 1.15 | 138.08 | 549.42 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 126.82 | 0.01 | 126.81 | 420.00 | 6.05 | 0.00 | 0.00 | 0.00 |
October | 112.43 | 0.00 | 112.43 | 298.87 | 30.26 | 0.00 | 0.00 | 0.00 |
November | 96.52 | 0.00 | 96.52 | 188.13 | 92.57 | 0.00 | 0.00 | 0.00 |
December | 85.09 | 0.00 | 85.09 | 108.17 | 174.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.06 | 1.61 | 121.44 | 317.10 | 76.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.09 | 0.00 | 85.09 | 96.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.99 | 9.05 | 153.94 | 561.62 | 214.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.17 | 0.00 | 91.17 | 96.08 | 214.20 | 0.00 | 0.00 | 0.00 |
February | 104.51 | 0.00 | 104.51 | 135.48 | 178.60 | 0.00 | 0.00 | 0.00 |
March | 120.04 | 0.00 | 120.04 | 198.22 | 131.65 | 0.00 | 0.00 | 0.00 |
April | 135.24 | 0.28 | 134.97 | 287.98 | 77.95 | 0.00 | 0.00 | 0.00 |
May | 152.23 | 4.46 | 147.77 | 440.24 | 17.58 | 0.00 | 0.00 | 0.00 |
June | 162.99 | 9.05 | 153.94 | 507.77 | 3.65 | 0.00 | 0.00 | 0.00 |
July | 149.56 | 4.31 | 145.25 | 561.62 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 139.23 | 1.15 | 138.08 | 549.42 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 126.82 | 0.01 | 126.81 | 420.00 | 6.05 | 0.00 | 0.00 | 0.00 |
October | 112.43 | 0.00 | 112.43 | 298.87 | 30.26 | 0.00 | 0.00 | 0.00 |
November | 96.52 | 0.00 | 96.52 | 188.13 | 92.57 | 0.00 | 0.00 | 0.00 |
December | 85.09 | 0.00 | 85.09 | 108.17 | 174.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.06 | 1.61 | 121.45 | 317.10 | 76.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.09 | 0.00 | 85.09 | 96.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.99 | 9.05 | 153.94 | 561.62 | 214.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.17 | 0.00 | 91.17 | 96.08 | 214.20 | 0.00 | 0.00 | 0.00 |
February | 104.51 | 0.00 | 104.51 | 135.48 | 178.60 | 0.00 | 0.00 | 0.00 |
March | 120.04 | 0.00 | 120.04 | 198.22 | 131.65 | 0.00 | 0.00 | 0.00 |
April | 135.24 | 0.28 | 134.97 | 287.98 | 77.95 | 0.00 | 0.00 | 0.00 |
May | 152.23 | 4.46 | 147.76 | 440.24 | 17.58 | 0.00 | 0.00 | 0.00 |
June | 162.99 | 9.05 | 153.94 | 507.77 | 3.65 | 0.00 | 0.00 | 0.00 |
July | 149.56 | 4.31 | 145.25 | 561.62 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 139.23 | 1.15 | 138.08 | 549.42 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 126.82 | 0.01 | 126.81 | 420.00 | 6.05 | 0.00 | 0.00 | 0.00 |
October | 112.43 | 0.00 | 112.43 | 298.87 | 30.26 | 0.00 | 0.00 | 0.00 |
November | 96.52 | 0.00 | 96.52 | 188.13 | 92.57 | 0.00 | 0.00 | 0.00 |
December | 85.09 | 0.00 | 85.09 | 108.17 | 174.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.06 | 1.61 | 121.44 | 317.10 | 76.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.09 | 0.00 | 85.09 | 96.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.99 | 9.05 | 153.94 | 561.62 | 214.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.17 | 0.00 | 91.17 | 96.08 | 214.20 | 0.00 | 0.00 | 0.00 |
February | 104.50 | 0.00 | 104.50 | 135.48 | 178.59 | 0.00 | 0.00 | 0.00 |
March | 120.03 | 0.00 | 120.03 | 198.21 | 131.65 | 0.00 | 0.00 | 0.00 |
April | 135.24 | 0.28 | 134.96 | 287.96 | 77.95 | 0.00 | 0.00 | 0.00 |
May | 152.22 | 4.46 | 147.76 | 440.22 | 17.58 | 0.00 | 0.00 | 0.00 |
June | 162.98 | 9.05 | 153.94 | 507.75 | 3.65 | 0.00 | 0.00 | 0.00 |
July | 149.55 | 4.31 | 145.24 | 561.60 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 139.22 | 1.15 | 138.07 | 549.39 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 126.82 | 0.01 | 126.80 | 419.98 | 6.05 | 0.00 | 0.00 | 0.00 |
October | 112.42 | 0.00 | 112.42 | 298.86 | 30.26 | 0.00 | 0.00 | 0.00 |
November | 96.51 | 0.00 | 96.51 | 188.12 | 92.57 | 0.00 | 0.00 | 0.00 |
December | 85.09 | 0.00 | 85.09 | 108.17 | 174.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.05 | 1.61 | 121.44 | 317.09 | 76.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.09 | 0.00 | 85.09 | 96.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.98 | 9.05 | 153.94 | 561.60 | 214.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.25 | 55.44 | 127.81 | 240.69 | 218.22 | 0.00 | 0.00 | 0.00 |
February | 199.70 | 54.12 | 145.58 | 294.70 | 181.47 | 0.00 | 0.00 | 0.00 |
March | 220.59 | 54.37 | 166.22 | 378.55 | 132.47 | 0.00 | 0.00 | 0.00 |
April | 268.58 | 78.25 | 190.32 | 541.66 | 76.59 | 0.00 | 0.00 | 0.00 |
May | 300.14 | 95.63 | 204.52 | 730.75 | 17.79 | 0.00 | 0.00 | 0.00 |
June | 293.94 | 89.89 | 204.05 | 773.22 | 2.80 | 0.00 | 0.00 | 0.00 |
July | 274.35 | 79.09 | 195.26 | 831.56 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 280.93 | 86.22 | 194.71 | 856.08 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 264.11 | 81.63 | 182.48 | 698.30 | 5.61 | 0.00 | 0.00 | 0.00 |
October | 239.65 | 78.29 | 161.36 | 546.28 | 28.18 | 0.00 | 0.00 | 0.00 |
November | 200.83 | 63.61 | 137.22 | 379.78 | 90.89 | 0.00 | 0.00 | 0.00 |
December | 162.55 | 44.60 | 117.95 | 238.34 | 172.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 240.88 | 71.84 | 169.04 | 543.92 | 76.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.55 | 44.60 | 117.95 | 238.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 300.14 | 95.63 | 204.52 | 856.08 | 218.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.25 | 55.44 | 127.81 | 240.69 | 218.22 | 0.00 | 0.00 | 0.00 |
February | 199.70 | 54.12 | 145.58 | 294.70 | 181.47 | 0.00 | 0.00 | 0.00 |
March | 220.59 | 54.37 | 166.22 | 378.55 | 132.47 | 0.00 | 0.00 | 0.00 |
April | 268.58 | 78.25 | 190.32 | 541.66 | 76.59 | 0.00 | 0.00 | 0.00 |
May | 300.14 | 95.63 | 204.52 | 730.75 | 17.79 | 0.00 | 0.00 | 0.00 |
June | 293.94 | 89.89 | 204.05 | 773.22 | 2.80 | 0.00 | 0.00 | 0.00 |
July | 274.35 | 79.09 | 195.26 | 831.56 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 280.93 | 86.22 | 194.71 | 856.08 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 264.11 | 81.63 | 182.48 | 698.30 | 5.61 | 0.00 | 0.00 | 0.00 |
October | 239.65 | 78.29 | 161.36 | 546.28 | 28.18 | 0.00 | 0.00 | 0.00 |
November | 200.83 | 63.61 | 137.22 | 379.78 | 90.89 | 0.00 | 0.00 | 0.00 |
December | 162.55 | 44.60 | 117.95 | 238.34 | 172.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 240.88 | 71.84 | 169.04 | 543.92 | 76.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.55 | 44.60 | 117.95 | 238.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 300.14 | 95.63 | 204.52 | 856.08 | 218.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 183.25 | 55.44 | 127.81 | 240.68 | 218.22 | 0.00 | 0.00 | 0.00 |
February | 199.70 | 54.12 | 145.58 | 294.69 | 181.47 | 0.00 | 0.00 | 0.00 |
March | 220.59 | 54.37 | 166.22 | 378.54 | 132.47 | 0.00 | 0.00 | 0.00 |
April | 268.57 | 78.25 | 190.32 | 541.65 | 76.59 | 0.00 | 0.00 | 0.00 |
May | 300.14 | 95.63 | 204.51 | 730.73 | 17.79 | 0.00 | 0.00 | 0.00 |
June | 293.94 | 89.89 | 204.05 | 773.21 | 2.80 | 0.00 | 0.00 | 0.00 |
July | 274.35 | 79.09 | 195.25 | 831.54 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 280.93 | 86.22 | 194.71 | 856.06 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 264.10 | 81.63 | 182.47 | 698.29 | 5.61 | 0.00 | 0.00 | 0.00 |
October | 239.65 | 78.29 | 161.35 | 546.27 | 28.18 | 0.00 | 0.00 | 0.00 |
November | 200.82 | 63.61 | 137.21 | 379.78 | 90.88 | 0.00 | 0.00 | 0.00 |
December | 162.55 | 44.60 | 117.95 | 238.34 | 172.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 240.87 | 71.83 | 169.04 | 543.91 | 76.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.55 | 44.60 | 117.95 | 238.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 300.14 | 95.63 | 204.51 | 856.06 | 218.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 294.65 | 138.53 | 156.12 | 452.26 | 202.62 | 0.00 | 0.00 | 0.00 |
February | 276.69 | 113.18 | 163.51 | 451.93 | 174.26 | 0.00 | 0.00 | 0.00 |
March | 227.73 | 61.83 | 165.90 | 415.89 | 133.38 | 0.00 | 0.00 | 0.00 |
April | 179.01 | 18.98 | 160.03 | 386.18 | 80.42 | 0.00 | 0.00 | 0.00 |
May | 151.64 | 2.32 | 149.31 | 439.03 | 17.91 | 0.00 | 0.00 | 0.00 |
June | 142.81 | 0.18 | 142.63 | 465.62 | 2.80 | 0.00 | 0.00 | 0.00 |
July | 142.80 | 1.21 | 141.59 | 545.46 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 165.64 | 11.74 | 153.90 | 608.10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 218.40 | 50.05 | 168.35 | 610.26 | 6.54 | 0.00 | 0.00 | 0.00 |
October | 285.93 | 113.67 | 172.25 | 634.69 | 32.60 | 0.00 | 0.00 | 0.00 |
November | 315.43 | 152.06 | 163.37 | 591.34 | 94.20 | 0.00 | 0.00 | 0.00 |
December | 292.82 | 144.64 | 148.17 | 478.15 | 168.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 224.15 | 67.12 | 157.03 | 506.95 | 75.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 142.80 | 0.18 | 141.59 | 386.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 315.43 | 152.06 | 172.25 | 634.69 | 202.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 294.64 | 138.53 | 156.12 | 452.26 | 202.62 | 0.00 | 0.00 | 0.00 |
February | 276.68 | 113.18 | 163.51 | 451.92 | 174.26 | 0.00 | 0.00 | 0.00 |
March | 227.72 | 61.83 | 165.90 | 415.88 | 133.38 | 0.00 | 0.00 | 0.00 |
April | 179.01 | 18.98 | 160.03 | 386.18 | 80.42 | 0.00 | 0.00 | 0.00 |
May | 151.64 | 2.32 | 149.31 | 439.03 | 17.91 | 0.00 | 0.00 | 0.00 |
June | 142.81 | 0.18 | 142.63 | 465.62 | 2.80 | 0.00 | 0.00 | 0.00 |
July | 142.80 | 1.21 | 141.59 | 545.46 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 165.64 | 11.74 | 153.90 | 608.10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 218.40 | 50.05 | 168.35 | 610.26 | 6.54 | 0.00 | 0.00 | 0.00 |
October | 285.92 | 113.67 | 172.25 | 634.68 | 32.60 | 0.00 | 0.00 | 0.00 |
November | 315.43 | 152.06 | 163.37 | 591.33 | 94.20 | 0.00 | 0.00 | 0.00 |
December | 292.82 | 144.64 | 148.17 | 478.14 | 168.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 224.15 | 67.12 | 157.03 | 506.95 | 75.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 142.80 | 0.18 | 141.59 | 386.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 315.43 | 152.06 | 172.25 | 634.68 | 202.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 294.65 | 138.53 | 156.12 | 452.26 | 202.62 | 0.00 | 0.00 | 0.00 |
February | 276.69 | 113.18 | 163.51 | 451.93 | 174.26 | 0.00 | 0.00 | 0.00 |
March | 227.73 | 61.83 | 165.90 | 415.89 | 133.38 | 0.00 | 0.00 | 0.00 |
April | 179.01 | 18.98 | 160.03 | 386.18 | 80.42 | 0.00 | 0.00 | 0.00 |
May | 151.64 | 2.32 | 149.31 | 439.03 | 17.91 | 0.00 | 0.00 | 0.00 |
June | 142.81 | 0.18 | 142.63 | 465.62 | 2.80 | 0.00 | 0.00 | 0.00 |
July | 142.80 | 1.21 | 141.59 | 545.46 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 165.64 | 11.74 | 153.90 | 608.10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 218.40 | 50.05 | 168.35 | 610.26 | 6.54 | 0.00 | 0.00 | 0.00 |
October | 285.93 | 113.67 | 172.25 | 634.69 | 32.60 | 0.00 | 0.00 | 0.00 |
November | 315.43 | 152.06 | 163.37 | 591.34 | 94.20 | 0.00 | 0.00 | 0.00 |
December | 292.82 | 144.64 | 148.17 | 478.15 | 168.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 224.15 | 67.12 | 157.03 | 506.95 | 75.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 142.80 | 0.18 | 141.59 | 386.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 315.43 | 152.06 | 172.25 | 634.69 | 202.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 294.64 | 138.53 | 156.12 | 452.26 | 202.62 | 0.00 | 0.00 | 0.00 |
February | 276.68 | 113.18 | 163.51 | 451.92 | 174.26 | 0.00 | 0.00 | 0.00 |
March | 227.72 | 61.83 | 165.90 | 415.88 | 133.38 | 0.00 | 0.00 | 0.00 |
April | 179.01 | 18.98 | 160.03 | 386.18 | 80.42 | 0.00 | 0.00 | 0.00 |
May | 151.64 | 2.32 | 149.31 | 439.03 | 17.91 | 0.00 | 0.00 | 0.00 |
June | 142.81 | 0.18 | 142.63 | 465.62 | 2.80 | 0.00 | 0.00 | 0.00 |
July | 142.80 | 1.21 | 141.59 | 545.46 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 165.64 | 11.74 | 153.90 | 608.10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 218.40 | 50.05 | 168.35 | 610.26 | 6.54 | 0.00 | 0.00 | 0.00 |
October | 285.92 | 113.67 | 172.25 | 634.68 | 32.60 | 0.00 | 0.00 | 0.00 |
November | 315.43 | 152.06 | 163.37 | 591.33 | 94.20 | 0.00 | 0.00 | 0.00 |
December | 292.82 | 144.64 | 148.17 | 478.14 | 168.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 224.15 | 67.12 | 157.03 | 506.95 | 75.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 142.80 | 0.18 | 141.59 | 386.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 315.43 | 152.06 | 172.25 | 634.68 | 202.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 294.63 | 138.52 | 156.11 | 452.24 | 202.61 | 0.00 | 0.00 | 0.00 |
February | 276.67 | 113.17 | 163.50 | 451.91 | 174.25 | 0.00 | 0.00 | 0.00 |
March | 227.72 | 61.82 | 165.89 | 415.87 | 133.37 | 0.00 | 0.00 | 0.00 |
April | 179.00 | 18.98 | 160.02 | 386.16 | 80.41 | 0.00 | 0.00 | 0.00 |
May | 151.63 | 2.32 | 149.31 | 439.01 | 17.91 | 0.00 | 0.00 | 0.00 |
June | 142.80 | 0.18 | 142.62 | 465.60 | 2.80 | 0.00 | 0.00 | 0.00 |
July | 142.80 | 1.21 | 141.58 | 545.44 | 0.05 | 0.00 | 0.00 | 0.00 |
August | 165.63 | 11.74 | 153.90 | 608.08 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 218.39 | 50.05 | 168.34 | 610.23 | 6.54 | 0.00 | 0.00 | 0.00 |
October | 285.91 | 113.67 | 172.25 | 634.66 | 32.60 | 0.00 | 0.00 | 0.00 |
November | 315.42 | 152.06 | 163.36 | 591.31 | 94.20 | 0.00 | 0.00 | 0.00 |
December | 292.80 | 144.64 | 148.17 | 478.12 | 168.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 224.14 | 67.12 | 157.02 | 506.93 | 75.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 142.80 | 0.18 | 141.58 | 386.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 315.42 | 152.06 | 172.25 | 634.66 | 202.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 179.71 | 51.61 | 128.10 | 240.74 | 257.66 | 0.00 | 0.00 | 0.00 |
February | 205.21 | 58.52 | 146.69 | 302.81 | 226.21 | 0.00 | 0.00 | 0.00 |
March | 243.08 | 71.96 | 171.11 | 408.40 | 178.31 | 0.00 | 0.00 | 0.00 |
April | 265.64 | 74.63 | 191.01 | 515.82 | 119.62 | 0.00 | 0.00 | 0.00 |
May | 289.15 | 86.55 | 202.60 | 697.93 | 28.36 | 0.00 | 0.00 | 0.00 |
June | 298.81 | 94.19 | 204.62 | 756.92 | 8.53 | 0.00 | 0.00 | 0.00 |
July | 274.13 | 78.42 | 195.71 | 789.00 | 0.63 | 0.00 | 0.00 | 0.00 |
August | 281.23 | 85.50 | 195.72 | 803.50 | 0.43 | 0.00 | 0.00 | 0.00 |
September | 267.52 | 84.05 | 183.47 | 684.48 | 10.90 | 0.00 | 0.00 | 0.00 |
October | 237.75 | 76.80 | 160.95 | 527.08 | 50.18 | 0.00 | 0.00 | 0.00 |
November | 204.31 | 66.82 | 137.50 | 377.33 | 132.95 | 0.00 | 0.00 | 0.00 |
December | 171.04 | 51.70 | 119.34 | 247.24 | 235.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 243.27 | 73.45 | 169.82 | 530.54 | 103.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 171.04 | 51.61 | 119.34 | 240.74 | 0.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 298.81 | 94.19 | 204.62 | 803.50 | 257.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 179.71 | 51.61 | 128.10 | 240.74 | 257.66 | 0.00 | 0.00 | 0.00 |
February | 205.21 | 58.52 | 146.69 | 302.81 | 226.21 | 0.00 | 0.00 | 0.00 |
March | 243.08 | 71.96 | 171.11 | 408.40 | 178.31 | 0.00 | 0.00 | 0.00 |
April | 265.64 | 74.63 | 191.01 | 515.82 | 119.62 | 0.00 | 0.00 | 0.00 |
May | 289.15 | 86.55 | 202.60 | 697.93 | 28.36 | 0.00 | 0.00 | 0.00 |
June | 298.81 | 94.19 | 204.62 | 756.92 | 8.53 | 0.00 | 0.00 | 0.00 |
July | 274.13 | 78.42 | 195.71 | 789.00 | 0.63 | 0.00 | 0.00 | 0.00 |
August | 281.23 | 85.50 | 195.72 | 803.50 | 0.43 | 0.00 | 0.00 | 0.00 |
September | 267.52 | 84.05 | 183.47 | 684.48 | 10.90 | 0.00 | 0.00 | 0.00 |
October | 237.75 | 76.80 | 160.95 | 527.08 | 50.18 | 0.00 | 0.00 | 0.00 |
November | 204.31 | 66.82 | 137.50 | 377.33 | 132.95 | 0.00 | 0.00 | 0.00 |
December | 171.04 | 51.70 | 119.34 | 247.24 | 235.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 243.27 | 73.45 | 169.82 | 530.54 | 103.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 171.04 | 51.61 | 119.34 | 240.74 | 0.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 298.81 | 94.19 | 204.62 | 803.50 | 257.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 179.71 | 51.61 | 128.09 | 240.73 | 257.65 | 0.00 | 0.00 | 0.00 |
February | 205.21 | 58.52 | 146.69 | 302.80 | 226.20 | 0.00 | 0.00 | 0.00 |
March | 243.07 | 71.96 | 171.11 | 408.39 | 178.31 | 0.00 | 0.00 | 0.00 |
April | 265.64 | 74.63 | 191.01 | 515.81 | 119.62 | 0.00 | 0.00 | 0.00 |
May | 289.15 | 86.55 | 202.59 | 697.92 | 28.36 | 0.00 | 0.00 | 0.00 |
June | 298.81 | 94.19 | 204.62 | 756.91 | 8.53 | 0.00 | 0.00 | 0.00 |
July | 274.12 | 78.42 | 195.70 | 788.99 | 0.63 | 0.00 | 0.00 | 0.00 |
August | 281.22 | 85.50 | 195.72 | 803.48 | 0.43 | 0.00 | 0.00 | 0.00 |
September | 267.51 | 84.05 | 183.47 | 684.47 | 10.90 | 0.00 | 0.00 | 0.00 |
October | 237.74 | 76.80 | 160.94 | 527.07 | 50.18 | 0.00 | 0.00 | 0.00 |
November | 204.31 | 66.82 | 137.49 | 377.33 | 132.95 | 0.00 | 0.00 | 0.00 |
December | 171.04 | 51.70 | 119.34 | 247.23 | 235.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 243.26 | 73.45 | 169.82 | 530.53 | 103.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 171.04 | 51.61 | 119.34 | 240.73 | 0.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 298.81 | 94.19 | 204.62 | 803.48 | 257.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 455.85 | 0.00 | 455.85 | 512.55 | 965.12 | 0.00 | 0.00 | 0.00 |
February | 522.53 | 0.00 | 522.53 | 707.52 | 802.28 | 0.00 | 0.00 | 0.00 |
March | 600.20 | 0.00 | 600.20 | 1012.95 | 614.46 | 0.00 | 0.00 | 0.00 |
April | 676.23 | 1.39 | 674.84 | 1464.95 | 383.27 | 0.00 | 0.00 | 0.00 |
May | 761.16 | 22.32 | 738.83 | 2222.85 | 91.51 | 0.00 | 0.00 | 0.00 |
June | 814.96 | 45.24 | 769.72 | 2572.16 | 18.34 | 0.00 | 0.00 | 0.00 |
July | 747.81 | 21.55 | 726.26 | 2867.19 | 0.22 | 0.00 | 0.00 | 0.00 |
August | 696.15 | 5.76 | 690.39 | 2823.01 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 634.13 | 0.07 | 634.05 | 2136.15 | 31.26 | 0.00 | 0.00 | 0.00 |
October | 562.14 | 0.00 | 562.14 | 1527.79 | 152.67 | 0.00 | 0.00 | 0.00 |
November | 482.58 | 0.00 | 482.58 | 970.37 | 438.84 | 0.00 | 0.00 | 0.00 |
December | 425.48 | 0.00 | 425.48 | 575.36 | 784.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 615.29 | 8.05 | 607.23 | 1621.68 | 354.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 425.48 | 0.00 | 425.48 | 512.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 814.96 | 45.24 | 769.72 | 2867.19 | 965.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 549.75 | 166.33 | 383.42 | 733.88 | 610.61 | 0.00 | 0.00 | 0.00 |
February | 599.10 | 162.36 | 436.74 | 889.92 | 513.80 | 0.00 | 0.00 | 0.00 |
March | 661.76 | 163.10 | 498.66 | 1131.64 | 397.26 | 0.00 | 0.00 | 0.00 |
April | 805.72 | 234.76 | 570.96 | 1613.52 | 253.39 | 0.00 | 0.00 | 0.00 |
May | 900.42 | 286.88 | 613.54 | 2185.55 | 60.16 | 0.00 | 0.00 | 0.00 |
June | 881.82 | 269.67 | 612.15 | 2314.06 | 10.46 | 0.00 | 0.00 | 0.00 |
July | 823.04 | 237.28 | 585.76 | 2498.09 | 0.08 | 0.00 | 0.00 | 0.00 |
August | 842.78 | 258.66 | 584.12 | 2576.88 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 792.31 | 244.90 | 547.42 | 2094.10 | 19.37 | 0.00 | 0.00 | 0.00 |
October | 718.95 | 234.88 | 484.07 | 1634.56 | 97.24 | 0.00 | 0.00 | 0.00 |
November | 602.48 | 190.83 | 411.64 | 1134.95 | 283.40 | 0.00 | 0.00 | 0.00 |
December | 487.65 | 133.79 | 353.86 | 720.27 | 499.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 722.63 | 215.51 | 507.12 | 1631.57 | 227.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 487.65 | 133.79 | 353.86 | 720.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 900.42 | 286.88 | 613.54 | 2576.88 | 610.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1473.26 | 692.65 | 780.61 | 2244.86 | 988.73 | 0.00 | 0.00 | 0.00 |
February | 1383.45 | 565.89 | 817.56 | 2248.28 | 838.96 | 0.00 | 0.00 | 0.00 |
March | 1138.64 | 309.14 | 829.51 | 2075.04 | 651.83 | 0.00 | 0.00 | 0.00 |
April | 895.06 | 94.89 | 800.17 | 1940.94 | 403.18 | 0.00 | 0.00 | 0.00 |
May | 758.19 | 11.61 | 746.58 | 2217.22 | 92.12 | 0.00 | 0.00 | 0.00 |
June | 714.04 | 0.88 | 713.16 | 2369.42 | 13.11 | 0.00 | 0.00 | 0.00 |
July | 714.02 | 6.07 | 707.96 | 2784.64 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 828.21 | 58.68 | 769.53 | 3105.81 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1092.01 | 250.26 | 841.74 | 3066.29 | 34.89 | 0.00 | 0.00 | 0.00 |
October | 1429.65 | 568.37 | 861.28 | 3172.09 | 171.94 | 0.00 | 0.00 | 0.00 |
November | 1577.19 | 760.32 | 816.87 | 2944.34 | 474.52 | 0.00 | 0.00 | 0.00 |
December | 1464.11 | 723.23 | 740.89 | 2382.57 | 822.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1120.75 | 335.61 | 785.14 | 2548.03 | 372.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 714.02 | 0.88 | 707.96 | 1940.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1577.19 | 760.32 | 861.28 | 3172.09 | 988.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 539.13 | 154.84 | 384.28 | 749.59 | 674.65 | 0.00 | 0.00 | 0.00 |
February | 615.63 | 175.55 | 440.07 | 941.37 | 569.78 | 0.00 | 0.00 | 0.00 |
March | 729.23 | 215.89 | 513.34 | 1258.72 | 450.26 | 0.00 | 0.00 | 0.00 |
April | 796.92 | 223.89 | 573.03 | 1591.57 | 297.96 | 0.00 | 0.00 | 0.00 |
May | 867.45 | 259.66 | 607.78 | 2120.42 | 77.33 | 0.00 | 0.00 | 0.00 |
June | 896.43 | 282.58 | 613.85 | 2328.94 | 15.84 | 0.00 | 0.00 | 0.00 |
July | 822.38 | 235.27 | 587.11 | 2465.84 | 0.27 | 0.00 | 0.00 | 0.00 |
August | 843.67 | 256.51 | 587.16 | 2531.46 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 802.55 | 252.14 | 550.41 | 2092.10 | 28.02 | 0.00 | 0.00 | 0.00 |
October | 713.23 | 230.39 | 482.84 | 1621.24 | 126.81 | 0.00 | 0.00 | 0.00 |
November | 612.93 | 200.45 | 412.48 | 1171.67 | 329.78 | 0.00 | 0.00 | 0.00 |
December | 513.12 | 155.11 | 358.01 | 790.30 | 566.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 729.80 | 220.34 | 509.46 | 1642.61 | 259.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 513.12 | 154.84 | 358.01 | 749.59 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 896.43 | 282.58 | 613.85 | 2531.46 | 674.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 455.85 | 0.00 | 455.85 | 548.49 | 865.38 | 0.00 | 0.00 | 0.00 |
February | 522.53 | 0.00 | 522.53 | 726.58 | 742.50 | 0.00 | 0.00 | 0.00 |
March | 600.20 | 0.00 | 600.20 | 1012.93 | 587.29 | 0.00 | 0.00 | 0.00 |
April | 676.23 | 1.39 | 674.84 | 1446.27 | 383.42 | 0.00 | 0.00 | 0.00 |
May | 761.16 | 22.32 | 738.83 | 2184.73 | 95.61 | 0.00 | 0.00 | 0.00 |
June | 814.96 | 45.24 | 769.72 | 2525.95 | 20.99 | 0.00 | 0.00 | 0.00 |
July | 747.81 | 21.55 | 726.26 | 2806.21 | 0.53 | 0.00 | 0.00 | 0.00 |
August | 696.15 | 5.76 | 690.39 | 2766.90 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 634.13 | 0.07 | 634.05 | 2096.06 | 32.30 | 0.00 | 0.00 | 0.00 |
October | 562.14 | 0.00 | 562.14 | 1504.94 | 156.16 | 0.00 | 0.00 | 0.00 |
November | 482.58 | 0.00 | 482.58 | 967.04 | 421.45 | 0.00 | 0.00 | 0.00 |
December | 425.48 | 0.00 | 425.48 | 597.45 | 719.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 615.29 | 8.05 | 607.23 | 1604.04 | 333.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 425.48 | 0.00 | 425.48 | 548.49 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 814.96 | 45.24 | 769.72 | 2806.21 | 865.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 549.75 | 166.33 | 383.42 | 759.85 | 560.08 | 0.00 | 0.00 | 0.00 |
February | 599.10 | 162.36 | 436.74 | 901.33 | 484.56 | 0.00 | 0.00 | 0.00 |
March | 661.76 | 163.10 | 498.66 | 1129.93 | 385.21 | 0.00 | 0.00 | 0.00 |
April | 805.72 | 234.76 | 570.96 | 1599.48 | 256.29 | 0.00 | 0.00 | 0.00 |
May | 900.42 | 286.88 | 613.54 | 2157.21 | 62.98 | 0.00 | 0.00 | 0.00 |
June | 881.82 | 269.67 | 612.15 | 2279.95 | 12.19 | 0.00 | 0.00 | 0.00 |
July | 823.04 | 237.28 | 585.76 | 2453.87 | 0.26 | 0.00 | 0.00 | 0.00 |
August | 842.78 | 258.66 | 584.12 | 2535.92 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 792.31 | 244.90 | 547.42 | 2064.06 | 19.99 | 0.00 | 0.00 | 0.00 |
October | 718.95 | 234.88 | 484.07 | 1616.39 | 100.38 | 0.00 | 0.00 | 0.00 |
November | 602.48 | 190.83 | 411.64 | 1130.83 | 276.12 | 0.00 | 0.00 | 0.00 |
December | 487.65 | 133.79 | 353.86 | 735.31 | 467.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 722.63 | 215.51 | 507.12 | 1617.83 | 217.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 487.65 | 133.79 | 353.86 | 735.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 900.42 | 286.88 | 613.54 | 2535.92 | 560.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1473.26 | 692.65 | 780.61 | 2269.97 | 914.49 | 0.00 | 0.00 | 0.00 |
February | 1383.45 | 565.89 | 817.56 | 2256.65 | 792.64 | 0.00 | 0.00 | 0.00 |
March | 1138.64 | 309.14 | 829.51 | 2068.80 | 629.71 | 0.00 | 0.00 | 0.00 |
April | 895.06 | 94.89 | 800.17 | 1921.80 | 403.44 | 0.00 | 0.00 | 0.00 |
May | 758.19 | 11.61 | 746.58 | 2180.09 | 94.80 | 0.00 | 0.00 | 0.00 |
June | 714.04 | 0.88 | 713.16 | 2325.22 | 14.27 | 0.00 | 0.00 | 0.00 |
July | 714.02 | 6.07 | 707.96 | 2724.89 | 0.16 | 0.00 | 0.00 | 0.00 |
August | 828.21 | 58.68 | 769.53 | 3050.88 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1092.01 | 250.26 | 841.74 | 3025.24 | 35.74 | 0.00 | 0.00 | 0.00 |
October | 1429.65 | 568.37 | 861.28 | 3144.91 | 177.04 | 0.00 | 0.00 | 0.00 |
November | 1577.19 | 760.32 | 816.87 | 2932.57 | 464.54 | 0.00 | 0.00 | 0.00 |
December | 1464.11 | 723.23 | 740.89 | 2393.34 | 777.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1120.75 | 335.61 | 785.14 | 2526.44 | 356.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 714.02 | 0.88 | 707.96 | 1921.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1577.19 | 760.32 | 861.28 | 3144.91 | 914.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 539.13 | 154.84 | 384.28 | 766.15 | 620.15 | 0.00 | 0.00 | 0.00 |
February | 615.63 | 175.55 | 440.07 | 948.57 | 536.52 | 0.00 | 0.00 | 0.00 |
March | 729.23 | 215.89 | 513.34 | 1254.30 | 435.35 | 0.00 | 0.00 | 0.00 |
April | 796.92 | 223.89 | 573.03 | 1577.87 | 297.39 | 0.00 | 0.00 | 0.00 |
May | 867.45 | 259.66 | 607.78 | 2096.26 | 78.69 | 0.00 | 0.00 | 0.00 |
June | 896.43 | 282.58 | 613.85 | 2301.28 | 16.91 | 0.00 | 0.00 | 0.00 |
July | 822.38 | 235.27 | 587.11 | 2429.61 | 0.42 | 0.00 | 0.00 | 0.00 |
August | 843.67 | 256.51 | 587.16 | 2498.46 | 0.10 | 0.00 | 0.00 | 0.00 |
September | 802.55 | 252.14 | 550.41 | 2067.75 | 28.15 | 0.00 | 0.00 | 0.00 |
October | 713.23 | 230.39 | 482.84 | 1606.19 | 128.46 | 0.00 | 0.00 | 0.00 |
November | 612.93 | 200.45 | 412.48 | 1166.41 | 319.93 | 0.00 | 0.00 | 0.00 |
December | 513.12 | 155.11 | 358.01 | 799.05 | 530.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 729.80 | 220.34 | 509.46 | 1629.89 | 247.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 513.12 | 154.84 | 358.01 | 766.15 | 0.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 896.43 | 282.58 | 613.85 | 2498.46 | 620.15 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244189E+09 | 0.00 | 0.244189E+09 | 0.257348E+09 | 0.573728E+09 |
February | 0.252823E+09 | 0.00 | 0.252823E+09 | 0.327764E+09 | 0.432066E+09 |
March | 0.321516E+09 | 0.00 | 0.321516E+09 | 0.530913E+09 | 0.352622E+09 |
April | 0.350558E+09 | 722302.30 | 0.349836E+09 | 0.746438E+09 | 0.202048E+09 |
May | 0.407737E+09 | 11958603.11 | 0.395778E+09 | 0.117915E+10 | 47087363.06 |
June | 0.422477E+09 | 23454509.89 | 0.399022E+09 | 0.131614E+10 | 9453302.01 |
July | 0.400586E+09 | 11541783.44 | 0.389044E+09 | 0.150426E+10 | 270074.91 |
August | 0.372912E+09 | 3084328.06 | 0.369827E+09 | 0.147156E+10 | 2762.51 |
September | 0.328730E+09 | 37669.26 | 0.328693E+09 | 0.108864E+10 | 15678738.45 |
October | 0.301126E+09 | 0.00 | 0.301126E+09 | 0.800509E+09 | 81051675.86 |
November | 0.250171E+09 | 0.00 | 0.250171E+09 | 0.487625E+09 | 0.239947E+09 |
December | 0.227919E+09 | 0.00 | 0.227919E+09 | 0.289725E+09 | 0.468291E+09 |
Annual Sum or Average | 0.388074E+10 | 50799196.06 | 0.382995E+10 | 0.100001E+11 | 0.242225E+10 |
Minimum of Months | 0.227919E+09 | 0.00 | 0.227919E+09 | 0.257348E+09 | 2762.51 |
Maximum of Months | 0.422477E+09 | 23454509.89 | 0.399022E+09 | 0.150426E+10 | 0.573728E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244186E+09 | 0.00 | 0.244186E+09 | 0.257343E+09 | 0.573725E+09 |
February | 0.252819E+09 | 0.00 | 0.252819E+09 | 0.327759E+09 | 0.432064E+09 |
March | 0.321511E+09 | 0.00 | 0.321511E+09 | 0.530907E+09 | 0.352620E+09 |
April | 0.350553E+09 | 722286.42 | 0.349831E+09 | 0.746432E+09 | 0.202045E+09 |
May | 0.407731E+09 | 11958340.21 | 0.395773E+09 | 0.117914E+10 | 47086159.08 |
June | 0.422471E+09 | 23453994.27 | 0.399017E+09 | 0.131614E+10 | 9452782.03 |
July | 0.400580E+09 | 11541529.71 | 0.389039E+09 | 0.150425E+10 | 270044.70 |
August | 0.372906E+09 | 3084260.25 | 0.369822E+09 | 0.147156E+10 | 2760.01 |
September | 0.328726E+09 | 37668.43 | 0.328688E+09 | 0.108863E+10 | 15678191.43 |
October | 0.301122E+09 | 0.00 | 0.301122E+09 | 0.800504E+09 | 81049768.19 |
November | 0.250168E+09 | 0.00 | 0.250168E+09 | 0.487621E+09 | 0.239944E+09 |
December | 0.227916E+09 | 0.00 | 0.227916E+09 | 0.289720E+09 | 0.468288E+09 |
Annual Sum or Average | 0.388069E+10 | 50798079.30 | 0.382989E+10 | 0.100000E+11 | 0.242223E+10 |
Minimum of Months | 0.227916E+09 | 0.00 | 0.227916E+09 | 0.257343E+09 | 2760.01 |
Maximum of Months | 0.422471E+09 | 23453994.27 | 0.399017E+09 | 0.150425E+10 | 0.573725E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244187E+09 | 0.00 | 0.244187E+09 | 0.257345E+09 | 0.573726E+09 |
February | 0.252820E+09 | 0.00 | 0.252820E+09 | 0.327760E+09 | 0.432065E+09 |
March | 0.321512E+09 | 0.00 | 0.321512E+09 | 0.530909E+09 | 0.352620E+09 |
April | 0.350555E+09 | 722291.71 | 0.349832E+09 | 0.746434E+09 | 0.202046E+09 |
May | 0.407733E+09 | 11958427.84 | 0.395775E+09 | 0.117914E+10 | 47086560.41 |
June | 0.422473E+09 | 23454166.14 | 0.399019E+09 | 0.131614E+10 | 9452955.35 |
July | 0.400582E+09 | 11541614.29 | 0.389041E+09 | 0.150426E+10 | 270054.77 |
August | 0.372908E+09 | 3084282.86 | 0.369824E+09 | 0.147156E+10 | 2760.84 |
September | 0.328727E+09 | 37668.71 | 0.328690E+09 | 0.108863E+10 | 15678373.77 |
October | 0.301123E+09 | 0.00 | 0.301123E+09 | 0.800506E+09 | 81050404.09 |
November | 0.250169E+09 | 0.00 | 0.250169E+09 | 0.487622E+09 | 0.239945E+09 |
December | 0.227917E+09 | 0.00 | 0.227917E+09 | 0.289722E+09 | 0.468289E+09 |
Annual Sum or Average | 0.388071E+10 | 50798451.55 | 0.382991E+10 | 0.100000E+11 | 0.242223E+10 |
Minimum of Months | 0.227917E+09 | 0.00 | 0.227917E+09 | 0.257345E+09 | 2760.84 |
Maximum of Months | 0.422473E+09 | 23454166.14 | 0.399019E+09 | 0.150426E+10 | 0.573726E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244186E+09 | 0.00 | 0.244186E+09 | 0.257343E+09 | 0.573725E+09 |
February | 0.252819E+09 | 0.00 | 0.252819E+09 | 0.327759E+09 | 0.432064E+09 |
March | 0.321511E+09 | 0.00 | 0.321511E+09 | 0.530907E+09 | 0.352620E+09 |
April | 0.350553E+09 | 722286.42 | 0.349831E+09 | 0.746432E+09 | 0.202045E+09 |
May | 0.407731E+09 | 11958340.21 | 0.395773E+09 | 0.117914E+10 | 47086159.08 |
June | 0.422471E+09 | 23453994.27 | 0.399017E+09 | 0.131614E+10 | 9452782.03 |
July | 0.400580E+09 | 11541529.71 | 0.389039E+09 | 0.150425E+10 | 270044.70 |
August | 0.372906E+09 | 3084260.25 | 0.369822E+09 | 0.147156E+10 | 2760.01 |
September | 0.328726E+09 | 37668.43 | 0.328688E+09 | 0.108863E+10 | 15678191.43 |
October | 0.301122E+09 | 0.00 | 0.301122E+09 | 0.800504E+09 | 81049768.19 |
November | 0.250168E+09 | 0.00 | 0.250168E+09 | 0.487621E+09 | 0.239944E+09 |
December | 0.227916E+09 | 0.00 | 0.227916E+09 | 0.289720E+09 | 0.468288E+09 |
Annual Sum or Average | 0.388069E+10 | 50798079.30 | 0.382989E+10 | 0.100000E+11 | 0.242223E+10 |
Minimum of Months | 0.227916E+09 | 0.00 | 0.227916E+09 | 0.257343E+09 | 2760.01 |
Maximum of Months | 0.422471E+09 | 23453994.27 | 0.399017E+09 | 0.150425E+10 | 0.573725E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244176E+09 | 0.00 | 0.244176E+09 | 0.257334E+09 | 0.573702E+09 |
February | 0.252809E+09 | 0.00 | 0.252809E+09 | 0.327746E+09 | 0.432047E+09 |
March | 0.321499E+09 | 0.00 | 0.321499E+09 | 0.530887E+09 | 0.352606E+09 |
April | 0.350540E+09 | 722259.96 | 0.349817E+09 | 0.746403E+09 | 0.202037E+09 |
May | 0.407716E+09 | 11957902.05 | 0.395758E+09 | 0.117909E+10 | 47084461.96 |
June | 0.422455E+09 | 23453134.90 | 0.399002E+09 | 0.131608E+10 | 9452487.70 |
July | 0.400565E+09 | 11541106.82 | 0.389024E+09 | 0.150419E+10 | 270038.85 |
August | 0.372892E+09 | 3084147.25 | 0.369808E+09 | 0.147150E+10 | 2760.32 |
September | 0.328713E+09 | 37667.05 | 0.328676E+09 | 0.108859E+10 | 15677650.70 |
October | 0.301110E+09 | 0.00 | 0.301110E+09 | 0.800473E+09 | 81046819.46 |
November | 0.250158E+09 | 0.00 | 0.250158E+09 | 0.487602E+09 | 0.239935E+09 |
December | 0.227907E+09 | 0.00 | 0.227907E+09 | 0.289709E+09 | 0.468270E+09 |
Annual Sum or Average | 0.388054E+10 | 50796218.03 | 0.382974E+10 | 0.999961E+10 | 0.242213E+10 |
Minimum of Months | 0.227907E+09 | 0.00 | 0.227907E+09 | 0.257334E+09 | 2760.32 |
Maximum of Months | 0.422455E+09 | 23453134.90 | 0.399002E+09 | 0.150419E+10 | 0.573702E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.490818E+09 | 0.148497E+09 | 0.342322E+09 | 0.644660E+09 | 0.584486E+09 |
February | 0.483117E+09 | 0.130927E+09 | 0.352190E+09 | 0.712932E+09 | 0.439014E+09 |
March | 0.590829E+09 | 0.145618E+09 | 0.445211E+09 | 0.101390E+10 | 0.354809E+09 |
April | 0.696153E+09 | 0.202836E+09 | 0.493317E+09 | 0.140398E+10 | 0.198526E+09 |
May | 0.803902E+09 | 0.256128E+09 | 0.547775E+09 | 0.195723E+10 | 47647296.81 |
June | 0.761902E+09 | 0.232998E+09 | 0.528904E+09 | 0.200419E+10 | 7253272.14 |
July | 0.734822E+09 | 0.211848E+09 | 0.522974E+09 | 0.222725E+10 | 152606.07 |
August | 0.752445E+09 | 0.230936E+09 | 0.521509E+09 | 0.229292E+10 | 0.00 |
September | 0.684567E+09 | 0.211592E+09 | 0.472975E+09 | 0.180999E+10 | 14534067.88 |
October | 0.641882E+09 | 0.209703E+09 | 0.432179E+09 | 0.146315E+10 | 75479278.17 |
November | 0.520548E+09 | 0.164883E+09 | 0.355665E+09 | 0.984401E+09 | 0.235578E+09 |
December | 0.435378E+09 | 0.119450E+09 | 0.315928E+09 | 0.638377E+09 | 0.461054E+09 |
Annual Sum or Average | 0.759636E+10 | 0.226541E+10 | 0.533095E+10 | 0.171530E+11 | 0.241853E+10 |
Minimum of Months | 0.435378E+09 | 0.119450E+09 | 0.315928E+09 | 0.638377E+09 | 0.00 |
Maximum of Months | 0.803902E+09 | 0.256128E+09 | 0.547775E+09 | 0.229292E+10 | 0.584486E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.490818E+09 | 0.148497E+09 | 0.342322E+09 | 0.644660E+09 | 0.584486E+09 |
February | 0.483117E+09 | 0.130927E+09 | 0.352190E+09 | 0.712932E+09 | 0.439014E+09 |
March | 0.590829E+09 | 0.145618E+09 | 0.445211E+09 | 0.101390E+10 | 0.354809E+09 |
April | 0.696153E+09 | 0.202836E+09 | 0.493317E+09 | 0.140398E+10 | 0.198526E+09 |
May | 0.803902E+09 | 0.256128E+09 | 0.547775E+09 | 0.195723E+10 | 47647296.81 |
June | 0.761902E+09 | 0.232998E+09 | 0.528904E+09 | 0.200419E+10 | 7253272.14 |
July | 0.734822E+09 | 0.211848E+09 | 0.522974E+09 | 0.222725E+10 | 152606.07 |
August | 0.752445E+09 | 0.230936E+09 | 0.521509E+09 | 0.229292E+10 | 0.00 |
September | 0.684567E+09 | 0.211592E+09 | 0.472975E+09 | 0.180999E+10 | 14534067.88 |
October | 0.641882E+09 | 0.209703E+09 | 0.432179E+09 | 0.146315E+10 | 75479278.17 |
November | 0.520548E+09 | 0.164883E+09 | 0.355665E+09 | 0.984401E+09 | 0.235578E+09 |
December | 0.435378E+09 | 0.119450E+09 | 0.315928E+09 | 0.638377E+09 | 0.461054E+09 |
Annual Sum or Average | 0.759636E+10 | 0.226541E+10 | 0.533095E+10 | 0.171530E+11 | 0.241853E+10 |
Minimum of Months | 0.435378E+09 | 0.119450E+09 | 0.315928E+09 | 0.638377E+09 | 0.00 |
Maximum of Months | 0.803902E+09 | 0.256128E+09 | 0.547775E+09 | 0.229292E+10 | 0.584486E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.490809E+09 | 0.148494E+09 | 0.342316E+09 | 0.644648E+09 | 0.584475E+09 |
February | 0.483108E+09 | 0.130925E+09 | 0.352183E+09 | 0.712919E+09 | 0.439006E+09 |
March | 0.590818E+09 | 0.145615E+09 | 0.445203E+09 | 0.101388E+10 | 0.354802E+09 |
April | 0.696141E+09 | 0.202833E+09 | 0.493308E+09 | 0.140395E+10 | 0.198523E+09 |
May | 0.803888E+09 | 0.256123E+09 | 0.547765E+09 | 0.195719E+10 | 47646426.19 |
June | 0.761888E+09 | 0.232994E+09 | 0.528894E+09 | 0.200415E+10 | 7253139.61 |
July | 0.734808E+09 | 0.211844E+09 | 0.522964E+09 | 0.222721E+10 | 152603.28 |
August | 0.752431E+09 | 0.230931E+09 | 0.521500E+09 | 0.229288E+10 | 0.00 |
September | 0.684554E+09 | 0.211588E+09 | 0.472967E+09 | 0.180996E+10 | 14533802.31 |
October | 0.641870E+09 | 0.209699E+09 | 0.432171E+09 | 0.146313E+10 | 75477899.00 |
November | 0.520538E+09 | 0.164880E+09 | 0.355658E+09 | 0.984383E+09 | 0.235574E+09 |
December | 0.435370E+09 | 0.119448E+09 | 0.315922E+09 | 0.638365E+09 | 0.461045E+09 |
Annual Sum or Average | 0.759622E+10 | 0.226537E+10 | 0.533085E+10 | 0.171527E+11 | 0.241849E+10 |
Minimum of Months | 0.435370E+09 | 0.119448E+09 | 0.315922E+09 | 0.638365E+09 | 0.00 |
Maximum of Months | 0.803888E+09 | 0.256123E+09 | 0.547765E+09 | 0.229288E+10 | 0.584475E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.789181E+09 | 0.371029E+09 | 0.418153E+09 | 0.121135E+10 | 0.542705E+09 |
February | 0.669358E+09 | 0.273796E+09 | 0.395562E+09 | 0.109330E+10 | 0.421563E+09 |
March | 0.609939E+09 | 0.165594E+09 | 0.444345E+09 | 0.111391E+10 | 0.357244E+09 |
April | 0.463993E+09 | 49191616.64 | 0.414801E+09 | 0.100097E+10 | 0.208440E+09 |
May | 0.406145E+09 | 6219631.86 | 0.399925E+09 | 0.117590E+10 | 47970839.24 |
June | 0.370157E+09 | 458077.22 | 0.369699E+09 | 0.120688E+10 | 7263464.97 |
July | 0.382485E+09 | 3249915.17 | 0.379235E+09 | 0.146095E+10 | 137628.13 |
August | 0.443651E+09 | 31434157.27 | 0.412217E+09 | 0.162874E+10 | 2701.48 |
September | 0.566088E+09 | 0.129735E+09 | 0.436353E+09 | 0.158179E+10 | 16951960.85 |
October | 0.765822E+09 | 0.304456E+09 | 0.461366E+09 | 0.169994E+10 | 87319815.66 |
November | 0.817603E+09 | 0.394144E+09 | 0.423459E+09 | 0.153274E+10 | 0.244173E+09 |
December | 0.784282E+09 | 0.387410E+09 | 0.396872E+09 | 0.128066E+10 | 0.452382E+09 |
Annual Sum or Average | 0.706870E+10 | 0.211672E+10 | 0.495199E+10 | 0.159872E+11 | 0.238615E+10 |
Minimum of Months | 0.370157E+09 | 458077.22 | 0.369699E+09 | 0.100097E+10 | 2701.48 |
Maximum of Months | 0.817603E+09 | 0.394144E+09 | 0.461366E+09 | 0.169994E+10 | 0.542705E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.789176E+09 | 0.371026E+09 | 0.418150E+09 | 0.121134E+10 | 0.542704E+09 |
February | 0.669354E+09 | 0.273794E+09 | 0.395560E+09 | 0.109330E+10 | 0.421562E+09 |
March | 0.609936E+09 | 0.165593E+09 | 0.444343E+09 | 0.111390E+10 | 0.357244E+09 |
April | 0.463990E+09 | 49191256.16 | 0.414799E+09 | 0.100097E+10 | 0.208439E+09 |
May | 0.406143E+09 | 6219586.28 | 0.399923E+09 | 0.117590E+10 | 47970442.77 |
June | 0.370155E+09 | 458073.87 | 0.369697E+09 | 0.120688E+10 | 7263329.13 |
July | 0.382483E+09 | 3249891.36 | 0.379233E+09 | 0.146095E+10 | 137620.65 |
August | 0.443649E+09 | 31433926.92 | 0.412215E+09 | 0.162874E+10 | 2700.71 |
September | 0.566084E+09 | 0.129734E+09 | 0.436351E+09 | 0.158179E+10 | 16951771.02 |
October | 0.765817E+09 | 0.304454E+09 | 0.461363E+09 | 0.169993E+10 | 87319171.13 |
November | 0.817597E+09 | 0.394141E+09 | 0.423456E+09 | 0.153273E+10 | 0.244172E+09 |
December | 0.784277E+09 | 0.387408E+09 | 0.396869E+09 | 0.128066E+10 | 0.452381E+09 |
Annual Sum or Average | 0.706866E+10 | 0.211670E+10 | 0.495196E+10 | 0.159871E+11 | 0.238615E+10 |
Minimum of Months | 0.370155E+09 | 458073.87 | 0.369697E+09 | 0.100097E+10 | 2700.71 |
Maximum of Months | 0.817597E+09 | 0.394141E+09 | 0.461363E+09 | 0.169993E+10 | 0.542704E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.789181E+09 | 0.371029E+09 | 0.418153E+09 | 0.121135E+10 | 0.542705E+09 |
February | 0.669358E+09 | 0.273796E+09 | 0.395562E+09 | 0.109330E+10 | 0.421563E+09 |
March | 0.609939E+09 | 0.165594E+09 | 0.444345E+09 | 0.111391E+10 | 0.357244E+09 |
April | 0.463993E+09 | 49191616.64 | 0.414801E+09 | 0.100097E+10 | 0.208440E+09 |
May | 0.406145E+09 | 6219631.86 | 0.399925E+09 | 0.117590E+10 | 47970839.24 |
June | 0.370157E+09 | 458077.22 | 0.369699E+09 | 0.120688E+10 | 7263464.97 |
July | 0.382485E+09 | 3249915.17 | 0.379235E+09 | 0.146095E+10 | 137628.13 |
August | 0.443651E+09 | 31434157.27 | 0.412217E+09 | 0.162874E+10 | 2701.48 |
September | 0.566088E+09 | 0.129735E+09 | 0.436353E+09 | 0.158179E+10 | 16951960.85 |
October | 0.765822E+09 | 0.304456E+09 | 0.461366E+09 | 0.169994E+10 | 87319815.66 |
November | 0.817603E+09 | 0.394144E+09 | 0.423459E+09 | 0.153274E+10 | 0.244173E+09 |
December | 0.784282E+09 | 0.387410E+09 | 0.396872E+09 | 0.128066E+10 | 0.452382E+09 |
Annual Sum or Average | 0.706870E+10 | 0.211672E+10 | 0.495199E+10 | 0.159872E+11 | 0.238615E+10 |
Minimum of Months | 0.370157E+09 | 458077.22 | 0.369699E+09 | 0.100097E+10 | 2701.48 |
Maximum of Months | 0.817603E+09 | 0.394144E+09 | 0.461366E+09 | 0.169994E+10 | 0.542705E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.789176E+09 | 0.371026E+09 | 0.418150E+09 | 0.121134E+10 | 0.542704E+09 |
February | 0.669354E+09 | 0.273794E+09 | 0.395560E+09 | 0.109330E+10 | 0.421562E+09 |
March | 0.609936E+09 | 0.165593E+09 | 0.444343E+09 | 0.111390E+10 | 0.357244E+09 |
April | 0.463990E+09 | 49191256.16 | 0.414799E+09 | 0.100097E+10 | 0.208439E+09 |
May | 0.406143E+09 | 6219586.28 | 0.399923E+09 | 0.117590E+10 | 47970442.77 |
June | 0.370155E+09 | 458073.87 | 0.369697E+09 | 0.120688E+10 | 7263329.13 |
July | 0.382483E+09 | 3249891.36 | 0.379233E+09 | 0.146095E+10 | 137620.65 |
August | 0.443649E+09 | 31433926.92 | 0.412215E+09 | 0.162874E+10 | 2700.71 |
September | 0.566084E+09 | 0.129734E+09 | 0.436351E+09 | 0.158179E+10 | 16951771.02 |
October | 0.765817E+09 | 0.304454E+09 | 0.461363E+09 | 0.169993E+10 | 87319171.13 |
November | 0.817597E+09 | 0.394141E+09 | 0.423456E+09 | 0.153273E+10 | 0.244172E+09 |
December | 0.784277E+09 | 0.387408E+09 | 0.396869E+09 | 0.128066E+10 | 0.452381E+09 |
Annual Sum or Average | 0.706866E+10 | 0.211670E+10 | 0.495196E+10 | 0.159871E+11 | 0.238615E+10 |
Minimum of Months | 0.370155E+09 | 458073.87 | 0.369697E+09 | 0.100097E+10 | 2700.71 |
Maximum of Months | 0.817597E+09 | 0.394141E+09 | 0.461363E+09 | 0.169993E+10 | 0.542704E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.789147E+09 | 0.371012E+09 | 0.418134E+09 | 0.121129E+10 | 0.542683E+09 |
February | 0.669329E+09 | 0.273784E+09 | 0.395545E+09 | 0.109326E+10 | 0.421546E+09 |
March | 0.609913E+09 | 0.165587E+09 | 0.444326E+09 | 0.111386E+10 | 0.357230E+09 |
April | 0.463973E+09 | 49189453.77 | 0.414783E+09 | 0.100093E+10 | 0.208431E+09 |
May | 0.406127E+09 | 6219358.39 | 0.399908E+09 | 0.117585E+10 | 47968707.58 |
June | 0.370141E+09 | 458057.08 | 0.369683E+09 | 0.120683E+10 | 7263104.30 |
July | 0.382468E+09 | 3249772.28 | 0.379219E+09 | 0.146090E+10 | 137618.85 |
August | 0.443632E+09 | 31432775.17 | 0.412199E+09 | 0.162867E+10 | 2700.99 |
September | 0.566063E+09 | 0.129729E+09 | 0.436334E+09 | 0.158173E+10 | 16951182.70 |
October | 0.765788E+09 | 0.304443E+09 | 0.461346E+09 | 0.169987E+10 | 87315974.04 |
November | 0.817567E+09 | 0.394127E+09 | 0.423440E+09 | 0.153267E+10 | 0.244163E+09 |
December | 0.784248E+09 | 0.387393E+09 | 0.396854E+09 | 0.128061E+10 | 0.452364E+09 |
Annual Sum or Average | 0.706840E+10 | 0.211662E+10 | 0.495177E+10 | 0.159865E+11 | 0.238605E+10 |
Minimum of Months | 0.370141E+09 | 458057.08 | 0.369683E+09 | 0.100093E+10 | 2700.99 |
Maximum of Months | 0.817567E+09 | 0.394127E+09 | 0.461346E+09 | 0.169987E+10 | 0.542683E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.481336E+09 | 0.138244E+09 | 0.343093E+09 | 0.644792E+09 | 0.690104E+09 |
February | 0.496446E+09 | 0.141566E+09 | 0.354880E+09 | 0.732552E+09 | 0.547240E+09 |
March | 0.651062E+09 | 0.192748E+09 | 0.458313E+09 | 0.109386E+10 | 0.477585E+09 |
April | 0.688547E+09 | 0.193445E+09 | 0.495102E+09 | 0.133701E+10 | 0.310050E+09 |
May | 0.774463E+09 | 0.231828E+09 | 0.542635E+09 | 0.186934E+10 | 75957580.60 |
June | 0.774525E+09 | 0.244151E+09 | 0.530374E+09 | 0.196194E+10 | 22103147.12 |
July | 0.734228E+09 | 0.210048E+09 | 0.524180E+09 | 0.211326E+10 | 1679346.95 |
August | 0.753237E+09 | 0.229016E+09 | 0.524221E+09 | 0.215209E+10 | 1140126.79 |
September | 0.693408E+09 | 0.217849E+09 | 0.475559E+09 | 0.177418E+10 | 28252609.09 |
October | 0.636778E+09 | 0.205697E+09 | 0.431081E+09 | 0.141174E+10 | 0.134396E+09 |
November | 0.529579E+09 | 0.173189E+09 | 0.356390E+09 | 0.978046E+09 | 0.344613E+09 |
December | 0.458118E+09 | 0.138481E+09 | 0.319637E+09 | 0.662204E+09 | 0.630972E+09 |
Annual Sum or Average | 0.767173E+10 | 0.231626E+10 | 0.535546E+10 | 0.167310E+11 | 0.326409E+10 |
Minimum of Months | 0.458118E+09 | 0.138244E+09 | 0.319637E+09 | 0.644792E+09 | 1140126.79 |
Maximum of Months | 0.774525E+09 | 0.244151E+09 | 0.542635E+09 | 0.215209E+10 | 0.690104E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.481336E+09 | 0.138244E+09 | 0.343093E+09 | 0.644792E+09 | 0.690104E+09 |
February | 0.496446E+09 | 0.141566E+09 | 0.354880E+09 | 0.732552E+09 | 0.547240E+09 |
March | 0.651062E+09 | 0.192748E+09 | 0.458313E+09 | 0.109386E+10 | 0.477585E+09 |
April | 0.688547E+09 | 0.193445E+09 | 0.495102E+09 | 0.133701E+10 | 0.310050E+09 |
May | 0.774463E+09 | 0.231828E+09 | 0.542635E+09 | 0.186934E+10 | 75957580.60 |
June | 0.774525E+09 | 0.244151E+09 | 0.530374E+09 | 0.196194E+10 | 22103147.12 |
July | 0.734228E+09 | 0.210048E+09 | 0.524180E+09 | 0.211326E+10 | 1679346.95 |
August | 0.753237E+09 | 0.229016E+09 | 0.524221E+09 | 0.215209E+10 | 1140126.79 |
September | 0.693408E+09 | 0.217849E+09 | 0.475559E+09 | 0.177418E+10 | 28252609.09 |
October | 0.636778E+09 | 0.205697E+09 | 0.431081E+09 | 0.141174E+10 | 0.134396E+09 |
November | 0.529579E+09 | 0.173189E+09 | 0.356390E+09 | 0.978046E+09 | 0.344613E+09 |
December | 0.458118E+09 | 0.138481E+09 | 0.319637E+09 | 0.662204E+09 | 0.630972E+09 |
Annual Sum or Average | 0.767173E+10 | 0.231626E+10 | 0.535546E+10 | 0.167310E+11 | 0.326409E+10 |
Minimum of Months | 0.458118E+09 | 0.138244E+09 | 0.319637E+09 | 0.644792E+09 | 1140126.79 |
Maximum of Months | 0.774525E+09 | 0.244151E+09 | 0.542635E+09 | 0.215209E+10 | 0.690104E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.481328E+09 | 0.138241E+09 | 0.343086E+09 | 0.644780E+09 | 0.690092E+09 |
February | 0.496437E+09 | 0.141564E+09 | 0.354873E+09 | 0.732539E+09 | 0.547230E+09 |
March | 0.651050E+09 | 0.192745E+09 | 0.458305E+09 | 0.109384E+10 | 0.477577E+09 |
April | 0.688534E+09 | 0.193441E+09 | 0.495093E+09 | 0.133699E+10 | 0.310045E+09 |
May | 0.774449E+09 | 0.231824E+09 | 0.542625E+09 | 0.186931E+10 | 75956192.69 |
June | 0.774511E+09 | 0.244147E+09 | 0.530364E+09 | 0.196190E+10 | 22102743.25 |
July | 0.734215E+09 | 0.210044E+09 | 0.524170E+09 | 0.211322E+10 | 1679316.26 |
August | 0.753223E+09 | 0.229012E+09 | 0.524211E+09 | 0.215205E+10 | 1140105.96 |
September | 0.693396E+09 | 0.217845E+09 | 0.475551E+09 | 0.177415E+10 | 28252092.86 |
October | 0.636766E+09 | 0.205693E+09 | 0.431073E+09 | 0.141171E+10 | 0.134393E+09 |
November | 0.529569E+09 | 0.173186E+09 | 0.356383E+09 | 0.978028E+09 | 0.344607E+09 |
December | 0.458110E+09 | 0.138479E+09 | 0.319632E+09 | 0.662192E+09 | 0.630961E+09 |
Annual Sum or Average | 0.767159E+10 | 0.231622E+10 | 0.535537E+10 | 0.167307E+11 | 0.326403E+10 |
Minimum of Months | 0.458110E+09 | 0.138241E+09 | 0.319632E+09 | 0.644780E+09 | 1140105.96 |
Maximum of Months | 0.774511E+09 | 0.244147E+09 | 0.542625E+09 | 0.215205E+10 | 0.690092E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122095E+10 | 0.00 | 0.122095E+10 | 0.137282E+10 | 0.258498E+10 |
February | 0.126412E+10 | 0.00 | 0.126412E+10 | 0.171163E+10 | 0.194087E+10 |
March | 0.160758E+10 | 0.00 | 0.160758E+10 | 0.271309E+10 | 0.164577E+10 |
April | 0.175279E+10 | 3611534.52 | 0.174918E+10 | 0.379715E+10 | 0.993425E+09 |
May | 0.203868E+10 | 59793396.57 | 0.197889E+10 | 0.595367E+10 | 0.245094E+09 |
June | 0.211239E+10 | 0.117273E+09 | 0.199511E+10 | 0.666703E+10 | 47538364.97 |
July | 0.200293E+10 | 57709284.98 | 0.194522E+10 | 0.767949E+10 | 588768.74 |
August | 0.186456E+10 | 15421738.58 | 0.184914E+10 | 0.756115E+10 | 986.26 |
September | 0.164365E+10 | 188347.50 | 0.164346E+10 | 0.553691E+10 | 81025960.95 |
October | 0.150563E+10 | 0.00 | 0.150563E+10 | 0.409203E+10 | 0.408919E+09 |
November | 0.125086E+10 | 0.00 | 0.125086E+10 | 0.251519E+10 | 0.113749E+10 |
December | 0.113960E+10 | 0.00 | 0.113960E+10 | 0.154105E+10 | 0.210121E+10 |
Annual Sum or Average | 0.194037E+11 | 0.253998E+09 | 0.191497E+11 | 0.511412E+11 | 0.111869E+11 |
Minimum of Months | 0.113960E+10 | 0.00 | 0.113960E+10 | 0.137282E+10 | 986.26 |
Maximum of Months | 0.211239E+10 | 0.117273E+09 | 0.199511E+10 | 0.767949E+10 | 0.258498E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147244E+10 | 0.445485E+09 | 0.102695E+10 | 0.196564E+10 | 0.163546E+10 |
February | 0.144933E+10 | 0.392777E+09 | 0.105656E+10 | 0.215289E+10 | 0.124298E+10 |
March | 0.177247E+10 | 0.436849E+09 | 0.133562E+10 | 0.303097E+10 | 0.106402E+10 |
April | 0.208844E+10 | 0.608502E+09 | 0.147994E+10 | 0.418223E+10 | 0.656788E+09 |
May | 0.241168E+10 | 0.768375E+09 | 0.164331E+10 | 0.585378E+10 | 0.161142E+09 |
June | 0.228568E+10 | 0.698987E+09 | 0.158670E+10 | 0.599805E+10 | 27113040.85 |
July | 0.220444E+10 | 0.635537E+09 | 0.156891E+10 | 0.669090E+10 | 205550.33 |
August | 0.225731E+10 | 0.692800E+09 | 0.156451E+10 | 0.690191E+10 | 0.00 |
September | 0.205368E+10 | 0.634768E+09 | 0.141891E+10 | 0.542790E+10 | 50196809.51 |
October | 0.192563E+10 | 0.629103E+09 | 0.129652E+10 | 0.437800E+10 | 0.260458E+09 |
November | 0.156163E+10 | 0.494644E+09 | 0.106698E+10 | 0.294179E+10 | 0.734564E+09 |
December | 0.130612E+10 | 0.358346E+09 | 0.947773E+09 | 0.192918E+10 | 0.133915E+10 |
Annual Sum or Average | 0.227889E+11 | 0.679617E+10 | 0.159927E+11 | 0.514532E+11 | 0.717208E+10 |
Minimum of Months | 0.130612E+10 | 0.358346E+09 | 0.947773E+09 | 0.192918E+10 | 0.00 |
Maximum of Months | 0.241168E+10 | 0.768375E+09 | 0.164331E+10 | 0.690191E+10 | 0.163546E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.394598E+10 | 0.185518E+10 | 0.209079E+10 | 0.601263E+10 | 0.264822E+10 |
February | 0.334685E+10 | 0.136901E+10 | 0.197784E+10 | 0.543904E+10 | 0.202961E+10 |
March | 0.304974E+10 | 0.827989E+09 | 0.222175E+10 | 0.555780E+10 | 0.174586E+10 |
April | 0.231999E+10 | 0.245963E+09 | 0.207403E+10 | 0.503092E+10 | 0.104504E+10 |
May | 0.203074E+10 | 31098813.25 | 0.199964E+10 | 0.593861E+10 | 0.246731E+09 |
June | 0.185080E+10 | 2290434.28 | 0.184851E+10 | 0.614154E+10 | 33993886.80 |
July | 0.191244E+10 | 16249917.57 | 0.189619E+10 | 0.745837E+10 | 81996.39 |
August | 0.221828E+10 | 0.157174E+09 | 0.206111E+10 | 0.831861E+10 | 0.00 |
September | 0.283048E+10 | 0.648687E+09 | 0.218179E+10 | 0.794781E+10 | 90425107.28 |
October | 0.382917E+10 | 0.152231E+10 | 0.230686E+10 | 0.849614E+10 | 0.460518E+09 |
November | 0.408809E+10 | 0.197076E+10 | 0.211732E+10 | 0.763173E+10 | 0.122996E+10 |
December | 0.392148E+10 | 0.193709E+10 | 0.198439E+10 | 0.638149E+10 | 0.220335E+10 |
Annual Sum or Average | 0.353440E+11 | 0.105838E+11 | 0.247602E+11 | 0.803547E+11 | 0.117338E+11 |
Minimum of Months | 0.185080E+10 | 2290434.28 | 0.184851E+10 | 0.503092E+10 | 0.00 |
Maximum of Months | 0.408809E+10 | 0.197076E+10 | 0.230686E+10 | 0.849614E+10 | 0.264822E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144399E+10 | 0.414727E+09 | 0.102927E+10 | 0.200770E+10 | 0.180698E+10 |
February | 0.148932E+10 | 0.424695E+09 | 0.106463E+10 | 0.227736E+10 | 0.137840E+10 |
March | 0.195316E+10 | 0.578239E+09 | 0.137493E+10 | 0.337136E+10 | 0.120599E+10 |
April | 0.206562E+10 | 0.580329E+09 | 0.148529E+10 | 0.412534E+10 | 0.772315E+09 |
May | 0.232336E+10 | 0.695476E+09 | 0.162789E+10 | 0.567934E+10 | 0.207122E+09 |
June | 0.232355E+10 | 0.732446E+09 | 0.159111E+10 | 0.603660E+10 | 41059092.66 |
July | 0.220266E+10 | 0.630138E+09 | 0.157252E+10 | 0.660451E+10 | 728041.49 |
August | 0.225969E+10 | 0.687041E+09 | 0.157265E+10 | 0.678026E+10 | 151506.20 |
September | 0.208020E+10 | 0.653540E+09 | 0.142666E+10 | 0.542272E+10 | 72637690.68 |
October | 0.191031E+10 | 0.617084E+09 | 0.129323E+10 | 0.434232E+10 | 0.339645E+09 |
November | 0.158872E+10 | 0.519563E+09 | 0.106916E+10 | 0.303696E+10 | 0.854790E+09 |
December | 0.137434E+10 | 0.415439E+09 | 0.958902E+09 | 0.211675E+10 | 0.151669E+10 |
Annual Sum or Average | 0.230149E+11 | 0.694872E+10 | 0.160662E+11 | 0.518012E+11 | 0.819651E+10 |
Minimum of Months | 0.137434E+10 | 0.414727E+09 | 0.958902E+09 | 0.200770E+10 | 151506.20 |
Maximum of Months | 0.232355E+10 | 0.732446E+09 | 0.162789E+10 | 0.678026E+10 | 0.180698E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122095E+10 | 0.00 | 0.122095E+10 | 0.146907E+10 | 0.231785E+10 |
February | 0.126412E+10 | 0.00 | 0.126412E+10 | 0.175773E+10 | 0.179625E+10 |
March | 0.160758E+10 | 0.00 | 0.160758E+10 | 0.271304E+10 | 0.157301E+10 |
April | 0.175279E+10 | 3611534.52 | 0.174918E+10 | 0.374874E+10 | 0.993815E+09 |
May | 0.203868E+10 | 59793396.57 | 0.197889E+10 | 0.585158E+10 | 0.256087E+09 |
June | 0.211239E+10 | 0.117273E+09 | 0.199511E+10 | 0.654727E+10 | 54394939.39 |
July | 0.200293E+10 | 57709284.98 | 0.194522E+10 | 0.751614E+10 | 1419422.84 |
August | 0.186456E+10 | 15421738.58 | 0.184914E+10 | 0.741088E+10 | 25782.47 |
September | 0.164365E+10 | 188347.50 | 0.164346E+10 | 0.543298E+10 | 83716491.11 |
October | 0.150563E+10 | 0.00 | 0.150563E+10 | 0.403082E+10 | 0.418260E+09 |
November | 0.125086E+10 | 0.00 | 0.125086E+10 | 0.250657E+10 | 0.109240E+10 |
December | 0.113960E+10 | 0.00 | 0.113960E+10 | 0.160020E+10 | 0.192713E+10 |
Annual Sum or Average | 0.194037E+11 | 0.253998E+09 | 0.191497E+11 | 0.505850E+11 | 0.105144E+11 |
Minimum of Months | 0.113960E+10 | 0.00 | 0.113960E+10 | 0.146907E+10 | 25782.47 |
Maximum of Months | 0.211239E+10 | 0.117273E+09 | 0.199511E+10 | 0.751614E+10 | 0.231785E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.147244E+10 | 0.445485E+09 | 0.102695E+10 | 0.203519E+10 | 0.150012E+10 |
February | 0.144933E+10 | 0.392777E+09 | 0.105656E+10 | 0.218049E+10 | 0.117224E+10 |
March | 0.177247E+10 | 0.436849E+09 | 0.133562E+10 | 0.302641E+10 | 0.103174E+10 |
April | 0.208844E+10 | 0.608502E+09 | 0.147994E+10 | 0.414585E+10 | 0.664301E+09 |
May | 0.241168E+10 | 0.768375E+09 | 0.164331E+10 | 0.577786E+10 | 0.168677E+09 |
June | 0.228568E+10 | 0.698987E+09 | 0.158670E+10 | 0.590963E+10 | 31604973.79 |
July | 0.220444E+10 | 0.635537E+09 | 0.156891E+10 | 0.657245E+10 | 686128.43 |
August | 0.225731E+10 | 0.692800E+09 | 0.156451E+10 | 0.679221E+10 | 0.00 |
September | 0.205368E+10 | 0.634768E+09 | 0.141891E+10 | 0.535004E+10 | 51808499.21 |
October | 0.192563E+10 | 0.629103E+09 | 0.129652E+10 | 0.432934E+10 | 0.268855E+09 |
November | 0.156163E+10 | 0.494644E+09 | 0.106698E+10 | 0.293110E+10 | 0.715714E+09 |
December | 0.130612E+10 | 0.358346E+09 | 0.947773E+09 | 0.196945E+10 | 0.125111E+10 |
Annual Sum or Average | 0.227889E+11 | 0.679617E+10 | 0.159927E+11 | 0.510200E+11 | 0.685686E+10 |
Minimum of Months | 0.130612E+10 | 0.358346E+09 | 0.947773E+09 | 0.196945E+10 | 0.00 |
Maximum of Months | 0.241168E+10 | 0.768375E+09 | 0.164331E+10 | 0.679221E+10 | 0.150012E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.394598E+10 | 0.185518E+10 | 0.209079E+10 | 0.607988E+10 | 0.244938E+10 |
February | 0.334685E+10 | 0.136901E+10 | 0.197784E+10 | 0.545928E+10 | 0.191755E+10 |
March | 0.304974E+10 | 0.827989E+09 | 0.222175E+10 | 0.554107E+10 | 0.168661E+10 |
April | 0.231999E+10 | 0.245963E+09 | 0.207403E+10 | 0.498131E+10 | 0.104571E+10 |
May | 0.203074E+10 | 31098813.25 | 0.199964E+10 | 0.583915E+10 | 0.253903E+09 |
June | 0.185080E+10 | 2290434.28 | 0.184851E+10 | 0.602696E+10 | 36983244.15 |
July | 0.191244E+10 | 16249917.57 | 0.189619E+10 | 0.729835E+10 | 429631.39 |
August | 0.221828E+10 | 0.157174E+09 | 0.206111E+10 | 0.817147E+10 | 4358.51 |
September | 0.283048E+10 | 0.648687E+09 | 0.218179E+10 | 0.784142E+10 | 92631740.48 |
October | 0.382917E+10 | 0.152231E+10 | 0.230686E+10 | 0.842333E+10 | 0.474175E+09 |
November | 0.408809E+10 | 0.197076E+10 | 0.211732E+10 | 0.760122E+10 | 0.120409E+10 |
December | 0.392148E+10 | 0.193709E+10 | 0.198439E+10 | 0.641032E+10 | 0.208196E+10 |
Annual Sum or Average | 0.353440E+11 | 0.105838E+11 | 0.247602E+11 | 0.796738E+11 | 0.112434E+11 |
Minimum of Months | 0.185080E+10 | 2290434.28 | 0.184851E+10 | 0.498131E+10 | 4358.51 |
Maximum of Months | 0.408809E+10 | 0.197076E+10 | 0.230686E+10 | 0.842333E+10 | 0.244938E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.144399E+10 | 0.414727E+09 | 0.102927E+10 | 0.205206E+10 | 0.166101E+10 |
February | 0.148932E+10 | 0.424695E+09 | 0.106463E+10 | 0.229479E+10 | 0.129795E+10 |
March | 0.195316E+10 | 0.578239E+09 | 0.137493E+10 | 0.335951E+10 | 0.116605E+10 |
April | 0.206562E+10 | 0.580329E+09 | 0.148529E+10 | 0.408985E+10 | 0.770833E+09 |
May | 0.232336E+10 | 0.695476E+09 | 0.162789E+10 | 0.561464E+10 | 0.210760E+09 |
June | 0.232355E+10 | 0.732446E+09 | 0.159111E+10 | 0.596492E+10 | 43841004.03 |
July | 0.220266E+10 | 0.630138E+09 | 0.157252E+10 | 0.650746E+10 | 1123829.80 |
August | 0.225969E+10 | 0.687041E+09 | 0.157265E+10 | 0.669188E+10 | 266994.34 |
September | 0.208020E+10 | 0.653540E+09 | 0.142666E+10 | 0.535960E+10 | 72962472.88 |
October | 0.191031E+10 | 0.617084E+09 | 0.129323E+10 | 0.430201E+10 | 0.344081E+09 |
November | 0.158872E+10 | 0.519563E+09 | 0.106916E+10 | 0.302334E+10 | 0.829258E+09 |
December | 0.137434E+10 | 0.415439E+09 | 0.958902E+09 | 0.214018E+10 | 0.142036E+10 |
Annual Sum or Average | 0.230149E+11 | 0.694872E+10 | 0.160662E+11 | 0.514002E+11 | 0.781850E+10 |
Minimum of Months | 0.137434E+10 | 0.414727E+09 | 0.958902E+09 | 0.205206E+10 | 266994.34 |
Maximum of Months | 0.232355E+10 | 0.732446E+09 | 0.162789E+10 | 0.669188E+10 | 0.166101E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 480.40 | 1071.01 | 455.84 | 0.00 | 455.84 | 0.00 | 0.00 |
February | 677.41 | 892.98 | 522.52 | 0.00 | 522.52 | 0.00 | 0.00 |
March | 991.09 | 658.26 | 600.19 | 0.00 | 600.19 | 0.00 | 0.00 |
April | 1439.87 | 389.75 | 676.22 | 1.39 | 674.83 | 0.00 | 0.00 |
May | 2201.19 | 87.90 | 761.14 | 22.32 | 738.82 | 0.00 | 0.00 |
June | 2538.83 | 18.23 | 814.95 | 45.24 | 769.71 | 0.00 | 0.00 |
July | 2808.10 | 0.50 | 747.80 | 21.55 | 726.25 | 0.00 | 0.00 |
August | 2747.06 | 0.01 | 696.13 | 5.76 | 690.38 | 0.00 | 0.00 |
September | 2099.97 | 30.24 | 634.11 | 0.07 | 634.04 | 0.00 | 0.00 |
October | 1494.36 | 151.30 | 562.13 | 0.00 | 562.13 | 0.00 | 0.00 |
November | 940.62 | 462.85 | 482.57 | 0.00 | 482.57 | 0.00 | 0.00 |
December | 540.84 | 874.19 | 425.47 | 0.00 | 425.47 | 0.00 | 0.00 |
Annual Sum or Average | 1585.48 | 384.04 | 615.28 | 8.05 | 607.22 | 0.00 | 0.00 |
Minimum of Months | 480.40 | 0.01 | 425.47 | 0.00 | 425.47 | 0.00 | 0.00 |
Maximum of Months | 2808.10 | 1071.01 | 814.95 | 45.24 | 769.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 722.06 | 654.66 | 549.75 | 166.33 | 383.42 | 0.00 | 0.00 |
February | 884.09 | 544.41 | 599.10 | 162.36 | 436.74 | 0.00 | 0.00 |
March | 1135.63 | 397.41 | 661.77 | 163.10 | 498.67 | 0.00 | 0.00 |
April | 1624.96 | 229.77 | 805.73 | 234.76 | 570.97 | 0.00 | 0.00 |
May | 2192.22 | 53.37 | 900.42 | 286.88 | 613.54 | 0.00 | 0.00 |
June | 2319.65 | 8.39 | 881.83 | 269.67 | 612.15 | 0.00 | 0.00 |
July | 2494.66 | 0.17 | 823.05 | 237.28 | 585.76 | 0.00 | 0.00 |
August | 2568.22 | 0.00 | 842.79 | 258.66 | 584.12 | 0.00 | 0.00 |
September | 2094.89 | 16.82 | 792.32 | 244.90 | 547.42 | 0.00 | 0.00 |
October | 1638.83 | 84.54 | 718.95 | 234.88 | 484.07 | 0.00 | 0.00 |
November | 1139.35 | 272.66 | 602.48 | 190.84 | 411.65 | 0.00 | 0.00 |
December | 715.02 | 516.41 | 487.65 | 133.79 | 353.86 | 0.00 | 0.00 |
Annual Sum or Average | 1631.74 | 230.07 | 722.63 | 215.51 | 507.13 | 0.00 | 0.00 |
Minimum of Months | 715.02 | 0.00 | 487.65 | 133.79 | 353.86 | 0.00 | 0.00 |
Maximum of Months | 2568.22 | 654.66 | 900.42 | 286.88 | 613.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2261.30 | 1013.11 | 1473.22 | 692.62 | 780.59 | 0.00 | 0.00 |
February | 2259.61 | 871.28 | 1383.41 | 565.87 | 817.54 | 0.00 | 0.00 |
March | 2079.40 | 666.89 | 1138.61 | 309.13 | 829.49 | 0.00 | 0.00 |
April | 1930.87 | 402.08 | 895.04 | 94.89 | 800.15 | 0.00 | 0.00 |
May | 2195.14 | 89.55 | 758.18 | 11.61 | 746.57 | 0.00 | 0.00 |
June | 2328.07 | 14.01 | 714.03 | 0.88 | 713.15 | 0.00 | 0.00 |
July | 2727.27 | 0.26 | 714.01 | 6.07 | 707.94 | 0.00 | 0.00 |
August | 3040.49 | 0.01 | 828.19 | 58.68 | 769.51 | 0.00 | 0.00 |
September | 3051.27 | 32.70 | 1091.98 | 250.26 | 841.72 | 0.00 | 0.00 |
October | 3173.40 | 163.01 | 1429.61 | 568.35 | 861.26 | 0.00 | 0.00 |
November | 2956.64 | 471.01 | 1577.15 | 760.30 | 816.85 | 0.00 | 0.00 |
December | 2390.70 | 844.49 | 1464.07 | 723.20 | 740.87 | 0.00 | 0.00 |
Annual Sum or Average | 2534.72 | 378.32 | 1120.72 | 335.60 | 785.12 | 0.00 | 0.00 |
Minimum of Months | 1930.87 | 0.01 | 714.01 | 0.88 | 707.94 | 0.00 | 0.00 |
Maximum of Months | 3173.40 | 1013.11 | 1577.15 | 760.30 | 861.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 722.21 | 772.96 | 539.13 | 154.84 | 384.29 | 0.00 | 0.00 |
February | 908.42 | 678.62 | 615.63 | 175.55 | 440.08 | 0.00 | 0.00 |
March | 1225.19 | 534.93 | 729.23 | 215.89 | 513.34 | 0.00 | 0.00 |
April | 1547.46 | 358.85 | 796.92 | 223.89 | 573.03 | 0.00 | 0.00 |
May | 2093.79 | 85.08 | 867.45 | 259.66 | 607.79 | 0.00 | 0.00 |
June | 2270.75 | 25.58 | 896.44 | 282.58 | 613.86 | 0.00 | 0.00 |
July | 2366.98 | 1.88 | 822.38 | 235.27 | 587.12 | 0.00 | 0.00 |
August | 2410.48 | 1.28 | 843.67 | 256.51 | 587.16 | 0.00 | 0.00 |
September | 2053.44 | 32.70 | 802.55 | 252.14 | 550.41 | 0.00 | 0.00 |
October | 1581.24 | 150.53 | 713.23 | 230.39 | 482.84 | 0.00 | 0.00 |
November | 1131.99 | 398.86 | 612.94 | 200.45 | 412.49 | 0.00 | 0.00 |
December | 741.71 | 706.73 | 513.12 | 155.11 | 358.01 | 0.00 | 0.00 |
Annual Sum or Average | 1591.60 | 310.51 | 729.80 | 220.34 | 509.46 | 0.00 | 0.00 |
Minimum of Months | 722.21 | 1.28 | 513.12 | 154.84 | 358.01 | 0.00 | 0.00 |
Maximum of Months | 2410.48 | 772.96 | 896.44 | 282.58 | 613.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 512.55 | 965.12 | 455.85 | 0.00 | 455.85 | 0.00 | 0.00 |
February | 707.52 | 802.28 | 522.53 | 0.00 | 522.53 | 0.00 | 0.00 |
March | 1012.95 | 614.46 | 600.20 | 0.00 | 600.20 | 0.00 | 0.00 |
April | 1464.95 | 383.27 | 676.23 | 1.39 | 674.84 | 0.00 | 0.00 |
May | 2222.85 | 91.51 | 761.16 | 22.32 | 738.83 | 0.00 | 0.00 |
June | 2572.16 | 18.34 | 814.96 | 45.24 | 769.72 | 0.00 | 0.00 |
July | 2867.19 | 0.22 | 747.81 | 21.55 | 726.26 | 0.00 | 0.00 |
August | 2823.01 | 0.00 | 696.15 | 5.76 | 690.39 | 0.00 | 0.00 |
September | 2136.15 | 31.26 | 634.13 | 0.07 | 634.05 | 0.00 | 0.00 |
October | 1527.79 | 152.67 | 562.14 | 0.00 | 562.14 | 0.00 | 0.00 |
November | 970.37 | 438.84 | 482.58 | 0.00 | 482.58 | 0.00 | 0.00 |
December | 575.36 | 784.50 | 425.48 | 0.00 | 425.48 | 0.00 | 0.00 |
Annual Sum or Average | 1621.68 | 354.73 | 615.29 | 8.05 | 607.23 | 0.00 | 0.00 |
Minimum of Months | 512.55 | 0.00 | 425.48 | 0.00 | 425.48 | 0.00 | 0.00 |
Maximum of Months | 2867.19 | 965.12 | 814.96 | 45.24 | 769.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 733.88 | 610.61 | 549.75 | 166.33 | 383.42 | 0.00 | 0.00 |
February | 889.92 | 513.80 | 599.10 | 162.36 | 436.74 | 0.00 | 0.00 |
March | 1131.64 | 397.26 | 661.76 | 163.10 | 498.66 | 0.00 | 0.00 |
April | 1613.52 | 253.39 | 805.72 | 234.76 | 570.96 | 0.00 | 0.00 |
May | 2185.55 | 60.16 | 900.42 | 286.88 | 613.54 | 0.00 | 0.00 |
June | 2314.06 | 10.46 | 881.82 | 269.67 | 612.15 | 0.00 | 0.00 |
July | 2498.09 | 0.08 | 823.04 | 237.28 | 585.76 | 0.00 | 0.00 |
August | 2576.88 | 0.00 | 842.78 | 258.66 | 584.12 | 0.00 | 0.00 |
September | 2094.10 | 19.37 | 792.31 | 244.90 | 547.42 | 0.00 | 0.00 |
October | 1634.56 | 97.24 | 718.95 | 234.88 | 484.07 | 0.00 | 0.00 |
November | 1134.95 | 283.40 | 602.48 | 190.83 | 411.64 | 0.00 | 0.00 |
December | 720.27 | 499.98 | 487.65 | 133.79 | 353.86 | 0.00 | 0.00 |
Annual Sum or Average | 1631.57 | 227.43 | 722.63 | 215.51 | 507.12 | 0.00 | 0.00 |
Minimum of Months | 720.27 | 0.00 | 487.65 | 133.79 | 353.86 | 0.00 | 0.00 |
Maximum of Months | 2576.88 | 610.61 | 900.42 | 286.88 | 613.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2244.86 | 988.73 | 1473.26 | 692.65 | 780.61 | 0.00 | 0.00 |
February | 2248.28 | 838.96 | 1383.45 | 565.89 | 817.56 | 0.00 | 0.00 |
March | 2075.04 | 651.83 | 1138.64 | 309.14 | 829.51 | 0.00 | 0.00 |
April | 1940.94 | 403.18 | 895.06 | 94.89 | 800.17 | 0.00 | 0.00 |
May | 2217.22 | 92.12 | 758.19 | 11.61 | 746.58 | 0.00 | 0.00 |
June | 2369.42 | 13.11 | 714.04 | 0.88 | 713.16 | 0.00 | 0.00 |
July | 2784.64 | 0.03 | 714.02 | 6.07 | 707.96 | 0.00 | 0.00 |
August | 3105.81 | 0.00 | 828.21 | 58.68 | 769.53 | 0.00 | 0.00 |
September | 3066.29 | 34.89 | 1092.01 | 250.26 | 841.74 | 0.00 | 0.00 |
October | 3172.09 | 171.94 | 1429.65 | 568.37 | 861.28 | 0.00 | 0.00 |
November | 2944.34 | 474.52 | 1577.19 | 760.32 | 816.87 | 0.00 | 0.00 |
December | 2382.57 | 822.64 | 1464.11 | 723.23 | 740.89 | 0.00 | 0.00 |
Annual Sum or Average | 2548.03 | 372.08 | 1120.75 | 335.61 | 785.14 | 0.00 | 0.00 |
Minimum of Months | 1940.94 | 0.00 | 714.02 | 0.88 | 707.96 | 0.00 | 0.00 |
Maximum of Months | 3172.09 | 988.73 | 1577.19 | 760.32 | 861.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 749.59 | 674.65 | 539.13 | 154.84 | 384.28 | 0.00 | 0.00 |
February | 941.37 | 569.78 | 615.63 | 175.55 | 440.07 | 0.00 | 0.00 |
March | 1258.72 | 450.26 | 729.23 | 215.89 | 513.34 | 0.00 | 0.00 |
April | 1591.57 | 297.96 | 796.92 | 223.89 | 573.03 | 0.00 | 0.00 |
May | 2120.42 | 77.33 | 867.45 | 259.66 | 607.78 | 0.00 | 0.00 |
June | 2328.94 | 15.84 | 896.43 | 282.58 | 613.85 | 0.00 | 0.00 |
July | 2465.84 | 0.27 | 822.38 | 235.27 | 587.11 | 0.00 | 0.00 |
August | 2531.46 | 0.06 | 843.67 | 256.51 | 587.16 | 0.00 | 0.00 |
September | 2092.10 | 28.02 | 802.55 | 252.14 | 550.41 | 0.00 | 0.00 |
October | 1621.24 | 126.81 | 713.23 | 230.39 | 482.84 | 0.00 | 0.00 |
November | 1171.67 | 329.78 | 612.93 | 200.45 | 412.48 | 0.00 | 0.00 |
December | 790.30 | 566.27 | 513.12 | 155.11 | 358.01 | 0.00 | 0.00 |
Annual Sum or Average | 1642.61 | 259.91 | 729.80 | 220.34 | 509.46 | 0.00 | 0.00 |
Minimum of Months | 749.59 | 0.06 | 513.12 | 154.84 | 358.01 | 0.00 | 0.00 |
Maximum of Months | 2531.46 | 674.65 | 896.43 | 282.58 | 613.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 548.49 | 865.38 | 455.85 | 0.00 | 455.85 | 0.00 | 0.00 |
February | 726.58 | 742.50 | 522.53 | 0.00 | 522.53 | 0.00 | 0.00 |
March | 1012.93 | 587.29 | 600.20 | 0.00 | 600.20 | 0.00 | 0.00 |
April | 1446.27 | 383.42 | 676.23 | 1.39 | 674.84 | 0.00 | 0.00 |
May | 2184.73 | 95.61 | 761.16 | 22.32 | 738.83 | 0.00 | 0.00 |
June | 2525.95 | 20.99 | 814.96 | 45.24 | 769.72 | 0.00 | 0.00 |
July | 2806.21 | 0.53 | 747.81 | 21.55 | 726.26 | 0.00 | 0.00 |
August | 2766.90 | 0.01 | 696.15 | 5.76 | 690.39 | 0.00 | 0.00 |
September | 2096.06 | 32.30 | 634.13 | 0.07 | 634.05 | 0.00 | 0.00 |
October | 1504.94 | 156.16 | 562.14 | 0.00 | 562.14 | 0.00 | 0.00 |
November | 967.04 | 421.45 | 482.58 | 0.00 | 482.58 | 0.00 | 0.00 |
December | 597.45 | 719.51 | 425.48 | 0.00 | 425.48 | 0.00 | 0.00 |
Annual Sum or Average | 1604.04 | 333.41 | 615.29 | 8.05 | 607.23 | 0.00 | 0.00 |
Minimum of Months | 548.49 | 0.01 | 425.48 | 0.00 | 425.48 | 0.00 | 0.00 |
Maximum of Months | 2806.21 | 865.38 | 814.96 | 45.24 | 769.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 759.85 | 560.08 | 549.75 | 166.33 | 383.42 | 0.00 | 0.00 |
February | 901.33 | 484.56 | 599.10 | 162.36 | 436.74 | 0.00 | 0.00 |
March | 1129.93 | 385.21 | 661.76 | 163.10 | 498.66 | 0.00 | 0.00 |
April | 1599.48 | 256.29 | 805.72 | 234.76 | 570.96 | 0.00 | 0.00 |
May | 2157.21 | 62.98 | 900.42 | 286.88 | 613.54 | 0.00 | 0.00 |
June | 2279.95 | 12.19 | 881.82 | 269.67 | 612.15 | 0.00 | 0.00 |
July | 2453.87 | 0.26 | 823.04 | 237.28 | 585.76 | 0.00 | 0.00 |
August | 2535.92 | 0.00 | 842.78 | 258.66 | 584.12 | 0.00 | 0.00 |
September | 2064.06 | 19.99 | 792.31 | 244.90 | 547.42 | 0.00 | 0.00 |
October | 1616.39 | 100.38 | 718.95 | 234.88 | 484.07 | 0.00 | 0.00 |
November | 1130.83 | 276.12 | 602.48 | 190.83 | 411.64 | 0.00 | 0.00 |
December | 735.31 | 467.11 | 487.65 | 133.79 | 353.86 | 0.00 | 0.00 |
Annual Sum or Average | 1617.83 | 217.43 | 722.63 | 215.51 | 507.12 | 0.00 | 0.00 |
Minimum of Months | 735.31 | 0.00 | 487.65 | 133.79 | 353.86 | 0.00 | 0.00 |
Maximum of Months | 2535.92 | 560.08 | 900.42 | 286.88 | 613.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2269.97 | 914.49 | 1473.26 | 692.65 | 780.61 | 0.00 | 0.00 |
February | 2256.65 | 792.64 | 1383.45 | 565.89 | 817.56 | 0.00 | 0.00 |
March | 2068.80 | 629.71 | 1138.64 | 309.14 | 829.51 | 0.00 | 0.00 |
April | 1921.80 | 403.44 | 895.06 | 94.89 | 800.17 | 0.00 | 0.00 |
May | 2180.09 | 94.80 | 758.19 | 11.61 | 746.58 | 0.00 | 0.00 |
June | 2325.22 | 14.27 | 714.04 | 0.88 | 713.16 | 0.00 | 0.00 |
July | 2724.89 | 0.16 | 714.02 | 6.07 | 707.96 | 0.00 | 0.00 |
August | 3050.88 | 0.00 | 828.21 | 58.68 | 769.53 | 0.00 | 0.00 |
September | 3025.24 | 35.74 | 1092.01 | 250.26 | 841.74 | 0.00 | 0.00 |
October | 3144.91 | 177.04 | 1429.65 | 568.37 | 861.28 | 0.00 | 0.00 |
November | 2932.57 | 464.54 | 1577.19 | 760.32 | 816.87 | 0.00 | 0.00 |
December | 2393.34 | 777.31 | 1464.11 | 723.23 | 740.89 | 0.00 | 0.00 |
Annual Sum or Average | 2526.44 | 356.53 | 1120.75 | 335.61 | 785.14 | 0.00 | 0.00 |
Minimum of Months | 1921.80 | 0.00 | 714.02 | 0.88 | 707.96 | 0.00 | 0.00 |
Maximum of Months | 3144.91 | 914.49 | 1577.19 | 760.32 | 861.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 766.15 | 620.15 | 539.13 | 154.84 | 384.28 | 0.00 | 0.00 |
February | 948.57 | 536.52 | 615.63 | 175.55 | 440.07 | 0.00 | 0.00 |
March | 1254.30 | 435.35 | 729.23 | 215.89 | 513.34 | 0.00 | 0.00 |
April | 1577.87 | 297.39 | 796.92 | 223.89 | 573.03 | 0.00 | 0.00 |
May | 2096.26 | 78.69 | 867.45 | 259.66 | 607.78 | 0.00 | 0.00 |
June | 2301.28 | 16.91 | 896.43 | 282.58 | 613.85 | 0.00 | 0.00 |
July | 2429.61 | 0.42 | 822.38 | 235.27 | 587.11 | 0.00 | 0.00 |
August | 2498.46 | 0.10 | 843.67 | 256.51 | 587.16 | 0.00 | 0.00 |
September | 2067.75 | 28.15 | 802.55 | 252.14 | 550.41 | 0.00 | 0.00 |
October | 1606.19 | 128.46 | 713.23 | 230.39 | 482.84 | 0.00 | 0.00 |
November | 1166.41 | 319.93 | 612.93 | 200.45 | 412.48 | 0.00 | 0.00 |
December | 799.05 | 530.30 | 513.12 | 155.11 | 358.01 | 0.00 | 0.00 |
Annual Sum or Average | 1629.89 | 247.92 | 729.80 | 220.34 | 509.46 | 0.00 | 0.00 |
Minimum of Months | 766.15 | 0.10 | 513.12 | 154.84 | 358.01 | 0.00 | 0.00 |
Maximum of Months | 2498.46 | 620.15 | 896.43 | 282.58 | 613.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.128671E+10 | 0.286861E+10 | 0.122092E+10 | 0.00 | 0.122092E+10 | 0.00 | 0.00 |
February | 0.163879E+10 | 0.216031E+10 | 0.126409E+10 | 0.00 | 0.126409E+10 | 0.00 | 0.00 |
March | 0.265452E+10 | 0.176309E+10 | 0.160755E+10 | 0.00 | 0.160755E+10 | 0.00 | 0.00 |
April | 0.373214E+10 | 0.101022E+10 | 0.175276E+10 | 3611426.82 | 0.174915E+10 | 0.00 | 0.00 |
May | 0.589567E+10 | 0.235431E+09 | 0.203865E+10 | 59791613.42 | 0.197886E+10 | 0.00 | 0.00 |
June | 0.658064E+10 | 47264309.11 | 0.211235E+10 | 0.117270E+09 | 0.199508E+10 | 0.00 | 0.00 |
July | 0.752122E+10 | 1350257.94 | 0.200289E+10 | 57707563.98 | 0.194519E+10 | 0.00 | 0.00 |
August | 0.735772E+10 | 13803.70 | 0.186452E+10 | 15421278.67 | 0.184910E+10 | 0.00 | 0.00 |
September | 0.544312E+10 | 78391145.79 | 0.164362E+10 | 188341.88 | 0.164343E+10 | 0.00 | 0.00 |
October | 0.400250E+10 | 0.405248E+09 | 0.150560E+10 | 0.00 | 0.150560E+10 | 0.00 | 0.00 |
November | 0.243809E+10 | 0.119971E+10 | 0.125083E+10 | 0.00 | 0.125083E+10 | 0.00 | 0.00 |
December | 0.144860E+10 | 0.234143E+10 | 0.113957E+10 | 0.00 | 0.113957E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.499997E+11 | 0.121111E+11 | 0.194034E+11 | 0.253990E+09 | 0.191494E+11 | 0.00 | 0.00 |
Minimum of Months | 0.128671E+10 | 13803.70 | 0.113957E+10 | 0.00 | 0.113957E+10 | 0.00 | 0.00 |
Maximum of Months | 0.752122E+10 | 0.286861E+10 | 0.211235E+10 | 0.117270E+09 | 0.199508E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.193397E+10 | 0.175345E+10 | 0.147245E+10 | 0.445487E+09 | 0.102696E+10 | 0.00 | 0.00 |
February | 0.213878E+10 | 0.131703E+10 | 0.144934E+10 | 0.392779E+09 | 0.105656E+10 | 0.00 | 0.00 |
March | 0.304167E+10 | 0.106442E+10 | 0.177248E+10 | 0.436850E+09 | 0.133563E+10 | 0.00 | 0.00 |
April | 0.421190E+10 | 0.595575E+09 | 0.208845E+10 | 0.608505E+09 | 0.147994E+10 | 0.00 | 0.00 |
May | 0.587165E+10 | 0.142941E+09 | 0.241169E+10 | 0.768378E+09 | 0.164331E+10 | 0.00 | 0.00 |
June | 0.601252E+10 | 21759683.89 | 0.228569E+10 | 0.698990E+09 | 0.158670E+10 | 0.00 | 0.00 |
July | 0.668170E+10 | 457815.41 | 0.220445E+10 | 0.635539E+09 | 0.156891E+10 | 0.00 | 0.00 |
August | 0.687873E+10 | 0.00 | 0.225732E+10 | 0.692802E+09 | 0.156452E+10 | 0.00 | 0.00 |
September | 0.542995E+10 | 43601938.06 | 0.205369E+10 | 0.634771E+09 | 0.141892E+10 | 0.00 | 0.00 |
October | 0.438943E+10 | 0.226436E+09 | 0.192563E+10 | 0.629106E+09 | 0.129653E+10 | 0.00 | 0.00 |
November | 0.295319E+10 | 0.706730E+09 | 0.156163E+10 | 0.494646E+09 | 0.106699E+10 | 0.00 | 0.00 |
December | 0.191512E+10 | 0.138315E+10 | 0.130612E+10 | 0.358348E+09 | 0.947777E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.514586E+11 | 0.725556E+10 | 0.227889E+11 | 0.679620E+10 | 0.159927E+11 | 0.00 | 0.00 |
Minimum of Months | 0.191512E+10 | 0.00 | 0.130612E+10 | 0.358348E+09 | 0.947777E+09 | 0.00 | 0.00 |
Maximum of Months | 0.687873E+10 | 0.175345E+10 | 0.241169E+10 | 0.768378E+09 | 0.164331E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.605666E+10 | 0.271350E+10 | 0.394586E+10 | 0.185512E+10 | 0.209074E+10 | 0.00 | 0.00 |
February | 0.546645E+10 | 0.210780E+10 | 0.334675E+10 | 0.136896E+10 | 0.197779E+10 | 0.00 | 0.00 |
March | 0.556947E+10 | 0.178621E+10 | 0.304966E+10 | 0.827962E+09 | 0.222170E+10 | 0.00 | 0.00 |
April | 0.500480E+10 | 0.104219E+10 | 0.231994E+10 | 0.245955E+09 | 0.207398E+10 | 0.00 | 0.00 |
May | 0.587946E+10 | 0.239851E+09 | 0.203070E+10 | 31097794.67 | 0.199960E+10 | 0.00 | 0.00 |
June | 0.603437E+10 | 36316692.50 | 0.185076E+10 | 2290359.26 | 0.184847E+10 | 0.00 | 0.00 |
July | 0.730471E+10 | 688116.42 | 0.191240E+10 | 16249385.34 | 0.189615E+10 | 0.00 | 0.00 |
August | 0.814364E+10 | 13505.37 | 0.221823E+10 | 0.157169E+09 | 0.206106E+10 | 0.00 | 0.00 |
September | 0.790888E+10 | 84758646.44 | 0.283041E+10 | 0.648666E+09 | 0.218174E+10 | 0.00 | 0.00 |
October | 0.849963E+10 | 0.436594E+09 | 0.382907E+10 | 0.152226E+10 | 0.230680E+10 | 0.00 | 0.00 |
November | 0.766362E+10 | 0.122085E+10 | 0.408797E+10 | 0.197070E+10 | 0.211727E+10 | 0.00 | 0.00 |
December | 0.640325E+10 | 0.226189E+10 | 0.392137E+10 | 0.193703E+10 | 0.198434E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.799349E+11 | 0.119307E+11 | 0.353431E+11 | 0.105835E+11 | 0.247597E+11 | 0.00 | 0.00 |
Minimum of Months | 0.500480E+10 | 13505.37 | 0.185076E+10 | 2290359.26 | 0.184847E+10 | 0.00 | 0.00 |
Maximum of Months | 0.849963E+10 | 0.271350E+10 | 0.408797E+10 | 0.197070E+10 | 0.230680E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.193436E+10 | 0.207030E+10 | 0.144400E+10 | 0.414729E+09 | 0.102927E+10 | 0.00 | 0.00 |
February | 0.219764E+10 | 0.164171E+10 | 0.148933E+10 | 0.424697E+09 | 0.106463E+10 | 0.00 | 0.00 |
March | 0.328156E+10 | 0.143275E+10 | 0.195317E+10 | 0.578242E+09 | 0.137493E+10 | 0.00 | 0.00 |
April | 0.401101E+10 | 0.930145E+09 | 0.206563E+10 | 0.580331E+09 | 0.148530E+10 | 0.00 | 0.00 |
May | 0.560800E+10 | 0.227871E+09 | 0.232337E+10 | 0.695479E+09 | 0.162789E+10 | 0.00 | 0.00 |
June | 0.588578E+10 | 66309037.48 | 0.232356E+10 | 0.732449E+09 | 0.159111E+10 | 0.00 | 0.00 |
July | 0.633973E+10 | 5038010.16 | 0.220267E+10 | 0.630141E+09 | 0.157253E+10 | 0.00 | 0.00 |
August | 0.645623E+10 | 3420359.55 | 0.225970E+10 | 0.687044E+09 | 0.157265E+10 | 0.00 | 0.00 |
September | 0.532251E+10 | 84757311.04 | 0.208021E+10 | 0.653543E+09 | 0.142667E+10 | 0.00 | 0.00 |
October | 0.423518E+10 | 0.403184E+09 | 0.191032E+10 | 0.617087E+09 | 0.129323E+10 | 0.00 | 0.00 |
November | 0.293412E+10 | 0.103383E+10 | 0.158873E+10 | 0.519565E+09 | 0.106916E+10 | 0.00 | 0.00 |
December | 0.198660E+10 | 0.189290E+10 | 0.137435E+10 | 0.415441E+09 | 0.958906E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.501927E+11 | 0.979222E+10 | 0.230150E+11 | 0.694875E+10 | 0.160663E+11 | 0.00 | 0.00 |
Minimum of Months | 0.193436E+10 | 3420359.55 | 0.137435E+10 | 0.414729E+09 | 0.958906E+09 | 0.00 | 0.00 |
Maximum of Months | 0.645623E+10 | 0.207030E+10 | 0.232356E+10 | 0.732449E+09 | 0.162789E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.137282E+10 | 0.258498E+10 | 0.122095E+10 | 0.00 | 0.122095E+10 | 0.00 | 0.00 |
February | 0.171163E+10 | 0.194087E+10 | 0.126412E+10 | 0.00 | 0.126412E+10 | 0.00 | 0.00 |
March | 0.271309E+10 | 0.164577E+10 | 0.160758E+10 | 0.00 | 0.160758E+10 | 0.00 | 0.00 |
April | 0.379715E+10 | 0.993425E+09 | 0.175279E+10 | 3611534.52 | 0.174918E+10 | 0.00 | 0.00 |
May | 0.595367E+10 | 0.245094E+09 | 0.203868E+10 | 59793396.57 | 0.197889E+10 | 0.00 | 0.00 |
June | 0.666703E+10 | 47538364.97 | 0.211239E+10 | 0.117273E+09 | 0.199511E+10 | 0.00 | 0.00 |
July | 0.767949E+10 | 588768.74 | 0.200293E+10 | 57709284.98 | 0.194522E+10 | 0.00 | 0.00 |
August | 0.756115E+10 | 986.26 | 0.186456E+10 | 15421738.58 | 0.184914E+10 | 0.00 | 0.00 |
September | 0.553691E+10 | 81025960.95 | 0.164365E+10 | 188347.50 | 0.164346E+10 | 0.00 | 0.00 |
October | 0.409203E+10 | 0.408919E+09 | 0.150563E+10 | 0.00 | 0.150563E+10 | 0.00 | 0.00 |
November | 0.251519E+10 | 0.113749E+10 | 0.125086E+10 | 0.00 | 0.125086E+10 | 0.00 | 0.00 |
December | 0.154105E+10 | 0.210121E+10 | 0.113960E+10 | 0.00 | 0.113960E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.511412E+11 | 0.111869E+11 | 0.194037E+11 | 0.253998E+09 | 0.191497E+11 | 0.00 | 0.00 |
Minimum of Months | 0.137282E+10 | 986.26 | 0.113960E+10 | 0.00 | 0.113960E+10 | 0.00 | 0.00 |
Maximum of Months | 0.767949E+10 | 0.258498E+10 | 0.211239E+10 | 0.117273E+09 | 0.199511E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.196564E+10 | 0.163546E+10 | 0.147244E+10 | 0.445485E+09 | 0.102695E+10 | 0.00 | 0.00 |
February | 0.215289E+10 | 0.124298E+10 | 0.144933E+10 | 0.392777E+09 | 0.105656E+10 | 0.00 | 0.00 |
March | 0.303097E+10 | 0.106402E+10 | 0.177247E+10 | 0.436849E+09 | 0.133562E+10 | 0.00 | 0.00 |
April | 0.418223E+10 | 0.656788E+09 | 0.208844E+10 | 0.608502E+09 | 0.147994E+10 | 0.00 | 0.00 |
May | 0.585378E+10 | 0.161142E+09 | 0.241168E+10 | 0.768375E+09 | 0.164331E+10 | 0.00 | 0.00 |
June | 0.599805E+10 | 27113040.85 | 0.228568E+10 | 0.698987E+09 | 0.158670E+10 | 0.00 | 0.00 |
July | 0.669090E+10 | 205550.33 | 0.220444E+10 | 0.635537E+09 | 0.156891E+10 | 0.00 | 0.00 |
August | 0.690191E+10 | 0.00 | 0.225731E+10 | 0.692800E+09 | 0.156451E+10 | 0.00 | 0.00 |
September | 0.542790E+10 | 50196809.51 | 0.205368E+10 | 0.634768E+09 | 0.141891E+10 | 0.00 | 0.00 |
October | 0.437800E+10 | 0.260458E+09 | 0.192563E+10 | 0.629103E+09 | 0.129652E+10 | 0.00 | 0.00 |
November | 0.294179E+10 | 0.734564E+09 | 0.156163E+10 | 0.494644E+09 | 0.106698E+10 | 0.00 | 0.00 |
December | 0.192918E+10 | 0.133915E+10 | 0.130612E+10 | 0.358346E+09 | 0.947773E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.514532E+11 | 0.717208E+10 | 0.227889E+11 | 0.679617E+10 | 0.159927E+11 | 0.00 | 0.00 |
Minimum of Months | 0.192918E+10 | 0.00 | 0.130612E+10 | 0.358346E+09 | 0.947773E+09 | 0.00 | 0.00 |
Maximum of Months | 0.690191E+10 | 0.163546E+10 | 0.241168E+10 | 0.768375E+09 | 0.164331E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.601263E+10 | 0.264822E+10 | 0.394598E+10 | 0.185518E+10 | 0.209079E+10 | 0.00 | 0.00 |
February | 0.543904E+10 | 0.202961E+10 | 0.334685E+10 | 0.136901E+10 | 0.197784E+10 | 0.00 | 0.00 |
March | 0.555780E+10 | 0.174586E+10 | 0.304974E+10 | 0.827989E+09 | 0.222175E+10 | 0.00 | 0.00 |
April | 0.503092E+10 | 0.104504E+10 | 0.231999E+10 | 0.245963E+09 | 0.207403E+10 | 0.00 | 0.00 |
May | 0.593861E+10 | 0.246731E+09 | 0.203074E+10 | 31098813.25 | 0.199964E+10 | 0.00 | 0.00 |
June | 0.614154E+10 | 33993886.80 | 0.185080E+10 | 2290434.28 | 0.184851E+10 | 0.00 | 0.00 |
July | 0.745837E+10 | 81996.39 | 0.191244E+10 | 16249917.57 | 0.189619E+10 | 0.00 | 0.00 |
August | 0.831861E+10 | 0.00 | 0.221828E+10 | 0.157174E+09 | 0.206111E+10 | 0.00 | 0.00 |
September | 0.794781E+10 | 90425107.28 | 0.283048E+10 | 0.648687E+09 | 0.218179E+10 | 0.00 | 0.00 |
October | 0.849614E+10 | 0.460518E+09 | 0.382917E+10 | 0.152231E+10 | 0.230686E+10 | 0.00 | 0.00 |
November | 0.763173E+10 | 0.122996E+10 | 0.408809E+10 | 0.197076E+10 | 0.211732E+10 | 0.00 | 0.00 |
December | 0.638149E+10 | 0.220335E+10 | 0.392148E+10 | 0.193709E+10 | 0.198439E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.803547E+11 | 0.117338E+11 | 0.353440E+11 | 0.105838E+11 | 0.247602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.503092E+10 | 0.00 | 0.185080E+10 | 2290434.28 | 0.184851E+10 | 0.00 | 0.00 |
Maximum of Months | 0.849614E+10 | 0.264822E+10 | 0.408809E+10 | 0.197076E+10 | 0.230686E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.200770E+10 | 0.180698E+10 | 0.144399E+10 | 0.414727E+09 | 0.102927E+10 | 0.00 | 0.00 |
February | 0.227736E+10 | 0.137840E+10 | 0.148932E+10 | 0.424695E+09 | 0.106463E+10 | 0.00 | 0.00 |
March | 0.337136E+10 | 0.120599E+10 | 0.195316E+10 | 0.578239E+09 | 0.137493E+10 | 0.00 | 0.00 |
April | 0.412534E+10 | 0.772315E+09 | 0.206562E+10 | 0.580329E+09 | 0.148529E+10 | 0.00 | 0.00 |
May | 0.567934E+10 | 0.207122E+09 | 0.232336E+10 | 0.695476E+09 | 0.162789E+10 | 0.00 | 0.00 |
June | 0.603660E+10 | 41059092.66 | 0.232355E+10 | 0.732446E+09 | 0.159111E+10 | 0.00 | 0.00 |
July | 0.660451E+10 | 728041.49 | 0.220266E+10 | 0.630138E+09 | 0.157252E+10 | 0.00 | 0.00 |
August | 0.678026E+10 | 151506.20 | 0.225969E+10 | 0.687041E+09 | 0.157265E+10 | 0.00 | 0.00 |
September | 0.542272E+10 | 72637690.68 | 0.208020E+10 | 0.653540E+09 | 0.142666E+10 | 0.00 | 0.00 |
October | 0.434232E+10 | 0.339645E+09 | 0.191031E+10 | 0.617084E+09 | 0.129323E+10 | 0.00 | 0.00 |
November | 0.303696E+10 | 0.854790E+09 | 0.158872E+10 | 0.519563E+09 | 0.106916E+10 | 0.00 | 0.00 |
December | 0.211675E+10 | 0.151669E+10 | 0.137434E+10 | 0.415439E+09 | 0.958902E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.518012E+11 | 0.819651E+10 | 0.230149E+11 | 0.694872E+10 | 0.160662E+11 | 0.00 | 0.00 |
Minimum of Months | 0.200770E+10 | 151506.20 | 0.137434E+10 | 0.414727E+09 | 0.958902E+09 | 0.00 | 0.00 |
Maximum of Months | 0.678026E+10 | 0.180698E+10 | 0.232355E+10 | 0.732446E+09 | 0.162789E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.146907E+10 | 0.231785E+10 | 0.122095E+10 | 0.00 | 0.122095E+10 | 0.00 | 0.00 |
February | 0.175773E+10 | 0.179625E+10 | 0.126412E+10 | 0.00 | 0.126412E+10 | 0.00 | 0.00 |
March | 0.271304E+10 | 0.157301E+10 | 0.160758E+10 | 0.00 | 0.160758E+10 | 0.00 | 0.00 |
April | 0.374874E+10 | 0.993815E+09 | 0.175279E+10 | 3611534.52 | 0.174918E+10 | 0.00 | 0.00 |
May | 0.585158E+10 | 0.256087E+09 | 0.203868E+10 | 59793396.57 | 0.197889E+10 | 0.00 | 0.00 |
June | 0.654727E+10 | 54394939.39 | 0.211239E+10 | 0.117273E+09 | 0.199511E+10 | 0.00 | 0.00 |
July | 0.751614E+10 | 1419422.84 | 0.200293E+10 | 57709284.98 | 0.194522E+10 | 0.00 | 0.00 |
August | 0.741088E+10 | 25782.47 | 0.186456E+10 | 15421738.58 | 0.184914E+10 | 0.00 | 0.00 |
September | 0.543298E+10 | 83716491.11 | 0.164365E+10 | 188347.50 | 0.164346E+10 | 0.00 | 0.00 |
October | 0.403082E+10 | 0.418260E+09 | 0.150563E+10 | 0.00 | 0.150563E+10 | 0.00 | 0.00 |
November | 0.250657E+10 | 0.109240E+10 | 0.125086E+10 | 0.00 | 0.125086E+10 | 0.00 | 0.00 |
December | 0.160020E+10 | 0.192713E+10 | 0.113960E+10 | 0.00 | 0.113960E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.505850E+11 | 0.105144E+11 | 0.194037E+11 | 0.253998E+09 | 0.191497E+11 | 0.00 | 0.00 |
Minimum of Months | 0.146907E+10 | 25782.47 | 0.113960E+10 | 0.00 | 0.113960E+10 | 0.00 | 0.00 |
Maximum of Months | 0.751614E+10 | 0.231785E+10 | 0.211239E+10 | 0.117273E+09 | 0.199511E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.203519E+10 | 0.150012E+10 | 0.147244E+10 | 0.445485E+09 | 0.102695E+10 | 0.00 | 0.00 |
February | 0.218049E+10 | 0.117224E+10 | 0.144933E+10 | 0.392777E+09 | 0.105656E+10 | 0.00 | 0.00 |
March | 0.302641E+10 | 0.103174E+10 | 0.177247E+10 | 0.436849E+09 | 0.133562E+10 | 0.00 | 0.00 |
April | 0.414585E+10 | 0.664301E+09 | 0.208844E+10 | 0.608502E+09 | 0.147994E+10 | 0.00 | 0.00 |
May | 0.577786E+10 | 0.168677E+09 | 0.241168E+10 | 0.768375E+09 | 0.164331E+10 | 0.00 | 0.00 |
June | 0.590963E+10 | 31604973.79 | 0.228568E+10 | 0.698987E+09 | 0.158670E+10 | 0.00 | 0.00 |
July | 0.657245E+10 | 686128.43 | 0.220444E+10 | 0.635537E+09 | 0.156891E+10 | 0.00 | 0.00 |
August | 0.679221E+10 | 0.00 | 0.225731E+10 | 0.692800E+09 | 0.156451E+10 | 0.00 | 0.00 |
September | 0.535004E+10 | 51808499.21 | 0.205368E+10 | 0.634768E+09 | 0.141891E+10 | 0.00 | 0.00 |
October | 0.432934E+10 | 0.268855E+09 | 0.192563E+10 | 0.629103E+09 | 0.129652E+10 | 0.00 | 0.00 |
November | 0.293110E+10 | 0.715714E+09 | 0.156163E+10 | 0.494644E+09 | 0.106698E+10 | 0.00 | 0.00 |
December | 0.196945E+10 | 0.125111E+10 | 0.130612E+10 | 0.358346E+09 | 0.947773E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.510200E+11 | 0.685686E+10 | 0.227889E+11 | 0.679617E+10 | 0.159927E+11 | 0.00 | 0.00 |
Minimum of Months | 0.196945E+10 | 0.00 | 0.130612E+10 | 0.358346E+09 | 0.947773E+09 | 0.00 | 0.00 |
Maximum of Months | 0.679221E+10 | 0.150012E+10 | 0.241168E+10 | 0.768375E+09 | 0.164331E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.607988E+10 | 0.244938E+10 | 0.394598E+10 | 0.185518E+10 | 0.209079E+10 | 0.00 | 0.00 |
February | 0.545928E+10 | 0.191755E+10 | 0.334685E+10 | 0.136901E+10 | 0.197784E+10 | 0.00 | 0.00 |
March | 0.554107E+10 | 0.168661E+10 | 0.304974E+10 | 0.827989E+09 | 0.222175E+10 | 0.00 | 0.00 |
April | 0.498131E+10 | 0.104571E+10 | 0.231999E+10 | 0.245963E+09 | 0.207403E+10 | 0.00 | 0.00 |
May | 0.583915E+10 | 0.253903E+09 | 0.203074E+10 | 31098813.25 | 0.199964E+10 | 0.00 | 0.00 |
June | 0.602696E+10 | 36983244.15 | 0.185080E+10 | 2290434.28 | 0.184851E+10 | 0.00 | 0.00 |
July | 0.729835E+10 | 429631.39 | 0.191244E+10 | 16249917.57 | 0.189619E+10 | 0.00 | 0.00 |
August | 0.817147E+10 | 4358.51 | 0.221828E+10 | 0.157174E+09 | 0.206111E+10 | 0.00 | 0.00 |
September | 0.784142E+10 | 92631740.48 | 0.283048E+10 | 0.648687E+09 | 0.218179E+10 | 0.00 | 0.00 |
October | 0.842333E+10 | 0.474175E+09 | 0.382917E+10 | 0.152231E+10 | 0.230686E+10 | 0.00 | 0.00 |
November | 0.760122E+10 | 0.120409E+10 | 0.408809E+10 | 0.197076E+10 | 0.211732E+10 | 0.00 | 0.00 |
December | 0.641032E+10 | 0.208196E+10 | 0.392148E+10 | 0.193709E+10 | 0.198439E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.796738E+11 | 0.112434E+11 | 0.353440E+11 | 0.105838E+11 | 0.247602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.498131E+10 | 4358.51 | 0.185080E+10 | 2290434.28 | 0.184851E+10 | 0.00 | 0.00 |
Maximum of Months | 0.842333E+10 | 0.244938E+10 | 0.408809E+10 | 0.197076E+10 | 0.230686E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.205206E+10 | 0.166101E+10 | 0.144399E+10 | 0.414727E+09 | 0.102927E+10 | 0.00 | 0.00 |
February | 0.229479E+10 | 0.129795E+10 | 0.148932E+10 | 0.424695E+09 | 0.106463E+10 | 0.00 | 0.00 |
March | 0.335951E+10 | 0.116605E+10 | 0.195316E+10 | 0.578239E+09 | 0.137493E+10 | 0.00 | 0.00 |
April | 0.408985E+10 | 0.770833E+09 | 0.206562E+10 | 0.580329E+09 | 0.148529E+10 | 0.00 | 0.00 |
May | 0.561464E+10 | 0.210760E+09 | 0.232336E+10 | 0.695476E+09 | 0.162789E+10 | 0.00 | 0.00 |
June | 0.596492E+10 | 43841004.03 | 0.232355E+10 | 0.732446E+09 | 0.159111E+10 | 0.00 | 0.00 |
July | 0.650746E+10 | 1123829.80 | 0.220266E+10 | 0.630138E+09 | 0.157252E+10 | 0.00 | 0.00 |
August | 0.669188E+10 | 266994.34 | 0.225969E+10 | 0.687041E+09 | 0.157265E+10 | 0.00 | 0.00 |
September | 0.535960E+10 | 72962472.88 | 0.208020E+10 | 0.653540E+09 | 0.142666E+10 | 0.00 | 0.00 |
October | 0.430201E+10 | 0.344081E+09 | 0.191031E+10 | 0.617084E+09 | 0.129323E+10 | 0.00 | 0.00 |
November | 0.302334E+10 | 0.829258E+09 | 0.158872E+10 | 0.519563E+09 | 0.106916E+10 | 0.00 | 0.00 |
December | 0.214018E+10 | 0.142036E+10 | 0.137434E+10 | 0.415439E+09 | 0.958902E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.514002E+11 | 0.781850E+10 | 0.230149E+11 | 0.694872E+10 | 0.160662E+11 | 0.00 | 0.00 |
Minimum of Months | 0.205206E+10 | 266994.34 | 0.137434E+10 | 0.414727E+09 | 0.958902E+09 | 0.00 | 0.00 |
Maximum of Months | 0.669188E+10 | 0.166101E+10 | 0.232355E+10 | 0.732446E+09 | 0.162789E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.281503E+11 | -0.271327E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101761E+10 | 58.96 | 0.00 | 0.00 |
February | 0.248855E+11 | -0.239653E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -920190770.9 | 58.97 | 0.00 | 0.00 |
March | 0.272188E+11 | -0.261960E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102276E+10 | 58.97 | 0.00 | 0.00 |
April | 0.223269E+11 | -0.213402E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986690083.2 | 58.97 | 0.00 | 0.00 |
May | 0.213160E+11 | -0.202958E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102023E+10 | 58.96 | 0.00 | 0.00 |
June | 0.192838E+11 | -0.182953E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988534052.4 | 58.96 | 0.00 | 0.00 |
July | 0.178674E+11 | -0.168513E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101609E+10 | 58.96 | 0.00 | 0.00 |
August | 0.203223E+11 | -0.193023E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101996E+10 | 58.96 | 0.00 | 0.00 |
September | 0.203730E+11 | -0.193883E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -984763902.6 | 58.96 | 0.00 | 0.00 |
October | 0.235083E+11 | -0.224921E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101613E+10 | 58.97 | 0.00 | 0.00 |
November | 0.254186E+11 | -0.244352E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -983451448.6 | 58.97 | 0.00 | 0.00 |
December | 0.269968E+11 | -0.259805E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101628E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.277668E+12 | -0.265675E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.119927E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.178674E+11 | -0.271327E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102276E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.281503E+11 | -0.168513E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -920190770.9 | 58.97 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-08:09 | 3735.09 | 33.67 | 309.67 | 288.50 | 888.10 | 24.90 | 281.00 | 274.83 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:20 | 1823.83 | 24.33 | 140.67 | 269.33 | 785.35 | 20.34 | 160.00 | 232.33 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:39 | 1318.90 | 17.15 | 5.00 | 304.83 | 671.24 | 19.84 | 97.17 | 263.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:49 | 1027.46 | 16.05 | 0.00 | 314.50 | 536.14 | 18.83 | 1.00 | 266.33 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-07:30 | 868.20 | 15.82 | 0.00 | 337.50 | 471.38 | 18.67 | 0.00 | 283.50 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-07:30 | 828.25 | 15.66 | 0.00 | 333.50 | 458.32 | 18.58 | 0.00 | 276.83 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-07:30 | 872.64 | 15.68 | 0.00 | 335.83 | 476.28 | 18.57 | 0.00 | 282.00 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-07:30 | 1028.11 | 16.26 | 0.00 | 333.50 | 545.14 | 19.12 | 18.17 | 285.83 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:30 | 1289.31 | 17.08 | 0.00 | 310.00 | 669.36 | 19.95 | 115.17 | 271.00 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:30 | 1744.09 | 19.08 | 32.83 | 310.50 | 805.46 | 20.92 | 203.67 | 275.33 |
November | 318.83 | 0.50 | 0.48 | 01-NOV-07:19 | 3082.53 | 30.51 | 246.83 | 290.00 | 915.43 | 24.48 | 284.50 | 273.50 |
December | 319.00 | 0.51 | 0.48 | 01-DEC-07:30 | 3708.92 | 32.96 | 293.50 | 281.83 | 956.78 | 26.11 | 280.50 | 269.50 |
Annual Sum or Average | 4323.33 | 0.52 | 1693.28 | 20.63 | 1028.50 | 3709.83 | 665.36 | 20.66 | 1441.17 | 3254.00 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 828.25 | 15.66 | 0.00 | 269.33 | 458.32 | 18.57 | 0.00 | 232.33 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 3735.09 | 33.67 | 309.67 | 337.50 | 956.78 | 26.11 | 284.50 | 285.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-07:00 | 1260.18 | 19.32 | 87.50 | 257.67 | 673.30 | 22.60 | 113.83 | 211.83 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-07:49 | 1364.50 | 19.14 | 77.67 | 248.83 | 580.65 | 21.08 | 89.50 | 204.50 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-07:00 | 1295.90 | 19.01 | 83.00 | 294.83 | 640.04 | 20.67 | 77.33 | 241.33 |
April | 375.00 | 0.54 | 0.48 | 01-APR-06:00 | 1505.90 | 18.25 | 84.33 | 306.17 | 769.86 | 21.74 | 89.00 | 257.17 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-06:30 | 1753.54 | 20.08 | 118.83 | 343.00 | 703.53 | 20.58 | 76.50 | 288.33 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-06:19 | 1681.34 | 19.82 | 114.33 | 339.17 | 694.43 | 20.56 | 92.67 | 287.00 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-06:40 | 1576.33 | 19.66 | 112.00 | 335.67 | 664.27 | 20.38 | 95.00 | 290.17 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-06:40 | 1587.42 | 18.58 | 87.83 | 327.67 | 694.00 | 20.87 | 104.83 | 287.00 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-06:49 | 1585.57 | 19.24 | 85.00 | 301.17 | 814.69 | 22.66 | 111.67 | 262.83 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-06:00 | 1475.23 | 19.53 | 87.83 | 290.33 | 757.28 | 22.38 | 124.17 | 248.00 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-06:00 | 1269.48 | 19.90 | 80.83 | 263.50 | 640.00 | 21.63 | 106.50 | 216.17 |
December | 319.00 | 0.53 | 0.48 | 01-DEC-07:19 | 1009.38 | 18.01 | 59.67 | 251.83 | 540.17 | 21.31 | 90.67 | 198.50 |
Annual Sum or Average | 4323.33 | 0.53 | 1463.68 | 19.23 | 1078.83 | 3559.83 | 684.45 | 21.33 | 1171.67 | 2992.83 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 1009.38 | 18.01 | 59.67 | 248.83 | 540.17 | 20.38 | 76.50 | 198.50 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1753.54 | 20.08 | 118.83 | 343.00 | 814.69 | 22.66 | 124.17 | 290.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.56 | 0.48 | 01-JAN-10:00 | 483.28 | 13.46 | 0.00 | 239.50 | 278.02 | 16.34 | 0.00 | 77.67 |
February | 308.33 | 0.54 | 0.48 | 01-FEB-09:20 | 550.30 | 14.31 | 0.00 | 240.50 | 315.34 | 17.21 | 0.00 | 143.50 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-09:09 | 643.90 | 15.02 | 0.00 | 294.67 | 362.79 | 17.85 | 0.00 | 217.83 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:00 | 739.12 | 15.39 | 0.00 | 318.33 | 410.09 | 18.14 | 0.00 | 263.67 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-07:10 | 869.30 | 16.40 | 1.67 | 357.83 | 476.51 | 19.18 | 0.00 | 310.50 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:49 | 963.00 | 18.42 | 43.50 | 353.83 | 516.45 | 19.68 | 1.83 | 315.50 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:10 | 933.32 | 16.24 | 0.00 | 352.00 | 504.16 | 20.40 | 28.33 | 312.33 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:19 | 842.50 | 16.09 | 0.00 | 342.67 | 467.10 | 18.94 | 0.00 | 296.67 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:40 | 732.03 | 15.67 | 0.00 | 307.67 | 417.09 | 18.54 | 0.00 | 253.83 |
October | 351.17 | 0.54 | 0.48 | 01-OCT-07:00 | 602.95 | 14.70 | 0.00 | 286.17 | 352.82 | 17.61 | 0.00 | 211.83 |
November | 318.83 | 0.54 | 0.48 | 01-NOV-08:30 | 521.42 | 14.29 | 0.00 | 244.50 | 306.68 | 17.29 | 0.00 | 129.33 |
December | 319.00 | 0.56 | 0.48 | 01-DEC-09:30 | 468.04 | 13.52 | 0.00 | 229.67 | 270.00 | 16.46 | 0.00 | 60.33 |
Annual Sum or Average | 4323.33 | 0.53 | 711.60 | 15.41 | 45.17 | 3567.33 | 397.65 | 18.25 | 30.17 | 2593.00 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 468.04 | 13.46 | 0.00 | 229.67 | 270.00 | 16.34 | 0.00 | 60.33 | |
Maximum of Months | 405.33 | 0.56 | 0.48 | 963.00 | 18.42 | 43.50 | 357.83 | 516.45 | 20.40 | 28.33 | 315.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-10:20 | 1226.35 | 19.25 | 86.50 | 258.67 | 644.17 | 22.33 | 110.17 | 208.83 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-09:39 | 1162.79 | 17.74 | 50.67 | 247.33 | 598.47 | 21.10 | 90.50 | 201.00 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-09:30 | 1391.33 | 19.34 | 84.67 | 296.17 | 684.46 | 20.93 | 81.50 | 244.67 |
April | 375.00 | 0.53 | 0.48 | 01-APR-08:50 | 1401.49 | 16.82 | 55.00 | 310.83 | 720.14 | 17.99 | 29.50 | 262.50 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-08:09 | 1467.59 | 14.65 | 0.00 | 336.00 | 756.20 | 18.26 | 32.67 | 289.00 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-08:09 | 1561.05 | 14.84 | 0.00 | 334.33 | 802.60 | 18.46 | 41.50 | 288.67 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-08:20 | 1498.06 | 14.88 | 3.67 | 335.67 | 661.46 | 18.25 | 51.67 | 286.67 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-08:20 | 1525.88 | 17.26 | 59.83 | 329.67 | 780.88 | 18.65 | 70.00 | 286.83 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-08:20 | 1477.82 | 19.43 | 84.33 | 305.00 | 743.58 | 21.28 | 110.83 | 258.50 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-08:20 | 1526.60 | 19.49 | 87.83 | 289.33 | 789.45 | 22.57 | 117.33 | 249.83 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-08:39 | 1329.82 | 20.19 | 85.00 | 265.50 | 665.78 | 21.71 | 105.17 | 218.00 |
December | 319.00 | 0.53 | 0.48 | 01-DEC-09:20 | 1162.07 | 19.76 | 87.33 | 255.00 | 582.05 | 21.20 | 98.33 | 200.50 |
Annual Sum or Average | 4323.33 | 0.53 | 1405.53 | 17.64 | 684.83 | 3563.50 | 707.32 | 20.09 | 939.17 | 2995.00 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 1162.07 | 14.65 | 0.00 | 247.33 | 582.05 | 17.99 | 29.50 | 200.50 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1561.05 | 20.19 | 87.83 | 336.00 | 802.60 | 22.57 | 117.33 | 289.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-08:09 | 3694.62 | 33.26 | 309.00 | 288.00 | 910.98 | 21.08 | 91.50 | 275.50 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:20 | 1786.33 | 20.74 | 140.00 | 269.00 | 807.83 | 15.62 | 0.00 | 233.33 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:30 | 1287.95 | 11.09 | 5.00 | 303.17 | 690.36 | 15.51 | 0.00 | 264.33 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:49 | 1004.75 | 10.42 | 0.00 | 313.17 | 551.08 | 14.92 | 0.00 | 269.17 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-07:30 | 850.43 | 10.32 | 0.00 | 336.00 | 484.53 | 14.96 | 0.00 | 285.83 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-07:30 | 811.63 | 10.16 | 0.00 | 332.17 | 471.01 | 14.81 | 0.00 | 279.00 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-07:30 | 854.69 | 10.10 | 0.00 | 334.50 | 489.34 | 14.64 | 0.00 | 284.33 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-07:30 | 1005.50 | 10.72 | 0.00 | 332.33 | 559.80 | 15.26 | 0.00 | 287.83 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:30 | 1260.91 | 11.32 | 0.00 | 309.67 | 687.80 | 15.99 | 0.00 | 272.50 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:30 | 1713.01 | 13.28 | 30.67 | 312.67 | 828.59 | 16.82 | 10.50 | 277.33 |
November | 318.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3028.21 | 27.71 | 236.50 | 286.50 | 940.32 | 20.77 | 76.33 | 274.67 |
December | 319.00 | 0.51 | 0.48 | 01-DEC-07:30 | 3659.50 | 32.34 | 292.67 | 280.33 | 979.37 | 22.56 | 113.00 | 269.67 |
Annual Sum or Average | 4323.33 | 0.52 | 1663.53 | 16.09 | 1013.83 | 3697.50 | 683.46 | 16.72 | 291.33 | 3273.50 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 811.63 | 10.10 | 0.00 | 269.00 | 471.01 | 14.64 | 0.00 | 233.33 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 3694.62 | 33.26 | 309.00 | 336.00 | 979.37 | 22.56 | 113.00 | 287.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-07:00 | 1252.28 | 16.49 | 87.50 | 256.67 | 687.82 | 20.69 | 80.67 | 214.50 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-07:49 | 1357.14 | 16.05 | 77.17 | 248.17 | 596.45 | 18.75 | 47.00 | 207.83 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-07:00 | 1296.00 | 15.88 | 83.00 | 294.50 | 657.85 | 18.20 | 52.33 | 247.00 |
April | 375.00 | 0.54 | 0.48 | 01-APR-06:00 | 1492.72 | 15.14 | 84.33 | 305.17 | 788.80 | 19.53 | 79.83 | 261.83 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-06:30 | 1672.67 | 15.20 | 88.83 | 341.83 | 724.49 | 18.06 | 56.83 | 293.33 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-06:19 | 1669.69 | 16.83 | 113.33 | 338.17 | 714.60 | 17.97 | 54.50 | 292.17 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-06:40 | 1530.65 | 14.99 | 87.17 | 334.33 | 684.29 | 17.81 | 52.50 | 294.67 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-06:40 | 1567.71 | 15.40 | 87.83 | 327.00 | 714.28 | 18.43 | 56.00 | 291.00 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-06:49 | 1578.69 | 16.16 | 85.00 | 300.17 | 831.96 | 20.33 | 75.50 | 265.33 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-06:00 | 1473.29 | 16.64 | 87.83 | 289.67 | 754.98 | 18.84 | 56.83 | 250.67 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-06:00 | 1259.61 | 16.97 | 80.83 | 262.67 | 656.26 | 19.42 | 54.33 | 219.50 |
December | 319.00 | 0.53 | 0.48 | 01-DEC-07:19 | 1000.74 | 14.80 | 59.50 | 251.00 | 553.50 | 19.20 | 55.67 | 202.33 |
Annual Sum or Average | 4323.33 | 0.53 | 1444.58 | 15.86 | 1022.33 | 3549.33 | 700.79 | 18.88 | 722.00 | 3040.17 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 1000.74 | 14.80 | 59.50 | 248.17 | 553.50 | 17.81 | 47.00 | 202.33 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1672.67 | 16.97 | 113.33 | 341.83 | 831.96 | 20.69 | 80.67 | 294.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.56 | 0.48 | 01-JAN-10:39 | 473.78 | 7.98 | 0.00 | 237.00 | 285.67 | 12.65 | 0.00 | 101.50 |
February | 308.33 | 0.54 | 0.48 | 01-FEB-09:20 | 539.76 | 8.64 | 0.00 | 238.67 | 324.18 | 13.44 | 0.00 | 153.17 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-09:09 | 631.85 | 9.44 | 0.00 | 292.00 | 373.14 | 14.15 | 0.00 | 225.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:49 | 725.17 | 10.02 | 0.00 | 316.67 | 421.73 | 14.61 | 0.00 | 267.17 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-07:10 | 852.92 | 10.84 | 1.67 | 357.17 | 489.92 | 15.61 | 1.17 | 314.00 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:40 | 944.43 | 13.46 | 43.50 | 353.50 | 534.13 | 17.52 | 34.17 | 320.17 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:00 | 914.98 | 10.53 | 0.00 | 349.83 | 517.72 | 16.82 | 27.33 | 314.67 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:19 | 825.94 | 10.68 | 0.00 | 341.50 | 479.79 | 15.34 | 0.00 | 299.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:40 | 718.02 | 10.45 | 0.00 | 306.33 | 428.56 | 15.14 | 0.00 | 255.83 |
October | 351.17 | 0.54 | 0.48 | 01-OCT-07:00 | 591.49 | 9.52 | 0.00 | 283.83 | 362.53 | 14.24 | 0.00 | 218.83 |
November | 318.83 | 0.54 | 0.48 | 01-NOV-08:20 | 511.09 | 8.80 | 0.00 | 242.83 | 314.95 | 13.73 | 0.00 | 141.00 |
December | 319.00 | 0.56 | 0.48 | 01-DEC-09:20 | 458.51 | 7.84 | 0.00 | 225.83 | 277.27 | 12.65 | 0.00 | 79.17 |
Annual Sum or Average | 4323.33 | 0.53 | 697.87 | 9.97 | 45.17 | 3545.17 | 408.94 | 14.79 | 62.67 | 2690.00 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 458.51 | 7.84 | 0.00 | 225.83 | 277.27 | 12.65 | 0.00 | 79.17 | |
Maximum of Months | 405.33 | 0.56 | 0.48 | 944.43 | 13.46 | 43.50 | 357.17 | 534.13 | 17.52 | 34.17 | 320.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-10:20 | 1218.30 | 16.44 | 86.33 | 258.00 | 658.41 | 20.42 | 77.17 | 212.67 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-09:30 | 1155.48 | 14.24 | 50.67 | 246.67 | 614.71 | 18.75 | 48.33 | 204.50 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-09:30 | 1392.36 | 16.17 | 84.50 | 295.67 | 703.59 | 18.44 | 55.00 | 249.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-08:50 | 1386.61 | 13.33 | 55.00 | 309.50 | 721.42 | 14.96 | 0.00 | 263.17 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-08:09 | 1452.26 | 10.36 | 0.00 | 335.50 | 776.80 | 15.18 | 0.00 | 294.17 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-08:09 | 1551.47 | 10.51 | 0.00 | 333.67 | 822.89 | 15.38 | 0.00 | 293.17 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-08:09 | 1484.49 | 10.65 | 3.67 | 334.83 | 681.39 | 15.19 | 0.00 | 289.67 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-08:09 | 1505.26 | 13.78 | 59.83 | 329.17 | 800.85 | 15.66 | 5.50 | 291.00 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-08:20 | 1470.38 | 16.39 | 84.33 | 304.00 | 763.30 | 18.93 | 57.33 | 263.00 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-08:20 | 1524.49 | 16.59 | 87.83 | 288.50 | 807.42 | 20.51 | 76.83 | 253.00 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-08:39 | 1320.13 | 17.26 | 85.00 | 264.17 | 682.23 | 19.47 | 55.00 | 221.00 |
December | 319.00 | 0.53 | 0.48 | 01-DEC-09:20 | 1153.58 | 16.87 | 87.33 | 254.67 | 595.94 | 18.98 | 56.67 | 204.33 |
Annual Sum or Average | 4323.33 | 0.53 | 1395.58 | 14.18 | 684.50 | 3554.33 | 724.10 | 17.48 | 431.83 | 3038.67 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 1153.58 | 10.36 | 0.00 | 246.67 | 595.94 | 14.96 | 0.00 | 204.33 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1551.47 | 17.26 | 87.83 | 335.50 | 822.89 | 20.51 | 77.17 | 294.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-08:09 | 3694.97 | 33.25 | 309.00 | 288.00 | 912.24 | 21.07 | 91.50 | 275.50 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:20 | 1787.20 | 20.71 | 140.00 | 269.00 | 809.01 | 15.61 | 0.00 | 233.50 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:30 | 1288.85 | 11.05 | 5.00 | 303.17 | 691.35 | 15.50 | 0.00 | 264.33 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:49 | 1005.42 | 10.38 | 0.00 | 313.17 | 551.82 | 14.91 | 0.00 | 269.17 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-07:30 | 850.87 | 10.28 | 0.00 | 336.00 | 485.10 | 14.95 | 0.00 | 285.83 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-07:30 | 811.98 | 10.12 | 0.00 | 332.17 | 471.54 | 14.79 | 0.00 | 279.33 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-07:30 | 855.09 | 10.07 | 0.00 | 334.50 | 489.92 | 14.62 | 0.00 | 284.50 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-07:30 | 1006.08 | 10.68 | 0.00 | 332.33 | 560.51 | 15.25 | 0.00 | 287.83 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:30 | 1261.71 | 11.28 | 0.00 | 309.67 | 688.73 | 15.97 | 0.00 | 272.83 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:30 | 1713.87 | 13.24 | 30.67 | 312.67 | 829.73 | 16.80 | 10.50 | 277.33 |
November | 318.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3028.73 | 27.69 | 236.50 | 286.33 | 941.61 | 20.76 | 76.33 | 274.67 |
December | 319.00 | 0.51 | 0.48 | 01-DEC-07:30 | 3659.65 | 32.33 | 292.67 | 280.33 | 980.63 | 22.55 | 113.00 | 269.67 |
Annual Sum or Average | 4323.33 | 0.52 | 1664.10 | 16.06 | 1013.83 | 3697.33 | 684.37 | 16.70 | 291.33 | 3274.50 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 811.98 | 10.07 | 0.00 | 269.00 | 471.54 | 14.62 | 0.00 | 233.50 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 3694.97 | 33.25 | 309.00 | 336.00 | 980.63 | 22.55 | 113.00 | 287.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-07:00 | 1252.28 | 16.45 | 87.50 | 256.67 | 688.46 | 20.68 | 80.67 | 214.83 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-07:49 | 1357.24 | 16.01 | 77.17 | 248.17 | 597.16 | 18.73 | 47.00 | 207.83 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-07:00 | 1296.37 | 15.84 | 83.00 | 294.50 | 658.60 | 18.18 | 52.33 | 247.33 |
April | 375.00 | 0.54 | 0.48 | 01-APR-06:00 | 1493.11 | 15.10 | 84.33 | 305.17 | 789.57 | 19.52 | 79.83 | 262.00 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-06:30 | 1672.97 | 15.17 | 88.83 | 342.00 | 725.26 | 18.04 | 56.83 | 293.33 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-06:19 | 1669.99 | 16.79 | 113.33 | 338.17 | 715.38 | 17.95 | 54.50 | 292.33 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-06:40 | 1531.02 | 14.95 | 87.17 | 334.33 | 685.09 | 17.80 | 52.50 | 294.67 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-06:40 | 1568.06 | 15.37 | 87.83 | 327.00 | 715.11 | 18.41 | 56.00 | 291.17 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-06:49 | 1578.96 | 16.13 | 85.00 | 300.17 | 832.80 | 20.32 | 75.50 | 265.33 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-06:00 | 1473.23 | 16.60 | 87.83 | 289.67 | 755.74 | 18.82 | 56.83 | 250.67 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-06:00 | 1259.56 | 16.93 | 80.83 | 262.50 | 656.94 | 19.41 | 54.33 | 219.50 |
December | 319.00 | 0.53 | 0.48 | 01-DEC-07:19 | 1000.73 | 14.76 | 59.50 | 251.00 | 554.11 | 19.18 | 55.67 | 202.33 |
Annual Sum or Average | 4323.33 | 0.53 | 1444.79 | 15.82 | 1022.33 | 3549.33 | 701.54 | 18.87 | 722.00 | 3041.33 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 1000.73 | 14.76 | 59.50 | 248.17 | 554.11 | 17.80 | 47.00 | 202.33 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1672.97 | 16.93 | 113.33 | 342.00 | 832.80 | 20.68 | 80.67 | 294.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.56 | 0.48 | 01-JAN-10:39 | 473.82 | 7.95 | 0.00 | 237.00 | 285.98 | 12.64 | 0.00 | 102.33 |
February | 308.33 | 0.54 | 0.48 | 01-FEB-09:20 | 539.84 | 8.59 | 0.00 | 238.67 | 324.53 | 13.42 | 0.00 | 153.67 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-09:09 | 632.01 | 9.40 | 0.00 | 292.00 | 373.56 | 14.13 | 0.00 | 225.50 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:49 | 725.41 | 9.98 | 0.00 | 316.67 | 422.22 | 14.59 | 0.00 | 267.50 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-07:10 | 853.23 | 10.80 | 1.67 | 357.17 | 490.49 | 15.60 | 1.17 | 314.00 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:40 | 944.79 | 13.43 | 43.50 | 353.50 | 534.77 | 17.51 | 34.17 | 320.17 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:00 | 915.34 | 10.49 | 0.00 | 350.00 | 518.34 | 16.80 | 27.33 | 314.67 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:19 | 826.20 | 10.64 | 0.00 | 341.50 | 480.34 | 15.32 | 0.00 | 299.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:40 | 718.14 | 10.41 | 0.00 | 306.33 | 429.02 | 15.12 | 0.00 | 255.83 |
October | 351.17 | 0.54 | 0.48 | 01-OCT-07:00 | 591.51 | 9.48 | 0.00 | 283.83 | 362.89 | 14.22 | 0.00 | 219.17 |
November | 318.83 | 0.54 | 0.48 | 01-NOV-08:20 | 511.08 | 8.76 | 0.00 | 242.83 | 315.26 | 13.71 | 0.00 | 141.50 |
December | 319.00 | 0.56 | 0.48 | 01-DEC-09:20 | 458.55 | 7.80 | 0.00 | 225.83 | 277.57 | 12.63 | 0.00 | 79.83 |
Annual Sum or Average | 4323.33 | 0.53 | 698.04 | 9.93 | 45.17 | 3545.33 | 409.40 | 14.77 | 62.67 | 2693.67 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 458.55 | 7.80 | 0.00 | 225.83 | 277.57 | 12.63 | 0.00 | 79.83 | |
Maximum of Months | 405.33 | 0.56 | 0.48 | 944.79 | 13.43 | 43.50 | 357.17 | 534.77 | 17.51 | 34.17 | 320.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-10:20 | 1218.30 | 16.41 | 86.33 | 258.00 | 659.05 | 20.41 | 77.17 | 212.83 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-09:30 | 1155.58 | 14.20 | 50.67 | 246.67 | 615.43 | 18.73 | 48.33 | 204.83 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-09:30 | 1392.56 | 16.13 | 84.50 | 295.67 | 704.38 | 18.43 | 55.00 | 249.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-08:50 | 1387.00 | 13.29 | 55.00 | 309.50 | 722.20 | 14.94 | 0.00 | 263.17 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-08:09 | 1452.60 | 10.32 | 0.00 | 335.50 | 777.58 | 15.17 | 0.00 | 294.17 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-07:00 | 1551.79 | 10.46 | 0.00 | 333.67 | 823.69 | 15.36 | 0.00 | 293.33 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-08:09 | 1484.89 | 10.61 | 3.67 | 334.83 | 682.20 | 15.17 | 0.00 | 289.83 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-08:09 | 1505.62 | 13.74 | 59.83 | 329.17 | 801.70 | 15.64 | 5.50 | 291.33 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-08:20 | 1470.70 | 16.35 | 84.33 | 304.00 | 764.15 | 18.91 | 57.33 | 263.00 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-08:20 | 1524.58 | 16.55 | 87.83 | 288.50 | 808.17 | 20.50 | 76.83 | 253.00 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-08:39 | 1320.06 | 17.22 | 85.00 | 264.17 | 682.90 | 19.46 | 55.00 | 221.17 |
December | 319.00 | 0.53 | 0.48 | 01-DEC-09:20 | 1153.56 | 16.83 | 87.33 | 254.67 | 596.55 | 18.97 | 56.67 | 204.33 |
Annual Sum or Average | 4323.33 | 0.53 | 1395.80 | 14.14 | 684.50 | 3554.33 | 724.86 | 17.47 | 431.83 | 3040.00 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 1153.56 | 10.32 | 0.00 | 246.67 | 596.55 | 14.94 | 0.00 | 204.33 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1551.79 | 17.22 | 87.83 | 335.50 | 823.69 | 20.50 | 77.17 | 294.17 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 92275.86 | 153.79 | 06-JAN-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 37294.73 | 62.16 | 01-FEB-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 129570.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 92275.86 | 153.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 30080218.93 | 1823.31 | 02-JAN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 937677.94 | 325.11 | 13-FEB-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31017896.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30080218.93 | 1823.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 11793996.45 | 1236.59 | 02-JAN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 43443.04 | 72.41 | 13-FEB-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16372.89 | 27.29 | 18-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 11853812.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11793996.45 | 1236.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 337071.65 | 270.57 | 20-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 337071.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 337071.65 | 270.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 6686885.23 | 525.73 | 20-JAN-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6686885.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6686885.23 | 525.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.715098E+11 | 0.685013E+11 | 210057.45 | 30-JAN-06:03 | 141506.31 | 0.53 |
February | 0.00 | 0.00 | 0.823144E+11 | 0.761813E+11 | 238223.07 | 06-FEB-06:02 | 157178.42 | 0.62 |
March | 0.00 | 0.00 | 0.120093E+12 | 0.111849E+12 | 227566.78 | 29-MAR-05:02 | 148093.82 | 0.70 |
April | 0.00 | 0.00 | 0.156554E+12 | 0.136595E+12 | 239846.38 | 10-APR-05:02 | 158682.62 | 0.83 |
May | 0.00 | 0.00 | 0.198856E+12 | 0.162778E+12 | 277216.22 | 30-MAY-05:03 | 167591.95 | 0.81 |
June | 0.00 | 0.00 | 0.259662E+12 | 0.182053E+12 | 289590.98 | 09-JUN-05:03 | 167773.15 | 0.88 |
July | 0.00 | 0.00 | 0.313375E+12 | 0.206525E+12 | 315478.37 | 05-JUL-05:02 | 176868.52 | 0.88 |
August | 0.00 | 0.00 | 0.343167E+12 | 0.225439E+12 | 315396.11 | 21-AUG-05:03 | 180421.22 | 0.89 |
September | 0.00 | 0.00 | 0.258940E+12 | 0.168713E+12 | 290828.97 | 08-SEP-05:02 | 166741.26 | 0.83 |
October | 0.00 | 0.00 | 0.212697E+12 | 0.157164E+12 | 283739.98 | 02-OCT-05:02 | 168209.66 | 0.81 |
November | 0.00 | 0.00 | 0.153081E+12 | 0.127375E+12 | 250948.06 | 01-NOV-05:02 | 157002.11 | 0.78 |
December | 0.00 | 0.00 | 0.109326E+12 | 0.976566E+11 | 211393.85 | 11-DEC-06:03 | 141476.72 | 0.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.227958E+13 | 0.172083E+13 | 0.77 | |||
Minimum of Months | 0.00 | 0.00 | 0.715098E+11 | 0.685013E+11 | 210057.45 | 141476.72 | 0.53 | |
Maximum of Months | 0.00 | 0.00 | 0.343167E+12 | 0.225439E+12 | 315478.37 | 180421.22 | 0.89 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.530990E+12 | 0.507351E+12 | 1742980.36 | 30-JAN-06:03 | 1147878.04 | 0.48 |
February | 0.00 | 0.00 | 0.601720E+12 | 0.552241E+12 | 2276203.65 | 09-FEB-06:02 | 1396689.22 | 0.56 |
March | 0.00 | 0.00 | 0.876185E+12 | 0.809967E+12 | 2240589.37 | 29-MAR-05:02 | 1389660.73 | 0.58 |
April | 0.00 | 0.00 | 0.113308E+13 | 0.986900E+12 | 2395291.47 | 20-APR-05:03 | 1444918.18 | 0.62 |
May | 0.00 | 0.00 | 0.178619E+13 | 0.145099E+13 | 2533727.43 | 24-MAY-05:03 | 1389157.10 | 0.74 |
June | 0.00 | 0.00 | 0.230525E+13 | 0.157468E+13 | 2858237.39 | 27-JUN-05:02 | 1556328.44 | 0.81 |
July | 0.00 | 0.00 | 0.280418E+13 | 0.176171E+13 | 3094915.38 | 12-JUL-05:02 | 1618005.56 | 0.84 |
August | 0.00 | 0.00 | 0.303128E+13 | 0.187853E+13 | 3016435.50 | 26-AUG-05:02 | 1522649.42 | 0.85 |
September | 0.00 | 0.00 | 0.235278E+13 | 0.148957E+13 | 2857715.88 | 28-SEP-05:02 | 1510772.91 | 0.77 |
October | 0.00 | 0.00 | 0.174057E+13 | 0.126820E+13 | 2736818.30 | 07-OCT-05:03 | 1489004.25 | 0.68 |
November | 0.00 | 0.00 | 0.114710E+13 | 0.932229E+12 | 2426652.64 | 10-NOV-06:02 | 1447357.40 | 0.60 |
December | 0.00 | 0.00 | 0.696966E+12 | 0.614842E+12 | 2211389.18 | 11-DEC-06:03 | 1393337.90 | 0.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.190063E+14 | 0.138272E+14 | 0.67 | |||
Minimum of Months | 0.00 | 0.00 | 0.530990E+12 | 0.507351E+12 | 1742980.36 | 1147878.04 | 0.48 | |
Maximum of Months | 0.00 | 0.00 | 0.303128E+13 | 0.187853E+13 | 3094915.38 | 1618005.56 | 0.85 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.465427E+11 | 0.442504E+11 | 161812.33 | 30-JAN-06:03 | 101746.43 | 0.47 |
February | 0.00 | 0.00 | 0.582734E+11 | 0.534156E+11 | 203629.73 | 06-FEB-06:02 | 134982.34 | 0.54 |
March | 0.00 | 0.00 | 0.902165E+11 | 0.835813E+11 | 230405.10 | 29-MAR-05:02 | 140962.76 | 0.57 |
April | 0.00 | 0.00 | 0.123160E+12 | 0.108122E+12 | 235207.90 | 19-APR-05:02 | 144944.32 | 0.62 |
May | 0.00 | 0.00 | 0.202818E+12 | 0.167612E+12 | 292142.29 | 31-MAY-05:02 | 176809.05 | 0.77 |
June | 0.00 | 0.00 | 0.260755E+12 | 0.184231E+12 | 323496.95 | 27-JUN-05:02 | 178625.92 | 0.83 |
July | 0.00 | 0.00 | 0.315049E+12 | 0.207566E+12 | 349531.01 | 12-JUL-05:02 | 188510.59 | 0.85 |
August | 0.00 | 0.00 | 0.338295E+12 | 0.219872E+12 | 353462.43 | 08-AUG-05:02 | 179474.51 | 0.87 |
September | 0.00 | 0.00 | 0.261473E+12 | 0.171210E+12 | 325650.02 | 08-SEP-05:02 | 180901.20 | 0.80 |
October | 0.00 | 0.00 | 0.188397E+12 | 0.139396E+12 | 309527.36 | 02-OCT-05:02 | 174934.77 | 0.69 |
November | 0.00 | 0.00 | 0.116495E+12 | 0.951350E+11 | 268405.01 | 01-NOV-05:02 | 159036.31 | 0.59 |
December | 0.00 | 0.00 | 0.653964E+11 | 0.574778E+11 | 194354.91 | 11-DEC-06:03 | 120919.46 | 0.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.206687E+13 | 0.153187E+13 | 0.68 | |||
Minimum of Months | 0.00 | 0.00 | 0.465427E+11 | 0.442504E+11 | 161812.33 | 101746.43 | 0.47 | |
Maximum of Months | 0.00 | 0.00 | 0.338295E+12 | 0.219872E+12 | 353462.43 | 188510.59 | 0.87 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.651652E+11 | 0.636699E+11 | 148561.69 | 30-JAN-04:03 | 91964.41 | 0.52 |
February | 0.00 | 0.00 | 0.623564E+11 | 0.602227E+11 | 157275.66 | 09-FEB-04:02 | 85316.98 | 0.57 |
March | 0.00 | 0.00 | 0.760848E+11 | 0.734980E+11 | 165747.36 | 29-MAR-03:02 | 86528.40 | 0.58 |
April | 0.00 | 0.00 | 0.794076E+11 | 0.745458E+11 | 167101.01 | 12-APR-03:02 | 87561.98 | 0.55 |
May | 0.00 | 0.00 | 0.104581E+12 | 0.918537E+11 | 223211.15 | 30-MAY-01:30 | 88309.00 | 0.60 |
June | 0.00 | 0.00 | 0.123841E+12 | 0.967158E+11 | 230579.38 | 25-JUN-19:00 | 94297.33 | 0.63 |
July | 0.00 | 0.00 | 0.148819E+12 | 0.105362E+12 | 241841.04 | 16-JUL-16:51 | 97884.81 | 0.62 |
August | 0.00 | 0.00 | 0.170581E+12 | 0.118822E+12 | 236751.32 | 21-AUG-01:40 | 92210.09 | 0.67 |
September | 0.00 | 0.00 | 0.136720E+12 | 0.994039E+11 | 246570.98 | 10-SEP-15:22 | 96049.36 | 0.64 |
October | 0.00 | 0.00 | 0.120886E+12 | 0.974259E+11 | 224614.08 | 01-OCT-22:10 | 90212.94 | 0.64 |
November | 0.00 | 0.00 | 0.982572E+11 | 0.854695E+11 | 179864.54 | 03-NOV-03:02 | 89375.13 | 0.63 |
December | 0.00 | 0.00 | 0.761037E+11 | 0.715972E+11 | 155756.59 | 06-DEC-04:02 | 84890.02 | 0.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.126280E+13 | 0.103859E+13 | 0.60 | |||
Minimum of Months | 0.00 | 0.00 | 0.623564E+11 | 0.602227E+11 | 148561.69 | 84890.02 | 0.52 | |
Maximum of Months | 0.00 | 0.00 | 0.170581E+12 | 0.118822E+12 | 246570.98 | 97884.81 | 0.67 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.563873E+10 | 0.531344E+10 | 2633.43 | 30-JAN-15:00 | 2224.42 | 0.00 |
February | 0.00 | 0.00 | 0.998705E+10 | 0.954866E+10 | 4744.57 | 07-FEB-16:10 | 4267.86 | 0.00 |
March | 0.00 | 0.00 | 0.162229E+11 | 0.157715E+11 | 8095.91 | 31-MAR-23:10 | 7617.05 | 0.00 |
April | 0.00 | 0.00 | 0.209086E+11 | 0.203153E+11 | 8715.48 | 30-APR-18:00 | 8160.49 | 0.00 |
May | 0.00 | 0.00 | 0.698876E+10 | 0.628252E+10 | 4561.08 | 31-MAY-23:05 | 4123.49 | 0.00 |
June | 0.00 | 0.00 | 0.122459E+11 | 0.110763E+11 | 6746.12 | 30-JUN-23:03 | 5955.12 | 0.00 |
July | 0.00 | 0.00 | 0.181902E+11 | 0.167180E+11 | 8578.70 | 31-JUL-23:57 | 7873.48 | 0.00 |
August | 0.00 | 0.00 | 0.226836E+11 | 0.211301E+11 | 8813.69 | 21-AUG-04:53 | 7996.96 | 0.00 |
September | 0.00 | 0.00 | 0.744417E+10 | 0.620203E+10 | 5020.16 | 30-SEP-23:03 | 4023.54 | 0.00 |
October | 0.00 | 0.00 | 0.122428E+11 | 0.112406E+11 | 6257.31 | 31-OCT-23:03 | 5876.49 | 0.00 |
November | 0.00 | 0.00 | 0.161808E+11 | 0.154688E+11 | 6883.91 | 01-NOV-15:00 | 6221.91 | 0.00 |
December | 0.00 | 0.00 | 0.212353E+11 | 0.206706E+11 | 8604.67 | 05-DEC-17:00 | 8033.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169969E+12 | 0.159738E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.563873E+10 | 0.531344E+10 | 2633.43 | 2224.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.226836E+11 | 0.211301E+11 | 8813.69 | 8160.49 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.470828E+11 | 0.439619E+11 | 24088.55 | 30-JAN-15:00 | 20085.98 | 0.00 |
February | 0.00 | 0.00 | 0.906893E+11 | 0.863572E+11 | 45167.07 | 07-FEB-16:10 | 40426.01 | 0.00 |
March | 0.00 | 0.00 | 0.152815E+12 | 0.148316E+12 | 77543.06 | 31-MAR-23:10 | 72695.90 | 0.00 |
April | 0.00 | 0.00 | 0.199635E+12 | 0.193706E+12 | 83072.51 | 30-APR-18:00 | 77513.19 | 0.00 |
May | 0.00 | 0.00 | 0.657560E+11 | 0.587742E+11 | 44265.66 | 31-MAY-23:05 | 39830.25 | 0.00 |
June | 0.00 | 0.00 | 0.116401E+12 | 0.104764E+12 | 65277.01 | 30-JUN-23:03 | 57268.41 | 0.00 |
July | 0.00 | 0.00 | 0.172895E+12 | 0.158216E+12 | 81960.32 | 31-JUL-24:00 | 74954.76 | 0.00 |
August | 0.00 | 0.00 | 0.216219E+12 | 0.200693E+12 | 83985.48 | 08-AUG-04:05 | 75282.97 | 0.00 |
September | 0.00 | 0.00 | 0.697702E+11 | 0.574969E+11 | 48984.72 | 30-SEP-23:03 | 38756.85 | 0.00 |
October | 0.00 | 0.00 | 0.116197E+12 | 0.106227E+12 | 60265.05 | 31-OCT-23:03 | 56384.49 | 0.00 |
November | 0.00 | 0.00 | 0.153323E+12 | 0.146226E+12 | 66143.38 | 01-NOV-15:00 | 59545.70 | 0.00 |
December | 0.00 | 0.00 | 0.199144E+12 | 0.193506E+12 | 82120.75 | 05-DEC-17:00 | 76420.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.159993E+13 | 0.149824E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.470828E+11 | 0.439619E+11 | 24088.55 | 20085.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216219E+12 | 0.200693E+12 | 83985.48 | 77513.19 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.401152E+10 | 0.369756E+10 | 2455.21 | 30-JAN-15:00 | 2044.48 | 0.00 |
February | 0.00 | 0.00 | 0.871008E+10 | 0.826295E+10 | 4595.34 | 07-FEB-16:10 | 4112.93 | 0.00 |
March | 0.00 | 0.00 | 0.151319E+11 | 0.146640E+11 | 7700.48 | 31-MAR-23:10 | 7205.87 | 0.00 |
April | 0.00 | 0.00 | 0.200307E+11 | 0.194196E+11 | 8566.49 | 30-APR-18:00 | 7999.94 | 0.00 |
May | 0.00 | 0.00 | 0.678702E+10 | 0.606770E+10 | 4505.49 | 31-MAY-23:05 | 4053.55 | 0.00 |
June | 0.00 | 0.00 | 0.118782E+11 | 0.106937E+11 | 6577.57 | 30-JUN-23:03 | 5769.32 | 0.00 |
July | 0.00 | 0.00 | 0.176153E+11 | 0.161264E+11 | 8438.08 | 31-JUL-23:03 | 7547.53 | 0.00 |
August | 0.00 | 0.00 | 0.221301E+11 | 0.205476E+11 | 8606.77 | 08-AUG-07:40 | 7664.53 | 0.00 |
September | 0.00 | 0.00 | 0.719276E+10 | 0.594162E+10 | 4948.20 | 30-SEP-23:03 | 3927.45 | 0.00 |
October | 0.00 | 0.00 | 0.117339E+11 | 0.107176E+11 | 6040.10 | 31-OCT-23:03 | 5641.54 | 0.00 |
November | 0.00 | 0.00 | 0.152549E+11 | 0.145272E+11 | 6692.71 | 01-NOV-15:00 | 6024.80 | 0.00 |
December | 0.00 | 0.00 | 0.195023E+11 | 0.189197E+11 | 8248.03 | 05-DEC-17:00 | 7670.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.159979E+12 | 0.149586E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.401152E+10 | 0.369756E+10 | 2455.21 | 2044.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.221301E+11 | 0.205476E+11 | 8606.77 | 7999.94 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 3.16 | 636.64 | 20-JAN-07:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.13 | 125.93 | 13-FEB-06:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 8.63 | 18-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.28 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 3.16 | 636.64 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 522977.40 | 1921967.21 | 30-JAN-06:03 | 23.90 | 93930.67 | 15-JAN-23:05 |
February | 598586.15 | 2250471.56 | 09-FEB-06:02 | 1.56 | 7223.96 | 12-FEB-22:15 |
March | 715952.90 | 2747795.35 | 29-MAR-05:04 | 24.11 | 171564.06 | 12-MAR-07:53 |
April | 870270.64 | 2559895.36 | 20-APR-05:03 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1136786.15 | 2896108.53 | 31-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1354623.81 | 3441257.52 | 08-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1519215.75 | 3413388.83 | 20-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1606441.67 | 3961114.41 | 03-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1341740.30 | 3560123.61 | 28-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 1078081.91 | 3364938.27 | 24-OCT-05:02 | 4.24 | 36918.36 | 20-OCT-23:53 |
November | 838297.19 | 3096781.40 | 10-NOV-06:04 | 8.72 | 89615.08 | 23-NOV-06:33 |
December | 630686.84 | 2316821.14 | 11-DEC-06:03 | 5.31 | 63652.71 | 17-DEC-07:43 |
Annual Sum or Average | 1020336.42 | 5.73 | ||||
Minimum of Months | 522977.40 | 1921967.21 | 0.00 | 0.00 | ||
Maximum of Months | 1606441.67 | 3961114.41 | 24.11 | 171564.06 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 327872.19 | 3279887.22 | 30-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 395513.35 | 4142254.36 | 09-FEB-06:02 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 506606.90 | 4341209.49 | 29-MAR-05:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 650005.82 | 4321704.70 | 19-APR-05:02 | 0.00 | 0.00 | 01-APR-00:05 |
May | 928594.09 | 4627855.50 | 02-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1199129.69 | 5180382.84 | 08-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1384170.11 | 5209800.24 | 27-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1489926.97 | 5371230.84 | 30-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1212107.91 | 5227400.82 | 28-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 905819.10 | 5109746.84 | 18-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 649995.08 | 4704700.26 | 10-NOV-06:02 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 417475.94 | 3854134.77 | 11-DEC-06:03 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 841605.35 | 0.00 | ||||
Minimum of Months | 327872.19 | 3279887.22 | 0.00 | 0.00 | ||
Maximum of Months | 1489926.97 | 5371230.84 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 49200.83 | 138033.08 | 23-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 93355.98 | 221687.08 | 06-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 148828.33 | 315656.76 | 27-MAR-11:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 219081.29 | 387294.57 | 28-APR-12:00 | 0.00 | 0.00 | 01-APR-00:05 |
May | 178189.97 | 294290.94 | 31-MAY-19:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 232434.99 | 344403.99 | 12-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 291927.98 | 410395.74 | 21-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 324107.57 | 435194.57 | 16-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 194159.87 | 288135.93 | 04-SEP-14:54 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 192436.44 | 283408.08 | 04-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 177192.61 | 270474.44 | 01-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 157199.97 | 255707.39 | 10-DEC-12:00 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 188763.43 | 0.00 | ||||
Minimum of Months | 49200.83 | 138033.08 | 0.00 | 0.00 | ||
Maximum of Months | 324107.57 | 435194.57 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 11557.70 | 37781.52 | 13-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11332.85 | 37387.74 | 01-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11206.51 | 35669.03 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:05 | 9664.01 | 32369.09 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 9010.48 | 29237.18 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 8495.42 | 26295.69 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 7733.71 | 24894.24 | 31-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 8644.93 | 26762.11 | 31-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 8916.26 | 29644.07 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 9824.35 | 33227.82 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 10850.28 | 36032.85 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 11125.44 | 37583.20 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 9855.60 | ||||
Minimum of Months | 0.00 | 0.00 | 7733.71 | 24894.24 | ||
Maximum of Months | 0.00 | 0.00 | 11557.70 | 37781.52 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 323691.51 | 1823702.79 | 30-JAN-06:03 | 565.12 | 121333.40 | 01-JAN-05:20 |
February | 411627.97 | 4332041.56 | 07-FEB-15:50 | 273.94 | 68610.68 | 13-FEB-04:35 |
March | 552773.37 | 4026835.66 | 28-MAR-16:00 | 270.46 | 53426.78 | 22-MAR-02:50 |
April | 919811.42 | 5785620.43 | 30-APR-15:02 | 89.72 | 27550.00 | 06-APR-00:03 |
May | 1987543.55 | 7349840.63 | 31-MAY-16:00 | 0.62 | 5578.17 | 07-MAY-06:10 |
June | 3462467.53 | 7695053.81 | 09-JUN-05:05 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 4409562.78 | 8170958.01 | 19-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 4868085.48 | 8218923.51 | 10-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 3756745.96 | 7915951.62 | 07-SEP-14:10 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 2173417.86 | 7135443.34 | 06-OCT-16:00 | 0.53 | 1973.09 | 20-OCT-03:00 |
November | 1032196.95 | 6705388.28 | 01-NOV-14:00 | 39.35 | 36843.37 | 26-NOV-02:15 |
December | 459553.17 | 4490368.56 | 05-DEC-15:40 | 422.92 | 76567.25 | 31-DEC-23:50 |
Annual Sum or Average | 2040207.39 | 138.61 | ||||
Minimum of Months | 323691.51 | 1823702.79 | 0.00 | 0.00 | ||
Maximum of Months | 4868085.48 | 8218923.51 | 565.12 | 121333.40 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158235E+11 | 0.89 | 9183.69 | 01-JAN-00:15 | 1.38 |
February | 0.139413E+11 | 0.86 | 9183.69 | 01-FEB-04:03 | 1.38 |
March | 0.154484E+11 | 0.86 | 9183.69 | 01-MAR-04:05 | 1.37 |
April | 0.141727E+11 | 0.82 | 9183.69 | 01-APR-03:05 | 1.37 |
May | 0.152783E+11 | 0.85 | 9183.69 | 01-MAY-00:20 | 1.37 |
June | 0.151233E+11 | 0.87 | 9183.69 | 01-JUN-03:02 | 1.38 |
July | 0.154427E+11 | 0.86 | 9183.69 | 01-JUL-03:02 | 1.38 |
August | 0.166161E+11 | 0.93 | 9183.69 | 01-AUG-03:02 | 1.38 |
September | 0.155519E+11 | 0.90 | 9183.69 | 01-SEP-03:02 | 1.38 |
October | 0.161689E+11 | 0.90 | 9183.69 | 01-OCT-11:03 | 1.37 |
November | 0.157115E+11 | 0.91 | 9183.69 | 01-NOV-03:02 | 1.38 |
December | 0.158157E+11 | 0.88 | 9183.69 | 01-DEC-04:02 | 1.38 |
Annual Sum or Average | 0.185094E+12 | 0.88 | |||
Minimum of Months | 0.139413E+11 | 0.82 | 9183.69 | 1.37 | |
Maximum of Months | 0.166161E+11 | 0.93 | 9183.69 | 1.38 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.606727E+10 | 0.39 | 17051.75 | 25-JAN-06:02 | 1.58 |
February | 0.659627E+10 | 0.44 | 20267.72 | 06-FEB-06:02 | 1.76 |
March | 0.926571E+10 | 0.54 | 20267.72 | 02-MAR-06:03 | 1.76 |
April | 0.104926E+11 | 0.62 | 20267.72 | 03-APR-05:02 | 1.76 |
May | 0.109026E+11 | 0.61 | 20267.72 | 01-MAY-04:23 | 1.76 |
June | 0.124709E+11 | 0.68 | 20267.72 | 01-JUN-05:02 | 1.76 |
July | 0.144791E+11 | 0.72 | 20267.72 | 01-JUL-05:02 | 1.76 |
August | 0.175019E+11 | 0.80 | 20267.72 | 01-AUG-05:03 | 1.76 |
September | 0.113614E+11 | 0.63 | 20267.72 | 01-SEP-05:03 | 1.76 |
October | 0.114046E+11 | 0.62 | 20267.72 | 02-OCT-05:02 | 1.76 |
November | 0.102132E+11 | 0.59 | 20267.72 | 01-NOV-05:02 | 1.76 |
December | 0.860216E+10 | 0.51 | 17992.45 | 11-DEC-06:03 | 1.63 |
Annual Sum or Average | 0.129358E+12 | 0.60 | |||
Minimum of Months | 0.606727E+10 | 0.39 | 17051.75 | 1.58 | |
Maximum of Months | 0.175019E+11 | 0.80 | 20267.72 | 1.76 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.412633E+11 | 0.32 | 141150.73 | 30-JAN-06:03 | 1.44 |
February | 0.423989E+11 | 0.35 | 192469.81 | 06-FEB-06:02 | 1.76 |
March | 0.599549E+11 | 0.40 | 192469.81 | 14-MAR-05:02 | 1.76 |
April | 0.667383E+11 | 0.44 | 192469.81 | 03-APR-05:02 | 1.76 |
May | 0.916324E+11 | 0.55 | 192469.81 | 05-MAY-05:02 | 1.76 |
June | 0.960711E+11 | 0.59 | 192469.81 | 02-JUN-05:02 | 1.76 |
July | 0.100429E+12 | 0.60 | 192469.81 | 27-JUL-05:02 | 1.76 |
August | 0.113919E+12 | 0.65 | 192469.81 | 05-AUG-05:02 | 1.76 |
September | 0.921420E+11 | 0.57 | 192469.81 | 06-SEP-05:02 | 1.76 |
October | 0.845394E+11 | 0.50 | 192469.81 | 03-OCT-05:03 | 1.76 |
November | 0.669223E+11 | 0.43 | 192469.81 | 04-NOV-05:02 | 1.76 |
December | 0.463221E+11 | 0.34 | 192469.81 | 11-DEC-06:03 | 1.76 |
Annual Sum or Average | 0.902334E+12 | 0.48 | |||
Minimum of Months | 0.412633E+11 | 0.32 | 141150.73 | 1.44 | |
Maximum of Months | 0.113919E+12 | 0.65 | 192469.81 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.324311E+10 | 0.28 | 10464.92 | 30-JAN-06:03 | 1.08 |
February | 0.361010E+10 | 0.30 | 16134.91 | 06-FEB-06:02 | 1.42 |
March | 0.546995E+10 | 0.36 | 21375.28 | 02-MAR-06:03 | 1.69 |
April | 0.661719E+10 | 0.41 | 22513.78 | 03-APR-05:02 | 1.75 |
May | 0.100516E+11 | 0.54 | 22513.78 | 09-MAY-05:03 | 1.74 |
June | 0.110005E+11 | 0.59 | 22513.78 | 26-JUN-05:02 | 1.75 |
July | 0.119520E+11 | 0.61 | 22513.78 | 03-JUL-05:02 | 1.75 |
August | 0.132989E+11 | 0.65 | 22513.78 | 07-AUG-05:02 | 1.75 |
September | 0.100792E+11 | 0.56 | 22513.78 | 06-SEP-05:02 | 1.75 |
October | 0.848096E+10 | 0.47 | 22513.78 | 02-OCT-05:02 | 1.75 |
November | 0.593473E+10 | 0.38 | 20839.49 | 01-NOV-05:02 | 1.66 |
December | 0.380464E+10 | 0.29 | 12259.14 | 11-DEC-06:03 | 1.19 |
Annual Sum or Average | 0.935428E+11 | 0.45 | |||
Minimum of Months | 0.324311E+10 | 0.28 | 10464.92 | 1.08 | |
Maximum of Months | 0.132989E+11 | 0.65 | 22513.78 | 1.75 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140279E+10 | 0.91 | 523.74 | 01-JAN-00:05 | 0.91 |
February | 0.126703E+10 | 0.91 | 523.74 | 01-FEB-00:10 | 0.91 |
March | 0.140279E+10 | 0.91 | 523.74 | 01-MAR-00:10 | 0.91 |
April | 0.135754E+10 | 0.91 | 523.74 | 01-APR-00:05 | 0.91 |
May | 0.140279E+10 | 0.91 | 523.74 | 01-MAY-00:03 | 0.91 |
June | 0.135754E+10 | 0.91 | 523.74 | 01-JUN-00:03 | 0.91 |
July | 0.140279E+10 | 0.91 | 523.74 | 01-JUL-00:03 | 0.91 |
August | 0.140279E+10 | 0.91 | 523.74 | 01-AUG-00:03 | 0.91 |
September | 0.135754E+10 | 0.91 | 523.74 | 01-SEP-00:03 | 0.91 |
October | 0.140279E+10 | 0.91 | 523.74 | 01-OCT-00:03 | 0.91 |
November | 0.135754E+10 | 0.91 | 523.74 | 01-NOV-00:03 | 0.91 |
December | 0.140279E+10 | 0.91 | 523.74 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.165167E+11 | 0.91 | |||
Minimum of Months | 0.126703E+10 | 0.91 | 523.74 | 0.91 | |
Maximum of Months | 0.140279E+10 | 0.91 | 523.74 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.133531E+11 | 0.91 | 4985.48 | 01-JAN-00:05 | 0.91 |
February | 0.120609E+11 | 0.91 | 4985.48 | 01-FEB-00:10 | 0.91 |
March | 0.133531E+11 | 0.91 | 4985.48 | 01-MAR-00:10 | 0.91 |
April | 0.129224E+11 | 0.91 | 4985.48 | 01-APR-00:05 | 0.91 |
May | 0.133531E+11 | 0.91 | 4985.48 | 01-MAY-00:03 | 0.91 |
June | 0.129224E+11 | 0.91 | 4985.48 | 01-JUN-00:03 | 0.91 |
July | 0.133531E+11 | 0.91 | 4985.48 | 01-JUL-00:03 | 0.91 |
August | 0.133531E+11 | 0.91 | 4985.48 | 01-AUG-00:03 | 0.91 |
September | 0.129224E+11 | 0.91 | 4985.48 | 01-SEP-00:03 | 0.91 |
October | 0.133531E+11 | 0.91 | 4985.48 | 01-OCT-00:03 | 0.91 |
November | 0.129224E+11 | 0.91 | 4985.48 | 01-NOV-00:03 | 0.91 |
December | 0.133531E+11 | 0.91 | 4985.48 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.157222E+12 | 0.91 | |||
Minimum of Months | 0.120609E+11 | 0.91 | 4985.48 | 0.91 | |
Maximum of Months | 0.133531E+11 | 0.91 | 4985.48 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134824E+10 | 0.91 | 503.38 | 01-JAN-00:05 | 0.91 |
February | 0.121777E+10 | 0.91 | 503.38 | 01-FEB-00:10 | 0.91 |
March | 0.134824E+10 | 0.91 | 503.38 | 01-MAR-00:10 | 0.91 |
April | 0.130475E+10 | 0.91 | 503.38 | 01-APR-00:05 | 0.91 |
May | 0.134824E+10 | 0.91 | 503.38 | 01-MAY-00:03 | 0.91 |
June | 0.130475E+10 | 0.91 | 503.38 | 01-JUN-00:03 | 0.91 |
July | 0.134824E+10 | 0.91 | 503.38 | 01-JUL-00:03 | 0.91 |
August | 0.134824E+10 | 0.91 | 503.38 | 01-AUG-00:03 | 0.91 |
September | 0.130475E+10 | 0.91 | 503.38 | 01-SEP-00:07 | 0.91 |
October | 0.134824E+10 | 0.91 | 503.38 | 01-OCT-00:03 | 0.91 |
November | 0.130475E+10 | 0.91 | 503.38 | 01-NOV-00:03 | 0.91 |
December | 0.134824E+10 | 0.91 | 503.38 | 01-DEC-00:05 | 0.92 |
Annual Sum or Average | 0.158745E+11 | 0.91 | |||
Minimum of Months | 0.121777E+10 | 0.91 | 503.38 | 0.91 | |
Maximum of Months | 0.134824E+10 | 0.91 | 503.38 | 0.92 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 190492.74 | 173157.90 | 12.36 | 02-JAN-06:08 | 11.24 | 11.24 | 79.27 | 0.01 |
February | 3801.94 | 3455.97 | 1.49 | 13-FEB-06:50 | 1.35 | 1.35 | 59.52 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 59.24 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 59.24 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 59.24 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 59.24 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 59.24 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 59.24 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 59.24 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 59.24 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 59.24 | 0.00 |
December | 60.41 | 54.91 | 0.10 | 18-DEC-07:00 | 0.09 | 0.09 | 59.24 | 0.00 |
Annual Sum or Average | 194355.09 | 176668.78 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.24 | 0.00 | |
Maximum of Months | 190492.74 | 173157.90 | 12.36 | 11.24 | 11.24 | 79.27 | 0.01 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.410997E+09 | 0.373596E+09 | 10010.52 | 30-JAN-06:03 | 9099.56 | 9099.56 | 8.03 | 87.87 |
February | 0.475044E+09 | 0.431815E+09 | 15590.34 | 09-FEB-06:02 | 14171.62 | 14171.62 | 7.68 | 105.22 |
March | 0.864179E+09 | 0.785538E+09 | 19218.20 | 29-MAR-05:02 | 17469.34 | 17469.34 | 7.98 | 114.40 |
April | 0.112528E+10 | 0.102288E+10 | 19680.93 | 20-APR-05:03 | 17889.96 | 17889.96 | 7.74 | 115.49 |
May | 0.174385E+10 | 0.158516E+10 | 22058.78 | 02-MAY-05:02 | 20051.43 | 20051.43 | 7.82 | 120.83 |
June | 0.224879E+10 | 0.204415E+10 | 26763.57 | 08-JUN-05:02 | 24328.08 | 24328.08 | 7.80 | 130.40 |
July | 0.297622E+10 | 0.270539E+10 | 26332.52 | 27-JUL-05:02 | 23936.26 | 23936.26 | 7.26 | 129.56 |
August | 0.342780E+10 | 0.311587E+10 | 26134.30 | 30-AUG-05:02 | 23756.08 | 23756.08 | 7.74 | 129.17 |
September | 0.236405E+10 | 0.214892E+10 | 26717.15 | 28-SEP-05:02 | 24285.89 | 24285.89 | 7.85 | 130.29 |
October | 0.168272E+10 | 0.152959E+10 | 26763.57 | 18-OCT-05:02 | 24328.08 | 24328.08 | 7.84 | 130.40 |
November | 0.103527E+10 | 0.941059E+09 | 24211.32 | 10-NOV-06:02 | 22008.09 | 22008.09 | 8.00 | 125.35 |
December | 0.547315E+09 | 0.497510E+09 | 15562.07 | 11-DEC-06:03 | 14145.92 | 14145.92 | 7.74 | 105.14 |
Annual Sum or Average | 0.189015E+11 | 0.171815E+11 | ||||||
Minimum of Months | 0.410997E+09 | 0.373596E+09 | 10010.52 | 9099.56 | 9099.56 | 7.26 | 87.87 | |
Maximum of Months | 0.342780E+10 | 0.311587E+10 | 26763.57 | 24328.08 | 24328.08 | 8.03 | 130.40 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.309485E+11 | 0.281322E+11 | 18420.64 | 01-JAN-00:15 | 16744.36 | 16744.36 | 8.54 | 130.40 |
February | 0.291488E+11 | 0.264963E+11 | 18420.64 | 01-FEB-04:03 | 16744.36 | 16744.36 | 8.80 | 130.40 |
March | 0.379373E+11 | 0.344850E+11 | 18420.64 | 01-MAR-03:42 | 16744.36 | 16744.36 | 8.15 | 130.40 |
April | 0.428241E+11 | 0.389271E+11 | 18420.64 | 01-APR-00:42 | 16744.36 | 16744.36 | 7.63 | 130.40 |
May | 0.444962E+11 | 0.404470E+11 | 18420.64 | 01-MAY-00:03 | 16744.36 | 16744.36 | 7.05 | 130.40 |
June | 0.459208E+11 | 0.417420E+11 | 18420.64 | 01-JUN-00:13 | 16744.36 | 16744.36 | 8.25 | 130.40 |
July | 0.480187E+11 | 0.436490E+11 | 18420.64 | 01-JUL-00:03 | 16744.36 | 16744.36 | 9.30 | 130.40 |
August | 0.482871E+11 | 0.438930E+11 | 18420.64 | 01-AUG-00:03 | 16744.36 | 16744.36 | 9.39 | 130.40 |
September | 0.441182E+11 | 0.401034E+11 | 18420.64 | 01-SEP-00:03 | 16744.36 | 16744.36 | 8.47 | 130.40 |
October | 0.437919E+11 | 0.398069E+11 | 18420.64 | 01-OCT-00:03 | 16744.36 | 16744.36 | 7.39 | 130.40 |
November | 0.398752E+11 | 0.362465E+11 | 18420.64 | 01-NOV-00:15 | 16744.36 | 16744.36 | 6.96 | 130.40 |
December | 0.380699E+11 | 0.346056E+11 | 18420.64 | 01-DEC-01:12 | 16744.36 | 16744.36 | 7.72 | 130.40 |
Annual Sum or Average | 0.493437E+12 | 0.448534E+12 | ||||||
Minimum of Months | 0.291488E+11 | 0.264963E+11 | 18420.64 | 16744.36 | 16744.36 | 6.96 | 130.40 | |
Maximum of Months | 0.482871E+11 | 0.438930E+11 | 18420.64 | 16744.36 | 16744.36 | 9.39 | 130.40 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.183366E+10 | 0.166680E+10 | 684.61 | 01-JAN-00:05 | 622.31 | 622.31 | 21.04 | 2.89 |
February | 0.165621E+10 | 0.150550E+10 | 684.61 | 01-FEB-00:10 | 622.31 | 622.31 | 23.30 | 2.89 |
March | 0.183366E+10 | 0.166680E+10 | 684.61 | 01-MAR-00:10 | 622.31 | 622.31 | 32.06 | 2.89 |
April | 0.177451E+10 | 0.161303E+10 | 684.61 | 01-APR-00:05 | 622.31 | 622.31 | 35.07 | 2.89 |
May | 0.183366E+10 | 0.166680E+10 | 684.61 | 01-MAY-00:03 | 622.31 | 622.31 | 31.41 | 2.89 |
June | 0.177451E+10 | 0.161303E+10 | 684.61 | 01-JUN-00:03 | 622.31 | 622.31 | 40.46 | 2.89 |
July | 0.183366E+10 | 0.166680E+10 | 684.61 | 01-JUL-00:03 | 622.31 | 622.31 | 43.01 | 2.89 |
August | 0.183366E+10 | 0.166680E+10 | 684.61 | 01-AUG-00:03 | 622.31 | 622.31 | 47.81 | 2.89 |
September | 0.177451E+10 | 0.161303E+10 | 684.61 | 01-SEP-00:03 | 622.31 | 622.31 | 36.70 | 2.89 |
October | 0.183366E+10 | 0.166680E+10 | 684.61 | 01-OCT-00:03 | 622.31 | 622.31 | 36.95 | 2.89 |
November | 0.177451E+10 | 0.161303E+10 | 684.61 | 01-NOV-00:03 | 622.31 | 622.31 | 37.67 | 2.89 |
December | 0.183366E+10 | 0.166680E+10 | 684.61 | 01-DEC-00:05 | 622.31 | 622.31 | 32.85 | 2.89 |
Annual Sum or Average | 0.215899E+11 | 0.196252E+11 | ||||||
Minimum of Months | 0.165621E+10 | 0.150550E+10 | 684.61 | 622.31 | 622.31 | 21.04 | 2.89 | |
Maximum of Months | 0.183366E+10 | 0.166680E+10 | 684.61 | 622.31 | 622.31 | 47.81 | 2.89 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:05 | 1.79 | 1.79 | 56.29 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:02 | 1.79 | 1.79 | 56.48 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:03 | 1.79 | 1.79 | 57.35 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:02 | 1.79 | 1.79 | 56.64 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:02 | 1.79 | 1.79 | 58.07 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:02 | 1.79 | 1.79 | 56.91 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:02 | 1.79 | 1.79 | 58.09 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:03 | 1.79 | 1.79 | 57.08 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 57.38 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 56.69 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:02 | 1.79 | 1.79 | 57.60 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:02 | 1.79 | 1.79 | 57.22 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 56.29 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 58.09 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.386691E+11 | 0.351503E+11 | 45140.56 | 30-JAN-06:03 | 41032.76 | 41032.76 | 23.98 | 151.57 |
February | 0.377721E+11 | 0.343348E+11 | 45285.12 | 07-FEB-15:50 | 41164.17 | 41164.17 | 27.94 | 151.57 |
March | 0.499115E+11 | 0.453695E+11 | 45266.81 | 28-MAR-16:00 | 41147.53 | 41147.53 | 27.46 | 151.57 |
April | 0.590950E+11 | 0.537174E+11 | 45318.19 | 30-APR-14:53 | 41194.24 | 41194.24 | 29.09 | 151.57 |
May | 0.711232E+11 | 0.646510E+11 | 45318.19 | 08-MAY-13:50 | 41194.24 | 41194.24 | 29.17 | 151.57 |
June | 0.819437E+11 | 0.744868E+11 | 45318.19 | 01-JUN-19:50 | 41194.24 | 41194.24 | 29.59 | 151.57 |
July | 0.916331E+11 | 0.832945E+11 | 45318.19 | 01-JUL-02:20 | 41194.24 | 41194.24 | 30.79 | 151.57 |
August | 0.955539E+11 | 0.868585E+11 | 45318.19 | 01-AUG-00:55 | 41194.24 | 41194.24 | 30.84 | 151.57 |
September | 0.813529E+11 | 0.739498E+11 | 45318.19 | 01-SEP-05:03 | 41194.24 | 41194.24 | 29.36 | 151.57 |
October | 0.721226E+11 | 0.655594E+11 | 45318.19 | 01-OCT-01:00 | 41194.24 | 41194.24 | 30.86 | 151.57 |
November | 0.564282E+11 | 0.512932E+11 | 45318.19 | 01-NOV-09:40 | 41194.24 | 41194.24 | 29.01 | 151.57 |
December | 0.486207E+11 | 0.441962E+11 | 45294.62 | 05-DEC-15:40 | 41172.81 | 41172.81 | 28.19 | 151.57 |
Annual Sum or Average | 0.784226E+12 | 0.712861E+12 | ||||||
Minimum of Months | 0.377721E+11 | 0.343348E+11 | 45140.56 | 41032.76 | 41032.76 | 23.98 | 151.57 | |
Maximum of Months | 0.955539E+11 | 0.868585E+11 | 45318.19 | 41194.24 | 41194.24 | 30.86 | 151.57 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 79.40 | 79.40 | 3.16 | 636.64 | 20-JAN-07:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 59.58 | 59.58 | 0.13 | 125.93 | 13-FEB-06:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 59.24 | 59.24 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 01-APR-00:05 | 59.24 | 59.24 | 0.00 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 59.24 | 59.24 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 59.24 | 59.24 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 59.24 | 59.24 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 59.24 | 59.24 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 59.24 | 59.24 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 59.24 | 59.24 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 59.24 | 59.24 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 59.24 | 59.24 | 0.00 | 8.63 | 18-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.28 | ||||||
Minimum of Months | 0.00 | 0.00 | 59.24 | 59.24 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 79.40 | 79.40 | 3.16 | 636.64 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 522977.40 | 1921967.21 | 30-JAN-06:03 | 11.22 | 7.70 | 23.90 | 93930.67 | 15-JAN-23:05 |
February | 598586.15 | 2250471.56 | 09-FEB-06:02 | 11.39 | 7.27 | 1.56 | 7223.96 | 12-FEB-22:15 |
March | 715952.90 | 2747795.35 | 29-MAR-05:04 | 12.68 | 7.65 | 24.11 | 171564.06 | 12-MAR-07:53 |
April | 870270.64 | 2559895.36 | 20-APR-05:03 | 12.09 | 7.41 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1136786.15 | 2896108.53 | 31-MAY-05:02 | 12.00 | 6.70 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1354623.81 | 3441257.52 | 08-JUN-05:02 | 13.14 | 7.44 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1519215.75 | 3413388.83 | 20-JUL-05:03 | 12.95 | 7.25 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1606441.67 | 3961114.41 | 03-AUG-05:03 | 13.96 | 8.25 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1341740.30 | 3560123.61 | 28-SEP-05:02 | 13.22 | 7.52 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 1078081.91 | 3364938.27 | 24-OCT-05:02 | 13.14 | 7.44 | 4.24 | 36918.36 | 20-OCT-23:53 |
November | 838297.19 | 3096781.40 | 10-NOV-06:04 | 13.10 | 7.43 | 8.72 | 89615.08 | 23-NOV-06:33 |
December | 630686.84 | 2316821.14 | 11-DEC-06:03 | 11.66 | 7.42 | 5.31 | 63652.71 | 17-DEC-07:43 |
Annual Sum or Average | 1020336.42 | 5.73 | ||||||
Minimum of Months | 522977.40 | 1921967.21 | 11.22 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1606441.67 | 3961114.41 | 13.96 | 8.25 | 24.11 | 171564.06 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 327872.19 | 3279887.22 | 30-JAN-06:03 | 15.62 | 7.76 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 395513.35 | 4142254.36 | 09-FEB-06:02 | 16.11 | 7.30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 506606.90 | 4341209.49 | 29-MAR-05:02 | 15.77 | 7.67 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 650005.82 | 4321704.70 | 19-APR-05:02 | 15.79 | 7.81 | 0.00 | 0.00 | 01-APR-00:05 |
May | 928594.09 | 4627855.50 | 02-MAY-05:02 | 15.85 | 7.45 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1199129.69 | 5180382.84 | 08-JUN-05:02 | 16.20 | 7.66 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1384170.11 | 5209800.24 | 27-JUL-05:02 | 16.31 | 6.84 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1489926.97 | 5371230.84 | 30-AUG-05:02 | 16.64 | 7.74 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1212107.91 | 5227400.82 | 28-SEP-05:02 | 16.29 | 7.73 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 905819.10 | 5109746.84 | 18-OCT-05:02 | 16.07 | 7.65 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 649995.08 | 4704700.26 | 10-NOV-06:02 | 15.67 | 7.79 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 417475.94 | 3854134.77 | 11-DEC-06:03 | 15.46 | 7.48 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 841605.35 | 0.00 | ||||||
Minimum of Months | 327872.19 | 3279887.22 | 15.46 | 6.84 | 0.00 | 0.00 | ||
Maximum of Months | 1489926.97 | 5371230.84 | 16.64 | 7.81 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 49200.83 | 138033.08 | 23-JAN-14:00 | 31.95 | 28.52 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 93355.98 | 221687.08 | 06-FEB-15:00 | 40.05 | 33.51 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 148828.33 | 315656.76 | 27-MAR-11:00 | 48.99 | 39.49 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 219081.29 | 387294.57 | 28-APR-12:00 | 55.71 | 43.89 | 0.00 | 0.00 | 01-APR-00:05 |
May | 178189.97 | 294290.94 | 31-MAY-19:00 | 46.97 | 42.76 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 232434.99 | 344403.99 | 12-JUN-12:00 | 51.70 | 44.19 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 291927.98 | 410395.74 | 21-JUL-12:00 | 57.86 | 47.64 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 324107.57 | 435194.57 | 16-AUG-12:00 | 60.16 | 47.97 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 194159.87 | 288135.93 | 04-SEP-14:54 | 46.38 | 41.73 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 192436.44 | 283408.08 | 04-OCT-12:00 | 45.93 | 39.07 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 177192.61 | 270474.44 | 01-NOV-14:00 | 44.71 | 34.58 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 157199.97 | 255707.39 | 10-DEC-12:00 | 43.30 | 31.79 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 188763.43 | 0.00 | ||||||
Minimum of Months | 49200.83 | 138033.08 | 31.95 | 28.52 | 0.00 | 0.00 | ||
Maximum of Months | 324107.57 | 435194.57 | 60.16 | 47.97 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.51 | 57.51 | 11557.70 | 37781.52 | 13-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.07 | 57.07 | 11332.85 | 37387.74 | 01-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.75 | 57.75 | 11206.51 | 35669.03 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:05 | 56.96 | 56.96 | 9664.01 | 32369.09 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 58.46 | 58.46 | 9010.48 | 29237.18 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 57.12 | 57.12 | 8495.42 | 26295.69 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 58.30 | 58.30 | 7733.71 | 24894.24 | 31-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.29 | 57.29 | 8644.93 | 26762.11 | 31-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 57.97 | 57.97 | 8916.26 | 29644.07 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 57.18 | 57.18 | 9824.35 | 33227.82 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 58.06 | 58.06 | 10850.28 | 36032.85 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 57.57 | 57.57 | 11125.44 | 37583.20 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 9855.60 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.96 | 56.96 | 7733.71 | 24894.24 | ||
Maximum of Months | 0.00 | 0.00 | 58.46 | 58.46 | 11557.70 | 37781.52 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 323691.51 | 1823702.79 | 30-JAN-06:03 | 23.98 | 22.46 | 565.12 | 121333.40 | 01-JAN-05:20 |
February | 411627.97 | 4332041.56 | 07-FEB-15:50 | 27.94 | 24.85 | 273.94 | 68610.68 | 13-FEB-04:35 |
March | 552773.37 | 4026835.66 | 28-MAR-16:00 | 27.46 | 24.39 | 270.46 | 53426.78 | 22-MAR-02:50 |
April | 919811.42 | 5785620.43 | 30-APR-15:02 | 30.23 | 27.49 | 89.72 | 27550.00 | 06-APR-00:03 |
May | 1987543.55 | 7349840.63 | 31-MAY-16:00 | 32.70 | 28.58 | 0.62 | 5578.17 | 07-MAY-06:10 |
June | 3462467.53 | 7695053.81 | 09-JUN-05:05 | 33.25 | 28.76 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 4409562.78 | 8170958.01 | 19-JUL-15:00 | 34.00 | 29.00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 4868085.48 | 8218923.51 | 10-AUG-16:00 | 34.07 | 29.02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 3756745.96 | 7915951.62 | 07-SEP-14:10 | 33.59 | 28.87 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 2173417.86 | 7135443.34 | 06-OCT-16:00 | 32.36 | 28.47 | 0.53 | 1973.09 | 20-OCT-03:00 |
November | 1032196.95 | 6705388.28 | 01-NOV-14:00 | 31.68 | 27.99 | 39.35 | 36843.37 | 26-NOV-02:15 |
December | 459553.17 | 4490368.56 | 05-DEC-15:40 | 28.19 | 24.95 | 422.92 | 76567.25 | 31-DEC-23:50 |
Annual Sum or Average | 2040207.39 | 138.61 | ||||||
Minimum of Months | 323691.51 | 1823702.79 | 23.98 | 22.46 | 0.00 | 0.00 | ||
Maximum of Months | 4868085.48 | 8218923.51 | 34.07 | 29.02 | 565.12 | 121333.40 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 92275.86 | 0.00 | 0.715098E+11 | 0.606727E+10 | 0.00 | 0.00 |
February | 37294.73 | 0.00 | 0.823144E+11 | 0.659627E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.120093E+12 | 0.926571E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.156554E+12 | 0.104926E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.198856E+12 | 0.109026E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.259662E+12 | 0.124709E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.313375E+12 | 0.144791E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.343167E+12 | 0.175019E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.258940E+12 | 0.113614E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.212697E+12 | 0.114046E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.153081E+12 | 0.102132E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.109326E+12 | 0.860216E+10 | 0.00 | 0.00 |
Annual Sum or Average | 129570.59 | 0.00 | 0.227958E+13 | 0.129358E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.715098E+11 | 0.606727E+10 | 0.00 | 0.00 |
Maximum of Months | 92275.86 | 0.00 | 0.343167E+12 | 0.175019E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.530990E+12 | 0.412633E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.601720E+12 | 0.423989E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.876185E+12 | 0.599549E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.113308E+13 | 0.667383E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.178619E+13 | 0.916324E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.230525E+13 | 0.960711E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.280418E+13 | 0.100429E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.303128E+13 | 0.113919E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.235278E+13 | 0.921420E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.174057E+13 | 0.845394E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.114710E+13 | 0.669223E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.696966E+12 | 0.463221E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.190063E+14 | 0.902334E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.530990E+12 | 0.412633E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.303128E+13 | 0.113919E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 48898172.26 | 0.00 | 0.465427E+11 | 0.324311E+10 | 0.00 | 0.00 |
February | 981120.98 | 0.00 | 0.582734E+11 | 0.361010E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.902165E+11 | 0.546995E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.123160E+12 | 0.661719E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.202818E+12 | 0.100516E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.260755E+12 | 0.110005E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.315049E+12 | 0.119520E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.338295E+12 | 0.132989E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.261473E+12 | 0.100792E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.188397E+12 | 0.848096E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.116495E+12 | 0.593473E+10 | 0.00 | 0.00 |
December | 16372.89 | 0.00 | 0.653964E+11 | 0.380464E+10 | 0.00 | 0.00 |
Annual Sum or Average | 49895666.13 | 0.00 | 0.206687E+13 | 0.935428E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.465427E+11 | 0.324311E+10 | 0.00 | 0.00 |
Maximum of Months | 48898172.26 | 0.00 | 0.338295E+12 | 0.132989E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.651652E+11 | 0.158235E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.623564E+11 | 0.139413E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.760848E+11 | 0.154484E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.794076E+11 | 0.141727E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.104581E+12 | 0.152783E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.123841E+12 | 0.151233E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.148819E+12 | 0.154427E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.170581E+12 | 0.166161E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.136720E+12 | 0.155519E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.120886E+12 | 0.161689E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.982572E+11 | 0.157115E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.761037E+11 | 0.158157E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.126280E+13 | 0.185094E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.623564E+11 | 0.139413E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.170581E+12 | 0.166161E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.690209E+10 | 0.266614E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.121964E+11 | 0.347634E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.199507E+11 | 0.513058E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.260424E+11 | 0.649140E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.909779E+10 | 0.351181E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.159229E+11 | 0.503447E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.237755E+11 | 0.698813E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.294599E+11 | 0.817903E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.969714E+10 | 0.361050E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.156254E+11 | 0.478542E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.201202E+11 | 0.529699E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.257196E+11 | 0.588711E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.214510E+12 | 0.610579E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.690209E+10 | 0.266614E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.294599E+11 | 0.817903E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.577491E+11 | 0.240194E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.110866E+12 | 0.322374E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.188004E+12 | 0.485422E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.248630E+12 | 0.619167E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.856042E+11 | 0.332013E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.151330E+12 | 0.478511E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.225956E+12 | 0.664138E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.280791E+12 | 0.779253E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.908695E+11 | 0.340217E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.148285E+12 | 0.454413E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.190678E+12 | 0.502765E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.241315E+12 | 0.555237E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.202008E+13 | 0.577370E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.577491E+11 | 0.240194E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.280791E+12 | 0.779253E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.494002E+10 | 0.227674E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.106718E+11 | 0.317949E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.186501E+11 | 0.486649E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.249887E+11 | 0.626271E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.884646E+10 | 0.340768E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.154625E+11 | 0.488899E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.230530E+11 | 0.678598E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.287963E+11 | 0.801447E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.937966E+10 | 0.349166E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.149955E+11 | 0.460992E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.190045E+11 | 0.505436E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.236804E+11 | 0.552635E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.202469E+12 | 0.583648E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.494002E+10 | 0.227674E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.287963E+11 | 0.801447E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.606727E+10 | 0.715098E+11 | 92275.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.659627E+10 | 0.823144E+11 | 37294.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.926571E+10 | 0.120093E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104926E+11 | 0.156554E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109026E+11 | 0.198856E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124709E+11 | 0.259662E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144791E+11 | 0.313375E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.175019E+11 | 0.343167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113614E+11 | 0.258940E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114046E+11 | 0.212697E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102132E+11 | 0.153081E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.860216E+10 | 0.109326E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129358E+12 | 0.227958E+13 | 129570.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.606727E+10 | 0.715098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.175019E+11 | 0.343167E+12 | 92275.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.412633E+11 | 0.530990E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.423989E+11 | 0.601720E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.599549E+11 | 0.876185E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.667383E+11 | 0.113308E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.916324E+11 | 0.178619E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.960711E+11 | 0.230525E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100429E+12 | 0.280418E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113919E+12 | 0.303128E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.921420E+11 | 0.235278E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.845394E+11 | 0.174057E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.669223E+11 | 0.114710E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.463221E+11 | 0.696966E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.902334E+12 | 0.190063E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.412633E+11 | 0.530990E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113919E+12 | 0.303128E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.324311E+10 | 0.465427E+11 | 48898172.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361010E+10 | 0.582734E+11 | 981120.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.546995E+10 | 0.902165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.661719E+10 | 0.123160E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100516E+11 | 0.202818E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110005E+11 | 0.260755E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119520E+11 | 0.315049E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132989E+11 | 0.338295E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100792E+11 | 0.261473E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.848096E+10 | 0.188397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.593473E+10 | 0.116495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.380464E+10 | 0.653964E+11 | 16372.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.935428E+11 | 0.206687E+13 | 49895666.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.324311E+10 | 0.465427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132989E+11 | 0.338295E+12 | 48898172.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158235E+11 | 0.651652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139413E+11 | 0.623564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154484E+11 | 0.760848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141727E+11 | 0.794076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152783E+11 | 0.104581E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151233E+11 | 0.123841E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154427E+11 | 0.148819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166161E+11 | 0.170581E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155519E+11 | 0.136720E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161689E+11 | 0.120886E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157115E+11 | 0.982572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158157E+11 | 0.761037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185094E+12 | 0.126280E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139413E+11 | 0.623564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166161E+11 | 0.170581E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140279E+10 | 0.563873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126703E+10 | 0.998705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140279E+10 | 0.162229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135754E+10 | 0.209086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140279E+10 | 0.698876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135754E+10 | 0.122459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140279E+10 | 0.181902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140279E+10 | 0.226836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135754E+10 | 0.744417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140279E+10 | 0.122428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135754E+10 | 0.161808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140279E+10 | 0.212353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165167E+11 | 0.169969E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126703E+10 | 0.563873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140279E+10 | 0.226836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.133531E+11 | 0.470828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120609E+11 | 0.906893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133531E+11 | 0.152815E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129224E+11 | 0.199635E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133531E+11 | 0.657560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129224E+11 | 0.116401E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133531E+11 | 0.172895E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133531E+11 | 0.216219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129224E+11 | 0.697702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133531E+11 | 0.116197E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129224E+11 | 0.153323E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133531E+11 | 0.199144E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157222E+12 | 0.159993E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120609E+11 | 0.470828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133531E+11 | 0.216219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.134824E+10 | 0.401152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121777E+10 | 0.871008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134824E+10 | 0.151319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130475E+10 | 0.200307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134824E+10 | 0.678702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130475E+10 | 0.118782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134824E+10 | 0.176153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134824E+10 | 0.221301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130475E+10 | 0.719276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134824E+10 | 0.117339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130475E+10 | 0.152549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134824E+10 | 0.195023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158745E+11 | 0.159979E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121777E+10 | 0.401152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134824E+10 | 0.221301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.606727E+10 | 92275.86 | 0.715098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.659627E+10 | 37294.73 | 0.823144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.926571E+10 | 0.00 | 0.120093E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104926E+11 | 0.00 | 0.156554E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109026E+11 | 0.00 | 0.198856E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124709E+11 | 0.00 | 0.259662E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144791E+11 | 0.00 | 0.313375E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.175019E+11 | 0.00 | 0.343167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113614E+11 | 0.00 | 0.258940E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114046E+11 | 0.00 | 0.212697E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102132E+11 | 0.00 | 0.153081E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.860216E+10 | 0.00 | 0.109326E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129358E+12 | 129570.59 | 0.227958E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.606727E+10 | 0.00 | 0.715098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.175019E+11 | 92275.86 | 0.343167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.412633E+11 | 0.00 | 0.530990E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.423989E+11 | 0.00 | 0.601720E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.599549E+11 | 0.00 | 0.876185E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.667383E+11 | 0.00 | 0.113308E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.916324E+11 | 0.00 | 0.178619E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.960711E+11 | 0.00 | 0.230525E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100429E+12 | 0.00 | 0.280418E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.113919E+12 | 0.00 | 0.303128E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.921420E+11 | 0.00 | 0.235278E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.845394E+11 | 0.00 | 0.174057E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.669223E+11 | 0.00 | 0.114710E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.463221E+11 | 0.00 | 0.696966E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.902334E+12 | 0.00 | 0.190063E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.412633E+11 | 0.00 | 0.530990E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113919E+12 | 0.00 | 0.303128E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.324311E+10 | 48898172.26 | 0.465427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361010E+10 | 981120.98 | 0.582734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.546995E+10 | 0.00 | 0.902165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.661719E+10 | 0.00 | 0.123160E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100516E+11 | 0.00 | 0.202818E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110005E+11 | 0.00 | 0.260755E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119520E+11 | 0.00 | 0.315049E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132989E+11 | 0.00 | 0.338295E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100792E+11 | 0.00 | 0.261473E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.848096E+10 | 0.00 | 0.188397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.593473E+10 | 0.00 | 0.116495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.380464E+10 | 16372.89 | 0.653964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.935428E+11 | 49895666.13 | 0.206687E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.324311E+10 | 0.00 | 0.465427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132989E+11 | 48898172.26 | 0.338295E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.158235E+11 | 0.00 | 0.651652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139413E+11 | 0.00 | 0.623564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154484E+11 | 0.00 | 0.760848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141727E+11 | 0.00 | 0.794076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152783E+11 | 0.00 | 0.104581E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151233E+11 | 0.00 | 0.123841E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154427E+11 | 0.00 | 0.148819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166161E+11 | 0.00 | 0.170581E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155519E+11 | 0.00 | 0.136720E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161689E+11 | 0.00 | 0.120886E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157115E+11 | 0.00 | 0.982572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158157E+11 | 0.00 | 0.761037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185094E+12 | 0.00 | 0.126280E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139413E+11 | 0.00 | 0.623564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166161E+11 | 0.00 | 0.170581E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140279E+10 | 0.00 | 0.690209E+10 | 0.00 | 0.126335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126703E+10 | 0.00 | 0.121964E+11 | 0.00 | 0.220931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140279E+10 | 0.00 | 0.199507E+11 | 0.00 | 0.372779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135754E+10 | 0.00 | 0.260424E+11 | 0.00 | 0.513386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140279E+10 | 0.00 | 0.909779E+10 | 0.00 | 0.210903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135754E+10 | 0.00 | 0.159229E+11 | 0.00 | 0.367694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140279E+10 | 0.00 | 0.237755E+11 | 0.00 | 0.558535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140279E+10 | 0.00 | 0.294599E+11 | 0.00 | 0.677624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135754E+10 | 0.00 | 0.969714E+10 | 0.00 | 0.225297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140279E+10 | 0.00 | 0.156254E+11 | 0.00 | 0.338263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135754E+10 | 0.00 | 0.201202E+11 | 0.00 | 0.393946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140279E+10 | 0.00 | 0.257196E+11 | 0.00 | 0.448432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165167E+11 | 0.00 | 0.214510E+12 | 0.00 | 0.445412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126703E+10 | 0.00 | 0.690209E+10 | 0.00 | 0.126335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140279E+10 | 0.00 | 0.294599E+11 | 0.00 | 0.677624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.133531E+11 | 0.00 | 0.577491E+11 | 0.00 | 0.106663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120609E+11 | 0.00 | 0.110866E+12 | 0.00 | 0.201766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133531E+11 | 0.00 | 0.188004E+12 | 0.00 | 0.351891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129224E+11 | 0.00 | 0.248630E+12 | 0.00 | 0.489943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133531E+11 | 0.00 | 0.856042E+11 | 0.00 | 0.198482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129224E+11 | 0.00 | 0.151330E+12 | 0.00 | 0.349287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133531E+11 | 0.00 | 0.225956E+12 | 0.00 | 0.530607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133531E+11 | 0.00 | 0.280791E+12 | 0.00 | 0.645722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129224E+11 | 0.00 | 0.908695E+11 | 0.00 | 0.210993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133531E+11 | 0.00 | 0.148285E+12 | 0.00 | 0.320882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129224E+11 | 0.00 | 0.190678E+12 | 0.00 | 0.373541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133531E+11 | 0.00 | 0.241315E+12 | 0.00 | 0.421706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157222E+12 | 0.00 | 0.202008E+13 | 0.00 | 0.420148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120609E+11 | 0.00 | 0.577491E+11 | 0.00 | 0.106663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133531E+11 | 0.00 | 0.280791E+12 | 0.00 | 0.645722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.134824E+10 | 0.00 | 0.494002E+10 | 0.00 | 0.928499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121777E+10 | 0.00 | 0.106718E+11 | 0.00 | 0.196173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134824E+10 | 0.00 | 0.186501E+11 | 0.00 | 0.351825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130475E+10 | 0.00 | 0.249887E+11 | 0.00 | 0.495796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134824E+10 | 0.00 | 0.884646E+10 | 0.00 | 0.205944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130475E+10 | 0.00 | 0.154625E+11 | 0.00 | 0.358424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134824E+10 | 0.00 | 0.230530E+11 | 0.00 | 0.543774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134824E+10 | 0.00 | 0.287963E+11 | 0.00 | 0.666623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130475E+10 | 0.00 | 0.937966E+10 | 0.00 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134824E+10 | 0.00 | 0.149955E+11 | 0.00 | 0.326167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130475E+10 | 0.00 | 0.190045E+11 | 0.00 | 0.374961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134824E+10 | 0.00 | 0.236804E+11 | 0.00 | 0.417810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158745E+11 | 0.00 | 0.202469E+12 | 0.00 | 0.424904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121777E+10 | 0.00 | 0.494002E+10 | 0.00 | 0.928499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134824E+10 | 0.00 | 0.287963E+11 | 0.00 | 0.666623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.152371E+10 | 0.486840E+09 | 0.00 | 0.118672E+09 | 17308870.48 | 0.00 | 0.155047E+11 | 0.00 | 0.42 |
February | 0.113799E+10 | 0.127522E+10 | 0.00 | 93128455.27 | 43952810.05 | 0.00 | 0.996318E+10 | 0.00 | 0.41 |
March | 0.519306E+09 | 0.354616E+10 | 0.00 | 82291775.45 | 60299080.36 | 0.00 | 0.762609E+10 | 0.00 | 0.41 |
April | 0.267348E+09 | 0.955136E+10 | 0.00 | 42496482.04 | 0.240172E+09 | 0.00 | 0.310156E+10 | 0.00 | 0.39 |
May | 31205741.49 | 0.263065E+11 | 0.00 | 14912856.83 | 0.832142E+09 | 0.00 | 0.467042E+09 | 0.00 | 0.41 |
June | 14436983.14 | 0.450655E+11 | 0.00 | 3812066.67 | 0.118062E+10 | 0.00 | 0.131294E+09 | 0.00 | 0.42 |
July | 7640402.95 | 0.661055E+11 | 0.00 | 4068716.31 | 0.179799E+10 | 0.00 | 0.103888E+09 | 0.00 | 0.42 |
August | 0.00 | 0.772283E+11 | 0.00 | 44010.39 | 0.152630E+10 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 3632386.23 | 0.541151E+11 | 0.00 | 2424570.85 | 0.156397E+10 | 0.00 | 55007124.53 | 0.00 | 0.43 |
October | 33938476.15 | 0.331885E+11 | 0.00 | 10660266.08 | 0.966618E+09 | 0.00 | 0.469455E+09 | 0.00 | 0.43 |
November | 0.193041E+09 | 0.140059E+11 | 0.00 | 46576450.42 | 0.224260E+09 | 0.00 | 0.176963E+10 | 0.00 | 0.43 |
December | 0.675315E+09 | 0.270943E+10 | 0.00 | 0.106581E+09 | 54942267.60 | 0.00 | 0.995358E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.440756E+10 | 0.333584E+12 | 0.00 | 0.525668E+09 | 0.850857E+10 | 0.00 | 0.491455E+11 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.486840E+09 | 0.00 | 44010.39 | 17308870.48 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.152371E+10 | 0.772283E+11 | 0.00 | 0.118672E+09 | 0.179799E+10 | 0.00 | 0.155047E+11 | 0.00 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.219795E+10 | 0.314809E+09 | 0.00 | 76245534.57 | 0.170972E+09 | 0.00 | 0.125042E+11 | 0.00 | 0.35 |
February | 0.187803E+10 | 0.124408E+10 | 0.00 | 60695737.48 | 0.447554E+09 | 0.00 | 0.770490E+10 | 0.00 | 0.36 |
March | 0.283856E+10 | 0.329898E+10 | 0.00 | 53084600.92 | 0.103335E+10 | 0.00 | 0.580567E+10 | 0.00 | 0.42 |
April | 0.167682E+10 | 0.795169E+10 | 0.00 | 20011587.90 | 0.622912E+10 | 0.00 | 0.171111E+10 | 0.00 | 0.46 |
May | 0.203527E+09 | 0.187065E+11 | 0.00 | 6170797.93 | 0.141592E+11 | 0.00 | 0.297474E+09 | 0.00 | 0.42 |
June | 16438172.40 | 0.315980E+11 | 0.00 | 733729.95 | 0.281582E+11 | 0.00 | 16876636.62 | 0.00 | 0.45 |
July | 71623316.97 | 0.431920E+11 | 0.00 | 764641.12 | 0.382449E+11 | 0.00 | 16937486.04 | 0.00 | 0.45 |
August | 0.00 | 0.516755E+11 | 0.00 | 0.00 | 0.350621E+11 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 199721.21 | 0.358286E+11 | 0.00 | 720457.27 | 0.293907E+11 | 0.00 | 11655046.48 | 0.00 | 0.43 |
October | 0.276851E+09 | 0.219724E+11 | 0.00 | 4436078.37 | 0.181538E+11 | 0.00 | 0.252699E+09 | 0.00 | 0.43 |
November | 0.108627E+10 | 0.106257E+11 | 0.00 | 16612999.42 | 0.366351E+10 | 0.00 | 0.918059E+09 | 0.00 | 0.43 |
December | 0.343523E+10 | 0.223174E+10 | 0.00 | 63625592.56 | 0.120996E+10 | 0.00 | 0.685930E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.136815E+11 | 0.228640E+12 | 0.00 | 0.303102E+09 | 0.175923E+12 | 0.00 | 0.360988E+11 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.314809E+09 | 0.00 | 0.00 | 0.170972E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.343523E+10 | 0.516755E+11 | 0.00 | 76245534.57 | 0.382449E+11 | 0.00 | 0.125042E+11 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163083E+11 | 0.229660E+10 | 0.00 | 0.505165E+09 | 0.220625E+10 | 0.00 | 0.113105E+12 | 0.00 | 0.33 |
February | 0.107431E+11 | 0.111088E+11 | 0.00 | 0.416507E+09 | 0.437513E+10 | 0.00 | 0.701688E+11 | 0.00 | 0.33 |
March | 0.111919E+11 | 0.318688E+11 | 0.00 | 0.411814E+09 | 0.553748E+10 | 0.00 | 0.557002E+11 | 0.00 | 0.34 |
April | 0.592511E+10 | 0.768328E+11 | 0.00 | 0.183090E+09 | 0.356948E+11 | 0.00 | 0.184544E+11 | 0.00 | 0.35 |
May | 0.197913E+10 | 0.182673E+12 | 0.00 | 46105090.60 | 0.116142E+12 | 0.00 | 0.290427E+10 | 0.00 | 0.39 |
June | 0.162499E+09 | 0.303416E+12 | 0.00 | 4615564.20 | 0.230338E+12 | 0.00 | 0.219563E+09 | 0.00 | 0.41 |
July | 0.643090E+09 | 0.401971E+12 | 0.00 | 1116142.87 | 0.353283E+12 | 0.00 | 0.110862E+09 | 0.00 | 0.43 |
August | 0.00 | 0.466434E+12 | 0.00 | 0.00 | 0.341036E+12 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 3500271.73 | 0.344719E+12 | 0.00 | 5441097.82 | 0.242079E+12 | 0.00 | 0.130133E+09 | 0.00 | 0.39 |
October | 0.211165E+10 | 0.211386E+12 | 0.00 | 35016014.74 | 0.116615E+12 | 0.00 | 0.275279E+10 | 0.00 | 0.36 |
November | 0.263229E+10 | 0.101940E+12 | 0.00 | 0.148988E+09 | 0.187590E+11 | 0.00 | 0.896374E+10 | 0.00 | 0.33 |
December | 0.106074E+11 | 0.191014E+11 | 0.00 | 0.432418E+09 | 0.813282E+10 | 0.00 | 0.649790E+11 | 0.00 | 0.33 |
Annual Sum or Average | 0.623078E+11 | 0.215375E+13 | 0.00 | 0.219028E+10 | 0.147420E+13 | 0.00 | 0.337489E+12 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.229660E+10 | 0.00 | 0.00 | 0.220625E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.163083E+11 | 0.466434E+12 | 0.00 | 0.505165E+09 | 0.353283E+12 | 0.00 | 0.113105E+12 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.470636E+10 | 0.185027E+09 | 0.00 | 29130595.14 | 0.180483E+09 | 0.00 | 0.613347E+10 | 0.00 | 0.30 |
February | 0.266739E+10 | 0.959269E+09 | 0.00 | 28988743.11 | 0.449149E+09 | 0.00 | 0.433701E+10 | 0.00 | 0.31 |
March | 0.182556E+10 | 0.272458E+10 | 0.00 | 32809675.35 | 0.512667E+09 | 0.00 | 0.411306E+10 | 0.00 | 0.33 |
April | 0.721795E+09 | 0.695971E+10 | 0.00 | 15606059.85 | 0.333475E+10 | 0.00 | 0.146757E+10 | 0.00 | 0.35 |
May | 0.177950E+09 | 0.173128E+11 | 0.00 | 4320307.32 | 0.116690E+11 | 0.00 | 0.255404E+09 | 0.00 | 0.40 |
June | 12368381.40 | 0.293497E+11 | 0.00 | 536710.00 | 0.234006E+11 | 0.00 | 22050710.87 | 0.00 | 0.42 |
July | 74628331.49 | 0.398159E+11 | 0.00 | 439096.08 | 0.343879E+11 | 0.00 | 11201153.35 | 0.00 | 0.43 |
August | 0.00 | 0.461929E+11 | 0.00 | 0.00 | 0.338386E+11 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 866763.11 | 0.336215E+11 | 0.00 | 353206.21 | 0.252249E+11 | 0.00 | 5777014.12 | 0.00 | 0.41 |
October | 0.207388E+09 | 0.202952E+11 | 0.00 | 3093641.73 | 0.119825E+11 | 0.00 | 0.239791E+09 | 0.00 | 0.36 |
November | 0.261331E+09 | 0.964052E+10 | 0.00 | 10655899.05 | 0.174669E+10 | 0.00 | 0.668969E+09 | 0.00 | 0.32 |
December | 0.250870E+10 | 0.161735E+10 | 0.00 | 28315964.37 | 0.871264E+09 | 0.00 | 0.388677E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.131643E+11 | 0.208675E+12 | 0.00 | 0.154250E+09 | 0.147599E+12 | 0.00 | 0.211411E+11 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.185027E+09 | 0.00 | 0.00 | 0.180483E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.470636E+10 | 0.461929E+11 | 0.00 | 32809675.35 | 0.343879E+11 | 0.00 | 0.613347E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.606103E+09 | 42846944.45 | 0.00 | 6074574.31 | 21539165.55 | 0.00 | 0.956292E+09 | 0.00 | 0.31 |
February | 0.421308E+09 | 0.186530E+09 | 0.00 | 5749115.42 | 56347692.76 | 0.00 | 0.639296E+09 | 0.00 | 0.35 |
March | 0.390792E+09 | 0.573302E+09 | 0.00 | 6173464.95 | 0.119161E+09 | 0.00 | 0.640553E+09 | 0.00 | 0.45 |
April | 0.208821E+09 | 0.163420E+10 | 0.00 | 2758845.34 | 0.676181E+09 | 0.00 | 0.221696E+09 | 0.00 | 0.56 |
May | 21864968.87 | 0.491165E+10 | 0.00 | 1361643.36 | 0.128245E+10 | 0.00 | 57865449.24 | 0.00 | 0.63 |
June | 1886136.00 | 0.908369E+10 | 0.00 | 197449.76 | 0.244748E+10 | 0.00 | 3799374.61 | 0.00 | 0.70 |
July | 6928756.28 | 0.134196E+11 | 0.00 | 246798.74 | 0.276239E+10 | 0.00 | 6155863.21 | 0.00 | 0.71 |
August | 0.00 | 0.144074E+11 | 0.00 | 0.00 | 0.282016E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
September | 13825.98 | 0.926423E+10 | 0.00 | 122736.79 | 0.265126E+10 | 0.00 | 1888723.27 | 0.00 | 0.62 |
October | 34743910.85 | 0.453792E+10 | 0.00 | 699672.16 | 0.191753E+10 | 0.00 | 37300381.62 | 0.00 | 0.55 |
November | 0.144364E+09 | 0.176433E+10 | 0.00 | 1878140.89 | 0.415751E+09 | 0.00 | 97682207.31 | 0.00 | 0.48 |
December | 0.499655E+09 | 0.313067E+09 | 0.00 | 6295764.03 | 0.152256E+09 | 0.00 | 0.655414E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.233648E+10 | 0.601387E+11 | 0.00 | 31558205.74 | 0.153225E+11 | 0.00 | 0.331794E+10 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 42846944.45 | 0.00 | 0.00 | 21539165.55 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.606103E+09 | 0.144074E+11 | 0.00 | 6295764.03 | 0.282016E+10 | 0.00 | 0.956292E+09 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.475616E+09 | 30219577.10 | 0.00 | 4630070.82 | 16352626.43 | 0.00 | 0.747068E+09 | 0.00 | 0.37 |
February | 0.335153E+09 | 0.124469E+09 | 0.00 | 4149788.73 | 42224356.02 | 0.00 | 0.482845E+09 | 0.00 | 0.40 |
March | 0.366860E+09 | 0.390403E+09 | 0.00 | 4002801.76 | 97223019.95 | 0.00 | 0.390798E+09 | 0.00 | 0.50 |
April | 0.186379E+09 | 0.111579E+10 | 0.00 | 1813690.76 | 0.535485E+09 | 0.00 | 0.138748E+09 | 0.00 | 0.63 |
May | 15157132.55 | 0.364761E+10 | 0.00 | 1071339.77 | 0.969285E+09 | 0.00 | 45735070.26 | 0.00 | 0.74 |
June | 1516387.77 | 0.627727E+10 | 0.00 | 118496.83 | 0.200675E+10 | 0.00 | 2508696.39 | 0.00 | 0.79 |
July | 5861971.30 | 0.875018E+10 | 0.00 | 126042.15 | 0.255577E+10 | 0.00 | 3348755.34 | 0.00 | 0.78 |
August | 0.00 | 0.955669E+10 | 0.00 | 0.00 | 0.243373E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
September | 34012.96 | 0.690228E+10 | 0.00 | 82967.80 | 0.202618E+10 | 0.00 | 1371641.54 | 0.00 | 0.73 |
October | 21462082.77 | 0.338484E+10 | 0.00 | 619875.31 | 0.142150E+10 | 0.00 | 36091878.60 | 0.00 | 0.64 |
November | 0.115882E+09 | 0.119481E+10 | 0.00 | 1192553.47 | 0.340870E+09 | 0.00 | 66713860.98 | 0.00 | 0.53 |
December | 0.468115E+09 | 0.194809E+09 | 0.00 | 3730652.14 | 0.117005E+09 | 0.00 | 0.372600E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.199204E+10 | 0.415694E+11 | 0.00 | 21538279.53 | 0.125624E+11 | 0.00 | 0.228783E+10 | 0.00 | 0.61 |
Minimum of Months | 0.00 | 30219577.10 | 0.00 | 0.00 | 16352626.43 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.475616E+09 | 0.955669E+10 | 0.00 | 4630070.82 | 0.255577E+10 | 0.00 | 0.747068E+09 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.580396E+09 | 76069154.76 | 0.00 | 10909065.98 | 14055522.44 | 0.00 | 0.152755E+10 | 0.00 | 0.44 |
February | 0.416209E+09 | 0.297553E+09 | 0.00 | 9008338.03 | 32049639.35 | 0.00 | 0.944152E+09 | 0.00 | 0.47 |
March | 0.413904E+09 | 0.762030E+09 | 0.00 | 8014687.96 | 0.102205E+09 | 0.00 | 0.772731E+09 | 0.00 | 0.55 |
April | 0.214665E+09 | 0.192413E+10 | 0.00 | 2943493.27 | 0.630007E+09 | 0.00 | 0.234071E+09 | 0.00 | 0.61 |
May | 23295071.17 | 0.492147E+10 | 0.00 | 1300564.10 | 0.134977E+10 | 0.00 | 55412090.86 | 0.00 | 0.63 |
June | 2016827.48 | 0.851005E+10 | 0.00 | 174071.50 | 0.274441E+10 | 0.00 | 3417587.45 | 0.00 | 0.68 |
July | 7767093.69 | 0.130233E+11 | 0.00 | 228705.52 | 0.310979E+10 | 0.00 | 5471588.22 | 0.00 | 0.71 |
August | 0.00 | 0.151518E+11 | 0.00 | 0.00 | 0.291260E+10 | 0.00 | 0.00 | 0.00 | 0.74 |
September | 0.00 | 0.116616E+11 | 0.00 | 134267.28 | 0.227119E+10 | 0.00 | 2039680.27 | 0.00 | 0.73 |
October | 23024974.20 | 0.674834E+10 | 0.00 | 1496573.94 | 0.148642E+10 | 0.00 | 67734846.33 | 0.00 | 0.71 |
November | 0.137791E+09 | 0.273143E+10 | 0.00 | 3297259.92 | 0.316799E+09 | 0.00 | 0.151508E+09 | 0.00 | 0.64 |
December | 0.504482E+09 | 0.563418E+09 | 0.00 | 10221729.58 | 0.109103E+09 | 0.00 | 0.954893E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.232355E+10 | 0.663711E+11 | 0.00 | 47728757.07 | 0.150784E+11 | 0.00 | 0.471898E+10 | 0.00 | 0.62 |
Minimum of Months | 0.00 | 76069154.76 | 0.00 | 0.00 | 14055522.44 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.580396E+09 | 0.151518E+11 | 0.00 | 10909065.98 | 0.310979E+10 | 0.00 | 0.152755E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.353679E+09 | 49622324.27 | 0.00 | 7670011.76 | 17651681.95 | 0.00 | 0.129987E+10 | 0.00 | 0.52 |
February | 0.203662E+09 | 0.245707E+09 | 0.00 | 8401748.19 | 30014140.54 | 0.00 | 0.102809E+10 | 0.00 | 0.63 |
March | 0.195041E+09 | 0.770816E+09 | 0.00 | 10554874.35 | 52879828.07 | 0.00 | 0.110225E+10 | 0.00 | 0.86 |
April | 70227180.45 | 0.268745E+10 | 0.00 | 5544361.88 | 0.168853E+09 | 0.00 | 0.483840E+09 | 0.00 | 1.06 |
May | 17407573.74 | 0.525108E+10 | 0.00 | 1452257.74 | 0.877898E+09 | 0.00 | 59165461.14 | 0.00 | 0.95 |
June | 1563923.83 | 0.103385E+11 | 0.00 | 219163.81 | 0.152354E+10 | 0.00 | 4362131.24 | 0.00 | 1.11 |
July | 2106997.84 | 0.163823E+11 | 0.00 | 382889.19 | 0.860818E+09 | 0.00 | 12094491.10 | 0.00 | 1.18 |
August | 0.00 | 0.193562E+11 | 0.00 | 0.00 | 0.458217E+09 | 0.00 | 0.00 | 0.00 | 1.26 |
September | 36178.06 | 0.101583E+11 | 0.00 | 106014.15 | 0.183223E+10 | 0.00 | 1759739.85 | 0.00 | 0.96 |
October | 19334080.78 | 0.579203E+10 | 0.00 | 1030999.58 | 0.116344E+10 | 0.00 | 59929340.42 | 0.00 | 0.93 |
November | 90270178.42 | 0.230929E+10 | 0.00 | 3844895.36 | 0.209318E+09 | 0.00 | 0.196073E+09 | 0.00 | 0.87 |
December | 0.249728E+09 | 0.532206E+09 | 0.00 | 12073287.02 | 63742486.00 | 0.00 | 0.127949E+10 | 0.00 | 0.82 |
Annual Sum or Average | 0.120306E+10 | 0.738734E+11 | 0.00 | 51280503.03 | 0.725861E+10 | 0.00 | 0.552693E+10 | 0.00 | 0.93 |
Minimum of Months | 0.00 | 49622324.27 | 0.00 | 0.00 | 17651681.95 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.353679E+09 | 0.193562E+11 | 0.00 | 12073287.02 | 0.183223E+10 | 0.00 | 0.129987E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.902844E+10 | 0.290895E+09 | 0.00 | 28743407.26 | 0.277890E+09 | 0.00 | 0.492955E+10 | 0.00 | 0.29 |
February | 0.516409E+10 | 0.165761E+10 | 0.00 | 30266255.54 | 0.554817E+09 | 0.00 | 0.400099E+10 | 0.00 | 0.31 |
March | 0.356093E+10 | 0.566732E+10 | 0.00 | 39604952.98 | 0.658335E+09 | 0.00 | 0.439190E+10 | 0.00 | 0.37 |
April | 0.103722E+10 | 0.163142E+11 | 0.00 | 21816891.11 | 0.393618E+10 | 0.00 | 0.212675E+10 | 0.00 | 0.45 |
May | 0.179730E+09 | 0.536053E+11 | 0.00 | 12584395.80 | 0.926899E+10 | 0.00 | 0.673288E+09 | 0.00 | 0.63 |
June | 13456957.13 | 0.100509E+12 | 0.00 | 2038542.97 | 0.169861E+11 | 0.00 | 58349952.52 | 0.00 | 0.73 |
July | 55669465.84 | 0.147662E+12 | 0.00 | 1893706.37 | 0.227282E+11 | 0.00 | 62398471.97 | 0.00 | 0.77 |
August | 0.00 | 0.159425E+12 | 0.00 | 0.00 | 0.245332E+11 | 0.00 | 0.00 | 0.00 | 0.77 |
September | 0.00 | 0.100935E+12 | 0.00 | 1111033.87 | 0.192092E+11 | 0.00 | 23843122.28 | 0.00 | 0.64 |
October | 0.265052E+09 | 0.467926E+11 | 0.00 | 5739723.56 | 0.116640E+11 | 0.00 | 0.409688E+09 | 0.00 | 0.50 |
November | 0.601949E+09 | 0.169885E+11 | 0.00 | 13484735.51 | 0.232159E+10 | 0.00 | 0.776088E+09 | 0.00 | 0.38 |
December | 0.507268E+10 | 0.258091E+10 | 0.00 | 30380239.83 | 0.941425E+09 | 0.00 | 0.346724E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.249792E+11 | 0.652430E+12 | 0.00 | 0.187664E+09 | 0.113080E+12 | 0.00 | 0.209201E+11 | 0.00 | 0.51 |
Minimum of Months | 0.00 | 0.290895E+09 | 0.00 | 0.00 | 0.277890E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.902844E+10 | 0.159425E+12 | 0.00 | 39604952.98 | 0.245332E+11 | 0.00 | 0.492955E+10 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.622727E+10 | 0.282397E+09 | 0.00 | 28435565.13 | 0.154644E+09 | 0.00 | 0.537621E+10 | 0.00 | 0.37 |
February | 0.366615E+10 | 0.124396E+10 | 0.00 | 29588315.90 | 0.433798E+09 | 0.00 | 0.414577E+10 | 0.00 | 0.40 |
March | 0.272871E+10 | 0.449382E+10 | 0.00 | 34501581.64 | 0.502323E+09 | 0.00 | 0.392280E+10 | 0.00 | 0.48 |
April | 0.836144E+09 | 0.137484E+11 | 0.00 | 21524609.30 | 0.271627E+10 | 0.00 | 0.199194E+10 | 0.00 | 0.59 |
May | 0.119812E+09 | 0.423852E+11 | 0.00 | 11099947.54 | 0.707134E+10 | 0.00 | 0.586015E+09 | 0.00 | 0.80 |
June | 12952166.41 | 0.765212E+11 | 0.00 | 1302340.11 | 0.140010E+11 | 0.00 | 42815210.71 | 0.00 | 0.88 |
July | 46193811.72 | 0.110407E+12 | 0.00 | 1154415.34 | 0.194315E+11 | 0.00 | 44099822.42 | 0.00 | 0.92 |
August | 0.00 | 0.122648E+12 | 0.00 | 0.00 | 0.199168E+11 | 0.00 | 0.00 | 0.00 | 0.94 |
September | 511172.69 | 0.807974E+11 | 0.00 | 803898.62 | 0.147121E+11 | 0.00 | 18388310.78 | 0.00 | 0.80 |
October | 0.136789E+09 | 0.393599E+11 | 0.00 | 6723328.49 | 0.809982E+10 | 0.00 | 0.484480E+09 | 0.00 | 0.64 |
November | 0.408742E+09 | 0.134179E+11 | 0.00 | 12116054.42 | 0.186413E+10 | 0.00 | 0.781533E+09 | 0.00 | 0.48 |
December | 0.357093E+10 | 0.211464E+10 | 0.00 | 25904719.06 | 0.667859E+09 | 0.00 | 0.341315E+10 | 0.00 | 0.38 |
Annual Sum or Average | 0.177542E+11 | 0.507420E+12 | 0.00 | 0.173155E+09 | 0.895715E+11 | 0.00 | 0.208072E+11 | 0.00 | 0.64 |
Minimum of Months | 0.00 | 0.282397E+09 | 0.00 | 0.00 | 0.154644E+09 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.622727E+10 | 0.122648E+12 | 0.00 | 34501581.64 | 0.199168E+11 | 0.00 | 0.537621E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.571878E+10 | 0.803849E+09 | 0.00 | 92464145.56 | 0.110237E+09 | 0.00 | 0.151400E+11 | 0.00 | 0.47 |
February | 0.392704E+10 | 0.310245E+10 | 0.00 | 74613306.44 | 0.246921E+09 | 0.00 | 0.923196E+10 | 0.00 | 0.48 |
March | 0.280791E+10 | 0.809923E+10 | 0.00 | 65752476.60 | 0.481027E+09 | 0.00 | 0.722495E+10 | 0.00 | 0.50 |
April | 0.970679E+09 | 0.196971E+11 | 0.00 | 25830134.50 | 0.359859E+10 | 0.00 | 0.247777E+10 | 0.00 | 0.52 |
May | 0.196288E+09 | 0.531900E+11 | 0.00 | 12085743.47 | 0.101009E+11 | 0.00 | 0.649777E+09 | 0.00 | 0.64 |
June | 17636141.94 | 0.930024E+11 | 0.00 | 1768376.79 | 0.204837E+11 | 0.00 | 51127810.87 | 0.00 | 0.70 |
July | 59992456.59 | 0.142853E+12 | 0.00 | 1633682.46 | 0.266402E+11 | 0.00 | 60014548.48 | 0.00 | 0.76 |
August | 0.00 | 0.170732E+12 | 0.00 | 0.00 | 0.244549E+11 | 0.00 | 0.00 | 0.00 | 0.82 |
September | 0.00 | 0.128350E+12 | 0.00 | 1270029.74 | 0.156318E+11 | 0.00 | 26944216.10 | 0.00 | 0.76 |
October | 0.142013E+09 | 0.738742E+11 | 0.00 | 14611400.44 | 0.677644E+10 | 0.00 | 0.778175E+09 | 0.00 | 0.71 |
November | 0.374515E+09 | 0.296512E+11 | 0.00 | 29826915.58 | 0.989918E+09 | 0.00 | 0.157123E+10 | 0.00 | 0.61 |
December | 0.313053E+10 | 0.584109E+10 | 0.00 | 81671529.94 | 0.523524E+09 | 0.00 | 0.942430E+10 | 0.00 | 0.50 |
Annual Sum or Average | 0.173454E+11 | 0.729197E+12 | 0.00 | 0.401528E+09 | 0.110038E+12 | 0.00 | 0.466362E+11 | 0.00 | 0.62 |
Minimum of Months | 0.00 | 0.803849E+09 | 0.00 | 0.00 | 0.110237E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.571878E+10 | 0.170732E+12 | 0.00 | 92464145.56 | 0.266402E+11 | 0.00 | 0.151400E+11 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.705622E+10 | 0.331478E+09 | 0.00 | 30257773.96 | 0.167326E+09 | 0.00 | 0.565914E+10 | 0.00 | 0.41 |
February | 0.395208E+10 | 0.169091E+10 | 0.00 | 33126166.33 | 0.347585E+09 | 0.00 | 0.452252E+10 | 0.00 | 0.45 |
March | 0.239898E+10 | 0.559283E+10 | 0.00 | 41473958.39 | 0.388057E+09 | 0.00 | 0.501249E+10 | 0.00 | 0.55 |
April | 0.627683E+09 | 0.170019E+11 | 0.00 | 21081474.19 | 0.217190E+10 | 0.00 | 0.217836E+10 | 0.00 | 0.65 |
May | 0.140894E+09 | 0.489100E+11 | 0.00 | 10380192.29 | 0.616099E+10 | 0.00 | 0.549637E+09 | 0.00 | 0.84 |
June | 12246711.03 | 0.879068E+11 | 0.00 | 1554412.92 | 0.123876E+11 | 0.00 | 45224687.17 | 0.00 | 0.95 |
July | 47949691.94 | 0.128012E+12 | 0.00 | 1729184.35 | 0.156823E+11 | 0.00 | 54662957.33 | 0.00 | 1.00 |
August | 0.00 | 0.145781E+12 | 0.00 | 0.00 | 0.160348E+11 | 0.00 | 0.00 | 0.00 | 1.05 |
September | 555247.43 | 0.934451E+11 | 0.00 | 800846.93 | 0.126000E+11 | 0.00 | 18647445.06 | 0.00 | 0.86 |
October | 0.222550E+09 | 0.444698E+11 | 0.00 | 5126037.84 | 0.749077E+10 | 0.00 | 0.364125E+09 | 0.00 | 0.69 |
November | 0.412487E+09 | 0.158655E+11 | 0.00 | 13957410.40 | 0.152872E+10 | 0.00 | 0.838275E+09 | 0.00 | 0.54 |
December | 0.367151E+10 | 0.276523E+10 | 0.00 | 31928616.16 | 0.667069E+09 | 0.00 | 0.411281E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.185431E+11 | 0.591772E+12 | 0.00 | 0.191416E+09 | 0.756271E+11 | 0.00 | 0.233559E+11 | 0.00 | 0.70 |
Minimum of Months | 0.00 | 0.331478E+09 | 0.00 | 0.00 | 0.167326E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.705622E+10 | 0.145781E+12 | 0.00 | 41473958.39 | 0.160348E+11 | 0.00 | 0.565914E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100724E+10 | 22534888.62 | 0.00 | 1621388.28 | 24415861.74 | 549753.87 | 0.345178E+09 | 0.00 | 0.30 |
February | 0.549598E+09 | 0.136291E+09 | 0.00 | 2391454.07 | 67164285.01 | 0.00 | 0.332952E+09 | 0.00 | 0.31 |
March | 0.390936E+09 | 0.475010E+09 | 0.00 | 3479334.08 | 66035504.68 | 0.00 | 0.379035E+09 | 0.00 | 0.37 |
April | 0.152977E+09 | 0.148038E+10 | 0.00 | 2173829.49 | 0.368908E+09 | 0.00 | 0.150537E+09 | 0.00 | 0.46 |
May | 17072490.63 | 0.510123E+10 | 0.00 | 1282997.05 | 0.893820E+09 | 0.00 | 58889111.62 | 0.00 | 0.64 |
June | 1204477.26 | 0.985443E+10 | 0.00 | 206620.58 | 0.163260E+10 | 0.00 | 5365623.37 | 0.00 | 0.73 |
July | 6724735.72 | 0.146316E+11 | 0.00 | 274453.50 | 0.193847E+10 | 0.00 | 7431738.77 | 0.00 | 0.77 |
August | 0.00 | 0.155684E+11 | 0.00 | 0.00 | 0.227852E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
September | 33535.17 | 0.993216E+10 | 0.00 | 84633.16 | 0.200101E+10 | 0.00 | 1107646.15 | 0.00 | 0.65 |
October | 27920003.67 | 0.455420E+10 | 0.00 | 585383.52 | 0.122093E+10 | 0.00 | 37448283.13 | 0.00 | 0.51 |
November | 68572506.33 | 0.158136E+10 | 0.00 | 1160557.92 | 0.240171E+09 | 0.00 | 56700498.95 | 0.00 | 0.38 |
December | 0.507658E+09 | 0.223192E+09 | 0.00 | 2153268.34 | 0.106095E+09 | 0.00 | 0.291958E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.272993E+10 | 0.635608E+11 | 0.00 | 15413919.99 | 0.108381E+11 | 549753.87 | 0.166660E+10 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 22534888.62 | 0.00 | 0.00 | 24415861.74 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.100724E+10 | 0.155684E+11 | 0.00 | 3479334.08 | 0.227852E+10 | 549753.87 | 0.379035E+09 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.661415E+09 | 22446906.55 | 0.00 | 2018623.83 | 14431397.92 | 0.00 | 0.413334E+09 | 0.00 | 0.37 |
February | 0.337820E+09 | 0.105246E+09 | 0.00 | 2647294.89 | 49911035.51 | 0.00 | 0.388296E+09 | 0.00 | 0.40 |
March | 0.252946E+09 | 0.391893E+09 | 0.00 | 3366862.22 | 45015879.77 | 0.00 | 0.381051E+09 | 0.00 | 0.47 |
April | 98141262.82 | 0.129015E+10 | 0.00 | 2328915.22 | 0.217830E+09 | 0.00 | 0.167823E+09 | 0.00 | 0.60 |
May | 8696922.68 | 0.406361E+10 | 0.00 | 1252760.63 | 0.643170E+09 | 0.00 | 54594374.13 | 0.00 | 0.81 |
June | 999370.14 | 0.753554E+10 | 0.00 | 153415.53 | 0.127030E+10 | 0.00 | 4245426.91 | 0.00 | 0.88 |
July | 5115941.39 | 0.109702E+11 | 0.00 | 181680.81 | 0.154482E+10 | 0.00 | 5346152.93 | 0.00 | 0.91 |
August | 0.00 | 0.120079E+11 | 0.00 | 0.00 | 0.173009E+10 | 0.00 | 0.00 | 0.00 | 0.93 |
September | 64081.55 | 0.800458E+10 | 0.00 | 67411.18 | 0.143638E+10 | 0.00 | 827552.94 | 0.00 | 0.81 |
October | 11087821.47 | 0.391944E+10 | 0.00 | 728103.95 | 0.784727E+09 | 0.00 | 47707107.10 | 0.00 | 0.65 |
November | 40740141.88 | 0.131256E+10 | 0.00 | 1152501.77 | 0.170024E+09 | 0.00 | 62205567.24 | 0.00 | 0.49 |
December | 0.347265E+09 | 0.184575E+09 | 0.00 | 2099467.30 | 79757609.27 | 0.00 | 0.285555E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.176429E+10 | 0.498081E+11 | 0.00 | 15997037.34 | 0.798647E+10 | 0.00 | 0.181099E+10 | 0.00 | 0.64 |
Minimum of Months | 0.00 | 22446906.55 | 0.00 | 0.00 | 14431397.92 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.661415E+09 | 0.120079E+11 | 0.00 | 3366862.22 | 0.173009E+10 | 0.00 | 0.413334E+09 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.672906E+09 | 63403433.61 | 0.00 | 7303156.66 | 11213037.06 | 0.00 | 0.133526E+10 | 0.00 | 0.46 |
February | 0.404687E+09 | 0.261539E+09 | 0.00 | 6742665.68 | 32140230.87 | 0.00 | 0.904746E+09 | 0.00 | 0.47 |
March | 0.327967E+09 | 0.666401E+09 | 0.00 | 6291785.07 | 52382685.55 | 0.00 | 0.668202E+09 | 0.00 | 0.49 |
April | 0.152506E+09 | 0.177623E+10 | 0.00 | 2636583.51 | 0.343655E+09 | 0.00 | 0.186765E+09 | 0.00 | 0.52 |
May | 19586792.47 | 0.502064E+10 | 0.00 | 1214409.55 | 0.104635E+10 | 0.00 | 56898776.38 | 0.00 | 0.65 |
June | 1548476.55 | 0.911000E+10 | 0.00 | 176222.97 | 0.206841E+10 | 0.00 | 4816736.00 | 0.00 | 0.71 |
July | 8120829.52 | 0.141666E+11 | 0.00 | 242084.54 | 0.239057E+10 | 0.00 | 6504969.91 | 0.00 | 0.77 |
August | 0.00 | 0.164882E+11 | 0.00 | 0.00 | 0.245765E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
September | 36451.30 | 0.123947E+11 | 0.00 | 97364.61 | 0.179123E+10 | 0.00 | 1279918.64 | 0.00 | 0.78 |
October | 13712531.03 | 0.706249E+10 | 0.00 | 1529607.62 | 0.788193E+09 | 0.00 | 75565952.92 | 0.00 | 0.71 |
November | 36122556.46 | 0.273272E+10 | 0.00 | 3355629.29 | 0.130926E+09 | 0.00 | 0.145099E+09 | 0.00 | 0.60 |
December | 0.340890E+09 | 0.509679E+09 | 0.00 | 6859696.90 | 62763300.84 | 0.00 | 0.855923E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.197808E+10 | 0.702526E+11 | 0.00 | 36449206.40 | 0.111755E+11 | 0.00 | 0.424106E+10 | 0.00 | 0.62 |
Minimum of Months | 0.00 | 63403433.61 | 0.00 | 0.00 | 11213037.06 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.672906E+09 | 0.164882E+11 | 0.00 | 7303156.66 | 0.245765E+10 | 0.00 | 0.133526E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.830156E+09 | 26316656.25 | 0.00 | 2087890.92 | 13656418.10 | 0.00 | 0.426247E+09 | 0.00 | 0.43 |
February | 0.432955E+09 | 0.139657E+09 | 0.00 | 2779215.10 | 45957143.44 | 0.00 | 0.399283E+09 | 0.00 | 0.46 |
March | 0.290231E+09 | 0.459011E+09 | 0.00 | 3798092.90 | 43221906.92 | 0.00 | 0.434390E+09 | 0.00 | 0.54 |
April | 0.106050E+09 | 0.149810E+10 | 0.00 | 2095029.00 | 0.212633E+09 | 0.00 | 0.164411E+09 | 0.00 | 0.65 |
May | 14208633.54 | 0.444712E+10 | 0.00 | 1054182.99 | 0.676797E+09 | 0.00 | 47719936.90 | 0.00 | 0.84 |
June | 1094103.15 | 0.824815E+10 | 0.00 | 151140.70 | 0.133467E+10 | 0.00 | 4095407.60 | 0.00 | 0.94 |
July | 5518016.01 | 0.119737E+11 | 0.00 | 223986.75 | 0.165629E+10 | 0.00 | 6555317.39 | 0.00 | 0.98 |
August | 0.00 | 0.134656E+11 | 0.00 | 0.00 | 0.175769E+10 | 0.00 | 0.00 | 0.00 | 1.02 |
September | 30071.53 | 0.881544E+10 | 0.00 | 67391.10 | 0.150316E+10 | 0.00 | 903983.10 | 0.00 | 0.86 |
October | 24180588.40 | 0.422244E+10 | 0.00 | 516980.16 | 0.845492E+09 | 0.00 | 33044907.57 | 0.00 | 0.70 |
November | 50574459.30 | 0.147267E+10 | 0.00 | 1299260.85 | 0.163531E+09 | 0.00 | 64225940.64 | 0.00 | 0.54 |
December | 0.396692E+09 | 0.240588E+09 | 0.00 | 2411563.89 | 74567536.38 | 0.00 | 0.346263E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.215169E+10 | 0.550087E+11 | 0.00 | 16484734.35 | 0.832766E+10 | 0.00 | 0.192714E+10 | 0.00 | 0.70 |
Minimum of Months | 0.00 | 26316656.25 | 0.00 | 0.00 | 13656418.10 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.830156E+09 | 0.134656E+11 | 0.00 | 3798092.90 | 0.175769E+10 | 0.00 | 0.434390E+09 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 47710190.18 | 0.00 | 6786591.94 | 0.00 | 0.00 | 0.218857E+09 | 0.00 | 0.58 |
February | 0.00 | 0.132390E+09 | 0.00 | 8286360.30 | 0.00 | 0.00 | 77720253.25 | 0.00 | 0.58 |
March | 0.00 | 0.206177E+09 | 0.00 | 13838460.65 | 0.00 | 0.00 | 56163834.33 | 0.00 | 0.59 |
April | 0.00 | 0.492404E+09 | 0.00 | 5249395.74 | 0.00 | 0.00 | 9427116.90 | 0.00 | 0.59 |
May | 0.00 | 0.827813E+09 | 0.00 | 129387.81 | 0.00 | 0.00 | 724153.76 | 0.00 | 0.59 |
June | 0.00 | 0.136702E+10 | 0.00 | 7197.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.180648E+10 | 0.00 | 6893.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.184874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.142821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.103002E+10 | 0.00 | 390589.18 | 0.00 | 0.00 | 913956.61 | 0.00 | 0.59 |
November | 0.00 | 0.537077E+09 | 0.00 | 1242312.41 | 0.00 | 0.00 | 1847047.08 | 0.00 | 0.58 |
December | 0.00 | 0.236774E+09 | 0.00 | 16822973.89 | 0.00 | 0.00 | 53804377.15 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.996082E+10 | 0.00 | 52760163.63 | 0.00 | 0.00 | 0.419458E+09 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 47710190.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.184874E+10 | 0.00 | 16822973.89 | 0.00 | 0.00 | 0.218857E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.435691E+09 | 0.00 | 54232843.42 | 0.00 | 0.00 | 0.227569E+10 | 0.00 | 0.58 |
February | 0.00 | 0.130069E+10 | 0.00 | 74099742.15 | 0.00 | 0.00 | 0.799349E+09 | 0.00 | 0.58 |
March | 0.00 | 0.205502E+10 | 0.00 | 0.130174E+09 | 0.00 | 0.00 | 0.569312E+09 | 0.00 | 0.59 |
April | 0.00 | 0.491940E+10 | 0.00 | 50439394.09 | 0.00 | 0.00 | 95285197.18 | 0.00 | 0.59 |
May | 0.00 | 0.820310E+10 | 0.00 | 1214286.44 | 0.00 | 0.00 | 7334921.30 | 0.00 | 0.59 |
June | 0.00 | 0.136181E+11 | 0.00 | 73956.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.180260E+11 | 0.00 | 64353.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.184958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.141416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.102576E+11 | 0.00 | 3690253.93 | 0.00 | 0.00 | 9327300.12 | 0.00 | 0.59 |
November | 0.00 | 0.535731E+10 | 0.00 | 11755634.17 | 0.00 | 0.00 | 19243250.27 | 0.00 | 0.58 |
December | 0.00 | 0.236286E+10 | 0.00 | 0.157448E+09 | 0.00 | 0.00 | 0.547709E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.991732E+11 | 0.00 | 0.483193E+09 | 0.00 | 0.00 | 0.432325E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.435691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.184958E+11 | 0.00 | 0.157448E+09 | 0.00 | 0.00 | 0.227569E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 45509398.75 | 0.00 | 3913410.51 | 0.00 | 0.00 | 0.228499E+09 | 0.00 | 0.58 |
February | 0.00 | 0.138317E+09 | 0.00 | 6556128.54 | 0.00 | 0.00 | 74761636.61 | 0.00 | 0.58 |
March | 0.00 | 0.216969E+09 | 0.00 | 11795133.04 | 0.00 | 0.00 | 51584752.65 | 0.00 | 0.59 |
April | 0.00 | 0.509452E+09 | 0.00 | 4476483.09 | 0.00 | 0.00 | 8308271.23 | 0.00 | 0.59 |
May | 0.00 | 0.840551E+09 | 0.00 | 89062.55 | 0.00 | 0.00 | 590342.47 | 0.00 | 0.59 |
June | 0.00 | 0.138234E+10 | 0.00 | 3090.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.182356E+10 | 0.00 | 236.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.189384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.143721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.104459E+10 | 0.00 | 326462.47 | 0.00 | 0.00 | 713677.47 | 0.00 | 0.59 |
November | 0.00 | 0.553173E+09 | 0.00 | 960737.41 | 0.00 | 0.00 | 1413918.08 | 0.00 | 0.58 |
December | 0.00 | 0.248706E+09 | 0.00 | 14116589.90 | 0.00 | 0.00 | 49758201.03 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.101342E+11 | 0.00 | 42237334.02 | 0.00 | 0.00 | 0.415630E+09 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 45509398.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.189384E+10 | 0.00 | 14116589.90 | 0.00 | 0.00 | 0.228499E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:05:50
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.267693E+12 | 0.513721E+10 | 0.00 | 0.453179E+12 | 0.951031E+12 |
February | 0.303085E+12 | 0.398178E+10 | 0.00 | 0.269912E+12 | 0.107108E+13 |
March | 0.374811E+12 | 0.177029E+10 | 0.00 | 0.148661E+12 | 0.155267E+13 |
April | 0.398801E+12 | -0.422293E+10 | 0.00 | -0.235942E+12 | 0.199766E+13 |
May | 0.417252E+12 | -0.123408E+11 | 0.00 | -0.833000E+12 | 0.270136E+13 |
June | 0.403291E+12 | -0.241266E+11 | 0.00 | -0.146848E+13 | 0.353977E+13 |
July | 0.396514E+12 | -0.328021E+11 | 0.00 | -0.203050E+13 | 0.439926E+13 |
August | 0.383127E+12 | -0.324783E+11 | 0.00 | -0.217794E+13 | 0.483111E+13 |
September | 0.334754E+12 | -0.253368E+11 | 0.00 | -0.167012E+13 | 0.355072E+13 |
October | 0.284243E+12 | -0.129971E+11 | 0.00 | -0.970197E+12 | 0.273886E+13 |
November | 0.228462E+12 | -0.300531E+10 | 0.00 | -0.263789E+12 | 0.193369E+13 |
December | 0.230608E+12 | 0.245184E+10 | 0.00 | 0.214326E+12 | 0.141144E+13 |
Annual Sum or Average | 0.402264E+13 | -0.133969E+12 | 0.00 | -0.856388E+13 | 0.306786E+14 |
Minimum of Months | 0.228462E+12 | -0.328021E+11 | 0.00 | -0.217794E+13 | 0.951031E+12 |
Maximum of Months | 0.417252E+12 | 0.513721E+10 | 0.00 | 0.453179E+12 | 0.483111E+13 |