Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:07
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 09:07:50
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31138.24 | 672.24 | 672.24 |
Net Site Energy | 31138.24 | 672.24 | 672.24 |
Total Source Energy | 79762.47 | 1721.97 | 1721.97 |
Net Source Energy | 79762.47 | 1721.97 | 1721.97 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1053.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 628.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7177.60 | 0.00 | 0.00 |
Interior Lighting | 2035.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 330.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3108.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1011.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 234.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 160.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1628.36 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 721.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 22185.30 | 1775.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7177.60 | 0.00 | 3908.53 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1053.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 628.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7177.60 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2035.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 330.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ComputerHVAC | 1199.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 1011.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 234.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 160.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1628.36 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 721.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1053.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 628.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7177.60 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2035.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 330.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 3108.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 1011.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 234.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 160.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1628.36 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 721.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 51.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 43.93 | 38.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.96 | 0.00 | 0.08 |
Other | 383.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 478.95 | 38.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.96 | 0.00 | 0.08 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 51.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 43.93 | 38.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.96 | 0.00 | 0.08 |
Other | 383.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 478.95 | 38.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.96 | 0.00 | 0.08 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 22185.302 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 22185.302 | 100.00 |
Total On-Site and Utility Electric Sources | 22185.302 | 100.00 |
Total Electricity End Uses | 22185.302 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 3908.53 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 3908.53 | 100.00 |
Total Water End Uses | 3908.53 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 20.83 |
Time Setpoint Not Met During Occupied Cooling | 77.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionDistrictHeatingCoolingMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:07 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.8895 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.8895 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 5.9168 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 5.9168 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.8895 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8895 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.8895 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8895 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.8895 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.9168 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.9168 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.8190 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
Time of Peak | 29-AUG-15:09 | 02-JAN-05:10 | - | - | - | - | - | - | - | - | 14-AUG-15:00 | 31-MAY-23:40 | 10-AUG-15:00 |
Heating | 0.00 | 1185094.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 | 0.00 |
Cooling | 241858.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369998.69 | 0.00 | 0.00 |
Interior Lighting | 171235.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 143548.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 187638.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 44596.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 40919.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 5695.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1608169.36 | 1190789.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369998.69 | 13.46 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 | 0.00 |
Boiler | 0.00 | 1185094.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 241858.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369998.69 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 171235.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3372.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ComputerHVAC | 60741.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 187638.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 44596.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 40919.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 5695.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1142.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Cooling | 1990.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7577.16 | 0.00 |
Interior Lighting | 6445.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1046.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 9843.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3202.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 742.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 509.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 782.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 70260.85 | 1924.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7577.16 | 0.01 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 24.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 42.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.58 | 0.00 |
Interior Lighting | 139.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 22.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 212.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 69.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 16.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 10.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1516.85 | 41.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.58 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 24.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 42.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.58 | 0.00 |
Interior Lighting | 139.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 22.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 212.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 69.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 16.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 10.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1516.85 | 41.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.58 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 4.91 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.490998 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.69 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.476884 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.28 | 0.360570 | 0.353000 | 1.86 | 0.961520 | 0.500000 | 0.001057 | 0.000162 | 1.86 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 49.21 | 0.386545 | 0.368000 | 18.11 | 1.00 | 0.500000 | 0.000986 | 0.003281 | 18.11 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 4.75 | 0.400350 | 0.392000 | 1.86 | 1.00 | 0.500000 | 0.000952 | 0.000620 | 2.14 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.759246 | 0.314550 | 0.308000 | 0.233848 | 0.838799 | 0.500000 | 0.001211 | 0.000061 | 0.233848 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.05 | 0.146014 | 0.200000 | 0.210808 | 0.389372 | 0.500000 | 0.002609 | 0.000049 | 0.210808 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.49 | 0.160788 | 0.200000 | 0.297069 | 0.428768 | 0.500000 | 0.002370 | 0.000082 | 0.297069 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.29 | 0.119013 | 0.200000 | 0.258635 | 0.317369 | 0.500000 | 0.003201 | 0.000039 | 0.258635 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 6.78 | 0.352206 | 0.336000 | 2.28 | 0.939215 | 0.500000 | 0.001082 | 0.001431 | 4.95 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 10.89 | 0.141372 | 0.200000 | 2.18 | 0.376991 | 0.500000 | 0.002695 | 0.000952 | 3.29 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 15.02 | 0.159003 | 0.200000 | 3.00 | 0.424007 | 0.500000 | 0.002396 | 0.001419 | 4.90 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 11.30 | 0.136145 | 0.200000 | 2.26 | 0.363053 | 0.500000 | 0.002798 | 0.000860 | 2.97 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.769236 | 0.310465 | 0.304000 | 0.233848 | 0.827906 | 0.500000 | 0.001227 | 0.000194 | 0.671358 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.08 | 0.142559 | 0.200000 | 0.215918 | 0.380156 | 0.500000 | 0.002673 | 0.000128 | 0.443000 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.60 | 0.149219 | 0.200000 | 0.320100 | 0.397919 | 0.500000 | 0.002553 | 0.000193 | 0.666402 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.20 | 0.128663 | 0.200000 | 0.239238 | 0.343101 | 0.500000 | 0.002961 | 0.000121 | 0.419142 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18481.79 | 0.000162 | 372.58 |
CORE_MID VAV BOX REHEAT COIL | 375031.35 | 0.003281 | 8475.61 |
CORE_TOP VAV BOX REHEAT COIL | 70826.43 | 0.000620 | 1870.82 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7029.62 | 0.000061 | 178.08 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5597.43 | 0.000049 | 135.59 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9425.32 | 0.000082 | 244.14 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4456.39 | 0.000039 | 96.89 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 163569.15 | 0.001431 | 4315.37 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 108845.88 | 0.000952 | 2871.52 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 162175.18 | 0.001419 | 4278.63 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 98248.28 | 0.000860 | 2592.24 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 22189.65 | 0.000194 | 585.23 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14641.25 | 0.000128 | 386.14 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22026.19 | 0.000193 | 580.93 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13854.17 | 0.000121 | 365.40 |
VAV_BOT WITH REHEAT HEATING COIL | 51547.46 | 0.000451 | 844.44 |
VAV_MID WITH REHEAT HEATING COIL | 475984.10 | 0.004164 | 7794.22 |
VAV_TOP WITH REHEAT HEATING COIL | 51244.92 | 0.000448 | 840.18 |
CAV_BAS HEATING COIL | 240273.75 | 0.002102 | 5345.37 |
Design Size Maximum Heating Air Flow Rate [m3/s] | Design Size Maximum Cooling Air Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT | 0.338402 | 21.53 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 4.93 | 2.86 | 9.87 | 2.86 | 8.51 | 8.51 | 0.300000 | 0.336307 | 8.51 |
VAV_MID WITH REHEAT | 46.60 | 27.83 | 93.20 | 27.83 | 78.25 | 78.25 | 0.300000 | 0.355647 | 78.25 |
VAV_TOP WITH REHEAT | 4.70 | 2.87 | 9.40 | 4.34 | 8.54 | 8.54 | 0.300000 | 0.507921 | 8.54 |
CAV_BAS | 4.91 | 4.91 | 4.91 | 4.91 | 4.91 | 4.91 | 1.00 | 1.00 | 4.91 |
AIRLOOP DATACENTER BOT | 0.490998 | 0.490998 | 0.490998 | 0.490998 | 0.490998 | 0.490998 | 1.00 | 1.00 | 0.490998 |
AIRLOOP DATACENTER MID | 4.69 | 4.69 | 4.69 | 4.69 | 4.69 | 4.69 | 1.00 | 1.00 | 4.69 |
AIRLOOP DATACENTER TOP | 0.476884 | 0.476884 | 0.476884 | 0.476884 | 0.476884 | 0.476884 | 1.00 | 1.00 | 0.476884 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.51 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 78.25 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.54 | |
CAV_BAS_OA_CONTROLLER | 4.91 | |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.490998 | 0.015633 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.69 | 0.156328 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.476884 | 0.015633 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.65 | 6.67 | 10.92 | 0.008863 | 0.008500 | 161229.47 | 0.006859 | 8.51 |
VAV_MID WITH REHEAT COOLING COIL | 25.84 | 6.67 | 10.92 | 0.008889 | 0.008500 | 1506394.28 | 0.064085 | 78.25 |
VAV_TOP WITH REHEAT COOLING COIL | 25.61 | 6.67 | 10.92 | 0.008857 | 0.008500 | 161122.55 | 0.006855 | 8.54 |
CAV_BAS COOLING COIL | 25.35 | 6.67 | 11.40 | 0.009003 | 0.008500 | 90416.94 | 0.003847 | 4.91 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.51 |
VAV_MID WITH REHEAT FAN | 78.25 |
VAV_TOP WITH REHEAT FAN | 8.54 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006859 | 0.000069 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000451 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.064085 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.004164 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.006855 | 0.000069 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000448 | |
CAV_BAS_COOLC_CONTROLLER | 0.003847 | 0.000124 |
CAV_BAS_HEATC_CONTROLLER | 0.002102 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 4.91 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.490998 | 9495.76 | 6878.09 | 0.000233 |
AIRLOOP DATACENTER MID COOLING COIL | 4.69 | 90801.16 | 65752.21 | 0.002224 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.476884 | 9225.78 | 6681.32 | 0.000226 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.490998 | 0.490998 | 0.490998 | 0.490998 | 9495.76 | 9495.76 | 824.16 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.69 | 4.69 | 4.69 | 4.69 | 90801.16 | 90801.16 | 8241.59 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.476884 | 0.476884 | 0.476884 | 0.476884 | 9225.78 | 9225.78 | 824.16 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.490998 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.69 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.476884 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT HEATING COIL | 0.490998 | 9495.76 | 0.000233 |
AIRLOOP DATACENTER MID HEATING COIL | 4.69 | 90801.16 | 0.002224 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.476884 | 9225.78 | 0.000226 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 824.16 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8241.59 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 824.16 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.081646 | 16657.56 | |
HEATSYS1 PUMP | 0.016757 | 4996.56 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.081646 | 9.80 |
HEATSYS1 | 0.016757 | 2.01 |
COOLSYS1_SUPPLY | 0.081646 | 9.80 |
SINGLE WATER PLANT LOOP | 0.002682 | 0.321864 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.081646 | 0.081646 | 342707.72 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1915448.31 | 1915448.31 | 0.016757 |
CENTRAL BOILER | 110483.80 | 110483.80 | 0.002682 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.081646 | 11532.59 |
PLANT CIRC PUMP | 0.002682 | 677.32 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.081646 | 0.041069 | 966438.36 | 972320.61 | 0.049295 |
COOLSYS1 CHILLER2 | 0.081646 | 0.041069 | 966438.36 | 972320.61 | 0.049295 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.002682 | 35644.39 | 21050.84 | 17822.20 | 1996.20 | 5855.09 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.098589 | 11.83 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.098589 | 29398.92 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 37.97 | 1155069.37 | 7.59 | 144383.67 |
TOWERWATERSYS COOLTOWER 2 | 37.97 | 1155069.37 | 7.59 | 144383.67 |
Design Water Flow Rate [m3/s] Equipment # 45 | |
WSHPPLANT OPERATION SCHEME | 0.049978 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.889 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.731 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.889 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.313 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16369.361 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16369.361 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4615.459 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4615.459 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.226 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.149 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.571 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6483 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7026 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4692 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.15847945E-14 | 0.40415870E-16 | -0.13570955E-09 | -0.55776231E-17 |
51 | 8 | 0.19900788E-07 | 0.16227319E-12 | 0.35673126E-03 | -0.22627880E-09 |
52 | 7 | -0.11611995E-01 | 0.86155623E-08 | -0.22179000E-01 | 0.13203260E-03 |
53 | 6 | 0.38824249 | 0.30290701E-05 | 0.45749374 | -0.45461023E-02 |
54 | 5 | -5.0235921 | 0.11413317E-03 | -4.3290265 | 0.61113495E-01 |
55 | 4 | 32.264180 | 0.94131685E-03 | 21.001374 | -0.41231550 |
56 | 3 | -109.65428 | 0.20665218E-02 | -54.756066 | 1.4924847 |
57 | 2 | 195.57288 | 0.11699747E-02 | 77.079281 | -2.8759721 |
58 | 1 | -170.58880 | 0.12564906E-03 | -55.024271 | 2.7354972 |
59 | 0 | 57.057407 | 0.71994484E-06 | 15.597457 | |
60 | 9 | 0.92194319E-15 | 0.45185080E-16 | -0.13934922E-09 | -0.37336789E-17 |
61 | 8 | 0.20414049E-07 | 0.15291409E-12 | 0.36227410E-03 | -0.23211478E-09 |
62 | 7 | -0.11777906E-01 | 0.80689916E-08 | -0.22418053E-01 | 0.13391908E-03 |
63 | 6 | 0.39275134 | 0.28300412E-05 | 0.46134659 | -0.45992504E-02 |
64 | 5 | -5.0676021 | 0.10641223E-03 | -4.3586752 | 0.61659190E-01 |
65 | 4 | 32.458904 | 0.87600040E-03 | 21.117392 | -0.41490080 |
66 | 3 | -110.06874 | 0.19199492E-02 | -54.985491 | 1.4984722 |
67 | 2 | 195.98384 | 0.10853975E-02 | 77.289466 | -2.8824978 |
68 | 1 | -170.74067 | 0.11640795E-03 | -55.084954 | 2.7381589 |
69 | 0 | 57.057407 | 0.66605595E-06 | 15.587079 | |
70 | 9 | 0.99499981E-15 | 0.49201796E-16 | -0.11918706E-09 | -0.33210447E-17 |
71 | 8 | 0.17565796E-07 | 0.20231051E-12 | 0.33086922E-03 | -0.19972915E-09 |
72 | 7 | -0.10835659E-01 | 0.11065463E-07 | -0.21059630E-01 | 0.12320537E-03 |
73 | 6 | 0.36714142 | 0.39371282E-05 | 0.43940598 | -0.42973741E-02 |
74 | 5 | -4.8175888 | 0.14987275E-03 | -4.1895891 | 0.58559222E-01 |
75 | 4 | 31.352470 | 0.12474171E-02 | 20.455190 | -0.40021127 |
76 | 3 | -107.71307 | 0.27606440E-02 | -53.675749 | 1.4644420 |
77 | 2 | 193.64724 | 0.15741070E-02 | 76.090603 | -2.8453956 |
78 | 1 | -169.87685 | 0.17016149E-03 | -54.740743 | 2.7230195 |
79 | 0 | 57.057407 | 0.98204117E-06 | 15.647518 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3628_SHGC_EAST_0.36 | 35 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.361 | ||
2 | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 36 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.361 | ||
3 | WINDOW_U_0.3628_SHGC_WEST_0.36 | 37 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.361 | ||
4 | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 38 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62909E-002 | 0.27318 | 0.51969 | 0.51969 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62909E-002 | 0.27318 | 0.51969 | 0.51969 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62909E-002 | 0.27318 | 0.51969 | 0.51969 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62909E-002 | 0.27318 | 0.51969 | 0.51969 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2.856E-002 | 9.114E-005 | 1.371E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.384E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2.856E-002 | 9.114E-005 | 1.371E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.384E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 4.231E-002 | 1.187E-005 | 1.424E-004 | 3.506E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 4.231E-002 | 1.187E-005 | 1.424E-004 | 3.506E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 4.231E-002 | 1.187E-005 | 1.096E-005 | 3.506E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.1010E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1029E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7549E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7565E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1562E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1575E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7698E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7704E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.1448E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2769E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7927E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.9113E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1881E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2818E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7873E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8319E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1187 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6873E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1364 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.0343E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.4206E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6937E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.7170E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3047E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.1473E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2891E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7953E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.9243E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1901E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2893E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7877E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8332E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.1008E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1028E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7546E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7564E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1561E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1574E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7697E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7704E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1604E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4988E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0075E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4007E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6309E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7441E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0284E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0591E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7265E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4783E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4825E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2857E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8443E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.0753E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8227E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4292E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0306E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1259E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8343E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9040E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5944E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6208E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0285E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0596E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9842E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9860E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6759E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6774E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4572E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4583E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7698E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7704E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0251E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1329E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7098E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7963E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4846E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5460E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7878E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8333E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3321E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9435E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5791E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4777E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5630E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0113E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.7170E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3043E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0241E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1308E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7086E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7936E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4830E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5413E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7873E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8320E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9841E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9859E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6758E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6773E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4572E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4582E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7697E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7704E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9121E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0085E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6802E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7505E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5151E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5408E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0286E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0596E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.5053E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3814E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1975E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1604E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6822E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0059E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8227E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4292E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0300E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.3346E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8380E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1866E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5506E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6602E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0283E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0590E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1122 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.2570E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1248 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1069 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.9410E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.9954E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.2949E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.0811E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.4316E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4059E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1682E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.1864E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.4847E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.8763E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.3948E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1031E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.9272E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7780E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1112E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1896E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0921E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6577E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2949E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0807E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.1909E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.2773E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8577E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0198E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.3109E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7895E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.3948E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1031E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1120 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.2630E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1246 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1069 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.9403E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.0044E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.2998E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.0851E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.4271E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4086E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1647E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.1892E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.4857E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.8811E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.3994E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1071E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.9217E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7791E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1074E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.1905E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0936E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6603E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2998E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0847E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.1865E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.2798E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8542E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0223E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.3119E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7941E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.3994E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1071E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 67259.17531 | 67259.17531 | 4.91008 | 4.91008 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2779.42662 | 149.60210 | 1.20019 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20019 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | -4.20000 | 2.69032E-003 | 2779.42662 | 149.60210 | 1.20019 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 72256.94450 | 72256.94450 | 5.27510 | 5.27510 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 674233.79465 | 674233.79465 | 49.20627 | 49.20627 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 195307.05217 | 195307.05217 | 8.31113 | 10.77825 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 65105.52815 | 65105.52815 | 4.75095 | 4.75095 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 49628.22529 | 49628.22529 | 2.13580 | 2.13580 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 10300.91469 | 10300.91469 | 0.75925 | 0.75925 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 4711.53084 | 4711.53084 | 0.20230 | 0.20230 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14300.61137 | 14300.61137 | 1.05404 | 1.05404 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 23.02133 | 8.81136E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 3507.37855 | 3507.37855 | 0.15076 | 0.15076 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 20152.29379 | 20152.29379 | 1.48535 | 1.48535 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 6479.29096 | 6479.29096 | 0.27893 | 0.27893 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 17545.10508 | 17545.10508 | 1.29317 | 1.29317 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 1894.93719 | 1894.93719 | 8.08270E-002 | 8.72129E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 91995.82905 | 91995.82905 | 6.78071 | 6.78071 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 114513.05671 | 114513.05671 | 4.94541 | 4.94541 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 147702.63309 | 147702.63309 | 10.88656 | 10.88656 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 23.35067 | 8.81188E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 76198.42682 | 76198.42682 | 3.29117 | 3.29117 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 203785.66373 | 203785.66373 | 15.02024 | 15.02024 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 113538.76947 | 113538.76947 | 4.90316 | 4.90316 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 153373.29928 | 153373.29928 | 11.30452 | 11.30452 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 27.77067 | 8.81889E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 68790.81600 | 68790.81600 | 2.96998 | 2.96998 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 10436.45615 | 10436.45615 | 0.76924 | 0.76924 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 15528.97934 | 15528.97934 | 0.67136 | 0.67136 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 14647.27812 | 14647.27812 | 1.07959 | 1.07959 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 10246.17305 | 10246.17305 | 0.44300 | 0.44300 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 21714.65596 | 21714.65596 | 1.60050 | 1.60050 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.82122E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 15414.70757 | 15414.70757 | 0.66640 | 0.66640 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 16229.23309 | 16229.23309 | 1.19619 | 1.19619 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 9695.92462 | 9695.92462 | 0.41914 | 0.41914 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8445.78872 | 8445.78872 | 0.49100 | 0.49100 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.81585E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56328E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 80721.30371 | 80721.30371 | 4.69278 | 4.69278 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.81585E-003 | 36.20274 | 1.94861 | 0.15633 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15633 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 0.15633 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8202.98728 | 8202.98728 | 0.47688 | 0.47688 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.81585E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56328E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370363.23371 | 370363.23371 | 21.53081 | 21.53081 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 19.93600 | 8.80655E-003 | 783.67941 | 42.18139 | 0.33840 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33840 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 02:00:00 | -4.20000 | 2.69032E-003 | 783.67941 | 42.18139 | 0.33840 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 127477.64 | 8.51149 | 8.51149 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 36438.23 | 1.79703 | 1.79703 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1160584.73 | 78.24741 | 78.24741 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 514267.58 | 26.88796 | 26.88796 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:40:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 130333.19 | 8.53618 | 8.53618 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 51457.48 | 4.33570 | 4.33570 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 |
7 | CAV_BAS | Cooling | Sensible | 65085.87 | 4.91008 | 4.91008 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 63273.94 | 1.20019 | 1.20019 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8294.04 | 0.49100 | 0.49100 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BOT | Heating | Sensible | 824.16 | 1.56328E-002 | 1.56328E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER MID | Cooling | Sensible | 79261.57 | 4.69278 | 4.69278 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER MID | Heating | Sensible | 8241.59 | 0.15633 | 0.15633 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8054.99 | 0.47688 | 0.47688 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER TOP | Heating | Sensible | 824.16 | 1.56328E-002 | 1.56328E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.91008 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.27510 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36057 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35300 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.86211 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96152 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05666E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.61687E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.86211 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18481.79481 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.61687E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 372.57848 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 49.20627 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38655 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36800 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.10791 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.85655E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.28094E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.10791 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 375031.34807 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.28094E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8475.60721 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.75095 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.40035 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.39200 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.86237 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.51667E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.19620E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.13580 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 70826.42970 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.19620E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1870.82360 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75925 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31455 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30800 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23385 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83880 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21126E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.14982E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23385 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7029.62490 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.14982E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 178.08279 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05404 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14601 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21081 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38937 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.60933E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.89687E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.21081 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5597.42761 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.89687E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 135.59317 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.48535 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16079 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29707 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42877 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.36958E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.24568E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29707 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9425.31973 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.24568E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 244.14489 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.29317 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11901 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25863 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31737 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.20132E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.89864E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25863 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4456.38999 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.89864E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 96.88804 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.78071 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35221 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33600 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.27832 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93922 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08175E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.43097E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.94541 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 163569.15034 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.43097E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4315.36693 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.88656 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14137 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.17731 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37699 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.69503E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.52231E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.29117 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 108845.87887 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.52231E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2871.51743 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 15.02024 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15900 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.00405 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42401 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.39619E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.41878E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.90316 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 162175.17945 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.41878E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4278.63479 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.30452 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13614 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.26090 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36305 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.79849E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.59519E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.96998 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 98248.28203 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.59519E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2592.23695 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76924 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31046 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30400 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23385 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82791 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22719E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.94125E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.67136 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22189.65057 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.94125E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 585.23231 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07959 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14256 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21592 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38016 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.67259E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.28088E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.44300 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14641.24827 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.28088E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 386.14117 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.60050 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14922 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32010 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39792 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55329E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.92695E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.66640 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22026.18637 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92695E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 580.92518 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.19619 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12866 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23924 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34310 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96123E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21202E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41914 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13854.16924 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21202E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 365.40021 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49100 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.69278 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47688 |
215 | ZoneHVAC:IdealLoadsAirSystem | AIRLOOP DATACENTER BASEMENT | Design Size Maximum Heating Air Flow Rate [m3/s] | 0.33840 |
216 | ZoneHVAC:IdealLoadsAirSystem | AIRLOOP DATACENTER BASEMENT | Design Size Maximum Cooling Air Flow Rate [m3/s] | 21.53081 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.93345 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.86247 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.86691 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.86247 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.51149 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.51149 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.33631 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 46.59915 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 27.82849 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 93.19830 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 27.82849 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 78.24741 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 78.24741 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.35565 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.69823 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.87148 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.39647 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.33570 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.53618 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.53618 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.50792 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.91008 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.91008 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.91008 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 4.91008 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.91008 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 4.91008 |
247 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49100 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49100 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49100 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49100 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49100 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.49100 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
257 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.69278 |
258 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.69278 |
259 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.69278 |
260 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.69278 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.69278 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.69278 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
265 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47688 |
266 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47688 |
267 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47688 |
268 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47688 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47688 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.47688 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
273 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.51149 |
274 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 78.24741 |
275 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.53618 |
276 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 4.91008 |
277 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.49100 |
278 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.69278 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.47688 |
280 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.51149 |
281 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.64666 |
282 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
283 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.91619 |
284 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.86253E-003 |
285 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 161229.46631 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.85907E-003 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.51149 |
289 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 51547.45602 |
290 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.50960E-004 |
291 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 844.44170 |
292 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.51149 |
293 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.85907E-003 |
294 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.94249E-005 |
295 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.50960E-004 |
296 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 78.24741 |
297 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.83538 |
298 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
299 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.91628 |
300 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.88912E-003 |
301 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1506394.28080 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.40855E-002 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 78.24741 |
305 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 475984.09843 |
306 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.16412E-003 |
307 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 7794.22230 |
308 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 78.24741 |
309 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.40855E-002 |
310 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.43055E-006 |
311 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.16412E-003 |
312 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.53618 |
313 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.60537 |
314 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
315 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.91617 |
316 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.85682E-003 |
317 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 161122.54517 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.85453E-003 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.53618 |
321 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 51244.92193 |
322 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.48313E-004 |
323 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 840.17879 |
324 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.53618 |
325 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.85453E-003 |
326 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.94710E-005 |
327 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.48313E-004 |
328 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.91008 |
329 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.34559 |
330 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
331 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.40164 |
332 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.00309E-003 |
333 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
334 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 90416.93614 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.84655E-003 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 4.91008 |
337 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 240273.75335 |
338 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.10202E-003 |
339 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5345.36561 |
340 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 4.91008 |
341 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.84655E-003 |
342 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.23797E-004 |
343 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.10202E-003 |
344 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49100 |
345 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56328E-002 |
346 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49100 |
347 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9495.76000 |
348 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6878.08702 |
349 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32551E-004 |
350 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49100 |
351 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49100 |
352 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49100 |
353 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49100 |
354 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9495.76000 |
355 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9495.76000 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 824.15923 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
358 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49100 |
359 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49100 |
360 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9495.76000 |
361 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32551E-004 |
362 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 824.15923 |
363 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.69278 |
364 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15633 |
365 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.69278 |
366 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 90801.16262 |
367 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 65752.20688 |
368 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.22371E-003 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.69278 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.69278 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.69278 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.69278 |
373 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 90801.16262 |
374 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 90801.16262 |
375 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8241.59228 |
376 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
377 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.69278 |
378 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.69278 |
379 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 90801.16262 |
380 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.22371E-003 |
381 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8241.59228 |
382 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47688 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56328E-002 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47688 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9225.77538 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6681.31542 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25939E-004 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.47688 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.47688 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.47688 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47688 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9225.77538 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9225.77538 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 824.15923 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
396 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47688 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47688 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9225.77538 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25939E-004 |
400 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 824.15923 |
401 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 8.16456E-002 |
402 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 16657.56474 |
403 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 8.16456E-002 |
404 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 9.79748 |
405 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 8.16456E-002 |
406 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 8.16456E-002 |
407 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 342707.71936 |
408 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
409 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.67572E-002 |
410 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.01086 |
411 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.67572E-002 |
412 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 4996.56034 |
413 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
414 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1915448.30969 |
415 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1915448.31000 |
416 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.67572E-002 |
417 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 8.16456E-002 |
418 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 9.79748 |
419 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 8.16456E-002 |
420 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 11532.59397 |
421 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.16456E-002 |
422 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.10686E-002 |
423 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 966438.36039 |
424 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 972320.61000 |
425 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 4.92946E-002 |
426 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.16456E-002 |
427 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.10686E-002 |
428 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 966438.36039 |
429 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 972320.61000 |
430 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 4.92946E-002 |
431 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 2.68220E-003 |
432 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 0.32186 |
433 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 2.68220E-003 |
434 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 677.32288 |
435 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 2.68220E-003 |
436 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 35644.39112 |
437 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 21050.83958 |
438 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 17822.19556 |
439 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 1996.19659 |
440 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 5855.08944 |
441 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 110483.80292 |
442 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 110483.80000 |
443 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 2.68220E-003 |
444 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
445 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
446 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
447 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
448 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
449 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 9.85892E-002 |
450 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 11.83070 |
451 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 9.85892E-002 |
452 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 29398.92113 |
453 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 37.97197 |
454 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1155069.36749 |
455 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 7.59439 |
456 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 144383.67094 |
457 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 37.97197 |
458 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1155069.36749 |
459 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 7.59439 |
460 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 144383.67094 |
461 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 4.99775E-002 |
462 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 4.99775E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17524.52 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 355396.89 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 67124.44 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6657.50 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5302.44 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8925.60 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4223.80 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 154985.01 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 103132.88 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 153664.49 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 93093.53 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21023.88 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13871.99 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20869.03 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13126.38 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 39296.12 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 362541.95 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 39132.36 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 190267.51 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 200876.81 | 141104.66 | 59772.15 | 0.70 | 20946.73 | 212.45 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 1859596.89 | 1303072.86 | 556524.02 | 0.70 | 193634.25 | 1963.95 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 201149.69 | 141373.06 | 59776.63 | 0.70 | 20982.08 | 212.81 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 112600.88 | 79689.73 | 32911.15 | 0.71 | 11474.79 | 116.38 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 7.08 | 24.14 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 7.08 | 24.14 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.36 | N/A | 2.061 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.36 | N/A | 2.061 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.36 | N/A | 2.061 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.36 | N/A | 2.061 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.36 | N/A | 2.061 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.36 | N/A | 2.061 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.36 | N/A | 2.061 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.36 | N/A | 2.061 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.36 | N/A | 2.061 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.36 | N/A | 2.061 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.1993922791 | 0.2161473360 | Pass | Pass | 1.5836473216 | 3.6383749399 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 2.6893145587E-003 | 5.6544002066E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.7305024338E-003 | 6.5545000736E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.5277270409E-002 | 1.1511246788E-002 | Pass | Pass | 0.9013422388 | 3.6174927944 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.0019260007E-002 | 1.0404029546E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.0957257478E-002 | 1.1303273431E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 1.1113433732E-002 | 1.1869901562E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.0346228616E-002 | 1.0883296593E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.1843481904E-002 | 1.2016143673E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.2821631108E-002 | 1.3024109599E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 1.3646451022E-002 | 1.4042739057E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.2763960771E-002 | 1.2669682956E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2281647614 | 0.2131487970 | Pass | Pass | 9.4954781027 | 27.2462381463 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2349684216 | 0.2208970658 | Pass | Pass | 6.8687285001 | 19.9990742236 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2192852214 | 0.2071645862 | Pass | Pass | 6.9845428023 | 19.9730970273 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1003833936 | 0.1132917803 | Pass | Pass | 6.1136955803 | 17.2902626892 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.0767656844E-003 | 1.5509123944E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.4874382545E-003 | 1.8058787999E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.2398179431E-002 | 4.9419029815E-002 | Pass | Pass | 0.4265954309 | 0.4755357767 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.5682153471E-006 | 7.3117948515E-006 | Pass | Pass | 1.2452203850E-003 | 9.3110535377E-004 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.4099049290E-003 | 2.7743320940E-003 | Pass | Pass | 1.2596781065E-003 | 1.1100901879E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.6854655124E-003 | 3.3790292265E-003 | Pass | Pass | 1.6527783913E-003 | 1.4887125556E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.5658487680E-015 | 2.5960362626E-015 | Pass | Pass | 2.8172204013E-005 | 1.1003634298E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5967.22 | 50.23 | 0.00 | 20764.17 | 4910.93 | 31692.55 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3628_SHGC_EAST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3628_SHGC_EAST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.3628_SHGC_EAST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3628_SHGC_WEST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3628_SHGC_WEST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.3628_SHGC_WEST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.061 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3628_SHGC_EAST_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.061 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.061 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3628_SHGC_WEST_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.061 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.061 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3628_SHGC_EAST_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.061 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.061 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3628_SHGC_WEST_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.061 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.061 | 0.361 | 0.361 | |||||||||||||||||
North Total or Average | 1043.06 | 2.061 | 0.361 | 0.361 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.061 | 0.361 | 0.361 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.8895 | 2779.43 | 16369.36 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 135.58 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8895 | 2496.12 | 14700.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 121.76 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8895 | 24961.20 | 147008.37 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 1217.57 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8895 | 2496.12 | 14700.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 121.76 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8895 | 313.41 | 1845.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.79 | 0.0000 | Y | 9.28 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.40 | 0.0000 | Y | 5.89 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8895 | 313.42 | 1845.88 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.03 | 0.0000 | Y | 9.02 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.39 | 0.0000 | Y | 5.89 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8895 | 3134.13 | 18458.37 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.80 | 0.0000 | Y | 92.87 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8895 | 2019.75 | 11895.27 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.39 | 0.0000 | Y | 58.93 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8895 | 3134.20 | 18458.77 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.04 | 0.0000 | Y | 90.24 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8895 | 2019.75 | 11895.27 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.38 | 0.0000 | Y | 58.90 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8895 | 313.41 | 1845.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.80 | 0.0000 | Y | 9.29 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.39 | 0.0000 | Y | 5.89 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8895 | 313.42 | 1845.88 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.04 | 0.0000 | Y | 9.02 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 26.38 | 0.0000 | Y | 5.89 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.8895 | 783.68 | 4615.46 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 38.23 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 8.8011 | 36.20 | 318.62 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.26 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 8.8011 | 362.03 | 3186.24 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 32.64 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 8.8011 | 36.20 | 318.62 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.26 |
Interior Lighting Total | 5.9168 | 46320.38 | 274067.57 | 639.14 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.05 | AstronomicalClock | - | 42.59 | 42.59 | 79.73 | |
EXTERIOR_LIGHTS_B | 991.40 | AstronomicalClock | - | 83.55 | 63.07 | 11.74 | |
EXTERIOR_LIGHTS_C | 26646.63 | AstronomicalClock | - | 83.55 | 47.80 | 239.08 | |
Exterior Lighting Total | 37611.08 | 330.56 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 1914749.72 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1915448.31 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 972320.61 | 5.33 | 961371.79 | 4.98 | 7.08 | 24.14 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 972320.61 | 5.33 | 961371.79 | 4.98 | 7.08 | 24.14 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 148548.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 110483.80 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1155069.37 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1155069.37 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 161229.47 | 200876.81 | 141104.66 | 59772.15 | 0.70 | - | 20946.73 | 212.45 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1506394.28 | 1859596.89 | 1303072.86 | 556524.02 | 0.70 | - | 193634.25 | 1963.95 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 161122.55 | 201149.69 | 141373.06 | 59776.63 | 0.70 | - | 20982.08 | 212.81 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 90416.94 | 112600.88 | 79689.73 | 32911.15 | 0.71 | - | 11474.79 | 116.38 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9495.76 | 6878.09 | 2617.67 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 90801.16 | 65752.21 | 25048.96 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9225.78 | 6681.32 | 2544.46 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18481.79 | 17524.52 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 375031.35 | 355396.89 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 70826.43 | 67124.44 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 7029.62 | 6657.50 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 5597.43 | 5302.44 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9425.32 | 8925.60 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 4456.39 | 4223.80 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 163569.15 | 154985.01 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 108845.88 | 103132.88 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 162175.18 | 153664.49 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 98248.28 | 93093.53 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 22189.65 | 21023.88 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14641.25 | 13871.99 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 22026.19 | 20869.03 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 13854.17 | 13126.38 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 51547.46 | 39296.12 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 475984.10 | 362541.95 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 51244.92 | 39132.36 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 240273.75 | 190267.51 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9495.76 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 90801.16 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9225.78 | 0.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 824.16 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8241.59 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 824.16 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 8.51 | 19437.92 | 2283.73 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 78.25 | 178695.79 | 2283.73 | 1.00 | 1.07 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 8.54 | 19494.32 | 2283.73 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 4.91 | 8325.79 | 1695.65 | 1.00 | 1.16 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 549.97 | 1120.11 | 1.00 | 1.61 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.69 | 5256.42 | 1120.11 | 1.00 | 1.16 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 534.16 | 1120.11 | 1.00 | 1.63 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.081646 | 16657.56 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.016757 | 4996.56 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.081646 | 11532.59 | 141251.81 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.002682 | 677.32 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.098589 | 29398.92 | 298196.27 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 67259.18 | 67259.18 | 24.20 | 4.910 | 4.910 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00902 | 21.70 | 0.00881 | 1.200 | 0.00 |
CORE_BOTTOM | 72256.94 | 72256.94 | 28.95 | 5.275 | 5.275 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 21.70 | 0.00881 | 1.078 | 0.00 |
CORE_MID | 674233.79 | 674233.79 | 270.11 | 49.206 | 49.206 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 21.70 | 0.00881 | 10.778 | 0.00 |
CORE_TOP | 65105.53 | 65105.53 | 26.08 | 4.751 | 4.751 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00898 | 21.70 | 0.00881 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 10300.91 | 10300.91 | 32.87 | 0.759 | 0.759 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00887 | 29.40 | 0.00882 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14300.61 | 14300.61 | 70.80 | 1.054 | 1.054 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00867 | 23.02 | 0.00881 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 20152.29 | 20152.29 | 64.30 | 1.485 | 1.485 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00869 | 29.05 | 0.00882 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 17545.11 | 17545.11 | 86.87 | 1.293 | 1.293 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00864 | 27.94 | 0.00882 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 91995.83 | 91995.83 | 293.53 | 6.781 | 6.781 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00891 | 29.40 | 0.00882 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 147702.63 | 147702.63 | 731.29 | 10.887 | 10.887 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00867 | 23.35 | 0.00881 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 203785.66 | 203785.66 | 650.20 | 15.020 | 15.020 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00869 | 29.14 | 0.00882 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 153373.30 | 153373.30 | 759.37 | 11.305 | 11.305 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00866 | 27.77 | 0.00882 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 10436.46 | 10436.46 | 33.30 | 0.769 | 0.769 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00887 | 29.40 | 0.00882 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14647.28 | 14647.28 | 72.52 | 1.080 | 1.080 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00867 | 23.68 | 0.00881 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 21714.66 | 21714.66 | 69.28 | 1.601 | 1.601 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00868 | 29.23 | 0.00882 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16229.23 | 16229.23 | 80.35 | 1.196 | 1.196 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00865 | 27.94 | 0.00882 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8445.79 | 8445.79 | 233.29 | 0.491 | 0.491 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 25.86 | 0.00882 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 80721.30 | 80721.30 | 2229.70 | 4.693 | 4.693 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 25.86 | 0.00882 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8202.99 | 8202.99 | 226.58 | 0.477 | 0.477 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 25.86 | 0.00882 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370363.23 | 370363.23 | 472.60 | 21.531 | 21.531 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 19.94 | 0.00881 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | 21.00 | 24.63 | 0.00269 | -4.20 | 0.00269 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | 19.60 | 22.28 | 0.00269 | -4.20 | 0.00269 | 1.078 | 0.00 |
CORE_MID | 195307.05 | 195307.05 | 78.24 | 8.311 | 10.778 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 10.778 | 0.00 |
CORE_TOP | 49628.23 | 49628.23 | 19.88 | 2.136 | 2.136 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 4711.53 | 4711.53 | 15.03 | 0.202 | 0.202 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00739 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 3507.38 | 3507.38 | 17.37 | 0.151 | 0.151 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00747 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 6479.29 | 6479.29 | 20.67 | 0.279 | 0.279 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00760 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 1894.94 | 1894.94 | 9.38 | 0.081 | 0.087 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00688 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 114513.06 | 114513.06 | 365.37 | 4.945 | 4.945 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 76198.43 | 76198.43 | 377.27 | 3.291 | 3.291 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 113538.77 | 113538.77 | 362.26 | 4.903 | 4.903 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 68790.82 | 68790.82 | 340.59 | 2.970 | 2.970 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 15528.98 | 15528.98 | 49.55 | 0.671 | 0.671 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 10246.17 | 10246.17 | 50.73 | 0.443 | 0.443 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15414.71 | 15414.71 | 49.18 | 0.666 | 0.666 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 9695.92 | 9695.92 | 48.01 | 0.419 | 0.419 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -4.20 | 0.00269 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 | 18.00 | 26.88 | 0.00850 | -4.20 | 0.00269 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 23.63 | 0.00670 | -4.20 | 0.00269 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 21.79 | 0.00302 | -4.20 | 0.00269 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 02:00:00 | 18.00 | 27.00 | 0.00850 | -4.20 | 0.00269 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 8.51 | 8.51 | 1.80 | 1.80 | 8.5115 | 2.8625 | 8.5115 | 0.3363 | 0.3000 |
VAV_MID WITH REHEAT | 78.25 | 78.25 | 26.89 | 26.89 | 78.2474 | 27.8285 | 78.2474 | 0.3556 | 0.3000 |
VAV_TOP WITH REHEAT | 8.54 | 8.54 | 4.34 | 4.34 | 8.5362 | 4.3357 | 8.5362 | 0.5079 | 0.3000 |
CAV_BAS | 4.91 | 4.91 | 1.20 | 1.20 | 4.9101 | 4.9101 | 4.9101 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.49 | 0.49 | 0.02 | 0.02 | 0.4910 | 0.4910 | 0.4910 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.69 | 4.69 | 0.16 | 0.16 | 4.6928 | 4.6928 | 4.6928 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.48 | 0.48 | 0.02 | 0.02 | 0.4769 | 0.4769 | 0.4769 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18481.795 | 18481.795 | 1.862111 | 0.00016169 | 372.578 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | 18481.79 | 18481.79 | 1.862111 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 18549.94 | 18549.94 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 375031.348 | 375031.348 | 18.107906 | 0.00328094 | 8475.607 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 375031.35 | 375031.35 | 18.107906 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 195307.05 | 0.00 | 376310.91 | 376310.91 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 70826.430 | 70826.430 | 2.135800 | 0.00061962 | 1870.824 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 70826.43 | 70826.43 | 2.135800 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 49628.23 | 0.00 | 71079.94 | 71079.94 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 7029.625 | 7029.625 | 0.233848 | 0.00006150 | 178.083 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7029.62 | 7029.62 | 0.233848 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00738636 | 47.1182 | 4711.53 | 0.00 | 7051.39 | 7051.39 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5597.428 | 5597.428 | 0.210808 | 0.00004897 | 135.593 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5597.43 | 5597.43 | 0.210808 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00747443 | 47.6732 | 3507.38 | 0.00 | 5615.51 | 5615.51 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9425.320 | 9425.320 | 0.297069 | 0.00008246 | 244.145 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9425.32 | 9425.32 | 0.297069 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00760430 | 48.4911 | 6479.29 | 0.00 | 9454.21 | 9454.21 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4456.390 | 4456.390 | 0.258635 | 0.00003899 | 96.888 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4456.39 | 4456.39 | 0.258635 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00688403 | 43.9488 | 1894.94 | 0.00 | 4471.89 | 4471.89 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 163569.150 | 163569.150 | 4.945412 | 0.00143097 | 4315.367 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 163569.15 | 163569.15 | 4.945412 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00774635 | 49.3859 | 114513.06 | 0.00 | 164117.44 | 164117.44 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 108845.879 | 108845.879 | 3.291167 | 0.00095223 | 2871.517 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 108845.88 | 108845.88 | 3.291167 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00775622 | 49.4480 | 76198.43 | 0.00 | 109209.93 | 109209.93 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 162175.179 | 162175.179 | 4.903155 | 0.00141878 | 4278.635 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 162175.18 | 162175.18 | 4.903155 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00774132 | 49.3543 | 113538.77 | 0.00 | 162719.12 | 162719.12 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 98248.282 | 98248.282 | 2.969977 | 0.00085952 | 2592.237 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 98248.28 | 98248.28 | 2.969977 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00769424 | 49.0581 | 68790.82 | 0.00 | 98579.05 | 98579.05 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 22189.651 | 22189.651 | 0.671358 | 0.00019412 | 585.232 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22189.65 | 22189.65 | 0.671358 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00782795 | 49.8992 | 15528.98 | 0.00 | 22262.69 | 22262.69 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14641.248 | 14641.248 | 0.443000 | 0.00012809 | 386.141 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14641.25 | 14641.25 | 0.443000 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00782763 | 49.8972 | 10246.17 | 0.00 | 14689.38 | 14689.38 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 22026.186 | 22026.186 | 0.666402 | 0.00019269 | 580.925 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22026.19 | 22026.19 | 0.666402 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00782621 | 49.8882 | 15414.71 | 0.00 | 22098.71 | 22098.71 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 13854.169 | 13854.169 | 0.419142 | 0.00012120 | 365.400 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13854.17 | 13854.17 | 0.419142 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00781231 | 49.8008 | 9695.92 | 0.00 | 13899.83 | 13899.83 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 161229.466 | -999.000 | 8.511487 | 0.00685907 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 161229.47 | 151608.36 | 8.511487 | 25.65 | 17.12 | 0.00886253 | 10.92 | 10.92 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 29.8208 | 24.00 | 0.00888055 | 47.0979 | 112871.12 | 0.00 | 163024.95 | 142927.20 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 51547.456 | 51547.456 | 2.553446 | 0.00045096 | 844.442 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 51547.46 | 51547.46 | 2.553446 | -4.12 | -4.14 | 0.00270165 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 99.4025 | 21.58 | 0.00532073 | 32.8576 | 16593.14 | 0.00 | 47538.60 | 47538.60 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1506394.281 | -999.000 | 78.247410 | 0.06408549 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1506394.28 | 1411493.94 | 78.247410 | 25.84 | 17.21 | 0.00888912 | 10.92 | 10.92 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 32.4381 | 24.00 | 0.00892396 | 47.3249 | 1012725.19 | 0.00 | 1523028.65 | 1332182.84 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 475984.098 | 475984.098 | 23.474223 | 0.00416412 | 7794.222 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 475984.10 | 475984.10 | 23.474223 | -4.20 | -4.20 | 0.00269032 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 108.1269 | 21.00 | 0.00779069 | 49.6638 | 491719.43 | 0.00 | 438583.70 | 438583.70 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 161122.545 | -999.000 | 8.536182 | 0.00685453 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 161122.55 | 151624.95 | 8.536182 | 25.61 | 17.10 | 0.00885682 | 10.92 | 10.92 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 29.7345 | 24.00 | 0.00887177 | 47.0520 | 115771.51 | 0.00 | 162920.19 | 142907.00 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 51244.922 | 51244.922 | 2.560855 | 0.00044831 | 840.179 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 51244.92 | 51244.92 | 2.560855 | -3.98 | -3.99 | 0.00273612 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 99.1150 | 21.00 | 0.00786558 | 50.1350 | 58394.36 | 0.00 | 47341.16 | 47341.16 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 90416.936 | -999.000 | 4.910076 | 0.00384655 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 90416.94 | 82955.69 | 4.910076 | 25.35 | 17.13 | 0.00900309 | 11.40 | 11.39 | 0.00850000 | 28.88 | 0.00882066 | 18.17 | 24.4434 | 24.00 | 0.00907261 | 48.1022 | 59010.53 | 0.00 | 91445.30 | 79134.57 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 240273.753 | 240273.753 | 4.910076 | 0.00210202 | 5345.366 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 240273.75 | 240273.75 | 4.910076 | -1.03 | -2.32 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 24.4434 | 24.67 | 0.00269032 | 13.8378 | 0.00 | 0.00 | 201038.70 | 201038.70 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9495.760 | 6878.087 | 0.490998 | 0.00023255 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 8800.09 | 8678.02 | -999.0 | 27.92 | 17.67 | 0.00859303 | 12.80 | 11.97 | 0.00850000 | 25.86 | 0.00881585 | 17.16 | -999.0000 | 27.00 | 0.00858570 | 38.1215 | 8445.79 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 90801.163 | 65752.207 | 4.692779 | 0.00222371 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 84155.44 | 82936.40 | -999.0 | 27.92 | 17.67 | 0.00859719 | 12.80 | 11.97 | 0.00850000 | 25.86 | 0.00881585 | 17.16 | -999.0000 | 27.00 | 0.00858965 | 38.1390 | 80721.30 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9225.775 | 6681.315 | 0.476884 | 0.00022594 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 8550.32 | 8428.26 | -999.0 | 27.92 | 17.67 | 0.00859577 | 12.80 | 11.97 | 0.00850000 | 25.86 | 0.00881585 | 17.16 | -999.0000 | 27.00 | 0.00858831 | 38.1330 | 8202.99 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9495.760 | 9495.760 | 0.490998 | 0.00023255 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9495.76 | 9495.76 | 0.490998 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1839 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 90801.163 | 90801.163 | 4.692779 | 0.00222371 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 90801.16 | 90801.16 | 4.692779 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.3312 | 24.77 | 0.00670051 | 34.0575 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9225.775 | 9225.775 | 0.476884 | 0.00022594 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9225.78 | 9225.78 | 0.476884 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.2781 | 23.62 | 0.00301695 | 16.5233 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 824.159 | 824.159 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.16 | 824.16 | 0.490998 | -0.13 | -0.13 | 0.00831503 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1839 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8241.592 | 8241.592 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8241.59 | 8241.59 | 4.692779 | -0.14 | -0.14 | 0.00656692 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.3312 | 24.77 | 0.00670051 | 34.0575 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 824.159 | 824.159 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.16 | 824.16 | 0.476884 | -0.14 | -1.32 | 0.00300625 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.2781 | 23.62 | 0.00301695 | 16.5233 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18481.795 | 18481.795 | 1.862111 | 0.00016169 | 372.578 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 0.9458 | 0.964881 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | Sensible | 18481.79 | 18481.79 | 1.0000 | 2.21030869 | 1.862111 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.16167031 | 60.00 | 32.22 | 27.78 | 0.000 | 18481.79 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 18549.94 | 18549.94 | 2.21030869 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 375031.348 | 375031.348 | 18.107906 | 0.00328094 | 8475.607 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 19.1930 | 19.579299 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 375031.35 | 375031.35 | 1.0000 | 21.49391743 | 18.107906 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 3.28060315 | 60.00 | 32.22 | 27.78 | 0.000 | 375031.35 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.56 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 195307.05 | 0.00 | 376310.91 | 376310.91 | 21.49391743 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.97 | 18.03 | 0.00800000 | 50567.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 70826.430 | 70826.430 | 2.135800 | 0.00061962 | 1870.824 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 3.6247 | 3.697642 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 70826.43 | 70826.43 | 1.0000 | 2.53517453 | 2.135800 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.61955730 | 60.00 | 32.22 | 27.78 | 0.000 | 70826.43 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 49628.23 | 0.00 | 71079.94 | 71079.94 | 2.53517453 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.30 | 21.27 | 0.00800000 | 61097.3 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7029.625 | 7029.625 | 0.233848 | 0.00006150 | 178.083 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 0.3598 | 0.366996 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7029.62 | 7029.62 | 1.0000 | 0.27757514 | 0.233848 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06149195 | 60.00 | 32.22 | 27.78 | 0.000 | 7029.62 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.86 | 0.00738636 | 21.00 | 0.00738636 | 47.1182 | 4711.53 | 0.00 | 7051.39 | 7051.39 | 0.27757514 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.71 | 20.50 | 0.00800000 | 58463.4 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5597.428 | 5597.428 | 0.210808 | 0.00004897 | 135.593 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 0.2865 | 0.292225 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5597.43 | 5597.43 | 1.0000 | 0.25022734 | 0.210808 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04896374 | 60.00 | 32.22 | 27.78 | 0.000 | 5597.43 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.86 | 0.00747443 | 21.00 | 0.00747443 | 47.6732 | 3507.38 | 0.00 | 5615.51 | 5615.51 | 0.25022734 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.81 | 19.60 | 0.00800000 | 55501.5 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9425.320 | 9425.320 | 0.297069 | 0.00008246 | 244.145 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 0.4824 | 0.492069 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9425.32 | 9425.32 | 1.0000 | 0.35261829 | 0.297069 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.08244840 | 60.00 | 32.22 | 27.78 | 0.000 | 9425.32 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00760430 | 21.00 | 0.00760430 | 48.4911 | 6479.29 | 0.00 | 9454.21 | 9454.21 | 0.35261829 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.09 | 20.91 | 0.00800000 | 59871.3 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4456.390 | 4456.390 | 0.258635 | 0.00003899 | 96.888 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 0.2281 | 0.232655 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4456.39 | 4456.39 | 1.0000 | 0.30699726 | 0.258635 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.03898247 | 60.00 | 32.22 | 27.78 | 0.000 | 4456.39 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.82 | 0.00688403 | 21.00 | 0.00688403 | 43.9488 | 1894.94 | 0.00 | 4471.89 | 4471.89 | 0.30699726 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 27.08 | 17.05 | 0.00800000 | 47626.4 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 163569.150 | 163569.150 | 4.945412 | 0.00143097 | 4315.367 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 8.3710 | 8.539471 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 163569.15 | 163569.15 | 1.0000 | 5.87015872 | 4.945412 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 1.43082831 | 60.00 | 32.22 | 27.78 | 0.000 | 163569.15 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00774635 | 21.00 | 0.00774635 | 49.3859 | 114513.06 | 0.00 | 164117.44 | 164117.44 | 5.87015872 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61017.8 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 108845.879 | 108845.879 | 3.291167 | 0.00095223 | 2871.517 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 5.5704 | 5.682528 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 108845.88 | 108845.88 | 1.0000 | 3.90658500 | 3.291167 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.95213409 | 60.00 | 32.22 | 27.78 | 0.000 | 108845.88 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00775622 | 21.00 | 0.00775622 | 49.4480 | 76198.43 | 0.00 | 109209.93 | 109209.93 | 3.90658500 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61015.2 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 162175.179 | 162175.179 | 4.903155 | 0.00141878 | 4278.635 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 8.2997 | 8.466696 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 162175.18 | 162175.18 | 1.0000 | 5.82000029 | 4.903155 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 1.41863449 | 60.00 | 32.22 | 27.78 | 0.000 | 162175.18 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00774132 | 21.00 | 0.00774132 | 49.3543 | 113538.77 | 0.00 | 162719.12 | 162719.12 | 5.82000029 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61018.4 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 98248.282 | 98248.282 | 2.969977 | 0.00085952 | 2592.237 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 5.0281 | 5.129258 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 98248.28 | 98248.28 | 1.0000 | 3.52533562 | 2.969977 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.85943115 | 60.00 | 32.22 | 27.78 | 0.000 | 98248.28 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00769424 | 21.00 | 0.00769424 | 49.0581 | 68790.82 | 0.00 | 98579.05 | 98579.05 | 3.52533562 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61022.9 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22189.651 | 22189.651 | 0.671358 | 0.00019412 | 585.232 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 1.1356 | 1.158457 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 22189.65 | 22189.65 | 1.0000 | 0.79689589 | 0.671358 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.19410494 | 60.00 | 32.22 | 27.78 | 0.000 | 22189.65 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00782795 | 21.00 | 0.00782795 | 49.8992 | 15528.98 | 0.00 | 22262.69 | 22262.69 | 0.79689589 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60996.6 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14641.248 | 14641.248 | 0.443000 | 0.00012809 | 386.141 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 0.7493 | 0.764377 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14641.25 | 14641.25 | 1.0000 | 0.52583648 | 0.443000 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.12807496 | 60.00 | 32.22 | 27.78 | 0.000 | 14641.25 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00782763 | 21.00 | 0.00782763 | 49.8972 | 10246.17 | 0.00 | 14689.38 | 14689.38 | 0.52583648 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60995.1 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22026.186 | 22026.186 | 0.666402 | 0.00019269 | 580.925 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 1.1272 | 1.149923 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 22026.19 | 22026.19 | 1.0000 | 0.79101323 | 0.666402 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.19267503 | 60.00 | 32.22 | 27.78 | 0.000 | 22026.19 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00782621 | 21.00 | 0.00782621 | 49.8882 | 15414.71 | 0.00 | 22098.71 | 22098.71 | 0.79101323 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60997.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13854.169 | 13854.169 | 0.419142 | 0.00012120 | 365.400 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 0.7090 | 0.723286 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13854.17 | 13854.17 | 1.0000 | 0.49751792 | 0.419142 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.12118995 | 60.00 | 32.22 | 27.78 | 0.000 | 13854.17 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781231 | 21.00 | 0.00781231 | 49.8008 | 9695.92 | 0.00 | 13899.83 | 13899.83 | 0.49751792 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60998.2 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 161229.466 | -999.000 | 8.511487 | 0.00685907 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3150 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.511487 | 10.10305643 | 4197.9300 | 999.8980 | 81.63731157 | 12.27 | 6.67 | 5.60 | 1919163.23 | 8.4010 | 8.401029 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 161229.47 | 151608.36 | 1.0000 | 10.10305643 | 8.511487 | 25.65 | 17.12 | 0.00886253 | 48358.0 | 10.92 | 10.92 | 0.00850000 | 32399.5 | 6.85837451 | 6.67 | 12.27 | 5.60 | 19437.919 | 141791.55 | 29.40 | 0.00882150 | 18.34 | 2.53819000 | 29.8208 | 24.00 | 0.00888055 | 24.00 | 0.00888055 | 47.0979 | 112871.12 | 0.00 | 163024.95 | 142927.20 | 10.10305643 | 25.65 | 17.27 | 0.00886253 | 48358.0 | 11.79 | 11.25 | 0.00807404 | 32221.8 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 51547.456 | 51547.456 | 2.553446 | 0.00045096 | 844.442 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.511487 | 10.10305643 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 2.6381 | 2.691143 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 51547.46 | 51547.46 | 1.0000 | 3.03091693 | 2.553446 | -4.12 | -4.14 | 0.00270165 | 2591.0 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.45091363 | 60.00 | 32.22 | 27.78 | 0.000 | 51547.46 | -4.20 | 0.00269032 | -4.20 | 2.53819000 | 99.4025 | 8.36 | 0.00458660 | 21.58 | 0.00532073 | 32.8576 | 16593.14 | 0.00 | 47538.60 | 47538.60 | 3.03091693 | 2.80 | 0.09 | 0.00270165 | 9584.3 | 18.33 | 8.29 | 0.00270165 | 25268.8 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1506394.281 | -999.000 | 78.247410 | 0.06408549 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3644 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 78.247410 | 92.87895467 | 4197.9300 | 999.8980 | 81.63731157 | 12.27 | 6.67 | 5.60 | 1919163.23 | 78.4922 | 78.492244 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 1506394.28 | 1411493.94 | 1.0000 | 92.87895467 | 78.247410 | 25.84 | 17.21 | 0.00888912 | 48618.5 | 10.92 | 10.92 | 0.00850000 | 32399.6 | 64.07895766 | 6.67 | 12.27 | 5.60 | 178695.787 | 1327698.49 | 29.40 | 0.00882150 | 18.34 | 25.38195000 | 32.4381 | 24.00 | 0.00892396 | 24.00 | 0.00892396 | 47.3249 | 1012725.19 | 0.00 | 1523028.65 | 1332182.84 | 92.87895467 | 25.84 | 17.36 | 0.00888912 | 48618.5 | 11.79 | 11.25 | 0.00807466 | 32220.5 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 475984.098 | 475984.098 | 23.474223 | 0.00416412 | 7794.222 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 78.247410 | 92.87895467 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 24.3595 | 24.849749 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 475984.10 | 475984.10 | 1.0000 | 27.86368640 | 23.474223 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 4.16369175 | 60.00 | 32.22 | 27.78 | 0.000 | 475984.10 | -4.20 | 0.00269032 | -4.20 | 25.38195000 | 108.1269 | 20.31 | 0.00782880 | 21.00 | 0.00779069 | 49.6638 | 491719.43 | 0.00 | 438583.70 | 438583.70 | 27.86368640 | 2.80 | 0.07 | 0.00269032 | 9555.9 | 18.39 | 8.31 | 0.00269032 | 25296.2 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 161122.545 | -999.000 | 8.536182 | 0.00685453 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3044 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.536182 | 10.13236918 | 4197.9300 | 999.8980 | 81.63731157 | 12.27 | 6.67 | 5.60 | 1919163.23 | 8.3955 | 8.395458 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 161122.55 | 151624.95 | 1.0000 | 10.13236918 | 8.536182 | 25.61 | 17.10 | 0.00885682 | 48301.2 | 10.92 | 10.92 | 0.00850000 | 32399.5 | 6.85382631 | 6.67 | 12.27 | 5.60 | 19494.316 | 141628.23 | 29.40 | 0.00882150 | 18.34 | 2.53819000 | 29.7345 | 24.00 | 0.00887177 | 24.00 | 0.00887177 | 47.0520 | 115771.51 | 0.00 | 162920.19 | 142907.00 | 10.13236918 | 25.61 | 17.25 | 0.00885682 | 48301.2 | 11.80 | 11.25 | 0.00807391 | 32222.1 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 51244.922 | 51244.922 | 2.560855 | 0.00044831 | 840.179 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.536182 | 10.13236918 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 2.6226 | 2.675349 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 51244.92 | 51244.92 | 1.0000 | 3.03971075 | 2.560855 | -3.98 | -3.99 | 0.00273612 | 2826.4 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.44826720 | 60.00 | 32.22 | 27.78 | 0.000 | 51244.92 | -4.20 | 0.00269032 | -4.20 | 2.53819000 | 99.1150 | 21.00 | 0.00786558 | 21.00 | 0.00786558 | 50.1350 | 58394.36 | 0.00 | 47341.16 | 47341.16 | 3.03971075 | 2.80 | 0.14 | 0.00273612 | 9670.7 | 18.22 | 8.28 | 0.00273612 | 25244.9 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 90416.936 | -999.000 | 4.910076 | 0.00384655 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5763 | 1004.8586 | 1.1870 | CAV_BAS FAN | Fan:ConstantVolume | 4.910076 | 5.82821553 | 4197.9300 | 999.8980 | 81.63731157 | 12.27 | 6.67 | 5.60 | 1919163.23 | 4.7113 | 4.711269 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 90416.94 | 82955.69 | 1.0000 | 5.82821553 | 4.910076 | 25.35 | 17.13 | 0.00900309 | 48408.6 | 11.40 | 11.39 | 0.00850000 | 32895.0 | 3.84615309 | 6.67 | 12.27 | 5.60 | 8325.793 | 82091.14 | 28.88 | 0.00882066 | 18.17 | 1.20019084 | 24.4434 | 24.00 | 0.00907261 | 24.00 | 0.00907261 | 48.1022 | 59010.53 | 0.00 | 91445.30 | 79134.57 | 5.82821553 | 25.35 | 17.28 | 0.00900309 | 48408.6 | 12.05 | 11.45 | 0.00816600 | 32718.5 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 240273.753 | 240273.753 | 4.910076 | 0.00210202 | 5345.366 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | CAV_BAS FAN | Fan:ConstantVolume | 4.910076 | 5.82821553 | 4197.9300 | 999.8980 | 16.75546800 | 54.44 | 82.22 | 27.78 | 1953997.47 | 12.2965 | 12.543996 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 240273.75 | 240273.75 | 1.0000 | 5.82821553 | 4.910076 | -1.03 | -2.32 | 0.00269032 | 5691.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 2.10180518 | 60.00 | 32.22 | 27.78 | 0.000 | 240273.75 | -4.20 | 0.00269032 | -4.20 | 1.20019084 | 24.4434 | 0.00 | 0.00269032 | 24.67 | 0.00269032 | 13.8378 | 0.00 | 0.00 | 201038.70 | 201038.70 | 5.82821553 | 12.80 | 5.58 | 0.00269032 | 19654.3 | 46.96 | 19.31 | 0.00269032 | 54148.3 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9495.760 | 6878.087 | 0.490998 | 0.00023255 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8140 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 8800.09 | 8678.02 | 0.9267 | -999.0 | -999.0 | 27.92 | 17.67 | 0.00859303 | 49993.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8800.09 | 25.86 | 0.00881585 | 17.16 | 0.01563279 | -999.0000 | 27.00 | 0.00858570 | 27.00 | 0.00858570 | 38.1215 | 8445.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 90801.163 | 65752.207 | 4.692779 | 0.00222371 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8217 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 84155.44 | 82936.40 | 0.9268 | -999.0 | -999.0 | 27.92 | 17.67 | 0.00859719 | 50002.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84155.44 | 25.86 | 0.00881585 | 17.16 | 0.15632792 | -999.0000 | 27.00 | 0.00858965 | 27.00 | 0.00858965 | 38.1390 | 80721.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9225.775 | 6681.315 | 0.476884 | 0.00022594 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8191 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 8550.32 | 8428.26 | 0.9268 | -999.0 | -999.0 | 27.92 | 17.67 | 0.00859577 | 49999.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8550.32 | 25.86 | 0.00881585 | 17.16 | 0.01563279 | -999.0000 | 27.00 | 0.00858831 | 27.00 | 0.00858831 | 38.1330 | 8202.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9495.760 | 9495.760 | 0.490998 | 0.00023255 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9495.76 | 9495.76 | 1.0000 | 0.58280969 | 0.490998 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9495.76 | -4.20 | 0.00269032 | -4.20 | 0.01563279 | 3.1839 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 90801.163 | 90801.163 | 4.692779 | 0.00222371 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 90801.16 | 90801.16 | 1.0000 | 5.57028484 | 4.692779 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 90801.16 | -4.20 | 0.00269032 | -4.20 | 0.15632792 | 3.3312 | 0.00 | 0.00670051 | 24.77 | 0.00670051 | 34.0575 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9225.775 | 9225.775 | 0.476884 | 0.00022594 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9225.78 | 9225.78 | 1.0000 | 0.56605672 | 0.476884 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9225.78 | -4.20 | 0.00269032 | -4.20 | 0.01563279 | 3.2781 | 0.00 | 0.00301695 | 23.62 | 0.00301695 | 16.5233 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 824.159 | 824.159 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.490998 | 0.58280969 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 824.16 | 824.16 | 1.0000 | 0.58280969 | 0.490998 | -0.13 | -0.13 | 0.00831503 | 20658.9 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 824.16 | -4.20 | 0.00269032 | -4.20 | 0.01563279 | 3.1839 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8241.592 | 8241.592 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.692779 | 5.57028484 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 8241.59 | 8241.59 | 1.0000 | 5.57028484 | 4.692779 | -0.14 | -0.14 | 0.00656692 | 16281.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8241.59 | -4.20 | 0.00269032 | -4.20 | 0.15632792 | 3.3312 | 0.00 | 0.00670051 | 24.77 | 0.00670051 | 34.0575 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 824.159 | 824.159 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.476884 | 0.56605672 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 824.16 | 824.16 | 1.0000 | 0.56605672 | 0.476884 | -0.14 | -1.32 | 0.00300625 | 7379.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 824.16 | -4.20 | 0.00269032 | -4.20 | 0.01563279 | 3.2781 | 0.00 | 0.00301695 | 23.62 | 0.00301695 | 16.5233 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 8.51 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 78.25 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 8.54 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.91 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | BASEMENT_DCV | 0.002360 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2491.00 | 285.17 | 0.00 |
CORE_BOTTOM | 2280.67 | 640.17 | 13.00 |
CORE_MID | 1115.50 | 3003.50 | 14.67 |
CORE_TOP | 1381.67 | 4024.67 | 514.67 |
PERIMETER_BOT_ZN_3 | 1279.67 | 3147.50 | 16.17 |
PERIMETER_BOT_ZN_2 | 1488.00 | 3397.50 | 59.33 |
PERIMETER_BOT_ZN_1 | 1860.50 | 2982.00 | 97.83 |
PERIMETER_BOT_ZN_4 | 2891.50 | 1537.67 | 122.50 |
PERIMETER_MID_ZN_3 | 1594.17 | 4320.67 | 913.00 |
PERIMETER_MID_ZN_2 | 1755.17 | 3500.67 | 843.83 |
PERIMETER_MID_ZN_1 | 2014.00 | 3545.33 | 582.67 |
PERIMETER_MID_ZN_4 | 2006.83 | 3850.67 | 639.50 |
PERIMETER_TOP_ZN_3 | 2384.00 | 4679.50 | 1764.67 |
PERIMETER_TOP_ZN_2 | 2723.00 | 4227.17 | 1632.50 |
PERIMETER_TOP_ZN_1 | 2501.33 | 4009.67 | 1274.17 |
PERIMETER_TOP_ZN_4 | 2501.17 | 4241.83 | 1343.83 |
DATACENTER_BOT_ZN_6 | 5943.00 | 448.17 | 448.17 |
DATACENTER_MID_ZN_6 | 5829.83 | 62.00 | 47.67 |
DATACENTER_TOP_ZN_6 | 5424.17 | 256.33 | 105.83 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 70.67 | 0.00 | 4.17 |
CORE_BOTTOM | 0.00 | 0.50 | 0.00 | 0.00 |
CORE_MID | 0.50 | 0.00 | 0.17 | 0.00 |
CORE_TOP | 6.83 | 0.00 | 1.17 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 9.33 | 0.00 | 9.33 |
PERIMETER_BOT_ZN_1 | 0.00 | 13.67 | 0.00 | 13.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 67.00 | 0.00 | 26.00 |
PERIMETER_MID_ZN_3 | 3.17 | 0.00 | 0.67 | 0.00 |
PERIMETER_MID_ZN_2 | 1.67 | 9.00 | 0.00 | 9.00 |
PERIMETER_MID_ZN_1 | 1.00 | 12.33 | 0.00 | 12.17 |
PERIMETER_MID_ZN_4 | 0.83 | 17.50 | 0.00 | 8.83 |
PERIMETER_TOP_ZN_3 | 64.50 | 0.00 | 20.83 | 0.00 |
PERIMETER_TOP_ZN_2 | 31.00 | 8.50 | 1.83 | 8.50 |
PERIMETER_TOP_ZN_1 | 21.00 | 10.50 | 0.67 | 10.17 |
PERIMETER_TOP_ZN_4 | 14.17 | 17.00 | 0.00 | 8.17 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 66.50 | 194.50 | 20.83 | 77.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.19 | 149.60 | 6779.02 | 1.250 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.95 | 134.35 | 6849.35 | 0.959 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.95 | 134.35 | 6849.35 | 0.718 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.95 | 134.35 | 6849.35 | 0.680 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.90 | 16.87 | 860.00 | 0.862 | 0.010 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.45 | 10.87 | 554.22 | 1.226 | 0.011 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.90 | 16.87 | 860.02 | 1.312 | 0.010 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.45 | 10.87 | 554.22 | 1.838 | 0.011 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.90 | 16.87 | 860.00 | 0.688 | 0.024 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.88 | 10.87 | 554.22 | 1.062 | 0.026 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.90 | 16.87 | 860.02 | 1.203 | 0.024 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.45 | 10.87 | 554.22 | 1.220 | 0.025 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.90 | 16.87 | 860.00 | 0.678 | 0.029 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.45 | 10.87 | 554.22 | 1.123 | 0.031 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.90 | 16.87 | 860.02 | 1.174 | 0.030 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.45 | 10.87 | 554.22 | 1.227 | 0.031 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.25 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.19 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.95 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.95 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.95 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.90 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.90 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.90 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.88 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.90 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.90 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.90 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.25 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.19 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 0.847 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.95 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.95 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.95 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.90 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.90 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.90 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.88 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.90 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.90 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.90 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.011 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.110 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.011 |
DATACENTER_BASEMENT_ZN_6 | 17.25 | 42.18 | 1911.37 | 783.68 | 0.239 | ||
Total Facility | 1014.08 | 2493.19 | 126016.35 | 46320.38 | 1.3878 | 157.549 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 51204436.35 | 0.00 | 51204436.35 | 0.00 | 51204436.35 | 29876159.83 | 3865.45 | 378.73 | 4515.82 | 343.04 |
CORE_BOTTOM | 40792115.09 | 0.00 | 40792115.09 | 0.00 | 40792115.09 | 33990283.35 | 4144.08 | 50.02 | 4565.90 | 444.85 |
CORE_MID | 0.29E+09 | 0.00 | 0.29E+09 | 0.00 | 0.29E+09 | 0.34E+09 | 5531.37 | 56.94 | 3171.69 | 119.30 |
CORE_TOP | 27707410.52 | 0.00 | 27707410.52 | 0.00 | 27707410.52 | 33990283.35 | 5859.23 | 51.02 | 2849.74 | 212.45 |
PERIMETER_BOT_ZN_3 | 4627748.95 | 0.00 | 4627748.95 | 105032.92 | 4732781.87 | 4267819.30 | 4800.30 | 70.89 | 3888.81 | 444.85 |
PERIMETER_BOT_ZN_2 | 4241323.69 | 0.00 | 4241323.69 | 70021.90 | 4311345.58 | 2750345.05 | 3456.74 | 5.91 | 5297.35 | 444.85 |
PERIMETER_BOT_ZN_1 | 6965615.07 | 0.00 | 6965615.07 | 105032.92 | 7070647.99 | 4267912.63 | 3505.48 | 25.99 | 5228.53 | 444.85 |
PERIMETER_BOT_ZN_4 | 6312444.08 | 0.00 | 6312444.08 | 70021.90 | 6382465.98 | 2750345.05 | 3426.13 | 1.07 | 5332.80 | 444.85 |
PERIMETER_MID_ZN_3 | 35218221.44 | 0.00 | 35218221.44 | 246330.46 | 35464551.90 | 42678193.03 | 5552.50 | 72.50 | 3135.00 | 119.30 |
PERIMETER_MID_ZN_2 | 38036923.63 | 0.00 | 38036923.63 | 164220.20 | 38201143.83 | 27503450.52 | 3961.88 | 5.21 | 4792.91 | 1028.30 |
PERIMETER_MID_ZN_1 | 61226584.40 | 0.00 | 61226584.40 | 246330.46 | 61472914.86 | 42679126.28 | 3996.77 | 3.62 | 4759.62 | 119.30 |
PERIMETER_MID_ZN_4 | 40272064.51 | 0.00 | 40272064.51 | 164220.20 | 40436284.71 | 27503450.52 | 3955.55 | 4.87 | 4799.58 | 119.30 |
PERIMETER_TOP_ZN_3 | 3477025.24 | 0.00 | 3477025.24 | 305844.10 | 3782869.33 | 4267819.30 | 5717.23 | 68.30 | 2974.47 | 212.45 |
PERIMETER_TOP_ZN_2 | 3697126.16 | 0.00 | 3697126.16 | 203895.93 | 3901022.09 | 2750345.05 | 4058.21 | 3.28 | 4698.51 | 212.45 |
PERIMETER_TOP_ZN_1 | 5983946.80 | 0.00 | 5983946.80 | 305844.10 | 6289790.90 | 4267912.63 | 4068.47 | 3.03 | 4688.50 | 212.45 |
PERIMETER_TOP_ZN_4 | 4057698.04 | 0.00 | 4057698.04 | 203895.93 | 4261593.97 | 2750345.05 | 4043.95 | 5.85 | 4710.20 | 212.45 |
DATACENTER_BOT_ZN_6 | 244303.03 | 0.00 | 244303.03 | 0.00 | 244303.03 | 389144.62 | 4419.00 | 504.00 | 3837.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2443030.26 | 0.00 | 2443030.26 | 0.00 | 2443030.26 | 3891446.16 | 4419.00 | 504.00 | 3837.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244303.03 | 0.00 | 244303.03 | 0.00 | 244303.03 | 389144.62 | 4419.00 | 504.00 | 3837.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8423799.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 0.49E+10 | 0.00 | 0.49E+10 | 9580602.88 | 0.49E+10 | 0.50E+10 | 8760.00 | 1107.75 | 5508.45 | 1612.18 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.3013 | 0.0000 | 2.3013 | 0.0000 | 2.3013 | 0.9949 | 1296.10 | 376.15 | 4270.75 |
CORE_BOTTOM | 1.7841 | 0.0000 | 1.7841 | 0.0000 | 1.7841 | 1.0778 | 1719.84 | 45.95 | 4177.21 |
CORE_MID | 13.3739 | 0.0000 | 13.3739 | 0.0000 | 13.3739 | 10.7782 | 2797.34 | 56.94 | 3088.72 |
CORE_TOP | 1.2685 | 0.0000 | 1.2685 | 0.0000 | 1.2685 | 1.0778 | 3096.83 | 50.82 | 2795.34 |
PERIMETER_BOT_ZN_3 | 0.2016 | 0.0000 | 0.2016 | 0.0024 | 0.2040 | 0.1353 | 2372.73 | 66.20 | 3504.07 |
PERIMETER_BOT_ZN_2 | 0.1850 | 0.0000 | 0.1850 | 0.0016 | 0.1866 | 0.0872 | 1080.57 | 5.13 | 4857.30 |
PERIMETER_BOT_ZN_1 | 0.3069 | 0.0000 | 0.3069 | 0.0024 | 0.3093 | 0.1353 | 1121.12 | 23.40 | 4798.48 |
PERIMETER_BOT_ZN_4 | 0.2768 | 0.0000 | 0.2768 | 0.0016 | 0.2784 | 0.0872 | 1053.99 | 1.05 | 4887.97 |
PERIMETER_MID_ZN_3 | 1.6116 | 0.0000 | 1.6116 | 0.0056 | 1.6172 | 1.3533 | 2818.58 | 72.46 | 3051.96 |
PERIMETER_MID_ZN_2 | 1.6052 | 0.0000 | 1.6052 | 0.0040 | 1.6092 | 0.8721 | 1233.60 | 4.16 | 3796.24 |
PERIMETER_MID_ZN_1 | 2.8162 | 0.0000 | 2.8162 | 0.0056 | 2.8218 | 1.3533 | 1265.20 | 2.99 | 4674.81 |
PERIMETER_MID_ZN_4 | 1.8419 | 0.0000 | 1.8419 | 0.0037 | 1.8456 | 0.8721 | 1228.14 | 3.57 | 4711.30 |
PERIMETER_TOP_ZN_3 | 0.1591 | 0.0000 | 0.1591 | 0.0069 | 0.1660 | 0.1353 | 2956.60 | 68.03 | 2918.37 |
PERIMETER_TOP_ZN_2 | 0.1696 | 0.0000 | 0.1696 | 0.0046 | 0.1743 | 0.0872 | 1310.03 | 2.32 | 4630.65 |
PERIMETER_TOP_ZN_1 | 0.2750 | 0.0000 | 0.2750 | 0.0069 | 0.2820 | 0.1353 | 1317.47 | 2.23 | 4623.30 |
PERIMETER_TOP_ZN_4 | 0.1854 | 0.0000 | 0.1854 | 0.0046 | 0.1900 | 0.0872 | 1298.67 | 4.20 | 4640.13 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0130 | 1602.00 | 504.00 | 3837.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1296 | 1602.00 | 504.00 | 3837.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0130 | 1602.00 | 504.00 | 3837.00 |
DATACENTER_BASEMENT_ZN_6 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.2805 | 5943.00 | 0.00 | 0.00 |
Total Facility | 220.7663 | 0.0000 | 220.7663 | 0.2201 | 220.9864 | 157.9346 | 5943.00 | 1091.48 | 4938.66 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 88678074.75 | 0.00 | 88678074.75 | 48026705.38 | 3434.86 | 1.88 | 5323.26 | 444.85 |
VAV_MID WITH REHEAT | 0.66E+09 | 0.00 | 0.66E+09 | 0.48E+09 | 3955.08 | 4.30 | 4800.62 | 119.30 |
VAV_TOP WITH REHEAT | 63294424.67 | 0.00 | 63294424.67 | 48026705.38 | 4052.99 | 4.16 | 4702.85 | 212.45 |
CAV_BAS | 72144343.11 | 0.00 | 72144343.11 | 29876159.83 | 3828.93 | 1.67 | 4929.40 | 343.04 |
AIRLOOP DATACENTER BOT | 344210.05 | 0.00 | 344210.05 | 389144.62 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3442100.45 | 0.00 | 3442100.45 | 3891446.16 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 344210.05 | 0.00 | 344210.05 | 389144.62 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.8809 | 0.0000 | 3.8809 | 1.5229 | 1061.78 | 1.43 | 4879.79 |
VAV_MID WITH REHEAT | 30.1352 | 0.0000 | 30.1352 | 15.2292 | 1227.64 | 3.16 | 4712.20 |
VAV_TOP WITH REHEAT | 2.8990 | 0.0000 | 2.8990 | 1.5229 | 1304.26 | 2.72 | 4636.03 |
CAV_BAS | 3.2424 | 0.0000 | 3.2424 | 0.9949 | 1290.08 | 0.11 | 4652.82 |
AIRLOOP DATACENTER BOT | 0.0161 | 0.0000 | 0.0161 | 0.0130 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1609 | 0.0000 | 0.1609 | 0.1296 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0161 | 0.0000 | 0.0161 | 0.0130 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.03 | 4574.37 | 0.00 | 0.00 | 0.00 | 763.00 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.03 | 3888.32 | 0.00 | 0.00 | 0.00 | 993.56 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 3338.77 | 0.00 | 0.00 | 0.00 | 1646.10 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 0.00 | 4627.89 | 0.00 | 0.00 | 0.00 | 375.07 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 5.1508 | 0.0000 | 0.0000 | 0.0000 | 2.3569 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 41.4398 | 0.0000 | 0.0000 | 0.0000 | 23.0646 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.3135 | 0.0000 | 0.0000 | 0.0000 | 2.2751 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 0.0000 | 4.3788 | 0.0000 | 0.0000 | 0.0000 | 1.3628 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2203 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 7 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1352 |
Defaulted Fields | 1168 |
Fields with Defaults | 3820 |
Autosized Fields | 313 |
Autosizable Fields | 391 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 22185.30 | 282902.00 | 16-JAN-04:40 | 1608169.36 | 29-AUG-15:10 |
Electricity:Building | 16711.58 | 216770.18 | 07-MAY-17:10 | 977223.71 | 01-DEC-16:20 |
Electricity:Zone:BASEMENT | 559.97 | 14115.26 | 01-JAN-00:10 | 25295.37 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16711.58 | 216770.18 | 07-MAY-17:10 | 977223.71 | 01-DEC-16:20 |
InteriorLights:Electricity | 2035.19 | 9514.02 | 15-JAN-12:20 | 198852.03 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:BASEMENT | 135.58 | 657.72 | 01-JAN-00:10 | 11837.83 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2035.19 | 9514.02 | 15-JAN-12:20 | 198852.03 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 2035.19 | 9514.02 | 15-JAN-12:20 | 198852.03 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 135.58 | 657.72 | 01-JAN-00:10 | 11837.83 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2035.19 | 9514.02 | 15-JAN-12:20 | 198852.03 | 02-JAN-16:30 |
Electricity:Zone:CORE_BOTTOM | 411.37 | 5043.91 | 01-JAN-00:10 | 27837.83 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4113.71 | 50438.97 | 01-JAN-00:10 | 278377.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1217.58 | 5906.80 | 01-JAN-00:10 | 106312.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1217.58 | 5906.80 | 01-JAN-00:10 | 106312.04 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 411.37 | 5043.90 | 01-JAN-00:10 | 27837.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 45.65 | 594.46 | 09-APR-17:10 | 3495.41 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.28 | 35.29 | 15-JAN-12:20 | 1334.85 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 9.28 | 35.29 | 15-JAN-12:20 | 1334.85 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 29.33 | 383.09 | 07-MAY-17:10 | 2252.57 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.89 | 22.74 | 01-JAN-10:30 | 860.23 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.89 | 22.74 | 01-JAN-10:30 | 860.23 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 45.38 | 594.47 | 09-APR-17:10 | 3495.47 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.02 | 35.29 | 01-JAN-10:10 | 1334.88 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 9.02 | 35.29 | 01-JAN-10:10 | 1334.88 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 29.33 | 383.09 | 19-MAR-17:10 | 2252.56 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.89 | 22.74 | 01-JAN-13:30 | 860.23 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.89 | 22.74 | 01-JAN-13:30 | 860.23 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 456.53 | 5944.59 | 09-APR-17:10 | 34954.06 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 92.87 | 352.88 | 15-JAN-12:00 | 13348.54 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 92.87 | 352.88 | 15-JAN-12:00 | 13348.54 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 293.28 | 3830.92 | 23-APR-17:10 | 22525.72 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 58.93 | 227.41 | 01-JAN-10:20 | 8602.31 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 58.93 | 227.41 | 01-JAN-10:20 | 8602.31 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 453.90 | 5944.68 | 19-MAR-17:10 | 34954.68 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 90.24 | 352.89 | 01-JAN-10:10 | 13348.83 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 90.24 | 352.89 | 01-JAN-10:10 | 13348.83 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 293.25 | 3830.90 | 19-MAR-17:10 | 22525.63 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 58.90 | 227.41 | 01-JAN-13:30 | 8602.31 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 58.90 | 227.41 | 01-JAN-13:30 | 8602.31 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 45.65 | 594.46 | 09-APR-17:10 | 3495.41 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.29 | 35.29 | 15-JAN-12:00 | 1334.85 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 9.29 | 35.29 | 15-JAN-12:00 | 1334.85 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 29.33 | 383.09 | 23-APR-17:10 | 2252.57 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.89 | 22.74 | 01-JAN-10:20 | 860.23 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.89 | 22.74 | 01-JAN-10:20 | 860.23 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 45.39 | 594.47 | 19-MAR-17:10 | 3495.47 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.02 | 35.29 | 01-JAN-10:10 | 1334.88 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 9.02 | 35.29 | 01-JAN-10:10 | 1334.88 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 29.33 | 383.09 | 19-MAR-17:10 | 2252.56 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.89 | 22.74 | 01-JAN-13:30 | 860.23 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.89 | 22.74 | 01-JAN-13:30 | 860.23 | 02-JAN-16:30 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7533.08 | 95093.58 | 01-JAN-00:10 | 382970.28 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 38.23 | 185.45 | 01-JAN-00:10 | 3337.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 38.23 | 185.45 | 01-JAN-00:10 | 3337.76 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.14 | 1964.44 | 01-JAN-00:10 | 8079.39 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1571.44 | 19644.38 | 01-JAN-00:10 | 80793.90 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 32.64 | 158.32 | 01-JAN-00:10 | 2849.68 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 32.64 | 158.32 | 01-JAN-00:10 | 2849.68 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.14 | 1964.44 | 01-JAN-00:10 | 8079.39 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 687.39 | 725.69 | 16-JAN-06:00 | 312177.13 | 29-AUG-14:30 |
HeatRejection:Electricity | 160.78 | 31.18 | 07-JAN-08:00 | 40919.94 | 27-APR-12:40 |
General:HeatRejection:Electricity | 160.78 | 31.18 | 07-JAN-08:00 | 40919.94 | 27-APR-12:40 |
Electricity:HVAC | 1401.98 | 7644.44 | 16-JAN-06:00 | 221807.82 | 10-AUG-14:40 |
ExteriorEquipment:Electricity | 3108.28 | 43347.20 | 01-JAN-00:10 | 177606.28 | 28-DEC-08:20 |
Transformer:ExteriorEquipment:Electricity | 54.49 | 979.82 | 01-JAN-00:10 | 3387.38 | 01-DEC-16:30 |
ElectricityPurchased:Facility | 22185.30 | 282902.00 | 16-JAN-04:40 | 1608169.36 | 29-AUG-15:10 |
ElectricityPurchased:Plant | 22185.30 | 282902.00 | 16-JAN-04:40 | 1608169.36 | 29-AUG-15:10 |
Cogeneration:ElectricityPurchased | 22185.30 | 282902.00 | 16-JAN-04:40 | 1608169.36 | 29-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 22185.30 | 282902.00 | 16-JAN-04:40 | 1608169.36 | 29-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 22185.30 | 282902.00 | 16-JAN-04:40 | 1608169.36 | 29-AUG-15:10 |
ElectricityNet:Plant | 22185.30 | 282902.00 | 16-JAN-04:40 | 1608169.36 | 29-AUG-15:10 |
Cogeneration:ElectricityNet | 22185.30 | 282902.00 | 16-JAN-04:40 | 1608169.36 | 29-AUG-15:10 |
General:Cogeneration:ElectricityNet | 22185.30 | 282902.00 | 16-JAN-04:40 | 1608169.36 | 29-AUG-15:10 |
Fans:Electricity | 1011.11 | 6340.55 | 15-JUL-19:00 | 191290.47 | 10-AUG-14:40 |
General:Fans:Electricity | 1011.11 | 6340.55 | 15-JUL-19:00 | 191290.47 | 10-AUG-14:40 |
ExteriorLights:Electricity | 330.56 | 0.00 | 01-JAN-08:10 | 37611.08 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 330.56 | 0.00 | 01-JAN-08:10 | 37611.08 | 01-JAN-06:10 |
ComputerHVAC:ExteriorEquipment:Electricity | 1199.18 | 15185.30 | 01-JAN-00:10 | 60741.22 | 31-MAR-23:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 628.64 | 192.63 | 07-JAN-08:00 | 253259.76 | 29-AUG-14:30 |
General:Cooling:Electricity | 628.64 | 192.63 | 07-JAN-08:00 | 253259.76 | 29-AUG-14:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 234.36 | 677.32 | 01-JAN-00:50 | 48504.91 | 27-JUN-13:50 |
General:Pumps:Electricity | 234.36 | 677.32 | 01-JAN-00:50 | 48504.91 | 27-JUN-13:50 |
WIRED_LTG_ELECTRICITY | 57.19 | 0.00 | 01-JAN-00:10 | 5587.74 | 02-JAN-16:40 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1775.33 | 5695.87 | 23-JUL-16:10 | 1190789.99 | 02-JAN-05:10 |
NaturalGas:Plant | 1775.33 | 5695.87 | 23-JUL-16:10 | 1190789.99 | 02-JAN-05:10 |
Heating:NaturalGas | 1053.50 | 0.00 | 01-JAN-00:10 | 1185094.12 | 02-JAN-05:10 |
Boiler:Heating:NaturalGas | 1053.50 | 0.00 | 01-JAN-00:10 | 1185094.12 | 02-JAN-05:10 |
WaterSystems:NaturalGas | 721.82 | 5695.87 | 17-JAN-06:10 | 81411.54 | 13-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 721.82 | 5695.87 | 17-JAN-06:10 | 81411.54 | 13-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 3947.99 | 927.47 | 07-JAN-08:00 | 1617686.68 | 29-AUG-14:30 |
PlantLoopCoolingDemand:HVAC | 3947.99 | 927.47 | 07-JAN-08:00 | 1617686.68 | 29-AUG-14:30 |
CoolingCoils:PlantLoopCoolingDemand | 3947.99 | 927.47 | 07-JAN-08:00 | 1617686.68 | 29-AUG-14:30 |
DistrictCooling:Facility | 7177.60 | 86361.52 | 17-JAN-05:00 | 369998.69 | 14-AUG-16:00 |
DistrictCooling:HVAC | 7177.60 | 86361.52 | 17-JAN-05:00 | 369998.69 | 14-AUG-16:00 |
Cooling:DistrictCooling | 7177.60 | 86361.52 | 17-JAN-05:00 | 369998.69 | 14-AUG-16:00 |
General:Cooling:DistrictCooling | 7177.60 | 86361.52 | 17-JAN-05:00 | 369998.69 | 14-AUG-16:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 3908.53 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
Water:Plant | 3908.53 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 3908.53 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
MainsWater:Plant | 3908.53 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 1628.36 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
General:HeatRejection:Water | 1628.36 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
HeatRejection:MainsWater | 1628.36 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
General:HeatRejection:MainsWater | 1628.36 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 28570.20 | 94201.20 | 16-JAN-06:00 | 7797505.38 | 29-AUG-14:30 |
EnergyTransfer:Building | 16539.87 | 88237.66 | 14-JAN-19:40 | 1479184.49 | 10-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 587.76 | 0.00 | 01-JAN-00:10 | 69144.52 | 05-SEP-05:10 |
Heating:EnergyTransfer | 214.16 | 0.00 | 01-FEB-00:10 | 800154.33 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.13 | 0.00 | 01-JAN-00:10 | 9082.76 | 01-APR-16:10 |
General:Heating:EnergyTransfer | 214.16 | 0.00 | 01-FEB-00:10 | 800154.33 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 3.13 | 0.00 | 01-JAN-00:10 | 9082.76 | 01-APR-16:10 |
Cooling:EnergyTransfer | 16325.71 | 87106.13 | 16-JAN-06:00 | 1479184.49 | 10-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 584.63 | 0.00 | 01-JAN-00:10 | 69144.52 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer | 16325.71 | 87106.13 | 16-JAN-06:00 | 1479184.49 | 10-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 584.63 | 0.00 | 01-JAN-00:10 | 69144.52 | 05-SEP-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 544.68 | 0.00 | 01-JAN-00:10 | 46934.33 | 03-JUL-05:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 544.68 | 0.00 | 01-JAN-00:10 | 46934.33 | 03-JUL-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 544.68 | 0.00 | 01-JAN-00:10 | 46934.33 | 03-JUL-05:10 |
EnergyTransfer:Zone:CORE_MID | 3679.58 | 0.00 | 01-JAN-00:10 | 389616.45 | 03-AUG-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 2.16 | 0.00 | 01-JAN-00:10 | 281131.24 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 2.16 | 0.00 | 01-JAN-00:10 | 281131.24 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 3677.42 | 0.00 | 01-JAN-00:10 | 389616.45 | 03-AUG-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 3677.42 | 0.00 | 01-JAN-00:10 | 389616.45 | 03-AUG-05:10 |
EnergyTransfer:Zone:CORE_TOP | 324.38 | 0.00 | 01-JAN-00:10 | 60754.42 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 7.01 | 0.00 | 01-JAN-00:10 | 60754.42 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 7.01 | 0.00 | 01-JAN-00:10 | 60754.42 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 317.37 | 0.00 | 01-JAN-00:10 | 43409.10 | 10-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 317.37 | 0.00 | 01-JAN-00:10 | 43409.10 | 10-AUG-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 57.30 | 0.00 | 01-JAN-00:10 | 8336.33 | 24-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 57.30 | 0.00 | 01-JAN-00:10 | 8336.33 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 57.30 | 0.00 | 01-JAN-00:10 | 8336.33 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 50.74 | 0.00 | 01-JAN-00:10 | 11886.89 | 31-JUL-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 192.14 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 192.14 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 50.74 | 0.00 | 01-JAN-00:10 | 11886.89 | 31-JUL-08:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 50.74 | 0.00 | 01-JAN-00:10 | 11886.89 | 31-JUL-08:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 85.52 | 0.00 | 01-JAN-00:10 | 18563.38 | 04-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.04 | 0.00 | 01-JAN-00:10 | 4136.35 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.04 | 0.00 | 01-JAN-00:10 | 4136.35 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 85.48 | 0.00 | 01-JAN-00:10 | 18563.38 | 04-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 85.48 | 0.00 | 01-JAN-00:10 | 18563.38 | 04-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 81.85 | 0.00 | 01-JAN-00:10 | 15733.43 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 81.85 | 0.00 | 01-JAN-00:10 | 15733.43 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 81.85 | 0.00 | 01-JAN-00:10 | 15733.43 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 386.19 | 0.00 | 01-JAN-00:10 | 86000.87 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.99 | 0.00 | 01-JAN-00:10 | 86000.87 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.99 | 0.00 | 01-JAN-00:10 | 86000.87 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 359.20 | 0.00 | 01-JAN-00:10 | 70186.25 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 359.20 | 0.00 | 01-JAN-00:10 | 70186.25 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 405.41 | 0.00 | 01-JAN-00:10 | 120825.15 | 10-AUG-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 18.09 | 0.00 | 01-JAN-00:10 | 75061.59 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 18.09 | 0.00 | 01-JAN-00:10 | 75061.59 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 387.32 | 0.00 | 01-JAN-00:10 | 120825.15 | 10-AUG-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 387.32 | 0.00 | 01-JAN-00:10 | 120825.15 | 10-AUG-08:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 713.99 | 0.00 | 01-JAN-00:10 | 198770.49 | 04-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 16.63 | 0.00 | 01-JAN-00:10 | 111729.17 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 16.63 | 0.00 | 01-JAN-00:10 | 111729.17 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 697.36 | 0.00 | 01-JAN-00:10 | 198770.49 | 04-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 697.36 | 0.00 | 01-JAN-00:10 | 198770.49 | 04-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 450.03 | 0.00 | 01-JAN-00:10 | 132850.19 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 8.03 | 0.00 | 01-JAN-00:10 | 60296.69 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 8.03 | 0.00 | 01-JAN-00:10 | 60296.69 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 442.01 | 0.00 | 01-JAN-00:10 | 132850.19 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 442.01 | 0.00 | 01-JAN-00:10 | 132850.19 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.42 | 0.00 | 01-JAN-00:10 | 10601.61 | 26-DEC-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.85 | 0.00 | 01-JAN-00:10 | 10601.61 | 26-DEC-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.85 | 0.00 | 01-JAN-00:10 | 10601.61 | 26-DEC-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.57 | 0.00 | 01-JAN-00:10 | 8002.52 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.57 | 0.00 | 01-JAN-00:10 | 8002.52 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 42.16 | 0.00 | 01-JAN-00:10 | 12121.52 | 10-AUG-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 8.30 | 0.00 | 01-JAN-00:10 | 11252.36 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 8.30 | 0.00 | 01-JAN-00:10 | 11252.36 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.85 | 0.00 | 01-JAN-00:10 | 12121.52 | 10-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.85 | 0.00 | 01-JAN-00:10 | 12121.52 | 10-AUG-09:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 70.21 | 0.00 | 01-JAN-00:10 | 19657.67 | 04-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 9.33 | 0.00 | 01-JAN-00:10 | 16754.96 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 9.33 | 0.00 | 01-JAN-00:10 | 16754.96 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 60.87 | 0.00 | 01-JAN-00:10 | 19657.67 | 04-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 60.87 | 0.00 | 01-JAN-00:10 | 19657.67 | 04-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 44.29 | 0.00 | 01-JAN-00:10 | 13959.45 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.93 | 0.00 | 01-JAN-00:10 | 10278.21 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.93 | 0.00 | 01-JAN-00:10 | 10278.21 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 39.36 | 0.00 | 01-JAN-00:10 | 13959.45 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 39.36 | 0.00 | 01-JAN-00:10 | 13959.45 | 10-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 44.20 | 0.00 | 01-JAN-00:10 | 7510.71 | 14-AUG-15:00 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.38 | 0.00 | 01-JAN-00:10 | 3959.35 | 03-DEC-11:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.38 | 0.00 | 01-JAN-00:10 | 3959.35 | 03-DEC-11:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 42.83 | 0.00 | 01-JAN-00:10 | 7510.71 | 14-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 42.83 | 0.00 | 01-JAN-00:10 | 7510.71 | 14-AUG-15:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 300.25 | 0.00 | 01-JAN-00:10 | 96178.52 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 61.15 | 0.00 | 01-JAN-00:10 | 96178.52 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 61.15 | 0.00 | 01-JAN-00:10 | 96178.52 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 239.09 | 0.00 | 01-JAN-00:10 | 55937.58 | 10-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 239.09 | 0.00 | 01-JAN-00:10 | 55937.58 | 10-AUG-15:10 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 63.27 | 0.00 | 01-JAN-00:10 | 17614.38 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 29.61 | 0.00 | 01-JAN-00:10 | 17614.38 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 29.61 | 0.00 | 01-JAN-00:10 | 17614.38 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 33.67 | 0.00 | 01-JAN-00:10 | 17035.78 | 10-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 33.67 | 0.00 | 01-JAN-00:10 | 17035.78 | 10-AUG-14:40 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.80 | 682.82 | 21-JAN-18:20 | 8386.69 | 06-AUG-18:30 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.80 | 682.82 | 21-JAN-18:20 | 8386.69 | 06-AUG-18:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.80 | 682.82 | 21-JAN-18:20 | 8386.69 | 06-AUG-18:30 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1168.76 | 4.24 | 17-JAN-10:00 | 77998.21 | 06-AUG-18:30 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 2.73 | 0.00 | 03-JAN-10:00 | 5301.95 | 16-JAN-20:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 2.73 | 0.00 | 03-JAN-10:00 | 5301.95 | 16-JAN-20:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1166.03 | 0.00 | 01-JAN-00:10 | 77998.21 | 06-AUG-18:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1166.03 | 0.00 | 01-JAN-00:10 | 77998.21 | 06-AUG-18:30 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 106.08 | 0.11 | 06-JAN-11:20 | 7928.32 | 06-AUG-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.80 | 0.00 | 03-JAN-11:00 | 581.58 | 08-JAN-17:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.80 | 0.00 | 03-JAN-11:00 | 581.58 | 08-JAN-17:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.28 | 0.00 | 01-JAN-00:10 | 7928.32 | 06-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.28 | 0.00 | 01-JAN-00:10 | 7928.32 | 06-AUG-18:20 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7152.98 | 86361.52 | 17-JAN-05:00 | 367399.68 | 14-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7152.98 | 86361.52 | 17-JAN-05:00 | 367399.68 | 14-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7152.98 | 86361.52 | 17-JAN-05:00 | 367399.68 | 14-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 1194.50 | 0.00 | 01-JAN-00:10 | 958830.02 | 02-JAN-06:20 |
PlantLoopHeatingDemand:Plant | 423.42 | 0.00 | 01-JAN-00:10 | 50364.90 | 10-FEB-12:50 |
WaterSystems:PlantLoopHeatingDemand | 423.42 | 0.00 | 01-JAN-00:10 | 50364.90 | 10-FEB-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 423.42 | 0.00 | 01-JAN-00:10 | 50364.90 | 10-FEB-12:50 |
EnergyTransfer:HVAC | 4382.68 | 1283.36 | 16-JAN-06:00 | 1590287.07 | 29-AUG-14:30 |
HeatingCoils:EnergyTransfer | 771.08 | 0.00 | 01-JAN-00:10 | 952714.48 | 02-JAN-06:20 |
PlantLoopHeatingDemand:HVAC | 771.08 | 0.00 | 01-JAN-00:10 | 952714.48 | 02-JAN-06:20 |
HeatingCoils:PlantLoopHeatingDemand | 771.08 | 0.00 | 01-JAN-00:10 | 952714.48 | 02-JAN-06:20 |
CoolingCoils:EnergyTransfer | 3611.60 | 734.85 | 07-JAN-08:00 | 1590287.07 | 29-AUG-14:30 |
DistrictHeating:Facility | 0.00 | 0.00 | 01-JAN-00:40 | 13.46 | 31-MAY-23:40 |
DistrictHeating:HVAC | 0.00 | 0.00 | 01-JAN-00:40 | 13.46 | 31-MAY-23:40 |
Heating:DistrictHeating | 0.00 | 0.00 | 01-JAN-00:40 | 13.46 | 31-MAY-23:40 |
General:Heating:DistrictHeating | 0.00 | 0.00 | 01-JAN-00:40 | 13.46 | 31-MAY-23:40 |
EnergyTransfer:Plant | 7647.65 | -832.00 | 25-FEB-05:20 | 4759340.20 | 29-AUG-14:30 |
LoopToLoop:EnergyTransfer | 2149.72 | -5196.78 | 24-FEB-06:10 | 1498381.79 | 29-AUG-14:30 |
WaterSystems:EnergyTransfer | 423.42 | 0.00 | 01-JAN-00:10 | 50364.90 | 10-FEB-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 423.42 | 0.00 | 01-JAN-00:10 | 50364.90 | 10-FEB-12:50 |
Boilers:EnergyTransfer | 767.23 | 0.00 | 01-JAN-00:10 | 985052.61 | 02-JAN-05:10 |
Chillers:EnergyTransfer | 2007.51 | 0.00 | 01-JAN-00:10 | 1505098.90 | 29-AUG-14:30 |
HeatRejection:EnergyTransfer | 2299.77 | 0.00 | 01-JAN-00:10 | 1730959.06 | 29-AUG-14:30 |
General:HeatRejection:EnergyTransfer | 2299.77 | 0.00 | 01-JAN-00:10 | 1730959.06 | 29-AUG-14:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.132 | -584.632 | 0.000 | 0.000 | 92.666 | 135.577 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -71.140 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -544.682 | 0.000 | 0.000 | 83.468 | 121.758 | 289.614 | 0.000 | 0.000 | 0.000 | 49.843 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 2.160 | -3677.404 | 0.000 | 0.000 | 852.120 | 1217.578 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1290.580 |
CORE_TOP | 0.000 | 0.000 | 7.015 | -317.366 | 0.000 | 0.000 | 88.879 | 121.758 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -189.899 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -57.302 | 0.000 | 0.000 | 10.755 | 9.284 | 36.365 | 17.421 | 0.000 | 0.004 | 31.010 | 0.000 | -45.885 | 0.000 | -1.651 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -50.736 | 0.000 | 0.000 | 7.031 | 5.894 | 23.435 | 34.599 | 0.000 | 0.002 | 9.341 | 0.000 | -28.493 | 0.000 | -1.073 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.037 | -85.480 | 0.000 | 0.000 | 10.848 | 9.018 | 36.366 | 75.233 | 0.000 | 0.003 | 0.001 | 0.000 | -42.784 | 0.000 | -1.628 | -1.613 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -81.854 | 0.000 | 0.000 | 6.818 | 5.892 | 23.435 | 36.515 | 0.000 | 0.002 | 43.610 | 0.000 | -33.204 | 0.000 | -1.213 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 26.989 | -359.203 | 0.000 | 0.000 | 113.721 | 92.873 | 363.654 | 183.090 | 0.000 | 0.104 | 17.883 | 0.000 | -404.860 | 0.000 | -34.252 | -0.005 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 18.088 | -387.326 | 0.000 | 0.000 | 53.902 | 58.927 | 234.352 | 348.750 | 0.000 | 0.054 | 0.021 | 0.000 | -261.186 | 0.000 | -23.109 | -42.454 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 16.634 | -697.353 | 0.000 | 0.000 | 111.343 | 90.242 | 363.660 | 752.685 | 0.000 | 0.071 | 0.028 | 0.000 | -407.844 | 0.000 | -36.214 | -193.224 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 8.026 | -442.003 | 0.000 | 0.000 | 73.010 | 58.903 | 234.351 | 374.826 | 0.000 | 0.048 | 0.011 | 0.000 | -280.617 | 0.000 | -24.255 | -2.288 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 13.846 | -29.572 | 0.000 | 0.000 | 11.650 | 9.286 | 36.365 | 18.971 | 0.000 | 0.012 | 0.001 | 0.000 | -37.174 | 0.000 | -3.924 | -19.462 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 8.301 | -33.855 | 0.000 | 0.000 | 7.435 | 5.892 | 23.435 | 35.316 | 0.000 | 0.006 | 0.001 | 0.000 | -24.218 | 0.000 | -2.671 | -19.642 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 9.332 | -60.872 | 0.000 | 0.000 | 11.405 | 9.024 | 36.366 | 76.043 | 0.000 | 0.008 | 0.001 | 0.000 | -37.773 | 0.000 | -4.170 | -39.364 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 4.934 | -39.360 | 0.000 | 0.000 | 7.463 | 5.890 | 23.435 | 37.814 | 0.000 | 0.006 | 0.000 | 0.000 | -26.206 | 0.000 | -2.821 | -11.155 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -136.798 | 0.000 | 0.000 | 0.950 | 3.264 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -21.296 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 2.730 | -1166.026 | 0.000 | 0.000 | 9.504 | 32.637 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -417.651 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.800 | -105.278 | 0.000 | 0.000 | 0.953 | 3.264 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -53.619 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | -7152.982 | 0.000 | 0.000 | 0.000 | 0.000 | 20.569 | 38.227 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -400.671 |
GROUNDFLOOR_PLENUM | 1.376 | -42.828 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.006 | 44.923 | 0.000 | 0.000 | 0.000 | -3.477 | 0.000 |
MIDFLOOR_PLENUM | 61.157 | -239.092 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.124 | 236.024 | 0.000 | 0.000 | 0.000 | -58.213 | -0.000 |
TOPFLOOR_PLENUM | 29.606 | -33.667 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.007 | 10.125 | 0.000 | 0.000 | 0.000 | -6.070 | -0.000 |
Total Facility | 92.139 | -7468.570 | 122.024 | -8857.102 | 0.000 | 0.000 | 1574.489 | 2035.189 | 14676.396 | 1991.263 | 0.000 | 0.457 | 442.821 | 0.000 | -1630.243 | 0.000 | -204.741 | -2774.067 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 13-NOV-04:01 | 0.00 | 0.00 | 0.00 | -99555.69 | 0.00 | 0.00 | 0.00 | 657.72 | 13457.54 | 0.00 | 0.00 | 0.00 | 85440.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 10-OCT-03:02 | 0.00 | 0.00 | 0.00 | -84061.10 | 0.00 | 0.00 | 0.00 | 590.68 | 5937.65 | 0.00 | 0.00 | 0.00 | 77532.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 03-AUG-05:02 | 0.00 | 0.00 | 0.00 | -724167.38 | 0.00 | 0.00 | 8372.50 | 11812.12 | 76473.61 | 0.00 | 0.00 | 0.00 | 627509.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 28-JUL-05:02 | 0.00 | 0.00 | 0.00 | -68615.58 | 0.00 | 0.00 | 843.22 | 1181.21 | 7647.36 | 0.00 | 0.00 | 0.00 | 58943.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 12-JUN-05:03 | 0.00 | 0.00 | 0.00 | -10316.16 | 0.00 | 0.00 | 107.94 | 76.41 | 960.25 | 118.06 | 0.00 | 0.00 | 9068.01 | 0.00 | -0.00 | 0.00 | -14.52 | 0.00 |
PERIMETER_BOT_ZN_2 | 13-AUG-09:02 | 0.00 | 0.00 | 0.00 | -19172.69 | 0.00 | 0.00 | 23.15 | 22.74 | 464.11 | 13631.31 | 0.00 | 0.00 | 5070.51 | 0.00 | -0.00 | 0.00 | -39.14 | 0.00 |
PERIMETER_BOT_ZN_1 | 13-AUG-12:22 | 0.00 | 0.00 | 0.00 | -26453.40 | 0.00 | 0.00 | 36.69 | 35.29 | 720.19 | 17946.68 | 0.00 | 0.00 | 7725.76 | 0.00 | -0.00 | 0.00 | -11.22 | 0.00 |
PERIMETER_BOT_ZN_4 | 23-JUL-16:52 | 0.00 | 0.00 | 0.00 | -23554.29 | 0.00 | 0.00 | 17.52 | 22.74 | 464.11 | 16056.42 | 0.00 | 0.00 | 7002.65 | 0.00 | -0.00 | 0.00 | -9.15 | 0.00 |
PERIMETER_MID_ZN_3 | 10-AUG-05:03 | 0.00 | 0.00 | 0.00 | -75490.26 | 0.00 | 0.00 | 1125.38 | 1441.89 | 9602.45 | 7686.58 | 0.00 | 0.00 | 55819.79 | 0.00 | -0.00 | 0.00 | -185.83 | 0.00 |
PERIMETER_MID_ZN_2 | 13-AUG-09:02 | 0.00 | 0.00 | 0.00 | -202397.78 | 0.00 | 0.00 | 221.10 | 227.41 | 4641.14 | 135022.04 | 0.00 | 0.00 | 63258.51 | 0.00 | -0.00 | 0.00 | -972.41 | 0.00 |
PERIMETER_MID_ZN_1 | 10-SEP-12:32 | 0.00 | 0.00 | 0.00 | -283715.16 | 0.00 | 0.00 | 336.52 | 352.89 | 7201.95 | 210265.91 | 0.00 | 0.00 | 66526.65 | 0.00 | -0.00 | 0.00 | -968.75 | 0.00 |
PERIMETER_MID_ZN_4 | 23-JUL-18:01 | 0.00 | 0.00 | 0.00 | -221976.48 | 0.00 | 0.00 | 0.00 | 227.41 | 3603.49 | 134368.36 | 0.00 | 0.00 | 84215.53 | 0.00 | -0.00 | 0.00 | -438.31 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -8002.32 | 0.00 | 0.00 | 1114.38 | 635.12 | 2160.55 | 4792.99 | 0.00 | 24.74 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -725.47 |
PERIMETER_TOP_ZN_2 | 30-JUL-09:22 | 0.00 | 0.00 | 0.00 | -19828.76 | 0.00 | 0.00 | 22.79 | 22.74 | 464.11 | 12247.75 | 0.00 | 0.00 | 7132.75 | 0.00 | -0.00 | 0.00 | -61.38 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-14:22 | 0.00 | 0.00 | 0.00 | -29921.72 | 0.00 | 0.00 | 33.58 | 35.29 | 720.19 | 16014.65 | 0.00 | 0.00 | 13215.35 | 0.00 | -0.00 | 0.00 | -97.35 | 0.00 |
PERIMETER_TOP_ZN_4 | 30-JUL-18:01 | 0.00 | 0.00 | 0.00 | -23536.69 | 0.00 | 0.00 | 0.00 | 22.74 | 360.35 | 13127.66 | 0.00 | 0.00 | 10081.19 | 0.00 | -0.00 | 0.00 | -55.25 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-AUG-18:22 | 0.00 | 0.00 | 0.00 | -8386.69 | 0.00 | 0.00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 576.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 06-AUG-18:23 | 0.00 | 0.00 | 0.00 | -77998.21 | 0.00 | 0.00 | 0.00 | 158.32 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -104.33 |
DATACENTER_TOP_ZN_6 | 06-AUG-18:12 | 0.00 | 0.00 | 0.00 | -7928.32 | 0.00 | 0.00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 118.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 14-AUG-16:00 | 0.00 | -367399.68 | 0.00 | 0.00 | 0.00 | 0.00 | 2183.10 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17753.71 |
GROUNDFLOOR_PLENUM | 14-AUG-05:15 | 0.00 | -9249.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9266.19 | 0.00 | -0.00 | 0.00 | -16.55 | 0.00 |
MIDFLOOR_PLENUM | 10-AUG-15:10 | 0.00 | -55938.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.42 | 55693.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 10-AUG-14:40 | 0.00 | -17035.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 17016.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-AUG-05:02 | 0.00 | -371883.02 | 0.00 | -1397700.77 | 0.00 | 0.00 | 16374.98 | 21950.55 | 616289.16 | 15520.05 | 0.00 | 0.00 | 1138403.04 | 0.00 | -38023.59 | 0.00 | -930.40 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 09-OCT-15:53 | 0.00 | 0.00 | 11833.38 | 0.00 | 0.00 | 0.00 | 417.36 | 657.72 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26366.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 323199.70 | 0.00 | 0.00 | 0.00 | 0.00 | 11812.12 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -394388.05 |
CORE_TOP | 17-JAN-04:01 | 0.00 | 0.00 | 68402.79 | 0.00 | 0.00 | 0.00 | 0.00 | 590.68 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -74931.09 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 17-JAN-06:01 | 0.00 | 0.00 | 1590.71 | 0.00 | 0.00 | 0.00 | 90.19 | 95.58 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2082.15 | 0.00 | -15.40 | -297.75 |
PERIMETER_BOT_ZN_1 | 17-JAN-05:01 | 0.00 | 0.00 | 9841.29 | 0.00 | 0.00 | 0.00 | 0.00 | 148.32 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2775.52 | 0.00 | -77.07 | -7882.58 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-04:01 | 0.00 | 0.00 | 96730.55 | 0.00 | 0.00 | 0.00 | 0.00 | 741.66 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15245.15 | 0.00 | -2945.59 | -86737.08 |
PERIMETER_MID_ZN_2 | 02-JAN-04:01 | 0.00 | 0.00 | 124371.01 | 0.00 | 0.00 | 0.00 | 0.00 | 477.95 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10046.97 | 0.00 | -2019.00 | -117587.66 |
PERIMETER_MID_ZN_1 | 02-JAN-04:01 | 0.00 | 0.00 | 178879.31 | 0.00 | 0.00 | 0.00 | 0.00 | 741.67 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15667.64 | 0.00 | -3049.78 | -168359.29 |
PERIMETER_MID_ZN_4 | 02-JAN-04:01 | 0.00 | 0.00 | 111853.68 | 0.00 | 0.00 | 0.00 | 0.00 | 477.95 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11412.57 | 0.00 | -2213.67 | -103510.03 |
PERIMETER_TOP_ZN_3 | 16-JAN-07:23 | 0.00 | 0.00 | 11408.05 | 0.00 | 0.00 | 0.00 | 88.10 | 74.17 | 720.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2492.11 | 0.00 | -249.61 | -9548.78 |
PERIMETER_TOP_ZN_2 | 17-JAN-04:01 | 0.00 | 0.00 | 15343.93 | 0.00 | 0.00 | 0.00 | 0.00 | 47.80 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1345.19 | 0.00 | -18.63 | -14508.38 |
PERIMETER_TOP_ZN_1 | 17-JAN-04:01 | 0.00 | 0.00 | 22869.97 | 0.00 | 0.00 | 0.00 | 0.00 | 74.17 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2005.36 | 0.00 | -28.03 | -21656.32 |
PERIMETER_TOP_ZN_4 | 17-JAN-04:01 | 0.00 | 0.00 | 15523.69 | 0.00 | 0.00 | 0.00 | 0.00 | 47.80 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1366.75 | 0.00 | -18.92 | -14666.28 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 17-JAN-04:42 | 0.00 | 0.00 | 5312.41 | 0.00 | 0.00 | 0.00 | 0.00 | 158.32 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24956.79 |
DATACENTER_TOP_ZN_6 | 08-JAN-17:50 | 0.00 | 0.00 | 581.59 | 0.00 | 0.00 | 0.00 | 6.08 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2552.10 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-DEC-05:01 | 11110.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -11110.40 |
MIDFLOOR_PLENUM | 02-JAN-06:13 | 113402.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1293.47 | -112109.05 |
TOPFLOOR_PLENUM | 09-JAN-06:13 | 20146.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -114.80 | -20031.20 |
Total Facility | 02-JAN-05:01 | -226168.25 | 179355.87 | 919787.22 | -179355.87 | 0.00 | 0.00 | 0.00 | 22094.05 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -73029.40 | 0.00 | -16613.17 | -858495.68 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 9.8669 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.5115 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 93.1983 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 78.2474 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.3965 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.5362 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 4.9101 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 4.9101 | 0.2444 | 1.0000 | Not calculated | 1.2002 | 0.2444 | ||
AIRLOOP DATACENTER BOT | 0.4910 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4910 | 0.0318 | 1.0000 | Not calculated | 0.0156 | 0.0318 | ||
AIRLOOP DATACENTER MID | 4.6928 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6928 | 0.0333 | 1.0000 | Not calculated | 0.1563 | 0.0333 | ||
AIRLOOP DATACENTER TOP | 0.4769 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4769 | 0.0328 | 1.0000 | Not calculated | 0.0156 | 0.0328 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 4.9335 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.8625 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 46.5991 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 27.8285 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.6982 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.8715 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 4.9101 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 4.9101 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2444 | ||
AIRLOOP DATACENTER BOT | 0.4910 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4910 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0318 | ||
AIRLOOP DATACENTER MID | 4.6928 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6928 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0333 | ||
AIRLOOP DATACENTER TOP | 0.4769 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4769 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0328 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.002360 | 149.6021 | 0.000305 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.002360 | 1.9486 | 0.000305 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.002360 | 19.4861 | 0.000305 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.002360 | 1.9486 | 0.000305 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.002360 | 149.60 | 0.000305 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BOT | 0.002360 | 1.95 | 0.000305 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.002360 | 19.49 | 0.000305 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.002360 | 1.95 | 0.000305 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9101 | 4.9101 | 4.9101 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2751 | 5.2751 | 1.8621 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 49.2063 | 49.2063 | 18.1079 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7510 | 4.7510 | 1.8624 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7592 | 0.7592 | 0.2338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0540 | 1.0540 | 0.2108 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4853 | 1.4853 | 0.2971 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2932 | 1.2932 | 0.2586 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.7807 | 6.7807 | 2.2783 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.8866 | 10.8866 | 2.1773 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 15.0202 | 15.0202 | 3.0040 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.3045 | 11.3045 | 2.2609 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7692 | 0.7692 | 0.2338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0796 | 1.0796 | 0.2159 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6005 | 1.6005 | 0.3201 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1962 | 1.1962 | 0.2392 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4910 | 0.4910 | 0.4910 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6928 | 4.6928 | 4.6928 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4769 | 0.4769 | 0.4769 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 9.8669 | 8.5115 | 9.8669 | 2.8625 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 93.1983 | 78.2474 | 93.1983 | 27.8285 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.3965 | 8.5362 | 9.3965 | 2.8715 | 0.0000 | 1.0000 |
CAV_BAS | 4.9101 | 4.9101 | 4.9101 | 4.9101 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4910 | 0.4910 | 0.4910 | 0.4910 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6928 | 4.6928 | 4.6928 | 4.6928 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4769 | 0.4769 | 0.4769 | 0.4769 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9101 | 4.9101 | 4.9101 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6376 | 2.6376 | 1.8621 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 24.6031 | 24.6031 | 18.1079 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3755 | 2.3755 | 1.8624 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3796 | 0.3796 | 0.2338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5270 | 0.5270 | 0.2108 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7427 | 0.7427 | 0.2971 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6466 | 0.6466 | 0.2586 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3904 | 3.3904 | 2.2783 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4433 | 5.4433 | 2.1773 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.5101 | 7.5101 | 3.0040 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6523 | 5.6523 | 2.2609 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3846 | 0.3846 | 0.2338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5398 | 0.5398 | 0.2159 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8003 | 0.8003 | 0.3201 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5981 | 0.5981 | 0.2392 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4910 | 0.4910 | 0.4910 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6928 | 4.6928 | 4.6928 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4769 | 0.4769 | 0.4769 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 4.9335 | 2.8625 | 2.8625 | 2.8625 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 46.5991 | 27.8285 | 27.8285 | 27.8285 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.6982 | 2.8715 | 2.8715 | 2.8715 | 0.0000 | 1.0000 |
CAV_BAS | 4.9101 | 4.9101 | 4.9101 | 4.9101 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4910 | 0.4910 | 0.4910 | 0.4910 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6928 | 4.6928 | 4.6928 | 4.6928 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4769 | 0.4769 | 0.4769 | 0.4769 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 20.83 |
Number of hours cooling loads not met | 77.83 |
Number of hours not met | 98.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 |
Heating -- Boiler | 0.00 | 0.00 | 1053.50 | 1185094.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 628.64 | 253259.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7177.60 | 369998.69 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2035.19 | 198852.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 330.56 | 37611.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.49 | 3387.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ComputerHVAC | 1199.18 | 60741.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 1011.11 | 191290.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 234.36 | 48504.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 160.78 | 40919.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 721.82 | 81411.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 22185.30 |
Natural Gas | 0.00 | 1775.33 |
Additional | 0.00 | 7177.61 |
Total | 14676.40 | 31138.24 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 43.94 |
Space Heating | 0.00 |
Space Cooling | 13.57 |
Fans (All) | 21.83 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 478.95 |
Subtotal | 478.95 |
Natural Gas [MJ/m2] | |
Space Heating | 22.74 |
Service Water Heating | 15.58 |
Miscellaneous (All) | 38.33 |
Subtotal | 38.33 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.54 |
Space Heating | 3.38 |
Space Cooling | 25.07 |
Fans (All) | 3.25 |
Service Water Heating | 2.32 |
Receptacle Equipment | 47.13 |
Miscellaneous | 12.31 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2362. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8512.33 | 247.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8726.50 | 33.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8744.50 | 15.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8743.33 | 16.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8522.83 | 237.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8743.17 | 16.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8709.00 | 51.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8744.50 | 15.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8742.00 | 18.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8714.33 | 45.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7979.50 | 780.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7933.50 | 826.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7899.00 | 861.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
Average | 8239.96 | 520.04 | 0.00 | 0.00 | 0.00 |
Sum | 189519.17 | 11960.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368117.83 | 498.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330741.00 | 72.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1764.50 | 503.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1729.17 | 538.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1710.00 | 558.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 103395.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368117.83 | 103395.00 | 0.00 | 0.00 | 0.00 |
Average | 75745.11 | 4589.80 | 0.00 | 0.00 | 0.00 |
Sum | 1742137.50 | 105565.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8337.67 | 422.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8584.67 | 175.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8643.00 | 117.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8682.83 | 77.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8751.50 | 8.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8740.33 | 19.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8719.67 | 40.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8452.83 | 307.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8721.67 | 38.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8690.50 | 69.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8623.33 | 136.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8732.50 | 27.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8702.50 | 57.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8648.67 | 111.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8544.00 | 216.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8509.00 | 251.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8510.17 | 249.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8741.67 | 18.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8744.83 | 15.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8662.83 | 97.17 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Max | 8759.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
Average | 8271.78 | 488.22 | 0.00 | 0.00 | 0.00 |
Sum | 190251.00 | 11229.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 367657.00 | 959.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330504.00 | 309.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330562.00 | 251.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330657.00 | 156.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2110.83 | 157.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2090.00 | 178.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2087.67 | 180.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 103395.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367657.00 | 103395.00 | 0.00 | 0.00 | 0.00 |
Average | 75744.24 | 4590.67 | 0.00 | 0.00 | 0.00 |
Sum | 1742117.50 | 105585.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:50
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.400117E+11 | 98476.81 | 02-JAN-04:01 | 6.60 | 5.58 | 0.566143E+10 | 7499.16 | 20-JAN-10:09 | 4.18 | 2.79 |
February | 0.388745E+11 | 95160.51 | 27-FEB-04:12 | 11.50 | 7.29 | 0.513736E+10 | 7499.03 | 08-FEB-10:09 | 11.50 | 7.29 |
March | 0.499114E+11 | 94992.06 | 06-MAR-04:01 | 6.70 | 6.36 | 0.613692E+10 | 7499.10 | 14-MAR-09:39 | 9.27 | 7.14 |
April | 0.480395E+11 | 95850.58 | 17-APR-03:02 | 6.10 | 5.06 | 0.545464E+10 | 7499.06 | 27-APR-13:09 | 26.10 | 16.37 |
May | 0.496876E+11 | 97972.87 | 30-MAY-03:02 | 10.60 | 9.74 | 0.590590E+10 | 7499.13 | 05-MAY-09:20 | 10.60 | 9.74 |
June | 0.520368E+11 | 96396.00 | 05-JUN-03:02 | 11.02 | 10.00 | 0.588738E+10 | 7499.16 | 09-JUN-13:20 | 21.87 | 13.52 |
July | 0.523892E+11 | 96258.50 | 03-JUL-03:02 | 11.60 | 8.31 | 0.547813E+10 | 7499.10 | 11-JUL-09:20 | 16.13 | 15.49 |
August | 0.579332E+11 | 89402.39 | 21-AUG-03:03 | 12.37 | 11.45 | 0.614281E+10 | 7499.49 | 09-AUG-09:00 | 12.37 | 11.45 |
September | 0.502922E+11 | 96386.73 | 05-SEP-03:02 | 11.70 | 9.88 | 0.545685E+10 | 7499.12 | 14-SEP-09:20 | 17.57 | 15.54 |
October | 0.511761E+11 | 96788.43 | 30-OCT-03:12 | 6.87 | 6.26 | 0.567366E+10 | 7499.05 | 12-OCT-09:20 | 6.87 | 6.26 |
November | 0.483505E+11 | 99560.98 | 13-NOV-04:01 | 1.60 | 1.20 | 0.561642E+10 | 7499.03 | 10-NOV-10:30 | 1.60 | 1.20 |
December | 0.459293E+11 | 98362.18 | 26-DEC-04:01 | -1.0 | -1.0 | 0.547026E+10 | 7499.25 | 13-DEC-14:20 | -1.0 | -1.0 |
Annual Sum or Average | 0.584632E+12 | 0.680218E+11 | ||||||||
Minimum of Months | 0.388745E+11 | 89402.39 | -1.0 | -1.0 | 0.513736E+10 | 7499.03 | -1.0 | -1.0 | ||
Maximum of Months | 0.579332E+11 | 99560.98 | 12.37 | 11.45 | 0.614281E+10 | 7499.49 | 26.10 | 16.37 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.314023E+11 | 77577.36 | 02-JAN-05:01 | 6.10 | 5.29 | 0.503644E+10 | 6734.77 | 20-JAN-10:09 | 4.18 | 2.79 |
February | 0.326485E+11 | 77529.41 | 27-FEB-05:02 | 6.60 | 5.58 | 0.458927E+10 | 6734.71 | 08-FEB-10:09 | 6.60 | 5.58 |
March | 0.454692E+11 | 77193.02 | 21-MAR-04:02 | 4.40 | 3.61 | 0.549917E+10 | 6734.76 | 14-MAR-09:00 | 4.40 | 3.61 |
April | 0.495151E+11 | 79485.27 | 17-APR-03:02 | 6.10 | 5.06 | 0.488291E+10 | 6734.72 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.460730E+11 | 80431.51 | 01-MAY-03:02 | 11.78 | 9.72 | 0.528503E+10 | 6734.83 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.509153E+11 | 81274.46 | 12-JUN-03:02 | 15.00 | 13.35 | 0.527038E+10 | 6734.84 | 05-JUN-09:00 | 15.00 | 13.35 |
July | 0.572075E+11 | 80165.71 | 17-JUL-03:02 | 14.90 | 13.04 | 0.489629E+10 | 6734.76 | 28-JUL-13:00 | 20.00 | 15.26 |
August | 0.642828E+11 | 78190.40 | 22-AUG-03:02 | 12.17 | 10.78 | 0.549649E+10 | 6735.26 | 09-AUG-09:00 | 12.17 | 10.78 |
September | 0.442486E+11 | 83606.39 | 05-SEP-03:02 | 11.70 | 9.88 | 0.488310E+10 | 6734.81 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.433415E+11 | 84063.41 | 10-OCT-03:02 | 12.20 | 10.91 | 0.507748E+10 | 6734.76 | 12-OCT-09:20 | 9.47 | 7.95 |
November | 0.403933E+11 | 80992.44 | 06-NOV-04:03 | 10.10 | 7.78 | 0.502734E+10 | 6734.73 | 13-NOV-10:39 | 2.43 | 2.35 |
December | 0.391857E+11 | 79248.64 | 26-DEC-05:02 | -0.6 | -0.6 | 0.489705E+10 | 6734.82 | 13-DEC-14:09 | -0.6 | -0.6 |
Annual Sum or Average | 0.544683E+12 | 0.608410E+11 | ||||||||
Minimum of Months | 0.314023E+11 | 77193.02 | -0.6 | -0.6 | 0.458927E+10 | 6734.71 | -0.6 | -0.6 | ||
Maximum of Months | 0.642828E+11 | 84063.41 | 15.00 | 13.35 | 0.549917E+10 | 6735.26 | 26.10 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207339E+11 | 18223.15 | 12-JAN-17:00 | 7.20 | 5.41 | 0.447072E+10 | 6607.34 | 12-JAN-14:00 | 7.20 | 5.41 |
February | 0.211769E+11 | 27164.70 | 28-FEB-06:03 | 10.60 | 9.74 | 0.430720E+10 | 6734.58 | 10-FEB-14:09 | 10.60 | 9.74 |
March | 0.287666E+11 | 64278.97 | 03-MAR-06:02 | 6.60 | 6.18 | 0.539346E+10 | 6734.75 | 14-MAR-09:50 | 9.63 | 7.44 |
April | 0.299321E+11 | 70691.67 | 27-APR-05:02 | 9.37 | 7.96 | 0.483059E+10 | 6734.73 | 14-APR-09:09 | 9.37 | 7.96 |
May | 0.363685E+11 | 72266.31 | 09-MAY-05:02 | 11.10 | 9.86 | 0.525657E+10 | 6734.80 | 05-MAY-09:09 | 11.10 | 9.86 |
June | 0.383736E+11 | 71744.35 | 01-JUN-05:02 | 9.08 | 8.10 | 0.525214E+10 | 6734.81 | 09-JUN-13:09 | 21.78 | 13.51 |
July | 0.392293E+11 | 71337.72 | 01-JUL-05:02 | 13.58 | 10.48 | 0.488486E+10 | 6734.75 | 28-JUL-13:00 | 20.00 | 15.26 |
August | 0.425421E+11 | 72422.07 | 03-AUG-05:02 | 11.80 | 11.34 | 0.548677E+10 | 6735.13 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.350380E+11 | 72139.68 | 08-SEP-05:02 | 10.18 | 9.80 | 0.486013E+10 | 6734.81 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.295888E+11 | 71146.34 | 05-OCT-05:02 | 8.30 | 5.23 | 0.500787E+10 | 6734.76 | 12-OCT-09:20 | 9.47 | 7.95 |
November | 0.238627E+11 | 64451.37 | 06-NOV-06:03 | 11.28 | 8.36 | 0.483051E+10 | 6734.72 | 10-NOV-10:30 | 7.25 | 5.94 |
December | 0.221296E+11 | 22332.53 | 06-DEC-17:00 | 1.10 | 0.98 | 0.451568E+10 | 6734.60 | 07-DEC-14:09 | 5.62 | 5.31 |
Annual Sum or Average | 0.367742E+12 | 0.590965E+11 | ||||||||
Minimum of Months | 0.207339E+11 | 18223.15 | 1.10 | 0.98 | 0.430720E+10 | 6607.34 | 5.62 | 5.31 | ||
Maximum of Months | 0.425421E+11 | 72422.07 | 13.58 | 11.34 | 0.548677E+10 | 6735.13 | 23.80 | 15.92 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151605E+11 | 16674.94 | 11-JAN-17:00 | 12.20 | 9.27 | 0.400805E+10 | 6029.90 | 12-JAN-14:00 | 7.20 | 5.88 |
February | 0.162183E+11 | 19574.27 | 28-FEB-17:00 | 14.40 | 10.82 | 0.378829E+10 | 6620.28 | 28-FEB-14:00 | 14.40 | 10.82 |
March | 0.229617E+11 | 23370.16 | 15-MAR-16:00 | 11.10 | 7.72 | 0.484399E+10 | 6734.39 | 15-MAR-13:00 | 11.10 | 7.72 |
April | 0.253843E+11 | 65516.28 | 28-APR-05:03 | 11.10 | 9.92 | 0.457816E+10 | 6734.72 | 27-APR-13:00 | 11.10 | 9.92 |
May | 0.326557E+11 | 65017.90 | 05-MAY-05:03 | 12.98 | 10.75 | 0.516207E+10 | 6734.78 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.369883E+11 | 67555.54 | 29-JUN-05:03 | 12.80 | 11.44 | 0.521837E+10 | 6734.80 | 09-JUN-13:09 | 12.80 | 11.44 |
July | 0.393360E+11 | 68629.15 | 28-JUL-05:02 | 14.50 | 12.30 | 0.486848E+10 | 6734.79 | 11-JUL-09:09 | 14.50 | 12.30 |
August | 0.419092E+11 | 68416.22 | 29-AUG-05:02 | 15.22 | 13.93 | 0.546443E+10 | 6735.12 | 09-AUG-09:00 | 15.22 | 13.93 |
September | 0.304390E+11 | 65216.91 | 15-SEP-05:03 | 11.60 | 11.30 | 0.475682E+10 | 6734.77 | 14-SEP-09:09 | 11.60 | 11.30 |
October | 0.230372E+11 | 32556.85 | 04-OCT-16:00 | 21.10 | 11.40 | 0.462250E+10 | 6734.60 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.178010E+11 | 18371.37 | 02-NOV-16:00 | 13.30 | 10.88 | 0.421074E+10 | 6442.45 | 06-NOV-14:00 | 11.10 | 10.22 |
December | 0.154766E+11 | 16650.45 | 05-DEC-16:40 | 6.10 | 4.53 | 0.390718E+10 | 6067.52 | 06-DEC-14:00 | 5.00 | 4.36 |
Annual Sum or Average | 0.317368E+12 | 0.554291E+11 | ||||||||
Minimum of Months | 0.151605E+11 | 16650.45 | 6.10 | 4.53 | 0.378829E+10 | 6029.90 | 5.00 | 4.36 | ||
Maximum of Months | 0.419092E+11 | 68629.15 | 21.10 | 13.93 | 0.546443E+10 | 6735.12 | 15.97 | 13.93 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253497E+10 | 2774.12 | 02-JAN-06:03 | 6.10 | 5.29 | 0.551195E+09 | 812.52 | 11-JAN-14:50 | 14.40 | 10.49 |
February | 0.265306E+10 | 3955.97 | 27-FEB-15:30 | 19.70 | 12.30 | 0.525507E+09 | 845.61 | 28-FEB-10:09 | 10.68 | 10.04 |
March | 0.381036E+10 | 4376.24 | 10-MAR-14:30 | 16.40 | 11.76 | 0.668374E+09 | 845.63 | 09-MAR-14:09 | 16.40 | 11.76 |
April | 0.496991E+10 | 6417.45 | 27-APR-15:20 | 27.20 | 17.16 | 0.605377E+09 | 845.63 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.546717E+10 | 6397.39 | 15-MAY-14:00 | 23.30 | 13.50 | 0.658404E+09 | 845.63 | 05-MAY-09:09 | 23.30 | 13.50 |
June | 0.663652E+10 | 10316.85 | 12-JUN-05:03 | 14.40 | 13.42 | 0.660477E+09 | 845.64 | 09-JUN-13:09 | 14.40 | 13.42 |
July | 0.793775E+10 | 10066.45 | 10-JUL-05:02 | 13.22 | 11.65 | 0.614460E+09 | 845.63 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.859948E+10 | 10111.80 | 28-AUG-05:02 | 14.83 | 13.93 | 0.689583E+09 | 845.71 | 25-AUG-13:50 | 14.83 | 13.93 |
September | 0.483476E+10 | 5960.88 | 05-SEP-13:10 | 16.20 | 11.51 | 0.607556E+09 | 845.63 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.383109E+10 | 5340.13 | 10-OCT-05:03 | 12.20 | 11.22 | 0.622118E+09 | 845.62 | 12-OCT-09:50 | 10.32 | 8.22 |
November | 0.315794E+10 | 4141.02 | 06-NOV-11:40 | 13.70 | 9.94 | 0.599089E+09 | 845.62 | 06-NOV-14:09 | 11.60 | 10.16 |
December | 0.286965E+10 | 2896.56 | 11-DEC-06:03 | 5.20 | 3.90 | 0.562384E+09 | 843.89 | 04-DEC-14:39 | 5.20 | 3.90 |
Annual Sum or Average | 0.573027E+11 | 0.736453E+10 | ||||||||
Minimum of Months | 0.253497E+10 | 2774.12 | 5.20 | 3.90 | 0.525507E+09 | 812.52 | 5.20 | 3.90 | ||
Maximum of Months | 0.859948E+10 | 10316.85 | 27.20 | 17.16 | 0.689583E+09 | 845.71 | 27.20 | 17.16 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205448E+10 | 2386.17 | 02-JAN-06:03 | 6.10 | 5.29 | 0.341031E+09 | 519.19 | 05-JAN-10:09 | 2.70 | 2.49 |
February | 0.221615E+10 | 3535.59 | 27-FEB-10:30 | 12.50 | 9.25 | 0.329474E+09 | 544.95 | 08-FEB-10:09 | 12.50 | 9.25 |
March | 0.331086E+10 | 6857.76 | 14-MAR-09:00 | 7.80 | 5.89 | 0.421102E+09 | 544.96 | 02-MAR-10:09 | 7.80 | 5.89 |
April | 0.455584E+10 | 9601.28 | 27-APR-08:30 | 16.95 | 12.18 | 0.386978E+09 | 544.96 | 20-APR-09:00 | 16.95 | 12.18 |
May | 0.503783E+10 | 17922.64 | 14-MAY-08:23 | 15.55 | 10.92 | 0.422316E+09 | 544.97 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.619277E+10 | 17779.09 | 25-JUN-09:32 | 17.43 | 12.65 | 0.424653E+09 | 544.97 | 09-JUN-13:09 | 17.43 | 12.65 |
July | 0.687256E+10 | 17200.94 | 30-JUL-08:52 | 20.60 | 15.79 | 0.394776E+09 | 545.84 | 31-JUL-09:20 | 22.57 | 17.16 |
August | 0.754049E+10 | 19176.14 | 13-AUG-09:02 | 21.20 | 16.02 | 0.442868E+09 | 545.71 | 10-AUG-09:20 | 21.20 | 16.02 |
September | 0.470161E+10 | 18026.36 | 10-SEP-08:62 | 14.68 | 12.94 | 0.389271E+09 | 544.97 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.343989E+10 | 7918.16 | 04-OCT-09:00 | 15.60 | 10.49 | 0.391670E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.252240E+10 | 3085.40 | 02-NOV-10:30 | 12.25 | 10.40 | 0.364844E+09 | 544.94 | 02-NOV-09:20 | 12.25 | 10.40 |
December | 0.229095E+10 | 2605.11 | 05-DEC-10:10 | 6.97 | 5.16 | 0.336922E+09 | 544.95 | 05-DEC-10:20 | 7.23 | 5.22 |
Annual Sum or Average | 0.507358E+11 | 0.464591E+10 | ||||||||
Minimum of Months | 0.205448E+10 | 2386.17 | 6.10 | 5.16 | 0.329474E+09 | 519.19 | 2.70 | 2.49 | ||
Maximum of Months | 0.754049E+10 | 19176.14 | 21.20 | 16.02 | 0.442868E+09 | 545.84 | 22.57 | 17.16 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313166E+10 | 11350.69 | 20-JAN-13:10 | 6.70 | 4.72 | 0.540557E+09 | 845.64 | 20-JAN-10:39 | 6.70 | 4.72 |
February | 0.425776E+10 | 14984.60 | 12-FEB-13:33 | 6.50 | 1.20 | 0.523277E+09 | 845.64 | 08-FEB-10:09 | 6.50 | 1.20 |
March | 0.655244E+10 | 15123.90 | 01-MAR-13:40 | 11.33 | 6.09 | 0.655825E+09 | 846.05 | 14-MAR-13:50 | 15.40 | 10.34 |
April | 0.781658E+10 | 16157.97 | 27-APR-13:00 | 26.10 | 16.28 | 0.599364E+09 | 846.42 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.763806E+10 | 15843.83 | 14-MAY-11:43 | 21.02 | 12.61 | 0.653352E+09 | 845.66 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.840142E+10 | 13304.02 | 11-JUN-11:23 | 21.15 | 15.41 | 0.657829E+09 | 845.68 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.106665E+11 | 19380.20 | 30-JUL-12:53 | 26.10 | 17.75 | 0.613742E+09 | 846.50 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.125324E+11 | 26456.72 | 13-AUG-12:22 | 26.30 | 18.24 | 0.689129E+09 | 847.33 | 29-AUG-13:30 | 29.30 | 20.07 |
September | 0.902317E+10 | 22903.22 | 10-SEP-12:43 | 20.40 | 13.99 | 0.605316E+09 | 846.94 | 15-SEP-13:50 | 21.70 | 16.50 |
October | 0.706558E+10 | 25516.66 | 08-OCT-12:32 | 17.80 | 13.47 | 0.612241E+09 | 846.54 | 02-OCT-13:20 | 17.80 | 13.47 |
November | 0.428637E+10 | 13101.91 | 04-NOV-13:30 | 20.85 | 16.00 | 0.578258E+09 | 845.63 | 06-NOV-14:09 | 11.60 | 10.16 |
December | 0.410858E+10 | 13171.74 | 05-DEC-12:30 | 10.30 | 6.13 | 0.543322E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.854806E+11 | 0.727221E+10 | ||||||||
Minimum of Months | 0.313166E+10 | 11350.69 | 6.50 | 1.20 | 0.523277E+09 | 845.63 | 6.50 | 1.20 | ||
Maximum of Months | 0.125324E+11 | 26456.72 | 26.30 | 18.24 | 0.689129E+09 | 847.33 | 29.30 | 20.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296347E+10 | 4072.93 | 05-JAN-15:30 | 6.40 | 4.89 | 0.363521E+09 | 544.94 | 11-JAN-14:30 | 14.40 | 10.49 |
February | 0.352742E+10 | 10864.53 | 24-FEB-06:02 | 13.90 | 12.04 | 0.357375E+09 | 544.95 | 22-FEB-14:09 | 13.90 | 12.04 |
March | 0.589788E+10 | 13393.86 | 03-MAR-06:02 | 6.60 | 6.18 | 0.443613E+09 | 544.96 | 09-MAR-14:09 | 14.90 | 12.35 |
April | 0.835608E+10 | 19080.08 | 02-APR-15:42 | 20.60 | 11.97 | 0.396298E+09 | 544.96 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.702853E+10 | 22150.54 | 07-MAY-16:42 | 21.78 | 16.19 | 0.426502E+09 | 544.96 | 05-MAY-09:09 | 21.78 | 16.19 |
June | 0.867423E+10 | 22476.34 | 18-JUN-17:02 | 17.12 | 12.23 | 0.427473E+09 | 544.97 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.117903E+11 | 23554.24 | 23-JUL-16:52 | 26.70 | 15.58 | 0.398242E+09 | 544.97 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.130946E+11 | 23408.06 | 06-AUG-16:52 | 23.40 | 15.11 | 0.446596E+09 | 545.03 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.655470E+10 | 19683.91 | 10-SEP-16:42 | 22.20 | 14.22 | 0.394342E+09 | 544.96 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.526569E+10 | 14591.01 | 04-OCT-05:02 | 11.52 | 8.71 | 0.408480E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.435929E+10 | 14714.83 | 27-NOV-06:01 | 11.70 | 10.85 | 0.403562E+09 | 544.95 | 03-NOV-09:09 | 11.70 | 10.85 |
December | 0.434247E+10 | 17049.39 | 11-DEC-06:01 | 5.20 | 3.90 | 0.393261E+09 | 544.97 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.818547E+11 | 0.485926E+10 | ||||||||
Minimum of Months | 0.296347E+10 | 4072.93 | 5.20 | 3.90 | 0.357375E+09 | 544.94 | 7.10 | 5.11 | ||
Maximum of Months | 0.130946E+11 | 23554.24 | 26.70 | 16.19 | 0.446596E+09 | 545.03 | 26.10 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.729163E+09 | 1755.05 | 11-JAN-16:20 | 13.67 | 10.10 | 0.470122E+09 | 689.72 | 11-JAN-14:00 | 13.67 | 10.10 |
February | 0.124819E+10 | 2142.16 | 28-FEB-15:00 | 13.90 | 10.81 | 0.443383E+09 | 795.36 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.238992E+10 | 2246.48 | 22-MAR-05:03 | 6.10 | 5.58 | 0.578963E+09 | 825.22 | 10-MAR-14:00 | 6.10 | 5.58 |
April | 0.283554E+10 | 4984.13 | 27-APR-15:50 | 27.20 | 16.97 | 0.557934E+09 | 845.62 | 27-APR-13:30 | 27.20 | 16.97 |
May | 0.406967E+10 | 5559.40 | 05-MAY-13:30 | 23.85 | 16.52 | 0.642398E+09 | 845.63 | 05-MAY-09:09 | 23.85 | 16.52 |
June | 0.479359E+10 | 6129.04 | 21-JUN-15:30 | 24.70 | 15.68 | 0.653738E+09 | 845.64 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.540544E+10 | 7018.63 | 24-JUL-15:00 | 30.60 | 18.78 | 0.610972E+09 | 845.63 | 28-JUL-13:00 | 20.00 | 15.26 |
August | 0.559960E+10 | 7549.72 | 10-AUG-05:03 | 17.33 | 14.38 | 0.684633E+09 | 845.68 | 09-AUG-09:00 | 17.33 | 14.38 |
September | 0.363085E+10 | 4958.97 | 12-SEP-14:40 | 24.40 | 16.65 | 0.590190E+09 | 845.63 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.258335E+10 | 2970.34 | 04-OCT-15:30 | 21.40 | 11.45 | 0.559130E+09 | 845.60 | 05-OCT-13:00 | 16.10 | 10.65 |
November | 0.170365E+10 | 2345.73 | 06-NOV-06:03 | 11.28 | 8.36 | 0.499117E+09 | 773.61 | 02-NOV-13:00 | 11.28 | 8.36 |
December | 0.931425E+09 | 1689.00 | 29-DEC-16:10 | 10.40 | 8.63 | 0.456686E+09 | 674.98 | 29-DEC-14:00 | 10.40 | 8.63 |
Annual Sum or Average | 0.359204E+11 | 0.674727E+10 | ||||||||
Minimum of Months | 0.729163E+09 | 1689.00 | 6.10 | 5.58 | 0.443383E+09 | 674.98 | 6.10 | 5.58 | ||
Maximum of Months | 0.559960E+10 | 7549.72 | 30.60 | 18.78 | 0.684633E+09 | 845.68 | 27.20 | 16.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.544014E+09 | 1593.19 | 05-JAN-09:40 | 1.67 | 1.50 | 0.220956E+09 | 414.60 | 05-JAN-09:50 | 2.23 | 2.03 |
February | 0.114439E+10 | 1995.33 | 08-FEB-10:00 | 2.20 | 1.26 | 0.211119E+09 | 480.70 | 08-FEB-09:00 | 2.20 | 1.26 |
March | 0.240404E+10 | 4892.37 | 14-MAR-10:10 | 10.28 | 7.92 | 0.276923E+09 | 521.21 | 14-MAR-10:20 | 10.57 | 8.09 |
April | 0.341583E+10 | 9640.15 | 27-APR-09:00 | 17.80 | 12.21 | 0.271429E+09 | 521.21 | 27-APR-12:20 | 25.37 | 15.73 |
May | 0.442036E+10 | 18203.62 | 14-MAY-08:13 | 15.17 | 10.71 | 0.302114E+09 | 521.23 | 15-MAY-10:09 | 19.18 | 13.24 |
June | 0.554713E+10 | 19244.81 | 25-JUN-08:42 | 16.52 | 11.95 | 0.308680E+09 | 521.22 | 07-JUN-10:09 | 16.52 | 11.95 |
July | 0.588266E+10 | 20169.82 | 23-JUL-08:42 | 18.72 | 13.76 | 0.289200E+09 | 521.50 | 31-JUL-08:00 | 22.20 | 16.89 |
August | 0.638012E+10 | 20243.61 | 13-AUG-09:02 | 21.20 | 16.02 | 0.323497E+09 | 521.40 | 23-AUG-08:00 | 21.20 | 15.17 |
September | 0.419112E+10 | 18450.18 | 10-SEP-09:53 | 17.20 | 13.54 | 0.277161E+09 | 521.21 | 13-SEP-07:10 | 14.68 | 13.29 |
October | 0.262541E+10 | 7021.84 | 04-OCT-09:00 | 15.60 | 10.49 | 0.264498E+09 | 521.21 | 05-OCT-10:09 | 14.08 | 9.36 |
November | 0.141274E+10 | 2222.69 | 06-NOV-06:03 | 11.28 | 8.36 | 0.230709E+09 | 490.80 | 02-NOV-10:50 | 11.28 | 8.36 |
December | 0.764590E+09 | 1792.65 | 05-DEC-10:00 | 6.70 | 5.10 | 0.215185E+09 | 445.55 | 05-DEC-09:00 | 6.70 | 5.10 |
Annual Sum or Average | 0.387324E+11 | 0.319147E+10 | ||||||||
Minimum of Months | 0.544014E+09 | 1593.19 | 1.67 | 1.26 | 0.211119E+09 | 414.60 | 2.20 | 1.26 | ||
Maximum of Months | 0.638012E+10 | 20243.61 | 21.20 | 16.02 | 0.323497E+09 | 521.50 | 25.37 | 16.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181603E+10 | 10536.47 | 20-JAN-13:30 | 6.70 | 4.72 | 0.499291E+09 | 845.63 | 20-JAN-14:20 | 6.87 | 4.79 |
February | 0.332078E+10 | 23259.35 | 12-FEB-14:02 | 6.70 | 1.41 | 0.489321E+09 | 845.64 | 10-FEB-14:09 | 6.70 | 1.41 |
March | 0.551763E+10 | 15810.37 | 01-MAR-13:40 | 11.33 | 6.09 | 0.620477E+09 | 846.06 | 01-MAR-14:39 | 12.77 | 7.03 |
April | 0.605886E+10 | 16405.66 | 27-APR-13:10 | 26.10 | 16.37 | 0.578635E+09 | 846.19 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.684946E+10 | 25276.49 | 14-MAY-13:32 | 22.60 | 12.25 | 0.641939E+09 | 845.66 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.708352E+10 | 11947.95 | 28-JUN-13:10 | 24.50 | 15.71 | 0.649786E+09 | 845.67 | 28-JUN-13:20 | 24.60 | 15.70 |
July | 0.856872E+10 | 23624.46 | 23-JUL-13:23 | 26.95 | 16.84 | 0.609521E+09 | 846.20 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.100565E+11 | 26863.20 | 13-AUG-12:22 | 26.30 | 18.24 | 0.684550E+09 | 847.11 | 29-AUG-13:39 | 29.43 | 20.04 |
September | 0.868000E+10 | 28368.52 | 10-SEP-12:32 | 20.20 | 13.87 | 0.596852E+09 | 846.75 | 15-SEP-13:00 | 21.70 | 16.45 |
October | 0.634011E+10 | 26709.63 | 08-OCT-13:02 | 18.17 | 13.70 | 0.588677E+09 | 846.10 | 02-OCT-13:39 | 18.17 | 13.70 |
November | 0.306528E+10 | 12842.99 | 04-NOV-13:30 | 20.85 | 16.00 | 0.530111E+09 | 845.63 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.237905E+10 | 11286.82 | 05-DEC-12:30 | 10.30 | 6.13 | 0.496285E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.697359E+11 | 0.698545E+10 | ||||||||
Minimum of Months | 0.181603E+10 | 10536.47 | 6.70 | 1.41 | 0.489321E+09 | 845.63 | 6.70 | 1.41 | ||
Maximum of Months | 0.100565E+11 | 28368.52 | 26.95 | 18.24 | 0.684550E+09 | 847.11 | 29.43 | 20.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.959675E+09 | 2016.31 | 05-JAN-15:50 | 6.20 | 4.71 | 0.305813E+09 | 473.36 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.156355E+10 | 5614.95 | 27-FEB-15:30 | 19.70 | 12.30 | 0.294441E+09 | 544.93 | 27-FEB-14:00 | 19.70 | 12.30 |
March | 0.277209E+10 | 7672.13 | 14-MAR-16:00 | 17.20 | 10.94 | 0.379390E+09 | 544.94 | 02-MAR-14:00 | 17.20 | 10.94 |
April | 0.367551E+10 | 11414.96 | 26-APR-16:00 | 24.40 | 14.49 | 0.363372E+09 | 544.95 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.501826E+10 | 21465.14 | 14-MAY-16:51 | 22.80 | 11.74 | 0.411702E+09 | 544.96 | 05-MAY-09:09 | 22.80 | 11.74 |
June | 0.550308E+10 | 18626.17 | 25-JUN-16:42 | 21.70 | 13.39 | 0.419451E+09 | 544.96 | 09-JUN-13:09 | 21.70 | 13.39 |
July | 0.708251E+10 | 22197.93 | 23-JUL-18:01 | 25.82 | 15.89 | 0.395057E+09 | 544.96 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.695474E+10 | 20483.30 | 06-AUG-17:21 | 23.60 | 15.18 | 0.441793E+09 | 545.00 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.468512E+10 | 20314.19 | 10-SEP-15:52 | 22.20 | 14.48 | 0.380193E+09 | 544.96 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.295066E+10 | 9280.71 | 04-OCT-16:00 | 21.10 | 11.40 | 0.361617E+09 | 544.94 | 02-OCT-13:09 | 21.10 | 11.40 |
November | 0.180110E+10 | 3318.98 | 04-NOV-15:00 | 21.10 | 15.94 | 0.322641E+09 | 533.37 | 10-NOV-14:00 | 10.00 | 6.84 |
December | 0.123449E+10 | 2197.26 | 05-DEC-15:40 | 7.40 | 5.40 | 0.300344E+09 | 510.01 | 05-DEC-14:00 | 7.40 | 5.40 |
Annual Sum or Average | 0.442008E+11 | 0.437582E+10 | ||||||||
Minimum of Months | 0.959675E+09 | 2016.31 | 6.20 | 4.71 | 0.294441E+09 | 473.36 | 6.10 | 4.61 | ||
Maximum of Months | 0.708251E+10 | 22197.93 | 25.82 | 15.94 | 0.441793E+09 | 545.00 | 26.10 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198077E+09 | 1626.36 | 11-JAN-16:20 | 13.67 | 10.10 | 0.463919E+09 | 645.19 | 11-JAN-14:00 | 13.67 | 10.10 |
February | 0.550147E+09 | 2029.69 | 28-FEB-15:10 | 13.90 | 10.77 | 0.428058E+09 | 749.33 | 28-FEB-14:00 | 13.90 | 10.77 |
March | 0.147684E+10 | 2156.71 | 10-MAR-15:00 | 16.10 | 11.51 | 0.531353E+09 | 784.87 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.231701E+10 | 5433.51 | 27-APR-15:50 | 27.20 | 16.97 | 0.519151E+09 | 845.62 | 27-APR-13:39 | 27.20 | 16.97 |
May | 0.366885E+10 | 5835.86 | 15-MAY-14:40 | 23.30 | 12.92 | 0.615650E+09 | 845.62 | 15-MAY-13:09 | 23.30 | 12.92 |
June | 0.460019E+10 | 6737.55 | 21-JUN-15:30 | 24.70 | 15.68 | 0.641224E+09 | 845.64 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.536490E+10 | 8002.52 | 24-JUL-15:00 | 30.60 | 18.78 | 0.605585E+09 | 845.63 | 28-JUL-13:00 | 20.00 | 15.26 |
August | 0.548986E+10 | 7437.53 | 09-AUG-15:30 | 28.70 | 18.83 | 0.676816E+09 | 845.68 | 09-AUG-09:00 | 28.70 | 18.83 |
September | 0.323047E+10 | 5227.49 | 14-SEP-15:50 | 24.32 | 17.03 | 0.560547E+09 | 845.61 | 07-SEP-13:09 | 24.32 | 17.03 |
October | 0.176862E+10 | 2730.53 | 04-OCT-13:30 | 20.85 | 11.31 | 0.509955E+09 | 821.91 | 05-OCT-13:00 | 16.10 | 10.65 |
November | 0.734112E+09 | 1895.89 | 02-NOV-14:50 | 13.48 | 11.22 | 0.468582E+09 | 710.90 | 02-NOV-13:00 | 13.48 | 11.22 |
December | 0.173359E+09 | 1564.21 | 29-DEC-16:10 | 10.40 | 8.63 | 0.448079E+09 | 633.65 | 29-DEC-14:00 | 10.40 | 8.63 |
Annual Sum or Average | 0.295724E+11 | 0.646892E+10 | ||||||||
Minimum of Months | 0.173359E+09 | 1564.21 | 10.40 | 8.63 | 0.428058E+09 | 633.65 | 10.40 | 8.63 | ||
Maximum of Months | 0.548986E+10 | 8002.52 | 30.60 | 18.83 | 0.676816E+09 | 845.68 | 28.70 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192150E+09 | 1464.59 | 12-JAN-06:05 | 6.70 | 6.36 | 0.299112E+09 | 403.99 | 11-JAN-14:00 | 6.70 | 6.36 |
February | 0.654428E+09 | 1823.91 | 27-FEB-16:10 | 19.32 | 12.38 | 0.277621E+09 | 468.96 | 27-FEB-14:00 | 19.32 | 12.38 |
March | 0.166223E+10 | 3175.99 | 14-MAR-10:00 | 10.00 | 7.75 | 0.356718E+09 | 544.95 | 14-MAR-09:00 | 10.00 | 7.75 |
April | 0.287946E+10 | 9123.90 | 27-APR-09:30 | 18.35 | 12.60 | 0.358914E+09 | 544.96 | 27-APR-13:30 | 26.10 | 16.55 |
May | 0.408026E+10 | 16198.34 | 14-MAY-10:02 | 19.18 | 12.29 | 0.403807E+09 | 544.97 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.543858E+10 | 15702.65 | 25-JUN-10:32 | 18.87 | 13.09 | 0.417455E+09 | 544.97 | 09-JUN-13:09 | 18.87 | 13.09 |
July | 0.593332E+10 | 19832.64 | 30-JUL-09:22 | 21.40 | 16.06 | 0.391197E+09 | 545.63 | 31-JUL-09:00 | 23.30 | 17.69 |
August | 0.638886E+10 | 19016.72 | 06-AUG-09:12 | 15.90 | 13.10 | 0.438576E+09 | 545.68 | 10-AUG-09:00 | 23.20 | 17.13 |
September | 0.382724E+10 | 16415.99 | 10-SEP-09:43 | 17.02 | 13.53 | 0.367014E+09 | 544.97 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.190147E+10 | 5704.28 | 04-OCT-09:30 | 16.40 | 10.73 | 0.341454E+09 | 544.95 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.672922E+09 | 1781.51 | 02-NOV-10:40 | 12.43 | 10.47 | 0.301333E+09 | 464.24 | 02-NOV-13:00 | 14.40 | 11.37 |
December | 0.224039E+09 | 1476.28 | 27-DEC-06:05 | 4.90 | 4.18 | 0.288960E+09 | 414.79 | 05-DEC-10:30 | 4.90 | 4.18 |
Annual Sum or Average | 0.338550E+11 | 0.424216E+10 | ||||||||
Minimum of Months | 0.192150E+09 | 1464.59 | 4.90 | 4.18 | 0.277621E+09 | 403.99 | 4.90 | 4.18 | ||
Maximum of Months | 0.638886E+10 | 19832.64 | 21.40 | 16.06 | 0.438576E+09 | 545.68 | 26.10 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106431E+10 | 8615.68 | 20-JAN-13:30 | 6.70 | 4.72 | 0.480480E+09 | 845.63 | 20-JAN-14:39 | 7.03 | 4.87 |
February | 0.222401E+10 | 12464.51 | 27-FEB-14:30 | 19.15 | 11.80 | 0.468344E+09 | 845.63 | 07-FEB-14:09 | 19.15 | 11.80 |
March | 0.409339E+10 | 14341.67 | 14-MAR-13:40 | 15.20 | 10.17 | 0.583367E+09 | 845.65 | 14-MAR-13:00 | 15.60 | 10.50 |
April | 0.519933E+10 | 16962.34 | 27-APR-13:20 | 26.10 | 16.46 | 0.552614E+09 | 846.33 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.635414E+10 | 24836.74 | 14-MAY-13:23 | 22.50 | 12.24 | 0.619957E+09 | 845.67 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.693571E+10 | 12700.19 | 28-JUN-13:20 | 24.60 | 15.70 | 0.636525E+09 | 845.67 | 09-JUN-13:09 | 24.60 | 15.70 |
July | 0.864616E+10 | 28749.59 | 30-JUL-13:22 | 26.40 | 17.72 | 0.602278E+09 | 846.32 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.100467E+11 | 27466.61 | 06-AUG-13:53 | 22.60 | 15.75 | 0.676596E+09 | 846.96 | 29-AUG-13:20 | 29.17 | 20.09 |
September | 0.815250E+10 | 29918.08 | 10-SEP-14:22 | 22.50 | 14.48 | 0.574754E+09 | 846.89 | 15-SEP-13:00 | 21.70 | 16.45 |
October | 0.504011E+10 | 19657.67 | 04-OCT-13:20 | 20.77 | 11.28 | 0.553565E+09 | 846.01 | 03-OCT-13:00 | 20.77 | 11.28 |
November | 0.181413E+10 | 11408.85 | 04-NOV-13:30 | 20.85 | 16.00 | 0.491779E+09 | 845.63 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.130261E+10 | 8328.36 | 05-DEC-12:30 | 10.30 | 6.13 | 0.474726E+09 | 845.64 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.608731E+11 | 0.671498E+10 | ||||||||
Minimum of Months | 0.106431E+10 | 8328.36 | 6.70 | 4.72 | 0.468344E+09 | 845.63 | 7.03 | 4.87 | ||
Maximum of Months | 0.100467E+11 | 29918.08 | 26.40 | 17.72 | 0.676596E+09 | 846.96 | 29.17 | 20.09 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.445006E+09 | 1976.27 | 05-JAN-15:50 | 6.20 | 4.71 | 0.300960E+09 | 448.61 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.956947E+09 | 4823.60 | 27-FEB-15:30 | 19.70 | 12.30 | 0.284370E+09 | 544.92 | 27-FEB-14:00 | 19.70 | 12.30 |
March | 0.208984E+10 | 7177.39 | 14-MAR-16:00 | 17.20 | 10.94 | 0.353761E+09 | 544.93 | 02-MAR-14:00 | 17.20 | 10.94 |
April | 0.325686E+10 | 11491.94 | 26-APR-16:00 | 24.40 | 14.49 | 0.343129E+09 | 544.96 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.478152E+10 | 22784.13 | 07-MAY-16:31 | 21.87 | 16.22 | 0.396112E+09 | 544.96 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.543605E+10 | 20956.88 | 25-JUN-16:32 | 21.70 | 13.31 | 0.410512E+09 | 544.96 | 09-JUN-13:09 | 21.70 | 13.31 |
July | 0.712695E+10 | 23537.78 | 30-JUL-18:01 | 26.32 | 17.50 | 0.391190E+09 | 544.96 | 28-JUL-13:50 | 26.32 | 17.50 |
August | 0.694416E+10 | 22911.38 | 06-AUG-17:11 | 23.53 | 15.16 | 0.436378E+09 | 545.00 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.442369E+10 | 21701.33 | 10-SEP-16:22 | 22.20 | 14.33 | 0.363812E+09 | 544.94 | 15-SEP-13:50 | 21.70 | 16.50 |
October | 0.233289E+10 | 9066.23 | 04-OCT-16:00 | 21.10 | 11.40 | 0.336133E+09 | 544.93 | 03-OCT-13:00 | 21.10 | 11.40 |
November | 0.102433E+10 | 2539.09 | 04-NOV-15:50 | 20.18 | 15.92 | 0.305168E+09 | 496.43 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.542074E+09 | 2097.68 | 05-DEC-15:40 | 7.40 | 5.40 | 0.292379E+09 | 472.53 | 05-DEC-14:00 | 7.40 | 5.40 |
Annual Sum or Average | 0.393603E+11 | 0.421390E+10 | ||||||||
Minimum of Months | 0.445006E+09 | 1976.27 | 6.20 | 4.71 | 0.284370E+09 | 448.61 | 6.10 | 4.61 | ||
Maximum of Months | 0.712695E+10 | 23537.78 | 26.32 | 17.50 | 0.436378E+09 | 545.00 | 26.32 | 17.50 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.776958E+09 | 2663.54 | 02-JAN-06:07 | 6.10 | 5.29 | 0.00 | 0.00 | 01-JAN-00:10 | 6.10 | 5.29 |
February | 0.108664E+10 | 3889.37 | 28-FEB-06:15 | 10.60 | 9.74 | 0.00 | 0.00 | 01-FEB-00:10 | 10.60 | 9.74 |
March | 0.259299E+10 | 4382.05 | 20-MAR-05:15 | 5.97 | 4.27 | 0.00 | 0.00 | 01-MAR-00:10 | 5.97 | 4.27 |
April | 0.384021E+10 | 5342.00 | 27-APR-16:00 | 27.20 | 16.90 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 16.90 |
May | 0.420564E+10 | 6093.57 | 08-MAY-05:03 | 9.50 | 9.45 | 0.00 | 0.00 | 01-MAY-00:10 | 9.50 | 9.45 |
June | 0.542606E+10 | 8799.59 | 12-JUN-05:15 | 14.40 | 13.42 | 0.00 | 0.00 | 01-JUN-00:10 | 14.40 | 13.42 |
July | 0.653676E+10 | 7735.59 | 24-JUL-05:15 | 16.13 | 13.30 | 0.00 | 0.00 | 01-JUL-00:10 | 16.13 | 13.30 |
August | 0.743304E+10 | 9249.94 | 14-AUG-05:15 | 15.33 | 13.50 | 0.00 | 0.00 | 01-AUG-00:10 | 15.33 | 13.50 |
September | 0.458959E+10 | 7481.43 | 05-SEP-05:15 | 10.77 | 9.27 | 0.00 | 0.00 | 01-SEP-00:10 | 10.77 | 9.27 |
October | 0.318603E+10 | 8007.24 | 10-OCT-05:15 | 12.20 | 11.16 | 0.00 | 0.00 | 01-OCT-00:10 | 12.20 | 11.16 |
November | 0.192057E+10 | 6135.42 | 06-NOV-06:15 | 11.47 | 8.44 | 0.00 | 0.00 | 01-NOV-00:10 | 11.47 | 8.44 |
December | 0.123395E+10 | 3650.48 | 06-DEC-06:10 | -0.5 | -0.5 | 0.00 | 0.00 | 01-DEC-00:10 | -0.5 | -0.5 |
Annual Sum or Average | 0.428285E+11 | 0.00 | ||||||||
Minimum of Months | 0.776958E+09 | 2663.54 | -0.5 | -0.5 | 0.00 | 0.00 | -0.5 | -0.5 | ||
Maximum of Months | 0.743304E+10 | 9249.94 | 27.20 | 16.90 | 0.00 | 0.00 | 27.20 | 16.90 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146075E+09 | 3888.24 | 17-JAN-05:01 | 1.60 | 0.13 | 0.00 | 0.00 | 01-JAN-00:10 | 1.60 | 0.13 |
February | 0.438794E+09 | 3389.93 | 18-FEB-05:01 | -1.2 | -2.4 | 0.00 | 0.00 | 01-FEB-00:10 | -1.2 | -2.4 |
March | 0.100676E+10 | 2700.82 | 06-MAR-06:01 | 6.70 | 6.18 | 0.00 | 0.00 | 01-MAR-00:10 | 6.70 | 6.18 |
April | 0.147924E+10 | 3855.69 | 29-APR-05:10 | 8.40 | 8.40 | 0.00 | 0.00 | 01-APR-00:10 | 8.40 | 8.40 |
May | 0.258688E+10 | 4107.44 | 06-MAY-05:10 | 13.07 | 11.42 | 0.00 | 0.00 | 01-MAY-00:10 | 13.07 | 11.42 |
June | 0.339064E+10 | 4311.50 | 12-JUN-05:15 | 14.40 | 13.42 | 0.00 | 0.00 | 01-JUN-00:10 | 14.40 | 13.42 |
July | 0.425268E+10 | 4760.96 | 31-JUL-15:20 | 28.50 | 19.00 | 0.00 | 0.00 | 01-JUL-00:10 | 28.50 | 19.00 |
August | 0.485557E+10 | 5593.76 | 10-AUG-15:10 | 30.37 | 18.88 | 0.00 | 0.00 | 01-AUG-00:10 | 30.37 | 18.88 |
September | 0.313353E+10 | 4642.67 | 14-SEP-15:10 | 23.98 | 16.97 | 0.00 | 0.00 | 01-SEP-00:10 | 23.98 | 16.97 |
October | 0.160039E+10 | 3912.88 | 05-OCT-05:10 | 8.30 | 5.23 | 0.00 | 0.00 | 01-OCT-00:10 | 8.30 | 5.23 |
November | 0.682671E+09 | 3798.35 | 13-NOV-06:01 | 1.70 | 1.50 | 0.00 | 0.00 | 01-NOV-00:10 | 1.70 | 1.50 |
December | 0.336115E+09 | 4178.99 | 09-DEC-06:02 | 0.87 | 0.59 | 0.00 | 0.00 | 01-DEC-00:10 | 0.87 | 0.59 |
Annual Sum or Average | 0.239093E+11 | 0.00 | ||||||||
Minimum of Months | 0.146075E+09 | 2700.82 | -1.2 | -2.4 | 0.00 | 0.00 | -1.2 | -2.4 | ||
Maximum of Months | 0.485557E+10 | 5593.76 | 30.37 | 19.00 | 0.00 | 0.00 | 30.37 | 19.00 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 | 4.99 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 69720980.10 | 1720.84 | 27-FEB-15:40 | 19.60 | 12.34 | 0.00 | 0.00 | 01-FEB-00:10 | 19.60 | 12.34 |
March | 0.500485E+09 | 3766.95 | 18-MAR-15:02 | 20.10 | 10.35 | 0.00 | 0.00 | 01-MAR-00:10 | 20.10 | 10.35 |
April | 0.222597E+10 | 13434.55 | 27-APR-14:20 | 26.47 | 16.98 | 0.00 | 0.00 | 01-APR-00:10 | 26.47 | 16.98 |
May | 0.440374E+10 | 14060.01 | 15-MAY-14:20 | 23.30 | 13.21 | 0.00 | 0.00 | 01-MAY-00:10 | 23.30 | 13.21 |
June | 0.601781E+10 | 14600.56 | 28-JUN-14:20 | 25.37 | 15.62 | 0.00 | 0.00 | 01-JUN-00:10 | 25.37 | 15.62 |
July | 0.801381E+10 | 16065.69 | 24-JUL-14:00 | 29.40 | 18.12 | 0.00 | 0.00 | 01-JUL-00:10 | 29.40 | 18.12 |
August | 0.778588E+10 | 17035.78 | 10-AUG-14:40 | 29.93 | 18.99 | 0.00 | 0.00 | 01-AUG-00:10 | 29.93 | 18.99 |
September | 0.375966E+10 | 12394.27 | 14-SEP-15:00 | 23.90 | 16.96 | 0.00 | 0.00 | 01-SEP-00:10 | 23.90 | 16.96 |
October | 0.832099E+09 | 7214.62 | 04-OCT-14:50 | 21.60 | 11.48 | 0.00 | 0.00 | 01-OCT-00:10 | 21.60 | 11.48 |
November | 58856219.26 | 3137.25 | 04-NOV-15:02 | 20.92 | 15.94 | 0.00 | 0.00 | 01-NOV-00:10 | 20.92 | 15.94 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.336680E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.801381E+10 | 17035.78 | 29.93 | 18.99 | 0.00 | 0.00 | 29.93 | 18.99 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.282151E+10 | 1792.41 | 05-JAN-16:10 | 5.73 | 4.38 | 95230014.34 | 126.82 | 02-JAN-10:09 | 5.73 | 4.38 |
February | 0.768176E+10 | 3869.66 | 07-FEB-16:50 | 7.30 | 3.84 | 86397227.21 | 126.83 | 24-FEB-10:00 | 13.30 | 12.07 |
March | 0.141205E+11 | 6976.79 | 31-MAR-24:00 | 8.00 | 7.45 | 0.103237E+09 | 126.83 | 09-MAR-14:00 | 8.00 | 7.45 |
April | 0.187630E+11 | 7946.70 | 26-APR-17:50 | 23.07 | 13.57 | 91605373.16 | 126.83 | 28-APR-13:09 | 16.97 | 14.14 |
May | 0.423547E+10 | 3434.30 | 31-MAY-24:00 | 13.00 | 10.11 | 99236138.07 | 126.84 | 31-MAY-13:00 | 13.00 | 10.11 |
June | 0.916490E+10 | 5312.61 | 30-JUN-24:00 | 15.50 | 12.58 | 98961089.99 | 126.84 | 12-JUN-13:00 | 15.50 | 12.58 |
July | 0.146525E+11 | 7222.26 | 31-JUL-23:43 | 17.63 | 14.21 | 91885051.81 | 126.84 | 11-JUL-09:50 | 17.63 | 14.21 |
August | 0.196244E+11 | 8386.69 | 06-AUG-18:22 | 22.80 | 15.13 | 0.103239E+09 | 126.83 | 31-AUG-09:09 | 15.72 | 14.84 |
September | 0.417251E+10 | 3300.64 | 30-SEP-24:00 | 14.30 | 12.32 | 91612086.59 | 126.84 | 13-SEP-13:00 | 14.30 | 12.32 |
October | 0.911722E+10 | 5008.08 | 31-OCT-24:00 | 9.10 | 7.85 | 95231790.82 | 126.83 | 26-OCT-13:00 | 9.10 | 7.85 |
November | 0.135310E+11 | 5647.50 | 12-NOV-15:53 | 5.00 | 4.02 | 94301383.47 | 126.83 | 01-NOV-13:00 | 5.00 | 4.02 |
December | 0.189135E+11 | 7595.86 | 05-DEC-15:50 | 6.75 | 4.97 | 91880917.39 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.136798E+12 | 0.114282E+10 | ||||||||
Minimum of Months | 0.282151E+10 | 1792.41 | 5.00 | 3.84 | 86397227.21 | 126.82 | 5.00 | 4.02 | ||
Maximum of Months | 0.196244E+11 | 8386.69 | 23.07 | 15.13 | 0.103239E+09 | 126.84 | 17.63 | 14.84 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.516598E+09 | 1212.43 | 05-JAN-16:20 | 5.37 | 4.14 | 94963125.67 | 126.82 | 18-JAN-14:00 | 4.40 | 2.53 |
February | 0.545239E+10 | 3493.36 | 08-FEB-17:00 | 6.70 | 3.26 | 86397177.21 | 126.83 | 24-FEB-10:00 | 13.30 | 12.07 |
March | 0.120370E+11 | 6118.70 | 31-MAR-24:00 | 8.00 | 7.45 | 0.103237E+09 | 126.83 | 09-MAR-14:00 | 8.00 | 7.45 |
April | 0.170429E+11 | 7539.27 | 26-APR-17:50 | 23.07 | 13.57 | 91605390.69 | 126.83 | 28-APR-13:09 | 16.97 | 14.14 |
May | 0.343934E+10 | 3177.48 | 31-MAY-24:00 | 13.00 | 10.11 | 99235959.64 | 126.84 | 31-MAY-13:00 | 13.00 | 10.11 |
June | 0.831611E+10 | 4967.57 | 30-JUN-24:00 | 15.50 | 12.58 | 98960860.74 | 126.84 | 12-JUN-13:00 | 15.50 | 12.58 |
July | 0.137532E+11 | 6976.71 | 31-JUL-23:57 | 17.40 | 14.08 | 91884816.46 | 126.84 | 11-JUL-09:50 | 17.40 | 14.08 |
August | 0.185543E+11 | 7799.82 | 06-AUG-18:23 | 22.80 | 15.13 | 0.103239E+09 | 126.83 | 31-AUG-09:30 | 15.75 | 14.73 |
September | 0.343210E+10 | 2898.70 | 30-SEP-24:00 | 14.30 | 12.32 | 91611634.00 | 126.84 | 14-SEP-13:50 | 14.30 | 12.32 |
October | 0.748918E+10 | 4144.15 | 31-OCT-24:00 | 9.10 | 7.85 | 95231690.41 | 126.83 | 26-OCT-13:00 | 9.10 | 7.85 |
November | 0.110241E+11 | 5179.60 | 10-NOV-16:10 | 8.53 | 6.27 | 94301323.02 | 126.83 | 01-NOV-13:00 | 8.53 | 6.27 |
December | 0.155455E+11 | 6957.69 | 05-DEC-16:00 | 6.10 | 4.53 | 91880938.28 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.116603E+12 | 0.114255E+10 | ||||||||
Minimum of Months | 0.516598E+09 | 1212.43 | 5.37 | 3.26 | 86397177.21 | 126.82 | 4.40 | 2.53 | ||
Maximum of Months | 0.185543E+11 | 7799.82 | 23.07 | 15.13 | 0.103239E+09 | 126.84 | 17.40 | 14.73 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135303E+09 | 1005.21 | 05-JAN-16:20 | 5.37 | 4.14 | 92617718.66 | 128.01 | 03-JAN-10:00 | 5.37 | 4.14 |
February | 0.381639E+10 | 3346.07 | 27-FEB-16:30 | 19.15 | 12.30 | 86397238.57 | 126.83 | 24-FEB-10:00 | 19.15 | 12.30 |
March | 0.105039E+11 | 5497.55 | 31-MAR-23:30 | 8.15 | 7.59 | 0.103237E+09 | 126.83 | 09-MAR-14:00 | 8.15 | 7.59 |
April | 0.161163E+11 | 7603.14 | 26-APR-17:50 | 23.07 | 13.57 | 91605416.79 | 126.83 | 28-APR-13:09 | 16.97 | 14.14 |
May | 0.285556E+10 | 3097.45 | 31-MAY-23:40 | 13.33 | 10.48 | 99235982.26 | 126.84 | 31-MAY-13:00 | 13.33 | 10.48 |
June | 0.805810E+10 | 4868.90 | 30-JUN-23:50 | 15.57 | 12.69 | 98960888.88 | 126.84 | 12-JUN-13:00 | 15.57 | 12.69 |
July | 0.136235E+11 | 6969.24 | 31-JUL-23:57 | 17.40 | 14.08 | 91884957.10 | 126.84 | 11-JUL-09:50 | 17.40 | 14.08 |
August | 0.183754E+11 | 7928.32 | 06-AUG-18:12 | 23.13 | 15.18 | 0.103239E+09 | 126.83 | 30-AUG-09:09 | 19.33 | 17.24 |
September | 0.282222E+10 | 2464.97 | 30-SEP-23:30 | 14.15 | 12.18 | 91610737.46 | 126.84 | 14-SEP-13:50 | 14.15 | 12.18 |
October | 0.612130E+10 | 3894.86 | 04-OCT-16:50 | 20.68 | 11.37 | 95231632.72 | 126.83 | 26-OCT-13:00 | 13.30 | 12.35 |
November | 0.924761E+10 | 4907.60 | 04-NOV-16:05 | 19.82 | 15.68 | 94301346.62 | 126.83 | 01-NOV-13:00 | 19.82 | 15.68 |
December | 0.136022E+11 | 6651.96 | 05-DEC-16:00 | 6.10 | 4.53 | 91880949.74 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.105278E+12 | 0.114020E+10 | ||||||||
Minimum of Months | 0.135303E+09 | 1005.21 | 5.37 | 4.14 | 86397238.57 | 126.82 | 5.37 | 4.14 | ||
Maximum of Months | 0.183754E+11 | 7928.32 | 23.13 | 15.68 | 0.103239E+09 | 128.01 | 19.82 | 17.24 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235463E+12 | 90325.17 | 03-JAN-17:00 | 7.20 | 6.66 | 0.206144E+10 | 2745.29 | 03-JAN-14:20 | 7.20 | 6.66 |
February | 0.434014E+12 | 182581.73 | 27-FEB-17:00 | 18.90 | 12.17 | 0.187022E+10 | 2745.29 | 24-FEB-14:30 | 18.90 | 12.17 |
March | 0.727988E+12 | 358022.16 | 31-MAR-24:00 | 8.00 | 7.45 | 0.223475E+10 | 2745.29 | 06-MAR-10:20 | 8.00 | 7.45 |
April | 0.942051E+12 | 366550.38 | 27-APR-16:00 | 27.20 | 16.90 | 0.198297E+10 | 2745.29 | 20-APR-13:20 | 27.20 | 16.90 |
May | 0.239743E+12 | 175694.73 | 31-MAY-24:00 | 13.00 | 10.11 | 0.214810E+10 | 2745.29 | 03-MAY-09:39 | 13.00 | 10.11 |
June | 0.469006E+12 | 267277.08 | 30-JUN-24:00 | 15.50 | 12.58 | 0.214213E+10 | 2745.29 | 19-JUN-13:39 | 15.50 | 12.58 |
July | 0.730835E+12 | 359776.53 | 31-JUL-24:00 | 17.40 | 14.08 | 0.198894E+10 | 2745.29 | 03-JUL-13:09 | 17.40 | 14.08 |
August | 0.976179E+12 | 367399.68 | 14-AUG-16:00 | 27.50 | 16.95 | 0.223475E+10 | 2745.29 | 01-AUG-13:20 | 27.50 | 16.95 |
September | 0.233632E+12 | 175319.16 | 30-SEP-24:00 | 14.30 | 12.32 | 0.198297E+10 | 2745.29 | 13-SEP-09:20 | 14.30 | 12.32 |
October | 0.484666E+12 | 266819.33 | 31-OCT-24:00 | 9.10 | 7.85 | 0.206144E+10 | 2745.29 | 04-OCT-13:30 | 9.10 | 7.85 |
November | 0.705700E+12 | 275155.34 | 06-NOV-15:00 | 11.10 | 10.22 | 0.204131E+10 | 2745.29 | 03-NOV-13:39 | 11.10 | 10.22 |
December | 0.973706E+12 | 366468.61 | 04-DEC-17:00 | 6.70 | 4.39 | 0.198894E+10 | 2745.29 | 07-DEC-10:09 | 8.40 | 4.67 |
Annual Sum or Average | 0.715298E+13 | 0.247380E+11 | ||||||||
Minimum of Months | 0.233632E+12 | 90325.17 | 6.70 | 4.39 | 0.187022E+10 | 2745.29 | 7.20 | 4.67 | ||
Maximum of Months | 0.976179E+12 | 367399.68 | 27.50 | 16.95 | 0.223475E+10 | 2745.29 | 27.50 | 16.95 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215054E+09 | 9746.38 | 11-JAN-05:04 | 10.00 |
February | 0.108601E+09 | 10003.94 | 25-FEB-05:15 | 10.77 |
March | 0.148370E+09 | 10120.49 | 20-MAR-03:07 | 6.10 |
April | 0.200979E+09 | 9911.85 | 01-APR-04:05 | 6.78 |
May | 0.224182E+09 | 9966.48 | 03-MAY-04:07 | 7.88 |
June | 0.278639E+09 | 9804.75 | 24-JUN-04:07 | 12.80 |
July | 0.298680E+09 | 9871.41 | 05-JUL-03:10 | 11.10 |
August | 0.304269E+09 | 11062.15 | 13-AUG-20:43 | 23.15 |
September | 0.483076E+09 | 11542.62 | 04-SEP-15:23 | 17.50 |
October | 0.405271E+09 | 11833.36 | 09-OCT-15:53 | 18.30 |
November | 0.357120E+09 | 11072.83 | 12-NOV-15:53 | 5.00 |
December | 0.107672E+09 | 9894.24 | 20-DEC-05:05 | 4.68 |
Annual Sum or Average | 0.313191E+10 | |||
Minimum of Months | 0.107672E+09 | 9746.38 | 4.68 | |
Maximum of Months | 0.483076E+09 | 11833.36 | 23.15 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212126E+09 | 32322.38 | 02-JAN-05:01 | 6.10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 3894648.98 | 25964.33 | 26-DEC-06:03 | -0.8 |
Annual Sum or Average | 0.216021E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.212126E+09 | 32322.38 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296578E+10 | 68402.80 | 17-JAN-04:01 | 1.70 |
February | 0.122072E+10 | 65671.13 | 21-FEB-04:01 | 1.70 |
March | 0.261114E+09 | 60988.98 | 06-MAR-05:01 | 6.70 |
April | 288954.39 | 1926.36 | 18-APR-05:03 | 3.30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 54207927.50 | 55697.76 | 16-OCT-05:03 | 7.12 |
November | 0.819633E+09 | 62421.28 | 13-NOV-05:01 | 1.20 |
December | 0.169290E+10 | 66792.65 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.701464E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.296578E+10 | 68402.80 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 257310.92 | 1590.70 | 17-JAN-06:01 | 1.20 |
February | 38558.30 | 354.55 | 14-FEB-06:04 | -0.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 295869.23 | |||
Minimum of Months | 0.00 | 0.00 | -0.4 | |
Maximum of Months | 257310.92 | 1590.70 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30049562.40 | 9841.43 | 17-JAN-05:01 | 1.60 |
February | 3711514.48 | 7101.79 | 18-FEB-06:01 | -1.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 3091362.71 | 6701.58 | 26-DEC-06:03 | -0.8 |
Annual Sum or Average | 36852439.59 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 30049562.40 | 9841.43 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128311E+10 | 9673.09 | 02-JAN-04:01 | 6.60 |
February | 0.464224E+09 | 8909.28 | 21-FEB-05:01 | 1.70 |
March | 42236165.24 | 8148.71 | 06-MAR-06:01 | 6.70 |
April | 679054.44 | 2598.39 | 19-APR-05:03 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 5547065.74 | 7194.48 | 30-OCT-05:03 | 7.20 |
November | 0.178682E+09 | 8312.20 | 13-NOV-05:01 | 1.20 |
December | 0.724459E+09 | 9148.48 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.269894E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.128311E+10 | 9673.09 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.844966E+09 | 12437.20 | 02-JAN-04:01 | 6.60 |
February | 0.276264E+09 | 11292.39 | 21-FEB-05:01 | 1.70 |
March | 25459177.30 | 10034.12 | 06-MAR-06:01 | 6.70 |
April | 1549022.78 | 2347.30 | 19-APR-05:03 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 3302620.19 | 4467.14 | 31-OCT-05:03 | 8.58 |
November | 0.130680E+09 | 10274.40 | 13-NOV-05:01 | 1.20 |
December | 0.526585E+09 | 11753.04 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.180881E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.844966E+09 | 12437.20 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.813248E+09 | 17888.07 | 02-JAN-04:01 | 6.60 |
February | 0.217816E+09 | 15593.06 | 21-FEB-05:01 | 1.70 |
March | 15546182.01 | 14468.96 | 06-MAR-06:01 | 6.70 |
April | 83333.75 | 362.94 | 18-APR-05:03 | 3.30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 278854.26 | 2189.60 | 28-OCT-05:02 | 8.22 |
November | 0.109600E+09 | 14535.40 | 24-NOV-06:01 | 2.02 |
December | 0.506805E+09 | 16776.79 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.166338E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.813248E+09 | 17888.07 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.437568E+09 | 11185.48 | 02-JAN-04:01 | 6.60 |
February | 0.122768E+09 | 9918.07 | 21-FEB-05:01 | 1.70 |
March | 3626316.91 | 8949.54 | 06-MAR-06:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 31775.68 | 211.84 | 31-OCT-05:05 | 8.58 |
November | 40616743.33 | 9240.81 | 24-NOV-06:01 | 2.02 |
December | 0.198012E+09 | 10643.07 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.802623E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.437568E+09 | 11185.48 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.428306E+10 | 11408.05 | 16-JAN-07:23 | -1.4 |
February | 0.257708E+10 | 11361.93 | 20-FEB-05:33 | -0.6 |
March | 0.991380E+09 | 10961.79 | 06-MAR-04:01 | 6.70 |
April | 0.267485E+09 | 9589.99 | 18-APR-04:02 | 2.88 |
May | 11521616.97 | 9060.30 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 12649751.39 | 8895.02 | 27-SEP-05:03 | 7.38 |
October | 0.424519E+09 | 10075.23 | 30-OCT-04:01 | 7.20 |
November | 0.172570E+10 | 11344.24 | 13-NOV-04:01 | 1.60 |
December | 0.355261E+10 | 11286.24 | 18-DEC-04:01 | 2.38 |
Annual Sum or Average | 0.138460E+11 | |||
Minimum of Months | 0.00 | 0.00 | -1.4 | |
Maximum of Months | 0.428306E+10 | 11408.05 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265800E+10 | 15343.93 | 17-JAN-04:01 | 1.70 |
February | 0.144116E+10 | 15225.86 | 21-FEB-04:01 | 1.70 |
March | 0.525918E+09 | 14447.43 | 06-MAR-04:01 | 6.70 |
April | 0.130861E+09 | 12499.49 | 18-APR-04:02 | 2.88 |
May | 9870439.14 | 11818.03 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 8016060.93 | 8104.11 | 27-SEP-05:03 | 7.38 |
October | 0.252503E+09 | 13017.94 | 16-OCT-04:01 | 7.20 |
November | 0.107034E+10 | 15097.61 | 13-NOV-04:01 | 1.60 |
December | 0.220455E+10 | 14982.11 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.830122E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.265800E+10 | 15343.93 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.299480E+10 | 22869.96 | 17-JAN-04:01 | 1.70 |
February | 0.147500E+10 | 22598.48 | 21-FEB-04:01 | 1.70 |
March | 0.608641E+09 | 21362.95 | 06-MAR-04:01 | 6.70 |
April | 0.192939E+09 | 18654.26 | 18-APR-04:02 | 2.88 |
May | 13473031.78 | 17737.49 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 8446776.45 | 8754.56 | 27-SEP-05:03 | 7.38 |
October | 0.256997E+09 | 19077.52 | 16-OCT-04:01 | 7.20 |
November | 0.123245E+10 | 21418.48 | 13-NOV-04:01 | 1.60 |
December | 0.254944E+10 | 22381.12 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.933218E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.299480E+10 | 22869.96 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179967E+10 | 15523.68 | 17-JAN-04:01 | 1.70 |
February | 0.827196E+09 | 15083.95 | 21-FEB-04:01 | 1.70 |
March | 0.286593E+09 | 13363.07 | 06-MAR-05:01 | 6.70 |
April | 64289484.65 | 10383.99 | 12-APR-05:02 | 3.80 |
May | 4792454.01 | 9865.52 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 69742.85 | 289.78 | 27-SEP-05:05 | 7.38 |
October | 0.107813E+09 | 11127.53 | 16-OCT-04:01 | 7.20 |
November | 0.581595E+09 | 13486.13 | 13-NOV-05:01 | 1.20 |
December | 0.126218E+10 | 15185.43 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.493420E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.179967E+10 | 15523.68 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.390453E+09 | 8945.08 | 02-JAN-05:01 | 6.10 |
February | 0.121095E+09 | 9879.41 | 21-FEB-06:01 | 1.70 |
March | 73420870.82 | 9537.02 | 06-MAR-05:01 | 6.70 |
April | 0.129688E+09 | 10079.00 | 10-APR-03:02 | 10.50 |
May | 76393016.12 | 8456.18 | 01-MAY-03:02 | 11.78 |
June | 74352198.43 | 7460.95 | 12-JUN-03:02 | 15.00 |
July | 0.113320E+09 | 8744.12 | 17-JUL-03:02 | 14.90 |
August | 0.104778E+09 | 8800.03 | 04-AUG-03:02 | 13.92 |
September | 57620405.48 | 6524.28 | 05-SEP-03:02 | 11.70 |
October | 79922838.12 | 8637.49 | 30-OCT-04:01 | 7.20 |
November | 73582694.63 | 10463.35 | 27-NOV-05:01 | 12.12 |
December | 81785667.63 | 11107.64 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.137641E+10 | |||
Minimum of Months | 57620405.48 | 6524.28 | -0.6 | |
Maximum of Months | 0.390453E+09 | 11107.64 | 15.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217183E+10 | 11340.63 | 02-JAN-06:13 | 6.10 |
February | 0.109102E+10 | 8473.35 | 12-FEB-14:02 | 6.70 |
March | 0.485475E+09 | 5157.07 | 29-MAR-05:03 | 4.40 |
April | 0.107474E+09 | 5210.63 | 10-APR-05:03 | 8.80 |
May | 47877259.61 | 7454.07 | 14-MAY-14:52 | 23.30 |
June | 39564553.20 | 4391.43 | 08-JUN-05:03 | 10.18 |
July | 55116416.87 | 6423.81 | 30-JUL-14:52 | 27.20 |
August | 40460240.66 | 7953.88 | 06-AUG-15:21 | 23.75 |
September | 38196406.57 | 7592.69 | 10-SEP-15:12 | 22.60 |
October | 0.196163E+09 | 5533.12 | 08-OCT-13:02 | 18.17 |
November | 0.621145E+09 | 5230.62 | 03-NOV-05:03 | 10.60 |
December | 0.122117E+10 | 4076.85 | 03-DEC-13:10 | 12.20 |
Annual Sum or Average | 0.611549E+10 | |||
Minimum of Months | 38196406.57 | 4076.85 | 4.40 | |
Maximum of Months | 0.217183E+10 | 11340.63 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.750682E+10 | 20146.10 | 09-JAN-06:13 | -1.3 |
February | 0.464405E+10 | 17972.90 | 21-FEB-06:13 | 1.70 |
March | 0.264578E+10 | 13681.48 | 06-MAR-06:13 | 6.70 |
April | 0.118234E+10 | 11872.00 | 27-APR-05:02 | 9.37 |
May | 0.534384E+09 | 12375.01 | 04-MAY-05:02 | 10.78 |
June | 0.241105E+09 | 12278.71 | 19-JUN-05:03 | 11.20 |
July | 0.132309E+09 | 11753.36 | 07-JUL-05:02 | 11.47 |
August | 0.178560E+09 | 11649.66 | 21-AUG-05:03 | 11.20 |
September | 0.527423E+09 | 12116.62 | 08-SEP-05:02 | 10.18 |
October | 0.172715E+10 | 7039.81 | 05-OCT-05:02 | 8.30 |
November | 0.386085E+10 | 16432.81 | 13-NOV-06:13 | 1.70 |
December | 0.642457E+10 | 19666.00 | 26-DEC-05:12 | -0.6 |
Annual Sum or Average | 0.296053E+11 | |||
Minimum of Months | 0.132309E+09 | 7039.81 | -1.3 | |
Maximum of Months | 0.750682E+10 | 20146.10 | 11.47 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.273006E+09 | 531.24 | 17-JAN-04:42 | 1.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.273006E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.70 | |
Maximum of Months | 0.273006E+09 | 531.24 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.780298E+09 | 581.58 | 08-JAN-17:50 | 3.12 |
February | 19471680.60 | 386.86 | 20-FEB-07:50 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 329514.28 | 366.46 | 29-MAY-06:55 | 10.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.800099E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.780298E+09 | 581.58 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113123E+11 | 11837.83 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.102611E+11 | 11837.83 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.121930E+11 | 11837.83 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.108909E+11 | 11837.83 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.117527E+11 | 11837.83 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.116958E+11 | 11837.83 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.109477E+11 | 11837.83 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.121930E+11 | 11837.83 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.108909E+11 | 11837.83 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.113123E+11 | 11837.83 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.111797E+11 | 11837.83 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.109477E+11 | 11837.83 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.135577E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.102611E+11 | 11837.83 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.121930E+11 | 11837.83 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.921110E+09 | 1334.85 | 02-JAN-16:30 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.750457E+09 | 1231.60 | 02-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.811296E+09 | 1106.67 | 22-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.680988E+09 | 929.33 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.711615E+09 | 713.68 | 17-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.693302E+09 | 696.80 | 16-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.655123E+09 | 892.87 | 12-JUL-08:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.741053E+09 | 837.18 | 02-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.706499E+09 | 1113.43 | 25-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.800666E+09 | 1320.66 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.887518E+09 | 1334.85 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.924362E+09 | 1334.85 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.928399E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.655123E+09 | 696.80 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.924362E+09 | 1334.85 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.570406E+09 | 860.23 | 02-JAN-16:30 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.472761E+09 | 801.13 | 02-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.517292E+09 | 690.10 | 22-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.438772E+09 | 472.50 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.461245E+09 | 443.38 | 05-MAY-14:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.450382E+09 | 440.43 | 08-JUN-15:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.425072E+09 | 457.20 | 12-JUL-08:30 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.480451E+09 | 471.48 | 02-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.450494E+09 | 695.88 | 25-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.504135E+09 | 848.90 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.553391E+09 | 860.23 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.569694E+09 | 860.23 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.589409E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.425072E+09 | 440.43 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.570406E+09 | 860.23 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.856951E+09 | 1334.88 | 02-JAN-16:30 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.711269E+09 | 1207.99 | 02-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.793762E+09 | 1096.52 | 22-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.680439E+09 | 914.91 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.715834E+09 | 714.80 | 17-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.699408E+09 | 702.59 | 29-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.663569E+09 | 861.46 | 12-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.746062E+09 | 827.79 | 02-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.699067E+09 | 1105.77 | 25-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.768005E+09 | 1318.04 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.833851E+09 | 1334.88 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.850188E+09 | 1334.88 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.901840E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.663569E+09 | 702.59 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.856951E+09 | 1334.88 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.569910E+09 | 860.23 | 02-JAN-16:30 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.468420E+09 | 776.73 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.517573E+09 | 723.40 | 22-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.439355E+09 | 635.90 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.460217E+09 | 471.38 | 17-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.448653E+09 | 464.90 | 29-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.426178E+09 | 652.93 | 12-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.479394E+09 | 650.05 | 28-AUG-07:30 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.455127E+09 | 726.69 | 25-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.505602E+09 | 851.35 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.552444E+09 | 860.23 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.569467E+09 | 860.23 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.589234E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.426178E+09 | 464.90 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.569910E+09 | 860.23 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.921913E+09 | 1334.85 | 02-JAN-16:30 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.751082E+09 | 1233.90 | 02-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.810985E+09 | 1111.71 | 22-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.680941E+09 | 938.03 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.711669E+09 | 711.05 | 17-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.692925E+09 | 693.79 | 16-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.654594E+09 | 900.57 | 12-JUL-08:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.740640E+09 | 847.83 | 02-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.706554E+09 | 1118.26 | 25-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.801132E+09 | 1320.96 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.888357E+09 | 1334.85 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.926479E+09 | 1334.85 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.928727E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.654594E+09 | 693.79 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.926479E+09 | 1334.85 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.570452E+09 | 860.23 | 02-JAN-16:30 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.472389E+09 | 801.29 | 02-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.517155E+09 | 691.25 | 22-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.438616E+09 | 471.34 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.461161E+09 | 440.71 | 05-MAY-14:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.450292E+09 | 437.36 | 08-JUN-15:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.425000E+09 | 455.41 | 12-JUL-08:30 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.480438E+09 | 470.06 | 02-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.450326E+09 | 696.95 | 25-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.503976E+09 | 848.98 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.553347E+09 | 860.23 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.569565E+09 | 860.23 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.589272E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.425000E+09 | 437.36 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.570452E+09 | 860.23 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.858999E+09 | 1334.88 | 02-JAN-16:30 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.711028E+09 | 1210.98 | 02-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.794103E+09 | 1101.92 | 22-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.680487E+09 | 924.04 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.715968E+09 | 712.17 | 17-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.699551E+09 | 699.65 | 29-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.663650E+09 | 870.11 | 12-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.746315E+09 | 838.68 | 02-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.699184E+09 | 1110.85 | 25-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.769033E+09 | 1318.45 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.834689E+09 | 1334.88 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.851233E+09 | 1334.88 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.902424E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.663650E+09 | 699.65 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.858999E+09 | 1334.88 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.569860E+09 | 860.23 | 02-JAN-16:30 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.468228E+09 | 776.94 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.517179E+09 | 723.70 | 22-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.439304E+09 | 636.34 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.459966E+09 | 469.62 | 17-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.448552E+09 | 462.95 | 29-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.426128E+09 | 652.98 | 12-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.479211E+09 | 650.19 | 28-AUG-07:30 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.454894E+09 | 726.98 | 25-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.505327E+09 | 851.38 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.552296E+09 | 860.23 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.569359E+09 | 860.23 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.589031E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.426128E+09 | 462.95 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.569860E+09 | 860.23 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.921735E+09 | 1334.85 | 02-JAN-16:30 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.751028E+09 | 1233.81 | 02-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.810868E+09 | 1111.46 | 22-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.680914E+09 | 937.65 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.711621E+09 | 710.85 | 17-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.692916E+09 | 693.56 | 16-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.654585E+09 | 900.18 | 12-JUL-08:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.740593E+09 | 847.29 | 02-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.706521E+09 | 1118.02 | 25-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.801066E+09 | 1320.94 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.888232E+09 | 1334.85 | 06-NOV-16:49 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.926351E+09 | 1334.85 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.928643E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.654585E+09 | 693.56 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.926351E+09 | 1334.85 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.570417E+09 | 860.23 | 02-JAN-16:30 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.472341E+09 | 801.23 | 02-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.517112E+09 | 691.12 | 22-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.438597E+09 | 471.25 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.461152E+09 | 440.56 | 05-MAY-14:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.450281E+09 | 437.24 | 08-JUN-15:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.424999E+09 | 455.27 | 12-JUL-08:30 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.480434E+09 | 469.95 | 02-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.450299E+09 | 696.82 | 25-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.503953E+09 | 848.97 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.553295E+09 | 860.23 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.569533E+09 | 860.23 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.589241E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.424999E+09 | 437.24 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.570417E+09 | 860.23 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.858935E+09 | 1334.88 | 02-JAN-16:30 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.711055E+09 | 1210.90 | 02-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.794073E+09 | 1101.68 | 22-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.680471E+09 | 923.65 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.715952E+09 | 711.98 | 17-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.699536E+09 | 699.43 | 29-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.663622E+09 | 869.77 | 12-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.746304E+09 | 838.14 | 02-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.699160E+09 | 1110.61 | 25-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.769007E+09 | 1318.43 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.834888E+09 | 1334.88 | 06-NOV-16:49 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.851194E+09 | 1334.88 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.902420E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.663622E+09 | 699.43 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.858935E+09 | 1334.88 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.569815E+09 | 860.23 | 02-JAN-16:30 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.468208E+09 | 776.85 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.517144E+09 | 723.55 | 22-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.439293E+09 | 636.11 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.459940E+09 | 469.52 | 17-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.448545E+09 | 462.83 | 29-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.426121E+09 | 652.81 | 12-JUL-07:30 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.479205E+09 | 650.12 | 28-AUG-07:30 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.454909E+09 | 726.83 | 25-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.505306E+09 | 851.37 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.552205E+09 | 860.23 | 06-NOV-16:49 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.569317E+09 | 860.23 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.589001E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.426121E+09 | 462.83 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.569815E+09 | 860.23 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.318958E+10 | 3337.76 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.289319E+10 | 3337.76 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.343791E+10 | 3337.76 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.307076E+10 | 3337.76 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.331375E+10 | 3337.76 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.329773E+10 | 3337.76 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.308678E+10 | 3337.76 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.343791E+10 | 3337.76 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.307076E+10 | 3337.76 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.318958E+10 | 3337.76 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.315220E+10 | 3337.76 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.308678E+10 | 3337.76 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.382269E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.289319E+10 | 3337.76 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.343791E+10 | 3337.76 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.113123E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.102611E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.108909E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.117527E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.116958E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.109477E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.108909E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.113123E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.111797E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.109477E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.135577E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.102611E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.921110E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203981E+09 |
February | 0.136985E+10 | 0.750457E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181985E+09 |
March | 0.163685E+10 | 0.811296E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175138E+09 |
April | 0.145243E+10 | 0.680988E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 249431.46 | 0.165161E+09 |
May | 0.157338E+10 | 0.711615E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9612.94 | 0.126057E+09 |
June | 0.156900E+10 | 0.693302E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96594.78 | 0.104292E+09 |
July | 0.145680E+10 | 0.655123E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1408241.61 | 85322417.63 |
August | 0.163685E+10 | 0.741053E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2127470.14 | 68920368.90 |
September | 0.145243E+10 | 0.706499E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9579.37 | 58708076.71 |
October | 0.150991E+10 | 0.800666E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140118E+09 |
November | 0.149516E+10 | 0.887518E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163136E+09 |
December | 0.145680E+10 | 0.924362E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178302E+09 |
Annual Sum or Average | 0.181194E+11 | 0.928399E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3900930.29 | 0.165112E+10 |
Minimum of Months | 0.136985E+10 | 0.655123E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58708076.71 |
Maximum of Months | 0.163685E+10 | 0.924362E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2127470.14 | 0.203981E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.570406E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133404E+09 |
February | 0.882782E+09 | 0.472761E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119540E+09 |
March | 0.105485E+10 | 0.517292E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113904E+09 |
April | 0.936002E+09 | 0.438772E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 186903.96 | 0.107012E+09 |
May | 0.101394E+10 | 0.461245E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6408.35 | 83604791.88 |
June | 0.101113E+10 | 0.450382E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64395.02 | 68820510.66 |
July | 0.938820E+09 | 0.425072E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 803159.05 | 54642998.65 |
August | 0.105485E+10 | 0.480451E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1370007.11 | 43656523.42 |
September | 0.936002E+09 | 0.450494E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6385.85 | 38833931.88 |
October | 0.973041E+09 | 0.504135E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91168832.17 |
November | 0.963541E+09 | 0.553391E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104390E+09 |
December | 0.938820E+09 | 0.569694E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113833E+09 |
Annual Sum or Average | 0.116768E+11 | 0.589409E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2437259.34 | 0.107281E+10 |
Minimum of Months | 0.882782E+09 | 0.425072E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38833931.88 |
Maximum of Months | 0.105485E+10 | 0.570406E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1370007.11 | 0.133404E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.856951E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196176E+09 |
February | 0.136988E+10 | 0.711269E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181222E+09 |
March | 0.163688E+10 | 0.793762E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173046E+09 |
April | 0.145246E+10 | 0.680439E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 198033.95 | 0.163531E+09 |
May | 0.157341E+10 | 0.715834E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9611.54 | 0.126332E+09 |
June | 0.156904E+10 | 0.699408E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96589.96 | 0.104282E+09 |
July | 0.145684E+10 | 0.663569E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 910817.84 | 85548991.88 |
August | 0.163688E+10 | 0.746062E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1961748.24 | 69621573.17 |
September | 0.145246E+10 | 0.699067E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9554.61 | 60323737.09 |
October | 0.150994E+10 | 0.768005E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139770E+09 |
November | 0.149520E+10 | 0.833851E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156833E+09 |
December | 0.145684E+10 | 0.850188E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171473E+09 |
Annual Sum or Average | 0.181198E+11 | 0.901840E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3186356.14 | 0.162816E+10 |
Minimum of Months | 0.136988E+10 | 0.663569E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60323737.09 |
Maximum of Months | 0.163688E+10 | 0.856951E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1961748.24 | 0.196176E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.569910E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141932E+09 |
February | 0.882782E+09 | 0.468420E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131626E+09 |
March | 0.105485E+10 | 0.517573E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128826E+09 |
April | 0.936002E+09 | 0.439355E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80094.16 | 0.123580E+09 |
May | 0.101394E+10 | 0.460217E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6408.06 | 91161722.28 |
June | 0.101113E+10 | 0.448653E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64392.34 | 76973074.86 |
July | 0.938820E+09 | 0.426178E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 541166.92 | 65992564.78 |
August | 0.105485E+10 | 0.479394E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1298630.43 | 54390020.62 |
September | 0.936002E+09 | 0.455127E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6385.27 | 43357624.54 |
October | 0.973041E+09 | 0.505602E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102507E+09 |
November | 0.963541E+09 | 0.552444E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119745E+09 |
December | 0.938820E+09 | 0.569467E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133104E+09 |
Annual Sum or Average | 0.116768E+11 | 0.589234E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1997077.18 | 0.121320E+10 |
Minimum of Months | 0.882782E+09 | 0.426178E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43357624.54 |
Maximum of Months | 0.105485E+10 | 0.569910E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1298630.43 | 0.141932E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.921913E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403772E+09 |
February | 0.136985E+10 | 0.751082E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365547E+09 |
March | 0.163685E+10 | 0.810985E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359969E+09 |
April | 0.145243E+10 | 0.680941E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 913116.34 | 0.347994E+09 |
May | 0.157338E+10 | 0.711669E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16005.38 | 0.277741E+09 |
June | 0.156900E+10 | 0.692925E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 198954.74 | 0.231867E+09 |
July | 0.145680E+10 | 0.654594E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4042030.05 | 0.194449E+09 |
August | 0.163685E+10 | 0.740640E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5235583.02 | 0.158209E+09 |
September | 0.145243E+10 | 0.706554E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16784.48 | 0.127598E+09 |
October | 0.150991E+10 | 0.801132E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287492E+09 |
November | 0.149516E+10 | 0.888357E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322970E+09 |
December | 0.145680E+10 | 0.926479E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347604E+09 |
Annual Sum or Average | 0.181194E+11 | 0.928727E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10422474.00 | 0.342521E+10 |
Minimum of Months | 0.136985E+10 | 0.654594E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127598E+09 |
Maximum of Months | 0.163685E+10 | 0.926479E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5235583.02 | 0.403772E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.570452E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268826E+09 |
February | 0.649041E+09 | 0.472389E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247596E+09 |
March | 0.773965E+09 | 0.517155E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242968E+09 |
April | 0.688021E+09 | 0.438616E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 514321.61 | 0.237543E+09 |
May | 0.744847E+09 | 0.461161E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10665.58 | 0.188252E+09 |
June | 0.742030E+09 | 0.450292E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 132624.87 | 0.158909E+09 |
July | 0.690839E+09 | 0.425000E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1676983.61 | 0.131970E+09 |
August | 0.773965E+09 | 0.480438E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3051739.79 | 0.108803E+09 |
September | 0.688021E+09 | 0.450326E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11190.33 | 86788091.36 |
October | 0.715730E+09 | 0.503976E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193585E+09 |
November | 0.708685E+09 | 0.553347E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213940E+09 |
December | 0.690839E+09 | 0.569565E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231690E+09 |
Annual Sum or Average | 0.858171E+10 | 0.589272E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5397525.79 | 0.231087E+10 |
Minimum of Months | 0.649041E+09 | 0.425000E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86788091.36 |
Maximum of Months | 0.773965E+09 | 0.570452E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3051739.79 | 0.268826E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.858999E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420131E+09 |
February | 0.136988E+10 | 0.711028E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398556E+09 |
March | 0.163688E+10 | 0.794103E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384622E+09 |
April | 0.145246E+10 | 0.680487E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 454785.31 | 0.367299E+09 |
May | 0.157341E+10 | 0.715968E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16001.72 | 0.288478E+09 |
June | 0.156904E+10 | 0.699551E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 198939.60 | 0.238266E+09 |
July | 0.145684E+10 | 0.663650E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1978320.54 | 0.202323E+09 |
August | 0.163688E+10 | 0.746315E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4411588.58 | 0.168010E+09 |
September | 0.145246E+10 | 0.699184E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16637.16 | 0.138897E+09 |
October | 0.150994E+10 | 0.769033E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313002E+09 |
November | 0.149520E+10 | 0.834689E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337189E+09 |
December | 0.145684E+10 | 0.851233E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364611E+09 |
Annual Sum or Average | 0.181198E+11 | 0.902424E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7076272.91 | 0.362138E+10 |
Minimum of Months | 0.136988E+10 | 0.663650E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138897E+09 |
Maximum of Months | 0.163688E+10 | 0.858999E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4411588.58 | 0.420131E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.569860E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278873E+09 |
February | 0.882782E+09 | 0.468228E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256932E+09 |
March | 0.105485E+10 | 0.517179E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253388E+09 |
April | 0.936002E+09 | 0.439304E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 190365.30 | 0.247253E+09 |
May | 0.101394E+10 | 0.459966E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10669.26 | 0.199191E+09 |
June | 0.101113E+10 | 0.448552E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 132628.43 | 0.165163E+09 |
July | 0.938820E+09 | 0.426128E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1426890.98 | 0.145348E+09 |
August | 0.105485E+10 | 0.479211E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3038961.05 | 0.118240E+09 |
September | 0.936002E+09 | 0.454894E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11187.46 | 93628514.77 |
October | 0.973041E+09 | 0.505327E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202895E+09 |
November | 0.963541E+09 | 0.552296E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223005E+09 |
December | 0.938820E+09 | 0.569359E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241634E+09 |
Annual Sum or Average | 0.116768E+11 | 0.589031E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4810702.49 | 0.242555E+10 |
Minimum of Months | 0.882782E+09 | 0.426128E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93628514.77 |
Maximum of Months | 0.105485E+10 | 0.569860E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3038961.05 | 0.278873E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.921735E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465023E+09 |
February | 0.136985E+10 | 0.751028E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412432E+09 |
March | 0.163685E+10 | 0.810868E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402824E+09 |
April | 0.145243E+10 | 0.680914E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1204092.43 | 0.396954E+09 |
May | 0.157338E+10 | 0.711621E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12990.43 | 0.326730E+09 |
June | 0.156900E+10 | 0.692916E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 215397.87 | 0.280086E+09 |
July | 0.145680E+10 | 0.654585E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4244583.58 | 0.237630E+09 |
August | 0.163685E+10 | 0.740593E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6153202.33 | 0.191490E+09 |
September | 0.145243E+10 | 0.706521E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14474.93 | 0.147543E+09 |
October | 0.150991E+10 | 0.801066E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315939E+09 |
November | 0.149516E+10 | 0.888232E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357061E+09 |
December | 0.145680E+10 | 0.926351E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389816E+09 |
Annual Sum or Average | 0.181194E+11 | 0.928643E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11844741.57 | 0.392353E+10 |
Minimum of Months | 0.136985E+10 | 0.654585E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147543E+09 |
Maximum of Months | 0.163685E+10 | 0.926351E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6153202.33 | 0.465023E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.570417E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310260E+09 |
February | 0.882782E+09 | 0.472341E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279106E+09 |
March | 0.105485E+10 | 0.517112E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274220E+09 |
April | 0.936002E+09 | 0.438597E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 648390.92 | 0.274928E+09 |
May | 0.101394E+10 | 0.461152E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8659.18 | 0.224356E+09 |
June | 0.101113E+10 | 0.450281E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 143591.56 | 0.194219E+09 |
July | 0.938820E+09 | 0.424999E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1630579.64 | 0.162905E+09 |
August | 0.105485E+10 | 0.480434E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3582115.99 | 0.133376E+09 |
September | 0.936002E+09 | 0.450299E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9648.46 | 0.102170E+09 |
October | 0.973041E+09 | 0.503953E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216264E+09 |
November | 0.963541E+09 | 0.553295E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238576E+09 |
December | 0.938820E+09 | 0.569533E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260606E+09 |
Annual Sum or Average | 0.116768E+11 | 0.589241E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6022985.75 | 0.267098E+10 |
Minimum of Months | 0.882782E+09 | 0.424999E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102170E+09 |
Maximum of Months | 0.105485E+10 | 0.570417E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3582115.99 | 0.310260E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.858935E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479063E+09 |
February | 0.136988E+10 | 0.711055E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447707E+09 |
March | 0.163688E+10 | 0.794073E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435834E+09 |
April | 0.145246E+10 | 0.680471E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 532724.50 | 0.424703E+09 |
May | 0.157341E+10 | 0.715952E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12986.53 | 0.341861E+09 |
June | 0.156904E+10 | 0.699536E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 215382.28 | 0.288459E+09 |
July | 0.145684E+10 | 0.663622E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2196040.33 | 0.248022E+09 |
August | 0.163688E+10 | 0.746304E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5256580.12 | 0.204420E+09 |
September | 0.145246E+10 | 0.699160E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14372.62 | 0.163762E+09 |
October | 0.150994E+10 | 0.769007E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352096E+09 |
November | 0.149520E+10 | 0.834888E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374962E+09 |
December | 0.145684E+10 | 0.851194E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408962E+09 |
Annual Sum or Average | 0.181198E+11 | 0.902420E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8228086.38 | 0.416985E+10 |
Minimum of Months | 0.136988E+10 | 0.663622E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163762E+09 |
Maximum of Months | 0.163688E+10 | 0.858935E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5256580.12 | 0.479063E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.569815E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319969E+09 |
February | 0.882782E+09 | 0.468208E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293320E+09 |
March | 0.105485E+10 | 0.517144E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289922E+09 |
April | 0.936002E+09 | 0.439293E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 238524.46 | 0.287973E+09 |
May | 0.101394E+10 | 0.459940E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8658.65 | 0.237428E+09 |
June | 0.101113E+10 | 0.448545E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 143585.05 | 0.200304E+09 |
July | 0.938820E+09 | 0.426121E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1621353.76 | 0.178492E+09 |
August | 0.105485E+10 | 0.479205E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3642358.58 | 0.144092E+09 |
September | 0.936002E+09 | 0.454909E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9648.36 | 0.110799E+09 |
October | 0.973041E+09 | 0.505306E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230281E+09 |
November | 0.963541E+09 | 0.552205E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252913E+09 |
December | 0.938820E+09 | 0.569317E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275770E+09 |
Annual Sum or Average | 0.116768E+11 | 0.589001E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5664128.86 | 0.282126E+10 |
Minimum of Months | 0.882782E+09 | 0.426121E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110799E+09 |
Maximum of Months | 0.105485E+10 | 0.569815E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3642358.58 | 0.319969E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.318958E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.289319E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.343791E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.307076E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.331375E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.329773E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.308678E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.343791E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.307076E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.318958E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.315220E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.308678E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.382269E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.289319E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.343791E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433289E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385183E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367889E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372234.56 | 0.344595E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1595.34 | 0.262916E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80125.47 | 0.216727E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2209388.66 | 0.180000E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3396651.83 | 0.148778E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 912.17 | 0.123932E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295184E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342464E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376086E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6060908.03 | 0.347704E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123932E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3396651.83 | 0.433289E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689641E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633215E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619836E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1018061.33 | 0.585094E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2744.86 | 0.459363E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147718.01 | 0.378230E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4736997.45 | 0.315929E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6443987.27 | 0.261878E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1424.66 | 0.216061E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497985E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560382E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603648E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12350933.58 | 0.582126E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216061E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6443987.27 | 0.689641E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692845E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634160E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630290E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 880258.38 | 0.623693E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511811E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37055.42 | 0.434601E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1513764.07 | 0.368569E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4479949.21 | 0.297562E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233564E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500856E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549509E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592905E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6911027.09 | 0.607036E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233564E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4479949.21 | 0.692845E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 11837.83 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 11837.83 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 11837.83 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 11837.83 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 11837.83 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 11837.83 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 11837.83 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 11837.83 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 11837.83 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 11837.83 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 11837.83 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 11837.83 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 11837.83 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 11837.83 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1334.85 | 02-JAN-16:30 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 336.16 | 28-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 1231.60 | 02-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 315.55 | 16-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1106.67 | 22-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 296.91 | 28-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 929.33 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.85 | 01-APR-17:02 | 305.22 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 713.68 | 17-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 | 05-MAY-16:00 | 217.78 | 18-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 696.80 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.23 | 28-JUN-16:00 | 301.61 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 892.87 | 12-JUL-08:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.00 | 23-JUL-16:00 | 153.40 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 837.18 | 02-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 | 13-AUG-15:10 | 187.88 | 11-AUG-03:50 |
September | 2010.79 | 01-SEP-09:09 | 1113.43 | 25-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 | 14-SEP-17:00 | 143.36 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 1320.66 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 262.13 | 31-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 1334.85 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 322.09 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 1334.85 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 266.88 | 17-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 696.80 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.36 | |||||
Maximum of Months | 2010.79 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 36.00 | 336.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 860.23 | 02-JAN-16:30 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 218.62 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 801.13 | 02-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 204.38 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 690.10 | 22-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 195.26 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 472.50 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.70 | 01-APR-17:02 | 200.45 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 443.38 | 05-MAY-14:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 | 05-MAY-16:00 | 142.26 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 440.43 | 08-JUN-15:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.82 | 28-JUN-16:00 | 196.72 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 457.20 | 12-JUL-08:30 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.12 | 23-JUL-16:00 | 98.27 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 471.48 | 02-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 | 13-AUG-15:10 | 120.86 | 11-AUG-03:50 |
September | 1295.83 | 01-SEP-09:09 | 695.88 | 25-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.91 | 14-SEP-17:00 | 93.16 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 848.90 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 167.04 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 205.87 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 170.73 | 17-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 440.43 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.16 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 22.70 | 218.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1334.88 | 02-JAN-16:30 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 321.15 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 1207.99 | 02-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 303.37 | 19-FEB-12:00 |
March | 2010.83 | 01-MAR-10:09 | 1096.52 | 22-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 299.24 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 914.91 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.72 | 01-APR-17:02 | 304.43 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 714.80 | 17-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 | 05-MAY-16:00 | 214.11 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 702.59 | 29-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.23 | 28-JUN-16:00 | 294.48 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 861.46 | 12-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.63 | 23-JUL-16:00 | 150.95 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 827.79 | 02-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 | 08-AUG-17:00 | 192.11 | 11-AUG-03:50 |
September | 2010.83 | 01-SEP-09:09 | 1105.77 | 25-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 | 14-SEP-17:00 | 138.25 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 1318.04 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 248.74 | 31-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 1334.88 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 307.53 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 1334.88 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 244.78 | 02-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 702.59 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.25 | |||||
Maximum of Months | 2010.83 | 1334.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 22.63 | 321.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 860.23 | 02-JAN-16:30 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 235.76 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 776.73 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 225.94 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 723.40 | 22-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 221.03 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 635.90 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.58 | 01-APR-16:00 | 229.11 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 471.38 | 17-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 | 05-MAY-16:00 | 153.49 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 464.90 | 29-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.82 | 28-JUN-16:00 | 219.68 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 652.93 | 12-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.47 | 23-JUL-15:56 | 119.01 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 650.05 | 28-AUG-07:30 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.21 | 08-AUG-17:00 | 147.34 | 11-AUG-03:50 |
September | 1295.83 | 01-SEP-09:09 | 726.69 | 25-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.91 | 14-SEP-17:00 | 101.87 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 851.35 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 185.47 | 31-OCT-21:20 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 234.91 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 199.67 | 17-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 464.90 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.87 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 11.21 | 235.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1334.85 | 02-JAN-16:30 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 688.67 | 12-JAN-24:00 |
February | 2010.79 | 01-FEB-10:09 | 1233.90 | 02-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 634.13 | 16-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1111.71 | 22-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 611.71 | 28-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 938.03 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.09 | 01-APR-17:02 | 645.11 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 711.05 | 17-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 | 05-MAY-16:00 | 479.55 | 18-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 693.79 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.40 | 28-JUN-16:00 | 647.50 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 900.57 | 12-JUL-08:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.18 | 23-JUL-16:10 | 324.19 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 847.83 | 02-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.37 | 13-AUG-15:10 | 457.81 | 11-AUG-03:55 |
September | 2010.79 | 01-SEP-09:09 | 1118.26 | 25-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 | 14-SEP-17:00 | 306.35 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 1320.96 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 542.39 | 31-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 1334.85 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 646.81 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 1334.85 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 513.59 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 693.79 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.35 | |||||
Maximum of Months | 2010.79 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 113.09 | 688.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 860.23 | 02-JAN-16:30 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 454.26 | 12-JAN-24:00 |
February | 1239.33 | 01-FEB-08:09 | 801.29 | 02-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 419.46 | 16-FEB-04:00 |
March | 1239.33 | 01-MAR-08:09 | 691.25 | 22-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 419.71 | 28-MAR-24:00 |
April | 1239.33 | 03-APR-07:10 | 471.34 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.06 | 01-APR-17:02 | 442.04 | 07-APR-24:00 |
May | 1239.33 | 01-MAY-07:10 | 440.71 | 05-MAY-14:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 05-MAY-16:00 | 315.01 | 22-MAY-24:00 |
June | 1239.33 | 01-JUN-07:10 | 437.36 | 08-JUN-15:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.27 | 28-JUN-16:00 | 431.74 | 13-JUN-03:00 |
July | 1239.33 | 03-JUL-07:10 | 455.41 | 12-JUL-08:30 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.42 | 23-JUL-16:10 | 214.78 | 02-JUL-04:00 |
August | 1239.33 | 01-AUG-07:10 | 470.06 | 02-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.79 | 08-AUG-17:00 | 313.57 | 11-AUG-03:55 |
September | 1239.33 | 01-SEP-07:10 | 696.95 | 25-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 | 14-SEP-17:00 | 199.94 | 18-SEP-23:00 |
October | 1239.33 | 02-OCT-07:10 | 848.98 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 353.25 | 31-OCT-21:10 |
November | 1239.33 | 01-NOV-07:10 | 860.23 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 427.96 | 29-NOV-23:00 |
December | 1239.33 | 01-DEC-08:09 | 860.23 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 341.08 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 437.36 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.94 | |||||
Maximum of Months | 1239.33 | 860.23 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 66.06 | 454.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1334.88 | 02-JAN-16:30 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 690.43 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 1210.98 | 02-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 686.49 | 19-FEB-12:00 |
March | 2010.83 | 01-MAR-10:09 | 1101.92 | 22-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 657.85 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 924.04 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.64 | 01-APR-17:02 | 665.89 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 712.17 | 17-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 | 05-MAY-16:00 | 477.53 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 699.65 | 29-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.40 | 28-JUN-16:00 | 643.95 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 870.11 | 12-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.13 | 23-JUL-16:10 | 331.35 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 838.68 | 02-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.69 | 08-AUG-17:00 | 479.51 | 11-AUG-03:55 |
September | 2010.83 | 01-SEP-09:09 | 1110.85 | 25-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 | 14-SEP-17:00 | 306.94 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 1318.45 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 538.45 | 31-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 1334.88 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 647.54 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 1334.88 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 526.16 | 02-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 699.65 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.94 | |||||
Maximum of Months | 2010.83 | 1334.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 51.13 | 690.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 860.23 | 02-JAN-16:30 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 465.25 | 12-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 776.94 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 431.32 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 723.70 | 22-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 428.13 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 636.34 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.21 | 01-APR-16:00 | 441.00 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 469.62 | 17-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 05-MAY-16:00 | 325.22 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 462.95 | 29-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.27 | 28-JUN-16:00 | 435.76 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 652.98 | 12-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.66 | 23-JUL-13:45 | 232.63 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 650.19 | 28-AUG-07:30 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.79 | 08-AUG-17:00 | 337.49 | 11-AUG-03:55 |
September | 1295.83 | 01-SEP-09:09 | 726.98 | 25-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 | 14-SEP-17:00 | 206.14 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 851.38 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 361.90 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 438.60 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 350.42 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 462.95 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.14 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 34.66 | 465.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1334.85 | 02-JAN-16:30 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 789.61 | 12-JAN-24:00 |
February | 2010.79 | 01-FEB-10:09 | 1233.81 | 02-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 706.93 | 16-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1111.46 | 22-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 705.55 | 29-MAR-04:55 |
April | 2010.79 | 03-APR-09:09 | 937.65 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.67 | 01-APR-17:02 | 750.67 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 710.85 | 17-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.60 | 05-MAY-16:00 | 563.85 | 22-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 693.56 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.03 | 28-JUN-16:00 | 752.72 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 900.18 | 12-JUL-08:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.46 | 23-JUL-13:53 | 373.32 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 847.29 | 02-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.22 | 13-AUG-14:51 | 561.82 | 11-AUG-03:55 |
September | 2010.79 | 01-SEP-09:09 | 1118.02 | 25-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.10 | 14-SEP-17:00 | 337.16 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 1320.94 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 632.72 | 31-OCT-21:05 |
November | 2010.79 | 01-NOV-09:09 | 1334.85 | 06-NOV-16:49 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 746.12 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 1334.85 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 600.16 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 693.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.16 | |||||
Maximum of Months | 2010.79 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 152.67 | 789.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 860.23 | 02-JAN-16:30 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 523.35 | 12-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 801.23 | 02-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 468.45 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 691.12 | 22-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 475.31 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 471.25 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.67 | 01-APR-17:02 | 522.49 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 440.56 | 05-MAY-14:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.73 | 05-MAY-16:00 | 377.38 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 437.24 | 08-JUN-15:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 | 28-JUN-16:00 | 503.19 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 455.27 | 12-JUL-08:30 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.03 | 23-JUL-16:00 | 247.87 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 469.95 | 02-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.41 | 08-AUG-17:00 | 386.82 | 11-AUG-03:55 |
September | 1295.83 | 01-SEP-09:09 | 696.82 | 25-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.07 | 14-SEP-17:00 | 221.13 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 848.97 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 421.19 | 31-OCT-21:05 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 494.86 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 398.70 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 437.24 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.13 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 87.67 | 523.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1334.88 | 02-JAN-16:30 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 792.38 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 1210.90 | 02-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 735.53 | 19-FEB-12:20 |
March | 2010.83 | 01-MAR-10:09 | 1101.68 | 22-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 753.57 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 923.65 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.61 | 01-APR-17:02 | 783.34 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 711.98 | 17-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.60 | 05-MAY-16:00 | 570.79 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 699.43 | 29-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.03 | 28-JUN-16:00 | 746.96 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 869.77 | 12-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 23-JUL-15:38 | 383.95 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 838.14 | 02-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.11 | 08-AUG-17:00 | 591.95 | 11-AUG-03:55 |
September | 2010.83 | 01-SEP-09:09 | 1110.61 | 25-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.10 | 14-SEP-17:00 | 350.04 | 30-SEP-04:55 |
October | 2010.83 | 02-OCT-09:09 | 1318.43 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 632.80 | 31-OCT-21:05 |
November | 2010.83 | 01-NOV-09:09 | 1334.88 | 06-NOV-16:49 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 746.96 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 1334.88 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 607.00 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 699.43 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.04 | |||||
Maximum of Months | 2010.83 | 1334.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 68.61 | 792.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 860.23 | 02-JAN-16:30 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 541.19 | 12-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 776.85 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 491.20 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 723.55 | 22-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 489.79 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 636.11 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 | 01-APR-16:00 | 518.26 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 469.52 | 17-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.73 | 05-MAY-16:00 | 390.30 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 462.83 | 29-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 | 28-JUN-16:00 | 508.08 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 652.81 | 12-JUL-07:30 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.02 | 23-JUL-13:53 | 272.63 | 22-JUL-22:53 |
August | 1295.83 | 01-AUG-09:09 | 650.12 | 28-AUG-07:30 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.41 | 08-AUG-17:00 | 416.50 | 11-AUG-03:55 |
September | 1295.83 | 01-SEP-09:09 | 726.83 | 25-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.07 | 14-SEP-17:00 | 237.58 | 30-SEP-04:55 |
October | 1295.83 | 02-OCT-09:09 | 851.37 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 426.40 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 860.23 | 06-NOV-16:49 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 513.11 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 860.23 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 413.75 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 462.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.58 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 44.02 | 541.19 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 3337.76 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 3337.76 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 3337.76 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 3337.76 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 3337.76 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 3337.76 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 3337.76 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 3337.76 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 3337.76 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 3337.76 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 3337.76 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 3337.76 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 3337.76 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 712.41 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 664.68 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 624.43 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.68 | 01-APR-17:02 | 634.38 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 | 05-MAY-16:00 | 465.47 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.85 | 28-JUN-15:00 | 627.82 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.39 | 23-JUL-16:00 | 315.50 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.63 | 13-AUG-14:51 | 406.93 | 11-AUG-03:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 14-SEP-17:00 | 293.37 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 556.10 | 31-OCT-21:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 678.23 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 559.35 | 17-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.37 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.39 | 712.41 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1184.26 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1103.49 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1059.16 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.54 | 01-APR-17:02 | 1093.57 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 05-MAY-16:00 | 825.76 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.56 | 28-JUN-15:00 | 1093.82 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.86 | 23-JUL-15:51 | 545.34 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.74 | 13-AUG-14:51 | 744.84 | 11-AUG-03:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 | 14-SEP-17:00 | 506.37 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 936.29 | 31-OCT-21:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1113.10 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 883.52 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.37 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.54 | 1184.26 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1208.21 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1101.71 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1069.15 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.49 | 01-APR-17:02 | 1170.99 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 842.12 | 22-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.74 | 28-JUN-17:00 | 1131.27 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.57 | 23-JUL-14:00 | 562.92 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.33 | 08-AUG-17:00 | 846.42 | 11-AUG-03:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 507.75 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 979.83 | 31-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1134.43 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 927.27 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.75 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.49 | 1208.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 98476.81 | 02-JAN-04:01 | 0.00 | 4604.05 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95160.51 | 27-FEB-04:12 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 94992.06 | 06-MAR-04:01 | 0.00 | 4604.05 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 95850.58 | 17-APR-03:02 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97972.87 | 30-MAY-03:02 | 0.00 | 3946.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 96396.00 | 05-JUN-03:02 | 0.00 | 3946.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 96258.50 | 03-JUL-03:02 | 0.00 | 3946.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 89402.39 | 21-AUG-03:03 | 0.00 | 1973.16 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 96386.73 | 05-SEP-03:02 | 0.00 | 3946.33 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 96788.43 | 30-OCT-03:12 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 99560.98 | 13-NOV-04:01 | 0.00 | 5919.49 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 98362.18 | 26-DEC-04:01 | 0.00 | 4604.05 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 89402.39 | 0.00 | 1973.16 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 99560.98 | 0.00 | 5919.49 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 77577.36 | 02-JAN-05:01 | 0.00 | 8268.49 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 77529.41 | 27-FEB-05:02 | 0.00 | 5906.06 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 77193.02 | 21-MAR-04:02 | 0.00 | 5906.06 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79485.27 | 17-APR-03:02 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80431.51 | 01-MAY-03:02 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 81274.46 | 12-JUN-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 80165.71 | 17-JUL-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 78190.40 | 22-AUG-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83606.39 | 05-SEP-03:02 | 0.00 | 3544.08 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84063.41 | 10-OCT-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 80992.44 | 06-NOV-04:03 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 79248.64 | 26-DEC-05:02 | 0.00 | 11812.12 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 77193.02 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84063.41 | 0.00 | 11812.12 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 18223.15 | 12-JAN-17:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27164.70 | 28-FEB-06:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 64278.97 | 03-MAR-06:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70691.67 | 27-APR-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72266.31 | 09-MAY-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 71744.35 | 01-JUN-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 71337.72 | 01-JUL-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 72422.07 | 03-AUG-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 72139.68 | 08-SEP-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 71146.34 | 05-OCT-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 64451.37 | 06-NOV-06:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22332.53 | 06-DEC-17:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 18223.15 | 6448.95 | 4724.85 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72422.07 | 15316.26 | 10631.20 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16674.94 | 11-JAN-17:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19574.27 | 28-FEB-17:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23370.16 | 15-MAR-16:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65516.28 | 28-APR-05:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 65017.90 | 05-MAY-05:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 67555.54 | 29-JUN-05:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 68629.15 | 28-JUL-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 68416.22 | 29-AUG-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 65216.91 | 15-SEP-05:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32556.85 | 04-OCT-16:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18371.37 | 02-NOV-16:00 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16650.45 | 05-DEC-16:40 | 15316.26 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 16650.45 | 6448.95 | 4724.85 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 68629.15 | 15316.26 | 10631.20 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2774.12 | 02-JAN-06:03 | 1417.03 | 1038.19 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 |
February | 3955.97 | 27-FEB-15:30 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.99 |
March | 4376.24 | 10-MAR-14:30 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.91 |
April | 6417.45 | 27-APR-15:20 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5.69 | 0.00 |
May | 6397.39 | 15-MAY-14:00 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 |
June | 10316.85 | 12-JUN-05:03 | 809.73 | 305.64 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.52 |
July | 10066.45 | 10-JUL-05:02 | 1012.16 | 623.17 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 |
August | 10111.80 | 28-AUG-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.26 |
September | 5960.88 | 05-SEP-13:10 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.24 |
October | 5340.13 | 10-OCT-05:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.73 |
November | 4141.02 | 06-NOV-11:40 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 |
December | 2896.56 | 11-DEC-06:03 | 1417.03 | 1038.19 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2774.12 | 809.73 | 305.64 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10316.85 | 2010.79 | 1038.19 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 5.69 | 49.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2386.17 | 02-JAN-06:03 | 913.19 | 669.05 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.04 |
February | 3535.59 | 27-FEB-10:30 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.25 |
March | 6857.76 | 14-MAR-09:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 |
April | 9601.28 | 27-APR-08:30 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 |
May | 17922.64 | 14-MAY-08:23 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.92 |
June | 17779.09 | 25-JUN-09:32 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 |
July | 17200.94 | 30-JUL-08:52 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.45 |
August | 19176.14 | 13-AUG-09:02 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.14 |
September | 18026.36 | 10-SEP-08:62 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.21 |
October | 7918.16 | 04-OCT-09:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.12 |
November | 3085.40 | 02-NOV-10:30 | 2478.65 | 818.60 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.99 |
December | 2605.11 | 05-DEC-10:10 | 2591.66 | 818.60 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2386.17 | 260.91 | 90.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 | |
Maximum of Months | 19176.14 | 2591.66 | 818.60 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11350.69 | 20-JAN-13:10 | 1923.15 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.04 |
February | 14984.60 | 12-FEB-13:33 | 303.66 | 105.87 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.80 |
March | 15123.90 | 01-MAR-13:40 | 1923.15 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 |
April | 16157.97 | 27-APR-13:00 | 1923.15 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 0.00 |
May | 15843.83 | 14-MAY-11:43 | 303.66 | 105.87 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.41 |
June | 13304.02 | 11-JUN-11:23 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.20 |
July | 19380.20 | 30-JUL-12:53 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.73 |
August | 26456.72 | 13-AUG-12:22 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.22 |
September | 22903.22 | 10-SEP-12:43 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.92 |
October | 25516.66 | 08-OCT-12:32 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.20 |
November | 13101.91 | 04-NOV-13:30 | 211.67 | 105.86 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13171.74 | 05-DEC-12:30 | 1058.33 | 635.14 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11350.69 | 211.67 | 105.86 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26456.72 | 1923.15 | 635.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 | 219.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4072.93 | 05-JAN-15:30 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 |
February | 10864.53 | 24-FEB-06:02 | 652.28 | 477.89 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.77 |
March | 13393.86 | 03-MAR-06:02 | 652.28 | 477.89 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.11 |
April | 19080.08 | 02-APR-15:42 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.14 |
May | 22150.54 | 07-MAY-16:42 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.22 |
June | 22476.34 | 18-JUN-17:02 | 0.00 | 136.45 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.29 |
July | 23554.24 | 23-JUL-16:52 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.15 |
August | 23408.06 | 06-AUG-16:52 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.87 |
September | 19683.91 | 10-SEP-16:42 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 |
October | 14591.01 | 04-OCT-05:02 | 652.28 | 477.89 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.13 |
November | 14714.83 | 27-NOV-06:01 | 913.19 | 669.05 | 4331.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.71 |
December | 17049.39 | 11-DEC-06:01 | 913.19 | 669.05 | 4331.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4072.93 | 0.00 | 113.70 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.52 | |
Maximum of Months | 23554.24 | 1239.33 | 669.05 | 4331.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1755.05 | 11-JAN-16:20 | 1923.11 | 1256.68 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.60 |
February | 2142.16 | 28-FEB-15:00 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2246.48 | 22-MAR-05:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4984.13 | 27-APR-15:50 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 12.89 | 0.00 |
May | 5559.40 | 05-MAY-13:30 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 |
June | 6129.04 | 21-JUN-15:30 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2.04 | 0.00 |
July | 7018.63 | 24-JUL-15:00 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 20.26 | 0.00 |
August | 7549.72 | 10-AUG-05:03 | 809.73 | 576.76 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.58 |
September | 4958.97 | 12-SEP-14:40 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 0.00 |
October | 2970.34 | 04-OCT-15:30 | 1923.11 | 668.17 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 |
November | 2345.73 | 06-NOV-06:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.94 |
December | 1689.00 | 29-DEC-16:10 | 1923.11 | 1265.82 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1689.00 | 809.73 | 576.76 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7549.72 | 2010.79 | 1265.82 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 20.26 | 52.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1593.19 | 05-JAN-09:40 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.31 |
February | 1995.33 | 08-FEB-10:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.12 |
March | 4892.37 | 14-MAR-10:10 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.55 |
April | 9640.15 | 27-APR-09:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.52 |
May | 18203.62 | 14-MAY-08:13 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.82 |
June | 19244.81 | 25-JUN-08:42 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.34 |
July | 20169.82 | 23-JUL-08:42 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.29 |
August | 20243.61 | 13-AUG-09:02 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.24 |
September | 18450.18 | 10-SEP-09:53 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.52 |
October | 7021.84 | 04-OCT-09:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.65 |
November | 2222.69 | 06-NOV-06:03 | 521.82 | 382.31 | 2475.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.07 |
December | 1792.65 | 05-DEC-10:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1593.19 | 260.91 | 90.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.52 | |
Maximum of Months | 20243.61 | 1239.33 | 409.30 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10536.47 | 20-JAN-13:30 | 1923.15 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 |
February | 23259.35 | 12-FEB-14:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.41 |
March | 15810.37 | 01-MAR-13:40 | 1923.15 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.53 |
April | 16405.66 | 27-APR-13:10 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | 0.00 |
May | 25276.49 | 14-MAY-13:32 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.85 |
June | 11947.95 | 28-JUN-13:10 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 | 0.00 |
July | 23624.46 | 23-JUL-13:23 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.00 |
August | 26863.20 | 13-AUG-12:22 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.89 |
September | 28368.52 | 10-SEP-12:32 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.87 |
October | 26709.63 | 08-OCT-13:02 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.73 |
November | 12842.99 | 04-NOV-13:30 | 211.67 | 105.86 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11286.82 | 05-DEC-12:30 | 1058.33 | 635.14 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10536.47 | 211.67 | 105.86 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28368.52 | 2010.83 | 635.14 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | 506.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2016.31 | 05-JAN-15:50 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.21 |
February | 5614.95 | 27-FEB-15:30 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 |
March | 7672.13 | 14-MAR-16:00 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.23 |
April | 11414.96 | 26-APR-16:00 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 | 0.00 |
May | 21465.14 | 14-MAY-16:51 | 456.59 | 159.19 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.85 |
June | 18626.17 | 25-JUN-16:42 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.38 |
July | 22197.93 | 23-JUL-18:01 | 0.00 | 181.93 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.83 |
August | 20483.30 | 06-AUG-17:21 | 0.00 | 204.67 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.11 |
September | 20314.19 | 10-SEP-15:52 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.68 |
October | 9280.71 | 04-OCT-16:00 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.78 |
November | 3318.98 | 04-NOV-15:00 | 130.46 | 68.22 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.40 |
December | 2197.26 | 05-DEC-15:40 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2016.31 | 0.00 | 68.22 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22197.93 | 1239.33 | 409.30 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 | 117.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1626.36 | 11-JAN-16:20 | 1923.11 | 1256.61 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.35 |
February | 2029.69 | 28-FEB-15:10 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 |
March | 2156.71 | 10-MAR-15:00 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.48 |
April | 5433.51 | 27-APR-15:50 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 15.44 | 0.00 |
May | 5835.86 | 15-MAY-14:40 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 |
June | 6737.55 | 21-JUN-15:30 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2.07 | 0.00 |
July | 8002.52 | 24-JUL-15:00 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 24.74 | 0.00 |
August | 7437.53 | 09-AUG-15:30 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 29.12 | 0.00 |
September | 5227.49 | 14-SEP-15:50 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 0.00 |
October | 2730.53 | 04-OCT-13:30 | 2010.79 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 |
November | 1895.89 | 02-NOV-14:50 | 1923.11 | 691.03 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.36 |
December | 1564.21 | 29-DEC-16:10 | 1923.11 | 1265.75 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1564.21 | 1923.11 | 635.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8002.52 | 2010.79 | 1265.75 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 29.12 | 61.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1464.59 | 12-JAN-06:05 | 521.82 | 382.31 | 2475.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.54 |
February | 1823.91 | 27-FEB-16:10 | 1239.33 | 444.92 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 |
March | 3175.99 | 14-MAR-10:00 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.91 |
April | 9123.90 | 27-APR-09:30 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 |
May | 16198.34 | 14-MAY-10:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.43 |
June | 15702.65 | 25-JUN-10:32 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.75 |
July | 19832.64 | 30-JUL-09:22 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.38 |
August | 19016.72 | 06-AUG-09:12 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.38 |
September | 16415.99 | 10-SEP-09:43 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.11 |
October | 5704.28 | 04-OCT-09:30 | 1295.83 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.63 |
November | 1781.51 | 02-NOV-10:40 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.31 |
December | 1476.28 | 27-DEC-06:05 | 782.73 | 573.47 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1464.59 | 260.91 | 90.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | |
Maximum of Months | 19832.64 | 1295.83 | 573.47 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8615.68 | 20-JAN-13:30 | 1923.15 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.05 |
February | 12464.51 | 27-FEB-14:30 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.15 |
March | 14341.67 | 14-MAR-13:40 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.70 |
April | 16962.34 | 27-APR-13:20 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 7.79 | 0.00 |
May | 24836.74 | 14-MAY-13:23 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.75 |
June | 12700.19 | 28-JUN-13:20 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2.10 | 0.00 |
July | 28749.59 | 30-JUL-13:22 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.96 |
August | 27466.61 | 06-AUG-13:53 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.05 |
September | 29918.08 | 10-SEP-14:22 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.35 |
October | 19657.67 | 04-OCT-13:20 | 2010.83 | 635.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.22 |
November | 11408.85 | 04-NOV-13:30 | 211.67 | 105.86 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8328.36 | 05-DEC-12:30 | 1058.33 | 635.14 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8328.36 | 211.67 | 105.86 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29918.08 | 2010.83 | 635.14 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 7.79 | 185.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1976.27 | 05-JAN-15:50 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.01 |
February | 4823.60 | 27-FEB-15:30 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 |
March | 7177.39 | 14-MAR-16:00 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.90 |
April | 11491.94 | 26-APR-16:00 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 | 0.00 |
May | 22784.13 | 07-MAY-16:31 | 456.59 | 159.19 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.23 |
June | 20956.88 | 25-JUN-16:32 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.71 |
July | 23537.78 | 30-JUL-18:01 | 0.00 | 181.93 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.25 |
August | 22911.38 | 06-AUG-17:11 | 0.00 | 159.19 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.53 |
September | 21701.33 | 10-SEP-16:22 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.03 |
October | 9066.23 | 04-OCT-16:00 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.87 |
November | 2539.09 | 04-NOV-15:50 | 130.46 | 68.22 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 |
December | 2097.68 | 05-DEC-15:40 | 1239.33 | 409.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1976.27 | 0.00 | 68.22 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23537.78 | 1239.33 | 409.30 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 | 98.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2663.54 | 02-JAN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.26 |
February | 3889.37 | 28-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.78 |
March | 4382.05 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.56 |
April | 5342.00 | 27-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.23 | 0.00 |
May | 6093.57 | 08-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 |
June | 8799.59 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 |
July | 7735.59 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.94 |
August | 9249.94 | 14-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.55 |
September | 7481.43 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 |
October | 8007.24 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.28 |
November | 6135.42 | 06-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.00 |
December | 3650.48 | 06-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2663.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9249.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.23 | 106.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3888.24 | 17-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.36 |
February | 3389.93 | 18-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.07 |
March | 2700.82 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.29 |
April | 3855.69 | 29-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.09 |
May | 4107.44 | 06-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 |
June | 4311.50 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.68 |
July | 4760.96 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.74 | 0.00 |
August | 5593.76 | 10-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.44 | 0.00 |
September | 4642.67 | 14-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 |
October | 3912.88 | 05-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.65 |
November | 3798.35 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.04 |
December | 4178.99 | 09-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2700.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5593.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.74 | 279.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.12 |
February | 1720.84 | 27-FEB-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 |
March | 3766.95 | 18-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.10 |
April | 13434.55 | 27-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.16 | 0.00 |
May | 14060.01 | 15-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.75 |
June | 14600.56 | 28-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 |
July | 16065.69 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.09 | 0.00 |
August | 17035.78 | 10-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 0.00 |
September | 12394.27 | 14-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.62 |
October | 7214.62 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.59 |
November | 3137.25 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17035.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.09 | 537.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1792.41 | 05-JAN-16:10 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3869.66 | 07-FEB-16:50 | 222.14 | 284.97 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6976.79 | 31-MAR-24:00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7946.70 | 26-APR-17:50 | 23.38 | 94.99 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3434.30 | 31-MAY-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5312.61 | 30-JUN-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7222.26 | 31-JUL-23:43 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8386.69 | 06-AUG-18:22 | 0.00 | 94.99 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3300.64 | 30-SEP-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5008.08 | 31-OCT-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5647.50 | 12-NOV-15:53 | 35.07 | 47.50 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7595.86 | 05-DEC-15:50 | 222.14 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1792.41 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8386.69 | 222.14 | 284.97 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1212.43 | 05-JAN-16:20 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3493.36 | 08-FEB-17:00 | 222.14 | 284.97 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6118.70 | 31-MAR-24:00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7539.27 | 26-APR-17:50 | 23.38 | 94.99 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3177.48 | 31-MAY-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4967.57 | 30-JUN-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6976.71 | 31-JUL-23:57 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7799.82 | 06-AUG-18:23 | 0.00 | 94.99 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2898.70 | 30-SEP-24:00 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4144.15 | 31-OCT-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5179.60 | 10-NOV-16:10 | 222.14 | 284.97 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6957.69 | 05-DEC-16:00 | 222.14 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1212.43 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7799.82 | 222.14 | 284.97 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1005.21 | 05-JAN-16:20 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3346.07 | 27-FEB-16:30 | 222.14 | 284.97 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5497.55 | 31-MAR-23:30 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7603.14 | 26-APR-17:50 | 23.38 | 94.99 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3097.45 | 31-MAY-23:40 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4868.90 | 30-JUN-23:50 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6969.24 | 31-JUL-23:57 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7928.32 | 06-AUG-18:12 | 0.00 | 94.99 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2464.97 | 30-SEP-23:30 | 0.00 | 15.83 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3894.86 | 04-OCT-16:50 | 70.15 | 158.31 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4907.60 | 04-NOV-16:05 | 23.38 | 31.66 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6651.96 | 05-DEC-16:00 | 222.14 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1005.21 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7928.32 | 222.14 | 284.97 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 90325.17 | 03-JAN-17:00 | 4808.68 | 3337.76 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182581.73 | 27-FEB-17:00 | 4808.68 | 3337.76 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358022.16 | 31-MAR-24:00 | 0.00 | 185.45 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366550.38 | 27-APR-16:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175694.73 | 31-MAY-24:00 | 0.00 | 185.45 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267277.08 | 30-JUN-24:00 | 0.00 | 185.45 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359776.53 | 31-JUL-24:00 | 0.00 | 556.35 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 367399.68 | 14-AUG-16:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175319.16 | 30-SEP-24:00 | 0.00 | 185.45 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 266819.33 | 31-OCT-24:00 | 0.00 | 185.45 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275155.34 | 06-NOV-15:00 | 5027.92 | 3337.76 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366468.61 | 04-DEC-17:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 90325.17 | 0.00 | 185.45 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 367399.68 | 5027.92 | 3337.76 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.125620E+13 | 828541.15 | 10-JAN-16:49 | 0.419501E+12 | 1190789.99 | 02-JAN-05:10 |
February | 0.147159E+13 | 976684.83 | 27-FEB-16:10 | 0.251126E+12 | 615330.49 | 18-FEB-07:19 |
March | 0.203454E+13 | 1125757.07 | 14-MAR-15:00 | 0.130949E+12 | 432219.59 | 01-MAR-07:10 |
April | 0.232134E+13 | 1502717.02 | 27-APR-15:20 | 0.809449E+11 | 309136.85 | 19-APR-06:10 |
May | 0.132718E+13 | 1046798.49 | 15-MAY-15:20 | 0.646061E+11 | 171008.46 | 18-MAY-06:10 |
June | 0.170778E+13 | 1220352.70 | 28-JUN-15:30 | 0.593309E+11 | 77888.36 | 01-JUN-11:00 |
July | 0.216060E+13 | 1432985.07 | 31-JUL-15:20 | 0.565530E+11 | 76428.03 | 06-JUL-11:39 |
August | 0.262991E+13 | 1608169.36 | 29-AUG-15:09 | 0.599769E+11 | 75944.25 | 31-AUG-11:00 |
September | 0.130940E+13 | 1097767.74 | 14-SEP-15:09 | 0.564257E+11 | 76736.94 | 27-SEP-11:30 |
October | 0.165374E+13 | 1061630.54 | 04-OCT-15:39 | 0.745228E+11 | 227552.30 | 16-OCT-06:30 |
November | 0.195113E+13 | 1118151.23 | 08-NOV-16:40 | 0.189472E+12 | 512498.26 | 24-NOV-07:10 |
December | 0.236189E+13 | 1247508.30 | 29-DEC-16:19 | 0.331920E+12 | 805971.20 | 26-DEC-07:10 |
Annual Sum or Average | 0.221853E+14 | 0.177533E+13 | ||||
Minimum of Months | 0.125620E+13 | 828541.15 | 0.564257E+11 | 75944.25 | ||
Maximum of Months | 0.262991E+13 | 1608169.36 | 0.419501E+12 | 1190789.99 |
Report: EnergyConsumptionDistrictHeatingCoolingMonthly
For: Meter
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportDISTRICTCOOLING:FACILITY [J] | DISTRICTCOOLING:FACILITY {Maximum} [W] | DISTRICTCOOLING:FACILITY {TIMESTAMP} | DISTRICTHEATING:FACILITY [J] | DISTRICTHEATING:FACILITY {Maximum} [W] | DISTRICTHEATING:FACILITY {TIMESTAMP} | |
January | 0.237516E+12 | 92991.93 | 03-JAN-14:00 | 138639.76 | 8.66 | 01-JAN-18:40 |
February | 0.435874E+12 | 185180.75 | 27-FEB-16:00 | 176637.85 | 13.45 | 01-FEB-00:40 |
March | 0.730214E+12 | 358023.06 | 31-MAR-23:00 | 218471.30 | 11.10 | 31-MAR-23:30 |
April | 0.944025E+12 | 369149.36 | 27-APR-15:00 | 146611.49 | 8.42 | 17-APR-23:30 |
May | 0.241881E+12 | 175698.24 | 31-MAY-23:00 | 122148.54 | 13.46 | 31-MAY-23:40 |
June | 0.471138E+12 | 267278.87 | 30-JUN-23:00 | 164213.72 | 10.92 | 30-JUN-23:30 |
July | 0.732815E+12 | 359776.56 | 31-JUL-23:00 | 82692.50 | 10.13 | 01-JUL-18:30 |
August | 0.978400E+12 | 369998.69 | 14-AUG-15:00 | 118079.27 | 11.50 | 21-AUG-23:30 |
September | 0.235606E+12 | 175319.16 | 30-SEP-23:00 | 120705.71 | 8.65 | 30-SEP-18:40 |
October | 0.486717E+12 | 266821.10 | 31-OCT-23:00 | 179240.51 | 11.01 | 31-OCT-23:30 |
November | 0.707732E+12 | 277871.76 | 06-NOV-14:00 | 197115.67 | 7.60 | 07-NOV-00:30 |
December | 0.975685E+12 | 369135.01 | 04-DEC-14:00 | 212008.21 | 11.10 | 01-DEC-00:30 |
Annual Sum or Average | 0.717760E+13 | 1876564.52 | ||||
Minimum of Months | 0.235606E+12 | 92991.93 | 82692.50 | 7.60 | ||
Maximum of Months | 0.978400E+12 | 369998.69 | 218471.30 | 13.46 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.174732E+12 | 0.407688E+11 | 0.766053E+12 | 0.202779E+12 | 0.635526E+11 | 0.346853E+10 | 0.00 | 0.413571E+10 | 0.705525E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155533E+12 | 0.317693E+11 | 0.978954E+12 | 0.219897E+12 | 0.591621E+11 | 0.465441E+10 | 0.00 | 0.184011E+11 | 0.321588E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182229E+12 | 0.284362E+11 | 0.141687E+13 | 0.284346E+12 | 0.737382E+11 | 0.657078E+10 | 0.00 | 0.352172E+11 | 0.713309E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161349E+12 | 0.215128E+11 | 0.165903E+13 | 0.314137E+12 | 0.794411E+11 | 0.139913E+11 | 0.00 | 0.569173E+11 | 0.149692E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173303E+12 | 0.181621E+11 | 0.774844E+12 | 0.202916E+12 | 0.919588E+11 | 0.206958E+11 | 0.00 | 0.359956E+11 | 0.930920E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.171913E+12 | 0.158132E+11 | 0.106252E+13 | 0.235793E+12 | 0.102151E+12 | 0.329872E+11 | 0.00 | 0.674085E+11 | 0.192001E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161212E+12 | 0.170051E+11 | 0.139340E+13 | 0.284102E+12 | 0.114616E+12 | 0.479257E+11 | 0.00 | 0.110592E+12 | 0.317488E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179915E+12 | 0.201205E+11 | 0.173200E+13 | 0.324799E+12 | 0.128255E+12 | 0.556799E+11 | 0.00 | 0.149372E+12 | 0.397680E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162209E+12 | 0.246719E+11 | 0.740713E+12 | 0.196274E+12 | 0.946360E+11 | 0.284308E+11 | 0.00 | 0.483952E+11 | 0.140685E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170633E+12 | 0.323063E+11 | 0.108340E+13 | 0.243505E+12 | 0.763795E+11 | 0.107210E+11 | 0.00 | 0.287308E+11 | 0.805887E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171986E+12 | 0.375734E+11 | 0.135889E+13 | 0.275007E+12 | 0.633557E+11 | 0.574779E+10 | 0.00 | 0.318594E+11 | 0.670773E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170175E+12 | 0.424162E+11 | 0.170972E+13 | 0.324722E+12 | 0.638604E+11 | 0.348647E+10 | 0.00 | 0.416197E+11 | 0.589125E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203519E+13 | 0.330556E+12 | 0.146764E+14 | 0.310828E+13 | 0.101111E+13 | 0.234360E+12 | 0.00 | 0.628644E+12 | 0.160776E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155533E+12 | 0.158132E+11 | 0.740713E+12 | 0.196274E+12 | 0.591621E+11 | 0.346853E+10 | 0.00 | 0.413571E+10 | 0.705525E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182229E+12 | 0.424162E+11 | 0.173200E+13 | 0.324799E+12 | 0.128255E+12 | 0.556799E+11 | 0.00 | 0.149372E+12 | 0.397680E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.355919E+12 | 0.00 | 0.635821E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.193129E+12 | 0.00 | 0.579969E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.643441E+11 | 0.00 | 0.666047E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.207926E+11 | 0.00 | 0.601522E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.266934E+10 | 0.00 | 0.619368E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 34103352.77 | 0.00 | 0.592968E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.565530E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.599769E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.480644E+09 | 0.00 | 0.559450E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.154611E+11 | 0.00 | 0.590617E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.130085E+12 | 0.00 | 0.593870E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.270589E+12 | 0.00 | 0.613306E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.105350E+13 | 0.00 | 0.721824E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.559450E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.355919E+12 | 0.00 | 0.666047E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 198852.03 | 02-JAN-16:30 | 37611.08 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 132049.12 | 04-JAN-08:20 | 57393.32 | 02-JAN-06:10 | 27578.90 | 02-JAN-06:19 | 0.00 | 01-JAN-00:10 |
February | 194325.94 | 02-FEB-16:00 | 37611.08 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 147232.94 | 02-FEB-08:20 | 66929.00 | 27-FEB-14:00 | 27009.95 | 27-FEB-14:00 | 0.00 | 01-FEB-00:10 |
March | 189699.95 | 22-MAR-07:10 | 37611.08 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 162416.44 | 22-MAR-07:19 | 80859.45 | 14-MAR-15:30 | 26920.00 | 18-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 181788.48 | 03-APR-07:10 | 37611.08 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 177597.58 | 03-APR-07:19 | 154559.09 | 27-APR-14:30 | 47409.15 | 26-APR-15:39 | 0.00 | 01-APR-00:10 |
May | 174047.52 | 17-MAY-07:10 | 24287.76 | 01-MAY-19:19 | 423497.50 | 01-MAY-07:10 | 132037.59 | 17-MAY-07:19 | 142434.88 | 15-MAY-15:20 | 46591.27 | 04-MAY-14:09 | 0.00 | 01-MAY-00:10 |
June | 173365.24 | 29-JUN-07:10 | 24287.76 | 01-JUN-19:00 | 541788.89 | 01-JUN-07:10 | 147222.54 | 29-JUN-07:19 | 149209.03 | 28-JUN-15:20 | 48504.91 | 27-JUN-13:50 | 0.00 | 01-JUN-00:10 |
July | 180160.71 | 12-JUL-08:30 | 24287.76 | 01-JUL-20:10 | 660080.29 | 03-JUL-07:10 | 162411.31 | 12-JUL-07:00 | 172731.71 | 31-JUL-14:00 | 47740.53 | 19-JUL-14:20 | 0.00 | 01-JUL-00:10 |
August | 178829.72 | 02-AUG-07:30 | 37611.08 | 16-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 177596.02 | 02-AUG-07:40 | 191290.47 | 10-AUG-14:39 | 46196.16 | 21-AUG-14:30 | 0.00 | 01-AUG-00:10 |
September | 189994.17 | 25-SEP-07:10 | 37611.08 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 132045.98 | 25-SEP-07:19 | 166437.15 | 14-SEP-15:09 | 47405.18 | 08-SEP-14:39 | 0.00 | 01-SEP-00:10 |
October | 198245.92 | 31-OCT-07:10 | 37611.08 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 147235.64 | 31-OCT-07:19 | 130658.82 | 04-OCT-15:39 | 28190.39 | 04-OCT-13:30 | 0.00 | 01-OCT-00:10 |
November | 198852.03 | 06-NOV-16:49 | 37611.08 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 162420.96 | 03-NOV-07:19 | 57203.87 | 06-NOV-06:10 | 27094.54 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 198852.03 | 01-DEC-16:19 | 37611.08 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 177606.28 | 28-DEC-08:20 | 52847.42 | 05-DEC-14:39 | 27115.61 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 173365.24 | 24287.76 | 423497.50 | 132037.59 | 52847.42 | 26920.00 | 0.00 | |||||||
Maximum of Months | 198852.03 | 37611.08 | 778371.69 | 177606.28 | 191290.47 | 48504.91 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 4741.40 | 10-JAN-16:49 | 1438.58 | 11-JAN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 59903.87 | 27-FEB-14:00 | 12919.85 | 27-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 55280.28 | 18-MAR-14:20 | 12749.20 | 18-MAR-14:09 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 184525.31 | 27-APR-14:50 | 40919.94 | 27-APR-12:39 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 160271.65 | 04-MAY-13:50 | 40919.94 | 05-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 170334.59 | 22-JUN-15:20 | 40919.94 | 20-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 229064.98 | 31-JUL-15:00 | 40919.94 | 07-JUL-12:50 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 253259.76 | 29-AUG-14:30 | 40919.94 | 07-AUG-11:20 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 163961.68 | 14-SEP-13:30 | 40919.94 | 11-SEP-13:39 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72099.12 | 04-OCT-11:50 | 13510.89 | 04-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 63576.05 | 04-NOV-13:00 | 13792.55 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18801.29 | 29-DEC-16:10 | 7163.33 | 14-DEC-11:00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4741.40 | 1438.58 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 253259.76 | 40919.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 828541.15 | 10-JAN-16:49 | 198852.03 | 423497.50 | 37611.08 | 98007.26 | 38375.64 | 26802.88 | 0.00 | 4741.40 | 653.36 |
February | 976684.83 | 27-FEB-16:10 | 172247.38 | 541788.89 | 0.00 | 113178.35 | 56756.24 | 26938.13 | 0.00 | 52991.45 | 12784.38 |
March | 1125757.07 | 14-MAR-15:00 | 171862.17 | 660080.29 | 0.00 | 128363.33 | 79080.68 | 26882.88 | 0.00 | 46870.64 | 12617.07 |
April | 1502717.02 | 27-APR-15:20 | 171235.93 | 778371.69 | 0.00 | 143548.64 | 147309.16 | 43386.57 | 0.00 | 177945.10 | 40919.94 |
May | 1046798.49 | 15-MAY-15:20 | 171235.93 | 423497.50 | 0.00 | 97992.72 | 142434.88 | 42759.60 | 0.00 | 155790.03 | 13087.84 |
June | 1220352.70 | 28-JUN-15:30 | 171235.93 | 541788.89 | 0.00 | 113178.03 | 149052.41 | 43788.12 | 0.00 | 160389.39 | 40919.94 |
July | 1432985.07 | 31-JUL-15:20 | 171235.93 | 660080.29 | 0.00 | 128363.33 | 171203.09 | 44162.37 | 0.00 | 217020.12 | 40919.94 |
August | 1608169.36 | 29-AUG-15:09 | 171235.93 | 778371.69 | 0.00 | 143548.64 | 187638.90 | 44596.14 | 0.00 | 241858.13 | 40919.94 |
September | 1097767.74 | 14-SEP-15:09 | 171235.93 | 423497.50 | 0.00 | 97992.72 | 166437.15 | 43226.11 | 0.00 | 154458.40 | 40919.94 |
October | 1061630.54 | 04-OCT-15:39 | 172020.17 | 541788.89 | 0.00 | 113178.37 | 130658.82 | 27384.49 | 0.00 | 63896.02 | 12703.78 |
November | 1118151.23 | 08-NOV-16:40 | 198852.03 | 660080.29 | 37611.08 | 128376.32 | 48826.11 | 26804.05 | 0.00 | 14992.66 | 2608.71 |
December | 1247508.30 | 29-DEC-16:19 | 198852.03 | 778371.69 | 37611.08 | 143561.54 | 39806.26 | 26806.52 | 0.00 | 18090.15 | 4409.04 |
Annual Sum or Average | |||||||||||
Minimum of Months | 828541.15 | 171235.93 | 423497.50 | 0.00 | 97992.72 | 38375.64 | 26802.88 | 0.00 | 4741.40 | 653.36 | |
Maximum of Months | 1608169.36 | 198852.03 | 778371.69 | 37611.08 | 143561.54 | 187638.90 | 44596.14 | 0.00 | 241858.13 | 40919.94 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1185094.12 | 02-JAN-05:10 | 0.00 | 81361.05 | 31-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 601891.84 | 18-FEB-07:10 | 0.00 | 81411.54 | 13-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 402815.06 | 01-MAR-07:10 | 0.00 | 81281.14 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 279564.02 | 19-APR-06:10 | 0.00 | 80487.73 | 04-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 141978.88 | 18-MAY-06:10 | 0.00 | 79352.33 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 3605.88 | 14-JUN-05:00 | 0.00 | 77888.36 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 76428.03 | 06-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 75944.25 | 31-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 33160.15 | 28-SEP-06:10 | 0.00 | 76736.94 | 27-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 198395.91 | 16-OCT-06:30 | 0.00 | 78217.67 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 483362.15 | 24-NOV-07:10 | 0.00 | 79661.15 | 30-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 776651.04 | 26-DEC-07:10 | 0.00 | 80729.64 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 75944.25 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1185094.12 | 0.00 | 81411.54 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 26.82 | 1.00 | 26.92 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 25.95 | 0.00 | 25.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 25.98 | 0.00 | 25.98 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 26.01 | 0.00 | 26.01 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 26.47 | 0.00 | 26.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 26.30 | 0.00 | 26.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 26.38 | 0.00 | 26.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 26.35 | 0.00 | 26.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 26.77 | 1.33 | 26.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 26.58 | 1.67 | 26.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 26.66 | 0.17 | 26.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 25.87 | 0.00 | 25.87 |
Annual Sum or Average | 0.00 | 0.00 | 70.67 | 26.46 | 4.17 | 26.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 25.87 | 0.00 | 25.87 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 26.82 | 1.67 | 26.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.16 | 0.00 | 26.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.63 | 0.00 | 25.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 25.81 | 0.00 | 25.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.16 | 0.00 | 26.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.55 | 0.17 | 19.74 | 0.00 | 19.74 | 0.00 | 19.74 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 19.55 | 0.17 | 19.74 | 0.00 | 19.74 | 0.00 | 19.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.55 | 0.17 | 19.74 | 0.00 | 19.74 | 0.00 | 19.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.83 | 18.95 | 0.83 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
February | 1.00 | 19.10 | 0.17 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
March | 0.17 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
December | 1.33 | 19.04 | 0.17 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
Annual Sum or Average | 6.83 | 19.01 | 1.17 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.83 | 19.29 | 0.83 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.67 | 1.33 | 27.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.60 | 2.00 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.03 | 2.33 | 28.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.95 | 2.33 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.71 | 1.33 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.33 | 27.82 | 9.33 | 27.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.03 | 2.33 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.35 | 0.50 | 27.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.58 | 1.17 | 27.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.56 | 1.50 | 27.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.44 | 0.67 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.68 | 3.00 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.81 | 3.17 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.00 | 1.83 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.78 | 0.83 | 27.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.37 | 0.67 | 27.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
Annual Sum or Average | 0.00 | 0.00 | 13.67 | 27.69 | 13.67 | 27.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.00 | 3.17 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.39 | 0.17 | 27.39 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.38 | 3.17 | 27.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.14 | 3.33 | 28.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.96 | 3.33 | 27.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 27.26 | 7.83 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 26.97 | 5.33 | 27.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.64 | 2.67 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.51 | 0.17 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 67.00 | 27.32 | 26.00 | 27.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 28.14 | 7.83 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 19.09 | 0.67 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
February | 0.50 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
Annual Sum or Average | 3.17 | 19.14 | 0.67 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.36 | 0.67 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
February | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.82 | 1.00 | 27.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.80 | 1.33 | 27.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.09 | 2.67 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.93 | 3.00 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.79 | 1.00 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
Annual Sum or Average | 1.67 | 18.78 | 0.00 | 18.78 | 9.00 | 26.50 | 9.00 | 27.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 19.31 | 0.00 | 19.31 | 3.00 | 28.09 | 3.00 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.52 | 0.67 | 27.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.63 | 0.83 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.56 | 1.67 | 27.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.40 | 0.67 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.81 | 2.17 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.84 | 3.00 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.21 | 1.67 | 28.25 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.71 | 1.00 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.43 | 0.50 | 27.43 |
December | 0.17 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Annual Sum or Average | 1.00 | 18.53 | 0.00 | 18.53 | 12.33 | 27.08 | 12.17 | 27.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 19.24 | 0.00 | 19.24 | 3.00 | 28.21 | 3.00 | 28.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.36 | 0.17 | 27.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.00 | 2.33 | 28.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.87 | 1.00 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.33 | 2.33 | 28.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.10 | 1.83 | 28.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.94 | 1.17 | 27.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Annual Sum or Average | 0.83 | 19.00 | 0.00 | 19.00 | 17.50 | 27.67 | 8.83 | 27.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.42 | 0.00 | 19.42 | 5.17 | 28.33 | 2.33 | 28.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.17 | 17.97 | 9.67 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 |
February | 13.50 | 18.38 | 4.83 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
March | 1.83 | 18.99 | 0.33 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
November | 6.83 | 19.04 | 1.83 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
December | 15.83 | 18.66 | 4.17 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
Annual Sum or Average | 64.50 | 18.37 | 20.83 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.17 | 19.28 | 9.67 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.50 | 16.64 | 1.33 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
February | 5.33 | 17.72 | 0.50 | 17.48 | 0.00 | 17.48 | 0.00 | 17.48 |
March | 1.17 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.72 | 0.67 | 27.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.73 | 1.00 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.91 | 3.17 | 27.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.82 | 3.00 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.64 | 0.67 | 27.64 |
October | 0.50 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
November | 3.33 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
December | 8.17 | 17.71 | 0.00 | 17.71 | 0.00 | 17.71 | 0.00 | 17.71 |
Annual Sum or Average | 31.00 | 17.44 | 1.83 | 17.30 | 8.50 | 19.46 | 8.50 | 20.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.50 | 19.37 | 1.33 | 19.37 | 3.17 | 27.91 | 3.17 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.17 | 17.35 | 0.67 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
February | 2.67 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
March | 0.83 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.51 | 0.83 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.57 | 1.50 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.48 | 0.50 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.78 | 2.67 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.90 | 2.67 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.24 | 1.67 | 28.24 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.68 | 0.33 | 27.68 |
November | 2.67 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
December | 5.67 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 |
Annual Sum or Average | 21.00 | 18.08 | 0.67 | 17.99 | 10.50 | 21.20 | 10.17 | 22.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.20 | 0.00 | 17.20 |
Maximum of Months | 9.17 | 18.72 | 0.67 | 18.72 | 2.83 | 28.24 | 2.67 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.50 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
February | 2.50 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 |
March | 0.50 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.04 | 2.17 | 28.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.92 | 1.00 | 27.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.34 | 2.50 | 28.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.22 | 1.50 | 28.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.91 | 1.00 | 27.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
December | 4.33 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
Annual Sum or Average | 14.17 | 18.63 | 0.00 | 18.63 | 17.00 | 23.82 | 8.17 | 24.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.50 | 18.95 | 0.00 | 18.95 | 5.33 | 28.34 | 2.50 | 28.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 120.83 | 24.02 | 68.83 | 24.72 | 0.00 | 24.72 |
February | 74.33 | 24.02 | 88.50 | 24.90 | 0.00 | 24.90 |
March | 42.83 | 24.01 | 101.67 | 25.33 | 0.00 | 25.33 |
April | 7.67 | 24.00 | 157.17 | 25.49 | 0.00 | 25.49 |
May | 1.50 | 24.00 | 211.00 | 25.20 | 0.00 | 25.20 |
June | 0.00 | 0.00 | 237.17 | 25.03 | 0.00 | 25.03 |
July | 0.00 | 0.00 | 378.00 | 24.83 | 0.00 | 24.83 |
August | 0.00 | 0.00 | 459.33 | 24.57 | 0.00 | 24.57 |
September | 0.00 | 0.00 | 334.33 | 24.83 | 0.00 | 24.83 |
October | 0.00 | 0.00 | 174.17 | 25.67 | 0.00 | 25.67 |
November | 4.50 | 24.00 | 173.50 | 25.51 | 0.00 | 25.51 |
December | 33.50 | 24.00 | 107.33 | 25.64 | 0.00 | 25.64 |
Annual Sum or Average | 285.17 | 24.01 | 2491.00 | 25.03 | 0.00 | 25.03 |
Minimum of Months | 0.00 | 0.00 | 68.83 | 24.57 | 0.00 | 24.57 |
Maximum of Months | 120.83 | 24.02 | 459.33 | 25.67 | 0.00 | 25.67 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 275.67 | 23.80 | 16.50 | 23.89 | 13.00 | 23.96 |
February | 142.00 | 23.78 | 57.67 | 24.10 | 0.00 | 24.10 |
March | 53.67 | 23.94 | 82.83 | 24.88 | 0.00 | 24.88 |
April | 5.67 | 23.98 | 143.50 | 24.93 | 0.00 | 24.93 |
May | 20.33 | 23.77 | 187.33 | 24.61 | 0.00 | 24.61 |
June | 0.00 | 0.00 | 237.17 | 24.53 | 0.00 | 24.53 |
July | 0.00 | 0.00 | 386.50 | 24.35 | 0.00 | 24.35 |
August | 0.00 | 0.00 | 468.17 | 24.24 | 0.00 | 24.24 |
September | 0.00 | 0.00 | 321.67 | 24.50 | 0.00 | 24.50 |
October | 14.17 | 23.68 | 138.83 | 25.13 | 0.00 | 25.13 |
November | 35.50 | 23.84 | 153.17 | 24.84 | 0.00 | 24.84 |
December | 93.17 | 23.88 | 87.33 | 24.75 | 0.00 | 24.75 |
Annual Sum or Average | 640.17 | 23.82 | 2280.67 | 24.47 | 13.00 | 24.48 |
Minimum of Months | 0.00 | 0.00 | 16.50 | 23.89 | 0.00 | 23.96 |
Maximum of Months | 275.67 | 23.98 | 468.17 | 25.13 | 13.00 | 25.13 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.30 | 14.67 | 22.21 | 14.67 | 22.13 |
February | 439.83 | 22.94 | 0.00 | 22.94 | 0.00 | 22.94 |
March | 407.50 | 23.53 | 0.00 | 23.53 | 0.00 | 23.53 |
April | 246.17 | 23.56 | 30.50 | 23.69 | 0.00 | 23.69 |
May | 133.17 | 23.55 | 77.33 | 23.89 | 0.00 | 23.89 |
June | 59.00 | 23.60 | 118.83 | 24.23 | 0.00 | 24.23 |
July | 16.33 | 23.56 | 256.50 | 24.34 | 0.00 | 24.34 |
August | 16.83 | 23.43 | 362.00 | 24.22 | 0.00 | 24.22 |
September | 56.17 | 23.45 | 210.00 | 24.23 | 0.00 | 24.23 |
October | 238.83 | 23.41 | 34.00 | 23.60 | 0.00 | 23.60 |
November | 393.33 | 23.20 | 11.67 | 23.23 | 0.00 | 23.23 |
December | 494.33 | 22.78 | 0.00 | 22.78 | 0.00 | 22.78 |
Annual Sum or Average | 3003.50 | 23.06 | 1115.50 | 23.41 | 14.67 | 23.40 |
Minimum of Months | 16.33 | 22.30 | 0.00 | 22.21 | 0.00 | 22.13 |
Maximum of Months | 502.00 | 23.60 | 362.00 | 24.34 | 14.67 | 24.34 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.90 | 180.00 | 20.56 | 180.00 | 20.37 |
February | 452.00 | 21.42 | 105.67 | 21.14 | 105.67 | 20.95 |
March | 509.50 | 22.29 | 25.67 | 22.21 | 25.67 | 22.13 |
April | 390.83 | 22.84 | 22.00 | 22.93 | 0.00 | 22.93 |
May | 261.17 | 23.21 | 57.33 | 23.40 | 0.00 | 23.40 |
June | 134.67 | 23.41 | 105.33 | 23.81 | 0.00 | 23.81 |
July | 53.83 | 23.47 | 253.50 | 24.14 | 0.00 | 24.14 |
August | 65.00 | 23.32 | 307.67 | 24.05 | 0.00 | 24.05 |
September | 214.33 | 23.14 | 121.17 | 23.53 | 0.00 | 23.53 |
October | 455.83 | 22.55 | 4.17 | 22.54 | 4.17 | 22.52 |
November | 488.50 | 21.74 | 56.17 | 21.58 | 56.17 | 21.45 |
December | 497.00 | 21.15 | 143.00 | 20.91 | 143.00 | 20.76 |
Annual Sum or Average | 4024.67 | 22.07 | 1381.67 | 22.22 | 514.67 | 22.02 |
Minimum of Months | 53.83 | 20.90 | 4.17 | 20.56 | 0.00 | 20.37 |
Maximum of Months | 509.50 | 23.47 | 307.67 | 24.14 | 180.00 | 24.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.12 | 13.00 | 22.09 | 13.00 | 22.06 |
February | 422.00 | 22.57 | 3.83 | 22.56 | 3.17 | 22.55 |
March | 440.33 | 23.33 | 0.00 | 23.33 | 0.00 | 23.33 |
April | 246.00 | 23.59 | 44.00 | 23.72 | 0.00 | 23.72 |
May | 163.33 | 23.56 | 96.50 | 23.89 | 0.00 | 23.89 |
June | 30.83 | 23.61 | 167.00 | 24.32 | 0.00 | 24.32 |
July | 0.50 | 23.80 | 349.33 | 24.34 | 0.00 | 24.34 |
August | 5.33 | 23.61 | 407.33 | 24.22 | 0.00 | 24.22 |
September | 116.00 | 23.41 | 166.67 | 23.99 | 0.00 | 23.99 |
October | 318.17 | 23.32 | 19.33 | 23.43 | 0.00 | 23.43 |
November | 406.00 | 23.05 | 12.67 | 23.10 | 0.00 | 23.10 |
December | 497.00 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
Annual Sum or Average | 3147.50 | 22.95 | 1279.67 | 23.35 | 16.17 | 23.34 |
Minimum of Months | 0.50 | 22.12 | 0.00 | 22.09 | 0.00 | 22.06 |
Maximum of Months | 502.00 | 23.80 | 407.33 | 24.34 | 13.00 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.76 | 19.67 | 21.72 | 19.67 | 21.68 |
February | 426.00 | 22.26 | 6.00 | 22.25 | 4.83 | 22.23 |
March | 432.83 | 22.91 | 2.33 | 22.92 | 0.00 | 22.92 |
April | 247.67 | 23.20 | 75.33 | 23.47 | 0.00 | 23.47 |
May | 173.33 | 23.32 | 160.17 | 23.88 | 3.83 | 23.92 |
June | 75.17 | 23.59 | 239.67 | 24.23 | 5.83 | 24.29 |
July | 48.50 | 24.11 | 338.83 | 24.30 | 10.00 | 24.37 |
August | 55.00 | 23.92 | 373.00 | 24.17 | 10.33 | 24.23 |
September | 152.17 | 23.23 | 220.33 | 23.93 | 4.83 | 23.97 |
October | 340.00 | 22.94 | 44.33 | 23.15 | 0.00 | 23.15 |
November | 448.83 | 22.48 | 8.33 | 22.52 | 0.00 | 22.52 |
December | 496.00 | 22.05 | 0.00 | 22.05 | 0.00 | 22.05 |
Annual Sum or Average | 3397.50 | 22.58 | 1488.00 | 23.11 | 59.33 | 23.12 |
Minimum of Months | 48.50 | 21.76 | 0.00 | 21.72 | 0.00 | 21.68 |
Maximum of Months | 502.00 | 24.11 | 373.00 | 24.30 | 19.67 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 474.00 | 21.72 | 46.83 | 21.67 | 40.67 | 21.59 |
February | 359.17 | 22.23 | 52.50 | 22.43 | 13.50 | 22.37 |
March | 355.17 | 22.88 | 42.83 | 23.04 | 0.00 | 23.04 |
April | 223.17 | 23.27 | 112.00 | 23.68 | 1.33 | 23.69 |
May | 183.50 | 23.36 | 159.83 | 23.90 | 4.67 | 23.94 |
June | 88.00 | 23.49 | 229.17 | 24.18 | 2.67 | 24.20 |
July | 38.00 | 24.45 | 360.17 | 24.42 | 10.50 | 24.48 |
August | 34.83 | 24.60 | 415.50 | 24.32 | 12.17 | 24.39 |
September | 116.33 | 23.40 | 272.33 | 24.15 | 7.17 | 24.20 |
October | 273.67 | 22.99 | 112.83 | 23.48 | 2.83 | 23.51 |
November | 396.33 | 22.48 | 37.33 | 22.69 | 0.33 | 22.70 |
December | 439.83 | 22.12 | 19.17 | 22.22 | 2.00 | 22.21 |
Annual Sum or Average | 2982.00 | 22.60 | 1860.50 | 23.27 | 97.83 | 23.27 |
Minimum of Months | 34.83 | 21.72 | 19.17 | 21.67 | 0.00 | 21.59 |
Maximum of Months | 474.00 | 24.60 | 415.50 | 24.42 | 40.67 | 24.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 491.67 | 22.52 | 0.00 | 22.52 | 0.00 | 22.52 |
February | 308.83 | 23.17 | 52.67 | 23.44 | 0.17 | 23.44 |
March | 104.17 | 23.62 | 131.33 | 24.40 | 0.00 | 24.40 |
April | 19.00 | 25.78 | 284.33 | 25.00 | 12.00 | 25.07 |
May | 70.33 | 24.10 | 282.00 | 24.56 | 14.33 | 24.66 |
June | 11.50 | 27.00 | 418.67 | 24.61 | 11.50 | 24.67 |
July | 34.33 | 26.95 | 488.17 | 24.82 | 34.33 | 24.95 |
August | 32.67 | 26.90 | 514.00 | 24.68 | 32.67 | 24.81 |
September | 36.00 | 24.71 | 357.00 | 24.61 | 14.17 | 24.69 |
October | 93.50 | 23.46 | 168.83 | 24.50 | 2.33 | 24.52 |
November | 146.67 | 23.49 | 124.50 | 24.18 | 1.00 | 24.19 |
December | 189.00 | 23.56 | 70.00 | 24.08 | 0.00 | 24.08 |
Annual Sum or Average | 1537.67 | 23.39 | 2891.50 | 24.26 | 122.50 | 24.34 |
Minimum of Months | 11.50 | 22.52 | 0.00 | 22.52 | 0.00 | 22.52 |
Maximum of Months | 491.67 | 27.00 | 514.00 | 25.00 | 34.33 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.44 | 315.50 | 20.29 | 315.50 | 20.23 |
February | 454.00 | 20.90 | 185.17 | 20.70 | 185.17 | 20.58 |
March | 514.00 | 21.82 | 36.67 | 21.74 | 36.67 | 21.67 |
April | 438.67 | 22.61 | 12.83 | 22.66 | 0.00 | 22.66 |
May | 315.67 | 23.13 | 42.67 | 23.26 | 0.00 | 23.26 |
June | 163.33 | 23.43 | 65.33 | 23.66 | 0.00 | 23.66 |
July | 73.17 | 23.51 | 220.00 | 24.04 | 0.00 | 24.04 |
August | 99.00 | 23.40 | 270.33 | 23.98 | 0.00 | 23.98 |
September | 286.50 | 23.08 | 70.00 | 23.29 | 0.00 | 23.29 |
October | 488.33 | 22.26 | 3.17 | 22.25 | 3.17 | 22.24 |
November | 489.00 | 21.29 | 111.83 | 21.11 | 111.83 | 20.99 |
December | 497.00 | 20.66 | 260.67 | 20.53 | 260.67 | 20.46 |
Annual Sum or Average | 4320.67 | 21.81 | 1594.17 | 21.83 | 913.00 | 21.62 |
Minimum of Months | 73.17 | 20.44 | 3.17 | 20.29 | 0.00 | 20.23 |
Maximum of Months | 514.00 | 23.51 | 315.50 | 24.04 | 315.50 | 24.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.34 | 287.00 | 20.20 | 287.00 | 20.14 |
February | 385.00 | 20.98 | 154.83 | 20.80 | 154.83 | 20.70 |
March | 424.50 | 21.83 | 19.67 | 21.76 | 19.67 | 21.71 |
April | 294.83 | 22.53 | 38.50 | 22.78 | 0.00 | 22.78 |
May | 237.17 | 22.91 | 82.83 | 23.37 | 3.33 | 23.41 |
June | 125.17 | 23.29 | 158.33 | 24.02 | 4.83 | 24.07 |
July | 87.83 | 23.76 | 246.17 | 24.32 | 11.17 | 24.41 |
August | 87.67 | 23.66 | 278.17 | 24.23 | 11.17 | 24.31 |
September | 214.83 | 22.84 | 128.33 | 23.46 | 3.83 | 23.50 |
October | 377.67 | 22.08 | 16.00 | 22.16 | 2.67 | 22.15 |
November | 417.00 | 21.14 | 106.67 | 20.97 | 106.67 | 20.86 |
December | 422.00 | 20.60 | 238.67 | 20.46 | 238.67 | 20.40 |
Annual Sum or Average | 3500.67 | 21.69 | 1755.17 | 21.97 | 843.83 | 21.76 |
Minimum of Months | 87.67 | 20.34 | 16.00 | 20.20 | 0.00 | 20.14 |
Maximum of Months | 427.00 | 23.76 | 287.00 | 24.32 | 287.00 | 24.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.17 | 20.93 | 228.83 | 20.71 | 225.33 | 20.59 |
February | 383.00 | 21.48 | 109.67 | 21.50 | 80.33 | 21.35 |
March | 393.17 | 22.10 | 49.50 | 22.28 | 11.33 | 22.24 |
April | 290.33 | 22.63 | 87.83 | 23.10 | 1.00 | 23.12 |
May | 244.67 | 23.02 | 127.17 | 23.55 | 4.83 | 23.59 |
June | 164.17 | 23.22 | 158.50 | 23.84 | 2.17 | 23.86 |
July | 94.83 | 23.65 | 307.00 | 24.26 | 9.67 | 24.33 |
August | 90.50 | 23.77 | 351.67 | 24.23 | 13.50 | 24.32 |
September | 167.50 | 23.12 | 235.33 | 23.90 | 7.50 | 23.96 |
October | 329.83 | 22.45 | 99.17 | 22.98 | 3.00 | 23.01 |
November | 438.83 | 21.62 | 77.83 | 21.69 | 50.00 | 21.58 |
December | 458.33 | 21.11 | 181.50 | 20.96 | 174.00 | 20.83 |
Annual Sum or Average | 3545.33 | 22.01 | 2014.00 | 22.50 | 582.67 | 22.34 |
Minimum of Months | 90.50 | 20.93 | 49.50 | 20.71 | 1.00 | 20.59 |
Maximum of Months | 490.17 | 23.77 | 351.67 | 24.26 | 225.33 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.66 | 246.33 | 20.51 | 246.33 | 20.43 |
February | 441.83 | 21.23 | 108.67 | 21.07 | 106.67 | 20.95 |
March | 473.83 | 22.03 | 20.67 | 22.06 | 10.50 | 22.03 |
April | 342.83 | 22.65 | 65.00 | 22.99 | 0.33 | 22.99 |
May | 244.83 | 23.18 | 143.50 | 23.70 | 10.83 | 23.79 |
June | 133.67 | 23.32 | 201.33 | 24.00 | 3.50 | 24.03 |
July | 55.17 | 24.26 | 364.33 | 24.51 | 13.83 | 24.59 |
August | 60.67 | 23.73 | 385.50 | 24.31 | 9.33 | 24.36 |
September | 195.50 | 23.12 | 203.83 | 23.82 | 8.00 | 23.88 |
October | 423.83 | 22.30 | 31.17 | 22.46 | 0.17 | 22.46 |
November | 479.50 | 21.44 | 57.67 | 21.39 | 51.17 | 21.31 |
December | 497.00 | 20.96 | 178.83 | 20.82 | 178.83 | 20.74 |
Annual Sum or Average | 3850.67 | 21.86 | 2006.83 | 22.35 | 639.50 | 22.19 |
Minimum of Months | 55.17 | 20.66 | 20.67 | 20.51 | 0.17 | 20.43 |
Maximum of Months | 502.00 | 24.26 | 385.50 | 24.51 | 246.33 | 24.59 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.98 | 417.00 | 19.88 | 417.00 | 19.84 |
February | 454.00 | 20.30 | 302.33 | 20.12 | 302.33 | 20.05 |
March | 514.00 | 20.94 | 208.83 | 20.75 | 208.83 | 20.64 |
April | 457.33 | 21.87 | 69.00 | 21.74 | 61.67 | 21.61 |
May | 370.00 | 22.56 | 43.00 | 22.69 | 3.50 | 22.67 |
June | 228.67 | 23.08 | 70.17 | 23.34 | 0.00 | 23.34 |
July | 137.17 | 23.29 | 210.50 | 23.85 | 0.00 | 23.85 |
August | 165.33 | 23.11 | 242.83 | 23.74 | 0.00 | 23.74 |
September | 363.00 | 22.50 | 49.00 | 22.69 | 0.00 | 22.69 |
October | 502.00 | 21.35 | 92.67 | 21.15 | 92.67 | 21.00 |
November | 489.00 | 20.47 | 255.17 | 20.26 | 255.17 | 20.15 |
December | 497.00 | 20.11 | 423.50 | 20.04 | 423.50 | 20.01 |
Annual Sum or Average | 4679.50 | 21.27 | 2384.00 | 21.19 | 1764.67 | 20.94 |
Minimum of Months | 137.17 | 19.98 | 43.00 | 19.88 | 0.00 | 19.84 |
Maximum of Months | 514.00 | 23.29 | 423.50 | 23.85 | 423.50 | 23.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.01 | 411.83 | 19.91 | 411.83 | 19.87 |
February | 454.00 | 20.44 | 267.17 | 20.25 | 267.17 | 20.16 |
March | 512.00 | 21.23 | 148.67 | 20.98 | 148.67 | 20.83 |
April | 364.83 | 22.06 | 69.33 | 22.07 | 38.00 | 21.94 |
May | 282.00 | 22.43 | 109.17 | 22.93 | 8.67 | 22.91 |
June | 153.00 | 22.98 | 200.67 | 23.82 | 3.33 | 23.85 |
July | 117.50 | 23.52 | 310.33 | 24.16 | 13.33 | 24.24 |
August | 120.67 | 23.40 | 331.67 | 24.07 | 13.67 | 24.15 |
September | 269.33 | 22.29 | 147.67 | 23.01 | 2.67 | 23.04 |
October | 465.83 | 21.49 | 75.67 | 21.31 | 74.33 | 21.16 |
November | 489.00 | 20.52 | 252.67 | 20.31 | 252.67 | 20.21 |
December | 497.00 | 20.14 | 398.17 | 20.05 | 398.17 | 20.01 |
Annual Sum or Average | 4227.17 | 21.23 | 2723.00 | 21.44 | 1632.50 | 21.18 |
Minimum of Months | 117.50 | 20.01 | 69.33 | 19.91 | 2.67 | 19.87 |
Maximum of Months | 512.00 | 23.52 | 411.83 | 24.16 | 411.83 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.00 | 20.32 | 335.50 | 20.10 | 335.50 | 20.01 |
February | 412.50 | 20.90 | 209.50 | 20.70 | 200.00 | 20.55 |
March | 433.17 | 21.41 | 135.50 | 21.28 | 113.83 | 21.10 |
April | 334.67 | 22.01 | 105.50 | 22.27 | 38.67 | 22.14 |
May | 290.50 | 22.44 | 111.83 | 22.97 | 9.33 | 22.99 |
June | 207.50 | 22.84 | 148.67 | 23.53 | 2.67 | 23.55 |
July | 138.67 | 23.30 | 287.67 | 24.07 | 9.83 | 24.13 |
August | 137.67 | 23.26 | 319.00 | 24.02 | 11.33 | 24.09 |
September | 239.67 | 22.55 | 205.33 | 23.41 | 6.67 | 23.46 |
October | 378.00 | 21.68 | 123.17 | 22.01 | 43.83 | 21.88 |
November | 458.67 | 20.83 | 204.83 | 20.69 | 187.67 | 20.54 |
December | 480.67 | 20.51 | 314.83 | 20.28 | 314.83 | 20.18 |
Annual Sum or Average | 4009.67 | 21.47 | 2501.33 | 21.76 | 1274.17 | 21.50 |
Minimum of Months | 137.67 | 20.32 | 105.50 | 20.10 | 2.67 | 20.01 |
Maximum of Months | 498.00 | 23.30 | 335.50 | 24.07 | 335.50 | 24.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.15 | 360.17 | 20.00 | 360.17 | 19.94 |
February | 451.17 | 20.71 | 235.50 | 20.49 | 235.50 | 20.38 |
March | 490.83 | 21.34 | 121.00 | 21.18 | 117.17 | 21.06 |
April | 373.67 | 21.99 | 77.17 | 22.24 | 24.00 | 22.17 |
May | 305.83 | 22.67 | 120.67 | 23.21 | 11.17 | 23.30 |
June | 193.17 | 22.95 | 182.00 | 23.67 | 3.50 | 23.70 |
July | 101.50 | 23.69 | 333.33 | 24.34 | 14.17 | 24.42 |
August | 108.83 | 23.30 | 333.67 | 24.12 | 9.67 | 24.18 |
September | 274.83 | 22.61 | 160.33 | 23.29 | 7.17 | 23.35 |
October | 458.17 | 21.61 | 52.00 | 21.60 | 37.67 | 21.50 |
November | 484.83 | 20.79 | 192.00 | 20.60 | 190.33 | 20.49 |
December | 497.00 | 20.42 | 333.33 | 20.29 | 333.33 | 20.23 |
Annual Sum or Average | 4241.83 | 21.41 | 2501.17 | 21.69 | 1343.83 | 21.46 |
Minimum of Months | 101.50 | 20.15 | 52.00 | 20.00 | 3.50 | 19.94 |
Maximum of Months | 502.00 | 23.69 | 360.17 | 24.34 | 360.17 | 24.42 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 4.83 | 27.00 | 514.00 | 27.00 | 4.83 | 27.00 |
April | 49.17 | 27.00 | 485.00 | 27.00 | 49.17 | 27.00 |
May | 0.17 | 27.00 | 508.00 | 27.00 | 0.17 | 27.00 |
June | 10.17 | 27.00 | 496.00 | 27.00 | 10.17 | 27.00 |
July | 107.00 | 27.00 | 497.00 | 27.00 | 107.00 | 27.00 |
August | 259.67 | 27.00 | 514.00 | 27.00 | 259.67 | 27.00 |
September | 9.00 | 27.00 | 485.00 | 27.00 | 9.00 | 27.00 |
October | 6.00 | 27.00 | 502.00 | 27.00 | 6.00 | 27.00 |
November | 1.33 | 27.00 | 489.00 | 27.00 | 1.33 | 27.00 |
December | 0.83 | 27.00 | 497.00 | 27.00 | 0.83 | 27.00 |
Annual Sum or Average | 448.17 | 27.00 | 5943.00 | 27.00 | 448.17 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 259.67 | 27.00 | 514.00 | 27.00 | 259.67 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.33 | 24.92 | 418.00 | 26.92 | 0.00 | 26.92 |
February | 0.00 | 0.00 | 424.83 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 3.67 | 27.00 | 485.00 | 27.00 | 3.67 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 1.67 | 27.00 | 496.00 | 27.00 | 1.67 | 27.00 |
July | 13.50 | 27.00 | 497.00 | 27.00 | 13.50 | 27.00 |
August | 27.00 | 27.00 | 514.00 | 27.00 | 27.00 | 27.00 |
September | 1.83 | 27.00 | 485.00 | 27.00 | 1.83 | 27.00 |
October | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 62.00 | 26.52 | 5829.83 | 26.99 | 47.67 | 26.99 |
Minimum of Months | 0.00 | 0.00 | 418.00 | 26.92 | 0.00 | 26.92 |
Maximum of Months | 27.00 | 27.00 | 514.00 | 27.00 | 27.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 131.17 | 24.63 | 270.67 | 26.08 | 12.00 | 25.97 |
February | 24.17 | 27.00 | 335.83 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 475.33 | 27.00 | 0.00 | 27.00 |
April | 5.33 | 27.00 | 485.00 | 27.00 | 5.33 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 3.50 | 27.00 | 496.00 | 27.00 | 3.50 | 27.00 |
July | 26.50 | 27.00 | 497.00 | 27.00 | 26.50 | 27.00 |
August | 55.33 | 27.00 | 514.00 | 27.00 | 55.33 | 27.00 |
September | 3.17 | 27.00 | 485.00 | 27.00 | 3.17 | 27.00 |
October | 0.00 | 0.00 | 500.50 | 27.00 | 0.00 | 27.00 |
November | 0.00 | 0.00 | 452.00 | 27.00 | 0.00 | 27.00 |
December | 7.17 | 27.00 | 404.83 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 256.33 | 25.79 | 5424.17 | 26.93 | 105.83 | 26.93 |
Minimum of Months | 0.00 | 0.00 | 270.67 | 26.08 | 0.00 | 25.97 |
Maximum of Months | 131.17 | 27.00 | 514.00 | 27.00 | 55.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5943.00 | 27.00 | 5943.00 | 27.00 | 5943.00 | 27.00 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 26.82835 | 0.76129 | 17.29561 |
February | 454.00000 | 27.00006 | 27.08342 | 0.82970 | 19.63896 |
March | 514.00000 | 27.00003 | 27.98879 | 0.89886 | 22.12197 |
April | 485.00000 | 27.00002 | 30.74943 | 0.97481 | 25.11567 |
May | 508.00000 | 27.00024 | 33.73961 | 0.22982 | 6.17003 |
June | 496.00000 | 27.00027 | 34.99844 | 0.30330 | 6.95813 |
July | 497.00000 | 27.00033 | 36.08103 | 0.37844 | 8.03720 |
August | 514.00000 | 27.00022 | 36.55744 | 0.41884 | 8.71759 |
September | 485.00000 | 27.00060 | 36.61416 | 0.26349 | 6.51457 |
October | 502.00000 | 27.00012 | 33.26137 | 0.91975 | 22.90160 |
November | 489.00000 | 27.00009 | 31.30140 | 0.91413 | 22.69904 |
December | 497.00000 | 27.00000 | 27.22898 | 0.89881 | 22.09594 |
Annual Sum or Average | 5943.00000 | 27.00017 | 31.89962 | 0.64739 | 15.64006 |
Minimum of Months | 454.00000 | 27.00000 | 26.82835 | 0.22982 | 6.17003 |
Maximum of Months | 514.00000 | 27.00060 | 36.61416 | 0.97481 | 25.11567 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.92474 | 27.50013 | 0.61061 | 13.02439 |
February | 454.00000 | 27.00006 | 27.08986 | 0.68286 | 14.97802 |
March | 514.00000 | 27.00003 | 27.96751 | 0.76010 | 17.27426 |
April | 485.00000 | 27.00002 | 30.72653 | 0.84025 | 19.99544 |
May | 508.00000 | 27.00022 | 33.76408 | 0.14585 | 5.56086 |
June | 496.00000 | 27.00026 | 34.99634 | 0.20289 | 5.93425 |
July | 497.00000 | 27.00032 | 36.07849 | 0.26493 | 6.54130 |
August | 514.00000 | 27.00024 | 36.55618 | 0.28641 | 6.80737 |
September | 485.00000 | 27.00057 | 36.73764 | 0.18169 | 5.79658 |
October | 502.00000 | 27.00011 | 33.25927 | 0.81041 | 18.92329 |
November | 489.00000 | 27.00008 | 31.28853 | 0.74926 | 16.91718 |
December | 497.00000 | 27.00000 | 27.21749 | 0.69026 | 15.09126 |
Annual Sum or Average | 5943.00000 | 26.99380 | 31.96262 | 0.51704 | 12.20209 |
Minimum of Months | 454.00000 | 26.92474 | 27.08986 | 0.14585 | 5.56086 |
Maximum of Months | 514.00000 | 27.00057 | 36.73764 | 0.84025 | 19.99544 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.28591 | 28.01085 | 0.42149 | 10.71094 |
February | 454.00000 | 27.00022 | 27.10653 | 0.60675 | 13.02508 |
March | 514.00000 | 27.00003 | 27.98137 | 0.68563 | 15.07112 |
April | 485.00000 | 27.00002 | 30.73767 | 0.79034 | 18.37368 |
May | 508.00000 | 27.00031 | 33.79889 | 0.10612 | 5.50865 |
June | 496.00000 | 27.00026 | 35.01254 | 0.18693 | 5.90189 |
July | 497.00000 | 27.00033 | 36.08916 | 0.26071 | 6.58389 |
August | 514.00000 | 27.00022 | 36.56860 | 0.27524 | 6.77674 |
September | 485.00000 | 27.00051 | 36.86582 | 0.13604 | 5.63467 |
October | 502.00000 | 27.00011 | 33.30193 | 0.74229 | 16.74851 |
November | 489.00000 | 27.00009 | 31.31410 | 0.66519 | 14.45074 |
December | 497.00000 | 27.00000 | 27.22319 | 0.60743 | 12.87711 |
Annual Sum or Average | 5943.00000 | 26.93986 | 32.03208 | 0.45537 | 10.94332 |
Minimum of Months | 454.00000 | 26.28591 | 27.10653 | 0.10612 | 5.50865 |
Maximum of Months | 514.00000 | 27.00051 | 36.86582 | 0.79034 | 18.37368 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 40.36170 | 1.10003 | 30.52197 |
February | 454.00000 | 27.00000 | 39.98069 | 1.27281 | 38.88372 |
March | 514.00000 | 27.00000 | 40.15168 | 1.43411 | 47.33886 |
April | 485.00000 | 27.00000 | 40.12256 | 1.57513 | 54.99080 |
May | 508.00000 | 27.00000 | 40.36924 | 0.55329 | 11.44781 |
June | 496.00000 | 27.00000 | 40.20470 | 0.78070 | 17.85271 |
July | 497.00000 | 27.00000 | 40.19853 | 0.99277 | 25.82413 |
August | 514.00000 | 27.00000 | 40.10546 | 1.18570 | 34.55596 |
September | 485.00000 | 27.00000 | 40.38514 | 0.58111 | 12.10982 |
October | 502.00000 | 27.00000 | 40.10456 | 1.30955 | 40.76424 |
November | 489.00000 | 27.00000 | 40.17937 | 1.44561 | 47.95744 |
December | 497.00000 | 27.00000 | 40.19726 | 1.56820 | 54.61298 |
Annual Sum or Average | 5943.00000 | 27.00000 | 40.19809 | 1.14888 | 34.69216 |
Minimum of Months | 454.00000 | 27.00000 | 39.98069 | 0.55329 | 11.44781 |
Maximum of Months | 514.00000 | 27.00000 | 40.38514 | 1.57513 | 54.99080 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.43499 | 27.51101 | 0.35263 | 7.91106 |
February | 454.00000 | 24.44987 | 28.63990 | 0.37191 | 8.23908 |
March | 514.00000 | 24.43704 | 28.32877 | 0.37983 | 8.33591 |
April | 485.00000 | 24.54406 | 31.85379 | 0.43267 | 9.42901 |
May | 508.00000 | 24.52249 | 36.48291 | -0.3982 | 9.20804 |
June | 496.00000 | 24.50003 | 38.52811 | -0.3799 | 8.82523 |
July | 497.00000 | 24.63541 | 43.86208 | -0.2969 | 7.95619 |
August | 514.00000 | 24.51378 | 47.79258 | -0.2981 | 7.70327 |
September | 485.00000 | 24.57506 | 44.03561 | -0.3169 | 8.19881 |
October | 502.00000 | 24.59481 | 35.02689 | 0.46990 | 10.20404 |
November | 489.00000 | 24.58345 | 33.40261 | 0.45163 | 9.86488 |
December | 497.00000 | 24.53398 | 28.04251 | 0.39543 | 8.72660 |
Annual Sum or Average | 5943.00000 | 24.52711 | 35.34292 | 0.09406 | 8.71584 |
Minimum of Months | 454.00000 | 24.43499 | 27.51101 | -0.3982 | 7.70327 |
Maximum of Months | 514.00000 | 24.63541 | 47.79258 | 0.46990 | 10.20404 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.99427 | 32.39530 | 0.27935 | 7.19807 |
February | 454.00000 | 24.15581 | 30.90991 | 0.32130 | 7.42534 |
March | 514.00000 | 24.28279 | 29.96217 | 0.36569 | 8.03036 |
April | 485.00000 | 24.31558 | 32.93421 | 0.40961 | 8.76414 |
May | 508.00000 | 24.26310 | 38.06239 | -0.4515 | 9.72121 |
June | 496.00000 | 24.25856 | 40.07049 | -0.4182 | 9.01359 |
July | 497.00000 | 24.27829 | 44.84409 | -0.3673 | 8.11149 |
August | 514.00000 | 24.21872 | 48.48087 | -0.3500 | 7.76523 |
September | 485.00000 | 24.32481 | 45.64650 | -0.3741 | 8.51740 |
October | 502.00000 | 24.35227 | 36.81513 | 0.43005 | 9.20233 |
November | 489.00000 | 24.35057 | 35.45141 | 0.41246 | 8.88625 |
December | 497.00000 | 24.32240 | 30.35523 | 0.36444 | 8.05727 |
Annual Sum or Average | 5943.00000 | 24.25996 | 37.20824 | 0.04891 | 8.39558 |
Minimum of Months | 454.00000 | 23.99427 | 29.96217 | -0.4515 | 7.19807 |
Maximum of Months | 514.00000 | 24.35227 | 48.48087 | 0.43005 | 9.72121 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.29999 | 35.47680 | -0.1567 | 6.35150 |
February | 454.00000 | 22.97350 | 34.24324 | 0.01428 | 5.70416 |
March | 514.00000 | 23.63604 | 32.70897 | 0.18280 | 6.00494 |
April | 485.00000 | 23.87495 | 35.29979 | 0.27162 | 6.85732 |
May | 508.00000 | 24.00275 | 39.20324 | -0.5660 | 12.10104 |
June | 496.00000 | 24.06550 | 41.02058 | -0.5177 | 10.87693 |
July | 497.00000 | 24.15635 | 46.09369 | -0.4508 | 9.60118 |
August | 514.00000 | 24.13288 | 49.55038 | -0.4276 | 9.16393 |
September | 485.00000 | 24.09068 | 46.79013 | -0.4797 | 10.23281 |
October | 502.00000 | 23.81571 | 39.14502 | 0.27783 | 6.94233 |
November | 489.00000 | 23.36796 | 39.32914 | 0.14870 | 6.01531 |
December | 497.00000 | 22.79035 | 34.62023 | -0.0324 | 5.57556 |
Annual Sum or Average | 5943.00000 | 23.60524 | 39.49348 | -0.1466 | 7.97161 |
Minimum of Months | 454.00000 | 22.29999 | 32.70897 | -0.5660 | 5.57556 |
Maximum of Months | 514.00000 | 24.15635 | 49.55038 | 0.27783 | 12.10104 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.89705 | 36.03891 | -0.5202 | 13.28857 |
February | 454.00000 | 21.43383 | 36.56190 | -0.3715 | 10.14908 |
March | 514.00000 | 22.30541 | 35.55879 | -0.1470 | 6.59746 |
April | 485.00000 | 23.09321 | 37.39147 | 0.07776 | 6.20359 |
May | 508.00000 | 23.62529 | 40.42349 | -0.7014 | 16.42237 |
June | 496.00000 | 23.92839 | 41.46463 | -0.5652 | 12.15697 |
July | 497.00000 | 24.07706 | 46.30859 | -0.4714 | 10.04630 |
August | 514.00000 | 24.00939 | 49.94680 | -0.4667 | 10.02409 |
September | 485.00000 | 23.66743 | 48.52613 | -0.6343 | 14.40599 |
October | 502.00000 | 22.68722 | 42.58376 | -0.0029 | 6.13244 |
November | 489.00000 | 21.74674 | 43.30023 | -0.2532 | 7.73587 |
December | 497.00000 | 21.14858 | 37.43781 | -0.4474 | 10.48365 |
Annual Sum or Average | 5943.00000 | 22.72866 | 41.32340 | -0.3759 | 10.30705 |
Minimum of Months | 454.00000 | 20.89705 | 35.55879 | -0.7014 | 6.13244 |
Maximum of Months | 514.00000 | 24.07706 | 49.94680 | 0.07776 | 16.42237 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.12483 | 32.42090 | -0.1985 | 6.60901 |
February | 454.00000 | 22.67968 | 32.21054 | -0.0586 | 6.11464 |
March | 514.00000 | 23.43889 | 31.08299 | 0.12589 | 5.79652 |
April | 485.00000 | 23.87341 | 33.25374 | 0.26831 | 6.86824 |
May | 508.00000 | 23.97811 | 37.76931 | -0.5742 | 12.56199 |
June | 496.00000 | 24.15933 | 39.48119 | -0.4702 | 9.94115 |
July | 497.00000 | 24.24970 | 44.10264 | -0.3860 | 8.39788 |
August | 514.00000 | 24.17576 | 47.83590 | -0.3827 | 8.31287 |
September | 485.00000 | 23.99398 | 45.80971 | -0.5241 | 11.37547 |
October | 502.00000 | 23.63784 | 37.92664 | 0.22264 | 6.46336 |
November | 489.00000 | 23.23051 | 37.23787 | 0.10833 | 5.90983 |
December | 497.00000 | 22.79086 | 32.32919 | -0.0357 | 5.42479 |
Annual Sum or Average | 5943.00000 | 23.53388 | 37.66003 | -0.1602 | 7.82616 |
Minimum of Months | 454.00000 | 22.12483 | 31.08299 | -0.5742 | 5.42479 |
Maximum of Months | 514.00000 | 24.24970 | 47.83590 | 0.26831 | 12.56199 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.76339 | 32.35738 | -0.2733 | 7.19206 |
February | 454.00000 | 22.37889 | 32.17229 | -0.1147 | 6.44822 |
March | 514.00000 | 23.09657 | 31.13252 | 0.06828 | 5.81532 |
April | 485.00000 | 23.65376 | 33.30558 | 0.25330 | 7.08227 |
May | 508.00000 | 23.91666 | 37.53919 | -0.5436 | 12.78697 |
June | 496.00000 | 24.11917 | 39.28087 | -0.4204 | 9.91587 |
July | 497.00000 | 24.16586 | 44.12199 | -0.3598 | 8.87719 |
August | 514.00000 | 24.06382 | 47.98547 | -0.3593 | 8.87906 |
September | 485.00000 | 23.90942 | 45.62326 | -0.4957 | 11.81702 |
October | 502.00000 | 23.35107 | 37.98045 | 0.18075 | 6.53408 |
November | 489.00000 | 22.61810 | 37.80872 | -0.0204 | 5.89835 |
December | 497.00000 | 22.05300 | 32.91624 | -0.1938 | 6.30634 |
Annual Sum or Average | 5943.00000 | 23.26432 | 37.72381 | -0.1911 | 8.14094 |
Minimum of Months | 454.00000 | 21.76339 | 31.13252 | -0.5436 | 5.81532 |
Maximum of Months | 514.00000 | 24.16586 | 47.98547 | 0.25330 | 12.78697 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.87295 | 32.37747 | -0.2526 | 7.83138 |
February | 454.00000 | 22.69182 | 31.60032 | -0.0342 | 7.23126 |
March | 514.00000 | 23.27445 | 30.61563 | 0.12466 | 6.48895 |
April | 485.00000 | 23.78263 | 32.90500 | 0.28913 | 7.76262 |
May | 508.00000 | 23.91873 | 37.49037 | -0.5486 | 13.11683 |
June | 496.00000 | 24.11615 | 39.35956 | -0.4482 | 10.28893 |
July | 497.00000 | 24.26781 | 43.80593 | -0.3283 | 8.36545 |
August | 514.00000 | 24.19971 | 47.46137 | -0.3029 | 7.99657 |
September | 485.00000 | 24.07420 | 45.01245 | -0.4086 | 10.50362 |
October | 502.00000 | 23.60865 | 37.25255 | 0.26129 | 7.85431 |
November | 489.00000 | 22.84729 | 37.40091 | 0.03368 | 6.70449 |
December | 497.00000 | 22.37602 | 32.42115 | -0.1164 | 6.79787 |
Annual Sum or Average | 5943.00000 | 23.42466 | 37.34876 | -0.1458 | 8.42053 |
Minimum of Months | 454.00000 | 21.87295 | 30.61563 | -0.5486 | 6.48895 |
Maximum of Months | 514.00000 | 24.26781 | 47.46137 | 0.28913 | 13.11683 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.55886 | 30.64620 | -0.0727 | 5.73069 |
February | 454.00000 | 23.57024 | 29.66332 | 0.18643 | 6.74119 |
March | 514.00000 | 24.23833 | 28.47464 | 0.37845 | 8.46050 |
April | 485.00000 | 24.55742 | 31.06401 | 0.53271 | 11.77087 |
May | 508.00000 | 24.30732 | 36.42589 | -0.3618 | 9.39909 |
June | 496.00000 | 24.45541 | 38.26834 | -0.2429 | 7.41978 |
July | 497.00000 | 24.65572 | 42.56999 | -0.0726 | 6.85170 |
August | 514.00000 | 24.54140 | 46.28776 | -0.0680 | 6.56723 |
September | 485.00000 | 24.37635 | 44.06362 | -0.2882 | 8.32233 |
October | 502.00000 | 24.25341 | 35.57246 | 0.42306 | 9.42068 |
November | 489.00000 | 24.14870 | 34.16381 | 0.36539 | 8.49827 |
December | 497.00000 | 24.13173 | 28.78385 | 0.31932 | 7.57175 |
Annual Sum or Average | 5943.00000 | 24.15285 | 35.54234 | 0.09014 | 8.06243 |
Minimum of Months | 454.00000 | 22.55886 | 28.47464 | -0.3618 | 5.73069 |
Maximum of Months | 514.00000 | 24.65572 | 46.28776 | 0.53271 | 11.77087 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.44198 | 34.92684 | -0.6539 | 15.48700 |
February | 454.00000 | 20.90215 | 35.36998 | -0.5085 | 11.97939 |
March | 514.00000 | 21.81835 | 34.67320 | -0.2646 | 7.29819 |
April | 485.00000 | 22.74983 | 36.38936 | -0.0134 | 6.10145 |
May | 508.00000 | 23.48124 | 39.37165 | -0.7617 | 18.47332 |
June | 496.00000 | 23.86625 | 40.64264 | -0.6000 | 13.07599 |
July | 497.00000 | 24.04670 | 45.15777 | -0.4932 | 10.49623 |
August | 514.00000 | 23.96747 | 49.03814 | -0.4956 | 10.69460 |
September | 485.00000 | 23.46775 | 47.73688 | -0.7192 | 16.95534 |
October | 502.00000 | 22.31283 | 41.54517 | -0.0970 | 6.11606 |
November | 489.00000 | 21.28651 | 41.75758 | -0.3666 | 8.94087 |
December | 497.00000 | 20.66436 | 36.22444 | -0.5783 | 12.63908 |
Annual Sum or Average | 5943.00000 | 22.42951 | 40.26615 | -0.4628 | 11.51854 |
Minimum of Months | 454.00000 | 20.44198 | 34.67320 | -0.7617 | 6.10145 |
Maximum of Months | 514.00000 | 24.04670 | 49.03814 | -0.0134 | 18.47332 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.33648 | 33.67353 | -0.6802 | 16.16695 |
February | 385.00000 | 20.97892 | 33.84146 | -0.4868 | 11.18638 |
March | 433.00000 | 21.86878 | 33.26312 | -0.2382 | 7.25110 |
April | 410.00000 | 23.01065 | 34.41235 | 0.07716 | 6.73047 |
May | 430.00000 | 23.51263 | 38.13277 | -0.7030 | 18.13784 |
June | 418.00000 | 23.97723 | 39.51546 | -0.4952 | 12.13003 |
July | 422.00000 | 24.16501 | 44.05925 | -0.3937 | 10.11764 |
August | 433.00000 | 24.09062 | 47.77279 | -0.3850 | 9.99234 |
September | 410.00000 | 23.50087 | 46.46093 | -0.6548 | 16.83637 |
October | 427.00000 | 22.32867 | 40.20920 | -0.0759 | 6.58072 |
November | 417.00000 | 21.13805 | 40.66894 | -0.3992 | 9.36381 |
December | 422.00000 | 20.59621 | 35.00529 | -0.5954 | 13.05823 |
Annual Sum or Average | 5034.00000 | 22.46757 | 38.94760 | -0.4192 | 11.46273 |
Minimum of Months | 385.00000 | 20.33648 | 33.26312 | -0.7030 | 6.58072 |
Maximum of Months | 433.00000 | 24.16501 | 47.77279 | 0.07716 | 18.13784 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.01398 | 33.47463 | -0.4938 | 12.40248 |
February | 454.00000 | 21.93889 | 32.97902 | -0.2282 | 9.20369 |
March | 514.00000 | 22.60543 | 32.38904 | -0.0369 | 7.16047 |
April | 485.00000 | 23.30408 | 34.27427 | 0.16378 | 7.49287 |
May | 508.00000 | 23.64530 | 38.27994 | -0.6484 | 16.47718 |
June | 496.00000 | 23.89113 | 40.07729 | -0.5412 | 12.74007 |
July | 497.00000 | 24.15582 | 44.43949 | -0.3917 | 9.80542 |
August | 514.00000 | 24.10844 | 48.05227 | -0.3610 | 9.44286 |
September | 485.00000 | 23.87068 | 45.68837 | -0.4786 | 12.65976 |
October | 502.00000 | 23.11696 | 38.69804 | 0.14315 | 7.80691 |
November | 489.00000 | 21.92449 | 39.76342 | -0.1955 | 8.28065 |
December | 497.00000 | 21.36637 | 34.35868 | -0.3872 | 10.41294 |
Annual Sum or Average | 5943.00000 | 22.91975 | 38.57705 | -0.2890 | 10.33468 |
Minimum of Months | 454.00000 | 21.01398 | 32.38904 | -0.6484 | 7.16047 |
Maximum of Months | 514.00000 | 24.15582 | 48.05227 | 0.16378 | 16.47718 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.66468 | 33.69582 | -0.5793 | 13.11619 |
February | 454.00000 | 21.30834 | 33.85788 | -0.3879 | 9.80984 |
March | 514.00000 | 22.20650 | 33.07410 | -0.1460 | 6.76053 |
April | 485.00000 | 23.15261 | 34.63651 | 0.12309 | 7.04989 |
May | 508.00000 | 23.71370 | 38.16260 | -0.6105 | 15.61944 |
June | 496.00000 | 23.97592 | 39.86629 | -0.4853 | 11.45404 |
July | 497.00000 | 24.34330 | 43.86672 | -0.2878 | 8.51784 |
August | 514.00000 | 24.19247 | 47.86405 | -0.3223 | 8.81064 |
September | 485.00000 | 23.78819 | 46.02469 | -0.5342 | 13.43578 |
October | 502.00000 | 22.61221 | 39.91798 | 0.00213 | 6.40690 |
November | 489.00000 | 21.49799 | 40.40706 | -0.2983 | 8.04213 |
December | 497.00000 | 20.95592 | 34.82704 | -0.4867 | 10.56007 |
Annual Sum or Average | 5943.00000 | 22.71230 | 38.88249 | -0.3345 | 9.96527 |
Minimum of Months | 454.00000 | 20.66468 | 33.07410 | -0.6105 | 6.40690 |
Maximum of Months | 514.00000 | 24.34330 | 47.86405 | 0.12309 | 15.61944 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.97582 | 36.03235 | -0.8173 | 21.84868 |
February | 454.00000 | 20.29626 | 36.56191 | -0.7042 | 18.15124 |
March | 514.00000 | 20.94335 | 36.39241 | -0.5051 | 11.66878 |
April | 485.00000 | 21.98697 | 37.98120 | -0.2067 | 7.73233 |
May | 508.00000 | 22.95946 | 40.68497 | -0.9412 | 26.19145 |
June | 496.00000 | 23.61851 | 41.29772 | -0.6843 | 16.15350 |
July | 497.00000 | 23.90168 | 45.48758 | -0.5389 | 11.99025 |
August | 514.00000 | 23.78175 | 49.57955 | -0.5570 | 12.66711 |
September | 485.00000 | 22.87787 | 49.53044 | -0.9229 | 25.16056 |
October | 502.00000 | 21.35157 | 44.02126 | -0.3465 | 8.85953 |
November | 489.00000 | 20.46918 | 43.71191 | -0.6092 | 14.85396 |
December | 497.00000 | 20.10759 | 37.49355 | -0.7720 | 19.57114 |
Annual Sum or Average | 5943.00000 | 21.86929 | 41.59299 | -0.6335 | 16.21822 |
Minimum of Months | 454.00000 | 19.97582 | 36.03235 | -0.9412 | 7.73233 |
Maximum of Months | 514.00000 | 23.90168 | 49.57955 | -0.2067 | 26.19145 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.00697 | 35.32780 | -0.8065 | 21.39324 |
February | 454.00000 | 20.43520 | 35.69072 | -0.6573 | 16.37180 |
March | 514.00000 | 21.23711 | 35.26336 | -0.4152 | 10.36638 |
April | 485.00000 | 22.55763 | 36.07745 | -0.0377 | 7.47124 |
May | 508.00000 | 23.21173 | 39.42280 | -0.8010 | 22.40824 |
June | 496.00000 | 23.85101 | 40.01725 | -0.5254 | 13.26978 |
July | 497.00000 | 24.05646 | 44.60727 | -0.4081 | 10.64586 |
August | 514.00000 | 23.96575 | 48.47442 | -0.4068 | 10.70745 |
September | 485.00000 | 23.12350 | 48.08694 | -0.7797 | 21.97358 |
October | 502.00000 | 21.67191 | 42.55777 | -0.2524 | 8.38356 |
November | 489.00000 | 20.51623 | 42.87200 | -0.5930 | 14.34636 |
December | 497.00000 | 20.14313 | 36.75221 | -0.7589 | 19.08457 |
Annual Sum or Average | 5943.00000 | 22.07829 | 40.45743 | -0.5362 | 14.68114 |
Minimum of Months | 454.00000 | 20.00697 | 35.26336 | -0.8065 | 7.47124 |
Maximum of Months | 514.00000 | 24.05646 | 48.47442 | -0.0377 | 22.40824 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.34980 | 34.78968 | -0.6952 | 18.36105 |
February | 454.00000 | 21.19849 | 34.31023 | -0.4486 | 13.18533 |
March | 514.00000 | 21.83657 | 34.03251 | -0.2523 | 9.65922 |
April | 485.00000 | 22.70184 | 35.64906 | 0.00496 | 8.10963 |
May | 508.00000 | 23.19241 | 39.41483 | -0.8069 | 23.00259 |
June | 496.00000 | 23.64286 | 40.68224 | -0.6239 | 15.90424 |
July | 497.00000 | 23.99497 | 44.79018 | -0.4394 | 11.44881 |
August | 514.00000 | 23.92826 | 48.55574 | -0.4175 | 11.25335 |
September | 485.00000 | 23.41393 | 47.07539 | -0.6404 | 18.59676 |
October | 502.00000 | 22.33750 | 40.82372 | -0.0664 | 8.58859 |
November | 489.00000 | 21.05435 | 41.70527 | -0.4466 | 12.26364 |
December | 497.00000 | 20.62676 | 35.92498 | -0.6146 | 16.20529 |
Annual Sum or Average | 5943.00000 | 22.36641 | 39.84804 | -0.4543 | 13.88715 |
Minimum of Months | 454.00000 | 20.34980 | 34.03251 | -0.8069 | 8.10963 |
Maximum of Months | 514.00000 | 23.99497 | 48.55574 | 0.00496 | 23.00259 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.15376 | 34.86195 | -0.7454 | 19.24565 |
February | 454.00000 | 20.73102 | 34.92347 | -0.5659 | 14.29285 |
March | 514.00000 | 21.46471 | 34.54256 | -0.3480 | 9.37529 |
April | 485.00000 | 22.52876 | 35.98361 | -0.0354 | 7.72038 |
May | 508.00000 | 23.26786 | 39.21986 | -0.7639 | 21.68343 |
June | 496.00000 | 23.72869 | 40.43249 | -0.5670 | 14.32911 |
July | 497.00000 | 24.20193 | 44.17819 | -0.3297 | 9.72917 |
August | 514.00000 | 24.01296 | 48.35780 | -0.3790 | 10.42948 |
September | 485.00000 | 23.31314 | 47.42514 | -0.6986 | 19.35452 |
October | 502.00000 | 21.84244 | 41.94642 | -0.1990 | 7.72175 |
November | 489.00000 | 20.81708 | 41.95322 | -0.5011 | 11.84910 |
December | 497.00000 | 20.42429 | 35.95327 | -0.6635 | 15.70611 |
Annual Sum or Average | 5943.00000 | 22.21960 | 40.01275 | -0.4827 | 13.44364 |
Minimum of Months | 454.00000 | 20.15376 | 34.54256 | -0.7639 | 7.72038 |
Maximum of Months | 514.00000 | 24.20193 | 48.35780 | -0.0354 | 21.68343 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.125774E+09 | 2055.42 | 02-JAN-05:23 | 17.18 | 0.646821E+09 | 0.00 | 0.772595E+09 | 0.12 | 5.23 | 26-JAN-06:30 | 0.00 | 0.00 |
February | 0.105224E+10 | 49978.72 | 27-FEB-15:00 | 31.81 | 0.640063E+10 | 0.00 | 0.745287E+10 | 0.25 | 7.36 | 27-FEB-15:00 | 0.00 | 0.00 |
March | 0.167089E+10 | 41327.63 | 18-MAR-14:10 | 50.29 | 0.915109E+10 | 0.00 | 0.108220E+11 | 0.35 | 6.85 | 18-MAR-14:10 | 0.00 | 0.00 |
April | 0.105354E+11 | 79887.49 | 27-APR-14:50 | 124.07 | 0.688522E+11 | 0.00 | 0.793876E+11 | 0.99 | 7.73 | 27-APR-10:40 | 0.00 | 0.00 |
May | 0.211126E+11 | 83127.34 | 04-MAY-15:30 | 192.97 | 0.137991E+12 | 0.00 | 0.159103E+12 | 1.54 | 7.74 | 03-MAY-14:50 | 0.00 | 0.00 |
June | 0.379601E+11 | 78920.91 | 22-JUN-15:20 | 313.91 | 0.252990E+12 | 0.00 | 0.290950E+12 | 2.66 | 7.74 | 19-JUN-14:10 | 0.00 | 0.00 |
July | 0.602582E+11 | 103976.84 | 31-JUL-16:00 | 456.24 | 0.417663E+12 | 0.00 | 0.477921E+12 | 3.85 | 7.75 | 11-JUL-14:10 | 0.00 | 0.00 |
August | 0.717120E+11 | 112930.08 | 29-AUG-14:30 | 507.69 | 0.499447E+12 | 0.00 | 0.571159E+12 | 4.29 | 7.91 | 30-AUG-05:02 | 0.00 | 0.00 |
September | 0.307285E+11 | 78438.82 | 14-SEP-13:30 | 267.81 | 0.204641E+12 | 0.00 | 0.235369E+12 | 2.24 | 7.77 | 14-SEP-10:30 | 0.00 | 0.00 |
October | 0.624212E+10 | 61771.09 | 04-OCT-11:50 | 94.21 | 0.376446E+11 | 0.00 | 0.438867E+11 | 0.69 | 7.70 | 04-OCT-11:50 | 0.00 | 0.00 |
November | 0.125477E+10 | 49535.17 | 04-NOV-14:00 | 42.23 | 0.775755E+10 | 0.00 | 0.901232E+10 | 0.31 | 7.29 | 04-NOV-14:00 | 0.00 | 0.00 |
December | 0.131894E+09 | 5609.58 | 29-DEC-06:02 | 17.50 | 0.677567E+09 | 0.00 | 0.809461E+09 | 0.12 | 5.24 | 19-DEC-06:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242784E+12 | 2115.91 | 0.164386E+13 | 0.00 | 0.188665E+13 | 1.46 | 0.00 | 0.00 | ||||
Minimum of Months | 0.125774E+09 | 2055.42 | 17.18 | 0.646821E+09 | 0.00 | 0.772595E+09 | 0.12 | 5.23 | 0.00 | 0.00 | ||
Maximum of Months | 0.717120E+11 | 112930.08 | 507.69 | 0.499447E+12 | 0.00 | 0.571159E+12 | 4.29 | 7.91 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.180681E+10 | 79887.49 | 27-APR-14:50 | 7.00 | 0.133973E+11 | 0.00 | 0.152041E+11 | 0.07 | 7.68 | 27-APR-11:20 | 0.00 | 0.00 |
May | 0.204924E+10 | 76662.32 | 04-MAY-13:50 | 8.33 | 0.153594E+11 | 0.00 | 0.174086E+11 | 0.08 | 7.69 | 04-MAY-13:40 | 0.00 | 0.00 |
June | 0.426343E+10 | 78920.91 | 22-JUN-15:20 | 17.00 | 0.322750E+11 | 0.00 | 0.365384E+11 | 0.18 | 7.70 | 21-JUN-13:50 | 0.00 | 0.00 |
July | 0.108652E+11 | 103976.84 | 31-JUL-16:00 | 40.60 | 0.799698E+11 | 0.00 | 0.908350E+11 | 0.40 | 7.70 | 19-JUL-13:30 | 0.00 | 0.00 |
August | 0.256503E+11 | 112930.08 | 29-AUG-14:30 | 90.17 | 0.186416E+12 | 0.00 | 0.212066E+12 | 0.88 | 7.68 | 11-AUG-14:30 | 0.00 | 0.00 |
September | 0.483479E+10 | 78438.82 | 14-SEP-13:30 | 19.33 | 0.362361E+11 | 0.00 | 0.410709E+11 | 0.20 | 7.71 | 08-SEP-14:40 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.494699E+11 | 182.43 | 0.363654E+12 | 0.00 | 0.413123E+12 | 0.15 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.256503E+11 | 112930.08 | 90.17 | 0.186416E+12 | 0.00 | 0.212066E+12 | 0.88 | 7.71 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.705525E+09 | 744.00 | 1438.58 | 11-JAN-15:30 | 20998.31 | 05-JAN-16:10 | 19.12 | 18.33 | 2.86 |
February | 0.321108E+10 | 672.00 | 12476.23 | 27-FEB-13:00 | 57869.70 | 27-FEB-16:30 | 22.31 | 18.34 | 2.86 |
March | 0.712899E+10 | 744.00 | 12476.23 | 14-MAR-16:00 | 97687.80 | 31-MAR-24:00 | 25.58 | 18.35 | 2.86 |
April | 0.144589E+11 | 720.00 | 12476.23 | 01-APR-10:30 | 122203.11 | 27-APR-18:10 | 28.97 | 18.69 | 2.86 |
May | 0.886870E+10 | 744.00 | 12476.23 | 02-MAY-15:20 | 55156.44 | 31-MAY-24:00 | 21.35 | 18.72 | 2.86 |
June | 0.182883E+11 | 720.00 | 12476.23 | 01-JUN-13:40 | 80945.38 | 30-JUN-24:00 | 24.67 | 19.17 | 2.86 |
July | 0.270290E+11 | 744.00 | 12476.23 | 01-JUL-12:20 | 111873.11 | 31-JUL-23:13 | 28.65 | 20.25 | 2.86 |
August | 0.299386E+11 | 744.00 | 12476.23 | 01-AUG-00:03 | 131671.11 | 10-AUG-18:30 | 32.34 | 21.28 | 2.86 |
September | 0.119803E+11 | 720.00 | 12476.23 | 01-SEP-14:10 | 50758.94 | 30-SEP-24:00 | 21.58 | 18.85 | 2.86 |
October | 0.802764E+10 | 744.00 | 12476.23 | 03-OCT-12:30 | 69211.03 | 31-OCT-24:00 | 23.18 | 18.38 | 2.86 |
November | 0.668625E+10 | 720.00 | 12476.23 | 04-NOV-10:50 | 83999.61 | 04-NOV-16:05 | 25.25 | 18.35 | 2.86 |
December | 0.589125E+10 | 744.00 | 7163.33 | 14-DEC-12:00 | 104560.84 | 05-DEC-15:50 | 27.47 | 18.33 | 2.86 |
Annual Sum or Average | 0.142215E+12 | 8760.00 | 25.06 | 18.93 | 2.86 | ||||
Minimum of Months | 0.705525E+09 | 672.00 | 1438.58 | 20998.31 | 19.12 | 18.33 | 2.86 | ||
Maximum of Months | 0.299386E+11 | 744.00 | 12476.23 | 131671.11 | 32.34 | 21.28 | 2.86 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 191312.70 | 07-JAN-05:45 | 20.99 | 20.99 | 0.13 |
February | 4798557.49 | 6.00 | 443.62 | 27-FEB-15:10 | 428533.01 | 27-FEB-15:10 | 21.03 | 21.01 | 0.85 |
March | 4098848.00 | 10.75 | 272.97 | 18-MAR-14:10 | 337351.47 | 18-MAR-14:20 | 21.04 | 21.02 | 1.54 |
April | 0.342971E+09 | 59.18 | 14221.85 | 27-APR-12:40 | 968457.24 | 26-APR-14:40 | 21.20 | 21.02 | 5.71 |
May | 0.415771E+09 | 133.62 | 14221.85 | 05-MAY-12:30 | 920283.38 | 04-MAY-15:40 | 21.42 | 21.09 | 11.18 |
June | 0.725597E+09 | 237.72 | 14221.85 | 20-JUN-13:00 | 937918.75 | 27-JUN-14:40 | 21.81 | 21.18 | 19.59 |
July | 0.343883E+10 | 336.13 | 14221.85 | 07-JUL-12:00 | 950768.96 | 19-JUL-13:30 | 22.16 | 21.15 | 26.96 |
August | 0.621776E+10 | 371.91 | 14221.85 | 07-AUG-09:50 | 918018.31 | 21-AUG-13:20 | 22.39 | 21.21 | 30.00 |
September | 0.153151E+10 | 193.86 | 14221.85 | 11-SEP-13:40 | 915436.99 | 08-SEP-14:40 | 21.74 | 21.23 | 16.63 |
October | 31231597.89 | 41.79 | 1034.66 | 04-OCT-15:20 | 797391.37 | 04-OCT-15:00 | 21.12 | 21.03 | 4.27 |
November | 21475971.55 | 6.83 | 1316.32 | 04-NOV-14:00 | 423316.59 | 04-NOV-14:00 | 21.02 | 21.00 | 0.98 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 191204.73 | 26-DEC-07:00 | 20.98 | 20.98 | 0.16 |
Annual Sum or Average | 0.127340E+11 | 1397.80 | 21.41 | 21.08 | 9.90 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 191204.73 | 20.98 | 20.98 | 0.13 | ||
Maximum of Months | 0.621776E+10 | 371.91 | 14221.85 | 968457.24 | 22.39 | 21.23 | 30.00 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 20.99 | 20.99 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.03 | 21.03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.04 | 21.04 | 0.00 |
April | 0.167335E+09 | 5.17 | 14221.85 | 27-APR-12:40 | 968457.24 | 26-APR-14:40 | 21.20 | 21.17 | 0.35 |
May | 24722217.99 | 1.67 | 14221.85 | 05-MAY-13:00 | 920283.38 | 04-MAY-15:40 | 21.42 | 21.41 | 0.11 |
June | 0.186194E+09 | 10.83 | 14221.85 | 20-JUN-13:00 | 937918.75 | 27-JUN-14:40 | 21.81 | 21.74 | 0.74 |
July | 0.128092E+10 | 30.00 | 14221.85 | 07-JUL-12:50 | 950768.96 | 19-JUL-13:30 | 22.16 | 22.01 | 1.98 |
August | 0.361162E+10 | 73.17 | 14221.85 | 07-AUG-11:20 | 918018.31 | 21-AUG-13:20 | 22.39 | 22.04 | 4.83 |
September | 0.556742E+09 | 12.33 | 14221.85 | 11-SEP-13:40 | 915436.99 | 08-SEP-14:40 | 21.74 | 21.68 | 0.84 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.12 | 21.12 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.02 | 21.02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.98 | 20.98 | 0.00 |
Annual Sum or Average | 0.582753E+10 | 133.17 | 21.41 | 21.35 | 0.75 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.98 | 20.98 | 0.00 | ||
Maximum of Months | 0.361162E+10 | 73.17 | 14221.85 | 968457.24 | 22.39 | 22.04 | 4.83 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.268117E+12 | 0.00 | 479.36 | 1374367.53 | 02-JAN-05:01 | 0.00 | 29.33 | 62.06 | 0.49 | 0.00 | 0.05 | 0.72 | 02-JAN-05:01 |
February | 0.142119E+12 | 0.00 | 361.73 | 996126.63 | 23-FEB-06:02 | 0.00 | 26.65 | 55.05 | 0.28 | 0.00 | 0.03 | 0.52 | 23-FEB-06:02 |
March | 0.433615E+11 | 0.00 | 295.78 | 854069.53 | 06-MAR-06:01 | 0.00 | 23.91 | 45.87 | 0.07 | 0.00 | 0.01 | 0.45 | 06-MAR-06:01 |
April | 0.136468E+11 | 0.00 | 125.25 | 213982.68 | 19-APR-06:05 | 0.00 | 23.68 | 33.34 | 0.02 | 0.00 | 0.00 | 0.11 | 19-APR-06:05 |
May | 0.171115E+10 | 0.00 | 42.91 | 121908.46 | 18-MAY-05:02 | 0.00 | 22.45 | 25.74 | 0.00 | 0.00 | 0.00 | 0.06 | 18-MAY-05:02 |
June | 21850097.10 | 0.00 | 5.72 | 2910.34 | 15-JUN-05:08 | 0.00 | 20.79 | 21.26 | 0.00 | 0.00 | 0.00 | 0.00 | 15-JUN-05:08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 20.69 | 20.69 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 20.69 | 20.69 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.307950E+09 | 0.00 | 24.18 | 64368.02 | 27-SEP-05:03 | 0.00 | 20.74 | 22.70 | 0.00 | 0.00 | 0.00 | 0.03 | 27-SEP-05:03 |
October | 0.100283E+11 | 0.00 | 178.41 | 424458.01 | 30-OCT-05:03 | 0.00 | 22.18 | 35.73 | 0.02 | 0.00 | 0.00 | 0.22 | 30-OCT-05:03 |
November | 0.905672E+11 | 0.00 | 334.11 | 960215.87 | 28-NOV-06:02 | 0.00 | 24.41 | 49.84 | 0.16 | 0.00 | 0.02 | 0.50 | 28-NOV-06:02 |
December | 0.197349E+12 | 0.00 | 430.02 | 1229830.10 | 26-DEC-06:03 | 0.00 | 27.05 | 57.60 | 0.35 | 0.00 | 0.04 | 0.64 | 26-DEC-06:03 |
Annual Sum or Average | 0.767230E+12 | 0.00 | 2277.47 | 0.00 | 23.53 | 37.47 | 0.12 | 0.00 | 0.01 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.69 | 20.69 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.268117E+12 | 0.00 | 479.36 | 1374367.53 | 0.00 | 29.33 | 62.06 | 0.49 | 0.00 | 0.05 | 0.72 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 19.12 | 19.12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 22.31 | 22.31 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 25.58 | 25.58 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 28.97 | 28.97 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 21.35 | 21.35 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 24.67 | 24.67 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 28.65 | 28.65 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 32.34 | 32.34 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 21.58 | 21.58 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 23.18 | 23.18 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 25.25 | 25.25 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 27.47 | 27.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 25.06 | 25.06 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.12 | 19.12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 32.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 483.95 | 0.00 | 0.31 | 483.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 | 02-JAN-06:01 | 0.78 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 |
February | 0.673873E+09 | 0.00 | 8.69 | 0.673873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45625.84 | 27-FEB-15:00 | 45625.84 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.878860E+09 | 0.00 | 26.92 | 0.878860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24564.14 | 18-MAR-14:10 | 24564.14 | 18-MAR-14:10 | 0.00 | 0.00 | 0.00 |
April | 0.873833E+10 | 0.00 | 94.84 | 0.873833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105460.50 | 27-APR-14:30 | 105460.50 | 27-APR-14:30 | 0.00 | 0.00 | 0.00 |
May | 0.141854E+11 | 0.00 | 178.33 | 0.141838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84821.97 | 04-MAY-15:00 | 84821.97 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.279831E+11 | 0.00 | 294.24 | 0.279790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95890.01 | 28-JUN-15:20 | 95890.01 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.515590E+11 | 0.00 | 427.18 | 0.506451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127565.89 | 31-JUL-16:00 | 115315.89 | 31-JUL-14:30 | 0.00 | 0.00 | 0.00 |
August | 0.716939E+11 | 0.00 | 491.31 | 0.689923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135330.90 | 29-AUG-14:30 | 121606.48 | 29-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.219998E+11 | 0.00 | 248.72 | 0.216224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95648.39 | 14-SEP-13:10 | 91706.87 | 12-SEP-14:40 | 0.00 | 0.00 | 0.00 |
October | 0.397142E+10 | 0.00 | 74.64 | 0.397142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66232.51 | 04-OCT-15:00 | 66232.51 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.566748E+09 | 0.00 | 10.23 | 0.566748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31427.71 | 04-NOV-14:00 | 31427.71 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 361.45 | 0.00 | 0.27 | 361.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 | 26-DEC-06:05 | 0.78 | 26-DEC-06:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202250E+12 | 0.00 | 1855.69 | 0.198252E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 361.45 | 0.00 | 0.27 | 361.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 | 0.78 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.716939E+11 | 0.00 | 491.31 | 0.689923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135330.90 | 121606.48 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 53644.70 | 0.00 | 16.88 | 53644.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 | 02-JAN-06:13 | 3.70 | 02-JAN-06:13 | 0.00 | 0.00 | 0.00 |
February | 0.387504E+10 | 0.00 | 31.15 | 0.387504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 264204.59 | 27-FEB-15:00 | 264204.59 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.582521E+10 | 0.00 | 47.61 | 0.582521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 220904.45 | 18-MAR-14:00 | 220904.45 | 18-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.632318E+11 | 0.00 | 106.79 | 0.632318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 859974.23 | 27-APR-14:50 | 859974.23 | 27-APR-14:50 | 0.00 | 0.00 | 0.00 |
May | 0.120778E+12 | 0.00 | 179.32 | 0.120753E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 773730.69 | 04-MAY-15:00 | 773730.69 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.224631E+12 | 0.00 | 281.97 | 0.224602E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 842520.92 | 28-JUN-15:30 | 842520.92 | 28-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.400717E+12 | 0.00 | 376.76 | 0.395317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1090402.33 | 31-JUL-16:00 | 954406.58 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 |
August | 0.537500E+12 | 0.00 | 394.19 | 0.519233E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1162224.11 | 29-AUG-14:30 | 1052653.14 | 29-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.192594E+12 | 0.00 | 242.52 | 0.188423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 911383.17 | 14-SEP-13:00 | 837871.42 | 12-SEP-15:20 | 0.00 | 0.00 | 0.00 |
October | 0.300181E+11 | 0.00 | 80.74 | 0.300181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 556802.52 | 04-OCT-15:00 | 556802.52 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.482927E+10 | 0.00 | 38.26 | 0.482927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 276327.01 | 04-NOV-14:00 | 276327.01 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 47343.63 | 0.00 | 17.13 | 47343.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3.47 | 26-DEC-06:03 | 3.47 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158400E+13 | 0.00 | 1813.32 | 0.155611E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 47343.63 | 0.00 | 16.88 | 47343.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3.47 | 3.47 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.537500E+12 | 0.00 | 394.19 | 0.519233E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1162224.11 | 1052653.14 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 129393.08 | 0.00 | 0.19 | 129393.08 | 0.00 | 0.00 | 0.00 | 0.00 | 406.48 | 02-JAN-04:30 | 406.48 | 02-JAN-04:30 | 0.00 | 0.00 | 0.00 |
February | 0.356705E+09 | 0.00 | 8.33 | 0.356705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23736.64 | 27-FEB-15:00 | 23736.64 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.532686E+09 | 0.00 | 24.83 | 0.532686E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21318.35 | 18-MAR-14:00 | 21318.35 | 18-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.641471E+10 | 0.00 | 75.79 | 0.641471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102670.64 | 27-APR-14:50 | 102670.64 | 27-APR-14:50 | 0.00 | 0.00 | 0.00 |
May | 0.124175E+11 | 0.00 | 168.22 | 0.124145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87025.61 | 04-MAY-15:00 | 87025.61 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.239406E+11 | 0.00 | 274.07 | 0.239392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104360.82 | 28-JUN-15:20 | 104360.82 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.436262E+11 | 0.00 | 362.60 | 0.430000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 129998.67 | 31-JUL-16:00 | 117775.67 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 |
August | 0.576274E+11 | 0.00 | 385.47 | 0.557319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135570.27 | 10-AUG-15:40 | 127804.20 | 10-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.188152E+11 | 0.00 | 231.08 | 0.185096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93218.60 | 14-SEP-13:10 | 89361.12 | 14-SEP-15:40 | 0.00 | 0.00 | 0.00 |
October | 0.249041E+10 | 0.00 | 58.14 | 0.249041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53994.68 | 04-OCT-15:00 | 53994.68 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.470360E+09 | 0.00 | 8.02 | 0.470360E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27013.43 | 04-NOV-14:00 | 27013.43 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 27294.25 | 0.00 | 0.18 | 27294.25 | 0.00 | 0.00 | 0.00 | 0.00 | 451.78 | 26-DEC-05:01 | 451.78 | 26-DEC-05:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166692E+12 | 0.00 | 1596.93 | 0.163860E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 27294.25 | 0.00 | 0.18 | 27294.25 | 0.00 | 0.00 | 0.00 | 0.00 | 406.48 | 406.48 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.576274E+11 | 0.00 | 385.47 | 0.557319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135570.27 | 127804.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2162289.83 | 0.00 | 0.07 | 2162289.83 | 0.00 | 0.00 | 0.00 | 0.00 | 8342.39 | 11-JAN-05:02 | 8342.39 | 11-JAN-05:02 | 0.00 | 0.00 | 0.00 |
February | 0.406424E+09 | 0.00 | 6.99 | 0.400533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39829.71 | 24-FEB-06:02 | 27654.19 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 76295979.78 | 0.00 | 4.68 | 71440749.85 | 0.00 | 0.00 | 0.00 | 0.00 | 20777.26 | 10-MAR-06:03 | 9849.53 | 09-MAR-06:03 | 0.00 | 0.00 | 0.00 |
April | 0.340122E+10 | 0.00 | 44.24 | 0.339951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52163.69 | 27-APR-15:00 | 52163.69 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.667136E+10 | 0.00 | 98.28 | 0.666578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50908.95 | 15-MAY-16:00 | 50908.95 | 15-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.138690E+11 | 0.00 | 195.32 | 0.138324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50617.80 | 28-JUN-15:00 | 50617.80 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.260690E+11 | 0.00 | 272.57 | 0.256697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75593.09 | 31-JUL-10:10 | 65345.28 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.361155E+11 | 0.00 | 312.08 | 0.354430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67804.81 | 29-AUG-13:10 | 62271.64 | 07-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.107769E+11 | 0.00 | 158.75 | 0.106744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51894.05 | 11-SEP-15:00 | 51894.05 | 11-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 0.149271E+10 | 0.00 | 38.52 | 0.148191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35321.91 | 04-OCT-15:00 | 35321.91 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.219622E+09 | 0.00 | 5.74 | 0.211959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27595.28 | 04-NOV-04:03 | 19418.73 | 27-NOV-04:02 | 0.00 | 0.00 | 0.00 |
December | 4719538.84 | 0.00 | 0.21 | 4719538.84 | 0.00 | 0.00 | 0.00 | 0.00 | 9637.71 | 16-DEC-06:03 | 9637.71 | 16-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.991049E+11 | 0.00 | 1137.45 | 0.978574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2162289.83 | 0.00 | 0.07 | 2162289.83 | 0.00 | 0.00 | 0.00 | 0.00 | 8342.39 | 8342.39 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.361155E+11 | 0.00 | 312.08 | 0.354430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75593.09 | 65345.28 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.376820E+10 | 0.908750E+09 | 744.00 | 0.376786E+10 | 339142.70 | 0.00 | 0.27 | 08-JAN-16:05 | 0.11 | 07-JAN-08:00 | 2062.53 | 08-JAN-16:10 | 2062.53 | 08-JAN-16:10 | 16.47 | 02-JAN-07:10 | 494.75 | 08-JAN-16:05 | 0.00 |
February | 0.857729E+10 | 0.191388E+10 | 672.00 | 0.856692E+10 | 10363410.75 | 0.00 | 0.53 | 12-FEB-16:33 | 0.37 | 18-FEB-08:00 | 4244.61 | 27-FEB-16:20 | 4233.83 | 27-FEB-16:20 | 128.18 | 24-FEB-11:10 | 956.70 | 12-FEB-16:33 | 0.00 |
March | 0.151416E+11 | 0.320468E+10 | 744.00 | 0.151337E+11 | 7950468.20 | 0.00 | 0.83 | 31-MAR-24:00 | 0.58 | 01-MAR-07:10 | 7526.76 | 31-MAR-24:00 | 7526.76 | 31-MAR-24:00 | 137.23 | 09-MAR-17:00 | 1504.98 | 31-MAR-24:00 | 0.00 |
April | 0.198419E+11 | 0.403631E+10 | 720.00 | 0.198288E+11 | 13154186.10 | 0.00 | 0.97 | 01-APR-17:32 | 0.30 | 30-APR-24:00 | 8445.52 | 23-APR-18:00 | 8445.52 | 23-APR-18:00 | 163.87 | 28-APR-11:10 | 2224.90 | 01-APR-17:02 | 0.00 |
May | 0.542685E+10 | 0.125087E+10 | 744.00 | 0.539072E+10 | 36138040.75 | 0.00 | 0.46 | 31-MAY-24:00 | 0.18 | 18-MAY-06:50 | 3992.85 | 31-MAY-24:00 | 3984.34 | 31-MAY-24:00 | 128.72 | 05-MAY-16:10 | 844.26 | 31-MAY-24:00 | 0.00 |
June | 0.103897E+11 | 0.227549E+10 | 720.00 | 0.103390E+11 | 50724946.05 | 0.00 | 0.65 | 30-JUN-24:00 | 0.42 | 07-JUN-06:20 | 5864.15 | 30-JUN-24:00 | 5862.59 | 30-JUN-24:00 | 194.49 | 12-JUN-15:00 | 1197.47 | 28-JUN-16:00 | 0.00 |
July | 0.160516E+11 | 0.347412E+10 | 744.00 | 0.159481E+11 | 0.103495E+09 | 0.00 | 0.85 | 31-JUL-23:03 | 0.62 | 01-JUL-07:00 | 7796.17 | 31-JUL-23:35 | 7772.30 | 31-JUL-23:43 | 235.49 | 11-JUL-10:00 | 1896.49 | 24-JUL-15:00 | 0.00 |
August | 0.210822E+11 | 0.455275E+10 | 744.00 | 0.209339E+11 | 0.148307E+09 | 0.00 | 1.00 | 10-AUG-18:10 | 0.29 | 31-AUG-24:00 | 8936.66 | 06-AUG-18:22 | 8936.66 | 06-AUG-18:22 | 266.54 | 30-AUG-08:00 | 2519.28 | 10-AUG-18:00 | 0.00 |
September | 0.543338E+10 | 0.123811E+10 | 720.00 | 0.534280E+10 | 90580276.40 | 0.00 | 0.45 | 30-SEP-24:00 | 0.19 | 28-SEP-07:00 | 3851.79 | 30-SEP-24:00 | 3850.62 | 30-SEP-24:00 | 173.08 | 14-SEP-11:00 | 817.60 | 30-SEP-24:00 | 0.00 |
October | 0.102542E+11 | 0.220963E+10 | 744.00 | 0.102318E+11 | 22428262.66 | 0.00 | 0.64 | 31-OCT-24:00 | 0.39 | 28-OCT-07:00 | 5558.05 | 31-OCT-24:00 | 5558.05 | 31-OCT-24:00 | 136.08 | 26-OCT-14:10 | 1154.86 | 31-OCT-24:00 | 0.00 |
November | 0.145456E+11 | 0.303130E+10 | 720.00 | 0.145221E+11 | 23462156.14 | 0.00 | 0.70 | 11-NOV-15:53 | 0.60 | 30-NOV-22:00 | 6197.44 | 12-NOV-16:00 | 6197.44 | 12-NOV-16:00 | 165.74 | 03-NOV-16:00 | 1365.41 | 04-NOV-15:50 | 0.00 |
December | 0.198850E+11 | 0.407138E+10 | 744.00 | 0.198825E+11 | 2496660.45 | 0.00 | 0.91 | 03-DEC-15:23 | 0.78 | 16-DEC-18:00 | 8019.94 | 10-DEC-15:40 | 8019.94 | 10-DEC-15:40 | 85.99 | 28-DEC-15:00 | 1651.50 | 03-DEC-15:23 | 0.00 |
Annual Sum or Average | 0.150397E+12 | 0.321673E+11 | 8760.00 | 0.149888E+12 | 0.509439E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.376820E+10 | 0.908750E+09 | 672.00 | 0.376786E+10 | 339142.70 | 0.00 | 0.27 | 0.11 | 2062.53 | 2062.53 | 16.47 | 494.75 | 0.00 | ||||||
Maximum of Months | 0.210822E+11 | 0.455275E+10 | 744.00 | 0.209339E+11 | 0.148307E+09 | 0.00 | 1.00 | 0.78 | 8936.66 | 8936.66 | 266.54 | 2519.28 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.112514E+11 | 0.302374E+10 | 658.50 | 0.112511E+11 | 250925.19 | 0.00 | 0.18 | 05-JAN-16:10 | 0.00 | 01-JAN-00:05 | 13365.25 | 05-JAN-16:10 | 13365.25 | 05-JAN-16:10 | 27.13 | 02-JAN-15:40 | 3183.05 | 05-JAN-16:10 | 0.00 |
February | 0.628885E+11 | 0.143523E+11 | 672.00 | 0.627876E+11 | 0.100822E+09 | 0.00 | 0.47 | 27-FEB-16:20 | 0.24 | 21-FEB-07:10 | 38396.02 | 27-FEB-16:30 | 38250.60 | 27-FEB-16:20 | 1223.02 | 24-FEB-11:10 | 8604.02 | 27-FEB-16:20 | 0.00 |
March | 0.129931E+12 | 0.278461E+11 | 744.00 | 0.129851E+12 | 80122169.39 | 0.00 | 0.77 | 31-MAR-24:00 | 0.51 | 06-MAR-07:10 | 66443.42 | 31-MAR-24:00 | 66443.42 | 31-MAR-24:00 | 1357.75 | 09-MAR-17:00 | 13422.00 | 31-MAR-24:00 | 0.00 |
April | 0.180591E+12 | 0.369937E+11 | 720.00 | 0.180457E+12 | 0.133697E+09 | 0.00 | 0.95 | 01-APR-17:32 | 0.24 | 30-APR-24:00 | 79899.97 | 26-APR-17:50 | 79899.97 | 26-APR-17:50 | 1635.69 | 28-APR-11:10 | 20794.11 | 27-APR-16:00 | 0.00 |
May | 0.456476E+11 | 0.106384E+11 | 744.00 | 0.452944E+11 | 0.353220E+09 | 0.00 | 0.45 | 31-MAY-24:00 | 0.12 | 18-MAY-07:00 | 37126.61 | 31-MAY-24:00 | 37032.01 | 31-MAY-24:00 | 1265.82 | 05-MAY-16:10 | 7871.21 | 31-MAY-24:00 | 0.00 |
June | 0.947754E+11 | 0.208653E+11 | 720.00 | 0.942713E+11 | 0.504147E+09 | 0.00 | 0.64 | 30-JUN-24:00 | 0.38 | 14-JUN-07:00 | 54949.76 | 30-JUN-24:00 | 54932.27 | 30-JUN-24:00 | 1932.08 | 12-JUN-15:00 | 11376.82 | 28-JUN-16:00 | 0.00 |
July | 0.150867E+12 | 0.327321E+11 | 744.00 | 0.149836E+12 | 0.103108E+10 | 0.00 | 0.85 | 31-JUL-23:13 | 0.61 | 18-JUL-06:10 | 75245.53 | 31-JUL-23:53 | 75024.15 | 31-JUL-23:57 | 2350.83 | 11-JUL-10:00 | 18034.18 | 24-JUL-15:00 | 0.00 |
August | 0.199467E+12 | 0.431566E+11 | 744.00 | 0.197986E+12 | 0.148077E+10 | 0.00 | 1.00 | 10-AUG-18:10 | 0.25 | 31-AUG-24:00 | 83254.63 | 06-AUG-18:23 | 83254.63 | 06-AUG-18:23 | 2662.30 | 30-AUG-08:00 | 24111.78 | 10-AUG-18:00 | 0.00 |
September | 0.462750E+11 | 0.106518E+11 | 720.00 | 0.453933E+11 | 0.881710E+09 | 0.00 | 0.42 | 30-SEP-24:00 | 0.13 | 28-SEP-07:00 | 34260.78 | 30-SEP-24:00 | 34243.54 | 30-SEP-24:00 | 1703.47 | 14-SEP-13:30 | 7322.43 | 30-SEP-24:00 | 0.00 |
October | 0.856084E+11 | 0.186804E+11 | 744.00 | 0.853863E+11 | 0.222113E+09 | 0.00 | 0.57 | 31-OCT-24:00 | 0.32 | 28-OCT-07:00 | 46697.88 | 31-OCT-24:00 | 46697.88 | 31-OCT-24:00 | 1322.44 | 26-OCT-14:10 | 10236.41 | 04-OCT-16:40 | 0.00 |
November | 0.119756E+12 | 0.253713E+11 | 720.00 | 0.119522E+12 | 0.234026E+09 | 0.00 | 0.66 | 04-NOV-16:00 | 0.49 | 24-NOV-07:10 | 55584.75 | 04-NOV-16:00 | 54594.41 | 04-NOV-16:05 | 1642.59 | 03-NOV-16:00 | 12388.10 | 04-NOV-15:50 | 0.00 |
December | 0.164520E+12 | 0.343341E+11 | 744.00 | 0.164495E+12 | 25258584.93 | 0.00 | 0.84 | 03-DEC-15:33 | 0.64 | 26-DEC-07:10 | 70933.04 | 05-DEC-15:50 | 70933.04 | 05-DEC-15:50 | 846.47 | 28-DEC-15:00 | 14440.53 | 03-DEC-15:33 | 0.00 |
Annual Sum or Average | 0.129158E+13 | 0.278646E+12 | 8674.50 | 0.128653E+13 | 0.504722E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.112514E+11 | 0.302374E+10 | 658.50 | 0.112511E+11 | 250925.19 | 0.00 | 0.18 | 0.00 | 13365.25 | 13365.25 | 27.13 | 3183.05 | 0.00 | ||||||
Maximum of Months | 0.199467E+12 | 0.431566E+11 | 744.00 | 0.197986E+12 | 0.148077E+10 | 0.00 | 1.00 | 0.64 | 83254.63 | 83254.63 | 2662.30 | 24111.78 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.266580E+09 | 77448966.13 | 253.86 | 0.266580E+09 | -0.0 | 0.00 | 0.16 | 05-JAN-16:10 | 0.00 | 01-JAN-00:05 | 1139.11 | 05-JAN-16:10 | 1139.11 | 05-JAN-16:10 | 0.00 | 26-JAN-10:30 | 275.59 | 05-JAN-16:10 | 0.00 |
February | 0.465390E+10 | 0.108264E+10 | 671.67 | 0.464403E+10 | 9868190.84 | 0.00 | 0.46 | 27-FEB-16:30 | 0.00 | 19-FEB-10:25 | 3750.00 | 27-FEB-16:30 | 3732.96 | 27-FEB-16:20 | 119.81 | 24-FEB-11:20 | 842.97 | 27-FEB-16:20 | 0.00 |
March | 0.114827E+11 | 0.249557E+10 | 744.00 | 0.114748E+11 | 7885884.96 | 0.00 | 0.70 | 31-MAR-23:30 | 0.36 | 06-MAR-04:15 | 6031.71 | 31-MAR-23:30 | 6031.71 | 31-MAR-23:30 | 134.76 | 09-MAR-17:00 | 1254.83 | 18-MAR-17:03 | 0.00 |
April | 0.171545E+11 | 0.354517E+10 | 720.00 | 0.171412E+11 | 13245628.09 | 0.00 | 0.93 | 26-APR-17:50 | 0.19 | 30-APR-24:00 | 8062.40 | 26-APR-17:50 | 8062.40 | 26-APR-17:50 | 163.10 | 28-APR-11:10 | 2102.87 | 27-APR-16:00 | 0.00 |
May | 0.400302E+10 | 0.944522E+09 | 743.83 | 0.396819E+10 | 34825313.51 | 0.00 | 0.44 | 31-MAY-23:30 | 0.00 | 29-MAY-04:45 | 3647.00 | 31-MAY-23:30 | 3631.71 | 31-MAY-23:40 | 127.66 | 05-MAY-16:10 | 775.39 | 31-MAY-23:30 | 0.00 |
June | 0.924144E+10 | 0.204411E+10 | 720.00 | 0.919122E+10 | 50225241.94 | 0.00 | 0.62 | 30-JUN-23:50 | 0.32 | 14-JUN-07:00 | 5405.45 | 30-JUN-23:50 | 5403.08 | 30-JUN-23:50 | 193.11 | 12-JUN-15:00 | 1164.25 | 28-JUN-16:00 | 0.00 |
July | 0.149798E+11 | 0.326184E+10 | 744.00 | 0.148768E+11 | 0.102985E+09 | 0.00 | 0.84 | 31-JUL-23:13 | 0.57 | 18-JUL-06:10 | 7525.75 | 31-JUL-23:53 | 7503.47 | 31-JUL-23:57 | 235.16 | 11-JUL-10:00 | 1834.68 | 24-JUL-15:00 | 0.00 |
August | 0.197904E+11 | 0.429990E+10 | 744.00 | 0.196426E+11 | 0.147849E+09 | 0.00 | 1.00 | 10-AUG-18:10 | 0.23 | 31-AUG-24:00 | 8462.48 | 06-AUG-18:12 | 8462.48 | 06-AUG-18:12 | 265.26 | 30-AUG-08:00 | 2446.50 | 10-AUG-18:00 | 0.00 |
September | 0.403765E+10 | 0.941997E+09 | 720.00 | 0.395153E+10 | 86117352.61 | 0.00 | 0.37 | 30-SEP-23:20 | 0.05 | 28-SEP-07:00 | 3003.47 | 30-SEP-23:20 | 2999.17 | 30-SEP-23:30 | 173.99 | 14-SEP-13:20 | 689.35 | 14-SEP-17:00 | 0.00 |
October | 0.721514E+10 | 0.159867E+10 | 744.00 | 0.719361E+10 | 21526707.51 | 0.00 | 0.54 | 04-OCT-16:50 | 0.20 | 16-OCT-06:10 | 4309.68 | 04-OCT-16:50 | 4309.68 | 04-OCT-16:50 | 128.61 | 26-OCT-14:10 | 1028.54 | 04-OCT-16:40 | 0.00 |
November | 0.102210E+11 | 0.220199E+10 | 720.00 | 0.101979E+11 | 23045426.16 | 0.00 | 0.63 | 04-NOV-16:00 | 0.34 | 13-NOV-05:00 | 5408.49 | 04-NOV-16:00 | 5309.13 | 04-NOV-16:00 | 163.20 | 03-NOV-16:00 | 1212.35 | 04-NOV-15:50 | 0.00 |
December | 0.145316E+11 | 0.308236E+10 | 744.00 | 0.145291E+11 | 2486695.09 | 0.00 | 0.79 | 05-DEC-15:50 | 0.46 | 26-DEC-04:03 | 6795.13 | 05-DEC-15:50 | 6795.13 | 05-DEC-15:50 | 83.99 | 28-DEC-15:10 | 1394.20 | 05-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.117578E+12 | 0.255762E+11 | 8269.36 | 0.117078E+12 | 0.500061E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.266580E+09 | 77448966.13 | 253.86 | 0.266580E+09 | -0.0 | 0.00 | 0.16 | 0.00 | 1139.11 | 1139.11 | 0.00 | 275.59 | 0.00 | ||||||
Maximum of Months | 0.197904E+11 | 0.429990E+10 | 744.00 | 0.196426E+11 | 0.147849E+09 | 0.00 | 1.00 | 0.57 | 8462.48 | 8462.48 | 265.26 | 2446.50 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.23 | 0.00 | 64.23 | 0.76 | 469.09 | 0.00 | 0.00 | 0.00 |
February | 99.94 | 0.00 | 99.94 | 12.49 | 414.69 | 0.00 | 0.00 | 0.00 |
March | 147.25 | 0.00 | 147.25 | 50.28 | 338.26 | 0.00 | 0.00 | 0.00 |
April | 208.38 | 0.74 | 207.64 | 124.48 | 264.57 | 0.00 | 0.00 | 0.00 |
May | 268.13 | 7.97 | 260.16 | 213.19 | 203.12 | 0.00 | 0.00 | 0.00 |
June | 281.93 | 18.62 | 263.31 | 250.24 | 155.88 | 0.00 | 0.00 | 0.00 |
July | 267.96 | 21.01 | 246.95 | 270.33 | 138.34 | 0.00 | 0.00 | 0.00 |
August | 216.92 | 5.86 | 211.05 | 221.60 | 136.13 | 0.00 | 0.00 | 0.00 |
September | 168.49 | 0.05 | 168.44 | 125.66 | 207.32 | 0.00 | 0.00 | 0.00 |
October | 115.45 | 0.00 | 115.45 | 43.54 | 295.81 | 0.00 | 0.00 | 0.00 |
November | 72.72 | 0.00 | 72.72 | 5.69 | 391.07 | 0.00 | 0.00 | 0.00 |
December | 54.58 | 0.00 | 54.58 | 0.15 | 485.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.15 | 4.55 | 159.59 | 110.48 | 291.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.58 | 0.00 | 54.58 | 0.15 | 136.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 281.93 | 21.01 | 263.31 | 270.33 | 485.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.23 | 0.00 | 64.23 | 0.76 | 469.10 | 0.00 | 0.00 | 0.00 |
February | 99.94 | 0.00 | 99.94 | 12.49 | 414.69 | 0.00 | 0.00 | 0.00 |
March | 147.25 | 0.00 | 147.25 | 50.28 | 338.26 | 0.00 | 0.00 | 0.00 |
April | 208.37 | 0.74 | 207.64 | 124.48 | 264.57 | 0.00 | 0.00 | 0.00 |
May | 268.13 | 7.97 | 260.16 | 213.19 | 203.12 | 0.00 | 0.00 | 0.00 |
June | 281.93 | 18.62 | 263.31 | 250.23 | 155.88 | 0.00 | 0.00 | 0.00 |
July | 267.96 | 21.01 | 246.95 | 270.32 | 138.34 | 0.00 | 0.00 | 0.00 |
August | 216.91 | 5.86 | 211.05 | 221.60 | 136.13 | 0.00 | 0.00 | 0.00 |
September | 168.49 | 0.05 | 168.44 | 125.66 | 207.32 | 0.00 | 0.00 | 0.00 |
October | 115.44 | 0.00 | 115.44 | 43.54 | 295.81 | 0.00 | 0.00 | 0.00 |
November | 72.72 | 0.00 | 72.72 | 5.69 | 391.07 | 0.00 | 0.00 | 0.00 |
December | 54.58 | 0.00 | 54.58 | 0.15 | 485.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.15 | 4.55 | 159.59 | 110.48 | 291.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.58 | 0.00 | 54.58 | 0.15 | 136.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 281.93 | 21.01 | 263.31 | 270.32 | 485.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.23 | 0.00 | 64.23 | 0.76 | 469.09 | 0.00 | 0.00 | 0.00 |
February | 99.94 | 0.00 | 99.94 | 12.49 | 414.69 | 0.00 | 0.00 | 0.00 |
March | 147.25 | 0.00 | 147.25 | 50.28 | 338.26 | 0.00 | 0.00 | 0.00 |
April | 208.38 | 0.74 | 207.64 | 124.48 | 264.57 | 0.00 | 0.00 | 0.00 |
May | 268.13 | 7.97 | 260.16 | 213.19 | 203.12 | 0.00 | 0.00 | 0.00 |
June | 281.93 | 18.62 | 263.31 | 250.24 | 155.88 | 0.00 | 0.00 | 0.00 |
July | 267.96 | 21.01 | 246.95 | 270.32 | 138.34 | 0.00 | 0.00 | 0.00 |
August | 216.91 | 5.86 | 211.05 | 221.60 | 136.13 | 0.00 | 0.00 | 0.00 |
September | 168.49 | 0.05 | 168.44 | 125.66 | 207.32 | 0.00 | 0.00 | 0.00 |
October | 115.44 | 0.00 | 115.44 | 43.54 | 295.81 | 0.00 | 0.00 | 0.00 |
November | 72.72 | 0.00 | 72.72 | 5.69 | 391.07 | 0.00 | 0.00 | 0.00 |
December | 54.58 | 0.00 | 54.58 | 0.15 | 485.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.15 | 4.55 | 159.59 | 110.48 | 291.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.58 | 0.00 | 54.58 | 0.15 | 136.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 281.93 | 21.01 | 263.31 | 270.32 | 485.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.23 | 0.00 | 64.23 | 0.76 | 469.10 | 0.00 | 0.00 | 0.00 |
February | 99.94 | 0.00 | 99.94 | 12.49 | 414.69 | 0.00 | 0.00 | 0.00 |
March | 147.25 | 0.00 | 147.25 | 50.28 | 338.26 | 0.00 | 0.00 | 0.00 |
April | 208.37 | 0.74 | 207.64 | 124.48 | 264.57 | 0.00 | 0.00 | 0.00 |
May | 268.13 | 7.97 | 260.16 | 213.19 | 203.12 | 0.00 | 0.00 | 0.00 |
June | 281.93 | 18.62 | 263.31 | 250.23 | 155.88 | 0.00 | 0.00 | 0.00 |
July | 267.96 | 21.01 | 246.95 | 270.32 | 138.34 | 0.00 | 0.00 | 0.00 |
August | 216.91 | 5.86 | 211.05 | 221.60 | 136.13 | 0.00 | 0.00 | 0.00 |
September | 168.49 | 0.05 | 168.44 | 125.66 | 207.32 | 0.00 | 0.00 | 0.00 |
October | 115.44 | 0.00 | 115.44 | 43.54 | 295.81 | 0.00 | 0.00 | 0.00 |
November | 72.72 | 0.00 | 72.72 | 5.69 | 391.07 | 0.00 | 0.00 | 0.00 |
December | 54.58 | 0.00 | 54.58 | 0.15 | 485.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.15 | 4.55 | 159.59 | 110.48 | 291.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.58 | 0.00 | 54.58 | 0.15 | 136.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 281.93 | 21.01 | 263.31 | 270.32 | 485.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.23 | 0.00 | 64.23 | 0.76 | 469.08 | 0.00 | 0.00 | 0.00 |
February | 99.94 | 0.00 | 99.94 | 12.49 | 414.67 | 0.00 | 0.00 | 0.00 |
March | 147.24 | 0.00 | 147.24 | 50.27 | 338.24 | 0.00 | 0.00 | 0.00 |
April | 208.37 | 0.74 | 207.63 | 124.47 | 264.56 | 0.00 | 0.00 | 0.00 |
May | 268.12 | 7.97 | 260.15 | 213.18 | 203.11 | 0.00 | 0.00 | 0.00 |
June | 281.92 | 18.62 | 263.30 | 250.23 | 155.87 | 0.00 | 0.00 | 0.00 |
July | 267.95 | 21.01 | 246.94 | 270.31 | 138.34 | 0.00 | 0.00 | 0.00 |
August | 216.90 | 5.86 | 211.04 | 221.59 | 136.13 | 0.00 | 0.00 | 0.00 |
September | 168.48 | 0.05 | 168.43 | 125.65 | 207.31 | 0.00 | 0.00 | 0.00 |
October | 115.44 | 0.00 | 115.44 | 43.54 | 295.80 | 0.00 | 0.00 | 0.00 |
November | 72.72 | 0.00 | 72.72 | 5.69 | 391.06 | 0.00 | 0.00 | 0.00 |
December | 54.58 | 0.00 | 54.58 | 0.15 | 485.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.14 | 4.55 | 159.59 | 110.48 | 290.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.58 | 0.00 | 54.58 | 0.15 | 136.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 281.92 | 21.01 | 263.30 | 270.31 | 485.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.68 | 29.07 | 85.60 | 35.61 | 484.35 | 0.00 | 0.00 | 0.00 |
February | 210.42 | 74.68 | 135.74 | 125.43 | 419.40 | 0.00 | 0.00 | 0.00 |
March | 314.18 | 113.73 | 200.44 | 251.38 | 345.52 | 0.00 | 0.00 | 0.00 |
April | 487.03 | 202.37 | 284.66 | 487.30 | 270.56 | 0.00 | 0.00 | 0.00 |
May | 518.24 | 180.18 | 338.06 | 549.57 | 223.53 | 0.00 | 0.00 | 0.00 |
June | 620.65 | 270.05 | 350.60 | 712.01 | 173.06 | 0.00 | 0.00 | 0.00 |
July | 577.97 | 259.43 | 318.54 | 694.38 | 148.05 | 0.00 | 0.00 | 0.00 |
August | 568.07 | 284.18 | 283.89 | 705.99 | 143.28 | 0.00 | 0.00 | 0.00 |
September | 420.00 | 193.71 | 226.29 | 460.52 | 217.81 | 0.00 | 0.00 | 0.00 |
October | 273.76 | 116.32 | 157.44 | 241.78 | 305.36 | 0.00 | 0.00 | 0.00 |
November | 134.18 | 37.88 | 96.30 | 63.87 | 398.65 | 0.00 | 0.00 | 0.00 |
December | 110.06 | 35.43 | 74.63 | 45.79 | 491.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 363.10 | 150.08 | 213.02 | 365.71 | 301.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.06 | 29.07 | 74.63 | 35.61 | 143.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.65 | 284.18 | 350.60 | 712.01 | 491.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.68 | 29.07 | 85.60 | 35.61 | 484.35 | 0.00 | 0.00 | 0.00 |
February | 210.42 | 74.68 | 135.74 | 125.43 | 419.40 | 0.00 | 0.00 | 0.00 |
March | 314.18 | 113.73 | 200.44 | 251.38 | 345.52 | 0.00 | 0.00 | 0.00 |
April | 487.03 | 202.37 | 284.66 | 487.30 | 270.56 | 0.00 | 0.00 | 0.00 |
May | 518.24 | 180.18 | 338.06 | 549.57 | 223.53 | 0.00 | 0.00 | 0.00 |
June | 620.65 | 270.05 | 350.60 | 712.01 | 173.06 | 0.00 | 0.00 | 0.00 |
July | 577.97 | 259.43 | 318.54 | 694.38 | 148.05 | 0.00 | 0.00 | 0.00 |
August | 568.07 | 284.18 | 283.89 | 705.99 | 143.28 | 0.00 | 0.00 | 0.00 |
September | 420.00 | 193.71 | 226.29 | 460.52 | 217.81 | 0.00 | 0.00 | 0.00 |
October | 273.76 | 116.32 | 157.44 | 241.78 | 305.36 | 0.00 | 0.00 | 0.00 |
November | 134.18 | 37.88 | 96.30 | 63.87 | 398.65 | 0.00 | 0.00 | 0.00 |
December | 110.06 | 35.43 | 74.63 | 45.79 | 491.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 363.10 | 150.08 | 213.02 | 365.71 | 301.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.06 | 29.07 | 74.63 | 35.61 | 143.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.65 | 284.18 | 350.60 | 712.01 | 491.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.68 | 29.07 | 85.60 | 35.61 | 484.34 | 0.00 | 0.00 | 0.00 |
February | 210.42 | 74.68 | 135.74 | 125.43 | 419.39 | 0.00 | 0.00 | 0.00 |
March | 314.17 | 113.73 | 200.44 | 251.38 | 345.52 | 0.00 | 0.00 | 0.00 |
April | 487.02 | 202.36 | 284.66 | 487.29 | 270.56 | 0.00 | 0.00 | 0.00 |
May | 518.23 | 180.18 | 338.05 | 549.56 | 223.53 | 0.00 | 0.00 | 0.00 |
June | 620.64 | 270.05 | 350.60 | 712.00 | 173.06 | 0.00 | 0.00 | 0.00 |
July | 577.96 | 259.42 | 318.54 | 694.37 | 148.05 | 0.00 | 0.00 | 0.00 |
August | 568.06 | 284.17 | 283.88 | 705.98 | 143.28 | 0.00 | 0.00 | 0.00 |
September | 419.99 | 193.70 | 226.29 | 460.51 | 217.81 | 0.00 | 0.00 | 0.00 |
October | 273.75 | 116.32 | 157.43 | 241.78 | 305.35 | 0.00 | 0.00 | 0.00 |
November | 134.18 | 37.88 | 96.30 | 63.87 | 398.64 | 0.00 | 0.00 | 0.00 |
December | 110.06 | 35.43 | 74.63 | 45.79 | 491.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 363.10 | 150.08 | 213.02 | 365.70 | 301.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.06 | 29.07 | 74.63 | 35.61 | 143.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.64 | 284.17 | 350.60 | 712.00 | 491.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 283.79 | 168.51 | 115.27 | 245.47 | 396.90 | 0.00 | 0.00 | 0.00 |
February | 436.42 | 270.15 | 166.27 | 434.89 | 359.00 | 0.00 | 0.00 | 0.00 |
March | 469.46 | 250.36 | 219.10 | 493.47 | 315.65 | 0.00 | 0.00 | 0.00 |
April | 495.66 | 215.21 | 280.45 | 553.80 | 264.85 | 0.00 | 0.00 | 0.00 |
May | 453.22 | 135.02 | 318.20 | 514.74 | 215.00 | 0.00 | 0.00 | 0.00 |
June | 414.65 | 111.33 | 303.32 | 481.43 | 170.34 | 0.00 | 0.00 | 0.00 |
July | 452.20 | 165.62 | 286.58 | 580.35 | 152.26 | 0.00 | 0.00 | 0.00 |
August | 485.83 | 226.55 | 259.28 | 644.27 | 147.47 | 0.00 | 0.00 | 0.00 |
September | 538.28 | 297.25 | 241.02 | 668.82 | 207.37 | 0.00 | 0.00 | 0.00 |
October | 487.59 | 301.05 | 186.54 | 550.38 | 276.60 | 0.00 | 0.00 | 0.00 |
November | 288.28 | 165.21 | 123.07 | 267.66 | 340.14 | 0.00 | 0.00 | 0.00 |
December | 301.62 | 195.19 | 106.43 | 288.21 | 415.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 425.40 | 208.07 | 217.33 | 477.13 | 271.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 283.79 | 111.33 | 106.43 | 245.47 | 147.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 538.28 | 301.05 | 318.20 | 668.82 | 415.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 283.78 | 168.51 | 115.27 | 245.46 | 396.90 | 0.00 | 0.00 | 0.00 |
February | 436.42 | 270.15 | 166.27 | 434.89 | 359.00 | 0.00 | 0.00 | 0.00 |
March | 469.46 | 250.36 | 219.10 | 493.47 | 315.65 | 0.00 | 0.00 | 0.00 |
April | 495.66 | 215.21 | 280.45 | 553.80 | 264.85 | 0.00 | 0.00 | 0.00 |
May | 453.22 | 135.02 | 318.20 | 514.74 | 215.00 | 0.00 | 0.00 | 0.00 |
June | 414.65 | 111.33 | 303.32 | 481.43 | 170.34 | 0.00 | 0.00 | 0.00 |
July | 452.19 | 165.62 | 286.58 | 580.35 | 152.26 | 0.00 | 0.00 | 0.00 |
August | 485.82 | 226.55 | 259.28 | 644.27 | 147.47 | 0.00 | 0.00 | 0.00 |
September | 538.27 | 297.25 | 241.02 | 668.81 | 207.37 | 0.00 | 0.00 | 0.00 |
October | 487.58 | 301.05 | 186.54 | 550.38 | 276.60 | 0.00 | 0.00 | 0.00 |
November | 288.28 | 165.21 | 123.07 | 267.65 | 340.14 | 0.00 | 0.00 | 0.00 |
December | 301.62 | 195.19 | 106.43 | 288.21 | 415.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 425.40 | 208.07 | 217.33 | 477.12 | 271.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 283.78 | 111.33 | 106.43 | 245.46 | 147.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 538.27 | 301.05 | 318.20 | 668.81 | 415.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 283.79 | 168.51 | 115.27 | 245.47 | 396.90 | 0.00 | 0.00 | 0.00 |
February | 436.42 | 270.15 | 166.27 | 434.89 | 359.00 | 0.00 | 0.00 | 0.00 |
March | 469.46 | 250.36 | 219.10 | 493.47 | 315.65 | 0.00 | 0.00 | 0.00 |
April | 495.66 | 215.21 | 280.45 | 553.80 | 264.85 | 0.00 | 0.00 | 0.00 |
May | 453.22 | 135.02 | 318.20 | 514.74 | 215.00 | 0.00 | 0.00 | 0.00 |
June | 414.65 | 111.33 | 303.32 | 481.43 | 170.34 | 0.00 | 0.00 | 0.00 |
July | 452.20 | 165.62 | 286.58 | 580.35 | 152.26 | 0.00 | 0.00 | 0.00 |
August | 485.83 | 226.55 | 259.28 | 644.27 | 147.47 | 0.00 | 0.00 | 0.00 |
September | 538.28 | 297.25 | 241.02 | 668.82 | 207.37 | 0.00 | 0.00 | 0.00 |
October | 487.59 | 301.05 | 186.54 | 550.38 | 276.60 | 0.00 | 0.00 | 0.00 |
November | 288.28 | 165.21 | 123.07 | 267.66 | 340.14 | 0.00 | 0.00 | 0.00 |
December | 301.62 | 195.19 | 106.43 | 288.21 | 415.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 425.40 | 208.07 | 217.33 | 477.13 | 271.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 283.79 | 111.33 | 106.43 | 245.47 | 147.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 538.28 | 301.05 | 318.20 | 668.82 | 415.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 283.78 | 168.51 | 115.27 | 245.46 | 396.90 | 0.00 | 0.00 | 0.00 |
February | 436.42 | 270.15 | 166.27 | 434.89 | 359.00 | 0.00 | 0.00 | 0.00 |
March | 469.46 | 250.36 | 219.10 | 493.47 | 315.65 | 0.00 | 0.00 | 0.00 |
April | 495.66 | 215.21 | 280.45 | 553.80 | 264.85 | 0.00 | 0.00 | 0.00 |
May | 453.22 | 135.02 | 318.20 | 514.74 | 215.00 | 0.00 | 0.00 | 0.00 |
June | 414.65 | 111.33 | 303.32 | 481.43 | 170.34 | 0.00 | 0.00 | 0.00 |
July | 452.19 | 165.62 | 286.58 | 580.35 | 152.26 | 0.00 | 0.00 | 0.00 |
August | 485.82 | 226.55 | 259.28 | 644.27 | 147.47 | 0.00 | 0.00 | 0.00 |
September | 538.27 | 297.25 | 241.02 | 668.81 | 207.37 | 0.00 | 0.00 | 0.00 |
October | 487.58 | 301.05 | 186.54 | 550.38 | 276.60 | 0.00 | 0.00 | 0.00 |
November | 288.28 | 165.21 | 123.07 | 267.65 | 340.14 | 0.00 | 0.00 | 0.00 |
December | 301.62 | 195.19 | 106.43 | 288.21 | 415.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 425.40 | 208.07 | 217.33 | 477.12 | 271.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 283.78 | 111.33 | 106.43 | 245.46 | 147.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 538.27 | 301.05 | 318.20 | 668.81 | 415.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 283.77 | 168.51 | 115.27 | 245.45 | 396.89 | 0.00 | 0.00 | 0.00 |
February | 436.40 | 270.14 | 166.26 | 434.87 | 358.98 | 0.00 | 0.00 | 0.00 |
March | 469.44 | 250.35 | 219.09 | 493.45 | 315.64 | 0.00 | 0.00 | 0.00 |
April | 495.64 | 215.20 | 280.44 | 553.78 | 264.84 | 0.00 | 0.00 | 0.00 |
May | 453.20 | 135.01 | 318.19 | 514.72 | 214.99 | 0.00 | 0.00 | 0.00 |
June | 414.64 | 111.32 | 303.31 | 481.41 | 170.34 | 0.00 | 0.00 | 0.00 |
July | 452.18 | 165.61 | 286.57 | 580.33 | 152.26 | 0.00 | 0.00 | 0.00 |
August | 485.81 | 226.54 | 259.27 | 644.24 | 147.46 | 0.00 | 0.00 | 0.00 |
September | 538.25 | 297.24 | 241.01 | 668.79 | 207.36 | 0.00 | 0.00 | 0.00 |
October | 487.57 | 301.03 | 186.53 | 550.36 | 276.59 | 0.00 | 0.00 | 0.00 |
November | 288.26 | 165.20 | 123.07 | 267.64 | 340.12 | 0.00 | 0.00 | 0.00 |
December | 301.61 | 195.18 | 106.43 | 288.20 | 415.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 425.38 | 208.06 | 217.32 | 477.11 | 271.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 283.77 | 111.32 | 106.43 | 245.45 | 147.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 538.25 | 301.03 | 318.19 | 668.79 | 415.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.96 | 35.67 | 85.29 | 44.67 | 520.81 | 0.00 | 0.00 | 0.00 |
February | 216.87 | 81.50 | 135.36 | 135.23 | 473.09 | 0.00 | 0.00 | 0.00 |
March | 303.89 | 102.57 | 201.32 | 233.47 | 404.39 | 0.00 | 0.00 | 0.00 |
April | 462.33 | 176.77 | 285.56 | 441.84 | 332.16 | 0.00 | 0.00 | 0.00 |
May | 594.91 | 241.68 | 353.23 | 647.37 | 253.23 | 0.00 | 0.00 | 0.00 |
June | 572.14 | 222.14 | 350.00 | 634.88 | 205.94 | 0.00 | 0.00 | 0.00 |
July | 706.80 | 371.53 | 335.27 | 863.35 | 190.67 | 0.00 | 0.00 | 0.00 |
August | 584.70 | 298.56 | 286.13 | 720.32 | 190.58 | 0.00 | 0.00 | 0.00 |
September | 476.15 | 228.47 | 247.68 | 541.85 | 250.27 | 0.00 | 0.00 | 0.00 |
October | 271.07 | 110.45 | 160.62 | 234.87 | 353.47 | 0.00 | 0.00 | 0.00 |
November | 134.99 | 38.07 | 96.92 | 61.62 | 462.86 | 0.00 | 0.00 | 0.00 |
December | 113.49 | 38.89 | 74.60 | 52.23 | 581.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 380.85 | 162.81 | 218.04 | 385.96 | 350.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 113.49 | 35.67 | 74.60 | 44.67 | 190.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 706.80 | 371.53 | 353.23 | 863.35 | 581.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.96 | 35.67 | 85.29 | 44.67 | 520.81 | 0.00 | 0.00 | 0.00 |
February | 216.87 | 81.50 | 135.36 | 135.23 | 473.09 | 0.00 | 0.00 | 0.00 |
March | 303.89 | 102.57 | 201.32 | 233.47 | 404.39 | 0.00 | 0.00 | 0.00 |
April | 462.33 | 176.77 | 285.56 | 441.84 | 332.16 | 0.00 | 0.00 | 0.00 |
May | 594.91 | 241.68 | 353.23 | 647.37 | 253.23 | 0.00 | 0.00 | 0.00 |
June | 572.14 | 222.14 | 350.00 | 634.88 | 205.94 | 0.00 | 0.00 | 0.00 |
July | 706.80 | 371.53 | 335.27 | 863.35 | 190.67 | 0.00 | 0.00 | 0.00 |
August | 584.70 | 298.56 | 286.13 | 720.32 | 190.58 | 0.00 | 0.00 | 0.00 |
September | 476.15 | 228.47 | 247.68 | 541.85 | 250.27 | 0.00 | 0.00 | 0.00 |
October | 271.07 | 110.45 | 160.62 | 234.87 | 353.47 | 0.00 | 0.00 | 0.00 |
November | 134.99 | 38.07 | 96.92 | 61.62 | 462.86 | 0.00 | 0.00 | 0.00 |
December | 113.49 | 38.89 | 74.60 | 52.23 | 581.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 380.85 | 162.81 | 218.04 | 385.96 | 350.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 113.49 | 35.67 | 74.60 | 44.67 | 190.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 706.80 | 371.53 | 353.23 | 863.35 | 581.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.96 | 35.67 | 85.29 | 44.67 | 520.80 | 0.00 | 0.00 | 0.00 |
February | 216.86 | 81.50 | 135.36 | 135.23 | 473.08 | 0.00 | 0.00 | 0.00 |
March | 303.88 | 102.57 | 201.31 | 233.47 | 404.39 | 0.00 | 0.00 | 0.00 |
April | 462.32 | 176.76 | 285.56 | 441.83 | 332.15 | 0.00 | 0.00 | 0.00 |
May | 594.90 | 241.68 | 353.23 | 647.36 | 253.23 | 0.00 | 0.00 | 0.00 |
June | 572.13 | 222.14 | 349.99 | 634.87 | 205.93 | 0.00 | 0.00 | 0.00 |
July | 706.79 | 371.53 | 335.27 | 863.34 | 190.67 | 0.00 | 0.00 | 0.00 |
August | 584.69 | 298.56 | 286.13 | 720.31 | 190.58 | 0.00 | 0.00 | 0.00 |
September | 476.14 | 228.46 | 247.68 | 541.84 | 250.27 | 0.00 | 0.00 | 0.00 |
October | 271.07 | 110.45 | 160.62 | 234.87 | 353.46 | 0.00 | 0.00 | 0.00 |
November | 134.99 | 38.07 | 96.92 | 61.62 | 462.85 | 0.00 | 0.00 | 0.00 |
December | 113.48 | 38.89 | 74.60 | 52.23 | 581.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 380.85 | 162.81 | 218.04 | 385.96 | 350.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 113.48 | 35.67 | 74.60 | 44.67 | 190.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 706.79 | 371.53 | 353.23 | 863.34 | 581.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 321.15 | 0.00 | 321.15 | 10.80 | 2008.14 | 0.00 | 0.00 | 0.00 |
February | 499.72 | 0.00 | 499.72 | 97.03 | 1790.63 | 0.00 | 0.00 | 0.00 |
March | 736.26 | 0.00 | 736.26 | 306.88 | 1484.64 | 0.00 | 0.00 | 0.00 |
April | 1041.89 | 3.70 | 1038.19 | 678.59 | 1188.44 | 0.00 | 0.00 | 0.00 |
May | 1340.65 | 39.83 | 1300.82 | 1093.53 | 960.92 | 0.00 | 0.00 | 0.00 |
June | 1409.66 | 93.09 | 1316.57 | 1271.65 | 740.03 | 0.00 | 0.00 | 0.00 |
July | 1339.80 | 105.05 | 1234.75 | 1372.78 | 663.46 | 0.00 | 0.00 | 0.00 |
August | 1084.58 | 29.32 | 1055.26 | 1132.19 | 648.77 | 0.00 | 0.00 | 0.00 |
September | 842.46 | 0.25 | 842.21 | 652.11 | 967.44 | 0.00 | 0.00 | 0.00 |
October | 577.23 | 0.00 | 577.23 | 261.37 | 1304.78 | 0.00 | 0.00 | 0.00 |
November | 363.60 | 0.00 | 363.60 | 48.91 | 1649.01 | 0.00 | 0.00 | 0.00 |
December | 272.90 | 0.00 | 272.90 | 4.90 | 2029.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 820.74 | 22.77 | 797.97 | 580.58 | 1283.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 272.90 | 0.00 | 272.90 | 4.90 | 648.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1409.66 | 105.05 | 1316.57 | 1372.78 | 2029.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 344.03 | 87.22 | 256.81 | 120.66 | 1270.62 | 0.00 | 0.00 | 0.00 |
February | 631.26 | 224.05 | 407.22 | 407.11 | 1127.84 | 0.00 | 0.00 | 0.00 |
March | 942.52 | 341.20 | 601.32 | 779.16 | 946.91 | 0.00 | 0.00 | 0.00 |
April | 1461.07 | 607.10 | 853.97 | 1472.17 | 767.73 | 0.00 | 0.00 | 0.00 |
May | 1554.71 | 540.54 | 1014.17 | 1650.59 | 645.03 | 0.00 | 0.00 | 0.00 |
June | 1861.94 | 810.14 | 1051.80 | 2125.73 | 508.19 | 0.00 | 0.00 | 0.00 |
July | 1733.90 | 778.27 | 955.62 | 2072.44 | 444.90 | 0.00 | 0.00 | 0.00 |
August | 1704.18 | 852.53 | 851.65 | 2105.82 | 436.07 | 0.00 | 0.00 | 0.00 |
September | 1259.99 | 581.12 | 678.87 | 1385.58 | 623.86 | 0.00 | 0.00 | 0.00 |
October | 821.26 | 348.96 | 472.30 | 745.08 | 836.99 | 0.00 | 0.00 | 0.00 |
November | 402.54 | 113.64 | 288.90 | 211.29 | 1052.01 | 0.00 | 0.00 | 0.00 |
December | 330.17 | 106.29 | 223.88 | 152.19 | 1295.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1089.30 | 450.24 | 639.06 | 1105.88 | 828.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 330.17 | 87.22 | 223.88 | 120.66 | 436.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1861.94 | 852.53 | 1051.80 | 2125.73 | 1295.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1418.95 | 842.58 | 576.37 | 1245.70 | 1847.83 | 0.00 | 0.00 | 0.00 |
February | 2182.13 | 1350.77 | 831.36 | 2189.12 | 1704.13 | 0.00 | 0.00 | 0.00 |
March | 2347.35 | 1251.81 | 1095.53 | 2470.05 | 1504.16 | 0.00 | 0.00 | 0.00 |
April | 2478.35 | 1076.09 | 1402.27 | 2766.52 | 1272.72 | 0.00 | 0.00 | 0.00 |
May | 2266.13 | 675.10 | 1591.03 | 2560.99 | 1052.50 | 0.00 | 0.00 | 0.00 |
June | 2073.29 | 556.65 | 1516.64 | 2399.16 | 829.20 | 0.00 | 0.00 | 0.00 |
July | 2261.02 | 828.10 | 1432.91 | 2891.74 | 750.83 | 0.00 | 0.00 | 0.00 |
August | 2429.18 | 1132.77 | 1296.41 | 3211.47 | 730.00 | 0.00 | 0.00 | 0.00 |
September | 2691.43 | 1486.30 | 1205.13 | 3332.26 | 1019.59 | 0.00 | 0.00 | 0.00 |
October | 2437.98 | 1505.27 | 932.71 | 2745.94 | 1331.02 | 0.00 | 0.00 | 0.00 |
November | 1441.41 | 826.05 | 615.36 | 1356.33 | 1585.23 | 0.00 | 0.00 | 0.00 |
December | 1508.13 | 975.97 | 532.16 | 1462.48 | 1916.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2127.03 | 1040.37 | 1086.66 | 2386.75 | 1293.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1418.95 | 556.65 | 532.16 | 1245.70 | 730.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2691.43 | 1505.27 | 1591.03 | 3332.26 | 1916.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.87 | 107.00 | 255.87 | 150.87 | 1324.62 | 0.00 | 0.00 | 0.00 |
February | 650.60 | 244.51 | 406.08 | 447.71 | 1184.55 | 0.00 | 0.00 | 0.00 |
March | 911.65 | 307.71 | 603.94 | 752.37 | 1006.53 | 0.00 | 0.00 | 0.00 |
April | 1386.98 | 530.30 | 856.68 | 1382.63 | 842.94 | 0.00 | 0.00 | 0.00 |
May | 1784.72 | 725.04 | 1059.68 | 1956.48 | 707.08 | 0.00 | 0.00 | 0.00 |
June | 1716.41 | 666.43 | 1049.99 | 1927.22 | 558.60 | 0.00 | 0.00 | 0.00 |
July | 2120.39 | 1114.59 | 1005.81 | 2611.26 | 520.94 | 0.00 | 0.00 | 0.00 |
August | 1754.07 | 895.68 | 858.39 | 2192.34 | 505.54 | 0.00 | 0.00 | 0.00 |
September | 1428.42 | 685.39 | 743.04 | 1641.95 | 689.57 | 0.00 | 0.00 | 0.00 |
October | 813.21 | 331.34 | 481.86 | 743.61 | 896.76 | 0.00 | 0.00 | 0.00 |
November | 404.97 | 114.22 | 290.75 | 217.68 | 1099.30 | 0.00 | 0.00 | 0.00 |
December | 340.46 | 116.67 | 223.79 | 180.36 | 1358.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1142.54 | 488.42 | 654.12 | 1188.56 | 889.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 340.46 | 107.00 | 223.79 | 150.87 | 505.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2120.39 | 1114.59 | 1059.68 | 2611.26 | 1358.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 321.15 | 0.00 | 321.15 | 16.80 | 1853.33 | 0.00 | 0.00 | 0.00 |
February | 499.72 | 0.00 | 499.72 | 118.93 | 1628.43 | 0.00 | 0.00 | 0.00 |
March | 736.26 | 0.00 | 736.26 | 349.97 | 1333.74 | 0.00 | 0.00 | 0.00 |
April | 1041.89 | 3.70 | 1038.19 | 722.27 | 1093.21 | 0.00 | 0.00 | 0.00 |
May | 1340.65 | 39.83 | 1300.82 | 1123.91 | 907.83 | 0.00 | 0.00 | 0.00 |
June | 1409.66 | 93.09 | 1316.57 | 1280.67 | 716.81 | 0.00 | 0.00 | 0.00 |
July | 1339.80 | 105.05 | 1234.75 | 1371.09 | 650.79 | 0.00 | 0.00 | 0.00 |
August | 1084.58 | 29.32 | 1055.26 | 1136.32 | 630.71 | 0.00 | 0.00 | 0.00 |
September | 842.46 | 0.25 | 842.21 | 679.45 | 898.27 | 0.00 | 0.00 | 0.00 |
October | 577.23 | 0.00 | 577.23 | 304.82 | 1157.15 | 0.00 | 0.00 | 0.00 |
November | 363.60 | 0.00 | 363.60 | 68.14 | 1457.67 | 0.00 | 0.00 | 0.00 |
December | 272.90 | 0.00 | 272.90 | 10.84 | 1843.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 820.74 | 22.77 | 797.97 | 601.57 | 1178.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 272.90 | 0.00 | 272.90 | 10.84 | 630.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1409.66 | 105.05 | 1316.57 | 1371.09 | 1853.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 344.03 | 87.22 | 256.81 | 130.83 | 1175.44 | 0.00 | 0.00 | 0.00 |
February | 631.26 | 224.05 | 407.22 | 432.14 | 1029.62 | 0.00 | 0.00 | 0.00 |
March | 942.52 | 341.20 | 601.32 | 810.73 | 860.00 | 0.00 | 0.00 | 0.00 |
April | 1461.07 | 607.10 | 853.97 | 1496.14 | 717.46 | 0.00 | 0.00 | 0.00 |
May | 1554.71 | 540.54 | 1014.17 | 1663.31 | 616.22 | 0.00 | 0.00 | 0.00 |
June | 1861.94 | 810.14 | 1051.80 | 2124.40 | 497.23 | 0.00 | 0.00 | 0.00 |
July | 1733.90 | 778.27 | 955.62 | 2067.61 | 440.78 | 0.00 | 0.00 | 0.00 |
August | 1704.18 | 852.53 | 851.65 | 2103.64 | 428.64 | 0.00 | 0.00 | 0.00 |
September | 1259.99 | 581.12 | 678.87 | 1398.70 | 588.22 | 0.00 | 0.00 | 0.00 |
October | 821.26 | 348.96 | 472.30 | 774.09 | 754.82 | 0.00 | 0.00 | 0.00 |
November | 402.54 | 113.64 | 288.90 | 230.54 | 939.76 | 0.00 | 0.00 | 0.00 |
December | 330.17 | 106.29 | 223.88 | 164.58 | 1181.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1089.30 | 450.24 | 639.06 | 1119.87 | 767.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 330.17 | 87.22 | 223.88 | 130.83 | 428.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1861.94 | 852.53 | 1051.80 | 2124.40 | 1181.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1418.95 | 842.58 | 576.37 | 1280.12 | 1698.96 | 0.00 | 0.00 | 0.00 |
February | 2182.13 | 1350.77 | 831.36 | 2237.31 | 1555.31 | 0.00 | 0.00 | 0.00 |
March | 2347.35 | 1251.81 | 1095.53 | 2509.38 | 1367.74 | 0.00 | 0.00 | 0.00 |
April | 2478.35 | 1076.09 | 1402.27 | 2797.41 | 1187.62 | 0.00 | 0.00 | 0.00 |
May | 2266.13 | 675.10 | 1591.03 | 2578.74 | 999.74 | 0.00 | 0.00 | 0.00 |
June | 2073.29 | 556.65 | 1516.64 | 2400.77 | 804.30 | 0.00 | 0.00 | 0.00 |
July | 2261.02 | 828.10 | 1432.91 | 2885.50 | 738.94 | 0.00 | 0.00 | 0.00 |
August | 2429.18 | 1132.77 | 1296.41 | 3208.52 | 713.58 | 0.00 | 0.00 | 0.00 |
September | 2691.43 | 1486.30 | 1205.13 | 3349.59 | 962.73 | 0.00 | 0.00 | 0.00 |
October | 2437.98 | 1505.27 | 932.71 | 2785.29 | 1205.21 | 0.00 | 0.00 | 0.00 |
November | 1441.41 | 826.05 | 615.36 | 1399.63 | 1416.52 | 0.00 | 0.00 | 0.00 |
December | 1508.13 | 975.97 | 532.16 | 1496.50 | 1743.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2127.03 | 1040.37 | 1086.66 | 2411.32 | 1197.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1418.95 | 556.65 | 532.16 | 1280.12 | 713.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2691.43 | 1505.27 | 1591.03 | 3349.59 | 1743.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.87 | 107.00 | 255.87 | 158.93 | 1225.41 | 0.00 | 0.00 | 0.00 |
February | 650.60 | 244.51 | 406.08 | 465.23 | 1094.68 | 0.00 | 0.00 | 0.00 |
March | 911.65 | 307.71 | 603.94 | 775.96 | 924.55 | 0.00 | 0.00 | 0.00 |
April | 1386.98 | 530.30 | 856.68 | 1403.04 | 790.90 | 0.00 | 0.00 | 0.00 |
May | 1784.72 | 725.04 | 1059.68 | 1966.84 | 675.58 | 0.00 | 0.00 | 0.00 |
June | 1716.41 | 666.43 | 1049.99 | 1927.30 | 542.84 | 0.00 | 0.00 | 0.00 |
July | 2120.39 | 1114.59 | 1005.81 | 2604.45 | 513.17 | 0.00 | 0.00 | 0.00 |
August | 1754.07 | 895.68 | 858.39 | 2189.92 | 495.06 | 0.00 | 0.00 | 0.00 |
September | 1428.42 | 685.39 | 743.04 | 1653.21 | 653.41 | 0.00 | 0.00 | 0.00 |
October | 813.21 | 331.34 | 481.86 | 766.20 | 818.37 | 0.00 | 0.00 | 0.00 |
November | 404.97 | 114.22 | 290.75 | 232.24 | 998.74 | 0.00 | 0.00 | 0.00 |
December | 340.46 | 116.67 | 223.79 | 188.22 | 1253.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1142.54 | 488.42 | 654.12 | 1199.09 | 830.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 340.46 | 107.00 | 223.79 | 158.93 | 495.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2120.39 | 1114.59 | 1059.68 | 2604.45 | 1253.61 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172035E+09 | 0.00 | 0.172035E+09 | 2024270.20 | 0.125642E+10 |
February | 0.241786E+09 | 0.00 | 0.241786E+09 | 30207921.98 | 0.100322E+10 |
March | 0.394401E+09 | 0.00 | 0.394401E+09 | 0.134663E+09 | 0.905986E+09 |
April | 0.540114E+09 | 1915937.09 | 0.538198E+09 | 0.322652E+09 | 0.685756E+09 |
May | 0.718157E+09 | 21335276.51 | 0.696822E+09 | 0.571013E+09 | 0.544028E+09 |
June | 0.730766E+09 | 48256418.36 | 0.682509E+09 | 0.648621E+09 | 0.404031E+09 |
July | 0.717705E+09 | 56271089.53 | 0.661434E+09 | 0.724042E+09 | 0.370532E+09 |
August | 0.580987E+09 | 15705726.41 | 0.565282E+09 | 0.593543E+09 | 0.364616E+09 |
September | 0.436732E+09 | 128784.92 | 0.436604E+09 | 0.325706E+09 | 0.537363E+09 |
October | 0.309209E+09 | 0.00 | 0.309209E+09 | 0.116616E+09 | 0.792294E+09 |
November | 0.188488E+09 | 0.00 | 0.188488E+09 | 14754570.43 | 0.101366E+10 |
December | 0.146185E+09 | 0.00 | 0.146185E+09 | 404133.23 | 0.129918E+10 |
Annual Sum or Average | 0.517657E+10 | 0.143613E+09 | 0.503295E+10 | 0.348425E+10 | 0.917709E+10 |
Minimum of Months | 0.146185E+09 | 0.00 | 0.146185E+09 | 404133.23 | 0.364616E+09 |
Maximum of Months | 0.730766E+09 | 56271089.53 | 0.696822E+09 | 0.724042E+09 | 0.129918E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172032E+09 | 0.00 | 0.172032E+09 | 2023976.73 | 0.125642E+10 |
February | 0.241782E+09 | 0.00 | 0.241782E+09 | 30206148.22 | 0.100322E+10 |
March | 0.394395E+09 | 0.00 | 0.394395E+09 | 0.134658E+09 | 0.905987E+09 |
April | 0.540106E+09 | 1915894.97 | 0.538190E+09 | 0.322644E+09 | 0.685756E+09 |
May | 0.718147E+09 | 21334807.47 | 0.696812E+09 | 0.571000E+09 | 0.544028E+09 |
June | 0.730755E+09 | 48255357.50 | 0.682500E+09 | 0.648608E+09 | 0.404030E+09 |
July | 0.717695E+09 | 56269852.47 | 0.661425E+09 | 0.724030E+09 | 0.370532E+09 |
August | 0.580979E+09 | 15705381.14 | 0.565274E+09 | 0.593533E+09 | 0.364615E+09 |
September | 0.436726E+09 | 128782.09 | 0.436597E+09 | 0.325699E+09 | 0.537362E+09 |
October | 0.309204E+09 | 0.00 | 0.309204E+09 | 0.116612E+09 | 0.792294E+09 |
November | 0.188485E+09 | 0.00 | 0.188485E+09 | 14753612.13 | 0.101366E+10 |
December | 0.146183E+09 | 0.00 | 0.146183E+09 | 404064.65 | 0.129918E+10 |
Annual Sum or Average | 0.517649E+10 | 0.143610E+09 | 0.503288E+10 | 0.348417E+10 | 0.917709E+10 |
Minimum of Months | 0.146183E+09 | 0.00 | 0.146183E+09 | 404064.65 | 0.364615E+09 |
Maximum of Months | 0.730755E+09 | 56269852.47 | 0.696812E+09 | 0.724030E+09 | 0.129918E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172033E+09 | 0.00 | 0.172033E+09 | 2024074.55 | 0.125642E+10 |
February | 0.241783E+09 | 0.00 | 0.241783E+09 | 30206739.47 | 0.100322E+10 |
March | 0.394397E+09 | 0.00 | 0.394397E+09 | 0.134659E+09 | 0.905987E+09 |
April | 0.540109E+09 | 1915909.01 | 0.538193E+09 | 0.322647E+09 | 0.685756E+09 |
May | 0.718150E+09 | 21334963.82 | 0.696815E+09 | 0.571005E+09 | 0.544028E+09 |
June | 0.730759E+09 | 48255711.12 | 0.682503E+09 | 0.648612E+09 | 0.404030E+09 |
July | 0.717699E+09 | 56270264.82 | 0.661428E+09 | 0.724034E+09 | 0.370532E+09 |
August | 0.580982E+09 | 15705496.23 | 0.565277E+09 | 0.593536E+09 | 0.364615E+09 |
September | 0.436728E+09 | 128783.03 | 0.436599E+09 | 0.325701E+09 | 0.537362E+09 |
October | 0.309205E+09 | 0.00 | 0.309205E+09 | 0.116613E+09 | 0.792294E+09 |
November | 0.188486E+09 | 0.00 | 0.188486E+09 | 14753931.56 | 0.101366E+10 |
December | 0.146184E+09 | 0.00 | 0.146184E+09 | 404087.51 | 0.129918E+10 |
Annual Sum or Average | 0.517652E+10 | 0.143611E+09 | 0.503290E+10 | 0.348420E+10 | 0.917709E+10 |
Minimum of Months | 0.146184E+09 | 0.00 | 0.146184E+09 | 404087.51 | 0.364615E+09 |
Maximum of Months | 0.730759E+09 | 56270264.82 | 0.696815E+09 | 0.724034E+09 | 0.129918E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172032E+09 | 0.00 | 0.172032E+09 | 2023976.73 | 0.125642E+10 |
February | 0.241782E+09 | 0.00 | 0.241782E+09 | 30206148.22 | 0.100322E+10 |
March | 0.394395E+09 | 0.00 | 0.394395E+09 | 0.134658E+09 | 0.905987E+09 |
April | 0.540106E+09 | 1915894.97 | 0.538190E+09 | 0.322644E+09 | 0.685756E+09 |
May | 0.718147E+09 | 21334807.47 | 0.696812E+09 | 0.571000E+09 | 0.544028E+09 |
June | 0.730755E+09 | 48255357.50 | 0.682500E+09 | 0.648608E+09 | 0.404030E+09 |
July | 0.717695E+09 | 56269852.47 | 0.661425E+09 | 0.724030E+09 | 0.370532E+09 |
August | 0.580979E+09 | 15705381.14 | 0.565274E+09 | 0.593533E+09 | 0.364615E+09 |
September | 0.436726E+09 | 128782.09 | 0.436597E+09 | 0.325699E+09 | 0.537362E+09 |
October | 0.309204E+09 | 0.00 | 0.309204E+09 | 0.116612E+09 | 0.792294E+09 |
November | 0.188485E+09 | 0.00 | 0.188485E+09 | 14753612.13 | 0.101366E+10 |
December | 0.146183E+09 | 0.00 | 0.146183E+09 | 404064.65 | 0.129918E+10 |
Annual Sum or Average | 0.517649E+10 | 0.143610E+09 | 0.503288E+10 | 0.348417E+10 | 0.917709E+10 |
Minimum of Months | 0.146183E+09 | 0.00 | 0.146183E+09 | 404064.65 | 0.364615E+09 |
Maximum of Months | 0.730755E+09 | 56269852.47 | 0.696812E+09 | 0.724030E+09 | 0.129918E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172026E+09 | 0.00 | 0.172026E+09 | 2023944.06 | 0.125637E+10 |
February | 0.241773E+09 | 0.00 | 0.241773E+09 | 30205226.39 | 0.100318E+10 |
March | 0.394380E+09 | 0.00 | 0.394380E+09 | 0.134653E+09 | 0.905950E+09 |
April | 0.540086E+09 | 1915824.77 | 0.538170E+09 | 0.322632E+09 | 0.685729E+09 |
May | 0.718120E+09 | 21334025.76 | 0.696785E+09 | 0.570980E+09 | 0.544006E+09 |
June | 0.730728E+09 | 48253589.40 | 0.682474E+09 | 0.648584E+09 | 0.404014E+09 |
July | 0.717668E+09 | 56267790.72 | 0.661400E+09 | 0.724003E+09 | 0.370517E+09 |
August | 0.580957E+09 | 15704805.69 | 0.565253E+09 | 0.593511E+09 | 0.364600E+09 |
September | 0.436710E+09 | 128777.37 | 0.436581E+09 | 0.325687E+09 | 0.537340E+09 |
October | 0.309192E+09 | 0.00 | 0.309192E+09 | 0.116608E+09 | 0.792262E+09 |
November | 0.188478E+09 | 0.00 | 0.188478E+09 | 14753177.20 | 0.101362E+10 |
December | 0.146178E+09 | 0.00 | 0.146178E+09 | 404059.79 | 0.129913E+10 |
Annual Sum or Average | 0.517629E+10 | 0.143605E+09 | 0.503269E+10 | 0.348404E+10 | 0.917672E+10 |
Minimum of Months | 0.146178E+09 | 0.00 | 0.146178E+09 | 404059.79 | 0.364600E+09 |
Maximum of Months | 0.730728E+09 | 56267790.72 | 0.696785E+09 | 0.724003E+09 | 0.129913E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307154E+09 | 77873834.77 | 0.229281E+09 | 95367597.99 | 0.129727E+10 |
February | 0.509057E+09 | 0.180675E+09 | 0.328382E+09 | 0.303443E+09 | 0.101461E+10 |
March | 0.841492E+09 | 0.304627E+09 | 0.536865E+09 | 0.673296E+09 | 0.925448E+09 |
April | 0.126238E+10 | 0.524536E+09 | 0.737841E+09 | 0.126307E+10 | 0.701296E+09 |
May | 0.138806E+10 | 0.482596E+09 | 0.905462E+09 | 0.147198E+10 | 0.598706E+09 |
June | 0.160873E+10 | 0.699971E+09 | 0.908761E+09 | 0.184553E+10 | 0.448572E+09 |
July | 0.154804E+10 | 0.694849E+09 | 0.853190E+09 | 0.185983E+10 | 0.396534E+09 |
August | 0.152151E+10 | 0.761145E+09 | 0.760362E+09 | 0.189093E+10 | 0.383758E+09 |
September | 0.108864E+10 | 0.502092E+09 | 0.586551E+09 | 0.119366E+10 | 0.564573E+09 |
October | 0.733228E+09 | 0.311553E+09 | 0.421675E+09 | 0.647586E+09 | 0.817877E+09 |
November | 0.347795E+09 | 98185949.29 | 0.249609E+09 | 0.165550E+09 | 0.103329E+10 |
December | 0.294779E+09 | 94898057.71 | 0.199881E+09 | 0.122654E+09 | 0.131592E+10 |
Annual Sum or Average | 0.114509E+11 | 0.473300E+10 | 0.671786E+10 | 0.115329E+11 | 0.949786E+10 |
Minimum of Months | 0.294779E+09 | 77873834.77 | 0.199881E+09 | 95367597.99 | 0.383758E+09 |
Maximum of Months | 0.160873E+10 | 0.761145E+09 | 0.908761E+09 | 0.189093E+10 | 0.131592E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307154E+09 | 77873834.77 | 0.229281E+09 | 95367597.99 | 0.129727E+10 |
February | 0.509057E+09 | 0.180675E+09 | 0.328382E+09 | 0.303443E+09 | 0.101461E+10 |
March | 0.841492E+09 | 0.304627E+09 | 0.536865E+09 | 0.673296E+09 | 0.925448E+09 |
April | 0.126238E+10 | 0.524536E+09 | 0.737841E+09 | 0.126307E+10 | 0.701296E+09 |
May | 0.138806E+10 | 0.482596E+09 | 0.905462E+09 | 0.147198E+10 | 0.598706E+09 |
June | 0.160873E+10 | 0.699971E+09 | 0.908761E+09 | 0.184553E+10 | 0.448572E+09 |
July | 0.154804E+10 | 0.694849E+09 | 0.853190E+09 | 0.185983E+10 | 0.396534E+09 |
August | 0.152151E+10 | 0.761145E+09 | 0.760362E+09 | 0.189093E+10 | 0.383758E+09 |
September | 0.108864E+10 | 0.502092E+09 | 0.586551E+09 | 0.119366E+10 | 0.564573E+09 |
October | 0.733228E+09 | 0.311553E+09 | 0.421675E+09 | 0.647586E+09 | 0.817877E+09 |
November | 0.347795E+09 | 98185949.29 | 0.249609E+09 | 0.165550E+09 | 0.103329E+10 |
December | 0.294779E+09 | 94898057.71 | 0.199881E+09 | 0.122654E+09 | 0.131592E+10 |
Annual Sum or Average | 0.114509E+11 | 0.473300E+10 | 0.671786E+10 | 0.115329E+11 | 0.949786E+10 |
Minimum of Months | 0.294779E+09 | 77873834.77 | 0.199881E+09 | 95367597.99 | 0.383758E+09 |
Maximum of Months | 0.160873E+10 | 0.761145E+09 | 0.908761E+09 | 0.189093E+10 | 0.131592E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307149E+09 | 77872411.84 | 0.229276E+09 | 95365855.42 | 0.129725E+10 |
February | 0.509047E+09 | 0.180672E+09 | 0.328376E+09 | 0.303438E+09 | 0.101459E+10 |
March | 0.841476E+09 | 0.304622E+09 | 0.536855E+09 | 0.673284E+09 | 0.925431E+09 |
April | 0.126235E+10 | 0.524527E+09 | 0.737827E+09 | 0.126305E+10 | 0.701283E+09 |
May | 0.138803E+10 | 0.482587E+09 | 0.905445E+09 | 0.147195E+10 | 0.598695E+09 |
June | 0.160870E+10 | 0.699958E+09 | 0.908744E+09 | 0.184550E+10 | 0.448564E+09 |
July | 0.154801E+10 | 0.694837E+09 | 0.853175E+09 | 0.185979E+10 | 0.396527E+09 |
August | 0.152148E+10 | 0.761131E+09 | 0.760348E+09 | 0.189090E+10 | 0.383751E+09 |
September | 0.108862E+10 | 0.502082E+09 | 0.586541E+09 | 0.119364E+10 | 0.564563E+09 |
October | 0.733215E+09 | 0.311548E+09 | 0.421668E+09 | 0.647574E+09 | 0.817862E+09 |
November | 0.347788E+09 | 98184155.22 | 0.249604E+09 | 0.165547E+09 | 0.103327E+10 |
December | 0.294774E+09 | 94896323.72 | 0.199877E+09 | 0.122651E+09 | 0.131590E+10 |
Annual Sum or Average | 0.114507E+11 | 0.473291E+10 | 0.671774E+10 | 0.115327E+11 | 0.949769E+10 |
Minimum of Months | 0.294774E+09 | 77872411.84 | 0.199877E+09 | 95365855.42 | 0.383751E+09 |
Maximum of Months | 0.160870E+10 | 0.761131E+09 | 0.908744E+09 | 0.189090E+10 | 0.131590E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.760091E+09 | 0.451345E+09 | 0.308746E+09 | 0.657455E+09 | 0.106307E+10 |
February | 0.105578E+10 | 0.653543E+09 | 0.402241E+09 | 0.105209E+10 | 0.868490E+09 |
March | 0.125740E+10 | 0.670558E+09 | 0.586846E+09 | 0.132171E+10 | 0.845443E+09 |
April | 0.128476E+10 | 0.557832E+09 | 0.726925E+09 | 0.143546E+10 | 0.686489E+09 |
May | 0.121391E+10 | 0.361632E+09 | 0.852273E+09 | 0.137868E+10 | 0.575855E+09 |
June | 0.107478E+10 | 0.288563E+09 | 0.786218E+09 | 0.124788E+10 | 0.441528E+09 |
July | 0.121116E+10 | 0.443590E+09 | 0.767575E+09 | 0.155442E+10 | 0.407824E+09 |
August | 0.130124E+10 | 0.606787E+09 | 0.694454E+09 | 0.172562E+10 | 0.394980E+09 |
September | 0.139521E+10 | 0.770479E+09 | 0.624733E+09 | 0.173358E+10 | 0.537498E+09 |
October | 0.130595E+10 | 0.806327E+09 | 0.499625E+09 | 0.147414E+10 | 0.740841E+09 |
November | 0.747215E+09 | 0.428216E+09 | 0.318999E+09 | 0.693766E+09 | 0.881633E+09 |
December | 0.807860E+09 | 0.522797E+09 | 0.285063E+09 | 0.771938E+09 | 0.111314E+10 |
Annual Sum or Average | 0.134154E+11 | 0.656167E+10 | 0.685370E+10 | 0.150467E+11 | 0.855678E+10 |
Minimum of Months | 0.747215E+09 | 0.288563E+09 | 0.285063E+09 | 0.657455E+09 | 0.394980E+09 |
Maximum of Months | 0.139521E+10 | 0.806327E+09 | 0.852273E+09 | 0.173358E+10 | 0.111314E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.760086E+09 | 0.451341E+09 | 0.308745E+09 | 0.657449E+09 | 0.106307E+10 |
February | 0.105578E+10 | 0.653538E+09 | 0.402238E+09 | 0.105208E+10 | 0.868490E+09 |
March | 0.125740E+10 | 0.670553E+09 | 0.586843E+09 | 0.132170E+10 | 0.845443E+09 |
April | 0.128475E+10 | 0.557828E+09 | 0.726921E+09 | 0.143545E+10 | 0.686489E+09 |
May | 0.121390E+10 | 0.361630E+09 | 0.852268E+09 | 0.137867E+10 | 0.575855E+09 |
June | 0.107477E+10 | 0.288561E+09 | 0.786214E+09 | 0.124787E+10 | 0.441528E+09 |
July | 0.121116E+10 | 0.443586E+09 | 0.767571E+09 | 0.155441E+10 | 0.407824E+09 |
August | 0.130123E+10 | 0.606783E+09 | 0.694451E+09 | 0.172561E+10 | 0.394979E+09 |
September | 0.139520E+10 | 0.770474E+09 | 0.624729E+09 | 0.173357E+10 | 0.537498E+09 |
October | 0.130594E+10 | 0.806321E+09 | 0.499622E+09 | 0.147413E+10 | 0.740841E+09 |
November | 0.747210E+09 | 0.428213E+09 | 0.318997E+09 | 0.693759E+09 | 0.881633E+09 |
December | 0.807854E+09 | 0.522794E+09 | 0.285061E+09 | 0.771930E+09 | 0.111314E+10 |
Annual Sum or Average | 0.134153E+11 | 0.656162E+10 | 0.685366E+10 | 0.150466E+11 | 0.855678E+10 |
Minimum of Months | 0.747210E+09 | 0.288561E+09 | 0.285061E+09 | 0.657449E+09 | 0.394979E+09 |
Maximum of Months | 0.139520E+10 | 0.806321E+09 | 0.852268E+09 | 0.173357E+10 | 0.111314E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.760091E+09 | 0.451345E+09 | 0.308746E+09 | 0.657455E+09 | 0.106307E+10 |
February | 0.105578E+10 | 0.653543E+09 | 0.402241E+09 | 0.105209E+10 | 0.868490E+09 |
March | 0.125740E+10 | 0.670558E+09 | 0.586846E+09 | 0.132171E+10 | 0.845443E+09 |
April | 0.128476E+10 | 0.557832E+09 | 0.726925E+09 | 0.143546E+10 | 0.686489E+09 |
May | 0.121391E+10 | 0.361632E+09 | 0.852273E+09 | 0.137868E+10 | 0.575855E+09 |
June | 0.107478E+10 | 0.288563E+09 | 0.786218E+09 | 0.124788E+10 | 0.441528E+09 |
July | 0.121116E+10 | 0.443590E+09 | 0.767575E+09 | 0.155442E+10 | 0.407824E+09 |
August | 0.130124E+10 | 0.606787E+09 | 0.694454E+09 | 0.172562E+10 | 0.394980E+09 |
September | 0.139521E+10 | 0.770479E+09 | 0.624733E+09 | 0.173358E+10 | 0.537498E+09 |
October | 0.130595E+10 | 0.806327E+09 | 0.499625E+09 | 0.147414E+10 | 0.740841E+09 |
November | 0.747215E+09 | 0.428216E+09 | 0.318999E+09 | 0.693766E+09 | 0.881633E+09 |
December | 0.807860E+09 | 0.522797E+09 | 0.285063E+09 | 0.771938E+09 | 0.111314E+10 |
Annual Sum or Average | 0.134154E+11 | 0.656167E+10 | 0.685370E+10 | 0.150467E+11 | 0.855678E+10 |
Minimum of Months | 0.747215E+09 | 0.288563E+09 | 0.285063E+09 | 0.657455E+09 | 0.394980E+09 |
Maximum of Months | 0.139521E+10 | 0.806327E+09 | 0.852273E+09 | 0.173358E+10 | 0.111314E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.760086E+09 | 0.451341E+09 | 0.308745E+09 | 0.657449E+09 | 0.106307E+10 |
February | 0.105578E+10 | 0.653538E+09 | 0.402238E+09 | 0.105208E+10 | 0.868490E+09 |
March | 0.125740E+10 | 0.670553E+09 | 0.586843E+09 | 0.132170E+10 | 0.845443E+09 |
April | 0.128475E+10 | 0.557828E+09 | 0.726921E+09 | 0.143545E+10 | 0.686489E+09 |
May | 0.121390E+10 | 0.361630E+09 | 0.852268E+09 | 0.137867E+10 | 0.575855E+09 |
June | 0.107477E+10 | 0.288561E+09 | 0.786214E+09 | 0.124787E+10 | 0.441528E+09 |
July | 0.121116E+10 | 0.443586E+09 | 0.767571E+09 | 0.155441E+10 | 0.407824E+09 |
August | 0.130123E+10 | 0.606783E+09 | 0.694451E+09 | 0.172561E+10 | 0.394979E+09 |
September | 0.139520E+10 | 0.770474E+09 | 0.624729E+09 | 0.173357E+10 | 0.537498E+09 |
October | 0.130594E+10 | 0.806321E+09 | 0.499622E+09 | 0.147413E+10 | 0.740841E+09 |
November | 0.747210E+09 | 0.428213E+09 | 0.318997E+09 | 0.693759E+09 | 0.881633E+09 |
December | 0.807854E+09 | 0.522794E+09 | 0.285061E+09 | 0.771930E+09 | 0.111314E+10 |
Annual Sum or Average | 0.134153E+11 | 0.656162E+10 | 0.685366E+10 | 0.150466E+11 | 0.855678E+10 |
Minimum of Months | 0.747210E+09 | 0.288561E+09 | 0.285061E+09 | 0.657449E+09 | 0.394979E+09 |
Maximum of Months | 0.139520E+10 | 0.806321E+09 | 0.852268E+09 | 0.173357E+10 | 0.111314E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.760058E+09 | 0.451325E+09 | 0.308733E+09 | 0.657425E+09 | 0.106302E+10 |
February | 0.105574E+10 | 0.653514E+09 | 0.402223E+09 | 0.105204E+10 | 0.868455E+09 |
March | 0.125735E+10 | 0.670528E+09 | 0.586821E+09 | 0.132166E+10 | 0.845409E+09 |
April | 0.128470E+10 | 0.557807E+09 | 0.726894E+09 | 0.143539E+10 | 0.686462E+09 |
May | 0.121385E+10 | 0.361616E+09 | 0.852236E+09 | 0.137862E+10 | 0.575832E+09 |
June | 0.107473E+10 | 0.288550E+09 | 0.786184E+09 | 0.124782E+10 | 0.441510E+09 |
July | 0.121111E+10 | 0.443570E+09 | 0.767542E+09 | 0.155435E+10 | 0.407807E+09 |
August | 0.130118E+10 | 0.606760E+09 | 0.694424E+09 | 0.172554E+10 | 0.394964E+09 |
September | 0.139515E+10 | 0.770445E+09 | 0.624706E+09 | 0.173350E+10 | 0.537477E+09 |
October | 0.130589E+10 | 0.806291E+09 | 0.499603E+09 | 0.147408E+10 | 0.740811E+09 |
November | 0.747182E+09 | 0.428197E+09 | 0.318985E+09 | 0.693735E+09 | 0.881597E+09 |
December | 0.807825E+09 | 0.522774E+09 | 0.285050E+09 | 0.771903E+09 | 0.111309E+10 |
Annual Sum or Average | 0.134148E+11 | 0.656138E+10 | 0.685340E+10 | 0.150461E+11 | 0.855644E+10 |
Minimum of Months | 0.747182E+09 | 0.288550E+09 | 0.285050E+09 | 0.657425E+09 | 0.394964E+09 |
Maximum of Months | 0.139515E+10 | 0.806291E+09 | 0.852236E+09 | 0.173350E+10 | 0.111309E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.323973E+09 | 95533745.08 | 0.228439E+09 | 0.119638E+09 | 0.139494E+10 |
February | 0.524646E+09 | 0.197177E+09 | 0.327469E+09 | 0.327149E+09 | 0.114449E+10 |
March | 0.813931E+09 | 0.274723E+09 | 0.539207E+09 | 0.625331E+09 | 0.108313E+10 |
April | 0.119836E+10 | 0.458180E+09 | 0.740182E+09 | 0.114524E+10 | 0.860961E+09 |
May | 0.159341E+10 | 0.647318E+09 | 0.946096E+09 | 0.173392E+10 | 0.678258E+09 |
June | 0.148299E+10 | 0.575798E+09 | 0.907197E+09 | 0.164561E+10 | 0.533792E+09 |
July | 0.189311E+10 | 0.995113E+09 | 0.897992E+09 | 0.231240E+10 | 0.510701E+09 |
August | 0.156605E+10 | 0.799671E+09 | 0.766380E+09 | 0.192931E+10 | 0.510447E+09 |
September | 0.123417E+10 | 0.592182E+09 | 0.641989E+09 | 0.140446E+10 | 0.648704E+09 |
October | 0.726038E+09 | 0.295826E+09 | 0.430212E+09 | 0.629080E+09 | 0.946725E+09 |
November | 0.349899E+09 | 98686103.42 | 0.251213E+09 | 0.159709E+09 | 0.119973E+10 |
December | 0.303963E+09 | 0.104160E+09 | 0.199803E+09 | 0.139903E+09 | 0.155630E+10 |
Annual Sum or Average | 0.120105E+11 | 0.513437E+10 | 0.687618E+10 | 0.121718E+11 | 0.110682E+11 |
Minimum of Months | 0.303963E+09 | 95533745.08 | 0.199803E+09 | 0.119638E+09 | 0.510447E+09 |
Maximum of Months | 0.189311E+10 | 0.995113E+09 | 0.946096E+09 | 0.231240E+10 | 0.155630E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.323973E+09 | 95533745.08 | 0.228439E+09 | 0.119638E+09 | 0.139494E+10 |
February | 0.524646E+09 | 0.197177E+09 | 0.327469E+09 | 0.327149E+09 | 0.114449E+10 |
March | 0.813931E+09 | 0.274723E+09 | 0.539207E+09 | 0.625331E+09 | 0.108313E+10 |
April | 0.119836E+10 | 0.458180E+09 | 0.740182E+09 | 0.114524E+10 | 0.860961E+09 |
May | 0.159341E+10 | 0.647318E+09 | 0.946096E+09 | 0.173392E+10 | 0.678258E+09 |
June | 0.148299E+10 | 0.575798E+09 | 0.907197E+09 | 0.164561E+10 | 0.533792E+09 |
July | 0.189311E+10 | 0.995113E+09 | 0.897992E+09 | 0.231240E+10 | 0.510701E+09 |
August | 0.156605E+10 | 0.799671E+09 | 0.766380E+09 | 0.192931E+10 | 0.510447E+09 |
September | 0.123417E+10 | 0.592182E+09 | 0.641989E+09 | 0.140446E+10 | 0.648704E+09 |
October | 0.726038E+09 | 0.295826E+09 | 0.430212E+09 | 0.629080E+09 | 0.946725E+09 |
November | 0.349899E+09 | 98686103.42 | 0.251213E+09 | 0.159709E+09 | 0.119973E+10 |
December | 0.303963E+09 | 0.104160E+09 | 0.199803E+09 | 0.139903E+09 | 0.155630E+10 |
Annual Sum or Average | 0.120105E+11 | 0.513437E+10 | 0.687618E+10 | 0.121718E+11 | 0.110682E+11 |
Minimum of Months | 0.303963E+09 | 95533745.08 | 0.199803E+09 | 0.119638E+09 | 0.510447E+09 |
Maximum of Months | 0.189311E+10 | 0.995113E+09 | 0.946096E+09 | 0.231240E+10 | 0.155630E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.323967E+09 | 95531999.47 | 0.228435E+09 | 0.119636E+09 | 0.139492E+10 |
February | 0.524636E+09 | 0.197173E+09 | 0.327463E+09 | 0.327143E+09 | 0.114447E+10 |
March | 0.813916E+09 | 0.274718E+09 | 0.539197E+09 | 0.625320E+09 | 0.108311E+10 |
April | 0.119834E+10 | 0.458172E+09 | 0.740169E+09 | 0.114522E+10 | 0.860946E+09 |
May | 0.159339E+10 | 0.647306E+09 | 0.946079E+09 | 0.173388E+10 | 0.678245E+09 |
June | 0.148297E+10 | 0.575787E+09 | 0.907180E+09 | 0.164558E+10 | 0.533783E+09 |
July | 0.189307E+10 | 0.995095E+09 | 0.897976E+09 | 0.231236E+10 | 0.510691E+09 |
August | 0.156602E+10 | 0.799656E+09 | 0.766366E+09 | 0.192927E+10 | 0.510438E+09 |
September | 0.123415E+10 | 0.592171E+09 | 0.641977E+09 | 0.140444E+10 | 0.648692E+09 |
October | 0.726025E+09 | 0.295820E+09 | 0.430204E+09 | 0.629068E+09 | 0.946708E+09 |
November | 0.349893E+09 | 98684300.21 | 0.251208E+09 | 0.159706E+09 | 0.119971E+10 |
December | 0.303958E+09 | 0.104159E+09 | 0.199799E+09 | 0.139901E+09 | 0.155627E+10 |
Annual Sum or Average | 0.120103E+11 | 0.513427E+10 | 0.687605E+10 | 0.121715E+11 | 0.110680E+11 |
Minimum of Months | 0.303958E+09 | 95531999.47 | 0.199799E+09 | 0.119636E+09 | 0.510438E+09 |
Maximum of Months | 0.189307E+10 | 0.995095E+09 | 0.946079E+09 | 0.231236E+10 | 0.155627E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.860177E+09 | 0.00 | 0.860177E+09 | 28921110.95 | 0.537859E+10 |
February | 0.120893E+10 | 0.00 | 0.120893E+10 | 0.234727E+09 | 0.433189E+10 |
March | 0.197201E+10 | 0.00 | 0.197201E+10 | 0.821937E+09 | 0.397645E+10 |
April | 0.270057E+10 | 9579746.50 | 0.269099E+10 | 0.175890E+10 | 0.308043E+10 |
May | 0.359079E+10 | 0.106677E+09 | 0.348411E+10 | 0.292890E+10 | 0.257374E+10 |
June | 0.365383E+10 | 0.241284E+09 | 0.341255E+10 | 0.329611E+10 | 0.191816E+10 |
July | 0.358852E+10 | 0.281357E+09 | 0.330717E+10 | 0.367686E+10 | 0.177701E+10 |
August | 0.290494E+10 | 78529132.50 | 0.282641E+10 | 0.303246E+10 | 0.173768E+10 |
September | 0.218366E+10 | 643928.69 | 0.218302E+10 | 0.169027E+10 | 0.250760E+10 |
October | 0.154604E+10 | 0.00 | 0.154604E+10 | 0.700067E+09 | 0.349473E+10 |
November | 0.942441E+09 | 0.00 | 0.942441E+09 | 0.126772E+09 | 0.427424E+10 |
December | 0.730928E+09 | 0.00 | 0.730928E+09 | 13134516.42 | 0.543550E+10 |
Annual Sum or Average | 0.258828E+11 | 0.718071E+09 | 0.251648E+11 | 0.183090E+11 | 0.404860E+11 |
Minimum of Months | 0.730928E+09 | 0.00 | 0.730928E+09 | 13134516.42 | 0.173768E+10 |
Maximum of Months | 0.365383E+10 | 0.281357E+09 | 0.348411E+10 | 0.367686E+10 | 0.543550E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.921454E+09 | 0.233619E+09 | 0.687835E+09 | 0.323176E+09 | 0.340323E+10 |
February | 0.152715E+10 | 0.542019E+09 | 0.985135E+09 | 0.984889E+09 | 0.272848E+10 |
March | 0.252445E+10 | 0.913872E+09 | 0.161058E+10 | 0.208691E+10 | 0.253621E+10 |
April | 0.378709E+10 | 0.157359E+10 | 0.221350E+10 | 0.381585E+10 | 0.198995E+10 |
May | 0.416413E+10 | 0.144777E+10 | 0.271636E+10 | 0.442095E+10 | 0.172764E+10 |
June | 0.482615E+10 | 0.209989E+10 | 0.272626E+10 | 0.550990E+10 | 0.131724E+10 |
July | 0.464407E+10 | 0.208453E+10 | 0.255954E+10 | 0.555082E+10 | 0.119161E+10 |
August | 0.456447E+10 | 0.228341E+10 | 0.228106E+10 | 0.564022E+10 | 0.116797E+10 |
September | 0.326590E+10 | 0.150626E+10 | 0.175964E+10 | 0.359141E+10 | 0.161705E+10 |
October | 0.219966E+10 | 0.934650E+09 | 0.126501E+10 | 0.199562E+10 | 0.224179E+10 |
November | 0.104337E+10 | 0.294555E+09 | 0.748819E+09 | 0.547667E+09 | 0.272681E+10 |
December | 0.884328E+09 | 0.284691E+09 | 0.599636E+09 | 0.407612E+09 | 0.347061E+10 |
Annual Sum or Average | 0.343522E+11 | 0.141989E+11 | 0.201534E+11 | 0.348750E+11 | 0.261186E+11 |
Minimum of Months | 0.884328E+09 | 0.233619E+09 | 0.599636E+09 | 0.323176E+09 | 0.116797E+10 |
Maximum of Months | 0.482615E+10 | 0.228341E+10 | 0.272626E+10 | 0.564022E+10 | 0.347061E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380053E+10 | 0.225677E+10 | 0.154376E+10 | 0.333649E+10 | 0.494922E+10 |
February | 0.527902E+10 | 0.326778E+10 | 0.201123E+10 | 0.529592E+10 | 0.412263E+10 |
March | 0.628713E+10 | 0.335286E+10 | 0.293427E+10 | 0.661579E+10 | 0.402874E+10 |
April | 0.642389E+10 | 0.278922E+10 | 0.363467E+10 | 0.717083E+10 | 0.329889E+10 |
May | 0.606962E+10 | 0.180820E+10 | 0.426142E+10 | 0.685935E+10 | 0.281902E+10 |
June | 0.537397E+10 | 0.144284E+10 | 0.393113E+10 | 0.621864E+10 | 0.214930E+10 |
July | 0.605590E+10 | 0.221799E+10 | 0.383791E+10 | 0.774524E+10 | 0.201102E+10 |
August | 0.650631E+10 | 0.303400E+10 | 0.347231E+10 | 0.860159E+10 | 0.195522E+10 |
September | 0.697618E+10 | 0.385248E+10 | 0.312370E+10 | 0.863721E+10 | 0.264278E+10 |
October | 0.652988E+10 | 0.403172E+10 | 0.249816E+10 | 0.735471E+10 | 0.356500E+10 |
November | 0.373614E+10 | 0.214113E+10 | 0.159502E+10 | 0.351560E+10 | 0.410892E+10 |
December | 0.403938E+10 | 0.261404E+10 | 0.142534E+10 | 0.391710E+10 | 0.513361E+10 |
Annual Sum or Average | 0.670779E+11 | 0.328090E+11 | 0.342689E+11 | 0.752685E+11 | 0.407844E+11 |
Minimum of Months | 0.373614E+10 | 0.144284E+10 | 0.142534E+10 | 0.333649E+10 | 0.195522E+10 |
Maximum of Months | 0.697618E+10 | 0.403172E+10 | 0.426142E+10 | 0.863721E+10 | 0.513361E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.971909E+09 | 0.286598E+09 | 0.685311E+09 | 0.404091E+09 | 0.354786E+10 |
February | 0.157392E+10 | 0.591524E+09 | 0.982398E+09 | 0.108311E+10 | 0.286567E+10 |
March | 0.244177E+10 | 0.824162E+09 | 0.161761E+10 | 0.201515E+10 | 0.269588E+10 |
April | 0.359505E+10 | 0.137453E+10 | 0.222052E+10 | 0.358378E+10 | 0.218489E+10 |
May | 0.478019E+10 | 0.194193E+10 | 0.283826E+10 | 0.524024E+10 | 0.189384E+10 |
June | 0.444894E+10 | 0.172738E+10 | 0.272156E+10 | 0.499535E+10 | 0.144788E+10 |
July | 0.567926E+10 | 0.298531E+10 | 0.269395E+10 | 0.699399E+10 | 0.139528E+10 |
August | 0.469811E+10 | 0.239899E+10 | 0.229912E+10 | 0.587195E+10 | 0.135405E+10 |
September | 0.370248E+10 | 0.177653E+10 | 0.192595E+10 | 0.425592E+10 | 0.178737E+10 |
October | 0.217809E+10 | 0.887468E+09 | 0.129062E+10 | 0.199167E+10 | 0.240189E+10 |
November | 0.104969E+10 | 0.296055E+09 | 0.753631E+09 | 0.564230E+09 | 0.284939E+10 |
December | 0.911880E+09 | 0.312478E+09 | 0.599402E+09 | 0.483086E+09 | 0.363771E+10 |
Annual Sum or Average | 0.360313E+11 | 0.154029E+11 | 0.206283E+11 | 0.374826E+11 | 0.280617E+11 |
Minimum of Months | 0.911880E+09 | 0.286598E+09 | 0.599402E+09 | 0.404091E+09 | 0.135405E+10 |
Maximum of Months | 0.567926E+10 | 0.298531E+10 | 0.283826E+10 | 0.699399E+10 | 0.363771E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.860177E+09 | 0.00 | 0.860177E+09 | 44994609.57 | 0.496395E+10 |
February | 0.120893E+10 | 0.00 | 0.120893E+10 | 0.287712E+09 | 0.393949E+10 |
March | 0.197201E+10 | 0.00 | 0.197201E+10 | 0.937349E+09 | 0.357228E+10 |
April | 0.270057E+10 | 9579746.50 | 0.269099E+10 | 0.187212E+10 | 0.283361E+10 |
May | 0.359079E+10 | 0.106677E+09 | 0.348411E+10 | 0.301029E+10 | 0.243153E+10 |
June | 0.365383E+10 | 0.241284E+09 | 0.341255E+10 | 0.331949E+10 | 0.185797E+10 |
July | 0.358852E+10 | 0.281357E+09 | 0.330717E+10 | 0.367233E+10 | 0.174308E+10 |
August | 0.290494E+10 | 78529132.50 | 0.282641E+10 | 0.304353E+10 | 0.168930E+10 |
September | 0.218366E+10 | 643928.69 | 0.218302E+10 | 0.176113E+10 | 0.232832E+10 |
October | 0.154604E+10 | 0.00 | 0.154604E+10 | 0.816422E+09 | 0.309932E+10 |
November | 0.942441E+09 | 0.00 | 0.942441E+09 | 0.176618E+09 | 0.377827E+10 |
December | 0.730928E+09 | 0.00 | 0.730928E+09 | 29027036.67 | 0.493651E+10 |
Annual Sum or Average | 0.258828E+11 | 0.718071E+09 | 0.251648E+11 | 0.189710E+11 | 0.371736E+11 |
Minimum of Months | 0.730928E+09 | 0.00 | 0.730928E+09 | 29027036.67 | 0.168930E+10 |
Maximum of Months | 0.365383E+10 | 0.281357E+09 | 0.348411E+10 | 0.367233E+10 | 0.496395E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.921454E+09 | 0.233619E+09 | 0.687835E+09 | 0.350424E+09 | 0.314830E+10 |
February | 0.152715E+10 | 0.542019E+09 | 0.985135E+09 | 0.104544E+10 | 0.249087E+10 |
March | 0.252445E+10 | 0.913872E+09 | 0.161058E+10 | 0.217145E+10 | 0.230341E+10 |
April | 0.378709E+10 | 0.157359E+10 | 0.221350E+10 | 0.387800E+10 | 0.185965E+10 |
May | 0.416413E+10 | 0.144777E+10 | 0.271636E+10 | 0.445501E+10 | 0.165047E+10 |
June | 0.482615E+10 | 0.209989E+10 | 0.272626E+10 | 0.550644E+10 | 0.128882E+10 |
July | 0.464407E+10 | 0.208453E+10 | 0.255954E+10 | 0.553789E+10 | 0.118059E+10 |
August | 0.456447E+10 | 0.228341E+10 | 0.228106E+10 | 0.563439E+10 | 0.114808E+10 |
September | 0.326590E+10 | 0.150626E+10 | 0.175964E+10 | 0.362544E+10 | 0.152467E+10 |
October | 0.219966E+10 | 0.934650E+09 | 0.126501E+10 | 0.207332E+10 | 0.202170E+10 |
November | 0.104337E+10 | 0.294555E+09 | 0.748819E+09 | 0.597562E+09 | 0.243587E+10 |
December | 0.884328E+09 | 0.284691E+09 | 0.599636E+09 | 0.440799E+09 | 0.316521E+10 |
Annual Sum or Average | 0.343522E+11 | 0.141989E+11 | 0.201534E+11 | 0.353162E+11 | 0.242176E+11 |
Minimum of Months | 0.884328E+09 | 0.233619E+09 | 0.599636E+09 | 0.350424E+09 | 0.114808E+10 |
Maximum of Months | 0.482615E+10 | 0.228341E+10 | 0.272626E+10 | 0.563439E+10 | 0.316521E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380053E+10 | 0.225677E+10 | 0.154376E+10 | 0.342867E+10 | 0.455051E+10 |
February | 0.527902E+10 | 0.326778E+10 | 0.201123E+10 | 0.541250E+10 | 0.376261E+10 |
March | 0.628713E+10 | 0.335286E+10 | 0.293427E+10 | 0.672111E+10 | 0.366336E+10 |
April | 0.642389E+10 | 0.278922E+10 | 0.363467E+10 | 0.725088E+10 | 0.307831E+10 |
May | 0.606962E+10 | 0.180820E+10 | 0.426142E+10 | 0.690689E+10 | 0.267770E+10 |
June | 0.537397E+10 | 0.144284E+10 | 0.393113E+10 | 0.622280E+10 | 0.208474E+10 |
July | 0.605590E+10 | 0.221799E+10 | 0.383791E+10 | 0.772853E+10 | 0.197919E+10 |
August | 0.650631E+10 | 0.303400E+10 | 0.347231E+10 | 0.859371E+10 | 0.191125E+10 |
September | 0.697618E+10 | 0.385248E+10 | 0.312370E+10 | 0.868215E+10 | 0.249539E+10 |
October | 0.652988E+10 | 0.403172E+10 | 0.249816E+10 | 0.746011E+10 | 0.322804E+10 |
November | 0.373614E+10 | 0.214113E+10 | 0.159502E+10 | 0.362783E+10 | 0.367162E+10 |
December | 0.403938E+10 | 0.261404E+10 | 0.142534E+10 | 0.400823E+10 | 0.467018E+10 |
Annual Sum or Average | 0.670779E+11 | 0.328090E+11 | 0.342689E+11 | 0.760434E+11 | 0.377729E+11 |
Minimum of Months | 0.373614E+10 | 0.144284E+10 | 0.142534E+10 | 0.342867E+10 | 0.191125E+10 |
Maximum of Months | 0.697618E+10 | 0.403172E+10 | 0.426142E+10 | 0.868215E+10 | 0.467018E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.971909E+09 | 0.286598E+09 | 0.685311E+09 | 0.425680E+09 | 0.328213E+10 |
February | 0.157392E+10 | 0.591524E+09 | 0.982398E+09 | 0.112548E+10 | 0.264826E+10 |
March | 0.244177E+10 | 0.824162E+09 | 0.161761E+10 | 0.207833E+10 | 0.247632E+10 |
April | 0.359505E+10 | 0.137453E+10 | 0.222052E+10 | 0.363668E+10 | 0.205002E+10 |
May | 0.478019E+10 | 0.194193E+10 | 0.283826E+10 | 0.526798E+10 | 0.180948E+10 |
June | 0.444894E+10 | 0.172738E+10 | 0.272156E+10 | 0.499555E+10 | 0.140704E+10 |
July | 0.567926E+10 | 0.298531E+10 | 0.269395E+10 | 0.697576E+10 | 0.137448E+10 |
August | 0.469811E+10 | 0.239899E+10 | 0.229912E+10 | 0.586549E+10 | 0.132596E+10 |
September | 0.370248E+10 | 0.177653E+10 | 0.192595E+10 | 0.428513E+10 | 0.169364E+10 |
October | 0.217809E+10 | 0.887468E+09 | 0.129062E+10 | 0.205218E+10 | 0.219191E+10 |
November | 0.104969E+10 | 0.296055E+09 | 0.753631E+09 | 0.601978E+09 | 0.258874E+10 |
December | 0.911880E+09 | 0.312478E+09 | 0.599402E+09 | 0.504116E+09 | 0.335766E+10 |
Annual Sum or Average | 0.360313E+11 | 0.154029E+11 | 0.206283E+11 | 0.378144E+11 | 0.262056E+11 |
Minimum of Months | 0.911880E+09 | 0.286598E+09 | 0.599402E+09 | 0.425680E+09 | 0.132596E+10 |
Maximum of Months | 0.567926E+10 | 0.298531E+10 | 0.283826E+10 | 0.697576E+10 | 0.335766E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.78 | 2345.46 | 321.15 | 0.00 | 321.15 | 0.00 | 0.00 |
February | 62.43 | 2073.44 | 499.71 | 0.00 | 499.71 | 0.00 | 0.00 |
March | 251.38 | 1691.27 | 736.25 | 0.00 | 736.25 | 0.00 | 0.00 |
April | 622.38 | 1322.82 | 1041.87 | 3.70 | 1038.17 | 0.00 | 0.00 |
May | 1065.93 | 1015.57 | 1340.62 | 39.83 | 1300.79 | 0.00 | 0.00 |
June | 1251.17 | 779.37 | 1409.63 | 93.09 | 1316.55 | 0.00 | 0.00 |
July | 1351.61 | 691.70 | 1339.78 | 105.04 | 1234.73 | 0.00 | 0.00 |
August | 1108.00 | 680.65 | 1084.56 | 29.32 | 1055.24 | 0.00 | 0.00 |
September | 628.28 | 1036.57 | 842.45 | 0.25 | 842.20 | 0.00 | 0.00 |
October | 217.69 | 1479.03 | 577.22 | 0.00 | 577.22 | 0.00 | 0.00 |
November | 28.46 | 1955.35 | 363.59 | 0.00 | 363.59 | 0.00 | 0.00 |
December | 0.75 | 2425.27 | 272.89 | 0.00 | 272.89 | 0.00 | 0.00 |
Annual Sum or Average | 552.41 | 1455.01 | 820.72 | 22.77 | 797.95 | 0.00 | 0.00 |
Minimum of Months | 0.75 | 680.65 | 272.89 | 0.00 | 272.89 | 0.00 | 0.00 |
Maximum of Months | 1351.61 | 2425.27 | 1409.63 | 105.04 | 1316.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 106.82 | 1453.03 | 344.03 | 87.22 | 256.81 | 0.00 | 0.00 |
February | 376.29 | 1258.19 | 631.27 | 224.05 | 407.22 | 0.00 | 0.00 |
March | 754.14 | 1036.56 | 942.53 | 341.20 | 601.32 | 0.00 | 0.00 |
April | 1461.88 | 811.68 | 1461.08 | 607.10 | 853.98 | 0.00 | 0.00 |
May | 1648.71 | 670.59 | 1554.71 | 540.54 | 1014.18 | 0.00 | 0.00 |
June | 2136.02 | 519.18 | 1861.95 | 810.15 | 1051.80 | 0.00 | 0.00 |
July | 2083.13 | 444.14 | 1733.90 | 778.28 | 955.63 | 0.00 | 0.00 |
August | 2117.97 | 429.83 | 1704.19 | 852.53 | 851.65 | 0.00 | 0.00 |
September | 1381.54 | 653.44 | 1260.00 | 581.12 | 678.87 | 0.00 | 0.00 |
October | 725.34 | 916.08 | 821.26 | 348.96 | 472.30 | 0.00 | 0.00 |
November | 191.61 | 1195.93 | 402.54 | 113.64 | 288.90 | 0.00 | 0.00 |
December | 137.38 | 1473.92 | 330.17 | 106.29 | 223.88 | 0.00 | 0.00 |
Annual Sum or Average | 1097.11 | 903.52 | 1089.31 | 450.24 | 639.06 | 0.00 | 0.00 |
Minimum of Months | 106.82 | 429.83 | 330.17 | 87.22 | 223.88 | 0.00 | 0.00 |
Maximum of Months | 2136.02 | 1473.92 | 1861.95 | 852.53 | 1051.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1227.31 | 1984.50 | 1418.91 | 842.55 | 576.36 | 0.00 | 0.00 |
February | 2174.42 | 1794.98 | 2182.07 | 1350.73 | 831.34 | 0.00 | 0.00 |
March | 2467.33 | 1578.25 | 2347.28 | 1251.77 | 1095.50 | 0.00 | 0.00 |
April | 2768.98 | 1324.24 | 2478.28 | 1076.05 | 1402.23 | 0.00 | 0.00 |
May | 2573.67 | 1074.99 | 2266.08 | 675.08 | 1590.99 | 0.00 | 0.00 |
June | 2407.15 | 851.71 | 2073.24 | 556.63 | 1516.61 | 0.00 | 0.00 |
July | 2901.73 | 761.31 | 2260.96 | 828.08 | 1432.88 | 0.00 | 0.00 |
August | 3221.32 | 737.34 | 2429.11 | 1132.73 | 1296.38 | 0.00 | 0.00 |
September | 3344.06 | 1036.83 | 2691.35 | 1486.25 | 1205.10 | 0.00 | 0.00 |
October | 2751.87 | 1382.98 | 2437.90 | 1505.22 | 932.68 | 0.00 | 0.00 |
November | 1338.27 | 1700.67 | 1441.37 | 826.02 | 615.35 | 0.00 | 0.00 |
December | 1441.02 | 2077.97 | 1508.08 | 975.94 | 532.15 | 0.00 | 0.00 |
Annual Sum or Average | 2385.62 | 1356.66 | 2126.97 | 1040.33 | 1086.63 | 0.00 | 0.00 |
Minimum of Months | 1227.31 | 737.34 | 1418.91 | 556.63 | 532.15 | 0.00 | 0.00 |
Maximum of Months | 3344.06 | 2077.97 | 2691.35 | 1505.22 | 1590.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 134.00 | 1562.43 | 362.87 | 107.00 | 255.87 | 0.00 | 0.00 |
February | 405.69 | 1419.26 | 650.60 | 244.51 | 406.09 | 0.00 | 0.00 |
March | 700.41 | 1213.18 | 911.66 | 307.71 | 603.95 | 0.00 | 0.00 |
April | 1325.51 | 996.48 | 1386.99 | 530.30 | 856.69 | 0.00 | 0.00 |
May | 1942.10 | 759.69 | 1784.73 | 725.04 | 1059.69 | 0.00 | 0.00 |
June | 1904.63 | 617.81 | 1716.42 | 666.43 | 1049.99 | 0.00 | 0.00 |
July | 2590.04 | 572.02 | 2120.40 | 1114.59 | 1005.81 | 0.00 | 0.00 |
August | 2160.95 | 571.73 | 1754.08 | 895.68 | 858.40 | 0.00 | 0.00 |
September | 1625.53 | 750.81 | 1428.43 | 685.39 | 743.04 | 0.00 | 0.00 |
October | 704.61 | 1060.39 | 813.21 | 331.34 | 481.87 | 0.00 | 0.00 |
November | 184.85 | 1388.57 | 404.97 | 114.22 | 290.75 | 0.00 | 0.00 |
December | 156.70 | 1743.16 | 340.46 | 116.67 | 223.79 | 0.00 | 0.00 |
Annual Sum or Average | 1157.88 | 1052.90 | 1142.55 | 488.43 | 654.12 | 0.00 | 0.00 |
Minimum of Months | 134.00 | 571.73 | 340.46 | 107.00 | 223.79 | 0.00 | 0.00 |
Maximum of Months | 2590.04 | 1743.16 | 2120.40 | 1114.59 | 1059.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.80 | 2008.14 | 321.15 | 0.00 | 321.15 | 0.00 | 0.00 |
February | 97.03 | 1790.63 | 499.72 | 0.00 | 499.72 | 0.00 | 0.00 |
March | 306.88 | 1484.64 | 736.26 | 0.00 | 736.26 | 0.00 | 0.00 |
April | 678.59 | 1188.44 | 1041.89 | 3.70 | 1038.19 | 0.00 | 0.00 |
May | 1093.53 | 960.92 | 1340.65 | 39.83 | 1300.82 | 0.00 | 0.00 |
June | 1271.65 | 740.03 | 1409.66 | 93.09 | 1316.57 | 0.00 | 0.00 |
July | 1372.78 | 663.46 | 1339.80 | 105.05 | 1234.75 | 0.00 | 0.00 |
August | 1132.19 | 648.77 | 1084.58 | 29.32 | 1055.26 | 0.00 | 0.00 |
September | 652.11 | 967.44 | 842.46 | 0.25 | 842.21 | 0.00 | 0.00 |
October | 261.37 | 1304.78 | 577.23 | 0.00 | 577.23 | 0.00 | 0.00 |
November | 48.91 | 1649.01 | 363.60 | 0.00 | 363.60 | 0.00 | 0.00 |
December | 4.90 | 2029.38 | 272.90 | 0.00 | 272.90 | 0.00 | 0.00 |
Annual Sum or Average | 580.58 | 1283.80 | 820.74 | 22.77 | 797.97 | 0.00 | 0.00 |
Minimum of Months | 4.90 | 648.77 | 272.90 | 0.00 | 272.90 | 0.00 | 0.00 |
Maximum of Months | 1372.78 | 2029.38 | 1409.66 | 105.05 | 1316.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 120.66 | 1270.62 | 344.03 | 87.22 | 256.81 | 0.00 | 0.00 |
February | 407.11 | 1127.84 | 631.26 | 224.05 | 407.22 | 0.00 | 0.00 |
March | 779.16 | 946.91 | 942.52 | 341.20 | 601.32 | 0.00 | 0.00 |
April | 1472.17 | 767.73 | 1461.07 | 607.10 | 853.97 | 0.00 | 0.00 |
May | 1650.59 | 645.03 | 1554.71 | 540.54 | 1014.17 | 0.00 | 0.00 |
June | 2125.73 | 508.19 | 1861.94 | 810.14 | 1051.80 | 0.00 | 0.00 |
July | 2072.44 | 444.90 | 1733.90 | 778.27 | 955.62 | 0.00 | 0.00 |
August | 2105.82 | 436.07 | 1704.18 | 852.53 | 851.65 | 0.00 | 0.00 |
September | 1385.58 | 623.86 | 1259.99 | 581.12 | 678.87 | 0.00 | 0.00 |
October | 745.08 | 836.99 | 821.26 | 348.96 | 472.30 | 0.00 | 0.00 |
November | 211.29 | 1052.01 | 402.54 | 113.64 | 288.90 | 0.00 | 0.00 |
December | 152.19 | 1295.78 | 330.17 | 106.29 | 223.88 | 0.00 | 0.00 |
Annual Sum or Average | 1105.88 | 828.22 | 1089.30 | 450.24 | 639.06 | 0.00 | 0.00 |
Minimum of Months | 120.66 | 436.07 | 330.17 | 87.22 | 223.88 | 0.00 | 0.00 |
Maximum of Months | 2125.73 | 1295.78 | 1861.94 | 852.53 | 1051.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1245.70 | 1847.83 | 1418.95 | 842.58 | 576.37 | 0.00 | 0.00 |
February | 2189.12 | 1704.13 | 2182.13 | 1350.77 | 831.36 | 0.00 | 0.00 |
March | 2470.05 | 1504.16 | 2347.35 | 1251.81 | 1095.53 | 0.00 | 0.00 |
April | 2766.52 | 1272.72 | 2478.35 | 1076.09 | 1402.27 | 0.00 | 0.00 |
May | 2560.99 | 1052.50 | 2266.13 | 675.10 | 1591.03 | 0.00 | 0.00 |
June | 2399.16 | 829.20 | 2073.29 | 556.65 | 1516.64 | 0.00 | 0.00 |
July | 2891.74 | 750.83 | 2261.02 | 828.10 | 1432.91 | 0.00 | 0.00 |
August | 3211.47 | 730.00 | 2429.18 | 1132.77 | 1296.41 | 0.00 | 0.00 |
September | 3332.26 | 1019.59 | 2691.43 | 1486.30 | 1205.13 | 0.00 | 0.00 |
October | 2745.94 | 1331.02 | 2437.98 | 1505.27 | 932.71 | 0.00 | 0.00 |
November | 1356.33 | 1585.23 | 1441.41 | 826.05 | 615.36 | 0.00 | 0.00 |
December | 1462.48 | 1916.67 | 1508.13 | 975.97 | 532.16 | 0.00 | 0.00 |
Annual Sum or Average | 2386.75 | 1293.26 | 2127.03 | 1040.37 | 1086.66 | 0.00 | 0.00 |
Minimum of Months | 1245.70 | 730.00 | 1418.95 | 556.65 | 532.16 | 0.00 | 0.00 |
Maximum of Months | 3332.26 | 1916.67 | 2691.43 | 1505.27 | 1591.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 150.87 | 1324.62 | 362.87 | 107.00 | 255.87 | 0.00 | 0.00 |
February | 447.71 | 1184.55 | 650.60 | 244.51 | 406.08 | 0.00 | 0.00 |
March | 752.37 | 1006.53 | 911.65 | 307.71 | 603.94 | 0.00 | 0.00 |
April | 1382.63 | 842.94 | 1386.98 | 530.30 | 856.68 | 0.00 | 0.00 |
May | 1956.48 | 707.08 | 1784.72 | 725.04 | 1059.68 | 0.00 | 0.00 |
June | 1927.22 | 558.60 | 1716.41 | 666.43 | 1049.99 | 0.00 | 0.00 |
July | 2611.26 | 520.94 | 2120.39 | 1114.59 | 1005.81 | 0.00 | 0.00 |
August | 2192.34 | 505.54 | 1754.07 | 895.68 | 858.39 | 0.00 | 0.00 |
September | 1641.95 | 689.57 | 1428.42 | 685.39 | 743.04 | 0.00 | 0.00 |
October | 743.61 | 896.76 | 813.21 | 331.34 | 481.86 | 0.00 | 0.00 |
November | 217.68 | 1099.30 | 404.97 | 114.22 | 290.75 | 0.00 | 0.00 |
December | 180.36 | 1358.16 | 340.46 | 116.67 | 223.79 | 0.00 | 0.00 |
Annual Sum or Average | 1188.56 | 889.83 | 1142.54 | 488.42 | 654.12 | 0.00 | 0.00 |
Minimum of Months | 150.87 | 505.54 | 340.46 | 107.00 | 223.79 | 0.00 | 0.00 |
Maximum of Months | 2611.26 | 1358.16 | 2120.39 | 1114.59 | 1059.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 16.80 | 1853.33 | 321.15 | 0.00 | 321.15 | 0.00 | 0.00 |
February | 118.93 | 1628.43 | 499.72 | 0.00 | 499.72 | 0.00 | 0.00 |
March | 349.97 | 1333.74 | 736.26 | 0.00 | 736.26 | 0.00 | 0.00 |
April | 722.27 | 1093.21 | 1041.89 | 3.70 | 1038.19 | 0.00 | 0.00 |
May | 1123.91 | 907.83 | 1340.65 | 39.83 | 1300.82 | 0.00 | 0.00 |
June | 1280.67 | 716.81 | 1409.66 | 93.09 | 1316.57 | 0.00 | 0.00 |
July | 1371.09 | 650.79 | 1339.80 | 105.05 | 1234.75 | 0.00 | 0.00 |
August | 1136.32 | 630.71 | 1084.58 | 29.32 | 1055.26 | 0.00 | 0.00 |
September | 679.45 | 898.27 | 842.46 | 0.25 | 842.21 | 0.00 | 0.00 |
October | 304.82 | 1157.15 | 577.23 | 0.00 | 577.23 | 0.00 | 0.00 |
November | 68.14 | 1457.67 | 363.60 | 0.00 | 363.60 | 0.00 | 0.00 |
December | 10.84 | 1843.08 | 272.90 | 0.00 | 272.90 | 0.00 | 0.00 |
Annual Sum or Average | 601.57 | 1178.77 | 820.74 | 22.77 | 797.97 | 0.00 | 0.00 |
Minimum of Months | 10.84 | 630.71 | 272.90 | 0.00 | 272.90 | 0.00 | 0.00 |
Maximum of Months | 1371.09 | 1853.33 | 1409.66 | 105.05 | 1316.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 130.83 | 1175.44 | 344.03 | 87.22 | 256.81 | 0.00 | 0.00 |
February | 432.14 | 1029.62 | 631.26 | 224.05 | 407.22 | 0.00 | 0.00 |
March | 810.73 | 860.00 | 942.52 | 341.20 | 601.32 | 0.00 | 0.00 |
April | 1496.14 | 717.46 | 1461.07 | 607.10 | 853.97 | 0.00 | 0.00 |
May | 1663.31 | 616.22 | 1554.71 | 540.54 | 1014.17 | 0.00 | 0.00 |
June | 2124.40 | 497.23 | 1861.94 | 810.14 | 1051.80 | 0.00 | 0.00 |
July | 2067.61 | 440.78 | 1733.90 | 778.27 | 955.62 | 0.00 | 0.00 |
August | 2103.64 | 428.64 | 1704.18 | 852.53 | 851.65 | 0.00 | 0.00 |
September | 1398.70 | 588.22 | 1259.99 | 581.12 | 678.87 | 0.00 | 0.00 |
October | 774.09 | 754.82 | 821.26 | 348.96 | 472.30 | 0.00 | 0.00 |
November | 230.54 | 939.76 | 402.54 | 113.64 | 288.90 | 0.00 | 0.00 |
December | 164.58 | 1181.76 | 330.17 | 106.29 | 223.88 | 0.00 | 0.00 |
Annual Sum or Average | 1119.87 | 767.94 | 1089.30 | 450.24 | 639.06 | 0.00 | 0.00 |
Minimum of Months | 130.83 | 428.64 | 330.17 | 87.22 | 223.88 | 0.00 | 0.00 |
Maximum of Months | 2124.40 | 1181.76 | 1861.94 | 852.53 | 1051.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1280.12 | 1698.96 | 1418.95 | 842.58 | 576.37 | 0.00 | 0.00 |
February | 2237.31 | 1555.31 | 2182.13 | 1350.77 | 831.36 | 0.00 | 0.00 |
March | 2509.38 | 1367.74 | 2347.35 | 1251.81 | 1095.53 | 0.00 | 0.00 |
April | 2797.41 | 1187.62 | 2478.35 | 1076.09 | 1402.27 | 0.00 | 0.00 |
May | 2578.74 | 999.74 | 2266.13 | 675.10 | 1591.03 | 0.00 | 0.00 |
June | 2400.77 | 804.30 | 2073.29 | 556.65 | 1516.64 | 0.00 | 0.00 |
July | 2885.50 | 738.94 | 2261.02 | 828.10 | 1432.91 | 0.00 | 0.00 |
August | 3208.52 | 713.58 | 2429.18 | 1132.77 | 1296.41 | 0.00 | 0.00 |
September | 3349.59 | 962.73 | 2691.43 | 1486.30 | 1205.13 | 0.00 | 0.00 |
October | 2785.29 | 1205.21 | 2437.98 | 1505.27 | 932.71 | 0.00 | 0.00 |
November | 1399.63 | 1416.52 | 1441.41 | 826.05 | 615.36 | 0.00 | 0.00 |
December | 1496.50 | 1743.65 | 1508.13 | 975.97 | 532.16 | 0.00 | 0.00 |
Annual Sum or Average | 2411.32 | 1197.77 | 2127.03 | 1040.37 | 1086.66 | 0.00 | 0.00 |
Minimum of Months | 1280.12 | 713.58 | 1418.95 | 556.65 | 532.16 | 0.00 | 0.00 |
Maximum of Months | 3349.59 | 1743.65 | 2691.43 | 1505.27 | 1591.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 158.93 | 1225.41 | 362.87 | 107.00 | 255.87 | 0.00 | 0.00 |
February | 465.23 | 1094.68 | 650.60 | 244.51 | 406.08 | 0.00 | 0.00 |
March | 775.96 | 924.55 | 911.65 | 307.71 | 603.94 | 0.00 | 0.00 |
April | 1403.04 | 790.90 | 1386.98 | 530.30 | 856.68 | 0.00 | 0.00 |
May | 1966.84 | 675.58 | 1784.72 | 725.04 | 1059.68 | 0.00 | 0.00 |
June | 1927.30 | 542.84 | 1716.41 | 666.43 | 1049.99 | 0.00 | 0.00 |
July | 2604.45 | 513.17 | 2120.39 | 1114.59 | 1005.81 | 0.00 | 0.00 |
August | 2189.92 | 495.06 | 1754.07 | 895.68 | 858.39 | 0.00 | 0.00 |
September | 1653.21 | 653.41 | 1428.42 | 685.39 | 743.04 | 0.00 | 0.00 |
October | 766.20 | 818.37 | 813.21 | 331.34 | 481.86 | 0.00 | 0.00 |
November | 232.24 | 998.74 | 404.97 | 114.22 | 290.75 | 0.00 | 0.00 |
December | 188.22 | 1253.61 | 340.46 | 116.67 | 223.79 | 0.00 | 0.00 |
Annual Sum or Average | 1199.09 | 830.98 | 1142.54 | 488.42 | 654.12 | 0.00 | 0.00 |
Minimum of Months | 158.93 | 495.06 | 340.46 | 107.00 | 223.79 | 0.00 | 0.00 |
Maximum of Months | 2604.45 | 1253.61 | 2120.39 | 1114.59 | 1059.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 10120242.27 | 0.628207E+10 | 0.860158E+09 | 0.00 | 0.860158E+09 | 0.00 | 0.00 |
February | 0.151032E+09 | 0.501606E+10 | 0.120891E+10 | 0.00 | 0.120891E+10 | 0.00 | 0.00 |
March | 0.673291E+09 | 0.452990E+10 | 0.197197E+10 | 0.00 | 0.197197E+10 | 0.00 | 0.00 |
April | 0.161322E+10 | 0.342875E+10 | 0.270052E+10 | 9579460.82 | 0.269094E+10 | 0.00 | 0.00 |
May | 0.285500E+10 | 0.272012E+10 | 0.359072E+10 | 0.106674E+09 | 0.348405E+10 | 0.00 | 0.00 |
June | 0.324303E+10 | 0.202014E+10 | 0.365376E+10 | 0.241276E+09 | 0.341249E+10 | 0.00 | 0.00 |
July | 0.362014E+10 | 0.185264E+10 | 0.358846E+10 | 0.281349E+09 | 0.330711E+10 | 0.00 | 0.00 |
August | 0.296766E+10 | 0.182306E+10 | 0.290489E+10 | 78526790.61 | 0.282636E+10 | 0.00 | 0.00 |
September | 0.162849E+10 | 0.268679E+10 | 0.218362E+10 | 643909.49 | 0.218298E+10 | 0.00 | 0.00 |
October | 0.583060E+09 | 0.396144E+10 | 0.154601E+10 | 0.00 | 0.154601E+10 | 0.00 | 0.00 |
November | 73768903.45 | 0.506828E+10 | 0.942421E+09 | 0.00 | 0.942421E+09 | 0.00 | 0.00 |
December | 2020409.83 | 0.649584E+10 | 0.730913E+09 | 0.00 | 0.730913E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.174208E+11 | 0.458851E+11 | 0.258824E+11 | 0.718049E+09 | 0.251643E+11 | 0.00 | 0.00 |
Minimum of Months | 2020409.83 | 0.182306E+10 | 0.730913E+09 | 0.00 | 0.730913E+09 | 0.00 | 0.00 |
Maximum of Months | 0.362014E+10 | 0.649584E+10 | 0.365376E+10 | 0.281349E+09 | 0.348405E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.286101E+09 | 0.389179E+10 | 0.921457E+09 | 0.233620E+09 | 0.687837E+09 | 0.00 | 0.00 |
February | 0.910324E+09 | 0.304382E+10 | 0.152716E+10 | 0.542021E+09 | 0.985139E+09 | 0.00 | 0.00 |
March | 0.201988E+10 | 0.277633E+10 | 0.252446E+10 | 0.913876E+09 | 0.161058E+10 | 0.00 | 0.00 |
April | 0.378920E+10 | 0.210388E+10 | 0.378711E+10 | 0.157360E+10 | 0.221351E+10 | 0.00 | 0.00 |
May | 0.441592E+10 | 0.179611E+10 | 0.416415E+10 | 0.144778E+10 | 0.271637E+10 | 0.00 | 0.00 |
June | 0.553656E+10 | 0.134571E+10 | 0.482617E+10 | 0.209990E+10 | 0.272627E+10 | 0.00 | 0.00 |
July | 0.557945E+10 | 0.118960E+10 | 0.464409E+10 | 0.208454E+10 | 0.255955E+10 | 0.00 | 0.00 |
August | 0.567277E+10 | 0.115127E+10 | 0.456449E+10 | 0.228342E+10 | 0.228107E+10 | 0.00 | 0.00 |
September | 0.358096E+10 | 0.169371E+10 | 0.326591E+10 | 0.150627E+10 | 0.175964E+10 | 0.00 | 0.00 |
October | 0.194275E+10 | 0.245362E+10 | 0.219967E+10 | 0.934654E+09 | 0.126502E+10 | 0.00 | 0.00 |
November | 0.496647E+09 | 0.309986E+10 | 0.104338E+10 | 0.294556E+09 | 0.748822E+09 | 0.00 | 0.00 |
December | 0.367958E+09 | 0.394774E+10 | 0.884331E+09 | 0.284692E+09 | 0.599639E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.345985E+11 | 0.284934E+11 | 0.343524E+11 | 0.141989E+11 | 0.201535E+11 | 0.00 | 0.00 |
Minimum of Months | 0.286101E+09 | 0.115127E+10 | 0.884331E+09 | 0.233620E+09 | 0.599639E+09 | 0.00 | 0.00 |
Maximum of Months | 0.567277E+10 | 0.394774E+10 | 0.482617E+10 | 0.228342E+10 | 0.272627E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.328723E+10 | 0.531529E+10 | 0.380041E+10 | 0.225670E+10 | 0.154372E+10 | 0.00 | 0.00 |
February | 0.526036E+10 | 0.434241E+10 | 0.527886E+10 | 0.326768E+10 | 0.201118E+10 | 0.00 | 0.00 |
March | 0.660849E+10 | 0.422718E+10 | 0.628695E+10 | 0.335275E+10 | 0.293420E+10 | 0.00 | 0.00 |
April | 0.717721E+10 | 0.343242E+10 | 0.642371E+10 | 0.278913E+10 | 0.363459E+10 | 0.00 | 0.00 |
May | 0.689332E+10 | 0.287925E+10 | 0.606946E+10 | 0.180814E+10 | 0.426132E+10 | 0.00 | 0.00 |
June | 0.623932E+10 | 0.220762E+10 | 0.537384E+10 | 0.144280E+10 | 0.393105E+10 | 0.00 | 0.00 |
July | 0.777199E+10 | 0.203910E+10 | 0.605575E+10 | 0.221792E+10 | 0.383783E+10 | 0.00 | 0.00 |
August | 0.862799E+10 | 0.197488E+10 | 0.650613E+10 | 0.303390E+10 | 0.347223E+10 | 0.00 | 0.00 |
September | 0.866779E+10 | 0.268747E+10 | 0.697598E+10 | 0.385235E+10 | 0.312363E+10 | 0.00 | 0.00 |
October | 0.737062E+10 | 0.370417E+10 | 0.652968E+10 | 0.403159E+10 | 0.249810E+10 | 0.00 | 0.00 |
November | 0.346879E+10 | 0.440813E+10 | 0.373603E+10 | 0.214105E+10 | 0.159498E+10 | 0.00 | 0.00 |
December | 0.385964E+10 | 0.556564E+10 | 0.403925E+10 | 0.261396E+10 | 0.142530E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.752328E+11 | 0.427836E+11 | 0.670761E+11 | 0.328080E+11 | 0.342681E+11 | 0.00 | 0.00 |
Minimum of Months | 0.328723E+10 | 0.197488E+10 | 0.373603E+10 | 0.144280E+10 | 0.142530E+10 | 0.00 | 0.00 |
Maximum of Months | 0.866779E+10 | 0.556564E+10 | 0.697598E+10 | 0.403159E+10 | 0.426132E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.358912E+09 | 0.418480E+10 | 0.971913E+09 | 0.286599E+09 | 0.685314E+09 | 0.00 | 0.00 |
February | 0.981441E+09 | 0.343346E+10 | 0.157393E+10 | 0.591527E+09 | 0.982402E+09 | 0.00 | 0.00 |
March | 0.187598E+10 | 0.324937E+10 | 0.244178E+10 | 0.824165E+09 | 0.161761E+10 | 0.00 | 0.00 |
April | 0.343571E+10 | 0.258287E+10 | 0.359507E+10 | 0.137453E+10 | 0.222053E+10 | 0.00 | 0.00 |
May | 0.520171E+10 | 0.203476E+10 | 0.478021E+10 | 0.194194E+10 | 0.283827E+10 | 0.00 | 0.00 |
June | 0.493680E+10 | 0.160137E+10 | 0.444896E+10 | 0.172738E+10 | 0.272157E+10 | 0.00 | 0.00 |
July | 0.693716E+10 | 0.153209E+10 | 0.567928E+10 | 0.298532E+10 | 0.269396E+10 | 0.00 | 0.00 |
August | 0.578790E+10 | 0.153133E+10 | 0.469813E+10 | 0.239900E+10 | 0.229913E+10 | 0.00 | 0.00 |
September | 0.421337E+10 | 0.194610E+10 | 0.370249E+10 | 0.177654E+10 | 0.192595E+10 | 0.00 | 0.00 |
October | 0.188723E+10 | 0.284016E+10 | 0.217810E+10 | 0.887472E+09 | 0.129063E+10 | 0.00 | 0.00 |
November | 0.479124E+09 | 0.359917E+10 | 0.104969E+10 | 0.296057E+09 | 0.753634E+09 | 0.00 | 0.00 |
December | 0.419707E+09 | 0.466887E+10 | 0.911884E+09 | 0.312479E+09 | 0.599404E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.365150E+11 | 0.332044E+11 | 0.360314E+11 | 0.154030E+11 | 0.206284E+11 | 0.00 | 0.00 |
Minimum of Months | 0.358912E+09 | 0.153133E+10 | 0.911884E+09 | 0.286599E+09 | 0.599404E+09 | 0.00 | 0.00 |
Maximum of Months | 0.693716E+10 | 0.466887E+10 | 0.567928E+10 | 0.298532E+10 | 0.283827E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 28921110.95 | 0.537859E+10 | 0.860177E+09 | 0.00 | 0.860177E+09 | 0.00 | 0.00 |
February | 0.234727E+09 | 0.433189E+10 | 0.120893E+10 | 0.00 | 0.120893E+10 | 0.00 | 0.00 |
March | 0.821937E+09 | 0.397645E+10 | 0.197201E+10 | 0.00 | 0.197201E+10 | 0.00 | 0.00 |
April | 0.175890E+10 | 0.308043E+10 | 0.270057E+10 | 9579746.50 | 0.269099E+10 | 0.00 | 0.00 |
May | 0.292890E+10 | 0.257374E+10 | 0.359079E+10 | 0.106677E+09 | 0.348411E+10 | 0.00 | 0.00 |
June | 0.329611E+10 | 0.191816E+10 | 0.365383E+10 | 0.241284E+09 | 0.341255E+10 | 0.00 | 0.00 |
July | 0.367686E+10 | 0.177701E+10 | 0.358852E+10 | 0.281357E+09 | 0.330717E+10 | 0.00 | 0.00 |
August | 0.303246E+10 | 0.173768E+10 | 0.290494E+10 | 78529132.50 | 0.282641E+10 | 0.00 | 0.00 |
September | 0.169027E+10 | 0.250760E+10 | 0.218366E+10 | 643928.69 | 0.218302E+10 | 0.00 | 0.00 |
October | 0.700067E+09 | 0.349473E+10 | 0.154604E+10 | 0.00 | 0.154604E+10 | 0.00 | 0.00 |
November | 0.126772E+09 | 0.427424E+10 | 0.942441E+09 | 0.00 | 0.942441E+09 | 0.00 | 0.00 |
December | 13134516.42 | 0.543550E+10 | 0.730928E+09 | 0.00 | 0.730928E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.183090E+11 | 0.404860E+11 | 0.258828E+11 | 0.718071E+09 | 0.251648E+11 | 0.00 | 0.00 |
Minimum of Months | 13134516.42 | 0.173768E+10 | 0.730928E+09 | 0.00 | 0.730928E+09 | 0.00 | 0.00 |
Maximum of Months | 0.367686E+10 | 0.543550E+10 | 0.365383E+10 | 0.281357E+09 | 0.348411E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.323176E+09 | 0.340323E+10 | 0.921454E+09 | 0.233619E+09 | 0.687835E+09 | 0.00 | 0.00 |
February | 0.984889E+09 | 0.272848E+10 | 0.152715E+10 | 0.542019E+09 | 0.985135E+09 | 0.00 | 0.00 |
March | 0.208691E+10 | 0.253621E+10 | 0.252445E+10 | 0.913872E+09 | 0.161058E+10 | 0.00 | 0.00 |
April | 0.381585E+10 | 0.198995E+10 | 0.378709E+10 | 0.157359E+10 | 0.221350E+10 | 0.00 | 0.00 |
May | 0.442095E+10 | 0.172764E+10 | 0.416413E+10 | 0.144777E+10 | 0.271636E+10 | 0.00 | 0.00 |
June | 0.550990E+10 | 0.131724E+10 | 0.482615E+10 | 0.209989E+10 | 0.272626E+10 | 0.00 | 0.00 |
July | 0.555082E+10 | 0.119161E+10 | 0.464407E+10 | 0.208453E+10 | 0.255954E+10 | 0.00 | 0.00 |
August | 0.564022E+10 | 0.116797E+10 | 0.456447E+10 | 0.228341E+10 | 0.228106E+10 | 0.00 | 0.00 |
September | 0.359141E+10 | 0.161705E+10 | 0.326590E+10 | 0.150626E+10 | 0.175964E+10 | 0.00 | 0.00 |
October | 0.199562E+10 | 0.224179E+10 | 0.219966E+10 | 0.934650E+09 | 0.126501E+10 | 0.00 | 0.00 |
November | 0.547667E+09 | 0.272681E+10 | 0.104337E+10 | 0.294555E+09 | 0.748819E+09 | 0.00 | 0.00 |
December | 0.407612E+09 | 0.347061E+10 | 0.884328E+09 | 0.284691E+09 | 0.599636E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.348750E+11 | 0.261186E+11 | 0.343522E+11 | 0.141989E+11 | 0.201534E+11 | 0.00 | 0.00 |
Minimum of Months | 0.323176E+09 | 0.116797E+10 | 0.884328E+09 | 0.233619E+09 | 0.599636E+09 | 0.00 | 0.00 |
Maximum of Months | 0.564022E+10 | 0.347061E+10 | 0.482615E+10 | 0.228341E+10 | 0.272626E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.333649E+10 | 0.494922E+10 | 0.380053E+10 | 0.225677E+10 | 0.154376E+10 | 0.00 | 0.00 |
February | 0.529592E+10 | 0.412263E+10 | 0.527902E+10 | 0.326778E+10 | 0.201123E+10 | 0.00 | 0.00 |
March | 0.661579E+10 | 0.402874E+10 | 0.628713E+10 | 0.335286E+10 | 0.293427E+10 | 0.00 | 0.00 |
April | 0.717083E+10 | 0.329889E+10 | 0.642389E+10 | 0.278922E+10 | 0.363467E+10 | 0.00 | 0.00 |
May | 0.685935E+10 | 0.281902E+10 | 0.606962E+10 | 0.180820E+10 | 0.426142E+10 | 0.00 | 0.00 |
June | 0.621864E+10 | 0.214930E+10 | 0.537397E+10 | 0.144284E+10 | 0.393113E+10 | 0.00 | 0.00 |
July | 0.774524E+10 | 0.201102E+10 | 0.605590E+10 | 0.221799E+10 | 0.383791E+10 | 0.00 | 0.00 |
August | 0.860159E+10 | 0.195522E+10 | 0.650631E+10 | 0.303400E+10 | 0.347231E+10 | 0.00 | 0.00 |
September | 0.863721E+10 | 0.264278E+10 | 0.697618E+10 | 0.385248E+10 | 0.312370E+10 | 0.00 | 0.00 |
October | 0.735471E+10 | 0.356500E+10 | 0.652988E+10 | 0.403172E+10 | 0.249816E+10 | 0.00 | 0.00 |
November | 0.351560E+10 | 0.410892E+10 | 0.373614E+10 | 0.214113E+10 | 0.159502E+10 | 0.00 | 0.00 |
December | 0.391710E+10 | 0.513361E+10 | 0.403938E+10 | 0.261404E+10 | 0.142534E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.752685E+11 | 0.407844E+11 | 0.670779E+11 | 0.328090E+11 | 0.342689E+11 | 0.00 | 0.00 |
Minimum of Months | 0.333649E+10 | 0.195522E+10 | 0.373614E+10 | 0.144284E+10 | 0.142534E+10 | 0.00 | 0.00 |
Maximum of Months | 0.863721E+10 | 0.513361E+10 | 0.697618E+10 | 0.403172E+10 | 0.426142E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.404091E+09 | 0.354786E+10 | 0.971909E+09 | 0.286598E+09 | 0.685311E+09 | 0.00 | 0.00 |
February | 0.108311E+10 | 0.286567E+10 | 0.157392E+10 | 0.591524E+09 | 0.982398E+09 | 0.00 | 0.00 |
March | 0.201515E+10 | 0.269588E+10 | 0.244177E+10 | 0.824162E+09 | 0.161761E+10 | 0.00 | 0.00 |
April | 0.358378E+10 | 0.218489E+10 | 0.359505E+10 | 0.137453E+10 | 0.222052E+10 | 0.00 | 0.00 |
May | 0.524024E+10 | 0.189384E+10 | 0.478019E+10 | 0.194193E+10 | 0.283826E+10 | 0.00 | 0.00 |
June | 0.499535E+10 | 0.144788E+10 | 0.444894E+10 | 0.172738E+10 | 0.272156E+10 | 0.00 | 0.00 |
July | 0.699399E+10 | 0.139528E+10 | 0.567926E+10 | 0.298531E+10 | 0.269395E+10 | 0.00 | 0.00 |
August | 0.587195E+10 | 0.135405E+10 | 0.469811E+10 | 0.239899E+10 | 0.229912E+10 | 0.00 | 0.00 |
September | 0.425592E+10 | 0.178737E+10 | 0.370248E+10 | 0.177653E+10 | 0.192595E+10 | 0.00 | 0.00 |
October | 0.199167E+10 | 0.240189E+10 | 0.217809E+10 | 0.887468E+09 | 0.129062E+10 | 0.00 | 0.00 |
November | 0.564230E+09 | 0.284939E+10 | 0.104969E+10 | 0.296055E+09 | 0.753631E+09 | 0.00 | 0.00 |
December | 0.483086E+09 | 0.363771E+10 | 0.911880E+09 | 0.312478E+09 | 0.599402E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.374826E+11 | 0.280617E+11 | 0.360313E+11 | 0.154029E+11 | 0.206283E+11 | 0.00 | 0.00 |
Minimum of Months | 0.404091E+09 | 0.135405E+10 | 0.911880E+09 | 0.286598E+09 | 0.599402E+09 | 0.00 | 0.00 |
Maximum of Months | 0.699399E+10 | 0.363771E+10 | 0.567926E+10 | 0.298531E+10 | 0.283826E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 44994609.57 | 0.496395E+10 | 0.860177E+09 | 0.00 | 0.860177E+09 | 0.00 | 0.00 |
February | 0.287712E+09 | 0.393949E+10 | 0.120893E+10 | 0.00 | 0.120893E+10 | 0.00 | 0.00 |
March | 0.937349E+09 | 0.357228E+10 | 0.197201E+10 | 0.00 | 0.197201E+10 | 0.00 | 0.00 |
April | 0.187212E+10 | 0.283361E+10 | 0.270057E+10 | 9579746.50 | 0.269099E+10 | 0.00 | 0.00 |
May | 0.301029E+10 | 0.243153E+10 | 0.359079E+10 | 0.106677E+09 | 0.348411E+10 | 0.00 | 0.00 |
June | 0.331949E+10 | 0.185797E+10 | 0.365383E+10 | 0.241284E+09 | 0.341255E+10 | 0.00 | 0.00 |
July | 0.367233E+10 | 0.174308E+10 | 0.358852E+10 | 0.281357E+09 | 0.330717E+10 | 0.00 | 0.00 |
August | 0.304353E+10 | 0.168930E+10 | 0.290494E+10 | 78529132.50 | 0.282641E+10 | 0.00 | 0.00 |
September | 0.176113E+10 | 0.232832E+10 | 0.218366E+10 | 643928.69 | 0.218302E+10 | 0.00 | 0.00 |
October | 0.816422E+09 | 0.309932E+10 | 0.154604E+10 | 0.00 | 0.154604E+10 | 0.00 | 0.00 |
November | 0.176618E+09 | 0.377827E+10 | 0.942441E+09 | 0.00 | 0.942441E+09 | 0.00 | 0.00 |
December | 29027036.67 | 0.493651E+10 | 0.730928E+09 | 0.00 | 0.730928E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.189710E+11 | 0.371736E+11 | 0.258828E+11 | 0.718071E+09 | 0.251648E+11 | 0.00 | 0.00 |
Minimum of Months | 29027036.67 | 0.168930E+10 | 0.730928E+09 | 0.00 | 0.730928E+09 | 0.00 | 0.00 |
Maximum of Months | 0.367233E+10 | 0.496395E+10 | 0.365383E+10 | 0.281357E+09 | 0.348411E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.350424E+09 | 0.314830E+10 | 0.921454E+09 | 0.233619E+09 | 0.687835E+09 | 0.00 | 0.00 |
February | 0.104544E+10 | 0.249087E+10 | 0.152715E+10 | 0.542019E+09 | 0.985135E+09 | 0.00 | 0.00 |
March | 0.217145E+10 | 0.230341E+10 | 0.252445E+10 | 0.913872E+09 | 0.161058E+10 | 0.00 | 0.00 |
April | 0.387800E+10 | 0.185965E+10 | 0.378709E+10 | 0.157359E+10 | 0.221350E+10 | 0.00 | 0.00 |
May | 0.445501E+10 | 0.165047E+10 | 0.416413E+10 | 0.144777E+10 | 0.271636E+10 | 0.00 | 0.00 |
June | 0.550644E+10 | 0.128882E+10 | 0.482615E+10 | 0.209989E+10 | 0.272626E+10 | 0.00 | 0.00 |
July | 0.553789E+10 | 0.118059E+10 | 0.464407E+10 | 0.208453E+10 | 0.255954E+10 | 0.00 | 0.00 |
August | 0.563439E+10 | 0.114808E+10 | 0.456447E+10 | 0.228341E+10 | 0.228106E+10 | 0.00 | 0.00 |
September | 0.362544E+10 | 0.152467E+10 | 0.326590E+10 | 0.150626E+10 | 0.175964E+10 | 0.00 | 0.00 |
October | 0.207332E+10 | 0.202170E+10 | 0.219966E+10 | 0.934650E+09 | 0.126501E+10 | 0.00 | 0.00 |
November | 0.597562E+09 | 0.243587E+10 | 0.104337E+10 | 0.294555E+09 | 0.748819E+09 | 0.00 | 0.00 |
December | 0.440799E+09 | 0.316521E+10 | 0.884328E+09 | 0.284691E+09 | 0.599636E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.353162E+11 | 0.242176E+11 | 0.343522E+11 | 0.141989E+11 | 0.201534E+11 | 0.00 | 0.00 |
Minimum of Months | 0.350424E+09 | 0.114808E+10 | 0.884328E+09 | 0.233619E+09 | 0.599636E+09 | 0.00 | 0.00 |
Maximum of Months | 0.563439E+10 | 0.316521E+10 | 0.482615E+10 | 0.228341E+10 | 0.272626E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.342867E+10 | 0.455051E+10 | 0.380053E+10 | 0.225677E+10 | 0.154376E+10 | 0.00 | 0.00 |
February | 0.541250E+10 | 0.376261E+10 | 0.527902E+10 | 0.326778E+10 | 0.201123E+10 | 0.00 | 0.00 |
March | 0.672111E+10 | 0.366336E+10 | 0.628713E+10 | 0.335286E+10 | 0.293427E+10 | 0.00 | 0.00 |
April | 0.725088E+10 | 0.307831E+10 | 0.642389E+10 | 0.278922E+10 | 0.363467E+10 | 0.00 | 0.00 |
May | 0.690689E+10 | 0.267770E+10 | 0.606962E+10 | 0.180820E+10 | 0.426142E+10 | 0.00 | 0.00 |
June | 0.622280E+10 | 0.208474E+10 | 0.537397E+10 | 0.144284E+10 | 0.393113E+10 | 0.00 | 0.00 |
July | 0.772853E+10 | 0.197919E+10 | 0.605590E+10 | 0.221799E+10 | 0.383791E+10 | 0.00 | 0.00 |
August | 0.859371E+10 | 0.191125E+10 | 0.650631E+10 | 0.303400E+10 | 0.347231E+10 | 0.00 | 0.00 |
September | 0.868215E+10 | 0.249539E+10 | 0.697618E+10 | 0.385248E+10 | 0.312370E+10 | 0.00 | 0.00 |
October | 0.746011E+10 | 0.322804E+10 | 0.652988E+10 | 0.403172E+10 | 0.249816E+10 | 0.00 | 0.00 |
November | 0.362783E+10 | 0.367162E+10 | 0.373614E+10 | 0.214113E+10 | 0.159502E+10 | 0.00 | 0.00 |
December | 0.400823E+10 | 0.467018E+10 | 0.403938E+10 | 0.261404E+10 | 0.142534E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.760434E+11 | 0.377729E+11 | 0.670779E+11 | 0.328090E+11 | 0.342689E+11 | 0.00 | 0.00 |
Minimum of Months | 0.342867E+10 | 0.191125E+10 | 0.373614E+10 | 0.144284E+10 | 0.142534E+10 | 0.00 | 0.00 |
Maximum of Months | 0.868215E+10 | 0.467018E+10 | 0.697618E+10 | 0.403172E+10 | 0.426142E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.425680E+09 | 0.328213E+10 | 0.971909E+09 | 0.286598E+09 | 0.685311E+09 | 0.00 | 0.00 |
February | 0.112548E+10 | 0.264826E+10 | 0.157392E+10 | 0.591524E+09 | 0.982398E+09 | 0.00 | 0.00 |
March | 0.207833E+10 | 0.247632E+10 | 0.244177E+10 | 0.824162E+09 | 0.161761E+10 | 0.00 | 0.00 |
April | 0.363668E+10 | 0.205002E+10 | 0.359505E+10 | 0.137453E+10 | 0.222052E+10 | 0.00 | 0.00 |
May | 0.526798E+10 | 0.180948E+10 | 0.478019E+10 | 0.194193E+10 | 0.283826E+10 | 0.00 | 0.00 |
June | 0.499555E+10 | 0.140704E+10 | 0.444894E+10 | 0.172738E+10 | 0.272156E+10 | 0.00 | 0.00 |
July | 0.697576E+10 | 0.137448E+10 | 0.567926E+10 | 0.298531E+10 | 0.269395E+10 | 0.00 | 0.00 |
August | 0.586549E+10 | 0.132596E+10 | 0.469811E+10 | 0.239899E+10 | 0.229912E+10 | 0.00 | 0.00 |
September | 0.428513E+10 | 0.169364E+10 | 0.370248E+10 | 0.177653E+10 | 0.192595E+10 | 0.00 | 0.00 |
October | 0.205218E+10 | 0.219191E+10 | 0.217809E+10 | 0.887468E+09 | 0.129062E+10 | 0.00 | 0.00 |
November | 0.601978E+09 | 0.258874E+10 | 0.104969E+10 | 0.296055E+09 | 0.753631E+09 | 0.00 | 0.00 |
December | 0.504116E+09 | 0.335766E+10 | 0.911880E+09 | 0.312478E+09 | 0.599402E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.378144E+11 | 0.262056E+11 | 0.360313E+11 | 0.154029E+11 | 0.206283E+11 | 0.00 | 0.00 |
Minimum of Months | 0.425680E+09 | 0.132596E+10 | 0.911880E+09 | 0.286598E+09 | 0.599402E+09 | 0.00 | 0.00 |
Maximum of Months | 0.697576E+10 | 0.335766E+10 | 0.567926E+10 | 0.298531E+10 | 0.283826E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.388592E+11 | -0.378304E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102878E+10 | 58.97 | 0.00 | 0.00 |
February | 0.355439E+11 | -0.346158E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -928143121.4 | 58.98 | 0.00 | 0.00 |
March | 0.412859E+11 | -0.402590E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102689E+10 | 58.97 | 0.00 | 0.00 |
April | 0.364890E+11 | -0.354992E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989814563.0 | 58.98 | 0.00 | 0.00 |
May | 0.375194E+11 | -0.364955E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102390E+10 | 58.98 | 0.00 | 0.00 |
June | 0.358040E+11 | -0.348129E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991119384.2 | 58.98 | 0.00 | 0.00 |
July | 0.331999E+11 | -0.321806E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101926E+10 | 58.98 | 0.00 | 0.00 |
August | 0.359562E+11 | -0.349330E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102322E+10 | 58.98 | 0.00 | 0.00 |
September | 0.331059E+11 | -0.321176E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988317085.4 | 58.98 | 0.00 | 0.00 |
October | 0.352115E+11 | -0.341905E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102100E+10 | 58.97 | 0.00 | 0.00 |
November | 0.358811E+11 | -0.348922E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988946424.2 | 58.98 | 0.00 | 0.00 |
December | 0.370382E+11 | -0.360146E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102357E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.435894E+12 | -0.423841E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120530E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.331059E+11 | -0.402590E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102878E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.412859E+11 | -0.321176E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -928143121.4 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-10:09 | 2226.13 | 28.90 | 189.83 | 207.17 | 1854.28 | 33.31 | 225.00 | 169.00 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:39 | 3953.00 | 30.94 | 220.83 | 232.50 | 1685.34 | 28.50 | 208.17 | 205.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:40 | 6700.07 | 32.11 | 206.67 | 301.83 | 1296.30 | 21.26 | 132.00 | 246.17 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:19 | 1727.32 | 17.27 | 0.00 | 333.67 | 933.53 | 20.24 | 182.00 | 285.33 |
May | 427.83 | 0.52 | 0.48 | 01-MAY-07:30 | 1589.20 | 17.10 | 0.00 | 372.17 | 847.23 | 20.03 | 164.83 | 317.00 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-06:30 | 1378.00 | 16.61 | 0.00 | 378.83 | 776.83 | 19.56 | 122.17 | 319.67 |
July | 471.00 | 0.54 | 0.48 | 01-JUL-06:10 | 1224.86 | 15.38 | 0.00 | 371.83 | 702.89 | 18.32 | 122.00 | 305.33 |
August | 366.67 | 0.53 | 0.48 | 01-AUG-06:19 | 1443.59 | 16.44 | 0.00 | 355.00 | 844.94 | 19.42 | 123.00 | 303.50 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:49 | 2385.70 | 19.47 | 27.00 | 308.67 | 1120.35 | 21.04 | 155.67 | 266.83 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:00 | 6177.30 | 33.40 | 216.33 | 274.00 | 1547.87 | 22.52 | 141.67 | 241.17 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:20 | 2534.23 | 29.04 | 199.17 | 213.33 | 2095.72 | 32.94 | 229.33 | 176.83 |
December | 160.33 | 0.51 | 0.48 | 01-DEC-09:39 | 2860.92 | 29.76 | 111.17 | 193.50 | 2659.86 | 36.62 | 149.67 | 143.17 |
Annual Sum or Average | 3714.00 | 0.52 | 2551.55 | 22.10 | 1171.00 | 3542.50 | 1211.57 | 23.06 | 1955.50 | 2979.67 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1224.86 | 15.38 | 0.00 | 193.50 | 702.89 | 18.32 | 122.00 | 143.17 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 6700.07 | 33.40 | 220.83 | 378.83 | 2659.86 | 36.62 | 229.33 | 319.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 01-JAN-10:30 | 697.69 | 16.76 | 43.00 | 179.33 | 458.32 | 21.08 | 69.33 | 95.00 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-08:39 | 1197.82 | 19.21 | 67.00 | 210.33 | 605.45 | 20.66 | 67.83 | 148.17 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-07:40 | 2207.40 | 21.59 | 79.00 | 285.67 | 904.03 | 21.73 | 98.33 | 219.00 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:30 | 2178.66 | 19.26 | 78.83 | 332.83 | 1267.52 | 22.50 | 143.17 | 280.00 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 2361.83 | 19.71 | 109.67 | 375.67 | 1001.69 | 21.69 | 149.17 | 324.33 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:30 | 2388.40 | 18.85 | 69.00 | 386.50 | 1337.24 | 21.89 | 106.17 | 328.17 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:10 | 2320.99 | 18.83 | 118.67 | 384.50 | 1034.98 | 21.17 | 131.17 | 338.33 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:30 | 2731.68 | 20.19 | 96.33 | 357.83 | 1162.66 | 22.28 | 114.00 | 311.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2136.32 | 19.89 | 66.33 | 309.00 | 1236.84 | 22.93 | 97.17 | 253.17 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-07:49 | 2029.76 | 21.14 | 81.00 | 253.17 | 836.62 | 21.39 | 82.17 | 187.83 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-08:20 | 906.76 | 18.34 | 62.17 | 188.83 | 477.33 | 21.13 | 67.67 | 104.17 |
December | 160.33 | 0.55 | 0.48 | 01-DEC-09:39 | 788.28 | 18.12 | 38.17 | 158.83 | 460.33 | 21.78 | 50.33 | 76.33 |
Annual Sum or Average | 3714.00 | 0.52 | 1975.74 | 19.37 | 909.17 | 3422.50 | 964.42 | 21.72 | 1176.50 | 2665.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 697.69 | 16.76 | 38.17 | 158.83 | 458.32 | 20.66 | 50.33 | 76.33 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 2731.68 | 21.59 | 118.67 | 386.50 | 1337.24 | 22.93 | 149.17 | 338.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.59 | 0.48 | 06-JAN-11:30 | 391.37 | 12.38 | 0.00 | 138.50 | 212.59 | 15.31 | 0.00 | 3.17 |
February | 259.50 | 0.55 | 0.48 | 01-FEB-11:20 | 493.60 | 13.55 | 0.00 | 186.50 | 279.10 | 16.58 | 0.00 | 62.33 |
March | 247.00 | 0.53 | 0.48 | 01-MAR-08:00 | 659.48 | 15.06 | 0.00 | 276.17 | 392.63 | 18.13 | 0.00 | 147.50 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:40 | 778.16 | 15.93 | 0.00 | 337.67 | 450.72 | 18.85 | 0.00 | 261.83 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:30 | 950.70 | 16.77 | 1.50 | 388.50 | 550.00 | 20.58 | 55.33 | 337.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:40 | 1009.58 | 18.51 | 35.83 | 403.33 | 576.74 | 20.93 | 64.83 | 361.00 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-05:10 | 854.00 | 17.35 | 44.50 | 412.33 | 491.26 | 19.93 | 60.33 | 341.00 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 724.68 | 15.87 | 0.00 | 371.00 | 461.56 | 18.85 | 2.33 | 299.50 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:00 | 712.81 | 15.87 | 0.00 | 299.33 | 436.33 | 18.93 | 0.00 | 215.17 |
October | 245.33 | 0.55 | 0.48 | 01-OCT-11:39 | 530.90 | 13.95 | 0.00 | 233.50 | 324.82 | 17.12 | 0.00 | 113.17 |
November | 242.67 | 0.58 | 0.48 | 01-NOV-11:50 | 422.20 | 12.75 | 0.00 | 157.67 | 229.02 | 15.62 | 0.00 | 14.50 |
December | 160.33 | 0.61 | 0.48 | 01-DEC-10:20 | 358.32 | 12.13 | 0.00 | 105.17 | 211.70 | 15.41 | 0.00 | 2.50 |
Annual Sum or Average | 3714.00 | 0.53 | 710.19 | 15.50 | 81.83 | 3309.67 | 415.71 | 18.49 | 182.83 | 2158.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 358.32 | 12.13 | 0.00 | 105.17 | 211.70 | 15.31 | 0.00 | 2.50 | |
Maximum of Months | 471.00 | 0.61 | 0.48 | 1009.58 | 18.51 | 44.50 | 412.33 | 576.74 | 20.93 | 64.83 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 01-JAN-13:30 | 829.49 | 18.48 | 63.33 | 181.83 | 430.34 | 19.82 | 50.33 | 92.67 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-11:09 | 1087.78 | 17.58 | 42.17 | 212.50 | 597.11 | 20.81 | 70.67 | 149.83 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-08:00 | 1842.11 | 19.91 | 58.83 | 287.50 | 1018.53 | 23.13 | 109.83 | 218.33 |
April | 379.50 | 0.52 | 0.48 | 01-APR-08:09 | 2307.25 | 20.54 | 105.17 | 328.83 | 982.23 | 21.17 | 130.50 | 281.83 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-08:39 | 2305.45 | 17.74 | 52.17 | 378.67 | 1258.48 | 19.37 | 86.83 | 324.67 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-06:40 | 2428.77 | 17.26 | 42.83 | 383.83 | 1063.43 | 19.09 | 73.67 | 338.83 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-09:00 | 2676.06 | 16.48 | 58.83 | 382.83 | 1142.94 | 17.99 | 75.67 | 333.33 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-07:40 | 2414.46 | 18.85 | 72.83 | 362.67 | 1451.77 | 21.15 | 94.00 | 313.50 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-08:20 | 2642.79 | 20.72 | 78.67 | 299.50 | 1555.91 | 23.85 | 119.50 | 244.00 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-11:39 | 1800.25 | 19.79 | 66.50 | 253.67 | 811.73 | 21.78 | 89.83 | 187.17 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-10:30 | 885.01 | 18.30 | 59.67 | 190.83 | 451.64 | 19.77 | 48.50 | 103.00 |
December | 160.33 | 0.55 | 0.48 | 01-DEC-10:09 | 786.44 | 17.39 | 31.67 | 161.83 | 463.79 | 20.89 | 43.50 | 71.33 |
Annual Sum or Average | 3714.00 | 0.52 | 2001.04 | 18.51 | 732.67 | 3424.50 | 1007.36 | 20.52 | 992.83 | 2658.50 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 786.44 | 16.48 | 31.67 | 161.83 | 430.34 | 17.99 | 43.50 | 71.33 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 2676.06 | 20.72 | 105.17 | 383.83 | 1555.91 | 23.85 | 130.50 | 338.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-10:09 | 1988.20 | 22.14 | 139.00 | 205.00 | 1854.38 | 31.35 | 207.33 | 167.33 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:39 | 3908.89 | 30.09 | 216.17 | 231.50 | 1722.13 | 26.85 | 154.83 | 208.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:40 | 6655.04 | 31.05 | 206.17 | 300.67 | 1339.09 | 16.62 | 7.50 | 248.50 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:19 | 1690.11 | 11.09 | 0.00 | 331.33 | 964.07 | 15.84 | 0.00 | 288.00 |
May | 427.83 | 0.52 | 0.48 | 01-MAY-07:19 | 1553.90 | 11.06 | 0.00 | 369.83 | 873.68 | 15.74 | 0.00 | 321.17 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-06:19 | 1354.29 | 10.97 | 0.00 | 375.33 | 802.40 | 15.65 | 0.00 | 322.33 |
July | 471.00 | 0.54 | 0.48 | 01-JUL-06:10 | 1207.57 | 9.56 | 0.00 | 369.67 | 728.43 | 14.23 | 0.00 | 309.17 |
August | 366.67 | 0.53 | 0.48 | 01-AUG-06:19 | 1425.71 | 10.63 | 0.00 | 352.17 | 877.50 | 15.47 | 0.00 | 305.50 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 2348.86 | 13.89 | 26.83 | 307.33 | 1160.42 | 16.76 | 0.00 | 268.67 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:00 | 6119.07 | 32.59 | 216.33 | 271.00 | 1588.64 | 18.07 | 26.17 | 242.67 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:20 | 2484.08 | 27.36 | 188.83 | 212.00 | 2116.02 | 32.47 | 225.00 | 177.83 |
December | 160.33 | 0.51 | 0.48 | 01-DEC-09:39 | 2330.70 | 20.55 | 72.00 | 190.83 | 2685.48 | 36.02 | 149.67 | 144.67 |
Annual Sum or Average | 3714.00 | 0.52 | 2483.02 | 17.31 | 1065.33 | 3516.67 | 1240.58 | 19.56 | 770.50 | 3004.50 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1207.57 | 9.56 | 0.00 | 190.83 | 728.43 | 14.23 | 0.00 | 144.67 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 6655.04 | 32.59 | 216.33 | 375.33 | 2685.48 | 36.02 | 225.00 | 322.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 01-JAN-10:20 | 690.77 | 13.53 | 42.17 | 177.33 | 467.63 | 19.19 | 63.00 | 98.83 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-08:39 | 1191.20 | 16.33 | 65.00 | 209.33 | 620.28 | 18.41 | 42.50 | 152.00 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-07:40 | 2056.37 | 16.70 | 58.50 | 285.33 | 928.68 | 19.40 | 37.67 | 222.33 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:30 | 2177.24 | 16.01 | 78.33 | 331.83 | 1294.65 | 20.22 | 78.17 | 282.50 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 2356.33 | 16.66 | 108.17 | 374.67 | 1029.13 | 19.24 | 73.33 | 327.17 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:30 | 2379.33 | 15.49 | 69.00 | 385.67 | 1371.57 | 19.41 | 62.67 | 332.17 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:10 | 2320.24 | 15.78 | 118.67 | 383.67 | 1051.49 | 18.58 | 84.67 | 343.67 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:40 | 2735.35 | 17.20 | 96.33 | 356.50 | 1135.82 | 18.37 | 48.67 | 313.67 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2127.43 | 16.66 | 64.17 | 308.17 | 1264.23 | 20.76 | 57.00 | 258.00 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-07:49 | 1853.52 | 16.54 | 62.83 | 252.33 | 851.73 | 18.99 | 38.00 | 192.83 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-08:20 | 900.51 | 15.43 | 60.33 | 187.83 | 468.96 | 17.63 | 42.33 | 106.67 |
December | 160.33 | 0.55 | 0.48 | 01-DEC-09:39 | 781.78 | 15.22 | 38.17 | 157.67 | 470.90 | 20.06 | 38.83 | 79.67 |
Annual Sum or Average | 3714.00 | 0.52 | 1950.31 | 16.05 | 861.67 | 3410.33 | 979.67 | 19.18 | 666.83 | 2709.50 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 690.77 | 13.53 | 38.17 | 157.67 | 467.63 | 17.63 | 37.67 | 79.67 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 2735.35 | 17.20 | 118.67 | 385.67 | 1371.57 | 20.76 | 84.67 | 343.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.59 | 0.48 | 06-JAN-11:09 | 381.45 | 6.04 | 0.00 | 133.17 | 217.88 | 10.83 | 0.00 | 4.67 |
February | 259.50 | 0.55 | 0.48 | 01-FEB-11:09 | 482.16 | 7.58 | 0.00 | 183.50 | 286.38 | 12.44 | 0.00 | 72.00 |
March | 247.00 | 0.53 | 0.48 | 01-MAR-08:50 | 646.38 | 9.68 | 0.00 | 273.33 | 403.42 | 14.53 | 0.00 | 154.67 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:30 | 763.30 | 10.59 | 0.00 | 335.50 | 463.63 | 15.33 | 0.00 | 266.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:30 | 947.38 | 11.19 | 1.50 | 387.83 | 566.86 | 17.18 | 27.33 | 342.00 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:40 | 994.66 | 13.76 | 35.17 | 402.33 | 616.47 | 19.59 | 60.33 | 368.50 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-05:19 | 846.69 | 12.34 | 44.33 | 412.00 | 528.80 | 16.89 | 45.00 | 353.50 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 733.47 | 10.81 | 0.00 | 373.33 | 475.95 | 15.75 | 0.00 | 307.50 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:00 | 699.20 | 10.96 | 0.00 | 297.50 | 448.57 | 15.80 | 0.00 | 219.33 |
October | 245.33 | 0.55 | 0.48 | 01-OCT-09:20 | 519.79 | 8.65 | 0.00 | 230.17 | 333.42 | 13.54 | 0.00 | 120.67 |
November | 242.67 | 0.58 | 0.48 | 01-NOV-11:50 | 411.79 | 6.43 | 0.00 | 153.17 | 234.90 | 11.17 | 0.00 | 17.33 |
December | 160.33 | 0.61 | 0.48 | 01-DEC-10:20 | 348.73 | 6.19 | 0.00 | 98.00 | 216.39 | 11.25 | 0.00 | 4.33 |
Annual Sum or Average | 3714.00 | 0.53 | 701.49 | 10.10 | 81.00 | 3279.83 | 432.87 | 15.14 | 132.67 | 2230.50 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 348.73 | 6.04 | 0.00 | 98.00 | 216.39 | 10.83 | 0.00 | 4.33 | |
Maximum of Months | 471.00 | 0.61 | 0.48 | 994.66 | 13.76 | 44.33 | 412.00 | 616.47 | 19.59 | 60.33 | 368.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 01-JAN-13:30 | 823.42 | 15.69 | 62.00 | 180.83 | 440.35 | 17.62 | 40.83 | 96.83 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-11:09 | 1082.34 | 14.27 | 42.17 | 211.00 | 612.37 | 18.59 | 41.83 | 154.33 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-08:50 | 1835.24 | 16.89 | 58.83 | 286.33 | 1041.79 | 21.13 | 57.00 | 221.33 |
April | 379.50 | 0.52 | 0.48 | 01-APR-08:09 | 2304.59 | 17.66 | 104.00 | 328.50 | 970.91 | 18.60 | 50.17 | 284.17 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-08:30 | 2295.89 | 13.91 | 50.83 | 378.33 | 1288.68 | 16.13 | 0.00 | 328.67 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-06:30 | 2419.03 | 13.55 | 42.83 | 382.83 | 1094.29 | 15.96 | 0.00 | 341.67 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-09:00 | 2675.71 | 12.67 | 58.83 | 382.33 | 1134.63 | 14.70 | 3.67 | 334.00 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-07:40 | 2418.13 | 15.50 | 72.83 | 361.17 | 1486.29 | 18.51 | 50.17 | 318.00 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-08:20 | 2647.31 | 17.70 | 78.67 | 299.17 | 1588.36 | 21.69 | 69.67 | 247.00 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-09:20 | 1771.81 | 16.64 | 63.50 | 253.00 | 833.52 | 19.62 | 43.67 | 191.83 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-10:30 | 801.17 | 13.35 | 39.67 | 188.17 | 462.56 | 17.48 | 40.00 | 106.67 |
December | 160.33 | 0.55 | 0.48 | 01-DEC-10:09 | 780.20 | 14.32 | 31.67 | 160.17 | 474.32 | 19.00 | 31.67 | 73.50 |
Annual Sum or Average | 3714.00 | 0.52 | 1990.52 | 15.06 | 705.83 | 3411.83 | 1023.65 | 17.91 | 428.67 | 2698.00 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 780.20 | 12.67 | 31.67 | 160.17 | 440.35 | 14.70 | 0.00 | 73.50 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 2675.71 | 17.70 | 104.00 | 382.83 | 1588.36 | 21.69 | 69.67 | 341.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-10:09 | 1987.46 | 22.12 | 139.00 | 204.83 | 1855.13 | 31.34 | 207.33 | 167.33 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:39 | 3908.28 | 30.07 | 216.17 | 231.50 | 1723.30 | 26.84 | 154.83 | 209.00 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:40 | 6655.12 | 31.04 | 206.17 | 300.67 | 1340.59 | 16.61 | 7.50 | 249.00 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:19 | 1691.03 | 11.05 | 0.00 | 331.33 | 965.31 | 15.82 | 0.00 | 288.17 |
May | 427.83 | 0.52 | 0.48 | 01-MAY-07:19 | 1554.90 | 11.02 | 0.00 | 369.83 | 874.82 | 15.72 | 0.00 | 321.50 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-06:19 | 1354.93 | 10.93 | 0.00 | 375.33 | 803.28 | 15.63 | 0.00 | 322.33 |
July | 471.00 | 0.54 | 0.48 | 01-JUL-06:10 | 1208.16 | 9.52 | 0.00 | 369.67 | 729.21 | 14.21 | 0.00 | 309.17 |
August | 366.67 | 0.53 | 0.48 | 01-AUG-06:19 | 1426.27 | 10.59 | 0.00 | 352.00 | 878.40 | 15.45 | 0.00 | 305.50 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 2349.28 | 13.85 | 26.83 | 307.33 | 1161.73 | 16.74 | 0.00 | 268.83 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:00 | 6094.65 | 32.25 | 213.17 | 271.00 | 1589.96 | 18.06 | 26.17 | 242.67 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:20 | 2406.18 | 25.32 | 170.50 | 210.67 | 2116.93 | 32.46 | 225.00 | 178.17 |
December | 160.33 | 0.51 | 0.48 | 01-DEC-09:39 | 2329.18 | 20.52 | 72.00 | 191.00 | 2686.09 | 36.02 | 149.67 | 145.00 |
Annual Sum or Average | 3714.00 | 0.52 | 2476.60 | 17.13 | 1043.83 | 3515.17 | 1241.62 | 19.55 | 770.50 | 3006.67 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1208.16 | 9.52 | 0.00 | 191.00 | 729.21 | 14.21 | 0.00 | 145.00 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 6655.12 | 32.25 | 216.17 | 375.33 | 2686.09 | 36.02 | 225.00 | 322.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 01-JAN-10:20 | 690.74 | 13.49 | 42.17 | 177.33 | 468.08 | 19.17 | 63.00 | 98.83 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-08:39 | 1191.11 | 16.30 | 64.83 | 209.33 | 620.85 | 18.40 | 42.33 | 152.00 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-07:40 | 2056.15 | 16.67 | 58.50 | 285.33 | 929.46 | 19.38 | 37.67 | 222.33 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:30 | 2177.21 | 15.97 | 78.33 | 331.83 | 1295.53 | 20.21 | 78.17 | 282.67 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 2356.66 | 16.62 | 108.17 | 374.50 | 1030.09 | 19.23 | 73.33 | 327.33 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:30 | 2379.28 | 15.45 | 69.00 | 385.50 | 1372.48 | 19.40 | 62.67 | 332.33 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:10 | 2320.30 | 15.74 | 118.67 | 383.83 | 1052.20 | 18.57 | 84.67 | 343.83 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:40 | 2735.08 | 17.16 | 96.33 | 356.50 | 1136.54 | 18.36 | 48.67 | 313.83 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2127.00 | 16.62 | 64.17 | 308.17 | 1264.93 | 20.74 | 57.00 | 258.17 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-07:49 | 1853.16 | 16.50 | 62.83 | 252.17 | 852.32 | 18.97 | 38.00 | 193.00 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-08:20 | 900.49 | 15.39 | 60.17 | 187.83 | 469.45 | 17.61 | 42.33 | 107.00 |
December | 160.33 | 0.55 | 0.48 | 01-DEC-09:39 | 781.51 | 15.18 | 38.17 | 157.50 | 471.28 | 20.05 | 38.83 | 79.67 |
Annual Sum or Average | 3714.00 | 0.52 | 1950.23 | 16.01 | 861.33 | 3409.83 | 980.38 | 19.16 | 666.67 | 2711.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 690.74 | 13.49 | 38.17 | 157.50 | 468.08 | 17.61 | 37.67 | 79.67 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 2735.08 | 17.16 | 118.67 | 385.50 | 1372.48 | 20.74 | 84.67 | 343.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.59 | 0.48 | 06-JAN-11:09 | 381.55 | 6.00 | 0.00 | 132.83 | 218.16 | 10.82 | 0.00 | 4.83 |
February | 259.50 | 0.55 | 0.48 | 01-FEB-11:09 | 482.23 | 7.54 | 0.00 | 183.50 | 286.71 | 12.42 | 0.00 | 72.50 |
March | 247.00 | 0.53 | 0.48 | 01-MAR-08:50 | 646.35 | 9.64 | 0.00 | 273.33 | 403.81 | 14.51 | 0.00 | 155.00 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:30 | 763.37 | 10.55 | 0.00 | 335.50 | 464.11 | 15.31 | 0.00 | 266.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:19 | 947.56 | 11.15 | 1.50 | 387.83 | 567.47 | 17.17 | 27.33 | 342.33 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:40 | 994.63 | 13.72 | 35.17 | 402.33 | 617.00 | 19.57 | 60.17 | 368.67 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-05:19 | 846.71 | 12.30 | 44.33 | 412.17 | 529.26 | 16.87 | 45.00 | 353.67 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 733.36 | 10.77 | 0.00 | 373.33 | 476.33 | 15.73 | 0.00 | 307.83 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:00 | 699.09 | 10.92 | 0.00 | 297.33 | 448.95 | 15.79 | 0.00 | 219.83 |
October | 245.33 | 0.55 | 0.48 | 01-OCT-09:20 | 519.69 | 8.61 | 0.00 | 230.17 | 333.71 | 13.52 | 0.00 | 120.83 |
November | 242.67 | 0.58 | 0.48 | 01-NOV-11:50 | 411.92 | 6.39 | 0.00 | 153.33 | 235.20 | 11.16 | 0.00 | 17.33 |
December | 160.33 | 0.61 | 0.48 | 01-DEC-10:20 | 348.66 | 6.15 | 0.00 | 98.17 | 216.60 | 11.23 | 0.00 | 4.33 |
Annual Sum or Average | 3714.00 | 0.53 | 701.50 | 10.06 | 81.00 | 3279.83 | 433.29 | 15.12 | 132.50 | 2233.33 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 348.66 | 6.00 | 0.00 | 98.17 | 216.60 | 10.82 | 0.00 | 4.33 | |
Maximum of Months | 471.00 | 0.61 | 0.48 | 994.63 | 13.72 | 44.33 | 412.17 | 617.00 | 19.57 | 60.17 | 368.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 01-JAN-13:30 | 823.39 | 15.66 | 61.83 | 180.83 | 440.79 | 17.60 | 40.83 | 97.33 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-11:09 | 1082.24 | 14.23 | 42.17 | 211.00 | 612.94 | 18.58 | 41.83 | 154.67 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-08:50 | 1835.01 | 16.85 | 58.83 | 286.33 | 1042.58 | 21.11 | 57.00 | 221.50 |
April | 379.50 | 0.52 | 0.48 | 01-APR-08:09 | 2304.55 | 17.62 | 104.00 | 328.50 | 971.80 | 18.59 | 50.17 | 284.17 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-08:30 | 2296.10 | 13.87 | 50.83 | 378.33 | 1289.71 | 16.11 | 0.00 | 329.00 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-06:30 | 2419.03 | 13.51 | 42.83 | 382.83 | 1095.20 | 15.94 | 0.00 | 341.83 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-09:00 | 2675.72 | 12.63 | 58.83 | 382.17 | 1135.41 | 14.68 | 3.67 | 334.00 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-07:40 | 2417.84 | 15.46 | 72.83 | 361.17 | 1487.00 | 18.49 | 50.17 | 318.00 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-08:20 | 2646.83 | 17.66 | 78.67 | 299.17 | 1589.22 | 21.67 | 69.67 | 247.00 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-09:20 | 1771.40 | 16.60 | 63.50 | 253.17 | 834.13 | 19.60 | 43.67 | 192.00 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-10:30 | 801.16 | 13.31 | 39.67 | 188.17 | 463.04 | 17.47 | 40.00 | 106.83 |
December | 160.33 | 0.55 | 0.48 | 01-DEC-10:09 | 779.92 | 14.27 | 31.67 | 160.17 | 474.69 | 18.99 | 31.67 | 73.50 |
Annual Sum or Average | 3714.00 | 0.52 | 1990.41 | 15.02 | 705.67 | 3411.83 | 1024.40 | 17.89 | 428.67 | 2699.83 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 779.92 | 12.63 | 31.67 | 160.17 | 440.79 | 14.68 | 0.00 | 73.50 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 2675.72 | 17.66 | 104.00 | 382.83 | 1589.22 | 21.67 | 69.67 | 341.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.711354E+10 | 25020.44 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.416242E+10 | 20594.62 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.667740E+09 | 15858.43 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155287E+09 | 9553.54 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29527767.96 | 4527.23 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31724102.16 | 2372.06 | 24-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137857E+10 | 13105.12 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358614E+10 | 18787.49 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.711354E+10 | 25020.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 28881064.66 | 1151.27 | 09-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 977261.48 | 234.46 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29858326.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28881064.66 | 1151.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111235E+09 | 3357.23 | 17-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23722458.72 | 1871.69 | 14-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18068725.00 | 951.16 | 22-DEC-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111235E+09 | 3357.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.291766E+09 | 13782.16 | 09-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 74859491.29 | 13792.12 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1302368.67 | 1381.70 | 06-MAR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8021543.77 | 2423.58 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 74341100.32 | 13854.76 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.450291E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.291766E+09 | 13854.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 127653.47 | 120.32 | 17-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127653.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 127653.47 | 120.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.126668E+12 | 280829.90 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.762854E+11 | 234952.06 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.245500E+11 | 185718.13 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.869201E+10 | 134651.95 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104360E+10 | 61335.19 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37914359.75 | 9793.66 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.285544E+10 | 65552.04 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.466179E+11 | 182749.00 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.968711E+11 | 246004.99 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.383621E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126668E+12 | 280829.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.667859E+10 | 408952.74 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143742E+09 | 32490.68 | 21-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.362777E+09 | 409861.42 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.718511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.667859E+10 | 409861.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.267675E+11 | 100764.70 | 02-JAN-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121687E+11 | 100221.85 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.248042E+10 | 100115.87 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.366300E+09 | 39611.11 | 19-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.681981E+09 | 92325.32 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.656930E+10 | 100459.62 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187683E+11 | 100604.30 | 26-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.678025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.267675E+11 | 100764.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.231260E+11 | 132833.77 | 07-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105332E+11 | 132550.39 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.229823E+10 | 129575.90 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.374263E+09 | 36487.51 | 19-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17939348.43 | 6013.40 | 18-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3694721.02 | 2392.33 | 27-SEP-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110109E+10 | 58851.59 | 31-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.740602E+10 | 131410.27 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174571E+11 | 132662.06 | 26-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.623176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.231260E+11 | 132833.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.209740E+11 | 191364.93 | 07-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.811292E+10 | 190954.01 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155442E+10 | 186688.34 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.417822E+09 | 21438.93 | 19-APR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8396272.33 | 2764.03 | 18-MAY-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.626033E+09 | 41116.20 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.572188E+10 | 189323.54 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156219E+11 | 191121.63 | 26-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.530374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.209740E+11 | 191364.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.159575E+11 | 127017.81 | 07-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.653260E+10 | 126749.85 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116604E+10 | 123883.32 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183338E+09 | 14580.75 | 18-APR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 844688.67 | 787.52 | 18-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.439032E+09 | 16855.90 | 31-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.417544E+10 | 125645.92 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107403E+11 | 126744.19 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159575E+11 | 127017.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.145397E+11 | 30918.59 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.945345E+10 | 27436.11 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.428927E+10 | 22726.85 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163400E+10 | 17690.54 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.317229E+09 | 9636.32 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 469884.21 | 592.82 | 15-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 46613552.94 | 4369.77 | 27-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.875820E+09 | 10353.53 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.645778E+10 | 21879.38 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122054E+11 | 27718.93 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.498197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.145397E+11 | 30918.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.757988E+10 | 70301.90 | 23-JAN-05:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.369641E+10 | 70304.01 | 06-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.859183E+09 | 70033.13 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 60706906.08 | 13860.84 | 18-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.342131E+09 | 69465.26 | 16-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.266363E+10 | 70340.26 | 13-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.552306E+10 | 70284.39 | 11-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.757988E+10 | 70340.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.634236E+10 | 11415.72 | 30-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.408922E+10 | 11428.09 | 23-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198598E+10 | 11397.09 | 06-MAR-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.611234E+09 | 11336.23 | 07-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69932489.97 | 11254.52 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1445235.45 | 412.93 | 14-JUN-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 60018188.30 | 11351.27 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.103201E+10 | 11396.13 | 16-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.314350E+10 | 11423.09 | 27-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.559602E+10 | 11415.54 | 01-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.634236E+10 | 11428.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.452313E+10 | 15517.35 | 07-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.268099E+10 | 15489.66 | 18-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125503E+10 | 15172.55 | 25-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.348399E+09 | 15170.65 | 18-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74254934.64 | 15107.19 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7182952.24 | 1395.30 | 14-JUN-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 60594865.82 | 10362.91 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.758189E+09 | 15108.88 | 17-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.237000E+10 | 15381.10 | 13-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.400019E+10 | 15467.97 | 26-DEC-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.452313E+10 | 15517.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.516328E+10 | 23170.73 | 07-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285746E+10 | 23129.30 | 18-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149053E+10 | 22614.74 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.563243E+09 | 22653.39 | 18-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116816E+09 | 22558.80 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13434076.05 | 1797.63 | 14-JUN-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 66951548.93 | 11213.28 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.788001E+09 | 22494.85 | 27-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.272109E+10 | 22934.81 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.454458E+10 | 23097.16 | 26-DEC-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.516328E+10 | 23170.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.362704E+10 | 15860.03 | 07-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202883E+10 | 15786.29 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.981331E+09 | 15475.85 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.298600E+09 | 13245.76 | 12-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 53198589.72 | 12592.62 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 577511.97 | 204.32 | 14-JUN-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30052671.95 | 1856.93 | 27-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.539067E+09 | 13853.63 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.175998E+10 | 15696.16 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.296557E+10 | 15796.11 | 26-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.362704E+10 | 15860.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 483.95 | 483.95 | 0.78 | 02-JAN-06:01 | 0.78 | 0.00 |
February | 0.00 | 0.00 | 0.673873E+09 | 0.673873E+09 | 45625.84 | 27-FEB-15:00 | 45625.84 | 0.00 |
March | 0.00 | 0.00 | 0.878860E+09 | 0.878860E+09 | 24564.14 | 18-MAR-14:10 | 24564.14 | 0.01 |
April | 0.00 | 0.00 | 0.873833E+10 | 0.873833E+10 | 105460.50 | 27-APR-14:30 | 105460.50 | 0.04 |
May | 0.00 | 0.00 | 0.141854E+11 | 0.141838E+11 | 84821.97 | 04-MAY-15:00 | 84821.97 | 0.13 |
June | 0.00 | 0.00 | 0.279831E+11 | 0.279790E+11 | 95890.01 | 28-JUN-15:20 | 95890.01 | 0.23 |
July | 0.00 | 0.00 | 0.515590E+11 | 0.506451E+11 | 127565.89 | 31-JUL-16:00 | 109713.61 | 0.48 |
August | 0.00 | 0.00 | 0.716939E+11 | 0.689923E+11 | 135330.90 | 29-AUG-14:30 | 116887.05 | 0.65 |
September | 0.00 | 0.00 | 0.219998E+11 | 0.216224E+11 | 95648.39 | 14-SEP-13:10 | 74649.78 | 0.31 |
October | 0.00 | 0.00 | 0.397142E+10 | 0.397142E+10 | 66232.51 | 04-OCT-15:00 | 66232.51 | 0.02 |
November | 0.00 | 0.00 | 0.566748E+09 | 0.566748E+09 | 31427.71 | 04-NOV-14:00 | 31427.71 | 0.01 |
December | 0.00 | 0.00 | 361.45 | 361.45 | 0.78 | 26-DEC-06:05 | 0.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.202250E+12 | 0.198252E+12 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 361.45 | 361.45 | 0.78 | 0.78 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.716939E+11 | 0.689923E+11 | 135330.90 | 116887.05 | 0.65 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 53644.70 | 53644.70 | 3.70 | 02-JAN-06:13 | 3.70 | 0.01 |
February | 0.00 | 0.00 | 0.387504E+10 | 0.387504E+10 | 264204.59 | 27-FEB-15:00 | 264204.59 | 0.01 |
March | 0.00 | 0.00 | 0.582521E+10 | 0.582521E+10 | 220904.45 | 18-MAR-14:00 | 220904.45 | 0.01 |
April | 0.00 | 0.00 | 0.632318E+11 | 0.632318E+11 | 859974.23 | 27-APR-14:50 | 859974.23 | 0.04 |
May | 0.00 | 0.00 | 0.120778E+12 | 0.120753E+12 | 773730.69 | 04-MAY-15:00 | 773730.69 | 0.13 |
June | 0.00 | 0.00 | 0.224631E+12 | 0.224602E+12 | 842520.92 | 28-JUN-15:30 | 842520.92 | 0.22 |
July | 0.00 | 0.00 | 0.400717E+12 | 0.395317E+12 | 1090402.33 | 31-JUL-16:00 | 923342.86 | 0.42 |
August | 0.00 | 0.00 | 0.537500E+12 | 0.519233E+12 | 1162224.11 | 29-AUG-14:30 | 997241.78 | 0.52 |
September | 0.00 | 0.00 | 0.192594E+12 | 0.188423E+12 | 911383.17 | 14-SEP-13:00 | 663363.90 | 0.30 |
October | 0.00 | 0.00 | 0.300181E+11 | 0.300181E+11 | 556802.52 | 04-OCT-15:00 | 556802.52 | 0.02 |
November | 0.00 | 0.00 | 0.482927E+10 | 0.482927E+10 | 276327.01 | 04-NOV-14:00 | 276327.01 | 0.02 |
December | 0.00 | 0.00 | 47343.63 | 47343.63 | 3.47 | 26-DEC-06:03 | 3.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.158400E+13 | 0.155611E+13 | 0.14 | |||
Minimum of Months | 0.00 | 0.00 | 47343.63 | 47343.63 | 3.47 | 3.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.537500E+12 | 0.519233E+12 | 1162224.11 | 997241.78 | 0.52 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 129393.08 | 129393.08 | 406.48 | 02-JAN-04:30 | 406.48 | 0.00 |
February | 0.00 | 0.00 | 0.356705E+09 | 0.356705E+09 | 23736.64 | 27-FEB-15:00 | 23736.64 | 0.00 |
March | 0.00 | 0.00 | 0.532686E+09 | 0.532686E+09 | 21318.35 | 18-MAR-14:00 | 21318.35 | 0.01 |
April | 0.00 | 0.00 | 0.641471E+10 | 0.641471E+10 | 102670.64 | 27-APR-14:50 | 102670.64 | 0.03 |
May | 0.00 | 0.00 | 0.124175E+11 | 0.124145E+11 | 87025.61 | 04-MAY-15:00 | 87025.61 | 0.12 |
June | 0.00 | 0.00 | 0.239406E+11 | 0.239392E+11 | 104360.82 | 28-JUN-15:20 | 104360.82 | 0.21 |
July | 0.00 | 0.00 | 0.436262E+11 | 0.430000E+11 | 129998.67 | 31-JUL-16:00 | 112063.12 | 0.41 |
August | 0.00 | 0.00 | 0.576274E+11 | 0.557319E+11 | 135570.27 | 10-AUG-15:40 | 123677.32 | 0.51 |
September | 0.00 | 0.00 | 0.188152E+11 | 0.185096E+11 | 93218.60 | 14-SEP-13:10 | 72229.49 | 0.28 |
October | 0.00 | 0.00 | 0.249041E+10 | 0.249041E+10 | 53994.68 | 04-OCT-15:00 | 53994.68 | 0.00 |
November | 0.00 | 0.00 | 0.470360E+09 | 0.470360E+09 | 27013.43 | 04-NOV-14:00 | 27013.43 | 0.01 |
December | 0.00 | 0.00 | 27294.25 | 27294.25 | 451.78 | 26-DEC-05:01 | 451.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.166692E+12 | 0.163860E+12 | 0.13 | |||
Minimum of Months | 0.00 | 0.00 | 27294.25 | 27294.25 | 406.48 | 406.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.576274E+11 | 0.557319E+11 | 135570.27 | 123677.32 | 0.51 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2162289.83 | 2162289.83 | 8342.39 | 11-JAN-05:02 | 8342.39 | 0.00 |
February | 0.00 | 0.00 | 0.406424E+09 | 0.400533E+09 | 39829.71 | 24-FEB-06:02 | 27168.43 | 0.00 |
March | 0.00 | 0.00 | 76295979.78 | 71440749.85 | 20777.26 | 10-MAR-06:03 | 9516.39 | 0.00 |
April | 0.00 | 0.00 | 0.340122E+10 | 0.339951E+10 | 52163.69 | 27-APR-15:00 | 52163.69 | 0.02 |
May | 0.00 | 0.00 | 0.667136E+10 | 0.666578E+10 | 50908.95 | 15-MAY-16:00 | 50908.95 | 0.09 |
June | 0.00 | 0.00 | 0.138690E+11 | 0.138324E+11 | 50617.80 | 28-JUN-15:00 | 50617.80 | 0.16 |
July | 0.00 | 0.00 | 0.260690E+11 | 0.256697E+11 | 75593.09 | 31-JUL-10:10 | 59423.13 | 0.31 |
August | 0.00 | 0.00 | 0.361155E+11 | 0.354430E+11 | 67804.81 | 29-AUG-13:10 | 59092.80 | 0.41 |
September | 0.00 | 0.00 | 0.107769E+11 | 0.106744E+11 | 51894.05 | 11-SEP-15:00 | 51894.05 | 0.19 |
October | 0.00 | 0.00 | 0.149271E+10 | 0.148191E+10 | 35321.91 | 04-OCT-15:00 | 35321.91 | 0.00 |
November | 0.00 | 0.00 | 0.219622E+09 | 0.211959E+09 | 27595.28 | 04-NOV-04:03 | 18100.43 | 0.01 |
December | 0.00 | 0.00 | 4719538.84 | 4719538.84 | 9637.71 | 16-DEC-06:03 | 9637.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.991049E+11 | 0.978574E+11 | 0.10 | |||
Minimum of Months | 0.00 | 0.00 | 2162289.83 | 2162289.83 | 8342.39 | 8342.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.361155E+11 | 0.354430E+11 | 75593.09 | 59423.13 | 0.41 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.376820E+10 | 0.376786E+10 | 2062.53 | 08-JAN-16:10 | 2062.53 | 0.00 |
February | 0.00 | 0.00 | 0.857729E+10 | 0.856692E+10 | 4244.61 | 27-FEB-16:20 | 4233.83 | 0.00 |
March | 0.00 | 0.00 | 0.151416E+11 | 0.151337E+11 | 7526.76 | 31-MAR-24:00 | 7526.76 | 0.00 |
April | 0.00 | 0.00 | 0.198419E+11 | 0.198288E+11 | 8445.52 | 23-APR-18:00 | 8445.52 | 0.00 |
May | 0.00 | 0.00 | 0.542685E+10 | 0.539072E+10 | 3992.85 | 31-MAY-24:00 | 3984.34 | 0.00 |
June | 0.00 | 0.00 | 0.103897E+11 | 0.103390E+11 | 5864.15 | 30-JUN-24:00 | 5862.59 | 0.00 |
July | 0.00 | 0.00 | 0.160516E+11 | 0.159481E+11 | 7796.17 | 31-JUL-23:35 | 7771.49 | 0.00 |
August | 0.00 | 0.00 | 0.210822E+11 | 0.209339E+11 | 8936.66 | 06-AUG-18:22 | 8936.66 | 0.00 |
September | 0.00 | 0.00 | 0.543338E+10 | 0.534280E+10 | 3851.79 | 30-SEP-24:00 | 3850.62 | 0.00 |
October | 0.00 | 0.00 | 0.102542E+11 | 0.102318E+11 | 5558.05 | 31-OCT-24:00 | 5558.05 | 0.00 |
November | 0.00 | 0.00 | 0.145456E+11 | 0.145221E+11 | 6197.44 | 12-NOV-16:00 | 6197.44 | 0.00 |
December | 0.00 | 0.00 | 0.198850E+11 | 0.198825E+11 | 8019.94 | 10-DEC-15:40 | 8019.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150397E+12 | 0.149888E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.376820E+10 | 0.376786E+10 | 2062.53 | 2062.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.210822E+11 | 0.209339E+11 | 8936.66 | 8936.66 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.112514E+11 | 0.112511E+11 | 13365.25 | 05-JAN-16:10 | 13365.25 | 0.00 |
February | 0.00 | 0.00 | 0.628885E+11 | 0.627876E+11 | 38396.02 | 27-FEB-16:30 | 38212.21 | 0.00 |
March | 0.00 | 0.00 | 0.129931E+12 | 0.129851E+12 | 66443.42 | 31-MAR-24:00 | 66443.42 | 0.00 |
April | 0.00 | 0.00 | 0.180591E+12 | 0.180457E+12 | 79899.97 | 26-APR-17:50 | 79899.97 | 0.00 |
May | 0.00 | 0.00 | 0.456476E+11 | 0.452944E+11 | 37126.61 | 31-MAY-24:00 | 37032.01 | 0.00 |
June | 0.00 | 0.00 | 0.947754E+11 | 0.942713E+11 | 54949.76 | 30-JUN-24:00 | 54932.27 | 0.00 |
July | 0.00 | 0.00 | 0.150867E+12 | 0.149836E+12 | 75245.53 | 31-JUL-23:53 | 75022.64 | 0.00 |
August | 0.00 | 0.00 | 0.199467E+12 | 0.197986E+12 | 83254.63 | 06-AUG-18:23 | 83254.63 | 0.00 |
September | 0.00 | 0.00 | 0.462750E+11 | 0.453933E+11 | 34260.78 | 30-SEP-24:00 | 34243.54 | 0.00 |
October | 0.00 | 0.00 | 0.856084E+11 | 0.853863E+11 | 46697.88 | 31-OCT-24:00 | 46697.88 | 0.00 |
November | 0.00 | 0.00 | 0.119756E+12 | 0.119522E+12 | 55584.75 | 04-NOV-16:00 | 54583.80 | 0.00 |
December | 0.00 | 0.00 | 0.164520E+12 | 0.164495E+12 | 70933.04 | 05-DEC-15:50 | 70933.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.129158E+13 | 0.128653E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.112514E+11 | 0.112511E+11 | 13365.25 | 13365.25 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.199467E+12 | 0.197986E+12 | 83254.63 | 83254.63 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.266580E+09 | 0.266580E+09 | 1139.11 | 05-JAN-16:10 | 1139.11 | 0.00 |
February | 0.00 | 0.00 | 0.465390E+10 | 0.464403E+10 | 3750.00 | 27-FEB-16:30 | 3731.84 | 0.00 |
March | 0.00 | 0.00 | 0.114827E+11 | 0.114748E+11 | 6031.71 | 31-MAR-23:30 | 6031.71 | 0.00 |
April | 0.00 | 0.00 | 0.171545E+11 | 0.171412E+11 | 8062.40 | 26-APR-17:50 | 8062.40 | 0.00 |
May | 0.00 | 0.00 | 0.400302E+10 | 0.396819E+10 | 3647.00 | 31-MAY-23:30 | 3631.46 | 0.00 |
June | 0.00 | 0.00 | 0.924144E+10 | 0.919122E+10 | 5405.45 | 30-JUN-23:50 | 5403.08 | 0.00 |
July | 0.00 | 0.00 | 0.149798E+11 | 0.148768E+11 | 7525.75 | 31-JUL-23:53 | 7503.32 | 0.00 |
August | 0.00 | 0.00 | 0.197904E+11 | 0.196426E+11 | 8462.48 | 06-AUG-18:12 | 8462.48 | 0.00 |
September | 0.00 | 0.00 | 0.403765E+10 | 0.395153E+10 | 3003.47 | 30-SEP-23:20 | 2999.04 | 0.00 |
October | 0.00 | 0.00 | 0.721514E+10 | 0.719361E+10 | 4309.68 | 04-OCT-16:50 | 4309.68 | 0.00 |
November | 0.00 | 0.00 | 0.102210E+11 | 0.101979E+11 | 5408.49 | 04-NOV-16:00 | 5309.13 | 0.00 |
December | 0.00 | 0.00 | 0.145316E+11 | 0.145291E+11 | 6795.13 | 05-DEC-15:50 | 6795.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.117578E+12 | 0.117078E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.266580E+09 | 0.266580E+09 | 1139.11 | 1139.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.197904E+11 | 0.196426E+11 | 8462.48 | 8462.48 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 100103.30 | 1374367.53 | 02-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58746.36 | 996126.63 | 23-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16189.33 | 854069.53 | 06-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5264.97 | 213982.68 | 19-APR-06:05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 638.87 | 121908.46 | 18-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 8.43 | 2910.34 | 15-JUN-05:08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 118.81 | 64368.02 | 27-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3744.13 | 424458.01 | 30-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 34941.06 | 960215.87 | 28-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 73681.84 | 1229830.10 | 26-DEC-06:03 |
Annual Sum or Average | 0.00 | 24328.71 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 100103.30 | 1374367.53 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 480.10 | 20840.69 | 14-JAN-06:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 5259.86 | 731702.53 | 27-FEB-15:00 | 0.09 | 1870.03 | 24-FEB-06:02 |
March | 6792.36 | 563051.65 | 18-MAR-14:10 | 16.52 | 82490.83 | 23-MAR-05:03 |
April | 52878.91 | 1169983.26 | 26-APR-15:40 | 49.28 | 144022.60 | 01-APR-23:23 |
May | 102505.53 | 1208646.83 | 04-MAY-15:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 194228.68 | 1200559.54 | 22-JUN-15:20 | 122.44 | 211198.34 | 18-JUN-09:05 |
July | 310400.47 | 1429948.47 | 31-JUL-16:00 | 1.57 | 8904.70 | 08-JUL-21:03 |
August | 371580.97 | 1505098.90 | 29-AUG-14:30 | 5.09 | 27210.85 | 23-AUG-00:43 |
September | 157136.79 | 1152633.09 | 14-SEP-13:00 | 4.30 | 30500.42 | 04-SEP-07:43 |
October | 27941.56 | 945423.03 | 04-OCT-11:50 | 0.49 | 6623.77 | 09-OCT-09:53 |
November | 5949.94 | 718378.75 | 04-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 502.92 | 57322.41 | 29-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 103779.25 | 16.49 | ||||
Minimum of Months | 480.10 | 20840.69 | 0.00 | 0.00 | ||
Maximum of Months | 371580.97 | 1505098.90 | 122.44 | 211198.34 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.02 | 294.22 | 11-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 2691.44 | 452771.31 | 27-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 3395.79 | 329500.90 | 18-MAR-14:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 37636.57 | 1254779.57 | 26-APR-15:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 73706.16 | 1257754.92 | 04-MAY-14:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 145569.44 | 1300013.20 | 22-JUN-15:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 243908.75 | 1422512.95 | 31-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 310175.95 | 2149735.54 | 30-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 121799.07 | 1435697.37 | 10-SEP-15:12 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 18496.84 | 898987.87 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3070.09 | 456266.29 | 04-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 13.99 | 55636.39 | 16-DEC-05:01 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 80707.50 | 0.00 | ||||
Minimum of Months | 0.02 | 294.22 | 0.00 | 0.00 | ||
Maximum of Months | 310175.95 | 2149735.54 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7826.73 | 20998.31 | 05-JAN-16:10 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 39495.91 | 77292.30 | 27-FEB-15:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 72256.47 | 112361.70 | 18-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 106424.78 | 228163.38 | 27-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 29951.25 | 106979.37 | 05-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 63166.68 | 156874.21 | 28-JUN-17:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 103197.07 | 233563.74 | 24-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 140686.98 | 280563.69 | 10-AUG-17:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 32312.43 | 110430.59 | 14-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 48185.81 | 101368.85 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 68874.10 | 118210.13 | 04-NOV-15:02 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 91185.93 | 104560.84 | 05-DEC-15:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 67181.43 | 0.00 | ||||
Minimum of Months | 7826.73 | 20998.31 | 0.00 | 0.00 | ||
Maximum of Months | 140686.98 | 280563.69 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15536.78 | 52063.50 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 15721.07 | 52133.93 | 09-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16438.23 | 51959.90 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15106.40 | 50819.15 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15038.26 | 49259.23 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14841.88 | 47369.77 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 13429.04 | 45750.75 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 14451.07 | 45098.29 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 13809.13 | 46053.24 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14181.89 | 47795.32 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14876.17 | 49646.39 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14861.17 | 51152.26 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 14852.68 | ||||
Minimum of Months | 0.00 | 0.00 | 13429.04 | 45098.29 | ||
Maximum of Months | 0.00 | 0.00 | 16438.23 | 52133.93 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16.73 | 17931.50 | 02-JAN-06:30 | 571.28 | 119869.95 | 20-JAN-06:50 |
February | 2746.04 | 428533.01 | 27-FEB-15:10 | 1032.45 | 94849.50 | 16-FEB-05:30 |
March | 3275.30 | 337351.47 | 18-MAR-14:20 | 1062.39 | 97217.98 | 24-MAR-11:30 |
April | 41343.10 | 1936914.47 | 26-APR-14:40 | 1529.76 | 101510.26 | 24-APR-06:00 |
May | 71973.07 | 1840566.77 | 04-MAY-15:40 | 670.69 | 72287.46 | 27-MAY-05:50 |
June | 146057.48 | 1918016.24 | 28-JUN-15:30 | 571.87 | 52619.62 | 15-JUN-21:00 |
July | 256496.16 | 2656613.81 | 31-JUL-16:00 | 946.06 | 66842.30 | 03-JUL-09:00 |
August | 372853.24 | 3050473.69 | 29-AUG-14:30 | 831.37 | 57812.79 | 23-AUG-05:40 |
September | 124579.56 | 1968894.29 | 14-SEP-12:40 | 498.73 | 66942.08 | 27-SEP-05:30 |
October | 16823.38 | 797391.37 | 04-OCT-15:00 | 1030.62 | 79793.63 | 27-OCT-16:00 |
November | 2958.31 | 423316.59 | 04-NOV-14:00 | 1105.66 | 102921.72 | 10-NOV-06:30 |
December | 20.90 | 19648.20 | 21-DEC-05:30 | 569.31 | 98284.56 | 09-DEC-06:30 |
Annual Sum or Average | 87370.59 | 866.36 | ||||
Minimum of Months | 16.73 | 17931.50 | 498.73 | 52619.62 | ||
Maximum of Months | 372853.24 | 3050473.69 | 1529.76 | 119869.95 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.124354E+11 | 0.79 | 8325.79 | 01-JAN-00:40 | 1.41 |
February | 0.111715E+11 | 0.78 | 8325.79 | 01-FEB-05:02 | 1.40 |
March | 0.132805E+11 | 0.84 | 8325.79 | 01-MAR-05:03 | 1.41 |
April | 0.123288E+11 | 0.80 | 8325.79 | 01-APR-04:03 | 1.41 |
May | 0.129350E+11 | 0.81 | 8325.79 | 01-MAY-03:02 | 1.40 |
June | 0.131231E+11 | 0.85 | 8325.79 | 01-JUN-03:02 | 1.40 |
July | 0.126136E+11 | 0.79 | 8325.79 | 01-JUL-03:02 | 1.41 |
August | 0.138420E+11 | 0.87 | 8325.79 | 01-AUG-03:10 | 1.40 |
September | 0.129116E+11 | 0.84 | 8325.79 | 01-SEP-03:02 | 1.40 |
October | 0.129757E+11 | 0.82 | 8325.79 | 02-OCT-03:02 | 1.41 |
November | 0.123097E+11 | 0.80 | 8325.79 | 01-NOV-04:03 | 1.40 |
December | 0.121602E+11 | 0.77 | 8325.79 | 01-DEC-05:01 | 1.41 |
Annual Sum or Average | 0.152087E+12 | 0.81 | |||
Minimum of Months | 0.111715E+11 | 0.77 | 8325.79 | 1.40 | |
Maximum of Months | 0.138420E+11 | 0.87 | 8325.79 | 1.41 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.331541E+10 | 0.31 | 10292.17 | 02-JAN-06:01 | 1.27 |
February | 0.380404E+10 | 0.34 | 10733.21 | 24-FEB-06:02 | 1.30 |
March | 0.602934E+10 | 0.43 | 11606.59 | 03-MAR-06:02 | 1.37 |
April | 0.779093E+10 | 0.51 | 15773.78 | 27-APR-14:30 | 1.65 |
May | 0.696623E+10 | 0.46 | 13115.76 | 15-MAY-14:30 | 1.48 |
June | 0.863929E+10 | 0.54 | 17493.16 | 12-JUN-05:03 | 1.76 |
July | 0.106031E+11 | 0.62 | 17573.14 | 31-JUL-14:30 | 1.76 |
August | 0.124830E+11 | 0.70 | 19430.14 | 14-AUG-05:02 | 1.89 |
September | 0.710374E+10 | 0.47 | 14898.94 | 11-SEP-15:00 | 1.59 |
October | 0.595888E+10 | 0.41 | 12674.06 | 04-OCT-15:10 | 1.45 |
November | 0.471031E+10 | 0.37 | 12028.23 | 27-NOV-06:01 | 1.39 |
December | 0.456993E+10 | 0.36 | 12837.31 | 11-DEC-06:01 | 1.46 |
Annual Sum or Average | 0.819742E+11 | 0.46 | |||
Minimum of Months | 0.331541E+10 | 0.31 | 10292.17 | 1.27 | |
Maximum of Months | 0.124830E+11 | 0.70 | 19430.14 | 1.89 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.274186E+11 | 0.30 | 47653.78 | 02-JAN-05:21 | 0.85 |
February | 0.260011E+11 | 0.31 | 39048.79 | 27-FEB-15:00 | 0.76 |
March | 0.343296E+11 | 0.34 | 86111.55 | 02-MAR-06:03 | 1.20 |
April | 0.395050E+11 | 0.35 | 111512.82 | 27-APR-14:30 | 1.40 |
May | 0.507033E+11 | 0.40 | 113610.37 | 15-MAY-05:03 | 1.42 |
June | 0.585239E+11 | 0.45 | 116687.74 | 12-JUN-05:03 | 1.44 |
July | 0.677583E+11 | 0.47 | 135717.47 | 25-JUL-05:03 | 1.58 |
August | 0.775047E+11 | 0.51 | 178624.31 | 14-AUG-05:02 | 1.88 |
September | 0.536799E+11 | 0.41 | 128302.94 | 11-SEP-05:03 | 1.53 |
October | 0.374000E+11 | 0.33 | 95790.22 | 04-OCT-15:40 | 1.28 |
November | 0.271863E+11 | 0.30 | 83769.31 | 03-NOV-05:03 | 1.18 |
December | 0.271327E+11 | 0.30 | 47653.78 | 26-DEC-06:03 | 0.85 |
Annual Sum or Average | 0.527144E+12 | 0.37 | |||
Minimum of Months | 0.260011E+11 | 0.30 | 39048.79 | 0.76 | |
Maximum of Months | 0.775047E+11 | 0.51 | 178624.31 | 1.88 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.340061E+10 | 0.36 | 4376.35 | 02-JAN-04:11 | 0.77 |
February | 0.284629E+10 | 0.33 | 4376.35 | 06-FEB-05:01 | 0.77 |
March | 0.311627E+10 | 0.33 | 4376.35 | 06-MAR-05:01 | 0.77 |
April | 0.338170E+10 | 0.32 | 12606.15 | 27-APR-14:30 | 1.43 |
May | 0.437179E+10 | 0.36 | 12569.18 | 15-MAY-15:20 | 1.44 |
June | 0.542985E+10 | 0.41 | 13408.33 | 28-JUN-15:20 | 1.49 |
July | 0.665806E+10 | 0.43 | 15843.76 | 31-JUL-15:20 | 1.65 |
August | 0.744291E+10 | 0.47 | 17709.91 | 10-AUG-15:00 | 1.77 |
September | 0.450593E+10 | 0.36 | 13166.08 | 14-SEP-15:00 | 1.47 |
October | 0.306235E+10 | 0.30 | 8379.56 | 04-OCT-15:20 | 1.12 |
November | 0.271468E+10 | 0.30 | 4376.35 | 13-NOV-05:01 | 0.77 |
December | 0.301494E+10 | 0.32 | 4376.35 | 01-DEC-06:02 | 0.77 |
Annual Sum or Average | 0.499454E+11 | 0.36 | |||
Minimum of Months | 0.271468E+10 | 0.30 | 4376.35 | 0.77 | |
Maximum of Months | 0.744291E+10 | 0.47 | 17709.91 | 1.77 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147304E+10 | 0.93 | 549.97 | 01-JAN-00:05 | 0.93 |
February | 0.133049E+10 | 0.93 | 549.97 | 01-FEB-00:10 | 0.93 |
March | 0.147304E+10 | 0.93 | 549.97 | 01-MAR-00:10 | 0.93 |
April | 0.142552E+10 | 0.93 | 549.97 | 01-APR-00:10 | 0.93 |
May | 0.147304E+10 | 0.93 | 549.97 | 01-MAY-00:10 | 0.93 |
June | 0.142552E+10 | 0.93 | 549.97 | 01-JUN-00:10 | 0.93 |
July | 0.147304E+10 | 0.93 | 549.97 | 01-JUL-00:10 | 0.93 |
August | 0.147304E+10 | 0.93 | 549.97 | 01-AUG-00:03 | 0.93 |
September | 0.142552E+10 | 0.93 | 549.97 | 01-SEP-00:10 | 0.93 |
October | 0.147304E+10 | 0.93 | 549.97 | 01-OCT-00:10 | 0.93 |
November | 0.142552E+10 | 0.93 | 549.97 | 01-NOV-00:10 | 0.93 |
December | 0.147304E+10 | 0.93 | 549.97 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.173439E+11 | 0.93 | |||
Minimum of Months | 0.133049E+10 | 0.93 | 549.97 | 0.93 | |
Maximum of Months | 0.147304E+10 | 0.93 | 549.97 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140788E+11 | 0.93 | 5256.42 | 01-JAN-00:05 | 0.92 |
February | 0.127163E+11 | 0.93 | 5256.42 | 01-FEB-00:10 | 0.93 |
March | 0.140788E+11 | 0.93 | 5256.42 | 01-MAR-00:10 | 0.93 |
April | 0.136246E+11 | 0.93 | 5256.42 | 01-APR-00:10 | 0.93 |
May | 0.140788E+11 | 0.93 | 5256.42 | 01-MAY-00:10 | 0.93 |
June | 0.136246E+11 | 0.93 | 5256.42 | 01-JUN-00:10 | 0.93 |
July | 0.140788E+11 | 0.93 | 5256.42 | 01-JUL-00:10 | 0.93 |
August | 0.140788E+11 | 0.93 | 5256.42 | 01-AUG-00:03 | 0.93 |
September | 0.136246E+11 | 0.93 | 5256.42 | 01-SEP-00:10 | 0.93 |
October | 0.140788E+11 | 0.93 | 5256.42 | 01-OCT-00:10 | 0.93 |
November | 0.136246E+11 | 0.93 | 5256.42 | 01-NOV-00:10 | 0.93 |
December | 0.140788E+11 | 0.93 | 5256.42 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.165766E+12 | 0.93 | |||
Minimum of Months | 0.127163E+11 | 0.93 | 5256.42 | 0.92 | |
Maximum of Months | 0.140788E+11 | 0.93 | 5256.42 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143070E+10 | 0.93 | 534.16 | 01-JAN-00:05 | 0.92 |
February | 0.129224E+10 | 0.93 | 534.16 | 01-FEB-00:10 | 0.93 |
March | 0.143070E+10 | 0.93 | 534.16 | 01-MAR-00:10 | 0.93 |
April | 0.138455E+10 | 0.93 | 534.16 | 01-APR-00:10 | 0.93 |
May | 0.143070E+10 | 0.93 | 534.16 | 01-MAY-00:10 | 0.93 |
June | 0.138455E+10 | 0.93 | 534.16 | 01-JUN-00:10 | 0.93 |
July | 0.143070E+10 | 0.93 | 534.16 | 01-JUL-00:10 | 0.93 |
August | 0.143070E+10 | 0.93 | 534.16 | 01-AUG-00:03 | 0.93 |
September | 0.138455E+10 | 0.93 | 534.16 | 01-SEP-00:10 | 0.93 |
October | 0.143070E+10 | 0.93 | 534.16 | 01-OCT-00:10 | 0.93 |
November | 0.138455E+10 | 0.93 | 534.16 | 01-NOV-00:10 | 0.93 |
December | 0.143070E+10 | 0.93 | 534.16 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.168453E+11 | 0.93 | |||
Minimum of Months | 0.129224E+10 | 0.93 | 534.16 | 0.92 | |
Maximum of Months | 0.143070E+10 | 0.93 | 534.16 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 26602422.09 | 24181601.68 | 983.87 | 02-JAN-06:01 | 894.34 | 894.34 | 49.02 | 8.51 |
February | 10255590.46 | 9322331.73 | 314.83 | 21-FEB-06:01 | 286.18 | 286.18 | 42.33 | 5.15 |
March | 2000853.28 | 1818775.64 | 312.90 | 06-MAR-06:01 | 284.42 | 284.42 | 40.23 | 5.14 |
April | 528232.50 | 480163.34 | 12.81 | 19-APR-06:10 | 11.64 | 11.64 | 27.06 | 0.94 |
May | 53102.18 | 48269.88 | 5.19 | 18-MAY-05:02 | 4.72 | 4.72 | 23.56 | 0.52 |
June | 550.41 | 500.33 | 0.07 | 15-JUN-05:08 | 0.07 | 0.07 | 20.77 | 0.01 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 20.69 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 20.69 | 0.00 |
September | 8219.27 | 7471.31 | 2.11 | 27-SEP-05:03 | 1.91 | 1.91 | 20.80 | 0.26 |
October | 359184.62 | 326498.82 | 45.70 | 30-OCT-05:03 | 41.54 | 41.54 | 28.53 | 1.98 |
November | 5044351.96 | 4585315.93 | 316.59 | 27-NOV-06:01 | 287.78 | 287.78 | 39.41 | 5.17 |
December | 14285631.40 | 12985638.94 | 960.31 | 26-DEC-06:03 | 872.93 | 872.93 | 46.33 | 8.43 |
Annual Sum or Average | 59138138.17 | 53756567.60 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.69 | 0.00 | |
Maximum of Months | 26602422.09 | 24181601.68 | 983.87 | 894.34 | 894.34 | 49.02 | 8.51 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1176.99 | 1069.88 | 4.42 | 11-JAN-05:02 | 4.02 | 4.02 | 6.72 | 0.87 |
February | 2013908.99 | 1830643.28 | 181.24 | 27-FEB-15:00 | 164.75 | 164.75 | 8.76 | 10.62 |
March | 2309479.48 | 2099316.85 | 96.30 | 18-MAR-14:00 | 87.54 | 87.54 | 8.53 | 7.49 |
April | 0.109157E+09 | 99223667.03 | 5940.40 | 26-APR-15:40 | 5399.83 | 5399.83 | 7.04 | 53.82 |
May | 0.186462E+09 | 0.169494E+09 | 5122.41 | 04-MAY-14:10 | 4656.27 | 4656.27 | 7.14 | 50.61 |
June | 0.495913E+09 | 0.450785E+09 | 7032.99 | 27-JUN-13:50 | 6392.99 | 6392.99 | 7.35 | 57.68 |
July | 0.787358E+09 | 0.715709E+09 | 6271.17 | 19-JUL-14:20 | 5700.50 | 5700.50 | 7.21 | 55.03 |
August | 0.107929E+10 | 0.981071E+09 | 14944.87 | 30-AUG-05:02 | 13584.89 | 13584.89 | 8.31 | 78.04 |
September | 0.358839E+09 | 0.326184E+09 | 5911.40 | 08-SEP-14:40 | 5373.46 | 5373.46 | 7.57 | 53.71 |
October | 30249475.07 | 27496772.84 | 1344.90 | 04-OCT-13:30 | 1222.52 | 1222.52 | 8.06 | 28.36 |
November | 3646620.33 | 3314777.88 | 265.98 | 04-NOV-14:00 | 241.78 | 241.78 | 8.56 | 12.99 |
December | 23418.57 | 21287.48 | 32.26 | 16-DEC-05:01 | 29.32 | 29.32 | 8.45 | 3.85 |
Annual Sum or Average | 0.305526E+10 | 0.277723E+10 | ||||||
Minimum of Months | 1176.99 | 1069.88 | 4.42 | 4.02 | 4.02 | 6.72 | 0.87 | |
Maximum of Months | 0.107929E+10 | 0.981071E+09 | 14944.87 | 13584.89 | 13584.89 | 8.76 | 78.04 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.713357E+09 | 0.648441E+09 | 11532.59 | 01-JAN-14:43 | 10483.13 | 10483.13 | 8.43 | 81.64 |
February | 0.132187E+10 | 0.120158E+10 | 11532.59 | 01-FEB-06:03 | 10483.13 | 10483.13 | 8.41 | 81.64 |
March | 0.209836E+10 | 0.190741E+10 | 11532.59 | 01-MAR-10:20 | 10483.13 | 10483.13 | 8.43 | 81.64 |
April | 0.517179E+10 | 0.470116E+10 | 11532.59 | 01-APR-05:03 | 10483.13 | 10483.13 | 8.43 | 81.64 |
May | 0.801169E+10 | 0.728263E+10 | 11532.59 | 01-MAY-03:02 | 10483.13 | 10483.13 | 8.60 | 81.64 |
June | 0.130689E+11 | 0.118796E+11 | 11532.59 | 01-JUN-04:03 | 10483.13 | 10483.13 | 8.64 | 81.64 |
July | 0.189513E+11 | 0.172267E+11 | 11532.59 | 01-JUL-05:02 | 10483.13 | 10483.13 | 9.05 | 81.64 |
August | 0.210871E+11 | 0.191682E+11 | 11532.59 | 01-AUG-00:03 | 10483.13 | 10483.13 | 8.20 | 81.64 |
September | 0.111266E+11 | 0.101141E+11 | 11532.59 | 01-SEP-00:23 | 10483.13 | 10483.13 | 8.33 | 81.64 |
October | 0.391359E+10 | 0.355745E+10 | 11532.59 | 01-OCT-12:43 | 10483.13 | 10483.13 | 8.43 | 81.64 |
November | 0.175333E+10 | 0.159378E+10 | 11532.59 | 01-NOV-04:03 | 10483.13 | 10483.13 | 8.62 | 81.64 |
December | 0.726702E+09 | 0.660572E+09 | 11532.59 | 01-DEC-13:20 | 10483.13 | 10483.13 | 8.43 | 81.64 |
Annual Sum or Average | 0.879446E+11 | 0.799416E+11 | ||||||
Minimum of Months | 0.713357E+09 | 0.648441E+09 | 11532.59 | 10483.13 | 10483.13 | 8.20 | 81.64 | |
Maximum of Months | 0.210871E+11 | 0.191682E+11 | 11532.59 | 10483.13 | 10483.13 | 9.05 | 81.64 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.181414E+10 | 0.164905E+10 | 677.32 | 01-JAN-00:05 | 615.69 | 615.69 | 18.61 | 2.86 |
February | 0.163858E+10 | 0.148947E+10 | 677.32 | 01-FEB-00:10 | 615.69 | 615.69 | 21.86 | 2.86 |
March | 0.181414E+10 | 0.164905E+10 | 677.32 | 01-MAR-00:10 | 615.69 | 615.69 | 25.31 | 2.86 |
April | 0.175562E+10 | 0.159586E+10 | 677.32 | 01-APR-00:10 | 615.69 | 615.69 | 28.11 | 2.86 |
May | 0.181414E+10 | 0.164905E+10 | 677.32 | 01-MAY-00:10 | 615.69 | 615.69 | 21.13 | 2.86 |
June | 0.175562E+10 | 0.159586E+10 | 677.32 | 01-JUN-00:10 | 615.69 | 615.69 | 23.87 | 2.86 |
July | 0.181414E+10 | 0.164905E+10 | 677.32 | 01-JUL-00:10 | 615.69 | 615.69 | 26.45 | 2.86 |
August | 0.181414E+10 | 0.164905E+10 | 677.32 | 01-AUG-00:03 | 615.69 | 615.69 | 29.85 | 2.86 |
September | 0.175562E+10 | 0.159586E+10 | 677.32 | 01-SEP-00:10 | 615.69 | 615.69 | 21.35 | 2.86 |
October | 0.181414E+10 | 0.164905E+10 | 677.32 | 01-OCT-00:10 | 615.69 | 615.69 | 23.43 | 2.86 |
November | 0.175562E+10 | 0.159586E+10 | 677.32 | 01-NOV-00:10 | 615.69 | 615.69 | 25.28 | 2.86 |
December | 0.181414E+10 | 0.164905E+10 | 677.32 | 01-DEC-00:10 | 615.69 | 615.69 | 27.27 | 2.86 |
Annual Sum or Average | 0.213601E+11 | 0.194163E+11 | ||||||
Minimum of Months | 0.163858E+10 | 0.148947E+10 | 677.32 | 615.69 | 615.69 | 18.61 | 2.86 | |
Maximum of Months | 0.181414E+10 | 0.164905E+10 | 677.32 | 615.69 | 615.69 | 29.85 | 2.86 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:03 | 1.79 | 1.79 | 55.44 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:03 | 1.79 | 1.79 | 55.52 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:03 | 1.79 | 1.79 | 56.29 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:03 | 1.79 | 1.79 | 55.67 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:03 | 1.79 | 1.79 | 55.93 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:02 | 1.79 | 1.79 | 55.85 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:02 | 1.79 | 1.79 | 56.63 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:03 | 1.79 | 1.79 | 57.13 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 56.57 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 56.20 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:03 | 1.79 | 1.79 | 55.71 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:02 | 1.79 | 1.79 | 55.85 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.44 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 57.13 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.902462E+09 | 0.820338E+09 | 14591.94 | 02-JAN-06:30 | 13264.08 | 13264.08 | 21.19 | 49.09 |
February | 0.167088E+10 | 0.151883E+10 | 14612.95 | 27-FEB-15:10 | 13283.18 | 13283.18 | 23.19 | 49.09 |
March | 0.264201E+10 | 0.240159E+10 | 14608.28 | 18-MAR-14:20 | 13278.93 | 13278.93 | 22.74 | 49.09 |
April | 0.694261E+10 | 0.631083E+10 | 29284.25 | 26-APR-14:40 | 26619.38 | 26619.38 | 25.82 | 98.19 |
May | 0.106715E+11 | 0.970035E+10 | 29278.48 | 04-MAY-15:40 | 26614.14 | 26614.14 | 25.59 | 98.19 |
June | 0.176553E+11 | 0.160486E+11 | 29283.12 | 28-JUN-15:30 | 26618.35 | 26618.35 | 25.77 | 98.19 |
July | 0.263610E+11 | 0.239621E+11 | 29327.35 | 31-JUL-16:00 | 26658.56 | 26658.56 | 27.57 | 98.19 |
August | 0.316874E+11 | 0.288038E+11 | 29350.99 | 29-AUG-14:30 | 26680.05 | 26680.05 | 28.53 | 98.19 |
September | 0.151781E+11 | 0.137969E+11 | 29286.16 | 14-SEP-12:40 | 26621.12 | 26621.12 | 25.90 | 98.19 |
October | 0.495071E+10 | 0.450020E+10 | 14631.87 | 04-OCT-15:00 | 13300.37 | 13300.37 | 24.99 | 49.09 |
November | 0.221856E+10 | 0.201667E+10 | 14612.69 | 04-NOV-14:00 | 13282.93 | 13282.93 | 23.16 | 49.09 |
December | 0.919347E+09 | 0.835687E+09 | 14592.03 | 21-DEC-05:30 | 13264.16 | 13264.16 | 21.20 | 49.09 |
Annual Sum or Average | 0.121800E+12 | 0.110716E+12 | ||||||
Minimum of Months | 0.902462E+09 | 0.820338E+09 | 14591.94 | 13264.08 | 13264.08 | 21.19 | 49.09 | |
Maximum of Months | 0.316874E+11 | 0.288038E+11 | 29350.99 | 26680.05 | 26680.05 | 28.53 | 98.19 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 35.76 | 35.76 | 100103.30 | 1374367.53 | 02-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.73 | 26.73 | 58746.36 | 996126.63 | 23-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.49 | 22.49 | 16189.33 | 854069.53 | 06-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 21.67 | 21.67 | 5264.97 | 213982.68 | 19-APR-06:05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 23.68 | 23.68 | 638.87 | 121908.46 | 18-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.94 | 20.94 | 8.43 | 2910.34 | 15-JUN-05:08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.69 | 20.69 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.69 | 20.69 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 20.69 | 20.69 | 118.81 | 64368.02 | 27-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21.62 | 21.62 | 3744.13 | 424458.01 | 30-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.94 | 22.94 | 34941.06 | 960215.87 | 28-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 27.78 | 27.78 | 73681.84 | 1229830.10 | 26-DEC-06:03 |
Annual Sum or Average | 0.00 | 24328.71 | ||||||
Minimum of Months | 0.00 | 0.00 | 20.69 | 20.69 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 35.76 | 35.76 | 100103.30 | 1374367.53 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 480.10 | 20840.69 | 14-JAN-06:00 | 8.43 | 8.40 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 5259.86 | 731702.53 | 27-FEB-15:00 | 9.85 | 8.77 | 0.09 | 1870.03 | 24-FEB-06:02 |
March | 6792.36 | 563051.65 | 18-MAR-14:10 | 9.35 | 8.53 | 16.52 | 82490.83 | 23-MAR-05:03 |
April | 52878.91 | 1169983.26 | 26-APR-15:40 | 10.44 | 7.02 | 49.28 | 144022.60 | 01-APR-23:23 |
May | 102505.53 | 1208646.83 | 04-MAY-15:30 | 10.62 | 8.48 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 194228.68 | 1200559.54 | 22-JUN-15:20 | 10.67 | 7.16 | 122.44 | 211198.34 | 18-JUN-09:05 |
July | 310400.47 | 1429948.47 | 31-JUL-16:00 | 10.88 | 6.70 | 1.57 | 8904.70 | 08-JUL-21:03 |
August | 371580.97 | 1505098.90 | 29-AUG-14:30 | 11.10 | 6.70 | 5.09 | 27210.85 | 23-AUG-00:43 |
September | 157136.79 | 1152633.09 | 14-SEP-13:00 | 10.66 | 7.29 | 4.30 | 30500.42 | 04-SEP-07:43 |
October | 27941.56 | 945423.03 | 04-OCT-11:50 | 10.42 | 9.03 | 0.49 | 6623.77 | 09-OCT-09:53 |
November | 5949.94 | 718378.75 | 04-NOV-14:00 | 9.64 | 8.59 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 502.92 | 57322.41 | 29-DEC-06:02 | 8.54 | 8.45 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 103779.25 | 16.49 | ||||||
Minimum of Months | 480.10 | 20840.69 | 8.43 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 371580.97 | 1505098.90 | 11.10 | 9.03 | 122.44 | 211198.34 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.02 | 294.22 | 11-JAN-06:03 | 6.79 | 8.39 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 2691.44 | 452771.31 | 27-FEB-15:00 | 16.89 | 8.78 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 3395.79 | 329500.90 | 18-MAR-14:10 | 17.28 | 8.54 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 37636.57 | 1254779.57 | 26-APR-15:40 | 12.27 | 8.27 | 0.00 | 0.00 | 01-APR-00:10 |
May | 73706.16 | 1257754.92 | 04-MAY-14:10 | 12.63 | 8.37 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 145569.44 | 1300013.20 | 22-JUN-15:20 | 12.32 | 8.42 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 243908.75 | 1422512.95 | 31-JUL-16:00 | 14.49 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 310175.95 | 2149735.54 | 30-AUG-05:02 | 13.28 | 8.98 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 121799.07 | 1435697.37 | 10-SEP-15:12 | 13.27 | 8.07 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 18496.84 | 898987.87 | 04-OCT-15:00 | 15.49 | 8.61 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3070.09 | 456266.29 | 04-NOV-14:00 | 15.09 | 8.55 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 13.99 | 55636.39 | 16-DEC-05:01 | 10.15 | 8.41 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 80707.50 | 0.00 | ||||||
Minimum of Months | 0.02 | 294.22 | 6.79 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 310175.95 | 2149735.54 | 17.28 | 8.98 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7826.73 | 20998.31 | 05-JAN-16:10 | 20.45 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 39495.91 | 77292.30 | 27-FEB-15:10 | 26.08 | 20.65 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 72256.47 | 112361.70 | 18-MAR-16:00 | 29.56 | 21.69 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 106424.78 | 228163.38 | 27-APR-16:00 | 40.90 | 28.91 | 0.00 | 0.00 | 01-APR-00:10 |
May | 29951.25 | 106979.37 | 05-MAY-16:00 | 29.03 | 25.49 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 63166.68 | 156874.21 | 28-JUN-17:00 | 33.95 | 27.59 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 103197.07 | 233563.74 | 24-JUL-15:00 | 41.42 | 31.95 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 140686.98 | 280563.69 | 10-AUG-17:00 | 45.95 | 33.58 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 32312.43 | 110430.59 | 14-SEP-17:00 | 29.37 | 25.53 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 48185.81 | 101368.85 | 04-OCT-15:00 | 28.48 | 22.52 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 68874.10 | 118210.13 | 04-NOV-15:02 | 30.14 | 22.04 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 91185.93 | 104560.84 | 05-DEC-15:50 | 28.79 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 67181.43 | 0.00 | ||||||
Minimum of Months | 7826.73 | 20998.31 | 20.45 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 140686.98 | 280563.69 | 45.95 | 33.58 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.52 | 56.52 | 15536.78 | 52063.50 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.20 | 56.20 | 15721.07 | 52133.93 | 09-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.91 | 56.91 | 16438.23 | 51959.90 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.33 | 56.33 | 15106.40 | 50819.15 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.80 | 56.80 | 15038.26 | 49259.23 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.38 | 56.38 | 14841.88 | 47369.77 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.78 | 56.78 | 13429.04 | 45750.75 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.46 | 57.46 | 14451.07 | 45098.29 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.14 | 57.14 | 13809.13 | 46053.24 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.20 | 57.20 | 14181.89 | 47795.32 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.31 | 56.31 | 14876.17 | 49646.39 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.41 | 56.41 | 14861.17 | 51152.26 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 14852.68 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.20 | 56.20 | 13429.04 | 45098.29 | ||
Maximum of Months | 0.00 | 0.00 | 57.46 | 57.46 | 16438.23 | 52133.93 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16.73 | 17931.50 | 02-JAN-06:30 | 21.19 | 20.47 | 571.28 | 119869.95 | 20-JAN-06:50 |
February | 2746.04 | 428533.01 | 27-FEB-15:10 | 23.19 | 21.10 | 1032.45 | 94849.50 | 16-FEB-05:30 |
March | 3275.30 | 337351.47 | 18-MAR-14:20 | 22.74 | 21.10 | 1062.39 | 97217.98 | 24-MAR-11:30 |
April | 41343.10 | 1936914.47 | 26-APR-14:40 | 25.82 | 21.10 | 1529.76 | 101510.26 | 24-APR-06:00 |
May | 71973.07 | 1840566.77 | 04-MAY-15:40 | 25.59 | 21.10 | 670.69 | 72287.46 | 27-MAY-05:50 |
June | 146057.48 | 1918016.24 | 28-JUN-15:30 | 25.77 | 21.38 | 571.87 | 52619.62 | 15-JUN-21:00 |
July | 256496.16 | 2656613.81 | 31-JUL-16:00 | 27.57 | 23.53 | 946.06 | 66842.30 | 03-JUL-09:00 |
August | 372853.24 | 3050473.69 | 29-AUG-14:30 | 28.53 | 24.25 | 831.37 | 57812.79 | 23-AUG-05:40 |
September | 124579.56 | 1968894.29 | 14-SEP-12:40 | 25.90 | 22.05 | 498.73 | 66942.08 | 27-SEP-05:30 |
October | 16823.38 | 797391.37 | 04-OCT-15:00 | 24.99 | 21.10 | 1030.62 | 79793.63 | 27-OCT-16:00 |
November | 2958.31 | 423316.59 | 04-NOV-14:00 | 23.16 | 21.10 | 1105.66 | 102921.72 | 10-NOV-06:30 |
December | 20.90 | 19648.20 | 21-DEC-05:30 | 21.20 | 20.36 | 569.31 | 98284.56 | 09-DEC-06:30 |
Annual Sum or Average | 87370.59 | 866.36 | ||||||
Minimum of Months | 16.73 | 17931.50 | 21.19 | 20.36 | 498.73 | 52619.62 | ||
Maximum of Months | 372853.24 | 3050473.69 | 28.53 | 24.25 | 1529.76 | 119869.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.754555E+10 | 0.00 | 483.95 | 0.331541E+10 | 0.00 | 0.00 |
February | 0.426198E+10 | 0.00 | 0.673873E+09 | 0.380404E+10 | 0.00 | 0.00 |
March | 0.669043E+09 | 0.00 | 0.878860E+09 | 0.602934E+10 | 0.00 | 0.00 |
April | 0.155287E+09 | 0.00 | 0.873833E+10 | 0.779093E+10 | 0.00 | 0.00 |
May | 29527767.96 | 0.00 | 0.141854E+11 | 0.696623E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.279831E+11 | 0.863929E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.515590E+11 | 0.106031E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.716939E+11 | 0.124830E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.219998E+11 | 0.710374E+10 | 0.00 | 0.00 |
October | 31724102.16 | 0.00 | 0.397142E+10 | 0.595888E+10 | 0.00 | 0.00 |
November | 0.138659E+10 | 0.00 | 0.566748E+09 | 0.471031E+10 | 0.00 | 0.00 |
December | 0.367855E+10 | 0.00 | 361.45 | 0.456993E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.177582E+11 | 0.00 | 0.202250E+12 | 0.819742E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 361.45 | 0.331541E+10 | 0.00 | 0.00 |
Maximum of Months | 0.754555E+10 | 0.00 | 0.716939E+11 | 0.124830E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.220172E+12 | 0.00 | 53644.70 | 0.274186E+11 | 0.00 | 0.00 |
February | 0.113777E+12 | 0.00 | 0.387504E+10 | 0.260011E+11 | 0.00 | 0.00 |
March | 0.320491E+11 | 0.00 | 0.582521E+10 | 0.343296E+11 | 0.00 | 0.00 |
April | 0.100337E+11 | 0.00 | 0.632318E+11 | 0.395050E+11 | 0.00 | 0.00 |
May | 0.107078E+10 | 0.00 | 0.120778E+12 | 0.507033E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.224631E+12 | 0.585239E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.400717E+12 | 0.677583E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.537500E+12 | 0.775047E+11 | 0.00 | 0.00 |
September | 41609080.77 | 0.00 | 0.192594E+12 | 0.536799E+11 | 0.00 | 0.00 |
October | 0.570358E+10 | 0.00 | 0.300181E+11 | 0.374000E+11 | 0.00 | 0.00 |
November | 0.704905E+11 | 0.00 | 0.482927E+10 | 0.271863E+11 | 0.00 | 0.00 |
December | 0.159821E+12 | 0.00 | 47343.63 | 0.271327E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.613159E+12 | 0.00 | 0.158400E+13 | 0.527144E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 47343.63 | 0.260011E+11 | 0.00 | 0.00 |
Maximum of Months | 0.220172E+12 | 0.00 | 0.537500E+12 | 0.775047E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.417754E+11 | 0.00 | 129393.08 | 0.340061E+10 | 0.00 | 0.00 |
February | 0.248064E+11 | 0.00 | 0.356705E+09 | 0.284629E+10 | 0.00 | 0.00 |
March | 0.108613E+11 | 0.00 | 0.532686E+09 | 0.311627E+10 | 0.00 | 0.00 |
April | 0.351618E+10 | 0.00 | 0.641471E+10 | 0.338170E+10 | 0.00 | 0.00 |
May | 0.631431E+09 | 0.00 | 0.124175E+11 | 0.437179E+10 | 0.00 | 0.00 |
June | 23109659.92 | 0.00 | 0.239406E+11 | 0.542985E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.436262E+11 | 0.665806E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.576274E+11 | 0.744291E+10 | 0.00 | 0.00 |
September | 0.264231E+09 | 0.00 | 0.188152E+11 | 0.450593E+10 | 0.00 | 0.00 |
October | 0.433522E+10 | 0.00 | 0.249041E+10 | 0.306235E+10 | 0.00 | 0.00 |
November | 0.191160E+11 | 0.00 | 0.470360E+09 | 0.271468E+10 | 0.00 | 0.00 |
December | 0.348348E+11 | 0.00 | 27294.25 | 0.301494E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.140164E+12 | 0.00 | 0.166692E+12 | 0.499454E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 27294.25 | 0.271468E+10 | 0.00 | 0.00 |
Maximum of Months | 0.417754E+11 | 0.00 | 0.576274E+11 | 0.744291E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 2162289.83 | 0.124354E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.406424E+09 | 0.111715E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 76295979.78 | 0.132805E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.340122E+10 | 0.123288E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.667136E+10 | 0.129350E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.138690E+11 | 0.131231E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.260690E+11 | 0.126136E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.361155E+11 | 0.138420E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.107769E+11 | 0.129116E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.149271E+10 | 0.129757E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.219622E+09 | 0.123097E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 4719538.84 | 0.121602E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.991049E+11 | 0.152087E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 2162289.83 | 0.111715E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.361155E+11 | 0.138420E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.467695E+10 | 0.238179E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.104912E+11 | 0.324437E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.183463E+11 | 0.467772E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.238782E+11 | 0.546183E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.667773E+10 | 0.272391E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.126652E+11 | 0.370101E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.195257E+11 | 0.494716E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.256349E+11 | 0.602579E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.667149E+10 | 0.266363E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.124638E+11 | 0.368267E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.175769E+11 | 0.445682E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.239564E+11 | 0.554442E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.182565E+12 | 0.495111E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.467695E+10 | 0.238179E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.256349E+11 | 0.602579E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.142751E+11 | 0.171025E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.772408E+11 | 0.270687E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.157777E+12 | 0.419249E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.217584E+12 | 0.506183E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.562860E+11 | 0.247172E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.115641E+12 | 0.344900E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.183599E+12 | 0.468109E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.242624E+12 | 0.572354E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.569268E+11 | 0.242765E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.104289E+12 | 0.327592E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.145128E+12 | 0.389960E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.198854E+12 | 0.484129E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157022E+13 | 0.444412E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.142751E+11 | 0.171025E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.242624E+12 | 0.572354E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.344029E+09 | 0.150815E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.573654E+10 | 0.237489E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.139783E+11 | 0.392627E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.206996E+11 | 0.492971E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.494754E+10 | 0.237522E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.112855E+11 | 0.342865E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.182416E+11 | 0.469254E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.240903E+11 | 0.573060E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.497965E+10 | 0.232654E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.881380E+10 | 0.302936E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.124229E+11 | 0.358654E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.176139E+11 | 0.451306E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143154E+12 | 0.424215E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.344029E+09 | 0.150815E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.240903E+11 | 0.573060E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.331541E+10 | 483.95 | 0.754555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.380404E+10 | 0.673873E+09 | 0.426198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.602934E+10 | 0.878860E+09 | 0.669043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.779093E+10 | 0.873833E+10 | 0.155287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.696623E+10 | 0.141854E+11 | 29527767.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.863929E+10 | 0.279831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.106031E+11 | 0.515590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124830E+11 | 0.716939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.710374E+10 | 0.219998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.595888E+10 | 0.397142E+10 | 31724102.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.471031E+10 | 0.566748E+09 | 0.138659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.456993E+10 | 361.45 | 0.367855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.819742E+11 | 0.202250E+12 | 0.177582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.331541E+10 | 361.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124830E+11 | 0.716939E+11 | 0.754555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.274186E+11 | 53644.70 | 0.220172E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.260011E+11 | 0.387504E+10 | 0.113777E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.343296E+11 | 0.582521E+10 | 0.320491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.395050E+11 | 0.632318E+11 | 0.100337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.507033E+11 | 0.120778E+12 | 0.107078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.585239E+11 | 0.224631E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677583E+11 | 0.400717E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.775047E+11 | 0.537500E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.536799E+11 | 0.192594E+12 | 41609080.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.374000E+11 | 0.300181E+11 | 0.570358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.271863E+11 | 0.482927E+10 | 0.704905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271327E+11 | 47343.63 | 0.159821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.527144E+12 | 0.158400E+13 | 0.613159E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.260011E+11 | 47343.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.775047E+11 | 0.537500E+12 | 0.220172E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.340061E+10 | 129393.08 | 0.417754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.284629E+10 | 0.356705E+09 | 0.248064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311627E+10 | 0.532686E+09 | 0.108613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.338170E+10 | 0.641471E+10 | 0.351618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.437179E+10 | 0.124175E+11 | 0.631431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.542985E+10 | 0.239406E+11 | 23109659.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.665806E+10 | 0.436262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.744291E+10 | 0.576274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.450593E+10 | 0.188152E+11 | 0.264231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.306235E+10 | 0.249041E+10 | 0.433522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.271468E+10 | 0.470360E+09 | 0.191160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.301494E+10 | 27294.25 | 0.348348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.499454E+11 | 0.166692E+12 | 0.140164E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.271468E+10 | 27294.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.744291E+10 | 0.576274E+11 | 0.417754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.124354E+11 | 2162289.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111715E+11 | 0.406424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132805E+11 | 76295979.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123288E+11 | 0.340122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129350E+11 | 0.667136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131231E+11 | 0.138690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.126136E+11 | 0.260690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138420E+11 | 0.361155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129116E+11 | 0.107769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129757E+11 | 0.149271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123097E+11 | 0.219622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121602E+11 | 4719538.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152087E+12 | 0.991049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111715E+11 | 2162289.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138420E+11 | 0.361155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147304E+10 | 0.376820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133049E+10 | 0.857729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147304E+10 | 0.151416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142552E+10 | 0.198419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147304E+10 | 0.542685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142552E+10 | 0.103897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147304E+10 | 0.160516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147304E+10 | 0.210822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142552E+10 | 0.543338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147304E+10 | 0.102542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142552E+10 | 0.145456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147304E+10 | 0.198850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173439E+11 | 0.150397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133049E+10 | 0.376820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147304E+10 | 0.210822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140788E+11 | 0.112514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127163E+11 | 0.628885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140788E+11 | 0.129931E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136246E+11 | 0.180591E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140788E+11 | 0.456476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136246E+11 | 0.947754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140788E+11 | 0.150867E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140788E+11 | 0.199467E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136246E+11 | 0.462750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140788E+11 | 0.856084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136246E+11 | 0.119756E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140788E+11 | 0.164520E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165766E+12 | 0.129158E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127163E+11 | 0.112514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140788E+11 | 0.199467E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143070E+10 | 0.266580E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129224E+10 | 0.465390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143070E+10 | 0.114827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138455E+10 | 0.171545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143070E+10 | 0.400302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138455E+10 | 0.924144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143070E+10 | 0.149798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143070E+10 | 0.197904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138455E+10 | 0.403765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143070E+10 | 0.721514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138455E+10 | 0.102210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143070E+10 | 0.145316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168453E+11 | 0.117578E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129224E+10 | 0.266580E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143070E+10 | 0.197904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.331541E+10 | 0.754555E+10 | 483.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.380404E+10 | 0.426198E+10 | 0.673873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.602934E+10 | 0.669043E+09 | 0.878860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.779093E+10 | 0.155287E+09 | 0.873833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.696623E+10 | 29527767.96 | 0.141854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.863929E+10 | 0.00 | 0.279831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.106031E+11 | 0.00 | 0.515590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124830E+11 | 0.00 | 0.716939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.710374E+10 | 0.00 | 0.219998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.595888E+10 | 31724102.16 | 0.397142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.471031E+10 | 0.138659E+10 | 0.566748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.456993E+10 | 0.367855E+10 | 361.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.819742E+11 | 0.177582E+11 | 0.202250E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.331541E+10 | 0.00 | 361.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124830E+11 | 0.754555E+10 | 0.716939E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.274186E+11 | 0.220172E+12 | 53644.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.260011E+11 | 0.113777E+12 | 0.387504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.343296E+11 | 0.320491E+11 | 0.582521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.395050E+11 | 0.100337E+11 | 0.632318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.507033E+11 | 0.107078E+10 | 0.120778E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.585239E+11 | 0.00 | 0.224631E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.677583E+11 | 0.00 | 0.400717E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.775047E+11 | 0.00 | 0.537500E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.536799E+11 | 41609080.77 | 0.192594E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.374000E+11 | 0.570358E+10 | 0.300181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.271863E+11 | 0.704905E+11 | 0.482927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.271327E+11 | 0.159821E+12 | 47343.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.527144E+12 | 0.613159E+12 | 0.158400E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.260011E+11 | 0.00 | 47343.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.775047E+11 | 0.220172E+12 | 0.537500E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.340061E+10 | 0.417754E+11 | 129393.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.284629E+10 | 0.248064E+11 | 0.356705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311627E+10 | 0.108613E+11 | 0.532686E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.338170E+10 | 0.351618E+10 | 0.641471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.437179E+10 | 0.631431E+09 | 0.124175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.542985E+10 | 23109659.92 | 0.239406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.665806E+10 | 0.00 | 0.436262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.744291E+10 | 0.00 | 0.576274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.450593E+10 | 0.264231E+09 | 0.188152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.306235E+10 | 0.433522E+10 | 0.249041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.271468E+10 | 0.191160E+11 | 0.470360E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.301494E+10 | 0.348348E+11 | 27294.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.499454E+11 | 0.140164E+12 | 0.166692E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.271468E+10 | 0.00 | 27294.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.744291E+10 | 0.417754E+11 | 0.576274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.124354E+11 | 0.00 | 2162289.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111715E+11 | 0.00 | 0.406424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132805E+11 | 0.00 | 76295979.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123288E+11 | 0.00 | 0.340122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129350E+11 | 0.00 | 0.667136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131231E+11 | 0.00 | 0.138690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.126136E+11 | 0.00 | 0.260690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138420E+11 | 0.00 | 0.361155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129116E+11 | 0.00 | 0.107769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129757E+11 | 0.00 | 0.149271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123097E+11 | 0.00 | 0.219622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121602E+11 | 0.00 | 4719538.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152087E+12 | 0.00 | 0.991049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111715E+11 | 0.00 | 2162289.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138420E+11 | 0.00 | 0.361155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147304E+10 | 0.00 | 0.467695E+10 | 0.00 | 0.908750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133049E+10 | 0.00 | 0.104912E+11 | 0.00 | 0.191388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147304E+10 | 0.00 | 0.183463E+11 | 0.00 | 0.320468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142552E+10 | 0.00 | 0.238782E+11 | 0.00 | 0.403631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147304E+10 | 0.00 | 0.667773E+10 | 0.00 | 0.125087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142552E+10 | 0.00 | 0.126652E+11 | 0.00 | 0.227549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147304E+10 | 0.00 | 0.195257E+11 | 0.00 | 0.347412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147304E+10 | 0.00 | 0.256349E+11 | 0.00 | 0.455275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142552E+10 | 0.00 | 0.667149E+10 | 0.00 | 0.123811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147304E+10 | 0.00 | 0.124638E+11 | 0.00 | 0.220963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142552E+10 | 0.00 | 0.175769E+11 | 0.00 | 0.303130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147304E+10 | 0.00 | 0.239564E+11 | 0.00 | 0.407138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173439E+11 | 0.00 | 0.182565E+12 | 0.00 | 0.321673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133049E+10 | 0.00 | 0.467695E+10 | 0.00 | 0.908750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147304E+10 | 0.00 | 0.256349E+11 | 0.00 | 0.455275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140788E+11 | 0.00 | 0.142751E+11 | 0.00 | 0.302374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127163E+11 | 0.00 | 0.772408E+11 | 0.00 | 0.143523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140788E+11 | 0.00 | 0.157777E+12 | 0.00 | 0.278461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136246E+11 | 0.00 | 0.217584E+12 | 0.00 | 0.369937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140788E+11 | 0.00 | 0.562860E+11 | 0.00 | 0.106384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136246E+11 | 0.00 | 0.115641E+12 | 0.00 | 0.208653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140788E+11 | 0.00 | 0.183599E+12 | 0.00 | 0.327321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140788E+11 | 0.00 | 0.242624E+12 | 0.00 | 0.431566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136246E+11 | 0.00 | 0.569268E+11 | 0.00 | 0.106518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140788E+11 | 0.00 | 0.104289E+12 | 0.00 | 0.186804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136246E+11 | 0.00 | 0.145128E+12 | 0.00 | 0.253713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140788E+11 | 0.00 | 0.198854E+12 | 0.00 | 0.343341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165766E+12 | 0.00 | 0.157022E+13 | 0.00 | 0.278646E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127163E+11 | 0.00 | 0.142751E+11 | 0.00 | 0.302374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140788E+11 | 0.00 | 0.242624E+12 | 0.00 | 0.431566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.143070E+10 | 0.00 | 0.344029E+09 | 0.00 | 77448966.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129224E+10 | 0.00 | 0.573654E+10 | 0.00 | 0.108264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143070E+10 | 0.00 | 0.139783E+11 | 0.00 | 0.249557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138455E+10 | 0.00 | 0.206996E+11 | 0.00 | 0.354517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143070E+10 | 0.00 | 0.494754E+10 | 0.00 | 0.944522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138455E+10 | 0.00 | 0.112855E+11 | 0.00 | 0.204411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143070E+10 | 0.00 | 0.182416E+11 | 0.00 | 0.326184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143070E+10 | 0.00 | 0.240903E+11 | 0.00 | 0.429990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138455E+10 | 0.00 | 0.497965E+10 | 0.00 | 0.941997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143070E+10 | 0.00 | 0.881380E+10 | 0.00 | 0.159867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138455E+10 | 0.00 | 0.124229E+11 | 0.00 | 0.220199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143070E+10 | 0.00 | 0.176139E+11 | 0.00 | 0.308236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168453E+11 | 0.00 | 0.143154E+12 | 0.00 | 0.255762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129224E+10 | 0.00 | 0.344029E+09 | 0.00 | 77448966.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143070E+10 | 0.00 | 0.240903E+11 | 0.00 | 0.429990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.216922E+10 | 0.00 | 0.00 | 83952581.67 | 0.00 | 0.00 | 0.558015E+11 | 0.00 | 0.48 |
February | 0.153771E+10 | 0.00 | 0.00 | 80113251.19 | 0.00 | 0.00 | 0.531588E+11 | 0.00 | 0.58 |
March | 0.708932E+09 | 0.00 | 0.00 | 0.100083E+09 | 0.00 | 0.00 | 0.683975E+11 | 0.00 | 0.75 |
April | 0.523044E+09 | 16160313.66 | 0.00 | 94946995.68 | 301772.00 | 0.00 | 0.616594E+11 | 0.00 | 0.83 |
May | 0.425942E+09 | 11734229.88 | 0.00 | 98269705.50 | 0.00 | 0.00 | 0.612139E+11 | 0.00 | 1.02 |
June | 0.246447E+09 | 9811434.82 | 0.00 | 0.103415E+09 | 598900.57 | 0.00 | 0.566114E+11 | 0.00 | 1.23 |
July | 0.249722E+09 | 0.210371E+09 | 0.00 | 0.100495E+09 | 4146999.73 | 0.00 | 0.440048E+11 | 0.00 | 1.17 |
August | 0.213637E+09 | 0.407917E+09 | 0.00 | 0.105106E+09 | 869802.29 | 0.00 | 0.416936E+11 | 0.00 | 1.16 |
September | 0.407041E+09 | 0.00 | 0.00 | 0.103913E+09 | 0.00 | 0.00 | 0.569737E+11 | 0.00 | 1.17 |
October | 0.525820E+09 | 0.00 | 0.00 | 0.106639E+09 | 0.00 | 0.00 | 0.675012E+11 | 0.00 | 0.91 |
November | 0.816770E+09 | 0.00 | 0.00 | 0.102008E+09 | 0.00 | 0.00 | 0.649872E+11 | 0.00 | 0.70 |
December | 0.144796E+10 | 0.00 | 0.00 | 98205454.99 | 0.00 | 0.00 | 0.620237E+11 | 0.00 | 0.55 |
Annual Sum or Average | 0.927225E+10 | 0.655994E+09 | 0.00 | 0.117715E+10 | 5917474.60 | 0.00 | 0.694027E+12 | 0.00 | 0.88 |
Minimum of Months | 0.213637E+09 | 0.00 | 0.00 | 80113251.19 | 0.00 | 0.00 | 0.416936E+11 | 0.00 | 0.48 |
Maximum of Months | 0.216922E+10 | 0.407917E+09 | 0.00 | 0.106639E+09 | 4146999.73 | 0.00 | 0.683975E+11 | 0.00 | 1.23 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107317E+11 | 0.00 | 0.00 | 40706581.38 | 0.00 | 0.00 | 0.323626E+11 | 0.00 | 0.34 |
February | 0.397068E+10 | 0.00 | 0.00 | 52389509.60 | 0.00 | 0.00 | 0.386874E+11 | 0.00 | 0.43 |
March | 0.422132E+10 | 0.00 | 0.00 | 80016575.93 | 0.00 | 0.00 | 0.528833E+11 | 0.00 | 0.59 |
April | 0.791963E+10 | 14528132.34 | 0.00 | 77618460.41 | 443081.97 | 0.00 | 0.496143E+11 | 0.00 | 0.74 |
May | 0.572332E+10 | 529957.95 | 0.00 | 74720639.09 | 0.00 | 0.00 | 0.451870E+11 | 0.00 | 0.78 |
June | 0.638149E+10 | 15778741.09 | 0.00 | 80891905.57 | 5030878.18 | 0.00 | 0.429206E+11 | 0.00 | 0.95 |
July | 0.121581E+11 | 0.180842E+09 | 0.00 | 73207926.66 | 12298679.75 | 0.00 | 0.316347E+11 | 0.00 | 1.00 |
August | 0.121053E+11 | 0.676601E+09 | 0.00 | 74419651.95 | 6620832.17 | 0.00 | 0.299054E+11 | 0.00 | 1.05 |
September | 0.515456E+10 | 0.00 | 0.00 | 73661693.13 | 0.00 | 0.00 | 0.394157E+11 | 0.00 | 0.83 |
October | 0.467164E+10 | 0.00 | 0.00 | 75246903.73 | 0.00 | 0.00 | 0.481527E+11 | 0.00 | 0.67 |
November | 0.420018E+10 | 0.00 | 0.00 | 71507403.62 | 0.00 | 0.00 | 0.469253E+11 | 0.00 | 0.52 |
December | 0.400175E+10 | 0.00 | 0.00 | 71066304.89 | 0.00 | 0.00 | 0.462600E+11 | 0.00 | 0.42 |
Annual Sum or Average | 0.812397E+11 | 0.888280E+09 | 0.00 | 0.845454E+09 | 24393472.08 | 0.00 | 0.503949E+12 | 0.00 | 0.70 |
Minimum of Months | 0.397068E+10 | 0.00 | 0.00 | 40706581.38 | 0.00 | 0.00 | 0.299054E+11 | 0.00 | 0.34 |
Maximum of Months | 0.121581E+11 | 0.676601E+09 | 0.00 | 80891905.57 | 12298679.75 | 0.00 | 0.528833E+11 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.308099E+12 | 0.00 | 0.00 | 9876713.98 | 0.00 | 0.217410E+10 | 0.257148E+11 | 0.00 | 0.29 |
February | 0.212929E+12 | 0.00 | 0.00 | 74568573.83 | 0.00 | 0.00 | 0.908195E+11 | 0.00 | 0.32 |
March | 0.144858E+12 | 0.00 | 0.00 | 0.280233E+09 | 0.00 | 0.00 | 0.224504E+12 | 0.00 | 0.39 |
April | 0.962409E+11 | 0.140802E+09 | 0.00 | 0.344918E+09 | 96559355.63 | 0.00 | 0.252750E+12 | 0.00 | 0.46 |
May | 0.618494E+11 | 8157855.22 | 0.00 | 0.495154E+09 | 476245.57 | 0.00 | 0.337245E+12 | 0.00 | 0.63 |
June | 0.387764E+11 | 0.127622E+09 | 0.00 | 0.565467E+09 | 42511510.25 | 0.00 | 0.329335E+12 | 0.00 | 0.73 |
July | 0.433409E+11 | 0.132566E+10 | 0.00 | 0.536373E+09 | 0.156575E+09 | 0.00 | 0.243707E+12 | 0.00 | 0.70 |
August | 0.343216E+11 | 0.555971E+10 | 0.00 | 0.554995E+09 | 63566442.79 | 0.00 | 0.228436E+12 | 0.00 | 0.70 |
September | 0.503936E+11 | 0.00 | 0.00 | 0.501425E+09 | 0.00 | 0.00 | 0.295332E+12 | 0.00 | 0.66 |
October | 0.100622E+12 | 0.00 | 0.00 | 0.346969E+09 | 0.00 | 0.00 | 0.257375E+12 | 0.00 | 0.47 |
November | 0.166301E+12 | 0.00 | 0.00 | 0.158428E+09 | 0.00 | 0.00 | 0.154076E+12 | 0.00 | 0.33 |
December | 0.252897E+12 | 0.00 | 0.00 | 55434128.81 | 0.00 | 30339082.38 | 0.762361E+11 | 0.00 | 0.29 |
Annual Sum or Average | 0.151063E+13 | 0.716195E+10 | 0.00 | 0.392384E+10 | 0.359689E+09 | 0.220444E+10 | 0.251553E+13 | 0.00 | 0.50 |
Minimum of Months | 0.343216E+11 | 0.00 | 0.00 | 9876713.98 | 0.00 | 0.00 | 0.257148E+11 | 0.00 | 0.29 |
Maximum of Months | 0.308099E+12 | 0.555971E+10 | 0.00 | 0.565467E+09 | 0.156575E+09 | 0.217410E+10 | 0.337245E+12 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.277541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272251E+10 | 0.00 | 0.00 | 0.29 |
February | 0.254876E+11 | 0.00 | 0.00 | 327023.54 | 0.00 | 0.113825E+10 | 0.514134E+09 | 0.00 | 0.31 |
March | 0.264183E+11 | 0.00 | 0.00 | 2772307.01 | 0.00 | 0.235753E+09 | 0.444019E+10 | 0.00 | 0.35 |
April | 0.162307E+11 | 1732469.72 | 0.00 | 15319338.56 | 5601196.14 | 1650440.21 | 0.136411E+11 | 0.00 | 0.41 |
May | 0.113840E+11 | 0.00 | 0.00 | 33080955.91 | 0.00 | 0.00 | 0.246622E+11 | 0.00 | 0.58 |
June | 0.789400E+10 | 4488743.63 | 0.00 | 46207026.71 | 2637522.91 | 0.00 | 0.275447E+11 | 0.00 | 0.72 |
July | 0.584927E+10 | 89179079.20 | 0.00 | 49519196.16 | 9268824.52 | 0.00 | 0.225759E+11 | 0.00 | 0.71 |
August | 0.493160E+10 | 0.402466E+09 | 0.00 | 48717112.22 | 11082910.04 | 0.00 | 0.194837E+11 | 0.00 | 0.68 |
September | 0.111601E+11 | 0.00 | 0.00 | 30455335.58 | 0.00 | 0.00 | 0.180704E+11 | 0.00 | 0.60 |
October | 0.193300E+11 | 0.00 | 0.00 | 8665149.96 | 0.00 | 84303455.12 | 0.863440E+10 | 0.00 | 0.39 |
November | 0.249759E+11 | 0.00 | 0.00 | 366099.21 | 43458.31 | 0.810614E+09 | 0.114237E+10 | 0.00 | 0.31 |
December | 0.270617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192503E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.208477E+12 | 0.497867E+09 | 0.00 | 0.235430E+09 | 28633911.92 | 0.691812E+10 | 0.140709E+12 | 0.00 | 0.47 |
Minimum of Months | 0.493160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.277541E+11 | 0.402466E+09 | 0.00 | 49519196.16 | 11082910.04 | 0.272251E+10 | 0.275447E+11 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.440581E+10 | 0.00 | 0.00 | 2325.59 | 0.00 | 0.00 | 27539122.69 | 0.00 | 0.28 |
February | 0.350706E+10 | 0.00 | 0.00 | 542646.13 | 0.00 | 0.00 | 0.559053E+09 | 0.00 | 0.33 |
March | 0.257288E+10 | 0.00 | 0.00 | 2803107.45 | 0.00 | 0.00 | 0.255055E+10 | 0.00 | 0.43 |
April | 0.197342E+10 | 2139994.36 | 0.00 | 5058149.62 | 55643.15 | 0.00 | 0.386995E+10 | 0.00 | 0.62 |
May | 0.136064E+10 | 118275.47 | 0.00 | 6808336.70 | 0.00 | 0.00 | 0.459439E+10 | 0.00 | 0.76 |
June | 0.983214E+09 | 2699116.73 | 0.00 | 9385623.78 | 631788.08 | 0.00 | 0.515327E+10 | 0.00 | 1.00 |
July | 0.158957E+10 | 32069834.07 | 0.00 | 9629782.30 | 972693.32 | 0.00 | 0.411784E+10 | 0.00 | 1.10 |
August | 0.158503E+10 | 0.114634E+09 | 0.00 | 9004918.67 | 788632.79 | 0.00 | 0.359490E+10 | 0.00 | 1.09 |
September | 0.142001E+10 | 0.00 | 0.00 | 5660003.84 | 0.00 | 0.00 | 0.335513E+10 | 0.00 | 0.74 |
October | 0.220692E+10 | 0.00 | 0.00 | 3184670.88 | 0.00 | 0.00 | 0.268094E+10 | 0.00 | 0.50 |
November | 0.295372E+10 | 0.00 | 0.00 | 1324579.34 | 0.00 | 0.00 | 0.145907E+10 | 0.00 | 0.36 |
December | 0.399689E+10 | 0.00 | 0.00 | 193525.17 | 0.00 | 0.00 | 0.357843E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.285552E+11 | 0.151661E+09 | 0.00 | 53597669.47 | 2448757.34 | 0.00 | 0.323205E+11 | 0.00 | 0.63 |
Minimum of Months | 0.983214E+09 | 0.00 | 0.00 | 2325.59 | 0.00 | 0.00 | 27539122.69 | 0.00 | 0.28 |
Maximum of Months | 0.440581E+10 | 0.114634E+09 | 0.00 | 9629782.30 | 972693.32 | 0.00 | 0.515327E+10 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.398472E+10 | 0.00 | 0.00 | 2005.80 | 0.00 | 6506067.33 | 5325877.68 | 0.00 | 0.39 |
February | 0.318331E+10 | 0.00 | 0.00 | 487287.92 | 0.00 | 566057.77 | 0.455248E+09 | 0.00 | 0.45 |
March | 0.262043E+10 | 0.00 | 0.00 | 2304057.99 | 0.00 | 0.00 | 0.201843E+10 | 0.00 | 0.59 |
April | 0.195889E+10 | 1692180.45 | 0.00 | 4895296.98 | 50160.97 | 0.00 | 0.353110E+10 | 0.00 | 0.90 |
May | 0.139834E+10 | 95859.15 | 0.00 | 6536869.09 | 0.00 | 0.00 | 0.415026E+10 | 0.00 | 1.09 |
June | 0.104996E+10 | 1741767.50 | 0.00 | 8918611.75 | 569541.83 | 0.00 | 0.492243E+10 | 0.00 | 1.46 |
July | 0.159291E+10 | 25116418.30 | 0.00 | 8562901.20 | 715879.38 | 0.00 | 0.354897E+10 | 0.00 | 1.51 |
August | 0.164446E+10 | 87878021.62 | 0.00 | 8243760.39 | 374786.24 | 0.00 | 0.309828E+10 | 0.00 | 1.54 |
September | 0.144183E+10 | 0.00 | 0.00 | 5962074.89 | 0.00 | 0.00 | 0.326748E+10 | 0.00 | 1.13 |
October | 0.240459E+10 | 0.00 | 0.00 | 2753790.57 | 0.00 | 0.00 | 0.214616E+10 | 0.00 | 0.72 |
November | 0.338104E+10 | 0.00 | 0.00 | 370692.31 | 0.00 | 0.00 | 0.485478E+09 | 0.00 | 0.48 |
December | 0.383269E+10 | 0.00 | 0.00 | 86275.21 | 0.00 | 0.00 | 97011447.45 | 0.00 | 0.40 |
Annual Sum or Average | 0.284932E+11 | 0.116524E+09 | 0.00 | 49123624.10 | 1710368.42 | 7072125.10 | 0.277262E+11 | 0.00 | 0.89 |
Minimum of Months | 0.104996E+10 | 0.00 | 0.00 | 2005.80 | 0.00 | 0.00 | 5325877.68 | 0.00 | 0.39 |
Maximum of Months | 0.398472E+10 | 87878021.62 | 0.00 | 8918611.75 | 715879.38 | 6506067.33 | 0.492243E+10 | 0.00 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.485608E+10 | 0.00 | 0.00 | 1080653.76 | 0.00 | 0.167800E+09 | 0.907893E+09 | 0.00 | 0.37 |
February | 0.379796E+10 | 0.00 | 0.00 | 3394511.02 | 0.00 | 30331172.97 | 0.258536E+10 | 0.00 | 0.53 |
March | 0.331479E+10 | 0.00 | 0.00 | 6944907.37 | 0.00 | 0.00 | 0.552967E+10 | 0.00 | 0.76 |
April | 0.260636E+10 | 5397641.50 | 0.00 | 8980812.16 | 19961.75 | 0.00 | 0.633434E+10 | 0.00 | 1.01 |
May | 0.201080E+10 | 213634.58 | 0.00 | 9835478.21 | 0.00 | 0.00 | 0.614673E+10 | 0.00 | 1.09 |
June | 0.161236E+10 | 3257522.02 | 0.00 | 11086677.22 | 802593.63 | 0.00 | 0.592355E+10 | 0.00 | 1.28 |
July | 0.214268E+10 | 53656986.79 | 0.00 | 12336099.69 | 653500.90 | 0.00 | 0.501520E+10 | 0.00 | 1.46 |
August | 0.215771E+10 | 0.207762E+09 | 0.00 | 12758192.59 | 122890.92 | 0.00 | 0.443874E+10 | 0.00 | 1.50 |
September | 0.179133E+10 | 0.00 | 0.00 | 13334388.27 | 0.00 | 0.00 | 0.615064E+10 | 0.00 | 1.40 |
October | 0.277440E+10 | 0.00 | 0.00 | 8489815.12 | 0.00 | 0.00 | 0.598167E+10 | 0.00 | 0.96 |
November | 0.402374E+10 | 0.00 | 0.00 | 2625071.56 | 0.00 | 0.00 | 0.211573E+10 | 0.00 | 0.51 |
December | 0.453105E+10 | 0.00 | 0.00 | 2465101.37 | 0.00 | 23854049.99 | 0.190822E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.356193E+11 | 0.270288E+09 | 0.00 | 93331708.33 | 1598947.20 | 0.221985E+09 | 0.530377E+11 | 0.00 | 0.94 |
Minimum of Months | 0.161236E+10 | 0.00 | 0.00 | 1080653.76 | 0.00 | 0.00 | 0.907893E+09 | 0.00 | 0.37 |
Maximum of Months | 0.485608E+10 | 0.207762E+09 | 0.00 | 13334388.27 | 802593.63 | 0.167800E+09 | 0.633434E+10 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.454952E+10 | 0.00 | 0.00 | 250459.26 | 0.00 | 0.00 | 0.371150E+09 | 0.00 | 0.48 |
February | 0.219825E+10 | 0.00 | 0.00 | 2780483.52 | 0.00 | 0.00 | 0.270953E+10 | 0.00 | 0.63 |
March | 0.744416E+09 | 0.00 | 0.00 | 8904421.76 | 0.00 | 0.00 | 0.669189E+10 | 0.00 | 0.99 |
April | 0.670877E+09 | 4027521.89 | 0.00 | 14161946.45 | 0.00 | 0.00 | 0.848933E+10 | 0.00 | 1.57 |
May | 0.843802E+09 | 130221.21 | 0.00 | 12144532.12 | 0.00 | 0.00 | 0.631538E+10 | 0.00 | 1.51 |
June | 0.611520E+09 | 7312472.85 | 0.00 | 14967219.25 | 625393.70 | 0.00 | 0.683849E+10 | 0.00 | 1.99 |
July | 0.960209E+09 | 64081024.39 | 0.00 | 19087393.39 | 64424.32 | 0.00 | 0.665178E+10 | 0.00 | 2.43 |
August | 0.811804E+09 | 0.201065E+09 | 0.00 | 19988930.91 | 404224.60 | 0.00 | 0.639047E+10 | 0.00 | 2.41 |
September | 0.690681E+09 | 0.00 | 0.00 | 10676001.71 | 0.00 | 0.00 | 0.520302E+10 | 0.00 | 1.54 |
October | 0.973239E+09 | 0.00 | 0.00 | 7215785.06 | 0.00 | 0.00 | 0.537532E+10 | 0.00 | 1.05 |
November | 0.111648E+10 | 0.00 | 0.00 | 5577285.43 | 0.00 | 0.00 | 0.447435E+10 | 0.00 | 0.72 |
December | 0.979349E+09 | 0.00 | 0.00 | 5576107.98 | 0.00 | 0.00 | 0.471975E+10 | 0.00 | 0.59 |
Annual Sum or Average | 0.151502E+11 | 0.276616E+09 | 0.00 | 0.121331E+09 | 1094042.61 | 0.00 | 0.642305E+11 | 0.00 | 1.33 |
Minimum of Months | 0.611520E+09 | 0.00 | 0.00 | 250459.26 | 0.00 | 0.00 | 0.371150E+09 | 0.00 | 0.48 |
Maximum of Months | 0.454952E+10 | 0.201065E+09 | 0.00 | 19988930.91 | 625393.70 | 0.00 | 0.848933E+10 | 0.00 | 2.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.209998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215054E+11 | 0.00 | 0.00 | 0.29 |
February | 0.281545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961702E+10 | 0.00 | 0.00 | 0.31 |
March | 0.396637E+11 | 0.00 | 0.00 | 112166.46 | 0.00 | 0.196941E+10 | 0.329529E+09 | 0.00 | 0.35 |
April | 0.292721E+11 | 19978052.11 | 0.00 | 9462941.67 | 12149008.07 | 27059304.00 | 0.793457E+10 | 0.00 | 0.39 |
May | 0.191680E+11 | 1556875.03 | 0.00 | 37636869.93 | 0.00 | 0.00 | 0.255808E+11 | 0.00 | 0.59 |
June | 0.113350E+11 | 22442268.35 | 0.00 | 58089965.53 | 5348758.57 | 0.00 | 0.322703E+11 | 0.00 | 0.74 |
July | 0.974704E+10 | 0.240154E+09 | 0.00 | 63111543.21 | 19700171.35 | 0.00 | 0.265877E+11 | 0.00 | 0.76 |
August | 0.917300E+10 | 0.972671E+09 | 0.00 | 55050158.82 | 7997870.55 | 0.00 | 0.218050E+11 | 0.00 | 0.70 |
September | 0.201891E+11 | 0.00 | 0.00 | 28558551.87 | 0.00 | 0.00 | 0.162151E+11 | 0.00 | 0.58 |
October | 0.339940E+11 | 0.00 | 0.00 | 3659777.12 | 0.00 | 0.235606E+09 | 0.392278E+10 | 0.00 | 0.39 |
November | 0.331733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541266E+10 | 0.00 | 0.00 | 0.32 |
December | 0.250314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163140E+11 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.279901E+12 | 0.125680E+10 | 0.00 | 0.255682E+09 | 45195808.55 | 0.550812E+11 | 0.134646E+12 | 0.00 | 0.48 |
Minimum of Months | 0.917300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.396637E+11 | 0.972671E+09 | 0.00 | 63111543.21 | 19700171.35 | 0.215054E+11 | 0.322703E+11 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.202595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202873E+11 | 0.00 | 0.00 | 0.43 |
February | 0.282677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784264E+10 | 0.00 | 0.00 | 0.47 |
March | 0.335747E+11 | 0.00 | 0.00 | 6235470.55 | 0.00 | 0.139679E+10 | 0.616938E+10 | 0.00 | 0.53 |
April | 0.201425E+11 | 20267061.70 | 0.00 | 31289353.31 | 11610392.96 | 0.109224E+09 | 0.221162E+11 | 0.00 | 0.70 |
May | 0.169482E+11 | 1609667.36 | 0.00 | 50682181.86 | 0.00 | 0.00 | 0.314843E+11 | 0.00 | 0.98 |
June | 0.928252E+10 | 16878507.82 | 0.00 | 78788999.87 | 5111626.28 | 0.00 | 0.430985E+11 | 0.00 | 1.32 |
July | 0.896477E+10 | 0.232105E+09 | 0.00 | 80885318.89 | 10210257.23 | 0.00 | 0.316767E+11 | 0.00 | 1.29 |
August | 0.763801E+10 | 0.912000E+09 | 0.00 | 79542946.91 | 3469505.07 | 0.00 | 0.284482E+11 | 0.00 | 1.28 |
September | 0.185783E+11 | 0.00 | 0.00 | 46449879.68 | 0.00 | 0.00 | 0.233071E+11 | 0.00 | 1.04 |
October | 0.277258E+11 | 0.00 | 0.00 | 13235977.42 | 0.00 | 0.272896E+09 | 0.108948E+11 | 0.00 | 0.62 |
November | 0.317131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518247E+10 | 0.00 | 0.00 | 0.47 |
December | 0.240279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155068E+11 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.247123E+12 | 0.118286E+10 | 0.00 | 0.387110E+09 | 30401781.53 | 0.505981E+11 | 0.197195E+12 | 0.00 | 0.80 |
Minimum of Months | 0.763801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.335747E+11 | 0.912000E+09 | 0.00 | 80885318.89 | 11610392.96 | 0.202873E+11 | 0.430985E+11 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.365026E+11 | 0.00 | 0.00 | 5247539.18 | 0.00 | 0.158365E+11 | 0.486519E+10 | 0.00 | 0.39 |
February | 0.345633E+11 | 0.00 | 0.00 | 28688943.17 | 0.00 | 0.591594E+10 | 0.203192E+11 | 0.00 | 0.52 |
March | 0.366427E+11 | 0.00 | 0.00 | 54332752.29 | 0.00 | 0.776183E+09 | 0.410386E+11 | 0.00 | 0.68 |
April | 0.253328E+11 | 0.102305E+09 | 0.00 | 65054754.05 | 597132.26 | 9945931.90 | 0.445281E+11 | 0.00 | 0.80 |
May | 0.223011E+11 | 3373128.17 | 0.00 | 83014473.49 | 0.00 | 0.00 | 0.500337E+11 | 0.00 | 0.99 |
June | 0.169327E+11 | 30363853.04 | 0.00 | 88767308.08 | 7052531.68 | 0.00 | 0.455050E+11 | 0.00 | 1.09 |
July | 0.143375E+11 | 0.500388E+09 | 0.00 | 0.101297E+09 | 9590095.74 | 0.00 | 0.384219E+11 | 0.00 | 1.17 |
August | 0.113268E+11 | 0.213608E+10 | 0.00 | 0.107473E+09 | 1381003.19 | 0.00 | 0.351193E+11 | 0.00 | 1.17 |
September | 0.194864E+11 | 0.00 | 0.00 | 0.130728E+09 | 0.00 | 0.00 | 0.536007E+11 | 0.00 | 1.35 |
October | 0.294306E+11 | 0.00 | 0.00 | 74301730.18 | 0.00 | 8099537.40 | 0.494136E+11 | 0.00 | 0.89 |
November | 0.412628E+11 | 0.00 | 0.00 | 15013869.50 | 0.00 | 0.389353E+10 | 0.983082E+10 | 0.00 | 0.47 |
December | 0.352563E+11 | 0.00 | 0.00 | 14121502.15 | 0.00 | 0.131596E+11 | 0.108324E+11 | 0.00 | 0.42 |
Annual Sum or Average | 0.323375E+12 | 0.277251E+10 | 0.00 | 0.768040E+09 | 18620762.87 | 0.395998E+11 | 0.403509E+12 | 0.00 | 0.83 |
Minimum of Months | 0.113268E+11 | 0.00 | 0.00 | 5247539.18 | 0.00 | 0.00 | 0.486519E+10 | 0.00 | 0.39 |
Maximum of Months | 0.412628E+11 | 0.213608E+10 | 0.00 | 0.130728E+09 | 9590095.74 | 0.158365E+11 | 0.536007E+11 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.293064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127332E+11 | 0.00 | 0.00 | 0.45 |
February | 0.303461E+11 | 0.00 | 0.00 | 2473271.63 | 0.00 | 0.534760E+10 | 0.208312E+10 | 0.00 | 0.49 |
March | 0.351057E+11 | 0.00 | 0.00 | 9798082.80 | 0.00 | 0.174964E+09 | 0.888162E+10 | 0.00 | 0.58 |
April | 0.229644E+11 | 45061523.88 | 0.00 | 29090443.47 | 2472111.03 | 0.00 | 0.204615E+11 | 0.00 | 0.75 |
May | 0.158648E+11 | 1473140.43 | 0.00 | 74472780.40 | 0.00 | 0.00 | 0.346010E+11 | 0.00 | 1.11 |
June | 0.101638E+11 | 67977718.61 | 0.00 | 76795709.24 | 5307870.57 | 0.00 | 0.349834E+11 | 0.00 | 1.29 |
July | 0.682150E+10 | 0.541733E+09 | 0.00 | 96646857.43 | 695591.39 | 0.00 | 0.337130E+11 | 0.00 | 1.47 |
August | 0.679752E+10 | 0.160143E+10 | 0.00 | 86506543.71 | 5279609.72 | 0.00 | 0.259679E+11 | 0.00 | 1.25 |
September | 0.164833E+11 | 0.00 | 0.00 | 58402764.43 | 0.00 | 0.00 | 0.249882E+11 | 0.00 | 1.13 |
October | 0.303278E+11 | 0.00 | 0.00 | 14091970.93 | 0.00 | 2921589.66 | 0.106430E+11 | 0.00 | 0.68 |
November | 0.351356E+11 | 0.00 | 0.00 | 592682.73 | 0.00 | 0.241227E+10 | 0.732683E+09 | 0.00 | 0.49 |
December | 0.327682E+11 | 0.00 | 0.00 | 54098.71 | 0.00 | 0.809864E+10 | 0.113481E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.272085E+12 | 0.225767E+10 | 0.00 | 0.448925E+09 | 13755182.71 | 0.287696E+11 | 0.197169E+12 | 0.00 | 0.85 |
Minimum of Months | 0.679752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.351356E+11 | 0.160143E+10 | 0.00 | 96646857.43 | 5307870.57 | 0.127332E+11 | 0.349834E+11 | 0.00 | 1.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.802042E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313568E+10 | 0.00 | 0.00 | 0.29 |
February | 0.130243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216997E+10 | 0.00 | 0.00 | 0.32 |
March | 0.290524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100816E+10 | 0.00 | 0.00 | 0.35 |
April | 0.282254E+10 | 234644.37 | 0.00 | 515658.31 | 703310.87 | 0.326988E+09 | 0.408687E+09 | 0.00 | 0.39 |
May | 0.238558E+10 | 0.00 | 0.00 | 2717216.40 | 0.00 | 23417460.34 | 0.185155E+10 | 0.00 | 0.56 |
June | 0.153291E+10 | 703670.14 | 0.00 | 4940149.83 | 331179.00 | 0.00 | 0.274000E+10 | 0.00 | 0.73 |
July | 0.109060E+10 | 15352971.03 | 0.00 | 6079277.28 | 1163834.45 | 0.00 | 0.255133E+10 | 0.00 | 0.76 |
August | 0.112326E+10 | 67687626.05 | 0.00 | 5118998.19 | 1391619.02 | 0.00 | 0.181520E+10 | 0.00 | 0.69 |
September | 0.235031E+10 | 0.00 | 0.00 | 1907326.59 | 0.00 | 29529393.38 | 0.100468E+10 | 0.00 | 0.55 |
October | 0.283405E+10 | 0.00 | 0.00 | 68058.67 | 0.00 | 0.478971E+09 | 0.106298E+09 | 0.00 | 0.38 |
November | 0.162633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179395E+10 | 0.00 | 8975.03 | 0.32 |
December | 0.733377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299235E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.215087E+11 | 83978911.58 | 0.00 | 21346685.27 | 3589943.33 | 0.119590E+11 | 0.104777E+11 | 8975.03 | 0.47 |
Minimum of Months | 0.733377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.290524E+10 | 67687626.05 | 0.00 | 6079277.28 | 1391619.02 | 0.313568E+10 | 0.274000E+10 | 8975.03 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.919807E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264543E+10 | 0.00 | 0.00 | 0.41 |
February | 0.152706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163809E+10 | 0.00 | 0.00 | 0.45 |
March | 0.282889E+10 | 0.00 | 0.00 | 145911.83 | 0.00 | 0.601044E+09 | 0.182654E+09 | 0.00 | 0.50 |
April | 0.179181E+10 | 250258.28 | 0.00 | 2371482.58 | 649386.94 | 0.169870E+09 | 0.177214E+10 | 0.00 | 0.65 |
May | 0.172377E+10 | 0.00 | 0.00 | 4464203.97 | 0.00 | 27722140.53 | 0.284387E+10 | 0.00 | 0.94 |
June | 0.102184E+10 | 561896.19 | 0.00 | 7495703.00 | 305786.99 | 0.00 | 0.416298E+10 | 0.00 | 1.32 |
July | 0.877854E+09 | 14658495.15 | 0.00 | 8366839.50 | 512276.00 | 0.00 | 0.322617E+10 | 0.00 | 1.32 |
August | 0.754010E+09 | 64223572.49 | 0.00 | 7925968.71 | 587024.41 | 0.00 | 0.270996E+10 | 0.00 | 1.29 |
September | 0.176380E+10 | 0.00 | 0.00 | 4081941.58 | 0.00 | 21418409.44 | 0.203518E+10 | 0.00 | 0.99 |
October | 0.236731E+10 | 0.00 | 0.00 | 729819.93 | 0.00 | 0.347973E+09 | 0.566753E+09 | 0.00 | 0.57 |
November | 0.163604E+10 | 0.00 | 449.50 | 0.00 | 0.00 | 0.150185E+10 | 0.00 | 9439.28 | 0.45 |
December | 0.915809E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247377E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.181280E+11 | 79694222.11 | 449.50 | 35581871.09 | 2054474.34 | 0.942716E+10 | 0.174997E+11 | 9439.28 | 0.78 |
Minimum of Months | 0.754010E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.282889E+10 | 64223572.49 | 449.50 | 8366839.50 | 649386.94 | 0.264543E+10 | 0.416298E+10 | 9439.28 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.228915E+10 | 0.00 | 0.00 | 197683.01 | 0.00 | 0.288620E+10 | 0.154091E+09 | 0.00 | 0.40 |
February | 0.237014E+10 | 0.00 | 0.00 | 1717267.77 | 0.00 | 0.162553E+10 | 0.126163E+10 | 0.00 | 0.49 |
March | 0.307484E+10 | 0.00 | 0.00 | 3698938.89 | 0.00 | 0.790737E+09 | 0.288356E+10 | 0.00 | 0.62 |
April | 0.251617E+10 | 2497091.11 | 0.00 | 5233183.37 | 82843.60 | 0.326987E+09 | 0.365442E+10 | 0.00 | 0.75 |
May | 0.261102E+10 | 0.00 | 0.00 | 7138802.54 | 0.00 | 27368299.10 | 0.449505E+10 | 0.00 | 0.96 |
June | 0.203474E+10 | 989075.54 | 0.00 | 8173187.85 | 453330.81 | 0.00 | 0.436603E+10 | 0.00 | 1.10 |
July | 0.157470E+10 | 30973253.37 | 0.00 | 10394548.96 | 267300.86 | 0.00 | 0.400747E+10 | 0.00 | 1.21 |
August | 0.136034E+10 | 0.144619E+09 | 0.00 | 10826653.29 | 141500.85 | 0.00 | 0.332632E+10 | 0.00 | 1.20 |
September | 0.233572E+10 | 0.00 | 0.00 | 11683711.20 | 0.00 | 33732327.03 | 0.482309E+10 | 0.00 | 1.31 |
October | 0.266644E+10 | 0.00 | 0.00 | 5336720.50 | 0.00 | 0.392361E+09 | 0.374836E+10 | 0.00 | 0.80 |
November | 0.278486E+10 | 0.00 | 0.00 | 756989.45 | 2675.74 | 0.159949E+10 | 0.422138E+09 | 11984.42 | 0.46 |
December | 0.214577E+10 | 0.00 | 0.00 | 640847.63 | 0.00 | 0.252829E+10 | 0.478256E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.277639E+11 | 0.179078E+09 | 0.00 | 65798534.45 | 947651.85 | 0.102107E+11 | 0.336204E+11 | 11984.42 | 0.81 |
Minimum of Months | 0.136034E+10 | 0.00 | 0.00 | 197683.01 | 0.00 | 0.00 | 0.154091E+09 | 0.00 | 0.40 |
Maximum of Months | 0.307484E+10 | 0.144619E+09 | 0.00 | 11683711.20 | 453330.81 | 0.288620E+10 | 0.482309E+10 | 11984.42 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.158697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234179E+10 | 0.00 | 0.00 | 0.46 |
February | 0.208554E+10 | 0.00 | 0.00 | 111035.32 | 0.00 | 0.132463E+10 | 90080284.09 | 0.00 | 0.50 |
March | 0.310805E+10 | 0.00 | 0.00 | 552081.81 | 0.00 | 0.485940E+09 | 0.547659E+09 | 0.00 | 0.58 |
April | 0.243856E+10 | 1036517.40 | 0.00 | 2393489.10 | 202681.02 | 0.145838E+09 | 0.161125E+10 | 0.00 | 0.75 |
May | 0.201861E+10 | 0.00 | 0.00 | 6741946.72 | 0.00 | 15744273.39 | 0.305451E+10 | 0.00 | 1.10 |
June | 0.139848E+10 | 2042965.30 | 0.00 | 7155388.69 | 338812.73 | 0.00 | 0.325179E+10 | 0.00 | 1.32 |
July | 0.810341E+09 | 33245929.35 | 0.00 | 10417279.53 | 329516.00 | 0.00 | 0.344849E+10 | 0.00 | 1.52 |
August | 0.872759E+09 | 0.106784E+09 | 0.00 | 8587101.36 | 1338262.69 | 0.00 | 0.239060E+10 | 0.00 | 1.26 |
September | 0.203933E+10 | 0.00 | 0.00 | 4909208.64 | 0.00 | 662649.47 | 0.203561E+10 | 0.00 | 1.12 |
October | 0.278251E+10 | 0.00 | 0.00 | 925726.03 | 0.00 | 0.232084E+09 | 0.709384E+09 | 0.00 | 0.66 |
November | 0.238781E+10 | 0.00 | 1046.82 | 8012.94 | 1999.81 | 0.107248E+10 | 4089591.00 | 2535.97 | 0.50 |
December | 0.171728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201590E+10 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.232462E+11 | 0.143109E+09 | 1046.82 | 41801270.13 | 2211272.25 | 0.763507E+10 | 0.171435E+11 | 2535.97 | 0.85 |
Minimum of Months | 0.810341E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.310805E+10 | 0.106784E+09 | 1046.82 | 10417279.53 | 1338262.69 | 0.234179E+10 | 0.344849E+10 | 2535.97 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2706945.63 | 0.00 | 0.00 | 0.621394E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 6977115.39 | 0.00 | 0.00 | 0.514163E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 13403205.83 | 0.00 | 0.00 | 0.541607E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 16675708.00 | 0.00 | 0.00 | 0.420968E+09 | 0.00 | 0.29 |
May | 0.00 | 16367.22 | 0.00 | 3816182.72 | 0.00 | 0.00 | 0.379680E+09 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 8430717.71 | 0.00 | 0.00 | 0.295024E+09 | 0.00 | 0.30 |
July | 0.00 | 4655939.25 | 0.00 | 10925418.01 | 0.00 | 0.00 | 0.166237E+09 | 0.00 | 0.28 |
August | 0.00 | 14989029.71 | 0.00 | 14153947.50 | 0.00 | 0.00 | 0.123336E+09 | 0.00 | 0.31 |
September | 0.00 | 86735.21 | 0.00 | 3690584.88 | 0.00 | 0.00 | 0.256412E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 7947338.82 | 0.00 | 0.00 | 0.425246E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 11807371.37 | 0.00 | 0.00 | 0.495277E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16496431.69 | 0.00 | 0.00 | 0.576578E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 19748071.39 | 0.00 | 0.117031E+09 | 0.00 | 0.00 | 0.481592E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2706945.63 | 0.00 | 0.00 | 0.123336E+09 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 14989029.71 | 0.00 | 16675708.00 | 0.00 | 0.00 | 0.621394E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.816573E+09 | 0.00 | 0.00 | 8218914.74 | 0.00 | 0.00 | 0.544171E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 52932704.03 | 0.00 | 0.00 | 0.516170E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.116892E+09 | 0.00 | 0.00 | 0.543247E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.153217E+09 | 0.00 | 0.00 | 0.422158E+10 | 0.00 | 0.29 |
May | 0.00 | 134144.35 | 0.00 | 32182793.64 | 0.00 | 0.00 | 0.380953E+10 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 77612666.48 | 0.00 | 0.00 | 0.295815E+10 | 0.00 | 0.30 |
July | 0.00 | 46149555.07 | 0.00 | 0.103168E+09 | 0.00 | 0.00 | 0.166872E+10 | 0.00 | 0.28 |
August | 0.00 | 0.149242E+09 | 0.00 | 0.134362E+09 | 0.00 | 0.00 | 0.124046E+10 | 0.00 | 0.31 |
September | 0.00 | 685145.27 | 0.00 | 31327383.09 | 0.00 | 0.00 | 0.259115E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 67200686.34 | 0.00 | 0.00 | 0.426647E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 98948034.74 | 0.00 | 0.00 | 0.497188E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.139782E+09 | 0.00 | 0.00 | 0.579100E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.816573E+09 | 0.196211E+09 | 0.00 | 0.101584E+10 | 0.00 | 0.00 | 0.475548E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 8218914.74 | 0.00 | 0.00 | 0.124046E+10 | 0.00 | 0.28 |
Maximum of Months | 0.816573E+09 | 0.149242E+09 | 0.00 | 0.153217E+09 | 0.00 | 0.00 | 0.579100E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.359194E+09 | 0.00 | 0.00 | 239630.60 | 0.00 | 0.00 | 0.256316E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 4328928.44 | 0.00 | 0.00 | 0.517320E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 10580586.34 | 0.00 | 0.00 | 0.544489E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 14695361.19 | 0.00 | 0.00 | 0.422892E+09 | 0.00 | 0.29 |
May | 0.00 | 12685.01 | 0.00 | 2870752.65 | 0.00 | 0.00 | 0.381832E+09 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 7615819.28 | 0.00 | 0.00 | 0.296195E+09 | 0.00 | 0.30 |
July | 0.00 | 4623238.57 | 0.00 | 10270640.31 | 0.00 | 0.00 | 0.167077E+09 | 0.00 | 0.28 |
August | 0.00 | 14922769.35 | 0.00 | 13332748.43 | 0.00 | 0.00 | 0.124352E+09 | 0.00 | 0.31 |
September | 0.00 | 62996.99 | 0.00 | 2726362.33 | 0.00 | 0.00 | 0.261623E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 5792714.63 | 0.00 | 0.00 | 0.428255E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 8758135.48 | 0.00 | 0.00 | 0.498693E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 12838128.00 | 0.00 | 0.00 | 0.580266E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.359194E+09 | 19621689.92 | 0.00 | 94049807.68 | 0.00 | 0.00 | 0.447931E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 239630.60 | 0.00 | 0.00 | 0.124352E+09 | 0.00 | 0.28 |
Maximum of Months | 0.359194E+09 | 14922769.35 | 0.00 | 14695361.19 | 0.00 | 0.00 | 0.580266E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:07:50
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.124487E+12 | 0.603547E+10 | 0.00 | 0.149063E+13 | 0.110683E+12 |
February | 0.238888E+12 | 0.546409E+10 | 0.00 | 0.150736E+13 | 0.158307E+12 |
March | 0.433987E+12 | 0.514913E+10 | 0.00 | 0.179328E+13 | 0.233909E+12 |
April | 0.665739E+12 | 0.503721E+10 | 0.00 | 0.185504E+13 | 0.396440E+12 |
May | 0.872729E+12 | 0.398173E+10 | 0.00 | 0.192144E+13 | 0.264201E+12 |
June | 0.886987E+12 | 0.328147E+10 | 0.00 | 0.176237E+13 | 0.530780E+12 |
July | 0.931696E+12 | 0.291525E+10 | 0.00 | 0.176782E+13 | 0.892001E+12 |
August | 0.734587E+12 | 0.227449E+10 | 0.00 | 0.147066E+13 | 0.118008E+13 |
September | 0.512153E+12 | 0.189872E+10 | 0.00 | 0.190927E+13 | 0.392232E+12 |
October | 0.329505E+12 | 0.417327E+10 | 0.00 | 0.191653E+13 | 0.192738E+12 |
November | 0.141954E+12 | 0.485741E+10 | 0.00 | 0.174966E+13 | 0.234769E+12 |
December | 0.945064E+11 | 0.516375E+10 | 0.00 | 0.162003E+13 | 0.324793E+12 |
Annual Sum or Average | 0.596722E+13 | 0.502320E+11 | 0.00 | 0.207641E+14 | 0.491093E+13 |
Minimum of Months | 0.945064E+11 | 0.189872E+10 | 0.00 | 0.147066E+13 | 0.110683E+12 |
Maximum of Months | 0.931696E+12 | 0.603547E+10 | 0.00 | 0.192144E+13 | 0.118008E+13 |