Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:07
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 09:07:39
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 30833.56 | 665.66 | 665.66 |
Net Site Energy | 30833.56 | 665.66 | 665.66 |
Total Source Energy | 81052.47 | 1749.82 | 1749.82 |
Net Source Energy | 81052.47 | 1749.82 | 1749.82 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 39.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1042.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7166.03 | 0.00 | 0.00 |
Interior Lighting | 2026.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 321.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3108.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1017.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 456.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 313.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3549.15 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 665.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 22963.00 | 704.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7166.03 | 0.00 | 5829.32 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 39.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1042.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7166.03 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2026.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 321.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ComputerHVAC | 1199.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 1017.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 456.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 313.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3549.15 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 665.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 39.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1042.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7166.03 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2026.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 321.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 3108.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 1017.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 456.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 313.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3549.15 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 665.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 61.09 | 15.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.71 | 0.00 | 0.13 |
Other | 383.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 495.74 | 15.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.71 | 0.00 | 0.13 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 61.09 | 15.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.71 | 0.00 | 0.13 |
Other | 383.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 495.74 | 15.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.71 | 0.00 | 0.13 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 22962.996 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 22962.996 | 100.00 |
Total On-Site and Utility Electric Sources | 22962.996 | 100.00 |
Total Electricity End Uses | 22962.996 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5829.32 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5829.32 | 100.00 |
Total Water End Uses | 5829.32 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 152.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionDistrictHeatingCoolingMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:07 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.8895 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.8895 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 5.9168 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 5.9168 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.8895 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8895 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.8895 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8895 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.8895 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.9168 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.9168 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.8190 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
Time of Peak | 18-AUG-15:50 | 03-JAN-07:10 | - | - | - | - | - | - | - | - | 26-DEC-14:00 | 31-MAY-23:40 | 16-OCT-11:09 |
Heating | 0.00 | 299869.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 0.00 |
Cooling | 273658.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369114.52 | 0.00 | 0.00 |
Interior Lighting | 171235.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 143548.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 121782.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 45689.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 40740.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 28748.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1575027.12 | 328617.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369114.52 | 13.50 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 0.00 |
Boiler | 0.00 | 299869.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 273658.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369114.52 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 171235.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3372.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ComputerHVAC | 60741.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 121782.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 45689.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 40740.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 28748.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 42.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Cooling | 3303.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7564.94 | 0.00 |
Interior Lighting | 6419.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1018.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 9843.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1444.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 992.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 720.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 72723.81 | 763.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7564.94 | 0.01 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.32 | 0.00 |
Interior Lighting | 138.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 22.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 212.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 69.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 31.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 21.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 15.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1570.02 | 16.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.32 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.32 | 0.00 |
Interior Lighting | 138.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 22.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 212.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 69.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 31.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 21.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 15.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1570.02 | 16.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.32 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 4.79 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.468421 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.46 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.453915 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.24 | 0.362788 | 0.353000 | 1.85 | 0.967435 | 0.500000 | 0.001050 | 0.000160 | 1.85 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 49.12 | 0.387213 | 0.367000 | 18.03 | 1.00 | 0.500000 | 0.000984 | 0.003094 | 18.03 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 4.78 | 0.397603 | 0.384000 | 1.84 | 1.00 | 0.500000 | 0.000958 | 0.000539 | 1.86 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.783686 | 0.304740 | 0.296000 | 0.231971 | 0.812640 | 0.500000 | 0.001250 | 0.000047 | 0.231971 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.881936 | 0.174508 | 0.200000 | 0.176387 | 0.465355 | 0.500000 | 0.002183 | 0.000036 | 0.176387 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.06 | 0.225518 | 0.219000 | 0.231923 | 0.601382 | 0.500000 | 0.001689 | 0.000062 | 0.231923 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.14 | 0.134802 | 0.200000 | 0.228343 | 0.359471 | 0.500000 | 0.002826 | 0.000027 | 0.228343 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 7.20 | 0.331840 | 0.315000 | 2.27 | 0.884907 | 0.500000 | 0.001148 | 0.001244 | 4.32 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 9.05 | 0.169996 | 0.200000 | 1.81 | 0.453321 | 0.500000 | 0.002241 | 0.000834 | 2.89 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 10.11 | 0.236212 | 0.224000 | 2.26 | 0.629900 | 0.500000 | 0.001613 | 0.001250 | 4.34 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 9.60 | 0.160320 | 0.200000 | 1.92 | 0.427520 | 0.500000 | 0.002376 | 0.000736 | 2.55 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.824171 | 0.289771 | 0.280000 | 0.230768 | 0.772722 | 0.500000 | 0.001315 | 0.000171 | 0.594917 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.903882 | 0.170271 | 0.200000 | 0.180776 | 0.454056 | 0.500000 | 0.002238 | 0.000114 | 0.394345 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.11 | 0.214525 | 0.207000 | 0.230448 | 0.572067 | 0.500000 | 0.001776 | 0.000172 | 0.597341 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.03 | 0.148943 | 0.200000 | 0.206663 | 0.397182 | 0.500000 | 0.002558 | 0.000106 | 0.369290 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18288.14 | 0.000160 | 368.67 |
CORE_MID VAV BOX REHEAT COIL | 353694.58 | 0.003094 | 7902.99 |
CORE_TOP VAV BOX REHEAT COIL | 61606.24 | 0.000539 | 1627.96 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5420.54 | 0.000047 | 126.48 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4115.44 | 0.000036 | 95.99 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 7128.98 | 0.000062 | 182.56 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3121.96 | 0.000027 | 65.41 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 142164.55 | 0.001244 | 3751.08 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 95323.68 | 0.000834 | 2515.06 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 142839.46 | 0.001250 | 3768.87 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 84154.17 | 0.000736 | 2220.63 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19580.62 | 0.000171 | 516.47 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12978.31 | 0.000114 | 342.31 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 19660.25 | 0.000172 | 518.57 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12155.31 | 0.000106 | 320.62 |
VAV_BOT WITH REHEAT HEATING COIL | 26766.09 | 0.000234 | 460.13 |
VAV_MID WITH REHEAT HEATING COIL | 246969.93 | 0.002161 | 4245.59 |
VAV_TOP WITH REHEAT HEATING COIL | 26127.60 | 0.000229 | 449.15 |
CAV_BAS HEATING COIL | 222325.21 | 0.001945 | 5042.56 |
Design Size Maximum Heating Air Flow Rate [m3/s] | Design Size Maximum Cooling Air Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT | 0.338402 | 21.55 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 4.55 | 2.72 | 9.11 | 2.72 | 8.35 | 8.35 | 0.300000 | 0.325751 | 8.35 |
VAV_MID WITH REHEAT | 42.54 | 26.29 | 85.08 | 26.29 | 77.03 | 77.03 | 0.300000 | 0.341312 | 77.03 |
VAV_TOP WITH REHEAT | 4.33 | 2.69 | 8.66 | 3.82 | 8.15 | 8.15 | 0.300000 | 0.468800 | 8.15 |
CAV_BAS | 4.79 | 4.79 | 4.79 | 4.79 | 4.79 | 4.79 | 1.00 | 1.00 | 4.79 |
AIRLOOP DATACENTER BOT | 0.468421 | 0.468421 | 0.468421 | 0.468421 | 0.468421 | 0.468421 | 1.00 | 1.00 | 0.468421 |
AIRLOOP DATACENTER MID | 4.46 | 4.46 | 4.46 | 4.46 | 4.46 | 4.46 | 1.00 | 1.00 | 4.46 |
AIRLOOP DATACENTER TOP | 0.453915 | 0.453915 | 0.453915 | 0.453915 | 0.453915 | 0.453915 | 1.00 | 1.00 | 0.453915 |
Maximum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.35 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 77.03 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.15 |
CAV_BAS_OA_CONTROLLER | 4.79 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.468421 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.46 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.453915 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.35 | 6.67 | 11.01 | 0.008684 | 0.008500 | 159045.76 | 0.006766 | 8.35 |
VAV_MID WITH REHEAT COOLING COIL | 26.64 | 6.67 | 11.01 | 0.008683 | 0.008500 | 1494554.74 | 0.063582 | 77.03 |
VAV_TOP WITH REHEAT COOLING COIL | 26.27 | 6.67 | 11.01 | 0.008676 | 0.008500 | 154351.23 | 0.006566 | 8.15 |
CAV_BAS COOLING COIL | 25.71 | 6.67 | 11.40 | 0.008844 | 0.008500 | 87746.81 | 0.003733 | 4.79 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.35 |
VAV_MID WITH REHEAT FAN | 77.03 |
VAV_TOP WITH REHEAT FAN | 8.15 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006766 | 0.000070 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000234 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.063582 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.002161 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.006566 | 0.000073 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000229 | |
CAV_BAS_COOLC_CONTROLLER | 0.003733 | 0.000128 |
CAV_BAS_HEATC_CONTROLLER | 0.001945 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 4.79 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.468421 | 9065.97 | 6522.46 | 0.000222 |
AIRLOOP DATACENTER MID COOLING COIL | 4.46 | 86435.81 | 62161.75 | 0.002117 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.453915 | 8789.21 | 6321.75 | 0.000215 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.468421 | 0.468421 | 0.468421 | 0.468421 | 9065.97 | 9065.97 | 672.03 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.46 | 4.46 | 4.46 | 4.46 | 86435.81 | 86435.81 | 6720.26 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.453915 | 0.453915 | 0.453915 | 0.453915 | 8789.21 | 8789.21 | 672.03 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.468421 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.46 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.453915 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT HEATING COIL | 0.468421 | 9065.97 | 0.000222 |
AIRLOOP DATACENTER MID HEATING COIL | 4.46 | 86435.81 | 0.002117 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.453915 | 8789.21 | 0.000215 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 672.03 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6720.26 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 672.03 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.080647 | 16453.90 | |
HEATSYS1 PUMP | 0.013161 | 3924.37 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.080647 | 9.68 |
HEATSYS1 | 0.013161 | 1.58 |
COOLSYS1_SUPPLY | 0.080647 | 9.68 |
SINGLE WATER PLANT LOOP | 0.002554 | 0.306490 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.080647 | 0.080647 | 338517.60 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1504421.06 | 1504421.06 | 0.013161 |
CENTRAL BOILER | 105206.18 | 105206.18 | 0.002554 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.080647 | 11391.59 |
PLANT CIRC PUMP | 0.002554 | 644.97 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.080647 | 0.040809 | 960324.67 | 966170.08 | 0.048983 |
COOLSYS1 CHILLER2 | 0.080647 | 0.040809 | 960324.67 | 966170.08 | 0.048983 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.002554 | 35644.39 | 24144.71 | 17822.20 | 1996.20 | 5960.76 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.097966 | 11.76 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.097966 | 29212.95 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 37.90 | 1147124.87 | 7.58 | 143390.61 |
TOWERWATERSYS COOLTOWER 2 | 37.90 | 1147124.87 | 7.58 | 143390.61 |
Design Water Flow Rate [m3/s] Equipment # 45 | |
WSHPPLANT OPERATION SCHEME | 0.049662 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.889 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.731 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.889 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.313 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16369.361 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16369.361 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4615.459 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4615.459 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.498 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.416 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.867 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5004 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5391 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3683 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.14091426E-14 | 0.48101397E-16 | -0.12271849E-09 | -0.49605034E-17 |
51 | 8 | 0.18065296E-07 | 0.19413100E-12 | 0.33649602E-03 | -0.20540863E-09 |
52 | 7 | -0.11004888E-01 | 0.10546945E-07 | -0.21303752E-01 | 0.12512956E-03 |
53 | 6 | 0.37174157 | 0.37425545E-05 | 0.44335749 | -0.43515980E-02 |
54 | 5 | -4.8625044 | 0.14213861E-03 | -4.2200868 | 0.59116134E-01 |
55 | 4 | 31.551289 | 0.11806248E-02 | 20.574731 | -0.40285082 |
56 | 3 | -108.13650 | 0.26081321E-02 | -53.912227 | 1.4705586 |
57 | 2 | 194.06739 | 0.14847903E-02 | 76.306869 | -2.8520668 |
58 | 1 | -170.03224 | 0.16027253E-03 | -54.802483 | 2.7257428 |
59 | 0 | 57.057407 | 0.92345258E-06 | 15.636386 | |
60 | 9 | 0.11726792E-14 | 0.46876770E-16 | -0.12664795E-09 | -0.40425794E-17 |
61 | 8 | 0.18621286E-07 | 0.18477046E-12 | 0.34269676E-03 | -0.21173044E-09 |
62 | 7 | -0.11191167E-01 | 0.99660246E-08 | -0.21572393E-01 | 0.12724763E-03 |
63 | 6 | 0.37680492 | 0.35261678E-05 | 0.44770143 | -0.44112820E-02 |
64 | 5 | -4.9119389 | 0.13358806E-03 | -4.2535898 | 0.59729078E-01 |
65 | 4 | 31.770087 | 0.11071467E-02 | 20.706000 | -0.40575564 |
66 | 3 | -108.60241 | 0.24410452E-02 | -54.171883 | 1.4772891 |
67 | 2 | 194.52961 | 0.13872791E-02 | 76.544434 | -2.8594062 |
68 | 1 | -170.20315 | 0.14950961E-03 | -54.870487 | 2.7287383 |
69 | 0 | 57.057407 | 0.85997654E-06 | 15.624277 | |
70 | 9 | 0.98458787E-15 | 0.55454857E-16 | -0.10492535E-09 | -0.15601002E-17 |
71 | 8 | 0.15540463E-07 | 0.23311053E-12 | 0.30746206E-03 | -0.17670042E-09 |
72 | 7 | -0.10129638E-01 | 0.13130386E-07 | -0.20040359E-01 | 0.11517765E-03 |
73 | 6 | 0.34794661 | 0.47273228E-05 | 0.42286390 | -0.40711180E-02 |
74 | 5 | -4.6301347 | 0.18177508E-03 | -4.0616887 | 0.56235001E-01 |
75 | 4 | 30.522476 | 0.15264987E-02 | 19.953355 | -0.38919251 |
76 | 3 | -105.94476 | 0.34047073E-02 | -52.682811 | 1.4388992 |
77 | 2 | 191.89184 | 0.19546755E-02 | 75.183526 | -2.8175246 |
78 | 1 | -169.22736 | 0.21263380E-03 | -54.483619 | 2.7116363 |
79 | 0 | 57.057407 | 0.12355163E-05 | 15.695393 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.4237_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.408 | 2.408 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.408 | 2.408 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.4237_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.408 | 2.408 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.4237_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.408 | 2.408 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.98522E-002 | 0.16139 | 0.62038 | 0.62038 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.98522E-002 | 0.16139 | 0.62038 | 0.62038 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.98522E-002 | 0.16139 | 0.62038 | 0.62038 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.98522E-002 | 0.16139 | 0.62038 | 0.62038 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9647E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9660E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1968E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1979E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2356E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2364E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2447E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2452E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9949E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0851E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2226E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3025E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2575E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3217E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2574E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2891E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1882E-002 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8269E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.2417E-002 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2191E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.3077E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4762E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6042E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.1095E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9934E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0763E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2208E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2923E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2559E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3153E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2577E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2900E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9645E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9658E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1966E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1977E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2355E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2363E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2447E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2451E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.5610E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6954E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.3815E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5217E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.3340E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4031E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1302E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1521E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8209E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4512E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.5557E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2719E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9726E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2433E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6787E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.9865E-003 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.5228E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5804E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.3325E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3741E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.3115E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3272E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1303E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1525E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2595E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2607E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0742E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0751E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.5120E-004 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.5185E-004 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2447E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2452E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2861E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3552E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0954E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1491E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.6729E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0025E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2577E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2900E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9901E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1438E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5430E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.6894E-003 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5429E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.1162E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6042E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.1067E-003 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2860E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3531E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0957E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1488E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.6854E-004 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0065E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2574E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2891E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2595E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2607E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0742E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0751E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.5118E-004 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.5189E-004 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2447E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2451E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6910E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7474E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.5398E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5808E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.4564E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4728E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1303E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1525E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1470E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5790E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9538E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4277E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2717E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.3618E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6787E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 9.9865E-003 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7338E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8881E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.5945E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7596E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.4795E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5530E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1302E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1521E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.5365E-002 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.9925E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.2154E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.4591E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.5174E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.4235E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.0133E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.4574E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.2681E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.0173E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 2.9793E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.8012E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.3952E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7600E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.0820E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4729E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3873E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6781E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8997E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3285E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8945E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.0334E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0133E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4571E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6221E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1848E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.4118E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0060E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.7169E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9102E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.0820E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.4729E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.5317E-002 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.0000E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.2109E-002 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.4682E-002 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.5195E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.4306E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.0168E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.4602E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.2663E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.0190E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 2.9782E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.8028E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.3965E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7629E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.0854E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4757E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3843E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6788E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8977E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3291E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8955E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.0350E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0168E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4599E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6204E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1868E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.4110E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0080E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.7183E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9135E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.0854E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4757E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 65393.20889 | 65393.20889 | 4.79447 | 4.79447 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2779.42662 | 149.60210 | 1.20019 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20019 | 00:10:00 | 3.80000 | 5.05843E-003 | 2779.42662 | 149.60210 | 1.20019 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 71501.76345 | 71501.76345 | 5.24285 | 5.24285 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 670123.93698 | 670123.93698 | 49.12145 | 49.12145 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 175553.29915 | 175553.29915 | 7.48380 | 10.77825 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 65265.75753 | 65265.75753 | 4.78378 | 4.78378 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 43184.27654 | 43184.27654 | 1.86427 | 1.86427 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 10585.86868 | 10585.86868 | 0.78369 | 0.78369 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30000 | 8.23349E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 3133.28847 | 3133.28847 | 0.13436 | 0.13533 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 12000.55686 | 12000.55686 | 0.88194 | 0.88194 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 2375.85698 | 2375.85698 | 0.10215 | 0.10215 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 14304.90160 | 14304.90160 | 1.05901 | 1.05901 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 30.85500 | 8.23278E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 4840.75388 | 4840.75388 | 0.20883 | 0.20883 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 15422.19756 | 15422.19756 | 1.14172 | 1.14172 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 872.64649 | 872.64649 | 3.77341E-002 | 8.72129E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 97214.22828 | 97214.22828 | 7.19686 | 7.19686 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30000 | 8.23349E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 99556.46603 | 99556.46603 | 4.31615 | 4.31615 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 122294.07690 | 122294.07690 | 9.05348 | 9.05348 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 25.27767 | 8.22398E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 66750.66172 | 66750.66172 | 2.89431 | 2.89431 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 136573.48171 | 136573.48171 | 10.11064 | 10.11064 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.23290E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 100028.32794 | 100028.32794 | 4.33669 | 4.33669 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 129674.58874 | 129674.58874 | 9.59987 | 9.59987 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 30.29133 | 8.23188E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 58941.40857 | 58941.40857 | 2.55448 | 2.55448 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 11132.83838 | 11132.83838 | 0.82417 | 0.82417 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 31.30000 | 8.23349E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 13705.91294 | 13705.91294 | 0.59492 | 0.59492 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 12209.63701 | 12209.63701 | 0.90388 | 0.90388 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 26.65717 | 8.22614E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 9084.19250 | 9084.19250 | 0.39434 | 0.39434 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 15038.07859 | 15038.07859 | 1.11328 | 1.11328 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.07750 | 8.23314E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 13761.57203 | 13761.57203 | 0.59734 | 0.59734 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 13957.97633 | 13957.97633 | 1.03331 | 1.03331 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 8508.88893 | 8508.88893 | 0.36929 | 0.36929 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8022.01358 | 8022.01358 | 0.46842 | 0.46842 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 28.94150 | 8.22975E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56328E-002 | 00:10:00 | 3.80000 | 5.05843E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 76428.72781 | 76428.72781 | 4.46286 | 4.46286 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 28.94150 | 8.22975E-003 | 36.20274 | 1.94861 | 0.15633 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15633 | 00:10:00 | 3.80000 | 5.05843E-003 | 36.20274 | 1.94861 | 0.15633 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7773.54391 | 7773.54391 | 0.45391 | 0.45391 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 29.16400 | 8.23009E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56328E-002 | 00:10:00 | 3.80000 | 5.05843E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 369078.44698 | 369078.44698 | 21.55077 | 21.55077 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 23.20100 | 8.22076E-003 | 783.67941 | 42.18139 | 0.33840 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33840 | 00:10:00 | 3.80000 | 5.05843E-003 | 783.67941 | 42.18139 | 0.33840 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 127035.07 | 8.34795 | 8.34795 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 17221.61 | 1.61135 | 1.61135 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1154176.71 | 77.02633 | 77.02633 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 265908.38 | 24.87989 | 24.87989 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 130376.67 | 8.14882 | 8.14882 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 27096.51 | 3.82016 | 3.82016 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 |
7 | CAV_BAS | Cooling | Sensible | 66069.93 | 4.79447 | 4.79447 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 51594.09 | 1.20019 | 1.20019 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 7936.57 | 0.46842 | 0.46842 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BOT | Heating | Sensible | 672.03 | 1.56328E-002 | 1.56328E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER MID | Cooling | Sensible | 75622.21 | 4.46286 | 4.46286 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER MID | Heating | Sensible | 6720.26 | 0.15633 | 0.15633 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7693.54 | 0.45391 | 0.45391 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER TOP | Heating | Sensible | 672.03 | 1.56328E-002 | 1.56328E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.79447 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.24285 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36279 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35300 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.85073 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96743 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05020E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.59993E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.85073 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18288.14279 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.59993E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 368.67460 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 49.12145 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38721 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36700 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.02757 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.83956E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.09427E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.02757 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 353694.57531 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.09427E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7902.99403 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.78378 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.39760 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.38400 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.83697 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.58243E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.38958E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.86427 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 61606.24461 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.38958E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1627.95642 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78369 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30474 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29600 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23197 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81264 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.25025E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.74213E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23197 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5420.54121 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.74213E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 126.48397 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88194 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17451 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17639 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46536 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18328E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.60037E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17639 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4115.43909 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.60037E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 95.98989 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05901 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22552 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21900 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23192 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60138 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.68944E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.23675E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23192 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7128.98360 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.23675E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 182.55670 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.14172 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13480 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22834 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35947 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.82638E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.73123E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.22834 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3121.96372 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.73123E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 65.40990 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.19686 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33184 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31500 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.26701 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88491 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14814E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.24372E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.31615 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 142164.54562 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.24372E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3751.08107 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.05348 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.81070 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45332 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.24124E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.33933E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.89431 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 95323.67744 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.33933E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2515.06042 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.11064 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23621 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22400 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.26478 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62990 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61295E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.24962E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.33669 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 142839.45982 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.24962E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3768.87005 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.59987 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16032 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.91997 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42752 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.37650E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.36217E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.55448 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 84154.17159 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.36217E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2220.63169 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82417 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28977 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23077 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77272 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.31483E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.71300E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.59492 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19580.62070 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.71300E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 516.46785 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90388 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17027 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18078 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45406 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.23761E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.13540E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39434 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12978.30903 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.13540E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 342.31193 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.11328 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21453 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20700 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23045 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57207 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.77602E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.71996E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.59734 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19660.24504 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.71996E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 518.56589 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03331 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14894 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20666 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39718 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55802E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.06340E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36929 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12155.30732 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06340E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 320.62375 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46842 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.46286 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45391 |
215 | ZoneHVAC:IdealLoadsAirSystem | AIRLOOP DATACENTER BASEMENT | Design Size Maximum Heating Air Flow Rate [m3/s] | 0.33840 |
216 | ZoneHVAC:IdealLoadsAirSystem | AIRLOOP DATACENTER BASEMENT | Design Size Maximum Cooling Air Flow Rate [m3/s] | 21.55077 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.55460 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.71935 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.10920 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.71935 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.34795 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.34795 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32575 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 42.54114 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 26.29003 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 85.08228 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 26.29003 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 77.02633 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 77.02633 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34131 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.32921 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.68563 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.65842 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.82016 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.14882 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.14882 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.46880 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.79447 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.79447 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.79447 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 4.79447 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.79447 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 4.79447 |
247 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46842 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46842 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46842 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46842 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46842 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.46842 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
257 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.46286 |
258 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.46286 |
259 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.46286 |
260 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.46286 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.46286 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.46286 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
265 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45391 |
266 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45391 |
267 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45391 |
268 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45391 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45391 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45391 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
273 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.34795 |
274 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 77.02633 |
275 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.14882 |
276 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 4.79447 |
277 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.46842 |
278 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.46286 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45391 |
280 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.34795 |
281 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.34532 |
282 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
283 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00903 |
284 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.68380E-003 |
285 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 159045.75708 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.76617E-003 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.34795 |
289 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 26766.08982 |
290 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.34161E-004 |
291 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 460.12793 |
292 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.34795 |
293 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.76617E-003 |
294 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.03781E-005 |
295 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.34161E-004 |
296 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 77.02633 |
297 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.63717 |
298 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
299 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00902 |
300 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.68345E-003 |
301 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1494554.74283 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.35818E-002 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 77.02633 |
305 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 246969.93463 |
306 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.16060E-003 |
307 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 4245.58702 |
308 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 77.02633 |
309 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.35818E-002 |
310 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.48941E-006 |
311 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.16060E-003 |
312 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.14882 |
313 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.27300 |
314 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
315 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00900 |
316 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.67607E-003 |
317 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 154351.22750 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.56646E-003 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.14882 |
321 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 26127.59652 |
322 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.28576E-004 |
323 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 449.15178 |
324 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.14882 |
325 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.56646E-003 |
326 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.25186E-005 |
327 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.28576E-004 |
328 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.79447 |
329 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.70977 |
330 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
331 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.39506 |
332 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.84385E-003 |
333 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
334 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 87746.80960 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.73295E-003 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 4.79447 |
337 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 222325.21310 |
338 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.94500E-003 |
339 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5042.55937 |
340 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 4.79447 |
341 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.73295E-003 |
342 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.27564E-004 |
343 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.94500E-003 |
344 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46842 |
345 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46842 |
346 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9065.96831 |
347 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6522.45946 |
348 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.22025E-004 |
349 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46842 |
350 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46842 |
351 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46842 |
352 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46842 |
353 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9065.96831 |
354 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9065.96831 |
355 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 672.02623 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
357 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46842 |
358 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46842 |
359 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9065.96831 |
360 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.22025E-004 |
361 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 672.02623 |
362 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.46286 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.46286 |
364 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 86435.80568 |
365 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 62161.75310 |
366 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.11681E-003 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.46286 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.46286 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.46286 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.46286 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 86435.80568 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 86435.80568 |
373 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6720.26231 |
374 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
375 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.46286 |
376 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.46286 |
377 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 86435.80568 |
378 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.11681E-003 |
379 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6720.26231 |
380 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45391 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45391 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 8789.20740 |
383 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6321.74715 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.15247E-004 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45391 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45391 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45391 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45391 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 8789.20740 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 8789.20740 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 672.02623 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
393 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45391 |
394 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45391 |
395 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 8789.20740 |
396 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.15247E-004 |
397 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 672.02623 |
398 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 8.06474E-002 |
399 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 16453.90066 |
400 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 8.06474E-002 |
401 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 9.67769 |
402 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 8.06474E-002 |
403 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 8.06474E-002 |
404 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 338517.59589 |
405 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
406 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.31613E-002 |
407 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.57936 |
408 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.31613E-002 |
409 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3924.37142 |
410 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
411 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1504421.06099 |
412 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1504421.06000 |
413 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.31613E-002 |
414 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 8.06474E-002 |
415 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 9.67769 |
416 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 8.06474E-002 |
417 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 11391.59045 |
418 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.06474E-002 |
419 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.08088E-002 |
420 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 960324.67046 |
421 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 966170.08000 |
422 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 4.89828E-002 |
423 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.06474E-002 |
424 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.08088E-002 |
425 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 960324.67046 |
426 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 966170.08000 |
427 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 4.89828E-002 |
428 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 2.55408E-003 |
429 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 0.30649 |
430 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 2.55408E-003 |
431 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 644.96829 |
432 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 2.55408E-003 |
433 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 35644.39112 |
434 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 24144.71459 |
435 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 17822.19556 |
436 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 1996.19659 |
437 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 5960.75981 |
438 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 105206.17593 |
439 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 105206.18000 |
440 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 2.55408E-003 |
441 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
442 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
443 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
444 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
445 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
446 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 9.79655E-002 |
447 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 11.75586 |
448 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 9.79655E-002 |
449 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 29212.95475 |
450 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 37.89906 |
451 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1147124.86878 |
452 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 7.57981 |
453 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 143390.60860 |
454 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 37.89906 |
455 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1147124.86878 |
456 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 7.57981 |
457 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 143390.60860 |
458 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 4.96625E-002 |
459 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 4.96625E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17340.96 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 335195.46 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 58391.18 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5135.74 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3899.21 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6751.39 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2959.76 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 134707.68 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 90323.05 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 135347.07 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 79741.31 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 18552.39 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12296.71 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 18627.82 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11517.06 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 22464.16 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 207276.15 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 21928.29 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 180157.96 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 196690.71 | 137725.34 | 58965.37 | 0.70 | 20361.89 | 206.52 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 1828423.52 | 1276884.40 | 551539.12 | 0.70 | 188872.95 | 1915.65 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 191520.09 | 134222.69 | 57297.40 | 0.70 | 19837.39 | 201.20 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 109682.99 | 77454.17 | 32228.82 | 0.71 | 11186.80 | 113.46 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 7.08 | 24.14 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 7.08 | 24.14 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.498 | 1.223 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_NORTH_0.25 | N/A | 2.408 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_NORTH_0.25 | N/A | 2.408 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_NORTH_0.25 | N/A | 2.408 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_NORTH_0.25 | N/A | 2.408 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_NORTH_0.25 | N/A | 2.408 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.498 | 1.223 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_EAST_0.25 | N/A | 2.408 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_EAST_0.25 | N/A | 2.408 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_EAST_0.25 | N/A | 2.408 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.498 | 1.223 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | N/A | 2.408 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | N/A | 2.408 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | N/A | 2.408 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | N/A | 2.408 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | N/A | 2.408 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.498 | 1.223 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_WEST_0.25 | N/A | 2.408 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_WEST_0.25 | N/A | 2.408 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_WEST_0.25 | N/A | 2.408 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.416 | 1.168 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_NORTH_0.25 | N/A | 2.408 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.416 | 1.168 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_EAST_0.25 | N/A | 2.408 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.416 | 1.168 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | N/A | 2.408 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.416 | 1.168 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_WEST_0.25 | N/A | 2.408 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.867 | 1.459 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_NORTH_0.25 | N/A | 2.408 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.867 | 1.459 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_EAST_0.25 | N/A | 2.408 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.867 | 1.459 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | N/A | 2.408 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.867 | 1.459 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_WEST_0.25 | N/A | 2.408 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.498 | 1.223 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.498 | 1.223 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.498 | 1.223 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.498 | 1.223 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.416 | 1.168 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.416 | 1.168 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.416 | 1.168 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.416 | 1.168 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.867 | 1.459 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.867 | 1.459 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.867 | 1.459 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.867 | 1.459 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.3477606683 | 0.2783873140 | Pass | Pass | 0.6549334242 | 0.6214595784 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.0559918061E-003 | 5.9437036376E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.5166025323E-003 | 6.0150504802E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.3568194072E-002 | 9.7047992762E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.9148896255E-002 | 1.7006682486E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.8217992114E-002 | 8.4781666496E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 5.8517458697E-002 | 7.1432690263E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.0757242845E-002 | 3.1944689043E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.0424890006E-002 | 1.7728206158E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.9392068630E-002 | 8.6872259638E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.1421093539E-002 | 7.1340988560E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.2291299355E-002 | 3.0466500272E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.5266047026E-002 | 1.8920423477E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.9762552415E-002 | 8.2864851495E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.3940520859E-002 | 6.9558651948E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.7373175221E-002 | 3.1191576894E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.7437852046E-003 | 4.3640656010E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.7188511370E-003 | 5.7931840438E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.3431199282E-002 | 3.2123597499E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.9370698632E-006 | 6.7333236919E-006 | Pass | Pass | 2.1859917811E-003 | 1.7431169666E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.0289325688E-006 | 5.2745226075E-006 | Pass | Pass | 1.5850410520E-002 | 9.3006921996E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.2192152963E-002 | 9.5967687564E-003 | Pass | Pass | 4.5751374411E-003 | 3.3325621789E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.3684757859E-015 | 2.5809866502E-015 | Pass | Pass | 4.2881137509E-005 | 1.0431406329E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6689.70 | 82.59 | 0.00 | 18861.89 | 8206.07 | 33840.26 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.223 | 1.498 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.223 | 1.498 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.223 | 1.498 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.223 | 1.498 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.168 | 1.416 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.168 | 1.416 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.168 | 1.416 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.168 | 1.416 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.459 | 1.867 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.459 | 1.867 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.459 | 1.867 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.459 | 1.867 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.223 | 1.498 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.223 | 1.498 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.223 | 1.498 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.223 | 1.498 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.168 | 1.416 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.168 | 1.416 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.168 | 1.416 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.168 | 1.416 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.459 | 1.867 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.459 | 1.867 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.459 | 1.867 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.459 | 1.867 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.4237_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.4237_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.4237_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.4237_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.4237_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.4237_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.4237_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.4237_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.4237_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.4237_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.4237_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.4237_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.408 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.4237_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.408 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.408 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.4237_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.408 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.4237_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.408 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.4237_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.408 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.408 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.4237_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.408 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.408 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 1043.06 | 2.408 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.408 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.8895 | 2779.43 | 16369.36 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 135.58 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8895 | 2496.12 | 14700.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 121.76 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8895 | 24961.20 | 147008.37 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 1217.57 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8895 | 2496.12 | 14700.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 121.76 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8895 | 313.41 | 1845.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.09 | 0.0000 | Y | 9.04 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.85 | 0.0000 | Y | 5.77 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8895 | 313.42 | 1845.88 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.49 | 0.0000 | Y | 8.83 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.79 | 0.0000 | Y | 5.76 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8895 | 3134.13 | 18458.37 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.09 | 0.0000 | Y | 90.39 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8895 | 2019.75 | 11895.27 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.84 | 0.0000 | Y | 57.70 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8895 | 3134.20 | 18458.77 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.50 | 0.0000 | Y | 88.35 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8895 | 2019.75 | 11895.27 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.78 | 0.0000 | Y | 57.57 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8895 | 313.41 | 1845.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.09 | 0.0000 | Y | 9.04 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.84 | 0.0000 | Y | 5.77 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8895 | 313.42 | 1845.88 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.50 | 0.0000 | Y | 8.84 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.78 | 0.0000 | Y | 5.76 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.8895 | 783.68 | 4615.46 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 38.23 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 8.8011 | 36.20 | 318.62 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.26 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 8.8011 | 362.03 | 3186.24 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 32.64 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 8.8011 | 36.20 | 318.62 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.26 |
Interior Lighting Total | 5.9168 | 46320.38 | 274067.57 | 637.07 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.05 | AstronomicalClock | - | 42.14 | 42.14 | 78.90 | |
EXTERIOR_LIGHTS_B | 991.40 | AstronomicalClock | - | 83.75 | 62.95 | 11.71 | |
EXTERIOR_LIGHTS_C | 26646.63 | AstronomicalClock | - | 83.75 | 46.20 | 231.11 | |
Exterior Lighting Total | 37611.08 | 321.73 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 1891338.99 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1504421.06 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 966170.08 | 5.33 | 955290.50 | 4.98 | 7.08 | 24.14 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 966170.08 | 5.33 | 955290.50 | 4.98 | 7.08 | 24.14 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 148548.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 105206.18 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1147124.87 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1147124.87 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 159045.76 | 196690.71 | 137725.34 | 58965.37 | 0.70 | - | 20361.89 | 206.52 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1494554.74 | 1828423.52 | 1276884.40 | 551539.12 | 0.70 | - | 188872.95 | 1915.65 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 154351.23 | 191520.09 | 134222.69 | 57297.40 | 0.70 | - | 19837.39 | 201.20 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 87746.81 | 109682.99 | 77454.17 | 32228.82 | 0.71 | - | 11186.80 | 113.46 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9065.97 | 6522.46 | 2543.51 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 86435.81 | 62161.75 | 24274.05 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 8789.21 | 6321.75 | 2467.46 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18288.14 | 17340.96 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 353694.58 | 335195.46 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 61606.24 | 58391.18 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 5420.54 | 5135.74 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 4115.44 | 3899.21 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 7128.98 | 6751.39 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3121.96 | 2959.76 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 142164.55 | 134707.68 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 95323.68 | 90323.05 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 142839.46 | 135347.07 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 84154.17 | 79741.31 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 19580.62 | 18552.39 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12978.31 | 12296.71 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19660.25 | 18627.82 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12155.31 | 11517.06 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 26766.09 | 22464.16 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 246969.93 | 207276.15 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 26127.60 | 21928.29 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 222325.21 | 180157.96 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9065.97 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 86435.81 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 8789.21 | 0.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 672.03 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6720.26 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 672.03 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.35 | 18039.49 | 2160.95 | 1.00 | 1.12 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 77.03 | 166449.81 | 2160.95 | 1.00 | 1.08 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.15 | 17609.16 | 2160.95 | 1.00 | 1.13 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 4.79 | 8129.76 | 1695.65 | 1.00 | 1.17 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 524.68 | 1120.11 | 1.00 | 1.64 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.46 | 4998.89 | 1120.11 | 1.00 | 1.16 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 508.43 | 1120.11 | 1.00 | 1.65 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.080647 | 16453.90 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.013161 | 3924.37 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.080647 | 11391.59 | 141251.81 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.002554 | 644.97 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.097966 | 29212.95 | 298196.27 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 65393.21 | 65393.21 | 23.53 | 4.794 | 4.794 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00904 | 24.71 | 0.00822 | 1.200 | 0.00 |
CORE_BOTTOM | 71501.76 | 71501.76 | 28.65 | 5.243 | 5.243 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 24.71 | 0.00822 | 1.078 | 0.00 |
CORE_MID | 670123.94 | 670123.94 | 268.47 | 49.121 | 49.121 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00897 | 24.71 | 0.00822 | 10.778 | 0.00 |
CORE_TOP | 65265.76 | 65265.76 | 26.15 | 4.784 | 4.784 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00898 | 24.71 | 0.00822 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 10585.87 | 10585.87 | 33.78 | 0.784 | 0.784 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00884 | 31.30 | 0.00823 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 12000.56 | 12000.56 | 59.42 | 0.882 | 0.882 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00870 | 24.71 | 0.00822 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 14304.90 | 14304.90 | 45.64 | 1.059 | 1.059 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 24.00 | 24.00 | 0.00876 | 30.86 | 0.00823 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 15422.20 | 15422.20 | 76.36 | 1.142 | 1.142 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00865 | 30.41 | 0.00823 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 97214.23 | 97214.23 | 310.18 | 7.197 | 7.197 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00885 | 31.30 | 0.00823 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 122294.08 | 122294.08 | 605.49 | 9.053 | 9.053 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 24.00 | 24.00 | 0.00868 | 25.28 | 0.00822 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 136573.48 | 136573.48 | 435.75 | 10.111 | 10.111 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00875 | 30.93 | 0.00823 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 129674.59 | 129674.59 | 642.03 | 9.600 | 9.600 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 24.00 | 24.00 | 0.00867 | 30.29 | 0.00823 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 11132.84 | 11132.84 | 35.52 | 0.824 | 0.824 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00880 | 31.30 | 0.00823 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 12209.64 | 12209.64 | 60.45 | 0.904 | 0.904 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00868 | 26.66 | 0.00823 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15038.08 | 15038.08 | 47.98 | 1.113 | 1.113 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00872 | 31.08 | 0.00823 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 13957.98 | 13957.98 | 69.11 | 1.033 | 1.033 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00866 | 30.41 | 0.00823 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8022.01 | 8022.01 | 221.59 | 0.468 | 0.468 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 27.00 | 27.00 | 0.00859 | 28.94 | 0.00823 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 76428.73 | 76428.73 | 2111.13 | 4.463 | 4.463 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 27.00 | 27.00 | 0.00859 | 28.94 | 0.00823 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7773.54 | 7773.54 | 214.72 | 0.454 | 0.454 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 27.00 | 27.00 | 0.00859 | 29.16 | 0.00823 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 369078.45 | 369078.45 | 470.96 | 21.551 | 21.551 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 23.20 | 0.00822 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 24.87 | 0.00506 | 3.80 | 0.00506 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 22.70 | 0.00506 | 3.80 | 0.00506 | 1.078 | 0.00 | |
CORE_MID | 175553.30 | 175553.30 | 70.33 | 7.484 | 10.778 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 10.778 | 0.00 |
CORE_TOP | 43184.28 | 43184.28 | 17.30 | 1.864 | 1.864 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 3133.29 | 3133.29 | 10.00 | 0.134 | 0.135 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00689 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 2375.86 | 2375.86 | 11.76 | 0.102 | 0.102 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00702 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 4840.75 | 4840.75 | 15.44 | 0.209 | 0.209 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00724 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 872.65 | 872.65 | 4.32 | 0.038 | 0.087 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00633 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 99556.47 | 99556.47 | 317.65 | 4.316 | 4.316 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00755 | 3.80 | 0.00506 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 66750.66 | 66750.66 | 330.49 | 2.894 | 2.894 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00757 | 3.80 | 0.00506 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 100028.33 | 100028.33 | 319.15 | 4.337 | 4.337 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00755 | 3.80 | 0.00506 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 58941.41 | 58941.41 | 291.83 | 2.554 | 2.554 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00746 | 3.80 | 0.00506 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13705.91 | 13705.91 | 43.73 | 0.595 | 0.595 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00770 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 9084.19 | 9084.19 | 44.98 | 0.394 | 0.394 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 13761.57 | 13761.57 | 43.91 | 0.597 | 0.597 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00770 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 8508.89 | 8508.89 | 42.13 | 0.369 | 0.369 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00767 | 3.80 | 0.00506 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 3.80 | 0.00506 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 25.03 | 0.00820 | 3.80 | 0.00506 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.04 | 0.00534 | 3.80 | 0.00506 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 3.80 | 0.00506 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 8.35 | 8.35 | 1.61 | 1.61 | 8.3480 | 2.7194 | 8.3480 | 0.3258 | 0.3000 |
VAV_MID WITH REHEAT | 77.03 | 77.03 | 24.88 | 24.88 | 77.0263 | 26.2900 | 77.0263 | 0.3413 | 0.3000 |
VAV_TOP WITH REHEAT | 8.15 | 8.15 | 3.82 | 3.82 | 8.1488 | 3.8202 | 8.1488 | 0.4688 | 0.3000 |
CAV_BAS | 4.79 | 4.79 | 1.20 | 1.20 | 4.7945 | 4.7945 | 4.7945 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.47 | 0.47 | 0.02 | 0.02 | 0.4684 | 0.4684 | 0.4684 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.46 | 4.46 | 0.16 | 0.16 | 4.4629 | 4.4629 | 4.4629 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.45 | 0.45 | 0.02 | 0.02 | 0.4539 | 0.4539 | 0.4539 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18288.143 | 18288.143 | 1.850727 | 0.00015999 | 368.675 | 12/21 00:10:00 | 12/21 00:10:00 | 18288.14 | 18288.14 | 1.850727 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 18355.58 | 18355.58 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 353694.575 | 353694.575 | 18.027571 | 0.00309427 | 7902.994 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 353694.58 | 353694.58 | 18.027571 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 175553.30 | 0.00 | 354907.29 | 354907.29 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 61606.245 | 61606.245 | 1.864269 | 0.00053896 | 1627.956 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 61606.24 | 61606.24 | 1.864269 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 43184.28 | 0.00 | 61831.59 | 61831.59 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5420.541 | 5420.541 | 0.231971 | 0.00004742 | 126.484 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5420.54 | 5420.54 | 0.231971 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00688633 | 43.7708 | 3133.29 | 0.00 | 5438.38 | 5438.38 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4115.439 | 4115.439 | 0.176387 | 0.00003600 | 95.990 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4115.44 | 4115.44 | 0.176387 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00701548 | 44.5828 | 2375.86 | 0.00 | 4128.98 | 4128.98 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 7128.984 | 7128.984 | 0.231923 | 0.00006237 | 182.557 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7128.98 | 7128.98 | 0.231923 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00723939 | 45.9893 | 4840.75 | 0.00 | 7150.94 | 7150.94 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3121.964 | 3121.964 | 0.228343 | 0.00002731 | 65.410 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3121.96 | 3121.96 | 0.228343 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00632664 | 40.2479 | 872.65 | 0.00 | 3133.26 | 3133.26 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 142164.546 | 142164.546 | 4.316155 | 0.00124372 | 3751.081 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 142164.55 | 142164.55 | 4.316155 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00754926 | 47.9346 | 99556.47 | 0.00 | 142644.12 | 142644.12 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 95323.677 | 95323.677 | 2.894308 | 0.00083393 | 2515.060 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 95323.68 | 95323.68 | 2.894308 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00756838 | 48.0545 | 66750.66 | 0.00 | 95644.51 | 95644.51 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 142839.460 | 142839.460 | 4.336693 | 0.00124962 | 3768.870 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 142839.46 | 142839.46 | 4.336693 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00755280 | 47.9568 | 100028.33 | 0.00 | 143321.18 | 143321.18 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 84154.172 | 84154.172 | 2.554485 | 0.00073622 | 2220.632 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 84154.17 | 84154.17 | 2.554485 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00746219 | 47.3888 | 58941.41 | 0.00 | 84439.37 | 84439.37 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 19580.621 | 19580.621 | 0.594917 | 0.00017130 | 516.468 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19580.62 | 19580.62 | 0.594917 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00770262 | 48.8957 | 13705.91 | 0.00 | 19645.40 | 19645.40 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 12978.309 | 12978.309 | 0.394345 | 0.00011354 | 342.312 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12978.31 | 12978.31 | 0.394345 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00770633 | 48.9189 | 9084.19 | 0.00 | 13021.18 | 13021.18 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 19660.245 | 19660.245 | 0.597341 | 0.00017200 | 518.566 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19660.25 | 19660.25 | 0.597341 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00770443 | 48.9070 | 13761.57 | 0.00 | 19725.28 | 19725.28 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12155.307 | 12155.307 | 0.369290 | 0.00010634 | 320.624 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12155.31 | 12155.31 | 0.369290 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00767017 | 48.6925 | 8508.89 | 0.00 | 12195.59 | 12195.59 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 159045.757 | -999.000 | 8.347954 | 0.00676617 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 159045.76 | 154330.84 | 8.347954 | 26.35 | 17.17 | 0.00868380 | 11.01 | 11.01 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 30.4049 | 24.00 | 0.00889706 | 46.9770 | 106677.71 | 0.00 | 161309.44 | 145887.99 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 26766.090 | 26766.090 | 2.504386 | 0.00023416 | 460.128 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26766.09 | 26766.09 | 2.504386 | 3.80 | 3.80 | 0.00505843 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 101.3498 | 21.87 | 0.00598235 | 36.1098 | 11222.55 | 0.00 | 27193.54 | 27193.54 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1494554.743 | -999.000 | 77.026334 | 0.06358181 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1494554.74 | 1451138.23 | 77.026334 | 26.64 | 17.26 | 0.00868345 | 11.01 | 11.01 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 32.9523 | 24.00 | 0.00893805 | 47.1903 | 948778.41 | 0.00 | 1515608.51 | 1372957.85 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 246969.935 | 246969.935 | 23.107900 | 0.00216060 | 4245.587 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 246969.93 | 246969.93 | 23.107900 | 3.80 | 3.80 | 0.00505843 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 109.8410 | 21.00 | 0.00769851 | 48.8692 | 500830.16 | 0.00 | 250913.96 | 250913.96 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 154351.228 | -999.000 | 8.148818 | 0.00656646 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 154351.23 | 149941.97 | 8.148818 | 26.27 | 17.13 | 0.00867607 | 11.01 | 11.01 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 31.1480 | 24.00 | 0.00887629 | 46.8688 | 110071.91 | 0.00 | 156555.07 | 141686.23 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 26127.597 | 26127.597 | 2.444645 | 0.00022858 | 449.152 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26127.60 | 26127.60 | 2.444645 | 3.80 | 3.80 | 0.00505843 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 103.8265 | 21.00 | 0.00781414 | 49.5929 | 58050.93 | 0.00 | 26544.85 | 26544.85 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 87746.810 | -999.000 | 4.794468 | 0.00373295 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 87746.81 | 82807.32 | 4.794468 | 25.71 | 17.08 | 0.00884385 | 11.40 | 11.35 | 0.00850000 | 30.14 | 0.00823165 | 18.07 | 25.0328 | 24.00 | 0.00908014 | 47.9302 | 59482.47 | 0.00 | 89033.15 | 79006.08 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 222325.213 | 222325.213 | 4.794468 | 0.00194500 | 5042.559 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 222325.21 | 222325.21 | 4.794468 | 0.95 | 0.95 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 25.0328 | 24.87 | 0.00505843 | 25.5017 | 0.00 | 0.00 | 190571.29 | 190571.29 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9065.968 | 6522.459 | 0.468421 | 0.00022202 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 8396.98 | 8299.93 | -999.0 | 28.03 | 17.65 | 0.00857816 | 12.80 | 11.93 | 0.00850000 | 29.16 | 0.00823009 | 17.74 | -999.0000 | 27.00 | 0.00859018 | 37.9738 | 8020.39 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 86435.806 | 62161.753 | 4.462863 | 0.00211681 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 80066.80 | 79098.06 | -999.0 | 28.04 | 17.65 | 0.00858188 | 12.80 | 11.93 | 0.00850000 | 29.16 | 0.00823009 | 17.74 | -999.0000 | 27.00 | 0.00859465 | 37.9936 | 76401.56 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8789.207 | 6321.747 | 0.453915 | 0.00021525 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 8141.25 | 8044.26 | -999.0 | 28.04 | 17.65 | 0.00858060 | 12.80 | 11.93 | 0.00850000 | 29.16 | 0.00823009 | 17.74 | -999.0000 | 27.00 | 0.00859310 | 37.9867 | 7773.54 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9065.968 | 9065.968 | 0.468421 | 0.00022202 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9065.97 | 9065.97 | 0.468421 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.3373 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 86435.806 | 86435.806 | 4.462863 | 0.00211681 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 86435.81 | 86435.81 | 4.462863 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.5029 | 25.03 | 0.00819560 | 40.7264 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8789.207 | 8789.207 | 0.453915 | 0.00021525 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8789.21 | 8789.21 | 0.453915 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.4440 | 24.04 | 0.00533924 | 28.2868 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 672.026 | 672.026 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 672.03 | 672.03 | 0.468421 | 0.13 | 0.13 | 0.00838514 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.3373 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6720.262 | 6720.262 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6720.26 | 6720.26 | 4.462863 | 0.13 | 0.13 | 0.00808571 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.5029 | 25.03 | 0.00819560 | 40.7264 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 672.026 | 672.026 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 672.03 | 672.03 | 0.453915 | 0.13 | 0.13 | 0.00532957 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.4440 | 24.04 | 0.00533924 | 28.2868 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18288.143 | 18288.143 | 1.850727 | 0.00015999 | 368.675 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 1.1916 | 1.215627 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 18288.14 | 18288.14 | 1.0000 | 2.18714911 | 1.850727 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.15997633 | 60.00 | 32.22 | 27.78 | 0.000 | 18288.14 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 18355.58 | 18355.58 | 2.18714911 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 353694.575 | 353694.575 | 18.027571 | 0.00309427 | 7902.994 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 23.0465 | 23.510345 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 353694.58 | 353694.58 | 1.0000 | 21.30459819 | 18.027571 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 3.09395879 | 60.00 | 32.22 | 27.78 | 0.000 | 353694.58 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 175553.30 | 0.00 | 354907.29 | 354907.29 | 21.30459819 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.14 | 17.75 | 0.00800000 | 49718.5 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 61606.245 | 61606.245 | 1.864269 | 0.00053896 | 1627.956 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 4.0142 | 4.095013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 61606.24 | 61606.24 | 1.0000 | 2.20315379 | 1.864269 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.53890332 | 60.00 | 32.22 | 27.78 | 0.000 | 61606.24 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 43184.28 | 0.00 | 61831.59 | 61831.59 | 2.20315379 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.32 | 21.28 | 0.00800000 | 61124.9 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5420.541 | 5420.541 | 0.231971 | 0.00004742 | 126.484 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 0.3532 | 0.360307 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5420.54 | 5420.54 | 1.0000 | 0.27413847 | 0.231971 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.04741642 | 60.00 | 32.22 | 27.78 | 0.000 | 5420.54 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.87 | 0.00688633 | 21.00 | 0.00688633 | 43.7708 | 3133.29 | 0.00 | 5438.38 | 5438.38 | 0.27413847 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.25 | 18.78 | 0.00800000 | 52897.9 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4115.439 | 4115.439 | 0.176387 | 0.00003600 | 95.990 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 0.2682 | 0.273556 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4115.44 | 4115.44 | 1.0000 | 0.20845070 | 0.176387 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.03599998 | 60.00 | 32.22 | 27.78 | 0.000 | 4115.44 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.87 | 0.00701548 | 21.00 | 0.00701548 | 44.5828 | 2375.86 | 0.00 | 4128.98 | 4128.98 | 0.20845070 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.23 | 18.77 | 0.00800000 | 52867.8 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7128.984 | 7128.984 | 0.231923 | 0.00006237 | 182.557 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 0.4645 | 0.473869 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7128.98 | 7128.98 | 1.0000 | 0.27408137 | 0.231923 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.06236110 | 60.00 | 32.22 | 27.78 | 0.000 | 7128.98 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.86 | 0.00723939 | 21.00 | 0.00723939 | 45.9893 | 4840.75 | 0.00 | 7150.94 | 7150.94 | 0.27408137 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 38.39 | 20.70 | 0.00800000 | 59150.4 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3121.964 | 3121.964 | 0.228343 | 0.00002731 | 65.410 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 0.2034 | 0.207519 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 3121.96 | 3121.96 | 1.0000 | 0.26985098 | 0.228343 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.02730951 | 60.00 | 32.22 | 27.78 | 0.000 | 3121.96 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.92 | 0.00632664 | 21.00 | 0.00632664 | 40.2479 | 872.65 | 0.00 | 3133.26 | 3133.26 | 0.26985098 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 24.19 | 16.02 | 0.00800000 | 44670.9 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 142164.546 | 142164.546 | 4.316155 | 0.00124372 | 3751.081 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 9.2634 | 9.449784 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 142164.55 | 142164.55 | 1.0000 | 5.10073948 | 4.316155 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 1.24359059 | 60.00 | 32.22 | 27.78 | 0.000 | 142164.55 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00754926 | 21.00 | 0.00754926 | 47.9346 | 99556.47 | 0.00 | 142644.12 | 142644.12 | 5.10073948 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61025.2 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 95323.677 | 95323.677 | 2.894308 | 0.00083393 | 2515.060 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 6.2112 | 6.336237 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 95323.68 | 95323.68 | 1.0000 | 3.42043131 | 2.894308 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.83384804 | 60.00 | 32.22 | 27.78 | 0.000 | 95323.68 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00756838 | 21.00 | 0.00756838 | 48.0545 | 66750.66 | 0.00 | 95644.51 | 95644.51 | 3.42043131 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61022.5 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 142839.460 | 142839.460 | 4.336693 | 0.00124962 | 3768.870 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 9.3073 | 9.494646 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 142839.46 | 142839.46 | 1.0000 | 5.12501111 | 4.336693 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 1.24949443 | 60.00 | 32.22 | 27.78 | 0.000 | 142839.46 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00755280 | 21.00 | 0.00755280 | 47.9568 | 100028.33 | 0.00 | 143321.18 | 143321.18 | 5.12501111 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61024.9 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 84154.172 | 84154.172 | 2.554485 | 0.00073622 | 2220.632 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 5.4834 | 5.593791 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 84154.17 | 84154.17 | 1.0000 | 3.01883573 | 2.554485 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.73614230 | 60.00 | 32.22 | 27.78 | 0.000 | 84154.17 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00746219 | 21.00 | 0.00746219 | 47.3888 | 58941.41 | 0.00 | 84439.37 | 84439.37 | 3.01883573 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61030.7 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19580.621 | 19580.621 | 0.594917 | 0.00017130 | 516.468 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 1.2759 | 1.301539 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19580.62 | 19580.62 | 1.0000 | 0.70305986 | 0.594917 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.17128234 | 60.00 | 32.22 | 27.78 | 0.000 | 19580.62 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00770262 | 21.00 | 0.00770262 | 48.8957 | 13705.91 | 0.00 | 19645.40 | 19645.40 | 0.70305986 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61002.5 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12978.309 | 12978.309 | 0.394345 | 0.00011354 | 342.312 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 0.8457 | 0.862678 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12978.31 | 12978.31 | 1.0000 | 0.46602817 | 0.394345 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.11352833 | 60.00 | 32.22 | 27.78 | 0.000 | 12978.31 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00770633 | 21.00 | 0.00770633 | 48.9189 | 9084.19 | 0.00 | 13021.18 | 13021.18 | 0.46602817 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61000.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19660.245 | 19660.245 | 0.597341 | 0.00017200 | 518.566 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 1.2810 | 1.306831 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19660.25 | 19660.25 | 1.0000 | 0.70592530 | 0.597341 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.17197885 | 60.00 | 32.22 | 27.78 | 0.000 | 19660.25 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00770443 | 21.00 | 0.00770443 | 48.9070 | 13761.57 | 0.00 | 19725.28 | 19725.28 | 0.70592530 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61002.3 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12155.307 | 12155.307 | 0.369290 | 0.00010634 | 320.624 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 0.7920 | 0.807972 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12155.31 | 12155.31 | 1.0000 | 0.43641894 | 0.369290 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.10632908 | 60.00 | 32.22 | 27.78 | 0.000 | 12155.31 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00767017 | 21.00 | 0.00767017 | 48.6925 | 8508.89 | 0.00 | 12195.59 | 12195.59 | 0.43641894 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61004.5 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 159045.757 | -999.000 | 8.347954 | 0.00676617 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9827 | 1004.8586 | 1.1818 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.347954 | 9.86543451 | 4197.9300 | 999.8980 | 80.63917119 | 12.27 | 6.67 | 5.60 | 1895698.54 | 8.3898 | 8.389823 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 159045.76 | 154330.84 | 1.0000 | 9.86543451 | 8.347954 | 26.35 | 17.17 | 0.00868380 | 48615.8 | 11.01 | 11.01 | 0.00850000 | 32494.3 | 6.76548395 | 6.67 | 12.27 | 5.60 | 18039.485 | 141006.27 | 31.30 | 0.00823349 | 18.45 | 2.53819000 | 30.4049 | 24.00 | 0.00889706 | 24.00 | 0.00889706 | 46.9770 | 106677.71 | 0.00 | 161309.44 | 145887.99 | 9.86543451 | 26.35 | 17.36 | 0.00868380 | 48615.8 | 11.86 | 11.26 | 0.00806422 | 32264.8 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 26766.090 | 26766.090 | 2.504386 | 0.00023416 | 460.128 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.347954 | 9.86543451 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 1.7441 | 1.779162 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26766.09 | 26766.09 | 1.0000 | 2.95963035 | 2.504386 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.23413754 | 60.00 | 32.22 | 27.78 | 0.000 | 26766.09 | 3.80 | 0.00505843 | 3.80 | 2.53819000 | 101.3498 | 6.91 | 0.00568731 | 21.87 | 0.00598235 | 36.1098 | 11222.55 | 0.00 | 27193.54 | 27193.54 | 2.95963035 | 2.80 | 2.80 | 0.00505843 | 15490.7 | 11.86 | 7.98 | 0.00505843 | 24678.9 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1494554.743 | -999.000 | 77.026334 | 0.06358181 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9821 | 1004.8586 | 1.1818 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 77.026334 | 91.02807810 | 4197.9300 | 999.8980 | 80.63917119 | 12.27 | 6.67 | 5.60 | 1895698.54 | 78.8393 | 78.839262 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 1494554.74 | 1451138.23 | 1.0000 | 91.02807810 | 77.026334 | 26.64 | 17.26 | 0.00868345 | 48912.9 | 11.01 | 11.01 | 0.00850000 | 32494.3 | 63.57532772 | 6.67 | 12.27 | 5.60 | 166449.806 | 1328104.94 | 31.30 | 0.00823349 | 18.45 | 25.38195000 | 32.9523 | 24.00 | 0.00893805 | 24.00 | 0.00893805 | 47.1903 | 948778.41 | 0.00 | 1515608.51 | 1372957.85 | 91.02807810 | 26.64 | 17.46 | 0.00868345 | 48912.9 | 11.86 | 11.26 | 0.00806232 | 32263.0 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 246969.935 | 246969.935 | 23.107900 | 0.00216060 | 4245.587 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 77.026334 | 91.02807810 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 16.0924 | 16.416277 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 246969.93 | 246969.93 | 1.0000 | 27.30842343 | 23.107900 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 2.16038032 | 60.00 | 32.22 | 27.78 | 0.000 | 246969.93 | 3.80 | 0.00505843 | 3.80 | 25.38195000 | 109.8410 | 20.76 | 0.00773843 | 21.00 | 0.00769851 | 48.8692 | 500830.16 | 0.00 | 250913.96 | 250913.96 | 27.30842343 | 2.80 | 2.80 | 0.00505843 | 15490.7 | 11.86 | 7.98 | 0.00505843 | 24678.9 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 154351.228 | -999.000 | 8.148818 | 0.00656646 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9684 | 1004.8586 | 1.1818 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.148818 | 9.63009890 | 4197.9300 | 999.8980 | 80.63917119 | 12.27 | 6.67 | 5.60 | 1895698.54 | 8.1422 | 8.142182 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 154351.23 | 149941.97 | 1.0000 | 9.63009890 | 8.148818 | 26.27 | 17.13 | 0.00867607 | 48522.2 | 11.01 | 11.01 | 0.00850000 | 32494.2 | 6.56578819 | 6.67 | 12.27 | 5.60 | 17609.161 | 136742.07 | 31.30 | 0.00823349 | 18.45 | 2.53819000 | 31.1480 | 24.00 | 0.00887629 | 24.00 | 0.00887629 | 46.8688 | 110071.91 | 0.00 | 156555.07 | 141686.23 | 9.63009890 | 26.27 | 17.33 | 0.00867607 | 48522.2 | 11.86 | 11.26 | 0.00806410 | 32265.4 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 26127.597 | 26127.597 | 2.444645 | 0.00022858 | 449.152 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.148818 | 9.63009890 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 1.7025 | 1.736721 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26127.60 | 26127.60 | 1.0000 | 2.88902967 | 2.444645 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.22855230 | 60.00 | 32.22 | 27.78 | 0.000 | 26127.60 | 3.80 | 0.00505843 | 3.80 | 2.53819000 | 103.8265 | 21.00 | 0.00781414 | 21.00 | 0.00781414 | 49.5929 | 58050.93 | 0.00 | 26544.85 | 26544.85 | 2.88902967 | 2.80 | 2.80 | 0.00505843 | 15490.7 | 11.86 | 7.98 | 0.00505843 | 24678.9 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 87746.810 | -999.000 | 4.794468 | 0.00373295 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2803 | 1004.8586 | 1.1818 | CAV_BAS FAN | Fan:ConstantVolume | 4.794468 | 5.66600042 | 4197.9300 | 999.8980 | 80.63917119 | 12.27 | 6.67 | 5.60 | 1895698.54 | 4.6287 | 4.628732 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 87746.81 | 82807.32 | 1.0000 | 5.66600042 | 4.794468 | 25.71 | 17.08 | 0.00884385 | 48374.8 | 11.40 | 11.35 | 0.00850000 | 32888.3 | 3.73257133 | 6.67 | 12.27 | 5.60 | 8129.761 | 79617.05 | 30.14 | 0.00823165 | 18.07 | 1.20019084 | 25.0328 | 24.00 | 0.00908014 | 24.00 | 0.00908014 | 47.9302 | 59482.47 | 0.00 | 89033.15 | 79006.08 | 5.66600042 | 25.71 | 17.28 | 0.00884385 | 48374.8 | 12.06 | 11.43 | 0.00814252 | 32661.2 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 222325.213 | 222325.213 | 4.794468 | 0.00194500 | 5042.559 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | CAV_BAS FAN | Fan:ConstantVolume | 4.794468 | 5.66600042 | 4197.9300 | 999.8980 | 13.15998914 | 54.44 | 82.22 | 27.78 | 1534698.13 | 14.4866 | 14.778124 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 222325.21 | 222325.21 | 1.0000 | 5.66600042 | 4.794468 | 0.95 | 0.95 | 0.00505843 | 13615.6 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 1.94479954 | 60.00 | 32.22 | 27.78 | 0.000 | 222325.21 | 3.80 | 0.00505843 | 3.80 | 1.20019084 | 25.0328 | 0.00 | 0.00505843 | 24.87 | 0.00505843 | 25.5017 | 0.00 | 0.00 | 190571.29 | 190571.29 | 5.66600042 | 12.80 | 8.42 | 0.00505843 | 25633.1 | 45.96 | 20.81 | 0.00505843 | 59267.3 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9065.968 | 6522.459 | 0.468421 | 0.00022202 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7864 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | Sensible | 8396.98 | 8299.93 | 0.9262 | -999.0 | -999.0 | 28.03 | 17.65 | 0.00857816 | 50070.8 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8396.98 | 29.16 | 0.00823009 | 17.74 | 0.01563279 | -999.0000 | 27.00 | 0.00859018 | 27.00 | 0.00859018 | 37.9738 | 8020.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 86435.806 | 62161.753 | 4.462863 | 0.00211681 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7933 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | Sensible | 80066.80 | 79098.06 | 0.9263 | -999.0 | -999.0 | 28.04 | 17.65 | 0.00858188 | 50083.9 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 80066.80 | 29.16 | 0.00823009 | 17.74 | 0.15632792 | -999.0000 | 27.00 | 0.00859465 | 27.00 | 0.00859465 | 37.9936 | 76401.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 8789.207 | 6321.747 | 0.453915 | 0.00021525 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7909 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | Sensible | 8141.25 | 8044.26 | 0.9263 | -999.0 | -999.0 | 28.04 | 17.65 | 0.00858060 | 50079.4 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8141.25 | 29.16 | 0.00823009 | 17.74 | 0.01563279 | -999.0000 | 27.00 | 0.00859310 | 27.00 | 0.00859310 | 37.9867 | 7773.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9065.968 | 9065.968 | 0.468421 | 0.00022202 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9065.97 | 9065.97 | 1.0000 | 0.55356986 | 0.468421 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9065.97 | 3.80 | 0.00505843 | 3.80 | 0.01563279 | 3.3373 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 86435.806 | 86435.806 | 4.462863 | 0.00211681 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 86435.81 | 86435.81 | 1.0000 | 5.27411646 | 4.462863 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86435.81 | 3.80 | 0.00505843 | 3.80 | 0.15632792 | 3.5029 | 0.00 | 0.00819560 | 25.03 | 0.00819560 | 40.7264 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8789.207 | 8789.207 | 0.453915 | 0.00021525 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 8789.21 | 8789.21 | 1.0000 | 0.53642673 | 0.453915 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8789.21 | 3.80 | 0.00505843 | 3.80 | 0.01563279 | 3.4440 | 0.00 | 0.00533924 | 24.04 | 0.00533924 | 28.2868 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 672.026 | 672.026 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.468421 | 0.55356986 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 672.03 | 672.03 | 1.0000 | 0.55356986 | 0.468421 | 0.13 | 0.13 | 0.00838514 | 21100.1 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 672.03 | 3.80 | 0.00505843 | 3.80 | 0.01563279 | 3.3373 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6720.262 | 6720.262 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.462863 | 5.27411646 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 6720.26 | 6720.26 | 1.0000 | 5.27411646 | 4.462863 | 0.13 | 0.13 | 0.00808571 | 20357.6 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6720.26 | 3.80 | 0.00505843 | 3.80 | 0.15632792 | 3.5029 | 0.00 | 0.00819560 | 25.03 | 0.00819560 | 40.7264 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 672.026 | 672.026 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.453915 | 0.53642673 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 672.03 | 672.03 | 1.0000 | 0.53642673 | 0.453915 | 0.13 | 0.13 | 0.00532957 | 13461.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 672.03 | 3.80 | 0.00505843 | 3.80 | 0.01563279 | 3.4440 | 0.00 | 0.00533924 | 24.04 | 0.00533924 | 28.2868 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 8.35 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 77.03 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 8.15 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.79 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | BASEMENT_DCV | 0.002360 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6_DCV | 0.002360 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6_DCV | 0.002360 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6_DCV | 0.002360 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 4207.67 | 465.83 | 298.50 |
CORE_BOTTOM | 4188.83 | 175.17 | 12.33 |
CORE_MID | 2797.50 | 1325.33 | 20.33 |
CORE_TOP | 2151.67 | 2725.00 | 21.50 |
PERIMETER_BOT_ZN_3 | 2600.83 | 1842.50 | 0.00 |
PERIMETER_BOT_ZN_2 | 2945.00 | 1666.17 | 53.00 |
PERIMETER_BOT_ZN_1 | 3650.67 | 1037.50 | 79.67 |
PERIMETER_BOT_ZN_4 | 4676.17 | 518.33 | 261.83 |
PERIMETER_MID_ZN_3 | 1553.00 | 3521.83 | 36.83 |
PERIMETER_MID_ZN_2 | 1840.00 | 2456.33 | 72.50 |
PERIMETER_MID_ZN_1 | 2946.17 | 1800.67 | 76.67 |
PERIMETER_MID_ZN_4 | 2773.33 | 2395.33 | 104.33 |
PERIMETER_TOP_ZN_3 | 1763.83 | 4007.50 | 452.00 |
PERIMETER_TOP_ZN_2 | 2251.00 | 3202.33 | 226.00 |
PERIMETER_TOP_ZN_1 | 2620.67 | 2479.83 | 159.67 |
PERIMETER_TOP_ZN_4 | 2512.50 | 2997.67 | 261.67 |
DATACENTER_BOT_ZN_6 | 5943.00 | 627.50 | 627.50 |
DATACENTER_MID_ZN_6 | 5943.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 5913.67 | 24.00 | 17.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 77.33 | 0.00 | 7.83 |
CORE_BOTTOM | 0.00 | 1.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 12.33 | 0.00 | 12.33 |
PERIMETER_BOT_ZN_1 | 0.00 | 30.33 | 0.00 | 30.33 |
PERIMETER_BOT_ZN_4 | 0.00 | 106.33 | 0.00 | 48.83 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 10.67 | 0.00 | 10.67 |
PERIMETER_MID_ZN_1 | 0.00 | 32.00 | 0.00 | 31.83 |
PERIMETER_MID_ZN_4 | 0.00 | 22.50 | 0.00 | 17.50 |
PERIMETER_TOP_ZN_3 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 1.50 | 7.67 | 0.00 | 7.67 |
PERIMETER_TOP_ZN_1 | 1.00 | 13.17 | 0.00 | 12.83 |
PERIMETER_TOP_ZN_4 | 0.83 | 22.17 | 0.00 | 16.67 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 2.67 | 283.17 | 0.00 | 152.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 1.624 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 1.240 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.946 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.891 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 1.103 | 0.030 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 1.487 | 0.031 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 1.637 | 0.030 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 2.485 | 0.031 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.846 | 0.070 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 1.204 | 0.075 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 1.407 | 0.070 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 1.493 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.844 | 0.086 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 1.284 | 0.089 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 1.338 | 0.087 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 1.509 | 0.089 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.371 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.371 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.371 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.22 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 0.847 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.95 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.011 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.110 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.011 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 783.68 | 0.239 | ||
Total Facility | 1031.21 | 2493.19 | 126016.35 | 46320.38 | 1.3878 | 157.549 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 66439587.67 | 0.00 | 66439587.67 | 0.00 | 66439587.67 | 29876159.83 | 3804.97 | 403.10 | 4551.93 | 365.94 |
CORE_BOTTOM | 52974810.75 | 0.00 | 52974810.75 | 0.00 | 52974810.75 | 33990283.35 | 3349.43 | 26.29 | 5384.28 | 591.06 |
CORE_MID | 0.38E+09 | 0.00 | 0.38E+09 | 0.00 | 0.38E+09 | 0.34E+09 | 4021.35 | 91.32 | 4647.34 | 89.19 |
CORE_TOP | 35798905.35 | 0.00 | 35798905.35 | 0.00 | 35798905.35 | 33990283.35 | 4155.81 | 139.89 | 4464.29 | 84.64 |
PERIMETER_BOT_ZN_3 | 5949144.85 | 0.00 | 5949144.85 | 258141.27 | 6207286.12 | 4267819.30 | 3297.10 | 33.27 | 5429.63 | 591.06 |
PERIMETER_BOT_ZN_2 | 5122125.32 | 0.00 | 5122125.32 | 172094.06 | 5294219.39 | 2750345.05 | 3158.84 | 8.96 | 5592.20 | 591.06 |
PERIMETER_BOT_ZN_1 | 8617901.81 | 0.00 | 8617901.81 | 258141.27 | 8876043.08 | 4267912.63 | 3232.99 | 25.54 | 5501.47 | 591.06 |
PERIMETER_BOT_ZN_4 | 8477539.81 | 0.00 | 8477539.81 | 172094.06 | 8649633.87 | 2750345.05 | 3138.59 | 0.00 | 5621.41 | 591.06 |
PERIMETER_MID_ZN_3 | 42980534.19 | 0.00 | 42980534.19 | 605406.74 | 43585940.93 | 42678193.03 | 3954.91 | 100.29 | 4704.80 | 89.19 |
PERIMETER_MID_ZN_2 | 42432363.35 | 0.00 | 42432363.35 | 403604.22 | 42835967.56 | 27503450.52 | 3807.50 | 2.65 | 4949.85 | 998.19 |
PERIMETER_MID_ZN_1 | 70941661.22 | 0.00 | 70941661.22 | 605406.74 | 71547067.95 | 42679126.28 | 3862.51 | 89.64 | 4807.84 | 89.19 |
PERIMETER_MID_ZN_4 | 48634754.61 | 0.00 | 48634754.61 | 403604.22 | 49038358.82 | 27503450.52 | 3801.27 | 0.72 | 4958.01 | 89.19 |
PERIMETER_TOP_ZN_3 | 4271985.16 | 0.00 | 4271985.16 | 751668.47 | 5023653.63 | 4267819.30 | 4083.69 | 149.58 | 4526.73 | 84.64 |
PERIMETER_TOP_ZN_2 | 4169345.67 | 0.00 | 4169345.67 | 501111.97 | 4670457.64 | 2750345.05 | 3926.94 | 2.02 | 4831.04 | 84.64 |
PERIMETER_TOP_ZN_1 | 6728549.70 | 0.00 | 6728549.70 | 751668.47 | 7480218.17 | 4267912.63 | 4023.04 | 125.64 | 4611.31 | 84.64 |
PERIMETER_TOP_ZN_4 | 4902047.21 | 0.00 | 4902047.21 | 501111.97 | 5403159.18 | 2750345.05 | 3909.23 | 4.31 | 4846.46 | 84.64 |
DATACENTER_BOT_ZN_6 | 212025.13 | 0.00 | 212025.13 | 0.00 | 212025.13 | 389144.62 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2120251.31 | 0.00 | 2120251.31 | 0.00 | 2120251.31 | 3891446.16 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 212025.13 | 0.00 | 212025.13 | 0.00 | 212025.13 | 389144.62 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8423799.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 0.61E+10 | 0.00 | 0.61E+10 | 23546250.62 | 0.61E+10 | 0.50E+10 | 8760.00 | 4368.51 | 5817.05 | 1662.55 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.9836 | 0.0000 | 2.9836 | 0.0000 | 2.9836 | 0.9949 | 1281.23 | 401.58 | 4260.19 |
CORE_BOTTOM | 2.3007 | 0.0000 | 2.3007 | 0.0000 | 2.3007 | 1.0778 | 1104.97 | 22.77 | 4815.27 |
CORE_MID | 17.5657 | 0.0000 | 17.5657 | 0.0000 | 17.5657 | 10.7782 | 1293.54 | 91.32 | 4558.14 |
CORE_TOP | 1.6548 | 0.0000 | 1.6548 | 0.0000 | 1.6548 | 1.0778 | 1384.84 | 139.89 | 4418.27 |
PERIMETER_BOT_ZN_3 | 0.2571 | 0.0000 | 0.2571 | 0.0069 | 0.2640 | 0.1353 | 1050.94 | 29.04 | 4863.02 |
PERIMETER_BOT_ZN_2 | 0.2234 | 0.0000 | 0.2234 | 0.0046 | 0.2281 | 0.0872 | 929.33 | 8.16 | 5005.51 |
PERIMETER_BOT_ZN_1 | 0.3818 | 0.0000 | 0.3818 | 0.0069 | 0.3887 | 0.1353 | 986.77 | 21.21 | 4935.02 |
PERIMETER_BOT_ZN_4 | 0.3730 | 0.0000 | 0.3730 | 0.0046 | 0.3776 | 0.0872 | 912.65 | 0.00 | 5030.35 |
PERIMETER_MID_ZN_3 | 1.9753 | 0.0000 | 1.9753 | 0.0163 | 1.9916 | 1.3533 | 1227.10 | 100.29 | 4615.61 |
PERIMETER_MID_ZN_2 | 1.8102 | 0.0000 | 1.8102 | 0.0112 | 1.8214 | 0.8721 | 1077.70 | 1.48 | 3954.82 |
PERIMETER_MID_ZN_1 | 3.2818 | 0.0000 | 3.2818 | 0.0163 | 3.2981 | 1.3533 | 1134.71 | 89.64 | 4718.65 |
PERIMETER_MID_ZN_4 | 2.2421 | 0.0000 | 2.2421 | 0.0109 | 2.2530 | 0.8721 | 1073.46 | 0.72 | 4868.82 |
PERIMETER_TOP_ZN_3 | 0.1973 | 0.0000 | 0.1973 | 0.0202 | 0.2175 | 0.1353 | 1314.56 | 149.46 | 4478.98 |
PERIMETER_TOP_ZN_2 | 0.1930 | 0.0000 | 0.1930 | 0.0135 | 0.2065 | 0.0872 | 1161.56 | 1.28 | 4780.16 |
PERIMETER_TOP_ZN_1 | 0.3121 | 0.0000 | 0.3121 | 0.0202 | 0.3324 | 0.1353 | 1252.56 | 125.64 | 4564.80 |
PERIMETER_TOP_ZN_4 | 0.2268 | 0.0000 | 0.2268 | 0.0135 | 0.2403 | 0.0872 | 1147.29 | 2.93 | 4792.78 |
DATACENTER_BOT_ZN_6 | 0.0099 | 0.0000 | 0.0099 | 0.0000 | 0.0099 | 0.0130 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.0991 | 0.0000 | 0.0991 | 0.0000 | 0.0991 | 0.1296 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0099 | 0.0000 | 0.0099 | 0.0000 | 0.0099 | 0.0130 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.2805 | 5943.00 | 0.00 | 0.00 |
Total Facility | 278.8652 | 0.0000 | 278.8652 | 0.6373 | 279.5026 | 157.9346 | 5943.00 | 4359.30 | 5111.41 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 0.11E+09 | 0.00 | 0.11E+09 | 48026705.38 | 3138.59 | 0.00 | 5621.41 | 591.06 |
VAV_MID WITH REHEAT | 0.82E+09 | 0.00 | 0.82E+09 | 0.48E+09 | 3798.34 | 0.44 | 4961.22 | 89.19 |
VAV_TOP WITH REHEAT | 78029256.26 | 0.00 | 78029256.26 | 48026705.38 | 3900.44 | 4.35 | 4855.21 | 84.64 |
CAV_BAS | 92789581.96 | 0.00 | 92789581.96 | 29876159.83 | 3780.96 | 0.64 | 4978.40 | 365.94 |
AIRLOOP DATACENTER BOT | 296114.47 | 0.00 | 296114.47 | 389144.62 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 2961144.70 | 0.00 | 2961144.70 | 3891446.16 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 296114.47 | 0.00 | 296114.47 | 389144.62 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.9385 | 0.0000 | 4.9385 | 1.5229 | 912.65 | 0.00 | 5030.35 |
VAV_MID WITH REHEAT | 37.7380 | 0.0000 | 37.7380 | 15.2292 | 1070.53 | 0.44 | 4872.02 |
VAV_TOP WITH REHEAT | 3.6089 | 0.0000 | 3.6089 | 1.5229 | 1142.17 | 2.46 | 4798.37 |
CAV_BAS | 4.1669 | 0.0000 | 4.1669 | 0.9949 | 1277.63 | 0.11 | 4665.26 |
AIRLOOP DATACENTER BOT | 0.0138 | 0.0000 | 0.0138 | 0.0130 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1384 | 0.0000 | 0.1384 | 0.1296 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0138 | 0.0000 | 0.0138 | 0.0130 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 5424.16 | 0.00 | 0.00 | 0.00 | 197.25 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 4707.96 | 0.00 | 0.00 | 0.00 | 255.50 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 4595.58 | 0.00 | 0.00 | 0.00 | 318.54 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 0.00 | 4638.28 | 0.00 | 0.00 | 0.00 | 401.01 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 5.9779 | 0.0000 | 0.0000 | 0.0000 | 2.3249 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 47.2551 | 0.0000 | 0.0000 | 0.0000 | 23.7370 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.5931 | 0.0000 | 0.0000 | 0.0000 | 2.3044 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 0.0000 | 5.6620 | 0.0000 | 0.0000 | 0.0000 | 1.4370 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0190 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.1895 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0190 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 7 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1352 |
Defaulted Fields | 1168 |
Fields with Defaults | 3820 |
Autosized Fields | 310 |
Autosizable Fields | 391 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 22963.00 | 284920.93 | 01-JAN-04:50 | 1575027.12 | 18-AUG-15:50 |
Electricity:Building | 16703.28 | 216790.15 | 29-MAY-17:10 | 977223.71 | 01-DEC-16:40 |
Electricity:Zone:BASEMENT | 559.97 | 14115.26 | 01-JAN-00:10 | 25295.37 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16703.28 | 216790.15 | 29-MAY-17:10 | 977223.71 | 01-DEC-16:40 |
InteriorLights:Electricity | 2026.88 | 9514.02 | 01-JAN-09:20 | 198852.03 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:BASEMENT | 135.58 | 657.72 | 01-JAN-00:10 | 11837.83 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2026.88 | 9514.02 | 01-JAN-09:20 | 198852.03 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 2026.88 | 9514.02 | 01-JAN-09:20 | 198852.03 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 135.58 | 657.72 | 01-JAN-00:10 | 11837.83 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2026.88 | 9514.02 | 01-JAN-09:20 | 198852.03 | 02-JAN-16:50 |
Electricity:Zone:CORE_BOTTOM | 411.37 | 5043.91 | 01-JAN-00:10 | 27837.83 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4113.71 | 50438.97 | 01-JAN-00:10 | 278377.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1217.58 | 5906.80 | 01-JAN-00:10 | 106312.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1217.58 | 5906.80 | 01-JAN-00:10 | 106312.04 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 411.37 | 5043.90 | 01-JAN-00:10 | 27837.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 45.41 | 594.46 | 16-APR-17:10 | 3495.41 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.04 | 35.29 | 01-JAN-09:20 | 1334.85 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.04 | 35.29 | 01-JAN-09:20 | 1334.85 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 29.21 | 384.60 | 18-JUN-17:10 | 2252.57 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.77 | 22.74 | 01-JAN-07:30 | 860.23 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.77 | 22.74 | 01-JAN-07:30 | 860.23 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 45.20 | 594.47 | 16-APR-17:10 | 3495.47 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.83 | 35.29 | 01-JAN-07:30 | 1334.88 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.83 | 35.29 | 01-JAN-07:30 | 1334.88 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 29.19 | 383.09 | 12-MAR-17:10 | 2252.56 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.76 | 22.74 | 01-JAN-09:20 | 860.23 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.76 | 22.74 | 01-JAN-09:20 | 860.23 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 454.05 | 5944.59 | 16-APR-17:10 | 34954.06 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 90.39 | 352.88 | 01-JAN-09:20 | 13348.54 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 90.39 | 352.88 | 01-JAN-09:20 | 13348.54 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 292.05 | 3844.65 | 18-JUN-17:10 | 22525.72 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 57.70 | 227.41 | 01-JAN-07:30 | 8602.31 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 57.70 | 227.41 | 01-JAN-07:30 | 8602.31 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 452.01 | 5944.68 | 16-APR-17:10 | 34954.68 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 88.35 | 352.89 | 01-JAN-07:30 | 13348.83 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 88.35 | 352.89 | 01-JAN-07:30 | 13348.83 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 291.92 | 3830.90 | 12-MAR-17:10 | 22525.63 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 57.57 | 227.41 | 01-JAN-09:10 | 8602.31 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 57.57 | 227.41 | 01-JAN-09:10 | 8602.31 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 45.40 | 594.46 | 16-APR-17:10 | 3495.41 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.04 | 35.29 | 01-JAN-09:20 | 1334.85 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.04 | 35.29 | 01-JAN-09:20 | 1334.85 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 29.21 | 384.46 | 18-JUN-17:10 | 2252.57 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.77 | 22.74 | 01-JAN-07:30 | 860.23 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.77 | 22.74 | 01-JAN-07:30 | 860.23 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 45.20 | 594.47 | 16-APR-17:10 | 3495.47 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.84 | 35.29 | 01-JAN-07:30 | 1334.88 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.84 | 35.29 | 01-JAN-07:30 | 1334.88 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 29.19 | 383.09 | 12-MAR-17:10 | 2252.56 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.76 | 22.74 | 01-JAN-09:10 | 860.23 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.76 | 22.74 | 01-JAN-09:10 | 860.23 | 02-JAN-16:50 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7533.08 | 95093.58 | 01-JAN-00:10 | 382970.28 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 38.23 | 185.45 | 01-JAN-00:10 | 3337.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 38.23 | 185.45 | 01-JAN-00:10 | 3337.76 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.14 | 1964.44 | 01-JAN-00:10 | 8079.39 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1571.44 | 19644.38 | 01-JAN-00:10 | 80793.90 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 32.64 | 158.32 | 01-JAN-00:10 | 2849.68 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 32.64 | 158.32 | 01-JAN-00:10 | 2849.68 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.14 | 1964.44 | 01-JAN-00:10 | 8079.39 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1448.93 | 937.99 | 03-JAN-07:20 | 336995.96 | 18-AUG-15:50 |
HeatRejection:Electricity | 313.32 | 265.79 | 03-JAN-07:10 | 40740.66 | 23-MAR-14:00 |
General:HeatRejection:Electricity | 313.32 | 265.79 | 03-JAN-07:10 | 40740.66 | 23-MAR-14:00 |
Electricity:HVAC | 1435.27 | 9210.22 | 01-JAN-05:30 | 153624.17 | 18-AUG-15:00 |
ExteriorEquipment:Electricity | 3108.27 | 43347.20 | 01-JAN-00:10 | 177595.49 | 08-DEC-08:20 |
Transformer:ExteriorEquipment:Electricity | 54.48 | 979.82 | 01-JAN-00:10 | 3387.38 | 01-DEC-16:50 |
ElectricityPurchased:Facility | 22963.00 | 284920.93 | 01-JAN-04:50 | 1575027.12 | 18-AUG-15:50 |
ElectricityPurchased:Plant | 22963.00 | 284920.93 | 01-JAN-04:50 | 1575027.12 | 18-AUG-15:50 |
Cogeneration:ElectricityPurchased | 22963.00 | 284920.93 | 01-JAN-04:50 | 1575027.12 | 18-AUG-15:50 |
General:Cogeneration:ElectricityPurchased | 22963.00 | 284920.93 | 01-JAN-04:50 | 1575027.12 | 18-AUG-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 22963.00 | 284920.93 | 01-JAN-04:50 | 1575027.12 | 18-AUG-15:50 |
ElectricityNet:Plant | 22963.00 | 284920.93 | 01-JAN-04:50 | 1575027.12 | 18-AUG-15:50 |
Cogeneration:ElectricityNet | 22963.00 | 284920.93 | 01-JAN-04:50 | 1575027.12 | 18-AUG-15:50 |
General:Cogeneration:ElectricityNet | 22963.00 | 284920.93 | 01-JAN-04:50 | 1575027.12 | 18-AUG-15:50 |
Fans:Electricity | 1017.40 | 6032.00 | 02-JAN-23:40 | 125640.42 | 18-AUG-15:00 |
General:Fans:Electricity | 1017.40 | 6032.00 | 02-JAN-23:40 | 125640.42 | 18-AUG-15:00 |
ExteriorLights:Electricity | 321.73 | 0.00 | 01-JAN-07:00 | 37611.08 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 321.73 | 0.00 | 01-JAN-07:00 | 37611.08 | 01-JAN-06:10 |
ComputerHVAC:ExteriorEquipment:Electricity | 1199.18 | 15185.30 | 01-JAN-00:10 | 60741.22 | 31-MAR-23:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 1042.95 | 1666.52 | 03-JAN-07:10 | 273658.61 | 18-AUG-15:50 |
General:Cooling:Electricity | 1042.95 | 1666.52 | 03-JAN-07:10 | 273658.61 | 18-AUG-15:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 456.06 | 644.97 | 01-JAN-00:10 | 57440.88 | 16-OCT-14:40 |
General:Pumps:Electricity | 456.06 | 644.97 | 01-JAN-00:10 | 57440.88 | 16-OCT-14:40 |
WIRED_LTG_ELECTRICITY | 56.96 | 0.00 | 01-JAN-00:10 | 5587.74 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 704.54 | 5695.87 | 01-JAN-00:10 | 328617.98 | 03-JAN-07:10 |
NaturalGas:Plant | 704.54 | 5695.87 | 01-JAN-00:10 | 328617.98 | 03-JAN-07:10 |
Heating:NaturalGas | 39.51 | 0.00 | 01-JAN-00:10 | 299869.97 | 03-JAN-07:10 |
Boiler:Heating:NaturalGas | 39.51 | 0.00 | 01-JAN-00:10 | 299869.97 | 03-JAN-07:10 |
WaterSystems:NaturalGas | 665.02 | 5695.87 | 01-JAN-00:10 | 76423.38 | 31-JAN-12:40 |
Water Heater:WaterSystems:NaturalGas | 665.02 | 5695.87 | 01-JAN-00:10 | 76423.38 | 31-JAN-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 6904.96 | 8178.01 | 03-JAN-07:10 | 1771449.72 | 18-AUG-15:50 |
PlantLoopCoolingDemand:HVAC | 6904.96 | 8178.01 | 03-JAN-07:10 | 1771449.72 | 18-AUG-15:50 |
CoolingCoils:PlantLoopCoolingDemand | 6904.96 | 8178.01 | 03-JAN-07:10 | 1771449.72 | 18-AUG-15:50 |
DistrictCooling:Facility | 7166.03 | 87162.01 | 14-MAY-05:00 | 369114.52 | 26-DEC-15:00 |
DistrictCooling:HVAC | 7166.03 | 87162.01 | 14-MAY-05:00 | 369114.52 | 26-DEC-15:00 |
Cooling:DistrictCooling | 7166.03 | 87162.01 | 14-MAY-05:00 | 369114.52 | 26-DEC-15:00 |
General:Cooling:DistrictCooling | 7166.03 | 87162.01 | 14-MAY-05:00 | 369114.52 | 26-DEC-15:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 5829.32 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
Water:Plant | 5829.32 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 5829.32 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
MainsWater:Plant | 5829.32 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 3549.15 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
General:HeatRejection:Water | 3549.15 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
HeatRejection:MainsWater | 3549.15 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
General:HeatRejection:MainsWater | 3549.15 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 39573.70 | 101922.89 | 01-JAN-05:30 | 8243489.75 | 18-AUG-15:50 |
EnergyTransfer:Building | 17629.26 | 92683.55 | 01-JAN-06:50 | 1316083.93 | 18-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 597.52 | 0.00 | 01-JAN-00:10 | 68594.15 | 13-NOV-06:10 |
Heating:EnergyTransfer | 28.56 | 0.00 | 03-JAN-22:10 | 156310.96 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.30 | 0.00 | 01-JAN-00:10 | 12248.26 | 14-OCT-16:10 |
General:Heating:EnergyTransfer | 28.56 | 0.00 | 03-JAN-22:10 | 156310.96 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 3.30 | 0.00 | 01-JAN-00:10 | 12248.26 | 14-OCT-16:10 |
Cooling:EnergyTransfer | 17600.70 | 92160.47 | 01-JAN-07:00 | 1316083.93 | 18-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 594.23 | 0.00 | 01-JAN-00:10 | 68594.15 | 13-NOV-06:10 |
General:Cooling:EnergyTransfer | 17600.70 | 92160.47 | 01-JAN-07:00 | 1316083.93 | 18-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 594.23 | 0.00 | 01-JAN-00:10 | 68594.15 | 13-NOV-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 594.43 | 0.00 | 01-JAN-00:10 | 48563.38 | 13-NOV-08:50 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 594.43 | 0.00 | 01-JAN-00:10 | 48563.38 | 13-NOV-08:50 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 594.43 | 0.00 | 01-JAN-00:10 | 48563.38 | 13-NOV-08:50 |
EnergyTransfer:Zone:CORE_MID | 4204.05 | 0.00 | 01-JAN-00:10 | 388190.63 | 21-SEP-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4204.05 | 0.00 | 01-JAN-00:10 | 388190.63 | 21-SEP-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4204.05 | 0.00 | 01-JAN-00:10 | 388190.63 | 21-SEP-05:10 |
EnergyTransfer:Zone:CORE_TOP | 377.76 | 0.00 | 01-JAN-00:10 | 42614.66 | 16-OCT-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.23 | 0.00 | 01-JAN-00:10 | 31006.48 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.23 | 0.00 | 01-JAN-00:10 | 31006.48 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 377.54 | 0.00 | 01-JAN-00:10 | 42614.66 | 16-OCT-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 377.54 | 0.00 | 01-JAN-00:10 | 42614.66 | 16-OCT-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 65.26 | 0.00 | 01-JAN-00:10 | 7608.95 | 16-OCT-11:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 65.26 | 0.00 | 01-JAN-00:10 | 7608.95 | 16-OCT-11:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 65.26 | 0.00 | 01-JAN-00:10 | 7608.95 | 16-OCT-11:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 56.12 | 0.00 | 01-JAN-00:10 | 8879.13 | 16-OCT-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 56.12 | 0.00 | 01-JAN-00:10 | 8879.13 | 16-OCT-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 56.12 | 0.00 | 01-JAN-00:10 | 8879.13 | 16-OCT-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 97.06 | 0.00 | 01-JAN-00:10 | 15077.48 | 16-OCT-12:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 97.06 | 0.00 | 01-JAN-00:10 | 15077.48 | 16-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 97.06 | 0.00 | 01-JAN-00:10 | 15077.48 | 16-OCT-12:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 95.77 | 0.00 | 01-JAN-00:10 | 12574.86 | 26-APR-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 95.77 | 0.00 | 01-JAN-00:10 | 12574.86 | 26-APR-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 95.77 | 0.00 | 01-JAN-00:10 | 12574.86 | 26-APR-15:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 441.41 | 0.00 | 01-JAN-00:10 | 64407.14 | 16-OCT-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.73 | 0.00 | 01-JAN-00:10 | 44260.39 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.73 | 0.00 | 01-JAN-00:10 | 44260.39 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 440.67 | 0.00 | 01-JAN-00:10 | 64407.14 | 16-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 440.67 | 0.00 | 01-JAN-00:10 | 64407.14 | 16-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 454.40 | 0.00 | 01-JAN-00:10 | 86657.94 | 14-AUG-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.27 | 0.00 | 01-JAN-00:10 | 31120.31 | 30-MAR-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.27 | 0.00 | 01-JAN-00:10 | 31120.31 | 30-MAR-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 454.13 | 0.00 | 01-JAN-00:10 | 86657.94 | 14-AUG-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 454.13 | 0.00 | 01-JAN-00:10 | 86657.94 | 14-AUG-08:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 799.29 | 0.00 | 01-JAN-00:10 | 147037.41 | 16-OCT-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.11 | 0.00 | 01-JAN-00:10 | 29604.71 | 30-MAR-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.11 | 0.00 | 01-JAN-00:10 | 29604.71 | 30-MAR-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 799.18 | 0.00 | 01-JAN-00:10 | 147037.41 | 16-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 799.18 | 0.00 | 01-JAN-00:10 | 147037.41 | 16-OCT-12:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 526.52 | 0.00 | 01-JAN-00:10 | 99828.26 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.05 | 0.00 | 01-JAN-00:10 | 13227.66 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.05 | 0.00 | 01-JAN-00:10 | 13227.66 | 03-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 526.46 | 0.00 | 01-JAN-00:10 | 99828.26 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 526.46 | 0.00 | 01-JAN-00:10 | 99828.26 | 29-SEP-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 41.83 | 0.00 | 01-JAN-00:10 | 8931.84 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.02 | 0.00 | 01-JAN-00:10 | 8931.84 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.02 | 0.00 | 01-JAN-00:10 | 8931.84 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.81 | 0.00 | 01-JAN-00:10 | 7183.83 | 16-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.81 | 0.00 | 01-JAN-00:10 | 7183.83 | 16-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 43.31 | 0.00 | 01-JAN-00:10 | 8668.84 | 14-AUG-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.76 | 0.00 | 01-JAN-00:10 | 6342.38 | 30-MAR-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.76 | 0.00 | 01-JAN-00:10 | 6342.38 | 30-MAR-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 42.56 | 0.00 | 01-JAN-00:10 | 8668.84 | 14-AUG-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 42.56 | 0.00 | 01-JAN-00:10 | 8668.84 | 14-AUG-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 72.99 | 0.00 | 01-JAN-00:10 | 15986.80 | 16-OCT-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.63 | 0.00 | 01-JAN-00:10 | 8060.31 | 30-MAR-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.63 | 0.00 | 01-JAN-00:10 | 8060.31 | 30-MAR-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 72.35 | 0.00 | 01-JAN-00:10 | 15986.80 | 16-OCT-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 72.35 | 0.00 | 01-JAN-00:10 | 15986.80 | 16-OCT-13:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 50.63 | 0.00 | 01-JAN-00:10 | 10594.87 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.41 | 0.00 | 01-JAN-00:10 | 4897.23 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.41 | 0.00 | 01-JAN-00:10 | 4897.23 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 50.22 | 0.00 | 01-JAN-00:10 | 10594.87 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 50.22 | 0.00 | 01-JAN-00:10 | 10594.87 | 29-SEP-15:30 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 58.88 | 0.00 | 01-JAN-00:10 | 7610.92 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.01 | 0.00 | 01-JAN-00:10 | 3382.30 | 25-DEC-09:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.01 | 0.00 | 01-JAN-00:10 | 3382.30 | 25-DEC-09:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 57.88 | 0.00 | 01-JAN-00:10 | 7610.92 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 57.88 | 0.00 | 01-JAN-00:10 | 7610.92 | 16-OCT-16:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 333.05 | 0.00 | 01-JAN-00:10 | 55291.02 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 9.87 | 0.00 | 01-JAN-00:10 | 27071.75 | 02-JAN-14:40 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 9.87 | 0.00 | 01-JAN-00:10 | 27071.75 | 02-JAN-14:40 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 323.18 | 0.00 | 01-JAN-00:10 | 55291.02 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 323.18 | 0.00 | 01-JAN-00:10 | 55291.02 | 16-OCT-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 59.21 | 0.00 | 01-JAN-00:10 | 15165.74 | 16-OCT-14:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 9.03 | 0.00 | 01-JAN-00:10 | 8757.54 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 9.03 | 0.00 | 01-JAN-00:10 | 8757.54 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.18 | 0.00 | 01-JAN-00:10 | 15165.74 | 16-OCT-14:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.18 | 0.00 | 01-JAN-00:10 | 15165.74 | 16-OCT-14:10 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.82 | 1140.21 | 10-JAN-07:50 | 7846.51 | 06-AUG-17:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.82 | 1140.21 | 10-JAN-07:50 | 7846.51 | 06-AUG-17:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.82 | 1140.21 | 10-JAN-07:50 | 7846.51 | 06-AUG-17:40 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1260.24 | 1942.68 | 01-JAN-07:00 | 73227.19 | 06-AUG-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1260.24 | 1942.68 | 01-JAN-07:00 | 73227.19 | 06-AUG-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1260.24 | 1942.68 | 01-JAN-07:00 | 73227.19 | 06-AUG-17:50 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 118.28 | 2.30 | 07-JAN-09:50 | 7444.05 | 20-AUG-17:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.14 | 0.00 | 02-JAN-11:00 | 526.13 | 08-JAN-06:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.14 | 0.00 | 02-JAN-11:00 | 526.13 | 08-JAN-06:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 118.14 | 0.00 | 01-JAN-00:10 | 7444.05 | 20-AUG-17:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 118.14 | 0.00 | 01-JAN-00:10 | 7444.05 | 20-AUG-17:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7141.41 | 87162.01 | 14-MAY-05:00 | 366446.42 | 26-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7141.41 | 87162.01 | 14-MAY-05:00 | 366446.42 | 26-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7141.41 | 87162.01 | 14-MAY-05:00 | 366446.42 | 26-DEC-17:00 |
PlantLoopHeatingDemand:Facility | 404.36 | 0.00 | 01-JAN-00:10 | 243411.70 | 03-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 377.81 | 0.00 | 01-JAN-00:10 | 43843.54 | 02-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 377.81 | 0.00 | 01-JAN-00:10 | 43843.54 | 02-FEB-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 377.81 | 0.00 | 01-JAN-00:10 | 43843.54 | 02-FEB-12:30 |
EnergyTransfer:HVAC | 6568.11 | 8975.84 | 01-JAN-07:00 | 1748357.14 | 18-AUG-15:50 |
HeatingCoils:EnergyTransfer | 26.54 | 0.00 | 01-JAN-00:10 | 228966.74 | 03-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 26.54 | 0.00 | 01-JAN-00:10 | 228966.74 | 03-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 26.54 | 0.00 | 01-JAN-00:10 | 228966.74 | 03-JAN-07:10 |
CoolingCoils:EnergyTransfer | 6541.56 | 6511.49 | 03-JAN-07:10 | 1748357.14 | 18-AUG-15:50 |
DistrictHeating:Facility | 0.00 | 0.00 | 01-JAN-01:20 | 13.50 | 31-MAY-23:40 |
DistrictHeating:HVAC | 0.00 | 0.00 | 01-JAN-01:20 | 13.50 | 31-MAY-23:40 |
Heating:DistrictHeating | 0.00 | 0.00 | 01-JAN-01:20 | 13.50 | 31-MAY-23:40 |
General:Heating:DistrictHeating | 0.00 | 0.00 | 01-JAN-01:20 | 13.50 | 31-MAY-23:40 |
EnergyTransfer:Plant | 15376.34 | -3312.31 | 02-JAN-04:20 | 5184794.69 | 18-AUG-15:50 |
LoopToLoop:EnergyTransfer | 5034.68 | -4052.68 | 02-JAN-05:00 | 1655191.76 | 18-AUG-15:50 |
WaterSystems:EnergyTransfer | 377.81 | 0.00 | 01-JAN-00:10 | 43843.54 | 02-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 377.81 | 0.00 | 01-JAN-00:10 | 43843.54 | 02-FEB-12:30 |
Boilers:EnergyTransfer | 26.24 | 0.00 | 01-JAN-00:10 | 238889.92 | 03-JAN-07:10 |
Chillers:EnergyTransfer | 4629.02 | 0.00 | 01-JAN-00:10 | 1624313.27 | 18-AUG-15:50 |
HeatRejection:EnergyTransfer | 5308.58 | 0.00 | 01-JAN-00:10 | 1874879.30 | 18-AUG-15:50 |
General:HeatRejection:EnergyTransfer | 5308.58 | 0.00 | 01-JAN-00:10 | 1874879.30 | 18-AUG-15:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.296 | -594.232 | 0.000 | 0.000 | 92.641 | 135.577 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -61.679 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -594.434 | 0.000 | 0.000 | 83.412 | 121.758 | 289.614 | 0.000 | 0.000 | 0.000 | 99.650 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_MID | 0.000 | 0.000 | 0.000 | -4204.057 | 0.000 | 0.000 | 837.999 | 1217.578 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -747.648 |
CORE_TOP | 0.000 | 0.000 | 0.228 | -377.535 | 0.000 | 0.000 | 85.479 | 121.758 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -119.542 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -65.263 | 0.000 | 0.000 | 10.551 | 9.042 | 36.365 | 16.893 | 0.000 | 0.021 | 32.243 | 0.000 | -37.210 | 0.000 | -2.643 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -56.122 | 0.000 | 0.000 | 6.790 | 5.773 | 23.435 | 38.754 | 0.000 | 0.013 | 6.599 | 0.000 | -23.477 | 0.000 | -1.766 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -97.066 | 0.000 | 0.000 | 10.513 | 8.832 | 36.366 | 76.424 | 0.000 | 0.018 | 4.289 | 0.000 | -36.642 | 0.000 | -2.733 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -95.771 | 0.000 | 0.000 | 6.742 | 5.760 | 23.435 | 43.107 | 0.000 | 0.012 | 46.616 | 0.000 | -27.878 | 0.000 | -2.024 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.733 | -440.675 | 0.000 | 0.000 | 108.966 | 90.391 | 363.654 | 181.658 | 0.000 | 0.556 | 85.451 | 0.000 | -336.291 | 0.000 | -54.442 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.273 | -454.131 | 0.000 | 0.000 | 50.732 | 57.700 | 234.352 | 389.453 | 0.000 | 0.295 | 0.003 | 0.000 | -222.700 | 0.000 | -38.674 | -17.301 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.114 | -799.196 | 0.000 | 0.000 | 105.858 | 88.353 | 363.660 | 762.735 | 0.000 | 0.406 | 0.002 | 0.000 | -355.204 | 0.000 | -61.521 | -105.204 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.053 | -526.467 | 0.000 | 0.000 | 69.137 | 57.569 | 234.351 | 440.700 | 0.000 | 0.316 | 8.190 | 0.000 | -243.040 | 0.000 | -40.808 | -0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 2.019 | -39.809 | 0.000 | 0.000 | 11.180 | 9.039 | 36.365 | 18.944 | 0.000 | 0.076 | 0.001 | 0.000 | -31.070 | 0.000 | -6.135 | -0.610 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.756 | -42.557 | 0.000 | 0.000 | 7.001 | 5.770 | 23.435 | 39.439 | 0.000 | 0.037 | 0.002 | 0.000 | -20.910 | 0.000 | -4.437 | -8.533 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.631 | -72.356 | 0.000 | 0.000 | 10.739 | 8.835 | 36.366 | 76.812 | 0.000 | 0.050 | 0.003 | 0.000 | -33.485 | 0.000 | -7.115 | -20.476 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.411 | -50.220 | 0.000 | 0.000 | 7.066 | 5.757 | 23.435 | 44.331 | 0.000 | 0.041 | 0.000 | 0.000 | -22.889 | 0.000 | -4.725 | -3.207 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -139.824 | 0.000 | 0.000 | 0.950 | 3.264 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -18.271 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1260.240 | 0.000 | 0.000 | 9.501 | 32.637 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -320.704 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.137 | -118.143 | 0.000 | 0.000 | 0.950 | 3.264 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -40.089 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | -7141.409 | 0.000 | 0.000 | 0.000 | 0.000 | 20.569 | 38.227 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -412.244 |
GROUNDFLOOR_PLENUM | 1.005 | -57.880 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.033 | 62.568 | 0.000 | 0.000 | 0.000 | -5.727 | 0.000 |
MIDFLOOR_PLENUM | 9.873 | -323.178 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.654 | 409.476 | 0.000 | 0.000 | 0.000 | -96.825 | 0.000 |
TOPFLOOR_PLENUM | 9.030 | -50.178 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.060 | 51.334 | 0.000 | 0.000 | 0.000 | -10.246 | -0.000 |
Total Facility | 19.908 | -7572.645 | 8.652 | -10028.098 | 0.000 | 0.000 | 1536.775 | 2026.881 | 14676.396 | 2129.250 | 0.000 | 2.587 | 806.428 | 0.000 | -1390.796 | 0.000 | -339.819 | -1875.508 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 30-JAN-04:12 | 0.00 | 0.00 | 0.00 | -94145.32 | 0.00 | 0.00 | 0.00 | 657.72 | 13457.54 | 0.00 | 0.00 | 0.00 | 80030.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 13-NOV-04:02 | 0.00 | 0.00 | 0.00 | -84555.65 | 0.00 | 0.00 | 0.00 | 590.68 | 5937.65 | 0.00 | 0.00 | 0.00 | 78027.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | -721377.57 | 0.00 | 0.00 | 8369.70 | 11812.12 | 76473.61 | 0.00 | 0.00 | 0.00 | 624722.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 28-JUL-05:04 | 0.00 | 0.00 | 0.00 | -68272.44 | 0.00 | 0.00 | 846.30 | 1181.21 | 7647.36 | 0.00 | 0.00 | 0.00 | 58597.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 | -10227.45 | 0.00 | 0.00 | 110.47 | 132.84 | 960.25 | 0.00 | 0.00 | 0.00 | 10162.34 | 0.00 | -1138.44 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 15-OCT-08:43 | 0.00 | 0.00 | 0.00 | -15083.17 | 0.00 | 0.00 | 24.93 | 22.74 | 464.11 | 9995.00 | 0.00 | 103.65 | 4472.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 19-NOV-12:12 | 0.00 | 0.00 | 0.00 | -19392.39 | 0.00 | 0.00 | 36.77 | 35.29 | 720.19 | 17486.42 | 0.00 | 0.00 | 1163.30 | 0.00 | -0.00 | 0.00 | -49.59 | 0.00 |
PERIMETER_BOT_ZN_4 | 20-AUG-15:52 | 0.00 | 0.00 | 0.00 | -19756.22 | 0.00 | 0.00 | 20.92 | 22.74 | 464.11 | 10040.47 | 0.00 | 0.00 | 9294.85 | 0.00 | -0.00 | 0.00 | -86.88 | 0.00 |
PERIMETER_MID_ZN_3 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | -84482.63 | 0.00 | 0.00 | 1112.82 | 1483.13 | 9602.45 | 0.00 | 0.00 | 0.00 | 79501.80 | 0.00 | -7212.45 | 0.00 | -5.12 | 0.00 |
PERIMETER_MID_ZN_2 | 23-JUL-09:02 | 0.00 | 0.00 | 0.00 | -156080.98 | 0.00 | 0.00 | 250.65 | 227.41 | 4641.14 | 87744.61 | 0.00 | 0.00 | 64001.63 | 0.00 | -0.00 | 0.00 | -784.45 | 0.00 |
PERIMETER_MID_ZN_1 | 15-OCT-11:52 | 0.00 | 0.00 | 0.00 | -191430.34 | 0.00 | 0.00 | 347.59 | 352.89 | 7201.95 | 160779.66 | 0.00 | 2639.58 | 20108.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 15-OCT-14:32 | 0.00 | 0.00 | 0.00 | -170462.12 | 0.00 | 0.00 | 241.54 | 227.41 | 4641.11 | 103316.23 | 0.00 | 1447.16 | 60588.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 05-OCT-05:02 | 0.00 | 0.00 | 0.00 | -8887.54 | 0.00 | 0.00 | 111.72 | 148.31 | 960.25 | 0.00 | 0.00 | 0.00 | 8490.60 | 0.00 | -823.35 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 15-OCT-08:43 | 0.00 | 0.00 | 0.00 | -15310.36 | 0.00 | 0.00 | 25.40 | 22.74 | 464.11 | 9930.58 | 0.00 | 298.60 | 4568.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 19-NOV-13:22 | 0.00 | 0.00 | 0.00 | -20189.40 | 0.00 | 0.00 | 37.33 | 35.29 | 720.19 | 14674.64 | 0.00 | 0.00 | 4887.19 | 0.00 | -0.00 | 0.00 | -165.25 | 0.00 |
PERIMETER_TOP_ZN_4 | 23-JUL-16:32 | 0.00 | 0.00 | 0.00 | -18542.47 | 0.00 | 0.00 | 23.18 | 22.74 | 464.11 | 9112.14 | 0.00 | 0.00 | 9075.88 | 0.00 | -0.00 | 0.00 | -155.59 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-AUG-17:33 | 0.00 | 0.00 | 0.00 | -7846.46 | 0.00 | 0.00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 36.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 06-AUG-17:42 | 0.00 | 0.00 | 0.00 | -73226.95 | 0.00 | 0.00 | 0.00 | 158.32 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4875.60 |
DATACENTER_TOP_ZN_6 | 20-AUG-17:33 | 0.00 | 0.00 | 0.00 | -7444.00 | 0.00 | 0.00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -366.26 |
DATACENTER_BASEMENT_ZN_6 | 26-DEC-17:00 | 0.00 | -366446.42 | 0.00 | 0.00 | 0.00 | 0.00 | 2183.10 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18706.96 |
GROUNDFLOOR_PLENUM | 02-OCT-05:15 | 0.00 | -9639.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9680.90 | 0.00 | -0.00 | 0.00 | -41.49 | 0.00 |
MIDFLOOR_PLENUM | 02-OCT-05:15 | 0.00 | -75516.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76267.39 | 0.00 | -0.00 | 0.00 | -750.50 | 0.00 |
TOPFLOOR_PLENUM | 16-OCT-14:10 | 0.00 | -15166.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.00 | 14984.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-AUG-05:02 | 0.00 | -362041.14 | 0.00 | -1261863.03 | 0.00 | 0.00 | 16094.01 | 22094.05 | 616289.16 | 0.00 | 0.00 | 0.00 | 1030060.27 | 0.00 | -56735.10 | 0.00 | -3898.22 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 14-OCT-15:02 | 0.00 | 0.00 | 15391.30 | 0.00 | 0.00 | 0.00 | 1040.25 | 1973.00 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -31862.09 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-05:01 | 0.00 | 0.00 | 56124.83 | 0.00 | 0.00 | 0.00 | 0.00 | 1181.21 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -63243.66 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 03-JAN-06:02 | 0.00 | 0.00 | 86032.39 | 0.00 | 0.00 | 0.00 | 1486.58 | 1483.13 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -30210.88 | 0.00 | -1201.03 | -67192.64 |
PERIMETER_MID_ZN_2 | 30-MAR-05:02 | 0.00 | 0.00 | 86726.24 | 0.00 | 0.00 | 0.00 | 962.32 | 955.79 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19604.79 | 0.00 | -1854.48 | -73373.26 |
PERIMETER_MID_ZN_1 | 30-MAR-05:02 | 0.00 | 0.00 | 115163.25 | 0.00 | 0.00 | 0.00 | 1463.99 | 1483.16 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -30226.74 | 0.00 | -2845.31 | -94640.94 |
PERIMETER_MID_ZN_4 | 02-JAN-06:02 | 0.00 | 0.00 | 66569.39 | 0.00 | 0.00 | 0.00 | 921.65 | 955.79 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -12928.51 | 0.00 | -1044.45 | -60662.01 |
PERIMETER_TOP_ZN_3 | 02-JAN-04:02 | 0.00 | 0.00 | 11324.51 | 0.00 | 0.00 | 0.00 | 0.00 | 74.17 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1334.81 | 0.00 | -901.39 | -9908.04 |
PERIMETER_TOP_ZN_2 | 30-MAR-04:01 | 0.00 | 0.00 | 11732.33 | 0.00 | 0.00 | 0.00 | 0.00 | 95.58 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1760.44 | 0.00 | -819.22 | -9728.72 |
PERIMETER_TOP_ZN_1 | 30-MAR-04:01 | 0.00 | 0.00 | 14489.44 | 0.00 | 0.00 | 0.00 | 0.00 | 148.32 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2710.57 | 0.00 | -1252.66 | -11420.10 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 11585.53 | 0.00 | 0.00 | 0.00 | 0.00 | 95.58 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -922.77 | 0.00 | -684.24 | -10554.56 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 08-JAN-06:00 | 0.00 | 0.00 | 526.13 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2490.57 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 18-DEC-04:02 | 10204.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -904.25 | -9300.08 |
MIDFLOOR_PLENUM | 28-MAR-05:02 | 57812.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4483.10 | -53328.97 |
TOPFLOOR_PLENUM | 05-JUN-05:02 | 13470.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -134.29 | -13336.61 |
Total Facility | 02-JAN-06:02 | -424297.41 | 338099.50 | 433102.80 | -338099.50 | 0.00 | 0.00 | 18846.00 | 22094.05 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -75311.79 | 0.00 | -8942.14 | -226906.47 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 9.1092 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.3480 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 85.0823 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 77.0263 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 8.6584 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.1488 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 4.7945 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 4.7945 | 0.2503 | 1.0000 | Not calculated | 1.2002 | 0.2503 | ||
AIRLOOP DATACENTER BOT | 0.4684 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4684 | 0.0334 | 1.0000 | Not calculated | 0.0156 | 0.0334 | ||
AIRLOOP DATACENTER MID | 4.4629 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4629 | 0.0350 | 1.0000 | Not calculated | 0.1563 | 0.0350 | ||
AIRLOOP DATACENTER TOP | 0.4539 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4539 | 0.0344 | 1.0000 | Not calculated | 0.0156 | 0.0344 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 4.5546 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.7194 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 42.5411 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 26.2900 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.3292 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.6856 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 4.7945 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 4.7945 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2503 | ||
AIRLOOP DATACENTER BOT | 0.4684 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4684 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0334 | ||
AIRLOOP DATACENTER MID | 4.4629 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4629 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0350 | ||
AIRLOOP DATACENTER TOP | 0.4539 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4539 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0344 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.002360 | 149.6021 | 0.000305 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.002360 | 1.9486 | 0.000305 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.002360 | 19.4861 | 0.000305 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.002360 | 1.9486 | 0.000305 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.002360 | 149.60 | 0.000305 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BOT | 0.002360 | 1.95 | 0.000305 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.002360 | 19.49 | 0.000305 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.002360 | 1.95 | 0.000305 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7945 | 4.7945 | 4.7945 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2429 | 5.2429 | 1.8507 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 49.1214 | 49.1214 | 18.0276 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7838 | 4.7838 | 1.8370 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7837 | 0.7837 | 0.2320 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8819 | 0.8819 | 0.1764 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0590 | 1.0590 | 0.2319 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1417 | 1.1417 | 0.2283 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.1969 | 7.1969 | 2.2670 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.0535 | 9.0535 | 1.8107 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.1106 | 10.1106 | 2.2648 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.5999 | 9.5999 | 1.9200 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8242 | 0.8242 | 0.2308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9039 | 0.9039 | 0.1808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1133 | 1.1133 | 0.2304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0333 | 1.0333 | 0.2067 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4684 | 0.4684 | 0.4684 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4629 | 4.4629 | 4.4629 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4539 | 0.4539 | 0.4539 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 9.1092 | 8.3480 | 9.1092 | 2.7194 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 85.0823 | 77.0263 | 85.0823 | 26.2900 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 8.6584 | 8.1488 | 8.6584 | 2.6856 | 0.0000 | 1.0000 |
CAV_BAS | 4.7945 | 4.7945 | 4.7945 | 4.7945 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4684 | 0.4684 | 0.4684 | 0.4684 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4629 | 4.4629 | 4.4629 | 4.4629 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4539 | 0.4539 | 0.4539 | 0.4539 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7945 | 4.7945 | 4.7945 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6214 | 2.6214 | 1.8507 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 24.5607 | 24.5607 | 18.0276 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3919 | 2.3919 | 1.8370 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3918 | 0.3918 | 0.2320 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4410 | 0.4410 | 0.1764 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5295 | 0.5295 | 0.2319 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5709 | 0.5709 | 0.2283 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.5984 | 3.5984 | 2.2670 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.5267 | 4.5267 | 1.8107 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0553 | 5.0553 | 2.2648 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7999 | 4.7999 | 1.9200 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4121 | 0.4121 | 0.2308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4519 | 0.4519 | 0.1808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5566 | 0.5566 | 0.2304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5167 | 0.5167 | 0.2067 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4684 | 0.4684 | 0.4684 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4629 | 4.4629 | 4.4629 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4539 | 0.4539 | 0.4539 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 4.5546 | 2.7194 | 2.7194 | 2.7194 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 42.5411 | 26.2900 | 26.2900 | 26.2900 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.3292 | 2.6856 | 2.6856 | 2.6856 | 0.0000 | 1.0000 |
CAV_BAS | 4.7945 | 4.7945 | 4.7945 | 4.7945 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4684 | 0.4684 | 0.4684 | 0.4684 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4629 | 4.4629 | 4.4629 | 4.4629 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4539 | 0.4539 | 0.4539 | 0.4539 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 152.67 |
Number of hours not met | 152.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 |
Heating -- Boiler | 0.00 | 0.00 | 39.51 | 299869.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1042.95 | 273658.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7166.03 | 369114.52 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2026.88 | 198852.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 321.73 | 37611.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.48 | 3387.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ComputerHVAC | 1199.18 | 60741.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 1017.40 | 125640.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 456.06 | 57440.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 313.32 | 40740.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 665.02 | 76423.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 22963.00 |
Natural Gas | 0.00 | 704.54 |
Additional | 0.00 | 7166.03 |
Total | 14676.40 | 30833.56 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 43.76 |
Space Heating | 0.00 |
Space Cooling | 22.52 |
Fans (All) | 21.96 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 495.74 |
Subtotal | 495.74 |
Natural Gas [MJ/m2] | |
Space Heating | 0.85 |
Service Water Heating | 14.36 |
Miscellaneous (All) | 15.21 |
Subtotal | 15.21 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.57 |
Space Heating | 0.13 |
Space Cooling | 26.62 |
Fans (All) | 3.30 |
Service Water Heating | 2.16 |
Receptacle Equipment | 47.60 |
Miscellaneous | 13.62 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2362. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8242.33 | 517.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8698.33 | 56.67 | 5.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8717.17 | 42.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8719.50 | 40.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8035.00 | 725.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8703.33 | 56.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8704.33 | 55.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8647.50 | 112.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8712.83 | 47.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8716.67 | 43.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8662.50 | 97.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7207.17 | 1552.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7140.17 | 1619.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7084.33 | 1675.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8723.33 | 36.67 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 8760.00 | 5.00 | 0.00 | 0.00 |
Average | 8088.46 | 671.33 | 0.22 | 0.00 | 0.00 |
Sum | 186034.50 | 15440.50 | 5.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367498.33 | 1117.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330706.00 | 78.00 | 29.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1168.00 | 1100.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1132.17 | 1135.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1095.50 | 1172.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 103395.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367498.33 | 103395.00 | 29.00 | 0.00 | 0.00 |
Average | 75638.04 | 4695.61 | 1.26 | 0.00 | 0.00 |
Sum | 1739675.00 | 107999.00 | 29.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 7029.50 | 1730.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 7908.33 | 823.67 | 28.00 | 0.00 | 0.00 |
CORE_MID | 7932.33 | 827.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8200.00 | 560.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8507.33 | 252.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8473.67 | 286.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8339.67 | 420.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7310.33 | 1449.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8609.33 | 150.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8356.50 | 403.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8327.00 | 433.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7975.83 | 784.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8664.33 | 95.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8408.67 | 351.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8448.83 | 311.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8074.33 | 685.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8185.50 | 574.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8128.50 | 631.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8072.33 | 687.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8020.17 | 739.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8302.33 | 457.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7975.50 | 784.50 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 95.67 | 0.00 | 0.00 | 0.00 |
Max | 8664.33 | 8760.00 | 28.00 | 0.00 | 0.00 |
Average | 7793.49 | 965.29 | 1.22 | 0.00 | 0.00 |
Sum | 179250.33 | 22201.67 | 28.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 360784.00 | 7832.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 329357.67 | 1383.33 | 72.00 | 0.00 | 0.00 |
CORE_MID | 329666.33 | 1146.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330151.00 | 662.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24890.83 | 18.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1784.33 | 483.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1741.00 | 527.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1708.83 | 559.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 103395.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 360784.00 | 103395.00 | 72.00 | 0.00 | 0.00 |
Average | 75287.99 | 5043.79 | 3.13 | 0.00 | 0.00 |
Sum | 1731623.83 | 116007.17 | 72.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:39
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.495499E+11 | 94162.41 | 30-JAN-04:12 | 9.00 | 8.26 | 0.567363E+10 | 7499.45 | 10-JAN-14:20 | 9.00 | 8.26 |
February | 0.424291E+11 | 91447.70 | 21-FEB-04:13 | 7.33 | 6.01 | 0.514364E+10 | 7500.25 | 01-FEB-14:20 | 7.33 | 6.01 |
March | 0.501312E+11 | 93195.44 | 20-MAR-03:02 | 8.50 | 8.42 | 0.613806E+10 | 7499.46 | 01-MAR-14:20 | 8.50 | 8.42 |
April | 0.471496E+11 | 92631.32 | 17-APR-03:02 | 10.00 | 8.82 | 0.545419E+10 | 7499.37 | 13-APR-09:00 | 10.00 | 8.82 |
May | 0.475420E+11 | 91716.21 | 15-MAY-03:13 | 9.00 | 8.43 | 0.590434E+10 | 7499.44 | 05-MAY-13:00 | 9.00 | 8.43 |
June | 0.485411E+11 | 86565.59 | 05-JUN-03:02 | 12.00 | 11.37 | 0.588502E+10 | 7499.14 | 21-JUN-13:20 | 23.67 | 16.91 |
July | 0.493892E+11 | 83009.23 | 17-JUL-03:02 | 14.17 | 13.59 | 0.547593E+10 | 7499.08 | 13-JUL-09:50 | 14.17 | 13.59 |
August | 0.543108E+11 | 82297.70 | 28-AUG-03:02 | 14.00 | 14.00 | 0.614134E+10 | 7510.54 | 07-AUG-09:30 | 14.00 | 14.00 |
September | 0.486796E+11 | 84075.44 | 20-SEP-04:03 | 11.17 | 10.03 | 0.545598E+10 | 7499.33 | 21-SEP-09:09 | 19.33 | 17.40 |
October | 0.530694E+11 | 92350.55 | 30-OCT-03:02 | 9.00 | 6.92 | 0.567689E+10 | 7544.03 | 16-OCT-13:20 | 9.00 | 6.92 |
November | 0.519637E+11 | 93332.55 | 24-NOV-04:03 | 7.17 | 1.09 | 0.562012E+10 | 7499.80 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.514722E+11 | 92491.15 | 11-DEC-04:03 | 8.00 | 7.91 | 0.547735E+10 | 7500.06 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.594228E+12 | 0.680465E+11 | ||||||||
Minimum of Months | 0.424291E+11 | 82297.70 | 7.17 | 1.09 | 0.514364E+10 | 7499.08 | 7.33 | 6.01 | ||
Maximum of Months | 0.543108E+11 | 94162.41 | 14.17 | 14.00 | 0.614134E+10 | 7544.03 | 23.67 | 17.40 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.415651E+11 | 82935.27 | 02-JAN-04:02 | 10.17 | 8.61 | 0.507653E+10 | 6735.03 | 10-JAN-14:09 | 16.83 | 11.85 |
February | 0.394483E+11 | 79608.32 | 21-FEB-04:03 | 7.17 | 5.77 | 0.460353E+10 | 6735.63 | 01-FEB-14:09 | 7.17 | 5.77 |
March | 0.488740E+11 | 78227.32 | 20-MAR-03:02 | 8.50 | 8.42 | 0.549989E+10 | 6735.02 | 01-MAR-14:09 | 8.50 | 8.42 |
April | 0.528916E+11 | 77815.82 | 17-APR-03:02 | 10.00 | 8.82 | 0.488113E+10 | 6735.12 | 13-APR-09:00 | 10.00 | 8.82 |
May | 0.454445E+11 | 78623.94 | 30-MAY-03:02 | 11.83 | 10.73 | 0.528441E+10 | 6735.16 | 03-MAY-13:00 | 11.83 | 10.73 |
June | 0.499339E+11 | 80251.94 | 12-JUN-03:02 | 13.00 | 11.87 | 0.527131E+10 | 6734.73 | 22-JUN-09:00 | 23.00 | 17.27 |
July | 0.573123E+11 | 77203.47 | 06-JUL-03:02 | 13.17 | 12.60 | 0.489386E+10 | 6734.75 | 11-JUL-09:09 | 19.33 | 16.00 |
August | 0.638882E+11 | 72632.63 | 29-AUG-05:02 | 15.83 | 14.60 | 0.549523E+10 | 6734.63 | 22-AUG-13:09 | 15.83 | 14.60 |
September | 0.455940E+11 | 80993.42 | 05-SEP-03:02 | 15.17 | 13.86 | 0.488117E+10 | 6734.73 | 01-SEP-13:09 | 15.17 | 13.86 |
October | 0.510167E+11 | 81800.11 | 10-OCT-03:02 | 13.00 | 12.44 | 0.507754E+10 | 6735.04 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.484013E+11 | 84565.66 | 13-NOV-04:02 | 11.83 | 10.73 | 0.503030E+10 | 6735.38 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.500605E+11 | 81994.40 | 26-DEC-04:02 | 8.33 | 1.44 | 0.490181E+10 | 6735.70 | 20-DEC-14:00 | 8.33 | 1.44 |
Annual Sum or Average | 0.594430E+12 | 0.608967E+11 | ||||||||
Minimum of Months | 0.394483E+11 | 72632.63 | 7.17 | 1.44 | 0.460353E+10 | 6734.63 | 7.17 | 1.44 | ||
Maximum of Months | 0.638882E+11 | 84565.66 | 15.83 | 14.60 | 0.549989E+10 | 6735.70 | 23.00 | 17.27 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303133E+11 | 69762.88 | 20-JAN-06:03 | 11.33 | 10.71 | 0.501046E+10 | 6734.97 | 10-JAN-14:09 | 11.33 | 10.71 |
February | 0.280318E+11 | 68044.68 | 03-FEB-06:03 | 12.33 | 3.94 | 0.455420E+10 | 6735.48 | 01-FEB-14:09 | 12.33 | 3.94 |
March | 0.327240E+11 | 71288.43 | 24-MAR-05:02 | 12.00 | 12.00 | 0.544777E+10 | 6734.95 | 01-MAR-14:09 | 12.00 | 12.00 |
April | 0.337628E+11 | 71955.91 | 13-APR-05:02 | 12.00 | 11.91 | 0.484917E+10 | 6735.04 | 13-APR-13:00 | 20.00 | 15.65 |
May | 0.360591E+11 | 71849.17 | 25-MAY-05:02 | 14.83 | 13.74 | 0.525961E+10 | 6735.12 | 03-MAY-13:00 | 14.83 | 13.74 |
June | 0.383158E+11 | 71991.61 | 07-JUN-05:02 | 13.17 | 12.03 | 0.525368E+10 | 6734.71 | 22-JUN-09:00 | 23.00 | 17.27 |
July | 0.396032E+11 | 69819.85 | 21-JUL-04:03 | 17.00 | 16.37 | 0.488290E+10 | 6734.74 | 07-JUL-13:09 | 17.00 | 16.37 |
August | 0.425194E+11 | 69892.58 | 15-AUG-04:03 | 17.00 | 16.37 | 0.548604E+10 | 6734.75 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.367907E+11 | 71381.85 | 02-SEP-05:02 | 14.33 | 11.88 | 0.486508E+10 | 6734.75 | 01-SEP-13:09 | 14.33 | 11.88 |
October | 0.382656E+11 | 72153.39 | 10-OCT-05:02 | 11.83 | 11.29 | 0.505755E+10 | 6734.96 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.324918E+11 | 71063.04 | 02-NOV-05:02 | 11.67 | 10.11 | 0.499352E+10 | 6735.17 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.315272E+11 | 69774.28 | 08-DEC-06:03 | 11.95 | 11.53 | 0.484860E+10 | 6735.50 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.420405E+12 | 0.605086E+11 | ||||||||
Minimum of Months | 0.280318E+11 | 68044.68 | 11.33 | 3.94 | 0.455420E+10 | 6734.71 | 11.33 | 3.94 | ||
Maximum of Months | 0.425194E+11 | 72153.39 | 17.00 | 16.37 | 0.548604E+10 | 6735.50 | 23.00 | 17.27 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236837E+11 | 30408.34 | 19-JAN-16:20 | 18.67 | 14.64 | 0.466636E+10 | 6734.68 | 25-JAN-14:00 | 17.00 | 13.48 |
February | 0.224693E+11 | 30557.29 | 02-FEB-16:20 | 17.67 | 13.13 | 0.429556E+10 | 6735.53 | 01-FEB-14:09 | 17.67 | 13.13 |
March | 0.270396E+11 | 46078.24 | 24-MAR-05:02 | 12.00 | 12.00 | 0.515120E+10 | 6734.70 | 09-MAR-14:09 | 12.00 | 12.00 |
April | 0.310799E+11 | 65212.55 | 27-APR-05:03 | 15.00 | 14.41 | 0.476933E+10 | 6735.04 | 13-APR-13:00 | 15.00 | 14.41 |
May | 0.332891E+11 | 64845.59 | 04-MAY-05:03 | 14.33 | 12.38 | 0.519100E+10 | 6735.16 | 03-MAY-13:00 | 14.33 | 12.38 |
June | 0.377614E+11 | 67051.34 | 28-JUN-05:03 | 16.17 | 15.98 | 0.522662E+10 | 6734.66 | 22-JUN-09:00 | 16.17 | 15.98 |
July | 0.405443E+11 | 68293.91 | 28-JUL-05:04 | 17.00 | 17.00 | 0.487147E+10 | 6734.70 | 07-JUL-13:09 | 17.00 | 17.00 |
August | 0.429646E+11 | 68016.22 | 01-AUG-05:02 | 17.00 | 15.07 | 0.547194E+10 | 6734.71 | 29-AUG-13:09 | 25.67 | 17.79 |
September | 0.346866E+11 | 67973.84 | 25-SEP-05:03 | 17.00 | 16.37 | 0.483119E+10 | 6734.71 | 01-SEP-13:09 | 17.00 | 16.37 |
October | 0.343471E+11 | 67096.69 | 06-OCT-05:03 | 19.00 | 17.08 | 0.499255E+10 | 6734.83 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.254444E+11 | 31914.35 | 01-NOV-05:03 | 12.83 | 9.89 | 0.480164E+10 | 6735.09 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.242255E+11 | 29835.74 | 07-DEC-16:20 | 17.33 | 14.71 | 0.456074E+10 | 6735.39 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.377536E+12 | 0.588296E+11 | ||||||||
Minimum of Months | 0.224693E+11 | 29835.74 | 12.00 | 9.89 | 0.429556E+10 | 6734.66 | 12.00 | 12.00 | ||
Maximum of Months | 0.429646E+11 | 68293.91 | 19.00 | 17.08 | 0.547194E+10 | 6735.53 | 26.83 | 17.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366535E+10 | 5105.62 | 17-JAN-13:40 | 23.33 | 17.00 | 0.617686E+09 | 845.63 | 24-JAN-14:39 | 24.67 | 15.21 |
February | 0.358967E+10 | 4238.08 | 21-FEB-13:10 | 20.67 | 13.69 | 0.566601E+09 | 845.73 | 01-FEB-14:09 | 20.67 | 13.69 |
March | 0.452348E+10 | 5104.38 | 13-MAR-13:40 | 17.67 | 13.75 | 0.678230E+09 | 845.65 | 01-MAR-14:09 | 17.67 | 13.75 |
April | 0.572060E+10 | 6141.57 | 26-APR-14:00 | 26.00 | 16.74 | 0.608510E+09 | 845.67 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.527790E+10 | 5975.38 | 04-MAY-13:40 | 23.00 | 16.67 | 0.659505E+09 | 845.68 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.650502E+10 | 10010.13 | 26-JUN-05:02 | 17.17 | 15.13 | 0.660749E+09 | 845.62 | 22-JUN-09:00 | 17.17 | 15.13 |
July | 0.776127E+10 | 10228.60 | 05-JUL-05:02 | 17.00 | 14.42 | 0.614286E+09 | 845.63 | 07-JUL-13:09 | 22.83 | 17.20 |
August | 0.819276E+10 | 7440.58 | 17-AUG-05:02 | 18.00 | 17.34 | 0.689342E+09 | 845.62 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.534691E+10 | 9184.30 | 30-SEP-05:03 | 23.80 | 13.84 | 0.610091E+09 | 845.63 | 01-SEP-13:09 | 23.80 | 13.84 |
October | 0.580375E+10 | 9945.28 | 16-OCT-05:02 | 18.67 | 9.56 | 0.634061E+09 | 845.65 | 10-OCT-09:09 | 18.67 | 9.56 |
November | 0.446101E+10 | 4897.14 | 28-NOV-14:10 | 24.67 | 11.00 | 0.624001E+09 | 845.69 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.441437E+10 | 5373.97 | 05-DEC-15:00 | 25.00 | 13.22 | 0.604969E+09 | 845.72 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.652621E+11 | 0.756803E+10 | ||||||||
Minimum of Months | 0.358967E+10 | 4238.08 | 17.00 | 9.56 | 0.566601E+09 | 845.62 | 17.17 | 9.56 | ||
Maximum of Months | 0.819276E+10 | 10228.60 | 26.00 | 17.34 | 0.689342E+09 | 845.73 | 26.00 | 17.20 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.325637E+10 | 5588.71 | 20-JAN-09:00 | 17.00 | 13.94 | 0.405122E+09 | 544.98 | 10-JAN-14:09 | 17.00 | 13.94 |
February | 0.306166E+10 | 6499.48 | 21-FEB-08:50 | 13.67 | 9.75 | 0.365562E+09 | 545.02 | 01-FEB-14:09 | 13.67 | 9.75 |
March | 0.385257E+10 | 7344.64 | 23-MAR-08:40 | 18.33 | 14.51 | 0.436994E+09 | 544.98 | 01-MAR-14:09 | 18.33 | 14.51 |
April | 0.515121E+10 | 11639.67 | 30-APR-09:03 | 22.50 | 15.57 | 0.392187E+09 | 545.00 | 13-APR-09:00 | 22.50 | 15.57 |
May | 0.473194E+10 | 10095.19 | 28-MAY-08:33 | 18.67 | 14.13 | 0.425656E+09 | 545.00 | 03-MAY-13:00 | 18.67 | 14.13 |
June | 0.543274E+10 | 11296.22 | 18-JUN-08:13 | 20.00 | 15.82 | 0.425318E+09 | 544.96 | 22-JUN-09:00 | 23.00 | 17.27 |
July | 0.670800E+10 | 15066.07 | 23-JUL-08:23 | 24.00 | 19.32 | 0.395939E+09 | 544.96 | 07-JUL-13:09 | 24.00 | 19.32 |
August | 0.715570E+10 | 11609.96 | 06-AUG-07:53 | 22.00 | 18.09 | 0.444098E+09 | 544.95 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.481059E+10 | 11037.41 | 10-SEP-09:13 | 22.33 | 17.55 | 0.393417E+09 | 544.96 | 12-SEP-09:00 | 23.00 | 17.26 |
October | 0.483308E+10 | 15083.88 | 15-OCT-08:43 | 32.33 | 15.60 | 0.409029E+09 | 544.99 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.360146E+10 | 6113.37 | 20-NOV-08:40 | 12.33 | 11.60 | 0.402676E+09 | 545.00 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.352570E+10 | 6059.33 | 05-DEC-09:00 | 24.00 | 11.80 | 0.390617E+09 | 545.02 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.561210E+11 | 0.488662E+10 | ||||||||
Minimum of Months | 0.306166E+10 | 5588.71 | 12.33 | 9.75 | 0.365562E+09 | 544.95 | 13.67 | 9.75 | ||
Maximum of Months | 0.715570E+10 | 15083.88 | 32.33 | 19.32 | 0.444098E+09 | 545.02 | 24.00 | 19.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.845555E+10 | 18445.08 | 22-JAN-12:23 | 17.00 | 12.16 | 0.632525E+09 | 846.81 | 20-JAN-14:09 | 17.00 | 12.16 |
February | 0.654843E+10 | 18063.87 | 19-FEB-13:13 | 16.20 | 13.29 | 0.570254E+09 | 846.25 | 16-FEB-14:00 | 16.20 | 13.29 |
March | 0.681633E+10 | 14669.98 | 19-MAR-12:43 | 20.17 | 15.26 | 0.678964E+09 | 846.17 | 10-MAR-14:20 | 20.17 | 15.26 |
April | 0.760043E+10 | 10336.85 | 26-APR-13:10 | 26.83 | 17.07 | 0.609231E+09 | 845.70 | 13-APR-13:00 | 26.83 | 17.07 |
May | 0.555142E+10 | 7547.16 | 04-MAY-12:30 | 23.50 | 16.62 | 0.657044E+09 | 845.71 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.632594E+10 | 6956.24 | 30-JUN-12:30 | 23.50 | 17.99 | 0.659349E+09 | 845.64 | 22-JUN-09:00 | 23.50 | 17.99 |
July | 0.803290E+10 | 10936.65 | 31-JUL-05:02 | 17.00 | 16.37 | 0.614193E+09 | 845.65 | 07-JUL-13:09 | 17.00 | 16.37 |
August | 0.101070E+11 | 11194.01 | 30-AUG-12:40 | 23.67 | 17.83 | 0.690152E+09 | 846.21 | 30-AUG-13:00 | 23.00 | 18.43 |
September | 0.846868E+10 | 15904.79 | 04-SEP-13:43 | 21.17 | 16.57 | 0.612567E+09 | 859.56 | 29-SEP-13:30 | 35.00 | 18.05 |
October | 0.101210E+11 | 18769.56 | 01-OCT-11:43 | 25.67 | 20.89 | 0.639097E+09 | 895.82 | 16-OCT-13:09 | 33.75 | 16.65 |
November | 0.916555E+10 | 19392.34 | 19-NOV-12:12 | 26.33 | 15.30 | 0.629957E+09 | 847.14 | 28-NOV-14:00 | 23.00 | 10.79 |
December | 0.987160E+10 | 18631.94 | 03-DEC-13:02 | 16.17 | 12.63 | 0.613893E+09 | 867.04 | 19-DEC-14:09 | 22.83 | 9.79 |
Annual Sum or Average | 0.970648E+11 | 0.760723E+10 | ||||||||
Minimum of Months | 0.555142E+10 | 6956.24 | 16.17 | 12.16 | 0.570254E+09 | 845.64 | 16.20 | 9.79 | ||
Maximum of Months | 0.101210E+11 | 19392.34 | 26.83 | 20.89 | 0.690152E+09 | 895.82 | 35.00 | 18.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.462635E+10 | 7893.98 | 18-JAN-14:50 | 23.27 | 14.80 | 0.405880E+09 | 544.99 | 10-JAN-14:09 | 23.27 | 14.80 |
February | 0.510283E+10 | 10912.31 | 16-FEB-06:03 | 11.98 | 11.91 | 0.371897E+09 | 545.05 | 01-FEB-14:09 | 11.98 | 11.91 |
March | 0.722396E+10 | 17155.16 | 19-MAR-17:23 | 15.50 | 13.71 | 0.445366E+09 | 544.99 | 01-MAR-14:09 | 15.50 | 13.71 |
April | 0.988658E+10 | 19595.62 | 30-APR-15:42 | 22.17 | 15.97 | 0.396870E+09 | 545.00 | 13-APR-13:00 | 22.17 | 15.97 |
May | 0.675577E+10 | 13590.73 | 01-MAY-03:02 | 13.50 | 12.35 | 0.427956E+09 | 545.01 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.885481E+10 | 17878.71 | 04-JUN-16:42 | 18.17 | 14.44 | 0.427945E+09 | 544.96 | 22-JUN-09:00 | 23.00 | 17.27 |
July | 0.112359E+11 | 19595.63 | 23-JUL-16:22 | 24.00 | 19.02 | 0.398337E+09 | 544.96 | 07-JUL-13:09 | 24.00 | 19.02 |
August | 0.129108E+11 | 19763.77 | 20-AUG-15:52 | 22.00 | 17.40 | 0.446706E+09 | 544.95 | 30-AUG-13:00 | 23.00 | 18.43 |
September | 0.708371E+10 | 17950.57 | 17-SEP-15:32 | 19.33 | 15.98 | 0.395944E+09 | 544.96 | 01-SEP-13:09 | 19.33 | 15.98 |
October | 0.769094E+10 | 19350.13 | 15-OCT-15:22 | 30.50 | 15.19 | 0.412075E+09 | 544.98 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.693834E+10 | 19206.41 | 19-NOV-13:32 | 25.67 | 15.08 | 0.407808E+09 | 545.06 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.745991E+10 | 18459.06 | 03-DEC-15:02 | 17.00 | 12.80 | 0.397685E+09 | 545.07 | 20-DEC-14:50 | 19.20 | 11.87 |
Annual Sum or Average | 0.957699E+11 | 0.493447E+10 | ||||||||
Minimum of Months | 0.462635E+10 | 7893.98 | 11.98 | 11.91 | 0.371897E+09 | 544.95 | 11.98 | 11.71 | ||
Maximum of Months | 0.129108E+11 | 19763.77 | 30.50 | 19.02 | 0.446706E+09 | 545.07 | 24.00 | 19.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.260660E+10 | 3268.25 | 18-JAN-14:20 | 24.07 | 14.82 | 0.557637E+09 | 845.62 | 24-JAN-14:39 | 24.67 | 15.21 |
February | 0.245235E+10 | 2722.96 | 03-FEB-14:10 | 23.00 | 8.84 | 0.516728E+09 | 845.60 | 16-FEB-14:30 | 17.05 | 13.87 |
March | 0.287831E+10 | 3280.15 | 24-MAR-15:10 | 18.00 | 15.36 | 0.618508E+09 | 845.62 | 21-MAR-13:09 | 18.00 | 15.36 |
April | 0.331931E+10 | 4654.80 | 26-APR-14:00 | 26.00 | 16.74 | 0.587110E+09 | 845.66 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.385848E+10 | 5178.24 | 04-MAY-14:00 | 23.00 | 16.67 | 0.646797E+09 | 845.67 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.472629E+10 | 5153.03 | 29-JUN-16:00 | 23.00 | 18.43 | 0.655424E+09 | 845.62 | 22-JUN-09:00 | 23.00 | 18.43 |
July | 0.524056E+10 | 8020.94 | 26-JUL-05:02 | 18.00 | 16.69 | 0.611294E+09 | 845.63 | 07-JUL-13:09 | 18.00 | 16.69 |
August | 0.522298E+10 | 5624.26 | 18-AUG-15:00 | 27.00 | 20.85 | 0.684718E+09 | 845.63 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.406666E+10 | 8448.26 | 30-SEP-05:03 | 23.80 | 13.84 | 0.602038E+09 | 845.63 | 01-SEP-13:09 | 23.80 | 13.84 |
October | 0.413057E+10 | 7906.22 | 02-OCT-05:02 | 19.08 | 17.74 | 0.619984E+09 | 845.65 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.282975E+10 | 2936.14 | 28-NOV-13:50 | 24.83 | 10.89 | 0.579651E+09 | 845.62 | 10-NOV-14:00 | 24.83 | 10.89 |
December | 0.273543E+10 | 3066.91 | 05-DEC-14:50 | 24.83 | 13.11 | 0.542928E+09 | 845.63 | 06-DEC-14:00 | 19.00 | 12.39 |
Annual Sum or Average | 0.440673E+11 | 0.722282E+10 | ||||||||
Minimum of Months | 0.245235E+10 | 2722.96 | 18.00 | 8.84 | 0.516728E+09 | 845.60 | 17.05 | 10.89 | ||
Maximum of Months | 0.524056E+10 | 8448.26 | 27.00 | 20.85 | 0.684718E+09 | 845.67 | 26.83 | 18.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245138E+10 | 4707.15 | 20-JAN-09:30 | 18.00 | 14.38 | 0.281439E+09 | 521.21 | 19-JAN-11:20 | 18.00 | 14.38 |
February | 0.230705E+10 | 4478.73 | 21-FEB-10:00 | 17.00 | 11.03 | 0.255751E+09 | 521.26 | 01-FEB-13:00 | 17.00 | 11.03 |
March | 0.286417E+10 | 6746.51 | 23-MAR-09:00 | 19.00 | 14.76 | 0.305499E+09 | 521.22 | 10-MAR-08:20 | 19.00 | 14.76 |
April | 0.396427E+10 | 11302.24 | 30-APR-08:43 | 21.33 | 15.18 | 0.285143E+09 | 521.26 | 13-APR-10:09 | 21.33 | 15.18 |
May | 0.399268E+10 | 7173.65 | 18-MAY-08:50 | 19.50 | 14.41 | 0.308679E+09 | 521.28 | 24-MAY-10:39 | 21.00 | 14.32 |
June | 0.473284E+10 | 11516.68 | 18-JUN-08:53 | 22.00 | 16.85 | 0.310051E+09 | 521.22 | 22-JUN-10:09 | 23.00 | 17.27 |
July | 0.573177E+10 | 15616.04 | 23-JUL-09:02 | 25.00 | 19.70 | 0.291389E+09 | 521.21 | 05-JUL-07:10 | 25.00 | 19.70 |
August | 0.602164E+10 | 11527.82 | 13-AUG-09:43 | 24.00 | 19.80 | 0.325654E+09 | 521.21 | 29-AUG-12:30 | 25.00 | 17.42 |
September | 0.421827E+10 | 11548.59 | 10-SEP-09:03 | 22.17 | 17.48 | 0.286414E+09 | 521.22 | 12-SEP-10:09 | 22.83 | 17.20 |
October | 0.400323E+10 | 15514.74 | 15-OCT-09:13 | 32.33 | 16.14 | 0.297807E+09 | 521.26 | 27-OCT-10:30 | 22.00 | 13.04 |
November | 0.260536E+10 | 4365.29 | 20-NOV-09:00 | 13.00 | 11.87 | 0.287041E+09 | 521.23 | 10-NOV-11:20 | 13.00 | 11.87 |
December | 0.252001E+10 | 4701.37 | 05-DEC-09:30 | 25.00 | 12.45 | 0.273634E+09 | 521.23 | 07-DEC-11:00 | 21.00 | 14.99 |
Annual Sum or Average | 0.454127E+11 | 0.350850E+10 | ||||||||
Minimum of Months | 0.230705E+10 | 4365.29 | 13.00 | 11.03 | 0.255751E+09 | 521.21 | 13.00 | 11.03 | ||
Maximum of Months | 0.602164E+10 | 15616.04 | 32.33 | 19.80 | 0.325654E+09 | 521.28 | 25.00 | 19.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.787607E+10 | 17792.19 | 22-JAN-14:32 | 17.33 | 12.40 | 0.627292E+09 | 862.99 | 18-JAN-14:09 | 17.33 | 12.40 |
February | 0.569719E+10 | 17417.01 | 20-FEB-13:43 | 17.00 | 10.89 | 0.560350E+09 | 846.06 | 01-FEB-14:09 | 17.00 | 10.89 |
March | 0.539213E+10 | 11626.53 | 23-MAR-13:30 | 22.50 | 17.06 | 0.660708E+09 | 845.90 | 01-MAR-14:09 | 22.50 | 17.06 |
April | 0.545497E+10 | 9478.79 | 26-APR-13:10 | 26.83 | 17.07 | 0.600762E+09 | 845.70 | 13-APR-13:00 | 26.83 | 17.07 |
May | 0.446605E+10 | 6864.81 | 04-MAY-12:30 | 23.50 | 16.62 | 0.648178E+09 | 845.71 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.488166E+10 | 6137.22 | 30-JUN-13:10 | 23.00 | 17.85 | 0.654228E+09 | 845.63 | 22-JUN-09:00 | 23.00 | 17.85 |
July | 0.577881E+10 | 9118.17 | 31-JUL-05:02 | 17.00 | 16.37 | 0.611425E+09 | 845.65 | 07-JUL-13:09 | 17.00 | 16.37 |
August | 0.741344E+10 | 10500.23 | 30-AUG-13:00 | 24.00 | 18.12 | 0.687803E+09 | 845.96 | 30-AUG-13:50 | 23.17 | 18.38 |
September | 0.763857E+10 | 14255.04 | 29-SEP-13:20 | 35.33 | 18.10 | 0.610811E+09 | 887.60 | 29-SEP-13:39 | 34.67 | 17.98 |
October | 0.905903E+10 | 19143.37 | 15-OCT-11:52 | 32.00 | 16.89 | 0.637673E+09 | 918.98 | 16-OCT-13:09 | 33.75 | 16.65 |
November | 0.787960E+10 | 17970.92 | 19-NOV-11:02 | 26.00 | 15.13 | 0.625970E+09 | 855.98 | 27-NOV-14:09 | 22.83 | 9.22 |
December | 0.838053E+10 | 18241.76 | 25-DEC-13:52 | 22.00 | 9.96 | 0.608756E+09 | 877.07 | 19-DEC-14:09 | 22.00 | 9.96 |
Annual Sum or Average | 0.799181E+11 | 0.753396E+10 | ||||||||
Minimum of Months | 0.446605E+10 | 6137.22 | 17.00 | 9.96 | 0.560350E+09 | 845.63 | 17.00 | 9.22 | ||
Maximum of Months | 0.905903E+10 | 19143.37 | 35.33 | 18.12 | 0.687803E+09 | 918.98 | 34.67 | 18.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.281427E+10 | 6144.30 | 18-JAN-15:00 | 23.00 | 14.79 | 0.376404E+09 | 544.96 | 20-JAN-14:09 | 17.00 | 14.51 |
February | 0.275878E+10 | 6660.63 | 22-FEB-16:00 | 16.00 | 12.00 | 0.346281E+09 | 545.03 | 01-FEB-14:09 | 16.00 | 12.00 |
March | 0.340780E+10 | 8764.64 | 23-MAR-15:50 | 21.17 | 17.23 | 0.413241E+09 | 544.98 | 01-MAR-14:09 | 21.17 | 17.23 |
April | 0.452886E+10 | 11829.02 | 23-APR-16:22 | 16.50 | 13.77 | 0.387509E+09 | 544.99 | 13-APR-13:00 | 16.50 | 13.77 |
May | 0.460627E+10 | 11821.76 | 28-MAY-16:12 | 19.67 | 14.47 | 0.420737E+09 | 545.01 | 03-MAY-13:00 | 19.67 | 14.47 |
June | 0.562295E+10 | 16519.59 | 25-JUN-16:12 | 21.00 | 16.52 | 0.424326E+09 | 544.95 | 22-JUN-09:00 | 21.00 | 16.52 |
July | 0.641550E+10 | 17017.24 | 04-JUL-16:32 | 19.67 | 15.52 | 0.396584E+09 | 544.95 | 07-JUL-13:09 | 22.83 | 17.20 |
August | 0.669538E+10 | 16598.57 | 06-AUG-16:12 | 23.67 | 19.59 | 0.444571E+09 | 544.95 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.498118E+10 | 14818.12 | 10-SEP-16:23 | 21.50 | 16.68 | 0.392604E+09 | 544.96 | 01-SEP-13:09 | 21.50 | 16.68 |
October | 0.453721E+10 | 17046.62 | 15-OCT-14:32 | 31.00 | 15.41 | 0.404341E+09 | 544.98 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.326211E+10 | 6533.68 | 07-NOV-15:30 | 19.00 | 14.51 | 0.387568E+09 | 545.03 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.301610E+10 | 6439.13 | 19-DEC-15:30 | 21.50 | 8.94 | 0.368939E+09 | 545.04 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.526464E+11 | 0.476310E+10 | ||||||||
Minimum of Months | 0.275878E+10 | 6144.30 | 16.00 | 8.94 | 0.346281E+09 | 544.95 | 16.00 | 12.00 | ||
Maximum of Months | 0.669538E+10 | 17046.62 | 31.00 | 19.59 | 0.444571E+09 | 545.04 | 26.83 | 17.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189360E+10 | 2851.75 | 18-JAN-14:10 | 24.33 | 14.82 | 0.519882E+09 | 841.65 | 19-JAN-14:00 | 20.00 | 15.12 |
February | 0.184996E+10 | 2418.13 | 02-FEB-14:20 | 18.33 | 13.67 | 0.480004E+09 | 830.75 | 16-FEB-14:00 | 17.10 | 13.80 |
March | 0.231366E+10 | 3234.66 | 23-MAR-16:00 | 21.00 | 17.19 | 0.576668E+09 | 845.61 | 23-MAR-13:39 | 21.00 | 17.19 |
April | 0.306497E+10 | 5066.80 | 26-APR-14:00 | 26.00 | 16.74 | 0.565706E+09 | 845.66 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.359837E+10 | 5687.26 | 04-MAY-14:00 | 23.00 | 16.67 | 0.626981E+09 | 845.68 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.465091E+10 | 5784.03 | 30-JUN-14:00 | 23.00 | 17.85 | 0.647271E+09 | 845.61 | 22-JUN-09:00 | 23.00 | 17.85 |
July | 0.533328E+10 | 6601.41 | 19-JUL-15:00 | 27.00 | 20.17 | 0.608426E+09 | 845.63 | 07-JUL-13:09 | 27.00 | 20.17 |
August | 0.524632E+10 | 6260.76 | 18-AUG-15:00 | 27.00 | 20.85 | 0.680048E+09 | 845.62 | 29-AUG-13:09 | 25.67 | 17.79 |
September | 0.386151E+10 | 6951.91 | 29-SEP-14:30 | 33.50 | 17.67 | 0.589956E+09 | 845.63 | 01-SEP-13:09 | 33.50 | 17.67 |
October | 0.376329E+10 | 8889.88 | 05-OCT-05:02 | 20.00 | 18.62 | 0.602153E+09 | 845.63 | 25-OCT-13:00 | 24.00 | 11.58 |
November | 0.224379E+10 | 2805.62 | 19-NOV-13:22 | 26.00 | 15.06 | 0.539390E+09 | 845.59 | 10-NOV-14:00 | 26.00 | 15.06 |
December | 0.198914E+10 | 2912.23 | 19-DEC-13:40 | 24.00 | 10.42 | 0.503281E+09 | 836.32 | 05-DEC-14:00 | 24.00 | 10.42 |
Annual Sum or Average | 0.398088E+11 | 0.693977E+10 | ||||||||
Minimum of Months | 0.184996E+10 | 2418.13 | 18.33 | 10.42 | 0.480004E+09 | 830.75 | 17.10 | 10.42 | ||
Maximum of Months | 0.533328E+10 | 8889.88 | 33.50 | 20.85 | 0.680048E+09 | 845.68 | 33.50 | 20.17 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194432E+10 | 3396.01 | 20-JAN-10:10 | 19.33 | 14.89 | 0.364195E+09 | 544.96 | 24-JAN-14:50 | 24.83 | 15.33 |
February | 0.178491E+10 | 3284.30 | 02-FEB-10:10 | 17.17 | 12.19 | 0.334948E+09 | 545.02 | 01-FEB-14:09 | 17.17 | 12.19 |
March | 0.237142E+10 | 5784.98 | 23-MAR-09:40 | 21.00 | 15.89 | 0.400745E+09 | 544.96 | 09-MAR-14:09 | 21.00 | 15.89 |
April | 0.374187E+10 | 7530.15 | 26-APR-09:20 | 23.33 | 16.79 | 0.384702E+09 | 545.00 | 13-APR-09:00 | 23.33 | 16.79 |
May | 0.381927E+10 | 6736.29 | 04-MAY-09:30 | 21.00 | 15.49 | 0.415499E+09 | 545.00 | 03-MAY-13:00 | 21.00 | 15.49 |
June | 0.479361E+10 | 10010.67 | 25-JUN-09:23 | 22.50 | 16.84 | 0.420210E+09 | 544.96 | 22-JUN-09:00 | 22.50 | 16.84 |
July | 0.592906E+10 | 11852.04 | 04-JUL-08:53 | 22.00 | 15.83 | 0.395185E+09 | 544.96 | 17-JUL-09:39 | 22.33 | 17.42 |
August | 0.620378E+10 | 11010.24 | 13-AUG-09:23 | 24.00 | 19.61 | 0.443110E+09 | 544.96 | 29-AUG-13:09 | 25.67 | 17.79 |
September | 0.413854E+10 | 9305.67 | 10-SEP-08:53 | 22.00 | 17.40 | 0.386944E+09 | 544.96 | 12-SEP-09:00 | 23.00 | 17.26 |
October | 0.373880E+10 | 15312.40 | 15-OCT-08:43 | 32.33 | 15.60 | 0.401158E+09 | 544.98 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.211050E+10 | 3182.37 | 01-NOV-09:30 | 15.00 | 12.66 | 0.376548E+09 | 544.98 | 29-NOV-14:00 | 18.00 | 10.62 |
December | 0.198108E+10 | 3349.69 | 05-DEC-09:50 | 25.67 | 12.88 | 0.353049E+09 | 544.96 | 19-DEC-10:09 | 23.33 | 10.05 |
Annual Sum or Average | 0.425572E+11 | 0.467629E+10 | ||||||||
Minimum of Months | 0.178491E+10 | 3182.37 | 15.00 | 12.19 | 0.334948E+09 | 544.96 | 17.17 | 10.05 | ||
Maximum of Months | 0.620378E+10 | 15312.40 | 32.33 | 19.61 | 0.443110E+09 | 545.02 | 25.67 | 17.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.639897E+10 | 18957.62 | 22-JAN-14:23 | 17.50 | 12.39 | 0.611482E+09 | 846.24 | 20-JAN-14:09 | 17.50 | 12.39 |
February | 0.464402E+10 | 15036.94 | 20-FEB-13:43 | 17.00 | 10.89 | 0.539669E+09 | 846.03 | 01-FEB-14:09 | 17.00 | 10.89 |
March | 0.453678E+10 | 11803.06 | 23-MAR-14:00 | 23.00 | 17.27 | 0.630172E+09 | 845.90 | 23-MAR-13:00 | 23.00 | 17.27 |
April | 0.510792E+10 | 10017.73 | 26-APR-13:10 | 26.83 | 17.07 | 0.587487E+09 | 845.70 | 13-APR-13:00 | 26.83 | 17.07 |
May | 0.416948E+10 | 7353.76 | 04-MAY-12:40 | 23.33 | 16.64 | 0.630901E+09 | 845.71 | 03-MAY-13:00 | 23.33 | 16.64 |
June | 0.482499E+10 | 6776.04 | 30-JUN-13:20 | 23.00 | 17.85 | 0.645693E+09 | 845.63 | 07-JUN-13:00 | 23.00 | 17.85 |
July | 0.591320E+10 | 9365.74 | 31-JUL-13:10 | 27.83 | 21.13 | 0.608589E+09 | 845.65 | 07-JUL-13:09 | 27.83 | 21.13 |
August | 0.751752E+10 | 11086.69 | 30-AUG-13:10 | 23.83 | 18.18 | 0.684937E+09 | 845.67 | 29-AUG-13:09 | 23.83 | 18.18 |
September | 0.741063E+10 | 15526.74 | 29-SEP-13:30 | 35.00 | 18.05 | 0.605065E+09 | 877.68 | 29-SEP-13:39 | 34.67 | 17.98 |
October | 0.850688E+10 | 19849.13 | 15-OCT-12:42 | 32.00 | 16.02 | 0.629593E+09 | 906.98 | 16-OCT-13:20 | 33.40 | 16.49 |
November | 0.656483E+10 | 20190.14 | 19-NOV-13:22 | 26.00 | 15.06 | 0.613594E+09 | 846.14 | 08-NOV-14:50 | 26.00 | 15.06 |
December | 0.675967E+10 | 19045.55 | 25-DEC-13:52 | 22.00 | 9.96 | 0.593858E+09 | 846.11 | 20-DEC-14:00 | 22.00 | 9.96 |
Annual Sum or Average | 0.723549E+11 | 0.738104E+10 | ||||||||
Minimum of Months | 0.416948E+10 | 6776.04 | 17.00 | 9.96 | 0.539669E+09 | 845.63 | 17.00 | 9.96 | ||
Maximum of Months | 0.850688E+10 | 20190.14 | 35.00 | 21.13 | 0.684937E+09 | 906.98 | 34.67 | 21.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235515E+10 | 5776.25 | 18-JAN-15:00 | 23.00 | 14.79 | 0.355895E+09 | 544.96 | 24-JAN-14:00 | 25.00 | 15.45 |
February | 0.235764E+10 | 6250.58 | 22-FEB-16:20 | 15.33 | 12.12 | 0.326053E+09 | 545.04 | 01-FEB-14:09 | 15.33 | 12.12 |
March | 0.305304E+10 | 8835.51 | 23-MAR-15:50 | 21.17 | 17.23 | 0.389737E+09 | 544.96 | 09-MAR-14:09 | 21.17 | 17.23 |
April | 0.438834E+10 | 10531.05 | 02-APR-16:23 | 18.50 | 14.07 | 0.376572E+09 | 544.99 | 13-APR-13:00 | 20.00 | 15.65 |
May | 0.448175E+10 | 11606.36 | 28-MAY-16:12 | 19.67 | 14.47 | 0.409407E+09 | 545.01 | 03-MAY-13:00 | 19.67 | 14.47 |
June | 0.565585E+10 | 17621.40 | 18-JUN-16:33 | 21.33 | 17.27 | 0.419267E+09 | 544.95 | 26-JUN-09:39 | 23.33 | 17.70 |
July | 0.657556E+10 | 18552.39 | 23-JUL-16:32 | 24.00 | 18.92 | 0.395178E+09 | 544.96 | 07-JUL-13:09 | 24.00 | 18.92 |
August | 0.678626E+10 | 18331.76 | 13-AUG-16:22 | 23.50 | 19.73 | 0.442626E+09 | 544.96 | 29-AUG-13:09 | 25.67 | 17.79 |
September | 0.488893E+10 | 14851.90 | 10-SEP-16:23 | 21.50 | 16.68 | 0.386682E+09 | 544.96 | 01-SEP-13:09 | 21.50 | 16.68 |
October | 0.433623E+10 | 17603.31 | 01-OCT-14:43 | 23.17 | 19.60 | 0.394427E+09 | 544.98 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.283392E+10 | 6265.99 | 10-NOV-14:50 | 19.17 | 15.85 | 0.367582E+09 | 545.02 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.250708E+10 | 6209.16 | 19-DEC-15:30 | 21.50 | 8.94 | 0.347547E+09 | 545.04 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.502198E+11 | 0.461097E+10 | ||||||||
Minimum of Months | 0.235515E+10 | 5776.25 | 15.33 | 8.94 | 0.326053E+09 | 544.95 | 15.33 | 12.12 | ||
Maximum of Months | 0.678626E+10 | 18552.39 | 24.00 | 19.73 | 0.442626E+09 | 545.04 | 26.83 | 18.92 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.326832E+10 | 5698.56 | 17-JAN-06:15 | 15.67 | 13.46 | 0.00 | 0.00 | 01-JAN-00:10 | 15.67 | 13.46 |
February | 0.299124E+10 | 5155.45 | 21-FEB-06:15 | 8.00 | 6.97 | 0.00 | 0.00 | 01-FEB-00:10 | 8.00 | 6.97 |
March | 0.361489E+10 | 5455.18 | 13-MAR-05:15 | 11.67 | 10.55 | 0.00 | 0.00 | 01-MAR-00:10 | 11.67 | 10.55 |
April | 0.489994E+10 | 5478.51 | 10-APR-05:15 | 12.00 | 10.34 | 0.00 | 0.00 | 01-APR-00:10 | 12.00 | 10.34 |
May | 0.419880E+10 | 5770.57 | 01-MAY-05:15 | 13.33 | 12.00 | 0.00 | 0.00 | 01-MAY-00:10 | 13.33 | 12.00 |
June | 0.540684E+10 | 6046.27 | 12-JUN-05:15 | 13.47 | 12.39 | 0.00 | 0.00 | 01-JUN-00:10 | 13.47 | 12.39 |
July | 0.646167E+10 | 6859.13 | 05-JUL-05:15 | 17.00 | 14.32 | 0.00 | 0.00 | 01-JUL-00:10 | 17.00 | 14.32 |
August | 0.721799E+10 | 6814.97 | 07-AUG-05:15 | 18.00 | 17.96 | 0.00 | 0.00 | 01-AUG-00:10 | 18.00 | 17.96 |
September | 0.519157E+10 | 8305.01 | 05-SEP-05:15 | 16.00 | 14.76 | 0.00 | 0.00 | 01-SEP-00:10 | 16.00 | 14.76 |
October | 0.578663E+10 | 9640.25 | 02-OCT-05:15 | 19.07 | 17.72 | 0.00 | 0.00 | 01-OCT-00:10 | 19.07 | 17.72 |
November | 0.447944E+10 | 6171.41 | 20-NOV-06:15 | 9.67 | 7.76 | 0.00 | 0.00 | 01-NOV-00:10 | 9.67 | 7.76 |
December | 0.436199E+10 | 7617.90 | 26-DEC-06:15 | 7.00 | 1.09 | 0.00 | 0.00 | 01-DEC-00:10 | 7.00 | 1.09 |
Annual Sum or Average | 0.578793E+11 | 0.00 | ||||||||
Minimum of Months | 0.299124E+10 | 5155.45 | 7.00 | 1.09 | 0.00 | 0.00 | 7.00 | 1.09 | ||
Maximum of Months | 0.721799E+10 | 9640.25 | 19.07 | 17.96 | 0.00 | 0.00 | 19.07 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146433E+10 | 3235.21 | 20-JAN-06:10 | 11.33 | 10.71 | 0.00 | 0.00 | 01-JAN-00:10 | 11.33 | 10.71 |
February | 0.137311E+10 | 2964.25 | 04-FEB-06:10 | 5.67 | 0.59 | 0.00 | 0.00 | 01-FEB-00:10 | 5.67 | 0.59 |
March | 0.142811E+10 | 3435.92 | 24-MAR-05:10 | 12.00 | 12.00 | 0.00 | 0.00 | 01-MAR-00:10 | 12.00 | 12.00 |
April | 0.236827E+10 | 3529.65 | 26-APR-05:10 | 13.83 | 12.28 | 0.00 | 0.00 | 01-APR-00:10 | 13.83 | 12.28 |
May | 0.252269E+10 | 3470.46 | 02-MAY-05:10 | 13.17 | 11.36 | 0.00 | 0.00 | 01-MAY-00:10 | 13.17 | 11.36 |
June | 0.339487E+10 | 3847.74 | 30-JUN-16:00 | 22.70 | 17.88 | 0.00 | 0.00 | 01-JUN-00:10 | 22.70 | 17.88 |
July | 0.422631E+10 | 4427.68 | 26-JUL-05:15 | 18.00 | 16.69 | 0.00 | 0.00 | 01-JUL-00:10 | 18.00 | 16.69 |
August | 0.462346E+10 | 4423.01 | 18-AUG-15:20 | 26.00 | 20.57 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 20.57 |
September | 0.356095E+10 | 4730.01 | 30-SEP-05:15 | 23.80 | 13.84 | 0.00 | 0.00 | 01-SEP-00:10 | 23.80 | 13.84 |
October | 0.367032E+10 | 7552.43 | 02-OCT-05:15 | 19.07 | 17.72 | 0.00 | 0.00 | 01-OCT-00:10 | 19.07 | 17.72 |
November | 0.198119E+10 | 3599.63 | 02-NOV-05:10 | 11.67 | 10.11 | 0.00 | 0.00 | 01-NOV-00:10 | 11.67 | 10.11 |
December | 0.170427E+10 | 3072.18 | 20-DEC-06:10 | 8.67 | 1.20 | 0.00 | 0.00 | 01-DEC-00:10 | 8.67 | 1.20 |
Annual Sum or Average | 0.323179E+11 | 0.00 | ||||||||
Minimum of Months | 0.137311E+10 | 2964.25 | 5.67 | 0.59 | 0.00 | 0.00 | 5.67 | 0.59 | ||
Maximum of Months | 0.462346E+10 | 7552.43 | 26.00 | 20.57 | 0.00 | 0.00 | 26.00 | 20.57 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118655E+10 | 6081.75 | 18-JAN-15:00 | 23.00 | 14.79 | 0.00 | 0.00 | 01-JAN-00:10 | 23.00 | 14.79 |
February | 0.123555E+10 | 5817.18 | 01-FEB-14:10 | 19.00 | 15.70 | 0.00 | 0.00 | 01-FEB-00:10 | 19.00 | 15.70 |
March | 0.198802E+10 | 9467.83 | 23-MAR-14:40 | 22.33 | 17.37 | 0.00 | 0.00 | 01-MAR-00:10 | 22.33 | 17.37 |
April | 0.455991E+10 | 12939.26 | 26-APR-13:50 | 26.17 | 16.81 | 0.00 | 0.00 | 01-APR-00:10 | 26.17 | 16.81 |
May | 0.456791E+10 | 12063.66 | 03-MAY-13:10 | 23.83 | 15.35 | 0.00 | 0.00 | 01-MAY-00:10 | 23.83 | 15.35 |
June | 0.655891E+10 | 12382.90 | 30-JUN-13:10 | 23.00 | 17.85 | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 | 17.85 |
July | 0.845714E+10 | 14077.27 | 19-JUL-13:40 | 27.00 | 20.62 | 0.00 | 0.00 | 01-JUL-00:10 | 27.00 | 20.62 |
August | 0.864798E+10 | 13612.66 | 14-AUG-13:10 | 25.83 | 20.42 | 0.00 | 0.00 | 01-AUG-00:10 | 25.83 | 20.42 |
September | 0.558272E+10 | 13485.73 | 29-SEP-14:00 | 34.00 | 17.85 | 0.00 | 0.00 | 01-SEP-00:10 | 34.00 | 17.85 |
October | 0.460869E+10 | 15165.74 | 16-OCT-14:10 | 31.67 | 15.90 | 0.00 | 0.00 | 01-OCT-00:10 | 31.67 | 15.90 |
November | 0.157745E+10 | 5821.63 | 10-NOV-14:10 | 19.83 | 15.69 | 0.00 | 0.00 | 01-NOV-00:10 | 19.83 | 15.69 |
December | 0.120688E+10 | 5448.67 | 05-DEC-15:00 | 25.00 | 13.22 | 0.00 | 0.00 | 01-DEC-00:10 | 25.00 | 13.22 |
Annual Sum or Average | 0.501777E+11 | 0.00 | ||||||||
Minimum of Months | 0.118655E+10 | 5448.67 | 19.00 | 13.22 | 0.00 | 0.00 | 19.00 | 13.22 | ||
Maximum of Months | 0.864798E+10 | 15165.74 | 34.00 | 20.62 | 0.00 | 0.00 | 34.00 | 20.62 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.392161E+10 | 1941.49 | 30-JAN-16:40 | 14.00 | 11.39 | 95233187.64 | 126.84 | 20-JAN-14:00 | 14.00 | 11.39 |
February | 0.823096E+10 | 3940.97 | 20-FEB-17:00 | 17.00 | 11.53 | 86400483.56 | 126.84 | 13-FEB-14:00 | 17.00 | 11.53 |
March | 0.142831E+11 | 7004.37 | 31-MAR-24:00 | 9.70 | 9.11 | 0.103240E+09 | 126.83 | 24-MAR-13:50 | 9.70 | 9.11 |
April | 0.188397E+11 | 7782.56 | 30-APR-17:30 | 21.00 | 15.77 | 91606884.87 | 126.83 | 05-APR-09:09 | 21.00 | 15.77 |
May | 0.421689E+10 | 3290.27 | 31-MAY-24:00 | 13.10 | 11.97 | 99240654.77 | 126.84 | 05-MAY-13:00 | 13.10 | 11.97 |
June | 0.916218E+10 | 5339.68 | 30-JUN-24:00 | 16.40 | 15.78 | 98967717.69 | 126.85 | 29-JUN-13:50 | 16.40 | 15.78 |
July | 0.145665E+11 | 7204.12 | 31-JUL-23:35 | 18.20 | 17.33 | 91889343.24 | 126.84 | 20-JUL-09:09 | 18.20 | 17.33 |
August | 0.195541E+11 | 7846.51 | 06-AUG-17:40 | 21.67 | 19.02 | 0.103239E+09 | 126.83 | 08-AUG-09:09 | 20.42 | 18.12 |
September | 0.423319E+10 | 3503.01 | 30-SEP-24:00 | 18.40 | 17.30 | 91615557.49 | 126.85 | 08-SEP-13:00 | 18.40 | 17.30 |
October | 0.946212E+10 | 5309.54 | 31-OCT-24:00 | 14.90 | 11.04 | 95236562.39 | 126.85 | 02-OCT-13:00 | 14.90 | 11.04 |
November | 0.139442E+11 | 5835.33 | 12-NOV-16:20 | 16.33 | 13.71 | 94303198.57 | 126.83 | 10-NOV-14:00 | 16.33 | 13.71 |
December | 0.194091E+11 | 7812.66 | 25-DEC-16:15 | 19.33 | 9.96 | 91897178.89 | 127.55 | 19-DEC-10:00 | 19.33 | 9.96 |
Annual Sum or Average | 0.139824E+12 | 0.114287E+10 | ||||||||
Minimum of Months | 0.392161E+10 | 1941.49 | 9.70 | 9.11 | 86400483.56 | 126.83 | 9.70 | 9.11 | ||
Maximum of Months | 0.195541E+11 | 7846.51 | 21.67 | 19.02 | 0.103240E+09 | 127.55 | 21.00 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262760E+10 | 1741.34 | 30-JAN-16:50 | 14.00 | 11.30 | 95232940.05 | 126.84 | 20-JAN-14:00 | 14.00 | 11.30 |
February | 0.691863E+10 | 3655.29 | 22-FEB-17:00 | 14.00 | 12.23 | 86400257.26 | 126.84 | 13-FEB-14:00 | 14.00 | 12.23 |
March | 0.126847E+11 | 6227.95 | 31-MAR-23:40 | 9.83 | 9.24 | 0.103240E+09 | 126.83 | 24-MAR-13:50 | 9.83 | 9.24 |
April | 0.175020E+11 | 7234.40 | 30-APR-17:30 | 21.00 | 15.77 | 91606893.78 | 126.83 | 05-APR-09:09 | 21.00 | 15.77 |
May | 0.349191E+10 | 2946.27 | 31-MAY-24:00 | 13.10 | 11.97 | 99240058.56 | 126.84 | 05-MAY-13:00 | 13.10 | 11.97 |
June | 0.837941E+10 | 5035.00 | 30-JUN-24:00 | 16.40 | 15.78 | 98967235.02 | 126.84 | 29-JUN-13:00 | 16.40 | 15.78 |
July | 0.137218E+11 | 6886.23 | 31-JUL-23:57 | 18.10 | 17.45 | 91888773.11 | 126.84 | 28-JUL-13:00 | 18.10 | 17.45 |
August | 0.185426E+11 | 7322.72 | 06-AUG-17:42 | 21.33 | 19.00 | 0.103239E+09 | 126.83 | 08-AUG-09:09 | 20.42 | 18.12 |
September | 0.362529E+10 | 3328.86 | 30-SEP-24:00 | 18.40 | 17.30 | 91612309.32 | 126.84 | 05-SEP-13:39 | 18.40 | 17.30 |
October | 0.852970E+10 | 4895.62 | 31-OCT-24:00 | 14.90 | 11.04 | 95236180.61 | 126.85 | 02-OCT-13:00 | 14.90 | 11.04 |
November | 0.124798E+11 | 5428.28 | 07-NOV-16:20 | 18.33 | 14.34 | 94303036.73 | 126.83 | 10-NOV-14:00 | 19.00 | 15.88 |
December | 0.175207E+11 | 7227.01 | 19-DEC-16:20 | 20.33 | 7.94 | 91881502.64 | 126.83 | 08-DEC-14:00 | 20.33 | 7.94 |
Annual Sum or Average | 0.126024E+12 | 0.114285E+10 | ||||||||
Minimum of Months | 0.262760E+10 | 1741.34 | 9.83 | 7.94 | 86400257.26 | 126.83 | 9.83 | 7.94 | ||
Maximum of Months | 0.185426E+11 | 7322.72 | 21.33 | 19.00 | 0.103240E+09 | 126.85 | 21.00 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145568E+10 | 1714.08 | 18-JAN-16:10 | 21.83 | 15.33 | 95102568.14 | 126.84 | 20-JAN-14:00 | 17.00 | 14.51 |
February | 0.581791E+10 | 3633.83 | 22-FEB-17:00 | 14.00 | 12.23 | 86400213.45 | 126.84 | 13-FEB-14:00 | 14.00 | 12.23 |
March | 0.116508E+11 | 5782.97 | 31-MAR-23:20 | 9.97 | 9.37 | 0.103240E+09 | 126.83 | 24-MAR-13:50 | 9.97 | 9.37 |
April | 0.169850E+11 | 7290.70 | 30-APR-17:30 | 21.00 | 15.77 | 91607147.95 | 126.83 | 05-APR-09:09 | 21.00 | 15.77 |
May | 0.298020E+10 | 2677.55 | 31-MAY-23:50 | 13.15 | 12.11 | 99240006.84 | 126.84 | 05-MAY-13:00 | 13.15 | 12.11 |
June | 0.815437E+10 | 4929.64 | 30-JUN-24:00 | 16.40 | 15.78 | 98967602.42 | 126.85 | 29-JUN-13:00 | 16.40 | 15.78 |
July | 0.136428E+11 | 6805.33 | 31-JUL-23:57 | 18.10 | 17.45 | 91889204.14 | 126.84 | 28-JUL-13:00 | 18.10 | 17.45 |
August | 0.184334E+11 | 7444.05 | 20-AUG-17:40 | 19.60 | 16.68 | 0.103240E+09 | 126.83 | 08-AUG-09:09 | 19.60 | 16.68 |
September | 0.331313E+10 | 3281.36 | 30-SEP-24:00 | 18.40 | 17.30 | 91612702.23 | 126.85 | 07-SEP-13:00 | 18.40 | 17.30 |
October | 0.802705E+10 | 4677.78 | 31-OCT-23:40 | 15.13 | 11.58 | 95236234.13 | 126.85 | 02-OCT-13:00 | 15.13 | 11.58 |
November | 0.114608E+11 | 5410.14 | 10-NOV-16:20 | 17.67 | 15.55 | 94303104.15 | 126.83 | 10-NOV-14:00 | 17.67 | 15.55 |
December | 0.162222E+11 | 7222.78 | 19-DEC-16:20 | 20.33 | 7.94 | 91881504.08 | 126.83 | 08-DEC-14:00 | 20.33 | 7.94 |
Annual Sum or Average | 0.118143E+12 | 0.114272E+10 | ||||||||
Minimum of Months | 0.145568E+10 | 1714.08 | 9.97 | 7.94 | 86400213.45 | 126.83 | 9.97 | 7.94 | ||
Maximum of Months | 0.184334E+11 | 7444.05 | 21.83 | 17.45 | 0.103240E+09 | 126.85 | 21.00 | 17.45 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238332E+12 | 91372.76 | 17-JAN-15:00 | 20.00 | 15.65 | 0.206144E+10 | 2745.29 | 10-JAN-14:20 | 20.00 | 15.65 |
February | 0.434407E+12 | 182331.78 | 21-FEB-17:00 | 16.00 | 13.03 | 0.187022E+10 | 2745.29 | 06-FEB-14:30 | 16.00 | 13.03 |
March | 0.726640E+12 | 357431.63 | 31-MAR-24:00 | 9.70 | 9.11 | 0.223475E+10 | 2745.29 | 02-MAR-10:09 | 9.70 | 9.11 |
April | 0.940059E+12 | 365477.51 | 10-APR-16:00 | 18.00 | 14.37 | 0.198297E+10 | 2745.29 | 06-APR-13:00 | 18.00 | 14.37 |
May | 0.238261E+12 | 174733.69 | 31-MAY-24:00 | 13.10 | 11.97 | 0.214810E+10 | 2745.29 | 04-MAY-09:39 | 13.10 | 11.97 |
June | 0.466464E+12 | 266403.03 | 30-JUN-24:00 | 16.40 | 15.78 | 0.214213E+10 | 2745.29 | 22-JUN-09:30 | 16.40 | 15.78 |
July | 0.728010E+12 | 358526.83 | 31-JUL-23:53 | 18.10 | 17.45 | 0.198894E+10 | 2745.29 | 12-JUL-09:00 | 18.10 | 17.45 |
August | 0.972902E+12 | 365961.18 | 07-AUG-16:00 | 23.00 | 18.99 | 0.223475E+10 | 2745.29 | 17-AUG-13:39 | 27.33 | 20.97 |
September | 0.232286E+12 | 175385.01 | 30-SEP-24:00 | 18.40 | 17.30 | 0.198297E+10 | 2745.29 | 01-SEP-09:30 | 18.40 | 17.30 |
October | 0.484326E+12 | 267241.15 | 31-OCT-24:00 | 14.90 | 11.04 | 0.206144E+10 | 2745.29 | 20-OCT-13:09 | 14.90 | 11.04 |
November | 0.705599E+12 | 274877.86 | 13-NOV-17:00 | 15.00 | 13.80 | 0.204131E+10 | 2745.29 | 13-NOV-14:50 | 15.00 | 13.80 |
December | 0.974126E+12 | 366446.42 | 26-DEC-17:00 | 16.00 | 8.71 | 0.198894E+10 | 2745.29 | 08-DEC-14:50 | 16.00 | 8.71 |
Annual Sum or Average | 0.714141E+13 | 0.247380E+11 | ||||||||
Minimum of Months | 0.232286E+12 | 91372.76 | 9.70 | 8.71 | 0.187022E+10 | 2745.29 | 9.70 | 8.71 | ||
Maximum of Months | 0.974126E+12 | 366446.42 | 23.00 | 18.99 | 0.223475E+10 | 2745.29 | 27.33 | 20.97 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.555876E+09 | 9862.11 | 23-JAN-04:07 | 9.00 |
February | 0.236921E+09 | 9830.01 | 06-FEB-04:07 | 8.83 |
March | 0.130809E+09 | 9770.92 | 06-MAR-04:07 | 10.92 |
April | 0.166495E+09 | 9633.85 | 01-APR-04:05 | 8.00 |
May | 0.175029E+09 | 9911.50 | 30-MAY-03:27 | 11.50 |
June | 0.155466E+09 | 9545.98 | 01-JUN-04:07 | 12.00 |
July | 0.179048E+09 | 9379.38 | 06-JUL-03:04 | 13.17 |
August | 0.175606E+09 | 9405.90 | 22-AUG-04:37 | 15.33 |
September | 0.343194E+09 | 14087.32 | 30-SEP-15:02 | 31.50 |
October | 0.415140E+09 | 15391.28 | 14-OCT-15:02 | 32.83 |
November | 0.431552E+09 | 11128.75 | 12-NOV-11:23 | 16.50 |
December | 0.331147E+09 | 11186.82 | 25-DEC-19:03 | 14.33 |
Annual Sum or Average | 0.329628E+10 | |||
Minimum of Months | 0.130809E+09 | 9379.38 | 8.00 | |
Maximum of Months | 0.555876E+09 | 15391.28 | 32.83 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197790E+09 | 56125.39 | 02-JAN-05:01 | 11.00 |
February | 15810501.70 | 50169.41 | 27-FEB-06:03 | 11.00 |
March | 6175659.95 | 43606.94 | 30-MAR-05:02 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 7884998.32 | 46037.95 | 26-DEC-06:03 | 7.00 |
Annual Sum or Average | 0.227661E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.97 | |
Maximum of Months | 0.197790E+09 | 56125.39 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 46059976.65 | 8603.21 | 03-JAN-06:02 | 4.67 |
February | 632213.29 | 1911.09 | 27-FEB-06:03 | 11.00 |
March | 19283917.58 | 8533.80 | 30-MAR-05:02 | 4.97 |
April | 728518.20 | 3278.12 | 01-APR-05:03 | 7.83 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 401509.11 | 1650.58 | 24-NOV-06:03 | 8.92 |
December | 6214359.91 | 7966.26 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 73320494.73 | |||
Minimum of Months | 0.00 | 0.00 | 4.67 | |
Maximum of Months | 46059976.65 | 8603.21 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13655928.95 | 8580.92 | 03-JAN-06:02 | 4.67 |
February | 244139.13 | 1477.96 | 28-FEB-06:03 | 10.17 |
March | 10454172.62 | 8672.49 | 30-MAR-05:02 | 4.97 |
April | 237831.50 | 1399.95 | 01-APR-05:03 | 7.83 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 2733567.57 | 6401.90 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 27325639.76 | |||
Minimum of Months | 0.00 | 0.00 | 4.67 | |
Maximum of Months | 13655928.95 | 8672.49 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2288745.36 | 10130.91 | 02-JAN-06:02 | 11.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 8717489.29 | 11516.20 | 30-MAR-05:02 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 354152.23 | 2361.01 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 11360386.88 | |||
Minimum of Months | 0.00 | 0.00 | 4.97 | |
Maximum of Months | 8717489.29 | 11516.20 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3698928.16 | 6657.07 | 02-JAN-06:02 | 11.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 1530610.99 | 4632.62 | 30-MAR-05:02 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 103257.51 | 688.38 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 5332796.65 | |||
Minimum of Months | 0.00 | 0.00 | 4.97 | |
Maximum of Months | 3698928.16 | 6657.07 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.669608E+09 | 11324.53 | 02-JAN-04:02 | 10.17 |
February | 0.300246E+09 | 10387.76 | 27-FEB-05:02 | 11.00 |
March | 0.396079E+09 | 10926.75 | 30-MAR-04:01 | 4.48 |
April | 40881675.55 | 10054.41 | 01-APR-04:03 | 8.00 |
May | 4911974.58 | 9537.18 | 13-MAY-05:02 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 8499799.28 | 9563.43 | 30-OCT-05:03 | 10.83 |
November | 0.174205E+09 | 10307.95 | 24-NOV-05:02 | 8.17 |
December | 0.424981E+09 | 10637.43 | 13-DEC-05:01 | 6.83 |
Annual Sum or Average | 0.201941E+10 | |||
Minimum of Months | 0.00 | 0.00 | 4.48 | |
Maximum of Months | 0.669608E+09 | 11324.53 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253108E+09 | 11460.39 | 03-JAN-05:01 | 3.33 |
February | 0.125599E+09 | 10765.41 | 27-FEB-05:02 | 11.00 |
March | 0.161803E+09 | 11732.11 | 30-MAR-04:01 | 4.48 |
April | 14671033.33 | 9190.11 | 01-APR-05:03 | 7.83 |
May | 1533945.67 | 7549.98 | 13-MAY-05:02 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 1022927.41 | 2915.76 | 30-OCT-05:03 | 10.83 |
November | 50547681.90 | 10621.95 | 24-NOV-05:02 | 8.17 |
December | 0.148173E+09 | 11333.47 | 13-DEC-05:01 | 6.83 |
Annual Sum or Average | 0.756458E+09 | |||
Minimum of Months | 0.00 | 0.00 | 3.33 | |
Maximum of Months | 0.253108E+09 | 11732.11 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174952E+09 | 14435.01 | 02-JAN-05:01 | 11.00 |
February | 0.104718E+09 | 12882.76 | 13-FEB-06:03 | 14.83 |
March | 0.230333E+09 | 14489.23 | 30-MAR-04:01 | 4.48 |
April | 26511871.41 | 12799.02 | 01-APR-05:03 | 7.83 |
May | 8064430.44 | 12803.73 | 13-MAY-05:02 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 14383490.61 | 12572.64 | 24-NOV-06:03 | 8.92 |
December | 71534420.09 | 13987.05 | 13-DEC-05:01 | 6.83 |
Annual Sum or Average | 0.630497E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.48 | |
Maximum of Months | 0.230333E+09 | 14489.23 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176878E+09 | 11584.86 | 02-JAN-05:01 | 11.00 |
February | 45783621.15 | 8624.27 | 28-FEB-06:03 | 10.17 |
March | 91387010.20 | 11203.46 | 30-MAR-04:01 | 4.48 |
April | 10143298.60 | 8719.15 | 01-APR-05:03 | 7.83 |
May | 1000353.42 | 5353.80 | 13-MAY-05:02 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 14727322.29 | 8285.01 | 24-NOV-06:03 | 8.92 |
December | 71344370.95 | 11035.18 | 13-DEC-05:01 | 6.83 |
Annual Sum or Average | 0.411264E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.48 | |
Maximum of Months | 0.176878E+09 | 11584.86 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58975834.56 | 7807.94 | 02-JAN-04:02 | 10.17 |
February | 69188911.55 | 8407.19 | 27-FEB-05:02 | 11.00 |
March | 79036272.99 | 8640.34 | 30-MAR-04:01 | 4.48 |
April | 0.129719E+09 | 8971.81 | 17-APR-03:02 | 10.00 |
May | 64848113.39 | 6209.28 | 15-MAY-04:03 | 8.83 |
June | 54890084.86 | 7060.52 | 12-JUN-03:02 | 13.00 |
July | 0.102905E+09 | 6903.92 | 14-JUL-03:02 | 15.17 |
August | 99870599.00 | 7585.54 | 23-AUG-03:02 | 15.37 |
September | 54165506.72 | 7044.67 | 01-SEP-03:02 | 15.25 |
October | 76766770.36 | 8182.07 | 23-OCT-03:02 | 17.00 |
November | 96192174.38 | 8511.50 | 13-NOV-04:02 | 11.83 |
December | 0.118702E+09 | 10203.79 | 18-DEC-04:02 | 18.00 |
Annual Sum or Average | 0.100526E+10 | |||
Minimum of Months | 54165506.72 | 6209.28 | 4.48 | |
Maximum of Months | 0.129719E+09 | 10203.79 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.270650E+09 | 5507.59 | 17-JAN-06:03 | 15.83 |
February | 0.141489E+09 | 5697.85 | 14-FEB-06:03 | 13.00 |
March | 0.197105E+09 | 5780.92 | 28-MAR-05:02 | 11.83 |
April | 40547678.67 | 4895.61 | 17-APR-05:03 | 11.00 |
May | 35745754.16 | 4928.15 | 08-MAY-05:03 | 14.00 |
June | 31078067.65 | 4627.61 | 12-JUN-04:03 | 13.03 |
July | 38763502.41 | 3514.31 | 07-JUL-04:03 | 17.00 |
August | 34404151.15 | 3856.80 | 30-AUG-04:03 | 18.00 |
September | 35873287.92 | 4361.81 | 25-SEP-04:03 | 17.00 |
October | 45324065.77 | 4648.00 | 15-OCT-13:52 | 31.00 |
November | 42936855.55 | 5206.97 | 13-NOV-05:03 | 11.00 |
December | 73399134.16 | 5314.78 | 19-DEC-06:02 | 16.83 |
Annual Sum or Average | 0.987316E+09 | |||
Minimum of Months | 31078067.65 | 3514.31 | 11.00 | |
Maximum of Months | 0.270650E+09 | 5780.92 | 31.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174204E+10 | 9478.51 | 02-JAN-06:03 | 11.00 |
February | 0.123399E+10 | 6552.08 | 09-FEB-05:03 | 6.57 |
March | 0.147027E+10 | 10565.69 | 24-MAR-05:02 | 12.00 |
April | 0.545278E+09 | 12577.87 | 26-APR-05:02 | 13.83 |
May | 0.444763E+09 | 11074.87 | 04-MAY-05:03 | 14.33 |
June | 0.183590E+09 | 13470.55 | 05-JUN-05:02 | 12.17 |
July | 77903639.22 | 11444.33 | 06-JUL-05:03 | 14.33 |
August | 93371972.23 | 11302.14 | 31-AUG-05:02 | 15.17 |
September | 0.224317E+09 | 11614.22 | 12-SEP-05:02 | 15.00 |
October | 0.469576E+09 | 11783.12 | 18-OCT-05:02 | 15.00 |
November | 0.100593E+10 | 7524.85 | 01-NOV-05:03 | 12.83 |
December | 0.153864E+10 | 6642.13 | 20-DEC-06:02 | 8.67 |
Annual Sum or Average | 0.902968E+10 | |||
Minimum of Months | 77903639.22 | 6552.08 | 6.57 | |
Maximum of Months | 0.174204E+10 | 13470.55 | 15.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137052E+09 | 526.13 | 08-JAN-06:00 | 3.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 406823.54 | 354.61 | 14-MAY-04:45 | 8.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.137459E+09 | |||
Minimum of Months | 0.00 | 0.00 | 3.00 | |
Maximum of Months | 0.137052E+09 | 526.13 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113123E+11 | 11837.83 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.102611E+11 | 11837.83 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.121930E+11 | 11837.83 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.108909E+11 | 11837.83 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.117527E+11 | 11837.83 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.116958E+11 | 11837.83 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.109477E+11 | 11837.83 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.121930E+11 | 11837.83 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.108909E+11 | 11837.83 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.113123E+11 | 11837.83 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.111797E+11 | 11837.83 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.109477E+11 | 11837.83 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.135577E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.102611E+11 | 11837.83 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.121930E+11 | 11837.83 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.837572E+09 | 1334.85 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.706468E+09 | 1204.75 | 27-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.803063E+09 | 960.25 | 16-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.688000E+09 | 882.54 | 21-APR-15:00 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.722976E+09 | 739.96 | 09-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.713683E+09 | 726.57 | 09-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.671975E+09 | 709.46 | 12-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.755728E+09 | 741.42 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.708058E+09 | 1007.37 | 18-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.790405E+09 | 1045.67 | 30-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.815292E+09 | 1334.85 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.828445E+09 | 1334.85 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.904167E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.671975E+09 | 709.46 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.837572E+09 | 1334.85 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.523772E+09 | 860.23 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.449200E+09 | 780.20 | 27-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.514302E+09 | 635.10 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.444368E+09 | 598.69 | 21-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.469612E+09 | 460.34 | 09-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.464009E+09 | 454.02 | 16-JUN-14:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.436807E+09 | 447.34 | 28-JUL-15:39 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.489428E+09 | 458.38 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.453965E+09 | 601.74 | 21-SEP-07:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.496426E+09 | 689.55 | 20-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.516512E+09 | 860.23 | 06-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.514338E+09 | 860.23 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.577274E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.436807E+09 | 447.34 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.523772E+09 | 860.23 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.786776E+09 | 1334.88 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.680842E+09 | 1196.54 | 27-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.791482E+09 | 919.73 | 16-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.688562E+09 | 864.94 | 21-APR-15:00 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.729088E+09 | 743.22 | 09-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.722138E+09 | 734.34 | 09-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.679378E+09 | 719.79 | 12-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.760047E+09 | 743.09 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.702733E+09 | 991.07 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.745597E+09 | 972.45 | 24-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.774199E+09 | 1334.88 | 06-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.771010E+09 | 1334.88 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.883185E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.679378E+09 | 719.79 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.791482E+09 | 1334.88 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522487E+09 | 860.23 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.446694E+09 | 764.84 | 27-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.514562E+09 | 654.47 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.444956E+09 | 591.18 | 05-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.469539E+09 | 568.71 | 09-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.463053E+09 | 534.21 | 09-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.435792E+09 | 475.43 | 12-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.490417E+09 | 582.03 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.456599E+09 | 677.34 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.493195E+09 | 681.54 | 24-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.508834E+09 | 860.23 | 06-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.513583E+09 | 860.23 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.575971E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.435792E+09 | 475.43 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.522487E+09 | 860.23 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.837386E+09 | 1334.85 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.706252E+09 | 1207.54 | 27-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.802876E+09 | 968.02 | 16-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.688074E+09 | 891.86 | 21-APR-15:00 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.722931E+09 | 737.96 | 09-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.713763E+09 | 724.28 | 09-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.672031E+09 | 706.82 | 12-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.755316E+09 | 739.49 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.707986E+09 | 1014.14 | 18-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.789510E+09 | 1049.48 | 30-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.814714E+09 | 1334.85 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.828297E+09 | 1334.85 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.903914E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.672031E+09 | 706.82 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.837386E+09 | 1334.85 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.523554E+09 | 860.23 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.448964E+09 | 780.36 | 27-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.513990E+09 | 637.59 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.444193E+09 | 599.13 | 21-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.469386E+09 | 458.72 | 09-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.463856E+09 | 451.68 | 16-JUN-14:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.436743E+09 | 444.52 | 28-JUL-15:39 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.489292E+09 | 456.90 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.453706E+09 | 603.42 | 21-SEP-07:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.495862E+09 | 689.83 | 20-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.516445E+09 | 860.23 | 06-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.513981E+09 | 860.23 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.576997E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.436743E+09 | 444.52 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.523554E+09 | 860.23 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.787076E+09 | 1334.88 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.681453E+09 | 1199.66 | 27-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.791504E+09 | 928.78 | 16-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.688680E+09 | 874.75 | 21-APR-15:00 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.729053E+09 | 741.25 | 09-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.722144E+09 | 732.13 | 09-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.679449E+09 | 717.27 | 12-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.760088E+09 | 741.18 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.702868E+09 | 998.31 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.746814E+09 | 980.43 | 24-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.774957E+09 | 1334.88 | 06-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.771174E+09 | 1334.88 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.883526E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.679449E+09 | 717.27 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.791504E+09 | 1334.88 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522301E+09 | 860.23 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.446432E+09 | 765.38 | 27-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.514205E+09 | 654.86 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.444698E+09 | 591.60 | 05-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.469321E+09 | 569.15 | 09-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.462826E+09 | 534.69 | 09-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.435625E+09 | 473.77 | 12-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.490217E+09 | 582.46 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.456370E+09 | 677.57 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.492748E+09 | 681.89 | 24-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.508558E+09 | 860.23 | 06-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.513578E+09 | 860.23 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.575688E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.435625E+09 | 473.77 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.522301E+09 | 860.23 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.837427E+09 | 1334.85 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.706195E+09 | 1207.40 | 27-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.802850E+09 | 967.68 | 16-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.688060E+09 | 891.37 | 21-APR-15:00 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.722920E+09 | 737.81 | 09-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.713753E+09 | 724.10 | 09-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.672027E+09 | 706.62 | 12-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.755309E+09 | 739.34 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.707947E+09 | 1013.80 | 18-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.789466E+09 | 1049.67 | 30-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.814669E+09 | 1334.85 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.828263E+09 | 1334.85 | 01-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.903889E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.672027E+09 | 706.62 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.837427E+09 | 1334.85 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.523546E+09 | 860.23 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.448957E+09 | 780.27 | 27-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.513982E+09 | 637.76 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.444181E+09 | 598.84 | 21-APR-15:00 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.469377E+09 | 458.59 | 09-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.463851E+09 | 451.54 | 16-JUN-14:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.436742E+09 | 444.40 | 28-JUL-15:39 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.489280E+09 | 456.77 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.453719E+09 | 603.20 | 21-SEP-07:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.495867E+09 | 689.67 | 20-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.516446E+09 | 860.23 | 06-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.513938E+09 | 860.23 | 01-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.576989E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.436742E+09 | 444.40 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.523546E+09 | 860.23 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.787076E+09 | 1334.88 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.681450E+09 | 1199.51 | 27-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.791488E+09 | 928.43 | 16-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.688636E+09 | 874.26 | 21-APR-15:00 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.729038E+09 | 741.11 | 09-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.722146E+09 | 731.97 | 09-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.679421E+09 | 717.09 | 12-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.760080E+09 | 741.03 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.702835E+09 | 997.96 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.746794E+09 | 980.12 | 24-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.774958E+09 | 1334.88 | 06-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.771175E+09 | 1334.88 | 01-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.883510E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.679421E+09 | 717.09 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.791488E+09 | 1334.88 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522370E+09 | 860.23 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.446431E+09 | 765.30 | 27-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.514197E+09 | 654.65 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.444688E+09 | 591.33 | 05-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.469313E+09 | 568.85 | 09-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.462825E+09 | 534.35 | 09-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.435613E+09 | 473.68 | 12-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.490216E+09 | 582.18 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.456360E+09 | 677.39 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.492773E+09 | 681.71 | 24-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.508559E+09 | 860.23 | 06-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.513588E+09 | 860.23 | 01-DEC-16:40 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.575693E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.435613E+09 | 473.68 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.522370E+09 | 860.23 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.318958E+10 | 3337.76 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.289319E+10 | 3337.76 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.343791E+10 | 3337.76 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.307076E+10 | 3337.76 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.331375E+10 | 3337.76 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.329773E+10 | 3337.76 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.308678E+10 | 3337.76 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.343791E+10 | 3337.76 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.307076E+10 | 3337.76 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.318958E+10 | 3337.76 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.315220E+10 | 3337.76 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.308678E+10 | 3337.76 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.382269E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.289319E+10 | 3337.76 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.343791E+10 | 3337.76 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.113123E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.102611E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.108909E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.117527E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.116958E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.109477E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.108909E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.113123E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.111797E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.109477E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.135577E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.102611E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.837572E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 287154.40 | 0.288780E+09 |
February | 0.136985E+10 | 0.706468E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45304.59 | 0.338452E+09 |
March | 0.163685E+10 | 0.803063E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3560.13 | 0.358981E+09 |
April | 0.145243E+10 | 0.688000E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 369066.03 | 0.206762E+09 |
May | 0.157338E+10 | 0.722976E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.05 | 0.245563E+09 |
June | 0.156900E+10 | 0.713683E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28188.77 | 0.131267E+09 |
July | 0.145680E+10 | 0.671975E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1945404.23 | 90266292.71 |
August | 0.163685E+10 | 0.755728E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2036131.19 | 0.111430E+09 |
September | 0.145243E+10 | 0.708058E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3192183.84 | 0.114062E+09 |
October | 0.150991E+10 | 0.790405E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11853330.37 | 0.183315E+09 |
November | 0.149516E+10 | 0.815292E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 705149.43 | 0.273749E+09 |
December | 0.145680E+10 | 0.828445E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 198863.67 | 0.299883E+09 |
Annual Sum or Average | 0.181194E+11 | 0.904167E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20664388.71 | 0.264251E+10 |
Minimum of Months | 0.136985E+10 | 0.671975E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.05 | 90266292.71 |
Maximum of Months | 0.163685E+10 | 0.837572E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11853330.37 | 0.358981E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.523772E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 171029.19 | 0.195213E+09 |
February | 0.882782E+09 | 0.449200E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30202.09 | 0.225043E+09 |
March | 0.105485E+10 | 0.514302E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.93 | 0.237759E+09 |
April | 0.936002E+09 | 0.444368E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 138912.92 | 0.137991E+09 |
May | 0.101394E+10 | 0.469612E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.35 | 0.166885E+09 |
June | 0.101113E+10 | 0.464009E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18784.11 | 87756355.25 |
July | 0.938820E+09 | 0.436807E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1248593.27 | 61550647.88 |
August | 0.105485E+10 | 0.489428E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1307722.98 | 74312634.24 |
September | 0.936002E+09 | 0.453965E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2125313.14 | 78391202.30 |
October | 0.973041E+09 | 0.496426E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7278150.86 | 0.122721E+09 |
November | 0.963541E+09 | 0.516512E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262469.60 | 0.181317E+09 |
December | 0.938820E+09 | 0.514338E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 131923.04 | 0.196764E+09 |
Annual Sum or Average | 0.116768E+11 | 0.577274E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12713187.48 | 0.176570E+10 |
Minimum of Months | 0.882782E+09 | 0.436807E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.35 | 61550647.88 |
Maximum of Months | 0.105485E+10 | 0.523772E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7278150.86 | 0.237759E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.786776E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 228168.42 | 0.302125E+09 |
February | 0.136988E+10 | 0.680842E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45286.08 | 0.347715E+09 |
March | 0.163688E+10 | 0.791482E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.30 | 0.361331E+09 |
April | 0.145246E+10 | 0.688562E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 208376.87 | 0.212411E+09 |
May | 0.157341E+10 | 0.729088E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.91 | 0.242139E+09 |
June | 0.156904E+10 | 0.722138E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28189.95 | 0.128258E+09 |
July | 0.145684E+10 | 0.679378E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1923099.83 | 90941405.33 |
August | 0.163688E+10 | 0.760047E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1945955.95 | 0.116985E+09 |
September | 0.145246E+10 | 0.702733E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3171983.39 | 0.124829E+09 |
October | 0.150994E+10 | 0.745597E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10110759.99 | 0.199092E+09 |
November | 0.149520E+10 | 0.774199E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97033.36 | 0.289648E+09 |
December | 0.145684E+10 | 0.771010E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 171032.93 | 0.317155E+09 |
Annual Sum or Average | 0.181198E+11 | 0.883185E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17930023.98 | 0.273263E+10 |
Minimum of Months | 0.136988E+10 | 0.679378E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.91 | 90941405.33 |
Maximum of Months | 0.163688E+10 | 0.791482E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10110759.99 | 0.361331E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.522487E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 153034.27 | 0.208652E+09 |
February | 0.882782E+09 | 0.446694E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30203.86 | 0.254267E+09 |
March | 0.105485E+10 | 0.514562E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.78 | 0.269548E+09 |
April | 0.936002E+09 | 0.444956E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 138921.45 | 0.163160E+09 |
May | 0.101394E+10 | 0.469539E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.26 | 0.183347E+09 |
June | 0.101113E+10 | 0.463053E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18788.13 | 0.100209E+09 |
July | 0.938820E+09 | 0.435792E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1244722.32 | 74773495.55 |
August | 0.105485E+10 | 0.490417E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1295396.92 | 94075557.16 |
September | 0.936002E+09 | 0.456599E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2118155.07 | 89126329.19 |
October | 0.973041E+09 | 0.493195E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7047967.63 | 0.143528E+09 |
November | 0.963541E+09 | 0.508834E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114334.83 | 0.209928E+09 |
December | 0.938820E+09 | 0.513583E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 122319.35 | 0.233539E+09 |
Annual Sum or Average | 0.116768E+11 | 0.575971E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12283936.86 | 0.202415E+10 |
Minimum of Months | 0.882782E+09 | 0.435792E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.26 | 74773495.55 |
Maximum of Months | 0.105485E+10 | 0.522487E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7047967.63 | 0.269548E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.837386E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1512055.83 | 0.575055E+09 |
February | 0.136985E+10 | 0.706252E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 137737.78 | 0.671778E+09 |
March | 0.163685E+10 | 0.802876E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 277221.18 | 0.730251E+09 |
April | 0.145243E+10 | 0.688074E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1925881.13 | 0.433690E+09 |
May | 0.157338E+10 | 0.722931E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531133E+09 |
June | 0.156900E+10 | 0.713763E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52731.76 | 0.287756E+09 |
July | 0.145680E+10 | 0.672031E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4768576.23 | 0.202796E+09 |
August | 0.163685E+10 | 0.755316E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5177237.38 | 0.252657E+09 |
September | 0.145243E+10 | 0.707986E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7363966.29 | 0.242485E+09 |
October | 0.150991E+10 | 0.789510E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28452721.84 | 0.379839E+09 |
November | 0.149516E+10 | 0.814714E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3692965.07 | 0.551879E+09 |
December | 0.145680E+10 | 0.828297E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2286536.30 | 0.584865E+09 |
Annual Sum or Average | 0.181194E+11 | 0.903914E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55647630.80 | 0.544418E+10 |
Minimum of Months | 0.136985E+10 | 0.672031E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202796E+09 |
Maximum of Months | 0.163685E+10 | 0.837386E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28452721.84 | 0.730251E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.523554E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 592523.74 | 0.405051E+09 |
February | 0.649041E+09 | 0.448964E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63683.91 | 0.469497E+09 |
March | 0.773965E+09 | 0.513990E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1919.97 | 0.509762E+09 |
April | 0.688021E+09 | 0.444193E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 311420.79 | 0.315564E+09 |
May | 0.744847E+09 | 0.469386E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376139E+09 |
June | 0.742030E+09 | 0.463856E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35135.40 | 0.202101E+09 |
July | 0.690839E+09 | 0.436743E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2770990.04 | 0.152316E+09 |
August | 0.773965E+09 | 0.489292E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2856667.85 | 0.187989E+09 |
September | 0.688021E+09 | 0.453706E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4897890.84 | 0.176414E+09 |
October | 0.715730E+09 | 0.495862E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16425971.63 | 0.271062E+09 |
November | 0.708685E+09 | 0.516445E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1024195.15 | 0.388793E+09 |
December | 0.690839E+09 | 0.513981E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 477874.65 | 0.412697E+09 |
Annual Sum or Average | 0.858171E+10 | 0.576997E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29458273.96 | 0.386738E+10 |
Minimum of Months | 0.649041E+09 | 0.436743E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152316E+09 |
Maximum of Months | 0.773965E+09 | 0.523554E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16425971.63 | 0.509762E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.787076E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 470262.22 | 0.680387E+09 |
February | 0.136988E+10 | 0.681453E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95531.35 | 0.769914E+09 |
March | 0.163688E+10 | 0.791504E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.796283E+09 |
April | 0.145246E+10 | 0.688680E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 547776.22 | 0.479858E+09 |
May | 0.157341E+10 | 0.729053E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543717E+09 |
June | 0.156904E+10 | 0.722144E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52732.84 | 0.287128E+09 |
July | 0.145684E+10 | 0.679449E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4557864.34 | 0.209188E+09 |
August | 0.163688E+10 | 0.760088E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4275462.26 | 0.276858E+09 |
September | 0.145246E+10 | 0.702868E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7237834.25 | 0.288938E+09 |
October | 0.150994E+10 | 0.746814E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22791370.66 | 0.456214E+09 |
November | 0.149520E+10 | 0.774957E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 194641.32 | 0.653894E+09 |
December | 0.145684E+10 | 0.771174E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 347342.24 | 0.709691E+09 |
Annual Sum or Average | 0.181198E+11 | 0.883526E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40570817.68 | 0.615207E+10 |
Minimum of Months | 0.136988E+10 | 0.679449E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209188E+09 |
Maximum of Months | 0.163688E+10 | 0.791504E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22791370.66 | 0.796283E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.522301E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 537782.11 | 0.417424E+09 |
February | 0.882782E+09 | 0.446432E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70175.88 | 0.491743E+09 |
March | 0.105485E+10 | 0.514205E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63367.35 | 0.527368E+09 |
April | 0.936002E+09 | 0.444698E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 816132.14 | 0.336801E+09 |
May | 0.101394E+10 | 0.469321E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398466E+09 |
June | 0.101113E+10 | 0.462826E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35151.72 | 0.215204E+09 |
July | 0.938820E+09 | 0.435625E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2981626.96 | 0.164262E+09 |
August | 0.105485E+10 | 0.490217E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3043559.33 | 0.203325E+09 |
September | 0.936002E+09 | 0.456370E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4880709.28 | 0.193305E+09 |
October | 0.973041E+09 | 0.492748E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17058837.79 | 0.290715E+09 |
November | 0.963541E+09 | 0.508558E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1458126.63 | 0.408154E+09 |
December | 0.938820E+09 | 0.513578E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 618791.07 | 0.434065E+09 |
Annual Sum or Average | 0.116768E+11 | 0.575688E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31564260.26 | 0.408083E+10 |
Minimum of Months | 0.882782E+09 | 0.435625E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164262E+09 |
Maximum of Months | 0.105485E+10 | 0.522301E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17058837.79 | 0.527368E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.837427E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3054612.61 | 0.617782E+09 |
February | 0.136985E+10 | 0.706195E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 279704.27 | 0.719881E+09 |
March | 0.163685E+10 | 0.802850E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 504694.85 | 0.813853E+09 |
April | 0.145243E+10 | 0.688060E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3240711.32 | 0.501285E+09 |
May | 0.157338E+10 | 0.722920E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620207E+09 |
June | 0.156900E+10 | 0.713753E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50745.40 | 0.349668E+09 |
July | 0.145680E+10 | 0.672027E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5658894.88 | 0.255115E+09 |
August | 0.163685E+10 | 0.755309E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5931395.14 | 0.311489E+09 |
September | 0.145243E+10 | 0.707947E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8984910.70 | 0.287838E+09 |
October | 0.150991E+10 | 0.789466E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35507514.98 | 0.429445E+09 |
November | 0.149516E+10 | 0.814669E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6184094.14 | 0.600536E+09 |
December | 0.145680E+10 | 0.828263E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6851880.11 | 0.628098E+09 |
Annual Sum or Average | 0.181194E+11 | 0.903889E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76249158.41 | 0.613520E+10 |
Minimum of Months | 0.136985E+10 | 0.672027E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255115E+09 |
Maximum of Months | 0.163685E+10 | 0.837427E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35507514.98 | 0.813853E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.523546E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1141188.81 | 0.441577E+09 |
February | 0.882782E+09 | 0.448957E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70252.28 | 0.513288E+09 |
March | 0.105485E+10 | 0.513982E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10698.88 | 0.577218E+09 |
April | 0.936002E+09 | 0.444181E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 380679.64 | 0.372791E+09 |
May | 0.101394E+10 | 0.469377E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445988E+09 |
June | 0.101113E+10 | 0.463851E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33819.47 | 0.248481E+09 |
July | 0.938820E+09 | 0.436742E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3243662.57 | 0.193669E+09 |
August | 0.105485E+10 | 0.489280E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3288788.64 | 0.235284E+09 |
September | 0.936002E+09 | 0.453719E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5963552.80 | 0.214090E+09 |
October | 0.973041E+09 | 0.495867E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19665629.59 | 0.313136E+09 |
November | 0.963541E+09 | 0.516446E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1737906.74 | 0.431848E+09 |
December | 0.938820E+09 | 0.513938E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1220000.58 | 0.449508E+09 |
Annual Sum or Average | 0.116768E+11 | 0.576989E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36756180.00 | 0.443688E+10 |
Minimum of Months | 0.882782E+09 | 0.436742E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193669E+09 |
Maximum of Months | 0.105485E+10 | 0.523546E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19665629.59 | 0.577218E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.787076E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 632253.98 | 0.762122E+09 |
February | 0.136988E+10 | 0.681450E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105385.41 | 0.855360E+09 |
March | 0.163688E+10 | 0.791488E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903062E+09 |
April | 0.145246E+10 | 0.688636E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 783590.69 | 0.564122E+09 |
May | 0.157341E+10 | 0.729038E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637468E+09 |
June | 0.156904E+10 | 0.722146E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50746.60 | 0.349292E+09 |
July | 0.145684E+10 | 0.679421E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5474174.09 | 0.263570E+09 |
August | 0.163688E+10 | 0.760080E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4929744.57 | 0.343608E+09 |
September | 0.145246E+10 | 0.702835E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8858805.89 | 0.350567E+09 |
October | 0.150994E+10 | 0.746794E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28067120.89 | 0.536021E+09 |
November | 0.149520E+10 | 0.774958E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 221154.73 | 0.747483E+09 |
December | 0.145684E+10 | 0.771175E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 407908.59 | 0.802044E+09 |
Annual Sum or Average | 0.181198E+11 | 0.883510E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49530885.47 | 0.711472E+10 |
Minimum of Months | 0.136988E+10 | 0.679421E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263570E+09 |
Maximum of Months | 0.163688E+10 | 0.791488E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28067120.89 | 0.903062E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.522370E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1010729.34 | 0.465309E+09 |
February | 0.882782E+09 | 0.446431E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140358.50 | 0.547751E+09 |
March | 0.105485E+10 | 0.514197E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 138298.26 | 0.602485E+09 |
April | 0.936002E+09 | 0.444688E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1177596.04 | 0.399021E+09 |
May | 0.101394E+10 | 0.469313E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473952E+09 |
June | 0.101113E+10 | 0.462825E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33826.51 | 0.262389E+09 |
July | 0.938820E+09 | 0.435613E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3609666.54 | 0.204756E+09 |
August | 0.105485E+10 | 0.490216E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3626501.39 | 0.251099E+09 |
September | 0.936002E+09 | 0.456360E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5962884.64 | 0.234200E+09 |
October | 0.973041E+09 | 0.492773E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21153186.07 | 0.338559E+09 |
November | 0.963541E+09 | 0.508559E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2245599.87 | 0.461549E+09 |
December | 0.938820E+09 | 0.513588E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1609915.08 | 0.483855E+09 |
Annual Sum or Average | 0.116768E+11 | 0.575693E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40708562.25 | 0.472493E+10 |
Minimum of Months | 0.882782E+09 | 0.435613E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204756E+09 |
Maximum of Months | 0.105485E+10 | 0.522370E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21153186.07 | 0.602485E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.318958E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.289319E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.343791E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.307076E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.331375E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.329773E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.308678E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.343791E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.307076E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.318958E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.315220E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.308678E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.382269E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.289319E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.343791E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308433.71 | 0.628956E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55161.61 | 0.729606E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765579E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406732.53 | 0.448078E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519382E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8135.19 | 0.277967E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2668044.32 | 0.199968E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2498039.04 | 0.253010E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5650074.46 | 0.250309E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20867162.62 | 0.403056E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712524.82 | 0.596242E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157006.51 | 0.654848E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33331314.81 | 0.572700E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199968E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20867162.62 | 0.765579E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1070259.81 | 0.104464E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122693.16 | 0.122015E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24222.80 | 0.129093E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1412048.95 | 0.757315E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.896708E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14844.71 | 0.478331E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5159881.43 | 0.346150E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4871099.07 | 0.442361E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10226896.38 | 0.430293E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39133805.26 | 0.686566E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2801688.77 | 0.100520E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575713.09 | 0.108388E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65413153.43 | 0.968252E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346150E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39133805.26 | 0.129093E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2035398.76 | 0.100978E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52073.43 | 0.119361E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132791E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395048.70 | 0.857635E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102197E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586631E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2226093.65 | 0.455904E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1668180.96 | 0.534148E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10297311.83 | 0.508395E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38585113.94 | 0.716099E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3411829.02 | 0.997818E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1142848.67 | 0.103576E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59813898.97 | 0.102457E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455904E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38585113.94 | 0.132791E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 11837.83 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 11837.83 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 11837.83 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 11837.83 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 11837.83 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 11837.83 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 11837.83 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 11837.83 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 11837.83 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 11837.83 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 11837.83 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 11837.83 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 11837.83 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 11837.83 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1334.85 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.22 | 14-JAN-11:00 | 729.33 | 02-JAN-02:55 |
February | 2010.79 | 01-FEB-10:09 | 1204.75 | 27-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 01-FEB-12:00 | 642.69 | 12-FEB-19:00 |
March | 2010.79 | 01-MAR-10:09 | 960.25 | 16-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 | 11-MAR-12:30 | 688.41 | 28-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 882.54 | 21-APR-15:00 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.73 | 30-APR-11:10 | 427.66 | 17-APR-03:00 |
May | 2010.79 | 01-MAY-09:09 | 739.96 | 09-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:00 | 382.22 | 27-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 726.57 | 09-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.04 | 29-JUN-11:00 | 278.03 | 07-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 709.46 | 12-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.21 | 31-JUL-13:00 | 215.87 | 09-JUL-17:10 |
August | 2010.79 | 01-AUG-09:09 | 741.42 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.94 | 06-AUG-12:55 | 197.86 | 21-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1007.37 | 18-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.05 | 29-SEP-14:00 | 234.16 | 04-SEP-17:50 |
October | 2010.79 | 02-OCT-09:09 | 1045.67 | 30-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.59 | 15-OCT-13:00 | 460.59 | 30-OCT-02:53 |
November | 2010.79 | 01-NOV-09:09 | 1334.85 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.80 | 19-NOV-13:00 | 607.30 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 1334.85 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.59 | 05-DEC-10:00 | 557.86 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 709.46 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 197.86 | |||||
Maximum of Months | 2010.79 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 259.59 | 729.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 860.23 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 | 14-JAN-15:00 | 488.99 | 02-JAN-02:55 |
February | 1295.83 | 01-FEB-10:09 | 780.20 | 27-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | 01-FEB-12:00 | 413.07 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 635.10 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 11-MAR-14:00 | 442.70 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 598.69 | 21-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 | 26-APR-13:00 | 279.14 | 17-APR-03:00 |
May | 1295.83 | 01-MAY-09:09 | 460.34 | 09-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:00 | 254.35 | 27-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 454.02 | 16-JUN-14:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 | 29-JUN-11:00 | 180.92 | 07-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 447.34 | 28-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 | 31-JUL-13:00 | 138.02 | 16-JUL-17:50 |
August | 1295.83 | 01-AUG-09:09 | 458.38 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.91 | 17-AUG-14:00 | 126.21 | 21-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 601.74 | 21-SEP-07:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.37 | 29-SEP-14:00 | 180.33 | 03-SEP-07:00 |
October | 1295.83 | 02-OCT-09:09 | 689.55 | 20-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.70 | 15-OCT-13:00 | 308.18 | 30-OCT-02:53 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 06-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 | 19-NOV-13:00 | 395.00 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.39 | 05-DEC-10:00 | 363.67 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 447.34 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 126.21 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 157.70 | 488.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1334.88 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 14-JAN-11:00 | 652.29 | 02-JAN-02:55 |
February | 2010.83 | 01-FEB-10:09 | 1196.54 | 27-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 01-FEB-12:00 | 623.81 | 25-FEB-03:00 |
March | 2010.83 | 01-MAR-10:09 | 919.73 | 16-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 11-MAR-14:00 | 671.11 | 28-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 864.94 | 21-APR-15:00 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.32 | 26-APR-13:00 | 421.97 | 17-APR-03:00 |
May | 2010.83 | 01-MAY-09:09 | 743.22 | 09-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:00 | 371.19 | 27-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 734.34 | 09-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.04 | 29-JUN-11:00 | 273.51 | 07-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 719.79 | 12-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.21 | 31-JUL-13:00 | 213.03 | 09-JUL-17:10 |
August | 2010.83 | 01-AUG-09:09 | 743.09 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.36 | 17-AUG-14:00 | 199.32 | 21-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 991.07 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.67 | 29-SEP-14:00 | 263.95 | 04-SEP-17:50 |
October | 2010.83 | 02-OCT-09:09 | 972.45 | 24-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.98 | 15-OCT-13:00 | 480.34 | 30-OCT-02:53 |
November | 2010.83 | 01-NOV-09:09 | 1334.88 | 06-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.37 | 19-NOV-12:56 | 622.59 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 1334.88 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 | 05-DEC-10:00 | 568.88 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 719.79 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 199.32 | |||||
Maximum of Months | 2010.83 | 1334.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 205.98 | 671.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 860.23 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.23 | 14-JAN-11:00 | 504.29 | 02-JAN-02:55 |
February | 1295.83 | 01-FEB-10:09 | 764.84 | 27-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | 01-FEB-12:00 | 488.11 | 12-FEB-19:00 |
March | 1295.83 | 01-MAR-10:09 | 654.47 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 11-MAR-14:00 | 511.41 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 591.18 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 | 26-APR-13:00 | 340.96 | 17-APR-03:00 |
May | 1295.83 | 01-MAY-09:09 | 568.71 | 09-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:00 | 318.34 | 07-MAY-15:00 |
June | 1295.83 | 01-JUN-09:09 | 534.21 | 09-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 | 29-JUN-11:00 | 227.97 | 04-JUN-17:20 |
July | 1295.83 | 03-JUL-09:09 | 475.43 | 12-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 | 31-JUL-13:00 | 217.42 | 09-JUL-17:10 |
August | 1295.83 | 01-AUG-09:09 | 582.03 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.91 | 17-AUG-14:00 | 176.15 | 27-AUG-18:10 |
September | 1295.83 | 01-SEP-09:09 | 677.34 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.37 | 29-SEP-14:00 | 219.80 | 03-SEP-16:50 |
October | 1295.83 | 02-OCT-09:09 | 681.54 | 24-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.09 | 15-OCT-09:00 | 356.55 | 11-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 06-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.40 | 19-NOV-12:56 | 472.39 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.39 | 05-DEC-10:00 | 422.42 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 475.43 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 176.15 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 148.09 | 511.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1334.85 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.88 | 15-JAN-10:00 | 1243.43 | 27-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 1207.54 | 27-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.44 | 01-FEB-12:00 | 1281.58 | 25-FEB-03:00 |
March | 2010.79 | 01-MAR-10:09 | 968.02 | 16-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 | 11-MAR-14:00 | 1387.00 | 28-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 891.86 | 21-APR-15:00 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.01 | 30-APR-11:00 | 873.10 | 21-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 737.96 | 09-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 865.05 | 20-MAY-18:00 |
June | 2010.79 | 01-JUN-09:09 | 724.28 | 09-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 | 29-JUN-11:00 | 594.15 | 06-JUN-21:10 |
July | 2010.79 | 03-JUL-09:09 | 706.82 | 12-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.07 | 23-JUL-10:53 | 459.21 | 02-JUL-18:55 |
August | 2010.79 | 01-AUG-09:09 | 739.49 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.39 | 06-AUG-13:10 | 426.25 | 21-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 1014.14 | 18-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.61 | 29-SEP-14:00 | 464.26 | 02-SEP-02:00 |
October | 2010.79 | 02-OCT-09:09 | 1049.48 | 30-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 627.36 | 15-OCT-13:00 | 925.98 | 30-OCT-02:53 |
November | 2010.79 | 01-NOV-09:09 | 1334.85 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.36 | 19-NOV-12:52 | 1193.72 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 1334.85 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 148.25 | 25-DEC-12:00 | 1149.63 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 706.82 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.25 | |||||
Maximum of Months | 2010.79 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 627.36 | 1387.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 860.23 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.62 | 15-JAN-14:47 | 839.03 | 27-JAN-05:00 |
February | 1239.33 | 01-FEB-08:09 | 780.36 | 27-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.09 | 01-FEB-12:00 | 848.07 | 25-FEB-03:00 |
March | 1239.33 | 01-MAR-08:09 | 637.59 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 | 11-MAR-14:00 | 913.06 | 28-MAR-22:00 |
April | 1239.33 | 03-APR-07:10 | 599.13 | 21-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.12 | 26-APR-13:00 | 589.97 | 21-APR-22:00 |
May | 1239.33 | 01-MAY-07:10 | 458.72 | 09-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 564.93 | 20-MAY-18:00 |
June | 1239.33 | 01-JUN-07:10 | 451.68 | 16-JUN-14:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.20 | 29-JUN-11:00 | 420.00 | 04-JUN-13:53 |
July | 1239.33 | 03-JUL-07:10 | 444.52 | 28-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.54 | 31-JUL-13:00 | 344.05 | 04-JUL-13:53 |
August | 1239.33 | 01-AUG-07:10 | 456.90 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.13 | 17-AUG-14:00 | 289.43 | 21-AUG-23:53 |
September | 1239.33 | 01-SEP-07:10 | 603.42 | 21-SEP-07:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.06 | 29-SEP-14:00 | 389.07 | 03-SEP-07:00 |
October | 1239.33 | 02-OCT-07:10 | 689.83 | 20-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 337.21 | 15-OCT-12:40 | 645.47 | 30-OCT-02:53 |
November | 1239.33 | 01-NOV-07:10 | 860.23 | 06-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.61 | 19-NOV-12:52 | 813.26 | 23-NOV-04:00 |
December | 1239.33 | 01-DEC-08:09 | 860.23 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 | 17-DEC-12:53 | 779.34 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 444.52 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.43 | |||||
Maximum of Months | 1239.33 | 860.23 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 337.21 | 913.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1334.88 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | 14-JAN-11:00 | 1335.23 | 07-JAN-02:00 |
February | 2010.83 | 01-FEB-10:09 | 1199.66 | 27-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 | 01-FEB-12:00 | 1325.68 | 20-FEB-15:00 |
March | 2010.83 | 01-MAR-10:09 | 928.78 | 16-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1418.46 | 28-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 874.75 | 21-APR-15:00 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.18 | 26-APR-13:00 | 900.89 | 17-APR-03:00 |
May | 2010.83 | 01-MAY-09:09 | 741.25 | 09-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 852.61 | 20-MAY-18:00 |
June | 2010.83 | 01-JUN-09:09 | 732.13 | 09-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 | 29-JUN-11:00 | 594.41 | 07-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 717.27 | 12-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.20 | 23-JUL-10:50 | 467.99 | 02-JUL-18:55 |
August | 2010.83 | 01-AUG-09:09 | 741.18 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.70 | 17-AUG-14:00 | 442.05 | 21-AUG-23:53 |
September | 2010.83 | 01-SEP-09:09 | 998.31 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.06 | 29-SEP-14:00 | 602.62 | 03-SEP-17:45 |
October | 2010.83 | 02-OCT-09:09 | 980.43 | 24-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 473.13 | 15-OCT-13:00 | 1072.32 | 30-OCT-02:53 |
November | 2010.83 | 01-NOV-09:09 | 1334.88 | 06-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.16 | 18-NOV-13:00 | 1330.74 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 1334.88 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.91 | 05-DEC-10:00 | 1251.47 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 717.27 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.05 | |||||
Maximum of Months | 2010.83 | 1334.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 473.13 | 1418.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 860.23 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.72 | 14-JAN-11:00 | 858.40 | 27-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 765.38 | 27-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.79 | 01-FEB-12:00 | 884.97 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 654.86 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.32 | 11-MAR-12:20 | 966.43 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 591.60 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.19 | 30-APR-11:00 | 723.76 | 16-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 569.15 | 09-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 782.12 | 20-MAY-18:00 |
June | 1295.83 | 01-JUN-09:09 | 534.69 | 09-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.20 | 29-JUN-11:00 | 525.13 | 03-JUN-17:08 |
July | 1295.83 | 03-JUL-09:09 | 473.77 | 12-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.24 | 23-JUL-10:50 | 466.19 | 09-JUL-17:20 |
August | 1295.83 | 01-AUG-09:09 | 582.46 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.76 | 06-AUG-12:20 | 378.85 | 27-AUG-18:10 |
September | 1295.83 | 01-SEP-09:09 | 677.57 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.07 | 29-SEP-14:00 | 492.54 | 03-SEP-16:30 |
October | 1295.83 | 02-OCT-09:09 | 681.89 | 24-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 397.95 | 15-OCT-09:00 | 679.18 | 30-OCT-02:53 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 06-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.63 | 19-NOV-11:53 | 859.38 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.05 | 25-DEC-12:00 | 811.35 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 473.77 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.85 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 397.95 | 966.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1334.85 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 209.70 | 15-JAN-10:00 | 1405.83 | 27-JAN-05:07 |
February | 2010.79 | 01-FEB-10:09 | 1207.40 | 27-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.10 | 01-FEB-12:00 | 1391.18 | 25-FEB-03:00 |
March | 2010.79 | 01-MAR-10:09 | 967.68 | 16-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.06 | 11-MAR-13:20 | 1604.90 | 28-MAR-21:05 |
April | 2010.79 | 03-APR-09:09 | 891.37 | 21-APR-15:00 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.13 | 30-APR-10:40 | 1012.25 | 21-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 737.81 | 09-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1007.14 | 20-MAY-18:00 |
June | 2010.79 | 01-JUN-09:09 | 724.10 | 09-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.32 | 29-JUN-11:00 | 720.43 | 06-JUN-21:10 |
July | 2010.79 | 03-JUL-09:09 | 706.62 | 12-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.60 | 23-JUL-10:53 | 601.68 | 09-JUL-17:10 |
August | 2010.79 | 01-AUG-09:09 | 739.34 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.65 | 06-AUG-12:55 | 505.22 | 21-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 1013.80 | 18-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.09 | 29-SEP-14:00 | 579.00 | 24-SEP-15:00 |
October | 2010.79 | 02-OCT-09:09 | 1049.67 | 30-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 780.11 | 15-OCT-09:00 | 1015.17 | 30-OCT-02:53 |
November | 2010.79 | 01-NOV-09:09 | 1334.85 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.44 | 19-NOV-13:00 | 1255.47 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 1334.85 | 01-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.13 | 25-DEC-12:00 | 1287.77 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 706.62 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.22 | |||||
Maximum of Months | 2010.79 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 780.11 | 1604.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 860.23 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.33 | 15-JAN-10:00 | 949.75 | 27-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 780.27 | 27-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.68 | 01-FEB-12:00 | 924.78 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 637.76 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.81 | 11-MAR-14:00 | 1068.73 | 28-MAR-21:05 |
April | 1295.83 | 03-APR-09:09 | 598.84 | 21-APR-15:00 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.38 | 26-APR-13:00 | 691.43 | 21-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 458.59 | 09-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 688.55 | 29-MAY-12:55 |
June | 1295.83 | 01-JUN-09:09 | 451.54 | 16-JUN-14:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.21 | 29-JUN-11:00 | 512.84 | 04-JUN-13:35 |
July | 1295.83 | 03-JUL-09:09 | 444.40 | 28-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.62 | 31-JUL-13:00 | 448.58 | 02-JUL-18:55 |
August | 1295.83 | 01-AUG-09:09 | 456.77 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.05 | 17-AUG-14:00 | 366.20 | 27-AUG-18:20 |
September | 1295.83 | 01-SEP-09:09 | 603.20 | 21-SEP-07:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.39 | 29-SEP-14:00 | 446.81 | 03-SEP-17:55 |
October | 1295.83 | 02-OCT-09:09 | 689.67 | 20-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 422.72 | 15-OCT-13:00 | 716.69 | 30-OCT-02:53 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 06-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.23 | 19-NOV-12:54 | 868.20 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.60 | 17-DEC-13:00 | 878.83 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 444.40 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.20 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 422.72 | 1068.73 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1334.88 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.40 | 15-JAN-10:00 | 1564.82 | 06-JAN-23:00 |
February | 2010.83 | 01-FEB-10:09 | 1199.51 | 27-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.02 | 01-FEB-12:00 | 1588.23 | 20-FEB-15:00 |
March | 2010.83 | 01-MAR-10:09 | 928.43 | 16-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1614.24 | 28-MAR-21:05 |
April | 2010.83 | 03-APR-09:09 | 874.26 | 21-APR-15:00 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.57 | 30-APR-09:53 | 1050.30 | 16-APR-17:53 |
May | 2010.83 | 01-MAY-09:09 | 741.11 | 09-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 997.34 | 20-MAY-18:00 |
June | 2010.83 | 01-JUN-09:09 | 731.97 | 09-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.32 | 29-JUN-11:00 | 721.68 | 06-JUN-21:10 |
July | 2010.83 | 03-JUL-09:09 | 717.09 | 12-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.11 | 23-JUL-10:53 | 615.45 | 09-JUL-17:10 |
August | 2010.83 | 01-AUG-09:09 | 741.03 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.08 | 17-AUG-14:00 | 552.18 | 27-AUG-18:20 |
September | 2010.83 | 01-SEP-09:09 | 997.96 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.06 | 29-SEP-14:00 | 756.55 | 24-SEP-15:00 |
October | 2010.83 | 02-OCT-09:09 | 980.12 | 24-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 575.10 | 15-OCT-13:00 | 1218.45 | 30-OCT-02:53 |
November | 2010.83 | 01-NOV-09:09 | 1334.88 | 06-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.59 | 18-NOV-13:00 | 1453.67 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 1334.88 | 01-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.65 | 05-DEC-10:00 | 1435.42 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 717.09 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552.18 | |||||
Maximum of Months | 2010.83 | 1334.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 575.10 | 1614.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 860.23 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 90.37 | 15-JAN-10:00 | 983.60 | 06-JAN-23:00 |
February | 1295.83 | 01-FEB-10:09 | 765.30 | 27-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.44 | 01-FEB-12:00 | 978.80 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 654.65 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.58 | 11-MAR-12:20 | 1096.97 | 28-MAR-21:10 |
April | 1295.83 | 03-APR-09:09 | 591.33 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.53 | 30-APR-10:40 | 927.89 | 16-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 568.85 | 09-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 915.31 | 20-MAY-18:00 |
June | 1295.83 | 01-JUN-09:09 | 534.35 | 09-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.21 | 29-JUN-11:00 | 657.80 | 03-JUN-17:08 |
July | 1295.83 | 03-JUL-09:09 | 473.68 | 12-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.33 | 23-JUL-10:53 | 613.88 | 09-JUL-17:10 |
August | 1295.83 | 01-AUG-09:09 | 582.18 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.76 | 06-AUG-12:55 | 452.44 | 27-AUG-17:40 |
September | 1295.83 | 01-SEP-09:09 | 677.39 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.39 | 29-SEP-14:00 | 609.48 | 03-SEP-16:20 |
October | 1295.83 | 02-OCT-09:09 | 681.71 | 24-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 499.83 | 15-OCT-09:00 | 771.13 | 30-OCT-02:53 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 06-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.96 | 19-NOV-12:23 | 937.63 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:40 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.13 | 25-DEC-12:10 | 929.54 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 473.68 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.44 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 499.83 | 1096.97 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 3337.76 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 3337.76 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 3337.76 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 3337.76 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 3337.76 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 3337.76 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 3337.76 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 3337.76 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 3337.76 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 3337.76 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 3337.76 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 3337.76 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 3337.76 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.37 | 14-JAN-11:00 | 1589.07 | 02-JAN-02:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.29 | 01-FEB-12:00 | 1382.64 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1469.44 | 28-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.56 | 30-APR-10:53 | 905.57 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 820.31 | 27-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.08 | 29-JUN-11:00 | 575.65 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.82 | 31-JUL-13:00 | 429.26 | 02-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.14 | 17-AUG-14:00 | 411.96 | 21-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 | 29-SEP-13:50 | 504.66 | 04-SEP-17:57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.44 | 15-OCT-13:00 | 983.92 | 30-OCT-02:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.66 | 19-NOV-12:52 | 1342.32 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.40 | 05-DEC-10:00 | 1201.44 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.96 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.44 | 1589.07 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.42 | 15-JAN-10:00 | 2239.01 | 02-JAN-02:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.57 | 01-FEB-12:00 | 2350.05 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.21 | 11-MAR-13:00 | 2485.19 | 28-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.54 | 30-APR-11:00 | 1518.32 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1455.76 | 27-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.01 | 29-JUN-11:00 | 997.82 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.02 | 23-JUL-10:53 | 739.21 | 02-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.76 | 06-AUG-12:55 | 721.68 | 21-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.43 | 29-SEP-13:50 | 819.08 | 04-SEP-18:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 918.81 | 15-OCT-13:00 | 1658.25 | 30-OCT-02:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.36 | 19-NOV-12:52 | 2283.93 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.80 | 05-DEC-10:00 | 2071.29 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 721.68 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 918.81 | 2485.19 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.45 | 15-JAN-10:00 | 2201.80 | 27-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 01-FEB-12:00 | 2271.11 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2577.43 | 28-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.64 | 30-APR-10:53 | 1645.50 | 16-APR-17:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1705.22 | 07-MAY-14:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 1299.13 | 04-JUN-13:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.79 | 31-JUL-13:00 | 1074.07 | 09-JUL-16:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.13 | 17-AUG-14:00 | 876.38 | 27-AUG-17:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.11 | 29-SEP-13:30 | 1071.39 | 24-SEP-15:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1044.23 | 15-OCT-08:55 | 1633.97 | 11-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.10 | 19-NOV-13:00 | 2027.88 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.64 | 25-DEC-11:53 | 2080.54 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 876.38 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1044.23 | 2577.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 94162.41 | 30-JAN-04:12 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 91447.70 | 21-FEB-04:13 | 0.00 | 1973.16 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 93195.44 | 20-MAR-03:02 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 92631.32 | 17-APR-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 91716.21 | 15-MAY-03:13 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86565.59 | 05-JUN-03:02 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83009.23 | 17-JUL-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82297.70 | 28-AUG-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84075.44 | 20-SEP-04:03 | 0.00 | 3945.83 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 92350.55 | 30-OCT-03:02 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 93332.55 | 24-NOV-04:03 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 92491.15 | 11-DEC-04:03 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 82297.70 | 0.00 | 1973.16 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 94162.41 | 0.00 | 3945.83 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 82935.27 | 02-JAN-04:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 79608.32 | 21-FEB-04:03 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 78227.32 | 20-MAR-03:02 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 77815.82 | 17-APR-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 78623.94 | 30-MAY-03:02 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80251.94 | 12-JUN-03:02 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 77203.47 | 06-JUL-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 72632.63 | 29-AUG-05:02 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80993.42 | 05-SEP-03:02 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 81800.11 | 10-OCT-03:02 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84565.66 | 13-NOV-04:02 | 0.00 | 3544.08 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 81994.40 | 26-DEC-04:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 72632.63 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84565.66 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 69762.88 | 20-JAN-06:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 68044.68 | 03-FEB-06:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 71288.43 | 24-MAR-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 71955.91 | 13-APR-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71849.17 | 25-MAY-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 71991.61 | 07-JUN-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 69819.85 | 21-JUL-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 69892.58 | 15-AUG-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 71381.85 | 02-SEP-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72153.39 | 10-OCT-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 71063.04 | 02-NOV-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 69774.28 | 08-DEC-06:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 68044.68 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72153.39 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 30408.34 | 19-JAN-16:20 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30557.29 | 02-FEB-16:20 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 46078.24 | 24-MAR-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65212.55 | 27-APR-05:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 64845.59 | 04-MAY-05:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 67051.34 | 28-JUN-05:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 68293.91 | 28-JUL-05:04 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 68016.22 | 01-AUG-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 67973.84 | 25-SEP-05:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 67096.69 | 06-OCT-05:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 31914.35 | 01-NOV-05:03 | 4836.72 | 3543.64 | 22942.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 29835.74 | 07-DEC-16:20 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 29835.74 | 4836.72 | 3543.64 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 68293.91 | 15316.26 | 10631.20 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5105.62 | 17-JAN-13:40 | 1923.11 | 665.57 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 |
February | 4238.08 | 21-FEB-13:10 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.32 |
March | 5104.38 | 13-MAR-13:40 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.27 |
April | 6141.57 | 26-APR-14:00 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 | 0.00 |
May | 5975.38 | 04-MAY-13:40 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.78 |
June | 10010.13 | 26-JUN-05:02 | 1012.16 | 685.05 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 |
July | 10228.60 | 05-JUL-05:02 | 1012.16 | 664.21 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7440.58 | 17-AUG-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.63 |
September | 9184.30 | 30-SEP-05:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
October | 9945.28 | 16-OCT-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.71 |
November | 4897.14 | 28-NOV-14:10 | 2010.79 | 670.09 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 0.00 |
December | 5373.97 | 05-DEC-15:00 | 2010.79 | 681.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4238.08 | 809.73 | 593.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10228.60 | 2010.79 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 | 62.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5588.71 | 20-JAN-09:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6499.48 | 21-FEB-08:50 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.43 |
March | 7344.64 | 23-MAR-08:40 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11639.67 | 30-APR-09:03 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.77 |
May | 10095.19 | 28-MAY-08:33 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.59 |
June | 11296.22 | 18-JUN-08:13 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.94 |
July | 15066.07 | 23-JUL-08:23 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.37 |
August | 11609.96 | 06-AUG-07:53 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.02 |
September | 11037.41 | 10-SEP-09:13 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.03 |
October | 15083.88 | 15-OCT-08:43 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 103.65 | 0.00 |
November | 6113.37 | 20-NOV-08:40 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6059.33 | 05-DEC-09:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5588.71 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15083.88 | 1239.33 | 409.30 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 103.65 | 113.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18445.08 | 22-JAN-12:23 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.88 |
February | 18063.87 | 19-FEB-13:13 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.23 |
March | 14669.98 | 19-MAR-12:43 | 303.66 | 105.87 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.73 |
April | 10336.85 | 26-APR-13:10 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 19.74 | 0.00 |
May | 7547.16 | 04-MAY-12:30 | 1923.15 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.73 |
June | 6956.24 | 30-JUN-12:30 | 1923.15 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 |
July | 10936.65 | 31-JUL-05:02 | 1012.19 | 738.67 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.48 |
August | 11194.01 | 30-AUG-12:40 | 1923.15 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 |
September | 15904.79 | 04-SEP-13:43 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.79 |
October | 18769.56 | 01-OCT-11:43 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.79 |
November | 19392.34 | 19-NOV-12:12 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.59 |
December | 18631.94 | 03-DEC-13:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6956.24 | 303.66 | 105.87 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19392.34 | 2010.83 | 738.67 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 19.74 | 308.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7893.98 | 18-JAN-14:50 | 1295.83 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 |
February | 10912.31 | 16-FEB-06:03 | 521.82 | 382.31 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 |
March | 17155.16 | 19-MAR-17:23 | 0.00 | 130.94 | 1441.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.88 |
April | 19595.62 | 30-APR-15:42 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.74 |
May | 13590.73 | 01-MAY-03:02 | 0.00 | 238.98 | 2402.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.72 |
June | 17878.71 | 04-JUN-16:42 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.11 |
July | 19595.63 | 23-JUL-16:22 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.73 |
August | 19763.77 | 20-AUG-15:52 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.88 |
September | 17950.57 | 17-SEP-15:32 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.16 |
October | 19350.13 | 15-OCT-15:22 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 56.78 | 0.00 |
November | 19206.41 | 19-NOV-13:32 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 |
December | 18459.06 | 03-DEC-15:02 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7893.98 | 0.00 | 90.96 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19763.77 | 1295.83 | 409.30 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 56.78 | 196.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3268.25 | 18-JAN-14:20 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
February | 2722.96 | 03-FEB-14:10 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 |
March | 3280.15 | 24-MAR-15:10 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.11 |
April | 4654.80 | 26-APR-14:00 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 27.77 | 0.00 |
May | 5178.24 | 04-MAY-14:00 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.63 |
June | 5153.03 | 29-JUN-16:00 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 |
July | 8020.94 | 26-JUL-05:02 | 1012.16 | 675.86 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5624.26 | 18-AUG-15:00 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 42.40 | 0.00 |
September | 8448.26 | 30-SEP-05:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
October | 7906.22 | 02-OCT-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 |
November | 2936.14 | 28-NOV-13:50 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 12.64 | 0.00 |
December | 3066.91 | 05-DEC-14:50 | 2010.79 | 672.01 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 11.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2722.96 | 809.73 | 593.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8448.26 | 2010.79 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 42.40 | 96.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4707.15 | 20-JAN-09:30 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.88 |
February | 4478.73 | 21-FEB-10:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6746.51 | 23-MAR-09:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11302.24 | 30-APR-08:43 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.27 |
May | 7173.65 | 18-MAY-08:50 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.76 |
June | 11516.68 | 18-JUN-08:53 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.21 |
July | 15616.04 | 23-JUL-09:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.45 |
August | 11527.82 | 13-AUG-09:43 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.41 |
September | 11548.59 | 10-SEP-09:03 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.05 |
October | 15514.74 | 15-OCT-09:13 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 219.29 | 0.00 |
November | 4365.29 | 20-NOV-09:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4701.37 | 05-DEC-09:30 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 11.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4365.29 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15616.04 | 1239.33 | 409.30 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 219.29 | 149.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17792.19 | 22-JAN-14:32 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 591.80 |
February | 17417.01 | 20-FEB-13:43 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 986.72 |
March | 11626.53 | 23-MAR-13:30 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.58 |
April | 9478.79 | 26-APR-13:10 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 0.00 |
May | 6864.81 | 04-MAY-12:30 | 1923.15 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.53 |
June | 6137.22 | 30-JUN-13:10 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.99 |
July | 9118.17 | 31-JUL-05:02 | 1012.19 | 738.73 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.96 |
August | 10500.23 | 30-AUG-13:00 | 1923.15 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 |
September | 14255.04 | 29-SEP-13:20 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 187.01 | 0.00 |
October | 19143.37 | 15-OCT-11:52 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 263.96 | 0.00 |
November | 17970.92 | 19-NOV-11:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.36 |
December | 18241.76 | 25-DEC-13:52 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6137.22 | 404.87 | 141.16 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19143.37 | 2010.83 | 738.73 | 4801.30 | 0.00 | 0.00 | 0.00 | 0.00 | 263.96 | 986.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6144.30 | 18-JAN-15:00 | 1295.83 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.53 |
February | 6660.63 | 22-FEB-16:00 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.73 |
March | 8764.64 | 23-MAR-15:50 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.56 |
April | 11829.02 | 23-APR-16:22 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.09 |
May | 11821.76 | 28-MAY-16:12 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.66 |
June | 16519.59 | 25-JUN-16:12 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.98 |
July | 17017.24 | 04-JUL-16:32 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16598.57 | 06-AUG-16:12 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.95 |
September | 14818.12 | 10-SEP-16:23 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.52 |
October | 17046.62 | 15-OCT-14:32 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 144.72 | 0.00 |
November | 6533.68 | 07-NOV-15:30 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.77 |
December | 6439.13 | 19-DEC-15:30 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6144.30 | 260.91 | 90.96 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17046.62 | 1295.83 | 409.30 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 144.72 | 449.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2851.75 | 18-JAN-14:10 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 6.56 | 0.00 |
February | 2418.13 | 02-FEB-14:20 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.41 |
March | 3234.66 | 23-MAR-16:00 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.36 |
April | 5066.80 | 26-APR-14:00 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 32.49 | 0.00 |
May | 5687.26 | 04-MAY-14:00 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.77 |
June | 5784.03 | 30-JUN-14:00 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.63 |
July | 6601.41 | 19-JUL-15:00 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 64.58 | 0.00 |
August | 6260.76 | 18-AUG-15:00 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 50.65 | 0.00 |
September | 6951.91 | 29-SEP-14:30 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 221.53 | 0.00 |
October | 8889.88 | 05-OCT-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2805.62 | 19-NOV-13:22 | 506.08 | 176.44 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 222.11 | 0.00 |
December | 2912.23 | 19-DEC-13:40 | 1923.11 | 664.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 8.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2418.13 | 506.08 | 176.44 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8889.88 | 2010.79 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 222.11 | 135.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3396.01 | 20-JAN-10:10 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.46 |
February | 3284.30 | 02-FEB-10:10 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.93 |
March | 5784.98 | 23-MAR-09:40 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.51 |
April | 7530.15 | 26-APR-09:20 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 |
May | 6736.29 | 04-MAY-09:30 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 |
June | 10010.67 | 25-JUN-09:23 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.14 |
July | 11852.04 | 04-JUL-08:53 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.49 |
August | 11010.24 | 13-AUG-09:23 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.31 |
September | 9305.67 | 10-SEP-08:53 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.02 |
October | 15312.40 | 15-OCT-08:43 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 298.60 | 0.00 |
November | 3182.37 | 01-NOV-09:30 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.68 |
December | 3349.69 | 05-DEC-09:50 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3182.37 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15312.40 | 1295.83 | 409.30 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 298.60 | 206.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18957.62 | 22-JAN-14:23 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 680.48 |
February | 15036.94 | 20-FEB-13:43 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1184.91 |
March | 11803.06 | 23-MAR-14:00 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.61 |
April | 10017.73 | 26-APR-13:10 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 53.05 | 0.00 |
May | 7353.76 | 04-MAY-12:40 | 1923.15 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 |
June | 6776.04 | 30-JUN-13:20 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.63 |
July | 9365.74 | 31-JUL-13:10 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 92.71 | 0.00 |
August | 11086.69 | 30-AUG-13:10 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 |
September | 15526.74 | 29-SEP-13:30 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 233.89 | 0.00 |
October | 19849.13 | 15-OCT-12:42 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 456.17 | 0.00 |
November | 20190.14 | 19-NOV-13:22 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.25 |
December | 19045.55 | 25-DEC-13:52 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6776.04 | 404.87 | 141.16 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20190.14 | 2010.83 | 635.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 456.17 | 1184.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5776.25 | 18-JAN-15:00 | 1295.83 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.09 |
February | 6250.58 | 22-FEB-16:20 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.48 |
March | 8835.51 | 23-MAR-15:50 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.19 |
April | 10531.05 | 02-APR-16:23 | 195.68 | 68.22 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.21 |
May | 11606.36 | 28-MAY-16:12 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.95 |
June | 17621.40 | 18-JUN-16:33 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.26 |
July | 18552.39 | 23-JUL-16:32 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.59 |
August | 18331.76 | 13-AUG-16:22 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.07 |
September | 14851.90 | 10-SEP-16:23 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.40 |
October | 17603.31 | 01-OCT-14:43 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.39 |
November | 6265.99 | 10-NOV-14:50 | 1295.83 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.16 |
December | 6209.16 | 19-DEC-15:30 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5776.25 | 195.68 | 68.22 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.09 | |
Maximum of Months | 18552.39 | 1295.83 | 409.30 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5698.56 | 17-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.40 |
February | 5155.45 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.03 |
March | 5455.18 | 13-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.73 |
April | 5478.51 | 10-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.74 |
May | 5770.57 | 01-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6046.27 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.47 |
July | 6859.13 | 05-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6814.97 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.02 |
September | 8305.01 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9640.25 | 02-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.49 |
November | 6171.41 | 20-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.27 |
December | 7617.90 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5155.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9640.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3235.21 | 20-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.00 |
February | 2964.25 | 04-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.00 |
March | 3435.92 | 24-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.23 |
April | 3529.65 | 26-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.64 |
May | 3470.46 | 02-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.74 |
June | 3847.74 | 30-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.85 |
July | 4427.68 | 26-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4423.01 | 18-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.85 | 0.00 |
September | 4730.01 | 30-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 |
October | 7552.43 | 02-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.05 |
November | 3599.63 | 02-NOV-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.15 |
December | 3072.18 | 20-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2964.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7552.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.85 | 525.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6081.75 | 18-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.67 |
February | 5817.18 | 01-FEB-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.47 |
March | 9467.83 | 23-MAR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.63 |
April | 12939.26 | 26-APR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.66 | 0.00 |
May | 12063.66 | 03-MAY-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.23 |
June | 12382.90 | 30-JUN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.19 |
July | 14077.27 | 19-JUL-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.74 | 0.00 |
August | 13612.66 | 14-AUG-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.10 |
September | 13485.73 | 29-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.53 | 0.00 |
October | 15165.74 | 16-OCT-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.00 | 0.00 |
November | 5821.63 | 10-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.71 |
December | 5448.67 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5448.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15165.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.53 | 214.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1941.49 | 30-JAN-16:40 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3940.97 | 20-FEB-17:00 | 23.38 | 31.66 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7004.37 | 31-MAR-24:00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7782.56 | 30-APR-17:30 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3290.27 | 31-MAY-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5339.68 | 30-JUN-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7204.12 | 31-JUL-23:35 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7846.51 | 06-AUG-17:40 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3503.01 | 30-SEP-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5309.54 | 31-OCT-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5835.33 | 12-NOV-16:20 | 23.38 | 31.66 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7812.66 | 25-DEC-16:15 | 23.38 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1941.49 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7846.51 | 222.14 | 284.97 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1741.34 | 30-JAN-16:50 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3655.29 | 22-FEB-17:00 | 222.14 | 284.97 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6227.95 | 31-MAR-23:40 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7234.40 | 30-APR-17:30 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2946.27 | 31-MAY-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5035.00 | 30-JUN-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6886.23 | 31-JUL-23:57 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7322.72 | 06-AUG-17:42 | 0.00 | 94.99 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3328.86 | 30-SEP-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4895.62 | 31-OCT-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5428.28 | 07-NOV-16:20 | 222.14 | 284.97 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7227.01 | 19-DEC-16:20 | 222.14 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1741.34 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7322.72 | 222.14 | 284.97 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1714.08 | 18-JAN-16:10 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3633.83 | 22-FEB-17:00 | 222.14 | 284.97 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5782.97 | 31-MAR-23:20 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7290.70 | 30-APR-17:30 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2677.55 | 31-MAY-23:50 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4929.64 | 30-JUN-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6805.33 | 31-JUL-23:57 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7444.05 | 20-AUG-17:40 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3281.36 | 30-SEP-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4677.78 | 31-OCT-23:40 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5410.14 | 10-NOV-16:20 | 222.14 | 284.97 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7222.78 | 19-DEC-16:20 | 222.14 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1714.08 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7444.05 | 222.14 | 284.97 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91372.76 | 17-JAN-15:00 | 5027.92 | 3337.76 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182331.78 | 21-FEB-17:00 | 4808.68 | 3337.76 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357431.63 | 31-MAR-24:00 | 0.00 | 185.45 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 365477.51 | 10-APR-16:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 174733.69 | 31-MAY-24:00 | 0.00 | 185.45 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 266403.03 | 30-JUN-24:00 | 0.00 | 185.45 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 358526.83 | 31-JUL-23:53 | 0.00 | 556.35 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 365961.18 | 07-AUG-16:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175385.01 | 30-SEP-24:00 | 0.00 | 185.45 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267241.15 | 31-OCT-24:00 | 0.00 | 185.45 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 274877.86 | 13-NOV-17:00 | 4808.68 | 3337.76 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366446.42 | 26-DEC-17:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91372.76 | 0.00 | 185.45 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 366446.42 | 5027.92 | 3337.76 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.131844E+13 | 942625.09 | 18-JAN-14:30 | 0.725698E+11 | 328617.98 | 03-JAN-07:10 |
February | 0.151340E+13 | 1023927.79 | 03-FEB-16:10 | 0.567417E+11 | 141120.00 | 27-FEB-06:10 |
March | 0.207272E+13 | 1226544.61 | 23-MAR-13:00 | 0.704379E+11 | 303225.22 | 30-MAR-05:10 |
April | 0.237809E+13 | 1413915.12 | 26-APR-13:39 | 0.554863E+11 | 154232.20 | 01-APR-06:10 |
May | 0.135644E+13 | 958230.35 | 03-MAY-12:30 | 0.568959E+11 | 74586.68 | 01-MAY-11:39 |
June | 0.174928E+13 | 1175726.09 | 29-JUN-15:00 | 0.549817E+11 | 73505.05 | 01-JUN-11:20 |
July | 0.222885E+13 | 1425601.73 | 31-JUL-15:50 | 0.530476E+11 | 72571.36 | 07-JUL-11:39 |
August | 0.268460E+13 | 1575027.12 | 18-AUG-15:50 | 0.564446E+11 | 72569.76 | 31-AUG-11:39 |
September | 0.138404E+13 | 1066394.68 | 29-SEP-15:00 | 0.526470E+11 | 73232.60 | 27-SEP-11:39 |
October | 0.182330E+13 | 1206431.36 | 17-OCT-15:00 | 0.553134E+11 | 74118.40 | 24-OCT-11:00 |
November | 0.202135E+13 | 1183344.80 | 28-NOV-16:40 | 0.563899E+11 | 75185.24 | 24-NOV-12:20 |
December | 0.243251E+13 | 1358591.60 | 05-DEC-16:40 | 0.635805E+11 | 195744.56 | 13-DEC-06:10 |
Annual Sum or Average | 0.229630E+14 | 0.704536E+12 | ||||
Minimum of Months | 0.131844E+13 | 942625.09 | 0.526470E+11 | 72569.76 | ||
Maximum of Months | 0.268460E+13 | 1575027.12 | 0.725698E+11 | 328617.98 |
Report: EnergyConsumptionDistrictHeatingCoolingMonthly
For: Meter
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportDISTRICTCOOLING:FACILITY [J] | DISTRICTCOOLING:FACILITY {Maximum} [W] | DISTRICTCOOLING:FACILITY {TIMESTAMP} | DISTRICTHEATING:FACILITY [J] | DISTRICTHEATING:FACILITY {Maximum} [W] | DISTRICTHEATING:FACILITY {TIMESTAMP} | |
January | 0.240378E+12 | 94089.90 | 17-JAN-14:00 | 137382.50 | 4.44 | 18-JAN-00:40 |
February | 0.436267E+12 | 184940.72 | 21-FEB-14:00 | 183520.27 | 13.46 | 01-FEB-00:40 |
March | 0.728865E+12 | 357432.54 | 31-MAR-23:00 | 216888.98 | 11.10 | 31-MAR-23:30 |
April | 0.942033E+12 | 368076.46 | 10-APR-15:00 | 119810.27 | 10.68 | 01-APR-18:30 |
May | 0.240399E+12 | 174737.21 | 31-MAY-23:00 | 117862.34 | 13.50 | 31-MAY-23:40 |
June | 0.468597E+12 | 266404.82 | 30-JUN-23:00 | 154996.57 | 10.96 | 30-JUN-23:30 |
July | 0.729991E+12 | 358526.87 | 31-JUL-23:00 | 89465.99 | 10.17 | 26-JUL-23:30 |
August | 0.975126E+12 | 368560.11 | 07-AUG-15:00 | 58864.41 | 11.49 | 05-AUG-18:30 |
September | 0.234258E+12 | 175385.01 | 30-SEP-23:00 | 125293.74 | 8.70 | 16-SEP-18:40 |
October | 0.486378E+12 | 267242.93 | 31-OCT-23:00 | 158985.21 | 10.96 | 31-OCT-23:30 |
November | 0.707631E+12 | 277565.90 | 13-NOV-14:00 | 196677.80 | 10.16 | 05-NOV-17:30 |
December | 0.976105E+12 | 369114.52 | 26-DEC-14:00 | 206150.04 | 11.08 | 01-DEC-00:30 |
Annual Sum or Average | 0.716603E+13 | 1765898.11 | ||||
Minimum of Months | 0.234258E+12 | 94089.90 | 58864.41 | 4.44 | ||
Maximum of Months | 0.976105E+12 | 369114.52 | 216888.98 | 13.50 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.171725E+12 | 0.349015E+11 | 0.766053E+12 | 0.202778E+12 | 0.718969E+11 | 0.253722E+11 | 0.00 | 0.360743E+11 | 0.963518E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154098E+12 | 0.287002E+11 | 0.978954E+12 | 0.219897E+12 | 0.653306E+11 | 0.194617E+11 | 0.00 | 0.361953E+11 | 0.107664E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182027E+12 | 0.276802E+11 | 0.141687E+13 | 0.284346E+12 | 0.753549E+11 | 0.200543E+11 | 0.00 | 0.512672E+11 | 0.151158E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161665E+12 | 0.229615E+11 | 0.165903E+13 | 0.314137E+12 | 0.832038E+11 | 0.310713E+11 | 0.00 | 0.814911E+11 | 0.245375E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173807E+12 | 0.211832E+11 | 0.774844E+12 | 0.202916E+12 | 0.823974E+11 | 0.341791E+11 | 0.00 | 0.514905E+11 | 0.156195E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172768E+12 | 0.195325E+11 | 0.106252E+13 | 0.235793E+12 | 0.917601E+11 | 0.454274E+11 | 0.00 | 0.910567E+11 | 0.304197E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161865E+12 | 0.204752E+11 | 0.139340E+13 | 0.284102E+12 | 0.101309E+12 | 0.626702E+11 | 0.00 | 0.156449E+12 | 0.485721E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180495E+12 | 0.225013E+11 | 0.173200E+13 | 0.324799E+12 | 0.112980E+12 | 0.682648E+11 | 0.00 | 0.189450E+12 | 0.541077E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162328E+12 | 0.250795E+11 | 0.740713E+12 | 0.196274E+12 | 0.916014E+11 | 0.457601E+11 | 0.00 | 0.913453E+11 | 0.309364E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169980E+12 | 0.300722E+11 | 0.108340E+13 | 0.243505E+12 | 0.907244E+11 | 0.497141E+11 | 0.00 | 0.120722E+12 | 0.351784E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169420E+12 | 0.327441E+11 | 0.135889E+13 | 0.275005E+12 | 0.764253E+11 | 0.281939E+11 | 0.00 | 0.622059E+11 | 0.184621E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166703E+12 | 0.358944E+11 | 0.170972E+13 | 0.324721E+12 | 0.744121E+11 | 0.258874E+11 | 0.00 | 0.752039E+11 | 0.199682E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202688E+13 | 0.321726E+12 | 0.146764E+14 | 0.310827E+13 | 0.101740E+13 | 0.456056E+12 | 0.00 | 0.104295E+13 | 0.313319E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154098E+12 | 0.195325E+11 | 0.740713E+12 | 0.196274E+12 | 0.653306E+11 | 0.194617E+11 | 0.00 | 0.360743E+11 | 0.963518E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182027E+12 | 0.358944E+11 | 0.173200E+13 | 0.324799E+12 | 0.112980E+12 | 0.682648E+11 | 0.00 | 0.189450E+12 | 0.541077E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.148936E+11 | 0.00 | 0.576762E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.436466E+10 | 0.00 | 0.523770E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.103390E+11 | 0.00 | 0.600989E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.814847E+09 | 0.00 | 0.546715E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.123458E+09 | 0.00 | 0.567725E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.549817E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.530476E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.564446E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.526470E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.116135E+09 | 0.00 | 0.551973E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.144635E+10 | 0.00 | 0.549436E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.741396E+10 | 0.00 | 0.561665E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.395119E+11 | 0.00 | 0.665024E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.523770E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.148936E+11 | 0.00 | 0.600989E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 198852.03 | 02-JAN-16:49 | 37611.08 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 132040.64 | 31-JAN-08:20 | 87083.87 | 18-JAN-15:50 | 52767.68 | 18-JAN-14:30 | 0.00 | 01-JAN-00:10 |
February | 193597.83 | 27-FEB-16:00 | 37611.08 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 147224.25 | 10-FEB-08:20 | 88668.07 | 03-FEB-15:39 | 41838.73 | 03-FEB-13:20 | 0.00 | 01-FEB-00:10 |
March | 183082.45 | 16-MAR-07:10 | 37611.08 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 162412.95 | 16-MAR-07:19 | 105313.52 | 23-MAR-15:09 | 42729.17 | 23-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 180219.47 | 21-APR-15:00 | 37611.08 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 177595.27 | 05-APR-07:19 | 113484.87 | 26-APR-14:39 | 43295.97 | 26-APR-14:39 | 0.00 | 01-APR-00:10 |
May | 176259.09 | 09-MAY-07:10 | 24287.76 | 01-MAY-18:30 | 423497.50 | 01-MAY-07:10 | 132038.75 | 09-MAY-07:19 | 100297.36 | 03-MAY-15:20 | 44610.57 | 03-MAY-12:30 | 0.00 | 01-MAY-00:10 |
June | 175437.63 | 09-JUN-07:10 | 24287.76 | 01-JUN-18:49 | 541788.89 | 01-JUN-07:10 | 147223.63 | 09-JUN-07:19 | 109592.35 | 30-JUN-15:00 | 43001.63 | 29-JUN-12:00 | 0.00 | 01-JUN-00:10 |
July | 173861.99 | 12-JUL-07:10 | 24287.76 | 01-JUL-18:00 | 660080.29 | 03-JUL-07:10 | 162408.10 | 12-JUL-07:19 | 121534.74 | 31-JUL-14:00 | 45391.75 | 31-JUL-15:50 | 0.00 | 01-JUL-00:10 |
August | 176414.22 | 21-AUG-07:10 | 37611.08 | 08-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 177594.75 | 21-AUG-07:19 | 125640.42 | 18-AUG-14:00 | 45689.26 | 18-AUG-15:50 | 0.00 | 01-AUG-00:10 |
September | 185528.35 | 18-SEP-07:10 | 37611.08 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 132043.63 | 18-SEP-07:19 | 113045.40 | 28-SEP-15:30 | 54962.91 | 29-SEP-10:50 | 0.00 | 01-SEP-00:10 |
October | 185523.35 | 24-OCT-07:10 | 37611.08 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 147228.93 | 24-OCT-07:19 | 122992.70 | 16-OCT-08:30 | 57440.88 | 16-OCT-14:39 | 0.00 | 01-OCT-00:10 |
November | 198852.03 | 06-NOV-16:00 | 37611.08 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 162409.85 | 24-NOV-08:39 | 92141.21 | 13-NOV-15:09 | 42184.98 | 10-NOV-13:39 | 0.00 | 01-NOV-00:10 |
December | 198852.03 | 01-DEC-16:40 | 37611.08 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 177595.49 | 08-DEC-08:20 | 90646.26 | 05-DEC-15:00 | 43589.81 | 07-DEC-11:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 173861.99 | 24287.76 | 423497.50 | 132038.75 | 87083.87 | 41838.73 | 0.00 | |||||||
Maximum of Months | 198852.03 | 37611.08 | 778371.69 | 177595.49 | 125640.42 | 57440.88 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 166618.40 | 18-JAN-14:30 | 26608.45 | 13-JAN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 80204.27 | 01-FEB-12:39 | 14978.63 | 01-FEB-13:20 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 148950.84 | 23-MAR-14:20 | 40740.66 | 23-MAR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 173148.82 | 26-APR-13:39 | 40740.66 | 26-APR-10:30 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 138209.01 | 03-MAY-12:30 | 40740.66 | 03-MAY-12:30 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 183755.54 | 29-JUN-12:00 | 40740.66 | 21-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 260807.67 | 31-JUL-15:50 | 40740.66 | 12-JUL-12:09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 273658.61 | 18-AUG-15:50 | 40740.66 | 02-AUG-09:30 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 196089.87 | 22-SEP-11:30 | 40740.66 | 05-SEP-12:50 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 239319.48 | 03-OCT-13:30 | 40740.66 | 02-OCT-07:19 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 85396.81 | 28-NOV-12:20 | 26608.45 | 10-NOV-13:09 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 154721.48 | 05-DEC-14:50 | 14938.26 | 05-DEC-14:30 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 80204.27 | 14938.26 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 273658.61 | 40740.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 942625.09 | 18-JAN-14:30 | 171264.20 | 423497.50 | 0.00 | 52601.55 | 59864.97 | 52767.68 | 0.00 | 166618.40 | 16010.79 |
February | 1023927.79 | 03-FEB-16:10 | 172573.18 | 541788.89 | 0.00 | 113178.67 | 84561.15 | 26887.17 | 0.00 | 72005.53 | 12933.21 |
March | 1226544.61 | 23-MAR-13:00 | 171235.93 | 660080.29 | 0.00 | 82972.15 | 79956.56 | 42729.17 | 0.00 | 148829.85 | 40740.66 |
April | 1413915.12 | 26-APR-13:39 | 171235.93 | 778371.69 | 0.00 | 98157.45 | 109788.24 | 42472.33 | 0.00 | 173148.82 | 40740.66 |
May | 958230.35 | 03-MAY-12:30 | 171235.93 | 423497.50 | 0.00 | 52601.54 | 87335.15 | 44610.57 | 0.00 | 138209.01 | 40740.66 |
June | 1175726.09 | 29-JUN-15:00 | 171235.93 | 541788.89 | 0.00 | 113178.03 | 107534.81 | 42682.96 | 0.00 | 158564.81 | 40740.66 |
July | 1425601.73 | 31-JUL-15:50 | 171235.93 | 660080.29 | 0.00 | 128363.33 | 118982.10 | 45391.75 | 0.00 | 260807.67 | 40740.66 |
August | 1575027.12 | 18-AUG-15:50 | 171235.93 | 778371.69 | 0.00 | 143548.64 | 121782.33 | 45689.26 | 0.00 | 273658.61 | 40740.66 |
September | 1066394.68 | 29-SEP-15:00 | 172169.39 | 423497.50 | 0.00 | 97993.10 | 111706.06 | 46270.32 | 0.00 | 174017.65 | 40740.66 |
October | 1206431.36 | 17-OCT-15:00 | 178028.97 | 541788.89 | 0.00 | 113181.26 | 119975.91 | 44165.69 | 0.00 | 168549.98 | 40740.66 |
November | 1183344.80 | 28-NOV-16:40 | 198852.03 | 660080.29 | 37611.08 | 128377.39 | 63338.96 | 26666.80 | 0.00 | 55723.56 | 12694.69 |
December | 1358591.60 | 05-DEC-16:40 | 198852.03 | 778371.69 | 37611.08 | 143562.22 | 76060.65 | 26952.80 | 0.00 | 83724.08 | 13457.05 |
Annual Sum or Average | |||||||||||
Minimum of Months | 942625.09 | 171235.93 | 423497.50 | 0.00 | 52601.54 | 59864.97 | 26666.80 | 0.00 | 55723.56 | 12694.69 | |
Maximum of Months | 1575027.12 | 198852.03 | 778371.69 | 37611.08 | 143562.22 | 121782.33 | 52767.68 | 0.00 | 273658.61 | 40740.66 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 299869.97 | 03-JAN-07:10 | 0.00 | 76423.38 | 31-JAN-12:39 | 0.00 |
February | 0.00 | 0.00 | 114439.16 | 27-FEB-06:10 | 0.00 | 76418.97 | 08-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 297529.35 | 30-MAR-05:10 | 0.00 | 76142.20 | 06-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 127118.10 | 01-APR-06:10 | 0.00 | 75467.17 | 04-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 30845.30 | 13-MAY-05:10 | 0.00 | 74586.68 | 01-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 73505.05 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 72571.36 | 07-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 72569.76 | 31-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 73232.60 | 27-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 13902.31 | 30-OCT-05:10 | 0.00 | 74118.40 | 24-OCT-11:00 | 0.00 |
November | 0.00 | 0.00 | 68879.84 | 27-NOV-06:10 | 0.00 | 75185.24 | 24-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 190048.69 | 13-DEC-06:10 | 0.00 | 76084.12 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 72569.76 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 299869.97 | 0.00 | 76423.38 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 26.91 | 3.50 | 27.01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.67 | 0.00 | 26.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 25.91 | 0.00 | 25.91 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 25.99 | 0.00 | 25.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.12 | 0.00 | 26.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 25.82 | 0.00 | 25.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 25.81 | 0.00 | 25.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 25.89 | 0.00 | 25.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.58 | 0.67 | 26.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 26.66 | 1.00 | 26.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.79 | 1.83 | 26.88 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 26.63 | 0.83 | 26.70 |
Annual Sum or Average | 0.00 | 0.00 | 77.33 | 26.54 | 7.83 | 26.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 25.81 | 0.00 | 25.81 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 26.91 | 3.50 | 27.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.71 | 0.00 | 25.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.67 | 0.00 | 25.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.71 | 0.00 | 25.71 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 25.68 | 0.00 | 25.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.71 | 0.00 | 25.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.41 | 0.17 | 27.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.39 | 0.33 | 27.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.52 | 0.83 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.43 | 0.67 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.50 | 1.83 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.53 | 3.33 | 27.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.50 | 2.33 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.53 | 1.17 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.57 | 1.50 | 27.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.33 | 27.51 | 12.33 | 27.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.57 | 3.33 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.48 | 3.50 | 27.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.49 | 3.17 | 27.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.39 | 1.00 | 27.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.35 | 1.33 | 27.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.13 | 10.00 | 27.13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.69 | 4.67 | 27.69 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.65 | 6.67 | 27.65 |
Annual Sum or Average | 0.00 | 0.00 | 30.33 | 27.43 | 30.33 | 27.43 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.69 | 10.00 | 27.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.56 | 1.00 | 27.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.56 | 2.33 | 27.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.11 | 5.83 | 27.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.54 | 4.00 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.18 | 3.50 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 27.11 | 8.83 | 27.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 26.97 | 7.00 | 27.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.56 | 3.17 | 27.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.34 | 5.67 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.57 | 3.17 | 27.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.24 | 4.17 | 27.44 |
Annual Sum or Average | 0.00 | 0.00 | 106.33 | 27.17 | 48.83 | 27.40 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.97 | 0.17 | 27.18 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 27.57 | 8.83 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.45 | 0.83 | 27.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.51 | 1.33 | 27.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.58 | 3.67 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.53 | 2.67 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.52 | 0.67 | 27.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.63 | 1.17 | 27.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.67 | 27.54 | 10.67 | 27.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.63 | 3.67 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.61 | 2.83 | 27.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.47 | 2.67 | 27.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.30 | 0.67 | 27.30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 26.14 | 15.50 | 26.13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.70 | 4.17 | 27.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.62 | 5.83 | 27.62 |
Annual Sum or Average | 0.00 | 0.00 | 32.00 | 26.88 | 31.83 | 26.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.70 | 15.50 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.59 | 2.50 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.54 | 1.67 | 27.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.59 | 2.00 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.73 | 4.67 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.77 | 2.83 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.60 | 2.17 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.90 | 1.50 | 27.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 22.50 | 27.68 | 17.50 | 27.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.90 | 4.67 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
December | 0.33 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Annual Sum or Average | 2.67 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.39 | 0.83 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.54 | 3.33 | 27.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.45 | 2.00 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.35 | 0.33 | 27.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.58 | 1.17 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Annual Sum or Average | 1.50 | 19.01 | 0.00 | 19.01 | 7.67 | 26.11 | 7.67 | 26.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.26 | 0.00 | 19.26 | 3.33 | 27.58 | 3.33 | 27.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.99 | 0.00 | 18.99 | 0.83 | 24.33 | 0.83 | 25.56 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
March | 0.33 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.28 | 0.50 | 27.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.78 | 7.50 | 26.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.61 | 2.17 | 27.61 |
December | 0.17 | 19.43 | 0.00 | 19.43 | 1.50 | 26.62 | 1.50 | 27.00 |
Annual Sum or Average | 1.00 | 19.14 | 0.00 | 19.14 | 13.17 | 26.51 | 12.83 | 26.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.43 | 0.00 | 19.43 | 7.83 | 27.61 | 7.50 | 27.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.61 | 1.67 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.55 | 1.33 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.66 | 2.00 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.80 | 4.83 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.80 | 3.33 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.61 | 1.83 | 27.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.95 | 1.67 | 27.97 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 19.19 | 0.00 | 19.19 | 22.17 | 27.43 | 16.67 | 27.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.43 | 0.00 | 19.43 | 7.33 | 27.95 | 4.83 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 37.17 | 24.00 | 226.83 | 25.10 | 0.00 | 25.10 |
February | 32.50 | 24.00 | 219.00 | 24.95 | 0.00 | 24.95 |
March | 0.00 | 0.00 | 293.67 | 24.77 | 0.00 | 24.77 |
April | 3.83 | 24.00 | 369.50 | 24.69 | 0.00 | 24.69 |
May | 2.33 | 24.00 | 366.83 | 24.69 | 0.00 | 24.69 |
June | 2.83 | 24.00 | 471.33 | 24.49 | 2.83 | 24.48 |
July | 105.17 | 25.19 | 497.00 | 24.71 | 105.17 | 24.78 |
August | 123.33 | 25.18 | 514.00 | 24.62 | 123.33 | 24.71 |
September | 37.00 | 25.35 | 448.33 | 24.66 | 37.00 | 24.71 |
October | 37.83 | 24.59 | 331.00 | 24.91 | 28.17 | 24.90 |
November | 33.83 | 24.20 | 271.50 | 24.99 | 2.00 | 25.00 |
December | 50.00 | 24.00 | 198.67 | 25.18 | 0.00 | 25.18 |
Annual Sum or Average | 465.83 | 24.75 | 4207.67 | 24.76 | 298.50 | 24.79 |
Minimum of Months | 0.00 | 0.00 | 198.67 | 24.49 | 0.00 | 24.48 |
Maximum of Months | 123.33 | 25.35 | 514.00 | 25.18 | 123.33 | 25.18 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 64.50 | 24.44 | 201.33 | 24.75 | 12.33 | 24.84 |
February | 35.00 | 23.96 | 217.17 | 24.52 | 0.00 | 24.52 |
March | 0.00 | 0.00 | 309.17 | 24.47 | 0.00 | 24.47 |
April | 5.83 | 23.94 | 401.67 | 24.32 | 0.00 | 24.32 |
May | 3.67 | 23.66 | 343.50 | 24.38 | 0.00 | 24.38 |
June | 0.00 | 0.00 | 475.00 | 24.29 | 0.00 | 24.29 |
July | 0.00 | 0.00 | 497.00 | 24.24 | 0.00 | 24.24 |
August | 0.00 | 0.00 | 514.00 | 24.20 | 0.00 | 24.20 |
September | 0.00 | 0.00 | 443.83 | 24.32 | 0.00 | 24.32 |
October | 5.17 | 24.00 | 321.83 | 24.50 | 0.00 | 24.50 |
November | 27.67 | 24.01 | 271.17 | 24.59 | 0.00 | 24.59 |
December | 33.33 | 24.01 | 193.17 | 24.74 | 0.00 | 24.74 |
Annual Sum or Average | 175.17 | 24.15 | 4188.83 | 24.40 | 12.33 | 24.41 |
Minimum of Months | 0.00 | 0.00 | 193.17 | 24.20 | 0.00 | 24.20 |
Maximum of Months | 64.50 | 24.44 | 514.00 | 24.75 | 12.33 | 24.84 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 241.17 | 23.49 | 69.83 | 23.65 | 13.00 | 23.64 |
February | 200.17 | 23.49 | 59.67 | 23.68 | 0.00 | 23.68 |
March | 175.67 | 23.43 | 120.50 | 23.75 | 0.00 | 23.75 |
April | 72.00 | 23.41 | 206.67 | 24.06 | 0.00 | 24.06 |
May | 68.17 | 23.45 | 224.00 | 24.12 | 0.00 | 24.12 |
June | 14.17 | 23.34 | 364.33 | 24.17 | 0.00 | 24.17 |
July | 1.00 | 23.35 | 460.67 | 24.15 | 0.00 | 24.15 |
August | 0.00 | 0.00 | 493.33 | 24.13 | 0.00 | 24.13 |
September | 11.00 | 23.39 | 383.67 | 24.17 | 0.00 | 24.17 |
October | 85.50 | 23.69 | 248.67 | 24.17 | 0.00 | 24.17 |
November | 176.67 | 23.73 | 119.50 | 24.04 | 7.33 | 24.08 |
December | 279.83 | 23.61 | 46.67 | 23.73 | 0.00 | 23.73 |
Annual Sum or Average | 1325.33 | 23.54 | 2797.50 | 24.01 | 20.33 | 24.01 |
Minimum of Months | 0.00 | 0.00 | 46.67 | 23.65 | 0.00 | 23.64 |
Maximum of Months | 279.83 | 23.73 | 493.33 | 24.17 | 13.00 | 24.17 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 422.17 | 22.53 | 30.50 | 22.51 | 12.33 | 22.43 |
February | 369.00 | 22.66 | 18.17 | 22.72 | 0.00 | 22.72 |
March | 387.50 | 22.80 | 53.17 | 22.95 | 0.00 | 22.95 |
April | 205.50 | 23.01 | 145.83 | 23.46 | 0.00 | 23.46 |
May | 188.17 | 23.10 | 166.83 | 23.59 | 0.00 | 23.59 |
June | 62.67 | 23.24 | 308.33 | 23.99 | 0.00 | 23.99 |
July | 5.17 | 23.29 | 439.33 | 24.12 | 0.00 | 24.12 |
August | 6.00 | 23.31 | 461.83 | 24.09 | 0.00 | 24.09 |
September | 74.00 | 23.27 | 298.67 | 23.96 | 0.00 | 23.96 |
October | 206.50 | 23.31 | 173.83 | 23.70 | 0.00 | 23.70 |
November | 351.33 | 22.97 | 44.00 | 23.09 | 7.17 | 23.11 |
December | 447.00 | 22.71 | 11.17 | 22.72 | 2.00 | 22.72 |
Annual Sum or Average | 2725.00 | 22.85 | 2151.67 | 23.40 | 21.50 | 23.39 |
Minimum of Months | 5.17 | 22.53 | 11.17 | 22.51 | 0.00 | 22.43 |
Maximum of Months | 447.00 | 23.31 | 461.83 | 24.12 | 12.33 | 24.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 348.50 | 23.19 | 28.17 | 23.28 | 0.00 | 23.28 |
February | 292.67 | 23.35 | 27.33 | 23.40 | 0.00 | 23.40 |
March | 241.17 | 23.29 | 93.83 | 23.53 | 0.00 | 23.53 |
April | 92.67 | 23.47 | 189.67 | 23.93 | 0.00 | 23.93 |
May | 104.67 | 23.48 | 199.50 | 23.97 | 0.00 | 23.97 |
June | 3.33 | 23.45 | 407.50 | 24.24 | 0.00 | 24.24 |
July | 0.00 | 0.00 | 487.00 | 24.24 | 0.00 | 24.24 |
August | 0.00 | 0.00 | 503.50 | 24.15 | 0.00 | 24.15 |
September | 27.50 | 23.43 | 338.67 | 24.15 | 0.00 | 24.15 |
October | 111.50 | 23.67 | 231.00 | 24.11 | 0.00 | 24.11 |
November | 264.17 | 23.57 | 75.00 | 23.74 | 0.00 | 23.74 |
December | 356.33 | 23.56 | 19.67 | 23.59 | 0.00 | 23.59 |
Annual Sum or Average | 1842.50 | 23.42 | 2600.83 | 23.89 | 0.00 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 19.67 | 23.28 | 0.00 | 23.28 |
Maximum of Months | 356.33 | 23.67 | 503.50 | 24.24 | 0.00 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 266.83 | 23.23 | 70.67 | 23.54 | 0.00 | 23.54 |
February | 251.67 | 23.16 | 70.17 | 23.43 | 0.00 | 23.43 |
March | 224.33 | 23.09 | 148.50 | 23.58 | 1.00 | 23.59 |
April | 107.67 | 23.34 | 270.00 | 24.04 | 3.00 | 24.06 |
May | 91.67 | 23.42 | 266.67 | 24.17 | 1.50 | 24.19 |
June | 36.67 | 24.06 | 393.50 | 24.28 | 8.00 | 24.33 |
July | 22.33 | 26.02 | 465.83 | 24.41 | 17.33 | 24.49 |
August | 17.00 | 25.99 | 477.83 | 24.27 | 13.17 | 24.34 |
September | 39.67 | 23.91 | 379.33 | 24.26 | 7.00 | 24.30 |
October | 77.83 | 23.54 | 269.00 | 24.23 | 2.00 | 24.24 |
November | 224.50 | 23.41 | 105.17 | 23.74 | 0.00 | 23.74 |
December | 306.00 | 23.37 | 28.33 | 23.50 | 0.00 | 23.50 |
Annual Sum or Average | 1666.17 | 23.38 | 2945.00 | 24.00 | 53.00 | 24.03 |
Minimum of Months | 17.00 | 23.09 | 28.33 | 23.43 | 0.00 | 23.43 |
Maximum of Months | 306.00 | 26.02 | 477.83 | 24.41 | 17.33 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 140.83 | 23.46 | 202.50 | 24.12 | 5.50 | 24.16 |
February | 170.17 | 23.28 | 154.33 | 23.89 | 5.17 | 23.94 |
March | 182.67 | 23.23 | 180.50 | 23.78 | 4.83 | 23.82 |
April | 83.83 | 23.37 | 280.50 | 24.12 | 0.17 | 24.12 |
May | 139.33 | 23.32 | 198.33 | 23.86 | 0.00 | 23.86 |
June | 29.83 | 23.39 | 368.67 | 24.14 | 0.00 | 24.14 |
July | 0.33 | 26.81 | 475.17 | 24.26 | 0.33 | 24.26 |
August | 1.17 | 26.78 | 506.50 | 24.25 | 1.17 | 24.25 |
September | 23.50 | 25.20 | 426.17 | 24.44 | 12.50 | 24.50 |
October | 64.33 | 25.18 | 362.00 | 24.71 | 31.17 | 24.86 |
November | 89.00 | 23.97 | 270.50 | 24.44 | 9.17 | 24.51 |
December | 112.50 | 23.83 | 225.50 | 24.41 | 9.67 | 24.49 |
Annual Sum or Average | 1037.50 | 23.60 | 3650.67 | 24.22 | 79.67 | 24.26 |
Minimum of Months | 0.33 | 23.23 | 154.33 | 23.78 | 0.00 | 23.82 |
Maximum of Months | 182.67 | 26.81 | 506.50 | 24.71 | 31.17 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 146.83 | 23.40 | 170.17 | 24.03 | 0.00 | 24.03 |
February | 54.00 | 23.85 | 254.00 | 24.45 | 3.50 | 24.48 |
March | 23.83 | 24.87 | 378.67 | 24.55 | 9.33 | 24.60 |
April | 33.00 | 26.78 | 474.33 | 24.79 | 30.67 | 24.91 |
May | 30.50 | 25.46 | 405.33 | 24.59 | 18.00 | 24.68 |
June | 24.83 | 26.94 | 493.67 | 24.65 | 24.83 | 24.76 |
July | 58.00 | 26.96 | 497.00 | 24.91 | 58.00 | 25.10 |
August | 53.50 | 26.93 | 514.00 | 24.78 | 53.50 | 24.96 |
September | 17.83 | 26.88 | 470.17 | 24.58 | 17.83 | 24.67 |
October | 28.00 | 26.46 | 395.50 | 24.83 | 23.67 | 24.95 |
November | 24.83 | 25.37 | 327.67 | 24.81 | 11.50 | 24.87 |
December | 23.17 | 25.40 | 295.67 | 24.98 | 11.00 | 25.04 |
Annual Sum or Average | 518.33 | 25.25 | 4676.17 | 24.68 | 261.83 | 24.79 |
Minimum of Months | 17.83 | 23.40 | 170.17 | 24.03 | 0.00 | 24.03 |
Maximum of Months | 146.83 | 26.96 | 514.00 | 24.98 | 58.00 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 473.67 | 22.13 | 21.83 | 22.08 | 18.83 | 22.03 |
February | 439.00 | 22.30 | 3.33 | 22.30 | 2.67 | 22.29 |
March | 468.50 | 22.37 | 15.67 | 22.41 | 1.50 | 22.40 |
April | 331.67 | 22.88 | 54.17 | 23.03 | 0.00 | 23.03 |
May | 273.83 | 23.10 | 77.50 | 23.31 | 0.00 | 23.31 |
June | 90.67 | 23.31 | 262.00 | 23.89 | 0.00 | 23.89 |
July | 22.17 | 23.27 | 404.83 | 24.09 | 0.00 | 24.09 |
August | 46.83 | 23.19 | 374.33 | 23.96 | 0.00 | 23.96 |
September | 165.00 | 23.17 | 200.33 | 23.65 | 0.00 | 23.65 |
October | 268.17 | 23.12 | 120.00 | 23.45 | 0.00 | 23.45 |
November | 451.00 | 22.60 | 8.50 | 22.61 | 3.33 | 22.60 |
December | 491.33 | 22.23 | 10.50 | 22.20 | 10.50 | 22.17 |
Annual Sum or Average | 3521.83 | 22.58 | 1553.00 | 23.02 | 36.83 | 23.00 |
Minimum of Months | 22.17 | 22.13 | 3.33 | 22.08 | 0.00 | 22.03 |
Maximum of Months | 491.33 | 23.31 | 404.83 | 24.09 | 18.83 | 24.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 370.83 | 22.59 | 23.33 | 22.64 | 5.33 | 22.61 |
February | 317.67 | 22.45 | 17.50 | 22.56 | 0.33 | 22.56 |
March | 312.67 | 22.47 | 51.67 | 22.74 | 1.33 | 22.73 |
April | 168.33 | 22.95 | 161.00 | 23.71 | 2.33 | 23.73 |
May | 173.00 | 23.10 | 160.67 | 23.80 | 0.83 | 23.81 |
June | 84.00 | 23.56 | 258.17 | 24.16 | 9.00 | 24.23 |
July | 40.67 | 25.47 | 370.67 | 24.57 | 25.50 | 24.70 |
August | 37.50 | 25.21 | 371.33 | 24.41 | 21.00 | 24.53 |
September | 99.33 | 23.26 | 240.17 | 24.01 | 4.67 | 24.05 |
October | 149.83 | 23.18 | 157.00 | 23.88 | 1.17 | 23.89 |
November | 308.67 | 22.85 | 26.17 | 22.97 | 0.50 | 22.97 |
December | 393.83 | 22.72 | 2.33 | 22.72 | 0.50 | 22.72 |
Annual Sum or Average | 2456.33 | 22.86 | 1840.00 | 23.52 | 72.50 | 23.56 |
Minimum of Months | 37.50 | 22.45 | 2.33 | 22.56 | 0.33 | 22.56 |
Maximum of Months | 393.83 | 25.47 | 371.33 | 24.57 | 25.50 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 197.50 | 23.13 | 177.67 | 23.80 | 7.83 | 23.85 |
February | 227.00 | 22.78 | 117.50 | 23.40 | 4.67 | 23.45 |
March | 287.67 | 22.74 | 125.67 | 23.21 | 2.33 | 23.23 |
April | 174.17 | 23.00 | 197.00 | 23.71 | 0.00 | 23.71 |
May | 239.83 | 23.08 | 136.83 | 23.48 | 0.00 | 23.48 |
June | 116.00 | 23.27 | 257.50 | 23.84 | 0.00 | 23.84 |
July | 26.17 | 23.37 | 401.83 | 24.14 | 0.50 | 24.14 |
August | 16.33 | 23.80 | 450.67 | 24.18 | 2.33 | 24.20 |
September | 48.67 | 24.08 | 382.33 | 24.33 | 10.83 | 24.40 |
October | 104.83 | 24.41 | 314.17 | 24.58 | 31.00 | 24.74 |
November | 164.33 | 23.51 | 207.50 | 24.14 | 9.00 | 24.21 |
December | 198.17 | 23.36 | 177.50 | 24.03 | 8.17 | 24.10 |
Annual Sum or Average | 1800.67 | 23.18 | 2946.17 | 23.92 | 76.67 | 23.97 |
Minimum of Months | 16.33 | 22.74 | 117.50 | 23.21 | 0.00 | 23.23 |
Maximum of Months | 287.67 | 24.41 | 450.67 | 24.58 | 31.00 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 395.33 | 22.54 | 41.17 | 22.68 | 2.00 | 22.67 |
February | 342.50 | 22.63 | 53.50 | 22.86 | 0.00 | 22.86 |
March | 357.33 | 22.70 | 91.50 | 23.01 | 1.00 | 23.02 |
April | 143.67 | 23.26 | 235.00 | 23.99 | 11.00 | 24.07 |
May | 152.50 | 23.32 | 246.00 | 24.01 | 8.50 | 24.07 |
June | 46.67 | 24.18 | 391.83 | 24.30 | 12.83 | 24.38 |
July | 28.50 | 26.83 | 482.83 | 24.56 | 28.50 | 24.68 |
August | 21.00 | 26.45 | 496.17 | 24.39 | 18.67 | 24.47 |
September | 46.50 | 24.07 | 372.67 | 24.32 | 11.00 | 24.39 |
October | 154.50 | 23.52 | 249.17 | 24.09 | 10.67 | 24.16 |
November | 315.17 | 22.95 | 87.00 | 23.25 | 0.17 | 23.25 |
December | 391.67 | 22.76 | 26.50 | 22.86 | 0.00 | 22.86 |
Annual Sum or Average | 2395.33 | 22.97 | 2773.33 | 23.72 | 104.33 | 23.78 |
Minimum of Months | 21.00 | 22.54 | 26.50 | 22.68 | 0.00 | 22.67 |
Maximum of Months | 395.33 | 26.83 | 496.17 | 24.56 | 28.50 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 495.17 | 21.36 | 128.17 | 21.10 | 128.17 | 20.94 |
February | 448.83 | 21.51 | 71.83 | 21.33 | 71.83 | 21.19 |
March | 491.67 | 21.68 | 64.67 | 21.59 | 54.00 | 21.47 |
April | 368.33 | 22.37 | 60.00 | 22.53 | 8.67 | 22.49 |
May | 332.67 | 22.62 | 69.33 | 22.84 | 2.17 | 22.82 |
June | 164.67 | 23.07 | 225.17 | 23.64 | 0.00 | 23.64 |
July | 58.67 | 23.12 | 363.33 | 23.99 | 0.50 | 23.99 |
August | 111.00 | 23.10 | 333.17 | 23.81 | 0.00 | 23.81 |
September | 241.00 | 22.87 | 157.83 | 23.33 | 0.00 | 23.33 |
October | 317.00 | 22.61 | 104.33 | 22.98 | 3.00 | 22.96 |
November | 481.50 | 21.86 | 57.17 | 21.72 | 54.83 | 21.60 |
December | 497.00 | 21.37 | 128.83 | 21.14 | 128.83 | 20.99 |
Annual Sum or Average | 4007.50 | 22.01 | 1763.83 | 22.34 | 452.00 | 22.19 |
Minimum of Months | 58.67 | 21.36 | 57.17 | 21.10 | 0.00 | 20.94 |
Maximum of Months | 497.00 | 23.12 | 363.33 | 23.99 | 128.83 | 23.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 458.00 | 21.93 | 66.17 | 21.79 | 55.33 | 21.63 |
February | 397.00 | 21.93 | 41.50 | 21.83 | 32.67 | 21.71 |
March | 405.83 | 22.02 | 77.67 | 22.18 | 23.67 | 22.08 |
April | 205.33 | 22.50 | 199.67 | 23.35 | 2.67 | 23.34 |
May | 227.17 | 22.73 | 186.00 | 23.45 | 0.33 | 23.45 |
June | 118.83 | 23.17 | 304.83 | 23.96 | 6.33 | 24.00 |
July | 55.83 | 24.92 | 430.50 | 24.47 | 28.17 | 24.59 |
August | 57.00 | 24.43 | 434.83 | 24.29 | 21.67 | 24.40 |
September | 144.00 | 22.91 | 274.67 | 23.77 | 3.17 | 23.79 |
October | 215.33 | 22.87 | 168.17 | 23.52 | 0.83 | 23.53 |
November | 437.50 | 22.44 | 25.83 | 22.43 | 13.17 | 22.38 |
December | 480.50 | 22.03 | 41.17 | 21.91 | 38.00 | 21.80 |
Annual Sum or Average | 3202.33 | 22.37 | 2251.00 | 23.04 | 226.00 | 23.00 |
Minimum of Months | 55.83 | 21.93 | 25.83 | 21.79 | 0.33 | 21.63 |
Maximum of Months | 480.50 | 24.92 | 434.83 | 24.47 | 55.33 | 24.59 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 266.50 | 22.41 | 150.33 | 22.85 | 30.67 | 22.69 |
February | 288.50 | 22.08 | 115.67 | 22.56 | 21.83 | 22.44 |
March | 349.50 | 22.09 | 124.83 | 22.46 | 27.50 | 22.35 |
April | 230.67 | 22.55 | 181.33 | 23.27 | 5.33 | 23.24 |
May | 298.17 | 22.62 | 122.67 | 23.03 | 2.67 | 23.01 |
June | 173.00 | 22.99 | 224.50 | 23.61 | 0.00 | 23.61 |
July | 66.17 | 23.18 | 366.33 | 24.04 | 1.50 | 24.05 |
August | 53.33 | 23.29 | 411.83 | 24.09 | 2.83 | 24.11 |
September | 104.67 | 23.38 | 337.50 | 24.11 | 10.67 | 24.18 |
October | 152.67 | 23.58 | 280.33 | 24.23 | 23.83 | 24.38 |
November | 234.33 | 22.81 | 166.50 | 23.46 | 12.00 | 23.45 |
December | 262.33 | 22.60 | 138.83 | 23.12 | 20.83 | 23.00 |
Annual Sum or Average | 2479.83 | 22.62 | 2620.67 | 23.41 | 159.67 | 23.37 |
Minimum of Months | 53.33 | 22.08 | 115.67 | 22.46 | 0.00 | 22.35 |
Maximum of Months | 349.50 | 23.58 | 411.83 | 24.23 | 30.67 | 24.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 440.83 | 21.89 | 79.17 | 21.82 | 55.83 | 21.66 |
February | 379.67 | 21.93 | 57.33 | 22.04 | 21.33 | 21.96 |
March | 403.33 | 22.03 | 88.00 | 22.27 | 20.83 | 22.21 |
April | 219.17 | 22.76 | 193.00 | 23.52 | 11.33 | 23.58 |
May | 230.33 | 22.85 | 197.83 | 23.56 | 8.17 | 23.63 |
June | 100.17 | 23.49 | 342.67 | 24.11 | 13.33 | 24.19 |
July | 42.50 | 25.68 | 452.33 | 24.52 | 29.17 | 24.65 |
August | 37.17 | 25.03 | 458.33 | 24.33 | 19.50 | 24.43 |
September | 110.50 | 23.29 | 311.67 | 24.05 | 10.33 | 24.12 |
October | 211.83 | 22.95 | 206.17 | 23.67 | 8.17 | 23.73 |
November | 380.33 | 22.31 | 74.33 | 22.46 | 19.67 | 22.39 |
December | 441.83 | 22.08 | 51.67 | 21.97 | 44.00 | 21.85 |
Annual Sum or Average | 2997.67 | 22.41 | 2512.50 | 23.17 | 261.67 | 23.16 |
Minimum of Months | 37.17 | 21.89 | 51.67 | 21.82 | 8.17 | 21.66 |
Maximum of Months | 441.83 | 25.68 | 458.33 | 24.52 | 55.83 | 24.65 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 4.83 | 27.00 | 454.00 | 27.00 | 4.83 | 27.00 |
March | 20.67 | 27.00 | 514.00 | 27.00 | 20.67 | 27.00 |
April | 134.67 | 27.00 | 485.00 | 27.00 | 134.67 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 1.50 | 27.00 | 496.00 | 27.00 | 1.50 | 27.00 |
July | 105.83 | 27.00 | 497.00 | 27.00 | 105.83 | 27.00 |
August | 256.17 | 27.00 | 514.00 | 27.00 | 256.17 | 27.00 |
September | 1.00 | 27.00 | 485.00 | 27.00 | 1.00 | 27.00 |
October | 16.33 | 27.00 | 502.00 | 27.00 | 16.33 | 27.00 |
November | 34.17 | 27.00 | 489.00 | 27.00 | 34.17 | 27.00 |
December | 52.33 | 27.00 | 497.00 | 27.00 | 52.33 | 27.00 |
Annual Sum or Average | 627.50 | 27.00 | 5943.00 | 27.00 | 627.50 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 256.17 | 27.00 | 514.00 | 27.00 | 256.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 0.00 | 0.00 | 496.00 | 27.00 | 0.00 | 27.00 |
July | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
August | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 0.00 | 5943.00 | 27.00 | 0.00 | 27.00 | |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.83 | 25.34 | 479.17 | 26.97 | 0.00 | 26.97 |
February | 0.00 | 0.00 | 447.50 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 1.33 | 27.00 | 485.00 | 27.00 | 1.33 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 0.00 | 0.00 | 496.00 | 27.00 | 0.00 | 27.00 |
July | 2.67 | 27.00 | 497.00 | 27.00 | 2.67 | 27.00 |
August | 12.67 | 27.00 | 514.00 | 27.00 | 12.67 | 27.00 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 0.50 | 27.00 | 502.00 | 27.00 | 0.50 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 24.00 | 26.53 | 5913.67 | 27.00 | 17.17 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 447.50 | 26.97 | 0.00 | 26.97 |
Maximum of Months | 12.67 | 27.00 | 514.00 | 27.00 | 12.67 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5943.00 | 27.00 | 5943.00 | 27.00 | 5943.00 | 27.00 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00028 | 32.59557 | 0.87904 | 21.37444 |
February | 454.00000 | 27.00034 | 33.22470 | 0.92099 | 22.96938 |
March | 514.00000 | 27.00030 | 34.60038 | 0.96811 | 24.82377 |
April | 485.00000 | 27.00015 | 35.11410 | 1.01977 | 26.98549 |
May | 508.00000 | 27.00063 | 36.42099 | 0.25076 | 6.35138 |
June | 496.00000 | 27.00086 | 36.60646 | 0.31647 | 7.11675 |
July | 497.00000 | 27.00074 | 36.77245 | 0.37282 | 7.92825 |
August | 514.00000 | 27.00026 | 36.61664 | 0.41241 | 8.58017 |
September | 485.00000 | 27.00099 | 37.61804 | 0.27691 | 6.64017 |
October | 502.00000 | 27.00055 | 34.29131 | 0.95539 | 24.31790 |
November | 489.00000 | 27.00023 | 32.25875 | 0.96054 | 24.54907 |
December | 497.00000 | 27.00107 | 30.12231 | 0.96940 | 24.91017 |
Annual Sum or Average | 5943.00000 | 27.00053 | 34.69994 | 0.68966 | 17.15048 |
Minimum of Months | 454.00000 | 27.00015 | 30.12231 | 0.25076 | 6.35138 |
Maximum of Months | 514.00000 | 27.00107 | 37.61804 | 1.01977 | 26.98549 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00026 | 32.67060 | 0.79811 | 18.53779 |
February | 454.00000 | 27.00032 | 33.25685 | 0.82412 | 19.41111 |
March | 514.00000 | 27.00028 | 34.59328 | 0.85486 | 20.48252 |
April | 485.00000 | 27.00015 | 35.09789 | 0.90878 | 22.49871 |
May | 508.00000 | 27.00059 | 36.52448 | 0.17471 | 5.71056 |
June | 496.00000 | 27.00084 | 36.65159 | 0.22406 | 6.09708 |
July | 497.00000 | 27.00070 | 36.79572 | 0.26492 | 6.50333 |
August | 514.00000 | 27.00025 | 36.62473 | 0.28481 | 6.73634 |
September | 485.00000 | 27.00076 | 37.78504 | 0.20786 | 5.96353 |
October | 502.00000 | 27.00052 | 34.31814 | 0.88332 | 21.52556 |
November | 489.00000 | 27.00022 | 32.24759 | 0.84968 | 20.32390 |
December | 497.00000 | 27.00005 | 30.09953 | 0.82934 | 19.58838 |
Annual Sum or Average | 5943.00000 | 27.00041 | 34.73513 | 0.58974 | 14.39512 |
Minimum of Months | 454.00000 | 27.00005 | 30.09953 | 0.17471 | 5.71056 |
Maximum of Months | 514.00000 | 27.00084 | 37.78504 | 0.90878 | 22.49871 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.95383 | 33.25546 | 0.72944 | 16.48800 |
February | 454.00000 | 27.00032 | 33.32402 | 0.76578 | 17.52663 |
March | 514.00000 | 27.00029 | 34.62939 | 0.80357 | 18.76209 |
April | 485.00000 | 27.00017 | 35.11930 | 0.88370 | 21.62435 |
May | 508.00000 | 27.00059 | 36.58818 | 0.14331 | 5.63502 |
June | 496.00000 | 27.00086 | 36.66635 | 0.21389 | 6.09202 |
July | 497.00000 | 27.00074 | 36.80429 | 0.26890 | 6.61027 |
August | 514.00000 | 27.00029 | 36.63810 | 0.28507 | 6.80705 |
September | 485.00000 | 27.00079 | 37.83677 | 0.18895 | 5.89277 |
October | 502.00000 | 27.00053 | 34.34065 | 0.85864 | 20.67109 |
November | 489.00000 | 27.00023 | 32.27648 | 0.79590 | 18.51463 |
December | 497.00000 | 27.00005 | 30.11697 | 0.76268 | 17.40046 |
Annual Sum or Average | 5943.00000 | 26.99650 | 34.81304 | 0.55619 | 13.45625 |
Minimum of Months | 454.00000 | 26.95383 | 30.11697 | 0.14331 | 5.63502 |
Maximum of Months | 514.00000 | 27.00086 | 37.83677 | 0.88370 | 21.62435 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 40.34529 | 1.13960 | 32.35419 |
February | 454.00000 | 27.00000 | 39.97082 | 1.27896 | 39.19411 |
March | 514.00000 | 27.00000 | 39.92398 | 1.42207 | 46.69258 |
April | 485.00000 | 27.00000 | 39.96602 | 1.55948 | 54.13806 |
May | 508.00000 | 27.00000 | 40.18327 | 0.52489 | 10.80278 |
June | 496.00000 | 27.00000 | 39.98518 | 0.74562 | 16.71517 |
July | 497.00000 | 27.00000 | 39.90962 | 0.95889 | 24.42831 |
August | 514.00000 | 27.00000 | 39.86316 | 1.15017 | 32.85329 |
September | 485.00000 | 27.00000 | 40.01764 | 0.55715 | 11.52986 |
October | 502.00000 | 27.00000 | 39.94597 | 1.30707 | 40.63468 |
November | 489.00000 | 27.00000 | 40.03281 | 1.44624 | 47.99115 |
December | 497.00000 | 27.00000 | 40.04935 | 1.57285 | 54.86633 |
Annual Sum or Average | 5943.00000 | 27.00000 | 40.01633 | 1.13739 | 34.29677 |
Minimum of Months | 454.00000 | 27.00000 | 39.86316 | 0.52489 | 10.80278 |
Maximum of Months | 514.00000 | 27.00000 | 40.34529 | 1.57285 | 54.86633 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.59485 | 35.26556 | 0.46815 | 10.26596 |
February | 454.00000 | 24.53771 | 38.09983 | 0.46948 | 10.21688 |
March | 514.00000 | 24.45078 | 40.73797 | 0.47206 | 10.06749 |
April | 485.00000 | 24.53685 | 44.36199 | 0.51779 | 11.03897 |
May | 508.00000 | 24.50076 | 43.86915 | -0.3595 | 8.48781 |
June | 496.00000 | 24.46540 | 50.54662 | -0.3164 | 7.78450 |
July | 497.00000 | 24.60377 | 57.09328 | -0.2211 | 7.06515 |
August | 514.00000 | 24.48928 | 58.45696 | -0.2393 | 7.05822 |
September | 485.00000 | 24.56228 | 52.31290 | -0.2672 | 7.56749 |
October | 502.00000 | 24.63044 | 41.89329 | 0.53152 | 11.70207 |
November | 489.00000 | 24.62914 | 36.09232 | 0.49022 | 10.83563 |
December | 497.00000 | 24.62411 | 31.22963 | 0.45257 | 10.12785 |
Annual Sum or Average | 5943.00000 | 24.55168 | 44.22124 | 0.16345 | 9.34034 |
Minimum of Months | 454.00000 | 24.45078 | 31.22963 | -0.3595 | 7.05822 |
Maximum of Months | 514.00000 | 24.63044 | 58.45696 | 0.53152 | 11.70207 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.34340 | 38.48529 | 0.43810 | 9.79845 |
February | 454.00000 | 24.29627 | 39.35079 | 0.43707 | 9.30561 |
March | 514.00000 | 24.28786 | 42.24103 | 0.46301 | 9.75718 |
April | 485.00000 | 24.27566 | 45.49627 | 0.49539 | 10.32831 |
May | 508.00000 | 24.25184 | 45.50400 | -0.4034 | 8.78434 |
June | 496.00000 | 24.27406 | 51.44295 | -0.3380 | 7.78283 |
July | 497.00000 | 24.24007 | 55.13453 | -0.3095 | 7.19653 |
August | 514.00000 | 24.19930 | 55.92312 | -0.3069 | 7.12886 |
September | 485.00000 | 24.28909 | 52.70890 | -0.3290 | 7.72710 |
October | 502.00000 | 24.33690 | 42.78652 | 0.48932 | 10.43101 |
November | 489.00000 | 24.38641 | 37.28534 | 0.45881 | 9.90793 |
December | 497.00000 | 24.37424 | 32.03451 | 0.42115 | 9.15354 |
Annual Sum or Average | 5943.00000 | 24.29589 | 44.91618 | 0.12320 | 8.93655 |
Minimum of Months | 454.00000 | 24.19930 | 32.03451 | -0.4034 | 7.12886 |
Maximum of Months | 514.00000 | 24.38641 | 55.92312 | 0.49539 | 10.43101 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.83797 | 40.48099 | 0.29521 | 7.20820 |
February | 454.00000 | 23.84431 | 41.61228 | 0.30738 | 7.22567 |
March | 514.00000 | 23.87640 | 44.48001 | 0.33689 | 7.61578 |
April | 485.00000 | 23.98249 | 47.24786 | 0.39410 | 8.50426 |
May | 508.00000 | 24.03052 | 46.63418 | -0.5050 | 10.66766 |
June | 496.00000 | 24.08366 | 52.56044 | -0.4326 | 9.17352 |
July | 497.00000 | 24.11416 | 56.38645 | -0.3892 | 8.38520 |
August | 514.00000 | 24.10413 | 57.24085 | -0.3813 | 8.22117 |
September | 485.00000 | 24.10657 | 53.74124 | -0.4166 | 8.93506 |
October | 502.00000 | 24.10736 | 44.09429 | 0.41332 | 8.89556 |
November | 489.00000 | 24.01221 | 39.55139 | 0.34297 | 7.92894 |
December | 497.00000 | 23.85743 | 34.53993 | 0.26713 | 6.82377 |
Annual Sum or Average | 5943.00000 | 23.99729 | 46.59333 | 0.01639 | 8.30694 |
Minimum of Months | 454.00000 | 23.83797 | 34.53993 | -0.5050 | 6.82377 |
Maximum of Months | 514.00000 | 24.11416 | 57.24085 | 0.41332 | 10.66766 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.76232 | 43.30761 | 0.02192 | 6.44881 |
February | 454.00000 | 22.90343 | 44.65928 | 0.07162 | 6.17979 |
March | 514.00000 | 23.08472 | 46.94944 | 0.13636 | 6.38207 |
April | 485.00000 | 23.59998 | 48.58530 | 0.30046 | 7.62021 |
May | 508.00000 | 23.70653 | 47.85866 | -0.6192 | 14.02604 |
June | 496.00000 | 23.94698 | 53.13325 | -0.4751 | 10.12013 |
July | 497.00000 | 24.06875 | 56.55605 | -0.3936 | 8.45876 |
August | 514.00000 | 24.03951 | 57.51619 | -0.3949 | 8.45312 |
September | 485.00000 | 23.90679 | 54.75029 | -0.4856 | 10.38227 |
October | 502.00000 | 23.77199 | 45.51299 | 0.32888 | 7.87736 |
November | 489.00000 | 23.25676 | 42.08156 | 0.14900 | 6.48923 |
December | 497.00000 | 22.83102 | 37.78911 | 0.00949 | 6.02821 |
Annual Sum or Average | 5943.00000 | 23.49375 | 48.26015 | -0.1148 | 8.22344 |
Minimum of Months | 454.00000 | 22.76232 | 37.78911 | -0.6192 | 6.02821 |
Maximum of Months | 514.00000 | 24.06875 | 57.51619 | 0.32888 | 14.02604 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.48984 | 37.82134 | 0.18609 | 6.36633 |
February | 454.00000 | 23.58368 | 40.22251 | 0.23180 | 6.51540 |
March | 514.00000 | 23.69546 | 43.05711 | 0.28417 | 7.16664 |
April | 485.00000 | 23.96007 | 45.77036 | 0.38851 | 8.36706 |
May | 508.00000 | 23.98342 | 45.34326 | -0.5215 | 11.10799 |
June | 496.00000 | 24.17766 | 50.87160 | -0.3874 | 8.42165 |
July | 497.00000 | 24.23158 | 54.53504 | -0.3240 | 7.43841 |
August | 514.00000 | 24.14164 | 55.58555 | -0.3495 | 7.72515 |
September | 485.00000 | 24.07335 | 52.67012 | -0.4329 | 9.27122 |
October | 502.00000 | 24.08319 | 42.78682 | 0.40144 | 8.79668 |
November | 489.00000 | 23.81929 | 37.94501 | 0.28218 | 7.10454 |
December | 497.00000 | 23.70324 | 32.64111 | 0.21458 | 6.28638 |
Annual Sum or Average | 5943.00000 | 23.91386 | 44.98075 | -0.0048 | 7.89064 |
Minimum of Months | 454.00000 | 23.48984 | 32.64111 | -0.5215 | 6.28638 |
Maximum of Months | 514.00000 | 24.23158 | 55.58555 | 0.40144 | 11.10799 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.71261 | 36.79244 | 0.25905 | 7.11535 |
February | 454.00000 | 23.60386 | 39.82864 | 0.25804 | 7.06103 |
March | 514.00000 | 23.68244 | 42.73795 | 0.30576 | 7.80164 |
April | 485.00000 | 23.99063 | 45.39322 | 0.43261 | 9.54261 |
May | 508.00000 | 24.09667 | 44.72392 | -0.4403 | 10.27382 |
June | 496.00000 | 24.16964 | 50.68040 | -0.3501 | 8.54612 |
July | 497.00000 | 24.28860 | 54.06331 | -0.2528 | 7.41492 |
August | 514.00000 | 24.16629 | 55.15332 | -0.2836 | 7.57660 |
September | 485.00000 | 24.13772 | 52.11711 | -0.3647 | 8.73306 |
October | 502.00000 | 24.13621 | 42.41091 | 0.43956 | 9.65782 |
November | 489.00000 | 23.82709 | 37.63700 | 0.30427 | 7.50798 |
December | 497.00000 | 23.67747 | 32.37499 | 0.22834 | 6.60944 |
Annual Sum or Average | 5943.00000 | 23.95972 | 44.53516 | 0.04231 | 8.15976 |
Minimum of Months | 454.00000 | 23.60386 | 32.37499 | -0.4403 | 6.60944 |
Maximum of Months | 514.00000 | 24.28860 | 55.15332 | 0.43956 | 10.27382 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.07042 | 35.68801 | 0.38884 | 9.18677 |
February | 454.00000 | 23.89617 | 38.98749 | 0.35163 | 8.67154 |
March | 514.00000 | 23.82487 | 42.20766 | 0.34617 | 8.52270 |
April | 485.00000 | 24.08961 | 45.11426 | 0.44621 | 9.74006 |
May | 508.00000 | 23.90098 | 45.50938 | -0.5435 | 11.97239 |
June | 496.00000 | 24.09206 | 51.15712 | -0.4210 | 9.05470 |
July | 497.00000 | 24.23413 | 54.48551 | -0.3191 | 7.52781 |
August | 514.00000 | 24.23402 | 55.03100 | -0.2813 | 7.16230 |
September | 485.00000 | 24.31718 | 51.47734 | -0.2858 | 7.76314 |
October | 502.00000 | 24.43233 | 41.51611 | 0.54406 | 12.23373 |
November | 489.00000 | 24.27835 | 36.24178 | 0.45799 | 10.28696 |
December | 497.00000 | 24.25053 | 30.82566 | 0.42057 | 9.71707 |
Annual Sum or Average | 5943.00000 | 24.13548 | 44.06848 | 0.08894 | 9.32446 |
Minimum of Months | 454.00000 | 23.82487 | 30.82566 | -0.5435 | 7.16230 |
Maximum of Months | 514.00000 | 24.43233 | 55.03100 | 0.54406 | 12.23373 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.04208 | 35.73371 | 0.36331 | 8.38871 |
February | 454.00000 | 24.28389 | 37.66494 | 0.46057 | 10.00151 |
March | 514.00000 | 24.38575 | 40.29791 | 0.53217 | 11.57378 |
April | 485.00000 | 24.63264 | 43.29135 | 0.67267 | 15.42571 |
May | 508.00000 | 24.39013 | 43.62252 | -0.2840 | 8.03006 |
June | 496.00000 | 24.53259 | 49.25941 | -0.1313 | 6.74147 |
July | 497.00000 | 24.67147 | 52.59810 | -0.0078 | 6.74940 |
August | 514.00000 | 24.55611 | 53.54335 | -0.0111 | 6.49737 |
September | 485.00000 | 24.48000 | 50.75445 | -0.1817 | 6.94086 |
October | 502.00000 | 24.56741 | 40.91449 | 0.59677 | 13.45073 |
November | 489.00000 | 24.53738 | 35.35973 | 0.53624 | 11.86477 |
December | 497.00000 | 24.56950 | 29.92656 | 0.51199 | 11.30787 |
Annual Sum or Average | 5943.00000 | 24.47122 | 42.79362 | 0.25247 | 9.73243 |
Minimum of Months | 454.00000 | 24.04208 | 29.92656 | -0.2840 | 6.49737 |
Maximum of Months | 514.00000 | 24.67147 | 53.54335 | 0.67267 | 15.42571 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.22756 | 40.42361 | -0.1217 | 6.70824 |
February | 454.00000 | 22.35750 | 43.44640 | -0.0656 | 5.99027 |
March | 514.00000 | 22.50121 | 46.55957 | -0.0096 | 6.09720 |
April | 485.00000 | 23.21620 | 48.48670 | 0.19106 | 6.53113 |
May | 508.00000 | 23.50956 | 47.04775 | -0.7016 | 16.26613 |
June | 496.00000 | 23.88073 | 52.27570 | -0.5152 | 10.93609 |
July | 497.00000 | 24.03128 | 56.09838 | -0.4243 | 9.01832 |
August | 514.00000 | 23.90056 | 57.68899 | -0.4648 | 9.81082 |
September | 485.00000 | 23.69372 | 54.43232 | -0.5812 | 12.66346 |
October | 502.00000 | 23.55897 | 44.59992 | 0.26075 | 7.24323 |
November | 489.00000 | 22.70771 | 40.99106 | 0.00681 | 6.05585 |
December | 497.00000 | 22.24832 | 35.63492 | -0.1416 | 6.32591 |
Annual Sum or Average | 5943.00000 | 23.15829 | 47.34495 | -0.2159 | 8.66300 |
Minimum of Months | 454.00000 | 22.22756 | 35.63492 | -0.7016 | 5.99027 |
Maximum of Months | 514.00000 | 24.03128 | 57.68899 | 0.26075 | 16.26613 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.78527 | 38.66499 | 0.02532 | 6.28320 |
February | 385.00000 | 22.75109 | 41.86970 | 0.04377 | 6.23390 |
March | 433.00000 | 22.93520 | 44.25471 | 0.11055 | 6.86468 |
April | 410.00000 | 23.73142 | 46.12191 | 0.34576 | 8.68526 |
May | 430.00000 | 23.81745 | 45.40678 | -0.5591 | 13.45183 |
June | 418.00000 | 24.02307 | 51.15776 | -0.4250 | 10.31642 |
July | 422.00000 | 24.34882 | 54.41907 | -0.2606 | 8.10462 |
August | 433.00000 | 24.20330 | 55.89761 | -0.2972 | 8.27023 |
September | 410.00000 | 23.91693 | 52.95136 | -0.4637 | 10.90635 |
October | 427.00000 | 23.86914 | 43.56490 | 0.35993 | 8.62504 |
November | 417.00000 | 23.17915 | 39.33268 | 0.13404 | 6.32213 |
December | 422.00000 | 22.80757 | 33.92593 | 0.00430 | 5.87753 |
Annual Sum or Average | 5034.00000 | 23.53521 | 45.65160 | -0.0831 | 8.34032 |
Minimum of Months | 385.00000 | 22.75109 | 33.92593 | -0.5591 | 5.87753 |
Maximum of Months | 433.00000 | 24.34882 | 55.89761 | 0.35993 | 13.45183 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.83196 | 36.10072 | 0.32836 | 8.87432 |
February | 454.00000 | 23.52184 | 40.08739 | 0.25792 | 8.18976 |
March | 514.00000 | 23.35889 | 43.70672 | 0.22639 | 7.80246 |
April | 485.00000 | 23.76778 | 46.34576 | 0.35144 | 8.58721 |
May | 508.00000 | 23.60077 | 46.54713 | -0.6586 | 15.33251 |
June | 496.00000 | 23.84440 | 52.32633 | -0.5243 | 11.29090 |
July | 497.00000 | 24.07462 | 55.81758 | -0.3991 | 8.80300 |
August | 514.00000 | 24.11536 | 56.44567 | -0.3490 | 8.13959 |
September | 485.00000 | 24.20769 | 52.07603 | -0.3347 | 8.61134 |
October | 502.00000 | 24.31069 | 42.03939 | 0.50650 | 11.68070 |
November | 489.00000 | 24.04946 | 37.00437 | 0.39315 | 9.57504 |
December | 497.00000 | 23.97906 | 31.42995 | 0.34235 | 9.02620 |
Annual Sum or Average | 5943.00000 | 23.88949 | 45.04389 | 0.00854 | 9.67606 |
Minimum of Months | 454.00000 | 23.35889 | 31.42995 | -0.6586 | 7.80246 |
Maximum of Months | 514.00000 | 24.31069 | 56.44567 | 0.50650 | 15.33251 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.86895 | 38.35008 | 0.05528 | 6.54417 |
February | 454.00000 | 22.99924 | 41.23119 | 0.11441 | 6.55460 |
March | 514.00000 | 23.11419 | 44.16274 | 0.16838 | 7.01709 |
April | 485.00000 | 23.91823 | 45.77349 | 0.40967 | 9.75746 |
May | 508.00000 | 23.94241 | 45.21362 | -0.4903 | 11.98338 |
June | 496.00000 | 24.17146 | 50.82609 | -0.3360 | 8.54976 |
July | 497.00000 | 24.40893 | 54.29020 | -0.2043 | 7.21008 |
August | 514.00000 | 24.27350 | 55.66308 | -0.2394 | 7.26705 |
September | 485.00000 | 24.17109 | 52.21391 | -0.3444 | 8.72745 |
October | 502.00000 | 24.00907 | 42.85031 | 0.40842 | 9.60382 |
November | 489.00000 | 23.37619 | 38.65551 | 0.19649 | 7.00828 |
December | 497.00000 | 23.04309 | 33.40403 | 0.07254 | 6.23596 |
Annual Sum or Average | 5943.00000 | 23.69534 | 45.26010 | -0.0177 | 8.04767 |
Minimum of Months | 454.00000 | 22.86895 | 33.40403 | -0.4903 | 6.23596 |
Maximum of Months | 514.00000 | 24.40893 | 55.66308 | 0.40967 | 11.98338 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.39588 | 42.36717 | -0.3418 | 9.68044 |
February | 454.00000 | 21.53458 | 45.43883 | -0.2788 | 8.16420 |
March | 514.00000 | 21.77409 | 48.43354 | -0.1971 | 7.50145 |
April | 485.00000 | 22.74802 | 49.76521 | 0.07762 | 6.65171 |
May | 508.00000 | 23.08458 | 48.21201 | -0.8462 | 22.13206 |
June | 496.00000 | 23.68599 | 52.90070 | -0.5779 | 12.97538 |
July | 497.00000 | 23.94687 | 56.40446 | -0.4445 | 9.68806 |
August | 514.00000 | 23.79060 | 58.15970 | -0.4961 | 10.80128 |
September | 485.00000 | 23.41017 | 55.51375 | -0.6766 | 15.95214 |
October | 502.00000 | 23.14853 | 45.81777 | 0.15984 | 7.19792 |
November | 489.00000 | 21.89107 | 42.81473 | -0.2006 | 7.44176 |
December | 497.00000 | 21.36968 | 37.49463 | -0.3714 | 9.43405 |
Annual Sum or Average | 5943.00000 | 22.65644 | 48.64243 | -0.3508 | 10.66322 |
Minimum of Months | 454.00000 | 21.36968 | 37.49463 | -0.8462 | 6.65171 |
Maximum of Months | 514.00000 | 23.94687 | 58.15970 | 0.15984 | 22.13206 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.10834 | 40.38879 | -0.1517 | 7.61171 |
February | 454.00000 | 22.18386 | 43.65164 | -0.1078 | 7.23315 |
March | 514.00000 | 22.44992 | 46.22489 | -0.0147 | 7.37188 |
April | 485.00000 | 23.47189 | 47.05600 | 0.28887 | 8.47148 |
May | 508.00000 | 23.54149 | 46.34422 | -0.6457 | 16.35296 |
June | 496.00000 | 23.89420 | 51.70506 | -0.4503 | 11.14165 |
July | 497.00000 | 24.27312 | 54.68306 | -0.2574 | 8.08983 |
August | 514.00000 | 24.13342 | 56.10586 | -0.2947 | 8.27204 |
September | 485.00000 | 23.75074 | 53.72420 | -0.5070 | 12.28880 |
October | 502.00000 | 23.60965 | 44.24785 | 0.29877 | 8.15737 |
November | 489.00000 | 22.60389 | 40.91508 | -0.0144 | 6.45654 |
December | 497.00000 | 22.09308 | 35.80450 | -0.1802 | 7.08467 |
Annual Sum or Average | 5943.00000 | 23.18301 | 46.76934 | -0.1709 | 9.05976 |
Minimum of Months | 454.00000 | 22.09308 | 35.80450 | -0.6457 | 6.45654 |
Maximum of Months | 514.00000 | 24.27312 | 56.10586 | 0.29877 | 16.35296 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.27042 | 37.54596 | 0.16841 | 8.64533 |
February | 454.00000 | 22.89782 | 41.79852 | 0.08879 | 8.31457 |
March | 514.00000 | 22.75655 | 45.36531 | 0.06702 | 8.05581 |
April | 485.00000 | 23.40441 | 47.39982 | 0.26159 | 8.32571 |
May | 508.00000 | 23.20762 | 47.65071 | -0.7935 | 20.70404 |
June | 496.00000 | 23.65221 | 52.93840 | -0.5857 | 13.40850 |
July | 497.00000 | 23.99616 | 56.10795 | -0.4164 | 9.47475 |
August | 514.00000 | 24.03255 | 56.83198 | -0.3695 | 8.82960 |
September | 485.00000 | 24.02698 | 52.83306 | -0.3969 | 10.32002 |
October | 502.00000 | 24.06373 | 42.90122 | 0.44167 | 11.00374 |
November | 489.00000 | 23.58381 | 38.21758 | 0.26123 | 8.61526 |
December | 497.00000 | 23.44014 | 32.71963 | 0.18656 | 8.31131 |
Annual Sum or Average | 5943.00000 | 23.53028 | 46.07153 | -0.0933 | 10.36206 |
Minimum of Months | 454.00000 | 22.75655 | 32.71963 | -0.7935 | 8.05581 |
Maximum of Months | 514.00000 | 24.06373 | 56.83198 | 0.44167 | 20.70404 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.15306 | 39.94786 | -0.1311 | 7.81760 |
February | 454.00000 | 22.28719 | 42.90173 | -0.0667 | 7.23826 |
March | 514.00000 | 22.47100 | 45.79356 | 0.00614 | 7.33678 |
April | 485.00000 | 23.53783 | 46.79035 | 0.31851 | 9.21387 |
May | 508.00000 | 23.58074 | 46.15628 | -0.6119 | 16.21573 |
June | 496.00000 | 23.98958 | 51.38356 | -0.3912 | 10.11651 |
July | 497.00000 | 24.32017 | 54.61069 | -0.2221 | 7.67579 |
August | 514.00000 | 24.17648 | 56.08260 | -0.2632 | 7.83754 |
September | 485.00000 | 23.95055 | 53.05127 | -0.4167 | 10.61304 |
October | 502.00000 | 23.66085 | 43.82088 | 0.32414 | 9.07384 |
November | 489.00000 | 22.70599 | 40.10456 | 0.02717 | 7.02194 |
December | 497.00000 | 22.28777 | 34.94098 | -0.1220 | 7.19282 |
Annual Sum or Average | 5943.00000 | 23.26617 | 46.33498 | -0.1305 | 8.96183 |
Minimum of Months | 454.00000 | 22.15306 | 34.94098 | -0.6119 | 7.02194 |
Maximum of Months | 514.00000 | 24.32017 | 56.08260 | 0.32414 | 16.21573 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.249824E+11 | 80034.15 | 18-JAN-14:30 | 247.86 | 0.161211E+12 | 0.00 | 0.186193E+12 | 1.95 | 7.71 | 19-JAN-14:20 | 0.00 | 0.00 |
February | 0.153748E+11 | 68462.50 | 01-FEB-12:40 | 190.11 | 0.936918E+11 | 0.00 | 0.109067E+12 | 1.57 | 7.70 | 03-FEB-13:20 | 0.00 | 0.00 |
March | 0.166427E+11 | 67752.67 | 22-MAR-12:30 | 193.21 | 0.104647E+12 | 0.00 | 0.121289E+12 | 1.47 | 7.72 | 22-MAR-14:20 | 0.00 | 0.00 |
April | 0.349763E+11 | 74789.87 | 26-APR-13:40 | 308.32 | 0.233082E+12 | 0.00 | 0.268059E+12 | 2.60 | 7.73 | 27-APR-14:10 | 0.00 | 0.00 |
May | 0.382509E+11 | 67204.23 | 04-MAY-15:00 | 342.60 | 0.248398E+12 | 0.00 | 0.286649E+12 | 2.73 | 7.72 | 02-MAY-15:30 | 0.00 | 0.00 |
June | 0.572846E+11 | 85630.78 | 29-JUN-13:00 | 441.64 | 0.385806E+12 | 0.00 | 0.443090E+12 | 3.79 | 7.95 | 28-JUN-05:03 | 0.00 | 0.00 |
July | 0.864373E+11 | 121306.22 | 31-JUL-15:50 | 577.20 | 0.590027E+12 | 0.00 | 0.676465E+12 | 4.87 | 7.91 | 27-JUL-05:03 | 0.00 | 0.00 |
August | 0.963008E+11 | 125283.02 | 18-AUG-15:50 | 612.19 | 0.663345E+12 | 0.00 | 0.759646E+12 | 5.21 | 7.89 | 21-AUG-05:02 | 0.00 | 0.00 |
September | 0.619115E+11 | 95186.28 | 30-SEP-05:03 | 425.15 | 0.424462E+12 | 0.00 | 0.486373E+12 | 3.74 | 7.91 | 14-SEP-05:03 | 0.00 | 0.00 |
October | 0.703529E+11 | 126944.77 | 02-OCT-05:04 | 450.94 | 0.488379E+12 | 0.00 | 0.558732E+12 | 3.88 | 7.77 | 19-OCT-14:50 | 0.00 | 0.00 |
November | 0.277802E+11 | 67801.12 | 08-NOV-11:10 | 279.71 | 0.180937E+12 | 0.00 | 0.208717E+12 | 2.28 | 7.73 | 20-NOV-13:00 | 0.00 | 0.00 |
December | 0.287354E+11 | 67782.57 | 04-DEC-09:40 | 252.91 | 0.193909E+12 | 0.00 | 0.222644E+12 | 2.07 | 7.75 | 07-DEC-14:40 | 0.00 | 0.00 |
Annual Sum or Average | 0.559030E+12 | 4321.85 | 0.376790E+13 | 0.00 | 0.432692E+13 | 3.02 | 0.00 | 0.00 | ||||
Minimum of Months | 0.153748E+11 | 67204.23 | 190.11 | 0.936918E+11 | 0.00 | 0.109067E+12 | 1.47 | 7.70 | 0.00 | 0.00 | ||
Maximum of Months | 0.963008E+11 | 126944.77 | 612.19 | 0.663345E+12 | 0.00 | 0.759646E+12 | 5.21 | 7.95 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.375076E+09 | 80034.15 | 18-JAN-14:30 | 1.50 | 0.281943E+10 | 0.00 | 0.319451E+10 | 0.02 | 7.66 | 18-JAN-14:40 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.158112E+09 | 66177.72 | 23-MAR-14:20 | 0.67 | 0.118703E+10 | 0.00 | 0.134514E+10 | 0.01 | 7.57 | 23-MAR-14:20 | 0.00 | 0.00 |
April | 0.102998E+10 | 74789.87 | 26-APR-13:40 | 4.17 | 0.759376E+10 | 0.00 | 0.862374E+10 | 0.04 | 7.65 | 26-APR-14:40 | 0.00 | 0.00 |
May | 0.193818E+09 | 65767.32 | 03-MAY-12:30 | 0.83 | 0.147078E+10 | 0.00 | 0.166459E+10 | 0.01 | 7.61 | 03-MAY-12:30 | 0.00 | 0.00 |
June | 0.811609E+10 | 85630.78 | 29-JUN-13:00 | 31.75 | 0.591689E+11 | 0.00 | 0.672850E+11 | 0.32 | 7.95 | 28-JUN-05:03 | 0.00 | 0.00 |
July | 0.302293E+11 | 121306.22 | 31-JUL-15:50 | 104.46 | 0.212727E+12 | 0.00 | 0.242956E+12 | 0.99 | 7.80 | 19-JUL-05:02 | 0.00 | 0.00 |
August | 0.419704E+11 | 125283.02 | 18-AUG-15:50 | 143.92 | 0.296192E+12 | 0.00 | 0.338163E+12 | 1.37 | 7.88 | 24-AUG-05:02 | 0.00 | 0.00 |
September | 0.153531E+11 | 95186.28 | 30-SEP-05:03 | 58.43 | 0.111627E+12 | 0.00 | 0.126980E+12 | 0.59 | 7.84 | 09-SEP-05:04 | 0.00 | 0.00 |
October | 0.229046E+11 | 126944.77 | 02-OCT-05:04 | 82.51 | 0.166866E+12 | 0.00 | 0.189770E+12 | 0.81 | 7.73 | 19-OCT-13:20 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.195576E+09 | 66000.76 | 05-DEC-14:50 | 0.83 | 0.147512E+10 | 0.00 | 0.167069E+10 | 0.01 | 7.58 | 05-DEC-14:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.120526E+12 | 429.07 | 0.861127E+12 | 0.00 | 0.981653E+12 | 0.35 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.419704E+11 | 126944.77 | 143.92 | 0.296192E+12 | 0.00 | 0.338163E+12 | 1.37 | 7.95 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.912663E+10 | 744.00 | 12476.23 | 03-JAN-12:10 | 34226.03 | 18-JAN-16:10 | 21.02 | 18.74 | 2.72 |
February | 0.106007E+11 | 672.00 | 12476.23 | 01-FEB-08:00 | 60882.80 | 01-FEB-16:20 | 23.65 | 18.47 | 2.72 |
March | 0.145698E+11 | 744.00 | 12476.23 | 01-MAR-10:20 | 98808.03 | 31-MAR-23:40 | 26.60 | 18.57 | 2.72 |
April | 0.228915E+11 | 720.00 | 12476.23 | 01-APR-08:40 | 118810.05 | 26-APR-14:10 | 30.27 | 19.13 | 2.72 |
May | 0.145154E+11 | 744.00 | 12476.23 | 01-MAY-09:40 | 51419.41 | 31-MAY-24:00 | 21.65 | 18.82 | 2.72 |
June | 0.241815E+11 | 720.00 | 12476.23 | 01-JUN-08:40 | 81469.51 | 30-JUN-24:00 | 25.41 | 19.52 | 2.72 |
July | 0.313941E+11 | 744.00 | 12476.23 | 01-JUL-05:40 | 108773.56 | 31-JUL-23:53 | 29.46 | 20.58 | 2.72 |
August | 0.323238E+11 | 744.00 | 12476.23 | 01-AUG-00:05 | 123345.38 | 18-AUG-15:10 | 32.57 | 20.93 | 2.72 |
September | 0.216630E+11 | 720.00 | 12476.23 | 01-SEP-08:40 | 56924.91 | 30-SEP-24:00 | 22.94 | 19.86 | 2.72 |
October | 0.260105E+11 | 744.00 | 12476.23 | 01-OCT-00:10 | 79445.82 | 31-OCT-24:00 | 26.45 | 20.61 | 2.72 |
November | 0.180785E+11 | 720.00 | 12476.23 | 01-NOV-11:40 | 88299.85 | 07-NOV-16:20 | 26.96 | 18.78 | 2.72 |
December | 0.196998E+11 | 744.00 | 12476.23 | 04-DEC-07:15 | 116075.26 | 05-DEC-15:50 | 29.80 | 19.01 | 2.72 |
Annual Sum or Average | 0.245055E+12 | 8760.00 | 26.42 | 19.43 | 2.72 | ||||
Minimum of Months | 0.912663E+10 | 672.00 | 12476.23 | 34226.03 | 21.02 | 18.47 | 2.72 | ||
Maximum of Months | 0.323238E+11 | 744.00 | 12476.23 | 123345.38 | 32.57 | 20.93 | 2.72 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.502510E+09 | 165.47 | 14132.22 | 13-JAN-13:50 | 886000.92 | 18-JAN-14:40 | 21.51 | 21.12 | 13.79 |
February | 0.165687E+09 | 108.43 | 2502.40 | 01-FEB-13:20 | 825952.06 | 01-FEB-12:00 | 21.30 | 21.05 | 11.44 |
March | 0.537436E+09 | 125.99 | 14132.22 | 22-MAR-12:10 | 725085.71 | 23-MAR-13:20 | 21.31 | 21.06 | 10.51 |
April | 0.150191E+10 | 235.36 | 14132.22 | 04-APR-12:20 | 811571.79 | 13-APR-09:30 | 21.66 | 21.09 | 19.06 |
May | 0.109125E+10 | 271.67 | 14132.22 | 02-MAY-12:50 | 874572.60 | 03-MAY-12:30 | 21.68 | 21.10 | 21.03 |
June | 0.464404E+10 | 381.66 | 14132.22 | 13-JUN-13:30 | 749709.76 | 21-JUN-14:00 | 22.18 | 21.25 | 28.78 |
July | 0.118795E+11 | 493.35 | 14132.22 | 01-JUL-10:40 | 923764.32 | 31-JUL-16:00 | 22.90 | 21.54 | 36.20 |
August | 0.145231E+11 | 524.03 | 14132.22 | 01-AUG-10:00 | 936519.50 | 18-AUG-16:00 | 23.14 | 21.64 | 38.77 |
September | 0.651671E+10 | 377.57 | 14132.22 | 01-SEP-10:50 | 873914.89 | 29-SEP-07:40 | 22.45 | 21.43 | 28.03 |
October | 0.618236E+10 | 389.10 | 14132.22 | 01-OCT-10:40 | 933362.05 | 16-OCT-08:40 | 22.57 | 21.42 | 28.21 |
November | 0.383565E+09 | 182.92 | 14132.22 | 10-NOV-13:10 | 883871.41 | 28-NOV-14:00 | 21.53 | 21.09 | 16.32 |
December | 0.266484E+09 | 173.47 | 2120.54 | 07-DEC-13:20 | 892468.73 | 05-DEC-15:20 | 21.55 | 21.07 | 14.24 |
Annual Sum or Average | 0.481945E+11 | 3429.03 | 21.99 | 21.24 | 22.28 | ||||
Minimum of Months | 0.165687E+09 | 108.43 | 2120.54 | 725085.71 | 21.30 | 21.05 | 10.51 | ||
Maximum of Months | 0.145231E+11 | 524.03 | 14132.22 | 936519.50 | 23.14 | 21.64 | 38.77 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 6036312.28 | 0.83 | 2782.82 | 18-JAN-14:40 | 886000.92 | 18-JAN-14:40 | 21.51 | 21.50 | 0.05 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.30 | 21.30 | 0.00 |
March | 8479330.11 | 0.17 | 14132.22 | 23-MAR-14:00 | 641295.68 | 23-MAR-14:00 | 21.31 | 21.31 | 0.01 |
April | 0.144149E+09 | 2.83 | 14132.22 | 26-APR-10:30 | 762730.53 | 26-APR-14:10 | 21.66 | 21.64 | 0.19 |
May | 12820011.42 | 0.83 | 14132.22 | 03-MAY-12:30 | 874572.60 | 03-MAY-12:30 | 21.68 | 21.67 | 0.05 |
June | 0.159411E+10 | 31.33 | 14132.22 | 21-JUN-13:00 | 733586.45 | 21-JUN-13:00 | 22.18 | 22.05 | 2.12 |
July | 0.529859E+10 | 104.15 | 14132.22 | 12-JUL-12:10 | 923764.32 | 31-JUL-16:00 | 22.90 | 22.44 | 6.83 |
August | 0.726079E+10 | 142.72 | 14132.22 | 02-AUG-09:30 | 936519.50 | 18-AUG-16:00 | 23.14 | 22.51 | 9.36 |
September | 0.275666E+10 | 54.37 | 14132.22 | 05-SEP-12:50 | 850728.90 | 29-SEP-08:50 | 22.45 | 22.21 | 3.68 |
October | 0.298553E+10 | 67.51 | 14132.22 | 01-OCT-11:13 | 933362.05 | 16-OCT-08:40 | 22.57 | 22.24 | 4.43 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.53 | 21.53 | 0.00 |
December | 1942925.05 | 0.50 | 1231.01 | 05-DEC-14:30 | 885584.14 | 05-DEC-14:30 | 21.55 | 21.55 | 0.03 |
Annual Sum or Average | 0.200691E+11 | 405.24 | 21.99 | 21.83 | 2.26 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.30 | 21.30 | 0.00 | ||
Maximum of Months | 0.726079E+10 | 142.72 | 14132.22 | 936519.50 | 23.14 | 22.51 | 9.36 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.101213E+11 | 0.00 | 150.25 | 654473.85 | 03-JAN-06:02 | 0.00 | 28.23 | 38.72 | 0.02 | 0.00 | 0.00 | 0.44 | 03-JAN-06:02 |
February | 0.281810E+10 | 0.00 | 112.60 | 250582.96 | 27-FEB-06:03 | 0.00 | 25.43 | 34.42 | 0.01 | 0.00 | 0.00 | 0.17 | 27-FEB-06:03 |
March | 0.687033E+10 | 0.00 | 116.40 | 719336.60 | 30-MAR-05:02 | 0.00 | 25.57 | 33.89 | 0.01 | 0.00 | 0.00 | 0.48 | 30-MAR-05:02 |
April | 0.527880E+09 | 0.00 | 20.88 | 175834.51 | 01-APR-05:03 | 0.00 | 23.79 | 25.38 | 0.00 | 0.00 | 0.00 | 0.12 | 01-APR-05:03 |
May | 79463336.58 | 0.00 | 8.97 | 85823.22 | 13-MAY-05:02 | 0.00 | 24.55 | 25.21 | 0.00 | 0.00 | 0.00 | 0.06 | 13-MAY-05:02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 25.03 | 25.03 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 25.03 | 25.03 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 25.03 | 25.03 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 25.03 | 25.03 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 74408010.32 | 0.00 | 16.86 | 27956.28 | 30-OCT-05:03 | 0.00 | 24.64 | 25.89 | 0.00 | 0.00 | 0.00 | 0.02 | 30-OCT-05:03 |
November | 0.932132E+09 | 0.00 | 66.05 | 125308.23 | 24-NOV-06:03 | 0.00 | 26.57 | 31.36 | 0.00 | 0.00 | 0.00 | 0.08 | 24-NOV-06:03 |
December | 0.481473E+10 | 0.00 | 128.54 | 465003.25 | 13-DEC-06:03 | 0.00 | 26.14 | 35.29 | 0.01 | 0.00 | 0.00 | 0.31 | 13-DEC-06:03 |
Annual Sum or Average | 0.262383E+11 | 0.00 | 620.55 | 0.00 | 25.42 | 29.17 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.79 | 25.03 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.101213E+11 | 0.00 | 150.25 | 719336.60 | 0.00 | 28.23 | 38.72 | 0.02 | 0.00 | 0.00 | 0.48 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 21.02 | 21.02 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 23.65 | 23.65 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 26.60 | 26.60 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 30.27 | 30.27 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 21.65 | 21.65 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 25.41 | 25.41 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 29.46 | 29.46 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 32.57 | 32.57 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 22.94 | 22.94 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 26.45 | 26.45 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 26.96 | 26.96 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 29.80 | 29.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 26.42 | 26.42 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 | 21.02 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.57 | 32.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.170844E+11 | 0.00 | 216.12 | 0.170609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76846.85 | 18-JAN-13:20 | 76846.85 | 18-JAN-13:20 | 0.00 | 0.00 | 0.00 |
February | 0.100549E+11 | 0.00 | 169.47 | 0.998685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72397.62 | 01-FEB-12:00 | 72397.62 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.121751E+11 | 0.00 | 172.11 | 0.118935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82238.36 | 23-MAR-14:00 | 70728.52 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.281334E+11 | 0.00 | 292.38 | 0.280763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96181.11 | 26-APR-13:10 | 93154.51 | 26-APR-13:50 | 0.00 | 0.00 | 0.00 |
May | 0.250289E+11 | 0.00 | 324.74 | 0.249479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68882.07 | 03-MAY-13:00 | 68882.07 | 03-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.467966E+11 | 0.00 | 425.64 | 0.422215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111550.63 | 29-JUN-13:00 | 76559.88 | 26-JUN-10:00 | 0.00 | 0.00 | 0.00 |
July | 0.875878E+11 | 0.00 | 556.06 | 0.635415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158971.46 | 31-JUL-15:40 | 97711.73 | 31-JUL-13:10 | 0.00 | 0.00 | 0.00 |
August | 0.108338E+12 | 0.00 | 595.48 | 0.736705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 162115.63 | 07-AUG-10:40 | 99444.60 | 07-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.525867E+11 | 0.00 | 405.30 | 0.436483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124925.69 | 22-SEP-12:30 | 123162.32 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.661566E+11 | 0.00 | 424.61 | 0.555816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 157907.68 | 05-OCT-05:02 | 118264.02 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.213583E+11 | 0.00 | 254.23 | 0.211329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82593.59 | 28-NOV-14:00 | 82593.59 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.252008E+11 | 0.00 | 232.53 | 0.251260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88672.06 | 05-DEC-15:00 | 88672.06 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.500502E+12 | 0.00 | 4068.68 | 0.416888E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.100549E+11 | 0.00 | 169.47 | 0.998685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68882.07 | 68882.07 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.108338E+12 | 0.00 | 595.48 | 0.736705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 162115.63 | 123162.32 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.134489E+12 | 0.00 | 231.58 | 0.133989E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 613497.39 | 18-JAN-13:20 | 613497.39 | 18-JAN-13:20 | 0.00 | 0.00 | 0.00 |
February | 0.726511E+11 | 0.00 | 178.99 | 0.720484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 566884.75 | 01-FEB-12:00 | 566884.75 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.825092E+11 | 0.00 | 175.46 | 0.810073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 635008.95 | 23-MAR-14:20 | 550159.92 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.189786E+12 | 0.00 | 269.43 | 0.189693E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 721276.35 | 26-APR-14:00 | 721276.35 | 26-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.197201E+12 | 0.00 | 320.93 | 0.196550E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 593384.21 | 03-MAY-13:00 | 593384.21 | 03-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.363143E+12 | 0.00 | 403.67 | 0.329462E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 929938.48 | 30-JUN-05:03 | 624532.90 | 29-JUN-11:00 | 0.00 | 0.00 | 0.00 |
July | 0.649832E+12 | 0.00 | 446.07 | 0.479907E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1241299.45 | 31-JUL-15:50 | 779334.75 | 19-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.764864E+12 | 0.00 | 460.39 | 0.537292E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1288127.99 | 18-AUG-15:50 | 803496.94 | 17-AUG-14:10 | 0.00 | 0.00 | 0.00 |
September | 0.434754E+12 | 0.00 | 392.13 | 0.364038E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1114238.17 | 30-SEP-05:03 | 1114238.17 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.518391E+12 | 0.00 | 400.75 | 0.438707E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1467934.79 | 05-OCT-05:02 | 1030268.50 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.144799E+12 | 0.00 | 253.27 | 0.143654E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 588438.58 | 28-NOV-14:00 | 588438.58 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.166934E+12 | 0.00 | 226.33 | 0.166416E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 622572.56 | 05-DEC-15:00 | 622572.56 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371935E+13 | 0.00 | 3758.98 | 0.313276E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.726511E+11 | 0.00 | 175.46 | 0.720484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 566884.75 | 550159.92 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.764864E+12 | 0.00 | 460.39 | 0.537292E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1467934.79 | 1114238.17 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.103661E+11 | 0.00 | 198.44 | 0.103661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57456.28 | 18-JAN-13:40 | 57456.28 | 18-JAN-13:40 | 0.00 | 0.00 | 0.00 |
February | 0.577057E+10 | 0.00 | 153.26 | 0.571234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50050.99 | 03-FEB-15:00 | 50050.99 | 03-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.709783E+10 | 0.00 | 150.87 | 0.702439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62293.84 | 23-MAR-15:00 | 57220.34 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.185353E+11 | 0.00 | 256.09 | 0.185213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90951.89 | 26-APR-13:50 | 88569.12 | 26-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.192659E+11 | 0.00 | 305.82 | 0.192102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67950.72 | 03-MAY-13:10 | 67950.72 | 03-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.379305E+11 | 0.00 | 392.40 | 0.341797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105510.94 | 29-JUN-13:00 | 68966.21 | 21-JUN-13:10 | 0.00 | 0.00 | 0.00 |
July | 0.700199E+11 | 0.00 | 434.93 | 0.515185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155543.70 | 31-JUL-15:20 | 97196.31 | 19-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.817907E+11 | 0.00 | 446.14 | 0.569360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158825.48 | 18-AUG-15:30 | 97829.64 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.430475E+11 | 0.00 | 376.29 | 0.362120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114364.18 | 29-SEP-13:40 | 114364.18 | 29-SEP-13:40 | 0.00 | 0.00 | 0.00 |
October | 0.495090E+11 | 0.00 | 381.93 | 0.418668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153751.66 | 05-OCT-05:02 | 116055.54 | 16-OCT-13:10 | 0.00 | 0.00 | 0.00 |
November | 0.111376E+11 | 0.00 | 226.17 | 0.111357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54539.31 | 19-NOV-13:22 | 54539.31 | 19-NOV-13:22 | 0.00 | 0.00 | 0.00 |
December | 0.130699E+11 | 0.00 | 203.21 | 0.130677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61815.67 | 05-DEC-15:00 | 61815.67 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367541E+12 | 0.00 | 3525.55 | 0.305751E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.577057E+10 | 0.00 | 150.87 | 0.571234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50050.99 | 50050.99 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.817907E+11 | 0.00 | 446.14 | 0.569360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158825.48 | 116055.54 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.105371E+11 | 0.00 | 153.52 | 0.104822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66345.79 | 17-JAN-12:00 | 61075.65 | 17-JAN-12:00 | 0.00 | 0.00 | 0.00 |
February | 0.471321E+10 | 0.00 | 93.49 | 0.466714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48530.42 | 01-FEB-12:00 | 48530.42 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.526671E+10 | 0.00 | 96.65 | 0.523332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40177.88 | 23-MAR-14:00 | 40177.88 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.135341E+11 | 0.00 | 192.13 | 0.134676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50917.11 | 26-APR-13:10 | 50917.11 | 26-APR-13:10 | 0.00 | 0.00 | 0.00 |
May | 0.131628E+11 | 0.00 | 209.08 | 0.130963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47262.47 | 03-MAY-04:03 | 44928.43 | 03-MAY-12:20 | 0.00 | 0.00 | 0.00 |
June | 0.243364E+11 | 0.00 | 277.05 | 0.231338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65401.61 | 26-JUN-12:10 | 55460.07 | 26-JUN-10:00 | 0.00 | 0.00 | 0.00 |
July | 0.416264E+11 | 0.00 | 322.37 | 0.349772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93998.47 | 31-JUL-09:10 | 60940.41 | 31-JUL-12:10 | 0.00 | 0.00 | 0.00 |
August | 0.482945E+11 | 0.00 | 357.89 | 0.389361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108908.25 | 07-AUG-10:00 | 63170.86 | 14-AUG-11:00 | 0.00 | 0.00 | 0.00 |
September | 0.292931E+11 | 0.00 | 281.86 | 0.257919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83642.12 | 22-SEP-10:00 | 71611.97 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.383246E+11 | 0.00 | 301.84 | 0.331534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96285.72 | 02-OCT-13:00 | 78463.52 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.119272E+11 | 0.00 | 176.91 | 0.119055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53749.98 | 27-NOV-12:00 | 53749.98 | 27-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 0.146407E+11 | 0.00 | 159.74 | 0.146339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63087.30 | 04-DEC-10:00 | 63087.30 | 04-DEC-10:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255657E+12 | 0.00 | 2622.52 | 0.229479E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.471321E+10 | 0.00 | 93.49 | 0.466714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40177.88 | 40177.88 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.482945E+11 | 0.00 | 357.89 | 0.389361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108908.25 | 78463.52 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.512948E+10 | 0.118881E+10 | 744.00 | 0.508799E+10 | 41492574.98 | 0.00 | 0.32 | 15-JAN-16:05 | 0.19 | 28-JAN-07:20 | 2374.50 | 18-JAN-16:10 | 2338.08 | 15-JAN-16:10 | 164.80 | 17-JAN-15:00 | 629.73 | 15-JAN-14:33 | 0.00 |
February | 0.932725E+10 | 0.200663E+10 | 672.00 | 0.926814E+10 | 59108665.78 | 0.00 | 0.55 | 05-FEB-16:55 | 0.41 | 25-FEB-18:00 | 4475.10 | 20-FEB-16:55 | 4465.71 | 20-FEB-17:00 | 205.15 | 13-FEB-17:00 | 1103.10 | 01-FEB-12:00 | 0.00 |
March | 0.154872E+11 | 0.318019E+10 | 744.00 | 0.154007E+11 | 86446432.31 | 0.00 | 0.86 | 31-MAR-24:00 | 0.63 | 01-MAR-07:05 | 7529.05 | 31-MAR-24:00 | 7529.05 | 31-MAR-24:00 | 248.48 | 23-MAR-16:00 | 1485.81 | 31-MAR-24:00 | 0.00 |
April | 0.201109E+11 | 0.404289E+10 | 720.00 | 0.199970E+11 | 0.113863E+09 | 0.00 | 0.96 | 02-APR-13:52 | 0.31 | 30-APR-23:55 | 8325.83 | 30-APR-17:25 | 8307.25 | 30-APR-17:30 | 230.39 | 13-APR-16:00 | 2074.33 | 26-APR-13:00 | 0.00 |
May | 0.551086E+10 | 0.125209E+10 | 744.00 | 0.541480E+10 | 96065013.98 | 0.00 | 0.47 | 31-MAY-24:00 | 0.21 | 13-MAY-07:00 | 3830.46 | 31-MAY-24:00 | 3815.08 | 31-MAY-24:00 | 206.69 | 05-MAY-15:30 | 810.38 | 31-MAY-24:00 | 0.00 |
June | 0.105297E+11 | 0.230337E+10 | 720.00 | 0.103565E+11 | 0.173233E+09 | 0.00 | 0.68 | 30-JUN-24:00 | 0.44 | 01-JUN-06:10 | 5868.34 | 30-JUN-24:00 | 5864.38 | 30-JUN-24:00 | 281.14 | 29-JUN-13:40 | 1186.50 | 30-JUN-24:00 | 0.00 |
July | 0.161027E+11 | 0.349235E+10 | 744.00 | 0.158559E+11 | 0.246810E+09 | 0.00 | 0.87 | 31-JUL-23:23 | 0.67 | 08-JUL-07:00 | 7736.31 | 31-JUL-23:35 | 7728.82 | 31-JUL-23:35 | 356.67 | 28-JUL-14:00 | 1730.90 | 31-JUL-13:00 | 0.00 |
August | 0.211233E+11 | 0.447143E+10 | 744.00 | 0.208324E+11 | 0.290973E+09 | 0.00 | 0.97 | 17-AUG-14:20 | 0.31 | 31-AUG-24:00 | 8391.84 | 06-AUG-17:37 | 8371.20 | 06-AUG-17:37 | 371.04 | 18-AUG-16:00 | 2185.73 | 17-AUG-14:00 | 0.00 |
September | 0.562032E+10 | 0.131525E+10 | 720.00 | 0.545178E+10 | 0.168538E+09 | 0.00 | 0.49 | 30-SEP-24:00 | 0.23 | 20-SEP-06:40 | 4027.69 | 30-SEP-24:00 | 4027.69 | 30-SEP-24:00 | 322.95 | 22-SEP-10:50 | 927.10 | 29-SEP-13:00 | 0.00 |
October | 0.108535E+11 | 0.249405E+10 | 744.00 | 0.107399E+11 | 0.113652E+09 | 0.00 | 0.68 | 31-OCT-24:00 | 0.44 | 28-OCT-07:00 | 5836.99 | 31-OCT-24:00 | 5834.24 | 31-OCT-24:00 | 338.86 | 05-OCT-16:00 | 1660.78 | 16-OCT-11:00 | 0.00 |
November | 0.151506E+11 | 0.315728E+10 | 720.00 | 0.150857E+11 | 64947334.42 | 0.00 | 0.80 | 28-NOV-14:00 | 0.65 | 18-NOV-07:40 | 6368.51 | 12-NOV-16:15 | 6360.04 | 12-NOV-16:20 | 235.16 | 10-NOV-17:00 | 1656.52 | 28-NOV-14:00 | 0.00 |
December | 0.206180E+11 | 0.421316E+10 | 744.00 | 0.205884E+11 | 29647158.82 | 0.00 | 1.00 | 19-DEC-10:30 | 0.83 | 23-DEC-07:15 | 8337.34 | 25-DEC-16:15 | 8337.34 | 25-DEC-16:15 | 213.02 | 07-DEC-16:20 | 2132.01 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.155564E+12 | 0.331175E+11 | 8760.00 | 0.154079E+12 | 0.148478E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.512948E+10 | 0.118881E+10 | 672.00 | 0.508799E+10 | 29647158.82 | 0.00 | 0.32 | 0.19 | 2374.50 | 2338.08 | 164.80 | 629.73 | 0.00 | ||||||
Maximum of Months | 0.211233E+11 | 0.447143E+10 | 744.00 | 0.208324E+11 | 0.290973E+09 | 0.00 | 1.00 | 0.83 | 8391.84 | 8371.20 | 371.04 | 2185.73 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.376786E+11 | 0.892245E+10 | 744.00 | 0.372760E+11 | 0.402666E+09 | 0.00 | 0.30 | 18-JAN-16:10 | 0.08 | 02-JAN-07:10 | 22009.20 | 18-JAN-16:10 | 21167.77 | 18-JAN-16:10 | 1608.76 | 20-JAN-16:20 | 5638.43 | 24-JAN-16:00 | 0.00 |
February | 0.795436E+11 | 0.172984E+11 | 672.00 | 0.789585E+11 | 0.585099E+09 | 0.00 | 0.54 | 03-FEB-15:00 | 0.34 | 25-FEB-18:00 | 40717.23 | 01-FEB-16:50 | 39144.16 | 22-FEB-17:00 | 2063.05 | 13-FEB-17:00 | 10180.39 | 01-FEB-12:00 | 0.00 |
March | 0.138222E+12 | 0.286079E+11 | 744.00 | 0.137359E+12 | 0.863116E+09 | 0.00 | 0.81 | 31-MAR-23:40 | 0.56 | 30-MAR-06:05 | 67278.34 | 31-MAR-23:40 | 67278.34 | 31-MAR-23:40 | 2470.50 | 23-MAR-16:00 | 13815.88 | 23-MAR-14:00 | 0.00 |
April | 0.187089E+12 | 0.377448E+11 | 720.00 | 0.185950E+12 | 0.113871E+10 | 0.00 | 0.95 | 26-APR-13:30 | 0.27 | 30-APR-24:00 | 77631.06 | 26-APR-16:00 | 77343.05 | 30-APR-17:30 | 2292.86 | 13-APR-16:00 | 19778.74 | 26-APR-13:00 | 0.00 |
May | 0.471750E+11 | 0.108143E+11 | 744.00 | 0.462341E+11 | 0.940869E+09 | 0.00 | 0.44 | 31-MAY-24:00 | 0.15 | 13-MAY-07:00 | 34659.51 | 31-MAY-24:00 | 34463.18 | 31-MAY-24:00 | 2032.69 | 05-MAY-15:30 | 7367.67 | 31-MAY-24:00 | 0.00 |
June | 0.968154E+11 | 0.212617E+11 | 720.00 | 0.950945E+11 | 0.172091E+10 | 0.00 | 0.68 | 30-JUN-24:00 | 0.42 | 01-JUN-06:50 | 55393.08 | 30-JUN-24:00 | 55349.16 | 30-JUN-24:00 | 2797.72 | 29-JUN-13:40 | 11213.78 | 30-JUN-24:00 | 0.00 |
July | 0.151908E+12 | 0.329926E+11 | 744.00 | 0.149447E+12 | 0.246060E+10 | 0.00 | 0.87 | 31-JUL-23:53 | 0.65 | 08-JUL-07:00 | 73931.03 | 31-JUL-23:53 | 73861.37 | 31-JUL-23:57 | 3549.96 | 28-JUL-14:00 | 16502.52 | 31-JUL-13:00 | 0.00 |
August | 0.200451E+12 | 0.424641E+11 | 744.00 | 0.197545E+12 | 0.290633E+10 | 0.00 | 0.98 | 17-AUG-14:20 | 0.26 | 31-AUG-24:00 | 79993.46 | 17-AUG-16:00 | 78226.30 | 06-AUG-17:42 | 3692.77 | 18-AUG-16:00 | 20896.81 | 17-AUG-14:00 | 0.00 |
September | 0.494520E+11 | 0.116585E+11 | 720.00 | 0.477955E+11 | 0.165657E+10 | 0.00 | 0.49 | 30-SEP-24:00 | 0.20 | 20-SEP-07:00 | 38287.49 | 30-SEP-24:00 | 38287.49 | 30-SEP-24:00 | 3177.99 | 22-SEP-11:00 | 8671.78 | 29-SEP-13:00 | 0.00 |
October | 0.985402E+11 | 0.227836E+11 | 744.00 | 0.974108E+11 | 0.112935E+10 | 0.00 | 0.66 | 31-OCT-24:00 | 0.40 | 28-OCT-07:00 | 53989.07 | 31-OCT-24:00 | 53955.32 | 31-OCT-24:00 | 3355.65 | 05-OCT-16:00 | 15699.28 | 16-OCT-11:00 | 0.00 |
November | 0.136219E+12 | 0.285908E+11 | 720.00 | 0.135571E+12 | 0.648031E+09 | 0.00 | 0.79 | 28-NOV-14:00 | 0.59 | 18-NOV-07:50 | 59644.67 | 10-NOV-16:20 | 58684.27 | 12-NOV-16:30 | 2348.98 | 10-NOV-17:00 | 15519.74 | 28-NOV-14:00 | 0.00 |
December | 0.186635E+12 | 0.384354E+11 | 744.00 | 0.186336E+12 | 0.298988E+09 | 0.00 | 1.00 | 19-DEC-13:00 | 0.77 | 13-DEC-07:10 | 77582.46 | 07-DEC-16:10 | 76086.86 | 19-DEC-16:10 | 2119.20 | 07-DEC-16:20 | 20321.71 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.140973E+13 | 0.301575E+12 | 8760.00 | 0.139498E+13 | 0.147512E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.376786E+11 | 0.892245E+10 | 672.00 | 0.372760E+11 | 0.298988E+09 | 0.00 | 0.30 | 0.08 | 22009.20 | 21167.77 | 1608.76 | 5638.43 | 0.00 | ||||||
Maximum of Months | 0.200451E+12 | 0.424641E+11 | 744.00 | 0.197545E+12 | 0.290633E+10 | 0.00 | 1.00 | 0.77 | 79993.46 | 78226.30 | 3692.77 | 20896.81 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.248048E+10 | 0.605582E+09 | 687.76 | 0.244154E+10 | 38941526.04 | 0.00 | 0.30 | 18-JAN-16:10 | 0.00 | 01-JAN-00:05 | 2211.59 | 18-JAN-16:10 | 2127.14 | 18-JAN-16:10 | 161.65 | 20-JAN-16:10 | 556.41 | 24-JAN-16:00 | 0.00 |
February | 0.687344E+10 | 0.151550E+10 | 672.00 | 0.681583E+10 | 57606796.75 | 0.00 | 0.53 | 03-FEB-15:00 | 0.23 | 26-FEB-07:20 | 4084.04 | 01-FEB-16:40 | 3913.15 | 03-FEB-16:50 | 208.07 | 13-FEB-17:00 | 1013.45 | 03-FEB-15:00 | 0.00 |
March | 0.128108E+11 | 0.267828E+10 | 744.00 | 0.127250E+11 | 85799142.03 | 0.00 | 0.75 | 31-MAR-23:20 | 0.45 | 30-MAR-06:05 | 6291.41 | 31-MAR-23:20 | 6291.41 | 31-MAR-23:20 | 247.28 | 23-MAR-16:00 | 1394.62 | 23-MAR-14:00 | 0.00 |
April | 0.182137E+11 | 0.369711E+10 | 720.00 | 0.181001E+11 | 0.113623E+09 | 0.00 | 0.94 | 26-APR-13:30 | 0.24 | 30-APR-24:00 | 7840.20 | 26-APR-16:00 | 7799.15 | 30-APR-17:30 | 229.25 | 13-APR-16:00 | 1999.25 | 26-APR-13:00 | 0.00 |
May | 0.422734E+10 | 0.979352E+09 | 743.92 | 0.413420E+10 | 93148941.03 | 0.00 | 0.41 | 31-MAY-23:30 | 0.00 | 14-MAY-04:45 | 3221.60 | 31-MAY-23:20 | 3186.23 | 31-MAY-23:40 | 201.20 | 05-MAY-15:30 | 689.52 | 31-MAY-23:30 | 0.00 |
June | 0.947851E+10 | 0.209100E+10 | 720.00 | 0.930656E+10 | 0.171948E+09 | 0.00 | 0.66 | 30-JUN-24:00 | 0.36 | 01-JUN-06:40 | 5442.85 | 30-JUN-24:00 | 5438.10 | 30-JUN-24:00 | 280.98 | 29-JUN-13:40 | 1106.27 | 30-JUN-24:00 | 0.00 |
July | 0.151346E+11 | 0.329751E+10 | 744.00 | 0.148886E+11 | 0.245968E+09 | 0.00 | 0.85 | 31-JUL-23:43 | 0.62 | 06-JUL-06:40 | 7320.82 | 31-JUL-23:53 | 7313.78 | 31-JUL-23:57 | 355.36 | 28-JUL-14:00 | 1675.78 | 31-JUL-13:00 | 0.00 |
August | 0.199585E+11 | 0.424275E+10 | 744.00 | 0.196681E+11 | 0.290421E+09 | 0.00 | 0.97 | 17-AUG-14:20 | 0.24 | 31-AUG-24:00 | 8080.48 | 17-AUG-16:00 | 7952.50 | 20-AUG-17:37 | 369.65 | 18-AUG-16:00 | 2111.16 | 17-AUG-14:00 | 0.00 |
September | 0.465460E+10 | 0.110696E+10 | 720.00 | 0.448958E+10 | 0.165020E+09 | 0.00 | 0.48 | 30-SEP-24:00 | 0.13 | 20-SEP-07:00 | 3789.79 | 30-SEP-24:00 | 3789.79 | 30-SEP-24:00 | 319.07 | 22-SEP-11:00 | 904.66 | 29-SEP-13:00 | 0.00 |
October | 0.937390E+10 | 0.218646E+10 | 744.00 | 0.926134E+10 | 0.112559E+09 | 0.00 | 0.63 | 31-OCT-23:40 | 0.31 | 30-OCT-06:25 | 5192.90 | 31-OCT-23:30 | 5186.26 | 31-OCT-23:40 | 335.54 | 05-OCT-16:00 | 1590.28 | 16-OCT-11:00 | 0.00 |
November | 0.126247E+11 | 0.267768E+10 | 720.00 | 0.125602E+11 | 64446675.15 | 0.00 | 0.77 | 28-NOV-14:00 | 0.48 | 27-NOV-07:05 | 5975.75 | 10-NOV-16:20 | 5747.49 | 10-NOV-16:10 | 234.35 | 10-NOV-17:00 | 1546.02 | 28-NOV-14:00 | 0.00 |
December | 0.173877E+11 | 0.362434E+10 | 744.00 | 0.173581E+11 | 29664970.05 | 0.00 | 0.98 | 19-DEC-13:10 | 0.67 | 26-DEC-07:05 | 7750.16 | 07-DEC-16:10 | 7613.17 | 19-DEC-16:10 | 211.81 | 07-DEC-16:20 | 2023.29 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.133218E+12 | 0.287025E+11 | 8703.68 | 0.131749E+12 | 0.146915E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.248048E+10 | 0.605582E+09 | 672.00 | 0.244154E+10 | 29664970.05 | 0.00 | 0.30 | 0.00 | 2211.59 | 2127.14 | 161.65 | 556.41 | 0.00 | ||||||
Maximum of Months | 0.199585E+11 | 0.424275E+10 | 744.00 | 0.196681E+11 | 0.290421E+09 | 0.00 | 0.98 | 0.67 | 8080.48 | 7952.50 | 369.65 | 2111.16 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 0.00 | 78.16 | 40.59 | 327.59 | 0.00 | 0.00 | 0.00 |
February | 98.12 | 0.00 | 98.12 | 50.21 | 298.81 | 0.00 | 0.00 | 0.00 |
March | 120.24 | 0.00 | 120.24 | 76.27 | 303.50 | 0.00 | 0.00 | 0.00 |
April | 138.53 | 0.53 | 137.99 | 111.30 | 236.87 | 0.00 | 0.00 | 0.00 |
May | 166.46 | 7.75 | 158.71 | 146.50 | 201.20 | 0.00 | 0.00 | 0.00 |
June | 177.38 | 17.34 | 160.03 | 189.69 | 158.61 | 0.00 | 0.00 | 0.00 |
July | 167.95 | 14.08 | 153.87 | 199.63 | 138.77 | 0.00 | 0.00 | 0.00 |
August | 139.47 | 2.79 | 136.68 | 158.80 | 146.41 | 0.00 | 0.00 | 0.00 |
September | 118.05 | 0.02 | 118.03 | 123.04 | 180.17 | 0.00 | 0.00 | 0.00 |
October | 93.64 | 0.00 | 93.64 | 103.94 | 205.05 | 0.00 | 0.00 | 0.00 |
November | 84.79 | 0.00 | 84.79 | 47.96 | 301.28 | 0.00 | 0.00 | 0.00 |
December | 72.76 | 0.00 | 72.76 | 33.61 | 337.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.39 | 3.56 | 117.83 | 107.14 | 235.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.76 | 0.00 | 72.76 | 33.61 | 138.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 177.38 | 17.34 | 160.03 | 199.63 | 337.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 0.00 | 78.16 | 40.59 | 327.59 | 0.00 | 0.00 | 0.00 |
February | 98.12 | 0.00 | 98.12 | 50.21 | 298.81 | 0.00 | 0.00 | 0.00 |
March | 120.23 | 0.00 | 120.23 | 76.27 | 303.50 | 0.00 | 0.00 | 0.00 |
April | 138.52 | 0.53 | 137.99 | 111.29 | 236.87 | 0.00 | 0.00 | 0.00 |
May | 166.46 | 7.75 | 158.71 | 146.50 | 201.20 | 0.00 | 0.00 | 0.00 |
June | 177.37 | 17.34 | 160.03 | 189.68 | 158.61 | 0.00 | 0.00 | 0.00 |
July | 167.94 | 14.08 | 153.87 | 199.63 | 138.77 | 0.00 | 0.00 | 0.00 |
August | 139.47 | 2.79 | 136.68 | 158.80 | 146.41 | 0.00 | 0.00 | 0.00 |
September | 118.05 | 0.02 | 118.03 | 123.04 | 180.17 | 0.00 | 0.00 | 0.00 |
October | 93.64 | 0.00 | 93.64 | 103.94 | 205.05 | 0.00 | 0.00 | 0.00 |
November | 84.78 | 0.00 | 84.78 | 47.96 | 301.28 | 0.00 | 0.00 | 0.00 |
December | 72.76 | 0.00 | 72.76 | 33.61 | 337.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.39 | 3.56 | 117.83 | 107.14 | 235.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.76 | 0.00 | 72.76 | 33.61 | 138.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 177.37 | 17.34 | 160.03 | 199.63 | 337.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 0.00 | 78.16 | 40.59 | 327.59 | 0.00 | 0.00 | 0.00 |
February | 98.12 | 0.00 | 98.12 | 50.21 | 298.81 | 0.00 | 0.00 | 0.00 |
March | 120.23 | 0.00 | 120.23 | 76.27 | 303.50 | 0.00 | 0.00 | 0.00 |
April | 138.52 | 0.53 | 137.99 | 111.30 | 236.87 | 0.00 | 0.00 | 0.00 |
May | 166.46 | 7.75 | 158.71 | 146.50 | 201.20 | 0.00 | 0.00 | 0.00 |
June | 177.37 | 17.34 | 160.03 | 189.68 | 158.61 | 0.00 | 0.00 | 0.00 |
July | 167.95 | 14.08 | 153.87 | 199.63 | 138.77 | 0.00 | 0.00 | 0.00 |
August | 139.47 | 2.79 | 136.68 | 158.80 | 146.41 | 0.00 | 0.00 | 0.00 |
September | 118.05 | 0.02 | 118.03 | 123.04 | 180.17 | 0.00 | 0.00 | 0.00 |
October | 93.64 | 0.00 | 93.64 | 103.94 | 205.05 | 0.00 | 0.00 | 0.00 |
November | 84.79 | 0.00 | 84.79 | 47.96 | 301.28 | 0.00 | 0.00 | 0.00 |
December | 72.76 | 0.00 | 72.76 | 33.61 | 337.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.39 | 3.56 | 117.83 | 107.14 | 235.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.76 | 0.00 | 72.76 | 33.61 | 138.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 177.37 | 17.34 | 160.03 | 199.63 | 337.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 0.00 | 78.16 | 40.59 | 327.59 | 0.00 | 0.00 | 0.00 |
February | 98.12 | 0.00 | 98.12 | 50.21 | 298.81 | 0.00 | 0.00 | 0.00 |
March | 120.23 | 0.00 | 120.23 | 76.27 | 303.50 | 0.00 | 0.00 | 0.00 |
April | 138.52 | 0.53 | 137.99 | 111.29 | 236.87 | 0.00 | 0.00 | 0.00 |
May | 166.46 | 7.75 | 158.71 | 146.50 | 201.20 | 0.00 | 0.00 | 0.00 |
June | 177.37 | 17.34 | 160.03 | 189.68 | 158.61 | 0.00 | 0.00 | 0.00 |
July | 167.94 | 14.08 | 153.87 | 199.63 | 138.77 | 0.00 | 0.00 | 0.00 |
August | 139.47 | 2.79 | 136.68 | 158.80 | 146.41 | 0.00 | 0.00 | 0.00 |
September | 118.05 | 0.02 | 118.03 | 123.04 | 180.17 | 0.00 | 0.00 | 0.00 |
October | 93.64 | 0.00 | 93.64 | 103.94 | 205.05 | 0.00 | 0.00 | 0.00 |
November | 84.78 | 0.00 | 84.78 | 47.96 | 301.28 | 0.00 | 0.00 | 0.00 |
December | 72.76 | 0.00 | 72.76 | 33.61 | 337.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.39 | 3.56 | 117.83 | 107.14 | 235.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.76 | 0.00 | 72.76 | 33.61 | 138.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 177.37 | 17.34 | 160.03 | 199.63 | 337.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 0.00 | 78.16 | 40.59 | 327.57 | 0.00 | 0.00 | 0.00 |
February | 98.11 | 0.00 | 98.11 | 50.21 | 298.80 | 0.00 | 0.00 | 0.00 |
March | 120.23 | 0.00 | 120.23 | 76.26 | 303.49 | 0.00 | 0.00 | 0.00 |
April | 138.52 | 0.53 | 137.99 | 111.29 | 236.86 | 0.00 | 0.00 | 0.00 |
May | 166.46 | 7.75 | 158.70 | 146.49 | 201.19 | 0.00 | 0.00 | 0.00 |
June | 177.37 | 17.34 | 160.03 | 189.68 | 158.60 | 0.00 | 0.00 | 0.00 |
July | 167.94 | 14.08 | 153.86 | 199.62 | 138.76 | 0.00 | 0.00 | 0.00 |
August | 139.47 | 2.79 | 136.67 | 158.79 | 146.40 | 0.00 | 0.00 | 0.00 |
September | 118.04 | 0.02 | 118.03 | 123.04 | 180.17 | 0.00 | 0.00 | 0.00 |
October | 93.64 | 0.00 | 93.64 | 103.94 | 205.04 | 0.00 | 0.00 | 0.00 |
November | 84.78 | 0.00 | 84.78 | 47.96 | 301.27 | 0.00 | 0.00 | 0.00 |
December | 72.76 | 0.00 | 72.76 | 33.61 | 337.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.39 | 3.56 | 117.83 | 107.13 | 235.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.76 | 0.00 | 72.76 | 33.61 | 138.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 177.37 | 17.34 | 160.03 | 199.62 | 337.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 234.27 | 125.29 | 108.98 | 272.80 | 337.97 | 0.00 | 0.00 | 0.00 |
February | 247.13 | 113.21 | 133.92 | 271.36 | 307.69 | 0.00 | 0.00 | 0.00 |
March | 300.19 | 133.75 | 166.44 | 347.02 | 310.42 | 0.00 | 0.00 | 0.00 |
April | 383.79 | 192.48 | 191.31 | 511.60 | 248.13 | 0.00 | 0.00 | 0.00 |
May | 362.19 | 151.15 | 211.04 | 463.63 | 226.77 | 0.00 | 0.00 | 0.00 |
June | 359.94 | 156.17 | 203.77 | 495.39 | 180.16 | 0.00 | 0.00 | 0.00 |
July | 407.84 | 202.66 | 205.17 | 606.48 | 157.21 | 0.00 | 0.00 | 0.00 |
August | 402.77 | 213.94 | 188.83 | 606.83 | 159.29 | 0.00 | 0.00 | 0.00 |
September | 293.25 | 134.38 | 158.87 | 415.25 | 194.24 | 0.00 | 0.00 | 0.00 |
October | 259.58 | 133.42 | 126.16 | 373.73 | 214.22 | 0.00 | 0.00 | 0.00 |
November | 236.64 | 120.22 | 116.42 | 277.73 | 307.37 | 0.00 | 0.00 | 0.00 |
December | 225.75 | 125.43 | 100.32 | 262.31 | 338.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 309.86 | 150.47 | 159.39 | 409.63 | 248.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 225.75 | 113.21 | 100.32 | 262.31 | 157.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 407.84 | 213.94 | 211.04 | 606.83 | 338.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 234.27 | 125.29 | 108.98 | 272.80 | 337.97 | 0.00 | 0.00 | 0.00 |
February | 247.13 | 113.21 | 133.92 | 271.36 | 307.69 | 0.00 | 0.00 | 0.00 |
March | 300.19 | 133.75 | 166.44 | 347.02 | 310.42 | 0.00 | 0.00 | 0.00 |
April | 383.79 | 192.48 | 191.31 | 511.60 | 248.13 | 0.00 | 0.00 | 0.00 |
May | 362.19 | 151.15 | 211.04 | 463.63 | 226.77 | 0.00 | 0.00 | 0.00 |
June | 359.94 | 156.17 | 203.77 | 495.39 | 180.16 | 0.00 | 0.00 | 0.00 |
July | 407.84 | 202.66 | 205.17 | 606.48 | 157.21 | 0.00 | 0.00 | 0.00 |
August | 402.77 | 213.94 | 188.83 | 606.83 | 159.29 | 0.00 | 0.00 | 0.00 |
September | 293.25 | 134.38 | 158.87 | 415.25 | 194.24 | 0.00 | 0.00 | 0.00 |
October | 259.58 | 133.42 | 126.16 | 373.73 | 214.22 | 0.00 | 0.00 | 0.00 |
November | 236.64 | 120.22 | 116.42 | 277.73 | 307.37 | 0.00 | 0.00 | 0.00 |
December | 225.75 | 125.43 | 100.32 | 262.31 | 338.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 309.86 | 150.47 | 159.39 | 409.63 | 248.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 225.75 | 113.21 | 100.32 | 262.31 | 157.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 407.84 | 213.94 | 211.04 | 606.83 | 338.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 234.27 | 125.29 | 108.98 | 272.80 | 337.96 | 0.00 | 0.00 | 0.00 |
February | 247.13 | 113.21 | 133.92 | 271.35 | 307.69 | 0.00 | 0.00 | 0.00 |
March | 300.19 | 133.75 | 166.44 | 347.02 | 310.42 | 0.00 | 0.00 | 0.00 |
April | 383.79 | 192.48 | 191.31 | 511.59 | 248.12 | 0.00 | 0.00 | 0.00 |
May | 362.19 | 151.15 | 211.04 | 463.63 | 226.76 | 0.00 | 0.00 | 0.00 |
June | 359.93 | 156.17 | 203.76 | 495.38 | 180.15 | 0.00 | 0.00 | 0.00 |
July | 407.83 | 202.66 | 205.17 | 606.47 | 157.21 | 0.00 | 0.00 | 0.00 |
August | 402.76 | 213.93 | 188.83 | 606.82 | 159.29 | 0.00 | 0.00 | 0.00 |
September | 293.24 | 134.38 | 158.87 | 415.24 | 194.23 | 0.00 | 0.00 | 0.00 |
October | 259.57 | 133.41 | 126.16 | 373.73 | 214.22 | 0.00 | 0.00 | 0.00 |
November | 236.63 | 120.22 | 116.41 | 277.72 | 307.37 | 0.00 | 0.00 | 0.00 |
December | 225.74 | 125.43 | 100.32 | 262.30 | 338.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 309.85 | 150.47 | 159.38 | 409.62 | 248.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 225.74 | 113.21 | 100.32 | 262.30 | 157.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 407.83 | 213.93 | 211.04 | 606.82 | 338.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.82 | 378.38 | 137.44 | 749.20 | 305.23 | 0.00 | 0.00 | 0.00 |
February | 405.41 | 249.71 | 155.70 | 554.05 | 280.11 | 0.00 | 0.00 | 0.00 |
March | 323.21 | 156.12 | 167.08 | 433.63 | 292.50 | 0.00 | 0.00 | 0.00 |
April | 270.05 | 102.97 | 167.08 | 387.77 | 242.92 | 0.00 | 0.00 | 0.00 |
May | 192.30 | 23.66 | 168.63 | 224.13 | 215.39 | 0.00 | 0.00 | 0.00 |
June | 168.70 | 10.19 | 158.51 | 196.32 | 169.61 | 0.00 | 0.00 | 0.00 |
July | 178.69 | 20.12 | 158.58 | 243.47 | 148.36 | 0.00 | 0.00 | 0.00 |
August | 229.57 | 72.41 | 157.16 | 362.00 | 156.09 | 0.00 | 0.00 | 0.00 |
September | 319.44 | 161.87 | 157.57 | 506.26 | 185.17 | 0.00 | 0.00 | 0.00 |
October | 406.26 | 271.59 | 134.66 | 643.60 | 202.58 | 0.00 | 0.00 | 0.00 |
November | 493.76 | 348.59 | 145.17 | 714.95 | 282.86 | 0.00 | 0.00 | 0.00 |
December | 551.07 | 419.43 | 131.63 | 803.24 | 310.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 337.57 | 184.37 | 153.21 | 484.68 | 232.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 168.70 | 10.19 | 131.63 | 196.32 | 148.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.07 | 419.43 | 168.63 | 803.24 | 310.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.82 | 378.38 | 137.44 | 749.19 | 305.23 | 0.00 | 0.00 | 0.00 |
February | 405.41 | 249.71 | 155.70 | 554.04 | 280.11 | 0.00 | 0.00 | 0.00 |
March | 323.21 | 156.12 | 167.08 | 433.62 | 292.50 | 0.00 | 0.00 | 0.00 |
April | 270.05 | 102.97 | 167.08 | 387.77 | 242.92 | 0.00 | 0.00 | 0.00 |
May | 192.30 | 23.66 | 168.63 | 224.13 | 215.39 | 0.00 | 0.00 | 0.00 |
June | 168.69 | 10.18 | 158.51 | 196.32 | 169.61 | 0.00 | 0.00 | 0.00 |
July | 178.69 | 20.12 | 158.58 | 243.47 | 148.36 | 0.00 | 0.00 | 0.00 |
August | 229.57 | 72.41 | 157.16 | 362.00 | 156.09 | 0.00 | 0.00 | 0.00 |
September | 319.44 | 161.87 | 157.57 | 506.26 | 185.17 | 0.00 | 0.00 | 0.00 |
October | 406.25 | 271.59 | 134.66 | 643.59 | 202.58 | 0.00 | 0.00 | 0.00 |
November | 493.76 | 348.58 | 145.17 | 714.94 | 282.86 | 0.00 | 0.00 | 0.00 |
December | 551.06 | 419.43 | 131.63 | 803.23 | 310.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 337.57 | 184.36 | 153.21 | 484.68 | 232.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 168.69 | 10.18 | 131.63 | 196.32 | 148.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.06 | 419.43 | 168.63 | 803.23 | 310.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.82 | 378.38 | 137.44 | 749.20 | 305.23 | 0.00 | 0.00 | 0.00 |
February | 405.41 | 249.71 | 155.70 | 554.05 | 280.11 | 0.00 | 0.00 | 0.00 |
March | 323.21 | 156.12 | 167.08 | 433.63 | 292.50 | 0.00 | 0.00 | 0.00 |
April | 270.05 | 102.97 | 167.08 | 387.77 | 242.92 | 0.00 | 0.00 | 0.00 |
May | 192.30 | 23.66 | 168.63 | 224.13 | 215.39 | 0.00 | 0.00 | 0.00 |
June | 168.70 | 10.19 | 158.51 | 196.32 | 169.61 | 0.00 | 0.00 | 0.00 |
July | 178.69 | 20.12 | 158.58 | 243.47 | 148.36 | 0.00 | 0.00 | 0.00 |
August | 229.57 | 72.41 | 157.16 | 362.00 | 156.09 | 0.00 | 0.00 | 0.00 |
September | 319.44 | 161.87 | 157.57 | 506.26 | 185.17 | 0.00 | 0.00 | 0.00 |
October | 406.26 | 271.59 | 134.66 | 643.60 | 202.58 | 0.00 | 0.00 | 0.00 |
November | 493.76 | 348.59 | 145.17 | 714.95 | 282.86 | 0.00 | 0.00 | 0.00 |
December | 551.07 | 419.43 | 131.63 | 803.24 | 310.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 337.57 | 184.37 | 153.21 | 484.68 | 232.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 168.70 | 10.19 | 131.63 | 196.32 | 148.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.07 | 419.43 | 168.63 | 803.24 | 310.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.82 | 378.38 | 137.44 | 749.19 | 305.23 | 0.00 | 0.00 | 0.00 |
February | 405.41 | 249.71 | 155.70 | 554.04 | 280.11 | 0.00 | 0.00 | 0.00 |
March | 323.21 | 156.12 | 167.08 | 433.62 | 292.50 | 0.00 | 0.00 | 0.00 |
April | 270.05 | 102.97 | 167.08 | 387.77 | 242.92 | 0.00 | 0.00 | 0.00 |
May | 192.30 | 23.66 | 168.63 | 224.13 | 215.39 | 0.00 | 0.00 | 0.00 |
June | 168.69 | 10.18 | 158.51 | 196.32 | 169.61 | 0.00 | 0.00 | 0.00 |
July | 178.69 | 20.12 | 158.58 | 243.47 | 148.36 | 0.00 | 0.00 | 0.00 |
August | 229.57 | 72.41 | 157.16 | 362.00 | 156.09 | 0.00 | 0.00 | 0.00 |
September | 319.44 | 161.87 | 157.57 | 506.26 | 185.17 | 0.00 | 0.00 | 0.00 |
October | 406.25 | 271.59 | 134.66 | 643.59 | 202.58 | 0.00 | 0.00 | 0.00 |
November | 493.76 | 348.58 | 145.17 | 714.94 | 282.86 | 0.00 | 0.00 | 0.00 |
December | 551.06 | 419.43 | 131.63 | 803.23 | 310.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 337.57 | 184.36 | 153.21 | 484.68 | 232.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 168.69 | 10.18 | 131.63 | 196.32 | 148.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.06 | 419.43 | 168.63 | 803.23 | 310.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.80 | 378.36 | 137.44 | 749.17 | 305.22 | 0.00 | 0.00 | 0.00 |
February | 405.39 | 249.70 | 155.69 | 554.02 | 280.10 | 0.00 | 0.00 | 0.00 |
March | 323.19 | 156.12 | 167.08 | 433.61 | 292.49 | 0.00 | 0.00 | 0.00 |
April | 270.04 | 102.97 | 167.07 | 387.76 | 242.91 | 0.00 | 0.00 | 0.00 |
May | 192.29 | 23.66 | 168.62 | 224.12 | 215.38 | 0.00 | 0.00 | 0.00 |
June | 168.69 | 10.18 | 158.50 | 196.31 | 169.60 | 0.00 | 0.00 | 0.00 |
July | 178.69 | 20.11 | 158.57 | 243.46 | 148.36 | 0.00 | 0.00 | 0.00 |
August | 229.56 | 72.41 | 157.15 | 361.99 | 156.08 | 0.00 | 0.00 | 0.00 |
September | 319.43 | 161.86 | 157.56 | 506.24 | 185.16 | 0.00 | 0.00 | 0.00 |
October | 406.24 | 271.58 | 134.66 | 643.57 | 202.58 | 0.00 | 0.00 | 0.00 |
November | 493.74 | 348.57 | 145.17 | 714.92 | 282.85 | 0.00 | 0.00 | 0.00 |
December | 551.04 | 419.41 | 131.63 | 803.20 | 310.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 337.56 | 184.36 | 153.20 | 484.66 | 232.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 168.69 | 10.18 | 131.63 | 196.31 | 148.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 551.04 | 419.41 | 168.62 | 803.20 | 310.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.99 | 112.46 | 110.52 | 266.81 | 380.69 | 0.00 | 0.00 | 0.00 |
February | 266.02 | 122.81 | 143.21 | 302.21 | 360.34 | 0.00 | 0.00 | 0.00 |
March | 304.93 | 134.91 | 170.03 | 350.53 | 370.33 | 0.00 | 0.00 | 0.00 |
April | 420.37 | 218.88 | 201.48 | 555.97 | 306.60 | 0.00 | 0.00 | 0.00 |
May | 412.93 | 190.73 | 222.20 | 539.22 | 256.97 | 0.00 | 0.00 | 0.00 |
June | 437.46 | 218.72 | 218.74 | 603.79 | 210.94 | 0.00 | 0.00 | 0.00 |
July | 463.08 | 247.79 | 215.29 | 673.53 | 190.66 | 0.00 | 0.00 | 0.00 |
August | 434.46 | 235.46 | 199.00 | 638.51 | 202.66 | 0.00 | 0.00 | 0.00 |
September | 371.98 | 199.04 | 172.94 | 534.27 | 220.92 | 0.00 | 0.00 | 0.00 |
October | 284.36 | 155.25 | 129.11 | 411.46 | 254.95 | 0.00 | 0.00 | 0.00 |
November | 256.86 | 134.36 | 122.51 | 312.99 | 368.00 | 0.00 | 0.00 | 0.00 |
December | 226.85 | 121.67 | 105.18 | 269.54 | 416.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 342.16 | 174.56 | 167.59 | 455.64 | 294.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 222.99 | 112.46 | 105.18 | 266.81 | 190.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 463.08 | 247.79 | 222.20 | 673.53 | 416.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.99 | 112.46 | 110.52 | 266.81 | 380.69 | 0.00 | 0.00 | 0.00 |
February | 266.02 | 122.81 | 143.21 | 302.21 | 360.34 | 0.00 | 0.00 | 0.00 |
March | 304.93 | 134.91 | 170.03 | 350.53 | 370.33 | 0.00 | 0.00 | 0.00 |
April | 420.37 | 218.88 | 201.48 | 555.97 | 306.60 | 0.00 | 0.00 | 0.00 |
May | 412.93 | 190.73 | 222.20 | 539.22 | 256.97 | 0.00 | 0.00 | 0.00 |
June | 437.46 | 218.72 | 218.74 | 603.79 | 210.94 | 0.00 | 0.00 | 0.00 |
July | 463.08 | 247.79 | 215.29 | 673.53 | 190.66 | 0.00 | 0.00 | 0.00 |
August | 434.46 | 235.46 | 199.00 | 638.51 | 202.66 | 0.00 | 0.00 | 0.00 |
September | 371.98 | 199.04 | 172.94 | 534.27 | 220.92 | 0.00 | 0.00 | 0.00 |
October | 284.36 | 155.25 | 129.11 | 411.46 | 254.95 | 0.00 | 0.00 | 0.00 |
November | 256.86 | 134.36 | 122.51 | 312.99 | 368.00 | 0.00 | 0.00 | 0.00 |
December | 226.85 | 121.67 | 105.18 | 269.54 | 416.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 342.16 | 174.56 | 167.59 | 455.64 | 294.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 222.99 | 112.46 | 105.18 | 266.81 | 190.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 463.08 | 247.79 | 222.20 | 673.53 | 416.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.98 | 112.46 | 110.52 | 266.80 | 380.68 | 0.00 | 0.00 | 0.00 |
February | 266.02 | 122.81 | 143.21 | 302.21 | 360.33 | 0.00 | 0.00 | 0.00 |
March | 304.93 | 134.90 | 170.02 | 350.52 | 370.32 | 0.00 | 0.00 | 0.00 |
April | 420.36 | 218.88 | 201.48 | 555.96 | 306.60 | 0.00 | 0.00 | 0.00 |
May | 412.92 | 190.73 | 222.20 | 539.21 | 256.96 | 0.00 | 0.00 | 0.00 |
June | 437.45 | 218.72 | 218.73 | 603.78 | 210.94 | 0.00 | 0.00 | 0.00 |
July | 463.07 | 247.79 | 215.29 | 673.52 | 190.66 | 0.00 | 0.00 | 0.00 |
August | 434.45 | 235.46 | 199.00 | 638.50 | 202.66 | 0.00 | 0.00 | 0.00 |
September | 371.97 | 199.04 | 172.94 | 534.26 | 220.91 | 0.00 | 0.00 | 0.00 |
October | 284.36 | 155.25 | 129.11 | 411.45 | 254.94 | 0.00 | 0.00 | 0.00 |
November | 256.86 | 134.36 | 122.50 | 312.98 | 368.00 | 0.00 | 0.00 | 0.00 |
December | 226.85 | 121.67 | 105.18 | 269.53 | 416.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 342.15 | 174.56 | 167.59 | 455.64 | 294.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 222.98 | 112.46 | 105.18 | 266.80 | 190.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 463.07 | 247.79 | 222.20 | 673.52 | 416.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 390.82 | 0.00 | 390.82 | 255.14 | 1449.74 | 0.00 | 0.00 | 0.00 |
February | 490.59 | 0.00 | 490.59 | 305.19 | 1314.32 | 0.00 | 0.00 | 0.00 |
March | 601.18 | 0.00 | 601.18 | 439.54 | 1347.51 | 0.00 | 0.00 | 0.00 |
April | 692.63 | 2.67 | 689.96 | 605.41 | 1073.83 | 0.00 | 0.00 | 0.00 |
May | 832.32 | 38.76 | 793.56 | 765.93 | 944.76 | 0.00 | 0.00 | 0.00 |
June | 886.88 | 86.71 | 800.17 | 968.55 | 747.42 | 0.00 | 0.00 | 0.00 |
July | 839.73 | 70.38 | 769.35 | 1020.23 | 666.05 | 0.00 | 0.00 | 0.00 |
August | 697.37 | 13.96 | 683.41 | 819.95 | 696.68 | 0.00 | 0.00 | 0.00 |
September | 590.25 | 0.09 | 590.16 | 637.09 | 837.71 | 0.00 | 0.00 | 0.00 |
October | 468.21 | 0.00 | 468.21 | 551.90 | 937.20 | 0.00 | 0.00 | 0.00 |
November | 423.93 | 0.00 | 423.93 | 292.39 | 1333.08 | 0.00 | 0.00 | 0.00 |
December | 363.82 | 0.00 | 363.82 | 231.30 | 1463.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 606.97 | 17.81 | 589.16 | 576.03 | 1066.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 363.82 | 0.00 | 363.82 | 231.30 | 666.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 886.88 | 86.71 | 800.17 | 1020.23 | 1463.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 702.81 | 375.88 | 326.93 | 843.12 | 931.75 | 0.00 | 0.00 | 0.00 |
February | 741.39 | 339.64 | 401.75 | 834.41 | 848.47 | 0.00 | 0.00 | 0.00 |
March | 900.57 | 401.25 | 499.33 | 1057.96 | 869.46 | 0.00 | 0.00 | 0.00 |
April | 1151.37 | 577.43 | 573.93 | 1534.20 | 718.74 | 0.00 | 0.00 | 0.00 |
May | 1086.56 | 453.45 | 633.12 | 1390.58 | 655.15 | 0.00 | 0.00 | 0.00 |
June | 1079.80 | 468.51 | 611.29 | 1480.51 | 525.59 | 0.00 | 0.00 | 0.00 |
July | 1223.49 | 607.99 | 615.51 | 1806.83 | 476.09 | 0.00 | 0.00 | 0.00 |
August | 1208.30 | 641.81 | 566.49 | 1807.55 | 486.52 | 0.00 | 0.00 | 0.00 |
September | 879.74 | 403.13 | 476.61 | 1245.42 | 559.79 | 0.00 | 0.00 | 0.00 |
October | 778.73 | 400.25 | 378.48 | 1123.73 | 615.04 | 0.00 | 0.00 | 0.00 |
November | 709.90 | 360.66 | 349.24 | 849.65 | 860.77 | 0.00 | 0.00 | 0.00 |
December | 677.23 | 376.28 | 300.96 | 812.13 | 935.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 929.57 | 451.41 | 478.15 | 1234.95 | 706.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 677.23 | 339.64 | 300.96 | 812.13 | 476.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1223.49 | 641.81 | 633.12 | 1807.55 | 935.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2579.17 | 1891.94 | 687.23 | 3732.04 | 1496.21 | 0.00 | 0.00 | 0.00 |
February | 2027.09 | 1248.58 | 778.51 | 2757.59 | 1349.91 | 0.00 | 0.00 | 0.00 |
March | 1616.06 | 780.64 | 835.43 | 2169.23 | 1398.34 | 0.00 | 0.00 | 0.00 |
April | 1350.26 | 514.87 | 835.39 | 1941.19 | 1164.45 | 0.00 | 0.00 | 0.00 |
May | 961.49 | 118.32 | 843.17 | 1124.08 | 1040.60 | 0.00 | 0.00 | 0.00 |
June | 843.48 | 50.93 | 792.56 | 990.84 | 811.88 | 0.00 | 0.00 | 0.00 |
July | 893.48 | 100.58 | 792.90 | 1227.99 | 720.37 | 0.00 | 0.00 | 0.00 |
August | 1147.85 | 362.07 | 785.78 | 1812.21 | 765.28 | 0.00 | 0.00 | 0.00 |
September | 1597.24 | 809.38 | 787.86 | 2516.50 | 908.59 | 0.00 | 0.00 | 0.00 |
October | 2031.31 | 1357.99 | 673.32 | 3200.36 | 994.80 | 0.00 | 0.00 | 0.00 |
November | 2468.85 | 1742.97 | 725.88 | 3558.28 | 1374.76 | 0.00 | 0.00 | 0.00 |
December | 2755.38 | 2097.20 | 658.18 | 4004.37 | 1504.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1687.89 | 921.85 | 766.04 | 2418.62 | 1126.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 843.48 | 50.93 | 658.18 | 990.84 | 720.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2755.38 | 2097.20 | 843.17 | 4004.37 | 1504.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 668.95 | 337.39 | 331.56 | 834.47 | 1008.95 | 0.00 | 0.00 | 0.00 |
February | 798.06 | 368.42 | 429.64 | 946.37 | 921.64 | 0.00 | 0.00 | 0.00 |
March | 914.79 | 404.72 | 510.07 | 1098.99 | 940.85 | 0.00 | 0.00 | 0.00 |
April | 1261.09 | 656.65 | 604.44 | 1707.91 | 795.67 | 0.00 | 0.00 | 0.00 |
May | 1238.78 | 572.19 | 666.59 | 1628.80 | 714.91 | 0.00 | 0.00 | 0.00 |
June | 1312.36 | 656.15 | 656.20 | 1826.45 | 569.42 | 0.00 | 0.00 | 0.00 |
July | 1389.23 | 743.37 | 645.87 | 2042.90 | 518.95 | 0.00 | 0.00 | 0.00 |
August | 1303.37 | 706.37 | 597.00 | 1943.88 | 538.60 | 0.00 | 0.00 | 0.00 |
September | 1115.93 | 597.12 | 518.81 | 1609.91 | 610.36 | 0.00 | 0.00 | 0.00 |
October | 853.08 | 465.74 | 387.33 | 1259.55 | 675.42 | 0.00 | 0.00 | 0.00 |
November | 770.58 | 403.07 | 367.51 | 981.28 | 933.90 | 0.00 | 0.00 | 0.00 |
December | 680.56 | 365.02 | 315.54 | 862.52 | 1028.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1026.45 | 523.68 | 502.77 | 1397.45 | 770.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 668.95 | 337.39 | 315.54 | 834.47 | 518.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1389.23 | 743.37 | 666.59 | 2042.90 | 1028.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 390.82 | 0.00 | 390.82 | 302.15 | 1295.92 | 0.00 | 0.00 | 0.00 |
February | 490.59 | 0.00 | 490.59 | 352.31 | 1171.59 | 0.00 | 0.00 | 0.00 |
March | 601.18 | 0.00 | 601.18 | 483.61 | 1231.03 | 0.00 | 0.00 | 0.00 |
April | 692.63 | 2.67 | 689.96 | 629.88 | 1008.09 | 0.00 | 0.00 | 0.00 |
May | 832.32 | 38.76 | 793.56 | 793.83 | 893.45 | 0.00 | 0.00 | 0.00 |
June | 886.88 | 86.71 | 800.17 | 970.73 | 722.23 | 0.00 | 0.00 | 0.00 |
July | 839.73 | 70.38 | 769.35 | 1009.63 | 654.54 | 0.00 | 0.00 | 0.00 |
August | 697.37 | 13.96 | 683.41 | 814.36 | 681.48 | 0.00 | 0.00 | 0.00 |
September | 590.25 | 0.09 | 590.16 | 646.18 | 796.73 | 0.00 | 0.00 | 0.00 |
October | 468.21 | 0.00 | 468.21 | 572.23 | 875.51 | 0.00 | 0.00 | 0.00 |
November | 423.93 | 0.00 | 423.93 | 336.65 | 1199.28 | 0.00 | 0.00 | 0.00 |
December | 363.82 | 0.00 | 363.82 | 278.87 | 1303.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 606.97 | 17.81 | 589.16 | 600.72 | 985.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 363.82 | 0.00 | 363.82 | 278.87 | 654.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 886.88 | 86.71 | 800.17 | 1009.63 | 1303.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 702.81 | 375.88 | 326.93 | 882.59 | 844.58 | 0.00 | 0.00 | 0.00 |
February | 741.39 | 339.64 | 401.75 | 867.05 | 768.97 | 0.00 | 0.00 | 0.00 |
March | 900.57 | 401.25 | 499.33 | 1087.14 | 806.24 | 0.00 | 0.00 | 0.00 |
April | 1151.37 | 577.43 | 573.93 | 1545.06 | 687.08 | 0.00 | 0.00 | 0.00 |
May | 1086.56 | 453.45 | 633.12 | 1402.53 | 627.36 | 0.00 | 0.00 | 0.00 |
June | 1079.80 | 468.51 | 611.29 | 1478.71 | 513.34 | 0.00 | 0.00 | 0.00 |
July | 1223.49 | 607.99 | 615.51 | 1796.55 | 473.12 | 0.00 | 0.00 | 0.00 |
August | 1208.30 | 641.81 | 566.49 | 1799.09 | 481.82 | 0.00 | 0.00 | 0.00 |
September | 879.74 | 403.13 | 476.61 | 1247.04 | 539.66 | 0.00 | 0.00 | 0.00 |
October | 778.73 | 400.25 | 378.48 | 1134.12 | 584.36 | 0.00 | 0.00 | 0.00 |
November | 709.90 | 360.66 | 349.24 | 882.30 | 789.25 | 0.00 | 0.00 | 0.00 |
December | 677.23 | 376.28 | 300.96 | 852.69 | 847.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 929.57 | 451.41 | 478.15 | 1250.59 | 663.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 677.23 | 339.64 | 300.96 | 852.69 | 473.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1223.49 | 641.81 | 633.12 | 1799.09 | 847.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2579.17 | 1891.94 | 687.23 | 3773.82 | 1379.89 | 0.00 | 0.00 | 0.00 |
February | 2027.09 | 1248.58 | 778.51 | 2797.18 | 1232.39 | 0.00 | 0.00 | 0.00 |
March | 1616.06 | 780.64 | 835.43 | 2205.64 | 1295.01 | 0.00 | 0.00 | 0.00 |
April | 1350.26 | 514.87 | 835.39 | 1954.84 | 1106.57 | 0.00 | 0.00 | 0.00 |
May | 961.49 | 118.32 | 843.17 | 1142.45 | 985.36 | 0.00 | 0.00 | 0.00 |
June | 843.48 | 50.93 | 792.56 | 992.06 | 785.60 | 0.00 | 0.00 | 0.00 |
July | 893.48 | 100.58 | 792.90 | 1217.65 | 710.65 | 0.00 | 0.00 | 0.00 |
August | 1147.85 | 362.07 | 785.78 | 1801.41 | 753.45 | 0.00 | 0.00 | 0.00 |
September | 1597.24 | 809.38 | 787.86 | 2513.91 | 876.96 | 0.00 | 0.00 | 0.00 |
October | 2031.31 | 1357.99 | 673.32 | 3208.16 | 951.59 | 0.00 | 0.00 | 0.00 |
November | 2468.85 | 1742.97 | 725.88 | 3589.09 | 1281.17 | 0.00 | 0.00 | 0.00 |
December | 2755.38 | 2097.20 | 658.18 | 4044.70 | 1393.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1687.89 | 921.85 | 766.04 | 2435.69 | 1061.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 843.48 | 50.93 | 658.18 | 992.06 | 710.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2755.38 | 2097.20 | 843.17 | 4044.70 | 1393.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 668.95 | 337.39 | 331.56 | 858.59 | 924.63 | 0.00 | 0.00 | 0.00 |
February | 798.06 | 368.42 | 429.64 | 970.10 | 843.49 | 0.00 | 0.00 | 0.00 |
March | 914.79 | 404.72 | 510.07 | 1119.91 | 874.94 | 0.00 | 0.00 | 0.00 |
April | 1261.09 | 656.65 | 604.44 | 1713.54 | 759.36 | 0.00 | 0.00 | 0.00 |
May | 1238.78 | 572.19 | 666.59 | 1634.35 | 682.85 | 0.00 | 0.00 | 0.00 |
June | 1312.36 | 656.15 | 656.20 | 1820.25 | 553.56 | 0.00 | 0.00 | 0.00 |
July | 1389.23 | 743.37 | 645.87 | 2030.33 | 512.22 | 0.00 | 0.00 | 0.00 |
August | 1303.37 | 706.37 | 597.00 | 1933.16 | 530.40 | 0.00 | 0.00 | 0.00 |
September | 1115.93 | 597.12 | 518.81 | 1607.57 | 588.93 | 0.00 | 0.00 | 0.00 |
October | 853.08 | 465.74 | 387.33 | 1266.02 | 641.95 | 0.00 | 0.00 | 0.00 |
November | 770.58 | 403.07 | 367.51 | 1002.33 | 862.55 | 0.00 | 0.00 | 0.00 |
December | 680.56 | 365.02 | 315.54 | 887.04 | 941.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1026.45 | 523.68 | 502.77 | 1405.71 | 725.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 668.95 | 337.39 | 315.54 | 858.59 | 512.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1389.23 | 743.37 | 666.59 | 2030.33 | 941.55 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209357E+09 | 0.00 | 0.209357E+09 | 0.108710E+09 | 0.877407E+09 |
February | 0.237367E+09 | 0.00 | 0.237367E+09 | 0.121471E+09 | 0.722883E+09 |
March | 0.322040E+09 | 0.00 | 0.322040E+09 | 0.204281E+09 | 0.812890E+09 |
April | 0.359060E+09 | 1381952.98 | 0.357678E+09 | 0.288481E+09 | 0.613979E+09 |
May | 0.445857E+09 | 20761368.39 | 0.425095E+09 | 0.392392E+09 | 0.538889E+09 |
June | 0.459758E+09 | 44948691.38 | 0.414809E+09 | 0.491665E+09 | 0.411105E+09 |
July | 0.449829E+09 | 37702800.77 | 0.412126E+09 | 0.534694E+09 | 0.371683E+09 |
August | 0.373568E+09 | 7480269.97 | 0.366088E+09 | 0.425333E+09 | 0.392146E+09 |
September | 0.305987E+09 | 47959.78 | 0.305939E+09 | 0.318928E+09 | 0.467010E+09 |
October | 0.250810E+09 | 0.00 | 0.250810E+09 | 0.278403E+09 | 0.549209E+09 |
November | 0.219765E+09 | 0.00 | 0.219765E+09 | 0.124313E+09 | 0.780923E+09 |
December | 0.194894E+09 | 0.00 | 0.194894E+09 | 90017300.93 | 0.903931E+09 |
Annual Sum or Average | 0.382829E+10 | 0.112323E+09 | 0.371597E+10 | 0.337869E+10 | 0.744206E+10 |
Minimum of Months | 0.194894E+09 | 0.00 | 0.194894E+09 | 90017300.93 | 0.371683E+09 |
Maximum of Months | 0.459758E+09 | 44948691.38 | 0.425095E+09 | 0.534694E+09 | 0.903931E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209354E+09 | 0.00 | 0.209354E+09 | 0.108708E+09 | 0.877405E+09 |
February | 0.237363E+09 | 0.00 | 0.237363E+09 | 0.121468E+09 | 0.722882E+09 |
March | 0.322035E+09 | 0.00 | 0.322035E+09 | 0.204275E+09 | 0.812889E+09 |
April | 0.359055E+09 | 1381922.60 | 0.357673E+09 | 0.288476E+09 | 0.613978E+09 |
May | 0.445851E+09 | 20760911.98 | 0.425090E+09 | 0.392384E+09 | 0.538888E+09 |
June | 0.459751E+09 | 44947703.23 | 0.414804E+09 | 0.491656E+09 | 0.411104E+09 |
July | 0.449823E+09 | 37701971.92 | 0.412122E+09 | 0.534687E+09 | 0.371682E+09 |
August | 0.373564E+09 | 7480105.53 | 0.366084E+09 | 0.425329E+09 | 0.392144E+09 |
September | 0.305984E+09 | 47958.73 | 0.305936E+09 | 0.318924E+09 | 0.467008E+09 |
October | 0.250807E+09 | 0.00 | 0.250807E+09 | 0.278400E+09 | 0.549207E+09 |
November | 0.219762E+09 | 0.00 | 0.219762E+09 | 0.124310E+09 | 0.780921E+09 |
December | 0.194891E+09 | 0.00 | 0.194891E+09 | 90015550.01 | 0.903928E+09 |
Annual Sum or Average | 0.382824E+10 | 0.112321E+09 | 0.371592E+10 | 0.337863E+10 | 0.744204E+10 |
Minimum of Months | 0.194891E+09 | 0.00 | 0.194891E+09 | 90015550.01 | 0.371682E+09 |
Maximum of Months | 0.459751E+09 | 44947703.23 | 0.425090E+09 | 0.534687E+09 | 0.903928E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209355E+09 | 0.00 | 0.209355E+09 | 0.108709E+09 | 0.877406E+09 |
February | 0.237365E+09 | 0.00 | 0.237365E+09 | 0.121469E+09 | 0.722882E+09 |
March | 0.322037E+09 | 0.00 | 0.322037E+09 | 0.204277E+09 | 0.812889E+09 |
April | 0.359057E+09 | 1381932.73 | 0.357675E+09 | 0.288478E+09 | 0.613978E+09 |
May | 0.445853E+09 | 20761064.12 | 0.425092E+09 | 0.392387E+09 | 0.538888E+09 |
June | 0.459754E+09 | 44948032.62 | 0.414806E+09 | 0.491659E+09 | 0.411104E+09 |
July | 0.449825E+09 | 37702248.20 | 0.412123E+09 | 0.534689E+09 | 0.371682E+09 |
August | 0.373565E+09 | 7480160.34 | 0.366085E+09 | 0.425330E+09 | 0.392145E+09 |
September | 0.305985E+09 | 47959.08 | 0.305937E+09 | 0.318925E+09 | 0.467009E+09 |
October | 0.250808E+09 | 0.00 | 0.250808E+09 | 0.278401E+09 | 0.549208E+09 |
November | 0.219763E+09 | 0.00 | 0.219763E+09 | 0.124311E+09 | 0.780922E+09 |
December | 0.194892E+09 | 0.00 | 0.194892E+09 | 90016133.65 | 0.903929E+09 |
Annual Sum or Average | 0.382826E+10 | 0.112321E+09 | 0.371594E+10 | 0.337865E+10 | 0.744204E+10 |
Minimum of Months | 0.194892E+09 | 0.00 | 0.194892E+09 | 90016133.65 | 0.371682E+09 |
Maximum of Months | 0.459754E+09 | 44948032.62 | 0.425092E+09 | 0.534689E+09 | 0.903929E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209354E+09 | 0.00 | 0.209354E+09 | 0.108708E+09 | 0.877405E+09 |
February | 0.237363E+09 | 0.00 | 0.237363E+09 | 0.121468E+09 | 0.722882E+09 |
March | 0.322035E+09 | 0.00 | 0.322035E+09 | 0.204275E+09 | 0.812889E+09 |
April | 0.359055E+09 | 1381922.60 | 0.357673E+09 | 0.288476E+09 | 0.613978E+09 |
May | 0.445851E+09 | 20760911.98 | 0.425090E+09 | 0.392384E+09 | 0.538888E+09 |
June | 0.459751E+09 | 44947703.23 | 0.414804E+09 | 0.491656E+09 | 0.411104E+09 |
July | 0.449823E+09 | 37701971.92 | 0.412122E+09 | 0.534687E+09 | 0.371682E+09 |
August | 0.373564E+09 | 7480105.53 | 0.366084E+09 | 0.425329E+09 | 0.392144E+09 |
September | 0.305984E+09 | 47958.73 | 0.305936E+09 | 0.318924E+09 | 0.467008E+09 |
October | 0.250807E+09 | 0.00 | 0.250807E+09 | 0.278400E+09 | 0.549207E+09 |
November | 0.219762E+09 | 0.00 | 0.219762E+09 | 0.124310E+09 | 0.780921E+09 |
December | 0.194891E+09 | 0.00 | 0.194891E+09 | 90015550.01 | 0.903928E+09 |
Annual Sum or Average | 0.382824E+10 | 0.112321E+09 | 0.371592E+10 | 0.337863E+10 | 0.744204E+10 |
Minimum of Months | 0.194891E+09 | 0.00 | 0.194891E+09 | 90015550.01 | 0.371682E+09 |
Maximum of Months | 0.459751E+09 | 44947703.23 | 0.425090E+09 | 0.534687E+09 | 0.903928E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209346E+09 | 0.00 | 0.209346E+09 | 0.108704E+09 | 0.877370E+09 |
February | 0.237354E+09 | 0.00 | 0.237354E+09 | 0.121464E+09 | 0.722853E+09 |
March | 0.322023E+09 | 0.00 | 0.322023E+09 | 0.204268E+09 | 0.812856E+09 |
April | 0.359042E+09 | 1381871.97 | 0.357660E+09 | 0.288465E+09 | 0.613953E+09 |
May | 0.445834E+09 | 20760151.29 | 0.425073E+09 | 0.392370E+09 | 0.538866E+09 |
June | 0.459734E+09 | 44946056.33 | 0.414788E+09 | 0.491638E+09 | 0.411088E+09 |
July | 0.449806E+09 | 37700590.50 | 0.412106E+09 | 0.534667E+09 | 0.371667E+09 |
August | 0.373550E+09 | 7479831.45 | 0.366070E+09 | 0.425312E+09 | 0.392129E+09 |
September | 0.305972E+09 | 47956.97 | 0.305924E+09 | 0.318912E+09 | 0.466990E+09 |
October | 0.250797E+09 | 0.00 | 0.250797E+09 | 0.278389E+09 | 0.549186E+09 |
November | 0.219753E+09 | 0.00 | 0.219753E+09 | 0.124305E+09 | 0.780890E+09 |
December | 0.194884E+09 | 0.00 | 0.194884E+09 | 90012213.80 | 0.903892E+09 |
Annual Sum or Average | 0.382810E+10 | 0.112316E+09 | 0.371578E+10 | 0.337851E+10 | 0.744174E+10 |
Minimum of Months | 0.194884E+09 | 0.00 | 0.194884E+09 | 90012213.80 | 0.371667E+09 |
Maximum of Months | 0.459734E+09 | 44946056.33 | 0.425073E+09 | 0.534667E+09 | 0.903892E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.627473E+09 | 0.335587E+09 | 0.291886E+09 | 0.730676E+09 | 0.905212E+09 |
February | 0.597862E+09 | 0.273886E+09 | 0.323977E+09 | 0.656470E+09 | 0.744368E+09 |
March | 0.804038E+09 | 0.358236E+09 | 0.445802E+09 | 0.929471E+09 | 0.831441E+09 |
April | 0.994793E+09 | 0.498909E+09 | 0.495884E+09 | 0.132606E+10 | 0.643148E+09 |
May | 0.970094E+09 | 0.404843E+09 | 0.565251E+09 | 0.124180E+10 | 0.607368E+09 |
June | 0.932955E+09 | 0.404793E+09 | 0.528162E+09 | 0.128404E+10 | 0.466965E+09 |
July | 0.109235E+10 | 0.542816E+09 | 0.549530E+09 | 0.162439E+10 | 0.421078E+09 |
August | 0.107878E+10 | 0.573012E+09 | 0.505768E+09 | 0.162532E+10 | 0.426647E+09 |
September | 0.760101E+09 | 0.348307E+09 | 0.411794E+09 | 0.107632E+10 | 0.503463E+09 |
October | 0.695256E+09 | 0.357344E+09 | 0.337912E+09 | 0.100101E+10 | 0.573768E+09 |
November | 0.613362E+09 | 0.311613E+09 | 0.301749E+09 | 0.719875E+09 | 0.796711E+09 |
December | 0.604640E+09 | 0.335945E+09 | 0.268696E+09 | 0.702559E+09 | 0.905433E+09 |
Annual Sum or Average | 0.977170E+10 | 0.474529E+10 | 0.502641E+10 | 0.129180E+11 | 0.782560E+10 |
Minimum of Months | 0.597862E+09 | 0.273886E+09 | 0.268696E+09 | 0.656470E+09 | 0.421078E+09 |
Maximum of Months | 0.109235E+10 | 0.573012E+09 | 0.565251E+09 | 0.162532E+10 | 0.905433E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.627473E+09 | 0.335587E+09 | 0.291886E+09 | 0.730676E+09 | 0.905212E+09 |
February | 0.597862E+09 | 0.273886E+09 | 0.323977E+09 | 0.656470E+09 | 0.744368E+09 |
March | 0.804038E+09 | 0.358236E+09 | 0.445802E+09 | 0.929471E+09 | 0.831441E+09 |
April | 0.994793E+09 | 0.498909E+09 | 0.495884E+09 | 0.132606E+10 | 0.643148E+09 |
May | 0.970094E+09 | 0.404843E+09 | 0.565251E+09 | 0.124180E+10 | 0.607368E+09 |
June | 0.932955E+09 | 0.404793E+09 | 0.528162E+09 | 0.128404E+10 | 0.466965E+09 |
July | 0.109235E+10 | 0.542816E+09 | 0.549530E+09 | 0.162439E+10 | 0.421078E+09 |
August | 0.107878E+10 | 0.573012E+09 | 0.505768E+09 | 0.162532E+10 | 0.426647E+09 |
September | 0.760101E+09 | 0.348307E+09 | 0.411794E+09 | 0.107632E+10 | 0.503463E+09 |
October | 0.695256E+09 | 0.357344E+09 | 0.337912E+09 | 0.100101E+10 | 0.573768E+09 |
November | 0.613362E+09 | 0.311613E+09 | 0.301749E+09 | 0.719875E+09 | 0.796711E+09 |
December | 0.604640E+09 | 0.335945E+09 | 0.268696E+09 | 0.702559E+09 | 0.905433E+09 |
Annual Sum or Average | 0.977170E+10 | 0.474529E+10 | 0.502641E+10 | 0.129180E+11 | 0.782560E+10 |
Minimum of Months | 0.597862E+09 | 0.273886E+09 | 0.268696E+09 | 0.656470E+09 | 0.421078E+09 |
Maximum of Months | 0.109235E+10 | 0.573012E+09 | 0.565251E+09 | 0.162532E+10 | 0.905433E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.627461E+09 | 0.335581E+09 | 0.291880E+09 | 0.730663E+09 | 0.905195E+09 |
February | 0.597852E+09 | 0.273881E+09 | 0.323971E+09 | 0.656458E+09 | 0.744355E+09 |
March | 0.804023E+09 | 0.358229E+09 | 0.445794E+09 | 0.929454E+09 | 0.831426E+09 |
April | 0.994775E+09 | 0.498900E+09 | 0.495875E+09 | 0.132603E+10 | 0.643136E+09 |
May | 0.970077E+09 | 0.404836E+09 | 0.565241E+09 | 0.124177E+10 | 0.607357E+09 |
June | 0.932938E+09 | 0.404785E+09 | 0.528152E+09 | 0.128402E+10 | 0.466957E+09 |
July | 0.109233E+10 | 0.542806E+09 | 0.549520E+09 | 0.162436E+10 | 0.421071E+09 |
August | 0.107876E+10 | 0.573001E+09 | 0.505759E+09 | 0.162529E+10 | 0.426639E+09 |
September | 0.760087E+09 | 0.348301E+09 | 0.411786E+09 | 0.107630E+10 | 0.503454E+09 |
October | 0.695243E+09 | 0.357337E+09 | 0.337906E+09 | 0.100099E+10 | 0.573757E+09 |
November | 0.613351E+09 | 0.311608E+09 | 0.301743E+09 | 0.719862E+09 | 0.796696E+09 |
December | 0.604629E+09 | 0.335938E+09 | 0.268691E+09 | 0.702546E+09 | 0.905417E+09 |
Annual Sum or Average | 0.977152E+10 | 0.474520E+10 | 0.502632E+10 | 0.129177E+11 | 0.782546E+10 |
Minimum of Months | 0.597852E+09 | 0.273881E+09 | 0.268691E+09 | 0.656458E+09 | 0.421071E+09 |
Maximum of Months | 0.109233E+10 | 0.573001E+09 | 0.565241E+09 | 0.162529E+10 | 0.905417E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138158E+10 | 0.101345E+10 | 0.368131E+09 | 0.200666E+10 | 0.817541E+09 |
February | 0.980770E+09 | 0.604101E+09 | 0.376669E+09 | 0.134035E+10 | 0.677653E+09 |
March | 0.865679E+09 | 0.418162E+09 | 0.447517E+09 | 0.116142E+10 | 0.783433E+09 |
April | 0.699966E+09 | 0.266902E+09 | 0.433064E+09 | 0.100511E+10 | 0.629660E+09 |
May | 0.515046E+09 | 63382741.22 | 0.451663E+09 | 0.600311E+09 | 0.576892E+09 |
June | 0.437258E+09 | 26399694.62 | 0.410858E+09 | 0.508857E+09 | 0.439626E+09 |
July | 0.478615E+09 | 53877696.07 | 0.424738E+09 | 0.652123E+09 | 0.397371E+09 |
August | 0.614875E+09 | 0.193949E+09 | 0.420926E+09 | 0.969593E+09 | 0.418062E+09 |
September | 0.827995E+09 | 0.419571E+09 | 0.408424E+09 | 0.131223E+10 | 0.479950E+09 |
October | 0.108811E+10 | 0.727433E+09 | 0.360682E+09 | 0.172381E+10 | 0.542602E+09 |
November | 0.127983E+10 | 0.903539E+09 | 0.376292E+09 | 0.185315E+10 | 0.733178E+09 |
December | 0.147597E+10 | 0.112341E+10 | 0.352567E+09 | 0.215138E+10 | 0.832550E+09 |
Annual Sum or Average | 0.106457E+11 | 0.581418E+10 | 0.483153E+10 | 0.152850E+11 | 0.732852E+10 |
Minimum of Months | 0.437258E+09 | 26399694.62 | 0.352567E+09 | 0.508857E+09 | 0.397371E+09 |
Maximum of Months | 0.147597E+10 | 0.112341E+10 | 0.451663E+09 | 0.215138E+10 | 0.832550E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138158E+10 | 0.101345E+10 | 0.368129E+09 | 0.200664E+10 | 0.817540E+09 |
February | 0.980763E+09 | 0.604097E+09 | 0.376667E+09 | 0.134033E+10 | 0.677652E+09 |
March | 0.865673E+09 | 0.418159E+09 | 0.447515E+09 | 0.116141E+10 | 0.783433E+09 |
April | 0.699962E+09 | 0.266900E+09 | 0.433063E+09 | 0.100510E+10 | 0.629660E+09 |
May | 0.515043E+09 | 63382276.75 | 0.451661E+09 | 0.600307E+09 | 0.576892E+09 |
June | 0.437256E+09 | 26399501.16 | 0.410856E+09 | 0.508854E+09 | 0.439626E+09 |
July | 0.478613E+09 | 53877301.25 | 0.424736E+09 | 0.652119E+09 | 0.397371E+09 |
August | 0.614872E+09 | 0.193947E+09 | 0.420924E+09 | 0.969588E+09 | 0.418062E+09 |
September | 0.827990E+09 | 0.419568E+09 | 0.408422E+09 | 0.131222E+10 | 0.479950E+09 |
October | 0.108811E+10 | 0.727427E+09 | 0.360680E+09 | 0.172380E+10 | 0.542601E+09 |
November | 0.127982E+10 | 0.903532E+09 | 0.376290E+09 | 0.185313E+10 | 0.733178E+09 |
December | 0.147596E+10 | 0.112340E+10 | 0.352566E+09 | 0.215137E+10 | 0.832549E+09 |
Annual Sum or Average | 0.106456E+11 | 0.581413E+10 | 0.483151E+10 | 0.152849E+11 | 0.732851E+10 |
Minimum of Months | 0.437256E+09 | 26399501.16 | 0.352566E+09 | 0.508854E+09 | 0.397371E+09 |
Maximum of Months | 0.147596E+10 | 0.112340E+10 | 0.451661E+09 | 0.215137E+10 | 0.832549E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138158E+10 | 0.101345E+10 | 0.368131E+09 | 0.200666E+10 | 0.817541E+09 |
February | 0.980770E+09 | 0.604101E+09 | 0.376669E+09 | 0.134035E+10 | 0.677653E+09 |
March | 0.865679E+09 | 0.418162E+09 | 0.447517E+09 | 0.116142E+10 | 0.783433E+09 |
April | 0.699966E+09 | 0.266902E+09 | 0.433064E+09 | 0.100511E+10 | 0.629660E+09 |
May | 0.515046E+09 | 63382741.22 | 0.451663E+09 | 0.600311E+09 | 0.576892E+09 |
June | 0.437258E+09 | 26399694.62 | 0.410858E+09 | 0.508857E+09 | 0.439626E+09 |
July | 0.478615E+09 | 53877696.07 | 0.424738E+09 | 0.652123E+09 | 0.397371E+09 |
August | 0.614875E+09 | 0.193949E+09 | 0.420926E+09 | 0.969593E+09 | 0.418062E+09 |
September | 0.827995E+09 | 0.419571E+09 | 0.408424E+09 | 0.131223E+10 | 0.479950E+09 |
October | 0.108811E+10 | 0.727433E+09 | 0.360682E+09 | 0.172381E+10 | 0.542602E+09 |
November | 0.127983E+10 | 0.903539E+09 | 0.376292E+09 | 0.185315E+10 | 0.733178E+09 |
December | 0.147597E+10 | 0.112341E+10 | 0.352567E+09 | 0.215138E+10 | 0.832550E+09 |
Annual Sum or Average | 0.106457E+11 | 0.581418E+10 | 0.483153E+10 | 0.152850E+11 | 0.732852E+10 |
Minimum of Months | 0.437258E+09 | 26399694.62 | 0.352567E+09 | 0.508857E+09 | 0.397371E+09 |
Maximum of Months | 0.147597E+10 | 0.112341E+10 | 0.451663E+09 | 0.215138E+10 | 0.832550E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138158E+10 | 0.101345E+10 | 0.368129E+09 | 0.200664E+10 | 0.817540E+09 |
February | 0.980763E+09 | 0.604097E+09 | 0.376667E+09 | 0.134033E+10 | 0.677652E+09 |
March | 0.865673E+09 | 0.418159E+09 | 0.447515E+09 | 0.116141E+10 | 0.783433E+09 |
April | 0.699962E+09 | 0.266900E+09 | 0.433063E+09 | 0.100510E+10 | 0.629660E+09 |
May | 0.515043E+09 | 63382276.75 | 0.451661E+09 | 0.600307E+09 | 0.576892E+09 |
June | 0.437256E+09 | 26399501.16 | 0.410856E+09 | 0.508854E+09 | 0.439626E+09 |
July | 0.478613E+09 | 53877301.25 | 0.424736E+09 | 0.652119E+09 | 0.397371E+09 |
August | 0.614872E+09 | 0.193947E+09 | 0.420924E+09 | 0.969588E+09 | 0.418062E+09 |
September | 0.827990E+09 | 0.419568E+09 | 0.408422E+09 | 0.131222E+10 | 0.479950E+09 |
October | 0.108811E+10 | 0.727427E+09 | 0.360680E+09 | 0.172380E+10 | 0.542601E+09 |
November | 0.127982E+10 | 0.903532E+09 | 0.376290E+09 | 0.185313E+10 | 0.733178E+09 |
December | 0.147596E+10 | 0.112340E+10 | 0.352566E+09 | 0.215137E+10 | 0.832549E+09 |
Annual Sum or Average | 0.106456E+11 | 0.581413E+10 | 0.483151E+10 | 0.152849E+11 | 0.732851E+10 |
Minimum of Months | 0.437256E+09 | 26399501.16 | 0.352566E+09 | 0.508854E+09 | 0.397371E+09 |
Maximum of Months | 0.147596E+10 | 0.112340E+10 | 0.451661E+09 | 0.215137E+10 | 0.832549E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138152E+10 | 0.101341E+10 | 0.368115E+09 | 0.200657E+10 | 0.817507E+09 |
February | 0.980727E+09 | 0.604074E+09 | 0.376653E+09 | 0.134029E+10 | 0.677625E+09 |
March | 0.865641E+09 | 0.418143E+09 | 0.447498E+09 | 0.116137E+10 | 0.783402E+09 |
April | 0.699936E+09 | 0.266890E+09 | 0.433046E+09 | 0.100506E+10 | 0.629634E+09 |
May | 0.515024E+09 | 63379954.39 | 0.451644E+09 | 0.600285E+09 | 0.576869E+09 |
June | 0.437239E+09 | 26398533.87 | 0.410841E+09 | 0.508835E+09 | 0.439609E+09 |
July | 0.478595E+09 | 53875327.16 | 0.424720E+09 | 0.652095E+09 | 0.397355E+09 |
August | 0.614849E+09 | 0.193940E+09 | 0.420908E+09 | 0.969551E+09 | 0.418045E+09 |
September | 0.827959E+09 | 0.419553E+09 | 0.408406E+09 | 0.131217E+10 | 0.479930E+09 |
October | 0.108807E+10 | 0.727401E+09 | 0.360666E+09 | 0.172374E+10 | 0.542580E+09 |
November | 0.127977E+10 | 0.903499E+09 | 0.376276E+09 | 0.185307E+10 | 0.733148E+09 |
December | 0.147591E+10 | 0.112336E+10 | 0.352552E+09 | 0.215129E+10 | 0.832516E+09 |
Annual Sum or Average | 0.106452E+11 | 0.581392E+10 | 0.483132E+10 | 0.152843E+11 | 0.732822E+10 |
Minimum of Months | 0.437239E+09 | 26398533.87 | 0.352552E+09 | 0.508835E+09 | 0.397355E+09 |
Maximum of Months | 0.147591E+10 | 0.112336E+10 | 0.451644E+09 | 0.215129E+10 | 0.832516E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.597244E+09 | 0.301223E+09 | 0.296021E+09 | 0.714620E+09 | 0.101964E+10 |
February | 0.643562E+09 | 0.297098E+09 | 0.346464E+09 | 0.731114E+09 | 0.871732E+09 |
March | 0.816733E+09 | 0.361335E+09 | 0.455397E+09 | 0.938862E+09 | 0.991883E+09 |
April | 0.108959E+10 | 0.567348E+09 | 0.522243E+09 | 0.144108E+10 | 0.794710E+09 |
May | 0.110600E+10 | 0.510859E+09 | 0.595139E+09 | 0.144425E+10 | 0.688261E+09 |
June | 0.113389E+10 | 0.566922E+09 | 0.566965E+09 | 0.156503E+10 | 0.546762E+09 |
July | 0.124032E+10 | 0.663685E+09 | 0.576636E+09 | 0.180399E+10 | 0.510663E+09 |
August | 0.116366E+10 | 0.630657E+09 | 0.533006E+09 | 0.171018E+10 | 0.542811E+09 |
September | 0.964171E+09 | 0.515914E+09 | 0.448257E+09 | 0.138483E+10 | 0.572616E+09 |
October | 0.761634E+09 | 0.415819E+09 | 0.345814E+09 | 0.110204E+10 | 0.682853E+09 |
November | 0.665790E+09 | 0.348255E+09 | 0.317535E+09 | 0.811259E+09 | 0.953868E+09 |
December | 0.607608E+09 | 0.325892E+09 | 0.281715E+09 | 0.721926E+09 | 0.111686E+10 |
Annual Sum or Average | 0.107902E+11 | 0.550501E+10 | 0.528519E+10 | 0.143692E+11 | 0.929266E+10 |
Minimum of Months | 0.597244E+09 | 0.297098E+09 | 0.281715E+09 | 0.714620E+09 | 0.510663E+09 |
Maximum of Months | 0.124032E+10 | 0.663685E+09 | 0.595139E+09 | 0.180399E+10 | 0.111686E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.597244E+09 | 0.301223E+09 | 0.296021E+09 | 0.714620E+09 | 0.101964E+10 |
February | 0.643562E+09 | 0.297098E+09 | 0.346464E+09 | 0.731114E+09 | 0.871732E+09 |
March | 0.816733E+09 | 0.361335E+09 | 0.455397E+09 | 0.938862E+09 | 0.991883E+09 |
April | 0.108959E+10 | 0.567348E+09 | 0.522243E+09 | 0.144108E+10 | 0.794710E+09 |
May | 0.110600E+10 | 0.510859E+09 | 0.595139E+09 | 0.144425E+10 | 0.688261E+09 |
June | 0.113389E+10 | 0.566922E+09 | 0.566965E+09 | 0.156503E+10 | 0.546762E+09 |
July | 0.124032E+10 | 0.663685E+09 | 0.576636E+09 | 0.180399E+10 | 0.510663E+09 |
August | 0.116366E+10 | 0.630657E+09 | 0.533006E+09 | 0.171018E+10 | 0.542811E+09 |
September | 0.964171E+09 | 0.515914E+09 | 0.448257E+09 | 0.138483E+10 | 0.572616E+09 |
October | 0.761634E+09 | 0.415819E+09 | 0.345814E+09 | 0.110204E+10 | 0.682853E+09 |
November | 0.665790E+09 | 0.348255E+09 | 0.317535E+09 | 0.811259E+09 | 0.953868E+09 |
December | 0.607608E+09 | 0.325892E+09 | 0.281715E+09 | 0.721926E+09 | 0.111686E+10 |
Annual Sum or Average | 0.107902E+11 | 0.550501E+10 | 0.528519E+10 | 0.143692E+11 | 0.929266E+10 |
Minimum of Months | 0.597244E+09 | 0.297098E+09 | 0.281715E+09 | 0.714620E+09 | 0.510663E+09 |
Maximum of Months | 0.124032E+10 | 0.663685E+09 | 0.595139E+09 | 0.180399E+10 | 0.111686E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.597233E+09 | 0.301218E+09 | 0.296016E+09 | 0.714607E+09 | 0.101963E+10 |
February | 0.643550E+09 | 0.297093E+09 | 0.346457E+09 | 0.731101E+09 | 0.871716E+09 |
March | 0.816718E+09 | 0.361329E+09 | 0.455389E+09 | 0.938844E+09 | 0.991865E+09 |
April | 0.108957E+10 | 0.567338E+09 | 0.522233E+09 | 0.144105E+10 | 0.794695E+09 |
May | 0.110598E+10 | 0.510849E+09 | 0.595129E+09 | 0.144422E+10 | 0.688249E+09 |
June | 0.113387E+10 | 0.566912E+09 | 0.566955E+09 | 0.156500E+10 | 0.546753E+09 |
July | 0.124030E+10 | 0.663673E+09 | 0.576625E+09 | 0.180396E+10 | 0.510653E+09 |
August | 0.116364E+10 | 0.630646E+09 | 0.532996E+09 | 0.171015E+10 | 0.542802E+09 |
September | 0.964154E+09 | 0.515905E+09 | 0.448249E+09 | 0.138481E+10 | 0.572605E+09 |
October | 0.761620E+09 | 0.415812E+09 | 0.345808E+09 | 0.110202E+10 | 0.682840E+09 |
November | 0.665778E+09 | 0.348249E+09 | 0.317529E+09 | 0.811244E+09 | 0.953851E+09 |
December | 0.607596E+09 | 0.325886E+09 | 0.281710E+09 | 0.721913E+09 | 0.111684E+10 |
Annual Sum or Average | 0.107900E+11 | 0.550491E+10 | 0.528510E+10 | 0.143689E+11 | 0.929249E+10 |
Minimum of Months | 0.597233E+09 | 0.297093E+09 | 0.281710E+09 | 0.714607E+09 | 0.510653E+09 |
Maximum of Months | 0.124030E+10 | 0.663673E+09 | 0.595129E+09 | 0.180396E+10 | 0.111684E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104678E+10 | 0.00 | 0.104678E+10 | 0.683375E+09 | 0.388299E+10 |
February | 0.118683E+10 | 0.00 | 0.118683E+10 | 0.738312E+09 | 0.317959E+10 |
March | 0.161020E+10 | 0.00 | 0.161020E+10 | 0.117728E+10 | 0.360918E+10 |
April | 0.179529E+10 | 6909808.95 | 0.178838E+10 | 0.156921E+10 | 0.278336E+10 |
May | 0.222928E+10 | 0.103808E+09 | 0.212547E+10 | 0.205146E+10 | 0.253044E+10 |
June | 0.229879E+10 | 0.224745E+09 | 0.207404E+10 | 0.251048E+10 | 0.193732E+10 |
July | 0.224914E+10 | 0.188515E+09 | 0.206063E+10 | 0.273257E+10 | 0.178395E+10 |
August | 0.186784E+10 | 37401588.21 | 0.183043E+10 | 0.219617E+10 | 0.186598E+10 |
September | 0.152993E+10 | 239800.43 | 0.152969E+10 | 0.165133E+10 | 0.217134E+10 |
October | 0.125405E+10 | 0.00 | 0.125405E+10 | 0.147820E+10 | 0.251021E+10 |
November | 0.109882E+10 | 0.00 | 0.109882E+10 | 0.757868E+09 | 0.345535E+10 |
December | 0.974467E+09 | 0.00 | 0.974467E+09 | 0.619513E+09 | 0.391943E+10 |
Annual Sum or Average | 0.191414E+11 | 0.561619E+09 | 0.185798E+11 | 0.181658E+11 | 0.336291E+11 |
Minimum of Months | 0.974467E+09 | 0.00 | 0.974467E+09 | 0.619513E+09 | 0.178395E+10 |
Maximum of Months | 0.229879E+10 | 0.224745E+09 | 0.212547E+10 | 0.273257E+10 | 0.391943E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188240E+10 | 0.100675E+10 | 0.875648E+09 | 0.225822E+10 | 0.249561E+10 |
February | 0.179357E+10 | 0.821648E+09 | 0.971921E+09 | 0.201860E+10 | 0.205262E+10 |
March | 0.241209E+10 | 0.107470E+10 | 0.133739E+10 | 0.283363E+10 | 0.232876E+10 |
April | 0.298435E+10 | 0.149671E+10 | 0.148764E+10 | 0.397664E+10 | 0.186298E+10 |
May | 0.291025E+10 | 0.121452E+10 | 0.169574E+10 | 0.372454E+10 | 0.175475E+10 |
June | 0.279884E+10 | 0.121437E+10 | 0.158447E+10 | 0.383747E+10 | 0.136233E+10 |
July | 0.327700E+10 | 0.162843E+10 | 0.164857E+10 | 0.483941E+10 | 0.127515E+10 |
August | 0.323631E+10 | 0.171902E+10 | 0.151729E+10 | 0.484135E+10 | 0.130310E+10 |
September | 0.228028E+10 | 0.104491E+10 | 0.123537E+10 | 0.322814E+10 | 0.145097E+10 |
October | 0.208575E+10 | 0.107202E+10 | 0.101373E+10 | 0.300981E+10 | 0.164732E+10 |
November | 0.184007E+10 | 0.934830E+09 | 0.905237E+09 | 0.220230E+10 | 0.223112E+10 |
December | 0.181390E+10 | 0.100782E+10 | 0.806080E+09 | 0.217521E+10 | 0.250527E+10 |
Annual Sum or Average | 0.293148E+11 | 0.142357E+11 | 0.150791E+11 | 0.389453E+11 | 0.222700E+11 |
Minimum of Months | 0.179357E+10 | 0.821648E+09 | 0.806080E+09 | 0.201860E+10 | 0.127515E+10 |
Maximum of Months | 0.327700E+10 | 0.171902E+10 | 0.169574E+10 | 0.484135E+10 | 0.250527E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.690805E+10 | 0.506738E+10 | 0.184068E+10 | 0.999589E+10 | 0.400746E+10 |
February | 0.490394E+10 | 0.302057E+10 | 0.188337E+10 | 0.667116E+10 | 0.326571E+10 |
March | 0.432847E+10 | 0.209085E+10 | 0.223761E+10 | 0.581007E+10 | 0.374530E+10 |
April | 0.349988E+10 | 0.133454E+10 | 0.216534E+10 | 0.503157E+10 | 0.301826E+10 |
May | 0.257525E+10 | 0.316920E+09 | 0.225833E+10 | 0.301075E+10 | 0.278713E+10 |
June | 0.218631E+10 | 0.132001E+09 | 0.205430E+10 | 0.256826E+10 | 0.210440E+10 |
July | 0.239309E+10 | 0.269394E+09 | 0.212370E+10 | 0.328905E+10 | 0.192945E+10 |
August | 0.307441E+10 | 0.969765E+09 | 0.210464E+10 | 0.485382E+10 | 0.204974E+10 |
September | 0.414004E+10 | 0.209790E+10 | 0.204214E+10 | 0.652277E+10 | 0.235507E+10 |
October | 0.544067E+10 | 0.363724E+10 | 0.180343E+10 | 0.857184E+10 | 0.266446E+10 |
November | 0.639927E+10 | 0.451779E+10 | 0.188148E+10 | 0.922307E+10 | 0.356338E+10 |
December | 0.738001E+10 | 0.561715E+10 | 0.176286E+10 | 0.107253E+11 | 0.403004E+10 |
Annual Sum or Average | 0.532294E+11 | 0.290715E+11 | 0.241579E+11 | 0.762735E+11 | 0.355204E+11 |
Minimum of Months | 0.218631E+10 | 0.132001E+09 | 0.176286E+10 | 0.256826E+10 | 0.192945E+10 |
Maximum of Months | 0.738001E+10 | 0.561715E+10 | 0.225833E+10 | 0.107253E+11 | 0.403004E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179171E+10 | 0.903660E+09 | 0.888054E+09 | 0.223504E+10 | 0.270236E+10 |
February | 0.193067E+10 | 0.891285E+09 | 0.103938E+10 | 0.228947E+10 | 0.222964E+10 |
March | 0.245017E+10 | 0.108400E+10 | 0.136618E+10 | 0.294353E+10 | 0.251998E+10 |
April | 0.326874E+10 | 0.170203E+10 | 0.156671E+10 | 0.442689E+10 | 0.206239E+10 |
May | 0.331796E+10 | 0.153256E+10 | 0.178540E+10 | 0.436258E+10 | 0.191480E+10 |
June | 0.340163E+10 | 0.170075E+10 | 0.170088E+10 | 0.473417E+10 | 0.147593E+10 |
July | 0.372092E+10 | 0.199103E+10 | 0.172989E+10 | 0.547171E+10 | 0.138997E+10 |
August | 0.349095E+10 | 0.189195E+10 | 0.159900E+10 | 0.520650E+10 | 0.144258E+10 |
September | 0.289248E+10 | 0.154773E+10 | 0.134476E+10 | 0.417289E+10 | 0.158205E+10 |
October | 0.228488E+10 | 0.124745E+10 | 0.103743E+10 | 0.337358E+10 | 0.180906E+10 |
November | 0.199735E+10 | 0.104475E+10 | 0.952595E+09 | 0.254348E+10 | 0.242066E+10 |
December | 0.182280E+10 | 0.977667E+09 | 0.845137E+09 | 0.231018E+10 | 0.275458E+10 |
Annual Sum or Average | 0.323703E+11 | 0.165149E+11 | 0.158554E+11 | 0.440700E+11 | 0.243040E+11 |
Minimum of Months | 0.179171E+10 | 0.891285E+09 | 0.845137E+09 | 0.223504E+10 | 0.138997E+10 |
Maximum of Months | 0.372092E+10 | 0.199103E+10 | 0.178540E+10 | 0.547171E+10 | 0.275458E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104678E+10 | 0.00 | 0.104678E+10 | 0.809282E+09 | 0.347099E+10 |
February | 0.118683E+10 | 0.00 | 0.118683E+10 | 0.852311E+09 | 0.283432E+10 |
March | 0.161020E+10 | 0.00 | 0.161020E+10 | 0.129531E+10 | 0.329718E+10 |
April | 0.179529E+10 | 6909808.95 | 0.178838E+10 | 0.163265E+10 | 0.261298E+10 |
May | 0.222928E+10 | 0.103808E+09 | 0.212547E+10 | 0.212620E+10 | 0.239302E+10 |
June | 0.229879E+10 | 0.224745E+09 | 0.207404E+10 | 0.251614E+10 | 0.187201E+10 |
July | 0.224914E+10 | 0.188515E+09 | 0.206063E+10 | 0.270419E+10 | 0.175312E+10 |
August | 0.186784E+10 | 37401588.21 | 0.183043E+10 | 0.218117E+10 | 0.182528E+10 |
September | 0.152993E+10 | 239800.43 | 0.152969E+10 | 0.167490E+10 | 0.206512E+10 |
October | 0.125405E+10 | 0.00 | 0.125405E+10 | 0.153265E+10 | 0.234495E+10 |
November | 0.109882E+10 | 0.00 | 0.109882E+10 | 0.872589E+09 | 0.310853E+10 |
December | 0.974467E+09 | 0.00 | 0.974467E+09 | 0.746914E+09 | 0.349252E+10 |
Annual Sum or Average | 0.191414E+11 | 0.561619E+09 | 0.185798E+11 | 0.189443E+11 | 0.310700E+11 |
Minimum of Months | 0.974467E+09 | 0.00 | 0.974467E+09 | 0.746914E+09 | 0.175312E+10 |
Maximum of Months | 0.229879E+10 | 0.224745E+09 | 0.212547E+10 | 0.270419E+10 | 0.349252E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188240E+10 | 0.100675E+10 | 0.875648E+09 | 0.236393E+10 | 0.226211E+10 |
February | 0.179357E+10 | 0.821648E+09 | 0.971921E+09 | 0.209756E+10 | 0.186028E+10 |
March | 0.241209E+10 | 0.107470E+10 | 0.133739E+10 | 0.291179E+10 | 0.215942E+10 |
April | 0.298435E+10 | 0.149671E+10 | 0.148764E+10 | 0.400479E+10 | 0.178090E+10 |
May | 0.291025E+10 | 0.121452E+10 | 0.169574E+10 | 0.375655E+10 | 0.168031E+10 |
June | 0.279884E+10 | 0.121437E+10 | 0.158447E+10 | 0.383281E+10 | 0.133058E+10 |
July | 0.327700E+10 | 0.162843E+10 | 0.164857E+10 | 0.481188E+10 | 0.126721E+10 |
August | 0.323631E+10 | 0.171902E+10 | 0.151729E+10 | 0.481867E+10 | 0.129049E+10 |
September | 0.228028E+10 | 0.104491E+10 | 0.123537E+10 | 0.323232E+10 | 0.139880E+10 |
October | 0.208575E+10 | 0.107202E+10 | 0.101373E+10 | 0.303761E+10 | 0.156514E+10 |
November | 0.184007E+10 | 0.934830E+09 | 0.905237E+09 | 0.228693E+10 | 0.204573E+10 |
December | 0.181390E+10 | 0.100782E+10 | 0.806080E+09 | 0.228384E+10 | 0.226935E+10 |
Annual Sum or Average | 0.293148E+11 | 0.142357E+11 | 0.150791E+11 | 0.394387E+11 | 0.209103E+11 |
Minimum of Months | 0.179357E+10 | 0.821648E+09 | 0.806080E+09 | 0.209756E+10 | 0.126721E+10 |
Maximum of Months | 0.327700E+10 | 0.171902E+10 | 0.169574E+10 | 0.481867E+10 | 0.226935E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.690805E+10 | 0.506738E+10 | 0.184068E+10 | 0.101078E+11 | 0.369590E+10 |
February | 0.490394E+10 | 0.302057E+10 | 0.188337E+10 | 0.676695E+10 | 0.298141E+10 |
March | 0.432847E+10 | 0.209085E+10 | 0.223761E+10 | 0.590758E+10 | 0.346855E+10 |
April | 0.349988E+10 | 0.133454E+10 | 0.216534E+10 | 0.506695E+10 | 0.286824E+10 |
May | 0.257525E+10 | 0.316920E+09 | 0.225833E+10 | 0.305993E+10 | 0.263919E+10 |
June | 0.218631E+10 | 0.132001E+09 | 0.205430E+10 | 0.257141E+10 | 0.203628E+10 |
July | 0.239309E+10 | 0.269394E+09 | 0.212370E+10 | 0.326136E+10 | 0.190342E+10 |
August | 0.307441E+10 | 0.969765E+09 | 0.210464E+10 | 0.482489E+10 | 0.201803E+10 |
September | 0.414004E+10 | 0.209790E+10 | 0.204214E+10 | 0.651604E+10 | 0.227309E+10 |
October | 0.544067E+10 | 0.363724E+10 | 0.180343E+10 | 0.859274E+10 | 0.254873E+10 |
November | 0.639927E+10 | 0.451779E+10 | 0.188148E+10 | 0.930292E+10 | 0.332080E+10 |
December | 0.738001E+10 | 0.561715E+10 | 0.176286E+10 | 0.108333E+11 | 0.373160E+10 |
Annual Sum or Average | 0.532294E+11 | 0.290715E+11 | 0.241579E+11 | 0.768119E+11 | 0.334852E+11 |
Minimum of Months | 0.218631E+10 | 0.132001E+09 | 0.176286E+10 | 0.257141E+10 | 0.190342E+10 |
Maximum of Months | 0.738001E+10 | 0.561715E+10 | 0.225833E+10 | 0.108333E+11 | 0.373160E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179171E+10 | 0.903660E+09 | 0.888054E+09 | 0.229964E+10 | 0.247653E+10 |
February | 0.193067E+10 | 0.891285E+09 | 0.103938E+10 | 0.234686E+10 | 0.204057E+10 |
March | 0.245017E+10 | 0.108400E+10 | 0.136618E+10 | 0.299958E+10 | 0.234343E+10 |
April | 0.326874E+10 | 0.170203E+10 | 0.156671E+10 | 0.444150E+10 | 0.196826E+10 |
May | 0.331796E+10 | 0.153256E+10 | 0.178540E+10 | 0.437744E+10 | 0.182894E+10 |
June | 0.340163E+10 | 0.170075E+10 | 0.170088E+10 | 0.471808E+10 | 0.143482E+10 |
July | 0.372092E+10 | 0.199103E+10 | 0.172989E+10 | 0.543804E+10 | 0.137192E+10 |
August | 0.349095E+10 | 0.189195E+10 | 0.159900E+10 | 0.517776E+10 | 0.142063E+10 |
September | 0.289248E+10 | 0.154773E+10 | 0.134476E+10 | 0.416681E+10 | 0.152651E+10 |
October | 0.228488E+10 | 0.124745E+10 | 0.103743E+10 | 0.339091E+10 | 0.171940E+10 |
November | 0.199735E+10 | 0.104475E+10 | 0.952595E+09 | 0.259804E+10 | 0.223574E+10 |
December | 0.182280E+10 | 0.977667E+09 | 0.845137E+09 | 0.237585E+10 | 0.252184E+10 |
Annual Sum or Average | 0.323703E+11 | 0.165149E+11 | 0.158554E+11 | 0.443305E+11 | 0.228886E+11 |
Minimum of Months | 0.179171E+10 | 0.891285E+09 | 0.845137E+09 | 0.229964E+10 | 0.137192E+10 |
Maximum of Months | 0.372092E+10 | 0.199103E+10 | 0.178540E+10 | 0.543804E+10 | 0.252184E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 202.93 | 1637.92 | 390.82 | 0.00 | 390.82 | 0.00 | 0.00 |
February | 251.05 | 1494.04 | 490.58 | 0.00 | 490.58 | 0.00 | 0.00 |
March | 381.34 | 1517.48 | 601.17 | 0.00 | 601.17 | 0.00 | 0.00 |
April | 556.47 | 1184.36 | 692.62 | 2.67 | 689.95 | 0.00 | 0.00 |
May | 732.50 | 1005.98 | 832.30 | 38.76 | 793.55 | 0.00 | 0.00 |
June | 948.41 | 793.02 | 886.86 | 86.70 | 800.16 | 0.00 | 0.00 |
July | 998.14 | 693.85 | 839.72 | 70.38 | 769.34 | 0.00 | 0.00 |
August | 793.99 | 732.04 | 697.36 | 13.96 | 683.40 | 0.00 | 0.00 |
September | 615.21 | 900.86 | 590.24 | 0.09 | 590.15 | 0.00 | 0.00 |
October | 519.71 | 1025.25 | 468.20 | 0.00 | 468.20 | 0.00 | 0.00 |
November | 239.80 | 1506.40 | 423.92 | 0.00 | 423.92 | 0.00 | 0.00 |
December | 168.04 | 1687.43 | 363.82 | 0.00 | 363.82 | 0.00 | 0.00 |
Annual Sum or Average | 535.68 | 1179.92 | 606.96 | 17.81 | 589.15 | 0.00 | 0.00 |
Minimum of Months | 168.04 | 693.85 | 363.82 | 0.00 | 363.82 | 0.00 | 0.00 |
Maximum of Months | 998.14 | 1687.43 | 886.86 | 86.70 | 800.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 818.40 | 1013.90 | 702.81 | 375.88 | 326.93 | 0.00 | 0.00 |
February | 814.07 | 923.07 | 741.39 | 339.64 | 401.75 | 0.00 | 0.00 |
March | 1041.07 | 931.27 | 900.57 | 401.25 | 499.33 | 0.00 | 0.00 |
April | 1534.78 | 744.38 | 1151.37 | 577.44 | 573.94 | 0.00 | 0.00 |
May | 1390.89 | 680.29 | 1086.57 | 453.45 | 633.12 | 0.00 | 0.00 |
June | 1486.15 | 540.47 | 1079.80 | 468.51 | 611.29 | 0.00 | 0.00 |
July | 1819.42 | 471.64 | 1223.50 | 607.99 | 615.51 | 0.00 | 0.00 |
August | 1820.47 | 477.87 | 1208.30 | 641.81 | 566.49 | 0.00 | 0.00 |
September | 1245.73 | 582.71 | 879.74 | 403.13 | 476.61 | 0.00 | 0.00 |
October | 1121.19 | 642.66 | 778.73 | 400.25 | 378.48 | 0.00 | 0.00 |
November | 833.18 | 922.11 | 709.91 | 360.66 | 349.24 | 0.00 | 0.00 |
December | 786.91 | 1014.14 | 677.24 | 376.28 | 300.96 | 0.00 | 0.00 |
Annual Sum or Average | 1228.87 | 744.44 | 929.57 | 451.41 | 478.16 | 0.00 | 0.00 |
Minimum of Months | 786.91 | 471.64 | 677.24 | 339.64 | 300.96 | 0.00 | 0.00 |
Maximum of Months | 1820.47 | 1014.14 | 1223.50 | 641.81 | 633.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3745.95 | 1526.16 | 2579.09 | 1891.88 | 687.21 | 0.00 | 0.00 |
February | 2770.19 | 1400.56 | 2027.03 | 1248.54 | 778.49 | 0.00 | 0.00 |
March | 2168.10 | 1462.49 | 1616.02 | 780.61 | 835.41 | 0.00 | 0.00 |
April | 1938.84 | 1214.61 | 1350.23 | 514.85 | 835.38 | 0.00 | 0.00 |
May | 1120.64 | 1076.93 | 961.47 | 118.32 | 843.15 | 0.00 | 0.00 |
June | 981.58 | 848.04 | 843.47 | 50.92 | 792.54 | 0.00 | 0.00 |
July | 1217.36 | 741.80 | 893.46 | 100.58 | 792.89 | 0.00 | 0.00 |
August | 1810.00 | 780.43 | 1147.83 | 362.06 | 785.77 | 0.00 | 0.00 |
September | 2531.28 | 925.82 | 1597.19 | 809.35 | 787.85 | 0.00 | 0.00 |
October | 3217.95 | 1012.91 | 2031.25 | 1357.95 | 673.31 | 0.00 | 0.00 |
November | 3574.70 | 1414.30 | 2468.78 | 1742.92 | 725.86 | 0.00 | 0.00 |
December | 4016.13 | 1554.18 | 2755.30 | 2097.14 | 658.16 | 0.00 | 0.00 |
Annual Sum or Average | 2423.39 | 1161.92 | 1687.85 | 921.82 | 766.03 | 0.00 | 0.00 |
Minimum of Months | 981.58 | 741.80 | 843.47 | 50.92 | 658.16 | 0.00 | 0.00 |
Maximum of Months | 4016.13 | 1554.18 | 2755.30 | 2097.14 | 843.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 800.42 | 1142.07 | 668.95 | 337.39 | 331.56 | 0.00 | 0.00 |
February | 906.63 | 1081.01 | 798.06 | 368.42 | 429.64 | 0.00 | 0.00 |
March | 1051.59 | 1110.97 | 914.79 | 404.72 | 510.07 | 0.00 | 0.00 |
April | 1667.90 | 919.80 | 1261.09 | 656.65 | 604.44 | 0.00 | 0.00 |
May | 1617.65 | 770.90 | 1238.79 | 572.19 | 666.59 | 0.00 | 0.00 |
June | 1811.36 | 632.82 | 1312.36 | 656.16 | 656.21 | 0.00 | 0.00 |
July | 2020.59 | 571.98 | 1389.24 | 743.37 | 645.87 | 0.00 | 0.00 |
August | 1915.51 | 607.98 | 1303.38 | 706.38 | 597.00 | 0.00 | 0.00 |
September | 1602.81 | 662.75 | 1115.93 | 597.12 | 518.81 | 0.00 | 0.00 |
October | 1234.36 | 764.84 | 853.08 | 465.74 | 387.33 | 0.00 | 0.00 |
November | 938.95 | 1104.01 | 770.59 | 403.07 | 367.52 | 0.00 | 0.00 |
December | 808.60 | 1250.95 | 680.56 | 365.02 | 315.54 | 0.00 | 0.00 |
Annual Sum or Average | 1366.92 | 884.00 | 1026.46 | 523.68 | 502.77 | 0.00 | 0.00 |
Minimum of Months | 800.42 | 571.98 | 668.95 | 337.39 | 315.54 | 0.00 | 0.00 |
Maximum of Months | 2020.59 | 1250.95 | 1389.24 | 743.37 | 666.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 255.14 | 1449.74 | 390.82 | 0.00 | 390.82 | 0.00 | 0.00 |
February | 305.19 | 1314.32 | 490.59 | 0.00 | 490.59 | 0.00 | 0.00 |
March | 439.54 | 1347.51 | 601.18 | 0.00 | 601.18 | 0.00 | 0.00 |
April | 605.41 | 1073.83 | 692.63 | 2.67 | 689.96 | 0.00 | 0.00 |
May | 765.93 | 944.76 | 832.32 | 38.76 | 793.56 | 0.00 | 0.00 |
June | 968.55 | 747.42 | 886.88 | 86.71 | 800.17 | 0.00 | 0.00 |
July | 1020.23 | 666.05 | 839.73 | 70.38 | 769.35 | 0.00 | 0.00 |
August | 819.95 | 696.68 | 697.37 | 13.96 | 683.41 | 0.00 | 0.00 |
September | 637.09 | 837.71 | 590.25 | 0.09 | 590.16 | 0.00 | 0.00 |
October | 551.90 | 937.20 | 468.21 | 0.00 | 468.21 | 0.00 | 0.00 |
November | 292.39 | 1333.08 | 423.93 | 0.00 | 423.93 | 0.00 | 0.00 |
December | 231.30 | 1463.35 | 363.82 | 0.00 | 363.82 | 0.00 | 0.00 |
Annual Sum or Average | 576.03 | 1066.37 | 606.97 | 17.81 | 589.16 | 0.00 | 0.00 |
Minimum of Months | 231.30 | 666.05 | 363.82 | 0.00 | 363.82 | 0.00 | 0.00 |
Maximum of Months | 1020.23 | 1463.35 | 886.88 | 86.71 | 800.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 843.12 | 931.75 | 702.81 | 375.88 | 326.93 | 0.00 | 0.00 |
February | 834.41 | 848.47 | 741.39 | 339.64 | 401.75 | 0.00 | 0.00 |
March | 1057.96 | 869.46 | 900.57 | 401.25 | 499.33 | 0.00 | 0.00 |
April | 1534.20 | 718.74 | 1151.37 | 577.43 | 573.93 | 0.00 | 0.00 |
May | 1390.58 | 655.15 | 1086.56 | 453.45 | 633.12 | 0.00 | 0.00 |
June | 1480.51 | 525.59 | 1079.80 | 468.51 | 611.29 | 0.00 | 0.00 |
July | 1806.83 | 476.09 | 1223.49 | 607.99 | 615.51 | 0.00 | 0.00 |
August | 1807.55 | 486.52 | 1208.30 | 641.81 | 566.49 | 0.00 | 0.00 |
September | 1245.42 | 559.79 | 879.74 | 403.13 | 476.61 | 0.00 | 0.00 |
October | 1123.73 | 615.04 | 778.73 | 400.25 | 378.48 | 0.00 | 0.00 |
November | 849.65 | 860.77 | 709.90 | 360.66 | 349.24 | 0.00 | 0.00 |
December | 812.13 | 935.36 | 677.23 | 376.28 | 300.96 | 0.00 | 0.00 |
Annual Sum or Average | 1234.95 | 706.18 | 929.57 | 451.41 | 478.15 | 0.00 | 0.00 |
Minimum of Months | 812.13 | 476.09 | 677.23 | 339.64 | 300.96 | 0.00 | 0.00 |
Maximum of Months | 1807.55 | 935.36 | 1223.49 | 641.81 | 633.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3732.04 | 1496.21 | 2579.17 | 1891.94 | 687.23 | 0.00 | 0.00 |
February | 2757.59 | 1349.91 | 2027.09 | 1248.58 | 778.51 | 0.00 | 0.00 |
March | 2169.23 | 1398.34 | 1616.06 | 780.64 | 835.43 | 0.00 | 0.00 |
April | 1941.19 | 1164.45 | 1350.26 | 514.87 | 835.39 | 0.00 | 0.00 |
May | 1124.08 | 1040.60 | 961.49 | 118.32 | 843.17 | 0.00 | 0.00 |
June | 990.84 | 811.88 | 843.48 | 50.93 | 792.56 | 0.00 | 0.00 |
July | 1227.99 | 720.37 | 893.48 | 100.58 | 792.90 | 0.00 | 0.00 |
August | 1812.21 | 765.28 | 1147.85 | 362.07 | 785.78 | 0.00 | 0.00 |
September | 2516.50 | 908.59 | 1597.24 | 809.38 | 787.86 | 0.00 | 0.00 |
October | 3200.36 | 994.80 | 2031.31 | 1357.99 | 673.32 | 0.00 | 0.00 |
November | 3558.28 | 1374.76 | 2468.85 | 1742.97 | 725.88 | 0.00 | 0.00 |
December | 4004.37 | 1504.64 | 2755.38 | 2097.20 | 658.18 | 0.00 | 0.00 |
Annual Sum or Average | 2418.62 | 1126.34 | 1687.89 | 921.85 | 766.04 | 0.00 | 0.00 |
Minimum of Months | 990.84 | 720.37 | 843.48 | 50.93 | 658.18 | 0.00 | 0.00 |
Maximum of Months | 4004.37 | 1504.64 | 2755.38 | 2097.20 | 843.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 834.47 | 1008.95 | 668.95 | 337.39 | 331.56 | 0.00 | 0.00 |
February | 946.37 | 921.64 | 798.06 | 368.42 | 429.64 | 0.00 | 0.00 |
March | 1098.99 | 940.85 | 914.79 | 404.72 | 510.07 | 0.00 | 0.00 |
April | 1707.91 | 795.67 | 1261.09 | 656.65 | 604.44 | 0.00 | 0.00 |
May | 1628.80 | 714.91 | 1238.78 | 572.19 | 666.59 | 0.00 | 0.00 |
June | 1826.45 | 569.42 | 1312.36 | 656.15 | 656.20 | 0.00 | 0.00 |
July | 2042.90 | 518.95 | 1389.23 | 743.37 | 645.87 | 0.00 | 0.00 |
August | 1943.88 | 538.60 | 1303.37 | 706.37 | 597.00 | 0.00 | 0.00 |
September | 1609.91 | 610.36 | 1115.93 | 597.12 | 518.81 | 0.00 | 0.00 |
October | 1259.55 | 675.42 | 853.08 | 465.74 | 387.33 | 0.00 | 0.00 |
November | 981.28 | 933.90 | 770.58 | 403.07 | 367.51 | 0.00 | 0.00 |
December | 862.52 | 1028.44 | 680.56 | 365.02 | 315.54 | 0.00 | 0.00 |
Annual Sum or Average | 1397.45 | 770.67 | 1026.45 | 523.68 | 502.77 | 0.00 | 0.00 |
Minimum of Months | 834.47 | 518.95 | 668.95 | 337.39 | 315.54 | 0.00 | 0.00 |
Maximum of Months | 2042.90 | 1028.44 | 1389.23 | 743.37 | 666.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 302.15 | 1295.92 | 390.82 | 0.00 | 390.82 | 0.00 | 0.00 |
February | 352.31 | 1171.59 | 490.59 | 0.00 | 490.59 | 0.00 | 0.00 |
March | 483.61 | 1231.03 | 601.18 | 0.00 | 601.18 | 0.00 | 0.00 |
April | 629.88 | 1008.09 | 692.63 | 2.67 | 689.96 | 0.00 | 0.00 |
May | 793.83 | 893.45 | 832.32 | 38.76 | 793.56 | 0.00 | 0.00 |
June | 970.73 | 722.23 | 886.88 | 86.71 | 800.17 | 0.00 | 0.00 |
July | 1009.63 | 654.54 | 839.73 | 70.38 | 769.35 | 0.00 | 0.00 |
August | 814.36 | 681.48 | 697.37 | 13.96 | 683.41 | 0.00 | 0.00 |
September | 646.18 | 796.73 | 590.25 | 0.09 | 590.16 | 0.00 | 0.00 |
October | 572.23 | 875.51 | 468.21 | 0.00 | 468.21 | 0.00 | 0.00 |
November | 336.65 | 1199.28 | 423.93 | 0.00 | 423.93 | 0.00 | 0.00 |
December | 278.87 | 1303.96 | 363.82 | 0.00 | 363.82 | 0.00 | 0.00 |
Annual Sum or Average | 600.72 | 985.22 | 606.97 | 17.81 | 589.16 | 0.00 | 0.00 |
Minimum of Months | 278.87 | 654.54 | 363.82 | 0.00 | 363.82 | 0.00 | 0.00 |
Maximum of Months | 1009.63 | 1303.96 | 886.88 | 86.71 | 800.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 882.59 | 844.58 | 702.81 | 375.88 | 326.93 | 0.00 | 0.00 |
February | 867.05 | 768.97 | 741.39 | 339.64 | 401.75 | 0.00 | 0.00 |
March | 1087.14 | 806.24 | 900.57 | 401.25 | 499.33 | 0.00 | 0.00 |
April | 1545.06 | 687.08 | 1151.37 | 577.43 | 573.93 | 0.00 | 0.00 |
May | 1402.53 | 627.36 | 1086.56 | 453.45 | 633.12 | 0.00 | 0.00 |
June | 1478.71 | 513.34 | 1079.80 | 468.51 | 611.29 | 0.00 | 0.00 |
July | 1796.55 | 473.12 | 1223.49 | 607.99 | 615.51 | 0.00 | 0.00 |
August | 1799.09 | 481.82 | 1208.30 | 641.81 | 566.49 | 0.00 | 0.00 |
September | 1247.04 | 539.66 | 879.74 | 403.13 | 476.61 | 0.00 | 0.00 |
October | 1134.12 | 584.36 | 778.73 | 400.25 | 378.48 | 0.00 | 0.00 |
November | 882.30 | 789.25 | 709.90 | 360.66 | 349.24 | 0.00 | 0.00 |
December | 852.69 | 847.28 | 677.23 | 376.28 | 300.96 | 0.00 | 0.00 |
Annual Sum or Average | 1250.59 | 663.06 | 929.57 | 451.41 | 478.15 | 0.00 | 0.00 |
Minimum of Months | 852.69 | 473.12 | 677.23 | 339.64 | 300.96 | 0.00 | 0.00 |
Maximum of Months | 1799.09 | 847.28 | 1223.49 | 641.81 | 633.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3773.82 | 1379.89 | 2579.17 | 1891.94 | 687.23 | 0.00 | 0.00 |
February | 2797.18 | 1232.39 | 2027.09 | 1248.58 | 778.51 | 0.00 | 0.00 |
March | 2205.64 | 1295.01 | 1616.06 | 780.64 | 835.43 | 0.00 | 0.00 |
April | 1954.84 | 1106.57 | 1350.26 | 514.87 | 835.39 | 0.00 | 0.00 |
May | 1142.45 | 985.36 | 961.49 | 118.32 | 843.17 | 0.00 | 0.00 |
June | 992.06 | 785.60 | 843.48 | 50.93 | 792.56 | 0.00 | 0.00 |
July | 1217.65 | 710.65 | 893.48 | 100.58 | 792.90 | 0.00 | 0.00 |
August | 1801.41 | 753.45 | 1147.85 | 362.07 | 785.78 | 0.00 | 0.00 |
September | 2513.91 | 876.96 | 1597.24 | 809.38 | 787.86 | 0.00 | 0.00 |
October | 3208.16 | 951.59 | 2031.31 | 1357.99 | 673.32 | 0.00 | 0.00 |
November | 3589.09 | 1281.17 | 2468.85 | 1742.97 | 725.88 | 0.00 | 0.00 |
December | 4044.70 | 1393.22 | 2755.38 | 2097.20 | 658.18 | 0.00 | 0.00 |
Annual Sum or Average | 2435.69 | 1061.81 | 1687.89 | 921.85 | 766.04 | 0.00 | 0.00 |
Minimum of Months | 992.06 | 710.65 | 843.48 | 50.93 | 658.18 | 0.00 | 0.00 |
Maximum of Months | 4044.70 | 1393.22 | 2755.38 | 2097.20 | 843.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 858.59 | 924.63 | 668.95 | 337.39 | 331.56 | 0.00 | 0.00 |
February | 970.10 | 843.49 | 798.06 | 368.42 | 429.64 | 0.00 | 0.00 |
March | 1119.91 | 874.94 | 914.79 | 404.72 | 510.07 | 0.00 | 0.00 |
April | 1713.54 | 759.36 | 1261.09 | 656.65 | 604.44 | 0.00 | 0.00 |
May | 1634.35 | 682.85 | 1238.78 | 572.19 | 666.59 | 0.00 | 0.00 |
June | 1820.25 | 553.56 | 1312.36 | 656.15 | 656.20 | 0.00 | 0.00 |
July | 2030.33 | 512.22 | 1389.23 | 743.37 | 645.87 | 0.00 | 0.00 |
August | 1933.16 | 530.40 | 1303.37 | 706.37 | 597.00 | 0.00 | 0.00 |
September | 1607.57 | 588.93 | 1115.93 | 597.12 | 518.81 | 0.00 | 0.00 |
October | 1266.02 | 641.95 | 853.08 | 465.74 | 387.33 | 0.00 | 0.00 |
November | 1002.33 | 862.55 | 770.58 | 403.07 | 367.51 | 0.00 | 0.00 |
December | 887.04 | 941.55 | 680.56 | 365.02 | 315.54 | 0.00 | 0.00 |
Annual Sum or Average | 1405.71 | 725.79 | 1026.45 | 523.68 | 502.77 | 0.00 | 0.00 |
Minimum of Months | 858.59 | 512.22 | 668.95 | 337.39 | 315.54 | 0.00 | 0.00 |
Maximum of Months | 2030.33 | 941.55 | 1389.23 | 743.37 | 666.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.543539E+09 | 0.438699E+10 | 0.104677E+10 | 0.00 | 0.104677E+10 | 0.00 | 0.00 |
February | 0.607340E+09 | 0.361438E+10 | 0.118681E+10 | 0.00 | 0.118681E+10 | 0.00 | 0.00 |
March | 0.102138E+10 | 0.406441E+10 | 0.161017E+10 | 0.00 | 0.161017E+10 | 0.00 | 0.00 |
April | 0.144238E+10 | 0.306987E+10 | 0.179527E+10 | 6909602.89 | 0.178836E+10 | 0.00 | 0.00 |
May | 0.196192E+10 | 0.269442E+10 | 0.222924E+10 | 0.103804E+09 | 0.212544E+10 | 0.00 | 0.00 |
June | 0.245827E+10 | 0.205551E+10 | 0.229875E+10 | 0.224738E+09 | 0.207401E+10 | 0.00 | 0.00 |
July | 0.267342E+10 | 0.185840E+10 | 0.224911E+10 | 0.188510E+09 | 0.206060E+10 | 0.00 | 0.00 |
August | 0.212663E+10 | 0.196071E+10 | 0.186781E+10 | 37400472.82 | 0.183041E+10 | 0.00 | 0.00 |
September | 0.159461E+10 | 0.233503E+10 | 0.152991E+10 | 239793.28 | 0.152967E+10 | 0.00 | 0.00 |
October | 0.139199E+10 | 0.274602E+10 | 0.125403E+10 | 0.00 | 0.125403E+10 | 0.00 | 0.00 |
November | 0.621549E+09 | 0.390458E+10 | 0.109880E+10 | 0.00 | 0.109880E+10 | 0.00 | 0.00 |
December | 0.450077E+09 | 0.451961E+10 | 0.974451E+09 | 0.00 | 0.974451E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.168931E+11 | 0.372099E+11 | 0.191411E+11 | 0.561602E+09 | 0.185795E+11 | 0.00 | 0.00 |
Minimum of Months | 0.450077E+09 | 0.185840E+10 | 0.974451E+09 | 0.00 | 0.974451E+09 | 0.00 | 0.00 |
Maximum of Months | 0.267342E+10 | 0.451961E+10 | 0.229875E+10 | 0.224738E+09 | 0.212544E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.219201E+10 | 0.271562E+10 | 0.188241E+10 | 0.100676E+10 | 0.875651E+09 | 0.00 | 0.00 |
February | 0.196940E+10 | 0.223309E+10 | 0.179358E+10 | 0.821652E+09 | 0.971925E+09 | 0.00 | 0.00 |
March | 0.278840E+10 | 0.249431E+10 | 0.241210E+10 | 0.107470E+10 | 0.133740E+10 | 0.00 | 0.00 |
April | 0.397814E+10 | 0.192943E+10 | 0.298436E+10 | 0.149672E+10 | 0.148764E+10 | 0.00 | 0.00 |
May | 0.372537E+10 | 0.182209E+10 | 0.291027E+10 | 0.121452E+10 | 0.169574E+10 | 0.00 | 0.00 |
June | 0.385210E+10 | 0.140089E+10 | 0.279885E+10 | 0.121437E+10 | 0.158448E+10 | 0.00 | 0.00 |
July | 0.487314E+10 | 0.126323E+10 | 0.327702E+10 | 0.162844E+10 | 0.164858E+10 | 0.00 | 0.00 |
August | 0.487594E+10 | 0.127993E+10 | 0.323632E+10 | 0.171902E+10 | 0.151730E+10 | 0.00 | 0.00 |
September | 0.322893E+10 | 0.151038E+10 | 0.228029E+10 | 0.104491E+10 | 0.123537E+10 | 0.00 | 0.00 |
October | 0.300300E+10 | 0.172129E+10 | 0.208575E+10 | 0.107202E+10 | 0.101373E+10 | 0.00 | 0.00 |
November | 0.215961E+10 | 0.239012E+10 | 0.184007E+10 | 0.934834E+09 | 0.905241E+09 | 0.00 | 0.00 |
December | 0.210766E+10 | 0.271628E+10 | 0.181391E+10 | 0.100783E+10 | 0.806083E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.387537E+11 | 0.234767E+11 | 0.293149E+11 | 0.142358E+11 | 0.150791E+11 | 0.00 | 0.00 |
Minimum of Months | 0.196940E+10 | 0.126323E+10 | 0.179358E+10 | 0.821652E+09 | 0.806083E+09 | 0.00 | 0.00 |
Maximum of Months | 0.487594E+10 | 0.271628E+10 | 0.327702E+10 | 0.171902E+10 | 0.169574E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100332E+11 | 0.408767E+10 | 0.690784E+10 | 0.506721E+10 | 0.184063E+10 | 0.00 | 0.00 |
February | 0.670165E+10 | 0.338824E+10 | 0.490379E+10 | 0.302047E+10 | 0.188332E+10 | 0.00 | 0.00 |
March | 0.580704E+10 | 0.391713E+10 | 0.432835E+10 | 0.209078E+10 | 0.223756E+10 | 0.00 | 0.00 |
April | 0.502548E+10 | 0.314827E+10 | 0.349979E+10 | 0.133449E+10 | 0.216530E+10 | 0.00 | 0.00 |
May | 0.300152E+10 | 0.288444E+10 | 0.257520E+10 | 0.316910E+09 | 0.225829E+10 | 0.00 | 0.00 |
June | 0.254426E+10 | 0.219811E+10 | 0.218627E+10 | 0.131997E+09 | 0.205427E+10 | 0.00 | 0.00 |
July | 0.326058E+10 | 0.198684E+10 | 0.239305E+10 | 0.269385E+09 | 0.212367E+10 | 0.00 | 0.00 |
August | 0.484791E+10 | 0.209029E+10 | 0.307434E+10 | 0.969733E+09 | 0.210461E+10 | 0.00 | 0.00 |
September | 0.656107E+10 | 0.239973E+10 | 0.413993E+10 | 0.209783E+10 | 0.204210E+10 | 0.00 | 0.00 |
October | 0.861897E+10 | 0.271299E+10 | 0.544051E+10 | 0.363712E+10 | 0.180339E+10 | 0.00 | 0.00 |
November | 0.926563E+10 | 0.366586E+10 | 0.639908E+10 | 0.451764E+10 | 0.188144E+10 | 0.00 | 0.00 |
December | 0.107568E+11 | 0.416272E+10 | 0.737979E+10 | 0.561697E+10 | 0.176282E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.764241E+11 | 0.366423E+11 | 0.532279E+11 | 0.290705E+11 | 0.241574E+11 | 0.00 | 0.00 |
Minimum of Months | 0.254426E+10 | 0.198684E+10 | 0.218627E+10 | 0.131997E+09 | 0.176282E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107568E+11 | 0.416272E+10 | 0.737979E+10 | 0.561697E+10 | 0.225829E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.214385E+10 | 0.305891E+10 | 0.179172E+10 | 0.903664E+09 | 0.888058E+09 | 0.00 | 0.00 |
February | 0.219333E+10 | 0.261518E+10 | 0.193067E+10 | 0.891289E+09 | 0.103938E+10 | 0.00 | 0.00 |
March | 0.281657E+10 | 0.297563E+10 | 0.245018E+10 | 0.108400E+10 | 0.136618E+10 | 0.00 | 0.00 |
April | 0.432321E+10 | 0.238411E+10 | 0.326875E+10 | 0.170204E+10 | 0.156672E+10 | 0.00 | 0.00 |
May | 0.433271E+10 | 0.206477E+10 | 0.331797E+10 | 0.153257E+10 | 0.178541E+10 | 0.00 | 0.00 |
June | 0.469505E+10 | 0.164028E+10 | 0.340164E+10 | 0.170076E+10 | 0.170089E+10 | 0.00 | 0.00 |
July | 0.541195E+10 | 0.153198E+10 | 0.372094E+10 | 0.199104E+10 | 0.172990E+10 | 0.00 | 0.00 |
August | 0.513051E+10 | 0.162842E+10 | 0.349097E+10 | 0.189196E+10 | 0.159901E+10 | 0.00 | 0.00 |
September | 0.415448E+10 | 0.171784E+10 | 0.289250E+10 | 0.154773E+10 | 0.134476E+10 | 0.00 | 0.00 |
October | 0.330611E+10 | 0.204855E+10 | 0.228489E+10 | 0.124745E+10 | 0.103744E+10 | 0.00 | 0.00 |
November | 0.243376E+10 | 0.286159E+10 | 0.199736E+10 | 0.104476E+10 | 0.952599E+09 | 0.00 | 0.00 |
December | 0.216577E+10 | 0.335055E+10 | 0.182281E+10 | 0.977671E+09 | 0.845141E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.431073E+11 | 0.278778E+11 | 0.323704E+11 | 0.165149E+11 | 0.158555E+11 | 0.00 | 0.00 |
Minimum of Months | 0.214385E+10 | 0.153198E+10 | 0.179172E+10 | 0.891289E+09 | 0.845141E+09 | 0.00 | 0.00 |
Maximum of Months | 0.541195E+10 | 0.335055E+10 | 0.372094E+10 | 0.199104E+10 | 0.178541E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.683375E+09 | 0.388299E+10 | 0.104678E+10 | 0.00 | 0.104678E+10 | 0.00 | 0.00 |
February | 0.738312E+09 | 0.317959E+10 | 0.118683E+10 | 0.00 | 0.118683E+10 | 0.00 | 0.00 |
March | 0.117728E+10 | 0.360918E+10 | 0.161020E+10 | 0.00 | 0.161020E+10 | 0.00 | 0.00 |
April | 0.156921E+10 | 0.278336E+10 | 0.179529E+10 | 6909808.95 | 0.178838E+10 | 0.00 | 0.00 |
May | 0.205146E+10 | 0.253044E+10 | 0.222928E+10 | 0.103808E+09 | 0.212547E+10 | 0.00 | 0.00 |
June | 0.251048E+10 | 0.193732E+10 | 0.229879E+10 | 0.224745E+09 | 0.207404E+10 | 0.00 | 0.00 |
July | 0.273257E+10 | 0.178395E+10 | 0.224914E+10 | 0.188515E+09 | 0.206063E+10 | 0.00 | 0.00 |
August | 0.219617E+10 | 0.186598E+10 | 0.186784E+10 | 37401588.21 | 0.183043E+10 | 0.00 | 0.00 |
September | 0.165133E+10 | 0.217134E+10 | 0.152993E+10 | 239800.43 | 0.152969E+10 | 0.00 | 0.00 |
October | 0.147820E+10 | 0.251021E+10 | 0.125405E+10 | 0.00 | 0.125405E+10 | 0.00 | 0.00 |
November | 0.757868E+09 | 0.345535E+10 | 0.109882E+10 | 0.00 | 0.109882E+10 | 0.00 | 0.00 |
December | 0.619513E+09 | 0.391943E+10 | 0.974467E+09 | 0.00 | 0.974467E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.181658E+11 | 0.336291E+11 | 0.191414E+11 | 0.561619E+09 | 0.185798E+11 | 0.00 | 0.00 |
Minimum of Months | 0.619513E+09 | 0.178395E+10 | 0.974467E+09 | 0.00 | 0.974467E+09 | 0.00 | 0.00 |
Maximum of Months | 0.273257E+10 | 0.391943E+10 | 0.229879E+10 | 0.224745E+09 | 0.212547E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.225822E+10 | 0.249561E+10 | 0.188240E+10 | 0.100675E+10 | 0.875648E+09 | 0.00 | 0.00 |
February | 0.201860E+10 | 0.205262E+10 | 0.179357E+10 | 0.821648E+09 | 0.971921E+09 | 0.00 | 0.00 |
March | 0.283363E+10 | 0.232876E+10 | 0.241209E+10 | 0.107470E+10 | 0.133739E+10 | 0.00 | 0.00 |
April | 0.397664E+10 | 0.186298E+10 | 0.298435E+10 | 0.149671E+10 | 0.148764E+10 | 0.00 | 0.00 |
May | 0.372454E+10 | 0.175475E+10 | 0.291025E+10 | 0.121452E+10 | 0.169574E+10 | 0.00 | 0.00 |
June | 0.383747E+10 | 0.136233E+10 | 0.279884E+10 | 0.121437E+10 | 0.158447E+10 | 0.00 | 0.00 |
July | 0.483941E+10 | 0.127515E+10 | 0.327700E+10 | 0.162843E+10 | 0.164857E+10 | 0.00 | 0.00 |
August | 0.484135E+10 | 0.130310E+10 | 0.323631E+10 | 0.171902E+10 | 0.151729E+10 | 0.00 | 0.00 |
September | 0.322814E+10 | 0.145097E+10 | 0.228028E+10 | 0.104491E+10 | 0.123537E+10 | 0.00 | 0.00 |
October | 0.300981E+10 | 0.164732E+10 | 0.208575E+10 | 0.107202E+10 | 0.101373E+10 | 0.00 | 0.00 |
November | 0.220230E+10 | 0.223112E+10 | 0.184007E+10 | 0.934830E+09 | 0.905237E+09 | 0.00 | 0.00 |
December | 0.217521E+10 | 0.250527E+10 | 0.181390E+10 | 0.100782E+10 | 0.806080E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.389453E+11 | 0.222700E+11 | 0.293148E+11 | 0.142357E+11 | 0.150791E+11 | 0.00 | 0.00 |
Minimum of Months | 0.201860E+10 | 0.127515E+10 | 0.179357E+10 | 0.821648E+09 | 0.806080E+09 | 0.00 | 0.00 |
Maximum of Months | 0.484135E+10 | 0.250527E+10 | 0.327700E+10 | 0.171902E+10 | 0.169574E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.999589E+10 | 0.400746E+10 | 0.690805E+10 | 0.506738E+10 | 0.184068E+10 | 0.00 | 0.00 |
February | 0.667116E+10 | 0.326571E+10 | 0.490394E+10 | 0.302057E+10 | 0.188337E+10 | 0.00 | 0.00 |
March | 0.581007E+10 | 0.374530E+10 | 0.432847E+10 | 0.209085E+10 | 0.223761E+10 | 0.00 | 0.00 |
April | 0.503157E+10 | 0.301826E+10 | 0.349988E+10 | 0.133454E+10 | 0.216534E+10 | 0.00 | 0.00 |
May | 0.301075E+10 | 0.278713E+10 | 0.257525E+10 | 0.316920E+09 | 0.225833E+10 | 0.00 | 0.00 |
June | 0.256826E+10 | 0.210440E+10 | 0.218631E+10 | 0.132001E+09 | 0.205430E+10 | 0.00 | 0.00 |
July | 0.328905E+10 | 0.192945E+10 | 0.239309E+10 | 0.269394E+09 | 0.212370E+10 | 0.00 | 0.00 |
August | 0.485382E+10 | 0.204974E+10 | 0.307441E+10 | 0.969765E+09 | 0.210464E+10 | 0.00 | 0.00 |
September | 0.652277E+10 | 0.235507E+10 | 0.414004E+10 | 0.209790E+10 | 0.204214E+10 | 0.00 | 0.00 |
October | 0.857184E+10 | 0.266446E+10 | 0.544067E+10 | 0.363724E+10 | 0.180343E+10 | 0.00 | 0.00 |
November | 0.922307E+10 | 0.356338E+10 | 0.639927E+10 | 0.451779E+10 | 0.188148E+10 | 0.00 | 0.00 |
December | 0.107253E+11 | 0.403004E+10 | 0.738001E+10 | 0.561715E+10 | 0.176286E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.762735E+11 | 0.355204E+11 | 0.532294E+11 | 0.290715E+11 | 0.241579E+11 | 0.00 | 0.00 |
Minimum of Months | 0.256826E+10 | 0.192945E+10 | 0.218631E+10 | 0.132001E+09 | 0.176286E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107253E+11 | 0.403004E+10 | 0.738001E+10 | 0.561715E+10 | 0.225833E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.223504E+10 | 0.270236E+10 | 0.179171E+10 | 0.903660E+09 | 0.888054E+09 | 0.00 | 0.00 |
February | 0.228947E+10 | 0.222964E+10 | 0.193067E+10 | 0.891285E+09 | 0.103938E+10 | 0.00 | 0.00 |
March | 0.294353E+10 | 0.251998E+10 | 0.245017E+10 | 0.108400E+10 | 0.136618E+10 | 0.00 | 0.00 |
April | 0.442689E+10 | 0.206239E+10 | 0.326874E+10 | 0.170203E+10 | 0.156671E+10 | 0.00 | 0.00 |
May | 0.436258E+10 | 0.191480E+10 | 0.331796E+10 | 0.153256E+10 | 0.178540E+10 | 0.00 | 0.00 |
June | 0.473417E+10 | 0.147593E+10 | 0.340163E+10 | 0.170075E+10 | 0.170088E+10 | 0.00 | 0.00 |
July | 0.547171E+10 | 0.138997E+10 | 0.372092E+10 | 0.199103E+10 | 0.172989E+10 | 0.00 | 0.00 |
August | 0.520650E+10 | 0.144258E+10 | 0.349095E+10 | 0.189195E+10 | 0.159900E+10 | 0.00 | 0.00 |
September | 0.417289E+10 | 0.158205E+10 | 0.289248E+10 | 0.154773E+10 | 0.134476E+10 | 0.00 | 0.00 |
October | 0.337358E+10 | 0.180906E+10 | 0.228488E+10 | 0.124745E+10 | 0.103743E+10 | 0.00 | 0.00 |
November | 0.254348E+10 | 0.242066E+10 | 0.199735E+10 | 0.104475E+10 | 0.952595E+09 | 0.00 | 0.00 |
December | 0.231018E+10 | 0.275458E+10 | 0.182280E+10 | 0.977667E+09 | 0.845137E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.440700E+11 | 0.243040E+11 | 0.323703E+11 | 0.165149E+11 | 0.158554E+11 | 0.00 | 0.00 |
Minimum of Months | 0.223504E+10 | 0.138997E+10 | 0.179171E+10 | 0.891285E+09 | 0.845137E+09 | 0.00 | 0.00 |
Maximum of Months | 0.547171E+10 | 0.275458E+10 | 0.372092E+10 | 0.199103E+10 | 0.178540E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.809282E+09 | 0.347099E+10 | 0.104678E+10 | 0.00 | 0.104678E+10 | 0.00 | 0.00 |
February | 0.852311E+09 | 0.283432E+10 | 0.118683E+10 | 0.00 | 0.118683E+10 | 0.00 | 0.00 |
March | 0.129531E+10 | 0.329718E+10 | 0.161020E+10 | 0.00 | 0.161020E+10 | 0.00 | 0.00 |
April | 0.163265E+10 | 0.261298E+10 | 0.179529E+10 | 6909808.95 | 0.178838E+10 | 0.00 | 0.00 |
May | 0.212620E+10 | 0.239302E+10 | 0.222928E+10 | 0.103808E+09 | 0.212547E+10 | 0.00 | 0.00 |
June | 0.251614E+10 | 0.187201E+10 | 0.229879E+10 | 0.224745E+09 | 0.207404E+10 | 0.00 | 0.00 |
July | 0.270419E+10 | 0.175312E+10 | 0.224914E+10 | 0.188515E+09 | 0.206063E+10 | 0.00 | 0.00 |
August | 0.218117E+10 | 0.182528E+10 | 0.186784E+10 | 37401588.21 | 0.183043E+10 | 0.00 | 0.00 |
September | 0.167490E+10 | 0.206512E+10 | 0.152993E+10 | 239800.43 | 0.152969E+10 | 0.00 | 0.00 |
October | 0.153265E+10 | 0.234495E+10 | 0.125405E+10 | 0.00 | 0.125405E+10 | 0.00 | 0.00 |
November | 0.872589E+09 | 0.310853E+10 | 0.109882E+10 | 0.00 | 0.109882E+10 | 0.00 | 0.00 |
December | 0.746914E+09 | 0.349252E+10 | 0.974467E+09 | 0.00 | 0.974467E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.189443E+11 | 0.310700E+11 | 0.191414E+11 | 0.561619E+09 | 0.185798E+11 | 0.00 | 0.00 |
Minimum of Months | 0.746914E+09 | 0.175312E+10 | 0.974467E+09 | 0.00 | 0.974467E+09 | 0.00 | 0.00 |
Maximum of Months | 0.270419E+10 | 0.349252E+10 | 0.229879E+10 | 0.224745E+09 | 0.212547E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.236393E+10 | 0.226211E+10 | 0.188240E+10 | 0.100675E+10 | 0.875648E+09 | 0.00 | 0.00 |
February | 0.209756E+10 | 0.186028E+10 | 0.179357E+10 | 0.821648E+09 | 0.971921E+09 | 0.00 | 0.00 |
March | 0.291179E+10 | 0.215942E+10 | 0.241209E+10 | 0.107470E+10 | 0.133739E+10 | 0.00 | 0.00 |
April | 0.400479E+10 | 0.178090E+10 | 0.298435E+10 | 0.149671E+10 | 0.148764E+10 | 0.00 | 0.00 |
May | 0.375655E+10 | 0.168031E+10 | 0.291025E+10 | 0.121452E+10 | 0.169574E+10 | 0.00 | 0.00 |
June | 0.383281E+10 | 0.133058E+10 | 0.279884E+10 | 0.121437E+10 | 0.158447E+10 | 0.00 | 0.00 |
July | 0.481188E+10 | 0.126721E+10 | 0.327700E+10 | 0.162843E+10 | 0.164857E+10 | 0.00 | 0.00 |
August | 0.481867E+10 | 0.129049E+10 | 0.323631E+10 | 0.171902E+10 | 0.151729E+10 | 0.00 | 0.00 |
September | 0.323232E+10 | 0.139880E+10 | 0.228028E+10 | 0.104491E+10 | 0.123537E+10 | 0.00 | 0.00 |
October | 0.303761E+10 | 0.156514E+10 | 0.208575E+10 | 0.107202E+10 | 0.101373E+10 | 0.00 | 0.00 |
November | 0.228693E+10 | 0.204573E+10 | 0.184007E+10 | 0.934830E+09 | 0.905237E+09 | 0.00 | 0.00 |
December | 0.228384E+10 | 0.226935E+10 | 0.181390E+10 | 0.100782E+10 | 0.806080E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.394387E+11 | 0.209103E+11 | 0.293148E+11 | 0.142357E+11 | 0.150791E+11 | 0.00 | 0.00 |
Minimum of Months | 0.209756E+10 | 0.126721E+10 | 0.179357E+10 | 0.821648E+09 | 0.806080E+09 | 0.00 | 0.00 |
Maximum of Months | 0.481867E+10 | 0.226935E+10 | 0.327700E+10 | 0.171902E+10 | 0.169574E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101078E+11 | 0.369590E+10 | 0.690805E+10 | 0.506738E+10 | 0.184068E+10 | 0.00 | 0.00 |
February | 0.676695E+10 | 0.298141E+10 | 0.490394E+10 | 0.302057E+10 | 0.188337E+10 | 0.00 | 0.00 |
March | 0.590758E+10 | 0.346855E+10 | 0.432847E+10 | 0.209085E+10 | 0.223761E+10 | 0.00 | 0.00 |
April | 0.506695E+10 | 0.286824E+10 | 0.349988E+10 | 0.133454E+10 | 0.216534E+10 | 0.00 | 0.00 |
May | 0.305993E+10 | 0.263919E+10 | 0.257525E+10 | 0.316920E+09 | 0.225833E+10 | 0.00 | 0.00 |
June | 0.257141E+10 | 0.203628E+10 | 0.218631E+10 | 0.132001E+09 | 0.205430E+10 | 0.00 | 0.00 |
July | 0.326136E+10 | 0.190342E+10 | 0.239309E+10 | 0.269394E+09 | 0.212370E+10 | 0.00 | 0.00 |
August | 0.482489E+10 | 0.201803E+10 | 0.307441E+10 | 0.969765E+09 | 0.210464E+10 | 0.00 | 0.00 |
September | 0.651604E+10 | 0.227309E+10 | 0.414004E+10 | 0.209790E+10 | 0.204214E+10 | 0.00 | 0.00 |
October | 0.859274E+10 | 0.254873E+10 | 0.544067E+10 | 0.363724E+10 | 0.180343E+10 | 0.00 | 0.00 |
November | 0.930292E+10 | 0.332080E+10 | 0.639927E+10 | 0.451779E+10 | 0.188148E+10 | 0.00 | 0.00 |
December | 0.108333E+11 | 0.373160E+10 | 0.738001E+10 | 0.561715E+10 | 0.176286E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.768119E+11 | 0.334852E+11 | 0.532294E+11 | 0.290715E+11 | 0.241579E+11 | 0.00 | 0.00 |
Minimum of Months | 0.257141E+10 | 0.190342E+10 | 0.218631E+10 | 0.132001E+09 | 0.176286E+10 | 0.00 | 0.00 |
Maximum of Months | 0.108333E+11 | 0.373160E+10 | 0.738001E+10 | 0.561715E+10 | 0.225833E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.229964E+10 | 0.247653E+10 | 0.179171E+10 | 0.903660E+09 | 0.888054E+09 | 0.00 | 0.00 |
February | 0.234686E+10 | 0.204057E+10 | 0.193067E+10 | 0.891285E+09 | 0.103938E+10 | 0.00 | 0.00 |
March | 0.299958E+10 | 0.234343E+10 | 0.245017E+10 | 0.108400E+10 | 0.136618E+10 | 0.00 | 0.00 |
April | 0.444150E+10 | 0.196826E+10 | 0.326874E+10 | 0.170203E+10 | 0.156671E+10 | 0.00 | 0.00 |
May | 0.437744E+10 | 0.182894E+10 | 0.331796E+10 | 0.153256E+10 | 0.178540E+10 | 0.00 | 0.00 |
June | 0.471808E+10 | 0.143482E+10 | 0.340163E+10 | 0.170075E+10 | 0.170088E+10 | 0.00 | 0.00 |
July | 0.543804E+10 | 0.137192E+10 | 0.372092E+10 | 0.199103E+10 | 0.172989E+10 | 0.00 | 0.00 |
August | 0.517776E+10 | 0.142063E+10 | 0.349095E+10 | 0.189195E+10 | 0.159900E+10 | 0.00 | 0.00 |
September | 0.416681E+10 | 0.152651E+10 | 0.289248E+10 | 0.154773E+10 | 0.134476E+10 | 0.00 | 0.00 |
October | 0.339091E+10 | 0.171940E+10 | 0.228488E+10 | 0.124745E+10 | 0.103743E+10 | 0.00 | 0.00 |
November | 0.259804E+10 | 0.223574E+10 | 0.199735E+10 | 0.104475E+10 | 0.952595E+09 | 0.00 | 0.00 |
December | 0.237585E+10 | 0.252184E+10 | 0.182280E+10 | 0.977667E+09 | 0.845137E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.443305E+11 | 0.228886E+11 | 0.323703E+11 | 0.165149E+11 | 0.158554E+11 | 0.00 | 0.00 |
Minimum of Months | 0.229964E+10 | 0.137192E+10 | 0.179171E+10 | 0.891285E+09 | 0.845137E+09 | 0.00 | 0.00 |
Maximum of Months | 0.543804E+10 | 0.252184E+10 | 0.372092E+10 | 0.199103E+10 | 0.178540E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.341089E+11 | -0.330873E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102155E+10 | 58.98 | 0.00 | 0.00 |
February | 0.310258E+11 | -0.301009E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -924835203.7 | 58.98 | 0.00 | 0.00 |
March | 0.360497E+11 | -0.350231E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102664E+10 | 58.98 | 0.00 | 0.00 |
April | 0.320853E+11 | -0.310953E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989980557.5 | 58.97 | 0.00 | 0.00 |
May | 0.333798E+11 | -0.323547E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102501E+10 | 58.97 | 0.00 | 0.00 |
June | 0.323329E+11 | -0.313400E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992854968.9 | 58.98 | 0.00 | 0.00 |
July | 0.303766E+11 | -0.293564E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102026E+10 | 58.96 | 0.00 | 0.00 |
August | 0.331160E+11 | -0.320919E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102417E+10 | 58.96 | 0.00 | 0.00 |
September | 0.304567E+11 | -0.294679E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988856860.4 | 58.97 | 0.00 | 0.00 |
October | 0.321107E+11 | -0.310912E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101945E+10 | 58.97 | 0.00 | 0.00 |
November | 0.322961E+11 | -0.313094E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986699606.5 | 58.97 | 0.00 | 0.00 |
December | 0.328883E+11 | -0.318687E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101955E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.390227E+12 | -0.378187E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120398E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.303766E+11 | -0.350231E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102664E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.360497E+11 | -0.293564E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -924835203.7 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:30 | 6809.02 | 36.64 | 284.50 | 273.17 | 1328.70 | 25.84 | 165.83 | 260.50 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:30 | 6039.46 | 34.03 | 265.33 | 267.00 | 961.83 | 23.71 | 164.33 | 244.67 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:00 | 1641.00 | 17.38 | 10.50 | 306.83 | 765.52 | 19.75 | 101.33 | 266.33 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:19 | 1034.91 | 16.43 | 0.00 | 320.67 | 623.93 | 19.36 | 16.00 | 273.17 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-06:00 | 897.34 | 16.14 | 0.00 | 351.50 | 512.65 | 19.05 | 0.33 | 283.50 |
June | 381.00 | 0.52 | 0.48 | 01-JUN-06:00 | 791.44 | 15.70 | 0.00 | 342.00 | 468.64 | 18.65 | 0.00 | 270.17 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-06:00 | 791.87 | 15.73 | 0.00 | 350.33 | 486.12 | 18.70 | 0.00 | 289.33 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:30 | 886.01 | 15.98 | 0.00 | 341.00 | 548.59 | 18.91 | 1.17 | 284.33 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:00 | 1323.12 | 17.22 | 14.00 | 299.83 | 718.18 | 19.47 | 31.33 | 260.33 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 3255.38 | 25.20 | 141.67 | 296.83 | 887.37 | 20.32 | 53.83 | 259.50 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 6590.56 | 36.11 | 290.00 | 275.00 | 1183.16 | 25.25 | 171.50 | 265.00 |
December | 297.00 | 0.51 | 0.48 | 01-DEC-07:30 | 6605.58 | 34.97 | 265.33 | 271.17 | 1729.80 | 27.99 | 172.67 | 263.67 |
Annual Sum or Average | 4065.67 | 0.51 | 2773.24 | 22.48 | 1271.33 | 3695.33 | 812.24 | 21.10 | 878.33 | 3220.50 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 791.44 | 15.70 | 0.00 | 267.00 | 468.64 | 18.65 | 0.00 | 244.67 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 6809.02 | 36.64 | 290.00 | 351.50 | 1729.80 | 27.99 | 172.67 | 289.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-07:30 | 1228.53 | 18.41 | 56.67 | 244.67 | 692.81 | 21.94 | 74.83 | 174.50 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-07:10 | 1508.34 | 19.76 | 70.50 | 246.00 | 757.48 | 21.23 | 68.67 | 184.33 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 1802.48 | 18.99 | 82.33 | 299.83 | 1020.22 | 22.51 | 98.33 | 240.83 |
April | 358.33 | 0.51 | 0.48 | 01-APR-05:00 | 1855.48 | 18.92 | 77.00 | 322.33 | 934.69 | 20.80 | 56.67 | 268.17 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:19 | 1762.24 | 18.30 | 76.50 | 360.83 | 982.80 | 21.63 | 83.00 | 292.00 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:19 | 1771.47 | 17.79 | 71.50 | 351.83 | 949.74 | 20.85 | 64.33 | 285.00 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:30 | 1967.88 | 18.27 | 82.33 | 361.67 | 1037.41 | 21.15 | 71.83 | 303.83 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-06:49 | 1992.87 | 18.72 | 85.67 | 342.50 | 999.40 | 21.62 | 70.33 | 290.33 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:40 | 2126.26 | 19.64 | 89.50 | 297.33 | 753.28 | 20.09 | 44.67 | 227.83 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 1831.29 | 18.37 | 68.50 | 253.00 | 765.05 | 20.42 | 51.67 | 187.17 |
November | 300.00 | 0.53 | 0.48 | 01-NOV-06:49 | 1560.52 | 19.41 | 79.50 | 242.00 | 858.40 | 22.26 | 80.00 | 180.17 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-07:19 | 1354.32 | 19.97 | 81.17 | 242.33 | 693.80 | 21.41 | 64.67 | 166.00 |
Annual Sum or Average | 4065.67 | 0.52 | 1751.32 | 18.83 | 921.17 | 3564.33 | 884.52 | 21.32 | 829.00 | 2800.17 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1228.53 | 17.79 | 56.67 | 242.00 | 692.81 | 20.09 | 44.67 | 166.00 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 2126.26 | 19.97 | 89.50 | 361.67 | 1037.41 | 22.51 | 98.33 | 303.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.56 | 0.48 | 01-JAN-09:20 | 407.64 | 12.87 | 0.00 | 197.00 | 269.26 | 16.38 | 0.00 | 28.67 |
February | 279.67 | 0.54 | 0.48 | 01-FEB-09:30 | 494.77 | 13.87 | 0.00 | 222.83 | 306.06 | 17.02 | 0.00 | 87.33 |
March | 338.17 | 0.54 | 0.48 | 01-MAR-08:00 | 584.31 | 14.40 | 0.00 | 288.17 | 349.65 | 17.30 | 0.00 | 187.00 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:40 | 641.11 | 15.56 | 0.00 | 323.67 | 411.09 | 18.56 | 0.00 | 262.50 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:49 | 817.45 | 16.42 | 0.00 | 374.83 | 474.01 | 19.32 | 0.00 | 324.17 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:40 | 864.95 | 18.49 | 42.50 | 367.67 | 513.96 | 21.12 | 42.33 | 327.67 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:00 | 803.17 | 18.30 | 45.00 | 377.83 | 470.95 | 19.34 | 0.17 | 346.83 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:30 | 649.41 | 15.64 | 0.00 | 356.17 | 424.45 | 18.60 | 0.00 | 304.00 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-07:10 | 571.76 | 14.77 | 0.00 | 289.00 | 369.67 | 17.84 | 0.00 | 199.67 |
October | 296.17 | 0.56 | 0.48 | 01-OCT-09:39 | 435.70 | 13.12 | 0.00 | 216.50 | 288.64 | 16.41 | 0.00 | 74.17 |
November | 300.00 | 0.57 | 0.48 | 01-NOV-08:30 | 415.50 | 12.63 | 0.00 | 203.50 | 271.34 | 15.93 | 0.00 | 46.33 |
December | 297.00 | 0.58 | 0.48 | 01-DEC-09:20 | 368.83 | 12.15 | 0.00 | 175.00 | 249.12 | 15.70 | 0.00 | 17.33 |
Annual Sum or Average | 4065.67 | 0.53 | 607.51 | 15.09 | 87.50 | 3392.17 | 377.14 | 17.97 | 42.50 | 2205.67 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 368.83 | 12.15 | 0.00 | 175.00 | 249.12 | 15.70 | 0.00 | 17.33 | |
Maximum of Months | 408.67 | 0.58 | 0.48 | 864.95 | 18.49 | 45.00 | 377.83 | 513.96 | 21.12 | 42.33 | 346.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.54 | 0.48 | 01-JAN-09:20 | 1747.35 | 19.97 | 86.17 | 225.17 | 658.77 | 21.11 | 71.83 | 168.83 |
February | 279.67 | 0.53 | 0.48 | 01-FEB-09:30 | 1637.76 | 19.78 | 73.50 | 237.17 | 842.05 | 21.35 | 71.67 | 182.00 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:00 | 1811.38 | 18.82 | 80.50 | 291.00 | 997.67 | 22.04 | 94.50 | 234.33 |
April | 358.33 | 0.51 | 0.48 | 01-APR-08:20 | 2484.00 | 19.11 | 82.33 | 314.67 | 927.55 | 18.33 | 5.33 | 266.83 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-07:40 | 2446.87 | 16.92 | 52.33 | 350.17 | 919.34 | 18.51 | 15.67 | 293.17 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-07:19 | 1991.14 | 14.39 | 0.00 | 343.17 | 1085.81 | 18.51 | 10.00 | 295.50 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-07:30 | 2107.02 | 14.44 | 5.67 | 352.17 | 1117.24 | 18.41 | 6.83 | 314.50 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:00 | 2706.97 | 18.63 | 86.67 | 332.67 | 1026.83 | 18.50 | 7.50 | 292.83 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-07:00 | 2335.10 | 19.92 | 87.00 | 287.50 | 1213.26 | 22.70 | 79.83 | 242.00 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 2319.28 | 21.34 | 104.00 | 258.00 | 869.50 | 21.23 | 59.00 | 198.83 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-08:30 | 1725.41 | 19.44 | 82.33 | 230.17 | 975.04 | 22.84 | 90.00 | 176.67 |
December | 297.00 | 0.55 | 0.48 | 01-DEC-09:09 | 1563.35 | 19.43 | 84.00 | 215.00 | 893.90 | 22.70 | 89.17 | 159.83 |
Annual Sum or Average | 4065.67 | 0.52 | 2103.17 | 18.30 | 824.50 | 3436.83 | 970.68 | 20.32 | 601.33 | 2825.33 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1563.35 | 14.39 | 0.00 | 215.00 | 658.77 | 18.33 | 5.33 | 159.83 | |
Maximum of Months | 408.67 | 0.55 | 0.48 | 2706.97 | 21.34 | 104.00 | 352.17 | 1213.26 | 22.84 | 94.50 | 314.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:30 | 6795.32 | 36.21 | 284.33 | 272.83 | 1372.67 | 21.70 | 96.83 | 261.17 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:30 | 5991.14 | 32.37 | 254.00 | 264.33 | 996.43 | 19.76 | 61.00 | 246.00 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:00 | 1618.18 | 11.46 | 9.83 | 305.50 | 792.92 | 15.63 | 3.00 | 269.17 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:19 | 1025.49 | 10.80 | 0.00 | 319.33 | 647.33 | 15.66 | 0.00 | 276.17 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-06:00 | 882.39 | 10.65 | 0.00 | 349.33 | 528.72 | 15.42 | 0.00 | 287.83 |
June | 381.00 | 0.52 | 0.48 | 01-JUN-06:00 | 779.20 | 10.40 | 0.00 | 339.50 | 483.43 | 15.18 | 0.00 | 275.00 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-06:49 | 781.38 | 10.60 | 0.00 | 349.17 | 501.89 | 15.41 | 0.00 | 294.50 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:30 | 877.92 | 10.66 | 0.00 | 339.50 | 568.58 | 15.49 | 0.00 | 288.17 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:00 | 1312.29 | 11.48 | 14.00 | 298.00 | 746.80 | 15.47 | 0.00 | 262.67 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 3227.85 | 21.07 | 137.67 | 294.33 | 926.18 | 15.83 | 14.00 | 261.83 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 6531.17 | 34.17 | 274.67 | 270.33 | 1223.97 | 21.12 | 90.67 | 265.17 |
December | 297.00 | 0.51 | 0.48 | 01-DEC-07:30 | 6594.20 | 34.16 | 265.00 | 270.83 | 1775.37 | 24.38 | 135.50 | 264.17 |
Annual Sum or Average | 4065.67 | 0.51 | 2753.67 | 18.32 | 1239.50 | 3673.00 | 840.06 | 17.30 | 401.00 | 3251.83 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 779.20 | 10.40 | 0.00 | 264.33 | 483.43 | 15.18 | 0.00 | 246.00 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 6795.32 | 36.21 | 284.33 | 349.33 | 1775.37 | 24.38 | 135.50 | 294.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-07:30 | 1228.67 | 15.31 | 56.67 | 243.83 | 711.99 | 19.98 | 54.83 | 183.00 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-07:10 | 1505.96 | 16.89 | 70.50 | 245.33 | 778.11 | 18.97 | 44.00 | 189.00 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 1807.45 | 16.07 | 82.33 | 299.17 | 1042.95 | 20.44 | 77.00 | 245.83 |
April | 358.33 | 0.51 | 0.48 | 01-APR-05:00 | 1855.31 | 15.69 | 77.00 | 320.83 | 962.39 | 18.17 | 49.00 | 272.83 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:19 | 1750.84 | 14.93 | 76.50 | 358.83 | 1007.54 | 19.22 | 70.00 | 297.33 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:19 | 1765.33 | 14.46 | 71.50 | 351.33 | 975.14 | 18.40 | 60.67 | 289.83 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:30 | 1959.36 | 15.05 | 82.33 | 360.50 | 1066.15 | 18.74 | 68.67 | 309.83 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-06:49 | 1986.36 | 15.57 | 85.67 | 341.17 | 1027.78 | 19.18 | 68.50 | 295.50 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:40 | 2133.31 | 16.86 | 89.00 | 296.17 | 777.72 | 17.58 | 37.50 | 235.17 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 1836.37 | 15.30 | 68.50 | 252.67 | 759.01 | 17.64 | 38.67 | 193.50 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-06:49 | 1527.46 | 16.45 | 75.50 | 241.00 | 818.03 | 18.76 | 50.50 | 184.83 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-07:19 | 1183.91 | 14.83 | 55.67 | 239.83 | 713.21 | 19.58 | 56.17 | 171.33 |
Annual Sum or Average | 4065.67 | 0.52 | 1734.45 | 15.57 | 891.17 | 3550.67 | 902.02 | 18.88 | 675.50 | 2868.00 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1183.91 | 14.46 | 55.67 | 239.83 | 711.99 | 17.58 | 37.50 | 171.33 | |
Maximum of Months | 408.67 | 0.54 | 0.48 | 2133.31 | 16.89 | 89.00 | 360.50 | 1066.15 | 20.44 | 77.00 | 309.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.56 | 0.48 | 01-JAN-09:20 | 399.88 | 7.43 | 0.00 | 191.83 | 276.56 | 12.73 | 0.00 | 41.83 |
February | 279.67 | 0.54 | 0.48 | 01-FEB-09:20 | 485.65 | 8.59 | 0.00 | 219.00 | 314.71 | 13.56 | 0.00 | 107.00 |
March | 338.17 | 0.54 | 0.48 | 01-MAR-08:50 | 574.42 | 9.33 | 0.00 | 286.50 | 360.07 | 14.02 | 0.00 | 196.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:30 | 632.92 | 10.60 | 0.00 | 322.67 | 424.23 | 15.55 | 0.00 | 266.67 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:49 | 805.32 | 11.03 | 0.00 | 373.83 | 488.23 | 15.96 | 0.00 | 328.00 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:40 | 853.57 | 13.60 | 42.33 | 366.83 | 529.37 | 18.08 | 40.83 | 329.83 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:00 | 794.82 | 13.66 | 44.83 | 377.83 | 486.13 | 16.20 | 0.00 | 348.33 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:30 | 650.61 | 10.76 | 0.00 | 357.33 | 437.86 | 15.72 | 0.00 | 311.17 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-07:10 | 563.86 | 9.78 | 0.00 | 288.00 | 381.18 | 14.71 | 0.00 | 211.67 |
October | 296.17 | 0.56 | 0.48 | 01-OCT-09:39 | 429.97 | 7.93 | 0.00 | 215.00 | 297.75 | 13.07 | 0.00 | 87.17 |
November | 300.00 | 0.57 | 0.48 | 01-NOV-08:20 | 407.96 | 7.54 | 0.00 | 198.83 | 278.88 | 12.49 | 0.00 | 58.17 |
December | 297.00 | 0.58 | 0.48 | 01-DEC-09:09 | 361.55 | 6.85 | 0.00 | 169.50 | 255.72 | 12.07 | 0.00 | 22.67 |
Annual Sum or Average | 4065.67 | 0.53 | 599.67 | 10.01 | 87.17 | 3367.17 | 388.56 | 14.71 | 40.83 | 2309.00 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 361.55 | 6.85 | 0.00 | 169.50 | 255.72 | 12.07 | 0.00 | 22.67 | |
Maximum of Months | 408.67 | 0.58 | 0.48 | 853.57 | 13.66 | 44.83 | 377.83 | 529.37 | 18.08 | 40.83 | 348.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.54 | 0.48 | 01-JAN-09:09 | 1745.30 | 17.30 | 86.17 | 224.83 | 677.70 | 19.07 | 45.00 | 176.67 |
February | 279.67 | 0.53 | 0.48 | 01-FEB-09:20 | 1633.15 | 16.93 | 73.50 | 236.33 | 863.23 | 19.11 | 48.00 | 187.00 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:50 | 1816.18 | 15.87 | 80.33 | 291.00 | 1020.24 | 19.88 | 70.67 | 240.00 |
April | 358.33 | 0.51 | 0.48 | 01-APR-08:09 | 2481.07 | 15.93 | 82.33 | 314.17 | 956.33 | 15.13 | 0.00 | 271.00 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-07:40 | 2431.78 | 13.14 | 52.33 | 349.33 | 947.25 | 15.26 | 0.00 | 299.67 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-07:19 | 1982.44 | 9.92 | 0.00 | 342.83 | 1113.98 | 15.18 | 0.00 | 300.83 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-07:19 | 2095.52 | 10.09 | 5.67 | 351.00 | 1147.60 | 15.11 | 0.00 | 319.33 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:00 | 2695.26 | 15.43 | 86.67 | 331.83 | 1056.69 | 15.37 | 7.00 | 297.33 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-07:49 | 2312.41 | 16.64 | 84.00 | 287.33 | 1242.76 | 20.44 | 71.83 | 246.50 |
October | 296.17 | 0.52 | 0.48 | 01-OCT-09:39 | 2173.21 | 16.49 | 81.83 | 257.33 | 894.11 | 18.91 | 52.50 | 205.67 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-08:20 | 1723.08 | 16.86 | 82.33 | 229.67 | 986.63 | 20.81 | 72.50 | 181.00 |
December | 297.00 | 0.55 | 0.48 | 01-DEC-08:00 | 1562.23 | 16.90 | 83.83 | 215.00 | 852.03 | 19.30 | 58.17 | 163.33 |
Annual Sum or Average | 4065.67 | 0.52 | 2085.56 | 14.86 | 799.00 | 3430.67 | 991.15 | 17.55 | 425.67 | 2888.33 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1562.23 | 9.92 | 0.00 | 215.00 | 677.70 | 15.11 | 0.00 | 163.33 | |
Maximum of Months | 408.67 | 0.55 | 0.48 | 2695.26 | 17.30 | 86.67 | 351.00 | 1242.76 | 20.81 | 72.50 | 319.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:30 | 6794.49 | 36.20 | 284.33 | 272.83 | 1373.68 | 21.68 | 96.83 | 261.17 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:30 | 5991.31 | 32.36 | 254.00 | 264.33 | 997.50 | 19.74 | 61.00 | 246.00 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:00 | 1618.81 | 11.43 | 9.83 | 305.50 | 793.86 | 15.61 | 3.00 | 269.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:19 | 1025.78 | 10.76 | 0.00 | 319.33 | 647.91 | 15.64 | 0.00 | 276.50 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-06:00 | 882.72 | 10.61 | 0.00 | 349.33 | 529.27 | 15.40 | 0.00 | 288.33 |
June | 381.00 | 0.52 | 0.48 | 01-JUN-06:00 | 779.39 | 10.36 | 0.00 | 339.50 | 483.87 | 15.16 | 0.00 | 275.17 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-06:49 | 781.45 | 10.56 | 0.00 | 349.17 | 502.29 | 15.39 | 0.00 | 294.67 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:30 | 878.05 | 10.62 | 0.00 | 339.50 | 569.04 | 15.47 | 0.00 | 288.33 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:00 | 1312.69 | 11.44 | 14.00 | 298.00 | 747.48 | 15.45 | 0.00 | 262.83 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 3228.14 | 21.04 | 137.67 | 294.33 | 926.94 | 15.81 | 14.00 | 261.83 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 6530.73 | 34.16 | 274.67 | 270.33 | 1224.97 | 21.11 | 90.67 | 265.33 |
December | 297.00 | 0.51 | 0.48 | 01-DEC-07:30 | 6593.12 | 34.14 | 265.00 | 270.83 | 1776.29 | 24.37 | 135.50 | 264.17 |
Annual Sum or Average | 4065.67 | 0.51 | 2753.72 | 18.29 | 1239.50 | 3673.00 | 840.77 | 17.29 | 401.00 | 3253.83 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 779.39 | 10.36 | 0.00 | 264.33 | 483.87 | 15.16 | 0.00 | 246.00 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 6794.49 | 36.20 | 284.33 | 349.33 | 1776.29 | 24.37 | 135.50 | 294.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-07:30 | 1228.30 | 15.27 | 56.67 | 243.67 | 712.38 | 19.96 | 54.83 | 183.00 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-07:10 | 1505.74 | 16.85 | 70.50 | 245.33 | 778.64 | 18.96 | 44.00 | 189.17 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 1807.44 | 16.03 | 82.33 | 299.17 | 1043.58 | 20.42 | 77.00 | 246.17 |
April | 358.33 | 0.51 | 0.48 | 01-APR-05:00 | 1855.16 | 15.65 | 77.00 | 320.83 | 962.96 | 18.15 | 49.00 | 272.83 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:19 | 1750.87 | 14.88 | 76.50 | 359.00 | 1008.20 | 19.20 | 70.00 | 297.50 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:19 | 1765.26 | 14.42 | 71.33 | 351.33 | 975.74 | 18.38 | 60.67 | 289.83 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:30 | 1959.12 | 15.01 | 82.33 | 360.50 | 1066.73 | 18.72 | 68.67 | 309.83 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-06:49 | 1964.77 | 15.33 | 83.17 | 341.17 | 1028.29 | 19.17 | 68.50 | 295.50 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:40 | 2029.02 | 15.36 | 73.00 | 295.83 | 778.23 | 17.56 | 37.50 | 235.17 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 1836.09 | 15.26 | 68.50 | 252.67 | 759.42 | 17.62 | 38.67 | 193.50 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-06:49 | 1527.15 | 16.41 | 75.50 | 241.00 | 818.44 | 18.74 | 50.50 | 185.17 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-07:19 | 1183.53 | 14.79 | 55.67 | 239.83 | 713.52 | 19.56 | 56.17 | 171.33 |
Annual Sum or Average | 4065.67 | 0.52 | 1723.79 | 15.39 | 872.50 | 3550.33 | 902.54 | 18.86 | 675.50 | 2869.00 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1183.53 | 14.42 | 55.67 | 239.83 | 712.38 | 17.56 | 37.50 | 171.33 | |
Maximum of Months | 408.67 | 0.54 | 0.48 | 2029.02 | 16.85 | 83.17 | 360.50 | 1066.73 | 20.42 | 77.00 | 309.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.56 | 0.48 | 01-JAN-09:20 | 399.69 | 7.38 | 0.00 | 191.83 | 276.73 | 12.71 | 0.00 | 42.33 |
February | 279.67 | 0.54 | 0.48 | 01-FEB-09:20 | 485.57 | 8.55 | 0.00 | 219.00 | 314.97 | 13.54 | 0.00 | 107.00 |
March | 338.17 | 0.54 | 0.48 | 01-MAR-08:50 | 574.44 | 9.29 | 0.00 | 286.67 | 360.41 | 14.00 | 0.00 | 197.17 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:30 | 632.79 | 10.55 | 0.00 | 322.67 | 424.53 | 15.53 | 0.00 | 266.67 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:49 | 805.38 | 10.99 | 0.00 | 373.83 | 488.68 | 15.94 | 0.00 | 328.17 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:40 | 853.60 | 13.56 | 42.33 | 366.83 | 529.81 | 18.06 | 40.83 | 329.83 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:00 | 794.70 | 13.63 | 44.83 | 377.83 | 486.50 | 16.18 | 0.00 | 348.33 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:30 | 650.43 | 10.71 | 0.00 | 357.33 | 438.14 | 15.70 | 0.00 | 311.17 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-07:10 | 563.72 | 9.73 | 0.00 | 288.00 | 381.44 | 14.69 | 0.00 | 211.83 |
October | 296.17 | 0.56 | 0.48 | 01-OCT-09:39 | 429.83 | 7.88 | 0.00 | 214.67 | 297.94 | 13.05 | 0.00 | 87.17 |
November | 300.00 | 0.57 | 0.48 | 01-NOV-08:20 | 407.80 | 7.49 | 0.00 | 198.67 | 279.07 | 12.47 | 0.00 | 58.50 |
December | 297.00 | 0.58 | 0.48 | 01-DEC-09:09 | 361.34 | 6.80 | 0.00 | 169.00 | 255.85 | 12.05 | 0.00 | 22.83 |
Annual Sum or Average | 4065.67 | 0.53 | 599.57 | 9.97 | 87.17 | 3366.33 | 388.85 | 14.69 | 40.83 | 2311.00 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 361.34 | 6.80 | 0.00 | 169.00 | 255.85 | 12.05 | 0.00 | 22.83 | |
Maximum of Months | 408.67 | 0.58 | 0.48 | 853.60 | 13.63 | 44.83 | 377.83 | 529.81 | 18.06 | 40.83 | 348.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.54 | 0.48 | 01-JAN-09:09 | 1744.89 | 17.26 | 86.17 | 224.83 | 678.13 | 19.05 | 45.00 | 176.83 |
February | 279.67 | 0.53 | 0.48 | 01-FEB-09:20 | 1632.79 | 16.89 | 73.33 | 236.17 | 863.80 | 19.10 | 48.00 | 187.00 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:50 | 1816.04 | 15.83 | 80.33 | 290.83 | 1020.90 | 19.87 | 70.67 | 240.00 |
April | 358.33 | 0.51 | 0.48 | 01-APR-08:09 | 2480.77 | 15.89 | 82.33 | 314.17 | 956.95 | 15.11 | 0.00 | 271.17 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-07:40 | 2431.67 | 13.10 | 52.33 | 349.33 | 947.94 | 15.24 | 0.00 | 299.67 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-07:19 | 1982.17 | 9.87 | 0.00 | 342.67 | 1114.65 | 15.16 | 0.00 | 300.83 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-07:19 | 2095.09 | 10.04 | 5.67 | 351.00 | 1148.18 | 15.08 | 0.00 | 319.50 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:00 | 2694.86 | 15.39 | 86.67 | 331.83 | 1057.24 | 15.34 | 7.00 | 297.50 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-07:49 | 2312.08 | 16.60 | 84.00 | 287.33 | 1243.39 | 20.43 | 71.83 | 246.50 |
October | 296.17 | 0.52 | 0.48 | 01-OCT-09:39 | 2172.86 | 16.45 | 81.83 | 257.33 | 894.54 | 18.89 | 52.50 | 205.67 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-08:20 | 1722.68 | 16.82 | 82.33 | 229.67 | 987.08 | 20.79 | 72.50 | 181.00 |
December | 297.00 | 0.55 | 0.48 | 01-DEC-08:00 | 1561.78 | 16.86 | 83.83 | 215.00 | 852.37 | 19.28 | 58.17 | 163.33 |
Annual Sum or Average | 4065.67 | 0.52 | 2085.23 | 14.82 | 798.83 | 3430.17 | 991.71 | 17.53 | 425.67 | 2889.00 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1561.78 | 9.87 | 0.00 | 215.00 | 678.13 | 15.08 | 0.00 | 163.33 | |
Maximum of Months | 408.67 | 0.55 | 0.48 | 2694.86 | 17.26 | 86.67 | 351.00 | 1243.39 | 20.79 | 72.50 | 319.50 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.156140E+09 | 8793.30 | 28-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3130569.13 | 1781.95 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 61513179.83 | 5898.23 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 957785.17 | 1409.54 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19385555.55 | 4323.64 | 12-DEC-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.156140E+09 | 8793.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.350216E+10 | 122286.49 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.355727E+09 | 42840.49 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.249367E+10 | 80604.98 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46517543.67 | 37578.53 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18719035.31 | 11363.04 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164050E+10 | 70214.47 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.805728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.350216E+10 | 122286.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172293E+10 | 105709.92 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.372661E+09 | 33809.53 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.881403E+09 | 114634.40 | 08-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97848763.42 | 46788.38 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 99424066.48 | 37519.54 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.661741E+09 | 111362.20 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.383601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172293E+10 | 114634.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.580649E+09 | 111382.28 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166684E+09 | 26278.16 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.349669E+09 | 111035.70 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31584573.17 | 25200.24 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9661820.22 | 6774.14 | 24-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178687E+09 | 89397.01 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.580649E+09 | 111382.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.161468E+09 | 129553.16 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10729308.20 | 8679.99 | 28-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.316756E+09 | 144452.16 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 48058932.56 | 9175.60 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 39545561.49 | 44216.23 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.576557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.316756E+09 | 144452.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.426027E+09 | 86541.32 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6442233.86 | 2675.93 | 28-FEB-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178449E+09 | 58913.44 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33215910.67 | 7791.40 | 01-APR-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 81110717.84 | 24362.30 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.725246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.426027E+09 | 86541.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.768853E+09 | 16213.22 | 03-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185446E+09 | 8139.81 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.598937E+09 | 12249.83 | 30-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16506191.56 | 7507.23 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2067521.53 | 1895.54 | 12-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 31342473.68 | 5594.86 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.471944E+09 | 10872.30 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.768853E+09 | 16213.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.553117E+09 | 65518.51 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154607E+09 | 64727.16 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103457E+09 | 55744.20 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 30259864.62 | 10660.28 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 91042853.01 | 58775.17 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.932484E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.553117E+09 | 65518.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123305E+10 | 12187.25 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.707505E+09 | 12128.04 | 13-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.809503E+09 | 12101.64 | 28-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115506E+09 | 12094.73 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24564754.82 | 12074.75 | 13-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 53164085.00 | 12099.06 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.432231E+09 | 12100.52 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.881976E+09 | 12091.41 | 22-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.425750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123305E+10 | 12187.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.471279E+09 | 13029.16 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.356509E+09 | 12920.99 | 25-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.362560E+09 | 13036.64 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38387016.26 | 11737.36 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4340305.58 | 9662.89 | 13-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14846844.90 | 4080.88 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132403E+09 | 12909.66 | 25-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.319562E+09 | 13001.68 | 13-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.471279E+09 | 13036.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.329635E+09 | 16359.41 | 03-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.284182E+09 | 16369.49 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.464776E+09 | 16321.77 | 30-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 69686354.91 | 16275.18 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36901486.88 | 16298.98 | 13-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1786080.75 | 568.77 | 12-OCT-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 58819551.52 | 16059.72 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178144E+09 | 16350.46 | 13-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.464776E+09 | 16369.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.440712E+09 | 13476.95 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.238160E+09 | 11017.53 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.278391E+09 | 13484.92 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37486208.87 | 11136.59 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9908879.20 | 6859.44 | 13-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5713338.72 | 458.25 | 30-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113912E+09 | 10584.42 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.276530E+09 | 13425.42 | 13-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.440712E+09 | 13484.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.170844E+11 | 0.170609E+11 | 76846.85 | 18-JAN-13:20 | 76846.85 | 0.14 |
February | 0.00 | 0.00 | 0.100549E+11 | 0.998685E+10 | 72397.62 | 01-FEB-12:00 | 72397.62 | 0.14 |
March | 0.00 | 0.00 | 0.121751E+11 | 0.118935E+11 | 82238.36 | 23-MAR-14:00 | 70728.52 | 0.17 |
April | 0.00 | 0.00 | 0.281334E+11 | 0.280763E+11 | 96181.11 | 26-APR-13:10 | 93000.49 | 0.35 |
May | 0.00 | 0.00 | 0.250289E+11 | 0.249479E+11 | 68882.07 | 03-MAY-13:00 | 68882.07 | 0.37 |
June | 0.00 | 0.00 | 0.467966E+11 | 0.422215E+11 | 111550.63 | 29-JUN-13:00 | 71562.73 | 0.58 |
July | 0.00 | 0.00 | 0.875878E+11 | 0.635415E+11 | 158971.46 | 31-JUL-15:40 | 90797.34 | 0.75 |
August | 0.00 | 0.00 | 0.108338E+12 | 0.736705E+11 | 162115.63 | 07-AUG-10:40 | 93200.05 | 0.80 |
September | 0.00 | 0.00 | 0.525867E+11 | 0.436483E+11 | 124925.69 | 22-SEP-12:30 | 65463.61 | 0.54 |
October | 0.00 | 0.00 | 0.661566E+11 | 0.555816E+11 | 157907.68 | 05-OCT-05:02 | 69011.03 | 0.38 |
November | 0.00 | 0.00 | 0.213583E+11 | 0.211329E+11 | 82593.59 | 28-NOV-14:00 | 82593.59 | 0.18 |
December | 0.00 | 0.00 | 0.252008E+11 | 0.251260E+11 | 88672.06 | 05-DEC-15:00 | 88672.06 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.500502E+12 | 0.416888E+12 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 0.100549E+11 | 0.998685E+10 | 68882.07 | 65463.61 | 0.07 | |
Maximum of Months | 0.00 | 0.00 | 0.108338E+12 | 0.736705E+11 | 162115.63 | 93200.05 | 0.80 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.134489E+12 | 0.133989E+12 | 613497.39 | 18-JAN-13:20 | 613497.39 | 0.15 |
February | 0.00 | 0.00 | 0.726511E+11 | 0.720484E+11 | 566884.75 | 01-FEB-12:00 | 566884.75 | 0.14 |
March | 0.00 | 0.00 | 0.825092E+11 | 0.810073E+11 | 635008.95 | 23-MAR-14:20 | 539453.42 | 0.17 |
April | 0.00 | 0.00 | 0.189786E+12 | 0.189693E+12 | 721276.35 | 26-APR-14:00 | 721276.35 | 0.33 |
May | 0.00 | 0.00 | 0.197201E+12 | 0.196550E+12 | 593384.21 | 03-MAY-13:00 | 593384.21 | 0.37 |
June | 0.00 | 0.00 | 0.363143E+12 | 0.329462E+12 | 929938.48 | 30-JUN-05:03 | 397714.54 | 0.55 |
July | 0.00 | 0.00 | 0.649832E+12 | 0.479907E+12 | 1241299.45 | 31-JUL-15:50 | 715478.12 | 0.60 |
August | 0.00 | 0.00 | 0.764864E+12 | 0.537292E+12 | 1288127.99 | 18-AUG-15:50 | 742794.05 | 0.62 |
September | 0.00 | 0.00 | 0.434754E+12 | 0.364038E+12 | 1114238.17 | 30-SEP-05:03 | 1114238.17 | 0.52 |
October | 0.00 | 0.00 | 0.518391E+12 | 0.438707E+12 | 1467934.79 | 05-OCT-05:02 | 641166.48 | 0.35 |
November | 0.00 | 0.00 | 0.144799E+12 | 0.143654E+12 | 588438.58 | 28-NOV-14:00 | 588438.58 | 0.18 |
December | 0.00 | 0.00 | 0.166934E+12 | 0.166416E+12 | 622572.56 | 05-DEC-15:00 | 622572.56 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.371935E+13 | 0.313276E+13 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 0.726511E+11 | 0.720484E+11 | 566884.75 | 397714.54 | 0.06 | |
Maximum of Months | 0.00 | 0.00 | 0.764864E+12 | 0.537292E+12 | 1467934.79 | 1114238.17 | 0.62 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.103661E+11 | 0.103661E+11 | 57456.28 | 18-JAN-13:40 | 57456.28 | 0.13 |
February | 0.00 | 0.00 | 0.577057E+10 | 0.571234E+10 | 50050.99 | 03-FEB-15:00 | 50050.99 | 0.13 |
March | 0.00 | 0.00 | 0.709783E+10 | 0.702439E+10 | 62293.84 | 23-MAR-15:00 | 52898.27 | 0.15 |
April | 0.00 | 0.00 | 0.185353E+11 | 0.185213E+11 | 90951.89 | 26-APR-13:50 | 88329.38 | 0.31 |
May | 0.00 | 0.00 | 0.192659E+11 | 0.192102E+11 | 67950.72 | 03-MAY-13:10 | 67950.72 | 0.35 |
June | 0.00 | 0.00 | 0.379305E+11 | 0.341797E+11 | 105510.94 | 29-JUN-13:00 | 67930.72 | 0.53 |
July | 0.00 | 0.00 | 0.700199E+11 | 0.515185E+11 | 155543.70 | 31-JUL-15:20 | 92015.35 | 0.58 |
August | 0.00 | 0.00 | 0.817907E+11 | 0.569360E+11 | 158825.48 | 18-AUG-15:30 | 93416.18 | 0.60 |
September | 0.00 | 0.00 | 0.430475E+11 | 0.362120E+11 | 114364.18 | 29-SEP-13:40 | 114364.18 | 0.50 |
October | 0.00 | 0.00 | 0.495090E+11 | 0.418668E+11 | 153751.66 | 05-OCT-05:02 | 67207.68 | 0.34 |
November | 0.00 | 0.00 | 0.111376E+11 | 0.111357E+11 | 54539.31 | 19-NOV-13:22 | 54539.31 | 0.16 |
December | 0.00 | 0.00 | 0.130699E+11 | 0.130677E+11 | 61815.67 | 05-DEC-15:00 | 61815.67 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.367541E+12 | 0.305751E+12 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 0.577057E+10 | 0.571234E+10 | 50050.99 | 50050.99 | 0.05 | |
Maximum of Months | 0.00 | 0.00 | 0.817907E+11 | 0.569360E+11 | 158825.48 | 114364.18 | 0.60 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.105371E+11 | 0.104822E+11 | 66345.79 | 17-JAN-12:00 | 61075.65 | 0.09 |
February | 0.00 | 0.00 | 0.471321E+10 | 0.466714E+10 | 48530.42 | 01-FEB-12:00 | 48530.42 | 0.07 |
March | 0.00 | 0.00 | 0.526671E+10 | 0.523332E+10 | 40177.88 | 23-MAR-14:00 | 40177.88 | 0.10 |
April | 0.00 | 0.00 | 0.135341E+11 | 0.134676E+11 | 50917.11 | 26-APR-13:10 | 50917.11 | 0.23 |
May | 0.00 | 0.00 | 0.131628E+11 | 0.130963E+11 | 47262.47 | 03-MAY-04:03 | 21403.34 | 0.24 |
June | 0.00 | 0.00 | 0.243364E+11 | 0.231338E+11 | 65401.61 | 26-JUN-12:10 | 47220.98 | 0.37 |
July | 0.00 | 0.00 | 0.416264E+11 | 0.349772E+11 | 93998.47 | 31-JUL-09:10 | 55996.26 | 0.43 |
August | 0.00 | 0.00 | 0.482945E+11 | 0.389361E+11 | 108908.25 | 07-AUG-10:00 | 59720.06 | 0.48 |
September | 0.00 | 0.00 | 0.292931E+11 | 0.257919E+11 | 83642.12 | 22-SEP-10:00 | 34932.27 | 0.37 |
October | 0.00 | 0.00 | 0.383246E+11 | 0.331534E+11 | 96285.72 | 02-OCT-13:00 | 51722.22 | 0.27 |
November | 0.00 | 0.00 | 0.119272E+11 | 0.119055E+11 | 53749.98 | 27-NOV-12:00 | 53749.98 | 0.12 |
December | 0.00 | 0.00 | 0.146407E+11 | 0.146339E+11 | 63087.30 | 04-DEC-10:00 | 63087.30 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.255657E+12 | 0.229479E+12 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.471321E+10 | 0.466714E+10 | 40177.88 | 21403.34 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.482945E+11 | 0.389361E+11 | 108908.25 | 63087.30 | 0.48 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.512948E+10 | 0.508799E+10 | 2374.50 | 18-JAN-16:10 | 2288.27 | 0.00 |
February | 0.00 | 0.00 | 0.932725E+10 | 0.926814E+10 | 4475.10 | 20-FEB-16:55 | 4465.70 | 0.00 |
March | 0.00 | 0.00 | 0.154872E+11 | 0.154007E+11 | 7529.05 | 31-MAR-24:00 | 7529.05 | 0.00 |
April | 0.00 | 0.00 | 0.201109E+11 | 0.199970E+11 | 8325.83 | 30-APR-17:25 | 8307.25 | 0.00 |
May | 0.00 | 0.00 | 0.551086E+10 | 0.541480E+10 | 3830.46 | 31-MAY-24:00 | 3815.08 | 0.00 |
June | 0.00 | 0.00 | 0.105297E+11 | 0.103565E+11 | 5868.34 | 30-JUN-24:00 | 5864.38 | 0.00 |
July | 0.00 | 0.00 | 0.161027E+11 | 0.158559E+11 | 7736.31 | 31-JUL-23:35 | 7728.82 | 0.00 |
August | 0.00 | 0.00 | 0.211233E+11 | 0.208324E+11 | 8391.84 | 06-AUG-17:37 | 8371.20 | 0.00 |
September | 0.00 | 0.00 | 0.562032E+10 | 0.545178E+10 | 4027.69 | 30-SEP-24:00 | 4027.69 | 0.00 |
October | 0.00 | 0.00 | 0.108535E+11 | 0.107399E+11 | 5836.99 | 31-OCT-24:00 | 5834.24 | 0.00 |
November | 0.00 | 0.00 | 0.151506E+11 | 0.150857E+11 | 6368.51 | 12-NOV-16:15 | 6360.03 | 0.00 |
December | 0.00 | 0.00 | 0.206180E+11 | 0.205884E+11 | 8337.34 | 25-DEC-16:15 | 8337.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.155564E+12 | 0.154079E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.512948E+10 | 0.508799E+10 | 2374.50 | 2288.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.211233E+11 | 0.208324E+11 | 8391.84 | 8371.20 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.376786E+11 | 0.372760E+11 | 22009.20 | 18-JAN-16:10 | 21167.77 | 0.00 |
February | 0.00 | 0.00 | 0.795436E+11 | 0.789585E+11 | 40717.23 | 01-FEB-16:50 | 38748.71 | 0.00 |
March | 0.00 | 0.00 | 0.138222E+12 | 0.137359E+12 | 67278.34 | 31-MAR-23:40 | 67278.34 | 0.00 |
April | 0.00 | 0.00 | 0.187089E+12 | 0.185950E+12 | 77631.06 | 26-APR-16:00 | 75761.77 | 0.00 |
May | 0.00 | 0.00 | 0.471750E+11 | 0.462341E+11 | 34659.51 | 31-MAY-24:00 | 34463.18 | 0.00 |
June | 0.00 | 0.00 | 0.968154E+11 | 0.950945E+11 | 55393.08 | 30-JUN-24:00 | 55349.16 | 0.00 |
July | 0.00 | 0.00 | 0.151908E+12 | 0.149447E+12 | 73931.03 | 31-JUL-23:53 | 73860.97 | 0.00 |
August | 0.00 | 0.00 | 0.200451E+12 | 0.197545E+12 | 79993.46 | 17-AUG-16:00 | 76461.91 | 0.00 |
September | 0.00 | 0.00 | 0.494520E+11 | 0.477955E+11 | 38287.49 | 30-SEP-24:00 | 38287.49 | 0.00 |
October | 0.00 | 0.00 | 0.985402E+11 | 0.974108E+11 | 53989.07 | 31-OCT-24:00 | 53955.32 | 0.00 |
November | 0.00 | 0.00 | 0.136219E+12 | 0.135571E+12 | 59644.67 | 10-NOV-16:20 | 57345.74 | 0.00 |
December | 0.00 | 0.00 | 0.186635E+12 | 0.186336E+12 | 77582.46 | 07-DEC-16:10 | 75501.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.140973E+13 | 0.139498E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.376786E+11 | 0.372760E+11 | 22009.20 | 21167.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.200451E+12 | 0.197545E+12 | 79993.46 | 76461.91 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.248048E+10 | 0.244154E+10 | 2211.59 | 18-JAN-16:10 | 2127.14 | 0.00 |
February | 0.00 | 0.00 | 0.687344E+10 | 0.681583E+10 | 4084.04 | 01-FEB-16:40 | 3884.60 | 0.00 |
March | 0.00 | 0.00 | 0.128108E+11 | 0.127250E+11 | 6291.41 | 31-MAR-23:20 | 6291.41 | 0.00 |
April | 0.00 | 0.00 | 0.182137E+11 | 0.181001E+11 | 7840.20 | 26-APR-16:00 | 7653.20 | 0.00 |
May | 0.00 | 0.00 | 0.422734E+10 | 0.413420E+10 | 3221.60 | 31-MAY-23:20 | 3179.79 | 0.00 |
June | 0.00 | 0.00 | 0.947851E+10 | 0.930656E+10 | 5442.85 | 30-JUN-24:00 | 5438.10 | 0.00 |
July | 0.00 | 0.00 | 0.151346E+11 | 0.148886E+11 | 7320.82 | 31-JUL-23:53 | 7313.74 | 0.00 |
August | 0.00 | 0.00 | 0.199585E+11 | 0.196681E+11 | 8080.48 | 17-AUG-16:00 | 7727.04 | 0.00 |
September | 0.00 | 0.00 | 0.465460E+10 | 0.448958E+10 | 3789.79 | 30-SEP-24:00 | 3789.79 | 0.00 |
October | 0.00 | 0.00 | 0.937390E+10 | 0.926134E+10 | 5192.90 | 31-OCT-23:30 | 5184.28 | 0.00 |
November | 0.00 | 0.00 | 0.126247E+11 | 0.125602E+11 | 5975.75 | 10-NOV-16:20 | 5746.10 | 0.00 |
December | 0.00 | 0.00 | 0.173877E+11 | 0.173581E+11 | 7750.16 | 07-DEC-16:10 | 7542.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.133218E+12 | 0.131749E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.248048E+10 | 0.244154E+10 | 2211.59 | 2127.14 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.199585E+11 | 0.196681E+11 | 8080.48 | 7727.04 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 3778.84 | 654473.85 | 03-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1164.89 | 250582.96 | 27-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2565.09 | 719336.60 | 30-MAR-05:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 203.66 | 175834.51 | 01-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 29.67 | 85823.22 | 13-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.78 | 27956.28 | 30-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 359.62 | 125308.23 | 24-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1797.62 | 465003.25 | 13-DEC-06:03 |
Annual Sum or Average | 0.00 | 832.01 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 3778.84 | 719336.60 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 119036.11 | 1219097.76 | 18-JAN-14:30 | 11.49 | 129864.61 | 16-JAN-12:43 |
February | 76566.22 | 1043877.38 | 01-FEB-11:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 77278.22 | 1040134.74 | 22-MAR-12:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 177822.90 | 1086816.33 | 26-APR-14:40 | 32.77 | 135434.65 | 02-APR-07:30 |
May | 183332.16 | 1036369.84 | 04-MAY-15:00 | 1.14 | 8980.32 | 06-MAY-18:03 |
June | 294813.78 | 1201754.30 | 29-JUN-13:00 | 0.39 | 5042.21 | 18-JUN-20:53 |
July | 437415.53 | 1587794.12 | 31-JUL-15:50 | 0.82 | 9273.15 | 22-JUL-02:23 |
August | 492247.82 | 1624313.27 | 18-AUG-15:50 | 1.90 | 22102.48 | 23-AUG-01:23 |
September | 324811.74 | 1413514.77 | 30-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 361953.90 | 1835385.11 | 02-OCT-05:04 | 4.82 | 58046.53 | 01-OCT-06:42 |
November | 138020.74 | 1039564.16 | 28-NOV-15:00 | 4.60 | 26743.41 | 12-NOV-09:13 |
December | 143173.68 | 1035145.04 | 18-DEC-15:20 | 0.11 | 1427.43 | 25-DEC-16:43 |
Annual Sum or Average | 236864.35 | 4.83 | ||||
Minimum of Months | 76566.22 | 1035145.04 | 0.00 | 0.00 | ||
Maximum of Months | 492247.82 | 1835385.11 | 32.77 | 135434.65 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 84772.07 | 1363430.70 | 18-JAN-14:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 50984.75 | 966757.07 | 21-FEB-13:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 51791.45 | 1045513.88 | 23-MAR-14:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 126803.61 | 1141655.12 | 26-APR-14:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 129048.48 | 1045889.10 | 03-MAY-12:30 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 228635.93 | 2031427.25 | 28-JUN-05:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 369122.50 | 2536099.21 | 28-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 430172.60 | 2563343.14 | 07-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 263006.09 | 2310716.87 | 30-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 298598.65 | 2783617.64 | 05-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 97480.11 | 958774.89 | 28-NOV-13:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 104455.54 | 1105478.61 | 07-DEC-11:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 187430.54 | 0.00 | ||||
Minimum of Months | 50984.75 | 958774.89 | 0.00 | 0.00 | ||
Maximum of Months | 430172.60 | 2783617.64 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 25461.91 | 104995.30 | 18-JAN-13:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 50366.76 | 134801.37 | 01-FEB-12:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 78501.14 | 141504.18 | 11-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 113863.14 | 211117.19 | 26-APR-13:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 31427.38 | 89339.25 | 03-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 67192.70 | 132025.31 | 29-JUN-11:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 106079.83 | 195961.91 | 31-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 136048.84 | 225990.01 | 17-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 43711.54 | 212484.77 | 29-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 77248.82 | 255862.21 | 16-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 82048.37 | 172614.30 | 19-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 109284.36 | 198411.94 | 19-DEC-13:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 76987.29 | 0.00 | ||||
Minimum of Months | 25461.91 | 89339.25 | 0.00 | 0.00 | ||
Maximum of Months | 136048.84 | 255862.21 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 13772.96 | 45622.25 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13862.39 | 45625.19 | 03-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 14490.21 | 45400.28 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 13410.25 | 44601.90 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 13498.05 | 43635.72 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13506.59 | 42546.44 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 12376.61 | 41704.45 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 13395.03 | 41629.46 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 12789.97 | 42302.60 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13026.36 | 43400.67 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 13498.09 | 44457.56 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 13317.47 | 45247.24 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 13409.51 | ||||
Minimum of Months | 0.00 | 0.00 | 12376.61 | 41629.46 | ||
Maximum of Months | 0.00 | 0.00 | 14490.21 | 45625.19 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 78997.66 | 1772001.84 | 18-JAN-14:40 | 1093.04 | 90591.06 | 04-JAN-07:00 |
February | 46592.97 | 825952.06 | 01-FEB-12:00 | 949.51 | 82651.04 | 06-FEB-07:00 |
March | 49514.43 | 1447411.29 | 23-MAR-14:00 | 932.67 | 82540.36 | 09-MAR-06:40 |
April | 119054.86 | 1807934.49 | 26-APR-13:10 | 528.88 | 79301.99 | 01-APR-06:00 |
May | 117920.77 | 1759074.97 | 03-MAY-12:30 | 429.37 | 57559.39 | 10-MAY-18:00 |
June | 245893.55 | 2353329.81 | 29-JUN-13:00 | 232.37 | 40129.36 | 22-JUN-20:30 |
July | 514478.98 | 3429352.98 | 31-JUL-16:00 | 259.22 | 28729.33 | 06-JUL-05:40 |
August | 623101.91 | 3479619.01 | 18-AUG-16:00 | 217.25 | 41517.51 | 22-AUG-05:50 |
September | 307667.53 | 2961307.00 | 22-SEP-11:30 | 204.01 | 27506.78 | 18-SEP-06:30 |
October | 369610.12 | 3100326.43 | 03-OCT-13:40 | 468.06 | 80654.30 | 25-OCT-06:00 |
November | 87359.96 | 883871.41 | 28-NOV-14:00 | 1075.73 | 78921.56 | 22-NOV-20:40 |
December | 97250.02 | 1771168.28 | 05-DEC-14:30 | 965.43 | 87083.46 | 22-DEC-06:50 |
Annual Sum or Average | 223235.54 | 611.32 | ||||
Minimum of Months | 46592.97 | 825952.06 | 204.01 | 27506.78 | ||
Maximum of Months | 623101.91 | 3479619.01 | 1093.04 | 90591.06 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.128865E+11 | 0.83 | 8129.76 | 01-JAN-00:20 | 1.41 |
February | 0.111553E+11 | 0.80 | 8129.76 | 01-FEB-05:03 | 1.42 |
March | 0.129613E+11 | 0.84 | 8129.76 | 01-MAR-05:02 | 1.41 |
April | 0.119776E+11 | 0.80 | 8129.76 | 01-APR-04:03 | 1.42 |
May | 0.125093E+11 | 0.81 | 8129.76 | 01-MAY-03:02 | 1.41 |
June | 0.124686E+11 | 0.83 | 8129.76 | 01-JUN-04:03 | 1.41 |
July | 0.121373E+11 | 0.78 | 8129.76 | 01-JUL-04:03 | 1.41 |
August | 0.132848E+11 | 0.85 | 8129.76 | 01-AUG-03:02 | 1.41 |
September | 0.124167E+11 | 0.83 | 8129.76 | 01-SEP-03:02 | 1.40 |
October | 0.128484E+11 | 0.83 | 8129.76 | 01-OCT-23:53 | 1.39 |
November | 0.124418E+11 | 0.83 | 8129.76 | 01-NOV-03:03 | 1.41 |
December | 0.126293E+11 | 0.82 | 8129.76 | 01-DEC-04:03 | 1.41 |
Annual Sum or Average | 0.149717E+12 | 0.82 | |||
Minimum of Months | 0.111553E+11 | 0.78 | 8129.76 | 1.39 | |
Maximum of Months | 0.132848E+11 | 0.85 | 8129.76 | 1.42 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.533284E+10 | 0.38 | 9118.53 | 25-JAN-06:03 | 1.17 |
February | 0.520015E+10 | 0.40 | 10554.06 | 21-FEB-15:40 | 1.28 |
March | 0.667213E+10 | 0.45 | 10963.55 | 24-MAR-05:02 | 1.31 |
April | 0.829875E+10 | 0.54 | 12074.16 | 26-APR-14:00 | 1.39 |
May | 0.618580E+10 | 0.43 | 10965.68 | 25-MAY-05:02 | 1.31 |
June | 0.762712E+10 | 0.50 | 16118.85 | 26-JUN-05:02 | 1.67 |
July | 0.921077E+10 | 0.58 | 17885.98 | 31-JUL-05:02 | 1.78 |
August | 0.110422E+11 | 0.66 | 15451.94 | 17-AUG-05:02 | 1.62 |
September | 0.701621E+10 | 0.46 | 18032.27 | 30-SEP-05:03 | 1.80 |
October | 0.757218E+10 | 0.48 | 18032.27 | 02-OCT-05:02 | 1.79 |
November | 0.699913E+10 | 0.46 | 12314.89 | 13-NOV-09:30 | 1.41 |
December | 0.699241E+10 | 0.45 | 12644.47 | 18-DEC-16:00 | 1.45 |
Annual Sum or Average | 0.881497E+11 | 0.48 | |||
Minimum of Months | 0.520015E+10 | 0.38 | 9118.53 | 1.17 | |
Maximum of Months | 0.110422E+11 | 0.66 | 18032.27 | 1.80 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.346137E+11 | 0.32 | 76875.35 | 11-JAN-06:03 | 1.11 |
February | 0.317477E+11 | 0.33 | 75917.47 | 01-FEB-06:03 | 1.10 |
March | 0.364540E+11 | 0.34 | 100120.35 | 29-MAR-05:02 | 1.31 |
April | 0.433250E+11 | 0.37 | 92710.44 | 24-APR-05:02 | 1.24 |
May | 0.435486E+11 | 0.36 | 94136.80 | 01-MAY-05:03 | 1.25 |
June | 0.509453E+11 | 0.41 | 124056.31 | 26-JUN-05:02 | 1.49 |
July | 0.577087E+11 | 0.43 | 166383.23 | 26-JUL-05:02 | 1.79 |
August | 0.656990E+11 | 0.46 | 135371.05 | 07-AUG-05:03 | 1.57 |
September | 0.517147E+11 | 0.40 | 166383.23 | 30-SEP-05:03 | 1.80 |
October | 0.497349E+11 | 0.39 | 166383.23 | 02-OCT-05:02 | 1.79 |
November | 0.383686E+11 | 0.34 | 75917.47 | 01-NOV-05:03 | 1.10 |
December | 0.357262E+11 | 0.33 | 83618.52 | 13-DEC-06:03 | 1.17 |
Annual Sum or Average | 0.539586E+12 | 0.37 | |||
Minimum of Months | 0.317477E+11 | 0.32 | 75917.47 | 1.10 | |
Maximum of Months | 0.656990E+11 | 0.46 | 166383.23 | 1.80 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.290771E+10 | 0.30 | 5150.83 | 18-JAN-15:30 | 0.85 |
February | 0.263494E+10 | 0.30 | 5329.81 | 02-FEB-15:20 | 0.86 |
March | 0.311143E+10 | 0.32 | 7532.91 | 23-MAR-15:30 | 1.05 |
April | 0.396751E+10 | 0.34 | 9504.09 | 26-APR-14:30 | 1.22 |
May | 0.399762E+10 | 0.34 | 8758.72 | 03-MAY-15:20 | 1.16 |
June | 0.508407E+10 | 0.39 | 10626.60 | 26-JUN-05:02 | 1.30 |
July | 0.609604E+10 | 0.42 | 12893.76 | 28-JUL-05:02 | 1.47 |
August | 0.679836E+10 | 0.45 | 11331.51 | 21-AUG-05:02 | 1.35 |
September | 0.481870E+10 | 0.37 | 15587.74 | 30-SEP-05:03 | 1.66 |
October | 0.441272E+10 | 0.36 | 17602.12 | 05-OCT-05:02 | 1.79 |
November | 0.298076E+10 | 0.30 | 5393.10 | 10-NOV-14:50 | 0.86 |
December | 0.290800E+10 | 0.30 | 5204.02 | 05-DEC-15:40 | 0.86 |
Annual Sum or Average | 0.497179E+11 | 0.35 | |||
Minimum of Months | 0.263494E+10 | 0.30 | 5150.83 | 0.85 | |
Maximum of Months | 0.679836E+10 | 0.45 | 17602.12 | 1.79 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140531E+10 | 0.93 | 524.68 | 01-JAN-00:05 | 0.93 |
February | 0.126931E+10 | 0.93 | 524.68 | 01-FEB-00:10 | 0.93 |
March | 0.140531E+10 | 0.93 | 524.68 | 01-MAR-00:10 | 0.93 |
April | 0.135998E+10 | 0.93 | 524.68 | 01-APR-00:10 | 0.93 |
May | 0.140531E+10 | 0.93 | 524.68 | 01-MAY-00:05 | 0.93 |
June | 0.135998E+10 | 0.93 | 524.68 | 01-JUN-00:10 | 0.93 |
July | 0.140531E+10 | 0.93 | 524.68 | 01-JUL-00:10 | 0.93 |
August | 0.140531E+10 | 0.93 | 524.68 | 01-AUG-00:05 | 0.93 |
September | 0.135998E+10 | 0.93 | 524.68 | 01-SEP-00:03 | 0.93 |
October | 0.140531E+10 | 0.93 | 524.68 | 01-OCT-00:10 | 0.93 |
November | 0.135998E+10 | 0.93 | 524.68 | 01-NOV-00:10 | 0.93 |
December | 0.140531E+10 | 0.93 | 524.68 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.165464E+11 | 0.93 | |||
Minimum of Months | 0.126931E+10 | 0.93 | 524.68 | 0.93 | |
Maximum of Months | 0.140531E+10 | 0.93 | 524.68 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.133890E+11 | 0.93 | 4998.89 | 01-JAN-00:05 | 0.93 |
February | 0.120933E+11 | 0.93 | 4998.89 | 01-FEB-00:10 | 0.93 |
March | 0.133890E+11 | 0.93 | 4998.89 | 01-MAR-00:10 | 0.93 |
April | 0.129571E+11 | 0.93 | 4998.89 | 01-APR-00:10 | 0.93 |
May | 0.133890E+11 | 0.93 | 4998.89 | 01-MAY-00:05 | 0.93 |
June | 0.129571E+11 | 0.93 | 4998.89 | 01-JUN-00:10 | 0.93 |
July | 0.133890E+11 | 0.93 | 4998.89 | 01-JUL-00:10 | 0.93 |
August | 0.133890E+11 | 0.93 | 4998.89 | 01-AUG-00:05 | 0.93 |
September | 0.129571E+11 | 0.93 | 4998.89 | 01-SEP-00:03 | 0.93 |
October | 0.133890E+11 | 0.93 | 4998.89 | 01-OCT-00:10 | 0.93 |
November | 0.129571E+11 | 0.93 | 4998.89 | 01-NOV-00:10 | 0.93 |
December | 0.133890E+11 | 0.93 | 4998.89 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.157645E+12 | 0.93 | |||
Minimum of Months | 0.120933E+11 | 0.93 | 4998.89 | 0.93 | |
Maximum of Months | 0.133890E+11 | 0.93 | 4998.89 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136179E+10 | 0.93 | 508.43 | 01-JAN-00:05 | 0.93 |
February | 0.123000E+10 | 0.93 | 508.43 | 01-FEB-00:10 | 0.93 |
March | 0.136179E+10 | 0.93 | 508.43 | 01-MAR-00:10 | 0.93 |
April | 0.131786E+10 | 0.93 | 508.43 | 01-APR-00:10 | 0.93 |
May | 0.136179E+10 | 0.93 | 508.43 | 01-MAY-00:05 | 0.93 |
June | 0.131786E+10 | 0.93 | 508.43 | 01-JUN-00:10 | 0.93 |
July | 0.136179E+10 | 0.93 | 508.43 | 01-JUL-00:10 | 0.93 |
August | 0.136179E+10 | 0.93 | 508.43 | 01-AUG-00:05 | 0.93 |
September | 0.131786E+10 | 0.93 | 508.43 | 01-SEP-00:03 | 0.93 |
October | 0.136179E+10 | 0.93 | 508.43 | 01-OCT-00:10 | 0.93 |
November | 0.131786E+10 | 0.93 | 508.43 | 01-NOV-00:10 | 0.93 |
December | 0.136179E+10 | 0.93 | 508.43 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.160340E+11 | 0.93 | |||
Minimum of Months | 0.123000E+10 | 0.93 | 508.43 | 0.93 | |
Maximum of Months | 0.136179E+10 | 0.93 | 508.43 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 596029.32 | 541790.65 | 331.05 | 02-JAN-06:02 | 300.92 | 300.92 | 52.31 | 4.60 |
February | 96275.44 | 87514.38 | 22.34 | 27-FEB-06:03 | 20.30 | 20.30 | 29.12 | 1.19 |
March | 348895.02 | 317145.57 | 285.34 | 30-MAR-05:02 | 259.38 | 259.38 | 40.46 | 4.33 |
April | 19147.08 | 17404.69 | 11.76 | 01-APR-05:03 | 10.69 | 10.69 | 28.13 | 0.81 |
May | 2433.99 | 2212.50 | 3.65 | 13-MAY-05:02 | 3.32 | 3.32 | 24.45 | 0.37 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 25.03 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 25.03 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 25.03 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 25.03 | 0.00 |
October | 2036.73 | 1851.38 | 0.88 | 30-OCT-05:03 | 0.80 | 0.80 | 24.20 | 0.12 |
November | 30504.83 | 27728.89 | 7.43 | 24-NOV-06:03 | 6.76 | 6.76 | 30.31 | 0.61 |
December | 193504.80 | 175895.86 | 95.67 | 13-DEC-06:03 | 86.96 | 86.96 | 36.87 | 2.58 |
Annual Sum or Average | 1288827.21 | 1171543.93 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.20 | 0.00 | |
Maximum of Months | 596029.32 | 541790.65 | 331.05 | 300.92 | 300.92 | 52.31 | 4.60 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.221227E+09 | 0.201095E+09 | 11654.10 | 18-JAN-14:30 | 10593.58 | 10593.58 | 7.32 | 70.20 |
February | 78267420.15 | 71145084.92 | 3371.94 | 21-FEB-13:20 | 3065.10 | 3065.10 | 8.98 | 42.14 |
March | 81812492.02 | 74367555.25 | 1614.96 | 23-MAR-14:00 | 1468.00 | 1468.00 | 7.61 | 30.58 |
April | 0.265510E+09 | 0.241348E+09 | 2245.89 | 13-APR-12:10 | 2041.52 | 2041.52 | 8.76 | 35.37 |
May | 0.304507E+09 | 0.276797E+09 | 3478.95 | 03-MAY-12:30 | 3162.36 | 3162.36 | 7.44 | 42.71 |
June | 0.506303E+09 | 0.460230E+09 | 10729.10 | 28-JUN-05:03 | 9752.75 | 9752.75 | 8.44 | 67.92 |
July | 0.100835E+10 | 0.916594E+09 | 16550.98 | 25-JUL-05:02 | 15044.84 | 15044.84 | 8.32 | 80.64 |
August | 0.128736E+10 | 0.117021E+10 | 16550.98 | 08-AUG-05:03 | 15044.84 | 15044.84 | 8.29 | 80.64 |
September | 0.846139E+09 | 0.769140E+09 | 13816.56 | 29-SEP-10:50 | 12559.25 | 12559.25 | 6.74 | 75.10 |
October | 0.115933E+10 | 0.105383E+10 | 16550.98 | 02-OCT-05:02 | 15044.84 | 15044.84 | 8.24 | 80.64 |
November | 0.203620E+09 | 0.185090E+09 | 2254.67 | 08-NOV-14:50 | 2049.50 | 2049.50 | 7.94 | 35.43 |
December | 0.229311E+09 | 0.208444E+09 | 5305.64 | 07-DEC-11:30 | 4822.82 | 4822.82 | 8.94 | 50.99 |
Annual Sum or Average | 0.619174E+10 | 0.562829E+10 | ||||||
Minimum of Months | 78267420.15 | 71145084.92 | 1614.96 | 1468.00 | 1468.00 | 6.74 | 30.58 | |
Maximum of Months | 0.128736E+10 | 0.117021E+10 | 16550.98 | 15044.84 | 15044.84 | 8.98 | 80.64 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.101759E+11 | 0.924986E+10 | 11391.59 | 02-JAN-04:13 | 10354.96 | 10354.96 | 8.37 | 80.64 |
February | 0.779652E+10 | 0.708704E+10 | 11391.59 | 01-FEB-05:03 | 10354.96 | 10354.96 | 8.64 | 80.64 |
March | 0.792365E+10 | 0.720260E+10 | 11391.59 | 01-MAR-06:03 | 10354.96 | 10354.96 | 8.59 | 80.64 |
April | 0.126569E+11 | 0.115051E+11 | 11391.59 | 01-APR-05:03 | 10354.96 | 10354.96 | 8.46 | 80.64 |
May | 0.140544E+11 | 0.127754E+11 | 11391.59 | 01-MAY-00:05 | 10354.96 | 10354.96 | 8.43 | 80.64 |
June | 0.181137E+11 | 0.164653E+11 | 11391.59 | 01-JUN-04:03 | 10354.96 | 10354.96 | 8.66 | 80.64 |
July | 0.236747E+11 | 0.215203E+11 | 11391.59 | 01-JUL-03:02 | 10354.96 | 10354.96 | 8.54 | 80.64 |
August | 0.251104E+11 | 0.228253E+11 | 11391.59 | 01-AUG-00:33 | 10354.96 | 10354.96 | 8.16 | 80.64 |
September | 0.174353E+11 | 0.158487E+11 | 11391.59 | 01-SEP-01:03 | 10354.96 | 10354.96 | 8.38 | 80.64 |
October | 0.185005E+11 | 0.168170E+11 | 11391.59 | 01-OCT-06:42 | 10354.96 | 10354.96 | 7.69 | 80.64 |
November | 0.114786E+11 | 0.104341E+11 | 11391.59 | 01-NOV-04:55 | 10354.96 | 10354.96 | 8.49 | 80.64 |
December | 0.103740E+11 | 0.942995E+10 | 11391.59 | 01-DEC-06:03 | 10354.96 | 10354.96 | 8.70 | 80.64 |
Annual Sum or Average | 0.177294E+12 | 0.161161E+12 | ||||||
Minimum of Months | 0.779652E+10 | 0.708704E+10 | 11391.59 | 10354.96 | 10354.96 | 7.69 | 80.64 | |
Maximum of Months | 0.251104E+11 | 0.228253E+11 | 11391.59 | 10354.96 | 10354.96 | 8.70 | 80.64 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.172748E+10 | 0.157028E+10 | 644.97 | 01-JAN-00:05 | 586.28 | 586.28 | 19.74 | 2.72 |
February | 0.156031E+10 | 0.141832E+10 | 644.97 | 01-FEB-00:10 | 586.28 | 586.28 | 23.19 | 2.72 |
March | 0.172748E+10 | 0.157028E+10 | 644.97 | 01-MAR-00:10 | 586.28 | 586.28 | 25.61 | 2.72 |
April | 0.167176E+10 | 0.151963E+10 | 644.97 | 01-APR-00:10 | 586.28 | 586.28 | 28.70 | 2.72 |
May | 0.172748E+10 | 0.157028E+10 | 644.97 | 01-MAY-00:05 | 586.28 | 586.28 | 21.50 | 2.72 |
June | 0.167176E+10 | 0.151963E+10 | 644.97 | 01-JUN-00:10 | 586.28 | 586.28 | 23.76 | 2.72 |
July | 0.172748E+10 | 0.157028E+10 | 644.97 | 01-JUL-00:10 | 586.28 | 586.28 | 26.91 | 2.72 |
August | 0.172748E+10 | 0.157028E+10 | 644.97 | 01-AUG-00:05 | 586.28 | 586.28 | 30.46 | 2.72 |
September | 0.167176E+10 | 0.151963E+10 | 644.97 | 01-SEP-00:03 | 586.28 | 586.28 | 21.42 | 2.72 |
October | 0.172748E+10 | 0.157028E+10 | 644.97 | 01-OCT-00:10 | 586.28 | 586.28 | 24.94 | 2.72 |
November | 0.167176E+10 | 0.151963E+10 | 644.97 | 01-NOV-00:10 | 586.28 | 586.28 | 26.70 | 2.72 |
December | 0.172748E+10 | 0.157028E+10 | 644.97 | 01-DEC-00:10 | 586.28 | 586.28 | 28.86 | 2.72 |
Annual Sum or Average | 0.203397E+11 | 0.184888E+11 | ||||||
Minimum of Months | 0.156031E+10 | 0.141832E+10 | 644.97 | 586.28 | 586.28 | 19.74 | 2.72 | |
Maximum of Months | 0.172748E+10 | 0.157028E+10 | 644.97 | 586.28 | 586.28 | 30.46 | 2.72 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:05 | 1.79 | 1.79 | 55.70 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:03 | 1.79 | 1.79 | 56.34 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:03 | 1.79 | 1.79 | 55.71 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:03 | 1.79 | 1.79 | 55.74 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:03 | 1.79 | 1.79 | 57.25 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:03 | 1.79 | 1.79 | 56.56 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:02 | 1.79 | 1.79 | 56.56 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:02 | 1.79 | 1.79 | 56.50 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:02 | 1.79 | 1.79 | 56.87 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 56.13 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:03 | 1.79 | 1.79 | 56.23 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:03 | 1.79 | 1.79 | 57.05 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.70 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 57.25 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.132351E+11 | 0.120307E+11 | 29089.88 | 18-JAN-14:40 | 26442.70 | 26442.70 | 25.45 | 97.57 |
February | 0.100157E+11 | 0.910429E+10 | 29032.73 | 03-FEB-15:20 | 26390.75 | 26390.75 | 22.78 | 97.57 |
March | 0.103090E+11 | 0.937090E+10 | 29071.70 | 23-MAR-14:00 | 26426.18 | 26426.18 | 24.65 | 97.57 |
April | 0.164656E+11 | 0.149672E+11 | 29092.02 | 26-APR-13:10 | 26444.65 | 26444.65 | 25.53 | 97.57 |
May | 0.180808E+11 | 0.164355E+11 | 29089.10 | 03-MAY-12:30 | 26442.00 | 26442.00 | 25.41 | 97.57 |
June | 0.251241E+11 | 0.228378E+11 | 29124.67 | 29-JUN-13:00 | 26474.32 | 26474.32 | 26.87 | 97.57 |
July | 0.362477E+11 | 0.329492E+11 | 29172.06 | 28-JUL-12:30 | 26517.40 | 26517.40 | 28.91 | 97.57 |
August | 0.401276E+11 | 0.364760E+11 | 29172.06 | 07-AUG-10:00 | 26517.40 | 26517.40 | 28.88 | 97.57 |
September | 0.257953E+11 | 0.234480E+11 | 29161.13 | 22-SEP-11:30 | 26507.47 | 26507.47 | 28.36 | 97.57 |
October | 0.283148E+11 | 0.257381E+11 | 29169.48 | 03-OCT-13:40 | 26515.06 | 26515.06 | 28.70 | 97.57 |
November | 0.148283E+11 | 0.134789E+11 | 29032.95 | 28-NOV-15:00 | 26390.95 | 26390.95 | 22.79 | 97.57 |
December | 0.135444E+11 | 0.123119E+11 | 29089.83 | 05-DEC-14:30 | 26442.65 | 26442.65 | 25.44 | 97.57 |
Annual Sum or Average | 0.252088E+12 | 0.229148E+12 | ||||||
Minimum of Months | 0.100157E+11 | 0.910429E+10 | 29032.73 | 26390.75 | 26390.75 | 22.78 | 97.57 | |
Maximum of Months | 0.401276E+11 | 0.364760E+11 | 29172.06 | 26517.40 | 26517.40 | 28.91 | 97.57 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 79.60 | 79.60 | 3778.84 | 654473.85 | 03-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.68 | 26.68 | 1164.89 | 250582.96 | 27-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 23.89 | 23.89 | 2565.09 | 719336.60 | 30-MAR-05:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.15 | 25.15 | 203.66 | 175834.51 | 01-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 23.75 | 23.75 | 29.67 | 85823.22 | 13-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 25.03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.03 | 25.03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.03 | 25.03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 25.03 | 25.03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.03 | 25.03 | 27.78 | 27956.28 | 30-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 24.20 | 24.20 | 359.62 | 125308.23 | 24-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 27.14 | 27.14 | 1797.62 | 465003.25 | 13-DEC-06:03 |
Annual Sum or Average | 0.00 | 832.01 | ||||||
Minimum of Months | 0.00 | 0.00 | 23.75 | 23.75 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 79.60 | 79.60 | 3778.84 | 719336.60 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 119036.11 | 1219097.76 | 18-JAN-14:30 | 10.74 | 7.14 | 11.49 | 129864.61 | 16-JAN-12:43 |
February | 76566.22 | 1043877.38 | 01-FEB-11:10 | 10.27 | 8.60 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 77278.22 | 1040134.74 | 22-MAR-12:30 | 10.49 | 8.83 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 177822.90 | 1086816.33 | 26-APR-14:40 | 10.32 | 7.11 | 32.77 | 135434.65 | 02-APR-07:30 |
May | 183332.16 | 1036369.84 | 04-MAY-15:00 | 10.47 | 8.83 | 1.14 | 8980.32 | 06-MAY-18:03 |
June | 294813.78 | 1201754.30 | 29-JUN-13:00 | 10.66 | 7.11 | 0.39 | 5042.21 | 18-JUN-20:53 |
July | 437415.53 | 1587794.12 | 31-JUL-15:50 | 11.76 | 7.06 | 0.82 | 9273.15 | 22-JUL-02:23 |
August | 492247.82 | 1624313.27 | 18-AUG-15:50 | 11.84 | 7.03 | 1.90 | 22102.48 | 23-AUG-01:23 |
September | 324811.74 | 1413514.77 | 30-SEP-05:03 | 11.32 | 7.14 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 361953.90 | 1835385.11 | 02-OCT-05:04 | 13.28 | 7.85 | 4.82 | 58046.53 | 01-OCT-06:42 |
November | 138020.74 | 1039564.16 | 28-NOV-15:00 | 10.33 | 8.67 | 4.60 | 26743.41 | 12-NOV-09:13 |
December | 143173.68 | 1035145.04 | 18-DEC-15:20 | 10.42 | 8.78 | 0.11 | 1427.43 | 25-DEC-16:43 |
Annual Sum or Average | 236864.35 | 4.83 | ||||||
Minimum of Months | 76566.22 | 1035145.04 | 10.27 | 7.03 | 0.00 | 0.00 | ||
Maximum of Months | 492247.82 | 1835385.11 | 13.28 | 8.83 | 32.77 | 135434.65 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 84772.07 | 1363430.70 | 18-JAN-14:30 | 11.34 | 8.34 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 50984.75 | 966757.07 | 21-FEB-13:20 | 12.18 | 8.97 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 51791.45 | 1045513.88 | 23-MAR-14:20 | 14.99 | 8.63 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 126803.61 | 1141655.12 | 26-APR-14:40 | 14.50 | 8.36 | 0.00 | 0.00 | 01-APR-00:10 |
May | 129048.48 | 1045889.10 | 03-MAY-12:30 | 12.55 | 8.37 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 228635.93 | 2031427.25 | 28-JUN-05:03 | 13.84 | 9.15 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 369122.50 | 2536099.21 | 28-JUL-05:02 | 14.21 | 8.19 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 430172.60 | 2563343.14 | 07-AUG-05:03 | 14.33 | 8.05 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 263006.09 | 2310716.87 | 30-SEP-05:03 | 15.50 | 7.16 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 298598.65 | 2783617.64 | 05-OCT-05:02 | 14.95 | 7.76 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 97480.11 | 958774.89 | 28-NOV-13:50 | 14.44 | 8.26 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 104455.54 | 1105478.61 | 07-DEC-11:30 | 11.88 | 8.95 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 187430.54 | 0.00 | ||||||
Minimum of Months | 50984.75 | 958774.89 | 11.34 | 7.16 | 0.00 | 0.00 | ||
Maximum of Months | 430172.60 | 2783617.64 | 15.50 | 9.15 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 25461.91 | 104995.30 | 18-JAN-13:00 | 29.36 | 26.27 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 50366.76 | 134801.37 | 01-FEB-12:00 | 32.45 | 26.51 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 78501.14 | 141504.18 | 11-MAR-14:00 | 33.14 | 24.73 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 113863.14 | 211117.19 | 26-APR-13:00 | 40.28 | 28.08 | 0.00 | 0.00 | 01-APR-00:10 |
May | 31427.38 | 89339.25 | 03-MAY-13:00 | 27.73 | 24.29 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 67192.70 | 132025.31 | 29-JUN-11:00 | 32.16 | 25.57 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 106079.83 | 195961.91 | 31-JUL-13:00 | 38.73 | 28.87 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 136048.84 | 225990.01 | 17-AUG-14:00 | 41.79 | 29.13 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 43711.54 | 212484.77 | 29-SEP-13:00 | 40.42 | 36.36 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 77248.82 | 255862.21 | 16-OCT-11:00 | 44.81 | 37.64 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 82048.37 | 172614.30 | 19-NOV-13:00 | 36.34 | 27.75 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 109284.36 | 198411.94 | 19-DEC-13:00 | 38.98 | 27.05 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 76987.29 | 0.00 | ||||||
Minimum of Months | 25461.91 | 89339.25 | 27.73 | 24.29 | 0.00 | 0.00 | ||
Maximum of Months | 136048.84 | 255862.21 | 44.81 | 37.64 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.93 | 56.93 | 13772.96 | 45622.25 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.91 | 56.91 | 13862.39 | 45625.19 | 03-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.28 | 56.28 | 14490.21 | 45400.28 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.29 | 56.29 | 13410.25 | 44601.90 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 57.97 | 57.97 | 13498.05 | 43635.72 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.09 | 57.09 | 13506.59 | 42546.44 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.02 | 57.02 | 12376.61 | 41704.45 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 56.96 | 56.96 | 13395.03 | 41629.46 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 57.29 | 57.29 | 12789.97 | 42302.60 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.06 | 57.06 | 13026.36 | 43400.67 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.86 | 56.86 | 13498.09 | 44457.56 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.50 | 57.50 | 13317.47 | 45247.24 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 13409.51 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.28 | 56.28 | 12376.61 | 41629.46 | ||
Maximum of Months | 0.00 | 0.00 | 57.97 | 57.97 | 14490.21 | 45625.19 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 78997.66 | 1772001.84 | 18-JAN-14:40 | 25.45 | 21.10 | 1093.04 | 90591.06 | 04-JAN-07:00 |
February | 46592.97 | 825952.06 | 01-FEB-12:00 | 25.15 | 21.10 | 949.51 | 82651.04 | 06-FEB-07:00 |
March | 49514.43 | 1447411.29 | 23-MAR-14:00 | 24.65 | 21.50 | 932.67 | 82540.36 | 09-MAR-06:40 |
April | 119054.86 | 1807934.49 | 26-APR-13:10 | 25.53 | 21.90 | 528.88 | 79301.99 | 01-APR-06:00 |
May | 117920.77 | 1759074.97 | 03-MAY-12:30 | 25.41 | 21.12 | 429.37 | 57559.39 | 10-MAY-18:00 |
June | 245893.55 | 2353329.81 | 29-JUN-13:00 | 26.87 | 23.44 | 232.37 | 40129.36 | 22-JUN-20:30 |
July | 514478.98 | 3429352.98 | 31-JUL-16:00 | 29.51 | 24.98 | 259.22 | 28729.33 | 06-JUL-05:40 |
August | 623101.91 | 3479619.01 | 18-AUG-16:00 | 29.63 | 25.04 | 217.25 | 41517.51 | 22-AUG-05:50 |
September | 307667.53 | 2961307.00 | 22-SEP-11:30 | 28.36 | 24.83 | 204.01 | 27506.78 | 18-SEP-06:30 |
October | 369610.12 | 3100326.43 | 03-OCT-13:40 | 28.70 | 24.40 | 468.06 | 80654.30 | 25-OCT-06:00 |
November | 87359.96 | 883871.41 | 28-NOV-14:00 | 25.44 | 21.10 | 1075.73 | 78921.56 | 22-NOV-20:40 |
December | 97250.02 | 1771168.28 | 05-DEC-14:30 | 25.44 | 21.10 | 965.43 | 87083.46 | 22-DEC-06:50 |
Annual Sum or Average | 223235.54 | 611.32 | ||||||
Minimum of Months | 46592.97 | 825952.06 | 24.65 | 21.10 | 204.01 | 27506.78 | ||
Maximum of Months | 623101.91 | 3479619.01 | 29.63 | 25.04 | 1093.04 | 90591.06 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.156140E+09 | 0.00 | 0.170844E+11 | 0.533284E+10 | 0.00 | 0.00 |
February | 3130569.13 | 0.00 | 0.100549E+11 | 0.520015E+10 | 0.00 | 0.00 |
March | 61513179.83 | 0.00 | 0.121751E+11 | 0.667213E+10 | 0.00 | 0.00 |
April | 957785.17 | 0.00 | 0.281334E+11 | 0.829875E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.250289E+11 | 0.618580E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.467966E+11 | 0.762712E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.875878E+11 | 0.921077E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.108338E+12 | 0.110422E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.525867E+11 | 0.701621E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.661566E+11 | 0.757218E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.213583E+11 | 0.699913E+10 | 0.00 | 0.00 |
December | 19385555.55 | 0.00 | 0.252008E+11 | 0.699241E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241127E+09 | 0.00 | 0.500502E+12 | 0.881497E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.100549E+11 | 0.520015E+10 | 0.00 | 0.00 |
Maximum of Months | 0.156140E+09 | 0.00 | 0.108338E+12 | 0.110422E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.639323E+10 | 0.00 | 0.134489E+12 | 0.346137E+11 | 0.00 | 0.00 |
February | 0.912244E+09 | 0.00 | 0.726511E+11 | 0.317477E+11 | 0.00 | 0.00 |
March | 0.421994E+10 | 0.00 | 0.825092E+11 | 0.364540E+11 | 0.00 | 0.00 |
April | 0.257226E+09 | 0.00 | 0.189786E+12 | 0.433250E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.197201E+12 | 0.435486E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.363143E+12 | 0.509453E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.649832E+12 | 0.577087E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.764864E+12 | 0.656990E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.434754E+12 | 0.517147E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.518391E+12 | 0.497349E+11 | 0.00 | 0.00 |
November | 0.127805E+09 | 0.00 | 0.144799E+12 | 0.383686E+11 | 0.00 | 0.00 |
December | 0.260158E+10 | 0.00 | 0.166934E+12 | 0.357262E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.145120E+11 | 0.00 | 0.371935E+13 | 0.539586E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.726511E+11 | 0.317477E+11 | 0.00 | 0.00 |
Maximum of Months | 0.639323E+10 | 0.00 | 0.764864E+12 | 0.656990E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.379665E+10 | 0.00 | 0.103661E+11 | 0.290771E+10 | 0.00 | 0.00 |
February | 0.192641E+10 | 0.00 | 0.577057E+10 | 0.263494E+10 | 0.00 | 0.00 |
March | 0.261762E+10 | 0.00 | 0.709783E+10 | 0.311143E+10 | 0.00 | 0.00 |
April | 0.277572E+09 | 0.00 | 0.185353E+11 | 0.396751E+10 | 0.00 | 0.00 |
May | 75715426.48 | 0.00 | 0.192659E+11 | 0.399762E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.379305E+11 | 0.508407E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.700199E+11 | 0.609604E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.817907E+11 | 0.679836E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.430475E+11 | 0.481870E+10 | 0.00 | 0.00 |
October | 77577870.91 | 0.00 | 0.495090E+11 | 0.441272E+10 | 0.00 | 0.00 |
November | 0.798969E+09 | 0.00 | 0.111376E+11 | 0.298076E+10 | 0.00 | 0.00 |
December | 0.221920E+10 | 0.00 | 0.130699E+11 | 0.290800E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.117897E+11 | 0.00 | 0.367541E+12 | 0.497179E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.577057E+10 | 0.263494E+10 | 0.00 | 0.00 |
Maximum of Months | 0.379665E+10 | 0.00 | 0.817907E+11 | 0.679836E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.105371E+11 | 0.128865E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.471321E+10 | 0.111553E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.526671E+10 | 0.129613E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.135341E+11 | 0.119776E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.131628E+11 | 0.125093E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.243364E+11 | 0.124686E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.416264E+11 | 0.121373E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.482945E+11 | 0.132848E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.292931E+11 | 0.124167E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.383246E+11 | 0.128484E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.119272E+11 | 0.124418E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.146407E+11 | 0.126293E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.255657E+12 | 0.149717E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.471321E+10 | 0.111553E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.482945E+11 | 0.132848E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.631829E+10 | 0.259412E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.113339E+11 | 0.327594E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.186674E+11 | 0.458550E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.241537E+11 | 0.540286E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.676296E+10 | 0.265740E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.128331E+11 | 0.366335E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.195951E+11 | 0.489766E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.255948E+11 | 0.587674E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.693557E+10 | 0.267523E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.133476E+11 | 0.389936E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.183079E+11 | 0.451725E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.248312E+11 | 0.561847E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.188681E+12 | 0.496639E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.631829E+10 | 0.259412E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.255948E+11 | 0.587674E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.466011E+11 | 0.223115E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.968420E+11 | 0.293917E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.166830E+12 | 0.419970E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.224833E+12 | 0.507019E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.579893E+11 | 0.242033E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.118077E+12 | 0.342188E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.184901E+12 | 0.463816E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.242915E+12 | 0.558532E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.611105E+11 | 0.246156E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.121324E+12 | 0.361726E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.164810E+12 | 0.415479E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.225071E+12 | 0.518244E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.171130E+13 | 0.459219E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.466011E+11 | 0.223115E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.242915E+12 | 0.558532E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.308607E+10 | 0.196737E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.838894E+10 | 0.274551E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.154891E+11 | 0.404007E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.219109E+11 | 0.501497E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.520670E+10 | 0.234114E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.115695E+11 | 0.340886E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.184321E+11 | 0.465930E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.242013E+11 | 0.560454E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.576156E+10 | 0.242482E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.115604E+11 | 0.354825E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.153024E+11 | 0.399554E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.210121E+11 | 0.498612E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.161921E+12 | 0.447365E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.308607E+10 | 0.196737E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.242013E+11 | 0.560454E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.533284E+10 | 0.170844E+11 | 0.156140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.520015E+10 | 0.100549E+11 | 3130569.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.667213E+10 | 0.121751E+11 | 61513179.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.829875E+10 | 0.281334E+11 | 957785.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.618580E+10 | 0.250289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.762712E+10 | 0.467966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.921077E+10 | 0.875878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110422E+11 | 0.108338E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.701621E+10 | 0.525867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.757218E+10 | 0.661566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.699913E+10 | 0.213583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.699241E+10 | 0.252008E+11 | 19385555.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.881497E+11 | 0.500502E+12 | 0.241127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.520015E+10 | 0.100549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110422E+11 | 0.108338E+12 | 0.156140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.346137E+11 | 0.134489E+12 | 0.639323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317477E+11 | 0.726511E+11 | 0.912244E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.364540E+11 | 0.825092E+11 | 0.421994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.433250E+11 | 0.189786E+12 | 0.257226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.435486E+11 | 0.197201E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.509453E+11 | 0.363143E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.577087E+11 | 0.649832E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.656990E+11 | 0.764864E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.517147E+11 | 0.434754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.497349E+11 | 0.518391E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.383686E+11 | 0.144799E+12 | 0.127805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357262E+11 | 0.166934E+12 | 0.260158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.539586E+12 | 0.371935E+13 | 0.145120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.317477E+11 | 0.726511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.656990E+11 | 0.764864E+12 | 0.639323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.290771E+10 | 0.103661E+11 | 0.379665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.263494E+10 | 0.577057E+10 | 0.192641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311143E+10 | 0.709783E+10 | 0.261762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.396751E+10 | 0.185353E+11 | 0.277572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.399762E+10 | 0.192659E+11 | 75715426.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.508407E+10 | 0.379305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.609604E+10 | 0.700199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.679836E+10 | 0.817907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.481870E+10 | 0.430475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.441272E+10 | 0.495090E+11 | 77577870.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.298076E+10 | 0.111376E+11 | 0.798969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.290800E+10 | 0.130699E+11 | 0.221920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.497179E+11 | 0.367541E+12 | 0.117897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.263494E+10 | 0.577057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.679836E+10 | 0.817907E+11 | 0.379665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.128865E+11 | 0.105371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111553E+11 | 0.471321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129613E+11 | 0.526671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119776E+11 | 0.135341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125093E+11 | 0.131628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124686E+11 | 0.243364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121373E+11 | 0.416264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132848E+11 | 0.482945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124167E+11 | 0.292931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128484E+11 | 0.383246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124418E+11 | 0.119272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126293E+11 | 0.146407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149717E+12 | 0.255657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111553E+11 | 0.471321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132848E+11 | 0.482945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140531E+10 | 0.512948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126931E+10 | 0.932725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140531E+10 | 0.154872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135998E+10 | 0.201109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140531E+10 | 0.551086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135998E+10 | 0.105297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140531E+10 | 0.161027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140531E+10 | 0.211233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135998E+10 | 0.562032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140531E+10 | 0.108535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135998E+10 | 0.151506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140531E+10 | 0.206180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165464E+11 | 0.155564E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126931E+10 | 0.512948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140531E+10 | 0.211233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.133890E+11 | 0.376786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120933E+11 | 0.795436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133890E+11 | 0.138222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129571E+11 | 0.187089E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133890E+11 | 0.471750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129571E+11 | 0.968154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133890E+11 | 0.151908E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133890E+11 | 0.200451E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129571E+11 | 0.494520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133890E+11 | 0.985402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129571E+11 | 0.136219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133890E+11 | 0.186635E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157645E+12 | 0.140973E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120933E+11 | 0.376786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133890E+11 | 0.200451E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136179E+10 | 0.248048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123000E+10 | 0.687344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136179E+10 | 0.128108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131786E+10 | 0.182137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136179E+10 | 0.422734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131786E+10 | 0.947851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136179E+10 | 0.151346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136179E+10 | 0.199585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131786E+10 | 0.465460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136179E+10 | 0.937390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131786E+10 | 0.126247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136179E+10 | 0.173877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160340E+11 | 0.133218E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123000E+10 | 0.248048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136179E+10 | 0.199585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.533284E+10 | 0.156140E+09 | 0.170844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.520015E+10 | 3130569.13 | 0.100549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.667213E+10 | 61513179.83 | 0.121751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.829875E+10 | 957785.17 | 0.281334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.618580E+10 | 0.00 | 0.250289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.762712E+10 | 0.00 | 0.467966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.921077E+10 | 0.00 | 0.875878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.110422E+11 | 0.00 | 0.108338E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.701621E+10 | 0.00 | 0.525867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.757218E+10 | 0.00 | 0.661566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.699913E+10 | 0.00 | 0.213583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.699241E+10 | 19385555.55 | 0.252008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.881497E+11 | 0.241127E+09 | 0.500502E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.520015E+10 | 0.00 | 0.100549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110422E+11 | 0.156140E+09 | 0.108338E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.346137E+11 | 0.639323E+10 | 0.134489E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317477E+11 | 0.912244E+09 | 0.726511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.364540E+11 | 0.421994E+10 | 0.825092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.433250E+11 | 0.257226E+09 | 0.189786E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.435486E+11 | 0.00 | 0.197201E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.509453E+11 | 0.00 | 0.363143E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.577087E+11 | 0.00 | 0.649832E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.656990E+11 | 0.00 | 0.764864E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.517147E+11 | 0.00 | 0.434754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.497349E+11 | 0.00 | 0.518391E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.383686E+11 | 0.127805E+09 | 0.144799E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357262E+11 | 0.260158E+10 | 0.166934E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.539586E+12 | 0.145120E+11 | 0.371935E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.317477E+11 | 0.00 | 0.726511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.656990E+11 | 0.639323E+10 | 0.764864E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.290771E+10 | 0.379665E+10 | 0.103661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.263494E+10 | 0.192641E+10 | 0.577057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311143E+10 | 0.261762E+10 | 0.709783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.396751E+10 | 0.277572E+09 | 0.185353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.399762E+10 | 75715426.48 | 0.192659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.508407E+10 | 0.00 | 0.379305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.609604E+10 | 0.00 | 0.700199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.679836E+10 | 0.00 | 0.817907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.481870E+10 | 0.00 | 0.430475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.441272E+10 | 77577870.91 | 0.495090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.298076E+10 | 0.798969E+09 | 0.111376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.290800E+10 | 0.221920E+10 | 0.130699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.497179E+11 | 0.117897E+11 | 0.367541E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.263494E+10 | 0.00 | 0.577057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.679836E+10 | 0.379665E+10 | 0.817907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.128865E+11 | 0.00 | 0.105371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111553E+11 | 0.00 | 0.471321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129613E+11 | 0.00 | 0.526671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119776E+11 | 0.00 | 0.135341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125093E+11 | 0.00 | 0.131628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124686E+11 | 0.00 | 0.243364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121373E+11 | 0.00 | 0.416264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132848E+11 | 0.00 | 0.482945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124167E+11 | 0.00 | 0.292931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128484E+11 | 0.00 | 0.383246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124418E+11 | 0.00 | 0.119272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126293E+11 | 0.00 | 0.146407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149717E+12 | 0.00 | 0.255657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111553E+11 | 0.00 | 0.471321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132848E+11 | 0.00 | 0.482945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140531E+10 | 0.00 | 0.631829E+10 | 0.00 | 0.118881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126931E+10 | 0.00 | 0.113339E+11 | 0.00 | 0.200663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140531E+10 | 0.00 | 0.186674E+11 | 0.00 | 0.318019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135998E+10 | 0.00 | 0.241537E+11 | 0.00 | 0.404289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140531E+10 | 0.00 | 0.676296E+10 | 0.00 | 0.125209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135998E+10 | 0.00 | 0.128331E+11 | 0.00 | 0.230337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140531E+10 | 0.00 | 0.195951E+11 | 0.00 | 0.349235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140531E+10 | 0.00 | 0.255948E+11 | 0.00 | 0.447143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135998E+10 | 0.00 | 0.693557E+10 | 0.00 | 0.131525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140531E+10 | 0.00 | 0.133476E+11 | 0.00 | 0.249405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135998E+10 | 0.00 | 0.183079E+11 | 0.00 | 0.315728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140531E+10 | 0.00 | 0.248312E+11 | 0.00 | 0.421316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165464E+11 | 0.00 | 0.188681E+12 | 0.00 | 0.331175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126931E+10 | 0.00 | 0.631829E+10 | 0.00 | 0.118881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140531E+10 | 0.00 | 0.255948E+11 | 0.00 | 0.447143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.133890E+11 | 0.00 | 0.466011E+11 | 0.00 | 0.892245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120933E+11 | 0.00 | 0.968420E+11 | 0.00 | 0.172984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133890E+11 | 0.00 | 0.166830E+12 | 0.00 | 0.286079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129571E+11 | 0.00 | 0.224833E+12 | 0.00 | 0.377448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133890E+11 | 0.00 | 0.579893E+11 | 0.00 | 0.108143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129571E+11 | 0.00 | 0.118077E+12 | 0.00 | 0.212617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133890E+11 | 0.00 | 0.184901E+12 | 0.00 | 0.329926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133890E+11 | 0.00 | 0.242915E+12 | 0.00 | 0.424641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129571E+11 | 0.00 | 0.611105E+11 | 0.00 | 0.116585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133890E+11 | 0.00 | 0.121324E+12 | 0.00 | 0.227836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129571E+11 | 0.00 | 0.164810E+12 | 0.00 | 0.285908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133890E+11 | 0.00 | 0.225071E+12 | 0.00 | 0.384354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157645E+12 | 0.00 | 0.171130E+13 | 0.00 | 0.301575E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120933E+11 | 0.00 | 0.466011E+11 | 0.00 | 0.892245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133890E+11 | 0.00 | 0.242915E+12 | 0.00 | 0.424641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.136179E+10 | 0.00 | 0.308607E+10 | 0.00 | 0.605582E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123000E+10 | 0.00 | 0.838894E+10 | 0.00 | 0.151550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136179E+10 | 0.00 | 0.154891E+11 | 0.00 | 0.267828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131786E+10 | 0.00 | 0.219109E+11 | 0.00 | 0.369711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136179E+10 | 0.00 | 0.520670E+10 | 0.00 | 0.979352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131786E+10 | 0.00 | 0.115695E+11 | 0.00 | 0.209100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136179E+10 | 0.00 | 0.184321E+11 | 0.00 | 0.329751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136179E+10 | 0.00 | 0.242013E+11 | 0.00 | 0.424275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131786E+10 | 0.00 | 0.576156E+10 | 0.00 | 0.110696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136179E+10 | 0.00 | 0.115604E+11 | 0.00 | 0.218646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131786E+10 | 0.00 | 0.153024E+11 | 0.00 | 0.267768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136179E+10 | 0.00 | 0.210121E+11 | 0.00 | 0.362434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160340E+11 | 0.00 | 0.161921E+12 | 0.00 | 0.287025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123000E+10 | 0.00 | 0.308607E+10 | 0.00 | 0.605582E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136179E+10 | 0.00 | 0.242013E+11 | 0.00 | 0.424275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.596170E+09 | 74957422.52 | 0.00 | 0.102295E+09 | 0.00 | 0.00 | 0.565833E+11 | 0.00 | 1.02 |
February | 0.442450E+09 | 3668881.98 | 0.00 | 84121039.30 | 0.00 | 0.00 | 0.534192E+11 | 0.00 | 1.02 |
March | 0.524779E+09 | 0.00 | 0.00 | 98658961.34 | 0.00 | 0.00 | 0.633666E+11 | 0.00 | 1.05 |
April | 0.374396E+09 | 7433229.68 | 0.00 | 93862625.91 | 0.00 | 0.00 | 0.504519E+11 | 0.00 | 1.14 |
May | 0.360168E+09 | 4516994.64 | 0.00 | 91755579.98 | 0.00 | 0.00 | 0.522644E+11 | 0.00 | 1.20 |
June | 0.261895E+09 | 0.132243E+09 | 0.00 | 93089537.41 | 0.00 | 0.00 | 0.422301E+11 | 0.00 | 1.33 |
July | 0.220369E+09 | 0.219126E+10 | 0.00 | 80417207.03 | 451326.49 | 0.00 | 0.270471E+11 | 0.00 | 1.16 |
August | 0.256791E+09 | 0.283527E+10 | 0.00 | 85009084.15 | 0.00 | 0.00 | 0.277384E+11 | 0.00 | 1.27 |
September | 0.294341E+09 | 0.987542E+09 | 0.00 | 90237117.81 | 28636115.29 | 0.00 | 0.377463E+11 | 0.00 | 1.25 |
October | 0.323662E+09 | 0.247827E+10 | 0.00 | 89998792.37 | 19366379.98 | 0.00 | 0.350389E+11 | 0.00 | 1.15 |
November | 0.425790E+09 | 5938165.26 | 0.00 | 0.106049E+09 | 0.00 | 0.00 | 0.575456E+11 | 0.00 | 1.13 |
December | 0.578036E+09 | 68851.49 | 0.00 | 0.106072E+09 | 0.00 | 0.00 | 0.540444E+11 | 0.00 | 1.03 |
Annual Sum or Average | 0.465885E+10 | 0.872117E+10 | 0.00 | 0.112157E+10 | 48453821.76 | 0.00 | 0.557476E+12 | 0.00 | 1.15 |
Minimum of Months | 0.220369E+09 | 0.00 | 0.00 | 80417207.03 | 0.00 | 0.00 | 0.270471E+11 | 0.00 | 1.02 |
Maximum of Months | 0.596170E+09 | 0.283527E+10 | 0.00 | 0.106072E+09 | 28636115.29 | 0.00 | 0.633666E+11 | 0.00 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.456842E+10 | 60605208.70 | 0.00 | 70719625.33 | 22508318.15 | 0.00 | 0.379810E+11 | 0.00 | 0.71 |
February | 0.491068E+10 | 17752867.19 | 0.00 | 66280376.88 | 0.00 | 0.00 | 0.388871E+11 | 0.00 | 0.77 |
March | 0.539279E+10 | 0.00 | 0.00 | 82637499.10 | 9706720.86 | 0.00 | 0.491749E+11 | 0.00 | 0.84 |
April | 0.105563E+11 | 8921440.76 | 0.00 | 77741802.15 | 55328446.21 | 0.00 | 0.388827E+11 | 0.00 | 0.99 |
May | 0.560968E+10 | 31507645.99 | 0.00 | 72693593.45 | 0.00 | 0.00 | 0.367428E+11 | 0.00 | 0.87 |
June | 0.607955E+10 | 0.473196E+09 | 0.00 | 73717353.60 | 0.00 | 0.00 | 0.293338E+11 | 0.00 | 1.01 |
July | 0.979020E+10 | 0.406503E+10 | 0.00 | 48619901.98 | 0.411905E+09 | 0.00 | 0.137120E+11 | 0.00 | 1.05 |
August | 0.892673E+10 | 0.562668E+10 | 0.00 | 48658796.18 | 0.429529E+09 | 0.00 | 0.127137E+11 | 0.00 | 1.16 |
September | 0.450078E+10 | 0.104018E+10 | 0.00 | 64608679.21 | 0.104651E+09 | 0.00 | 0.233760E+11 | 0.00 | 0.88 |
October | 0.487273E+10 | 0.252425E+10 | 0.00 | 62159851.54 | 0.340772E+09 | 0.00 | 0.226443E+11 | 0.00 | 0.86 |
November | 0.582778E+10 | 5764680.34 | 0.00 | 80918069.20 | 16006761.24 | 0.00 | 0.428582E+11 | 0.00 | 0.88 |
December | 0.702472E+10 | 3142266.80 | 0.00 | 83726929.09 | 0.00 | 0.00 | 0.404807E+11 | 0.00 | 0.83 |
Annual Sum or Average | 0.780603E+11 | 0.138570E+11 | 0.00 | 0.832482E+09 | 0.139041E+10 | 0.00 | 0.386787E+12 | 0.00 | 0.91 |
Minimum of Months | 0.450078E+10 | 0.00 | 0.00 | 48619901.98 | 0.00 | 0.00 | 0.127137E+11 | 0.00 | 0.71 |
Maximum of Months | 0.105563E+11 | 0.562668E+10 | 0.00 | 83726929.09 | 0.429529E+09 | 0.00 | 0.491749E+11 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.990395E+11 | 93030828.51 | 0.00 | 0.349015E+09 | 0.586270E+09 | 0.00 | 0.203663E+12 | 0.00 | 0.52 |
February | 0.845821E+11 | 0.164919E+09 | 0.00 | 0.328861E+09 | 0.00 | 0.00 | 0.223194E+12 | 0.00 | 0.56 |
March | 0.954039E+11 | 0.00 | 0.00 | 0.390956E+09 | 0.330831E+09 | 0.00 | 0.268307E+12 | 0.00 | 0.57 |
April | 0.518696E+11 | 40237230.13 | 0.00 | 0.466148E+09 | 0.566004E+09 | 0.00 | 0.260291E+12 | 0.00 | 0.66 |
May | 0.481235E+11 | 0.322647E+09 | 0.00 | 0.505724E+09 | 0.00 | 0.00 | 0.286543E+12 | 0.00 | 0.70 |
June | 0.359128E+11 | 0.285254E+10 | 0.00 | 0.542510E+09 | 5068374.62 | 0.00 | 0.230685E+12 | 0.00 | 0.78 |
July | 0.334391E+11 | 0.278709E+11 | 0.00 | 0.382284E+09 | 0.321066E+10 | 0.00 | 0.109155E+12 | 0.00 | 0.74 |
August | 0.225308E+11 | 0.358257E+11 | 0.00 | 0.405654E+09 | 0.337557E+10 | 0.00 | 0.103952E+12 | 0.00 | 0.78 |
September | 0.323424E+11 | 0.825116E+10 | 0.00 | 0.472085E+09 | 0.169975E+10 | 0.00 | 0.187772E+12 | 0.00 | 0.72 |
October | 0.300387E+11 | 0.198023E+11 | 0.00 | 0.422821E+09 | 0.416798E+10 | 0.00 | 0.167556E+12 | 0.00 | 0.65 |
November | 0.543424E+11 | 27165455.59 | 0.00 | 0.436777E+09 | 0.183499E+09 | 0.00 | 0.271722E+12 | 0.00 | 0.60 |
December | 0.881468E+11 | 33727476.23 | 0.00 | 0.379839E+09 | 21892627.79 | 0.00 | 0.208323E+12 | 0.00 | 0.54 |
Annual Sum or Average | 0.675771E+12 | 0.952843E+11 | 0.00 | 0.508267E+10 | 0.141475E+11 | 0.00 | 0.252116E+13 | 0.00 | 0.65 |
Minimum of Months | 0.225308E+11 | 0.00 | 0.00 | 0.328861E+09 | 0.00 | 0.00 | 0.103952E+12 | 0.00 | 0.52 |
Maximum of Months | 0.990395E+11 | 0.358257E+11 | 0.00 | 0.542510E+09 | 0.416798E+10 | 0.00 | 0.286543E+12 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.169243E+11 | 3666634.94 | 0.00 | 10989051.41 | 59926421.70 | 0.254302E+09 | 0.756098E+10 | 0.00 | 0.45 |
February | 0.148522E+11 | 5395794.98 | 0.00 | 12712974.19 | 0.00 | 19342513.94 | 0.102360E+11 | 0.00 | 0.48 |
March | 0.174777E+11 | 0.00 | 0.00 | 15598972.78 | 19459227.33 | 3860931.04 | 0.131424E+11 | 0.00 | 0.50 |
April | 0.939513E+10 | 162667.47 | 0.00 | 33284446.45 | 33807644.65 | 0.00 | 0.201273E+11 | 0.00 | 0.62 |
May | 0.918296E+10 | 12682547.39 | 0.00 | 37772277.28 | 0.00 | 0.00 | 0.224946E+11 | 0.00 | 0.66 |
June | 0.628742E+10 | 0.142462E+09 | 0.00 | 47801996.10 | 0.00 | 0.00 | 0.205894E+11 | 0.00 | 0.78 |
July | 0.381791E+10 | 0.243728E+10 | 0.00 | 38025548.88 | 0.282890E+09 | 0.00 | 0.107878E+11 | 0.00 | 0.76 |
August | 0.246178E+10 | 0.333383E+10 | 0.00 | 40316418.86 | 0.265430E+09 | 0.00 | 0.981034E+10 | 0.00 | 0.81 |
September | 0.599930E+10 | 0.646547E+09 | 0.00 | 38167701.60 | 0.117299E+09 | 0.00 | 0.149104E+11 | 0.00 | 0.69 |
October | 0.704335E+10 | 0.155503E+10 | 0.00 | 27050672.43 | 0.466232E+09 | 0.00 | 0.989934E+10 | 0.00 | 0.61 |
November | 0.126530E+11 | 283154.78 | 0.00 | 18648040.64 | 13787567.62 | 0.00 | 0.133657E+11 | 0.00 | 0.51 |
December | 0.153090E+11 | 1322862.27 | 0.00 | 11899678.41 | 11342686.51 | 12848805.76 | 0.774943E+10 | 0.00 | 0.46 |
Annual Sum or Average | 0.121404E+12 | 0.813867E+10 | 0.00 | 0.332268E+09 | 0.127018E+10 | 0.290354E+09 | 0.160674E+12 | 0.00 | 0.61 |
Minimum of Months | 0.246178E+10 | 0.00 | 0.00 | 10989051.41 | 0.00 | 0.00 | 0.756098E+10 | 0.00 | 0.45 |
Maximum of Months | 0.174777E+11 | 0.333383E+10 | 0.00 | 47801996.10 | 0.466232E+09 | 0.254302E+09 | 0.224946E+11 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.232120E+10 | 3506622.42 | 0.00 | 2763963.69 | 6459256.76 | 0.00 | 0.165779E+10 | 0.00 | 0.53 |
February | 0.203560E+10 | 1954482.96 | 0.00 | 3161832.25 | 0.00 | 0.00 | 0.215154E+10 | 0.00 | 0.58 |
March | 0.207599E+10 | 0.00 | 0.00 | 4492850.69 | 1216645.73 | 0.00 | 0.313285E+10 | 0.00 | 0.65 |
April | 0.195909E+10 | 1072097.50 | 0.00 | 6319317.38 | 6934897.88 | 0.00 | 0.339221E+10 | 0.00 | 0.88 |
May | 0.132730E+10 | 4322530.63 | 0.00 | 6511383.60 | 0.00 | 0.00 | 0.354827E+10 | 0.00 | 0.82 |
June | 0.882302E+09 | 69421558.53 | 0.00 | 8566973.05 | 0.00 | 0.00 | 0.354169E+10 | 0.00 | 1.05 |
July | 0.126339E+10 | 0.641380E+09 | 0.00 | 5823970.35 | 45794851.44 | 0.00 | 0.168480E+10 | 0.00 | 1.13 |
August | 0.115092E+10 | 0.824799E+09 | 0.00 | 5132310.40 | 53036863.48 | 0.00 | 0.137745E+10 | 0.00 | 1.19 |
September | 0.907772E+09 | 0.159051E+09 | 0.00 | 5459210.55 | 9925317.37 | 0.00 | 0.215529E+10 | 0.00 | 0.82 |
October | 0.108978E+10 | 0.365786E+09 | 0.00 | 4633347.65 | 40303514.89 | 0.00 | 0.175944E+10 | 0.00 | 0.77 |
November | 0.198817E+10 | 623373.65 | 0.00 | 4546128.66 | 2006296.26 | 0.00 | 0.260444E+10 | 0.00 | 0.67 |
December | 0.224441E+10 | 334758.42 | 0.00 | 4112942.74 | 0.00 | 0.00 | 0.205078E+10 | 0.00 | 0.61 |
Annual Sum or Average | 0.192459E+11 | 0.207225E+10 | 0.00 | 61524231.02 | 0.165678E+09 | 0.00 | 0.290565E+11 | 0.00 | 0.81 |
Minimum of Months | 0.882302E+09 | 0.00 | 0.00 | 2763963.69 | 0.00 | 0.00 | 0.137745E+10 | 0.00 | 0.53 |
Maximum of Months | 0.232120E+10 | 0.824799E+09 | 0.00 | 8566973.05 | 53036863.48 | 0.00 | 0.354827E+10 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.142716E+10 | 5656100.35 | 0.00 | 3659044.32 | 2145201.10 | 0.00 | 0.207297E+10 | 0.00 | 0.72 |
February | 0.144389E+10 | 1474088.75 | 0.00 | 3289842.76 | 0.00 | 0.00 | 0.210383E+10 | 0.00 | 0.77 |
March | 0.158596E+10 | 143350.19 | 0.00 | 4405174.93 | 781768.61 | 0.00 | 0.275659E+10 | 0.00 | 0.86 |
April | 0.151219E+10 | 1923919.69 | 0.00 | 6502470.12 | 4798746.94 | 0.00 | 0.328126E+10 | 0.00 | 1.24 |
May | 0.901173E+09 | 4191959.68 | 0.00 | 6482416.37 | 0.00 | 0.00 | 0.341616E+10 | 0.00 | 1.13 |
June | 0.802350E+09 | 55525757.91 | 0.00 | 7262745.23 | 0.00 | 0.00 | 0.280221E+10 | 0.00 | 1.36 |
July | 0.998498E+09 | 0.535424E+09 | 0.00 | 5542880.08 | 25961363.33 | 0.00 | 0.153481E+10 | 0.00 | 1.53 |
August | 0.943802E+09 | 0.764106E+09 | 0.00 | 4626473.15 | 30887892.28 | 0.00 | 0.122801E+10 | 0.00 | 1.62 |
September | 0.719038E+09 | 0.126473E+09 | 0.00 | 5528487.11 | 7196931.04 | 0.00 | 0.199919E+10 | 0.00 | 1.14 |
October | 0.838582E+09 | 0.276834E+09 | 0.00 | 4184833.64 | 30661612.34 | 0.00 | 0.160671E+10 | 0.00 | 0.97 |
November | 0.141383E+10 | 451214.12 | 0.00 | 4165922.96 | 1525556.98 | 0.00 | 0.234532E+10 | 0.00 | 0.84 |
December | 0.164016E+10 | 275775.67 | 0.00 | 3758476.70 | 0.00 | 0.00 | 0.181589E+10 | 0.00 | 0.76 |
Annual Sum or Average | 0.142266E+11 | 0.177248E+10 | 0.00 | 59408767.36 | 0.103959E+09 | 0.00 | 0.269629E+11 | 0.00 | 1.08 |
Minimum of Months | 0.719038E+09 | 143350.19 | 0.00 | 3289842.76 | 0.00 | 0.00 | 0.122801E+10 | 0.00 | 0.72 |
Maximum of Months | 0.164016E+10 | 0.764106E+09 | 0.00 | 7262745.23 | 30887892.28 | 0.00 | 0.341616E+10 | 0.00 | 1.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120688E+10 | 31262144.40 | 0.00 | 12746773.36 | 2820617.35 | 0.00 | 0.669780E+10 | 0.00 | 1.18 |
February | 0.142144E+10 | 5615719.36 | 0.00 | 9405341.15 | 0.00 | 0.00 | 0.537758E+10 | 0.00 | 1.05 |
March | 0.176568E+10 | 1368209.89 | 0.00 | 9009953.69 | 236752.98 | 0.00 | 0.537373E+10 | 0.00 | 0.99 |
April | 0.194242E+10 | 2847400.27 | 0.00 | 9651978.80 | 5925091.83 | 0.00 | 0.469363E+10 | 0.00 | 1.17 |
May | 0.153446E+10 | 5318892.10 | 0.00 | 6771126.23 | 0.00 | 0.00 | 0.347331E+10 | 0.00 | 0.87 |
June | 0.110475E+10 | 77886415.71 | 0.00 | 7711964.03 | 0.00 | 0.00 | 0.310068E+10 | 0.00 | 1.03 |
July | 0.127569E+10 | 0.719617E+09 | 0.00 | 5572107.01 | 44252410.33 | 0.00 | 0.161326E+10 | 0.00 | 1.17 |
August | 0.114469E+10 | 0.112490E+10 | 0.00 | 6330437.71 | 50162014.84 | 0.00 | 0.163024E+10 | 0.00 | 1.44 |
September | 0.681028E+09 | 0.271565E+09 | 0.00 | 10343234.07 | 8335770.16 | 0.00 | 0.353408E+10 | 0.00 | 1.26 |
October | 0.827436E+09 | 0.698840E+09 | 0.00 | 10673454.92 | 22448495.95 | 0.00 | 0.323226E+10 | 0.00 | 1.24 |
November | 0.109257E+10 | 4957415.30 | 0.00 | 14119181.07 | 315349.27 | 0.00 | 0.711390E+10 | 0.00 | 1.33 |
December | 0.124227E+10 | 778133.14 | 0.00 | 16490430.08 | 0.00 | 0.00 | 0.680440E+10 | 0.00 | 1.32 |
Annual Sum or Average | 0.152393E+11 | 0.294496E+10 | 0.00 | 0.118826E+09 | 0.134497E+09 | 0.00 | 0.526449E+11 | 0.00 | 1.17 |
Minimum of Months | 0.681028E+09 | 778133.14 | 0.00 | 5572107.01 | 0.00 | 0.00 | 0.161326E+10 | 0.00 | 0.87 |
Maximum of Months | 0.194242E+10 | 0.112490E+10 | 0.00 | 16490430.08 | 50162014.84 | 0.00 | 0.711390E+10 | 0.00 | 1.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124206E+10 | 13302209.76 | 0.00 | 5570863.32 | 2406451.28 | 0.00 | 0.344733E+10 | 0.00 | 1.00 |
February | 0.665329E+09 | 2921655.70 | 0.00 | 7706409.87 | 0.00 | 0.00 | 0.486876E+10 | 0.00 | 1.24 |
March | 0.524822E+09 | 60617.53 | 0.00 | 12014875.94 | 1137000.03 | 0.00 | 0.729707E+10 | 0.00 | 1.56 |
April | 0.592082E+09 | 8835248.88 | 0.00 | 18332403.08 | 1877274.80 | 0.00 | 0.814226E+10 | 0.00 | 2.28 |
May | 0.563598E+09 | 4596428.69 | 0.00 | 10968749.56 | 0.00 | 0.00 | 0.546191E+10 | 0.00 | 1.59 |
June | 0.374820E+09 | 79868766.49 | 0.00 | 14842431.78 | 0.00 | 0.00 | 0.549659E+10 | 0.00 | 2.18 |
July | 0.623054E+09 | 0.976635E+09 | 0.00 | 14537178.48 | 13653594.03 | 0.00 | 0.339916E+10 | 0.00 | 2.48 |
August | 0.506102E+09 | 0.129360E+10 | 0.00 | 14656122.25 | 15621148.96 | 0.00 | 0.320220E+10 | 0.00 | 2.83 |
September | 0.405147E+09 | 0.185683E+09 | 0.00 | 10265233.93 | 5359537.50 | 0.00 | 0.358773E+10 | 0.00 | 1.66 |
October | 0.433270E+09 | 0.454099E+09 | 0.00 | 9359779.87 | 23938143.05 | 0.00 | 0.319199E+10 | 0.00 | 1.54 |
November | 0.568136E+09 | 3634333.63 | 0.00 | 11375488.86 | 310481.92 | 0.00 | 0.611651E+10 | 0.00 | 1.56 |
December | 0.585232E+09 | 511017.02 | 0.00 | 13001591.77 | 0.00 | 0.00 | 0.611377E+10 | 0.00 | 1.53 |
Annual Sum or Average | 0.708365E+10 | 0.302375E+10 | 0.00 | 0.142631E+09 | 64303631.57 | 0.00 | 0.603253E+11 | 0.00 | 1.79 |
Minimum of Months | 0.374820E+09 | 60617.53 | 0.00 | 5570863.32 | 0.00 | 0.00 | 0.319199E+10 | 0.00 | 1.00 |
Maximum of Months | 0.124206E+10 | 0.129360E+10 | 0.00 | 18332403.08 | 23938143.05 | 0.00 | 0.814226E+10 | 0.00 | 2.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.296440E+11 | 0.00 | 0.00 | 4705132.46 | 83989440.74 | 0.136298E+10 | 0.235106E+10 | 0.00 | 0.44 |
February | 0.294298E+11 | 14883501.83 | 0.00 | 2858507.73 | 0.00 | 14088953.42 | 0.319373E+10 | 0.00 | 0.46 |
March | 0.330260E+11 | 0.00 | 0.00 | 6215451.21 | 41602765.93 | 0.592107E+09 | 0.497106E+10 | 0.00 | 0.47 |
April | 0.201956E+11 | 4239740.17 | 0.00 | 23654197.56 | 71176340.21 | 53488647.26 | 0.126865E+11 | 0.00 | 0.55 |
May | 0.172997E+11 | 40305644.95 | 0.00 | 36006031.35 | 0.00 | 0.00 | 0.195012E+11 | 0.00 | 0.62 |
June | 0.101148E+11 | 0.402326E+09 | 0.00 | 53118577.09 | 637360.14 | 0.00 | 0.217960E+11 | 0.00 | 0.78 |
July | 0.677631E+10 | 0.428406E+10 | 0.00 | 36090315.21 | 0.398289E+09 | 0.00 | 0.106465E+11 | 0.00 | 0.77 |
August | 0.726546E+10 | 0.497172E+10 | 0.00 | 28588909.60 | 0.404776E+09 | 0.00 | 0.709373E+10 | 0.00 | 0.76 |
September | 0.132481E+11 | 0.129337E+10 | 0.00 | 29307208.56 | 98796180.95 | 0.00 | 0.107091E+11 | 0.00 | 0.64 |
October | 0.143764E+11 | 0.280623E+10 | 0.00 | 20228074.03 | 0.407628E+09 | 0.00 | 0.669772E+10 | 0.00 | 0.57 |
November | 0.270714E+11 | 1177057.95 | 0.00 | 5902539.11 | 24412848.99 | 11772656.70 | 0.581094E+10 | 0.00 | 0.48 |
December | 0.295141E+11 | 1030058.92 | 0.00 | 2652955.04 | 4635176.21 | 0.299253E+09 | 0.192419E+10 | 0.00 | 0.45 |
Annual Sum or Average | 0.237962E+12 | 0.138193E+11 | 0.00 | 0.249328E+09 | 0.153594E+10 | 0.233369E+10 | 0.107382E+12 | 0.00 | 0.58 |
Minimum of Months | 0.677631E+10 | 0.00 | 0.00 | 2652955.04 | 0.00 | 0.00 | 0.192419E+10 | 0.00 | 0.44 |
Maximum of Months | 0.330260E+11 | 0.497172E+10 | 0.00 | 53118577.09 | 0.407628E+09 | 0.136298E+10 | 0.217960E+11 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.187666E+11 | 15572526.31 | 0.00 | 13292342.43 | 51511117.61 | 0.366757E+09 | 0.863205E+10 | 0.00 | 0.58 |
February | 0.174456E+11 | 14724269.41 | 0.00 | 16179195.49 | 0.00 | 11617149.09 | 0.108208E+11 | 0.00 | 0.63 |
March | 0.194824E+11 | 1698939.27 | 0.00 | 22538010.96 | 31743723.10 | 0.162711E+09 | 0.142616E+11 | 0.00 | 0.68 |
April | 0.109580E+11 | 13084584.26 | 0.00 | 50729433.28 | 52219328.93 | 14238130.97 | 0.249358E+11 | 0.00 | 0.97 |
May | 0.110936E+11 | 48239168.37 | 0.00 | 48967444.44 | 0.00 | 0.00 | 0.253128E+11 | 0.00 | 0.98 |
June | 0.722579E+10 | 0.372503E+09 | 0.00 | 61794083.83 | 180546.82 | 0.00 | 0.232318E+11 | 0.00 | 1.20 |
July | 0.439354E+10 | 0.437528E+10 | 0.00 | 54210743.30 | 0.226583E+09 | 0.00 | 0.144198E+11 | 0.00 | 1.30 |
August | 0.394735E+10 | 0.617102E+10 | 0.00 | 46941876.70 | 0.202620E+09 | 0.00 | 0.116437E+11 | 0.00 | 1.35 |
September | 0.866944E+10 | 0.118181E+10 | 0.00 | 43053132.19 | 69732417.93 | 0.00 | 0.150157E+11 | 0.00 | 1.01 |
October | 0.901842E+10 | 0.262022E+10 | 0.00 | 28817223.88 | 0.273908E+09 | 0.00 | 0.105559E+11 | 0.00 | 0.81 |
November | 0.155271E+11 | 2008316.20 | 0.00 | 19600766.24 | 18430731.74 | 0.00 | 0.126900E+11 | 0.00 | 0.64 |
December | 0.187678E+11 | 2834674.76 | 0.00 | 13149556.04 | 2198902.85 | 69436710.39 | 0.720972E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.145295E+12 | 0.148190E+11 | 0.00 | 0.419274E+09 | 0.929128E+09 | 0.624760E+09 | 0.178730E+12 | 0.00 | 0.90 |
Minimum of Months | 0.394735E+10 | 1698939.27 | 0.00 | 13149556.04 | 0.00 | 0.00 | 0.720972E+10 | 0.00 | 0.58 |
Maximum of Months | 0.194824E+11 | 0.617102E+10 | 0.00 | 61794083.83 | 0.273908E+09 | 0.366757E+09 | 0.253128E+11 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114149E+11 | 0.368501E+09 | 0.00 | 0.117224E+09 | 0.00 | 0.116000E+09 | 0.578382E+11 | 0.00 | 1.08 |
February | 0.142274E+11 | 66360531.64 | 0.00 | 78568367.45 | 0.00 | 0.00 | 0.430479E+11 | 0.00 | 0.93 |
March | 0.191991E+11 | 29531626.24 | 0.00 | 64011235.90 | 17996631.83 | 0.252687E+09 | 0.366804E+11 | 0.00 | 0.80 |
April | 0.139363E+11 | 19255171.40 | 0.00 | 68240836.71 | 61618891.07 | 0.00 | 0.327635E+11 | 0.00 | 0.86 |
May | 0.164945E+11 | 54035999.83 | 0.00 | 47568399.51 | 0.00 | 0.00 | 0.241505E+11 | 0.00 | 0.71 |
June | 0.113055E+11 | 0.479575E+09 | 0.00 | 53483762.83 | 636733.88 | 0.00 | 0.208893E+11 | 0.00 | 0.81 |
July | 0.734541E+10 | 0.512595E+10 | 0.00 | 38440438.56 | 0.394359E+09 | 0.00 | 0.105984E+11 | 0.00 | 0.84 |
August | 0.518548E+10 | 0.780671E+10 | 0.00 | 50020790.04 | 0.384223E+09 | 0.00 | 0.120713E+11 | 0.00 | 1.06 |
September | 0.783050E+10 | 0.266933E+10 | 0.00 | 87666270.44 | 75970665.84 | 0.00 | 0.287475E+11 | 0.00 | 1.14 |
October | 0.771240E+10 | 0.715044E+10 | 0.00 | 92257812.66 | 0.101834E+09 | 0.00 | 0.255310E+11 | 0.00 | 1.09 |
November | 0.961137E+10 | 60470813.81 | 0.00 | 0.118287E+09 | 1982612.87 | 0.00 | 0.583665E+11 | 0.00 | 1.15 |
December | 0.107069E+11 | 24717173.47 | 0.00 | 0.138048E+09 | 0.00 | 5166218.75 | 0.529248E+11 | 0.00 | 1.11 |
Annual Sum or Average | 0.134970E+12 | 0.238549E+11 | 0.00 | 0.953816E+09 | 0.103862E+10 | 0.373853E+09 | 0.403609E+12 | 0.00 | 0.96 |
Minimum of Months | 0.518548E+10 | 19255171.40 | 0.00 | 38440438.56 | 0.00 | 0.00 | 0.105984E+11 | 0.00 | 0.71 |
Maximum of Months | 0.191991E+11 | 0.780671E+10 | 0.00 | 0.138048E+09 | 0.394359E+09 | 0.252687E+09 | 0.583665E+11 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.210199E+11 | 65991578.71 | 0.00 | 17507314.99 | 24862043.93 | 0.246317E+09 | 0.999403E+10 | 0.00 | 0.66 |
February | 0.190155E+11 | 20298823.61 | 0.00 | 19691066.59 | 0.00 | 0.00 | 0.132966E+11 | 0.00 | 0.73 |
March | 0.206720E+11 | 0.00 | 0.00 | 28163554.70 | 35234178.24 | 44519660.11 | 0.189910E+11 | 0.00 | 0.80 |
April | 0.961625E+10 | 50383119.26 | 0.00 | 62773933.12 | 26068432.72 | 0.00 | 0.306514E+11 | 0.00 | 1.10 |
May | 0.993940E+10 | 38431515.64 | 0.00 | 62733695.52 | 0.00 | 0.00 | 0.311886E+11 | 0.00 | 1.11 |
June | 0.524263E+10 | 0.386558E+09 | 0.00 | 82395981.65 | 75948.97 | 0.00 | 0.308288E+11 | 0.00 | 1.41 |
July | 0.289599E+10 | 0.568059E+10 | 0.00 | 71435130.93 | 0.164984E+09 | 0.00 | 0.171978E+11 | 0.00 | 1.43 |
August | 0.271015E+10 | 0.631782E+10 | 0.00 | 61355295.65 | 0.194767E+09 | 0.00 | 0.137657E+11 | 0.00 | 1.49 |
September | 0.627221E+10 | 0.140472E+10 | 0.00 | 59831520.01 | 49267644.07 | 0.00 | 0.211681E+11 | 0.00 | 1.18 |
October | 0.857053E+10 | 0.306996E+10 | 0.00 | 35704531.02 | 0.199959E+09 | 0.00 | 0.117309E+11 | 0.00 | 0.91 |
November | 0.167356E+11 | 8183158.03 | 0.00 | 27627512.28 | 16255826.22 | 0.00 | 0.167293E+11 | 0.00 | 0.79 |
December | 0.195394E+11 | 4980446.29 | 0.00 | 20006772.12 | 2030953.07 | 4379672.88 | 0.100962E+11 | 0.00 | 0.68 |
Annual Sum or Average | 0.142229E+12 | 0.170479E+11 | 0.00 | 0.549226E+09 | 0.713505E+09 | 0.295217E+09 | 0.225638E+12 | 0.00 | 1.03 |
Minimum of Months | 0.271015E+10 | 0.00 | 0.00 | 17507314.99 | 0.00 | 0.00 | 0.999403E+10 | 0.00 | 0.66 |
Maximum of Months | 0.210199E+11 | 0.631782E+10 | 0.00 | 82395981.65 | 0.199959E+09 | 0.246317E+09 | 0.311886E+11 | 0.00 | 1.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.238248E+10 | 0.00 | 42131.53 | 124871.62 | 7944636.95 | 0.565583E+09 | 81739175.75 | 2054.29 | 0.44 |
February | 0.253921E+10 | 500820.89 | 0.00 | 74690.71 | 0.00 | 0.348396E+09 | 99466920.00 | 0.00 | 0.45 |
March | 0.310940E+10 | 0.00 | 0.00 | 286404.94 | 2444548.61 | 0.316625E+09 | 0.229137E+09 | 0.00 | 0.46 |
April | 0.212134E+10 | 17902.21 | 0.00 | 1805938.53 | 4247056.13 | 52632010.35 | 0.108593E+10 | 0.00 | 0.54 |
May | 0.195582E+10 | 1442580.56 | 0.00 | 2855533.01 | 0.00 | 6980182.13 | 0.166871E+10 | 0.00 | 0.60 |
June | 0.114497E+10 | 19370512.87 | 0.00 | 5092927.70 | 0.00 | 0.00 | 0.214042E+10 | 0.00 | 0.78 |
July | 0.714684E+09 | 0.370827E+09 | 0.00 | 3906515.49 | 35931061.71 | 0.00 | 0.109870E+10 | 0.00 | 0.80 |
August | 0.658185E+09 | 0.453836E+09 | 0.00 | 3346353.59 | 39246117.27 | 0.00 | 0.762144E+09 | 0.00 | 0.80 |
September | 0.138030E+10 | 96302812.91 | 0.00 | 2753805.16 | 11129766.35 | 0.00 | 0.971650E+09 | 0.00 | 0.62 |
October | 0.142226E+10 | 0.221303E+09 | 0.00 | 1499629.28 | 46852266.80 | 21776359.63 | 0.490130E+09 | 0.00 | 0.56 |
November | 0.265182E+10 | 0.00 | 0.00 | 100298.03 | 1766784.25 | 0.253219E+09 | 0.113548E+09 | 0.00 | 0.47 |
December | 0.231742E+10 | 0.00 | 0.00 | 68124.59 | 1569964.54 | 0.436576E+09 | 58609793.51 | 0.00 | 0.44 |
Annual Sum or Average | 0.223979E+11 | 0.116360E+10 | 42131.53 | 21915092.65 | 0.151132E+09 | 0.200179E+10 | 0.880019E+10 | 2054.29 | 0.58 |
Minimum of Months | 0.658185E+09 | 0.00 | 0.00 | 68124.59 | 0.00 | 0.00 | 58609793.51 | 0.00 | 0.44 |
Maximum of Months | 0.310940E+10 | 0.453836E+09 | 42131.53 | 5092927.70 | 46852266.80 | 0.565583E+09 | 0.214042E+10 | 2054.29 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184546E+10 | 302440.93 | 34101.53 | 570977.48 | 5921144.60 | 0.233351E+09 | 0.318331E+09 | 512.28 | 0.54 |
February | 0.160927E+10 | 491959.26 | 0.00 | 943393.40 | 0.00 | 0.174464E+09 | 0.630762E+09 | 0.00 | 0.57 |
March | 0.194064E+10 | 95563.05 | 0.00 | 1387982.23 | 1854634.07 | 0.149029E+09 | 0.942417E+09 | 0.00 | 0.62 |
April | 0.102720E+10 | 526726.75 | 0.00 | 4634361.54 | 2830626.38 | 19421629.60 | 0.241991E+10 | 0.00 | 0.94 |
May | 0.118028E+10 | 2087240.89 | 0.00 | 4520198.28 | 0.00 | 669972.87 | 0.238985E+10 | 0.00 | 0.95 |
June | 0.745774E+09 | 19079862.28 | 0.00 | 6399069.97 | 0.00 | 0.00 | 0.244395E+10 | 0.00 | 1.23 |
July | 0.402051E+09 | 0.394389E+09 | 0.00 | 5977625.22 | 10072444.11 | 0.00 | 0.156254E+10 | 0.00 | 1.36 |
August | 0.339080E+09 | 0.582322E+09 | 0.00 | 5395262.83 | 14385730.94 | 0.00 | 0.121761E+10 | 0.00 | 1.43 |
September | 0.822034E+09 | 96039653.87 | 0.00 | 4416295.80 | 7558627.81 | 0.00 | 0.152269E+10 | 0.00 | 1.00 |
October | 0.869559E+09 | 0.231549E+09 | 0.00 | 2487558.45 | 23835646.58 | 8186334.89 | 0.836907E+09 | 0.00 | 0.79 |
November | 0.159583E+10 | 27208.76 | 0.00 | 881720.08 | 1356835.97 | 59859794.64 | 0.737879E+09 | 0.00 | 0.58 |
December | 0.181987E+10 | 169810.85 | 0.00 | 485223.21 | 1116234.96 | 0.174738E+09 | 0.222347E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.141971E+11 | 0.132708E+10 | 34101.53 | 38099668.50 | 68931925.42 | 0.819720E+09 | 0.152452E+11 | 512.28 | 0.88 |
Minimum of Months | 0.339080E+09 | 27208.76 | 0.00 | 485223.21 | 0.00 | 0.00 | 0.222347E+09 | 0.00 | 0.54 |
Maximum of Months | 0.194064E+10 | 0.582322E+09 | 34101.53 | 6399069.97 | 23835646.58 | 0.233351E+09 | 0.244395E+10 | 512.28 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119666E+10 | 32924111.33 | 0.00 | 8599381.31 | 107428.68 | 0.150646E+09 | 0.441102E+10 | 0.00 | 0.94 |
February | 0.142540E+10 | 2416073.23 | 0.00 | 5768294.74 | 0.00 | 0.124641E+09 | 0.339466E+10 | 0.00 | 0.82 |
March | 0.204769E+10 | 1211718.87 | 0.00 | 4844177.41 | 1602426.53 | 0.187063E+09 | 0.290511E+10 | 0.00 | 0.73 |
April | 0.140394E+10 | 40043.31 | 0.00 | 6193698.06 | 4241173.16 | 37712398.24 | 0.327823E+10 | 0.00 | 0.83 |
May | 0.180695E+10 | 1925155.51 | 0.00 | 4043757.03 | 0.00 | 16702888.91 | 0.222626E+10 | 0.00 | 0.69 |
June | 0.119771E+10 | 23035470.16 | 0.00 | 5298607.33 | 0.00 | 0.00 | 0.215510E+10 | 0.00 | 0.81 |
July | 0.726987E+09 | 0.442422E+09 | 0.00 | 4408374.88 | 30743570.44 | 0.00 | 0.117978E+10 | 0.00 | 0.88 |
August | 0.507885E+09 | 0.696322E+09 | 0.00 | 5996507.40 | 34386639.10 | 0.00 | 0.129269E+10 | 0.00 | 1.12 |
September | 0.769362E+09 | 0.202217E+09 | 0.00 | 8972865.00 | 7194362.23 | 0.00 | 0.302422E+10 | 0.00 | 1.11 |
October | 0.790483E+09 | 0.603468E+09 | 0.00 | 8280679.62 | 9900631.62 | 0.00 | 0.231055E+10 | 0.00 | 1.07 |
November | 0.108761E+10 | 3080868.22 | 0.00 | 8990944.03 | 296651.72 | 20426150.80 | 0.476141E+10 | 0.00 | 1.02 |
December | 0.117113E+10 | 5627250.46 | 0.00 | 9502947.20 | 0.00 | 81735403.18 | 0.384155E+10 | 0.00 | 0.97 |
Annual Sum or Average | 0.141318E+11 | 0.201469E+10 | 0.00 | 80900234.00 | 88472883.48 | 0.618927E+09 | 0.347806E+11 | 0.00 | 0.91 |
Minimum of Months | 0.507885E+09 | 40043.31 | 0.00 | 4043757.03 | 0.00 | 0.00 | 0.117978E+10 | 0.00 | 0.69 |
Maximum of Months | 0.204769E+10 | 0.696322E+09 | 0.00 | 9502947.20 | 34386639.10 | 0.187063E+09 | 0.476141E+10 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.190202E+10 | 4449401.85 | 0.00 | 1122176.83 | 3620063.14 | 0.265295E+09 | 0.727777E+09 | 0.00 | 0.66 |
February | 0.193996E+10 | 718936.55 | 0.00 | 1357440.65 | 0.00 | 0.113835E+09 | 0.972996E+09 | 0.00 | 0.72 |
March | 0.222337E+10 | 0.00 | 0.00 | 2134678.15 | 2189198.68 | 0.136586E+09 | 0.150908E+10 | 0.00 | 0.79 |
April | 0.118699E+10 | 2366258.36 | 0.00 | 5485814.23 | 1796175.71 | 19910067.38 | 0.296192E+10 | 0.00 | 1.10 |
May | 0.128267E+10 | 1214089.08 | 0.00 | 5487796.93 | 0.00 | 1898239.56 | 0.298242E+10 | 0.00 | 1.11 |
June | 0.726052E+09 | 17547750.09 | 0.00 | 8091743.12 | 0.00 | 0.00 | 0.315047E+10 | 0.00 | 1.43 |
July | 0.366863E+09 | 0.491687E+09 | 0.00 | 7771995.55 | 21917645.17 | 0.00 | 0.181400E+10 | 0.00 | 1.50 |
August | 0.316788E+09 | 0.567577E+09 | 0.00 | 6711862.56 | 21192324.16 | 0.00 | 0.139747E+10 | 0.00 | 1.57 |
September | 0.710180E+09 | 0.104509E+09 | 0.00 | 5753856.40 | 6161173.92 | 0.00 | 0.212784E+10 | 0.00 | 1.17 |
October | 0.978228E+09 | 0.241101E+09 | 0.00 | 3050882.62 | 29315643.05 | 0.00 | 0.100543E+10 | 0.00 | 0.92 |
November | 0.189184E+10 | 193059.95 | 0.00 | 1908489.24 | 1405350.06 | 46832167.89 | 0.119245E+10 | 0.00 | 0.76 |
December | 0.186298E+10 | 184512.35 | 0.00 | 1260733.95 | 1289457.22 | 0.163144E+09 | 0.669036E+09 | 0.00 | 0.67 |
Annual Sum or Average | 0.153879E+11 | 0.143155E+10 | 0.00 | 50137470.22 | 88887031.11 | 0.747500E+09 | 0.205109E+11 | 0.00 | 1.03 |
Minimum of Months | 0.316788E+09 | 0.00 | 0.00 | 1122176.83 | 0.00 | 0.00 | 0.669036E+09 | 0.00 | 0.66 |
Maximum of Months | 0.222337E+10 | 0.567577E+09 | 0.00 | 8091743.12 | 29315643.05 | 0.265295E+09 | 0.315047E+10 | 0.00 | 1.57 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3507957.92 | 0.00 | 0.00 | 0.290020E+09 | 0.00 | 0.24 |
February | 0.00 | 0.00 | 0.00 | 7267803.81 | 0.00 | 0.00 | 0.252897E+09 | 0.00 | 0.25 |
March | 0.00 | 61205.09 | 0.00 | 13213267.00 | 0.00 | 0.00 | 0.292417E+09 | 0.00 | 0.27 |
April | 0.00 | 261679.32 | 0.00 | 16398918.49 | 0.00 | 0.00 | 0.165455E+09 | 0.00 | 0.25 |
May | 0.00 | 0.00 | 0.00 | 3766107.60 | 0.00 | 0.00 | 0.209890E+09 | 0.00 | 0.26 |
June | 0.00 | 7895012.27 | 0.00 | 7292235.53 | 0.00 | 0.00 | 97552944.47 | 0.00 | 0.26 |
July | 0.00 | 57842862.83 | 0.00 | 4724394.58 | 0.00 | 0.00 | 19589822.40 | 0.00 | 0.24 |
August | 0.00 | 76543241.23 | 0.00 | 4750499.45 | 0.00 | 0.00 | 13410685.87 | 0.00 | 0.27 |
September | 0.00 | 12522673.82 | 0.00 | 2898982.51 | 0.00 | 0.00 | 78490217.77 | 0.00 | 0.25 |
October | 0.00 | 20766795.51 | 0.00 | 6133112.44 | 0.00 | 0.00 | 0.126863E+09 | 0.00 | 0.25 |
November | 0.00 | 0.00 | 0.00 | 11921155.38 | 0.00 | 0.00 | 0.239918E+09 | 0.00 | 0.25 |
December | 0.00 | 0.00 | 0.00 | 16668912.90 | 0.00 | 0.00 | 0.270658E+09 | 0.00 | 0.24 |
Annual Sum or Average | 0.00 | 0.175893E+09 | 0.00 | 98543347.60 | 0.00 | 0.00 | 0.205716E+10 | 0.00 | 0.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2898982.51 | 0.00 | 0.00 | 13410685.87 | 0.00 | 0.24 |
Maximum of Months | 0.00 | 76543241.23 | 0.00 | 16668912.90 | 0.00 | 0.00 | 0.292417E+09 | 0.00 | 0.27 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 26136549.03 | 0.00 | 0.00 | 0.292054E+10 | 0.00 | 0.24 |
February | 0.00 | 0.00 | 0.00 | 63299959.98 | 0.00 | 0.00 | 0.254397E+10 | 0.00 | 0.25 |
March | 0.00 | 552773.45 | 0.00 | 0.119537E+09 | 0.00 | 0.00 | 0.293757E+10 | 0.00 | 0.27 |
April | 0.00 | 2585820.86 | 0.00 | 0.153903E+09 | 0.00 | 0.00 | 0.166382E+10 | 0.00 | 0.25 |
May | 0.00 | 0.00 | 0.00 | 32463227.15 | 0.00 | 0.00 | 0.212128E+10 | 0.00 | 0.26 |
June | 0.00 | 76896498.87 | 0.00 | 67925838.10 | 0.00 | 0.00 | 0.986721E+09 | 0.00 | 0.26 |
July | 0.00 | 0.574744E+09 | 0.00 | 44793556.62 | 0.00 | 0.00 | 0.199283E+09 | 0.00 | 0.24 |
August | 0.00 | 0.763250E+09 | 0.00 | 45403736.74 | 0.00 | 0.00 | 0.136250E+09 | 0.00 | 0.27 |
September | 0.00 | 0.117433E+09 | 0.00 | 25789482.77 | 0.00 | 0.00 | 0.805862E+09 | 0.00 | 0.25 |
October | 0.00 | 0.204482E+09 | 0.00 | 55958655.67 | 0.00 | 0.00 | 0.127572E+10 | 0.00 | 0.25 |
November | 0.00 | 0.00 | 0.00 | 0.108918E+09 | 0.00 | 0.00 | 0.240926E+10 | 0.00 | 0.25 |
December | 0.00 | 0.00 | 0.00 | 0.153285E+09 | 0.00 | 0.00 | 0.271672E+10 | 0.00 | 0.24 |
Annual Sum or Average | 0.00 | 0.173994E+10 | 0.00 | 0.897414E+09 | 0.00 | 0.00 | 0.207170E+11 | 0.00 | 0.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 25789482.77 | 0.00 | 0.00 | 0.136250E+09 | 0.00 | 0.24 |
Maximum of Months | 0.00 | 0.763250E+09 | 0.00 | 0.153903E+09 | 0.00 | 0.00 | 0.293757E+10 | 0.00 | 0.27 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 33966414.01 | 0.00 | 0.00 | 1803447.22 | 0.00 | 0.00 | 0.262038E+09 | 0.00 | 0.24 |
February | 0.00 | 0.00 | 0.00 | 5638179.20 | 0.00 | 0.00 | 0.256002E+09 | 0.00 | 0.25 |
March | 0.00 | 54748.07 | 0.00 | 11234107.74 | 0.00 | 0.00 | 0.295019E+09 | 0.00 | 0.27 |
April | 0.00 | 256641.10 | 0.00 | 15103204.98 | 0.00 | 0.00 | 0.166937E+09 | 0.00 | 0.25 |
May | 0.00 | 0.00 | 0.00 | 2984954.90 | 0.00 | 0.00 | 0.213351E+09 | 0.00 | 0.26 |
June | 0.00 | 7727459.16 | 0.00 | 6700450.78 | 0.00 | 0.00 | 99007186.87 | 0.00 | 0.26 |
July | 0.00 | 57436961.07 | 0.00 | 4466778.11 | 0.00 | 0.00 | 20009578.13 | 0.00 | 0.24 |
August | 0.00 | 76203175.21 | 0.00 | 4522047.30 | 0.00 | 0.00 | 13722913.21 | 0.00 | 0.27 |
September | 0.00 | 11580469.99 | 0.00 | 2437654.84 | 0.00 | 0.00 | 81255727.19 | 0.00 | 0.25 |
October | 0.00 | 20393807.37 | 0.00 | 5314467.54 | 0.00 | 0.00 | 0.128118E+09 | 0.00 | 0.25 |
November | 0.00 | 0.00 | 0.00 | 10274788.45 | 0.00 | 0.00 | 0.241935E+09 | 0.00 | 0.25 |
December | 0.00 | 0.00 | 0.00 | 14534937.56 | 0.00 | 0.00 | 0.272704E+09 | 0.00 | 0.24 |
Annual Sum or Average | 33966414.01 | 0.173653E+09 | 0.00 | 85015018.63 | 0.00 | 0.00 | 0.205010E+10 | 0.00 | 0.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1803447.22 | 0.00 | 0.00 | 13722913.21 | 0.00 | 0.24 |
Maximum of Months | 33966414.01 | 76203175.21 | 0.00 | 15103204.98 | 0.00 | 0.00 | 0.295019E+09 | 0.00 | 0.27 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:07:39
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.337600E+12 | 0.901334E+10 | 0.00 | 0.177467E+13 | 0.287983E+12 |
February | 0.410826E+12 | 0.106948E+11 | 0.00 | 0.173347E+13 | 0.252804E+12 |
March | 0.567292E+12 | 0.110523E+11 | 0.00 | 0.183935E+13 | 0.356213E+12 |
April | 0.714187E+12 | 0.670522E+10 | 0.00 | 0.173422E+13 | 0.605254E+12 |
May | 0.751135E+12 | 0.805677E+10 | 0.00 | 0.181509E+13 | 0.407756E+12 |
June | 0.733723E+12 | 0.424173E+10 | 0.00 | 0.153311E+13 | 0.740502E+12 |
July | 0.784841E+12 | 0.207873E+10 | 0.00 | 0.102415E+13 | 0.126361E+13 |
August | 0.732773E+12 | 0.224372E+10 | 0.00 | 0.821239E+12 | 0.151662E+13 |
September | 0.572417E+12 | 0.354407E+10 | 0.00 | 0.139029E+13 | 0.766933E+12 |
October | 0.409123E+12 | 0.580293E+10 | 0.00 | 0.135681E+13 | 0.989687E+12 |
November | 0.368107E+12 | 0.908134E+10 | 0.00 | 0.192274E+13 | 0.456414E+12 |
December | 0.307673E+12 | 0.100789E+11 | 0.00 | 0.191655E+13 | 0.562291E+12 |
Annual Sum or Average | 0.668970E+13 | 0.825938E+11 | 0.00 | 0.188617E+14 | 0.820607E+13 |
Minimum of Months | 0.307673E+12 | 0.207873E+10 | 0.00 | 0.821239E+12 | 0.252804E+12 |
Maximum of Months | 0.784841E+12 | 0.110523E+11 | 0.00 | 0.192274E+13 | 0.151662E+13 |