Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:06
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 09:07:12
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 34509.47 | 745.02 | 745.02 |
Net Site Energy | 34509.47 | 745.02 | 745.02 |
Total Source Energy | 92893.38 | 2005.45 | 2005.45 |
Net Source Energy | 92893.38 | 2005.45 | 2005.45 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2929.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7209.48 | 0.00 | 0.00 |
Interior Lighting | 2023.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 323.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3258.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1304.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1169.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 929.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12954.11 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 119.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 563.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 26735.18 | 564.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7209.48 | 0.00 | 15234.28 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2929.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7209.48 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2023.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 323.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ComputerHVAC | 1349.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 1304.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 1169.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 929.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12954.11 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 119.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 563.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2929.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7209.48 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2023.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 323.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 3258.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 1304.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1169.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 929.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12954.11 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 119.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 563.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 136.72 | 12.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.64 | 0.00 | 0.33 |
Other | 389.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 577.18 | 12.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.64 | 0.00 | 0.33 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 136.72 | 12.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.64 | 0.00 | 0.33 |
Other | 389.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 577.18 | 12.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.64 | 0.00 | 0.33 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 26735.181 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 26735.181 | 100.00 |
Total On-Site and Utility Electric Sources | 26735.181 | 100.00 |
Total Electricity End Uses | 26735.181 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 3269.80 | 99.69 |
Air to Air Heat Recovery for Heating | 10.26 | 0.31 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3280.06 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 15234.28 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 15234.28 | 100.00 |
Total Water End Uses | 15234.28 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 317.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EnergyConsumptionDistrictHeatingCoolingMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:06 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 5.8895 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.8895 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 5.8895 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 5.8895 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8011 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 5.8895 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 5.9168 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 5.9168 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 5.8895 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.8895 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 5.8895 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.8895 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.8895 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.8895 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.8895 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 8.8011 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 5.8895 | 18.58 | 484.4232 | |
Total | 46320.38 | 5.9168 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 5.9168 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 1.8190 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
Time of Peak | 23-AUG-15:00 | 04-FEB-06:10 | - | - | - | - | - | - | - | - | 21-AUG-13:00 | 01-FEB-00:40 | 22-MAY-12:00 |
Heating | 0.00 | 62214.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 0.00 |
Cooling | 285724.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370450.14 | 0.00 | 0.00 |
Interior Lighting | 171235.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 151141.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 138738.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 66506.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 56753.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 26211.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1654085.04 | 88425.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370450.14 | 13.50 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | District Heating [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 0.00 |
Boiler | 0.00 | 62214.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 285724.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370450.14 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 171235.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3372.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ComputerHVAC | 68333.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 138738.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 66506.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 56753.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 26211.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9276.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7610.80 | 0.00 |
Interior Lighting | 6409.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1026.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 10318.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4132.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3702.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2944.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 379.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 611.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 84670.32 | 612.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7610.80 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 200.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.31 | 0.00 |
Interior Lighting | 138.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 22.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 222.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 89.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 79.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 63.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1827.93 | 13.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.31 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 200.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.31 | 0.00 |
Interior Lighting | 138.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 22.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 222.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 89.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 79.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 63.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1827.93 | 13.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.31 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 4.96 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.458252 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.35 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.442100 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.26 | 0.361866 | 0.353000 | 1.86 | 0.964977 | 0.500000 | 0.001053 | 0.000163 | 1.86 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 49.12 | 0.387244 | 0.369000 | 18.12 | 1.00 | 0.500000 | 0.000984 | 0.002842 | 18.12 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 4.98 | 0.381597 | 0.372000 | 1.85 | 1.00 | 0.500000 | 0.000998 | 0.000483 | 1.85 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.880538 | 0.271221 | 0.265000 | 0.233343 | 0.723256 | 0.500000 | 0.001405 | 0.000023 | 0.233343 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.832857 | 0.184792 | 0.200000 | 0.166571 | 0.492778 | 0.500000 | 0.002062 | 0.000018 | 0.166571 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.864515 | 0.276254 | 0.270000 | 0.233419 | 0.736677 | 0.500000 | 0.001379 | 0.000040 | 0.233419 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.11 | 0.138939 | 0.200000 | 0.221543 | 0.370504 | 0.500000 | 0.002742 | 0.000019 | 0.221543 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.24 | 0.289898 | 0.276000 | 2.27 | 0.773062 | 0.500000 | 0.001314 | 0.000939 | 3.20 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 8.49 | 0.181319 | 0.200000 | 1.70 | 0.483517 | 0.500000 | 0.002101 | 0.000627 | 2.14 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 7.86 | 0.303838 | 0.289000 | 2.27 | 0.810234 | 0.500000 | 0.001254 | 0.000937 | 3.19 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 9.14 | 0.168431 | 0.200000 | 1.83 | 0.449149 | 0.500000 | 0.002262 | 0.000532 | 1.83 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.922942 | 0.258760 | 0.252000 | 0.232581 | 0.690027 | 0.500000 | 0.001472 | 0.000136 | 0.464501 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.874698 | 0.175952 | 0.200000 | 0.174940 | 0.469206 | 0.500000 | 0.002165 | 0.000090 | 0.306679 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.925037 | 0.258180 | 0.252000 | 0.233109 | 0.688479 | 0.500000 | 0.001476 | 0.000136 | 0.463574 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.01 | 0.152146 | 0.200000 | 0.202312 | 0.405723 | 0.500000 | 0.002504 | 0.000081 | 0.277038 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18659.91 | 0.000163 | 376.17 |
CORE_MID VAV BOX REHEAT COIL | 324904.90 | 0.002842 | 7099.46 |
CORE_TOP VAV BOX REHEAT COIL | 55211.16 | 0.000483 | 1386.39 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 2572.39 | 0.000023 | 52.35 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 2110.59 | 0.000018 | 43.66 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 4609.73 | 0.000040 | 102.75 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2228.03 | 0.000019 | 44.92 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 107373.31 | 0.000939 | 2834.76 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 71653.36 | 0.000627 | 1891.58 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 107095.23 | 0.000937 | 2827.44 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 60816.04 | 0.000532 | 1599.33 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 15571.90 | 0.000136 | 410.88 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 10280.34 | 0.000090 | 271.25 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 15540.92 | 0.000136 | 410.07 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9288.97 | 0.000081 | 245.12 |
VAV_BOT WITH REHEAT HEATING COIL | 12568.00 | 0.000110 | 223.64 |
VAV_MID WITH REHEAT HEATING COIL | 116012.11 | 0.001015 | 2064.39 |
VAV_TOP WITH REHEAT HEATING COIL | 12510.59 | 0.000109 | 222.62 |
CAV_BAS HEATING COIL | 227073.88 | 0.001987 | 5209.48 |
Design Size Maximum Heating Air Flow Rate [m3/s] | Design Size Maximum Cooling Air Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT | 0.338402 | 21.25 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 4.47 | 2.71 | 8.94 | 2.71 | 8.45 | 8.45 | 0.300000 | 0.320579 | 8.45 |
VAV_MID WITH REHEAT | 41.42 | 26.19 | 82.84 | 26.19 | 78.04 | 78.04 | 0.300000 | 0.335655 | 78.04 |
VAV_TOP WITH REHEAT | 4.36 | 2.70 | 8.72 | 3.06 | 8.42 | 8.42 | 0.300000 | 0.363651 | 8.42 |
CAV_BAS | 4.96 | 4.96 | 4.96 | 4.96 | 4.96 | 4.96 | 1.00 | 1.00 | 4.96 |
AIRLOOP DATACENTER BOT | 0.458252 | 0.458252 | 0.458252 | 0.458252 | 0.458252 | 0.458252 | 1.00 | 1.00 | 0.458252 |
AIRLOOP DATACENTER MID | 4.35 | 4.35 | 4.35 | 4.35 | 4.35 | 4.35 | 1.00 | 1.00 | 4.35 |
AIRLOOP DATACENTER TOP | 0.442100 | 0.442100 | 0.442100 | 0.442100 | 0.442100 | 0.442100 | 1.00 | 1.00 | 0.442100 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.45 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 78.04 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.42 | |
CAV_BAS_OA_CONTROLLER | 4.96 | 1.20 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.458252 | 0.015633 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.35 | 0.156328 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.442100 | 0.015633 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.99 | 6.67 | 11.05 | 0.011602 | 0.008500 | 245910.09 | 0.010462 | 8.45 |
VAV_MID WITH REHEAT COOLING COIL | 27.41 | 6.67 | 11.05 | 0.012032 | 0.008500 | 2412859.74 | 0.102649 | 78.04 |
VAV_TOP WITH REHEAT COOLING COIL | 26.76 | 6.67 | 11.05 | 0.011426 | 0.008500 | 237887.93 | 0.010120 | 8.42 |
CAV_BAS COOLING COIL | 25.13 | 6.67 | 11.42 | 0.010987 | 0.008500 | 121211.60 | 0.005157 | 4.96 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.45 |
VAV_MID WITH REHEAT FAN | 78.04 |
VAV_TOP WITH REHEAT FAN | 8.42 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.010462 | 0.000046 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000110 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.102649 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.001015 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.010120 | 0.000047 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000109 | |
CAV_BAS_COOLC_CONTROLLER | 0.005157 | 0.000092 |
CAV_BAS_HEATC_CONTROLLER | 0.001987 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 4.96 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT COOLING COIL | 0.458252 | 9382.00 | 6719.37 | 0.000230 |
AIRLOOP DATACENTER MID COOLING COIL | 4.35 | 89399.08 | 63930.52 | 0.002189 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.442100 | 9067.88 | 6488.15 | 0.000222 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.458252 | 0.458252 | 0.458252 | 0.458252 | 9382.00 | 9382.00 | 591.37 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.35 | 4.35 | 4.35 | 4.35 | 89399.08 | 89399.08 | 5913.67 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.442100 | 0.442100 | 0.442100 | 0.442100 | 9067.88 | 9067.88 | 591.37 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.458252 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.35 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.442100 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BOT HEATING COIL | 0.458252 | 9382.00 | 0.000230 |
AIRLOOP DATACENTER MID HEATING COIL | 4.35 | 89399.08 | 0.002189 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.442100 | 9067.88 | 0.000222 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 591.37 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 5913.67 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 591.37 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.128387 | 26193.89 | |
HEATSYS1 PUMP | 0.010289 | 3067.88 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.128387 | 15.41 |
HEATSYS1 | 0.010289 | 1.23 |
COOLSYS1_SUPPLY | 0.128387 | 15.41 |
SINGLE WATER PLANT LOOP | 0.002641 | 0.316946 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.128387 | 0.128387 | 538905.24 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1176081.38 | 1176081.38 | 0.010289 |
CENTRAL BOILER | 108795.39 | 108795.39 | 0.002641 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.128387 | 18134.91 |
PLANT CIRC PUMP | 0.002641 | 666.97 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.128387 | 0.064685 | 1524221.28 | 1531438.03 | 0.075785 |
COOLSYS1 CHILLER2 | 0.128387 | 0.064685 | 1524221.28 | 1531438.03 | 0.075785 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.002641 | 35644.39 | 21862.43 | 17822.20 | 1996.20 | 5887.19 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.151570 | 18.19 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.151570 | 45197.72 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 58.33 | 1817027.31 | 11.67 | 227128.41 |
TOWERWATERSYS COOLTOWER 2 | 58.33 | 1817027.31 | 11.67 | 227128.41 |
Design Water Flow Rate [m3/s] Equipment # 45 | |
WSHPPLANT OPERATION SCHEME | 0.078717 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 5.889 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 10.731 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 5.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.959 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 8.801 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.100 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 5.889 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 490.313 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 16369.361 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16369.361 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 14700.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14700.837 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 1845.837 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.837 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 1845.877 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1845.877 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1189.527 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1189.527 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 4615.459 | 5.889 | 109.419 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4615.459 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 318.624 | 8.801 | 163.514 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 318.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.743 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.656 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 2.135 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4064 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4365 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3009 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
47 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
48 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
49 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
50 | 9 | 0.76055735E-15 | 0.55973061E-16 | -0.11090261E-09 | -0.43371185E-17 |
51 | 8 | 0.16390423E-07 | 0.22068143E-12 | 0.31740643E-03 | -0.18636477E-09 |
52 | 7 | -0.10429999E-01 | 0.12271718E-07 | -0.20474149E-01 | 0.11859286E-03 |
53 | 6 | 0.35611320 | 0.43955117E-05 | 0.42991281 | -0.41673803E-02 |
54 | 5 | -4.7098961 | 0.16827687E-03 | -4.1162358 | 0.57223947E-01 |
55 | 4 | 30.875684 | 0.14076848E-02 | 20.167480 | -0.39388153 |
56 | 3 | -106.69740 | 0.31291265E-02 | -53.106522 | 1.4497707 |
57 | 2 | 192.63914 | 0.17911574E-02 | 75.570394 | -2.8293896 |
58 | 1 | -169.50392 | 0.19431750E-03 | -54.592911 | 2.7164834 |
59 | 0 | 57.057407 | 0.11257899E-05 | 15.674734 | |
60 | 9 | 0.11474244E-14 | 0.54197419E-16 | -0.11508650E-09 | -0.49945851E-17 |
61 | 8 | 0.16984416E-07 | 0.21156325E-12 | 0.32425024E-03 | -0.19311866E-09 |
62 | 7 | -0.10636353E-01 | 0.11664670E-07 | -0.20772028E-01 | 0.12093918E-03 |
63 | 6 | 0.36172330 | 0.41637772E-05 | 0.43474562 | -0.42335086E-02 |
64 | 5 | -4.7646824 | 0.15893927E-03 | -4.1535939 | 0.57903236E-01 |
65 | 4 | 31.118254 | 0.13261305E-02 | 20.314042 | -0.39710182 |
66 | 3 | -107.21418 | 0.29411649E-02 | -53.396504 | 1.4572354 |
67 | 2 | 193.15212 | 0.16802168E-02 | 75.835339 | -2.8375342 |
68 | 1 | -169.69371 | 0.18194848E-03 | -54.668081 | 2.7198097 |
69 | 0 | 57.057407 | 0.10520719E-05 | 15.660794 | |
70 | 9 | 0.66246833E-15 | 0.57738042E-16 | -0.92036509E-10 | -0.27018983E-17 |
71 | 8 | 0.13701644E-07 | 0.25726543E-12 | 0.28527343E-03 | -0.15579243E-09 |
72 | 7 | -0.94571194E-02 | 0.14940887E-07 | -0.19068097E-01 | 0.10753086E-03 |
73 | 6 | 0.32965778 | 0.54453531E-05 | 0.40701455 | -0.38555430E-02 |
74 | 5 | -4.4514676 | 0.21157254E-03 | -3.9387765 | 0.54019785E-01 |
75 | 4 | 29.731016 | 0.17930056E-02 | 19.470280 | -0.37868589 |
76 | 3 | -104.25747 | 0.40308508E-02 | -51.726693 | 1.4145289 |
77 | 2 | 190.21562 | 0.23301583E-02 | 74.311741 | -2.7909129 |
78 | 1 | -168.60668 | 0.25508611E-03 | -54.239505 | 2.7007581 |
79 | 0 | 57.057407 | 0.14924561E-05 | 15.743350 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.5037_SHGC_EAST_0.23 | 35 | 1 | VerySmooth | 2.864 | 2.864 | 1.000 | 0.231 | ||
2 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 36 | 1 | VerySmooth | 2.864 | 2.864 | 1.000 | 0.231 | ||
3 | WINDOW_U_0.5037_SHGC_WEST_0.23 | 37 | 1 | VerySmooth | 2.864 | 2.864 | 1.000 | 0.231 | ||
4 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 38 | 1 | VerySmooth | 2.864 | 2.864 | 1.000 | 0.231 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.92411E-002 | 0.14129 | 0.63052 | 0.63052 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10752 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.92411E-002 | 0.14129 | 0.63052 | 0.63052 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10752 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.92411E-002 | 0.14129 | 0.63052 | 0.63052 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10752 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.92411E-002 | 0.14129 | 0.63052 | 0.63052 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10752 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2.856E-002 | 9.114E-005 | 1.371E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.384E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2.856E-002 | 9.114E-005 | 1.371E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.384E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2.856E-002 | 9.114E-005 | 1.424E-004 | 0.120 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1.904E-002 | 9.429E-005 | 1.424E-004 | 0.124 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 4.231E-002 | 1.187E-005 | 1.424E-004 | 3.506E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 4.231E-002 | 1.187E-005 | 1.424E-004 | 3.506E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 4.231E-002 | 1.187E-005 | 1.096E-005 | 3.506E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.3506E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3516E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4633E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4641E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9359E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9365E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1459E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1463E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.3744E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4409E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4827E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5383E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9509E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9949E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1575E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1867E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4136E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6289E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.0471E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7486E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3791E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9640E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.3959E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.3815E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.3793E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4640E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4879E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5630E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9557E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.0133E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1578E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1876E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.3505E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3517E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4632E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4643E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9359E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9366E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1458E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1463E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.5226E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6307E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.4034E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5132E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.2779E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3368E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 1.9611E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9812E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9711E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4401E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8134E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.3062E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0028E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2170E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.4646E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.1889E-003 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.4988E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5450E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.3740E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4080E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.2605E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2750E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 1.9612E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9816E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1108E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1119E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.5794E-004 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.5882E-004 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 8.4787E-004 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.4850E-004 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1459E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1463E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1353E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1958E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.7800E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0262E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 8.6355E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.9772E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1578E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1876E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7198E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.6656E-003 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3493E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.4239E-003 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3161E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.2100E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3959E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.3789E-003 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1335E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1932E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.7573E-004 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0215E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 8.5979E-004 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.8629E-004 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1576E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1867E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1107E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1117E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.5787E-004 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.5867E-004 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 8.4779E-004 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.4828E-004 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1459E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1463E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1613E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2094E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 1.9682E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0031E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 1.9354E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9484E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 1.9612E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9816E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3161E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.1962E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.0354E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.0182E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3360E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 9.6506E-003 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.4646E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 9.1889E-003 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1805E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2669E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 1.9922E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0759E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 1.9517E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0035E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 1.9611E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9812E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.4045E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.6163E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.8824E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.7829E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.6667E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.7972E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 2.7727E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.3412E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.4145E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9960E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.2437E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.8383E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.4172E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7209E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 2.8359E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.3555E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0790E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4404E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.6739E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.1540E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.6316E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 8.9640E-003 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7727E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3410E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.7025E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.6756E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.3963E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.4582E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.6978E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.3978E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.8359E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.3555E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.4055E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.6219E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.8849E-002 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.7894E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.6709E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.8031E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 2.7759E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.3438E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.4138E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9980E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.2439E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.8403E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.4191E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7239E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 2.8390E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.3581E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0768E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4410E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.6724E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.1546E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.6326E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 8.9769E-003 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7759E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3436E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.7011E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.6769E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.3956E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4594E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.6992E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4001E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.8390E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.3581E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 68816.55146 | 68816.55146 | 4.95815 | 4.95815 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 2779.42662 | 149.60210 | 1.20019 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20019 | 00:10:00 | 8.70000 | 6.99286E-003 | 2779.42662 | 149.60210 | 1.20019 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 72954.39570 | 72954.39570 | 5.25621 | 5.25621 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 8.70000 | 6.99286E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 681952.71005 | 681952.71005 | 49.11744 | 49.11744 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 142630.93361 | 142630.93361 | 5.97687 | 10.77825 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 68521.78562 | 68521.78562 | 4.98444 | 4.98444 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.20000 | 1.71672E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 36563.61962 | 36563.61962 | 1.54863 | 1.54863 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12208.20447 | 12208.20447 | 0.88054 | 0.88054 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 228.18322 | 228.18322 | 9.77512E-003 | 0.13533 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 11449.40152 | 11449.40152 | 0.83286 | 0.83286 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 30.08450 | 1.71613E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 436.52312 | 436.52312 | 1.86306E-002 | 8.72129E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 11884.55487 | 11884.55487 | 0.86452 | 0.86452 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.20000 | 1.71672E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 2263.20260 | 2263.20260 | 9.54009E-002 | 0.13533 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 15228.02297 | 15228.02297 | 1.10772 | 1.10772 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 0.00000 | 0.00000 | 0.00000 | 8.72129E-002 | 00:10:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 | |
17 | PERIMETER_MID_ZN_3 | Cooling | 114237.62067 | 114237.62067 | 8.23809 | 8.23809 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 75209.82412 | 75209.82412 | 3.19897 | 3.19897 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 116684.08817 | 116684.08817 | 8.48809 | 8.48809 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 30.27433 | 1.71616E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 50186.15788 | 50186.15788 | 2.13511 | 2.13511 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 108053.33059 | 108053.33059 | 7.86031 | 7.86031 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.20000 | 1.71672E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 75015.49450 | 75015.49450 | 3.19064 | 3.19064 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 125612.44158 | 125612.44158 | 9.13757 | 9.13757 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 42442.89541 | 42442.89541 | 1.80342 | 1.80342 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 12687.32099 | 12687.32099 | 0.92294 | 0.92294 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.13300 | 1.71671E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 10901.16988 | 10901.16988 | 0.46450 | 0.46450 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 12024.18109 | 12024.18109 | 0.87470 | 0.87470 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 30.65400 | 1.71624E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 7196.56530 | 7196.56530 | 0.30668 | 0.30668 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 12716.11710 | 12716.11710 | 0.92504 | 0.92504 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.20000 | 1.71672E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 10879.51510 | 10879.51510 | 0.46357 | 0.46357 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 13905.63921 | 13905.63921 | 1.01156 | 1.01156 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 6503.34815 | 6503.34815 | 0.27704 | 0.27704 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 7987.98699 | 7987.98699 | 0.45825 | 0.45825 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 26.54467 | 1.71546E-002 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56328E-002 | 00:10:00 | 8.70000 | 6.99286E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 75896.15304 | 75896.15304 | 4.35399 | 4.35399 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 26.54467 | 1.71546E-002 | 36.20274 | 1.94861 | 0.15633 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15633 | 00:10:00 | 8.70000 | 6.99286E-003 | 36.20274 | 1.94861 | 0.15633 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7705.49471 | 7705.49471 | 0.44210 | 0.44210 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 30.92200 | 1.71629E-002 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56328E-002 | 00:10:00 | 8.70000 | 6.99286E-003 | 36.20274 | 1.94861 | 1.56328E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370351.79718 | 370351.79718 | 21.24823 | 21.24823 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.10300 | 1.71556E-002 | 783.67941 | 42.18139 | 0.33840 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33840 | 00:10:00 | 8.70000 | 6.99286E-003 | 783.67941 | 42.18139 | 0.33840 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 133906.08 | 8.45444 | 8.45444 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 7546.34 | 1.52292 | 1.52292 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1210113.02 | 78.04084 | 78.04084 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 104586.11 | 21.10638 | 21.10638 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 141481.51 | 8.41582 | 8.41582 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 12571.85 | 3.06042 | 3.06042 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:20:00 |
7 | CAV_BAS | Cooling | Sensible | 73691.61 | 4.95815 | 4.95815 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 45401.58 | 1.20019 | 1.20019 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 7865.47 | 0.45825 | 0.45825 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BOT | Heating | Sensible | 591.37 | 1.56328E-002 | 1.56328E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER MID | Cooling | Sensible | 74857.59 | 4.35399 | 4.35399 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER MID | Heating | Sensible | 5913.67 | 0.15633 | 0.15633 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7662.17 | 0.44210 | 0.44210 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER TOP | Heating | Sensible | 591.37 | 1.56328E-002 | 1.56328E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.95815 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.25621 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36187 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35300 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.85544 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96498 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05288E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.63245E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.85544 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18659.91420 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.63245E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 376.16922 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 49.11744 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38724 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36900 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.12433 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.83876E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.84241E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.12433 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 324904.90476 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.84241E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7099.45766 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.98444 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38160 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.37200 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.85421 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.98437E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.83011E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.85421 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 55211.16320 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.83011E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1386.38760 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88054 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27122 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26500 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23334 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72326 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.40476E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.25044E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23334 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2572.38825 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.25044E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 52.35183 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83286 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18479 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16657 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49278 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06178E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.84643E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.16657 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2110.58504 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.84643E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 43.66471 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86452 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27625 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23342 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73668 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37917E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.03279E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23342 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4609.73054 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.03279E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 102.75096 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.10772 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13894 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22154 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37050 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.74221E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.94918E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.22154 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2228.03287 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.94918E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 44.91539 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.23809 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28990 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27600 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.27371 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77306 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.31425E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.39349E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.19897 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 107373.31131 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.39349E-004 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2834.76328 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.48809 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18132 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.69762 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48352 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10127E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.26855E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.13511 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 71653.35908 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.26855E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1891.58171 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.86031 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30384 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28900 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.27163 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81023 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.25396E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.36916E-004 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.19064 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 107095.23434 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.36916E-004 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2827.43887 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.13757 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16843 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.82751 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44915 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.26205E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.32045E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.82751 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 60816.03834 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.32045E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1599.33220 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92294 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25876 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25200 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23258 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69003 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47241E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.36230E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.46450 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15571.90018 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.36230E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 410.88319 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87470 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17595 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17494 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46921 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.16536E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.99369E-005 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30668 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10280.34133 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.99369E-005 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 271.25023 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92504 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25818 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25200 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23311 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68848 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47572E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.35959E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.46357 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15540.91869 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35959E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 410.06700 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.01156 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15215 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20231 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40572 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.50417E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.12640E-005 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.27704 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9288.97403 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.12640E-005 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 245.11973 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45825 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.35399 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.44210 |
215 | ZoneHVAC:IdealLoadsAirSystem | AIRLOOP DATACENTER BASEMENT | Design Size Maximum Heating Air Flow Rate [m3/s] | 0.33840 |
216 | ZoneHVAC:IdealLoadsAirSystem | AIRLOOP DATACENTER BASEMENT | Design Size Maximum Cooling Air Flow Rate [m3/s] | 21.24823 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.47092 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.71032 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.94183 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.71032 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.45444 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.45444 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32058 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 41.42075 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 26.19481 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 82.84150 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 26.19481 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 78.04084 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 78.04084 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.33566 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.35934 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.69715 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.71868 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.06042 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.41582 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.41582 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.36365 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.95815 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.95815 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.95815 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 4.95815 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.95815 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 4.95815 |
247 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45825 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45825 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45825 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45825 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45825 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.45825 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
257 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.35399 |
258 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.35399 |
259 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.35399 |
260 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.35399 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.35399 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.35399 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
265 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.44210 |
266 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.44210 |
267 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.44210 |
268 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.44210 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.44210 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.44210 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
273 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.45444 |
274 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 78.04084 |
275 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.41582 |
276 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 4.95815 |
277 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.45825 |
278 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.35399 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.44210 |
280 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.45444 |
281 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
282 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.98975 |
283 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
284 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04954 |
285 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.16023E-002 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 245910.09355 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.04616E-002 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.45444 |
290 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 12568.00256 |
291 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.09950E-004 |
292 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 223.64254 |
293 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.45444 |
294 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.04616E-002 |
295 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.55180E-005 |
296 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.09950E-004 |
297 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 78.04084 |
298 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
299 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.40532 |
300 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
301 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.05090 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.20324E-002 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2412859.73766 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 0.10265 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 78.04084 |
307 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 116012.11418 |
308 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01492E-003 |
309 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2064.38880 |
310 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 78.04084 |
311 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.10265 |
312 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.63903E-006 |
313 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.01492E-003 |
314 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.41582 |
315 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
316 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.76420 |
317 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04898 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.14256E-002 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 237887.92827 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.01203E-002 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.41582 |
324 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 12510.59361 |
325 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.09448E-004 |
326 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 222.62097 |
327 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.41582 |
328 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.01203E-002 |
329 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.70530E-005 |
330 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.09448E-004 |
331 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.95815 |
332 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20019 |
333 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.13162 |
334 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.42491 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.09872E-002 |
337 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 121211.59901 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.15662E-003 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 4.95815 |
341 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 227073.87598 |
342 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.98654E-003 |
343 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5209.47526 |
344 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 4.95815 |
345 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.15662E-003 |
346 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.23454E-005 |
347 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.98654E-003 |
348 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45825 |
349 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56328E-002 |
350 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45825 |
351 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9382.00102 |
352 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6719.37195 |
353 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29765E-004 |
354 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45825 |
355 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45825 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45825 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45825 |
358 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9382.00102 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9382.00102 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 591.36718 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
362 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45825 |
363 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45825 |
364 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9382.00102 |
365 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29765E-004 |
366 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 591.36718 |
367 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.35399 |
368 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15633 |
369 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.35399 |
370 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 89399.08449 |
371 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 63930.52003 |
372 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.18938E-003 |
373 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.35399 |
374 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.35399 |
375 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.35399 |
376 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.35399 |
377 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 89399.08449 |
378 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 89399.08449 |
379 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 5913.67179 |
380 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
381 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.35399 |
382 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.35399 |
383 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 89399.08449 |
384 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.18938E-003 |
385 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 5913.67179 |
386 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.44210 |
387 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56328E-002 |
388 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44210 |
389 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9067.88468 |
390 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6488.14818 |
391 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.22072E-004 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.44210 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.44210 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.44210 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.44210 |
396 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9067.88468 |
397 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9067.88468 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 591.36718 |
399 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
400 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.44210 |
401 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.44210 |
402 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9067.88468 |
403 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.22072E-004 |
404 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 591.36718 |
405 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.12839 |
406 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 26193.89193 |
407 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.12839 |
408 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 15.40646 |
409 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.12839 |
410 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.12839 |
411 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 538905.24259 |
412 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
413 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.02889E-002 |
414 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.23466 |
415 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.02889E-002 |
416 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3067.87793 |
417 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
418 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1176081.38249 |
419 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1176081.38000 |
420 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.02889E-002 |
421 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.12839 |
422 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 15.40646 |
423 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 0.12839 |
424 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 18134.91497 |
425 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12839 |
426 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.46850E-002 |
427 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1524221.27741 |
428 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1531438.03000 |
429 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.57852E-002 |
430 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12839 |
431 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.46850E-002 |
432 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1524221.27741 |
433 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1531438.03000 |
434 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.57852E-002 |
435 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 2.64121E-003 |
436 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 0.31695 |
437 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 2.64121E-003 |
438 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 666.97202 |
439 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 2.64121E-003 |
440 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 35644.39112 |
441 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 21862.43244 |
442 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 17822.19556 |
443 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 1996.19659 |
444 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 5887.19151 |
445 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 108795.38748 |
446 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 108795.39000 |
447 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 2.64121E-003 |
448 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
449 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
450 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
451 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
452 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
453 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.15157 |
454 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 18.18845 |
455 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.15157 |
456 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 45197.72380 |
457 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 58.33500 |
458 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1817027.30611 |
459 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.66700 |
460 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 227128.41326 |
461 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 58.33500 |
462 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1817027.30611 |
463 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.66700 |
464 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 227128.41326 |
465 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 7.87175E-002 |
466 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 7.87175E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17693.24 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 307934.21 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 52288.68 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 2439.01 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 2001.00 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 4368.55 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2112.61 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 101749.06 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 67899.21 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 101485.67 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 57588.22 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 14754.70 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 9740.78 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 14725.35 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 8801.62 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 11253.41 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 103877.42 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 11202.00 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 186514.37 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 237312.14 | 159010.67 | 78301.47 | 0.67 | 24870.50 | 252.25 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2238962.77 | 1490779.19 | 748183.58 | 0.67 | 236121.97 | 2394.88 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 233785.84 | 157127.20 | 76658.64 | 0.67 | 24443.89 | 247.92 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 129196.02 | 88460.55 | 40735.48 | 0.68 | 13218.24 | 134.07 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2014397624 | 0.1915373967 | Pass | Pass | 1.5534976363 | 3.9711932312 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2770640985 | 0.2318564106 | Pass | Pass | 0.2838899191 | 0.4499545014 | Pass | Fail |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1654791364 | 0.1985555927 | Pass | Pass | 0.2321230953 | 0.4206974049 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1223390731 | 0.1681332718 | Pass | Pass | 0.2096838501 | 0.4052653611 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2406878943 | 0.2053311442 | Pass | Pass | 0.2790061911 | 0.4464924910 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3189180618 | 0.3193090044 | Pass | Pass | 0.3049041205 | 0.4746860247 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3413366638 | 0.3706847035 | Pass | Pass | 0.3485667947 | 0.5379316940 | Pass | Fail |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3639913995 | 0.3249264009 | Pass | Pass | 0.2821201443 | 0.4457965194 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1514265081 | 0.1908246708 | Pass | Pass | 0.2311018989 | 0.4192016179 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2321110387 | 0.2856544803 | Pass | Pass | 0.2380143798 | 0.4245878062 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2681198116 | 0.3894045057 | Pass | Pass | 0.2964996432 | 0.5359646304 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1959790535 | 0.2459058434 | Pass | Pass | 0.2317969003 | 0.4184763643 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1221988829 | 0.1645528957 | Pass | Pass | 0.2092809078 | 0.4040772196 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1906429385 | 0.2524666647 | Pass | Pass | 0.2113854415 | 0.4059457484 | Pass | Fail |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2386330575 | 0.3679413683 | Pass | Pass | 0.2559565384 | 0.4751792975 | Pass | Fail |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1652153429 | 0.2314797491 | Pass | Pass | 0.2101186415 | 0.4035016126 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.8283683083E-002 | 4.1576686489E-002 | Pass | Pass | 0.3057752274 | 0.4739764598 | Fail | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.7731112574E-002 | 4.2575798434E-002 | Pass | Pass | 0.2778572948 | 0.6247328909 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.2337724242E-002 | 6.5620256842E-002 | Pass | Pass | 0.2274110252 | 0.4302632934 | Fail | Fail |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.6029460276E-004 | 2.6973528513E-004 | Pass | Pass | 1.9027371541E-003 | 1.4492269932E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.8139981664E-006 | 6.3609830394E-006 | Pass | Pass | 2.2073782084E-003 | 2.1290348659E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.0449545812E-006 | 5.1212202158E-006 | Pass | Pass | 4.0682164482E-003 | 3.0455639911E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.7270135939E-015 | 2.6804784280E-015 | Pass | Pass | 3.3978736655E-005 | 1.0695404463E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5680.34 | -29.2 | 0.00 | -7349.5 | 23044.95 | 21346.56 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.5037_SHGC_EAST_0.23 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.5037_SHGC_EAST_0.23 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.5037_SHGC_EAST_0.23 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.5037_SHGC_WEST_0.23 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.5037_SHGC_WEST_0.23 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.5037_SHGC_WEST_0.23 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.864 | 0.231 | 0.231 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5037_SHGC_EAST_0.23 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.864 | 0.231 | 0.231 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.864 | 0.231 | 0.231 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5037_SHGC_WEST_0.23 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.864 | 0.231 | 0.231 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.864 | 0.231 | 0.231 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5037_SHGC_EAST_0.23 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.864 | 0.231 | 0.231 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.864 | 0.231 | 0.231 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5037_SHGC_WEST_0.23 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.864 | 0.231 | 0.231 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.864 | 0.231 | 0.231 | |||||||||||||||||
North Total or Average | 1043.06 | 2.864 | 0.231 | 0.231 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.864 | 0.231 | 0.231 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 5.8895 | 2779.43 | 16369.36 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 135.58 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.8895 | 2496.12 | 14700.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 121.76 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.8895 | 24961.20 | 147008.37 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 1217.57 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.8895 | 2496.12 | 14700.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 121.76 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.8895 | 313.41 | 1845.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.84 | 0.0000 | Y | 8.95 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.62 | 0.0000 | Y | 5.72 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.8895 | 313.42 | 1845.88 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.29 | 0.0000 | Y | 8.76 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.65 | 0.0000 | Y | 5.73 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.8895 | 3134.13 | 18458.37 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.82 | 0.0000 | Y | 89.48 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.8895 | 2019.75 | 11895.27 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.61 | 0.0000 | Y | 57.19 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.8895 | 3134.20 | 18458.77 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.29 | 0.0000 | Y | 87.62 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.8895 | 2019.75 | 11895.27 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.64 | 0.0000 | Y | 57.25 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.8895 | 313.41 | 1845.84 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.82 | 0.0000 | Y | 8.95 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.61 | 0.0000 | Y | 5.72 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.8895 | 313.42 | 1845.88 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.29 | 0.0000 | Y | 8.76 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.8895 | 201.98 | 1189.53 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 25.64 | 0.0000 | Y | 5.72 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 5.8895 | 783.68 | 4615.46 | LightsWired | LTG_SCH_OFFICE | 45.29 | 168.00 | 44.12 | 0.0000 | Y | 38.23 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 8.8011 | 36.20 | 318.62 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.26 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 8.8011 | 362.03 | 3186.24 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 32.64 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 8.8011 | 36.20 | 318.62 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.26 |
Interior Lighting Total | 5.9168 | 46320.38 | 274067.57 | 636.34 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.88 | 711.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.88 | 255.65 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1845.84 | 711.94 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1845.84 | 255.65 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1189.53 | 458.80 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1189.53 | 164.75 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.05 | AstronomicalClock | - | 41.82 | 41.82 | 78.30 | |
EXTERIOR_LIGHTS_B | 991.40 | AstronomicalClock | - | 83.82 | 62.82 | 11.69 | |
EXTERIOR_LIGHTS_C | 26646.63 | AstronomicalClock | - | 83.82 | 46.78 | 233.98 | |
Exterior Lighting Total | 37611.08 | 323.97 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3010929.15 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1176081.38 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1531438.03 | 6.28 | 1465789.03 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1531438.03 | 6.28 | 1465789.03 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 148548.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 108795.39 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1817027.31 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1817027.31 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 245910.09 | 237312.14 | 159010.67 | 78301.47 | 0.67 | - | 24870.50 | 252.25 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2412859.74 | 2238962.77 | 1490779.19 | 748183.58 | 0.67 | - | 236121.97 | 2394.88 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 237887.93 | 233785.84 | 157127.20 | 76658.64 | 0.67 | - | 24443.89 | 247.92 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 121211.60 | 129196.02 | 88460.55 | 40735.48 | 0.68 | - | 13218.24 | 134.07 |
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9382.00 | 6719.37 | 2662.63 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 89399.08 | 63930.52 | 25468.56 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9067.88 | 6488.15 | 2579.74 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18659.91 | 17693.24 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 324904.90 | 307934.21 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 55211.16 | 52288.68 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 2572.39 | 2439.01 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 2110.59 | 2001.00 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4609.73 | 4368.55 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 2228.03 | 2112.61 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 107373.31 | 101749.06 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 71653.36 | 67899.21 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 107095.23 | 101485.67 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 60816.04 | 57588.22 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 15571.90 | 14754.70 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 10280.34 | 9740.78 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15540.92 | 14725.35 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 9288.97 | 8801.62 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 12568.00 | 11253.41 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 116012.11 | 103877.42 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 12510.59 | 11202.00 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 227073.88 | 186514.37 | - |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9382.00 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 89399.08 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9067.88 | 0.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 591.37 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 5913.67 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 591.37 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.45 | 18269.59 | 2160.95 | 1.00 | 1.12 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 78.04 | 168642.09 | 2160.95 | 1.00 | 1.08 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.42 | 18186.14 | 2160.95 | 1.00 | 1.12 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 4.96 | 8407.31 | 1695.65 | 1.00 | 1.16 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 513.29 | 1120.11 | 1.00 | 1.65 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.35 | 4876.93 | 1120.11 | 1.00 | 1.16 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.44 | 495.20 | 1120.11 | 1.00 | 1.66 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.128387 | 26193.89 | 204022.71 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.010289 | 3067.88 | 298174.34 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.128387 | 18134.91 | 141251.81 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.002641 | 666.97 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.151570 | 45197.72 | 298196.27 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 68816.55 | 68816.55 | 24.76 | 4.958 | 4.958 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00901 | 28.24 | 0.01716 | 1.200 | 0.00 |
CORE_BOTTOM | 72954.40 | 72954.40 | 29.23 | 5.256 | 5.256 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 28.24 | 0.01716 | 1.078 | 0.00 |
CORE_MID | 681952.71 | 681952.71 | 273.21 | 49.117 | 49.117 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 28.24 | 0.01716 | 10.778 | 0.00 |
CORE_TOP | 68521.79 | 68521.79 | 27.45 | 4.984 | 4.984 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00894 | 33.20 | 0.01717 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12208.20 | 12208.20 | 38.95 | 0.881 | 0.881 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 28.24 | 0.01716 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 11449.40 | 11449.40 | 56.69 | 0.833 | 0.833 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00876 | 30.08 | 0.01716 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 11884.55 | 11884.55 | 37.92 | 0.865 | 0.865 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00888 | 33.20 | 0.01717 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 15228.02 | 15228.02 | 75.40 | 1.108 | 1.108 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00869 | 32.26 | 0.01717 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 114237.62 | 114237.62 | 364.50 | 8.238 | 8.238 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00900 | 28.24 | 0.01716 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 116684.09 | 116684.09 | 577.72 | 8.488 | 8.488 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00881 | 30.27 | 0.01716 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 108053.33 | 108053.33 | 344.76 | 7.860 | 7.860 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00901 | 33.20 | 0.01717 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 125612.44 | 125612.44 | 621.92 | 9.138 | 9.138 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00878 | 32.26 | 0.01717 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12687.32 | 12687.32 | 40.48 | 0.923 | 0.923 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00896 | 33.13 | 0.01717 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 12024.18 | 12024.18 | 59.53 | 0.875 | 0.875 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 24.00 | 24.00 | 0.00882 | 30.65 | 0.01716 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 12716.12 | 12716.12 | 40.57 | 0.925 | 0.925 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00896 | 33.20 | 0.01717 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 13905.64 | 13905.64 | 68.85 | 1.012 | 1.012 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00878 | 32.26 | 0.01717 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 7987.99 | 7987.99 | 220.65 | 0.458 | 0.458 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 26.54 | 0.01715 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 75896.15 | 75896.15 | 2096.42 | 4.354 | 4.354 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 26.54 | 0.01715 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7705.49 | 7705.49 | 212.84 | 0.442 | 0.442 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 30.92 | 0.01716 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370351.80 | 370351.80 | 472.58 | 21.248 | 21.248 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 27.10 | 0.01716 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 26.35 | 0.00699 | 8.70 | 0.00699 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 23.92 | 0.00699 | 8.70 | 0.00699 | 1.078 | 0.00 | |
CORE_MID | 142630.93 | 142630.93 | 57.14 | 5.977 | 10.778 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 10.778 | 0.00 |
CORE_TOP | 36563.62 | 36563.62 | 14.65 | 1.549 | 1.549 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 228.18 | 228.18 | 0.73 | 0.010 | 0.135 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00742 | 8.70 | 0.00699 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 436.52 | 436.52 | 2.16 | 0.019 | 0.087 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | 8.70 | 0.00699 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 2263.20 | 2263.20 | 7.22 | 0.095 | 0.135 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00779 | 8.70 | 0.00699 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 0.00 | 0.000 | 0.087 | 00:10:00 | 15.60 | 21.56 | 0.00699 | 8.70 | 0.00699 | 0.087 | 0.00 | |
PERIMETER_MID_ZN_3 | 75209.82 | 75209.82 | 239.97 | 3.199 | 3.199 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 8.70 | 0.00699 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 50186.16 | 50186.16 | 248.48 | 2.135 | 2.135 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 8.70 | 0.00699 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 75015.49 | 75015.49 | 239.35 | 3.191 | 3.191 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 8.70 | 0.00699 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 42442.90 | 42442.90 | 210.14 | 1.803 | 1.803 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | 8.70 | 0.00699 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 10901.17 | 10901.17 | 34.78 | 0.465 | 0.465 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 8.70 | 0.00699 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 7196.57 | 7196.57 | 35.63 | 0.307 | 0.307 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | 8.70 | 0.00699 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 10879.52 | 10879.52 | 34.71 | 0.464 | 0.464 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 8.70 | 0.00699 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 6503.35 | 6503.35 | 32.20 | 0.277 | 0.277 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | 8.70 | 0.00699 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 8.70 | 0.00699 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 25.35 | 0.00849 | 8.70 | 0.00699 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.44 | 0.00736 | 8.70 | 0.00699 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 8.70 | 0.00699 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 8.45 | 8.45 | 1.52 | 1.52 | 8.4544 | 2.7103 | 8.4544 | 0.3206 | 0.3000 |
VAV_MID WITH REHEAT | 78.04 | 78.04 | 21.11 | 21.11 | 78.0408 | 26.1948 | 78.0408 | 0.3357 | 0.3000 |
VAV_TOP WITH REHEAT | 8.42 | 8.42 | 3.06 | 3.06 | 8.4158 | 3.0604 | 8.4158 | 0.3637 | 0.3000 |
CAV_BAS | 4.96 | 4.96 | 1.20 | 1.20 | 4.9582 | 4.9582 | 4.9582 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.46 | 0.46 | 0.02 | 0.02 | 0.4583 | 0.4583 | 0.4583 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.35 | 4.35 | 0.16 | 0.16 | 4.3540 | 4.3540 | 4.3540 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.44 | 0.44 | 0.02 | 0.02 | 0.4421 | 0.4421 | 0.4421 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18659.914 | 18659.914 | 1.855441 | 0.00016325 | 376.169 | 1/21 00:10:00 | 1/21 00:10:00 | 18659.91 | 18659.91 | 1.855441 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 0.00 | 0.00 | 18728.72 | 18728.72 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 324904.905 | 324904.905 | 18.124334 | 0.00284241 | 7099.458 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 324904.90 | 324904.90 | 18.124334 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 142630.93 | 0.00 | 326031.54 | 326031.54 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 55211.163 | 55211.163 | 1.854211 | 0.00048301 | 1386.388 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 55211.16 | 55211.16 | 1.854211 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 36563.62 | 0.00 | 55382.86 | 55382.86 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 2572.388 | 2572.388 | 0.233343 | 0.00002250 | 52.352 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2572.39 | 2572.39 | 0.233343 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00742061 | 47.9591 | 228.18 | 0.00 | 2581.83 | 2581.83 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 2110.585 | 2110.585 | 0.166571 | 0.00001846 | 43.665 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2110.59 | 2110.59 | 0.166571 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00763714 | 49.3417 | 436.52 | 0.00 | 2118.27 | 2118.27 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 4609.731 | 4609.731 | 0.233419 | 0.00004033 | 102.751 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4609.73 | 4609.73 | 0.233419 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00779060 | 50.3211 | 2263.20 | 0.00 | 4625.55 | 4625.55 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 2228.033 | 2228.033 | 0.221543 | 0.00001949 | 44.915 | 1/21 00:10:00 | 1/21 00:10:00 | 2228.03 | 2228.03 | 0.221543 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 0.00 | 0.00 | 2236.25 | 2236.25 | ||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 107373.311 | 107373.311 | 3.198969 | 0.00093935 | 2834.763 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 107373.31 | 107373.31 | 3.198969 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788146 | 50.9012 | 75209.82 | 0.00 | 107747.49 | 107747.49 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 71653.359 | 71653.359 | 2.135107 | 0.00062685 | 1891.582 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 71653.36 | 71653.36 | 2.135107 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788470 | 50.9218 | 50186.16 | 0.00 | 71902.06 | 71902.06 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 107095.234 | 107095.234 | 3.190642 | 0.00093692 | 2827.439 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 107095.23 | 107095.23 | 3.190642 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788102 | 50.8983 | 75015.49 | 0.00 | 107468.56 | 107468.56 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 60816.038 | 60816.038 | 1.827515 | 0.00053205 | 1599.332 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 60816.04 | 60816.04 | 1.827515 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00784588 | 50.6743 | 42442.90 | 0.00 | 60997.55 | 60997.55 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 15571.900 | 15571.900 | 0.464501 | 0.00013623 | 410.883 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15571.90 | 15571.90 | 0.464501 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00793366 | 51.2338 | 10901.17 | 0.00 | 15624.51 | 15624.51 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 10280.341 | 10280.341 | 0.306679 | 0.00008994 | 271.250 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10280.34 | 10280.34 | 0.306679 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00793501 | 51.2424 | 7196.57 | 0.00 | 10315.01 | 10315.01 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 15540.919 | 15540.919 | 0.463574 | 0.00013596 | 410.067 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15540.92 | 15540.92 | 0.463574 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00793346 | 51.2325 | 10879.52 | 0.00 | 15593.43 | 15593.43 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 9288.974 | 9288.974 | 0.277038 | 0.00008126 | 245.120 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9288.97 | 9288.97 | 0.277038 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00791790 | 51.1334 | 6503.35 | 0.00 | 9320.49 | 9320.49 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 245910.094 | -999.000 | 8.454440 | 0.01046158 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 245910.09 | 163588.63 | 8.454440 | 26.99 | 19.86 | 0.01160230 | 11.05 | 11.05 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 30.0220 | 24.00 | 0.00892207 | 47.9430 | 107339.87 | 0.00 | 246253.61 | 160459.92 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 12568.003 | 12568.003 | 2.536332 | 0.00010995 | 223.643 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 12568.00 | 12568.00 | 2.536332 | 8.70 | 8.70 | 0.00699286 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 100.0733 | 21.46 | 0.00741163 | 46.5825 | 0.00 | 0.00 | 13625.10 | 13625.10 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2412859.738 | -999.000 | 78.040836 | 0.10264863 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2412859.74 | 1548581.72 | 78.040836 | 27.41 | 20.31 | 0.01203240 | 11.05 | 11.05 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 32.5239 | 24.00 | 0.00901357 | 48.4281 | 942420.46 | 0.00 | 2416417.17 | 1525337.00 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 116012.114 | 116012.114 | 23.412251 | 0.00101492 | 2064.389 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 116012.11 | 116012.11 | 23.412251 | 8.70 | 8.70 | 0.00699286 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 108.4131 | 21.00 | 0.00792132 | 51.1550 | 385485.31 | 0.00 | 125769.95 | 125769.95 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 237887.928 | -999.000 | 8.415821 | 0.01012030 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 237887.93 | 160568.63 | 8.415821 | 26.76 | 19.66 | 0.01142563 | 11.05 | 11.05 | 0.00850000 | 33.13 | 0.01716709 | 25.31 | 30.1597 | 24.00 | 0.00893238 | 47.9981 | 115242.55 | 0.00 | 238213.44 | 157200.05 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 12510.594 | 12510.594 | 2.524746 | 0.00010945 | 222.621 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:20:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12510.59 | 12510.59 | 2.524746 | 8.70 | 8.70 | 0.00699286 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 100.5325 | 21.00 | 0.00797766 | 51.5138 | 59158.96 | 0.00 | 13562.87 | 13562.87 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 121211.599 | -999.000 | 4.958153 | 0.00515662 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 121211.60 | 83127.63 | 4.958153 | 25.13 | 18.80 | 0.01098716 | 11.42 | 11.42 | 0.00850000 | 28.67 | 0.01715859 | 24.15 | 24.2064 | 24.00 | 0.00900898 | 48.4034 | 67972.00 | 0.00 | 121390.38 | 81295.56 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 227073.876 | 227073.876 | 4.958153 | 0.00198654 | 5209.475 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 227073.88 | 227073.88 | 4.958153 | 2.11 | 2.11 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 24.2064 | 26.35 | 0.00699286 | 32.7686 | 0.00 | 0.00 | 197472.72 | 197472.72 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9382.001 | 6719.372 | 0.458252 | 0.00022976 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 8797.29 | 8310.23 | -999.0 | 28.08 | 18.10 | 0.00888659 | 12.80 | 12.09 | 0.00850000 | 30.92 | 0.01716288 | 24.74 | -999.0000 | 27.00 | 0.00859148 | 38.6531 | 7913.71 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 89399.084 | 63930.520 | 4.353986 | 0.00218938 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | 83868.49 | 79005.04 | -999.0 | 28.09 | 18.12 | 0.00890621 | 12.80 | 12.09 | 0.00850000 | 30.92 | 0.01716288 | 24.74 | -999.0000 | 27.00 | 0.00859615 | 38.6742 | 75280.32 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9067.885 | 6488.148 | 0.442100 | 0.00022207 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8505.42 | 8022.80 | -999.0 | 28.09 | 18.11 | 0.00889702 | 12.80 | 12.09 | 0.00850000 | 31.09 | 0.01716319 | 24.78 | -999.0000 | 27.00 | 0.00859395 | 38.6642 | 7704.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9382.001 | 9382.001 | 0.458252 | 0.00022976 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9382.00 | 9382.00 | 0.458252 | 8.70 | 8.70 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.4114 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 89399.084 | 89399.084 | 4.353986 | 0.00218938 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 89399.08 | 89399.08 | 4.353986 | 8.70 | 8.70 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.5905 | 25.35 | 0.00849456 | 42.1263 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9067.885 | 9067.885 | 0.442100 | 0.00022207 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9067.88 | 9067.88 | 0.442100 | 8.70 | 8.70 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.5360 | 24.44 | 0.00736003 | 38.6045 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 591.367 | 591.367 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 591.37 | 591.37 | 0.458252 | 0.30 | 0.30 | 0.00844859 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.4114 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 5913.672 | 5913.672 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 5913.67 | 5913.67 | 4.353986 | 0.31 | 0.31 | 0.00844064 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.5905 | 25.35 | 0.00849456 | 42.1263 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 591.367 | 591.367 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 591.37 | 591.37 | 0.442100 | 0.31 | 0.31 | 0.00734704 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.5360 | 24.44 | 0.00736003 | 38.6045 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18659.914 | 18659.914 | 1.855441 | 0.00016325 | 376.169 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 1.5553 | 1.586618 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 18659.91 | 18659.91 | 1.0000 | 2.23161068 | 1.855441 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.16322842 | 60.00 | 32.22 | 27.78 | 0.000 | 18659.91 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 0.00 | 0.00 | 18728.72 | 18728.72 | 2.23161068 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 324904.905 | 324904.905 | 18.124334 | 0.00284241 | 7099.458 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 27.0810 | 27.626056 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 324904.90 | 324904.90 | 1.0000 | 21.79884172 | 18.124334 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 2.84211989 | 60.00 | 32.22 | 27.78 | 0.000 | 324904.90 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.63 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 142630.93 | 0.00 | 326031.54 | 326031.54 | 21.79884172 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 27.47 | 17.18 | 0.00800000 | 48016.2 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 55211.163 | 55211.163 | 1.854211 | 0.00048301 | 1386.388 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 4.6019 | 4.694502 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 55211.16 | 55211.16 | 1.0000 | 2.23013123 | 1.854211 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.48296207 | 60.00 | 32.22 | 27.78 | 0.000 | 55211.16 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 36563.62 | 0.00 | 55382.86 | 55382.86 | 2.23013123 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.15 | 20.33 | 0.00800000 | 57893.7 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2572.388 | 2572.388 | 0.233343 | 0.00002250 | 52.352 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 0.2144 | 0.218725 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2572.39 | 2572.39 | 1.0000 | 0.28065035 | 0.233343 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.02250208 | 60.00 | 32.22 | 27.78 | 0.000 | 2572.39 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.99 | 0.00742061 | 21.00 | 0.00742061 | 47.9591 | 228.18 | 0.00 | 2581.83 | 2581.83 | 0.28065035 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.82 | 15.16 | 0.00800000 | 42259.3 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2110.585 | 2110.585 | 0.166571 | 0.00001846 | 43.665 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 0.1759 | 0.179459 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2110.59 | 2110.59 | 1.0000 | 0.20034192 | 0.166571 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.01846244 | 60.00 | 32.22 | 27.78 | 0.000 | 2110.59 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.97 | 0.00763714 | 21.00 | 0.00763714 | 49.3417 | 436.52 | 0.00 | 2118.27 | 2118.27 | 0.20034192 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 23.17 | 15.65 | 0.00800000 | 43633.1 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4609.731 | 4609.731 | 0.233419 | 0.00004033 | 102.751 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 0.3842 | 0.391957 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4609.73 | 4609.73 | 1.0000 | 0.28074232 | 0.233419 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.04032382 | 60.00 | 32.22 | 27.78 | 0.000 | 4609.73 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.87 | 0.00779060 | 21.00 | 0.00779060 | 50.3211 | 2263.20 | 0.00 | 4625.55 | 4625.55 | 0.28074232 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.96 | 17.69 | 0.00800000 | 49536.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2228.033 | 2228.033 | 0.221543 | 0.00001949 | 44.915 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 0.1857 | 0.189445 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 2228.03 | 2228.03 | 1.0000 | 0.26645899 | 0.221543 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.01948982 | 60.00 | 32.22 | 27.78 | 0.000 | 2228.03 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 0.00 | 0.00 | 2236.25 | 2236.25 | 0.26645899 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 107373.311 | 107373.311 | 3.198969 | 0.00093935 | 2834.763 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 8.9496 | 9.129752 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 107373.31 | 107373.31 | 1.0000 | 3.84752411 | 3.198969 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.93925274 | 60.00 | 32.22 | 27.78 | 0.000 | 107373.31 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00788146 | 21.00 | 0.00788146 | 50.9012 | 75209.82 | 0.00 | 107747.49 | 107747.49 | 3.84752411 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.26 | 21.26 | 0.00800000 | 61064.2 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 71653.359 | 71653.359 | 2.135107 | 0.00062685 | 1891.582 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 5.9724 | 6.092551 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 71653.36 | 71653.36 | 1.0000 | 2.56797667 | 2.135107 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.62679090 | 60.00 | 32.22 | 27.78 | 0.000 | 71653.36 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00788470 | 21.00 | 0.00788470 | 50.9218 | 50186.16 | 0.00 | 71902.06 | 71902.06 | 2.56797667 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.26 | 21.26 | 0.00800000 | 61059.3 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 107095.234 | 107095.234 | 3.190642 | 0.00093692 | 2827.439 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 8.9265 | 9.106107 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 107095.23 | 107095.23 | 1.0000 | 3.83750915 | 3.190642 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.93682025 | 60.00 | 32.22 | 27.78 | 0.000 | 107095.23 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00788102 | 21.00 | 0.00788102 | 50.8983 | 75015.49 | 0.00 | 107468.56 | 107468.56 | 3.83750915 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.26 | 21.26 | 0.00800000 | 61064.6 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 60816.038 | 60816.038 | 1.827515 | 0.00053205 | 1599.332 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 5.0691 | 5.171074 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 60816.04 | 60816.04 | 1.0000 | 2.19802308 | 1.827515 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.53199096 | 60.00 | 32.22 | 27.78 | 0.000 | 60816.04 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.92 | 0.00784588 | 21.00 | 0.00784588 | 50.6743 | 42442.90 | 0.00 | 60997.55 | 60997.55 | 2.19802308 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.01 | 21.19 | 0.00800000 | 60810.9 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15571.900 | 15571.900 | 0.464501 | 0.00013623 | 410.883 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 1.2979 | 1.324050 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15571.90 | 15571.90 | 1.0000 | 0.55867352 | 0.464501 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.13621588 | 60.00 | 32.22 | 27.78 | 0.000 | 15571.90 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00793366 | 21.00 | 0.00793366 | 51.2338 | 10901.17 | 0.00 | 15624.51 | 15624.51 | 0.55867352 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61027.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10280.341 | 10280.341 | 0.306679 | 0.00008994 | 271.250 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 0.8569 | 0.874118 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10280.34 | 10280.34 | 1.0000 | 0.36885441 | 0.306679 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.08992774 | 60.00 | 32.22 | 27.78 | 0.000 | 10280.34 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00793501 | 21.00 | 0.00793501 | 51.2424 | 7196.57 | 0.00 | 10315.01 | 10315.01 | 0.36885441 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61024.8 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15540.919 | 15540.919 | 0.463574 | 0.00013596 | 410.067 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 1.2953 | 1.321415 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15540.92 | 15540.92 | 1.0000 | 0.55755816 | 0.463574 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.13594487 | 60.00 | 32.22 | 27.78 | 0.000 | 15540.92 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00793346 | 21.00 | 0.00793346 | 51.2325 | 10879.52 | 0.00 | 15593.43 | 15593.43 | 0.55755816 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61027.2 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9288.974 | 9288.974 | 0.277038 | 0.00008126 | 245.120 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 0.7742 | 0.789824 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9288.97 | 9288.97 | 1.0000 | 0.33320426 | 0.277038 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.08125571 | 60.00 | 32.22 | 27.78 | 0.000 | 9288.97 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00791790 | 21.00 | 0.00791790 | 51.1334 | 6503.35 | 0.00 | 9320.49 | 9320.49 | 0.33320426 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61032.1 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 245910.094 | -999.000 | 8.454440 | 0.01046158 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.4081 | 1004.8586 | 1.2027 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.454440 | 10.16848377 | 4197.9300 | 999.8980 | 128.37404211 | 12.27 | 6.67 | 5.60 | 3017869.36 | 8.1485 | 8.148467 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 245910.09 | 163588.63 | 1.0000 | 10.16848377 | 8.454440 | 26.99 | 19.86 | 0.01160230 | 56719.2 | 11.05 | 11.05 | 0.00850000 | 32535.6 | 10.46051666 | 6.67 | 12.27 | 5.60 | 18269.594 | 227640.50 | 33.20 | 0.01716721 | 25.32 | 2.53819000 | 30.0220 | 24.00 | 0.00892207 | 24.00 | 0.00892207 | 47.9430 | 107339.87 | 0.00 | 246253.61 | 160459.92 | 10.16848377 | 26.99 | 19.88 | 0.01160230 | 56719.2 | 11.62 | 11.36 | 0.00825756 | 32501.8 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 12568.003 | 12568.003 | 2.536332 | 0.00010995 | 223.643 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.454440 | 10.16848377 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 1.0476 | 1.068634 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 12568.00 | 12568.00 | 1.0000 | 3.05054513 | 2.536332 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 0.10993915 | 60.00 | 32.22 | 27.78 | 0.000 | 12568.00 | 8.70 | 0.00699286 | 8.70 | 2.53819000 | 100.0733 | 4.93 | 0.00715576 | 21.46 | 0.00741163 | 46.5825 | 0.00 | 0.00 | 13625.10 | 13625.10 | 3.05054513 | 2.80 | 2.80 | 0.00699286 | 20338.7 | 7.19 | 7.19 | 0.00699286 | 24805.1 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2412859.738 | -999.000 | 78.040836 | 0.10264863 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.2076 | 1004.8586 | 1.2027 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 78.040836 | 93.86275144 | 4197.9300 | 999.8980 | 128.37404211 | 12.27 | 6.67 | 5.60 | 3017869.36 | 79.9524 | 79.952425 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2412859.74 | 1548581.72 | 1.0000 | 93.86275144 | 78.040836 | 27.41 | 20.31 | 0.01203240 | 58243.2 | 11.05 | 11.05 | 0.00850000 | 32537.0 | 102.63815983 | 6.67 | 12.27 | 5.60 | 168642.090 | 2244217.65 | 33.20 | 0.01716721 | 25.32 | 25.38195000 | 32.5239 | 24.00 | 0.00901357 | 24.00 | 0.00901357 | 48.4281 | 942420.46 | 0.00 | 2416417.17 | 1525337.00 | 93.86275144 | 27.41 | 20.32 | 0.01203240 | 58243.2 | 11.59 | 11.36 | 0.00826886 | 32499.1 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 116012.114 | 116012.114 | 23.412251 | 0.00101492 | 2064.389 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 78.040836 | 93.86275144 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 9.6697 | 9.864293 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 116012.11 | 116012.11 | 1.0000 | 28.15882543 | 23.412251 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 1.01482105 | 60.00 | 32.22 | 27.78 | 0.000 | 116012.11 | 8.70 | 0.00699286 | 8.70 | 25.38195000 | 108.4131 | 20.77 | 0.00793922 | 21.00 | 0.00792132 | 51.1550 | 385485.31 | 0.00 | 125769.95 | 125769.95 | 28.15882543 | 2.80 | 2.80 | 0.00699286 | 20338.7 | 7.19 | 7.19 | 0.00699286 | 24805.1 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 237887.928 | -999.000 | 8.415821 | 0.01012030 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.0797 | 1004.8586 | 1.2027 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.415821 | 10.12203550 | 4197.9300 | 999.8980 | 128.37404211 | 12.27 | 6.67 | 5.60 | 3017869.36 | 7.8826 | 7.882645 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 237887.93 | 160568.63 | 1.0000 | 10.12203550 | 8.415821 | 26.76 | 19.66 | 0.01142563 | 56037.0 | 11.05 | 11.05 | 0.00850000 | 32535.0 | 10.11927002 | 6.67 | 12.27 | 5.60 | 18186.141 | 219701.79 | 33.13 | 0.01716709 | 25.31 | 2.53819000 | 30.1597 | 24.00 | 0.00893238 | 24.00 | 0.00893238 | 47.9981 | 115242.55 | 0.00 | 238213.44 | 157200.05 | 10.12203550 | 26.76 | 19.67 | 0.01142563 | 56037.0 | 11.63 | 11.36 | 0.00825279 | 32502.9 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 12510.594 | 12510.594 | 2.524746 | 0.00010945 | 222.621 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.415821 | 10.12203550 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 1.0428 | 1.063752 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:20:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12510.59 | 12510.59 | 1.0000 | 3.03661065 | 2.524746 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 0.10943697 | 60.00 | 32.22 | 27.78 | 0.000 | 12510.59 | 8.70 | 0.00699286 | 8.70 | 2.53819000 | 100.5325 | 21.00 | 0.00797766 | 21.00 | 0.00797766 | 51.5138 | 59158.96 | 0.00 | 13562.87 | 13562.87 | 3.03661065 | 2.80 | 2.80 | 0.00699286 | 20338.7 | 7.19 | 7.19 | 0.00699286 | 24805.1 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 121211.599 | -999.000 | 4.958153 | 0.00515662 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.2646 | 1004.8586 | 1.2027 | CAV_BAS FAN | Fan:ConstantVolume | 4.958153 | 5.96336358 | 4197.9300 | 999.8980 | 128.37404211 | 12.27 | 6.67 | 5.60 | 3017869.36 | 4.0165 | 4.016463 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 121211.60 | 83127.63 | 1.0000 | 5.96336358 | 4.958153 | 25.13 | 18.80 | 0.01098716 | 53244.8 | 11.42 | 11.42 | 0.00850000 | 32918.7 | 5.15609560 | 6.67 | 12.27 | 5.60 | 8407.314 | 112804.29 | 28.67 | 0.01715859 | 24.15 | 1.20019084 | 24.2064 | 24.00 | 0.00900898 | 24.00 | 0.00900898 | 48.4034 | 67972.00 | 0.00 | 121390.38 | 81295.56 | 5.96336358 | 25.13 | 18.81 | 0.01098716 | 53244.8 | 11.84 | 11.52 | 0.00832220 | 32888.7 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 227073.876 | 227073.876 | 4.958153 | 0.00198654 | 5209.475 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | CAV_BAS FAN | Fan:ConstantVolume | 4.958153 | 5.96336358 | 4197.9300 | 999.8980 | 10.28782341 | 54.44 | 82.22 | 27.78 | 1199750.49 | 18.9268 | 19.307667 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 227073.88 | 227073.88 | 1.0000 | 5.96336358 | 4.958153 | 2.11 | 2.11 | 0.00699286 | 19632.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 1.98633868 | 60.00 | 32.22 | 27.78 | 0.000 | 227073.88 | 8.70 | 0.00699286 | 8.70 | 1.20019084 | 24.2064 | 0.00 | 0.00699286 | 26.35 | 0.00699286 | 32.7686 | 0.00 | 0.00 | 197472.72 | 197472.72 | 5.96336358 | 12.80 | 10.55 | 0.00699286 | 30517.1 | 45.33 | 22.02 | 0.00699286 | 63631.4 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9382.001 | 6719.372 | 0.458252 | 0.00022976 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3597 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | Sensible | 8797.29 | 8310.23 | 0.9377 | -999.0 | -999.0 | 28.08 | 18.10 | 0.00888659 | 50905.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8797.29 | 30.92 | 0.01716288 | 24.74 | 0.01563279 | -999.0000 | 27.00 | 0.00859148 | 27.00 | 0.00859148 | 38.6531 | 7913.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 89399.084 | 63930.520 | 4.353986 | 0.00218938 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3962 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:20:00 | Sensible | 83868.49 | 79005.04 | 0.9381 | -999.0 | -999.0 | 28.09 | 18.12 | 0.00890621 | 50962.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 83868.49 | 30.92 | 0.01716288 | 24.74 | 0.15632792 | -999.0000 | 27.00 | 0.00859615 | 27.00 | 0.00859615 | 38.6742 | 75280.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9067.885 | 6488.148 | 0.442100 | 0.00022207 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3791 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8505.42 | 8022.80 | 0.9380 | -999.0 | -999.0 | 28.09 | 18.11 | 0.00889702 | 50941.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8505.42 | 31.09 | 0.01716319 | 24.78 | 0.01563279 | -999.0000 | 27.00 | 0.00859395 | 27.00 | 0.00859395 | 38.6642 | 7704.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9382.001 | 9382.001 | 0.458252 | 0.00022976 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9382.00 | 9382.00 | 1.0000 | 0.55115781 | 0.458252 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9382.00 | 8.70 | 0.00699286 | 8.70 | 0.01563279 | 3.4114 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 89399.084 | 89399.084 | 4.353986 | 0.00218938 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 89399.08 | 89399.08 | 1.0000 | 5.23670822 | 4.353986 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89399.08 | 8.70 | 0.00699286 | 8.70 | 0.15632792 | 3.5905 | 0.00 | 0.00849456 | 25.35 | 0.00849456 | 42.1263 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9067.885 | 9067.885 | 0.442100 | 0.00022207 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9067.88 | 9067.88 | 1.0000 | 0.53173064 | 0.442100 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9067.88 | 8.70 | 0.00699286 | 8.70 | 0.01563279 | 3.5360 | 0.00 | 0.00736003 | 24.44 | 0.00736003 | 38.6045 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 591.367 | 591.367 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.458252 | 0.55115781 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 591.37 | 591.37 | 1.0000 | 0.55115781 | 0.458252 | 0.30 | 0.30 | 0.00844859 | 21432.3 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 591.37 | 8.70 | 0.00699286 | 8.70 | 0.01563279 | 3.4114 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5913.672 | 5913.672 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.353986 | 5.23670822 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 5913.67 | 5913.67 | 1.0000 | 5.23670822 | 4.353986 | 0.31 | 0.31 | 0.00844064 | 21428.3 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5913.67 | 8.70 | 0.00699286 | 8.70 | 0.15632792 | 3.5905 | 0.00 | 0.00849456 | 25.35 | 0.00849456 | 42.1263 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 591.367 | 591.367 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.442100 | 0.53173064 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 591.37 | 591.37 | 1.0000 | 0.53173064 | 0.442100 | 0.31 | 0.31 | 0.00734704 | 18687.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 591.37 | 8.70 | 0.00699286 | 8.70 | 0.01563279 | 3.5360 | 0.00 | 0.00736003 | 24.44 | 0.00736003 | 38.6045 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5685.17 | 2123.67 | 2122.17 |
CORE_BOTTOM | 5678.00 | 9.50 | 0.67 |
CORE_MID | 5303.17 | 122.17 | 0.00 |
CORE_TOP | 5092.83 | 447.50 | 0.00 |
PERIMETER_BOT_ZN_3 | 5366.33 | 278.17 | 32.67 |
PERIMETER_BOT_ZN_2 | 5412.17 | 401.83 | 193.67 |
PERIMETER_BOT_ZN_1 | 5630.17 | 348.50 | 245.50 |
PERIMETER_BOT_ZN_4 | 5739.33 | 684.67 | 652.83 |
PERIMETER_MID_ZN_3 | 4887.50 | 875.67 | 176.67 |
PERIMETER_MID_ZN_2 | 4344.00 | 768.00 | 390.33 |
PERIMETER_MID_ZN_1 | 5495.17 | 567.33 | 374.17 |
PERIMETER_MID_ZN_4 | 5293.83 | 772.17 | 379.67 |
PERIMETER_TOP_ZN_3 | 4726.17 | 1235.00 | 317.83 |
PERIMETER_TOP_ZN_2 | 5027.33 | 1035.00 | 460.83 |
PERIMETER_TOP_ZN_1 | 5334.17 | 814.00 | 469.83 |
PERIMETER_TOP_ZN_4 | 5082.83 | 1049.00 | 457.67 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1333.33 | 1333.33 |
DATACENTER_MID_ZN_6 | 5943.00 | 9.00 | 9.00 |
DATACENTER_TOP_ZN_6 | 5939.33 | 235.67 | 235.67 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 98.00 | 0.00 | 4.83 |
CORE_BOTTOM | 0.00 | 1.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 4.83 | 0.00 | 0.67 |
PERIMETER_BOT_ZN_2 | 0.00 | 28.33 | 0.00 | 25.67 |
PERIMETER_BOT_ZN_1 | 0.00 | 89.33 | 0.00 | 83.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 269.33 | 0.00 | 85.83 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 35.50 | 0.00 | 34.67 |
PERIMETER_MID_ZN_1 | 0.00 | 145.00 | 0.00 | 143.17 |
PERIMETER_MID_ZN_4 | 0.00 | 58.83 | 0.00 | 30.17 |
PERIMETER_TOP_ZN_3 | 0.00 | 17.50 | 0.00 | 12.83 |
PERIMETER_TOP_ZN_2 | 0.00 | 66.17 | 0.00 | 56.33 |
PERIMETER_TOP_ZN_1 | 0.00 | 82.67 | 0.00 | 74.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 75.17 | 0.00 | 37.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 611.33 | 0.00 | 317.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.521 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.488 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.464 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.458 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.579 | 0.011 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.681 | 0.012 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.718 | 0.011 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 1.060 | 0.012 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.571 | 0.026 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.721 | 0.029 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.757 | 0.026 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.819 | 0.027 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.564 | 0.033 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.760 | 0.034 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.746 | 0.033 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.808 | 0.034 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.584 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.584 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.584 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.572 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.572 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.572 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 60.99 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 0.847 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.86 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.011 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.79 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.110 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.011 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 783.68 | 0.239 | ||
Total Facility | 1010.73 | 2493.19 | 126016.35 | 46320.38 | 1.3878 | 157.549 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 23536663.13 | 0.00 | 23536663.13 | 0.00 | 23536663.13 | 29876159.83 | 3312.56 | 504.00 | 4943.44 | 715.70 |
CORE_BOTTOM | 24731232.86 | 0.00 | 24731232.86 | 0.00 | 24731232.86 | 33990283.35 | 7719.44 | 337.10 | 703.46 | 1391.81 |
CORE_MID | 0.20E+09 | 0.00 | 0.20E+09 | 0.00 | 0.20E+09 | 0.34E+09 | 6990.06 | 1227.19 | 542.75 | 492.35 |
CORE_TOP | 20225119.89 | 0.00 | 20225119.89 | 0.00 | 20225119.89 | 33990283.35 | 7532.46 | 907.02 | 320.51 | 530.26 |
PERIMETER_BOT_ZN_3 | 3559226.29 | 0.00 | 3559226.29 | 104952.48 | 3664178.76 | 4267819.30 | 4876.26 | 856.42 | 3027.32 | 1391.81 |
PERIMETER_BOT_ZN_2 | 2667678.59 | 0.00 | 2667678.59 | 69968.27 | 2737646.86 | 2750345.05 | 2725.01 | 125.28 | 5909.71 | 1391.81 |
PERIMETER_BOT_ZN_1 | 4259171.22 | 0.00 | 4259171.22 | 104952.48 | 4364123.70 | 4267912.63 | 3760.43 | 823.66 | 4175.90 | 1391.81 |
PERIMETER_BOT_ZN_4 | 4130528.39 | 0.00 | 4130528.39 | 69968.27 | 4200496.66 | 2750345.05 | 2052.89 | 0.42 | 6706.69 | 1391.81 |
PERIMETER_MID_ZN_3 | 30862652.72 | 0.00 | 30862652.72 | 246137.54 | 31108790.26 | 42678193.03 | 4752.21 | 1182.70 | 2825.09 | 492.35 |
PERIMETER_MID_ZN_2 | 26186577.02 | 0.00 | 26186577.02 | 164091.58 | 26350668.60 | 27503450.52 | 3360.24 | 36.08 | 5363.68 | 1401.35 |
PERIMETER_MID_ZN_1 | 40208570.27 | 0.00 | 40208570.27 | 246137.54 | 40454707.81 | 42679126.28 | 3663.07 | 1017.98 | 4078.95 | 492.35 |
PERIMETER_MID_ZN_4 | 28434204.65 | 0.00 | 28434204.65 | 164091.58 | 28598296.23 | 27503450.52 | 3301.40 | 27.71 | 5430.89 | 492.35 |
PERIMETER_TOP_ZN_3 | 3073448.10 | 0.00 | 3073448.10 | 305599.26 | 3379047.36 | 4267819.30 | 5336.54 | 644.61 | 2778.85 | 530.26 |
PERIMETER_TOP_ZN_2 | 2641269.37 | 0.00 | 2641269.37 | 203732.70 | 2845002.07 | 2750345.05 | 3243.20 | 19.07 | 5497.73 | 530.26 |
PERIMETER_TOP_ZN_1 | 3992950.57 | 0.00 | 3992950.57 | 305599.26 | 4298549.83 | 4267912.63 | 3655.83 | 1120.69 | 3983.48 | 530.26 |
PERIMETER_TOP_ZN_4 | 2841727.37 | 0.00 | 2841727.37 | 203732.70 | 3045460.06 | 2750345.05 | 3197.38 | 3.35 | 5559.27 | 530.26 |
DATACENTER_BOT_ZN_6 | 492995.74 | 0.00 | 492995.74 | 0.00 | 492995.74 | 389144.62 | 0.00 | 504.00 | 8256.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929957.41 | 0.00 | 4929957.41 | 0.00 | 4929957.41 | 3891446.16 | 0.00 | 504.00 | 8256.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492995.74 | 0.00 | 492995.74 | 0.00 | 492995.74 | 389144.62 | 0.00 | 504.00 | 8256.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8423799.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 0.34E+10 | 0.00 | 0.34E+10 | 9573087.90 | 0.34E+10 | 0.50E+10 | 8760.00 | 2944.32 | 8760.00 | 3726.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9556 | 0.0000 | 0.9556 | 0.0000 | 0.9556 | 0.9949 | 1211.26 | 504.00 | 4227.74 |
CORE_BOTTOM | 0.9068 | 0.0000 | 0.9068 | 0.0000 | 0.9068 | 1.0778 | 5041.22 | 212.30 | 689.48 |
CORE_MID | 8.6243 | 0.0000 | 8.6243 | 0.0000 | 8.6243 | 10.7782 | 4587.28 | 822.43 | 533.29 |
CORE_TOP | 0.8506 | 0.0000 | 0.8506 | 0.0000 | 0.8506 | 1.0778 | 4924.63 | 701.94 | 316.44 |
PERIMETER_BOT_ZN_3 | 0.1350 | 0.0000 | 0.1350 | 0.0026 | 0.1377 | 0.1353 | 2505.88 | 426.19 | 3010.93 |
PERIMETER_BOT_ZN_2 | 0.1024 | 0.0000 | 0.1024 | 0.0017 | 0.1042 | 0.0872 | 1277.63 | 117.84 | 4547.54 |
PERIMETER_BOT_ZN_1 | 0.1675 | 0.0000 | 0.1675 | 0.0026 | 0.1702 | 0.1353 | 1437.69 | 358.23 | 4147.08 |
PERIMETER_BOT_ZN_4 | 0.1593 | 0.0000 | 0.1593 | 0.0017 | 0.1611 | 0.0872 | 626.96 | 0.22 | 5315.83 |
PERIMETER_MID_ZN_3 | 1.3307 | 0.0000 | 1.3307 | 0.0062 | 1.3369 | 1.3533 | 2332.33 | 798.21 | 2812.46 |
PERIMETER_MID_ZN_2 | 1.0835 | 0.0000 | 1.0835 | 0.0043 | 1.0878 | 0.8721 | 976.21 | 26.57 | 4031.22 |
PERIMETER_MID_ZN_1 | 1.7645 | 0.0000 | 1.7645 | 0.0062 | 1.7707 | 1.3533 | 1221.28 | 673.18 | 4048.54 |
PERIMETER_MID_ZN_4 | 1.2302 | 0.0000 | 1.2302 | 0.0041 | 1.2343 | 0.8721 | 974.17 | 27.66 | 4941.17 |
PERIMETER_TOP_ZN_3 | 0.1315 | 0.0000 | 0.1315 | 0.0076 | 0.1392 | 0.1353 | 2631.04 | 555.03 | 2756.93 |
PERIMETER_TOP_ZN_2 | 0.1143 | 0.0000 | 0.1143 | 0.0051 | 0.1193 | 0.0872 | 953.86 | 18.75 | 4970.39 |
PERIMETER_TOP_ZN_1 | 0.1741 | 0.0000 | 0.1741 | 0.0076 | 0.1817 | 0.1353 | 1219.38 | 782.38 | 3941.24 |
PERIMETER_TOP_ZN_4 | 0.1214 | 0.0000 | 0.1214 | 0.0051 | 0.1265 | 0.0872 | 910.46 | 3.32 | 5029.23 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0130 | 0.00 | 504.00 | 5439.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1296 | 0.00 | 504.00 | 5439.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0130 | 0.00 | 504.00 | 5439.00 |
DATACENTER_BASEMENT_ZN_6 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.2805 | 5943.00 | 0.00 | 0.00 |
Total Facility | 145.7459 | 0.0000 | 145.7459 | 0.2416 | 145.9874 | 157.9346 | 5943.00 | 2063.38 | 5943.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 56919837.46 | 0.00 | 56919837.46 | 48026705.38 | 2050.59 | 0.00 | 6709.41 | 1391.81 |
VAV_MID WITH REHEAT | 0.48E+09 | 0.00 | 0.48E+09 | 0.48E+09 | 3238.42 | 0.00 | 5521.58 | 492.35 |
VAV_TOP WITH REHEAT | 47410991.24 | 0.00 | 47410991.24 | 48026705.38 | 3190.92 | 0.00 | 5569.08 | 530.26 |
CAV_BAS | 34047688.41 | 0.00 | 34047688.41 | 29876159.83 | 3312.56 | 0.00 | 5447.44 | 715.70 |
AIRLOOP DATACENTER BOT | 713158.25 | 0.00 | 713158.25 | 389144.62 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 7131582.45 | 0.00 | 7131582.45 | 3891446.16 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 713158.25 | 0.00 | 713158.25 | 389144.62 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.1281 | 0.0000 | 2.1281 | 1.5229 | 625.39 | 0.00 | 5317.61 |
VAV_MID WITH REHEAT | 20.3820 | 0.0000 | 20.3820 | 15.2292 | 913.76 | 0.00 | 5029.24 |
VAV_TOP WITH REHEAT | 2.0134 | 0.0000 | 2.0134 | 1.5229 | 904.19 | 0.00 | 5038.81 |
CAV_BAS | 1.3823 | 0.0000 | 1.3823 | 0.9949 | 1211.26 | 0.00 | 4731.74 |
AIRLOOP DATACENTER BOT | 0.0226 | 0.0000 | 0.0226 | 0.0130 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2261 | 0.0000 | 0.2261 | 0.1296 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0226 | 0.0000 | 0.0226 | 0.0130 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6709.41 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5521.58 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5569.08 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 5447.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.3787 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 24.0864 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.3751 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7364 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2261 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 7 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1358 |
Defaulted Fields | 1168 |
Fields with Defaults | 3880 |
Autosized Fields | 317 |
Autosizable Fields | 394 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 26735.18 | 288578.70 | 22-JAN-05:00 | 1654085.04 | 23-AUG-16:00 |
Electricity:Building | 16700.32 | 216790.79 | 29-MAY-17:10 | 974384.39 | 15-DEC-17:00 |
Electricity:Zone:BASEMENT | 559.97 | 14115.26 | 01-JAN-00:10 | 25295.37 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 16700.32 | 216790.79 | 29-MAY-17:10 | 974384.39 | 15-DEC-17:00 |
InteriorLights:Electricity | 2023.92 | 9514.02 | 01-JAN-10:20 | 198852.03 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 135.58 | 657.72 | 01-JAN-00:10 | 11837.83 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2023.92 | 9514.02 | 01-JAN-10:20 | 198852.03 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity | 2023.92 | 9514.02 | 01-JAN-10:20 | 198852.03 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 135.58 | 657.72 | 01-JAN-00:10 | 11837.83 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2023.92 | 9514.02 | 01-JAN-10:20 | 198852.03 | 27-SEP-07:10 |
Electricity:Zone:CORE_BOTTOM | 411.37 | 5043.91 | 01-JAN-00:10 | 27837.83 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4113.71 | 50438.97 | 01-JAN-00:10 | 278377.67 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1217.58 | 5906.80 | 01-JAN-00:10 | 106312.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1217.58 | 5906.80 | 01-JAN-00:10 | 106312.04 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 411.37 | 5043.90 | 01-JAN-00:10 | 27837.77 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 121.76 | 590.68 | 01-JAN-00:10 | 10631.20 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 45.32 | 594.46 | 23-APR-17:10 | 3495.41 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.95 | 35.29 | 01-JAN-10:20 | 1334.85 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 8.95 | 35.29 | 01-JAN-10:20 | 1334.85 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 29.16 | 384.35 | 09-JUL-17:10 | 2252.57 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.72 | 22.74 | 01-JAN-07:50 | 860.23 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 5.72 | 22.74 | 01-JAN-07:50 | 860.23 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 45.13 | 594.47 | 23-APR-17:10 | 3495.47 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.76 | 35.29 | 01-JAN-07:40 | 1334.88 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 8.76 | 35.29 | 01-JAN-07:40 | 1334.88 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 29.16 | 383.09 | 12-MAR-17:10 | 2252.56 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.73 | 22.74 | 01-JAN-10:20 | 860.23 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 5.73 | 22.74 | 01-JAN-10:20 | 860.23 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 453.14 | 5944.59 | 23-APR-17:10 | 34954.06 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 89.48 | 352.88 | 01-JAN-10:10 | 13348.54 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 89.48 | 352.88 | 01-JAN-10:10 | 13348.54 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 291.54 | 3842.04 | 09-JUL-17:10 | 22525.72 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 57.19 | 227.41 | 01-JAN-07:50 | 8602.31 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 57.19 | 227.41 | 01-JAN-07:50 | 8602.31 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 451.28 | 5944.68 | 23-APR-17:10 | 34954.68 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 87.62 | 352.89 | 01-JAN-07:40 | 13348.83 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 87.62 | 352.89 | 01-JAN-07:40 | 13348.83 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 291.60 | 3830.90 | 12-MAR-17:10 | 22525.63 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 57.25 | 227.41 | 01-JAN-10:10 | 8602.31 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 57.25 | 227.41 | 01-JAN-10:10 | 8602.31 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 45.31 | 594.46 | 23-APR-17:10 | 3495.41 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.95 | 35.29 | 01-JAN-10:10 | 1334.85 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 8.95 | 35.29 | 01-JAN-10:10 | 1334.85 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 29.15 | 384.20 | 09-JUL-17:10 | 2252.57 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.72 | 22.74 | 01-JAN-07:50 | 860.23 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 5.72 | 22.74 | 01-JAN-07:50 | 860.23 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 45.13 | 594.47 | 23-APR-17:10 | 3495.47 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.76 | 35.29 | 01-JAN-07:40 | 1334.88 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 8.76 | 35.29 | 01-JAN-07:40 | 1334.88 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 29.16 | 383.09 | 12-MAR-17:10 | 2252.56 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.72 | 22.74 | 01-JAN-10:10 | 860.23 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 5.72 | 22.74 | 01-JAN-10:10 | 860.23 | 27-SEP-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7533.08 | 95093.58 | 01-JAN-00:10 | 382970.28 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 38.23 | 185.45 | 01-JAN-00:10 | 3337.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 38.23 | 185.45 | 01-JAN-00:10 | 3337.76 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.14 | 1964.44 | 01-JAN-00:10 | 8079.39 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1571.44 | 19644.38 | 01-JAN-00:10 | 80793.90 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 32.64 | 158.32 | 01-JAN-00:10 | 2849.68 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 32.64 | 158.32 | 01-JAN-00:10 | 2849.68 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.14 | 1964.44 | 01-JAN-00:10 | 8079.39 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.26 | 15.83 | 01-JAN-00:10 | 284.97 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 4544.76 | 1407.46 | 25-JAN-05:50 | 395316.91 | 03-OCT-13:10 |
HeatRejection:Electricity | 929.75 | 699.77 | 25-JAN-07:00 | 56753.04 | 02-JAN-09:10 |
General:HeatRejection:Electricity | 929.75 | 699.77 | 25-JAN-07:00 | 56753.04 | 02-JAN-09:10 |
Electricity:HVAC | 1962.45 | 10306.52 | 22-JAN-06:00 | 185744.04 | 24-JUL-16:00 |
ExteriorEquipment:Electricity | 3258.17 | 45245.36 | 01-JAN-00:10 | 185194.46 | 29-DEC-08:40 |
Transformer:ExteriorEquipment:Electricity | 54.48 | 979.82 | 01-JAN-00:10 | 3387.38 | 27-SEP-07:20 |
ElectricityPurchased:Facility | 26735.18 | 288578.70 | 22-JAN-05:00 | 1654085.04 | 23-AUG-16:00 |
ElectricityPurchased:Plant | 26735.18 | 288578.70 | 22-JAN-05:00 | 1654085.04 | 23-AUG-16:00 |
Cogeneration:ElectricityPurchased | 26735.18 | 288578.70 | 22-JAN-05:00 | 1654085.04 | 23-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 26735.18 | 288578.70 | 22-JAN-05:00 | 1654085.04 | 23-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 26735.18 | 288578.70 | 22-JAN-05:00 | 1654085.04 | 23-AUG-16:00 |
ElectricityNet:Plant | 26735.18 | 288578.70 | 22-JAN-05:00 | 1654085.04 | 23-AUG-16:00 |
Cogeneration:ElectricityNet | 26735.18 | 288578.70 | 22-JAN-05:00 | 1654085.04 | 23-AUG-16:00 |
General:Cogeneration:ElectricityNet | 26735.18 | 288578.70 | 22-JAN-05:00 | 1654085.04 | 23-AUG-16:00 |
Fans:Electricity | 1304.80 | 5885.43 | 05-FEB-11:20 | 152921.49 | 24-JUL-16:00 |
General:Fans:Electricity | 1304.80 | 5885.43 | 05-FEB-11:20 | 152921.49 | 24-JUL-16:00 |
ExteriorLights:Electricity | 323.97 | 0.00 | 01-JAN-07:20 | 37611.08 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 323.97 | 0.00 | 01-JAN-07:20 | 37611.08 | 01-JAN-06:10 |
ComputerHVAC:ExteriorEquipment:Electricity | 1349.07 | 17083.47 | 01-JAN-00:10 | 68333.87 | 31-MAR-23:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 119.90 | 0.00 | 01-JAN-00:10 | 5613.48 | 01-JAN-08:50 |
General:HeatRecovery:Electricity | 119.90 | 0.00 | 01-JAN-00:10 | 5613.48 | 01-JAN-08:50 |
Cooling:Electricity | 2929.24 | 3312.55 | 26-JAN-06:00 | 294154.24 | 31-AUG-13:10 |
General:Cooling:Electricity | 2929.24 | 3312.55 | 26-JAN-06:00 | 294154.24 | 31-AUG-13:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 1169.03 | 666.97 | 01-JAN-00:10 | 69139.04 | 06-OCT-15:30 |
General:Pumps:Electricity | 1169.03 | 666.97 | 01-JAN-00:10 | 69139.04 | 06-OCT-15:30 |
WIRED_LTG_ELECTRICITY | 56.87 | 0.00 | 01-JAN-00:10 | 5587.74 | 27-SEP-07:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 564.81 | 5695.87 | 01-JAN-00:10 | 88425.82 | 04-FEB-06:10 |
NaturalGas:Plant | 564.81 | 5695.87 | 01-JAN-00:10 | 88425.82 | 04-FEB-06:10 |
Heating:NaturalGas | 0.82 | 0.00 | 01-JAN-00:10 | 62214.37 | 04-FEB-06:10 |
Boiler:Heating:NaturalGas | 0.82 | 0.00 | 01-JAN-00:10 | 62214.37 | 04-FEB-06:10 |
WaterSystems:NaturalGas | 563.99 | 5695.87 | 01-JAN-00:10 | 68192.61 | 13-JAN-12:20 |
Water Heater:WaterSystems:NaturalGas | 563.99 | 5695.87 | 01-JAN-00:10 | 68192.61 | 13-JAN-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 19540.34 | 16721.14 | 26-JAN-06:00 | 1688127.02 | 22-JUN-05:10 |
PlantLoopCoolingDemand:HVAC | 19540.34 | 16721.14 | 26-JAN-06:00 | 1688127.02 | 22-JUN-05:10 |
CoolingCoils:PlantLoopCoolingDemand | 19540.34 | 16721.14 | 26-JAN-06:00 | 1688127.02 | 22-JUN-05:10 |
DistrictCooling:Facility | 7209.48 | 88616.59 | 27-MAY-18:40 | 370450.14 | 21-AUG-14:00 |
DistrictCooling:HVAC | 7209.48 | 88616.59 | 27-MAY-18:40 | 370450.14 | 21-AUG-14:00 |
Cooling:DistrictCooling | 7209.48 | 88616.59 | 27-MAY-18:40 | 370450.14 | 21-AUG-14:00 |
General:Cooling:DistrictCooling | 7209.48 | 88616.59 | 27-MAY-18:40 | 370450.14 | 21-AUG-14:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 15234.28 | 0.00 | 01-JAN-00:10 | 0.00 | 22-MAY-13:00 |
Water:Plant | 15234.28 | 0.00 | 01-JAN-00:10 | 0.00 | 22-MAY-13:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 15234.28 | 0.00 | 01-JAN-00:10 | 0.00 | 22-MAY-13:00 |
MainsWater:Plant | 15234.28 | 0.00 | 01-JAN-00:10 | 0.00 | 22-MAY-13:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 12954.11 | 0.00 | 01-JAN-00:10 | 0.00 | 22-MAY-13:00 |
General:HeatRejection:Water | 12954.11 | 0.00 | 01-JAN-00:10 | 0.00 | 22-MAY-13:00 |
HeatRejection:MainsWater | 12954.11 | 0.00 | 01-JAN-00:10 | 0.00 | 22-MAY-13:00 |
General:HeatRejection:MainsWater | 12954.11 | 0.00 | 01-JAN-00:10 | 0.00 | 22-MAY-13:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 96248.09 | 114058.04 | 26-JAN-05:40 | 9022624.78 | 31-AUG-15:30 |
EnergyTransfer:Building | 21019.59 | 100524.21 | 26-JAN-05:40 | 1454316.12 | 31-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 688.41 | 0.00 | 01-JAN-00:10 | 69334.75 | 17-JAN-06:20 |
Heating:EnergyTransfer | 11.02 | 0.00 | 01-JAN-00:10 | 27693.19 | 04-FEB-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.45 | 0.00 | 01-JAN-00:10 | 21053.65 | 29-JUL-16:10 |
General:Heating:EnergyTransfer | 11.02 | 0.00 | 01-JAN-00:10 | 27693.19 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.45 | 0.00 | 01-JAN-00:10 | 21053.65 | 29-JUL-16:10 |
Cooling:EnergyTransfer | 21008.57 | 100524.21 | 26-JAN-05:40 | 1454316.12 | 31-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 683.96 | 0.00 | 01-JAN-00:10 | 69334.75 | 17-JAN-06:20 |
General:Cooling:EnergyTransfer | 21008.57 | 100524.21 | 26-JAN-05:40 | 1454316.12 | 31-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 683.96 | 0.00 | 01-JAN-00:10 | 69334.75 | 17-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 713.45 | 0.00 | 01-JAN-00:10 | 50126.86 | 13-NOV-08:50 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 713.45 | 0.00 | 01-JAN-00:10 | 50126.86 | 13-NOV-08:50 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 713.45 | 0.00 | 01-JAN-00:10 | 50126.86 | 13-NOV-08:50 |
EnergyTransfer:Zone:CORE_MID | 5183.07 | 0.00 | 01-JAN-00:10 | 415266.90 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5183.07 | 0.00 | 01-JAN-00:10 | 415266.90 | 02-JAN-06:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5183.07 | 0.00 | 01-JAN-00:10 | 415266.90 | 02-JAN-06:10 |
EnergyTransfer:Zone:CORE_TOP | 544.65 | 0.00 | 01-JAN-00:10 | 46491.23 | 23-AUG-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 544.65 | 0.00 | 01-JAN-00:10 | 46491.23 | 23-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 544.65 | 0.00 | 01-JAN-00:10 | 46491.23 | 23-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 107.36 | 0.00 | 01-JAN-00:10 | 9841.28 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 107.36 | 0.00 | 01-JAN-00:10 | 9841.28 | 31-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 107.36 | 0.00 | 01-JAN-00:10 | 9841.28 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 81.41 | 0.00 | 01-JAN-00:10 | 9347.08 | 12-JUN-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 81.41 | 0.00 | 01-JAN-00:10 | 9347.08 | 12-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 81.41 | 0.00 | 01-JAN-00:10 | 9347.08 | 12-JUN-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 132.56 | 0.00 | 01-JAN-00:10 | 13186.25 | 04-DEC-14:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 132.56 | 0.00 | 01-JAN-00:10 | 13186.25 | 04-DEC-14:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 132.56 | 0.00 | 01-JAN-00:10 | 13186.25 | 04-DEC-14:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 125.87 | 0.00 | 01-JAN-00:10 | 12886.90 | 12-APR-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 125.87 | 0.00 | 01-JAN-00:10 | 12886.90 | 12-APR-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 125.87 | 0.00 | 01-JAN-00:10 | 12886.90 | 12-APR-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 815.37 | 0.00 | 01-JAN-00:10 | 88058.70 | 01-JUN-14:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 815.37 | 0.00 | 01-JAN-00:10 | 88058.70 | 01-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 815.37 | 0.00 | 01-JAN-00:10 | 88058.70 | 01-JUN-14:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 705.07 | 0.00 | 01-JAN-00:10 | 93489.53 | 25-JUL-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 705.07 | 0.00 | 01-JAN-00:10 | 93489.53 | 25-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 705.07 | 0.00 | 01-JAN-00:10 | 93489.53 | 25-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1091.88 | 0.00 | 01-JAN-00:10 | 123624.29 | 04-DEC-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1091.88 | 0.00 | 01-JAN-00:10 | 123624.29 | 04-DEC-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1091.88 | 0.00 | 01-JAN-00:10 | 123624.29 | 04-DEC-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 755.18 | 0.00 | 01-JAN-00:10 | 103248.09 | 17-MAY-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 755.18 | 0.00 | 01-JAN-00:10 | 103248.09 | 17-MAY-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 755.18 | 0.00 | 01-JAN-00:10 | 103248.09 | 17-MAY-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 86.68 | 0.00 | 01-JAN-00:10 | 10025.01 | 01-JUN-14:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.09 | 0.00 | 01-JAN-00:10 | 4175.79 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.09 | 0.00 | 01-JAN-00:10 | 4175.79 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 86.59 | 0.00 | 01-JAN-00:10 | 10025.01 | 01-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 86.59 | 0.00 | 01-JAN-00:10 | 10025.01 | 01-JUN-14:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 75.71 | 0.00 | 01-JAN-00:10 | 9979.89 | 25-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 2982.16 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 2982.16 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 75.69 | 0.00 | 01-JAN-00:10 | 9979.89 | 25-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 75.69 | 0.00 | 01-JAN-00:10 | 9979.89 | 25-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 114.80 | 0.00 | 01-JAN-00:10 | 13973.55 | 04-DEC-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.01 | 0.00 | 01-JAN-00:10 | 3417.05 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.01 | 0.00 | 01-JAN-00:10 | 3417.05 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 114.79 | 0.00 | 01-JAN-00:10 | 13973.55 | 04-DEC-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 114.79 | 0.00 | 01-JAN-00:10 | 13973.55 | 04-DEC-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 80.27 | 0.00 | 01-JAN-00:10 | 11207.31 | 17-MAY-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 2610.86 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 2610.86 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 80.26 | 0.00 | 01-JAN-00:10 | 11207.31 | 17-MAY-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 80.26 | 0.00 | 01-JAN-00:10 | 11207.31 | 17-MAY-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 96.06 | 0.00 | 01-JAN-00:10 | 10258.80 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.73 | 0.00 | 01-JAN-00:10 | 2996.90 | 05-FEB-11:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.73 | 0.00 | 01-JAN-00:10 | 2996.90 | 05-FEB-11:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 95.33 | 0.00 | 01-JAN-00:10 | 10258.80 | 02-JAN-08:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 95.33 | 0.00 | 01-JAN-00:10 | 10258.80 | 02-JAN-08:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 703.02 | 0.00 | 01-JAN-00:10 | 68454.21 | 05-SEP-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 3.37 | 0.00 | 01-JAN-00:10 | 20652.19 | 29-JAN-10:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 3.37 | 0.00 | 01-JAN-00:10 | 20652.19 | 29-JAN-10:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 699.65 | 0.00 | 01-JAN-00:10 | 68454.21 | 05-SEP-07:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 699.65 | 0.00 | 01-JAN-00:10 | 68454.21 | 05-SEP-07:10 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 124.73 | 0.00 | 01-JAN-00:10 | 20824.07 | 28-JUL-15:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 2.35 | 0.00 | 01-JAN-00:10 | 6580.60 | 04-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 2.35 | 0.00 | 01-JAN-00:10 | 6580.60 | 04-FEB-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 122.38 | 0.00 | 01-JAN-00:10 | 20824.07 | 28-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 122.38 | 0.00 | 01-JAN-00:10 | 20824.07 | 28-JUL-15:20 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.22 | 1278.44 | 26-JAN-08:00 | 7811.74 | 09-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.22 | 1278.44 | 26-JAN-08:00 | 7811.74 | 09-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.22 | 1278.44 | 26-JAN-08:00 | 7811.74 | 09-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1334.29 | 8584.76 | 26-JAN-08:00 | 73537.54 | 09-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1334.29 | 8584.76 | 26-JAN-08:00 | 73537.54 | 09-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1334.29 | 8584.76 | 26-JAN-08:00 | 73537.54 | 09-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 132.60 | 161.91 | 26-JAN-08:00 | 7629.29 | 09-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 132.60 | 161.91 | 26-JAN-08:00 | 7629.29 | 09-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 132.60 | 161.91 | 26-JAN-08:00 | 7629.29 | 09-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7184.94 | 88615.67 | 27-MAY-18:20 | 367794.18 | 21-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7184.94 | 88615.67 | 27-MAY-18:20 | 367794.18 | 21-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7184.94 | 88615.67 | 27-MAY-18:20 | 367794.18 | 21-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 297.40 | 0.00 | 01-JAN-00:10 | 51954.15 | 04-FEB-06:10 |
PlantLoopHeatingDemand:Plant | 296.73 | 0.00 | 01-JAN-00:10 | 36110.36 | 19-JAN-13:00 |
WaterSystems:PlantLoopHeatingDemand | 296.73 | 0.00 | 01-JAN-00:10 | 36110.36 | 19-JAN-13:00 |
General:WaterSystems:PlantLoopHeatingDemand | 296.73 | 0.00 | 01-JAN-00:10 | 36110.36 | 19-JAN-13:00 |
EnergyTransfer:HVAC | 22337.81 | 13408.59 | 26-JAN-06:00 | 2108038.99 | 21-AUG-16:00 |
HeatingCoils:EnergyTransfer | 0.67 | 0.00 | 01-JAN-00:10 | 47510.16 | 04-FEB-06:10 |
PlantLoopHeatingDemand:HVAC | 0.67 | 0.00 | 01-JAN-00:10 | 47510.16 | 04-FEB-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 0.67 | 0.00 | 01-JAN-00:10 | 47510.16 | 04-FEB-06:10 |
CoolingCoils:EnergyTransfer | 19057.08 | 13408.59 | 26-JAN-06:00 | 1675109.03 | 22-JUN-05:10 |
DistrictHeating:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 13.50 | 01-FEB-00:40 |
DistrictHeating:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 13.50 | 01-FEB-00:40 |
Heating:DistrictHeating | 0.00 | 0.00 | 01-JAN-00:10 | 13.50 | 01-FEB-00:40 |
General:Heating:DistrictHeating | 0.00 | 0.00 | 01-JAN-00:10 | 13.50 | 01-FEB-00:40 |
HeatRecoveryForHeating:EnergyTransfer | 10.26 | 0.00 | 01-JAN-00:10 | 146934.26 | 21-FEB-17:30 |
HeatRecoveryForCooling:EnergyTransfer | 3269.80 | 0.00 | 01-JAN-00:10 | 518173.68 | 22-JUL-15:00 |
EnergyTransfer:Plant | 52890.69 | 0.00 | 01-JAN-00:10 | 5712995.11 | 03-OCT-15:10 |
LoopToLoop:EnergyTransfer | 18485.40 | 0.00 | 01-JAN-00:10 | 1803042.67 | 03-OCT-15:10 |
WaterSystems:EnergyTransfer | 296.73 | 0.00 | 01-JAN-00:10 | 36110.36 | 19-JAN-13:00 |
WaterUse:WaterSystems:EnergyTransfer | 296.73 | 0.00 | 01-JAN-00:10 | 36110.36 | 19-JAN-13:00 |
Boilers:EnergyTransfer | 0.52 | 0.00 | 01-JAN-00:10 | 39804.58 | 04-FEB-06:10 |
Chillers:EnergyTransfer | 15831.03 | 0.00 | 01-JAN-00:10 | 1808041.37 | 03-OCT-15:10 |
HeatRejection:EnergyTransfer | 18277.01 | 0.00 | 01-JAN-00:10 | 2077364.66 | 03-OCT-15:10 |
General:HeatRejection:EnergyTransfer | 18277.01 | 0.00 | 01-JAN-00:10 | 2077364.66 | 03-OCT-15:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.448 | -683.953 | 0.000 | 0.000 | 92.582 | 135.577 | 424.397 | 0.000 | 0.000 | 0.000 | 26.948 | 0.000 | 0.000 | 0.000 | 0.000 | -0.018 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -713.454 | 0.000 | 0.000 | 83.437 | 121.758 | 289.614 | 0.000 | 0.000 | 0.000 | 218.646 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5183.057 | 0.000 | 0.000 | 835.333 | 1217.578 | 2896.128 | 0.000 | 0.000 | 0.000 | 234.019 | 0.000 | 0.000 | 0.000 | 0.000 | -0.009 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -544.646 | 0.000 | 0.000 | 83.750 | 121.758 | 289.613 | 0.000 | 0.000 | 0.000 | 49.525 | 0.000 | 0.000 | 0.000 | 0.000 | -0.004 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -107.358 | 0.000 | 0.000 | 10.479 | 8.952 | 36.365 | 33.475 | 0.000 | 0.160 | 32.397 | 0.000 | -14.203 | 0.000 | -0.268 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -81.409 | 0.000 | 0.000 | 6.751 | 5.721 | 23.435 | 45.196 | 0.000 | 0.108 | 8.994 | 0.000 | -8.623 | 0.000 | -0.174 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -132.555 | 0.000 | 0.000 | 10.443 | 8.763 | 36.366 | 69.886 | 0.000 | 0.151 | 21.386 | 0.000 | -14.145 | 0.000 | -0.295 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -125.875 | 0.000 | 0.000 | 6.730 | 5.728 | 23.435 | 42.207 | 0.000 | 0.090 | 59.970 | 0.000 | -12.048 | 0.000 | -0.236 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -815.362 | 0.000 | 0.000 | 105.423 | 89.481 | 363.654 | 340.215 | 0.000 | 3.548 | 50.841 | 0.000 | -131.729 | 0.000 | -6.072 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -705.062 | 0.000 | 0.000 | 49.630 | 57.187 | 234.352 | 447.911 | 0.000 | 2.196 | 4.981 | 0.000 | -86.788 | 0.000 | -4.406 | -0.003 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -1091.871 | 0.000 | 0.000 | 104.322 | 87.625 | 363.660 | 696.241 | 0.000 | 3.265 | 0.002 | 0.000 | -139.607 | 0.000 | -7.275 | -16.358 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -755.179 | 0.000 | 0.000 | 67.656 | 57.250 | 234.351 | 431.120 | 0.000 | 2.062 | 68.849 | 0.000 | -101.226 | 0.000 | -4.883 | -0.002 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.087 | -86.588 | 0.000 | 0.000 | 10.607 | 8.948 | 36.365 | 33.533 | 0.000 | 0.406 | 10.094 | 0.000 | -12.730 | 0.000 | -0.721 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.022 | -75.692 | 0.000 | 0.000 | 6.775 | 5.719 | 23.435 | 44.397 | 0.000 | 0.255 | 4.125 | 0.000 | -8.505 | 0.000 | -0.531 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.010 | -114.790 | 0.000 | 0.000 | 10.481 | 8.762 | 36.366 | 69.020 | 0.000 | 0.379 | 4.388 | 0.000 | -13.732 | 0.000 | -0.884 | -0.001 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.010 | -80.260 | 0.000 | 0.000 | 6.804 | 5.725 | 23.435 | 42.767 | 0.000 | 0.247 | 11.720 | 0.000 | -9.860 | 0.000 | -0.587 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -142.220 | 0.000 | 0.000 | 0.950 | 3.264 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -15.875 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1334.287 | 0.000 | 0.000 | 9.500 | 32.637 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -246.656 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.000 | -132.599 | 0.000 | 0.000 | 0.950 | 3.264 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -25.496 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | -7184.939 | 0.000 | 0.000 | 0.000 | 0.000 | 20.569 | 38.227 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -368.714 |
GROUNDFLOOR_PLENUM | 0.732 | -95.326 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.277 | 94.924 | 0.000 | 0.000 | 0.000 | -0.607 | -0.000 |
MIDFLOOR_PLENUM | 3.367 | -699.647 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.063 | 701.706 | 0.000 | 0.000 | 0.000 | -10.489 | -0.000 |
TOPFLOOR_PLENUM | 2.348 | -122.377 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.426 | 120.727 | 0.000 | 0.000 | 0.000 | -1.124 | -0.000 |
Total Facility | 6.447 | -8102.289 | 4.578 | -12906.217 | 0.000 | 0.000 | 1523.171 | 2023.923 | 14676.396 | 2295.969 | 0.000 | 18.634 | 1724.242 | 0.000 | -553.198 | 0.000 | -38.555 | -673.138 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 27-FEB-04:02 | 0.00 | 0.00 | 0.00 | -83369.22 | 0.00 | 0.00 | 0.00 | 657.72 | 13457.54 | 0.00 | 0.00 | 0.00 | 69253.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 13-NOV-04:02 | 0.00 | 0.00 | 0.00 | -86014.89 | 0.00 | 0.00 | 0.00 | 590.68 | 5937.65 | 0.00 | 0.00 | 0.00 | 79486.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 13-NOV-04:02 | 0.00 | 0.00 | 0.00 | -757581.63 | 0.00 | 0.00 | 0.00 | 5906.80 | 59376.23 | 0.00 | 0.00 | 0.00 | 692298.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 06-MAR-04:03 | 0.00 | 0.00 | 0.00 | -75676.37 | 0.00 | 0.00 | 0.00 | 590.68 | 5937.62 | 0.00 | 0.00 | 0.00 | 69148.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 09-JUL-17:01 | 0.00 | 0.00 | 0.00 | -15146.86 | 0.00 | 0.00 | 0.00 | 35.29 | 559.17 | 3445.59 | 0.00 | 26.88 | 11079.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 10-SEP-09:02 | 0.00 | 0.00 | 0.00 | -14472.83 | 0.00 | 0.00 | 25.87 | 22.74 | 464.11 | 8714.07 | 0.00 | 8.61 | 5237.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-DEC-12:52 | 0.00 | 0.00 | 0.00 | -16363.00 | 0.00 | 0.00 | 36.77 | 35.29 | 720.19 | 13840.30 | 0.00 | 0.67 | 1729.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 09-JUL-17:01 | 0.00 | 0.00 | 0.00 | -21275.32 | 0.00 | 0.00 | 0.00 | 22.74 | 360.35 | 7838.39 | 0.00 | 7.33 | 13046.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 31-JUL-03:02 | 0.00 | 0.00 | 0.00 | -128781.31 | 0.00 | 0.00 | 0.00 | 741.66 | 7455.61 | 0.00 | 0.00 | 13.18 | 125931.16 | 0.00 | -5360.29 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 16-APR-09:52 | 0.00 | 0.00 | 0.00 | -154417.89 | 0.00 | 0.00 | 243.50 | 227.41 | 4641.14 | 81288.67 | 0.00 | 0.00 | 68053.61 | 0.00 | -0.00 | 0.00 | -36.44 | 0.00 |
PERIMETER_MID_ZN_1 | 03-DEC-13:52 | 0.00 | 0.00 | 0.00 | -154502.89 | 0.00 | 0.00 | 351.23 | 352.89 | 7201.95 | 141112.26 | 0.00 | 0.00 | 5971.44 | 0.00 | -0.00 | 0.00 | -486.88 | 0.00 |
PERIMETER_MID_ZN_4 | 09-APR-17:32 | 0.00 | 0.00 | 0.00 | -168486.39 | 0.00 | 0.00 | 0.00 | 227.41 | 3603.49 | 62135.63 | 0.00 | 0.00 | 102751.79 | 0.00 | -0.00 | 0.00 | -231.93 | 0.00 |
PERIMETER_TOP_ZN_3 | 29-MAY-15:42 | 0.00 | 0.00 | 0.00 | -16317.14 | 0.00 | 0.00 | 40.71 | 35.29 | 720.18 | 3631.20 | 0.00 | 226.84 | 11662.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 30-JUL-08:43 | 0.00 | 0.00 | 0.00 | -15527.17 | 0.00 | 0.00 | 24.74 | 22.74 | 464.11 | 8390.22 | 0.00 | 23.35 | 6602.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 03-DEC-14:22 | 0.00 | 0.00 | 0.00 | -18174.21 | 0.00 | 0.00 | 34.47 | 35.29 | 720.19 | 12986.92 | 0.00 | 0.00 | 4459.43 | 0.00 | -0.00 | 0.00 | -62.09 | 0.00 |
PERIMETER_TOP_ZN_4 | 29-MAY-15:42 | 0.00 | 0.00 | 0.00 | -19069.16 | 0.00 | 0.00 | 21.60 | 22.74 | 464.11 | 9226.60 | 0.00 | 125.11 | 9209.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 09-APR-17:55 | 0.00 | 0.00 | 0.00 | -7811.69 | 0.00 | 0.00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 1.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 09-APR-17:55 | 0.00 | 0.00 | 0.00 | -73537.09 | 0.00 | 0.00 | 0.00 | 158.32 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4565.46 |
DATACENTER_TOP_ZN_6 | 09-APR-17:55 | 0.00 | 0.00 | 0.00 | -7629.25 | 0.00 | 0.00 | 0.00 | 15.83 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -181.00 |
DATACENTER_BASEMENT_ZN_6 | 21-AUG-16:00 | 0.00 | -367794.18 | 0.00 | 0.00 | 0.00 | 0.00 | 2183.10 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17359.21 |
GROUNDFLOOR_PLENUM | 21-AUG-05:15 | 0.00 | -13514.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 | 13510.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 02-JAN-06:15 | 0.00 | -87850.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88199.52 | 0.00 | -0.00 | 0.00 | -349.41 | 0.00 |
TOPFLOOR_PLENUM | 28-JUL-15:20 | 0.00 | -20823.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.91 | 20778.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-AUG-05:02 | 0.00 | -406073.22 | 0.00 | -1447954.05 | 0.00 | 0.00 | 15880.22 | 22094.05 | 616289.16 | 0.00 | 0.00 | 207.54 | 1203096.70 | 0.00 | -3540.40 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 29-JUL-16:02 | 0.00 | 0.00 | 22331.31 | 0.00 | 0.00 | 0.00 | 484.18 | 657.72 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -36930.76 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 25-JAN-06:02 | 0.00 | 0.00 | 10905.42 | 0.00 | 0.00 | 0.00 | 146.08 | 148.31 | 960.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2678.86 | 0.00 | -59.45 | -9421.76 |
PERIMETER_TOP_ZN_2 | 04-FEB-06:03 | 0.00 | 0.00 | 8637.79 | 0.00 | 0.00 | 0.00 | 94.15 | 95.58 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2249.87 | 0.00 | -88.82 | -7107.64 |
PERIMETER_TOP_ZN_1 | 04-FEB-06:03 | 0.00 | 0.00 | 10840.39 | 0.00 | 0.00 | 0.00 | 146.10 | 148.32 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3441.42 | 0.00 | -132.65 | -8521.00 |
PERIMETER_TOP_ZN_4 | 04-FEB-06:03 | 0.00 | 0.00 | 8251.07 | 0.00 | 0.00 | 0.00 | 94.15 | 95.58 | 618.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2353.00 | 0.00 | -89.04 | -6617.57 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 22-DEC-04:02 | 9464.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -60.85 | -9403.81 |
MIDFLOOR_PLENUM | 28-AUG-03:02 | 57491.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -57491.27 |
TOPFLOOR_PLENUM | 20-MAR-05:03 | 15058.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -111.48 | -14947.42 |
Total Facility | 04-FEB-06:03 | -1089762.69 | 949995.42 | 38601.79 | -949995.42 | 0.00 | 0.00 | 17349.36 | 22094.05 | 379706.36 | 0.00 | 0.00 | 0.00 | 789478.59 | 0.00 | -150920.92 | 0.00 | -6546.56 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 8.9418 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.4544 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 82.8415 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 78.0408 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 8.7187 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.4158 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 4.9582 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 4.9582 | 0.2421 | 1.0000 | Not calculated | 1.2002 | 0.2421 | ||
AIRLOOP DATACENTER BOT | 0.4583 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4583 | 0.0341 | 1.0000 | Not calculated | 0.0156 | 0.0341 | ||
AIRLOOP DATACENTER MID | 4.3540 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.3540 | 0.0359 | 1.0000 | Not calculated | 0.1563 | 0.0359 | ||
AIRLOOP DATACENTER TOP | 0.4421 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4421 | 0.0354 | 1.0000 | Not calculated | 0.0156 | 0.0354 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 4.4709 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.7103 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 41.4207 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 26.1948 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.3593 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.6972 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 4.9582 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 4.9582 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2421 | ||
AIRLOOP DATACENTER BOT | 0.4583 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4583 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0341 | ||
AIRLOOP DATACENTER MID | 4.3540 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.3540 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0359 | ||
AIRLOOP DATACENTER TOP | 0.4421 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4421 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0354 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.002360 | 149.6021 | 0.000305 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.002360 | 1.9486 | 0.000305 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.002360 | 19.4861 | 0.000305 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.002360 | 1.9486 | 0.000305 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.002360 | 149.60 | 0.000305 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BOT | 0.002360 | 1.95 | 0.000305 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.002360 | 19.49 | 0.000305 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.002360 | 1.95 | 0.000305 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9582 | 4.9582 | 4.9582 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2562 | 5.2562 | 1.8554 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 49.1174 | 49.1174 | 18.1243 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9844 | 4.9844 | 1.8542 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8805 | 0.8805 | 0.2333 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8329 | 0.8329 | 0.1666 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8645 | 0.8645 | 0.2334 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1077 | 1.1077 | 0.2215 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.2381 | 8.2381 | 2.2737 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.4881 | 8.4881 | 1.6976 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.8603 | 7.8603 | 2.2716 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.1376 | 9.1376 | 1.8275 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9229 | 0.9229 | 0.2326 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8747 | 0.8747 | 0.1749 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9250 | 0.9250 | 0.2331 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0116 | 1.0116 | 0.2023 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4583 | 0.4583 | 0.4583 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.3540 | 4.3540 | 4.3540 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4421 | 0.4421 | 0.4421 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 8.9418 | 8.4544 | 8.9418 | 2.7103 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 82.8415 | 78.0408 | 82.8415 | 26.1948 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 8.7187 | 8.4158 | 8.7187 | 2.6972 | 0.0000 | 1.0000 |
CAV_BAS | 4.9582 | 4.9582 | 4.9582 | 4.9582 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4583 | 0.4583 | 0.4583 | 0.4583 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.3540 | 4.3540 | 4.3540 | 4.3540 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4421 | 0.4421 | 0.4421 | 0.4421 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9582 | 4.9582 | 4.9582 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6281 | 2.6281 | 1.8554 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 24.5587 | 24.5587 | 18.1243 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4922 | 2.4922 | 1.8542 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4403 | 0.4403 | 0.2333 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4164 | 0.4164 | 0.1666 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4323 | 0.4323 | 0.2334 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5539 | 0.5539 | 0.2215 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.1190 | 4.1190 | 2.2737 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.2440 | 4.2440 | 1.6976 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.9302 | 3.9302 | 2.2716 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.5688 | 4.5688 | 1.8275 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4615 | 0.4615 | 0.2326 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4373 | 0.4373 | 0.1749 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4625 | 0.4625 | 0.2331 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5058 | 0.5058 | 0.2023 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4583 | 0.4583 | 0.4583 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.3540 | 4.3540 | 4.3540 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4421 | 0.4421 | 0.4421 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 4.4709 | 2.7103 | 2.7103 | 2.7103 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 41.4207 | 26.1948 | 26.1948 | 26.1948 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.3593 | 2.6972 | 2.6972 | 2.6972 | 0.0000 | 1.0000 |
CAV_BAS | 4.9582 | 4.9582 | 4.9582 | 4.9582 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4583 | 0.4583 | 0.4583 | 0.4583 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.3540 | 4.3540 | 4.3540 | 4.3540 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4421 | 0.4421 | 0.4421 | 0.4421 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 317.50 |
Number of hours not met | 317.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 |
Heating -- Boiler | 0.00 | 0.00 | 0.82 | 62214.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2929.24 | 294154.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7209.48 | 370450.14 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2023.92 | 198852.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 323.97 | 37611.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.48 | 3387.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ComputerHVAC | 1349.07 | 68333.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 1304.80 | 152921.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1169.03 | 69139.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 929.75 | 56753.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 119.90 | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 563.99 | 68192.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 26735.18 |
Natural Gas | 0.00 | 564.81 |
Additional | 0.00 | 7209.48 |
Total | 14676.40 | 34509.47 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 43.69 |
Space Heating | 0.00 |
Space Cooling | 63.24 |
Fans (All) | 28.17 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 577.18 |
Subtotal | 577.18 |
Natural Gas [MJ/m2] | |
Space Heating | 0.02 |
Service Water Heating | 12.18 |
Miscellaneous (All) | 12.19 |
Subtotal | 12.19 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.86 |
Space Heating | 0.00 |
Space Cooling | 29.38 |
Fans (All) | 3.78 |
Service Water Heating | 1.63 |
Receptacle Equipment | 42.53 |
Miscellaneous | 16.81 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2362. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 6755.67 | 2004.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8720.67 | 39.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8738.33 | 21.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8646.83 | 113.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8554.67 | 205.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7316.83 | 1443.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8700.83 | 59.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8411.17 | 348.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8287.33 | 472.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7651.83 | 1108.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8575.17 | 184.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8283.33 | 476.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8162.17 | 597.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7673.17 | 1086.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1744.00 | 7016.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1742.83 | 7017.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1681.50 | 7078.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8756.17 | 3.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8375.33 | 384.67 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
Average | 7089.36 | 1670.64 | 0.00 | 0.00 | 0.00 |
Sum | 163055.33 | 38424.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 363345.00 | 5271.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330754.00 | 59.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330807.00 | 6.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 284.67 | 1983.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 284.50 | 1983.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 276.50 | 1991.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 103395.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 363345.00 | 103395.00 | 0.00 | 0.00 | 0.00 |
Average | 75348.42 | 4986.49 | 0.00 | 0.00 | 0.00 |
Sum | 1733013.67 | 114689.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 3724.17 | 5035.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 7015.50 | 1744.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 6376.00 | 2384.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 6371.17 | 2388.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6130.50 | 2629.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6553.33 | 2206.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5732.00 | 3028.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 5224.00 | 3536.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 5719.17 | 3040.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 5604.67 | 3155.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 5386.00 | 3374.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 5424.33 | 3335.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 5744.00 | 3016.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 5624.33 | 3135.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 5414.33 | 3345.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 5489.17 | 3270.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 3325.33 | 5434.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 3292.83 | 5467.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 3220.83 | 5539.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 5074.17 | 3685.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 5112.67 | 3647.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3784.17 | 4975.83 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 1744.50 | 0.00 | 0.00 | 0.00 |
Max | 7015.50 | 8760.00 | 0.00 | 0.00 | 0.00 |
Average | 5014.90 | 3745.10 | 0.00 | 0.00 | 0.00 |
Sum | 115342.67 | 86137.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 333469.83 | 35146.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 327261.00 | 3552.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 327014.00 | 3799.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 325659.33 | 5153.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38922.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24885.50 | 23.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38919.50 | 5.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18349.17 | 4.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38915.00 | 10.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24889.00 | 20.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38920.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24905.83 | 3.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38914.17 | 10.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24892.00 | 17.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 584.33 | 1683.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 578.33 | 1689.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 562.33 | 1705.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 103395.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 333469.83 | 103395.00 | 0.00 | 0.00 | 0.00 |
Average | 73542.44 | 6792.47 | 0.00 | 0.00 | 0.00 |
Sum | 1691476.17 | 156226.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:07:12
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.574706E+11 | 81271.81 | 23-JAN-04:03 | 12.20 | 11.63 | 0.567843E+10 | 7499.14 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.507848E+11 | 83374.26 | 27-FEB-04:02 | 15.60 | 13.66 | 0.514946E+10 | 7499.10 | 23-FEB-10:09 | 15.60 | 13.66 |
March | 0.568400E+11 | 78079.20 | 13-MAR-03:02 | 21.70 | 19.47 | 0.614256E+10 | 7499.07 | 17-MAR-13:09 | 21.20 | 14.87 |
April | 0.522600E+11 | 78097.69 | 20-APR-03:02 | 21.02 | 15.02 | 0.545837E+10 | 7499.09 | 21-APR-09:20 | 25.40 | 18.57 |
May | 0.557776E+11 | 69977.99 | 09-MAY-03:02 | 24.40 | 19.56 | 0.590985E+10 | 7498.80 | 25-MAY-09:20 | 24.23 | 23.36 |
June | 0.555864E+11 | 67303.35 | 17-JUN-03:02 | 26.52 | 21.99 | 0.588972E+10 | 7498.79 | 28-JUN-09:20 | 26.30 | 24.72 |
July | 0.571227E+11 | 67787.02 | 04-JUL-15:47 | 31.88 | 25.00 | 0.548200E+10 | 7498.78 | 07-JUL-13:20 | 32.03 | 25.28 |
August | 0.634168E+11 | 69190.86 | 08-AUG-03:02 | 26.10 | 23.70 | 0.614662E+10 | 7529.67 | 21-AUG-09:09 | 30.68 | 26.07 |
September | 0.571175E+11 | 69199.28 | 25-SEP-03:02 | 24.40 | 22.49 | 0.546129E+10 | 7524.80 | 05-SEP-09:30 | 24.40 | 22.49 |
October | 0.601382E+11 | 72330.87 | 17-OCT-03:02 | 24.40 | 19.50 | 0.568095E+10 | 7526.16 | 10-OCT-09:09 | 24.40 | 19.50 |
November | 0.592863E+11 | 80547.58 | 27-NOV-05:23 | 10.00 | 8.82 | 0.562446E+10 | 7612.67 | 13-NOV-10:20 | 10.00 | 8.82 |
December | 0.581579E+11 | 79617.51 | 13-DEC-04:03 | 10.68 | 9.95 | 0.548161E+10 | 7499.17 | 21-DEC-10:09 | 19.08 | 15.38 |
Annual Sum or Average | 0.683959E+12 | 0.681053E+11 | ||||||||
Minimum of Months | 0.507848E+11 | 67303.35 | 10.00 | 8.82 | 0.514946E+10 | 7498.78 | 10.00 | 8.82 | ||
Maximum of Months | 0.634168E+11 | 83374.26 | 31.88 | 25.00 | 0.614662E+10 | 7612.67 | 32.03 | 26.07 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.485674E+11 | 85045.48 | 17-JAN-04:02 | 13.80 | 12.18 | 0.507819E+10 | 6734.88 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.475588E+11 | 83113.32 | 13-FEB-04:02 | 20.50 | 19.41 | 0.460639E+10 | 6734.82 | 14-FEB-14:39 | 24.23 | 20.09 |
March | 0.609596E+11 | 82396.48 | 20-MAR-03:02 | 12.70 | 9.59 | 0.549613E+10 | 6734.78 | 01-MAR-10:09 | 12.70 | 9.59 |
April | 0.635893E+11 | 76166.21 | 17-APR-05:04 | 18.90 | 16.76 | 0.487675E+10 | 6734.79 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.567934E+11 | 77131.29 | 09-MAY-03:02 | 24.40 | 19.56 | 0.528449E+10 | 6734.57 | 22-MAY-13:00 | 33.90 | 23.74 |
June | 0.613280E+11 | 73140.50 | 05-JUN-05:04 | 25.50 | 23.67 | 0.526607E+10 | 6734.67 | 12-JUN-09:00 | 30.60 | 24.52 |
July | 0.663832E+11 | 74151.32 | 31-JUL-05:04 | 26.10 | 24.46 | 0.489206E+10 | 6734.56 | 19-JUL-13:00 | 26.10 | 24.46 |
August | 0.710667E+11 | 74771.41 | 28-AUG-05:04 | 26.02 | 24.78 | 0.549421E+10 | 6734.75 | 07-AUG-13:20 | 26.02 | 24.78 |
September | 0.564006E+11 | 78702.22 | 26-SEP-03:02 | 23.30 | 22.57 | 0.487911E+10 | 6734.76 | 11-SEP-13:39 | 23.30 | 22.57 |
October | 0.606903E+11 | 78235.34 | 14-OCT-03:02 | 22.88 | 22.30 | 0.507361E+10 | 6734.89 | 26-OCT-13:20 | 26.83 | 22.68 |
November | 0.595004E+11 | 86019.04 | 13-NOV-04:02 | 12.80 | 8.34 | 0.502717E+10 | 6734.87 | 27-NOV-10:00 | 22.20 | 16.63 |
December | 0.606166E+11 | 81149.43 | 27-DEC-04:03 | 9.40 | 8.79 | 0.489772E+10 | 6734.98 | 22-DEC-14:39 | 9.40 | 8.79 |
Annual Sum or Average | 0.713454E+12 | 0.608719E+11 | ||||||||
Minimum of Months | 0.475588E+11 | 73140.50 | 9.40 | 8.34 | 0.460639E+10 | 6734.56 | 9.40 | 8.79 | ||
Maximum of Months | 0.710667E+11 | 86019.04 | 26.10 | 24.78 | 0.549613E+10 | 6734.98 | 33.90 | 24.78 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382370E+11 | 75199.82 | 02-JAN-04:02 | 18.80 | 18.44 | 0.505842E+10 | 6734.86 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.354622E+11 | 75709.07 | 13-FEB-04:02 | 20.50 | 19.41 | 0.458938E+10 | 6734.80 | 23-FEB-10:09 | 23.07 | 17.34 |
March | 0.427704E+11 | 72659.30 | 16-MAR-05:02 | 6.70 | 4.49 | 0.548796E+10 | 6734.77 | 01-MAR-10:09 | 6.70 | 4.49 |
April | 0.420882E+11 | 72323.64 | 07-APR-05:04 | 23.30 | 20.25 | 0.487350E+10 | 6734.78 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.463969E+11 | 70571.86 | 11-MAY-04:03 | 21.70 | 21.27 | 0.527973E+10 | 6734.57 | 18-MAY-09:20 | 28.67 | 22.27 |
June | 0.469520E+11 | 69926.11 | 19-JUN-03:02 | 24.40 | 23.08 | 0.526374E+10 | 6734.59 | 09-JUN-09:20 | 24.40 | 23.08 |
July | 0.471380E+11 | 71441.40 | 15-JUL-05:04 | 26.10 | 24.11 | 0.488762E+10 | 6734.57 | 19-JUL-13:00 | 27.80 | 25.31 |
August | 0.486957E+11 | 71033.22 | 29-AUG-04:03 | 23.80 | 23.12 | 0.549109E+10 | 6734.69 | 07-AUG-13:20 | 23.80 | 23.12 |
September | 0.454246E+11 | 72409.56 | 26-SEP-05:04 | 23.30 | 22.01 | 0.487363E+10 | 6734.76 | 11-SEP-13:39 | 23.30 | 22.01 |
October | 0.454887E+11 | 72091.60 | 02-OCT-03:02 | 26.70 | 25.31 | 0.506921E+10 | 6734.88 | 26-OCT-13:39 | 24.27 | 21.92 |
November | 0.413563E+11 | 75785.25 | 13-NOV-04:02 | 12.80 | 8.34 | 0.502175E+10 | 6734.89 | 27-NOV-10:00 | 22.20 | 16.63 |
December | 0.382968E+11 | 72772.69 | 20-DEC-06:02 | 13.03 | 10.85 | 0.487913E+10 | 6734.92 | 18-DEC-14:39 | 13.03 | 10.85 |
Annual Sum or Average | 0.518307E+12 | 0.607752E+11 | ||||||||
Minimum of Months | 0.354622E+11 | 69926.11 | 6.70 | 4.49 | 0.458938E+10 | 6734.57 | 6.70 | 4.49 | ||
Maximum of Months | 0.486957E+11 | 75785.25 | 26.70 | 25.31 | 0.549109E+10 | 6734.92 | 28.67 | 25.31 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334094E+11 | 70678.78 | 03-JAN-06:03 | 20.00 | 19.21 | 0.497378E+10 | 6734.64 | 10-JAN-14:00 | 22.20 | 16.63 |
February | 0.335735E+11 | 73506.91 | 13-FEB-04:02 | 20.50 | 19.41 | 0.454996E+10 | 6734.77 | 23-FEB-10:09 | 23.07 | 17.34 |
March | 0.424638E+11 | 75693.05 | 06-MAR-04:03 | 22.30 | 21.89 | 0.545759E+10 | 6734.74 | 01-MAR-10:09 | 22.30 | 21.89 |
April | 0.451171E+11 | 72015.97 | 26-APR-05:04 | 20.60 | 19.80 | 0.487037E+10 | 6734.77 | 20-APR-09:09 | 20.60 | 19.80 |
May | 0.521640E+11 | 72325.11 | 22-MAY-03:02 | 23.22 | 21.01 | 0.528361E+10 | 6734.54 | 30-MAY-13:09 | 25.97 | 24.15 |
June | 0.537739E+11 | 73116.40 | 19-JUN-03:02 | 24.40 | 23.08 | 0.526822E+10 | 6734.57 | 05-JUN-13:00 | 24.40 | 23.08 |
July | 0.548010E+11 | 70944.35 | 03-JUL-03:02 | 25.50 | 24.73 | 0.489500E+10 | 6734.55 | 14-JUL-13:00 | 28.90 | 26.06 |
August | 0.548102E+11 | 70507.50 | 15-AUG-03:02 | 27.30 | 25.19 | 0.549425E+10 | 6734.60 | 07-AUG-13:00 | 27.30 | 25.19 |
September | 0.508320E+11 | 74433.34 | 05-SEP-03:02 | 23.30 | 21.69 | 0.487878E+10 | 6734.74 | 11-SEP-13:39 | 28.73 | 24.51 |
October | 0.482116E+11 | 75020.21 | 02-OCT-03:02 | 26.70 | 25.31 | 0.506993E+10 | 6734.82 | 26-OCT-13:39 | 24.27 | 21.92 |
November | 0.407192E+11 | 75108.81 | 06-NOV-04:03 | 21.60 | 19.75 | 0.500398E+10 | 6734.81 | 27-NOV-10:00 | 22.20 | 16.63 |
December | 0.347727E+11 | 71221.85 | 01-DEC-05:03 | 22.38 | 18.19 | 0.481328E+10 | 6734.71 | 18-DEC-14:20 | 25.00 | 19.88 |
Annual Sum or Average | 0.544648E+12 | 0.605588E+11 | ||||||||
Minimum of Months | 0.334094E+11 | 70507.50 | 20.00 | 18.19 | 0.454996E+10 | 6734.54 | 20.60 | 16.63 | ||
Maximum of Months | 0.548102E+11 | 75693.05 | 27.30 | 25.31 | 0.549425E+10 | 6734.82 | 28.90 | 26.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.529151E+10 | 12398.98 | 30-JAN-04:02 | 21.60 | 20.86 | 0.632050E+09 | 845.63 | 27-JAN-10:00 | 21.60 | 20.86 |
February | 0.588187E+10 | 11339.13 | 18-FEB-06:02 | 23.40 | 20.68 | 0.575815E+09 | 845.65 | 14-FEB-14:39 | 23.40 | 20.68 |
March | 0.787795E+10 | 11397.30 | 09-MAR-06:02 | 22.80 | 20.51 | 0.688203E+09 | 845.63 | 17-MAR-13:09 | 21.20 | 14.87 |
April | 0.935347E+10 | 11498.88 | 29-APR-05:02 | 22.80 | 20.23 | 0.612919E+09 | 845.63 | 20-APR-09:00 | 22.80 | 20.23 |
May | 0.980336E+10 | 15017.19 | 29-MAY-15:42 | 33.22 | 24.49 | 0.665048E+09 | 845.61 | 22-MAY-13:00 | 33.22 | 24.49 |
June | 0.111616E+11 | 11941.79 | 15-JUN-05:02 | 27.20 | 24.02 | 0.663013E+09 | 845.63 | 12-JUN-09:00 | 27.20 | 24.02 |
July | 0.119605E+11 | 15150.42 | 09-JUL-17:01 | 29.82 | 25.13 | 0.616605E+09 | 845.61 | 19-JUL-13:00 | 27.80 | 25.31 |
August | 0.120420E+11 | 13106.47 | 21-AUG-03:02 | 27.70 | 24.78 | 0.691386E+09 | 845.65 | 07-AUG-13:20 | 27.70 | 24.78 |
September | 0.958496E+10 | 11988.93 | 11-SEP-05:04 | 27.12 | 24.30 | 0.614216E+09 | 845.64 | 11-SEP-13:39 | 28.73 | 24.51 |
October | 0.921087E+10 | 11862.40 | 30-OCT-04:42 | 27.02 | 25.46 | 0.638126E+09 | 845.66 | 26-OCT-13:20 | 27.02 | 25.46 |
November | 0.812165E+10 | 11711.73 | 29-NOV-06:02 | 25.00 | 19.84 | 0.630971E+09 | 845.64 | 30-NOV-14:30 | 27.20 | 24.74 |
December | 0.706824E+10 | 11069.33 | 11-DEC-06:03 | 22.20 | 21.65 | 0.612447E+09 | 845.66 | 22-DEC-14:39 | 24.27 | 20.02 |
Annual Sum or Average | 0.107358E+12 | 0.764080E+10 | ||||||||
Minimum of Months | 0.529151E+10 | 11069.33 | 21.60 | 19.84 | 0.575815E+09 | 845.61 | 21.20 | 14.87 | ||
Maximum of Months | 0.120420E+11 | 15150.42 | 33.22 | 25.46 | 0.691386E+09 | 845.66 | 33.22 | 25.46 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.441137E+10 | 14408.09 | 01-JAN-10:23 | 25.85 | 21.37 | 0.409083E+09 | 544.97 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.471140E+10 | 9801.70 | 26-FEB-09:33 | 21.27 | 15.88 | 0.371784E+09 | 544.97 | 14-FEB-14:39 | 21.27 | 15.88 |
March | 0.640485E+10 | 8665.50 | 06-MAR-06:02 | 22.80 | 22.00 | 0.443944E+09 | 544.96 | 01-MAR-10:09 | 22.80 | 22.00 |
April | 0.728379E+10 | 14468.37 | 16-APR-08:23 | 24.45 | 21.59 | 0.395012E+09 | 544.98 | 17-APR-09:39 | 23.50 | 20.48 |
May | 0.773849E+10 | 14372.09 | 07-MAY-09:02 | 26.97 | 21.77 | 0.428661E+09 | 545.23 | 18-MAY-09:50 | 29.22 | 22.39 |
June | 0.823845E+10 | 11667.70 | 04-JUN-07:43 | 27.52 | 24.83 | 0.427250E+09 | 545.83 | 12-JUN-09:00 | 30.60 | 24.52 |
July | 0.869452E+10 | 11787.30 | 09-JUL-16:21 | 30.55 | 25.08 | 0.397450E+09 | 545.29 | 25-JUL-09:00 | 32.80 | 25.50 |
August | 0.852636E+10 | 14092.83 | 20-AUG-11:02 | 31.78 | 26.18 | 0.445329E+09 | 545.13 | 30-AUG-09:20 | 29.80 | 23.47 |
September | 0.753003E+10 | 14479.57 | 10-SEP-09:02 | 28.58 | 25.00 | 0.396135E+09 | 544.97 | 11-SEP-13:39 | 28.73 | 24.51 |
October | 0.713117E+10 | 11584.01 | 09-OCT-08:63 | 27.38 | 24.06 | 0.411334E+09 | 544.98 | 26-OCT-13:20 | 26.83 | 22.68 |
November | 0.588744E+10 | 7582.64 | 07-NOV-09:00 | 23.90 | 21.61 | 0.406463E+09 | 544.96 | 13-NOV-10:09 | 19.68 | 13.91 |
December | 0.485115E+10 | 6164.91 | 08-DEC-09:50 | 25.92 | 22.59 | 0.393538E+09 | 544.98 | 22-DEC-14:39 | 24.27 | 20.02 |
Annual Sum or Average | 0.814090E+11 | 0.492598E+10 | ||||||||
Minimum of Months | 0.441137E+10 | 6164.91 | 21.27 | 15.88 | 0.371784E+09 | 544.96 | 19.68 | 13.91 | ||
Maximum of Months | 0.869452E+10 | 14479.57 | 31.78 | 26.18 | 0.445329E+09 | 545.83 | 32.80 | 25.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.955609E+10 | 16088.26 | 01-JAN-13:42 | 26.28 | 21.78 | 0.640184E+09 | 929.23 | 02-JAN-14:39 | 28.90 | 23.86 |
February | 0.929916E+10 | 15923.94 | 20-FEB-12:13 | 24.07 | 17.34 | 0.581525E+09 | 910.95 | 21-FEB-14:30 | 25.85 | 14.25 |
March | 0.107720E+11 | 14928.79 | 26-MAR-13:03 | 27.30 | 22.23 | 0.690282E+09 | 875.94 | 01-MAR-14:30 | 27.30 | 22.23 |
April | 0.105086E+11 | 12918.54 | 16-APR-15:02 | 31.52 | 21.13 | 0.613600E+09 | 846.13 | 14-APR-13:39 | 31.52 | 21.13 |
May | 0.975811E+10 | 14791.55 | 29-MAY-15:42 | 33.22 | 24.49 | 0.665015E+09 | 845.92 | 22-MAY-13:00 | 33.22 | 24.49 |
June | 0.107032E+11 | 11741.91 | 19-JUN-03:02 | 24.40 | 23.08 | 0.662814E+09 | 845.75 | 02-JUN-13:00 | 24.40 | 23.08 |
July | 0.117014E+11 | 14755.48 | 30-JUL-13:02 | 32.88 | 25.38 | 0.616485E+09 | 846.05 | 03-JUL-13:20 | 32.88 | 25.38 |
August | 0.126796E+11 | 14881.54 | 20-AUG-12:23 | 32.20 | 25.83 | 0.691609E+09 | 847.95 | 07-AUG-13:20 | 32.20 | 25.83 |
September | 0.115107E+11 | 15470.85 | 17-SEP-14:22 | 31.10 | 24.59 | 0.615162E+09 | 855.61 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.127478E+11 | 15578.67 | 09-OCT-11:23 | 30.25 | 24.03 | 0.642125E+09 | 885.53 | 25-OCT-13:20 | 30.20 | 22.36 |
November | 0.119846E+11 | 16111.35 | 19-NOV-12:52 | 26.70 | 21.27 | 0.638896E+09 | 928.17 | 07-NOV-14:09 | 26.70 | 21.27 |
December | 0.113341E+11 | 16370.20 | 10-DEC-12:52 | 28.30 | 23.48 | 0.619426E+09 | 944.64 | 04-DEC-14:39 | 28.30 | 23.48 |
Annual Sum or Average | 0.132556E+12 | 0.767712E+10 | ||||||||
Minimum of Months | 0.929916E+10 | 11741.91 | 24.07 | 17.34 | 0.581525E+09 | 845.75 | 24.40 | 14.25 | ||
Maximum of Months | 0.127478E+11 | 16370.20 | 33.22 | 25.83 | 0.691609E+09 | 944.64 | 33.22 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.591779E+10 | 14593.77 | 30-JAN-04:02 | 21.60 | 20.86 | 0.410500E+09 | 544.97 | 27-JAN-10:00 | 21.60 | 20.86 |
February | 0.723891E+10 | 19098.06 | 20-FEB-16:12 | 26.70 | 17.88 | 0.373766E+09 | 544.98 | 14-FEB-14:39 | 26.70 | 17.88 |
March | 0.107574E+11 | 19355.03 | 12-MAR-16:12 | 24.40 | 18.45 | 0.446558E+09 | 544.96 | 24-MAR-13:00 | 26.10 | 19.80 |
April | 0.128543E+11 | 19971.68 | 02-APR-16:22 | 26.15 | 18.17 | 0.396967E+09 | 544.96 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.999484E+10 | 20347.41 | 29-MAY-15:42 | 33.22 | 24.49 | 0.429527E+09 | 544.95 | 22-MAY-13:00 | 33.22 | 24.49 |
June | 0.113140E+11 | 18237.06 | 25-JUN-14:23 | 30.55 | 24.99 | 0.428121E+09 | 544.96 | 12-JUN-09:00 | 30.55 | 24.99 |
July | 0.132704E+11 | 21287.01 | 09-JUL-17:01 | 29.82 | 25.13 | 0.398455E+09 | 544.95 | 26-JUL-13:00 | 31.70 | 25.48 |
August | 0.146623E+11 | 19590.05 | 20-AUG-16:22 | 30.60 | 24.86 | 0.446808E+09 | 544.98 | 07-AUG-13:20 | 30.60 | 24.86 |
September | 0.950091E+10 | 20436.80 | 17-SEP-16:22 | 31.10 | 24.77 | 0.396724E+09 | 544.97 | 11-SEP-13:39 | 31.10 | 24.77 |
October | 0.103863E+11 | 18378.54 | 08-OCT-14:13 | 29.40 | 23.92 | 0.412677E+09 | 544.99 | 26-OCT-13:20 | 26.83 | 22.68 |
November | 0.994012E+10 | 19566.70 | 19-NOV-14:52 | 26.70 | 20.63 | 0.408589E+09 | 544.98 | 30-NOV-14:30 | 27.20 | 24.74 |
December | 0.100373E+11 | 19770.00 | 25-DEC-14:32 | 26.30 | 23.46 | 0.398276E+09 | 545.01 | 22-DEC-14:39 | 26.30 | 23.46 |
Annual Sum or Average | 0.125875E+12 | 0.494697E+10 | ||||||||
Minimum of Months | 0.591779E+10 | 14593.77 | 21.60 | 17.88 | 0.373766E+09 | 544.95 | 21.60 | 17.53 | ||
Maximum of Months | 0.146623E+11 | 21287.01 | 33.22 | 25.13 | 0.446808E+09 | 545.01 | 33.22 | 25.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.404633E+10 | 10206.00 | 30-JAN-06:03 | 20.18 | 19.68 | 0.610591E+09 | 845.62 | 11-JAN-14:00 | 20.18 | 19.68 |
February | 0.421388E+10 | 10406.67 | 17-FEB-06:02 | 22.80 | 20.57 | 0.567485E+09 | 845.64 | 14-FEB-14:39 | 22.80 | 20.57 |
March | 0.541568E+10 | 10419.57 | 07-MAR-06:03 | 20.00 | 18.87 | 0.677697E+09 | 845.62 | 22-MAR-13:39 | 23.30 | 17.33 |
April | 0.635442E+10 | 10578.54 | 07-APR-05:02 | 23.30 | 20.25 | 0.611972E+09 | 845.63 | 20-APR-09:39 | 24.40 | 17.85 |
May | 0.844040E+10 | 12843.43 | 30-MAY-03:02 | 25.60 | 24.11 | 0.664917E+09 | 845.61 | 22-MAY-13:00 | 25.60 | 24.11 |
June | 0.932255E+10 | 12714.42 | 09-JUN-03:02 | 28.22 | 25.01 | 0.663222E+09 | 845.61 | 09-JUN-09:20 | 29.80 | 24.83 |
July | 0.947208E+10 | 12881.79 | 31-JUL-03:02 | 26.10 | 24.52 | 0.616751E+09 | 845.61 | 25-JUL-09:20 | 26.10 | 24.52 |
August | 0.908131E+10 | 12497.18 | 19-AUG-03:02 | 27.30 | 24.11 | 0.691442E+09 | 845.63 | 07-AUG-13:20 | 27.30 | 24.11 |
September | 0.818222E+10 | 12699.78 | 25-SEP-03:02 | 24.40 | 22.49 | 0.614065E+09 | 845.64 | 11-SEP-13:39 | 24.40 | 22.49 |
October | 0.712351E+10 | 11557.61 | 30-OCT-03:02 | 26.60 | 25.28 | 0.637892E+09 | 845.65 | 26-OCT-13:39 | 26.60 | 25.28 |
November | 0.561602E+10 | 10553.40 | 30-NOV-06:02 | 25.60 | 24.37 | 0.627639E+09 | 845.64 | 30-NOV-14:39 | 27.20 | 24.74 |
December | 0.426870E+10 | 10747.86 | 01-DEC-06:03 | 23.30 | 18.35 | 0.593357E+09 | 845.64 | 18-DEC-14:39 | 25.00 | 19.68 |
Annual Sum or Average | 0.815371E+11 | 0.757703E+10 | ||||||||
Minimum of Months | 0.404633E+10 | 10206.00 | 20.00 | 18.35 | 0.567485E+09 | 845.61 | 20.18 | 17.33 | ||
Maximum of Months | 0.947208E+10 | 12881.79 | 28.22 | 25.28 | 0.691442E+09 | 845.65 | 29.80 | 25.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362559E+10 | 13026.61 | 01-JAN-10:43 | 26.42 | 21.52 | 0.298116E+09 | 521.23 | 27-JAN-11:20 | 22.07 | 15.40 |
February | 0.390405E+10 | 8760.94 | 18-FEB-06:02 | 23.40 | 20.68 | 0.271918E+09 | 521.21 | 28-FEB-08:09 | 20.05 | 15.64 |
March | 0.527754E+10 | 10231.11 | 28-MAR-05:02 | 21.60 | 19.81 | 0.325343E+09 | 521.22 | 17-MAR-10:39 | 21.60 | 19.81 |
April | 0.613706E+10 | 15448.66 | 16-APR-09:52 | 27.20 | 21.71 | 0.291176E+09 | 521.22 | 20-APR-10:20 | 24.97 | 18.53 |
May | 0.719326E+10 | 14809.46 | 07-MAY-10:23 | 28.60 | 21.92 | 0.315677E+09 | 521.24 | 02-MAY-08:00 | 28.60 | 21.92 |
June | 0.756472E+10 | 14805.07 | 04-JUN-10:02 | 30.68 | 24.94 | 0.314535E+09 | 521.65 | 09-JUN-10:30 | 30.60 | 24.52 |
July | 0.781804E+10 | 15103.98 | 02-JUL-09:32 | 30.37 | 24.37 | 0.293736E+09 | 521.88 | 25-JUL-10:30 | 33.05 | 25.33 |
August | 0.747791E+10 | 14594.91 | 20-AUG-11:23 | 31.95 | 26.15 | 0.327825E+09 | 521.31 | 30-AUG-08:00 | 29.40 | 23.47 |
September | 0.696853E+10 | 15075.98 | 10-SEP-09:53 | 30.00 | 24.68 | 0.292016E+09 | 521.21 | 11-SEP-14:20 | 26.87 | 24.09 |
October | 0.627386E+10 | 10746.67 | 30-OCT-05:02 | 27.12 | 25.55 | 0.303507E+09 | 521.24 | 10-OCT-12:20 | 27.12 | 25.55 |
November | 0.477869E+10 | 10507.79 | 30-NOV-06:02 | 25.60 | 24.37 | 0.299073E+09 | 521.22 | 27-NOV-11:20 | 25.60 | 24.37 |
December | 0.348784E+10 | 10193.41 | 09-DEC-06:02 | 24.90 | 22.63 | 0.285813E+09 | 521.24 | 11-DEC-11:39 | 23.30 | 18.39 |
Annual Sum or Average | 0.705071E+11 | 0.361874E+10 | ||||||||
Minimum of Months | 0.348784E+10 | 8760.94 | 21.60 | 19.81 | 0.271918E+09 | 521.21 | 20.05 | 15.40 | ||
Maximum of Months | 0.781804E+10 | 15448.66 | 31.95 | 26.15 | 0.327825E+09 | 521.88 | 33.05 | 25.55 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.870235E+10 | 14494.34 | 01-JAN-10:43 | 26.42 | 21.52 | 0.643294E+09 | 966.82 | 02-JAN-14:39 | 28.90 | 23.86 |
February | 0.802994E+10 | 15022.06 | 20-FEB-14:02 | 26.20 | 17.78 | 0.582580E+09 | 939.30 | 21-FEB-14:39 | 25.93 | 14.05 |
March | 0.852846E+10 | 12433.91 | 12-MAR-15:22 | 24.40 | 18.19 | 0.688495E+09 | 901.95 | 01-MAR-14:39 | 24.40 | 18.19 |
April | 0.765695E+10 | 13426.93 | 16-APR-13:53 | 31.70 | 21.16 | 0.613344E+09 | 845.96 | 25-APR-13:00 | 27.20 | 24.01 |
May | 0.839730E+10 | 12201.55 | 30-MAY-03:02 | 25.60 | 24.11 | 0.664869E+09 | 845.81 | 22-MAY-13:00 | 25.60 | 24.11 |
June | 0.883342E+10 | 12063.97 | 09-JUN-03:02 | 28.22 | 25.01 | 0.662938E+09 | 845.69 | 02-JUN-13:00 | 28.22 | 25.01 |
July | 0.920787E+10 | 13337.78 | 30-JUL-14:02 | 33.40 | 24.78 | 0.616548E+09 | 845.79 | 26-JUL-13:00 | 33.40 | 24.78 |
August | 0.980675E+10 | 12285.82 | 06-AUG-14:02 | 32.12 | 25.32 | 0.691809E+09 | 851.50 | 31-AUG-13:20 | 31.70 | 24.32 |
September | 0.102316E+11 | 14114.45 | 17-SEP-13:13 | 31.10 | 24.35 | 0.615517E+09 | 879.65 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.110376E+11 | 14753.10 | 29-OCT-11:52 | 30.60 | 24.87 | 0.646099E+09 | 916.06 | 25-OCT-13:00 | 30.60 | 24.87 |
November | 0.992311E+10 | 14861.82 | 19-NOV-13:32 | 26.70 | 21.27 | 0.642873E+09 | 968.95 | 07-NOV-14:20 | 26.70 | 21.27 |
December | 0.883303E+10 | 15445.59 | 03-DEC-13:52 | 24.40 | 18.35 | 0.619242E+09 | 976.73 | 04-DEC-14:39 | 25.93 | 17.99 |
Annual Sum or Average | 0.109188E+12 | 0.768761E+10 | ||||||||
Minimum of Months | 0.765695E+10 | 12063.97 | 24.40 | 17.78 | 0.582580E+09 | 845.69 | 24.40 | 14.05 | ||
Maximum of Months | 0.110376E+11 | 15445.59 | 33.40 | 25.32 | 0.691809E+09 | 976.73 | 33.40 | 25.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.383446E+10 | 9293.84 | 14-JAN-06:03 | 23.62 | 21.60 | 0.399991E+09 | 544.96 | 11-JAN-14:39 | 23.62 | 21.60 |
February | 0.425041E+10 | 15836.29 | 20-FEB-15:22 | 26.70 | 17.88 | 0.368854E+09 | 544.97 | 14-FEB-14:39 | 26.70 | 17.88 |
March | 0.584470E+10 | 15891.48 | 12-MAR-16:42 | 24.40 | 18.60 | 0.441215E+09 | 544.95 | 01-MAR-10:09 | 24.40 | 18.60 |
April | 0.677474E+10 | 16853.38 | 09-APR-17:32 | 25.97 | 18.41 | 0.396095E+09 | 544.96 | 20-APR-09:20 | 24.40 | 17.64 |
May | 0.758849E+10 | 16044.57 | 29-MAY-16:32 | 32.23 | 24.43 | 0.429269E+09 | 544.94 | 22-MAY-13:00 | 32.23 | 24.43 |
June | 0.758655E+10 | 14944.13 | 10-JUN-17:06 | 30.60 | 24.10 | 0.427882E+09 | 544.94 | 09-JUN-09:20 | 30.60 | 24.10 |
July | 0.816542E+10 | 16548.33 | 16-JUL-16:12 | 30.20 | 23.46 | 0.398157E+09 | 544.94 | 25-JUL-09:20 | 30.93 | 25.34 |
August | 0.825867E+10 | 15888.49 | 20-AUG-16:42 | 30.60 | 24.86 | 0.446416E+09 | 544.96 | 07-AUG-13:20 | 30.60 | 24.86 |
September | 0.702654E+10 | 15852.86 | 17-SEP-16:32 | 31.10 | 24.71 | 0.396440E+09 | 544.96 | 11-SEP-13:39 | 31.10 | 24.71 |
October | 0.664211E+10 | 16297.80 | 15-OCT-15:32 | 29.07 | 20.86 | 0.412087E+09 | 544.97 | 26-OCT-13:30 | 25.55 | 22.33 |
November | 0.526250E+10 | 11801.77 | 20-NOV-04:02 | 24.40 | 20.57 | 0.405929E+09 | 544.97 | 30-NOV-14:39 | 27.20 | 24.74 |
December | 0.428372E+10 | 11822.99 | 23-DEC-06:02 | 22.80 | 22.12 | 0.388842E+09 | 544.98 | 18-DEC-14:39 | 22.80 | 22.12 |
Annual Sum or Average | 0.755183E+11 | 0.491118E+10 | ||||||||
Minimum of Months | 0.383446E+10 | 9293.84 | 22.80 | 17.88 | 0.368854E+09 | 544.94 | 22.80 | 17.64 | ||
Maximum of Months | 0.825867E+10 | 16853.38 | 32.23 | 24.86 | 0.446416E+09 | 544.98 | 32.23 | 25.34 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363827E+10 | 9742.60 | 30-JAN-06:03 | 20.18 | 19.68 | 0.589646E+09 | 845.61 | 20-JAN-14:20 | 20.18 | 19.68 |
February | 0.405091E+10 | 11727.93 | 18-FEB-06:02 | 23.40 | 20.68 | 0.557578E+09 | 845.62 | 14-FEB-14:39 | 23.40 | 20.68 |
March | 0.547753E+10 | 11332.13 | 06-MAR-06:02 | 22.80 | 22.00 | 0.667039E+09 | 845.62 | 17-MAR-13:00 | 21.70 | 14.91 |
April | 0.677231E+10 | 11776.53 | 07-APR-05:02 | 23.30 | 20.25 | 0.610840E+09 | 845.63 | 20-APR-09:00 | 24.40 | 18.06 |
May | 0.932182E+10 | 16320.55 | 29-MAY-15:42 | 33.22 | 24.49 | 0.665185E+09 | 845.61 | 22-MAY-13:00 | 33.22 | 24.49 |
June | 0.104036E+11 | 15706.83 | 25-JUN-16:03 | 28.98 | 24.10 | 0.663575E+09 | 845.68 | 02-JUN-13:00 | 28.98 | 24.10 |
July | 0.107082E+11 | 16105.98 | 16-JUL-16:12 | 30.20 | 23.46 | 0.617261E+09 | 845.60 | 14-JUL-13:39 | 30.20 | 23.46 |
August | 0.100134E+11 | 15551.04 | 06-AUG-14:02 | 32.12 | 25.32 | 0.691685E+09 | 845.61 | 07-AUG-13:20 | 29.07 | 24.82 |
September | 0.903549E+10 | 15473.50 | 04-SEP-15:13 | 30.40 | 24.10 | 0.614419E+09 | 845.63 | 11-SEP-13:39 | 28.73 | 24.51 |
October | 0.754507E+10 | 12015.39 | 02-OCT-05:03 | 26.70 | 25.31 | 0.637680E+09 | 845.64 | 26-OCT-13:30 | 25.55 | 22.33 |
November | 0.561351E+10 | 11832.11 | 30-NOV-06:02 | 25.60 | 24.37 | 0.622462E+09 | 845.62 | 30-NOV-14:30 | 27.20 | 24.74 |
December | 0.400922E+10 | 11459.62 | 09-DEC-06:02 | 24.90 | 22.63 | 0.575046E+09 | 845.63 | 07-DEC-14:00 | 24.90 | 22.63 |
Annual Sum or Average | 0.865893E+11 | 0.751242E+10 | ||||||||
Minimum of Months | 0.363827E+10 | 9742.60 | 20.18 | 19.68 | 0.557578E+09 | 845.60 | 20.18 | 14.91 | ||
Maximum of Months | 0.107082E+11 | 16320.55 | 33.22 | 25.32 | 0.691685E+09 | 845.68 | 33.22 | 24.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333571E+10 | 11552.33 | 01-JAN-10:32 | 26.13 | 21.45 | 0.400705E+09 | 544.97 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.385779E+10 | 7982.43 | 18-FEB-06:02 | 23.40 | 20.68 | 0.367427E+09 | 544.96 | 23-FEB-10:50 | 24.13 | 18.14 |
March | 0.538892E+10 | 10126.35 | 14-MAR-05:02 | 23.30 | 22.15 | 0.441934E+09 | 544.96 | 01-MAR-10:09 | 23.30 | 22.15 |
April | 0.661042E+10 | 15314.87 | 16-APR-11:23 | 30.00 | 21.34 | 0.395189E+09 | 544.96 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.798458E+10 | 15266.54 | 29-MAY-15:42 | 33.22 | 24.49 | 0.428936E+09 | 545.32 | 17-MAY-09:00 | 33.22 | 24.49 |
June | 0.850240E+10 | 15430.73 | 04-JUN-10:02 | 30.68 | 24.94 | 0.427837E+09 | 545.66 | 12-JUN-09:00 | 30.60 | 24.52 |
July | 0.888660E+10 | 15534.51 | 30-JUL-08:43 | 29.72 | 24.67 | 0.398204E+09 | 545.24 | 25-JUL-09:00 | 29.72 | 24.67 |
August | 0.832532E+10 | 15208.48 | 20-AUG-11:23 | 31.95 | 26.15 | 0.445997E+09 | 545.27 | 30-AUG-09:00 | 30.60 | 23.44 |
September | 0.778627E+10 | 15422.21 | 24-SEP-10:13 | 29.97 | 24.76 | 0.396433E+09 | 544.96 | 11-SEP-13:39 | 29.97 | 24.76 |
October | 0.675593E+10 | 12728.45 | 29-OCT-15:12 | 29.80 | 25.43 | 0.411691E+09 | 544.97 | 26-OCT-13:20 | 29.80 | 25.43 |
November | 0.489778E+10 | 10866.19 | 30-NOV-06:02 | 25.60 | 24.37 | 0.405033E+09 | 544.96 | 13-NOV-10:09 | 25.60 | 24.37 |
December | 0.336124E+10 | 9344.19 | 09-DEC-06:02 | 24.90 | 22.63 | 0.382341E+09 | 544.96 | 22-DEC-14:30 | 24.45 | 19.96 |
Annual Sum or Average | 0.756930E+11 | 0.490173E+10 | ||||||||
Minimum of Months | 0.333571E+10 | 7982.43 | 23.30 | 20.68 | 0.367427E+09 | 544.96 | 21.70 | 15.05 | ||
Maximum of Months | 0.888660E+10 | 15534.51 | 33.22 | 26.15 | 0.445997E+09 | 545.66 | 33.22 | 25.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.817369E+10 | 17221.88 | 01-JAN-13:12 | 26.83 | 21.65 | 0.630244E+09 | 921.34 | 02-JAN-14:39 | 28.90 | 23.86 |
February | 0.788886E+10 | 17642.43 | 20-FEB-13:52 | 26.10 | 17.76 | 0.575135E+09 | 900.82 | 21-FEB-14:50 | 26.02 | 13.83 |
March | 0.859632E+10 | 16524.45 | 26-MAR-13:32 | 27.60 | 22.33 | 0.682310E+09 | 862.13 | 01-MAR-14:39 | 27.60 | 22.33 |
April | 0.815627E+10 | 15723.30 | 16-APR-16:42 | 31.02 | 22.09 | 0.612466E+09 | 846.15 | 14-APR-13:20 | 31.02 | 22.09 |
May | 0.927008E+10 | 16323.71 | 29-MAY-15:42 | 33.22 | 24.49 | 0.665054E+09 | 845.99 | 22-MAY-13:00 | 33.22 | 24.49 |
June | 0.987132E+10 | 15578.43 | 25-JUN-14:43 | 30.18 | 24.78 | 0.663298E+09 | 845.63 | 12-JUN-09:00 | 30.18 | 24.78 |
July | 0.104205E+11 | 16104.56 | 30-JUL-14:02 | 33.40 | 24.78 | 0.617056E+09 | 845.88 | 26-JUL-13:00 | 33.40 | 24.78 |
August | 0.107893E+11 | 15909.64 | 06-AUG-14:02 | 32.12 | 25.32 | 0.691975E+09 | 846.06 | 02-AUG-13:20 | 32.12 | 25.32 |
September | 0.112969E+11 | 16799.20 | 17-SEP-13:13 | 31.10 | 24.35 | 0.615436E+09 | 861.98 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.117456E+11 | 17451.41 | 29-OCT-11:52 | 30.60 | 24.87 | 0.642257E+09 | 891.05 | 25-OCT-13:00 | 30.60 | 24.87 |
November | 0.100724E+11 | 16863.62 | 26-NOV-14:02 | 21.70 | 12.56 | 0.635512E+09 | 930.92 | 07-NOV-14:20 | 21.70 | 12.56 |
December | 0.851058E+10 | 18172.71 | 03-DEC-14:22 | 24.40 | 18.50 | 0.607991E+09 | 934.81 | 04-DEC-14:39 | 25.93 | 17.99 |
Annual Sum or Average | 0.114792E+12 | 0.763873E+10 | ||||||||
Minimum of Months | 0.788886E+10 | 15578.43 | 21.70 | 12.56 | 0.575135E+09 | 845.63 | 21.70 | 12.56 | ||
Maximum of Months | 0.117456E+11 | 18172.71 | 33.40 | 25.32 | 0.691975E+09 | 934.81 | 33.40 | 25.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.364134E+10 | 8505.30 | 30-JAN-06:03 | 20.18 | 19.68 | 0.387643E+09 | 544.95 | 10-JAN-14:00 | 20.18 | 19.68 |
February | 0.419921E+10 | 18177.48 | 20-FEB-16:32 | 26.70 | 17.88 | 0.363333E+09 | 544.96 | 21-FEB-14:00 | 26.10 | 13.62 |
March | 0.597231E+10 | 18366.43 | 12-MAR-16:32 | 24.40 | 18.55 | 0.434851E+09 | 544.95 | 24-MAR-13:00 | 26.10 | 19.80 |
April | 0.719740E+10 | 18827.54 | 09-APR-17:32 | 25.97 | 18.41 | 0.395567E+09 | 544.96 | 20-APR-09:00 | 24.40 | 18.06 |
May | 0.831518E+10 | 19076.71 | 29-MAY-15:42 | 33.22 | 24.49 | 0.429226E+09 | 544.94 | 22-MAY-13:00 | 33.22 | 24.49 |
June | 0.842612E+10 | 17226.28 | 25-JUN-16:03 | 28.98 | 24.10 | 0.427904E+09 | 544.94 | 12-JUN-09:00 | 28.98 | 24.10 |
July | 0.915231E+10 | 18692.33 | 16-JUL-16:12 | 30.20 | 23.46 | 0.398222E+09 | 544.94 | 26-JUL-13:00 | 31.70 | 25.48 |
August | 0.902458E+10 | 17613.54 | 20-AUG-16:42 | 30.60 | 24.86 | 0.446406E+09 | 544.95 | 07-AUG-13:20 | 30.60 | 24.86 |
September | 0.776383E+10 | 17888.14 | 10-SEP-15:42 | 31.10 | 25.01 | 0.396405E+09 | 544.96 | 11-SEP-13:39 | 28.73 | 24.51 |
October | 0.705203E+10 | 18129.95 | 15-OCT-15:32 | 29.07 | 20.86 | 0.411816E+09 | 544.97 | 26-OCT-13:20 | 26.83 | 22.68 |
November | 0.533334E+10 | 12705.02 | 30-NOV-06:02 | 25.60 | 24.37 | 0.402926E+09 | 544.96 | 16-NOV-14:39 | 25.60 | 24.37 |
December | 0.418345E+10 | 18035.00 | 10-DEC-15:22 | 28.60 | 22.59 | 0.378216E+09 | 544.97 | 18-DEC-14:20 | 25.00 | 19.88 |
Annual Sum or Average | 0.802611E+11 | 0.487251E+10 | ||||||||
Minimum of Months | 0.364134E+10 | 8505.30 | 20.18 | 17.88 | 0.363333E+09 | 544.94 | 20.18 | 13.62 | ||
Maximum of Months | 0.915231E+10 | 19076.71 | 33.22 | 25.01 | 0.446406E+09 | 544.97 | 33.22 | 25.48 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.549239E+10 | 12873.12 | 02-JAN-06:15 | 19.23 | 19.01 | 0.00 | 0.00 | 01-JAN-00:10 | 19.23 | 19.01 |
February | 0.564046E+10 | 10052.48 | 21-FEB-06:15 | 15.60 | 15.30 | 0.00 | 0.00 | 01-FEB-00:10 | 15.60 | 15.30 |
March | 0.717619E+10 | 8894.67 | 27-MAR-05:15 | 20.40 | 20.06 | 0.00 | 0.00 | 01-MAR-00:10 | 20.40 | 20.06 |
April | 0.804865E+10 | 11559.45 | 17-APR-05:15 | 18.90 | 16.76 | 0.00 | 0.00 | 01-APR-00:10 | 18.90 | 16.76 |
May | 0.839433E+10 | 13226.61 | 30-MAY-05:15 | 24.03 | 22.53 | 0.00 | 0.00 | 01-MAY-00:10 | 24.03 | 22.53 |
June | 0.921731E+10 | 11983.38 | 12-JUN-05:15 | 25.60 | 24.44 | 0.00 | 0.00 | 01-JUN-00:10 | 25.60 | 24.44 |
July | 0.100606E+11 | 13279.78 | 31-JUL-05:15 | 26.10 | 24.39 | 0.00 | 0.00 | 01-JUL-00:10 | 26.10 | 24.39 |
August | 0.102619E+11 | 13515.92 | 21-AUG-05:15 | 27.20 | 24.60 | 0.00 | 0.00 | 01-AUG-00:10 | 27.20 | 24.60 |
September | 0.869705E+10 | 12594.76 | 05-SEP-05:15 | 22.93 | 21.59 | 0.00 | 0.00 | 01-SEP-00:10 | 22.93 | 21.59 |
October | 0.845448E+10 | 11730.27 | 10-OCT-05:15 | 23.90 | 22.40 | 0.00 | 0.00 | 01-OCT-00:10 | 23.90 | 22.40 |
November | 0.746613E+10 | 10566.43 | 24-NOV-06:15 | 21.10 | 21.10 | 0.00 | 0.00 | 01-NOV-00:10 | 21.10 | 21.10 |
December | 0.641656E+10 | 11194.53 | 26-DEC-06:15 | 20.03 | 17.71 | 0.00 | 0.00 | 01-DEC-00:10 | 20.03 | 17.71 |
Annual Sum or Average | 0.953261E+11 | 0.00 | ||||||||
Minimum of Months | 0.549239E+10 | 8894.67 | 15.60 | 15.30 | 0.00 | 0.00 | 15.60 | 15.30 | ||
Maximum of Months | 0.102619E+11 | 13515.92 | 27.20 | 24.60 | 0.00 | 0.00 | 27.20 | 24.60 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.365887E+10 | 8785.85 | 02-JAN-06:15 | 19.23 | 19.01 | 0.00 | 0.00 | 01-JAN-00:10 | 19.23 | 19.01 |
February | 0.365712E+10 | 5552.85 | 21-FEB-06:15 | 15.60 | 15.30 | 0.00 | 0.00 | 01-FEB-00:10 | 15.60 | 15.30 |
March | 0.487610E+10 | 6584.83 | 06-MAR-06:02 | 22.80 | 22.00 | 0.00 | 0.00 | 01-MAR-00:10 | 22.80 | 22.00 |
April | 0.558203E+10 | 7224.14 | 17-APR-05:02 | 18.90 | 16.76 | 0.00 | 0.00 | 01-APR-00:10 | 18.90 | 16.76 |
May | 0.692050E+10 | 7828.90 | 31-MAY-05:02 | 25.00 | 24.24 | 0.00 | 0.00 | 01-MAY-00:10 | 25.00 | 24.24 |
June | 0.744714E+10 | 7754.55 | 19-JUN-05:15 | 24.40 | 23.01 | 0.00 | 0.00 | 01-JUN-00:10 | 24.40 | 23.01 |
July | 0.767755E+10 | 7475.43 | 03-JUL-05:15 | 25.20 | 24.18 | 0.00 | 0.00 | 01-JUL-00:10 | 25.20 | 24.18 |
August | 0.752421E+10 | 7563.25 | 01-AUG-05:02 | 28.30 | 24.58 | 0.00 | 0.00 | 01-AUG-00:10 | 28.30 | 24.58 |
September | 0.709520E+10 | 8487.88 | 05-SEP-05:15 | 22.93 | 21.59 | 0.00 | 0.00 | 01-SEP-00:10 | 22.93 | 21.59 |
October | 0.651643E+10 | 8548.70 | 02-OCT-05:15 | 26.70 | 25.24 | 0.00 | 0.00 | 01-OCT-00:10 | 26.70 | 25.24 |
November | 0.514476E+10 | 7312.13 | 07-NOV-06:15 | 20.20 | 19.86 | 0.00 | 0.00 | 01-NOV-00:10 | 20.20 | 19.86 |
December | 0.386510E+10 | 5547.98 | 09-DEC-06:15 | 24.80 | 22.60 | 0.00 | 0.00 | 01-DEC-00:10 | 24.80 | 22.60 |
Annual Sum or Average | 0.699650E+11 | 0.00 | ||||||||
Minimum of Months | 0.365712E+10 | 5547.98 | 15.60 | 15.30 | 0.00 | 0.00 | 15.60 | 15.30 | ||
Maximum of Months | 0.767755E+10 | 8785.85 | 28.30 | 25.24 | 0.00 | 0.00 | 28.30 | 25.24 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.412775E+10 | 11417.47 | 02-JAN-15:00 | 28.90 | 23.37 | 0.00 | 0.00 | 01-JAN-00:10 | 28.90 | 23.37 |
February | 0.554719E+10 | 11710.30 | 17-FEB-14:30 | 26.70 | 21.51 | 0.00 | 0.00 | 01-FEB-00:10 | 26.70 | 21.51 |
March | 0.803180E+10 | 14989.21 | 27-MAR-15:20 | 27.60 | 22.33 | 0.00 | 0.00 | 01-MAR-00:10 | 27.60 | 22.33 |
April | 0.107336E+11 | 17945.07 | 13-APR-14:00 | 28.90 | 24.03 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 24.03 |
May | 0.137735E+11 | 19713.76 | 18-MAY-13:50 | 30.78 | 23.04 | 0.00 | 0.00 | 01-MAY-00:10 | 30.78 | 23.04 |
June | 0.145874E+11 | 20492.50 | 09-JUN-13:50 | 31.02 | 24.94 | 0.00 | 0.00 | 01-JUN-00:10 | 31.02 | 24.94 |
July | 0.158693E+11 | 20824.07 | 28-JUL-15:20 | 35.00 | 25.13 | 0.00 | 0.00 | 01-JUL-00:10 | 35.00 | 25.13 |
August | 0.143264E+11 | 19607.58 | 23-AUG-13:50 | 32.48 | 25.39 | 0.00 | 0.00 | 01-AUG-00:10 | 32.48 | 25.39 |
September | 0.130034E+11 | 17267.58 | 08-SEP-15:20 | 32.20 | 23.36 | 0.00 | 0.00 | 01-SEP-00:10 | 32.20 | 23.36 |
October | 0.103926E+11 | 16511.24 | 06-OCT-13:10 | 29.82 | 23.71 | 0.00 | 0.00 | 01-OCT-00:10 | 29.82 | 23.71 |
November | 0.734022E+10 | 13139.33 | 10-NOV-14:10 | 28.90 | 24.10 | 0.00 | 0.00 | 01-NOV-00:10 | 28.90 | 24.10 |
December | 0.464558E+10 | 11228.72 | 08-DEC-14:40 | 27.40 | 22.79 | 0.00 | 0.00 | 01-DEC-00:10 | 27.40 | 22.79 |
Annual Sum or Average | 0.122379E+12 | 0.00 | ||||||||
Minimum of Months | 0.412775E+10 | 11228.72 | 26.70 | 21.51 | 0.00 | 0.00 | 26.70 | 21.51 | ||
Maximum of Months | 0.158693E+11 | 20824.07 | 35.00 | 25.39 | 0.00 | 0.00 | 35.00 | 25.39 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.429339E+10 | 1955.53 | 17-JAN-17:00 | 21.70 | 15.62 | 95234508.45 | 126.85 | 18-JAN-14:09 | 23.30 | 17.93 |
February | 0.855245E+10 | 4138.20 | 20-FEB-17:45 | 25.28 | 17.48 | 86409112.83 | 126.86 | 13-FEB-14:00 | 25.28 | 17.48 |
March | 0.145319E+11 | 7211.65 | 31-MAR-23:53 | 22.60 | 17.97 | 0.103247E+09 | 126.85 | 13-MAR-09:00 | 22.60 | 17.97 |
April | 0.189752E+11 | 7811.74 | 09-APR-18:00 | 25.60 | 18.39 | 91608089.17 | 126.83 | 26-APR-13:00 | 22.20 | 21.37 |
May | 0.455489E+10 | 3494.95 | 31-MAY-24:00 | 26.70 | 24.69 | 99233700.88 | 126.85 | 01-MAY-13:00 | 26.70 | 24.69 |
June | 0.927102E+10 | 5343.56 | 30-JUN-23:57 | 26.90 | 23.74 | 98988274.89 | 126.88 | 23-JUN-13:00 | 26.90 | 23.74 |
July | 0.146747E+11 | 7273.02 | 31-JUL-24:00 | 28.60 | 26.07 | 91897178.14 | 126.85 | 12-JUL-09:09 | 28.60 | 26.07 |
August | 0.196757E+11 | 7732.63 | 20-AUG-18:12 | 29.63 | 24.40 | 0.103269E+09 | 128.18 | 23-AUG-13:39 | 32.77 | 25.41 |
September | 0.443263E+10 | 3459.07 | 30-SEP-23:57 | 28.00 | 23.53 | 91605144.51 | 126.82 | 25-SEP-09:09 | 28.00 | 23.53 |
October | 0.960230E+10 | 5367.66 | 31-OCT-24:00 | 22.50 | 21.29 | 95255914.93 | 126.87 | 04-OCT-13:09 | 22.50 | 21.29 |
November | 0.141224E+11 | 5795.10 | 26-NOV-16:55 | 21.10 | 12.60 | 94314051.11 | 126.85 | 24-NOV-10:09 | 21.10 | 12.60 |
December | 0.195331E+11 | 7759.20 | 03-DEC-16:55 | 23.90 | 16.19 | 91883754.43 | 126.83 | 29-DEC-10:09 | 19.27 | 17.74 |
Annual Sum or Average | 0.142220E+12 | 0.114295E+10 | ||||||||
Minimum of Months | 0.429339E+10 | 1955.53 | 21.10 | 12.60 | 86409112.83 | 126.82 | 19.27 | 12.60 | ||
Maximum of Months | 0.196757E+11 | 7811.74 | 29.63 | 26.07 | 0.103269E+09 | 128.18 | 32.77 | 26.07 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.353489E+10 | 1788.16 | 02-JAN-17:00 | 25.00 | 20.39 | 95232589.94 | 126.84 | 19-JAN-14:00 | 25.00 | 18.53 |
February | 0.775407E+10 | 3784.35 | 20-FEB-17:45 | 25.28 | 17.48 | 86408333.45 | 126.86 | 02-FEB-10:50 | 25.28 | 17.48 |
March | 0.136670E+11 | 6928.25 | 31-MAR-23:53 | 22.60 | 17.97 | 0.103246E+09 | 126.85 | 10-MAR-10:00 | 22.60 | 17.97 |
April | 0.180783E+11 | 7353.77 | 09-APR-18:00 | 25.60 | 18.39 | 91608010.21 | 126.83 | 26-APR-13:00 | 22.20 | 21.37 |
May | 0.419377E+10 | 3371.50 | 31-MAY-24:00 | 26.70 | 24.69 | 99233281.03 | 126.82 | 24-MAY-09:00 | 26.70 | 24.69 |
June | 0.877876E+10 | 5200.86 | 30-JUN-23:57 | 26.90 | 23.74 | 98986365.33 | 126.87 | 23-JUN-13:00 | 26.90 | 23.74 |
July | 0.139645E+11 | 6990.75 | 31-JUL-24:00 | 28.60 | 26.07 | 91896539.89 | 126.85 | 10-JUL-09:09 | 28.60 | 26.07 |
August | 0.187605E+11 | 7258.33 | 20-AUG-17:44 | 30.10 | 24.42 | 0.103334E+09 | 129.39 | 23-AUG-13:50 | 32.48 | 25.39 |
September | 0.406176E+10 | 3328.14 | 30-SEP-23:27 | 28.15 | 23.35 | 91605145.51 | 126.82 | 12-SEP-09:30 | 28.15 | 23.35 |
October | 0.904347E+10 | 5058.87 | 31-OCT-24:00 | 22.50 | 21.29 | 95254308.93 | 126.87 | 04-OCT-09:09 | 22.50 | 21.29 |
November | 0.132853E+11 | 5508.29 | 07-NOV-17:00 | 27.80 | 22.39 | 94313120.61 | 126.85 | 29-NOV-10:00 | 26.10 | 24.93 |
December | 0.183064E+11 | 7300.35 | 06-DEC-17:00 | 25.60 | 21.66 | 91883752.62 | 126.83 | 29-DEC-10:09 | 19.27 | 17.74 |
Annual Sum or Average | 0.133429E+12 | 0.114300E+10 | ||||||||
Minimum of Months | 0.353489E+10 | 1788.16 | 22.50 | 17.48 | 86408333.45 | 126.82 | 19.27 | 17.48 | ||
Maximum of Months | 0.187605E+11 | 7353.77 | 30.10 | 26.07 | 0.103334E+09 | 129.39 | 32.48 | 26.07 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298315E+10 | 1818.40 | 02-JAN-17:00 | 25.00 | 20.39 | 95232083.27 | 126.84 | 19-JAN-14:00 | 25.00 | 18.53 |
February | 0.745495E+10 | 3902.16 | 20-FEB-17:35 | 25.57 | 17.57 | 86408650.03 | 126.86 | 02-FEB-10:00 | 25.57 | 17.57 |
March | 0.135069E+11 | 6887.04 | 31-MAR-23:53 | 22.60 | 17.97 | 0.103247E+09 | 126.85 | 10-MAR-10:00 | 22.60 | 17.97 |
April | 0.181089E+11 | 7629.30 | 09-APR-18:00 | 25.60 | 18.39 | 91608412.80 | 126.83 | 26-APR-13:00 | 22.20 | 21.37 |
May | 0.432331E+10 | 3397.78 | 31-MAY-24:00 | 26.70 | 24.69 | 99233562.63 | 126.84 | 01-MAY-13:00 | 26.70 | 24.69 |
June | 0.891505E+10 | 5223.24 | 30-JUN-23:57 | 26.90 | 23.74 | 98987915.69 | 126.87 | 23-JUN-13:00 | 26.90 | 23.74 |
July | 0.141330E+11 | 7022.46 | 31-JUL-24:00 | 28.60 | 26.07 | 91897502.77 | 126.85 | 17-JUL-13:09 | 28.60 | 26.07 |
August | 0.188630E+11 | 7532.87 | 06-AUG-16:05 | 28.22 | 23.94 | 0.103310E+09 | 129.21 | 23-AUG-13:50 | 32.48 | 25.39 |
September | 0.418626E+10 | 3399.26 | 30-SEP-23:57 | 28.00 | 23.53 | 91605147.21 | 126.82 | 12-SEP-09:30 | 28.00 | 23.53 |
October | 0.908562E+10 | 4985.04 | 31-OCT-24:00 | 22.50 | 21.29 | 95255171.31 | 126.87 | 04-OCT-09:09 | 22.50 | 21.29 |
November | 0.131295E+11 | 5570.12 | 07-NOV-17:00 | 27.80 | 22.39 | 94313692.96 | 126.85 | 30-NOV-14:00 | 27.20 | 24.74 |
December | 0.179089E+11 | 7359.60 | 06-DEC-17:00 | 25.60 | 21.66 | 91884159.57 | 126.83 | 29-DEC-10:09 | 19.27 | 17.74 |
Annual Sum or Average | 0.132599E+12 | 0.114298E+10 | ||||||||
Minimum of Months | 0.298315E+10 | 1818.40 | 22.50 | 17.57 | 86408650.03 | 126.82 | 19.27 | 17.57 | ||
Maximum of Months | 0.188630E+11 | 7629.30 | 28.60 | 26.07 | 0.103310E+09 | 129.21 | 32.48 | 26.07 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241861E+12 | 92927.03 | 02-JAN-17:00 | 25.00 | 20.39 | 0.206144E+10 | 2745.29 | 02-JAN-10:30 | 25.00 | 20.39 |
February | 0.438524E+12 | 183885.79 | 21-FEB-17:00 | 25.60 | 14.07 | 0.187022E+10 | 2745.29 | 01-FEB-10:20 | 25.60 | 14.07 |
March | 0.730116E+12 | 359120.95 | 31-MAR-23:53 | 22.60 | 17.97 | 0.223475E+10 | 2745.29 | 07-MAR-14:20 | 22.60 | 17.97 |
April | 0.942805E+12 | 366578.09 | 17-APR-16:00 | 31.70 | 20.29 | 0.198297E+10 | 2745.29 | 11-APR-09:20 | 31.70 | 20.29 |
May | 0.241634E+12 | 176165.24 | 31-MAY-24:00 | 26.70 | 24.69 | 0.214810E+10 | 2745.29 | 12-MAY-13:50 | 26.70 | 24.69 |
June | 0.469889E+12 | 267644.09 | 30-JUN-23:53 | 26.90 | 23.74 | 0.214213E+10 | 2745.29 | 13-JUN-09:39 | 26.90 | 23.74 |
July | 0.731742E+12 | 359963.91 | 31-JUL-24:00 | 28.60 | 26.07 | 0.198894E+10 | 2745.29 | 27-JUL-09:00 | 28.60 | 26.07 |
August | 0.977415E+12 | 367794.18 | 21-AUG-16:00 | 32.20 | 26.46 | 0.223475E+10 | 2745.29 | 23-AUG-13:39 | 32.77 | 25.41 |
September | 0.235987E+12 | 176532.71 | 30-SEP-23:57 | 28.00 | 23.53 | 0.198297E+10 | 2745.29 | 07-SEP-13:39 | 28.00 | 23.53 |
October | 0.487818E+12 | 268431.12 | 31-OCT-24:00 | 22.50 | 21.29 | 0.206144E+10 | 2745.29 | 24-OCT-13:00 | 22.50 | 21.29 |
November | 0.709249E+12 | 275996.61 | 06-NOV-17:00 | 27.80 | 20.36 | 0.204131E+10 | 2745.29 | 01-NOV-13:30 | 27.80 | 20.36 |
December | 0.977900E+12 | 367758.45 | 26-DEC-17:00 | 17.20 | 13.09 | 0.198894E+10 | 2745.29 | 11-DEC-10:20 | 17.20 | 13.09 |
Annual Sum or Average | 0.718494E+13 | 0.247380E+11 | ||||||||
Minimum of Months | 0.235987E+12 | 92927.03 | 17.20 | 13.09 | 0.187022E+10 | 2745.29 | 17.20 | 13.09 | ||
Maximum of Months | 0.977900E+12 | 367794.18 | 32.20 | 26.46 | 0.223475E+10 | 2745.29 | 32.77 | 26.07 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104315E+09 | 9242.82 | 01-JAN-10:55 | 26.70 |
February | 0.159107E+09 | 11859.07 | 11-FEB-16:03 | 27.70 |
March | 0.185622E+09 | 11621.34 | 04-MAR-16:03 | 27.52 |
April | 0.303142E+09 | 17278.05 | 15-APR-16:02 | 31.70 |
May | 0.482468E+09 | 17655.17 | 29-MAY-14:54 | 32.80 |
June | 0.416624E+09 | 17548.56 | 10-JUN-15:02 | 31.70 |
July | 0.618692E+09 | 22331.19 | 29-JUL-16:02 | 35.40 |
August | 0.536815E+09 | 17408.99 | 19-AUG-15:02 | 31.70 |
September | 0.638998E+09 | 16615.38 | 30-SEP-15:02 | 31.10 |
October | 0.527867E+09 | 16101.13 | 14-OCT-15:02 | 30.78 |
November | 0.299439E+09 | 10928.51 | 18-NOV-16:03 | 27.12 |
December | 0.175140E+09 | 11723.65 | 10-DEC-15:34 | 28.50 |
Annual Sum or Average | 0.444823E+10 | |||
Minimum of Months | 0.104315E+09 | 9242.82 | 26.70 | |
Maximum of Months | 0.638998E+09 | 22331.19 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20364042.25 | 10905.65 | 25-JAN-06:02 | 9.40 |
February | 38022513.53 | 10872.50 | 04-FEB-06:03 | 5.50 |
March | 9003822.32 | 10713.08 | 16-MAR-05:02 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 19481007.64 | 10754.06 | 21-DEC-06:03 | 11.20 |
Annual Sum or Average | 86871385.74 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 38022513.53 | 10905.65 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3956855.53 | 4967.15 | 25-JAN-06:02 | 9.40 |
February | 12510367.56 | 8637.77 | 04-FEB-06:03 | 5.50 |
March | 875924.97 | 996.07 | 16-MAR-05:02 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 4596488.57 | 4774.61 | 21-DEC-06:03 | 11.20 |
Annual Sum or Average | 21939636.63 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 12510367.56 | 8637.77 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 10494413.93 | 10840.36 | 04-FEB-06:03 | 5.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 10494413.93 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 10494413.93 | 10840.36 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27751.07 | 182.84 | 25-JAN-06:04 | 9.40 |
February | 10433983.79 | 8251.05 | 04-FEB-06:03 | 5.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 8927.69 | 59.52 | 21-DEC-06:08 | 11.20 |
Annual Sum or Average | 10470662.55 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 10433983.79 | 8251.05 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55180720.45 | 8256.53 | 30-JAN-04:02 | 21.60 |
February | 67220973.53 | 8093.39 | 13-FEB-04:02 | 20.50 |
March | 83179732.28 | 7750.29 | 20-MAR-03:02 | 12.70 |
April | 58377468.22 | 4152.20 | 16-APR-15:02 | 31.52 |
May | 48765137.81 | 5921.11 | 25-MAY-03:02 | 24.72 |
June | 38492709.83 | 4744.92 | 19-JUN-03:02 | 24.40 |
July | 34045685.20 | 4302.27 | 09-JUL-16:21 | 30.55 |
August | 37526508.68 | 4089.37 | 20-AUG-11:02 | 31.78 |
September | 44786641.80 | 5655.23 | 27-SEP-03:02 | 23.90 |
October | 62803039.52 | 5755.61 | 14-OCT-03:02 | 22.88 |
November | 87056177.67 | 7111.58 | 14-NOV-04:02 | 20.63 |
December | 0.114079E+09 | 9464.44 | 22-DEC-04:02 | 18.80 |
Annual Sum or Average | 0.731514E+09 | |||
Minimum of Months | 34045685.20 | 4089.37 | 12.70 | |
Maximum of Months | 0.114079E+09 | 9464.44 | 31.78 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32763735.26 | 5154.10 | 30-JAN-04:02 | 21.60 |
February | 31819118.00 | 5130.98 | 13-FEB-04:02 | 20.50 |
March | 26349714.74 | 4780.94 | 20-MAR-04:03 | 12.20 |
April | 26503465.28 | 4168.85 | 13-APR-03:02 | 24.90 |
May | 25458666.22 | 4803.79 | 08-MAY-03:02 | 23.30 |
June | 24771421.28 | 5730.96 | 08-JUN-03:02 | 28.90 |
July | 26250655.90 | 5349.26 | 03-JUL-03:02 | 25.50 |
August | 24182652.55 | 5749.11 | 28-AUG-03:02 | 25.68 |
September | 24793293.69 | 5398.52 | 19-SEP-03:02 | 27.20 |
October | 31913236.43 | 5086.85 | 02-OCT-03:02 | 26.70 |
November | 29375123.96 | 4938.08 | 13-NOV-04:02 | 12.80 |
December | 32531542.78 | 5197.83 | 18-DEC-06:02 | 17.30 |
Annual Sum or Average | 0.336713E+09 | |||
Minimum of Months | 24182652.55 | 4168.85 | 12.20 | |
Maximum of Months | 32763735.26 | 5749.11 | 28.90 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.619033E+09 | 10475.21 | 02-JAN-05:03 | 18.48 |
February | 0.376334E+09 | 14691.33 | 22-FEB-06:02 | 11.70 |
March | 0.394734E+09 | 15056.82 | 20-MAR-05:03 | 11.93 |
April | 86834551.79 | 13080.10 | 19-APR-05:03 | 15.10 |
May | 46518279.50 | 8617.07 | 22-MAY-03:02 | 23.22 |
June | 30866858.37 | 8267.21 | 05-JUN-03:02 | 25.60 |
July | 38370427.52 | 9008.24 | 24-JUL-03:02 | 24.40 |
August | 31279027.13 | 7125.96 | 31-AUG-03:02 | 25.68 |
September | 38355400.21 | 9272.80 | 05-SEP-03:02 | 23.30 |
October | 50683874.68 | 9485.49 | 16-OCT-03:02 | 21.70 |
November | 0.144001E+09 | 12324.25 | 07-NOV-06:02 | 20.10 |
December | 0.491062E+09 | 14182.55 | 04-DEC-06:02 | 17.20 |
Annual Sum or Average | 0.234807E+10 | |||
Minimum of Months | 30866858.37 | 7125.96 | 11.70 | |
Maximum of Months | 0.619033E+09 | 15056.82 | 25.68 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.113123E+11 | 11837.83 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.102611E+11 | 11837.83 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.121930E+11 | 11837.83 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.108909E+11 | 11837.83 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.117527E+11 | 11837.83 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.116958E+11 | 11837.83 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.109477E+11 | 11837.83 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.121930E+11 | 11837.83 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.108909E+11 | 11837.83 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.113123E+11 | 11837.83 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.111797E+11 | 11837.83 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.109477E+11 | 11837.83 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.135577E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.102611E+11 | 11837.83 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.121930E+11 | 11837.83 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.101592E+11 | 10631.20 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.921518E+10 | 10631.20 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.109502E+11 | 10631.20 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.978077E+10 | 10631.20 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.105547E+11 | 10631.20 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.105037E+11 | 10631.20 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.983180E+10 | 10631.20 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.109502E+11 | 10631.20 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.978077E+10 | 10631.20 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.101592E+11 | 10631.20 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.100402E+11 | 10631.20 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.983180E+10 | 10631.20 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.121758E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.921518E+10 | 10631.20 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.109502E+11 | 10631.20 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.818066E+09 | 1162.33 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.702225E+09 | 1013.35 | 07-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.797685E+09 | 1071.71 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.691362E+09 | 1003.04 | 12-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.727664E+09 | 824.33 | 25-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.724469E+09 | 1155.05 | 15-JUN-07:30 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.674562E+09 | 739.48 | 05-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.761900E+09 | 1002.35 | 28-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.706491E+09 | 1334.85 | 27-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.762827E+09 | 1168.72 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.785499E+09 | 1133.39 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.799615E+09 | 1264.38 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.895237E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.674562E+09 | 739.48 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.818066E+09 | 1334.85 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.509977E+09 | 756.16 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.445895E+09 | 661.37 | 13-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.505217E+09 | 563.59 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.446817E+09 | 584.73 | 12-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.473609E+09 | 527.18 | 25-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.471729E+09 | 731.79 | 15-JUN-07:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.439319E+09 | 469.10 | 05-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.492261E+09 | 590.26 | 28-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.454467E+09 | 860.23 | 27-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.480914E+09 | 725.52 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.497187E+09 | 744.68 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.503920E+09 | 815.69 | 15-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.572131E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.439319E+09 | 469.10 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.509977E+09 | 860.23 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.755855E+09 | 1124.61 | 04-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.672314E+09 | 888.92 | 08-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.780625E+09 | 1020.69 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.693021E+09 | 1011.89 | 12-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.738408E+09 | 878.56 | 25-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.739488E+09 | 1176.19 | 15-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.684844E+09 | 868.75 | 05-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.766193E+09 | 1024.61 | 28-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.701679E+09 | 1334.88 | 27-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.736639E+09 | 1145.67 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.744731E+09 | 1064.59 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.748769E+09 | 1259.95 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.876257E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.672314E+09 | 868.75 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.780625E+09 | 1334.88 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.505614E+09 | 711.82 | 04-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.441941E+09 | 660.82 | 07-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.513076E+09 | 711.50 | 15-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.447333E+09 | 687.14 | 12-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.476269E+09 | 613.12 | 25-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.475879E+09 | 770.49 | 15-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.442074E+09 | 607.72 | 05-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.497677E+09 | 689.99 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.457282E+09 | 860.23 | 27-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.488353E+09 | 760.93 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.490494E+09 | 707.27 | 24-NOV-08:09 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.492418E+09 | 810.39 | 15-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.572841E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.441941E+09 | 607.72 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.513076E+09 | 860.23 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.817909E+09 | 1165.94 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.701542E+09 | 1016.56 | 07-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.797418E+09 | 1076.18 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.691176E+09 | 1010.12 | 12-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.727378E+09 | 835.16 | 25-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.723397E+09 | 1158.84 | 15-JUN-07:30 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.674443E+09 | 737.65 | 05-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.761916E+09 | 1009.49 | 28-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.706247E+09 | 1334.85 | 27-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.762614E+09 | 1172.22 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.785043E+09 | 1137.64 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.799061E+09 | 1265.88 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.894814E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.674443E+09 | 737.65 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.817909E+09 | 1334.85 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.509667E+09 | 756.40 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.445656E+09 | 661.69 | 13-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.504973E+09 | 565.01 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.446664E+09 | 588.30 | 12-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.473328E+09 | 526.32 | 25-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.471351E+09 | 732.28 | 15-JUN-07:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.439043E+09 | 467.08 | 05-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.492092E+09 | 593.39 | 28-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.454281E+09 | 860.23 | 27-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.480911E+09 | 726.56 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.497035E+09 | 745.01 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.503737E+09 | 815.79 | 15-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.571874E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.439043E+09 | 467.08 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.509667E+09 | 860.23 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.755912E+09 | 1129.67 | 04-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.672342E+09 | 899.28 | 08-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.780826E+09 | 1024.89 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.693047E+09 | 1018.67 | 12-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.738408E+09 | 887.74 | 25-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.739480E+09 | 1179.35 | 15-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.684807E+09 | 878.02 | 05-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.766341E+09 | 1031.03 | 28-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.701793E+09 | 1334.88 | 27-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.735624E+09 | 1150.03 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.744619E+09 | 1071.63 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.749293E+09 | 1261.63 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.876249E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.672342E+09 | 878.02 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.780826E+09 | 1334.88 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.504906E+09 | 713.08 | 04-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.441652E+09 | 661.16 | 07-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.512687E+09 | 713.18 | 15-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.447279E+09 | 687.45 | 12-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.475964E+09 | 613.54 | 25-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.475461E+09 | 770.64 | 15-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.441853E+09 | 608.16 | 05-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.497501E+09 | 690.30 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.457113E+09 | 860.23 | 27-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.488137E+09 | 761.15 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.490241E+09 | 707.59 | 24-NOV-08:09 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.492179E+09 | 810.61 | 15-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.572497E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.441652E+09 | 608.16 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.512687E+09 | 860.23 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.817870E+09 | 1165.76 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.701500E+09 | 1016.75 | 07-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.797394E+09 | 1076.35 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.691138E+09 | 1009.83 | 12-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.727347E+09 | 834.73 | 25-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.723348E+09 | 1158.63 | 15-JUN-07:30 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.674430E+09 | 737.51 | 05-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.761893E+09 | 1009.19 | 28-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.706215E+09 | 1334.85 | 27-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.762591E+09 | 1172.05 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.785011E+09 | 1137.48 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.799071E+09 | 1265.79 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.894781E+10 | 0.363654E+11 | ||||
Minimum of Months | 0.674430E+09 | 737.51 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.817870E+09 | 1334.85 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.509631E+09 | 756.30 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.445652E+09 | 661.53 | 13-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.504972E+09 | 565.17 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.446679E+09 | 588.16 | 12-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.473319E+09 | 526.16 | 25-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.471337E+09 | 732.16 | 15-JUN-07:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.439028E+09 | 467.01 | 05-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.492078E+09 | 593.25 | 28-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.454267E+09 | 860.23 | 27-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.480897E+09 | 726.48 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.496980E+09 | 744.91 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.503732E+09 | 815.73 | 15-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.571857E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.439028E+09 | 467.01 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.509631E+09 | 860.23 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.755904E+09 | 1129.50 | 04-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.672318E+09 | 898.96 | 08-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.780822E+09 | 1025.09 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.693079E+09 | 1018.38 | 12-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.738388E+09 | 887.32 | 25-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.739451E+09 | 1179.20 | 15-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.684760E+09 | 877.61 | 05-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.766316E+09 | 1030.74 | 28-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.701766E+09 | 1334.88 | 27-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.735627E+09 | 1149.86 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.744595E+09 | 1071.47 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.749268E+09 | 1261.55 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.876229E+10 | 0.363660E+11 | ||||
Minimum of Months | 0.672318E+09 | 877.61 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.780822E+09 | 1334.88 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.504908E+09 | 712.99 | 04-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.441640E+09 | 661.32 | 07-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.512724E+09 | 713.33 | 15-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.447295E+09 | 687.27 | 12-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.475955E+09 | 613.30 | 25-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.475441E+09 | 770.55 | 15-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.441835E+09 | 607.92 | 05-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.497476E+09 | 690.12 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.457090E+09 | 860.23 | 27-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.488129E+09 | 761.04 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.490266E+09 | 707.42 | 24-NOV-08:09 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.492156E+09 | 810.56 | 15-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.572492E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.441640E+09 | 607.92 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.512724E+09 | 860.23 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272315E+09 | 284.97 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.247010E+09 | 284.97 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.293517E+09 | 284.97 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.262171E+09 | 284.97 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.282916E+09 | 284.97 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.281548E+09 | 284.97 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.263538E+09 | 284.97 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.293517E+09 | 284.97 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.262171E+09 | 284.97 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.272315E+09 | 284.97 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.269124E+09 | 284.97 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.263538E+09 | 284.97 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.326368E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.247010E+09 | 284.97 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.293517E+09 | 284.97 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.318958E+10 | 3337.76 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.289319E+10 | 3337.76 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.343791E+10 | 3337.76 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.307076E+10 | 3337.76 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.331375E+10 | 3337.76 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.329773E+10 | 3337.76 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.308678E+10 | 3337.76 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.343791E+10 | 3337.76 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.307076E+10 | 3337.76 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.318958E+10 | 3337.76 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.315220E+10 | 3337.76 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.308678E+10 | 3337.76 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.382269E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.289319E+10 | 3337.76 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.343791E+10 | 3337.76 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.113123E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.102611E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.108909E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.117527E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.116958E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.109477E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.108909E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.113123E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.111797E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.109477E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.135577E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.102611E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.121930E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.101592E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.978077E+10 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.105547E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.105037E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.983180E+10 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.978077E+10 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.101592E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.100402E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.983180E+10 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.121758E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.921518E+10 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.109502E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.818066E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1465196.11 | 45086647.96 |
February | 0.136985E+10 | 0.702225E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2883851.42 | 60549870.59 |
March | 0.163685E+10 | 0.797685E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3418192.14 | 49344572.33 |
April | 0.145243E+10 | 0.691362E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7746617.00 | 17758197.85 |
May | 0.157338E+10 | 0.727664E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19597270.22 | 7247508.44 |
June | 0.156900E+10 | 0.724469E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24833906.69 | 1264625.61 |
July | 0.145680E+10 | 0.674562E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22488616.38 | 1257675.36 |
August | 0.163685E+10 | 0.761900E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26982330.27 | 740560.83 |
September | 0.145243E+10 | 0.706491E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24640072.43 | 2128310.61 |
October | 0.150991E+10 | 0.762827E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16522937.39 | 3836108.79 |
November | 0.149516E+10 | 0.785499E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7604809.07 | 35126360.90 |
December | 0.145680E+10 | 0.799615E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2265676.42 | 43655790.70 |
Annual Sum or Average | 0.181194E+11 | 0.895237E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160449E+09 | 0.267996E+09 |
Minimum of Months | 0.136985E+10 | 0.674562E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1465196.11 | 740560.83 |
Maximum of Months | 0.163685E+10 | 0.818066E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26982330.27 | 60549870.59 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.509977E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 819401.63 | 30745493.77 |
February | 0.882782E+09 | 0.445895E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1855816.98 | 40334412.44 |
March | 0.105485E+10 | 0.505217E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2285122.75 | 31700275.49 |
April | 0.936002E+09 | 0.446817E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4855209.85 | 10701549.15 |
May | 0.101394E+10 | 0.473609E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12978461.37 | 4718305.89 |
June | 0.101113E+10 | 0.471729E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17069200.38 | 693585.49 |
July | 0.938820E+09 | 0.439319E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15217908.97 | 713261.94 |
August | 0.105485E+10 | 0.492261E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18782866.19 | 359298.36 |
September | 0.936002E+09 | 0.454467E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15949085.13 | 1426826.77 |
October | 0.973041E+09 | 0.480914E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10909788.08 | 2290920.86 |
November | 0.963541E+09 | 0.497187E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5444651.57 | 22961963.70 |
December | 0.938820E+09 | 0.503920E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1589905.79 | 27361375.87 |
Annual Sum or Average | 0.116768E+11 | 0.572131E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107757E+09 | 0.174007E+09 |
Minimum of Months | 0.882782E+09 | 0.439319E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 819401.63 | 359298.36 |
Maximum of Months | 0.105485E+10 | 0.509977E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18782866.19 | 40334412.44 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.755855E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1041179.57 | 49952017.06 |
February | 0.136988E+10 | 0.672314E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2338565.84 | 66436815.96 |
March | 0.163688E+10 | 0.780625E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3017195.23 | 53213581.46 |
April | 0.145246E+10 | 0.693021E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6740863.87 | 19029281.31 |
May | 0.157341E+10 | 0.738408E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19636402.18 | 7178546.57 |
June | 0.156904E+10 | 0.739488E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25238977.09 | 1274969.43 |
July | 0.145684E+10 | 0.684844E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22712153.15 | 1235278.65 |
August | 0.163688E+10 | 0.766193E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26551733.56 | 777072.47 |
September | 0.145246E+10 | 0.701679E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22652926.06 | 2453253.29 |
October | 0.150994E+10 | 0.736639E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13593604.12 | 5338733.09 |
November | 0.149520E+10 | 0.744731E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5893034.41 | 39929881.68 |
December | 0.145684E+10 | 0.748769E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1504255.14 | 47801709.95 |
Annual Sum or Average | 0.181198E+11 | 0.876257E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150921E+09 | 0.294621E+09 |
Minimum of Months | 0.136988E+10 | 0.672314E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1041179.57 | 777072.47 |
Maximum of Months | 0.163688E+10 | 0.780625E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26551733.56 | 66436815.96 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.505614E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 807503.72 | 34227878.46 |
February | 0.882782E+09 | 0.441941E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1614418.51 | 49662844.08 |
March | 0.105485E+10 | 0.513076E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1948090.72 | 43891294.43 |
April | 0.936002E+09 | 0.447333E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4042656.00 | 20337058.26 |
May | 0.101394E+10 | 0.476269E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11599447.12 | 8109097.49 |
June | 0.101113E+10 | 0.475879E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14122710.48 | 1857075.03 |
July | 0.938820E+09 | 0.442074E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12908396.18 | 1872473.87 |
August | 0.105485E+10 | 0.497677E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14581530.97 | 1249308.48 |
September | 0.936002E+09 | 0.457282E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14351173.05 | 2239594.11 |
October | 0.973041E+09 | 0.488353E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8814402.41 | 5130304.16 |
November | 0.963541E+09 | 0.490494E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3681202.41 | 30573136.40 |
December | 0.938820E+09 | 0.492418E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1072824.61 | 37264795.83 |
Annual Sum or Average | 0.116768E+11 | 0.572841E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89544356.19 | 0.236415E+09 |
Minimum of Months | 0.882782E+09 | 0.441941E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 807503.72 | 1249308.48 |
Maximum of Months | 0.105485E+10 | 0.513076E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14581530.97 | 49662844.08 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.817909E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4281477.80 | 93473921.81 |
February | 0.136985E+10 | 0.701542E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7412743.90 | 0.126511E+09 |
March | 0.163685E+10 | 0.797418E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7847823.05 | 0.114313E+09 |
April | 0.145243E+10 | 0.691176E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18433682.94 | 49360637.26 |
May | 0.157338E+10 | 0.727378E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43258041.80 | 19823534.72 |
June | 0.156900E+10 | 0.723397E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51915956.93 | 5688571.43 |
July | 0.145680E+10 | 0.674443E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49628288.58 | 5271034.21 |
August | 0.163685E+10 | 0.761916E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58998214.46 | 2752920.21 |
September | 0.145243E+10 | 0.706247E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55119642.14 | 5890544.35 |
October | 0.150991E+10 | 0.762614E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35907115.40 | 12139799.02 |
November | 0.149516E+10 | 0.785043E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16102276.70 | 77563886.34 |
December | 0.145680E+10 | 0.799061E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5929499.65 | 94459730.93 |
Annual Sum or Average | 0.181194E+11 | 0.894814E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354835E+09 | 0.607249E+09 |
Minimum of Months | 0.136985E+10 | 0.674443E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4281477.80 | 2752920.21 |
Maximum of Months | 0.163685E+10 | 0.817909E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58998214.46 | 0.126511E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.509667E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1871385.13 | 67860655.76 |
February | 0.649041E+09 | 0.445656E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4179267.32 | 91218061.21 |
March | 0.773965E+09 | 0.504973E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4725496.80 | 82527709.76 |
April | 0.688021E+09 | 0.446664E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9997959.30 | 36960848.57 |
May | 0.744847E+09 | 0.473328E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27521183.36 | 14887119.86 |
June | 0.742030E+09 | 0.471351E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33576168.59 | 4261021.74 |
July | 0.690839E+09 | 0.439043E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31399774.71 | 4124393.79 |
August | 0.773965E+09 | 0.492092E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37451959.15 | 2042639.72 |
September | 0.688021E+09 | 0.454281E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34094255.33 | 4510507.04 |
October | 0.715730E+09 | 0.480911E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21541015.63 | 9481361.20 |
November | 0.708685E+09 | 0.497035E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9818190.53 | 56674175.88 |
December | 0.690839E+09 | 0.503737E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3389802.70 | 66063316.87 |
Annual Sum or Average | 0.858171E+10 | 0.571874E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219566E+09 | 0.440612E+09 |
Minimum of Months | 0.649041E+09 | 0.439043E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1871385.13 | 2042639.72 |
Maximum of Months | 0.773965E+09 | 0.509667E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37451959.15 | 91218061.21 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.755912E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2095212.57 | 0.115626E+09 |
February | 0.136988E+10 | 0.672342E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4897161.05 | 0.153567E+09 |
March | 0.163688E+10 | 0.780826E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6501417.59 | 0.131291E+09 |
April | 0.145246E+10 | 0.693047E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15497915.95 | 54503632.26 |
May | 0.157341E+10 | 0.738408E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43612844.75 | 19673498.36 |
June | 0.156904E+10 | 0.739480E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53400913.01 | 5412722.80 |
July | 0.145684E+10 | 0.684807E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50605252.92 | 5019123.56 |
August | 0.163688E+10 | 0.766341E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57423094.15 | 2898637.72 |
September | 0.145246E+10 | 0.701793E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49409913.38 | 7044363.19 |
October | 0.150994E+10 | 0.735624E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28286932.24 | 18135150.99 |
November | 0.149520E+10 | 0.744619E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11617171.64 | 98612647.34 |
December | 0.145684E+10 | 0.749293E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3116883.51 | 0.115767E+09 |
Annual Sum or Average | 0.181198E+11 | 0.876249E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326465E+09 | 0.727550E+09 |
Minimum of Months | 0.136988E+10 | 0.672342E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2095212.57 | 2898637.72 |
Maximum of Months | 0.163688E+10 | 0.780826E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57423094.15 | 0.153567E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.504906E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2244640.24 | 69161907.21 |
February | 0.882782E+09 | 0.441652E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3690916.41 | 97637399.86 |
March | 0.105485E+10 | 0.512687E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4483883.75 | 92430284.54 |
April | 0.936002E+09 | 0.447279E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9856890.53 | 45441233.79 |
May | 0.101394E+10 | 0.475964E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26216962.16 | 19615049.12 |
June | 0.101113E+10 | 0.475461E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31259327.04 | 5349047.57 |
July | 0.938820E+09 | 0.441853E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30081537.18 | 5290017.48 |
August | 0.105485E+10 | 0.497501E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34192987.89 | 2851436.54 |
September | 0.936002E+09 | 0.457113E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32106809.06 | 5361428.40 |
October | 0.973041E+09 | 0.488137E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20195306.71 | 12390584.32 |
November | 0.963541E+09 | 0.490241E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9019519.06 | 59625583.38 |
December | 0.938820E+09 | 0.492179E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2879068.11 | 73173125.05 |
Annual Sum or Average | 0.116768E+11 | 0.572497E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206228E+09 | 0.488327E+09 |
Minimum of Months | 0.882782E+09 | 0.441652E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2244640.24 | 2851436.54 |
Maximum of Months | 0.105485E+10 | 0.512687E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34192987.89 | 97637399.86 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.817870E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5345032.95 | 0.105651E+09 |
February | 0.136985E+10 | 0.701500E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8426618.93 | 0.146525E+09 |
March | 0.163685E+10 | 0.797394E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8495882.26 | 0.137294E+09 |
April | 0.145243E+10 | 0.691138E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19996442.56 | 62854580.30 |
May | 0.157338E+10 | 0.727347E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49335442.40 | 27808805.02 |
June | 0.156900E+10 | 0.723348E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60239565.64 | 8099038.99 |
July | 0.145680E+10 | 0.674430E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57080460.51 | 7766547.81 |
August | 0.163685E+10 | 0.761893E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68676491.28 | 3955220.57 |
September | 0.145243E+10 | 0.706215E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63235533.00 | 7984803.32 |
October | 0.150991E+10 | 0.762591E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40704602.18 | 15909836.09 |
November | 0.149516E+10 | 0.785011E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18200758.79 | 89653919.31 |
December | 0.145680E+10 | 0.799071E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6679509.78 | 0.107821E+09 |
Annual Sum or Average | 0.181194E+11 | 0.894781E+10 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406416E+09 | 0.721324E+09 |
Minimum of Months | 0.136985E+10 | 0.674430E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5345032.95 | 3955220.57 |
Maximum of Months | 0.163685E+10 | 0.817870E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68676491.28 | 0.146525E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.509631E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2117064.38 | 78597701.83 |
February | 0.882782E+09 | 0.445652E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4625881.10 | 0.107358E+09 |
March | 0.105485E+10 | 0.504972E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5222115.17 | 0.100862E+09 |
April | 0.936002E+09 | 0.446679E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11294351.16 | 47316006.93 |
May | 0.101394E+10 | 0.473319E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31921749.38 | 20581301.29 |
June | 0.101113E+10 | 0.471337E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39529719.69 | 5916485.75 |
July | 0.938820E+09 | 0.439028E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36834913.27 | 5816870.52 |
August | 0.105485E+10 | 0.492078E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44161988.66 | 2863647.70 |
September | 0.936002E+09 | 0.454267E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40057286.99 | 6068347.48 |
October | 0.973041E+09 | 0.480897E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24795707.34 | 12484603.62 |
November | 0.963541E+09 | 0.496980E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11054405.12 | 66709479.57 |
December | 0.938820E+09 | 0.503732E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3781567.10 | 76645106.82 |
Annual Sum or Average | 0.116768E+11 | 0.571857E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255397E+09 | 0.531219E+09 |
Minimum of Months | 0.882782E+09 | 0.439028E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2117064.38 | 2863647.70 |
Maximum of Months | 0.105485E+10 | 0.509631E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44161988.66 | 0.107358E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.755904E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2593517.29 | 0.135902E+09 |
February | 0.136988E+10 | 0.672318E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5904544.93 | 0.182944E+09 |
March | 0.163688E+10 | 0.780822E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7350883.80 | 0.160373E+09 |
April | 0.145246E+10 | 0.693079E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17401275.61 | 69846845.16 |
May | 0.157341E+10 | 0.738388E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49806044.67 | 27491622.92 |
June | 0.156904E+10 | 0.739451E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61897495.88 | 7725174.16 |
July | 0.145684E+10 | 0.684760E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58067946.51 | 7397686.22 |
August | 0.163688E+10 | 0.766316E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67188663.90 | 4138267.91 |
September | 0.145246E+10 | 0.701766E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58016344.93 | 9457128.07 |
October | 0.150994E+10 | 0.735627E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33608287.70 | 23960390.31 |
November | 0.149520E+10 | 0.744595E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13900898.46 | 0.118085E+09 |
December | 0.145684E+10 | 0.749268E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3714728.00 | 0.136964E+09 |
Annual Sum or Average | 0.181198E+11 | 0.876229E+10 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379451E+09 | 0.884286E+09 |
Minimum of Months | 0.136988E+10 | 0.672318E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2593517.29 | 4138267.91 |
Maximum of Months | 0.163688E+10 | 0.780822E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67188663.90 | 0.182944E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.504908E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2768695.11 | 80055077.53 |
February | 0.882782E+09 | 0.441640E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4289292.11 | 0.115763E+09 |
March | 0.105485E+10 | 0.512724E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5140338.41 | 0.112403E+09 |
April | 0.936002E+09 | 0.447295E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11533803.57 | 56979928.75 |
May | 0.101394E+10 | 0.475955E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31240682.65 | 25999223.93 |
June | 0.101113E+10 | 0.475441E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37581866.76 | 6951902.67 |
July | 0.938820E+09 | 0.441835E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36179660.95 | 7014555.19 |
August | 0.105485E+10 | 0.497476E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41236310.95 | 3844043.12 |
September | 0.936002E+09 | 0.457090E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38616713.16 | 6897233.47 |
October | 0.973041E+09 | 0.488129E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24137493.82 | 15812626.58 |
November | 0.963541E+09 | 0.490266E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10590323.00 | 70360740.72 |
December | 0.938820E+09 | 0.492156E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3477118.31 | 85349085.89 |
Annual Sum or Average | 0.116768E+11 | 0.572492E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246792E+09 | 0.587431E+09 |
Minimum of Months | 0.882782E+09 | 0.441640E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2768695.11 | 3844043.12 |
Maximum of Months | 0.105485E+10 | 0.512724E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41236310.95 | 0.115763E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.272315E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.247010E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.293517E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.262171E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.282916E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.281548E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.263538E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.293517E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.262171E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.272315E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.269124E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.263538E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.326368E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.247010E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.293517E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.318958E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.289319E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.343791E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.307076E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.331375E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.329773E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.308678E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.343791E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.307076E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.318958E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.315220E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.308678E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.382269E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.289319E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.343791E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1654248.76 | 99469136.80 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3340790.06 | 0.133099E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4721924.51 | 0.113319E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12186830.72 | 45044519.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34080341.69 | 14470286.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45259776.28 | 2835063.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41842674.98 | 3198775.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48511453.29 | 2170216.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44973865.42 | 4789468.38 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27078192.12 | 10138746.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10442965.77 | 79461982.79 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3255698.70 | 98963447.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277349E+09 | 0.606960E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1654248.76 | 2170216.45 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48511453.29 | 0.133099E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3705012.29 | 0.169986E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6744834.80 | 0.225819E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8735686.78 | 0.197920E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22882267.96 | 80855219.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62215757.54 | 25591349.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80409827.79 | 5820868.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76510582.18 | 6078709.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88448935.03 | 4020308.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81778401.84 | 8533408.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48879878.50 | 18927227.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19182755.19 | 0.137079E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6762727.64 | 0.168305E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506257E+09 | 0.104894E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3705012.29 | 4020308.53 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88448935.03 | 0.225819E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1995182.20 | 0.171760E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2728075.52 | 0.233702E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3183382.86 | 0.216755E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12361190.04 | 97472928.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49744044.71 | 33454142.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74320069.21 | 9570451.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65825627.68 | 9496485.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84371485.45 | 5766440.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73131254.38 | 10026458.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40884398.84 | 19758001.20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14651474.69 | 0.141262E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3242300.07 | 0.175015E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426438E+09 | 0.112404E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1995182.20 | 5766440.41 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84371485.45 | 0.233702E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 11837.83 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 11837.83 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 11837.83 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 11837.83 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 11837.83 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 11837.83 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 11837.83 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 11837.83 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 11837.83 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 11837.83 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 11837.83 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 11837.83 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 11837.83 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 11837.83 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 10631.20 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 10631.20 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 10631.20 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 10631.20 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 10631.20 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 10631.20 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 10631.20 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 10631.20 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 10631.20 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 10631.20 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 10631.20 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 10631.20 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 10631.20 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1162.33 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.80 | 15-JAN-13:53 | 126.39 | 24-JAN-03:00 |
February | 2010.79 | 01-FEB-10:09 | 1013.35 | 07-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.49 | 20-FEB-15:00 | 216.00 | 04-FEB-05:00 |
March | 2010.79 | 01-MAR-10:09 | 1071.71 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.04 | 05-MAR-13:50 | 209.92 | 16-MAR-02:00 |
April | 2010.79 | 03-APR-09:09 | 1003.04 | 12-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.94 | 15-APR-17:02 | 65.20 | 18-APR-23:53 |
May | 2010.79 | 01-MAY-09:09 | 824.33 | 25-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.58 | 29-MAY-15:50 | 37.34 | 08-MAY-00:20 |
June | 2010.79 | 01-JUN-09:09 | 1155.05 | 15-JUN-07:30 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.86 | 17-JUN-17:30 | 32.52 | 18-JUN-20:07 |
July | 2010.79 | 03-JUL-09:09 | 739.48 | 05-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.44 | 30-JUL-15:50 | 28.45 | 02-JUL-15:40 |
August | 2010.79 | 01-AUG-09:09 | 1002.35 | 28-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.62 | 13-AUG-13:00 | 43.76 | 14-AUG-03:10 |
September | 2010.79 | 01-SEP-09:09 | 1334.85 | 27-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.31 | 17-SEP-13:50 | 20.25 | 19-SEP-23:10 |
October | 2010.79 | 02-OCT-09:09 | 1168.72 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.60 | 29-OCT-13:42 | 33.11 | 16-OCT-02:30 |
November | 2010.79 | 01-NOV-09:09 | 1133.39 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.14 | 22-NOV-22:03 | 191.31 | 11-NOV-08:33 |
December | 2010.79 | 01-DEC-10:09 | 1264.38 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.53 | 10-DEC-15:00 | 198.99 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 739.48 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 20.49 | 20.25 | |||||
Maximum of Months | 2010.79 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 97.58 | 216.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 756.16 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 | 29-JAN-12:40 | 84.09 | 24-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 661.37 | 13-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 | 19-FEB-16:00 | 142.09 | 04-FEB-05:00 |
March | 1295.83 | 01-MAR-10:09 | 563.59 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.98 | 05-MAR-14:17 | 139.80 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 584.73 | 12-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.10 | 15-APR-17:02 | 42.61 | 18-APR-23:53 |
May | 1295.83 | 01-MAY-09:09 | 527.18 | 25-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.89 | 29-MAY-15:47 | 26.78 | 07-MAY-19:15 |
June | 1295.83 | 01-JUN-09:09 | 731.79 | 15-JUN-07:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.94 | 17-JUN-17:30 | 18.98 | 18-JUN-20:07 |
July | 1295.83 | 03-JUL-09:09 | 469.10 | 05-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 30-JUL-15:50 | 20.34 | 02-JUL-15:40 |
August | 1295.83 | 01-AUG-09:09 | 590.26 | 28-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.81 | 13-AUG-13:00 | 25.89 | 14-AUG-03:10 |
September | 1295.83 | 01-SEP-09:09 | 860.23 | 27-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.37 | 17-SEP-16:30 | 13.51 | 19-SEP-23:10 |
October | 1295.83 | 02-OCT-09:09 | 725.52 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.23 | 29-OCT-14:10 | 21.28 | 16-OCT-02:30 |
November | 1295.83 | 01-NOV-09:09 | 744.68 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.43 | 05-NOV-16:53 | 139.48 | 11-NOV-09:10 |
December | 1295.83 | 01-DEC-10:09 | 815.69 | 15-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.32 | 10-DEC-15:00 | 129.74 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 469.10 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 | 13.51 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 68.89 | 142.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1124.61 | 04-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 07-JAN-13:00 | 131.88 | 24-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 888.92 | 08-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.64 | 02-FEB-14:00 | 217.02 | 04-FEB-05:00 |
March | 2010.83 | 01-MAR-10:09 | 1020.69 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.69 | 05-MAR-14:10 | 215.29 | 16-MAR-02:00 |
April | 2010.83 | 03-APR-09:09 | 1011.89 | 12-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.57 | 15-APR-17:02 | 66.55 | 18-APR-23:53 |
May | 2010.83 | 01-MAY-09:09 | 878.56 | 25-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.35 | 29-MAY-15:50 | 37.61 | 08-MAY-00:20 |
June | 2010.83 | 01-JUN-09:09 | 1176.19 | 15-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 17-JUN-17:30 | 33.99 | 18-JUN-20:07 |
July | 2010.83 | 03-JUL-09:09 | 868.75 | 05-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.59 | 30-JUL-15:50 | 28.70 | 02-JUL-15:40 |
August | 2010.83 | 01-AUG-09:09 | 1024.61 | 28-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.43 | 13-AUG-13:00 | 43.85 | 14-AUG-03:10 |
September | 2010.83 | 01-SEP-09:09 | 1334.88 | 27-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.75 | 17-SEP-13:46 | 23.94 | 19-SEP-23:10 |
October | 2010.83 | 02-OCT-09:09 | 1145.67 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.58 | 29-OCT-13:50 | 38.69 | 16-OCT-02:30 |
November | 2010.83 | 01-NOV-09:09 | 1064.59 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.98 | 29-NOV-22:03 | 209.91 | 11-NOV-09:10 |
December | 2010.83 | 01-DEC-10:09 | 1259.95 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.35 | 10-DEC-14:56 | 204.60 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 868.75 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 23.94 | |||||
Maximum of Months | 2010.83 | 1334.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 97.35 | 217.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 711.82 | 04-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 | 29-JAN-12:00 | 93.47 | 24-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 660.82 | 07-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 | 02-FEB-14:00 | 157.28 | 04-FEB-05:00 |
March | 1295.83 | 01-MAR-10:09 | 711.50 | 15-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.29 | 05-MAR-14:10 | 161.06 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 687.14 | 12-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.24 | 15-APR-17:10 | 55.16 | 18-APR-23:50 |
May | 1295.83 | 01-MAY-09:09 | 613.12 | 25-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.36 | 29-MAY-15:45 | 31.69 | 07-MAY-19:10 |
June | 1295.83 | 01-JUN-09:09 | 770.49 | 15-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.93 | 25-JUN-13:53 | 31.52 | 18-JUN-20:07 |
July | 1295.83 | 03-JUL-09:09 | 607.72 | 05-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.28 | 30-JUL-15:48 | 27.53 | 02-JUL-15:40 |
August | 1295.83 | 01-AUG-09:09 | 689.99 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.69 | 20-AUG-11:48 | 43.96 | 14-AUG-03:10 |
September | 1295.83 | 01-SEP-09:09 | 860.23 | 27-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.21 | 17-SEP-13:46 | 22.10 | 19-SEP-23:10 |
October | 1295.83 | 02-OCT-09:09 | 760.93 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.27 | 29-OCT-12:10 | 29.12 | 16-OCT-02:30 |
November | 1295.83 | 01-NOV-09:09 | 707.27 | 24-NOV-08:09 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 | 23-NOV-12:00 | 145.69 | 11-NOV-08:33 |
December | 1295.83 | 01-DEC-10:09 | 810.39 | 15-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.41 | 10-DEC-14:54 | 152.37 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 607.72 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 | 22.10 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 63.36 | 161.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1165.94 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 80.53 | 15-JAN-13:53 | 268.94 | 24-JAN-03:00 |
February | 2010.79 | 01-FEB-10:09 | 1016.56 | 07-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.56 | 20-FEB-15:10 | 459.28 | 04-FEB-05:00 |
March | 2010.79 | 01-MAR-10:09 | 1076.18 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.15 | 26-MAR-14:50 | 450.08 | 16-MAR-02:00 |
April | 2010.79 | 03-APR-09:09 | 1010.12 | 12-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.33 | 15-APR-17:02 | 147.96 | 18-APR-23:53 |
May | 2010.79 | 01-MAY-09:09 | 835.16 | 25-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.57 | 29-MAY-16:00 | 95.34 | 25-MAY-03:55 |
June | 2010.79 | 01-JUN-09:09 | 1158.84 | 15-JUN-07:30 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.92 | 17-JUN-17:30 | 95.62 | 18-JUN-19:53 |
July | 2010.79 | 03-JUL-09:09 | 737.65 | 05-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.18 | 30-JUL-15:50 | 75.10 | 02-JUL-16:00 |
August | 2010.79 | 01-AUG-09:09 | 1009.49 | 28-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.11 | 13-AUG-13:00 | 106.13 | 14-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 1334.85 | 27-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.92 | 17-SEP-14:00 | 52.25 | 19-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 1172.22 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.00 | 29-OCT-14:00 | 82.26 | 16-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 1137.64 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.34 | 22-NOV-22:03 | 452.89 | 11-NOV-09:00 |
December | 2010.79 | 01-DEC-10:09 | 1265.88 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 128.93 | 10-DEC-14:30 | 427.09 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 737.65 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 62.34 | 52.25 | |||||
Maximum of Months | 2010.79 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 228.57 | 459.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 756.40 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.90 | 29-JAN-12:20 | 184.28 | 24-JAN-03:00 |
February | 1239.33 | 01-FEB-08:09 | 661.69 | 13-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.57 | 19-FEB-15:50 | 309.53 | 04-FEB-05:00 |
March | 1239.33 | 01-MAR-08:09 | 565.01 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.27 | 05-MAR-14:10 | 311.76 | 16-MAR-02:00 |
April | 1239.33 | 03-APR-07:10 | 588.30 | 12-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.41 | 15-APR-17:02 | 103.28 | 18-APR-23:53 |
May | 1239.33 | 01-MAY-07:10 | 526.32 | 25-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.16 | 29-MAY-16:00 | 75.19 | 07-MAY-18:55 |
June | 1239.33 | 01-JUN-07:10 | 732.28 | 15-JUN-07:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.58 | 17-JUN-17:30 | 64.34 | 18-JUN-19:53 |
July | 1239.33 | 03-JUL-07:10 | 467.08 | 05-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.26 | 30-JUL-15:28 | 59.64 | 02-JUL-16:00 |
August | 1239.33 | 01-AUG-07:10 | 593.39 | 28-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.59 | 13-AUG-12:40 | 74.29 | 14-AUG-03:00 |
September | 1239.33 | 01-SEP-07:10 | 860.23 | 27-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.81 | 17-SEP-13:30 | 38.24 | 19-SEP-23:00 |
October | 1239.33 | 02-OCT-07:10 | 726.56 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 29-OCT-14:00 | 57.84 | 16-OCT-03:00 |
November | 1239.33 | 01-NOV-07:10 | 745.01 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.43 | 22-NOV-22:03 | 350.36 | 11-NOV-09:00 |
December | 1239.33 | 01-DEC-08:09 | 815.79 | 15-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.61 | 10-DEC-14:30 | 289.78 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 467.08 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 28.90 | 38.24 | |||||
Maximum of Months | 1239.33 | 860.23 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 156.16 | 350.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1129.67 | 04-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.42 | 07-JAN-13:00 | 298.06 | 24-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 899.28 | 08-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.32 | 02-FEB-14:00 | 484.60 | 04-FEB-05:00 |
March | 2010.83 | 01-MAR-10:09 | 1024.89 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.20 | 05-MAR-14:10 | 482.38 | 16-MAR-02:00 |
April | 2010.83 | 03-APR-09:09 | 1018.67 | 12-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.83 | 15-APR-17:02 | 154.70 | 18-APR-23:53 |
May | 2010.83 | 01-MAY-09:09 | 887.74 | 25-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.10 | 29-MAY-16:00 | 95.68 | 25-MAY-03:55 |
June | 2010.83 | 01-JUN-09:09 | 1179.35 | 15-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.43 | 17-JUN-17:30 | 96.64 | 18-JUN-19:53 |
July | 2010.83 | 03-JUL-09:09 | 878.02 | 05-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.03 | 30-JUL-15:50 | 73.62 | 02-JUL-16:00 |
August | 2010.83 | 01-AUG-09:09 | 1031.03 | 28-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.01 | 13-AUG-13:00 | 109.24 | 14-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 1334.88 | 27-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.96 | 17-SEP-16:38 | 62.06 | 19-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 1150.03 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.44 | 29-OCT-13:56 | 99.35 | 16-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1071.63 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 | 29-NOV-22:03 | 519.14 | 11-NOV-09:00 |
December | 2010.83 | 01-DEC-10:09 | 1261.63 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 69.76 | 10-DEC-14:50 | 460.38 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 878.02 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 33.42 | 62.06 | |||||
Maximum of Months | 2010.83 | 1334.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 229.10 | 519.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 713.08 | 04-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.99 | 15-JAN-12:20 | 192.71 | 24-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 661.16 | 07-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.88 | 02-FEB-14:00 | 317.89 | 04-FEB-05:00 |
March | 1295.83 | 01-MAR-10:09 | 713.18 | 15-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.05 | 05-MAR-14:10 | 325.75 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 687.45 | 12-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.41 | 15-APR-17:07 | 112.59 | 18-APR-23:53 |
May | 1295.83 | 01-MAY-09:09 | 613.54 | 25-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.00 | 29-MAY-15:55 | 78.59 | 07-MAY-18:55 |
June | 1295.83 | 01-JUN-09:09 | 770.64 | 15-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.19 | 11-JUN-12:00 | 76.05 | 18-JUN-19:53 |
July | 1295.83 | 03-JUL-09:09 | 608.16 | 05-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.82 | 30-JUL-15:28 | 59.35 | 04-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 690.30 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.89 | 13-AUG-13:00 | 90.05 | 14-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 860.23 | 27-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.53 | 17-SEP-13:20 | 48.16 | 19-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 761.15 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.60 | 29-OCT-12:00 | 65.62 | 16-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 707.59 | 24-NOV-08:09 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.41 | 19-NOV-12:20 | 314.13 | 11-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 810.61 | 15-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.43 | 10-DEC-13:50 | 298.28 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 608.16 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 26.88 | 48.16 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 148.00 | 325.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1165.76 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.73 | 15-JAN-14:10 | 310.41 | 24-JAN-03:00 |
February | 2010.79 | 01-FEB-10:09 | 1016.75 | 07-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.61 | 20-FEB-14:42 | 528.10 | 04-FEB-05:07 |
March | 2010.79 | 01-MAR-10:09 | 1076.35 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 72.08 | 26-MAR-15:00 | 514.37 | 16-MAR-02:00 |
April | 2010.79 | 03-APR-09:09 | 1009.83 | 12-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.60 | 15-APR-17:02 | 177.17 | 18-APR-23:53 |
May | 2010.79 | 01-MAY-09:09 | 834.73 | 25-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.99 | 29-MAY-15:47 | 120.90 | 25-MAY-03:55 |
June | 2010.79 | 01-JUN-09:09 | 1158.63 | 15-JUN-07:30 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.17 | 25-JUN-14:10 | 114.48 | 18-JUN-20:10 |
July | 2010.79 | 03-JUL-09:09 | 737.51 | 05-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.07 | 30-JUL-15:28 | 105.11 | 02-JUL-16:00 |
August | 2010.79 | 01-AUG-09:09 | 1009.19 | 28-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.79 | 13-AUG-13:00 | 147.30 | 14-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 1334.85 | 27-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.48 | 17-SEP-14:00 | 73.00 | 19-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 1172.05 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.58 | 29-OCT-14:00 | 103.33 | 16-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 1137.48 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.59 | 22-NOV-22:03 | 525.89 | 11-NOV-09:00 |
December | 2010.79 | 01-DEC-10:09 | 1265.79 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.09 | 10-DEC-14:50 | 476.27 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 737.51 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 72.08 | 73.00 | |||||
Maximum of Months | 2010.79 | 1334.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 270.99 | 528.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 756.30 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.16 | 29-JAN-12:40 | 215.27 | 24-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 661.53 | 13-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.04 | 19-FEB-15:50 | 350.24 | 04-FEB-05:07 |
March | 1295.83 | 01-MAR-10:09 | 565.17 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.57 | 05-MAR-14:00 | 360.79 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 588.16 | 12-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.97 | 15-APR-17:02 | 124.39 | 18-APR-23:53 |
May | 1295.83 | 01-MAY-09:09 | 526.16 | 25-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.06 | 29-MAY-15:47 | 98.24 | 07-MAY-19:10 |
June | 1295.83 | 01-JUN-09:09 | 732.16 | 15-JUN-07:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.65 | 17-JUN-17:30 | 75.61 | 18-JUN-20:10 |
July | 1295.83 | 03-JUL-09:09 | 467.01 | 05-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.70 | 30-JUL-15:28 | 79.43 | 02-JUL-16:00 |
August | 1295.83 | 01-AUG-09:09 | 593.25 | 28-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.78 | 13-AUG-12:40 | 101.66 | 14-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 860.23 | 27-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.08 | 17-SEP-13:18 | 53.23 | 19-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 726.48 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.86 | 29-OCT-14:00 | 72.42 | 16-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 744.91 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.77 | 22-NOV-22:03 | 410.31 | 11-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 815.73 | 15-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.96 | 10-DEC-14:50 | 326.45 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 467.01 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 35.16 | 53.23 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 184.06 | 410.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1129.50 | 04-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.41 | 07-JAN-13:00 | 352.05 | 24-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 898.96 | 08-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.76 | 02-FEB-14:00 | 541.14 | 04-FEB-05:00 |
March | 2010.83 | 01-MAR-10:09 | 1025.09 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 64.36 | 05-MAR-14:30 | 560.72 | 16-MAR-02:00 |
April | 2010.83 | 03-APR-09:09 | 1018.38 | 12-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.83 | 15-APR-17:02 | 186.34 | 18-APR-23:53 |
May | 2010.83 | 01-MAY-09:09 | 887.32 | 25-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.63 | 29-MAY-15:47 | 121.40 | 25-MAY-03:55 |
June | 2010.83 | 01-JUN-09:09 | 1179.20 | 15-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.66 | 17-JUN-17:30 | 115.91 | 18-JUN-20:10 |
July | 2010.83 | 03-JUL-09:09 | 877.61 | 05-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.53 | 30-JUL-15:28 | 103.50 | 02-JUL-16:00 |
August | 2010.83 | 01-AUG-09:09 | 1030.74 | 28-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.91 | 13-AUG-13:00 | 150.27 | 14-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 1334.88 | 27-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.09 | 17-SEP-13:55 | 86.40 | 19-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 1149.86 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.02 | 29-OCT-13:56 | 123.80 | 16-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1071.47 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.83 | 29-NOV-22:03 | 608.30 | 11-NOV-09:00 |
December | 2010.83 | 01-DEC-10:09 | 1261.55 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.93 | 10-DEC-15:00 | 526.86 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 877.61 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 40.41 | 86.40 | |||||
Maximum of Months | 2010.83 | 1334.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 270.63 | 608.30 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 712.99 | 04-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 57.31 | 15-JAN-12:10 | 227.49 | 24-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 661.32 | 07-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.51 | 02-FEB-14:00 | 356.73 | 04-FEB-05:00 |
March | 1295.83 | 01-MAR-10:09 | 713.33 | 15-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.62 | 05-MAR-14:30 | 379.71 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 687.27 | 12-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.51 | 15-APR-17:07 | 136.14 | 18-APR-23:53 |
May | 1295.83 | 01-MAY-09:09 | 613.30 | 25-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.95 | 29-MAY-15:45 | 93.92 | 07-MAY-19:10 |
June | 1295.83 | 01-JUN-09:09 | 770.55 | 15-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.22 | 11-JUN-12:00 | 85.54 | 18-JUN-20:10 |
July | 1295.83 | 03-JUL-09:09 | 607.92 | 05-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.14 | 30-JUL-15:28 | 76.99 | 04-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 690.12 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.62 | 20-AUG-12:10 | 118.70 | 14-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 860.23 | 27-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.01 | 17-SEP-13:18 | 66.00 | 19-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 761.04 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.25 | 29-OCT-12:00 | 80.43 | 01-OCT-07:00 |
November | 1295.83 | 01-NOV-09:09 | 707.42 | 24-NOV-08:09 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.16 | 22-NOV-22:03 | 367.96 | 11-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 810.56 | 15-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.80 | 10-DEC-14:08 | 340.12 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 607.92 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 32.51 | 66.00 | |||||
Maximum of Months | 1295.83 | 860.23 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 181.95 | 379.71 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 284.97 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 284.97 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 284.97 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 284.97 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 284.97 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 284.97 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 284.97 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 284.97 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 284.97 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 284.97 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 284.97 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 284.97 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 3337.76 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 3337.76 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 3337.76 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 3337.76 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 3337.76 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 3337.76 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 3337.76 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 3337.76 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 3337.76 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 3337.76 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 3337.76 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 3337.76 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 3337.76 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 29-JAN-12:00 | 267.72 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.04 | 02-FEB-14:00 | 474.95 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.37 | 05-MAR-13:53 | 456.34 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.13 | 15-APR-17:02 | 142.25 | 18-APR-23:57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.93 | 29-MAY-16:00 | 74.81 | 25-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.54 | 25-JUN-14:00 | 54.73 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.53 | 30-JUL-16:00 | 49.25 | 02-JUL-15:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.87 | 13-AUG-13:00 | 81.09 | 14-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.16 | 17-SEP-14:00 | 33.46 | 19-SEP-23:17 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.98 | 29-OCT-13:52 | 72.62 | 16-OCT-04:33 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.56 | 04-NOV-17:03 | 428.58 | 11-NOV-08:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.44 | 10-DEC-14:42 | 436.21 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.04 | 33.46 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.93 | 474.95 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.07 | 29-JAN-12:20 | 460.42 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.90 | 19-FEB-16:00 | 834.77 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.23 | 05-MAR-14:00 | 804.12 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.61 | 15-APR-17:02 | 251.73 | 18-APR-23:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.52 | 29-MAY-16:00 | 135.78 | 25-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.96 | 25-JUN-13:53 | 108.05 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.80 | 30-JUL-15:50 | 95.45 | 04-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.82 | 13-AUG-13:00 | 141.37 | 14-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.94 | 17-SEP-14:00 | 59.96 | 19-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.10 | 29-OCT-14:00 | 130.91 | 16-OCT-04:33 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.36 | 04-NOV-17:03 | 754.19 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.04 | 10-DEC-14:50 | 766.16 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.90 | 59.96 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.52 | 834.77 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.50 | 29-JAN-12:40 | 475.40 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.91 | 02-FEB-14:00 | 786.56 | 04-FEB-05:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.46 | 13-MAR-17:00 | 785.97 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.08 | 15-APR-17:02 | 252.47 | 18-APR-23:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.09 | 29-MAY-16:00 | 168.55 | 25-MAY-04:07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.95 | 16-JUN-21:03 | 157.31 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.38 | 29-JUL-18:00 | 164.33 | 02-JUL-16:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.96 | 13-AUG-13:00 | 185.25 | 14-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.33 | 17-SEP-17:00 | 105.52 | 03-SEP-13:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.37 | 29-OCT-11:02 | 138.68 | 01-OCT-07:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.70 | 22-NOV-22:03 | 793.45 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.87 | 10-DEC-14:30 | 721.68 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.91 | 105.52 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.09 | 793.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 81271.81 | 23-JAN-04:03 | 0.00 | 1973.16 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83374.26 | 27-FEB-04:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 78079.20 | 13-MAR-03:02 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78097.69 | 20-APR-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69977.99 | 09-MAY-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 67303.35 | 17-JUN-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 67787.02 | 04-JUL-15:47 | 6283.29 | 4604.05 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 69190.86 | 08-AUG-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 69199.28 | 25-SEP-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72330.87 | 17-OCT-03:02 | 0.00 | 3288.60 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 80547.58 | 27-NOV-05:23 | 0.00 | 3945.83 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 79617.51 | 13-DEC-04:03 | 0.00 | 2630.88 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 67303.35 | 0.00 | 1973.16 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83374.26 | 6283.29 | 4604.05 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 85045.48 | 17-JAN-04:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83113.32 | 13-FEB-04:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 82396.48 | 20-MAR-03:02 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 76166.21 | 17-APR-05:04 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 77131.29 | 09-MAY-03:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73140.50 | 05-JUN-05:04 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 74151.32 | 31-JUL-05:04 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 74771.41 | 28-AUG-05:04 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 78702.22 | 26-SEP-03:02 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 78235.34 | 14-OCT-03:02 | 0.00 | 2953.40 | 22266.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86019.04 | 13-NOV-04:02 | 0.00 | 2953.40 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 81149.43 | 27-DEC-04:03 | 0.00 | 2362.72 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 73140.50 | 0.00 | 2362.72 | 22266.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86019.04 | 8061.19 | 5906.06 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 75199.82 | 02-JAN-04:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 75709.07 | 13-FEB-04:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 72659.30 | 16-MAR-05:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72323.64 | 07-APR-05:04 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 70571.86 | 11-MAY-04:03 | 0.00 | 3543.64 | 17812.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 69926.11 | 19-JUN-03:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 71441.40 | 15-JUL-05:04 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 71033.22 | 29-AUG-04:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 72409.56 | 26-SEP-05:04 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72091.60 | 02-OCT-03:02 | 0.00 | 2362.72 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 75785.25 | 13-NOV-04:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 72772.69 | 20-DEC-06:02 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 69926.11 | 0.00 | 2362.72 | 17812.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75785.25 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 70678.78 | 03-JAN-06:03 | 6448.95 | 4724.85 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 73506.91 | 13-FEB-04:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 75693.05 | 06-MAR-04:03 | 0.00 | 2362.72 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72015.97 | 26-APR-05:04 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72325.11 | 22-MAY-03:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73116.40 | 19-JUN-03:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 70944.35 | 03-JUL-03:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 70507.50 | 15-AUG-03:02 | 0.00 | 2953.40 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74433.34 | 05-SEP-03:02 | 0.00 | 2362.72 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75020.21 | 02-OCT-03:02 | 0.00 | 2362.72 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 75108.81 | 06-NOV-04:03 | 0.00 | 2362.72 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71221.85 | 01-DEC-05:03 | 0.00 | 4724.85 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 70507.50 | 0.00 | 2362.72 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75693.05 | 8061.19 | 5906.06 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12398.98 | 30-JAN-04:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.82 |
February | 11339.13 | 18-FEB-06:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 |
March | 11397.30 | 09-MAR-06:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 |
April | 11498.88 | 29-APR-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.79 |
May | 15017.19 | 29-MAY-15:42 | 607.30 | 211.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.52 | 0.00 |
June | 11941.79 | 15-JUN-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 4.61 | 0.00 |
July | 15150.42 | 09-JUL-17:01 | 0.00 | 247.02 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 26.88 | 0.00 |
August | 13106.47 | 21-AUG-03:02 | 0.00 | 444.99 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 14.08 | 0.00 |
September | 11988.93 | 11-SEP-05:04 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 | 0.00 |
October | 11862.40 | 30-OCT-04:42 | 0.00 | 593.25 | 2982.24 | 0.00 | 0.00 | 0.00 | 0.00 | 11.56 | 0.00 |
November | 11711.73 | 29-NOV-06:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 | 0.00 |
December | 11069.33 | 11-DEC-06:03 | 607.30 | 444.94 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11069.33 | 0.00 | 211.73 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15150.42 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 87.52 | 3.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14408.09 | 01-JAN-10:23 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
February | 9801.70 | 26-FEB-09:33 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.74 |
March | 8665.50 | 06-MAR-06:02 | 652.28 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.01 |
April | 14468.37 | 16-APR-08:23 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 |
May | 14372.09 | 07-MAY-09:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 | 0.00 |
June | 11667.70 | 04-JUN-07:43 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 | 0.00 |
July | 11787.30 | 09-JUL-16:21 | 456.59 | 159.19 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 26.75 | 0.00 |
August | 14092.83 | 20-AUG-11:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 31.57 | 0.00 |
September | 14479.57 | 10-SEP-09:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 8.61 | 0.00 |
October | 11584.01 | 09-OCT-08:63 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 2.09 | 0.00 |
November | 7582.64 | 07-NOV-09:00 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6164.91 | 08-DEC-09:50 | 1239.33 | 409.30 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6164.91 | 195.68 | 68.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14479.57 | 1239.33 | 477.89 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 31.57 | 21.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16088.26 | 01-JAN-13:42 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 |
February | 15923.94 | 20-FEB-12:13 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.88 |
March | 14928.79 | 26-MAR-13:03 | 303.66 | 105.87 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 | 0.00 |
April | 12918.54 | 16-APR-15:02 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 28.51 | 0.00 |
May | 14791.55 | 29-MAY-15:42 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 86.89 | 0.00 |
June | 11741.91 | 19-JUN-03:02 | 0.00 | 370.84 | 3727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.22 |
July | 14755.48 | 30-JUL-13:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 57.08 | 0.00 |
August | 14881.54 | 20-AUG-12:23 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 56.15 | 0.00 |
September | 15470.85 | 17-SEP-14:22 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 47.06 | 0.00 |
October | 15578.67 | 09-OCT-11:23 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 0.00 |
November | 16111.35 | 19-NOV-12:52 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.47 |
December | 16370.20 | 10-DEC-12:52 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11741.91 | 0.00 | 105.87 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16370.20 | 607.31 | 370.84 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 86.89 | 50.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14593.77 | 30-JAN-04:02 | 0.00 | 238.98 | 2402.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 |
February | 19098.06 | 20-FEB-16:12 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 |
March | 19355.03 | 12-MAR-16:12 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.39 |
April | 19971.68 | 02-APR-16:22 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 |
May | 20347.41 | 29-MAY-15:42 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 48.35 | 0.00 |
June | 18237.06 | 25-JUN-14:23 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 23.06 | 0.00 |
July | 21287.01 | 09-JUL-17:01 | 0.00 | 159.19 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 0.00 |
August | 19590.05 | 20-AUG-16:22 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 19.11 | 0.00 |
September | 20436.80 | 17-SEP-16:22 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 28.18 | 0.00 |
October | 18378.54 | 08-OCT-14:13 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 12.73 | 0.00 |
November | 19566.70 | 19-NOV-14:52 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.88 |
December | 19770.00 | 25-DEC-14:32 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14593.77 | 0.00 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21287.01 | 391.37 | 238.98 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 48.35 | 17.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10206.00 | 30-JAN-06:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.82 |
February | 10406.67 | 17-FEB-06:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 |
March | 10419.57 | 07-MAR-06:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.97 |
April | 10578.54 | 07-APR-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 |
May | 12843.43 | 30-MAY-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
June | 12714.42 | 09-JUN-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 30.19 | 0.00 |
July | 12881.79 | 31-JUL-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 | 0.00 |
August | 12497.18 | 19-AUG-03:02 | 0.00 | 370.83 | 2795.85 | 0.00 | 0.00 | 0.00 | 0.00 | 28.38 | 0.00 |
September | 12699.78 | 25-SEP-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 |
October | 11557.61 | 30-OCT-03:02 | 0.00 | 370.83 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 13.74 | 0.00 |
November | 10553.40 | 30-NOV-06:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 | 0.00 |
December | 10747.86 | 01-DEC-06:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10206.00 | 0.00 | 370.83 | 2795.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12881.79 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 30.19 | 18.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13026.61 | 01-JAN-10:43 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.76 |
February | 8760.94 | 18-FEB-06:02 | 652.28 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 |
March | 10231.11 | 28-MAR-05:02 | 652.28 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 |
April | 15448.66 | 16-APR-09:52 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 |
May | 14809.46 | 07-MAY-10:23 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 20.22 | 0.00 |
June | 14805.07 | 04-JUN-10:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 33.80 | 0.00 |
July | 15103.98 | 02-JUL-09:32 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 25.39 | 0.00 |
August | 14594.91 | 20-AUG-11:23 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 80.73 | 0.00 |
September | 15075.98 | 10-SEP-09:53 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 25.92 | 0.00 |
October | 10746.67 | 30-OCT-05:02 | 652.28 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.22 | 0.00 |
November | 10507.79 | 30-NOV-06:02 | 652.28 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 | 0.00 |
December | 10193.41 | 09-DEC-06:02 | 652.28 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8760.94 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15448.66 | 652.28 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 80.73 | 3.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14494.34 | 01-JAN-10:43 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.53 |
February | 15022.06 | 20-FEB-14:02 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.48 |
March | 12433.91 | 12-MAR-15:22 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.18 |
April | 13426.93 | 16-APR-13:53 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 70.10 | 0.00 |
May | 12201.55 | 30-MAY-03:02 | 0.00 | 370.84 | 3727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 |
June | 12063.97 | 09-JUN-03:02 | 0.00 | 370.84 | 3727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 31.08 | 0.00 |
July | 13337.78 | 30-JUL-14:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 111.71 | 0.00 |
August | 12285.82 | 06-AUG-14:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 106.58 | 0.00 |
September | 14114.45 | 17-SEP-13:13 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 109.47 | 0.00 |
October | 14753.10 | 29-OCT-11:52 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 62.06 | 0.00 |
November | 14861.82 | 19-NOV-13:32 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.87 |
December | 15445.59 | 03-DEC-13:52 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12063.97 | 0.00 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15445.59 | 607.31 | 370.84 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 111.71 | 58.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9293.84 | 14-JAN-06:03 | 521.82 | 382.31 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 |
February | 15836.29 | 20-FEB-15:22 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.58 |
March | 15891.48 | 12-MAR-16:42 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.93 |
April | 16853.38 | 09-APR-17:32 | 0.00 | 136.45 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.19 |
May | 16044.57 | 29-MAY-16:32 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 121.33 | 0.00 |
June | 14944.13 | 10-JUN-17:06 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 33.61 | 0.00 |
July | 16548.33 | 16-JUL-16:12 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 25.30 | 0.00 |
August | 15888.49 | 20-AUG-16:42 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 45.39 | 0.00 |
September | 15852.86 | 17-SEP-16:32 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 84.85 | 0.00 |
October | 16297.80 | 15-OCT-15:32 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 0.00 |
November | 11801.77 | 20-NOV-04:02 | 0.00 | 286.77 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.35 |
December | 11822.99 | 23-DEC-06:02 | 652.28 | 477.89 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9293.84 | 0.00 | 113.70 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16853.38 | 652.28 | 477.89 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 121.33 | 44.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9742.60 | 30-JAN-06:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.84 |
February | 11727.93 | 18-FEB-06:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.57 |
March | 11332.13 | 06-MAR-06:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 |
April | 11776.53 | 07-APR-05:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 |
May | 16320.55 | 29-MAY-15:42 | 607.30 | 211.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.84 | 0.00 |
June | 15706.83 | 25-JUN-16:03 | 404.87 | 141.15 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 4.04 | 0.00 |
July | 16105.98 | 16-JUL-16:12 | 607.30 | 211.73 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.44 | 0.00 |
August | 15551.04 | 06-AUG-14:02 | 404.87 | 141.15 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 128.24 | 0.00 |
September | 15473.50 | 04-SEP-15:13 | 404.87 | 141.15 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 59.99 | 0.00 |
October | 12015.39 | 02-OCT-05:03 | 809.73 | 593.25 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 | 0.00 |
November | 11832.11 | 30-NOV-06:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 | 0.00 |
December | 11459.62 | 09-DEC-06:02 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9742.60 | 404.87 | 141.15 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16320.55 | 1012.16 | 741.56 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 226.84 | 14.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11552.33 | 01-JAN-10:32 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 |
February | 7982.43 | 18-FEB-06:02 | 652.28 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.05 |
March | 10126.35 | 14-MAR-05:02 | 652.28 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 |
April | 15314.87 | 16-APR-11:23 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 33.09 | 0.00 |
May | 15266.54 | 29-MAY-15:42 | 391.37 | 136.45 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 156.16 | 0.00 |
June | 15430.73 | 04-JUN-10:02 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 38.81 | 0.00 |
July | 15534.51 | 30-JUL-08:43 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 23.35 | 0.00 |
August | 15208.48 | 20-AUG-11:23 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 92.58 | 0.00 |
September | 15422.21 | 24-SEP-10:13 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 31.20 | 0.00 |
October | 12728.45 | 29-OCT-15:12 | 326.14 | 113.70 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 64.57 | 0.00 |
November | 10866.19 | 30-NOV-06:02 | 652.28 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.63 | 0.00 |
December | 9344.19 | 09-DEC-06:02 | 652.28 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7982.43 | 260.91 | 90.96 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15534.51 | 652.28 | 477.89 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 156.16 | 5.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17221.88 | 01-JAN-13:12 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.28 |
February | 17642.43 | 20-FEB-13:52 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.36 |
March | 16524.45 | 26-MAR-13:32 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 0.00 |
April | 15723.30 | 16-APR-16:42 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 59.88 | 0.00 |
May | 16323.71 | 29-MAY-15:42 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 228.05 | 0.00 |
June | 15578.43 | 25-JUN-14:43 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 67.88 | 0.00 |
July | 16104.56 | 30-JUL-14:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 127.87 | 0.00 |
August | 15909.64 | 06-AUG-14:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 121.07 | 0.00 |
September | 16799.20 | 17-SEP-13:13 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 121.52 | 0.00 |
October | 17451.41 | 29-OCT-11:52 | 506.09 | 176.44 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 69.75 | 0.00 |
November | 16863.62 | 26-NOV-14:02 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.00 |
December | 18172.71 | 03-DEC-14:22 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15578.43 | 404.87 | 141.16 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18172.71 | 607.31 | 211.73 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 228.05 | 225.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8505.30 | 30-JAN-06:03 | 521.82 | 382.31 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 |
February | 18177.48 | 20-FEB-16:32 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.73 |
March | 18366.43 | 12-MAR-16:32 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.67 |
April | 18827.54 | 09-APR-17:32 | 0.00 | 136.45 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.92 |
May | 19076.71 | 29-MAY-15:42 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 125.11 | 0.00 |
June | 17226.28 | 25-JUN-16:03 | 260.91 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 2.68 | 0.00 |
July | 18692.33 | 16-JUL-16:12 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 25.05 | 0.00 |
August | 17613.54 | 20-AUG-16:42 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 51.96 | 0.00 |
September | 17888.14 | 10-SEP-15:42 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 71.32 | 0.00 |
October | 18129.95 | 15-OCT-15:32 | 326.14 | 113.70 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 26.14 | 0.00 |
November | 12705.02 | 30-NOV-06:02 | 652.28 | 477.89 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 5.08 | 0.00 |
December | 18035.00 | 10-DEC-15:22 | 391.37 | 136.45 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 24.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8505.30 | 0.00 | 90.96 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19076.71 | 652.28 | 477.89 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 125.11 | 70.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12873.12 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.11 |
February | 10052.48 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.59 |
March | 8894.67 | 27-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.81 |
April | 11559.45 | 17-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 |
May | 13226.61 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.60 |
June | 11983.38 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 0.00 |
July | 13279.78 | 31-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.51 | 0.00 |
August | 13515.92 | 21-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 | 0.00 |
September | 12594.76 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 |
October | 11730.27 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 |
November | 10566.43 | 24-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.82 |
December | 11194.53 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8894.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 | 40.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8785.85 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.94 |
February | 5552.85 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.19 |
March | 6584.83 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 |
April | 7224.14 | 17-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.67 |
May | 7828.90 | 31-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 |
June | 7754.55 | 19-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.98 |
July | 7475.43 | 03-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
August | 7563.25 | 01-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 | 0.00 |
September | 8487.88 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.44 |
October | 8548.70 | 02-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.45 | 0.00 |
November | 7312.13 | 07-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5547.98 | 09-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5547.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8785.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 | 59.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11417.47 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.97 | 0.00 |
February | 11710.30 | 17-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.12 | 0.00 |
March | 14989.21 | 27-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.49 | 0.00 |
April | 17945.07 | 13-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.42 | 0.00 |
May | 19713.76 | 18-MAY-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.73 | 0.00 |
June | 20492.50 | 09-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.57 | 0.00 |
July | 20824.07 | 28-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.91 | 0.00 |
August | 19607.58 | 23-AUG-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.95 | 0.00 |
September | 17267.58 | 08-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.23 | 0.00 |
October | 16511.24 | 06-OCT-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 | 0.00 |
November | 13139.33 | 10-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 0.00 |
December | 11228.72 | 08-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 11228.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.88 | 0.00 | |
Maximum of Months | 20824.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.95 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1955.53 | 17-JAN-17:00 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4138.20 | 20-FEB-17:45 | 46.77 | 63.33 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7211.65 | 31-MAR-23:53 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7811.74 | 09-APR-18:00 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3494.95 | 31-MAY-24:00 | 0.00 | 31.66 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5343.56 | 30-JUN-23:57 | 0.00 | 47.50 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7273.02 | 31-JUL-24:00 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7732.63 | 20-AUG-18:12 | 0.00 | 79.16 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3459.07 | 30-SEP-23:57 | 0.00 | 47.50 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5367.66 | 31-OCT-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5795.10 | 26-NOV-16:55 | 23.38 | 31.66 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7759.20 | 03-DEC-16:55 | 46.77 | 63.33 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1955.53 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7811.74 | 222.14 | 284.97 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1788.16 | 02-JAN-17:00 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3784.35 | 20-FEB-17:45 | 46.77 | 63.33 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6928.25 | 31-MAR-23:53 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7353.77 | 09-APR-18:00 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3371.50 | 31-MAY-24:00 | 0.00 | 31.66 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5200.86 | 30-JUN-23:57 | 0.00 | 47.50 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6990.75 | 31-JUL-24:00 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7258.33 | 20-AUG-17:44 | 0.00 | 79.16 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3328.14 | 30-SEP-23:27 | 0.00 | 47.50 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5058.87 | 31-OCT-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5508.29 | 07-NOV-17:00 | 222.14 | 284.97 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7300.35 | 06-DEC-17:00 | 222.14 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1788.16 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7353.77 | 222.14 | 284.97 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1818.40 | 02-JAN-17:00 | 222.14 | 284.97 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3902.16 | 20-FEB-17:35 | 46.77 | 63.33 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6887.04 | 31-MAR-23:53 | 0.00 | 47.50 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7629.30 | 09-APR-18:00 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3397.78 | 31-MAY-24:00 | 0.00 | 31.66 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5223.24 | 30-JUN-23:57 | 0.00 | 47.50 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7022.46 | 31-JUL-24:00 | 0.00 | 31.66 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7532.87 | 06-AUG-16:05 | 46.77 | 63.33 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3399.26 | 30-SEP-23:57 | 0.00 | 47.50 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4985.04 | 31-OCT-24:00 | 0.00 | 15.83 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5570.12 | 07-NOV-17:00 | 222.14 | 284.97 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7359.60 | 06-DEC-17:00 | 222.14 | 284.97 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1818.40 | 0.00 | 15.83 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7629.30 | 222.14 | 284.97 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92927.03 | 02-JAN-17:00 | 4808.68 | 3337.76 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183885.79 | 21-FEB-17:00 | 4808.68 | 3337.76 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 359120.95 | 31-MAR-23:53 | 0.00 | 556.35 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366578.09 | 17-APR-16:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176165.24 | 31-MAY-24:00 | 0.00 | 370.90 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267644.09 | 30-JUN-23:53 | 0.00 | 556.35 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359963.91 | 31-JUL-24:00 | 0.00 | 370.90 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 367794.18 | 21-AUG-16:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176532.71 | 30-SEP-23:57 | 0.00 | 556.35 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268431.12 | 31-OCT-24:00 | 0.00 | 185.45 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275996.61 | 06-NOV-17:00 | 4808.68 | 3337.76 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367758.45 | 26-DEC-17:00 | 4808.68 | 3337.76 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92927.03 | 0.00 | 185.45 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 367794.18 | 4808.68 | 3337.76 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.152022E+13 | 1152423.68 | 02-JAN-09:30 | 0.504990E+11 | 68192.61 | 13-JAN-12:20 |
February | 0.173385E+13 | 1237859.49 | 10-FEB-15:20 | 0.458416E+11 | 88425.82 | 04-FEB-06:10 |
March | 0.238607E+13 | 1464187.46 | 06-MAR-08:00 | 0.514304E+11 | 67097.72 | 01-MAR-12:30 |
April | 0.269466E+13 | 1635078.87 | 14-APR-15:00 | 0.460872E+11 | 63421.06 | 19-APR-11:50 |
May | 0.174174E+13 | 1228663.98 | 30-MAY-15:39 | 0.470575E+11 | 62487.77 | 01-MAY-11:00 |
June | 0.215832E+13 | 1370985.32 | 29-JUN-15:39 | 0.450446E+11 | 59897.22 | 01-JUN-11:00 |
July | 0.258879E+13 | 1516393.18 | 28-JUL-15:50 | 0.436470E+11 | 58032.06 | 07-JUL-11:50 |
August | 0.301944E+13 | 1654085.04 | 23-AUG-15:00 | 0.465794E+11 | 59437.57 | 31-AUG-11:30 |
September | 0.173664E+13 | 1211566.38 | 11-SEP-07:00 | 0.443106E+11 | 61612.07 | 27-SEP-11:39 |
October | 0.212218E+13 | 1350765.76 | 02-OCT-07:40 | 0.472379E+11 | 63678.92 | 20-OCT-11:00 |
November | 0.235000E+13 | 1475842.96 | 10-NOV-08:20 | 0.476630E+11 | 66181.49 | 21-NOV-12:39 |
December | 0.268328E+13 | 1593803.43 | 08-DEC-08:30 | 0.494126E+11 | 67879.52 | 26-DEC-12:39 |
Annual Sum or Average | 0.267352E+14 | 0.564811E+12 | ||||
Minimum of Months | 0.152022E+13 | 1152423.68 | 0.436470E+11 | 58032.06 | ||
Maximum of Months | 0.301944E+13 | 1654085.04 | 0.514304E+11 | 88425.82 |
Report: EnergyConsumptionDistrictHeatingCoolingMonthly
For: Meter
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportDISTRICTCOOLING:FACILITY [J] | DISTRICTCOOLING:FACILITY {Maximum} [W] | DISTRICTCOOLING:FACILITY {TIMESTAMP} | DISTRICTHEATING:FACILITY [J] | DISTRICTHEATING:FACILITY {Maximum} [W] | DISTRICTHEATING:FACILITY {TIMESTAMP} | |
January | 0.243911E+12 | 95617.36 | 02-JAN-14:00 | 129259.41 | 4.74 | 08-JAN-18:40 |
February | 0.440386E+12 | 186484.83 | 21-FEB-16:00 | 132527.79 | 13.50 | 01-FEB-00:40 |
March | 0.732336E+12 | 359120.99 | 31-MAR-23:00 | 117567.19 | 10.75 | 01-MAR-00:30 |
April | 0.944772E+12 | 369224.18 | 17-APR-13:00 | 65029.99 | 7.03 | 17-APR-23:19 |
May | 0.243761E+12 | 176165.28 | 31-MAY-23:00 | 79284.79 | 8.01 | 31-MAY-23:40 |
June | 0.472010E+12 | 267644.17 | 30-JUN-23:00 | 28323.06 | 6.95 | 21-JUN-23:40 |
July | 0.733711E+12 | 359963.93 | 31-JUL-23:00 | 32150.44 | 5.63 | 24-JUL-23:30 |
August | 0.979627E+12 | 370450.14 | 21-AUG-13:00 | 95265.73 | 7.04 | 07-AUG-23:19 |
September | 0.237950E+12 | 176532.71 | 30-SEP-23:00 | 53255.45 | 4.95 | 26-SEP-23:40 |
October | 0.489860E+12 | 268432.93 | 31-OCT-23:00 | 52363.69 | 10.81 | 31-OCT-23:30 |
November | 0.711275E+12 | 278636.81 | 20-NOV-14:00 | 75490.40 | 10.07 | 12-NOV-18:30 |
December | 0.979877E+12 | 370427.75 | 26-DEC-14:00 | 108553.97 | 10.68 | 17-DEC-18:30 |
Annual Sum or Average | 0.720948E+13 | 969071.89 | ||||
Minimum of Months | 0.237950E+12 | 95617.36 | 28323.06 | 4.74 | ||
Maximum of Months | 0.979877E+12 | 370450.14 | 132527.79 | 13.50 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.170742E+12 | 0.330962E+11 | 0.766053E+12 | 0.207861E+12 | 0.818037E+11 | 0.739891E+11 | 0.00 | 0.139770E+12 | 0.382953E+11 | 0.00 | 0.860565E+10 | 0.00 | 0.00 |
February | 0.153836E+12 | 0.276170E+11 | 0.978954E+12 | 0.229081E+12 | 0.802064E+11 | 0.694546E+11 | 0.00 | 0.145749E+12 | 0.409064E+11 | 0.00 | 0.804355E+10 | 0.00 | 0.00 |
March | 0.181707E+12 | 0.278834E+11 | 0.141687E+13 | 0.299605E+12 | 0.102434E+12 | 0.913289E+11 | 0.00 | 0.200501E+12 | 0.558042E+11 | 0.00 | 0.993834E+10 | 0.00 | 0.00 |
April | 0.161815E+12 | 0.244520E+11 | 0.165903E+13 | 0.333797E+12 | 0.109903E+12 | 0.996358E+11 | 0.00 | 0.231315E+12 | 0.644387E+11 | 0.00 | 0.102773E+11 | 0.00 | 0.00 |
May | 0.174100E+12 | 0.229325E+11 | 0.774844E+12 | 0.208007E+12 | 0.127784E+12 | 0.957762E+11 | 0.00 | 0.241286E+12 | 0.866946E+11 | 0.00 | 0.103131E+11 | 0.00 | 0.00 |
June | 0.173334E+12 | 0.212886E+11 | 0.106252E+13 | 0.245640E+12 | 0.132247E+12 | 0.108826E+12 | 0.00 | 0.300461E+12 | 0.103249E+12 | 0.00 | 0.107551E+11 | 0.00 | 0.00 |
July | 0.162061E+12 | 0.224361E+11 | 0.139340E+13 | 0.299361E+12 | 0.134423E+12 | 0.119030E+12 | 0.00 | 0.335454E+12 | 0.111260E+12 | 0.00 | 0.113576E+11 | 0.00 | 0.00 |
August | 0.180770E+12 | 0.243805E+11 | 0.173200E+13 | 0.345115E+12 | 0.135365E+12 | 0.121076E+12 | 0.00 | 0.355461E+12 | 0.113865E+12 | 0.00 | 0.114094E+11 | 0.00 | 0.00 |
September | 0.162310E+12 | 0.257500E+11 | 0.740713E+12 | 0.201201E+12 | 0.115250E+12 | 0.102947E+12 | 0.00 | 0.279419E+12 | 0.988065E+11 | 0.00 | 0.102465E+11 | 0.00 | 0.00 |
October | 0.169289E+12 | 0.293050E+11 | 0.108340E+13 | 0.253679E+12 | 0.107202E+12 | 0.103485E+12 | 0.00 | 0.273451E+12 | 0.921463E+11 | 0.00 | 0.102162E+11 | 0.00 | 0.00 |
November | 0.168248E+12 | 0.311419E+11 | 0.135889E+13 | 0.289765E+12 | 0.939978E+11 | 0.928284E+11 | 0.00 | 0.233218E+12 | 0.725985E+11 | 0.00 | 0.931135E+10 | 0.00 | 0.00 |
December | 0.165710E+12 | 0.336829E+11 | 0.170972E+13 | 0.345056E+12 | 0.841827E+11 | 0.906584E+11 | 0.00 | 0.193151E+12 | 0.516887E+11 | 0.00 | 0.943036E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.202392E+13 | 0.323966E+12 | 0.146764E+14 | 0.325817E+13 | 0.130480E+13 | 0.116903E+13 | 0.00 | 0.292924E+13 | 0.929753E+12 | 0.00 | 0.119904E+12 | 0.00 | 0.00 |
Minimum of Months | 0.153836E+12 | 0.212886E+11 | 0.740713E+12 | 0.201201E+12 | 0.802064E+11 | 0.694546E+11 | 0.00 | 0.139770E+12 | 0.382953E+11 | 0.00 | 0.804355E+10 | 0.00 | 0.00 |
Maximum of Months | 0.181707E+12 | 0.336829E+11 | 0.173200E+13 | 0.345115E+12 | 0.135365E+12 | 0.121076E+12 | 0.00 | 0.355461E+12 | 0.113865E+12 | 0.00 | 0.114094E+11 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 66976409.05 | 0.00 | 0.504320E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.382381E+09 | 0.00 | 0.454592E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.110797E+09 | 0.00 | 0.513196E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.460872E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.470575E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.450446E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.436470E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.465794E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.443106E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.472379E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 15663233.02 | 0.00 | 0.476473E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.248136E+09 | 0.00 | 0.491645E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.823954E+09 | 0.00 | 0.563987E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.436470E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.382381E+09 | 0.00 | 0.513196E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 191339.97 | 04-JAN-16:00 | 37611.08 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 133939.74 | 30-JAN-08:20 | 103533.73 | 02-JAN-08:50 | 69107.80 | 02-JAN-10:09 | 0.00 | 01-JAN-00:10 |
February | 182390.21 | 08-FEB-16:00 | 37611.08 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 151021.74 | 07-FEB-08:20 | 103767.74 | 13-FEB-13:50 | 67091.38 | 17-FEB-13:50 | 0.00 | 01-FEB-00:10 |
March | 185399.31 | 14-MAR-07:10 | 37611.08 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 168108.66 | 14-MAR-07:19 | 116353.12 | 09-MAR-16:19 | 68124.39 | 27-MAR-13:09 | 0.00 | 01-MAR-00:10 |
April | 185805.65 | 12-APR-07:10 | 37611.08 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 185192.34 | 12-APR-07:19 | 137940.78 | 14-APR-15:00 | 66744.95 | 14-APR-14:50 | 0.00 | 01-APR-00:10 |
May | 179745.20 | 25-MAY-07:10 | 37611.08 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 133938.75 | 25-MAY-07:19 | 144062.46 | 30-MAY-15:30 | 66432.81 | 17-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 191910.50 | 15-JUN-07:10 | 37611.08 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 151028.62 | 15-JUN-07:19 | 146590.05 | 29-JUN-15:39 | 66515.35 | 01-JUN-14:09 | 0.00 | 01-JUN-00:10 |
July | 178332.41 | 05-JUL-07:10 | 37611.08 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 168104.94 | 05-JUL-07:19 | 152921.49 | 24-JUL-15:00 | 67171.41 | 31-JUL-14:30 | 0.00 | 01-JUL-00:10 |
August | 186042.26 | 28-AUG-07:10 | 37611.08 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 185192.47 | 28-AUG-07:19 | 147174.17 | 02-AUG-15:00 | 68991.67 | 31-AUG-14:09 | 0.00 | 01-AUG-00:10 |
September | 198852.03 | 27-SEP-07:10 | 37611.08 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 133948.82 | 27-SEP-07:19 | 128075.29 | 05-SEP-15:09 | 68878.12 | 18-SEP-12:20 | 0.00 | 01-SEP-00:10 |
October | 191879.55 | 31-OCT-07:10 | 37611.08 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 151028.61 | 31-OCT-07:19 | 122398.46 | 02-OCT-12:09 | 69139.04 | 06-OCT-15:30 | 0.00 | 01-OCT-00:10 |
November | 189587.31 | 29-NOV-16:00 | 37611.08 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 168110.05 | 24-NOV-08:20 | 108550.61 | 06-NOV-09:30 | 68991.69 | 07-NOV-09:30 | 0.00 | 01-NOV-00:10 |
December | 196012.70 | 15-DEC-16:00 | 37611.08 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 185194.46 | 29-DEC-08:39 | 105176.44 | 01-DEC-16:00 | 68573.91 | 11-DEC-10:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 178332.41 | 37611.08 | 423497.50 | 133938.75 | 103533.73 | 66432.81 | 0.00 | |||||||
Maximum of Months | 198852.03 | 37611.08 | 778371.69 | 185194.46 | 152921.49 | 69139.04 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 271179.65 | 02-JAN-14:09 | 56753.04 | 02-JAN-09:09 | 0.00 | 5613.48 | 01-JAN-08:50 | 0.00 | 0.00 |
February | 245567.31 | 10-FEB-15:20 | 56753.04 | 02-FEB-12:20 | 0.00 | 5613.48 | 01-FEB-06:10 | 0.00 | 0.00 |
March | 268017.09 | 27-MAR-12:00 | 56753.04 | 03-MAR-14:09 | 0.00 | 5613.48 | 01-MAR-06:10 | 0.00 | 0.00 |
April | 282497.69 | 14-APR-14:00 | 56753.04 | 01-APR-14:30 | 0.00 | 5613.48 | 01-APR-04:10 | 0.00 | 0.00 |
May | 265560.35 | 31-MAY-13:39 | 56753.04 | 01-MAY-14:39 | 0.00 | 5613.48 | 01-MAY-03:09 | 0.00 | 0.00 |
June | 274496.83 | 05-JUN-10:00 | 56753.04 | 01-JUN-07:00 | 0.00 | 5613.48 | 01-JUN-03:20 | 0.00 | 0.00 |
July | 282194.41 | 14-JUL-09:20 | 56753.04 | 01-JUL-06:19 | 0.00 | 5613.48 | 01-JUL-03:30 | 0.00 | 0.00 |
August | 294154.24 | 31-AUG-13:09 | 56753.04 | 01-AUG-03:09 | 0.00 | 5613.48 | 01-AUG-01:19 | 0.00 | 0.00 |
September | 277120.76 | 21-SEP-12:30 | 56753.04 | 01-SEP-07:49 | 0.00 | 5613.48 | 01-SEP-03:20 | 0.00 | 0.00 |
October | 286459.07 | 03-OCT-15:09 | 56753.04 | 01-OCT-01:30 | 0.00 | 5613.48 | 01-OCT-05:30 | 0.00 | 0.00 |
November | 278635.06 | 03-NOV-10:00 | 56753.04 | 01-NOV-09:50 | 0.00 | 5613.48 | 01-NOV-05:19 | 0.00 | 0.00 |
December | 268018.21 | 08-DEC-10:09 | 56753.04 | 01-DEC-14:20 | 0.00 | 5613.48 | 01-DEC-05:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 245567.31 | 56753.04 | 0.00 | 5613.48 | 0.00 | 0.00 | |||
Maximum of Months | 294154.24 | 56753.04 | 0.00 | 5613.48 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1152423.68 | 02-JAN-09:30 | 172325.38 | 423497.50 | 0.00 | 99891.54 | 78726.74 | 68378.36 | 0.00 | 247237.65 | 56753.04 |
February | 1237859.49 | 10-FEB-15:20 | 171235.93 | 541788.89 | 0.00 | 71583.17 | 79092.53 | 66225.15 | 0.00 | 245567.31 | 56753.04 |
March | 1464187.46 | 06-MAR-08:00 | 171622.03 | 660080.29 | 0.00 | 168101.45 | 93476.80 | 65890.43 | 0.00 | 242649.94 | 56753.04 |
April | 1635078.87 | 14-APR-15:00 | 171235.93 | 778371.69 | 0.00 | 151141.29 | 137940.78 | 66038.39 | 0.00 | 267984.29 | 56753.04 |
May | 1228663.98 | 30-MAY-15:39 | 171235.93 | 423497.50 | 0.00 | 99890.88 | 143758.29 | 66346.14 | 0.00 | 261568.73 | 56753.04 |
June | 1370985.32 | 29-JUN-15:39 | 171235.93 | 541788.89 | 0.00 | 116974.35 | 146590.05 | 66152.01 | 0.00 | 265877.58 | 56753.04 |
July | 1516393.18 | 28-JUL-15:50 | 171235.93 | 660080.29 | 0.00 | 134057.82 | 143806.34 | 66536.74 | 0.00 | 278309.55 | 56753.04 |
August | 1654085.04 | 23-AUG-15:00 | 171235.93 | 778371.69 | 0.00 | 151141.29 | 138738.86 | 66506.72 | 0.00 | 285724.04 | 56753.04 |
September | 1211566.38 | 11-SEP-07:00 | 171598.31 | 423497.50 | 0.00 | 133934.47 | 107114.05 | 65901.82 | 0.00 | 247153.72 | 56753.04 |
October | 1350765.76 | 02-OCT-07:40 | 174564.70 | 541788.89 | 0.00 | 151019.75 | 97748.54 | 65795.13 | 0.00 | 257482.24 | 56753.04 |
November | 1475842.96 | 10-NOV-08:20 | 172324.45 | 660080.29 | 0.00 | 168101.88 | 87189.04 | 66004.29 | 0.00 | 259776.50 | 56753.04 |
December | 1593803.43 | 08-DEC-08:30 | 172460.34 | 778371.69 | 0.00 | 185185.42 | 83902.35 | 65560.61 | 0.00 | 245956.51 | 56753.04 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1152423.68 | 171235.93 | 423497.50 | 0.00 | 71583.17 | 78726.74 | 65560.61 | 0.00 | 242649.94 | 56753.04 | |
Maximum of Months | 1654085.04 | 174564.70 | 778371.69 | 0.00 | 185185.42 | 146590.05 | 68378.36 | 0.00 | 285724.04 | 56753.04 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 6118.90 | 26-JAN-06:10 | 0.00 | 68192.61 | 13-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 62214.37 | 04-FEB-06:10 | 0.00 | 67876.53 | 10-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 36339.53 | 16-MAR-05:19 | 0.00 | 67097.72 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 63421.06 | 19-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 62487.77 | 01-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 59897.22 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 58032.06 | 07-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 59437.57 | 31-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 61612.07 | 27-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 63678.92 | 20-OCT-11:00 | 0.00 |
November | 0.00 | 0.00 | 1847.93 | 27-NOV-06:00 | 0.00 | 66181.49 | 21-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 19581.53 | 21-DEC-06:10 | 0.00 | 67879.52 | 26-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 58032.06 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 62214.37 | 0.00 | 68192.61 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.70 | 1.00 | 26.68 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 26.49 | 0.33 | 26.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.99 | 0.00 | 25.99 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 26.13 | 0.00 | 26.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.33 | 0.33 | 26.23 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.16 | 0.00 | 26.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 26.53 | 0.00 | 26.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.43 | 0.67 | 26.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 26.61 | 0.33 | 26.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.53 | 0.50 | 26.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 26.68 | 1.00 | 26.73 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 26.51 | 0.67 | 26.52 |
Annual Sum or Average | 0.00 | 0.00 | 98.00 | 26.51 | 4.83 | 26.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.99 | 0.00 | 25.99 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 26.70 | 1.00 | 26.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.60 | 0.00 | 25.60 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.68 | 0.00 | 25.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.77 | 0.00 | 25.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 25.57 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 25.63 | 0.00 | 25.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.77 | 0.00 | 25.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.46 | 0.33 | 26.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.61 | 0.00 | 25.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.99 | 0.33 | 26.20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.65 | 0.00 | 25.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.60 | 0.00 | 25.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.83 | 25.87 | 0.67 | 26.03 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 26.46 | 0.33 | 26.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.51 | 1.17 | 27.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.40 | 0.83 | 27.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.54 | 2.83 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.21 | 2.67 | 27.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.34 | 2.67 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.41 | 7.00 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.22 | 2.17 | 27.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.19 | 4.83 | 27.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.53 | 1.50 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 28.33 | 27.35 | 25.67 | 27.43 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.54 | 7.00 | 27.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 26.26 | 11.83 | 26.26 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 26.03 | 10.50 | 26.03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.44 | 1.67 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.39 | 1.00 | 27.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.45 | 0.33 | 26.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.58 | 0.00 | 25.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 26.45 | 1.17 | 26.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 26.74 | 2.00 | 26.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.23 | 6.17 | 27.36 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.43 | 9.33 | 27.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 25.54 | 23.33 | 25.54 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 25.97 | 15.67 | 25.97 |
Annual Sum or Average | 0.00 | 0.00 | 89.33 | 26.26 | 83.00 | 26.28 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.54 | 0.00 | 25.54 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 27.44 | 23.33 | 27.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.02 | 0.67 | 27.18 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.01 | 4.17 | 27.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 26.89 | 5.67 | 27.07 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 27.24 | 9.50 | 27.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 26.79 | 4.33 | 26.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 26.85 | 5.83 | 27.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 38.00 | 27.28 | 13.33 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 | 27.32 | 11.00 | 27.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 26.94 | 6.17 | 27.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 26.99 | 8.67 | 27.15 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 26.90 | 7.33 | 27.07 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 27.05 | 9.17 | 27.24 |
Annual Sum or Average | 0.00 | 0.00 | 269.33 | 27.07 | 85.83 | 27.24 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.79 | 0.67 | 26.97 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 | 27.32 | 13.33 | 27.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.58 | 0.50 | 27.58 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.59 | 4.33 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.44 | 3.50 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.49 | 4.83 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.60 | 11.00 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.42 | 3.50 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.47 | 5.17 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.55 | 1.83 | 27.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 35.50 | 27.53 | 34.67 | 27.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.60 | 11.00 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 28.50 | 25.35 | 28.50 | 25.35 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 25.47 | 20.50 | 25.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 25.66 | 3.17 | 25.66 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.26 | 0.33 | 27.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.88 | 0.50 | 27.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.23 | 5.33 | 27.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 25.84 | 22.67 | 25.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 39.83 | 25.34 | 39.83 | 25.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 25.69 | 22.00 | 25.69 |
Annual Sum or Average | 0.00 | 0.00 | 145.00 | 25.60 | 143.17 | 25.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 39.83 | 27.27 | 39.83 | 27.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.75 | 1.83 | 27.75 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.48 | 1.17 | 27.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.48 | 3.67 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.23 | 2.50 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 26.61 | 2.50 | 26.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.09 | 5.17 | 27.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.64 | 3.00 | 26.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.03 | 4.00 | 27.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.41 | 4.17 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.43 | 1.00 | 27.43 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.52 | 1.17 | 27.52 |
Annual Sum or Average | 0.00 | 0.00 | 58.83 | 27.08 | 30.17 | 27.30 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.75 | 5.17 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.32 | 2.00 | 27.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.17 | 1.83 | 27.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.30 | 5.17 | 27.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.29 | 1.83 | 27.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.12 | 2.00 | 27.22 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.50 | 27.26 | 12.83 | 27.33 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.32 | 5.17 | 27.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.40 | 0.17 | 27.40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.57 | 6.83 | 27.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.49 | 6.50 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.50 | 7.33 | 27.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.66 | 13.33 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.45 | 6.33 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.47 | 9.00 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.40 | 6.67 | 27.40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 66.17 | 27.53 | 56.33 | 27.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.66 | 13.33 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.59 | 7.33 | 26.59 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.63 | 7.17 | 26.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.51 | 1.83 | 27.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.42 | 2.67 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.31 | 1.83 | 27.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.37 | 0.83 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.32 | 4.67 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.34 | 2.67 | 27.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.29 | 7.33 | 27.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.43 | 10.00 | 27.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 25.89 | 17.83 | 25.89 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 26.75 | 9.83 | 26.75 |
Annual Sum or Average | 0.00 | 0.00 | 82.67 | 26.84 | 74.00 | 26.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.89 | 0.83 | 25.89 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 27.51 | 17.83 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.80 | 1.83 | 27.82 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.78 | 1.50 | 27.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.72 | 4.17 | 27.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.37 | 3.50 | 27.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.94 | 3.33 | 27.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.22 | 7.00 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 26.90 | 3.67 | 27.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.27 | 5.17 | 27.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.71 | 4.67 | 27.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.50 | 1.33 | 27.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.57 | 1.33 | 27.57 |
Annual Sum or Average | 0.00 | 0.00 | 75.17 | 27.29 | 37.50 | 27.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.80 | 7.00 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 116.50 | 25.64 | 425.33 | 24.95 | 115.83 | 25.07 |
February | 96.00 | 25.34 | 389.00 | 24.85 | 95.17 | 24.93 |
March | 127.67 | 25.31 | 446.00 | 24.75 | 127.67 | 24.85 |
April | 186.17 | 25.33 | 478.17 | 24.81 | 186.17 | 24.92 |
May | 252.67 | 25.15 | 508.00 | 24.77 | 252.67 | 24.86 |
June | 242.83 | 25.09 | 496.00 | 24.72 | 242.83 | 24.81 |
July | 225.00 | 25.52 | 497.00 | 24.95 | 225.00 | 25.08 |
August | 191.17 | 25.48 | 514.00 | 24.81 | 191.17 | 24.95 |
September | 209.67 | 25.46 | 485.00 | 24.88 | 209.67 | 25.01 |
October | 192.67 | 25.72 | 502.00 | 24.97 | 192.67 | 25.13 |
November | 161.67 | 25.71 | 486.83 | 24.94 | 161.67 | 25.10 |
December | 121.67 | 25.95 | 457.83 | 24.99 | 121.67 | 25.16 |
Annual Sum or Average | 2123.67 | 25.44 | 5685.17 | 24.86 | 2122.17 | 24.99 |
Minimum of Months | 96.00 | 25.09 | 389.00 | 24.72 | 95.17 | 24.81 |
Maximum of Months | 252.67 | 25.95 | 514.00 | 24.99 | 252.67 | 25.16 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 24.43 | 421.00 | 24.42 | 0.67 | 24.43 |
February | 4.83 | 23.95 | 388.67 | 24.39 | 0.00 | 24.39 |
March | 0.00 | 0.00 | 445.50 | 24.25 | 0.00 | 24.25 |
April | 0.00 | 0.00 | 480.83 | 24.20 | 0.00 | 24.20 |
May | 0.00 | 0.00 | 508.00 | 24.24 | 0.00 | 24.24 |
June | 0.00 | 0.00 | 496.00 | 24.18 | 0.00 | 24.18 |
July | 0.00 | 0.00 | 497.00 | 24.20 | 0.00 | 24.20 |
August | 0.00 | 0.00 | 514.00 | 24.18 | 0.00 | 24.18 |
September | 0.00 | 0.00 | 483.00 | 24.25 | 0.00 | 24.25 |
October | 0.00 | 0.00 | 502.00 | 24.27 | 0.00 | 24.27 |
November | 0.00 | 0.00 | 484.33 | 24.33 | 0.00 | 24.33 |
December | 0.00 | 0.00 | 457.67 | 24.33 | 0.00 | 24.33 |
Annual Sum or Average | 9.50 | 24.18 | 5678.00 | 24.26 | 0.67 | 24.26 |
Minimum of Months | 0.00 | 0.00 | 388.67 | 24.18 | 0.00 | 24.18 |
Maximum of Months | 4.83 | 24.43 | 514.00 | 24.42 | 0.67 | 24.43 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.67 | 23.60 | 340.00 | 24.21 | 0.00 | 24.21 |
February | 36.00 | 23.46 | 326.00 | 24.17 | 0.00 | 24.17 |
March | 22.00 | 23.69 | 389.17 | 24.21 | 0.00 | 24.21 |
April | 0.00 | 0.00 | 458.67 | 24.20 | 0.00 | 24.20 |
May | 0.00 | 0.00 | 502.83 | 24.19 | 0.00 | 24.19 |
June | 0.00 | 0.00 | 493.00 | 24.17 | 0.00 | 24.17 |
July | 0.00 | 0.00 | 495.00 | 24.16 | 0.00 | 24.16 |
August | 0.00 | 0.00 | 511.00 | 24.16 | 0.00 | 24.16 |
September | 1.00 | 23.27 | 476.67 | 24.19 | 0.00 | 24.19 |
October | 0.00 | 0.00 | 480.83 | 24.26 | 0.00 | 24.26 |
November | 0.00 | 0.00 | 466.33 | 24.28 | 0.00 | 24.28 |
December | 28.50 | 23.41 | 363.67 | 24.20 | 0.00 | 24.20 |
Annual Sum or Average | 122.17 | 23.53 | 5303.17 | 24.20 | 0.00 | 24.20 |
Minimum of Months | 0.00 | 0.00 | 326.00 | 24.16 | 0.00 | 24.16 |
Maximum of Months | 36.00 | 23.69 | 511.00 | 24.28 | 0.00 | 24.28 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 146.83 | 23.17 | 244.83 | 23.77 | 0.00 | 23.77 |
February | 86.67 | 22.95 | 295.33 | 23.93 | 0.00 | 23.93 |
March | 73.67 | 23.35 | 375.67 | 24.08 | 0.00 | 24.08 |
April | 2.33 | 23.42 | 461.83 | 24.22 | 0.00 | 24.22 |
May | 0.00 | 0.00 | 508.00 | 24.25 | 0.00 | 24.25 |
June | 0.00 | 0.00 | 496.00 | 24.23 | 0.00 | 24.23 |
July | 0.00 | 0.00 | 497.00 | 24.27 | 0.00 | 24.27 |
August | 0.83 | 23.21 | 509.00 | 24.22 | 0.00 | 24.22 |
September | 0.00 | 0.00 | 485.00 | 24.26 | 0.00 | 24.26 |
October | 0.00 | 0.00 | 498.33 | 24.28 | 0.00 | 24.28 |
November | 17.83 | 23.24 | 437.50 | 24.20 | 0.00 | 24.20 |
December | 119.33 | 23.09 | 284.33 | 23.86 | 0.00 | 23.86 |
Annual Sum or Average | 447.50 | 23.14 | 5092.83 | 24.15 | 0.00 | 24.15 |
Minimum of Months | 0.00 | 0.00 | 244.83 | 23.77 | 0.00 | 23.77 |
Maximum of Months | 146.83 | 23.42 | 509.00 | 24.28 | 0.00 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 97.00 | 23.41 | 316.83 | 24.08 | 0.00 | 24.08 |
February | 49.00 | 23.32 | 338.67 | 24.16 | 0.00 | 24.16 |
March | 51.33 | 23.60 | 396.33 | 24.19 | 0.00 | 24.19 |
April | 1.67 | 23.64 | 472.00 | 24.28 | 0.00 | 24.28 |
May | 5.17 | 26.66 | 508.00 | 24.44 | 5.17 | 24.47 |
June | 2.67 | 26.76 | 496.00 | 24.41 | 2.67 | 24.42 |
July | 14.67 | 26.71 | 497.00 | 24.55 | 14.67 | 24.61 |
August | 7.67 | 26.71 | 514.00 | 24.39 | 7.67 | 24.42 |
September | 2.50 | 26.76 | 485.00 | 24.45 | 2.50 | 24.46 |
October | 0.00 | 0.00 | 502.00 | 24.40 | 0.00 | 24.40 |
November | 4.33 | 23.55 | 474.33 | 24.31 | 0.00 | 24.31 |
December | 42.17 | 23.38 | 366.17 | 24.20 | 0.00 | 24.20 |
Annual Sum or Average | 278.17 | 23.82 | 5366.33 | 24.33 | 32.67 | 24.35 |
Minimum of Months | 0.00 | 0.00 | 316.83 | 24.08 | 0.00 | 24.08 |
Maximum of Months | 97.00 | 26.76 | 514.00 | 24.55 | 14.67 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 74.67 | 23.72 | 342.17 | 24.27 | 8.17 | 24.32 |
February | 37.83 | 23.68 | 361.50 | 24.27 | 4.17 | 24.30 |
March | 33.33 | 23.57 | 418.83 | 24.19 | 1.67 | 24.20 |
April | 20.33 | 26.43 | 470.00 | 24.40 | 18.17 | 24.48 |
May | 23.33 | 26.70 | 508.00 | 24.54 | 23.33 | 24.63 |
June | 24.17 | 26.75 | 496.00 | 24.50 | 24.17 | 24.60 |
July | 47.83 | 26.77 | 497.00 | 24.71 | 47.83 | 24.87 |
August | 18.17 | 26.73 | 514.00 | 24.40 | 18.17 | 24.48 |
September | 34.67 | 26.75 | 485.00 | 24.65 | 34.67 | 24.78 |
October | 12.33 | 26.78 | 502.00 | 24.48 | 12.33 | 24.54 |
November | 3.67 | 24.29 | 475.50 | 24.30 | 1.00 | 24.31 |
December | 71.50 | 23.23 | 342.17 | 24.07 | 0.00 | 24.07 |
Annual Sum or Average | 401.83 | 24.97 | 5412.17 | 24.41 | 193.67 | 24.49 |
Minimum of Months | 3.67 | 23.23 | 342.17 | 24.07 | 0.00 | 24.07 |
Maximum of Months | 74.67 | 26.78 | 514.00 | 24.71 | 47.83 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.83 | 25.09 | 403.33 | 24.64 | 29.33 | 24.77 |
February | 41.00 | 25.13 | 393.83 | 24.60 | 20.17 | 24.70 |
March | 37.17 | 24.58 | 435.50 | 24.39 | 12.17 | 24.45 |
April | 14.83 | 26.36 | 474.17 | 24.42 | 13.00 | 24.48 |
May | 5.83 | 26.70 | 508.00 | 24.44 | 5.83 | 24.47 |
June | 1.33 | 26.79 | 496.00 | 24.38 | 1.33 | 24.38 |
July | 15.67 | 26.73 | 497.00 | 24.54 | 15.67 | 24.61 |
August | 14.50 | 26.75 | 514.00 | 24.44 | 14.50 | 24.50 |
September | 31.50 | 26.81 | 485.00 | 24.68 | 31.50 | 24.80 |
October | 39.33 | 26.88 | 502.00 | 24.76 | 39.33 | 24.90 |
November | 34.33 | 26.62 | 483.33 | 24.72 | 31.50 | 24.84 |
December | 50.17 | 25.58 | 438.00 | 24.64 | 31.17 | 24.77 |
Annual Sum or Average | 348.50 | 25.85 | 5630.17 | 24.55 | 245.50 | 24.65 |
Minimum of Months | 1.33 | 24.58 | 393.83 | 24.38 | 1.33 | 24.38 |
Maximum of Months | 62.83 | 26.88 | 514.00 | 24.76 | 39.33 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.33 | 24.26 | 410.00 | 24.48 | 6.50 | 24.52 |
February | 35.83 | 26.29 | 409.67 | 24.76 | 28.67 | 24.90 |
March | 43.50 | 26.75 | 473.17 | 24.77 | 41.67 | 24.93 |
April | 75.50 | 26.82 | 485.00 | 24.94 | 75.50 | 25.16 |
May | 48.50 | 26.83 | 508.00 | 24.78 | 48.50 | 24.94 |
June | 53.83 | 26.80 | 496.00 | 24.77 | 53.83 | 24.95 |
July | 93.00 | 26.78 | 497.00 | 25.02 | 93.00 | 25.26 |
August | 84.17 | 26.77 | 514.00 | 24.89 | 84.17 | 25.12 |
September | 50.17 | 26.85 | 485.00 | 24.81 | 50.17 | 24.99 |
October | 62.67 | 26.87 | 502.00 | 24.90 | 62.67 | 25.10 |
November | 50.17 | 26.88 | 483.17 | 24.88 | 50.17 | 25.05 |
December | 58.00 | 26.85 | 476.33 | 24.93 | 58.00 | 25.11 |
Annual Sum or Average | 684.67 | 26.68 | 5739.33 | 24.84 | 652.83 | 25.02 |
Minimum of Months | 29.33 | 24.26 | 409.67 | 24.48 | 6.50 | 24.52 |
Maximum of Months | 93.00 | 26.88 | 514.00 | 25.02 | 93.00 | 25.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 236.17 | 22.95 | 184.67 | 23.48 | 3.83 | 23.48 |
February | 137.83 | 23.06 | 256.17 | 23.78 | 10.17 | 23.83 |
March | 143.50 | 23.46 | 342.33 | 24.01 | 23.33 | 24.07 |
April | 22.67 | 25.09 | 446.17 | 24.32 | 16.00 | 24.37 |
May | 21.33 | 26.08 | 508.00 | 24.48 | 21.33 | 24.54 |
June | 13.67 | 26.37 | 496.00 | 24.48 | 13.67 | 24.53 |
July | 5.17 | 26.73 | 497.00 | 24.54 | 5.17 | 24.56 |
August | 12.17 | 25.86 | 514.00 | 24.41 | 12.17 | 24.45 |
September | 6.67 | 26.19 | 485.00 | 24.45 | 6.67 | 24.47 |
October | 22.33 | 25.99 | 500.83 | 24.46 | 22.33 | 24.53 |
November | 53.83 | 24.20 | 418.67 | 24.25 | 22.17 | 24.31 |
December | 200.33 | 23.07 | 238.67 | 23.70 | 19.83 | 23.76 |
Annual Sum or Average | 875.67 | 23.51 | 4887.50 | 24.22 | 176.67 | 24.27 |
Minimum of Months | 5.17 | 22.95 | 184.67 | 23.48 | 3.83 | 23.48 |
Maximum of Months | 236.17 | 26.73 | 514.00 | 24.54 | 23.33 | 24.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 133.00 | 23.24 | 227.00 | 23.98 | 8.33 | 24.03 |
February | 70.67 | 23.45 | 260.33 | 24.16 | 11.00 | 24.22 |
March | 74.17 | 24.09 | 323.83 | 24.33 | 25.00 | 24.42 |
April | 43.50 | 26.30 | 392.83 | 24.70 | 40.33 | 24.85 |
May | 40.50 | 26.57 | 430.00 | 24.74 | 40.50 | 24.88 |
June | 41.17 | 26.69 | 418.00 | 24.76 | 41.17 | 24.92 |
July | 59.00 | 26.82 | 422.00 | 24.98 | 59.00 | 25.19 |
August | 36.00 | 26.64 | 433.00 | 24.69 | 36.00 | 24.83 |
September | 46.00 | 26.70 | 410.00 | 24.84 | 46.00 | 25.01 |
October | 41.50 | 26.59 | 426.50 | 24.78 | 41.50 | 24.92 |
November | 33.50 | 25.11 | 376.50 | 24.49 | 21.83 | 24.57 |
December | 149.00 | 23.25 | 224.00 | 23.96 | 19.67 | 24.04 |
Annual Sum or Average | 768.00 | 24.78 | 4344.00 | 24.57 | 390.33 | 24.71 |
Minimum of Months | 33.50 | 23.24 | 224.00 | 23.96 | 8.33 | 24.03 |
Maximum of Months | 149.00 | 26.82 | 433.00 | 24.98 | 59.00 | 25.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 95.17 | 24.56 | 381.50 | 24.59 | 34.83 | 24.73 |
February | 60.50 | 24.72 | 371.83 | 24.56 | 27.83 | 24.69 |
March | 78.17 | 24.48 | 412.33 | 24.41 | 32.00 | 24.52 |
April | 24.17 | 25.89 | 464.50 | 24.46 | 21.83 | 24.54 |
May | 21.67 | 26.00 | 508.00 | 24.47 | 21.67 | 24.53 |
June | 12.50 | 26.27 | 496.00 | 24.44 | 12.50 | 24.48 |
July | 5.67 | 26.69 | 497.00 | 24.52 | 5.67 | 24.54 |
August | 20.00 | 26.22 | 514.00 | 24.48 | 20.00 | 24.54 |
September | 36.33 | 26.71 | 485.00 | 24.70 | 36.33 | 24.83 |
October | 61.67 | 26.80 | 502.00 | 24.90 | 61.67 | 25.09 |
November | 53.00 | 26.40 | 471.00 | 24.82 | 48.83 | 24.98 |
December | 98.50 | 24.93 | 392.00 | 24.66 | 51.00 | 24.84 |
Annual Sum or Average | 567.33 | 25.41 | 5495.17 | 24.59 | 374.17 | 24.70 |
Minimum of Months | 5.67 | 24.48 | 371.83 | 24.41 | 5.67 | 24.48 |
Maximum of Months | 98.50 | 26.80 | 514.00 | 24.90 | 61.67 | 25.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 143.83 | 23.12 | 284.50 | 23.89 | 3.67 | 23.89 |
February | 85.17 | 23.60 | 330.00 | 24.22 | 17.50 | 24.30 |
March | 96.83 | 24.30 | 413.50 | 24.42 | 32.83 | 24.53 |
April | 39.33 | 26.50 | 478.17 | 24.67 | 37.50 | 24.80 |
May | 41.33 | 26.66 | 508.00 | 24.71 | 41.33 | 24.85 |
June | 34.00 | 26.81 | 496.00 | 24.66 | 34.00 | 24.79 |
July | 43.83 | 26.85 | 497.00 | 24.82 | 43.83 | 24.97 |
August | 35.33 | 26.71 | 514.00 | 24.66 | 35.33 | 24.78 |
September | 34.33 | 26.81 | 485.00 | 24.71 | 34.33 | 24.84 |
October | 45.00 | 26.73 | 502.00 | 24.75 | 45.00 | 24.90 |
November | 39.83 | 25.25 | 456.17 | 24.48 | 27.00 | 24.57 |
December | 133.33 | 23.63 | 329.50 | 24.21 | 27.33 | 24.31 |
Annual Sum or Average | 772.17 | 24.79 | 5293.83 | 24.54 | 379.67 | 24.66 |
Minimum of Months | 34.00 | 23.12 | 284.50 | 23.89 | 3.67 | 23.89 |
Maximum of Months | 143.83 | 26.85 | 514.00 | 24.82 | 45.00 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 306.33 | 22.49 | 152.00 | 22.98 | 11.50 | 22.96 |
February | 175.50 | 22.66 | 244.17 | 23.44 | 21.83 | 23.41 |
March | 169.67 | 23.04 | 318.33 | 23.82 | 27.17 | 23.87 |
April | 38.83 | 24.56 | 424.17 | 24.34 | 19.33 | 24.40 |
May | 37.83 | 26.27 | 508.00 | 24.58 | 37.83 | 24.69 |
June | 30.83 | 26.54 | 496.00 | 24.59 | 30.83 | 24.70 |
July | 35.83 | 26.69 | 497.00 | 24.72 | 35.83 | 24.84 |
August | 30.83 | 26.25 | 512.67 | 24.52 | 30.83 | 24.61 |
September | 25.17 | 26.58 | 485.00 | 24.58 | 25.17 | 24.68 |
October | 29.00 | 26.07 | 489.83 | 24.52 | 28.17 | 24.61 |
November | 93.83 | 23.60 | 379.50 | 24.13 | 24.00 | 24.19 |
December | 261.33 | 22.62 | 219.50 | 23.34 | 25.33 | 23.39 |
Annual Sum or Average | 1235.00 | 23.37 | 4726.17 | 24.16 | 317.83 | 24.24 |
Minimum of Months | 25.17 | 22.49 | 152.00 | 22.98 | 11.50 | 22.96 |
Maximum of Months | 306.33 | 26.69 | 512.67 | 24.72 | 37.83 | 24.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 188.50 | 22.78 | 240.50 | 23.61 | 10.83 | 23.64 |
February | 108.00 | 23.00 | 292.17 | 23.90 | 15.50 | 23.91 |
March | 96.83 | 23.84 | 377.00 | 24.22 | 30.17 | 24.32 |
April | 52.33 | 26.16 | 451.00 | 24.63 | 46.67 | 24.80 |
May | 51.33 | 26.53 | 507.67 | 24.69 | 51.33 | 24.84 |
June | 45.00 | 26.74 | 496.00 | 24.69 | 45.00 | 24.85 |
July | 62.17 | 26.90 | 497.00 | 24.90 | 62.17 | 25.10 |
August | 42.50 | 26.63 | 512.00 | 24.63 | 42.50 | 24.77 |
September | 51.00 | 26.78 | 485.00 | 24.77 | 51.00 | 24.95 |
October | 59.33 | 26.62 | 496.17 | 24.75 | 59.17 | 24.93 |
November | 59.17 | 24.17 | 419.83 | 24.32 | 23.33 | 24.40 |
December | 218.83 | 22.84 | 253.00 | 23.64 | 23.17 | 23.71 |
Annual Sum or Average | 1035.00 | 24.35 | 5027.33 | 24.44 | 460.83 | 24.57 |
Minimum of Months | 42.50 | 22.78 | 240.50 | 23.61 | 10.83 | 23.64 |
Maximum of Months | 218.83 | 26.90 | 512.00 | 24.90 | 62.17 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 134.17 | 23.72 | 348.50 | 24.27 | 32.67 | 24.41 |
February | 87.00 | 23.95 | 351.17 | 24.34 | 32.83 | 24.44 |
March | 100.67 | 24.07 | 391.00 | 24.32 | 37.83 | 24.45 |
April | 40.33 | 25.74 | 445.33 | 24.52 | 33.17 | 24.63 |
May | 37.33 | 26.21 | 507.50 | 24.56 | 37.33 | 24.66 |
June | 25.00 | 26.49 | 496.00 | 24.53 | 25.00 | 24.62 |
July | 32.83 | 26.70 | 497.00 | 24.68 | 32.83 | 24.80 |
August | 33.33 | 26.36 | 512.67 | 24.55 | 33.33 | 24.66 |
September | 41.00 | 26.81 | 485.00 | 24.75 | 41.00 | 24.90 |
October | 61.67 | 26.85 | 499.33 | 24.89 | 61.67 | 25.08 |
November | 68.67 | 25.58 | 454.67 | 24.71 | 49.17 | 24.87 |
December | 152.00 | 24.08 | 346.00 | 24.40 | 53.00 | 24.59 |
Annual Sum or Average | 814.00 | 24.93 | 5334.17 | 24.55 | 469.83 | 24.69 |
Minimum of Months | 25.00 | 23.72 | 346.00 | 24.27 | 25.00 | 24.41 |
Maximum of Months | 152.00 | 26.85 | 512.67 | 24.89 | 61.67 | 25.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 214.50 | 22.61 | 221.50 | 23.43 | 5.33 | 23.43 |
February | 120.17 | 23.12 | 304.17 | 23.96 | 26.17 | 24.00 |
March | 114.50 | 23.75 | 395.00 | 24.27 | 34.67 | 24.40 |
April | 43.33 | 26.29 | 467.83 | 24.66 | 39.17 | 24.80 |
May | 52.50 | 26.62 | 508.00 | 24.74 | 52.50 | 24.91 |
June | 43.17 | 26.75 | 496.00 | 24.70 | 43.17 | 24.85 |
July | 59.83 | 26.82 | 497.00 | 24.89 | 59.83 | 25.07 |
August | 45.50 | 26.67 | 514.00 | 24.69 | 45.50 | 24.84 |
September | 42.67 | 26.80 | 485.00 | 24.75 | 42.67 | 24.90 |
October | 47.67 | 26.68 | 495.83 | 24.75 | 47.33 | 24.91 |
November | 66.33 | 24.31 | 418.67 | 24.37 | 30.83 | 24.47 |
December | 198.83 | 23.06 | 279.83 | 23.86 | 30.50 | 23.97 |
Annual Sum or Average | 1049.00 | 24.28 | 5082.83 | 24.46 | 457.67 | 24.59 |
Minimum of Months | 42.67 | 22.61 | 221.50 | 23.43 | 5.33 | 23.43 |
Maximum of Months | 214.50 | 26.82 | 514.00 | 24.89 | 59.83 | 25.07 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 27.00 | 502.00 | 27.00 | 2.50 | 27.00 |
February | 9.67 | 27.00 | 454.00 | 27.00 | 9.67 | 27.00 |
March | 57.83 | 27.00 | 514.00 | 27.00 | 57.83 | 27.00 |
April | 266.17 | 27.00 | 485.00 | 27.00 | 266.17 | 27.00 |
May | 4.17 | 27.00 | 508.00 | 27.00 | 4.17 | 27.00 |
June | 25.67 | 27.00 | 496.00 | 27.00 | 25.67 | 27.00 |
July | 251.50 | 27.00 | 497.00 | 27.00 | 251.50 | 27.00 |
August | 398.83 | 27.00 | 514.00 | 27.00 | 398.83 | 27.00 |
September | 14.67 | 27.00 | 485.00 | 27.00 | 14.67 | 27.00 |
October | 43.33 | 27.00 | 502.00 | 27.00 | 43.33 | 27.00 |
November | 92.17 | 27.00 | 489.00 | 27.00 | 92.17 | 27.00 |
December | 166.83 | 27.00 | 497.00 | 27.00 | 166.83 | 27.00 |
Annual Sum or Average | 1333.33 | 27.00 | 5943.00 | 27.00 | 1333.33 | 27.00 |
Minimum of Months | 2.50 | 27.00 | 454.00 | 27.00 | 2.50 | 27.00 |
Maximum of Months | 398.83 | 27.00 | 514.00 | 27.00 | 398.83 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.67 | 27.00 | 454.00 | 27.00 | 0.67 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 0.50 | 27.00 | 485.00 | 27.00 | 0.50 | 27.00 |
May | 0.33 | 27.00 | 508.00 | 27.00 | 0.33 | 27.00 |
June | 0.00 | 0.00 | 496.00 | 27.00 | 0.00 | 27.00 |
July | 0.67 | 27.00 | 497.00 | 27.00 | 0.67 | 27.00 |
August | 5.67 | 27.13 | 514.00 | 27.01 | 5.67 | 27.01 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 0.50 | 27.00 | 502.00 | 27.00 | 0.50 | 27.00 |
November | 0.33 | 27.00 | 489.00 | 27.00 | 0.33 | 27.00 |
December | 0.33 | 27.00 | 497.00 | 27.00 | 0.33 | 27.00 |
Annual Sum or Average | 9.00 | 27.08 | 5943.00 | 27.00 | 9.00 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 5.67 | 27.13 | 514.00 | 27.01 | 5.67 | 27.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 2.83 | 27.00 | 450.33 | 27.00 | 2.83 | 27.00 |
March | 3.67 | 27.00 | 514.00 | 27.00 | 3.67 | 27.00 |
April | 38.83 | 27.00 | 485.00 | 27.00 | 38.83 | 27.00 |
May | 13.33 | 27.00 | 508.00 | 27.00 | 13.33 | 27.00 |
June | 12.50 | 27.00 | 496.00 | 27.00 | 12.50 | 27.00 |
July | 51.50 | 27.00 | 497.00 | 27.00 | 51.50 | 27.00 |
August | 62.67 | 27.06 | 514.00 | 27.01 | 62.67 | 27.02 |
September | 20.33 | 27.00 | 485.00 | 27.00 | 20.33 | 27.00 |
October | 16.50 | 27.00 | 502.00 | 27.00 | 16.50 | 27.00 |
November | 4.50 | 27.00 | 489.00 | 27.00 | 4.50 | 27.00 |
December | 9.00 | 27.00 | 497.00 | 27.00 | 9.00 | 27.00 |
Annual Sum or Average | 235.67 | 27.02 | 5939.33 | 27.00 | 235.67 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 450.33 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 62.67 | 27.06 | 514.00 | 27.01 | 62.67 | 27.02 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5943.00 | 27.00 | 5943.00 | 27.00 | 5943.00 | 27.00 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00049 | 37.21612 | 0.93994 | 23.72434 |
February | 454.00000 | 27.00146 | 35.86086 | 0.96955 | 24.92014 |
March | 514.00000 | 27.00107 | 35.85976 | 1.00263 | 26.27196 |
April | 485.00000 | 27.00037 | 37.21748 | 1.05186 | 28.36809 |
May | 508.00000 | 27.00011 | 43.19174 | 0.34353 | 7.47974 |
June | 496.00000 | 27.00324 | 41.16312 | 0.37130 | 7.88960 |
July | 497.00000 | 27.00184 | 39.84665 | 0.41513 | 8.61767 |
August | 514.00000 | 27.00340 | 38.93501 | 0.44738 | 9.20276 |
September | 485.00000 | 27.00001 | 44.61658 | 0.35758 | 7.68368 |
October | 502.00000 | 27.00278 | 40.37153 | 1.02063 | 27.01004 |
November | 489.00000 | 27.00153 | 37.66376 | 1.02482 | 27.19398 |
December | 497.00000 | 27.00037 | 35.83075 | 1.02968 | 27.41598 |
Annual Sum or Average | 5943.00000 | 27.00140 | 38.99569 | 0.74561 | 18.74828 |
Minimum of Months | 454.00000 | 27.00001 | 35.83075 | 0.34353 | 7.47974 |
Maximum of Months | 514.00000 | 27.00340 | 44.61658 | 1.05186 | 28.36809 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00030 | 37.51030 | 0.88679 | 21.68998 |
February | 454.00000 | 27.00139 | 35.92992 | 0.89995 | 22.19792 |
March | 514.00000 | 27.00100 | 35.85555 | 0.92687 | 23.20396 |
April | 485.00000 | 27.00036 | 37.18073 | 0.96774 | 24.79972 |
May | 508.00000 | 27.00005 | 43.53078 | 0.29551 | 6.83980 |
June | 496.00000 | 27.00309 | 41.30265 | 0.30058 | 6.89787 |
July | 497.00000 | 27.00177 | 39.89326 | 0.31879 | 7.13547 |
August | 514.00000 | 27.00615 | 38.93393 | 0.33081 | 7.30417 |
September | 485.00000 | 27.00001 | 45.05154 | 0.30737 | 6.98631 |
October | 502.00000 | 27.00265 | 40.49848 | 0.96799 | 24.80739 |
November | 489.00000 | 27.00144 | 37.69029 | 0.94698 | 23.97343 |
December | 497.00000 | 27.00037 | 35.79605 | 0.92555 | 23.14217 |
Annual Sum or Average | 5943.00000 | 27.00156 | 39.11239 | 0.67058 | 16.52093 |
Minimum of Months | 454.00000 | 27.00001 | 35.79605 | 0.29551 | 6.83980 |
Maximum of Months | 514.00000 | 27.00615 | 45.05154 | 0.96799 | 24.80739 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00024 | 37.73744 | 0.86084 | 20.80594 |
February | 454.00000 | 27.00141 | 35.97598 | 0.88685 | 21.79636 |
March | 514.00000 | 27.00104 | 35.88790 | 0.92257 | 23.09843 |
April | 485.00000 | 27.00040 | 37.21461 | 0.97711 | 25.21197 |
May | 508.00000 | 27.00009 | 43.40886 | 0.31682 | 7.15063 |
June | 496.00000 | 27.00322 | 41.27080 | 0.32486 | 7.24603 |
July | 497.00000 | 27.00185 | 39.89544 | 0.34952 | 7.61025 |
August | 514.00000 | 27.00834 | 38.96054 | 0.35349 | 7.67843 |
September | 485.00000 | 27.00001 | 44.92153 | 0.32731 | 7.28786 |
October | 502.00000 | 27.00272 | 40.51345 | 0.97669 | 25.18326 |
November | 489.00000 | 27.00149 | 37.73245 | 0.94262 | 23.84525 |
December | 497.00000 | 27.00041 | 35.85016 | 0.90424 | 22.38940 |
Annual Sum or Average | 5943.00000 | 27.00179 | 39.12871 | 0.67638 | 16.55066 |
Minimum of Months | 454.00000 | 27.00001 | 35.85016 | 0.31682 | 7.15063 |
Maximum of Months | 514.00000 | 27.00834 | 44.92153 | 0.97711 | 25.21197 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 41.02858 | 1.18485 | 34.51353 |
February | 454.00000 | 27.00000 | 40.93146 | 1.32792 | 41.71562 |
March | 514.00000 | 27.00000 | 40.88378 | 1.45859 | 48.65733 |
April | 485.00000 | 27.00000 | 40.81391 | 1.58730 | 55.65357 |
May | 508.00000 | 27.00000 | 40.96013 | 0.59059 | 12.33888 |
June | 496.00000 | 27.00000 | 40.83317 | 0.79791 | 18.42878 |
July | 497.00000 | 27.00000 | 40.78658 | 1.00767 | 26.45108 |
August | 514.00000 | 27.00000 | 40.75860 | 1.20389 | 35.44128 |
September | 485.00000 | 27.00000 | 40.89471 | 0.62334 | 13.17924 |
October | 502.00000 | 27.00000 | 40.69552 | 1.34315 | 42.50952 |
November | 489.00000 | 27.00000 | 40.78189 | 1.48190 | 49.91865 |
December | 497.00000 | 27.00000 | 40.83613 | 1.60631 | 56.68836 |
Annual Sum or Average | 5943.00000 | 27.00000 | 40.84992 | 1.18327 | 36.23665 |
Minimum of Months | 454.00000 | 27.00000 | 40.69552 | 0.59059 | 12.33888 |
Maximum of Months | 514.00000 | 27.00000 | 41.02858 | 1.60631 | 56.68836 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.65211 | 52.45638 | 0.62237 | 14.14787 |
February | 454.00000 | 24.62410 | 52.97667 | 0.61650 | 13.88231 |
March | 514.00000 | 24.51031 | 54.76807 | 0.60170 | 13.37446 |
April | 485.00000 | 24.59768 | 60.40630 | 0.66011 | 14.95507 |
May | 508.00000 | 24.57785 | 63.64644 | -0.1654 | 7.05921 |
June | 496.00000 | 24.53392 | 63.99783 | -0.1739 | 7.00107 |
July | 497.00000 | 24.68872 | 62.73332 | -0.1289 | 7.21810 |
August | 514.00000 | 24.55449 | 62.42621 | -0.1624 | 7.12853 |
September | 485.00000 | 24.63228 | 62.88886 | -0.1409 | 7.24008 |
October | 502.00000 | 24.68365 | 61.32209 | 0.69941 | 16.36112 |
November | 489.00000 | 24.68687 | 59.30868 | 0.68621 | 15.86531 |
December | 497.00000 | 24.68202 | 54.74588 | 0.64882 | 14.93638 |
Annual Sum or Average | 5943.00000 | 24.61808 | 59.34185 | 0.31039 | 11.56803 |
Minimum of Months | 454.00000 | 24.51031 | 52.45638 | -0.1739 | 7.00107 |
Maximum of Months | 514.00000 | 24.68872 | 63.99783 | 0.69941 | 16.36112 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.35490 | 50.22500 | 0.54183 | 11.56020 |
February | 454.00000 | 24.33584 | 50.38644 | 0.54495 | 11.57103 |
March | 514.00000 | 24.21981 | 51.40421 | 0.53227 | 11.13100 |
April | 485.00000 | 24.19488 | 55.42212 | 0.56201 | 11.69261 |
May | 508.00000 | 24.24084 | 56.84564 | -0.2966 | 7.11299 |
June | 496.00000 | 24.17988 | 56.79882 | -0.3060 | 7.09464 |
July | 497.00000 | 24.20322 | 56.28955 | -0.2917 | 6.90931 |
August | 514.00000 | 24.17907 | 56.00402 | -0.2940 | 6.92645 |
September | 485.00000 | 24.24491 | 55.95160 | -0.2959 | 7.11449 |
October | 502.00000 | 24.27021 | 54.96700 | 0.57239 | 12.02670 |
November | 489.00000 | 24.32370 | 53.85545 | 0.57925 | 12.25032 |
December | 497.00000 | 24.30387 | 51.60371 | 0.55554 | 11.69801 |
Annual Sum or Average | 5943.00000 | 24.25349 | 54.16692 | 0.19691 | 9.73707 |
Minimum of Months | 454.00000 | 24.17907 | 50.22500 | -0.3060 | 6.90931 |
Maximum of Months | 514.00000 | 24.35490 | 56.84564 | 0.57925 | 12.25032 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.13426 | 51.31758 | 0.46974 | 9.91014 |
February | 454.00000 | 24.13309 | 51.49624 | 0.47321 | 10.06004 |
March | 514.00000 | 24.15747 | 52.23425 | 0.48937 | 10.29133 |
April | 485.00000 | 24.17941 | 56.71755 | 0.52949 | 11.03581 |
May | 508.00000 | 24.18446 | 57.49553 | -0.3396 | 7.66391 |
June | 496.00000 | 24.16158 | 57.49857 | -0.3432 | 7.69987 |
July | 497.00000 | 24.15444 | 57.37089 | -0.3470 | 7.72813 |
August | 514.00000 | 24.16101 | 57.30174 | -0.3460 | 7.71985 |
September | 485.00000 | 24.17523 | 56.45021 | -0.3461 | 7.79090 |
October | 502.00000 | 24.22687 | 55.50991 | 0.53884 | 11.27731 |
November | 489.00000 | 24.26277 | 55.16386 | 0.53896 | 11.33108 |
December | 497.00000 | 24.12324 | 52.85518 | 0.47940 | 10.05846 |
Annual Sum or Average | 5943.00000 | 24.17125 | 55.13698 | 0.14647 | 9.36990 |
Minimum of Months | 454.00000 | 24.12324 | 51.31758 | -0.3470 | 7.66391 |
Maximum of Months | 514.00000 | 24.26277 | 57.49857 | 0.53896 | 11.33108 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.77588 | 53.16677 | 0.37892 | 8.60535 |
February | 454.00000 | 23.91679 | 52.50827 | 0.42197 | 9.66056 |
March | 514.00000 | 24.06275 | 52.82131 | 0.47022 | 10.13104 |
April | 485.00000 | 24.19797 | 56.48262 | 0.54308 | 11.36485 |
May | 508.00000 | 24.25455 | 56.82175 | -0.2966 | 7.18940 |
June | 496.00000 | 24.22989 | 56.75468 | -0.2988 | 7.14943 |
July | 497.00000 | 24.26936 | 56.41187 | -0.2848 | 7.01989 |
August | 514.00000 | 24.21179 | 56.81109 | -0.3085 | 7.26488 |
September | 485.00000 | 24.26181 | 56.12387 | -0.2984 | 7.22093 |
October | 502.00000 | 24.27229 | 55.78685 | 0.55986 | 11.78720 |
November | 489.00000 | 24.16192 | 56.14117 | 0.52022 | 10.92523 |
December | 497.00000 | 23.85057 | 54.47390 | 0.41205 | 9.15265 |
Annual Sum or Average | 5943.00000 | 24.12328 | 55.37232 | 0.14864 | 8.94449 |
Minimum of Months | 454.00000 | 23.77588 | 52.50827 | -0.3085 | 7.01989 |
Maximum of Months | 514.00000 | 24.27229 | 56.82175 | 0.55986 | 11.78720 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.04898 | 50.50986 | 0.43875 | 9.62985 |
February | 454.00000 | 24.14344 | 50.19017 | 0.47896 | 10.37509 |
March | 514.00000 | 24.16149 | 51.00112 | 0.50039 | 10.72037 |
April | 485.00000 | 24.27550 | 54.47780 | 0.57912 | 12.25190 |
May | 508.00000 | 24.42100 | 55.58435 | -0.2071 | 6.63960 |
June | 496.00000 | 24.39596 | 55.28254 | -0.1906 | 6.39753 |
July | 497.00000 | 24.49149 | 54.59215 | -0.1523 | 6.36531 |
August | 514.00000 | 24.35553 | 54.70058 | -0.2046 | 6.48825 |
September | 485.00000 | 24.43977 | 54.56093 | -0.2055 | 6.64602 |
October | 502.00000 | 24.40165 | 53.89953 | 0.60467 | 13.02824 |
November | 489.00000 | 24.30623 | 53.18861 | 0.56271 | 11.86798 |
December | 497.00000 | 24.15584 | 51.65661 | 0.49079 | 10.49696 |
Annual Sum or Average | 5943.00000 | 24.30047 | 53.32091 | 0.22180 | 9.22521 |
Minimum of Months | 454.00000 | 24.04898 | 50.19017 | -0.2071 | 6.36531 |
Maximum of Months | 514.00000 | 24.49149 | 55.58435 | 0.60467 | 13.02824 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.15943 | 49.73257 | 0.48767 | 10.81770 |
February | 454.00000 | 24.21731 | 49.75231 | 0.51929 | 11.26762 |
March | 514.00000 | 24.15481 | 50.67692 | 0.52844 | 11.33985 |
April | 485.00000 | 24.29761 | 54.21724 | 0.61126 | 13.32219 |
May | 508.00000 | 24.43879 | 55.30910 | -0.1616 | 6.49456 |
June | 496.00000 | 24.39464 | 55.14542 | -0.1621 | 6.39569 |
July | 497.00000 | 24.50754 | 54.41753 | -0.1191 | 6.62179 |
August | 514.00000 | 24.32048 | 54.71148 | -0.1957 | 6.54219 |
September | 485.00000 | 24.50152 | 54.11479 | -0.1458 | 6.63069 |
October | 502.00000 | 24.42671 | 53.54595 | 0.63412 | 13.93078 |
November | 489.00000 | 24.28611 | 53.05414 | 0.57255 | 12.14379 |
December | 497.00000 | 24.02748 | 51.90726 | 0.46987 | 10.20843 |
Annual Sum or Average | 5943.00000 | 24.31116 | 53.06749 | 0.25030 | 9.62177 |
Minimum of Months | 454.00000 | 24.02748 | 49.73257 | -0.1957 | 6.39569 |
Maximum of Months | 514.00000 | 24.50754 | 55.30910 | 0.63412 | 13.93078 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.41918 | 48.64427 | 0.58445 | 13.19444 |
February | 454.00000 | 24.44582 | 48.86867 | 0.60187 | 13.49767 |
March | 514.00000 | 24.30057 | 50.16747 | 0.57262 | 12.49403 |
April | 485.00000 | 24.35526 | 54.10117 | 0.61355 | 13.29267 |
May | 508.00000 | 24.41474 | 55.61131 | -0.2103 | 6.67693 |
June | 496.00000 | 24.36978 | 55.41112 | -0.2087 | 6.48834 |
July | 497.00000 | 24.47246 | 54.67479 | -0.1639 | 6.42577 |
August | 514.00000 | 24.37448 | 54.57929 | -0.1870 | 6.44035 |
September | 485.00000 | 24.53819 | 54.05231 | -0.1347 | 6.61136 |
October | 502.00000 | 24.59415 | 52.91197 | 0.69739 | 15.95728 |
November | 489.00000 | 24.57617 | 51.88991 | 0.67939 | 15.35195 |
December | 497.00000 | 24.44097 | 50.12363 | 0.61671 | 13.94198 |
Annual Sum or Average | 5943.00000 | 24.44106 | 52.60901 | 0.28506 | 10.83423 |
Minimum of Months | 454.00000 | 24.30057 | 48.64427 | -0.2103 | 6.42577 |
Maximum of Months | 514.00000 | 24.59415 | 55.61131 | 0.69739 | 15.95728 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.38470 | 48.78677 | 0.56966 | 12.50295 |
February | 454.00000 | 24.56320 | 48.40342 | 0.65389 | 14.91111 |
March | 514.00000 | 24.54489 | 49.16875 | 0.69640 | 16.08079 |
April | 485.00000 | 24.64607 | 52.80792 | 0.79119 | 19.04004 |
May | 508.00000 | 24.58410 | 54.66410 | -0.0545 | 6.43499 |
June | 496.00000 | 24.55116 | 54.45157 | -0.0336 | 6.32213 |
July | 497.00000 | 24.69378 | 53.61373 | 0.05211 | 6.84451 |
August | 514.00000 | 24.58141 | 53.52847 | 0.03695 | 6.55837 |
September | 485.00000 | 24.60448 | 53.68839 | -0.0594 | 6.58322 |
October | 502.00000 | 24.65710 | 52.59170 | 0.74732 | 17.57906 |
November | 489.00000 | 24.66006 | 51.46997 | 0.73562 | 17.13745 |
December | 497.00000 | 24.66402 | 49.25241 | 0.71279 | 16.69898 |
Annual Sum or Average | 5943.00000 | 24.59428 | 51.88875 | 0.40137 | 12.18588 |
Minimum of Months | 454.00000 | 24.38470 | 48.40342 | -0.0594 | 6.32213 |
Maximum of Months | 514.00000 | 24.69378 | 54.66410 | 0.79119 | 19.04004 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.50986 | 52.50224 | 0.29892 | 7.86875 |
February | 454.00000 | 23.75317 | 52.10482 | 0.36928 | 9.00147 |
March | 514.00000 | 23.92855 | 52.84078 | 0.42646 | 9.82601 |
April | 485.00000 | 24.23908 | 56.08934 | 0.54652 | 11.54864 |
May | 508.00000 | 24.41521 | 56.70509 | -0.2246 | 6.84368 |
June | 496.00000 | 24.42803 | 56.29392 | -0.2004 | 6.64796 |
July | 497.00000 | 24.51860 | 55.64714 | -0.1723 | 6.57256 |
August | 514.00000 | 24.38033 | 56.28889 | -0.2312 | 6.80223 |
September | 485.00000 | 24.42777 | 55.29654 | -0.2283 | 6.87474 |
October | 502.00000 | 24.39442 | 55.00678 | 0.58681 | 12.64617 |
November | 489.00000 | 24.15697 | 55.01952 | 0.50716 | 10.82425 |
December | 497.00000 | 23.66269 | 54.29060 | 0.35368 | 8.64738 |
Annual Sum or Average | 5943.00000 | 24.15349 | 54.85638 | 0.16686 | 8.66545 |
Minimum of Months | 454.00000 | 23.50986 | 52.10482 | -0.2312 | 6.57256 |
Maximum of Months | 514.00000 | 24.51860 | 56.70509 | 0.58681 | 12.64617 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.91012 | 50.57249 | 0.40862 | 9.74133 |
February | 385.00000 | 24.07153 | 50.60456 | 0.46408 | 10.50904 |
March | 433.00000 | 24.19440 | 51.54776 | 0.51806 | 11.58264 |
April | 410.00000 | 24.48658 | 54.82437 | 0.63595 | 14.28842 |
May | 430.00000 | 24.56833 | 56.02016 | -0.1405 | 6.76969 |
June | 418.00000 | 24.57304 | 55.66896 | -0.1238 | 6.72230 |
July | 422.00000 | 24.72818 | 54.75435 | -0.0705 | 7.07548 |
August | 433.00000 | 24.52938 | 55.64324 | -0.1521 | 6.77633 |
September | 410.00000 | 24.63536 | 54.54921 | -0.1240 | 6.95204 |
October | 427.00000 | 24.59967 | 54.34310 | 0.65996 | 14.96188 |
November | 417.00000 | 24.35129 | 54.16834 | 0.57125 | 12.43646 |
December | 422.00000 | 23.86019 | 53.23319 | 0.41180 | 9.82093 |
Annual Sum or Average | 5034.00000 | 24.37690 | 53.84502 | 0.25295 | 9.79131 |
Minimum of Months | 385.00000 | 23.86019 | 50.57249 | -0.1521 | 6.72230 |
Maximum of Months | 433.00000 | 24.72818 | 56.02016 | 0.65996 | 14.96188 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.37075 | 48.96220 | 0.56386 | 12.92466 |
February | 454.00000 | 24.37844 | 49.52228 | 0.57289 | 13.01523 |
March | 514.00000 | 24.26334 | 51.21040 | 0.54746 | 12.15503 |
April | 485.00000 | 24.36731 | 55.43686 | 0.59486 | 12.88153 |
May | 508.00000 | 24.40713 | 56.74627 | -0.2285 | 6.86270 |
June | 496.00000 | 24.39190 | 56.48434 | -0.2225 | 6.73134 |
July | 497.00000 | 24.49040 | 55.77203 | -0.1871 | 6.60774 |
August | 514.00000 | 24.41157 | 56.08572 | -0.2070 | 6.70706 |
September | 485.00000 | 24.55083 | 54.58468 | -0.1460 | 6.78599 |
October | 502.00000 | 24.66647 | 53.52696 | 0.70295 | 16.29289 |
November | 489.00000 | 24.61493 | 52.78140 | 0.67395 | 15.40441 |
December | 497.00000 | 24.38199 | 51.00846 | 0.58452 | 13.50610 |
Annual Sum or Average | 5943.00000 | 24.44088 | 53.53637 | 0.26744 | 10.79662 |
Minimum of Months | 454.00000 | 24.26334 | 48.96220 | -0.2285 | 6.60774 |
Maximum of Months | 514.00000 | 24.66647 | 56.74627 | 0.70295 | 16.29289 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.86689 | 50.84994 | 0.40887 | 9.42450 |
February | 454.00000 | 24.10479 | 50.48978 | 0.48795 | 11.22935 |
March | 514.00000 | 24.26589 | 51.20824 | 0.55465 | 12.54985 |
April | 485.00000 | 24.50696 | 54.73738 | 0.66629 | 15.07694 |
May | 508.00000 | 24.55175 | 55.88884 | -0.1192 | 6.70075 |
June | 496.00000 | 24.51406 | 55.74916 | -0.1279 | 6.61842 |
July | 497.00000 | 24.64136 | 54.96919 | -0.0744 | 6.71635 |
August | 514.00000 | 24.52052 | 55.43169 | -0.1179 | 6.58958 |
September | 485.00000 | 24.56214 | 54.52930 | -0.1321 | 6.86724 |
October | 502.00000 | 24.57293 | 53.99557 | 0.67071 | 15.25956 |
November | 489.00000 | 24.35851 | 53.82392 | 0.58997 | 12.91811 |
December | 497.00000 | 24.06719 | 52.35306 | 0.48136 | 11.05553 |
Annual Sum or Average | 5943.00000 | 24.37924 | 53.68740 | 0.27155 | 10.06334 |
Minimum of Months | 454.00000 | 23.86689 | 50.48978 | -0.1321 | 6.58958 |
Maximum of Months | 514.00000 | 24.64136 | 55.88884 | 0.67071 | 15.25956 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.08083 | 54.28759 | 0.19436 | 7.60456 |
February | 454.00000 | 23.50813 | 53.07102 | 0.31129 | 9.11986 |
March | 514.00000 | 23.76141 | 53.57197 | 0.39158 | 9.91356 |
April | 485.00000 | 24.22699 | 56.04550 | 0.55188 | 11.84435 |
May | 508.00000 | 24.44903 | 56.34742 | -0.1936 | 6.84097 |
June | 496.00000 | 24.46830 | 55.75390 | -0.1658 | 6.62719 |
July | 497.00000 | 24.57778 | 55.03802 | -0.1276 | 6.69524 |
August | 514.00000 | 24.40934 | 56.05280 | -0.2015 | 6.77572 |
September | 485.00000 | 24.47702 | 55.23138 | -0.1924 | 6.89876 |
October | 502.00000 | 24.40999 | 55.50350 | 0.60147 | 13.15227 |
November | 489.00000 | 24.02597 | 56.04031 | 0.48213 | 10.71302 |
December | 497.00000 | 23.31115 | 56.04120 | 0.27124 | 8.46069 |
Annual Sum or Average | 5943.00000 | 24.06195 | 55.26069 | 0.15807 | 8.70983 |
Minimum of Months | 454.00000 | 23.08083 | 53.07102 | -0.2015 | 6.62719 |
Maximum of Months | 514.00000 | 24.57778 | 56.34742 | 0.60147 | 13.15227 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.62833 | 52.11539 | 0.34471 | 9.21270 |
February | 454.00000 | 23.87908 | 51.44306 | 0.42837 | 10.39145 |
March | 514.00000 | 24.08576 | 52.02911 | 0.50728 | 11.58473 |
April | 485.00000 | 24.39936 | 54.93958 | 0.64056 | 14.42890 |
May | 508.00000 | 24.49976 | 55.77837 | -0.1214 | 6.65522 |
June | 496.00000 | 24.50592 | 55.30147 | -0.1030 | 6.58195 |
July | 497.00000 | 24.64904 | 54.45248 | -0.0482 | 7.03752 |
August | 514.00000 | 24.45855 | 55.51430 | -0.1342 | 6.67749 |
September | 485.00000 | 24.56204 | 54.48079 | -0.1064 | 6.86582 |
October | 502.00000 | 24.51999 | 54.57591 | 0.66532 | 15.11854 |
November | 489.00000 | 24.20812 | 54.91806 | 0.55234 | 12.16727 |
December | 497.00000 | 23.58330 | 54.75794 | 0.35276 | 9.49841 |
Annual Sum or Average | 5943.00000 | 24.25032 | 54.20795 | 0.24585 | 9.66858 |
Minimum of Months | 454.00000 | 23.58330 | 51.44306 | -0.1342 | 6.58195 |
Maximum of Months | 514.00000 | 24.64904 | 55.77837 | 0.66532 | 15.11854 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.08481 | 50.32219 | 0.49174 | 11.91373 |
February | 454.00000 | 24.19378 | 50.33958 | 0.52983 | 12.59365 |
March | 514.00000 | 24.15310 | 51.85893 | 0.52639 | 12.16289 |
April | 485.00000 | 24.34925 | 55.42356 | 0.60037 | 13.18569 |
May | 508.00000 | 24.43661 | 56.40536 | -0.1991 | 6.86607 |
June | 496.00000 | 24.43394 | 55.93480 | -0.1882 | 6.67693 |
July | 497.00000 | 24.55068 | 55.16201 | -0.1426 | 6.70871 |
August | 514.00000 | 24.43467 | 55.87499 | -0.1787 | 6.70556 |
September | 485.00000 | 24.57380 | 54.61567 | -0.1156 | 6.89605 |
October | 502.00000 | 24.63860 | 54.13915 | 0.71124 | 16.63444 |
November | 489.00000 | 24.49137 | 53.73299 | 0.65305 | 15.02071 |
December | 497.00000 | 24.13581 | 52.45285 | 0.52684 | 12.85416 |
Annual Sum or Average | 5943.00000 | 24.37345 | 53.87778 | 0.26488 | 10.66033 |
Minimum of Months | 454.00000 | 24.08481 | 50.32219 | -0.1991 | 6.67693 |
Maximum of Months | 514.00000 | 24.63860 | 56.40536 | 0.71124 | 16.63444 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.47346 | 52.42748 | 0.31593 | 8.77281 |
February | 454.00000 | 23.88487 | 51.35771 | 0.43817 | 11.02950 |
March | 514.00000 | 24.10727 | 51.87702 | 0.52402 | 12.46890 |
April | 485.00000 | 24.47412 | 54.75731 | 0.66918 | 15.26803 |
May | 508.00000 | 24.55080 | 55.63202 | -0.0980 | 6.76108 |
June | 496.00000 | 24.51794 | 55.32128 | -0.1042 | 6.62743 |
July | 497.00000 | 24.65233 | 54.53283 | -0.0440 | 6.88498 |
August | 514.00000 | 24.51971 | 55.29266 | -0.0966 | 6.63547 |
September | 485.00000 | 24.56463 | 54.59105 | -0.1093 | 6.95230 |
October | 502.00000 | 24.55366 | 54.55188 | 0.67915 | 15.56446 |
November | 489.00000 | 24.22794 | 54.79122 | 0.56701 | 12.69688 |
December | 497.00000 | 23.73335 | 53.93629 | 0.40618 | 10.48327 |
Annual Sum or Average | 5943.00000 | 24.27381 | 54.10427 | 0.26006 | 9.99223 |
Minimum of Months | 454.00000 | 23.47346 | 51.35771 | -0.1093 | 6.62743 |
Maximum of Months | 514.00000 | 24.65233 | 55.63202 | 0.67915 | 15.56446 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.121123E+12 | 161456.23 | 14-JAN-06:03 | 477.61 | 0.766630E+12 | 0.00 | 0.887754E+12 | 3.81 | 7.73 | 02-JAN-06:03 | 0.00 | 0.00 |
February | 0.117983E+12 | 161628.84 | 11-FEB-06:03 | 448.69 | 0.758938E+12 | 0.00 | 0.876921E+12 | 4.04 | 7.62 | 13-FEB-06:02 | 0.00 | 0.00 |
March | 0.147516E+12 | 192841.47 | 06-MAR-06:02 | 585.70 | 0.949837E+12 | 0.00 | 0.109735E+13 | 4.67 | 7.72 | 28-MAR-05:02 | 0.00 | 0.00 |
April | 0.162998E+12 | 178045.28 | 07-APR-05:04 | 639.62 | 0.105763E+13 | 0.00 | 0.122063E+13 | 5.29 | 7.68 | 17-APR-05:02 | 0.00 | 0.00 |
May | 0.189550E+12 | 213997.54 | 31-MAY-05:02 | 579.91 | 0.124162E+13 | 0.00 | 0.143117E+13 | 4.89 | 7.76 | 01-MAY-05:03 | 0.00 | 0.00 |
June | 0.202911E+12 | 217829.18 | 22-JUN-05:04 | 622.88 | 0.130038E+13 | 0.00 | 0.150329E+13 | 5.23 | 7.41 | 17-JUN-05:03 | 0.00 | 0.00 |
July | 0.213283E+12 | 220820.93 | 15-JUL-05:04 | 683.54 | 0.134794E+13 | 0.00 | 0.156122E+13 | 5.43 | 7.41 | 07-JUL-05:03 | 0.00 | 0.00 |
August | 0.215844E+12 | 207429.75 | 26-AUG-05:02 | 692.68 | 0.137111E+13 | 0.00 | 0.158695E+13 | 5.50 | 7.39 | 29-AUG-05:03 | 0.00 | 0.00 |
September | 0.196817E+12 | 211605.61 | 08-SEP-05:03 | 581.05 | 0.126620E+13 | 0.00 | 0.146302E+13 | 4.96 | 7.51 | 05-SEP-03:02 | 0.00 | 0.00 |
October | 0.188781E+12 | 224606.78 | 03-OCT-05:02 | 607.50 | 0.122534E+13 | 0.00 | 0.141412E+13 | 4.97 | 7.64 | 19-OCT-05:03 | 0.00 | 0.00 |
November | 0.158950E+12 | 206205.56 | 04-NOV-05:03 | 565.82 | 0.103650E+13 | 0.00 | 0.119545E+13 | 4.74 | 7.78 | 01-NOV-05:04 | 0.00 | 0.00 |
December | 0.132482E+12 | 199548.12 | 09-DEC-06:04 | 585.76 | 0.833946E+12 | 0.00 | 0.966428E+12 | 4.50 | 7.76 | 19-DEC-06:04 | 0.00 | 0.00 |
Annual Sum or Average | 0.204824E+13 | 7070.75 | 0.131561E+14 | 0.00 | 0.152043E+14 | 4.84 | 0.00 | 0.00 | ||||
Minimum of Months | 0.117983E+12 | 161456.23 | 448.69 | 0.758938E+12 | 0.00 | 0.876921E+12 | 3.81 | 7.39 | 0.00 | 0.00 | ||
Maximum of Months | 0.215844E+12 | 224606.78 | 692.68 | 0.137111E+13 | 0.00 | 0.158695E+13 | 5.50 | 7.78 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.435676E+10 | 161456.23 | 14-JAN-06:03 | 10.39 | 0.306340E+11 | 0.00 | 0.349908E+11 | 0.10 | 7.73 | 02-JAN-06:03 | 0.00 | 0.00 |
February | 0.130162E+10 | 161628.84 | 11-FEB-06:03 | 3.11 | 0.925706E+10 | 0.00 | 0.105587E+11 | 0.03 | 7.62 | 13-FEB-06:02 | 0.00 | 0.00 |
March | 0.934575E+10 | 192841.47 | 06-MAR-06:02 | 22.35 | 0.650265E+11 | 0.00 | 0.743723E+11 | 0.21 | 7.72 | 28-MAR-05:02 | 0.00 | 0.00 |
April | 0.100931E+11 | 178045.28 | 07-APR-05:04 | 23.79 | 0.690916E+11 | 0.00 | 0.791847E+11 | 0.23 | 7.68 | 17-APR-05:02 | 0.00 | 0.00 |
May | 0.303123E+11 | 213997.54 | 31-MAY-05:02 | 71.51 | 0.206045E+12 | 0.00 | 0.236357E+12 | 0.65 | 7.76 | 01-MAY-05:03 | 0.00 | 0.00 |
June | 0.598545E+11 | 217829.18 | 22-JUN-05:04 | 137.90 | 0.400019E+12 | 0.00 | 0.459874E+12 | 1.28 | 7.41 | 17-JUN-05:03 | 0.00 | 0.00 |
July | 0.672691E+11 | 220820.93 | 15-JUL-05:04 | 152.39 | 0.445412E+12 | 0.00 | 0.512681E+12 | 1.36 | 7.41 | 07-JUL-05:03 | 0.00 | 0.00 |
August | 0.705968E+11 | 207429.75 | 26-AUG-05:02 | 160.43 | 0.469315E+12 | 0.00 | 0.539912E+12 | 1.43 | 7.39 | 29-AUG-05:03 | 0.00 | 0.00 |
September | 0.605905E+11 | 211605.61 | 08-SEP-05:03 | 138.26 | 0.405836E+12 | 0.00 | 0.466427E+12 | 1.29 | 7.51 | 05-SEP-03:02 | 0.00 | 0.00 |
October | 0.478056E+11 | 224606.78 | 03-OCT-05:02 | 109.46 | 0.324620E+12 | 0.00 | 0.372426E+12 | 1.00 | 7.64 | 19-OCT-05:03 | 0.00 | 0.00 |
November | 0.290683E+11 | 206205.56 | 04-NOV-05:03 | 68.67 | 0.200029E+12 | 0.00 | 0.229097E+12 | 0.66 | 7.78 | 01-NOV-05:04 | 0.00 | 0.00 |
December | 0.714127E+10 | 199548.12 | 09-DEC-06:04 | 17.17 | 0.496912E+11 | 0.00 | 0.568325E+11 | 0.16 | 7.76 | 19-DEC-06:04 | 0.00 | 0.00 |
Annual Sum or Average | 0.397736E+12 | 915.43 | 0.267498E+13 | 0.00 | 0.307271E+13 | 0.70 | 0.00 | 0.00 | ||||
Minimum of Months | 0.130162E+10 | 161456.23 | 3.11 | 0.925706E+10 | 0.00 | 0.105587E+11 | 0.03 | 7.39 | 0.00 | 0.00 | ||
Maximum of Months | 0.705968E+11 | 224606.78 | 160.43 | 0.469315E+12 | 0.00 | 0.539912E+12 | 1.43 | 7.78 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.247340E+11 | 744.00 | 12476.23 | 01-JAN-00:05 | 42775.44 | 02-JAN-15:10 | 23.73 | 20.91 | 2.81 |
February | 0.266562E+11 | 672.00 | 12476.23 | 01-FEB-01:30 | 71258.22 | 19-FEB-17:22 | 28.14 | 22.35 | 2.81 |
March | 0.309254E+11 | 744.00 | 12476.23 | 01-MAR-09:10 | 113101.25 | 31-MAR-23:13 | 31.97 | 23.23 | 2.81 |
April | 0.322303E+11 | 720.00 | 12476.23 | 01-APR-00:03 | 129765.90 | 14-APR-15:10 | 37.36 | 25.60 | 2.81 |
May | 0.334163E+11 | 744.00 | 12476.23 | 01-MAY-00:10 | 70496.62 | 31-MAY-23:20 | 30.66 | 26.88 | 2.81 |
June | 0.323384E+11 | 720.00 | 12476.23 | 01-JUN-00:03 | 96439.09 | 30-JUN-23:13 | 35.38 | 28.53 | 2.81 |
July | 0.334163E+11 | 744.00 | 12476.23 | 01-JUL-00:03 | 126175.08 | 31-JUL-23:15 | 39.05 | 29.34 | 2.81 |
August | 0.334163E+11 | 744.00 | 12476.23 | 01-AUG-00:03 | 133336.19 | 06-AUG-15:02 | 41.99 | 29.54 | 2.81 |
September | 0.323384E+11 | 720.00 | 12476.23 | 01-SEP-00:05 | 68282.58 | 30-SEP-23:13 | 31.92 | 27.98 | 2.81 |
October | 0.334163E+11 | 744.00 | 12476.23 | 01-OCT-00:03 | 89406.43 | 31-OCT-23:20 | 33.82 | 27.17 | 2.81 |
November | 0.314353E+11 | 720.00 | 12476.23 | 01-NOV-00:10 | 100284.74 | 03-NOV-14:10 | 33.95 | 24.92 | 2.81 |
December | 0.309227E+11 | 744.00 | 12476.23 | 01-DEC-00:10 | 127199.76 | 08-DEC-16:40 | 33.64 | 22.41 | 2.81 |
Annual Sum or Average | 0.375246E+12 | 8760.00 | 33.50 | 25.75 | 2.81 | ||||
Minimum of Months | 0.247340E+11 | 672.00 | 12476.23 | 42775.44 | 23.73 | 20.91 | 2.81 | ||
Maximum of Months | 0.334163E+11 | 744.00 | 12476.23 | 133336.19 | 41.99 | 29.54 | 2.81 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.126879E+11 | 430.10 | 22138.41 | 01-JAN-08:50 | 1249996.22 | 02-JAN-06:05 | 22.86 | 21.74 | 47.07 |
February | 0.138783E+11 | 404.27 | 22138.41 | 01-FEB-11:20 | 1227083.95 | 27-FEB-16:00 | 23.02 | 21.74 | 48.63 |
March | 0.228334E+11 | 538.98 | 22138.41 | 03-MAR-09:00 | 1285736.99 | 28-MAR-05:04 | 23.20 | 21.78 | 57.69 |
April | 0.298131E+11 | 610.16 | 22138.41 | 01-APR-00:53 | 1205431.00 | 28-APR-05:05 | 23.56 | 21.95 | 65.94 |
May | 0.445458E+11 | 579.52 | 22138.41 | 01-MAY-04:07 | 1429475.10 | 30-MAY-05:04 | 25.56 | 23.79 | 57.87 |
June | 0.496423E+11 | 622.88 | 22138.41 | 01-JUN-01:03 | 1405532.39 | 22-JUN-05:04 | 27.00 | 25.10 | 60.38 |
July | 0.539535E+11 | 683.54 | 22138.41 | 01-JUL-00:10 | 1307432.15 | 15-JUL-05:04 | 27.11 | 25.20 | 63.68 |
August | 0.552052E+11 | 692.68 | 22138.41 | 01-AUG-00:03 | 1332024.18 | 24-AUG-05:04 | 27.25 | 25.30 | 64.06 |
September | 0.463085E+11 | 581.05 | 22138.41 | 01-SEP-00:05 | 1284937.43 | 20-SEP-05:04 | 26.98 | 25.13 | 56.66 |
October | 0.449645E+11 | 607.50 | 22138.41 | 01-OCT-00:03 | 1379253.71 | 17-OCT-05:04 | 25.71 | 23.95 | 59.24 |
November | 0.328130E+11 | 537.75 | 22138.41 | 01-NOV-03:02 | 1309370.70 | 01-NOV-03:02 | 24.40 | 22.83 | 56.60 |
December | 0.192941E+11 | 518.76 | 22138.41 | 01-DEC-06:05 | 1310850.50 | 11-DEC-15:30 | 23.03 | 21.78 | 57.36 |
Annual Sum or Average | 0.425940E+12 | 6807.18 | 24.98 | 23.37 | 57.99 | ||||
Minimum of Months | 0.126879E+11 | 404.27 | 22138.41 | 1205431.00 | 22.86 | 21.74 | 47.07 | ||
Maximum of Months | 0.552052E+11 | 692.68 | 22138.41 | 1429475.10 | 27.25 | 25.30 | 65.94 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.873360E+09 | 10.96 | 22138.41 | 02-JAN-06:05 | 1249996.22 | 02-JAN-06:05 | 22.86 | 22.82 | 1.11 |
February | 0.371925E+09 | 4.67 | 22138.41 | 02-FEB-06:03 | 1207922.17 | 16-FEB-06:04 | 23.02 | 23.00 | 0.52 |
March | 0.204537E+10 | 25.66 | 22138.41 | 03-MAR-14:10 | 1285736.99 | 28-MAR-05:04 | 23.20 | 23.10 | 2.56 |
April | 0.239530E+10 | 30.09 | 22138.41 | 01-APR-05:05 | 1202906.58 | 07-APR-05:04 | 23.56 | 23.44 | 3.06 |
May | 0.873249E+10 | 109.57 | 22138.41 | 01-MAY-05:03 | 1429475.10 | 30-MAY-05:04 | 25.56 | 25.14 | 10.14 |
June | 0.212684E+11 | 266.86 | 22138.41 | 01-JUN-03:02 | 1405532.39 | 22-JUN-05:04 | 27.00 | 25.96 | 23.06 |
July | 0.238899E+11 | 299.75 | 22138.41 | 01-JUL-05:03 | 1307432.15 | 15-JUL-05:04 | 27.11 | 25.99 | 24.75 |
August | 0.252439E+11 | 316.74 | 22138.41 | 01-AUG-03:03 | 1332024.18 | 24-AUG-05:04 | 27.25 | 26.05 | 25.92 |
September | 0.201597E+11 | 252.95 | 22138.41 | 01-SEP-03:02 | 1284937.43 | 20-SEP-05:04 | 26.98 | 25.99 | 22.26 |
October | 0.137654E+11 | 172.72 | 22138.41 | 01-OCT-01:23 | 1379253.71 | 17-OCT-05:04 | 25.71 | 25.04 | 15.11 |
November | 0.835016E+10 | 104.77 | 22138.41 | 01-NOV-05:04 | 1288328.95 | 01-NOV-05:04 | 24.40 | 23.97 | 9.39 |
December | 0.147198E+10 | 18.47 | 22138.41 | 01-DEC-06:05 | 1299506.49 | 11-DEC-13:20 | 23.03 | 22.95 | 1.87 |
Annual Sum or Average | 0.128568E+12 | 1613.21 | 24.98 | 24.46 | 11.71 | ||||
Minimum of Months | 0.371925E+09 | 4.67 | 22138.41 | 1202906.58 | 22.86 | 22.82 | 0.52 | ||
Maximum of Months | 0.252439E+11 | 316.74 | 22138.41 | 1429475.10 | 27.25 | 26.05 | 25.92 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 42347687.16 | 0.00 | 16.88 | 12945.64 | 26-JAN-06:02 | 0.00 | 69.95 | 70.33 | 0.00 | 0.00 | 0.00 | 0.01 | 26-JAN-06:02 |
February | 0.242052E+09 | 0.00 | 13.20 | 65353.63 | 04-FEB-06:03 | 0.00 | 29.68 | 30.64 | 0.00 | 0.00 | 0.00 | 0.06 | 04-FEB-06:03 |
March | 70055760.62 | 0.00 | 7.96 | 41224.74 | 16-MAR-05:20 | 0.00 | 26.70 | 27.27 | 0.00 | 0.00 | 0.00 | 0.04 | 16-MAR-05:20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 26.07 | 26.07 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 26.07 | 26.07 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 26.07 | 26.07 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 26.07 | 26.07 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 26.07 | 26.07 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 26.07 | 26.07 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 26.07 | 26.07 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 9903512.31 | 0.00 | 4.21 | 1251.56 | 27-NOV-06:20 | 0.00 | 25.89 | 26.20 | 0.00 | 0.00 | 0.00 | 0.00 | 27-NOV-06:20 |
December | 0.156891E+09 | 0.00 | 17.17 | 38468.29 | 21-DEC-06:03 | 0.00 | 25.05 | 26.31 | 0.00 | 0.00 | 0.00 | 0.03 | 21-DEC-06:03 |
Annual Sum or Average | 0.521250E+09 | 0.00 | 59.41 | 0.00 | 30.02 | 30.31 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.05 | 26.07 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.242052E+09 | 0.00 | 17.17 | 65353.63 | 0.00 | 69.95 | 70.33 | 0.00 | 0.00 | 0.00 | 0.06 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 23.73 | 23.73 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 28.14 | 28.14 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 31.97 | 31.97 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 37.36 | 37.36 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 30.66 | 30.66 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 35.38 | 35.38 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 39.05 | 39.05 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 41.99 | 41.99 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 31.92 | 31.92 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 33.82 | 33.82 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 33.95 | 33.95 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 33.64 | 33.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 33.50 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.73 | 23.73 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.99 | 41.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.827070E+11 | 0.00 | 447.08 | 0.695806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 220028.40 | 30-JAN-04:02 | 136012.37 | 30-JAN-04:02 | 0.00 | 0.00 | 0.00 |
February | 0.923787E+11 | 0.00 | 430.14 | 0.772692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 214413.64 | 18-FEB-06:02 | 136077.24 | 18-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.124053E+12 | 0.00 | 566.94 | 0.100749E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 214342.76 | 14-MAR-05:02 | 134996.76 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.143514E+12 | 0.00 | 613.30 | 0.116999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 219039.86 | 13-APR-05:02 | 135877.95 | 24-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.148984E+12 | 0.00 | 545.68 | 0.113687E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 234527.55 | 27-MAY-05:03 | 141601.74 | 20-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.169683E+12 | 0.00 | 590.47 | 0.126237E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 232321.33 | 12-JUN-05:02 | 142968.12 | 08-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.185161E+12 | 0.00 | 642.61 | 0.138205E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 230369.49 | 03-JUL-05:02 | 147757.17 | 10-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.196353E+12 | 0.00 | 656.98 | 0.146043E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 227906.18 | 24-AUG-05:02 | 149023.50 | 21-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.157933E+12 | 0.00 | 540.82 | 0.115044E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 227914.37 | 13-SEP-03:02 | 148426.86 | 11-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.158340E+12 | 0.00 | 571.50 | 0.118483E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 223800.29 | 05-OCT-05:02 | 145676.89 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.138278E+12 | 0.00 | 538.33 | 0.106367E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 220162.63 | 30-NOV-06:02 | 142203.79 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.114255E+12 | 0.00 | 561.94 | 0.906678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 228028.14 | 09-DEC-06:02 | 134040.82 | 09-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171164E+13 | 0.00 | 6705.81 | 0.131933E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.827070E+11 | 0.00 | 430.14 | 0.695806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 214342.76 | 134040.82 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.196353E+12 | 0.00 | 656.98 | 0.146043E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 234527.55 | 149023.50 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.648133E+12 | 0.00 | 420.86 | 0.531097E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2088852.44 | 14-JAN-06:03 | 1203873.78 | 14-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.694686E+12 | 0.00 | 384.31 | 0.566696E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2163346.55 | 11-FEB-06:03 | 1244699.07 | 18-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.864053E+12 | 0.00 | 454.02 | 0.694646E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2055017.93 | 14-MAR-05:02 | 1231744.61 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.981284E+12 | 0.00 | 455.85 | 0.789294E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2130244.29 | 12-APR-05:03 | 1269273.09 | 12-APR-05:03 | 0.00 | 0.00 | 0.00 |
May | 0.125812E+13 | 0.00 | 487.95 | 0.946841E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2301144.02 | 27-MAY-05:03 | 1307106.18 | 20-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.136216E+13 | 0.00 | 493.60 | 0.992580E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2346423.19 | 19-JUN-03:02 | 1344596.94 | 28-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.139652E+13 | 0.00 | 512.09 | 0.101921E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2308251.01 | 03-JUL-03:02 | 1344354.65 | 14-JUL-05:03 | 0.00 | 0.00 | 0.00 |
August | 0.142724E+13 | 0.00 | 511.89 | 0.102834E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2268836.74 | 28-AUG-03:02 | 1349895.46 | 23-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.133663E+13 | 0.00 | 482.04 | 0.948590E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2193439.12 | 21-SEP-03:02 | 1344482.80 | 01-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.123720E+13 | 0.00 | 468.78 | 0.908856E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2224523.89 | 02-OCT-05:03 | 1332121.08 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.993996E+12 | 0.00 | 425.36 | 0.745857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2136602.05 | 30-NOV-06:02 | 1295766.84 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 0.698578E+12 | 0.00 | 420.18 | 0.554916E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2194691.11 | 09-DEC-06:02 | 1284949.53 | 09-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128986E+14 | 0.00 | 5516.93 | 0.972692E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.648133E+12 | 0.00 | 384.31 | 0.531097E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2055017.93 | 1203873.78 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.142724E+13 | 0.00 | 512.09 | 0.102834E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2346423.19 | 1349895.46 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.597624E+11 | 0.00 | 407.18 | 0.485837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 207221.93 | 07-JAN-06:03 | 116330.71 | 30-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.698530E+11 | 0.00 | 374.23 | 0.571004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 212222.16 | 18-FEB-06:02 | 128330.02 | 18-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.913385E+11 | 0.00 | 449.48 | 0.733922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 216540.11 | 14-MAR-05:02 | 126209.51 | 14-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.109812E+12 | 0.00 | 456.53 | 0.893947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 217893.91 | 13-APR-05:02 | 132085.23 | 13-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.144294E+12 | 0.00 | 497.38 | 0.111443E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 241819.48 | 27-MAY-05:03 | 142441.41 | 23-MAY-03:02 | 0.00 | 0.00 | 0.00 |
June | 0.157242E+12 | 0.00 | 512.54 | 0.118126E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 246385.34 | 19-JUN-03:02 | 144597.84 | 08-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.163392E+12 | 0.00 | 531.37 | 0.123411E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 247293.49 | 03-JUL-03:02 | 145407.95 | 14-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.161716E+12 | 0.00 | 524.87 | 0.120362E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 224918.28 | 12-AUG-05:03 | 141954.41 | 02-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.150376E+12 | 0.00 | 498.25 | 0.110503E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 238154.13 | 20-SEP-03:02 | 146165.20 | 23-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.132705E+12 | 0.00 | 476.33 | 0.100002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 231469.73 | 02-OCT-05:03 | 139518.75 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.101897E+12 | 0.00 | 417.85 | 0.772899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 226205.63 | 30-NOV-06:02 | 136106.10 | 30-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.676399E+11 | 0.00 | 414.36 | 0.532920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 227963.03 | 09-DEC-06:02 | 133170.32 | 09-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141003E+13 | 0.00 | 5560.37 | 0.108290E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.597624E+11 | 0.00 | 374.23 | 0.485837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 207221.93 | 116330.71 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.163392E+12 | 0.00 | 531.37 | 0.123411E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 247293.49 | 146165.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.677543E+11 | 0.00 | 427.08 | 0.605652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143206.88 | 30-JAN-04:02 | 81025.47 | 01-JAN-10:53 | 0.00 | 0.00 | 0.00 |
February | 0.653154E+11 | 0.00 | 380.59 | 0.576369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 147008.58 | 11-FEB-05:03 | 88032.53 | 20-FEB-13:16 | 0.00 | 0.00 | 0.00 |
March | 0.751919E+11 | 0.00 | 439.09 | 0.650157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152030.72 | 06-MAR-04:03 | 82754.82 | 13-MAR-03:02 | 0.00 | 0.00 | 0.00 |
April | 0.781527E+11 | 0.00 | 410.11 | 0.658227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 151811.05 | 13-APR-03:02 | 82245.26 | 20-APR-03:02 | 0.00 | 0.00 | 0.00 |
May | 0.100801E+12 | 0.00 | 444.56 | 0.760965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 169478.65 | 29-MAY-12:30 | 84818.10 | 29-MAY-15:40 | 0.00 | 0.00 | 0.00 |
June | 0.113996E+12 | 0.00 | 440.46 | 0.779716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168948.43 | 26-JUN-03:02 | 79218.80 | 17-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.119320E+12 | 0.00 | 434.60 | 0.809656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168160.16 | 09-JUL-16:51 | 85219.03 | 04-JUL-15:47 | 0.00 | 0.00 | 0.00 |
August | 0.130509E+12 | 0.00 | 470.25 | 0.883596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 171890.90 | 13-AUG-15:52 | 84020.00 | 20-AUG-14:20 | 0.00 | 0.00 | 0.00 |
September | 0.114980E+12 | 0.00 | 442.59 | 0.790353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170584.79 | 10-SEP-14:58 | 81930.94 | 04-SEP-12:00 | 0.00 | 0.00 | 0.00 |
October | 0.109624E+12 | 0.00 | 456.96 | 0.801022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 176801.13 | 30-OCT-02:50 | 84544.97 | 15-OCT-16:12 | 0.00 | 0.00 | 0.00 |
November | 0.936201E+11 | 0.00 | 425.58 | 0.721708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158836.81 | 30-NOV-04:03 | 83011.08 | 20-NOV-04:02 | 0.00 | 0.00 | 0.00 |
December | 0.721399E+11 | 0.00 | 430.44 | 0.626901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 163944.75 | 26-DEC-04:03 | 80803.09 | 10-DEC-14:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114140E+13 | 0.00 | 5202.32 | 0.866432E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.653154E+11 | 0.00 | 380.59 | 0.576369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143206.88 | 79218.80 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.130509E+12 | 0.00 | 470.25 | 0.883596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 176801.13 | 88032.53 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.564950E+10 | 0.137664E+10 | 744.00 | 0.528197E+10 | 0.367539E+09 | 0.00 | 0.35 | 02-JAN-15:00 | 0.20 | 26-JAN-08:00 | 2811.67 | 02-JAN-15:00 | 2418.44 | 02-JAN-15:00 | 397.64 | 06-JAN-17:00 | 830.51 | 02-JAN-15:00 | 0.00 |
February | 0.991475E+10 | 0.239050E+10 | 672.00 | 0.951296E+10 | 0.401788E+09 | 0.00 | 0.57 | 19-FEB-17:20 | 0.42 | 04-FEB-08:00 | 4770.03 | 19-FEB-17:22 | 4619.18 | 20-FEB-17:45 | 436.95 | 11-FEB-17:40 | 1290.58 | 02-FEB-14:00 | 0.00 |
March | 0.161881E+11 | 0.383443E+10 | 744.00 | 0.156321E+11 | 0.555988E+09 | 0.00 | 0.88 | 31-MAR-23:05 | 0.63 | 11-MAR-08:00 | 7806.79 | 31-MAR-23:05 | 7641.78 | 31-MAR-23:53 | 527.03 | 14-MAR-09:00 | 1864.58 | 13-MAR-16:00 | 0.00 |
April | 0.208121E+11 | 0.506501E+10 | 720.00 | 0.201671E+11 | 0.644923E+09 | 0.00 | 0.99 | 14-APR-15:00 | 0.32 | 30-APR-23:53 | 8599.55 | 14-APR-16:00 | 8299.16 | 09-APR-18:00 | 560.93 | 25-APR-15:30 | 2488.67 | 17-APR-15:00 | 0.00 |
May | 0.676946E+10 | 0.189357E+10 | 744.00 | 0.590729E+10 | 0.862170E+09 | 0.00 | 0.56 | 31-MAY-23:10 | 0.27 | 27-MAY-13:00 | 4722.35 | 31-MAY-23:10 | 4007.17 | 31-MAY-23:47 | 762.20 | 31-MAY-23:10 | 1258.86 | 31-MAY-23:10 | 0.00 |
June | 0.117822E+11 | 0.328329E+10 | 720.00 | 0.106464E+11 | 0.113579E+10 | 0.00 | 0.75 | 30-JUN-23:05 | 0.51 | 17-JUN-06:50 | 6438.81 | 30-JUN-23:05 | 5859.17 | 30-JUN-23:57 | 625.02 | 23-JUN-14:00 | 1707.80 | 30-JUN-23:05 | 0.00 |
July | 0.173352E+11 | 0.477048E+10 | 744.00 | 0.161197E+11 | 0.121547E+10 | 0.00 | 0.96 | 31-JUL-23:03 | 0.70 | 14-JUL-20:00 | 8434.43 | 31-JUL-23:03 | 7823.23 | 31-JUL-24:00 | 684.46 | 25-JUL-15:00 | 2280.12 | 31-JUL-23:15 | 0.00 |
August | 0.223853E+11 | 0.599411E+10 | 744.00 | 0.211132E+11 | 0.127215E+10 | 0.00 | 1.00 | 06-AUG-13:13 | 0.35 | 31-AUG-23:13 | 8737.39 | 20-AUG-18:25 | 8306.19 | 20-AUG-18:14 | 663.02 | 21-AUG-12:30 | 2637.19 | 23-AUG-13:00 | 0.00 |
September | 0.681483E+10 | 0.194815E+10 | 720.00 | 0.579742E+10 | 0.101741E+10 | 0.00 | 0.55 | 30-SEP-23:03 | 0.29 | 16-SEP-07:00 | 4523.32 | 30-SEP-23:03 | 3995.47 | 30-SEP-23:57 | 550.58 | 30-SEP-23:03 | 1265.80 | 30-SEP-23:07 | 0.00 |
October | 0.119558E+11 | 0.322647E+10 | 744.00 | 0.109525E+11 | 0.100329E+10 | 0.00 | 0.71 | 31-OCT-23:10 | 0.49 | 28-OCT-07:00 | 6246.74 | 31-OCT-23:10 | 5797.19 | 31-OCT-24:00 | 648.88 | 04-OCT-08:20 | 1489.23 | 03-OCT-15:00 | 0.00 |
November | 0.160838E+11 | 0.396715E+10 | 720.00 | 0.152897E+11 | 0.794098E+09 | 0.00 | 0.79 | 07-NOV-17:00 | 0.65 | 27-NOV-07:00 | 6736.72 | 07-NOV-17:00 | 6323.48 | 07-NOV-17:00 | 618.34 | 29-NOV-11:00 | 1881.21 | 17-NOV-15:00 | 0.00 |
December | 0.211506E+11 | 0.471871E+10 | 744.00 | 0.205678E+11 | 0.582799E+09 | 0.00 | 0.97 | 10-DEC-16:23 | 0.81 | 16-DEC-08:00 | 8648.69 | 08-DEC-16:50 | 8213.23 | 03-DEC-16:55 | 513.68 | 08-DEC-16:50 | 2311.65 | 10-DEC-15:02 | 0.00 |
Annual Sum or Average | 0.166842E+12 | 0.424685E+11 | 8760.00 | 0.156988E+12 | 0.985341E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.564950E+10 | 0.137664E+10 | 672.00 | 0.528197E+10 | 0.367539E+09 | 0.00 | 0.35 | 0.20 | 2811.67 | 2418.44 | 397.64 | 830.51 | 0.00 | ||||||
Maximum of Months | 0.223853E+11 | 0.599411E+10 | 744.00 | 0.211132E+11 | 0.127215E+10 | 0.00 | 1.00 | 0.81 | 8737.39 | 8306.19 | 762.20 | 2637.19 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.481214E+11 | 0.118471E+11 | 744.00 | 0.445475E+11 | 0.357393E+10 | 0.00 | 0.35 | 02-JAN-15:00 | 0.15 | 26-JAN-08:00 | 26280.05 | 02-JAN-15:00 | 22401.13 | 02-JAN-17:00 | 3932.43 | 02-JAN-15:20 | 7761.89 | 02-JAN-15:00 | 0.00 |
February | 0.905183E+11 | 0.219362E+11 | 672.00 | 0.865264E+11 | 0.399186E+10 | 0.00 | 0.56 | 19-FEB-17:20 | 0.37 | 04-FEB-08:00 | 44529.75 | 19-FEB-17:22 | 42397.34 | 20-FEB-17:45 | 4340.10 | 11-FEB-17:40 | 12181.85 | 02-FEB-14:00 | 0.00 |
March | 0.152543E+12 | 0.362042E+11 | 744.00 | 0.146986E+12 | 0.555725E+10 | 0.00 | 0.88 | 31-MAR-23:13 | 0.60 | 21-MAR-07:00 | 74945.76 | 31-MAR-23:05 | 73327.78 | 31-MAR-23:53 | 5267.19 | 14-MAR-09:00 | 17784.65 | 13-MAR-16:00 | 0.00 |
April | 0.198497E+12 | 0.483056E+11 | 720.00 | 0.192039E+12 | 0.645821E+10 | 0.00 | 0.99 | 14-APR-15:00 | 0.29 | 30-APR-23:53 | 82360.78 | 14-APR-16:00 | 78155.91 | 09-APR-18:00 | 5584.91 | 25-APR-15:30 | 23742.11 | 17-APR-15:00 | 0.00 |
May | 0.632933E+11 | 0.177150E+11 | 744.00 | 0.547745E+11 | 0.851874E+10 | 0.00 | 0.57 | 31-MAY-23:10 | 0.26 | 01-MAY-06:00 | 45907.33 | 31-MAY-23:10 | 38580.90 | 31-MAY-24:00 | 7867.74 | 31-MAY-23:10 | 12186.32 | 31-MAY-23:10 | 0.00 |
June | 0.112193E+12 | 0.312429E+11 | 720.00 | 0.100878E+12 | 0.113157E+11 | 0.00 | 0.76 | 30-JUN-23:05 | 0.50 | 21-JUN-20:30 | 62642.52 | 30-JUN-23:05 | 56908.72 | 30-JUN-23:57 | 6204.73 | 23-JUN-13:50 | 16559.73 | 30-JUN-23:05 | 0.00 |
July | 0.165548E+12 | 0.455235E+11 | 744.00 | 0.153410E+12 | 0.121384E+11 | 0.00 | 0.97 | 31-JUL-23:03 | 0.70 | 14-JUL-20:00 | 81554.02 | 31-JUL-23:03 | 75153.68 | 31-JUL-24:00 | 6821.52 | 25-JUL-15:00 | 21980.39 | 31-JUL-23:07 | 0.00 |
August | 0.214014E+12 | 0.572601E+11 | 744.00 | 0.201293E+12 | 0.127205E+11 | 0.00 | 1.00 | 01-AUG-12:30 | 0.32 | 31-AUG-23:33 | 83446.21 | 22-AUG-14:20 | 78104.12 | 20-AUG-17:50 | 6614.15 | 21-AUG-12:30 | 25132.62 | 23-AUG-13:00 | 0.00 |
September | 0.636496E+11 | 0.181989E+11 | 720.00 | 0.536003E+11 | 0.100493E+11 | 0.00 | 0.55 | 30-SEP-23:03 | 0.27 | 16-SEP-07:00 | 43850.28 | 30-SEP-23:03 | 38421.13 | 30-SEP-23:27 | 5657.38 | 30-SEP-23:03 | 12227.36 | 30-SEP-23:07 | 0.00 |
October | 0.113241E+12 | 0.305609E+11 | 744.00 | 0.103251E+12 | 0.999050E+10 | 0.00 | 0.71 | 31-OCT-23:10 | 0.47 | 28-OCT-07:00 | 59182.81 | 31-OCT-23:10 | 54628.24 | 31-OCT-24:00 | 6460.62 | 04-OCT-08:20 | 14226.54 | 03-OCT-15:00 | 0.00 |
November | 0.151792E+12 | 0.375019E+11 | 720.00 | 0.143863E+12 | 0.792956E+10 | 0.00 | 0.79 | 07-NOV-17:00 | 0.61 | 27-NOV-07:00 | 64321.08 | 30-NOV-16:40 | 60147.23 | 07-NOV-17:00 | 6174.68 | 29-NOV-11:00 | 17986.71 | 03-NOV-14:00 | 0.00 |
December | 0.198560E+12 | 0.444264E+11 | 744.00 | 0.192726E+12 | 0.583449E+10 | 0.00 | 0.97 | 08-DEC-16:40 | 0.77 | 16-DEC-08:00 | 82505.35 | 08-DEC-16:50 | 77640.06 | 06-DEC-17:00 | 5125.58 | 08-DEC-17:00 | 21756.58 | 10-DEC-14:52 | 0.00 |
Annual Sum or Average | 0.157197E+13 | 0.400723E+12 | 8760.00 | 0.147389E+13 | 0.980784E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.481214E+11 | 0.118471E+11 | 672.00 | 0.445475E+11 | 0.357393E+10 | 0.00 | 0.35 | 0.15 | 26280.05 | 22401.13 | 3932.43 | 7761.89 | 0.00 | ||||||
Maximum of Months | 0.214014E+12 | 0.572601E+11 | 744.00 | 0.201293E+12 | 0.127205E+11 | 0.00 | 1.00 | 0.77 | 83446.21 | 78155.91 | 7867.74 | 25132.62 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.427271E+10 | 0.106693E+10 | 744.00 | 0.392304E+10 | 0.349666E+09 | 0.00 | 0.35 | 02-JAN-15:00 | 0.06 | 26-JAN-08:00 | 2690.66 | 02-JAN-15:00 | 2296.94 | 02-JAN-15:00 | 396.99 | 02-JAN-15:20 | 794.34 | 02-JAN-15:00 | 0.00 |
February | 0.876937E+10 | 0.213827E+10 | 672.00 | 0.837167E+10 | 0.397697E+09 | 0.00 | 0.57 | 19-FEB-17:20 | 0.25 | 05-FEB-07:30 | 4601.29 | 19-FEB-17:22 | 4370.46 | 20-FEB-17:35 | 435.69 | 02-FEB-11:00 | 1241.12 | 02-FEB-14:00 | 0.00 |
March | 0.151133E+11 | 0.360050E+10 | 744.00 | 0.145587E+11 | 0.554658E+09 | 0.00 | 0.87 | 31-MAR-23:13 | 0.53 | 16-MAR-07:00 | 7462.69 | 31-MAR-23:05 | 7299.07 | 31-MAR-23:53 | 526.64 | 14-MAR-09:00 | 1801.95 | 13-MAR-16:00 | 0.00 |
April | 0.198988E+11 | 0.485233E+10 | 720.00 | 0.192540E+11 | 0.644838E+09 | 0.00 | 1.00 | 16-APR-17:00 | 0.29 | 30-APR-23:53 | 8338.21 | 14-APR-16:00 | 8101.36 | 09-APR-17:42 | 558.20 | 25-APR-15:30 | 2408.51 | 16-APR-15:00 | 0.00 |
May | 0.648269E+10 | 0.181572E+10 | 744.00 | 0.562715E+10 | 0.855544E+09 | 0.00 | 0.56 | 31-MAY-23:10 | 0.24 | 01-MAY-06:00 | 4620.38 | 31-MAY-23:10 | 3891.87 | 31-MAY-24:00 | 780.83 | 31-MAY-23:10 | 1228.09 | 31-MAY-23:10 | 0.00 |
June | 0.113761E+11 | 0.316981E+10 | 720.00 | 0.102435E+11 | 0.113260E+10 | 0.00 | 0.76 | 30-JUN-23:05 | 0.49 | 14-JUN-06:00 | 6296.41 | 30-JUN-23:05 | 5720.75 | 30-JUN-23:57 | 622.73 | 23-JUN-13:50 | 1666.53 | 30-JUN-23:05 | 0.00 |
July | 0.167434E+11 | 0.460775E+10 | 744.00 | 0.155295E+11 | 0.121387E+10 | 0.00 | 0.96 | 31-JUL-23:03 | 0.69 | 14-JUL-21:13 | 8159.10 | 31-JUL-23:03 | 7554.58 | 31-JUL-24:00 | 682.66 | 25-JUL-15:00 | 2203.97 | 31-JUL-23:15 | 0.00 |
August | 0.215229E+11 | 0.576657E+10 | 744.00 | 0.202519E+11 | 0.127107E+10 | 0.00 | 1.00 | 02-AUG-13:40 | 0.32 | 31-AUG-23:13 | 8532.49 | 06-AUG-15:55 | 8063.82 | 06-AUG-16:00 | 662.05 | 21-AUG-12:30 | 2549.10 | 23-AUG-13:00 | 0.00 |
September | 0.651291E+10 | 0.186419E+10 | 720.00 | 0.550403E+10 | 0.100888E+10 | 0.00 | 0.55 | 30-SEP-23:03 | 0.25 | 26-SEP-07:00 | 4447.77 | 30-SEP-23:03 | 3917.57 | 30-SEP-23:57 | 555.78 | 30-SEP-23:03 | 1241.56 | 30-SEP-23:07 | 0.00 |
October | 0.113859E+11 | 0.307732E+10 | 744.00 | 0.103873E+11 | 0.998596E+09 | 0.00 | 0.69 | 31-OCT-23:10 | 0.45 | 28-OCT-07:00 | 5856.31 | 31-OCT-23:10 | 5396.50 | 31-OCT-24:00 | 646.25 | 04-OCT-08:20 | 1450.28 | 03-OCT-15:00 | 0.00 |
November | 0.150414E+11 | 0.373076E+10 | 720.00 | 0.142499E+11 | 0.791541E+09 | 0.00 | 0.79 | 07-NOV-17:00 | 0.54 | 27-NOV-08:00 | 6496.05 | 07-NOV-17:00 | 6084.07 | 07-NOV-17:00 | 618.34 | 29-NOV-11:00 | 1821.54 | 03-NOV-14:00 | 0.00 |
December | 0.194769E+11 | 0.438253E+10 | 744.00 | 0.188952E+11 | 0.581722E+09 | 0.00 | 0.97 | 10-DEC-16:12 | 0.69 | 16-DEC-08:00 | 8324.80 | 08-DEC-16:50 | 7853.87 | 10-DEC-16:27 | 512.55 | 08-DEC-16:50 | 2213.96 | 10-DEC-15:02 | 0.00 |
Annual Sum or Average | 0.156597E+12 | 0.400727E+11 | 8760.00 | 0.146796E+12 | 0.980067E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.427271E+10 | 0.106693E+10 | 672.00 | 0.392304E+10 | 0.349666E+09 | 0.00 | 0.35 | 0.06 | 2690.66 | 2296.94 | 396.99 | 794.34 | 0.00 | ||||||
Maximum of Months | 0.215229E+11 | 0.576657E+10 | 744.00 | 0.202519E+11 | 0.127107E+10 | 0.00 | 1.00 | 0.69 | 8532.49 | 8101.36 | 780.83 | 2549.10 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.20 | 0.00 | 77.20 | 78.17 | 209.80 | 0.00 | 0.00 | 0.00 |
February | 91.38 | 0.00 | 91.38 | 120.78 | 173.70 | 0.00 | 0.00 | 0.00 |
March | 108.97 | 0.00 | 108.97 | 147.17 | 140.81 | 0.00 | 0.00 | 0.00 |
April | 122.11 | 0.55 | 121.56 | 207.95 | 86.16 | 0.00 | 0.00 | 0.00 |
May | 139.44 | 6.24 | 133.20 | 291.34 | 43.69 | 0.00 | 0.00 | 0.00 |
June | 148.95 | 10.72 | 138.23 | 336.29 | 18.09 | 0.00 | 0.00 | 0.00 |
July | 150.73 | 7.39 | 143.35 | 354.76 | 26.77 | 0.00 | 0.00 | 0.00 |
August | 133.40 | 1.23 | 132.18 | 297.63 | 18.05 | 0.00 | 0.00 | 0.00 |
September | 118.34 | 0.01 | 118.33 | 276.69 | 31.81 | 0.00 | 0.00 | 0.00 |
October | 99.14 | 0.00 | 99.14 | 203.11 | 50.77 | 0.00 | 0.00 | 0.00 |
November | 86.21 | 0.00 | 86.21 | 140.08 | 105.81 | 0.00 | 0.00 | 0.00 |
December | 76.36 | 0.00 | 76.36 | 88.37 | 179.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.79 | 2.19 | 110.60 | 212.30 | 90.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.36 | 0.00 | 76.36 | 78.17 | 18.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 150.73 | 10.72 | 143.35 | 354.76 | 209.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.20 | 0.00 | 77.20 | 78.17 | 209.80 | 0.00 | 0.00 | 0.00 |
February | 91.37 | 0.00 | 91.37 | 120.78 | 173.69 | 0.00 | 0.00 | 0.00 |
March | 108.97 | 0.00 | 108.97 | 147.17 | 140.81 | 0.00 | 0.00 | 0.00 |
April | 122.11 | 0.55 | 121.56 | 207.95 | 86.16 | 0.00 | 0.00 | 0.00 |
May | 139.44 | 6.24 | 133.20 | 291.33 | 43.69 | 0.00 | 0.00 | 0.00 |
June | 148.95 | 10.72 | 138.23 | 336.29 | 18.09 | 0.00 | 0.00 | 0.00 |
July | 150.73 | 7.39 | 143.35 | 354.76 | 26.77 | 0.00 | 0.00 | 0.00 |
August | 133.40 | 1.23 | 132.17 | 297.63 | 18.05 | 0.00 | 0.00 | 0.00 |
September | 118.34 | 0.01 | 118.33 | 276.69 | 31.81 | 0.00 | 0.00 | 0.00 |
October | 99.14 | 0.00 | 99.14 | 203.11 | 50.77 | 0.00 | 0.00 | 0.00 |
November | 86.20 | 0.00 | 86.20 | 140.07 | 105.80 | 0.00 | 0.00 | 0.00 |
December | 76.36 | 0.00 | 76.36 | 88.37 | 179.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.79 | 2.19 | 110.60 | 212.30 | 90.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.36 | 0.00 | 76.36 | 78.17 | 18.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 150.73 | 10.72 | 143.35 | 354.76 | 209.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.20 | 0.00 | 77.20 | 78.17 | 209.80 | 0.00 | 0.00 | 0.00 |
February | 91.37 | 0.00 | 91.37 | 120.78 | 173.69 | 0.00 | 0.00 | 0.00 |
March | 108.97 | 0.00 | 108.97 | 147.17 | 140.81 | 0.00 | 0.00 | 0.00 |
April | 122.11 | 0.55 | 121.56 | 207.95 | 86.16 | 0.00 | 0.00 | 0.00 |
May | 139.44 | 6.24 | 133.20 | 291.33 | 43.69 | 0.00 | 0.00 | 0.00 |
June | 148.95 | 10.72 | 138.23 | 336.29 | 18.09 | 0.00 | 0.00 | 0.00 |
July | 150.73 | 7.39 | 143.35 | 354.76 | 26.77 | 0.00 | 0.00 | 0.00 |
August | 133.40 | 1.23 | 132.17 | 297.63 | 18.05 | 0.00 | 0.00 | 0.00 |
September | 118.34 | 0.01 | 118.33 | 276.69 | 31.81 | 0.00 | 0.00 | 0.00 |
October | 99.14 | 0.00 | 99.14 | 203.11 | 50.77 | 0.00 | 0.00 | 0.00 |
November | 86.21 | 0.00 | 86.21 | 140.07 | 105.80 | 0.00 | 0.00 | 0.00 |
December | 76.36 | 0.00 | 76.36 | 88.37 | 179.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.79 | 2.19 | 110.60 | 212.30 | 90.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.36 | 0.00 | 76.36 | 78.17 | 18.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 150.73 | 10.72 | 143.35 | 354.76 | 209.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.20 | 0.00 | 77.20 | 78.17 | 209.80 | 0.00 | 0.00 | 0.00 |
February | 91.37 | 0.00 | 91.37 | 120.78 | 173.69 | 0.00 | 0.00 | 0.00 |
March | 108.97 | 0.00 | 108.97 | 147.17 | 140.81 | 0.00 | 0.00 | 0.00 |
April | 122.11 | 0.55 | 121.56 | 207.95 | 86.16 | 0.00 | 0.00 | 0.00 |
May | 139.44 | 6.24 | 133.20 | 291.33 | 43.69 | 0.00 | 0.00 | 0.00 |
June | 148.95 | 10.72 | 138.23 | 336.29 | 18.09 | 0.00 | 0.00 | 0.00 |
July | 150.73 | 7.39 | 143.35 | 354.76 | 26.77 | 0.00 | 0.00 | 0.00 |
August | 133.40 | 1.23 | 132.17 | 297.63 | 18.05 | 0.00 | 0.00 | 0.00 |
September | 118.34 | 0.01 | 118.33 | 276.69 | 31.81 | 0.00 | 0.00 | 0.00 |
October | 99.14 | 0.00 | 99.14 | 203.11 | 50.77 | 0.00 | 0.00 | 0.00 |
November | 86.20 | 0.00 | 86.20 | 140.07 | 105.80 | 0.00 | 0.00 | 0.00 |
December | 76.36 | 0.00 | 76.36 | 88.37 | 179.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.79 | 2.19 | 110.60 | 212.30 | 90.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.36 | 0.00 | 76.36 | 78.17 | 18.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 150.73 | 10.72 | 143.35 | 354.76 | 209.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.19 | 0.00 | 77.19 | 78.17 | 209.79 | 0.00 | 0.00 | 0.00 |
February | 91.37 | 0.00 | 91.37 | 120.77 | 173.69 | 0.00 | 0.00 | 0.00 |
March | 108.97 | 0.00 | 108.97 | 147.17 | 140.80 | 0.00 | 0.00 | 0.00 |
April | 122.10 | 0.55 | 121.55 | 207.94 | 86.15 | 0.00 | 0.00 | 0.00 |
May | 139.43 | 6.24 | 133.20 | 291.32 | 43.69 | 0.00 | 0.00 | 0.00 |
June | 148.94 | 10.72 | 138.22 | 336.27 | 18.09 | 0.00 | 0.00 | 0.00 |
July | 150.73 | 7.39 | 143.34 | 354.75 | 26.77 | 0.00 | 0.00 | 0.00 |
August | 133.40 | 1.23 | 132.17 | 297.62 | 18.05 | 0.00 | 0.00 | 0.00 |
September | 118.34 | 0.01 | 118.33 | 276.68 | 31.81 | 0.00 | 0.00 | 0.00 |
October | 99.14 | 0.00 | 99.14 | 203.10 | 50.77 | 0.00 | 0.00 | 0.00 |
November | 86.20 | 0.00 | 86.20 | 140.07 | 105.80 | 0.00 | 0.00 | 0.00 |
December | 76.35 | 0.00 | 76.35 | 88.37 | 179.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.79 | 2.19 | 110.60 | 212.29 | 90.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.35 | 0.00 | 76.35 | 78.17 | 18.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 150.73 | 10.72 | 143.34 | 354.75 | 209.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 206.53 | 98.94 | 107.59 | 295.26 | 215.07 | 0.00 | 0.00 | 0.00 |
February | 238.48 | 110.39 | 128.09 | 372.93 | 176.76 | 0.00 | 0.00 | 0.00 |
March | 291.16 | 137.65 | 153.51 | 461.41 | 138.63 | 0.00 | 0.00 | 0.00 |
April | 315.98 | 140.99 | 174.99 | 562.94 | 89.94 | 0.00 | 0.00 | 0.00 |
May | 298.93 | 119.04 | 179.89 | 584.12 | 46.06 | 0.00 | 0.00 | 0.00 |
June | 295.05 | 113.33 | 181.72 | 609.10 | 17.89 | 0.00 | 0.00 | 0.00 |
July | 303.17 | 109.33 | 193.84 | 645.40 | 26.74 | 0.00 | 0.00 | 0.00 |
August | 277.22 | 92.70 | 184.52 | 575.08 | 15.15 | 0.00 | 0.00 | 0.00 |
September | 267.26 | 96.62 | 170.64 | 560.40 | 34.81 | 0.00 | 0.00 | 0.00 |
October | 246.00 | 105.94 | 140.06 | 478.38 | 52.80 | 0.00 | 0.00 | 0.00 |
November | 199.66 | 79.61 | 120.05 | 345.44 | 104.52 | 0.00 | 0.00 | 0.00 |
December | 161.28 | 56.94 | 104.34 | 237.48 | 179.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.44 | 105.05 | 153.38 | 477.72 | 91.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.28 | 56.94 | 104.34 | 237.48 | 15.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 315.98 | 140.99 | 193.84 | 645.40 | 215.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 206.53 | 98.94 | 107.59 | 295.26 | 215.07 | 0.00 | 0.00 | 0.00 |
February | 238.48 | 110.39 | 128.09 | 372.93 | 176.76 | 0.00 | 0.00 | 0.00 |
March | 291.16 | 137.65 | 153.51 | 461.41 | 138.63 | 0.00 | 0.00 | 0.00 |
April | 315.98 | 140.99 | 174.99 | 562.94 | 89.94 | 0.00 | 0.00 | 0.00 |
May | 298.93 | 119.04 | 179.89 | 584.12 | 46.06 | 0.00 | 0.00 | 0.00 |
June | 295.05 | 113.33 | 181.72 | 609.10 | 17.89 | 0.00 | 0.00 | 0.00 |
July | 303.17 | 109.33 | 193.84 | 645.40 | 26.74 | 0.00 | 0.00 | 0.00 |
August | 277.22 | 92.70 | 184.52 | 575.08 | 15.15 | 0.00 | 0.00 | 0.00 |
September | 267.26 | 96.62 | 170.64 | 560.40 | 34.81 | 0.00 | 0.00 | 0.00 |
October | 246.00 | 105.94 | 140.06 | 478.38 | 52.80 | 0.00 | 0.00 | 0.00 |
November | 199.66 | 79.61 | 120.05 | 345.44 | 104.52 | 0.00 | 0.00 | 0.00 |
December | 161.28 | 56.94 | 104.34 | 237.48 | 179.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.44 | 105.05 | 153.38 | 477.72 | 91.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.28 | 56.94 | 104.34 | 237.48 | 15.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 315.98 | 140.99 | 193.84 | 645.40 | 215.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 206.53 | 98.94 | 107.59 | 295.25 | 215.07 | 0.00 | 0.00 | 0.00 |
February | 238.47 | 110.39 | 128.08 | 372.93 | 176.76 | 0.00 | 0.00 | 0.00 |
March | 291.16 | 137.65 | 153.51 | 461.40 | 138.63 | 0.00 | 0.00 | 0.00 |
April | 315.98 | 140.99 | 174.99 | 562.93 | 89.94 | 0.00 | 0.00 | 0.00 |
May | 298.93 | 119.04 | 179.89 | 584.11 | 46.06 | 0.00 | 0.00 | 0.00 |
June | 295.05 | 113.33 | 181.72 | 609.08 | 17.89 | 0.00 | 0.00 | 0.00 |
July | 303.16 | 109.33 | 193.84 | 645.39 | 26.73 | 0.00 | 0.00 | 0.00 |
August | 277.22 | 92.70 | 184.52 | 575.07 | 15.15 | 0.00 | 0.00 | 0.00 |
September | 267.25 | 96.61 | 170.64 | 560.39 | 34.81 | 0.00 | 0.00 | 0.00 |
October | 246.00 | 105.94 | 140.06 | 478.37 | 52.79 | 0.00 | 0.00 | 0.00 |
November | 199.66 | 79.61 | 120.05 | 345.43 | 104.52 | 0.00 | 0.00 | 0.00 |
December | 161.28 | 56.94 | 104.34 | 237.47 | 179.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.43 | 105.05 | 153.38 | 477.72 | 91.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.28 | 56.94 | 104.34 | 237.47 | 15.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 315.98 | 140.99 | 193.84 | 645.39 | 215.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.82 | 235.71 | 127.10 | 582.51 | 199.49 | 0.00 | 0.00 | 0.00 |
February | 328.22 | 189.92 | 138.31 | 557.44 | 169.56 | 0.00 | 0.00 | 0.00 |
March | 252.00 | 106.54 | 145.46 | 434.28 | 138.29 | 0.00 | 0.00 | 0.00 |
April | 171.36 | 30.05 | 141.31 | 325.72 | 90.48 | 0.00 | 0.00 | 0.00 |
May | 137.31 | 2.97 | 134.34 | 288.19 | 43.24 | 0.00 | 0.00 | 0.00 |
June | 130.92 | 0.25 | 130.67 | 296.89 | 18.40 | 0.00 | 0.00 | 0.00 |
July | 140.18 | 1.30 | 138.88 | 331.58 | 26.89 | 0.00 | 0.00 | 0.00 |
August | 159.10 | 13.43 | 145.67 | 357.64 | 18.72 | 0.00 | 0.00 | 0.00 |
September | 203.66 | 49.91 | 153.76 | 456.29 | 34.56 | 0.00 | 0.00 | 0.00 |
October | 280.08 | 131.40 | 148.67 | 555.54 | 58.15 | 0.00 | 0.00 | 0.00 |
November | 318.67 | 177.85 | 140.82 | 564.90 | 107.13 | 0.00 | 0.00 | 0.00 |
December | 349.65 | 220.54 | 129.11 | 574.54 | 175.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 235.73 | 96.24 | 139.49 | 443.22 | 89.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.92 | 0.25 | 127.10 | 288.19 | 18.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.82 | 235.71 | 153.76 | 582.51 | 199.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.81 | 235.71 | 127.10 | 582.51 | 199.49 | 0.00 | 0.00 | 0.00 |
February | 328.22 | 189.91 | 138.30 | 557.43 | 169.56 | 0.00 | 0.00 | 0.00 |
March | 252.00 | 106.54 | 145.46 | 434.28 | 138.29 | 0.00 | 0.00 | 0.00 |
April | 171.35 | 30.05 | 141.31 | 325.72 | 90.48 | 0.00 | 0.00 | 0.00 |
May | 137.31 | 2.97 | 134.34 | 288.19 | 43.24 | 0.00 | 0.00 | 0.00 |
June | 130.92 | 0.25 | 130.67 | 296.88 | 18.40 | 0.00 | 0.00 | 0.00 |
July | 140.18 | 1.30 | 138.88 | 331.58 | 26.89 | 0.00 | 0.00 | 0.00 |
August | 159.09 | 13.43 | 145.67 | 357.64 | 18.72 | 0.00 | 0.00 | 0.00 |
September | 203.66 | 49.91 | 153.75 | 456.29 | 34.56 | 0.00 | 0.00 | 0.00 |
October | 280.07 | 131.40 | 148.67 | 555.54 | 58.15 | 0.00 | 0.00 | 0.00 |
November | 318.66 | 177.85 | 140.81 | 564.90 | 107.13 | 0.00 | 0.00 | 0.00 |
December | 349.65 | 220.54 | 129.11 | 574.54 | 175.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 235.73 | 96.24 | 139.49 | 443.22 | 89.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.92 | 0.25 | 127.10 | 288.19 | 18.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.81 | 235.71 | 153.75 | 582.51 | 199.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.82 | 235.71 | 127.10 | 582.51 | 199.49 | 0.00 | 0.00 | 0.00 |
February | 328.22 | 189.92 | 138.31 | 557.44 | 169.56 | 0.00 | 0.00 | 0.00 |
March | 252.00 | 106.54 | 145.46 | 434.28 | 138.29 | 0.00 | 0.00 | 0.00 |
April | 171.36 | 30.05 | 141.31 | 325.72 | 90.48 | 0.00 | 0.00 | 0.00 |
May | 137.31 | 2.97 | 134.34 | 288.19 | 43.24 | 0.00 | 0.00 | 0.00 |
June | 130.92 | 0.25 | 130.67 | 296.89 | 18.40 | 0.00 | 0.00 | 0.00 |
July | 140.18 | 1.30 | 138.88 | 331.58 | 26.89 | 0.00 | 0.00 | 0.00 |
August | 159.10 | 13.43 | 145.67 | 357.64 | 18.72 | 0.00 | 0.00 | 0.00 |
September | 203.66 | 49.91 | 153.76 | 456.29 | 34.56 | 0.00 | 0.00 | 0.00 |
October | 280.08 | 131.40 | 148.67 | 555.54 | 58.15 | 0.00 | 0.00 | 0.00 |
November | 318.67 | 177.85 | 140.82 | 564.90 | 107.13 | 0.00 | 0.00 | 0.00 |
December | 349.65 | 220.54 | 129.11 | 574.54 | 175.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 235.73 | 96.24 | 139.49 | 443.22 | 89.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.92 | 0.25 | 127.10 | 288.19 | 18.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.82 | 235.71 | 153.76 | 582.51 | 199.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.81 | 235.71 | 127.10 | 582.51 | 199.49 | 0.00 | 0.00 | 0.00 |
February | 328.22 | 189.91 | 138.30 | 557.43 | 169.56 | 0.00 | 0.00 | 0.00 |
March | 252.00 | 106.54 | 145.46 | 434.28 | 138.29 | 0.00 | 0.00 | 0.00 |
April | 171.35 | 30.05 | 141.31 | 325.72 | 90.48 | 0.00 | 0.00 | 0.00 |
May | 137.31 | 2.97 | 134.34 | 288.19 | 43.24 | 0.00 | 0.00 | 0.00 |
June | 130.92 | 0.25 | 130.67 | 296.88 | 18.40 | 0.00 | 0.00 | 0.00 |
July | 140.18 | 1.30 | 138.88 | 331.58 | 26.89 | 0.00 | 0.00 | 0.00 |
August | 159.09 | 13.43 | 145.67 | 357.64 | 18.72 | 0.00 | 0.00 | 0.00 |
September | 203.66 | 49.91 | 153.75 | 456.29 | 34.56 | 0.00 | 0.00 | 0.00 |
October | 280.07 | 131.40 | 148.67 | 555.54 | 58.15 | 0.00 | 0.00 | 0.00 |
November | 318.66 | 177.85 | 140.81 | 564.90 | 107.13 | 0.00 | 0.00 | 0.00 |
December | 349.65 | 220.54 | 129.11 | 574.54 | 175.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 235.73 | 96.24 | 139.49 | 443.22 | 89.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.92 | 0.25 | 127.10 | 288.19 | 18.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.81 | 235.71 | 153.75 | 582.51 | 199.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.80 | 235.70 | 127.10 | 582.49 | 199.48 | 0.00 | 0.00 | 0.00 |
February | 328.21 | 189.91 | 138.30 | 557.41 | 169.55 | 0.00 | 0.00 | 0.00 |
March | 251.99 | 106.54 | 145.45 | 434.26 | 138.28 | 0.00 | 0.00 | 0.00 |
April | 171.35 | 30.05 | 141.30 | 325.71 | 90.48 | 0.00 | 0.00 | 0.00 |
May | 137.31 | 2.97 | 134.34 | 288.18 | 43.24 | 0.00 | 0.00 | 0.00 |
June | 130.91 | 0.25 | 130.66 | 296.87 | 18.40 | 0.00 | 0.00 | 0.00 |
July | 140.17 | 1.30 | 138.87 | 331.56 | 26.89 | 0.00 | 0.00 | 0.00 |
August | 159.09 | 13.42 | 145.66 | 357.63 | 18.72 | 0.00 | 0.00 | 0.00 |
September | 203.65 | 49.91 | 153.75 | 456.27 | 34.56 | 0.00 | 0.00 | 0.00 |
October | 280.06 | 131.40 | 148.67 | 555.52 | 58.15 | 0.00 | 0.00 | 0.00 |
November | 318.65 | 177.84 | 140.81 | 564.88 | 107.13 | 0.00 | 0.00 | 0.00 |
December | 349.64 | 220.53 | 129.11 | 574.52 | 175.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 235.72 | 96.24 | 139.49 | 443.20 | 89.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 130.91 | 0.25 | 127.10 | 288.18 | 18.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.80 | 235.70 | 153.75 | 582.49 | 199.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 185.53 | 79.99 | 105.55 | 262.24 | 253.32 | 0.00 | 0.00 | 0.00 |
February | 232.01 | 105.00 | 127.01 | 364.77 | 224.36 | 0.00 | 0.00 | 0.00 |
March | 288.92 | 131.94 | 156.98 | 457.50 | 192.27 | 0.00 | 0.00 | 0.00 |
April | 318.02 | 147.25 | 170.76 | 550.61 | 134.93 | 0.00 | 0.00 | 0.00 |
May | 289.91 | 111.60 | 178.31 | 562.54 | 67.76 | 0.00 | 0.00 | 0.00 |
June | 245.64 | 68.91 | 176.74 | 500.46 | 36.10 | 0.00 | 0.00 | 0.00 |
July | 274.53 | 84.93 | 189.60 | 572.61 | 51.92 | 0.00 | 0.00 | 0.00 |
August | 273.91 | 89.27 | 184.64 | 542.27 | 47.42 | 0.00 | 0.00 | 0.00 |
September | 233.66 | 68.90 | 164.76 | 486.32 | 48.23 | 0.00 | 0.00 | 0.00 |
October | 232.44 | 90.61 | 141.83 | 443.13 | 82.93 | 0.00 | 0.00 | 0.00 |
November | 191.74 | 70.33 | 121.41 | 323.91 | 152.00 | 0.00 | 0.00 | 0.00 |
December | 192.09 | 85.88 | 106.21 | 281.75 | 241.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.64 | 94.53 | 152.12 | 446.13 | 127.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 185.53 | 68.90 | 105.55 | 262.24 | 36.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 318.02 | 147.25 | 189.60 | 572.61 | 253.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 185.53 | 79.99 | 105.55 | 262.24 | 253.32 | 0.00 | 0.00 | 0.00 |
February | 232.01 | 105.00 | 127.01 | 364.77 | 224.36 | 0.00 | 0.00 | 0.00 |
March | 288.92 | 131.94 | 156.98 | 457.50 | 192.27 | 0.00 | 0.00 | 0.00 |
April | 318.02 | 147.25 | 170.76 | 550.61 | 134.93 | 0.00 | 0.00 | 0.00 |
May | 289.91 | 111.60 | 178.31 | 562.54 | 67.76 | 0.00 | 0.00 | 0.00 |
June | 245.64 | 68.91 | 176.74 | 500.46 | 36.10 | 0.00 | 0.00 | 0.00 |
July | 274.53 | 84.93 | 189.60 | 572.61 | 51.92 | 0.00 | 0.00 | 0.00 |
August | 273.91 | 89.27 | 184.64 | 542.27 | 47.42 | 0.00 | 0.00 | 0.00 |
September | 233.66 | 68.90 | 164.76 | 486.32 | 48.23 | 0.00 | 0.00 | 0.00 |
October | 232.44 | 90.61 | 141.83 | 443.13 | 82.93 | 0.00 | 0.00 | 0.00 |
November | 191.74 | 70.33 | 121.41 | 323.91 | 152.00 | 0.00 | 0.00 | 0.00 |
December | 192.09 | 85.88 | 106.21 | 281.75 | 241.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.64 | 94.53 | 152.12 | 446.13 | 127.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 185.53 | 68.90 | 105.55 | 262.24 | 36.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 318.02 | 147.25 | 189.60 | 572.61 | 253.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 185.53 | 79.99 | 105.55 | 262.24 | 253.32 | 0.00 | 0.00 | 0.00 |
February | 232.00 | 104.99 | 127.01 | 364.77 | 224.36 | 0.00 | 0.00 | 0.00 |
March | 288.91 | 131.93 | 156.98 | 457.49 | 192.26 | 0.00 | 0.00 | 0.00 |
April | 318.01 | 147.25 | 170.76 | 550.60 | 134.92 | 0.00 | 0.00 | 0.00 |
May | 289.91 | 111.60 | 178.31 | 562.53 | 67.76 | 0.00 | 0.00 | 0.00 |
June | 245.64 | 68.90 | 176.74 | 500.46 | 36.10 | 0.00 | 0.00 | 0.00 |
July | 274.53 | 84.93 | 189.60 | 572.60 | 51.92 | 0.00 | 0.00 | 0.00 |
August | 273.90 | 89.26 | 184.64 | 542.26 | 47.42 | 0.00 | 0.00 | 0.00 |
September | 233.65 | 68.90 | 164.76 | 486.31 | 48.23 | 0.00 | 0.00 | 0.00 |
October | 232.44 | 90.61 | 141.83 | 443.12 | 82.93 | 0.00 | 0.00 | 0.00 |
November | 191.74 | 70.33 | 121.41 | 323.91 | 152.00 | 0.00 | 0.00 | 0.00 |
December | 192.08 | 85.88 | 106.20 | 281.74 | 241.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.64 | 94.52 | 152.12 | 446.12 | 127.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 185.53 | 68.90 | 105.55 | 262.24 | 36.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 318.01 | 147.25 | 189.60 | 572.60 | 253.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 385.99 | 0.00 | 385.99 | 419.10 | 951.92 | 0.00 | 0.00 | 0.00 |
February | 456.88 | 0.00 | 456.88 | 632.34 | 786.61 | 0.00 | 0.00 | 0.00 |
March | 544.86 | 0.00 | 544.86 | 752.02 | 655.36 | 0.00 | 0.00 | 0.00 |
April | 610.54 | 2.74 | 607.80 | 1055.52 | 412.94 | 0.00 | 0.00 | 0.00 |
May | 697.20 | 31.19 | 666.02 | 1459.96 | 213.09 | 0.00 | 0.00 | 0.00 |
June | 744.76 | 53.63 | 691.14 | 1685.29 | 95.46 | 0.00 | 0.00 | 0.00 |
July | 753.67 | 36.93 | 716.74 | 1788.82 | 136.40 | 0.00 | 0.00 | 0.00 |
August | 667.01 | 6.13 | 660.88 | 1512.73 | 88.18 | 0.00 | 0.00 | 0.00 |
September | 591.72 | 0.05 | 591.67 | 1395.23 | 155.10 | 0.00 | 0.00 | 0.00 |
October | 495.72 | 0.00 | 495.72 | 1028.76 | 242.14 | 0.00 | 0.00 | 0.00 |
November | 431.03 | 0.00 | 431.03 | 719.15 | 484.89 | 0.00 | 0.00 | 0.00 |
December | 381.79 | 0.00 | 381.79 | 471.09 | 809.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 563.97 | 10.94 | 553.02 | 1078.82 | 417.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 381.79 | 0.00 | 381.79 | 419.10 | 88.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 753.67 | 53.63 | 716.74 | 1788.82 | 951.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 619.59 | 296.82 | 322.77 | 887.42 | 612.24 | 0.00 | 0.00 | 0.00 |
February | 715.42 | 331.17 | 384.25 | 1114.53 | 507.55 | 0.00 | 0.00 | 0.00 |
March | 873.48 | 412.94 | 460.53 | 1365.04 | 417.67 | 0.00 | 0.00 | 0.00 |
April | 947.94 | 422.97 | 524.97 | 1665.53 | 287.81 | 0.00 | 0.00 | 0.00 |
May | 896.79 | 357.12 | 539.67 | 1734.73 | 143.54 | 0.00 | 0.00 | 0.00 |
June | 885.15 | 339.98 | 545.17 | 1805.33 | 65.89 | 0.00 | 0.00 | 0.00 |
July | 909.50 | 327.98 | 581.51 | 1919.69 | 98.29 | 0.00 | 0.00 | 0.00 |
August | 831.66 | 278.09 | 553.57 | 1709.89 | 61.93 | 0.00 | 0.00 | 0.00 |
September | 801.77 | 289.84 | 511.93 | 1666.90 | 110.04 | 0.00 | 0.00 | 0.00 |
October | 738.00 | 317.83 | 420.17 | 1421.85 | 170.25 | 0.00 | 0.00 | 0.00 |
November | 598.98 | 238.84 | 360.14 | 1027.39 | 313.86 | 0.00 | 0.00 | 0.00 |
December | 483.85 | 170.82 | 313.03 | 711.50 | 525.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 775.30 | 315.15 | 460.15 | 1420.32 | 275.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 483.85 | 170.82 | 313.03 | 711.50 | 61.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 947.94 | 422.97 | 581.51 | 1919.69 | 612.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1814.11 | 1178.59 | 635.52 | 2882.25 | 983.01 | 0.00 | 0.00 | 0.00 |
February | 1641.13 | 949.60 | 691.53 | 2760.99 | 828.04 | 0.00 | 0.00 | 0.00 |
March | 1260.02 | 532.72 | 727.29 | 2151.79 | 679.03 | 0.00 | 0.00 | 0.00 |
April | 856.79 | 150.25 | 706.54 | 1627.80 | 444.72 | 0.00 | 0.00 | 0.00 |
May | 686.58 | 14.85 | 671.72 | 1445.33 | 208.23 | 0.00 | 0.00 | 0.00 |
June | 654.59 | 1.24 | 653.36 | 1495.99 | 94.36 | 0.00 | 0.00 | 0.00 |
July | 700.89 | 6.50 | 694.39 | 1676.85 | 134.60 | 0.00 | 0.00 | 0.00 |
August | 795.49 | 67.13 | 728.36 | 1806.53 | 93.49 | 0.00 | 0.00 | 0.00 |
September | 1018.33 | 249.54 | 768.79 | 2273.95 | 173.86 | 0.00 | 0.00 | 0.00 |
October | 1400.41 | 657.03 | 743.38 | 2756.79 | 297.06 | 0.00 | 0.00 | 0.00 |
November | 1593.35 | 889.27 | 704.09 | 2799.36 | 530.92 | 0.00 | 0.00 | 0.00 |
December | 1748.30 | 1102.73 | 645.57 | 2848.67 | 865.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1178.69 | 481.21 | 697.48 | 2207.77 | 442.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 654.59 | 1.24 | 635.52 | 1445.33 | 93.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1814.11 | 1178.59 | 768.79 | 2882.25 | 983.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 556.60 | 239.96 | 316.64 | 807.57 | 673.56 | 0.00 | 0.00 | 0.00 |
February | 696.01 | 314.99 | 381.03 | 1122.34 | 578.93 | 0.00 | 0.00 | 0.00 |
March | 866.75 | 395.80 | 470.95 | 1397.34 | 495.85 | 0.00 | 0.00 | 0.00 |
April | 954.04 | 441.75 | 512.29 | 1687.71 | 342.02 | 0.00 | 0.00 | 0.00 |
May | 869.73 | 334.81 | 534.92 | 1695.41 | 182.04 | 0.00 | 0.00 | 0.00 |
June | 736.93 | 206.71 | 530.21 | 1529.62 | 86.13 | 0.00 | 0.00 | 0.00 |
July | 823.58 | 254.79 | 568.79 | 1756.24 | 122.45 | 0.00 | 0.00 | 0.00 |
August | 821.71 | 267.79 | 553.92 | 1676.63 | 91.63 | 0.00 | 0.00 | 0.00 |
September | 700.96 | 206.69 | 494.27 | 1474.90 | 126.37 | 0.00 | 0.00 | 0.00 |
October | 697.33 | 271.84 | 425.49 | 1350.83 | 207.47 | 0.00 | 0.00 | 0.00 |
November | 575.22 | 210.99 | 364.23 | 1005.19 | 367.99 | 0.00 | 0.00 | 0.00 |
December | 576.25 | 257.64 | 318.61 | 884.81 | 590.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 739.93 | 283.58 | 456.35 | 1367.07 | 320.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 556.60 | 206.69 | 316.64 | 807.57 | 86.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 954.04 | 441.75 | 568.79 | 1756.24 | 673.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 385.99 | 0.00 | 385.99 | 438.52 | 873.77 | 0.00 | 0.00 | 0.00 |
February | 456.88 | 0.00 | 456.88 | 639.33 | 741.04 | 0.00 | 0.00 | 0.00 |
March | 544.86 | 0.00 | 544.86 | 746.91 | 629.50 | 0.00 | 0.00 | 0.00 |
April | 610.54 | 2.74 | 607.80 | 1033.97 | 415.72 | 0.00 | 0.00 | 0.00 |
May | 697.20 | 31.19 | 666.02 | 1430.36 | 226.59 | 0.00 | 0.00 | 0.00 |
June | 744.76 | 53.63 | 691.14 | 1647.37 | 104.62 | 0.00 | 0.00 | 0.00 |
July | 753.67 | 36.93 | 716.74 | 1749.51 | 151.71 | 0.00 | 0.00 | 0.00 |
August | 667.01 | 6.13 | 660.88 | 1481.94 | 97.97 | 0.00 | 0.00 | 0.00 |
September | 591.72 | 0.05 | 591.67 | 1358.90 | 161.84 | 0.00 | 0.00 | 0.00 |
October | 495.72 | 0.00 | 495.72 | 1008.79 | 247.43 | 0.00 | 0.00 | 0.00 |
November | 431.03 | 0.00 | 431.03 | 715.99 | 460.56 | 0.00 | 0.00 | 0.00 |
December | 381.79 | 0.00 | 381.79 | 483.39 | 750.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 563.97 | 10.94 | 553.02 | 1063.32 | 403.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 381.79 | 0.00 | 381.79 | 438.52 | 97.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 753.67 | 53.63 | 716.74 | 1749.51 | 873.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 619.59 | 296.82 | 322.77 | 899.29 | 575.12 | 0.00 | 0.00 | 0.00 |
February | 715.42 | 331.17 | 384.25 | 1117.01 | 485.98 | 0.00 | 0.00 | 0.00 |
March | 873.48 | 412.94 | 460.53 | 1356.26 | 408.51 | 0.00 | 0.00 | 0.00 |
April | 947.94 | 422.97 | 524.97 | 1647.51 | 291.35 | 0.00 | 0.00 | 0.00 |
May | 896.79 | 357.12 | 539.67 | 1712.10 | 152.38 | 0.00 | 0.00 | 0.00 |
June | 885.15 | 339.98 | 545.17 | 1778.58 | 71.60 | 0.00 | 0.00 | 0.00 |
July | 909.50 | 327.98 | 581.51 | 1892.90 | 107.79 | 0.00 | 0.00 | 0.00 |
August | 831.66 | 278.09 | 553.57 | 1687.58 | 67.98 | 0.00 | 0.00 | 0.00 |
September | 801.77 | 289.84 | 511.93 | 1641.76 | 114.47 | 0.00 | 0.00 | 0.00 |
October | 738.00 | 317.83 | 420.17 | 1406.03 | 174.56 | 0.00 | 0.00 | 0.00 |
November | 598.98 | 238.84 | 360.14 | 1022.98 | 302.69 | 0.00 | 0.00 | 0.00 |
December | 483.85 | 170.82 | 313.03 | 718.60 | 495.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 775.30 | 315.15 | 460.15 | 1407.83 | 269.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 483.85 | 170.82 | 313.03 | 718.60 | 67.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 947.94 | 422.97 | 581.51 | 1892.90 | 575.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1814.11 | 1178.59 | 635.52 | 2894.27 | 931.16 | 0.00 | 0.00 | 0.00 |
February | 1641.13 | 949.60 | 691.53 | 2760.03 | 796.90 | 0.00 | 0.00 | 0.00 |
March | 1260.02 | 532.72 | 727.29 | 2138.28 | 662.76 | 0.00 | 0.00 | 0.00 |
April | 856.79 | 150.25 | 706.54 | 1604.11 | 449.09 | 0.00 | 0.00 | 0.00 |
May | 686.58 | 14.85 | 671.72 | 1414.92 | 221.10 | 0.00 | 0.00 | 0.00 |
June | 654.59 | 1.24 | 653.36 | 1458.46 | 103.29 | 0.00 | 0.00 | 0.00 |
July | 700.89 | 6.50 | 694.39 | 1637.23 | 149.75 | 0.00 | 0.00 | 0.00 |
August | 795.49 | 67.13 | 728.36 | 1774.04 | 102.96 | 0.00 | 0.00 | 0.00 |
September | 1018.33 | 249.54 | 768.79 | 2238.03 | 181.64 | 0.00 | 0.00 | 0.00 |
October | 1400.41 | 657.03 | 743.38 | 2735.10 | 304.14 | 0.00 | 0.00 | 0.00 |
November | 1593.35 | 889.27 | 704.09 | 2791.73 | 516.16 | 0.00 | 0.00 | 0.00 |
December | 1748.30 | 1102.73 | 645.57 | 2851.08 | 825.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1178.69 | 481.21 | 697.48 | 2188.61 | 435.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 654.59 | 1.24 | 635.52 | 1414.92 | 102.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1814.11 | 1178.59 | 768.79 | 2894.27 | 931.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 556.60 | 239.96 | 316.64 | 815.55 | 629.31 | 0.00 | 0.00 | 0.00 |
February | 696.01 | 314.99 | 381.03 | 1121.76 | 554.07 | 0.00 | 0.00 | 0.00 |
March | 866.75 | 395.80 | 470.95 | 1389.09 | 481.45 | 0.00 | 0.00 | 0.00 |
April | 954.04 | 441.75 | 512.29 | 1671.77 | 342.97 | 0.00 | 0.00 | 0.00 |
May | 869.73 | 334.81 | 534.92 | 1676.28 | 188.84 | 0.00 | 0.00 | 0.00 |
June | 736.93 | 206.71 | 530.21 | 1508.47 | 90.85 | 0.00 | 0.00 | 0.00 |
July | 823.58 | 254.79 | 568.79 | 1733.70 | 129.00 | 0.00 | 0.00 | 0.00 |
August | 821.71 | 267.79 | 553.92 | 1658.25 | 97.13 | 0.00 | 0.00 | 0.00 |
September | 700.96 | 206.69 | 494.27 | 1455.53 | 129.77 | 0.00 | 0.00 | 0.00 |
October | 697.33 | 271.84 | 425.49 | 1337.85 | 209.45 | 0.00 | 0.00 | 0.00 |
November | 575.22 | 210.99 | 364.23 | 1000.73 | 354.48 | 0.00 | 0.00 | 0.00 |
December | 576.25 | 257.64 | 318.61 | 888.66 | 557.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 739.93 | 283.58 | 456.35 | 1356.12 | 312.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 556.60 | 206.69 | 316.64 | 815.55 | 90.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 954.04 | 441.75 | 568.79 | 1733.70 | 629.31 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206765E+09 | 0.00 | 0.206765E+09 | 0.209372E+09 | 0.561930E+09 |
February | 0.221055E+09 | 0.00 | 0.221055E+09 | 0.292189E+09 | 0.420204E+09 |
March | 0.291870E+09 | 0.00 | 0.291870E+09 | 0.394189E+09 | 0.377148E+09 |
April | 0.316503E+09 | 1421757.78 | 0.315082E+09 | 0.539005E+09 | 0.223321E+09 |
May | 0.373478E+09 | 16706433.35 | 0.356772E+09 | 0.780313E+09 | 0.117020E+09 |
June | 0.386085E+09 | 27799119.40 | 0.358286E+09 | 0.871666E+09 | 46883583.79 |
July | 0.403728E+09 | 19783349.91 | 0.383945E+09 | 0.950201E+09 | 71699288.33 |
August | 0.357305E+09 | 3286205.83 | 0.354019E+09 | 0.797184E+09 | 48338023.73 |
September | 0.306748E+09 | 24266.49 | 0.306724E+09 | 0.717191E+09 | 82464007.42 |
October | 0.265546E+09 | 0.00 | 0.265546E+09 | 0.544017E+09 | 0.135986E+09 |
November | 0.223446E+09 | 0.00 | 0.223446E+09 | 0.363076E+09 | 0.274248E+09 |
December | 0.204517E+09 | 0.00 | 0.204517E+09 | 0.236702E+09 | 0.481494E+09 |
Annual Sum or Average | 0.355705E+10 | 69021132.76 | 0.348803E+10 | 0.669510E+10 | 0.284074E+10 |
Minimum of Months | 0.204517E+09 | 0.00 | 0.204517E+09 | 0.209372E+09 | 46883583.79 |
Maximum of Months | 0.403728E+09 | 27799119.40 | 0.383945E+09 | 0.950201E+09 | 0.561930E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206762E+09 | 0.00 | 0.206762E+09 | 0.209369E+09 | 0.561928E+09 |
February | 0.221052E+09 | 0.00 | 0.221052E+09 | 0.292185E+09 | 0.420202E+09 |
March | 0.291866E+09 | 0.00 | 0.291866E+09 | 0.394184E+09 | 0.377145E+09 |
April | 0.316499E+09 | 1421726.53 | 0.315078E+09 | 0.538999E+09 | 0.223319E+09 |
May | 0.373473E+09 | 16706066.08 | 0.356767E+09 | 0.780304E+09 | 0.117019E+09 |
June | 0.386079E+09 | 27798508.27 | 0.358281E+09 | 0.871657E+09 | 46882547.88 |
July | 0.403722E+09 | 19782915.00 | 0.383940E+09 | 0.950191E+09 | 71697787.34 |
August | 0.357300E+09 | 3286133.58 | 0.354014E+09 | 0.797177E+09 | 48336742.45 |
September | 0.306744E+09 | 24265.96 | 0.306720E+09 | 0.717185E+09 | 82462733.00 |
October | 0.265542E+09 | 0.00 | 0.265542E+09 | 0.544012E+09 | 0.135984E+09 |
November | 0.223442E+09 | 0.00 | 0.223442E+09 | 0.363071E+09 | 0.274246E+09 |
December | 0.204514E+09 | 0.00 | 0.204514E+09 | 0.236699E+09 | 0.481492E+09 |
Annual Sum or Average | 0.355700E+10 | 69019615.42 | 0.348798E+10 | 0.669503E+10 | 0.284071E+10 |
Minimum of Months | 0.204514E+09 | 0.00 | 0.204514E+09 | 0.209369E+09 | 46882547.88 |
Maximum of Months | 0.403722E+09 | 27798508.27 | 0.383940E+09 | 0.950191E+09 | 0.561928E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206763E+09 | 0.00 | 0.206763E+09 | 0.209370E+09 | 0.561929E+09 |
February | 0.221053E+09 | 0.00 | 0.221053E+09 | 0.292186E+09 | 0.420203E+09 |
March | 0.291867E+09 | 0.00 | 0.291867E+09 | 0.394185E+09 | 0.377146E+09 |
April | 0.316501E+09 | 1421736.94 | 0.315079E+09 | 0.539001E+09 | 0.223320E+09 |
May | 0.373475E+09 | 16706188.50 | 0.356768E+09 | 0.780307E+09 | 0.117019E+09 |
June | 0.386081E+09 | 27798711.98 | 0.358282E+09 | 0.871660E+09 | 46882893.18 |
July | 0.403724E+09 | 19783059.97 | 0.383941E+09 | 0.950195E+09 | 71698287.69 |
August | 0.357302E+09 | 3286157.66 | 0.354016E+09 | 0.797179E+09 | 48337169.55 |
September | 0.306745E+09 | 24266.13 | 0.306721E+09 | 0.717187E+09 | 82463157.80 |
October | 0.265544E+09 | 0.00 | 0.265544E+09 | 0.544013E+09 | 0.135985E+09 |
November | 0.223443E+09 | 0.00 | 0.223443E+09 | 0.363073E+09 | 0.274246E+09 |
December | 0.204515E+09 | 0.00 | 0.204515E+09 | 0.236700E+09 | 0.481492E+09 |
Annual Sum or Average | 0.355701E+10 | 69020121.20 | 0.348799E+10 | 0.669506E+10 | 0.284072E+10 |
Minimum of Months | 0.204515E+09 | 0.00 | 0.204515E+09 | 0.209370E+09 | 46882893.18 |
Maximum of Months | 0.403724E+09 | 27798711.98 | 0.383941E+09 | 0.950195E+09 | 0.561929E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206762E+09 | 0.00 | 0.206762E+09 | 0.209369E+09 | 0.561928E+09 |
February | 0.221052E+09 | 0.00 | 0.221052E+09 | 0.292185E+09 | 0.420202E+09 |
March | 0.291866E+09 | 0.00 | 0.291866E+09 | 0.394184E+09 | 0.377145E+09 |
April | 0.316499E+09 | 1421726.53 | 0.315078E+09 | 0.538999E+09 | 0.223319E+09 |
May | 0.373473E+09 | 16706066.08 | 0.356767E+09 | 0.780304E+09 | 0.117019E+09 |
June | 0.386079E+09 | 27798508.27 | 0.358281E+09 | 0.871657E+09 | 46882547.88 |
July | 0.403722E+09 | 19782915.00 | 0.383940E+09 | 0.950191E+09 | 71697787.34 |
August | 0.357300E+09 | 3286133.58 | 0.354014E+09 | 0.797177E+09 | 48336742.45 |
September | 0.306744E+09 | 24265.96 | 0.306720E+09 | 0.717185E+09 | 82462733.00 |
October | 0.265542E+09 | 0.00 | 0.265542E+09 | 0.544012E+09 | 0.135984E+09 |
November | 0.223442E+09 | 0.00 | 0.223442E+09 | 0.363071E+09 | 0.274246E+09 |
December | 0.204514E+09 | 0.00 | 0.204514E+09 | 0.236699E+09 | 0.481492E+09 |
Annual Sum or Average | 0.355700E+10 | 69019615.42 | 0.348798E+10 | 0.669503E+10 | 0.284071E+10 |
Minimum of Months | 0.204514E+09 | 0.00 | 0.204514E+09 | 0.209369E+09 | 46882547.88 |
Maximum of Months | 0.403722E+09 | 27798508.27 | 0.383940E+09 | 0.950191E+09 | 0.561928E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.206755E+09 | 0.00 | 0.206755E+09 | 0.209361E+09 | 0.561906E+09 |
February | 0.221044E+09 | 0.00 | 0.221044E+09 | 0.292174E+09 | 0.420185E+09 |
March | 0.291855E+09 | 0.00 | 0.291855E+09 | 0.394169E+09 | 0.377131E+09 |
April | 0.316487E+09 | 1421674.43 | 0.315066E+09 | 0.538978E+09 | 0.223311E+09 |
May | 0.373459E+09 | 16705453.96 | 0.356753E+09 | 0.780274E+09 | 0.117014E+09 |
June | 0.386065E+09 | 27797489.72 | 0.358267E+09 | 0.871623E+09 | 46880830.95 |
July | 0.403707E+09 | 19782190.14 | 0.383925E+09 | 0.950155E+09 | 71695147.77 |
August | 0.357287E+09 | 3286013.18 | 0.354001E+09 | 0.797146E+09 | 48335007.81 |
September | 0.306732E+09 | 24265.07 | 0.306708E+09 | 0.717157E+09 | 82459621.78 |
October | 0.265532E+09 | 0.00 | 0.265532E+09 | 0.543991E+09 | 0.135979E+09 |
November | 0.223434E+09 | 0.00 | 0.223434E+09 | 0.363058E+09 | 0.274235E+09 |
December | 0.204506E+09 | 0.00 | 0.204506E+09 | 0.236690E+09 | 0.481473E+09 |
Annual Sum or Average | 0.355686E+10 | 69017086.50 | 0.348784E+10 | 0.669477E+10 | 0.284060E+10 |
Minimum of Months | 0.204506E+09 | 0.00 | 0.204506E+09 | 0.209361E+09 | 46880830.95 |
Maximum of Months | 0.403707E+09 | 27797489.72 | 0.383925E+09 | 0.950155E+09 | 0.561906E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.553176E+09 | 0.265005E+09 | 0.288170E+09 | 0.790821E+09 | 0.576045E+09 |
February | 0.576922E+09 | 0.267058E+09 | 0.309864E+09 | 0.902203E+09 | 0.427626E+09 |
March | 0.779846E+09 | 0.368678E+09 | 0.411169E+09 | 0.123584E+10 | 0.371305E+09 |
April | 0.819030E+09 | 0.365447E+09 | 0.453582E+09 | 0.145915E+10 | 0.233117E+09 |
May | 0.800663E+09 | 0.318843E+09 | 0.481820E+09 | 0.156452E+10 | 0.123365E+09 |
June | 0.764775E+09 | 0.293745E+09 | 0.471030E+09 | 0.157878E+10 | 46365827.81 |
July | 0.812007E+09 | 0.292827E+09 | 0.519180E+09 | 0.172864E+10 | 71608090.96 |
August | 0.742510E+09 | 0.248280E+09 | 0.494230E+09 | 0.154030E+10 | 40567705.95 |
September | 0.692736E+09 | 0.250427E+09 | 0.442310E+09 | 0.145254E+10 | 90217535.62 |
October | 0.658890E+09 | 0.283758E+09 | 0.375132E+09 | 0.128129E+10 | 0.141407E+09 |
November | 0.517525E+09 | 0.206357E+09 | 0.311168E+09 | 0.895368E+09 | 0.270923E+09 |
December | 0.431983E+09 | 0.152511E+09 | 0.279472E+09 | 0.636059E+09 | 0.481821E+09 |
Annual Sum or Average | 0.815006E+10 | 0.331294E+10 | 0.483713E+10 | 0.150655E+11 | 0.287437E+10 |
Minimum of Months | 0.431983E+09 | 0.152511E+09 | 0.279472E+09 | 0.636059E+09 | 40567705.95 |
Maximum of Months | 0.819030E+09 | 0.368678E+09 | 0.519180E+09 | 0.172864E+10 | 0.576045E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.553176E+09 | 0.265005E+09 | 0.288170E+09 | 0.790821E+09 | 0.576045E+09 |
February | 0.576922E+09 | 0.267058E+09 | 0.309864E+09 | 0.902203E+09 | 0.427626E+09 |
March | 0.779846E+09 | 0.368678E+09 | 0.411169E+09 | 0.123584E+10 | 0.371305E+09 |
April | 0.819030E+09 | 0.365447E+09 | 0.453582E+09 | 0.145915E+10 | 0.233117E+09 |
May | 0.800663E+09 | 0.318843E+09 | 0.481820E+09 | 0.156452E+10 | 0.123365E+09 |
June | 0.764775E+09 | 0.293745E+09 | 0.471030E+09 | 0.157878E+10 | 46365827.81 |
July | 0.812007E+09 | 0.292827E+09 | 0.519180E+09 | 0.172864E+10 | 71608090.96 |
August | 0.742510E+09 | 0.248280E+09 | 0.494230E+09 | 0.154030E+10 | 40567705.95 |
September | 0.692736E+09 | 0.250427E+09 | 0.442310E+09 | 0.145254E+10 | 90217535.62 |
October | 0.658890E+09 | 0.283758E+09 | 0.375132E+09 | 0.128129E+10 | 0.141407E+09 |
November | 0.517525E+09 | 0.206357E+09 | 0.311168E+09 | 0.895368E+09 | 0.270923E+09 |
December | 0.431983E+09 | 0.152511E+09 | 0.279472E+09 | 0.636059E+09 | 0.481821E+09 |
Annual Sum or Average | 0.815006E+10 | 0.331294E+10 | 0.483713E+10 | 0.150655E+11 | 0.287437E+10 |
Minimum of Months | 0.431983E+09 | 0.152511E+09 | 0.279472E+09 | 0.636059E+09 | 40567705.95 |
Maximum of Months | 0.819030E+09 | 0.368678E+09 | 0.519180E+09 | 0.172864E+10 | 0.576045E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.553166E+09 | 0.265001E+09 | 0.288165E+09 | 0.790807E+09 | 0.576035E+09 |
February | 0.576911E+09 | 0.267053E+09 | 0.309858E+09 | 0.902187E+09 | 0.427618E+09 |
March | 0.779832E+09 | 0.368671E+09 | 0.411161E+09 | 0.123582E+10 | 0.371298E+09 |
April | 0.819015E+09 | 0.365441E+09 | 0.453574E+09 | 0.145913E+10 | 0.233113E+09 |
May | 0.800648E+09 | 0.318837E+09 | 0.481811E+09 | 0.156449E+10 | 0.123363E+09 |
June | 0.764761E+09 | 0.293739E+09 | 0.471021E+09 | 0.157875E+10 | 46364980.60 |
July | 0.811992E+09 | 0.292821E+09 | 0.519171E+09 | 0.172861E+10 | 71606782.53 |
August | 0.742496E+09 | 0.248275E+09 | 0.494221E+09 | 0.154027E+10 | 40566964.69 |
September | 0.692724E+09 | 0.250422E+09 | 0.442301E+09 | 0.145252E+10 | 90215887.15 |
October | 0.658878E+09 | 0.283753E+09 | 0.375125E+09 | 0.128127E+10 | 0.141404E+09 |
November | 0.517516E+09 | 0.206354E+09 | 0.311162E+09 | 0.895351E+09 | 0.270918E+09 |
December | 0.431975E+09 | 0.152508E+09 | 0.279467E+09 | 0.636047E+09 | 0.481812E+09 |
Annual Sum or Average | 0.814991E+10 | 0.331288E+10 | 0.483704E+10 | 0.150652E+11 | 0.287432E+10 |
Minimum of Months | 0.431975E+09 | 0.152508E+09 | 0.279467E+09 | 0.636047E+09 | 40566964.69 |
Maximum of Months | 0.819015E+09 | 0.368671E+09 | 0.519171E+09 | 0.172861E+10 | 0.576035E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.971766E+09 | 0.631333E+09 | 0.340433E+09 | 0.156021E+10 | 0.534305E+09 |
February | 0.794031E+09 | 0.459443E+09 | 0.334588E+09 | 0.134855E+10 | 0.410194E+09 |
March | 0.674955E+09 | 0.285364E+09 | 0.389591E+09 | 0.116317E+10 | 0.370398E+09 |
April | 0.444154E+09 | 77886648.22 | 0.366267E+09 | 0.844269E+09 | 0.234532E+09 |
May | 0.367782E+09 | 7956782.79 | 0.359825E+09 | 0.771890E+09 | 0.115808E+09 |
June | 0.339337E+09 | 640378.28 | 0.338697E+09 | 0.769527E+09 | 47690295.58 |
July | 0.375449E+09 | 3480044.25 | 0.371969E+09 | 0.888095E+09 | 72015034.01 |
August | 0.426122E+09 | 35958141.79 | 0.390164E+09 | 0.957907E+09 | 50131718.19 |
September | 0.527894E+09 | 0.129361E+09 | 0.398534E+09 | 0.118271E+10 | 89588097.33 |
October | 0.750157E+09 | 0.351949E+09 | 0.398208E+09 | 0.148796E+10 | 0.155743E+09 |
November | 0.825980E+09 | 0.460987E+09 | 0.364993E+09 | 0.146423E+10 | 0.277687E+09 |
December | 0.936510E+09 | 0.590696E+09 | 0.345814E+09 | 0.153886E+10 | 0.470929E+09 |
Annual Sum or Average | 0.743414E+10 | 0.303505E+10 | 0.439908E+10 | 0.139774E+11 | 0.282902E+10 |
Minimum of Months | 0.339337E+09 | 640378.28 | 0.334588E+09 | 0.769527E+09 | 47690295.58 |
Maximum of Months | 0.971766E+09 | 0.631333E+09 | 0.398534E+09 | 0.156021E+10 | 0.534305E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.971759E+09 | 0.631328E+09 | 0.340431E+09 | 0.156019E+10 | 0.534304E+09 |
February | 0.794026E+09 | 0.459439E+09 | 0.334586E+09 | 0.134854E+10 | 0.410194E+09 |
March | 0.674950E+09 | 0.285362E+09 | 0.389589E+09 | 0.116317E+10 | 0.370397E+09 |
April | 0.444151E+09 | 77886077.47 | 0.366265E+09 | 0.844265E+09 | 0.234532E+09 |
May | 0.367780E+09 | 7956724.48 | 0.359824E+09 | 0.771887E+09 | 0.115807E+09 |
June | 0.339335E+09 | 640373.59 | 0.338695E+09 | 0.769525E+09 | 47689949.13 |
July | 0.375447E+09 | 3480018.75 | 0.371967E+09 | 0.888092E+09 | 72014528.48 |
August | 0.426120E+09 | 35957878.29 | 0.390162E+09 | 0.957904E+09 | 50131303.73 |
September | 0.527891E+09 | 0.129360E+09 | 0.398532E+09 | 0.118270E+10 | 89587637.89 |
October | 0.750153E+09 | 0.351947E+09 | 0.398206E+09 | 0.148795E+10 | 0.155742E+09 |
November | 0.825975E+09 | 0.460983E+09 | 0.364991E+09 | 0.146422E+10 | 0.277686E+09 |
December | 0.936504E+09 | 0.590692E+09 | 0.345812E+09 | 0.153885E+10 | 0.470928E+09 |
Annual Sum or Average | 0.743409E+10 | 0.303503E+10 | 0.439906E+10 | 0.139773E+11 | 0.282901E+10 |
Minimum of Months | 0.339335E+09 | 640373.59 | 0.334586E+09 | 0.769525E+09 | 47689949.13 |
Maximum of Months | 0.971759E+09 | 0.631328E+09 | 0.398532E+09 | 0.156019E+10 | 0.534304E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.971766E+09 | 0.631333E+09 | 0.340433E+09 | 0.156021E+10 | 0.534305E+09 |
February | 0.794031E+09 | 0.459443E+09 | 0.334588E+09 | 0.134855E+10 | 0.410194E+09 |
March | 0.674955E+09 | 0.285364E+09 | 0.389591E+09 | 0.116317E+10 | 0.370398E+09 |
April | 0.444154E+09 | 77886648.22 | 0.366267E+09 | 0.844269E+09 | 0.234532E+09 |
May | 0.367782E+09 | 7956782.79 | 0.359825E+09 | 0.771890E+09 | 0.115808E+09 |
June | 0.339337E+09 | 640378.28 | 0.338697E+09 | 0.769527E+09 | 47690295.58 |
July | 0.375449E+09 | 3480044.25 | 0.371969E+09 | 0.888095E+09 | 72015034.01 |
August | 0.426122E+09 | 35958141.79 | 0.390164E+09 | 0.957907E+09 | 50131718.19 |
September | 0.527894E+09 | 0.129361E+09 | 0.398534E+09 | 0.118271E+10 | 89588097.33 |
October | 0.750157E+09 | 0.351949E+09 | 0.398208E+09 | 0.148796E+10 | 0.155743E+09 |
November | 0.825980E+09 | 0.460987E+09 | 0.364993E+09 | 0.146423E+10 | 0.277687E+09 |
December | 0.936510E+09 | 0.590696E+09 | 0.345814E+09 | 0.153886E+10 | 0.470929E+09 |
Annual Sum or Average | 0.743414E+10 | 0.303505E+10 | 0.439908E+10 | 0.139774E+11 | 0.282902E+10 |
Minimum of Months | 0.339337E+09 | 640378.28 | 0.334588E+09 | 0.769527E+09 | 47690295.58 |
Maximum of Months | 0.971766E+09 | 0.631333E+09 | 0.398534E+09 | 0.156021E+10 | 0.534305E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.971759E+09 | 0.631328E+09 | 0.340431E+09 | 0.156019E+10 | 0.534304E+09 |
February | 0.794026E+09 | 0.459439E+09 | 0.334586E+09 | 0.134854E+10 | 0.410194E+09 |
March | 0.674950E+09 | 0.285362E+09 | 0.389589E+09 | 0.116317E+10 | 0.370397E+09 |
April | 0.444151E+09 | 77886077.47 | 0.366265E+09 | 0.844265E+09 | 0.234532E+09 |
May | 0.367780E+09 | 7956724.48 | 0.359824E+09 | 0.771887E+09 | 0.115807E+09 |
June | 0.339335E+09 | 640373.59 | 0.338695E+09 | 0.769525E+09 | 47689949.13 |
July | 0.375447E+09 | 3480018.75 | 0.371967E+09 | 0.888092E+09 | 72014528.48 |
August | 0.426120E+09 | 35957878.29 | 0.390162E+09 | 0.957904E+09 | 50131303.73 |
September | 0.527891E+09 | 0.129360E+09 | 0.398532E+09 | 0.118270E+10 | 89587637.89 |
October | 0.750153E+09 | 0.351947E+09 | 0.398206E+09 | 0.148795E+10 | 0.155742E+09 |
November | 0.825975E+09 | 0.460983E+09 | 0.364991E+09 | 0.146422E+10 | 0.277686E+09 |
December | 0.936504E+09 | 0.590692E+09 | 0.345812E+09 | 0.153885E+10 | 0.470928E+09 |
Annual Sum or Average | 0.743409E+10 | 0.303503E+10 | 0.439906E+10 | 0.139773E+11 | 0.282901E+10 |
Minimum of Months | 0.339335E+09 | 640373.59 | 0.334586E+09 | 0.769525E+09 | 47689949.13 |
Maximum of Months | 0.971759E+09 | 0.631328E+09 | 0.398532E+09 | 0.156019E+10 | 0.534304E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.971723E+09 | 0.631305E+09 | 0.340418E+09 | 0.156014E+10 | 0.534283E+09 |
February | 0.793996E+09 | 0.459423E+09 | 0.334574E+09 | 0.134849E+10 | 0.410178E+09 |
March | 0.674925E+09 | 0.285351E+09 | 0.389574E+09 | 0.116312E+10 | 0.370382E+09 |
April | 0.444135E+09 | 77883223.68 | 0.366251E+09 | 0.844233E+09 | 0.234523E+09 |
May | 0.367766E+09 | 7956432.94 | 0.359810E+09 | 0.771858E+09 | 0.115803E+09 |
June | 0.339323E+09 | 640350.13 | 0.338682E+09 | 0.769495E+09 | 47688200.23 |
July | 0.375433E+09 | 3479891.24 | 0.371953E+09 | 0.888057E+09 | 72011878.74 |
August | 0.426104E+09 | 35956560.77 | 0.390147E+09 | 0.957867E+09 | 50129490.44 |
September | 0.527872E+09 | 0.129355E+09 | 0.398517E+09 | 0.118266E+10 | 89584256.83 |
October | 0.750125E+09 | 0.351934E+09 | 0.398191E+09 | 0.148790E+10 | 0.155736E+09 |
November | 0.825944E+09 | 0.460967E+09 | 0.364978E+09 | 0.146416E+10 | 0.277675E+09 |
December | 0.936469E+09 | 0.590670E+09 | 0.345799E+09 | 0.153879E+10 | 0.470909E+09 |
Annual Sum or Average | 0.743381E+10 | 0.303492E+10 | 0.439889E+10 | 0.139768E+11 | 0.282890E+10 |
Minimum of Months | 0.339323E+09 | 640350.13 | 0.334574E+09 | 0.769495E+09 | 47688200.23 |
Maximum of Months | 0.971723E+09 | 0.631305E+09 | 0.398517E+09 | 0.156014E+10 | 0.534283E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.496936E+09 | 0.214236E+09 | 0.282700E+09 | 0.702390E+09 | 0.678499E+09 |
February | 0.561270E+09 | 0.254007E+09 | 0.307263E+09 | 0.882458E+09 | 0.542780E+09 |
March | 0.773840E+09 | 0.353376E+09 | 0.420464E+09 | 0.122537E+10 | 0.514971E+09 |
April | 0.824297E+09 | 0.381676E+09 | 0.442620E+09 | 0.142717E+10 | 0.349726E+09 |
May | 0.776502E+09 | 0.298917E+09 | 0.477585E+09 | 0.150670E+10 | 0.181482E+09 |
June | 0.636711E+09 | 0.178603E+09 | 0.458108E+09 | 0.129720E+10 | 93560750.43 |
July | 0.735302E+09 | 0.227479E+09 | 0.507822E+09 | 0.153369E+10 | 0.139074E+09 |
August | 0.733630E+09 | 0.239089E+09 | 0.494541E+09 | 0.145241E+10 | 0.127009E+09 |
September | 0.605637E+09 | 0.178583E+09 | 0.427054E+09 | 0.126053E+10 | 0.125017E+09 |
October | 0.622581E+09 | 0.242701E+09 | 0.379879E+09 | 0.118687E+10 | 0.222112E+09 |
November | 0.496997E+09 | 0.182302E+09 | 0.314696E+09 | 0.839580E+09 | 0.393983E+09 |
December | 0.514483E+09 | 0.230021E+09 | 0.284461E+09 | 0.754636E+09 | 0.647934E+09 |
Annual Sum or Average | 0.777819E+10 | 0.298099E+10 | 0.479719E+10 | 0.140690E+11 | 0.401615E+10 |
Minimum of Months | 0.496936E+09 | 0.178583E+09 | 0.282700E+09 | 0.702390E+09 | 93560750.43 |
Maximum of Months | 0.824297E+09 | 0.381676E+09 | 0.507822E+09 | 0.153369E+10 | 0.678499E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.496936E+09 | 0.214236E+09 | 0.282700E+09 | 0.702390E+09 | 0.678499E+09 |
February | 0.561270E+09 | 0.254007E+09 | 0.307263E+09 | 0.882458E+09 | 0.542780E+09 |
March | 0.773840E+09 | 0.353376E+09 | 0.420464E+09 | 0.122537E+10 | 0.514971E+09 |
April | 0.824297E+09 | 0.381676E+09 | 0.442620E+09 | 0.142717E+10 | 0.349726E+09 |
May | 0.776502E+09 | 0.298917E+09 | 0.477585E+09 | 0.150670E+10 | 0.181482E+09 |
June | 0.636711E+09 | 0.178603E+09 | 0.458108E+09 | 0.129720E+10 | 93560750.43 |
July | 0.735302E+09 | 0.227479E+09 | 0.507822E+09 | 0.153369E+10 | 0.139074E+09 |
August | 0.733630E+09 | 0.239089E+09 | 0.494541E+09 | 0.145241E+10 | 0.127009E+09 |
September | 0.605637E+09 | 0.178583E+09 | 0.427054E+09 | 0.126053E+10 | 0.125017E+09 |
October | 0.622581E+09 | 0.242701E+09 | 0.379879E+09 | 0.118687E+10 | 0.222112E+09 |
November | 0.496997E+09 | 0.182302E+09 | 0.314696E+09 | 0.839580E+09 | 0.393983E+09 |
December | 0.514483E+09 | 0.230021E+09 | 0.284461E+09 | 0.754636E+09 | 0.647934E+09 |
Annual Sum or Average | 0.777819E+10 | 0.298099E+10 | 0.479719E+10 | 0.140690E+11 | 0.401615E+10 |
Minimum of Months | 0.496936E+09 | 0.178583E+09 | 0.282700E+09 | 0.702390E+09 | 93560750.43 |
Maximum of Months | 0.824297E+09 | 0.381676E+09 | 0.507822E+09 | 0.153369E+10 | 0.678499E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.496927E+09 | 0.214233E+09 | 0.282695E+09 | 0.702377E+09 | 0.678487E+09 |
February | 0.561259E+09 | 0.254002E+09 | 0.307257E+09 | 0.882442E+09 | 0.542770E+09 |
March | 0.773826E+09 | 0.353370E+09 | 0.420457E+09 | 0.122535E+10 | 0.514962E+09 |
April | 0.824282E+09 | 0.381669E+09 | 0.442612E+09 | 0.142714E+10 | 0.349720E+09 |
May | 0.776488E+09 | 0.298912E+09 | 0.477576E+09 | 0.150667E+10 | 0.181479E+09 |
June | 0.636700E+09 | 0.178600E+09 | 0.458100E+09 | 0.129718E+10 | 93559040.87 |
July | 0.735288E+09 | 0.227475E+09 | 0.507813E+09 | 0.153366E+10 | 0.139071E+09 |
August | 0.733616E+09 | 0.239084E+09 | 0.494532E+09 | 0.145238E+10 | 0.127006E+09 |
September | 0.605626E+09 | 0.178580E+09 | 0.427046E+09 | 0.126051E+10 | 0.125014E+09 |
October | 0.622569E+09 | 0.242697E+09 | 0.379872E+09 | 0.118685E+10 | 0.222108E+09 |
November | 0.496988E+09 | 0.182298E+09 | 0.314690E+09 | 0.839565E+09 | 0.393976E+09 |
December | 0.514473E+09 | 0.230017E+09 | 0.284456E+09 | 0.754622E+09 | 0.647922E+09 |
Annual Sum or Average | 0.777804E+10 | 0.298094E+10 | 0.479711E+10 | 0.140688E+11 | 0.401607E+10 |
Minimum of Months | 0.496927E+09 | 0.178580E+09 | 0.282695E+09 | 0.702377E+09 | 93559040.87 |
Maximum of Months | 0.824282E+09 | 0.381669E+09 | 0.507813E+09 | 0.153366E+10 | 0.678487E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103383E+10 | 0.00 | 0.103383E+10 | 0.112252E+10 | 0.254963E+10 |
February | 0.110528E+10 | 0.00 | 0.110528E+10 | 0.152975E+10 | 0.190296E+10 |
March | 0.145935E+10 | 0.00 | 0.145935E+10 | 0.201420E+10 | 0.175533E+10 |
April | 0.158252E+10 | 7108834.21 | 0.157541E+10 | 0.273591E+10 | 0.107033E+10 |
May | 0.186739E+10 | 83532699.08 | 0.178386E+10 | 0.391035E+10 | 0.570752E+09 |
June | 0.193043E+10 | 0.138996E+09 | 0.179143E+10 | 0.436826E+10 | 0.247429E+09 |
July | 0.201864E+10 | 98917379.94 | 0.191972E+10 | 0.479118E+10 | 0.365333E+09 |
August | 0.178653E+10 | 16431133.84 | 0.177010E+10 | 0.405170E+10 | 0.236185E+09 |
September | 0.153374E+10 | 121333.23 | 0.153362E+10 | 0.361644E+10 | 0.402024E+09 |
October | 0.132773E+10 | 0.00 | 0.132773E+10 | 0.275542E+10 | 0.648552E+09 |
November | 0.111723E+10 | 0.00 | 0.111723E+10 | 0.186404E+10 | 0.125683E+10 |
December | 0.102258E+10 | 0.00 | 0.102258E+10 | 0.126176E+10 | 0.216752E+10 |
Annual Sum or Average | 0.177852E+11 | 0.345108E+09 | 0.174401E+11 | 0.340215E+11 | 0.131729E+11 |
Minimum of Months | 0.102258E+10 | 0.00 | 0.102258E+10 | 0.112252E+10 | 0.236185E+09 |
Maximum of Months | 0.201864E+10 | 0.138996E+09 | 0.191972E+10 | 0.479118E+10 | 0.254963E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.165951E+10 | 0.795008E+09 | 0.864502E+09 | 0.237687E+10 | 0.163983E+10 |
February | 0.173075E+10 | 0.801166E+09 | 0.929581E+09 | 0.269627E+10 | 0.122788E+10 |
March | 0.233952E+10 | 0.110602E+10 | 0.123349E+10 | 0.365612E+10 | 0.111870E+10 |
April | 0.245706E+10 | 0.109633E+10 | 0.136073E+10 | 0.431705E+10 | 0.746003E+09 |
May | 0.240196E+10 | 0.956518E+09 | 0.144545E+10 | 0.464630E+10 | 0.384463E+09 |
June | 0.229430E+10 | 0.881225E+09 | 0.141308E+10 | 0.467941E+10 | 0.170781E+09 |
July | 0.243600E+10 | 0.878471E+09 | 0.155753E+10 | 0.514170E+10 | 0.263262E+09 |
August | 0.222751E+10 | 0.744831E+09 | 0.148268E+10 | 0.457977E+10 | 0.165870E+09 |
September | 0.207819E+10 | 0.751273E+09 | 0.132691E+10 | 0.432060E+10 | 0.285213E+09 |
October | 0.197665E+10 | 0.851267E+09 | 0.112538E+10 | 0.380829E+10 | 0.455990E+09 |
November | 0.155256E+10 | 0.619066E+09 | 0.933494E+09 | 0.266301E+10 | 0.813515E+09 |
December | 0.129593E+10 | 0.457528E+09 | 0.838407E+09 | 0.190569E+10 | 0.140734E+10 |
Annual Sum or Average | 0.244499E+11 | 0.993871E+10 | 0.145112E+11 | 0.447911E+11 | 0.867884E+10 |
Minimum of Months | 0.129593E+10 | 0.457528E+09 | 0.838407E+09 | 0.190569E+10 | 0.165870E+09 |
Maximum of Months | 0.245706E+10 | 0.110602E+10 | 0.155753E+10 | 0.514170E+10 | 0.163983E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.485892E+10 | 0.315673E+10 | 0.170219E+10 | 0.771981E+10 | 0.263288E+10 |
February | 0.397022E+10 | 0.229726E+10 | 0.167296E+10 | 0.667939E+10 | 0.200320E+10 |
March | 0.337482E+10 | 0.142685E+10 | 0.194798E+10 | 0.576335E+10 | 0.181871E+10 |
April | 0.222079E+10 | 0.389441E+09 | 0.183135E+10 | 0.421926E+10 | 0.115270E+10 |
May | 0.183893E+10 | 39784750.56 | 0.179914E+10 | 0.387116E+10 | 0.557715E+09 |
June | 0.169670E+10 | 3201958.74 | 0.169350E+10 | 0.387761E+10 | 0.244574E+09 |
July | 0.187726E+10 | 17400587.18 | 0.185986E+10 | 0.449127E+10 | 0.360525E+09 |
August | 0.213063E+10 | 0.179794E+09 | 0.195084E+10 | 0.483860E+10 | 0.250391E+09 |
September | 0.263951E+10 | 0.646818E+09 | 0.199269E+10 | 0.589407E+10 | 0.450643E+09 |
October | 0.375085E+10 | 0.175978E+10 | 0.199107E+10 | 0.738380E+10 | 0.795650E+09 |
November | 0.412998E+10 | 0.230498E+10 | 0.182499E+10 | 0.725594E+10 | 0.137615E+10 |
December | 0.468264E+10 | 0.295354E+10 | 0.172909E+10 | 0.762987E+10 | 0.231761E+10 |
Annual Sum or Average | 0.371713E+11 | 0.151756E+11 | 0.219957E+11 | 0.696241E+11 | 0.139607E+11 |
Minimum of Months | 0.169670E+10 | 3201958.74 | 0.167296E+10 | 0.387116E+10 | 0.244574E+09 |
Maximum of Months | 0.485892E+10 | 0.315673E+10 | 0.199269E+10 | 0.771981E+10 | 0.263288E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.149079E+10 | 0.642703E+09 | 0.848091E+09 | 0.216299E+10 | 0.180407E+10 |
February | 0.168379E+10 | 0.762012E+09 | 0.921779E+09 | 0.271516E+10 | 0.140055E+10 |
March | 0.232150E+10 | 0.106012E+10 | 0.126138E+10 | 0.374265E+10 | 0.132808E+10 |
April | 0.247286E+10 | 0.114502E+10 | 0.132785E+10 | 0.437454E+10 | 0.886519E+09 |
May | 0.232948E+10 | 0.896742E+09 | 0.143274E+10 | 0.454098E+10 | 0.487566E+09 |
June | 0.191011E+10 | 0.535805E+09 | 0.137431E+10 | 0.396478E+10 | 0.223249E+09 |
July | 0.220588E+10 | 0.682431E+09 | 0.152345E+10 | 0.470390E+10 | 0.327966E+09 |
August | 0.220087E+10 | 0.717259E+09 | 0.148361E+10 | 0.449067E+10 | 0.245410E+09 |
September | 0.181689E+10 | 0.535745E+09 | 0.128115E+10 | 0.382295E+10 | 0.327549E+09 |
October | 0.186772E+10 | 0.728096E+09 | 0.113963E+10 | 0.361805E+10 | 0.555686E+09 |
November | 0.149098E+10 | 0.546899E+09 | 0.944078E+09 | 0.260546E+10 | 0.953838E+09 |
December | 0.154343E+10 | 0.690057E+09 | 0.853376E+09 | 0.236988E+10 | 0.158208E+10 |
Annual Sum or Average | 0.233343E+11 | 0.894288E+10 | 0.143914E+11 | 0.431120E+11 | 0.101226E+11 |
Minimum of Months | 0.149079E+10 | 0.535745E+09 | 0.848091E+09 | 0.216299E+10 | 0.223249E+09 |
Maximum of Months | 0.247286E+10 | 0.114502E+10 | 0.152345E+10 | 0.470390E+10 | 0.180407E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103383E+10 | 0.00 | 0.103383E+10 | 0.117453E+10 | 0.234030E+10 |
February | 0.110528E+10 | 0.00 | 0.110528E+10 | 0.154668E+10 | 0.179273E+10 |
March | 0.145935E+10 | 0.00 | 0.145935E+10 | 0.200053E+10 | 0.168605E+10 |
April | 0.158252E+10 | 7108834.21 | 0.157541E+10 | 0.268005E+10 | 0.107754E+10 |
May | 0.186739E+10 | 83532699.08 | 0.178386E+10 | 0.383108E+10 | 0.606901E+09 |
June | 0.193043E+10 | 0.138996E+09 | 0.179143E+10 | 0.426998E+10 | 0.271179E+09 |
July | 0.201864E+10 | 98917379.94 | 0.191972E+10 | 0.468590E+10 | 0.406342E+09 |
August | 0.178653E+10 | 16431133.84 | 0.177010E+10 | 0.396923E+10 | 0.262411E+09 |
September | 0.153374E+10 | 121333.23 | 0.153362E+10 | 0.352226E+10 | 0.419477E+09 |
October | 0.132773E+10 | 0.00 | 0.132773E+10 | 0.270194E+10 | 0.662703E+09 |
November | 0.111723E+10 | 0.00 | 0.111723E+10 | 0.185586E+10 | 0.119377E+10 |
December | 0.102258E+10 | 0.00 | 0.102258E+10 | 0.129472E+10 | 0.201103E+10 |
Annual Sum or Average | 0.177852E+11 | 0.345108E+09 | 0.174401E+11 | 0.335328E+11 | 0.127304E+11 |
Minimum of Months | 0.102258E+10 | 0.00 | 0.102258E+10 | 0.117453E+10 | 0.262411E+09 |
Maximum of Months | 0.201864E+10 | 0.138996E+09 | 0.191972E+10 | 0.468590E+10 | 0.234030E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.165951E+10 | 0.795008E+09 | 0.864502E+09 | 0.240866E+10 | 0.154039E+10 |
February | 0.173075E+10 | 0.801166E+09 | 0.929581E+09 | 0.270226E+10 | 0.117568E+10 |
March | 0.233952E+10 | 0.110602E+10 | 0.123349E+10 | 0.363262E+10 | 0.109415E+10 |
April | 0.245706E+10 | 0.109633E+10 | 0.136073E+10 | 0.427034E+10 | 0.755178E+09 |
May | 0.240196E+10 | 0.956518E+09 | 0.144545E+10 | 0.458569E+10 | 0.408131E+09 |
June | 0.229430E+10 | 0.881225E+09 | 0.141308E+10 | 0.461009E+10 | 0.185588E+09 |
July | 0.243600E+10 | 0.878471E+09 | 0.155753E+10 | 0.506995E+10 | 0.288718E+09 |
August | 0.222751E+10 | 0.744831E+09 | 0.148268E+10 | 0.452001E+10 | 0.182076E+09 |
September | 0.207819E+10 | 0.751273E+09 | 0.132691E+10 | 0.425545E+10 | 0.296700E+09 |
October | 0.197665E+10 | 0.851267E+09 | 0.112538E+10 | 0.376591E+10 | 0.467554E+09 |
November | 0.155256E+10 | 0.619066E+09 | 0.933494E+09 | 0.265156E+10 | 0.784572E+09 |
December | 0.129593E+10 | 0.457528E+09 | 0.838407E+09 | 0.192471E+10 | 0.132642E+10 |
Annual Sum or Average | 0.244499E+11 | 0.993871E+10 | 0.145112E+11 | 0.443972E+11 | 0.850516E+10 |
Minimum of Months | 0.129593E+10 | 0.457528E+09 | 0.838407E+09 | 0.192471E+10 | 0.182076E+09 |
Maximum of Months | 0.245706E+10 | 0.110602E+10 | 0.155753E+10 | 0.506995E+10 | 0.154039E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.485892E+10 | 0.315673E+10 | 0.170219E+10 | 0.775202E+10 | 0.249402E+10 |
February | 0.397022E+10 | 0.229726E+10 | 0.167296E+10 | 0.667707E+10 | 0.192786E+10 |
March | 0.337482E+10 | 0.142685E+10 | 0.194798E+10 | 0.572716E+10 | 0.177515E+10 |
April | 0.222079E+10 | 0.389441E+09 | 0.183135E+10 | 0.415785E+10 | 0.116405E+10 |
May | 0.183893E+10 | 39784750.56 | 0.179914E+10 | 0.378973E+10 | 0.592194E+09 |
June | 0.169670E+10 | 3201958.74 | 0.169350E+10 | 0.378032E+10 | 0.267731E+09 |
July | 0.187726E+10 | 17400587.18 | 0.185986E+10 | 0.438515E+10 | 0.401104E+09 |
August | 0.213063E+10 | 0.179794E+09 | 0.195084E+10 | 0.475159E+10 | 0.275768E+09 |
September | 0.263951E+10 | 0.646818E+09 | 0.199269E+10 | 0.580098E+10 | 0.470819E+09 |
October | 0.375085E+10 | 0.175978E+10 | 0.199107E+10 | 0.732568E+10 | 0.814600E+09 |
November | 0.412998E+10 | 0.230498E+10 | 0.182499E+10 | 0.723617E+10 | 0.133788E+10 |
December | 0.468264E+10 | 0.295354E+10 | 0.172909E+10 | 0.763634E+10 | 0.221121E+10 |
Annual Sum or Average | 0.371713E+11 | 0.151756E+11 | 0.219957E+11 | 0.690201E+11 | 0.137324E+11 |
Minimum of Months | 0.169670E+10 | 3201958.74 | 0.167296E+10 | 0.378032E+10 | 0.267731E+09 |
Maximum of Months | 0.485892E+10 | 0.315673E+10 | 0.199269E+10 | 0.775202E+10 | 0.249402E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.149079E+10 | 0.642703E+09 | 0.848091E+09 | 0.218436E+10 | 0.168554E+10 |
February | 0.168379E+10 | 0.762012E+09 | 0.921779E+09 | 0.271376E+10 | 0.134040E+10 |
March | 0.232150E+10 | 0.106012E+10 | 0.126138E+10 | 0.372055E+10 | 0.128951E+10 |
April | 0.247286E+10 | 0.114502E+10 | 0.132785E+10 | 0.433323E+10 | 0.888983E+09 |
May | 0.232948E+10 | 0.896742E+09 | 0.143274E+10 | 0.448976E+10 | 0.505802E+09 |
June | 0.191011E+10 | 0.535805E+09 | 0.137431E+10 | 0.390995E+10 | 0.235488E+09 |
July | 0.220588E+10 | 0.682431E+09 | 0.152345E+10 | 0.464355E+10 | 0.345520E+09 |
August | 0.220087E+10 | 0.717259E+09 | 0.148361E+10 | 0.444146E+10 | 0.260144E+09 |
September | 0.181689E+10 | 0.535745E+09 | 0.128115E+10 | 0.377275E+10 | 0.336359E+09 |
October | 0.186772E+10 | 0.728096E+09 | 0.113963E+10 | 0.358329E+10 | 0.560982E+09 |
November | 0.149098E+10 | 0.546899E+09 | 0.944078E+09 | 0.259389E+10 | 0.918819E+09 |
December | 0.154343E+10 | 0.690057E+09 | 0.853376E+09 | 0.238018E+10 | 0.149257E+10 |
Annual Sum or Average | 0.233343E+11 | 0.894288E+10 | 0.143914E+11 | 0.427667E+11 | 0.986012E+10 |
Minimum of Months | 0.149079E+10 | 0.535745E+09 | 0.848091E+09 | 0.218436E+10 | 0.235488E+09 |
Maximum of Months | 0.247286E+10 | 0.114502E+10 | 0.152345E+10 | 0.464355E+10 | 0.168554E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 390.85 | 1048.99 | 385.98 | 0.00 | 385.98 | 0.00 | 0.00 |
February | 603.89 | 868.47 | 456.87 | 0.00 | 456.87 | 0.00 | 0.00 |
March | 735.85 | 704.05 | 544.85 | 0.00 | 544.85 | 0.00 | 0.00 |
April | 1039.73 | 430.78 | 610.53 | 2.74 | 607.79 | 0.00 | 0.00 |
May | 1456.65 | 218.45 | 697.19 | 31.19 | 666.00 | 0.00 | 0.00 |
June | 1681.43 | 90.44 | 744.75 | 53.62 | 691.13 | 0.00 | 0.00 |
July | 1773.80 | 133.84 | 753.66 | 36.93 | 716.73 | 0.00 | 0.00 |
August | 1488.15 | 90.23 | 667.00 | 6.13 | 660.87 | 0.00 | 0.00 |
September | 1383.45 | 159.07 | 591.71 | 0.05 | 591.66 | 0.00 | 0.00 |
October | 1015.55 | 253.85 | 495.71 | 0.00 | 495.71 | 0.00 | 0.00 |
November | 700.37 | 529.02 | 431.02 | 0.00 | 431.02 | 0.00 | 0.00 |
December | 441.86 | 898.84 | 381.78 | 0.00 | 381.78 | 0.00 | 0.00 |
Annual Sum or Average | 1061.49 | 450.39 | 563.96 | 10.94 | 553.01 | 0.00 | 0.00 |
Minimum of Months | 390.85 | 90.23 | 381.78 | 0.00 | 381.78 | 0.00 | 0.00 |
Maximum of Months | 1773.80 | 1048.99 | 753.66 | 53.62 | 716.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 885.77 | 645.21 | 619.59 | 296.82 | 322.77 | 0.00 | 0.00 |
February | 1118.80 | 530.29 | 715.42 | 331.17 | 384.25 | 0.00 | 0.00 |
March | 1384.22 | 415.89 | 873.48 | 412.94 | 460.54 | 0.00 | 0.00 |
April | 1688.82 | 269.81 | 947.95 | 422.97 | 524.98 | 0.00 | 0.00 |
May | 1752.36 | 138.18 | 896.79 | 357.12 | 539.67 | 0.00 | 0.00 |
June | 1827.28 | 53.66 | 885.15 | 339.98 | 545.17 | 0.00 | 0.00 |
July | 1936.19 | 80.21 | 909.50 | 327.98 | 581.52 | 0.00 | 0.00 |
August | 1725.24 | 45.44 | 831.66 | 278.09 | 553.57 | 0.00 | 0.00 |
September | 1681.18 | 104.42 | 801.77 | 289.84 | 511.93 | 0.00 | 0.00 |
October | 1435.13 | 158.38 | 738.00 | 317.83 | 420.17 | 0.00 | 0.00 |
November | 1036.30 | 313.57 | 598.98 | 238.84 | 360.15 | 0.00 | 0.00 |
December | 712.43 | 539.67 | 483.85 | 170.82 | 313.03 | 0.00 | 0.00 |
Annual Sum or Average | 1433.16 | 273.44 | 775.31 | 315.16 | 460.15 | 0.00 | 0.00 |
Minimum of Months | 712.43 | 45.44 | 483.85 | 170.82 | 313.03 | 0.00 | 0.00 |
Maximum of Months | 1936.19 | 645.21 | 947.95 | 422.97 | 581.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2912.54 | 997.42 | 1814.06 | 1178.55 | 635.51 | 0.00 | 0.00 |
February | 2787.15 | 847.78 | 1641.08 | 949.56 | 691.52 | 0.00 | 0.00 |
March | 2171.37 | 691.45 | 1259.98 | 532.71 | 727.28 | 0.00 | 0.00 |
April | 1628.59 | 452.41 | 856.77 | 150.24 | 706.53 | 0.00 | 0.00 |
May | 1440.94 | 216.19 | 686.56 | 14.85 | 671.71 | 0.00 | 0.00 |
June | 1484.41 | 91.99 | 654.58 | 1.24 | 653.34 | 0.00 | 0.00 |
July | 1657.87 | 134.44 | 700.88 | 6.50 | 694.38 | 0.00 | 0.00 |
August | 1788.19 | 93.58 | 795.47 | 67.13 | 728.34 | 0.00 | 0.00 |
September | 2281.43 | 172.81 | 1018.30 | 249.54 | 768.77 | 0.00 | 0.00 |
October | 2777.67 | 290.74 | 1400.37 | 657.01 | 743.36 | 0.00 | 0.00 |
November | 2824.48 | 535.66 | 1593.31 | 889.24 | 704.07 | 0.00 | 0.00 |
December | 2872.69 | 879.12 | 1748.24 | 1102.69 | 645.55 | 0.00 | 0.00 |
Annual Sum or Average | 2216.07 | 448.53 | 1178.66 | 481.20 | 697.46 | 0.00 | 0.00 |
Minimum of Months | 1440.94 | 91.99 | 654.58 | 1.24 | 635.51 | 0.00 | 0.00 |
Maximum of Months | 2912.54 | 997.42 | 1814.06 | 1178.55 | 768.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 786.72 | 759.96 | 556.60 | 239.96 | 316.64 | 0.00 | 0.00 |
February | 1094.31 | 673.09 | 696.01 | 314.99 | 381.03 | 0.00 | 0.00 |
March | 1372.50 | 576.80 | 866.75 | 395.80 | 470.95 | 0.00 | 0.00 |
April | 1651.81 | 404.77 | 954.04 | 441.75 | 512.29 | 0.00 | 0.00 |
May | 1687.60 | 203.27 | 869.73 | 334.81 | 534.93 | 0.00 | 0.00 |
June | 1501.38 | 108.29 | 736.93 | 206.72 | 530.21 | 0.00 | 0.00 |
July | 1717.83 | 155.77 | 823.59 | 254.79 | 568.79 | 0.00 | 0.00 |
August | 1626.79 | 142.26 | 821.71 | 267.79 | 553.92 | 0.00 | 0.00 |
September | 1458.94 | 144.69 | 700.97 | 206.69 | 494.27 | 0.00 | 0.00 |
October | 1329.37 | 248.78 | 697.33 | 271.84 | 425.49 | 0.00 | 0.00 |
November | 971.73 | 456.00 | 575.22 | 211.00 | 364.23 | 0.00 | 0.00 |
December | 845.24 | 725.73 | 576.25 | 257.64 | 318.62 | 0.00 | 0.00 |
Annual Sum or Average | 1338.37 | 382.05 | 739.93 | 283.58 | 456.35 | 0.00 | 0.00 |
Minimum of Months | 786.72 | 108.29 | 556.60 | 206.69 | 316.64 | 0.00 | 0.00 |
Maximum of Months | 1717.83 | 759.96 | 954.04 | 441.75 | 568.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 419.10 | 951.92 | 385.99 | 0.00 | 385.99 | 0.00 | 0.00 |
February | 632.34 | 786.61 | 456.88 | 0.00 | 456.88 | 0.00 | 0.00 |
March | 752.02 | 655.36 | 544.86 | 0.00 | 544.86 | 0.00 | 0.00 |
April | 1055.52 | 412.94 | 610.54 | 2.74 | 607.80 | 0.00 | 0.00 |
May | 1459.96 | 213.09 | 697.20 | 31.19 | 666.02 | 0.00 | 0.00 |
June | 1685.29 | 95.46 | 744.76 | 53.63 | 691.14 | 0.00 | 0.00 |
July | 1788.82 | 136.40 | 753.67 | 36.93 | 716.74 | 0.00 | 0.00 |
August | 1512.73 | 88.18 | 667.01 | 6.13 | 660.88 | 0.00 | 0.00 |
September | 1395.23 | 155.10 | 591.72 | 0.05 | 591.67 | 0.00 | 0.00 |
October | 1028.76 | 242.14 | 495.72 | 0.00 | 495.72 | 0.00 | 0.00 |
November | 719.15 | 484.89 | 431.03 | 0.00 | 431.03 | 0.00 | 0.00 |
December | 471.09 | 809.26 | 381.79 | 0.00 | 381.79 | 0.00 | 0.00 |
Annual Sum or Average | 1078.82 | 417.71 | 563.97 | 10.94 | 553.02 | 0.00 | 0.00 |
Minimum of Months | 419.10 | 88.18 | 381.79 | 0.00 | 381.79 | 0.00 | 0.00 |
Maximum of Months | 1788.82 | 951.92 | 753.67 | 53.63 | 716.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 887.42 | 612.24 | 619.59 | 296.82 | 322.77 | 0.00 | 0.00 |
February | 1114.53 | 507.55 | 715.42 | 331.17 | 384.25 | 0.00 | 0.00 |
March | 1365.04 | 417.67 | 873.48 | 412.94 | 460.53 | 0.00 | 0.00 |
April | 1665.53 | 287.81 | 947.94 | 422.97 | 524.97 | 0.00 | 0.00 |
May | 1734.73 | 143.54 | 896.79 | 357.12 | 539.67 | 0.00 | 0.00 |
June | 1805.33 | 65.89 | 885.15 | 339.98 | 545.17 | 0.00 | 0.00 |
July | 1919.69 | 98.29 | 909.50 | 327.98 | 581.51 | 0.00 | 0.00 |
August | 1709.89 | 61.93 | 831.66 | 278.09 | 553.57 | 0.00 | 0.00 |
September | 1666.90 | 110.04 | 801.77 | 289.84 | 511.93 | 0.00 | 0.00 |
October | 1421.85 | 170.25 | 738.00 | 317.83 | 420.17 | 0.00 | 0.00 |
November | 1027.39 | 313.86 | 598.98 | 238.84 | 360.14 | 0.00 | 0.00 |
December | 711.50 | 525.44 | 483.85 | 170.82 | 313.03 | 0.00 | 0.00 |
Annual Sum or Average | 1420.32 | 275.20 | 775.30 | 315.15 | 460.15 | 0.00 | 0.00 |
Minimum of Months | 711.50 | 61.93 | 483.85 | 170.82 | 313.03 | 0.00 | 0.00 |
Maximum of Months | 1919.69 | 612.24 | 947.94 | 422.97 | 581.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2882.25 | 983.01 | 1814.11 | 1178.59 | 635.52 | 0.00 | 0.00 |
February | 2760.99 | 828.04 | 1641.13 | 949.60 | 691.53 | 0.00 | 0.00 |
March | 2151.79 | 679.03 | 1260.02 | 532.72 | 727.29 | 0.00 | 0.00 |
April | 1627.80 | 444.72 | 856.79 | 150.25 | 706.54 | 0.00 | 0.00 |
May | 1445.33 | 208.23 | 686.58 | 14.85 | 671.72 | 0.00 | 0.00 |
June | 1495.99 | 94.36 | 654.59 | 1.24 | 653.36 | 0.00 | 0.00 |
July | 1676.85 | 134.60 | 700.89 | 6.50 | 694.39 | 0.00 | 0.00 |
August | 1806.53 | 93.49 | 795.49 | 67.13 | 728.36 | 0.00 | 0.00 |
September | 2273.95 | 173.86 | 1018.33 | 249.54 | 768.79 | 0.00 | 0.00 |
October | 2756.79 | 297.06 | 1400.41 | 657.03 | 743.38 | 0.00 | 0.00 |
November | 2799.36 | 530.92 | 1593.35 | 889.27 | 704.09 | 0.00 | 0.00 |
December | 2848.67 | 865.30 | 1748.30 | 1102.73 | 645.57 | 0.00 | 0.00 |
Annual Sum or Average | 2207.77 | 442.69 | 1178.69 | 481.21 | 697.48 | 0.00 | 0.00 |
Minimum of Months | 1445.33 | 93.49 | 654.59 | 1.24 | 635.52 | 0.00 | 0.00 |
Maximum of Months | 2882.25 | 983.01 | 1814.11 | 1178.59 | 768.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 807.57 | 673.56 | 556.60 | 239.96 | 316.64 | 0.00 | 0.00 |
February | 1122.34 | 578.93 | 696.01 | 314.99 | 381.03 | 0.00 | 0.00 |
March | 1397.34 | 495.85 | 866.75 | 395.80 | 470.95 | 0.00 | 0.00 |
April | 1687.71 | 342.02 | 954.04 | 441.75 | 512.29 | 0.00 | 0.00 |
May | 1695.41 | 182.04 | 869.73 | 334.81 | 534.92 | 0.00 | 0.00 |
June | 1529.62 | 86.13 | 736.93 | 206.71 | 530.21 | 0.00 | 0.00 |
July | 1756.24 | 122.45 | 823.58 | 254.79 | 568.79 | 0.00 | 0.00 |
August | 1676.63 | 91.63 | 821.71 | 267.79 | 553.92 | 0.00 | 0.00 |
September | 1474.90 | 126.37 | 700.96 | 206.69 | 494.27 | 0.00 | 0.00 |
October | 1350.83 | 207.47 | 697.33 | 271.84 | 425.49 | 0.00 | 0.00 |
November | 1005.19 | 367.99 | 575.22 | 210.99 | 364.23 | 0.00 | 0.00 |
December | 884.81 | 590.68 | 576.25 | 257.64 | 318.61 | 0.00 | 0.00 |
Annual Sum or Average | 1367.07 | 320.98 | 739.93 | 283.58 | 456.35 | 0.00 | 0.00 |
Minimum of Months | 807.57 | 86.13 | 556.60 | 206.69 | 316.64 | 0.00 | 0.00 |
Maximum of Months | 1756.24 | 673.56 | 954.04 | 441.75 | 568.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 438.52 | 873.77 | 385.99 | 0.00 | 385.99 | 0.00 | 0.00 |
February | 639.33 | 741.04 | 456.88 | 0.00 | 456.88 | 0.00 | 0.00 |
March | 746.91 | 629.50 | 544.86 | 0.00 | 544.86 | 0.00 | 0.00 |
April | 1033.97 | 415.72 | 610.54 | 2.74 | 607.80 | 0.00 | 0.00 |
May | 1430.36 | 226.59 | 697.20 | 31.19 | 666.02 | 0.00 | 0.00 |
June | 1647.37 | 104.62 | 744.76 | 53.63 | 691.14 | 0.00 | 0.00 |
July | 1749.51 | 151.71 | 753.67 | 36.93 | 716.74 | 0.00 | 0.00 |
August | 1481.94 | 97.97 | 667.01 | 6.13 | 660.88 | 0.00 | 0.00 |
September | 1358.90 | 161.84 | 591.72 | 0.05 | 591.67 | 0.00 | 0.00 |
October | 1008.79 | 247.43 | 495.72 | 0.00 | 495.72 | 0.00 | 0.00 |
November | 715.99 | 460.56 | 431.03 | 0.00 | 431.03 | 0.00 | 0.00 |
December | 483.39 | 750.83 | 381.79 | 0.00 | 381.79 | 0.00 | 0.00 |
Annual Sum or Average | 1063.32 | 403.68 | 563.97 | 10.94 | 553.02 | 0.00 | 0.00 |
Minimum of Months | 438.52 | 97.97 | 381.79 | 0.00 | 381.79 | 0.00 | 0.00 |
Maximum of Months | 1749.51 | 873.77 | 753.67 | 53.63 | 716.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 899.29 | 575.12 | 619.59 | 296.82 | 322.77 | 0.00 | 0.00 |
February | 1117.01 | 485.98 | 715.42 | 331.17 | 384.25 | 0.00 | 0.00 |
March | 1356.26 | 408.51 | 873.48 | 412.94 | 460.53 | 0.00 | 0.00 |
April | 1647.51 | 291.35 | 947.94 | 422.97 | 524.97 | 0.00 | 0.00 |
May | 1712.10 | 152.38 | 896.79 | 357.12 | 539.67 | 0.00 | 0.00 |
June | 1778.58 | 71.60 | 885.15 | 339.98 | 545.17 | 0.00 | 0.00 |
July | 1892.90 | 107.79 | 909.50 | 327.98 | 581.51 | 0.00 | 0.00 |
August | 1687.58 | 67.98 | 831.66 | 278.09 | 553.57 | 0.00 | 0.00 |
September | 1641.76 | 114.47 | 801.77 | 289.84 | 511.93 | 0.00 | 0.00 |
October | 1406.03 | 174.56 | 738.00 | 317.83 | 420.17 | 0.00 | 0.00 |
November | 1022.98 | 302.69 | 598.98 | 238.84 | 360.14 | 0.00 | 0.00 |
December | 718.60 | 495.23 | 483.85 | 170.82 | 313.03 | 0.00 | 0.00 |
Annual Sum or Average | 1407.83 | 269.70 | 775.30 | 315.15 | 460.15 | 0.00 | 0.00 |
Minimum of Months | 718.60 | 67.98 | 483.85 | 170.82 | 313.03 | 0.00 | 0.00 |
Maximum of Months | 1892.90 | 575.12 | 947.94 | 422.97 | 581.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2894.27 | 931.16 | 1814.11 | 1178.59 | 635.52 | 0.00 | 0.00 |
February | 2760.03 | 796.90 | 1641.13 | 949.60 | 691.53 | 0.00 | 0.00 |
March | 2138.28 | 662.76 | 1260.02 | 532.72 | 727.29 | 0.00 | 0.00 |
April | 1604.11 | 449.09 | 856.79 | 150.25 | 706.54 | 0.00 | 0.00 |
May | 1414.92 | 221.10 | 686.58 | 14.85 | 671.72 | 0.00 | 0.00 |
June | 1458.46 | 103.29 | 654.59 | 1.24 | 653.36 | 0.00 | 0.00 |
July | 1637.23 | 149.75 | 700.89 | 6.50 | 694.39 | 0.00 | 0.00 |
August | 1774.04 | 102.96 | 795.49 | 67.13 | 728.36 | 0.00 | 0.00 |
September | 2238.03 | 181.64 | 1018.33 | 249.54 | 768.79 | 0.00 | 0.00 |
October | 2735.10 | 304.14 | 1400.41 | 657.03 | 743.38 | 0.00 | 0.00 |
November | 2791.73 | 516.16 | 1593.35 | 889.27 | 704.09 | 0.00 | 0.00 |
December | 2851.08 | 825.57 | 1748.30 | 1102.73 | 645.57 | 0.00 | 0.00 |
Annual Sum or Average | 2188.61 | 435.45 | 1178.69 | 481.21 | 697.48 | 0.00 | 0.00 |
Minimum of Months | 1414.92 | 102.96 | 654.59 | 1.24 | 635.52 | 0.00 | 0.00 |
Maximum of Months | 2894.27 | 931.16 | 1814.11 | 1178.59 | 768.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 815.55 | 629.31 | 556.60 | 239.96 | 316.64 | 0.00 | 0.00 |
February | 1121.76 | 554.07 | 696.01 | 314.99 | 381.03 | 0.00 | 0.00 |
March | 1389.09 | 481.45 | 866.75 | 395.80 | 470.95 | 0.00 | 0.00 |
April | 1671.77 | 342.97 | 954.04 | 441.75 | 512.29 | 0.00 | 0.00 |
May | 1676.28 | 188.84 | 869.73 | 334.81 | 534.92 | 0.00 | 0.00 |
June | 1508.47 | 90.85 | 736.93 | 206.71 | 530.21 | 0.00 | 0.00 |
July | 1733.70 | 129.00 | 823.58 | 254.79 | 568.79 | 0.00 | 0.00 |
August | 1658.25 | 97.13 | 821.71 | 267.79 | 553.92 | 0.00 | 0.00 |
September | 1455.53 | 129.77 | 700.96 | 206.69 | 494.27 | 0.00 | 0.00 |
October | 1337.85 | 209.45 | 697.33 | 271.84 | 425.49 | 0.00 | 0.00 |
November | 1000.73 | 354.48 | 575.22 | 210.99 | 364.23 | 0.00 | 0.00 |
December | 888.66 | 557.26 | 576.25 | 257.64 | 318.61 | 0.00 | 0.00 |
Annual Sum or Average | 1356.12 | 312.66 | 739.93 | 283.58 | 456.35 | 0.00 | 0.00 |
Minimum of Months | 815.55 | 90.85 | 556.60 | 206.69 | 316.64 | 0.00 | 0.00 |
Maximum of Months | 1733.70 | 629.31 | 954.04 | 441.75 | 568.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104684E+10 | 0.280962E+10 | 0.103381E+10 | 0.00 | 0.103381E+10 | 0.00 | 0.00 |
February | 0.146092E+10 | 0.210100E+10 | 0.110526E+10 | 0.00 | 0.110526E+10 | 0.00 | 0.00 |
March | 0.197091E+10 | 0.188572E+10 | 0.145932E+10 | 0.00 | 0.145932E+10 | 0.00 | 0.00 |
April | 0.269498E+10 | 0.111659E+10 | 0.158249E+10 | 7108622.21 | 0.157538E+10 | 0.00 | 0.00 |
May | 0.390150E+10 | 0.585091E+09 | 0.186736E+10 | 83530207.98 | 0.178383E+10 | 0.00 | 0.00 |
June | 0.435826E+10 | 0.234412E+09 | 0.193039E+10 | 0.138992E+09 | 0.179140E+10 | 0.00 | 0.00 |
July | 0.475093E+10 | 0.358488E+09 | 0.201860E+10 | 98914430.03 | 0.191969E+10 | 0.00 | 0.00 |
August | 0.398586E+10 | 0.241684E+09 | 0.178649E+10 | 16430643.83 | 0.177006E+10 | 0.00 | 0.00 |
September | 0.358590E+10 | 0.412312E+09 | 0.153371E+10 | 121329.61 | 0.153359E+10 | 0.00 | 0.00 |
October | 0.272004E+10 | 0.679919E+09 | 0.132771E+10 | 0.00 | 0.132771E+10 | 0.00 | 0.00 |
November | 0.181535E+10 | 0.137122E+10 | 0.111721E+10 | 0.00 | 0.111721E+10 | 0.00 | 0.00 |
December | 0.118349E+10 | 0.240744E+10 | 0.102256E+10 | 0.00 | 0.102256E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.334750E+11 | 0.142035E+11 | 0.177849E+11 | 0.345098E+09 | 0.174398E+11 | 0.00 | 0.00 |
Minimum of Months | 0.104684E+10 | 0.234412E+09 | 0.102256E+10 | 0.00 | 0.102256E+10 | 0.00 | 0.00 |
Maximum of Months | 0.475093E+10 | 0.280962E+10 | 0.201860E+10 | 0.138992E+09 | 0.191969E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.237245E+10 | 0.172813E+10 | 0.165952E+10 | 0.795011E+09 | 0.864506E+09 | 0.00 | 0.00 |
February | 0.270659E+10 | 0.128287E+10 | 0.173075E+10 | 0.801170E+09 | 0.929585E+09 | 0.00 | 0.00 |
March | 0.370749E+10 | 0.111391E+10 | 0.233953E+10 | 0.110603E+10 | 0.123350E+10 | 0.00 | 0.00 |
April | 0.437743E+10 | 0.699347E+09 | 0.245707E+10 | 0.109634E+10 | 0.136074E+10 | 0.00 | 0.00 |
May | 0.469353E+10 | 0.370094E+09 | 0.240197E+10 | 0.956522E+09 | 0.144545E+10 | 0.00 | 0.00 |
June | 0.473630E+10 | 0.139097E+09 | 0.229431E+10 | 0.881229E+09 | 0.141308E+10 | 0.00 | 0.00 |
July | 0.518590E+10 | 0.214823E+09 | 0.243601E+10 | 0.878474E+09 | 0.155753E+10 | 0.00 | 0.00 |
August | 0.462087E+10 | 0.121702E+09 | 0.222752E+10 | 0.744834E+09 | 0.148268E+10 | 0.00 | 0.00 |
September | 0.435761E+10 | 0.270651E+09 | 0.207820E+10 | 0.751276E+09 | 0.132692E+10 | 0.00 | 0.00 |
October | 0.384385E+10 | 0.424218E+09 | 0.197666E+10 | 0.851270E+09 | 0.112539E+10 | 0.00 | 0.00 |
November | 0.268609E+10 | 0.812763E+09 | 0.155257E+10 | 0.619068E+09 | 0.933498E+09 | 0.00 | 0.00 |
December | 0.190817E+10 | 0.144545E+10 | 0.129594E+10 | 0.457530E+09 | 0.838410E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.451963E+11 | 0.862305E+10 | 0.244500E+11 | 0.993875E+10 | 0.145113E+11 | 0.00 | 0.00 |
Minimum of Months | 0.190817E+10 | 0.121702E+09 | 0.129594E+10 | 0.457530E+09 | 0.838410E+09 | 0.00 | 0.00 |
Maximum of Months | 0.518590E+10 | 0.172813E+10 | 0.245707E+10 | 0.110603E+10 | 0.155753E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.780093E+10 | 0.267150E+10 | 0.485877E+10 | 0.315663E+10 | 0.170215E+10 | 0.00 | 0.00 |
February | 0.674267E+10 | 0.205095E+10 | 0.397011E+10 | 0.229719E+10 | 0.167292E+10 | 0.00 | 0.00 |
March | 0.581581E+10 | 0.185197E+10 | 0.337474E+10 | 0.142680E+10 | 0.194793E+10 | 0.00 | 0.00 |
April | 0.422130E+10 | 0.117265E+10 | 0.222074E+10 | 0.389429E+09 | 0.183132E+10 | 0.00 | 0.00 |
May | 0.385941E+10 | 0.579034E+09 | 0.183889E+10 | 39783447.48 | 0.179911E+10 | 0.00 | 0.00 |
June | 0.384760E+10 | 0.238449E+09 | 0.169667E+10 | 3201853.87 | 0.169347E+10 | 0.00 | 0.00 |
July | 0.444043E+10 | 0.360071E+09 | 0.187723E+10 | 17400017.26 | 0.185983E+10 | 0.00 | 0.00 |
August | 0.478949E+10 | 0.250656E+09 | 0.213059E+10 | 0.179789E+09 | 0.195080E+10 | 0.00 | 0.00 |
September | 0.591348E+10 | 0.447936E+09 | 0.263944E+10 | 0.646797E+09 | 0.199265E+10 | 0.00 | 0.00 |
October | 0.743972E+10 | 0.778707E+09 | 0.375075E+10 | 0.175973E+10 | 0.199102E+10 | 0.00 | 0.00 |
November | 0.732105E+10 | 0.138842E+10 | 0.412985E+10 | 0.230491E+10 | 0.182495E+10 | 0.00 | 0.00 |
December | 0.769420E+10 | 0.235462E+10 | 0.468250E+10 | 0.295345E+10 | 0.172905E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.698861E+11 | 0.141450E+11 | 0.371703E+11 | 0.151751E+11 | 0.219952E+11 | 0.00 | 0.00 |
Minimum of Months | 0.384760E+10 | 0.238449E+09 | 0.169667E+10 | 3201853.87 | 0.167292E+10 | 0.00 | 0.00 |
Maximum of Months | 0.780093E+10 | 0.267150E+10 | 0.485877E+10 | 0.315663E+10 | 0.199265E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.210716E+10 | 0.203549E+10 | 0.149080E+10 | 0.642705E+09 | 0.848095E+09 | 0.00 | 0.00 |
February | 0.264736E+10 | 0.162833E+10 | 0.168380E+10 | 0.762015E+09 | 0.921783E+09 | 0.00 | 0.00 |
March | 0.367610E+10 | 0.154490E+10 | 0.232151E+10 | 0.106012E+10 | 0.126139E+10 | 0.00 | 0.00 |
April | 0.428149E+10 | 0.104917E+10 | 0.247288E+10 | 0.114502E+10 | 0.132785E+10 | 0.00 | 0.00 |
May | 0.452006E+10 | 0.544443E+09 | 0.232949E+10 | 0.896745E+09 | 0.143275E+10 | 0.00 | 0.00 |
June | 0.389159E+10 | 0.280681E+09 | 0.191012E+10 | 0.535807E+09 | 0.137432E+10 | 0.00 | 0.00 |
July | 0.460105E+10 | 0.417219E+09 | 0.220589E+10 | 0.682434E+09 | 0.152346E+10 | 0.00 | 0.00 |
August | 0.435721E+10 | 0.381023E+09 | 0.220088E+10 | 0.717262E+09 | 0.148361E+10 | 0.00 | 0.00 |
September | 0.378158E+10 | 0.375047E+09 | 0.181690E+10 | 0.535747E+09 | 0.128115E+10 | 0.00 | 0.00 |
October | 0.356058E+10 | 0.666332E+09 | 0.186773E+10 | 0.728099E+09 | 0.113963E+10 | 0.00 | 0.00 |
November | 0.251873E+10 | 0.118194E+10 | 0.149098E+10 | 0.546901E+09 | 0.944082E+09 | 0.00 | 0.00 |
December | 0.226389E+10 | 0.194379E+10 | 0.154344E+10 | 0.690060E+09 | 0.853379E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.422068E+11 | 0.120484E+11 | 0.233344E+11 | 0.894292E+10 | 0.143915E+11 | 0.00 | 0.00 |
Minimum of Months | 0.210716E+10 | 0.280681E+09 | 0.149080E+10 | 0.535747E+09 | 0.848095E+09 | 0.00 | 0.00 |
Maximum of Months | 0.460105E+10 | 0.203549E+10 | 0.247288E+10 | 0.114502E+10 | 0.152346E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112252E+10 | 0.254963E+10 | 0.103383E+10 | 0.00 | 0.103383E+10 | 0.00 | 0.00 |
February | 0.152975E+10 | 0.190296E+10 | 0.110528E+10 | 0.00 | 0.110528E+10 | 0.00 | 0.00 |
March | 0.201420E+10 | 0.175533E+10 | 0.145935E+10 | 0.00 | 0.145935E+10 | 0.00 | 0.00 |
April | 0.273591E+10 | 0.107033E+10 | 0.158252E+10 | 7108834.21 | 0.157541E+10 | 0.00 | 0.00 |
May | 0.391035E+10 | 0.570752E+09 | 0.186739E+10 | 83532699.08 | 0.178386E+10 | 0.00 | 0.00 |
June | 0.436826E+10 | 0.247429E+09 | 0.193043E+10 | 0.138996E+09 | 0.179143E+10 | 0.00 | 0.00 |
July | 0.479118E+10 | 0.365333E+09 | 0.201864E+10 | 98917379.94 | 0.191972E+10 | 0.00 | 0.00 |
August | 0.405170E+10 | 0.236185E+09 | 0.178653E+10 | 16431133.84 | 0.177010E+10 | 0.00 | 0.00 |
September | 0.361644E+10 | 0.402024E+09 | 0.153374E+10 | 121333.23 | 0.153362E+10 | 0.00 | 0.00 |
October | 0.275542E+10 | 0.648552E+09 | 0.132773E+10 | 0.00 | 0.132773E+10 | 0.00 | 0.00 |
November | 0.186404E+10 | 0.125683E+10 | 0.111723E+10 | 0.00 | 0.111723E+10 | 0.00 | 0.00 |
December | 0.126176E+10 | 0.216752E+10 | 0.102258E+10 | 0.00 | 0.102258E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.340215E+11 | 0.131729E+11 | 0.177852E+11 | 0.345108E+09 | 0.174401E+11 | 0.00 | 0.00 |
Minimum of Months | 0.112252E+10 | 0.236185E+09 | 0.102258E+10 | 0.00 | 0.102258E+10 | 0.00 | 0.00 |
Maximum of Months | 0.479118E+10 | 0.254963E+10 | 0.201864E+10 | 0.138996E+09 | 0.191972E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.237687E+10 | 0.163983E+10 | 0.165951E+10 | 0.795008E+09 | 0.864502E+09 | 0.00 | 0.00 |
February | 0.269627E+10 | 0.122788E+10 | 0.173075E+10 | 0.801166E+09 | 0.929581E+09 | 0.00 | 0.00 |
March | 0.365612E+10 | 0.111870E+10 | 0.233952E+10 | 0.110602E+10 | 0.123349E+10 | 0.00 | 0.00 |
April | 0.431705E+10 | 0.746003E+09 | 0.245706E+10 | 0.109633E+10 | 0.136073E+10 | 0.00 | 0.00 |
May | 0.464630E+10 | 0.384463E+09 | 0.240196E+10 | 0.956518E+09 | 0.144545E+10 | 0.00 | 0.00 |
June | 0.467941E+10 | 0.170781E+09 | 0.229430E+10 | 0.881225E+09 | 0.141308E+10 | 0.00 | 0.00 |
July | 0.514170E+10 | 0.263262E+09 | 0.243600E+10 | 0.878471E+09 | 0.155753E+10 | 0.00 | 0.00 |
August | 0.457977E+10 | 0.165870E+09 | 0.222751E+10 | 0.744831E+09 | 0.148268E+10 | 0.00 | 0.00 |
September | 0.432060E+10 | 0.285213E+09 | 0.207819E+10 | 0.751273E+09 | 0.132691E+10 | 0.00 | 0.00 |
October | 0.380829E+10 | 0.455990E+09 | 0.197665E+10 | 0.851267E+09 | 0.112538E+10 | 0.00 | 0.00 |
November | 0.266301E+10 | 0.813515E+09 | 0.155256E+10 | 0.619066E+09 | 0.933494E+09 | 0.00 | 0.00 |
December | 0.190569E+10 | 0.140734E+10 | 0.129593E+10 | 0.457528E+09 | 0.838407E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.447911E+11 | 0.867884E+10 | 0.244499E+11 | 0.993871E+10 | 0.145112E+11 | 0.00 | 0.00 |
Minimum of Months | 0.190569E+10 | 0.165870E+09 | 0.129593E+10 | 0.457528E+09 | 0.838407E+09 | 0.00 | 0.00 |
Maximum of Months | 0.514170E+10 | 0.163983E+10 | 0.245706E+10 | 0.110602E+10 | 0.155753E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.771981E+10 | 0.263288E+10 | 0.485892E+10 | 0.315673E+10 | 0.170219E+10 | 0.00 | 0.00 |
February | 0.667939E+10 | 0.200320E+10 | 0.397022E+10 | 0.229726E+10 | 0.167296E+10 | 0.00 | 0.00 |
March | 0.576335E+10 | 0.181871E+10 | 0.337482E+10 | 0.142685E+10 | 0.194798E+10 | 0.00 | 0.00 |
April | 0.421926E+10 | 0.115270E+10 | 0.222079E+10 | 0.389441E+09 | 0.183135E+10 | 0.00 | 0.00 |
May | 0.387116E+10 | 0.557715E+09 | 0.183893E+10 | 39784750.56 | 0.179914E+10 | 0.00 | 0.00 |
June | 0.387761E+10 | 0.244574E+09 | 0.169670E+10 | 3201958.74 | 0.169350E+10 | 0.00 | 0.00 |
July | 0.449127E+10 | 0.360525E+09 | 0.187726E+10 | 17400587.18 | 0.185986E+10 | 0.00 | 0.00 |
August | 0.483860E+10 | 0.250391E+09 | 0.213063E+10 | 0.179794E+09 | 0.195084E+10 | 0.00 | 0.00 |
September | 0.589407E+10 | 0.450643E+09 | 0.263951E+10 | 0.646818E+09 | 0.199269E+10 | 0.00 | 0.00 |
October | 0.738380E+10 | 0.795650E+09 | 0.375085E+10 | 0.175978E+10 | 0.199107E+10 | 0.00 | 0.00 |
November | 0.725594E+10 | 0.137615E+10 | 0.412998E+10 | 0.230498E+10 | 0.182499E+10 | 0.00 | 0.00 |
December | 0.762987E+10 | 0.231761E+10 | 0.468264E+10 | 0.295354E+10 | 0.172909E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.696241E+11 | 0.139607E+11 | 0.371713E+11 | 0.151756E+11 | 0.219957E+11 | 0.00 | 0.00 |
Minimum of Months | 0.387116E+10 | 0.244574E+09 | 0.169670E+10 | 3201958.74 | 0.167296E+10 | 0.00 | 0.00 |
Maximum of Months | 0.771981E+10 | 0.263288E+10 | 0.485892E+10 | 0.315673E+10 | 0.199269E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.216299E+10 | 0.180407E+10 | 0.149079E+10 | 0.642703E+09 | 0.848091E+09 | 0.00 | 0.00 |
February | 0.271516E+10 | 0.140055E+10 | 0.168379E+10 | 0.762012E+09 | 0.921779E+09 | 0.00 | 0.00 |
March | 0.374265E+10 | 0.132808E+10 | 0.232150E+10 | 0.106012E+10 | 0.126138E+10 | 0.00 | 0.00 |
April | 0.437454E+10 | 0.886519E+09 | 0.247286E+10 | 0.114502E+10 | 0.132785E+10 | 0.00 | 0.00 |
May | 0.454098E+10 | 0.487566E+09 | 0.232948E+10 | 0.896742E+09 | 0.143274E+10 | 0.00 | 0.00 |
June | 0.396478E+10 | 0.223249E+09 | 0.191011E+10 | 0.535805E+09 | 0.137431E+10 | 0.00 | 0.00 |
July | 0.470390E+10 | 0.327966E+09 | 0.220588E+10 | 0.682431E+09 | 0.152345E+10 | 0.00 | 0.00 |
August | 0.449067E+10 | 0.245410E+09 | 0.220087E+10 | 0.717259E+09 | 0.148361E+10 | 0.00 | 0.00 |
September | 0.382295E+10 | 0.327549E+09 | 0.181689E+10 | 0.535745E+09 | 0.128115E+10 | 0.00 | 0.00 |
October | 0.361805E+10 | 0.555686E+09 | 0.186772E+10 | 0.728096E+09 | 0.113963E+10 | 0.00 | 0.00 |
November | 0.260546E+10 | 0.953838E+09 | 0.149098E+10 | 0.546899E+09 | 0.944078E+09 | 0.00 | 0.00 |
December | 0.236988E+10 | 0.158208E+10 | 0.154343E+10 | 0.690057E+09 | 0.853376E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.431120E+11 | 0.101226E+11 | 0.233343E+11 | 0.894288E+10 | 0.143914E+11 | 0.00 | 0.00 |
Minimum of Months | 0.216299E+10 | 0.223249E+09 | 0.149079E+10 | 0.535745E+09 | 0.848091E+09 | 0.00 | 0.00 |
Maximum of Months | 0.470390E+10 | 0.180407E+10 | 0.247286E+10 | 0.114502E+10 | 0.152345E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117453E+10 | 0.234030E+10 | 0.103383E+10 | 0.00 | 0.103383E+10 | 0.00 | 0.00 |
February | 0.154668E+10 | 0.179273E+10 | 0.110528E+10 | 0.00 | 0.110528E+10 | 0.00 | 0.00 |
March | 0.200053E+10 | 0.168605E+10 | 0.145935E+10 | 0.00 | 0.145935E+10 | 0.00 | 0.00 |
April | 0.268005E+10 | 0.107754E+10 | 0.158252E+10 | 7108834.21 | 0.157541E+10 | 0.00 | 0.00 |
May | 0.383108E+10 | 0.606901E+09 | 0.186739E+10 | 83532699.08 | 0.178386E+10 | 0.00 | 0.00 |
June | 0.426998E+10 | 0.271179E+09 | 0.193043E+10 | 0.138996E+09 | 0.179143E+10 | 0.00 | 0.00 |
July | 0.468590E+10 | 0.406342E+09 | 0.201864E+10 | 98917379.94 | 0.191972E+10 | 0.00 | 0.00 |
August | 0.396923E+10 | 0.262411E+09 | 0.178653E+10 | 16431133.84 | 0.177010E+10 | 0.00 | 0.00 |
September | 0.352226E+10 | 0.419477E+09 | 0.153374E+10 | 121333.23 | 0.153362E+10 | 0.00 | 0.00 |
October | 0.270194E+10 | 0.662703E+09 | 0.132773E+10 | 0.00 | 0.132773E+10 | 0.00 | 0.00 |
November | 0.185586E+10 | 0.119377E+10 | 0.111723E+10 | 0.00 | 0.111723E+10 | 0.00 | 0.00 |
December | 0.129472E+10 | 0.201103E+10 | 0.102258E+10 | 0.00 | 0.102258E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.335328E+11 | 0.127304E+11 | 0.177852E+11 | 0.345108E+09 | 0.174401E+11 | 0.00 | 0.00 |
Minimum of Months | 0.117453E+10 | 0.262411E+09 | 0.102258E+10 | 0.00 | 0.102258E+10 | 0.00 | 0.00 |
Maximum of Months | 0.468590E+10 | 0.234030E+10 | 0.201864E+10 | 0.138996E+09 | 0.191972E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.240866E+10 | 0.154039E+10 | 0.165951E+10 | 0.795008E+09 | 0.864502E+09 | 0.00 | 0.00 |
February | 0.270226E+10 | 0.117568E+10 | 0.173075E+10 | 0.801166E+09 | 0.929581E+09 | 0.00 | 0.00 |
March | 0.363262E+10 | 0.109415E+10 | 0.233952E+10 | 0.110602E+10 | 0.123349E+10 | 0.00 | 0.00 |
April | 0.427034E+10 | 0.755178E+09 | 0.245706E+10 | 0.109633E+10 | 0.136073E+10 | 0.00 | 0.00 |
May | 0.458569E+10 | 0.408131E+09 | 0.240196E+10 | 0.956518E+09 | 0.144545E+10 | 0.00 | 0.00 |
June | 0.461009E+10 | 0.185588E+09 | 0.229430E+10 | 0.881225E+09 | 0.141308E+10 | 0.00 | 0.00 |
July | 0.506995E+10 | 0.288718E+09 | 0.243600E+10 | 0.878471E+09 | 0.155753E+10 | 0.00 | 0.00 |
August | 0.452001E+10 | 0.182076E+09 | 0.222751E+10 | 0.744831E+09 | 0.148268E+10 | 0.00 | 0.00 |
September | 0.425545E+10 | 0.296700E+09 | 0.207819E+10 | 0.751273E+09 | 0.132691E+10 | 0.00 | 0.00 |
October | 0.376591E+10 | 0.467554E+09 | 0.197665E+10 | 0.851267E+09 | 0.112538E+10 | 0.00 | 0.00 |
November | 0.265156E+10 | 0.784572E+09 | 0.155256E+10 | 0.619066E+09 | 0.933494E+09 | 0.00 | 0.00 |
December | 0.192471E+10 | 0.132642E+10 | 0.129593E+10 | 0.457528E+09 | 0.838407E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.443972E+11 | 0.850516E+10 | 0.244499E+11 | 0.993871E+10 | 0.145112E+11 | 0.00 | 0.00 |
Minimum of Months | 0.192471E+10 | 0.182076E+09 | 0.129593E+10 | 0.457528E+09 | 0.838407E+09 | 0.00 | 0.00 |
Maximum of Months | 0.506995E+10 | 0.154039E+10 | 0.245706E+10 | 0.110602E+10 | 0.155753E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.775202E+10 | 0.249402E+10 | 0.485892E+10 | 0.315673E+10 | 0.170219E+10 | 0.00 | 0.00 |
February | 0.667707E+10 | 0.192786E+10 | 0.397022E+10 | 0.229726E+10 | 0.167296E+10 | 0.00 | 0.00 |
March | 0.572716E+10 | 0.177515E+10 | 0.337482E+10 | 0.142685E+10 | 0.194798E+10 | 0.00 | 0.00 |
April | 0.415785E+10 | 0.116405E+10 | 0.222079E+10 | 0.389441E+09 | 0.183135E+10 | 0.00 | 0.00 |
May | 0.378973E+10 | 0.592194E+09 | 0.183893E+10 | 39784750.56 | 0.179914E+10 | 0.00 | 0.00 |
June | 0.378032E+10 | 0.267731E+09 | 0.169670E+10 | 3201958.74 | 0.169350E+10 | 0.00 | 0.00 |
July | 0.438515E+10 | 0.401104E+09 | 0.187726E+10 | 17400587.18 | 0.185986E+10 | 0.00 | 0.00 |
August | 0.475159E+10 | 0.275768E+09 | 0.213063E+10 | 0.179794E+09 | 0.195084E+10 | 0.00 | 0.00 |
September | 0.580098E+10 | 0.470819E+09 | 0.263951E+10 | 0.646818E+09 | 0.199269E+10 | 0.00 | 0.00 |
October | 0.732568E+10 | 0.814600E+09 | 0.375085E+10 | 0.175978E+10 | 0.199107E+10 | 0.00 | 0.00 |
November | 0.723617E+10 | 0.133788E+10 | 0.412998E+10 | 0.230498E+10 | 0.182499E+10 | 0.00 | 0.00 |
December | 0.763634E+10 | 0.221121E+10 | 0.468264E+10 | 0.295354E+10 | 0.172909E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.690201E+11 | 0.137324E+11 | 0.371713E+11 | 0.151756E+11 | 0.219957E+11 | 0.00 | 0.00 |
Minimum of Months | 0.378032E+10 | 0.267731E+09 | 0.169670E+10 | 3201958.74 | 0.167296E+10 | 0.00 | 0.00 |
Maximum of Months | 0.775202E+10 | 0.249402E+10 | 0.485892E+10 | 0.315673E+10 | 0.199269E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.218436E+10 | 0.168554E+10 | 0.149079E+10 | 0.642703E+09 | 0.848091E+09 | 0.00 | 0.00 |
February | 0.271376E+10 | 0.134040E+10 | 0.168379E+10 | 0.762012E+09 | 0.921779E+09 | 0.00 | 0.00 |
March | 0.372055E+10 | 0.128951E+10 | 0.232150E+10 | 0.106012E+10 | 0.126138E+10 | 0.00 | 0.00 |
April | 0.433323E+10 | 0.888983E+09 | 0.247286E+10 | 0.114502E+10 | 0.132785E+10 | 0.00 | 0.00 |
May | 0.448976E+10 | 0.505802E+09 | 0.232948E+10 | 0.896742E+09 | 0.143274E+10 | 0.00 | 0.00 |
June | 0.390995E+10 | 0.235488E+09 | 0.191011E+10 | 0.535805E+09 | 0.137431E+10 | 0.00 | 0.00 |
July | 0.464355E+10 | 0.345520E+09 | 0.220588E+10 | 0.682431E+09 | 0.152345E+10 | 0.00 | 0.00 |
August | 0.444146E+10 | 0.260144E+09 | 0.220087E+10 | 0.717259E+09 | 0.148361E+10 | 0.00 | 0.00 |
September | 0.377275E+10 | 0.336359E+09 | 0.181689E+10 | 0.535745E+09 | 0.128115E+10 | 0.00 | 0.00 |
October | 0.358329E+10 | 0.560982E+09 | 0.186772E+10 | 0.728096E+09 | 0.113963E+10 | 0.00 | 0.00 |
November | 0.259389E+10 | 0.918819E+09 | 0.149098E+10 | 0.546899E+09 | 0.944078E+09 | 0.00 | 0.00 |
December | 0.238018E+10 | 0.149257E+10 | 0.154343E+10 | 0.690057E+09 | 0.853376E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.427667E+11 | 0.986012E+10 | 0.233343E+11 | 0.894288E+10 | 0.143914E+11 | 0.00 | 0.00 |
Minimum of Months | 0.218436E+10 | 0.235488E+09 | 0.149079E+10 | 0.535745E+09 | 0.848091E+09 | 0.00 | 0.00 |
Maximum of Months | 0.464355E+10 | 0.168554E+10 | 0.247286E+10 | 0.114502E+10 | 0.152345E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.282871E+11 | -0.272688E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101833E+10 | 58.96 | 0.00 | 0.00 |
February | 0.254630E+11 | -0.245421E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -920854633.6 | 58.97 | 0.00 | 0.00 |
March | 0.289961E+11 | -0.279730E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102318E+10 | 58.97 | 0.00 | 0.00 |
April | 0.251801E+11 | -0.241926E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987435501.3 | 58.98 | 0.00 | 0.00 |
May | 0.255675E+11 | -0.245465E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102101E+10 | 58.97 | 0.00 | 0.00 |
June | 0.243402E+11 | -0.233507E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989478543.5 | 58.97 | 0.00 | 0.00 |
July | 0.228236E+11 | -0.218064E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101721E+10 | 58.97 | 0.00 | 0.00 |
August | 0.251881E+11 | -0.241669E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102128E+10 | 58.97 | 0.00 | 0.00 |
September | 0.237481E+11 | -0.227621E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986010788.1 | 58.97 | 0.00 | 0.00 |
October | 0.257133E+11 | -0.246963E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101700E+10 | 58.96 | 0.00 | 0.00 |
November | 0.264326E+11 | -0.254482E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -984466843.3 | 58.97 | 0.00 | 0.00 |
December | 0.272634E+11 | -0.262462E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101728E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.309003E+12 | -0.297000E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120036E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.228236E+11 | -0.279730E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102318E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.289961E+11 | -0.218064E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -920854633.6 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.51 | 0.48 | 01-JAN-07:40 | 5710.61 | 35.15 | 274.17 | 285.67 | 993.97 | 24.57 | 167.67 | 261.50 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-08:30 | 1988.46 | 24.11 | 133.83 | 271.33 | 762.83 | 19.64 | 79.00 | 234.83 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:00 | 1177.48 | 16.97 | 5.67 | 309.17 | 634.05 | 19.56 | 54.00 | 268.67 |
April | 357.50 | 0.52 | 0.48 | 01-APR-08:39 | 911.99 | 16.20 | 0.00 | 312.00 | 511.86 | 19.03 | 5.00 | 251.83 |
May | 389.00 | 0.53 | 0.48 | 01-MAY-07:40 | 784.16 | 15.63 | 0.00 | 325.33 | 434.95 | 18.49 | 0.00 | 244.83 |
June | 388.17 | 0.55 | 0.48 | 01-JUN-07:40 | 742.07 | 14.92 | 0.00 | 302.50 | 407.15 | 17.79 | 0.50 | 227.33 |
July | 403.83 | 0.53 | 0.48 | 01-JUL-07:19 | 830.03 | 15.86 | 0.00 | 335.17 | 456.98 | 18.76 | 0.83 | 264.83 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:49 | 989.08 | 16.47 | 0.00 | 327.50 | 532.41 | 19.32 | 14.67 | 269.50 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:30 | 1193.21 | 16.80 | 0.00 | 304.17 | 622.62 | 19.68 | 74.83 | 251.67 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-11:39 | 1586.59 | 18.73 | 30.50 | 304.67 | 762.10 | 20.33 | 123.00 | 262.50 |
November | 314.83 | 0.51 | 0.48 | 01-NOV-07:10 | 3152.64 | 29.64 | 236.50 | 282.67 | 851.33 | 22.24 | 174.00 | 253.00 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:39 | 5368.45 | 34.15 | 264.50 | 269.00 | 1179.83 | 25.94 | 189.83 | 253.00 |
Annual Sum or Average | 4111.50 | 0.52 | 1875.35 | 20.50 | 945.17 | 3629.17 | 655.08 | 20.22 | 883.33 | 3043.50 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 742.07 | 14.92 | 0.00 | 269.00 | 407.15 | 17.79 | 0.00 | 227.33 | |
Maximum of Months | 403.83 | 0.55 | 0.48 | 5710.61 | 35.15 | 274.17 | 335.17 | 1179.83 | 25.94 | 189.83 | 269.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-07:49 | 1653.04 | 19.49 | 81.67 | 239.17 | 894.51 | 22.62 | 84.17 | 180.33 |
February | 304.33 | 0.54 | 0.48 | 01-FEB-07:00 | 1706.90 | 18.75 | 75.67 | 236.00 | 642.04 | 20.65 | 60.83 | 183.83 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:30 | 1636.87 | 18.91 | 84.83 | 297.67 | 827.77 | 20.71 | 69.83 | 240.00 |
April | 357.50 | 0.52 | 0.48 | 01-APR-06:00 | 1905.12 | 18.52 | 80.67 | 299.83 | 1036.17 | 21.70 | 79.00 | 241.67 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-06:19 | 1816.32 | 19.46 | 103.00 | 328.67 | 723.43 | 20.19 | 60.83 | 264.00 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-06:10 | 1767.09 | 19.68 | 111.00 | 319.67 | 706.09 | 20.23 | 71.17 | 249.67 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-06:30 | 1731.26 | 19.91 | 113.33 | 341.83 | 729.48 | 20.69 | 85.50 | 277.00 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-06:49 | 1653.97 | 18.68 | 75.50 | 324.83 | 886.43 | 21.96 | 93.33 | 265.50 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-06:49 | 1637.61 | 19.21 | 84.00 | 290.33 | 849.56 | 22.33 | 105.17 | 239.33 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-07:19 | 1617.78 | 19.49 | 81.33 | 281.50 | 857.65 | 22.17 | 91.83 | 233.67 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-06:00 | 1299.90 | 19.39 | 80.83 | 248.33 | 640.64 | 20.96 | 81.83 | 191.17 |
December | 282.67 | 0.54 | 0.48 | 01-DEC-08:39 | 1389.83 | 19.17 | 75.17 | 227.50 | 563.00 | 20.28 | 63.83 | 165.17 |
Annual Sum or Average | 4111.50 | 0.53 | 1662.27 | 19.23 | 1047.00 | 3435.33 | 782.43 | 21.18 | 947.33 | 2731.33 | ||
Minimum of Months | 282.67 | 0.52 | 0.48 | 1299.90 | 18.52 | 75.17 | 227.50 | 563.00 | 20.19 | 60.83 | 165.17 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 1905.12 | 19.91 | 113.33 | 341.83 | 1036.17 | 22.62 | 105.17 | 277.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.58 | 0.48 | 01-JAN-10:20 | 401.80 | 12.41 | 0.00 | 191.83 | 258.13 | 15.67 | 0.00 | 40.17 |
February | 304.33 | 0.56 | 0.48 | 01-FEB-09:50 | 461.24 | 13.36 | 0.00 | 215.67 | 286.75 | 16.44 | 0.00 | 80.17 |
March | 362.67 | 0.53 | 0.48 | 01-MAR-10:00 | 554.07 | 14.59 | 0.00 | 280.00 | 336.41 | 17.56 | 0.00 | 173.67 |
April | 357.50 | 0.52 | 0.48 | 01-APR-08:50 | 663.30 | 15.60 | 0.00 | 316.67 | 395.88 | 18.43 | 0.00 | 232.00 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:40 | 793.33 | 16.26 | 1.33 | 351.83 | 443.17 | 20.00 | 24.83 | 276.67 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-06:49 | 845.41 | 17.40 | 32.83 | 333.33 | 452.78 | 18.92 | 12.67 | 264.83 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:40 | 890.22 | 16.61 | 0.00 | 360.17 | 486.35 | 20.51 | 27.17 | 303.67 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:40 | 799.83 | 16.25 | 0.00 | 337.83 | 451.18 | 19.09 | 0.00 | 273.00 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:40 | 671.55 | 15.33 | 0.00 | 298.00 | 383.81 | 18.19 | 0.00 | 210.17 |
October | 323.50 | 0.54 | 0.48 | 02-OCT-11:39 | 527.47 | 14.22 | 0.00 | 266.50 | 324.63 | 17.23 | 0.00 | 145.83 |
November | 314.83 | 0.56 | 0.48 | 01-NOV-08:39 | 466.72 | 13.55 | 0.00 | 218.83 | 281.01 | 16.62 | 0.00 | 77.83 |
December | 282.67 | 0.56 | 0.48 | 01-DEC-09:30 | 440.54 | 13.20 | 0.00 | 200.67 | 273.46 | 16.42 | 0.00 | 42.17 |
Annual Sum or Average | 4111.50 | 0.53 | 643.45 | 15.06 | 34.17 | 3371.33 | 372.51 | 18.08 | 64.67 | 2120.17 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 401.80 | 12.41 | 0.00 | 191.83 | 258.13 | 15.67 | 0.00 | 40.17 | |
Maximum of Months | 403.83 | 0.58 | 0.48 | 890.22 | 17.40 | 32.83 | 360.17 | 486.35 | 20.51 | 27.17 | 303.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.55 | 0.48 | 01-JAN-10:20 | 1407.42 | 18.51 | 71.50 | 237.17 | 791.88 | 21.91 | 79.83 | 166.17 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-09:50 | 1206.12 | 16.94 | 46.50 | 239.50 | 659.23 | 20.40 | 61.17 | 180.00 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-10:50 | 1605.13 | 18.95 | 85.00 | 292.00 | 799.07 | 20.75 | 68.33 | 235.83 |
April | 357.50 | 0.51 | 0.48 | 01-APR-09:09 | 1742.66 | 18.78 | 80.50 | 312.17 | 942.35 | 20.71 | 62.00 | 257.00 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-08:20 | 1575.82 | 14.34 | 0.00 | 328.33 | 819.50 | 18.13 | 9.50 | 265.00 |
June | 388.17 | 0.54 | 0.48 | 01-JUN-08:39 | 1314.28 | 13.95 | 0.00 | 310.67 | 581.79 | 17.64 | 27.17 | 248.17 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-08:39 | 1488.87 | 14.95 | 3.67 | 335.83 | 656.55 | 18.49 | 34.50 | 279.17 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-08:20 | 1613.55 | 17.65 | 56.83 | 322.17 | 829.24 | 18.93 | 37.67 | 266.83 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-08:30 | 1339.81 | 18.83 | 79.00 | 294.67 | 675.90 | 20.71 | 80.67 | 236.17 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-11:39 | 1594.24 | 19.28 | 83.33 | 275.00 | 853.10 | 22.51 | 96.17 | 226.83 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-08:50 | 1270.61 | 19.33 | 82.00 | 249.50 | 637.17 | 20.88 | 80.83 | 190.33 |
December | 282.67 | 0.52 | 0.48 | 01-DEC-09:30 | 1462.59 | 20.54 | 81.83 | 244.00 | 739.55 | 21.76 | 75.50 | 179.67 |
Annual Sum or Average | 4111.50 | 0.53 | 1473.98 | 17.50 | 670.17 | 3441.00 | 747.94 | 20.10 | 713.33 | 2731.17 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 1206.12 | 13.95 | 0.00 | 237.17 | 581.79 | 17.64 | 9.50 | 166.17 | |
Maximum of Months | 403.83 | 0.55 | 0.48 | 1742.66 | 20.54 | 85.00 | 335.83 | 942.35 | 22.51 | 96.17 | 279.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.51 | 0.48 | 01-JAN-07:40 | 5693.89 | 34.73 | 274.00 | 285.33 | 1027.86 | 20.50 | 81.00 | 262.50 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-08:30 | 1970.92 | 20.31 | 132.50 | 271.00 | 791.61 | 14.93 | 0.00 | 236.17 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:00 | 1160.74 | 11.14 | 5.67 | 308.00 | 656.16 | 15.62 | 0.00 | 271.50 |
April | 357.50 | 0.52 | 0.48 | 01-APR-08:39 | 896.14 | 10.79 | 0.00 | 310.67 | 527.73 | 15.52 | 0.00 | 256.33 |
May | 389.00 | 0.53 | 0.48 | 01-MAY-07:40 | 768.77 | 10.07 | 0.00 | 323.17 | 447.51 | 14.78 | 0.00 | 251.83 |
June | 388.17 | 0.55 | 0.48 | 01-JUN-07:40 | 727.19 | 9.29 | 0.00 | 301.33 | 418.85 | 13.96 | 0.00 | 232.50 |
July | 403.83 | 0.53 | 0.48 | 01-JUL-07:19 | 813.00 | 10.23 | 0.00 | 333.17 | 469.66 | 14.96 | 0.00 | 269.00 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:49 | 968.34 | 10.92 | 0.00 | 325.17 | 547.18 | 15.59 | 0.00 | 271.67 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:30 | 1167.88 | 10.88 | 0.00 | 301.50 | 640.31 | 15.55 | 0.00 | 254.17 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-11:39 | 1572.03 | 12.94 | 28.50 | 308.17 | 787.97 | 16.49 | 9.17 | 266.00 |
November | 314.83 | 0.51 | 0.48 | 01-NOV-07:10 | 3107.85 | 26.76 | 223.67 | 279.67 | 889.56 | 19.73 | 71.17 | 260.50 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:39 | 5332.27 | 33.36 | 262.67 | 268.00 | 1211.97 | 22.01 | 92.50 | 253.67 |
Annual Sum or Average | 4111.50 | 0.52 | 1854.52 | 15.89 | 927.00 | 3615.17 | 676.38 | 16.41 | 253.83 | 3085.83 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 727.19 | 9.29 | 0.00 | 268.00 | 418.85 | 13.96 | 0.00 | 232.50 | |
Maximum of Months | 403.83 | 0.55 | 0.48 | 5693.89 | 34.73 | 274.00 | 333.17 | 1211.97 | 22.01 | 92.50 | 271.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-07:49 | 1652.13 | 16.82 | 81.67 | 239.67 | 913.03 | 20.81 | 74.00 | 187.17 |
February | 304.33 | 0.54 | 0.48 | 01-FEB-07:00 | 1706.45 | 15.74 | 75.33 | 234.67 | 661.27 | 18.26 | 45.50 | 188.83 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:30 | 1645.56 | 15.74 | 84.50 | 296.83 | 850.71 | 18.18 | 54.50 | 246.50 |
April | 357.50 | 0.52 | 0.48 | 01-APR-06:00 | 1890.14 | 15.34 | 80.67 | 299.50 | 1058.51 | 19.36 | 70.67 | 247.83 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-06:19 | 1710.37 | 14.58 | 76.33 | 328.00 | 745.07 | 17.52 | 49.50 | 270.17 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-06:10 | 1758.61 | 16.58 | 110.00 | 319.67 | 726.74 | 17.54 | 53.00 | 254.67 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-06:30 | 1657.75 | 15.08 | 85.67 | 340.67 | 750.46 | 18.09 | 56.00 | 283.00 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-06:49 | 1633.80 | 15.43 | 75.50 | 324.50 | 907.40 | 19.73 | 70.67 | 271.17 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-06:49 | 1631.87 | 16.03 | 84.00 | 289.67 | 865.66 | 19.90 | 72.67 | 242.50 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-07:30 | 1621.11 | 16.60 | 81.33 | 280.83 | 839.73 | 18.73 | 52.83 | 236.17 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-06:00 | 1293.90 | 16.47 | 80.33 | 248.17 | 657.68 | 18.70 | 51.67 | 195.50 |
December | 282.67 | 0.54 | 0.48 | 01-DEC-08:39 | 1384.20 | 16.45 | 75.17 | 227.17 | 578.52 | 18.13 | 34.50 | 171.00 |
Annual Sum or Average | 4111.50 | 0.53 | 1640.81 | 15.86 | 990.50 | 3429.33 | 799.28 | 18.70 | 685.50 | 2794.50 | ||
Minimum of Months | 282.67 | 0.52 | 0.48 | 1293.90 | 14.58 | 75.17 | 227.17 | 578.52 | 17.52 | 34.50 | 171.00 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 1890.14 | 16.82 | 110.00 | 340.67 | 1058.51 | 20.81 | 74.00 | 283.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.58 | 0.48 | 01-JAN-10:09 | 394.75 | 7.15 | 0.00 | 187.33 | 265.46 | 12.10 | 0.00 | 51.00 |
February | 304.33 | 0.56 | 0.48 | 01-FEB-09:39 | 453.48 | 8.00 | 0.00 | 211.83 | 295.19 | 12.91 | 0.00 | 95.50 |
March | 362.67 | 0.53 | 0.48 | 01-MAR-10:30 | 544.97 | 9.41 | 0.00 | 278.00 | 346.48 | 14.29 | 0.00 | 185.17 |
April | 357.50 | 0.52 | 0.48 | 01-APR-08:50 | 652.63 | 10.51 | 0.00 | 315.00 | 407.81 | 15.33 | 0.00 | 240.50 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:40 | 779.30 | 10.63 | 1.33 | 350.67 | 456.44 | 16.65 | 25.67 | 287.50 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-06:30 | 830.95 | 12.14 | 32.17 | 332.33 | 475.47 | 16.82 | 32.67 | 281.50 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:40 | 900.24 | 10.84 | 0.00 | 360.50 | 499.79 | 17.01 | 26.17 | 306.67 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:40 | 784.66 | 10.88 | 0.00 | 336.83 | 463.70 | 15.64 | 0.00 | 278.00 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:30 | 658.82 | 9.92 | 0.00 | 296.33 | 394.55 | 14.61 | 0.00 | 217.00 |
October | 323.50 | 0.54 | 0.48 | 02-OCT-11:39 | 517.80 | 9.14 | 0.00 | 264.00 | 333.63 | 13.96 | 0.00 | 156.00 |
November | 314.83 | 0.56 | 0.48 | 01-NOV-08:39 | 457.66 | 7.99 | 0.00 | 215.33 | 288.74 | 12.90 | 0.00 | 89.67 |
December | 282.67 | 0.56 | 0.48 | 01-DEC-09:30 | 431.87 | 7.71 | 0.00 | 197.00 | 280.87 | 12.71 | 0.00 | 54.33 |
Annual Sum or Average | 4111.50 | 0.53 | 634.53 | 9.68 | 33.50 | 3345.17 | 384.08 | 14.76 | 84.50 | 2242.83 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 394.75 | 7.15 | 0.00 | 187.33 | 265.46 | 12.10 | 0.00 | 51.00 | |
Maximum of Months | 403.83 | 0.58 | 0.48 | 900.24 | 12.14 | 32.17 | 360.50 | 499.79 | 17.01 | 32.67 | 306.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-10:09 | 1405.57 | 15.75 | 71.50 | 237.17 | 808.76 | 20.06 | 65.83 | 172.17 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-09:50 | 1205.01 | 13.55 | 46.50 | 239.83 | 677.60 | 18.08 | 45.67 | 185.17 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-10:30 | 1614.12 | 15.75 | 84.67 | 291.17 | 821.64 | 18.19 | 55.83 | 241.00 |
April | 357.50 | 0.52 | 0.48 | 01-APR-09:09 | 1729.92 | 15.60 | 80.33 | 311.17 | 913.40 | 18.07 | 51.83 | 260.83 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-08:09 | 1563.13 | 9.88 | 0.00 | 327.83 | 840.99 | 14.91 | 0.00 | 272.33 |
June | 388.17 | 0.54 | 0.48 | 01-JUN-08:39 | 1307.00 | 9.65 | 0.00 | 310.50 | 599.53 | 14.50 | 0.00 | 253.17 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-08:30 | 1476.47 | 10.60 | 3.67 | 335.00 | 676.05 | 15.38 | 0.00 | 283.67 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-08:20 | 1593.76 | 14.11 | 56.83 | 321.33 | 850.12 | 15.88 | 5.50 | 270.83 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-08:20 | 1333.84 | 15.71 | 78.67 | 293.83 | 693.97 | 18.27 | 51.50 | 240.67 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-11:39 | 1595.41 | 16.39 | 83.33 | 273.83 | 871.38 | 20.45 | 74.00 | 232.83 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-08:39 | 1263.69 | 16.41 | 81.67 | 248.50 | 653.25 | 18.62 | 53.17 | 193.83 |
December | 282.67 | 0.52 | 0.48 | 01-DEC-09:30 | 1458.26 | 17.83 | 81.67 | 243.00 | 757.23 | 19.63 | 52.17 | 186.33 |
Annual Sum or Average | 4111.50 | 0.53 | 1467.43 | 14.04 | 668.83 | 3433.17 | 762.77 | 17.49 | 455.50 | 2792.83 | ||
Minimum of Months | 282.67 | 0.52 | 0.48 | 1205.01 | 9.65 | 0.00 | 237.17 | 599.53 | 14.50 | 0.00 | 172.17 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 1729.92 | 17.83 | 84.67 | 335.00 | 913.40 | 20.45 | 74.00 | 283.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.51 | 0.48 | 01-JAN-07:40 | 5693.79 | 34.71 | 274.00 | 285.33 | 1028.83 | 20.49 | 81.00 | 262.50 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-08:30 | 1971.43 | 20.28 | 132.50 | 271.00 | 792.50 | 14.91 | 0.00 | 236.33 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:00 | 1161.28 | 11.10 | 5.67 | 308.00 | 656.91 | 15.60 | 0.00 | 271.50 |
April | 357.50 | 0.52 | 0.48 | 01-APR-08:39 | 896.53 | 10.75 | 0.00 | 310.67 | 528.31 | 15.50 | 0.00 | 256.83 |
May | 389.00 | 0.53 | 0.48 | 01-MAY-07:40 | 769.11 | 10.03 | 0.00 | 323.17 | 448.01 | 14.76 | 0.00 | 251.83 |
June | 388.17 | 0.55 | 0.48 | 01-JUN-07:40 | 727.57 | 9.25 | 0.00 | 301.33 | 419.33 | 13.94 | 0.00 | 233.17 |
July | 403.83 | 0.53 | 0.48 | 01-JUL-07:19 | 813.37 | 10.19 | 0.00 | 333.17 | 470.19 | 14.94 | 0.00 | 269.00 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:49 | 968.86 | 10.88 | 0.00 | 325.17 | 547.84 | 15.57 | 0.00 | 271.67 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:30 | 1168.63 | 10.84 | 0.00 | 301.50 | 641.17 | 15.53 | 0.00 | 254.33 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-11:39 | 1572.68 | 12.90 | 28.50 | 308.17 | 788.93 | 16.47 | 9.17 | 266.17 |
November | 314.83 | 0.51 | 0.48 | 01-NOV-07:10 | 3108.22 | 26.74 | 223.67 | 279.67 | 890.66 | 19.71 | 71.17 | 260.50 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:39 | 5332.11 | 33.35 | 262.50 | 268.00 | 1213.11 | 22.00 | 92.50 | 253.83 |
Annual Sum or Average | 4111.50 | 0.52 | 1854.92 | 15.86 | 926.83 | 3615.17 | 677.14 | 16.40 | 253.83 | 3087.67 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 727.57 | 9.25 | 0.00 | 268.00 | 419.33 | 13.94 | 0.00 | 233.17 | |
Maximum of Months | 403.83 | 0.55 | 0.48 | 5693.79 | 34.71 | 274.00 | 333.17 | 1213.11 | 22.00 | 92.50 | 271.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-07:49 | 1651.87 | 16.78 | 81.67 | 239.50 | 913.47 | 20.79 | 74.00 | 187.17 |
February | 304.33 | 0.54 | 0.48 | 01-FEB-07:00 | 1706.27 | 15.70 | 75.33 | 234.67 | 661.80 | 18.25 | 45.50 | 189.17 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:30 | 1645.34 | 15.70 | 84.50 | 296.83 | 851.28 | 18.17 | 54.50 | 246.83 |
April | 357.50 | 0.52 | 0.48 | 01-APR-06:00 | 1890.14 | 15.30 | 80.67 | 299.50 | 1059.17 | 19.34 | 70.67 | 248.00 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-06:19 | 1710.48 | 14.54 | 76.33 | 328.00 | 745.75 | 17.51 | 49.50 | 270.50 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-06:10 | 1758.86 | 16.55 | 110.00 | 319.67 | 727.43 | 17.52 | 53.00 | 254.83 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-06:30 | 1657.94 | 15.04 | 85.67 | 340.67 | 751.22 | 18.07 | 56.00 | 283.00 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-06:49 | 1634.00 | 15.39 | 75.50 | 324.50 | 908.17 | 19.71 | 70.67 | 271.17 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-06:49 | 1632.05 | 15.99 | 84.00 | 289.83 | 866.46 | 19.89 | 72.67 | 242.50 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-07:19 | 1620.80 | 16.56 | 81.33 | 280.67 | 840.33 | 18.72 | 52.83 | 236.17 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-06:00 | 1293.78 | 16.43 | 80.33 | 248.00 | 658.24 | 18.69 | 51.67 | 196.00 |
December | 282.67 | 0.54 | 0.48 | 01-DEC-08:39 | 1384.04 | 16.41 | 75.17 | 227.17 | 579.03 | 18.11 | 34.50 | 171.17 |
Annual Sum or Average | 4111.50 | 0.53 | 1640.80 | 15.82 | 990.50 | 3429.00 | 799.92 | 18.68 | 685.50 | 2796.50 | ||
Minimum of Months | 282.67 | 0.52 | 0.48 | 1293.78 | 14.54 | 75.17 | 227.17 | 579.03 | 17.51 | 34.50 | 171.17 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 1890.14 | 16.78 | 110.00 | 340.67 | 1059.17 | 20.79 | 74.00 | 283.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.58 | 0.48 | 01-JAN-10:09 | 394.63 | 7.11 | 0.00 | 187.67 | 265.65 | 12.08 | 0.00 | 51.33 |
February | 304.33 | 0.56 | 0.48 | 01-FEB-09:39 | 453.43 | 7.96 | 0.00 | 212.00 | 295.43 | 12.89 | 0.00 | 95.67 |
March | 362.67 | 0.53 | 0.48 | 01-MAR-10:30 | 544.96 | 9.37 | 0.00 | 278.00 | 346.78 | 14.27 | 0.00 | 185.33 |
April | 357.50 | 0.52 | 0.48 | 01-APR-08:50 | 652.67 | 10.46 | 0.00 | 315.00 | 408.18 | 15.31 | 0.00 | 240.83 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:40 | 779.53 | 10.59 | 1.33 | 350.67 | 456.93 | 16.63 | 25.67 | 288.00 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-06:30 | 831.32 | 12.10 | 32.17 | 332.33 | 476.02 | 16.80 | 32.67 | 282.00 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:40 | 900.54 | 10.80 | 0.00 | 360.50 | 500.36 | 16.99 | 26.17 | 307.00 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:40 | 784.85 | 10.84 | 0.00 | 336.83 | 464.20 | 15.62 | 0.00 | 278.33 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:30 | 658.94 | 9.88 | 0.00 | 296.33 | 394.97 | 14.60 | 0.00 | 217.33 |
October | 323.50 | 0.54 | 0.48 | 02-OCT-11:39 | 517.72 | 9.10 | 0.00 | 264.00 | 333.91 | 13.94 | 0.00 | 156.00 |
November | 314.83 | 0.56 | 0.48 | 01-NOV-08:39 | 457.63 | 7.94 | 0.00 | 215.33 | 289.00 | 12.88 | 0.00 | 90.00 |
December | 282.67 | 0.56 | 0.48 | 01-DEC-09:30 | 431.78 | 7.67 | 0.00 | 196.83 | 281.10 | 12.69 | 0.00 | 54.50 |
Annual Sum or Average | 4111.50 | 0.53 | 634.62 | 9.64 | 33.50 | 3345.50 | 384.46 | 14.74 | 84.50 | 2246.33 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 394.63 | 7.11 | 0.00 | 187.67 | 265.65 | 12.08 | 0.00 | 51.33 | |
Maximum of Months | 403.83 | 0.58 | 0.48 | 900.54 | 12.10 | 32.17 | 360.50 | 500.36 | 16.99 | 32.67 | 307.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-10:09 | 1405.36 | 15.71 | 71.50 | 237.17 | 809.19 | 20.04 | 65.83 | 172.17 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-09:50 | 1204.82 | 13.51 | 46.33 | 239.67 | 678.11 | 18.06 | 45.67 | 185.50 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-10:30 | 1613.91 | 15.71 | 84.67 | 291.17 | 822.24 | 18.17 | 55.83 | 241.17 |
April | 357.50 | 0.52 | 0.48 | 01-APR-09:09 | 1729.90 | 15.56 | 80.33 | 310.83 | 914.00 | 18.05 | 51.83 | 261.00 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-08:09 | 1563.28 | 9.83 | 0.00 | 327.67 | 841.67 | 14.89 | 0.00 | 272.67 |
June | 388.17 | 0.54 | 0.48 | 01-JUN-08:39 | 1307.35 | 9.60 | 0.00 | 310.33 | 600.20 | 14.48 | 0.00 | 253.50 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-08:30 | 1476.74 | 10.55 | 3.67 | 335.00 | 676.79 | 15.36 | 0.00 | 283.83 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-08:09 | 1594.02 | 14.07 | 56.83 | 321.33 | 850.91 | 15.86 | 5.50 | 270.83 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-08:20 | 1334.12 | 15.67 | 78.67 | 293.83 | 694.71 | 18.26 | 51.50 | 240.83 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-11:39 | 1595.32 | 16.35 | 83.33 | 273.67 | 872.01 | 20.44 | 74.00 | 232.83 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-08:39 | 1263.58 | 16.37 | 81.67 | 248.50 | 653.82 | 18.61 | 53.17 | 193.83 |
December | 282.67 | 0.52 | 0.48 | 01-DEC-09:30 | 1458.05 | 17.79 | 81.67 | 243.00 | 757.74 | 19.61 | 52.17 | 186.33 |
Annual Sum or Average | 4111.50 | 0.53 | 1467.47 | 14.00 | 668.67 | 3432.17 | 763.40 | 17.47 | 455.50 | 2794.50 | ||
Minimum of Months | 282.67 | 0.52 | 0.48 | 1204.82 | 9.60 | 0.00 | 237.17 | 600.20 | 14.48 | 0.00 | 172.17 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 1729.90 | 17.79 | 84.67 | 335.00 | 914.00 | 20.44 | 74.00 | 283.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 64378.21 | 107.30 | 09-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4259798.42 | 5109.89 | 04-FEB-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1295925.84 | 2139.00 | 16-MAR-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 51795.50 | 86.33 | 14-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 49419.09 | 110.29 | 15-DEC-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5721317.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4259798.42 | 5109.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10095659.64 | 51025.18 | 04-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20398570.32 | 33584.46 | 16-MAR-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8205987.39 | 15202.29 | 15-DEC-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38700217.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20398570.32 | 51025.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 80873550.97 | 13894.41 | 04-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80873550.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80873550.97 | 13894.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20731040.82 | 6933.67 | 04-FEB-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20731040.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20731040.82 | 6933.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12560987.20 | 2723.35 | 04-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 12560987.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12560987.20 | 2723.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 463070.91 | 567.92 | 25-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 486519.51 | 2455.49 | 04-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334088.80 | 512.66 | 16-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 215792.04 | 140.41 | 27-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 301156.75 | 409.19 | 15-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1800628.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 486519.51 | 2455.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 81796741.66 | 13734.10 | 26-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 79875500.93 | 13657.21 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 32373236.68 | 13691.72 | 16-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9598586.01 | 1390.18 | 27-NOV-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 83643808.55 | 13752.32 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83643808.55 | 13752.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 24809078.96 | 6367.80 | 25-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23634984.57 | 11383.64 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7888245.57 | 2144.64 | 16-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 776108.78 | 434.41 | 13-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 40221874.99 | 6136.56 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97330292.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40221874.99 | 11383.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3118535.64 | 675.64 | 26-JAN-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26675991.77 | 13705.92 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6787511.68 | 1164.68 | 16-MAR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5077419.29 | 636.63 | 21-DEC-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41659458.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26675991.77 | 13705.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 16800688.37 | 1515.44 | 25-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35119535.72 | 11450.56 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4678042.14 | 851.79 | 16-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 797495.07 | 215.22 | 13-NOV-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23908533.75 | 1395.10 | 21-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81304295.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35119535.72 | 11450.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.827070E+11 | 0.695806E+11 | 220028.40 | 30-JAN-04:02 | 136012.37 | 0.52 |
February | 0.00 | 0.00 | 0.923787E+11 | 0.772692E+11 | 214413.64 | 18-FEB-06:02 | 136077.24 | 0.56 |
March | 0.00 | 0.00 | 0.124053E+12 | 0.100749E+12 | 214342.76 | 14-MAR-05:02 | 131505.63 | 0.67 |
April | 0.00 | 0.00 | 0.143514E+12 | 0.116999E+12 | 219039.86 | 13-APR-05:02 | 134353.22 | 0.85 |
May | 0.00 | 0.00 | 0.148984E+12 | 0.113687E+12 | 234527.55 | 27-MAY-05:03 | 134967.00 | 0.73 |
June | 0.00 | 0.00 | 0.169683E+12 | 0.126237E+12 | 232321.33 | 12-JUN-05:02 | 141277.91 | 0.82 |
July | 0.00 | 0.00 | 0.185161E+12 | 0.138205E+12 | 230369.49 | 03-JUL-05:02 | 139412.16 | 0.86 |
August | 0.00 | 0.00 | 0.196353E+12 | 0.146043E+12 | 227906.18 | 24-AUG-05:02 | 135642.10 | 0.88 |
September | 0.00 | 0.00 | 0.157933E+12 | 0.115044E+12 | 227914.37 | 13-SEP-03:02 | 136696.72 | 0.75 |
October | 0.00 | 0.00 | 0.158340E+12 | 0.118483E+12 | 223800.29 | 05-OCT-05:02 | 134995.57 | 0.77 |
November | 0.00 | 0.00 | 0.138278E+12 | 0.106367E+12 | 220162.63 | 30-NOV-06:02 | 141685.59 | 0.73 |
December | 0.00 | 0.00 | 0.114255E+12 | 0.906678E+11 | 228028.14 | 09-DEC-06:02 | 134040.82 | 0.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.171164E+13 | 0.131933E+13 | 0.74 | |||
Minimum of Months | 0.00 | 0.00 | 0.827070E+11 | 0.695806E+11 | 214342.76 | 131505.63 | 0.52 | |
Maximum of Months | 0.00 | 0.00 | 0.196353E+12 | 0.146043E+12 | 234527.55 | 141685.59 | 0.88 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.648133E+12 | 0.531097E+12 | 2088852.44 | 14-JAN-06:03 | 1203873.78 | 0.48 |
February | 0.00 | 0.00 | 0.694686E+12 | 0.566696E+12 | 2163346.55 | 11-FEB-06:03 | 1234545.23 | 0.50 |
March | 0.00 | 0.00 | 0.864053E+12 | 0.694646E+12 | 2055017.93 | 14-MAR-05:02 | 1198960.53 | 0.53 |
April | 0.00 | 0.00 | 0.981284E+12 | 0.789294E+12 | 2130244.29 | 12-APR-05:03 | 1269273.09 | 0.63 |
May | 0.00 | 0.00 | 0.125812E+13 | 0.946841E+12 | 2301144.02 | 27-MAY-05:03 | 1243068.91 | 0.66 |
June | 0.00 | 0.00 | 0.136216E+13 | 0.992580E+12 | 2346423.19 | 19-JUN-03:02 | 1292682.39 | 0.69 |
July | 0.00 | 0.00 | 0.139652E+13 | 0.101921E+13 | 2308251.01 | 03-JUL-03:02 | 1307521.69 | 0.69 |
August | 0.00 | 0.00 | 0.142724E+13 | 0.102834E+13 | 2268836.74 | 28-AUG-03:02 | 1300440.31 | 0.69 |
September | 0.00 | 0.00 | 0.133663E+13 | 0.948590E+12 | 2193439.12 | 21-SEP-03:02 | 1256474.41 | 0.67 |
October | 0.00 | 0.00 | 0.123720E+13 | 0.908856E+12 | 2224523.89 | 02-OCT-05:03 | 1329734.12 | 0.63 |
November | 0.00 | 0.00 | 0.993996E+12 | 0.745857E+12 | 2136602.05 | 30-NOV-06:02 | 1283932.36 | 0.58 |
December | 0.00 | 0.00 | 0.698578E+12 | 0.554916E+12 | 2194691.11 | 09-DEC-06:02 | 1284949.53 | 0.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.128986E+14 | 0.972692E+13 | 0.61 | |||
Minimum of Months | 0.00 | 0.00 | 0.648133E+12 | 0.531097E+12 | 2055017.93 | 1198960.53 | 0.48 | |
Maximum of Months | 0.00 | 0.00 | 0.142724E+13 | 0.102834E+13 | 2346423.19 | 1329734.12 | 0.69 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.597624E+11 | 0.485837E+11 | 207221.93 | 07-JAN-06:03 | 114744.66 | 0.47 |
February | 0.00 | 0.00 | 0.698530E+11 | 0.571004E+11 | 212222.16 | 18-FEB-06:02 | 128330.02 | 0.48 |
March | 0.00 | 0.00 | 0.913385E+11 | 0.733922E+11 | 216540.11 | 14-MAR-05:02 | 126209.51 | 0.53 |
April | 0.00 | 0.00 | 0.109812E+12 | 0.893947E+11 | 217893.91 | 13-APR-05:02 | 132085.23 | 0.63 |
May | 0.00 | 0.00 | 0.144294E+12 | 0.111443E+12 | 241819.48 | 27-MAY-05:03 | 131299.61 | 0.67 |
June | 0.00 | 0.00 | 0.157242E+12 | 0.118126E+12 | 246385.34 | 19-JUN-03:02 | 137074.30 | 0.71 |
July | 0.00 | 0.00 | 0.163392E+12 | 0.123411E+12 | 247293.49 | 03-JUL-03:02 | 142688.36 | 0.71 |
August | 0.00 | 0.00 | 0.161716E+12 | 0.120362E+12 | 224918.28 | 12-AUG-05:03 | 130839.80 | 0.71 |
September | 0.00 | 0.00 | 0.150376E+12 | 0.110503E+12 | 238154.13 | 20-SEP-03:02 | 138691.94 | 0.69 |
October | 0.00 | 0.00 | 0.132705E+12 | 0.100002E+12 | 231469.73 | 02-OCT-05:03 | 138438.19 | 0.64 |
November | 0.00 | 0.00 | 0.101897E+12 | 0.772899E+11 | 226205.63 | 30-NOV-06:02 | 136106.10 | 0.57 |
December | 0.00 | 0.00 | 0.676399E+11 | 0.532920E+11 | 227963.03 | 09-DEC-06:02 | 133170.32 | 0.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.141003E+13 | 0.108290E+13 | 0.61 | |||
Minimum of Months | 0.00 | 0.00 | 0.597624E+11 | 0.485837E+11 | 207221.93 | 114744.66 | 0.47 | |
Maximum of Months | 0.00 | 0.00 | 0.163392E+12 | 0.123411E+12 | 247293.49 | 142688.36 | 0.71 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.677543E+11 | 0.605652E+11 | 143206.88 | 30-JAN-04:02 | 73164.93 | 0.50 |
February | 0.00 | 0.00 | 0.653154E+11 | 0.576369E+11 | 147008.58 | 11-FEB-05:03 | 73327.27 | 0.48 |
March | 0.00 | 0.00 | 0.751919E+11 | 0.650157E+11 | 152030.72 | 06-MAR-04:03 | 71281.88 | 0.51 |
April | 0.00 | 0.00 | 0.781527E+11 | 0.658227E+11 | 151811.05 | 13-APR-03:02 | 75731.54 | 0.57 |
May | 0.00 | 0.00 | 0.100801E+12 | 0.760965E+11 | 169478.65 | 29-MAY-12:30 | 83920.67 | 0.60 |
June | 0.00 | 0.00 | 0.113996E+12 | 0.779716E+11 | 168948.43 | 26-JUN-03:02 | 72222.92 | 0.61 |
July | 0.00 | 0.00 | 0.119320E+12 | 0.809656E+11 | 168160.16 | 09-JUL-16:51 | 78797.43 | 0.58 |
August | 0.00 | 0.00 | 0.130509E+12 | 0.883596E+11 | 171890.90 | 13-AUG-15:52 | 78589.36 | 0.63 |
September | 0.00 | 0.00 | 0.114980E+12 | 0.790353E+11 | 170584.79 | 10-SEP-14:58 | 79569.63 | 0.61 |
October | 0.00 | 0.00 | 0.109624E+12 | 0.801022E+11 | 176801.13 | 30-OCT-02:50 | 74071.15 | 0.61 |
November | 0.00 | 0.00 | 0.936201E+11 | 0.721708E+11 | 158836.81 | 30-NOV-04:03 | 75286.17 | 0.57 |
December | 0.00 | 0.00 | 0.721399E+11 | 0.626901E+11 | 163944.75 | 26-DEC-04:03 | 69604.71 | 0.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.114140E+13 | 0.866432E+12 | 0.57 | |||
Minimum of Months | 0.00 | 0.00 | 0.653154E+11 | 0.576369E+11 | 143206.88 | 69604.71 | 0.48 | |
Maximum of Months | 0.00 | 0.00 | 0.130509E+12 | 0.883596E+11 | 176801.13 | 83920.67 | 0.63 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.564950E+10 | 0.528197E+10 | 2811.67 | 02-JAN-15:00 | 2418.44 | 0.00 |
February | 0.00 | 0.00 | 0.991475E+10 | 0.951296E+10 | 4770.03 | 19-FEB-17:22 | 4472.37 | 0.00 |
March | 0.00 | 0.00 | 0.161881E+11 | 0.156321E+11 | 7806.79 | 31-MAR-23:05 | 7607.43 | 0.00 |
April | 0.00 | 0.00 | 0.208121E+11 | 0.201671E+11 | 8599.55 | 14-APR-16:00 | 8080.51 | 0.00 |
May | 0.00 | 0.00 | 0.676946E+10 | 0.590729E+10 | 4722.35 | 31-MAY-23:10 | 3960.15 | 0.00 |
June | 0.00 | 0.00 | 0.117822E+11 | 0.106464E+11 | 6438.81 | 30-JUN-23:05 | 5833.50 | 0.00 |
July | 0.00 | 0.00 | 0.173352E+11 | 0.161197E+11 | 8434.43 | 31-JUL-23:03 | 7793.92 | 0.00 |
August | 0.00 | 0.00 | 0.223853E+11 | 0.211132E+11 | 8737.39 | 20-AUG-18:25 | 8304.15 | 0.00 |
September | 0.00 | 0.00 | 0.681483E+10 | 0.579742E+10 | 4523.32 | 30-SEP-23:03 | 3972.74 | 0.00 |
October | 0.00 | 0.00 | 0.119558E+11 | 0.109525E+11 | 6246.74 | 31-OCT-23:10 | 5757.86 | 0.00 |
November | 0.00 | 0.00 | 0.160838E+11 | 0.152897E+11 | 6736.72 | 07-NOV-17:00 | 6323.48 | 0.00 |
December | 0.00 | 0.00 | 0.211506E+11 | 0.205678E+11 | 8648.69 | 08-DEC-16:50 | 8135.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.166842E+12 | 0.156988E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.564950E+10 | 0.528197E+10 | 2811.67 | 2418.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.223853E+11 | 0.211132E+11 | 8737.39 | 8304.15 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.481214E+11 | 0.445475E+11 | 26280.05 | 02-JAN-15:00 | 22383.84 | 0.00 |
February | 0.00 | 0.00 | 0.905183E+11 | 0.865264E+11 | 44529.75 | 19-FEB-17:22 | 41564.65 | 0.00 |
March | 0.00 | 0.00 | 0.152543E+12 | 0.146986E+12 | 74945.76 | 31-MAR-23:05 | 72914.83 | 0.00 |
April | 0.00 | 0.00 | 0.198497E+12 | 0.192039E+12 | 82360.78 | 14-APR-16:00 | 77176.93 | 0.00 |
May | 0.00 | 0.00 | 0.632933E+11 | 0.547745E+11 | 45907.33 | 31-MAY-23:10 | 38039.59 | 0.00 |
June | 0.00 | 0.00 | 0.112193E+12 | 0.100878E+12 | 62642.52 | 30-JUN-23:05 | 56479.90 | 0.00 |
July | 0.00 | 0.00 | 0.165548E+12 | 0.153410E+12 | 81554.02 | 31-JUL-23:03 | 75074.00 | 0.00 |
August | 0.00 | 0.00 | 0.214014E+12 | 0.201293E+12 | 83446.21 | 22-AUG-14:20 | 77158.98 | 0.00 |
September | 0.00 | 0.00 | 0.636496E+11 | 0.536003E+11 | 43850.28 | 30-SEP-23:03 | 38192.90 | 0.00 |
October | 0.00 | 0.00 | 0.113241E+12 | 0.103251E+12 | 59182.81 | 31-OCT-23:10 | 54184.46 | 0.00 |
November | 0.00 | 0.00 | 0.151792E+12 | 0.143863E+12 | 64321.08 | 30-NOV-16:40 | 58471.76 | 0.00 |
December | 0.00 | 0.00 | 0.198560E+12 | 0.192726E+12 | 82505.35 | 08-DEC-16:50 | 77380.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157197E+13 | 0.147389E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.481214E+11 | 0.445475E+11 | 26280.05 | 22383.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.214014E+12 | 0.201293E+12 | 83446.21 | 77380.01 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.427271E+10 | 0.392304E+10 | 2690.66 | 02-JAN-15:00 | 2296.94 | 0.00 |
February | 0.00 | 0.00 | 0.876937E+10 | 0.837167E+10 | 4601.29 | 19-FEB-17:22 | 4304.10 | 0.00 |
March | 0.00 | 0.00 | 0.151133E+11 | 0.145587E+11 | 7462.69 | 31-MAR-23:05 | 7260.00 | 0.00 |
April | 0.00 | 0.00 | 0.198988E+11 | 0.192540E+11 | 8338.21 | 14-APR-16:00 | 7819.56 | 0.00 |
May | 0.00 | 0.00 | 0.648269E+10 | 0.562715E+10 | 4620.38 | 31-MAY-23:10 | 3839.55 | 0.00 |
June | 0.00 | 0.00 | 0.113761E+11 | 0.102435E+11 | 6296.41 | 30-JUN-23:05 | 5682.21 | 0.00 |
July | 0.00 | 0.00 | 0.167434E+11 | 0.155295E+11 | 8159.10 | 31-JUL-23:03 | 7514.11 | 0.00 |
August | 0.00 | 0.00 | 0.215229E+11 | 0.202519E+11 | 8532.49 | 06-AUG-15:55 | 8061.22 | 0.00 |
September | 0.00 | 0.00 | 0.651291E+10 | 0.550403E+10 | 4447.77 | 30-SEP-23:03 | 3891.99 | 0.00 |
October | 0.00 | 0.00 | 0.113859E+11 | 0.103873E+11 | 5856.31 | 31-OCT-23:10 | 5355.33 | 0.00 |
November | 0.00 | 0.00 | 0.150414E+11 | 0.142499E+11 | 6496.05 | 07-NOV-17:00 | 6084.07 | 0.00 |
December | 0.00 | 0.00 | 0.194769E+11 | 0.188952E+11 | 8324.80 | 08-DEC-16:50 | 7812.25 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.156597E+12 | 0.146796E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.427271E+10 | 0.392304E+10 | 2690.66 | 2296.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.215229E+11 | 0.202519E+11 | 8532.49 | 8061.22 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.81 | 12945.64 | 26-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 100.05 | 65353.63 | 04-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 26.16 | 41224.74 | 16-MAR-05:20 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 01-APR-00:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.82 | 1251.56 | 27-NOV-06:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 58.58 | 38468.29 | 21-DEC-06:03 |
Annual Sum or Average | 0.00 | 16.53 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 100.05 | 65353.63 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 568386.22 | 2438725.39 | 02-JAN-06:03 | 99.78 | 165997.00 | 23-JAN-00:40 |
February | 622937.34 | 2404692.40 | 11-FEB-06:03 | 73.50 | 298459.43 | 26-FEB-08:13 |
March | 704419.35 | 2827519.27 | 06-MAR-06:02 | 12.81 | 114388.54 | 20-MAR-02:35 |
April | 810539.58 | 2665723.86 | 07-APR-05:04 | 0.00 | 0.00 | 01-APR-00:03 |
May | 921603.96 | 2964743.19 | 31-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 998707.47 | 3362752.41 | 22-JUN-05:04 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1001980.03 | 3024534.98 | 15-JUL-05:04 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1019255.01 | 2964916.75 | 26-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 972527.99 | 3009941.48 | 26-SEP-05:04 | 0.97 | 12540.80 | 02-SEP-21:43 |
October | 910178.98 | 3004493.76 | 03-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 795043.39 | 2868054.58 | 04-NOV-05:03 | 48.09 | 246613.05 | 11-NOV-08:33 |
December | 618409.42 | 2872100.75 | 09-DEC-06:04 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 829638.41 | 19.23 | ||||
Minimum of Months | 568386.22 | 2404692.40 | 0.00 | 0.00 | ||
Maximum of Months | 1019255.01 | 3362752.41 | 99.78 | 298459.43 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 402208.32 | 3966060.51 | 30-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 460904.42 | 4044651.90 | 17-FEB-06:02 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 519437.76 | 4266016.07 | 06-MAR-06:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 591276.51 | 4229572.14 | 13-APR-05:02 | 0.00 | 0.00 | 01-APR-00:03 |
May | 707814.39 | 4250923.55 | 30-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 791988.31 | 4316049.21 | 22-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 783525.08 | 4272382.89 | 24-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 810530.67 | 4280504.65 | 24-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 774718.63 | 4286365.55 | 20-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 708765.68 | 4258231.29 | 06-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 608333.66 | 4160245.37 | 22-NOV-06:02 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 443139.18 | 4255927.68 | 09-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 634336.69 | 0.00 | ||||
Minimum of Months | 402208.32 | 3966060.51 | 0.00 | 0.00 | ||
Maximum of Months | 810530.67 | 4316049.21 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 53024.90 | 151575.88 | 02-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 96600.78 | 181812.15 | 11-FEB-14:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 134745.96 | 220725.35 | 13-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 188842.92 | 280264.16 | 17-APR-15:00 | 0.00 | 0.00 | 01-APR-00:03 |
May | 121622.99 | 207678.81 | 22-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 168844.94 | 215408.95 | 11-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 205975.17 | 285628.02 | 28-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 235863.80 | 302621.88 | 23-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 134222.30 | 188847.70 | 20-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 153206.67 | 216546.35 | 09-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 154635.89 | 226130.61 | 17-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 151537.41 | 244707.38 | 10-DEC-14:56 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 150236.95 | 0.00 | ||||
Minimum of Months | 53024.90 | 151575.88 | 0.00 | 0.00 | ||
Maximum of Months | 235863.80 | 302621.88 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 11607.05 | 37907.16 | 19-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11571.22 | 37811.09 | 01-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11863.01 | 37077.56 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:03 | 10760.61 | 35527.63 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10593.40 | 33959.90 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 10435.31 | 32418.79 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 9573.98 | 31464.40 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 10449.67 | 32179.38 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 10210.05 | 33524.73 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 10643.02 | 35300.55 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 11240.90 | 36794.99 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 11223.48 | 37693.95 | 28-DEC-13:00 |
Annual Sum or Average | 0.00 | 10843.73 | ||||
Minimum of Months | 0.00 | 0.00 | 9573.98 | 31464.40 | ||
Maximum of Months | 0.00 | 0.00 | 11863.01 | 37907.16 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 461063.99 | 5452412.07 | 02-JAN-14:10 | 582.74 | 128971.38 | 25-JAN-06:30 |
February | 524108.67 | 3822695.33 | 10-FEB-15:30 | 703.37 | 145231.83 | 04-FEB-07:40 |
March | 685499.97 | 4746011.01 | 06-MAR-06:04 | 553.27 | 145331.96 | 16-MAR-05:30 |
April | 841852.06 | 5335797.43 | 14-APR-15:00 | 200.36 | 83110.63 | 19-APR-03:50 |
May | 1482401.43 | 5998995.70 | 31-MAY-05:04 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 2283153.86 | 6198973.12 | 08-JUN-05:05 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 2455240.04 | 6269123.01 | 25-JUL-15:50 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 2522593.54 | 6281623.78 | 04-AUG-09:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 2184905.87 | 6362619.60 | 22-SEP-05:04 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1684268.99 | 6753084.56 | 03-OCT-05:04 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 1159133.61 | 5635518.81 | 04-NOV-05:03 | 251.61 | 63564.18 | 12-NOV-07:15 |
December | 614481.16 | 4633915.95 | 09-DEC-06:04 | 583.05 | 124505.32 | 15-DEC-06:30 |
Annual Sum or Average | 1413201.17 | 237.11 | ||||
Minimum of Months | 461063.99 | 3822695.33 | 0.00 | 0.00 | ||
Maximum of Months | 2522593.54 | 6753084.56 | 703.37 | 145331.96 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141831E+11 | 0.87 | 8407.31 | 01-JAN-00:15 | 1.37 |
February | 0.124954E+11 | 0.85 | 8407.31 | 01-FEB-04:10 | 1.38 |
March | 0.138847E+11 | 0.85 | 8407.31 | 01-MAR-04:03 | 1.38 |
April | 0.128312E+11 | 0.81 | 8407.31 | 01-APR-03:03 | 1.38 |
May | 0.138754E+11 | 0.85 | 8407.31 | 01-MAY-02:35 | 1.37 |
June | 0.135711E+11 | 0.86 | 8407.31 | 01-JUN-03:02 | 1.38 |
July | 0.135346E+11 | 0.83 | 8407.31 | 01-JUL-03:02 | 1.38 |
August | 0.146087E+11 | 0.89 | 8407.31 | 01-AUG-03:03 | 1.38 |
September | 0.138018E+11 | 0.87 | 8407.31 | 01-SEP-03:02 | 1.38 |
October | 0.142873E+11 | 0.87 | 8407.31 | 01-OCT-16:05 | 1.36 |
November | 0.138204E+11 | 0.87 | 8407.31 | 01-NOV-03:02 | 1.38 |
December | 0.139801E+11 | 0.85 | 8407.31 | 01-DEC-04:10 | 1.37 |
Annual Sum or Average | 0.164874E+12 | 0.86 | |||
Minimum of Months | 0.124954E+11 | 0.81 | 8407.31 | 1.36 | |
Maximum of Months | 0.146087E+11 | 0.89 | 8407.31 | 1.38 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.598171E+10 | 0.41 | 18262.29 | 02-JAN-06:03 | 1.76 |
February | 0.652978E+10 | 0.46 | 18262.29 | 13-FEB-06:02 | 1.76 |
March | 0.909721E+10 | 0.57 | 18262.29 | 06-MAR-06:02 | 1.76 |
April | 0.103869E+11 | 0.65 | 18262.29 | 03-APR-05:02 | 1.76 |
May | 0.964642E+10 | 0.57 | 18262.29 | 04-MAY-05:02 | 1.76 |
June | 0.107798E+11 | 0.65 | 18262.29 | 03-JUN-05:02 | 1.76 |
July | 0.120457E+11 | 0.69 | 18262.29 | 01-JUL-05:03 | 1.76 |
August | 0.127957E+11 | 0.72 | 18262.29 | 01-AUG-05:02 | 1.76 |
September | 0.891454E+10 | 0.56 | 18262.29 | 02-SEP-05:02 | 1.76 |
October | 0.865751E+10 | 0.55 | 18262.29 | 03-OCT-05:02 | 1.76 |
November | 0.823277E+10 | 0.54 | 18262.29 | 22-NOV-06:02 | 1.76 |
December | 0.776648E+10 | 0.52 | 17240.94 | 11-DEC-06:03 | 1.70 |
Annual Sum or Average | 0.110834E+12 | 0.58 | |||
Minimum of Months | 0.598171E+10 | 0.41 | 17240.94 | 1.70 | |
Maximum of Months | 0.127957E+11 | 0.72 | 18262.29 | 1.76 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.421554E+11 | 0.35 | 167307.40 | 30-JAN-06:03 | 1.75 |
February | 0.427737E+11 | 0.37 | 168574.63 | 16-FEB-06:02 | 1.76 |
March | 0.577760E+11 | 0.42 | 168574.63 | 04-MAR-06:02 | 1.76 |
April | 0.642425E+11 | 0.46 | 168574.63 | 01-APR-05:03 | 1.76 |
May | 0.791846E+11 | 0.51 | 168574.63 | 04-MAY-05:02 | 1.76 |
June | 0.828267E+11 | 0.54 | 168574.63 | 02-JUN-05:03 | 1.76 |
July | 0.829011E+11 | 0.53 | 168574.63 | 03-JUL-03:02 | 1.76 |
August | 0.823919E+11 | 0.53 | 168574.63 | 01-AUG-05:02 | 1.76 |
September | 0.691098E+11 | 0.49 | 168574.63 | 01-SEP-05:02 | 1.76 |
October | 0.617009E+11 | 0.44 | 168574.63 | 02-OCT-05:03 | 1.76 |
November | 0.514415E+11 | 0.40 | 168574.63 | 06-NOV-06:02 | 1.76 |
December | 0.426571E+11 | 0.35 | 168574.63 | 08-DEC-06:03 | 1.76 |
Annual Sum or Average | 0.759161E+12 | 0.45 | |||
Minimum of Months | 0.421554E+11 | 0.35 | 167307.40 | 1.75 | |
Maximum of Months | 0.829011E+11 | 0.54 | 168574.63 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.371990E+10 | 0.32 | 16049.45 | 30-JAN-06:03 | 1.62 |
February | 0.416955E+10 | 0.35 | 17542.00 | 18-FEB-06:02 | 1.72 |
March | 0.591240E+10 | 0.41 | 18178.87 | 14-MAR-05:02 | 1.76 |
April | 0.718757E+10 | 0.47 | 18178.87 | 13-APR-05:02 | 1.76 |
May | 0.931432E+10 | 0.54 | 18178.87 | 03-MAY-05:02 | 1.75 |
June | 0.981484E+10 | 0.58 | 18178.87 | 02-JUN-05:03 | 1.76 |
July | 0.101781E+11 | 0.58 | 18178.87 | 01-JUL-05:03 | 1.76 |
August | 0.980512E+10 | 0.56 | 18178.87 | 01-AUG-05:02 | 1.76 |
September | 0.816892E+10 | 0.52 | 18178.87 | 01-SEP-05:02 | 1.76 |
October | 0.679267E+10 | 0.45 | 18178.87 | 04-OCT-05:03 | 1.76 |
November | 0.524808E+10 | 0.38 | 18178.87 | 06-NOV-06:02 | 1.76 |
December | 0.401547E+10 | 0.33 | 18178.87 | 09-DEC-06:02 | 1.76 |
Annual Sum or Average | 0.843269E+11 | 0.46 | |||
Minimum of Months | 0.371990E+10 | 0.32 | 16049.45 | 1.62 | |
Maximum of Months | 0.101781E+11 | 0.58 | 18178.87 | 1.76 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137480E+10 | 0.91 | 513.29 | 01-JAN-00:05 | 0.91 |
February | 0.124176E+10 | 0.91 | 513.29 | 01-FEB-00:10 | 0.91 |
March | 0.137480E+10 | 0.91 | 513.29 | 01-MAR-00:10 | 0.91 |
April | 0.133045E+10 | 0.91 | 513.29 | 01-APR-00:03 | 0.91 |
May | 0.137480E+10 | 0.91 | 513.29 | 01-MAY-00:10 | 0.91 |
June | 0.133045E+10 | 0.91 | 513.29 | 01-JUN-00:03 | 0.91 |
July | 0.137480E+10 | 0.91 | 513.29 | 01-JUL-00:03 | 0.91 |
August | 0.137480E+10 | 0.91 | 513.29 | 01-AUG-00:03 | 0.91 |
September | 0.133045E+10 | 0.91 | 513.29 | 01-SEP-00:05 | 0.91 |
October | 0.137480E+10 | 0.91 | 513.29 | 01-OCT-00:03 | 0.91 |
November | 0.133045E+10 | 0.91 | 513.29 | 01-NOV-00:10 | 0.91 |
December | 0.137480E+10 | 0.91 | 513.29 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.161872E+11 | 0.91 | |||
Minimum of Months | 0.124176E+10 | 0.91 | 513.29 | 0.91 | |
Maximum of Months | 0.137480E+10 | 0.91 | 513.29 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.130624E+11 | 0.91 | 4876.93 | 01-JAN-00:05 | 0.91 |
February | 0.117983E+11 | 0.91 | 4876.93 | 01-FEB-00:10 | 0.91 |
March | 0.130624E+11 | 0.91 | 4876.93 | 01-MAR-00:10 | 0.91 |
April | 0.126410E+11 | 0.91 | 4876.93 | 01-APR-00:03 | 0.91 |
May | 0.130624E+11 | 0.91 | 4876.93 | 01-MAY-00:10 | 0.91 |
June | 0.126410E+11 | 0.91 | 4876.93 | 01-JUN-00:03 | 0.91 |
July | 0.130624E+11 | 0.91 | 4876.93 | 01-JUL-00:03 | 0.91 |
August | 0.130624E+11 | 0.91 | 4876.93 | 01-AUG-00:03 | 0.91 |
September | 0.126410E+11 | 0.91 | 4876.93 | 01-SEP-00:05 | 0.91 |
October | 0.130624E+11 | 0.91 | 4876.93 | 01-OCT-00:03 | 0.91 |
November | 0.126410E+11 | 0.91 | 4876.93 | 01-NOV-00:10 | 0.91 |
December | 0.130624E+11 | 0.91 | 4876.93 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.153799E+12 | 0.91 | |||
Minimum of Months | 0.117983E+11 | 0.91 | 4876.93 | 0.91 | |
Maximum of Months | 0.130624E+11 | 0.91 | 4876.93 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132634E+10 | 0.91 | 495.20 | 01-JAN-00:05 | 0.91 |
February | 0.119799E+10 | 0.91 | 495.20 | 01-FEB-00:10 | 0.91 |
March | 0.132634E+10 | 0.91 | 495.20 | 01-MAR-00:10 | 0.91 |
April | 0.128356E+10 | 0.91 | 495.20 | 01-APR-00:03 | 0.91 |
May | 0.132634E+10 | 0.91 | 495.20 | 01-MAY-00:10 | 0.91 |
June | 0.128356E+10 | 0.91 | 495.20 | 01-JUN-00:03 | 0.91 |
July | 0.132634E+10 | 0.91 | 495.20 | 01-JUL-00:03 | 0.91 |
August | 0.132634E+10 | 0.91 | 495.20 | 01-AUG-00:03 | 0.91 |
September | 0.128356E+10 | 0.91 | 495.20 | 01-SEP-00:10 | 0.91 |
October | 0.132634E+10 | 0.91 | 495.20 | 01-OCT-00:03 | 0.91 |
November | 0.128356E+10 | 0.91 | 495.20 | 01-NOV-00:10 | 0.91 |
December | 0.132634E+10 | 0.91 | 495.20 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.156166E+11 | 0.91 | |||
Minimum of Months | 0.119799E+10 | 0.91 | 495.20 | 0.91 | |
Maximum of Months | 0.132634E+10 | 0.91 | 495.20 | 0.91 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 541479.51 | 492204.87 | 166.53 | 25-JAN-06:02 | 151.38 | 151.38 | 67.62 | 0.17 |
February | 1263380.61 | 1148412.98 | 407.20 | 04-FEB-06:03 | 370.14 | 370.14 | 44.93 | 0.44 |
March | 307262.70 | 279301.80 | 179.16 | 16-MAR-05:20 | 162.85 | 162.85 | 27.85 | 0.19 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 26.07 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 26.07 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 26.07 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 26.07 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 26.07 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 26.07 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 26.07 | 0.00 |
November | 42933.66 | 39026.69 | 5.42 | 27-NOV-06:20 | 4.93 | 4.93 | 25.80 | 0.01 |
December | 668232.39 | 607423.24 | 160.02 | 21-DEC-06:03 | 145.46 | 145.46 | 24.85 | 0.17 |
Annual Sum or Average | 2823288.87 | 2566369.58 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.85 | 0.00 | |
Maximum of Months | 1263380.61 | 1148412.98 | 407.20 | 370.14 | 370.14 | 67.62 | 0.44 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.951950E+09 | 0.865322E+09 | 26348.44 | 30-JAN-06:03 | 23950.73 | 23950.73 | 8.07 | 128.37 |
February | 0.984718E+09 | 0.895108E+09 | 24683.53 | 17-FEB-06:02 | 22437.33 | 22437.33 | 7.70 | 125.11 |
March | 0.117291E+10 | 0.106617E+10 | 26348.44 | 06-MAR-06:02 | 23950.73 | 23950.73 | 8.16 | 128.37 |
April | 0.118736E+10 | 0.107931E+10 | 26348.44 | 13-APR-05:02 | 23950.73 | 23950.73 | 7.64 | 128.37 |
May | 0.157937E+10 | 0.143565E+10 | 26348.44 | 04-MAY-05:02 | 23950.73 | 23950.73 | 7.56 | 128.37 |
June | 0.182662E+10 | 0.166039E+10 | 26348.44 | 05-JUN-05:02 | 23950.73 | 23950.73 | 7.42 | 128.37 |
July | 0.187509E+10 | 0.170446E+10 | 26348.44 | 03-JUL-05:02 | 23950.73 | 23950.73 | 7.56 | 128.37 |
August | 0.207889E+10 | 0.188971E+10 | 26348.44 | 15-AUG-05:02 | 23950.73 | 23950.73 | 7.27 | 128.37 |
September | 0.216351E+10 | 0.196663E+10 | 26348.44 | 05-SEP-05:02 | 23950.73 | 23950.73 | 8.06 | 128.37 |
October | 0.232297E+10 | 0.211158E+10 | 26348.44 | 02-OCT-05:03 | 23950.73 | 23950.73 | 7.24 | 128.37 |
November | 0.185462E+10 | 0.168585E+10 | 26348.44 | 06-NOV-06:02 | 23950.73 | 23950.73 | 8.15 | 128.37 |
December | 0.114011E+10 | 0.103636E+10 | 26348.44 | 09-DEC-06:02 | 23950.73 | 23950.73 | 7.42 | 128.37 |
Annual Sum or Average | 0.191381E+11 | 0.173965E+11 | ||||||
Minimum of Months | 0.951950E+09 | 0.865322E+09 | 24683.53 | 22437.33 | 22437.33 | 7.24 | 125.11 | |
Maximum of Months | 0.232297E+10 | 0.211158E+10 | 26348.44 | 23950.73 | 23950.73 | 8.16 | 128.37 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.312301E+11 | 0.283882E+11 | 18134.91 | 01-JAN-00:15 | 16484.64 | 16484.64 | 7.82 | 128.37 |
February | 0.293205E+11 | 0.266524E+11 | 18134.91 | 01-FEB-04:15 | 16484.64 | 16484.64 | 8.43 | 128.37 |
March | 0.382431E+11 | 0.347630E+11 | 18134.91 | 01-MAR-04:03 | 16484.64 | 16484.64 | 8.76 | 128.37 |
April | 0.417582E+11 | 0.379582E+11 | 18134.91 | 01-APR-00:03 | 16484.64 | 16484.64 | 7.51 | 128.37 |
May | 0.378595E+11 | 0.344143E+11 | 18134.91 | 01-MAY-00:10 | 16484.64 | 16484.64 | 7.60 | 128.37 |
June | 0.406650E+11 | 0.369645E+11 | 18134.91 | 01-JUN-01:03 | 16484.64 | 16484.64 | 6.97 | 128.37 |
July | 0.446253E+11 | 0.405644E+11 | 18134.91 | 01-JUL-00:10 | 16484.64 | 16484.64 | 6.94 | 128.37 |
August | 0.452219E+11 | 0.411068E+11 | 18134.91 | 01-AUG-00:03 | 16484.64 | 16484.64 | 7.08 | 128.37 |
September | 0.379377E+11 | 0.344854E+11 | 18134.91 | 01-SEP-00:05 | 16484.64 | 16484.64 | 6.96 | 128.37 |
October | 0.396611E+11 | 0.360519E+11 | 18134.91 | 01-OCT-00:03 | 16484.64 | 16484.64 | 7.05 | 128.37 |
November | 0.369580E+11 | 0.335949E+11 | 18134.91 | 01-NOV-03:02 | 16484.64 | 16484.64 | 9.53 | 128.37 |
December | 0.382420E+11 | 0.347620E+11 | 18134.91 | 01-DEC-00:10 | 16484.64 | 16484.64 | 7.35 | 128.37 |
Annual Sum or Average | 0.461722E+12 | 0.419706E+12 | ||||||
Minimum of Months | 0.293205E+11 | 0.266524E+11 | 18134.91 | 16484.64 | 16484.64 | 6.94 | 128.37 | |
Maximum of Months | 0.452219E+11 | 0.411068E+11 | 18134.91 | 16484.64 | 16484.64 | 9.53 | 128.37 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.178642E+10 | 0.162385E+10 | 666.97 | 01-JAN-00:05 | 606.28 | 606.28 | 24.34 | 2.81 |
February | 0.161354E+10 | 0.146671E+10 | 666.97 | 01-FEB-00:10 | 606.28 | 606.28 | 22.86 | 2.81 |
March | 0.178642E+10 | 0.162385E+10 | 666.97 | 01-MAR-00:10 | 606.28 | 606.28 | 26.07 | 2.81 |
April | 0.172879E+10 | 0.157147E+10 | 666.97 | 01-APR-00:03 | 606.28 | 606.28 | 35.41 | 2.81 |
May | 0.178642E+10 | 0.162385E+10 | 666.97 | 01-MAY-00:10 | 606.28 | 606.28 | 26.02 | 2.81 |
June | 0.172879E+10 | 0.157147E+10 | 666.97 | 01-JUN-00:03 | 606.28 | 606.28 | 34.44 | 2.81 |
July | 0.178642E+10 | 0.162385E+10 | 666.97 | 01-JUL-00:03 | 606.28 | 606.28 | 37.60 | 2.81 |
August | 0.178642E+10 | 0.162385E+10 | 666.97 | 01-AUG-00:03 | 606.28 | 606.28 | 42.78 | 2.81 |
September | 0.172879E+10 | 0.157147E+10 | 666.97 | 01-SEP-00:05 | 606.28 | 606.28 | 31.43 | 2.81 |
October | 0.178642E+10 | 0.162385E+10 | 666.97 | 01-OCT-00:03 | 606.28 | 606.28 | 35.47 | 2.81 |
November | 0.172879E+10 | 0.157147E+10 | 666.97 | 01-NOV-00:10 | 606.28 | 606.28 | 32.44 | 2.81 |
December | 0.178642E+10 | 0.162385E+10 | 666.97 | 01-DEC-00:10 | 606.28 | 606.28 | 37.01 | 2.81 |
Annual Sum or Average | 0.210336E+11 | 0.191196E+11 | ||||||
Minimum of Months | 0.161354E+10 | 0.146671E+10 | 666.97 | 606.28 | 606.28 | 22.86 | 2.81 | |
Maximum of Months | 0.178642E+10 | 0.162385E+10 | 666.97 | 606.28 | 606.28 | 42.78 | 2.81 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:05 | 1.79 | 1.79 | 56.35 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:03 | 1.79 | 1.79 | 56.35 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:03 | 1.79 | 1.79 | 57.39 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:03 | 1.79 | 1.79 | 57.01 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:03 | 1.79 | 1.79 | 57.54 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:03 | 1.79 | 1.79 | 57.20 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:03 | 1.79 | 1.79 | 57.94 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:02 | 1.79 | 1.79 | 57.42 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:02 | 1.79 | 1.79 | 56.81 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:05 | 1.79 | 1.79 | 57.66 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:02 | 1.79 | 1.79 | 57.35 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:03 | 1.79 | 1.79 | 57.54 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 56.35 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 57.94 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.400081E+11 | 0.363674E+11 | 45134.45 | 02-JAN-14:00 | 41027.21 | 41027.21 | 29.57 | 150.95 |
February | 0.375238E+11 | 0.341091E+11 | 45072.01 | 10-FEB-15:30 | 40970.46 | 40970.46 | 27.16 | 150.95 |
March | 0.501143E+11 | 0.455539E+11 | 45127.42 | 06-MAR-06:04 | 41020.82 | 41020.82 | 28.62 | 150.95 |
April | 0.549499E+11 | 0.499494E+11 | 45134.45 | 13-APR-12:10 | 41027.21 | 41027.21 | 28.82 | 150.95 |
May | 0.545389E+11 | 0.495758E+11 | 45134.45 | 10-MAY-10:30 | 41027.21 | 41027.21 | 28.84 | 150.95 |
June | 0.645941E+11 | 0.587160E+11 | 45134.45 | 01-JUN-12:50 | 41027.21 | 41027.21 | 28.81 | 150.95 |
July | 0.707310E+11 | 0.642945E+11 | 45134.45 | 03-JUL-03:04 | 41027.21 | 41027.21 | 29.23 | 150.95 |
August | 0.719763E+11 | 0.654265E+11 | 45134.45 | 01-AUG-05:02 | 41027.21 | 41027.21 | 29.69 | 150.95 |
September | 0.611051E+11 | 0.555445E+11 | 45134.45 | 01-SEP-08:20 | 41027.21 | 41027.21 | 28.88 | 150.95 |
October | 0.597025E+11 | 0.542696E+11 | 45134.45 | 02-OCT-03:05 | 41027.21 | 41027.21 | 29.63 | 150.95 |
November | 0.522753E+11 | 0.475182E+11 | 45134.45 | 03-NOV-09:50 | 41027.21 | 41027.21 | 28.86 | 150.95 |
December | 0.494773E+11 | 0.449748E+11 | 45120.68 | 09-DEC-06:04 | 41014.70 | 41014.70 | 28.44 | 150.95 |
Annual Sum or Average | 0.666996E+12 | 0.606300E+12 | ||||||
Minimum of Months | 0.375238E+11 | 0.341091E+11 | 45072.01 | 40970.46 | 40970.46 | 27.16 | 150.95 | |
Maximum of Months | 0.719763E+11 | 0.654265E+11 | 45134.45 | 41027.21 | 41027.21 | 29.69 | 150.95 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 79.40 | 79.40 | 15.81 | 12945.64 | 26-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 46.96 | 46.96 | 100.05 | 65353.63 | 04-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 27.26 | 27.26 | 26.16 | 41224.74 | 16-MAR-05:20 |
April | 0.00 | 0.00 | 01-APR-00:03 | 26.07 | 26.07 | 0.00 | 0.00 | 01-APR-00:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.07 | 26.07 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 26.07 | 26.07 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 26.07 | 26.07 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 26.07 | 26.07 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.07 | 26.07 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.07 | 26.07 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 26.07 | 26.07 | 3.82 | 1251.56 | 27-NOV-06:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 25.54 | 25.54 | 58.58 | 38468.29 | 21-DEC-06:03 |
Annual Sum or Average | 0.00 | 16.53 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.54 | 25.54 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 79.40 | 79.40 | 100.05 | 65353.63 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 568386.22 | 2438725.39 | 02-JAN-06:03 | 12.35 | 7.81 | 99.78 | 165997.00 | 23-JAN-00:40 |
February | 622937.34 | 2404692.40 | 11-FEB-06:03 | 11.59 | 7.12 | 73.50 | 298459.43 | 26-FEB-08:13 |
March | 704419.35 | 2827519.27 | 06-MAR-06:02 | 12.55 | 7.29 | 12.81 | 114388.54 | 20-MAR-02:35 |
April | 810539.58 | 2665723.86 | 07-APR-05:04 | 12.17 | 7.21 | 0.00 | 0.00 | 01-APR-00:03 |
May | 921603.96 | 2964743.19 | 31-MAY-05:02 | 12.47 | 6.96 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 998707.47 | 3362752.41 | 22-JUN-05:04 | 13.23 | 7.53 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1001980.03 | 3024534.98 | 15-JUL-05:04 | 12.42 | 6.79 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1019255.01 | 2964916.75 | 26-AUG-05:02 | 12.47 | 6.96 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 972527.99 | 3009941.48 | 26-SEP-05:04 | 12.81 | 7.21 | 0.97 | 12540.80 | 02-SEP-21:43 |
October | 910178.98 | 3004493.76 | 03-OCT-05:02 | 12.38 | 6.79 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 795043.39 | 2868054.58 | 04-NOV-05:03 | 12.27 | 6.94 | 48.09 | 246613.05 | 11-NOV-08:33 |
December | 618409.42 | 2872100.75 | 09-DEC-06:04 | 12.31 | 6.97 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 829638.41 | 19.23 | ||||||
Minimum of Months | 568386.22 | 2404692.40 | 11.59 | 6.79 | 0.00 | 0.00 | ||
Maximum of Months | 1019255.01 | 3362752.41 | 13.23 | 7.81 | 99.78 | 298459.43 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 402208.32 | 3966060.51 | 30-JAN-06:03 | 14.08 | 7.75 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 460904.42 | 4044651.90 | 17-FEB-06:02 | 14.42 | 7.32 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 519437.76 | 4266016.07 | 06-MAR-06:02 | 14.64 | 7.82 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 591276.51 | 4229572.14 | 13-APR-05:02 | 14.57 | 7.19 | 0.00 | 0.00 | 01-APR-00:03 |
May | 707814.39 | 4250923.55 | 30-MAY-05:02 | 14.61 | 7.65 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 791988.31 | 4316049.21 | 22-JUN-05:02 | 14.73 | 7.44 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 783525.08 | 4272382.89 | 24-JUL-05:02 | 14.65 | 7.70 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 810530.67 | 4280504.65 | 24-AUG-05:02 | 14.67 | 7.41 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 774718.63 | 4286365.55 | 20-SEP-05:02 | 14.68 | 7.60 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 708765.68 | 4258231.29 | 06-OCT-05:02 | 14.63 | 7.64 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 608333.66 | 4160245.37 | 22-NOV-06:02 | 14.44 | 7.25 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 443139.18 | 4255927.68 | 09-DEC-06:02 | 14.62 | 7.05 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 634336.69 | 0.00 | ||||||
Minimum of Months | 402208.32 | 3966060.51 | 14.08 | 7.05 | 0.00 | 0.00 | ||
Maximum of Months | 810530.67 | 4316049.21 | 14.73 | 7.82 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 53024.90 | 151575.88 | 02-JAN-15:00 | 33.66 | 29.42 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 96600.78 | 181812.15 | 11-FEB-14:00 | 36.67 | 30.20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 134745.96 | 220725.35 | 13-MAR-16:00 | 40.51 | 30.64 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 188842.92 | 280264.16 | 17-APR-15:00 | 46.34 | 33.79 | 0.00 | 0.00 | 01-APR-00:03 |
May | 121622.99 | 207678.81 | 22-MAY-13:00 | 39.23 | 34.94 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 168844.94 | 215408.95 | 11-JUN-13:00 | 39.99 | 33.07 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 205975.17 | 285628.02 | 28-JUL-16:00 | 46.86 | 36.34 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 235863.80 | 302621.88 | 23-AUG-13:00 | 48.51 | 35.55 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 134222.30 | 188847.70 | 20-SEP-16:00 | 37.37 | 32.77 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 153206.67 | 216546.35 | 09-OCT-11:00 | 40.10 | 33.08 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 154635.89 | 226130.61 | 17-NOV-15:00 | 41.04 | 31.23 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 151537.41 | 244707.38 | 10-DEC-14:56 | 42.87 | 30.46 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 150236.95 | 0.00 | ||||||
Minimum of Months | 53024.90 | 151575.88 | 33.66 | 29.42 | 0.00 | 0.00 | ||
Maximum of Months | 235863.80 | 302621.88 | 48.51 | 36.34 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.70 | 57.70 | 11607.05 | 37907.16 | 19-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.80 | 56.80 | 11571.22 | 37811.09 | 01-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.77 | 57.77 | 11863.01 | 37077.56 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:03 | 57.39 | 57.39 | 10760.61 | 35527.63 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.07 | 58.07 | 10593.40 | 33959.90 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 57.58 | 57.58 | 10435.31 | 32418.79 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 58.18 | 58.18 | 9573.98 | 31464.40 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 58.16 | 58.16 | 10449.67 | 32179.38 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 57.10 | 57.10 | 10210.05 | 33524.73 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 58.12 | 58.12 | 10643.02 | 35300.55 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.73 | 57.73 | 11240.90 | 36794.99 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.94 | 57.94 | 11223.48 | 37693.95 | 28-DEC-13:00 |
Annual Sum or Average | 0.00 | 10843.73 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.80 | 56.80 | 9573.98 | 31464.40 | ||
Maximum of Months | 0.00 | 0.00 | 58.18 | 58.18 | 11863.01 | 37907.16 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 461063.99 | 5452412.07 | 02-JAN-14:10 | 29.74 | 26.39 | 582.74 | 128971.38 | 25-JAN-06:30 |
February | 524108.67 | 3822695.33 | 10-FEB-15:30 | 27.16 | 24.08 | 703.37 | 145231.83 | 04-FEB-07:40 |
March | 685499.97 | 4746011.01 | 06-MAR-06:04 | 28.62 | 24.59 | 553.27 | 145331.96 | 16-MAR-05:30 |
April | 841852.06 | 5335797.43 | 14-APR-15:00 | 29.56 | 26.28 | 200.36 | 83110.63 | 19-APR-03:50 |
May | 1482401.43 | 5998995.70 | 31-MAY-05:04 | 30.61 | 26.52 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 2283153.86 | 6198973.12 | 08-JUN-05:05 | 30.92 | 27.32 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 2455240.04 | 6269123.01 | 25-JUL-15:50 | 31.04 | 27.85 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 2522593.54 | 6281623.78 | 04-AUG-09:00 | 31.06 | 27.84 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 2184905.87 | 6362619.60 | 22-SEP-05:04 | 31.18 | 27.52 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1684268.99 | 6753084.56 | 03-OCT-05:04 | 31.80 | 27.54 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 1159133.61 | 5635518.81 | 04-NOV-05:03 | 30.03 | 26.15 | 251.61 | 63564.18 | 12-NOV-07:15 |
December | 614481.16 | 4633915.95 | 09-DEC-06:04 | 28.44 | 24.85 | 583.05 | 124505.32 | 15-DEC-06:30 |
Annual Sum or Average | 1413201.17 | 237.11 | ||||||
Minimum of Months | 461063.99 | 3822695.33 | 27.16 | 24.08 | 0.00 | 0.00 | ||
Maximum of Months | 2522593.54 | 6753084.56 | 31.80 | 27.85 | 703.37 | 145331.96 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 64378.21 | 0.00 | 0.827070E+11 | 0.598171E+10 | 0.00 | 0.00 |
February | 4259798.42 | 0.00 | 0.923787E+11 | 0.652978E+10 | 0.00 | 0.00 |
March | 1295925.84 | 0.00 | 0.124053E+12 | 0.909721E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.143514E+12 | 0.103869E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.148984E+12 | 0.964642E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.169683E+12 | 0.107798E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.185161E+12 | 0.120457E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.196353E+12 | 0.127957E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.157933E+12 | 0.891454E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.158340E+12 | 0.865751E+10 | 0.00 | 0.00 |
November | 51795.50 | 0.00 | 0.138278E+12 | 0.823277E+10 | 0.00 | 0.00 |
December | 49419.09 | 0.00 | 0.114255E+12 | 0.776648E+10 | 0.00 | 0.00 |
Annual Sum or Average | 5721317.06 | 0.00 | 0.171164E+13 | 0.110834E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.827070E+11 | 0.598171E+10 | 0.00 | 0.00 |
Maximum of Months | 4259798.42 | 0.00 | 0.196353E+12 | 0.127957E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.648133E+12 | 0.421554E+11 | 0.00 | 0.00 |
February | 0.124261E+09 | 0.00 | 0.694686E+12 | 0.427737E+11 | 0.00 | 0.00 |
March | 20398570.32 | 0.00 | 0.864053E+12 | 0.577760E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.981284E+12 | 0.642425E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.125812E+13 | 0.791846E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.136216E+13 | 0.828267E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.139652E+13 | 0.829011E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.142724E+13 | 0.823919E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.133663E+13 | 0.691098E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.123720E+13 | 0.617009E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.993996E+12 | 0.514415E+11 | 0.00 | 0.00 |
December | 8205987.39 | 0.00 | 0.698578E+12 | 0.426571E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.152866E+09 | 0.00 | 0.128986E+14 | 0.759161E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.648133E+12 | 0.421554E+11 | 0.00 | 0.00 |
Maximum of Months | 0.124261E+09 | 0.00 | 0.142724E+13 | 0.829011E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.126988E+09 | 0.00 | 0.597624E+11 | 0.371990E+10 | 0.00 | 0.00 |
February | 0.165793E+09 | 0.00 | 0.698530E+11 | 0.416955E+10 | 0.00 | 0.00 |
March | 52061124.87 | 0.00 | 0.913385E+11 | 0.591240E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.109812E+12 | 0.718757E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.144294E+12 | 0.931432E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.157242E+12 | 0.981484E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.163392E+12 | 0.101781E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.161716E+12 | 0.980512E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.150376E+12 | 0.816892E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.132705E+12 | 0.679267E+10 | 0.00 | 0.00 |
November | 11387981.90 | 0.00 | 0.101897E+12 | 0.524808E+10 | 0.00 | 0.00 |
December | 0.153153E+09 | 0.00 | 0.676399E+11 | 0.401547E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.509383E+09 | 0.00 | 0.141003E+13 | 0.843269E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.597624E+11 | 0.371990E+10 | 0.00 | 0.00 |
Maximum of Months | 0.165793E+09 | 0.00 | 0.163392E+12 | 0.101781E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.677543E+11 | 0.141831E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.653154E+11 | 0.124954E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.751919E+11 | 0.138847E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.781527E+11 | 0.128312E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.100801E+12 | 0.138754E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.113996E+12 | 0.135711E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.119320E+12 | 0.135346E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.130509E+12 | 0.146087E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.114980E+12 | 0.138018E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.109624E+12 | 0.142873E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.936201E+11 | 0.138204E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.721399E+11 | 0.139801E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.114140E+13 | 0.164874E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.653154E+11 | 0.124954E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.130509E+12 | 0.146087E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.702614E+10 | 0.275144E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.123052E+11 | 0.363225E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.200225E+11 | 0.520923E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.258771E+11 | 0.639547E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.866302E+10 | 0.326837E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.150655E+11 | 0.461374E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.221057E+11 | 0.614528E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.283795E+11 | 0.736891E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.876298E+10 | 0.327860E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.151823E+11 | 0.460127E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.200510E+11 | 0.529760E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.258693E+11 | 0.609351E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.209310E+12 | 0.586557E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.702614E+10 | 0.275144E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.283795E+11 | 0.736891E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.599685E+11 | 0.249094E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.112455E+12 | 0.337345E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.188747E+12 | 0.492665E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.246803E+12 | 0.609466E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.810083E+11 | 0.307774E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.143436E+12 | 0.438839E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.211072E+12 | 0.585859E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.271274E+12 | 0.703224E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.818485E+11 | 0.308399E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.143802E+12 | 0.436233E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.189294E+12 | 0.501429E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.242986E+12 | 0.574888E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.197270E+13 | 0.554522E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.599685E+11 | 0.249094E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.271274E+12 | 0.703224E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.533964E+10 | 0.239328E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.109076E+11 | 0.333625E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.187138E+11 | 0.492684E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.247511E+11 | 0.613588E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.829842E+10 | 0.314207E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.145459E+11 | 0.445337E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.213511E+11 | 0.593409E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.272895E+11 | 0.709291E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.837710E+10 | 0.314775E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.144632E+11 | 0.440367E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.187722E+11 | 0.501431E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.238595E+11 | 0.570887E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.196669E+12 | 0.556893E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.533964E+10 | 0.239328E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.272895E+11 | 0.709291E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.598171E+10 | 0.827070E+11 | 64378.21 | 45765432.81 | 0.263280E+10 | 0.00 | 0.00 | 0.00 |
February | 0.652978E+10 | 0.923787E+11 | 4259798.42 | 0.527971E+09 | 0.341802E+10 | 0.00 | 0.00 | 0.00 |
March | 0.909721E+10 | 0.124053E+12 | 1295925.84 | 86385818.98 | 0.528434E+10 | 0.00 | 0.00 | 0.00 |
April | 0.103869E+11 | 0.143514E+12 | 0.00 | 23284894.82 | 0.103626E+11 | 0.00 | 0.00 | 0.00 |
May | 0.964642E+10 | 0.148984E+12 | 0.00 | 0.00 | 0.264856E+11 | 0.00 | 0.00 | 0.00 |
June | 0.107798E+11 | 0.169683E+12 | 0.00 | 0.00 | 0.463611E+11 | 0.00 | 0.00 | 0.00 |
July | 0.120457E+11 | 0.185161E+12 | 0.00 | 0.00 | 0.534020E+11 | 0.00 | 0.00 | 0.00 |
August | 0.127957E+11 | 0.196353E+12 | 0.00 | 0.00 | 0.552767E+11 | 0.00 | 0.00 | 0.00 |
September | 0.891454E+10 | 0.157933E+12 | 0.00 | 0.00 | 0.403679E+11 | 0.00 | 0.00 | 0.00 |
October | 0.865751E+10 | 0.158340E+12 | 0.00 | 0.00 | 0.315175E+11 | 0.00 | 0.00 | 0.00 |
November | 0.823277E+10 | 0.138278E+12 | 51795.50 | 12618808.61 | 0.192052E+11 | 0.00 | 0.00 | 0.00 |
December | 0.776648E+10 | 0.114255E+12 | 49419.09 | 13799704.66 | 0.534529E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110834E+12 | 0.171164E+13 | 5721317.06 | 0.709825E+09 | 0.299659E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.598171E+10 | 0.827070E+11 | 0.00 | 0.00 | 0.263280E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127957E+11 | 0.196353E+12 | 4259798.42 | 0.527971E+09 | 0.552767E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.421554E+11 | 0.648133E+12 | 0.00 | 0.610315E+09 | 0.284236E+11 | 0.00 | 0.00 | 0.00 |
February | 0.427737E+11 | 0.694686E+12 | 0.124261E+09 | 0.585542E+10 | 0.351682E+11 | 0.00 | 0.00 | 0.00 |
March | 0.577760E+11 | 0.864053E+12 | 20398570.32 | 0.132562E+10 | 0.526357E+11 | 0.00 | 0.00 | 0.00 |
April | 0.642425E+11 | 0.981284E+12 | 0.00 | 0.405398E+09 | 0.976077E+11 | 0.00 | 0.00 | 0.00 |
May | 0.791846E+11 | 0.125812E+13 | 0.00 | 0.00 | 0.254763E+12 | 0.00 | 0.00 | 0.00 |
June | 0.828267E+11 | 0.136216E+13 | 0.00 | 0.00 | 0.409291E+12 | 0.00 | 0.00 | 0.00 |
July | 0.829011E+11 | 0.139652E+13 | 0.00 | 0.00 | 0.473206E+12 | 0.00 | 0.00 | 0.00 |
August | 0.823919E+11 | 0.142724E+13 | 0.00 | 0.00 | 0.463155E+12 | 0.00 | 0.00 | 0.00 |
September | 0.691098E+11 | 0.133663E+13 | 0.00 | 0.00 | 0.382376E+12 | 0.00 | 0.00 | 0.00 |
October | 0.617009E+11 | 0.123720E+13 | 0.00 | 3028321.52 | 0.287527E+12 | 0.00 | 0.00 | 0.00 |
November | 0.514415E+11 | 0.993996E+12 | 0.00 | 0.299109E+09 | 0.172748E+12 | 0.00 | 0.00 | 0.00 |
December | 0.426571E+11 | 0.698578E+12 | 8205987.39 | 0.160150E+09 | 0.533683E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.759161E+12 | 0.128986E+14 | 0.152866E+09 | 0.865905E+10 | 0.271027E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.421554E+11 | 0.648133E+12 | 0.00 | 0.00 | 0.284236E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.829011E+11 | 0.142724E+13 | 0.124261E+09 | 0.585542E+10 | 0.473206E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.371990E+10 | 0.597624E+11 | 0.126988E+09 | 47118950.48 | 0.226259E+10 | 0.00 | 0.00 | 0.00 |
February | 0.416955E+10 | 0.698530E+11 | 0.165793E+09 | 0.553484E+09 | 0.269047E+10 | 0.00 | 0.00 | 0.00 |
March | 0.591240E+10 | 0.913385E+11 | 52061124.87 | 0.117875E+09 | 0.379972E+10 | 0.00 | 0.00 | 0.00 |
April | 0.718757E+10 | 0.109812E+12 | 0.00 | 17076681.25 | 0.819845E+10 | 0.00 | 0.00 | 0.00 |
May | 0.931432E+10 | 0.144294E+12 | 0.00 | 0.00 | 0.242168E+11 | 0.00 | 0.00 | 0.00 |
June | 0.981484E+10 | 0.157242E+12 | 0.00 | 0.00 | 0.404830E+11 | 0.00 | 0.00 | 0.00 |
July | 0.101781E+11 | 0.163392E+12 | 0.00 | 0.00 | 0.461215E+11 | 0.00 | 0.00 | 0.00 |
August | 0.980512E+10 | 0.161716E+12 | 0.00 | 0.00 | 0.455775E+11 | 0.00 | 0.00 | 0.00 |
September | 0.816892E+10 | 0.150376E+12 | 0.00 | 0.00 | 0.377156E+11 | 0.00 | 0.00 | 0.00 |
October | 0.679267E+10 | 0.132705E+12 | 0.00 | 1068015.63 | 0.282661E+11 | 0.00 | 0.00 | 0.00 |
November | 0.524808E+10 | 0.101897E+12 | 11387981.90 | 60840893.70 | 0.162248E+11 | 0.00 | 0.00 | 0.00 |
December | 0.401547E+10 | 0.676399E+11 | 0.153153E+09 | 96348102.98 | 0.431005E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.843269E+11 | 0.141003E+13 | 0.509383E+09 | 0.893811E+09 | 0.259867E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371990E+10 | 0.597624E+11 | 0.00 | 0.00 | 0.226259E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101781E+11 | 0.163392E+12 | 0.165793E+09 | 0.553484E+09 | 0.461215E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141831E+11 | 0.677543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124954E+11 | 0.653154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138847E+11 | 0.751919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128312E+11 | 0.781527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138754E+11 | 0.100801E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135711E+11 | 0.113996E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135346E+11 | 0.119320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146087E+11 | 0.130509E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138018E+11 | 0.114980E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142873E+11 | 0.109624E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138204E+11 | 0.936201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139801E+11 | 0.721399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164874E+12 | 0.114140E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124954E+11 | 0.653154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146087E+11 | 0.130509E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137480E+10 | 0.564950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124176E+10 | 0.991475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137480E+10 | 0.161881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133045E+10 | 0.208121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137480E+10 | 0.676946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133045E+10 | 0.117822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137480E+10 | 0.173352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137480E+10 | 0.223853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133045E+10 | 0.681483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137480E+10 | 0.119558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133045E+10 | 0.160838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137480E+10 | 0.211506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161872E+11 | 0.166842E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124176E+10 | 0.564950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137480E+10 | 0.223853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.130624E+11 | 0.481214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117983E+11 | 0.905183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130624E+11 | 0.152543E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126410E+11 | 0.198497E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130624E+11 | 0.632933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126410E+11 | 0.112193E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.130624E+11 | 0.165548E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130624E+11 | 0.214014E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126410E+11 | 0.636496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130624E+11 | 0.113241E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126410E+11 | 0.151792E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130624E+11 | 0.198560E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153799E+12 | 0.157197E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117983E+11 | 0.481214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130624E+11 | 0.214014E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.132634E+10 | 0.427271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119799E+10 | 0.876937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132634E+10 | 0.151133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128356E+10 | 0.198988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132634E+10 | 0.648269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128356E+10 | 0.113761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132634E+10 | 0.167434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132634E+10 | 0.215229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128356E+10 | 0.651291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132634E+10 | 0.113859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128356E+10 | 0.150414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132634E+10 | 0.194769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156166E+11 | 0.156597E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119799E+10 | 0.427271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132634E+10 | 0.215229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.598171E+10 | 64378.21 | 0.827070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.652978E+10 | 4259798.42 | 0.923787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.909721E+10 | 1295925.84 | 0.124053E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103869E+11 | 0.00 | 0.143514E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.964642E+10 | 0.00 | 0.148984E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107798E+11 | 0.00 | 0.169683E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120457E+11 | 0.00 | 0.185161E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127957E+11 | 0.00 | 0.196353E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.891454E+10 | 0.00 | 0.157933E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.865751E+10 | 0.00 | 0.158340E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.823277E+10 | 51795.50 | 0.138278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.776648E+10 | 49419.09 | 0.114255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110834E+12 | 5721317.06 | 0.171164E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.598171E+10 | 0.00 | 0.827070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127957E+11 | 4259798.42 | 0.196353E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.421554E+11 | 0.00 | 0.648133E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427737E+11 | 0.124261E+09 | 0.694686E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.577760E+11 | 20398570.32 | 0.864053E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.642425E+11 | 0.00 | 0.981284E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.791846E+11 | 0.00 | 0.125812E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.828267E+11 | 0.00 | 0.136216E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.829011E+11 | 0.00 | 0.139652E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.823919E+11 | 0.00 | 0.142724E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.691098E+11 | 0.00 | 0.133663E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.617009E+11 | 0.00 | 0.123720E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.514415E+11 | 0.00 | 0.993996E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.426571E+11 | 8205987.39 | 0.698578E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.759161E+12 | 0.152866E+09 | 0.128986E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.421554E+11 | 0.00 | 0.648133E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.829011E+11 | 0.124261E+09 | 0.142724E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.371990E+10 | 0.126988E+09 | 0.597624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.416955E+10 | 0.165793E+09 | 0.698530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.591240E+10 | 52061124.87 | 0.913385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.718757E+10 | 0.00 | 0.109812E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.931432E+10 | 0.00 | 0.144294E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.981484E+10 | 0.00 | 0.157242E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101781E+11 | 0.00 | 0.163392E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.980512E+10 | 0.00 | 0.161716E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.816892E+10 | 0.00 | 0.150376E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.679267E+10 | 0.00 | 0.132705E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.524808E+10 | 11387981.90 | 0.101897E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.401547E+10 | 0.153153E+09 | 0.676399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.843269E+11 | 0.509383E+09 | 0.141003E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371990E+10 | 0.00 | 0.597624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101781E+11 | 0.165793E+09 | 0.163392E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.141831E+11 | 0.00 | 0.677543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124954E+11 | 0.00 | 0.653154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138847E+11 | 0.00 | 0.751919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128312E+11 | 0.00 | 0.781527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138754E+11 | 0.00 | 0.100801E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135711E+11 | 0.00 | 0.113996E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135346E+11 | 0.00 | 0.119320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146087E+11 | 0.00 | 0.130509E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138018E+11 | 0.00 | 0.114980E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142873E+11 | 0.00 | 0.109624E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138204E+11 | 0.00 | 0.936201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139801E+11 | 0.00 | 0.721399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164874E+12 | 0.00 | 0.114140E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124954E+11 | 0.00 | 0.653154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146087E+11 | 0.00 | 0.130509E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137480E+10 | 0.00 | 0.702614E+10 | 0.00 | 0.137664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124176E+10 | 0.00 | 0.123052E+11 | 0.00 | 0.239050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137480E+10 | 0.00 | 0.200225E+11 | 0.00 | 0.383443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133045E+10 | 0.00 | 0.258771E+11 | 0.00 | 0.506501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137480E+10 | 0.00 | 0.866302E+10 | 0.00 | 0.189357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133045E+10 | 0.00 | 0.150655E+11 | 0.00 | 0.328329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137480E+10 | 0.00 | 0.221057E+11 | 0.00 | 0.477048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137480E+10 | 0.00 | 0.283795E+11 | 0.00 | 0.599411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133045E+10 | 0.00 | 0.876298E+10 | 0.00 | 0.194815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137480E+10 | 0.00 | 0.151823E+11 | 0.00 | 0.322647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133045E+10 | 0.00 | 0.200510E+11 | 0.00 | 0.396715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137480E+10 | 0.00 | 0.258693E+11 | 0.00 | 0.471871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161872E+11 | 0.00 | 0.209310E+12 | 0.00 | 0.424685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124176E+10 | 0.00 | 0.702614E+10 | 0.00 | 0.137664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137480E+10 | 0.00 | 0.283795E+11 | 0.00 | 0.599411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.130624E+11 | 0.00 | 0.599685E+11 | 0.00 | 0.118471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117983E+11 | 0.00 | 0.112455E+12 | 0.00 | 0.219362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130624E+11 | 0.00 | 0.188747E+12 | 0.00 | 0.362042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126410E+11 | 0.00 | 0.246803E+12 | 0.00 | 0.483056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130624E+11 | 0.00 | 0.810083E+11 | 0.00 | 0.177150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126410E+11 | 0.00 | 0.143436E+12 | 0.00 | 0.312429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.130624E+11 | 0.00 | 0.211072E+12 | 0.00 | 0.455235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130624E+11 | 0.00 | 0.271274E+12 | 0.00 | 0.572601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126410E+11 | 0.00 | 0.818485E+11 | 0.00 | 0.181989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130624E+11 | 0.00 | 0.143802E+12 | 0.00 | 0.305609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126410E+11 | 0.00 | 0.189294E+12 | 0.00 | 0.375019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130624E+11 | 0.00 | 0.242986E+12 | 0.00 | 0.444264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153799E+12 | 0.00 | 0.197270E+13 | 0.00 | 0.400723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117983E+11 | 0.00 | 0.599685E+11 | 0.00 | 0.118471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130624E+11 | 0.00 | 0.271274E+12 | 0.00 | 0.572601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.132634E+10 | 0.00 | 0.533964E+10 | 0.00 | 0.106693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119799E+10 | 0.00 | 0.109076E+11 | 0.00 | 0.213827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132634E+10 | 0.00 | 0.187138E+11 | 0.00 | 0.360050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128356E+10 | 0.00 | 0.247511E+11 | 0.00 | 0.485233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132634E+10 | 0.00 | 0.829842E+10 | 0.00 | 0.181572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128356E+10 | 0.00 | 0.145459E+11 | 0.00 | 0.316981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132634E+10 | 0.00 | 0.213511E+11 | 0.00 | 0.460775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132634E+10 | 0.00 | 0.272895E+11 | 0.00 | 0.576657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128356E+10 | 0.00 | 0.837710E+10 | 0.00 | 0.186419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132634E+10 | 0.00 | 0.144632E+11 | 0.00 | 0.307732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128356E+10 | 0.00 | 0.187722E+11 | 0.00 | 0.373076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132634E+10 | 0.00 | 0.238595E+11 | 0.00 | 0.438253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156166E+11 | 0.00 | 0.196669E+12 | 0.00 | 0.400727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119799E+10 | 0.00 | 0.533964E+10 | 0.00 | 0.106693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132634E+10 | 0.00 | 0.272895E+11 | 0.00 | 0.576657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120482E+10 | 0.443381E+10 | 0.00 | 82962902.15 | 28688599.61 | 0.00 | 0.130475E+11 | 0.00 | 0.41 |
February | 0.851567E+09 | 0.475108E+10 | 0.00 | 65629705.93 | 87614982.75 | 0.00 | 0.686337E+10 | 0.00 | 0.40 |
March | 0.386575E+09 | 0.727788E+10 | 0.00 | 58383870.27 | 92370593.47 | 0.00 | 0.826014E+10 | 0.00 | 0.40 |
April | 0.167664E+09 | 0.103756E+11 | 0.00 | 32206741.64 | 0.201142E+09 | 0.00 | 0.216853E+10 | 0.00 | 0.38 |
May | 45278037.77 | 0.259167E+11 | 0.00 | 4073861.81 | 0.538389E+09 | 0.00 | 0.149482E+09 | 0.00 | 0.40 |
June | 0.00 | 0.392828E+11 | 0.00 | 87517.36 | 0.801216E+09 | 0.00 | 251473.37 | 0.00 | 0.41 |
July | 1439004.21 | 0.436127E+11 | 0.00 | 281647.66 | 0.102106E+10 | 0.00 | 8645931.38 | 0.00 | 0.39 |
August | 0.00 | 0.467441E+11 | 0.00 | 169019.38 | 0.982982E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 71929.22 | 0.390734E+11 | 0.00 | 754102.56 | 0.992342E+09 | 0.00 | 2845226.37 | 0.00 | 0.42 |
October | 29924186.62 | 0.300562E+11 | 0.00 | 6856614.96 | 0.650296E+09 | 0.00 | 0.164997E+09 | 0.00 | 0.42 |
November | 0.916735E+09 | 0.190562E+11 | 0.00 | 40512027.37 | 0.388283E+09 | 0.00 | 0.333616E+10 | 0.00 | 0.42 |
December | 0.701096E+09 | 0.627389E+10 | 0.00 | 76633498.46 | 0.148606E+09 | 0.00 | 0.108847E+11 | 0.00 | 0.41 |
Annual Sum or Average | 0.430517E+10 | 0.276854E+12 | 0.00 | 0.368552E+09 | 0.593299E+10 | 0.00 | 0.448866E+11 | 0.00 | 0.41 |
Minimum of Months | 0.00 | 0.443381E+10 | 0.00 | 87517.36 | 28688599.61 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.120482E+10 | 0.467441E+11 | 0.00 | 82962902.15 | 0.102106E+10 | 0.00 | 0.130475E+11 | 0.00 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.202153E+10 | 0.310991E+10 | 0.00 | 49713041.64 | 0.802283E+09 | 0.00 | 0.104914E+11 | 0.00 | 0.36 |
February | 0.144354E+10 | 0.337620E+10 | 0.00 | 35395858.07 | 0.982979E+09 | 0.00 | 0.530345E+10 | 0.00 | 0.37 |
March | 0.152692E+10 | 0.480203E+10 | 0.00 | 37428988.13 | 0.383543E+10 | 0.00 | 0.721903E+10 | 0.00 | 0.43 |
April | 0.115554E+10 | 0.530720E+10 | 0.00 | 14038353.49 | 0.457574E+10 | 0.00 | 0.132778E+10 | 0.00 | 0.46 |
May | 8167702.73 | 0.101233E+11 | 0.00 | 69301.44 | 0.619150E+10 | 0.00 | 708184.54 | 0.00 | 0.39 |
June | 0.00 | 0.132010E+11 | 0.00 | 0.00 | 0.910298E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.130687E+11 | 0.00 | 0.00 | 0.121497E+11 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.148986E+11 | 0.00 | 0.00 | 0.118149E+11 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.140381E+11 | 0.00 | 0.00 | 0.807280E+10 | 0.00 | 0.00 | 0.00 | 0.40 |
October | 8642325.09 | 0.111777E+11 | 0.00 | 1035976.20 | 0.823844E+10 | 0.00 | 5130116.30 | 0.00 | 0.42 |
November | 0.124120E+10 | 0.801952E+10 | 0.00 | 15037512.88 | 0.549889E+10 | 0.00 | 0.160303E+10 | 0.00 | 0.41 |
December | 0.216095E+10 | 0.373111E+10 | 0.00 | 47584813.45 | 0.513905E+10 | 0.00 | 0.940724E+10 | 0.00 | 0.45 |
Annual Sum or Average | 0.956649E+10 | 0.104853E+12 | 0.00 | 0.200304E+09 | 0.764048E+11 | 0.00 | 0.353577E+11 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.310991E+10 | 0.00 | 0.00 | 0.802283E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.216095E+10 | 0.148986E+11 | 0.00 | 49713041.64 | 0.121497E+11 | 0.00 | 0.104914E+11 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154170E+11 | 0.289332E+11 | 0.00 | 0.337375E+09 | 0.676682E+10 | 0.00 | 0.942417E+11 | 0.00 | 0.34 |
February | 0.116294E+11 | 0.304044E+11 | 0.00 | 0.234859E+09 | 0.657538E+10 | 0.00 | 0.446189E+11 | 0.00 | 0.33 |
March | 0.627246E+10 | 0.444831E+11 | 0.00 | 0.273100E+09 | 0.118578E+11 | 0.00 | 0.683678E+11 | 0.00 | 0.35 |
April | 0.296063E+10 | 0.487822E+11 | 0.00 | 0.116738E+09 | 0.166223E+11 | 0.00 | 0.137195E+11 | 0.00 | 0.34 |
May | 43682919.49 | 0.974369E+11 | 0.00 | 1274949.82 | 0.376963E+11 | 0.00 | 3368374.85 | 0.00 | 0.35 |
June | 0.00 | 0.128859E+12 | 0.00 | 0.00 | 0.469970E+11 | 0.00 | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.126560E+12 | 0.00 | 0.00 | 0.619820E+11 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.144135E+12 | 0.00 | 0.00 | 0.500461E+11 | 0.00 | 0.00 | 0.00 | 0.36 |
September | 0.00 | 0.136951E+12 | 0.00 | 0.00 | 0.539336E+11 | 0.00 | 0.00 | 0.00 | 0.36 |
October | 59507304.03 | 0.107944E+12 | 0.00 | 13422246.77 | 0.400587E+11 | 0.00 | 0.101279E+09 | 0.00 | 0.34 |
November | 0.687309E+10 | 0.781705E+11 | 0.00 | 0.106895E+09 | 0.181675E+11 | 0.00 | 0.141812E+11 | 0.00 | 0.33 |
December | 0.106578E+11 | 0.313993E+11 | 0.00 | 0.316737E+09 | 0.170822E+11 | 0.00 | 0.853061E+11 | 0.00 | 0.34 |
Annual Sum or Average | 0.539135E+11 | 0.100406E+13 | 0.00 | 0.140040E+10 | 0.367786E+12 | 0.00 | 0.320540E+12 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.289332E+11 | 0.00 | 0.00 | 0.657538E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.154170E+11 | 0.144135E+12 | 0.00 | 0.337375E+09 | 0.619820E+11 | 0.00 | 0.942417E+11 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.407953E+10 | 0.259132E+10 | 0.00 | 18130105.33 | 0.822356E+09 | 0.00 | 0.541426E+10 | 0.00 | 0.32 |
February | 0.183426E+10 | 0.298194E+10 | 0.00 | 17154965.05 | 0.647156E+09 | 0.00 | 0.302749E+10 | 0.00 | 0.32 |
March | 0.183263E+10 | 0.460191E+10 | 0.00 | 19422853.98 | 0.139984E+10 | 0.00 | 0.475715E+10 | 0.00 | 0.34 |
April | 0.309783E+09 | 0.493543E+10 | 0.00 | 10985992.88 | 0.191548E+10 | 0.00 | 0.131099E+10 | 0.00 | 0.34 |
May | 2852149.62 | 0.959924E+10 | 0.00 | 156281.85 | 0.419239E+10 | 0.00 | 185778.85 | 0.00 | 0.36 |
June | 0.00 | 0.127662E+11 | 0.00 | 0.00 | 0.547544E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.125654E+11 | 0.00 | 0.00 | 0.695770E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.139457E+11 | 0.00 | 0.00 | 0.571818E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
September | 0.00 | 0.132455E+11 | 0.00 | 0.00 | 0.585220E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
October | 3067141.48 | 0.101999E+11 | 0.00 | 1255571.63 | 0.402188E+10 | 0.00 | 9818759.54 | 0.00 | 0.34 |
November | 0.916825E+09 | 0.724527E+10 | 0.00 | 6215304.57 | 0.225454E+10 | 0.00 | 0.869650E+09 | 0.00 | 0.32 |
December | 0.291335E+10 | 0.267251E+10 | 0.00 | 17905942.21 | 0.216459E+10 | 0.00 | 0.527581E+10 | 0.00 | 0.32 |
Annual Sum or Average | 0.118923E+11 | 0.973503E+11 | 0.00 | 91227017.51 | 0.414217E+11 | 0.00 | 0.206654E+11 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.259132E+10 | 0.00 | 0.00 | 0.647156E+09 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.407953E+10 | 0.139457E+11 | 0.00 | 19422853.98 | 0.695770E+10 | 0.00 | 0.541426E+10 | 0.00 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.635231E+09 | 0.397166E+09 | 0.00 | 2826018.20 | 0.105605E+09 | 0.00 | 0.592745E+09 | 0.00 | 0.32 |
February | 0.372381E+09 | 0.476580E+09 | 0.00 | 2794366.28 | 0.124889E+09 | 0.00 | 0.330974E+09 | 0.00 | 0.36 |
March | 0.385728E+09 | 0.719332E+09 | 0.00 | 2931280.27 | 0.476947E+09 | 0.00 | 0.472952E+09 | 0.00 | 0.44 |
April | 0.150372E+09 | 0.861742E+09 | 0.00 | 1739774.09 | 0.553945E+09 | 0.00 | 0.162164E+09 | 0.00 | 0.52 |
May | 1036522.06 | 0.191144E+10 | 0.00 | 9498.72 | 0.706879E+09 | 0.00 | 81649.18 | 0.00 | 0.51 |
June | 0.00 | 0.277420E+10 | 0.00 | 0.00 | 0.990235E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.287369E+10 | 0.00 | 0.00 | 0.129967E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
August | 0.00 | 0.286347E+10 | 0.00 | 0.00 | 0.133448E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.258368E+10 | 0.00 | 0.00 | 0.925468E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 1069902.27 | 0.179120E+10 | 0.00 | 141279.27 | 0.100146E+10 | 0.00 | 674657.27 | 0.00 | 0.48 |
November | 0.201752E+09 | 0.120194E+10 | 0.00 | 1257029.57 | 0.680835E+09 | 0.00 | 0.103736E+09 | 0.00 | 0.44 |
December | 0.474414E+09 | 0.517657E+09 | 0.00 | 3397500.10 | 0.646545E+09 | 0.00 | 0.656111E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.222198E+10 | 0.189721E+11 | 0.00 | 15096746.50 | 0.884696E+10 | 0.00 | 0.231944E+10 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.397166E+09 | 0.00 | 0.00 | 0.105605E+09 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.635231E+09 | 0.287369E+10 | 0.00 | 3397500.10 | 0.133448E+10 | 0.00 | 0.656111E+09 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.401229E+09 | 0.312643E+09 | 0.00 | 3061808.17 | 67753814.98 | 0.00 | 0.650388E+09 | 0.00 | 0.40 |
February | 0.228921E+09 | 0.342295E+09 | 0.00 | 2950362.69 | 89919118.64 | 0.00 | 0.363140E+09 | 0.00 | 0.44 |
March | 0.242112E+09 | 0.533870E+09 | 0.00 | 3166144.14 | 0.343372E+09 | 0.00 | 0.596488E+09 | 0.00 | 0.54 |
April | 0.112002E+09 | 0.670177E+09 | 0.00 | 1346951.48 | 0.392136E+09 | 0.00 | 0.129855E+09 | 0.00 | 0.62 |
May | 716582.25 | 0.146921E+10 | 0.00 | 7918.43 | 0.499438E+09 | 0.00 | 80466.69 | 0.00 | 0.62 |
June | 0.00 | 0.204661E+10 | 0.00 | 0.00 | 0.698958E+09 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.208152E+10 | 0.00 | 0.00 | 0.928209E+09 | 0.00 | 0.00 | 0.00 | 0.68 |
August | 0.00 | 0.196456E+10 | 0.00 | 0.00 | 0.982824E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
September | 0.00 | 0.208680E+10 | 0.00 | 0.00 | 0.600154E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
October | 785373.08 | 0.137216E+10 | 0.00 | 114244.73 | 0.715168E+09 | 0.00 | 435072.43 | 0.00 | 0.57 |
November | 0.141235E+09 | 0.838280E+09 | 0.00 | 1014192.75 | 0.496067E+09 | 0.00 | 91125227.85 | 0.00 | 0.49 |
December | 0.410547E+09 | 0.334257E+09 | 0.00 | 2135669.43 | 0.466459E+09 | 0.00 | 0.411677E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.153755E+10 | 0.140524E+11 | 0.00 | 13797291.82 | 0.628046E+10 | 0.00 | 0.224319E+10 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.312643E+09 | 0.00 | 0.00 | 67753814.98 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.410547E+09 | 0.208680E+10 | 0.00 | 3166144.14 | 0.982824E+09 | 0.00 | 0.650388E+09 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.385960E+09 | 0.708021E+09 | 0.00 | 8922830.00 | 55159725.75 | 0.00 | 0.169766E+10 | 0.00 | 0.53 |
February | 0.260820E+09 | 0.710682E+09 | 0.00 | 7855661.66 | 0.104617E+09 | 0.00 | 0.756967E+09 | 0.00 | 0.53 |
March | 0.339085E+09 | 0.960401E+09 | 0.00 | 5562014.69 | 0.434022E+09 | 0.00 | 0.862011E+09 | 0.00 | 0.57 |
April | 0.148444E+09 | 0.100620E+10 | 0.00 | 2067437.41 | 0.529098E+09 | 0.00 | 0.188208E+09 | 0.00 | 0.57 |
May | 1036861.76 | 0.188529E+10 | 0.00 | 9676.77 | 0.707777E+09 | 0.00 | 81460.39 | 0.00 | 0.51 |
June | 0.00 | 0.261445E+10 | 0.00 | 0.00 | 0.100863E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.278158E+10 | 0.00 | 0.00 | 0.131241E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.306718E+10 | 0.00 | 0.00 | 0.128717E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
September | 0.00 | 0.334564E+10 | 0.00 | 0.00 | 0.734877E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
October | 746755.52 | 0.274840E+10 | 0.00 | 198079.00 | 0.807808E+09 | 0.00 | 1183123.67 | 0.00 | 0.63 |
November | 0.139138E+09 | 0.193049E+10 | 0.00 | 2978591.22 | 0.549102E+09 | 0.00 | 0.257015E+09 | 0.00 | 0.60 |
December | 0.387628E+09 | 0.100641E+10 | 0.00 | 8253736.58 | 0.527718E+09 | 0.00 | 0.138695E+10 | 0.00 | 0.61 |
Annual Sum or Average | 0.166286E+10 | 0.227647E+11 | 0.00 | 35848027.35 | 0.805839E+10 | 0.00 | 0.515008E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.708021E+09 | 0.00 | 0.00 | 55159725.75 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.387628E+09 | 0.334564E+10 | 0.00 | 8922830.00 | 0.131241E+10 | 0.00 | 0.169766E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.321966E+09 | 0.467082E+09 | 0.00 | 4685091.56 | 69672185.06 | 0.00 | 0.103324E+10 | 0.00 | 0.54 |
February | 0.164329E+09 | 0.644660E+09 | 0.00 | 5744905.24 | 58156435.64 | 0.00 | 0.683390E+09 | 0.00 | 0.67 |
March | 0.105473E+09 | 0.121148E+10 | 0.00 | 6700397.05 | 0.223419E+09 | 0.00 | 0.114106E+10 | 0.00 | 0.90 |
April | 53540617.81 | 0.175649E+10 | 0.00 | 5379789.63 | 0.108593E+09 | 0.00 | 0.362599E+09 | 0.00 | 1.08 |
May | 848283.48 | 0.221694E+10 | 0.00 | 31373.73 | 0.421153E+09 | 0.00 | 232199.60 | 0.00 | 0.82 |
June | 0.00 | 0.328621E+10 | 0.00 | 0.00 | 0.560695E+09 | 0.00 | 0.00 | 0.00 | 0.94 |
July | 0.00 | 0.417970E+10 | 0.00 | 0.00 | 0.441350E+09 | 0.00 | 0.00 | 0.00 | 1.05 |
August | 0.00 | 0.480721E+10 | 0.00 | 0.00 | 0.249348E+09 | 0.00 | 0.00 | 0.00 | 1.12 |
September | 0.00 | 0.295001E+10 | 0.00 | 0.00 | 0.542845E+09 | 0.00 | 0.00 | 0.00 | 0.80 |
October | 205271.01 | 0.250575E+10 | 0.00 | 208514.06 | 0.570819E+09 | 0.00 | 1762292.12 | 0.00 | 0.84 |
November | 0.109750E+09 | 0.186765E+10 | 0.00 | 2424670.11 | 0.331853E+09 | 0.00 | 0.245034E+09 | 0.00 | 0.82 |
December | 0.132711E+09 | 0.124053E+10 | 0.00 | 8276885.01 | 0.222316E+09 | 0.00 | 0.148542E+10 | 0.00 | 0.87 |
Annual Sum or Average | 0.888822E+09 | 0.271337E+11 | 0.00 | 33451626.39 | 0.380022E+10 | 0.00 | 0.495273E+10 | 0.00 | 0.87 |
Minimum of Months | 0.00 | 0.467082E+09 | 0.00 | 0.00 | 58156435.64 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.321966E+09 | 0.480721E+10 | 0.00 | 8276885.01 | 0.570819E+09 | 0.00 | 0.148542E+10 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.962858E+10 | 0.336160E+10 | 0.00 | 8501474.33 | 0.107843E+10 | 0.00 | 0.192196E+10 | 0.00 | 0.30 |
February | 0.416652E+10 | 0.401310E+10 | 0.00 | 13320145.16 | 0.915791E+09 | 0.00 | 0.188586E+10 | 0.00 | 0.32 |
March | 0.509658E+10 | 0.643228E+10 | 0.00 | 13022625.82 | 0.153438E+10 | 0.00 | 0.231337E+10 | 0.00 | 0.35 |
April | 0.572363E+09 | 0.774373E+10 | 0.00 | 12146801.28 | 0.207140E+10 | 0.00 | 0.147518E+10 | 0.00 | 0.40 |
May | 5480056.63 | 0.189229E+11 | 0.00 | 170871.82 | 0.425817E+10 | 0.00 | 511437.07 | 0.00 | 0.49 |
June | 0.00 | 0.285216E+11 | 0.00 | 0.00 | 0.474322E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.295250E+11 | 0.00 | 0.00 | 0.625181E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.289570E+11 | 0.00 | 0.00 | 0.547760E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
September | 0.00 | 0.264061E+11 | 0.00 | 0.00 | 0.594964E+10 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 7121039.27 | 0.175812E+11 | 0.00 | 1642658.56 | 0.468430E+10 | 0.00 | 13024744.55 | 0.00 | 0.41 |
November | 0.166068E+10 | 0.114276E+11 | 0.00 | 5791163.53 | 0.232248E+10 | 0.00 | 0.600365E+09 | 0.00 | 0.35 |
December | 0.726482E+10 | 0.401282E+10 | 0.00 | 9731160.88 | 0.224609E+10 | 0.00 | 0.269272E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.284021E+11 | 0.186905E+12 | 0.00 | 64326901.38 | 0.415333E+11 | 0.00 | 0.109030E+11 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.336160E+10 | 0.00 | 0.00 | 0.915791E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.962858E+10 | 0.295250E+11 | 0.00 | 13320145.16 | 0.625181E+10 | 0.00 | 0.269272E+10 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.461094E+10 | 0.306024E+10 | 0.00 | 20274388.67 | 0.614004E+09 | 0.00 | 0.525218E+10 | 0.00 | 0.40 |
February | 0.215806E+10 | 0.346344E+10 | 0.00 | 22197010.42 | 0.585884E+09 | 0.00 | 0.341495E+10 | 0.00 | 0.44 |
March | 0.191667E+10 | 0.588966E+10 | 0.00 | 26503967.25 | 0.100642E+10 | 0.00 | 0.644709E+10 | 0.00 | 0.52 |
April | 0.366022E+09 | 0.769380E+10 | 0.00 | 14612314.79 | 0.131692E+10 | 0.00 | 0.167528E+10 | 0.00 | 0.58 |
May | 3677766.15 | 0.160925E+11 | 0.00 | 183669.83 | 0.271387E+10 | 0.00 | 914468.93 | 0.00 | 0.63 |
June | 0.00 | 0.237731E+11 | 0.00 | 0.00 | 0.296919E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
July | 0.00 | 0.256239E+11 | 0.00 | 0.00 | 0.343757E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
August | 0.00 | 0.243674E+11 | 0.00 | 0.00 | 0.344460E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
September | 0.00 | 0.235704E+11 | 0.00 | 0.00 | 0.337706E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
October | 5676165.47 | 0.159238E+11 | 0.00 | 1628229.58 | 0.301544E+10 | 0.00 | 11254506.19 | 0.00 | 0.55 |
November | 0.988811E+09 | 0.959908E+10 | 0.00 | 7713080.17 | 0.168305E+10 | 0.00 | 0.945469E+09 | 0.00 | 0.46 |
December | 0.408463E+10 | 0.344603E+10 | 0.00 | 13479149.04 | 0.159508E+10 | 0.00 | 0.372357E+10 | 0.00 | 0.38 |
Annual Sum or Average | 0.141345E+11 | 0.162503E+12 | 0.00 | 0.106592E+09 | 0.257591E+11 | 0.00 | 0.214707E+11 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.306024E+10 | 0.00 | 0.00 | 0.585884E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.461094E+10 | 0.256239E+11 | 0.00 | 26503967.25 | 0.344460E+10 | 0.00 | 0.644709E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.394950E+10 | 0.720201E+10 | 0.00 | 84963881.45 | 0.438522E+09 | 0.00 | 0.174200E+11 | 0.00 | 0.57 |
February | 0.235546E+10 | 0.706227E+10 | 0.00 | 75689266.10 | 0.557568E+09 | 0.00 | 0.765613E+10 | 0.00 | 0.55 |
March | 0.273072E+10 | 0.948321E+10 | 0.00 | 46165494.28 | 0.112500E+10 | 0.00 | 0.889814E+10 | 0.00 | 0.53 |
April | 0.478978E+09 | 0.950587E+10 | 0.00 | 16922240.86 | 0.188932E+10 | 0.00 | 0.193691E+10 | 0.00 | 0.47 |
May | 5174696.23 | 0.186130E+11 | 0.00 | 188961.58 | 0.428865E+10 | 0.00 | 820654.48 | 0.00 | 0.48 |
June | 0.00 | 0.265006E+11 | 0.00 | 0.00 | 0.499642E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.283502E+11 | 0.00 | 0.00 | 0.641629E+10 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.316149E+11 | 0.00 | 0.00 | 0.506069E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
September | 0.00 | 0.352163E+11 | 0.00 | 0.00 | 0.417339E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
October | 5642188.77 | 0.296840E+11 | 0.00 | 2712513.72 | 0.263810E+10 | 0.00 | 20534106.23 | 0.00 | 0.61 |
November | 0.834580E+09 | 0.204676E+11 | 0.00 | 28185422.59 | 0.130595E+10 | 0.00 | 0.275824E+10 | 0.00 | 0.58 |
December | 0.301732E+10 | 0.985727E+10 | 0.00 | 66472825.78 | 0.100436E+10 | 0.00 | 0.148876E+11 | 0.00 | 0.57 |
Annual Sum or Average | 0.133774E+11 | 0.233557E+12 | 0.00 | 0.321301E+09 | 0.338943E+11 | 0.00 | 0.535784E+11 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.706227E+10 | 0.00 | 0.00 | 0.438522E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.394950E+10 | 0.352163E+11 | 0.00 | 84963881.45 | 0.641629E+10 | 0.00 | 0.174200E+11 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.582781E+10 | 0.332357E+10 | 0.00 | 17552797.20 | 0.654749E+09 | 0.00 | 0.451709E+10 | 0.00 | 0.42 |
February | 0.273655E+10 | 0.413250E+10 | 0.00 | 24610252.87 | 0.480089E+09 | 0.00 | 0.298266E+10 | 0.00 | 0.48 |
March | 0.287434E+10 | 0.706061E+10 | 0.00 | 26376634.26 | 0.780702E+09 | 0.00 | 0.491977E+10 | 0.00 | 0.58 |
April | 0.306130E+09 | 0.935144E+10 | 0.00 | 24206552.16 | 0.939213E+09 | 0.00 | 0.190480E+10 | 0.00 | 0.66 |
May | 3959176.98 | 0.180939E+11 | 0.00 | 193092.05 | 0.225385E+10 | 0.00 | 966618.52 | 0.00 | 0.68 |
June | 0.00 | 0.244197E+11 | 0.00 | 0.00 | 0.277354E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
July | 0.00 | 0.276564E+11 | 0.00 | 0.00 | 0.322910E+10 | 0.00 | 0.00 | 0.00 | 0.74 |
August | 0.00 | 0.286705E+11 | 0.00 | 0.00 | 0.270200E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
September | 0.00 | 0.245765E+11 | 0.00 | 0.00 | 0.315121E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
October | 4769696.16 | 0.177426E+11 | 0.00 | 1565685.76 | 0.262987E+10 | 0.00 | 13268172.49 | 0.00 | 0.59 |
November | 0.112378E+10 | 0.109491E+11 | 0.00 | 7672463.96 | 0.153613E+10 | 0.00 | 0.831244E+09 | 0.00 | 0.50 |
December | 0.416493E+10 | 0.490614E+10 | 0.00 | 18719279.87 | 0.123104E+10 | 0.00 | 0.471585E+10 | 0.00 | 0.45 |
Annual Sum or Average | 0.170423E+11 | 0.180883E+12 | 0.00 | 0.120897E+09 | 0.223615E+11 | 0.00 | 0.198856E+11 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.332357E+10 | 0.00 | 0.00 | 0.480089E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.582781E+10 | 0.286705E+11 | 0.00 | 26376634.26 | 0.322910E+10 | 0.00 | 0.491977E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.932871E+09 | 0.282900E+09 | 0.00 | 593045.00 | 0.142122E+09 | 26992356.21 | 0.140487E+09 | 0.00 | 0.30 |
February | 0.382938E+09 | 0.365477E+09 | 0.00 | 1145674.99 | 0.119332E+09 | 27856396.43 | 0.147757E+09 | 0.00 | 0.31 |
March | 0.509609E+09 | 0.636989E+09 | 0.00 | 1212308.26 | 0.204265E+09 | 11793016.67 | 0.205852E+09 | 0.00 | 0.35 |
April | 57700848.96 | 0.743330E+09 | 0.00 | 1232897.61 | 0.261942E+09 | 0.00 | 0.144585E+09 | 0.00 | 0.40 |
May | 351970.44 | 0.189010E+10 | 0.00 | 18029.57 | 0.419739E+09 | 0.00 | 28607.46 | 0.00 | 0.48 |
June | 0.00 | 0.285312E+10 | 0.00 | 0.00 | 0.479332E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.298288E+10 | 0.00 | 0.00 | 0.594647E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.283548E+10 | 0.00 | 0.00 | 0.553058E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.260652E+10 | 0.00 | 0.00 | 0.577506E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 396344.61 | 0.162034E+10 | 0.00 | 164326.08 | 0.511350E+09 | 0.00 | 1304792.71 | 0.00 | 0.41 |
November | 0.154606E+09 | 0.104130E+10 | 0.00 | 393518.42 | 0.305818E+09 | 0.00 | 57005567.22 | 0.00 | 0.34 |
December | 0.729780E+09 | 0.345373E+09 | 0.00 | 700411.38 | 0.283380E+09 | 33987787.95 | 0.170866E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.276825E+10 | 0.182038E+11 | 0.00 | 5460211.30 | 0.445249E+10 | 0.100630E+09 | 0.867886E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.282900E+09 | 0.00 | 0.00 | 0.119332E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.932871E+09 | 0.298288E+10 | 0.00 | 1232897.61 | 0.594647E+09 | 33987787.95 | 0.205852E+09 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.443428E+09 | 0.286099E+09 | 0.00 | 1580972.08 | 73739510.38 | 11757606.14 | 0.445230E+09 | 0.00 | 0.39 |
February | 0.199238E+09 | 0.334880E+09 | 0.00 | 2072359.77 | 73698303.40 | 11361621.69 | 0.303111E+09 | 0.00 | 0.44 |
March | 0.165957E+09 | 0.615146E+09 | 0.00 | 2456932.65 | 0.121374E+09 | 5933906.69 | 0.612270E+09 | 0.00 | 0.52 |
April | 31986528.61 | 0.776106E+09 | 0.00 | 1669488.32 | 0.153295E+09 | 0.00 | 0.177030E+09 | 0.00 | 0.59 |
May | 264739.86 | 0.160800E+10 | 0.00 | 18781.86 | 0.281613E+09 | 0.00 | 26500.08 | 0.00 | 0.64 |
June | 0.00 | 0.238504E+10 | 0.00 | 0.00 | 0.318389E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
July | 0.00 | 0.256774E+10 | 0.00 | 0.00 | 0.370118E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
August | 0.00 | 0.241559E+10 | 0.00 | 0.00 | 0.358387E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
September | 0.00 | 0.233024E+10 | 0.00 | 0.00 | 0.354288E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
October | 298116.56 | 0.153666E+10 | 0.00 | 181162.70 | 0.305810E+09 | 0.00 | 1394212.20 | 0.00 | 0.56 |
November | 94737035.07 | 0.927167E+09 | 0.00 | 604484.56 | 0.202881E+09 | 0.00 | 83878821.98 | 0.00 | 0.46 |
December | 0.400709E+09 | 0.307846E+09 | 0.00 | 1027364.38 | 0.201383E+09 | 19283322.20 | 0.300542E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.133662E+10 | 0.160905E+11 | 0.00 | 9611546.32 | 0.281498E+10 | 48336456.72 | 0.192348E+10 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.286099E+09 | 0.00 | 0.00 | 73698303.40 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.443428E+09 | 0.256774E+10 | 0.00 | 2456932.65 | 0.370118E+09 | 19283322.20 | 0.612270E+09 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.385839E+09 | 0.701253E+09 | 0.00 | 7295364.24 | 47681698.80 | 0.00 | 0.171677E+10 | 0.00 | 0.56 |
February | 0.214401E+09 | 0.668803E+09 | 0.00 | 7092282.90 | 64330883.00 | 12617153.72 | 0.752779E+09 | 0.00 | 0.54 |
March | 0.295972E+09 | 0.984516E+09 | 0.00 | 4520355.67 | 0.119192E+09 | 0.00 | 0.869429E+09 | 0.00 | 0.51 |
April | 47394866.59 | 0.942588E+09 | 0.00 | 1844644.24 | 0.213757E+09 | 0.00 | 0.196210E+09 | 0.00 | 0.46 |
May | 352769.39 | 0.184792E+10 | 0.00 | 19875.77 | 0.433143E+09 | 0.00 | 30497.66 | 0.00 | 0.48 |
June | 0.00 | 0.262670E+10 | 0.00 | 0.00 | 0.533394E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.285226E+10 | 0.00 | 0.00 | 0.625125E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.307537E+10 | 0.00 | 0.00 | 0.516723E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
September | 0.00 | 0.344606E+10 | 0.00 | 0.00 | 0.422126E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
October | 383877.85 | 0.281890E+10 | 0.00 | 268785.38 | 0.265394E+09 | 0.00 | 2024944.80 | 0.00 | 0.61 |
November | 70945755.06 | 0.198121E+10 | 0.00 | 2360235.14 | 0.150125E+09 | 0.00 | 0.281574E+09 | 0.00 | 0.58 |
December | 0.300250E+09 | 0.929973E+09 | 0.00 | 6843359.92 | 0.126129E+09 | 0.00 | 0.141898E+10 | 0.00 | 0.56 |
Annual Sum or Average | 0.131554E+10 | 0.228755E+11 | 0.00 | 30244903.26 | 0.351712E+10 | 12617153.72 | 0.523780E+10 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.668803E+09 | 0.00 | 0.00 | 47681698.80 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.385839E+09 | 0.344606E+10 | 0.00 | 7295364.24 | 0.625125E+09 | 12617153.72 | 0.171677E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.680332E+09 | 0.304268E+09 | 0.00 | 1392355.50 | 92270574.63 | 308060.69 | 0.363283E+09 | 0.00 | 0.43 |
February | 0.258335E+09 | 0.383272E+09 | 0.00 | 2340851.64 | 74102383.96 | 16959527.04 | 0.288630E+09 | 0.00 | 0.47 |
March | 0.356889E+09 | 0.723013E+09 | 0.00 | 2709124.78 | 0.102170E+09 | 0.00 | 0.453040E+09 | 0.00 | 0.57 |
April | 27934583.07 | 0.921579E+09 | 0.00 | 2581664.95 | 0.123641E+09 | 0.00 | 0.197965E+09 | 0.00 | 0.65 |
May | 306163.65 | 0.175792E+10 | 0.00 | 18152.49 | 0.265089E+09 | 0.00 | 26855.16 | 0.00 | 0.67 |
June | 0.00 | 0.236495E+10 | 0.00 | 0.00 | 0.354715E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
July | 0.00 | 0.267186E+10 | 0.00 | 0.00 | 0.400280E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
August | 0.00 | 0.273462E+10 | 0.00 | 0.00 | 0.330687E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
September | 0.00 | 0.236606E+10 | 0.00 | 0.00 | 0.384766E+09 | 0.00 | 0.00 | 0.00 | 0.66 |
October | 343270.16 | 0.164224E+10 | 0.00 | 147648.73 | 0.320456E+09 | 0.00 | 1147699.79 | 0.00 | 0.59 |
November | 0.116595E+09 | 0.102884E+10 | 0.00 | 574390.80 | 0.202556E+09 | 0.00 | 84891008.30 | 0.00 | 0.50 |
December | 0.524951E+09 | 0.440145E+09 | 0.00 | 1429688.38 | 0.183952E+09 | 70783.90 | 0.353682E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.196569E+10 | 0.173388E+11 | 0.00 | 11193877.26 | 0.283468E+10 | 17338371.63 | 0.174267E+10 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.304268E+09 | 0.00 | 0.00 | 74102383.96 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.680332E+09 | 0.273462E+10 | 0.00 | 2709124.78 | 0.400280E+09 | 16959527.04 | 0.453040E+09 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.148013E+09 | 0.00 | 5364961.29 | 0.00 | 0.00 | 0.267107E+09 | 0.00 | 0.58 |
February | 0.00 | 0.199216E+09 | 0.00 | 8865292.47 | 0.00 | 0.00 | 0.168021E+09 | 0.00 | 0.58 |
March | 0.00 | 0.337362E+09 | 0.00 | 11471999.13 | 0.00 | 0.00 | 0.158886E+09 | 0.00 | 0.58 |
April | 0.00 | 0.444845E+09 | 0.00 | 5637140.64 | 0.00 | 0.00 | 28462427.50 | 0.00 | 0.58 |
May | 0.00 | 0.729218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.106729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.118278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.123058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.949091E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.867962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.592148E+09 | 0.00 | 6821980.67 | 0.00 | 0.00 | 59603663.66 | 0.00 | 0.58 |
December | 0.00 | 0.330277E+09 | 0.00 | 17043346.20 | 0.00 | 0.00 | 0.169096E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.807877E+10 | 0.00 | 55204720.39 | 0.00 | 0.00 | 0.851177E+09 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.148013E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.123058E+10 | 0.00 | 17043346.20 | 0.00 | 0.00 | 0.267107E+09 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.141686E+10 | 0.00 | 43019051.21 | 0.00 | 0.00 | 0.270989E+10 | 0.00 | 0.58 |
February | 0.00 | 0.197314E+10 | 0.00 | 79173345.48 | 0.00 | 0.00 | 0.168781E+10 | 0.00 | 0.58 |
March | 0.00 | 0.337202E+10 | 0.00 | 0.106528E+09 | 0.00 | 0.00 | 0.159203E+10 | 0.00 | 0.58 |
April | 0.00 | 0.445770E+10 | 0.00 | 53559640.07 | 0.00 | 0.00 | 0.285058E+09 | 0.00 | 0.58 |
May | 0.00 | 0.719707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.106381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.118169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.123050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.937345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.864605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.591424E+10 | 0.00 | 62916802.10 | 0.00 | 0.00 | 0.599333E+09 | 0.00 | 0.58 |
December | 0.00 | 0.330542E+10 | 0.00 | 0.158323E+09 | 0.00 | 0.00 | 0.169531E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.804160E+11 | 0.00 | 0.503520E+09 | 0.00 | 0.00 | 0.856943E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.141686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.123050E+11 | 0.00 | 0.158323E+09 | 0.00 | 0.00 | 0.270989E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.138232E+09 | 0.00 | 3317639.69 | 0.00 | 0.00 | 0.275897E+09 | 0.00 | 0.58 |
February | 0.00 | 0.196466E+09 | 0.00 | 7342439.35 | 0.00 | 0.00 | 0.169885E+09 | 0.00 | 0.58 |
March | 0.00 | 0.336498E+09 | 0.00 | 10304259.32 | 0.00 | 0.00 | 0.159902E+09 | 0.00 | 0.58 |
April | 0.00 | 0.444872E+09 | 0.00 | 5308163.79 | 0.00 | 0.00 | 28662236.32 | 0.00 | 0.58 |
May | 0.00 | 0.722939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.106453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.118154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.122938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.940792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.864030E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.590251E+09 | 0.00 | 6020768.58 | 0.00 | 0.00 | 60371329.56 | 0.00 | 0.58 |
December | 0.00 | 0.329474E+09 | 0.00 | 15210042.63 | 0.00 | 0.00 | 0.170750E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.803901E+10 | 0.00 | 47503313.36 | 0.00 | 0.00 | 0.865468E+09 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.138232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.122938E+10 | 0.00 | 15210042.63 | 0.00 | 0.00 | 0.275897E+09 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:07:12
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.371748E+12 | 0.855329E+09 | 0.00 | 0.248605E+12 | 0.109488E+13 |
February | 0.393894E+12 | 0.724273E+09 | 0.00 | 0.856415E+11 | 0.116494E+13 |
March | 0.542314E+12 | -232398165.0 | 0.00 | -0.253280E+11 | 0.156829E+13 |
April | 0.587441E+12 | -0.121978E+10 | 0.00 | -0.268594E+12 | 0.177644E+13 |
May | 0.558360E+12 | -0.462485E+10 | 0.00 | -0.835344E+12 | 0.197525E+13 |
June | 0.500053E+12 | -0.495382E+10 | 0.00 | -0.122533E+13 | 0.239518E+13 |
July | 0.545945E+12 | -0.431399E+10 | 0.00 | -0.133274E+13 | 0.259436E+13 |
August | 0.598068E+12 | -0.511884E+10 | 0.00 | -0.136446E+13 | 0.273025E+13 |
September | 0.447246E+12 | -0.465777E+10 | 0.00 | -0.121224E+13 | 0.226858E+13 |
October | 0.449440E+12 | -0.402507E+10 | 0.00 | -0.965368E+12 | 0.217337E+13 |
November | 0.329666E+12 | -0.136034E+10 | 0.00 | -0.464475E+12 | 0.183810E+13 |
December | 0.356169E+12 | -271320864.6 | 0.00 | 0.101266E+11 | 0.146529E+13 |
Annual Sum or Average | 0.568034E+13 | -0.291986E+11 | 0.00 | -0.734951E+13 | 0.230449E+14 |
Minimum of Months | 0.329666E+12 | -0.511884E+10 | 0.00 | -0.136446E+13 | 0.109488E+13 |
Maximum of Months | 0.598068E+12 | 0.855329E+09 | 0.00 | 0.248605E+12 | 0.273025E+13 |