Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:07

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880

Simulation Timestamp: 2023-10-16 09:07:54


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 33412.14 721.33 721.33
Net Site Energy 33412.14 721.33 721.33
Total Source Energy 89221.75 1926.19 1926.19
Net Source Energy 89221.75 1926.19 1926.19


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 82.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 2459.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7190.82 0.00 0.00
Interior Lighting 2023.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 325.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 3333.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 915.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 978.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 770.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10503.98
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 61.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 595.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 25543.31 678.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7190.82 0.00 12784.15
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 82.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 2459.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7190.82 0.00 0.00
Interior Lighting LightsWired 2023.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 325.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5334.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 54.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ComputerHVAC 1424.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 915.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 978.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 770.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10503.98
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 61.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 595.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 82.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 2459.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7190.82 0.00 0.00
Interior Lighting GENERAL 2023.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 325.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 3333.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 915.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 978.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 770.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10503.98
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 61.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 595.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 110.62 14.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 155.24 0.00 0.28
Other 390.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 551.45 14.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 155.24 0.00 0.28


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 50.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 110.62 14.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 155.24 0.00 0.28
Other 390.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 551.45 14.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 155.24 0.00 0.28


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 25543.312 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 25543.312 100.00
     
Total On-Site and Utility Electric Sources 25543.312 100.00
Total Electricity End Uses 25543.312 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 2682.53 99.78
Air to Air Heat Recovery for Heating 5.99 0.22
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 2688.52 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 12784.15 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 12784.15 100.00
Total Water End Uses 12784.15 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.67
Time Setpoint Not Met During Occupied Cooling 175.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 5943.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EnergyConsumptionDistrictHeatingCoolingMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:07
RunPeriod RUNPERIOD 1
Weather File Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Latitude [deg] 27.85
Longitude [deg] -82.5
Elevation [m] 8.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 5.8895 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 5.8895 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 5.8895 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 5.8895 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 5.8895 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 5.8895 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 8.8011 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 8.8011 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 8.8011 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 5.8895 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 5.9168 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 5.9168 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 5.8895 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 5.8895 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 5.8895 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 5.8895 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 5.8895 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 5.8895 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 5.8895 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 5.8895 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 5.8895 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 5.8895 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 5.8895 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 5.8895 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 5.8895 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 5.8895 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 5.8895 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 5.8895 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 8.8011 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 8.8011 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 8.8011 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 5.8895 18.58 484.4232  
Total 46320.38             5.9168 9.29 17.8789  
Conditioned Total 46320.38             5.9168 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 1.8190 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] District Heating [W] Water [m3/s]
Time of Peak 30-AUG-15:50 06-FEB-06:10 - - - - - - - - 21-AUG-13:00 31-MAY-23:40 30-AUG-15:50
Heating 0.00 423881.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.56 0.00
Cooling 279391.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370154.94 0.00 0.00
Interior Lighting 171235.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 778371.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 154937.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 90954.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 67029.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 55581.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 5695.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1603116.60 429576.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370154.94 13.56 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] District Heating [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.56 0.00
  Boiler 0.00 423881.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 279391.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370154.94 0.00 0.00
Interior Lighting LightsWired 171235.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 3372.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ComputerHVAC 72130.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 263.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 90954.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 67029.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 55581.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 5695.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 89.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 7788.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7591.11 0.00
Interior Lighting 6407.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1029.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 46480.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 10555.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2900.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 3098.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 2439.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 195.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 645.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 80895.67 734.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7591.11 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 1.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 168.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 163.88 0.00
Interior Lighting 138.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 22.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 227.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 62.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 66.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 52.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 4.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 13.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1746.44 15.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 163.88 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 1.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 168.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 163.88 0.00
Interior Lighting 138.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 22.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 227.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 62.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 66.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 52.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 4.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 13.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1746.44 15.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 163.88 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 5.04
DATACENTER_BOT_ZN_6 DIRECT AIR 0.458462
DATACENTER_MID_ZN_6 DIRECT AIR 4.36
DATACENTER_TOP_ZN_6 DIRECT AIR 0.445033
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 5.28 0.360514 0.352000 1.86 0.961371 0.500000 0.001057 0.000163 1.86 12.80 0.008000
CORE_MID VAV BOX COMPONENT 49.21 0.386535 0.367000 18.06 1.00 0.500000 0.000986 0.003081 18.06 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 4.89 0.389051 0.379000 1.85 1.00 0.500000 0.000979 0.000526 1.85 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.844600 0.282762 0.276000 0.233110 0.754031 0.500000 0.001347 0.000043 0.233110 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 0.883795 0.174141 0.200000 0.176759 0.464376 0.500000 0.002188 0.000033 0.176759 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.03 0.231743 0.226000 0.232907 0.617982 0.500000 0.001644 0.000057 0.232907 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.15 0.134353 0.200000 0.229106 0.358273 0.500000 0.002836 0.000025 0.229106 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 7.69 0.310727 0.295000 2.27 0.828607 0.500000 0.001226 0.001146 3.91 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 9.04 0.170291 0.200000 1.81 0.454108 0.500000 0.002237 0.000765 2.61 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 9.59 0.248947 0.236000 2.26 0.663858 0.500000 0.001530 0.001140 3.88 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 9.53 0.161444 0.200000 1.91 0.430518 0.500000 0.002360 0.000665 2.27 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 0.889037 0.268628 0.261000 0.232039 0.716342 0.500000 0.001418 0.000159 0.541966 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 0.922741 0.166791 0.200000 0.184548 0.444777 0.500000 0.002284 0.000105 0.357885 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.07 0.222166 0.216000 0.232198 0.592442 0.500000 0.001715 0.000158 0.539261 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.04 0.148542 0.200000 0.207220 0.396113 0.500000 0.002565 0.000097 0.330987 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 18683.49 0.000163 376.64
CORE_MID VAV BOX REHEAT COIL 352123.36 0.003081 7826.57
CORE_TOP VAV BOX REHEAT COIL 60079.97 0.000526 1561.78
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 4910.08 0.000043 111.05
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 3759.73 0.000033 85.23
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 6519.25 0.000057 160.03
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 2807.51 0.000025 57.84
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 131020.14 0.001146 3457.77
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 87474.62 0.000765 2308.44
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 130259.72 0.001140 3437.73
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 76054.83 0.000665 2007.49
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 18167.21 0.000159 479.27
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 11995.90 0.000105 316.45
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 18076.76 0.000158 476.88
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 11096.38 0.000097 292.75
VAV_BOT WITH REHEAT HEATING COIL 25001.60 0.000219 432.11
VAV_MID WITH REHEAT HEATING COIL 230102.43 0.002013 3976.96
VAV_TOP WITH REHEAT HEATING COIL 24843.27 0.000217 429.38
CAV_BAS HEATING COIL 237002.75 0.002073 5383.16
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:IdealLoadsAirSystem

Design Size Maximum Heating Air Flow Rate [m3/s] Design Size Maximum Cooling Air Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT 0.338402 21.26
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 4.59 2.73 9.18 2.73 8.41 8.41 0.300000 0.324641 8.41
VAV_MID WITH REHEAT 42.53 26.30 85.06 26.30 77.37 77.37 0.300000 0.340000 77.37
VAV_TOP WITH REHEAT 4.41 2.71 8.81 3.53 8.35 8.35 0.300000 0.422183 8.35
CAV_BAS 5.04 5.04 5.04 5.04 5.04 5.04 1.00 1.00 5.04
AIRLOOP DATACENTER BOT 0.458462 0.458462 0.458462 0.458462 0.458462 0.458462 1.00 1.00 0.458462
AIRLOOP DATACENTER MID 4.36 4.36 4.36 4.36 4.36 4.36 1.00 1.00 4.36
AIRLOOP DATACENTER TOP 0.445033 0.445033 0.445033 0.445033 0.445033 0.445033 1.00 1.00 0.445033
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 8.41  
VAV_MID WITH REHEAT_OA_CONTROLLER 77.37  
VAV_TOP WITH REHEAT_OA_CONTROLLER 8.35  
CAV_BAS_OA_CONTROLLER 5.04  
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.458462 0.015633
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.36 0.156328
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.445033 0.015633
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT OA HEAT RECOVERY 2.54
VAV_MID WITH REHEAT OA HEAT RECOVERY 25.38
VAV_TOP WITH REHEAT OA HEAT RECOVERY 2.54
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 27.14 6.67 11.05 0.011324 0.008500 238952.87 0.010166 8.41
VAV_MID WITH REHEAT COOLING COIL 27.56 6.67 11.05 0.011699 0.008500 2328648.57 0.099066 77.37
VAV_TOP WITH REHEAT COOLING COIL 27.02 6.67 11.05 0.011242 0.008500 234131.85 0.009961 8.35
CAV_BAS COOLING COIL 25.09 6.67 11.42 0.010799 0.008500 120036.58 0.005107 5.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 8.41
VAV_MID WITH REHEAT FAN 77.37
VAV_TOP WITH REHEAT FAN 8.35
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.010166 0.000047
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000219  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.099066 0.000005
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.002013  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.009961 0.000048
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000217  
CAV_BAS_COOLC_CONTROLLER 0.005107 0.000093
CAV_BAS_HEATC_CONTROLLER 0.002073  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 5.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BOT COOLING COIL 0.458462 9361.61 6717.53 0.000229
AIRLOOP DATACENTER MID COOLING COIL 4.36 89307.37 63990.84 0.002187
AIRLOOP DATACENTER TOP COOLING COIL 0.445033 9105.26 6526.80 0.000223
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.458462 0.458462 0.458462 0.458462 9361.61 9361.61 669.07 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.36 4.36 4.36 4.36 89307.37 89307.37 6690.69 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.445033 0.445033 0.445033 0.445033 9105.26 9105.26 669.07 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BOT SUPPLY FAN 0.458462
AIRLOOP DATACENTER MID SUPPLY FAN 4.36
AIRLOOP DATACENTER TOP SUPPLY FAN 0.445033
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BOT HEATING COIL 0.458462 9361.61 0.000229
AIRLOOP DATACENTER MID HEATING COIL 4.36 89307.37 0.002187
AIRLOOP DATACENTER TOP HEATING COIL 0.445033 9105.26 0.000223
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 669.07
AIRLOOP DATACENTER MID_SUPPHEATCOIL 6690.69
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 669.07
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.124299 25359.79  
HEATSYS1 PUMP 0.012685 3782.36 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.124299 14.92
HEATSYS1 0.012685 1.52
COOLSYS1_SUPPLY 0.124299 14.92
SINGLE WATER PLANT LOOP 0.002639 0.316726
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.124299 0.124299 521744.62 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 1449979.01 1449979.01 0.012685
CENTRAL BOILER 108720.00 108720.00 0.002639
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.124299 17557.44
PLANT CIRC PUMP 0.002639 666.51
SWHSYS1 PUMP 0.000440 5.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.124299 0.062640 1476033.41 1482993.02 0.073388
COOLSYS1 CHILLER2 0.124299 0.062640 1476033.41 1482993.02 0.073388
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.002639 35644.39 21899.84 17822.20 1996.20 5888.66
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.146776 17.61
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.146776 43767.95
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 56.77 1759550.91 11.35 219943.86
TOWERWATERSYS COOLTOWER 2 56.77 1759550.91 11.35 219943.86
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 45
WSHPPLANT OPERATION SCHEME 0.076228
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 24.20 18.90 15.70 13.60 15.50 17.10 21.20 26.90 27.60 27.90 27.40 26.20


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Tampa-MacDill AFB FL USA TMY3 WMO#=747880 27.85 -82.52 -5.00 8.00 101229 1.2032


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 21.85 14.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 105.88 86.92 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 105.88 86.92 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 5.889 4.842 0.000 0.000 0.000 0.000 10.731 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 5.889 8.070 0.000 0.000 0.000 0.000 13.959 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 8.801 215.299 0.000 0.000 0.000 0.000 224.100 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 8.801 215.299 0.000 0.000 0.000 0.000 224.100 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 8.801 215.299 0.000 0.000 0.000 0.000 224.100 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 5.889 484.423 0.000 0.000 0.000 0.000 490.313 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 16369.361 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16369.361
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 14700.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14700.837
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 14700.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14700.837
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 14700.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 14700.837
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 1845.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.837
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 1845.877 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.877
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 1845.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.837
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 1845.877 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.877
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 1845.837 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.837
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 1845.877 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1845.877
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1189.527 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1189.527
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 4615.459 5.889 109.419 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4615.459
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 318.624 8.801 163.514 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 318.624
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 318.624 8.801 163.514 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 318.624
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 318.624 8.801 163.514 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 318.624


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.743 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.656 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 2.135 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.4064
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.4365
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.3009
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 0.9868
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 0.9868
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
47 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
48 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
49 0 21.361010 0.87247630E-01 5.4456762  
50 9 0.76055735E-15 0.55973061E-16 -0.11090261E-09 -0.43371185E-17
51 8 0.16390423E-07 0.22068143E-12 0.31740643E-03 -0.18636477E-09
52 7 -0.10429999E-01 0.12271718E-07 -0.20474149E-01 0.11859286E-03
53 6 0.35611320 0.43955117E-05 0.42991281 -0.41673803E-02
54 5 -4.7098961 0.16827687E-03 -4.1162358 0.57223947E-01
55 4 30.875684 0.14076848E-02 20.167480 -0.39388153
56 3 -106.69740 0.31291265E-02 -53.106522 1.4497707
57 2 192.63914 0.17911574E-02 75.570394 -2.8293896
58 1 -169.50392 0.19431750E-03 -54.592911 2.7164834
59 0 57.057407 0.11257899E-05 15.674734  
60 9 0.11474244E-14 0.54197419E-16 -0.11508650E-09 -0.49945851E-17
61 8 0.16984416E-07 0.21156325E-12 0.32425024E-03 -0.19311866E-09
62 7 -0.10636353E-01 0.11664670E-07 -0.20772028E-01 0.12093918E-03
63 6 0.36172330 0.41637772E-05 0.43474562 -0.42335086E-02
64 5 -4.7646824 0.15893927E-03 -4.1535939 0.57903236E-01
65 4 31.118254 0.13261305E-02 20.314042 -0.39710182
66 3 -107.21418 0.29411649E-02 -53.396504 1.4572354
67 2 193.15212 0.16802168E-02 75.835339 -2.8375342
68 1 -169.69371 0.18194848E-03 -54.668081 2.7198097
69 0 57.057407 0.10520719E-05 15.660794  
70 9 0.66246833E-15 0.57738042E-16 -0.92036509E-10 -0.27018983E-17
71 8 0.13701644E-07 0.25726543E-12 0.28527343E-03 -0.15579243E-09
72 7 -0.94571194E-02 0.14940887E-07 -0.19068097E-01 0.10753086E-03
73 6 0.32965778 0.54453531E-05 0.40701455 -0.38555430E-02
74 5 -4.4514676 0.21157254E-03 -3.9387765 0.54019785E-01
75 4 29.731016 0.17930056E-02 19.470280 -0.37868589
76 3 -104.25747 0.40308508E-02 -51.726693 1.4145289
77 2 190.21562 0.23301583E-02 74.311741 -2.7909129
78 1 -168.60668 0.25508611E-03 -54.239505 2.7007581
79 0 57.057407 0.14924561E-05 15.743350  
80 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
81 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
82 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
83 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
84 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
85 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
86 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
87 0 1.0055995 0.48413807E-04 60.838472  
88 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
89 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
90 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
91 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
92 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
93 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
94 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
95 0 1.0055995 0.48413807E-04 60.838472  
96 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
97 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
98 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
99 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
100 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
101 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
102 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
103 0 1.0055995 0.48413807E-04 60.838472  
104 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
105 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
106 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
107 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
108 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
109 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
110 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
111 0 1.0055995 0.48413807E-04 60.838472  
112 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
113 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
114 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
115 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
116 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
117 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
118 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
119 0 1.0055995 0.48413807E-04 60.838472  
120 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
121 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
122 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
123 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
124 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
125 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
126 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
127 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.4547_SHGC_EAST_0.25 35 1 VerySmooth 2.584 2.584 1.000 0.251    
2 WINDOW_U_0.4547_SHGC_SOUTH_0.25 36 1 VerySmooth 2.584 2.584 1.000 0.251    
3 WINDOW_U_0.4547_SHGC_WEST_0.25 37 1 VerySmooth 2.584 2.584 1.000 0.251    
4 WINDOW_U_0.4547_SHGC_NORTH_0.25 38 1 VerySmooth 2.584 2.584 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   2.60743E-002 0.16139 0.61671 0.61671 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.12075 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   2.60743E-002 0.16139 0.61671 0.61671 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.12075 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   2.60743E-002 0.16139 0.61671 0.61671 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.12075 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   2.60743E-002 0.16139 0.61671 0.61671 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.12075 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.496 7.5104E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 2.856E-002 9.114E-005 1.371E-004 0.120 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 1.904E-002 9.429E-005 1.384E-004 0.124 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 2.856E-002 9.114E-005 1.371E-004 0.120 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 1.904E-002 9.429E-005 1.384E-004 0.124 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 2.856E-002 9.114E-005 1.424E-004 0.120 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 1.904E-002 9.429E-005 1.424E-004 0.124 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 2.856E-002 9.114E-005 1.424E-004 0.120 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 1.904E-002 9.429E-005 1.424E-004 0.124 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 2.856E-002 9.114E-005 1.424E-004 0.120 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 1.904E-002 9.429E-005 1.424E-004 0.124 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 2.856E-002 9.114E-005 1.424E-004 0.120 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 1.904E-002 9.429E-005 1.424E-004 0.124 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 4.231E-002 1.187E-005 1.424E-004 3.506E-002 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 4.231E-002 1.187E-005 1.424E-004 3.506E-002 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 4.231E-002 1.187E-005 1.096E-005 3.506E-002 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6254E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.6265E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7661E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7670E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1309E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.1315E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2447E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2452E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6512E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7229E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7871E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8468E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1472E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.1952E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2574E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2891E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.2727E-002
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0291E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.0494E-002
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.2035E-002
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.9708E-002
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2098E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6042E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.1095E-003
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6579E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7555E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7943E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8820E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1538E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2204E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2577E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2900E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6253E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.6267E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7661E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7672E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1309E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.1317E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2447E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2451E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.8368E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.9662E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.7256E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.8595E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.5577E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.6254E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.1302E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1521E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.4075E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.6441E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.2729E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.5117E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.4408E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.3988E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6787E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 9.9865E-003
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.8074E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.8584E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6892E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.7267E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.5378E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.5542E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.1303E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1525E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2173E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2185E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0474E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0484E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.3115E-004
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.3188E-004
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2447E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2452E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2446E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3113E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0699E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1233E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.4925E-004
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.8862E-004
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2577E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2900E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8942E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0694E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4825E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 8.1954E-003
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4675E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 5.8147E-003
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6042E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.1067E-003
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2422E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3084E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0669E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1173E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.4412E-004
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.7295E-004
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2574E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2891E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2172E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2184E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0473E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0482E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.3105E-004
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.3158E-004
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2447E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2451E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.3332E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.3869E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1155E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1543E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.0937E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1081E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1303E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1525E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.4812E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.2955E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1647E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.0967E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.5251E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.0492E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.6787E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 9.9865E-003
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.3553E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.4510E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1434E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.2365E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1120E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1695E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1302E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1521E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 7.3410E-002
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 4.1344E-002
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 7.9692E-002
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 4.3683E-002
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 6.3222E-002
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 3.1272E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 3.0133E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 1.4574E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.9035E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.2699E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.7576E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.1160E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.9026E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.9643E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.0820E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.4729E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.2861E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.5883E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 1.8361E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.2694E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 1.8134E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 9.9391E-003
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.0133E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.4571E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 2.8977E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.8133E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 2.5522E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.5701E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 2.9157E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.5175E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.0820E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.4729E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 7.3413E-002
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 4.1409E-002
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 7.9711E-002
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 4.3759E-002
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 6.3264E-002
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 3.1337E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 3.0168E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 1.4602E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.9027E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.2722E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.7578E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.1183E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.9047E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.9678E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.0854E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.4757E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.2836E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.5890E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 1.8344E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.2700E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 1.8144E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 9.9535E-003
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.0168E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.4599E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 2.8960E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.8147E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 2.5513E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.5714E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 2.9171E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.5200E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.0854E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.4757E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 69955.87436 69955.87436 5.03877 5.03877 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 28.05400 1.65254E-002 2779.42662 149.60210 1.20019 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20019   00:10:00 4.60000 5.25715E-003 2779.42662 149.60210 1.20019 0.00000
3 CORE_BOTTOM Cooling 73252.66161 73252.66161 5.27592 5.27592 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 28.05400 1.65254E-002 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782   00:10:00 4.60000 5.25715E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 683437.97367 683437.97367 49.20754 49.20754 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 28.05400 1.65254E-002 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 170440.12056 170440.12056 7.13096 10.77825 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 67903.33379 67903.33379 4.88893 4.88893 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 28.05400 1.65254E-002 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 41438.92454 41438.92454 1.75640 1.75640 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 11614.98554 11614.98554 0.84460 0.84460 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 33.90000 1.65364E-002 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 2566.48423 2566.48423 0.10808 0.13533 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 12154.06691 12154.06691 0.88380 0.88380 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 30.22650 1.65295E-002 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 1982.54847 1982.54847 8.34813E-002 8.72129E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 14172.36861 14172.36861 1.03056 1.03056 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 33.76833 1.65361E-002 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 4177.18845 4177.18845 0.17668 0.17668 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 15753.57315 15753.57315 1.14553 1.14553 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 32.79400 1.65343E-002 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 505.54203 505.54203 2.15499E-002 8.72129E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 105694.40981 105694.40981 7.68585 7.68585 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 33.90000 1.65364E-002 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 91744.64662 91744.64662 3.90527 3.90527 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 124287.04513 124287.04513 9.03779 9.03779 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 30.67417 1.65303E-002 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 61249.47875 61249.47875 2.60761 2.60761 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 131927.68353 131927.68353 9.59345 9.59345 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 33.83417 1.65363E-002 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 91213.06785 91213.06785 3.88253 3.88253 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 131097.42303 131097.42303 9.53302 9.53302 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 32.66233 1.65340E-002 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 53266.05295 53266.05295 2.26616 2.26616 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 12225.81809 12225.81809 0.88904 0.88904 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 33.74200 1.65361E-002 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 12715.87243 12715.87243 0.54197 0.54197 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 12689.37376 12689.37376 0.92274 0.92274 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 30.89800 1.65307E-002 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 8396.11741 8396.11741 0.35789 0.35789 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 14783.01866 14783.01866 1.07499 1.07499 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 33.90000 1.65364E-002 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 12652.64398 12652.64398 0.53926 0.53926 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 14248.32292 14248.32292 1.03610 1.03610 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 32.79400 1.65343E-002 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 7767.30619 7767.30619 0.33099 0.33099 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 7993.56845 7993.56845 0.45846 0.45846 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 31.21400 1.65313E-002 36.20274 1.94861 1.56328E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56328E-002   00:10:00 4.60000 5.25715E-003 36.20274 1.94861 1.56328E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 76046.43022 76046.43022 4.36160 4.36160 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 31.21400 1.65313E-002 36.20274 1.94861 0.15633 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15633   00:10:00 4.60000 5.25715E-003 36.20274 1.94861 0.15633 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 7759.38259 7759.38259 0.44503 0.44503 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 31.21400 1.65313E-002 36.20274 1.94861 1.56328E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56328E-002   00:10:00 4.60000 5.25715E-003 36.20274 1.94861 1.56328E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 370763.86227 370763.86227 21.26430 21.26430 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:00:00 26.71100 1.65229E-002 783.67941 42.18139 0.33840 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33840   00:10:00 4.60000 5.25715E-003 783.67941 42.18139 0.33840 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 138768.59 8.40624 8.40624 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 15507.95 1.56426 1.56426 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1258702.92 77.36691 77.36691 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 232380.05 23.43981 23.43981 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00
5 VAV_TOP WITH REHEAT Cooling Sensible 142940.18 8.35301 8.35301 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 25147.62 3.52650 3.52650 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 11:20:00
7 CAV_BAS Cooling Sensible 74623.12 5.03877 5.03877 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
8 CAV_BAS Heating Sensible 51367.02 1.20019 1.20019 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BOT Cooling Sensible 7949.64 0.45846 0.45846 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
10 AIRLOOP DATACENTER BOT Heating Sensible 669.07 1.56328E-002 1.56328E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER MID Cooling Sensible 75667.29 4.36160 4.36160 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
12 AIRLOOP DATACENTER MID Heating Sensible 6690.69 0.15633 0.15633 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER TOP Cooling Sensible 7721.92 0.44503 0.44503 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
14 AIRLOOP DATACENTER TOP Heating Sensible 669.07 1.56328E-002 1.56328E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.03877
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.27592
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.36051
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.35200
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.85712
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.96137
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.05682E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.63451E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.85712
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18683.49429
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.63451E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 376.64458
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 49.20754
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.38653
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.36700
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 18.05917
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.85680E-004
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.08053E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 18.05917
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 352123.36454
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.08053E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7826.57115
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.88893
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.38905
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.37900
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.85290
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.79306E-004
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.25606E-004
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.85290
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 60079.96777
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.25606E-004
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1561.78031
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.84460
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.28276
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.27600
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23311
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.75403
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.34742E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.29555E-005
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.23311
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4910.07813
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.29555E-005
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 111.05419
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.88380
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17414
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.17676
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.46438
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.18788E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.28918E-005
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.17676
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3759.73242
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.28918E-005
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 85.23488
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.03056
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.23174
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22600
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23291
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.61798
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.64406E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.70333E-005
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.23291
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6519.25172
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.70333E-005
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 160.02588
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.14553
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13435
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.22911
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.35827
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.83582E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.45613E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.22911
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2807.50591
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.45613E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 57.83770
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 7.68585
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.31073
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.29500
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.26733
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.82861
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.22615E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.14622E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.90527
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 131020.13908
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.14622E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3457.77147
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.03779
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17029
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.80756
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.45411
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.23735E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.65266E-004
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.60761
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 87474.61699
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.65266E-004
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2308.44085
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.59345
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24895
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.23600
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.26405
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.66386
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.53045E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.13957E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.88253
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 130259.72320
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.13957E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3437.73317
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.53302
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16144
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.90660
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.43052
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.35995E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.65361E-004
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.26616
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 76054.83060
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.65361E-004
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2007.48863
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.88904
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.26863
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.26100
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23204
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.71634
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.41832E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.58935E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.54197
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18167.21160
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.58935E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 479.26582
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.92274
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16679
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.18455
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.44478
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.28429E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.04945E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.35789
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11995.90295
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.04945E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 316.45269
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.07499
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22217
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.21600
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23220
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.59244
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.71494E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.58143E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.53926
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18076.75683
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.58143E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 476.88244
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.03610
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14854
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20722
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.39611
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.56492E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.70759E-005
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.33099
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11096.37537
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.70759E-005
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 292.74827
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.45846
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.36160
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.44503
215 ZoneHVAC:IdealLoadsAirSystem AIRLOOP DATACENTER BASEMENT Design Size Maximum Heating Air Flow Rate [m3/s] 0.33840
216 ZoneHVAC:IdealLoadsAirSystem AIRLOOP DATACENTER BASEMENT Design Size Maximum Cooling Air Flow Rate [m3/s] 21.26430
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.59021
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.72901
219 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 9.18041
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 2.72901
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 8.40624
222 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 8.40624
223 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
224 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.32464
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 42.52883
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 26.30471
227 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 85.05766
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 26.30471
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 77.36691
230 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 77.36691
231 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
232 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.34000
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.40590
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.70891
235 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 8.81180
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.52650
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 8.35301
238 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 8.35301
239 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
240 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.42218
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.03877
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.03877
243 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 5.03877
244 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 5.03877
245 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 5.03877
246 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 5.03877
247 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
249 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.45846
250 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.45846
251 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.45846
252 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.45846
253 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.45846
254 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.45846
255 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
256 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
257 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.36160
258 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.36160
259 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.36160
260 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.36160
261 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.36160
262 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.36160
263 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
265 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.44503
266 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.44503
267 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.44503
268 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.44503
269 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.44503
270 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.44503
271 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
273 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 8.40624
274 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 77.36691
275 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 8.35301
276 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 5.03877
277 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.45846
278 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.36160
279 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.44503
280 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 8.40624
281 HeatExchanger:AirToAir:SensibleAndLatent VAV_BOT WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
282 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.13813
283 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
284 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.04928
285 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.13239E-002
286 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
287 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 238952.86578
288 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.01656E-002
289 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.40624
290 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 25001.59582
291 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.18725E-004
292 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 432.11353
293 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 8.40624
294 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.01656E-002
295 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.68433E-005
296 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.18725E-004
297 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 77.36691
298 HeatExchanger:AirToAir:SensibleAndLatent VAV_MID WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 25.38195
299 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.56213
300 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
301 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.05047
302 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.16988E-002
303 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
304 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 2328648.57305
305 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.90661E-002
306 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 77.36691
307 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 230102.43263
308 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.01304E-003
309 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 3976.96115
310 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 77.36691
311 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 9.90661E-002
312 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.80680E-006
313 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.01304E-003
314 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 8.35301
315 HeatExchanger:AirToAir:SensibleAndLatent VAV_TOP WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
316 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.02168
317 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
318 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.04902
319 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.12416E-002
320 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
321 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 234131.84997
322 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.96051E-003
323 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.35301
324 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 24843.27469
325 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.17340E-004
326 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 429.37720
327 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 8.35301
328 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 9.96051E-003
329 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.78078E-005
330 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.17340E-004
331 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.03877
332 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 25.08707
333 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
334 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.42493
335 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.07986E-002
336 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
337 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 120036.57806
338 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.10663E-003
339 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.03877
340 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 237002.75266
341 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.07340E-003
342 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 5383.15759
343 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 5.03877
344 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 5.10663E-003
345 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 9.32494E-005
346 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.07340E-003
347 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.45846
348 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56328E-002
349 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.45846
350 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9361.60868
351 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6717.53076
352 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.29265E-004
353 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.45846
354 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.45846
355 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.45846
356 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.45846
357 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9361.60868
358 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9361.60868
359 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 669.06860
360 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
361 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.45846
362 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.45846
363 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9361.60868
364 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.29265E-004
365 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 669.06860
366 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.36160
367 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15633
368 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.36160
369 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 89307.36748
370 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 63990.84233
371 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.18713E-003
372 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.36160
373 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.36160
374 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.36160
375 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.36160
376 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 89307.36748
377 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 89307.36748
378 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 6690.68596
379 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
380 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.36160
381 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.36160
382 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 89307.36748
383 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.18713E-003
384 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 6690.68596
385 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.44503
386 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56328E-002
387 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.44503
388 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9105.25894
389 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6526.80272
390 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.22987E-004
391 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.44503
392 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.44503
393 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.44503
394 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.44503
395 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9105.25894
396 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9105.25894
397 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 669.06860
398 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
399 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.44503
400 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.44503
401 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9105.25894
402 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.22987E-004
403 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 669.06860
404 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 0.12430
405 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 25359.78701
406 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 0.12430
407 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 14.91586
408 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 0.12430
409 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 0.12430
410 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 521744.61908
411 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
412 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 1.26850E-002
413 PlantLoop HEATSYS1 Plant Loop Volume [m3] 1.52221
414 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 1.26850E-002
415 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 3782.35610
416 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
417 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 1449979.00722
418 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 1449979.01000
419 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 1.26850E-002
420 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 0.12430
421 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 14.91586
422 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 0.12430
423 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 17557.43599
424 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 0.12430
425 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.26400E-002
426 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1476033.40523
427 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1482993.02000
428 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 7.33878E-002
429 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 0.12430
430 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.26400E-002
431 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1476033.40523
432 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1482993.02000
433 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 7.33878E-002
434 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 2.63938E-003
435 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 0.31673
436 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 2.63938E-003
437 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 666.50983
438 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 2.63938E-003
439 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 35644.39112
440 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 21899.83861
441 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 17822.19556
442 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 1996.19659
443 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 5888.66036
444 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 108719.99657
445 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 108720.00000
446 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 2.63938E-003
447 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
448 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
449 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
450 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 5.95776
451 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
452 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.14678
453 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 17.61308
454 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.14678
455 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 43767.95378
456 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 56.77130
457 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1759550.91278
458 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 11.35426
459 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 219943.86410
460 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 56.77130
461 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1759550.91278
462 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 11.35426
463 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 219943.86410
464 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 45 7.62275E-002
465 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 45 7.62275E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 17715.59
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 333704.62
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 56891.75
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 4652.89
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 3562.77
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 6174.79
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 2661.79
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 124148.55
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 82886.08
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 123428.21
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 72068.10
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 17213.14
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 11365.87
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 17127.46
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 10513.75
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 21199.84
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 195112.94
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 21065.59
19 Coil:Heating:Water CAV_BAS HEATING COIL 192368.80


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 233673.59 157072.86 76600.73 0.67 24382.62 247.30
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2195648.10 1467005.60 728642.50 0.67 230314.52 2335.98
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 231002.78 155513.89 75488.89 0.67 24078.61 244.22
4 Coil:Cooling:Water CAV_BAS COOLING COIL 129811.88 89228.60 40583.28 0.69 13252.31 134.41


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.84 23.33
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.84 23.33


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   105.88 200.61 105.88 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_NORTH_0.25 N/A 2.584 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_NORTH_0.25 N/A 2.584 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_NORTH_0.25 N/A 2.584 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_NORTH_0.25 N/A 2.584 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_NORTH_0.25 N/A 2.584 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   71.89 133.74 71.89 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_EAST_0.25 N/A 2.584 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_EAST_0.25 N/A 2.584 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_EAST_0.25 N/A 2.584 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   105.88 200.61 105.88 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_SOUTH_0.25 N/A 2.584 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_SOUTH_0.25 N/A 2.584 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_SOUTH_0.25 N/A 2.584 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_SOUTH_0.25 N/A 2.584 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_SOUTH_0.25 N/A 2.584 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   71.89 133.74 71.89 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_WEST_0.25 N/A 2.584 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_WEST_0.25 N/A 2.584 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_WEST_0.25 N/A 2.584 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_NORTH_0.25 N/A 2.584 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_EAST_0.25 N/A 2.584 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_SOUTH_0.25 N/A 2.584 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_WEST_0.25 N/A 2.584 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_NORTH_0.25 N/A 2.584 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_EAST_0.25 N/A 2.584 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_SOUTH_0.25 N/A 2.584 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4547_SHGC_WEST_0.25 N/A 2.584 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.940 0.824   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.2349949155 0.2331475396 Pass Pass 0.7497316074 0.7586655436 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 0.2368879420 0.2520423166 Pass Pass 0.2477897796 0.4314528979 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 0.1605356826 0.2154150483 Pass Pass 0.2110778569 0.4063540308 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 0.1434765342 0.2075324207 Pass Pass 0.1961457471 0.3958162788 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 0.2080261043 0.2266061402 Pass Pass 0.2445994975 0.4283722885 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.2726168379 0.2983185111 Pass Pass 0.2534977471 0.4382735364 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.3712136743 0.4934866528 Pass Pass 0.2634019722 0.4406694698 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 0.3524818135 0.4232864959 Pass Pass 0.2475428344 0.4278959872 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.1453112950 0.2008856104 Pass Pass 0.2105676437 0.4055544364 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.2130115300 0.2644736090 Pass Pass 0.2117641095 0.4071876103 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.3137358178 0.5131802396 Pass Pass 0.2538783277 0.4701281117 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.2071192766 0.2959107082 Pass Pass 0.2108997832 0.4049537493 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.1324773747 0.1837529775 Pass Pass 0.1958433376 0.3948662297 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.2001267582 0.2405883754 Pass Pass 0.1968264473 0.3968667102 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.3180218579 0.4984168255 Pass Pass 0.2236569429 0.4300629485 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.1946615784 0.2976940411 Pass Pass 0.1964550793 0.3940959209 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 5.4115142113E-002 5.0033309304E-002 Pass Pass 0.2596326369 0.4184114472 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 3.2554920493E-002 4.1148990982E-002 Pass Pass 0.2609910914 0.6852964326 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.5047225047E-002 7.5810558740E-002 Pass Pass 0.2120795165 0.4190840981 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 5.7870604279E-006 8.4739059997E-006 Pass Pass 3.2381170306E-003 3.7839650097E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 4.8435044289E-006 7.2730644227E-006 Pass Pass 5.0552086807E-003 5.7294804339E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 4.8440891050E-006 7.4831735446E-006 Pass Pass 7.0572725827E-003 6.1159352028E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 2.0724163126E-015 2.6972301664E-015 Pass Pass 4.8004441168E-005 1.1006655033E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 5952.35 -19.5 0.00 1994.56 19209.73 27137.19



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 4.60 0.00 4.60 Wetbulb [C] 2.50 10.00
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 33.90 7.90 25.10 Wetbulb [C] 3.10 270.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 66.00 12      
Feb 66.00 22      
Mar 126.00 32      
Apr 206.00 19      
May 144.00 46      
Jun 99.00 30      
Jul 192.00 52      
Aug 240.00 34      
Sep 310.00 44      
Oct 34.00 10      
Nov 63.00 12      
Dec 35.00 24      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.382 1.743 200.61 105.88 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.382 1.743 133.74 71.89 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.382 1.743 200.61 105.88 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.382 1.743 133.74 71.89 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.327 1.656 2006.06 1136.85 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.327 1.656 1337.37 757.90 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.327 1.656 2006.06 1136.85 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.327 1.656 1337.37 757.90 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.618 2.135 200.61 113.68 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.618 2.135 133.74 75.79 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.618 2.135 200.61 113.68 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.618 2.135 133.74 75.79 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.382 1.743 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 1.382 1.743 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.382 1.743 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.382 1.743 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.327 1.656 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.327 1.656 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.327 1.656 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.327 1.656 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.618 2.135 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.618 2.135 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.618 2.135 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.618 2.135 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.55 0.221 0.228 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.845 0.940 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.4547_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.584 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.4547_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.584 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.4547_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.584 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.4547_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.584 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.4547_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.584 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.4547_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.584 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.4547_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.584 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.4547_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.584 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.4547_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.584 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.4547_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.584 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.4547_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.584 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.4547_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.584 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.4547_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.584 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.4547_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.584 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.4547_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.584 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.4547_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.584 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.4547_SHGC_NORTH_0.25   86.92 0.00 0.00 86.92 869.21 2.584 0.251 0.251             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.4547_SHGC_EAST_0.25   57.95 0.00 0.00 57.95 579.48 2.584 0.251 0.251             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.4547_SHGC_SOUTH_0.25   86.92 0.00 0.00 86.92 869.21 2.584 0.251 0.251             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.4547_SHGC_WEST_0.25   57.95 0.00 0.00 57.95 579.48 2.584 0.251 0.251             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.4547_SHGC_NORTH_0.25   86.92 0.00 0.00 86.92 86.92 2.584 0.251 0.251             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.4547_SHGC_EAST_0.25   57.95 0.00 0.00 57.95 57.95 2.584 0.251 0.251             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.4547_SHGC_SOUTH_0.25   86.92 0.00 0.00 86.92 86.92 2.584 0.251 0.251             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.4547_SHGC_WEST_0.25   57.95 0.00 0.00 57.95 57.95 2.584 0.251 0.251             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             3476.85 2.584 0.251 0.251                      
North Total or Average             1043.06 2.584 0.251 0.251                      
Non-North Total or Average             2433.80 2.584 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 5.8895 2779.43 16369.36 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 135.58
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 5.8895 2496.12 14700.84 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 121.76
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 5.8895 24961.20 147008.37 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 1217.57
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 5.8895 2496.12 14700.84 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 121.76
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 5.8895 313.41 1845.84 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.77 0.0000 Y 8.93
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 5.8895 201.98 1189.53 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.54 0.0000 Y 5.70
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 5.8895 313.42 1845.88 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.21 0.0000 Y 8.74
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 5.8895 201.98 1189.53 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.60 0.0000 Y 5.72
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 5.8895 3134.13 18458.37 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.78 0.0000 Y 89.31
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 5.8895 2019.75 11895.27 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.53 0.0000 Y 57.00
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 5.8895 3134.20 18458.77 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.22 0.0000 Y 87.39
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 5.8895 2019.75 11895.27 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.59 0.0000 Y 57.14
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 5.8895 313.41 1845.84 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.77 0.0000 Y 8.93
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 5.8895 201.98 1189.53 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.53 0.0000 Y 5.70
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 5.8895 313.42 1845.88 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.22 0.0000 Y 8.74
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 5.8895 201.98 1189.53 LightsWired LTG_SCH_OFFICE 45.29 168.00 25.59 0.0000 Y 5.71
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 5.8895 783.68 4615.46 LightsWired LTG_SCH_OFFICE 45.29 168.00 44.12 0.0000 Y 38.23
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 8.8011 36.20 318.62 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 3.26
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 8.8011 362.03 3186.24 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 32.64
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 8.8011 36.20 318.62 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 3.26
Interior Lighting Total       5.9168 46320.38 274067.57               636.12


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.88 711.95
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.88 255.65
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.84 711.94
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.84 255.65
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.88 711.95
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.88 255.65
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.84 711.94
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.84 255.65
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.88 711.95
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.88 255.65
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 1845.84 711.94
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1845.84 255.65
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1189.53 458.80
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1189.53 164.75


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 9973.05 AstronomicalClock -   41.73 41.73 78.11
EXTERIOR_LIGHTS_B 991.40 AstronomicalClock -   83.73 62.73 11.67
EXTERIOR_LIGHTS_C 26646.63 AstronomicalClock -   83.73 47.05 235.35
Exterior Lighting Total 37611.08           325.14



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2915050.66          
HEATSYS1 BOILER Boiler:HotWater 1449979.01 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1482993.02 6.28 1419425.64 5.98 6.84 23.33
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1482993.02 6.28 1419425.64 5.98 6.84 23.33
CENTRAL TOWER FluidCooler:TwoSpeed 148548.00          
CENTRAL BOILER Boiler:HotWater 108720.00 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1759550.91          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1759550.91          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 238952.87 233673.59 157072.86 76600.73 0.67 - 24382.62 247.30
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 2328648.57 2195648.10 1467005.60 728642.50 0.67 - 230314.52 2335.98
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 234131.85 231002.78 155513.89 75488.89 0.67 - 24078.61 244.22
CAV_BAS COOLING COIL Coil:Cooling:Water 120036.58 129811.88 89228.60 40583.28 0.69 - 13252.31 134.41
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9361.61 6717.53 2644.08 0.72 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   89307.37 63990.84 25316.53 0.72 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9105.26 6526.80 2578.46 0.72 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 18683.49 17715.59 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 352123.36 333704.62 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 60079.97 56891.75 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 4910.08 4652.89 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 3759.73 3562.77 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 6519.25 6174.79 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 2807.51 2661.79 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 131020.14 124148.55 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 87474.62 82886.08 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 130259.72 123428.21 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 76054.83 72068.10 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 18167.21 17213.14 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 11995.90 11365.87 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 18076.76 17127.46 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 11096.38 10513.75 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 25001.60 21199.84 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 230102.43 195112.94 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 24843.27 21065.59 -
CAV_BAS HEATING COIL Coil:Heating:Water 237002.75 192368.80 -
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9361.61 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   89307.37 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9105.26 0.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   669.07 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   6690.69 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   669.07 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 8.41 18165.44 2160.95 1.00 1.12 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 77.37 167185.78 2160.95 1.00 1.08 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 8.35 18050.41 2160.95 1.00 1.12 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 5.04 8544.02 1695.65 1.00 1.16 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.46 513.53 1120.11 1.00 1.65 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.36 4885.47 1120.11 1.00 1.16 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.45 498.48 1120.11 1.00 1.66 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.124299 25359.79 204022.71 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.012685 3782.36 298174.34 0.91 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.124299 17557.44 141251.81 0.91 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.002639 666.51 252524.76 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 3168.45 0.000440 5.96 13540.37 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 180718.98 0.146776 43767.95 298196.27 0.91 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.50 0.08



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 69955.87 69955.87 25.17 5.039 5.039 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00900 28.05 0.01653 1.200 0.00
CORE_BOTTOM 73252.66 73252.66 29.35 5.276 5.276 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00893 28.05 0.01653 1.078 0.00
CORE_MID 683437.97 683437.97 273.80 49.208 49.208 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00896 28.05 0.01653 10.778 0.00
CORE_TOP 67903.33 67903.33 27.20 4.889 4.889 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00896 28.05 0.01653 1.078 0.00
PERIMETER_BOT_ZN_3 11614.99 11614.99 37.06 0.845 0.845 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 24.00 0.00887 33.90 0.01654 0.135 0.00
PERIMETER_BOT_ZN_2 12154.07 12154.07 60.18 0.884 0.884 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 24.00 24.00 0.00873 30.23 0.01653 0.087 0.00
PERIMETER_BOT_ZN_1 14172.37 14172.37 45.22 1.031 1.031 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 24.00 24.00 0.00880 33.77 0.01654 0.135 0.00
PERIMETER_BOT_ZN_4 15753.57 15753.57 78.00 1.146 1.146 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 24.00 24.00 0.00868 32.79 0.01653 0.087 0.00
PERIMETER_MID_ZN_3 105694.41 105694.41 337.24 7.686 7.686 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 24.00 24.00 0.00896 33.90 0.01654 1.353 0.00
PERIMETER_MID_ZN_2 124287.05 124287.05 615.36 9.038 9.038 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 24.00 24.00 0.00876 30.67 0.01653 0.872 0.00
PERIMETER_MID_ZN_1 131927.68 131927.68 420.93 9.593 9.593 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 24.00 24.00 0.00887 33.83 0.01654 1.353 0.00
PERIMETER_MID_ZN_4 131097.42 131097.42 649.08 9.533 9.533 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 24.00 24.00 0.00874 32.66 0.01653 0.872 0.00
PERIMETER_TOP_ZN_3 12225.82 12225.82 39.01 0.889 0.889 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 24.00 24.00 0.00892 33.74 0.01654 0.135 0.00
PERIMETER_TOP_ZN_2 12689.37 12689.37 62.83 0.923 0.923 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 24.00 24.00 0.00876 30.90 0.01653 0.087 0.00
PERIMETER_TOP_ZN_1 14783.02 14783.02 47.17 1.075 1.075 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 24.00 24.00 0.00885 33.90 0.01654 0.135 0.00
PERIMETER_TOP_ZN_4 14248.32 14248.32 70.54 1.036 1.036 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 24.00 24.00 0.00873 32.79 0.01653 0.087 0.00
DATACENTER_BOT_ZN_6 7993.57 7993.57 220.80 0.458 0.458 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 27.00 27.00 0.00859 31.21 0.01653 0.016 0.00
DATACENTER_MID_ZN_6 76046.43 76046.43 2100.57 4.362 4.362 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 27.00 27.00 0.00860 31.21 0.01653 0.156 0.00
DATACENTER_TOP_ZN_6 7759.38 7759.38 214.33 0.445 0.445 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 27.00 27.00 0.00859 31.21 0.01653 0.016 0.00
DATACENTER_BASEMENT_ZN_6 370763.86 370763.86 473.11 21.264 21.264 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:00:00 27.00 27.00 0.00854 26.71 0.01652 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200   00:10:00 15.60 25.40 0.00526 4.60 0.00526 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078   00:10:00 15.60 23.03 0.00526 4.60 0.00526 1.078 0.00
CORE_MID 170440.12 170440.12 68.28 7.131 10.778 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 4.60 0.00526 10.778 0.00
CORE_TOP 41438.92 41438.92 16.60 1.756 1.756 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 4.60 0.00526 1.078 0.00
PERIMETER_BOT_ZN_3 2566.48 2566.48 8.19 0.108 0.135 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00765 4.60 0.00526 0.135 0.00
PERIMETER_BOT_ZN_2 1982.55 1982.55 9.82 0.083 0.087 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00769 4.60 0.00526 0.087 0.00
PERIMETER_BOT_ZN_1 4177.19 4177.19 13.33 0.177 0.177 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00777 4.60 0.00526 0.135 0.00
PERIMETER_BOT_ZN_4 505.54 505.54 2.50 0.022 0.087 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00731 4.60 0.00526 0.087 0.00
PERIMETER_MID_ZN_3 91744.65 91744.65 292.73 3.905 3.905 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00785 4.60 0.00526 1.353 0.00
PERIMETER_MID_ZN_2 61249.48 61249.48 303.25 2.608 2.608 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00785 4.60 0.00526 0.872 0.00
PERIMETER_MID_ZN_1 91213.07 91213.07 291.03 3.883 3.883 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00784 4.60 0.00526 1.353 0.00
PERIMETER_MID_ZN_4 53266.05 53266.05 263.73 2.266 2.266 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00780 4.60 0.00526 0.872 0.00
PERIMETER_TOP_ZN_3 12715.87 12715.87 40.57 0.542 0.542 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00791 4.60 0.00526 0.135 0.00
PERIMETER_TOP_ZN_2 8396.12 8396.12 41.57 0.358 0.358 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00792 4.60 0.00526 0.087 0.00
PERIMETER_TOP_ZN_1 12652.64 12652.64 40.37 0.539 0.539 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00791 4.60 0.00526 0.135 0.00
PERIMETER_TOP_ZN_4 7767.31 7767.31 38.46 0.331 0.331 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00789 4.60 0.00526 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 27.00 0.00850 4.60 0.00526 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156   00:10:00 18.00 25.09 0.00834 4.60 0.00526 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 24.14 0.00568 4.60 0.00526 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338   00:10:00 18.00 27.00 0.00850 4.60 0.00526 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 8.41 8.41 1.56 1.56 8.4062 2.7290 8.4062 0.3246 0.3000
VAV_MID WITH REHEAT 77.37 77.37 23.44 23.44 77.3669 26.3047 77.3669 0.3400 0.3000
VAV_TOP WITH REHEAT 8.35 8.35 3.53 3.53 8.3530 3.5265 8.3530 0.4222 0.3000
CAV_BAS 5.04 5.04 1.20 1.20 5.0388 5.0388 5.0388 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.46 0.46 0.02 0.02 0.4585 0.4585 0.4585 1.0000 1.0000
AIRLOOP DATACENTER MID 4.36 4.36 0.16 0.16 4.3616 4.3616 4.3616 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.45 0.45 0.02 0.02 0.4450 0.4450 0.4450 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 18683.494 18683.494 1.857124 0.00016345 376.645   1/21 00:10:00   1/21 00:10:00 18683.49 18683.49 1.857124 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00800000 51.6744 0.00 0.00 18752.38 18752.38
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 352123.365 352123.365 18.059169 0.00308053 7826.571 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 352123.36 352123.36 18.059169 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00800000 51.6744 170440.12 0.00 353333.69 353333.69
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 60079.968 60079.968 1.852905 0.00052561 1561.780 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 60079.97 60079.97 1.852905 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00800000 51.6744 41438.92 0.00 60263.87 60263.87
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 4910.078 4910.078 0.233110 0.00004296 111.054 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4910.08 4910.08 0.233110 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00764670 49.4210 2566.48 0.00 4926.83 4926.83
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 3759.732 3759.732 0.176759 0.00003289 85.235 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 3759.73 3759.73 0.176759 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00768566 49.6698 1982.55 0.00 3772.54 3772.54
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 6519.252 6519.252 0.232907 0.00005703 160.026 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6519.25 6519.25 0.232907 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00776822 50.1967 4177.19 0.00 6539.79 6539.79
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 2807.506 2807.506 0.229106 0.00002456 57.838 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2807.51 2807.51 0.229106 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00730975 47.2682 505.54 0.00 2817.74 2817.74
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 131020.139 131020.139 3.905268 0.00114622 3457.771 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 131020.14 131020.14 3.905268 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00784597 50.6933 91744.65 0.00 131467.45 131467.45
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 87474.617 87474.617 2.607605 0.00076527 2308.441 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 87474.62 87474.62 2.607605 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00785209 50.7324 61249.48 0.00 87772.44 87772.44
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 130259.723 130259.723 3.882529 0.00113957 3437.733 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 130259.72 130259.72 3.882529 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00784410 50.6814 91213.07 0.00 130704.65 130704.65
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 76054.831 76054.831 2.266163 0.00066536 2007.489 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 76054.83 76054.83 2.266163 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00780006 50.4007 53266.05 0.00 76316.74 76316.74
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 18167.212 18167.212 0.541966 0.00015893 479.266 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 18167.21 18167.21 0.541966 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00791336 51.1229 12715.87 0.00 18227.89 18227.89
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 11995.903 11995.903 0.357885 0.00010495 316.453 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 11995.90 11995.90 0.357885 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00791539 51.1358 8396.12 0.00 12035.90 12035.90
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 18076.757 18076.757 0.539261 0.00015814 476.882 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 18076.76 18076.76 0.539261 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00791231 51.1162 12652.64 0.00 18137.15 18137.15
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 11096.375 11096.375 0.330987 0.00009708 292.748 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 11096.38 11096.38 0.330987 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00789404 50.9998 7767.31 0.00 11133.56 11133.56
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 238952.866 -999.000 8.406240 0.01016561 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 238952.87 164353.90 8.406240 27.14 19.70 0.01132385 11.05 11.05 0.00850000 33.90 0.01653638 25.13 30.1941 24.00 0.00890377 47.8630 110086.83 0.00 239230.99 160737.22
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 25001.596 25001.596 2.521872 0.00021872 432.114 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 25001.60 25001.60 2.521872 4.60 4.60 0.00525715 12.80 11.59 0.00800000 4.60 0.00525715 4.60 100.6471 22.15 0.00627136 37.8561 9231.76 0.00 25664.22 25664.22
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 2328648.573 -999.000 77.366915 0.09906609 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 2328648.57 1551746.77 77.366915 27.56 20.11 0.01169876 11.05 11.05 0.00850000 33.90 0.01653638 25.13 32.8072 24.00 0.00897878 48.2608 969855.67 0.00 2331523.64 1523593.49
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 230102.433 230102.433 23.210074 0.00201304 3976.961 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 230102.43 230102.43 23.210074 4.60 4.60 0.00525715 12.80 11.59 0.00800000 4.60 0.00525715 4.60 109.3575 21.00 0.00789665 51.0162 467913.37 0.00 236200.91 236200.91
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 234131.850 -999.000 8.353008 0.00996051 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 234131.85 162146.56 8.353008 27.02 19.60 0.01124156 11.05 11.05 0.00850000 33.90 0.01653638 25.13 30.3865 24.00 0.00891445 47.9199 114323.60 0.00 234400.96 158429.83
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 24843.275 24843.275 2.505902 0.00021734 429.377 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 11:20:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 24843.27 24843.27 2.505902 4.60 4.60 0.00525715 12.80 11.59 0.00800000 4.60 0.00525715 4.60 101.2885 21.00 0.00796081 51.4248 59204.57 0.00 25501.70 25501.70
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 120036.578 -999.000 5.038772 0.00510663 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 120036.58 84239.10 5.038772 25.09 18.64 0.01079856 11.42 11.42 0.00850000 28.55 0.01652632 23.72 23.8191 24.00 0.00900047 48.3755 69080.78 0.00 120184.22 82186.13
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 237002.753 237002.753 5.038772 0.00207340 5383.158 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 237002.75 237002.75 5.038772 1.10 1.10 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 23.8191 25.40 0.00525715 26.1354 0.00 0.00 203516.08 203516.08
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9361.609 6717.531 0.458462 0.00022927 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 8774.89 8319.21 -999.0 28.09 18.09 0.00886136 12.80 12.09 0.00850000 31.21 0.01653132 24.43 -999.0000 27.00 0.00859060 38.6629 7993.57 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 89307.367 63990.842 4.361603 0.00218713 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 83749.15 79193.70 -999.0 28.10 18.10 0.00887966 12.80 12.09 0.00850000 31.21 0.01653132 24.43 -999.0000 27.00 0.00859521 38.6837 76046.43 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9105.259 6526.803 0.445033 0.00022299 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 8537.48 8081.91 -999.0 28.10 18.10 0.00887213 12.80 12.09 0.00850000 31.41 0.01653169 24.48 -999.0000 27.00 0.00859324 38.6748 7758.48 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9361.609 9361.609 0.458462 0.00022927 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9361.61 9361.61 0.458462 4.60 4.60 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.4098 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 89307.367 89307.367 4.361603 0.00218713 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 89307.37 89307.37 4.361603 4.60 4.60 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.5842 25.09 0.00834293 42.0626 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9105.259 9105.259 0.445033 0.00022299 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9105.26 9105.26 0.445033 4.60 4.60 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.5127 24.14 0.00568123 30.4321 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 669.069 669.069 -999.0 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 669.07 669.07 0.458462 0.16 0.16 0.00838942 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.4098 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 6690.686 6690.686 -999.0 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 6690.69 6690.69 4.361603 0.16 0.16 0.00823233 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.5842 25.09 0.00834293 42.0626 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 669.069 669.069 -999.0 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 669.07 669.07 0.445033 0.16 0.16 0.00566633 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.5127 24.14 0.00568123 30.4321 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 18683.494 18683.494 1.857124 0.00016345 376.645 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 1.2631 1.288536   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 18683.49 18683.49 1.0000 2.23443071 1.857124 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.16343468 60.00 32.22 27.78 0.000 18683.49 4.60 0.00525715 4.60 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 51.6744 0.00 0.00 18752.38 18752.38 2.23443071 12.80 11.60 0.00800000 33059.8 21.03 14.86 0.00800000 41452.3
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 352123.365 352123.365 18.059169 0.00308053 7826.571 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 23.8056 24.284722 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 352123.36 352123.36 1.0000 21.72819430 18.059169 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 3.08021456 60.00 32.22 27.78 0.000 352123.36 4.60 0.00525715 4.60 0.00000000 0.0000 20.58 0.00800000 21.00 0.00800000 51.6744 170440.12 0.00 353333.69 353333.69 21.72819430 12.80 11.60 0.00800000 33059.8 28.75 17.62 0.00800000 49321.4
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 60079.968 60079.968 1.852905 0.00052561 1561.780 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 4.0618 4.143506 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 60079.97 60079.97 1.0000 2.22935382 1.852905 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.52555215 60.00 32.22 27.78 0.000 60079.97 4.60 0.00525715 4.60 0.00000000 0.0000 20.86 0.00800000 21.00 0.00800000 51.6744 41438.92 0.00 60263.87 60263.87 2.22935382 12.80 11.60 0.00800000 33059.8 39.31 20.98 0.00800000 60091.8
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 4910.078 4910.078 0.233110 0.00004296 111.054 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 0.3320 0.338631 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 4910.08 4910.08 1.0000 0.28046978 0.233110 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.04295112 60.00 32.22 27.78 0.000 4910.08 4.60 0.00525715 4.60 0.00000000 0.0000 20.85 0.00764670 21.00 0.00764670 49.4210 2566.48 0.00 4926.83 4926.83 0.28046978 12.80 11.60 0.00800000 33059.8 30.03 18.05 0.00800000 50626.2
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 3759.732 3759.732 0.176759 0.00003289 85.235 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 0.2542 0.259296 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 3759.73 3759.73 1.0000 0.21267067 0.176759 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.03288842 60.00 32.22 27.78 0.000 3759.73 4.60 0.00525715 4.60 0.00000000 0.0000 20.82 0.00768566 21.00 0.00768566 49.6698 1982.55 0.00 3772.54 3772.54 0.21267067 12.80 11.60 0.00800000 33059.8 30.20 18.10 0.00800000 50798.7
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 6519.252 6519.252 0.232907 0.00005703 160.026 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 0.4407 0.449610 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 6519.25 6519.25 1.0000 0.28022585 0.232907 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.05702744 60.00 32.22 27.78 0.000 6519.25 4.60 0.00525715 4.60 0.00000000 0.0000 20.87 0.00776822 21.00 0.00776822 50.1967 4177.19 0.00 6539.79 6539.79 0.28022585 12.80 11.60 0.00800000 33059.8 35.69 19.87 0.00800000 56397.4
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 2807.506 2807.506 0.229106 0.00002456 57.838 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 0.1898 0.193624 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 2807.51 2807.51 1.0000 0.27565314 0.229106 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.02455878 60.00 32.22 27.78 0.000 2807.51 4.60 0.00525715 4.60 0.00000000 0.0000 20.96 0.00730975 21.00 0.00730975 47.2682 505.54 0.00 2817.74 2817.74 0.27565314 12.80 11.60 0.00800000 33059.8 22.82 15.53 0.00800000 43281.9
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 131020.139 131020.139 3.905268 0.00114622 3457.771 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 8.8577 9.036002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 131020.14 131020.14 1.0000 4.69868952 3.905268 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 1.14610441 60.00 32.22 27.78 0.000 131020.14 4.60 0.00525715 4.60 0.00000000 0.0000 20.91 0.00784597 21.00 0.00784597 50.6933 91744.65 0.00 131467.45 131467.45 4.69868952 12.80 11.60 0.00800000 33059.8 40.24 21.25 0.00800000 61039.4
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 87474.617 87474.617 2.607605 0.00076527 2308.441 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 5.9138 6.032820 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 87474.62 87474.62 1.0000 3.13738427 2.607605 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.76518804 60.00 32.22 27.78 0.000 87474.62 4.60 0.00525715 4.60 0.00000000 0.0000 20.91 0.00785209 21.00 0.00785209 50.7324 61249.48 0.00 87772.44 87772.44 3.13738427 12.80 11.60 0.00800000 33059.8 40.24 21.25 0.00800000 61036.1
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 130259.723 130259.723 3.882529 0.00113957 3437.733 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 8.8063 8.983559 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 130259.72 130259.72 1.0000 4.67133042 3.882529 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 1.13945264 60.00 32.22 27.78 0.000 130259.72 4.60 0.00525715 4.60 0.00000000 0.0000 20.91 0.00784410 21.00 0.00784410 50.6814 91213.07 0.00 130704.65 130704.65 4.67133042 12.80 11.60 0.00800000 33059.8 40.24 21.25 0.00800000 61040.0
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 76054.831 76054.831 2.266163 0.00066536 2007.489 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 5.1418 5.245237 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 76054.83 76054.83 1.0000 2.72657250 2.266163 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.66529296 60.00 32.22 27.78 0.000 76054.83 4.60 0.00525715 4.60 0.00000000 0.0000 20.91 0.00780006 21.00 0.00780006 50.4007 53266.05 0.00 76316.74 76316.74 2.72657250 12.80 11.60 0.00800000 33059.8 40.25 21.26 0.00800000 61049.8
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 18167.212 18167.212 0.541966 0.00015893 479.266 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 1.2282 1.252929 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 18167.21 18167.21 1.0000 0.65207600 0.541966 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.15891848 60.00 32.22 27.78 0.000 18167.21 4.60 0.00525715 4.60 0.00000000 0.0000 20.95 0.00791336 21.00 0.00791336 51.1229 12715.87 0.00 18227.89 18227.89 0.65207600 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61013.4
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 11995.903 11995.903 0.357885 0.00010495 316.453 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 0.8110 0.827316 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 11995.90 11995.90 1.0000 0.43059583 0.357885 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.10493469 60.00 32.22 27.78 0.000 11995.90 4.60 0.00525715 4.60 0.00000000 0.0000 20.95 0.00791539 21.00 0.00791539 51.1358 8396.12 0.00 12035.90 12035.90 0.43059583 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61011.6
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 18076.757 18076.757 0.539261 0.00015814 476.882 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 1.2221 1.246691 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 18076.76 18076.76 1.0000 0.64882071 0.539261 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.15812722 60.00 32.22 27.78 0.000 18076.76 4.60 0.00525715 4.60 0.00000000 0.0000 20.95 0.00791231 21.00 0.00791231 51.1162 12652.64 0.00 18137.15 18137.15 0.64882071 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61013.9
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 11096.375 11096.375 0.330987 0.00009708 292.748 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 0.7502 0.765278 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 11096.38 11096.38 1.0000 0.39823226 0.330987 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.09706603 60.00 32.22 27.78 0.000 11096.38 4.60 0.00525715 4.60 0.00000000 0.0000 20.95 0.00789404 21.00 0.00789404 50.9998 7767.31 0.00 11133.56 11133.56 0.39823226 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61017.3
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 238952.866 -999.000 8.406240 0.01016561 -999.000 -999.0000 1.00000 1.00000 1025.8905 1004.8586 1.2032 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 8.406240 10.11411003   4197.9300 999.8980 124.28616463 12.27 6.67 5.60 2921769.87 8.1784 8.178360 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 Sensible 238952.87 164353.90 1.0000 10.11411003 8.406240 27.14 19.70 0.01132385 56161.0 11.05 11.05 0.00850000 32535.3 10.16457030 6.67 12.27 5.60 18165.438 220787.43 33.90 0.01653638 25.13 2.53819000 30.1941 24.00 0.00890377 24.00 0.00890377 47.8630 110086.83 0.00 239230.99 160737.22 10.11411003 27.14 19.71 0.01132385 56161.0 11.65 11.36 0.00824733 32507.8
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 25001.596 25001.596 2.521872 0.00021872 432.114 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 8.406240 10.11411003   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 1.6903 1.724273 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 25001.60 25001.60 1.0000 3.03423301 2.521872 4.60 4.60 0.00525715 17815.0 12.80 11.59 0.00800000 33059.8 0.21870255 60.00 32.22 27.78 0.000 25001.60 4.60 0.00525715 4.60 2.53819000 100.6471 6.49 0.00599734 22.15 0.00627136 37.8561 9231.76 0.00 25664.22 25664.22 3.03423301 2.80 2.80 0.00525715 15988.7 11.14 7.87 0.00525715 24447.0
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 2328648.573 -999.000 77.366915 0.09906609 -999.000 -999.0000 1.00000 1.00000 1026.5874 1004.8586 1.2032 VAV_MID WITH REHEAT FAN Fan:VariableVolume 77.366915 93.08531092   4197.9300 999.8980 124.28616463 12.27 6.67 5.60 2921769.87 79.6999 79.699931 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 Sensible 2328648.57 1551746.77 1.0000 93.08531092 77.366915 27.56 20.11 0.01169876 57552.8 11.05 11.05 0.00850000 32536.6 99.05598767 6.67 12.27 5.60 167185.783 2161462.79 33.90 0.01653638 25.13 25.38195000 32.8072 24.00 0.00897878 24.00 0.00897878 48.2608 969855.67 0.00 2331523.64 1523593.49 93.08531092 27.56 20.13 0.01169876 57552.8 11.62 11.36 0.00825800 32505.7
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 230102.433 230102.433 23.210074 0.00201304 3976.961 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 VAV_MID WITH REHEAT FAN Fan:VariableVolume 77.366915 93.08531092   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 15.5563 15.869363 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 230102.43 230102.43 1.0000 27.92559328 23.210074 4.60 4.60 0.00525715 17815.0 12.80 11.59 0.00800000 33059.8 2.01283111 60.00 32.22 27.78 0.000 230102.43 4.60 0.00525715 4.60 25.38195000 109.3575 20.76 0.00791273 21.00 0.00789665 51.0162 467913.37 0.00 236200.91 236200.91 27.92559328 2.80 2.80 0.00525715 15988.7 11.14 7.87 0.00525715 24447.0
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 234131.850 -999.000 8.353008 0.00996051 -999.000 -999.0000 1.00000 1.00000 1025.7375 1004.8586 1.2032 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 8.353008 10.05006302   4197.9300 999.8980 124.28616463 12.27 6.67 5.60 2921769.87 8.0134 8.013357 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 Sensible 234131.85 162146.56 1.0000 10.05006302 8.353008 27.02 19.60 0.01124156 55831.6 11.05 11.05 0.00850000 32535.1 9.95949407 6.67 12.27 5.60 18050.406 216081.44 33.90 0.01653638 25.13 2.53819000 30.3865 24.00 0.00891445 24.00 0.00891445 47.9199 114323.60 0.00 234400.96 158429.83 10.05006302 27.02 19.61 0.01124156 55831.6 11.65 11.36 0.00824495 32508.3
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 24843.275 24843.275 2.505902 0.00021734 429.377 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 8.353008 10.05006302   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 1.6796 1.713354 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 11:20:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 24843.27 24843.27 1.0000 3.01501891 2.505902 4.60 4.60 0.00525715 17815.0 12.80 11.59 0.00800000 33059.8 0.21731763 60.00 32.22 27.78 0.000 24843.27 4.60 0.00525715 4.60 2.53819000 101.2885 21.00 0.00796081 21.00 0.00796081 51.4248 59204.57 0.00 25501.70 25501.70 3.01501891 2.80 2.80 0.00525715 15988.7 11.14 7.87 0.00525715 24447.0
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 120036.578 -999.000 5.038772 0.00510663 -999.000 -999.0000 1.00000 1.00000 1024.9140 1004.8586 1.2032 CAV_BAS FAN Fan:ConstantVolume 5.038772 6.06248397   4197.9300 999.8980 124.28616463 12.27 6.67 5.60 2921769.87 4.1084 4.108352 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 Sensible 120036.58 84239.10 1.0000 6.06248397 5.038772 25.09 18.64 0.01079856 52718.6 11.42 11.42 0.00850000 32918.7 5.10611259 6.67 12.27 5.60 8544.016 111492.56 28.55 0.01652632 23.72 1.20019084 23.8191 24.00 0.00900047 24.00 0.00900047 48.3755 69080.78 0.00 120184.22 82186.13 6.06248397 25.09 18.65 0.01079856 52718.6 11.86 11.52 0.00831431 32894.4
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 237002.753 237002.753 5.038772 0.00207340 5383.158 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 CAV_BAS FAN Fan:ConstantVolume 5.038772 6.06248397   4197.9300 999.8980 12.68375489 54.44 82.22 27.78 1479160.41 16.0228 16.345254 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 237002.75 237002.75 1.0000 6.06248397 5.038772 1.10 1.10 0.00525715 14259.5 40.00 21.17 0.00800000 60796.0 2.07319196 60.00 32.22 27.78 0.000 237002.75 4.60 0.00525715 4.60 1.20019084 23.8191 0.00 0.00525715 25.40 0.00525715 26.1354 0.00 0.00 203516.08 203516.08 6.06248397 12.80 8.65 0.00525715 26134.9 45.89 20.94 0.00525715 59704.6
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9361.609 6717.531 0.458462 0.00022927 -999.000 -999.0000 -999.00000 -999.00000 1021.3128 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 Sensible 8774.89 8319.21 0.9373 -999.0 -999.0 28.09 18.09 0.00886136 50849.5 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8774.89 31.21 0.01653132 24.43 0.01563279 -999.0000 27.00 0.00859060 27.00 0.00859060 38.6629 7993.57 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 89307.367 63990.842 4.361603 0.00218713 -999.000 -999.0000 -999.00000 -999.00000 1021.3468 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 Sensible 83749.15 79193.70 0.9378 -999.0 -999.0 28.10 18.10 0.00887966 50903.6 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 83749.15 31.21 0.01653132 24.43 0.15632792 -999.0000 27.00 0.00859521 27.00 0.00859521 38.6837 76046.43 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9105.259 6526.803 0.445033 0.00022299 -999.000 -999.0000 -999.00000 -999.00000 1021.3328 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 Sensible 8537.48 8081.91 0.9376 -999.0 -999.0 28.10 18.10 0.00887213 50888.5 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8537.48 31.41 0.01653169 24.48 0.01563279 -999.0000 27.00 0.00859324 27.00 0.00859324 38.6748 7758.48 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9361.609 9361.609 0.458462 0.00022927 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9361.61 9361.61 1.0000 0.55160676 0.458462 4.60 4.60 0.00525715 17815.0 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9361.61 4.60 0.00525715 4.60 0.01563279 3.4098 0.00 0.00850000 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 89307.367 89307.367 4.361603 0.00218713 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 89307.37 89307.37 1.0000 5.24773579 4.361603 4.60 4.60 0.00525715 17815.0 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 89307.37 4.60 0.00525715 4.60 0.15632792 3.5842 0.00 0.00834293 25.09 0.00834293 42.0626 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9105.259 9105.259 0.445033 0.00022299 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9105.26 9105.26 1.0000 0.53544868 0.445033 4.60 4.60 0.00525715 17815.0 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9105.26 4.60 0.00525715 4.60 0.01563279 3.5127 0.00 0.00568123 24.14 0.00568123 30.4321 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 669.069 669.069 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.458462 0.55160676   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 669.07 669.07 1.0000 0.55160676 0.458462 0.16 0.16 0.00838942 21141.5 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 669.07 4.60 0.00525715 4.60 0.01563279 3.4098 0.00 0.00850000 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 6690.686 6690.686 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.361603 5.24773579   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 6690.69 6690.69 1.0000 5.24773579 4.361603 0.16 0.16 0.00823233 20756.8 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6690.69 4.60 0.00525715 4.60 0.15632792 3.5842 0.00 0.00834293 25.09 0.00834293 42.0626 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 669.069 669.069 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.445033 0.53544868   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 669.07 669.07 1.0000 0.53544868 0.445033 0.16 0.16 0.00566633 14335.2 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 669.07 4.60 0.00525715 4.60 0.01563279 3.5127 0.00 0.00568123 24.14 0.00568123 30.4321 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 8.41 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 77.37 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 8.35 -      
CAV_BAS_OA_CONTROLLER DifferentialEnthalpy 0.00 5.04 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT BASEMENT_DCV 0.002360 0.000305 0.000000 0.000000 Sum   1.00 1.00  
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 4947.50 1951.33 1865.33
CORE_BOTTOM 4268.67 320.50 0.00
CORE_MID 2346.67 1893.33 0.00
CORE_TOP 2579.00 2187.50 58.50
PERIMETER_BOT_ZN_3 3946.00 1306.67 2.83
PERIMETER_BOT_ZN_2 3867.83 1315.83 88.17
PERIMETER_BOT_ZN_1 4589.17 815.00 139.33
PERIMETER_BOT_ZN_4 5041.17 687.33 274.50
PERIMETER_MID_ZN_3 3277.00 2280.83 168.67
PERIMETER_MID_ZN_2 2921.33 1789.67 224.17
PERIMETER_MID_ZN_1 4198.50 1177.83 175.17
PERIMETER_MID_ZN_4 3848.50 1709.83 175.50
PERIMETER_TOP_ZN_3 3569.67 2450.33 526.17
PERIMETER_TOP_ZN_2 3714.67 2255.00 515.50
PERIMETER_TOP_ZN_1 4117.00 1512.00 327.33
PERIMETER_TOP_ZN_4 3796.50 2021.00 388.33
DATACENTER_BOT_ZN_6 5943.00 848.83 848.83
DATACENTER_MID_ZN_6 5943.00 16.67 16.67
DATACENTER_TOP_ZN_6 5865.83 124.83 110.67
DATACENTER_BASEMENT_ZN_6 5943.00 5943.00 5943.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5943.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 76.83 0.00 2.33
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.33 0.00 0.00
PERIMETER_BOT_ZN_2 0.00 17.83 0.00 17.83
PERIMETER_BOT_ZN_1 0.00 39.83 0.00 38.50
PERIMETER_BOT_ZN_4 0.00 154.50 0.00 57.50
PERIMETER_MID_ZN_3 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 0.00 23.50 0.00 23.50
PERIMETER_MID_ZN_1 0.00 39.67 0.00 39.17
PERIMETER_MID_ZN_4 0.00 29.17 0.00 18.33
PERIMETER_TOP_ZN_3 4.67 2.17 0.67 2.00
PERIMETER_TOP_ZN_2 2.50 46.67 0.00 44.17
PERIMETER_TOP_ZN_1 1.17 39.83 0.00 37.00
PERIMETER_TOP_ZN_4 1.17 40.00 0.00 24.67
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.83 0.00 0.83
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 4.67 354.00 0.67 175.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.01 149.60 6779.02 0.874 0.000 0.000 0.000
CORE_BOTTOM 55.69 134.35 6849.35 0.572 0.000 0.000 0.000
CORE_MID 55.69 134.35 6849.35 0.511 0.000 0.000 0.000
CORE_TOP 55.69 134.35 6849.35 0.500 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.99 16.87 860.00 0.617 0.008 0.000 0.000
PERIMETER_BOT_ZN_2 4.51 10.87 554.22 0.760 0.009 0.000 0.000
PERIMETER_BOT_ZN_1 6.99 16.87 860.02 0.832 0.008 0.000 0.000
PERIMETER_BOT_ZN_4 4.51 10.87 554.22 1.156 0.009 0.000 0.000
PERIMETER_MID_ZN_3 6.99 16.87 860.00 0.585 0.020 0.000 0.000
PERIMETER_MID_ZN_2 3.94 10.87 554.22 0.722 0.022 0.000 0.000
PERIMETER_MID_ZN_1 6.99 16.87 860.02 0.810 0.020 0.000 0.000
PERIMETER_MID_ZN_4 4.51 10.87 554.22 0.838 0.020 0.000 0.000
PERIMETER_TOP_ZN_3 6.99 16.87 860.00 0.581 0.024 0.000 0.000
PERIMETER_TOP_ZN_2 4.51 10.87 554.22 0.775 0.025 0.000 0.000
PERIMETER_TOP_ZN_1 6.99 16.87 860.02 0.765 0.025 0.000 0.000
PERIMETER_TOP_ZN_4 4.51 10.87 554.22 0.837 0.025 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.48 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.01 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 55.69 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 55.69 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 55.69 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.99 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 6.99 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 6.99 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.94 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 6.99 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 6.99 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 6.99 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.48 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.01 149.60 6779.02 2779.43 1.2002 0.847
CORE_BOTTOM VAV_BOT WITH REHEAT 55.69 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 55.69 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 55.69 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 6.99 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 6.99 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 6.99 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.94 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 6.99 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 6.99 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 6.99 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.81 1.95 99.34 36.20 0.0156 0.011
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.81 1.95 99.34 36.20 0.1563 0.110
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.81 1.95 99.34 36.20 0.0156 0.011
DATACENTER_BASEMENT_ZN_6   17.48 42.18 1911.37 783.68   0.239
Total Facility   1027.73 2493.19 126016.35 46320.38 1.3878 157.549


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 36453805.27 0.00 36453805.27 0.00 36453805.27 29876159.83 4075.23 2841.91 1842.86 240.62
CORE_BOTTOM 23921062.16 0.00 23921062.16 0.00 23921062.16 33990283.35 6743.03 233.65 1783.32 163.03
CORE_MID 0.20E+09 0.00 0.20E+09 0.00 0.20E+09 0.34E+09 6635.61 585.27 1539.12 11.78
CORE_TOP 20123285.08 0.00 20123285.08 0.00 20123285.08 33990283.35 6720.23 652.55 1387.21 35.92
PERIMETER_BOT_ZN_3 3223040.42 0.00 3223040.42 82232.77 3305273.20 4267819.30 4586.26 271.77 3901.98 163.03
PERIMETER_BOT_ZN_2 2555042.92 0.00 2555042.92 54821.81 2609864.73 2750345.05 4157.82 26.98 4575.20 163.03
PERIMETER_BOT_ZN_1 4301615.29 0.00 4301615.29 82232.77 4383848.06 4267912.63 4250.74 199.74 4309.52 163.03
PERIMETER_BOT_ZN_4 3867561.70 0.00 3867561.70 54821.81 3922383.51 2750345.05 4037.24 0.00 4722.76 163.03
PERIMETER_MID_ZN_3 29471419.01 0.00 29471419.01 192855.40 29664274.42 42678193.03 4776.34 586.84 3396.82 11.78
PERIMETER_MID_ZN_2 25359183.05 0.00 25359183.05 128570.18 25487753.23 27503450.52 4260.22 6.85 4492.93 920.78
PERIMETER_MID_ZN_1 40671393.72 0.00 40671393.72 192855.40 40864249.12 42679126.28 4330.57 505.40 3924.03 11.78
PERIMETER_MID_ZN_4 27148966.66 0.00 27148966.66 128570.18 27277536.84 27503450.52 4239.82 0.46 4519.72 11.78
PERIMETER_TOP_ZN_3 2938843.66 0.00 2938843.66 239446.20 3178289.86 4267819.30 4842.86 607.91 3309.24 35.92
PERIMETER_TOP_ZN_2 2522628.03 0.00 2522628.03 159630.69 2682258.72 2750345.05 4264.61 2.80 4492.59 35.92
PERIMETER_TOP_ZN_1 3852779.31 0.00 3852779.31 239446.20 4092225.51 4267912.63 4394.96 567.43 3797.61 35.92
PERIMETER_TOP_ZN_4 2722711.15 0.00 2722711.15 159630.69 2882341.84 2750345.05 4255.77 0.59 4503.64 35.92
DATACENTER_BOT_ZN_6 244303.03 0.00 244303.03 0.00 244303.03 389144.62 4419.00 504.00 3837.00 0.00
DATACENTER_MID_ZN_6 2443030.26 0.00 2443030.26 0.00 2443030.26 3891446.16 4419.00 504.00 3837.00 0.00
DATACENTER_TOP_ZN_6 244303.03 0.00 244303.03 0.00 244303.03 389144.62 4419.00 504.00 3837.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00 0.00 8423799.00 8760.00 0.00 0.00 0.00
Total Facility 0.34E+10 0.00 0.34E+10 7500774.64 0.34E+10 0.50E+10 8760.00 3265.93 4894.04 1235.26


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.6109 0.0000 1.6109 0.0000 1.6109 0.9949 1448.44 2841.00 1653.56
CORE_BOTTOM 1.0678 0.0000 1.0678 0.0000 1.0678 1.0778 4086.27 233.62 1623.10
CORE_MID 9.5331 0.0000 9.5331 0.0000 9.5331 10.7782 3828.22 585.27 1529.51
CORE_TOP 0.9341 0.0000 0.9341 0.0000 0.9341 1.0778 3917.44 651.60 1373.96
PERIMETER_BOT_ZN_3 0.1446 0.0000 0.1446 0.0020 0.1466 0.1353 1929.31 271.69 3742.01
PERIMETER_BOT_ZN_2 0.1148 0.0000 0.1148 0.0013 0.1161 0.0872 1503.85 26.57 4412.58
PERIMETER_BOT_ZN_1 0.1950 0.0000 0.1950 0.0020 0.1970 0.1353 1593.79 199.66 4149.55
PERIMETER_BOT_ZN_4 0.1744 0.0000 0.1744 0.0013 0.1757 0.0872 1383.27 0.00 4559.73
PERIMETER_MID_ZN_3 1.3734 0.0000 1.3734 0.0046 1.3780 1.3533 1969.13 586.84 3387.03
PERIMETER_MID_ZN_2 1.0919 0.0000 1.0919 0.0033 1.0951 0.8721 1443.23 5.17 3585.60
PERIMETER_MID_ZN_1 1.8968 0.0000 1.8968 0.0046 1.9014 1.3533 1523.18 505.40 3914.42
PERIMETER_MID_ZN_4 1.2653 0.0000 1.2653 0.0031 1.2684 0.8721 1434.60 0.42 4507.99
PERIMETER_TOP_ZN_3 0.1365 0.0000 0.1365 0.0057 0.1422 0.1353 2044.12 606.71 3292.17
PERIMETER_TOP_ZN_2 0.1172 0.0000 0.1172 0.0038 0.1211 0.0872 1473.60 2.42 4466.98
PERIMETER_TOP_ZN_1 0.1792 0.0000 0.1792 0.0057 0.1850 0.1353 1593.09 566.19 3783.72
PERIMETER_TOP_ZN_4 0.1265 0.0000 0.1265 0.0038 0.1303 0.0872 1465.05 0.20 4477.75
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0130 1602.00 504.00 3837.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1296 1602.00 504.00 3837.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0130 1602.00 504.00 3837.00
DATACENTER_BASEMENT_ZN_6 0.0000 0.0000 0.0000 0.0000 0.0000 0.2805 5943.00 0.00 0.00
Total Facility 157.5700 0.0000 157.5700 0.1816 157.7516 157.9346 5943.00 3262.13 4606.68


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 54817639.58 0.00 54817639.58 48026705.38 4037.24 0.00 4722.76 163.03
VAV_MID WITH REHEAT 0.47E+09 0.00 0.47E+09 0.48E+09 4239.49 0.00 4520.51 11.78
VAV_TOP WITH REHEAT 46557202.62 0.00 46557202.62 48026705.38 4246.17 2.15 4511.68 35.92
CAV_BAS 52770914.23 0.00 52770914.23 29876159.83 4058.01 0.26 4701.73 240.62
AIRLOOP DATACENTER BOT 353655.65 0.00 353655.65 389144.62 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 3536556.46 0.00 3536556.46 3891446.16 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 353655.65 0.00 353655.65 389144.62 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 2.4559 0.0000 2.4559 1.5229 1383.27 0.00 4559.73
VAV_MID WITH REHEAT 22.0768 0.0000 22.0768 15.2292 1434.26 0.00 4508.74
VAV_TOP WITH REHEAT 2.1621 0.0000 2.1621 1.5229 1459.24 1.71 4482.05
CAV_BAS 2.3320 0.0000 2.3320 0.9949 1446.67 0.00 4496.33
AIRLOOP DATACENTER BOT 0.0165 0.0000 0.0165 0.0130 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1653 0.0000 0.1653 0.1296 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0165 0.0000 0.0165 0.0130 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 0.00 1707.51 0.00 0.00 0.00 3015.25 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 0.00 1478.85 0.00 0.00 0.00 3041.67 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 0.00 1416.52 0.00 0.00 0.00 3108.75 0.00 0.00 0.00
CAV_BAS 0.00 0.00 1899.10 0.00 0.00 0.00 2840.67 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 0.0000 4.7536 0.0000 0.0000 0.0000 2.4067 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 0.0000 39.3196 0.0000 0.0000 0.0000 24.1764 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 0.0000 3.9112 0.0000 0.0000 0.0000 2.3977 0.0000 0.0000 0.0000
CAV_BAS 0.0000 0.0000 5.7703 0.0000 0.0000 0.0000 1.5112 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0226 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2264 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0226 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 7
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1361
Defaulted Fields 1168
Fields with Defaults 3868
Autosized Fields 316
Autosizable Fields 394
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 25543.31 287925.10 22-JAN-05:00 1603116.60 30-AUG-15:50
Electricity:Building 16699.48 216770.18 28-MAY-17:10 971964.54 12-DEC-08:10
Electricity:Zone:BASEMENT 559.97 14115.26 01-JAN-00:10 25295.37 02-JAN-08:10
Electricity:SpaceType:GENERAL 16699.48 216770.18 28-MAY-17:10 971964.54 12-DEC-08:10
InteriorLights:Electricity 2023.08 9514.02 01-JAN-10:00 193957.09 25-OCT-07:10
InteriorLights:Electricity:Zone:BASEMENT 135.58 657.72 01-JAN-00:10 11837.83 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 2023.08 9514.02 01-JAN-10:00 193957.09 25-OCT-07:10
LightsWired:InteriorLights:Electricity 2023.08 9514.02 01-JAN-10:00 193957.09 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 135.58 657.72 01-JAN-00:10 11837.83 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 2023.08 9514.02 01-JAN-10:00 193957.09 25-OCT-07:10
Electricity:Zone:CORE_BOTTOM 411.37 5043.91 01-JAN-00:10 27837.83 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 121.76 590.68 01-JAN-00:10 10631.20 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 121.76 590.68 01-JAN-00:10 10631.20 02-JAN-08:10
Electricity:Zone:CORE_MID 4113.71 50438.97 01-JAN-00:10 278377.67 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 1217.58 5906.80 01-JAN-00:10 106312.04 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 1217.58 5906.80 01-JAN-00:10 106312.04 02-JAN-08:10
Electricity:Zone:CORE_TOP 411.37 5043.90 01-JAN-00:10 27837.77 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 121.76 590.68 01-JAN-00:10 10631.20 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 121.76 590.68 01-JAN-00:10 10631.20 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 45.30 594.46 26-MAR-17:10 3374.64 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 8.93 35.29 01-JAN-10:00 1214.09 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 8.93 35.29 01-JAN-10:00 1214.09 25-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_2 29.14 383.09 28-MAY-17:10 2160.02 12-DEC-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 5.70 22.74 01-JAN-08:00 767.68 12-DEC-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 5.70 22.74 01-JAN-08:00 767.68 12-DEC-08:10
Electricity:Zone:PERIMETER_BOT_ZN_1 45.10 594.47 12-MAR-17:10 3367.21 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 8.74 35.29 01-JAN-08:00 1206.62 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 8.74 35.29 01-JAN-08:00 1206.62 25-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_4 29.15 383.09 12-MAR-17:10 2180.87 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 5.72 22.74 01-JAN-09:50 788.54 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 5.72 22.74 01-JAN-09:50 788.54 25-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_3 452.96 5944.59 26-MAR-17:10 33772.17 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 89.31 352.88 01-JAN-09:50 12166.65 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 89.31 352.88 01-JAN-09:50 12166.65 25-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_2 291.35 3830.92 28-MAY-17:10 21604.35 12-DEC-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 57.00 227.41 01-JAN-08:00 7680.93 12-DEC-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 57.00 227.41 01-JAN-08:00 7680.93 12-DEC-08:10
Electricity:Zone:PERIMETER_MID_ZN_1 451.05 5944.68 12-MAR-17:10 33700.43 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 87.39 352.89 01-JAN-08:00 12094.58 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 87.39 352.89 01-JAN-08:00 12094.58 25-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_4 291.50 3830.90 12-MAR-17:10 21810.15 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 57.14 227.41 01-JAN-09:50 7886.82 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 57.14 227.41 01-JAN-09:50 7886.82 25-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_3 45.30 594.46 26-MAR-17:10 3377.09 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 8.93 35.29 01-JAN-09:50 1216.54 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 8.93 35.29 01-JAN-09:50 1216.54 25-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_2 29.14 383.09 28-MAY-17:10 2160.34 12-DEC-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 5.70 22.74 01-JAN-08:00 768.00 12-DEC-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 5.70 22.74 01-JAN-08:00 768.00 12-DEC-08:10
Electricity:Zone:PERIMETER_TOP_ZN_1 45.10 594.47 12-MAR-17:10 3369.92 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 8.74 35.29 01-JAN-08:00 1209.33 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 8.74 35.29 01-JAN-08:00 1209.33 25-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_4 29.15 383.09 12-MAR-17:10 2180.94 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 5.71 22.74 01-JAN-09:50 788.60 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 5.71 22.74 01-JAN-09:50 788.60 25-OCT-07:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7533.08 95093.58 01-JAN-00:10 382970.28 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 38.23 185.45 01-JAN-00:10 3337.76 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 38.23 185.45 01-JAN-00:10 3337.76 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 157.14 1964.44 01-JAN-00:10 8079.39 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 3.26 15.83 01-JAN-00:10 284.97 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 3.26 15.83 01-JAN-00:10 284.97 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1571.44 19644.38 01-JAN-00:10 80793.90 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 32.64 158.32 01-JAN-00:10 2849.68 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 32.64 158.32 01-JAN-00:10 2849.68 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 157.14 1964.44 01-JAN-00:10 8079.39 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 3.26 15.83 01-JAN-00:10 284.97 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 3.26 15.83 01-JAN-00:10 284.97 02-JAN-08:10
InteriorEquipment:Electricity 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 3769.76 974.35 10-JAN-04:40 390054.01 17-AUG-14:10
HeatRejection:Electricity 770.22 153.55 10-JAN-07:20 55581.51 10-SEP-15:00
General:HeatRejection:Electricity 770.22 153.55 10-JAN-07:20 55581.51 10-SEP-15:00
Electricity:HVAC 1470.30 9387.69 10-JAN-04:40 131797.85 30-AUG-16:00
ExteriorEquipment:Electricity 3333.12 46194.44 01-JAN-00:10 188992.77 12-DEC-08:20
Transformer:ExteriorEquipment:Electricity 54.48 979.82 01-JAN-00:10 3384.80 25-OCT-07:20
ElectricityPurchased:Facility 25543.31 287925.10 22-JAN-05:00 1603116.60 30-AUG-15:50
ElectricityPurchased:Plant 25543.31 287925.10 22-JAN-05:00 1603116.60 30-AUG-15:50
Cogeneration:ElectricityPurchased 25543.31 287925.10 22-JAN-05:00 1603116.60 30-AUG-15:50
General:Cogeneration:ElectricityPurchased 25543.31 287925.10 22-JAN-05:00 1603116.60 30-AUG-15:50
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 25543.31 287925.10 22-JAN-05:00 1603116.60 30-AUG-15:50
ElectricityNet:Plant 25543.31 287925.10 22-JAN-05:00 1603116.60 30-AUG-15:50
Cogeneration:ElectricityNet 25543.31 287925.10 22-JAN-05:00 1603116.60 30-AUG-15:50
General:Cogeneration:ElectricityNet 25543.31 287925.10 22-JAN-05:00 1603116.60 30-AUG-15:50
Fans:Electricity 915.75 5897.48 03-JAN-00:20 91221.95 30-AUG-16:00
General:Fans:Electricity 915.75 5897.48 03-JAN-00:20 91221.95 30-AUG-16:00
ExteriorLights:Electricity 325.14 0.00 01-JAN-07:30 37611.08 01-JAN-06:10
General:ExteriorLights:Electricity 325.14 0.00 01-JAN-07:30 37611.08 01-JAN-06:10
ComputerHVAC:ExteriorEquipment:Electricity 1424.02 18032.55 01-JAN-00:10 72130.20 31-MAR-23:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
HeatRecovery:Electricity 61.82 0.00 01-JAN-00:10 5613.48 02-JAN-10:10
General:HeatRecovery:Electricity 61.82 0.00 01-JAN-00:10 5613.48 02-JAN-10:10
Cooling:Electricity 2459.32 1038.20 10-JAN-07:10 296302.86 17-AUG-14:10
General:Cooling:Electricity 2459.32 1038.20 10-JAN-07:10 296302.86 17-AUG-14:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 978.48 666.51 01-JAN-00:10 68241.86 14-SEP-16:00
General:Pumps:Electricity 978.48 666.51 01-JAN-00:10 68241.86 14-SEP-16:00
WIRED_LTG_ELECTRICITY 56.85 0.00 01-JAN-00:10 5450.19 25-OCT-07:20
WIRED_INT_EQUIP 5334.97 88964.76 31-MAR-23:10 305206.10 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 678.01 5695.87 01-JAN-00:10 429576.91 06-FEB-06:10
NaturalGas:Plant 678.01 5695.87 01-JAN-00:10 429576.91 06-FEB-06:10
Heating:NaturalGas 82.69 0.00 01-JAN-00:10 423881.04 06-FEB-06:10
Boiler:Heating:NaturalGas 82.69 0.00 01-JAN-00:10 423881.04 06-FEB-06:10
WaterSystems:NaturalGas 595.32 5695.87 01-JAN-00:10 73380.93 20-JAN-12:20
Water Heater:WaterSystems:NaturalGas 595.32 5695.87 01-JAN-00:10 73380.93 20-JAN-12:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 16267.25 4619.88 10-JAN-07:10 1723418.14 07-AUG-14:40
PlantLoopCoolingDemand:HVAC 16267.25 4619.88 10-JAN-07:10 1723418.14 07-AUG-14:40
CoolingCoils:PlantLoopCoolingDemand 16267.25 4619.88 10-JAN-07:10 1723418.14 07-AUG-14:40
DistrictCooling:Facility 7190.82 87779.68 22-JAN-06:00 370154.94 21-AUG-14:00
DistrictCooling:HVAC 7190.82 87779.68 22-JAN-06:00 370154.94 21-AUG-14:00
Cooling:DistrictCooling 7190.82 87779.68 22-JAN-06:00 370154.94 21-AUG-14:00
General:Cooling:DistrictCooling 7190.82 87779.68 22-JAN-06:00 370154.94 21-AUG-14:00


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 12784.15 0.00 01-JAN-00:10 0.00 30-AUG-15:50
Water:Plant 12784.15 0.00 01-JAN-00:10 0.00 30-AUG-15:50
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Facility 12784.15 0.00 01-JAN-00:10 0.00 30-AUG-15:50
MainsWater:Plant 12784.15 0.00 01-JAN-00:10 0.00 30-AUG-15:50
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 10503.98 0.00 01-JAN-00:10 0.00 30-AUG-15:50
General:HeatRejection:Water 10503.98 0.00 01-JAN-00:10 0.00 30-AUG-15:50
HeatRejection:MainsWater 10503.98 0.00 01-JAN-00:10 0.00 30-AUG-15:50
General:HeatRejection:MainsWater 10503.98 0.00 01-JAN-00:10 0.00 30-AUG-15:50


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 83030.99 102297.59 10-JAN-04:40 8852558.97 02-AUG-14:10
EnergyTransfer:Building 20258.81 92646.70 22-JAN-07:50 1468300.60 30-AUG-16:00
EnergyTransfer:Zone:BASEMENT 644.88 0.00 01-JAN-00:10 70466.48 13-NOV-06:10
Heating:EnergyTransfer 27.08 0.00 01-JAN-00:10 205165.29 06-FEB-06:10
Heating:EnergyTransfer:Zone:BASEMENT 5.19 0.00 01-JAN-00:10 17838.49 09-SEP-16:30
General:Heating:EnergyTransfer 27.08 0.00 01-JAN-00:10 205165.29 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 5.19 0.00 01-JAN-00:10 17838.49 09-SEP-16:30
Cooling:EnergyTransfer 20231.73 92138.46 22-JAN-07:40 1468300.60 30-AUG-16:00
Cooling:EnergyTransfer:Zone:BASEMENT 639.70 0.00 01-JAN-00:10 70466.48 13-NOV-06:10
General:Cooling:EnergyTransfer 20231.73 92138.46 22-JAN-07:40 1468300.60 30-AUG-16:00
General:Cooling:EnergyTransfer:Zone:BASEMENT 639.70 0.00 01-JAN-00:10 70466.48 13-NOV-06:10
EnergyTransfer:Zone:CORE_BOTTOM 697.20 0.00 01-JAN-00:10 50267.76 27-NOV-06:10
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 697.20 0.00 01-JAN-00:10 50267.76 27-NOV-06:10
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 697.20 0.00 01-JAN-00:10 50267.76 27-NOV-06:10
EnergyTransfer:Zone:CORE_MID 5080.03 0.00 01-JAN-00:10 427276.82 10-APR-05:10
Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_MID 5080.03 0.00 01-JAN-00:10 427276.82 10-APR-05:10
General:Cooling:EnergyTransfer:Zone:CORE_MID 5080.03 0.00 01-JAN-00:10 427276.82 10-APR-05:10
EnergyTransfer:Zone:CORE_TOP 523.78 0.00 01-JAN-00:10 45884.76 18-JUL-15:30
Heating:EnergyTransfer:Zone:CORE_TOP 0.55 0.00 01-JAN-00:10 39310.16 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 0.55 0.00 01-JAN-00:10 39310.16 06-FEB-05:10
Cooling:EnergyTransfer:Zone:CORE_TOP 523.23 0.00 01-JAN-00:10 45884.76 18-JUL-15:30
General:Cooling:EnergyTransfer:Zone:CORE_TOP 523.23 0.00 01-JAN-00:10 45884.76 18-JUL-15:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 99.76 0.00 01-JAN-00:10 10130.20 21-AUG-14:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 99.76 0.00 01-JAN-00:10 10130.20 21-AUG-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 99.76 0.00 01-JAN-00:10 10130.20 21-AUG-14:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 77.78 0.00 01-JAN-00:10 9671.32 11-SEP-09:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 77.78 0.00 01-JAN-00:10 9671.32 11-SEP-09:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 77.78 0.00 01-JAN-00:10 9671.32 11-SEP-09:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 124.94 0.00 01-JAN-00:10 14927.89 06-NOV-13:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 124.94 0.00 01-JAN-00:10 14927.89 06-NOV-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 124.94 0.00 01-JAN-00:10 14927.89 06-NOV-13:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 117.63 0.00 01-JAN-00:10 14098.04 30-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 117.63 0.00 01-JAN-00:10 14098.04 30-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 117.63 0.00 01-JAN-00:10 14098.04 30-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 746.15 0.00 01-JAN-00:10 88319.76 21-AUG-14:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 2.85 0.00 01-JAN-00:10 49772.38 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 2.85 0.00 01-JAN-00:10 49772.38 06-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 743.29 0.00 01-JAN-00:10 88319.76 21-AUG-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 743.29 0.00 01-JAN-00:10 88319.76 21-AUG-14:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 657.97 0.00 01-JAN-00:10 98654.96 03-MAY-09:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.08 0.00 01-JAN-00:10 29913.39 21-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.08 0.00 01-JAN-00:10 29913.39 21-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 656.89 0.00 01-JAN-00:10 98654.96 03-MAY-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 656.89 0.00 01-JAN-00:10 98654.96 03-MAY-09:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1025.21 0.00 01-JAN-00:10 142811.32 06-NOV-14:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.28 0.00 01-JAN-00:10 27509.05 21-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.28 0.00 01-JAN-00:10 27509.05 21-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1024.93 0.00 01-JAN-00:10 142811.32 06-NOV-14:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1024.93 0.00 01-JAN-00:10 142811.32 06-NOV-14:10
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 704.69 0.00 01-JAN-00:10 113620.11 30-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.28 0.00 01-JAN-00:10 22979.40 21-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.28 0.00 01-JAN-00:10 22979.40 21-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 704.41 0.00 01-JAN-00:10 113620.11 30-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 704.41 0.00 01-JAN-00:10 113620.11 30-AUG-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 79.43 0.00 01-JAN-00:10 11379.31 06-FEB-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 2.63 0.00 01-JAN-00:10 11379.31 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 2.63 0.00 01-JAN-00:10 11379.31 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 76.79 0.00 01-JAN-00:10 10113.06 19-JUL-15:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 76.79 0.00 01-JAN-00:10 10113.06 19-JUL-15:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 70.05 0.00 01-JAN-00:10 10239.06 03-MAY-09:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 1.07 0.00 01-JAN-00:10 8253.54 06-FEB-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 1.07 0.00 01-JAN-00:10 8253.54 06-FEB-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 68.97 0.00 01-JAN-00:10 10239.06 03-MAY-09:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 68.97 0.00 01-JAN-00:10 10239.06 03-MAY-09:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 105.22 0.00 01-JAN-00:10 15627.21 06-NOV-14:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 0.85 0.00 01-JAN-00:10 9152.60 06-FEB-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 0.85 0.00 01-JAN-00:10 9152.60 06-FEB-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 104.37 0.00 01-JAN-00:10 15627.21 06-NOV-14:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 104.37 0.00 01-JAN-00:10 15627.21 06-NOV-14:20
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 74.30 0.00 01-JAN-00:10 12211.97 30-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.63 0.00 01-JAN-00:10 5815.69 06-FEB-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.63 0.00 01-JAN-00:10 5815.69 06-FEB-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 73.68 0.00 01-JAN-00:10 12211.97 30-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 73.68 0.00 01-JAN-00:10 12211.97 30-AUG-16:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 76.77 0.00 01-JAN-00:10 7405.64 10-OCT-15:30
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.58 0.00 01-JAN-00:10 3680.20 12-MAR-14:30
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.58 0.00 01-JAN-00:10 3680.20 12-MAR-14:30
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 76.19 0.00 01-JAN-00:10 7405.64 10-OCT-15:30
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 76.19 0.00 01-JAN-00:10 7405.64 10-OCT-15:30
EnergyTransfer:Zone:MIDFLOOR_PLENUM 548.48 0.00 01-JAN-00:10 55863.42 30-AUG-16:00
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 5.52 0.00 01-JAN-00:10 22754.28 29-JAN-11:40
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 5.52 0.00 01-JAN-00:10 22754.28 29-JAN-11:40
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 542.96 0.00 01-JAN-00:10 55863.42 30-AUG-16:00
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 542.96 0.00 01-JAN-00:10 55863.42 30-AUG-16:00
EnergyTransfer:Zone:TOPFLOOR_PLENUM 95.31 0.00 01-JAN-00:10 17371.23 07-JUL-14:50
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 5.39 0.00 01-JAN-00:10 13565.22 06-FEB-06:20
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 5.39 0.00 01-JAN-00:10 13565.22 06-FEB-06:20
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 89.92 0.00 01-JAN-00:10 17371.23 07-JUL-14:50
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 89.92 0.00 01-JAN-00:10 17371.23 07-JUL-14:50
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 140.33 958.38 10-JAN-08:00 7829.21 16-APR-18:20
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 140.33 958.38 10-JAN-08:00 7829.21 16-APR-18:20
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 140.33 958.38 10-JAN-08:00 7829.21 16-APR-18:20
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1278.16 1963.86 10-JAN-07:00 73508.80 16-APR-18:10
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1278.16 1963.86 10-JAN-07:00 73508.80 16-APR-18:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1278.16 1963.86 10-JAN-07:00 73508.80 16-APR-18:10
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 124.52 3.80 13-JAN-07:50 7461.95 23-APR-18:10
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.17 0.00 01-JAN-00:10 519.55 10-JAN-04:50
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.17 0.00 01-JAN-00:10 519.55 10-JAN-04:50
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 124.35 0.00 04-JAN-03:20 7461.95 23-APR-18:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 124.35 0.00 04-JAN-03:20 7461.95 23-APR-18:10
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7166.23 87779.68 22-JAN-06:00 367527.12 21-AUG-16:00
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7166.23 87779.68 22-JAN-06:00 367527.12 21-AUG-16:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7166.23 87779.68 22-JAN-06:00 367527.12 21-AUG-16:00
PlantLoopHeatingDemand:Facility 378.25 0.00 01-JAN-00:10 325155.45 21-DEC-07:10
PlantLoopHeatingDemand:Plant 321.87 0.00 01-JAN-00:10 40639.71 23-JAN-12:20
WaterSystems:PlantLoopHeatingDemand 321.87 0.00 01-JAN-00:10 40639.71 23-JAN-12:20
General:WaterSystems:PlantLoopHeatingDemand 321.87 0.00 01-JAN-00:10 40639.71 23-JAN-12:20
EnergyTransfer:HVAC 18573.90 9013.49 10-JAN-21:10 2210628.47 06-OCT-14:00
HeatingCoils:EnergyTransfer 56.38 0.00 01-JAN-00:10 314398.69 06-FEB-06:10
PlantLoopHeatingDemand:HVAC 56.38 0.00 01-JAN-00:10 314398.69 06-FEB-06:10
HeatingCoils:PlantLoopHeatingDemand 56.38 0.00 01-JAN-00:10 314398.69 06-FEB-06:10
CoolingCoils:EnergyTransfer 15828.99 3581.68 10-JAN-07:10 1699646.06 07-AUG-14:40
DistrictHeating:Facility 0.00 0.00 01-JAN-00:10 13.56 31-MAY-23:40
DistrictHeating:HVAC 0.00 0.00 01-JAN-00:10 13.56 31-MAY-23:40
Heating:DistrictHeating 0.00 0.00 01-JAN-00:10 13.56 31-MAY-23:40
General:Heating:DistrictHeating 0.00 0.00 01-JAN-00:10 13.56 31-MAY-23:40
HeatRecoveryForHeating:EnergyTransfer 5.99 0.00 01-JAN-00:10 127001.52 20-DEC-08:00
HeatRecoveryForCooling:EnergyTransfer 2682.53 0.00 01-JAN-00:10 644836.39 07-OCT-08:00
EnergyTransfer:Plant 44198.28 0.00 01-JAN-00:10 5658202.36 14-SEP-16:00
LoopToLoop:EnergyTransfer 15644.87 0.00 01-JAN-00:10 1813394.13 14-SEP-16:00
WaterSystems:EnergyTransfer 321.87 0.00 01-JAN-00:10 40639.71 23-JAN-12:20
WaterUse:WaterSystems:EnergyTransfer 321.87 0.00 01-JAN-00:10 40639.71 23-JAN-12:20
Boilers:EnergyTransfer 55.71 0.00 01-JAN-00:10 342636.33 06-FEB-06:10
Chillers:EnergyTransfer 13077.38 0.00 01-JAN-00:10 1784750.67 14-SEP-16:00
HeatRejection:EnergyTransfer 15098.45 0.00 01-JAN-00:10 2035067.52 14-SEP-16:00
General:HeatRejection:EnergyTransfer 15098.45 0.00 01-JAN-00:10 2035067.52 14-SEP-16:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 5.185 -639.698 0.000 0.000 92.612 135.577 424.397 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.000 -18.074
CORE_BOTTOM 0.000 0.000 0.000 -697.202 0.000 0.000 83.608 121.758 289.614 0.000 0.000 0.000 202.223 0.000 0.000 0.000 0.000 -0.002
CORE_MID 0.000 0.000 0.000 -5080.017 0.000 0.000 845.738 1217.578 2896.128 0.000 0.000 0.000 120.574 0.000 0.000 0.000 0.000 -0.011
CORE_TOP 0.000 0.000 0.550 -523.224 0.000 0.000 86.224 121.758 289.613 0.000 0.000 0.000 25.080 0.000 0.000 0.000 0.000 -0.003
PERIMETER_BOT_ZN_3 0.000 0.000 0.000 -99.762 0.000 0.000 10.600 8.930 36.365 31.468 0.000 0.105 35.353 0.000 -22.613 0.000 -0.447 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.000 -77.776 0.000 0.000 6.813 5.702 23.435 45.739 0.000 0.070 10.046 0.000 -13.734 0.000 -0.296 -0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.000 -124.944 0.000 0.000 10.517 8.737 36.366 78.750 0.000 0.098 12.585 0.000 -21.629 0.000 -0.479 -0.000
PERIMETER_BOT_ZN_4 0.000 0.000 0.000 -117.633 0.000 0.000 6.760 5.717 23.435 43.552 0.000 0.058 56.063 0.000 -17.592 0.000 -0.360 0.000
PERIMETER_MID_ZN_3 0.000 0.000 2.854 -743.282 0.000 0.000 108.811 89.311 363.654 325.151 0.000 2.366 61.229 0.000 -200.827 0.000 -9.269 0.000
PERIMETER_MID_ZN_2 0.000 0.000 1.084 -656.879 0.000 0.000 50.886 57.002 234.352 457.199 0.000 1.423 0.023 0.000 -130.630 0.000 -6.655 -7.781
PERIMETER_MID_ZN_1 0.000 0.000 0.283 -1024.912 0.000 0.000 105.731 87.392 363.660 786.553 0.000 2.116 0.005 0.000 -210.399 0.000 -11.157 -99.265
PERIMETER_MID_ZN_4 0.000 0.000 0.283 -704.402 0.000 0.000 69.280 57.144 234.351 446.812 0.000 1.371 50.214 0.000 -147.848 0.000 -7.205 -0.005
PERIMETER_TOP_ZN_3 0.000 0.000 2.634 -76.792 0.000 0.000 11.003 8.931 36.365 32.408 0.000 0.275 5.224 0.000 -18.977 0.000 -1.070 -0.000
PERIMETER_TOP_ZN_2 0.000 0.000 1.073 -68.971 0.000 0.000 6.986 5.700 23.435 45.661 0.000 0.166 0.003 0.000 -12.488 0.000 -0.776 -0.785
PERIMETER_TOP_ZN_1 0.000 0.000 0.850 -104.372 0.000 0.000 10.667 8.739 36.366 78.475 0.000 0.246 0.000 0.000 -20.207 0.000 -1.313 -9.451
PERIMETER_TOP_ZN_4 0.000 0.000 0.626 -73.674 0.000 0.000 7.015 5.714 23.435 44.589 0.000 0.166 7.109 0.000 -14.134 0.000 -0.845 -0.000
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -140.325 0.000 0.000 0.950 3.264 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -17.769
DATACENTER_MID_ZN_6 0.000 0.000 0.000 -1278.161 0.000 0.000 9.499 32.637 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -302.780
DATACENTER_TOP_ZN_6 0.000 0.000 0.166 -124.350 0.000 0.000 0.950 3.264 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -33.910
DATACENTER_BASEMENT_ZN_6 0.000 -7166.230 0.000 0.000 0.000 0.000 20.569 38.227 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -387.423
GROUNDFLOOR_PLENUM 0.582 -76.189 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.179 76.419 0.000 0.000 0.000 -0.991 0.000
MIDFLOOR_PLENUM 5.521 -542.951 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 3.368 550.496 0.000 0.000 0.000 -16.433 0.000
TOPFLOOR_PLENUM 5.388 -89.922 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.292 85.942 0.000 0.000 0.000 -1.699 -0.001
Total Facility 11.491 -7875.293 15.587 -12356.376 0.000 0.000 1545.218 2023.080 14676.396 2416.356 0.000 12.296 1298.587 0.000 -831.078 0.000 -58.996 -877.261


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 09-JAN-04:12 0.00 0.00 0.00 -100674.72 0.00 0.00 0.00 657.72 13457.54 0.00 0.00 0.00 86559.45 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 13-NOV-04:02 0.00 0.00 0.00 -84100.34 0.00 0.00 0.00 590.68 5937.65 0.00 0.00 0.00 77572.02 0.00 -0.00 0.00 0.00 0.00
CORE_MID 14-APR-05:04 0.00 0.00 0.00 -733633.34 0.00 0.00 8371.48 11812.12 76473.61 0.00 0.00 0.00 636976.12 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 08-SEP-05:04 0.00 0.00 0.00 -73279.75 0.00 0.00 841.08 1181.21 7647.36 0.00 0.00 0.00 63610.10 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 03-JUL-05:03 0.00 0.00 0.00 -12670.63 0.00 0.00 102.77 148.31 960.25 0.00 0.00 2.91 11698.42 0.00 -242.04 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 29-MAY-08:62 0.00 0.00 0.00 -16208.99 0.00 0.00 23.78 22.74 464.11 11417.16 0.00 0.00 4283.60 0.00 -0.00 0.00 -2.41 0.00
PERIMETER_BOT_ZN_1 01-JAN-13:32 0.00 0.00 0.00 -20112.08 0.00 0.00 34.41 35.29 720.19 16650.16 0.00 0.00 2682.12 0.00 -0.00 0.00 -10.10 0.00
PERIMETER_BOT_ZN_4 25-JUN-15:52 0.00 0.00 0.00 -21302.70 0.00 0.00 21.90 22.74 464.11 9397.43 0.00 5.37 11391.16 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 14-AUG-03:02 0.00 0.00 0.00 -119318.33 0.00 0.00 0.00 741.66 7455.61 0.00 0.00 41.29 114379.20 0.00 -3299.43 0.00 0.00 0.00
PERIMETER_MID_ZN_2 29-MAY-09:32 0.00 0.00 0.00 -167695.22 0.00 0.00 230.66 227.41 4641.14 93557.97 0.00 18.03 69020.01 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 10-DEC-14:32 0.00 0.00 0.00 -187602.78 0.00 0.00 345.73 352.89 7201.95 147041.59 0.00 0.00 32792.43 0.00 -0.00 0.00 -131.81 0.00
PERIMETER_MID_ZN_4 03-SEP-15:42 0.00 0.00 0.00 -176792.98 0.00 0.00 228.77 227.41 4641.11 106973.43 0.00 489.13 64233.13 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 10-SEP-14:52 0.00 0.00 0.00 -15397.92 0.00 0.00 41.82 35.29 720.18 3778.41 0.00 77.68 10744.54 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 29-MAY-10:42 0.00 0.00 0.00 -17051.46 0.00 0.00 23.07 22.74 464.11 5939.28 0.00 11.81 10590.45 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 01-JAN-14:12 0.00 0.00 0.00 -21144.78 0.00 0.00 33.65 35.29 720.19 15362.81 0.00 0.00 5022.63 0.00 -0.00 0.00 -29.79 0.00
PERIMETER_TOP_ZN_4 03-SEP-15:42 0.00 0.00 0.00 -19454.82 0.00 0.00 21.57 22.74 464.11 10592.53 0.00 54.70 8299.16 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 16-APR-18:15 0.00 0.00 0.00 -7829.13 0.00 0.00 0.00 15.83 7794.42 0.00 0.00 0.00 18.88 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 16-APR-18:02 0.00 0.00 0.00 -73508.53 0.00 0.00 0.00 158.32 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -4594.02
DATACENTER_TOP_ZN_6 23-APR-18:10 0.00 0.00 0.00 -7461.95 0.00 0.00 0.00 15.83 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -348.30
DATACENTER_BASEMENT_ZN_6 21-AUG-16:00 0.00 -367527.12 0.00 0.00 0.00 0.00 2183.10 3337.76 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -17626.26
GROUNDFLOOR_PLENUM 02-JAN-06:15 0.00 -9123.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9136.96 0.00 -0.00 0.00 -13.44 0.00
MIDFLOOR_PLENUM 23-JUN-05:02 0.00 -76132.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.98 76116.40 0.00 -0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 07-JUL-14:50 0.00 -17370.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31.20 17339.48 0.00 -0.00 0.00 0.00 0.00
Total Facility 29-AUG-05:02 0.00 -394312.10 0.00 -1367551.41 0.00 0.00 15990.51 22094.05 616289.16 0.00 0.00 0.00 1140203.70 0.00 -32281.51 0.00 -432.39 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 09-SEP-16:13 0.00 0.00 18736.84 0.00 0.00 0.00 433.87 657.72 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -33285.98
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_TOP 06-FEB-05:01 0.00 0.00 51777.21 0.00 0.00 0.00 0.00 1181.21 5937.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -58896.04
PERIMETER_BOT_ZN_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 06-FEB-05:01 0.00 0.00 96770.40 0.00 0.00 0.00 0.00 1483.13 7455.61 0.00 0.00 0.00 0.00 0.00 -31587.20 0.00 -1176.23 -72945.71
PERIMETER_MID_ZN_2 21-DEC-05:01 0.00 0.00 73407.26 0.00 0.00 0.00 0.00 955.79 4804.68 0.00 0.00 0.00 0.00 0.00 -26508.02 0.00 -1317.58 -51342.14
PERIMETER_MID_ZN_1 21-DEC-06:01 0.00 0.00 98437.01 0.00 0.00 0.00 1460.97 1483.16 9602.60 0.00 0.00 0.00 0.00 0.00 -39496.61 0.00 -588.35 -70898.78
PERIMETER_MID_ZN_4 21-DEC-06:01 0.00 0.00 61678.84 0.00 0.00 0.00 941.50 955.79 6188.15 0.00 0.00 0.00 0.00 0.00 -26074.13 0.00 -390.36 -43299.78
PERIMETER_TOP_ZN_3 06-FEB-04:01 0.00 0.00 13081.53 0.00 0.00 0.00 0.00 74.17 745.56 0.00 0.00 0.00 0.00 0.00 -2457.57 0.00 -126.34 -11317.34
PERIMETER_TOP_ZN_2 06-FEB-04:01 0.00 0.00 11396.99 0.00 0.00 0.00 0.00 47.80 480.47 0.00 0.00 0.00 0.00 0.00 -1703.53 0.00 -87.61 -10134.11
PERIMETER_TOP_ZN_1 06-FEB-04:01 0.00 0.00 14349.58 0.00 0.00 0.00 0.00 74.17 745.57 0.00 0.00 0.00 0.00 0.00 -2802.58 0.00 -145.88 -12220.85
PERIMETER_TOP_ZN_4 06-FEB-04:01 0.00 0.00 10394.28 0.00 0.00 0.00 0.00 47.80 480.46 0.00 0.00 0.00 0.00 0.00 -1913.05 0.00 -97.67 -8911.82
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 10-JAN-04:45 0.00 0.00 525.60 0.00 0.00 0.00 0.00 15.83 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2490.04
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 13-MAR-04:01 9507.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -89.20 -9418.06
MIDFLOOR_PLENUM 22-MAY-03:02 67534.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 93.46 0.00 0.00 -0.00 0.00 0.00 -67627.84
TOPFLOOR_PLENUM 06-FEB-06:13 16751.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -46.84 -16705.09
Total Facility 21-DEC-06:01 -854454.01 457281.01 412532.51 -457281.01 0.00 0.00 19414.73 22094.05 616289.16 0.00 0.00 0.00 0.00 0.00 -156948.36 0.00 -3418.70 -55509.38



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 9.1804 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 8.4062 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 85.0577 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 77.3669 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 8.8118 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 8.3530 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.0388 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.0388 0.2382 1.0000 Not calculated 1.2002 0.2382    
AIRLOOP DATACENTER BOT 0.4585 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4585 0.0341 1.0000 Not calculated 0.0156 0.0341    
AIRLOOP DATACENTER MID 4.3616 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.3616 0.0358 1.0000 Not calculated 0.1563 0.0358    
AIRLOOP DATACENTER TOP 0.4450 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4450 0.0351 1.0000 Not calculated 0.0156 0.0351    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 4.5902 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.7290 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 42.5288 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 26.3047 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 4.4059 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.7089 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.0388 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.0388 1.0000 1.0000 Not calculated 1.2002 0.2382    
AIRLOOP DATACENTER BOT 0.4585 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4585 1.0000 1.0000 Not calculated 0.0156 0.0341    
AIRLOOP DATACENTER MID 4.3616 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.3616 1.0000 1.0000 Not calculated 0.1563 0.0358    
AIRLOOP DATACENTER TOP 0.4450 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4450 1.0000 1.0000 Not calculated 0.0156 0.0351    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.002360 149.6021 0.000305 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.002360 1.9486 0.000305 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.002360 19.4861 0.000305 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.002360 1.9486 0.000305 36.20 0.0156 1.0000 0.0156 1.000 0.0156


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.002360 149.60 0.000305 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BOT 0.002360 1.95 0.000305 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.002360 19.49 0.000305 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.002360 1.95 0.000305 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.0388 5.0388 5.0388 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.2759 5.2759 1.8571 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 49.2075 49.2075 18.0592 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.8889 4.8889 1.8529 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8446 0.8446 0.2331 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8838 0.8838 0.1768 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0306 1.0306 0.2329 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1455 1.1455 0.2291 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 7.6859 7.6859 2.2673 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.0378 9.0378 1.8076 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.5934 9.5934 2.2641 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.5330 9.5330 1.9066 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8890 0.8890 0.2320 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9227 0.9227 0.1845 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0750 1.0750 0.2322 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0361 1.0361 0.2072 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4585 0.4585 0.4585 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.3616 4.3616 4.3616 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4450 0.4450 0.4450 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 9.1804 8.4062 9.1804 2.7290 0.0000 1.0000
VAV_MID WITH REHEAT 85.0577 77.3669 85.0577 26.3047 0.0000 1.0000
VAV_TOP WITH REHEAT 8.8118 8.3530 8.8118 2.7089 0.0000 1.0000
CAV_BAS 5.0388 5.0388 5.0388 5.0388 1.2002 1.0000
AIRLOOP DATACENTER BOT 0.4585 0.4585 0.4585 0.4585 0.0156 1.0000
AIRLOOP DATACENTER MID 4.3616 4.3616 4.3616 4.3616 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4450 0.4450 0.4450 0.4450 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.0388 5.0388 5.0388 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6380 2.6380 1.8571 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 24.6038 24.6038 18.0592 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4445 2.4445 1.8529 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4223 0.4223 0.2331 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4419 0.4419 0.1768 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5153 0.5153 0.2329 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5728 0.5728 0.2291 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.8429 3.8429 2.2673 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.5189 4.5189 1.8076 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.7967 4.7967 2.2641 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.7665 4.7665 1.9066 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4445 0.4445 0.2320 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4614 0.4614 0.1845 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5375 0.5375 0.2322 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5181 0.5181 0.2072 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4585 0.4585 0.4585 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.3616 4.3616 4.3616 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4450 0.4450 0.4450 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 4.5902 2.7290 2.7290 2.7290 0.0000 1.0000
VAV_MID WITH REHEAT 42.5288 26.3047 26.3047 26.3047 0.0000 1.0000
VAV_TOP WITH REHEAT 4.4059 2.7089 2.7089 2.7089 0.0000 1.0000
CAV_BAS 5.0388 5.0388 5.0388 5.0388 1.2002 1.0000
AIRLOOP DATACENTER BOT 0.4585 0.4585 0.4585 0.4585 0.0156 1.0000
AIRLOOP DATACENTER MID 4.3616 4.3616 4.3616 4.3616 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4450 0.4450 0.4450 0.4450 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.67
Number of hours cooling loads not met 175.83
Number of hours not met 176.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.56
Heating -- Boiler 0.00 0.00 82.69 423881.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 2459.32 296302.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7190.82 370154.94 0.00 0.00
Interior Lighting -- LightsWired 2023.08 193957.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 325.14 37611.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5334.97 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 54.48 3384.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ComputerHVAC 1424.02 72130.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 915.75 91221.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 978.48 68241.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 770.22 55581.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 61.82 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 595.32 73380.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 14676.40 25543.31
Natural Gas 0.00 678.01
Additional 0.00 7190.82
Total 14676.40 33412.14


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 43.68
Space Heating 0.00
Space Cooling 53.09
Fans (All) 19.77
Service Water Heating 0.00
Receptacle Equipment 316.85
Miscellaneous (All) 551.45
Subtotal 551.45


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 1.79
Service Water Heating 12.85
Miscellaneous (All) 14.64
Subtotal 14.64


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.05
Space Heating 0.25
Space Cooling 28.88
Fans (All) 2.74
Service Water Heating 1.78
Receptacle Equipment 43.93
Miscellaneous 16.37


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2362. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4049. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 1565. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 7415.17 1344.83 0.00 0.00 0.00
CORE_BOTTOM 8742.00 18.00 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8755.33 4.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8694.67 65.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8663.33 96.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7719.17 1040.83 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8745.50 14.50 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8600.33 159.67 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8551.67 208.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8065.67 694.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8714.17 45.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8529.67 230.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8493.33 266.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8061.17 698.83 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 4785.67 3974.33 0.00 0.00 0.00
DATACENTER_MID_ZN_6 4863.00 3897.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 4810.17 3949.83 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 8760.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8573.83 186.17 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 8760.00 0.00 0.00 0.00
Average 7644.51 1115.49 0.00 0.00 0.00
Sum 175823.83 25656.17 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 364911.83 3704.17 0.00 0.00 0.00
CORE_BOTTOM 330776.00 37.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 605.50 1662.50 0.00 0.00 0.00
DATACENTER_MID_ZN_6 603.33 1664.67 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 587.67 1680.33 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 103395.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 364911.83 103395.00 0.00 0.00 0.00
Average 75459.10 4875.81 0.00 0.00 0.00
Sum 1735559.33 112143.67 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 4136.17 4623.83 0.00 0.00 0.00
CORE_BOTTOM 8672.00 88.00 0.00 0.00 0.00
CORE_MID 8758.83 1.17 0.00 0.00 0.00
CORE_TOP 8756.67 3.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8630.17 129.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8542.33 217.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8441.00 319.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7465.33 1294.67 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8005.83 754.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 7713.83 1046.17 0.00 0.00 0.00
PERIMETER_MID_ZN_1 7656.67 1103.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 7357.33 1402.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 7824.83 935.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 7603.33 1156.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 7509.83 1250.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 7390.83 1369.17 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 6127.83 2632.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 6087.17 2672.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 6066.33 2693.67 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 8760.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8754.67 5.33 0.00 0.00 0.00
MIDFLOOR_PLENUM 8714.83 45.17 0.00 0.00 0.00
TOPFLOOR_PLENUM 8427.83 332.17 0.00 0.00 0.00
Min 0.00 1.17 0.00 0.00 0.00
Max 8758.83 8760.00 0.00 0.00 0.00
Average 7332.33 1427.67 0.00 0.00 0.00
Sum 168643.67 32836.33 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 293217.17 75398.83 0.00 0.00 0.00
CORE_BOTTOM 330609.00 204.00 0.00 0.00 0.00
CORE_MID 330806.00 7.00 0.00 0.00 0.00
CORE_TOP 330796.00 17.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 831.83 1436.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 815.33 1452.67 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 800.83 1467.17 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 103395.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 330806.00 103395.00 0.00 0.00 0.00
Average 72361.96 7972.95 0.00 0.00 0.00
Sum 1664325.17 183377.83 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:07:54

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021

For: Environment

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A

For: Environment

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA

For: Environment

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.510972E+11 100714.27 09-JAN-04:12 8.67 6.99 0.567277E+10 7499.41 12-JAN-10:09 18.17 17.41
February 0.446855E+11 100289.71 13-FEB-04:03 6.38 2.53 0.514508E+10 7499.09 09-FEB-10:00 6.38 2.53
March 0.514119E+11 98286.81 20-MAR-03:02 12.55 8.37 0.613867E+10 7499.71 23-MAR-09:20 16.97 14.65
April 0.471341E+11 96806.33 10-APR-03:02 13.30 9.00 0.545470E+10 7499.32 12-APR-09:20 21.23 16.81
May 0.512338E+11 71226.47 30-MAY-03:02 25.60 23.91 0.590827E+10 7498.82 05-MAY-09:20 25.60 23.91
June 0.515616E+11 74281.70 07-JUN-03:02 21.10 18.25 0.588749E+10 7498.82 29-JUN-09:20 29.63 25.44
July 0.532924E+11 71744.94 05-JUL-03:02 25.60 23.97 0.547936E+10 7498.80 14-JUL-09:20 24.27 23.35
August 0.620320E+11 75370.86 28-AUG-03:02 26.27 23.76 0.614566E+10 7498.78 25-AUG-13:20 26.27 23.76
September 0.557254E+11 78567.97 05-SEP-02:13 23.20 23.20 0.546051E+10 7498.80 14-SEP-13:20 28.13 24.89
October 0.589485E+11 88874.08 28-OCT-05:03 10.00 5.56 0.567972E+10 7499.09 17-OCT-13:20 10.00 5.56
November 0.572188E+11 97038.41 24-NOV-04:03 10.03 8.79 0.562317E+10 7499.03 21-NOV-14:00 10.03 8.79
December 0.553546E+11 99135.99 04-DEC-04:03 6.00 5.06 0.548004E+10 7499.55 08-DEC-10:00 24.00 18.77
                     
Annual Sum or Average 0.639696E+12         0.680754E+11        
Minimum of Months 0.446855E+11 71226.47   6.00 2.53 0.514508E+10 7498.78   6.38 2.53
Maximum of Months 0.620320E+11 100714.27   26.27 23.97 0.614566E+10 7499.71   29.63 25.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.451328E+11 83572.81 02-JAN-04:02 17.00 16.27 0.504024E+10 6734.76 05-JAN-14:09 14.17 9.63
February 0.436681E+11 80586.93 21-FEB-04:03 17.30 17.30 0.458411E+10 6734.65 09-FEB-14:00 17.30 17.30
March 0.553513E+11 81033.29 20-MAR-03:02 12.55 8.37 0.548105E+10 6734.93 23-MAR-09:09 16.78 14.63
April 0.610045E+11 79016.52 10-APR-03:02 13.30 9.00 0.486751E+10 6734.83 10-APR-13:00 20.50 10.92
May 0.578848E+11 76261.15 09-MAY-03:02 23.90 21.88 0.526910E+10 6734.43 22-MAY-09:09 26.93 23.35
June 0.627979E+11 74077.96 07-JUN-03:02 21.10 18.25 0.525249E+10 6734.43 27-JUN-09:09 28.58 25.38
July 0.677113E+11 67027.64 12-JUL-05:02 23.90 23.16 0.488146E+10 6734.43 13-JUL-09:30 24.45 23.19
August 0.740768E+11 66853.99 01-AUG-05:02 23.90 22.91 0.548604E+10 6734.43 07-AUG-09:09 27.50 25.10
September 0.565939E+11 78029.09 20-SEP-03:02 22.38 21.02 0.486633E+10 6734.43 26-SEP-09:09 22.80 22.02
October 0.610594E+11 80965.90 30-OCT-03:02 17.00 14.54 0.506539E+10 6734.76 17-OCT-13:09 17.00 14.54
November 0.559588E+11 84093.15 13-NOV-04:02 9.98 8.04 0.501983E+10 6734.72 13-NOV-10:09 16.47 13.02
December 0.559627E+11 83730.07 26-DEC-04:02 6.82 3.27 0.488674E+10 6734.74 26-DEC-14:00 13.30 6.27
                     
Annual Sum or Average 0.697202E+12         0.607003E+11        
Minimum of Months 0.436681E+11 66853.99   6.82 3.27 0.458411E+10 6734.43   13.30 6.27
Maximum of Months 0.740768E+11 84093.15   23.90 23.16 0.548604E+10 6734.93   28.58 25.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.342035E+11 70706.70 20-JAN-06:04 17.00 17.00 0.480661E+10 6734.47 03-JAN-14:09 17.00 17.00
February 0.317597E+11 68997.04 24-FEB-06:03 14.50 14.50 0.442502E+10 6734.45 23-FEB-10:09 14.50 14.50
March 0.388599E+11 71616.10 28-MAR-05:04 19.05 18.47 0.534864E+10 6734.58 24-MAR-09:00 19.05 18.47
April 0.401875E+11 73372.89 14-APR-05:04 18.80 18.80 0.482737E+10 6734.74 10-APR-13:00 18.80 18.80
May 0.484283E+11 69064.57 23-MAY-04:03 24.32 23.29 0.524460E+10 6734.45 31-MAY-13:09 23.27 21.49
June 0.488529E+11 70862.51 07-JUN-04:03 21.10 18.53 0.522803E+10 6734.46 01-JUN-13:09 21.10 18.53
July 0.488963E+11 69581.97 12-JUL-04:03 23.40 22.98 0.485177E+10 6734.44 14-JUL-09:09 24.08 23.26
August 0.505900E+11 70282.77 17-AUG-04:03 21.77 21.49 0.545764E+10 6734.45 25-AUG-13:09 27.80 24.45
September 0.460511E+11 70017.20 08-SEP-04:03 24.17 23.46 0.483300E+10 6734.44 27-SEP-13:09 23.30 22.57
October 0.458805E+11 71165.85 17-OCT-04:03 17.42 12.92 0.503069E+10 6734.78 17-OCT-13:09 22.17 15.50
November 0.386151E+11 73022.89 01-NOV-05:04 22.62 22.36 0.495274E+10 6734.74 13-NOV-10:09 16.47 13.02
December 0.356782E+11 72726.97 12-DEC-06:04 20.17 20.17 0.472857E+10 6734.60 18-DEC-14:09 16.17 10.34
                     
Annual Sum or Average 0.508003E+12         0.597347E+11        
Minimum of Months 0.317597E+11 68997.04   14.50 12.92 0.442502E+10 6734.44   14.50 10.34
Maximum of Months 0.505900E+11 73372.89   24.32 23.46 0.545764E+10 6734.78   27.80 24.45



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.299399E+11 66898.55 20-JAN-06:02 17.00 17.00 0.437629E+10 6734.36 18-JAN-14:09 17.00 17.00
February 0.293755E+11 66210.95 03-FEB-06:03 18.90 18.50 0.414367E+10 6734.39 28-FEB-10:20 21.07 19.22
March 0.366940E+11 68196.05 28-MAR-05:02 19.05 18.47 0.507207E+10 6734.46 20-MAR-13:00 19.05 18.47
April 0.408247E+11 70472.24 06-APR-05:04 17.78 16.89 0.476651E+10 6734.71 10-APR-13:00 20.50 10.92
May 0.538600E+11 69727.37 23-MAY-04:03 24.32 23.29 0.525148E+10 6734.42 23-MAY-09:09 26.47 24.28
June 0.552468E+11 69990.53 30-JUN-03:02 23.48 22.93 0.523790E+10 6734.43 01-JUN-13:09 23.48 22.93
July 0.553398E+11 70094.66 12-JUL-04:03 23.40 22.98 0.486217E+10 6734.44 14-JUL-09:09 24.08 23.26
August 0.565705E+11 69113.62 01-AUG-04:03 23.90 22.80 0.546468E+10 6734.42 17-AUG-09:09 26.28 23.28
September 0.495937E+11 73289.84 08-SEP-05:04 24.58 23.92 0.483640E+10 6734.43 26-SEP-09:09 22.80 22.02
October 0.478946E+11 71681.92 17-OCT-05:04 16.83 11.73 0.500230E+10 6734.73 17-OCT-13:09 22.17 15.50
November 0.360971E+11 72393.33 04-NOV-05:04 20.58 20.07 0.473274E+10 6734.48 21-NOV-14:00 22.20 15.14
December 0.317895E+11 66272.70 12-DEC-06:02 20.17 20.17 0.433867E+10 6734.44 01-DEC-14:00 20.17 20.17
                     
Annual Sum or Average 0.523226E+12         0.580849E+11        
Minimum of Months 0.293755E+11 66210.95   16.83 11.73 0.414367E+10 6734.36   17.00 10.92
Maximum of Months 0.565705E+11 73289.84   24.58 23.92 0.546468E+10 6734.73   26.47 24.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.472573E+10 9695.97 31-JAN-06:02 18.17 18.17 0.588632E+09 845.59 02-JAN-14:39 18.17 18.17
February 0.481991E+10 6310.69 22-FEB-14:30 25.55 20.41 0.553900E+09 845.61 09-FEB-14:00 25.55 20.41
March 0.636125E+10 8134.79 27-MAR-05:02 19.82 18.59 0.671571E+09 845.61 24-MAR-09:20 19.82 18.59
April 0.826950E+10 10389.85 24-APR-05:02 20.08 20.03 0.609324E+09 845.65 18-APR-13:00 20.08 20.03
May 0.984317E+10 11405.88 31-MAY-03:02 23.22 21.33 0.664426E+09 845.60 31-MAY-13:09 23.27 21.49
June 0.111942E+11 11614.97 25-JUN-15:52 32.80 24.12 0.662264E+09 845.60 01-JUN-13:09 32.80 24.12
July 0.117800E+11 12672.33 03-JUL-05:03 26.10 23.49 0.615689E+09 845.60 12-JUL-13:39 24.47 22.46
August 0.124249E+11 12485.70 14-AUG-05:03 26.10 23.77 0.690630E+09 845.60 25-AUG-13:09 27.80 24.45
September 0.887390E+10 10850.99 05-SEP-05:03 22.80 22.80 0.613088E+09 845.60 27-SEP-13:09 23.30 22.57
October 0.895911E+10 10849.70 07-OCT-05:02 26.17 26.04 0.635753E+09 845.64 17-OCT-13:09 22.17 15.50
November 0.654338E+10 9719.95 02-NOV-05:02 23.38 22.55 0.623005E+09 845.63 13-NOV-10:09 16.47 13.02
December 0.596719E+10 10690.56 11-DEC-06:02 20.83 20.26 0.591454E+09 845.62 26-DEC-14:00 13.30 6.27
                     
Annual Sum or Average 0.997622E+11         0.751973E+10        
Minimum of Months 0.472573E+10 6310.69   18.17 18.17 0.553900E+09 845.59   13.30 6.27
Maximum of Months 0.124249E+11 12672.33   32.80 26.04 0.690630E+09 845.65   32.80 24.45



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.377890E+10 9858.53 01-JAN-10:13 20.67 16.62 0.393339E+09 544.95 11-JAN-10:09 14.67 12.06
February 0.393365E+10 7069.83 27-FEB-10:10 21.37 19.24 0.362865E+09 544.96 09-FEB-10:00 21.37 19.24
March 0.535747E+10 10041.24 26-MAR-09:02 23.67 19.70 0.433181E+09 544.97 23-MAR-09:09 23.67 19.70
April 0.670698E+10 12772.77 23-APR-11:02 26.70 20.26 0.391841E+09 544.97 18-APR-13:00 26.70 20.26
May 0.806037E+10 16209.80 29-MAY-08:62 26.88 22.53 0.428369E+09 544.94 31-MAY-13:09 23.27 21.49
June 0.865813E+10 15406.75 11-JUN-08:53 27.80 20.73 0.426643E+09 544.94 01-JUN-13:09 27.80 20.73
July 0.885479E+10 15552.00 23-JUL-09:53 31.10 26.51 0.396576E+09 544.93 12-JUL-13:39 31.10 26.51
August 0.902232E+10 13743.76 06-AUG-10:02 30.17 26.87 0.444486E+09 544.94 25-AUG-13:09 27.80 24.45
September 0.687953E+10 15616.42 24-SEP-09:23 28.85 25.01 0.395094E+09 544.93 27-SEP-13:09 23.30 22.57
October 0.703860E+10 15460.95 09-OCT-09:02 27.42 22.34 0.409507E+09 544.96 17-OCT-13:09 22.17 15.50
November 0.510722E+10 8703.35 11-NOV-09:03 24.40 21.68 0.402555E+09 544.95 09-NOV-10:09 24.40 21.68
December 0.437804E+10 5271.38 16-DEC-09:40 23.33 20.99 0.378900E+09 544.95 04-DEC-10:00 23.33 20.99
                     
Annual Sum or Average 0.777760E+11         0.486336E+10        
Minimum of Months 0.377890E+10 5271.38   20.67 16.62 0.362865E+09 544.93   14.67 12.06
Maximum of Months 0.902232E+10 16209.80   31.10 26.87 0.444486E+09 544.97   31.10 26.51



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.813918E+10 20113.83 01-JAN-13:32 25.67 18.12 0.624505E+09 860.90 19-JAN-14:20 25.00 21.54
February 0.799666E+10 18596.69 26-FEB-13:23 26.35 19.10 0.569903E+09 861.22 27-FEB-14:20 25.70 20.08
March 0.846299E+10 17722.26 26-MAR-14:23 26.90 20.14 0.675420E+09 845.65 23-MAR-09:30 26.90 20.14
April 0.952936E+10 12887.73 28-APR-05:02 22.80 21.69 0.609783E+09 845.69 18-APR-13:00 22.80 21.69
May 0.100214E+11 13168.16 22-MAY-05:03 26.10 22.55 0.664461E+09 845.62 31-MAY-13:09 23.27 21.49
June 0.108397E+11 13287.56 29-JUN-05:02 25.18 24.55 0.662083E+09 845.62 01-JUN-13:09 25.18 24.55
July 0.116543E+11 13792.04 24-JUL-05:03 27.02 24.85 0.615629E+09 845.61 12-JUL-13:39 27.02 24.85
August 0.133815E+11 13999.37 06-AUG-13:23 30.00 24.60 0.691036E+09 845.62 25-AUG-13:09 27.80 24.45
September 0.106211E+11 18412.61 10-SEP-13:02 35.13 27.70 0.614239E+09 845.62 20-SEP-13:39 26.60 22.72
October 0.130306E+11 19006.38 15-OCT-13:32 29.67 22.65 0.638861E+09 859.07 13-OCT-13:39 29.67 22.65
November 0.110563E+11 18597.68 11-NOV-11:02 26.18 21.89 0.631360E+09 892.47 06-NOV-14:09 26.18 21.89
December 0.102112E+11 19287.60 17-DEC-13:12 19.00 12.71 0.605976E+09 869.92 15-DEC-14:39 19.00 12.71
                     
Annual Sum or Average 0.124944E+12         0.760325E+10        
Minimum of Months 0.799666E+10 12887.73   19.00 12.71 0.569903E+09 845.61   19.00 12.71
Maximum of Months 0.133815E+11 20113.83   35.13 27.70 0.691036E+09 892.47   29.67 24.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.541455E+10 19622.35 01-JAN-16:12 24.67 18.84 0.392994E+09 544.96 05-JAN-14:00 15.00 10.71
February 0.615018E+10 20630.06 26-FEB-16:42 24.58 19.86 0.368312E+09 544.96 09-FEB-14:00 24.58 19.86
March 0.857760E+10 18351.83 26-MAR-14:23 26.90 20.14 0.444224E+09 544.97 23-MAR-09:09 26.90 20.14
April 0.116010E+11 20561.43 23-APR-18:22 24.40 20.99 0.396672E+09 545.00 18-APR-13:00 24.40 20.99
May 0.977846E+10 21173.29 28-MAY-15:52 33.90 24.40 0.429042E+09 544.94 31-MAY-13:09 23.27 21.49
June 0.117381E+11 21304.75 25-JUN-15:52 32.80 24.12 0.427915E+09 544.94 01-JUN-13:09 32.80 24.12
July 0.129228E+11 20414.04 02-JUL-15:42 28.98 25.06 0.398183E+09 544.93 12-JUL-13:39 24.47 22.46
August 0.148996E+11 20487.62 20-AUG-17:12 30.33 24.28 0.446578E+09 544.94 25-AUG-13:09 27.80 24.45
September 0.910596E+10 20567.05 24-SEP-16:02 30.32 25.93 0.396187E+09 544.93 07-SEP-13:39 30.32 25.93
October 0.103333E+11 20600.01 09-OCT-16:22 28.00 21.50 0.412099E+09 544.96 17-OCT-13:09 22.17 15.50
November 0.857115E+10 19237.04 05-NOV-14:43 27.20 20.17 0.407682E+09 544.97 21-NOV-14:00 22.20 15.14
December 0.854101E+10 20531.51 10-DEC-16:42 25.33 19.74 0.396448E+09 544.97 26-DEC-14:00 13.30 6.27
                     
Annual Sum or Average 0.117634E+12         0.491634E+10        
Minimum of Months 0.541455E+10 18351.83   24.40 18.84 0.368312E+09 544.93   13.30 6.27
Maximum of Months 0.148996E+11 21304.75   33.90 25.93 0.446578E+09 545.00   32.80 25.93



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.310626E+10 4101.53 02-JAN-13:30 26.00 18.64 0.528239E+09 845.59 02-JAN-14:39 26.67 18.58
February 0.332163E+10 4685.17 28-FEB-15:00 25.00 20.38 0.506152E+09 845.59 28-FEB-14:09 25.00 20.38
March 0.434099E+10 7573.57 28-MAR-05:02 19.05 18.47 0.619843E+09 845.59 28-MAR-13:39 27.20 21.71
April 0.534566E+10 9202.47 14-APR-05:02 18.80 18.80 0.596342E+09 845.60 12-APR-13:20 18.80 18.80
May 0.853108E+10 11756.53 26-MAY-03:02 25.50 23.88 0.663872E+09 845.60 31-MAY-13:09 23.27 21.49
June 0.925239E+10 11867.13 28-JUN-03:02 27.20 25.10 0.662210E+09 845.60 01-JUN-13:09 27.20 25.10
July 0.914000E+10 11875.67 10-JUL-03:02 25.60 23.91 0.615754E+09 845.59 12-JUL-13:39 24.47 22.46
August 0.905717E+10 11933.78 14-AUG-03:02 26.52 24.51 0.690528E+09 845.60 25-AUG-13:09 27.80 24.45
September 0.734527E+10 10365.35 11-SEP-05:02 25.42 23.91 0.611433E+09 845.59 07-SEP-13:39 25.42 23.91
October 0.680515E+10 11093.14 06-OCT-03:02 26.67 25.46 0.629473E+09 845.63 17-OCT-13:09 22.17 15.50
November 0.448764E+10 9281.79 01-NOV-05:02 22.62 22.36 0.586863E+09 845.60 21-NOV-14:00 22.20 15.14
December 0.359590E+10 8490.26 12-DEC-06:02 20.17 20.17 0.527510E+09 845.59 11-DEC-14:00 20.17 20.17
                     
Annual Sum or Average 0.743291E+11         0.723822E+10        
Minimum of Months 0.310626E+10 4101.53   18.80 18.47 0.506152E+09 845.59   18.80 15.14
Maximum of Months 0.925239E+10 11933.78   27.20 25.46 0.690528E+09 845.63   27.80 25.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.290915E+10 5689.03 19-JAN-10:00 23.00 20.89 0.264032E+09 521.19 02-JAN-15:20 23.00 20.89
February 0.307931E+10 6071.84 27-FEB-10:00 21.10 19.21 0.251230E+09 521.21 09-FEB-11:09 21.10 19.21
March 0.415217E+10 8225.52 26-MAR-09:53 25.50 20.23 0.305969E+09 521.23 23-MAR-08:50 25.50 20.23
April 0.532253E+10 15659.31 23-APR-11:02 26.70 20.26 0.286539E+09 521.24 18-APR-14:20 26.70 20.26
May 0.758591E+10 16771.03 29-MAY-09:32 28.53 23.16 0.315215E+09 521.20 03-MAY-12:09 28.53 23.16
June 0.792456E+10 15931.27 11-JUN-08:53 27.80 20.73 0.313898E+09 521.20 12-JUN-12:09 31.70 20.35
July 0.782266E+10 15960.63 16-JUL-08:32 28.53 23.97 0.292962E+09 521.20 05-JUL-12:09 28.53 23.97
August 0.764917E+10 15688.00 27-AUG-10:23 30.00 24.51 0.327084E+09 521.20 30-AUG-12:09 31.18 24.70
September 0.622301E+10 16589.43 03-SEP-09:42 29.98 24.61 0.290219E+09 521.20 07-SEP-14:20 24.20 22.95
October 0.604017E+10 15872.94 09-OCT-09:23 28.05 22.46 0.299526E+09 521.23 17-OCT-12:20 21.33 14.79
November 0.395096E+10 9410.98 01-NOV-05:02 22.62 22.36 0.288341E+09 521.20 21-NOV-15:39 21.47 15.14
December 0.302905E+10 5466.50 12-DEC-06:02 20.17 20.17 0.258097E+09 521.20 01-DEC-11:20 20.17 20.17
                     
Annual Sum or Average 0.656887E+11         0.349311E+10        
Minimum of Months 0.290915E+10 5466.50   20.17 19.21 0.251230E+09 521.19   20.17 14.79
Maximum of Months 0.792456E+10 16771.03   30.00 24.61 0.327084E+09 521.24   31.70 24.70



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.719380E+10 17503.37 16-JAN-14:32 26.67 18.75 0.615196E+09 890.16 19-JAN-14:50 25.00 21.54
February 0.685216E+10 17547.73 26-FEB-13:32 26.43 19.30 0.561151E+09 882.17 27-FEB-14:39 25.90 20.26
March 0.655985E+10 15073.98 05-MAR-12:53 27.70 18.32 0.658908E+09 845.63 03-MAR-14:00 27.70 18.32
April 0.678073E+10 11532.35 29-APR-05:03 23.20 21.68 0.604096E+09 845.67 10-APR-13:00 23.20 21.68
May 0.876873E+10 13091.64 22-MAY-03:02 26.10 22.50 0.663868E+09 845.61 31-MAY-13:09 23.27 21.49
June 0.890649E+10 12925.19 14-JUN-05:02 25.00 22.88 0.661867E+09 845.62 01-JUN-13:09 25.00 22.88
July 0.906282E+10 14365.02 20-JUL-03:02 26.70 24.39 0.615595E+09 845.61 12-JUL-13:39 26.70 24.39
August 0.101501E+11 14830.63 14-AUG-03:02 26.52 24.51 0.691111E+09 845.62 25-AUG-13:09 27.80 24.45
September 0.936054E+10 17093.21 03-SEP-14:22 32.45 24.62 0.613563E+09 845.62 20-SEP-13:39 26.60 22.72
October 0.113525E+11 18135.31 08-OCT-13:42 32.83 26.23 0.638847E+09 882.60 13-OCT-13:50 32.87 23.24
November 0.938609E+10 17435.09 05-NOV-14:43 27.20 20.17 0.629076E+09 919.62 06-NOV-14:09 28.30 21.03
December 0.811872E+10 18762.01 10-DEC-14:32 27.67 20.09 0.593427E+09 885.72 15-DEC-14:50 29.00 21.65
                     
Annual Sum or Average 0.102493E+12         0.754671E+10        
Minimum of Months 0.655985E+10 11532.35   23.20 18.32 0.561151E+09 845.61   23.20 18.32
Maximum of Months 0.113525E+11 18762.01   32.83 26.23 0.691111E+09 919.62   32.87 24.45



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.334894E+10 7660.06 20-JAN-06:02 17.00 17.00 0.359582E+09 544.93 02-JAN-14:39 17.00 17.00
February 0.358503E+10 8803.27 27-FEB-16:30 24.95 20.41 0.340483E+09 544.94 09-FEB-14:00 24.95 20.41
March 0.445647E+10 12145.99 06-MAR-06:02 18.80 18.03 0.411413E+09 544.93 03-MAR-14:00 18.80 18.03
April 0.580325E+10 16471.49 16-APR-16:31 19.97 13.44 0.389897E+09 544.96 10-APR-13:00 19.97 13.44
May 0.747515E+10 16955.44 28-MAY-18:02 29.32 24.32 0.428396E+09 544.93 31-MAY-13:09 23.27 21.49
June 0.805193E+10 16685.65 11-JUN-16:52 33.30 21.96 0.427391E+09 544.94 01-JUN-13:09 33.30 21.96
July 0.782567E+10 17308.33 16-JUL-16:32 30.17 24.94 0.397511E+09 544.93 11-JUL-13:09 30.17 24.94
August 0.826345E+10 16274.02 20-AUG-17:12 30.33 24.28 0.445893E+09 544.93 25-AUG-13:09 27.80 24.45
September 0.668726E+10 17680.34 03-SEP-15:42 32.28 24.61 0.394896E+09 544.93 07-SEP-13:39 26.07 23.43
October 0.663297E+10 17003.90 08-OCT-16:22 30.00 24.93 0.408389E+09 544.96 17-OCT-13:09 22.17 15.50
November 0.450085E+10 11607.15 01-NOV-05:02 22.62 22.36 0.388404E+09 544.95 21-NOV-14:00 22.20 15.14
December 0.381009E+10 11459.06 13-DEC-06:02 20.00 20.00 0.356546E+09 544.94 07-DEC-14:50 20.00 20.00
                     
Annual Sum or Average 0.704411E+11         0.474880E+10        
Minimum of Months 0.334894E+10 7660.06   17.00 13.44 0.340483E+09 544.93   17.00 13.44
Maximum of Months 0.826345E+10 17680.34   33.30 24.94 0.445893E+09 544.96   33.30 24.94



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.228940E+10 4399.37 31-JAN-16:00 25.00 21.54 0.510238E+09 845.59 02-JAN-14:09 25.00 21.54
February 0.285318E+10 5061.33 28-FEB-15:00 25.00 20.38 0.488621E+09 845.58 28-FEB-14:09 25.00 20.38
March 0.399956E+10 6376.07 30-MAR-13:30 28.55 22.55 0.596624E+09 845.59 27-MAR-13:09 28.55 22.55
April 0.550644E+10 10663.02 27-APR-05:02 20.92 20.25 0.585587E+09 845.60 12-APR-13:30 20.92 20.25
May 0.941380E+10 12722.48 22-MAY-03:02 26.10 22.50 0.664080E+09 845.60 31-MAY-13:09 23.27 21.49
June 0.103521E+11 13452.12 17-JUN-03:02 25.60 23.91 0.662494E+09 845.60 01-JUN-13:09 25.60 23.91
July 0.102424E+11 15086.01 23-JUL-14:22 32.50 25.44 0.616142E+09 845.59 11-JUL-13:09 32.50 25.44
August 0.100495E+11 13663.98 28-AUG-03:02 26.27 23.76 0.690695E+09 845.60 25-AUG-13:09 26.27 23.76
September 0.790544E+10 15398.21 10-SEP-14:52 35.60 27.28 0.611169E+09 845.60 07-SEP-13:00 35.60 27.28
October 0.714091E+10 11896.43 07-OCT-05:02 26.17 26.04 0.624128E+09 845.63 17-OCT-13:09 22.17 15.50
November 0.416228E+10 11002.68 02-NOV-05:02 23.38 22.55 0.561760E+09 845.59 08-NOV-14:00 22.70 16.46
December 0.287829E+10 5692.43 15-DEC-15:00 29.00 21.56 0.504551E+09 845.59 11-DEC-14:39 29.00 21.56
                     
Annual Sum or Average 0.767932E+11         0.711609E+10        
Minimum of Months 0.228940E+10 4399.37   20.92 20.25 0.488621E+09 845.58   20.92 15.50
Maximum of Months 0.103521E+11 15398.21   35.60 27.28 0.690695E+09 845.63   35.60 27.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.248472E+10 5351.09 19-JAN-10:30 23.85 21.17 0.342820E+09 544.93 02-JAN-14:39 23.85 21.17
February 0.281926E+10 5816.94 27-FEB-10:30 21.90 19.28 0.332449E+09 544.93 08-FEB-10:00 21.90 19.28
March 0.394630E+10 8838.24 27-MAR-05:02 19.82 18.59 0.408941E+09 544.95 23-MAR-09:50 19.82 18.59
April 0.552103E+10 16072.78 23-APR-11:02 26.70 20.26 0.388242E+09 544.97 10-APR-13:00 26.70 20.26
May 0.841484E+10 17053.15 29-MAY-10:42 29.82 23.25 0.428455E+09 544.93 31-MAY-13:09 23.27 21.49
June 0.889359E+10 16293.50 11-JUN-08:53 27.80 20.73 0.427214E+09 544.94 01-JUN-13:09 27.80 20.73
July 0.879319E+10 16360.45 16-JUL-08:32 28.53 23.97 0.397411E+09 544.93 12-JUL-13:09 28.53 23.97
August 0.854008E+10 16198.98 27-AUG-10:23 30.00 24.51 0.445296E+09 544.94 25-AUG-13:09 30.00 24.51
September 0.679547E+10 17013.45 03-SEP-09:42 29.98 24.61 0.394403E+09 544.94 07-SEP-13:00 24.40 22.88
October 0.641667E+10 16224.40 09-OCT-09:23 28.05 22.46 0.405556E+09 544.96 17-OCT-13:09 22.17 15.50
November 0.375448E+10 8041.49 01-NOV-05:02 22.62 22.36 0.382715E+09 544.95 21-NOV-14:00 22.20 15.14
December 0.259267E+10 4437.97 16-DEC-10:10 24.33 21.30 0.337572E+09 544.94 01-DEC-10:00 24.33 21.30
                     
Annual Sum or Average 0.689723E+11         0.469108E+10        
Minimum of Months 0.248472E+10 4437.97   19.82 18.59 0.332449E+09 544.93   19.82 15.14
Maximum of Months 0.889359E+10 17053.15   30.00 24.61 0.445296E+09 544.97   30.00 24.51



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.606290E+10 21147.29 01-JAN-14:12 25.67 18.12 0.596749E+09 868.19 19-JAN-14:50 25.00 21.54
February 0.623951E+10 19418.74 26-FEB-14:43 26.18 20.05 0.546739E+09 861.56 27-FEB-14:39 25.90 20.26
March 0.615332E+10 13941.69 27-MAR-05:02 19.82 18.59 0.637999E+09 845.63 03-MAR-14:00 19.82 18.59
April 0.698057E+10 12994.91 27-APR-05:02 20.92 20.25 0.595809E+09 845.66 10-APR-13:00 20.92 20.25
May 0.967522E+10 15235.59 22-MAY-03:02 26.10 22.50 0.664001E+09 845.61 31-MAY-13:09 23.27 21.49
June 0.999379E+10 14622.82 28-JUN-03:02 27.20 25.10 0.662080E+09 845.62 01-JUN-13:09 27.20 25.10
July 0.101597E+11 18069.91 23-JUL-14:22 32.50 25.44 0.615917E+09 845.61 11-JUL-13:09 32.50 25.44
August 0.112163E+11 18282.07 27-AUG-14:23 33.00 23.46 0.691290E+09 845.62 25-AUG-13:09 33.00 23.46
September 0.100975E+11 20007.72 10-SEP-14:52 35.60 27.28 0.613332E+09 845.62 07-SEP-13:00 35.60 27.28
October 0.118522E+11 20048.82 08-OCT-12:12 31.33 25.87 0.635790E+09 869.93 13-OCT-13:00 33.00 23.24
November 0.878670E+10 20748.64 11-NOV-14:12 26.27 22.90 0.618979E+09 896.71 06-NOV-14:20 26.27 22.90
December 0.715582E+10 21032.54 10-DEC-14:22 27.50 20.13 0.574300E+09 865.09 15-DEC-14:50 29.00 21.65
                     
Annual Sum or Average 0.104373E+12         0.745299E+10        
Minimum of Months 0.606290E+10 12994.91   19.82 18.12 0.546739E+09 845.61   19.82 18.59
Maximum of Months 0.118522E+11 21147.29   35.60 27.28 0.691290E+09 896.71   35.60 27.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.292575E+10 10097.47 01-JAN-16:12 24.67 18.84 0.345233E+09 544.93 02-JAN-14:39 26.67 18.58
February 0.339202E+10 17831.90 26-FEB-17:22 23.85 19.57 0.327954E+09 544.93 28-FEB-14:50 25.00 20.38
March 0.433041E+10 13117.07 27-MAR-05:02 19.82 18.59 0.395391E+09 544.93 27-MAR-13:09 26.78 20.95
April 0.605566E+10 18107.17 23-APR-18:22 24.40 20.99 0.382656E+09 544.96 10-APR-13:00 24.40 20.99
May 0.821220E+10 18614.29 28-MAY-18:02 29.32 24.32 0.428026E+09 544.93 31-MAY-13:09 23.27 21.49
June 0.893042E+10 18260.81 11-JUN-16:52 33.30 21.96 0.427142E+09 544.93 01-JUN-13:09 33.30 21.96
July 0.871008E+10 18918.36 16-JUL-16:32 30.17 24.94 0.397306E+09 544.93 11-JUL-13:09 30.17 24.94
August 0.906131E+10 17637.21 20-AUG-17:12 30.33 24.28 0.445735E+09 544.93 25-AUG-13:09 27.80 24.45
September 0.722704E+10 19456.13 03-SEP-15:42 32.28 24.61 0.393933E+09 544.94 07-SEP-13:00 24.40 22.88
October 0.700254E+10 17846.73 08-OCT-15:32 31.00 25.40 0.404729E+09 544.96 17-OCT-13:09 22.17 15.50
November 0.439969E+10 14175.15 11-NOV-15:32 26.27 22.90 0.373946E+09 544.95 21-NOV-14:00 22.20 15.14
December 0.342800E+10 10072.51 16-DEC-06:03 20.83 19.18 0.340185E+09 544.94 01-DEC-14:00 20.83 19.18
                     
Annual Sum or Average 0.736751E+11         0.466224E+10        
Minimum of Months 0.292575E+10 10072.51   19.82 18.59 0.327954E+09 544.93   20.83 15.14
Maximum of Months 0.906131E+10 19456.13   33.30 25.40 0.445735E+09 544.96   33.30 24.94



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.344402E+10 9123.69 02-JAN-06:15 16.00 15.39 0.00 0.00 01-JAN-00:10 16.00 15.39
February 0.363851E+10 5597.63 27-FEB-15:40 25.70 20.50 0.00 0.00 01-FEB-00:10 25.70 20.50
March 0.469726E+10 5665.60 20-MAR-05:03 12.10 7.78 0.00 0.00 01-MAR-00:10 12.10 7.78
April 0.603519E+10 5663.22 28-APR-16:00 32.20 25.55 0.00 0.00 01-APR-00:10 32.20 25.55
May 0.747339E+10 6781.63 06-MAY-05:03 24.40 21.68 0.00 0.00 01-MAY-00:10 24.40 21.68
June 0.811065E+10 6222.78 12-JUN-16:00 33.30 21.04 0.00 0.00 01-JUN-00:10 33.30 21.04
July 0.864351E+10 7782.23 18-JUL-05:03 24.32 22.84 0.00 0.00 01-JUL-00:10 24.32 22.84
August 0.928530E+10 8805.89 21-AUG-05:03 26.00 23.88 0.00 0.00 01-AUG-00:10 26.00 23.88
September 0.715802E+10 9008.33 25-SEP-05:03 23.38 22.59 0.00 0.00 01-SEP-00:10 23.38 22.59
October 0.753575E+10 7868.42 10-OCT-05:15 21.97 20.04 0.00 0.00 01-OCT-00:10 21.97 20.04
November 0.556380E+10 7269.09 13-NOV-06:13 9.60 8.03 0.00 0.00 01-NOV-00:10 9.60 8.03
December 0.460390E+10 6873.35 26-DEC-06:13 5.90 2.19 0.00 0.00 01-DEC-00:10 5.90 2.19
                     
Annual Sum or Average 0.761893E+11         0.00        
Minimum of Months 0.344402E+10 5597.63   5.90 2.19 0.00 0.00   5.90 2.19
Maximum of Months 0.928530E+10 9123.69   33.30 25.55 0.00 0.00   33.30 25.55



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.196162E+10 4659.35 03-JAN-06:10 2.83 0.47 0.00 0.00 01-JAN-00:10 2.83 0.47
February 0.210403E+10 4360.03 06-FEB-06:02 2.88 0.92 0.00 0.00 01-FEB-00:10 2.88 0.92
March 0.284072E+10 4209.89 28-MAR-05:10 19.05 18.47 0.00 0.00 01-MAR-00:10 19.05 18.47
April 0.394358E+10 4540.78 28-APR-16:00 32.20 25.55 0.00 0.00 01-APR-00:10 32.20 25.55
May 0.623108E+10 6761.25 06-MAY-05:03 24.40 21.68 0.00 0.00 01-MAY-00:10 24.40 21.68
June 0.649377E+10 7613.32 23-JUN-05:02 25.60 23.86 0.00 0.00 01-JUN-00:10 25.60 23.86
July 0.660786E+10 6675.34 25-JUL-05:02 24.50 23.30 0.00 0.00 01-JUL-00:10 24.50 23.30
August 0.674030E+10 6607.73 18-AUG-05:02 23.90 23.26 0.00 0.00 01-AUG-00:10 23.90 23.26
September 0.569740E+10 5691.80 13-SEP-05:03 23.22 21.59 0.00 0.00 01-SEP-00:10 23.22 21.59
October 0.565578E+10 7132.44 13-OCT-05:02 23.00 21.02 0.00 0.00 01-OCT-00:10 23.00 21.02
November 0.338485E+10 4410.80 09-NOV-06:10 10.42 5.53 0.00 0.00 01-NOV-00:10 10.42 5.53
December 0.263455E+10 4959.70 21-DEC-06:01 0.83 0.01 0.00 0.00 01-DEC-00:10 0.83 0.01
                     
Annual Sum or Average 0.542955E+11         0.00        
Minimum of Months 0.196162E+10 4209.89   0.83 0.01 0.00 0.00   0.83 0.01
Maximum of Months 0.674030E+10 7613.32   32.20 25.55 0.00 0.00   32.20 25.55



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.203303E+10 8359.51 19-JAN-15:00 25.00 21.54 0.00 0.00 01-JAN-00:10 25.00 21.54
February 0.290260E+10 10007.26 27-FEB-15:20 25.90 20.46 0.00 0.00 01-FEB-00:10 25.90 20.46
March 0.405006E+10 10189.35 06-MAR-14:50 26.18 21.15 0.00 0.00 01-MAR-00:10 26.18 21.15
April 0.690720E+10 15124.74 28-APR-15:00 33.30 23.06 0.00 0.00 01-APR-00:10 33.30 23.06
May 0.114829E+11 16201.75 10-MAY-14:50 32.80 23.14 0.00 0.00 01-MAY-00:10 32.80 23.14
June 0.127495E+11 17189.81 28-JUN-14:30 33.60 26.19 0.00 0.00 01-JUN-00:10 33.60 26.19
July 0.123417E+11 17371.23 07-JUL-14:50 34.82 23.96 0.00 0.00 01-JUL-00:10 34.82 23.96
August 0.123022E+11 16420.89 03-AUG-15:00 35.00 24.85 0.00 0.00 01-AUG-00:10 35.00 24.85
September 0.941256E+10 15263.81 01-SEP-14:00 32.20 22.62 0.00 0.00 01-SEP-00:10 32.20 22.62
October 0.892597E+10 15121.61 05-OCT-15:20 33.33 23.87 0.00 0.00 01-OCT-00:10 33.33 23.87
November 0.416102E+10 11847.76 02-NOV-14:00 29.40 24.47 0.00 0.00 01-NOV-00:10 29.40 24.47
December 0.265501E+10 9922.92 15-DEC-15:00 29.00 21.56 0.00 0.00 01-DEC-00:10 29.00 21.56
                     
Annual Sum or Average 0.899237E+11         0.00        
Minimum of Months 0.203303E+10 8359.51   25.00 20.46 0.00 0.00   25.00 20.46
Maximum of Months 0.127495E+11 17371.23   35.00 26.19 0.00 0.00   35.00 26.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.379658E+10 2009.47 01-JAN-17:03 23.33 19.19 95231924.64 126.85 02-JAN-10:00 24.00 19.35
February 0.824003E+10 4039.02 26-FEB-17:50 23.48 19.39 86406197.58 126.85 24-FEB-14:00 23.48 19.39
March 0.143005E+11 7170.92 31-MAR-24:00 20.70 19.78 0.103243E+09 126.85 07-MAR-14:00 20.70 19.78
April 0.188361E+11 7829.21 16-APR-18:20 18.07 13.19 91609734.42 126.83 14-APR-09:09 18.07 13.19
May 0.447038E+10 3460.71 31-MAY-24:00 23.00 21.40 99234996.68 126.85 08-MAY-13:00 23.00 21.40
June 0.921271E+10 5329.36 30-JUN-23:57 25.10 23.16 98983001.64 126.87 27-JUN-13:09 25.10 23.16
July 0.145720E+11 7187.81 31-JUL-23:53 25.20 23.65 91896857.74 126.85 14-JUL-13:00 25.20 23.65
August 0.195994E+11 7613.92 06-AUG-17:50 25.17 23.64 0.103375E+09 129.34 28-AUG-13:00 33.00 25.67
September 0.435146E+10 3480.98 30-SEP-24:00 22.30 21.22 91605633.79 126.82 05-SEP-13:30 22.30 21.22
October 0.955041E+10 5343.13 31-OCT-24:00 21.60 20.90 95250011.87 126.87 25-OCT-13:20 21.60 20.90
November 0.140095E+11 5854.63 06-NOV-17:00 26.60 19.72 94308222.88 126.85 01-NOV-09:00 26.60 19.72
December 0.193861E+11 7731.29 10-DEC-16:55 25.00 19.63 91882872.14 126.83 28-DEC-10:09 18.33 18.33
                     
Annual Sum or Average 0.140325E+12         0.114303E+10        
Minimum of Months 0.379658E+10 2009.47   18.07 13.19 86406197.58 126.82   18.07 13.19
Maximum of Months 0.195994E+11 7829.21   26.60 23.65 0.103375E+09 129.34   33.00 25.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.233830E+10 1748.02 19-JAN-17:00 24.00 20.62 95231042.33 126.84 02-JAN-14:09 24.00 20.62
February 0.687047E+10 3619.72 26-FEB-17:54 23.30 19.29 86405551.85 126.85 24-FEB-10:20 23.30 19.29
March 0.128244E+11 6669.80 31-MAR-24:00 20.70 19.78 0.103242E+09 126.84 07-MAR-14:00 20.70 19.78
April 0.177645E+11 7350.88 16-APR-18:06 18.43 13.27 91611674.40 126.83 24-APR-09:09 20.45 20.45
May 0.405177E+10 3218.38 31-MAY-24:00 23.00 21.40 99233579.45 126.82 26-MAY-13:09 23.00 21.40
June 0.868116E+10 5155.39 30-JUN-23:57 25.10 23.16 98981455.16 126.86 19-JUN-09:09 25.10 23.16
July 0.138258E+11 6879.26 31-JUL-23:53 25.20 23.65 91895927.46 126.85 14-JUL-13:00 25.20 23.65
August 0.186745E+11 7194.57 29-AUG-16:00 31.10 23.86 0.103461E+09 129.89 28-AUG-13:00 31.10 23.86
September 0.384378E+10 3191.99 30-SEP-24:00 22.30 21.22 91605370.43 126.82 05-SEP-13:30 22.30 21.22
October 0.880411E+10 4920.07 31-OCT-24:00 21.60 20.90 95248755.41 126.87 24-OCT-09:20 21.60 20.90
November 0.126828E+11 5538.52 06-NOV-17:00 26.60 19.72 94307552.42 126.85 01-NOV-09:00 26.60 19.72
December 0.174544E+11 7274.10 15-DEC-17:00 28.00 21.24 91882894.97 126.83 28-DEC-14:00 20.00 20.00
                     
Annual Sum or Average 0.127816E+12         0.114311E+10        
Minimum of Months 0.233830E+10 1748.02   18.43 13.27 86405551.85 126.82   20.00 19.29
Maximum of Months 0.186745E+11 7350.88   31.10 23.86 0.103461E+09 129.89   31.10 23.86



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.140343E+10 1815.75 19-JAN-17:00 24.00 20.62 95016880.30 127.20 09-JAN-10:09 24.00 20.62
February 0.604062E+10 3665.94 27-FEB-17:40 23.27 19.63 86405681.63 126.85 24-FEB-14:00 23.27 19.63
March 0.121992E+11 6560.21 31-MAR-24:00 20.70 19.78 0.103243E+09 126.85 07-MAR-14:00 20.70 19.78
April 0.176079E+11 7461.95 23-APR-18:05 25.13 21.19 91609923.40 126.83 24-APR-09:09 20.45 20.45
May 0.419472E+10 3201.24 31-MAY-24:00 23.00 21.40 99234752.10 126.85 08-MAY-13:00 23.00 21.40
June 0.883644E+10 5207.71 30-JUN-23:57 25.10 23.16 98982935.08 126.87 01-JUN-13:09 25.10 23.16
July 0.139768E+11 6868.87 31-JUL-23:53 25.20 23.65 91897032.46 126.85 12-JUL-13:20 25.20 23.65
August 0.187997E+11 7375.98 06-AUG-17:40 25.33 23.69 0.103340E+09 128.54 28-AUG-13:00 33.00 25.67
September 0.394963E+10 3222.88 30-SEP-24:00 22.30 21.22 91605386.02 126.82 05-SEP-13:30 22.30 21.22
October 0.874067E+10 4845.83 31-OCT-24:00 21.60 20.90 95249467.37 126.87 06-OCT-13:00 21.60 20.90
November 0.120748E+11 5598.98 06-NOV-17:00 26.60 19.72 94307871.26 126.85 07-NOV-14:00 27.70 24.03
December 0.165262E+11 7340.65 15-DEC-17:00 28.00 21.24 91883283.37 126.83 28-DEC-14:00 20.00 20.00
                     
Annual Sum or Average 0.124350E+12         0.114278E+10        
Minimum of Months 0.140343E+10 1815.75   20.70 19.63 86405681.63 126.82   20.00 19.63
Maximum of Months 0.187997E+11 7461.95   28.00 23.69 0.103340E+09 128.54   33.00 25.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.239534E+12 92474.00 02-JAN-15:00 27.00 18.67 0.206144E+10 2745.29 03-JAN-10:30 9.00 4.28
February 0.435841E+12 182993.35 27-FEB-17:00 24.40 20.28 0.187022E+10 2745.29 02-FEB-14:30 24.40 20.28
March 0.727453E+12 358199.25 31-MAR-24:00 20.70 19.78 0.223475E+10 2745.29 28-MAR-13:00 20.70 19.78
April 0.940116E+12 365498.39 28-APR-16:00 32.20 25.55 0.198297E+10 2745.29 07-APR-09:00 32.20 25.55
May 0.239669E+12 175334.95 31-MAY-24:00 23.00 21.40 0.214810E+10 2745.29 04-MAY-09:20 23.00 21.40
June 0.468058E+12 266978.84 30-JUN-23:53 25.10 23.16 0.214213E+10 2745.29 01-JUN-13:00 25.10 23.16
July 0.730139E+12 359207.51 31-JUL-24:00 25.20 23.65 0.198894E+10 2745.29 07-JUL-09:39 25.20 23.65
August 0.977148E+12 367527.12 21-AUG-16:00 34.00 23.39 0.223475E+10 2745.29 21-AUG-09:30 34.00 23.39
September 0.235625E+12 176337.73 30-SEP-24:00 22.30 21.22 0.198297E+10 2745.29 01-SEP-09:09 22.30 21.22
October 0.487473E+12 268335.65 31-OCT-24:00 21.60 20.90 0.206144E+10 2745.29 06-OCT-09:50 21.60 20.90
November 0.708489E+12 275847.86 06-NOV-17:00 26.60 19.72 0.204131E+10 2745.29 10-NOV-14:00 27.70 19.95
December 0.976687E+12 367387.09 26-DEC-17:00 12.70 5.60 0.198894E+10 2745.29 05-DEC-10:09 12.70 5.60
                     
Annual Sum or Average 0.716623E+13         0.247380E+11        
Minimum of Months 0.235625E+12 92474.00   12.70 5.60 0.187022E+10 2745.29   9.00 4.28
Maximum of Months 0.977148E+12 367527.12   34.00 25.55 0.223475E+10 2745.29   34.00 25.55



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.361047E+09 10330.07 03-JAN-04:05 5.67
February 0.263236E+09 12157.38 22-FEB-04:53 17.70
March 0.223972E+09 11400.19 17-MAR-03:53 15.80
April 0.279828E+09 13504.74 22-APR-15:02 30.42
May 0.394224E+09 15537.42 27-MAY-15:02 32.30
June 0.442339E+09 16573.23 10-JUN-15:02 33.40
July 0.465126E+09 18671.94 22-JUL-16:13 35.73
August 0.444508E+09 16309.95 19-AUG-15:02 33.30
September 0.547460E+09 18735.73 09-SEP-16:13 35.87
October 0.560617E+09 14938.78 07-OCT-15:02 31.95
November 0.562710E+09 12048.50 30-NOV-04:53 16.10
December 0.640316E+09 12184.55 25-DEC-12:13 15.67
         
Annual Sum or Average 0.518538E+10      
Minimum of Months 0.223972E+09 10330.07   5.67
Maximum of Months 0.640316E+09 18735.73   35.87



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.164599E+09 45630.22 05-JAN-06:02 0.17
February 0.265033E+09 51777.23 06-FEB-05:01 3.03
March 44420930.65 44343.93 13-MAR-05:03 6.68
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 76005933.19 47180.24 21-DEC-05:01 0.17
         
Annual Sum or Average 0.550059E+09      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 0.265033E+09 51777.23   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.124557E+09 9443.92 10-JAN-05:01 1.33
February 68610330.82 9676.93 06-FEB-05:01 3.03
March 25120174.05 8799.97 13-MAR-05:03 6.68
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 38141.44 317.85 16-NOV-06:06 9.40
December 67125045.22 9527.03 21-DEC-05:01 0.17
         
Annual Sum or Average 0.285451E+09      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 0.124557E+09 9676.93   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 42193610.43 7216.15 05-JAN-06:02 0.17
February 21498264.00 7274.35 06-FEB-05:01 3.03
March 9479659.01 6239.99 11-MAR-06:02 6.60
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 4338.18 36.15 16-NOV-06:08 9.40
December 35186255.58 7340.77 21-DEC-05:01 0.17
         
Annual Sum or Average 0.108362E+09      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 42193610.43 7340.77   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 6214716.23 9699.56 10-JAN-06:02 3.00
February 4099173.34 9730.65 06-FEB-06:02 2.88
March 1509163.61 3372.12 11-MAR-06:02 6.60
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 16491230.27 9843.70 21-DEC-06:01 0.83
         
Annual Sum or Average 28314283.45      
Minimum of Months 0.00 0.00   0.83
Maximum of Months 16491230.27 9843.70   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 11491013.52 6082.97 10-JAN-06:02 3.00
February 6375652.09 6074.75 06-FEB-06:02 2.88
March 7080.38 59.00 11-MAR-06:02 6.60
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 10403510.00 6167.87 21-DEC-06:01 0.83
         
Annual Sum or Average 28277255.99      
Minimum of Months 0.00 0.00   0.83
Maximum of Months 11491013.52 6167.87   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.104291E+10 12059.87 23-JAN-05:01 7.83
February 0.541141E+09 13081.37 06-FEB-04:01 3.35
March 0.347130E+09 11664.98 13-MAR-04:01 7.05
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 63753953.39 10798.59 16-NOV-06:02 9.40
December 0.638833E+09 11794.53 21-DEC-05:01 0.17
         
Annual Sum or Average 0.263377E+10      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 0.104291E+10 13081.37   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.398745E+09 10338.29 05-JAN-05:01 0.83
February 0.192581E+09 11396.80 06-FEB-04:01 3.35
March 0.166519E+09 9730.31 10-MAR-05:02 5.83
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 33004.48 220.03 28-OCT-05:08 10.00
November 13547633.50 8872.01 16-NOV-06:02 9.40
December 0.301392E+09 10306.70 21-DEC-05:01 0.17
         
Annual Sum or Average 0.107282E+10      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 0.398745E+09 11396.80   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.288714E+09 13725.13 10-JAN-05:01 1.33
February 0.161670E+09 14349.41 06-FEB-04:01 3.35
March 0.184284E+09 13002.78 10-MAR-05:02 5.83
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 2789171.13 7896.41 16-NOV-06:02 9.40
December 0.212777E+09 14027.04 21-DEC-05:01 0.17
         
Annual Sum or Average 0.850233E+09      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 0.288714E+09 14349.41   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.272288E+09 9935.06 10-JAN-05:01 1.33
February 0.129418E+09 10394.10 06-FEB-04:01 3.35
March 77051113.47 8472.13 10-MAR-06:03 5.68
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 4097751.01 7701.20 16-NOV-06:02 9.40
December 0.142728E+09 10068.08 21-DEC-05:01 0.17
         
Annual Sum or Average 0.625582E+09      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 0.272288E+09 10394.10   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 54159135.57 8113.79 09-JAN-05:02 7.83
February 51877162.18 8772.67 06-FEB-05:01 3.03
March 61434492.43 9507.36 13-MAR-04:01 7.05
April 64881839.64 8516.32 10-APR-03:02 13.30
May 32420272.19 5753.71 02-MAY-03:02 24.13
June 27644341.06 5140.17 07-JUN-03:02 21.10
July 25555428.78 3086.47 23-JUL-13:53 33.30
August 16605607.09 3073.85 06-AUG-15:22 28.00
September 30884028.59 6485.47 29-SEP-03:02 23.80
October 50108256.32 8274.00 30-OCT-03:02 17.00
November 66525410.22 8645.10 27-NOV-04:02 14.30
December 0.100128E+09 9476.30 22-DEC-05:02 8.33
         
Annual Sum or Average 0.582224E+09      
Minimum of Months 16605607.09 3073.85   3.03
Maximum of Months 0.100128E+09 9507.36   33.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.144783E+09 4709.39 31-JAN-06:02 18.17
February 92375176.96 4985.19 20-FEB-13:38 23.47
March 72929458.47 5085.99 06-MAR-06:02 18.80
April 21013630.67 4501.49 10-APR-05:02 12.20
May 19240210.38 6753.66 22-MAY-03:02 26.10
June 15174729.34 4367.45 15-JUN-03:02 26.52
July 18722494.53 5005.50 20-JUL-03:02 26.70
August 16835741.71 4972.39 03-AUG-03:02 25.95
September 23305544.06 4053.18 25-SEP-03:02 23.80
October 26728163.63 5025.70 06-OCT-03:02 26.67
November 30198493.28 5026.45 29-NOV-06:02 21.60
December 70804652.17 4731.97 25-DEC-11:08 14.17
         
Annual Sum or Average 0.552111E+09      
Minimum of Months 15174729.34 4053.18   12.20
Maximum of Months 0.144783E+09 6753.66   26.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.168845E+10 12178.56 10-JAN-06:03 3.00
February 0.921240E+09 16751.91 06-FEB-06:13 3.07
March 0.858237E+09 13056.01 20-MAR-05:03 12.10
April 0.154964E+09 13259.44 17-APR-05:02 12.70
May 29603992.36 5201.01 08-MAY-03:02 24.40
June 23800259.93 6552.16 07-JUN-04:03 21.10
July 20574917.61 5592.27 10-JUL-03:02 25.60
August 20779384.86 5729.34 01-AUG-04:03 23.90
September 24623140.59 7863.53 08-SEP-05:02 24.58
October 81223497.21 10244.10 27-OCT-05:03 15.00
November 0.328086E+09 8597.57 30-NOV-06:03 15.08
December 0.123589E+10 12436.09 21-DEC-06:03 0.83
         
Annual Sum or Average 0.538748E+10      
Minimum of Months 20574917.61 5201.01   0.83
Maximum of Months 0.168845E+10 16751.91   25.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.165561E+09 525.60 10-JAN-04:45 1.17
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.165561E+09      
Minimum of Months 0.00 0.00   1.17
Maximum of Months 0.165561E+09 525.60   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:03 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.113123E+11 11837.83 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.102611E+11 11837.83 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.121930E+11 11837.83 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.108909E+11 11837.83 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.117527E+11 11837.83 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.116958E+11 11837.83 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.109477E+11 11837.83 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.121930E+11 11837.83 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.108909E+11 11837.83 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.113123E+11 11837.83 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.111797E+11 11837.83 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.109477E+11 11837.83 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.135577E+12     0.424397E+12    
Minimum of Months 0.102611E+11 11837.83   0.325565E+11 13457.54  
Maximum of Months 0.121930E+11 11837.83   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101592E+11 10631.20 02-JAN-08:09 0.243681E+11 17206.63 02-JAN-08:09
February 0.921518E+10 10631.20 01-FEB-08:09 0.220609E+11 17206.63 01-FEB-08:09
March 0.109502E+11 10631.20 01-MAR-08:09 0.253549E+11 17206.63 01-MAR-08:09
April 0.978077E+10 10631.20 03-APR-07:10 0.235306E+11 17206.63 03-APR-07:10
May 0.105547E+11 10631.20 01-MAY-07:10 0.248615E+11 17206.63 01-MAY-07:10
June 0.105037E+11 10631.20 01-JUN-07:10 0.244160E+11 17206.63 01-JUN-07:10
July 0.983180E+10 10631.20 03-JUL-07:10 0.239708E+11 17206.63 03-JUL-07:10
August 0.109502E+11 10631.20 01-AUG-07:10 0.253549E+11 17206.63 01-AUG-07:10
September 0.978077E+10 10631.20 01-SEP-07:10 0.235199E+11 17206.63 01-SEP-07:10
October 0.101592E+11 10631.20 02-OCT-07:10 0.243735E+11 17206.63 02-OCT-07:10
November 0.100402E+11 10631.20 01-NOV-07:10 0.238373E+11 17206.63 01-NOV-07:10
December 0.983180E+10 10631.20 01-DEC-08:09 0.239654E+11 17206.63 01-DEC-08:09
             
Annual Sum or Average 0.121758E+12     0.289614E+12    
Minimum of Months 0.921518E+10 10631.20   0.220609E+11 17206.63  
Maximum of Months 0.109502E+11 10631.20   0.253549E+11 17206.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101592E+11 10631.20 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.921518E+10 10631.20 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.109502E+11 10631.20 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.978077E+10 10631.20 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.105547E+11 10631.20 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.105037E+11 10631.20 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.983180E+10 10631.20 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.109502E+11 10631.20 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.978077E+10 10631.20 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.101592E+11 10631.20 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.100402E+11 10631.20 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.983180E+10 10631.20 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.121758E+12     0.289613E+12    
Minimum of Months 0.921518E+10 10631.20   0.220609E+11 17206.56  
Maximum of Months 0.109502E+11 10631.20   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.101592E+11 10631.20 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.921518E+10 10631.20 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.109502E+11 10631.20 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.978077E+10 10631.20 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.105547E+11 10631.20 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.105037E+11 10631.20 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.983180E+10 10631.20 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.109502E+11 10631.20 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.978077E+10 10631.20 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.101592E+11 10631.20 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.100402E+11 10631.20 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.983180E+10 10631.20 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.121758E+12     0.289613E+12    
Minimum of Months 0.921518E+10 10631.20   0.220609E+11 17206.56  
Maximum of Months 0.109502E+11 10631.20   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.811160E+09 1135.02 31-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.702011E+09 1167.25 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.803448E+09 1091.46 27-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.694308E+09 1115.86 14-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.723357E+09 883.46 23-MAY-07:30 0.312174E+10 2160.55 01-MAY-07:10
June 0.709831E+09 689.07 27-JUN-11:30 0.306580E+10 2160.55 01-JUN-07:10
July 0.672503E+09 736.83 14-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.760486E+09 911.01 21-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.704043E+09 1088.83 26-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.752426E+09 1214.09 25-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.795053E+09 1174.17 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.801756E+09 1205.45 12-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.893038E+10     0.363654E+11    
Minimum of Months 0.672503E+09 689.07   0.277008E+10 2160.55  
Maximum of Months 0.811160E+09 1214.09   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.507326E+09 704.89 04-JAN-16:00 0.197184E+10 1392.34 02-JAN-08:09
February 0.444013E+09 729.41 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.509095E+09 661.70 27-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.446198E+09 696.02 14-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.469860E+09 560.96 30-MAY-15:30 0.201177E+10 1392.34 01-MAY-07:10
June 0.462571E+09 445.37 27-JUN-13:30 0.197572E+10 1392.34 01-JUN-07:10
July 0.436938E+09 451.48 14-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.491107E+09 472.79 21-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.451440E+09 658.09 26-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.479627E+09 767.38 25-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.500294E+09 764.09 21-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.503926E+09 767.68 12-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.570240E+10     0.234352E+11    
Minimum of Months 0.436938E+09 445.37   0.178515E+10 1392.34  
Maximum of Months 0.509095E+09 767.68   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.753915E+09 1106.32 31-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.670839E+09 1149.29 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.786625E+09 1081.67 27-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.695940E+09 1119.68 14-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.732927E+09 914.74 23-MAY-07:19 0.312179E+10 2160.58 01-MAY-07:10
June 0.720760E+09 719.77 16-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.680495E+09 857.85 14-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.764630E+09 946.49 21-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.699387E+09 1085.88 26-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.737534E+09 1206.62 25-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.746421E+09 1144.87 21-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.747149E+09 1194.94 12-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.873662E+10     0.363660E+11    
Minimum of Months 0.670839E+09 719.77   0.277013E+10 2160.58  
Maximum of Months 0.786625E+09 1206.62   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.502986E+09 741.01 31-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.443326E+09 758.17 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.517170E+09 726.59 27-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.451774E+09 734.93 14-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.473215E+09 637.06 24-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.464361E+09 561.45 16-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.439551E+09 603.04 14-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.496294E+09 681.58 23-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.458088E+09 727.14 26-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.483275E+09 788.54 25-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.492988E+09 771.05 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.493842E+09 778.02 12-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.571687E+10     0.234351E+11    
Minimum of Months 0.439551E+09 561.45   0.178514E+10 1392.33  
Maximum of Months 0.517170E+09 788.54   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.811064E+09 1139.16 31-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.702087E+09 1170.75 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.803282E+09 1096.78 27-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.694254E+09 1120.56 14-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.723821E+09 892.90 23-MAY-07:30 0.312174E+10 2160.55 01-MAY-07:10
June 0.709056E+09 684.55 27-JUN-11:30 0.306580E+10 2160.55 01-JUN-07:10
July 0.672651E+09 734.95 14-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.760616E+09 920.22 21-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.704010E+09 1094.11 26-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.752685E+09 1216.67 25-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.795121E+09 1177.57 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.802431E+09 1208.17 12-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.893108E+10     0.363654E+11    
Minimum of Months 0.672651E+09 684.55   0.277008E+10 2160.55  
Maximum of Months 0.811064E+09 1216.67   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.506884E+09 706.33 04-JAN-16:00 0.197184E+10 1392.34 02-JAN-08:09
February 0.443850E+09 730.25 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.508693E+09 663.73 27-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.446107E+09 697.47 14-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.469576E+09 559.82 30-MAY-15:30 0.201177E+10 1392.34 01-MAY-07:10
June 0.462451E+09 442.08 27-JUN-13:30 0.197572E+10 1392.34 01-JUN-07:10
July 0.436780E+09 449.98 14-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.491009E+09 471.62 21-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.451301E+09 660.42 26-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.479538E+09 768.03 25-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.500218E+09 764.31 21-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.503751E+09 768.09 12-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.570016E+10     0.234352E+11    
Minimum of Months 0.436780E+09 442.08   0.178515E+10 1392.34  
Maximum of Months 0.508693E+09 768.09   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.753999E+09 1111.44 31-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.670984E+09 1153.40 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.786677E+09 1087.32 27-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.696156E+09 1124.26 14-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.733034E+09 923.25 23-MAY-07:19 0.312179E+10 2160.58 01-MAY-07:10
June 0.720907E+09 717.43 16-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.680533E+09 867.36 14-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.764950E+09 954.53 21-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.699434E+09 1091.25 26-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.737811E+09 1209.46 25-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.746814E+09 1149.40 21-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.747875E+09 1198.05 12-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.873917E+10     0.363660E+11    
Minimum of Months 0.670984E+09 717.43   0.277013E+10 2160.58  
Maximum of Months 0.786677E+09 1209.46   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.502621E+09 741.26 31-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.443165E+09 758.38 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.516871E+09 726.84 27-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.451713E+09 735.16 14-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.472965E+09 637.17 24-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.464048E+09 561.61 16-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.439228E+09 603.49 14-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.496028E+09 682.14 23-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.457899E+09 727.39 26-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.483209E+09 788.68 25-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.493151E+09 771.27 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.493545E+09 778.20 12-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.571444E+10     0.234351E+11    
Minimum of Months 0.439228E+09 561.61   0.178514E+10 1392.33  
Maximum of Months 0.516871E+09 788.68   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.811105E+09 1138.96 31-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.702071E+09 1170.56 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.803214E+09 1096.55 27-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.694237E+09 1120.34 14-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.723803E+09 892.46 23-MAY-07:30 0.312174E+10 2160.55 01-MAY-07:10
June 0.709042E+09 684.39 27-JUN-11:30 0.306580E+10 2160.55 01-JUN-07:10
July 0.672637E+09 734.80 14-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.760599E+09 919.88 21-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.703964E+09 1093.89 26-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.752628E+09 1216.54 25-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.795090E+09 1177.44 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.802355E+09 1208.02 12-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.893074E+10     0.363654E+11    
Minimum of Months 0.672637E+09 684.39   0.277008E+10 2160.55  
Maximum of Months 0.811105E+09 1216.54   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.506887E+09 706.46 04-JAN-16:00 0.197184E+10 1392.34 02-JAN-08:09
February 0.443850E+09 730.15 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.508681E+09 663.61 27-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.446107E+09 697.34 14-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.469565E+09 559.68 30-MAY-15:30 0.201177E+10 1392.34 01-MAY-07:10
June 0.462443E+09 442.00 27-JUN-13:30 0.197572E+10 1392.34 01-JUN-07:10
July 0.436755E+09 449.85 14-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.491013E+09 471.53 21-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.451464E+09 660.31 26-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.479533E+09 767.96 25-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.500221E+09 764.21 21-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.503717E+09 768.00 12-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.570024E+10     0.234352E+11    
Minimum of Months 0.436755E+09 442.00   0.178515E+10 1392.34  
Maximum of Months 0.508681E+09 768.00   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.753994E+09 1111.23 31-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.670979E+09 1153.22 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.786661E+09 1087.10 27-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.696136E+09 1124.03 14-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.733010E+09 922.83 23-MAY-07:19 0.312179E+10 2160.58 01-MAY-07:10
June 0.720905E+09 717.27 16-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.680477E+09 866.95 14-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.764921E+09 954.20 21-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.699416E+09 1091.03 26-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.737796E+09 1209.33 25-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.746811E+09 1149.24 21-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.747866E+09 1197.90 12-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.873897E+10     0.363660E+11    
Minimum of Months 0.670979E+09 717.27   0.277013E+10 2160.58  
Maximum of Months 0.786661E+09 1209.33   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.502623E+09 741.13 31-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.443186E+09 758.27 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.516866E+09 726.71 27-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.451709E+09 735.02 14-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.472943E+09 637.02 24-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.464039E+09 561.42 16-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.439215E+09 603.25 14-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.496010E+09 682.08 23-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.457883E+09 727.25 26-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.483189E+09 788.60 25-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.493150E+09 771.19 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.493522E+09 778.10 12-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.571434E+10     0.234351E+11    
Minimum of Months 0.439215E+09 561.42   0.178514E+10 1392.33  
Maximum of Months 0.516866E+09 788.60   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272315E+09 284.97 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.247010E+09 284.97 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.293517E+09 284.97 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.262171E+09 284.97 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.282916E+09 284.97 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.281548E+09 284.97 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.263538E+09 284.97 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.293517E+09 284.97 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.262171E+09 284.97 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.272315E+09 284.97 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.269124E+09 284.97 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.263538E+09 284.97 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.326368E+10     0.153881E+12    
Minimum of Months 0.247010E+09 284.97   0.505780E+10 1948.61  
Maximum of Months 0.293517E+09 284.97   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272315E+09 284.97 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.247010E+09 284.97 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.293517E+09 284.97 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.262171E+09 284.97 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.282916E+09 284.97 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.281548E+09 284.97 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.263538E+09 284.97 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.293517E+09 284.97 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.262171E+09 284.97 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.272315E+09 284.97 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.269124E+09 284.97 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.263538E+09 284.97 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.326368E+10     0.153881E+12    
Minimum of Months 0.247010E+09 284.97   0.505780E+10 1948.61  
Maximum of Months 0.293517E+09 284.97   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272315E+09 284.97 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.247010E+09 284.97 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.293517E+09 284.97 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.262171E+09 284.97 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.282916E+09 284.97 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.281548E+09 284.97 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.263538E+09 284.97 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.293517E+09 284.97 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.262171E+09 284.97 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.272315E+09 284.97 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.269124E+09 284.97 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.263538E+09 284.97 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.326368E+10     0.153881E+12    
Minimum of Months 0.247010E+09 284.97   0.505780E+10 1948.61  
Maximum of Months 0.293517E+09 284.97   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.318958E+10 3337.76 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.289319E+10 3337.76 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.343791E+10 3337.76 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.307076E+10 3337.76 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.331375E+10 3337.76 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.329773E+10 3337.76 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.308678E+10 3337.76 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.343791E+10 3337.76 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.307076E+10 3337.76 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.318958E+10 3337.76 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.315220E+10 3337.76 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.308678E+10 3337.76 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.382269E+11     0.749486E+13    
Minimum of Months 0.289319E+10 3337.76   0.246344E+12 94908.13  
Maximum of Months 0.343791E+10 3337.76   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.113123E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.102611E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.121930E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.108909E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.117527E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.116958E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.109477E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.121930E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.108909E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.113123E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.111797E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.109477E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.135577E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.102611E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.121930E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.101592E+11 0.243681E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.109502E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.978077E+10 0.235306E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.105547E+11 0.248615E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.105037E+11 0.244160E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.983180E+10 0.239708E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.109502E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.978077E+10 0.235199E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.101592E+11 0.243735E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.100402E+11 0.238373E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.983180E+10 0.239654E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.121758E+12 0.289614E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.109502E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.101592E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.978077E+10 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.105547E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.105037E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.983180E+10 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.978077E+10 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.101592E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.100402E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.983180E+10 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.121758E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.101592E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.978077E+10 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.105547E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.105037E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.983180E+10 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.978077E+10 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.101592E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.100402E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.983180E+10 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.121758E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.921518E+10 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.109502E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.811160E+09 0.305979E+10 0.00 0.00 0.00 0.00 291468.04 92590153.40
February 0.136985E+10 0.702011E+09 0.277008E+10 0.00 0.00 0.00 0.00 535911.83 72354429.86
March 0.163685E+10 0.803448E+09 0.318369E+10 0.00 0.00 0.00 0.00 1683937.54 75467746.44
April 0.145243E+10 0.694308E+09 0.295462E+10 0.00 0.00 0.00 0.00 3419318.90 30903928.61
May 0.157338E+10 0.723357E+09 0.312174E+10 0.00 0.00 0.00 0.00 14195187.57 4329890.29
June 0.156900E+10 0.709831E+09 0.306580E+10 0.00 0.00 0.00 0.00 13283889.66 2656122.17
July 0.145680E+10 0.672503E+09 0.300989E+10 0.00 0.00 0.00 0.00 20004724.42 438275.87
August 0.163685E+10 0.760486E+09 0.318369E+10 0.00 0.00 0.00 0.00 18998996.53 2520104.36
September 0.145243E+10 0.704043E+09 0.295328E+10 0.00 0.00 0.00 0.00 16274761.32 7518194.64
October 0.150991E+10 0.752426E+09 0.306046E+10 0.00 0.00 0.00 0.00 13578189.23 26142115.95
November 0.149516E+10 0.795053E+09 0.299314E+10 0.00 0.00 0.00 0.00 1451096.21 47479902.38
December 0.145680E+10 0.801756E+09 0.300922E+10 0.00 0.00 0.00 0.00 907390.03 84102341.46
                   
Annual Sum or Average 0.181194E+11 0.893038E+10 0.363654E+11 0.00 0.00 0.00 0.00 0.104625E+09 0.446503E+09
Minimum of Months 0.136985E+10 0.672503E+09 0.277008E+10 0.00 0.00 0.00 0.00 291468.04 438275.87
Maximum of Months 0.163685E+10 0.811160E+09 0.318369E+10 0.00 0.00 0.00 0.00 20004724.42 92590153.40



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.507326E+09 0.197184E+10 0.00 0.00 0.00 0.00 155388.13 63369611.91
February 0.882782E+09 0.444013E+09 0.178515E+10 0.00 0.00 0.00 0.00 326198.96 49002418.54
March 0.105485E+10 0.509095E+09 0.205169E+10 0.00 0.00 0.00 0.00 975083.57 49900647.72
April 0.936002E+09 0.446198E+09 0.190407E+10 0.00 0.00 0.00 0.00 2263638.98 19958870.12
May 0.101394E+10 0.469860E+09 0.201177E+10 0.00 0.00 0.00 0.00 9185118.24 2853091.04
June 0.101113E+10 0.462571E+09 0.197572E+10 0.00 0.00 0.00 0.00 9052601.85 1493445.39
July 0.938820E+09 0.436938E+09 0.193969E+10 0.00 0.00 0.00 0.00 13966494.18 192700.99
August 0.105485E+10 0.491107E+09 0.205169E+10 0.00 0.00 0.00 0.00 13585499.62 1102226.10
September 0.936002E+09 0.451440E+09 0.190321E+10 0.00 0.00 0.00 0.00 10301957.13 4841621.02
October 0.973041E+09 0.479627E+09 0.197228E+10 0.00 0.00 0.00 0.00 8647919.35 17044970.07
November 0.963541E+09 0.500294E+09 0.192889E+10 0.00 0.00 0.00 0.00 891661.21 31556722.57
December 0.938820E+09 0.503926E+09 0.193926E+10 0.00 0.00 0.00 0.00 570877.00 54430380.15
                   
Annual Sum or Average 0.116768E+11 0.570240E+10 0.234352E+11 0.00 0.00 0.00 0.00 69922438.21 0.295747E+09
Minimum of Months 0.882782E+09 0.436938E+09 0.178515E+10 0.00 0.00 0.00 0.00 155388.13 192700.99
Maximum of Months 0.105485E+10 0.509095E+09 0.205169E+10 0.00 0.00 0.00 0.00 13966494.18 63369611.91



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.753915E+09 0.305983E+10 0.00 0.00 0.00 0.00 160690.30 0.100841E+09
February 0.136988E+10 0.670839E+09 0.277013E+10 0.00 0.00 0.00 0.00 375508.50 77186911.64
March 0.163688E+10 0.786625E+09 0.318374E+10 0.00 0.00 0.00 0.00 1181023.31 77122629.03
April 0.145246E+10 0.695940E+09 0.295467E+10 0.00 0.00 0.00 0.00 3058392.92 31999700.41
May 0.157341E+10 0.732927E+09 0.312179E+10 0.00 0.00 0.00 0.00 14158764.63 4307265.62
June 0.156904E+10 0.720760E+09 0.306585E+10 0.00 0.00 0.00 0.00 13485772.32 2564457.22
July 0.145684E+10 0.680495E+09 0.300994E+10 0.00 0.00 0.00 0.00 20023896.37 438211.32
August 0.163688E+10 0.764630E+09 0.318374E+10 0.00 0.00 0.00 0.00 18291888.17 2757775.03
September 0.145246E+10 0.699387E+09 0.295333E+10 0.00 0.00 0.00 0.00 14518029.72 8526681.01
October 0.150994E+10 0.737534E+09 0.306051E+10 0.00 0.00 0.00 0.00 10629634.65 30734010.89
November 0.149520E+10 0.746421E+09 0.299318E+10 0.00 0.00 0.00 0.00 1008201.92 52531315.27
December 0.145684E+10 0.747149E+09 0.300927E+10 0.00 0.00 0.00 0.00 645617.49 90343165.35
                   
Annual Sum or Average 0.181198E+11 0.873662E+10 0.363660E+11 0.00 0.00 0.00 0.00 97537420.31 0.479353E+09
Minimum of Months 0.136988E+10 0.670839E+09 0.277013E+10 0.00 0.00 0.00 0.00 160690.30 438211.32
Maximum of Months 0.163688E+10 0.786625E+09 0.318374E+10 0.00 0.00 0.00 0.00 20023896.37 0.100841E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.502986E+09 0.197183E+10 0.00 0.00 0.00 0.00 139462.05 68511402.79
February 0.882782E+09 0.443326E+09 0.178514E+10 0.00 0.00 0.00 0.00 271736.73 55053819.59
March 0.105485E+10 0.517170E+09 0.205168E+10 0.00 0.00 0.00 0.00 821763.09 59233040.25
April 0.936002E+09 0.451774E+09 0.190406E+10 0.00 0.00 0.00 0.00 1727021.76 27217614.78
May 0.101394E+10 0.473215E+09 0.201175E+10 0.00 0.00 0.00 0.00 8697208.97 4914692.38
June 0.101113E+10 0.464361E+09 0.197570E+10 0.00 0.00 0.00 0.00 7675845.57 3345266.20
July 0.938820E+09 0.439551E+09 0.193968E+10 0.00 0.00 0.00 0.00 10639028.80 1388536.74
August 0.105485E+10 0.496294E+09 0.205168E+10 0.00 0.00 0.00 0.00 10230524.68 4387487.33
September 0.936002E+09 0.458088E+09 0.190319E+10 0.00 0.00 0.00 0.00 9553066.18 7489411.94
October 0.973041E+09 0.483275E+09 0.197226E+10 0.00 0.00 0.00 0.00 7363269.16 23272507.00
November 0.963541E+09 0.492988E+09 0.192888E+10 0.00 0.00 0.00 0.00 719151.57 38096466.83
December 0.938820E+09 0.493842E+09 0.193924E+10 0.00 0.00 0.00 0.00 456027.70 67419966.93
                   
Annual Sum or Average 0.116768E+11 0.571687E+10 0.234351E+11 0.00 0.00 0.00 0.00 58294106.26 0.360330E+09
Minimum of Months 0.882782E+09 0.439551E+09 0.178514E+10 0.00 0.00 0.00 0.00 139462.05 1388536.74
Maximum of Months 0.105485E+10 0.517170E+09 0.205168E+10 0.00 0.00 0.00 0.00 10639028.80 68511402.79



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.811064E+09 0.305979E+10 0.00 0.00 0.00 0.00 1810449.41 0.184209E+09
February 0.136985E+10 0.702087E+09 0.277008E+10 0.00 0.00 0.00 0.00 1843754.45 0.143831E+09
March 0.163685E+10 0.803282E+09 0.318369E+10 0.00 0.00 0.00 0.00 5212752.88 0.155174E+09
April 0.145243E+10 0.694254E+09 0.295462E+10 0.00 0.00 0.00 0.00 7969308.12 69931997.58
May 0.157338E+10 0.723821E+09 0.312174E+10 0.00 0.00 0.00 0.00 32109437.64 11033819.11
June 0.156900E+10 0.709056E+09 0.306580E+10 0.00 0.00 0.00 0.00 29093778.35 8868624.64
July 0.145680E+10 0.672651E+09 0.300989E+10 0.00 0.00 0.00 0.00 41528337.82 3377653.75
August 0.163685E+10 0.760616E+09 0.318369E+10 0.00 0.00 0.00 0.00 39473985.29 11403822.40
September 0.145243E+10 0.704010E+09 0.295328E+10 0.00 0.00 0.00 0.00 37833158.78 17243520.68
October 0.150991E+10 0.752685E+09 0.306046E+10 0.00 0.00 0.00 0.00 32137473.05 58343693.30
November 0.149516E+10 0.795121E+09 0.299314E+10 0.00 0.00 0.00 0.00 4525394.12 96878627.82
December 0.145680E+10 0.802431E+09 0.300922E+10 0.00 0.00 0.00 0.00 3084933.76 0.166574E+09
                   
Annual Sum or Average 0.181194E+11 0.893108E+10 0.363654E+11 0.00 0.00 0.00 0.00 0.236623E+09 0.926870E+09
Minimum of Months 0.136985E+10 0.672651E+09 0.277008E+10 0.00 0.00 0.00 0.00 1810449.41 3377653.75
Maximum of Months 0.163685E+10 0.811064E+09 0.318369E+10 0.00 0.00 0.00 0.00 41528337.82 0.184209E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.506884E+09 0.197184E+10 0.00 0.00 0.00 0.00 626916.46 0.131094E+09
February 0.649041E+09 0.443850E+09 0.178515E+10 0.00 0.00 0.00 0.00 877873.16 0.103118E+09
March 0.773965E+09 0.508693E+09 0.205169E+10 0.00 0.00 0.00 0.00 2308514.60 0.111057E+09
April 0.688021E+09 0.446107E+09 0.190407E+10 0.00 0.00 0.00 0.00 4650753.60 51493768.46
May 0.744847E+09 0.469576E+09 0.201177E+10 0.00 0.00 0.00 0.00 19600286.42 8558560.94
June 0.742030E+09 0.462451E+09 0.197572E+10 0.00 0.00 0.00 0.00 18590352.32 6467418.51
July 0.690839E+09 0.436780E+09 0.193969E+10 0.00 0.00 0.00 0.00 25867847.31 2913702.06
August 0.773965E+09 0.491009E+09 0.205169E+10 0.00 0.00 0.00 0.00 25007104.51 8415206.39
September 0.688021E+09 0.451301E+09 0.190321E+10 0.00 0.00 0.00 0.00 22685072.44 12762195.59
October 0.715730E+09 0.479538E+09 0.197228E+10 0.00 0.00 0.00 0.00 18477766.86 42524677.63
November 0.708685E+09 0.500218E+09 0.192889E+10 0.00 0.00 0.00 0.00 2127777.15 70499954.96
December 0.690839E+09 0.503751E+09 0.193926E+10 0.00 0.00 0.00 0.00 1459550.03 0.116552E+09
                   
Annual Sum or Average 0.858171E+10 0.570016E+10 0.234352E+11 0.00 0.00 0.00 0.00 0.142280E+09 0.665457E+09
Minimum of Months 0.649041E+09 0.436780E+09 0.178515E+10 0.00 0.00 0.00 0.00 626916.46 2913702.06
Maximum of Months 0.773965E+09 0.508693E+09 0.205169E+10 0.00 0.00 0.00 0.00 25867847.31 0.131094E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.753999E+09 0.305983E+10 0.00 0.00 0.00 0.00 301546.60 0.228952E+09
February 0.136988E+10 0.670984E+09 0.277013E+10 0.00 0.00 0.00 0.00 806258.18 0.174082E+09
March 0.163688E+10 0.786677E+09 0.318374E+10 0.00 0.00 0.00 0.00 2639864.47 0.173190E+09
April 0.145246E+10 0.696156E+09 0.295467E+10 0.00 0.00 0.00 0.00 6871300.18 77402027.37
May 0.157341E+10 0.733034E+09 0.312179E+10 0.00 0.00 0.00 0.00 31925183.86 11310969.00
June 0.156904E+10 0.720907E+09 0.306585E+10 0.00 0.00 0.00 0.00 29749263.42 8487779.50
July 0.145684E+10 0.680533E+09 0.300994E+10 0.00 0.00 0.00 0.00 41895463.53 3301160.17
August 0.163688E+10 0.764950E+09 0.318374E+10 0.00 0.00 0.00 0.00 37923498.17 12520524.28
September 0.145246E+10 0.699434E+09 0.295333E+10 0.00 0.00 0.00 0.00 32481620.52 21414090.12
October 0.150994E+10 0.737811E+09 0.306051E+10 0.00 0.00 0.00 0.00 23327562.24 77471157.19
November 0.149520E+10 0.746814E+09 0.299318E+10 0.00 0.00 0.00 0.00 2213434.54 0.122212E+09
December 0.145684E+10 0.747875E+09 0.300927E+10 0.00 0.00 0.00 0.00 1419938.69 0.205397E+09
                   
Annual Sum or Average 0.181198E+11 0.873917E+10 0.363660E+11 0.00 0.00 0.00 0.00 0.211555E+09 0.111574E+10
Minimum of Months 0.136988E+10 0.670984E+09 0.277013E+10 0.00 0.00 0.00 0.00 301546.60 3301160.17
Maximum of Months 0.163688E+10 0.786677E+09 0.318374E+10 0.00 0.00 0.00 0.00 41895463.53 0.228952E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.502621E+09 0.197183E+10 0.00 0.00 0.00 0.00 538117.88 0.138100E+09
February 0.882782E+09 0.443165E+09 0.178514E+10 0.00 0.00 0.00 0.00 776931.24 0.107633E+09
March 0.105485E+10 0.516871E+09 0.205168E+10 0.00 0.00 0.00 0.00 2438926.25 0.116002E+09
April 0.936002E+09 0.451713E+09 0.190406E+10 0.00 0.00 0.00 0.00 4113989.02 57061032.22
May 0.101394E+10 0.472965E+09 0.201175E+10 0.00 0.00 0.00 0.00 19788924.72 10696396.07
June 0.101113E+10 0.464048E+09 0.197570E+10 0.00 0.00 0.00 0.00 17590214.03 8709713.89
July 0.938820E+09 0.439228E+09 0.193968E+10 0.00 0.00 0.00 0.00 24462317.67 4571507.28
August 0.105485E+10 0.496028E+09 0.205168E+10 0.00 0.00 0.00 0.00 24109086.40 11845098.26
September 0.936002E+09 0.457899E+09 0.190319E+10 0.00 0.00 0.00 0.00 21774653.65 16076456.97
October 0.973041E+09 0.483209E+09 0.197226E+10 0.00 0.00 0.00 0.00 17845752.05 49524013.34
November 0.963541E+09 0.493151E+09 0.192888E+10 0.00 0.00 0.00 0.00 2234654.03 74004830.75
December 0.938820E+09 0.493545E+09 0.193924E+10 0.00 0.00 0.00 0.00 1376503.84 0.126260E+09
                   
Annual Sum or Average 0.116768E+11 0.571444E+10 0.234351E+11 0.00 0.00 0.00 0.00 0.137050E+09 0.720484E+09
Minimum of Months 0.882782E+09 0.439228E+09 0.178514E+10 0.00 0.00 0.00 0.00 538117.88 4571507.28
Maximum of Months 0.105485E+10 0.516871E+09 0.205168E+10 0.00 0.00 0.00 0.00 24462317.67 0.138100E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.811105E+09 0.305979E+10 0.00 0.00 0.00 0.00 2520881.88 0.207396E+09
February 0.136985E+10 0.702071E+09 0.277008E+10 0.00 0.00 0.00 0.00 2568152.28 0.159872E+09
March 0.163685E+10 0.803214E+09 0.318369E+10 0.00 0.00 0.00 0.00 6300614.11 0.179143E+09
April 0.145243E+10 0.694237E+09 0.295462E+10 0.00 0.00 0.00 0.00 9080788.38 83945507.08
May 0.157338E+10 0.723803E+09 0.312174E+10 0.00 0.00 0.00 0.00 37072072.97 15623286.12
June 0.156900E+10 0.709042E+09 0.306580E+10 0.00 0.00 0.00 0.00 33646509.64 12388812.29
July 0.145680E+10 0.672637E+09 0.300989E+10 0.00 0.00 0.00 0.00 47378283.06 5265476.84
August 0.163685E+10 0.760599E+09 0.318369E+10 0.00 0.00 0.00 0.00 45982939.48 16094980.37
September 0.145243E+10 0.703964E+09 0.295328E+10 0.00 0.00 0.00 0.00 42959021.31 23369639.18
October 0.150991E+10 0.752628E+09 0.306046E+10 0.00 0.00 0.00 0.00 37041267.79 69948160.25
November 0.149516E+10 0.795090E+09 0.299314E+10 0.00 0.00 0.00 0.00 5871067.82 0.108720E+09
December 0.145680E+10 0.802355E+09 0.300922E+10 0.00 0.00 0.00 0.00 4260916.22 0.188640E+09
                   
Annual Sum or Average 0.181194E+11 0.893074E+10 0.363654E+11 0.00 0.00 0.00 0.00 0.274683E+09 0.107041E+10
Minimum of Months 0.136985E+10 0.672637E+09 0.277008E+10 0.00 0.00 0.00 0.00 2520881.88 5265476.84
Maximum of Months 0.163685E+10 0.811105E+09 0.318369E+10 0.00 0.00 0.00 0.00 47378283.06 0.207396E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.506887E+09 0.197184E+10 0.00 0.00 0.00 0.00 838659.46 0.148059E+09
February 0.882782E+09 0.443850E+09 0.178515E+10 0.00 0.00 0.00 0.00 1061800.80 0.115459E+09
March 0.105485E+10 0.508681E+09 0.205169E+10 0.00 0.00 0.00 0.00 2647091.08 0.130217E+09
April 0.936002E+09 0.446107E+09 0.190407E+10 0.00 0.00 0.00 0.00 5245141.64 62853130.38
May 0.101394E+10 0.469565E+09 0.201177E+10 0.00 0.00 0.00 0.00 23034265.28 11878963.93
June 0.101113E+10 0.462443E+09 0.197572E+10 0.00 0.00 0.00 0.00 21759865.24 8958778.05
July 0.938820E+09 0.436755E+09 0.193969E+10 0.00 0.00 0.00 0.00 30008188.22 4341352.84
August 0.105485E+10 0.491013E+09 0.205169E+10 0.00 0.00 0.00 0.00 29480041.18 11799108.60
September 0.936002E+09 0.451464E+09 0.190321E+10 0.00 0.00 0.00 0.00 26230834.03 17262588.68
October 0.973041E+09 0.479533E+09 0.197228E+10 0.00 0.00 0.00 0.00 21370576.96 51655762.34
November 0.963541E+09 0.500221E+09 0.192889E+10 0.00 0.00 0.00 0.00 2523503.69 80826985.32
December 0.938820E+09 0.503717E+09 0.193926E+10 0.00 0.00 0.00 0.00 1840410.15 0.132977E+09
                   
Annual Sum or Average 0.116768E+11 0.570024E+10 0.234352E+11 0.00 0.00 0.00 0.00 0.166040E+09 0.776289E+09
Minimum of Months 0.882782E+09 0.436755E+09 0.178515E+10 0.00 0.00 0.00 0.00 838659.46 4341352.84
Maximum of Months 0.105485E+10 0.508681E+09 0.205169E+10 0.00 0.00 0.00 0.00 30008188.22 0.148059E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.753994E+09 0.305983E+10 0.00 0.00 0.00 0.00 356308.80 0.263253E+09
February 0.136988E+10 0.670979E+09 0.277013E+10 0.00 0.00 0.00 0.00 939994.12 0.197129E+09
March 0.163688E+10 0.786661E+09 0.318374E+10 0.00 0.00 0.00 0.00 3059556.26 0.202499E+09
April 0.145246E+10 0.696136E+09 0.295467E+10 0.00 0.00 0.00 0.00 7807784.44 93856752.84
May 0.157341E+10 0.733010E+09 0.312179E+10 0.00 0.00 0.00 0.00 36910757.36 15994975.49
June 0.156904E+10 0.720905E+09 0.306585E+10 0.00 0.00 0.00 0.00 34385784.48 11894914.74
July 0.145684E+10 0.680477E+09 0.300994E+10 0.00 0.00 0.00 0.00 47900868.02 5120516.14
August 0.163688E+10 0.764921E+09 0.318374E+10 0.00 0.00 0.00 0.00 44358016.15 17619470.10
September 0.145246E+10 0.699416E+09 0.295333E+10 0.00 0.00 0.00 0.00 37926826.05 28868622.51
October 0.150994E+10 0.737796E+09 0.306051E+10 0.00 0.00 0.00 0.00 27621976.08 95450875.71
November 0.149520E+10 0.746811E+09 0.299318E+10 0.00 0.00 0.00 0.00 2672362.85 0.143726E+09
December 0.145684E+10 0.747866E+09 0.300927E+10 0.00 0.00 0.00 0.00 1687188.56 0.237541E+09
                   
Annual Sum or Average 0.181198E+11 0.873897E+10 0.363660E+11 0.00 0.00 0.00 0.00 0.245627E+09 0.131295E+10
Minimum of Months 0.136988E+10 0.670979E+09 0.277013E+10 0.00 0.00 0.00 0.00 356308.80 5120516.14
Maximum of Months 0.163688E+10 0.786661E+09 0.318374E+10 0.00 0.00 0.00 0.00 47900868.02 0.263253E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.502623E+09 0.197183E+10 0.00 0.00 0.00 0.00 715051.75 0.158847E+09
February 0.882782E+09 0.443186E+09 0.178514E+10 0.00 0.00 0.00 0.00 995336.04 0.122405E+09
March 0.105485E+10 0.516866E+09 0.205168E+10 0.00 0.00 0.00 0.00 2973359.61 0.136040E+09
April 0.936002E+09 0.451709E+09 0.190406E+10 0.00 0.00 0.00 0.00 4917880.54 68937953.34
May 0.101394E+10 0.472943E+09 0.201175E+10 0.00 0.00 0.00 0.00 23872590.24 14047417.22
June 0.101113E+10 0.464039E+09 0.197570E+10 0.00 0.00 0.00 0.00 21242307.89 11380693.19
July 0.938820E+09 0.439215E+09 0.193968E+10 0.00 0.00 0.00 0.00 29647666.15 6002175.45
August 0.105485E+10 0.496010E+09 0.205168E+10 0.00 0.00 0.00 0.00 29061226.34 15672003.29
September 0.936002E+09 0.457883E+09 0.190319E+10 0.00 0.00 0.00 0.00 26137983.67 20771135.10
October 0.973041E+09 0.483189E+09 0.197226E+10 0.00 0.00 0.00 0.00 21482758.41 60003714.46
November 0.963541E+09 0.493150E+09 0.192888E+10 0.00 0.00 0.00 0.00 2889501.26 85453729.16
December 0.938820E+09 0.493522E+09 0.193924E+10 0.00 0.00 0.00 0.00 1830737.79 0.145835E+09
                   
Annual Sum or Average 0.116768E+11 0.571434E+10 0.234351E+11 0.00 0.00 0.00 0.00 0.165766E+09 0.845395E+09
Minimum of Months 0.882782E+09 0.439215E+09 0.178514E+10 0.00 0.00 0.00 0.00 715051.75 6002175.45
Maximum of Months 0.105485E+10 0.516866E+09 0.205168E+10 0.00 0.00 0.00 0.00 29647666.15 0.158847E+09



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.272315E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.247010E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.293517E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.262171E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.282916E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.281548E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.263538E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.293517E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.262171E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.272315E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.269124E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.263538E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.326368E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.247010E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.293517E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.272315E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.247010E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.293517E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.262171E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.282916E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.281548E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.263538E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.293517E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.262171E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.272315E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.269124E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.263538E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.326368E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.247010E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.293517E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.272315E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.247010E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.293517E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.262171E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.282916E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.281548E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.263538E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.293517E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.262171E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.272315E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.269124E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.263538E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.326368E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.247010E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.293517E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.318958E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.289319E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.343791E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.307076E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.331375E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.329773E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.308678E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.343791E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.307076E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.318958E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.315220E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.308678E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.382269E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.289319E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.343791E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 228981.42 0.204851E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 576831.85 0.159044E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2331892.01 0.163916E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5268527.72 69874845.23
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25180107.44 8048192.33
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23416036.55 6278006.72
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36071219.14 1485015.57
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32263772.28 8175653.25
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28485085.94 16067270.10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22118627.55 60464996.45
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1919733.59 0.106362E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1243533.30 0.186073E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.179104E+09 0.990639E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 228981.42 1485015.57
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36071219.14 0.204851E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1078630.74 0.336590E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1696941.30 0.262738E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5796991.34 0.272821E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10228412.39 0.119645E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 47449256.91 13391775.12
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 43013908.22 11368550.99
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 65661344.58 2919561.88
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58390722.92 15747181.85
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54382446.17 25564666.85
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41935999.56 0.101885E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4241380.48 0.177358E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2880022.42 0.303290E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.336756E+09 0.164332E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1078630.74 2919561.88
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 65661344.58 0.336590E+09



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 480835.76 0.335376E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 690595.47 0.261178E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3252810.40 0.286153E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6593671.56 0.135415E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40507566.19 18036153.53
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 38257652.29 14442583.20
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58217561.79 5075588.60
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54015105.52 20714562.62
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 49962531.62 31035333.77
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34321661.16 0.109687E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3098807.12 0.178332E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2384205.27 0.303738E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.291783E+09 0.169918E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 480835.76 5075588.60
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58217561.79 0.335376E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 11837.83 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 11837.83 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 11837.83 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 11837.83 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 11837.83 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 11837.83 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 11837.83 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 11837.83 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 11837.83 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 11837.83 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 11837.83 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 11837.83 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   11837.83   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   11837.83   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 10631.20 02-JAN-08:09 17206.63 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 10631.20 01-FEB-08:09 17206.63 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 10631.20 01-MAR-08:09 17206.63 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 10631.20 03-APR-07:10 17206.63 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 10631.20 01-MAY-07:10 17206.63 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 10631.20 01-JUN-07:10 17206.63 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 10631.20 03-JUL-07:10 17206.63 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 10631.20 01-AUG-07:10 17206.63 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 10631.20 01-SEP-07:10 17206.63 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 10631.20 02-OCT-07:10 17206.63 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 10631.20 01-NOV-07:10 17206.63 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 10631.20 01-DEC-08:09 17206.63 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   10631.20   17206.63   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   10631.20   17206.63   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 10631.20 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 10631.20 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 10631.20 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 10631.20 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 10631.20 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 10631.20 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 10631.20 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 10631.20 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 10631.20 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 10631.20 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 10631.20 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 10631.20 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   10631.20   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   10631.20   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 10631.20 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 10631.20 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 10631.20 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 10631.20 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 10631.20 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 10631.20 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 10631.20 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 10631.20 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 10631.20 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 10631.20 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 10631.20 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 10631.20 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   10631.20   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   10631.20   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1135.02 31-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 13.62 16-JAN-15:00 179.64 09-JAN-05:00
February 2010.79 01-FEB-10:09 1167.25 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 12.48 02-FEB-13:00 250.14 05-FEB-08:00
March 2010.79 01-MAR-10:09 1091.46 27-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 28.83 05-MAR-13:10 215.86 20-MAR-22:00
April 2010.79 03-APR-09:09 1115.86 14-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 42.23 29-APR-17:02 130.49 01-APR-21:00
May 2010.79 01-MAY-09:09 883.46 23-MAY-07:30 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 61.32 21-MAY-13:50 25.56 09-MAY-02:00
June 2010.79 01-JUN-09:09 689.07 27-JUN-11:30 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 70.80 10-JUN-17:02 40.18 06-JUN-21:50
July 2010.79 03-JUL-09:09 736.83 14-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 65.39 22-JUL-18:50 18.33 30-JUL-10:53
August 2010.79 01-AUG-09:09 911.01 21-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 84.98 20-AUG-14:00 40.11 26-AUG-00:10
September 2010.79 01-SEP-09:09 1088.83 26-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 86.82 09-SEP-22:57 48.41 05-SEP-03:00
October 2010.79 02-OCT-09:09 1214.09 25-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 105.52 09-OCT-13:50 105.97 29-OCT-02:00
November 2010.79 01-NOV-09:09 1174.17 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 18.10 05-NOV-13:00 152.51 12-NOV-08:00
December 2010.79 01-DEC-10:09 1205.45 12-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 17.21 10-DEC-14:50 232.12 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   689.07   2160.55   0.00 0.00 0.00 0.00 12.48   18.33  
Maximum of Months 2010.79   1214.09   2160.55   0.00 0.00 0.00 0.00 105.52   250.14  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 704.89 04-JAN-16:00 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 7.47 16-JAN-15:00 119.08 22-JAN-08:00
February 1295.83 01-FEB-10:09 729.41 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 8.32 02-FEB-13:00 175.13 05-FEB-10:00
March 1295.83 01-MAR-10:09 661.70 27-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 17.08 05-MAR-13:10 142.02 20-MAR-22:00
April 1295.83 03-APR-09:09 696.02 14-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 29.59 29-APR-17:50 83.83 01-APR-21:00
May 1295.83 01-MAY-09:09 560.96 30-MAY-15:30 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 44.48 21-MAY-13:50 17.24 14-MAY-12:10
June 1295.83 01-JUN-09:09 445.37 27-JUN-13:30 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 49.33 10-JUN-17:02 25.19 06-JUN-22:00
July 1295.83 03-JUL-09:09 451.48 14-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 45.78 22-JUL-18:50 17.05 30-JUL-10:53
August 1295.83 01-AUG-09:09 472.79 21-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 57.86 20-AUG-14:00 24.33 26-AUG-00:10
September 1295.83 01-SEP-09:09 658.09 26-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 59.37 09-SEP-22:53 32.22 05-SEP-03:00
October 1295.83 02-OCT-09:09 767.38 25-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 64.56 09-OCT-13:50 69.96 29-OCT-02:00
November 1295.83 01-NOV-09:09 764.09 21-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 11.36 05-NOV-13:00 114.12 12-NOV-08:10
December 1295.83 01-DEC-10:09 767.68 12-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 11.27 10-DEC-14:50 149.34 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   445.37   1392.34   0.00 0.00 0.00 0.00 7.47   17.05  
Maximum of Months 1295.83   767.68   1392.34   0.00 0.00 0.00 0.00 64.56   175.13  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1106.32 31-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 4.58 19-JAN-12:10 180.89 26-JAN-03:00
February 2010.83 01-FEB-10:09 1149.29 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 12.47 02-FEB-13:00 249.07 05-FEB-08:00
March 2010.83 01-MAR-10:09 1081.67 27-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 17.47 26-MAR-13:55 218.25 20-MAR-22:00
April 2010.83 03-APR-09:09 1119.68 14-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 37.50 29-APR-17:02 132.00 01-APR-21:00
May 2010.83 01-MAY-09:09 914.74 23-MAY-07:19 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 60.79 21-MAY-13:50 25.70 09-MAY-02:00
June 2010.83 01-JUN-09:09 719.77 16-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 72.65 10-JUN-17:02 39.67 06-JUN-21:50
July 2010.83 03-JUL-09:09 857.85 14-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 66.37 22-JUL-18:50 19.72 30-JUL-10:53
August 2010.83 01-AUG-09:09 946.49 21-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 83.48 20-AUG-14:00 41.09 26-AUG-00:10
September 2010.83 01-SEP-09:09 1085.88 26-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 83.62 09-SEP-22:57 51.46 05-SEP-03:00
October 2010.83 02-OCT-09:09 1206.62 25-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 85.40 09-OCT-13:55 110.92 29-OCT-02:00
November 2010.83 01-NOV-09:09 1144.87 21-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 9.43 07-NOV-13:00 166.39 12-NOV-08:10
December 2010.83 01-DEC-10:09 1194.94 12-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 9.07 13-DEC-14:00 226.90 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   719.77   2160.58   0.00 0.00 0.00 0.00 4.58   19.72  
Maximum of Months 2010.83   1206.62   2160.58   0.00 0.00 0.00 0.00 85.40   249.07  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 741.01 31-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 4.50 16-JAN-14:10 126.80 26-JAN-03:00
February 1295.83 01-FEB-10:09 758.17 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 8.32 02-FEB-13:00 177.29 05-FEB-08:00
March 1295.83 01-MAR-10:09 726.59 27-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 11.76 05-MAR-12:50 161.55 20-MAR-22:00
April 1295.83 03-APR-09:09 734.93 14-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 14.68 29-APR-17:07 108.48 01-APR-21:00
May 1295.83 01-MAY-09:09 637.06 24-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 40.78 21-MAY-13:50 23.14 09-MAY-02:00
June 1295.83 01-JUN-09:09 561.45 16-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 41.72 10-JUN-17:08 38.24 06-JUN-21:50
July 1295.83 03-JUL-09:09 603.04 14-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 39.74 02-JUL-11:50 19.11 31-JUL-02:20
August 1295.83 01-AUG-09:09 681.58 23-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 56.24 20-AUG-13:58 39.38 25-AUG-23:35
September 1295.83 01-SEP-09:09 727.14 26-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 53.68 09-SEP-23:00 37.91 13-SEP-03:00
October 1295.83 02-OCT-09:09 788.54 25-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 60.98 09-OCT-13:48 83.46 29-OCT-02:00
November 1295.83 01-NOV-09:09 771.05 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 6.51 11-NOV-12:30 112.81 12-NOV-08:00
December 1295.83 01-DEC-10:09 778.02 12-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 6.05 13-DEC-14:00 178.19 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   561.45   1392.33   0.00 0.00 0.00 0.00 4.50   19.11  
Maximum of Months 1295.83   788.54   1392.33   0.00 0.00 0.00 0.00 60.98   178.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1139.16 31-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 53.07 16-JAN-15:00 370.99 21-JAN-05:55
February 2010.79 01-FEB-10:09 1170.75 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 69.46 20-FEB-15:00 517.09 05-FEB-07:55
March 2010.79 01-MAR-10:09 1096.78 27-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 92.63 05-MAR-13:00 457.51 20-MAR-22:00
April 2010.79 03-APR-09:09 1120.56 14-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 108.72 29-APR-17:02 265.24 01-APR-21:00
May 2010.79 01-MAY-09:09 892.90 23-MAY-07:30 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 142.93 07-MAY-14:00 53.02 09-MAY-02:00
June 2010.79 01-JUN-09:09 684.55 27-JUN-11:30 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 168.68 10-JUN-17:02 83.18 06-JUN-21:50
July 2010.79 03-JUL-09:09 734.95 14-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 157.94 22-JUL-18:50 43.35 31-JUL-02:35
August 2010.79 01-AUG-09:09 920.22 21-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 206.88 20-AUG-14:00 117.29 25-AUG-23:53
September 2010.79 01-SEP-09:09 1094.11 26-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 198.41 09-SEP-22:53 114.00 05-SEP-02:53
October 2010.79 02-OCT-09:09 1216.67 25-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 262.51 09-OCT-13:52 211.79 29-OCT-02:00
November 2010.79 01-NOV-09:09 1177.57 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 57.52 11-NOV-13:10 323.53 12-NOV-08:00
December 2010.79 01-DEC-10:09 1208.17 12-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 54.12 10-DEC-15:00 463.70 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   684.55   2160.55   0.00 0.00 0.00 0.00 53.07   43.35  
Maximum of Months 2010.79   1216.67   2160.55   0.00 0.00 0.00 0.00 262.51   517.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 706.33 04-JAN-16:00 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 26.91 16-JAN-15:00 246.94 21-JAN-05:55
February 1239.33 01-FEB-08:09 730.25 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 38.80 20-FEB-15:00 369.14 05-FEB-10:00
March 1239.33 01-MAR-08:09 663.73 27-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 41.04 05-MAR-13:00 312.27 20-MAR-22:00
April 1239.33 03-APR-07:10 697.47 14-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 67.73 29-APR-17:02 184.38 01-APR-21:00
May 1239.33 01-MAY-07:10 559.82 30-MAY-15:30 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 96.08 21-MAY-13:37 45.90 14-MAY-12:10
June 1239.33 01-JUN-07:10 442.08 27-JUN-13:30 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 114.55 10-JUN-17:02 56.25 06-JUN-22:00
July 1239.33 03-JUL-07:10 449.98 14-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 104.52 22-JUL-18:50 56.99 30-JUL-11:00
August 1239.33 01-AUG-07:10 471.62 21-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 134.00 20-AUG-14:00 80.65 25-AUG-23:53
September 1239.33 01-SEP-07:10 660.42 26-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 133.30 09-SEP-22:53 82.08 05-SEP-02:53
October 1239.33 02-OCT-07:10 768.03 25-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 142.20 09-OCT-13:50 146.86 29-OCT-02:00
November 1239.33 01-NOV-07:10 764.31 21-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 27.96 05-NOV-13:00 253.44 12-NOV-08:40
December 1239.33 01-DEC-08:09 768.09 12-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 28.79 10-DEC-15:00 311.03 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   442.08   1392.34   0.00 0.00 0.00 0.00 26.91   45.90  
Maximum of Months 1239.33   768.09   1392.34   0.00 0.00 0.00 0.00 142.20   369.14  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1111.44 31-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 9.51 19-JAN-12:10 404.48 26-JAN-03:00
February 2010.83 01-FEB-10:09 1153.40 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 28.52 02-FEB-13:00 551.95 05-FEB-08:00
March 2010.83 01-MAR-10:09 1087.32 27-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 38.08 26-MAR-13:53 481.77 20-MAR-22:00
April 2010.83 03-APR-09:09 1124.26 14-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 92.67 29-APR-17:02 286.01 01-APR-21:00
May 2010.83 01-MAY-09:09 923.25 23-MAY-07:19 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 135.23 21-MAY-13:37 55.06 09-MAY-02:00
June 2010.83 01-JUN-09:09 717.43 16-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 173.22 10-JUN-17:02 83.48 06-JUN-21:50
July 2010.83 03-JUL-09:09 867.36 14-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 161.04 22-JUL-18:50 45.11 31-JUL-02:35
August 2010.83 01-AUG-09:09 954.53 21-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 194.38 20-AUG-14:00 121.00 25-AUG-23:53
September 2010.83 01-SEP-09:09 1091.25 26-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 187.40 09-SEP-22:53 126.28 05-SEP-02:53
October 2010.83 02-OCT-09:09 1209.46 25-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 187.72 09-OCT-13:48 249.81 29-OCT-02:00
November 2010.83 01-NOV-09:09 1149.40 21-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 20.23 07-NOV-13:00 376.32 12-NOV-11:00
December 2010.83 01-DEC-10:09 1198.05 12-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 20.82 13-DEC-14:00 488.28 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   717.43   2160.58   0.00 0.00 0.00 0.00 9.51   45.11  
Maximum of Months 2010.83   1209.46   2160.58   0.00 0.00 0.00 0.00 194.38   551.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 741.26 31-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 19.69 16-JAN-13:40 256.23 26-JAN-03:00
February 1295.83 01-FEB-10:09 758.38 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 19.02 02-FEB-13:00 355.52 05-FEB-07:55
March 1295.83 01-MAR-10:09 726.84 27-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 51.73 05-MAR-12:40 325.99 20-MAR-22:00
April 1295.83 03-APR-09:09 735.16 14-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 36.48 29-APR-17:07 203.75 01-APR-17:53
May 1295.83 01-MAY-09:09 637.17 24-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 94.80 21-MAY-13:33 51.53 06-MAY-19:53
June 1295.83 01-JUN-09:09 561.61 16-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 95.52 10-JUN-17:08 67.73 06-JUN-21:50
July 1295.83 03-JUL-09:09 603.49 14-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 90.72 16-JUL-13:00 44.49 31-JUL-01:55
August 1295.83 01-AUG-09:09 682.14 23-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 136.29 20-AUG-14:00 90.54 25-AUG-23:53
September 1295.83 01-SEP-09:09 727.39 26-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 119.16 09-SEP-22:43 88.25 05-SEP-02:53
October 1295.83 02-OCT-09:09 788.68 25-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 154.82 09-OCT-12:10 161.93 29-OCT-02:00
November 1295.83 01-NOV-09:09 771.27 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 34.71 11-NOV-12:30 229.64 12-NOV-07:05
December 1295.83 01-DEC-10:09 778.20 12-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 28.68 10-DEC-11:20 323.58 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   561.61   1392.33   0.00 0.00 0.00 0.00 19.02   44.49  
Maximum of Months 1295.83   788.68   1392.33   0.00 0.00 0.00 0.00 154.82   355.52  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1138.96 31-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 68.94 15-JAN-14:10 447.75 21-JAN-06:00
February 2010.79 01-FEB-10:09 1170.56 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 73.48 20-FEB-15:10 572.46 05-FEB-08:00
March 2010.79 01-MAR-10:09 1096.55 27-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 114.66 05-MAR-12:50 538.88 20-MAR-22:00
April 2010.79 03-APR-09:09 1120.34 14-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 116.56 29-APR-17:02 314.74 01-APR-21:00
May 2010.79 01-MAY-09:09 892.46 23-MAY-07:30 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 161.00 07-MAY-14:00 72.00 09-MAY-02:00
June 2010.79 01-JUN-09:09 684.39 27-JUN-11:30 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 191.10 10-JUN-17:02 108.31 06-JUN-21:50
July 2010.79 03-JUL-09:09 734.80 14-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 164.72 22-JUL-18:50 65.73 30-JUL-11:00
August 2010.79 01-AUG-09:09 919.88 21-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 239.41 20-AUG-14:00 145.19 25-AUG-23:53
September 2010.79 01-SEP-09:09 1093.89 26-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 241.33 09-SEP-22:57 152.86 05-SEP-02:53
October 2010.79 02-OCT-09:09 1216.54 25-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 290.09 09-OCT-13:43 227.29 29-OCT-02:00
November 2010.79 01-NOV-09:09 1177.44 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 75.30 05-NOV-13:00 381.90 12-NOV-07:00
December 2010.79 01-DEC-10:09 1208.02 12-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 64.49 10-DEC-10:53 500.36 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   684.39   2160.55   0.00 0.00 0.00 0.00 64.49   65.73  
Maximum of Months 2010.79   1216.54   2160.55   0.00 0.00 0.00 0.00 290.09   572.46  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 706.46 04-JAN-16:00 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 34.83 16-JAN-15:00 298.51 21-JAN-05:55
February 1295.83 01-FEB-10:09 730.15 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 39.03 20-FEB-15:10 383.75 05-FEB-08:00
March 1295.83 01-MAR-10:09 663.61 27-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 52.74 05-MAR-13:10 371.58 20-MAR-22:00
April 1295.83 03-APR-09:09 697.34 14-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 70.97 29-APR-17:02 221.19 01-APR-21:00
May 1295.83 01-MAY-09:09 559.68 30-MAY-15:30 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 110.41 21-MAY-13:33 56.02 14-MAY-12:00
June 1295.83 01-JUN-09:09 442.00 27-JUN-13:30 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 129.69 10-JUN-17:02 74.92 18-JUN-13:55
July 1295.83 03-JUL-09:09 449.85 14-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 108.03 22-JUL-18:50 79.72 30-JUL-11:00
August 1295.83 01-AUG-09:09 471.53 21-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 167.93 20-AUG-14:00 100.12 25-AUG-23:53
September 1295.83 01-SEP-09:09 660.31 26-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 163.50 09-SEP-22:53 108.40 05-SEP-02:53
October 1295.83 02-OCT-09:09 767.96 25-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 173.43 09-OCT-14:10 159.15 29-OCT-02:00
November 1295.83 01-NOV-09:09 764.21 21-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 37.10 05-NOV-13:00 297.44 12-NOV-08:40
December 1295.83 01-DEC-10:09 768.00 12-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 32.31 10-DEC-15:10 336.93 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   442.00   1392.34   0.00 0.00 0.00 0.00 32.31   56.02  
Maximum of Months 1295.83   768.00   1392.34   0.00 0.00 0.00 0.00 173.43   383.75  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1111.23 31-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 11.77 19-JAN-12:00 470.74 22-JAN-16:55
February 2010.83 01-FEB-10:09 1153.22 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 34.48 02-FEB-13:00 573.99 04-FEB-20:00
March 2010.83 01-MAR-10:09 1087.10 27-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 43.27 26-MAR-13:45 574.00 20-MAR-22:00
April 2010.83 03-APR-09:09 1124.03 14-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 97.19 29-APR-17:02 346.90 01-APR-17:53
May 2010.83 01-MAY-09:09 922.83 23-MAY-07:19 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 153.61 21-MAY-13:33 74.63 09-MAY-02:00
June 2010.83 01-JUN-09:09 717.27 16-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 196.38 10-JUN-17:02 109.13 06-JUN-21:50
July 2010.83 03-JUL-09:09 866.95 14-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 168.52 22-JUL-18:50 68.15 30-JUL-11:00
August 2010.83 01-AUG-09:09 954.20 21-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 240.62 20-AUG-14:00 150.01 25-AUG-23:53
September 2010.83 01-SEP-09:09 1091.03 26-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 227.56 09-SEP-22:57 166.81 05-SEP-02:53
October 2010.83 02-OCT-09:09 1209.33 25-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 227.01 09-OCT-13:48 279.71 29-OCT-02:00
November 2010.83 01-NOV-09:09 1149.24 21-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 26.36 07-NOV-13:00 440.12 12-NOV-08:00
December 2010.83 01-DEC-10:09 1197.90 12-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 25.27 13-DEC-14:00 523.94 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   717.27   2160.58   0.00 0.00 0.00 0.00 11.77   68.15  
Maximum of Months 2010.83   1209.33   2160.58   0.00 0.00 0.00 0.00 240.62   574.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 741.13 31-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 27.35 16-JAN-13:20 298.51 21-JAN-06:00
February 1295.83 01-FEB-10:09 758.27 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 25.78 26-FEB-13:32 381.65 05-FEB-07:55
March 1295.83 01-MAR-10:09 726.71 27-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 64.37 05-MAR-13:10 387.93 20-MAR-22:00
April 1295.83 03-APR-09:09 735.02 14-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 43.26 29-APR-17:07 248.59 01-APR-17:53
May 1295.83 01-MAY-09:09 637.02 24-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 110.74 21-MAY-13:33 62.44 06-MAY-20:00
June 1295.83 01-JUN-09:09 561.42 16-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 116.69 10-JUN-17:08 87.40 06-JUN-21:50
July 1295.83 03-JUL-09:09 603.25 14-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 112.57 02-JUL-12:00 54.52 31-JUL-02:10
August 1295.83 01-AUG-09:09 682.08 23-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 165.66 20-AUG-14:00 112.50 25-AUG-23:53
September 1295.83 01-SEP-09:09 727.25 26-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 150.09 09-SEP-23:00 113.80 05-SEP-02:53
October 1295.83 02-OCT-09:09 788.60 25-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 187.96 09-OCT-12:10 181.54 29-OCT-02:00
November 1295.83 01-NOV-09:09 771.19 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 42.21 05-NOV-13:00 273.37 12-NOV-07:00
December 1295.83 01-DEC-10:09 778.10 12-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 35.50 10-DEC-11:10 358.98 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   561.42   1392.33   0.00 0.00 0.00 0.00 25.78   54.52  
Maximum of Months 1295.83   788.60   1392.33   0.00 0.00 0.00 0.00 187.96   387.93  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 284.97 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 284.97 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 284.97 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 284.97 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 284.97 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 284.97 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 284.97 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 284.97 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 284.97 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 284.97 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 284.97 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 284.97 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   284.97   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   284.97   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 284.97 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 284.97 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 284.97 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 284.97 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 284.97 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 284.97 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 284.97 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 284.97 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 284.97 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 284.97 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 284.97 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 284.97 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   284.97   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   284.97   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 284.97 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 284.97 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 284.97 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 284.97 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 284.97 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 284.97 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 284.97 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 284.97 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 284.97 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 284.97 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 284.97 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 284.97 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   284.97   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   284.97   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 3337.76 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 3337.76 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 3337.76 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 3337.76 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 3337.76 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 3337.76 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 3337.76 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 3337.76 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 3337.76 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 3337.76 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 3337.76 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 3337.76 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   3337.76   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   3337.76   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.52 16-JAN-15:00 382.30 09-JAN-05:04
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.25 02-FEB-13:00 549.23 05-FEB-07:55
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50.65 26-MAR-14:00 464.93 20-MAR-22:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 78.55 29-APR-17:02 269.41 01-APR-21:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 128.36 21-MAY-13:53 40.71 09-MAY-02:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 148.88 10-JUN-17:02 69.58 06-JUN-21:50
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 132.05 22-JUL-18:53 26.41 31-JUL-03:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 177.77 20-AUG-14:00 97.10 25-AUG-23:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 166.70 09-SEP-17:02 89.66 05-SEP-03:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 199.38 09-OCT-14:00 228.08 29-OCT-02:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.28 05-NOV-13:00 320.83 12-NOV-08:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.25 10-DEC-15:00 508.61 20-DEC-01:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.52   26.41  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 199.38   549.23  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.96 16-JAN-15:00 657.51 21-JAN-05:55
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 59.51 20-FEB-15:00 948.31 05-FEB-07:55
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 109.98 05-MAR-13:00 801.51 20-MAR-22:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 156.36 29-APR-17:02 451.65 01-APR-21:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 227.43 21-MAY-13:53 64.36 09-MAY-02:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 276.84 10-JUN-17:02 116.94 06-JUN-21:50
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 255.50 22-JUL-18:53 48.92 31-JUL-03:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 331.64 20-AUG-14:00 184.04 25-AUG-23:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 308.74 09-SEP-17:02 149.24 05-SEP-03:04
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 385.68 09-OCT-13:52 384.94 29-OCT-02:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 59.25 05-NOV-13:00 554.60 12-NOV-08:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 60.45 10-DEC-15:00 864.27 20-DEC-01:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.96   48.92  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 385.68   948.31  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.66 16-JAN-15:00 655.98 21-JAN-05:55
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34.29 02-FEB-13:00 870.52 05-FEB-07:55
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 84.07 26-MAR-13:53 844.02 20-MAR-22:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 112.13 29-APR-17:02 493.72 01-APR-17:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 191.22 07-MAY-14:00 128.13 14-MAY-11:55
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 254.33 10-JUN-17:02 127.02 07-JUN-01:40
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 200.92 02-JUL-10:53 122.84 30-JUL-11:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312.10 20-AUG-14:00 204.03 25-AUG-23:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 349.32 09-SEP-23:00 199.30 05-SEP-03:04
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 295.43 09-OCT-13:52 359.29 29-OCT-02:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 49.89 05-NOV-13:00 579.82 12-NOV-07:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 44.49 10-DEC-14:52 802.05 20-DEC-01:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34.29   122.84  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 349.32   870.52  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 100714.27 09-JAN-04:12 0.00 3288.60 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
February 100289.71 13-FEB-04:03 0.00 2630.88 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
March 98286.81 20-MAR-03:02 0.00 2630.88 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
April 96806.33 10-APR-03:02 0.00 3288.60 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
May 71226.47 30-MAY-03:02 0.00 3288.60 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
June 74281.70 07-JUN-03:02 0.00 3288.60 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
July 71744.94 05-JUL-03:02 0.00 3288.60 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
August 75370.86 28-AUG-03:02 0.00 3288.60 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
September 78567.97 05-SEP-02:13 0.00 2630.88 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
October 88874.08 28-OCT-05:03 7180.90 5261.11 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
November 97038.41 24-NOV-04:03 0.00 2630.88 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
December 99135.99 04-DEC-04:03 0.00 2630.88 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 71226.47   0.00 2630.88 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 100714.27   7180.90 5261.11 67287.72 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 83572.81 02-JAN-04:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
February 80586.93 21-FEB-04:03 0.00 2362.72 23750.58 0.00 0.00 0.00 0.00 0.00 0.00
March 81033.29 20-MAR-03:02 0.00 2362.72 23750.58 0.00 0.00 0.00 0.00 0.00 0.00
April 79016.52 10-APR-03:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
May 76261.15 09-MAY-03:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
June 74077.96 07-JUN-03:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
July 67027.64 12-JUL-05:02 8061.19 5906.06 38236.95 0.00 0.00 0.00 0.00 0.00 0.00
August 66853.99 01-AUG-05:02 8061.19 5906.06 38236.95 0.00 0.00 0.00 0.00 0.00 0.00
September 78029.09 20-SEP-03:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
October 80965.90 30-OCT-03:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
November 84093.15 13-NOV-04:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
December 83730.07 26-DEC-04:02 0.00 2953.40 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 66853.99   0.00 2362.72 23750.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 84093.15   8061.19 5906.06 38236.95 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 70706.70 20-JAN-06:04 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
February 68997.04 24-FEB-06:03 6448.95 4724.85 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
March 71616.10 28-MAR-05:04 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
April 73372.89 14-APR-05:04 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
May 69064.57 23-MAY-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
June 70862.51 07-JUN-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
July 69581.97 12-JUL-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
August 70282.77 17-AUG-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
September 70017.20 08-SEP-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
October 71165.85 17-OCT-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
November 73022.89 01-NOV-05:04 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
December 72726.97 12-DEC-06:04 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 68997.04   0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 73372.89   8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 66898.55 20-JAN-06:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
February 66210.95 03-FEB-06:03 6448.95 4724.85 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
March 68196.05 28-MAR-05:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
April 70472.24 06-APR-05:04 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
May 69727.37 23-MAY-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
June 69990.53 30-JUN-03:02 0.00 2953.40 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
July 70094.66 12-JUL-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
August 69113.62 01-AUG-04:03 0.00 4724.85 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
September 73289.84 08-SEP-05:04 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
October 71681.92 17-OCT-05:04 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
November 72393.33 04-NOV-05:04 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
December 66272.70 12-DEC-06:02 8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 66210.95   0.00 2953.40 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 73289.84   8061.19 5906.06 38236.81 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9695.97 31-JAN-06:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 7.17
February 6310.69 22-FEB-14:30 2010.79 635.12 2160.55 0.00 0.00 0.00 0.00 1.38 0.00
March 8134.79 27-MAR-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 5.57
April 10389.85 24-APR-05:02 1214.60 889.88 5761.47 0.00 0.00 0.00 0.00 0.00 0.30
May 11405.88 31-MAY-03:02 0.00 370.83 3727.80 0.00 0.00 0.00 0.00 0.00 0.00
June 11614.97 25-JUN-15:52 607.30 211.73 4321.10 0.00 0.00 0.00 0.00 10.59 0.00
July 12672.33 03-JUL-05:03 1214.60 889.88 5761.47 0.00 0.00 0.00 0.00 2.91 0.00
August 12485.70 14-AUG-05:03 1214.60 889.88 5761.47 0.00 0.00 0.00 0.00 1.87 0.00
September 10850.99 05-SEP-05:03 809.73 593.25 3840.98 0.00 0.00 0.00 0.00 0.00 4.36
October 10849.70 07-OCT-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 1.30 0.00
November 9719.95 02-NOV-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 0.44
December 10690.56 11-DEC-06:02 1214.60 889.88 5761.47 0.00 0.00 0.00 0.00 0.00 3.94
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6310.69   0.00 211.73 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12672.33   2010.79 889.88 5761.47 0.00 0.00 0.00 0.00 10.59 7.17



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9858.53 01-JAN-10:13 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 28.87
February 7069.83 27-FEB-10:10 1295.83 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 0.81
March 10041.24 26-MAR-09:02 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 6.77
April 12772.77 23-APR-11:02 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 0.10
May 16209.80 29-MAY-08:62 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 0.00 2.41
June 15406.75 11-JUN-08:53 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 4.69 0.00
July 15552.00 23-JUL-09:53 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 0.00
August 13743.76 06-AUG-10:02 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 9.02 0.00
September 15616.42 24-SEP-09:23 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 4.35 0.00
October 15460.95 09-OCT-09:02 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 2.88 0.00
November 8703.35 11-NOV-09:03 195.68 68.22 1392.34 0.00 0.00 0.00 0.00 0.00 6.96
December 5271.38 16-DEC-09:40 391.37 136.43 773.52 0.00 0.00 0.00 0.00 0.00 0.59
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5271.38   195.68 68.22 773.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16209.80   1295.83 409.30 2320.57 0.00 0.00 0.00 0.00 9.02 28.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 20113.83 01-JAN-13:32 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 0.00 10.10
February 18596.69 26-FEB-13:23 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 5.71
March 17722.26 26-MAR-14:23 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 0.27
April 12887.73 28-APR-05:02 1214.62 889.90 5761.56 0.00 0.00 0.00 0.00 0.00 0.68
May 13168.16 22-MAY-05:03 809.75 593.26 3841.04 0.00 0.00 0.00 0.00 5.62 0.00
June 13287.56 29-JUN-05:02 1012.19 741.58 4801.30 0.00 0.00 0.00 0.00 0.08 0.00
July 13792.04 24-JUL-05:03 809.75 593.26 3841.04 0.00 0.00 0.00 0.00 0.74 0.00
August 13999.37 06-AUG-13:23 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 20.75 0.00
September 18412.61 10-SEP-13:02 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 37.14 0.00
October 19006.38 15-OCT-13:32 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 15.76 0.00
November 18597.68 11-NOV-11:02 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 7.60
December 19287.60 17-DEC-13:12 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 0.00 91.11
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12887.73   404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20113.83   1214.62 889.90 5761.56 0.00 0.00 0.00 0.00 37.14 91.11



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19622.35 01-JAN-16:12 326.14 113.70 2320.55 0.00 0.00 0.00 0.00 0.00 3.54
February 20630.06 26-FEB-16:42 326.14 113.70 2320.55 0.00 0.00 0.00 0.00 0.00 9.00
March 18351.83 26-MAR-14:23 260.91 90.96 1856.44 0.00 0.00 0.00 0.00 0.25 0.00
April 20561.43 23-APR-18:22 0.00 156.39 1801.74 0.00 0.00 0.00 0.00 0.00 15.93
May 21173.29 28-MAY-15:52 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 17.83 0.00
June 21304.75 25-JUN-15:52 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 5.37 0.00
July 20414.04 02-JUL-15:42 326.14 113.70 2320.55 0.00 0.00 0.00 0.00 8.15 0.00
August 20487.62 20-AUG-17:12 0.00 113.70 1801.74 0.00 0.00 0.00 0.00 13.46 0.00
September 20567.05 24-SEP-16:02 326.14 113.70 2320.55 0.00 0.00 0.00 0.00 11.42 0.00
October 20600.01 09-OCT-16:22 326.14 113.70 2320.55 0.00 0.00 0.00 0.00 4.27 0.00
November 19237.04 05-NOV-14:43 260.91 90.96 1856.44 0.00 0.00 0.00 0.00 0.51 0.00
December 20531.51 10-DEC-16:42 326.14 113.70 2320.55 0.00 0.00 0.00 0.00 0.00 8.02
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 18351.83   0.00 90.96 1801.74 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21304.75   391.37 156.39 2784.67 0.00 0.00 0.00 0.00 17.83 15.93



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4101.53 02-JAN-13:30 1923.11 635.12 2160.55 0.00 0.00 0.00 0.00 4.05 0.00
February 4685.17 28-FEB-15:00 2010.79 635.12 2160.55 0.00 0.00 0.00 0.00 6.15 0.00
March 7573.57 28-MAR-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 15.84
April 9202.47 14-APR-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 7.28
May 11756.53 26-MAY-03:02 0.00 370.83 3727.80 0.00 0.00 0.00 0.00 0.00 2.45
June 11867.13 28-JUN-03:02 0.00 370.83 3727.80 0.00 0.00 0.00 0.00 7.38 0.00
July 11875.67 10-JUL-03:02 0.00 370.83 3727.80 0.00 0.00 0.00 0.00 0.00 0.91
August 11933.78 14-AUG-03:02 0.00 370.83 3727.80 0.00 0.00 0.00 0.00 4.13 0.00
September 10365.35 11-SEP-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 2.46 0.00
October 11093.14 06-OCT-03:02 0.00 370.83 3727.80 0.00 0.00 0.00 0.00 13.85 0.00
November 9281.79 01-NOV-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 2.93
December 8490.26 12-DEC-06:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 11.35
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4101.53   0.00 370.83 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11933.78   2010.79 741.56 4801.23 0.00 0.00 0.00 0.00 13.85 15.84



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5689.03 19-JAN-10:00 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 3.96
February 6071.84 27-FEB-10:00 1239.33 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 1.06
March 8225.52 26-MAR-09:53 195.68 68.22 1392.34 0.00 0.00 0.00 0.00 0.00 13.43
April 15659.31 23-APR-11:02 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 1.16
May 16771.03 29-MAY-09:32 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 1.80 0.00
June 15931.27 11-JUN-08:53 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 7.24 0.00
July 15960.63 16-JUL-08:32 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 14.62 0.00
August 15688.00 27-AUG-10:23 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 25.04 0.00
September 16589.43 03-SEP-09:42 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 13.72 0.00
October 15872.94 09-OCT-09:23 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 18.87 0.00
November 9410.98 01-NOV-05:02 652.28 477.89 3094.09 0.00 0.00 0.00 0.00 0.00 1.73
December 5466.50 12-DEC-06:02 652.28 477.89 3094.09 0.00 0.00 0.00 0.00 0.00 7.57
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5466.50   195.68 68.22 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16771.03   1239.33 477.89 3094.09 0.00 0.00 0.00 0.00 25.04 13.43



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 17503.37 16-JAN-14:32 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 12.32
February 17547.73 26-FEB-13:32 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 16.40
March 15073.98 05-MAR-12:53 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 18.40 0.00
April 11532.35 29-APR-05:03 809.75 593.26 3841.04 0.00 0.00 0.00 0.00 0.00 3.46
May 13091.64 22-MAY-03:02 0.00 370.84 3727.86 0.00 0.00 0.00 0.00 0.00 0.25
June 12925.19 14-JUN-05:02 1012.19 741.58 4801.30 0.00 0.00 0.00 0.00 0.72 0.00
July 14365.02 20-JUL-03:02 0.00 370.84 3727.86 0.00 0.00 0.00 0.00 3.83 0.00
August 14830.63 14-AUG-03:02 0.00 370.84 3727.86 0.00 0.00 0.00 0.00 4.49 0.00
September 17093.21 03-SEP-14:22 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 59.85 0.00
October 18135.31 08-OCT-13:42 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 120.46 0.00
November 17435.09 05-NOV-14:43 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 2.77
December 18762.01 10-DEC-14:32 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 0.00 13.18
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11532.35   0.00 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18762.01   1012.19 741.58 4801.30 0.00 0.00 0.00 0.00 120.46 16.40



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7660.06 20-JAN-06:02 652.28 477.89 3094.07 0.00 0.00 0.00 0.00 0.00 13.73
February 8803.27 27-FEB-16:30 1239.33 409.30 1392.33 0.00 0.00 0.00 0.00 2.08 0.00
March 12145.99 06-MAR-06:02 652.28 477.89 3094.07 0.00 0.00 0.00 0.00 0.00 17.33
April 16471.49 16-APR-16:31 456.59 159.19 3248.78 0.00 0.00 0.00 0.00 0.00 102.87
May 16955.44 28-MAY-18:02 0.00 113.70 1801.74 0.00 0.00 0.00 0.00 6.99 0.00
June 16685.65 11-JUN-16:52 326.14 113.70 2320.55 0.00 0.00 0.00 0.00 34.76 0.00
July 17308.33 16-JUL-16:32 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 31.35 0.00
August 16274.02 20-AUG-17:12 0.00 113.70 1801.74 0.00 0.00 0.00 0.00 38.56 0.00
September 17680.34 03-SEP-15:42 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 48.91 0.00
October 17003.90 08-OCT-16:22 326.14 113.70 2320.55 0.00 0.00 0.00 0.00 56.73 0.00
November 11607.15 01-NOV-05:02 652.28 477.89 3094.07 0.00 0.00 0.00 0.00 0.00 2.05
December 11459.06 13-DEC-06:02 652.28 477.89 3094.07 0.00 0.00 0.00 0.00 0.00 14.83
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7660.06   0.00 113.70 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17680.34   1239.33 477.89 3248.78 0.00 0.00 0.00 0.00 56.73 102.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4399.37 31-JAN-16:00 1923.11 664.70 2160.55 0.00 0.00 0.00 0.00 6.30 0.00
February 5061.33 28-FEB-15:00 2010.79 635.12 2160.55 0.00 0.00 0.00 0.00 6.70 0.00
March 6376.07 30-MAR-13:30 2010.79 635.12 2160.55 0.00 0.00 0.00 0.00 15.24 0.00
April 10663.02 27-APR-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 2.23
May 12722.48 22-MAY-03:02 0.00 370.83 3727.80 0.00 0.00 0.00 0.00 0.00 12.24
June 13452.12 17-JUN-03:02 0.00 370.83 2795.85 0.00 0.00 0.00 0.00 0.00 1.75
July 15086.01 23-JUL-14:22 506.08 176.44 3600.92 0.00 0.00 0.00 0.00 89.41 0.00
August 13663.98 28-AUG-03:02 0.00 370.83 3727.80 0.00 0.00 0.00 0.00 4.59 0.00
September 15398.21 10-SEP-14:52 607.30 211.73 4321.10 0.00 0.00 0.00 0.00 77.68 0.00
October 11896.43 07-OCT-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 3.64 0.00
November 11002.68 02-NOV-05:02 1012.16 741.56 4801.23 0.00 0.00 0.00 0.00 0.00 1.97
December 5692.43 15-DEC-15:00 2010.79 679.27 2160.55 0.00 0.00 0.00 0.00 16.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4399.37   0.00 176.44 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15398.21   2010.79 741.56 4801.23 0.00 0.00 0.00 0.00 89.41 12.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5351.09 19-JAN-10:30 1295.83 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 1.62
February 5816.94 27-FEB-10:30 1295.83 409.30 1392.34 0.00 0.00 0.00 0.00 0.00 4.16
March 8838.24 27-MAR-05:02 652.28 477.89 3094.09 0.00 0.00 0.00 0.00 0.00 11.50
April 16072.78 23-APR-11:02 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 0.00 2.14
May 17053.15 29-MAY-10:42 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 11.81 0.00
June 16293.50 11-JUN-08:53 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 6.81 0.00
July 16360.45 16-JUL-08:32 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 15.89 0.00
August 16198.98 27-AUG-10:23 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 28.35 0.00
September 17013.45 03-SEP-09:42 326.14 113.70 2320.57 0.00 0.00 0.00 0.00 15.60 0.00
October 16224.40 09-OCT-09:23 260.91 90.96 1856.46 0.00 0.00 0.00 0.00 19.87 0.00
November 8041.49 01-NOV-05:02 652.28 477.89 3094.09 0.00 0.00 0.00 0.00 0.00 2.19
December 4437.97 16-DEC-10:10 409.21 136.43 773.52 0.00 0.00 0.00 0.00 0.28 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4437.97   260.91 90.96 773.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17053.15   1295.83 477.89 3094.09 0.00 0.00 0.00 0.00 28.35 11.50



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 21147.29 01-JAN-14:12 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 0.00 29.79
February 19418.74 26-FEB-14:43 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 24.36
March 13941.69 27-MAR-05:02 1012.19 741.58 4801.30 0.00 0.00 0.00 0.00 0.00 18.65
April 12994.91 27-APR-05:02 1012.19 741.58 4801.30 0.00 0.00 0.00 0.00 0.00 2.28
May 15235.59 22-MAY-03:02 0.00 370.84 3727.86 0.00 0.00 0.00 0.00 0.00 7.94
June 14622.82 28-JUN-03:02 0.00 370.84 3727.86 0.00 0.00 0.00 0.00 8.54 0.00
July 18069.91 23-JUL-14:22 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 91.62 0.00
August 18282.07 27-AUG-14:23 404.87 141.16 2880.78 0.00 0.00 0.00 0.00 102.85 0.00
September 20007.72 10-SEP-14:52 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 67.56 0.00
October 20048.82 08-OCT-12:12 506.09 176.44 3600.97 0.00 0.00 0.00 0.00 97.94 0.00
November 20748.64 11-NOV-14:12 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 0.00 52.38
December 21032.54 10-DEC-14:22 607.31 211.73 4321.17 0.00 0.00 0.00 0.00 0.00 20.19
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12994.91   0.00 141.16 2880.78 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21147.29   1012.19 741.58 4801.30 0.00 0.00 0.00 0.00 102.85 52.38



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 10097.47 01-JAN-16:12 326.14 113.70 2320.55 0.00 0.00 0.00 0.00 0.00 10.50
February 17831.90 26-FEB-17:22 326.14 113.70 2320.55 0.00 0.00 0.00 0.00 0.00 26.02
March 13117.07 27-MAR-05:02 652.28 477.89 3094.07 0.00 0.00 0.00 0.00 0.00 11.79
April 18107.17 23-APR-18:22 0.00 159.35 1801.74 0.00 0.00 0.00 0.00 0.00 43.70
May 18614.29 28-MAY-18:02 0.00 113.70 1801.74 0.00 0.00 0.00 0.00 6.68 0.00
June 18260.81 11-JUN-16:52 326.14 113.70 2320.55 0.00 0.00 0.00 0.00 41.34 0.00
July 18918.36 16-JUL-16:32 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 31.51 0.00
August 17637.21 20-AUG-17:12 0.00 113.70 1801.74 0.00 0.00 0.00 0.00 43.34 0.00
September 19456.13 03-SEP-15:42 391.37 136.45 2784.67 0.00 0.00 0.00 0.00 54.70 0.00
October 17846.73 08-OCT-15:32 326.14 113.70 2320.55 0.00 0.00 0.00 0.00 102.94 0.00
November 14175.15 11-NOV-15:32 326.14 113.70 2320.55 0.00 0.00 0.00 0.00 0.00 8.05
December 10072.51 16-DEC-06:03 521.82 382.31 2475.26 0.00 0.00 0.00 0.00 0.00 8.28
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10072.51   0.00 113.70 1801.74 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19456.13   652.28 477.89 3094.07 0.00 0.00 0.00 0.00 102.94 43.70



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9123.69 02-JAN-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.44
February 5597.63 27-FEB-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.75 0.00
March 5665.60 20-MAR-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 49.79
April 5663.22 28-APR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.00 0.00
May 6781.63 06-MAY-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.63
June 6222.78 12-JUN-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.23 0.00
July 7782.23 18-JUL-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.07
August 8805.89 21-AUG-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.90 0.00
September 9008.33 25-SEP-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.28
October 7868.42 10-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.11
November 7269.09 13-NOV-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.08
December 6873.35 26-DEC-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 68.57
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 5597.63   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9123.69   0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.00 68.57



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4659.35 03-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 88.55
February 4360.03 06-FEB-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50.64
March 4209.89 28-MAR-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27.27
April 4540.78 28-APR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.25 0.00
May 6761.25 06-MAY-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.11
June 7613.32 23-JUN-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.60 0.00
July 6675.34 25-JUL-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.39
August 6607.73 18-AUG-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.99
September 5691.80 13-SEP-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.76
October 7132.44 13-OCT-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.60
November 4410.80 09-NOV-06:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 122.40
December 4959.70 21-DEC-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 99.27
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4209.89   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7613.32   0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.25 122.40



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8359.51 19-JAN-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.10
February 10007.26 27-FEB-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.09
March 10189.35 06-MAR-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.43 0.00
April 15124.74 28-APR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54.08 0.00
May 16201.75 10-MAY-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.01 0.00
June 17189.81 28-JUN-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 37.46 0.00
July 17371.23 07-JUL-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31.20 0.00
August 16420.89 03-AUG-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 74.56 0.00
September 15263.81 01-SEP-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27.93 0.00
October 15121.61 05-OCT-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.13 0.00
November 11847.76 02-NOV-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.17 0.00
December 9922.92 15-DEC-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.91 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 8359.51   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17371.23   0.00 0.00 0.00 0.00 0.00 0.00 0.00 74.56 9.10



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2009.47 01-JAN-17:03 35.07 47.50 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
February 4039.02 26-FEB-17:50 23.38 31.66 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
March 7170.92 31-MAR-24:00 0.00 15.83 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7829.21 16-APR-18:20 0.00 31.66 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
May 3460.71 31-MAY-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5329.36 30-JUN-23:57 0.00 47.50 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
July 7187.81 31-JUL-23:53 0.00 47.50 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7613.92 06-AUG-17:50 0.00 15.83 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3480.98 30-SEP-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5343.13 31-OCT-24:00 0.00 15.83 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5854.63 06-NOV-17:00 222.14 284.97 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7731.29 10-DEC-16:55 46.77 63.33 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2009.47   0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7829.21   222.14 284.97 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1748.02 19-JAN-17:00 222.14 284.97 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3619.72 26-FEB-17:54 58.46 79.16 19486.06 0.00 0.00 0.00 0.00 0.00 0.00
March 6669.80 31-MAR-24:00 0.00 15.83 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7350.88 16-APR-18:06 0.00 79.16 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
May 3218.38 31-MAY-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5155.39 30-JUN-23:57 0.00 47.50 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
July 6879.26 31-JUL-23:53 0.00 47.50 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7194.57 29-AUG-16:00 222.14 284.97 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3191.99 30-SEP-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4920.07 31-OCT-24:00 0.00 15.83 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5538.52 06-NOV-17:00 222.14 284.97 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7274.10 15-DEC-17:00 222.14 284.97 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1748.02   0.00 15.83 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7350.88   222.14 284.97 38972.11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1815.75 19-JAN-17:00 222.14 284.97 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3665.94 27-FEB-17:40 70.15 158.31 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6560.21 31-MAR-24:00 0.00 15.83 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7461.95 23-APR-18:05 0.00 31.66 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
May 3201.24 31-MAY-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5207.71 30-JUN-23:57 0.00 47.50 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
July 6868.87 31-JUL-23:53 0.00 47.50 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7375.98 06-AUG-17:40 0.00 31.66 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
September 3222.88 30-SEP-24:00 0.00 15.83 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4845.83 31-OCT-24:00 0.00 15.83 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5598.98 06-NOV-17:00 222.14 284.97 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7340.65 15-DEC-17:00 222.14 284.97 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1815.75   0.00 15.83 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7461.95   222.14 284.97 23383.27 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 92474.00 02-JAN-15:00 5027.92 3337.76 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 182993.35 27-FEB-17:00 4808.68 3337.76 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 358199.25 31-MAR-24:00 0.00 185.45 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 365498.39 28-APR-16:00 4808.68 3337.76 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
May 175334.95 31-MAY-24:00 0.00 185.45 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 266978.84 30-JUN-23:53 0.00 556.35 854173.17 0.00 0.00 0.00 0.00 0.00 0.00
July 359207.51 31-JUL-24:00 0.00 556.35 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
August 367527.12 21-AUG-16:00 4808.68 3337.76 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
September 176337.73 30-SEP-24:00 0.00 185.45 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 268335.65 31-OCT-24:00 0.00 185.45 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 275847.86 06-NOV-17:00 4808.68 3337.76 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 367387.09 26-DEC-17:00 4808.68 3337.76 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 92474.00   0.00 185.45 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 367527.12   5027.92 3337.76 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.137460E+13 1115397.53 19-JAN-16:40 0.862407E+11 383758.04 10-JAN-06:10
February 0.163000E+13 1261970.19 24-FEB-16:00 0.644211E+11 429576.91 06-FEB-06:10
March 0.223415E+13 1394676.56 07-MAR-16:30 0.681597E+11 279685.74 13-MAR-05:10
April 0.259642E+13 1596566.80 28-APR-15:30 0.493187E+11 69661.08 04-APR-11:20
May 0.170400E+13 1165012.66 17-MAY-15:30 0.493990E+11 66332.01 04-MAY-11:30
June 0.207798E+13 1313862.97 21-JUN-15:09 0.465477E+11 62958.17 02-JUN-11:20
July 0.251581E+13 1459751.42 07-JUL-15:00 0.446469E+11 60295.68 03-JUL-11:20
August 0.295478E+13 1603116.60 30-AUG-15:50 0.476408E+11 61258.58 28-AUG-11:30
September 0.165039E+13 1168797.95 12-SEP-15:30 0.456915E+11 64485.20 28-SEP-11:30
October 0.204369E+13 1319544.77 05-OCT-15:20 0.494712E+11 67431.00 30-OCT-11:09
November 0.220455E+13 1448812.47 02-NOV-15:20 0.518318E+11 88982.23 16-NOV-06:00
December 0.255695E+13 1561732.69 12-DEC-16:40 0.746432E+11 393598.72 21-DEC-06:10
             
Annual Sum or Average 0.255433E+14     0.678012E+12    
Minimum of Months 0.137460E+13 1115397.53   0.446469E+11 60295.68  
Maximum of Months 0.295478E+13 1603116.60   0.862407E+11 429576.91  



Table of Contents

Report: EnergyConsumptionDistrictHeatingCoolingMonthly

For: Meter

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

DISTRICTCOOLING:FACILITY [J] DISTRICTCOOLING:FACILITY {Maximum} [W] DISTRICTCOOLING:FACILITY {TIMESTAMP} DISTRICTHEATING:FACILITY [J] DISTRICTHEATING:FACILITY {Maximum} [W] DISTRICTHEATING:FACILITY {TIMESTAMP}
January 0.241581E+12 95191.06 02-JAN-14:00 129712.56 8.47 22-JAN-18:40
February 0.437700E+12 185592.44 27-FEB-16:00 159308.18 13.49 01-FEB-00:40
March 0.729677E+12 358200.20 31-MAR-23:00 198363.82 11.22 24-MAR-23:30
April 0.942087E+12 368097.36 28-APR-15:00 65877.68 10.68 01-APR-18:30
May 0.241802E+12 175338.47 31-MAY-23:00 74777.54 13.56 31-MAY-23:40
June 0.470191E+12 266978.92 30-JUN-23:00 40336.98 6.97 01-JUN-23:40
July 0.732116E+12 359207.53 31-JUL-23:00 29556.01 4.51 03-JUL-23:19
August 0.979368E+12 370154.94 21-AUG-13:00 69524.26 7.04 22-AUG-23:19
September 0.237593E+12 176337.73 30-SEP-23:00 78127.48 4.88 11-SEP-23:40
October 0.489519E+12 268337.49 31-OCT-23:00 83110.05 10.74 31-OCT-23:30
November 0.710519E+12 278457.05 13-NOV-14:00 131452.39 11.26 11-NOV-00:30
December 0.978665E+12 370011.12 26-DEC-14:00 131389.55 11.04 01-DEC-00:30
             
Annual Sum or Average 0.719082E+13     1191536.52    
Minimum of Months 0.237593E+12 95191.06   29556.01 4.51  
Maximum of Months 0.979368E+12 370154.94   198363.82 13.56  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.170576E+12 0.334121E+11 0.766053E+12 0.210403E+12 0.629730E+11 0.433396E+11 0.00 0.682829E+11 0.174793E+11 0.00 0.207811E+10 0.00 0.00
February 0.153822E+12 0.279329E+11 0.978954E+12 0.233673E+12 0.582159E+11 0.498304E+11 0.00 0.995387E+11 0.252674E+11 0.00 0.276969E+10 0.00 0.00
March 0.181942E+12 0.280724E+11 0.141687E+13 0.307234E+12 0.677570E+11 0.635811E+11 0.00 0.131830E+12 0.338939E+11 0.00 0.296392E+10 0.00 0.00
April 0.161936E+12 0.244742E+11 0.165903E+13 0.343627E+12 0.705975E+11 0.847987E+11 0.00 0.194527E+12 0.523990E+11 0.00 0.503641E+10 0.00 0.00
May 0.173911E+12 0.227784E+11 0.774844E+12 0.210552E+12 0.859212E+11 0.935084E+11 0.00 0.247313E+12 0.876133E+11 0.00 0.755798E+10 0.00 0.00
June 0.172695E+12 0.207734E+11 0.106252E+13 0.250564E+12 0.878366E+11 0.101211E+12 0.00 0.279838E+12 0.949869E+11 0.00 0.755798E+10 0.00 0.00
July 0.161929E+12 0.223257E+11 0.139340E+13 0.306990E+12 0.875252E+11 0.111285E+12 0.00 0.317380E+12 0.107794E+12 0.00 0.717402E+10 0.00 0.00
August 0.180707E+12 0.242541E+11 0.173200E+13 0.355272E+12 0.931706E+11 0.115683E+12 0.00 0.339384E+12 0.106447E+12 0.00 0.786111E+10 0.00 0.00
September 0.162229E+12 0.259141E+11 0.740713E+12 0.203664E+12 0.807260E+11 0.929113E+11 0.00 0.247038E+12 0.900191E+11 0.00 0.717402E+10 0.00 0.00
October 0.169119E+12 0.295852E+11 0.108340E+13 0.258767E+12 0.847125E+11 0.935515E+11 0.00 0.240993E+12 0.776810E+11 0.00 0.587619E+10 0.00 0.00
November 0.168466E+12 0.314578E+11 0.135889E+13 0.297145E+12 0.698724E+11 0.712876E+11 0.00 0.161825E+12 0.425619E+11 0.00 0.304082E+10 0.00 0.00
December 0.165749E+12 0.341568E+11 0.170972E+13 0.355224E+12 0.664469E+11 0.574885E+11 0.00 0.131372E+12 0.340729E+11 0.00 0.272478E+10 0.00 0.00
                           
Annual Sum or Average 0.202308E+13 0.325137E+12 0.146764E+14 0.333312E+13 0.915755E+12 0.978476E+12 0.00 0.245932E+13 0.770216E+12 0.00 0.618150E+11 0.00 0.00
Minimum of Months 0.153822E+12 0.207734E+11 0.740713E+12 0.203664E+12 0.582159E+11 0.433396E+11 0.00 0.682829E+11 0.174793E+11 0.00 0.207811E+10 0.00 0.00
Maximum of Months 0.181942E+12 0.341568E+11 0.173200E+13 0.355272E+12 0.931706E+11 0.115683E+12 0.00 0.339384E+12 0.107794E+12 0.00 0.786111E+10 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.315625E+11 0.00 0.546781E+11 0.00 0.00
February 0.00 0.00 0.151100E+11 0.00 0.493111E+11 0.00 0.00
March 0.00 0.00 0.127222E+11 0.00 0.554375E+11 0.00 0.00
April 0.00 0.00 0.220578E+09 0.00 0.490981E+11 0.00 0.00
May 0.00 0.00 0.00 0.00 0.493990E+11 0.00 0.00
June 0.00 0.00 0.00 0.00 0.465477E+11 0.00 0.00
July 0.00 0.00 0.00 0.00 0.446469E+11 0.00 0.00
August 0.00 0.00 0.00 0.00 0.476408E+11 0.00 0.00
September 0.00 0.00 0.00 0.00 0.456915E+11 0.00 0.00
October 0.00 0.00 68803006.69 0.00 0.494024E+11 0.00 0.00
November 0.00 0.00 0.122077E+10 0.00 0.506110E+11 0.00 0.00
December 0.00 0.00 0.217880E+11 0.00 0.528552E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.826929E+11 0.00 0.595320E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.446469E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.315625E+11 0.00 0.554375E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 190416.39 31-JAN-08:09 37611.08 01-JAN-06:10 423497.50 02-JAN-08:09 134893.45 31-JAN-08:20 72003.84 20-JAN-06:10 66102.39 19-JAN-16:40 0.00 01-JAN-00:10
February 191913.68 01-FEB-08:09 37611.08 01-FEB-06:10 541788.89 01-FEB-08:09 152926.79 01-FEB-08:20 68618.30 27-FEB-16:10 66233.55 24-FEB-16:00 0.00 01-FEB-00:10
March 189051.72 27-MAR-07:10 37611.08 01-MAR-06:10 660080.29 01-MAR-08:09 170957.83 27-MAR-07:19 73800.64 28-MAR-05:10 66294.31 07-MAR-14:00 0.00 01-MAR-00:10
April 190287.35 14-APR-07:10 37611.08 01-APR-05:10 778371.69 03-APR-07:10 188991.03 14-APR-07:19 86048.92 18-APR-14:50 66924.19 28-APR-15:30 0.00 01-APR-00:10
May 181078.57 23-MAY-07:30 37611.08 01-MAY-05:10 423497.50 01-MAY-07:10 134888.53 23-MAY-07:40 81094.74 17-MAY-05:10 66840.81 17-MAY-15:30 0.00 01-MAY-00:10
June 174592.27 16-JUN-07:10 37611.08 01-JUN-05:10 541788.89 01-JUN-07:10 152917.67 16-JUN-07:19 90421.80 28-JUN-05:10 67030.48 05-JUN-15:00 0.00 01-JUN-00:10
July 178031.58 14-JUL-07:10 37611.08 01-JUL-05:10 660080.29 03-JUL-07:10 170952.03 14-JUL-07:19 84266.60 07-JUL-15:00 67901.08 12-JUL-15:39 0.00 01-JUL-00:10
August 182181.15 21-AUG-07:10 37611.08 01-AUG-05:10 778371.69 01-AUG-07:10 188986.76 21-AUG-07:19 91221.95 30-AUG-15:00 67214.20 29-AUG-14:50 0.00 01-AUG-00:10
September 189033.85 26-SEP-07:10 37611.08 01-SEP-05:10 423497.50 01-SEP-07:10 134892.72 26-SEP-07:19 83327.24 21-SEP-05:10 68241.86 14-SEP-15:00 0.00 01-SEP-00:10
October 193957.09 25-OCT-07:10 37611.08 01-OCT-05:10 541788.89 02-OCT-07:10 152927.87 25-OCT-07:19 89940.32 05-OCT-15:30 67255.32 13-OCT-08:00 0.00 01-OCT-00:10
November 191933.16 21-NOV-16:00 37611.08 01-NOV-05:10 660080.29 01-NOV-07:10 170959.23 01-NOV-07:19 85419.87 01-NOV-05:10 66831.80 07-NOV-15:09 0.00 01-NOV-00:10
December 193592.86 12-DEC-08:09 37611.08 01-DEC-06:10 778371.69 01-DEC-08:09 188992.77 12-DEC-08:20 80391.49 12-DEC-06:10 66793.70 12-DEC-16:40 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 174592.27   37611.08   423497.50   134888.53   68618.30   66102.39   0.00  
Maximum of Months 193957.09   37611.08   778371.69   188992.77   91221.95   68241.86   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 232224.73 19-JAN-16:40 55581.51 19-JAN-10:30 0.00 5613.48 02-JAN-10:09 0.00 0.00
February 241504.09 24-FEB-16:00 55581.51 24-FEB-10:50 0.00 5613.48 01-FEB-11:39 0.00 0.00
March 251842.02 07-MAR-14:00 55581.51 06-MAR-12:00 0.00 5613.48 04-MAR-14:30 0.00 0.00
April 285540.13 28-APR-15:30 55581.51 14-APR-10:20 0.00 5613.48 01-APR-06:10 0.00 0.00
May 271054.35 26-MAY-10:50 55581.51 01-MAY-08:20 0.00 5613.48 01-MAY-06:10 0.00 0.00
June 281748.60 19-JUN-10:39 55581.51 01-JUN-09:20 0.00 5613.48 01-JUN-06:10 0.00 0.00
July 288992.84 03-JUL-09:00 55581.51 01-JUL-06:19 0.00 5613.48 01-JUL-06:10 0.00 0.00
August 296302.86 17-AUG-14:09 55581.51 01-AUG-06:30 0.00 5613.48 01-AUG-06:10 0.00 0.00
September 273471.42 18-SEP-10:09 55581.51 10-SEP-14:00 0.00 5613.48 01-SEP-06:10 0.00 0.00
October 284269.29 06-OCT-11:00 55581.51 08-OCT-12:50 0.00 5613.48 02-OCT-08:50 0.00 0.00
November 275919.73 02-NOV-14:50 55581.51 01-NOV-08:20 0.00 5613.48 01-NOV-06:10 0.00 0.00
December 264412.60 12-DEC-16:40 55581.51 11-DEC-14:50 0.00 5613.48 02-DEC-13:20 0.00 0.00
                   
Annual Sum or Average         0.00     0.00 0.00
Minimum of Months 232224.73   55581.51   0.00 5613.48   0.00 0.00
Maximum of Months 296302.86   55581.51   0.00 5613.48   0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1115397.53 19-JAN-16:40 172690.50 423497.50 0.00 100840.57 58846.85 66102.39 0.00 232224.73 55581.51
February 1261970.19 24-FEB-16:00 172307.68 541788.89 0.00 118872.94 60068.06 66233.55 0.00 241504.09 55581.51
March 1394676.56 07-MAR-16:30 171591.05 660080.29 0.00 136905.25 54633.02 66254.53 0.00 244017.43 55581.51
April 1596566.80 28-APR-15:30 171235.93 778371.69 0.00 154937.61 78362.27 66924.19 0.00 285540.13 55581.51
May 1165012.66 17-MAY-15:30 171235.93 423497.50 0.00 100839.97 77822.48 66840.81 0.00 263581.00 55581.51
June 1313862.97 21-JUN-15:09 171235.93 541788.89 0.00 118872.52 73603.58 66902.12 0.00 280264.95 55581.51
July 1459751.42 07-JUL-15:00 171235.93 660080.29 0.00 136905.07 84266.60 66893.47 0.00 279175.09 55581.51
August 1603116.60 30-AUG-15:50 171235.93 778371.69 0.00 154937.61 90954.55 67029.98 0.00 279391.86 55581.51
September 1168797.95 12-SEP-15:30 171235.93 423497.50 0.00 100839.97 77033.87 67046.46 0.00 267949.25 55581.51
October 1319544.77 05-OCT-15:20 171235.93 541788.89 0.00 118872.52 89732.40 67153.38 0.00 269566.67 55581.51
November 1448812.47 02-NOV-15:20 171818.25 660080.29 0.00 136905.09 76942.79 66816.90 0.00 275054.17 55581.51
December 1561732.69 12-DEC-16:40 178460.80 778371.69 0.00 154940.77 57558.15 66793.70 0.00 264412.60 55581.51
                       
Annual Sum or Average                      
Minimum of Months 1115397.53   171235.93 423497.50 0.00 100839.97 54633.02 66102.39 0.00 232224.73 55581.51
Maximum of Months 1603116.60   178460.80 778371.69 0.00 154940.77 90954.55 67153.38 0.00 285540.13 55581.51



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 378062.17 10-JAN-06:10 0.00 73380.93 20-JAN-12:20 0.00
February 0.00 0.00 423881.04 06-FEB-06:10 0.00 73307.27 03-FEB-12:39 0.00
March 0.00 0.00 273064.66 11-MAR-06:10 0.00 72210.55 03-MAR-12:00 0.00
April 0.00 0.00 38936.57 03-APR-16:49 0.00 69661.08 04-APR-11:20 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 66332.01 04-MAY-11:30 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 62958.17 02-JUN-11:20 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 60295.68 03-JUL-11:20 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 61258.58 28-AUG-11:30 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 64485.20 28-SEP-11:30 0.00
October 0.00 0.00 7310.77 28-OCT-06:49 0.00 67431.00 30-OCT-11:09 0.00
November 0.00 0.00 77275.55 16-NOV-06:10 0.00 70479.83 21-NOV-12:00 0.00
December 0.00 0.00 387902.85 21-DEC-06:10 0.00 72870.26 28-DEC-12:39 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 0.00   0.00 60295.68   0.00
Maximum of Months 0.00 0.00 423881.04   0.00 73380.93   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 8.83 26.75 0.00 26.75
February 0.00 0.00 0.00 0.00 5.00 26.69 0.00 26.69
March 0.00 0.00 0.00 0.00 2.83 25.99 0.00 25.99
April 0.00 0.00 0.00 0.00 3.17 26.00 0.00 26.00
May 0.00 0.00 0.00 0.00 3.50 25.79 0.17 25.74
June 0.00 0.00 0.00 0.00 1.33 25.73 0.00 25.73
July 0.00 0.00 0.00 0.00 4.83 26.10 0.00 26.10
August 0.00 0.00 0.00 0.00 6.17 26.07 0.00 26.07
September 0.00 0.00 0.00 0.00 6.17 26.67 1.17 26.78
October 0.00 0.00 0.00 0.00 8.83 26.54 0.00 26.54
November 0.00 0.00 0.00 0.00 12.83 26.92 0.67 26.94
December 0.00 0.00 0.00 0.00 13.33 26.88 0.33 26.89
                 
Annual Sum or Average 0.00   0.00   76.83 26.55 2.33 26.57
Minimum of Months 0.00 0.00 0.00 0.00 1.33 25.73 0.00 25.73
Maximum of Months 0.00 0.00 0.00 0.00 13.33 26.92 1.17 26.94



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.33 19.13 0.00 19.13 0.00 19.13 0.00 19.13
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 19.13 0.00 19.13 0.00 19.13 0.00 19.13
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 19.13 0.00 19.13 0.00 19.13 0.00 19.13



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.17 25.64 0.00 25.64
August 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.33 25.60 0.00 25.60
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 25.64 0.00 25.64



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 27.36 0.17 27.36
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.17 27.26 0.17 27.26
April 0.00 0.00 0.00 0.00 0.83 27.71 0.83 27.71
May 0.00 0.00 0.00 0.00 4.33 27.78 4.33 27.78
June 0.00 0.00 0.00 0.00 1.67 27.61 1.67 27.61
July 0.00 0.00 0.00 0.00 3.50 27.61 3.50 27.61
August 0.00 0.00 0.00 0.00 0.83 27.45 0.83 27.45
September 0.00 0.00 0.00 0.00 4.00 27.70 4.00 27.70
October 0.00 0.00 0.00 0.00 2.17 27.55 2.17 27.55
November 0.00 0.00 0.00 0.00 0.17 27.32 0.17 27.32
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   17.83 27.66 17.83 27.66
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 4.33 27.78 4.33 27.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 4.50 27.83 4.50 27.83
February 0.00 0.00 0.00 0.00 2.17 27.63 2.17 27.63
March 0.00 0.00 0.00 0.00 1.17 27.45 1.17 27.45
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.17 25.58 0.00 25.58
August 0.00 0.00 0.00 0.00 0.50 26.15 0.17 26.43
September 0.00 0.00 0.00 0.00 5.67 27.54 5.50 27.57
October 0.00 0.00 0.00 0.00 9.50 27.67 8.83 27.71
November 0.00 0.00 0.00 0.00 9.50 27.35 9.50 27.35
December 0.00 0.00 0.00 0.00 6.67 27.83 6.67 27.83
                 
Annual Sum or Average 0.00   0.00   39.83 27.58 38.50 27.61
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 9.50 27.83 9.50 27.83



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.83 27.55 0.83 27.55
February 0.00 0.00 0.00 0.00 1.67 27.74 1.50 27.77
March 0.00 0.00 0.00 0.00 6.00 27.21 2.83 27.40
April 0.00 0.00 0.00 0.00 19.67 27.05 5.83 27.25
May 0.00 0.00 0.00 0.00 7.67 27.55 3.67 27.61
June 0.00 0.00 0.00 0.00 20.33 27.00 4.83 27.17
July 0.00 0.00 0.00 0.00 27.33 27.11 9.50 27.29
August 0.00 0.00 0.00 0.00 28.17 27.11 7.67 27.27
September 0.00 0.00 0.00 0.00 7.33 27.61 3.83 27.75
October 0.00 0.00 0.00 0.00 17.00 27.13 6.83 27.32
November 0.00 0.00 0.00 0.00 8.00 27.16 4.83 27.39
December 0.00 0.00 0.00 0.00 10.50 27.18 5.33 27.37
                 
Annual Sum or Average 0.00   0.00   154.50 27.16 57.50 27.34
Minimum of Months 0.00 0.00 0.00 0.00 0.83 27.00 0.83 27.17
Maximum of Months 0.00 0.00 0.00 0.00 28.17 27.74 9.50 27.77



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.00 27.86 1.00 27.86
May 0.00 0.00 0.00 0.00 5.33 27.78 5.33 27.78
June 0.00 0.00 0.00 0.00 2.50 27.70 2.50 27.70
July 0.00 0.00 0.00 0.00 5.00 27.76 5.00 27.76
August 0.00 0.00 0.00 0.00 2.83 27.54 2.83 27.54
September 0.00 0.00 0.00 0.00 4.50 27.75 4.50 27.75
October 0.00 0.00 0.00 0.00 2.33 27.59 2.33 27.59
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   23.50 27.72 23.50 27.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 5.33 27.86 5.33 27.86



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 4.67 27.58 4.67 27.58
February 0.00 0.00 0.00 0.00 1.67 27.76 1.67 27.76
March 0.00 0.00 0.00 0.00 0.83 27.35 0.83 27.35
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 5.50 27.60 5.33 27.60
October 0.00 0.00 0.00 0.00 8.33 27.81 8.00 27.82
November 0.00 0.00 0.00 0.00 13.17 26.49 13.17 26.49
December 0.00 0.00 0.00 0.00 5.50 27.86 5.50 27.86
                 
Annual Sum or Average 0.00   0.00   39.67 27.31 39.17 27.31
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 13.17 27.86 13.17 27.86



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.33 27.76 0.33 27.76
March 0.00 0.00 0.00 0.00 0.33 27.36 0.33 27.36
April 0.00 0.00 0.00 0.00 2.83 27.72 1.67 27.71
May 0.00 0.00 0.00 0.00 3.17 27.96 1.67 27.98
June 0.00 0.00 0.00 0.00 4.00 27.88 2.50 27.90
July 0.00 0.00 0.00 0.00 6.17 27.46 4.17 27.50
August 0.00 0.00 0.00 0.00 3.50 27.09 1.67 27.26
September 0.00 0.00 0.00 0.00 4.67 27.91 2.83 27.96
October 0.00 0.00 0.00 0.00 4.00 27.65 3.00 27.70
November 0.00 0.00 0.00 0.00 0.17 27.31 0.17 27.31
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   29.17 27.65 18.33 27.70
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.17 27.96 4.17 27.98



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.67 19.15 0.00 19.15 0.00 19.15 0.00 19.15
February 2.00 19.08 0.67 19.33 0.00 19.33 0.00 19.33
March 0.33 19.33 0.00 19.33 0.00 19.33 0.00 19.33
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.50 27.32 0.33 27.33
July 0.00 0.00 0.00 0.00 0.83 27.38 0.83 27.38
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.83 27.40 0.83 27.40
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 19.44 0.00 19.44 0.00 19.44 0.00 19.44
December 0.50 18.78 0.00 18.78 0.00 18.78 0.00 18.78
                 
Annual Sum or Average 4.67 19.10 0.67 19.23 2.17 21.58 2.00 22.80
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.00 19.44 0.67 19.44 0.83 27.40 0.83 27.40



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.00 19.11 0.00 19.11 0.00 19.11 0.00 19.11
February 0.83 18.44 0.00 18.44 0.00 18.44 0.00 18.44
March 0.17 19.44 0.00 19.44 0.00 19.44 0.00 19.44
April 0.00 0.00 0.00 0.00 1.17 27.78 1.17 27.78
May 0.00 0.00 0.00 0.00 8.83 27.81 8.17 27.83
June 0.00 0.00 0.00 0.00 7.67 27.60 7.17 27.61
July 0.00 0.00 0.00 0.00 9.83 27.67 9.17 27.69
August 0.00 0.00 0.00 0.00 6.50 27.60 6.33 27.60
September 0.00 0.00 0.00 0.00 8.50 27.75 8.00 27.76
October 0.00 0.00 0.00 0.00 4.17 27.52 4.17 27.52
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.50 18.84 0.00 18.84 0.00 18.84 0.00 18.84
                 
Annual Sum or Average 2.50 18.85 0.00 18.85 46.67 27.23 44.17 27.45
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.00 19.44 0.00 19.44 9.83 27.81 9.17 27.83



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 19.25 0.00 19.25 3.17 27.10 3.17 27.49
February 0.33 18.78 0.00 18.78 1.50 26.12 1.50 26.85
March 0.00 0.00 0.00 0.00 1.17 27.41 1.17 27.41
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.83 27.36 0.83 27.36
August 0.00 0.00 0.00 0.00 3.00 27.42 3.00 27.42
September 0.00 0.00 0.00 0.00 7.83 27.77 6.67 27.79
October 0.00 0.00 0.00 0.00 9.83 27.89 8.50 27.92
November 0.00 0.00 0.00 0.00 8.00 27.02 7.83 27.02
December 0.50 19.18 0.00 19.18 4.33 27.04 4.33 27.47
                 
Annual Sum or Average 1.17 19.08 0.00 19.08 39.83 27.38 37.00 27.51
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 19.25 0.00 19.25 9.83 27.89 8.50 27.92



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 19.17 0.00 19.17 0.00 19.17 0.00 19.17
February 0.33 18.79 0.00 18.79 0.50 24.07 0.50 25.39
March 0.00 0.00 0.00 0.00 0.33 27.59 0.33 27.59
April 0.00 0.00 0.00 0.00 2.67 27.88 1.67 27.90
May 0.00 0.00 0.00 0.00 5.00 27.98 2.83 27.98
June 0.00 0.00 0.00 0.00 6.00 27.89 3.17 27.95
July 0.00 0.00 0.00 0.00 9.33 27.61 5.50 27.66
August 0.00 0.00 0.00 0.00 5.17 27.56 3.17 27.63
September 0.00 0.00 0.00 0.00 6.17 28.00 3.67 28.07
October 0.00 0.00 0.00 0.00 4.67 27.84 3.67 27.85
November 0.00 0.00 0.00 0.00 0.17 27.27 0.17 27.27
December 0.33 19.02 0.00 19.02 0.00 19.02 0.00 19.02
                 
Annual Sum or Average 1.17 19.02 0.00 19.02 40.00 27.55 24.67 27.68
Minimum of Months 0.00 0.00 0.00 0.00 0.00 19.02 0.00 19.02
Maximum of Months 0.50 19.17 0.00 19.17 9.33 28.00 5.50 28.07



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.83 27.60 0.83 27.60
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.83 27.60 0.83 27.60
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.83 27.60 0.83 27.60



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 67.50 24.51 242.67 25.00 38.67 24.99
February 84.33 24.60 309.83 24.74 62.83 24.75
March 111.83 24.65 312.00 24.69 83.33 24.72
April 177.50 24.84 431.33 24.67 176.50 24.71
May 295.83 24.95 508.00 24.70 295.83 24.76
June 264.17 24.94 496.00 24.65 264.17 24.72
July 248.00 25.30 497.00 24.87 248.00 24.98
August 188.17 25.47 514.00 24.79 188.17 24.94
September 214.00 25.40 485.00 24.86 214.00 24.99
October 162.67 25.69 454.50 24.99 162.67 25.14
November 74.83 25.53 381.17 24.97 74.83 25.05
December 62.50 25.16 316.00 25.04 56.33 25.07
             
Annual Sum or Average 1951.33 25.12 4947.50 24.81 1865.33 24.89
Minimum of Months 62.50 24.51 242.67 24.65 38.67 24.71
Maximum of Months 295.83 25.69 514.00 25.04 295.83 25.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 145.17 23.43 163.83 24.03 0.00 24.03
February 67.67 23.53 232.33 24.20 0.00 24.20
March 59.50 23.59 268.67 24.22 0.00 24.22
April 0.00 0.00 369.83 24.19 0.00 24.19
May 1.00 23.28 404.83 24.22 0.00 24.22
June 0.00 0.00 418.67 24.11 0.00 24.11
July 0.00 0.00 457.50 24.10 0.00 24.10
August 0.00 0.00 497.67 24.08 0.00 24.08
September 0.00 0.00 410.00 24.20 0.00 24.20
October 9.83 23.61 419.67 24.24 0.00 24.24
November 5.17 23.76 355.17 24.35 0.00 24.35
December 32.17 23.58 270.50 24.36 0.00 24.36
             
Annual Sum or Average 320.50 23.51 4268.67 24.19 0.00 24.19
Minimum of Months 0.00 0.00 163.83 24.03 0.00 24.03
Maximum of Months 145.17 23.76 497.67 24.36 0.00 24.36



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 403.33 23.01 43.50 23.13 0.00 23.13
February 290.33 23.06 92.83 23.33 0.00 23.33
March 280.50 23.10 123.17 23.44 0.00 23.44
April 125.33 23.20 220.50 23.93 0.00 23.93
May 45.50 23.12 284.83 24.10 0.00 24.10
June 44.50 23.12 274.17 24.07 0.00 24.07
July 57.00 23.15 262.00 24.06 0.00 24.06
August 32.00 23.13 295.33 24.13 0.00 24.13
September 63.00 23.11 252.67 24.00 0.00 24.00
October 66.50 23.19 249.67 24.06 0.00 24.06
November 180.17 23.19 155.67 23.68 0.00 23.68
December 305.17 23.04 92.33 23.33 0.00 23.33
             
Annual Sum or Average 1893.33 23.09 2346.67 23.73 0.00 23.73
Minimum of Months 32.00 23.01 43.50 23.13 0.00 23.13
Maximum of Months 403.33 23.20 295.33 24.13 0.00 24.13



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 430.83 21.89 47.67 22.00 15.67 21.96
February 347.67 22.19 83.00 22.35 20.83 22.24
March 342.67 22.45 106.83 22.78 9.67 22.72
April 160.17 23.10 201.33 23.76 0.00 23.76
May 21.00 23.13 350.17 24.18 0.00 24.18
June 7.83 23.25 349.00 24.18 0.00 24.18
July 13.67 23.24 343.83 24.20 0.00 24.20
August 15.67 23.26 363.83 24.20 0.00 24.20
September 51.83 23.21 303.50 24.08 0.00 24.08
October 86.00 22.95 268.17 23.95 0.00 23.95
November 305.50 22.72 92.33 23.05 0.00 23.05
December 404.67 22.21 69.33 22.40 12.33 22.35
             
Annual Sum or Average 2187.50 22.40 2579.00 23.34 58.50 23.30
Minimum of Months 7.83 21.89 47.67 22.00 0.00 21.96
Maximum of Months 430.83 23.26 363.83 24.20 20.83 24.20



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 360.17 22.56 81.83 22.87 0.00 22.87
February 241.17 22.82 127.00 23.28 1.67 23.27
March 233.33 23.10 182.00 23.61 0.00 23.61
April 41.67 23.44 322.33 24.11 0.00 24.11
May 0.67 26.39 503.83 24.37 0.67 24.37
June 0.00 0.00 490.67 24.32 0.00 24.32
July 0.50 26.96 495.17 24.39 0.50 24.40
August 0.00 0.00 513.83 24.27 0.00 24.27
September 0.00 0.00 460.83 24.36 0.00 24.36
October 33.67 23.41 410.17 24.28 0.00 24.28
November 145.83 23.38 216.33 23.88 0.00 23.88
December 249.67 22.99 142.00 23.42 0.00 23.42
             
Annual Sum or Average 1306.67 22.93 3946.00 23.96 2.83 23.96
Minimum of Months 0.00 0.00 81.83 22.87 0.00 22.87
Maximum of Months 360.17 26.96 513.83 24.39 1.67 24.40



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 311.33 22.73 104.67 23.18 0.83 23.19
February 212.50 22.85 142.83 23.45 1.33 23.44
March 198.33 22.78 203.83 23.59 1.17 23.60
April 72.67 23.29 309.33 24.06 3.67 24.09
May 22.17 26.74 484.00 24.55 21.17 24.65
June 8.17 26.40 478.50 24.37 7.00 24.41
July 15.00 26.74 477.17 24.48 14.50 24.54
August 6.17 26.54 480.67 24.28 5.67 24.31
September 21.33 26.71 430.50 24.58 20.33 24.68
October 48.17 24.10 392.17 24.39 11.50 24.45
November 140.67 23.19 234.83 23.92 1.00 23.93
December 259.33 22.73 129.33 23.25 0.00 23.25
             
Annual Sum or Average 1315.83 23.11 3867.83 24.05 88.17 24.10
Minimum of Months 6.17 22.73 104.67 23.18 0.00 23.19
Maximum of Months 311.33 26.74 484.00 24.58 21.17 24.68



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 195.17 23.23 186.83 23.97 16.00 24.09
February 124.33 23.15 250.00 24.03 9.33 24.06
March 167.33 23.00 240.50 23.83 4.00 23.86
April 36.17 23.35 349.83 24.20 0.00 24.20
May 0.67 26.25 504.83 24.37 0.67 24.37
June 0.00 0.00 486.17 24.31 0.00 24.31
July 0.50 27.02 492.17 24.39 0.50 24.39
August 3.83 27.00 513.00 24.34 3.83 24.36
September 25.67 26.86 472.33 24.60 25.67 24.71
October 49.33 25.98 452.17 24.72 36.00 24.86
November 68.00 24.69 365.67 24.62 24.67 24.75
December 144.00 23.48 275.67 24.25 18.67 24.38
             
Annual Sum or Average 815.00 23.64 4589.17 24.32 139.33 24.39
Minimum of Months 0.00 0.00 186.83 23.83 0.00 23.86
Maximum of Months 195.17 27.02 513.00 24.72 36.00 24.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 231.50 22.94 186.83 23.65 3.33 23.67
February 93.83 23.39 296.00 24.27 5.67 24.31
March 56.67 23.96 359.00 24.50 10.50 24.56
April 28.33 26.93 467.50 24.75 28.33 24.86
May 18.17 26.90 508.00 24.59 18.17 24.67
June 26.00 26.94 496.00 24.63 26.00 24.74
July 52.83 26.83 497.00 24.85 52.83 25.02
August 47.83 26.82 514.00 24.73 47.83 24.89
September 22.83 26.93 485.00 24.63 22.83 24.73
October 32.17 26.37 469.00 24.74 27.00 24.85
November 25.17 25.55 419.83 24.68 14.67 24.75
December 52.00 24.64 343.00 24.78 17.33 24.87
             
Annual Sum or Average 687.33 24.59 5041.17 24.59 274.50 24.69
Minimum of Months 18.17 22.94 186.83 23.65 3.33 23.67
Maximum of Months 231.50 26.94 514.00 24.85 52.83 25.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 462.50 21.60 68.33 21.59 50.67 21.50
February 384.83 21.96 77.17 21.97 40.33 21.83
March 389.17 22.28 90.67 22.47 19.50 22.39
April 181.17 23.16 208.00 23.74 4.50 23.77
May 9.67 26.20 488.00 24.37 9.67 24.40
June 1.00 23.37 486.17 24.34 0.00 24.34
July 3.83 26.16 481.17 24.46 3.83 24.47
August 0.00 0.00 490.50 24.34 0.00 24.34
September 10.50 24.63 402.50 24.34 6.50 24.36
October 94.83 23.19 336.17 24.08 9.00 24.11
November 326.67 22.53 80.00 22.84 0.00 22.84
December 416.67 21.89 68.33 22.02 24.67 21.95
             
Annual Sum or Average 2280.83 22.19 3277.00 23.36 168.67 23.30
Minimum of Months 0.00 0.00 68.33 21.59 0.00 21.50
Maximum of Months 462.50 26.20 490.50 24.46 50.67 24.47



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 373.67 21.97 52.67 22.12 18.33 22.06
February 284.17 22.23 73.83 22.51 13.00 22.43
March 252.00 22.35 126.50 22.98 9.17 22.92
April 106.83 23.31 230.67 24.16 9.50 24.23
May 36.50 26.71 404.33 24.75 36.17 24.90
June 17.50 26.58 404.67 24.60 16.17 24.68
July 34.17 26.77 402.00 24.83 33.83 24.97
August 17.00 26.73 404.83 24.60 16.50 24.68
September 39.33 25.88 335.00 24.74 30.00 24.88
October 90.33 23.87 295.33 24.43 24.17 24.56
November 213.33 22.73 120.00 23.36 0.50 23.37
December 324.83 22.07 71.50 22.33 16.83 22.26
             
Annual Sum or Average 1789.67 22.72 2921.33 23.81 224.17 23.87
Minimum of Months 17.00 21.97 52.67 22.12 0.50 22.06
Maximum of Months 373.67 26.77 404.83 24.83 36.17 24.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 237.50 22.87 157.67 23.62 16.83 23.73
February 178.50 22.80 200.67 23.64 13.33 23.64
March 224.67 22.56 187.00 23.33 8.00 23.29
April 105.50 23.30 284.33 24.10 4.67 24.12
May 9.67 26.19 480.33 24.39 9.67 24.42
June 1.00 23.36 476.33 24.33 0.00 24.33
July 3.83 26.07 476.50 24.45 3.83 24.46
August 0.67 26.95 498.00 24.39 0.67 24.40
September 32.17 26.50 450.00 24.62 30.83 24.74
October 69.67 25.51 440.50 24.73 43.83 24.89
November 111.50 24.01 315.17 24.48 24.17 24.62
December 203.17 22.93 232.00 23.88 19.33 23.98
             
Annual Sum or Average 1177.83 23.25 4198.50 24.20 175.17 24.26
Minimum of Months 0.67 22.56 157.67 23.33 0.00 23.29
Maximum of Months 237.50 26.95 498.00 24.73 43.83 24.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 383.00 22.05 73.83 22.34 10.83 22.31
February 279.50 22.29 127.33 22.79 16.00 22.72
March 266.50 22.43 164.67 23.14 7.83 23.11
April 89.17 23.73 330.50 24.34 14.17 24.42
May 19.17 26.70 497.83 24.53 19.17 24.61
June 15.17 26.89 491.50 24.54 15.17 24.61
July 27.50 26.80 488.00 24.69 27.50 24.80
August 12.67 26.80 509.17 24.52 12.67 24.58
September 24.33 26.29 441.33 24.57 21.67 24.66
October 64.33 24.33 411.50 24.46 23.00 24.55
November 218.17 22.83 181.67 23.52 1.50 23.53
December 310.33 22.18 131.17 22.80 6.00 22.78
             
Annual Sum or Average 1709.83 22.71 3848.50 23.90 175.50 23.95
Minimum of Months 12.67 22.05 73.83 22.34 1.50 22.31
Maximum of Months 383.00 26.89 509.17 24.69 27.50 24.80



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 466.33 21.17 183.00 21.03 167.33 20.89
February 397.67 21.51 126.83 21.41 91.50 21.20
March 402.67 21.86 135.33 21.95 65.83 21.77
April 208.17 22.87 203.83 23.56 7.83 23.60
May 12.50 26.24 480.33 24.44 12.50 24.48
June 6.83 25.60 485.50 24.42 4.67 24.44
July 14.17 26.33 480.33 24.56 13.17 24.61
August 7.83 25.65 487.83 24.41 5.67 24.43
September 28.67 24.35 407.00 24.39 11.50 24.43
October 112.00 22.85 332.83 23.98 10.17 24.02
November 362.67 22.02 93.33 22.29 20.67 22.21
December 430.83 21.44 153.50 21.43 115.33 21.28
             
Annual Sum or Average 2450.33 21.85 3569.67 23.04 526.17 22.88
Minimum of Months 6.83 21.17 93.33 21.03 4.67 20.89
Maximum of Months 466.33 26.33 487.83 24.56 167.33 24.61



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 444.50 21.48 133.17 21.50 94.33 21.34
February 346.67 21.83 121.33 21.98 48.17 21.78
March 297.33 21.99 190.00 22.60 39.83 22.44
April 126.83 23.11 292.83 24.03 14.17 24.11
May 48.00 26.61 480.67 24.70 46.33 24.87
June 33.83 26.49 484.67 24.60 31.00 24.72
July 55.50 26.57 478.17 24.80 52.67 24.98
August 37.33 26.33 487.17 24.59 33.00 24.72
September 63.83 25.67 416.00 24.68 45.17 24.85
October 115.50 23.68 362.00 24.32 32.00 24.46
November 291.33 22.43 135.33 22.96 8.00 22.92
December 394.33 21.67 133.33 21.83 70.83 21.69
             
Annual Sum or Average 2255.00 22.47 3714.67 23.54 515.50 23.54
Minimum of Months 33.83 21.48 121.33 21.50 8.00 21.34
Maximum of Months 444.50 26.61 487.17 24.80 94.33 24.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 289.00 22.32 158.00 22.88 47.00 22.82
February 226.67 22.27 193.67 23.02 31.33 22.90
March 264.33 22.15 202.00 22.79 42.00 22.64
April 140.83 23.03 271.67 23.93 9.00 23.98
May 15.50 26.34 472.50 24.47 15.50 24.53
June 6.17 25.05 475.17 24.39 3.17 24.41
July 16.33 25.90 476.83 24.54 13.17 24.59
August 20.67 26.43 495.00 24.52 19.33 24.59
September 43.00 26.27 443.17 24.67 37.67 24.82
October 82.67 25.03 431.33 24.67 46.33 24.85
November 155.67 23.24 273.17 24.12 18.67 24.23
December 251.17 22.39 224.50 23.25 44.17 23.22
             
Annual Sum or Average 1512.00 22.86 4117.00 23.97 327.33 23.98
Minimum of Months 6.17 22.15 158.00 22.79 3.17 22.64
Maximum of Months 289.00 26.43 495.00 24.67 47.00 24.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 414.67 21.63 124.17 21.75 73.50 21.62
February 317.17 21.83 141.17 22.14 51.50 21.95
March 301.00 21.98 178.33 22.57 37.83 22.43
April 132.50 23.32 292.50 24.14 18.17 24.25
May 24.67 26.61 480.00 24.58 24.33 24.67
June 21.50 26.39 483.17 24.56 18.67 24.65
July 38.50 26.50 483.50 24.72 36.00 24.85
August 21.33 26.62 501.17 24.58 20.17 24.66
September 40.50 25.53 425.50 24.59 27.33 24.71
October 86.50 23.81 388.83 24.36 25.67 24.47
November 273.17 22.32 149.17 23.02 3.50 23.02
December 349.50 21.73 149.00 22.16 51.67 22.04
             
Annual Sum or Average 2021.00 22.36 3796.50 23.60 388.33 23.58
Minimum of Months 21.33 21.63 124.17 21.75 3.50 21.62
Maximum of Months 414.67 26.62 501.17 24.72 73.50 24.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.67 27.00 502.00 27.00 0.67 27.00
February 5.00 27.00 454.00 27.00 5.00 27.00
March 9.50 27.00 514.00 27.00 9.50 27.00
April 145.33 27.00 485.00 27.00 145.33 27.00
May 0.00 0.00 508.00 27.00 0.00 27.00
June 18.50 27.00 496.00 27.00 18.50 27.00
July 163.00 27.00 497.00 27.00 163.00 27.00
August 339.50 27.02 514.00 27.01 339.50 27.01
September 3.00 27.00 485.00 27.00 3.00 27.00
October 35.00 27.00 502.00 27.00 35.00 27.00
November 41.50 27.00 489.00 27.00 41.50 27.00
December 87.83 27.00 497.00 27.00 87.83 27.00
             
Annual Sum or Average 848.83 27.01 5943.00 27.00 848.83 27.00
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 339.50 27.02 514.00 27.01 339.50 27.01



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 27.00 0.00 27.00
February 0.00 0.00 454.00 27.00 0.00 27.00
March 0.00 0.00 514.00 27.00 0.00 27.00
April 0.50 27.17 485.00 27.00 0.50 27.00
May 0.00 0.00 508.00 27.00 0.00 27.00
June 0.00 0.00 496.00 27.00 0.00 27.00
July 0.00 0.00 497.00 27.00 0.00 27.00
August 16.00 27.31 514.00 27.03 16.00 27.03
September 0.00 0.00 485.00 27.00 0.00 27.00
October 0.00 0.00 502.00 27.00 0.00 27.00
November 0.17 27.00 489.00 27.00 0.17 27.00
December 0.00 0.00 497.00 27.00 0.00 27.00
             
Annual Sum or Average 16.67 27.30 5943.00 27.00 16.67 27.00
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 16.00 27.31 514.00 27.03 16.00 27.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 8.67 26.05 464.00 26.98 0.00 26.98
February 5.50 27.00 430.67 27.00 0.00 27.00
March 0.00 0.00 506.33 27.00 0.00 27.00
April 11.00 27.01 485.00 27.00 11.00 27.00
May 1.83 27.00 508.00 27.00 1.83 27.00
June 6.83 27.00 496.00 27.00 6.83 27.00
July 22.83 27.00 497.00 27.00 22.83 27.00
August 58.00 27.07 514.00 27.01 58.00 27.02
September 3.50 27.00 485.00 27.00 3.50 27.00
October 3.33 27.00 502.00 27.00 3.33 27.00
November 1.17 27.00 489.00 27.00 1.17 27.00
December 2.17 27.00 488.83 27.00 2.17 27.00
             
Annual Sum or Average 124.83 26.97 5865.83 27.00 110.67 27.00
Minimum of Months 0.00 0.00 430.67 26.98 0.00 26.98
Maximum of Months 58.00 27.07 514.00 27.01 58.00 27.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 27.00 502.00 27.00 502.00 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.00 485.00 27.00 485.00 27.00
May 508.00 27.00 508.00 27.00 508.00 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 27.00 514.00 27.00 514.00 27.00
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.00 497.00 27.00 497.00 27.00
             
Annual Sum or Average 5943.00 27.00 5943.00 27.00 5943.00 27.00
Minimum of Months 454.00 27.00 454.00 27.00 454.00 27.00
Maximum of Months 514.00 27.00 514.00 27.00 514.00 27.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00017 32.32239 0.86730 21.01415
February 454.00000 27.00096 33.38689 0.92292 23.10301
March 514.00000 27.00060 33.57482 0.96114 24.57889
April 485.00000 27.00047 35.90929 1.02796 27.33590
May 508.00000 27.00026 41.97198 0.32225 7.19660
June 496.00000 27.00238 40.13716 0.35652 7.67574
July 497.00000 27.00154 39.22439 0.39715 8.31265
August 514.00000 27.01056 38.47022 0.43922 9.05683
September 485.00000 27.00017 42.38311 0.32808 7.28046
October 502.00000 27.00186 38.03631 0.99608 25.99764
November 489.00000 27.00072 35.04243 0.98968 25.73026
December 497.00000 27.00020 33.14069 0.99189 25.84788
           
Annual Sum or Average 5943.00000 27.00169 36.98665 0.71458 17.69970
Minimum of Months 454.00000 27.00017 32.32239 0.32225 7.19660
Maximum of Months 514.00000 27.01056 42.38311 1.02796 27.33590



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00010 32.51564 0.77674 17.90524
February 454.00000 27.00091 33.44975 0.82014 19.38889
March 514.00000 27.00055 33.56145 0.85097 20.40855
April 485.00000 27.00065 35.87030 0.93081 23.34313
May 508.00000 27.00014 42.25037 0.26926 6.55327
June 496.00000 27.00226 40.23254 0.28121 6.68039
July 497.00000 27.00146 39.25715 0.29560 6.84911
August 514.00000 27.01686 38.45726 0.31858 7.15989
September 485.00000 27.00010 42.78995 0.26527 6.51600
October 502.00000 27.00177 38.12067 0.93132 23.38737
November 489.00000 27.00067 35.02999 0.88220 21.51322
December 497.00000 27.00020 33.09665 0.84621 20.26181
           
Annual Sum or Average 5943.00000 27.00219 37.07244 0.62026 14.94530
Minimum of Months 454.00000 27.00010 32.51564 0.26527 6.51600
Maximum of Months 514.00000 27.01686 42.78995 0.93132 23.38737



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.96404 32.67272 0.71816 16.27884
February 454.00000 27.00092 33.52190 0.77887 18.17017
March 514.00000 27.00058 33.59604 0.82053 19.46733
April 485.00000 27.00049 35.90196 0.92661 23.23577
May 508.00000 27.00023 42.13121 0.28987 6.82890
June 496.00000 27.00239 40.19954 0.30794 7.04561
July 497.00000 27.00156 39.26242 0.32203 7.22579
August 514.00000 27.00837 38.48488 0.34055 7.49377
September 485.00000 27.00011 42.69665 0.28032 6.72448
October 502.00000 27.00183 38.12539 0.93303 23.51889
November 489.00000 27.00070 35.07564 0.84957 20.40563
December 497.00000 27.00023 33.13825 0.79729 18.68742
           
Annual Sum or Average 5943.00000 26.99844 37.08670 0.61188 14.54440
Minimum of Months 454.00000 26.96404 32.67272 0.28032 6.72448
Maximum of Months 514.00000 27.00837 42.69665 0.93303 23.51889



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00000 41.12180 1.15862 33.25791
February 454.00000 27.00000 40.91397 1.30096 40.32110
March 514.00000 27.00000 40.81080 1.43623 47.45321
April 485.00000 27.00000 40.76072 1.56650 54.52038
May 508.00000 27.00000 40.96818 0.55859 11.56118
June 496.00000 27.00000 40.77820 0.77399 17.63039
July 497.00000 27.00000 40.77875 0.98995 25.70654
August 514.00000 27.00000 40.77244 1.20102 35.30160
September 485.00000 27.00000 40.92490 0.61759 13.02938
October 502.00000 27.00000 40.87611 1.34167 42.43218
November 489.00000 27.00000 40.85137 1.47590 49.59360
December 497.00000 27.00000 40.88121 1.59723 56.19421
           
Annual Sum or Average 5943.00000 27.00000 40.86965 1.16706 35.53315
Minimum of Months 454.00000 27.00000 40.76072 0.55859 11.56118
Maximum of Months 514.00000 27.00000 41.12180 1.59723 56.19421



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.58370 37.95974 0.48807 10.84236
February 454.00000 24.55821 46.28585 0.53778 11.83523
March 514.00000 24.45640 45.29980 0.50934 11.17078
April 485.00000 24.54269 57.01624 0.61094 13.54888
May 508.00000 24.55133 65.15417 -0.1775 6.96715
June 496.00000 24.49839 64.61808 -0.1944 6.85436
July 497.00000 24.65108 64.17743 -0.1402 7.08164
August 514.00000 24.54897 62.00863 -0.1715 7.03155
September 485.00000 24.62185 62.70409 -0.1508 7.11354
October 502.00000 24.67419 57.25529 0.66570 15.52567
November 489.00000 24.67428 47.77258 0.59434 13.33379
December 497.00000 24.65947 42.86751 0.55088 12.39234
           
Annual Sum or Average 5943.00000 24.58469 54.47478 0.25716 10.28522
Minimum of Months 454.00000 24.45640 37.95974 -0.1944 6.85436
Maximum of Months 514.00000 24.67428 65.15417 0.66570 15.52567



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.04208 38.07606 0.37160 8.39551
February 454.00000 24.13334 41.78295 0.42451 9.20630
March 514.00000 24.11954 41.02161 0.42492 9.09546
April 485.00000 24.10994 46.37808 0.47147 9.78892
May 508.00000 24.10802 49.34900 -0.3917 8.51365
June 496.00000 24.04402 49.26503 -0.4035 8.53812
July 497.00000 24.07126 48.95633 -0.3888 8.24890
August 514.00000 24.07151 48.91499 -0.3786 8.04376
September 485.00000 24.11494 49.23430 -0.3861 8.41014
October 502.00000 24.18783 46.71460 0.49406 10.31214
November 489.00000 24.24742 43.39671 0.48145 10.14058
December 497.00000 24.20608 40.03137 0.44381 9.47068
           
Annual Sum or Average 5943.00000 24.12094 45.27787 0.09358 9.00761
Minimum of Months 454.00000 24.04208 38.07606 -0.4035 8.04376
Maximum of Months 514.00000 24.24742 49.34900 0.49406 10.31214



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.20435 40.77675 0.15506 6.19790
February 454.00000 23.40864 44.44211 0.23289 6.88348
March 514.00000 23.54443 43.55958 0.26773 7.13791
April 485.00000 23.87399 48.16664 0.39009 8.49344
May 508.00000 23.91986 50.34276 -0.4735 10.11907
June 496.00000 23.89417 50.30397 -0.4798 10.20158
July 497.00000 23.89056 50.28507 -0.4828 10.30011
August 514.00000 23.93392 50.31148 -0.4663 9.92664
September 485.00000 23.85410 50.56235 -0.4957 10.57392
October 502.00000 23.92659 48.15257 0.41336 8.86206
November 489.00000 23.74991 45.74241 0.34023 7.80999
December 497.00000 23.43596 43.07287 0.23461 6.93632
           
Annual Sum or Average 5943.00000 23.72153 47.15537 -0.0333 8.63034
Minimum of Months 454.00000 23.20435 40.77675 -0.4957 6.19790
Maximum of Months 514.00000 23.93392 50.56235 0.41336 10.57392



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.18353 42.92954 -0.0973 7.10536
February 454.00000 22.59506 46.34517 0.03682 7.46034
March 514.00000 22.97872 44.82382 0.13056 7.20214
April 485.00000 23.75528 48.52810 0.36633 8.30574
May 508.00000 24.02383 49.64310 -0.4219 9.12620
June 496.00000 24.02276 49.44517 -0.4170 8.94613
July 497.00000 24.03133 49.46354 -0.4177 9.00013
August 514.00000 24.03878 49.61428 -0.4141 8.96194
September 485.00000 23.94852 50.07251 -0.4524 9.68942
October 502.00000 23.86903 48.15614 0.40562 9.01441
November 489.00000 23.18794 47.37835 0.20401 6.88951
December 497.00000 22.54426 45.11850 0.01485 6.94274
           
Annual Sum or Average 5943.00000 23.43703 47.62695 -0.0905 8.22498
Minimum of Months 454.00000 22.18353 42.92954 -0.4524 6.88951
Maximum of Months 514.00000 24.03878 50.07251 0.40562 9.68942



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.99560 39.41091 0.09726 6.79637
February 454.00000 23.39557 42.29476 0.22245 7.44473
March 514.00000 23.66227 41.23724 0.28891 7.75442
April 485.00000 24.05445 45.62760 0.44474 9.36861
May 508.00000 24.36120 47.78035 -0.2831 7.24153
June 496.00000 24.31801 47.29230 -0.2755 7.01797
July 497.00000 24.39015 47.14560 -0.2478 6.89061
August 514.00000 24.27441 47.37503 -0.2824 7.05021
September 485.00000 24.33055 47.98514 -0.3051 7.51783
October 502.00000 24.23647 45.87965 0.50278 10.73878
November 489.00000 23.88242 43.57028 0.36681 8.31408
December 497.00000 23.53332 40.98966 0.25077 7.38783
           
Annual Sum or Average 5943.00000 23.95624 44.72573 0.06288 7.79129
Minimum of Months 454.00000 22.99560 39.41091 -0.3051 6.79637
Maximum of Months 514.00000 24.39015 47.98514 0.50278 10.73878



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.30824 38.43314 0.18654 7.45330
February 454.00000 23.54402 41.62533 0.27775 8.04661
March 514.00000 23.64746 40.75017 0.31358 8.57133
April 485.00000 23.98962 45.41204 0.45991 9.96366
May 508.00000 24.41678 47.29107 -0.2176 7.20601
June 496.00000 24.31218 47.06381 -0.2389 6.93141
July 497.00000 24.37536 46.99856 -0.2198 7.03515
August 514.00000 24.21548 47.37871 -0.2766 7.23664
September 485.00000 24.37996 47.56811 -0.2554 7.72587
October 502.00000 24.25128 45.51445 0.53097 11.67082
November 489.00000 23.91089 43.17064 0.39487 9.04377
December 497.00000 23.38425 41.06120 0.23066 7.56160
           
Annual Sum or Average 5943.00000 23.98051 44.36764 0.09658 8.20020
Minimum of Months 454.00000 23.30824 38.43314 -0.2766 6.93141
Maximum of Months 514.00000 24.41678 47.56811 0.53097 11.67082



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.87495 36.79597 0.34580 9.57318
February 454.00000 23.98265 40.24798 0.40402 10.10897
March 514.00000 23.83924 40.26721 0.35692 9.20739
April 485.00000 24.14151 45.17482 0.48212 10.24597
May 508.00000 24.36280 47.75402 -0.2795 7.23128
June 496.00000 24.29841 47.39383 -0.2894 7.17842
July 497.00000 24.38146 47.18623 -0.2535 6.97905
August 514.00000 24.31879 47.15608 -0.2508 6.88817
September 485.00000 24.46345 47.38492 -0.2264 7.32220
October 502.00000 24.50801 44.67322 0.61990 14.01509
November 489.00000 24.39940 41.57989 0.54919 12.39161
December 497.00000 24.09961 39.00840 0.43927 10.97874
           
Annual Sum or Average 5943.00000 24.22307 43.73798 0.15516 9.32912
Minimum of Months 454.00000 23.83924 36.79597 -0.2894 6.88817
Maximum of Months 514.00000 24.50801 47.75402 0.61990 14.01509



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.68438 37.03273 0.30556 8.57241
February 454.00000 24.18778 39.56434 0.47279 11.01564
March 514.00000 24.35438 38.63869 0.53393 12.02570
April 485.00000 24.59154 43.42336 0.68751 15.71519
May 508.00000 24.51148 46.84921 -0.1429 6.61153
June 496.00000 24.51314 46.31062 -0.0953 6.41706
July 497.00000 24.63718 45.96985 -0.0352 6.54738
August 514.00000 24.53670 46.06583 -0.0313 6.26674
September 485.00000 24.52099 46.86844 -0.1482 6.83795
October 502.00000 24.57944 44.28197 0.66642 15.18661
November 489.00000 24.53131 41.05428 0.60346 13.44859
December 497.00000 24.51200 37.73510 0.56634 12.90727
           
Annual Sum or Average 5943.00000 24.43086 42.83328 0.27961 10.10526
Minimum of Months 454.00000 23.68438 37.03273 -0.1482 6.26674
Maximum of Months 514.00000 24.63718 46.86844 0.68751 15.71519



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.78276 42.78347 -0.2076 7.96450
February 454.00000 22.25976 45.45894 -0.0611 7.74712
March 514.00000 22.69927 44.18690 0.04735 7.16457
April 485.00000 23.74384 47.79522 0.34972 8.24736
May 508.00000 24.31334 49.10680 -0.3122 7.58687
June 496.00000 24.33402 48.15047 -0.2936 7.33423
July 497.00000 24.42201 48.51504 -0.2659 7.29052
August 514.00000 24.31323 48.82317 -0.3079 7.54909
September 485.00000 24.22789 49.78228 -0.3566 8.20735
October 502.00000 24.01243 48.11422 0.43823 9.87305
November 489.00000 22.99974 46.73029 0.14533 6.78295
December 497.00000 22.22550 45.02803 -0.0738 7.41877
           
Annual Sum or Average 5943.00000 23.45236 47.04226 -0.0759 7.76279
Minimum of Months 454.00000 21.78276 42.78347 -0.3566 6.78295
Maximum of Months 514.00000 24.42201 49.78228 0.43823 9.87305



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 22.25988 41.03720 -0.0775 7.29282
February 385.00000 22.73441 43.26909 0.06578 7.45930
March 433.00000 23.15607 41.97552 0.17471 8.25940
April 410.00000 24.03860 46.13100 0.44732 10.22876
May 430.00000 24.51500 48.01853 -0.2038 7.56694
June 418.00000 24.48295 47.25007 -0.2083 7.17545
July 422.00000 24.61059 47.51842 -0.1684 7.41653
August 433.00000 24.44981 47.94049 -0.2306 7.41726
September 410.00000 24.40751 48.62431 -0.2671 8.42214
October 427.00000 24.21615 46.89734 0.50868 11.82420
November 417.00000 23.45498 44.57917 0.26825 7.90569
December 422.00000 22.55606 43.46425 0.01522 7.56746
           
Annual Sum or Average 5034.00000 23.74546 45.56469 0.02616 8.21269
Minimum of Months 385.00000 22.25988 41.03720 -0.2671 7.17545
Maximum of Months 433.00000 24.61059 48.62431 0.50868 11.82420



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.61772 37.94770 0.27717 9.24366
February 454.00000 23.70964 41.26944 0.32824 9.62446
March 514.00000 23.49754 41.71548 0.26211 8.66888
April 485.00000 24.03278 46.59482 0.43640 9.69532
May 508.00000 24.32156 49.04410 -0.3052 7.55117
June 496.00000 24.30557 48.29994 -0.3102 7.51293
July 497.00000 24.40782 48.57501 -0.2722 7.35651
August 514.00000 24.37038 48.47996 -0.2686 7.26903
September 485.00000 24.42635 48.77287 -0.2510 7.68496
October 502.00000 24.49102 45.92640 0.60874 13.96382
November 489.00000 24.26017 42.51429 0.50449 11.78193
December 497.00000 23.79765 40.56338 0.35371 10.52191
           
Annual Sum or Average 5943.00000 24.10463 44.99703 0.11083 9.22943
Minimum of Months 454.00000 23.49754 37.94770 -0.3102 7.26903
Maximum of Months 514.00000 24.49102 49.04410 0.60874 13.96382



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.53640 40.34722 0.00010 7.43817
February 454.00000 22.99446 42.90608 0.14506 8.25031
March 514.00000 23.27771 42.04760 0.21696 8.28995
April 485.00000 24.18280 45.88851 0.50211 11.24803
May 508.00000 24.43186 48.30387 -0.2190 7.13547
June 496.00000 24.45824 47.44082 -0.1950 6.99949
July 497.00000 24.55651 47.69076 -0.1685 7.07191
August 514.00000 24.45966 47.85987 -0.1929 6.88685
September 485.00000 24.39311 48.65266 -0.2454 7.65799
October 502.00000 24.29564 46.57517 0.54838 12.34932
November 489.00000 23.56463 44.47574 0.31118 8.34444
December 497.00000 22.94490 42.53118 0.12679 7.99057
           
Annual Sum or Average 5943.00000 23.84645 45.40422 0.06757 8.29755
Minimum of Months 454.00000 22.53640 40.34722 -0.2454 6.88685
Maximum of Months 514.00000 24.55651 48.65266 0.54838 12.34932



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.36417 43.87438 -0.3404 10.41867
February 454.00000 21.80609 46.71312 -0.1856 9.78911
March 514.00000 22.32558 45.01414 -0.0527 8.42626
April 485.00000 23.56981 48.23760 0.31337 8.29948
May 508.00000 24.35623 48.86814 -0.2787 7.42409
June 496.00000 24.38270 47.76288 -0.2544 7.13961
July 497.00000 24.47782 48.17898 -0.2251 7.19824
August 514.00000 24.35356 48.57752 -0.2745 7.40060
September 485.00000 24.27013 49.72270 -0.3285 8.20465
October 502.00000 23.92356 48.38870 0.42429 10.24312
November 489.00000 22.52003 48.00373 0.02568 7.30229
December 497.00000 21.76925 46.34711 -0.2066 9.13065
           
Annual Sum or Average 5943.00000 23.27002 47.46919 -0.1157 8.40568
Minimum of Months 454.00000 21.36417 43.87438 -0.3404 7.13961
Maximum of Months 514.00000 24.47782 49.72270 0.42429 10.41867



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.78559 42.37495 -0.2072 8.87894
February 454.00000 22.34636 44.81010 -0.0295 8.76794
March 514.00000 22.92706 42.93765 0.11800 9.05389
April 485.00000 23.92893 46.49660 0.43883 10.34140
May 508.00000 24.46140 47.96176 -0.1792 7.33390
June 496.00000 24.44333 47.12274 -0.1732 6.90720
July 497.00000 24.55775 47.42482 -0.1393 7.24727
August 514.00000 24.41200 47.88119 -0.2001 7.17564
September 485.00000 24.37311 48.71577 -0.2447 8.25726
October 502.00000 24.11006 47.12587 0.50326 12.10979
November 489.00000 23.11956 45.92113 0.18994 7.76236
December 497.00000 22.16529 44.86207 -0.0928 8.57149
           
Annual Sum or Average 5943.00000 23.56061 46.13689 -0.0021 8.52913
Minimum of Months 454.00000 21.78559 42.37495 -0.2447 6.90720
Maximum of Months 514.00000 24.55775 48.71577 0.50326 12.10979



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.15581 39.23874 0.14320 9.38244
February 454.00000 23.26472 42.47636 0.21072 9.96000
March 514.00000 23.14824 42.56555 0.16995 9.29363
April 485.00000 23.88384 47.03124 0.40666 9.69076
May 508.00000 24.36160 48.81830 -0.2723 7.43113
June 496.00000 24.35379 47.90842 -0.2713 7.29859
July 497.00000 24.46087 48.24638 -0.2325 7.26739
August 514.00000 24.40746 48.25616 -0.2352 7.19810
September 485.00000 24.44160 48.77948 -0.2285 7.82333
October 502.00000 24.42762 46.14761 0.60251 14.19832
November 489.00000 23.98703 43.34650 0.43028 11.09174
December 497.00000 23.36888 41.80871 0.23317 10.52332
           
Annual Sum or Average 5943.00000 23.94191 45.40045 0.07752 9.25314
Minimum of Months 454.00000 23.14824 39.23874 -0.2723 7.19810
Maximum of Months 514.00000 24.46087 48.81830 0.60251 14.19832



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.06157 41.42674 -0.1332 8.68354
February 454.00000 22.51705 44.12290 0.02446 9.24837
March 514.00000 22.88473 42.88998 0.11939 8.85026
April 485.00000 23.98399 46.38557 0.46325 11.01060
May 508.00000 24.42369 48.19006 -0.2000 7.19356
June 496.00000 24.45864 47.19570 -0.1700 6.99219
July 497.00000 24.55199 47.50533 -0.1461 7.12258
August 514.00000 24.46650 47.70734 -0.1693 6.91725
September 485.00000 24.37116 48.71978 -0.2352 7.92312
October 502.00000 24.17987 46.86867 0.53087 12.42688
November 489.00000 23.12088 45.59763 0.20488 8.08989
December 497.00000 22.46114 43.78063 -0.0016 8.68521
           
Annual Sum or Average 5943.00000 23.63067 45.86996 0.02297 8.58463
Minimum of Months 454.00000 22.06157 41.42674 -0.2352 6.91725
Maximum of Months 514.00000 24.55199 48.71978 0.53087 12.42688



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.577395E+11 112138.29 19-JAN-16:40 284.67 0.355434E+12 0.00 0.413173E+12 2.14 7.58 20-JAN-06:04 0.00 0.00
February 0.761419E+11 114048.59 24-FEB-17:00 330.41 0.486553E+12 0.00 0.562695E+12 2.91 7.43 28-FEB-06:03 0.00 0.00
March 0.926952E+11 127721.78 28-MAR-05:04 423.69 0.584096E+12 0.00 0.676791E+12 3.27 7.66 28-MAR-05:04 0.00 0.00
April 0.134024E+12 127958.77 14-APR-05:04 557.36 0.879633E+12 0.00 0.101366E+13 4.64 7.67 14-APR-05:04 0.00 0.00
May 0.180544E+12 158928.27 22-MAY-05:03 553.81 0.117934E+13 0.00 0.135988E+13 4.69 7.38 09-MAY-05:04 0.00 0.00
June 0.187638E+12 132476.30 19-JUN-10:40 596.32 0.121041E+13 0.00 0.139805E+13 5.07 7.30 07-JUN-05:05 0.00 0.00
July 0.198187E+12 138234.56 26-JUL-05:02 654.90 0.124908E+13 0.00 0.144727E+13 5.18 7.26 14-JUL-05:04 0.00 0.00
August 0.200989E+12 133935.58 17-AUG-14:10 676.02 0.128604E+13 0.00 0.148703E+13 5.39 7.33 29-AUG-05:04 0.00 0.00
September 0.178656E+12 131951.42 18-SEP-10:10 547.86 0.115971E+13 0.00 0.133836E+13 4.74 7.44 22-SEP-05:04 0.00 0.00
October 0.164071E+12 133726.79 21-OCT-05:04 562.86 0.106032E+13 0.00 0.122439E+13 4.59 7.37 13-OCT-05:02 0.00 0.00
November 0.110958E+12 142922.03 01-NOV-05:04 461.02 0.703896E+12 0.00 0.814854E+12 3.75 7.52 29-NOV-06:04 0.00 0.00
December 0.780601E+11 131532.17 12-DEC-06:04 374.89 0.491178E+12 0.00 0.569238E+12 2.85 7.59 12-DEC-06:04 0.00 0.00
                         
Annual Sum or Average 0.165970E+13     6023.81 0.106457E+14 0.00 0.123054E+14 4.11     0.00 0.00
Minimum of Months 0.577395E+11 112138.29   284.67 0.355434E+12 0.00 0.413173E+12 2.14 7.26   0.00 0.00
Maximum of Months 0.200989E+12 158928.27   676.02 0.128604E+13 0.00 0.148703E+13 5.39 7.67   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.400406E+09 112138.29 19-JAN-16:40 1.03 0.283095E+10 0.00 0.323135E+10 0.01 7.58 20-JAN-06:04 0.00 0.00
February 0.143241E+10 114048.59 24-FEB-17:00 3.71 0.101592E+11 0.00 0.115916E+11 0.04 7.41 03-FEB-06:05 0.00 0.00
March 0.123094E+10 127721.78 28-MAR-05:04 3.07 0.868939E+10 0.00 0.992033E+10 0.03 7.66 28-MAR-05:04 0.00 0.00
April 0.762516E+10 127958.77 14-APR-05:04 18.95 0.525638E+11 0.00 0.601889E+11 0.18 7.67 14-APR-05:04 0.00 0.00
May 0.461531E+11 158928.27 22-MAY-05:03 111.38 0.312422E+12 0.00 0.358575E+12 1.01 7.38 09-MAY-05:04 0.00 0.00
June 0.560627E+11 132476.30 19-JUN-10:40 131.31 0.375447E+12 0.00 0.431509E+12 1.22 7.30 07-JUN-05:05 0.00 0.00
July 0.662900E+11 138234.56 26-JUL-05:02 151.99 0.440945E+12 0.00 0.507235E+12 1.36 7.26 14-JUL-05:04 0.00 0.00
August 0.718832E+11 133935.58 17-AUG-14:10 165.79 0.480756E+12 0.00 0.552639E+12 1.49 7.33 29-AUG-05:04 0.00 0.00
September 0.490589E+11 131951.42 18-SEP-10:10 115.75 0.332061E+12 0.00 0.381120E+12 1.09 7.44 22-SEP-05:04 0.00 0.00
October 0.435979E+11 133726.79 21-OCT-05:04 102.40 0.295042E+12 0.00 0.338640E+12 0.93 7.37 13-OCT-05:02 0.00 0.00
November 0.124946E+11 142922.03 01-NOV-05:04 29.92 0.853350E+11 0.00 0.978297E+11 0.28 7.52 29-NOV-06:04 0.00 0.00
December 0.513469E+10 131532.17 12-DEC-06:04 12.90 0.354413E+11 0.00 0.405760E+11 0.12 7.59 12-DEC-06:04 0.00 0.00
                         
Annual Sum or Average 0.361364E+12     848.20 0.243169E+13 0.00 0.279306E+13 0.65     0.00 0.00
Minimum of Months 0.400406E+09 112138.29   1.03 0.283095E+10 0.00 0.323135E+10 0.01 7.26   0.00 0.00
Maximum of Months 0.718832E+11 158928.27   165.79 0.480756E+12 0.00 0.552639E+12 1.49 7.67   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.122244E+11 744.00 12476.23 01-JAN-08:33 39706.57 19-JAN-17:00 21.21 19.16 2.81
February 0.183251E+11 672.00 12476.23 01-FEB-00:10 67843.00 27-FEB-17:00 24.72 19.63 2.81
March 0.243751E+11 744.00 12476.23 01-MAR-00:10 107129.07 31-MAR-24:00 28.57 20.54 2.81
April 0.310201E+11 720.00 12476.23 01-APR-00:10 131046.40 28-APR-16:10 34.28 22.99 2.81
May 0.334163E+11 744.00 12476.23 01-MAY-00:03 58376.83 31-MAY-23:20 30.89 27.33 2.81
June 0.323384E+11 720.00 12476.23 01-JUN-00:10 87194.27 30-JUN-23:53 34.89 28.40 2.81
July 0.334163E+11 744.00 12476.23 01-JUL-00:10 113293.22 31-JUL-23:53 38.41 29.09 2.81
August 0.334163E+11 744.00 12476.23 01-AUG-00:03 133359.98 07-AUG-13:10 41.00 28.94 2.81
September 0.323384E+11 720.00 12476.23 01-SEP-00:05 57045.37 30-SEP-23:50 30.16 26.66 2.81
October 0.317924E+11 744.00 12476.23 01-OCT-00:10 81870.18 31-OCT-24:00 31.43 25.26 2.81
November 0.267241E+11 720.00 12476.23 01-NOV-00:10 100021.45 02-NOV-15:10 29.62 21.34 2.81
December 0.234289E+11 744.00 12476.23 01-DEC-10:30 126603.29 14-DEC-17:00 30.87 20.33 2.81
                   
Annual Sum or Average 0.332816E+12 8760.00         31.38 24.17 2.81
Minimum of Months 0.122244E+11 672.00 12476.23   39706.57   21.21 19.16 2.81
Maximum of Months 0.334163E+11 744.00 12476.23   133359.98   41.00 29.09 2.81



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.515143E+10 205.56 21552.64 02-JAN-10:30 1102317.68 02-JAN-16:20 21.80 21.26 24.61
February 0.665785E+10 274.57 21552.64 01-FEB-13:10 1075578.46 23-FEB-11:40 22.29 21.47 33.64
March 0.927307E+10 343.02 21552.64 06-MAR-08:50 1133166.73 28-MAR-05:06 22.29 21.40 37.98
April 0.196500E+11 487.17 21552.64 01-APR-03:02 1151631.61 18-APR-15:30 23.08 21.69 53.54
May 0.424038E+11 553.81 21552.64 01-MAY-01:03 1036663.59 22-MAY-05:05 26.06 24.31 53.14
June 0.450818E+11 596.32 21552.64 01-JUN-03:02 1032343.01 15-JUN-15:10 26.40 24.54 56.43
July 0.508132E+11 654.90 21552.64 01-JUL-00:10 1040777.85 20-JUL-13:50 27.35 25.49 57.59
August 0.515724E+11 675.52 21552.64 01-AUG-00:03 1037533.60 21-AUG-14:40 26.80 24.88 61.69
September 0.422869E+11 547.86 21552.64 01-SEP-00:05 1046187.85 01-SEP-15:50 26.62 24.84 52.07
October 0.328083E+11 538.89 21552.64 02-OCT-09:10 1440742.63 01-OCT-07:33 25.02 23.42 51.79
November 0.129166E+11 395.97 21552.64 01-NOV-01:53 1128275.34 08-NOV-11:40 22.93 21.82 44.20
December 0.954483E+10 288.87 21552.64 08-DEC-11:10 1092777.82 08-DEC-17:00 22.14 21.40 33.49
                   
Annual Sum or Average 0.328160E+12 5562.47         24.41 23.05 46.73
Minimum of Months 0.515143E+10 205.56 21552.64   1032343.01   21.80 21.26 24.61
Maximum of Months 0.515724E+11 675.52 21552.64   1440742.63   27.35 25.49 61.69



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.103453E+09 1.33 21552.64 19-JAN-10:30 957080.88 19-JAN-16:40 21.80 21.80 0.13
February 0.284495E+09 3.67 21552.64 24-FEB-10:50 962996.12 24-FEB-17:00 22.29 22.27 0.40
March 0.245700E+09 3.17 21552.64 06-MAR-13:00 972474.57 07-MAR-15:10 22.29 22.28 0.31
April 0.172895E+10 22.28 21552.64 14-APR-10:20 1017470.61 24-APR-11:00 23.08 22.99 2.20
May 0.117932E+11 151.99 21552.64 01-MAY-08:20 1036663.59 22-MAY-05:05 26.06 25.46 13.67
June 0.175667E+11 226.41 21552.64 01-JUN-05:05 1032343.01 15-JUN-15:10 26.40 25.48 18.87
July 0.235646E+11 303.71 21552.64 01-JUL-06:20 1040777.85 20-JUL-13:50 27.35 26.18 23.09
August 0.214587E+11 276.57 21552.64 01-AUG-05:04 1037533.60 21-AUG-14:40 26.80 25.71 22.45
September 0.153938E+11 198.40 21552.64 01-SEP-05:02 1046187.85 01-SEP-15:50 26.62 25.83 16.58
October 0.130803E+11 168.58 21552.64 02-OCT-14:10 1034276.38 23-OCT-13:20 25.02 24.36 13.80
November 0.292124E+10 37.65 21552.64 01-NOV-05:04 1032311.05 02-NOV-14:40 22.93 22.77 3.48
December 0.109918E+10 14.17 21552.64 11-DEC-14:50 1000397.12 12-DEC-16:40 22.14 22.09 1.37
                   
Annual Sum or Average 0.109240E+12 1407.93         24.41 23.94 9.77
Minimum of Months 0.103453E+09 1.33 21552.64   957080.88   21.80 21.80 0.13
Maximum of Months 0.235646E+11 303.71 21552.64   1046187.85   27.35 26.18 23.09



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.212664E+11 0.00 232.26 835402.57 10-JAN-06:02 0.00 25.84 42.96 0.04 0.00 0.01 0.58 10-JAN-06:02
February 0.102685E+11 0.00 122.18 791024.58 06-FEB-06:02 0.00 19.73 30.10 0.02 0.00 0.00 0.55 06-FEB-06:02
March 0.858775E+10 0.00 100.82 674912.12 11-MAR-06:02 0.00 21.26 28.96 0.01 0.00 0.00 0.47 11-MAR-06:02
April 0.141620E+09 0.00 8.39 24618.72 03-APR-16:50 0.00 26.95 27.60 0.00 0.00 0.00 0.02 03-APR-16:50
May 0.00 0.00 0.00 0.00 01-MAY-00:03 0.00 32.02 32.02 0.00 0.00 0.00 0.00 01-MAY-00:03
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 32.02 32.02 0.00 0.00 0.00 0.00 01-JUN-00:10
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 32.02 32.02 0.00 0.00 0.00 0.00 01-JUL-00:10
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 32.02 32.02 0.00 0.00 0.00 0.00 01-AUG-00:03
September 0.00 0.00 0.00 0.00 01-SEP-00:05 0.00 32.02 32.02 0.00 0.00 0.00 0.00 01-SEP-00:05
October 43502604.04 0.00 8.29 4622.43 28-OCT-06:50 0.00 31.62 32.18 0.00 0.00 0.00 0.00 28-OCT-06:50
November 0.773347E+09 0.00 48.11 98675.35 16-NOV-06:02 0.00 25.44 29.14 0.00 0.00 0.00 0.07 16-NOV-06:02
December 0.146308E+11 0.00 175.54 804124.28 21-DEC-06:01 0.00 21.20 34.69 0.02 0.00 0.00 0.55 21-DEC-06:01
                           
Annual Sum or Average 0.557120E+11 0.00 695.59     0.00 27.73 32.18 0.01 0.00 0.00    
Minimum of Months 0.00 0.00 0.00 0.00   0.00 19.73 27.60 0.00 0.00 0.00 0.00  
Maximum of Months 0.212664E+11 0.00 232.26 835402.57   0.00 32.02 42.96 0.04 0.00 0.01 0.58  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 21.21 21.21 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 24.72 24.72 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 28.57 28.57 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 34.28 34.28 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:03 0.00 30.89 30.89 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 34.89 34.89 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 38.41 38.41 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 41.00 41.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:05 0.00 30.16 30.16 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 31.43 31.43 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 29.62 29.62 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 30.87 30.87 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 31.38 31.38 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 21.21 21.21 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 41.00 41.00 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.394737E+11 0.00 268.00 0.299407E+11 0.00 0.00 0.00 0.00 144942.67 31-JAN-06:02 132349.35 30-JAN-06:02 0.00 0.00 0.00
February 0.565043E+11 0.00 321.07 0.413368E+11 0.00 0.00 0.00 0.00 131220.89 28-FEB-06:03 119282.02 27-FEB-06:03 0.00 0.00 0.00
March 0.704633E+11 0.00 413.18 0.557049E+11 0.00 0.00 0.00 0.00 136065.61 27-MAR-05:02 128614.96 27-MAR-05:02 0.00 0.00 0.00
April 0.113887E+12 0.00 545.30 0.910678E+11 0.00 0.00 0.00 0.00 145596.59 24-APR-05:02 135830.13 24-APR-05:02 0.00 0.00 0.00
May 0.142552E+12 0.00 521.85 0.111343E+12 0.00 0.00 0.00 0.00 161503.86 22-MAY-05:03 141541.02 30-MAY-05:02 0.00 0.00 0.00
June 0.154763E+12 0.00 569.12 0.123158E+12 0.00 0.00 0.00 0.00 150436.40 26-JUN-05:02 139320.04 26-JUN-05:02 0.00 0.00 0.00
July 0.167088E+12 0.00 612.81 0.131766E+12 0.00 0.00 0.00 0.00 156235.15 05-JUL-05:02 141902.28 05-JUL-05:02 0.00 0.00 0.00
August 0.181643E+12 0.00 647.84 0.144148E+12 0.00 0.00 0.00 0.00 155060.86 14-AUG-05:02 140687.66 14-AUG-05:02 0.00 0.00 0.00
September 0.142557E+12 0.00 508.34 0.105687E+12 0.00 0.00 0.00 0.00 164389.46 05-SEP-05:03 143076.15 05-SEP-05:03 0.00 0.00 0.00
October 0.134102E+12 0.00 531.53 0.106674E+12 0.00 0.00 0.00 0.00 161320.54 10-OCT-05:02 144746.02 10-OCT-05:02 0.00 0.00 0.00
November 0.854992E+11 0.00 447.99 0.691610E+11 0.00 0.00 0.00 0.00 147145.52 01-NOV-05:02 131775.34 02-NOV-05:02 0.00 0.00 0.00
December 0.632382E+11 0.00 360.79 0.501482E+11 0.00 0.00 0.00 0.00 151092.24 11-DEC-06:02 138280.35 11-DEC-06:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.135177E+13 0.00 5747.80 0.106014E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.394737E+11 0.00 268.00 0.299407E+11 0.00 0.00 0.00 0.00 131220.89   119282.02   0.00 0.00 0.00
Maximum of Months 0.181643E+12 0.00 647.84 0.144148E+12 0.00 0.00 0.00 0.00 164389.46   144746.02   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.304851E+12 0.00 257.92 0.224675E+12 0.00 0.00 0.00 0.00 1126680.77 20-JAN-06:02 912951.06 19-JAN-06:03 0.00 0.00 0.00
February 0.435918E+12 0.00 295.39 0.306262E+12 0.00 0.00 0.00 0.00 1201178.75 03-FEB-06:03 1056144.72 27-FEB-06:03 0.00 0.00 0.00
March 0.516071E+12 0.00 361.53 0.389006E+12 0.00 0.00 0.00 0.00 1369653.84 28-MAR-05:02 1185631.54 27-MAR-05:02 0.00 0.00 0.00
April 0.817918E+12 0.00 412.05 0.616538E+12 0.00 0.00 0.00 0.00 1413295.89 29-APR-05:03 1223953.47 29-APR-05:03 0.00 0.00 0.00
May 0.125516E+13 0.00 480.71 0.945060E+12 0.00 0.00 0.00 0.00 1840667.26 22-MAY-03:02 1280958.13 22-MAY-03:02 0.00 0.00 0.00
June 0.129195E+13 0.00 488.09 0.979148E+12 0.00 0.00 0.00 0.00 1451170.00 07-JUN-05:03 1234201.48 28-JUN-05:03 0.00 0.00 0.00
July 0.132969E+13 0.00 495.71 0.975580E+12 0.00 0.00 0.00 0.00 1468541.56 26-JUL-05:02 1245996.05 06-JUL-05:02 0.00 0.00 0.00
August 0.137627E+13 0.00 500.05 0.100783E+13 0.00 0.00 0.00 0.00 1489928.03 29-AUG-05:02 1258988.86 29-AUG-05:02 0.00 0.00 0.00
September 0.123468E+13 0.00 466.67 0.869302E+12 0.00 0.00 0.00 0.00 1601484.65 14-SEP-05:03 1238396.63 14-SEP-05:03 0.00 0.00 0.00
October 0.108876E+13 0.00 455.40 0.820747E+12 0.00 0.00 0.00 0.00 1544797.82 21-OCT-05:02 1237695.21 21-OCT-05:02 0.00 0.00 0.00
November 0.635493E+12 0.00 390.01 0.493183E+12 0.00 0.00 0.00 0.00 1460978.08 01-NOV-05:02 1223874.17 01-NOV-05:02 0.00 0.00 0.00
December 0.440595E+12 0.00 296.35 0.326063E+12 0.00 0.00 0.00 0.00 1386007.70 13-DEC-06:02 1202293.78 12-DEC-06:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.107274E+14 0.00 4899.87 0.795339E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.304851E+12 0.00 257.92 0.224675E+12 0.00 0.00 0.00 0.00 1126680.77   912951.06   0.00 0.00 0.00
Maximum of Months 0.137627E+13 0.00 500.05 0.100783E+13 0.00 0.00 0.00 0.00 1840667.26   1280958.13   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.312397E+11 0.00 253.78 0.227633E+11 0.00 0.00 0.00 0.00 116874.82 19-JAN-15:00 77864.18 19-JAN-15:50 0.00 0.00 0.00
February 0.450116E+11 0.00 290.92 0.314260E+11 0.00 0.00 0.00 0.00 114715.24 28-FEB-06:03 101963.08 28-FEB-06:03 0.00 0.00 0.00
March 0.541084E+11 0.00 359.24 0.405466E+11 0.00 0.00 0.00 0.00 139005.22 27-MAR-05:02 121128.24 27-MAR-05:02 0.00 0.00 0.00
April 0.871330E+11 0.00 409.45 0.665621E+11 0.00 0.00 0.00 0.00 143596.61 27-APR-05:02 142391.83 18-APR-15:00 0.00 0.00 0.00
May 0.140593E+12 0.00 490.03 0.108781E+12 0.00 0.00 0.00 0.00 196911.83 22-MAY-03:02 144830.60 22-MAY-03:02 0.00 0.00 0.00
June 0.146918E+12 0.00 502.02 0.114851E+12 0.00 0.00 0.00 0.00 155712.11 30-JUN-03:02 135745.60 30-JUN-03:02 0.00 0.00 0.00
July 0.150639E+12 0.00 515.39 0.114011E+12 0.00 0.00 0.00 0.00 166592.74 26-JUL-03:02 142193.61 26-JUL-03:02 0.00 0.00 0.00
August 0.154275E+12 0.00 514.69 0.116298E+12 0.00 0.00 0.00 0.00 161579.08 24-AUG-03:02 140410.23 24-AUG-03:02 0.00 0.00 0.00
September 0.134290E+12 0.00 472.21 0.966514E+11 0.00 0.00 0.00 0.00 189813.22 05-SEP-03:02 139051.28 05-SEP-03:02 0.00 0.00 0.00
October 0.117050E+12 0.00 456.72 0.899064E+11 0.00 0.00 0.00 0.00 166670.02 21-OCT-05:02 130118.79 21-OCT-05:02 0.00 0.00 0.00
November 0.637855E+11 0.00 385.28 0.495261E+11 0.00 0.00 0.00 0.00 151289.45 01-NOV-05:02 126441.01 01-NOV-05:02 0.00 0.00 0.00
December 0.441520E+11 0.00 292.61 0.326099E+11 0.00 0.00 0.00 0.00 132746.27 15-DEC-06:03 111558.08 15-DEC-06:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.116920E+13 0.00 4942.34 0.883932E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.312397E+11 0.00 253.78 0.227633E+11 0.00 0.00 0.00 0.00 114715.24   77864.18   0.00 0.00 0.00
Maximum of Months 0.154275E+12 0.00 515.39 0.116298E+12 0.00 0.00 0.00 0.00 196911.83   144830.60   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.204821E+11 0.00 146.17 0.158825E+11 0.00 0.00 0.00 0.00 110691.16 01-JAN-16:12 85566.53 01-JAN-16:53 0.00 0.00 0.00
February 0.243698E+11 0.00 190.24 0.196492E+11 0.00 0.00 0.00 0.00 100526.35 03-FEB-06:03 93983.67 21-FEB-04:03 0.00 0.00 0.00
March 0.326463E+11 0.00 233.67 0.274596E+11 0.00 0.00 0.00 0.00 130456.19 07-MAR-05:03 83078.22 06-MAR-06:04 0.00 0.00 0.00
April 0.507797E+11 0.00 339.56 0.439375E+11 0.00 0.00 0.00 0.00 135678.51 29-APR-05:03 76458.03 24-APR-05:02 0.00 0.00 0.00
May 0.935505E+11 0.00 427.83 0.720369E+11 0.00 0.00 0.00 0.00 163086.64 22-MAY-03:04 100954.03 29-MAY-12:43 0.00 0.00 0.00
June 0.982552E+11 0.00 426.85 0.737793E+11 0.00 0.00 0.00 0.00 163023.10 19-JUN-03:02 85036.75 12-JUN-03:02 0.00 0.00 0.00
July 0.105253E+12 0.00 410.96 0.744623E+11 0.00 0.00 0.00 0.00 168727.85 03-JUL-03:03 83581.38 05-JUL-03:02 0.00 0.00 0.00
August 0.117337E+12 0.00 465.42 0.852203E+11 0.00 0.00 0.00 0.00 156687.93 13-AUG-18:20 87596.00 28-AUG-03:02 0.00 0.00 0.00
September 0.100499E+12 0.00 431.75 0.734065E+11 0.00 0.00 0.00 0.00 160862.39 17-SEP-17:53 91780.84 05-SEP-02:13 0.00 0.00 0.00
October 0.866626E+11 0.00 408.59 0.667716E+11 0.00 0.00 0.00 0.00 161033.56 08-OCT-16:20 85480.16 09-OCT-19:40 0.00 0.00 0.00
November 0.486032E+11 0.00 302.06 0.399271E+11 0.00 0.00 0.00 0.00 144127.58 02-NOV-03:02 79639.58 02-NOV-03:02 0.00 0.00 0.00
December 0.315948E+11 0.00 203.48 0.254428E+11 0.00 0.00 0.00 0.00 134032.76 15-DEC-05:03 84992.29 11-DEC-04:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.810033E+12 0.00 3986.59 0.617976E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.204821E+11 0.00 146.17 0.158825E+11 0.00 0.00 0.00 0.00 100526.35   76458.03   0.00 0.00 0.00
Maximum of Months 0.117337E+12 0.00 465.42 0.852203E+11 0.00 0.00 0.00 0.00 168727.85   100954.03   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.497309E+10 0.117683E+10 744.00 0.486926E+10 0.103829E+09 0.00 0.33 19-JAN-17:00 0.14 05-JAN-08:00 2720.09 19-JAN-17:00 2523.00 01-JAN-17:10 392.39 31-JAN-17:00 715.16 02-JAN-15:00 0.00
February 0.944723E+10 0.211857E+10 672.00 0.926601E+10 0.181221E+09 0.00 0.55 27-FEB-17:00 0.39 17-FEB-07:50 4642.82 27-FEB-17:00 4552.54 26-FEB-17:50 391.98 24-FEB-17:00 1247.28 02-FEB-13:10 0.00
March 0.156457E+11 0.345698E+10 744.00 0.154473E+11 0.198407E+09 0.00 0.86 31-MAR-24:00 0.59 11-MAR-18:00 7684.44 31-MAR-24:00 7684.44 31-MAR-24:00 480.60 07-MAR-15:00 1832.71 30-MAR-13:00 0.00
April 0.203760E+11 0.463499E+10 720.00 0.200781E+11 0.297950E+09 0.00 1.00 28-APR-15:10 0.30 30-APR-23:55 8605.31 28-APR-16:10 8342.76 16-APR-18:20 527.88 24-APR-11:00 2596.23 28-APR-15:00 0.00
May 0.637587E+10 0.184013E+10 744.00 0.588497E+10 0.490903E+09 0.00 0.49 31-MAY-23:20 0.25 13-MAY-06:10 4062.61 31-MAY-23:10 3974.67 31-MAY-24:00 548.37 23-MAY-16:00 1016.11 31-MAY-23:20 0.00
June 0.111765E+11 0.316051E+10 720.00 0.106080E+11 0.568463E+09 0.00 0.70 30-JUN-23:53 0.47 01-JUN-06:00 5855.86 30-JUN-23:53 5842.92 30-JUN-23:57 675.78 29-JUN-15:00 1587.95 29-JUN-14:00 0.00
July 0.166550E+11 0.460955E+10 744.00 0.160060E+11 0.648954E+09 0.00 0.89 31-JUL-23:53 0.69 15-JUL-06:00 7708.72 31-JUL-23:53 7701.35 31-JUL-23:53 668.31 12-JUL-10:00 2274.11 21-JUL-16:00 0.00
August 0.217027E+11 0.578159E+10 744.00 0.210288E+11 0.673925E+09 0.00 1.00 01-AUG-13:40 0.32 31-AUG-24:00 8750.97 07-AUG-13:10 8190.69 30-AUG-18:20 727.09 07-AUG-13:20 2743.80 30-AUG-16:00 0.00
September 0.621027E+10 0.175210E+10 720.00 0.568213E+10 0.528144E+09 0.00 0.49 30-SEP-23:50 0.25 28-SEP-06:10 4018.78 30-SEP-24:00 3994.62 30-SEP-24:00 580.21 18-SEP-14:30 1007.46 09-SEP-17:00 0.00
October 0.113369E+11 0.296179E+10 744.00 0.108974E+11 0.439519E+09 0.00 0.68 31-OCT-24:00 0.43 28-OCT-07:00 5864.34 31-OCT-24:00 5856.67 31-OCT-24:00 680.92 24-OCT-14:10 1561.77 05-OCT-15:00 0.00
November 0.154412E+11 0.347180E+10 720.00 0.151973E+11 0.243854E+09 0.00 0.79 02-NOV-15:00 0.62 15-NOV-07:10 6718.24 07-NOV-16:40 6362.31 06-NOV-17:00 562.17 01-NOV-11:00 1899.20 01-NOV-14:00 0.00
December 0.207021E+11 0.438273E+10 744.00 0.205201E+11 0.181960E+09 0.00 0.98 15-DEC-17:00 0.79 20-DEC-07:40 8642.62 14-DEC-17:00 8244.82 10-DEC-16:55 574.84 12-DEC-15:00 2359.65 13-DEC-15:00 0.00
                                       
Annual Sum or Average 0.160043E+12 0.393476E+11 8760.00 0.155485E+12 0.455713E+10 0.00                         0.00
Minimum of Months 0.497309E+10 0.117683E+10 672.00 0.486926E+10 0.103829E+09 0.00 0.33   0.14   2720.09   2523.00   391.98   715.16   0.00
Maximum of Months 0.217027E+11 0.578159E+10 744.00 0.210288E+11 0.673925E+09 0.00 1.00   0.79   8750.97   8342.76   727.09   2743.80   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.344389E+11 0.837330E+10 744.00 0.334406E+11 0.998270E+09 0.00 0.33 19-JAN-17:00 0.05 10-JAN-07:10 25353.14 19-JAN-17:00 21815.61 19-JAN-17:00 3931.81 31-JAN-17:00 6570.81 19-JAN-16:50 0.00
February 0.801566E+11 0.181915E+11 672.00 0.783604E+11 0.179626E+10 0.00 0.55 27-FEB-17:00 0.29 06-FEB-07:10 43879.35 27-FEB-17:00 41082.70 26-FEB-17:54 3893.25 24-FEB-17:00 11615.53 24-FEB-14:00 0.00
March 0.141024E+12 0.314127E+11 744.00 0.139044E+12 0.197966E+10 0.00 0.84 31-MAR-24:00 0.50 11-MAR-18:00 71583.49 31-MAR-24:00 71583.49 31-MAR-24:00 4792.15 07-MAR-15:00 17456.95 30-MAR-13:00 0.00
April 0.192398E+12 0.438653E+11 720.00 0.189417E+12 0.298091E+10 0.00 1.00 28-APR-15:00 0.28 30-APR-23:55 82278.49 28-APR-16:30 78394.48 16-APR-18:06 5284.04 24-APR-11:00 24810.81 28-APR-15:00 0.00
May 0.588475E+11 0.170226E+11 744.00 0.539934E+11 0.485407E+10 0.00 0.48 31-MAY-23:20 0.24 02-MAY-06:10 38094.17 31-MAY-23:10 37074.20 31-MAY-24:00 5410.34 23-MAY-16:00 9532.28 31-MAY-23:20 0.00
June 0.105778E+12 0.299304E+11 720.00 0.100117E+12 0.566119E+10 0.00 0.70 30-JUN-23:53 0.46 07-JUN-06:10 56578.06 30-JUN-23:53 56439.74 30-JUN-23:57 6711.09 29-JUN-15:00 15188.24 29-JUN-14:00 0.00
July 0.158407E+12 0.438528E+11 744.00 0.151930E+12 0.647700E+10 0.00 0.89 31-JUL-23:53 0.67 11-JUL-21:20 73753.20 31-JUL-23:53 73678.24 31-JUL-23:53 6678.05 12-JUL-10:00 21787.42 21-JUL-16:00 0.00
August 0.207103E+12 0.551616E+11 744.00 0.200367E+12 0.673668E+10 0.00 1.00 01-AUG-13:10 0.29 31-AUG-24:00 83702.75 07-AUG-13:10 78182.02 30-AUG-18:30 7240.74 07-AUG-13:20 26177.16 30-AUG-16:00 0.00
September 0.563009E+11 0.159366E+11 720.00 0.510959E+11 0.520508E+10 0.00 0.47 30-SEP-23:50 0.23 28-SEP-06:10 37081.19 30-SEP-24:00 36806.79 30-SEP-24:00 5770.57 18-SEP-14:30 9292.96 09-SEP-17:00 0.00
October 0.105214E+12 0.275997E+11 744.00 0.100842E+12 0.437230E+10 0.00 0.66 31-OCT-24:00 0.38 28-OCT-07:00 54183.47 31-OCT-24:00 54086.41 31-OCT-24:00 6790.87 24-OCT-14:10 14895.94 05-OCT-15:00 0.00
November 0.140490E+12 0.318227E+11 720.00 0.138059E+12 0.243173E+10 0.00 0.79 02-NOV-15:00 0.57 15-NOV-08:00 64130.56 07-NOV-16:40 60211.89 06-NOV-17:00 5619.58 01-NOV-11:00 18127.21 01-NOV-14:00 0.00
December 0.187037E+12 0.399519E+11 744.00 0.185215E+12 0.182146E+10 0.00 0.97 15-DEC-17:00 0.71 30-DEC-08:00 82202.08 14-DEC-17:00 77842.38 15-DEC-17:00 5740.02 12-DEC-15:00 22493.35 13-DEC-15:00 0.00
                                       
Annual Sum or Average 0.146720E+13 0.363121E+12 8760.00 0.142188E+13 0.453146E+11 0.00                         0.00
Minimum of Months 0.344389E+11 0.837330E+10 672.00 0.334406E+11 0.998270E+09 0.00 0.33   0.05   25353.14   21815.61   3893.25   6570.81   0.00
Maximum of Months 0.207103E+12 0.551616E+11 744.00 0.200367E+12 0.673668E+10 0.00 1.00   0.71   83702.75   78394.48   7240.74   26177.16   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.236933E+10 0.592840E+09 682.65 0.227141E+10 97925473.29 0.00 0.33 19-JAN-17:00 0.00 04-JAN-02:55 2613.96 19-JAN-17:00 2259.25 19-JAN-17:00 396.89 31-JAN-17:00 677.36 19-JAN-16:30 0.00
February 0.720872E+10 0.165428E+10 672.00 0.703024E+10 0.178478E+09 0.00 0.55 27-FEB-17:00 0.10 05-FEB-09:00 4466.71 27-FEB-17:00 4128.76 26-FEB-17:50 390.11 24-FEB-17:00 1180.36 24-FEB-14:00 0.00
March 0.135032E+11 0.303386E+10 744.00 0.133058E+11 0.197389E+09 0.00 0.82 31-MAR-24:00 0.38 12-MAR-07:50 7059.03 31-MAR-24:00 7058.70 31-MAR-24:00 479.52 07-MAR-15:00 1768.20 30-MAR-13:00 0.00
April 0.191085E+11 0.437708E+10 720.00 0.188109E+11 0.297568E+09 0.00 1.00 28-APR-15:20 0.28 30-APR-23:55 8371.64 28-APR-16:10 7960.44 23-APR-18:10 527.61 24-APR-11:00 2521.89 28-APR-15:00 0.00
May 0.605677E+10 0.175342E+10 744.00 0.556897E+10 0.487804E+09 0.00 0.47 31-MAY-23:20 0.23 15-MAY-06:10 3806.14 31-MAY-23:10 3700.23 31-MAY-24:00 547.94 23-MAY-16:00 954.19 31-MAY-23:20 0.00
June 0.107596E+11 0.304736E+10 720.00 0.101927E+11 0.566910E+09 0.00 0.70 30-JUN-23:53 0.44 07-JUN-06:10 5719.90 30-JUN-23:53 5706.24 30-JUN-23:57 674.43 29-JUN-15:00 1557.35 29-JUN-14:00 0.00
July 0.160183E+11 0.444069E+10 744.00 0.153706E+11 0.647697E+09 0.00 0.87 31-JUL-23:53 0.66 15-JUL-06:00 7374.98 31-JUL-23:53 7367.37 31-JUL-23:53 669.65 12-JUL-10:00 2219.97 21-JUL-16:00 0.00
August 0.208622E+11 0.556832E+10 744.00 0.201888E+11 0.673411E+09 0.00 1.00 01-AUG-13:40 0.29 31-AUG-24:00 8445.85 10-AUG-16:00 7952.66 30-AUG-18:20 724.44 07-AUG-13:20 2668.62 30-AUG-16:00 0.00
September 0.576360E+10 0.163406E+10 720.00 0.524122E+10 0.522382E+09 0.00 0.47 30-SEP-23:30 0.22 28-SEP-07:00 3747.99 30-SEP-24:00 3721.50 30-SEP-24:00 579.86 18-SEP-10:40 989.80 09-SEP-17:00 0.00
October 0.104845E+11 0.276271E+10 744.00 0.100473E+11 0.437197E+09 0.00 0.64 31-OCT-24:00 0.31 28-OCT-08:00 5354.86 31-OCT-24:00 5344.35 31-OCT-24:00 680.76 24-OCT-14:10 1523.37 05-OCT-15:00 0.00
November 0.134660E+11 0.307817E+10 720.00 0.132237E+11 0.242294E+09 0.00 0.78 02-NOV-15:00 0.48 16-NOV-07:10 6474.40 07-NOV-16:40 6091.63 06-NOV-17:00 562.86 01-NOV-11:00 1835.32 01-NOV-14:00 0.00
December 0.178015E+11 0.384218E+10 744.00 0.176200E+11 0.181472E+09 0.00 0.97 15-DEC-17:00 0.61 20-DEC-07:10 8282.90 14-DEC-17:00 7860.74 15-DEC-17:00 574.30 12-DEC-15:00 2266.04 13-DEC-15:00 0.00
                                       
Annual Sum or Average 0.143402E+12 0.357850E+11 8698.65 0.138872E+12 0.453053E+10 0.00                         0.00
Minimum of Months 0.236933E+10 0.592840E+09 672.00 0.227141E+10 97925473.29 0.00 0.33   0.00   2613.96   2259.25   390.11   677.36   0.00
Maximum of Months 0.208622E+11 0.556832E+10 744.00 0.201888E+11 0.673411E+09 0.00 1.00   0.66   8445.85   7960.44   724.44   2668.62   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 83.36 0.00 83.36 54.98 327.15 0.00 0.00 0.00
February 98.34 0.00 98.34 76.80 278.24 0.00 0.00 0.00
March 114.09 0.00 114.09 113.39 235.80 0.00 0.00 0.00
April 134.65 0.55 134.10 183.91 140.03 0.00 0.00 0.00
May 152.52 5.58 146.94 311.55 37.54 0.00 0.00 0.00
June 173.44 12.01 161.43 367.95 30.39 0.00 0.00 0.00
July 168.32 6.41 161.90 353.99 19.08 0.00 0.00 0.00
August 150.73 1.19 149.54 318.30 28.23 0.00 0.00 0.00
September 130.20 0.01 130.19 254.60 45.06 0.00 0.00 0.00
October 113.14 0.00 113.14 203.54 87.83 0.00 0.00 0.00
November 85.89 0.00 85.89 88.53 211.76 0.00 0.00 0.00
December 77.49 0.00 77.49 58.56 288.19 0.00 0.00 0.00
                 
Annual Sum or Average 123.64 2.15 121.49 199.57 143.41 0.00 0.00 0.00
Minimum of Months 77.49 0.00 77.49 54.98 19.08 0.00 0.00 0.00
Maximum of Months 173.44 12.01 161.90 367.95 327.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 83.36 0.00 83.36 54.98 327.15 0.00 0.00 0.00
February 98.34 0.00 98.34 76.80 278.24 0.00 0.00 0.00
March 114.09 0.00 114.09 113.39 235.80 0.00 0.00 0.00
April 134.65 0.55 134.09 183.91 140.03 0.00 0.00 0.00
May 152.51 5.58 146.94 311.54 37.54 0.00 0.00 0.00
June 173.44 12.01 161.43 367.95 30.39 0.00 0.00 0.00
July 168.31 6.41 161.90 353.98 19.08 0.00 0.00 0.00
August 150.73 1.19 149.54 318.30 28.23 0.00 0.00 0.00
September 130.19 0.01 130.18 254.60 45.06 0.00 0.00 0.00
October 113.14 0.00 113.14 203.54 87.83 0.00 0.00 0.00
November 85.89 0.00 85.89 88.53 211.76 0.00 0.00 0.00
December 77.49 0.00 77.49 58.56 288.19 0.00 0.00 0.00
                 
Annual Sum or Average 123.64 2.15 121.48 199.57 143.41 0.00 0.00 0.00
Minimum of Months 77.49 0.00 77.49 54.98 19.08 0.00 0.00 0.00
Maximum of Months 173.44 12.01 161.90 367.95 327.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 83.36 0.00 83.36 54.98 327.15 0.00 0.00 0.00
February 98.34 0.00 98.34 76.80 278.24 0.00 0.00 0.00
March 114.09 0.00 114.09 113.39 235.80 0.00 0.00 0.00
April 134.65 0.55 134.10 183.91 140.03 0.00 0.00 0.00
May 152.51 5.58 146.94 311.55 37.54 0.00 0.00 0.00
June 173.44 12.01 161.43 367.95 30.39 0.00 0.00 0.00
July 168.31 6.41 161.90 353.98 19.08 0.00 0.00 0.00
August 150.73 1.19 149.54 318.30 28.23 0.00 0.00 0.00
September 130.20 0.01 130.19 254.60 45.06 0.00 0.00 0.00
October 113.14 0.00 113.14 203.54 87.83 0.00 0.00 0.00
November 85.89 0.00 85.89 88.53 211.76 0.00 0.00 0.00
December 77.49 0.00 77.49 58.56 288.19 0.00 0.00 0.00
                 
Annual Sum or Average 123.64 2.15 121.48 199.57 143.41 0.00 0.00 0.00
Minimum of Months 77.49 0.00 77.49 54.98 19.08 0.00 0.00 0.00
Maximum of Months 173.44 12.01 161.90 367.95 327.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 83.36 0.00 83.36 54.98 327.15 0.00 0.00 0.00
February 98.34 0.00 98.34 76.80 278.24 0.00 0.00 0.00
March 114.09 0.00 114.09 113.39 235.80 0.00 0.00 0.00
April 134.65 0.55 134.09 183.91 140.03 0.00 0.00 0.00
May 152.51 5.58 146.94 311.54 37.54 0.00 0.00 0.00
June 173.44 12.01 161.43 367.95 30.39 0.00 0.00 0.00
July 168.31 6.41 161.90 353.98 19.08 0.00 0.00 0.00
August 150.73 1.19 149.54 318.30 28.23 0.00 0.00 0.00
September 130.19 0.01 130.18 254.60 45.06 0.00 0.00 0.00
October 113.14 0.00 113.14 203.54 87.83 0.00 0.00 0.00
November 85.89 0.00 85.89 88.53 211.76 0.00 0.00 0.00
December 77.49 0.00 77.49 58.56 288.19 0.00 0.00 0.00
                 
Annual Sum or Average 123.64 2.15 121.48 199.57 143.41 0.00 0.00 0.00
Minimum of Months 77.49 0.00 77.49 54.98 19.08 0.00 0.00 0.00
Maximum of Months 173.44 12.01 161.90 367.95 327.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 83.36 0.00 83.36 54.98 327.14 0.00 0.00 0.00
February 98.34 0.00 98.34 76.79 278.23 0.00 0.00 0.00
March 114.08 0.00 114.08 113.39 235.79 0.00 0.00 0.00
April 134.64 0.55 134.09 183.90 140.03 0.00 0.00 0.00
May 152.51 5.58 146.93 311.53 37.53 0.00 0.00 0.00
June 173.43 12.01 161.43 367.93 30.39 0.00 0.00 0.00
July 168.31 6.41 161.89 353.97 19.08 0.00 0.00 0.00
August 150.72 1.19 149.54 318.28 28.23 0.00 0.00 0.00
September 130.19 0.01 130.18 254.59 45.06 0.00 0.00 0.00
October 113.13 0.00 113.13 203.53 87.82 0.00 0.00 0.00
November 85.89 0.00 85.89 88.53 211.75 0.00 0.00 0.00
December 77.49 0.00 77.49 58.56 288.18 0.00 0.00 0.00
                 
Annual Sum or Average 123.63 2.15 121.48 199.56 143.41 0.00 0.00 0.00
Minimum of Months 77.49 0.00 77.49 54.98 19.08 0.00 0.00 0.00
Maximum of Months 173.43 12.01 161.89 367.93 327.14 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 238.37 121.38 116.99 278.47 332.88 0.00 0.00 0.00
February 265.44 128.15 137.29 329.65 280.71 0.00 0.00 0.00
March 312.24 150.59 161.66 424.24 237.63 0.00 0.00 0.00
April 342.65 154.97 187.68 533.59 144.04 0.00 0.00 0.00
May 353.18 153.15 200.03 658.34 40.98 0.00 0.00 0.00
June 358.18 142.05 216.14 691.54 30.91 0.00 0.00 0.00
July 345.34 126.38 218.96 669.30 17.21 0.00 0.00 0.00
August 318.22 109.41 208.81 617.45 25.99 0.00 0.00 0.00
September 281.88 96.91 184.97 519.89 48.23 0.00 0.00 0.00
October 278.56 117.55 161.01 488.12 90.79 0.00 0.00 0.00
November 246.62 125.81 120.81 343.19 212.06 0.00 0.00 0.00
December 194.18 87.96 106.22 237.78 288.99 0.00 0.00 0.00
                 
Annual Sum or Average 294.67 126.13 168.54 483.46 145.17 0.00 0.00 0.00
Minimum of Months 194.18 87.96 106.22 237.78 17.21 0.00 0.00 0.00
Maximum of Months 358.18 154.97 218.96 691.54 332.88 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 238.37 121.38 116.99 278.47 332.88 0.00 0.00 0.00
February 265.44 128.15 137.29 329.65 280.71 0.00 0.00 0.00
March 312.24 150.59 161.66 424.24 237.63 0.00 0.00 0.00
April 342.65 154.97 187.68 533.59 144.04 0.00 0.00 0.00
May 353.18 153.15 200.03 658.34 40.98 0.00 0.00 0.00
June 358.18 142.05 216.14 691.54 30.91 0.00 0.00 0.00
July 345.34 126.38 218.96 669.30 17.21 0.00 0.00 0.00
August 318.22 109.41 208.81 617.45 25.99 0.00 0.00 0.00
September 281.88 96.91 184.97 519.89 48.23 0.00 0.00 0.00
October 278.56 117.55 161.01 488.12 90.79 0.00 0.00 0.00
November 246.62 125.81 120.81 343.19 212.06 0.00 0.00 0.00
December 194.18 87.96 106.22 237.78 288.99 0.00 0.00 0.00
                 
Annual Sum or Average 294.67 126.13 168.54 483.46 145.17 0.00 0.00 0.00
Minimum of Months 194.18 87.96 106.22 237.78 17.21 0.00 0.00 0.00
Maximum of Months 358.18 154.97 218.96 691.54 332.88 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 238.37 121.38 116.99 278.46 332.87 0.00 0.00 0.00
February 265.43 128.14 137.29 329.64 280.71 0.00 0.00 0.00
March 312.24 150.58 161.65 424.23 237.63 0.00 0.00 0.00
April 342.64 154.97 187.67 533.58 144.04 0.00 0.00 0.00
May 353.17 153.14 200.03 658.33 40.98 0.00 0.00 0.00
June 358.18 142.04 216.13 691.53 30.91 0.00 0.00 0.00
July 345.33 126.37 218.96 669.29 17.21 0.00 0.00 0.00
August 318.21 109.40 208.81 617.44 25.99 0.00 0.00 0.00
September 281.88 96.91 184.97 519.88 48.23 0.00 0.00 0.00
October 278.55 117.55 161.01 488.11 90.79 0.00 0.00 0.00
November 246.62 125.81 120.81 343.18 212.06 0.00 0.00 0.00
December 194.17 87.96 106.22 237.78 288.98 0.00 0.00 0.00
                 
Annual Sum or Average 294.67 126.13 168.54 483.45 145.16 0.00 0.00 0.00
Minimum of Months 194.17 87.96 106.22 237.78 17.21 0.00 0.00 0.00
Maximum of Months 358.18 154.97 218.96 691.53 332.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 481.83 343.63 138.20 689.30 296.89 0.00 0.00 0.00
February 436.99 282.86 154.13 638.09 256.42 0.00 0.00 0.00
March 278.98 125.91 153.08 418.42 226.01 0.00 0.00 0.00
April 206.78 48.45 158.33 343.34 143.95 0.00 0.00 0.00
May 158.00 6.71 151.28 326.54 38.78 0.00 0.00 0.00
June 156.07 1.45 154.62 332.24 31.32 0.00 0.00 0.00
July 163.38 3.00 160.38 345.58 18.84 0.00 0.00 0.00
August 192.21 23.07 169.14 406.85 30.59 0.00 0.00 0.00
September 230.62 60.78 169.84 452.31 48.91 0.00 0.00 0.00
October 357.81 186.38 171.43 644.07 93.31 0.00 0.00 0.00
November 455.33 313.50 141.83 706.29 201.34 0.00 0.00 0.00
December 470.80 338.11 132.70 698.31 267.24 0.00 0.00 0.00
                 
Annual Sum or Average 298.34 143.77 154.57 499.43 137.17 0.00 0.00 0.00
Minimum of Months 156.07 1.45 132.70 326.54 18.84 0.00 0.00 0.00
Maximum of Months 481.83 343.63 171.43 706.29 296.89 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 481.82 343.62 138.20 689.29 296.89 0.00 0.00 0.00
February 436.99 282.85 154.13 638.09 256.42 0.00 0.00 0.00
March 278.98 125.90 153.08 418.42 226.01 0.00 0.00 0.00
April 206.78 48.45 158.33 343.34 143.95 0.00 0.00 0.00
May 158.00 6.71 151.28 326.54 38.78 0.00 0.00 0.00
June 156.07 1.45 154.62 332.23 31.32 0.00 0.00 0.00
July 163.38 3.00 160.38 345.58 18.84 0.00 0.00 0.00
August 192.21 23.07 169.14 406.84 30.59 0.00 0.00 0.00
September 230.62 60.78 169.84 452.31 48.91 0.00 0.00 0.00
October 357.81 186.38 171.42 644.07 93.31 0.00 0.00 0.00
November 455.33 313.50 141.83 706.29 201.34 0.00 0.00 0.00
December 470.80 338.10 132.70 698.31 267.24 0.00 0.00 0.00
                 
Annual Sum or Average 298.34 143.77 154.57 499.43 137.17 0.00 0.00 0.00
Minimum of Months 156.07 1.45 132.70 326.54 18.84 0.00 0.00 0.00
Maximum of Months 481.82 343.62 171.42 706.29 296.89 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 481.83 343.63 138.20 689.30 296.89 0.00 0.00 0.00
February 436.99 282.86 154.13 638.09 256.42 0.00 0.00 0.00
March 278.98 125.91 153.08 418.42 226.01 0.00 0.00 0.00
April 206.78 48.45 158.33 343.34 143.95 0.00 0.00 0.00
May 158.00 6.71 151.28 326.54 38.78 0.00 0.00 0.00
June 156.07 1.45 154.62 332.24 31.32 0.00 0.00 0.00
July 163.38 3.00 160.38 345.58 18.84 0.00 0.00 0.00
August 192.21 23.07 169.14 406.85 30.59 0.00 0.00 0.00
September 230.62 60.78 169.84 452.31 48.91 0.00 0.00 0.00
October 357.81 186.38 171.43 644.07 93.31 0.00 0.00 0.00
November 455.33 313.50 141.83 706.29 201.34 0.00 0.00 0.00
December 470.80 338.11 132.70 698.31 267.24 0.00 0.00 0.00
                 
Annual Sum or Average 298.34 143.77 154.57 499.43 137.17 0.00 0.00 0.00
Minimum of Months 156.07 1.45 132.70 326.54 18.84 0.00 0.00 0.00
Maximum of Months 481.83 343.63 171.43 706.29 296.89 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 481.82 343.62 138.20 689.29 296.89 0.00 0.00 0.00
February 436.99 282.85 154.13 638.09 256.42 0.00 0.00 0.00
March 278.98 125.90 153.08 418.42 226.01 0.00 0.00 0.00
April 206.78 48.45 158.33 343.34 143.95 0.00 0.00 0.00
May 158.00 6.71 151.28 326.54 38.78 0.00 0.00 0.00
June 156.07 1.45 154.62 332.23 31.32 0.00 0.00 0.00
July 163.38 3.00 160.38 345.58 18.84 0.00 0.00 0.00
August 192.21 23.07 169.14 406.84 30.59 0.00 0.00 0.00
September 230.62 60.78 169.84 452.31 48.91 0.00 0.00 0.00
October 357.81 186.38 171.42 644.07 93.31 0.00 0.00 0.00
November 455.33 313.50 141.83 706.29 201.34 0.00 0.00 0.00
December 470.80 338.10 132.70 698.31 267.24 0.00 0.00 0.00
                 
Annual Sum or Average 298.34 143.77 154.57 499.43 137.17 0.00 0.00 0.00
Minimum of Months 156.07 1.45 132.70 326.54 18.84 0.00 0.00 0.00
Maximum of Months 481.82 343.62 171.42 706.29 296.89 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 481.81 343.61 138.20 689.27 296.88 0.00 0.00 0.00
February 436.97 282.84 154.13 638.06 256.41 0.00 0.00 0.00
March 278.97 125.90 153.07 418.40 226.00 0.00 0.00 0.00
April 206.77 48.45 158.32 343.33 143.94 0.00 0.00 0.00
May 157.99 6.71 151.27 326.52 38.77 0.00 0.00 0.00
June 156.07 1.45 154.61 332.22 31.31 0.00 0.00 0.00
July 163.38 3.00 160.37 345.56 18.83 0.00 0.00 0.00
August 192.20 23.07 169.13 406.83 30.59 0.00 0.00 0.00
September 230.61 60.78 169.84 452.29 48.91 0.00 0.00 0.00
October 357.79 186.38 171.42 644.04 93.31 0.00 0.00 0.00
November 455.31 313.49 141.83 706.26 201.33 0.00 0.00 0.00
December 470.78 338.09 132.69 698.28 267.23 0.00 0.00 0.00
                 
Annual Sum or Average 298.33 143.77 154.56 499.41 137.16 0.00 0.00 0.00
Minimum of Months 156.07 1.45 132.69 326.52 18.83 0.00 0.00 0.00
Maximum of Months 481.81 343.61 171.42 706.26 296.88 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 253.55 137.10 116.44 314.66 376.75 0.00 0.00 0.00
February 287.07 145.30 141.77 367.07 335.24 0.00 0.00 0.00
March 282.94 125.25 157.69 374.71 297.08 0.00 0.00 0.00
April 351.42 161.66 189.76 533.59 195.27 0.00 0.00 0.00
May 292.25 95.20 197.05 550.63 58.68 0.00 0.00 0.00
June 324.65 113.84 210.81 620.43 54.02 0.00 0.00 0.00
July 296.35 82.20 214.14 562.32 41.59 0.00 0.00 0.00
August 299.64 91.73 207.92 566.45 58.80 0.00 0.00 0.00
September 275.92 94.65 181.27 504.25 67.59 0.00 0.00 0.00
October 282.49 122.06 160.43 490.50 123.51 0.00 0.00 0.00
November 242.12 121.68 120.44 339.63 270.64 0.00 0.00 0.00
December 232.90 123.85 109.05 295.86 361.60 0.00 0.00 0.00
                 
Annual Sum or Average 284.95 117.60 167.35 460.34 185.95 0.00 0.00 0.00
Minimum of Months 232.90 82.20 109.05 295.86 41.59 0.00 0.00 0.00
Maximum of Months 351.42 161.66 214.14 620.43 376.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 253.55 137.10 116.44 314.66 376.75 0.00 0.00 0.00
February 287.07 145.30 141.77 367.07 335.24 0.00 0.00 0.00
March 282.94 125.25 157.69 374.71 297.08 0.00 0.00 0.00
April 351.42 161.66 189.76 533.59 195.27 0.00 0.00 0.00
May 292.25 95.20 197.05 550.63 58.68 0.00 0.00 0.00
June 324.65 113.84 210.81 620.43 54.02 0.00 0.00 0.00
July 296.35 82.20 214.14 562.32 41.59 0.00 0.00 0.00
August 299.64 91.73 207.92 566.45 58.80 0.00 0.00 0.00
September 275.92 94.65 181.27 504.25 67.59 0.00 0.00 0.00
October 282.49 122.06 160.43 490.50 123.51 0.00 0.00 0.00
November 242.12 121.68 120.44 339.63 270.64 0.00 0.00 0.00
December 232.90 123.85 109.05 295.86 361.60 0.00 0.00 0.00
                 
Annual Sum or Average 284.95 117.60 167.35 460.34 185.95 0.00 0.00 0.00
Minimum of Months 232.90 82.20 109.05 295.86 41.59 0.00 0.00 0.00
Maximum of Months 351.42 161.66 214.14 620.43 376.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 253.54 137.10 116.44 314.65 376.75 0.00 0.00 0.00
February 287.07 145.30 141.77 367.06 335.23 0.00 0.00 0.00
March 282.93 125.25 157.69 374.70 297.08 0.00 0.00 0.00
April 351.41 161.66 189.76 533.58 195.27 0.00 0.00 0.00
May 292.24 95.20 197.04 550.62 58.68 0.00 0.00 0.00
June 324.65 113.84 210.81 620.42 54.02 0.00 0.00 0.00
July 296.34 82.20 214.14 562.31 41.59 0.00 0.00 0.00
August 299.64 91.72 207.92 566.44 58.80 0.00 0.00 0.00
September 275.92 94.65 181.26 504.24 67.59 0.00 0.00 0.00
October 282.48 122.06 160.42 490.49 123.50 0.00 0.00 0.00
November 242.12 121.68 120.44 339.62 270.63 0.00 0.00 0.00
December 232.90 123.85 109.05 295.85 361.59 0.00 0.00 0.00
                 
Annual Sum or Average 284.94 117.59 167.35 460.33 185.94 0.00 0.00 0.00
Minimum of Months 232.90 82.20 109.05 295.85 41.59 0.00 0.00 0.00
Maximum of Months 351.41 161.66 214.14 620.42 376.75 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 416.80 0.00 416.80 332.34 1436.20 0.00 0.00 0.00
February 491.72 0.00 491.72 441.01 1210.23 0.00 0.00 0.00
March 570.44 0.00 570.44 622.28 1041.42 0.00 0.00 0.00
April 673.25 2.76 670.48 949.69 654.22 0.00 0.00 0.00
May 762.58 27.89 734.69 1567.97 180.07 0.00 0.00 0.00
June 867.22 60.05 807.17 1848.72 155.96 0.00 0.00 0.00
July 841.58 32.06 809.51 1782.36 100.16 0.00 0.00 0.00
August 753.65 5.93 747.72 1610.03 143.96 0.00 0.00 0.00
September 650.98 0.05 650.93 1289.32 203.22 0.00 0.00 0.00
October 565.69 0.00 565.69 1041.90 401.04 0.00 0.00 0.00
November 429.45 0.00 429.45 493.62 921.39 0.00 0.00 0.00
December 387.46 0.00 387.46 350.99 1229.70 0.00 0.00 0.00
                 
Annual Sum or Average 618.19 10.76 607.43 1031.05 636.82 0.00 0.00 0.00
Minimum of Months 387.46 0.00 387.46 332.34 100.16 0.00 0.00 0.00
Maximum of Months 867.22 60.05 809.51 1848.72 1436.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 715.11 364.14 350.98 865.32 903.99 0.00 0.00 0.00
February 796.30 384.43 411.87 1012.13 769.43 0.00 0.00 0.00
March 936.72 451.75 484.96 1279.22 671.05 0.00 0.00 0.00
April 1027.94 464.91 563.03 1587.91 441.41 0.00 0.00 0.00
May 1059.53 459.43 600.10 1959.90 127.75 0.00 0.00 0.00
June 1074.54 426.13 648.41 2058.56 109.35 0.00 0.00 0.00
July 1036.01 379.12 656.88 1987.75 70.58 0.00 0.00 0.00
August 954.65 328.22 626.43 1835.05 101.63 0.00 0.00 0.00
September 845.64 290.73 554.91 1552.07 141.66 0.00 0.00 0.00
October 835.67 352.65 483.02 1456.94 269.76 0.00 0.00 0.00
November 739.86 377.43 362.43 1038.80 595.33 0.00 0.00 0.00
December 582.53 263.87 318.66 735.35 791.22 0.00 0.00 0.00
                 
Annual Sum or Average 884.01 378.40 505.61 1449.77 414.22 0.00 0.00 0.00
Minimum of Months 582.53 263.87 318.66 735.35 70.58 0.00 0.00 0.00
Maximum of Months 1074.54 464.91 656.88 2058.56 903.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2409.18 1718.17 691.02 3426.32 1447.73 0.00 0.00 0.00
February 2184.99 1414.31 770.68 3177.27 1240.55 0.00 0.00 0.00
March 1394.95 629.54 765.41 2091.98 1078.98 0.00 0.00 0.00
April 1033.92 242.27 791.64 1719.76 702.73 0.00 0.00 0.00
May 789.99 33.57 756.41 1639.95 187.83 0.00 0.00 0.00
June 780.37 7.27 773.10 1672.22 159.00 0.00 0.00 0.00
July 816.92 15.01 801.91 1742.02 97.47 0.00 0.00 0.00
August 961.07 115.36 845.71 2043.46 158.38 0.00 0.00 0.00
September 1153.12 303.90 849.22 2257.08 235.03 0.00 0.00 0.00
October 1789.07 931.94 857.14 3203.31 465.77 0.00 0.00 0.00
November 2276.71 1567.54 709.17 3515.06 982.56 0.00 0.00 0.00
December 2354.07 1690.56 663.50 3481.19 1286.51 0.00 0.00 0.00
                 
Annual Sum or Average 1491.72 718.87 772.84 2494.14 667.17 0.00 0.00 0.00
Minimum of Months 780.37 7.27 663.50 1639.95 97.47 0.00 0.00 0.00
Maximum of Months 2409.18 1718.17 857.14 3515.06 1447.73 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 760.64 411.31 349.33 981.55 995.63 0.00 0.00 0.00
February 861.21 435.89 425.32 1147.23 857.56 0.00 0.00 0.00
March 848.81 375.75 473.06 1169.97 744.20 0.00 0.00 0.00
April 1054.25 484.97 569.27 1639.94 501.71 0.00 0.00 0.00
May 876.73 285.60 591.13 1665.74 155.85 0.00 0.00 0.00
June 973.95 341.51 632.43 1883.28 139.50 0.00 0.00 0.00
July 889.03 246.60 642.43 1724.52 94.93 0.00 0.00 0.00
August 898.92 275.17 623.75 1743.34 132.50 0.00 0.00 0.00
September 827.76 283.96 543.80 1526.86 171.73 0.00 0.00 0.00
October 847.45 366.17 481.28 1497.24 318.13 0.00 0.00 0.00
November 726.37 365.04 361.32 1065.59 670.90 0.00 0.00 0.00
December 698.70 371.56 327.14 945.10 868.20 0.00 0.00 0.00
                 
Annual Sum or Average 854.83 352.79 502.04 1416.83 468.82 0.00 0.00 0.00
Minimum of Months 698.70 246.60 327.14 945.10 94.93 0.00 0.00 0.00
Maximum of Months 1054.25 484.97 642.43 1883.28 995.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 416.80 0.00 416.80 358.25 1321.37 0.00 0.00 0.00
February 491.72 0.00 491.72 465.81 1110.46 0.00 0.00 0.00
March 570.44 0.00 570.44 640.18 974.01 0.00 0.00 0.00
April 673.25 2.76 670.48 949.43 636.22 0.00 0.00 0.00
May 762.58 27.89 734.69 1540.87 193.95 0.00 0.00 0.00
June 867.22 60.05 807.17 1817.36 169.70 0.00 0.00 0.00
July 841.58 32.06 809.51 1747.47 111.86 0.00 0.00 0.00
August 753.65 5.93 747.72 1581.81 156.00 0.00 0.00 0.00
September 650.98 0.05 650.93 1263.56 214.62 0.00 0.00 0.00
October 565.69 0.00 565.69 1032.39 394.36 0.00 0.00 0.00
November 429.45 0.00 429.45 518.52 843.88 0.00 0.00 0.00
December 387.46 0.00 387.46 375.82 1126.25 0.00 0.00 0.00
                 
Annual Sum or Average 618.19 10.76 607.43 1027.64 601.75 0.00 0.00 0.00
Minimum of Months 387.46 0.00 387.46 358.25 111.86 0.00 0.00 0.00
Maximum of Months 867.22 60.05 809.51 1817.36 1321.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 715.11 364.14 350.98 893.71 836.28 0.00 0.00 0.00
February 796.30 384.43 411.87 1034.57 713.13 0.00 0.00 0.00
March 936.72 451.75 484.96 1289.19 636.45 0.00 0.00 0.00
April 1027.94 464.91 563.03 1582.88 435.31 0.00 0.00 0.00
May 1059.53 459.43 600.10 1939.73 137.11 0.00 0.00 0.00
June 1074.54 426.13 648.41 2036.64 118.95 0.00 0.00 0.00
July 1036.01 379.12 656.88 1963.89 78.54 0.00 0.00 0.00
August 954.65 328.22 626.43 1814.69 110.04 0.00 0.00 0.00
September 845.64 290.73 554.91 1534.30 150.29 0.00 0.00 0.00
October 835.67 352.65 483.02 1447.54 267.93 0.00 0.00 0.00
November 739.86 377.43 362.43 1055.20 555.82 0.00 0.00 0.00
December 582.53 263.87 318.66 755.77 732.41 0.00 0.00 0.00
                 
Annual Sum or Average 884.01 378.40 505.61 1447.89 396.00 0.00 0.00 0.00
Minimum of Months 582.53 263.87 318.66 755.77 78.54 0.00 0.00 0.00
Maximum of Months 1074.54 464.91 656.88 2036.64 836.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2409.18 1718.17 691.02 3456.51 1351.44 0.00 0.00 0.00
February 2184.99 1414.31 770.68 3204.20 1159.38 0.00 0.00 0.00
March 1394.95 629.54 765.41 2104.95 1020.44 0.00 0.00 0.00
April 1033.92 242.27 791.64 1713.90 687.74 0.00 0.00 0.00
May 789.99 33.57 756.41 1612.80 202.15 0.00 0.00 0.00
June 780.37 7.27 773.10 1642.19 173.39 0.00 0.00 0.00
July 816.92 15.01 801.91 1706.36 108.61 0.00 0.00 0.00
August 961.07 115.36 845.71 2014.09 171.68 0.00 0.00 0.00
September 1153.12 303.90 849.22 2232.05 247.75 0.00 0.00 0.00
October 1789.07 931.94 857.14 3186.71 465.14 0.00 0.00 0.00
November 2276.71 1567.54 709.17 3527.21 932.92 0.00 0.00 0.00
December 2354.07 1690.56 663.50 3502.53 1202.01 0.00 0.00 0.00
                 
Annual Sum or Average 1491.72 718.87 772.84 2488.44 640.77 0.00 0.00 0.00
Minimum of Months 780.37 7.27 663.50 1612.80 108.61 0.00 0.00 0.00
Maximum of Months 2409.18 1718.17 857.14 3527.21 1351.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 760.64 411.31 349.33 996.45 929.65 0.00 0.00 0.00
February 861.21 435.89 425.32 1160.22 800.98 0.00 0.00 0.00
March 848.81 375.75 473.06 1177.42 704.97 0.00 0.00 0.00
April 1054.25 484.97 569.27 1635.86 489.85 0.00 0.00 0.00
May 876.73 285.60 591.13 1650.31 162.38 0.00 0.00 0.00
June 973.95 341.51 632.43 1865.32 145.82 0.00 0.00 0.00
July 889.03 246.60 642.43 1705.62 99.33 0.00 0.00 0.00
August 898.92 275.17 623.75 1726.33 138.82 0.00 0.00 0.00
September 827.76 283.96 543.80 1513.35 177.01 0.00 0.00 0.00
October 847.45 366.17 481.28 1490.01 314.31 0.00 0.00 0.00
November 726.37 365.04 361.32 1077.10 628.61 0.00 0.00 0.00
December 698.70 371.56 327.14 958.33 809.16 0.00 0.00 0.00
                 
Annual Sum or Average 854.83 352.79 502.04 1413.90 448.18 0.00 0.00 0.00
Minimum of Months 698.70 246.60 327.14 958.33 99.33 0.00 0.00 0.00
Maximum of Months 1054.25 484.97 642.43 1865.32 929.65 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223271E+09 0.00 0.223271E+09 0.147271E+09 0.876244E+09
February 0.237915E+09 0.00 0.237915E+09 0.185789E+09 0.673126E+09
March 0.305574E+09 0.00 0.305574E+09 0.303708E+09 0.631555E+09
April 0.349011E+09 1432452.17 0.347579E+09 0.476702E+09 0.362962E+09
May 0.408498E+09 14941839.27 0.393557E+09 0.834449E+09 0.100536E+09
June 0.449564E+09 31128636.17 0.418436E+09 0.953731E+09 78777030.49
July 0.450816E+09 17175142.31 0.433641E+09 0.948119E+09 51096605.22
August 0.403714E+09 3175239.04 0.400538E+09 0.852530E+09 75608134.15
September 0.337469E+09 25991.58 0.337443E+09 0.659922E+09 0.116802E+09
October 0.303029E+09 0.00 0.303029E+09 0.545173E+09 0.235238E+09
November 0.222627E+09 0.00 0.222627E+09 0.229479E+09 0.548877E+09
December 0.207556E+09 0.00 0.207556E+09 0.156847E+09 0.771900E+09
           
Annual Sum or Average 0.389904E+10 67879300.53 0.383116E+10 0.629372E+10 0.452272E+10
Minimum of Months 0.207556E+09 0.00 0.207556E+09 0.147271E+09 51096605.22
Maximum of Months 0.450816E+09 31128636.17 0.433641E+09 0.953731E+09 0.876244E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223268E+09 0.00 0.223268E+09 0.147269E+09 0.876242E+09
February 0.237912E+09 0.00 0.237912E+09 0.185787E+09 0.673125E+09
March 0.305570E+09 0.00 0.305570E+09 0.303704E+09 0.631554E+09
April 0.349007E+09 1432420.68 0.347574E+09 0.476696E+09 0.362960E+09
May 0.408493E+09 14941510.79 0.393551E+09 0.834440E+09 0.100535E+09
June 0.449558E+09 31127951.84 0.418430E+09 0.953721E+09 78775759.13
July 0.450809E+09 17174764.73 0.433634E+09 0.948109E+09 51095465.99
August 0.403708E+09 3175169.23 0.400533E+09 0.852522E+09 75606900.80
September 0.337464E+09 25991.01 0.337438E+09 0.659915E+09 0.116801E+09
October 0.303025E+09 0.00 0.303025E+09 0.545167E+09 0.235237E+09
November 0.222624E+09 0.00 0.222624E+09 0.229476E+09 0.548875E+09
December 0.207553E+09 0.00 0.207553E+09 0.156845E+09 0.771899E+09
           
Annual Sum or Average 0.389899E+10 67877808.28 0.383111E+10 0.629365E+10 0.452271E+10
Minimum of Months 0.207553E+09 0.00 0.207553E+09 0.147269E+09 51095465.99
Maximum of Months 0.450809E+09 31127951.84 0.433634E+09 0.953721E+09 0.876242E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223269E+09 0.00 0.223269E+09 0.147270E+09 0.876243E+09
February 0.237913E+09 0.00 0.237913E+09 0.185787E+09 0.673125E+09
March 0.305571E+09 0.00 0.305571E+09 0.303705E+09 0.631555E+09
April 0.349008E+09 1432431.18 0.347576E+09 0.476698E+09 0.362961E+09
May 0.408494E+09 14941620.28 0.393553E+09 0.834443E+09 0.100535E+09
June 0.449560E+09 31128179.95 0.418432E+09 0.953724E+09 78776182.92
July 0.450811E+09 17174890.59 0.433636E+09 0.948113E+09 51095845.74
August 0.403710E+09 3175192.50 0.400535E+09 0.852524E+09 75607311.85
September 0.337466E+09 25991.20 0.337440E+09 0.659917E+09 0.116801E+09
October 0.303026E+09 0.00 0.303026E+09 0.545169E+09 0.235237E+09
November 0.222625E+09 0.00 0.222625E+09 0.229477E+09 0.548876E+09
December 0.207554E+09 0.00 0.207554E+09 0.156845E+09 0.771899E+09
           
Annual Sum or Average 0.389901E+10 67878305.70 0.383113E+10 0.629367E+10 0.452271E+10
Minimum of Months 0.207554E+09 0.00 0.207554E+09 0.147270E+09 51095845.74
Maximum of Months 0.450811E+09 31128179.95 0.433636E+09 0.953724E+09 0.876243E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223268E+09 0.00 0.223268E+09 0.147269E+09 0.876242E+09
February 0.237912E+09 0.00 0.237912E+09 0.185787E+09 0.673125E+09
March 0.305570E+09 0.00 0.305570E+09 0.303704E+09 0.631554E+09
April 0.349007E+09 1432420.68 0.347574E+09 0.476696E+09 0.362960E+09
May 0.408493E+09 14941510.79 0.393551E+09 0.834440E+09 0.100535E+09
June 0.449558E+09 31127951.84 0.418430E+09 0.953721E+09 78775759.13
July 0.450809E+09 17174764.73 0.433634E+09 0.948109E+09 51095465.99
August 0.403708E+09 3175169.23 0.400533E+09 0.852522E+09 75606900.80
September 0.337464E+09 25991.01 0.337438E+09 0.659915E+09 0.116801E+09
October 0.303025E+09 0.00 0.303025E+09 0.545167E+09 0.235237E+09
November 0.222624E+09 0.00 0.222624E+09 0.229476E+09 0.548875E+09
December 0.207553E+09 0.00 0.207553E+09 0.156845E+09 0.771899E+09
           
Annual Sum or Average 0.389899E+10 67877808.28 0.383111E+10 0.629365E+10 0.452271E+10
Minimum of Months 0.207553E+09 0.00 0.207553E+09 0.147269E+09 51095465.99
Maximum of Months 0.450809E+09 31127951.84 0.433634E+09 0.953721E+09 0.876242E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223260E+09 0.00 0.223260E+09 0.147263E+09 0.876207E+09
February 0.237903E+09 0.00 0.237903E+09 0.185779E+09 0.673098E+09
March 0.305558E+09 0.00 0.305558E+09 0.303692E+09 0.631529E+09
April 0.348993E+09 1432368.20 0.347561E+09 0.476678E+09 0.362946E+09
May 0.408477E+09 14940963.33 0.393536E+09 0.834408E+09 0.100531E+09
June 0.449541E+09 31126811.29 0.418414E+09 0.953684E+09 78772796.01
July 0.450792E+09 17174135.44 0.433618E+09 0.948073E+09 51093596.49
August 0.403693E+09 3175052.89 0.400517E+09 0.852489E+09 75604059.02
September 0.337451E+09 25990.05 0.337425E+09 0.659890E+09 0.116796E+09
October 0.303013E+09 0.00 0.303013E+09 0.545146E+09 0.235228E+09
November 0.222615E+09 0.00 0.222615E+09 0.229467E+09 0.548853E+09
December 0.207545E+09 0.00 0.207545E+09 0.156839E+09 0.771868E+09
           
Annual Sum or Average 0.389884E+10 67875321.21 0.383097E+10 0.629341E+10 0.452253E+10
Minimum of Months 0.207545E+09 0.00 0.207545E+09 0.147263E+09 51093596.49
Maximum of Months 0.450792E+09 31126811.29 0.433618E+09 0.953684E+09 0.876207E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.638461E+09 0.325107E+09 0.313354E+09 0.745849E+09 0.891583E+09
February 0.642146E+09 0.310011E+09 0.332135E+09 0.797483E+09 0.679099E+09
March 0.836308E+09 0.403329E+09 0.432980E+09 0.113627E+10 0.636472E+09
April 0.888146E+09 0.401684E+09 0.486462E+09 0.138307E+10 0.373362E+09
May 0.945954E+09 0.410184E+09 0.535770E+09 0.176331E+10 0.109758E+09
June 0.928410E+09 0.368182E+09 0.560228E+09 0.179248E+10 80108736.54
July 0.924957E+09 0.338484E+09 0.586473E+09 0.179265E+10 46093921.93
August 0.852319E+09 0.293034E+09 0.559285E+09 0.165378E+10 69603779.80
September 0.730643E+09 0.251193E+09 0.479451E+09 0.134754E+10 0.125022E+09
October 0.746094E+09 0.314849E+09 0.431244E+09 0.130739E+10 0.243165E+09
November 0.639250E+09 0.326106E+09 0.313143E+09 0.889552E+09 0.549669E+09
December 0.520086E+09 0.235587E+09 0.284498E+09 0.636881E+09 0.774030E+09
           
Annual Sum or Average 0.929277E+10 0.397775E+10 0.531502E+10 0.152463E+11 0.457797E+10
Minimum of Months 0.520086E+09 0.235587E+09 0.284498E+09 0.636881E+09 46093921.93
Maximum of Months 0.945954E+09 0.410184E+09 0.586473E+09 0.179265E+10 0.891583E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.638461E+09 0.325107E+09 0.313354E+09 0.745849E+09 0.891583E+09
February 0.642146E+09 0.310011E+09 0.332135E+09 0.797483E+09 0.679099E+09
March 0.836308E+09 0.403329E+09 0.432980E+09 0.113627E+10 0.636472E+09
April 0.888146E+09 0.401684E+09 0.486462E+09 0.138307E+10 0.373362E+09
May 0.945954E+09 0.410184E+09 0.535770E+09 0.176331E+10 0.109758E+09
June 0.928410E+09 0.368182E+09 0.560228E+09 0.179248E+10 80108736.54
July 0.924957E+09 0.338484E+09 0.586473E+09 0.179265E+10 46093921.93
August 0.852319E+09 0.293034E+09 0.559285E+09 0.165378E+10 69603779.80
September 0.730643E+09 0.251193E+09 0.479451E+09 0.134754E+10 0.125022E+09
October 0.746094E+09 0.314849E+09 0.431244E+09 0.130739E+10 0.243165E+09
November 0.639250E+09 0.326106E+09 0.313143E+09 0.889552E+09 0.549669E+09
December 0.520086E+09 0.235587E+09 0.284498E+09 0.636881E+09 0.774030E+09
           
Annual Sum or Average 0.929277E+10 0.397775E+10 0.531502E+10 0.152463E+11 0.457797E+10
Minimum of Months 0.520086E+09 0.235587E+09 0.284498E+09 0.636881E+09 46093921.93
Maximum of Months 0.945954E+09 0.410184E+09 0.586473E+09 0.179265E+10 0.891583E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.638450E+09 0.325101E+09 0.313349E+09 0.745835E+09 0.891567E+09
February 0.642135E+09 0.310006E+09 0.332129E+09 0.797468E+09 0.679087E+09
March 0.836293E+09 0.403321E+09 0.432972E+09 0.113625E+10 0.636460E+09
April 0.888130E+09 0.401677E+09 0.486453E+09 0.138305E+10 0.373355E+09
May 0.945937E+09 0.410176E+09 0.535761E+09 0.176328E+10 0.109756E+09
June 0.928393E+09 0.368175E+09 0.560218E+09 0.179245E+10 80107272.78
July 0.924940E+09 0.338478E+09 0.586462E+09 0.179262E+10 46093079.69
August 0.852304E+09 0.293029E+09 0.559275E+09 0.165375E+10 69602507.98
September 0.730630E+09 0.251188E+09 0.479442E+09 0.134752E+10 0.125020E+09
October 0.746080E+09 0.314843E+09 0.431237E+09 0.130736E+10 0.243161E+09
November 0.639238E+09 0.326100E+09 0.313138E+09 0.889535E+09 0.549659E+09
December 0.520076E+09 0.235583E+09 0.284493E+09 0.636869E+09 0.774016E+09
           
Annual Sum or Average 0.929260E+10 0.397768E+10 0.531493E+10 0.152460E+11 0.457788E+10
Minimum of Months 0.520076E+09 0.235583E+09 0.284493E+09 0.636869E+09 46093079.69
Maximum of Months 0.945937E+09 0.410176E+09 0.586462E+09 0.179262E+10 0.891567E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.129053E+10 0.920368E+09 0.370159E+09 0.184622E+10 0.795203E+09
February 0.105717E+10 0.684285E+09 0.372883E+09 0.154367E+10 0.620341E+09
March 0.747233E+09 0.337225E+09 0.410008E+09 0.112069E+10 0.605342E+09
April 0.535976E+09 0.125591E+09 0.410385E+09 0.889939E+09 0.373120E+09
May 0.423176E+09 17984196.22 0.405192E+09 0.874597E+09 0.103856E+09
June 0.404542E+09 3770670.32 0.400771E+09 0.861154E+09 81171389.34
July 0.437605E+09 8043046.48 0.429562E+09 0.925595E+09 50449748.58
August 0.514818E+09 61793137.02 0.453025E+09 0.108970E+10 81944388.59
September 0.597768E+09 0.157536E+09 0.440232E+09 0.117239E+10 0.126772E+09
October 0.958355E+09 0.499210E+09 0.459145E+09 0.172508E+10 0.249928E+09
November 0.118023E+10 0.812596E+09 0.367630E+09 0.183072E+10 0.521869E+09
December 0.126100E+10 0.905582E+09 0.355420E+09 0.187036E+10 0.715781E+09
           
Annual Sum or Average 0.940840E+10 0.453399E+10 0.487441E+10 0.157501E+11 0.432578E+10
Minimum of Months 0.404542E+09 3770670.32 0.355420E+09 0.861154E+09 50449748.58
Maximum of Months 0.129053E+10 0.920368E+09 0.459145E+09 0.187036E+10 0.795203E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.129052E+10 0.920361E+09 0.370157E+09 0.184620E+10 0.795202E+09
February 0.105716E+10 0.684280E+09 0.372881E+09 0.154366E+10 0.620341E+09
March 0.747229E+09 0.337223E+09 0.410006E+09 0.112069E+10 0.605341E+09
April 0.535973E+09 0.125590E+09 0.410383E+09 0.889934E+09 0.373119E+09
May 0.423174E+09 17984064.43 0.405190E+09 0.874594E+09 0.103856E+09
June 0.404540E+09 3770642.69 0.400769E+09 0.861151E+09 81170944.27
July 0.437603E+09 8042987.54 0.429560E+09 0.925592E+09 50449380.81
August 0.514816E+09 61792684.20 0.453023E+09 0.108969E+10 81943958.69
September 0.597765E+09 0.157535E+09 0.440230E+09 0.117238E+10 0.126771E+09
October 0.958349E+09 0.499207E+09 0.459142E+09 0.172506E+10 0.249928E+09
November 0.118022E+10 0.812590E+09 0.367628E+09 0.183070E+10 0.521869E+09
December 0.126099E+10 0.905576E+09 0.355418E+09 0.187035E+10 0.715780E+09
           
Annual Sum or Average 0.940834E+10 0.453395E+10 0.487439E+10 0.157500E+11 0.432577E+10
Minimum of Months 0.404540E+09 3770642.69 0.355418E+09 0.861151E+09 50449380.81
Maximum of Months 0.129052E+10 0.920361E+09 0.459142E+09 0.187035E+10 0.795202E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.129053E+10 0.920368E+09 0.370159E+09 0.184622E+10 0.795203E+09
February 0.105717E+10 0.684285E+09 0.372883E+09 0.154367E+10 0.620341E+09
March 0.747233E+09 0.337225E+09 0.410008E+09 0.112069E+10 0.605342E+09
April 0.535976E+09 0.125591E+09 0.410385E+09 0.889939E+09 0.373120E+09
May 0.423176E+09 17984196.22 0.405192E+09 0.874597E+09 0.103856E+09
June 0.404542E+09 3770670.32 0.400771E+09 0.861154E+09 81171389.34
July 0.437605E+09 8043046.48 0.429562E+09 0.925595E+09 50449748.58
August 0.514818E+09 61793137.02 0.453025E+09 0.108970E+10 81944388.59
September 0.597768E+09 0.157536E+09 0.440232E+09 0.117239E+10 0.126772E+09
October 0.958355E+09 0.499210E+09 0.459145E+09 0.172508E+10 0.249928E+09
November 0.118023E+10 0.812596E+09 0.367630E+09 0.183072E+10 0.521869E+09
December 0.126100E+10 0.905582E+09 0.355420E+09 0.187036E+10 0.715781E+09
           
Annual Sum or Average 0.940840E+10 0.453399E+10 0.487441E+10 0.157501E+11 0.432578E+10
Minimum of Months 0.404542E+09 3770670.32 0.355420E+09 0.861154E+09 50449748.58
Maximum of Months 0.129053E+10 0.920368E+09 0.459145E+09 0.187036E+10 0.795203E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.129052E+10 0.920361E+09 0.370157E+09 0.184620E+10 0.795202E+09
February 0.105716E+10 0.684280E+09 0.372881E+09 0.154366E+10 0.620341E+09
March 0.747229E+09 0.337223E+09 0.410006E+09 0.112069E+10 0.605341E+09
April 0.535973E+09 0.125590E+09 0.410383E+09 0.889934E+09 0.373119E+09
May 0.423174E+09 17984064.43 0.405190E+09 0.874594E+09 0.103856E+09
June 0.404540E+09 3770642.69 0.400769E+09 0.861151E+09 81170944.27
July 0.437603E+09 8042987.54 0.429560E+09 0.925592E+09 50449380.81
August 0.514816E+09 61792684.20 0.453023E+09 0.108969E+10 81943958.69
September 0.597765E+09 0.157535E+09 0.440230E+09 0.117238E+10 0.126771E+09
October 0.958349E+09 0.499207E+09 0.459142E+09 0.172506E+10 0.249928E+09
November 0.118022E+10 0.812590E+09 0.367628E+09 0.183070E+10 0.521869E+09
December 0.126099E+10 0.905576E+09 0.355418E+09 0.187035E+10 0.715780E+09
           
Annual Sum or Average 0.940834E+10 0.453395E+10 0.487439E+10 0.157500E+11 0.432577E+10
Minimum of Months 0.404540E+09 3770642.69 0.355418E+09 0.861151E+09 50449380.81
Maximum of Months 0.129052E+10 0.920361E+09 0.459142E+09 0.187035E+10 0.795202E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.129047E+10 0.920327E+09 0.370144E+09 0.184614E+10 0.795171E+09
February 0.105712E+10 0.684255E+09 0.372867E+09 0.154360E+10 0.620316E+09
March 0.747201E+09 0.337211E+09 0.409990E+09 0.112065E+10 0.605317E+09
April 0.535953E+09 0.125586E+09 0.410367E+09 0.889900E+09 0.373104E+09
May 0.423158E+09 17983405.49 0.405175E+09 0.874560E+09 0.103852E+09
June 0.404524E+09 3770504.53 0.400754E+09 0.861118E+09 81167895.25
July 0.437587E+09 8042692.84 0.429544E+09 0.925556E+09 50447531.36
August 0.514796E+09 61790420.09 0.453006E+09 0.108965E+10 81940870.93
September 0.597743E+09 0.157529E+09 0.440213E+09 0.117234E+10 0.126766E+09
October 0.958314E+09 0.499188E+09 0.459125E+09 0.172500E+10 0.249918E+09
November 0.118017E+10 0.812560E+09 0.367614E+09 0.183063E+10 0.521848E+09
December 0.126095E+10 0.905542E+09 0.355404E+09 0.187028E+10 0.715752E+09
           
Annual Sum or Average 0.940799E+10 0.453379E+10 0.487420E+10 0.157494E+11 0.432560E+10
Minimum of Months 0.404524E+09 3770504.53 0.355404E+09 0.861118E+09 50447531.36
Maximum of Months 0.129047E+10 0.920327E+09 0.459125E+09 0.187028E+10 0.795171E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.679104E+09 0.367222E+09 0.311882E+09 0.842777E+09 0.100910E+10
February 0.694487E+09 0.351506E+09 0.342981E+09 0.888018E+09 0.811012E+09
March 0.757826E+09 0.335471E+09 0.422355E+09 0.100361E+10 0.795709E+09
April 0.910877E+09 0.419021E+09 0.491856E+09 0.138306E+10 0.506144E+09
May 0.782752E+09 0.254983E+09 0.527769E+09 0.147482E+10 0.157162E+09
June 0.841498E+09 0.295069E+09 0.546429E+09 0.160815E+10 0.140022E+09
July 0.793735E+09 0.220170E+09 0.573565E+09 0.150612E+10 0.111392E+09
August 0.802566E+09 0.245676E+09 0.556890E+09 0.151717E+10 0.157483E+09
September 0.715188E+09 0.245344E+09 0.469844E+09 0.130702E+10 0.175200E+09
October 0.756612E+09 0.326924E+09 0.429688E+09 0.131377E+10 0.330798E+09
November 0.627587E+09 0.315400E+09 0.312187E+09 0.880322E+09 0.701487E+09
December 0.623808E+09 0.331732E+09 0.292075E+09 0.792430E+09 0.968497E+09
           
Annual Sum or Average 0.898604E+10 0.370852E+10 0.527752E+10 0.145173E+11 0.586401E+10
Minimum of Months 0.623808E+09 0.220170E+09 0.292075E+09 0.792430E+09 0.111392E+09
Maximum of Months 0.910877E+09 0.419021E+09 0.573565E+09 0.160815E+10 0.100910E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.679104E+09 0.367222E+09 0.311882E+09 0.842777E+09 0.100910E+10
February 0.694487E+09 0.351506E+09 0.342981E+09 0.888018E+09 0.811012E+09
March 0.757826E+09 0.335471E+09 0.422355E+09 0.100361E+10 0.795709E+09
April 0.910877E+09 0.419021E+09 0.491856E+09 0.138306E+10 0.506144E+09
May 0.782752E+09 0.254983E+09 0.527769E+09 0.147482E+10 0.157162E+09
June 0.841498E+09 0.295069E+09 0.546429E+09 0.160815E+10 0.140022E+09
July 0.793735E+09 0.220170E+09 0.573565E+09 0.150612E+10 0.111392E+09
August 0.802566E+09 0.245676E+09 0.556890E+09 0.151717E+10 0.157483E+09
September 0.715188E+09 0.245344E+09 0.469844E+09 0.130702E+10 0.175200E+09
October 0.756612E+09 0.326924E+09 0.429688E+09 0.131377E+10 0.330798E+09
November 0.627587E+09 0.315400E+09 0.312187E+09 0.880322E+09 0.701487E+09
December 0.623808E+09 0.331732E+09 0.292075E+09 0.792430E+09 0.968497E+09
           
Annual Sum or Average 0.898604E+10 0.370852E+10 0.527752E+10 0.145173E+11 0.586401E+10
Minimum of Months 0.623808E+09 0.220170E+09 0.292075E+09 0.792430E+09 0.111392E+09
Maximum of Months 0.910877E+09 0.419021E+09 0.573565E+09 0.160815E+10 0.100910E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.679091E+09 0.367215E+09 0.311876E+09 0.842762E+09 0.100908E+10
February 0.694475E+09 0.351500E+09 0.342975E+09 0.888002E+09 0.810997E+09
March 0.757812E+09 0.335464E+09 0.422348E+09 0.100359E+10 0.795694E+09
April 0.910860E+09 0.419013E+09 0.491847E+09 0.138303E+10 0.506135E+09
May 0.782738E+09 0.254978E+09 0.527759E+09 0.147479E+10 0.157159E+09
June 0.841483E+09 0.295063E+09 0.546419E+09 0.160812E+10 0.140020E+09
July 0.793720E+09 0.220166E+09 0.573554E+09 0.150610E+10 0.111390E+09
August 0.802552E+09 0.245672E+09 0.556880E+09 0.151714E+10 0.157480E+09
September 0.715175E+09 0.245339E+09 0.469836E+09 0.130700E+10 0.175197E+09
October 0.756598E+09 0.326918E+09 0.429680E+09 0.131374E+10 0.330792E+09
November 0.627576E+09 0.315394E+09 0.312181E+09 0.880306E+09 0.701474E+09
December 0.623796E+09 0.331726E+09 0.292070E+09 0.792416E+09 0.968480E+09
           
Annual Sum or Average 0.898588E+10 0.370845E+10 0.527743E+10 0.145170E+11 0.586390E+10
Minimum of Months 0.623796E+09 0.220166E+09 0.292070E+09 0.792416E+09 0.111390E+09
Maximum of Months 0.910860E+09 0.419013E+09 0.573554E+09 0.160812E+10 0.100908E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111635E+10 0.00 0.111635E+10 0.890146E+09 0.384671E+10
February 0.118957E+10 0.00 0.118957E+10 0.106688E+10 0.292778E+10
March 0.152787E+10 0.00 0.152787E+10 0.166671E+10 0.278933E+10
April 0.174505E+10 7162306.50 0.173789E+10 0.246159E+10 0.169575E+10
May 0.204249E+10 74709672.45 0.196778E+10 0.419965E+10 0.482310E+09
June 0.224782E+10 0.155644E+09 0.209218E+10 0.479188E+10 0.404244E+09
July 0.225408E+10 85876258.80 0.216820E+10 0.477388E+10 0.268263E+09
August 0.201857E+10 15876296.36 0.200269E+10 0.431230E+10 0.385574E+09
September 0.168734E+10 129958.71 0.168721E+10 0.334191E+10 0.526733E+09
October 0.151514E+10 0.00 0.151514E+10 0.279063E+10 0.107416E+10
November 0.111313E+10 0.00 0.111313E+10 0.127947E+10 0.238825E+10
December 0.103778E+10 0.00 0.103778E+10 0.940096E+09 0.329364E+10
           
Annual Sum or Average 0.194952E+11 0.339399E+09 0.191558E+11 0.325151E+11 0.200827E+11
Minimum of Months 0.103778E+10 0.00 0.103778E+10 0.890146E+09 0.268263E+09
Maximum of Months 0.225408E+10 0.155644E+09 0.216820E+10 0.479188E+10 0.384671E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.191536E+10 0.975310E+09 0.940054E+09 0.231768E+10 0.242124E+10
February 0.192642E+10 0.930024E+09 0.996395E+09 0.244856E+10 0.186141E+10
March 0.250890E+10 0.120997E+10 0.129893E+10 0.342627E+10 0.179734E+10
April 0.266441E+10 0.120504E+10 0.145937E+10 0.411587E+10 0.114414E+10
May 0.283783E+10 0.123054E+10 0.160729E+10 0.524940E+10 0.342158E+09
June 0.278520E+10 0.110453E+10 0.168067E+10 0.533579E+10 0.283436E+09
July 0.277484E+10 0.101544E+10 0.175940E+10 0.532398E+10 0.189052E+09
August 0.255693E+10 0.879093E+09 0.167784E+10 0.491499E+10 0.272204E+09
September 0.219191E+10 0.753571E+09 0.143834E+10 0.402295E+10 0.367184E+09
October 0.223826E+10 0.944538E+09 0.129372E+10 0.390226E+10 0.722520E+09
November 0.191773E+10 0.978309E+09 0.939421E+09 0.269257E+10 0.154310E+10
December 0.156024E+10 0.706755E+09 0.853486E+09 0.196955E+10 0.211920E+10
           
Annual Sum or Average 0.278780E+11 0.119331E+11 0.159449E+11 0.457199E+11 0.130630E+11
Minimum of Months 0.156024E+10 0.706755E+09 0.853486E+09 0.196955E+10 0.189052E+09
Maximum of Months 0.283783E+10 0.123054E+10 0.175940E+10 0.533579E+10 0.242124E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.645276E+10 0.460194E+10 0.185082E+10 0.917705E+10 0.387761E+10
February 0.528594E+10 0.342150E+10 0.186444E+10 0.768646E+10 0.300114E+10
March 0.373623E+10 0.168616E+10 0.205006E+10 0.560316E+10 0.288994E+10
April 0.267991E+10 0.627970E+09 0.205194E+10 0.445763E+10 0.182147E+10
May 0.211590E+10 89922872.05 0.202598E+10 0.439244E+10 0.503093E+09
June 0.202273E+10 18853748.06 0.200387E+10 0.433441E+10 0.412132E+09
July 0.218805E+10 40216078.06 0.214783E+10 0.466583E+10 0.261074E+09
August 0.257412E+10 0.308972E+09 0.226515E+10 0.547319E+10 0.424211E+09
September 0.298889E+10 0.787698E+09 0.220119E+10 0.585035E+10 0.609196E+09
October 0.479186E+10 0.249610E+10 0.229575E+10 0.857975E+10 0.124751E+10
November 0.590124E+10 0.406306E+10 0.183817E+10 0.911103E+10 0.254679E+10
December 0.630513E+10 0.452801E+10 0.177712E+10 0.932402E+10 0.344579E+10
           
Annual Sum or Average 0.470427E+11 0.226704E+11 0.243723E+11 0.786553E+11 0.210399E+11
Minimum of Months 0.202273E+10 18853748.06 0.177712E+10 0.433441E+10 0.261074E+09
Maximum of Months 0.645276E+10 0.460194E+10 0.229575E+10 0.932402E+10 0.387761E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.203729E+10 0.110165E+10 0.935636E+09 0.262898E+10 0.266670E+10
February 0.208344E+10 0.105451E+10 0.102893E+10 0.277539E+10 0.207461E+10
March 0.227345E+10 0.100640E+10 0.126705E+10 0.313364E+10 0.199327E+10
April 0.273260E+10 0.125705E+10 0.147555E+10 0.425073E+10 0.130042E+10
May 0.234823E+10 0.764941E+09 0.158329E+10 0.446153E+10 0.417432E+09
June 0.252447E+10 0.885198E+09 0.163927E+10 0.488146E+10 0.361582E+09
July 0.238118E+10 0.660502E+09 0.172068E+10 0.461895E+10 0.254273E+09
August 0.240767E+10 0.737022E+09 0.167065E+10 0.466935E+10 0.354875E+09
September 0.214554E+10 0.736024E+09 0.140952E+10 0.395761E+10 0.445128E+09
October 0.226981E+10 0.980761E+09 0.128905E+10 0.401020E+10 0.852091E+09
November 0.188274E+10 0.946191E+09 0.936552E+09 0.276200E+10 0.173898E+10
December 0.187140E+10 0.995187E+09 0.876217E+09 0.253135E+10 0.232540E+10
           
Annual Sum or Average 0.269578E+11 0.111254E+11 0.158324E+11 0.446812E+11 0.147848E+11
Minimum of Months 0.187140E+10 0.660502E+09 0.876217E+09 0.253135E+10 0.254273E+09
Maximum of Months 0.273260E+10 0.125705E+10 0.172068E+10 0.488146E+10 0.266670E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111635E+10 0.00 0.111635E+10 0.959547E+09 0.353917E+10
February 0.118957E+10 0.00 0.118957E+10 0.112689E+10 0.268643E+10
March 0.152787E+10 0.00 0.152787E+10 0.171465E+10 0.260879E+10
April 0.174505E+10 7162306.50 0.173789E+10 0.246091E+10 0.164909E+10
May 0.204249E+10 74709672.45 0.196778E+10 0.412707E+10 0.519488E+09
June 0.224782E+10 0.155644E+09 0.209218E+10 0.471058E+10 0.439874E+09
July 0.225408E+10 85876258.80 0.216820E+10 0.468043E+10 0.299608E+09
August 0.201857E+10 15876296.36 0.200269E+10 0.423673E+10 0.417829E+09
September 0.168734E+10 129958.71 0.168721E+10 0.327515E+10 0.556306E+09
October 0.151514E+10 0.00 0.151514E+10 0.276516E+10 0.105626E+10
November 0.111313E+10 0.00 0.111313E+10 0.134400E+10 0.218733E+10
December 0.103778E+10 0.00 0.103778E+10 0.100660E+10 0.301656E+10
           
Annual Sum or Average 0.194952E+11 0.339399E+09 0.191558E+11 0.324077E+11 0.189767E+11
Minimum of Months 0.103778E+10 0.00 0.103778E+10 0.959547E+09 0.299608E+09
Maximum of Months 0.225408E+10 0.155644E+09 0.216820E+10 0.471058E+10 0.353917E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.191536E+10 0.975310E+09 0.940054E+09 0.239372E+10 0.223989E+10
February 0.192642E+10 0.930024E+09 0.996395E+09 0.250284E+10 0.172521E+10
March 0.250890E+10 0.120997E+10 0.129893E+10 0.345296E+10 0.170466E+10
April 0.266441E+10 0.120504E+10 0.145937E+10 0.410283E+10 0.112832E+10
May 0.283783E+10 0.123054E+10 0.160729E+10 0.519537E+10 0.367235E+09
June 0.278520E+10 0.110453E+10 0.168067E+10 0.527897E+10 0.308307E+09
July 0.277484E+10 0.101544E+10 0.175940E+10 0.526009E+10 0.210357E+09
August 0.255693E+10 0.879093E+09 0.167784E+10 0.486047E+10 0.294742E+09
September 0.219191E+10 0.753571E+09 0.143834E+10 0.397690E+10 0.389540E+09
October 0.223826E+10 0.944538E+09 0.129372E+10 0.387708E+10 0.717632E+09
November 0.191773E+10 0.978309E+09 0.939421E+09 0.273508E+10 0.144069E+10
December 0.156024E+10 0.706755E+09 0.853486E+09 0.202426E+10 0.196169E+10
           
Annual Sum or Average 0.278780E+11 0.119331E+11 0.159449E+11 0.456606E+11 0.124883E+11
Minimum of Months 0.156024E+10 0.706755E+09 0.853486E+09 0.202426E+10 0.210357E+09
Maximum of Months 0.283783E+10 0.123054E+10 0.175940E+10 0.527897E+10 0.223989E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.645276E+10 0.460194E+10 0.185082E+10 0.925790E+10 0.361971E+10
February 0.528594E+10 0.342150E+10 0.186444E+10 0.775161E+10 0.280477E+10
March 0.373623E+10 0.168616E+10 0.205006E+10 0.563790E+10 0.273314E+10
April 0.267991E+10 0.627970E+09 0.205194E+10 0.444243E+10 0.178261E+10
May 0.211590E+10 89922872.05 0.202598E+10 0.431973E+10 0.541430E+09
June 0.202273E+10 18853748.06 0.200387E+10 0.425656E+10 0.449428E+09
July 0.218805E+10 40216078.06 0.214783E+10 0.457032E+10 0.290903E+09
August 0.257412E+10 0.308972E+09 0.226515E+10 0.539454E+10 0.459819E+09
September 0.298889E+10 0.787698E+09 0.220119E+10 0.578546E+10 0.642167E+09
October 0.479186E+10 0.249610E+10 0.229575E+10 0.853528E+10 0.124584E+10
November 0.590124E+10 0.406306E+10 0.183817E+10 0.914252E+10 0.241813E+10
December 0.630513E+10 0.452801E+10 0.177712E+10 0.938119E+10 0.321947E+10
           
Annual Sum or Average 0.470427E+11 0.226704E+11 0.243723E+11 0.784754E+11 0.202074E+11
Minimum of Months 0.202273E+10 18853748.06 0.177712E+10 0.425656E+10 0.290903E+09
Maximum of Months 0.645276E+10 0.460194E+10 0.229575E+10 0.938119E+10 0.361971E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.203729E+10 0.110165E+10 0.935636E+09 0.266889E+10 0.248998E+10
February 0.208344E+10 0.105451E+10 0.102893E+10 0.280680E+10 0.193774E+10
March 0.227345E+10 0.100640E+10 0.126705E+10 0.315361E+10 0.188820E+10
April 0.273260E+10 0.125705E+10 0.147555E+10 0.424014E+10 0.126970E+10
May 0.234823E+10 0.764941E+09 0.158329E+10 0.442019E+10 0.434928E+09
June 0.252447E+10 0.885198E+09 0.163927E+10 0.483491E+10 0.377956E+09
July 0.238118E+10 0.660502E+09 0.172068E+10 0.456834E+10 0.266035E+09
August 0.240767E+10 0.737022E+09 0.167065E+10 0.462379E+10 0.371820E+09
September 0.214554E+10 0.736024E+09 0.140952E+10 0.392260E+10 0.458805E+09
October 0.226981E+10 0.980761E+09 0.128905E+10 0.399084E+10 0.841855E+09
November 0.188274E+10 0.946191E+09 0.936552E+09 0.279184E+10 0.162936E+10
December 0.187140E+10 0.995187E+09 0.876217E+09 0.256678E+10 0.216726E+10
           
Annual Sum or Average 0.269578E+11 0.111254E+11 0.158324E+11 0.445887E+11 0.141337E+11
Minimum of Months 0.187140E+10 0.660502E+09 0.876217E+09 0.256678E+10 0.266035E+09
Maximum of Months 0.273260E+10 0.125705E+10 0.172068E+10 0.483491E+10 0.248998E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 274.92 1635.74 416.79 0.00 416.79 0.00 0.00
February 383.98 1391.20 491.71 0.00 491.71 0.00 0.00
March 566.95 1178.97 570.43 0.00 570.43 0.00 0.00
April 919.55 700.15 673.24 2.76 670.47 0.00 0.00
May 1557.71 187.68 762.57 27.89 734.67 0.00 0.00
June 1839.73 151.96 867.20 60.05 807.15 0.00 0.00
July 1769.91 95.38 841.56 32.06 809.50 0.00 0.00
August 1591.47 141.14 753.63 5.93 747.71 0.00 0.00
September 1272.98 225.31 650.97 0.05 650.92 0.00 0.00
October 1017.71 439.13 565.68 0.00 565.68 0.00 0.00
November 442.66 1058.78 429.44 0.00 429.44 0.00 0.00
December 292.79 1440.96 387.46 0.00 387.46 0.00 0.00
               
Annual Sum or Average 997.85 717.07 618.18 10.76 607.42 0.00 0.00
Minimum of Months 274.92 95.38 387.46 0.00 387.46 0.00 0.00
Maximum of Months 1839.73 1635.74 867.20 60.05 809.50 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 835.40 998.63 715.12 364.14 350.98 0.00 0.00
February 988.94 842.13 796.31 384.44 411.87 0.00 0.00
March 1272.70 712.89 936.72 451.75 484.97 0.00 0.00
April 1600.77 432.13 1027.94 464.91 563.03 0.00 0.00
May 1975.02 122.94 1059.53 459.43 600.10 0.00 0.00
June 2074.62 92.72 1074.54 426.13 648.41 0.00 0.00
July 2007.89 51.63 1036.01 379.12 656.89 0.00 0.00
August 1852.34 77.96 954.65 328.22 626.44 0.00 0.00
September 1559.65 144.70 845.65 290.73 554.92 0.00 0.00
October 1464.36 272.36 835.67 352.65 483.02 0.00 0.00
November 1029.57 636.19 739.87 377.44 362.43 0.00 0.00
December 713.35 866.96 582.53 263.87 318.66 0.00 0.00
               
Annual Sum or Average 1450.36 435.50 884.01 378.40 505.61 0.00 0.00
Minimum of Months 713.35 51.63 582.53 263.87 318.66 0.00 0.00
Maximum of Months 2074.62 998.63 1074.54 464.91 656.89 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3446.45 1484.46 2409.11 1718.11 691.00 0.00 0.00
February 3190.42 1282.11 2184.93 1414.26 770.67 0.00 0.00
March 2092.07 1130.03 1394.91 629.52 765.39 0.00 0.00
April 1716.68 719.75 1033.89 242.26 791.63 0.00 0.00
May 1632.67 193.88 789.97 33.57 756.40 0.00 0.00
June 1661.16 156.58 780.36 7.27 773.08 0.00 0.00
July 1727.87 94.18 816.91 15.01 801.89 0.00 0.00
August 2034.21 152.97 961.05 115.35 845.69 0.00 0.00
September 2261.53 244.54 1153.09 303.89 849.20 0.00 0.00
October 3220.31 466.56 1789.02 931.91 857.12 0.00 0.00
November 3531.43 1006.68 2276.64 1567.49 709.16 0.00 0.00
December 3491.52 1336.20 2353.99 1690.51 663.49 0.00 0.00
               
Annual Sum or Average 2497.13 685.84 1491.68 718.85 772.82 0.00 0.00
Minimum of Months 1632.67 94.18 780.36 7.27 663.49 0.00 0.00
Maximum of Months 3531.43 1484.46 2409.11 1718.11 857.12 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 943.97 1130.26 760.64 411.31 349.33 0.00 0.00
February 1101.21 1005.71 861.21 435.89 425.32 0.00 0.00
March 1124.11 891.25 848.81 375.75 473.07 0.00 0.00
April 1600.75 585.81 1054.25 484.97 569.27 0.00 0.00
May 1651.89 176.03 876.73 285.60 591.14 0.00 0.00
June 1861.28 162.06 973.95 341.51 632.44 0.00 0.00
July 1686.96 124.77 889.03 246.60 642.43 0.00 0.00
August 1699.33 176.39 898.93 275.17 623.75 0.00 0.00
September 1512.75 202.78 827.76 283.96 543.80 0.00 0.00
October 1471.50 370.51 847.45 366.18 481.28 0.00 0.00
November 1018.88 811.90 726.37 365.04 361.33 0.00 0.00
December 887.57 1084.78 698.71 371.56 327.14 0.00 0.00
               
Annual Sum or Average 1381.01 557.84 854.83 352.79 502.04 0.00 0.00
Minimum of Months 887.57 124.77 698.71 246.60 327.14 0.00 0.00
Maximum of Months 1861.28 1130.26 1054.25 484.97 642.43 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 332.34 1436.20 416.80 0.00 416.80 0.00 0.00
February 441.01 1210.23 491.72 0.00 491.72 0.00 0.00
March 622.28 1041.42 570.44 0.00 570.44 0.00 0.00
April 949.69 654.22 673.25 2.76 670.48 0.00 0.00
May 1567.97 180.07 762.58 27.89 734.69 0.00 0.00
June 1848.72 155.96 867.22 60.05 807.17 0.00 0.00
July 1782.36 100.16 841.58 32.06 809.51 0.00 0.00
August 1610.03 143.96 753.65 5.93 747.72 0.00 0.00
September 1289.32 203.22 650.98 0.05 650.93 0.00 0.00
October 1041.90 401.04 565.69 0.00 565.69 0.00 0.00
November 493.62 921.39 429.45 0.00 429.45 0.00 0.00
December 350.99 1229.70 387.46 0.00 387.46 0.00 0.00
               
Annual Sum or Average 1031.05 636.82 618.19 10.76 607.43 0.00 0.00
Minimum of Months 332.34 100.16 387.46 0.00 387.46 0.00 0.00
Maximum of Months 1848.72 1436.20 867.22 60.05 809.51 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 865.32 903.99 715.11 364.14 350.98 0.00 0.00
February 1012.13 769.43 796.30 384.43 411.87 0.00 0.00
March 1279.22 671.05 936.72 451.75 484.96 0.00 0.00
April 1587.91 441.41 1027.94 464.91 563.03 0.00 0.00
May 1959.90 127.75 1059.53 459.43 600.10 0.00 0.00
June 2058.56 109.35 1074.54 426.13 648.41 0.00 0.00
July 1987.75 70.58 1036.01 379.12 656.88 0.00 0.00
August 1835.05 101.63 954.65 328.22 626.43 0.00 0.00
September 1552.07 141.66 845.64 290.73 554.91 0.00 0.00
October 1456.94 269.76 835.67 352.65 483.02 0.00 0.00
November 1038.80 595.33 739.86 377.43 362.43 0.00 0.00
December 735.35 791.22 582.53 263.87 318.66 0.00 0.00
               
Annual Sum or Average 1449.77 414.22 884.01 378.40 505.61 0.00 0.00
Minimum of Months 735.35 70.58 582.53 263.87 318.66 0.00 0.00
Maximum of Months 2058.56 903.99 1074.54 464.91 656.88 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3426.32 1447.73 2409.18 1718.17 691.02 0.00 0.00
February 3177.27 1240.55 2184.99 1414.31 770.68 0.00 0.00
March 2091.98 1078.98 1394.95 629.54 765.41 0.00 0.00
April 1719.76 702.73 1033.92 242.27 791.64 0.00 0.00
May 1639.95 187.83 789.99 33.57 756.41 0.00 0.00
June 1672.22 159.00 780.37 7.27 773.10 0.00 0.00
July 1742.02 97.47 816.92 15.01 801.91 0.00 0.00
August 2043.46 158.38 961.07 115.36 845.71 0.00 0.00
September 2257.08 235.03 1153.12 303.90 849.22 0.00 0.00
October 3203.31 465.77 1789.07 931.94 857.14 0.00 0.00
November 3515.06 982.56 2276.71 1567.54 709.17 0.00 0.00
December 3481.19 1286.51 2354.07 1690.56 663.50 0.00 0.00
               
Annual Sum or Average 2494.14 667.17 1491.72 718.87 772.84 0.00 0.00
Minimum of Months 1639.95 97.47 780.37 7.27 663.50 0.00 0.00
Maximum of Months 3515.06 1447.73 2409.18 1718.17 857.14 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 981.55 995.63 760.64 411.31 349.33 0.00 0.00
February 1147.23 857.56 861.21 435.89 425.32 0.00 0.00
March 1169.97 744.20 848.81 375.75 473.06 0.00 0.00
April 1639.94 501.71 1054.25 484.97 569.27 0.00 0.00
May 1665.74 155.85 876.73 285.60 591.13 0.00 0.00
June 1883.28 139.50 973.95 341.51 632.43 0.00 0.00
July 1724.52 94.93 889.03 246.60 642.43 0.00 0.00
August 1743.34 132.50 898.92 275.17 623.75 0.00 0.00
September 1526.86 171.73 827.76 283.96 543.80 0.00 0.00
October 1497.24 318.13 847.45 366.17 481.28 0.00 0.00
November 1065.59 670.90 726.37 365.04 361.32 0.00 0.00
December 945.10 868.20 698.70 371.56 327.14 0.00 0.00
               
Annual Sum or Average 1416.83 468.82 854.83 352.79 502.04 0.00 0.00
Minimum of Months 945.10 94.93 698.70 246.60 327.14 0.00 0.00
Maximum of Months 1883.28 995.63 1054.25 484.97 642.43 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 358.25 1321.37 416.80 0.00 416.80 0.00 0.00
February 465.81 1110.46 491.72 0.00 491.72 0.00 0.00
March 640.18 974.01 570.44 0.00 570.44 0.00 0.00
April 949.43 636.22 673.25 2.76 670.48 0.00 0.00
May 1540.87 193.95 762.58 27.89 734.69 0.00 0.00
June 1817.36 169.70 867.22 60.05 807.17 0.00 0.00
July 1747.47 111.86 841.58 32.06 809.51 0.00 0.00
August 1581.81 156.00 753.65 5.93 747.72 0.00 0.00
September 1263.56 214.62 650.98 0.05 650.93 0.00 0.00
October 1032.39 394.36 565.69 0.00 565.69 0.00 0.00
November 518.52 843.88 429.45 0.00 429.45 0.00 0.00
December 375.82 1126.25 387.46 0.00 387.46 0.00 0.00
               
Annual Sum or Average 1027.64 601.75 618.19 10.76 607.43 0.00 0.00
Minimum of Months 358.25 111.86 387.46 0.00 387.46 0.00 0.00
Maximum of Months 1817.36 1321.37 867.22 60.05 809.51 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 893.71 836.28 715.11 364.14 350.98 0.00 0.00
February 1034.57 713.13 796.30 384.43 411.87 0.00 0.00
March 1289.19 636.45 936.72 451.75 484.96 0.00 0.00
April 1582.88 435.31 1027.94 464.91 563.03 0.00 0.00
May 1939.73 137.11 1059.53 459.43 600.10 0.00 0.00
June 2036.64 118.95 1074.54 426.13 648.41 0.00 0.00
July 1963.89 78.54 1036.01 379.12 656.88 0.00 0.00
August 1814.69 110.04 954.65 328.22 626.43 0.00 0.00
September 1534.30 150.29 845.64 290.73 554.91 0.00 0.00
October 1447.54 267.93 835.67 352.65 483.02 0.00 0.00
November 1055.20 555.82 739.86 377.43 362.43 0.00 0.00
December 755.77 732.41 582.53 263.87 318.66 0.00 0.00
               
Annual Sum or Average 1447.89 396.00 884.01 378.40 505.61 0.00 0.00
Minimum of Months 755.77 78.54 582.53 263.87 318.66 0.00 0.00
Maximum of Months 2036.64 836.28 1074.54 464.91 656.88 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3456.51 1351.44 2409.18 1718.17 691.02 0.00 0.00
February 3204.20 1159.38 2184.99 1414.31 770.68 0.00 0.00
March 2104.95 1020.44 1394.95 629.54 765.41 0.00 0.00
April 1713.90 687.74 1033.92 242.27 791.64 0.00 0.00
May 1612.80 202.15 789.99 33.57 756.41 0.00 0.00
June 1642.19 173.39 780.37 7.27 773.10 0.00 0.00
July 1706.36 108.61 816.92 15.01 801.91 0.00 0.00
August 2014.09 171.68 961.07 115.36 845.71 0.00 0.00
September 2232.05 247.75 1153.12 303.90 849.22 0.00 0.00
October 3186.71 465.14 1789.07 931.94 857.14 0.00 0.00
November 3527.21 932.92 2276.71 1567.54 709.17 0.00 0.00
December 3502.53 1202.01 2354.07 1690.56 663.50 0.00 0.00
               
Annual Sum or Average 2488.44 640.77 1491.72 718.87 772.84 0.00 0.00
Minimum of Months 1612.80 108.61 780.37 7.27 663.50 0.00 0.00
Maximum of Months 3527.21 1351.44 2409.18 1718.17 857.14 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 996.45 929.65 760.64 411.31 349.33 0.00 0.00
February 1160.22 800.98 861.21 435.89 425.32 0.00 0.00
March 1177.42 704.97 848.81 375.75 473.06 0.00 0.00
April 1635.86 489.85 1054.25 484.97 569.27 0.00 0.00
May 1650.31 162.38 876.73 285.60 591.13 0.00 0.00
June 1865.32 145.82 973.95 341.51 632.43 0.00 0.00
July 1705.62 99.33 889.03 246.60 642.43 0.00 0.00
August 1726.33 138.82 898.92 275.17 623.75 0.00 0.00
September 1513.35 177.01 827.76 283.96 543.80 0.00 0.00
October 1490.01 314.31 847.45 366.17 481.28 0.00 0.00
November 1077.10 628.61 726.37 365.04 361.32 0.00 0.00
December 958.33 809.16 698.70 371.56 327.14 0.00 0.00
               
Annual Sum or Average 1413.90 448.18 854.83 352.79 502.04 0.00 0.00
Minimum of Months 958.33 99.33 698.70 246.60 327.14 0.00 0.00
Maximum of Months 1865.32 929.65 1054.25 484.97 642.43 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.736342E+09 0.438118E+10 0.111634E+10 0.00 0.111634E+10 0.00 0.00
February 0.928929E+09 0.336560E+10 0.118956E+10 0.00 0.118956E+10 0.00 0.00
March 0.151851E+10 0.315775E+10 0.152784E+10 0.00 0.152784E+10 0.00 0.00
April 0.238347E+10 0.181479E+10 0.174503E+10 7162092.90 0.173786E+10 0.00 0.00
May 0.417218E+10 0.502671E+09 0.204246E+10 74707444.46 0.196775E+10 0.00 0.00
June 0.476858E+10 0.393878E+09 0.224778E+10 0.155640E+09 0.209214E+10 0.00 0.00
July 0.474052E+10 0.255477E+09 0.225404E+10 85873697.81 0.216816E+10 0.00 0.00
August 0.426259E+10 0.378033E+09 0.201853E+10 15875822.90 0.200266E+10 0.00 0.00
September 0.329956E+10 0.584000E+09 0.168731E+10 129954.84 0.168718E+10 0.00 0.00
October 0.272582E+10 0.117618E+10 0.151512E+10 0.00 0.151512E+10 0.00 0.00
November 0.114737E+10 0.274436E+10 0.111311E+10 0.00 0.111311E+10 0.00 0.00
December 0.784220E+09 0.385946E+10 0.103776E+10 0.00 0.103776E+10 0.00 0.00
               
Annual Sum or Average 0.314681E+11 0.226134E+11 0.194949E+11 0.339389E+09 0.191555E+11 0.00 0.00
Minimum of Months 0.736342E+09 0.255477E+09 0.103776E+10 0.00 0.103776E+10 0.00 0.00
Maximum of Months 0.476858E+10 0.438118E+10 0.225404E+10 0.155640E+09 0.216816E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.223753E+10 0.267473E+10 0.191537E+10 0.975314E+09 0.940057E+09 0.00 0.00
February 0.239243E+10 0.203728E+10 0.192643E+10 0.930028E+09 0.996399E+09 0.00 0.00
March 0.340879E+10 0.190940E+10 0.250891E+10 0.120998E+10 0.129893E+10 0.00 0.00
April 0.414919E+10 0.112008E+10 0.266442E+10 0.120504E+10 0.145938E+10 0.00 0.00
May 0.528989E+10 0.329273E+09 0.283785E+10 0.123054E+10 0.160730E+10 0.00 0.00
June 0.537741E+10 0.240325E+09 0.278521E+10 0.110454E+10 0.168067E+10 0.00 0.00
July 0.537793E+10 0.138281E+09 0.277485E+10 0.101545E+10 0.175941E+10 0.00 0.00
August 0.496132E+10 0.208810E+09 0.255694E+10 0.879096E+09 0.167785E+10 0.00 0.00
September 0.404261E+10 0.375065E+09 0.219192E+10 0.753574E+09 0.143834E+10 0.00 0.00
October 0.392213E+10 0.729492E+09 0.223827E+10 0.944542E+09 0.129373E+10 0.00 0.00
November 0.266864E+10 0.164900E+10 0.191774E+10 0.978313E+09 0.939424E+09 0.00 0.00
December 0.191063E+10 0.232208E+10 0.156025E+10 0.706758E+09 0.853490E+09 0.00 0.00
               
Annual Sum or Average 0.457385E+11 0.137338E+11 0.278782E+11 0.119332E+11 0.159450E+11 0.00 0.00
Minimum of Months 0.191063E+10 0.138281E+09 0.156025E+10 0.706758E+09 0.853490E+09 0.00 0.00
Maximum of Months 0.537793E+10 0.267473E+10 0.283785E+10 0.123054E+10 0.175941E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.923098E+10 0.397598E+10 0.645256E+10 0.460178E+10 0.185078E+10 0.00 0.00
February 0.771825E+10 0.310168E+10 0.528578E+10 0.342138E+10 0.186440E+10 0.00 0.00
March 0.560341E+10 0.302668E+10 0.373613E+10 0.168611E+10 0.205002E+10 0.00 0.00
April 0.444965E+10 0.186558E+10 0.267985E+10 0.627949E+09 0.205190E+10 0.00 0.00
May 0.437294E+10 0.519275E+09 0.211586E+10 89919926.79 0.202594E+10 0.00 0.00
June 0.430573E+10 0.405853E+09 0.202269E+10 18853130.54 0.200383E+10 0.00 0.00
July 0.462793E+10 0.252246E+09 0.218800E+10 40214760.86 0.214779E+10 0.00 0.00
August 0.544842E+10 0.409718E+09 0.257406E+10 0.308962E+09 0.226510E+10 0.00 0.00
September 0.586188E+10 0.633852E+09 0.298881E+10 0.787672E+09 0.220114E+10 0.00 0.00
October 0.862528E+10 0.124963E+10 0.479172E+10 0.249602E+10 0.229570E+10 0.00 0.00
November 0.915347E+10 0.260932E+10 0.590106E+10 0.406293E+10 0.183813E+10 0.00 0.00
December 0.935169E+10 0.357887E+10 0.630494E+10 0.452786E+10 0.177708E+10 0.00 0.00
               
Annual Sum or Average 0.787496E+11 0.216287E+11 0.470415E+11 0.226697E+11 0.243718E+11 0.00 0.00
Minimum of Months 0.430573E+10 0.252246E+09 0.202269E+10 18853130.54 0.177708E+10 0.00 0.00
Maximum of Months 0.935169E+10 0.397598E+10 0.645256E+10 0.460178E+10 0.229570E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.252832E+10 0.302728E+10 0.203730E+10 0.110166E+10 0.935640E+09 0.00 0.00
February 0.266404E+10 0.243302E+10 0.208345E+10 0.105451E+10 0.102894E+10 0.00 0.00
March 0.301081E+10 0.238711E+10 0.227346E+10 0.100641E+10 0.126706E+10 0.00 0.00
April 0.414915E+10 0.151842E+10 0.273261E+10 0.125705E+10 0.147556E+10 0.00 0.00
May 0.442443E+10 0.471484E+09 0.234824E+10 0.764944E+09 0.158330E+10 0.00 0.00
June 0.482443E+10 0.420065E+09 0.252448E+10 0.885201E+09 0.163928E+10 0.00 0.00
July 0.451834E+10 0.334173E+09 0.238119E+10 0.660505E+09 0.172068E+10 0.00 0.00
August 0.455149E+10 0.472445E+09 0.240768E+10 0.737025E+09 0.167066E+10 0.00 0.00
September 0.392104E+10 0.525598E+09 0.214555E+10 0.736027E+09 0.140952E+10 0.00 0.00
October 0.394127E+10 0.992387E+09 0.226982E+10 0.980765E+09 0.128906E+10 0.00 0.00
November 0.264095E+10 0.210445E+10 0.188275E+10 0.946195E+09 0.936555E+09 0.00 0.00
December 0.237728E+10 0.290547E+10 0.187141E+10 0.995191E+09 0.876220E+09 0.00 0.00
               
Annual Sum or Average 0.435515E+11 0.175919E+11 0.269580E+11 0.111255E+11 0.158325E+11 0.00 0.00
Minimum of Months 0.237728E+10 0.334173E+09 0.187141E+10 0.660505E+09 0.876220E+09 0.00 0.00
Maximum of Months 0.482443E+10 0.302728E+10 0.273261E+10 0.125705E+10 0.172068E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.890146E+09 0.384671E+10 0.111635E+10 0.00 0.111635E+10 0.00 0.00
February 0.106688E+10 0.292778E+10 0.118957E+10 0.00 0.118957E+10 0.00 0.00
March 0.166671E+10 0.278933E+10 0.152787E+10 0.00 0.152787E+10 0.00 0.00
April 0.246159E+10 0.169575E+10 0.174505E+10 7162306.50 0.173789E+10 0.00 0.00
May 0.419965E+10 0.482310E+09 0.204249E+10 74709672.45 0.196778E+10 0.00 0.00
June 0.479188E+10 0.404244E+09 0.224782E+10 0.155644E+09 0.209218E+10 0.00 0.00
July 0.477388E+10 0.268263E+09 0.225408E+10 85876258.80 0.216820E+10 0.00 0.00
August 0.431230E+10 0.385574E+09 0.201857E+10 15876296.36 0.200269E+10 0.00 0.00
September 0.334191E+10 0.526733E+09 0.168734E+10 129958.71 0.168721E+10 0.00 0.00
October 0.279063E+10 0.107416E+10 0.151514E+10 0.00 0.151514E+10 0.00 0.00
November 0.127947E+10 0.238825E+10 0.111313E+10 0.00 0.111313E+10 0.00 0.00
December 0.940096E+09 0.329364E+10 0.103778E+10 0.00 0.103778E+10 0.00 0.00
               
Annual Sum or Average 0.325151E+11 0.200827E+11 0.194952E+11 0.339399E+09 0.191558E+11 0.00 0.00
Minimum of Months 0.890146E+09 0.268263E+09 0.103778E+10 0.00 0.103778E+10 0.00 0.00
Maximum of Months 0.479188E+10 0.384671E+10 0.225408E+10 0.155644E+09 0.216820E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.231768E+10 0.242124E+10 0.191536E+10 0.975310E+09 0.940054E+09 0.00 0.00
February 0.244856E+10 0.186141E+10 0.192642E+10 0.930024E+09 0.996395E+09 0.00 0.00
March 0.342627E+10 0.179734E+10 0.250890E+10 0.120997E+10 0.129893E+10 0.00 0.00
April 0.411587E+10 0.114414E+10 0.266441E+10 0.120504E+10 0.145937E+10 0.00 0.00
May 0.524940E+10 0.342158E+09 0.283783E+10 0.123054E+10 0.160729E+10 0.00 0.00
June 0.533579E+10 0.283436E+09 0.278520E+10 0.110453E+10 0.168067E+10 0.00 0.00
July 0.532398E+10 0.189052E+09 0.277484E+10 0.101544E+10 0.175940E+10 0.00 0.00
August 0.491499E+10 0.272204E+09 0.255693E+10 0.879093E+09 0.167784E+10 0.00 0.00
September 0.402295E+10 0.367184E+09 0.219191E+10 0.753571E+09 0.143834E+10 0.00 0.00
October 0.390226E+10 0.722520E+09 0.223826E+10 0.944538E+09 0.129372E+10 0.00 0.00
November 0.269257E+10 0.154310E+10 0.191773E+10 0.978309E+09 0.939421E+09 0.00 0.00
December 0.196955E+10 0.211920E+10 0.156024E+10 0.706755E+09 0.853486E+09 0.00 0.00
               
Annual Sum or Average 0.457199E+11 0.130630E+11 0.278780E+11 0.119331E+11 0.159449E+11 0.00 0.00
Minimum of Months 0.196955E+10 0.189052E+09 0.156024E+10 0.706755E+09 0.853486E+09 0.00 0.00
Maximum of Months 0.533579E+10 0.242124E+10 0.283783E+10 0.123054E+10 0.175940E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.917705E+10 0.387761E+10 0.645276E+10 0.460194E+10 0.185082E+10 0.00 0.00
February 0.768646E+10 0.300114E+10 0.528594E+10 0.342150E+10 0.186444E+10 0.00 0.00
March 0.560316E+10 0.288994E+10 0.373623E+10 0.168616E+10 0.205006E+10 0.00 0.00
April 0.445763E+10 0.182147E+10 0.267991E+10 0.627970E+09 0.205194E+10 0.00 0.00
May 0.439244E+10 0.503093E+09 0.211590E+10 89922872.05 0.202598E+10 0.00 0.00
June 0.433441E+10 0.412132E+09 0.202273E+10 18853748.06 0.200387E+10 0.00 0.00
July 0.466583E+10 0.261074E+09 0.218805E+10 40216078.06 0.214783E+10 0.00 0.00
August 0.547319E+10 0.424211E+09 0.257412E+10 0.308972E+09 0.226515E+10 0.00 0.00
September 0.585035E+10 0.609196E+09 0.298889E+10 0.787698E+09 0.220119E+10 0.00 0.00
October 0.857975E+10 0.124751E+10 0.479186E+10 0.249610E+10 0.229575E+10 0.00 0.00
November 0.911103E+10 0.254679E+10 0.590124E+10 0.406306E+10 0.183817E+10 0.00 0.00
December 0.932402E+10 0.344579E+10 0.630513E+10 0.452801E+10 0.177712E+10 0.00 0.00
               
Annual Sum or Average 0.786553E+11 0.210399E+11 0.470427E+11 0.226704E+11 0.243723E+11 0.00 0.00
Minimum of Months 0.433441E+10 0.261074E+09 0.202273E+10 18853748.06 0.177712E+10 0.00 0.00
Maximum of Months 0.932402E+10 0.387761E+10 0.645276E+10 0.460194E+10 0.229575E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.262898E+10 0.266670E+10 0.203729E+10 0.110165E+10 0.935636E+09 0.00 0.00
February 0.277539E+10 0.207461E+10 0.208344E+10 0.105451E+10 0.102893E+10 0.00 0.00
March 0.313364E+10 0.199327E+10 0.227345E+10 0.100640E+10 0.126705E+10 0.00 0.00
April 0.425073E+10 0.130042E+10 0.273260E+10 0.125705E+10 0.147555E+10 0.00 0.00
May 0.446153E+10 0.417432E+09 0.234823E+10 0.764941E+09 0.158329E+10 0.00 0.00
June 0.488146E+10 0.361582E+09 0.252447E+10 0.885198E+09 0.163927E+10 0.00 0.00
July 0.461895E+10 0.254273E+09 0.238118E+10 0.660502E+09 0.172068E+10 0.00 0.00
August 0.466935E+10 0.354875E+09 0.240767E+10 0.737022E+09 0.167065E+10 0.00 0.00
September 0.395761E+10 0.445128E+09 0.214554E+10 0.736024E+09 0.140952E+10 0.00 0.00
October 0.401020E+10 0.852091E+09 0.226981E+10 0.980761E+09 0.128905E+10 0.00 0.00
November 0.276200E+10 0.173898E+10 0.188274E+10 0.946191E+09 0.936552E+09 0.00 0.00
December 0.253135E+10 0.232540E+10 0.187140E+10 0.995187E+09 0.876217E+09 0.00 0.00
               
Annual Sum or Average 0.446812E+11 0.147848E+11 0.269578E+11 0.111254E+11 0.158324E+11 0.00 0.00
Minimum of Months 0.253135E+10 0.254273E+09 0.187140E+10 0.660502E+09 0.876217E+09 0.00 0.00
Maximum of Months 0.488146E+10 0.266670E+10 0.273260E+10 0.125705E+10 0.172068E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.959547E+09 0.353917E+10 0.111635E+10 0.00 0.111635E+10 0.00 0.00
February 0.112689E+10 0.268643E+10 0.118957E+10 0.00 0.118957E+10 0.00 0.00
March 0.171465E+10 0.260879E+10 0.152787E+10 0.00 0.152787E+10 0.00 0.00
April 0.246091E+10 0.164909E+10 0.174505E+10 7162306.50 0.173789E+10 0.00 0.00
May 0.412707E+10 0.519488E+09 0.204249E+10 74709672.45 0.196778E+10 0.00 0.00
June 0.471058E+10 0.439874E+09 0.224782E+10 0.155644E+09 0.209218E+10 0.00 0.00
July 0.468043E+10 0.299608E+09 0.225408E+10 85876258.80 0.216820E+10 0.00 0.00
August 0.423673E+10 0.417829E+09 0.201857E+10 15876296.36 0.200269E+10 0.00 0.00
September 0.327515E+10 0.556306E+09 0.168734E+10 129958.71 0.168721E+10 0.00 0.00
October 0.276516E+10 0.105626E+10 0.151514E+10 0.00 0.151514E+10 0.00 0.00
November 0.134400E+10 0.218733E+10 0.111313E+10 0.00 0.111313E+10 0.00 0.00
December 0.100660E+10 0.301656E+10 0.103778E+10 0.00 0.103778E+10 0.00 0.00
               
Annual Sum or Average 0.324077E+11 0.189767E+11 0.194952E+11 0.339399E+09 0.191558E+11 0.00 0.00
Minimum of Months 0.959547E+09 0.299608E+09 0.103778E+10 0.00 0.103778E+10 0.00 0.00
Maximum of Months 0.471058E+10 0.353917E+10 0.225408E+10 0.155644E+09 0.216820E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.239372E+10 0.223989E+10 0.191536E+10 0.975310E+09 0.940054E+09 0.00 0.00
February 0.250284E+10 0.172521E+10 0.192642E+10 0.930024E+09 0.996395E+09 0.00 0.00
March 0.345296E+10 0.170466E+10 0.250890E+10 0.120997E+10 0.129893E+10 0.00 0.00
April 0.410283E+10 0.112832E+10 0.266441E+10 0.120504E+10 0.145937E+10 0.00 0.00
May 0.519537E+10 0.367235E+09 0.283783E+10 0.123054E+10 0.160729E+10 0.00 0.00
June 0.527897E+10 0.308307E+09 0.278520E+10 0.110453E+10 0.168067E+10 0.00 0.00
July 0.526009E+10 0.210357E+09 0.277484E+10 0.101544E+10 0.175940E+10 0.00 0.00
August 0.486047E+10 0.294742E+09 0.255693E+10 0.879093E+09 0.167784E+10 0.00 0.00
September 0.397690E+10 0.389540E+09 0.219191E+10 0.753571E+09 0.143834E+10 0.00 0.00
October 0.387708E+10 0.717632E+09 0.223826E+10 0.944538E+09 0.129372E+10 0.00 0.00
November 0.273508E+10 0.144069E+10 0.191773E+10 0.978309E+09 0.939421E+09 0.00 0.00
December 0.202426E+10 0.196169E+10 0.156024E+10 0.706755E+09 0.853486E+09 0.00 0.00
               
Annual Sum or Average 0.456606E+11 0.124883E+11 0.278780E+11 0.119331E+11 0.159449E+11 0.00 0.00
Minimum of Months 0.202426E+10 0.210357E+09 0.156024E+10 0.706755E+09 0.853486E+09 0.00 0.00
Maximum of Months 0.527897E+10 0.223989E+10 0.283783E+10 0.123054E+10 0.175940E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.925790E+10 0.361971E+10 0.645276E+10 0.460194E+10 0.185082E+10 0.00 0.00
February 0.775161E+10 0.280477E+10 0.528594E+10 0.342150E+10 0.186444E+10 0.00 0.00
March 0.563790E+10 0.273314E+10 0.373623E+10 0.168616E+10 0.205006E+10 0.00 0.00
April 0.444243E+10 0.178261E+10 0.267991E+10 0.627970E+09 0.205194E+10 0.00 0.00
May 0.431973E+10 0.541430E+09 0.211590E+10 89922872.05 0.202598E+10 0.00 0.00
June 0.425656E+10 0.449428E+09 0.202273E+10 18853748.06 0.200387E+10 0.00 0.00
July 0.457032E+10 0.290903E+09 0.218805E+10 40216078.06 0.214783E+10 0.00 0.00
August 0.539454E+10 0.459819E+09 0.257412E+10 0.308972E+09 0.226515E+10 0.00 0.00
September 0.578546E+10 0.642167E+09 0.298889E+10 0.787698E+09 0.220119E+10 0.00 0.00
October 0.853528E+10 0.124584E+10 0.479186E+10 0.249610E+10 0.229575E+10 0.00 0.00
November 0.914252E+10 0.241813E+10 0.590124E+10 0.406306E+10 0.183817E+10 0.00 0.00
December 0.938119E+10 0.321947E+10 0.630513E+10 0.452801E+10 0.177712E+10 0.00 0.00
               
Annual Sum or Average 0.784754E+11 0.202074E+11 0.470427E+11 0.226704E+11 0.243723E+11 0.00 0.00
Minimum of Months 0.425656E+10 0.290903E+09 0.202273E+10 18853748.06 0.177712E+10 0.00 0.00
Maximum of Months 0.938119E+10 0.361971E+10 0.645276E+10 0.460194E+10 0.229575E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.266889E+10 0.248998E+10 0.203729E+10 0.110165E+10 0.935636E+09 0.00 0.00
February 0.280680E+10 0.193774E+10 0.208344E+10 0.105451E+10 0.102893E+10 0.00 0.00
March 0.315361E+10 0.188820E+10 0.227345E+10 0.100640E+10 0.126705E+10 0.00 0.00
April 0.424014E+10 0.126970E+10 0.273260E+10 0.125705E+10 0.147555E+10 0.00 0.00
May 0.442019E+10 0.434928E+09 0.234823E+10 0.764941E+09 0.158329E+10 0.00 0.00
June 0.483491E+10 0.377956E+09 0.252447E+10 0.885198E+09 0.163927E+10 0.00 0.00
July 0.456834E+10 0.266035E+09 0.238118E+10 0.660502E+09 0.172068E+10 0.00 0.00
August 0.462379E+10 0.371820E+09 0.240767E+10 0.737022E+09 0.167065E+10 0.00 0.00
September 0.392260E+10 0.458805E+09 0.214554E+10 0.736024E+09 0.140952E+10 0.00 0.00
October 0.399084E+10 0.841855E+09 0.226981E+10 0.980761E+09 0.128905E+10 0.00 0.00
November 0.279184E+10 0.162936E+10 0.188274E+10 0.946191E+09 0.936552E+09 0.00 0.00
December 0.256678E+10 0.216726E+10 0.187140E+10 0.995187E+09 0.876217E+09 0.00 0.00
               
Annual Sum or Average 0.445887E+11 0.141337E+11 0.269578E+11 0.111254E+11 0.158324E+11 0.00 0.00
Minimum of Months 0.256678E+10 0.266035E+09 0.187140E+10 0.660502E+09 0.876217E+09 0.00 0.00
Maximum of Months 0.483491E+10 0.248998E+10 0.273260E+10 0.125705E+10 0.172068E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.57 11.02 8.64 3.24 3.13 48.31 209.17 0.01
February 15.49 12.82 10.40 2.82 4.36 58.07 218.23 0.02
March 17.07 13.58 10.72 3.68 7.24 76.61 186.08 0.03
April 21.23 17.54 15.23 2.65 11.47 90.28 216.86 0.02
May 26.90 22.82 21.10 3.11 19.64 106.10 173.47 0.04
June 27.61 23.37 21.62 2.44 19.77 115.40 187.69 0.03
July 27.94 24.58 23.34 2.53 20.70 123.49 154.05 0.05
August 27.43 23.90 22.52 3.20 20.40 118.51 145.78 0.03
September 26.23 23.37 22.24 3.39 19.02 101.73 135.58 0.05
October 24.23 20.47 18.40 4.11 16.60 78.24 178.15 0.01
November 18.91 15.31 12.62 2.63 7.99 49.56 205.43 0.01
December 15.68 12.88 10.53 3.17 6.01 45.08 191.18 0.02
                 
Annual Sum or Average 21.89 18.50 16.48 3.09 13.08 84.44 183.16 0.03
Minimum of Months 13.57 11.02 8.64 2.44 3.13 45.08 135.58 0.01
Maximum of Months 27.94 24.58 23.34 4.11 20.70 123.49 218.23 0.05



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 27.00 02-JAN-14:00 18.67 14.00 1.50 17.75 146.50 0.00
February 28.30 02-FEB-12:00 20.78 17.20 6.60 17.93 127.50 748.50
March 30.00 26-MAR-13:00 19.88 14.40 3.00 19.52 288.50 548.00
April 33.30 28-APR-14:00 23.06 18.80 4.10 23.15 150.50 762.50
May 33.90 07-MAY-13:00 23.76 19.40 4.10 23.15 287.50 507.50
June 35.00 14-JUN-13:00 23.95 19.40 2.10 24.16 194.50 712.50
July 36.10 21-JUL-15:00 25.96 22.20 1.50 26.65 216.00 245.00
August 36.30 30-AUG-15:00 23.74 18.50 2.40 25.33 116.00 698.50
September 36.40 09-SEP-16:00 26.65 23.40 4.40 26.48 114.00 401.50
October 34.00 05-OCT-14:00 24.05 20.00 2.60 29.55 169.50 606.00
November 30.00 01-NOV-13:00 25.01 23.30 2.00 26.48 216.50 118.00
December 30.00 13-DEC-14:00 21.84 18.00 3.10 20.92 101.50 682.50
                 
Annual Sum or Average                
Minimum of Months 27.00   18.67 14.00 1.50 17.75 101.50 0.00
Maximum of Months 36.40   26.65 23.40 6.60 29.55 288.50 762.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 0.00 05-JAN-05:00 -0.0 -0.0 2.10 -16.0 0.00 0.00
February -3.4 05-FEB-07:10 -5.4 -9.4 4.68 -21.3 0.00 0.00
March 1.10 09-MAR-05:00 -2.1 -7.3 3.60 -14.4 0.00 0.00
April 8.30 11-APR-05:00 6.95 5.50 0.00 -6.9 0.00 0.00
May 21.10 07-MAY-00:00 19.58 18.90 0.00 11.46 0.00 0.00
June 20.60 07-JUN-01:00 18.00 16.70 3.60 10.50 0.00 0.00
July 22.20 11-JUL-19:00 21.37 21.10 2.10 20.22 0.00 0.00
August 20.20 25-AUG-23:00 20.20 20.20 5.30 11.84 0.00 0.00
September 19.20 07-SEP-17:00 19.20 19.20 2.50 16.85 35.00 7.00
October 10.00 28-OCT-04:00 5.56 0.00 3.60 -0.1 0.00 0.00
November 7.20 12-NOV-07:49 4.12 0.18 4.60 -9.0 36.00 517.00
December 0.00 21-DEC-04:00 -0.9 -2.0 2.10 -16.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -3.4   -5.4 -9.4 0.00 -21.3 0.00 0.00
Maximum of Months 22.20   21.37 21.10 5.30 20.22 36.00 517.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 22.11 31-JAN-12:00 25.00 21.00 5.70 20.92 336.50 96.00
February 21.49 24-FEB-12:00 27.70 18.80 4.10 17.75 165.00 746.50
March 22.77 30-MAR-12:00 29.40 20.00 2.50 27.14 340.00 0.00
April 25.55 28-APR-15:00 32.20 23.30 3.60 22.47 156.00 575.50
May 25.84 27-MAY-13:00 31.70 23.90 3.10 22.13 168.50 735.50
June 26.52 29-JUN-16:00 29.40 25.60 1.50 26.32 164.00 36.00
July 27.17 22-JUL-10:00 32.20 25.60 2.10 21.96 191.00 719.50
August 27.24 07-AUG-12:00 31.00 26.00 3.10 27.95 473.00 200.00
September 27.79 10-SEP-12:00 35.00 25.50 2.90 24.66 239.50 662.00
October 28.18 07-OCT-07:00 29.00 28.00 2.60 21.09 95.00 500.50
November 25.01 01-NOV-13:00 30.00 23.30 2.00 26.48 216.50 118.00
December 24.12 12-DEC-13:00 27.00 23.00 2.10 19.17 160.50 599.50
                 
Annual Sum or Average                
Minimum of Months 21.49   25.00 18.80 1.50 17.75 95.00 0.00
Maximum of Months 28.18   35.00 28.00 5.70 27.95 473.00 746.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 21.00 31-JAN-12:00 25.00 22.11 5.70 20.92 336.50 96.00
February 20.20 02-FEB-22:00 21.50 20.56 4.80 14.65 0.00 0.00
March 21.10 07-MAR-08:00 23.30 21.69 2.00 13.91 126.00 566.50
April 23.30 28-APR-15:00 32.20 25.55 3.60 22.47 156.00 575.50
May 24.40 26-MAY-08:20 27.07 25.09 3.10 23.71 252.67 47.33
June 25.60 29-JUN-14:00 27.20 26.00 5.10 24.16 335.00 238.00
July 25.60 02-JUL-05:00 26.10 25.71 2.60 19.52 30.50 8.50
August 26.60 09-AUG-18:00 26.60 26.60 1.90 19.52 26.00 23.00
September 25.50 10-SEP-12:00 35.00 27.79 2.90 24.66 239.50 662.00
October 28.00 07-OCT-07:00 29.00 28.18 2.60 21.09 95.00 500.50
November 23.80 01-NOV-10:00 26.10 24.39 2.00 22.64 228.50 113.00
December 23.00 12-DEC-13:00 27.00 24.12 2.10 19.17 160.50 599.50
                 
Annual Sum or Average                
Minimum of Months 20.20   21.50 20.56 1.90 13.91 0.00 0.00
Maximum of Months 28.00   35.00 28.18 5.70 24.66 336.50 662.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 20.46 29.60 0.00
February 18.00 13.00 16.00 20.78 36.65 0.00
March 18.00 13.00 16.00 22.23 38.94 0.00
April 18.00 13.00 16.00 24.49 49.11 0.00
May 18.00 13.00 16.00 26.95 46.95 0.00
June 18.00 13.00 16.00 28.93 51.71 0.00
July 18.00 13.00 16.00 29.89 48.43 0.00
August 18.00 13.00 16.00 29.58 45.50 0.00
September 18.00 13.00 16.00 28.08 39.22 0.00
October 18.00 13.00 16.00 25.80 37.51 0.00
November 18.00 13.00 16.00 23.35 31.26 0.00
December 18.00 13.00 16.00 21.40 27.18 0.00
             
Annual Sum or Average 18.00 13.00 16.00 25.18 40.17 0.00
Minimum of Months 18.00 13.00 16.00 20.46 27.18 0.00
Maximum of Months 18.00 13.00 16.00 29.89 51.71 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.316941E+11 -0.306723E+11 0.00 0.00 744.00 0.00 -0.102177E+10 58.98 0.00 0.00
February 0.285702E+11 -0.276466E+11 0.00 0.00 672.00 0.00 -923558399.0 58.97 0.00 0.00
March 0.322988E+11 -0.312725E+11 0.00 0.00 744.00 0.00 -0.102630E+10 58.98 0.00 0.00
April 0.276055E+11 -0.266158E+11 0.00 0.00 720.00 0.00 -989622625.1 58.96 0.00 0.00
May 0.274489E+11 -0.264265E+11 0.00 0.00 744.00 0.00 -0.102240E+10 58.96 0.00 0.00
June 0.255529E+11 -0.245617E+11 0.00 0.00 720.00 0.00 -991177991.0 58.97 0.00 0.00
July 0.236220E+11 -0.226038E+11 0.00 0.00 744.00 0.00 -0.101822E+10 58.97 0.00 0.00
August 0.260413E+11 -0.250196E+11 0.00 0.00 744.00 0.00 -0.102175E+10 58.97 0.00 0.00
September 0.248595E+11 -0.238729E+11 0.00 0.00 720.00 0.00 -986593713.7 58.98 0.00 0.00
October 0.274541E+11 -0.264366E+11 0.00 0.00 744.00 0.00 -0.101754E+10 58.97 0.00 0.00
November 0.288182E+11 -0.278329E+11 0.00 0.00 720.00 0.00 -985261849.6 58.98 0.00 0.00
December 0.302284E+11 -0.292101E+11 0.00 0.00 744.00 0.00 -0.101826E+10 58.97 0.00 0.00
                     
Annual Sum or Average 0.334194E+12 -0.322171E+12 0.00 0.00 8760.00 0.00 -0.120224E+11 58.97 0.00 0.00
Minimum of Months 0.236220E+11 -0.312725E+11 0.00 0.00 672.00 0.00 -0.102630E+10 58.96 0.00 0.00
Maximum of Months 0.322988E+11 -0.226038E+11 0.00 0.00 744.00 0.00 -923558399.0 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.51 0.48 01-JAN-07:00 6725.53 34.61 279.17 288.50 1112.85 25.01 167.17 270.67
February 295.50 0.51 0.48 01-FEB-11:39 2777.54 26.53 165.17 272.50 953.61 21.96 106.50 257.17
March 296.00 0.51 0.48 02-MAR-12:39 1216.55 16.86 0.00 306.50 703.80 19.77 50.00 258.17
April 347.33 0.53 0.48 01-APR-08:09 965.20 16.00 0.00 309.50 553.46 18.85 19.83 258.83
May 353.67 0.52 0.48 01-MAY-07:49 864.11 16.13 0.00 332.17 484.50 19.05 5.50 266.67
June 394.00 0.53 0.48 01-JUN-07:19 819.52 15.75 0.00 332.50 462.56 18.67 1.67 266.83
July 390.00 0.52 0.48 01-JUL-07:10 910.33 16.19 0.00 345.00 496.97 19.09 10.17 279.50
August 380.83 0.52 0.48 01-AUG-07:40 1062.71 16.59 0.00 335.00 567.17 19.44 36.50 281.67
September 342.17 0.52 0.48 01-SEP-07:40 1257.42 16.96 3.67 305.83 658.05 19.70 93.33 261.17
October 330.00 0.50 0.48 01-OCT-07:19 2251.76 21.48 80.50 307.17 887.59 20.92 144.50 271.17
November 308.00 0.51 0.48 01-NOV-08:09 6845.52 35.40 293.83 282.17 1061.02 22.98 131.33 262.00
December 282.83 0.50 0.48 01-DEC-07:49 6828.55 35.14 260.50 275.83 1454.25 26.98 168.17 258.83
                         
Annual Sum or Average 4027.67 0.52     2528.61 21.68 1082.83 3692.67 755.76 20.82 934.67 3192.67
Minimum of Months 282.83 0.50 0.48   819.52 15.75 0.00 272.50 462.56 18.67 1.67 257.17
Maximum of Months 394.00 0.53 0.48   6845.52 35.40 293.83 345.00 1454.25 26.98 168.17 281.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.55 0.48 01-JAN-07:00 1570.43 18.98 81.33 238.00 804.55 20.43 71.50 174.67
February 295.50 0.53 0.48 01-FEB-11:39 1735.06 19.03 71.83 237.17 943.11 22.33 72.83 191.67
March 296.00 0.52 0.48 02-MAR-12:39 1821.33 19.76 74.33 294.50 927.00 21.33 60.50 230.50
April 347.33 0.53 0.48 01-APR-07:19 1850.45 18.33 76.50 305.67 993.99 21.67 80.17 259.17
May 353.67 0.51 0.48 01-MAY-06:40 2070.86 19.07 80.83 339.67 817.13 20.95 68.50 278.17
June 394.00 0.52 0.48 01-JUN-06:19 1935.40 20.16 112.67 340.33 772.01 20.72 83.00 282.50
July 390.00 0.51 0.48 01-JUL-06:30 1808.71 18.98 87.17 347.50 765.15 20.95 95.00 285.00
August 380.83 0.52 0.48 01-AUG-06:00 1669.00 18.86 83.50 331.17 873.34 22.06 104.33 280.33
September 342.17 0.53 0.48 01-SEP-06:49 1599.61 19.10 80.50 296.00 815.11 21.96 101.50 246.33
October 330.00 0.52 0.48 01-OCT-06:00 1662.53 19.58 76.50 283.50 828.56 21.28 87.33 238.17
November 308.00 0.54 0.48 01-NOV-07:00 1267.09 17.68 56.83 236.67 703.99 21.22 72.17 189.67
December 282.83 0.54 0.48 01-DEC-07:49 1486.68 19.10 75.83 225.83 804.50 21.68 71.33 166.67
                         
Annual Sum or Average 4027.67 0.53     1718.08 19.07 957.83 3476.00 835.83 21.37 968.17 2822.83
Minimum of Months 282.83 0.51 0.48   1267.09 17.68 56.83 225.83 703.99 20.43 60.50 166.67
Maximum of Months 394.00 0.55 0.48   2070.86 20.16 112.67 347.50 993.99 22.33 104.33 285.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.58 0.48 01-JAN-09:00 401.73 12.34 0.00 194.67 265.47 15.69 0.00 54.00
February 295.50 0.55 0.48 01-FEB-11:00 463.81 13.51 0.00 215.83 307.40 16.79 0.00 112.33
March 296.00 0.53 0.48 02-MAR-12:00 548.39 14.67 0.00 282.00 348.93 17.70 0.00 156.67
April 347.33 0.53 0.48 01-APR-08:09 658.81 15.31 0.00 313.83 404.02 18.18 0.00 241.00
May 353.67 0.50 0.48 01-MAY-07:19 816.33 16.56 0.00 353.83 473.31 20.55 29.67 294.50
June 394.00 0.51 0.48 01-JUN-06:49 955.82 16.63 0.00 362.67 501.73 19.60 13.17 314.50
July 390.00 0.50 0.48 01-JUL-06:49 937.83 16.71 0.00 364.00 507.07 20.53 45.00 313.67
August 380.83 0.51 0.48 01-AUG-07:30 818.64 16.24 0.00 342.50 459.36 19.09 0.50 286.83
September 342.17 0.53 0.48 01-SEP-07:40 682.19 15.34 0.00 301.17 392.86 18.19 0.00 215.33
October 330.00 0.52 0.48 01-OCT-08:20 578.23 14.86 0.00 278.83 357.92 17.95 0.00 188.83
November 308.00 0.57 0.48 01-NOV-10:30 412.00 12.87 0.00 199.17 274.04 16.23 0.00 60.83
December 282.83 0.57 0.48 01-DEC-10:30 400.84 12.55 0.00 190.83 266.93 15.98 0.00 41.33
                         
Annual Sum or Average 4027.67 0.53     660.18 14.95 0.00 3399.33 388.87 18.19 88.33 2279.83
Minimum of Months 282.83 0.50 0.48   400.84 12.34 0.00 190.83 265.47 15.69 0.00 41.33
Maximum of Months 394.00 0.58 0.48   955.82 16.71 0.00 364.00 507.07 20.55 45.00 314.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.54 0.48 01-JAN-09:50 1770.46 19.34 83.83 245.33 1037.37 22.98 95.67 183.33
February 295.50 0.53 0.48 01-FEB-11:50 1614.34 19.93 79.00 245.33 819.79 21.30 65.50 200.00
March 296.00 0.52 0.48 02-MAR-12:39 1730.22 18.98 68.83 289.33 868.44 20.80 51.67 222.67
April 347.33 0.53 0.48 01-APR-08:50 1946.70 18.80 82.00 305.83 1034.14 20.54 63.67 263.83
May 353.67 0.52 0.48 01-MAY-08:30 1596.40 14.73 0.00 334.50 694.13 18.58 26.00 276.17
June 394.00 0.52 0.48 01-JUN-07:00 1749.52 14.66 0.00 340.00 705.11 18.41 29.17 283.33
July 390.00 0.51 0.48 01-JUL-07:40 1604.45 15.20 3.67 347.83 681.70 18.69 41.50 286.17
August 380.83 0.52 0.48 01-AUG-08:09 1623.29 17.50 59.00 332.00 727.02 18.96 49.33 279.67
September 342.17 0.53 0.48 01-SEP-08:20 1512.31 18.94 77.00 296.83 752.68 20.81 79.67 246.17
October 330.00 0.51 0.48 01-OCT-08:39 1919.38 20.02 84.00 287.50 788.94 21.95 91.33 241.17
November 308.00 0.54 0.48 01-NOV-10:09 1563.10 19.32 80.00 241.33 849.15 22.06 81.00 186.50
December 282.83 0.53 0.48 01-DEC-10:20 1678.16 20.48 85.00 243.33 870.32 21.95 75.83 173.33
                         
Annual Sum or Average 4027.67 0.52     1691.86 17.97 702.33 3509.17 811.62 20.45 750.33 2842.33
Minimum of Months 282.83 0.51 0.48   1512.31 14.66 0.00 241.33 681.70 18.41 26.00 173.33
Maximum of Months 394.00 0.54 0.48   1946.70 20.48 85.00 347.83 1037.37 22.98 95.67 286.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.51 0.48 01-JAN-07:00 6715.41 33.93 278.83 287.50 1153.68 20.87 92.17 271.67
February 295.50 0.51 0.48 01-FEB-11:39 2765.80 23.22 165.17 272.17 991.05 17.78 36.33 259.17
March 296.00 0.51 0.48 02-MAR-12:39 1203.26 11.02 0.00 305.33 730.22 15.94 0.00 260.33
April 347.33 0.53 0.48 01-APR-08:09 950.87 10.58 0.00 308.00 571.62 15.28 0.00 262.67
May 353.67 0.52 0.48 01-MAY-07:40 847.82 10.58 0.00 330.33 498.52 15.36 0.00 270.50
June 394.00 0.53 0.48 01-JUN-07:19 804.00 10.25 0.00 331.17 475.89 14.98 0.00 272.17
July 390.00 0.52 0.48 01-JUL-07:10 891.79 10.51 0.00 343.17 510.94 15.22 0.00 283.83
August 380.83 0.52 0.48 01-AUG-07:40 1040.46 10.90 0.00 332.83 583.31 15.56 0.00 285.67
September 342.17 0.52 0.48 01-SEP-07:40 1229.60 11.18 3.67 304.67 677.24 15.65 0.00 263.00
October 330.00 0.50 0.48 01-OCT-07:19 2220.90 16.37 77.17 306.00 922.87 16.97 10.33 273.50
November 308.00 0.51 0.48 01-NOV-08:09 6795.94 33.52 279.00 278.00 1130.95 20.67 90.83 269.33
December 282.83 0.51 0.48 01-DEC-07:00 6770.31 33.17 248.83 272.33 1496.40 23.18 110.83 259.50
                         
Annual Sum or Average 4027.67 0.52     2505.15 17.18 1052.67 3671.50 783.37 17.07 340.50 3231.33
Minimum of Months 282.83 0.50 0.48   804.00 10.25 0.00 272.17 475.89 14.98 0.00 259.17
Maximum of Months 394.00 0.53 0.48   6795.94 33.93 279.00 343.17 1496.40 23.18 110.83 285.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.55 0.48 01-JAN-07:00 1569.52 16.39 81.33 237.67 823.65 18.41 53.50 180.33
February 295.50 0.53 0.48 01-FEB-11:39 1735.37 16.13 71.83 236.67 964.76 20.33 64.33 197.17
March 296.00 0.52 0.48 02-MAR-12:39 1610.91 14.00 48.50 294.17 954.27 18.83 47.83 237.00
April 347.33 0.53 0.48 01-APR-07:19 1841.50 15.20 76.50 304.17 1017.92 19.37 68.00 263.33
May 353.67 0.51 0.48 01-MAY-06:40 2053.78 15.64 79.50 339.50 842.86 18.29 49.17 284.33
June 394.00 0.52 0.48 01-JUN-06:19 1845.87 15.22 85.00 338.83 795.42 18.09 54.00 287.83
July 390.00 0.51 0.48 01-JUL-06:30 1793.54 15.64 87.17 346.17 788.13 18.35 53.67 288.83
August 380.83 0.52 0.48 01-AUG-06:00 1650.87 15.61 83.50 330.33 895.03 19.76 75.50 284.83
September 342.17 0.53 0.48 01-SEP-06:49 1594.91 15.98 80.50 295.33 836.03 19.67 66.17 251.83
October 330.00 0.52 0.48 01-OCT-06:00 1663.17 16.56 76.33 282.50 850.23 18.93 48.50 242.83
November 308.00 0.54 0.48 01-NOV-07:00 1265.60 14.51 56.83 236.17 723.64 19.13 55.50 195.83
December 282.83 0.54 0.48 01-DEC-07:49 1484.76 16.54 75.83 224.83 822.29 19.90 60.33 172.33
                         
Annual Sum or Average 4027.67 0.53     1687.76 15.61 902.83 3466.33 858.08 19.05 696.50 2886.50
Minimum of Months 282.83 0.51 0.48   1265.60 14.00 48.50 224.83 723.64 18.09 47.83 172.33
Maximum of Months 394.00 0.55 0.48   2053.78 16.56 87.17 346.17 1017.92 20.33 75.50 288.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.58 0.48 01-JAN-09:50 394.77 7.24 0.00 188.67 273.00 12.22 0.00 66.67
February 295.50 0.55 0.48 01-FEB-11:00 456.51 8.44 0.00 212.50 316.41 13.48 0.00 123.50
March 296.00 0.53 0.48 02-MAR-12:00 540.47 9.76 0.00 279.00 359.63 14.68 0.00 171.67
April 347.33 0.53 0.48 01-APR-08:09 649.19 10.32 0.00 312.33 416.45 15.09 0.00 248.83
May 353.67 0.50 0.48 01-MAY-07:19 802.24 11.00 0.00 353.00 482.99 16.05 2.17 294.17
June 394.00 0.50 0.48 01-JUN-06:30 940.17 10.95 0.00 361.83 524.98 18.96 59.17 324.83
July 390.00 0.50 0.48 01-JUL-06:49 920.50 10.96 0.00 363.50 521.26 17.08 24.50 318.83
August 380.83 0.51 0.48 01-AUG-07:30 803.20 10.79 0.00 340.67 472.29 15.53 0.00 290.33
September 342.17 0.53 0.48 01-SEP-07:40 669.84 10.07 0.00 299.50 404.10 14.74 0.00 222.00
October 330.00 0.52 0.48 01-OCT-08:20 568.07 9.73 0.00 277.00 368.10 14.66 0.00 196.17
November 308.00 0.57 0.48 01-NOV-10:30 405.04 7.65 0.00 196.00 281.85 12.76 0.00 76.67
December 282.83 0.57 0.48 01-DEC-10:09 393.46 7.32 0.00 185.00 274.26 12.42 0.00 52.83
                         
Annual Sum or Average 4027.67 0.53     648.87 9.65 0.00 3369.00 400.59 14.99 85.83 2386.50
Minimum of Months 282.83 0.50 0.48   393.46 7.24 0.00 185.00 273.00 12.22 0.00 52.83
Maximum of Months 394.00 0.58 0.48   940.17 11.00 0.00 363.50 524.98 18.96 59.17 324.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.54 0.48 01-JAN-09:50 1762.94 16.60 82.83 244.67 1057.80 21.26 81.50 189.83
February 295.50 0.53 0.48 01-FEB-11:50 1419.40 14.33 51.33 244.83 842.88 19.08 51.17 206.00
March 296.00 0.52 0.48 02-MAR-12:39 1739.41 15.87 68.83 288.50 892.13 18.30 44.33 230.50
April 347.33 0.53 0.48 01-APR-08:50 1935.96 15.72 82.00 305.50 1058.38 17.98 53.00 267.33
May 353.67 0.52 0.48 01-MAY-08:30 1580.02 10.33 0.00 333.33 715.56 15.45 0.00 281.33
June 394.00 0.52 0.48 01-JUN-07:49 1680.71 10.32 0.00 338.67 726.96 15.31 0.00 289.17
July 390.00 0.51 0.48 01-JUL-07:30 1553.76 10.90 3.67 345.83 702.30 15.61 0.00 290.67
August 380.83 0.52 0.48 01-AUG-07:00 1606.16 13.94 59.00 330.83 748.15 15.95 5.50 283.17
September 342.17 0.52 0.48 01-SEP-08:20 1507.40 15.82 76.83 295.83 773.12 18.36 51.67 249.33
October 330.00 0.51 0.48 01-OCT-08:30 1919.71 17.05 84.00 286.83 803.01 19.38 50.33 244.00
November 308.00 0.54 0.48 01-NOV-10:09 1562.19 16.52 80.00 240.83 820.92 18.68 51.17 189.17
December 282.83 0.53 0.48 01-DEC-09:00 1678.88 17.96 85.00 242.17 880.38 19.68 56.00 178.67
                         
Annual Sum or Average 4027.67 0.52     1661.62 14.40 673.50 3497.83 828.16 17.75 444.67 2899.17
Minimum of Months 282.83 0.51 0.48   1419.40 10.32 0.00 240.83 702.30 15.31 0.00 178.67
Maximum of Months 394.00 0.54 0.48   1935.96 17.96 85.00 345.83 1058.38 21.26 81.50 290.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.51 0.48 01-JAN-07:00 6715.08 33.91 278.83 287.50 1154.60 20.86 92.17 271.67
February 295.50 0.51 0.48 01-FEB-11:39 2766.12 23.19 165.17 272.17 991.94 17.76 36.33 259.17
March 296.00 0.51 0.48 02-MAR-12:39 1203.75 10.98 0.00 305.33 730.97 15.92 0.00 260.33
April 347.33 0.53 0.48 01-APR-08:09 951.24 10.54 0.00 308.00 572.21 15.26 0.00 262.67
May 353.67 0.52 0.48 01-MAY-07:40 848.16 10.54 0.00 330.33 499.06 15.34 0.00 270.67
June 394.00 0.53 0.48 01-JUN-07:19 804.31 10.21 0.00 331.17 476.40 14.97 0.00 272.50
July 390.00 0.52 0.48 01-JUL-07:10 892.24 10.47 0.00 343.17 511.53 15.20 0.00 284.17
August 380.83 0.52 0.48 01-AUG-07:40 1041.08 10.86 0.00 332.83 584.04 15.54 0.00 286.00
September 342.17 0.52 0.48 01-SEP-07:40 1230.38 11.14 3.67 304.67 678.14 15.63 0.00 263.00
October 330.00 0.50 0.48 01-OCT-07:19 2221.55 16.34 77.17 305.83 923.94 16.95 10.33 273.50
November 308.00 0.51 0.48 01-NOV-08:09 6795.90 33.51 279.00 278.00 1131.88 20.66 90.83 269.33
December 282.83 0.51 0.48 01-DEC-07:00 6769.81 33.16 248.83 272.33 1497.38 23.17 110.83 259.50
                         
Annual Sum or Average 4027.67 0.52     2505.46 17.15 1052.67 3671.33 784.14 17.06 340.50 3232.50
Minimum of Months 282.83 0.50 0.48   804.31 10.21 0.00 272.17 476.40 14.97 0.00 259.17
Maximum of Months 394.00 0.53 0.48   6795.90 33.91 279.00 343.17 1497.38 23.17 110.83 286.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.55 0.48 01-JAN-07:00 1569.18 16.35 81.33 237.67 824.05 18.40 53.50 180.33
February 295.50 0.53 0.48 01-FEB-11:39 1735.03 16.09 71.83 236.67 965.24 20.31 64.33 197.17
March 296.00 0.52 0.48 02-MAR-12:39 1610.54 13.96 48.50 294.00 954.87 18.82 47.83 237.00
April 347.33 0.53 0.48 01-APR-07:19 1841.47 15.16 76.50 304.17 1018.53 19.35 68.00 263.67
May 353.67 0.51 0.48 01-MAY-06:40 2053.78 15.60 79.50 339.50 843.58 18.27 49.17 284.83
June 394.00 0.52 0.48 01-JUN-06:19 1845.97 15.18 85.00 338.83 796.17 18.07 54.00 287.83
July 390.00 0.51 0.48 01-JUL-06:30 1793.78 15.60 87.17 346.17 788.96 18.33 53.67 289.00
August 380.83 0.52 0.48 01-AUG-06:00 1651.16 15.57 83.50 330.33 889.70 19.56 73.17 284.50
September 342.17 0.53 0.48 01-SEP-06:49 1595.14 15.94 80.50 295.33 811.72 18.28 51.50 249.33
October 330.00 0.52 0.48 01-OCT-06:00 1662.88 16.52 76.33 282.67 850.90 18.91 48.50 242.83
November 308.00 0.54 0.48 01-NOV-07:00 1265.25 14.47 56.83 236.17 724.07 19.11 55.50 196.00
December 282.83 0.54 0.48 01-DEC-07:49 1484.44 16.50 75.83 224.50 822.68 19.88 60.33 172.50
                         
Annual Sum or Average 4027.67 0.53     1687.69 15.57 902.83 3466.00 856.00 18.90 679.50 2885.00
Minimum of Months 282.83 0.51 0.48   1265.25 13.96 48.50 224.50 724.07 18.07 47.83 172.50
Maximum of Months 394.00 0.55 0.48   2053.78 16.52 87.17 346.17 1018.53 20.31 73.17 289.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.58 0.48 01-JAN-09:50 394.60 7.20 0.00 188.83 273.17 12.20 0.00 66.83
February 295.50 0.55 0.48 01-FEB-11:00 456.32 8.39 0.00 212.50 316.60 13.46 0.00 123.67
March 296.00 0.53 0.48 02-MAR-12:00 540.36 9.72 0.00 279.00 359.89 14.66 0.00 172.00
April 347.33 0.53 0.48 01-APR-08:09 649.16 10.28 0.00 312.33 416.80 15.07 0.00 249.33
May 353.67 0.50 0.48 01-MAY-07:19 802.39 10.96 0.00 353.00 483.49 16.03 2.17 294.33
June 394.00 0.50 0.48 01-JUN-06:30 940.41 10.91 0.00 361.83 525.54 18.94 59.17 325.17
July 390.00 0.50 0.48 01-JUL-06:49 920.81 10.92 0.00 363.33 521.86 17.06 24.50 319.17
August 380.83 0.51 0.48 01-AUG-07:30 803.43 10.75 0.00 340.67 472.82 15.52 0.00 290.83
September 342.17 0.53 0.48 01-SEP-07:40 669.95 10.03 0.00 299.50 404.52 14.73 0.00 222.67
October 330.00 0.52 0.48 01-OCT-08:20 567.98 9.69 0.00 277.00 368.40 14.64 0.00 196.50
November 308.00 0.57 0.48 01-NOV-10:30 404.85 7.61 0.00 196.00 282.02 12.74 0.00 76.67
December 282.83 0.57 0.48 01-DEC-10:09 393.27 7.28 0.00 184.83 274.42 12.40 0.00 53.00
                         
Annual Sum or Average 4027.67 0.53     648.89 9.61 0.00 3368.83 400.95 14.97 85.83 2390.17
Minimum of Months 282.83 0.50 0.48   393.27 7.20 0.00 184.83 273.17 12.20 0.00 53.00
Maximum of Months 394.00 0.58 0.48   940.41 10.96 0.00 363.33 525.54 18.94 59.17 325.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.54 0.48 01-JAN-09:50 1762.61 16.57 82.83 244.67 1058.19 21.24 81.50 189.83
February 295.50 0.53 0.48 01-FEB-11:50 1418.97 14.29 51.33 244.67 843.36 19.06 51.17 206.17
March 296.00 0.52 0.48 02-MAR-12:39 1739.17 15.83 68.83 288.00 892.68 18.28 44.33 230.50
April 347.33 0.53 0.48 01-APR-08:50 1935.91 15.68 82.00 305.50 1059.02 17.96 53.00 267.50
May 353.67 0.52 0.48 01-MAY-08:30 1580.16 10.28 0.00 333.33 881.93 15.43 0.00 281.50
June 394.00 0.52 0.48 01-JUN-07:49 1680.88 10.27 0.00 338.50 727.67 15.29 0.00 289.33
July 390.00 0.51 0.48 01-JUL-07:30 1554.11 10.85 3.67 345.83 710.05 15.59 0.00 290.67
August 380.83 0.52 0.48 01-AUG-07:00 1606.49 13.90 59.00 330.83 864.27 15.93 5.50 283.50
September 342.17 0.52 0.48 01-SEP-08:20 1507.59 15.78 76.83 295.50 773.87 18.34 51.67 249.67
October 330.00 0.51 0.48 01-OCT-08:30 1919.49 17.01 84.00 286.83 803.67 19.36 50.33 244.17
November 308.00 0.54 0.48 01-NOV-10:09 1561.84 16.48 80.00 240.83 821.33 18.66 51.17 189.33
December 282.83 0.53 0.48 01-DEC-09:00 1678.52 17.92 85.00 242.17 880.77 19.67 56.00 178.83
                         
Annual Sum or Average 4027.67 0.52     1661.58 14.35 673.50 3496.67 854.90 17.73 444.67 2901.00
Minimum of Months 282.83 0.51 0.48   1418.97 10.27 0.00 240.83 710.05 15.29 0.00 178.83
Maximum of Months 394.00 0.54 0.48   1935.91 17.92 85.00 345.83 1059.02 21.24 81.50 290.67



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 13563039.37 6013.01 05-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 3850755.45 5294.62 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 7386279.96 5182.52 09-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 6642125.06 1953.82 03-APR-16:20 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 22446.27 21.40 18-NOV-13:20 0.00 0.00 0.00 0.00 0.00
December 8204267.24 7029.34 21-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 39668913.34     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 13563039.37 7029.34   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 8586581.68 1451.69 05-JAN-06:10 0.00 0.00 0.00 0.00 0.00
February 554483.37 335.13 06-FEB-07:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 1646591.30 506.87 21-DEC-07:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 10787656.35     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 8586581.68 1451.69   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 8522065.11 1049.86 10-JAN-06:10 0.00 0.00 0.00 0.00 0.00
February 2649511.03 849.76 06-FEB-06:10 0.00 0.00 0.00 0.00 0.00
March 2458959.56 364.98 11-MAR-13:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 13151605.69 1444.94 21-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 26782141.40     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 13151605.69 1444.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 6444072.29 871.99 21-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 3192970.65 1465.51 06-FEB-06:08 0.00 0.00 0.00 0.00 0.00
March 997283.71 264.66 11-MAR-13:50 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 7091813.28 1102.55 20-DEC-07:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 17726139.93     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 7091813.28 1465.51   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.305534E+09 81210.79 05-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.144407E+09 76483.98 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.132036E+09 72547.07 09-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 60413785.72 13505.49 03-APR-16:50 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 31368705.41 10786.05 18-NOV-15:00 0.00 0.00 0.00 0.00 0.00
December 0.217610E+09 98192.14 21-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.891370E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.305534E+09 98192.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.745712E+10 128504.26 05-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.348135E+10 127096.56 06-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.221442E+10 125213.26 13-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.193606E+09 25871.10 16-NOV-06:06 0.00 0.00 0.00 0.00 0.00
December 0.451325E+10 127546.73 21-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.178597E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.745712E+10 128504.26   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.288999E+10 111607.85 10-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.120790E+10 111601.21 06-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.138293E+10 94913.75 11-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 31459429.29 18450.08 16-NOV-06:08 0.00 0.00 0.00 0.00 0.00
December 0.256433E+10 112201.67 21-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.807661E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.288999E+10 112201.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.921549E+09 142123.97 10-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.447720E+09 142115.70 06-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.101710E+10 56290.15 11-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.900289E+09 142875.87 21-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.328665E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.101710E+10 142875.87   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.238776E+10 104737.82 10-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.102603E+10 104731.52 06-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.804196E+09 19628.78 11-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 12684789.81 3523.87 16-NOV-06:50 0.00 0.00 0.00 0.00 0.00
December 0.133224E+10 105296.72 21-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.556291E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.238776E+10 105296.72   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 41781220.01 12406.06 05-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 16689849.76 11461.53 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 9271455.46 11595.83 09-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 9418507.82 14662.89 18-APR-15:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 3455653.82 1449.06 18-NOV-15:00 0.00 0.00 0.00 0.00 0.00
December 24431851.18 13522.46 21-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.105049E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 41781220.01 14662.89   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.226789E+10 67830.71 05-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.131212E+10 67777.29 06-FEB-06:05 0.00 0.00 0.00 0.00 0.00
March 0.816158E+09 67082.93 10-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 28465788.77 5818.77 16-NOV-06:40 0.00 0.00 0.00 0.00 0.00
December 0.133898E+10 68089.72 21-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.576361E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.226789E+10 68089.72   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.253996E+10 14847.89 06-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.129142E+10 14826.05 09-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.886266E+09 14803.40 03-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 21681299.39 1936.62 11-APR-05:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 29285099.08 2122.78 28-OCT-06:40 0.00 0.00 0.00 0.00 0.00
November 0.289503E+09 14767.17 13-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.169486E+10 14863.97 20-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.675298E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.253996E+10 14863.97   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.104846E+10 13408.21 05-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.525997E+09 13397.59 06-FEB-06:05 0.00 0.00 0.00 0.00 0.00
March 0.475233E+09 13284.97 10-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 4621931.32 940.59 11-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 11389120.65 2062.95 28-OCT-05:08 0.00 0.00 0.00 0.00 0.00
November 0.102778E+09 13161.36 16-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.912982E+09 13459.34 21-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.308146E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.104846E+10 13459.34   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.699118E+09 17652.06 05-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.399256E+09 17622.09 06-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.520736E+09 17491.94 10-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 3890434.30 719.80 11-APR-05:50 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 4251296.57 1044.72 28-OCT-06:50 0.00 0.00 0.00 0.00 0.00
November 26595385.13 11285.30 16-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.561440E+09 17718.82 21-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.221529E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.699118E+09 17718.82   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.104879E+10 13586.87 05-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.496470E+09 13563.35 06-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.381890E+09 13436.47 10-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 181898.38 111.88 11-APR-07:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 10034425.70 1003.12 28-OCT-07:00 0.00 0.00 0.00 0.00 0.00
November 78911322.75 11469.98 16-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.674080E+09 13639.21 21-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.269036E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.104879E+10 13639.21   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.394737E+11 0.299407E+11 144942.67 31-JAN-06:02 127103.56 0.24
February 0.00 0.00 0.565043E+11 0.413368E+11 131220.89 28-FEB-06:03 118105.94 0.40
March 0.00 0.00 0.704633E+11 0.557049E+11 136065.61 27-MAR-05:02 128614.96 0.40
April 0.00 0.00 0.113887E+12 0.910678E+11 145596.59 24-APR-05:02 135830.13 0.68
May 0.00 0.00 0.142552E+12 0.111343E+12 161503.86 22-MAY-05:03 140652.07 0.70
June 0.00 0.00 0.154763E+12 0.123158E+12 150436.40 26-JUN-05:02 139320.04 0.79
July 0.00 0.00 0.167088E+12 0.131766E+12 156235.15 05-JUL-05:02 141902.28 0.82
August 0.00 0.00 0.181643E+12 0.144148E+12 155060.86 14-AUG-05:02 140687.66 0.87
September 0.00 0.00 0.142557E+12 0.105687E+12 164389.46 05-SEP-05:03 143076.15 0.71
October 0.00 0.00 0.134102E+12 0.106674E+12 161320.54 10-OCT-05:02 144746.02 0.65
November 0.00 0.00 0.854992E+11 0.691610E+11 147145.52 01-NOV-05:02 131564.72 0.52
December 0.00 0.00 0.632382E+11 0.501482E+11 151092.24 11-DEC-06:02 138280.35 0.37
                 
Annual Sum or Average 0.00 0.00 0.135177E+13 0.106014E+13       0.60
Minimum of Months 0.00 0.00 0.394737E+11 0.299407E+11 131220.89   118105.94 0.24
Maximum of Months 0.00 0.00 0.181643E+12 0.144148E+12 164389.46   144746.02 0.87



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.304851E+12 0.224675E+12 1126680.77 20-JAN-06:02 424536.24 0.23
February 0.00 0.00 0.435918E+12 0.306262E+12 1201178.75 03-FEB-06:03 975435.33 0.37
March 0.00 0.00 0.516071E+12 0.389006E+12 1369653.84 28-MAR-05:02 1120237.91 0.35
April 0.00 0.00 0.817918E+12 0.616538E+12 1413295.89 29-APR-05:03 1223953.47 0.51
May 0.00 0.00 0.125516E+13 0.945060E+12 1840667.26 22-MAY-03:02 1280958.13 0.65
June 0.00 0.00 0.129195E+13 0.979148E+12 1451170.00 07-JUN-05:03 1232732.04 0.68
July 0.00 0.00 0.132969E+13 0.975580E+12 1468541.56 26-JUL-05:02 1241194.99 0.67
August 0.00 0.00 0.137627E+13 0.100783E+13 1489928.03 29-AUG-05:02 1258988.86 0.67
September 0.00 0.00 0.123468E+13 0.869302E+12 1601484.65 14-SEP-05:03 1238396.63 0.65
October 0.00 0.00 0.108876E+13 0.820747E+12 1544797.82 21-OCT-05:02 1237695.21 0.55
November 0.00 0.00 0.635493E+12 0.493183E+12 1460978.08 01-NOV-05:02 1223874.17 0.44
December 0.00 0.00 0.440595E+12 0.326063E+12 1386007.70 13-DEC-06:02 1169993.86 0.29
                 
Annual Sum or Average 0.00 0.00 0.107274E+14 0.795339E+13       0.50
Minimum of Months 0.00 0.00 0.304851E+12 0.224675E+12 1126680.77   424536.24 0.23
Maximum of Months 0.00 0.00 0.137627E+13 0.100783E+13 1840667.26   1280958.13 0.68



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.312397E+11 0.227633E+11 116874.82 19-JAN-15:00 76293.80 0.22
February 0.00 0.00 0.450116E+11 0.314260E+11 114715.24 28-FEB-06:03 101963.08 0.37
March 0.00 0.00 0.541084E+11 0.405466E+11 139005.22 27-MAR-05:02 121128.24 0.34
April 0.00 0.00 0.871330E+11 0.665621E+11 143596.61 27-APR-05:02 125166.38 0.50
May 0.00 0.00 0.140593E+12 0.108781E+12 196911.83 22-MAY-03:02 144830.60 0.66
June 0.00 0.00 0.146918E+12 0.114851E+12 155712.11 30-JUN-03:02 135745.60 0.70
July 0.00 0.00 0.150639E+12 0.114011E+12 166592.74 26-JUL-03:02 142193.61 0.69
August 0.00 0.00 0.154275E+12 0.116298E+12 161579.08 24-AUG-03:02 140410.23 0.69
September 0.00 0.00 0.134290E+12 0.966514E+11 189813.22 05-SEP-03:02 139051.28 0.66
October 0.00 0.00 0.117050E+12 0.899064E+11 166670.02 21-OCT-05:02 130118.79 0.56
November 0.00 0.00 0.637855E+11 0.495261E+11 151289.45 01-NOV-05:02 126441.01 0.43
December 0.00 0.00 0.441520E+11 0.326099E+11 132746.27 15-DEC-06:03 111558.08 0.29
                 
Annual Sum or Average 0.00 0.00 0.116920E+13 0.883932E+12       0.51
Minimum of Months 0.00 0.00 0.312397E+11 0.227633E+11 114715.24   76293.80 0.22
Maximum of Months 0.00 0.00 0.154275E+12 0.116298E+12 196911.83   144830.60 0.70



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.204821E+11 0.158825E+11 110691.16 01-JAN-16:12 74916.62 0.16
February 0.00 0.00 0.243698E+11 0.196492E+11 100526.35 03-FEB-06:03 38555.02 0.26
March 0.00 0.00 0.326463E+11 0.274596E+11 130456.19 07-MAR-05:03 48949.98 0.25
April 0.00 0.00 0.507797E+11 0.439375E+11 135678.51 29-APR-05:03 73822.40 0.42
May 0.00 0.00 0.935505E+11 0.720369E+11 163086.64 22-MAY-03:04 74812.94 0.58
June 0.00 0.00 0.982552E+11 0.737793E+11 163023.10 19-JUN-03:02 78834.21 0.59
July 0.00 0.00 0.105253E+12 0.744623E+11 168727.85 03-JUL-03:03 76118.69 0.55
August 0.00 0.00 0.117337E+12 0.852203E+11 156687.93 13-AUG-18:20 76956.58 0.63
September 0.00 0.00 0.100499E+12 0.734065E+11 160862.39 17-SEP-17:53 76898.56 0.60
October 0.00 0.00 0.866626E+11 0.667716E+11 161033.56 08-OCT-16:20 78257.02 0.51
November 0.00 0.00 0.486032E+11 0.399271E+11 144127.58 02-NOV-03:02 79639.58 0.36
December 0.00 0.00 0.315948E+11 0.254428E+11 134032.76 15-DEC-05:03 73687.54 0.23
                 
Annual Sum or Average 0.00 0.00 0.810033E+12 0.617976E+12       0.43
Minimum of Months 0.00 0.00 0.204821E+11 0.158825E+11 100526.35   38555.02 0.16
Maximum of Months 0.00 0.00 0.117337E+12 0.852203E+11 168727.85   79639.58 0.63



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.497309E+10 0.486926E+10 2720.09 19-JAN-17:00 2365.24 0.00
February 0.00 0.00 0.944723E+10 0.926601E+10 4642.82 27-FEB-17:00 4289.49 0.00
March 0.00 0.00 0.156457E+11 0.154473E+11 7684.44 31-MAR-24:00 7684.44 0.00
April 0.00 0.00 0.203760E+11 0.200781E+11 8605.31 28-APR-16:10 8086.10 0.00
May 0.00 0.00 0.637587E+10 0.588497E+10 4062.61 31-MAY-23:10 3916.42 0.00
June 0.00 0.00 0.111765E+11 0.106080E+11 5855.86 30-JUN-23:53 5842.87 0.00
July 0.00 0.00 0.166550E+11 0.160060E+11 7708.72 31-JUL-23:53 7701.35 0.00
August 0.00 0.00 0.217027E+11 0.210288E+11 8750.97 07-AUG-13:10 8046.11 0.00
September 0.00 0.00 0.621027E+10 0.568213E+10 4018.78 30-SEP-24:00 3994.62 0.00
October 0.00 0.00 0.113369E+11 0.108974E+11 5864.34 31-OCT-24:00 5856.67 0.00
November 0.00 0.00 0.154412E+11 0.151973E+11 6718.24 07-NOV-16:40 6183.41 0.00
December 0.00 0.00 0.207021E+11 0.205201E+11 8642.62 14-DEC-17:00 8165.84 0.00
                 
Annual Sum or Average 0.00 0.00 0.160043E+12 0.155485E+12       0.00
Minimum of Months 0.00 0.00 0.497309E+10 0.486926E+10 2720.09   2365.24 0.00
Maximum of Months 0.00 0.00 0.217027E+11 0.210288E+11 8750.97   8165.84 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.344389E+11 0.334406E+11 25353.14 19-JAN-17:00 21815.61 0.00
February 0.00 0.00 0.801566E+11 0.783604E+11 43879.35 27-FEB-17:00 40366.83 0.00
March 0.00 0.00 0.141024E+12 0.139044E+12 71583.49 31-MAR-24:00 71583.49 0.00
April 0.00 0.00 0.192398E+12 0.189417E+12 82278.49 28-APR-16:30 77239.41 0.00
May 0.00 0.00 0.588475E+11 0.539934E+11 38094.17 31-MAY-23:10 36453.29 0.00
June 0.00 0.00 0.105778E+12 0.100117E+12 56578.06 30-JUN-23:53 56439.18 0.00
July 0.00 0.00 0.158407E+12 0.151930E+12 73753.20 31-JUL-23:53 73678.24 0.00
August 0.00 0.00 0.207103E+12 0.200367E+12 83702.75 07-AUG-13:10 76699.80 0.00
September 0.00 0.00 0.563009E+11 0.510959E+11 37081.19 30-SEP-24:00 36806.79 0.00
October 0.00 0.00 0.105214E+12 0.100842E+12 54183.47 31-OCT-24:00 54086.41 0.00
November 0.00 0.00 0.140490E+12 0.138059E+12 64130.56 07-NOV-16:40 58796.71 0.00
December 0.00 0.00 0.187037E+12 0.185215E+12 82202.08 14-DEC-17:00 77446.16 0.00
                 
Annual Sum or Average 0.00 0.00 0.146720E+13 0.142188E+13       0.00
Minimum of Months 0.00 0.00 0.344389E+11 0.334406E+11 25353.14   21815.61 0.00
Maximum of Months 0.00 0.00 0.207103E+12 0.200367E+12 83702.75   77446.16 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.236933E+10 0.227141E+10 2613.96 19-JAN-17:00 2259.25 0.00
February 0.00 0.00 0.720872E+10 0.703024E+10 4466.71 27-FEB-17:00 4114.71 0.00
March 0.00 0.00 0.135032E+11 0.133058E+11 7059.03 31-MAR-24:00 7058.70 0.00
April 0.00 0.00 0.191085E+11 0.188109E+11 8371.64 28-APR-16:10 7853.76 0.00
May 0.00 0.00 0.605677E+10 0.556897E+10 3806.14 31-MAY-23:10 3644.31 0.00
June 0.00 0.00 0.107596E+11 0.101927E+11 5719.90 30-JUN-23:53 5706.18 0.00
July 0.00 0.00 0.160183E+11 0.153706E+11 7374.98 31-JUL-23:53 7367.37 0.00
August 0.00 0.00 0.208622E+11 0.201888E+11 8445.85 10-AUG-16:00 7832.24 0.00
September 0.00 0.00 0.576360E+10 0.524122E+10 3747.99 30-SEP-24:00 3721.50 0.00
October 0.00 0.00 0.104845E+11 0.100473E+11 5354.86 31-OCT-24:00 5344.35 0.00
November 0.00 0.00 0.134660E+11 0.132237E+11 6474.40 07-NOV-16:40 5941.15 0.00
December 0.00 0.00 0.178015E+11 0.176200E+11 8282.90 14-DEC-17:00 7807.15 0.00
                 
Annual Sum or Average 0.00 0.00 0.143402E+12 0.138872E+12       0.00
Minimum of Months 0.00 0.00 0.236933E+10 0.227141E+10 2613.96   2259.25 0.00
Maximum of Months 0.00 0.00 0.208622E+11 0.201888E+11 8445.85   7853.76 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 7939.98 835402.57 10-JAN-06:02
February 0.00 0.00 01-FEB-00:10 4244.57 791024.58 06-FEB-06:02
March 0.00 0.00 01-MAR-00:10 3206.30 674912.12 11-MAR-06:02
April 0.00 0.00 01-APR-00:10 54.64 24618.72 03-APR-16:50
May 0.00 0.00 01-MAY-00:03 0.00 0.00 01-MAY-00:03
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:03 0.00 0.00 01-AUG-00:03
September 0.00 0.00 01-SEP-00:05 0.00 0.00 01-SEP-00:05
October 0.00 0.00 01-OCT-00:10 16.24 4622.43 28-OCT-06:50
November 0.00 0.00 01-NOV-00:10 298.36 98675.35 16-NOV-06:02
December 0.00 0.00 01-DEC-00:10 5462.52 804124.28 21-DEC-06:01
             
Annual Sum or Average 0.00     1766.61    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   7939.98 835402.57  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 263439.47 1655840.59 20-JAN-06:04 16.53 87635.05 30-JAN-04:12
February 399189.82 1631031.01 24-FEB-17:00 0.00 0.00 01-FEB-00:10
March 432880.04 1956350.23 28-MAR-05:04 19.12 122747.56 19-MAR-08:00
April 673911.62 1961768.07 14-APR-05:04 0.00 0.00 01-APR-00:10
May 875812.19 2278459.56 22-MAY-05:03 0.00 0.00 01-MAY-00:03
June 929170.74 1750778.01 21-JUN-15:10 0.00 0.00 01-JUN-00:10
July 928214.29 1930802.71 12-JUL-05:04 0.00 0.00 01-JUL-00:10
August 955831.04 1915951.72 29-AUG-05:04 0.00 0.00 01-AUG-00:03
September 890065.29 1931434.11 20-SEP-05:04 0.00 0.00 01-SEP-00:05
October 787505.05 1932204.51 21-OCT-05:04 0.52 5539.56 29-OCT-23:43
November 539481.18 2105999.99 01-NOV-05:04 4.80 48944.20 19-NOV-18:33
December 364215.72 1997655.87 12-DEC-06:04 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 671235.65     3.47    
Minimum of Months 263439.47 1631031.01   0.00 0.00  
Maximum of Months 955831.04 2278459.56   19.12 122747.56  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 200185.64 2254720.03 20-JAN-06:02 0.00 0.00 01-JAN-00:05
February 316156.60 2305323.54 27-FEB-06:03 0.00 0.00 01-FEB-00:10
March 329558.44 2665191.33 27-MAR-05:02 0.00 0.00 01-MAR-00:10
April 527382.16 2617700.69 14-APR-05:02 0.00 0.00 01-APR-00:10
May 735866.62 2817411.06 22-MAY-05:03 0.00 0.00 01-MAY-00:03
June 781067.23 2478397.72 01-JUN-05:03 0.00 0.00 01-JUN-00:10
July 775994.28 2554904.14 06-JUL-05:02 0.00 0.00 01-JUL-00:10
August 815739.99 2602225.76 29-AUG-05:02 0.00 0.00 01-AUG-00:03
September 758657.90 2652133.04 22-SEP-05:02 0.00 0.00 01-SEP-00:05
October 650317.84 2701712.98 21-OCT-05:02 0.00 0.00 01-OCT-00:10
November 418962.91 2812633.85 01-NOV-05:02 0.00 0.00 01-NOV-00:10
December 285747.10 2578014.50 12-DEC-06:02 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 550767.67     0.00    
Minimum of Months 200185.64 2254720.03   0.00 0.00  
Maximum of Months 815739.99 2817411.06   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 28186.40 124914.52 02-JAN-15:00 0.00 0.00 01-JAN-00:05
February 62710.05 169532.14 02-FEB-13:10 0.00 0.00 01-FEB-00:10
March 100764.25 218135.30 30-MAR-13:00 0.00 0.00 01-MAR-00:10
April 157845.94 295556.73 28-APR-15:00 0.00 0.00 01-APR-00:10
May 123824.96 198429.86 18-MAY-16:00 0.00 0.00 01-MAY-00:03
June 163937.93 248335.60 14-JUN-14:00 0.00 0.00 01-JUN-00:10
July 199385.08 297508.14 21-JUL-16:00 0.00 0.00 01-JUL-00:10
August 225637.60 324834.72 30-AUG-16:00 0.00 0.00 01-AUG-00:03
September 116610.07 228484.77 09-SEP-17:00 0.00 0.00 01-SEP-00:05
October 129378.00 238861.24 05-OCT-15:00 0.00 0.00 01-OCT-00:10
November 111214.39 227700.58 01-NOV-14:00 0.00 0.00 01-NOV-00:10
December 123681.25 256776.21 13-DEC-15:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 129043.05     0.00    
Minimum of Months 28186.40 124914.52   0.00 0.00  
Maximum of Months 225637.60 324834.72   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 12871.72 42424.03 25-JAN-12:40
February 0.00 0.00 01-FEB-00:10 12847.91 42353.45 01-FEB-12:30
March 0.00 0.00 01-MAR-00:10 13091.92 41416.62 01-MAR-12:50
April 0.00 0.00 01-APR-00:10 11687.25 39165.77 03-APR-12:00
May 0.00 0.00 01-MAY-00:03 11287.00 36780.07 01-MAY-11:50
June 0.00 0.00 01-JUN-00:10 10898.71 34306.95 01-JUN-11:40
July 0.00 0.00 01-JUL-00:10 9868.03 32662.19 03-JUL-11:50
August 0.00 0.00 01-AUG-00:03 10767.39 33353.66 31-AUG-11:40
September 0.00 0.00 01-SEP-00:05 10639.74 35277.13 29-SEP-11:40
October 0.00 0.00 01-OCT-00:10 11292.29 38034.64 31-OCT-11:30
November 0.00 0.00 01-NOV-00:10 12157.85 40415.14 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 12325.76 41969.98 29-DEC-12:40
             
Annual Sum or Average 0.00     11638.01    
Minimum of Months 0.00 0.00   9868.03 32662.19  
Maximum of Months 0.00 0.00   13091.92 42424.03  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 190324.23 3238903.48 19-JAN-15:00 1590.16 180023.89 04-JAN-08:00
February 286550.13 3161890.11 24-FEB-17:00 1030.34 178463.04 17-FEB-09:10
March 340404.40 3759327.63 07-MAR-15:00 1975.15 185950.92 09-MAR-08:40
April 641518.44 5612529.32 28-APR-16:00 901.08 103408.11 03-APR-04:50
May 1621087.00 5939734.76 26-MAY-10:40 0.00 0.00 01-MAY-00:03
June 1953814.54 6215091.75 27-JUN-15:00 0.00 0.00 01-JUN-00:10
July 2356150.28 6412201.90 12-JUL-10:10 0.00 0.00 01-JUL-00:10
August 2267477.33 6371226.05 17-AUG-14:10 0.00 0.00 01-AUG-00:03
September 1813838.09 6228143.37 18-SEP-10:00 0.00 0.00 01-SEP-00:05
October 1400221.36 6380596.67 24-OCT-10:40 268.44 93121.98 27-OCT-20:40
November 577949.41 5189123.04 02-NOV-14:00 728.55 111131.73 09-NOV-09:00
December 341856.29 4651384.81 12-DEC-14:00 1603.71 165691.92 20-DEC-20:10
             
Annual Sum or Average 1155288.12     674.79    
Minimum of Months 190324.23 3161890.11   0.00 0.00  
Maximum of Months 2356150.28 6412201.90   1975.15 185950.92  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.135521E+11 0.82 8544.02 01-JAN-00:15 1.37
February 0.118198E+11 0.79 8544.02 01-FEB-04:03 1.38
March 0.137337E+11 0.83 8544.02 01-MAR-04:03 1.38
April 0.125905E+11 0.78 8544.02 01-APR-03:02 1.38
May 0.135020E+11 0.81 8544.02 01-MAY-03:02 1.38
June 0.134637E+11 0.83 8544.02 01-JUN-03:02 1.38
July 0.129438E+11 0.78 8544.02 01-JUL-03:02 1.38
August 0.146198E+11 0.88 8544.02 01-AUG-03:02 1.38
September 0.137738E+11 0.85 8544.02 01-SEP-03:02 1.38
October 0.142453E+11 0.86 8544.02 01-OCT-15:53 1.38
November 0.137663E+11 0.86 8544.02 01-NOV-03:02 1.38
December 0.138456E+11 0.84 8544.02 01-DEC-04:03 1.39
           
Annual Sum or Average 0.161856E+12 0.83      
Minimum of Months 0.118198E+11 0.78 8544.02   1.37
Maximum of Months 0.146198E+11 0.88 8544.02   1.39



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.355840E+10 0.32 18158.17 30-JAN-06:02 1.76
February 0.364915E+10 0.34 12575.64 27-FEB-06:03 1.39
March 0.459576E+10 0.39 16154.62 27-MAR-05:02 1.63
April 0.541804E+10 0.46 18158.17 28-APR-05:02 1.76
May 0.545659E+10 0.43 18158.17 02-MAY-05:03 1.76
June 0.608899E+10 0.49 18158.17 06-JUN-05:02 1.76
July 0.659325E+10 0.51 18158.17 03-JUL-05:02 1.76
August 0.754641E+10 0.56 18158.17 07-AUG-05:03 1.76
September 0.523618E+10 0.43 18158.17 01-SEP-05:02 1.76
October 0.596378E+10 0.45 18158.17 03-OCT-05:03 1.76
November 0.506506E+10 0.41 17581.78 02-NOV-05:02 1.72
December 0.474974E+10 0.39 18158.17 11-DEC-06:02 1.76
           
Annual Sum or Average 0.639213E+11 0.43      
Minimum of Months 0.355840E+10 0.32 12575.64   1.39
Maximum of Months 0.754641E+10 0.56 18158.17   1.76



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.273363E+11 0.29 126729.94 20-JAN-06:02 1.47
February 0.258848E+11 0.30 124986.14 27-FEB-06:03 1.46
March 0.305833E+11 0.32 167118.91 27-MAR-05:02 1.76
April 0.338173E+11 0.33 167118.91 14-APR-05:02 1.76
May 0.459155E+11 0.39 167118.91 05-MAY-05:03 1.76
June 0.474574E+11 0.42 167118.91 01-JUN-05:03 1.76
July 0.467889E+11 0.40 167118.91 06-JUL-05:02 1.76
August 0.495398E+11 0.42 167118.91 01-AUG-05:02 1.76
September 0.418904E+11 0.38 167118.91 08-SEP-05:02 1.76
October 0.440613E+11 0.38 167118.91 03-OCT-05:03 1.76
November 0.326715E+11 0.32 167118.91 29-NOV-06:02 1.76
December 0.292168E+11 0.30 167118.91 12-DEC-06:02 1.76
           
Annual Sum or Average 0.455163E+12 0.35      
Minimum of Months 0.258848E+11 0.29 124986.14   1.46
Maximum of Months 0.495398E+11 0.42 167118.91   1.76



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.273040E+10 0.29 9701.84 20-JAN-06:02 1.19
February 0.259489E+10 0.29 11224.28 28-FEB-06:03 1.30
March 0.304852E+10 0.31 16785.05 27-MAR-05:02 1.68
April 0.348541E+10 0.32 18043.19 27-APR-05:02 1.76
May 0.525128E+10 0.41 18043.19 05-MAY-05:03 1.76
June 0.554028E+10 0.44 18043.19 21-JUN-05:03 1.76
July 0.540352E+10 0.43 18043.19 10-JUL-05:03 1.76
August 0.566881E+10 0.43 18043.19 01-AUG-05:02 1.76
September 0.453935E+10 0.39 18043.19 05-SEP-03:02 1.76
October 0.464639E+10 0.37 18043.19 21-OCT-05:02 1.76
November 0.308329E+10 0.31 18043.19 01-NOV-05:02 1.76
December 0.283898E+10 0.29 13353.42 15-DEC-06:03 1.45
           
Annual Sum or Average 0.488311E+11 0.36      
Minimum of Months 0.259489E+10 0.29 9701.84   1.19
Maximum of Months 0.566881E+10 0.44 18043.19   1.76



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.137543E+10 0.91 513.53 01-JAN-00:05 0.91
February 0.124233E+10 0.91 513.53 01-FEB-00:10 0.91
March 0.137543E+10 0.91 513.53 01-MAR-00:10 0.91
April 0.133106E+10 0.91 513.53 01-APR-00:10 0.91
May 0.137543E+10 0.91 513.53 01-MAY-00:03 0.91
June 0.133106E+10 0.91 513.53 01-JUN-00:10 0.91
July 0.137543E+10 0.91 513.53 01-JUL-00:10 0.91
August 0.137543E+10 0.91 513.53 01-AUG-00:03 0.91
September 0.133106E+10 0.91 513.53 01-SEP-00:05 0.91
October 0.137543E+10 0.91 513.53 01-OCT-00:10 0.91
November 0.133106E+10 0.91 513.53 01-NOV-00:10 0.91
December 0.137543E+10 0.91 513.53 01-DEC-00:10 0.91
           
Annual Sum or Average 0.161946E+11 0.91      
Minimum of Months 0.124233E+10 0.91 513.53   0.91
Maximum of Months 0.137543E+10 0.91 513.53   0.91



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.130852E+11 0.91 4885.47 01-JAN-00:05 0.91
February 0.118189E+11 0.91 4885.47 01-FEB-00:10 0.91
March 0.130852E+11 0.91 4885.47 01-MAR-00:10 0.91
April 0.126631E+11 0.91 4885.47 01-APR-00:10 0.91
May 0.130852E+11 0.91 4885.47 01-MAY-00:03 0.91
June 0.126631E+11 0.91 4885.47 01-JUN-00:10 0.91
July 0.130852E+11 0.91 4885.47 01-JUL-00:10 0.91
August 0.130852E+11 0.91 4885.47 01-AUG-00:03 0.91
September 0.126631E+11 0.91 4885.47 01-SEP-00:05 0.91
October 0.130852E+11 0.91 4885.47 01-OCT-00:10 0.91
November 0.126631E+11 0.91 4885.47 01-NOV-00:10 0.91
December 0.130852E+11 0.91 4885.47 01-DEC-00:10 0.91
           
Annual Sum or Average 0.154068E+12 0.91      
Minimum of Months 0.118189E+11 0.91 4885.47   0.91
Maximum of Months 0.130852E+11 0.91 4885.47   0.91



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.133514E+10 0.91 498.48 01-JAN-00:05 0.91
February 0.120593E+10 0.91 498.48 01-FEB-00:10 0.91
March 0.133514E+10 0.91 498.48 01-MAR-00:10 0.91
April 0.129207E+10 0.91 498.48 01-APR-00:10 0.91
May 0.133514E+10 0.91 498.48 01-MAY-00:03 0.91
June 0.129207E+10 0.91 498.48 01-JUN-00:10 0.91
July 0.133514E+10 0.91 498.48 01-JUL-00:10 0.91
August 0.133514E+10 0.91 498.48 01-AUG-00:03 0.91
September 0.129207E+10 0.91 498.48 01-SEP-00:05 0.91
October 0.133514E+10 0.91 498.48 01-OCT-00:10 0.91
November 0.129207E+10 0.91 498.48 01-NOV-00:10 0.91
December 0.133514E+10 0.91 498.48 01-DEC-00:10 0.91
           
Annual Sum or Average 0.157202E+11 0.91      
Minimum of Months 0.120593E+10 0.91 498.48   0.91
Maximum of Months 0.133514E+10 0.91 498.48   0.91



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 89682562.95 81521449.72 2589.69 10-JAN-06:02 2354.03 2354.03 38.30 4.73
February 43768120.38 39785221.43 2590.88 06-FEB-06:02 2355.11 2355.11 40.57 4.73
March 34956199.45 31775185.30 2172.47 11-MAR-06:02 1974.77 1974.77 31.65 3.34
April 607970.87 552645.52 98.92 03-APR-16:50 89.92 89.92 22.28 0.10
May 0.00 0.00 0.00 01-MAY-00:03 0.00 0.00 32.02 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 32.02 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 32.02 0.00
August 0.00 0.00 0.00 01-AUG-00:03 0.00 0.00 32.02 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00 0.00 32.02 0.00
October 205951.16 187209.60 21.88 28-OCT-06:50 19.88 19.88 30.34 0.02
November 3250410.43 2954623.09 397.33 16-NOV-06:02 361.17 361.17 24.59 0.43
December 60560773.63 55049743.23 2586.03 21-DEC-06:01 2350.70 2350.70 40.08 4.71
                 
Annual Sum or Average 0.233032E+09 0.211826E+09            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 22.28 0.00
Maximum of Months 89682562.95 81521449.72 2590.88   2355.11 2355.11 40.57 4.73



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.611764E+09 0.556093E+09 10742.64 20-JAN-06:04 9765.06 9765.06 8.67 87.93
February 0.975467E+09 0.886700E+09 9306.32 27-FEB-06:03 8459.45 8459.45 8.83 82.90
March 0.108078E+10 0.982430E+09 13022.34 27-MAR-05:02 11837.31 11837.31 8.54 95.09
April 0.180977E+10 0.164508E+10 14455.07 14-APR-05:04 13139.66 13139.66 8.47 99.18
May 0.319827E+10 0.290723E+10 15835.68 22-MAY-05:03 14394.63 14394.63 7.60 102.88
June 0.338376E+10 0.307584E+10 10781.37 07-JUN-05:03 9800.27 9800.27 8.42 88.06
July 0.354243E+10 0.322007E+10 10951.39 06-JUL-05:02 9954.81 9954.81 7.80 88.62
August 0.384932E+10 0.349903E+10 11140.97 29-AUG-05:02 10127.14 10127.14 8.10 89.25
September 0.329639E+10 0.299642E+10 12769.68 22-SEP-05:02 11607.64 11607.64 8.31 94.33
October 0.286841E+10 0.260739E+10 11826.24 21-OCT-05:02 10750.05 10750.05 7.72 91.44
November 0.149411E+10 0.135814E+10 12870.71 08-NOV-06:03 11699.48 11699.48 8.62 94.64
December 0.100719E+10 0.915534E+09 11732.69 12-DEC-06:04 10665.02 10665.02 8.28 91.15
                 
Annual Sum or Average 0.271177E+11 0.246500E+11            
Minimum of Months 0.611764E+09 0.556093E+09 9306.32   8459.45 8459.45 7.60 82.90
Maximum of Months 0.384932E+10 0.349903E+10 15835.68   14394.63 14394.63 8.83 102.88



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.180057E+11 0.163672E+11 17557.44 01-JAN-01:03 15959.71 15959.71 8.23 124.29
February 0.208840E+11 0.189836E+11 17557.44 01-FEB-04:03 15959.71 15959.71 9.54 124.29
March 0.267925E+11 0.243544E+11 17557.44 01-MAR-04:03 15959.71 15959.71 9.49 124.29
April 0.352292E+11 0.320233E+11 17557.44 01-APR-03:02 15959.71 15959.71 9.46 124.29
May 0.350043E+11 0.318189E+11 17557.44 01-MAY-00:03 15959.71 15959.71 7.64 124.29
June 0.376918E+11 0.342618E+11 17557.44 01-JUN-03:02 15959.71 15959.71 9.29 124.29
July 0.413939E+11 0.376271E+11 17557.44 01-JUL-00:10 15959.71 15959.71 7.19 124.29
August 0.427290E+11 0.388407E+11 17557.44 01-AUG-00:03 15959.71 15959.71 7.18 124.29
September 0.346287E+11 0.314775E+11 17557.44 01-SEP-00:05 15959.71 15959.71 7.21 124.29
October 0.355828E+11 0.323447E+11 17557.44 01-OCT-07:33 15959.71 15959.71 8.75 124.29
November 0.291504E+11 0.264977E+11 17557.44 01-NOV-01:53 15959.71 15959.71 9.09 124.29
December 0.236959E+11 0.215395E+11 17557.44 01-DEC-04:03 15959.71 15959.71 8.72 124.29
                 
Annual Sum or Average 0.380788E+12 0.346136E+12            
Minimum of Months 0.180057E+11 0.163672E+11 17557.44   15959.71 15959.71 7.18 124.29
Maximum of Months 0.427290E+11 0.388407E+11 17557.44   15959.71 15959.71 9.54 124.29



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.178518E+10 0.162273E+10 666.51 01-JAN-00:05 605.86 605.86 21.21 2.81
February 0.161242E+10 0.146569E+10 666.51 01-FEB-00:10 605.86 605.86 24.00 2.81
March 0.178518E+10 0.162273E+10 666.51 01-MAR-00:10 605.86 605.86 26.42 2.81
April 0.172759E+10 0.157038E+10 666.51 01-APR-00:10 605.86 605.86 32.90 2.81
May 0.178518E+10 0.162273E+10 666.51 01-MAY-00:03 605.86 605.86 26.11 2.81
June 0.172759E+10 0.157038E+10 666.51 01-JUN-00:10 605.86 605.86 29.54 2.81
July 0.178518E+10 0.162273E+10 666.51 01-JUL-00:10 605.86 605.86 34.96 2.81
August 0.178518E+10 0.162273E+10 666.51 01-AUG-00:03 605.86 605.86 37.99 2.81
September 0.172759E+10 0.157038E+10 666.51 01-SEP-00:05 605.86 605.86 28.70 2.81
October 0.178518E+10 0.162273E+10 666.51 01-OCT-00:10 605.86 605.86 28.67 2.81
November 0.172759E+10 0.157038E+10 666.51 01-NOV-00:10 605.86 605.86 30.96 2.81
December 0.178518E+10 0.162273E+10 666.51 01-DEC-00:10 605.86 605.86 28.61 2.81
                 
Annual Sum or Average 0.210191E+11 0.191063E+11            
Minimum of Months 0.161242E+10 0.146569E+10 666.51   605.86 605.86 21.21 2.81
Maximum of Months 0.178518E+10 0.162273E+10 666.51   605.86 605.86 37.99 2.81



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 11967951.72 3590385.52 5.96 01-JAN-06:05 1.79 1.79 56.28 0.44
February 10809762.85 3242928.85 5.96 01-FEB-06:03 1.79 1.79 56.92 0.44
March 11967951.72 3590385.52 5.96 01-MAR-06:03 1.79 1.79 56.31 0.44
April 11581888.76 3474566.63 5.96 01-APR-05:03 1.79 1.79 57.10 0.44
May 11967951.72 3590385.52 5.96 01-MAY-05:03 1.79 1.79 57.17 0.44
June 11581888.76 3474566.63 5.96 01-JUN-05:03 1.79 1.79 57.19 0.44
July 11967951.72 3590385.52 5.96 01-JUL-05:02 1.79 1.79 57.06 0.44
August 11967951.72 3590385.52 5.96 01-AUG-05:02 1.79 1.79 56.42 0.44
September 11581888.76 3474566.63 5.96 01-SEP-05:02 1.79 1.79 57.02 0.44
October 11967951.72 3590385.52 5.96 01-OCT-05:10 1.79 1.79 57.36 0.44
November 11581888.76 3474566.63 5.96 01-NOV-05:02 1.79 1.79 57.01 0.44
December 11967951.72 3590385.52 5.96 01-DEC-06:03 1.79 1.79 56.64 0.44
                 
Annual Sum or Average 0.140913E+09 42273893.99            
Minimum of Months 10809762.85 3242928.85 5.96   1.79 1.79 56.28 0.44
Maximum of Months 11967951.72 3590385.52 5.96   1.79 1.79 57.36 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.228353E+11 0.207573E+11 43618.49 19-JAN-15:00 39649.21 39649.21 26.40 146.18
February 0.263039E+11 0.239103E+11 43613.88 24-FEB-17:00 39645.02 39645.02 26.28 146.18
March 0.338757E+11 0.307930E+11 43649.67 07-MAR-15:00 39677.55 39677.55 27.25 146.18
April 0.460200E+11 0.418322E+11 43706.68 28-APR-15:20 39729.37 39729.37 28.99 146.18
May 0.535088E+11 0.486395E+11 43706.68 01-MAY-14:20 39729.37 39729.37 28.96 146.18
June 0.583960E+11 0.530819E+11 43706.68 01-JUN-11:50 39729.37 39729.37 29.08 146.18
July 0.645516E+11 0.586774E+11 43706.68 03-JUL-08:70 39729.37 39729.37 29.30 146.18
August 0.673073E+11 0.611823E+11 43706.68 01-AUG-08:50 39729.37 39729.37 29.54 146.18
September 0.532470E+11 0.484015E+11 43706.68 01-SEP-08:00 39729.37 39729.37 29.38 146.18
October 0.533029E+11 0.484524E+11 43706.68 05-OCT-09:10 39729.37 39729.37 28.82 146.18
November 0.389006E+11 0.353607E+11 43706.68 01-NOV-12:20 39729.37 39729.37 29.11 146.18
December 0.309278E+11 0.281133E+11 43703.21 12-DEC-14:00 39726.21 39726.21 28.71 146.18
                 
Annual Sum or Average 0.549177E+12 0.499202E+12            
Minimum of Months 0.228353E+11 0.207573E+11 43613.88   39645.02 39645.02 26.28 146.18
Maximum of Months 0.673073E+11 0.611823E+11 43706.68   39729.37 39729.37 29.54 146.18



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 79.40 79.40 7939.98 835402.57 10-JAN-06:02
February 0.00 0.00 01-FEB-00:10 18.45 18.45 4244.57 791024.58 06-FEB-06:02
March 0.00 0.00 01-MAR-00:10 17.76 17.76 3206.30 674912.12 11-MAR-06:02
April 0.00 0.00 01-APR-00:10 20.62 20.62 54.64 24618.72 03-APR-16:50
May 0.00 0.00 01-MAY-00:03 32.02 32.02 0.00 0.00 01-MAY-00:03
June 0.00 0.00 01-JUN-00:10 32.02 32.02 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 32.02 32.02 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:03 32.02 32.02 0.00 0.00 01-AUG-00:03
September 0.00 0.00 01-SEP-00:05 32.02 32.02 0.00 0.00 01-SEP-00:05
October 0.00 0.00 01-OCT-00:10 32.02 32.02 16.24 4622.43 28-OCT-06:50
November 0.00 0.00 01-NOV-00:10 28.59 28.59 298.36 98675.35 16-NOV-06:02
December 0.00 0.00 01-DEC-00:10 22.78 22.78 5462.52 804124.28 21-DEC-06:01
                 
Annual Sum or Average 0.00         1766.61    
Minimum of Months 0.00 0.00   17.76 17.76 0.00 0.00  
Maximum of Months 0.00 0.00   79.40 79.40 7939.98 835402.57  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 263439.47 1655840.59 20-JAN-06:04 11.34 8.16 16.53 87635.05 30-JAN-04:12
February 399189.82 1631031.01 24-FEB-17:00 10.18 7.05 0.00 0.00 01-FEB-00:10
March 432880.04 1956350.23 28-MAR-05:04 11.61 7.85 19.12 122747.56 19-MAR-08:00
April 673911.62 1961768.07 14-APR-05:04 11.66 7.89 0.00 0.00 01-APR-00:10
May 875812.19 2278459.56 22-MAY-05:03 11.17 6.79 0.00 0.00 01-MAY-00:03
June 929170.74 1750778.01 21-JUN-15:10 10.06 6.70 0.00 0.00 01-JUN-00:10
July 928214.29 1930802.71 12-JUL-05:04 10.83 7.12 0.00 0.00 01-JUL-00:10
August 955831.04 1915951.72 29-AUG-05:04 10.98 7.30 0.00 0.00 01-AUG-00:03
September 890065.29 1931434.11 20-SEP-05:04 10.94 7.23 0.00 0.00 01-SEP-00:05
October 787505.05 1932204.51 21-OCT-05:04 10.94 7.23 0.52 5539.56 29-OCT-23:43
November 539481.18 2105999.99 01-NOV-05:04 11.36 7.31 4.80 48944.20 19-NOV-18:33
December 364215.72 1997655.87 12-DEC-06:04 11.52 7.68 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 671235.65         3.47    
Minimum of Months 263439.47 1631031.01   10.06 6.70 0.00 0.00  
Maximum of Months 955831.04 2278459.56   11.66 8.16 19.12 122747.56  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 200185.64 2254720.03 20-JAN-06:02 13.12 8.82 0.00 0.00 01-JAN-00:05
February 316156.60 2305323.54 27-FEB-06:03 13.34 8.90 0.00 0.00 01-FEB-00:10
March 329558.44 2665191.33 27-MAR-05:02 13.39 8.54 0.00 0.00 01-MAR-00:10
April 527382.16 2617700.69 14-APR-05:02 13.36 8.66 0.00 0.00 01-APR-00:10
May 735866.62 2817411.06 22-MAY-05:03 13.24 7.25 0.00 0.00 01-MAY-00:03
June 781067.23 2478397.72 01-JUN-05:03 13.50 8.47 0.00 0.00 01-JUN-00:10
July 775994.28 2554904.14 06-JUL-05:02 13.59 7.48 0.00 0.00 01-JUL-00:10
August 815739.99 2602225.76 29-AUG-05:02 13.66 8.15 0.00 0.00 01-AUG-00:03
September 758657.90 2652133.04 22-SEP-05:02 13.41 8.31 0.00 0.00 01-SEP-00:05
October 650317.84 2701712.98 21-OCT-05:02 13.76 7.47 0.00 0.00 01-OCT-00:10
November 418962.91 2812633.85 01-NOV-05:02 13.99 8.11 0.00 0.00 01-NOV-00:10
December 285747.10 2578014.50 12-DEC-06:02 13.58 8.46 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 550767.67         0.00    
Minimum of Months 200185.64 2254720.03   13.12 7.25 0.00 0.00  
Maximum of Months 815739.99 2817411.06   13.99 8.90 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 28186.40 124914.52 02-JAN-15:00 31.01 27.43 0.00 0.00 01-JAN-00:05
February 62710.05 169532.14 02-FEB-13:10 35.46 28.99 0.00 0.00 01-FEB-00:10
March 100764.25 218135.30 30-MAR-13:00 40.27 30.60 0.00 0.00 01-MAR-00:10
April 157845.94 295556.73 28-APR-15:00 47.85 34.93 0.00 0.00 01-APR-00:10
May 123824.96 198429.86 18-MAY-16:00 38.33 33.85 0.00 0.00 01-MAY-00:03
June 163937.93 248335.60 14-JUN-14:00 43.24 35.92 0.00 0.00 01-JUN-00:10
July 199385.08 297508.14 21-JUL-16:00 48.04 37.44 0.00 0.00 01-JUL-00:10
August 225637.60 324834.72 30-AUG-16:00 50.68 37.92 0.00 0.00 01-AUG-00:03
September 116610.07 228484.77 09-SEP-17:00 41.29 36.94 0.00 0.00 01-SEP-00:05
October 129378.00 238861.24 05-OCT-15:00 42.31 34.92 0.00 0.00 01-OCT-00:10
November 111214.39 227700.58 01-NOV-14:00 41.21 31.24 0.00 0.00 01-NOV-00:10
December 123681.25 256776.21 13-DEC-15:00 44.07 31.57 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 129043.05         0.00    
Minimum of Months 28186.40 124914.52   31.01 27.43 0.00 0.00  
Maximum of Months 225637.60 324834.72   50.68 37.92 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 58.09 58.09 12871.72 42424.03 25-JAN-12:40
February 0.00 0.00 01-FEB-00:10 57.07 57.07 12847.91 42353.45 01-FEB-12:30
March 0.00 0.00 01-MAR-00:10 56.89 56.89 13091.92 41416.62 01-MAR-12:50
April 0.00 0.00 01-APR-00:10 57.19 57.19 11687.25 39165.77 03-APR-12:00
May 0.00 0.00 01-MAY-00:03 57.76 57.76 11287.00 36780.07 01-MAY-11:50
June 0.00 0.00 01-JUN-00:10 57.60 57.60 10898.71 34306.95 01-JUN-11:40
July 0.00 0.00 01-JUL-00:10 57.36 57.36 9868.03 32662.19 03-JUL-11:50
August 0.00 0.00 01-AUG-00:03 56.70 56.70 10767.39 33353.66 31-AUG-11:40
September 0.00 0.00 01-SEP-00:05 57.31 57.31 10639.74 35277.13 29-SEP-11:40
October 0.00 0.00 01-OCT-00:10 57.98 57.98 11292.29 38034.64 31-OCT-11:30
November 0.00 0.00 01-NOV-00:10 57.42 57.42 12157.85 40415.14 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 57.13 57.13 12325.76 41969.98 29-DEC-12:40
                 
Annual Sum or Average 0.00         11638.01    
Minimum of Months 0.00 0.00   56.70 56.70 9868.03 32662.19  
Maximum of Months 0.00 0.00   58.09 58.09 13091.92 42424.03  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 190324.23 3238903.48 19-JAN-15:00 26.40 23.45 1590.16 180023.89 04-JAN-08:00
February 286550.13 3161890.11 24-FEB-17:00 26.28 23.12 1030.34 178463.04 17-FEB-09:10
March 340404.40 3759327.63 07-MAR-15:00 27.25 24.08 1975.15 185950.92 09-MAR-08:40
April 641518.44 5612529.32 28-APR-16:00 30.29 27.13 901.08 103408.11 03-APR-04:50
May 1621087.00 5939734.76 26-MAY-10:40 30.82 27.48 0.00 0.00 01-MAY-00:03
June 1953814.54 6215091.75 27-JUN-15:00 31.27 28.03 0.00 0.00 01-JUN-00:10
July 2356150.28 6412201.90 12-JUL-10:10 31.59 28.24 0.00 0.00 01-JUL-00:10
August 2267477.33 6371226.05 17-AUG-14:10 31.53 28.21 0.00 0.00 01-AUG-00:03
September 1813838.09 6228143.37 18-SEP-10:00 31.29 28.05 0.00 0.00 01-SEP-00:05
October 1400221.36 6380596.67 24-OCT-10:40 31.54 28.22 268.44 93121.98 27-OCT-20:40
November 577949.41 5189123.04 02-NOV-14:00 29.59 26.27 728.55 111131.73 09-NOV-09:00
December 341856.29 4651384.81 12-DEC-14:00 28.71 25.74 1603.71 165691.92 20-DEC-20:10
                 
Annual Sum or Average 1155288.12         674.79    
Minimum of Months 190324.23 3161890.11   26.28 23.12 0.00 0.00  
Maximum of Months 2356150.28 6412201.90   31.59 28.24 1975.15 185950.92  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 37115758.46 0.00 0.394737E+11 0.355840E+10 0.00 0.00
February 10247720.49 0.00 0.565043E+11 0.364915E+10 0.00 0.00
March 10842523.22 0.00 0.704633E+11 0.459576E+10 0.00 0.00
April 6642125.06 0.00 0.113887E+12 0.541804E+10 0.00 0.00
May 0.00 0.00 0.142552E+12 0.545659E+10 0.00 0.00
June 0.00 0.00 0.154763E+12 0.608899E+10 0.00 0.00
July 0.00 0.00 0.167088E+12 0.659325E+10 0.00 0.00
August 0.00 0.00 0.181643E+12 0.754641E+10 0.00 0.00
September 0.00 0.00 0.142557E+12 0.523618E+10 0.00 0.00
October 0.00 0.00 0.134102E+12 0.596378E+10 0.00 0.00
November 22446.27 0.00 0.854992E+11 0.506506E+10 0.00 0.00
December 30094277.51 0.00 0.632382E+11 0.474974E+10 0.00 0.00
             
Annual Sum or Average 94964851.02 0.00 0.135177E+13 0.639213E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.394737E+11 0.355840E+10 0.00 0.00
Maximum of Months 37115758.46 0.00 0.181643E+12 0.754641E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.139620E+11 0.00 0.304851E+12 0.273363E+11 0.00 0.00
February 0.630740E+10 0.00 0.435918E+12 0.258848E+11 0.00 0.00
March 0.555067E+10 0.00 0.516071E+12 0.305833E+11 0.00 0.00
April 60413785.72 0.00 0.817918E+12 0.338173E+11 0.00 0.00
May 0.00 0.00 0.125516E+13 0.459155E+11 0.00 0.00
June 0.00 0.00 0.129195E+13 0.474574E+11 0.00 0.00
July 0.00 0.00 0.132969E+13 0.467889E+11 0.00 0.00
August 0.00 0.00 0.137627E+13 0.495398E+11 0.00 0.00
September 0.00 0.00 0.123468E+13 0.418904E+11 0.00 0.00
October 0.00 0.00 0.108876E+13 0.440613E+11 0.00 0.00
November 0.269119E+09 0.00 0.635493E+12 0.326715E+11 0.00 0.00
December 0.952772E+10 0.00 0.440595E+12 0.292168E+11 0.00 0.00
             
Annual Sum or Average 0.356773E+11 0.00 0.107274E+14 0.455163E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.304851E+12 0.258848E+11 0.00 0.00
Maximum of Months 0.139620E+11 0.00 0.137627E+13 0.495398E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.764601E+10 0.00 0.312397E+11 0.273040E+10 0.00 0.00
February 0.404196E+10 0.00 0.450116E+11 0.259489E+10 0.00 0.00
March 0.308955E+10 0.00 0.541084E+11 0.304852E+10 0.00 0.00
April 39794071.22 0.00 0.871330E+11 0.348541E+10 0.00 0.00
May 0.00 0.00 0.140593E+12 0.525128E+10 0.00 0.00
June 0.00 0.00 0.146918E+12 0.554028E+10 0.00 0.00
July 0.00 0.00 0.150639E+12 0.540352E+10 0.00 0.00
August 0.00 0.00 0.154275E+12 0.566881E+10 0.00 0.00
September 0.00 0.00 0.134290E+12 0.453935E+10 0.00 0.00
October 54959942.00 0.00 0.117050E+12 0.464639E+10 0.00 0.00
November 0.529709E+09 0.00 0.637855E+11 0.308329E+10 0.00 0.00
December 0.520677E+10 0.00 0.441520E+11 0.283898E+10 0.00 0.00
             
Annual Sum or Average 0.206087E+11 0.00 0.116920E+13 0.488311E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.312397E+11 0.259489E+10 0.00 0.00
Maximum of Months 0.764601E+10 0.00 0.154275E+12 0.566881E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.204821E+11 0.135521E+11 0.00 0.00
February 0.00 0.00 0.243698E+11 0.118198E+11 0.00 0.00
March 0.00 0.00 0.326463E+11 0.137337E+11 0.00 0.00
April 0.00 0.00 0.507797E+11 0.125905E+11 0.00 0.00
May 0.00 0.00 0.935505E+11 0.135020E+11 0.00 0.00
June 0.00 0.00 0.982552E+11 0.134637E+11 0.00 0.00
July 0.00 0.00 0.105253E+12 0.129438E+11 0.00 0.00
August 0.00 0.00 0.117337E+12 0.146198E+11 0.00 0.00
September 0.00 0.00 0.100499E+12 0.137738E+11 0.00 0.00
October 0.00 0.00 0.866626E+11 0.142453E+11 0.00 0.00
November 0.00 0.00 0.486032E+11 0.137663E+11 0.00 0.00
December 0.00 0.00 0.315948E+11 0.138456E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.810033E+12 0.161856E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.204821E+11 0.118198E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.117337E+12 0.146198E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.614992E+10 0.255226E+10 0.00 0.00
February 0.00 0.00 0.115658E+11 0.336090E+10 0.00 0.00
March 0.00 0.00 0.191027E+11 0.483241E+10 0.00 0.00
April 0.00 0.00 0.250110E+11 0.596605E+10 0.00 0.00
May 0.00 0.00 0.821600E+10 0.321556E+10 0.00 0.00
June 0.00 0.00 0.143370E+11 0.449157E+10 0.00 0.00
July 0.00 0.00 0.212645E+11 0.598498E+10 0.00 0.00
August 0.00 0.00 0.274843E+11 0.715703E+10 0.00 0.00
September 0.00 0.00 0.796237E+10 0.308316E+10 0.00 0.00
October 0.00 0.00 0.142987E+11 0.433722E+10 0.00 0.00
November 0.00 0.00 0.189130E+11 0.480286E+10 0.00 0.00
December 0.00 0.00 0.250848E+11 0.575816E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.199390E+12 0.555422E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.614992E+10 0.255226E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.274843E+11 0.715703E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.428122E+11 0.214585E+11 0.00 0.00
February 0.00 0.00 0.983481E+11 0.300104E+11 0.00 0.00
March 0.00 0.00 0.172436E+12 0.444979E+11 0.00 0.00
April 0.00 0.00 0.236264E+12 0.565284E+11 0.00 0.00
May 0.00 0.00 0.758700E+11 0.301078E+11 0.00 0.00
June 0.00 0.00 0.135708E+12 0.425935E+11 0.00 0.00
July 0.00 0.00 0.202259E+12 0.569380E+11 0.00 0.00
August 0.00 0.00 0.262265E+12 0.682469E+11 0.00 0.00
September 0.00 0.00 0.722375E+11 0.285997E+11 0.00 0.00
October 0.00 0.00 0.132814E+12 0.406849E+11 0.00 0.00
November 0.00 0.00 0.172313E+12 0.444858E+11 0.00 0.00
December 0.00 0.00 0.226989E+12 0.530371E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.183032E+13 0.517189E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.428122E+11 0.214585E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.262265E+12 0.682469E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.296217E+10 0.192798E+10 0.00 0.00
February 0.00 0.00 0.886300E+10 0.286021E+10 0.00 0.00
March 0.00 0.00 0.165371E+11 0.436900E+10 0.00 0.00
April 0.00 0.00 0.234856E+11 0.566916E+10 0.00 0.00
May 0.00 0.00 0.781019E+10 0.308856E+10 0.00 0.00
June 0.00 0.00 0.138070E+11 0.433943E+10 0.00 0.00
July 0.00 0.00 0.204590E+11 0.577583E+10 0.00 0.00
August 0.00 0.00 0.264305E+11 0.690346E+10 0.00 0.00
September 0.00 0.00 0.739767E+10 0.292614E+10 0.00 0.00
October 0.00 0.00 0.132472E+11 0.409785E+10 0.00 0.00
November 0.00 0.00 0.165441E+11 0.437025E+10 0.00 0.00
December 0.00 0.00 0.216436E+11 0.517732E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.179187E+12 0.515052E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.296217E+10 0.192798E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.264305E+11 0.690346E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.355840E+10 0.394737E+11 37115758.46 80450849.58 0.831438E+09 0.00 0.00 0.00
February 0.364915E+10 0.565043E+11 10247720.49 17286937.09 0.137199E+10 0.00 0.00 0.00
March 0.459576E+10 0.704633E+11 10842523.22 16986265.25 0.264568E+10 0.00 0.00 0.00
April 0.541804E+10 0.113887E+12 6642125.06 0.00 0.730908E+10 0.00 0.00 0.00
May 0.545659E+10 0.142552E+12 0.00 0.00 0.309336E+11 0.00 0.00 0.00
June 0.608899E+10 0.154763E+12 0.00 0.00 0.376469E+11 0.00 0.00 0.00
July 0.659325E+10 0.167088E+12 0.00 0.00 0.411811E+11 0.00 0.00 0.00
August 0.754641E+10 0.181643E+12 0.00 0.00 0.405055E+11 0.00 0.00 0.00
September 0.523618E+10 0.142557E+12 0.00 0.00 0.269111E+11 0.00 0.00 0.00
October 0.596378E+10 0.134102E+12 0.00 0.00 0.228873E+11 0.00 0.00 0.00
November 0.506506E+10 0.854992E+11 22446.27 0.00 0.555876E+10 0.00 0.00 0.00
December 0.474974E+10 0.632382E+11 30094277.51 45944351.37 0.302636E+10 0.00 0.00 0.00
                 
Annual Sum or Average 0.639213E+11 0.135177E+13 94964851.02 0.160668E+09 0.220809E+12 0.00 0.00 0.00
Minimum of Months 0.355840E+10 0.394737E+11 0.00 0.00 0.831438E+09 0.00 0.00 0.00
Maximum of Months 0.754641E+10 0.181643E+12 37115758.46 80450849.58 0.411811E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.273363E+11 0.304851E+12 0.139620E+11 0.189292E+10 0.103471E+11 0.00 0.00 0.00
February 0.258848E+11 0.435918E+12 0.630740E+10 0.591885E+09 0.169256E+11 0.00 0.00 0.00
March 0.305833E+11 0.516071E+12 0.555067E+10 0.398038E+09 0.316368E+11 0.00 0.00 0.00
April 0.338173E+11 0.817918E+12 60413785.72 0.00 0.728319E+11 0.00 0.00 0.00
May 0.459155E+11 0.125516E+13 0.00 0.00 0.313848E+12 0.00 0.00 0.00
June 0.474574E+11 0.129195E+13 0.00 0.00 0.379056E+12 0.00 0.00 0.00
July 0.467889E+11 0.132969E+13 0.00 0.00 0.413724E+12 0.00 0.00 0.00
August 0.495398E+11 0.137627E+13 0.00 0.00 0.409396E+12 0.00 0.00 0.00
September 0.418904E+11 0.123468E+13 0.00 0.00 0.276344E+12 0.00 0.00 0.00
October 0.440613E+11 0.108876E+13 0.00 0.00 0.231756E+12 0.00 0.00 0.00
November 0.326715E+11 0.635493E+12 0.269119E+09 0.00 0.609508E+11 0.00 0.00 0.00
December 0.292168E+11 0.440595E+12 0.952772E+10 0.179260E+10 0.322887E+11 0.00 0.00 0.00
                 
Annual Sum or Average 0.455163E+12 0.107274E+14 0.356773E+11 0.467545E+10 0.224910E+13 0.00 0.00 0.00
Minimum of Months 0.258848E+11 0.304851E+12 0.00 0.00 0.103471E+11 0.00 0.00 0.00
Maximum of Months 0.495398E+11 0.137627E+13 0.139620E+11 0.189292E+10 0.413724E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.273040E+10 0.312397E+11 0.764601E+10 0.486603E+09 0.399236E+09 0.00 0.00 0.00
February 0.259489E+10 0.450116E+11 0.404196E+10 0.167009E+09 0.806276E+09 0.00 0.00 0.00
March 0.304852E+10 0.541084E+11 0.308955E+10 0.114424E+09 0.208107E+10 0.00 0.00 0.00
April 0.348541E+10 0.871330E+11 39794071.22 0.00 0.620302E+10 0.00 0.00 0.00
May 0.525128E+10 0.140593E+12 0.00 0.00 0.302608E+11 0.00 0.00 0.00
June 0.554028E+10 0.146918E+12 0.00 0.00 0.363825E+11 0.00 0.00 0.00
July 0.540352E+10 0.150639E+12 0.00 0.00 0.396700E+11 0.00 0.00 0.00
August 0.566881E+10 0.154275E+12 0.00 0.00 0.393116E+11 0.00 0.00 0.00
September 0.453935E+10 0.134290E+12 0.00 0.00 0.264412E+11 0.00 0.00 0.00
October 0.464639E+10 0.117050E+12 54959942.00 0.00 0.224946E+11 0.00 0.00 0.00
November 0.308329E+10 0.637855E+11 0.529709E+09 0.00 0.570945E+10 0.00 0.00 0.00
December 0.283898E+10 0.441520E+11 0.520677E+10 0.388557E+09 0.285818E+10 0.00 0.00 0.00
                 
Annual Sum or Average 0.488311E+11 0.116920E+13 0.206087E+11 0.115659E+10 0.212618E+12 0.00 0.00 0.00
Minimum of Months 0.259489E+10 0.312397E+11 0.00 0.00 0.399236E+09 0.00 0.00 0.00
Maximum of Months 0.566881E+10 0.154275E+12 0.764601E+10 0.486603E+09 0.396700E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.135521E+11 0.204821E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.118198E+11 0.243698E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.137337E+11 0.326463E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.125905E+11 0.507797E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.135020E+11 0.935505E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.134637E+11 0.982552E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129438E+11 0.105253E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.146198E+11 0.117337E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.137738E+11 0.100499E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.142453E+11 0.866626E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.137663E+11 0.486032E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.138456E+11 0.315948E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.161856E+12 0.810033E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.118198E+11 0.204821E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.146198E+11 0.117337E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.137543E+10 0.497309E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.124233E+10 0.944723E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.137543E+10 0.156457E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.133106E+10 0.203760E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.137543E+10 0.637587E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.133106E+10 0.111765E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.137543E+10 0.166550E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.137543E+10 0.217027E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.133106E+10 0.621027E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.137543E+10 0.113369E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.133106E+10 0.154412E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.137543E+10 0.207021E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.161946E+11 0.160043E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.124233E+10 0.497309E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137543E+10 0.217027E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.130852E+11 0.344389E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.118189E+11 0.801566E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130852E+11 0.141024E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.126631E+11 0.192398E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.130852E+11 0.588475E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.126631E+11 0.105778E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.130852E+11 0.158407E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130852E+11 0.207103E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.126631E+11 0.563009E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.130852E+11 0.105214E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.126631E+11 0.140490E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.130852E+11 0.187037E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.154068E+12 0.146720E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.118189E+11 0.344389E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130852E+11 0.207103E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.133514E+10 0.236933E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.120593E+10 0.720872E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.133514E+10 0.135032E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.129207E+10 0.191085E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.133514E+10 0.605677E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.129207E+10 0.107596E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.133514E+10 0.160183E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.133514E+10 0.208622E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.129207E+10 0.576360E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133514E+10 0.104845E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.129207E+10 0.134660E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.133514E+10 0.178015E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.157202E+11 0.143402E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.120593E+10 0.236933E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.133514E+10 0.208622E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.355840E+10 37115758.46 0.394737E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.364915E+10 10247720.49 0.565043E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.459576E+10 10842523.22 0.704633E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.541804E+10 6642125.06 0.113887E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.545659E+10 0.00 0.142552E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.608899E+10 0.00 0.154763E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.659325E+10 0.00 0.167088E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.754641E+10 0.00 0.181643E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.523618E+10 0.00 0.142557E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.596378E+10 0.00 0.134102E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.506506E+10 22446.27 0.854992E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.474974E+10 30094277.51 0.632382E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.639213E+11 94964851.02 0.135177E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.355840E+10 0.00 0.394737E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.754641E+10 37115758.46 0.181643E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.273363E+11 0.139620E+11 0.304851E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.258848E+11 0.630740E+10 0.435918E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.305833E+11 0.555067E+10 0.516071E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.338173E+11 60413785.72 0.817918E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.459155E+11 0.00 0.125516E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.474574E+11 0.00 0.129195E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.467889E+11 0.00 0.132969E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.495398E+11 0.00 0.137627E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.418904E+11 0.00 0.123468E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.440613E+11 0.00 0.108876E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.326715E+11 0.269119E+09 0.635493E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.292168E+11 0.952772E+10 0.440595E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.455163E+12 0.356773E+11 0.107274E+14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.258848E+11 0.00 0.304851E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.495398E+11 0.139620E+11 0.137627E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.273040E+10 0.764601E+10 0.312397E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.259489E+10 0.404196E+10 0.450116E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.304852E+10 0.308955E+10 0.541084E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.348541E+10 39794071.22 0.871330E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.525128E+10 0.00 0.140593E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.554028E+10 0.00 0.146918E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.540352E+10 0.00 0.150639E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.566881E+10 0.00 0.154275E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453935E+10 0.00 0.134290E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.464639E+10 54959942.00 0.117050E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.308329E+10 0.529709E+09 0.637855E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.283898E+10 0.520677E+10 0.441520E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.488311E+11 0.206087E+11 0.116920E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.259489E+10 0.00 0.312397E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.566881E+10 0.764601E+10 0.154275E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.135521E+11 0.00 0.204821E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.118198E+11 0.00 0.243698E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.137337E+11 0.00 0.326463E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.125905E+11 0.00 0.507797E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.135020E+11 0.00 0.935505E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.134637E+11 0.00 0.982552E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129438E+11 0.00 0.105253E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.146198E+11 0.00 0.117337E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.137738E+11 0.00 0.100499E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.142453E+11 0.00 0.866626E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.137663E+11 0.00 0.486032E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.138456E+11 0.00 0.315948E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.161856E+12 0.00 0.810033E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.118198E+11 0.00 0.204821E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.146198E+11 0.00 0.117337E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.137543E+10 0.00 0.614992E+10 0.00 0.117683E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.124233E+10 0.00 0.115658E+11 0.00 0.211857E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.137543E+10 0.00 0.191027E+11 0.00 0.345698E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.133106E+10 0.00 0.250110E+11 0.00 0.463499E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.137543E+10 0.00 0.821600E+10 0.00 0.184013E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.133106E+10 0.00 0.143370E+11 0.00 0.316051E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.137543E+10 0.00 0.212645E+11 0.00 0.460955E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.137543E+10 0.00 0.274843E+11 0.00 0.578159E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.133106E+10 0.00 0.796237E+10 0.00 0.175210E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.137543E+10 0.00 0.142987E+11 0.00 0.296179E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.133106E+10 0.00 0.189130E+11 0.00 0.347180E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.137543E+10 0.00 0.250848E+11 0.00 0.438273E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.161946E+11 0.00 0.199390E+12 0.00 0.393476E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.124233E+10 0.00 0.614992E+10 0.00 0.117683E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137543E+10 0.00 0.274843E+11 0.00 0.578159E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.130852E+11 0.00 0.428122E+11 0.00 0.837330E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.118189E+11 0.00 0.983481E+11 0.00 0.181915E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130852E+11 0.00 0.172436E+12 0.00 0.314127E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.126631E+11 0.00 0.236264E+12 0.00 0.438653E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.130852E+11 0.00 0.758700E+11 0.00 0.170226E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.126631E+11 0.00 0.135708E+12 0.00 0.299304E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.130852E+11 0.00 0.202259E+12 0.00 0.438528E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130852E+11 0.00 0.262265E+12 0.00 0.551616E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.126631E+11 0.00 0.722375E+11 0.00 0.159366E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.130852E+11 0.00 0.132814E+12 0.00 0.275997E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.126631E+11 0.00 0.172313E+12 0.00 0.318227E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.130852E+11 0.00 0.226989E+12 0.00 0.399519E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.154068E+12 0.00 0.183032E+13 0.00 0.363121E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.118189E+11 0.00 0.428122E+11 0.00 0.837330E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130852E+11 0.00 0.262265E+12 0.00 0.551616E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.133514E+10 0.00 0.296217E+10 0.00 0.592840E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.120593E+10 0.00 0.886300E+10 0.00 0.165428E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.133514E+10 0.00 0.165371E+11 0.00 0.303386E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.129207E+10 0.00 0.234856E+11 0.00 0.437708E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.133514E+10 0.00 0.781019E+10 0.00 0.175342E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.129207E+10 0.00 0.138070E+11 0.00 0.304736E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.133514E+10 0.00 0.204590E+11 0.00 0.444069E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.133514E+10 0.00 0.264305E+11 0.00 0.556832E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.129207E+10 0.00 0.739767E+10 0.00 0.163406E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133514E+10 0.00 0.132472E+11 0.00 0.276271E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.129207E+10 0.00 0.165441E+11 0.00 0.307817E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.133514E+10 0.00 0.216436E+11 0.00 0.384218E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.157202E+11 0.00 0.179187E+12 0.00 0.357850E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.120593E+10 0.00 0.296217E+10 0.00 0.592840E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.133514E+10 0.00 0.264305E+11 0.00 0.556832E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.608432E+09 0.149314E+10 0.00 91494134.00 2772671.67 0.00 0.502336E+11 0.00 0.86
February 0.424394E+09 0.152851E+10 0.00 72201781.17 5484318.69 0.00 0.381802E+11 0.00 0.95
March 0.319142E+09 0.294973E+10 0.00 79338588.07 6012859.30 0.00 0.409997E+11 0.00 0.97
April 0.186705E+09 0.491499E+10 0.00 53995130.34 70835364.00 0.00 0.187823E+11 0.00 0.83
May 795109.23 0.231541E+11 0.00 1269361.76 0.219339E+09 0.00 56051099.46 0.00 0.29
June 2062510.87 0.278402E+11 0.00 1602813.74 0.333361E+09 0.00 0.166840E+09 0.00 0.31
July 0.00 0.336820E+11 0.00 55969.02 0.529319E+09 0.00 664647.51 0.00 0.27
August 92750.20 0.347703E+11 0.00 139190.17 0.348532E+09 0.00 16867863.66 0.00 0.30
September 3019722.80 0.259880E+11 0.00 1888632.17 0.318544E+09 0.00 0.118098E+09 0.00 0.29
October 0.112524E+09 0.196005E+11 0.00 35518168.28 0.268860E+09 0.00 0.114968E+11 0.00 0.59
November 0.328784E+09 0.605055E+10 0.00 88028946.85 40729324.07 0.00 0.333832E+11 0.00 1.02
December 0.477340E+09 0.387097E+10 0.00 91049397.88 21283774.55 0.00 0.458471E+11 0.00 0.86
                   
Annual Sum or Average 0.246329E+10 0.185843E+12 0.00 0.516582E+09 0.216507E+10 0.00 0.239281E+12 0.00 0.63
Minimum of Months 0.00 0.149314E+10 0.00 55969.02 2772671.67 0.00 664647.51 0.00 0.27
Maximum of Months 0.608432E+09 0.347703E+11 0.00 91494134.00 0.529319E+09 0.00 0.502336E+11 0.00 1.02



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.720455E+10 0.215935E+10 0.00 41292532.62 0.166386E+09 0.00 0.248780E+11 0.00 0.49
February 0.372380E+10 0.254712E+10 0.00 34668760.31 0.212353E+09 0.00 0.168291E+11 0.00 0.50
March 0.410885E+10 0.388542E+10 0.00 49132899.72 0.336893E+09 0.00 0.232255E+11 0.00 0.58
April 0.425467E+10 0.594112E+10 0.00 24240964.58 0.733417E+09 0.00 0.583099E+10 0.00 0.50
May 0.00 0.127075E+11 0.00 0.00 0.133361E+10 0.00 0.00 0.00 0.27
June 0.00 0.131124E+11 0.00 0.00 0.136951E+10 0.00 0.00 0.00 0.27
July 0.00 0.151395E+11 0.00 0.00 0.149588E+10 0.00 0.00 0.00 0.25
August 2301105.05 0.157639E+11 0.00 0.00 0.149578E+10 0.00 0.00 0.00 0.27
September 0.00 0.153909E+11 0.00 0.00 0.171090E+10 0.00 0.00 0.00 0.27
October 0.110410E+10 0.100958E+11 0.00 16135029.89 0.110635E+10 0.00 0.505352E+10 0.00 0.36
November 0.456266E+10 0.474144E+10 0.00 46746691.36 0.482403E+09 0.00 0.156376E+11 0.00 0.57
December 0.583948E+10 0.410925E+10 0.00 52196684.39 0.366279E+09 0.00 0.267180E+11 0.00 0.56
                   
Annual Sum or Average 0.308004E+11 0.105594E+12 0.00 0.264414E+09 0.108098E+11 0.00 0.118173E+12 0.00 0.41
Minimum of Months 0.00 0.215935E+10 0.00 0.00 0.166386E+09 0.00 0.00 0.00 0.25
Maximum of Months 0.720455E+10 0.157639E+11 0.00 52196684.39 0.171090E+10 0.00 0.267180E+11 0.00 0.58



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.163143E+12 0.136523E+11 0.00 94929927.19 0.900987E+10 0.00 0.890719E+11 0.00 0.41
February 0.905272E+11 0.184971E+11 0.00 94238730.76 0.825828E+10 0.00 0.583380E+11 0.00 0.40
March 0.930387E+11 0.260165E+11 0.00 0.183139E+09 0.137529E+11 0.00 0.102393E+12 0.00 0.45
April 0.221399E+11 0.421445E+11 0.00 0.150345E+09 0.246789E+11 0.00 0.350250E+11 0.00 0.38
May 0.00 0.115915E+12 0.00 0.00 0.224460E+11 0.00 0.00 0.00 0.27
June 0.00 0.121868E+12 0.00 0.00 0.221775E+11 0.00 0.00 0.00 0.28
July 0.00 0.136324E+12 0.00 0.00 0.296768E+11 0.00 0.00 0.00 0.25
August 0.00 0.145563E+12 0.00 0.00 0.242085E+11 0.00 0.00 0.00 0.28
September 0.00 0.132571E+12 0.00 0.00 0.345946E+11 0.00 0.00 0.00 0.27
October 0.154367E+11 0.906326E+11 0.00 93584549.60 0.197330E+11 0.00 0.324141E+11 0.00 0.33
November 0.642253E+11 0.374342E+11 0.00 0.208071E+09 0.118506E+11 0.00 0.734733E+11 0.00 0.45
December 0.118658E+12 0.283945E+11 0.00 0.138080E+09 0.151022E+11 0.00 0.927105E+11 0.00 0.41
                   
Annual Sum or Average 0.567169E+12 0.909013E+12 0.00 0.962388E+09 0.235489E+12 0.00 0.483426E+12 0.00 0.35
Minimum of Months 0.00 0.136523E+11 0.00 0.00 0.825828E+10 0.00 0.00 0.00 0.25
Maximum of Months 0.163143E+12 0.145563E+12 0.00 0.208071E+09 0.345946E+11 0.00 0.102393E+12 0.00 0.45



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.203186E+11 0.133018E+10 0.00 1975398.07 0.124264E+10 0.324626E+09 0.163914E+10 0.00 0.41
February 0.113607E+11 0.196192E+10 0.00 2250662.72 0.112804E+10 0.170088E+09 0.165198E+10 0.00 0.40
March 0.130837E+11 0.304763E+10 0.00 6162947.34 0.135011E+10 99306880.11 0.416630E+10 0.00 0.44
April 0.286712E+10 0.449124E+10 0.00 9127958.78 0.233715E+10 0.00 0.252817E+10 0.00 0.37
May 0.00 0.114098E+11 0.00 0.00 0.214973E+10 0.00 0.00 0.00 0.27
June 0.00 0.122242E+11 0.00 0.00 0.193285E+10 0.00 0.00 0.00 0.27
July 0.00 0.141298E+11 0.00 0.00 0.241007E+10 0.00 0.00 0.00 0.25
August 0.00 0.143106E+11 0.00 0.00 0.253449E+10 0.00 0.00 0.00 0.28
September 0.00 0.127371E+11 0.00 0.00 0.393107E+10 0.00 0.00 0.00 0.27
October 0.175689E+10 0.856456E+10 0.00 6786260.10 0.222181E+10 0.00 0.236801E+10 0.00 0.32
November 0.843846E+10 0.324446E+10 0.00 6841114.80 0.183501E+10 0.00 0.331855E+10 0.00 0.43
December 0.171826E+11 0.253078E+10 0.00 1105777.90 0.196419E+10 0.164015E+09 0.794413E+09 0.00 0.40
                   
Annual Sum or Average 0.750080E+11 0.899822E+11 0.00 34250119.71 0.250372E+11 0.758036E+09 0.164666E+11 0.00 0.34
Minimum of Months 0.00 0.133018E+10 0.00 0.00 0.112804E+10 0.00 0.00 0.00 0.25
Maximum of Months 0.203186E+11 0.143106E+11 0.00 9127958.78 0.393107E+10 0.324626E+09 0.416630E+10 0.00 0.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.305011E+10 0.256389E+09 0.00 552891.31 34187922.55 0.00 0.453187E+09 0.00 0.44
February 0.168036E+10 0.323871E+09 0.00 1092857.74 28543003.61 0.00 0.543135E+09 0.00 0.45
March 0.175504E+10 0.526966E+09 0.00 2268509.48 50434693.24 0.00 0.113144E+10 0.00 0.52
April 0.717182E+09 0.899398E+09 0.00 2041060.49 88202299.52 0.00 0.455839E+09 0.00 0.52
May 0.00 0.228395E+10 0.00 0.00 0.152981E+09 0.00 0.00 0.00 0.38
June 0.00 0.267177E+10 0.00 0.00 0.104146E+09 0.00 0.00 0.00 0.42
July 0.00 0.306129E+10 0.00 0.00 0.106427E+09 0.00 0.00 0.00 0.38
August 288838.86 0.300403E+10 0.00 0.00 99487369.33 0.00 0.00 0.00 0.39
September 0.00 0.250898E+10 0.00 0.00 0.195125E+09 0.00 0.00 0.00 0.34
October 0.317760E+09 0.167087E+10 0.00 1342398.52 0.124992E+09 0.00 0.404471E+09 0.00 0.41
November 0.124128E+10 0.649133E+09 0.00 2568466.87 60552138.87 0.00 0.937858E+09 0.00 0.52
December 0.240700E+10 0.526764E+09 0.00 1451162.51 48529497.38 0.00 0.886056E+09 0.00 0.47
                   
Annual Sum or Average 0.111690E+11 0.183834E+11 0.00 11317346.93 0.109361E+10 0.00 0.481198E+10 0.00 0.44
Minimum of Months 0.00 0.256389E+09 0.00 0.00 28543003.61 0.00 0.00 0.00 0.34
Maximum of Months 0.305011E+10 0.306129E+10 0.00 2568466.87 0.195125E+09 0.00 0.113144E+10 0.00 0.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.165702E+10 0.184143E+09 0.00 1492822.94 40510893.94 0.00 0.111146E+10 0.00 0.53
February 0.987578E+09 0.260146E+09 0.00 1578491.79 24680015.38 0.00 0.814230E+09 0.00 0.56
March 0.126463E+10 0.419044E+09 0.00 2611146.66 49690063.36 0.00 0.118539E+10 0.00 0.69
April 0.545647E+09 0.712108E+09 0.00 2008548.75 90512922.52 0.00 0.523039E+09 0.00 0.68
May 0.00 0.187103E+10 0.00 0.00 0.115068E+09 0.00 0.00 0.00 0.48
June 0.00 0.202976E+10 0.00 0.00 0.114910E+09 0.00 0.00 0.00 0.50
July 0.00 0.228985E+10 0.00 0.00 0.102328E+09 0.00 0.00 0.00 0.44
August 219016.66 0.211551E+10 0.00 0.00 0.118764E+09 0.00 0.00 0.00 0.44
September 0.00 0.192671E+10 0.00 0.00 0.153572E+09 0.00 0.00 0.00 0.41
October 0.233807E+09 0.130699E+10 0.00 1094915.68 0.103192E+09 0.00 0.334432E+09 0.00 0.50
November 0.911646E+09 0.465854E+09 0.00 2534838.15 65468097.69 0.00 0.891668E+09 0.00 0.64
December 0.184093E+10 0.316873E+09 0.00 1499540.77 72848786.88 0.00 0.762440E+09 0.00 0.56
                   
Annual Sum or Average 0.744148E+10 0.138980E+11 0.00 12820304.75 0.105155E+10 0.00 0.562266E+10 0.00 0.54
Minimum of Months 0.00 0.184143E+09 0.00 0.00 24680015.38 0.00 0.00 0.00 0.41
Maximum of Months 0.184093E+10 0.228985E+10 0.00 2611146.66 0.153572E+09 0.00 0.118539E+10 0.00 0.69



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.150833E+10 0.410756E+09 0.00 7454656.74 26203804.60 0.00 0.395925E+10 0.00 0.72
February 0.998519E+09 0.616818E+09 0.00 4908585.64 23093128.75 0.00 0.221082E+10 0.00 0.70
March 0.151872E+10 0.727394E+09 0.00 4920530.63 34406973.63 0.00 0.202414E+10 0.00 0.69
April 0.709345E+09 0.107272E+10 0.00 2522941.25 73166378.55 0.00 0.553130E+09 0.00 0.60
May 0.00 0.230903E+10 0.00 0.00 0.148329E+09 0.00 0.00 0.00 0.38
June 0.00 0.253956E+10 0.00 0.00 0.117487E+09 0.00 0.00 0.00 0.40
July 0.00 0.300485E+10 0.00 0.00 0.107741E+09 0.00 0.00 0.00 0.37
August 288587.65 0.327275E+10 0.00 0.00 80470355.13 0.00 0.00 0.00 0.43
September 0.00 0.308322E+10 0.00 0.00 0.148727E+09 0.00 0.00 0.00 0.41
October 0.226542E+09 0.252673E+10 0.00 2640179.41 49991062.38 0.00 0.704382E+09 0.00 0.60
November 0.759911E+09 0.107279E+10 0.00 9045141.38 32080331.29 0.00 0.269276E+10 0.00 0.88
December 0.152437E+10 0.856556E+09 0.00 8922187.86 34202952.68 0.00 0.351596E+10 0.00 0.81
                   
Annual Sum or Average 0.724602E+10 0.214932E+11 0.00 40414222.90 0.875899E+09 0.00 0.156604E+11 0.00 0.58
Minimum of Months 0.00 0.410756E+09 0.00 0.00 23093128.75 0.00 0.00 0.00 0.37
Maximum of Months 0.152437E+10 0.327275E+10 0.00 9045141.38 0.148727E+09 0.00 0.395925E+10 0.00 0.88



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.204205E+10 0.305935E+09 0.00 2743513.53 20526419.55 0.00 0.172678E+10 0.00 0.74
February 0.821037E+09 0.448559E+09 0.00 3997483.47 11915943.75 0.00 0.172668E+10 0.00 0.84
March 0.611419E+09 0.727267E+09 0.00 7433006.95 8908413.41 0.00 0.305493E+10 0.00 1.08
April 0.314916E+09 0.141552E+10 0.00 6394783.06 8047185.10 0.00 0.120407E+10 0.00 1.12
May 0.00 0.233965E+10 0.00 0.00 45888532.87 0.00 0.00 0.00 0.58
June 0.00 0.282997E+10 0.00 0.00 18768980.29 0.00 0.00 0.00 0.67
July 0.00 0.343157E+10 0.00 0.00 15023596.21 0.00 0.00 0.00 0.64
August 263304.14 0.375552E+10 0.00 3687.35 12855103.25 0.00 16887.02 0.00 0.74
September 0.00 0.266572E+10 0.00 0.00 82472083.13 0.00 0.00 0.00 0.54
October 0.125134E+09 0.200262E+10 0.00 2472073.19 29884724.12 0.00 0.700675E+09 0.00 0.74
November 0.479915E+09 0.891947E+09 0.00 7062891.68 7214115.34 0.00 0.221680E+10 0.00 1.05
December 0.680789E+09 0.792793E+09 0.00 7771953.42 10980109.92 0.00 0.351093E+10 0.00 1.01
                   
Annual Sum or Average 0.507553E+10 0.216071E+11 0.00 37879392.65 0.272485E+09 0.00 0.141409E+11 0.00 0.81
Minimum of Months 0.00 0.305935E+09 0.00 0.00 7214115.34 0.00 0.00 0.00 0.54
Maximum of Months 0.204205E+10 0.375552E+10 0.00 7771953.42 82472083.13 0.00 0.351093E+10 0.00 1.12



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.273197E+11 0.117813E+10 0.00 85384.96 0.166480E+10 0.381176E+10 24080388.37 0.00 0.41
February 0.160262E+11 0.189608E+10 0.00 425292.18 0.141867E+10 0.154751E+10 0.870391E+09 0.00 0.40
March 0.211474E+11 0.348904E+10 0.00 1737341.60 0.170850E+10 0.142268E+10 0.978940E+09 0.00 0.44
April 0.508898E+10 0.714165E+10 0.00 8283183.85 0.205478E+10 0.00 0.161825E+10 0.00 0.40
May 0.00 0.223696E+11 0.00 0.00 0.157743E+10 0.00 0.00 0.00 0.38
June 0.00 0.262058E+11 0.00 0.00 0.157570E+10 0.00 0.00 0.00 0.43
July 0.00 0.302318E+11 0.00 0.00 0.163778E+10 0.00 0.00 0.00 0.39
August 0.00 0.289057E+11 0.00 0.00 0.163817E+10 0.00 0.00 0.00 0.40
September 0.00 0.236539E+11 0.00 0.00 0.235413E+10 0.00 0.00 0.00 0.34
October 0.328760E+10 0.154884E+11 0.00 7267756.64 0.168243E+10 0.00 0.237137E+10 0.00 0.37
November 0.145903E+11 0.470832E+10 0.00 4126245.48 0.174858E+10 3297880.43 0.179780E+10 0.00 0.43
December 0.238511E+11 0.319653E+10 0.00 243029.47 0.226429E+10 0.200852E+10 0.131221E+09 0.00 0.40
                   
Annual Sum or Average 0.111311E+12 0.168465E+12 0.00 22168234.18 0.213253E+11 0.879377E+10 0.779205E+10 0.00 0.40
Minimum of Months 0.00 0.117813E+10 0.00 0.00 0.141867E+10 0.00 0.00 0.00 0.34
Maximum of Months 0.273197E+11 0.302318E+11 0.00 8283183.85 0.235413E+10 0.381176E+10 0.237137E+10 0.00 0.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.216344E+11 0.120239E+10 0.00 1168442.52 0.120281E+10 0.168914E+10 0.152227E+10 0.00 0.51
February 0.117570E+11 0.219157E+10 0.00 4312903.02 0.838007E+09 0.564561E+09 0.249418E+10 0.00 0.52
March 0.128279E+11 0.417209E+10 0.00 14221846.29 0.867429E+09 0.831111E+09 0.613349E+10 0.00 0.61
April 0.272067E+10 0.770061E+10 0.00 17137020.32 0.124205E+10 0.00 0.446805E+10 0.00 0.61
May 0.00 0.199739E+11 0.00 0.00 0.125385E+10 0.00 0.00 0.00 0.53
June 0.00 0.225629E+11 0.00 0.00 0.123241E+10 0.00 0.00 0.00 0.57
July 0.00 0.262671E+11 0.00 0.00 0.120138E+10 0.00 0.00 0.00 0.52
August 0.00 0.244587E+11 0.00 0.00 0.135145E+10 0.00 0.00 0.00 0.53
September 0.00 0.197655E+11 0.00 0.00 0.205187E+10 0.00 0.00 0.00 0.44
October 0.230267E+10 0.139058E+11 0.00 8079568.05 0.132145E+10 0.00 0.245130E+10 0.00 0.51
November 0.861289E+10 0.441828E+10 0.00 12754426.96 0.119365E+10 2629589.52 0.499068E+10 0.00 0.56
December 0.178177E+11 0.253161E+10 0.00 3071296.65 0.172794E+10 0.122978E+10 0.176087E+10 0.00 0.50
                   
Annual Sum or Average 0.776732E+11 0.149151E+12 0.00 60745503.81 0.154843E+11 0.431722E+10 0.238208E+11 0.00 0.53
Minimum of Months 0.00 0.120239E+10 0.00 0.00 0.838007E+09 0.00 0.00 0.00 0.44
Maximum of Months 0.216344E+11 0.262671E+11 0.00 17137020.32 0.205187E+10 0.168914E+10 0.613349E+10 0.00 0.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.142119E+11 0.413624E+10 0.00 63299212.41 0.533787E+09 0.515310E+09 0.327006E+11 0.00 0.67
February 0.922416E+10 0.658872E+10 0.00 39106594.99 0.340215E+09 0.162414E+09 0.164314E+11 0.00 0.65
March 0.147140E+11 0.660272E+10 0.00 33383341.56 0.741003E+09 0.286597E+09 0.132375E+11 0.00 0.60
April 0.394757E+10 0.969995E+10 0.00 18372799.15 0.142729E+10 0.00 0.374516E+10 0.00 0.49
May 0.00 0.228910E+11 0.00 0.00 0.156529E+10 0.00 0.00 0.00 0.39
June 0.00 0.249353E+11 0.00 0.00 0.161225E+10 0.00 0.00 0.00 0.41
July 0.00 0.298576E+11 0.00 0.00 0.162916E+10 0.00 0.00 0.00 0.38
August 0.00 0.326281E+11 0.00 0.00 0.146677E+10 0.00 0.00 0.00 0.45
September 0.00 0.308230E+11 0.00 0.00 0.196112E+10 0.00 0.00 0.00 0.43
October 0.214283E+10 0.261562E+11 0.00 22247080.46 0.810275E+09 0.00 0.557200E+10 0.00 0.61
November 0.544562E+10 0.108347E+11 0.00 78778565.83 0.558205E+09 0.00 0.226075E+11 0.00 0.82
December 0.131866E+11 0.854337E+10 0.00 70406082.69 0.722859E+09 0.712804E+09 0.250054E+11 0.00 0.71
                   
Annual Sum or Average 0.628727E+11 0.213697E+12 0.00 0.325594E+09 0.133682E+11 0.167712E+10 0.119300E+12 0.00 0.55
Minimum of Months 0.00 0.413624E+10 0.00 0.00 0.340215E+09 0.00 0.00 0.00 0.38
Maximum of Months 0.147140E+11 0.326281E+11 0.00 78778565.83 0.196112E+10 0.712804E+09 0.327006E+11 0.00 0.82



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.214391E+11 0.212982E+10 0.00 6539490.18 0.689053E+09 0.643917E+09 0.457913E+10 0.00 0.56
February 0.119990E+11 0.300697E+10 0.00 7495234.17 0.612124E+09 0.334204E+09 0.367915E+10 0.00 0.58
March 0.151332E+11 0.415719E+10 0.00 16167001.05 0.663307E+09 3514174.90 0.644152E+10 0.00 0.66
April 0.285299E+10 0.887854E+10 0.00 19487455.90 0.851494E+09 0.00 0.365877E+10 0.00 0.65
May 0.00 0.198234E+11 0.00 0.00 0.869130E+09 0.00 0.00 0.00 0.52
June 0.00 0.227928E+11 0.00 0.00 0.798535E+09 0.00 0.00 0.00 0.57
July 0.00 0.262800E+11 0.00 0.00 0.732143E+09 0.00 0.00 0.00 0.51
August 0.00 0.270945E+11 0.00 0.00 0.711414E+09 0.00 0.00 0.00 0.57
September 0.00 0.218245E+11 0.00 0.00 0.139611E+10 0.00 0.00 0.00 0.47
October 0.214256E+10 0.152342E+11 0.00 9938190.91 0.865676E+09 0.00 0.298250E+10 0.00 0.56
November 0.101277E+11 0.537926E+10 0.00 14351815.19 0.749007E+09 0.00 0.475074E+10 0.00 0.63
December 0.187818E+11 0.422177E+10 0.00 7240430.00 0.963979E+09 0.518225E+09 0.318432E+10 0.00 0.57
                   
Annual Sum or Average 0.824764E+11 0.160823E+12 0.00 81219617.41 0.990197E+10 0.149986E+10 0.292761E+11 0.00 0.57
Minimum of Months 0.00 0.212982E+10 0.00 0.00 0.612124E+09 0.00 0.00 0.00 0.47
Maximum of Months 0.214391E+11 0.270945E+11 0.00 19487455.90 0.139611E+10 0.643917E+09 0.644152E+10 0.00 0.66



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.173248E+10 0.126092E+09 44218.63 5115.83 0.197271E+09 0.108314E+10 2402251.46 805.46 0.41
February 0.110905E+10 0.197348E+09 0.00 1966.15 0.189102E+09 0.525241E+09 29759229.45 0.00 0.40
March 0.172070E+10 0.375622E+09 0.00 136212.13 0.202497E+09 0.380318E+09 55729567.55 0.00 0.44
April 0.507250E+09 0.705860E+09 0.00 728922.21 0.243523E+09 0.00 0.156685E+09 0.00 0.39
May 0.00 0.221722E+10 0.00 0.00 0.143108E+09 0.00 0.00 0.00 0.38
June 0.00 0.260664E+10 0.00 0.00 0.132856E+09 0.00 0.00 0.00 0.42
July 0.00 0.303335E+10 0.00 0.00 0.142147E+09 0.00 0.00 0.00 0.39
August 0.00 0.286650E+10 0.00 0.00 0.172879E+09 0.00 0.00 0.00 0.40
September 0.00 0.231931E+10 0.00 0.00 0.290631E+09 0.00 0.00 0.00 0.34
October 0.323443E+09 0.149313E+10 0.00 619510.19 0.191110E+09 0.00 0.185909E+09 0.00 0.37
November 0.129336E+10 0.435089E+09 2202486.45 252348.31 0.232182E+09 77619294.43 89911648.44 7348.84 0.43
December 0.152943E+10 0.290024E+09 1644674.45 168.57 0.279565E+09 0.755893E+09 4048418.54 18289.18 0.40
                   
Annual Sum or Average 0.821570E+10 0.166662E+11 3891379.54 1744243.38 0.241687E+10 0.282221E+10 0.524444E+09 26443.47 0.40
Minimum of Months 0.00 0.126092E+09 0.00 0.00 0.132856E+09 0.00 0.00 0.00 0.34
Maximum of Months 0.173248E+10 0.303335E+10 2202486.45 728922.21 0.290631E+09 0.108314E+10 0.185909E+09 18289.18 0.44



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.180809E+10 0.142997E+09 0.00 12244.35 0.130339E+09 0.418263E+09 3043982.86 0.00 0.51
February 0.103706E+10 0.252980E+09 0.00 221737.36 98697542.03 0.168393E+09 0.110958E+09 0.00 0.51
March 0.106576E+10 0.466136E+09 0.00 1003792.18 98403245.98 0.218547E+09 0.473024E+09 0.00 0.60
April 0.247681E+09 0.790090E+09 0.00 1622821.47 0.141922E+09 0.00 0.430717E+09 0.00 0.60
May 0.00 0.198498E+10 0.00 0.00 0.104238E+09 0.00 0.00 0.00 0.53
June 0.00 0.226788E+10 0.00 0.00 86609654.69 0.00 0.00 0.00 0.57
July 0.00 0.264361E+10 0.00 0.00 0.106103E+09 0.00 0.00 0.00 0.52
August 0.00 0.245565E+10 0.00 0.00 0.128888E+09 0.00 0.00 0.00 0.53
September 0.00 0.198984E+10 0.00 0.00 0.223884E+09 0.00 0.00 0.00 0.45
October 0.203716E+09 0.137435E+10 0.00 742118.80 0.139289E+09 397305.23 0.218223E+09 0.00 0.51
November 0.824461E+09 0.443899E+09 206966.27 688563.67 0.141444E+09 23051105.76 0.323237E+09 35.35 0.54
December 0.138333E+10 0.249148E+09 482205.77 94768.14 0.201887E+09 0.393702E+09 37553115.77 3453.83 0.49
                   
Annual Sum or Average 0.657010E+10 0.150616E+11 689172.05 4386045.97 0.160170E+10 0.122235E+10 0.159676E+10 3489.18 0.53
Minimum of Months 0.00 0.142997E+09 0.00 0.00 86609654.69 0.00 0.00 0.00 0.45
Maximum of Months 0.180809E+10 0.264361E+10 482205.77 1622821.47 0.223884E+09 0.418263E+09 0.473024E+09 3453.83 0.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.123100E+10 0.476727E+09 0.00 4237224.65 72707902.70 0.330721E+09 0.212106E+10 0.00 0.58
February 0.802037E+09 0.726634E+09 0.00 2793453.53 63536529.41 0.152266E+09 0.115747E+10 0.00 0.59
March 0.128739E+10 0.720288E+09 0.00 2668856.68 99051704.90 0.248279E+09 0.101701E+10 0.00 0.58
April 0.383714E+09 0.951338E+09 0.00 1757309.96 0.192101E+09 0.00 0.386338E+09 0.00 0.48
May 0.00 0.227037E+10 0.00 0.00 0.137526E+09 0.00 0.00 0.00 0.39
June 0.00 0.246503E+10 0.00 0.00 0.157326E+09 0.00 0.00 0.00 0.41
July 0.00 0.297866E+10 0.00 0.00 0.156411E+09 0.00 0.00 0.00 0.38
August 0.00 0.324313E+10 0.00 0.00 0.123962E+09 0.00 0.00 0.00 0.44
September 0.00 0.308236E+10 0.00 0.00 0.184539E+09 0.00 0.00 0.00 0.43
October 0.203597E+09 0.253889E+10 0.00 1929110.35 74193255.67 0.00 0.492810E+09 0.00 0.59
November 0.570462E+09 0.107023E+10 0.00 6016819.66 85134489.07 6102495.96 0.177998E+10 0.00 0.75
December 0.118238E+10 0.822027E+09 0.00 5395525.80 0.117235E+09 0.245163E+09 0.164902E+10 0.00 0.64
                   
Annual Sum or Average 0.566059E+10 0.213457E+11 0.00 24798300.62 0.146373E+10 0.982531E+09 0.860368E+10 0.00 0.52
Minimum of Months 0.00 0.476727E+09 0.00 0.00 63536529.41 0.00 0.00 0.00 0.38
Maximum of Months 0.128739E+10 0.324313E+10 0.00 6016819.66 0.192101E+09 0.330721E+09 0.212106E+10 0.00 0.75



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.183800E+10 0.210082E+09 0.00 323284.03 0.124967E+09 0.445075E+09 0.222726E+09 0.00 0.58
February 0.109205E+10 0.319732E+09 0.00 486122.51 0.109350E+09 0.178818E+09 0.227510E+09 0.00 0.59
March 0.138000E+10 0.427968E+09 0.00 1383965.05 0.118857E+09 0.162578E+09 0.531856E+09 0.00 0.68
April 0.334374E+09 0.885134E+09 0.00 1700616.25 0.124714E+09 0.00 0.354814E+09 0.00 0.65
May 0.00 0.193660E+10 0.00 0.00 78291903.79 0.00 0.00 0.00 0.51
June 0.00 0.221779E+10 0.00 0.00 66385371.17 0.00 0.00 0.00 0.56
July 0.00 0.256682E+10 0.00 0.00 81421222.38 0.00 0.00 0.00 0.50
August 0.00 0.265381E+10 0.00 0.00 73212741.46 0.00 0.00 0.00 0.56
September 0.00 0.215201E+10 0.00 0.00 0.178037E+09 0.00 0.00 0.00 0.47
October 0.247039E+09 0.147477E+10 0.00 799060.23 99125149.14 0.00 0.240418E+09 0.00 0.56
November 0.993879E+09 0.489716E+09 0.00 1068149.49 0.158707E+09 12866286.42 0.370034E+09 0.00 0.64
December 0.158860E+10 0.391388E+09 775783.56 453780.89 0.166073E+09 0.272688E+09 0.197817E+09 637.27 0.58
                   
Annual Sum or Average 0.747395E+10 0.157258E+11 775783.56 6214978.44 0.137914E+10 0.107202E+10 0.214517E+10 637.27 0.57
Minimum of Months 0.00 0.210082E+09 0.00 0.00 66385371.17 0.00 0.00 0.00 0.47
Maximum of Months 0.183800E+10 0.265381E+10 775783.56 1700616.25 0.178037E+09 0.445075E+09 0.531856E+09 637.27 0.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 31761234.67 0.00 2499321.68 0.00 0.00 0.325698E+09 0.00 0.28
February 0.00 50573442.05 0.00 4289320.22 0.00 0.00 0.174383E+09 0.00 0.29
March 0.00 86698685.99 0.00 8563519.47 0.00 0.00 0.218022E+09 0.00 0.31
April 0.00 0.167192E+09 0.00 4765828.86 0.00 0.00 48903953.93 0.00 0.29
May 0.00 0.425218E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.29
June 0.00 0.526346E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.30
July 0.00 0.610408E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.625334E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.430119E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.29
October 0.00 0.353820E+09 0.00 1511633.75 0.00 0.00 44334330.17 0.00 0.28
November 0.00 0.127563E+09 0.00 6718114.40 0.00 0.00 0.122729E+09 0.00 0.28
December 0.00 94096557.67 0.00 10973848.77 0.00 0.00 0.239241E+09 0.00 0.28
                   
Annual Sum or Average 0.00 0.352913E+10 0.00 39321587.15 0.00 0.00 0.117331E+10 0.00 0.29
Minimum of Months 0.00 31761234.67 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.00 0.625334E+09 0.00 10973848.77 0.00 0.00 0.325698E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.293209E+09 0.00 16089098.09 0.00 0.00 0.327550E+10 0.00 0.28
February 0.00 0.496334E+09 0.00 36178164.97 0.00 0.00 0.175300E+10 0.00 0.29
March 0.00 0.863791E+09 0.00 76536556.06 0.00 0.00 0.218594E+10 0.00 0.31
April 0.00 0.167345E+10 0.00 44782932.01 0.00 0.00 0.489800E+09 0.00 0.29
May 0.00 0.420335E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.29
June 0.00 0.524472E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.30
July 0.00 0.609517E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.624778E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.423333E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.29
October 0.00 0.352067E+10 0.00 13667499.47 0.00 0.00 0.443812E+09 0.00 0.28
November 0.00 0.127208E+10 0.00 60799187.63 0.00 0.00 0.123103E+10 0.00 0.28
December 0.00 0.940344E+09 0.00 98430274.05 0.00 0.00 0.239833E+10 0.00 0.28
                   
Annual Sum or Average 0.00 0.350842E+11 0.00 0.346484E+09 0.00 0.00 0.117774E+11 0.00 0.29
Minimum of Months 0.00 0.293209E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.00 0.624778E+10 0.00 98430274.05 0.00 0.00 0.327550E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 70776027.57 28866282.46 0.00 925577.93 0.00 0.00 0.257849E+09 0.00 0.28
February 0.00 49275002.47 0.00 3203744.79 0.00 0.00 0.176424E+09 0.00 0.29
March 0.00 86183203.25 0.00 7197961.25 0.00 0.00 0.219424E+09 0.00 0.31
April 0.00 0.167024E+09 0.00 4400143.59 0.00 0.00 49197104.84 0.00 0.29
May 0.00 0.422449E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.29
June 0.00 0.525103E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.30
July 0.00 0.609499E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.625028E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.424987E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.29
October 0.00 0.352139E+09 0.00 1299728.08 0.00 0.00 44543205.65 0.00 0.28
November 0.00 0.126891E+09 0.00 5742708.57 0.00 0.00 0.123814E+09 0.00 0.28
December 0.00 93759013.06 0.00 9218107.06 0.00 0.00 0.240830E+09 0.00 0.28
                   
Annual Sum or Average 70776027.57 0.351120E+10 0.00 31987971.27 0.00 0.00 0.111208E+10 0.00 0.29
Minimum of Months 0.00 28866282.46 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 70776027.57 0.625028E+09 0.00 9218107.06 0.00 0.00 0.257849E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:07:54

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.425768E+12 0.217507E+10 0.00 0.140861E+13 0.530332E+12
February 0.454591E+12 0.181921E+10 0.00 0.102811E+13 0.769774E+12
March 0.519601E+12 0.153588E+10 0.00 0.110399E+13 0.984890E+12
April 0.576130E+12 -312818542.7 0.00 0.367431E+12 0.151169E+13
May 0.573463E+12 -0.424138E+10 0.00 -0.677801E+12 0.202148E+13
June 0.569999E+12 -0.318563E+10 0.00 -0.782208E+12 0.221727E+13
July 0.589439E+12 -0.535040E+10 0.00 -0.876941E+12 0.243811E+13
August 0.543727E+12 -0.525789E+10 0.00 -0.877357E+12 0.260180E+13
September 0.471943E+12 -0.534730E+10 0.00 -0.686919E+12 0.201377E+13
October 0.475717E+12 -0.366496E+10 0.00 -0.191888E+12 0.191713E+13
November 0.369766E+12 0.665741E+09 0.00 0.896860E+12 0.123178E+13
December 0.382204E+12 0.171248E+10 0.00 0.128262E+13 0.971709E+12
           
Annual Sum or Average 0.595235E+13 -0.194520E+11 0.00 0.199451E+13 0.192097E+14
Minimum of Months 0.369766E+12 -0.535040E+10 0.00 -0.877357E+12 0.530332E+12
Maximum of Months 0.589439E+12 0.217507E+10 0.00 0.140861E+13 0.260180E+13